Return-Path: <no_reply_servicenow@ihstowers.com>
Delivered-To: loic.noumsi@matech-cameroun.com
Received: from node32-ca.n0c.com
	by node32-ca.n0c.com with LMTP
	id uO95JJWsw2h/YSYA9IX2vw
	(envelope-from <no_reply_servicenow@ihstowers.com>)
	for <loic.noumsi@matech-cameroun.com>; Fri, 12 Sep 2025 05:16:05 +0000
Received: from DU2PR03CU002.outbound.protection.outlook.com (unknown [52.101.65.58])
	by node32-ca.n0c.com (Postfix) with ESMTPS id 0F5728124A
	for <loic.noumsi@matech-cameroun.com>; Fri, 12 Sep 2025 05:16:02 +0000 (UTC)
DMARC-Filter: OpenDMARC Filter v1.4.1 node32-ca.n0c.com 0F5728124A
Authentication-Results: node32-ca.n0c.com; dmarc=pass (p=reject dis=none) header.from=ihstowers.com
Authentication-Results: node32-ca.n0c.com; spf=fail smtp.mailfrom=ihstowers.com
DKIM-Filter: OpenDKIM Filter v2.11.0 node32-ca.n0c.com 0F5728124A
Authentication-Results: node32-ca.n0c.com;
	dkim=pass (1024-bit key; unprotected) header.d=ihstowers.com header.i=@ihstowers.com header.a=rsa-sha256 header.s=selector1 header.b=dHLqST0c
ARC-Seal: i=1; a=rsa-sha256; s=arcselector10001; d=microsoft.com; cv=none;
 b=XKZZgwy9s1E6A0RlgSBntJOjb0bXfI9sn8l20DfxZnP7zTF2S9lcmIYnhB6s0E46X4pSdm0nAK/2eL02/hyTCjRcSNfhHGGufdmvIvkSOr3qYFHtiH0Y3G9h1xT3y3LRnSkq6JJSFBjhCktf63LeidI+diUz6d9Iv6EcXPWKw6O2eGnM7JaaBQNnTZHy6AIliXH8mZ6bKuqYl6JPhZfofn+ohPtPqUafk9zdMvfpBy8Wctzv9LQ7Z+3Hh1dYxxST7yrmTYVnZpLnsg0ZnxHcc/lVgiNBJPnjpjrG+5LIZTWd3G7soon++kehwbrHOfxb0VTW5W1YfSBSAqWuKAtX3g==
ARC-Message-Signature: i=1; a=rsa-sha256; c=relaxed/relaxed; d=microsoft.com;
 s=arcselector10001;
 h=From:Date:Subject:Message-ID:Content-Type:MIME-Version:X-MS-Exchange-AntiSpam-MessageData-ChunkCount:X-MS-Exchange-AntiSpam-MessageData-0:X-MS-Exchange-AntiSpam-MessageData-1;
 bh=UrqUYqNjq6+rEWz8zDyWgCPx3KF7UMNbSc501zechg8=;
 b=FcnTE3jdzkq165O8/JSQrh2EfkfdgomaWDua8I+IUNrpeE/ZYNrxFpc3IMFnXq9syySW4DizejIoqK8ab0ONEuQL0m2xjfztuFJtv+B5d5izoj50XQSsO1nxCDLAWsC2JAn9d83uvjTXG1WVg2mTvG8un3ah1EooyTLK70KAbsgKr8couB8Z0ueodpMNcizMV7zZnefwJfr208Co3LJKcjWH5tiZkEwFUlOruMzC5ElZQZzUUgCyzO3txRYJNHWjT4Ccfows9crB+AfuragZ+iuqttX0wc2fGf4NB885bwapG9ZcqbqHYzRDDhzJYXUWLMzLqelyxcwoXjlm6KrGTg==
ARC-Authentication-Results: i=1; mx.microsoft.com 1; spf=pass
 smtp.mailfrom=ihstowers.com; dmarc=pass action=none
 header.from=ihstowers.com; dkim=pass header.d=ihstowers.com; arc=none
DKIM-Signature: v=1; a=rsa-sha256; c=relaxed/relaxed; d=ihstowers.com;
 s=selector1;
 h=From:Date:Subject:Message-ID:Content-Type:MIME-Version:X-MS-Exchange-SenderADCheck;
 bh=UrqUYqNjq6+rEWz8zDyWgCPx3KF7UMNbSc501zechg8=;
 b=dHLqST0cEOjJNko9vhcsw9iv8qAosUIFHVFdIP0d986cb9acheVGFOLGGH/g2/Ln0JncITNn6jcTKhU0DYShKq6TBkkZQ3FsTIebCn8bgJ/B2pnBpSoOW43NavearIF4TmgQsv3jsPI4IFI941RX2jLZZjR7lUk5gc+U5kbMCAE=
Authentication-Results: dkim=none (message not signed)
 header.d=none;dmarc=none action=none header.from=ihstowers.com;
Received: from VI1PR05MB6079.eurprd05.prod.outlook.com (2603:10a6:803:e9::29)
 by AM9PR05MB7681.eurprd05.prod.outlook.com (2603:10a6:20b:2cf::11) with
 Microsoft SMTP Server (version=TLS1_2,
 cipher=TLS_ECDHE_RSA_WITH_AES_256_GCM_SHA384) id 15.20.9094.22; Fri, 12 Sep
 2025 05:15:53 +0000
Received: from VI1PR05MB6079.eurprd05.prod.outlook.com
 ([fe80::7f92:794a:4a23:aa24]) by VI1PR05MB6079.eurprd05.prod.outlook.com
 ([fe80::7f92:794a:4a23:aa24%6]) with mapi id 15.20.9094.021; Fri, 12 Sep 2025
 05:15:53 +0000
Date: Thu, 11 Sep 2025 22:15:51 -0700 (PDT)
From: IHS ServiceNow Alerts <no_reply_servicenow@ihstowers.com>
Reply-To: IHS ServiceNow Alerts <no_reply_servicenow@ihstowers.com>
To: loic.noumsi@matech-cameroun.com
Message-ID: <1169051893.42.1757654151675@app132153.dub201.service-now.com>
Subject: Attached is the CSV file you requested
Content-Type: multipart/mixed; 
	boundary="----=_Part_41_1366212289.1757654151520"
X-ServiceNow-Source: EmailOutbound
Precedence: bulk
Auto-Submitted: auto-generated
X-ServiceNow-Generated: true
X-ClientProxiedBy: DU7P191CA0020.EURP191.PROD.OUTLOOK.COM
 (2603:10a6:10:54e::30) To VI1PR05MB6079.eurprd05.prod.outlook.com
 (2603:10a6:803:e9::29)
MIME-Version: 1.0
X-MS-PublicTrafficType: Email
X-MS-TrafficTypeDiagnostic: VI1PR05MB6079:EE_|AM9PR05MB7681:EE_
X-MS-Office365-Filtering-Correlation-Id: 7cf2b8ec-1695-40a8-ff4b-08ddf1bb714a
X-LD-Processed: 5dadcdcb-ea32-47fe-84b2-0f6cc63c2e0f,ExtAddr
X-MS-Exchange-AtpMessageProperties: SA
X-MS-Exchange-SenderADCheck: 1
X-MS-Exchange-AntiSpam-Relay: 0
X-Microsoft-Antispam:
	BCL:0;ARA:13230040|366016|1800799024|376014|8096899003|4053099003;
X-Microsoft-Antispam-Message-Info:
	=?utf-8?B?TGFoakJrN0o1M1lMNDN2ZDdyRWx4VVJBSzdGYkhFY2Jqa0dTOEZ3eHpycnlo?=
 =?utf-8?B?THpPY0ZGTTRRL1hhQzg4TFg0SExSREF0TDRjZ0VJZ2R1dEF6TVBsdERpZXdi?=
 =?utf-8?B?NzVlcTAwVUF2aDNDZis3R01nVnBxZldoUmowSnd5eXVFUEFFZGNjVUVnU01x?=
 =?utf-8?B?TFRDZ25GRUlmRFZVbWk4eFo1SzQ0dGRvRFNvdHVFTEg2NW1pOGRBOHE4bWtm?=
 =?utf-8?B?K3l0V0pacGdaZnVqSDJXVkc5ZFZwbnNNUE0rZVlxY3JZc1p2RExOR1dvc3Vv?=
 =?utf-8?B?Q2o0RHhUUHM4YmlpZ294a3NFMEpuWWo3RzlrdXVHbXU5cDJ5VFYrR3J2OEJm?=
 =?utf-8?B?endibURSWTNJajhmQU1hRWptZ1c2NGF1RGt2RG9zbnE3TVdLTmViYkk4OUEw?=
 =?utf-8?B?ZWpsbG5CVVNPcFpuanpOZnYxd09qTDdPdXphRFhnMmFlejhOei81TDBQUnR4?=
 =?utf-8?B?WlJQUjAzbnEyNVcyYTI5dkpqSFZMQUZYNHkyU0MxUmwzV2t3T3dQQUtOTXJt?=
 =?utf-8?B?VzJzWk5xb2Rtd3BKbHAwNDlaY0NkYTdiaTJNdmRycGpyTXUrcEwrRENybldR?=
 =?utf-8?B?STVGaWVRM0tYMktURUlZZlY1Sy85ZW1hTFFjM00vVXNib3REbWFRdnA2dXpp?=
 =?utf-8?B?MDhKWSszdWNnYUwyRi82TERseVd0NlZhU0xyTmNuSEo1citwY1hhV3JEcGtk?=
 =?utf-8?B?MG96ZllYb3lydTdQaW0wdGR4U0tnT1VISUxobnBEVm1QU0tTTnN6VWJ0TUxX?=
 =?utf-8?B?VFJtNTR6eWZUczd1MlVSOCtqK3lUc0MyNVlBc0dxMzc1RmRKQ3RBRitmb0N1?=
 =?utf-8?B?bGFvVlpTZnBXS3RmK0dKUEg1aWJPUmRmNzQ1cmlqVWIwVGZ4Y1ltZ0xQaGZC?=
 =?utf-8?B?elRZQVh1UFFabzVoSmNoRW9YQ241bE5PZU1CU3FFQzdRZ2tEWU54QnJ0Q2Jp?=
 =?utf-8?B?M05UZmZjdWcwMDBoVG5oOWUyYkFGK3BFRW9TbjlxNkhhZ3VkV0NRMUdzM2xw?=
 =?utf-8?B?cGRpdSt4ZU4zQ20xWGhQalFSemhGcGFUUG1KRDFVUFR2dkxsNS8yc1pMd1Rt?=
 =?utf-8?B?Tzd4MEZaRTZWZkJxTGJFWDBtdHdLNWlMamdtSm44a3E2N1NWSzEyVVd3Y21j?=
 =?utf-8?B?N0UwblYvQ3F2RzV4NjNOM2ZOTnozNjZPLzIvaEpuL3FnL0VNZ1NkckFtM1dt?=
 =?utf-8?B?ZEw2MFE5aUxYSWV6M0tFdUNhbXNOa1NjTXlYQUJCN2w5aXV3TWJxRkZIRlVZ?=
 =?utf-8?B?bkU2QzNtUVZoTHcwbUFpK2pFLzlYc2VvQTh4U2dneGp3NzB1S202aVNPaVBR?=
 =?utf-8?B?MndTYU5hZVp3bzQyVU1FVUE1NXpiM3ZtU3d3MTZOckhhWkVUOWtoSTZCWUR4?=
 =?utf-8?B?ZWV0UnNtWGgxSWJkMVVFVXZRL2lQaDhsNURxZUpuMXZPcHZlNVJJYitoRi8y?=
 =?utf-8?B?MlJzZ2ZBbW5OQVNUbE5lTVUwWWVlRVhhbjZXNzNTMnhZRjE5MFFpWlU0R0R6?=
 =?utf-8?B?dzNJTnBIbDh2dEVtengydVVFOHlnUC9Qa1FEZ0JHbjB1bXVvK1RJeHk5dEc2?=
 =?utf-8?B?ZG5LcXNya09TeFRoRzJVNlVjL3ArWEI2MEJvS1lBMEZvZk9aUEt1b3BtNGYx?=
 =?utf-8?B?U0tSN2dkaXI4UUM4RVc5di9YMVhFSFg2WUZrZUxpUnpacEVTTXZpOTI4Z0xU?=
 =?utf-8?B?RzQ3QzBkdlV0WGlhMllpTVhwWnRIV0R6ak5ING5tME9JcVVjZnUrT3lxV25X?=
 =?utf-8?B?UGptS2FjSitvaDZqcnloYUZmOFIvZDdTdHZ3QlB5TGFhd0UyY2x6MDM1NTNq?=
 =?utf-8?B?ZUxmeUp0aWRuSUdPbFo2MEdUN1AvdUFoK0wveEgxa0YwWVY1TzU3WU1YaWR2?=
 =?utf-8?B?TVloT2ZCVlUrem5LdzNJSnFuMlJhd3NremJTdVhXZUJKY2w0dGxkaXFuTkNO?=
 =?utf-8?Q?wZeOWmMeO8U=3D?=
X-Forefront-Antispam-Report:
	CIP:255.255.255.255;CTRY:;LANG:en;SCL:1;SRV:;IPV:NLI;SFV:NSPM;H:VI1PR05MB6079.eurprd05.prod.outlook.com;PTR:;CAT:NONE;SFS:(13230040)(366016)(1800799024)(376014)(8096899003)(4053099003);DIR:OUT;SFP:1101;
X-MS-Exchange-AntiSpam-MessageData-ChunkCount: 1
X-MS-Exchange-AntiSpam-MessageData-0:
	=?utf-8?B?RXc0d1FVd2VKUVZGRDFjWXU0ZjZkdktFSlFLUk9KU0RCYXBCOUNsUE51SUJM?=
 =?utf-8?B?Y0FaVHJkM1dPbjI1TmlGRkNCaFcxNi9EQVMxMFQ2Y08zdDNHRy9ZUlRhaElX?=
 =?utf-8?B?R2pzamJ5M2JpN2RXeFhhL2FqT21Fek5hUGMySnF3amdLWlcwY0ZFMncvWDZP?=
 =?utf-8?B?WXM2Y0h2dFEyTlZpdDdyM1pRU1lwZFNqYkJFL1REUVRjeHdxWDhxUEZUczBT?=
 =?utf-8?B?eTJHNjRSM3p3NkdUVWwrYjZBQ1Y2SHBYRE9nWUpFenl5MjB0ZG1MQzBoUHNO?=
 =?utf-8?B?d3lIMkVSMjE1RHhncWozVm5YLzRxZXhLdXlaMEcvVGUxc1IrSDZZMDR1NzV2?=
 =?utf-8?B?TGdQS2tDTVQ3TnNQRXY1Z3RFeU5pKzBxWHBTVzM4VXFCZ3lJdkY5aDJESHMx?=
 =?utf-8?B?S0lqclhCVHJyeXQvZmtEa1p6c1JhSldBdmtnUXpvY2NraTBwQ3dQQnk2VXNs?=
 =?utf-8?B?TTFSaXNFeGxuYTFFdzRRZUhhYldDQU1Uc0xxVlExdHdncEtpTkc5TlFSSkY0?=
 =?utf-8?B?MWpaWmdvd3Z3N1hXZndBZzhNYTNoLzVqWmxGRWJjSitYVmMwSnZ1MDMrR0tR?=
 =?utf-8?B?eE1WcFNoN0Y5QlJ4TlV5a0QvUUVsRHJnOXd5NUZ3OTdLNDZLVjYybnZlVGlu?=
 =?utf-8?B?eWVXNEpxdmNJdkRvdlV0a0RaSmY2V1NvUkNnYzVNQW9JeUpmNFJBZlpwV2Za?=
 =?utf-8?B?b3dCemphSmtDeXIyWEJqUHBidHhKYjBEUERxUmRvc0NkV2g5VHRIcXN4eE1T?=
 =?utf-8?B?eVNDbVd5elY4ejZlWnJZNmJtRTZDNnlkM2w5cDNoVGwxeFZKbUcrWHFlQ3JK?=
 =?utf-8?B?MlEveXlFQlBkOVB5bDdjUXFVMXdPTTE0MDVwQnVYS2JMRThIZGhoUFF2cGRD?=
 =?utf-8?B?YVVTZy9oSlNrMVNyeXFPalIwdEM3NVJSbXRCRThieGgxQkVkTitmTWlMcTM2?=
 =?utf-8?B?YSs4aGdhWkpCN1htb0cwanlMQ0VhOEQ1b2RCY3ZrOGsrRHk2VEhFNVFqMWYv?=
 =?utf-8?B?ckc0bTc0YzV5Q1JXUDU0cVVQUThOdWhycWpjbGVNRUZ1dGEzTTJNVU1CWjdx?=
 =?utf-8?B?OUlZQ01QZHRCemJBTktudW15TGo4cDh5SjZGNW9ITzl2MHFLaTlVenlZcmVx?=
 =?utf-8?B?R04rOGNXbExmTFRBOVJCUjFnV0tGNHUwL1FKYmwyZ01ZNFhGcmh4R1JyNmVV?=
 =?utf-8?B?Sm54UHRZdGR3MWVRbHhJa3VNWFVhRDdnL1NrREpFMmVNTk1qaXlZSVFVRFBM?=
 =?utf-8?B?MmlpS0hYdEpPOXQwSlZ4RWV6NWk3ZmJwcWRmNitWMEVjNllMVEthNmg1U2dU?=
 =?utf-8?B?OFNUWDVybjJ1Z3VBTGF3OVRSU0JRZ1hkQ2tiZ3VvajhYMzMzNmlyTEYxTzVY?=
 =?utf-8?B?cmEvdFdGZk1CVU9xcjczWFhrTGpwTUFJNGJsZ1ZkcWJ2TUptNFRXOGRPK21s?=
 =?utf-8?B?aTAwRFJ0V2hlU1hZM0E4S0hCUWd2NlF6a1RLZks0L0VkZlpEdEhTaW5ib0V2?=
 =?utf-8?B?TVFRVlNOSHpmRE1ub2tMM2NSWnBDNktySjU2dHFDemhRMHYrTTcrTEhNM0xO?=
 =?utf-8?B?SkNGNWxQYk90OVFJc1JveHBDaWlUd0hJMWNleU1IRWRxaU54cGdZbFBYRHdj?=
 =?utf-8?B?c0lTMVM4YkxGaS8rUFB3NHNhUlpWRjlHdU1UKzlrbVlpVVdYZnNYQ254NzlQ?=
 =?utf-8?B?MzB2OXY3K0E5M2RrZitYekQvQkcwdTh6bmRSdUpqbVJaS2RoNlMyK1Rkb3NI?=
 =?utf-8?B?cUhTSTAwTEtObVVHSW9ZTEV6NGFGY24ybFFGZWlvdmZPT3Z2THVUL1l1OXR5?=
 =?utf-8?B?SXlkbklCSXVkOG9uVnNDSmZrYVQvaUdBNUhoR2FYNFVvcWN2VWNDRzdYQTdm?=
 =?utf-8?B?MnVIMEFDTWNpZmtMbUdjSDNWRlJEblM1TEFyWGJDa2w2UVRxc2xlU0tQWEFn?=
 =?utf-8?B?RnVhb1E2bk1yZDRDM0J1R3NqSFV0K1g1RlRxdlhDYXhTNnFLcG83aXBiVi9I?=
 =?utf-8?B?TXp1M2kzekU4cm9uNEdBV1VRbysrUUlqWTN6YTI4c1lsUFNIbnNZVlg5bCsz?=
 =?utf-8?B?UzRKQVVCS1BIMGppYTg2eFR0dXpVSTNLbFZCMFY0L0Q4TEczMUY4OC8zcmxY?=
 =?utf-8?B?YmdPbnVZWHpUaUd5VWxKbms4eFpEdHpzTFIzUHhKQVBBNHk2cXlTZ0FaeE5o?=
 =?utf-8?Q?/3cMGSDPqED6cTP3EOgBeNE=3D?=
X-OriginatorOrg: ihstowers.com
X-MS-Exchange-CrossTenant-Network-Message-Id: 7cf2b8ec-1695-40a8-ff4b-08ddf1bb714a
X-MS-Exchange-CrossTenant-AuthSource: VI1PR05MB6079.eurprd05.prod.outlook.com
X-MS-Exchange-CrossTenant-AuthAs: Internal
X-MS-Exchange-CrossTenant-OriginalArrivalTime: 12 Sep 2025 05:15:53.0227
 (UTC)
X-MS-Exchange-CrossTenant-FromEntityHeader: Hosted
X-MS-Exchange-CrossTenant-Id: 5dadcdcb-ea32-47fe-84b2-0f6cc63c2e0f
X-MS-Exchange-CrossTenant-MailboxType: HOSTED
X-MS-Exchange-CrossTenant-UserPrincipalName: 4g3hg3Cd9SzngKBKc3BE/KjoctBtbVLo/9Mqw2Tgk1926h0LO8Up3BzXTwIfSzrPtq4hkFXQ8CdlcETto6QOCMjH8ajHQGfqfgNHCZVR9jBMALurleqJwvPoiRx17QwZ
X-MS-Exchange-Transport-CrossTenantHeadersStamped: AM9PR05MB7681

------=_Part_41_1366212289.1757654151520
Content-Type: multipart/alternative; 
	boundary="----=_Part_40_1245965100.1757654151520"

------=_Part_40_1245965100.1757654151520
Content-Transfer-Encoding: 7bit
Content-Type: text/plain; charset=UTF-8

Ref:MSG74026702_JsiOtt3ZqExOe0pNzKG
------=_Part_40_1245965100.1757654151520
Content-Transfer-Encoding: 7bit
Content-Type: text/html; charset=UTF-8

<html><head>
<meta http-equiv="Content-Type" content="text/html; charset=utf-8"></head><body>Ref:MSG74026702_JsiOtt3ZqExOe0pNzKG</body></html>
------=_Part_40_1245965100.1757654151520--

------=_Part_41_1366212289.1757654151520
Content-Type: text/csv; charset=UTF-8; 
	name=sn_customerservice_noc_incident.csv
Content-Transfer-Encoding: quoted-printable
Content-Disposition: attachment; 
	filename=sn_customerservice_noc_incident.csv

"Incident State","Incident Type","Tenant Site ID","Site ID","Number","IHS S=
ite Name","Cascaded Site","Created","Outage Start Time","Outage End Time","=
Short description","SBC Field Engineer","Primary Cause","RCA 1","RCA 2","RC=
A 3","Resolution Comments","Created by","Mean Time to Detect (MTTD)","Opene=
d","IHS Site Maintenance Vendor"
"Resolved","Site Down","T1738","IHS_YND_560","NOCINC0005885229","Cite des n=
ations","","12-09-2025 05:28:47","12-09-2025 05:24:41","12-09-2025 05:32:25=
","Grid outage, site went down before Gen started due to Poor battery backu=
p // Site on Gen","Paul BIBOUM","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, site went down before Gen sta=
rted due to Poor battery backup // Site on Gen","franck.nkomot@matech-camer=
oun.com","248","12-09-2025 05:28:47","MATECH CMR"
"Resolved","Site Down","CTR_331","IHS_YND_253","NOCINC0005884933","Clge-Adv=
antiste","","12-09-2025 03:29:03","12-09-2025 03:24:10","12-09-2025 03:44:5=
3","Grid outage,site went down because gen overload(20kva,260A)// Site on G=
en","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Grid outage,site went down because gen overload(20kva,260A)// Site on G=
en","franck.nkomot@matech-cameroun.com","294","12-09-2025 03:29:03","MATECH=
 CMR"
"Resolved","Site Down","CTR_375","IHS_YND_087","NOCINC0005884524","Camp-Sic=
-Tsinga","","12-09-2025 00:56:17","12-09-2025 00:28:04","12-09-2025 01:40:4=
7","Grid only site/Awaiting Grid return","","Grid Supply","Passive","Grid",=
"National Grid - Grid Outage Issue","Grid only site/Awaiting Grid return","=
christian.fonkou@ihstowers.com","1694","12-09-2025 00:56:17","MATECH CMR"
"Resolved","Site Down","T0401","IHS_YND_205","NOCINC0005884384","Tongolo MT=
N","","12-09-2025 00:04:23","11-09-2025 22:26:13","12-09-2025 00:41:00","Gr=
id fluctuation, Site went down because gen fails to start due to grid bad v=
oltage // He bypasse the Grid and site on Gen","Fabrice Pouakam","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctu=
ation, Site went down because gen fails to start due to grid bad voltage //=
 He bypasse the Grid and site on Gen","franck.nkomot@matech-cameroun.com","=
5891","12-09-2025 00:04:23","MATECH CMR"
"Acknowledge","Site Down","T0773","IHS_YND_262","NOCINC0005884072","Mendong=
3","","11-09-2025 22:50:45","11-09-2025 22:35:36","","Grid only and no spac=
e//Grid return awaited","","","","","","","emmanuel.ghani@ihstowers.com","9=
10","11-09-2025 22:50:45","MATECH CMR"
"Assigned","Site Down","CTR_276","IHS_YND_172","NOCINC0005884066","Tradex-N=
komo","","11-09-2025 22:47:27","11-09-2025 22:45:13","","No power issue sit=
e on grid with U=3D54.2v Lionnel Steeve(655184876) from Huawei is informed"=
,"Albran Byorel","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue site on grid with U=3D54.2v Lio=
nnel Steeve(655184876) from Huawei is informed","franck.nkomot@matech-camer=
oun.com","136","11-09-2025 22:47:27","MATECH CMR"
"Acknowledge","Site Down","","IHS_YND_114","NOCINC0005883857","Kondengui","=
","11-09-2025 22:01:58","11-09-2025 21:59:51","11-09-2025 22:02:04","Cascad=
ed Incident from TTO6107743","Albran Byorel","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid only site/Grid return","stephane.nka=
mwa@ihstowers.com","127","11-09-2025 22:01:58","MATECH CMR"
"Acknowledge","Site Down","CTR_417","IHS_YND_121","NOCINC0005883854","Emomb=
o-Tchad","IHS_YND_114","11-09-2025 22:01:05","11-09-2025 21:59:51","11-09-2=
025 22:02:04","GRID only awaiting grid return","","","","","","","stephane.=
nkamwa@ihstowers.com","75","11-09-2025 22:01:05","MATECH CMR"
"Resolved","Site Down","","IHS_YND_535","NOCINC0005883805","Awae Ewonkan","=
","11-09-2025 21:51:25","11-09-2025 21:40:59","11-09-2025 21:59:40","Cascad=
ed Incident from TTO6107675","Albran Byorel","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to CB of rectifiers fa=
ulty causing by grid fluctuation //  He bypass CB of rectifiers","franck.nk=
omot@matech-cameroun.com","626","11-09-2025 21:51:25","MATECH CMR"
"Resolved","Site Down","CTR_236","IHS_YND_177","NOCINC0005883797","Awae-Yde=
","IHS_YND_535, IHS_YND_171","11-09-2025 21:50:32","11-09-2025 21:40:59","1=
1-09-2025 21:59:40","Site went down due to CB of rectifiers faulty causing =
by grid fluctuation //  He bypass CB of rectifiers","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site went down due to=
 CB of rectifiers faulty causing by grid fluctuation //  He bypass CB of re=
ctifiers","franck.nkomot@matech-cameroun.com","574","11-09-2025 21:50:32","=
MATECH CMR"
"Resolved","Site Down","CTR_168","IHS_YND_171","NOCINC0005883770","Awae Esc=
alier","","11-09-2025 21:44:03","11-09-2025 21:40:59","11-09-2025 21:59:40"=
,"","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Site went down due to CB of rectifiers faulty causing by grid fluc=
tuation //  He bypass CB of rectifiers","franck.nkomot@matech-cameroun.com"=
,"834","11-09-2025 21:44:03","MATECH CMR"
"Resolved","Site Down","CTR_935","IHS_YND_559","NOCINC0005883718","BATA Mok=
olo OCM","","11-09-2025 21:34:38","11-09-2025 20:48:28","12-09-2025 01:37:0=
4","GRID only awaiting grid return","","Grid Supply","Passive","Grid","Nati=
onal Grid - Grid Outage Issue","Grid only site, Grid outage and no space//G=
rid return","stephane.nkamwa@ihstowers.com","2771","11-09-2025 21:34:38","M=
ATECH CMR"
"Resolved","Site Down","CTR_050","IHS_YND_080","NOCINC0005883708","Mini-Fer=
me","","11-09-2025 21:33:35","11-09-2025 20:48:11","12-09-2025 01:38:39","G=
rid only awainting grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","Grid only/ Grid return","stephane.nkamwa@ihstow=
ers.com","2725","11-09-2025 21:33:35","MATECH CMR"
"Acknowledge","Site Down","CTR_409","IHS_YND_090","NOCINC0005883702","BATA-=
Mokolo","","11-09-2025 21:32:23","11-09-2025 20:48:13","12-09-2025 01:26:04=
","grid only awainting grid return","","","","","","","stephane.nkamwa@ihst=
owers.com","2652","11-09-2025 21:32:23","MATECH CMR"
"Acknowledge","Site Down","CTR_017","IHS_YND_083","NOCINC0005883697","H-Pro=
gres","","11-09-2025 21:31:32","11-09-2025 20:47:22","","GRID only awaiting=
 grid return","","","","","","","stephane.nkamwa@ihstowers.com","2651","11-=
09-2025 21:31:32","MATECH CMR"
"Resolved","Site Down","T1278","IHS_YND_802","NOCINC0005883687","NYOM FACE =
MAETUR","","11-09-2025 21:29:31","11-09-2025 21:22:26","11-09-2025 22:23:02=
","Grid outage, site went down because gen stopped by the residents due to =
the noise of the generator. // Gen start manually","Fabrice Pouakam","Site =
Intrusion","Intrusion On Site","Intrusion On Site","Intrusion - Vandalism/S=
abotage","Grid outage, site went down because gen stopped by the residents =
due to the noise of the generator. // Gen start manually","loic.noumsi@mate=
ch-cameroun.com","427","11-09-2025 21:29:31","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_519","IHS_YND_543","NOCINC000588=
3640","Entree Cite Verte","","11-09-2025 21:23:15","11-09-2025 21:13:59","1=
1-09-2025 21:14:59","Active // No power issue, site is on Grid with Ubaie=
=3D53.6V, the technicien tx Brice Tsague(650214096 / Huawei) is informed","=
Paul BIBOUM","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active // No power issue, site is on Grid with Uba=
ie=3D53.6V, the technicien tx Brice Tsague(650214096 / Huawei) is informed"=
,"franck.nkomot@matech-cameroun.com","884","11-09-2025 21:23:15","MATECH CM=
R"
"Resolved","Site Down","T1543","IHS_YND_336","NOCINC0005883619","EKIE","","=
11-09-2025 21:18:36","11-09-2025 21:12:21","11-09-2025 23:17:58","Grid fluc=
tuations, Site went down because gen failed to start due to grid bad voltag=
e and no rcp on site // He made a bridge with a Good phase","Albran Byorel"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid fluctuations, Site went down because gen failed to start due to grid b=
ad voltage and no rcp on site // He made a bridge with a Good phase","loic.=
noumsi@matech-cameroun.com","376","11-09-2025 21:18:36","MATECH CMR"
"Acknowledge","Site Down","CTR_375","IHS_YND_087","NOCINC0005883488","Camp-=
Sic-Tsinga","","11-09-2025 21:02:03","11-09-2025 20:49:38","11-09-2025 22:1=
0:45","GRID only awaiting grid return","","","","","","","stephane.nkamwa@i=
hstowers.com","746","11-09-2025 21:02:03","MATECH CMR"
"Resolved","Site Down","CTR_543","IHS_YND_155","NOCINC0005883472","Obobogo"=
,"","11-09-2025 20:59:03","11-09-2025 20:52:59","11-09-2025 22:56:10","Inco=
rrectly logged ticket","MINKA NICOLAS","Incorrectly Logged Tickets","Error"=
,"Error","Error","Incorrectly logged ticket","franck.nkomot@matech-cameroun=
.com","592","11-09-2025 20:59:03","MATECH CMR"
"Resolved","Warning","T0029","IHS_YND_357","NOCINC0005883399","Sacre Coeur =
Catholic Church","","11-09-2025 20:48:38","","","Our FME was on site and sa=
ys that it is false alarm high temp.","Mboua Thierry","Warning","Warning","=
SYSTEM","Warning - False Alarm","Our FME was on site and says that it is fa=
lse alarm high temp.","loic.noumsi@matech-cameroun.com","2","11-09-2025 20:=
48:38","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_071","IHS_YND_112","NOCINC000588=
3313","Madison","IHS_YND_109","11-09-2025 20:35:57","11-09-2025 20:26:49","=
11-09-2025 21:18:19","NO POWER ISSUE U=3D53.6V SITE ON GRID","MFOUAGUEGUE M=
ATHIEU","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","NO POWER ISSUE U=3D53.6V SITE ON GRID","stephane.nkamwa=
@ihstowers.com","549","11-09-2025 20:35:57","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_068","IHS_YND_109","NOCINC000588=
3302","Mobil-Essos","","11-09-2025 20:34:06","11-09-2025 20:26:49","11-09-2=
025 21:18:19","","Siligap Boris","Cascade Outage","Active","Cascade Active"=
,"Cascade Active","NO POWER ISSUE U=3D53.6V SITE ON GRID","loic.noumsi@mate=
ch-cameroun.com","1474","11-09-2025 20:34:06","MATECH CMR"
"Assigned","Site Down","T0468","IHS_YND_120","NOCINC0005883269","Sapeur Mim=
boman","","11-09-2025 20:28:49","11-09-2025 20:26:37","","FME Antoine repor=
ted Access Issue due to landlord","Mba Lazare Herve","","","","","","loic.n=
oumsi@matech-cameroun.com","134","11-09-2025 20:28:49","MATECH CMR"
"Acknowledge","Site Down","T0291","IHS_YND_147","NOCINC0005883263","Club Fr=
ance","","11-09-2025 20:27:45","11-09-2025 20:21:36",""," Grid outage , no =
space ;  awaiting grid return","","","","","","","adonis.defokoua@ihstowers=
.com","370","11-09-2025 20:27:45","MATECH CMR"
"Acknowledge","Site Down","T0526","IHS_YND_088","NOCINC0005883181","Elobi M=
okolo","","11-09-2025 20:11:08","11-09-2025 20:08:03","","Access issue due =
to insecurity","Mboua Thierry","","","","","","loic.noumsi@matech-cameroun.=
com","186","11-09-2025 20:11:08","MATECH CMR"
"Resolved","Site Down","CTR_002","IHS_YND_010","NOCINC0005883095","CNR","",=
"11-09-2025 20:01:05","11-09-2025 19:58:39","11-09-2025 21:01:49","Site wen=
t down due to insufficiency of rectifiers // Site stabilized","Mboua Thierr=
y","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went d=
own due to insufficiency of rectifiers//Site stabilized","franck.nkomot@mat=
ech-cameroun.com","147","11-09-2025 20:01:05","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_409","IHS_YND_090","NOCINC000588=
3069","BATA-Mokolo","","11-09-2025 19:55:43","11-09-2025 19:48:37","11-09-2=
025 20:01:37","grid only no space awaiting grid return///GRID RETURN","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid only=
 no space awaiting grid return///GRID RETURN","stephane.nkamwa@ihstowers.co=
m","428","11-09-2025 19:55:43","MATECH CMR"
"Resolved","Site Down","T1543","IHS_YND_336","NOCINC0005882984","EKIE","","=
11-09-2025 19:39:52","11-09-2025 19:37:44","11-09-2025 20:13:59","Grid outa=
ge, site went down due to main gen faulty // Grid return","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outa=
ge, site went down due to main gen faulty // Grid return","loic.noumsi@mate=
ch-cameroun.com","129","11-09-2025 19:39:52","MATECH CMR"
"Acknowledge","Site Down","T0120","IHS_YND_031","NOCINC0005882919","Sime Bu=
ilding","","11-09-2025 19:27:54","11-09-2025 19:23:50","","Access issue due=
 to landlord and bad weather","Mboua Thierry","","","","","","loic.noumsi@m=
atech-cameroun.com","245","11-09-2025 19:27:54","MATECH CMR"
"Acknowledge","Site Down","CTR_489","IHS_YND_546","NOCINC0005882899","Biyem=
assi LAC","","11-09-2025 19:21:57","11-09-2025 19:12:49","11-09-2025 19:39:=
18","GRID only no space awaiting grid return","","","","","","","stephane.n=
kamwa@ihstowers.com","550","11-09-2025 19:21:57","MATECH CMR"
"Resolved","Site Down","T2039","IHS_YND_724","NOCINC0005882898","BIYEMASSI =
NIKI","","11-09-2025 19:21:44","11-09-2025 19:15:39","11-09-2025 19:42:55",=
"Grid outage, site went down because Gen failed to start due to Oil pressur=
e sensor faulty // He reset it and started Gen manually","Hyemafo Gildas","=
Equipment Repair","Passive","ACDG Gen","ACDG - Oil Pressure Sensor Faulty",=
"Grid outage, site went down because Gen failed to start due to Oil pressur=
e sensor faulty // He reset it and started Gen manually","loic.noumsi@matec=
h-cameroun.com","366","11-09-2025 19:21:44","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_482","IHS_YND_562","NOCINC000588=
2860","Accacia New","","11-09-2025 19:17:25","11-09-2025 19:12:18","11-09-2=
025 19:39:18","Grid only no space awainting grid return//GRID RETURN","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only=
 no space awainting grid return//GRID RETURN","stephane.nkamwa@ihstowers.co=
m","309","11-09-2025 19:17:25","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_199","IHS_YND_050","NOCINC000588=
2762","Satcom","","11-09-2025 19:03:26","11-09-2025 19:02:07","11-09-2025 1=
9:03:07","No power issue on site, site on Grid Ubaie=3D50,9V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site, site on Grid Ubaie=3D50,9V .The Tx Fme Armand n=
guetsa(691144412) From huawei is informed.","franck.nkomot@matech-cameroun.=
com","80","11-09-2025 19:03:26","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_339","IHS_YND_073","NOCINC000588=
2750","Chapelle-Obili","","11-09-2025 19:01:47","11-09-2025 18:52:59","11-0=
9-2025 19:02:59","Site went down because gen fails to start due to grid bad=
 voltage // Site stabilized","Paul BIBOUM","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","Site went down because gen fails =
to start due to grid bad voltage // Site stabilized","franck.nkomot@matech-=
cameroun.com","528","11-09-2025 19:01:47","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000588=
2739","CNR","","11-09-2025 19:00:50","11-09-2025 18:50:59","11-09-2025 19:1=
2:59","RM IHS reports that Site went down because gen fails to start due to=
 grid bad voltage // Site stabilized","Mboua Thierry","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","RM IHS reports that Si=
te went down because gen fails to start due to grid bad voltage // Site sta=
bilized","franck.nkomot@matech-cameroun.com","592","11-09-2025 19:00:50","M=
ATECH CMR"
"Internal Reconciliation","Site Down","T1121","IHS_YND_690","NOCINC00058826=
52","Ntui administration","","11-09-2025 18:39:25","11-09-2025 18:26:06","1=
1-09-2025 20:29:32","Grid fluctuations, site went down due to grid bad volt=
age (lack of 02 phases) // He bypassed Grid and started Gen manually","Park=
er Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","Grid fluctuations, site went down due to grid bad voltage (lack o=
f 02 phases) // He bypassed Grid and started Gen manually","loic.noumsi@mat=
ech-cameroun.com","800","11-09-2025 18:39:25","MATECH CMR"
"Internal Reconciliation","Site Down","T0058","IHS_YND_293","NOCINC00058826=
10","Nkoabang MTN","","11-09-2025 18:29:44","11-09-2025 18:23:18","11-09-20=
25 20:16:29","Active: No power issue, site is on Grid with Ubaie=3D53.7V, L=
ionel steeve(655184876) from Huawei is informed","Mba Lazare Herve","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: No power issue, site is on Grid with Ubaie=3D53.7V, Lionel ste=
eve(655184876) from Huawei is informed","loic.noumsi@matech-cameroun.com","=
387","11-09-2025 18:29:44","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000588=
2554","CNR","","11-09-2025 18:18:06","11-09-2025 18:14:00","11-09-2025 18:4=
4:00","RM IHS reports that Site went down because gen fails to start due to=
 grid bad voltage // Site stabilized","Mboua Thierry","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","RM IHS reports that Si=
te went down because gen fails to start due to grid bad voltage // Site sta=
bilized","franck.nkomot@matech-cameroun.com","247","11-09-2025 18:18:06","M=
ATECH CMR"
"Resolved","Warning","CTR_211","IHS_YND_248","NOCINC0005882542","Biteng",""=
,"11-09-2025 18:17:00","","","HYBRID GEN // Gen start automatically","Mba L=
azare Herve","Warning","Warning","POWER","Warning - Site on Battery","HYBRI=
D GEN // Gen start automatically","loic.noumsi@matech-cameroun.com","2","11=
-09-2025 18:17:00","MATECH CMR"
"Acknowledge","Site Down","T1568","IHS_YND_084","NOCINC0005882502","Briquet=
terie","","11-09-2025 18:08:10","11-09-2025 17:47:01","","Grid outage ; no =
space for MDG / awaiting grid return","","","","","","","adonis.defokoua@ih=
stowers.com","1271","11-09-2025 18:08:10","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000588=
2486","CNR","","11-09-2025 18:05:15","11-09-2025 18:03:02","11-09-2025 18:1=
0:02","RM IHS reports that Site went down because gen fails to start due to=
 grid bad voltage // Site stabilized","Mboua Thierry","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","RM IHS reports that Si=
te went down because gen fails to start due to grid bad voltage // Site sta=
bilized","franck.nkomot@matech-cameroun.com","135","11-09-2025 18:05:15","M=
ATECH CMR"
"Internal Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058824=
45","Cite des nations","","11-09-2025 17:58:09","11-09-2025 17:52:44","11-0=
9-2025 18:10:47","Grid outage, site went down before Gen started due to Poo=
r battery backup // Site stabilised","Paul BIBOUM","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before Gen started due to Poor battery backup // Site stabilised","loi=
c.noumsi@matech-cameroun.com","326","11-09-2025 17:58:09","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_271","IHS_YND_275","NOCINC000588=
2430","Nkolbong","","11-09-2025 17:56:26","11-09-2025 17:53:04","11-09-2025=
 18:27:04","Gen failed to start due to malfunction of the ATS // ATS reset =
and Gen start manually","Delor Telezing","Equipment Repair","Passive","Cont=
rol Panel","ATS-AMF Issue","Gen failed to start due to malfunction of the A=
TS // ATS reset and Gen start manually","franck.nkomot@matech-cameroun.com"=
,"204","11-09-2025 17:56:26","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_375","IHS_YND_087","NOCINC000588=
2423","Camp-Sic-Tsinga","","11-09-2025 17:55:42","11-09-2025 17:48:31","11-=
09-2025 20:35:55","Grid only no space awainting grid return//grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
only no space awainting grid return//grid return","stephane.nkamwa@ihstower=
s.com","433","11-09-2025 17:55:42","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_339","IHS_YND_073","NOCINC000588=
2420","Chapelle-Obili","","11-09-2025 17:55:11","11-09-2025 17:49:01","11-0=
9-2025 18:03:01","Site went down because gen fails to start due to grid bad=
 voltage // Site stabilized","Paul BIBOUM","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","Site went down because gen fails =
to start due to grid bad voltage // Site stabilized","franck.nkomot@matech-=
cameroun.com","371","11-09-2025 17:55:11","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000588=
2368","CNR","","11-09-2025 17:49:33","11-09-2025 17:39:59","11-09-2025 17:5=
7:59","RM IHS reports that Site went down because gen fails to start due to=
 grid bad voltage // Site stabilized","Mboua Thierry","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","RM IHS reports that Si=
te went down because gen fails to start due to grid bad voltage // Site sta=
bilized","franck.nkomot@matech-cameroun.com","576","11-09-2025 17:49:33","M=
ATECH CMR"
"Internal Reconciliation","Site Down","CTR_160","IHS_YND_523","NOCINC000588=
2317","EMANA BILICK CITY","","11-09-2025 17:39:48","11-09-2025 17:29:59","1=
1-09-2025 19:22:45","Access issue in the site at night. Grid outage, site w=
ent down because site behaves as Grid only site (Gen Noise)//Grid return","=
Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord Related Issues"=
,"Access Issue - Land Lord","Access issue in the site at night. Grid outage=
, site went down because site behaves as Grid only site (Gen Noise)//Grid r=
eturn","franck.nkomot@matech-cameroun.com","591","11-09-2025 17:39:48","MAT=
ECH CMR"
"Acknowledge","Site Down","T0286","IHS_YND_060","NOCINC0005882316","Ngoa Ek=
elle","","11-09-2025 17:39:43","11-09-2025 17:35:37","11-09-2025 18:01:18",=
"Site up awaiting feedback","Paul BIBOUM","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup/ // Gen automatically started","loic.noumsi=
@matech-cameroun.com","247","11-09-2025 17:39:43","MATECH CMR"
"Internal Reconciliation","Site Down","T1868","IHS_YND_524","NOCINC00058823=
11","ODZA BORNE 10","","11-09-2025 17:39:10","11-09-2025 17:28:04","11-09-2=
025 19:50:37","Grid outage, site went down because Gen failed to start due =
to Gen battery faulty // Grid return","Albran Byorel","Equipment Repair","P=
assive","ACDG Gen","ACDG - Generator Battery","Grid outage, site went down =
because Gen failed to start due to Gen battery faulty // Grid return","loic=
.noumsi@matech-cameroun.com","667","11-09-2025 17:39:10","MATECH CMR"
"Resolved","Site Down","T0120","IHS_YND_031","NOCINC0005882261","Sime Build=
ing","","11-09-2025 17:30:22","11-09-2025 17:28:52","11-09-2025 18:38:18","=
Grid outage, Site went down before Gen start due to poor backup // Gen auto=
matically started","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Gen automatically started","loic.noumsi@matech-=
cameroun.com","91","11-09-2025 17:30:22","MATECH CMR"
"Resolved","Warning","T0772","IHS_YND_207","NOCINC0005882241","ARMP Buildin=
g","","11-09-2025 17:26:20","","","Site alarming because Grid outage// Grid=
 power Return and alarm cleared","Mboua Thierry","Warning","Warning","POWER=
","Warning - National Grid - Grid Outage Issue","Site alarming because Grid=
 outage// Grid power Return and alarm cleared","loic.noumsi@matech-cameroun=
.com","2","11-09-2025 17:26:20","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_622","IHS_YND_535","NOCINC000588=
2224","Awae Ewonkan","","11-09-2025 17:23:46","11-09-2025 17:12:59","11-09-=
2025 17:50:59","","Albran Byorel","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Site went diwn due to CB of rectifier disjuncted cau=
sing by grid fluctuation// We rearmed Cb","franck.nkomot@matech-cameroun.co=
m","2901","11-09-2025 17:23:46","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_236","IHS_YND_177","NOCINC000588=
2206","Awae-Yde","IHS_YND_535","11-09-2025 17:22:30","11-09-2025 17:12:59",=
"11-09-2025 17:50:59","Site went diwn due to CB of rectifier disjuncted cau=
sing by grid fluctuation// We rearmed Cb","Albran Byorel","Equipment Repair=
","Passive","Rectifier","Rectifier - Circuit Breaker","Site went diwn due t=
o CB of rectifier disjuncted causing by grid fluctuation// We rearmed Cb","=
franck.nkomot@matech-cameroun.com","2898","11-09-2025 17:22:30","MATECH CMR=
"
"Resolved","Site Down","T0466","IHS_YND_151","NOCINC0005882142","Tamtam Wee=
kend","","11-09-2025 17:15:09","11-09-2025 17:11:56","11-09-2025 17:15:04",=
"Grid Outage Site went down because Gen Overload (20KVA, 300A) // Grid retu=
rned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid Outage Site went down because Gen Overload (20KVA, 300A) // Gri=
d returned","loic.noumsi@matech-cameroun.com","194","11-09-2025 17:15:09","=
MATECH CMR"
"Internal Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00058821=
40","Mokolo Yaounde","","11-09-2025 17:14:48","11-09-2025 16:50:40","11-09-=
2025 17:28:07","Grid outage  ; battery discharged / grid return","","Grid S=
upply","Passive","Grid","National Grid - Low Current Supply","Grid outage  =
; battery discharged / grid return","adonis.defokoua@ihstowers.com","1450",=
"11-09-2025 17:14:48","MATECH CMR"
"Assigned","Site Down","T0219","IHS_YND_024","NOCINC0005882124","Garbati bu=
ilding","","11-09-2025 17:11:23","11-09-2025 17:04:18","11-09-2025 17:05:56=
","Active, no power issue U:54V site on Grid. TX FME Armand Nghetsa (691144=
412) from Huawei is informed","Delor Telezing","","","","","","loic.noumsi@=
matech-cameroun.com","427","11-09-2025 17:11:23","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_331","IHS_YND_253","NOCINC000588=
2121","Clge-Advantiste","","11-09-2025 17:11:00","11-09-2025 17:01:24","11-=
09-2025 18:38:39","No power issue site on grid with U=3D49.4V on Gen. Lionn=
el Steeve(655184876) from Huawei is informed","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue site on grid with U=3D49.4V on Gen. Lionnel Steeve(655184876)=
 from Huawei is informed","franck.nkomot@matech-cameroun.com","5505","11-09=
-2025 17:11:00","MATECH CMR"
"Assigned","Site Down","T1554","IHS_YND_286","NOCINC0005882112","Dagobert",=
"","11-09-2025 17:09:23","11-09-2025 17:03:19","11-09-2025 17:10:47","Activ=
e: No power issue, site is on Grid with Ubaie=3D54,6V, FME TX Mohamadou//69=
1144435 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue, site is on Grid with Ubaie=3D54,6V, FME TX Mohamadou//=
691144435 from Huawei is informed","loic.noumsi@matech-cameroun.com","365",=
"11-09-2025 17:09:23","MATECH CMR"
"Resolved","Site Down","T0456","IHS_YND_224","NOCINC0005882110","Messa Carr=
iere","","11-09-2025 17:08:42","11-09-2025 17:02:38","11-09-2025 17:58:28",=
"Grid outage,site went down because CB of Gen tripped due to burnt grid dis=
tributor  // He rearmed the CB.","Mboua Thierry","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Load Breaker","Grid outage,site went down because CB =
of Gen tripped due to burnt grid distributor  // He rearmed the CB.","loic.=
noumsi@matech-cameroun.com","366","11-09-2025 17:08:42","MATECH CMR"
"Resolved","Warning","CTR_044","IHS_YND_089","NOCINC0005882065","H-Prince",=
"","11-09-2025 17:02:48","","","Grid outage // grid return","Mboua Thierry"=
,"Warning","Warning","POWER","Warning - National Grid - Grid Outage Issue",=
"Grid outage // grid return","loic.noumsi@matech-cameroun.com","2","11-09-2=
025 17:02:48","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_029","IHS_YND_046","NOCINC000588=
2031","Djoungolo","IHS_YND_711","11-09-2025 16:55:26","11-09-2025 16:46:59"=
,"11-09-2025 18:39:49","No power issue, site is on Grid with Ubaie =3D52.8V=
. The TX Armand Nguetsa (699949553) from Huawei is informed","Mboua Thierry=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue, site is on Grid with Ubaie =3D52.8V. The TX A=
rmand Nguetsa (699949553) from Huawei is informed","franck.nkomot@matech-ca=
meroun.com","508","11-09-2025 16:55:26","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_102","IHS_YND_711","NOCINC000588=
2027","H-Franco New","","11-09-2025 16:54:09","11-09-2025 16:46:59","11-09-=
2025 16:48:59","","Delor Telezing","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","No power issue, site is on Grid with Ubaie =3D52.8V. T=
he TX Armand Nguetsa (699949553) from Huawei is informed","franck.nkomot@ma=
tech-cameroun.com","864","11-09-2025 16:54:09","MATECH CMR"
"Internal Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058820=
24","Cite des nations","","11-09-2025 16:52:59","11-09-2025 16:52:28","11-0=
9-2025 16:58:39","Grid outage, site went down before Gen started due to Poo=
r battery backup // Grid stabilised","Paul BIBOUM","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before Gen started due to Poor battery backup // Grid stabilised","loi=
c.noumsi@matech-cameroun.com","33","11-09-2025 16:52:59","MATECH CMR"
"Resolved","Site Down","T2208","IHS_YND_282","NOCINC0005881948","Meyo","","=
11-09-2025 16:38:21","11-09-2025 16:30:14","11-09-2025 16:42:02","ACTIVE //=
 No power issue Ubaie: 54,6V Site on Grid The Tx Fme Georges /6974661814 fr=
om huawei is informed","Hyemafo Gildas","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE // No power issu=
e Ubaie: 54,6V Site on Grid The Tx Fme Georges /6974661814 from huawei is i=
nformed","loic.noumsi@matech-cameroun.com","488","11-09-2025 16:38:21","MAT=
ECH CMR"
"Acknowledge","Site Down","T1736","IHS_YND_161","NOCINC0005881942","Sofavin=
c","","11-09-2025 16:36:57","11-09-2025 16:30:50","11-09-2025 16:41:27","",=
"MINKA NICOLAS","","","","","","loic.noumsi@matech-cameroun.com","368","11-=
09-2025 16:36:57","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_604","IHS_YND_252","NOCINC000588=
1941","Koweit City","","11-09-2025 16:36:41","11-09-2025 16:28:06","11-09-2=
025 16:51:06","No power issue site on grid with U=3D52V Lionnel Steeve from=
 Huawei is informed","Albran Byorel","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gri=
d with U=3D52V Lionnel Steeve from Huawei is informed","franck.nkomot@matec=
h-cameroun.com","516","11-09-2025 16:36:41","MATECH CMR"
"Acknowledge","Site Down","CTR_642","IHS_YND_537","NOCINC0005881896","MEFOU=
 ASSI","","11-09-2025 16:27:00","11-09-2025 16:21:50","11-09-2025 16:27:50"=
,"Site up, awaiting feedback","Fanda Brice","","","","","","franck.nkomot@m=
atech-cameroun.com","313","11-09-2025 16:27:00","MATECH CMR"
"Internal Reconciliation","Site Down","T1257","IHS_YND_800","NOCINC00058818=
95","ODZA CITE MBIA","","11-09-2025 16:26:41","11-09-2025 16:21:37","11-09-=
2025 16:38:01","Active//No power issue U=3D53,3V site on Grid.TX FME Leonel=
 Steve (655184876) from Huawei is informed","Albran Byorel","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue U=3D53,3V site on Grid.TX FME Leonel Steve (655184876) =
from Huawei is informed","loic.noumsi@matech-cameroun.com","306","11-09-202=
5 16:26:41","MATECH CMR"
"Resolved","Site Down","T1543","IHS_YND_336","NOCINC0005881872","EKIE","","=
11-09-2025 16:24:07","11-09-2025 16:21:53","11-09-2025 16:28:48","Grid outa=
ge, site went down due to main gen faulty // Grid return","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outa=
ge, site went down due to main gen faulty // Grid return","loic.noumsi@mate=
ch-cameroun.com","135","11-09-2025 16:24:07","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_454","NOCINC0005881806","=
Ngouetou","","11-09-2025 16:16:10","11-09-2025 16:03:09","11-09-2025 16:04:=
48","Cascaded Incident from TTO6105408","Parker Tchoup","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No Power issue on site Ubaie 52V =
Site on battery . FME TX_Abdouraman 657959647 is informed","stephane.nkamwa=
@ihstowers.com","781","11-09-2025 16:16:10","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_456","NOCINC0005881800","=
MBIMBIM","","11-09-2025 16:15:56","11-09-2025 16:03:09","11-09-2025 16:04:4=
8","Cascaded Incident from TTO6105408","Parker Tchoup","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No Power issue on site Ubaie 52V S=
ite on battery . FME TX_Abdouraman 657959647 is informed","stephane.nkamwa@=
ihstowers.com","767","11-09-2025 16:15:56","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_474","NOCINC0005881799","=
Yoko OCM","","11-09-2025 16:15:55","11-09-2025 16:03:09","11-09-2025 16:04:=
48","Cascaded Incident from TTO6105408","Parker Tchoup","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No Power issue on site Ubaie 52V =
Site on battery . FME TX_Abdouraman 657959647 is informed","stephane.nkamwa=
@ihstowers.com","766","11-09-2025 16:15:55","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_460","NOCINC0005881798","=
Matsari","","11-09-2025 16:15:55","11-09-2025 16:03:09","11-09-2025 16:04:4=
8","Cascaded Incident from TTO6105408","Parker Tchoup","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No Power issue on site Ubaie 52V S=
ite on battery . FME TX_Abdouraman 657959647 is informed","stephane.nkamwa@=
ihstowers.com","766","11-09-2025 16:15:55","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_475","NOCINC0005881797","=
Ngoum","","11-09-2025 16:15:55","11-09-2025 16:03:09","11-09-2025 16:04:48"=
,"Cascaded Incident from TTO6105408","Parker Tchoup","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No Power issue on site Ubaie 52V Sit=
e on battery . FME TX_Abdouraman 657959647 is informed","stephane.nkamwa@ih=
stowers.com","766","11-09-2025 16:15:55","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_016","IHS_YND_226","NOCINC000588=
1533","Mvog-Betsi","","11-09-2025 15:41:52","11-09-2025 15:31:59","11-09-20=
25 20:17:29","No power issue on site ,Site on Gen with Ubaie=3D52,3 V The T=
x Fme Mohamadou//691144435 from Huawei is informed","Hyemafo Gildas","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site ,Site on Gen with Ubaie=3D52,3 V The Tx Fme Mo=
hamadou//691144435 from Huawei is informed","franck.nkomot@matech-cameroun.=
com","594","11-09-2025 15:41:52","MATECH CMR"
"Acknowledge","Site Down","CTR_160","IHS_YND_523","NOCINC0005881392","EMANA=
 BILICK CITY","","11-09-2025 15:20:19","11-09-2025 15:16:08","11-09-2025 16=
:07:08","FME reports that Site behaves as Grid only site. Awaiting Grid res=
toration ","Fabrice Pouakam","","","","","","franck.nkomot@matech-cameroun.=
com","254","11-09-2025 15:20:19","MATECH CMR"
"Internal Reconciliation","Site Down","T0033","IHS_YND_167","NOCINC00058813=
33","Touring Club International","","11-09-2025 15:12:15","11-09-2025 15:07=
:52","11-09-2025 15:45:47","Site went down due to high temp // Shelter door=
 opened","Albran Byorel","Equipment Repair","Passive","Environmental","Airc=
on Switch Faulty","Site went down due to high temp // Shelter door opened",=
"loic.noumsi@matech-cameroun.com","264","11-09-2025 15:12:15","MATECH CMR"
"Resolved","Warning","T0033","IHS_YND_167","NOCINC0005881304","Touring Club=
 International","","11-09-2025 15:07:03","","","Site went down due to high =
temp // Shelter door opened","Albran Byorel","Warning","Warning","ENVIRONME=
NT","Warning - High Temperature","Site went down due to high temp // Shelte=
r door opened","loic.noumsi@matech-cameroun.com","3","11-09-2025 15:07:03",=
"MATECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000588=
1298","CNR","","11-09-2025 15:06:22","11-09-2025 15:04:51","11-09-2025 15:0=
7:51","RM IHS reports that Site went down because gen fails to start due to=
 grid bad voltage // Site stabilized","Mboua Thierry","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","RM IHS reports that Si=
te went down because gen fails to start due to grid bad voltage // Site sta=
bilized","franck.nkomot@matech-cameroun.com","92","11-09-2025 15:06:22","MA=
TECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000588=
0959","CNR","","11-09-2025 14:29:10","11-09-2025 14:24:05","11-09-2025 14:3=
2:05","Site went down due to insufficiency of rectifiers//Site stabilized",=
"Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to insufficiency of rectifiers//Site stabilized","fran=
ck.nkomot@matech-cameroun.com","307","11-09-2025 14:29:10","MATECH CMR"
"Internal Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058806=
22","Cite des nations","","11-09-2025 13:25:03","11-09-2025 13:18:55","11-0=
9-2025 13:36:26","Grid outage, site went down before Gen started due to Poo=
r battery backup // Grid stabilised","Paul BIBOUM","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before Gen started due to Poor battery backup // Grid stabilised","ger=
ard.tchangoue@matech-cameroun.com","370","11-09-2025 13:25:03","MATECH CMR"
"Internal Reconciliation","Site Down","T0394","IHS_YND_241","NOCINC00058804=
64","Etoudi","","11-09-2025 12:57:57","11-09-2025 12:49:52","11-09-2025 13:=
16:40","Grid outage .site went down due to gen overload(20kva,300 A) SS HIS=
 Bernard Atangana is informed // Grid return","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage .site went down=
 due to gen overload(20kva,300 A) SS HIS Bernard Atangana is informed // Gr=
id return","gerard.tchangoue@matech-cameroun.com","486","11-09-2025 12:57:5=
7","MATECH CMR"
"Internal Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058804=
28","Cite des nations","","11-09-2025 12:50:47","11-09-2025 12:46:28","11-0=
9-2025 12:54:28","Site went down due to poor backup // Grid return","Paul B=
IBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet - Batter=
y Low","Site went down due to poor backup // Grid return","gerard.tchangoue=
@matech-cameroun.com","260","11-09-2025 12:50:47","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_463","IHS_YND_313","NOCINC000588=
0400","Afanoya","","11-09-2025 12:46:26","11-09-2025 12:44:10","11-09-2025 =
12:46:16","Grid outage , site went down before Gen started due to poor batt=
ery backup// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage , site went down be=
fore Gen started due to poor battery backup// Grid return","edwige.kapawo@m=
atech-cameroun.com","137","11-09-2025 12:46:26","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_973","IHS_YND_796","NOCINC000588=
0379","Nkoabang Ebolmedjock","","11-09-2025 12:42:29","11-09-2025 12:37:15"=
,"11-09-2025 12:43:13","Active//No power issue, Site on Gen. Notice that it=
 is impacted by Nkolmesseng-Abom(CTR-711) Not Managed By IHS","Mba Lazare H=
erve","Customer Equipment Failure","Active","Active Equipment Failure","Aff=
ected by 3rd Party Site","Active//No power issue, Site on Gen. Notice that =
it is impacted by Nkolmesseng-Abom(CTR-711) Not Managed By IHS","edwige.kap=
awo@matech-cameroun.com","316","11-09-2025 12:42:29","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_453","NOCINC0005880269","=
Song-bong","","11-09-2025 12:32:09","11-09-2025 12:07:40","11-09-2025 13:02=
:04","Cascaded Incident from TTO6103630","Kemeni Franklin","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went Down due to Work,=
  Franklin (652735506/Matech) was on site for work / End of work","edwige.k=
apawo@matech-cameroun.com","1469","11-09-2025 12:32:09","MATECH CMR"
"Internal Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00058802=
44","Mokolo Yaounde","","11-09-2025 12:27:38","11-09-2025 12:25:08","11-09-=
2025 15:14:56","Site down due to lack of rectifier / 02 Rectifiers added ",=
"","Equipment Repair","Passive","Rectifier","Rectifier Battery","Site down =
due to lack of rectifier / 02 Rectifiers added ","joelle.ekessi@ihstowers.c=
om","152","11-09-2025 12:27:38","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_378","NOCINC0005880152","=
Eseka Town","","11-09-2025 12:12:15","11-09-2025 12:07:40","11-09-2025 13:0=
2:04","Cascaded Incident from TTO6103630","Kemeni Franklin","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went Down due to Work=
,  Franklin (652735506/Matech) was on site for work / End of work","edwige.=
kapawo@matech-cameroun.com","275","11-09-2025 12:12:15","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_067","IHS_YND_377","NOCINC000588=
0149","Eseka OCM","IHS_YND_378, IHS_YND_453","11-09-2025 12:11:49","11-09-2=
025 12:07:40","11-09-2025 13:02:04","Site went Down due to Work,  Franklin =
(652735506/Matech) was on site for work / End of work","Kemeni Franklin","E=
quipment Replacement","Passive","Planned Activity","Planned Activity - Pass=
ive","Site went Down due to Work,  Franklin (652735506/Matech) was on site =
for work / End of work","edwige.kapawo@matech-cameroun.com","250","11-09-20=
25 12:11:49","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_070","NOCINC0005879688","=
Efoulan","","11-09-2025 10:52:13","11-09-2025 10:51:13","11-09-2025 10:55:1=
4","Cascaded Incident from TTO6103101","MINKA NICOLAS","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue, Site impacted by C=
TR_773 Efoulan ont with is not manage by IHS","edwige.kapawo@matech-camerou=
n.com","60","11-09-2025 10:52:13","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_543","IHS_YND_155","NOCINC000587=
9682","Obobogo","IHS_YND_070","11-09-2025 10:51:29","11-09-2025 10:51:13","=
11-09-2025 10:55:14","No power issue, Site impacted by CTR_773 Efoulan ont =
with is not manage by IHS","MINKA NICOLAS","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","Affected by 3rd Party Site","No power iss=
ue, Site impacted by CTR_773 Efoulan ont with is not manage by IHS","edwige=
.kapawo@matech-cameroun.com","18","11-09-2025 10:51:29","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_210","IHS_YND_071","NOCINC000587=
9664","Scalom","","11-09-2025 10:48:07","11-09-2025 10:46:58","11-09-2025 1=
0:50:58","fme Paul repor that SS IHS Francois is on site for work // End of=
 work","Paul BIBOUM","Installation Activity","Passive","Planned Activity","=
Installation Activity","fme Paul repor that SS IHS Francois is on site for =
work // End of work","edwige.kapawo@matech-cameroun.com","70","11-09-2025 1=
0:48:07","MATECH CMR"
"Internal Reconciliation","Site Down","T0528","IHS_YND_027","NOCINC00058790=
34","Hopital Central","","11-09-2025 09:19:31","11-09-2025 09:02:20","11-09=
-2025 10:06:33","No Power issue on site, site on GRID U=3D54 V","","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No Power issue on site, site on GRID U=3D54 V","joelle.ekessi@ihstowers=
.com","1033","11-09-2025 09:19:31","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_540","IHS_YND_077","NOCINC000587=
9017","Obili Carrefour","IHS_YND_140","11-09-2025 09:17:09","11-09-2025 09:=
12:01","11-09-2025 09:17:45","Grid outage site went down due to grid fluctu=
ation and no RCP//grid power stabilized","Paul BIBOUM","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid outage site went=
 down due to grid fluctuation and no RCP//grid power stabilized","edwige.ka=
pawo@matech-cameroun.com","309","11-09-2025 09:17:09","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_157","IHS_YND_140","NOCINC000587=
9015","BISCUITERIE","","11-09-2025 09:16:35","11-09-2025 09:12:01","11-09-2=
025 09:17:45","","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage site went down due to grid fluctuation and =
no RCP//grid power stabilized","edwige.kapawo@matech-cameroun.com","873","1=
1-09-2025 09:16:35","MATECH CMR"
"Internal Reconciliation","Site Down","T1568","IHS_YND_084","NOCINC00058789=
10","Briquetterie","","11-09-2025 08:56:23","11-09-2025 08:55:18","11-09-20=
25 08:57:23","Grid only, No space to deploy // GRID RETURN","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid only, No space=
 to deploy // GRID RETURN","joelle.ekessi@ihstowers.com","67","11-09-2025 0=
8:56:23","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_674","IHS_YND_720","NOCINC000587=
8861","SOA UNIVERSITY STADIUM","","11-09-2025 08:47:47","11-09-2025 08:43:3=
9","11-09-2025 09:15:03","Grid fluctuation, Site went down because gen fail=
s to start due to grid bad voltage // He bypassed the Grid and site on Gen"=
,"Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid fluctuation, Site went down because gen fails to start=
 due to grid bad voltage // He bypassed the Grid and site on Gen","edwige.k=
apawo@matech-cameroun.com","249","11-09-2025 08:47:47","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_472","IHS_YND_698","NOCINC000587=
6271","EBOM","","10-09-2025 21:35:50","10-09-2025 21:22:42","10-09-2025 21:=
23:05","Active//No power issue on site U=3D53,6V site on Grid FME TX FULBER=
T//654266068 from Huawei is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue on site U=3D53,6V site on Grid FME TX FULBERT//654266068 fro=
m Huawei is informed","loic.noumsi@matech-cameroun.com","789","10-09-2025 2=
1:35:50","MATECH CMR"
"Internal Reconciliation","Site Down","T3231","IHS_YND_743","NOCINC00058762=
59","Ngousso Vallee","","10-09-2025 21:32:11","10-09-2025 21:30:34","10-09-=
2025 22:22:39","Eneo outage, Gen failled to start due to alarm oil pressure=
 // Gen card reseted and gen start manually","Siligap Boris","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Eneo outage, Gen failled =
to start due to alarm oil pressure // Gen card reseted and gen start manual=
ly","loic.noumsi@matech-cameroun.com","98","10-09-2025 21:32:11","MATECH CM=
R"
"Internal Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058762=
35","Messa Carriere","","10-09-2025 21:28:56","10-09-2025 21:24:51","10-09-=
2025 21:57:42","Site went down because SS IHS Francois is on site for work =
// End of work","Mboua Thierry","Equipment Replacement","Passive","Planned =
Activity","Planned Activity - Passive","Site went down because SS IHS Franc=
ois is on site for work // End of work","loic.noumsi@matech-cameroun.com","=
246","10-09-2025 21:28:56","MATECH CMR"
"Internal Reconciliation","Site Down","T0056","IHS_YND_189","NOCINC00058760=
34","Paradis Hotel","","10-09-2025 20:52:18","10-09-2025 20:49:11","10-09-2=
025 20:52:20","Site went down due to poor backup // Grid return","Siligap B=
oris","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery=
 Low","Site went down due to poor backup // Grid return","loic.noumsi@matec=
h-cameroun.com","188","10-09-2025 20:52:18","MATECH CMR"
"Internal Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058760=
01","Messa Carriere","","10-09-2025 20:46:27","10-09-2025 20:43:21","10-09-=
2025 21:02:39","Site went down because SS IHS Francois was on site for work=
 // End of work","Mboua Thierry","Installation Activity","Passive","Planned=
 Activity","Installation Activity","Site went down because SS IHS Francois =
was on site for work // End of work","loic.noumsi@matech-cameroun.com","187=
","10-09-2025 20:46:27","MATECH CMR"
"Internal Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058757=
74","Cite des nations","","10-09-2025 20:11:55","10-09-2025 20:07:46","10-0=
9-2025 20:15:18","Site went down due to poor backup // Grid return","Paul B=
IBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet - Batter=
y Low","Site went down due to poor backup // Grid return","loic.noumsi@mate=
ch-cameroun.com","250","10-09-2025 20:11:55","MATECH CMR"
"Internal Reconciliation","Site Down","T2859","IHS_YND_071","NOCINC00058756=
75","Scalom","","10-09-2025 19:58:58","10-09-2025 19:55:49","10-09-2025 20:=
05:07","Grid outage, site went down because Gen failed to start due to PWC =
ZTE malfunction // He reset it and put site on Gen","Paul BIBOUM","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage,=
 site went down because Gen failed to start due to PWC ZTE malfunction // H=
e reset it and put site on Gen","loic.noumsi@matech-cameroun.com","191","10=
-09-2025 19:58:58","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_599","IHS_YND_279","NOCINC000587=
5332","Messassi okolo","","10-09-2025 18:54:03","10-09-2025 18:44:59","10-0=
9-2025 20:45:59","ACTIVE//No power issue on site Ubaie=3D56V, site on Grid =
The TX Fme Synphorien 691316854 of Huawei is informed","Fabrice Pouakam","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE//No power issue on site Ubaie=3D56V, site on Grid The TX F=
me Synphorien 691316854 of Huawei is informed","franck.nkomot@matech-camero=
un.com","547","10-09-2025 18:54:03","MATECH CMR"
"Internal Reconciliation","Site Down","T0401","IHS_YND_205","NOCINC00058751=
82","Tongolo MTN","","10-09-2025 18:32:15","10-09-2025 18:25:10","10-09-202=
5 18:32:02","Site went down because FME Fabrice was on site for work (insta=
llation of Grid contactor) // End of work","Fabrice Pouakam","Installation =
Activity","Passive","Planned Activity","Installation Activity","Site went d=
own because FME Fabrice was on site for work (installation of Grid contacto=
r) // End of work","loic.noumsi@matech-cameroun.com","426","10-09-2025 18:3=
2:15","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_505","NOCINC0005875107","=
Scalom-IHS","","10-09-2025 18:20:42","10-09-2025 18:15:34","10-09-2025 18:5=
9:34","Cascaded Incident from TTO6097987","","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because Gen f=
ailed to start due to PWC ZTE malfunction // He put site on Gen","franck.nk=
omot@matech-cameroun.com","308","10-09-2025 18:20:42","MATECH CMR"
"Internal Reconciliation","Site Down","T2859","IHS_YND_071","NOCINC00058750=
88","Scalom","IHS_YND_505","10-09-2025 18:17:56","10-09-2025 18:15:34","10-=
09-2025 18:59:34","Grid outage, site went down because Gen failed to start =
due to PWC ZTE malfunction // He put site on Gen","Paul BIBOUM","Equipment =
Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, s=
ite went down because Gen failed to start due to PWC ZTE malfunction // He =
put site on Gen","loic.noumsi@matech-cameroun.com","143","10-09-2025 18:17:=
56","MATECH CMR"
"Internal Reconciliation","Site Down","T0292","IHS_YND_231","NOCINC00058750=
35","Nkolso","","10-09-2025 18:09:12","10-09-2025 18:06:44","10-09-2025 18:=
26:51","Grid outage, site went down due to gen (20kva, 265A) OVERLOAD //  H=
e reduced load, site on GEN","TIENTCHEU NZETCHIEU GAEL","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen (20kva, 265A) OVERLOAD //  He reduced load, site on GEN","loic.noumsi@m=
atech-cameroun.com","149","10-09-2025 18:09:12","MATECH CMR"
"Internal Reconciliation","Site Down","T1105","IHS_YND_266","NOCINC00058750=
08","Mimboman4","","10-09-2025 18:02:42","10-09-2025 17:58:16","10-09-2025 =
18:04:48","Site went down because FME Herve was on site for WORK / End of w=
ork","Mba Lazare Herve","Installation Activity","Passive","Planned Activity=
","Installation Activity","Site went down because FME Herve was on site for=
 WORK / End of work","loic.noumsi@matech-cameroun.com","268","10-09-2025 18=
:02:42","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_409","IHS_YND_090","NOCINC000587=
4902","BATA-Mokolo","","10-09-2025 17:36:04","10-09-2025 17:34:48","10-09-2=
025 18:59:47","Site went down due to insuffiency of rectifier // 03 Rectifi=
ers added","","Equipment Repair","Passive","Rectifier","Rectifier Distribut=
ion","Site went down due to insuffiency of rectifier // 03 Rectifiers added=
","joelle.ekessi@ihstowers.com","78","10-09-2025 17:36:04","MATECH CMR"
"Closed Complete","Warning","CTR_387","IHS_YND_276","NOCINC0005874876","Eko=
mbitie","","10-09-2025 17:31:09","","","High Temp ","Fabrice Pouakam","Warn=
ing","Warning","ENVIRONMENT","Warning - High Temperature","High Temp ","loi=
c.noumsi@matech-cameroun.com","2","10-09-2025 17:31:09","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000587=
4817","CNR","","10-09-2025 17:22:50","10-09-2025 17:22:42","10-09-2025 17:2=
7:42","Site went down due to insufficiency of rectifiers//Site stabilized",=
"Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to insufficiency of rectifiers//Site stabilized","fran=
ck.nkomot@matech-cameroun.com","9","10-09-2025 17:22:50","MATECH CMR"
"Closed Complete","Warning","CTR_047","IHS_YND_012","NOCINC0005874141","Eli=
g-Essono","","10-09-2025 16:02:49","","","High temp alarm // Alarm cleared"=
,"Paul BIBOUM","Warning","Warning","ENVIRONMENT","Warning - High Temperatur=
e","High temp alarm // Alarm cleared","franck.nkomot@matech-cameroun.com","=
10","10-09-2025 16:02:49","MATECH CMR"
"Internal Reconciliation","Site Down","T0401","IHS_YND_205","NOCINC00058738=
85","Tongolo MTN","","10-09-2025 15:35:28","10-09-2025 15:33:25","10-09-202=
5 15:55:38","Site went down because FME Fabrice was on site for work (insta=
llation of Grid contactor) // End of work","Fabrice Pouakam","Installation =
Activity","Passive","Planned Activity","Installation Activity","Site went d=
own because FME Fabrice was on site for work (installation of Grid contacto=
r) // End of work","loic.noumsi@matech-cameroun.com","124","10-09-2025 15:3=
5:28","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000587=
3743","CNR","","10-09-2025 15:17:32","10-09-2025 15:09:06","10-09-2025 16:1=
0:06","Site went down due to insufficiency of rectifiers//Site stabilized",=
"Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to insufficiency of rectifiers//Site stabilized","fran=
ck.nkomot@matech-cameroun.com","507","10-09-2025 15:17:32","MATECH CMR"
"Internal Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058736=
51","Messa Carriere","","10-09-2025 15:01:57","10-09-2025 14:57:48","10-09-=
2025 16:25:11","Site went down because gen started and stopped due to Gen C=
B (32A) faulty // He did bridge on it, site on gen","Mboua Thierry","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Load Breaker","Site went down beca=
use gen started and stopped due to Gen CB (32A) faulty // He did bridge on =
it, site on gen","loic.noumsi@matech-cameroun.com","250","10-09-2025 15:01:=
57","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_409","IHS_YND_090","NOCINC000587=
3507","BATA-Mokolo","","10-09-2025 14:37:55","10-09-2025 14:36:46","10-09-2=
025 17:20:02","Site went down due to Insuffiency of Rectifier // Site stabi=
lized","","Equipment Repair","Passive","Rectifier","Rectifier Module","Site=
 went down due to Insuffiency of Rectifier // Site stabilized","joelle.ekes=
si@ihstowers.com","70","10-09-2025 14:37:55","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_456","NOCINC0005873236","=
MBIMBIM","","10-09-2025 13:55:57","10-09-2025 13:45:59","10-09-2025 14:07:4=
4","Cascaded Incident from TTO6095842","Parker Tchoup","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive",".","stephane.nkamwa@ihstowers.c=
om","598","10-09-2025 13:55:57","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_474","NOCINC0005873234","=
Yoko OCM","","10-09-2025 13:55:57","10-09-2025 13:45:59","10-09-2025 14:07:=
44","Cascaded Incident from TTO6095842","Parker Tchoup","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive",".","stephane.nkamwa@ihstowers.=
com","598","10-09-2025 13:55:57","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_454","NOCINC0005873235","=
Ngouetou","","10-09-2025 13:55:57","10-09-2025 13:45:59","10-09-2025 14:07:=
44","Cascaded Incident from TTO6095842","Parker Tchoup","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive",".","stephane.nkamwa@ihstowers.=
com","598","10-09-2025 13:55:57","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_475","NOCINC0005873233","=
Ngoum","","10-09-2025 13:55:56","10-09-2025 13:45:59","10-09-2025 14:07:44"=
,"Cascaded Incident from TTO6095842","Parker Tchoup","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive",".","stephane.nkamwa@ihstowers.com=
","597","10-09-2025 13:55:56","MATECH CMR"
"Acknowledge","Site Down","CTR_321","IHS_YND_085","NOCINC0005873157","Briqu=
eterie","","10-09-2025 13:43:13","10-09-2025 13:33:05","","Grid only no spa=
ce awaiting grid return.","","","","","","","stephane.nkamwa@ihstowers.com"=
,"609","10-09-2025 13:43:13","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_075","IHS_YND_133","NOCINC000587=
2817","Elig-Edzoa","","10-09-2025 12:52:42","10-09-2025 12:45:34","10-09-20=
25 16:31:07","Grid only no space/ GRID RETURN","","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","Grid only no space/ GRID RETURN"=
,"edwige.kapawo@matech-cameroun.com","430","10-09-2025 12:52:42","MATECH CM=
R"
"Internal Reconciliation","Site Down","T1744","IHS_YND_556","NOCINC00058724=
65","NKOMKANA ELIZA HOTEL","","10-09-2025 11:58:15","10-09-2025 11:52:09","=
10-09-2025 12:09:33","Gird outage no space // grid return ","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Gird outage no spac=
e // grid return ","adonis.defokoua@ihstowers.com","367","10-09-2025 11:58:=
15","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_692","IHS_YND_223","NOCINC000587=
2269","Febe Village","","10-09-2025 11:36:18","10-09-2025 11:32:09","10-09-=
2025 11:47:36","Site went down because gen failed to start due to grid bad =
voltage // He bypassed the grid and gen manually started","Mboua Thierry","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Si=
te went down because gen failed to start due to grid bad voltage // He bypa=
ssed the grid and gen manually started","gerard.tchangoue@matech-cameroun.c=
om","251","10-09-2025 11:36:18","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000587=
1657","CNR","","10-09-2025 10:04:09","10-09-2025 10:02:58","10-09-2025 14:3=
5:58","Site went down due to insufficiency of rectifiers//Site stabilized",=
"Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to insufficiency of rectifiers//Site stabilized","edwi=
ge.kapawo@matech-cameroun.com","72","10-09-2025 10:04:09","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_973","IHS_YND_796","NOCINC000587=
1446","Nkoabang Ebolmedjock","","10-09-2025 09:24:35","10-09-2025 09:22:28"=
,"10-09-2025 09:26:40","Active//No power issue, Site on Gen. Notice that it=
 is impacted by Nkolmesseng-Abom(CTR-711) Not Managed By IHS","Mba Lazare H=
erve","Customer Equipment Failure","Active","Active Equipment Failure","Aff=
ected by 3rd Party Site","Active//No power issue, Site on Gen. Notice that =
it is impacted by Nkolmesseng-Abom(CTR-711) Not Managed By IHS","edwige.kap=
awo@matech-cameroun.com","129","10-09-2025 09:24:35","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_458","IHS_YND_526","NOCINC000587=
1257","Nkoabang2","","10-09-2025 08:54:28","10-09-2025 08:52:17","10-09-202=
5 08:55:12","Grid outage, site went down due to gen overload (22KVA, 330A),=
 SS Blaise IHS is informed //site stabilised","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went dow=
n due to gen overload (22KVA, 330A), SS Blaise IHS is informed //site stabi=
lised","stephane.nkamwa@ihstowers.com","134","10-09-2025 08:54:28","MATECH =
CMR"
"Internal Reconciliation","Site Down","CTR_096","IHS_YND_042","NOCINC000587=
0767","Mvog-Ada_OCM","","10-09-2025 07:35:33","10-09-2025 07:29:05","10-09-=
2025 09:30:36","Grid outage, No space to deploy / Awaiting grid return////G=
RID RETURN","","Grid Supply","Passive","Grid","National Grid - Grid Outage =
Issue","Grid outage, No space to deploy / Awaiting grid return////GRID RETU=
RN","stephane.nkamwa@ihstowers.com","389","10-09-2025 07:35:33","MATECH CMR=
"
"Internal Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00058706=
24","Mokolo Yaounde","","10-09-2025 07:05:12","10-09-2025 07:03:20","10-09-=
2025 07:04:40","Site down due to grid fluctuation / grid stabilized","","Gr=
id Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue","S=
ite down due to grid fluctuation / grid stabilized","adonis.defokoua@ihstow=
ers.com","114","10-09-2025 07:05:12","MATECH CMR"
"Internal Reconciliation","Site Down","T0058","IHS_YND_293","NOCINC00058700=
74","Nkoabang MTN","","10-09-2025 05:00:07","10-09-2025 04:58:54","10-09-20=
25 05:34:40","GRID outage, site went down because gen ran untill fuel short=
age // refueling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel",=
"Diesel Outage","GRID outage, site went down because gen ran untill fuel sh=
ortage // refueling done","cedric.tiani@matech-cameroun.com","74","10-09-20=
25 05:00:07","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_321","IHS_YND_085","NOCINC000586=
8875","Briqueterie","","09-09-2025 23:23:33","09-09-2025 22:53:28","10-09-2=
025 10:39:49","Site went down to CB 125 (A) disjunted in the PWC// He reame=
d the CB 125 (A) and Site is on Grid","","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down to CB 12=
5 (A) disjunted in the PWC// He reamed the CB 125 (A) and Site is on Grid",=
"alexandre.kamal@ihstowers.com","1807","09-09-2025 23:23:33","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_321","IHS_YND_085","NOCINC000586=
8656","Briqueterie","","09-09-2025 22:41:39","09-09-2025 22:07:29","09-09-2=
025 22:41:29","","","Grid Supply","Passive","Grid","National Grid - Grid In=
complete Phase","Grid outage (No space to deployed a mobile Gen)// Grid ret=
urn","alexandre.kamal@ihstowers.com","2052","09-09-2025 22:41:39","MATECH C=
MR"
"Cancelled","Warning","CTR_008","IHS_YND_068","NOCINC0005868646","Ndisamba"=
,"","09-09-2025 22:39:49","","","","MINKA NICOLAS","","","","","","alexandr=
e.kamal@ihstowers.com","590","09-09-2025 22:39:49","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_015","IHS_YND_115","NOCINC000586=
8634","Labogenie","","09-09-2025 22:38:14","09-09-2025 22:29:06","09-09-202=
5 22:30:06","","","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active // No power issue U =3D54,5V site on G=
rid. The Tx FME Eloundou (693212405 )from Huawei is informed.","alexandre.k=
amal@ihstowers.com","550","09-09-2025 22:38:14","MATECH CMR"
"Internal Reconciliation","Site Down","T1568","IHS_YND_084","NOCINC00058682=
98","Briquetterie","","09-09-2025 21:39:27","09-09-2025 21:35:02","10-09-20=
25 10:39:45","Grid outage ; no space for MDG / Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage ; no sp=
ace for MDG / Grid return","landry.etame@ihstowers.com","266","09-09-2025 2=
1:39:27","MATECH CMR"
"Internal Reconciliation","Site Down","T0638","IHS_YND_318","NOCINC00058681=
78","SOA University","","09-09-2025 21:25:48","09-09-2025 21:15:59","09-09-=
2025 21:51:59","Site went down due to 01/02 rectifiers on site faulty//He r=
eset it and site on Grid(Replacement ongoing)","Siligap Boris","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down due to 01/0=
2 rectifiers on site faulty//He reset it and site on Grid(Replacement ongoi=
ng)","franck.nkomot@matech-cameroun.com","590","09-09-2025 21:25:48","MATEC=
H CMR"
"Internal Reconciliation","Site Down","T1834","IHS_YND_132","NOCINC00058681=
56","Manguiers Dispensaire","","09-09-2025 21:20:20","09-09-2025 21:13:10",=
"09-09-2025 21:14:49","incorrectly logged ticket","Fabrice Pouakam","Incorr=
ectly Logged Tickets","Error","Error","Error","incorrectly logged ticket","=
franck.nkomot@matech-cameroun.com","431","09-09-2025 21:20:20","MATECH CMR"
"Internal Reconciliation","Site Down","T0050","IHS_YND_039","NOCINC00058681=
16","Siantou Radio TV","","09-09-2025 21:12:27","09-09-2025 20:56:16","10-0=
9-2025 13:00:27","Grid outage no space // awaiting grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no =
space // awaiting grid return","landry.etame@ihstowers.com","972","09-09-20=
25 21:12:27","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_674","IHS_YND_720","NOCINC000586=
7926","SOA UNIVERSITY STADIUM","","09-09-2025 20:51:35","09-09-2025 20:46:2=
6","09-09-2025 21:32:26","Grid fluctuation, Site went down because gen fail=
s to start due to grid bad voltage // He bypassed the Grid and site on Gen"=
,"Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid fluctuation, Site went down because gen fails to start=
 due to grid bad voltage // He bypassed the Grid and site on Gen","vanel.mb=
iada@matech-cameroun.com","310","09-09-2025 20:51:35","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_049","IHS_YND_209","NOCINC000586=
7880","Manguier","","09-09-2025 20:44:17","09-09-2025 20:44:04","09-09-2025=
 20:56:24","Active//No power issue on site Ubaie=3D54.5V site on Grid The T=
x FME Armand Nguetsa//699949553 from Huawei is informed","Fabrice Pouakam",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active//No power issue on site Ubaie=3D54.5V site on Grid The T=
x FME Armand Nguetsa//699949553 from Huawei is informed","vanel.mbiada@mate=
ch-cameroun.com","14","09-09-2025 20:44:17","MATECH CMR"
"Internal Reconciliation","Site Down","T1105","IHS_YND_266","NOCINC00058676=
58","Mimboman4","","09-09-2025 20:13:15","09-09-2025 20:11:06","09-09-2025 =
20:19:06","Grid outage, site went down because gen start and stopped due to=
 High temperature caused by faulty water pump  // He added water and manual=
ly start the gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen=
","ACDG - Water Pump","Grid outage, site went down because gen start and st=
opped due to High temperature caused by faulty water pump  // He added wate=
r and manually start the gen","franck.nkomot@matech-cameroun.com","131","09=
-09-2025 20:13:15","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_409","IHS_YND_090","NOCINC000586=
7572","BATA-Mokolo","","09-09-2025 19:59:46","09-09-2025 19:56:14","09-09-2=
025 19:59:59","","","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficiency of rectifiers//Site stabilised","=
kouoh.jean@ihstowers.com","214","09-09-2025 19:59:46","MATECH CMR"
"Internal Reconciliation","Site Down","T1105","IHS_YND_266","NOCINC00058674=
35","Mimboman4","","09-09-2025 19:38:05","09-09-2025 19:35:53","09-09-2025 =
20:07:53","Grid outage, site went down because gen start and stopped due to=
 High temperature caused by faulty water pump  // He added water and manual=
ly start the gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen=
","ACDG - Water Pump","Grid outage, site went down because gen start and st=
opped due to High temperature caused by faulty water pump  // He added wate=
r and manually start the gen","franck.nkomot@matech-cameroun.com","134","09=
-09-2025 19:38:05","MATECH CMR"
"Internal Reconciliation","Site Down","T2581","IHS_YND_750","NOCINC00058674=
03","Nkoabang entree carriere","","09-09-2025 19:32:58","09-09-2025 19:25:4=
9","09-09-2025 19:47:49","Grid outage, Site went down before Gen start due =
to poor backup // Gen started Automatically","Mba Lazare Herve","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outag=
e, Site went down before Gen start due to poor backup // Gen started Automa=
tically","franck.nkomot@matech-cameroun.com","430","09-09-2025 19:32:58","M=
ATECH CMR"
"Internal Reconciliation","Site Down","CTR_409","IHS_YND_090","NOCINC000586=
7315","BATA-Mokolo","","09-09-2025 19:18:45","09-09-2025 19:10:31","09-09-2=
025 19:15:31","","","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficiency of rectifiers//Site stabilised","=
kouoh.jean@ihstowers.com","496","09-09-2025 19:18:45","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_409","IHS_YND_090","NOCINC000586=
7309","BATA-Mokolo","","09-09-2025 19:17:18","09-09-2025 06:25:31","09-09-2=
025 11:13:31","","","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficiency of rectifiers//Site stabilised","=
kouoh.jean@ihstowers.com","46309","09-09-2025 19:17:18","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000586=
6524","CNR","","09-09-2025 17:31:08","09-09-2025 17:23:58","09-09-2025 17:3=
1:59","Site went down due to insufficiency of rectifiers//Site stabilised",=
"Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to insufficiency of rectifiers//Site stabilised","vane=
l.mbiada@matech-cameroun.com","431","09-09-2025 17:31:08","MATECH CMR"
"Internal Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00058661=
55","Mokolo Yaounde","","09-09-2025 16:40:22","09-09-2025 16:36:04","09-09-=
2025 16:38:08","rectifier hanguing // rectifier reset","","Equipment Repair=
","Passive","Rectifier","Rectifier Distribution","rectifier hanguing // rec=
tifier reset","landry.etame@ihstowers.com","260","09-09-2025 16:40:22","MAT=
ECH CMR"
"Closed Complete","Warning","T0527","IHS_YND_019","NOCINC0005865936","Hotel=
 de Ville Yde","","09-09-2025 16:08:44","","","Grid bad voltage on site // =
Site stabilized","Paul BIBOUM","Warning","Warning","POWER","Warning - Natio=
nal Grid - Grid Incomplete Phase","Grid bad voltage on site // Site stabili=
zed","franck.nkomot@matech-cameroun.com","9","09-09-2025 16:08:44","MATECH =
CMR"
"Internal Reconciliation","Site Down","CTR_160","IHS_YND_523","NOCINC000586=
5902","EMANA BILICK CITY","","09-09-2025 16:03:28","09-09-2025 16:00:18","1=
1-09-2025 13:28:10","Access issue in the site at night. Grid outage, site w=
ent down because site behaves as Grid only site with eneo meter has burned =
out.//Grid return(replacement eneo meter)","Fabrice Pouakam","Access Denial=
","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Ac=
cess issue in the site at night. Grid outage, site went down because site b=
ehaves as Grid only site with eneo meter has burned out.//Grid return(repla=
cement eneo meter)","vanel.mbiada@matech-cameroun.com","193","09-09-2025 16=
:03:28","MATECH CMR"
"Internal Reconciliation","Site Down","T1737","IHS_YND_005","NOCINC00058658=
93","Imm-Olympique","","09-09-2025 16:01:05","09-09-2025 15:58:46","09-09-2=
025 18:05:51","Grid Outage Site went down because Gen overload(20KVA//295A)=
 SS HIS Raoul is informed//Grid return","Paul BIBOUM","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid Outage Site went down because Ge=
n overload(20KVA//295A) SS HIS Raoul is informed//Grid return","franck.nkom=
ot@matech-cameroun.com","140","09-09-2025 16:01:05","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_323","IHS_YND_043","NOCINC000586=
5859","Emia","","09-09-2025 15:56:24","09-09-2025 15:54:01","09-09-2025 17:=
50:30","Grid only no space // Grid return ","","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue","Grid only no space // Grid return "=
,"kouoh.jean@ihstowers.com","144","09-09-2025 15:56:24","MATECH CMR"
"Closed Complete","Warning","T0123","IHS_YND_013","NOCINC0005865838","Labor=
atoire T.Bella","","09-09-2025 15:52:27","","","High temp // The FME opened=
 the shelter","Paul BIBOUM","Warning","Warning","ENVIRONMENT","Warning - Hi=
gh Temperature","High temp // The FME opened the shelter","franck.nkomot@ma=
tech-cameroun.com","1950","09-09-2025 15:52:27","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000586=
5535","CNR","","09-09-2025 15:07:14","09-09-2025 15:06:08","09-09-2025 15:1=
3:47","No power issue site on grid with U=3D53.8V //site impacted by CNDH w=
hich is not our responsability","Mboua Thierry","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
site on grid with U=3D53.8V //site impacted by CNDH which is not our respon=
sability","vanel.mbiada@matech-cameroun.com","67","09-09-2025 15:07:14","MA=
TECH CMR"
"Internal Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058654=
09","Cite des nations","","09-09-2025 14:51:08","09-09-2025 14:43:18","09-0=
9-2025 14:48:18","Active //No power issue ,site on Grid on site with Ubaie:=
53.8V on Gen. Fme Hosiah / 674007438 from huawei is informed","Paul BIBOUM"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active //No power issue ,site on Grid on site with Ubaie:53.8V=
 on Gen. Fme Hosiah / 674007438 from huawei is informed","franck.nkomot@mat=
ech-cameroun.com","471","09-09-2025 14:51:08","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_171","NOCINC0005865353","=
Awae Escalier","","09-09-2025 14:41:21","09-09-2025 14:20:56","09-09-2025 1=
5:17:25","Cascaded Incident from TTO6086873","Albran Byorel","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid Outage Site went dow=
n because Gen Failed to Start due to Relay 220V faulty // He bypass Relay s=
ite on grid ","vanel.mbiada@matech-cameroun.com","1225","09-09-2025 14:41:2=
1","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_535","NOCINC0005865335","=
Awae Ewonkan","","09-09-2025 14:37:34","09-09-2025 14:20:56","09-09-2025 15=
:17:25","Cascaded Incident from TTO6086873","Albran Byorel","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid Outage Site went down=
 because Gen Failed to Start due to Relay 220V faulty // He bypass Relay si=
te on grid ","vanel.mbiada@matech-cameroun.com","998","09-09-2025 14:37:34"=
,"MATECH CMR"
"Internal Reconciliation","Site Down","CTR_236","IHS_YND_177","NOCINC000586=
5219","Awae-Yde","IHS_YND_535, IHS_YND_171","09-09-2025 14:23:04","09-09-20=
25 14:20:56","09-09-2025 15:17:25","Grid Outage Site went down because Gen =
Failed to Start due to Relay 220V faulty // He bypass Relay site on grid ",=
"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Relay Fault=
y","Grid Outage Site went down because Gen Failed to Start due to Relay 220=
V faulty // He bypass Relay site on grid ","vanel.mbiada@matech-cameroun.co=
m","129","09-09-2025 14:23:04","MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_029","NOCINC0005864965","=
Sapeur","","09-09-2025 13:39:39","09-09-2025 13:34:12","10-09-2025 15:52:21=
","Cascaded Incident from TTO6086580","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, No space to deploy =
// GRID RETURN","joelle.ekessi@ihstowers.com","326","09-09-2025 13:39:39","=
MATECH CMR"
"Internal Reconciliation","Site Down","CTR_076","IHS_YND_030","NOCINC000586=
4964","E-Police","IHS_YND_029","09-09-2025 13:39:17","09-09-2025 13:34:12",=
"10-09-2025 15:52:21","Grid outage, No space to deploy // GRID RETURN","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age, No space to deploy // GRID RETURN","joelle.ekessi@ihstowers.com","307"=
,"09-09-2025 13:39:17","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_593","IHS_YND_309","NOCINC000586=
4751","Leboudi","","09-09-2025 13:10:32","09-09-2025 13:02:09","09-09-2025 =
13:03:44","Active // no power issue, site is on Grid with Ubaie=3D54.3V, Mo=
hamadou(691144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active // no power issue, site is on Grid with Ubaie=3D54.3V, Moha=
madou(691144435) from Huawei is informed.","vanel.mbiada@matech-cameroun.co=
m","504","09-09-2025 13:10:32","MATECH CMR"
"Internal Reconciliation","Site Down","T0638","IHS_YND_318","NOCINC00058645=
63","SOA University","","09-09-2025 12:41:41","09-09-2025 12:40:33","09-09-=
2025 12:50:42","	Grid outage,site went down because gen failed to start due=
 to grid bad voltage(01 phases off)//he did a bridge with the good phase","=
Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","	Grid outage,site went down because gen failed to start due t=
o grid bad voltage(01 phases off)//he did a bridge with the good phase","fr=
anck.nkomot@matech-cameroun.com","69","09-09-2025 12:41:41","MATECH CMR"
"Closed Complete","Warning","CTR_080","IHS_YND_298","NOCINC0005864436","Ole=
mbe","","09-09-2025 12:18:42","","","Grid fluctuation, Site went down becau=
se Gen failed to start due to Grid bad voltage / Site stabilised","Fabrice =
Pouakam","Warning","Warning","POWER","Warning - National Grid - Grid Incomp=
lete Phase","Grid fluctuation, Site went down because Gen failed to start d=
ue to Grid bad voltage / Site stabilised","vanel.mbiada@matech-cameroun.com=
","6012","09-09-2025 12:18:42","MATECH CMR"
"Closed Complete","Warning","CTR_109","IHS_YND_037","NOCINC0005864424","Nko=
lndongo","","09-09-2025 12:16:43","","","FME Nicolas was on site and reppor=
t that, faulty compressor and Shelter is open","MINKA NICOLAS","Warning","W=
arning","ENVIRONMENT","Warning - Aircon Compressor High Temp","FME Nicolas =
was on site and repport that, faulty compressor and Shelter is open","vanel=
.mbiada@matech-cameroun.com","6011","09-09-2025 12:16:43","MATECH CMR"
"Closed Complete","Warning","T0211","IHS_YND_393","NOCINC0005864420","Ezeza=
ng","","09-09-2025 12:16:03","","","Ahanda reported Shelter Open but AirCon=
 faulty ","Parker Tchoup","Warning","Warning","ENVIRONMENT","Warning - Faul=
ty Aircondition","Ahanda reported Shelter Open but AirCon faulty ","vanel.m=
biada@matech-cameroun.com","5837","09-09-2025 12:16:03","MATECH CMR"
"Closed Complete","Warning","T0029","IHS_YND_357","NOCINC0005864413","Sacre=
 Coeur Catholic Church","","09-09-2025 12:15:07","","","Alarm unproven","Mb=
oua Thierry","Warning","Warning","Unlisted RCA","Warning - Others","Alarm u=
nproven","vanel.mbiada@matech-cameroun.com","6014","09-09-2025 12:15:07","M=
ATECH CMR"
"Closed Complete","Warning","T0091","IHS_YND_314","NOCINC0005864404","Sous =
Prefecture","","09-09-2025 12:14:18","","","High temp alarm // Alarm cleare=
d","Fanda Brice","Warning","Warning","ENVIRONMENT","Warning - High Temperat=
ure","High temp alarm // Alarm cleared","vanel.mbiada@matech-cameroun.com",=
"5784","09-09-2025 12:14:18","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_911","IHS_YND_762","NOCINC000586=
3619","Nkolfon Cimencam","","09-09-2025 10:10:11","09-09-2025 10:05:48","09=
-09-2025 10:13:05","Site went down because FME  was on site for work (water=
 and Oil adding) // End of work","Hyemafo Gildas","Equipment Replacement","=
Passive","Planned Activity","Planned Activity - ACDG Inspection","Site went=
 down because FME  was on site for work (water and Oil adding) // End of wo=
rk","vanel.mbiada@matech-cameroun.com","265","09-09-2025 10:10:11","MATECH =
CMR"
"Internal Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000586=
3508","CNR","","09-09-2025 09:49:41","09-09-2025 09:42:34","09-09-2025 09:4=
3:21","No power issue site on grid with U=3D53.8V //site impacted by CNDH w=
hich is not our responsability","Mboua Thierry","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
site on grid with U=3D53.8V //site impacted by CNDH which is not our respon=
sability","vanel.mbiada@matech-cameroun.com","428","09-09-2025 09:49:41","M=
ATECH CMR"
"Internal Reconciliation","Site Down","CTR_599","IHS_YND_279","NOCINC000586=
3057","Messassi okolo","","09-09-2025 08:40:41","09-09-2025 08:35:43","09-0=
9-2025 09:29:14","Grid outage gen started and stopped due to alarm high tem=
p//We add water and gen manually started ","Fabrice Pouakam","Equipment Rep=
air","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","=
Grid outage gen started and stopped due to alarm high temp//We add water an=
d gen manually started ","vanel.mbiada@matech-cameroun.com","301","09-09-20=
25 08:40:41","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_271","IHS_YND_275","NOCINC000586=
3021","Nkolbong","","09-09-2025 08:29:24","09-09-2025 08:26:18","09-09-2025=
 09:14:18","Gen failed to start due to malfunction of the ATS // ATS reset =
and Gen start manually","Delor Telezing","Equipment Repair","Passive","Cont=
rol Panel","ATS-AMF Issue","Gen failed to start due to malfunction of the A=
TS // ATS reset and Gen start manually","vanel.mbiada@matech-cameroun.com",=
"189","09-09-2025 08:29:24","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_465","IHS_YND_291","NOCINC000586=
3018","Ekoumdoum OCM","","09-09-2025 08:27:45","09-09-2025 08:24:26","09-09=
-2025 09:04:09","Grid outage.gen ran until fuel shortage//Refueling done","=
Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outag=
e.gen ran until fuel shortage//Refueling done","vanel.mbiada@matech-camerou=
n.com","201","09-09-2025 08:27:45","MATECH CMR"
"Closed Complete","Warning","T0033","IHS_YND_167","NOCINC0005862881","Touri=
ng Club International","","09-09-2025 07:49:40","","","High Temp // Aboubac=
ar opened the shelter.","Albran Byorel","Warning","Warning","ENVIRONMENT","=
Warning - High Temperature","High Temp // Aboubacar opened the shelter.","v=
anel.mbiada@matech-cameroun.com","17","09-09-2025 07:49:40","MATECH CMR"
"Internal Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00058627=
19","Mokolo Yaounde","","09-09-2025 07:09:35","09-09-2025 07:08:25","09-09-=
2025 07:11:34","Grid only, Grid Outage on site, no space to deploy MDGE // =
Grid return","","Grid Supply","Passive","Grid","National Grid - Grid Outage=
 Issue","Grid only, Grid Outage on site, no space to deploy MDGE // Grid re=
turn","franck.nkomot@matech-cameroun.com","73","09-09-2025 07:09:35","MATEC=
H CMR"
"Closed Complete","Warning","T0638","IHS_YND_318","NOCINC0005862096","SOA U=
niversity","","09-09-2025 03:52:18","","","Grid outage,site went down becau=
se gen failed to start due to grid bad voltage(01 phases off)//he did a bri=
dge with the good phase","Siligap Boris","Warning","Warning","POWER","Warni=
ng - National Grid - Grid Incomplete Phase","Grid outage,site went down bec=
ause gen failed to start due to grid bad voltage(01 phases off)//he did a b=
ridge with the good phase","franck.nkomot@matech-cameroun.com","2620","09-0=
9-2025 03:52:18","MATECH CMR"
"Internal Reconciliation","Site Down","T3231","IHS_YND_743","NOCINC00058618=
71","Ngousso Vallee","","09-09-2025 02:41:09","09-09-2025 02:39:58","09-09-=
2025 08:03:19","Acces issue during the nigth; Grid fluctuations site went d=
own due to bad grid voltage and no RCP //He made a bridge with a good phase=
","Siligap Boris","Access Denial","Lease Or Legal","Landlord Related Issues=
","Access Issue - Land Lord","Acces issue during the nigth; Grid fluctuatio=
ns site went down due to bad grid voltage and no RCP //He made a bridge wit=
h a good phase","franck.nkomot@matech-cameroun.com","72","09-09-2025 02:41:=
09","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_528","NOCINC0005861757","=
MEHANDAN","","09-09-2025 02:09:31","09-09-2025 02:01:31","09-09-2025 02:02:=
31","Cascaded Incident from TTO6083022","Albran Byorel","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active: No power issue on site Ub=
aie =3D55.1V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei=
 is informe","franck.nkomot@matech-cameroun.com","480","09-09-2025 02:09:31=
","MATECH CMR"
"External Reconciliation","Site Down","T2818","IHS_YND_527","NOCINC00058617=
53","Odza II OCM","IHS_YND_528","09-09-2025 02:09:06","09-09-2025 02:01:31"=
,"09-09-2025 02:02:31","Active: No power issue on site Ubaie =3D55.1V site =
on Grid. The TX FME Lionnel Adhex (655184876) from Huawei is informe","Albr=
an Byorel","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","Active: No power issue on site Ubaie =3D55.1V site o=
n Grid. The TX FME Lionnel Adhex (655184876) from Huawei is informe","franc=
k.nkomot@matech-cameroun.com","458","09-09-2025 02:09:06","MATECH CMR"
"External Reconciliation","Site Down","T0401","IHS_YND_205","NOCINC00058615=
52","Tongolo MTN","","09-09-2025 01:21:44","09-09-2025 01:14:34","09-09-202=
5 02:04:34","Grid outage site went down because Gen failed to start due to =
Gen card faulty // he reset and started Gen manually","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage si=
te went down because Gen failed to start due to Gen card faulty // he reset=
 and started Gen manually","franck.nkomot@matech-cameroun.com","431","09-09=
-2025 01:21:44","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_160","IHS_YND_523","NOCINC000586=
1323","EMANA BILICK CITY","","09-09-2025 00:36:18","09-09-2025 00:30:54","0=
9-09-2025 14:57:54","Grid outage,site behaves as Grid only site (Gen Noise)=
//Grid return","Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord=
 Related Issues","Access Issue - Land Lord","Grid outage,site behaves as Gr=
id only site (Gen Noise)//Grid return","franck.nkomot@matech-cameroun.com",=
"326","09-09-2025 00:36:18","MATECH CMR"
"External Reconciliation","Site Down","T2141","IHS_YND_531","NOCINC00058612=
99","OTELE MTN","","09-09-2025 00:30:18","09-09-2025 00:25:06","09-09-2025 =
00:34:06","Site went down because Gen fail to start due to Gen starter rela=
y faulty // He bypassed hit and started the Gen manually","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Relay Faulty","Site went down =
because Gen fail to start due to Gen starter relay faulty // He bypassed hi=
t and started the Gen manually","franck.nkomot@matech-cameroun.com","314","=
09-09-2025 00:30:18","MATECH CMR"
"External Reconciliation","Site Down","T0290","IHS_YND_067","NOCINC00058610=
97","Nkoa Ayos","","08-09-2025 23:56:59","08-09-2025 23:55:46","09-09-2025 =
00:01:46","Grid outage, site went down because gen start an stopped due to =
water infiltration in tank // Grid returned","MINKA NICOLAS","Fuel Outage (=
Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","Gri=
d outage, site went down because gen start an stopped due to water infiltra=
tion in tank // Grid returned","franck.nkomot@matech-cameroun.com","74","08=
-09-2025 23:56:59","MATECH CMR"
"External Reconciliation","Site Down","CTR_661","IHS_YND_067","NOCINC000586=
0745","Nkoa Ayos","","08-09-2025 22:49:34","08-09-2025 22:44:24","08-09-202=
5 23:50:24","Grid outage, site went down because gen start an stopped due t=
o water infiltration in tank // Grid returned","MINKA NICOLAS","Fuel Outage=
 (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","G=
rid outage, site went down because gen start an stopped due to water infilt=
ration in tank // Grid returned","franck.nkomot@matech-cameroun.com","312",=
"08-09-2025 22:49:34","MATECH CMR"
"Internal Reconciliation","Site Down","T1744","IHS_YND_556","NOCINC00058600=
28","NKOMKANA ELIZA HOTEL","","08-09-2025 20:42:34","08-09-2025 20:34:24","=
08-09-2025 21:56:26","Grid only no space // grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid only no space // =
grid return","kamga.virgile@ihstowers.com","492","08-09-2025 20:42:34","MAT=
ECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058596=
48","Messa Carriere","","08-09-2025 19:37:16","08-09-2025 19:34:07","08-09-=
2025 19:46:14","Site went down due to insufficiency of rectifiers//site sta=
bilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficiency of rectifiers//site stabilis=
ed","edwige.kapawo@matech-cameroun.com","191","08-09-2025 19:37:16","MATECH=
 CMR"
"Internal Reconciliation","Site Down","CTR_149","IHS_YND_517","NOCINC000585=
9326","Montee-Des-Soeurs","","08-09-2025 18:44:06","08-09-2025 18:39:55","0=
9-09-2025 15:04:55","Grid outage ,site went down due to Gen overload (15 KV=
A/210 A); Grid returned","Hyemafo Gildas","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Grid outage ,site went down due to Gen overload (=
15 KVA/210 A); Grid returned","vanel.mbiada@matech-cameroun.com","253","08-=
09-2025 18:44:06","MATECH CMR"
"External Reconciliation","Site Down","CTR_161","IHS_YND_506","NOCINC000585=
9322","Omnisport-Rail","","08-09-2025 18:43:22","08-09-2025 18:40:52","08-0=
9-2025 18:51:38","No power issue site on grid with U=3D53.4v,Armand Nguetsa=
 from Huawei is informed.","Delor Telezing","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on grid with U=3D53.4v,Armand Nguetsa from Huawei is informed.","vanel.mbi=
ada@matech-cameroun.com","152","08-09-2025 18:43:22","MATECH CMR"
"External Reconciliation","Site Down","CTR_335","IHS_YND_474","NOCINC000585=
9056","Yoko OCM","","08-09-2025 18:05:23","08-09-2025 17:59:05","08-09-2025=
 18:06:57","Site went down due to insufficiency rectifiers on site// He res=
et site on Grid","Parker Tchoup","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to insufficiency rectifiers on site//=
 He reset site on Grid","vanel.mbiada@matech-cameroun.com","379","08-09-202=
5 18:05:23","MATECH CMR"
"External Reconciliation","Site Down","CTR_240","IHS_YND_021","NOCINC000585=
8316","C-Supreme","","08-09-2025 16:29:01","08-09-2025 16:24:57","08-09-202=
5 19:26:57","No power issue, U =3D 54.4 V on grid","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue, U =3D 54.4 V on grid","alexandre.kamal@ihstowers.com","245","08-09-2=
025 16:29:01","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_762","NOCINC0005858035","=
Nkolfon Cimencam","","08-09-2025 15:49:48","08-09-2025 15:46:15","08-09-202=
5 16:01:20","Cascaded Incident from TTO6078830","Hyemafo Gildas","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Felix zambe (IHS) on =
site work with orange teams//End work ","vanel.mbiada@matech-cameroun.com",=
"213","08-09-2025 15:49:48","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_257","NOCINC0005858034","=
Ahala","","08-09-2025 15:49:47","08-09-2025 15:46:15","08-09-2025 16:01:20"=
,"Cascaded Incident from TTO6078830","Hyemafo Gildas","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Felix zambe (IHS) on site work w=
ith orange teams//End work ","vanel.mbiada@matech-cameroun.com","212","08-0=
9-2025 15:49:47","MATECH CMR"
"External Reconciliation","Site Down","CTR_320","IHS_YND_282","NOCINC000585=
8026","Meyo","IHS_YND_257, IHS_YND_762","08-09-2025 15:48:42","08-09-2025 1=
5:46:15","08-09-2025 16:09:12","Felix zambe (IHS) on site work with orange =
teams//End work ","Hyemafo Gildas","Installation Activity","Passive","Plann=
ed Activity","Installation Activity","Felix zambe (IHS) on site work with o=
range teams//End work ","vanel.mbiada@matech-cameroun.com","148","08-09-202=
5 15:48:42","MATECH CMR"
"External Reconciliation","Site Down","CTR_016","IHS_YND_226","NOCINC000585=
7489","Mvog-Betsi","","08-09-2025 14:26:55","08-09-2025 14:24:48","08-09-20=
25 15:16:33","Grid fluctuation, Site went down because Gen failed to start =
due to Grid bad voltage // Grid stabilized","Hyemafo Gildas","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
n, Site went down because Gen failed to start due to Grid bad voltage // Gr=
id stabilized","vanel.mbiada@matech-cameroun.com","128","08-09-2025 14:26:5=
5","MATECH CMR"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000585=
7456","CNR","","08-09-2025 14:21:06","08-09-2025 14:17:57","08-09-2025 18:0=
2:58","(Unstable)Site went down due to insufficiency of rectifiers// Grid r=
eturn ","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","(Unstable)Site went down due to insufficiency of rectifiers// Gri=
d return ","vanel.mbiada@matech-cameroun.com","190","08-09-2025 14:21:06","=
MATECH CMR"
"External Reconciliation","Site Down","CTR_973","IHS_YND_796","NOCINC000585=
7429","Nkoabang Ebolmedjock","","08-09-2025 14:15:28","08-09-2025 14:12:21"=
,"08-09-2025 14:17:04","Active//No power issue, Site on Gen. Notice that it=
 is impacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare H=
erve","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matec=
h-cameroun.com","189","08-09-2025 14:15:28","MATECH CMR"
"External Reconciliation","Site Down","T1103","IHS_YND_242","NOCINC00058573=
35","Mballa 4","","08-09-2025 13:59:04","08-09-2025 13:52:48","08-09-2025 1=
4:31:16","site went down because gen start an stopped due to water infiltra=
tion in tank // He purged The tank and Gen manually started","Delor Telezin=
g","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water =
In The Fuel","site went down because gen start an stopped due to water infi=
ltration in tank // He purged The tank and Gen manually started","cedric.ti=
ani@matech-cameroun.com","377","08-09-2025 13:59:04","MATECH CMR"
"External Reconciliation","Site Down","CTR_414","IHS_YND_202","NOCINC000585=
7094","Cite-Verte","","08-09-2025 13:23:53","08-09-2025 13:08:32","08-09-20=
25 17:53:49","Grid outage // Grid return","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid outage // Grid return","kouoh.je=
an@ihstowers.com","922","08-09-2025 13:23:53","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_409","IHS_YND_090","NOCINC000585=
7056","BATA-Mokolo","","08-09-2025 13:23:09","08-09-2025 13:21:02","09-09-2=
025 01:10:37","Insufficiency of rectifiers","","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module","(Unstable)Site went down due to insufficie=
ncy of rectifiers // Site stabilised","kouoh.jean@ihstowers.com","130","08-=
09-2025 13:23:09","MATECH CMR"
"External Reconciliation","Site Down","CTR_080","IHS_YND_298","NOCINC000585=
6943","Olembe","","08-09-2025 13:02:01","08-09-2025 13:00:45","08-09-2025 1=
3:33:26","Grid fluctuation, Site went down because Gen failed to start due =
to Grid bad voltage // We bypass grid and gen manually started ","Fabrice P=
ouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, Site went down because Gen failed to start due to =
Grid bad voltage // We bypass grid and gen manually started ","cedric.tiani=
@matech-cameroun.com","78","08-09-2025 13:02:01","MATECH CMR"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000585=
6716","CNR","","08-09-2025 12:29:10","08-09-2025 12:24:01","08-09-2025 13:5=
0:10","(Unstable)Site went down due to insufficiency of rectifiers // Site =
stabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Recti=
fier Module","(Unstable)Site went down due to insufficiency of rectifiers /=
/ Site stabilised","gerard.tchangoue@matech-cameroun.com","311","08-09-2025=
 12:29:10","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_694","NOCINC0005856683","=
ETOUDI CHAPELLE","","08-09-2025 12:22:46","08-09-2025 11:57:13","08-09-2025=
 12:44:28","Cascaded Incident from TTO6077237","Delor Telezing","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Site went down because=
 Gen started and stopped with alarm *low oil pressure*//He added oil and st=
arted the Gen manually","gerard.tchangoue@matech-cameroun.com","1533","08-0=
9-2025 12:22:46","MATECH CMR"
"External Reconciliation","Site Down","CTR_104","IHS_YND_244","NOCINC000585=
6602","Abattoir","","08-09-2025 12:09:22","08-09-2025 12:08:04","08-09-2025=
 14:31:00","Grid outage,Site went down due to Gen overload (20KVA//295A) SS=
 HIS Bernard Atangana is informed and confirmed//Grid return","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
,Site went down due to Gen overload (20KVA//295A) SS HIS Bernard Atangana i=
s informed and confirmed//Grid return","cedric.tiani@matech-cameroun.com","=
80","08-09-2025 12:09:22","MATECH CMR"
"External Reconciliation","Site Down","CTR_086","IHS_YND_211","NOCINC000585=
6580","Etoudi 2","IHS_YND_694","08-09-2025 12:06:27","08-09-2025 11:57:13",=
"08-09-2025 12:53:23","Site went down because Gen started and stopped with =
alarm *low oil pressure*//He added oil and started the Gen manually","Fabri=
ce Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressur=
e","Site went down because Gen started and stopped with alarm *low oil pres=
sure*//He added oil and started the Gen manually","gerard.tchangoue@matech-=
cameroun.com","555","08-09-2025 12:06:27","MATECH CMR"
"External Reconciliation","Site Down","T0394","IHS_YND_241","NOCINC00058565=
27","Etoudi","","08-09-2025 11:59:10","08-09-2025 11:56:50","08-09-2025 12:=
49:29","Grid outage .site went down due to gen overload(20kva,300 A) SS HIS=
 Bernard Atangana is informed//He reduiced the load and started the Gen man=
ually","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage .site went down due to gen overload(20kva,300 A) SS HI=
S Bernard Atangana is informed//He reduiced the load and started the Gen ma=
nually","cedric.tiani@matech-cameroun.com","141","08-09-2025 11:59:10","MAT=
ECH CMR"
"External Reconciliation","Site Down","T1744","IHS_YND_556","NOCINC00058565=
16","NKOMKANA ELIZA HOTEL","","08-09-2025 11:55:34","08-09-2025 11:40:27","=
08-09-2025 14:30:27","Grid outage, no space // awaiting grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outag=
e /grid return","landry.etame@ihstowers.com","908","08-09-2025 11:55:34","M=
ATECH CMR"
"External Reconciliation","Site Down","CTR_086","IHS_YND_211","NOCINC000585=
6162","Etoudi 2","","08-09-2025 11:01:24","08-09-2025 10:56:51","08-09-2025=
 11:02:31","Site went down because Gen started and stopped with alarm *low =
oil pressure*//He added oil and started the Gen manually","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Site we=
nt down because Gen started and stopped with alarm *low oil pressure*//He a=
dded oil and started the Gen manually","gerard.tchangoue@matech-cameroun.co=
m","274","08-09-2025 11:01:24","MATECH CMR"
"External Reconciliation","Site Down","T0056","IHS_YND_189","NOCINC00058561=
43","Paradis Hotel","","08-09-2025 10:57:43","08-09-2025 10:56:27","08-09-2=
025 12:16:23","Site went down due to Fuel shoetage // Refueling done","Sili=
gap Boris","Fuel Outage","Passive","Diesel","Diesel Outage","Site went down=
 due to Fuel shoetage // Refueling done","cedric.tiani@matech-cameroun.com"=
,"78","08-09-2025 10:57:43","MATECH CMR"
"External Reconciliation","Site Down","T0237","IHS_YND_302","NOCINC00058560=
61","Nkolndom","","08-09-2025 10:44:36","08-09-2025 10:43:28","08-09-2025 1=
0:52:51","Site went down due to lightning which burned  cable of ATS burned=
 and  damaged powercom //W bypass powercom and normalize cables and site on=
 gen ","Fabrice Pouakam","Force Majeure","Natural Disaster","Thunderstrike"=
,"Equipment Damaged","Site went down due to lightning which burned  cable o=
f ATS burned and  damaged powercom //W bypass powercom and normalize cables=
 and site on gen ","cedric.tiani@matech-cameroun.com","69","08-09-2025 10:4=
4:36","MATECH CMR"
"External Reconciliation","Site Down","T0920","IHS_YND_416","NOCINC00058558=
19","Ngwopi Boga","","08-09-2025 09:58:29","08-09-2025 09:53:18","08-09-202=
5 10:27:22","No power issue, site is on battery  with Ubaie(Threshold=3D49.=
7V); TX FME Etienne Fopa (693961474) from HUAWEI is informed","Kemeni Frank=
lin","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue, site is on battery  with Ubaie(Threshold=
=3D49.7V); TX FME Etienne Fopa (693961474) from HUAWEI is informed","cedric=
.tiani@matech-cameroun.com","312","08-09-2025 09:58:29","MATECH CMR"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000585=
5731","CNR","","08-09-2025 09:44:08","08-09-2025 09:41:49","08-09-2025 11:3=
2:49","(Unstable)Site went down due to insufficiency of rectifiers // Site =
stabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Recti=
fier Module","(Unstable)Site went down due to insufficiency of rectifiers /=
/ Site stabilised","gerard.tchangoue@matech-cameroun.com","140","08-09-2025=
 09:44:08","MATECH CMR"
"External Reconciliation","Site Down","T3230","IHS_YND_745","NOCINC00058556=
22","Okolo Kilombo","","08-09-2025 09:23:02","08-09-2025 09:18:43","08-09-2=
025 10:10:46","Site went down due  to PWC dysfunction on site //He reset it=
 and started the Gen manually ","Fabrice Pouakam","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due  to PWC d=
ysfunction on site //He reset it and started the Gen manually ","cedric.tia=
ni@matech-cameroun.com","260","08-09-2025 09:23:02","MATECH CMR"
"External Reconciliation","Site Down","CTR_086","IHS_YND_211","NOCINC000585=
5565","Etoudi 2","","08-09-2025 09:13:02","08-09-2025 08:31:41","08-09-2025=
 10:37:24","Site went down because Gen started and stopped with alarm *low =
oil pressure*//He added oil and started the Gen manually","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Site we=
nt down because Gen started and stopped with alarm *low oil pressure*//He a=
dded oil and started the Gen manually","gerard.tchangoue@matech-cameroun.co=
m","2482","08-09-2025 09:13:02","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_242","NOCINC0005855427","=
Mballa 4","","08-09-2025 08:45:14","08-09-2025 08:34:06","08-09-2025 09:34:=
55","Cascaded Incident from TTO6075927","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage,site went down be=
cause Gen failed to start due to AVR faulty//He replaced it and site on GEN=
","gerard.tchangoue@matech-cameroun.com","668","08-09-2025 08:45:14","MATEC=
H CMR"
"External Reconciliation","Site Down","CTR_213","IHS_YND_247","NOCINC000585=
5378","Okolo","IHS_YND_242, IHS_YND_274, IHS_YND_279, IHS_YND_685","08-09-2=
025 08:35:14","08-09-2025 08:34:06","08-09-2025 09:34:55","Grid outage,site=
 went down because Gen failed to start due to AVR faulty//He replaced it an=
d site on GEN","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - AVR","Grid outage,site went down because Gen failed to start due to A=
VR faulty//He replaced it and site on GEN","gerard.tchangoue@matech-camerou=
n.com","69","08-09-2025 08:35:14","MATECH CMR"
"External Reconciliation","Site Down","T0760","IHS_YND_419","NOCINC00058553=
77","Ngog Mapubi","","08-09-2025 08:35:09","08-09-2025 08:28:59","08-09-202=
5 10:42:07","Site went down because Gen started and stopped with   alarm *E=
mergency stop*//He reset it and site on Gen","Kemeni Franklin","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Site went down because =
Gen started and stopped with   alarm *Emergency stop*//He reset it and site=
 on Gen","cedric.tiani@matech-cameroun.com","371","08-09-2025 08:35:09","MA=
TECH CMR"
"Internal Reconciliation","Site Down","CTR_093","IHS_YND_188","NOCINC000585=
5358","H-Paradis","","08-09-2025 08:29:22","08-09-2025 08:24:06","08-09-202=
5 14:24:08","Grid only , No space to deploy // Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid only , No spac=
e to deploy // Grid return","gerard.tchangoue@matech-cameroun.com","317","0=
8-09-2025 08:29:22","MATECH CMR"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000585=
5311","CNR","","08-09-2025 08:17:46","08-09-2025 08:14:39","08-09-2025 09:3=
6:29","(Unstable)Site went down due to insufficiency of rectifiers // Site =
stabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Recti=
fier Module","(Unstable)Site went down due to insufficiency of rectifiers /=
/ Site stabilised","gerard.tchangoue@matech-cameroun.com","189","08-09-2025=
 08:17:46","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_542","NOCINC0005855216","=
SAA Entrance","","08-09-2025 08:00:09","08-09-2025 07:42:50","08-09-2025 07=
:47:58","Cascaded Incident from TTO6075651","Parker Tchoup","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue on site ,site =
on Gen with Ubaie =3D53.1V The Tx Technician from Huawei Gr=E9goire//654547=
479 is informed","cedric.tiani@matech-cameroun.com","1039","08-09-2025 08:0=
0:09","MATECH CMR"
"External Reconciliation","Site Down","T0601","IHS_YND_098","NOCINC00058551=
70","Ekounou","","08-09-2025 07:51:30","08-09-2025 07:49:19","08-09-2025 08=
:35:07","Site went down because Gen failed to start due to preheating syste=
m alarming//He reset it and site on Gen","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Site went down because Gen fa=
iled to start due to preheating system alarming//He reset it and site on Ge=
n","cedric.tiani@matech-cameroun.com","133","08-09-2025 07:51:30","MATECH C=
MR"
"External Reconciliation","Site Down","T1620","IHS_YND_405","NOCINC00058551=
24","Saa","IHS_YND_542","08-09-2025 07:43:58","08-09-2025 07:42:50","08-09-=
2025 07:47:58","No power issue on site ,site on Gen with Ubaie =3D53.1V The=
 Tx Technician from Huawei Gr=E9goire//654547479 is informed","Parker Tchou=
p","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue on site ,site on Gen with Ubaie =3D53.1V The =
Tx Technician from Huawei Gr=E9goire//654547479 is informed","cedric.tiani@=
matech-cameroun.com","70","08-09-2025 07:43:58","MATECH CMR"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000585=
5112","CNR","","08-09-2025 07:41:00","08-09-2025 07:36:28","08-09-2025 08:1=
0:28","Site went down due to insufficiency of rectifiers // Site stabilised=
","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficiency of rectifiers // Site stabilised","=
gerard.tchangoue@matech-cameroun.com","274","08-09-2025 07:41:00","MATECH C=
MR"
"External Reconciliation","Site Down","T1241","IHS_YND_794","NOCINC00058550=
81","Nkoulou Carriere carrefourt","","08-09-2025 07:36:35","08-09-2025 07:3=
3:24","08-09-2025 09:05:14","Site went down because 02/05 rectifiers on sit=
e alarming//he reset it and stsrted the Gen manually","Mba Lazare Herve","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went down b=
ecause 02/05 rectifiers on site alarming//he reset it and stsrted the Gen m=
anually","cedric.tiani@matech-cameroun.com","193","08-09-2025 07:36:35","MA=
TECH CMR"
"External Reconciliation","Site Down","T0457","IHS_YND_246","NOCINC00058550=
65","Emana","","08-09-2025 07:31:00","08-09-2025 07:27:48","08-09-2025 09:3=
4:17","Site went down  due to CB gen disjuncted causing by lightning//CB re=
armed and site on gen","Fabrice Pouakam","Force Majeure","Natural Disaster"=
,"Thunderstrike","Equipment Damaged","Site went down  due to CB gen disjunc=
ted causing by lightning//CB rearmed and site on gen","cedric.tiani@matech-=
cameroun.com","193","08-09-2025 07:31:00","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_802","NOCINC0005855019","=
NYOM FACE MAETUR","","08-09-2025 07:27:54","08-09-2025 07:12:59","08-09-202=
5 08:35:24","Cascaded Incident from TTO6075485","Fabrice Pouakam","Cascade =
Outage","Passive","Cascade Passive","Cascade Passive","Site went down due t=
o lightning which burned cable of ATS burned and damaged powercom //W bypas=
s powercom and normalize cables and site on gen","cedric.tiani@matech-camer=
oun.com","895","08-09-2025 07:27:54","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_274","NOCINC0005855018","=
Emana Lycee","","08-09-2025 07:27:54","08-09-2025 07:12:59","08-09-2025 09:=
34:55","Cascaded Incident from TTO6075485","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage,site went dow=
n because Gen failed to start due to AVR faulty//He replaced it and site on=
 GEN","cedric.tiani@matech-cameroun.com","895","08-09-2025 07:27:54","MATEC=
H CMR"
"External Reconciliation","Site Down","","IHS_YND_306","NOCINC0005855017","=
Nkozoa","","08-09-2025 07:27:53","08-09-2025 07:12:59","08-09-2025 08:35:24=
","Cascaded Incident from TTO6075485","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to lightnin=
g which burned cable of ATS burned and damaged powercom //W bypass powercom=
 and normalize cables and site on gen","cedric.tiani@matech-cameroun.com","=
894","08-09-2025 07:27:53","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_280","NOCINC0005854986","=
Messassi 2","","08-09-2025 07:22:16","08-09-2025 07:12:59","08-09-2025 08:3=
5:24","Cascaded Incident from TTO6075485","Fabrice Pouakam","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down due to ligh=
tning which burned cable of ATS burned and damaged powercom //W bypass powe=
rcom and normalize cables and site on gen","cedric.tiani@matech-cameroun.co=
m","557","08-09-2025 07:22:16","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_799","NOCINC0005854988","=
Messassi Ngonlonk","","08-09-2025 07:22:16","08-09-2025 07:12:59","08-09-20=
25 08:35:24","Cascaded Incident from TTO6075485","Fabrice Pouakam","Cascade=
 Outage","Passive","Cascade Passive","Cascade Passive","Site went down due =
to lightning which burned cable of ATS burned and damaged powercom //W bypa=
ss powercom and normalize cables and site on gen","cedric.tiani@matech-came=
roun.com","557","08-09-2025 07:22:16","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_304","NOCINC0005854989","=
Nkolondom","","08-09-2025 07:22:16","08-09-2025 07:12:59","08-09-2025 08:35=
:24","Cascaded Incident from TTO6075485","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to light=
ning which burned cable of ATS burned and damaged powercom //W bypass power=
com and normalize cables and site on gen","cedric.tiani@matech-cameroun.com=
","557","08-09-2025 07:22:16","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_685","NOCINC0005854984","=
Emana lycee 2","","08-09-2025 07:22:15","08-09-2025 07:12:59","08-09-2025 0=
9:34:55","Cascaded Incident from TTO6075485","Fabrice Pouakam","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Grid outage,site went d=
own because Gen failed to start due to AVR faulty//He replaced it and site =
on GEN","cedric.tiani@matech-cameroun.com","556","08-09-2025 07:22:15","MAT=
ECH CMR"
"External Reconciliation","Site Down","","IHS_YND_761","NOCINC0005854985","=
Djonassi-Yde","","08-09-2025 07:22:15","08-09-2025 07:12:59","08-09-2025 08=
:35:24","Cascaded Incident from TTO6075485","Fabrice Pouakam","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down due to li=
ghtning which burned cable of ATS burned and damaged powercom //W bypass po=
wercom and normalize cables and site on gen","cedric.tiani@matech-cameroun.=
com","556","08-09-2025 07:22:15","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_316","NOCINC0005854983","=
Akak-Nkozoa-MTN-IHS","","08-09-2025 07:22:15","08-09-2025 07:12:59","08-09-=
2025 08:35:24","Cascaded Incident from TTO6075485","Fabrice Pouakam","Casca=
de Outage","Passive","Cascade Passive","Cascade Passive","Site went down du=
e to lightning which burned cable of ATS burned and damaged powercom //W by=
pass powercom and normalize cables and site on gen","cedric.tiani@matech-ca=
meroun.com","556","08-09-2025 07:22:15","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_298","NOCINC0005854982","=
Olembe","","08-09-2025 07:22:15","08-09-2025 07:12:59","08-09-2025 08:35:24=
","Cascaded Incident from TTO6075485","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to lightnin=
g which burned cable of ATS burned and damaged powercom //W bypass powercom=
 and normalize cables and site on gen","cedric.tiani@matech-cameroun.com","=
556","08-09-2025 07:22:15","MATECH CMR"
"External Reconciliation","Site Down","T0237","IHS_YND_302","NOCINC00058549=
71","Nkolndom","IHS_YND_298, IHS_YND_316, IHS_YND_685, IHS_YND_761, IHS_YND=
_306, IHS_YND_274, IHS_YND_220, IHS_YND_280, IHS_YND_799, IHS_YND_802, IHS_=
YND_304, IHS_YND_299","08-09-2025 07:19:23","08-09-2025 07:12:59","08-09-20=
25 08:35:24","Site went down due to lightning which burned cable of ATS bur=
ned and damaged powercom //W bypass powercom and normalize cables and site =
on gen","Fabrice Pouakam","Force Majeure","Natural Disaster","Thunderstrike=
","Equipment Damaged","Site went down due to lightning which burned cable o=
f ATS burned and damaged powercom //W bypass powercom and normalize cables =
and site on gen","cedric.tiani@matech-cameroun.com","384","08-09-2025 07:19=
:23","MATECH CMR"
"External Reconciliation","Site Down","T0417-1","IHS_YND_220","NOCINC000585=
4925","Golf Quater","","08-09-2025 07:11:38","08-09-2025 07:12:59","08-09-2=
025 08:35:24","","Mboua Thierry","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Site went down due to lightning which burned cable of=
 ATS burned and damaged powercom //W bypass powercom and normalize cables a=
nd site on gen","cedric.tiani@matech-cameroun.com","630","08-09-2025 07:11:=
38","MATECH CMR"
"External Reconciliation","Site Down","CTR_441","IHS_YND_687","NOCINC000585=
4883","OLAMA","","08-09-2025 07:04:13","08-09-2025 06:59:02","08-09-2025 07=
:10:11","Active // No power issue on site Ubaie: 54.6V site on Gen The TX F=
ME Henri (699949693) from Huawei is informed","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue on site Ubaie: 54.6V site on Gen The TX FME Henri (69=
9949693) from Huawei is informed","cedric.tiani@matech-cameroun.com","312",=
"08-09-2025 07:04:13","MATECH CMR"
"External Reconciliation","Site Down","T0237","IHS_YND_302","NOCINC00058548=
39","Nkolndom","","08-09-2025 06:51:50","08-09-2025 06:47:42","08-09-2025 0=
7:00:34","Site went down due to lightning which burned  cable of ATS burned=
 and  damaged powercom //W bypass powercom and normalize cables and site on=
 gen ","Fabrice Pouakam","Force Majeure","Natural Disaster","Thunderstrike"=
,"Equipment Damaged","Site went down due to lightning which burned  cable o=
f ATS burned and  damaged powercom //W bypass powercom and normalize cables=
 and site on gen ","cedric.tiani@matech-cameroun.com","249","08-09-2025 06:=
51:50","MATECH CMR"
"External Reconciliation","Site Down","CTR_185","IHS_YND_378","NOCINC000585=
4825","Eseka Town","","08-09-2025 06:50:57","08-09-2025 06:49:42","08-09-20=
25 07:11:51","Grid outage,site went down due to Gen card dysfunction//He re=
set it and stsrted the Gen manually","Kemeni Franklin","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down due =
to Gen card dysfunction//He reset it and stsrted the Gen manually","cedric.=
tiani@matech-cameroun.com","77","08-09-2025 06:50:57","MATECH CMR"
"External Reconciliation","Site Down","CTR_234","IHS_YND_415","NOCINC000585=
4819","Boga-Mahole","","08-09-2025 06:49:27","08-09-2025 06:40:59","08-09-2=
025 11:02:07","Site went down because Gen failed to stsrt  due to Gen card =
 faulty //He manually started the Gen","Kemeni Franklin","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Site went down because Gen fa=
iled to stsrt  due to Gen card  faulty //He manually started the Gen","cedr=
ic.tiani@matech-cameroun.com","509","08-09-2025 06:49:27","MATECH CMR"
"External Reconciliation","Site Down","CTR_160","IHS_YND_523","NOCINC000585=
4700","EMANA BILICK CITY","","08-09-2025 06:14:54","08-09-2025 05:54:42","0=
8-09-2025 10:07:07","Grid outage,site behaves as Grid only site (Gen Noise)=
//Grid return","Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord=
 Related Issues","Access Issue - Land Lord","Grid outage,site behaves as Gr=
id only site (Gen Noise)//Grid return","gerard.tchangoue@matech-cameroun.co=
m","1681","08-09-2025 06:14:54","MATECH CMR"
"External Reconciliation","Site Down","T1665","IHS_YND_014","NOCINC00058545=
63","ELIg-Essono","","08-09-2025 05:33:05","08-09-2025 05:30:51","08-09-202=
5 06:33:24","Grid outage,DG stopped due with alarm ""Gen short circuit""( u=
nprouven Alarm ) // He reset gen card and Gen manually start","Delor Telezi=
ng","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage,DG stopped due with alarm ""Gen short circuit""( unprouven Alarm ) // =
He reset gen card and Gen manually start","edwige.kapawo@matech-cameroun.co=
m","135","08-09-2025 05:33:05","MATECH CMR"
"External Reconciliation","Site Down","T0649","IHS_YND_279","NOCINC00058545=
39","Messassi okolo","","08-09-2025 05:24:22","08-09-2025 04:53:59","08-09-=
2025 09:34:55","Site went down due to pwc Huawei dysfunction //He reset it =
and site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site went down due to pwc Huawei dysfuncti=
on //He reset it and site on Grid","edwige.kapawo@matech-cameroun.com","182=
4","08-09-2025 05:24:22","MATECH CMR"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000585=
4349","CNR","","08-09-2025 04:18:07","08-09-2025 04:09:59","08-09-2025 07:3=
2:39","Site went down due to insufficiency of rectifiers // Site stabilised=
","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficiency of rectifiers // Site stabilised","=
gerard.tchangoue@matech-cameroun.com","489","08-09-2025 04:18:07","MATECH C=
MR"
"External Reconciliation","Site Down","T1324","IHS_YND_307","NOCINC00058542=
88","Ebogo","","08-09-2025 03:49:22","08-09-2025 03:42:13","08-09-2025 06:0=
3:12","Active// No Power issue on site Ubaie 49.89V site on Grid, Julien /6=
93095849 from Huawei is informed","Siligap Boris","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No P=
ower issue on site Ubaie 49.89V site on Grid, Julien /693095849 from Huawei=
 is informed","edwige.kapawo@matech-cameroun.com","431","08-09-2025 03:49:2=
2","MATECH CMR"
"Internal Reconciliation","Site Down","T0636","IHS_YND_299","NOCINC00058542=
71","Olembe MTN","","08-09-2025 03:48:06","08-09-2025 03:43:54","08-09-2025=
 08:35:24","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Site went down due to lightning which burned cable of =
ATS burned and damaged powercom //W bypass powercom and normalize cables an=
d site on gen","edwige.kapawo@matech-cameroun.com","253","08-09-2025 03:48:=
06","MATECH CMR"
"External Reconciliation","Site Down","CTR_379","IHS_YND_277","NOCINC000585=
4268","Ngoulmekong-Nord","","08-09-2025 03:47:05","08-09-2025 01:53:32","08=
-09-2025 02:18:38","Site impacted by Eleveur","Siligap Boris","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","No power issue on site UB=
=3D51.1V site on Grid THE TX FME SYMPHORIEN (650257151) from HUAWEI is info=
rmed","gerard.tchangoue@matech-cameroun.com","7943","08-09-2025 03:47:05","=
MATECH CMR"
"External Reconciliation","Site Down","CTR_202","IHS_YND_370","NOCINC000585=
4044","Mom","IHS_YND_368, IHS_YND_369, IHS_YND_371, IHS_YND_372","08-09-202=
5 03:17:15","08-09-2025 03:08:53","08-09-2025 03:22:17","Site impacted by O=
TELE-CAMRAIL","Fanda Brice","Customer Equipment Failure","Active","Active E=
quipment Failure","Affected by 3rd Party Site","Site impacted by OTELE-CAMR=
AIL","gerard.tchangoue@matech-cameroun.com","504","08-09-2025 03:17:15","MA=
TECH CMR"
"External Reconciliation","Site Down","T0237","IHS_YND_302","NOCINC00058537=
97","Nkolndom","","08-09-2025 02:43:46","08-09-2025 02:43:32","08-09-2025 0=
6:37:17","Site went down due to lightning which burned  cable of ATS burned=
 and  damaged powercom //W bypass powercom and normalize cables and site on=
 gen ","Fabrice Pouakam","Force Majeure","Natural Disaster","Thunderstrike"=
,"Equipment Damaged","Site went down due to lightning which burned  cable o=
f ATS burned and  damaged powercom //W bypass powercom and normalize cables=
 and site on gen ","edwige.kapawo@matech-cameroun.com","14","08-09-2025 02:=
43:46","MATECH CMR"
"External Reconciliation","Site Down","T1665","IHS_YND_014","NOCINC00058537=
92","ELIg-Essono","","08-09-2025 02:42:52","08-09-2025 02:29:35","08-09-202=
5 05:03:47","Grid outage,DG stopped due with alarm ""Gen short circuit""( u=
nprouven Alarm ) // He reset gen card and Gen manually start","Delor Telezi=
ng","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage,DG stopped due with alarm ""Gen short circuit""( unprouven Alarm ) // =
He reset gen card and Gen manually start","edwige.kapawo@matech-cameroun.co=
m","798","08-09-2025 02:42:52","MATECH CMR"
"External Reconciliation","Site Down","CTR_211","IHS_YND_248","NOCINC000585=
3759","Biteng","","08-09-2025 02:40:43","08-09-2025 02:37:32","08-09-2025 0=
3:46:22","Active// No power issue, site on Batt with Ubaie=3D48.73V, Lionne=
l Steve (655184876/Huawei) is informed","Mba Lazare Herve","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power issue, site on Batt with Ubaie=3D48.73V, Lionnel Steve (65518=
4876/Huawei) is informed","gerard.tchangoue@matech-cameroun.com","193","08-=
09-2025 02:40:43","MATECH CMR"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000585=
3739","CNR","","08-09-2025 02:35:00","08-09-2025 02:33:53","08-09-2025 04:0=
4:30","Site went down due to insufficiency of rectifiers // Grid stabilised=
","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficiency of rectifiers // Grid stabilised","=
gerard.tchangoue@matech-cameroun.com","68","08-09-2025 02:35:00","MATECH CM=
R"
"Internal Reconciliation","Site Down","","IHS_YND_506","NOCINC0005853650","=
Omnisport-Rail","","08-09-2025 02:07:53","08-09-2025 01:58:21","08-09-2025 =
13:32:06","Cascaded Incident from TTO6074030","Delor Telezing","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Lightning struck and th=
e equipment was burned // Power issue already solved. , Huawei Team is invo=
lved.","gerard.tchangoue@matech-cameroun.com","572","08-09-2025 02:07:53","=
MATECH CMR"
"Internal Reconciliation","Site Down","","IHS_YND_509","NOCINC0005853651","=
MANGUIERS CHAPELLE","","08-09-2025 02:07:53","08-09-2025 01:58:21","08-09-2=
025 13:32:09","Cascaded Incident from TTO6074030","Fabrice Pouakam","Cascad=
e Outage","Passive","Cascade Passive","Cascade Passive","Lightning struck a=
nd the equipment was burned // Power issue already solved. , Huawei Team is=
 involved.","gerard.tchangoue@matech-cameroun.com","572","08-09-2025 02:07:=
53","MATECH CMR"
"Internal Reconciliation","Site Down","CTR_049","IHS_YND_209","NOCINC000585=
3643","Manguier","IHS_YND_506, IHS_YND_509","08-09-2025 02:03:45","08-09-20=
25 01:58:21","09-09-2025 15:45:45","Lightning struck and the equipment was =
burned","Fabrice Pouakam","Force Majeure","Natural Disaster","Thunderstrike=
","Equipment Damaged","Lightning struck and the equipment was burned // Pow=
er issue already solved. , Huawei Team and Armand ngeutsa  are  informed.."=
,"gerard.tchangoue@matech-cameroun.com","326","08-09-2025 02:03:45","MATECH=
 CMR"
"External Reconciliation","Site Down","CTR_254","IHS_YND_216","NOCINC000585=
3642","Eleveur","IHS_YND_277","08-09-2025 02:02:42","08-09-2025 01:53:32","=
08-09-2025 02:18:38","No power issue on site UB=3D51.1V site on Grid THE TX=
 FME SYMPHORIEN (650257151) from HUAWEI is informed","Siligap Boris","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site UB=3D51.1V site on Grid THE TX FME SYMPHORIEN =
(650257151) from HUAWEI is informed","gerard.tchangoue@matech-cameroun.com"=
,"551","08-09-2025 02:02:42","MATECH CMR"
"External Reconciliation","Site Down","CTR_622","IHS_YND_535","NOCINC000585=
3554","Awae Ewonkan","","08-09-2025 01:29:24","08-09-2025 01:22:13","08-09-=
2025 05:21:16","No power issue on site Tx issue U=3D48.49V site on Batt , t=
he FME TX Leonel Steve //655184876 from Huawei is informed","Albran Byorel"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue on site Tx issue U=3D48.49V site on Batt , the =
FME TX Leonel Steve //655184876 from Huawei is informed","gerard.tchangoue@=
matech-cameroun.com","434","08-09-2025 01:29:24","MATECH CMR"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000585=
3515","CNR","","08-09-2025 01:20:14","08-09-2025 01:18:01","08-09-2025 02:2=
0:28","Site went down due to insufficiency of rectifiers // Grid stabilised=
","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficiency of rectifiers // Grid stabilised","=
gerard.tchangoue@matech-cameroun.com","134","08-09-2025 01:20:14","MATECH C=
MR"
"External Reconciliation","Site Down","T0814","IHS_YND_274","NOCINC00058535=
14","Emana Lycee","","08-09-2025 01:20:09","08-09-2025 01:19:58","08-09-202=
5 01:21:04","Grid outage, site went down due to poor backup battery // Grid=
 returned","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, site went down due to poor backu=
p battery // Grid returned","edwige.kapawo@matech-cameroun.com","12","08-09=
-2025 01:20:09","MATECH CMR"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000585=
3371","CNR","","08-09-2025 00:31:33","08-09-2025 00:22:25","08-09-2025 00:4=
2:28","Site went down due to insufficiency of rectifiers // Grid stabilised=
","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficiency of rectifiers // grid stabilised","=
gerard.tchangoue@matech-cameroun.com","549","08-09-2025 00:31:33","MATECH C=
MR"
"External Reconciliation","Site Down","CTR_335","IHS_YND_474","NOCINC000585=
3240","Yoko OCM","","07-09-2025 23:51:41","07-09-2025 22:38:20","08-09-2025=
 06:34:31","Site went down due to  insufficiency  rectifiers on site//He ad=
ded 01 rectifier","Parker Tchoup","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site went down due to  insufficiency  rectifiers on sit=
e//He added 01 rectifier","gerard.tchangoue@matech-cameroun.com","4403","07=
-09-2025 23:51:41","MATECH CMR"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000585=
3078","CNR","","07-09-2025 23:01:21","07-09-2025 22:59:10","07-09-2025 23:0=
1:37","Site went down due to insufficiency of rectifiers  // grid stabilise=
d","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site went down due to insufficiency of rectifiers  // grid stabilised"=
,"gerard.tchangoue@matech-cameroun.com","132","07-09-2025 23:01:21","MATECH=
 CMR"
"External Reconciliation","Site Down","CTR_623","IHS_YND_515","NOCINC000585=
2774","Etoug ebe Meweulo","","07-09-2025 21:53:19","07-09-2025 21:50:10","0=
7-09-2025 22:34:28","Grid fluctuation site went down because Gen started an=
d stopped due to Grid bad voltage // He bypass Grid and put Site on Gen","H=
yemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation site went down because Gen started and stopp=
ed due to Grid bad voltage // He bypass Grid and put Site on Gen","vanel.mb=
iada@matech-cameroun.com","190","07-09-2025 21:53:19","MATECH CMR"
"External Reconciliation","Site Down","CTR_466","IHS_YND_271","NOCINC000585=
2536","Yona Hotel","","07-09-2025 21:11:31","07-09-2025 21:10:20","07-09-20=
25 21:12:07","Site went down because Gen failed to start due to Grid bad vo=
ltage on site // Grid stabilised","TIENTCHEU NZETCHIEU GAEL","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Site went down =
because Gen failed to start due to Grid bad voltage on site // Grid stabili=
sed","vanel.mbiada@matech-cameroun.com","73","07-09-2025 21:11:31","MATECH =
CMR"
"External Reconciliation","Site Down","T3217","IHS_YND_763","NOCINC00058523=
13","Nkolbisson usines des eaux 2","","07-09-2025 20:34:42","07-09-2025 20:=
31:34","07-09-2025 23:10:06","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Access issues due to landlo=
rd Grid outage gen failed to start due to automation malfunctionning//Gen m=
anually started ","cedric.tiani@matech-cameroun.com","2033","07-09-2025 20:=
34:42","MATECH CMR"
"External Reconciliation","Site Down","T3402","IHS_YND_285","NOCINC00058523=
07","Nkolbisson","IHS_YND_763","07-09-2025 20:33:43","07-09-2025 20:31:34",=
"07-09-2025 23:10:06","Access issues due to landlord Grid outage gen failed=
 to start due to automation malfunctionning//Gen manually started ","TIENTC=
HEU NZETCHIEU GAEL","Access Denial","Lease Or Legal","Landlord Related Issu=
es","Access Issue - Land Lord","Access issues due to landlord Grid outage g=
en failed to start due to automation malfunctionning//Gen manually started =
","cedric.tiani@matech-cameroun.com","130","07-09-2025 20:33:43","MATECH CM=
R"
"External Reconciliation","Site Down","T2829","IHS_YND_526","NOCINC00058522=
57","Nkoabang2","","07-09-2025 20:22:59","07-09-2025 20:17:49","07-09-2025 =
20:23:12","	Grid outage, site went down due to gen overload (22KVA, 330A), =
SS Blaise IHS is informed //site stabilised","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","	Grid outage, site went dow=
n due to gen overload (22KVA, 330A), SS Blaise IHS is informed //site stabi=
lised","cedric.tiani@matech-cameroun.com","312","07-09-2025 20:22:59","MATE=
CH CMR"
"External Reconciliation","Site Down","T2829","IHS_YND_526","NOCINC00058522=
18","Nkoabang2","","07-09-2025 20:14:07","07-09-2025 20:07:49","07-09-2025 =
20:16:36","Grid outage, site went down due to gen overload (22KVA, 330A), S=
S Blaise IHS is informed // Site stabilised","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down=
 due to gen overload (22KVA, 330A), SS Blaise IHS is informed // Site stabi=
lised","cedric.tiani@matech-cameroun.com","381","07-09-2025 20:14:07","MATE=
CH CMR"
"External Reconciliation","Site Down","T1394","IHS_YND_511","NOCINC00058522=
16","Etoug ebe Carrefour","","07-09-2025 20:14:02","07-09-2025 20:05:54","0=
7-09-2025 20:09:34","Site went down due to MPR dysfunction//Site stabilised=
","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Cabi=
net","Site went down due to MPR dysfunction//Site stabilised","ludivine.nga=
maleu@ihstowers.com","2536","07-09-2025 20:14:02","MATECH CMR"
"External Reconciliation","Site Down","T1834","IHS_YND_132","NOCINC00058521=
22","Manguiers Dispensaire","","07-09-2025 20:00:20","07-09-2025 19:55:08",=
"07-09-2025 20:17:12","Site went down because Gen failed to start due to ba=
d grid voltage // He bypass grid and Gen manually started","Fabrice Pouakam=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Site went down because Gen failed to start due to bad grid voltage // He b=
ypass grid and Gen manually started","cedric.tiani@matech-cameroun.com","31=
4","07-09-2025 20:00:20","MATECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058520=
79","Messa Carriere","","07-09-2025 19:53:02","07-09-2025 19:49:50","07-09-=
2025 19:55:15","Site went down due to insufficiency of rectifiers//site sta=
bilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficiency of rectifiers//site stabilis=
ed","cedric.tiani@matech-cameroun.com","194","07-09-2025 19:53:02","MATECH =
CMR"
"External Reconciliation","Site Down","T3217","IHS_YND_763","NOCINC00058516=
15","Nkolbisson usines des eaux 2","","07-09-2025 18:43:35","07-09-2025 18:=
41:39","07-09-2025 18:47:39","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","ccess issues due to lanlord=
 (Grid outage,Gen failed to start investigation ongoing)","cedric.tiani@mat=
ech-cameroun.com","1544","07-09-2025 18:43:35","MATECH CMR"
"External Reconciliation","Site Down","T3402","IHS_YND_285","NOCINC00058516=
11","Nkolbisson","IHS_YND_763","07-09-2025 18:42:50","07-09-2025 18:41:39",=
"07-09-2025 18:47:39","ccess issues due to lanlord (Grid outage,Gen failed =
to start investigation ongoing)","TIENTCHEU NZETCHIEU GAEL","Access Denial"=
,"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","cce=
ss issues due to lanlord (Grid outage,Gen failed to start investigation ong=
oing)","cedric.tiani@matech-cameroun.com","1541","07-09-2025 18:42:50","MAT=
ECH CMR"
"External Reconciliation","Site Down","CTR_599","IHS_YND_279","NOCINC000585=
1583","Messassi okolo","","07-09-2025 18:36:37","07-09-2025 18:33:28","07-0=
9-2025 18:51:59","Site went down due to pwc Huawei dysfunction //He reset i=
t and site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down due to pwc Huawei dysfunc=
tion //He reset it and site on Grid","vanel.mbiada@matech-cameroun.com","19=
2","07-09-2025 18:36:37","MATECH CMR"
"External Reconciliation","Site Down","CTR_160","IHS_YND_523","NOCINC000585=
1522","EMANA BILICK CITY","","07-09-2025 18:21:03","07-09-2025 18:18:49","0=
7-09-2025 18:49:57","Access issue in the site at night. Grid outage, site w=
ent down because site behaves as Grid only site (Gen Noise) // Grid return"=
,"Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord Related Issue=
s","Access Issue - Land Lord","Access issue in the site at night. Grid outa=
ge, site went down because site behaves as Grid only site (Gen Noise) // Gr=
id return","vanel.mbiada@matech-cameroun.com","136","07-09-2025 18:21:03","=
MATECH CMR"
"External Reconciliation","Site Down","T3217","IHS_YND_763","NOCINC00058514=
34","Nkolbisson usines des eaux 2","","07-09-2025 18:04:34","07-09-2025 18:=
00:42","07-09-2025 18:06:39","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Access issues due to lanlor=
d (Grid outage,Gen failed to start investigation ongoing)","cedric.tiani@ma=
tech-cameroun.com","267","07-09-2025 18:04:34","MATECH CMR"
"External Reconciliation","Site Down","T3402","IHS_YND_285","NOCINC00058514=
05","Nkolbisson","IHS_YND_763","07-09-2025 18:01:51","07-09-2025 18:00:42",=
"07-09-2025 18:06:39","Access issues due to lanlord (Grid outage,Gen failed=
 to start investigation ongoing)","TIENTCHEU NZETCHIEU GAEL","Access Denial=
","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Ac=
cess issues due to lanlord (Grid outage,Gen failed to start investigation o=
ngoing)","cedric.tiani@matech-cameroun.com","70","07-09-2025 18:01:51","MAT=
ECH CMR"
"External Reconciliation","Site Down","CTR_016","IHS_YND_226","NOCINC000585=
1122","Mvog-Betsi","","07-09-2025 17:13:32","07-09-2025 17:10:00","07-09-20=
25 17:35:42","Grid outage, site went down before gen start due to poor batt=
ery backup // Gen manual start","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen manual start","vanel.=
mbiada@matech-cameroun.com","213","07-09-2025 17:13:32","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_732","NOCINC0005851037","=
Nsam escale LP","","07-09-2025 16:57:39","07-09-2025 16:53:01","07-09-2025 =
16:59:27","Cascaded Incident from TTO6071065","","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down before Ge=
n start due to poor backup/ // Gen automatically started","cedric.tiani@mat=
ech-cameroun.com","278","07-09-2025 16:57:39","MATECH CMR"
"External Reconciliation","Site Down","T0476","IHS_YND_163","NOCINC00058510=
34","Nsam Sofavinc","IHS_YND_732","07-09-2025 16:57:14","07-09-2025 16:53:0=
1","07-09-2025 16:59:27","Grid outage, Site went down before Gen start due =
to poor backup/ // Gen automatically started","MINKA NICOLAS","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,=
 Site went down before Gen start due to poor backup/ // Gen automatically s=
tarted","cedric.tiani@matech-cameroun.com","255","07-09-2025 16:57:14","MAT=
ECH CMR"
"External Reconciliation","Site Down","CTR_471","IHS_YND_231","NOCINC000585=
1029","Nkolso","","07-09-2025 16:55:53","07-09-2025 16:54:37","07-09-2025 1=
7:58:07","Site went down because Gen started and stopped with alarm *Overcu=
rrent*//He reduiced 3 rack of battery and site on Gen","TIENTCHEU NZETCHIEU=
 GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Governor","Site went=
 down because Gen started and stopped with alarm *Overcurrent*//He reduiced=
 3 rack of battery and site on Gen","vanel.mbiada@matech-cameroun.com","77"=
,"07-09-2025 16:55:53","MATECH CMR"
"External Reconciliation","Site Down","T1569","IHS_YND_226","NOCINC00058509=
94","Mvog-Betsi","","07-09-2025 16:51:05","07-09-2025 16:50:57","07-09-2025=
 17:00:29","Grid fluctuation, Site went down because Gen failed to start du=
e to Grid bad voltage // Grid stabilized","Hyemafo Gildas","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,=
 Site went down because Gen failed to start due to Grid bad voltage // Grid=
 stabilized","cedric.tiani@matech-cameroun.com","9","07-09-2025 16:51:05","=
MATECH CMR"
"External Reconciliation","Site Down","CTR_471","IHS_YND_231","NOCINC000585=
0807","Nkolso","","07-09-2025 16:21:15","07-09-2025 16:19:05","07-09-2025 1=
6:34:30","Site went down because Gen started and stopped with alarm *Overcu=
rrent*//He reduiced 3 rack of battery and site on Gen","TIENTCHEU NZETCHIEU=
 GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Governor","Site went=
 down because Gen started and stopped with alarm *Overcurrent*//He reduiced=
 3 rack of battery and site on Gen","vanel.mbiada@matech-cameroun.com","131=
","07-09-2025 16:21:15","MATECH CMR"
"External Reconciliation","Site Down","T3402","IHS_YND_285","NOCINC00058507=
88","Nkolbisson","IHS_YND_763","07-09-2025 16:18:29","07-09-2025 16:14:20",=
"07-09-2025 16:58:57","Access issues due to lanlord (Grid outage,Gen failed=
 to start investigation ongoing)","TIENTCHEU NZETCHIEU GAEL","Access Denial=
","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Ac=
cess issues due to lanlord (Grid outage,Gen failed to start investigation o=
ngoing)","cedric.tiani@matech-cameroun.com","250","07-09-2025 16:18:29","MA=
TECH CMR"
"External Reconciliation","Site Down","T3217","IHS_YND_763","NOCINC00058507=
72","Nkolbisson usines des eaux 2","","07-09-2025 16:17:43","07-09-2025 16:=
14:20","07-09-2025 16:58:57","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Access issues due to lanlor=
d (Grid outage,Gen failed to start investigation ongoing)","cedric.tiani@ma=
tech-cameroun.com","291","07-09-2025 16:17:43","MATECH CMR"
"External Reconciliation","Site Down","T1744","IHS_YND_556","NOCINC00058505=
08","NKOMKANA ELIZA HOTEL","","07-09-2025 15:29:04","07-09-2025 15:24:08","=
07-09-2025 16:54:08","Grid outage ; No space to deploy MDG / Grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage ; No space to deploy MDG / Grid return","ludivine.ngamaleu@ihstowers=
.com","297","07-09-2025 15:29:04","MATECH CMR"
"External Reconciliation","Site Down","CTR_016","IHS_YND_226","NOCINC000585=
0499","Mvog-Betsi","","07-09-2025 15:26:42","07-09-2025 15:23:32","07-09-20=
25 15:33:38","Grid outage, Site went down because Gen failed to start due t=
o PWC ZTE disfunction// He reset it, Site on Gen","Hyemafo Gildas","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage=
, Site went down because Gen failed to start due to PWC ZTE disfunction// H=
e reset it, Site on Gen","vanel.mbiada@matech-cameroun.com","191","07-09-20=
25 15:26:42","MATECH CMR"
"External Reconciliation","Site Down","CTR_973","IHS_YND_796","NOCINC000585=
0183","Nkoabang Ebolmedjock","","07-09-2025 14:30:52","07-09-2025 14:29:38"=
,"07-09-2025 14:32:30","Active//No power issue, Site on Gen. Notice that it=
 is impacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare H=
erve","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matec=
h-cameroun.com","75","07-09-2025 14:30:52","MATECH CMR"
"External Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00058497=
19","Mokolo Yaounde","","07-09-2025 13:08:01","07-09-2025 08:11:43","07-09-=
2025 11:39:43","","","Grid Supply","Passive","Grid","National Grid - Grid O=
utage Issue","GRID OUTAGE /GRID RETURN","kamga.virgile@ihstowers.com","1778=
0","07-09-2025 13:08:01","MATECH CMR"
"External Reconciliation","Site Down","CTR_973","IHS_YND_796","NOCINC000584=
8928","Nkoabang Ebolmedjock","","07-09-2025 10:31:45","07-09-2025 10:30:29"=
,"07-09-2025 10:32:19","Site impacted by Nkolmesseng-Abom(CTR-711) Not Mana=
ged By IHS","Mba Lazare Herve","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Site impacted by Nkolmesseng-Abo=
m(CTR-711) Not Managed By IHS","gerard.tchangoue@matech-cameroun.com","78",=
"07-09-2025 10:31:45","MATECH CMR"
"External Reconciliation","Site Down","T1744","IHS_YND_556","NOCINC00058485=
39","NKOMKANA ELIZA HOTEL","","07-09-2025 09:18:33","07-09-2025 09:10:23","=
07-09-2025 09:30:23","","","Grid Supply","Passive","Grid","National Grid - =
Grid Outage Issue","grid outage /grid return","kamga.virgile@ihstowers.com"=
,"492","07-09-2025 09:18:33","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_732","NOCINC0005848501","=
Nsam escale LP","","07-09-2025 09:11:22","07-09-2025 09:07:34","07-09-2025 =
09:13:22","Cascaded Incident from TTO6068111","","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down before gen=
 started due to poor battery backup// Grid return","loic.noumsi@matech-came=
roun.com","228","07-09-2025 09:11:22","MATECH CMR"
"External Reconciliation","Site Down","T0476","IHS_YND_163","NOCINC00058484=
99","Nsam Sofavinc","IHS_YND_732","07-09-2025 09:11:00","07-09-2025 09:07:3=
4","07-09-2025 09:13:22","Grid outage site went down before gen started due=
 to poor battery backup// Grid return","MINKA NICOLAS","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site we=
nt down before gen started due to poor battery backup// Grid return","loic.=
noumsi@matech-cameroun.com","207","07-09-2025 09:11:00","MATECH CMR"
"Resolved","Warning","T0420","IHS_YND_082","NOCINC0005848426","Mokolo Yaoun=
de","","07-09-2025 08:52:49","","","Grid only, Grid Outage on site, no spac=
e to deploy MDGE // Grid return","","Warning","Warning","POWER","Warning - =
National Grid - Grid Outage Issue","Grid only, Grid Outage on site, no spac=
e to deploy MDGE // Grid return","kamga.virgile@ihstowers.com","1286","07-0=
9-2025 08:52:49","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_793","NOCINC0005848351","=
Eloumdem stade","","07-09-2025 08:32:51","07-09-2025 08:28:41","07-09-2025 =
09:32:34","Cascaded Incident from TTO6067931","Fanda Brice","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n because Gen failed to start due to alarm undervoltage // He reset DG Card=
, site on Gen","loic.noumsi@matech-cameroun.com","250","07-09-2025 08:32:51=
","MATECH CMR"
"External Reconciliation","Site Down","T0602","IHS_YND_259","NOCINC00058483=
44","Simbock MTN","IHS_YND_793","07-09-2025 08:31:51","07-09-2025 08:28:41"=
,"07-09-2025 09:32:34","Grid outage, site went down because Gen failed to s=
tart due to alarm overvoltage // He reset DG Card, site on Gen","Fanda Bric=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, site went down because Gen failed to start due to alarm undervoltage /=
/ He reset DG Card, site on Gen","loic.noumsi@matech-cameroun.com","191","0=
7-09-2025 08:31:51","MATECH CMR"
"External Reconciliation","Site Down","T0816","IHS_YND_260","NOCINC00058482=
91","Simbock Maetur","","07-09-2025 08:12:25","07-09-2025 08:08:16","07-09-=
2025 08:10:50","Active//No power Issue Site on Grid Ubaie =3D54.3V, The FME=
 The TX FME Fulbert (654266068) is informed.","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power Issue Site on Grid Ubaie =3D54.3V, The FME The TX FME Fulb=
ert (654266068) is informed.","loic.noumsi@matech-cameroun.com","250","07-0=
9-2025 08:12:25","MATECH CMR"
"Closed Complete","Warning","T0772","IHS_YND_207","NOCINC0005847401","ARMP =
Building","","07-09-2025 02:37:58","","","Site on battery at 48.7 V. The te=
chnician Thierry Mboua reports that no access at night // Grid return","Mbo=
ua Thierry","Warning","Warning","POWER","Warning - Site on Battery","Site o=
n battery at 48.7 V. The technician Thierry Mboua reports that no access at=
 night // Grid return","franck.nkomot@matech-cameroun.com","427","07-09-202=
5 02:37:58","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_372","NOCINC0005846987","=
Bondjock","","07-09-2025 00:17:26","06-09-2025 21:54:59","07-09-2025 01:43:=
59","Cascaded Incident from TTO6066211","Fanda Brice","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","BACKTRACKING. Grid outage, Site =
went down because Gen failed to start due to battery Gen discharged// He st=
arted Gen with external battery","christian.fonkou@ihstowers.com","8547","0=
7-09-2025 00:17:26","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_369","NOCINC0005846985","=
Mbeng","","07-09-2025 00:17:09","06-09-2025 21:54:59","07-09-2025 01:43:59"=
,"Cascaded Incident from TTO6066211","Fanda Brice","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Cascaded Incident from TTO6066211",=
"franck.nkomot@matech-cameroun.com","8530","07-09-2025 00:17:09","MATECH CM=
R"
"External Reconciliation","Site Down","","IHS_YND_531","NOCINC0005846963","=
OTELE MTN","","07-09-2025 00:13:15","06-09-2025 21:55:59","07-09-2025 01:43=
:59","Cascaded Incident from TTO6066180","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","BACKTRACKING. Grid outage, Site=
 went down because Gen failed to start due to battery Gen discharged// He s=
tarted Gen with external battery","franck.nkomot@matech-cameroun.com","8236=
","07-09-2025 00:13:15","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_370","NOCINC0005846964","=
Mom","","07-09-2025 00:13:15","06-09-2025 21:55:59","07-09-2025 01:43:59","=
Cascaded Incident from TTO6066180","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","BACKTRACKING. Grid outage, Site went =
down because Gen failed to start due to battery Gen discharged// He started=
 Gen with external battery","franck.nkomot@matech-cameroun.com","8236","07-=
09-2025 00:13:15","MATECH CMR"
"Closed Complete","Warning","T0029","IHS_YND_357","NOCINC0005846898","Sacre=
 Coeur Catholic Church","","06-09-2025 23:50:04","","","FME reports that si=
te alarming due to insufficiency of rectifiers","Mboua Thierry","Warning","=
Warning","POWER","Warning - Rectifier Module","FME reports that site alarmi=
ng due to insufficiency of rectifiers","franck.nkomot@matech-cameroun.com",=
"8395","06-09-2025 23:50:04","MATECH CMR"
"Closed Complete","Warning","T0370","IHS_YND_227","NOCINC0005846863","Mvog =
Betsi","","06-09-2025 23:41:59","","","The Site alarming on Grid with the l=
ack of one phase // FME Gildas reports that this site works like this","Hye=
mafo Gildas","Warning","Warning","POWER","Warning - AC Phase 1 Voltage low"=
,"The Site alarming on Grid with the lack of one phase // FME Gildas report=
s that this site works like this","franck.nkomot@matech-cameroun.com","6965=
","06-09-2025 23:41:59","MATECH CMR"
"External Reconciliation","Site Down","T0917","IHS_YND_371","NOCINC00058467=
49","Minka","IHS_YND_369, IHS_YND_372","06-09-2025 23:12:07","06-09-2025 21=
:54:59","07-09-2025 01:43:59","BACKTRACKING. Grid outage, Site went down be=
cause Gen failed to start due to Gen battery discharged// He started Gen wi=
th external battery","Fanda Brice","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Generator Battery","BACKTRACKING. Grid outage, Site went down becau=
se Gen failed to start due to Gen battery discharged// He started Gen with =
external battery","franck.nkomot@matech-cameroun.com","5053","06-09-2025 23=
:12:07","MATECH CMR"
"Closed Complete","Warning","CTR_207","IHS_YND_093","NOCINC0005845586","Cha=
pelle-Essos","","06-09-2025 19:38:22","","","High temps alarm. FME is on si=
te and report fault alarm//Site on air con","Delor Telezing","Warning","War=
ning","ENVIRONMENT","Warning - Aircon 1 on","High temps alarm. FME is on si=
te and report fault alarm//Site on air con","cedric.tiani@matech-cameroun.c=
om","4271","06-09-2025 19:38:22","MATECH CMR"
"Closed Complete","Warning","CTR_084","IHS_YND_294","NOCINC0005845573","Nko=
abang","","06-09-2025 19:37:14","","","High temps alarm. FME is on site and=
 report fault alarm//Site on air con","Mba Lazare Herve","Warning","Warning=
","ENVIRONMENT","Warning - Aircon 1 on","High temps alarm. FME is on site a=
nd report fault alarm//Site on air con","cedric.tiani@matech-cameroun.com",=
"5770","06-09-2025 19:37:14","MATECH CMR"
"External Reconciliation","Site Down","CTR_084","IHS_YND_294","NOCINC000584=
5552","Nkoabang","","06-09-2025 19:34:57","06-09-2025 18:01:57","06-09-2025=
 18:52:25","incorrectly logged ticket","Mba Lazare Herve","Incorrectly Logg=
ed Tickets","Error","Error","Error","incorrectly logged ticket","cedric.tia=
ni@matech-cameroun.com","5581","06-09-2025 19:34:57","MATECH CMR"
"External Reconciliation","Site Down","CTR_471","IHS_YND_231","NOCINC000584=
5470","Nkolso","","06-09-2025 19:18:39","06-09-2025 19:14:32","06-09-2025 1=
9:39:52","Site went down because Gen started and stopped with alarm *Overcu=
rrent*//He reduiced 3 rack of battery and site on Gen","TIENTCHEU NZETCHIEU=
 GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Site =
went down because Gen started and stopped with alarm *Overcurrent*//He redu=
iced 3 rack of battery and site on Gen","gerard.tchangoue@matech-cameroun.c=
om","248","06-09-2025 19:18:39","MATECH CMR"
"External Reconciliation","Site Down","CTR_271","IHS_YND_275","NOCINC000584=
5361","Nkolbong","","06-09-2025 19:03:55","06-09-2025 18:55:46","06-09-2025=
 20:58:33","Active/ No power issue on site Ubaie; 56V site on Gen, The FME =
TX Julien (+237 6 93 09 58 49) from Huawei is informed,","Delor Telezing","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active/ No power issue on site Ubaie; 56V site on Gen, The FME T=
X Julien (+237 6 93 09 58 49) from Huawei is informed,","gerard.tchangoue@m=
atech-cameroun.com","491","06-09-2025 19:03:55","MATECH CMR"
"External Reconciliation","Site Down","CTR_016","IHS_YND_226","NOCINC000584=
5346","Mvog-Betsi","","06-09-2025 19:00:29","06-09-2025 18:54:15","06-09-20=
25 19:02:23","Grid fluctuation site went down because Gen failed to start d=
ue to Grid bad voltage // He bypassed the Grid and site on Gen","Hyemafo Gi=
ldas","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation site went down because Gen failed to start due to Gri=
d bad voltage // He bypassed the Grid and site on Gen","gerard.tchangoue@ma=
tech-cameroun.com","375","06-09-2025 19:00:29","MATECH CMR"
"External Reconciliation","Site Down","CTR_149","IHS_YND_517","NOCINC000584=
5237","Montee-Des-Soeurs","","06-09-2025 18:35:04","06-09-2025 18:26:44","0=
6-09-2025 19:52:54","Active // No power issue, site is on Grid with Ubaie: =
54.5V, the fme Mbah hosiah (699699694 / Huawei) is informed.","Hyemafo Gild=
as","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active // No power issue, site is on Grid with Ubaie: 54.5V=
, the fme Mbah hosiah (699699694 / Huawei) is informed.","gerard.tchangoue@=
matech-cameroun.com","502","06-09-2025 18:35:04","MATECH CMR"
"External Reconciliation","Site Down","CTR_080","IHS_YND_298","NOCINC000584=
4840","Olembe","","06-09-2025 17:31:52","06-09-2025 17:30:42","06-09-2025 1=
8:03:54","Grid fluctuation, Site went down because gen fails to start due t=
o grid bad voltage // He bypass grid and manually start the gen","Fabrice P=
ouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, Site went down because gen fails to start due to g=
rid bad voltage // He bypass grid and manually start the gen","gerard.tchan=
goue@matech-cameroun.com","72","06-09-2025 17:31:52","MATECH CMR"
"External Reconciliation","Site Down","T1543","IHS_YND_336","NOCINC00058441=
83","EKIE","","06-09-2025 15:28:11","06-09-2025 15:22:01","06-09-2025 15:48=
:32","Grid outage,Site went down because main gen faulty//He deploy a 20KVA=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator=
 Faulty","Grid outage,Site went down because main gen faulty//He deploy a 2=
0KVA","cedric.tiani@matech-cameroun.com","371","06-09-2025 15:28:11","MATEC=
H CMR"
"External Reconciliation","Site Down","T1278","IHS_YND_802","NOCINC00058439=
05","NYOM FACE MAETUR","","06-09-2025 14:37:14","06-09-2025 14:35:01","06-0=
9-2025 15:01:29","Grid outage, Site went down before Gen start due to poor =
backup // Gen automatically started","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site w=
ent down before Gen start due to poor backup // Gen automatically started",=
"cedric.tiani@matech-cameroun.com","135","06-09-2025 14:37:14","MATECH CMR"
"External Reconciliation","Site Down","CTR_310","IHS_YND_057","NOCINC000584=
3520","Mvolye-New","","06-09-2025 13:41:08","06-09-2025 13:39:48","06-09-20=
25 13:41:48","Active// No power Issue Site on Grid Ubaie =3D51.1V, The TX F=
ME Mbah Hosiah (674007438) is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power Is=
sue Site on Grid Ubaie =3D51.1V, The TX FME Mbah Hosiah (674007438) is info=
rmed","vanel.mbiada@matech-cameroun.com","82","06-09-2025 13:41:08","MATECH=
 CMR"
"External Reconciliation","Site Down","T0056","IHS_YND_189","NOCINC00058435=
02","Paradis Hotel","","06-09-2025 13:34:41","06-09-2025 13:32:29","06-09-2=
025 13:54:27","Grid Outage, site went down because Gen Overload (12.5Kva, 1=
00A) SS IHS BLAISE RAOUL ETCHEU is confirmed//Grid return","Siligap Boris",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, sit=
e went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL ETCHEU=
 is confirmed//Grid return","cedric.tiani@matech-cameroun.com","133","06-09=
-2025 13:34:41","MATECH CMR"
"External Reconciliation","Site Down","CTR_097","IHS_YND_350","NOCINC000584=
3339","Mambine","","06-09-2025 13:08:57","06-09-2025 13:06:47","06-09-2025 =
17:01:27","site went down because Gen started and stopped due to infiltrati=
on of water in the tank// He removed the water and started the Gen","Fanda =
Brice","Fuel Outage (Probable)","Passive","Diesel","Fuel Line Issue","site =
went down because Gen started and stopped due to infiltration of water in t=
he tank// He removed the water and started the Gen","vanel.mbiada@matech-ca=
meroun.com","132","06-09-2025 13:08:57","MATECH CMR"
"External Reconciliation","Site Down","CTR_973","IHS_YND_796","NOCINC000584=
3141","Nkoabang Ebolmedjock","","06-09-2025 12:50:13","06-09-2025 12:48:59"=
,"06-09-2025 12:51:24","Site impacted by Nkolmesseng-Abom(CTR-711) Not Mana=
ged By IHS","Mba Lazare Herve","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Site impacted by Nkolmesseng-Abo=
m(CTR-711) Not Managed By IHS","vanel.mbiada@matech-cameroun.com","76","06-=
09-2025 12:50:13","MATECH CMR"
"External Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00058431=
27","Mokolo Yaounde","","06-09-2025 12:47:52","06-09-2025 12:46:27","06-09-=
2025 13:29:08","Grid only, Grid Outage on site, no space to deploy MDGE // =
Grid return","","Grid Supply","Passive","Grid","National Grid - Grid Outage=
 Issue","Grid only, Grid Outage on site, no space to deploy MDGE // Grid re=
turn","joelle.ekessi@ihstowers.com","87","06-09-2025 12:47:52","MATECH CMR"
"External Reconciliation","Site Down","CTR_829","IHS_YND_404","NOCINC000584=
2331","SAA 2","","06-09-2025 11:06:15","06-09-2025 11:03:47","06-09-2025 11=
:12:22","Grid fluctuation, Site went down because gen failed to start due t=
o grid bad voltage // Grid stabilized","Parker Tchoup","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Sit=
e went down because gen failed to start due to grid bad voltage // Grid sta=
bilized","vanel.mbiada@matech-cameroun.com","150","06-09-2025 11:06:15","MA=
TECH CMR"
"External Reconciliation","Site Down","T3220","IHS_YND_765","NOCINC00058423=
03","MBALNGONG LYCEE","","06-09-2025 11:00:15","06-09-2025 10:53:00","06-09=
-2025 11:02:00","Active//No power Issue Site on Grid Ubai =3D53.8V, The FME=
 The TX FME Fulbert(654266068) is informed.","Fanda Brice","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power Issue Site on Grid Ubai =3D53.8V, The FME The TX FME Fulbert(6=
54266068) is informed.","cedric.tiani@matech-cameroun.com","439","06-09-202=
5 11:00:15","MATECH CMR"
"External Reconciliation","Site Down","T3148","IHS_YND_276","NOCINC00058385=
69","Ekombitie","","05-09-2025 19:22:35","05-09-2025 19:18:27","05-09-2025 =
20:12:09","Site went down because gen started and stopped due to fuel short=
age // Refuelling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel",=
"Diesel Outage","Site went down because gen started and stopped due to fuel=
 shortage // Refuelling done","loic.noumsi@matech-cameroun.com","249","05-0=
9-2025 19:22:35","MATECH CMR"
"Closed Complete","Warning","CTR_080","IHS_YND_298","NOCINC0005838547","Ole=
mbe","","05-09-2025 19:18:14","","","site went in alarm due to Grid bad vol=
tage // He bypassed GRID and started Gen manually","Fabrice Pouakam","Warni=
ng","Warning","POWER","Warning - National Grid - Grid Incomplete Phase","si=
te went in alarm due to Grid bad voltage // He bypassed GRID and started Ge=
n manually","loic.noumsi@matech-cameroun.com","6","05-09-2025 19:18:14","MA=
TECH CMR"
"Closed Complete","Warning","T0351","IHS_YND_146","NOCINC0005838102","Nsime=
yong","","05-09-2025 17:56:13","","","Site went in alarm because SS IHS Fel=
ix Zambe was on site for work // End of work","MINKA NICOLAS","Warning","Wa=
rning","SYSTEM","Warning - Planned Activity - Active","Site went in alarm b=
ecause SS IHS Felix Zambe was on site for work // End of work","loic.noumsi=
@matech-cameroun.com","2","05-09-2025 17:56:13","MATECH CMR"
"External Reconciliation","Site Down","T2586","IHS_YND_747","NOCINC00058375=
75","Akok Ndoe Yde","","05-09-2025 16:46:14","05-09-2025 16:43:43","05-09-2=
025 16:47:31","Grid outage, site went down due to grid bad voltage and no r=
cp on site // He bypassed Grid and started Gen manually","Hyemafo Gildas","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id outage, site went down due to grid bad voltage and no rcp on site // He =
bypassed Grid and started Gen manually","loic.noumsi@matech-cameroun.com","=
153","05-09-2025 16:46:14","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_518","NOCINC0005837393","=
Montee-Jouvence-II","","05-09-2025 16:16:13","05-09-2025 16:08:51","05-09-2=
025 16:20:20","Cascaded Incident from TTO6055628 - Cascade Removed From TTO=
6055628","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Cascaded Incident from TTO6055628 - Cascade Removed From TTO=
6055628","loic.noumsi@matech-cameroun.com","1088","05-09-2025 16:16:13","MA=
TECH CMR"
"External Reconciliation","Site Down","CTR_074","IHS_YND_166","NOCINC000583=
7367","Damas","","05-09-2025 16:15:19","05-09-2025 16:08:51","05-09-2025 16=
:20:20","CASCADED SITE","MINKA NICOLAS","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","CASCADED SITE","loic.noumsi@matech-cameroun.co=
m","996","05-09-2025 16:15:19","MATECH CMR"
"External Reconciliation","Site Down","T0792","IHS_YND_506","NOCINC00058373=
41","Omnisport-Rail","IHS_YND_166, IHS_YND_518","05-09-2025 16:10:41","05-0=
9-2025 16:08:51","05-09-2025 17:06:56","Grid bad voltage, site went down be=
cause gen failed due to 01/06 rectifiers faulty // He replaced it, site on =
GEN","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Grid bad voltage, site went down because gen failed due to 01/06 re=
ctifiers faulty // He replaced it, site on GEN","loic.noumsi@matech-camerou=
n.com","112","05-09-2025 16:10:41","MATECH CMR"
"Closed Complete","Warning","T0772","IHS_YND_207","NOCINC0005837218","ARMP =
Building","","05-09-2025 15:56:16","","","Site alarming because Grid outage=
// Grid power Return and alarm cleared","Mboua Thierry","Warning","Warning"=
,"POWER","Warning - Site on Battery","Site alarming because Grid outage// G=
rid power Return and alarm cleared","loic.noumsi@matech-cameroun.com","2","=
05-09-2025 15:56:16","MATECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058368=
06","Messa Carriere","","05-09-2025 14:42:44","05-09-2025 14:37:39","05-09-=
2025 14:49:39","Site went down due to insufficiency of rectifiers // Site s=
tabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers // Site stab=
ilised","franck.nkomot@matech-cameroun.com","307","05-09-2025 14:42:44","MA=
TECH CMR"
"Closed Complete","Warning","T0294","IHS_YND_016","NOCINC0005836142","Maetu=
r","","05-09-2025 12:26:46","","","Gen stopped with alarm high temperature/=
/ He added water in the radiator and started the Gen","Mboua Thierry","Warn=
ing","Warning","ENVIRONMENT","Warning - High Temperature","Gen stopped with=
 alarm high temperature// He added water in the radiator and started the Ge=
n","cedric.tiani@matech-cameroun.com","4956","05-09-2025 12:26:46","MATECH =
CMR"
"External Reconciliation","Site Down","CTR_441","IHS_YND_687","NOCINC000583=
5825","OLAMA","","05-09-2025 11:35:51","05-09-2025 11:31:42","05-09-2025 12=
:23:50","Active // No power issue on site Ubaie: 54.6V site on Gen The TX F=
ME Henri (699949693) from Huawei is informed","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue on site Ubaie: 54.6V site on Gen The TX FME Henri (69=
9949693) from Huawei is informed","cedric.tiani@matech-cameroun.com","251",=
"05-09-2025 11:35:51","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_732","NOCINC0005835764","=
Nsam escale LP","","05-09-2025 11:25:10","05-09-2025 11:23:15","05-09-2025 =
11:29:59","Cascaded Incident from TTO6053809","","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down before gen=
 started due to poor battery backup// Grid returned","cedric.tiani@matech-c=
ameroun.com","115","05-09-2025 11:25:10","MATECH CMR"
"External Reconciliation","Site Down","T0476","IHS_YND_163","NOCINC00058357=
60","Nsam Sofavinc","IHS_YND_732","05-09-2025 11:24:25","05-09-2025 11:23:1=
5","05-09-2025 11:29:59","Grid outage site went down before gen started due=
 to poor battery backup// Grid returned","MINKA NICOLAS","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site =
went down before gen started due to poor battery backup// Grid returned","c=
edric.tiani@matech-cameroun.com","71","05-09-2025 11:24:25","MATECH CMR"
"External Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058354=
96","Cite des nations","","05-09-2025 10:51:30","05-09-2025 10:46:19","05-0=
9-2025 13:00:54","Site went down due to work of our Fme Paul  on site(insta=
llation of MPR)//End of work","Paul BIBOUM","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to work o=
f our Fme Paul  on site(installation of MPR)//End of work","cedric.tiani@ma=
tech-cameroun.com","312","05-09-2025 10:51:30","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_460","NOCINC0005835294","=
Matsari","","05-09-2025 10:09:02","05-09-2025 08:26:41","05-09-2025 11:34:2=
7","Cascaded Incident from TTO6052716","Parker Tchoup","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","DG battery faulty // DG started=
 with an external battery","christian.fonkou@ihstowers.com","6141","05-09-2=
025 10:09:02","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_456","NOCINC0005835297","=
MBIMBIM","","05-09-2025 10:09:02","05-09-2025 08:26:41","05-09-2025 11:34:2=
7","Cascaded Incident from TTO6052716","Parker Tchoup","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","DG battery faulty // DG started=
 with an external battery","christian.fonkou@ihstowers.com","6141","05-09-2=
025 10:09:02","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_474","NOCINC0005835295","=
Yoko OCM","","05-09-2025 10:09:02","05-09-2025 08:26:41","05-09-2025 11:34:=
27","Cascaded Incident from TTO6052716","Parker Tchoup","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","DG battery faulty // DG starte=
d with an external battery","christian.fonkou@ihstowers.com","6141","05-09-=
2025 10:09:02","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_454","NOCINC0005835296","=
Ngouetou","","05-09-2025 10:09:02","05-09-2025 08:26:41","05-09-2025 11:34:=
27","Cascaded Incident from TTO6052716","Parker Tchoup","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","DG battery faulty // DG starte=
d with an external battery","christian.fonkou@ihstowers.com","6141","05-09-=
2025 10:09:02","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_475","NOCINC0005835293","=
Ngoum","","05-09-2025 10:09:01","05-09-2025 08:26:41","05-09-2025 11:34:27"=
,"Cascaded Incident from TTO6052716","Parker Tchoup","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","DG battery faulty // DG started w=
ith an external battery","christian.fonkou@ihstowers.com","6140","05-09-202=
5 10:09:01","MATECH CMR"
"Closed Complete","Warning","T0183","IHS_YND_184","NOCINC0005834646","Nkolm=
esseng","","05-09-2025 07:45:45","","","HIgh temp//Shelter door open","Sili=
gap Boris","Warning","Warning","ENVIRONMENT","Warning - High Temperature","=
HIgh temp//Shelter door open","cedric.tiani@matech-cameroun.com","16096","0=
5-09-2025 07:45:45","MATECH CMR"
"External Reconciliation","Site Down","T0120","IHS_YND_031","NOCINC00058344=
56","Sime Building","","05-09-2025 06:50:14","05-09-2025 06:45:05","05-09-2=
025 06:53:29","Grid outage, Site went down before Gen start due to poor bac=
kup // Grid return","Mboua Thierry","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Grid return","cedric.tiani@matech-cameroun.com=
","310","05-09-2025 06:50:14","MATECH CMR"
"External Reconciliation","Site Down","CTR_202","IHS_YND_370","NOCINC000583=
4316","Mom","","05-09-2025 05:59:31","05-09-2025 05:46:04","05-09-2025 05:4=
7:04","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade =
Active","Site impacted by OTELE CAMRAIL (CTR_452), Not manage by IHS","fran=
ck.nkomot@matech-cameroun.com","2020","05-09-2025 05:59:31","MATECH CMR"
"External Reconciliation","Site Down","CTR_186","IHS_YND_371","NOCINC000583=
4303","Minka","","05-09-2025 05:57:52","05-09-2025 05:46:04","05-09-2025 05=
:47:04","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Site impacted by OTELE CAMRAIL (CTR_452), Not manage by IHS","fr=
anck.nkomot@matech-cameroun.com","1999","05-09-2025 05:57:52","MATECH CMR"
"External Reconciliation","Site Down","CTR_549","IHS_YND_283","NOCINC000583=
4301","Abome","","05-09-2025 05:56:26","05-09-2025 05:53:17","05-09-2025 06=
:13:17","Grid outage, Site went down before Gen start due to poor backup// =
Gen Automatically Started","MINKA NICOLAS","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen Automatically Started","gerard.tchan=
goue@matech-cameroun.com","191","05-09-2025 05:56:26","MATECH CMR"
"External Reconciliation","Site Down","CTR_201","IHS_YND_368","NOCINC000583=
4291","Otele","IHS_YND_370, IHS_YND_371","05-09-2025 05:51:12","05-09-2025 =
05:46:04","05-09-2025 05:47:04","Site impacted by OTELE CAMRAIL (CTR_452), =
Not manage by IHS","Fanda Brice","Customer Equipment Failure","Active","Act=
ive Equipment Failure","Affected by 3rd Party Site","Site impacted by OTELE=
 CAMRAIL (CTR_452), Not manage by IHS","gerard.tchangoue@matech-cameroun.co=
m","309","05-09-2025 05:51:12","MATECH CMR"
"External Reconciliation","Site Down","T1324","IHS_YND_307","NOCINC00058340=
98","Ebogo","","05-09-2025 04:28:56","05-09-2025 04:18:59","05-09-2025 04:1=
9:59","Active// No Power issue on site Ubaie 53.2V site on Grid, Julien /69=
3095849 from Huawei is informed","Siligap Boris","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Po=
wer issue on site Ubaie 53.2V site on Grid, Julien /693095849 from Huawei i=
s informed","franck.nkomot@matech-cameroun.com","663","05-09-2025 04:28:56"=
,"MATECH CMR"
"External Reconciliation","Site Down","T1278","IHS_YND_802","NOCINC00058340=
00","NYOM FACE MAETUR","","05-09-2025 03:34:14","05-09-2025 03:30:54","05-0=
9-2025 03:40:42","Grid outage, Site went down before Gen start due to poor =
backup // GRID return","Fabrice Pouakam","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // GRID return","franck.nkomot@matech-camero=
un.com","202","05-09-2025 03:34:14","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_732","NOCINC0005833965","=
Nsam escale LP","","05-09-2025 03:12:29","05-09-2025 03:08:42","05-09-2025 =
03:36:42","Cascaded Incident from TTO6051772","","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down before gen=
 started due to poor battery backup// Grid returned","franck.nkomot@matech-=
cameroun.com","227","05-09-2025 03:12:29","MATECH CMR"
"External Reconciliation","Site Down","T0476","IHS_YND_163","NOCINC00058339=
62","Nsam Sofavinc","IHS_YND_732","05-09-2025 03:12:00","05-09-2025 03:08:4=
2","05-09-2025 03:36:42","Grid outage site went down before gen started due=
 to poor battery backup// Grid returned","MINKA NICOLAS","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site =
went down before gen started due to poor battery backup// Grid returned","f=
ranck.nkomot@matech-cameroun.com","199","05-09-2025 03:12:00","MATECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058333=
12","Messa Carriere","","04-09-2025 23:03:25","04-09-2025 22:56:12","04-09-=
2025 23:12:12","Site went down due to insufficiency of rectifiers // Site s=
tabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers // Site stab=
ilised","franck.nkomot@matech-cameroun.com","435","04-09-2025 23:03:25","MA=
TECH CMR"
"External Reconciliation","Site Down","T0649","IHS_YND_279","NOCINC00058329=
33","Messassi okolo","","04-09-2025 21:48:33","04-09-2025 21:45:59","04-09-=
2025 21:56:14","Site went down because Gen failed to start due to grid badv=
oltage//he bypassed the Grid and site on Gen","Fabrice Pouakam","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Site went do=
wn because Gen failed to start due to grid badvoltage//he bypassed the Grid=
 and site on Gen","loic.noumsi@matech-cameroun.com","156","04-09-2025 21:48=
:33","MATECH CMR"
"External Reconciliation","Site Down","T1565","IHS_YND_261","NOCINC00058311=
03","Barriere","","04-09-2025 16:57:34","04-09-2025 16:55:21","04-09-2025 1=
7:15:09","Grid outage.gen started and stopped due to fuel pump faulty // We=
 change fuel pump and gen manually starte","Hyemafo Gildas","Fuel Outage (P=
robable)","Passive","ACDG Gen","ACDG - Fuel Pump","Grid outage.gen started =
and stopped due to fuel pump faulty//We change fuel pump and gen manually s=
tarte","loic.noumsi@matech-cameroun.com","135","04-09-2025 16:57:34","MATEC=
H CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058308=
40","Messa Carriere","","04-09-2025 16:05:08","04-09-2025 16:02:57","04-09-=
2025 16:20:28","Site went down due to insufficiency of rectifiers // Site s=
tabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers // Site stab=
ilised","loic.noumsi@matech-cameroun.com","132","04-09-2025 16:05:08","MATE=
CH CMR"
"External Reconciliation","Site Down","T2039","IHS_YND_724","NOCINC00058307=
88","BIYEMASSI NIKI","","04-09-2025 15:56:02","04-09-2025 15:52:56","04-09-=
2025 16:05:04","Grid outage, site went down due to 01/05 rectifiers dysfunc=
tionning // He reset it, site on Grid","Hyemafo Gildas","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","Grid outage, site went down due t=
o 01/05 rectifiers dysfunctionning // He reset it, site on Grid","loic.noum=
si@matech-cameroun.com","1176","04-09-2025 15:56:02","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_067","NOCINC0005830716","=
Nkoa Ayos","","04-09-2025 15:43:32","04-09-2025 15:33:59","04-09-2025 16:14=
:53","Cascaded Incident from TTO6048156","MINKA NICOLAS","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue U =3D54,5V site o=
n Grid. The Tx FME Brice Tsague (650214096 )from Huawei is informed.","gera=
rd.tchangoue@matech-cameroun.com","573","04-09-2025 15:43:32","MATECH CMR"
"External Reconciliation","Site Down","CTR_389","IHS_YND_066","NOCINC000583=
0710","GSO","IHS_YND_067","04-09-2025 15:42:13","04-09-2025 15:33:59","04-0=
9-2025 16:42:53","No power issue U =3D54,5V site on Grid. The Tx FME Brice =
Tsague (650214096 )from Huawei is informed.","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue U =3D54,5V site on Grid. The Tx FME Brice Tsague (650214096 )f=
rom Huawei is informed.","gerard.tchangoue@matech-cameroun.com","495","04-0=
9-2025 15:42:13","MATECH CMR"
"External Reconciliation","Site Down","T1377","IHS_YND_807","NOCINC00058307=
09","Ahala Echangeur","","04-09-2025 15:42:10","04-09-2025 15:39:04","04-09=
-2025 16:11:45","Grid outage, site went down due to Grid bad voltage // He =
bypassed Grid and started Gen manually","MINKA NICOLAS","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","Grid outage, site we=
nt down due to Grid bad voltage // He bypassed Grid and started Gen manuall=
y","loic.noumsi@matech-cameroun.com","188","04-09-2025 15:42:10","MATECH CM=
R"
"External Reconciliation","Site Down","T2585","IHS_YND_744","NOCINC00058306=
60","Eleveur Meec Bon Berger","","04-09-2025 15:33:46","04-09-2025 15:30:40=
","04-09-2025 15:32:43","no power issue on site Tx issue U=3D53.6V site on =
Grid , the fme TX Symphorien//650257151 from Huawei is informed","Siligap B=
oris","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","no power issue on site Tx issue U=3D53.6V site on Grid , =
the fme TX Symphorien//650257151 from Huawei is informed","loic.noumsi@mate=
ch-cameroun.com","187","04-09-2025 15:33:46","MATECH CMR"
"External Reconciliation","Site Down","CTR_632","IHS_YND_721","NOCINC000583=
0555","VOIRIE MUNICIPALE YAOUNDE","","04-09-2025 15:17:40","04-09-2025 15:0=
9:34","04-09-2025 15:45:00"," No power issue Ubaie:54.5 V site on Grid   Th=
e TX FME Brice Tsague (654419973)  from Huawei is informed. Site went down =
due to work: vehua ( 699044809 / omniom) working on site // end of work ","=
Paul BIBOUM","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm"," No power issue Ubaie:54.5 V site on Grid   The TX=
 FME Brice Tsague (654419973)  from Huawei is informed. Site went down due =
to work: vehua ( 699044809 / omniom) working on site // end of work ","gera=
rd.tchangoue@matech-cameroun.com","487","04-09-2025 15:17:40","MATECH CMR"
"External Reconciliation","Site Down","CTR_477","IHS_YND_566","NOCINC000583=
0544","Crf Cornier","","04-09-2025 15:17:03","04-09-2025 15:14:56","04-09-2=
025 16:00:03","ACTIVE //No power issue Ubaie: 54.6V site on Grid Armand NGU=
ETSA // 699949553// from huawei is informed,","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
CTIVE //No power issue Ubaie: 54.6V site on Grid Armand NGUETSA // 69994955=
3// from huawei is informed,","gerard.tchangoue@matech-cameroun.com","129",=
"04-09-2025 15:17:03","MATECH CMR"
"External Reconciliation","Site Down","T1377","IHS_YND_807","NOCINC00058304=
22","Ahala Echangeur","","04-09-2025 15:06:14","04-09-2025 15:01:09","04-09=
-2025 15:23:11","Grid outage, site went down due to Grid bad voltage // He =
bypassed Grid and started Gen manually","MINKA NICOLAS","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","Grid outage, site we=
nt down due to Grid bad voltage // He bypassed Grid and started Gen manuall=
y","loic.noumsi@matech-cameroun.com","307","04-09-2025 15:06:14","MATECH CM=
R"
"External Reconciliation","Site Down","","IHS_YND_024","NOCINC0005830416","=
Garbati building","","04-09-2025 15:05:49","04-09-2025 15:01:59","04-09-202=
5 15:02:16","Cascaded Incident from TTO6047815","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Site went down becaus=
e SS IHS Bernard Atangana was on site for work (Transmission secured) // En=
d of work","loic.noumsi@matech-cameroun.com","230","04-09-2025 15:05:49","M=
ATECH CMR"
"External Reconciliation","Site Down","T1547","IHS_YND_064","NOCINC00058304=
03","HOPITAL DE LA CAISSE","IHS_YND_024","04-09-2025 15:05:07","04-09-2025 =
15:01:59","04-09-2025 15:33:21","Site went down because SS IHS Bernard Atan=
gana was on site for work (Transmission secured) // End of work","Delor Tel=
ezing","Installation Activity","Passive","Planned Activity","Installation A=
ctivity","Site went down because SS IHS Bernard Atangana was on site for wo=
rk (Transmission secured) // End of work","loic.noumsi@matech-cameroun.com"=
,"189","04-09-2025 15:05:07","MATECH CMR"
"External Reconciliation","Site Down","T1248","IHS_YND_797","NOCINC00058303=
27","Fouda rue des g=E9n=E9raux","","04-09-2025 14:53:52","04-09-2025 14:51=
:48","04-09-2025 15:22:24","Grid outage, Site went down because Gen failed =
to start due to battery Gen faulty// He started Gen with external battery",=
"Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Generator =
Battery","Grid outage, Site went down because Gen failed to start due to ba=
ttery Gen faulty// He started Gen with external battery","loic.noumsi@matec=
h-cameroun.com","125","04-09-2025 14:53:52","MATECH CMR"
"External Reconciliation","Site Down","T3216","IHS_YND_762","NOCINC00058302=
83","Nkolfon Cimencam","","04-09-2025 14:50:42","04-09-2025 14:47:59","04-0=
9-2025 15:29:33","Site went down because FME Dowen (650631358) was on site =
for work (Swap of Gen) // End of work","Hyemafo Gildas","Installation Activ=
ity","Passive","Planned Activity","Installation Activity","Site went down b=
ecause FME Dowen (650631358) was on site for work (Swap of Gen) // End of w=
ork","loic.noumsi@matech-cameroun.com","164","04-09-2025 14:50:42","MATECH =
CMR"
"External Reconciliation","Site Down","","IHS_YND_024","NOCINC0005830236","=
Garbati building","","04-09-2025 14:46:50","04-09-2025 14:43:18","04-09-202=
5 14:47:11","Cascaded Incident from TTO6047630","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid Outage, Site wen=
t down before Gen start due to poor backup // Grid return","loic.noumsi@mat=
ech-cameroun.com","212","04-09-2025 14:46:50","MATECH CMR"
"External Reconciliation","Site Down","T1547","IHS_YND_064","NOCINC00058302=
33","HOPITAL DE LA CAISSE","IHS_YND_024","04-09-2025 14:46:25","04-09-2025 =
14:43:18","04-09-2025 14:47:11","Grid Outage, Site went down before Gen sta=
rt due to poor backup // Grid return","Delor Telezing","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site w=
ent down before Gen start due to poor backup // Grid return","loic.noumsi@m=
atech-cameroun.com","188","04-09-2025 14:46:25","MATECH CMR"
"External Reconciliation","Site Down","T0896","IHS_YND_707","NOCINC00058300=
68","NYOM 2 IHS","","04-09-2025 14:25:27","04-09-2025 14:23:23","04-09-2025=
 14:34:06","Active // No power issue Ubaie:52.7 V site on Gen, site up with=
out intervention. TX fme symphorien /650257151 from huawei is informed.","F=
abrice Pouakam","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active // No power issue Ubaie:52.7 V site on G=
en, site up without intervention. TX fme symphorien /650257151 from huawei =
is informed.","loic.noumsi@matech-cameroun.com","126","04-09-2025 14:25:27"=
,"MATECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058298=
43","Messa Carriere","","04-09-2025 14:08:15","04-09-2025 14:07:03","04-09-=
2025 14:25:25","Site went down due to insufficiency of rectifiers // Site s=
tabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers // Site stab=
ilised","cedric.tiani@matech-cameroun.com","73","04-09-2025 14:08:15","MATE=
CH CMR"
"External Reconciliation","Site Down","T1394","IHS_YND_511","NOCINC00058296=
39","Etoug ebe Carrefour","","04-09-2025 14:01:07","04-09-2025 13:59:57","0=
4-09-2025 14:05:57","Grid outage site went down before gen started due to p=
oor battery backup// Grid returned","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage site went=
 down before gen started due to poor battery backup// Grid returned","cedri=
c.tiani@matech-cameroun.com","72","04-09-2025 14:01:07","MATECH CMR"
"External Reconciliation","Site Down","T2104","IHS_YND_711","NOCINC00058288=
03","H-Franco New","","04-09-2025 12:19:55","04-09-2025 12:16:48","04-09-20=
25 12:24:05","Site went down due to work of our  Fme Delor  on site (doing =
PM)//End of work","Delor Telezing","Installation Activity","Passive","Plann=
ed Activity","Installation Activity","Site went down due to work of our  Fm=
e Delor  on site (doing PM)//End of work","cedric.tiani@matech-cameroun.com=
","188","04-09-2025 12:19:55","MATECH CMR"
"External Reconciliation","Site Down","CTR_521","IHS_YND_692","NOCINC000582=
8581","Mendong vallee","","04-09-2025 11:39:37","04-09-2025 11:30:29","04-0=
9-2025 12:30:38","FME of I-Eng (697488578) is on site for work // End of wo=
rk ","Fanda Brice","Installation Activity","Passive","Planned Activity","In=
stallation Activity","FME of I-Eng (697488578) is on site for work // End o=
f work ","gerard.tchangoue@matech-cameroun.com","550","04-09-2025 11:39:37"=
,"MATECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058283=
22","Messa Carriere","","04-09-2025 11:08:53","04-09-2025 11:06:34","04-09-=
2025 11:18:34","Site went down due to insufficiency of rectifiers // Site s=
tabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers // Site stab=
ilised","cedric.tiani@matech-cameroun.com","140","04-09-2025 11:08:53","MAT=
ECH CMR"
"External Reconciliation","Site Down","T1278","IHS_YND_802","NOCINC00058271=
85","NYOM FACE MAETUR","","04-09-2025 09:23:59","04-09-2025 09:22:52","04-0=
9-2025 09:24:59","Grid outage, Site went down before Gen start due to poor =
backup // GRID return","Fabrice Pouakam","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // GRID return","cedric.tiani@matech-camerou=
n.com","70","04-09-2025 09:23:59","MATECH CMR"
"External Reconciliation","Site Down","T2585","IHS_YND_744","NOCINC00058271=
37","Eleveur Meec Bon Berger","","04-09-2025 09:21:21","04-09-2025 09:18:38=
","04-09-2025 10:30:32","no power issue on site Tx issue U=3D53.6V site on =
Grid , the fme tx Symphorien//650257151 from Huawei is informed","Siligap B=
oris","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","no power issue on site Tx issue U=3D53.6V site on Grid , =
the fme tx Symphorien//650257151 from Huawei is informed","cedric.tiani@mat=
ech-cameroun.com","164","04-09-2025 09:21:21","MATECH CMR"
"External Reconciliation","Site Down","T3231","IHS_YND_743","NOCINC00058269=
46","Ngousso Vallee","","04-09-2025 08:49:55","04-09-2025 08:48:33","04-09-=
2025 08:52:59"," Grid fluctuations site went down due to bad grid voltage a=
nd no RCP //He made a bridge with a good phase  ","Siligap Boris","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty"," Grid fluc=
tuations site went down due to bad grid voltage and no RCP //He made a brid=
ge with a good phase  ","cedric.tiani@matech-cameroun.com","83","04-09-2025=
 08:49:55","MATECH CMR"
"External Reconciliation","Site Down","T1832","IHS_YND_216","NOCINC00058268=
73","Eleveur","","04-09-2025 08:34:52","04-09-2025 04:56:24","04-09-2025 08=
:02:12","Backtracking Site went down becaause MTN depart was vandalised (48=
v cable replaced  was stolen and The power supply of camtel radios was cut =
and removed on site)//Cable has been replaced by 16mm2","Siligap Boris","Si=
te Asset Theft","Theft","Theft","DC Cable Stolen","Backtracking Site went d=
own becaause MTN depart was vandalised (48v cable replaced  was stolen and =
The power supply of camtel radios was cut and removed on site)//Cable has b=
een replaced.","cedric.tiani@matech-cameroun.com","13109","04-09-2025 08:34=
:52","MATECH CMR"
"External Reconciliation","Site Down","T1832","IHS_YND_216","NOCINC00058260=
24","Eleveur","","04-09-2025 04:47:14","04-09-2025 04:37:59","04-09-2025 04=
:55:01","No power issue on site UB=3D50.9V site on Grid THE TX FME SYMPHORI=
EN (650257151) from HUAWEI is informed","Siligap Boris","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site UB=3D52.1V site on Grid THE TX FME SYMPHORIEN (650257151) f=
rom HUAWEI is informed","ludivine.ngamaleu@ihstowers.com","556","04-09-2025=
 04:47:14","MATECH CMR"
"External Reconciliation","Site Down","T2585","IHS_YND_744","NOCINC00058258=
17","Eleveur Meec Bon Berger","","04-09-2025 03:25:24","04-09-2025 03:21:13=
","04-09-2025 03:37:12","no power issue on site Tx issue U=3D56.6V site on =
Grid , the fme tx Symphorien//650257151 from Huawei is informed","Siligap B=
oris","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","no power issue on site Tx issue U=3D56.6V site on Grid , =
the fme tx Symphorien//650257151 from Huawei is informed","vanel.mbiada@mat=
ech-cameroun.com","252","04-09-2025 03:25:24","MATECH CMR"
"External Reconciliation","Site Down","T2563","IHS_YND_748","NOCINC00058254=
73","Nkoabang Alembe","","04-09-2025 01:55:40","04-09-2025 01:54:31","04-09=
-2025 02:31:57","Site went down because 02/03 rectifiers alarming on site /=
/He reset it and site on Grid","Mba Lazare Herve","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down because 02/03 rectifiers=
 alarming on site //He reset it and site on Grid","vanel.mbiada@matech-came=
roun.com","69","04-09-2025 01:55:40","MATECH CMR"
"External Reconciliation","Site Down","T1278","IHS_YND_802","NOCINC00058253=
12","NYOM FACE MAETUR","","04-09-2025 01:08:29","04-09-2025 01:06:22","04-0=
9-2025 02:09:20","Grid outage site went down because Gen failed to start du=
e to grid contactor faulty //he replaced, site on Grid ","Fabrice Pouakam",=
"Equipment Repair","Passive","Control Panel","ATS Relay Faulty","Grid outag=
e site went down because Gen failed to start due to grid contactor faulty /=
/he replaced site on Grid ","vanel.mbiada@matech-cameroun.com","130","04-09=
-2025 01:08:29","MATECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058251=
25","Messa Carriere","","04-09-2025 00:09:28","04-09-2025 00:08:10","04-09-=
2025 00:24:31","Site went down due to insufficiency of rectifiers//Grid sta=
bilized","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficiency of rectifiers//Grid stabiliz=
ed","vanel.mbiada@matech-cameroun.com","79","04-09-2025 00:09:28","MATECH C=
MR"
"External Reconciliation","Site Down","T3231","IHS_YND_743","NOCINC00058250=
57","Ngousso Vallee","","03-09-2025 23:27:19","03-09-2025 23:24:41","03-09-=
2025 23:28:17","Acces issue during the nigth. Grid fluctuations site went d=
own due to bad grid voltage and no RCP //grid power stabilized","Siligap Bo=
ris","Access Denial","Lease Or Legal","Landlord Related Issues","Access Iss=
ue - Land Lord","Acces issue during the nigth. Grid fluctuations site went =
down due to bad grid voltage and no RCP //grid power stabilized","vanel.mbi=
ada@matech-cameroun.com","159","03-09-2025 23:27:19","MATECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058249=
98","Messa Carriere","","03-09-2025 23:01:56","03-09-2025 22:58:43","03-09-=
2025 23:14:44","Site went down due to insufficiency of rectifiers// Grid st=
abilized","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to insufficiency of rectifiers// Grid stabil=
ized","vanel.mbiada@matech-cameroun.com","195","03-09-2025 23:01:56","MATEC=
H CMR"
"External Reconciliation","Site Down","T3148","IHS_YND_276","NOCINC00058246=
70","Ekombitie","","03-09-2025 21:45:05","03-09-2025 21:43:00","03-09-2025 =
22:27:14","Grid outage Site went down due to Bad voltage , Gen failed to st=
art due to battery Gen faulty// He started Gen with external battery site o=
n Gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ge=
nerator Battery","Grid outage, Site went down due to Bad voltage , Gen fail=
ed to start due to battery Gen faulty// He started Gen with external batter=
y site on Gen","loic.noumsi@matech-cameroun.com","127","03-09-2025 21:45:05=
","MATECH CMR"
"External Reconciliation","Site Down","T0896","IHS_YND_707","NOCINC00058246=
64","NYOM 2 IHS","","03-09-2025 21:44:03","03-09-2025 21:41:53","03-09-2025=
 23:37:20","Site went down due to disjunction of Cb(125A) in PWC // He ream=
ed Cb(125A)// site on Gen","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down due =
to disjunction of Cb(125A) in PWC // He reamed Cb(125A)// site on Gen","loi=
c.noumsi@matech-cameroun.com","132","03-09-2025 21:44:03","MATECH CMR"
"External Reconciliation","Site Down","T3148","IHS_YND_276","NOCINC00058245=
68","Ekombitie","","03-09-2025 21:26:16","03-09-2025 21:22:18","03-09-2025 =
21:34:04","Grid outage Site went down due to Bad voltage , Gen failed to st=
art due to battery Gen faulty// He started Gen with external battery site o=
n Gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ge=
nerator Battery","Grid outage Site went down due to Bad voltage , Gen faile=
d to start due to battery Gen faulty// He started Gen with external battery=
 site on Gen","loic.noumsi@matech-cameroun.com","239","03-09-2025 21:26:16"=
,"MATECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058244=
90","Messa Carriere","","03-09-2025 21:12:02","03-09-2025 21:06:57","03-09-=
2025 21:16:32","Site went down due to insufficiency of rectifiers // Site s=
tabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers // Site stab=
ilised","loic.noumsi@matech-cameroun.com","306","03-09-2025 21:12:02","MATE=
CH CMR"
"Closed Complete","Warning","T0289","IHS_YND_106","NOCINC0005824462","Mfand=
ena","","03-09-2025 21:06:18","","","High temp. FME report that air conditi=
oner is faulty. // He opened the shelter","Delor Telezing","Warning","Warni=
ng","ENVIRONMENT","Warning - High Temperature","High temp. FME report that =
air conditioner is faulty. // He opened the shelter","loic.noumsi@matech-ca=
meroun.com","108","03-09-2025 21:06:18","MATECH CMR"
"External Reconciliation","Site Down","CTR_648","IHS_YND_707","NOCINC000582=
4215","NYOM 2 IHS","","03-09-2025 20:35:37","03-09-2025 20:34:28","03-09-20=
25 21:04:49","Site  went down due to CB(125A) in PWC that tripped MTN//He r=
earmed it and site on Grid","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Circuit Breaker Issue","Site  went down du=
e to CB(125A) in PWC that tripped MTN//He rearmed it and site on Grid","ger=
ard.tchangoue@matech-cameroun.com","71","03-09-2025 20:35:37","MATECH CMR"
"External Reconciliation","Site Down","CTR_017","IHS_YND_083","NOCINC000582=
3994","H-Progres","","03-09-2025 19:55:55","03-09-2025 19:50:53","04-09-202=
5 14:23:43","No space, awaiting grid return","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid outage , No space to  deploy =
// Grid return","alexandre.kamal@ihstowers.com","304","03-09-2025 19:55:55"=
,"MATECH CMR"
"External Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058239=
71","Cite des nations","","03-09-2025 19:52:37","03-09-2025 19:45:32","03-0=
9-2025 19:51:56","Grid Outage, Site went down due to MPR DYSFUNCTIONNING on=
 site // Site stabilised","Paul BIBOUM","Equipment Repair","Passive","Recti=
fier","Rectifier Cabinet","Grid Outage, Site went down due to MPR DYSFUNCTI=
ONNING on site // Site stabilised","loic.noumsi@matech-cameroun.com","426",=
"03-09-2025 19:52:37","MATECH CMR"
"External Reconciliation","Site Down","CTR_160","IHS_YND_523","NOCINC000582=
3865","EMANA BILICK CITY","","03-09-2025 19:37:36","03-09-2025 19:21:29","0=
3-09-2025 19:49:29","Access issue in the site at night. Grid outage, site w=
ent down because site behaves as Grid only site (Gen Noise) // Grid return"=
,"Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord Related Issue=
s","Access Issue - Land Lord","Access issue in the site at night. Grid outa=
ge, site went down because site behaves as Grid only site (Gen Noise) // Gr=
id return","gerard.tchangoue@matech-cameroun.com","970","03-09-2025 19:37:3=
6","MATECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058237=
84","Messa Carriere","","03-09-2025 19:18:13","03-09-2025 19:11:08","03-09-=
2025 19:23:44","Site went down due to insufficiency of rectifiers // Site s=
tabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers // Site stab=
ilised","loic.noumsi@matech-cameroun.com","427","03-09-2025 19:18:13","MATE=
CH CMR"
"External Reconciliation","Site Down","T0649","IHS_YND_279","NOCINC00058237=
18","Messassi okolo","","03-09-2025 19:04:34","03-09-2025 19:00:23","03-09-=
2025 19:55:50","Gid outage,site went down because Gen started and stopped d=
ue to Alarm*Overvoltage*//He reduiced the Frequency and started the Gen man=
ually","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
er Voltage","Gid outage,site went down because Gen started and stopped due =
to Alarm*Overvoltage*//He reduiced the Frequency and started the Gen manual=
ly","loic.noumsi@matech-cameroun.com","252","03-09-2025 19:04:34","MATECH C=
MR"
"External Reconciliation","Site Down","T1248","IHS_YND_797","NOCINC00058237=
12","Fouda rue des g=E9n=E9raux","","03-09-2025 19:02:47","03-09-2025 18:58=
:30","03-09-2025 19:28:12","Grid outage, Site went down because Gen failed =
to start due to battery Gen faulty // Grid return","Delor Telezing","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, S=
ite went down because Gen failed to start due to battery Gen faulty // Grid=
 return","loic.noumsi@matech-cameroun.com","258","03-09-2025 19:02:47","MAT=
ECH CMR"
"External Reconciliation","Site Down","CTR_097","IHS_YND_350","NOCINC000582=
3510","Mambine","","03-09-2025 18:25:41","03-09-2025 18:20:34","03-09-2025 =
18:34:26","Grid outage, site went down due to Grid bad voltage // He bypass=
ed Grid and started Gen manually","Fanda Brice","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","Grid outage, site went down =
due to Grid bad voltage // He bypassed Grid and started Gen manually","gera=
rd.tchangoue@matech-cameroun.com","309","03-09-2025 18:25:41","MATECH CMR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058234=
68","Messa Carriere","","03-09-2025 18:18:42","03-09-2025 18:16:38","03-09-=
2025 18:28:59","Site went down due to insufficiency of rectifiers // Site s=
tabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers // Site stab=
ilised","loic.noumsi@matech-cameroun.com","125","03-09-2025 18:18:42","MATE=
CH CMR"
"External Reconciliation","Site Down","T0816","IHS_YND_260","NOCINC00058233=
31","Simbock Maetur","","03-09-2025 17:50:19","03-09-2025 17:46:13","03-09-=
2025 19:00:08","Site went down because Grid return and Grid contactor did n=
ot stick due to ATS faulty ATS is faulty // He bypass ATS and site on Grid"=
,"Hyemafo Gildas","Equipment Repair","Passive","Control Panel","ATS Relay F=
aulty","Site went down because Grid return and Grid contactor did not stick=
 due to ATS faulty ATS is faulty // He bypass ATS and site on Grid","loic.n=
oumsi@matech-cameroun.com","247","03-09-2025 17:50:19","MATECH CMR"
"External Reconciliation","Site Down","T0649","IHS_YND_279","NOCINC00058233=
15","Messassi okolo","","03-09-2025 17:47:26","03-09-2025 17:44:20","03-09-=
2025 18:28:11","Gid outage,site went down because Gen started and stopped d=
ue to Alarm*Overvoltage*//He reduced the Frequency and started the Gen manu=
ally","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
r Voltage","Gid outage,site went down because Gen started and stopped due t=
o Alarm*Overvoltage*//He reduced the Frequency and started the Gen manually=
","loic.noumsi@matech-cameroun.com","187","03-09-2025 17:47:26","MATECH CMR=
"
"Closed Complete","Warning","T0351","IHS_YND_146","NOCINC0005823134","Nsime=
yong","","03-09-2025 17:22:43","","","site alarming due to site on battery/=
/alarm is clear","MINKA NICOLAS","Warning","Warning","POWER","Warning - Sit=
e on Battery","site alarming due to site on battery//alarm is clear","loic.=
noumsi@matech-cameroun.com","2","03-09-2025 17:22:43","MATECH CMR"
"External Reconciliation","Site Down","T1665","IHS_YND_014","NOCINC00058230=
84","ELIg-Essono","","03-09-2025 17:16:50","03-09-2025 17:08:41","03-09-202=
5 17:20:53","Grid outage Site went down because gen failed due to fuse of G=
en card faulty//We did a bridge on a fuse and gen manually started","Delor =
Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage Site went down because gen failed due to fuse of Gen card faulty=
//We did a bridge on a fuse and gen manually started","loic.noumsi@matech-c=
ameroun.com","490","03-09-2025 17:16:50","MATECH CMR"
"External Reconciliation","Site Down","T0033","IHS_YND_167","NOCINC00058229=
50","Touring Club International","","03-09-2025 16:52:28","03-09-2025 16:49=
:22","03-09-2025 16:52:16","Site went down due to plan work done by SS IHS =
Pascaline // End of work","Albran Byorel","Installation Activity","Passive"=
,"Planned Activity","Installation Activity","Site went down due to plan wor=
k done by SS IHS Pascaline // End of work","loic.noumsi@matech-cameroun.com=
","188","03-09-2025 16:52:28","MATECH CMR"
"External Reconciliation","Site Down","T1297","IHS_YND_734","NOCINC00058229=
33","Mimboman Chateau","","03-09-2025 16:49:47","03-09-2025 16:45:43","03-0=
9-2025 16:50:47","Grid_Only site // Grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid_Only site // Grid return"=
,"loic.noumsi@matech-cameroun.com","244","03-09-2025 16:49:47","MATECH CMR"
"External Reconciliation","Site Down","T2347","IHS_YND_731","NOCINC00058229=
04","UPAC LP","","03-09-2025 16:41:12","03-09-2025 16:19:42","04-09-2025 12=
:26:04","Grid_only , No space to deploy // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid_only , No space to=
 deploy // Grid return","ange.kongo@ihstowers.com","1292","03-09-2025 16:41=
:12","MATECH CMR"
"External Reconciliation","Site Down","T1665","IHS_YND_014","NOCINC00058228=
76","ELIg-Essono","","03-09-2025 16:35:26","03-09-2025 16:31:20","03-09-202=
5 16:46:42","Grid outage Site went down because gen failed due to fuse of G=
en card faulty//We did a bridge on a fuse and gen manually started","Delor =
Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage Site went down because gen failed due to fuse of Gen card faulty=
//We did a bridge on a fuse and gen manually started","loic.noumsi@matech-c=
ameroun.com","247","03-09-2025 16:35:26","MATECH CMR"
"External Reconciliation","Site Down","T1248","IHS_YND_797","NOCINC00058228=
68","Fouda rue des g=E9n=E9raux","","03-09-2025 16:33:45","03-09-2025 16:30=
:40","03-09-2025 17:42:12","Grid outage, Site went down because Gen failed =
to start due to battery Gen faulty // He started Gen with battery backup","=
Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Generator B=
attery","Grid outage, Site went down because Gen failed to start due to bat=
tery Gen faulty // He started Gen with battery backup","loic.noumsi@matech-=
cameroun.com","185","03-09-2025 16:33:45","MATECH CMR"
"External Reconciliation","Site Down","CTR_090","IHS_YND_063","NOCINC000582=
2816","Av-Germaine","","03-09-2025 16:23:45","03-09-2025 16:18:39","03-09-2=
025 16:29:39","	Grid only site","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","Grid outage // grid return","gerard.tchangoue@m=
atech-cameroun.com","307","03-09-2025 16:23:45","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_277","NOCINC0005822810","=
Ngoulmekong-Nord","","03-09-2025 16:22:52","03-09-2025 16:18:22","03-09-202=
5 17:06:47","Cascaded Incident from TTO6039468","Siligap Boris","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","No power issue on site UB=
=3D52.1V site on Grid THE TX FME SYMPHORIEN (650257151) from HUAWEI is info=
rmed	","gerard.tchangoue@matech-cameroun.com","270","03-09-2025 16:22:52","=
MATECH CMR"
"External Reconciliation","Site Down","CTR_254","IHS_YND_216","NOCINC000582=
2808","Eleveur","IHS_YND_277","03-09-2025 16:22:30","03-09-2025 16:18:22","=
03-09-2025 17:06:47","No power issue on site UB=3D52.1V site on Grid THE TX=
 FME SYMPHORIEN (650257151) from HUAWEI is informed	","Siligap Boris","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site UB=3D52.1V site on Grid THE TX FME SYMPHORIEN=
 (650257151) from HUAWEI is informed	","gerard.tchangoue@matech-cameroun.co=
m","249","03-09-2025 16:22:30","MATECH CMR"
"External Reconciliation","Site Down","CTR_542","IHS_YND_182","NOCINC000582=
2791","Titi Garage","","03-09-2025 16:19:40","03-09-2025 16:14:28","03-09-2=
025 16:28:35","Active//No power issue on site U=3D53.5 V site on Grid The T=
X FME Armand // 691144412 from Huawei is informed.","Delor Telezing","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue on site U=3D53.5 V site on Grid The TX FME Arm=
and // 691144412 from Huawei is informed.","gerard.tchangoue@matech-camerou=
n.com","313","03-09-2025 16:19:40","MATECH CMR"
"External Reconciliation","Site Down","CTR_075","IHS_YND_133","NOCINC000582=
2776","Elig-Edzoa","","03-09-2025 16:17:56","03-09-2025 16:14:47","03-09-20=
25 16:25:23","ACTIVE// No Power issue on site ,site on Grid with Ubaie=3D54=
,4 VThe Tx FME Armand Nguetsa //","","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No Power issue on=
 site ,site on Grid with Ubaie=3D54,4 VThe Tx FME Armand Nguetsa //","gerar=
d.tchangoue@matech-cameroun.com","191","03-09-2025 16:17:56","MATECH CMR"
"External Reconciliation","Site Down","CTR_149","IHS_YND_517","NOCINC000582=
2756","Montee-Des-Soeurs","","03-09-2025 16:12:12","03-09-2025 16:06:06","0=
3-09-2025 16:35:34"," Grid outage ,site went down due to Gen overload (15 K=
VA/210 A) // Grid return","Hyemafo Gildas","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload"," Grid outage ,site went down due to Gen overload=
 (15 KVA/210 A) // Grid return","gerard.tchangoue@matech-cameroun.com","369=
","03-09-2025 16:12:12","MATECH CMR"
"External Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00058227=
48","Mokolo Yaounde","","03-09-2025 16:11:38","03-09-2025 16:06:32","04-09-=
2025 00:52:46","Grid only , No space to deploy // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only , No s=
pace to deploy // Grid return","loic.noumsi@matech-cameroun.com","309","03-=
09-2025 16:11:38","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_192","NOCINC0005822676","=
Dragage","","03-09-2025 15:56:18","03-09-2025 15:49:40","03-09-2025 16:17:2=
7","Cascaded Incident from TTO6039271","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site. Site on Ge=
n with Ubaie=3D54.3V The TX FME Eloundou // 693212405// From Huawei is info=
rmed.","gerard.tchangoue@matech-cameroun.com","398","03-09-2025 15:56:18","=
MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_208","NOCINC0005822672","=
ARMP","","03-09-2025 15:55:56","03-09-2025 15:49:40","03-09-2025 16:17:27",=
"Cascaded Incident from TTO6039271","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue on site. Site on Gen with Ubaie=3D5=
4.3V The TX FME Eloundou // 693212405// From Huawei is informed.","gerard.t=
changoue@matech-cameroun.com","376","03-09-2025 15:55:56","MATECH CMR"
"External Reconciliation","Site Down","CTR_020","IHS_YND_137","NOCINC000582=
2641","Masque","IHS_YND_192, IHS_YND_208","03-09-2025 15:51:46","03-09-2025=
 15:49:40","03-09-2025 16:17:27","No power issue on site. Site on Gen with =
Ubaie=3D54.3V The TX FME Eloundou // 693212405// From Huawei is informed.",=
"Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","No power issue on site. Site on Gen with Ubai=
e=3D54.3V The TX FME Eloundou // 693212405// From Huawei is informed.","ger=
ard.tchangoue@matech-cameroun.com","129","03-09-2025 15:51:46","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_024","NOCINC0005822639","=
Garbati building","","03-09-2025 15:51:40","03-09-2025 15:47:13","03-09-202=
5 15:55:39","Cascaded Incident from TTO6039252","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid Outage, Site wen=
t down before Gen start due to poor backup // Grid return","loic.noumsi@mat=
ech-cameroun.com","267","03-09-2025 15:51:40","MATECH CMR"
"External Reconciliation","Site Down","T1547","IHS_YND_064","NOCINC00058226=
22","HOPITAL DE LA CAISSE","IHS_YND_024","03-09-2025 15:50:45","03-09-2025 =
15:47:13","03-09-2025 15:55:39","Grid Outage, Site went down before Gen sta=
rt due to poor backup // Grid return","Delor Telezing","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site w=
ent down before Gen start due to poor backup // Grid return","loic.noumsi@m=
atech-cameroun.com","213","03-09-2025 15:50:45","MATECH CMR"
"Closed Complete","Warning","CTR_109","IHS_YND_037","NOCINC0005822405","Nko=
lndongo","","03-09-2025 15:13:36","","","Low voltage. Hybrid gen site .site=
 went down due ""high temp alarm""//we add water and gen manually started,"=
,"MINKA NICOLAS","Warning","Warning","POWER","Warning - Low Voltage","Low v=
oltage. Hybrid gen site .site went down due ""high temp alarm""//we add wat=
er and gen manually started,","loic.noumsi@matech-cameroun.com","3","03-09-=
2025 15:13:36","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_029","NOCINC0005822229","=
Sapeur","","03-09-2025 14:41:04","03-09-2025 14:36:55","03-09-2025 15:33:55=
","Cascaded Incident from TTO6038819","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, no space  // Grid r=
eturn","gerard.tchangoue@matech-cameroun.com","249","03-09-2025 14:41:04","=
MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_030","NOCINC0005822228","=
E-Police","","03-09-2025 14:41:03","03-09-2025 14:36:55","03-09-2025 15:33:=
55","Cascaded Incident from TTO6038819","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, no space  // Grid return","ger=
ard.tchangoue@matech-cameroun.com","248","03-09-2025 14:41:03","MATECH CMR"
"External Reconciliation","Site Down","CTR_323","IHS_YND_043","NOCINC000582=
2222","Emia","IHS_YND_030, IHS_YND_029","03-09-2025 14:40:16","03-09-2025 1=
4:36:55","03-09-2025 15:33:55","Grid-Only site","","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid outage, no space // Grid r=
eturn	","gerard.tchangoue@matech-cameroun.com","202","03-09-2025 14:40:16",=
"MATECH CMR"
"External Reconciliation","Site Down","CTR_310","IHS_YND_057","NOCINC000582=
2216","Mvolye-New","","03-09-2025 14:39:46","03-09-2025 14:06:40","03-09-20=
25 15:06:40","Grid only, no space, awaiting grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid only, no space, a=
waiting grid return","alexandre.kamal@ihstowers.com","1987","03-09-2025 14:=
39:46","MATECH CMR"
"External Reconciliation","Site Down","T0530","IHS_YND_252","NOCINC00058222=
02","Koweit City","","03-09-2025 14:38:29","03-09-2025 14:33:22","03-09-202=
5 20:55:47","Grid outage, site went down due to Sensor Gen HS (oil pressure=
). SS IHS Pascaline is informed // Grid return","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Oil Pressure Sensor Faulty","Grid outa=
ge, site went down due to Sensor Gen HS (oil pressure). SS IHS Pascaline is=
 informed // Grid return","cedric.tiani@matech-cameroun.com","309","03-09-2=
025 14:38:29","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_257","NOCINC0005822061","=
Ahala","","03-09-2025 14:17:04","03-09-2025 14:04:05","03-09-2025 15:43:07"=
,"Cascaded Incident from TTO6038585","Hyemafo Gildas","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, site went down beca=
use Gen started and stopped due to alarm ''oil pressure'' // he reset DG Ca=
rd, site on GEN","gerard.tchangoue@matech-cameroun.com","779","03-09-2025 1=
4:17:04","MATECH CMR"
"External Reconciliation","Site Down","CTR_320","IHS_YND_282","NOCINC000582=
2001","Meyo","IHS_YND_257","03-09-2025 14:12:35","03-09-2025 14:04:05","03-=
09-2025 15:49:19","Grid outage, site went down because Gen started and stop=
ped due to alarm ''oil pressure'' // he reset DG Card, site on GEN","Hyemaf=
o Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, site went down because Gen started and stopped due to alarm ''o=
il pressure'' // he reset DG Card, site on GEN","gerard.tchangoue@matech-ca=
meroun.com","512","03-09-2025 14:12:35","MATECH CMR"
"External Reconciliation","Site Down","T0033","IHS_YND_167","NOCINC00058218=
74","Touring Club International","","03-09-2025 13:52:58","03-09-2025 13:48=
:49","03-09-2025 14:06:35","Site went down due to work of SS HIS PASCALINE =
IS ON SITE //End of work","Albran Byorel","Installation Activity","Passive"=
,"Planned Activity","Installation Activity","Site went down due to work of =
SS HIS PASCALINE IS ON SITE //End of work","cedric.tiani@matech-cameroun.co=
m","250","03-09-2025 13:52:58","MATECH CMR"
"External Reconciliation","Site Down","CTR_310","IHS_YND_057","NOCINC000582=
1816","Mvolye-New","","03-09-2025 13:45:11","03-09-2025 12:57:05","03-09-20=
25 13:56:05","No space to deploy MDG// grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","No space to deploy MDG// gr=
id return","kouoh.jean@ihstowers.com","2888","03-09-2025 13:45:11","MATECH =
CMR"
"External Reconciliation","Site Down","","IHS_YND_098","NOCINC0005821798","=
Ekounou","","03-09-2025 13:41:23","03-09-2025 12:48:35","03-09-2025 13:24:1=
2","Cascaded Incident from TTO6038203","Albran Byorel","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue U =3D54,5V site on =
Grid. The Tx FME Brice Tsague (650214096 )from Huawei is informed.","gerard=
.tchangoue@matech-cameroun.com","3168","03-09-2025 13:41:23","MATECH CMR"
"External Reconciliation","Site Down","CTR_047","IHS_YND_012","NOCINC000582=
1765","Elig-Essono","","03-09-2025 13:34:42","03-09-2025 13:24:59","03-09-2=
025 14:25:12","Active: No power issue, site is on grid with Ubaie=3D53.5V, =
The TX FME Armand Nguetsa/691144412  From hawei is informed. (CB=92s disjun=
ction due to clamp=92s issue in the DC BOX (OCM) : DC CABLE DAMAGED. )","Pa=
ul BIBOUM","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","Active: No power issue, site is on grid with Ubaie=
=3D53.5V, The TX FME Armand Nguetsa/691144412  From hawei is informed. (CB=
=92s disjunction due to clamp=92s issue in the DC BOX (OCM) : DC CABLE DAMA=
GED. )","gerard.tchangoue@matech-cameroun.com","584","03-09-2025 13:34:42",=
"MATECH CMR"
"External Reconciliation","Site Down","T0286","IHS_YND_060","NOCINC00058217=
26","Ngoa Ekelle","","03-09-2025 13:28:03","03-09-2025 13:21:52","03-09-202=
5 15:41:16","Grid outage.gen failed to star due to card GE dysfunctionning =
(with false alarm ""Low oil pressure"") // We reset card GE and gen manuall=
y started (investigation ongoing)	","Paul BIBOUM","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to star due t=
o card GE dysfunctionning (with false alarm ""Low oil pressure"") // We res=
et card GE and gen manually started (investigation ongoing)	","cedric.tiani=
@matech-cameroun.com","372","03-09-2025 13:28:03","MATECH CMR"
"External Reconciliation","Site Down","CTR_025","IHS_YND_238","NOCINC000582=
1695","Mendong","","03-09-2025 13:21:24","03-09-2025 13:16:17","03-09-2025 =
17:49:28","Grid outage, site down due to Gen overload (15KVA//130A) // Grid=
 return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, site down due to Gen overload (15KVA//130A) // Grid =
return","gerard.tchangoue@matech-cameroun.com","309","03-09-2025 13:21:24",=
"MATECH CMR"
"External Reconciliation","Site Down","T1278","IHS_YND_802","NOCINC00058216=
63","NYOM FACE MAETUR","","03-09-2025 13:14:27","03-09-2025 13:06:12","03-0=
9-2025 13:28:52","Grid outage, Site went down before Gen start due to poor =
backup // GRID return","Fabrice Pouakam","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // GRID return","cedric.tiani@matech-camerou=
n.com","497","03-09-2025 13:14:27","MATECH CMR"
"External Reconciliation","Site Down","CTR_389","IHS_YND_066","NOCINC000582=
1662","GSO","IHS_YND_098, IHS_YND_067","03-09-2025 13:14:19","03-09-2025 13=
:18:35","03-09-2025 13:24:12","No power issue U =3D54,5V site on Grid. The =
Tx FME Brice Tsague (650214096 )from Huawei is informed.","MINKA NICOLAS","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue U =3D54,5V site on Grid. The Tx FME Brice Tsague =
(650214096 )from Huawei is informed.","gerard.tchangoue@matech-cameroun.com=
","2869","03-09-2025 13:14:19","MATECH CMR"
"External Reconciliation","Site Down","T0322","IHS_YND_312","NOCINC00058216=
56","Nkolnda","","03-09-2025 13:13:42","03-09-2025 13:06:36","03-09-2025 14=
:02:08","Grid fluctuation, site went down before Gen start due to poor batt=
ery backup // Gen started automatically","Albran Byorel","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid fluctuation,=
 site went down before Gen start due to poor battery backup // Gen started =
automatically","cedric.tiani@matech-cameroun.com","428","03-09-2025 13:13:4=
2","MATECH CMR"
"External Reconciliation","Site Down","CTR_661","IHS_YND_067","NOCINC000582=
1648","Nkoa Ayos","","03-09-2025 13:12:04","03-09-2025 12:48:35","03-09-202=
5 13:24:12","Site impacted by GSO","MINKA NICOLAS","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue U =3D54,5V site on Grid=
. The Tx FME Brice Tsague (650214096 )from Huawei is informed.","gerard.tch=
angoue@matech-cameroun.com","1720","03-09-2025 13:12:04","MATECH CMR"
"External Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058214=
95","Cite des nations","","03-09-2025 12:41:05","03-09-2025 12:38:56","03-0=
9-2025 13:46:58","Grid Outage, Site went down due to MPR DYSFUNCTIONNING on=
 site // He reset the MPR, site on Gen","Paul BIBOUM","Equipment Repair","P=
assive","Rectifier","Rectifier Cabinet","Grid Outage, Site went down due to=
 MPR DYSFUNCTIONNING on site // He reset the MPR, site on Gen","cedric.tian=
i@matech-cameroun.com","130","03-09-2025 12:41:05","MATECH CMR"
"External Reconciliation","Site Down","T3216","IHS_YND_762","NOCINC00058214=
61","Nkolfon Cimencam","","03-09-2025 12:34:17","03-09-2025 12:29:52","03-0=
9-2025 12:33:59","Grid outage, Site went down before Gen start due to poor =
backup // Gen Started automatically","Hyemafo Gildas","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site we=
nt down before Gen start due to poor backup // Gen Started automatically","=
cedric.tiani@matech-cameroun.com","293","03-09-2025 12:34:17","MATECH CMR"
"External Reconciliation","Site Down","T2588","IHS_YND_742","NOCINC00058213=
97","Mendong NB","","03-09-2025 12:25:32","03-09-2025 12:20:21","03-09-2025=
 15:54:54","Grid only, No space to deploy // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid only, No space t=
o deploy // Grid return","cedric.tiani@matech-cameroun.com","312","03-09-20=
25 12:25:32","MATECH CMR"
"External Reconciliation","Site Down","T1394","IHS_YND_511","NOCINC00058212=
93","Etoug ebe Carrefour","","03-09-2025 12:07:50","03-09-2025 12:04:43","0=
3-09-2025 12:10:20","Grid outage site went down before gen started due to p=
oor battery backup// Gen manually started","Hyemafo Gildas","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage si=
te went down before gen started due to poor battery backup// Gen manually s=
tarted","cedric.tiani@matech-cameroun.com","188","03-09-2025 12:07:50","MAT=
ECH CMR"
"External Reconciliation","Site Down","T3447","IHS_YND_713","NOCINC00058211=
78","NKONGKARAK","","03-09-2025 11:55:27","03-09-2025 11:52:17","03-09-2025=
 12:09:03","Grid outage, Site went down because Gen started and stopped due=
 to High temp alarm //He added water and Gen start manually","TIENTCHEU NZE=
TCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Te=
mp - Coolant Level Issue","Grid outage, Site went down because Gen started =
and stopped due to High temp alarm //He added water and Gen start manually"=
,"cedric.tiani@matech-cameroun.com","191","03-09-2025 11:55:27","MATECH CMR=
"
"External Reconciliation","Site Down","T1546","IHS_YND_165","NOCINC00058211=
69","Ahala","","03-09-2025 11:54:02","03-09-2025 11:50:54","03-09-2025 12:0=
4:45","Grid fluctuation,site went down because gen failed to start due to G=
rid bad voltage//site on Gen","MINKA NICOLAS","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid fluctuation,site went dow=
n because gen failed to start due to Grid bad voltage//site on Gen","cedric=
.tiani@matech-cameroun.com","189","03-09-2025 11:54:02","MATECH CMR"
"External Reconciliation","Site Down","T1257","IHS_YND_800","NOCINC00058210=
65","ODZA CITE MBIA","","03-09-2025 11:37:33","03-09-2025 11:35:20","03-09-=
2025 12:17:00","Gid outage,site went down because Gen started and stopped d=
ue to Alarm*Overvoltage*//He reset the Gen card and started the Gen manuall=
y","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Gid outage,site went down because Gen started and stopped due to Al=
arm*Overvoltage*//He reset the Gen card and started the Gen manually","cedr=
ic.tiani@matech-cameroun.com","134","03-09-2025 11:37:33","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_024","NOCINC0005820965","=
Garbati building","","03-09-2025 11:24:05","03-09-2025 11:21:29","03-09-202=
5 11:23:59","Cascaded Incident from TTO6037423","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid Outage, Site wen=
t down before Gen start due to poor backup // Gen Started Automatically","c=
edric.tiani@matech-cameroun.com","156","03-09-2025 11:24:05","MATECH CMR"
"External Reconciliation","Site Down","T1547","IHS_YND_064","NOCINC00058209=
62","HOPITAL DE LA CAISSE","IHS_YND_024","03-09-2025 11:23:38","03-09-2025 =
11:21:29","03-09-2025 11:23:59","Grid Outage, Site went down before Gen sta=
rt due to poor backup // Gen Started Automatically","Delor Telezing","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
Outage, Site went down before Gen start due to poor backup // Gen Started A=
utomatically","cedric.tiani@matech-cameroun.com","130","03-09-2025 11:23:38=
","MATECH CMR"
"External Reconciliation","Site Down","T1394","IHS_YND_511","NOCINC00058209=
57","Etoug ebe Carrefour","","03-09-2025 11:22:55","03-09-2025 11:20:37","0=
3-09-2025 11:38:25","Grid outage site went down before gen started due to p=
oor battery backup// Gen manually started","Hyemafo Gildas","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage si=
te went down before gen started due to poor battery backup// Gen manually s=
tarted","cedric.tiani@matech-cameroun.com","139","03-09-2025 11:22:55","MAT=
ECH CMR"
"External Reconciliation","Site Down","","IHS_YND_732","NOCINC0005820694","=
Nsam escale LP","","03-09-2025 10:48:05","03-09-2025 10:43:21","03-09-2025 =
10:49:44","Cascaded Incident from TTO6037123","","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down before gen=
 started due to poor battery backup// Grid returned","cedric.tiani@matech-c=
ameroun.com","284","03-09-2025 10:48:05","MATECH CMR"
"External Reconciliation","Site Down","T0476","IHS_YND_163","NOCINC00058206=
91","Nsam Sofavinc","IHS_YND_732","03-09-2025 10:47:30","03-09-2025 10:43:2=
1","03-09-2025 10:49:44","Grid outage site went down before gen started due=
 to poor battery backup// Grid returned","MINKA NICOLAS","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site =
went down before gen started due to poor battery backup// Grid returned","c=
edric.tiani@matech-cameroun.com","250","03-09-2025 10:47:30","MATECH CMR"
"External Reconciliation","Site Down","T1394","IHS_YND_511","NOCINC00058206=
13","Etoug ebe Carrefour","","03-09-2025 10:34:13","03-09-2025 10:31:03","0=
3-09-2025 10:49:59","Grid outage site went down before gen started due to p=
oor battery backup// Grid returned","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage site went=
 down before gen started due to poor battery backup// Grid returned","cedri=
c.tiani@matech-cameroun.com","191","03-09-2025 10:34:13","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_019","NOCINC0005820566","=
Hotel de Ville Yde","","03-09-2025 10:25:24","03-09-2025 10:22:14","03-09-2=
025 10:25:14","Cascaded Incident from TTO6036966","Paul BIBOUM","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid Only, No space to=
 deploy MGE // Grid return","gerard.tchangoue@matech-cameroun.com","190","0=
3-09-2025 10:25:24","MATECH CMR"
"External Reconciliation","Site Down","CTR_038","IHS_YND_052","NOCINC000582=
0557","NR-Bastos","IHS_YND_019","03-09-2025 10:24:27","03-09-2025 10:22:14"=
,"03-09-2025 10:25:14","Grid Only, No space to deploy MGE // Grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
Only, No space to deploy MGE // Grid return","gerard.tchangoue@matech-camer=
oun.com","135","03-09-2025 10:24:27","MATECH CMR"
"External Reconciliation","Site Down","T1394","IHS_YND_511","NOCINC00058203=
24","Etoug ebe Carrefour","","03-09-2025 09:50:27","03-09-2025 09:45:19","0=
3-09-2025 09:56:06","Grid outage site went down before gen started due to p=
oor battery backup// Grid returned","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage site went=
 down before gen started due to poor battery backup// Grid returned","cedri=
c.tiani@matech-cameroun.com","309","03-09-2025 09:50:27","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_339","NOCINC0005820322","=
Ebeba","","03-09-2025 09:49:49","03-09-2025 09:41:59","03-09-2025 10:15:03"=
,"Cascaded Incident from TTO6036713","Fanda Brice","Cascade Outage","Active=
","Cascade Active","Cascade Active","ACTIVE / No power issue site on Grid w=
ith U=3D50 V The Tx FME Etienne 695033981 of huawei is informed","cedric.ti=
ani@matech-cameroun.com","470","03-09-2025 09:49:49","MATECH CMR"
"External Reconciliation","Site Down","T0150","IHS_YND_347","NOCINC00058203=
19","Nkeng likok","IHS_YND_339","03-09-2025 09:49:31","03-09-2025 09:41:59"=
,"03-09-2025 10:15:03","ACTIVE / No power issue site on Grid with U=3D50 V =
The Tx FME Etienne 695033981 of huawei is informed","Kemeni Franklin","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","ACTIVE / No power issue site on Grid with U=3D50 V The Tx FME Etienn=
e 695033981 of huawei is informed","cedric.tiani@matech-cameroun.com","453"=
,"03-09-2025 09:49:31","MATECH CMR"
"External Reconciliation","Site Down","T1394","IHS_YND_511","NOCINC00058200=
13","Etoug ebe Carrefour","","03-09-2025 08:52:25","03-09-2025 08:50:58","0=
3-09-2025 09:08:13","Grid outage site went down before gen started due to p=
oor battery backup// Grid returned","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage site went=
 down before gen started due to poor battery backup// Grid returned","cedri=
c.tiani@matech-cameroun.com","88","03-09-2025 08:52:25","MATECH CMR"
"External Reconciliation","Site Down","CTR_911","IHS_YND_762","NOCINC000581=
9113","Nkolfon Cimencam","","03-09-2025 03:15:21","03-09-2025 01:39:59","03=
-09-2025 09:37:51","Grid outage, site went down because Gen failed to start=
 due to alarm ""low oil pressure""//We added oil and gen manually started",=
"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pr=
essure","Grid outage, site went down because Gen failed to start due to ala=
rm ""low oil pressure""//We added oil and gen manually started","franck.nko=
mot@matech-cameroun.com","5744","03-09-2025 03:15:21","MATECH CMR"
"External Reconciliation","Site Down","CTR_164","IHS_YND_257","NOCINC000581=
8682","Ahala","","03-09-2025 00:46:58","03-09-2025 00:45:35","03-09-2025 01=
:18:34","site went down because gen failed to start due to grid bad voltage=
// He bypassed Grid and Gen manually started","Hyemafo Gildas","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","site went dow=
n because gen failed to start due to grid bad voltage// He bypassed Grid an=
d Gen manually started","franck.nkomot@matech-cameroun.com","85","03-09-202=
5 00:46:58","MATECH CMR"
"External Reconciliation","Site Down","T1546","IHS_YND_165","NOCINC00058186=
51","Ahala","","03-09-2025 00:28:19","03-09-2025 00:21:42","03-09-2025 00:3=
2:42","Grid outage, Site went down due to Gen overload (15KVA, 350A) //Site=
 stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down due to Gen overload (15KVA, 350A) =
//Site stabilized","franck.nkomot@matech-cameroun.com","992","03-09-2025 00=
:28:19","MATECH CMR"
"External Reconciliation","Site Down","CTR_109","IHS_YND_037","NOCINC000581=
8584","Nkolndongo","","03-09-2025 00:07:21","03-09-2025 00:05:14","03-09-20=
25 01:05:14","Grid outage,gen failed to start due to CB 63A alimented the A=
TS disjuncted//he reamed the CB","MINKA NICOLAS","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Circuit Breaker Issue","Grid outage,gen=
 failed to start due to CB 63A alimented the ATS disjuncted//he reamed the =
CB","franck.nkomot@matech-cameroun.com","128","03-09-2025 00:07:21","MATECH=
 CMR"
"External Reconciliation","Site Down","T1549","IHS_YND_295","NOCINC00058185=
40","NGONA","","02-09-2025 23:49:25","02-09-2025 23:39:59","02-09-2025 23:4=
0:50","wrongly ticket","Mba Lazare Herve","Incorrectly Logged Tickets","Err=
or","Error","Error","wrongly ticket","franck.nkomot@matech-cameroun.com","5=
67","02-09-2025 23:49:25","MATECH CMR"
"External Reconciliation","Site Down","T1394","IHS_YND_511","NOCINC00058184=
95","Etoug ebe Carrefour","","02-09-2025 23:27:07","02-09-2025 23:23:01","0=
2-09-2025 23:41:01","Grid outage site went down before gen started due to p=
oor battery backup// Grid returned","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage site went=
 down before gen started due to poor battery backup// Grid returned","franc=
k.nkomot@matech-cameroun.com","247","02-09-2025 23:27:07","MATECH CMR"
"External Reconciliation","Site Down","CTR_149","IHS_YND_517","NOCINC000581=
8192","Montee-Des-Soeurs","","02-09-2025 22:13:00","02-09-2025 22:12:54","0=
3-09-2025 07:21:55","Acces issue due to night. Grid outage ,site went down =
due to Gen overload (15 KVA/210 A) // Grid return","Hyemafo Gildas","Access=
 Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lo=
rd","Acces issue due to night. Grid outage ,site went down due to Gen overl=
oad (15 KVA/210 A) // Grid return","vanel.mbiada@matech-cameroun.com","8","=
02-09-2025 22:13:00","MATECH CMR"
"External Reconciliation","Site Down","CTR_336","IHS_YND_212","NOCINC000581=
8122","H-General-Yde","","02-09-2025 22:02:11","02-09-2025 21:59:52","02-09=
-2025 22:19:52","Grid outage, Site went down because Gen failed to start du=
e to ATS faulty // Gtrid returned","Siligap Boris","Equipment Repair","Pass=
ive","Control Panel","ATS-AMF Issue","Grid outage, Site went down because G=
en failed to start due to ATS faulty // Gtrid returned","vanel.mbiada@matec=
h-cameroun.com","140","02-09-2025 22:02:11","MATECH CMR"
"External Reconciliation","Site Down","CTR_336","IHS_YND_212","NOCINC000581=
7854","H-General-Yde","","02-09-2025 21:10:22","02-09-2025 21:07:11","02-09=
-2025 21:39:47","Grid outage, Site went down because Gen failed to start du=
e to ATS faulty // Gtrid returned","Siligap Boris","Equipment Repair","Pass=
ive","Control Panel","ATS-AMF Issue","Grid outage, Site went down because G=
en failed to start due to ATS faulty // Gtrid returned","vanel.mbiada@matec=
h-cameroun.com","193","02-09-2025 21:10:22","MATECH CMR"
"External Reconciliation","Site Down","T1105","IHS_YND_266","NOCINC00058178=
07","Mimboman4","","02-09-2025 21:02:03","02-09-2025 20:55:14","02-09-2025 =
21:51:59","Site went down due to 02/04 rectifiers alarming on site //He res=
et it","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to 02/04 rectifiers alarming on site //He re=
set it","vanel.mbiada@matech-cameroun.com","411","02-09-2025 21:02:03","MAT=
ECH CMR"
"External Reconciliation","Site Down","CTR_104","IHS_YND_244","NOCINC000581=
7736","Abattoir","","02-09-2025 20:49:05","02-09-2025 20:44:57","02-09-2025=
 21:32:22","Grid outage,Site went down due to Gen overload (20KVA//295A) SS=
 HIS Bernard Atangana is informed and confirmed//Grid return","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
,Site went down due to Gen overload (20KVA//295A) SS HIS Bernard Atangana i=
s informed and confirmed//Grid return","vanel.mbiada@matech-cameroun.com","=
250","02-09-2025 20:49:05","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_801","NOCINC0005817622","=
HOPITAL GENERAL RAIL YDE","","02-09-2025 20:23:01","02-09-2025 20:18:30","0=
2-09-2025 21:34:26","Cascaded Incident from TTO6033692","Delor Telezing","C=
ascade Outage","Passive","Cascade Passive","Cascade Passive","Access issues=
 during the night due to landlord(Gen failed to start investigation ongoing=
)//Grid return","cedric.tiani@matech-cameroun.com","271","02-09-2025 20:23:=
01","MATECH CMR"
"External Reconciliation","Site Down","T0536","IHS_YND_210","NOCINC00058176=
21","Pharmacie Bleue","IHS_YND_801","02-09-2025 20:22:42","02-09-2025 20:18=
:30","02-09-2025 21:34:26","Access issues during the night due to landlord(=
Gen failed to start investigation ongoing)//Grid return","Siligap Boris","A=
ccess Denial","Lease Or Legal","Landlord Related Issues","Access Issue - La=
nd Lord","Access issues during the night due to landlord(Gen failed to star=
t investigation ongoing)//Grid return","cedric.tiani@matech-cameroun.com","=
253","02-09-2025 20:22:42","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_528","NOCINC0005817607","=
MEHANDAN","","02-09-2025 20:18:40","02-09-2025 20:14:54","02-09-2025 21:09:=
29","Cascaded Incident from TTO6033670","Albran Byorel","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause gen fails to start due to battery ge faulty//Gen manually started wit=
h external battery","vanel.mbiada@matech-cameroun.com","226","02-09-2025 20=
:18:40","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_527","NOCINC0005817606","=
Odza II OCM","","02-09-2025 20:18:39","02-09-2025 20:14:54","02-09-2025 21:=
09:29","Cascaded Incident from TTO6033670","Albran Byorel","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 because gen fails to start due to battery ge faulty//Gen manually started =
with external battery","vanel.mbiada@matech-cameroun.com","225","02-09-2025=
 20:18:39","MATECH CMR"
"External Reconciliation","Site Down","CTR_330","IHS_YND_255","NOCINC000581=
7600","Odza-PK10","IHS_YND_527, IHS_YND_528","02-09-2025 20:17:18","02-09-2=
025 20:14:54","02-09-2025 21:09:29","Grid outage, site went down because ge=
n fails to start due to battery ge faulty//Gen manually started with extern=
al battery","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Generator Battery","Grid outage, site went down because gen fails to start=
 due to battery ge faulty//Gen manually started with external battery","van=
el.mbiada@matech-cameroun.com","145","02-09-2025 20:17:18","MATECH CMR"
"External Reconciliation","Site Down","T1284","IHS_YND_248","NOCINC00058175=
74","Biteng","","02-09-2025 20:12:51","02-09-2025 20:11:38","02-09-2025 20:=
21:46","Site went down due to DISJUNCTION of CB(125A) in PWC that tripped M=
TN //He rearmed it and site on Grid","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site wen=
t down due to DISJUNCTION of CB(125A) in PWC that tripped MTN //He rearmed =
it and site on Grid","cedric.tiani@matech-cameroun.com","74","02-09-2025 20=
:12:51","MATECH CMR"
"External Reconciliation","Site Down","T1249","IHS_YND_798","NOCINC00058175=
33","AKAK Nkozoa","","02-09-2025 20:03:07","02-09-2025 19:55:54","02-09-202=
5 21:42:15","Grid outage,site went down due to Gen overload(11KVA//185A )SS=
 HIS Felix Bate //He reduiced the load and manually started the Gen","Fabri=
ce Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage,site went down due to Gen overload(11KVA//185A )SS HIS Felix Bate /=
/He reduiced the load and manually started the Gen","cedric.tiani@matech-ca=
meroun.com","434","02-09-2025 20:03:07","MATECH CMR"
"External Reconciliation","Site Down","T0394","IHS_YND_241","NOCINC00058175=
27","Etoudi","","02-09-2025 19:59:35","02-09-2025 19:57:21","02-09-2025 20:=
16:55","Grid outage .site went down due to gen overload(20kva,300 A) SS HIS=
 Bernard Atangana is informed //He reduiced the load and started the Gen ma=
nually","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage .site went down due to gen overload(20kva,300 A) SS H=
IS Bernard Atangana is informed //He reduiced the load and started the Gen =
manually","cedric.tiani@matech-cameroun.com","135","02-09-2025 19:59:35","M=
ATECH CMR"
"External Reconciliation","Site Down","T1244","IHS_YND_796","NOCINC00058175=
16","Nkoabang Ebolmedjock","","02-09-2025 19:57:56","02-09-2025 19:56:46","=
02-09-2025 20:56:31","Grid outage,site went down because Gen failed to star=
t due to Gen card dysfunctionning//He reset it and started the Gen manually=
 ","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Grid outage,site went down because Gen failed to start due to Ge=
n card dysfunctionning//He reset it and started the Gen manually ","cedric.=
tiani@matech-cameroun.com","72","02-09-2025 19:57:56","MATECH CMR"
"External Reconciliation","Site Down","T0056","IHS_YND_189","NOCINC00058175=
14","Paradis Hotel","","02-09-2025 19:57:15","02-09-2025 19:56:09","02-09-2=
025 20:42:59","Grid Outage, site went down because Gen Overload (12.5Kva, 1=
00A) SS IHS BLAISE RAOUL ETCHEU is confirmed//Grid return","Siligap Boris",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, sit=
e went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL ETCHEU=
 is confirmed//Grid return","cedric.tiani@matech-cameroun.com","67","02-09-=
2025 19:57:15","MATECH CMR"
"External Reconciliation","Site Down","T1324","IHS_YND_307","NOCINC00058174=
51","Ebogo","","02-09-2025 19:49:14","02-09-2025 19:48:02","02-09-2025 20:0=
0:45","Active// No Power issue on site Ubaie 56V site on Grid, Julien /6930=
95849 from Huawei is informed","Siligap Boris","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Powe=
r issue on site Ubaie 56V site on Grid, Julien /693095849 from Huawei is in=
formed","cedric.tiani@matech-cameroun.com","73","02-09-2025 19:49:14","MATE=
CH CMR"
"External Reconciliation","Site Down","CTR_080","IHS_YND_298","NOCINC000581=
7356","Olembe","","02-09-2025 19:25:19","02-09-2025 19:22:34","02-09-2025 1=
9:41:40","Site went down because gen start and stopped due to grid bad volt=
age// Grid stabilized","Fabrice Pouakam","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","Site went down because gen start an=
d stopped due to grid bad voltage// Grid stabilized","vanel.mbiada@matech-c=
ameroun.com","167","02-09-2025 19:25:19","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_024","NOCINC0005817344","=
Garbati building","","02-09-2025 19:21:23","02-09-2025 19:20:48","02-09-202=
5 19:22:59","Cascaded Incident from TTO6033366","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid Outage, Site wen=
t down before Gen start due to poor backup // Gen Started Automatically","c=
edric.tiani@matech-cameroun.com","35","02-09-2025 19:21:23","MATECH CMR"
"External Reconciliation","Site Down","T1547","IHS_YND_064","NOCINC00058173=
40","HOPITAL DE LA CAISSE","IHS_YND_024","02-09-2025 19:20:55","02-09-2025 =
19:20:48","02-09-2025 19:22:59","Grid Outage, Site went down before Gen sta=
rt due to poor backup // Gen Started Automatically","Delor Telezing","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
Outage, Site went down before Gen start due to poor backup // Gen Started A=
utomatically","cedric.tiani@matech-cameroun.com","8","02-09-2025 19:20:55",=
"MATECH CMR"
"External Reconciliation","Site Down","T2829","IHS_YND_526","NOCINC00058172=
94","Nkoabang2","","02-09-2025 19:10:51","02-09-2025 19:09:19","02-09-2025 =
19:11:37","Grid outage, site went down due to gen overload (22KVA, 330A), S=
S Blaise IHS is informed // Site stabilised","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down=
 due to gen overload (22KVA, 330A), SS Blaise IHS is informed // Site stabi=
lised","cedric.tiani@matech-cameroun.com","95","02-09-2025 19:10:51","MATEC=
H CMR"
"External Reconciliation","Site Down","T1232","IHS_YND_792","NOCINC00058172=
71","NKOABANG NKOLO 3","","02-09-2025 19:07:14","02-09-2025 19:02:02","02-0=
9-2025 19:11:22","Active: no power issue, site is on gen with Ubaie=3D51.2V=
, lionel adjep (655184876) from Huawei is informed","Mba Lazare Herve","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active: no power issue, site is on gen with Ubaie=3D51.2V, lionel a=
djep (655184876) from Huawei is informed","cedric.tiani@matech-cameroun.com=
","313","02-09-2025 19:07:14","MATECH CMR"
"External Reconciliation","Site Down","CTR_230","IHS_YND_393","NOCINC000581=
7267","Ezezang","","02-09-2025 19:06:23","02-09-2025 19:02:09","02-09-2025 =
19:56:14","Grid outage, Site went down because gen stopped due to belt cut =
// He changed belt(A-38) and Gen manually started","Parker Tchoup","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Fan Belt","Grid outage, Site went d=
own because gen stopped due to belt cut // He changed belt(A-38) and Gen ma=
nually started","vanel.mbiada@matech-cameroun.com","255","02-09-2025 19:06:=
23","MATECH CMR"
"External Reconciliation","Site Down","T0351","IHS_YND_146","NOCINC00058170=
23","Nsimeyong","","02-09-2025 18:19:29","02-09-2025 18:13:06","02-09-2025 =
19:24:15","Site went down due to CB(63A) in PWC  that tripped MTN down due =
to high charged //He replaced by a CB(125A)","MINKA NICOLAS","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Sit=
e went down due to CB(63A) in PWC  that tripped MTN down due to high charge=
d //He replaced by a CB(125A)","ludivine.ngamaleu@ihstowers.com","384","02-=
09-2025 18:19:29","MATECH CMR"
"External Reconciliation","Site Down","T1832","IHS_YND_216","NOCINC00058169=
35","Eleveur","","02-09-2025 17:54:34","02-09-2025 14:26:25","02-09-2025 17=
:29:44","Site went down becaause MTN depart was  vandalised (1.5 m2 of 25mm=
2 was stolen on site)//Cable has been replaced by 16mm2 ","Siligap Boris","=
Site Asset Theft","Theft","Theft","DC Cable Stolen","Site went down becaaus=
e MTN depart was  vandalised (1.5 m2 of 25mm2 was stolen on site)//Cable ha=
s been replaced by 16mm2 ","cedric.tiani@matech-cameroun.com","12490","02-0=
9-2025 17:54:34","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_381","NOCINC0005816524","=
Boumnyebel","","02-09-2025 16:44:39","02-09-2025 16:14:57","02-09-2025 16:2=
1:12","Cascaded Incident from TTO6032180","Kemeni Franklin","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue site on Gen wi=
th U=3D53V Freddy (690419006) from Huawei is informed and up 04:21 PM","oli=
vier.kwedi@ihstowers.com","1782","02-09-2025 16:44:39","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_378","NOCINC0005816500","=
Eseka Town","","02-09-2025 16:41:40","02-09-2025 16:14:57","02-09-2025 16:2=
1:12","Cascaded Incident from TTO6032374 - Cascade Removed From TTO6032374"=
,"Kemeni Franklin","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","No power issue site on Gen with U=3D53V Freddy (690419006) from Huawei=
 is informed and up 04:21 PM","vanel.mbiada@matech-cameroun.com","3975","02=
-09-2025 16:41:40","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_453","NOCINC0005816501","=
Song-bong","","02-09-2025 16:41:40","02-09-2025 16:14:57","02-09-2025 16:21=
:12","Cascaded Incident from TTO6032374 - Cascade Removed From TTO6032374",=
"Kemeni Franklin","Cascade Outage","Active","Cascade Active","Cascade Activ=
e","No power issue site on Gen with U=3D53V Freddy (690419006) from Huawei =
is informed and up 04:21 PM","vanel.mbiada@matech-cameroun.com","4011","02-=
09-2025 16:41:40","MATECH CMR"
"External Reconciliation","Site Down","CTR_067","IHS_YND_377","NOCINC000581=
6490","Eseka OCM","","02-09-2025 16:40:09","02-09-2025 16:14:57","02-09-202=
5 16:21:12","","Kemeni Franklin","Cascade Outage","Active","Cascade Active"=
,"Cascade Active","No power issue site on Gen with U=3D53V Freddy (69041900=
6) from Huawei is informed and up 04:21 PM","vanel.mbiada@matech-cameroun.c=
om","3927","02-09-2025 16:40:09","MATECH CMR"
"External Reconciliation","Site Down","T0476","IHS_YND_163","NOCINC00058163=
09","Nsam Sofavinc","","02-09-2025 16:16:48","02-09-2025 16:09:32","02-09-2=
025 16:15:04","Grid outage, Site went down before Gen start due to poor bac=
kup/ // Gen automatically started","MINKA NICOLAS","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup/ // Gen automatically started","ce=
dric.tiani@matech-cameroun.com","437","02-09-2025 16:16:48","MATECH CMR"
"External Reconciliation","Site Down","T0603","IHS_YND_069","NOCINC00058162=
79","Efoulan MTN","","02-09-2025 16:10:23","02-09-2025 16:08:58","02-09-202=
5 16:18:18","Grid outage, Site went down before Gen start due to poor backu=
p/ // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup/ // Grid return","cedric.tiani@matech-cameroun.com=
","86","02-09-2025 16:10:23","MATECH CMR"
"External Reconciliation","Site Down","T1864","IHS_YND_244","NOCINC00058161=
95","Abattoir","","02-09-2025 15:58:00","02-09-2025 15:56:51","02-09-2025 1=
6:22:59","Grid outage,Site went down due to Gen overload (20KVA//295A) SS H=
IS Bernard Atangana is informed and confirmed//He reduiced load and started=
 Gen manually","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage,Site went down due to Gen overload (20KVA//295=
A) SS HIS Bernard Atangana is informed and confirmed//He reduiced load and =
started Gen manually","cedric.tiani@matech-cameroun.com","71","02-09-2025 1=
5:58:00","MATECH CMR"
"External Reconciliation","Site Down","CTR_464","IHS_YND_674","NOCINC000581=
6169","Mfou EPC","","02-09-2025 15:51:10","02-09-2025 15:43:59","02-09-2025=
 16:03:20","Site went down due to CB(63A) in PWC that tripped ocm is faulty=
//He replaced by CB(125A)","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down due=
 to CB(63A) in PWC that tripped ocm is faulty//He replaced by CB(125A)","va=
nel.mbiada@matech-cameroun.com","433","02-09-2025 15:51:10","MATECH CMR"
"External Reconciliation","Site Down","T1249","IHS_YND_798","NOCINC00058160=
30","AKAK Nkozoa","","02-09-2025 15:25:52","02-09-2025 15:19:43","02-09-202=
5 16:02:28","Grid fluctuation, site went down because Gen started and stopp=
ed to start due to grid bad voltage // He bypassed the grid and started Gen=
 manually","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Grid fluctuation, site went down because Gen st=
arted and stopped to start due to grid bad voltage // He bypassed the grid =
and started Gen manually","cedric.tiani@matech-cameroun.com","370","02-09-2=
025 15:25:52","MATECH CMR"
"External Reconciliation","Site Down","CTR_310","IHS_YND_057","NOCINC000581=
5983","Mvolye-New","","02-09-2025 15:17:00","02-09-2025 15:14:15","02-09-20=
25 15:37:51","Active// No power Issue Site on Grid Ubaie =3D51.1V, The TX F=
ME Mbah Hosiah (674007438) is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power Is=
sue Site on Grid Ubaie =3D51.1V, The TX FME Mbah Hosiah (674007438) is info=
rmed","vanel.mbiada@matech-cameroun.com","167","02-09-2025 15:17:00","MATEC=
H CMR"
"External Reconciliation","Site Down","CTR_093","IHS_YND_188","NOCINC000581=
5745","H-Paradis","","02-09-2025 14:30:34","02-09-2025 14:22:20","02-09-202=
5 16:55:33","Grid Outage, No space to deploy MGE // grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, N=
o space to deploy MGE // grid return","vanel.mbiada@matech-cameroun.com","4=
95","02-09-2025 14:30:34","MATECH CMR"
"External Reconciliation","Site Down","T0563","IHS_YND_332","NOCINC00058156=
44","NKOMEKUI OCM","","02-09-2025 14:16:49","02-09-2025 14:14:40","02-09-20=
25 17:18:41","No power issue site on Gen with U=3D54.5 V The Tx Fme Mohamad=
ou mouam // 691144435 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue site on Gen with U=3D54.5 V The Tx Fme Mohamadou =
mouam // 691144435 from Huawei is informed","cedric.tiani@matech-cameroun.c=
om","131","02-09-2025 14:16:49","MATECH CMR"
"External Reconciliation","Site Down","CTR_633","IHS_YND_241","NOCINC000581=
5502","Etoudi","","02-09-2025 13:51:39","02-09-2025 13:48:34","02-09-2025 1=
3:55:21","Active: no power issue, site is on grid with Ubaie Ubaie=3D53V, A=
rmand Nguetsa(691144412) from Huawei is informed","Fabrice Pouakam","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: no power issue, site is on grid with Ubaie Ubaie=3D53V, Armand=
 Nguetsa(691144412) from Huawei is informed","vanel.mbiada@matech-cameroun.=
com","187","02-09-2025 13:51:39","MATECH CMR"
"External Reconciliation","Site Down","T0563","IHS_YND_332","NOCINC00058154=
76","NKOMEKUI OCM","","02-09-2025 13:48:21","02-09-2025 13:43:55","02-09-20=
25 13:44:13","No power issue site on Gen with U=3D54.5 V The Tx Fme Mohamad=
ou mouam // 691144435 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue site on Gen with U=3D54.5 V The Tx Fme Mohamadou =
mouam // 691144435 from Huawei is informed","loic.noumsi@matech-cameroun.co=
m","268","02-09-2025 13:48:21","MATECH CMR"
"External Reconciliation","Site Down","T1832","IHS_YND_216","NOCINC00058153=
99","Eleveur","","02-09-2025 13:36:21","02-09-2025 13:31:49","02-09-2025 14=
:25:31","No power issue on site UB=3D52.1V site on Grid THE TX FME SYMPHORI=
EN (650257151) from HUAWEI is informed","Siligap Boris","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site UB=3D52.1V site on Grid THE TX FME SYMPHORIEN (650257151) f=
rom HUAWEI is informed","loic.noumsi@matech-cameroun.com","273","02-09-2025=
 13:36:21","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_422","NOCINC0005815202","=
Botmakak","","02-09-2025 13:03:48","02-09-2025 12:01:59","02-09-2025 13:04:=
28","Cascaded Incident from TTO6030575","Kemeni Franklin","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage,site went down b=
ecause Gen started and stopped with *unknown alarm* //He reset the Gen card=
 and started the Gen manually","alexandre.kamal@ihstowers.com","3709","02-0=
9-2025 13:03:48","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_373","NOCINC0005815199","=
Maloun","","02-09-2025 13:03:47","02-09-2025 12:01:59","02-09-2025 13:04:28=
","Cascaded Incident from TTO6030575","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,site went down bec=
ause Gen started and stopped with *unknown alarm* //He reset the Gen card a=
nd started the Gen manually","alexandre.kamal@ihstowers.com","3708","02-09-=
2025 13:03:47","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_375","NOCINC0005815200","=
Ngoung","","02-09-2025 13:03:47","02-09-2025 12:01:59","02-09-2025 13:04:28=
","Cascaded Incident from TTO6030575","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,site went down bec=
ause Gen started and stopped with *unknown alarm* //He reset the Gen card a=
nd started the Gen manually","alexandre.kamal@ihstowers.com","3708","02-09-=
2025 13:03:47","MATECH CMR"
"External Reconciliation","Site Down","CTR_310","IHS_YND_057","NOCINC000581=
5167","Mvolye-New","","02-09-2025 12:57:51","02-09-2025 12:48:44","02-09-20=
25 14:57:37","No space to deploy MDG// grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","No space to deploy MDG// gr=
id return","alexandre.kamal@ihstowers.com","549","02-09-2025 12:57:51","MAT=
ECH CMR"
"External Reconciliation","Site Down","CTR_973","IHS_YND_796","NOCINC000581=
5123","Nkoabang Ebolmedjock","","02-09-2025 12:53:00","02-09-2025 12:46:54"=
,"02-09-2025 12:54:12","Active//No power issue, Site on Gen. Notice that it=
 is impacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare H=
erve","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matec=
h-cameroun.com","369","02-09-2025 12:53:00","MATECH CMR"
"External Reconciliation","Site Down","CTR_911","IHS_YND_762","NOCINC000581=
5052","Nkolfon Cimencam","","02-09-2025 12:37:56","02-09-2025 12:35:47","02=
-09-2025 12:40:59","Grid Outage, site went down due to work ( Oil add) Poor=
 battery backup // End of work and Site on Gen","Hyemafo Gildas","Equipment=
 Replacement","Passive","Planned Activity","Planned Activity - Passive","Gr=
id Outage, site went down due to work ( Oil add) Poor battery backup // End=
 of work and Site on Gen","vanel.mbiada@matech-cameroun.com","131","02-09-2=
025 12:37:56","MATECH CMR"
"External Reconciliation","Site Down","CTR_104","IHS_YND_244","NOCINC000581=
4983","Abattoir","","02-09-2025 12:23:54","02-09-2025 12:22:46","02-09-2025=
 12:38:05","Grid outage,Site went down due to Gen overload (20KVA//295A) SS=
 HIS Bernard Atangana is informed and confirmed //Grid return","Fabrice Pou=
akam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outag=
e,Site went down due to Gen overload (20KVA//295A) SS HIS Bernard Atangana =
is informed and confirmed //Grid return","vanel.mbiada@matech-cameroun.com"=
,"70","02-09-2025 12:23:54","MATECH CMR"
"External Reconciliation","Site Down","T1394","IHS_YND_511","NOCINC00058149=
18","Etoug ebe Carrefour","","02-09-2025 12:16:21","02-09-2025 12:10:10","0=
2-09-2025 12:16:09","Site went down due to 01/04 rectifiers dysfunctionning=
 // He reset it, site on Grid","Hyemafo Gildas","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down due to 01/04 rectifiers dy=
sfunctionning // He reset it, site on Grid","loic.noumsi@matech-cameroun.co=
m","372","02-09-2025 12:16:21","MATECH CMR"
"External Reconciliation","Site Down","CTR_005","IHS_YND_374","NOCINC000581=
4888","Matomb","IHS_YND_373, IHS_YND_375, IHS_EDA_101, IHS_YND_422","02-09-=
2025 12:09:45","02-09-2025 12:01:59","02-09-2025 13:04:28","Grid outage,sit=
e went down because Gen started and stopped with *unknown alarm* //He reset=
 the Gen card and started the Gen manually","Kemeni Franklin","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went do=
wn because Gen started and stopped with *unknown alarm* //He reset the Gen =
card and started the Gen manually","vanel.mbiada@matech-cameroun.com","502"=
,"02-09-2025 12:09:45","MATECH CMR"
"External Reconciliation","Site Down","T1249","IHS_YND_798","NOCINC00058147=
35","AKAK Nkozoa","","02-09-2025 11:52:52","02-09-2025 11:48:46","02-09-202=
5 12:00:04","Grid fluctuation, site went down because Gen started and stopp=
ed to start due to grid bad voltage // He bypassed the grid and started Gen=
 manually","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Grid fluctuation, site went down because Gen st=
arted and stopped to start due to grid bad voltage // He bypassed the grid =
and started Gen manually","loic.noumsi@matech-cameroun.com","247","02-09-20=
25 11:52:52","MATECH CMR"
"Closed Complete","Warning","CTR_005","IHS_YND_374","NOCINC0005814709","Mat=
omb","","02-09-2025 11:47:13","","","DG stopped due to over frequency alarm=
 // DG card reset and Gen started","Kemeni Franklin","Warning","Warning","P=
OWER","Warning - Gen Failure","DG stopped due to over frequency alarm // DG=
 card reset and Gen started","loic.noumsi@matech-cameroun.com","3","02-09-2=
025 11:47:13","MATECH CMR"
"External Reconciliation","Site Down","CTR_104","IHS_YND_244","NOCINC000581=
4687","Abattoir","","02-09-2025 11:41:29","02-09-2025 11:39:23","02-09-2025=
 12:00:00","Grid outage, Gen overload(22 kva //280A ) //load reduction and =
site on GE","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, Gen overload(22 kva //280A ) //load reduction an=
d site on GE","vanel.mbiada@matech-cameroun.com","128","02-09-2025 11:41:29=
","MATECH CMR"
"External Reconciliation","Site Down","CTR_274","IHS_YND_116","NOCINC000581=
4276","Stade-Abega","","02-09-2025 10:39:44","02-09-2025 10:33:37","02-09-2=
025 11:02:56","No power issue on site and site impacted by Ekounou II that =
is not managed by us","Mba Lazare Herve","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 and site impacted by Ekounou II that is not managed by us","vanel.mbiada@m=
atech-cameroun.com","369","02-09-2025 10:39:44","MATECH CMR"
"External Reconciliation","Site Down","CTR_104","IHS_YND_244","NOCINC000581=
4162","Abattoir","","02-09-2025 10:22:29","02-09-2025 10:20:22","02-09-2025=
 10:28:31","Grid outage, Gen overload(22 kva //280A ) //load reduction and =
site on GE","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, Gen overload(22 kva //280A ) //load reduction an=
d site on GE","vanel.mbiada@matech-cameroun.com","129","02-09-2025 10:22:29=
","MATECH CMR"
"External Reconciliation","Site Down","CTR_310","IHS_YND_057","NOCINC000581=
4020","Mvolye-New","","02-09-2025 09:54:02","02-09-2025 09:50:53","02-09-20=
25 11:05:53","No space to deploy MDG, awaiting grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spa=
ce // Grid returned
","vanel.mbiada@matech-cameroun.com","190","02-09-2025 09:54:02","MATECH CM=
R"
"External Reconciliation","Site Down","T1835","IHS_YND_160","NOCINC00058138=
56","Complex Beac II","","02-09-2025 09:26:33","02-09-2025 09:22:34","02-09=
-2025 14:37:25","Site went down because he has been vandalized (power cable=
s have been stolen) // Our FME replaced the DC current (4 m) on site and si=
te on Grid ","Albran Byorel","Site Asset Theft","Theft","Theft","DC Cable S=
tolen","Site went down because he has been vandalized (power cables have be=
en stolen) // Our FME replaced the DC current (4 m) on site and site on Gri=
d ","loic.noumsi@matech-cameroun.com","240","02-09-2025 09:26:33","MATECH C=
MR"
"External Reconciliation","Site Down","T1835","IHS_YND_160","NOCINC00058137=
33","Complex Beac II","","02-09-2025 09:04:04","02-09-2025 08:55:57","02-09=
-2025 09:05:52"," Site went down because he has been vandalized (power cabl=
es have been stolen) // Our FME connected the remaining cables on site, Sit=
e on Grid","Albran Byorel","Site Intrusion","Intrusion On Site","Intrusion =
On Site","Intrusion - Vandalism/Sabotage"," Site went down because he has b=
een vandalized (power cables have been stolen) // Our FME connected the rem=
aining cables on site, Site on Grid","loic.noumsi@matech-cameroun.com","488=
","02-09-2025 09:04:04","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_801","NOCINC0005813653","=
HOPITAL GENERAL RAIL YDE","","02-09-2025 08:51:01","02-09-2025 08:42:25","0=
2-09-2025 10:34:34","Cascaded Incident from TTO6029193","Delor Telezing","C=
ascade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage, =
site went down because gen failed to start due to gen card faulty // Gen st=
arted manually","loic.noumsi@matech-cameroun.com","516","02-09-2025 08:51:0=
1","MATECH CMR"
"External Reconciliation","Site Down","T0536","IHS_YND_210","NOCINC00058136=
37","Pharmacie Bleue","IHS_YND_801","02-09-2025 08:45:37","02-09-2025 08:42=
:25","02-09-2025 10:34:34","Grid outage, site went down because gen failed =
to start due to gen card faulty // Gen started manually","Siligap Boris","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, =
site went down because gen failed to start due to gen card faulty // Gen st=
arted manually","loic.noumsi@matech-cameroun.com","193","02-09-2025 08:45:3=
7","MATECH CMR"
"External Reconciliation","Site Down","T1869","IHS_YND_528","NOCINC00058136=
05","MEHANDAN","","02-09-2025 08:39:38","02-09-2025 08:36:30","02-09-2025 1=
0:27:48","Grid outage.gen failed to start due to automation failure//Gen ma=
nually started ","Albran Byorel","Equipment Repair","Passive","Control Pane=
l","ATS-AMF Issue","Grid outage.gen failed to start due to automation failu=
re//Gen manually started ","loic.noumsi@matech-cameroun.com","189","02-09-2=
025 08:39:38","MATECH CMR"
"Cancelled","Warning","CTR_578","IHS_YND_017","NOCINC0005813601","H-Deputes=
","","02-09-2025 08:37:51","","","","","","","","","","alexandre.kamal@ihst=
owers.com","4","02-09-2025 08:37:51","MATECH CMR"
"External Reconciliation","Site Down","T0056","IHS_YND_189","NOCINC00058135=
23","Paradis Hotel","","02-09-2025 08:18:40","02-09-2025 08:17:04","02-09-2=
025 16:53:46","Grid Outage, site went down because Gen Overload (12.5Kva, 1=
00A) SS IHS BLAISE RAOUL ETCHEU is confirmed//Grid return","Siligap Boris",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, sit=
e went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL ETCHEU=
 is confirmed//Grid return","loic.noumsi@matech-cameroun.com","98","02-09-2=
025 08:18:40","MATECH CMR"
"External Reconciliation","Site Down","T0917","IHS_YND_371","NOCINC00058134=
44","Minka","","02-09-2025 08:02:14","02-09-2025 08:01:02","02-09-2025 08:4=
7:31","Grid outage, site went down because Gen failed to start due to PWC d=
ysfunctionning // He reset it, Site on Gen ","Fanda Brice","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site w=
ent down because Gen failed to start due to PWC dysfunctionning // He reset=
 it, Site on Gen ","loic.noumsi@matech-cameroun.com","75","02-09-2025 08:02=
:14","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_129","NOCINC0005812893","=
Bastos-BAT","","02-09-2025 06:08:35","02-09-2025 05:53:14","02-09-2025 06:3=
3:34","Cascaded Incident from TTO6028373","Mboua Thierry","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Access issue due to landlord=
//Grid outage, Site went down because gen failed to start due to automatism=
 dysfunctionning // Grid return","franck.nkomot@matech-cameroun.com","921",=
"02-09-2025 06:08:35","MATECH CMR"
"External Reconciliation","Site Down","T3151","IHS_YND_192","NOCINC00058128=
79","Dragage","","02-09-2025 06:04:40","02-09-2025 05:55:59","02-09-2025 05=
:56:44","Active//No power issue, site is on Grid with Ubaie=3D53.4V, TX FME=
 Eloundou bertrand (652586578) from Huawei is informed","Mboua Thierry","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue, site is on Grid with Ubaie=3D53.4 V, TX FM=
E Eloundou bertrand (652586578) from Huawei is informed","franck.nkomot@mat=
ech-cameroun.com","522","02-09-2025 06:04:40","MATECH CMR"
"External Reconciliation","Site Down","T0772","IHS_YND_207","NOCINC00058128=
66","ARMP Building","IHS_YND_129","02-09-2025 05:57:26","02-09-2025 05:53:1=
4","02-09-2025 06:33:34","Access issue due to landlord//Grid outage, Site w=
ent down because gen failed to start due to automatism dysfunctionning // G=
rid return","Mboua Thierry","Access Denial","Lease Or Legal","Landlord Rela=
ted Issues","Access Issue - Land Lord","Access issue due to landlord//Grid =
outage, Site went down because gen failed to start due to automatism dysfun=
ctionning // Grid return","franck.nkomot@matech-cameroun.com","253","02-09-=
2025 05:57:26","MATECH CMR"
"External Reconciliation","Site Down","T0210","IHS_YND_206","NOCINC00058123=
31","ARMP","","02-09-2025 02:18:20","02-09-2025 02:08:59","02-09-2025 06:34=
:53","Access issue due to landlord//Site went down because Gen failed to st=
art due to Ge card dysfunctionning // Grid return","Mboua Thierry","Access =
Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lor=
d","Access issue due to landlord//Site went down because Gen failed to star=
t due to Ge card dysfunctionning // Grid return","franck.nkomot@matech-came=
roun.com","562","02-09-2025 02:18:20","MATECH CMR"
"External Reconciliation","Site Down","CTR_529","IHS_YND_316","NOCINC000581=
2304","Akak-Nkozoa-MTN-IHS","","02-09-2025 02:07:48","01-09-2025 17:59:09",=
"01-09-2025 18:00:33","no power issue on site ,site on Gen with Ubaie=3D50.=
4 V The TX FME Synohorien//675295205 from Huawei is informed","Fabrice Poua=
kam","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","no power issue on site ,site on Gen with Ubaie=3D50.4 V Th=
e TX FME Synohorien//675295205 from Huawei is informed","vanel.mbiada@matec=
h-cameroun.com","29322","02-09-2025 02:07:48","MATECH CMR"
"External Reconciliation","Site Down","T1835","IHS_YND_160","NOCINC00058123=
00","Complex Beac II","","02-09-2025 02:07:10","02-09-2025 01:58:52","02-09=
-2025 01:59:22","Our FME Albran reports that the Site went down because he =
has been vandalized (power cables have been stolen) // Our FME connected th=
e remaining cables on site, Site on Grid","Albran Byorel","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no po=
wer issue on site ,site on Grid with Ubaie=3D54.6V The TX FME Henri//691145=
055 from Huawei is informed","franck.nkomot@matech-cameroun.com","499","02-=
09-2025 02:07:10","MATECH CMR"
"External Reconciliation","Site Down","CTR_937","IHS_YND_013","NOCINC000581=
2147","Laboratoire T.Bella","","02-09-2025 01:29:41","02-09-2025 01:20:57",=
"02-09-2025 13:57:35","","Paul BIBOUM","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","Grid only site/No space to deploye MDG/Awaiting=
 Grid return","vanel.mbiada@matech-cameroun.com","999","02-09-2025 01:29:41=
","MATECH CMR"
"External Reconciliation","Site Down","CTR_369","IHS_YND_019","NOCINC000581=
2140","Hotel de Ville Yde","","02-09-2025 01:26:27","02-09-2025 01:20:57","=
02-09-2025 13:57:35","","Paul BIBOUM","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid only site/No space to deploye MDG/Awaiting =
Grid return","vanel.mbiada@matech-cameroun.com","1024","02-09-2025 01:26:27=
","MATECH CMR"
"External Reconciliation","Site Down","CTR_038","IHS_YND_052","NOCINC000581=
2137","NR-Bastos","IHS_YND_019, IHS_YND_013","02-09-2025 01:25:35","02-09-2=
025 01:20:57","02-09-2025 13:57:35","Grid Only, No space to deploy MGE // G=
rid return","","Grid Supply","Passive","Grid","National Grid - Grid Outage =
Issue","Grid Only, No space to deploy MGE // Grid return","vanel.mbiada@mat=
ech-cameroun.com","279","02-09-2025 01:25:35","MATECH CMR"
"External Reconciliation","Site Down","CTR_132","IHS_YND_107","NOCINC000581=
2006","NR-Omnisport","","02-09-2025 01:02:20","02-09-2025 00:55:06","02-09-=
2025 07:06:08","ZTE bay malfunction // reconfiguration of the ZTE bay","Del=
or Telezing","Access Denial","Lease Or Legal","Landlord Related Issues","Ac=
cess Issue - Land Lord","ZTE bay malfunction // reconfiguration of the ZTE =
bay","vanel.mbiada@matech-cameroun.com","435","02-09-2025 01:02:20","MATECH=
 CMR"
"External Reconciliation","Site Down","CTR_237","IHS_YND_261","NOCINC000581=
1888","Barriere","","02-09-2025 00:51:05","02-09-2025 00:45:22","02-09-2025=
 03:08:29","Grid outage, site went down because gen ran until fuel shortage=
 // he tilted the tank","Hyemafo Gildas","Fuel Outage","Passive","Diesel","=
Diesel Outage","Grid outage, site went down because gen ran until fuel shor=
tage // he tilted the tank","vanel.mbiada@matech-cameroun.com","346","02-09=
-2025 00:51:05","MATECH CMR"
"External Reconciliation","Site Down","T1835","IHS_YND_160","NOCINC00058118=
11","Complex Beac II","","02-09-2025 00:31:22","02-09-2025 00:27:28","02-09=
-2025 00:37:28","Grid outage, Site went down because disjunction of CB (32A=
) in DC BOX MTN // He rearmed CB(32A), site on Gen","Albran Byorel","Equipm=
ent Repair","Passive","Control Panel","BTS Breaker Tripped","Grid outage, S=
ite went down because disjunction of CB (32A) in DC BOX MTN // He rearmed C=
B(32A), site on Gen","franck.nkomot@matech-cameroun.com","235","02-09-2025 =
00:31:22","MATECH CMR"
"External Reconciliation","Site Down","T0210","IHS_YND_206","NOCINC00058117=
27","ARMP","","02-09-2025 00:02:45","01-09-2025 23:57:30","02-09-2025 00:29=
:30","Site down because Gen started and stopped due to GE card faulty// He =
reset the Card GE and put site on Gen","Mboua Thierry","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Site down because Gen started a=
nd stopped due to GE card faulty// He reset the Card GE and put site on Gen=
","franck.nkomot@matech-cameroun.com","316","02-09-2025 00:02:45","MATECH C=
MR"
"External Reconciliation","Site Down","T2570","IHS_YND_749","NOCINC00058113=
45","ODZA MINKAN EDIBI ASSI","","01-09-2025 22:34:18","01-09-2025 22:30:12"=
,"02-09-2025 14:11:38","Grid outage,site went down because Gen failed to st=
art due to Gen overload(12.5 kva //180A )SS HIS Francois is informed // Gri=
d return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage,site went down because Gen failed to start due to Gen=
 overload(12.5 kva //180A )SS HIS Francois is informed // Grid return","fra=
nck.nkomot@matech-cameroun.com","247","01-09-2025 22:34:18","MATECH CMR"
"External Reconciliation","Site Down","T2584","IHS_YND_741","NOCINC00058112=
65","Mvog Betsi Hospital","","01-09-2025 22:18:03","01-09-2025 22:14:58","0=
1-09-2025 22:19:58","Grid outage, Site went down before Gen start due to po=
or backup // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup // Grid return","franck.nkomot@matech-came=
roun.com","186","01-09-2025 22:18:03","MATECH CMR"
"External Reconciliation","Site Down","T1832","IHS_YND_216","NOCINC00058111=
90","Eleveur","","01-09-2025 22:04:56","01-09-2025 22:02:28","01-09-2025 22=
:25:28","No power issue on site UB=3D50.5V site on Grid THE TX FME SYMPHORI=
EN (650257151) from HUAWEI is informed","Siligap Boris","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site UB=3D50.5V site on Grid THE TX FME SYMPHORIEN (650257151) f=
rom HUAWEI is informed","cedric.tiani@matech-cameroun.com","149","01-09-202=
5 22:04:56","MATECH CMR"
"External Reconciliation","Site Down","T1835","IHS_YND_160","NOCINC00058111=
77","Complex Beac II","","01-09-2025 22:03:54","01-09-2025 21:56:34","02-09=
-2025 00:12:34","Our FME Albran reports that the Site went down because he =
has been vandalized (power cables have been stolen) // Our FME connected th=
e remaining cables on site, Site on Grid","Albran Byorel","Site Intrusion",=
"Intrusion On Site","Intrusion On Site","Intrusion - Vandalism/Sabotage","O=
ur FME Albran reports that the Site went down because he has been vandalize=
d (power cables have been stolen) // Our FME connected the remaining cables=
 on site, Site on Grid","cedric.tiani@matech-cameroun.com","441","01-09-202=
5 22:03:54","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_528","NOCINC0005810441","=
MEHANDAN","","01-09-2025 20:07:27","01-09-2025 20:00:44","01-09-2025 21:09:=
15","Cascaded Incident from TTO6025683","Albran Byorel","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen failed to start due to Gen card faulty // Grid return","vanel.mbia=
da@matech-cameroun.com","403","01-09-2025 20:07:27","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_527","NOCINC0005810440","=
Odza II OCM","","01-09-2025 20:07:27","01-09-2025 20:00:44","01-09-2025 21:=
09:15","Cascaded Incident from TTO6025683","Albran Byorel","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage site went down =
because Gen failed to start due to Gen card faulty // Grid return","vanel.m=
biada@matech-cameroun.com","403","01-09-2025 20:07:27","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_327","NOCINC0005810419","=
Nsimalen OCM","","01-09-2025 20:04:08","01-09-2025 20:00:44","01-09-2025 21=
:09:15","Cascaded Incident from TTO6025683","Albran Byorel","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage site went down=
 because Gen failed to start due to Gen card faulty // Grid return","vanel.=
mbiada@matech-cameroun.com","204","01-09-2025 20:04:08","MATECH CMR"
"External Reconciliation","Site Down","CTR_215","IHS_YND_311","NOCINC000581=
0408","Nkolda","IHS_YND_527, IHS_YND_528, IHS_YND_327","01-09-2025 20:02:52=
","01-09-2025 20:00:44","01-09-2025 21:09:15","Grid outage site went down b=
ecause Gen failed to start due to Gen card faulty // Grid return","Albran B=
yorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage site went down because Gen failed to start due to Gen card faulty /=
/ Grid return","vanel.mbiada@matech-cameroun.com","129","01-09-2025 20:02:5=
2","MATECH CMR"
"External Reconciliation","Site Down","T1868","IHS_YND_524","NOCINC00058102=
05","ODZA BORNE 10","","01-09-2025 19:28:39","01-09-2025 19:26:26","01-09-2=
025 20:24:28","Grid outage, Site went down because Gen started and stopped =
with ""low oil pressure"" alarm// He reset card GE and gen manually started=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid outage, Site went down because Gen started and stopped with ""l=
ow oil pressure"" alarm// He reset card GE and gen manually started","cedri=
c.tiani@matech-cameroun.com","134","01-09-2025 19:28:39","MATECH CMR"
"External Reconciliation","Site Down","T1249","IHS_YND_798","NOCINC00058099=
21","AKAK Nkozoa","","01-09-2025 18:30:32","01-09-2025 18:25:19","01-09-202=
5 18:30:28","Active// No power issue, site is on Grid with Ubaie=3D50,4 V T=
X FME Symphorien (650257151) from Huawei is informed","Fabrice Pouakam","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active// No power issue, site is on Grid with Ubaie=3D50,4 V TX FM=
E Symphorien (650257151) from Huawei is informed","cedric.tiani@matech-came=
roun.com","314","01-09-2025 18:30:32","MATECH CMR"
"External Reconciliation","Site Down","CTR_025","IHS_YND_238","NOCINC000580=
9596","Mendong","","01-09-2025 17:19:48","01-09-2025 17:16:00","01-09-2025 =
17:19:49","Grid fluctuations, Site went down due to Gen overload (15KVA//13=
0A) // grid stabilized","Hyemafo Gildas","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Grid fluctuations, Site went down due to Gen overl=
oad (15KVA//130A) // grid stabilized","vanel.mbiada@matech-cameroun.com","2=
29","01-09-2025 17:19:48","MATECH CMR"
"External Reconciliation","Site Down","CTR_270","IHS_YND_023","NOCINC000580=
9529","Montesquieux","","01-09-2025 17:03:18","01-09-2025 17:01:03","01-09-=
2025 17:07:42","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid power return","Paul BIBOUM","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Grid power return","vanel.mbiada@matech-c=
ameroun.com","136","01-09-2025 17:03:18","MATECH CMR"
"External Reconciliation","Site Down","T1284","IHS_YND_248","NOCINC00058094=
02","Biteng","","01-09-2025 16:42:48","01-09-2025 16:38:38","01-09-2025 18:=
18:37","Site went down due to CB(125A) in PWC that tripped MTN //He rearmed=
 it and site on Grid ","Mba Lazare Herve","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to =
CB(125A) in PWC that tripped MTN //He rearmed it and site on Grid ","cedric=
.tiani@matech-cameroun.com","251","01-09-2025 16:42:48","MATECH CMR"
"External Reconciliation","Site Down","CTR_321","IHS_YND_085","NOCINC000580=
9198","Briqueterie","","01-09-2025 15:58:55","01-09-2025 15:56:22","02-09-2=
025 18:40:06","Grid outage No space to deployed a mobile Gen// Grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d outage No space to deployed a mobile Gen// Grid return","vanel.mbiada@mat=
ech-cameroun.com","155","01-09-2025 15:58:55","MATECH CMR"
"External Reconciliation","Site Down","T1744","IHS_YND_556","NOCINC00058091=
43","NKOMKANA ELIZA HOTEL","","01-09-2025 15:50:47","01-09-2025 15:47:35","=
01-09-2025 17:07:37","Grid outage, No space to deploy MDG ///Grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage, No space to deploy MDG ///Grid return","cedric.tiani@matech-camerou=
n.com","194","01-09-2025 15:50:47","MATECH CMR"
"External Reconciliation","Site Down","T1568","IHS_YND_084","NOCINC00058091=
31","Briquetterie","","01-09-2025 15:49:51","01-09-2025 15:40:41","01-09-20=
25 16:31:53","Grid outage, No space to deploy MDG//Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No=
 space to deploy MDG//Grid return","cedric.tiani@matech-cameroun.com","551"=
,"01-09-2025 15:49:51","MATECH CMR"
"External Reconciliation","Site Down","CTR_310","IHS_YND_057","NOCINC000580=
8899","Mvolye-New","","01-09-2025 15:13:53","01-09-2025 15:04:56","01-09-20=
25 15:30:04","Active// No power Issue Site on Grid Ubaie =3D51.1V, The TX F=
ME Mbah Hosiah (674007438) is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power Is=
sue Site on Grid Ubaie =3D51.1V, The TX FME Mbah Hosiah (674007438) is info=
rmed","denis.mballa@ihstowers.com","538","01-09-2025 15:13:53","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_376","NOCINC0005808894","=
Mamb","","01-09-2025 15:12:14","01-09-2025 14:58:13","01-09-2025 15:06:49",=
"Cascaded Incident from TTO6023876","Kemeni Franklin","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","Swapp Pwc ongoing","denis.mballa@ih=
stowers.com","841","01-09-2025 15:12:14","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_453","NOCINC0005808893","=
Song-bong","","01-09-2025 15:12:13","01-09-2025 14:58:13","01-09-2025 15:06=
:49","Cascaded Incident from TTO6023876","Kemeni Franklin","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Swapp Pwc ongoing","denis.mbal=
la@ihstowers.com","840","01-09-2025 15:12:13","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_377","NOCINC0005808892","=
Eseka OCM","","01-09-2025 15:12:13","01-09-2025 14:58:13","01-09-2025 15:06=
:49","Cascaded Incident from TTO6023876","Kemeni Franklin","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Swapp Pwc ongoing","denis.mbal=
la@ihstowers.com","840","01-09-2025 15:12:13","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_419","NOCINC0005808891","=
Ngog Mapubi","","01-09-2025 15:12:13","01-09-2025 14:58:13","01-09-2025 15:=
06:49","Cascaded Incident from TTO6023876","Kemeni Franklin","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Swapp Pwc ongoing","denis.mb=
alla@ihstowers.com","840","01-09-2025 15:12:13","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_380","NOCINC0005808889","=
Boumnyebel OCM","","01-09-2025 15:12:12","01-09-2025 14:58:13","01-09-2025 =
15:06:49","Cascaded Incident from TTO6023876","Kemeni Franklin","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","Swapp Pwc ongoing","denis=
.mballa@ihstowers.com","839","01-09-2025 15:12:12","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_378","NOCINC0005808890","=
Eseka Town","","01-09-2025 15:12:12","01-09-2025 14:58:13","01-09-2025 15:0=
6:49","Cascaded Incident from TTO6023876","Kemeni Franklin","Cascade Outage=
","Active","Cascade Active","Cascade Active","Swapp Pwc ongoing","denis.mba=
lla@ihstowers.com","839","01-09-2025 15:12:12","MATECH CMR"
"External Reconciliation","Site Down","CTR_310","IHS_YND_057","NOCINC000580=
8473","Mvolye-New","","01-09-2025 14:30:08","01-09-2025 14:28:58","01-09-20=
25 14:30:32","Grid outage no space to deploy a mobil gen // Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage no space to deploy a mobil gen // Grid return","gerard.tchangoue@mate=
ch-cameroun.com","71","01-09-2025 14:30:08","MATECH CMR"
"External Reconciliation","Site Down","T0563","IHS_YND_332","NOCINC00058084=
08","NKOMEKUI OCM","","01-09-2025 14:14:55","01-09-2025 14:12:48","01-09-20=
25 15:51:23","No power issue site on Gen with U=3D54.5 V The Tx Fme Mohamad=
ou mouam // 691144435 from Huawei is informed.Noticed that there is heavy r=
ain on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
Gen with U=3D54.5 V The Tx Fme Mohamadou mouam // 691144435 from Huawei is =
informed.Noticed that there is heavy rain on site","loic.noumsi@matech-came=
roun.com","129","01-09-2025 14:14:55","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_732","NOCINC0005808316","=
Nsam escale LP","","01-09-2025 14:04:40","01-09-2025 14:02:01","01-09-2025 =
14:09:24","Cascaded Incident from TTO6023350","","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down before Ge=
n start due to poor backup/ // Gen automatically started","loic.noumsi@mate=
ch-cameroun.com","159","01-09-2025 14:04:40","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_327","NOCINC0005808312","=
Nsimalen OCM","","01-09-2025 14:04:17","01-09-2025 13:54:15","01-09-2025 14=
:00:18","Cascaded Incident from TTO6023239","Albran Byorel","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n before Gen start due to poor backup // Grid return","gerard.tchangoue@mat=
ech-cameroun.com","602","01-09-2025 14:04:17","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_527","NOCINC0005808310","=
Odza II OCM","","01-09-2025 14:04:16","01-09-2025 13:54:15","01-09-2025 14:=
00:18","Cascaded Incident from TTO6023239","Albran Byorel","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down=
 before Gen start due to poor backup // Grid return","gerard.tchangoue@mate=
ch-cameroun.com","601","01-09-2025 14:04:16","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_528","NOCINC0005808311","=
MEHANDAN","","01-09-2025 14:04:16","01-09-2025 13:54:15","01-09-2025 14:00:=
18","Cascaded Incident from TTO6023239","Albran Byorel","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
fore Gen start due to poor backup // Grid return","gerard.tchangoue@matech-=
cameroun.com","601","01-09-2025 14:04:16","MATECH CMR"
"External Reconciliation","Site Down","T0476","IHS_YND_163","NOCINC00058083=
09","Nsam Sofavinc","IHS_YND_732","01-09-2025 14:04:08","01-09-2025 14:02:0=
1","01-09-2025 14:09:24","Grid outage, Site went down before Gen start due =
to poor backup/ // Gen automatically started","MINKA NICOLAS","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,=
 Site went down before Gen start due to poor backup/ // Gen automatically s=
tarted","loic.noumsi@matech-cameroun.com","128","01-09-2025 14:04:08","MATE=
CH CMR"
"External Reconciliation","Site Down","CTR_215","IHS_YND_311","NOCINC000580=
8201","Nkolda","IHS_YND_527, IHS_YND_528, IHS_YND_327","01-09-2025 14:00:23=
","01-09-2025 13:54:15","01-09-2025 14:00:18","Grid outage, Site went down =
before Gen start due to poor backup // Grid return","Albran Byorel","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage, Site went down before Gen start due to poor backup // Grid return","=
gerard.tchangoue@matech-cameroun.com","370","01-09-2025 14:00:23","MATECH C=
MR"
"External Reconciliation","Site Down","T1085","IHS_YND_130","NOCINC00058078=
61","Bastos usine","","01-09-2025 13:11:05","01-09-2025 13:08:15","01-09-20=
25 13:09:57","Active//No power issue on site Site on Grid Ubae=3D52,82V, TX=
 FME Eloundou(652586578) from Huawei is informed","Mboua Thierry","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site Site on Grid Ubae=3D52,82V, TX FME Elound=
ou(652586578) from Huawei is informed","loic.noumsi@matech-cameroun.com","1=
71","01-09-2025 13:11:05","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_569","NOCINC0005807660","=
Mendong Maeture","","01-09-2025 12:34:03","01-09-2025 12:24:25","01-09-2025=
 12:37:47","Cascaded Incident from TTO6022548","Hyemafo Gildas","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid fluctuations, Sit=
e went down due to Gen overload (15KVA//130A) // grid stabilized","gerard.t=
changoue@matech-cameroun.com","578","01-09-2025 12:34:03","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_692","NOCINC0005807659","=
Mendong vallee","","01-09-2025 12:34:03","01-09-2025 12:24:25","01-09-2025 =
12:37:47","Cascaded Incident from TTO6022548","Fanda Brice","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid fluctuations, Site we=
nt down due to Gen overload (15KVA//130A) // grid stabilized","gerard.tchan=
goue@matech-cameroun.com","578","01-09-2025 12:34:03","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_236","NOCINC0005807657","=
Montee-Jouvence","","01-09-2025 12:33:39","01-09-2025 12:24:25","01-09-2025=
 12:37:47","Cascaded Incident from TTO6022548","Hyemafo Gildas","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid fluctuations, Sit=
e went down due to Gen overload (15KVA//130A) // grid stabilized","gerard.t=
changoue@matech-cameroun.com","554","01-09-2025 12:33:39","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_526","NOCINC0005807656","=
Nkoabang2","","01-09-2025 12:33:39","01-09-2025 12:24:25","01-09-2025 12:37=
:47","Cascaded Incident from TTO6022548","Mba Lazare Herve","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid fluctuations, Site we=
nt down due to Gen overload (15KVA//130A) // grid stabilized","gerard.tchan=
goue@matech-cameroun.com","554","01-09-2025 12:33:39","MATECH CMR"
"External Reconciliation","Site Down","CTR_479","IHS_YND_580","NOCINC000580=
7651","Marche Odza","","01-09-2025 12:33:21","01-09-2025 12:25:59","01-09-2=
025 12:27:37","Grid Outage, site went down due to poor batterie backup// Ge=
n start automaticaly","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid Outage, site went down due to p=
oor batterie backup// Gen start automaticaly","gerard.tchangoue@matech-came=
roun.com","444","01-09-2025 12:33:21","MATECH CMR"
"External Reconciliation","Site Down","CTR_025","IHS_YND_238","NOCINC000580=
7561","Mendong","IHS_YND_692, IHS_YND_569, IHS_YND_526, IHS_YND_236","01-09=
-2025 12:27:33","01-09-2025 12:24:25","01-09-2025 12:37:47","Grid fluctuati=
ons, Site went down due to Gen overload (15KVA//130A) // grid stabilized","=
Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid fluctuations, Site went down due to Gen overload (15KVA//130A) // grid=
 stabilized","gerard.tchangoue@matech-cameroun.com","189","01-09-2025 12:27=
:33","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_732","NOCINC0005807210","=
Nsam escale LP","","01-09-2025 11:24:44","01-09-2025 11:20:54","01-09-2025 =
11:26:16","Cascaded Incident from TTO6022156","","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down before Ge=
n start due to poor backup/ // Grid return","loic.noumsi@matech-cameroun.co=
m","230","01-09-2025 11:24:44","MATECH CMR"
"External Reconciliation","Site Down","T0476","IHS_YND_163","NOCINC00058072=
08","Nsam Sofavinc","IHS_YND_732","01-09-2025 11:24:10","01-09-2025 11:20:5=
4","01-09-2025 11:26:16","Grid outage, Site went down before Gen start due =
to poor backup/ // Grid return","MINKA NICOLAS","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup/ // Grid return","loic.noumsi@matech-=
cameroun.com","197","01-09-2025 11:24:10","MATECH CMR"
"External Reconciliation","Site Down","T3240","IHS_YND_771","NOCINC00058064=
19","Jouvence Mbenda","","01-09-2025 08:27:51","01-09-2025 08:25:46","01-09=
-2025 08:52:31","Site went down due to disjunction of PWC CB (50 A) // He r=
earmed it, site on GRID","Hyemafo Gildas","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to =
disjunction of PWC CB (50 A) // He rearmed it, site on GRID","loic.noumsi@m=
atech-cameroun.com","127","01-09-2025 08:27:51","MATECH CMR"
"External Reconciliation","Site Down","T0578","IHS_YND_375","NOCINC00058055=
42","Ngoung","","01-09-2025 01:34:26","01-09-2025 01:30:04","01-09-2025 02:=
38:35","Active// No power issue, site is on Gen with Ubaie=3D53V The TX FME=
 Etienne //695033981// from Huawei is informed","Kemeni Franklin","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power issue, site is on Gen with Ubaie=3D53V The TX FME Etie=
nne //695033981// from Huawei is informed","franck.nkomot@matech-cameroun.c=
om","263","01-09-2025 01:34:26","MATECH CMR"
"External Reconciliation","Site Down","T1394","IHS_YND_511","NOCINC00058048=
18","Etoug ebe Carrefour","","31-08-2025 21:50:54","31-08-2025 21:42:59","3=
1-08-2025 22:00:59","Grid outage site went down before gen started due to p=
oor battery backup// Grid returned","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage site went=
 down before gen started due to poor battery backup// Grid returned","franc=
k.nkomot@matech-cameroun.com","476","31-08-2025 21:50:54","MATECH CMR"
"External Reconciliation","Site Down","CTR_370","IHS_YND_274","NOCINC000580=
4359","Emana Lycee","","31-08-2025 20:44:36","31-08-2025 20:40:29","31-08-2=
025 21:15:04","Site went down because gen fails to start due to grid bad vo=
ltage // He bypass grid and manually start the gen","Fabrice Pouakam","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site w=
ent down because gen fails to start due to grid bad voltage // He bypass gr=
id and manually start the gen","edwige.kapawo@matech-cameroun.com","249","3=
1-08-2025 20:44:36","MATECH CMR"
"External Reconciliation","Site Down","CTR_080","IHS_YND_298","NOCINC000580=
4211","Olembe","","31-08-2025 20:22:39","31-08-2025 20:20:34","31-08-2025 2=
0:28:02","Grid fluctuation, Site went down because gen fails to start due t=
o grid bad voltage // He bypass grid and manually start the gen","Fabrice P=
ouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, Site went down because gen fails to start due to g=
rid bad voltage // He bypass grid and manually start the gen","edwige.kapaw=
o@matech-cameroun.com","127","31-08-2025 20:22:39","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_475","NOCINC0005803742","=
Ngoum","","31-08-2025 18:46:05","31-08-2025 18:17:34","31-08-2025 18:18:34"=
,"Cascaded Incident from TTO6018184","Parker Tchoup","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No Power issue on site, Site is on B=
attery; Ubaie =3D 48.4V (Hybrid Gen site with threshold U =3D 47V)=20

TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.
","kombi.samuel@ihstowers.com","1711","31-08-2025 18:46:05","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_454","NOCINC0005803743","=
Ngouetou","","31-08-2025 18:46:05","31-08-2025 18:17:34","31-08-2025 18:18:=
34","Cascaded Incident from TTO6018184 ","Parker Tchoup","Cascade Outage","=
Active","Cascade Active","Cascade Active","No Power issue on site, Site is =
on Battery; Ubaie =3D 48.4V (Hybrid Gen site with threshold U =3D 47V)=20

TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","kombi.samuel@ihstowe=
rs.com","1711","31-08-2025 18:46:05","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_456","NOCINC0005803665","=
MBIMBIM","","31-08-2025 18:30:29","31-08-2025 18:17:34","31-08-2025 18:18:3=
4","Cascaded Incident from TTO6018184","Parker Tchoup","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No Power issue on site, Site is on=
 Battery; Ubaie =3D 48.4V (Hybrid Gen site with threshold U =3D 47V)=20

TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.
","stephane.nkamwa@ihstowers.com","775","31-08-2025 18:30:29","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_460","NOCINC0005803653","=
Matsari","","31-08-2025 18:29:08","31-08-2025 18:17:34","31-08-2025 18:18:3=
4","Cascaded Incident from TTO6018184","Parker Tchoup","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No Power issue on site, Site is on=
 Battery; Ubaie =3D 48.4V (Hybrid Gen site with threshold U =3D 47V)=20

TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.
","stephane.nkamwa@ihstowers.com","694","31-08-2025 18:29:08","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_474","NOCINC0005803654","=
Yoko OCM","","31-08-2025 18:29:08","31-08-2025 18:17:34","31-08-2025 18:18:=
34","Cascaded Incident from TTO6018184","Parker Tchoup","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No Power issue on site, Site is o=
n Battery; Ubaie =3D 48.4V (Hybrid Gen site with threshold U =3D 47V)=20

TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.
","stephane.nkamwa@ihstowers.com","694","31-08-2025 18:29:08","MATECH CMR"
"External Reconciliation","Site Down","T0401","IHS_YND_205","NOCINC00058035=
46","Tongolo MTN","","31-08-2025 18:01:21","31-08-2025 18:00:12","31-08-202=
5 18:50:12","Grid outage site went down because Gen failed to start due to =
Gen card faulty // he reset and started Gen manually","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage si=
te went down because Gen failed to start due to Gen card faulty // he reset=
 and started Gen manually","franck.nkomot@matech-cameroun.com","70","31-08-=
2025 18:01:21","MATECH CMR"
"External Reconciliation","Site Down","CTR_519","IHS_YND_543","NOCINC000580=
3516","Entree Cite Verte","","31-08-2025 17:53:33","31-08-2025 17:52:26","3=
1-08-2025 19:44:24","Active // No power issue, site is on Grid with Ubaie=
=3D54.6V,  the technicien tx Brice Tsague(650214096 / Huawei) is informed",=
"Paul BIBOUM","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active // No power issue, site is on Grid with Ub=
aie=3D54.6V,  the technicien tx Brice Tsague(650214096 / Huawei) is informe=
d","edwige.kapawo@matech-cameroun.com","68","31-08-2025 17:53:33","MATECH C=
MR"
"External Reconciliation","Site Down","T0456","IHS_YND_224","NOCINC00058032=
28","Messa Carriere","","31-08-2025 16:42:50","31-08-2025 16:35:50","31-08-=
2025 16:50:46","Grid outage, site went down before Gen start due to poor ba=
ttery backup // Grid return","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen start due to poor battery backup // Grid return","franck.nkomot@m=
atech-cameroun.com","421","31-08-2025 16:42:50","MATECH CMR"
"External Reconciliation","Site Down","CTR_050","IHS_YND_080","NOCINC000580=
3182","Mini-Ferme","","31-08-2025 16:35:05","31-08-2025 16:33:44","31-08-20=
25 16:36:51","Grid Only, No space to deploy MGE // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No s=
pace to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","82"=
,"31-08-2025 16:35:05","MATECH CMR"
"External Reconciliation","Site Down","T1278","IHS_YND_802","NOCINC00058029=
30","NYOM FACE MAETUR","","31-08-2025 16:12:04","31-08-2025 16:02:59","31-0=
8-2025 16:54:59","Grid fluctuations , site went down because Gen failed to =
start due to Grid bad voltage // He bypassed Grid and started Gen manually"=
,"Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuations , site went down because Gen failed to =
start due to Grid bad voltage // He bypassed Grid and started Gen manually"=
,"franck.nkomot@matech-cameroun.com","547","31-08-2025 16:12:04","MATECH CM=
R"
"External Reconciliation","Site Down","CTR_417","IHS_YND_121","NOCINC000580=
2454","Emombo-Tchad","","31-08-2025 14:29:06","31-08-2025 14:27:57","31-08-=
2025 15:10:42","Grid outage, no space to deploy MGE // grid power return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage, no space to deploy MGE // grid power return","vanel.mbiada@matech-c=
ameroun.com","70","31-08-2025 14:29:06","MATECH CMR"
"External Reconciliation","Site Down","CTR_040","IHS_YND_114","NOCINC000580=
2449","Kondengui","","31-08-2025 14:28:28","31-08-2025 14:26:50","31-08-202=
5 14:52:50","Grid fluctuation, Site went down because Gen failed to start d=
ue to Grid bad voltage //He bypassed Grid and started Gen manualy","Albran =
Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, Site went down because Gen failed to start due to =
Grid bad voltage //He bypassed Grid and started Gen manualy","vanel.mbiada@=
matech-cameroun.com","99","31-08-2025 14:28:28","MATECH CMR"
"External Reconciliation","Site Down","T2570","IHS_YND_749","NOCINC00058023=
25","ODZA MINKAN EDIBI ASSI","","31-08-2025 14:04:36","31-08-2025 14:02:27"=
,"31-08-2025 18:12:02","Grid outage,site went down because Gen failed to st=
art due to Gen overload(12.5 kva //180A )SS HIS Francois is informed // Gri=
d return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage,site went down because Gen failed to start due to Gen=
 overload(12.5 kva //180A )SS HIS Francois is informed // Grid return","ced=
ric.tiani@matech-cameroun.com","130","31-08-2025 14:04:36","MATECH CMR"
"External Reconciliation","Site Down","T1316","IHS_YND_111","NOCINC00058022=
68","Essos Marche","","31-08-2025 13:50:02","31-08-2025 13:45:55","31-08-20=
25 14:57:55","Grid outage, No MDGE to deploy // Grid return","Delor Telezin=
g","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage, No MDGE to deploy // Grid return","vanel.mbiada@matech-cameroun.co=
m","248","31-08-2025 13:50:02","MATECH CMR"
"External Reconciliation","Site Down","CTR_911","IHS_YND_762","NOCINC000580=
2247","Nkolfon Cimencam","","31-08-2025 13:42:08","31-08-2025 13:39:57","31=
-08-2025 14:25:53","	Grid outage.Gen failed to start due to alarm ""low oil=
 pressure""//We add oil and gen manually started","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","	Grid outage.Gen=
 failed to start due to alarm ""low oil pressure""//We add oil and gen manu=
ally started","vanel.mbiada@matech-cameroun.com","132","31-08-2025 13:42:08=
","MATECH CMR"
"External Reconciliation","Site Down","CTR_068","IHS_YND_109","NOCINC000580=
2053","Mobil-Essos","","31-08-2025 12:57:50","31-08-2025 12:21:42","31-08-2=
025 13:08:57","Active// No power issue on site U=3D54,1 V site on grid Bric=
e Tsague (650214096) from huawei is informed","Siligap Boris","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive// No power issue on site U=3D54,1 V site on grid Brice Tsague (650214=
096) from huawei is informed","vanel.mbiada@matech-cameroun.com","2169","31=
-08-2025 12:57:50","MATECH CMR"
"External Reconciliation","Site Down","CTR_104","IHS_YND_244","NOCINC000580=
2024","Abattoir","","31-08-2025 12:51:50","31-08-2025 12:48:37","31-08-2025=
 13:04:49","Grid outage,Site went down because Gen failed to start due to G=
ren overload (20KVA//295A) SS HIS Bernard Atangana is informed and confirme=
d //Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage,Site went down because Gen failed to start d=
ue to Gren overload (20KVA//295A) SS HIS Bernard Atangana is informed and c=
onfirmed //Grid return","vanel.mbiada@matech-cameroun.com","194","31-08-202=
5 12:51:50","MATECH CMR"
"External Reconciliation","Site Down","CTR_075","IHS_YND_133","NOCINC000580=
2014","Elig-Edzoa","","31-08-2025 12:47:59","31-08-2025 12:44:54","31-08-20=
25 17:57:59","Grid only site,No mobile gen available //Grid restored","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only=
 site,No mobile gen available //Grid restored","vanel.mbiada@matech-camerou=
n.com","187","31-08-2025 12:47:59","MATECH CMR"
"External Reconciliation","Site Down","T0065","IHS_YND_735","NOCINC00058019=
91","Maison komkana New","","31-08-2025 12:40:11","31-08-2025 12:38:01","31=
-08-2025 12:40:23","Grid outage, Site went down before Gen start due to poo=
r backup // GRID return","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // GRID return","cedric.tiani@matech-camerou=
n.com","131","31-08-2025 12:40:11","MATECH CMR"
"External Reconciliation","Site Down","CTR_342","IHS_YND_190","NOCINC000580=
1979","Ngousso-II","","31-08-2025 12:35:56","31-08-2025 12:31:49","31-08-20=
25 12:47:23","Grid outage, site went down because gen Overload(22Kva, 300A)=
//Grid return","MFOUAGUEGUE MATHIEU","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid outage, site went down because gen Overload(22Kva=
, 300A)//Grid return","vanel.mbiada@matech-cameroun.com","248","31-08-2025 =
12:35:56","MATECH CMR"
"External Reconciliation","Site Down","T1622","IHS_YND_186","NOCINC00058019=
74","Ngousso Carrefour","","31-08-2025 12:34:12","31-08-2025 12:31:01","31-=
08-2025 12:51:27","Grid outage, site Down due to Gen Overload (20KVA, 280A)=
 //  Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Grid outage, site Down due to Gen Overload (20KVA, 280A) =
//  Grid return","cedric.tiani@matech-cameroun.com","191","31-08-2025 12:34=
:12","MATECH CMR"
"External Reconciliation","Site Down","CTR_336","IHS_YND_212","NOCINC000580=
1968","H-General-Yde","","31-08-2025 12:32:15","31-08-2025 12:29:04","31-08=
-2025 12:38:00","Grid outage, Site went down because Gen failed to start du=
e to ATS faulty // He bypassed it and started Gen manualy","Siligap Boris",=
"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, =
Site went down because Gen failed to start due to ATS faulty // He bypassed=
 it and started Gen manualy","vanel.mbiada@matech-cameroun.com","192","31-0=
8-2025 12:32:15","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_566","NOCINC0005801949","=
Crf Cornier","","31-08-2025 12:26:16","31-08-2025 12:22:28","31-08-2025 14:=
56:19","Cascaded Incident from TTO6016286","MINKA NICOLAS","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage,no space to dep=
loy MGE // Grid returned","vanel.mbiada@matech-cameroun.com","228","31-08-2=
025 12:26:16","MATECH CMR"
"External Reconciliation","Site Down","CTR_071","IHS_YND_112","NOCINC000580=
1946","Madison","IHS_YND_566","31-08-2025 12:25:42","31-08-2025 12:22:28","=
31-08-2025 14:56:19","Grid outage,no space to deploy MGE // Grid returned",=
"MFOUAGUEGUE MATHIEU","Grid Supply","Passive","Grid","National Grid - Grid =
Outage Issue","Grid outage,no space to deploy MGE // Grid returned","vanel.=
mbiada@matech-cameroun.com","195","31-08-2025 12:25:42","MATECH CMR"
"External Reconciliation","Site Down","T0468","IHS_YND_120","NOCINC00058019=
39","Sapeur Mimboman","","31-08-2025 12:23:55","31-08-2025 12:22:38","31-08=
-2025 14:53:38","Site went down because Gen faul to start due to oil pressu=
re sensor faulty // Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Oil Pressure Sensor Faulty","Site went down becaus=
e Gen faul to start due to oil pressure sensor faulty // Grid return","cedr=
ic.tiani@matech-cameroun.com","78","31-08-2025 12:23:55","MATECH CMR"
"External Reconciliation","Site Down","T0532","IHS_YND_239","NOCINC00058019=
35","Mendong2","","31-08-2025 12:23:02","31-08-2025 12:20:56","31-08-2025 1=
2:48:15","Site went down because gen fails to start due to grid bad voltage=
 // He bypass grid and manually start the gen","Hyemafo Gildas","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Site went do=
wn because gen fails to start due to grid bad voltage // He bypass grid and=
 manually start the gen","cedric.tiani@matech-cameroun.com","127","31-08-20=
25 12:23:02","MATECH CMR"
"External Reconciliation","Site Down","CTR_096","IHS_YND_042","NOCINC000580=
1931","Mvog-Ada_OCM","","31-08-2025 12:21:59","31-08-2025 12:16:39","31-08-=
2025 12:38:39","Grid only on site, No space on site to deploy MDGE //Grid r=
eturn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Grid only on site, No space on site to deploy MDGE //Grid return","vanel=
.mbiada@matech-cameroun.com","322","31-08-2025 12:21:59","MATECH CMR"
"External Reconciliation","Site Down","T0394","IHS_YND_241","NOCINC00058019=
22","Etoudi","","31-08-2025 12:20:26","31-08-2025 12:17:18","31-08-2025 12:=
44:09","Grid outage .site went down due to gen overload(20kva,300 A) SS HIS=
 Bernard Atangana is informed // Grid return","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage .site went down=
 due to gen overload(20kva,300 A) SS HIS Bernard Atangana is informed // Gr=
id return","cedric.tiani@matech-cameroun.com","189","31-08-2025 12:20:26","=
MATECH CMR"
"External Reconciliation","Site Down","T0056","IHS_YND_189","NOCINC00058019=
18","Paradis Hotel","","31-08-2025 12:19:37","31-08-2025 12:15:25","31-08-2=
025 13:02:17","Grid Outage, site went down because Gen Overload (12.5Kva, 1=
00A) SS IHS BLAISE RAOUL ETCHEU is confirmed // Grid return","Siligap Boris=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, s=
ite went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL ETCH=
EU is confirmed // Grid return","cedric.tiani@matech-cameroun.com","254","3=
1-08-2025 12:19:37","MATECH CMR"
"External Reconciliation","Site Down","CTR_486","IHS_YND_569","NOCINC000580=
1917","Mendong Maeture","","31-08-2025 12:19:20","31-08-2025 12:11:10","31-=
08-2025 19:45:15","Active//No power issue, site is on grid with Ubaie=3D53V=
, TX FME Mbah hosiah(699699694) from Huawei is informed.","Hyemafo Gildas",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active//No power issue, site is on grid with Ubaie=3D53V, TX FM=
E Mbah hosiah(699699694) from Huawei is informed.","vanel.mbiada@matech-cam=
eroun.com","491","31-08-2025 12:19:20","MATECH CMR"
"External Reconciliation","Site Down","T1744","IHS_YND_556","NOCINC00058019=
15","NKOMKANA ELIZA HOTEL","","31-08-2025 12:19:06","31-08-2025 12:15:56","=
31-08-2025 12:54:37","Grid only, Grid Outage on site, no space to deploy MD=
GE// Grid return","","Grid Supply","Passive","Grid","National Grid - Grid O=
utage Issue","Grid only, Grid Outage on site, no space to deploy MDGE// Gri=
d return","cedric.tiani@matech-cameroun.com","191","31-08-2025 12:19:06","M=
ATECH CMR"
"External Reconciliation","Site Down","T0528","IHS_YND_027","NOCINC00058019=
11","Hopital Central","","31-08-2025 12:18:42","31-08-2025 12:14:32","31-08=
-2025 12:34:34","Grid only, Grid Outage on site, no space to deploy MDGE //=
 Grid return","","Grid Supply","Passive","Grid","National Grid - Grid Outag=
e Issue","Grid only, Grid Outage on site, no space to deploy MDGE // Grid r=
eturn","cedric.tiani@matech-cameroun.com","251","31-08-2025 12:18:42","MATE=
CH CMR"
"External Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00058019=
08","Mokolo Yaounde","","31-08-2025 12:17:39","31-08-2025 12:14:33","31-08-=
2025 12:28:37","Grid only, Grid Outage on site, no space to deploy MDGE // =
Grid return","","Grid Supply","Passive","Grid","National Grid - Grid Outage=
 Issue","Grid only, Grid Outage on site, no space to deploy MDGE // Grid re=
turn","cedric.tiani@matech-cameroun.com","188","31-08-2025 12:17:39","MATEC=
H CMR"
"External Reconciliation","Site Down","T1543","IHS_YND_336","NOCINC00058019=
04","EKIE","","31-08-2025 12:16:36","31-08-2025 12:14:25","31-08-2025 12:45=
:22","Grid Outage, site went down due to Main Gen Faulty // He deploy MGE (=
20KVA)","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Gen=
erator Faulty","Grid Outage, site went down due to Main Gen Faulty // He de=
ploy MGE (20KVA)","cedric.tiani@matech-cameroun.com","131","31-08-2025 12:1=
6:36","MATECH CMR"
"External Reconciliation","Site Down","T0120","IHS_YND_031","NOCINC00058019=
02","Sime Building","","31-08-2025 12:15:34","31-08-2025 12:13:07","31-08-2=
025 12:21:42","Grid outage, Site went down before Gen start due to poor bac=
kup // Gen automatically started","Mboua Thierry","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen automatically started","cedr=
ic.tiani@matech-cameroun.com","148","31-08-2025 12:15:34","MATECH CMR"
"External Reconciliation","Site Down","T0065","IHS_YND_735","NOCINC00058018=
37","Maison komkana New","","31-08-2025 11:59:24","31-08-2025 11:57:18","31=
-08-2025 12:19:40","Grid outage, Site went down before Gen start due to poo=
r backup // GRID return","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // GRID return","cedric.tiani@matech-camerou=
n.com","127","31-08-2025 11:59:24","MATECH CMR"
"External Reconciliation","Site Down","CTR_336","IHS_YND_212","NOCINC000580=
1828","H-General-Yde","","31-08-2025 11:56:44","31-08-2025 11:53:25","31-08=
-2025 11:59:25","Grid outage, Site went down because Gen failed to start du=
e to ATS faulty // He bypassed it and started Gen manualy","Siligap Boris",=
"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, =
Site went down because Gen failed to start due to ATS faulty // He bypassed=
 it and started Gen manualy","vanel.mbiada@matech-cameroun.com","199","31-0=
8-2025 11:56:44","MATECH CMR"
"External Reconciliation","Site Down","CTR_330","IHS_YND_255","NOCINC000580=
1579","Odza-PK10","","31-08-2025 11:07:38","31-08-2025 11:04:29","31-08-202=
5 11:45:38","Grid outage, Site went down because Gen failed to start due to=
 battery Gen Faulty// He started Gen with external battery","Albran Byorel"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid o=
utage, Site went down because Gen failed to start due to battery Gen Faulty=
// He started Gen with external battery","vanel.mbiada@matech-cameroun.com"=
,"190","31-08-2025 11:07:38","MATECH CMR"
"External Reconciliation","Site Down","T1366","IHS_YND_804","NOCINC00058015=
46","BEATITUDE ENTR=C9E PAVE","","31-08-2025 11:02:18","31-08-2025 11:01:10=
","31-08-2025 16:20:39","Site went down because Gen faul to start due to ki=
ck starter faulty // Kick starter has been replaced, Site on Gen","TIENTCHE=
U NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Star=
ter","Site went down because Gen faul to start due to kick starter faulty /=
/ Kick starter has been replaced, Site on Gen","cedric.tiani@matech-camerou=
n.com","68","31-08-2025 11:02:18","MATECH CMR"
"External Reconciliation","Site Down","T1622","IHS_YND_186","NOCINC00058015=
05","Ngousso Carrefour","","31-08-2025 10:55:57","31-08-2025 10:53:35","31-=
08-2025 11:25:51","Grid outage, site Down due to Gen Overload (20KVA, 280A)=
 // Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, site Down due to Gen Overload (20KVA, 280A) /=
/ Grid return","cedric.tiani@matech-cameroun.com","143","31-08-2025 10:55:5=
7","MATECH CMR"
"External Reconciliation","Site Down","CTR_342","IHS_YND_190","NOCINC000580=
1495","Ngousso-II","","31-08-2025 10:54:28","31-08-2025 10:52:21","31-08-20=
25 11:21:33","Grid outage, site Down due to Gen Overload (20KVA, 280A) //Gr=
id return","MFOUAGUEGUE MATHIEU","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, site Down due to Gen Overload (20KVA, 280A) /=
/Grid return","vanel.mbiada@matech-cameroun.com","128","31-08-2025 10:54:28=
","MATECH CMR"
"External Reconciliation","Site Down","T0816","IHS_YND_260","NOCINC00058014=
80","Simbock Maetur","","31-08-2025 10:53:55","31-08-2025 09:01:40","31-08-=
2025 11:30:16","Grid outage,site went down because Gen started and stopped =
to unknown alarrm//He reset the gen card and started the Gen manually","Hye=
mafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage,site went down because Gen started and stopped to unknown ala=
rrm//He reset the gen card and started the Gen manually","cedric.tiani@mate=
ch-cameroun.com","6736","31-08-2025 10:53:55","MATECH CMR"
"External Reconciliation","Site Down","T1868","IHS_YND_524","NOCINC00058013=
89","ODZA BORNE 10","","31-08-2025 10:36:27","31-08-2025 10:35:19","31-08-2=
025 12:11:21","site went down because gen start an stopped due to water inf=
iltration in tank // He purged The tank and Gen manually started","Albran B=
yorel","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Wa=
ter In The Fuel","site went down because gen start an stopped due to water =
infiltration in tank // He purged The tank and Gen manually started","cedri=
c.tiani@matech-cameroun.com","69","31-08-2025 10:36:27","MATECH CMR"
"External Reconciliation","Site Down","T0291","IHS_YND_147","NOCINC00058013=
77","Club France","","31-08-2025 10:34:35","31-08-2025 10:27:23","31-08-202=
5 11:08:21","Grid only site, No space to deploy a MDG // Grid restored","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid on=
ly site, No space to deploy a MDG // Grid restored","cedric.tiani@matech-ca=
meroun.com","433","31-08-2025 10:34:35","MATECH CMR"
"External Reconciliation","Site Down","T0210","IHS_YND_206","NOCINC00058013=
73","ARMP","","31-08-2025 10:33:48","31-08-2025 10:31:32","31-08-2025 11:19=
:05","ACCESS ISSUES due to landlord(Grid outage,gen failed to start investi=
gation ongoing)//Grid return","Mboua Thierry","Access Denial","Lease Or Leg=
al","Landlord Related Issues","Access Issue - Land Lord","ACCESS ISSUES due=
 to landlord(Grid outage,gen failed to start investigation ongoing)//Grid r=
eturn","cedric.tiani@matech-cameroun.com","137","31-08-2025 10:33:48","MATE=
CH CMR"
"External Reconciliation","Site Down","CTR_484","IHS_YND_118","NOCINC000580=
1336","ESSOS OASIS 1111","","31-08-2025 10:26:45","31-08-2025 10:21:36","31=
-08-2025 12:16:37","Grid outage, site went down because Gen failed to start=
 due to PWC dysfuntionning // He reset it, and started Gen manually","Silig=
ap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module Overlo=
aded","Grid outage, site went down because Gen failed to start due to PWC d=
ysfuntionning // He reset it, and started Gen manually","vanel.mbiada@matec=
h-cameroun.com","310","31-08-2025 10:26:45","MATECH CMR"
"External Reconciliation","Site Down","CTR_414","IHS_YND_202","NOCINC000580=
1297","Cite-Verte","","31-08-2025 10:18:32","31-08-2025 10:12:25","31-08-20=
25 10:26:51","Grid, outage , No MG to deploy on site // Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid, outa=
ge , No MG to deploy on site // Grid return","vanel.mbiada@matech-cameroun.=
com","368","31-08-2025 10:18:32","MATECH CMR"
"External Reconciliation","Site Down","T3233","IHS_YND_768","NOCINC00058012=
82","ELOUMDEM CARRIERE 2","","31-08-2025 10:13:42","31-08-2025 10:09:35","3=
1-08-2025 11:03:43","site went down because gen start an stopped due to wat=
er infiltration in tank // He purged The tank and Gen manually started","Fa=
nda Brice","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue =
- Water In The Fuel","site went down because gen start an stopped due to wa=
ter infiltration in tank // He purged The tank and Gen manually started","c=
edric.tiani@matech-cameroun.com","249","31-08-2025 10:13:42","MATECH CMR"
"External Reconciliation","Site Down","T2588","IHS_YND_742","NOCINC00058012=
80","Mendong NB","","31-08-2025 10:12:56","31-08-2025 10:10:48","31-08-2025=
 16:52:59","Grid Only, No space to deploy MDG // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No spa=
ce to deploy MDG // Grid return","cedric.tiani@matech-cameroun.com","129","=
31-08-2025 10:12:56","MATECH CMR"
"External Reconciliation","Site Down","T0294","IHS_YND_016","NOCINC00058012=
57","Maetur","","31-08-2025 10:06:43","31-08-2025 09:57:26","31-08-2025 11:=
16:30","Grid outage, site down due to GE circuit breaker  disjunction // CB=
 rearmed","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - L=
oad Breaker","Grid outage, site down due to GE circuit breaker  disjunction=
 // CB rearmed","cedric.tiani@matech-cameroun.com","558","31-08-2025 10:06:=
43","MATECH CMR"
"External Reconciliation","Site Down","T1582","IHS_YND_138","NOCINC00058012=
46","Nkomkana 2","","31-08-2025 10:03:32","31-08-2025 10:01:22","31-08-2025=
 11:17:02","Grid outage, site went down due to gen overload (240A / 17,5kVA=
) // He reduce the load and manually start the Gen","Mboua Thierry","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went =
down due to gen overload (240A / 17,5kVA) // He reduce the load and manuall=
y start the Gen","cedric.tiani@matech-cameroun.com","131","31-08-2025 10:03=
:32","MATECH CMR"
"External Reconciliation","Site Down","T1742","IHS_YND_042","NOCINC00058012=
43","Mvog-Ada_OCM","","31-08-2025 10:02:22","31-08-2025 09:58:59","31-08-20=
25 11:16:04","Grid only on site, No space on site to deploy MDGE //Grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid only on site, No space on site to deploy MDGE //Grid return","cedric.=
tiani@matech-cameroun.com","205","31-08-2025 10:02:22","MATECH CMR"
"External Reconciliation","Site Down","T1282","IHS_YND_803","NOCINC00058011=
84","Etoug ebe biscuiterie","","31-08-2025 09:47:36","31-08-2025 09:40:22",=
"31-08-2025 10:45:32","Grid outage, site went down because gen failed to st=
art due to gen card faulty //Gen manually started","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site =
went down because gen failed to start due to gen card faulty //Gen manually=
 started","cedric.tiani@matech-cameroun.com","435","31-08-2025 09:47:36","M=
ATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_236","NOCINC0005801144","=
Montee-Jouvence","","31-08-2025 09:34:09","31-08-2025 09:30:31","31-08-2025=
 12:56:00","Cascaded Incident from TTO6015398","Hyemafo Gildas","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid fluctuations, Sit=
e went down due to Gen overload (15KVA//130A) // grid stabilized","vanel.mb=
iada@matech-cameroun.com","218","31-08-2025 09:34:09","MATECH CMR"
"External Reconciliation","Site Down","CTR_025","IHS_YND_238","NOCINC000580=
1138","Mendong","IHS_YND_236","31-08-2025 09:33:40","31-08-2025 09:30:31","=
31-08-2025 12:56:00","Grid fluctuations, Site went down due to Gen overload=
 (15KVA//130A) // grid stabilized","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid fluctuations, Site went down due t=
o Gen overload (15KVA//130A) // grid stabilized","vanel.mbiada@matech-camer=
oun.com","190","31-08-2025 09:33:40","MATECH CMR"
"External Reconciliation","Site Down","T0465","IHS_YND_143","NOCINC00058011=
15","Byemassi Carrefour","","31-08-2025 09:26:07","31-08-2025 09:22:59","31=
-08-2025 11:16:31","Grid Outage, Site went Down due to main Gen faulty // G=
rid return","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - G=
enerator Faulty","Grid Outage, Site went Down due to main Gen faulty // Gri=
d return","cedric.tiani@matech-cameroun.com","189","31-08-2025 09:26:07","M=
ATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_528","NOCINC0005801110","=
MEHANDAN","","31-08-2025 09:24:38","31-08-2025 09:12:02","31-08-2025 11:45:=
28","Cascaded Incident from TTO6015363 - Cascade Removed From TTO6015363 - =
Cascade Removed From TTO6015363","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","(Cascaded bihind NOCINC0005801090) Gr=
id outage, site went down because gen failed to start due to PWC ZTE malfun=
ction // / He reset contoller and Gen manually started","vanel.mbiada@matec=
h-cameroun.com","756","31-08-2025 09:24:38","MATECH CMR"
"External Reconciliation","Site Down","CTR_158","IHS_YND_527","NOCINC000580=
1109","Odza II OCM","IHS_YND_528","31-08-2025 09:24:09","31-08-2025 09:12:0=
2","31-08-2025 11:45:28","(Cascaded bihind NOCINC0005801090) Grid outage, s=
ite went down because gen failed to start due to PWC ZTE malfunction // / H=
e reset contoller and Gen manually started","Albran Byorel","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","(Cascaded bihind N=
OCINC0005801090) Grid outage, site went down because gen failed to start du=
e to PWC ZTE malfunction // / He reset contoller and Gen manually started",=
"vanel.mbiada@matech-cameroun.com","730","31-08-2025 09:24:09","MATECH CMR"
"External Reconciliation","Site Down","CTR_010","IHS_YND_327","NOCINC000580=
1104","Nsimalen OCM","","31-08-2025 09:23:37","31-08-2025 09:12:27","31-08-=
2025 11:20:24","","Albran Byorel","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Grid outage, site went down because gen failed to st=
art due to PWC ZTE malfunction // / He reset contoller and Gen manually sta=
rted","vanel.mbiada@matech-cameroun.com","2043","31-08-2025 09:23:37","MATE=
CH CMR"
"External Reconciliation","Site Down","","IHS_YND_202","NOCINC0005801093","=
Cite-Verte","","31-08-2025 09:20:04","31-08-2025 09:09:40","31-08-2025 09:5=
2:44","Cascaded Incident from TTO6015330","","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down baecause gen =
failed to start due to battery Gen discharged // Gen manually start with ex=
ternal battery","vanel.mbiada@matech-cameroun.com","624","31-08-2025 09:20:=
04","MATECH CMR"
"External Reconciliation","Site Down","CTR_215","IHS_YND_311","NOCINC000580=
1090","Nkolda","IHS_YND_327","31-08-2025 09:19:37","31-08-2025 09:12:27","3=
1-08-2025 11:20:24","Grid outage, site went down because gen failed to star=
t due to PWC ZTE malfunction // / He reset contoller and Gen manually start=
ed","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Grid outage, site went down because gen failed to start du=
e to PWC ZTE malfunction // / He reset contoller and Gen manually started",=
"vanel.mbiada@matech-cameroun.com","431","31-08-2025 09:19:37","MATECH CMR"
"External Reconciliation","Site Down","CTR_122","IHS_YND_230","NOCINC000580=
1081","Meyong-Meyeme","IHS_YND_202","31-08-2025 09:17:48","31-08-2025 09:09=
:40","31-08-2025 09:52:44","Grid outage, site went down baecause gen failed=
 to start due to battery Gen discharged // Gen manually start with external=
 battery","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen=
","ACDG - Generator Battery","Grid outage, site went down baecause gen fail=
ed to start due to battery Gen discharged // Gen manually start with extern=
al battery","vanel.mbiada@matech-cameroun.com","489","31-08-2025 09:17:48",=
"MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_220","NOCINC0005801065","=
Golf Quater","","31-08-2025 09:15:08","31-08-2025 09:09:12","31-08-2025 09:=
52:15","Cascaded Incident from TTO6015285 - Cascade Removed From TTO6015285=
","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Grid outage, site went down due to gen overload (240A / 17,5kVA) // =
He reduce the load and manually start the Gen","vanel.mbiada@matech-camerou=
n.com","87426","31-08-2025 09:15:08","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_563","NOCINC0005801066","=
Bastos Bethesda","","31-08-2025 09:15:08","31-08-2025 09:09:12","31-08-2025=
 09:52:15","Cascaded Incident from TTO6015285 - Cascade Removed From TTO601=
5285","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, site went down due to gen overload (240A / 17,5kVA)=
 // He reduce the load and manually start the Gen","vanel.mbiada@matech-cam=
eroun.com","87356","31-08-2025 09:15:08","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_127","NOCINC0005801067","=
Tsinga","","31-08-2025 09:15:08","31-08-2025 09:09:12","31-08-2025 09:52:15=
","Cascaded Incident from TTO6015285 - Cascade Removed From TTO6015285","Mb=
oua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"Grid outage, site went down due to gen overload (240A / 17,5kVA) // He re=
duce the load and manually start the Gen","vanel.mbiada@matech-cameroun.com=
","87389","31-08-2025 09:15:08","MATECH CMR"
"External Reconciliation","Site Down","T0603","IHS_YND_069","NOCINC00058010=
64","Efoulan MTN","","31-08-2025 09:14:59","31-08-2025 09:13:51","31-08-202=
5 10:05:19","Grid outage, Site went down because Gen started and stopped wi=
th ""low oil pressure"" alarm// He reset card GE and gen manually started",=
"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Grid outage, Site went down because Gen started and stopped with ""low=
 oil pressure"" alarm// He reset card GE and gen manually started","cedric.=
tiani@matech-cameroun.com","69","31-08-2025 09:14:59","MATECH CMR"
"External Reconciliation","Site Down","CTR_427","IHS_YND_200","NOCINC000580=
1057","Nkomkana","IHS_YND_220, IHS_YND_563, IHS_YND_127","31-08-2025 09:13:=
20","31-08-2025 09:09:12","31-08-2025 09:52:15","Grid Only, No space to dep=
loy MDGE // Grid returned","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","Grid Only, No space to deploy MDGE // Grid returned"=
,"vanel.mbiada@matech-cameroun.com","251","31-08-2025 09:13:20","MATECH CMR=
"
"External Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058010=
46","Cite des nations","","31-08-2025 09:11:29","31-08-2025 09:10:23","31-0=
8-2025 10:40:33","Grid Outage, Site went down due to MPR DYSFONNCTION on si=
te  // He reset the MPR","Paul BIBOUM","Equipment Repair","Passive","Rectif=
ier","Rectifier Cabinet","Grid Outage, Site went down due to MPR DYSFONNCTI=
ON on site  // He reset the MPR","cedric.tiani@matech-cameroun.com","67","3=
1-08-2025 09:11:29","MATECH CMR"
"External Reconciliation","Site Down","CTR_198","IHS_YND_126","NOCINC000580=
1045","Bastos-Nylon","","31-08-2025 09:11:19","31-08-2025 10:01:22","31-08-=
2025 11:17:02","","Mboua Thierry","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Grid outage, site went down due to gen overload (240=
A / 17,5kVA) // He reduce the load and manually start the Gen","vanel.mbiad=
a@matech-cameroun.com","4913","31-08-2025 09:11:19","MATECH CMR"
"External Reconciliation","Site Down","T0528","IHS_YND_027","NOCINC00058010=
31","Hopital Central","","31-08-2025 09:08:57","31-08-2025 09:00:41","31-08=
-2025 11:09:15","Grid outage No Space to deploy a MDG //Grid return	","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge No Space to deploy a MDG //Grid return	","cedric.tiani@matech-cameroun.c=
om","497","31-08-2025 09:08:57","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_793","NOCINC0005801024","=
Eloumdem stade","","31-08-2025 09:07:06","31-08-2025 09:01:15","31-08-2025 =
09:23:09","Cascaded Incident from TTO6015251","Fanda Brice","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue site  on batte=
ry  with Threshold  U=3D47.7v TX FME Flubert from Huawei is informed","cedr=
ic.tiani@matech-cameroun.com","351","31-08-2025 09:07:06","MATECH CMR"
"External Reconciliation","Site Down","CTR_157","IHS_YND_140","NOCINC000580=
1018","BISCUITERIE","","31-08-2025 09:05:31","31-08-2025 09:01:23","31-08-2=
025 09:06:21","Grid outage, Site went down because Gen failed to start due =
to PWC ZTE disfunction // Grid return","Paul BIBOUM","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Grid outage, Site went do=
wn because Gen failed to start due to PWC ZTE disfunction // Grid return","=
vanel.mbiada@matech-cameroun.com","249","31-08-2025 09:05:31","MATECH CMR"
"External Reconciliation","Site Down","T0602","IHS_YND_259","NOCINC00058010=
15","Simbock MTN","IHS_YND_793","31-08-2025 09:03:21","31-08-2025 09:01:15"=
,"31-08-2025 09:23:09","No power issue site  on battery  with Threshold  U=
=3D47.7v TX FME Flubert from Huawei is informed","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue site  on battery  with Threshold  U=3D47.7v TX FME Flubert f=
rom Huawei is informed","cedric.tiani@matech-cameroun.com","127","31-08-202=
5 09:03:21","MATECH CMR"
"External Reconciliation","Site Down","T1266","IHS_YND_801","NOCINC00058009=
91","HOPITAL GENERAL RAIL YDE","","31-08-2025 08:57:22","31-08-2025 08:52:4=
8","31-08-2025 10:26:51","","Delor Telezing","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen f=
ailed to start due to gen card faulty // Gen started manually","cedric.tian=
i@matech-cameroun.com","467","31-08-2025 08:57:22","MATECH CMR"
"External Reconciliation","Site Down","T0536","IHS_YND_210","NOCINC00058009=
75","Pharmacie Bleue","IHS_YND_801","31-08-2025 08:56:54","31-08-2025 08:52=
:48","31-08-2025 10:26:51","Grid outage, site went down because gen failed =
to start due to gen card faulty // Gen started manually","Siligap Boris","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, =
site went down because gen failed to start due to gen card faulty // Gen st=
arted manually","cedric.tiani@matech-cameroun.com","247","31-08-2025 08:56:=
54","MATECH CMR"
"External Reconciliation","Site Down","CTR_642","IHS_YND_537","NOCINC000580=
0958","MEFOU ASSI","","31-08-2025 08:53:16","31-08-2025 08:49:07","31-08-20=
25 09:22:03","Active // No power issue site on grid with Ubaie: 55.2V TX FM=
E Flubert (654266068 /Huawei) is informed","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue site on grid with Ubaie: 55.2V TX FME Flubert (654266068=
 /Huawei) is informed","vanel.mbiada@matech-cameroun.com","251","31-08-2025=
 08:53:16","MATECH CMR"
"External Reconciliation","Site Down","CTR_476","IHS_YND_520","NOCINC000580=
0948","SIMBOCK BONAMBAPE","","31-08-2025 08:51:26","31-08-2025 08:49:14","3=
1-08-2025 09:23:45","Grid outage,Site went down because Gen overload(20KVA/=
/300A )SS HIS Felix Bateu is informed//Grid return","Hyemafo Gildas","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went =
down because Gen overload(20KVA//300A )SS HIS Felix Bateu is informed//Grid=
 return","vanel.mbiada@matech-cameroun.com","134","31-08-2025 08:51:26","MA=
TECH CMR"
"External Reconciliation","Site Down","T0373","IHS_YND_097","NOCINC00058009=
43","Kondengui MTN","","31-08-2025 08:50:18","31-08-2025 08:47:09","31-08-2=
025 09:57:26","Grid outage.gen failed to start due to battery GE faulty//Ge=
n manually started with external battery","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to st=
art due to battery GE faulty//Gen manually started with external battery","=
cedric.tiani@matech-cameroun.com","189","31-08-2025 08:50:18","MATECH CMR"
"External Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00058009=
15","Mokolo Yaounde","","31-08-2025 08:42:09","31-08-2025 08:33:55","31-08-=
2025 11:07:52","Grid only, Grid Outage on site, no space to deploy MDGE // =
 Grid return","","Grid Supply","Passive","Grid","National Grid - Grid Outag=
e Issue","Grid only, Grid Outage on site, no space to deploy MDGE //  Grid =
return","cedric.tiani@matech-cameroun.com","496","31-08-2025 08:42:09","MAT=
ECH CMR"
"External Reconciliation","Site Down","T1744","IHS_YND_556","NOCINC00058009=
01","NKOMKANA ELIZA HOTEL","","31-08-2025 08:35:47","31-08-2025 08:32:30","=
31-08-2025 11:10:47","Grid only, Grid Outage on site, no space to deploy MD=
GE // Grid return","","Grid Supply","Passive","Grid","National Grid - Grid =
Outage Issue","Grid only, Grid Outage on site, no space to deploy MDGE // G=
rid return","cedric.tiani@matech-cameroun.com","198","31-08-2025 08:35:47",=
"MATECH CMR"
"External Reconciliation","Site Down","T0120","IHS_YND_031","NOCINC00058008=
99","Sime Building","","31-08-2025 08:35:15","31-08-2025 08:29:26","31-08-2=
025 08:37:01","Grid outage, Site went down before Gen start due to poor bac=
kup // Gen automatically started","Mboua Thierry","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen automatically started","cedr=
ic.tiani@matech-cameroun.com","350","31-08-2025 08:35:15","MATECH CMR"
"External Reconciliation","Site Down","T1738","IHS_YND_560","NOCINC00058008=
95","Cite des nations","","31-08-2025 08:34:01","31-08-2025 08:29:44","31-0=
8-2025 08:37:37","Grid outage, site went down before Gen started due to Poo=
r battery backup // Grid stabilised","Paul BIBOUM","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before Gen started due to Poor battery backup // Grid stabilised","ced=
ric.tiani@matech-cameroun.com","258","31-08-2025 08:34:01","MATECH CMR"
"External Reconciliation","Site Down","CTR_248","IHS_YND_304","NOCINC000580=
0888","Nkolondom","","31-08-2025 08:32:39","31-08-2025 08:27:29","31-08-202=
5 09:17:10","Grid outage,site went down because GEN failed to start due to =
emergency stop button faulty//He bypassed it and manually started the Gen",=
"Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency=
 Stop","Grid outage,site went down because GEN failed to start due to emerg=
ency stop button faulty//He bypassed it and manually started the Gen","vane=
l.mbiada@matech-cameroun.com","312","31-08-2025 08:32:39","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_732","NOCINC0005800883","=
Nsam escale LP","","31-08-2025 08:32:15","31-08-2025 08:29:41","31-08-2025 =
08:35:23","Cascaded Incident from TTO6015109","","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down before Ge=
n start due to poor backup/ // Gen automatically started","cedric.tiani@mat=
ech-cameroun.com","154","31-08-2025 08:32:15","MATECH CMR"
"External Reconciliation","Site Down","T0476","IHS_YND_163","NOCINC00058008=
82","Nsam Sofavinc","IHS_YND_732","31-08-2025 08:31:49","31-08-2025 08:29:4=
1","31-08-2025 08:35:23","Grid outage, Site went down before Gen start due =
to poor backup/ // Gen automatically started","MINKA NICOLAS","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,=
 Site went down before Gen start due to poor backup/ // Gen automatically s=
tarted","cedric.tiani@matech-cameroun.com","129","31-08-2025 08:31:49","MAT=
ECH CMR"
"External Reconciliation","Site Down","T0056","IHS_YND_189","NOCINC00058008=
74","Paradis Hotel","","31-08-2025 08:29:51","31-08-2025 08:26:43","31-08-2=
025 11:24:28","Grid Outage, site went down because Gen Overload (12.5Kva, 1=
00A) SS IHS BLAISE RAOUL confirmed //Grid return","Siligap Boris","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, site went do=
wn because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL confirmed //Gri=
d return","cedric.tiani@matech-cameroun.com","189","31-08-2025 08:29:51","M=
ATECH CMR"
"External Reconciliation","Site Down","CTR_633","IHS_YND_241","NOCINC000580=
0871","Etoudi","","31-08-2025 08:29:18","31-08-2025 08:26:08","31-08-2025 0=
9:20:18","Grid outage .site went down due to gen overload(20kva,300 A) SS H=
IS Bernard Atangana is informed // we reduced load and site is on Gen","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage .site went down due to gen overload(20kva,300 A) SS HIS Bernard A=
tangana is informed // we reduced load and site is on Gen","vanel.mbiada@ma=
tech-cameroun.com","192","31-08-2025 08:29:18","MATECH CMR"
"External Reconciliation","Site Down","CTR_464","IHS_YND_674","NOCINC000579=
9080","Mfou EPC","","30-08-2025 20:50:45","30-08-2025 20:31:34","30-08-2025=
 21:59:09","Site went down because CB (63A) tripped in PWC who feed equipme=
nts OCM // He rearmed cb","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down beca=
use CB (63A) tripped in PWC who feed equipments OCM // He rearmed cb","edwi=
ge.kapawo@matech-cameroun.com","2844","30-08-2025 20:50:45","MATECH CMR"
"External Reconciliation","Site Down","T2347","IHS_YND_731","NOCINC00057984=
64","UPAC LP","","30-08-2025 18:51:05","30-08-2025 18:41:59","30-08-2025 19=
:19:38","Active, no power issue, site on grid with U=3D54.4V Tx FME mand Ng=
etsa (??699949553??) From Huawei is informed.","","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no po=
wer issue, site on grid with U=3D54.4V Tx FME mand Ngetsa (??699949553??) F=
rom Huawei is informed.","franck.nkomot@matech-cameroun.com","547","30-08-2=
025 18:51:05","MATECH CMR"
"External Reconciliation","Site Down","CTR_110","IHS_YND_028","NOCINC000579=
8262","H-Central","","30-08-2025 18:10:58","30-08-2025 18:02:52","30-08-202=
5 18:35:47","Site went down because the technician Herman (DOWEN /699 99 96=
 25) was ON SITE FOR work (SWAP PWC) // end of work","Paul BIBOUM","Equipme=
nt Replacement","Passive","Planned Activity","Planned Activity - Passive","=
Site went down because the technician Herman (DOWEN /699 99 96 25) was ON S=
ITE FOR work (SWAP PWC) // end of work","franck.nkomot@matech-cameroun.com"=
,"486","30-08-2025 18:10:58","MATECH CMR"
"External Reconciliation","Site Down","CTR_476","IHS_YND_520","NOCINC000579=
8113","SIMBOCK BONAMBAPE","","30-08-2025 17:36:12","30-08-2025 17:34:04","3=
0-08-2025 17:40:51","Grid outage, Site went down before Gen start due to po=
or backup/ // Grid Return","Hyemafo Gildas","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup/ // Grid Return","edwige.kapawo@matech-ca=
meroun.com","130","30-08-2025 17:36:12","MATECH CMR"
"External Reconciliation","Site Down","CTR_075","IHS_YND_133","NOCINC000579=
7493","Elig-Edzoa","","30-08-2025 15:53:43","30-08-2025 15:50:35","30-08-20=
25 16:00:06","Grid only site,No mobile gen available // Grid restored","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid onl=
y site,No mobile gen available // Grid restored","edwige.kapawo@matech-came=
roun.com","190","30-08-2025 15:53:43","MATECH CMR"
"External Reconciliation","Site Down","T1377","IHS_YND_807","NOCINC00057973=
12","Ahala Echangeur","","30-08-2025 15:24:00","30-08-2025 14:32:59","30-08=
-2025 16:12:10","Grid outage, Site went down because  Gen CB tripped // He =
rearmed  Gen CB","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","A=
CDG - Load Breaker","Site went down because  Gen CB tripped // He rearmed  =
Gen CB","franck.nkomot@matech-cameroun.com","3081","30-08-2025 15:24:00","M=
ATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_537","NOCINC0005797213","=
MEFOU ASSI","","30-08-2025 15:09:51","30-08-2025 15:03:58","30-08-2025 15:0=
8:28","Cascaded Incident from TTO6010953","Fanda Brice","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
fore Gen start due to poor backup/ // Grid Return","edwige.kapawo@matech-ca=
meroun.com","353","30-08-2025 15:09:51","MATECH CMR"
"External Reconciliation","Site Down","CTR_476","IHS_YND_520","NOCINC000579=
7196","SIMBOCK BONAMBAPE","IHS_YND_537","30-08-2025 15:08:05","30-08-2025 1=
5:03:58","30-08-2025 15:08:28","Grid outage, Site went down before Gen star=
t due to poor backup/ // Grid Return","Hyemafo Gildas","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site w=
ent down before Gen start due to poor backup/ // Grid Return","edwige.kapaw=
o@matech-cameroun.com","249","30-08-2025 15:08:05","MATECH CMR"
"External Reconciliation","Site Down","T2829","IHS_YND_526","NOCINC00057967=
87","Nkoabang2","","30-08-2025 14:13:13","30-08-2025 14:11:47","30-08-2025 =
14:15:42","Grid outage, site went down due to gen overload (22KVA, 330A), S=
S Blaise IHS is informed// Grid return","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due =
to gen overload (22KVA, 330A), SS Blaise IHS is informed// Grid return","ce=
dric.tiani@matech-cameroun.com","89","30-08-2025 14:13:13","MATECH CMR"
"External Reconciliation","Site Down","CTR_096","IHS_YND_042","NOCINC000579=
6761","Mvog-Ada_OCM","","30-08-2025 14:07:37","30-08-2025 14:02:27","30-08-=
2025 14:15:27","Grid only on site, No space on site to deploy MDGE // Grid =
return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid only on site, No space on site to deploy MDGE // Grid return","van=
el.mbiada@matech-cameroun.com","311","30-08-2025 14:07:37","MATECH CMR"
"External Reconciliation","Site Down","CTR_377","IHS_YND_005","NOCINC000579=
6588","Imm-Olympique","","30-08-2025 13:41:28","30-08-2025 12:13:43","30-08=
-2025 12:25:20","(backtracking) Active//No power issue on Site ,Site on Gri=
d with Ubaie=3D52V The TX FME Mohamadou mouam //691144435 from Huawei is in=
formed","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","(backtracking) Active//No power issue on =
Site ,Site on Grid with Ubaie=3D52V The TX FME Mohamadou mouam //691144435 =
from Huawei is informed","vanel.mbiada@matech-cameroun.com","5266","30-08-2=
025 13:41:28","MATECH CMR"
"External Reconciliation","Site Down","CTR_310","IHS_YND_057","NOCINC000579=
6577","Mvolye-New","","30-08-2025 13:37:13","30-08-2025 13:34:48","30-08-20=
25 13:56:58","Active// No power Issue Site on Grid Ubaie =3D51.8V, The TX F=
ME Mbah Hosiah (674007438) is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power Is=
sue Site on Grid Ubaie =3D51.8V, The TX FME Mbah Hosiah (674007438) is info=
rmed","vanel.mbiada@matech-cameroun.com","146","30-08-2025 13:37:13","MATEC=
H CMR"
"External Reconciliation","Site Down","CTR_377","IHS_YND_005","NOCINC000579=
6010","Imm-Olympique","","30-08-2025 12:02:40","30-08-2025 11:59:23","30-08=
-2025 12:12:48","Grid outage,site went down because Gen failed to start due=
 to Gen overload(20KVA//295A)//Grid return","Paul BIBOUM","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage,site went down becaus=
e Gen failed to start due to Gen overload(20KVA//295A)//Grid return","vanel=
.mbiada@matech-cameroun.com","199","30-08-2025 12:02:40","MATECH CMR"
"External Reconciliation","Site Down","CTR_096","IHS_YND_042","NOCINC000579=
5817","Mvog-Ada_OCM","","30-08-2025 11:32:13","30-08-2025 11:29:04","30-08-=
2025 11:43:41","Grid only on site, No space on site to deploy MDGE // Grid =
return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid only on site, No space on site to deploy MDGE // Grid return","van=
el.mbiada@matech-cameroun.com","190","30-08-2025 11:32:13","MATECH CMR"
"External Reconciliation","Site Down","CTR_270","IHS_YND_023","NOCINC000579=
5442","Montesquieux","","30-08-2025 10:37:47","30-08-2025 10:36:40","30-08-=
2025 10:39:17","Site went down because  rectifiers went faulty (02/05) // H=
e removed rectifier faulty(site on 03)","Paul BIBOUM","Equipment Repair","P=
assive","Rectifier","Rectifier Module","Site went down because  rectifiers =
went faulty (02/05) // He removed rectifier faulty(site on 03)","vanel.mbia=
da@matech-cameroun.com","68","30-08-2025 10:37:47","MATECH CMR"
"External Reconciliation","Site Down","CTR_199","IHS_YND_050","NOCINC000579=
5430","Satcom","","30-08-2025 10:34:18","30-08-2025 10:28:44","30-08-2025 1=
0:50:40","No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand n=
guetsa(691144412) From huawei is informed.","vanel.mbiada@matech-cameroun.c=
om","335","30-08-2025 10:34:18","MATECH CMR"
"External Reconciliation","Site Down","CTR_395","IHS_YND_249","NOCINC000579=
4838","Biteng-Maetur","","30-08-2025 08:54:06","30-08-2025 08:50:17","30-08=
-2025 08:59:55","Active//No power issue on site Ubaie =3D50.6V site on Grid=
 The TX FME Henri (699949693) from Huawei is informed","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site Ubaie =3D50.6V site on Grid The T=
X FME Henri (699949693) from Huawei is informed","vanel.mbiada@matech-camer=
oun.com","232","30-08-2025 08:54:06","MATECH CMR"
"External Reconciliation","Site Down","CTR_266","IHS_YND_179","NOCINC000579=
4834","Essomba","","30-08-2025 08:52:21","30-08-2025 08:50:10","30-08-2025 =
09:53:09","Active // No power issue site on Gen with U=3D51.6 V Tx Fme Henr=
i(691145055) of Huawei is informed.","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue site on Gen with U=3D51.6 V Tx Fme Henri(691145055) of Hu=
awei is informed.","vanel.mbiada@matech-cameroun.com","133","30-08-2025 08:=
52:21","MATECH CMR"
"External Reconciliation","Site Down","CTR_133","IHS_YND_120","NOCINC000579=
4772","Sapeur Mimboman","","30-08-2025 08:41:16","30-08-2025 08:34:59","30-=
08-2025 08:55:26","Active//No power issue on site Ubaie=3D48.8V and Ubaie2=
=3D51.8V site on Grid. The TX FME Lionel adjep//655 18 48 76// from huawei =
is informed","Mba Lazare Herve","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site =
Ubaie=3D48.8V and Ubaie2=3D51.8V site on Grid. The TX FME Lionel adjep//655=
 18 48 76// from huawei is informed","vanel.mbiada@matech-cameroun.com","37=
8","30-08-2025 08:41:16","MATECH CMR"
"External Reconciliation","Site Down","CTR_068","IHS_YND_109","NOCINC000579=
4767","Mobil-Essos","","30-08-2025 08:40:18","30-08-2025 08:34:06","30-08-2=
025 11:22:41","Active// No power issue on site U=3D54,1 V site on grid Bric=
e Tsague (650214096) from huawei is informed","Siligap Boris","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive// No power issue on site U=3D54,1 V site on grid Brice Tsague (650214=
096) from huawei is informed","vanel.mbiada@matech-cameroun.com","374","30-=
08-2025 08:40:18","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_566","NOCINC0005794759","=
Crf Cornier","","30-08-2025 08:38:33","30-08-2025 08:34:41","30-08-2025 09:=
03:37","Cascaded Incident from TTO6008205","MINKA NICOLAS","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D53.=
5v site on grid Tx fme Armand Nguetsa of huawei is informed","vanel.mbiada@=
matech-cameroun.com","232","30-08-2025 08:38:33","MATECH CMR"
"External Reconciliation","Site Down","CTR_071","IHS_YND_112","NOCINC000579=
4755","Madison","IHS_YND_566","30-08-2025 08:36:54","30-08-2025 08:34:41","=
30-08-2025 08:45:15","No power issue on site U=3D53.5v site on grid Tx fme =
Armand Nguetsa of huawei is informed","MFOUAGUEGUE MATHIEU","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site U=3D53.5v site on grid Tx fme Armand Nguetsa of huawei =
is informed","vanel.mbiada@matech-cameroun.com","134","30-08-2025 08:36:54"=
,"MATECH CMR"
"External Reconciliation","Site Down","CTR_115","IHS_YND_375","NOCINC000579=
3953","Ngoung","","30-08-2025 04:28:36","30-08-2025 04:21:49","30-08-2025 0=
6:17:47","Grid outage, site went down because gen failed to start due to gr=
id contactor faulty // He bypassed ATS and Gen manually started","Kemeni Fr=
anklin","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid =
outage, site went down because gen failed to start due to grid contactor fa=
ulty // He bypassed ATS and Gen manually started","loic.noumsi@matech-camer=
oun.com","407","30-08-2025 04:28:36","MATECH CMR"
"External Reconciliation","Site Down","CTR_271","IHS_YND_275","NOCINC000579=
3637","Nkolbong","","30-08-2025 01:34:52","30-08-2025 01:31:05","30-08-2025=
 01:32:17","Active/ No power issue on site Ubaie; 55.9V site on Gen, The FM=
E TX Julien (+237 6 93 09 58 49) from Huawei is informed,","Delor Telezing"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active/ No power issue on site Ubaie; 55.9V site on Gen, The F=
ME TX Julien (+237 6 93 09 58 49) from Huawei is informed,","loic.noumsi@ma=
tech-cameroun.com","229","30-08-2025 01:34:52","MATECH CMR"
"External Reconciliation","Site Down","T3220","IHS_YND_765","NOCINC00057930=
59","MBALNGONG LYCEE","","29-08-2025 22:20:10","29-08-2025 22:16:49","29-08=
-2025 22:20:10","Active//No power Issue Site on Grid Ubai =3D53.8V, The FME=
 The TX FME Fulbert(654266068) is informed.","Fanda Brice","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power Issue Site on Grid Ubai =3D53.8V, The FME The TX FME Fulbert(6=
54266068) is informed.","loic.noumsi@matech-cameroun.com","204","29-08-2025=
 22:20:10","MATECH CMR"
"External Reconciliation","Site Down","T3220","IHS_YND_765","NOCINC00057929=
02","MBALNGONG LYCEE","","29-08-2025 21:43:45","29-08-2025 21:42:34","29-08=
-2025 21:44:59","Active//No power Issue Site on Grid Ubai =3D53.8V, The FME=
 The TX FME Fulbert(654266068) is informed.","Fanda Brice","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power Issue Site on Grid Ubai =3D53.8V, The FME The TX FME Fulbert(6=
54266068) is informed.","cedric.tiani@matech-cameroun.com","74","29-08-2025=
 21:43:45","MATECH CMR"
"External Reconciliation","Site Down","T1440","IHS_YND_698","NOCINC00057924=
34","EBOM","","29-08-2025 20:38:27","29-08-2025 20:35:16","29-08-2025 21:58=
:13","Grid outage, Site went down because Gen failed to start due to PWC dy=
sfunctionning// He reset it and manually start the Gen","Hyemafo Gildas","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage, Site went down because Gen failed to start due to PWC dysfunctionni=
ng// He reset it and manually start the Gen","cedric.tiani@matech-cameroun.=
com","192","29-08-2025 20:38:27","MATECH CMR"
"External Reconciliation","Site Down","T2588","IHS_YND_742","NOCINC00057924=
24","Mendong NB","","29-08-2025 20:37:30","29-08-2025 20:33:59","30-08-2025=
 02:14:12","Grid Only, No space to deploy MDG // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No spa=
ce to deploy MDG // Grid return","cedric.tiani@matech-cameroun.com","212","=
29-08-2025 20:37:30","MATECH CMR"
"External Reconciliation","Site Down","T1874","IHS_YND_520","NOCINC00057917=
56","SIMBOCK BONAMBAPE","IHS_YND_537","29-08-2025 18:54:42","29-08-2025 18:=
50:24","29-08-2025 19:01:26","Grid outage, Site went down before Gen start =
due to poor backup/ // Grid Return","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down before Gen=
 start due to poor backup/ // Grid Return","cedric.tiani@matech-cameroun.co=
m","259","29-08-2025 18:54:42","MATECH CMR"
"External Reconciliation","Site Down","CTR_164","IHS_YND_257","NOCINC000579=
1209","Ahala","","29-08-2025 16:56:29","29-08-2025 16:54:18","29-08-2025 17=
:07:16","Grid outage,site went down because Gen started and stopped due to =
Alarm*Over current*//He reset the Gen card and started the Gen manually","H=
yemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage,site went down because Gen started and stopped due to Alarm=
*Over current*//He reset the Gen card and started the Gen manually","cedric=
.tiani@matech-cameroun.com","132","29-08-2025 16:56:29","MATECH CMR"
"External Reconciliation","Site Down","T0573","IHS_YND_387","NOCINC00057911=
13","Talla Monatele","","29-08-2025 16:33:32","29-08-2025 16:30:21","29-08-=
2025 17:47:03","Grid outage, Site went down before Gen start due to poor ba=
ckup// GRID RETURN","Parker Tchoup","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup// GRID RETURN","cedric.tiani@matech-cameroun.com"=
,"192","29-08-2025 16:33:32","MATECH CMR"
"External Reconciliation","Site Down","T0287","IHS_YND_038","NOCINC00057909=
32","Siantou Inferieur","","29-08-2025 16:10:30","29-08-2025 16:05:20","29-=
08-2025 16:29:21","No power issue on site , site on Grid with Ubaie=3D54,5 =
V ","","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site , site on Grid with Ubaie=3D54,5 =
V ","cedric.tiani@matech-cameroun.com","311","29-08-2025 16:10:30","MATECH =
CMR"
"External Reconciliation","Site Down","T1440","IHS_YND_698","NOCINC00057909=
06","EBOM","","29-08-2025 16:02:56","29-08-2025 15:59:34","29-08-2025 16:57=
:57","Grid fluctuation, Site went down because Gen failed to start due to G=
rid bad voltage and No RCP on site // Grid stabilized","Hyemafo Gildas","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuation, Site went down because Gen failed to start due to Grid bad vo=
ltage and No RCP on site // Grid stabilized","cedric.tiani@matech-cameroun.=
com","203","29-08-2025 16:02:56","MATECH CMR"
"External Reconciliation","Site Down","T0420","IHS_YND_082","NOCINC00057904=
84","Mokolo Yaounde","","29-08-2025 14:51:16","29-08-2025 14:48:59","29-08-=
2025 14:52:09","Active // No power issue Ubaie: 54.7 V site on grid. TX FME=
 Brice Tsague (650214096) from HUAWEI is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubaie: 54.7 V site on grid. TX FME Brice Tsague (650214096)=
 from HUAWEI is informed","cedric.tiani@matech-cameroun.com","139","29-08-2=
025 14:51:16","MATECH CMR"
"External Reconciliation","Site Down","CTR_185","IHS_YND_378","NOCINC000579=
0280","Eseka Town","","29-08-2025 14:02:44","29-08-2025 13:56:30","29-08-20=
25 14:10:20","Active// No power issue, Site on Gen Ubaie:50V, The FME Tx Et=
ienne/695033981 From Huawei is informed","Kemeni Franklin","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power issue, Site on Gen Ubaie:50V, The FME Tx Etienne/695033981 Fr=
om Huawei is informed","edwige.kapawo@matech-cameroun.com","375","29-08-202=
5 14:02:44","MATECH CMR"
"External Reconciliation","Site Down","CTR_526","IHS_YND_696","NOCINC000579=
0239","Barriere IHS","","29-08-2025 13:57:00","29-08-2025 13:56:56","29-08-=
2025 14:00:24","No power issue, Site impacted by Simbock-chefferie-MTN not =
managed by IHS","Hyemafo Gildas","Customer Equipment Failure","Active","Act=
ive Equipment Failure","Affected by 3rd Party Site","No power issue, Site i=
mpacted by Simbock-chefferie-MTN not managed by IHS","edwige.kapawo@matech-=
cameroun.com","6","29-08-2025 13:57:00","MATECH CMR"
"External Reconciliation","Site Down","CTR_911","IHS_YND_762","NOCINC000579=
0059","Nkolfon Cimencam","","29-08-2025 13:25:41","29-08-2025 13:24:59","29=
-08-2025 13:31:54","Grid outage, Site went down before Gen start due to poo=
r backup // Gen Started automatically","Hyemafo Gildas","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site =
went down before Gen start due to poor backup // Gen Started automatically"=
,"edwige.kapawo@matech-cameroun.com","44","29-08-2025 13:25:41","MATECH CMR=
"
"External Reconciliation","Site Down","CTR_149","IHS_YND_517","NOCINC000578=
9710","Montee-Des-Soeurs","","29-08-2025 12:16:36","29-08-2025 12:14:24","2=
9-08-2025 13:23:57","Active // No power issue, site is on Grid with Ubaie: =
54.5V,  the fme Mbah hosiah (699699694 / Huawei) is informed.","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active // No power issue, site is on Grid with Ubaie: 54.5=
V,  the fme Mbah hosiah (699699694 / Huawei) is informed.","edwige.kapawo@m=
atech-cameroun.com","134","29-08-2025 12:16:36","MATECH CMR"
"External Reconciliation","Site Down","T1868","IHS_YND_524","NOCINC00057894=
34","ODZA BORNE 10","","29-08-2025 11:41:56","29-08-2025 11:36:46","29-08-2=
025 16:39:05","Grid outage, Site went down due to Gen overload (12.5 kva, 1=
80A)//Grid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage, Site went down due to Gen overload (12.5 kv=
a, 180A)//Grid return","franck.nkomot@matech-cameroun.com","311","29-08-202=
5 11:41:56","MATECH CMR"
"External Reconciliation","Site Down","CTR_642","IHS_YND_537","NOCINC000578=
9219","MEFOU ASSI","","29-08-2025 11:02:40","29-08-2025 10:57:55","29-08-20=
25 10:59:55","No power issue site on grid with Ubaie: 54.6V TX FME Flubert =
(654266068) from Huawei is informed","Fanda Brice","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on grid with Ubaie: 54.6V TX FME Flubert (654266068) from Huawei is=
 informed","franck.nkomot@matech-cameroun.com","288","29-08-2025 11:02:40",=
"MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_527","NOCINC0005789066","=
Odza II OCM","","29-08-2025 10:40:12","29-08-2025 10:34:00","29-08-2025 11:=
07:07","Cascaded Incident from TTO6001803","Albran Byorel","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down because Gen =
failed Start due to  Gen CB (32A) tripped // He rearmed  Gen CB","edwige.ka=
pawo@matech-cameroun.com","372","29-08-2025 10:40:12","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_528","NOCINC0005789067","=
MEHANDAN","","29-08-2025 10:40:12","29-08-2025 10:34:00","29-08-2025 11:07:=
07","Cascaded Incident from TTO6001803","Albran Byorel","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down because Gen fai=
led Start due to  Gen CB (32A) tripped // He rearmed  Gen CB","edwige.kapaw=
o@matech-cameroun.com","372","29-08-2025 10:40:12","MATECH CMR"
"External Reconciliation","Site Down","CTR_330","IHS_YND_255","NOCINC000578=
9053","Odza-PK10","IHS_YND_527, IHS_YND_528","29-08-2025 10:39:05","29-08-2=
025 10:34:00","29-08-2025 11:07:07","Site went down because Gen failed Star=
t due to  Gen CB (32A) tripped // He rearmed  Gen CB","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Site went down be=
cause Gen failed Start due to  Gen CB (32A) tripped // He rearmed  Gen CB",=
"edwige.kapawo@matech-cameroun.com","306","29-08-2025 10:39:05","MATECH CMR=
"
"External Reconciliation","Site Down","CTR_002","IHS_YND_010","NOCINC000578=
9048","CNR","","29-08-2025 10:38:15","29-08-2025 10:34:09","29-08-2025 12:2=
6:34","Grid fluctuation,Site went down because GEN failed to start due to g=
rid bad voltage // He did a bridge on the good phase","Mboua Thierry","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid f=
luctuation,Site went down because GEN failed to start due to grid bad volta=
ge // He did a bridge on the good phase","edwige.kapawo@matech-cameroun.com=
","247","29-08-2025 10:38:15","MATECH CMR"
"External Reconciliation","Site Down","T1868","IHS_YND_524","NOCINC00057887=
28","ODZA BORNE 10","","29-08-2025 09:38:41","29-08-2025 09:32:31","29-08-2=
025 11:19:31","Grid outage, Site went down due to Gen overload (12.5 kva, 1=
80A)//Grid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage, Site went down due to Gen overload (12.5 kv=
a, 180A)//Grid return","franck.nkomot@matech-cameroun.com","371","29-08-202=
5 09:38:41","MATECH CMR"
"Closed Complete","Warning","T0289","IHS_YND_106","NOCINC0005788165","Mfand=
ena","","29-08-2025 07:05:11","","","High temp. FME report that air conditi=
oner is faulty. // He opened the shelter","Delor Telezing","Warning","Warni=
ng","POWER","Warning - AC Failure","High temp. FME report that air conditio=
ner is faulty. He opened the shelter","franck.nkomot@matech-cameroun.com","=
563","29-08-2025 07:05:11","MATECH CMR"
"External Reconciliation","Site Down","T0379","IHS_YND_473","NOCINC00057875=
48","Yoko MTN","","29-08-2025 02:59:02","29-08-2025 02:55:47","29-08-2025 0=
3:08:00","Grid outage, Site went down because Gen started and stopped due e=
mergency stop button was  not activeted// He actived the button and started=
 Gen manualy","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Emergency Stop","Grid outage, Site went down because Gen started and sto=
pped due emergency stop button was  not activeted// He actived the button a=
nd started Gen manualy","cedric.tiani@matech-cameroun.com","196","29-08-202=
5 02:59:02","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005785978","S=
ous Prefecture","","28-08-2025 21:05:06","28-08-2025 20:56:50","28-08-2025 =
21:10:28","No power issue site on Grid Ubaie =3D54.7V, The tx Huawei Fulber=
t (654266068) is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 Grid Ubaie =3D54.7V, The tx Huawei Fulbert (654266068) is informed","gerar=
d.tchangoue@matech-cameroun.com","498","28-08-2025 21:05:06","MATECH CMR"
"Closed Complete","Site Down","T1747","IHS_YND_728","NOCINC0005785719","TRO=
PICANA NEW","","28-08-2025 20:14:27","28-08-2025 20:11:20","28-08-2025 20:3=
4:13","Grid outage, site went down because Gen started and stopped due to d=
isjunction of Gen CB (32A) // He rearmed it, site on GEN","MINKA NICOLAS","=
Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Grid outage, =
site went down because Gen started and stopped due to disjuncttion of Gen C=
B (32A) // He rearmed it, site on GEN","gerard.tchangoue@matech-cameroun.co=
m","188","28-08-2025 20:14:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005785208","Nsam esc=
ale LP","","28-08-2025 18:57:18","28-08-2025 18:49:41","28-08-2025 18:55:58=
","Cascaded Incident from TTO5997498","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, Site went down before Gen start =
due to poor backup/ // Gen automatically started","loic.noumsi@matech-camer=
oun.com","457","28-08-2025 18:57:18","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005785195","Nsa=
m Sofavinc","IHS_YND_732","28-08-2025 18:54:47","28-08-2025 18:49:41","28-0=
8-2025 18:55:58","Grid outage, Site went down before Gen start due to poor =
backup/ // Gen automatically started","MINKA NICOLAS","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site we=
nt down before Gen start due to poor backup/ // Gen automatically started",=
"loic.noumsi@matech-cameroun.com","307","28-08-2025 18:54:47","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005785187","SIM=
BOCK BONAMBAPE","","28-08-2025 18:52:55","28-08-2025 18:49:48","28-08-2025 =
18:53:03","Grid outage, Site went down before Gen start due to poor backup/=
 // Grid Return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup/ // Grid Return","loic.noumsi@matech-cameroun.com",=
"189","28-08-2025 18:52:55","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005785153","Ron=
d Point Express1114","","28-08-2025 18:47:18","28-08-2025 18:45:12","28-08-=
2025 18:54:16","Site went down due to PWC CB (100A) faulty // He changed it=
, site on Grid","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Circuit Breaker Issue","Site went down due to PWC CB (1=
00A) faulty // He changed it, site on Grid","loic.noumsi@matech-cameroun.co=
m","127","28-08-2025 18:47:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_801","NOCINC0005784202","HOPITAL =
GENERAL RAIL YDE","","28-08-2025 16:57:07","28-08-2025 16:54:01","28-08-202=
5 17:12:06","Cascaded Incident from TTO5996410","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down because gen failed to start due to gen card faulty //Grid return","l=
oic.noumsi@matech-cameroun.com","186","28-08-2025 16:57:07","MATECH CMR"
"Tasks Completed","Warning","T0211","IHS_YND_393","NOCINC0005784204","Ezeza=
ng","","28-08-2025 16:57:07","","","Site went in alarm because FME Ahanda (=
697487490) was on site for PM // End of work","Parker Tchoup","Warning","Wa=
rning","SYSTEM","Warning - Planned Activity - Active","Site went in alarm b=
ecause FME Ahanda (697487490) was on site for PM // End of work","gerard.tc=
hangoue@matech-cameroun.com","1529","28-08-2025 16:57:07","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005784195","Pha=
rmacie Bleue","IHS_YND_801","28-08-2025 16:56:21","28-08-2025 16:54:01","28=
-08-2025 17:12:06","Grid outage, site went down because gen failed to start=
 due to gen card faulty //Grid return","Siligap Boris","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down bec=
ause gen failed to start due to gen card faulty //Grid return","loic.noumsi=
@matech-cameroun.com","141","28-08-2025 16:56:21","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005784024","Par=
adis Hotel","","28-08-2025 16:35:22","28-08-2025 16:32:14","28-08-2025 17:0=
8:11","Grid Outage, site went down because Gen Overload (12.5Kva, 100A) SS =
IHS BLAISE RAOUL confirmed // Grid return","Siligap Boris","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid Outage, site went down beca=
use Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL confirmed // Grid retu=
rn","loic.noumsi@matech-cameroun.com","189","28-08-2025 16:35:22","MATECH C=
MR"
"Closed Complete","Warning","T0209","IHS_YND_197","NOCINC0005783921","Palai=
s Des Congres","","28-08-2025 16:19:28","","","Grid outage, Site went in al=
arm because Gen failed to start due to fuse of grid contactor is faulty// H=
e made a bridge of fuse, Site on gen","Mboua Thierry","Warning","Warning","=
POWER","Warning - National Grid - Fuse Burnt","Grid outage, Site went in al=
arm because Gen failed to start due to fuse of grid contactor is faulty// H=
e made a bridge of fuse, Site on gen","loic.noumsi@matech-cameroun.com","3"=
,"28-08-2025 16:19:28","MATECH CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0005783817","Fou=
da rue des g=E9n=E9raux","","28-08-2025 16:06:11","28-08-2025 16:04:44","28=
-08-2025 16:07:21","Grid outage, site went down due to fuel shortage // Ref=
uelling done","Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, site went down due to fuel shortage // Refuelling done",=
"loic.noumsi@matech-cameroun.com","88","28-08-2025 16:06:11","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005783272","N=
koabang Ebolmedjock","","28-08-2025 14:23:46","28-08-2025 14:19:25","28-08-=
2025 14:25:01","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","gerard.tchangoue@m=
atech-cameroun.com","263","28-08-2025 14:23:46","MATECH CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0005782854","N=
kolndongo","","28-08-2025 13:42:10","28-08-2025 13:37:59","28-08-2025 14:58=
:59","site down due to work of Ronix (Grato // 695934760) (Swap of MPR) // =
End of Work","MINKA NICOLAS","Equipment Replacement","Passive","Planned Act=
ivity","Planned Activity - Passive","site down due to work of Ronix (Grato =
// 695934760) (Swap of MPR) // End of Work","gerard.tchangoue@matech-camero=
un.com","252","28-08-2025 13:42:10","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005782238","E=
toudi","","28-08-2025 12:23:15","28-08-2025 12:18:06","28-08-2025 13:03:38"=
,"Grid outage .site went down due to gen overload(20kva,300 A) SS HIS Berna=
rd Atangana is informed // we reduce load and site is on Gen","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
 .site went down due to gen overload(20kva,300 A) SS HIS Bernard Atangana i=
s informed // we reduce load and site is on Gen","gerard.tchangoue@matech-c=
ameroun.com","310","28-08-2025 12:23:15","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005781794","S=
ous Prefecture","","28-08-2025 11:27:51","28-08-2025 11:19:40","28-08-2025 =
11:20:36","No power issue site on Grid Ubaie =3D54.5V, The tx Huawei Fulber=
t (654266068) is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 Grid Ubaie =3D54.5V, The tx Huawei Fulbert (654266068) is informed","gerar=
d.tchangoue@matech-cameroun.com","493","28-08-2025 11:27:51","MATECH CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0005781430","C=
lge-Advantiste","","28-08-2025 10:40:13","28-08-2025 10:38:04","28-08-2025 =
11:01:26","No power issue site on grid with U=3D53.7V Lionnel Steeve(655184=
876) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on grid with U=3D53.7V Lionnel Steeve(655184876) from Huawei is informed=
","gerard.tchangoue@matech-cameroun.com","130","28-08-2025 10:40:13","MATEC=
H CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0005779103","Sap=
eur Mimboman","","28-08-2025 02:14:57","28-08-2025 02:11:48","28-08-2025 07=
:43:53","the cable that supplies the MTN BTS is burnt // cable junction","M=
ba Lazare Herve","Equipment Repair","Passive","Infrastructure","Armoured Ca=
ble","the cable that supplies the MTN BTS is burnt // cable junction","cedr=
ic.tiani@matech-cameroun.com","191","28-08-2025 02:14:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005778951","Messassi=
 okolo","","28-08-2025 01:39:09","28-08-2025 01:32:29","28-08-2025 01:34:01=
","Cascaded Incident from TTO5990666","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","ACTIVE// No power issue site Ubai=
e=3D53.5V site on Grid, The tx Fme Symphorien(650257151)from Huawei is info=
rmed.","gerard.tchangoue@matech-cameroun.com","400","28-08-2025 01:39:09","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0005778952","Emana ly=
cee 2","","28-08-2025 01:39:09","28-08-2025 01:32:29","28-08-2025 01:34:01"=
,"Cascaded Incident from TTO5990666","Fabrice Pouakam","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","ACTIVE// No power issue site Ubaie=
=3D53.5V site on Grid, The tx Fme Symphorien(650257151)from Huawei is infor=
med.","gerard.tchangoue@matech-cameroun.com","400","28-08-2025 01:39:09","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0005778948","Mballa 4=
","","28-08-2025 01:39:08","28-08-2025 01:32:29","28-08-2025 01:34:01","Cas=
caded Incident from TTO5990666","Delor Telezing","Cascade Outage","Active",=
"Cascade Active","Cascade Active","ACTIVE// No power issue site Ubaie=3D53.=
5V site on Grid, The tx Fme Symphorien(650257151)from Huawei is informed.",=
"gerard.tchangoue@matech-cameroun.com","399","28-08-2025 01:39:08","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0005778949","EMANA BI=
LICK CITY","","28-08-2025 01:39:08","28-08-2025 01:32:29","28-08-2025 01:34=
:01","Cascaded Incident from TTO5990666","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","ACTIVE// No power issue site U=
baie=3D53.5V site on Grid, The tx Fme Symphorien(650257151)from Huawei is i=
nformed.","gerard.tchangoue@matech-cameroun.com","399","28-08-2025 01:39:08=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005778950","Emana Ly=
cee","","28-08-2025 01:39:08","28-08-2025 01:32:29","28-08-2025 01:34:01","=
Cascaded Incident from TTO5990666","Fabrice Pouakam","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","ACTIVE// No power issue site Ubaie=
=3D53.5V site on Grid, The tx Fme Symphorien(650257151)from Huawei is infor=
med.","gerard.tchangoue@matech-cameroun.com","399","28-08-2025 01:39:08","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0005778939","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","28=
-08-2025 01:36:46","28-08-2025 01:32:29","28-08-2025 01:50:50","ACTIVE// No=
 power issue site Ubaie=3D53.5V site on Grid, The tx Fme Symphorien(6502571=
51)from Huawei is informed.","Fabrice Pouakam","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No powe=
r issue site Ubaie=3D53.5V site on Grid, The tx Fme Symphorien(650257151)fr=
om Huawei is informed.","gerard.tchangoue@matech-cameroun.com","258","28-08=
-2025 01:36:46","MATECH CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0005778543","Sap=
eur Mimboman","","28-08-2025 00:29:00","28-08-2025 00:26:51","28-08-2025 02=
:06:10","Access issues due to lanlord during the night//Grid return","Mba L=
azare Herve","Access Denial","Lease Or Legal","Landlord Related Issues","Ac=
cess Issue - Land Lord","Access issues due to lanlord during the night//Gri=
d return","cedric.tiani@matech-cameroun.com","131","28-08-2025 00:29:00","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005778488","N=
kolfon Cimencam","","28-08-2025 00:22:52","28-08-2025 00:21:43","28-08-2025=
 01:56:59","Grid outage, Site went down because Gen started and stopped wit=
h ''low oil pressure'' alarm // he added oil and manually started Gen","Hye=
mafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressu=
re","Grid outage, Site went down because Gen started and stopped with ''low=
 oil pressure'' alarm // he added oil and manually started Gen","gerard.tch=
angoue@matech-cameroun.com","71","28-08-2025 00:22:52","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0005778298","UPA=
C LP","","27-08-2025 23:48:56","27-08-2025 23:47:45","28-08-2025 00:17:09",=
"Active, no power issue, site on grid with U=3D54.4V Tx FME mand Ngetsa (??=
699949553??) From Huawei is informed.","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issu=
e, site on grid with U=3D54.4V Tx FME mand Ngetsa (??699949553??) From Huaw=
ei is informed.","cedric.tiani@matech-cameroun.com","73","27-08-2025 23:48:=
56","MATECH CMR"
"Closed Complete","Site Down","CTR_525","IHS_YND_544","NOCINC0005778294","J=
ean Vespa 2","","27-08-2025 23:46:30","18-08-2025 18:01:00","18-08-2025 18:=
06:26","Bactracking Active//No power issue on site Ubaie =3D54,6 V site on =
Grid The TX FME Martial//690087047 from Huawei is informed","Mboua Thierry"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue on site Ubaie =3D54,6 V site on Grid Th=
e TX FME Martial//690087047 from Huawei is informed","cedric.tiani@matech-c=
ameroun.com","798331","27-08-2025 23:46:30","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005778269","M=
endong","","27-08-2025 23:42:54","18-08-2025 12:49:10","18-08-2025 12:58:10=
","Active//No  power issue on site  , Site On Grid and Ubaie=3D54.5 V, The =
fme Tx Bah Hosiah//674007438// from Huawei is informed","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No  power issue on site  , Site On Grid and Ubaie=3D54.5 =
V, The fme Tx Bah Hosiah//674007438// from Huawei is informed","cedric.tian=
i@matech-cameroun.com","816824","27-08-2025 23:42:54","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005778253","M=
endong","","27-08-2025 23:39:33","19-08-2025 19:01:12","19-08-2025 19:02:12=
","Grid fluctuations, Site went down due to Gen overload (15KVA//130A) // g=
rid stabilized","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid fluctuations, Site went down due to Gen overload (15K=
VA//130A) // grid stabilized","cedric.tiani@matech-cameroun.com","707901","=
27-08-2025 23:39:33","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0005778201","Ebe=
ba","","27-08-2025 23:25:53","27-08-2025 23:20:18","27-08-2025 23:48:39",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid outage.gen failed to start due to no automatism on site//Gen manua=
lly started","gerard.tchangoue@matech-cameroun.com","738","27-08-2025 23:25=
:53","MATECH CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0005778199","Nke=
ng likok","IHS_YND_339","27-08-2025 23:24:55","27-08-2025 23:20:18","27-08-=
2025 23:48:39","Grid outage.gen failed to start due to no automatism on sit=
e//Gen manually started","Kemeni Franklin","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage.gen failed to start due to no a=
utomatism on site//Gen manually started","gerard.tchangoue@matech-cameroun.=
com","278","27-08-2025 23:24:55","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005778002","S=
IMBOCK BONAMBAPE","","27-08-2025 22:36:24","27-08-2025 22:33:13","27-08-202=
5 22:37:50","Grid outage, Site went down before Gen start due to poor backu=
p/ // Grid Return","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Grid Return","cedric.tiani@matech-cameroun.co=
m","193","27-08-2025 22:36:24","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005777760","E=
foulan","","27-08-2025 21:57:10","21-08-2025 09:45:00","21-08-2025 12:41:16=
","Site impacted by Efoulan Pont which is not managed by IHS","MINKA NICOLA=
S","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","	Site impacted by Efoulan Pont which is not managed by IHS",=
"gerard.tchangoue@matech-cameroun.com","562330","27-08-2025 21:57:10","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005777717","D=
amas","","27-08-2025 21:53:23","22-08-2025 13:43:26","22-08-2025 16:15:27",=
"Active// No power issue, site is on gen with Ubaie=3D48.8V The Tx Fme, Elo=
undou(652586578) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue, site is on gen with Ubaie=3D48.8V The Tx Fme, Eloundou(=
652586578) from Huawei is informed","gerard.tchangoue@matech-cameroun.com",=
"461397","27-08-2025 21:53:23","MATECH CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0005777613","B=
astos-BAT","","27-08-2025 21:36:23","22-08-2025 16:23:09","22-08-2025 17:00=
:04","Active// No power issue, site is on gen with Ubaie=3D48.8V The Tx Fme=
, Eloundou(652586578) from Huawei is informed","Mboua Thierry","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power issue, site is on gen with Ubaie=3D48.8V The Tx Fme, Elou=
ndou(652586578) from Huawei is informed","gerard.tchangoue@matech-cameroun.=
com","450795","27-08-2025 21:36:23","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005777511","S=
IMBOCK BONAMBAPE","","27-08-2025 21:17:13","27-08-2025 21:12:07","27-08-202=
5 21:16:52","Grid outage, Site went down before Gen start due to poor backu=
p/ // Grid Return","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Grid Return","gerard.tchangoue@matech-camerou=
n.com","308","27-08-2025 21:17:13","MATECH CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0005777499","B=
yemassi Carrefour","","27-08-2025 21:14:34","22-08-2025 16:22:21","22-08-20=
25 17:06:47","Grid outage, Site went down before Gen start due to poor back=
up/ // Grid Return","Paul BIBOUM","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup/ // Grid Return","gerard.tchangoue@matech-cameroun.=
com","449534","27-08-2025 21:14:34","MATECH CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0005777479","Sap=
eur Mimboman","","27-08-2025 21:09:11","27-08-2025 21:04:06","28-08-2025 00=
:21:17","Access issues due to lanlord during the night//Grid return","Mba L=
azare Herve","Access Denial","Lease Or Legal","Landlord Related Issues","Ac=
cess Issue - Land Lord","Access issues due to lanlord during the night//Gri=
d return","gerard.tchangoue@matech-cameroun.com","306","27-08-2025 21:09:11=
","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005776555","M=
endong","","27-08-2025 18:56:48","27-08-2025 18:56:38","27-08-2025 18:57:04=
","Grid fluctuations, Site went down due to Gen overload (15KVA//130A) // g=
rid stabilized","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid fluctuations, Site went down due to Gen overload (15K=
VA//130A) // grid stabilized","gerard.tchangoue@matech-cameroun.com","11","=
27-08-2025 18:56:48","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005775952","C=
-Supreme","","27-08-2025 16:57:00","27-08-2025 16:54:52","27-08-2025 17:10:=
11","Active // No power issue, site on Grid with Ubaie=3D54.5V, TX FME Bric=
e Tsague (650 21 40 96 / Huawei) is informed","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No p=
ower issue, site on Grid with Ubaie=3D54.5V, TX FME Brice Tsague (650 21 40=
 96 / Huawei) is informed","gerard.tchangoue@matech-cameroun.com","129","27=
-08-2025 16:57:00","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005775722","M=
vog-Ada_OCM","","27-08-2025 16:14:50","27-08-2025 16:09:44","27-08-2025 16:=
23:51","Grid only on site, No space on site to deploy MDGE // Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 only on site, No space on site to deploy MDGE // Grid return","gerard.tcha=
ngoue@matech-cameroun.com","308","27-08-2025 16:14:50","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0005775699","Nko=
londom","","27-08-2025 16:11:50","27-08-2025 16:10:44","27-08-2025 16:20:38=
","Site down due to work of Roberto (GAIO /674715333) // End of work","Fabr=
ice Pouakam","Equipment Replacement","Passive","Planned Activity","Planned =
Activity - Passive","Site down due to work of Roberto (GAIO /674715333) // =
End of work","loic.noumsi@matech-cameroun.com","67","27-08-2025 16:11:50","=
MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005775369","N=
koabang Ebolmedjock","","27-08-2025 15:28:38","27-08-2025 15:23:27","27-08-=
2025 15:26:33","	Active//No power issue, Site on Gen. Notice that it is imp=
acted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","	Active//No power issue, Site on Gen. Notice that it is impacted=
 by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","gerard.tchangoue@matech-=
cameroun.com","313","27-08-2025 15:28:38","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005775363","N=
simalen OCM","","27-08-2025 15:27:34","27-08-2025 15:19:27","27-08-2025 16:=
46:26","le c=E2ble du g=E9n=E9rateur qui alimente le site est br=FBl=E9 // =
jonction de c=E2ble et d=E9marrage manuel du g=E9n=E9rateur","Albran Byorel=
","Equipment Repair","Passive","Infrastructure","Armoured Cable","le c=E2bl=
e du g=E9n=E9rateur qui alimente le site est br=FBl=E9 // jonction de c=E2b=
le et d=E9marrage manuel du g=E9n=E9rateur","gerard.tchangoue@matech-camero=
un.com","488","27-08-2025 15:27:34","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005774925","EKI=
E","","27-08-2025 14:31:51","27-08-2025 14:27:47","27-08-2025 14:45:02","Gr=
id outage, site went down due to main gen faulty // Grid return","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Gr=
id outage, site went down due to main gen faulty // Grid return","loic.noum=
si@matech-cameroun.com","245","27-08-2025 14:31:51","MATECH CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0005774401","B=
iteng","","27-08-2025 13:09:30","27-08-2025 13:05:02","27-08-2025 13:40:11"=
,"Site impacted by Mimboman Nodal (Site not managed by IHS)","Mba Lazare He=
rve","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","Site impacted by Mimboman Nodal (Site not managed =
by IHS)","gerard.tchangoue@matech-cameroun.com","269","27-08-2025 13:09:30"=
,"MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005774362","Nko=
abang2","","27-08-2025 13:07:36","27-08-2025 13:06:26","27-08-2025 15:36:53=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed// Grid return","Mba Lazare Herve","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen o=
verload (22KVA, 330A), SS Blaise IHS is informed// Grid return","cedric.tia=
ni@matech-cameroun.com","72","27-08-2025 13:07:36","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005774218","Fou=
da Quarter","","27-08-2025 12:44:00","27-08-2025 12:43:50","27-08-2025 13:0=
7:44","Site went down due to work of Our Fme Delor (659906652) is on site (=
Replacement of Grid Contactor)//End of work","Delor Telezing","Installation=
 Activity","Passive","Planned Activity","Installation Activity","Site went =
down due to work of Our Fme Delor (659906652) is on site (Replacement of Gr=
id Contactor)//End of work","cedric.tiani@matech-cameroun.com","11","27-08-=
2025 12:44:00","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005774195","EKI=
E","","27-08-2025 12:40:31","27-08-2025 12:36:17","27-08-2025 14:18:21","Gr=
id outage, site went down due to main gen faulty // Grid return","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Gr=
id outage, site went down due to main gen faulty // Grid return","cedric.ti=
ani@matech-cameroun.com","255","27-08-2025 12:40:31","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005774161","Ona=
ngondi (melen bikop)","","27-08-2025 12:30:38","27-08-2025 12:24:11","27-08=
-2025 13:04:24","Site went down because Gen failed to start due to Gen in m=
anual mode //He started the Gen manually","Fanda Brice","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Site went down because Gen fai=
led to start due to Gen in manual mode //He started the Gen manually","cedr=
ic.tiani@matech-cameroun.com","388","27-08-2025 12:30:38","MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0005774012","c=
hina embassy yde","","27-08-2025 12:07:49","27-08-2025 11:58:32","27-08-202=
5 12:08:46","Active//No power issue site on grid with U=3D52.4V The Tx FME =
Eloundou Bertrand from Huawei is informed","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power =
issue site on grid with U=3D52.4V The Tx FME Eloundou Bertrand from Huawei =
is informed","gerard.tchangoue@matech-cameroun.com","558","27-08-2025 12:07=
:49","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0005773847","Mam=
bine","","27-08-2025 11:51:42","27-08-2025 11:48:37","27-08-2025 12:48:19",=
"	Grid outage, site went down because gen ran untill fuel shortage // Refue=
ling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","=
	Grid outage, site went down because gen ran untill fuel shortage // Refuel=
ing done","cedric.tiani@matech-cameroun.com","187","27-08-2025 11:51:42","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_178","NOCINC0005773724","Emombo",=
"","27-08-2025 11:34:32","27-08-2025 11:30:19","27-08-2025 11:36:00","Casca=
ded Incident from TTO5984852","Mba Lazare Herve","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Site impacted by Mimboman Nodal","gerard=
.tchangoue@matech-cameroun.com","253","27-08-2025 11:34:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0005773719","Kondengu=
i","","27-08-2025 11:34:32","27-08-2025 11:30:19","27-08-2025 11:36:00","Ca=
scaded Incident from TTO5984852","Albran Byorel","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Site impacted by Mimboman Nodal","gerard=
.tchangoue@matech-cameroun.com","253","27-08-2025 11:34:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_736","NOCINC0005773723","CRF Nkoa=
bang","","27-08-2025 11:34:32","27-08-2025 11:30:19","27-08-2025 11:36:00",=
"Cascaded Incident from TTO5984852","Mba Lazare Herve","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Site impacted by Mimboman Nodal","=
gerard.tchangoue@matech-cameroun.com","253","27-08-2025 11:34:32","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0005773721","Nkolo II=
 New","","27-08-2025 11:34:32","27-08-2025 11:30:19","27-08-2025 11:36:00",=
"Cascaded Incident from TTO5984852","Mba Lazare Herve","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Site impacted by Mimboman Nodal","=
gerard.tchangoue@matech-cameroun.com","253","27-08-2025 11:34:32","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_093","NOCINC0005773717","Chapelle=
-Essos","","27-08-2025 11:34:31","27-08-2025 11:30:19","27-08-2025 11:36:00=
","Cascaded Incident from TTO5984852","Delor Telezing","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Site impacted by Mimboman Nodal","=
gerard.tchangoue@matech-cameroun.com","252","27-08-2025 11:34:31","MATECH C=
MR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005773700","E=
SSOS OASIS 1111","IHS_YND_093, IHS_YND_114, IHS_YND_709, IHS_YND_736, IHS_Y=
ND_178","27-08-2025 11:31:32","27-08-2025 11:30:19","27-08-2025 11:36:00","=
Site impacted by Mimboman Nodal","Siligap Boris","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","Site i=
mpacted by Mimboman Nodal","gerard.tchangoue@matech-cameroun.com","74","27-=
08-2025 11:31:32","MATECH CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0005773656","San=
ta Barbara Gottam","","27-08-2025 11:23:57","27-08-2025 11:22:52","27-08-20=
25 11:23:55","ACTIVE No power issue U=3D52,9V site on Grid tx fme Symphorie=
n /650257151 from huawei is informed","Delor Telezing","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE N=
o power issue U=3D52,9V site on Grid tx fme Symphorien /650257151 from huaw=
ei is informed","cedric.tiani@matech-cameroun.com","66","27-08-2025 11:23:5=
7","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005773589","Nko=
abang2","","27-08-2025 11:06:47","27-08-2025 11:05:17","27-08-2025 11:16:12=
","Grid outage, Site went down due to Gen overload (22KVA, 330A), SS Blaise=
 IHS is informed/He reduiced the load and started the Gen manually","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down due to Gen overload (22KVA, 330A), SS Blaise IHS is=
 informed/He reduiced the load and started the Gen manually","cedric.tiani@=
matech-cameroun.com","92","27-08-2025 11:06:47","MATECH CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0005773301","E=
lig-Essono","","27-08-2025 10:13:26","27-08-2025 10:10:19","27-08-2025 11:4=
5:48","Site went down due to PWC dysfunction ZTE cause by low voltage //He =
reset it and site on Grid","Paul BIBOUM","Equipment Repair","Passive","Rect=
ifier","Rectifier Module Overloaded","Site went down due to PWC dysfunction=
 ZTE cause by low voltage //He reset it and site on Grid","gerard.tchangoue=
@matech-cameroun.com","188","27-08-2025 10:13:26","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005772602","N=
koabang2","","27-08-2025 08:19:06","27-08-2025 08:14:53","27-08-2025 10:59:=
37","Grid fluctuations, site went down due to gen overload (22KVA, 330A), S=
S Blaise IHS is informed // Grid stabilised","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, site wen=
t down due to gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid=
 stabilised","gerard.tchangoue@matech-cameroun.com","255","27-08-2025 08:19=
:06","MATECH CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0005772601","Nko=
ngtock","","27-08-2025 08:19:03","27-08-2025 08:18:56","27-08-2025 08:56:37=
","No power issue on site Ubaie=3D48,7V site on Gen The Tx FME Etienne//695=
033981 from Huawei is informed","Kemeni Franklin","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site Ubaie=3D48,7V site on Gen The Tx FME Etienne//695033981 from Huaw=
ei is informed","cedric.tiani@matech-cameroun.com","8","27-08-2025 08:19:03=
","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005772566","T=
SINGA VILLAGE 2","","27-08-2025 08:09:26","27-08-2025 08:01:18","27-08-2025=
 08:41:44","Grid outage,site went down because Gen failed to start due to p=
riming pump faulty//He manually started the Gen (Replacement ongoing)","Del=
or Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Lifting P=
ump Faulty","Grid outage,site went down because Gen failed to start due to =
priming pump faulty//He manually started the Gen (Replacement ongoing)","ol=
ivier.kwedi@ihstowers.com","490","27-08-2025 08:09:26","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005772535","Nko=
lnda","","27-08-2025 08:00:42","27-08-2025 07:56:31","27-08-2025 08:49:13",=
"Grid fluctuation, site went down before Gen start due to poor battery back=
up // Grid return","Albran Byorel","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid fluctuation, site went down before=
 Gen start due to poor battery backup // Grid return","gerard.tchangoue@mat=
ech-cameroun.com","253","27-08-2025 08:00:42","MATECH CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0005772423","M=
VAN SACEL","","27-08-2025 07:36:18","27-08-2025 07:33:05","27-08-2025 07:58=
:12","Grid outage,site went down because Gen failed to start due to Gen con=
tactor faulty//He started the Gen  manually","MINKA NICOLAS","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage,site went do=
wn because Gen failed to start due to Gen contactor faulty//He started the =
Gen  manually","gerard.tchangoue@matech-cameroun.com","195","27-08-2025 07:=
36:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0005772189","Essomba"=
,"","27-08-2025 06:49:44","27-08-2025 04:00:59","27-08-2025 10:13:59","Casc=
aded Incident from TTO5982628","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down  because  thieves hav=
e stolen almost all cables on site//Some section has been reconnected to br=
ing up the site(Site Vandalised)","gerard.tchangoue@matech-cameroun.com","1=
0125","27-08-2025 06:49:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0005772188","AWAE OCM=
","","27-08-2025 06:49:43","27-08-2025 04:00:59","27-08-2025 10:13:59","Cas=
caded Incident from TTO5982628","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down  because  thieves ha=
ve stolen almost all cables on site//Some section has been reconnected to b=
ring up the site(Site Vandalised)","gerard.tchangoue@matech-cameroun.com","=
10124","27-08-2025 06:49:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0005772186","Bitoto",=
"","27-08-2025 06:49:43","27-08-2025 04:00:59","27-08-2025 10:13:59","Casca=
ded Incident from TTO5982628","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down  because  thieves have=
 stolen almost all cables on site//Some section has been reconnected to bri=
ng up the site(Site Vandalised)","gerard.tchangoue@matech-cameroun.com","10=
124","27-08-2025 06:49:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0005772187","Tradex-N=
komo","","27-08-2025 06:49:43","27-08-2025 04:00:59","27-08-2025 10:13:59",=
"Cascaded Incident from TTO5982628","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down  because  thieves h=
ave stolen almost all cables on site//Some section has been reconnected to =
bring up the site(Site Vandalised)","gerard.tchangoue@matech-cameroun.com",=
"10124","27-08-2025 06:49:43","MATECH CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0005772141","C=
arington","","27-08-2025 06:38:05","27-08-2025 06:36:55","29-08-2025 00:08:=
52","Grid only, Landlor refuses to deploy Gen//Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid only, Landlor =
refuses to deploy Gen//Grid return","gerard.tchangoue@matech-cameroun.com",=
"72","27-08-2025 06:38:05","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005772099","Nko=
abang2","","27-08-2025 06:26:33","27-08-2025 06:22:18","27-08-2025 07:01:58=
","Grid fluctuations, site went down due to gen overload (22KVA, 330A), SS =
Blaise IHS is informed // Grid stabilised","Mba Lazare Herve","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, site went =
down due to gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid s=
tabilised","franck.nkomot@matech-cameroun.com","258","27-08-2025 06:26:33",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005771873","M=
vog-Ada_OCM","","27-08-2025 05:19:10","27-08-2025 05:16:01","27-08-2025 05:=
38:01","Grid only on site, No space on site to deploy MDGE // Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 only on site, No space on site to deploy MDGE // Grid return","franck.nkom=
ot@matech-cameroun.com","191","27-08-2025 05:19:10","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005771845","Nko=
abang2","","27-08-2025 05:06:06","27-08-2025 04:57:49","27-08-2025 06:16:49=
","Grid fluctuations, site went down due to gen overload (22KVA, 330A), SS =
Blaise IHS is informed // Grid stabilised","Mba Lazare Herve","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, site went =
down due to gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid s=
tabilised","franck.nkomot@matech-cameroun.com","499","27-08-2025 05:06:06",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0005771728","Biteng-M=
aetur","","27-08-2025 04:15:30","27-08-2025 04:00:59","27-08-2025 10:13:59"=
,"Cascaded Incident from TTO5982628","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down  because  thiev=
es have stolen almost all cables on site//Some section has been reconnected=
 to bring up the site(Site Vandalised)","franck.nkomot@matech-cameroun.com"=
,"870","27-08-2025 04:15:30","MATECH CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0005771711","Bit=
eng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179, IHS_YND_249","27-=
08-2025 04:09:56","27-08-2025 04:00:59","27-08-2025 12:58:37","Site went do=
wn  because  thieves have stolen almost all cables on site//Some section ha=
s been reconnected to bring up the site(Site Vandalised)","Mba Lazare Herve=
","Site Asset Theft","Theft","Theft","AC Cable Stolen","Site went down  bec=
ause  thieves have stolen almost all cables on site//Some section has been =
reconnected to bring up the site(Site Vandalised)","franck.nkomot@matech-ca=
meroun.com","538","27-08-2025 04:09:56","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0005771096","H=
-General-Yde","","27-08-2025 00:45:49","27-08-2025 00:44:42","27-08-2025 00=
:54:42","Grid fluctuation,Site went down because GEN failed to start due to=
 grid bad voltage (lack of 02 phases) // He bridged the gap with the right =
phase","Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation,Site went down because GEN failed to=
 start due to grid bad voltage (lack of 02 phases) // He bridged the gap wi=
th the right phase","franck.nkomot@matech-cameroun.com","68","27-08-2025 00=
:45:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_190","NOCINC0005770785","Ngousso-=
II","","26-08-2025 23:17:51","26-08-2025 23:00:35","27-08-2025 00:05:35","C=
ascaded Incident from TTO5981567","MFOUAGUEGUE MATHIEU","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down because the PWC=
 IPT dysfunctioning // He reset hit, Site on Grid","franck.nkomot@matech-ca=
meroun.com","1036","26-08-2025 23:17:51","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005770750","Par=
adis Hotel","","26-08-2025 23:07:56","26-08-2025 23:01:50","26-08-2025 23:2=
3:50","Grid Outage, site went down because Gen Overload (12.5Kva, 100A) SS =
IHS BLAISE RAOUL confirmed//Grid return","Siligap Boris","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid Outage, site went down becaus=
e Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL confirmed//Grid return",=
"franck.nkomot@matech-cameroun.com","367","26-08-2025 23:07:56","MATECH CMR=
"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005770739","E=
toudi","","26-08-2025 23:06:15","26-08-2025 23:00:07","26-08-2025 23:29:07"=
,"Grid outage,site went down due to gen overload(20kva,300 A) SS HIS Bernar=
d Atangana is informed // Site stabilised","Fabrice Pouakam","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage,site went down due=
 to gen overload(20kva,300 A) SS HIS Bernard Atangana is informed // Site s=
tabilised","franck.nkomot@matech-cameroun.com","369","26-08-2025 23:06:15",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0005770738","N=
kolmesseng","IHS_YND_190","26-08-2025 23:04:57","26-08-2025 23:00:35","27-0=
8-2025 00:07:35","Site went down because the PWC IPT dysfunctioning // He r=
eset hit, Site on Grid","Siligap Boris","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Site went down because the PWC IPT dys=
functioning // He reset hit, Site on Grid","franck.nkomot@matech-cameroun.c=
om","262","26-08-2025 23:04:57","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0005770718","Mam=
bine","","26-08-2025 23:01:10","26-08-2025 22:54:00","26-08-2025 23:16:00",=
"Grid outage, site went down because gen ran until fuel shortage // Refueli=
ng done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage, site went down because gen ran until fuel shortage // Refueling =
done","franck.nkomot@matech-cameroun.com","431","26-08-2025 23:01:10","MATE=
CH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005770549","Nsi=
meyong","","26-08-2025 22:18:40","26-08-2025 22:12:32","27-08-2025 00:45:32=
","Grid outage, Site went down because Gen started and stopped due to High =
temp, // Door opened, the generator has cooled down and Gen card reset. Gen=
 started manually","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen",=
"ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site went dow=
n because Gen started and stopped due to High temp, // Door opened, the gen=
erator has cooled down and Gen card reset. Gen started manually","cedric.ti=
ani@matech-cameroun.com","369","26-08-2025 22:18:40","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005770491","EKI=
E","","26-08-2025 22:09:37","26-08-2025 21:00:29","26-08-2025 22:57:29","Si=
te went down because gen started and stopped with low oil pressure due to o=
il pipeline broken //he reconnected it and added oil and started the gen","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pres=
sure","Site went down because gen started and stopped with low oil pressure=
 due to oil pipeline broken //he reconnected it and added oil and started t=
he gen","vanel.mbiada@matech-cameroun.com","4149","26-08-2025 22:09:37","MA=
TECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005770288","Nsi=
meyong","","26-08-2025 21:30:35","26-08-2025 21:27:33","26-08-2025 21:32:09=
","Grid outage, Site went down because Gen started and stopped due to High =
temp, // Door opened the generator has cooled down and Gen card reset and G=
en start manually","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen",=
"ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site went dow=
n because Gen started and stopped due to High temp, // Door opened the gene=
rator has cooled down and Gen card reset and Gen start manually","cedric.ti=
ani@matech-cameroun.com","183","26-08-2025 21:30:35","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005770094","ODZ=
A MINKAN EDIBI ASSI","","26-08-2025 20:53:01","26-08-2025 20:50:50","26-08-=
2025 21:00:50","ACTIVE//No power issue on site ,site on Grid with Ubaie=3D =
53V The Tx FME Leonel Adjep /655184876/From HUAWEI is informed","Albran Byo=
rel","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","ACTIVE//No power issue on site ,site on Grid with Ubaie=3D=
 53V The Tx FME Leonel Adjep /655184876/From HUAWEI is informed","cedric.ti=
ani@matech-cameroun.com","132","26-08-2025 20:53:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005770080","Emana Ly=
cee","","26-08-2025 20:51:17","26-08-2025 20:44:41","26-08-2025 21:04:06","=
Cascaded Incident from TTO5980803","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to CB(80A)PWC =
Huawei  that tripped OCM is faulty.// He repaced by a 125A and site on Gen"=
,"vanel.mbiada@matech-cameroun.com","396","26-08-2025 20:51:17","MATECH CMR=
"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005770066","E=
mana lycee 2","IHS_YND_274","26-08-2025 20:48:46","26-08-2025 20:44:41","26=
-08-2025 21:11:52","Site went down due to CB(80A)PWC Huawei  that tripped O=
CM is faulty.// He repaced by a 125A and site on Gen","Fabrice Pouakam","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker =
Issue","Site went down due to CB(80A)PWC Huawei  that tripped OCM is faulty=
.// He repaced by a 125A and site on Gen","vanel.mbiada@matech-cameroun.com=
","247","26-08-2025 20:48:46","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005769933","ODZ=
A MINKAN EDIBI ASSI","","26-08-2025 20:24:13","26-08-2025 20:20:06","26-08-=
2025 20:43:34","ACTIVE//No power issue on site ,site on Grid with Ubaie=3D =
53V The Tx FME Leonel Adjep /655184876/From HUAWEI is informed","Albran Byo=
rel","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","ACTIVE//No power issue on site ,site on Grid with Ubaie=3D=
 53V The Tx FME Leonel Adjep /655184876/From HUAWEI is informed","cedric.ti=
ani@matech-cameroun.com","248","26-08-2025 20:24:13","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005769866","Nsi=
meyong","","26-08-2025 20:12:57","26-08-2025 20:11:47","26-08-2025 20:29:08=
","Grid outage, Site went down because Gen started and stopped due to High =
temp, // Door opened, the generator has cooled down and Gen card reset. Gen=
 started manually","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen",=
"ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site went dow=
n because Gen started and stopped due to High temp, // Door opened, the gen=
erator has cooled down and Gen card reset. Gen started manually","cedric.ti=
ani@matech-cameroun.com","71","26-08-2025 20:12:57","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005769858","D=
amas","IHS_YND_518","26-08-2025 20:10:40","26-08-2025 20:00:59","26-08-2025=
 20:15:18","ACTIVE// No power issue on site, site on Grid with Ubaie=3D 54V=
 The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed. impacted by N=
simeyong","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","ACTIVE// No power issue on site, site=
 on Grid with Ubaie=3D 54V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI =
is informed. impacted by Nsimeyong","vanel.mbiada@matech-cameroun.com","582=
","26-08-2025 20:10:40","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005769834","M=
ontee-Jouvence-II","","26-08-2025 20:05:59","26-08-2025 20:00:59","26-08-20=
25 20:15:18","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active"=
,"Cascade Active","ACTIVE// No power issue on site, site on Grid with Ubaie=
=3D 54V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed. impact=
ed by Nsimeyong","vanel.mbiada@matech-cameroun.com","689","26-08-2025 20:05=
:59","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005769779","E=
lig-Edzoa","","26-08-2025 19:51:24","26-08-2025 19:50:16","26-08-2025 22:24=
:16","Grid only site,No mobile gen available // Grid restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site,N=
o mobile gen available // Grid restored","vanel.mbiada@matech-cameroun.com"=
,"70","26-08-2025 19:51:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005769681","Angongo"=
,"","26-08-2025 19:35:11","26-08-2025 19:27:33","26-08-2025 19:47:41","Casc=
aded Incident from TTO5980355","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site, Site went down because =
gen fails to start due to hybrid systeme dysfunctionning // Reset done and =
gen started","vanel.mbiada@matech-cameroun.com","458","26-08-2025 19:35:11"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0005769674","E=
beba","IHS_YND_335","26-08-2025 19:33:49","26-08-2025 19:27:33","26-08-2025=
 19:47:41","Grid outage site, Site went down because gen fails to start due=
 to hybrid systeme dysfunctionning // Reset done and gen started","Fanda Br=
ice","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid out=
age site, Site went down because gen fails to start due to hybrid systeme d=
ysfunctionning // Reset done and gen started","vanel.mbiada@matech-cameroun=
.com","377","26-08-2025 19:33:49","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005769605","M=
ontee-Jouvence-II","","26-08-2025 19:20:06","26-08-2025 19:14:50","26-08-20=
25 19:27:34","Grid fluctuation, Site went down because Gen failed to start =
due to Grid bad voltage //Grid stabilized","Hyemafo Gildas","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation=
, Site went down because Gen failed to start due to Grid bad voltage //Grid=
 stabilized","vanel.mbiada@matech-cameroun.com","318","26-08-2025 19:20:06"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005769597","D=
amas","","26-08-2025 19:18:27","26-08-2025 19:14:18","26-08-2025 19:28:05",=
"ACTIVE// No power issue on site, site on Grid with Ubaie=3D 54V The Tx Fme=
 Mbah Hosiah //674007438/ from HUAWEI is informed. impacted by Nsimeyong","=
MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","ACTIVE// No power issue on site, site on Grid wi=
th Ubaie=3D 54V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed=
. impacted by Nsimeyong","vanel.mbiada@matech-cameroun.com","250","26-08-20=
25 19:18:27","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005769582","Nsi=
meyong","","26-08-2025 19:16:22","26-08-2025 19:10:13","26-08-2025 19:26:40=
","Grid outage, Site went down because Gen started and stopped due to High =
temp, // Door opened the generator has cooled down and Gen card reset and G=
en start manually","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen",=
"ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site went dow=
n because Gen started and stopped due to High temp, // Door opened the gene=
rator has cooled down and Gen card reset and Gen start manually","cedric.ti=
ani@matech-cameroun.com","370","26-08-2025 19:16:22","MATECH CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0005769499","M=
ontee-Jouvence","","26-08-2025 19:02:29","26-08-2025 19:01:20","26-08-2025 =
19:20:07","Grid Outage Site went down because Gen failed to start due to Gr=
id Contactors Faulty // He started Gen manualy","Hyemafo Gildas","Equipment=
 Repair","Passive","Control Panel","ATS-AMF Issue","Grid Outage Site went d=
own because Gen failed to start due to Grid Contactors Faulty // He started=
 Gen manualy","vanel.mbiada@matech-cameroun.com","70","26-08-2025 19:02:29"=
,"MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005769142","Nsi=
meyong","","26-08-2025 18:11:15","26-08-2025 18:08:07","26-08-2025 18:23:34=
","Grid outage, Site went down because Gen started and stopped due to High =
temp, // Door opened the generator has cooled down and Gen card reset and G=
en start manually","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen",=
"ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site went dow=
n because Gen started and stopped due to High temp, // Door opened the gene=
rator has cooled down and Gen card reset and Gen start manually","cedric.ti=
ani@matech-cameroun.com","189","26-08-2025 18:11:15","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005768889","EKI=
E","","26-08-2025 17:29:51","26-08-2025 17:22:43","26-08-2025 17:47:43","Si=
te went down because gen started and stopped with low oil pressure due to o=
il pipeline broken  //he reconnected it and  added oil and started the gen"=
,"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pr=
essure","Site went down because gen started and stopped with low oil pressu=
re due to oil pipeline broken  //he reconnected it and  added oil and start=
ed the gen","cedric.tiani@matech-cameroun.com","429","26-08-2025 17:29:51",=
"MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005768699","Mai=
son komkana New","","26-08-2025 17:05:31","26-08-2025 17:04:23","26-08-2025=
 18:25:47","Site went down due to insufficient rectifiers on site//He reset=
 it and site on Grid","Mboua Thierry","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down due to insufficient rectifiers on si=
te//He reset it and site on Grid","cedric.tiani@matech-cameroun.com","69","=
26-08-2025 17:05:31","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005768684","Jou=
vence Mbenda","","26-08-2025 17:03:31","26-08-2025 16:54:19","26-08-2025 17=
:38:08","Grid outage, site went down because gen start and stopped with hig=
h temp alarm //Grid return","Hyemafo Gildas","Equipment Repair","Passive","=
ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, sit=
e went down because gen start and stopped with high temp alarm //Grid retur=
n","cedric.tiani@matech-cameroun.com","553","26-08-2025 17:03:31","MATECH C=
MR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005768640","Elo=
umdem stade","","26-08-2025 16:53:51","26-08-2025 16:47:42","26-08-2025 16:=
54:12","No power issue, site is on Grid and Ubaie=3D56.5V, The FME TX Fulbe=
rt(654266068)   of huawei is informed.","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue, site is on Grid and Ubaie=3D56.5V, The FME TX Fulbert(654266068)   o=
f huawei is informed.","cedric.tiani@matech-cameroun.com","371","26-08-2025=
 16:53:51","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005768511","D=
amas","","26-08-2025 16:41:14","26-08-2025 16:39:01","26-08-2025 16:54:50",=
"ACTIVE// No power issue on site, site on Grid with Ubaie=3D 54V The Tx Fme=
 Mbah Hosiah //674007438/ from HUAWEI is informed. impacted by Nsimeyon","M=
INKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","ACTIVE// No power issue on site, site on Grid wit=
h Ubaie=3D 54V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed.=
 impacted by Nsimeyon","vanel.mbiada@matech-cameroun.com","134","26-08-2025=
 16:41:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005768495","Ahala","=
","26-08-2025 16:39:46","26-08-2025 16:28:31","26-08-2025 16:50:40","Cascad=
ed Incident from TTO5978942","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, Site went down because Gen =
started and stopped due to High temp, // Door opened the generator has cool=
ed down and Gen card reset and Gen start manually","cedric.tiani@matech-cam=
eroun.com","675","26-08-2025 16:39:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0005768496","Afanoya"=
,"","26-08-2025 16:39:46","26-08-2025 16:28:31","26-08-2025 16:50:40","Casc=
aded Incident from TTO5978942","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down because Ge=
n started and stopped due to High temp, // Door opened the generator has co=
oled down and Gen card reset and Gen start manually","cedric.tiani@matech-c=
ameroun.com","675","26-08-2025 16:39:46","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005768469","MBA=
LNGONG LYCEE","","26-08-2025 16:38:15","26-08-2025 16:34:09","26-08-2025 16=
:38:39","Active//No power Issue Site on Grid Ubai =3D53.8V, The FME The TX =
FME Fulbert(654266068) is informed.","Fanda Brice","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower Issue Site on Grid Ubai =3D53.8V, The FME The TX FME Fulbert(654266068=
) is informed.","cedric.tiani@matech-cameroun.com","248","26-08-2025 16:38:=
15","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005768382","Nsi=
meyong","IHS_YND_257, IHS_YND_313","26-08-2025 16:29:39","26-08-2025 16:28:=
31","26-08-2025 16:50:40","Grid outage, Site went down because Gen started =
and stopped due to High temp, // Door opened the generator has cooled down =
and Gen card reset and Gen start manually","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gr=
id outage, Site went down because Gen started and stopped due to High temp,=
 // Door opened the generator has cooled down and Gen card reset and Gen st=
art manually","cedric.tiani@matech-cameroun.com","69","26-08-2025 16:29:39"=
,"MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005768340","EKI=
E","","26-08-2025 16:24:58","26-08-2025 16:19:49","26-08-2025 17:11:37","Si=
te went down because gen started and stopped with low oil pressure due to o=
il pipeline broken  //he reconnected it and  added oil and started the gen"=
,"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pr=
essure","Site went down because gen started and stopped with low oil pressu=
re due to oil pipeline broken  //he reconnected it and  added oil and start=
ed the gen","cedric.tiani@matech-cameroun.com","310","26-08-2025 16:24:58",=
"MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005767941","Aka=
k-Nkozoa-MTN-IHS","","26-08-2025 15:37:40","26-08-2025 15:36:31","26-08-202=
5 16:16:15","Site went down due to work of SS HIS Felix Bateu  on site(Repl=
acement of the DC BOX)//End of work","Fabrice Pouakam","Installation Activi=
ty","Passive","Planned Activity","Installation Activity","Site went down du=
e to work of SS HIS Felix Bateu  on site(Replacement of the DC BOX)//End of=
 work","cedric.tiani@matech-cameroun.com","71","26-08-2025 15:37:40","MATEC=
H CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005767794","Jou=
vence Mbenda","","26-08-2025 15:16:23","26-08-2025 15:14:12","26-08-2025 15=
:17:00","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and manually start the gen","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // He added water and manually start the gen","cedric.ti=
ani@matech-cameroun.com","133","26-08-2025 15:16:23","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005767761","O=
LAMA","","26-08-2025 15:08:26","26-08-2025 15:03:12","26-08-2025 15:10:28",=
"Active // No power issue on site Ubaie: 54.6V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue on site Ubaie: 54.6V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","vanel.mbiada@matech-cameroun.com","316","26-08-2=
025 15:08:26","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005767343","EKI=
E","","26-08-2025 14:21:17","26-08-2025 14:18:11","26-08-2025 14:41:21","Si=
te went down because gen started and stopped with low oil pressure //he add=
ed oil and started the gen","Albran Byorel","Equipment Repair","Passive","A=
CDG Gen","ACDG - Low Oil Pressure","Site went down because gen started and =
stopped with low oil pressure //he added oil and started the gen","loic.nou=
msi@matech-cameroun.com","187","26-08-2025 14:21:17","MATECH CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0005767135","H=
-Deputes","","26-08-2025 13:39:27","26-08-2025 13:34:16","26-08-2025 15:14:=
30","grid outage,no space to deploy a mobil gen//Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no sp=
ace to deploy a mobil gen//Grid return","vanel.mbiada@matech-cameroun.com",=
"311","26-08-2025 13:39:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0005767023","Obobogo"=
,"","26-08-2025 13:25:19","26-08-2025 12:56:17","26-08-2025 13:02:49","Casc=
aded Incident from TTO5977224","MINKA NICOLAS","Cascade Outage","Active","C=
ascade Active","Cascade Active","	Site impacted by Efoulan Pont which is no=
t managed by IHS","vanel.mbiada@matech-cameroun.com","1742","26-08-2025 13:=
25:19","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005766890","N=
kozoa","","26-08-2025 12:59:55","26-08-2025 12:57:46","26-08-2025 12:59:36"=
,"Site down because IHS SS Felix BATEU is on site for work (installation of=
 DC BOX) // End of work","Fabrice Pouakam","Equipment Replacement","Passive=
","Planned Activity","Planned Activity - Passive","Site down because IHS SS=
 Felix BATEU is on site for work (installation of DC BOX) // End of work","=
vanel.mbiada@matech-cameroun.com","131","26-08-2025 12:59:55","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005766885","E=
foulan","IHS_YND_155","26-08-2025 12:57:28","26-08-2025 12:56:17","26-08-20=
25 13:02:49","	Site impacted by Efoulan Pont which is not managed by IHS","=
MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","	Site impacted by Efoulan Pont which is not mana=
ged by IHS","vanel.mbiada@matech-cameroun.com","72","26-08-2025 12:57:28","=
MATECH CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0005766872","Sim=
bock Maetur","","26-08-2025 12:55:45","26-08-2025 12:54:40","26-08-2025 12:=
56:23","Active//No power Issue Site on Grid Ubai =3D54.3V, The FME The TX F=
ME Mbah Hosiah (674007438) is informed.","Hyemafo Gildas","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power Issue Site on Grid Ubai =3D54.3V, The FME The TX FME Mbah Hosia=
h (674007438) is informed.","loic.noumsi@matech-cameroun.com","66","26-08-2=
025 12:55:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005766853","Montee-J=
ouvence","","26-08-2025 12:53:36","26-08-2025 12:48:54","26-08-2025 12:52:2=
5","Cascaded Incident from TTO5977172","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive"," grid outage, site down due to=
 DG overload (15KVA//130A) // He reduice the load and started DG","vanel.mb=
iada@matech-cameroun.com","282","26-08-2025 12:53:36","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005766836","M=
endong","IHS_YND_692, IHS_YND_569, IHS_YND_236","26-08-2025 12:51:59","26-0=
8-2025 12:48:54","26-08-2025 13:06:17"," grid outage, site down due to DG o=
verload (15KVA//130A) // He reduice the load and started DG","Hyemafo Gilda=
s","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"," grid outage,=
 site down due to DG overload (15KVA//130A) // He reduice the load and star=
ted DG","vanel.mbiada@matech-cameroun.com","187","26-08-2025 12:51:59","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0005766826","M=
endong Maeture","","26-08-2025 12:50:45","26-08-2025 12:48:54","26-08-2025 =
13:06:17","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive"," grid outage, site down due to DG overload (15KVA//130A)=
 // He reduice the load and started DG","vanel.mbiada@matech-cameroun.com",=
"4592","26-08-2025 12:50:45","MATECH CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0005766652","Sim=
bock MTN","","26-08-2025 12:21:46","26-08-2025 12:19:40","26-08-2025 12:21:=
55","Grid outage, site went down due to poor battery backup // Site stabili=
sed","Fanda Brice","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Battery Low","Grid outage, site went down due to poor battery backup =
// Site stabilised","loic.noumsi@matech-cameroun.com","127","26-08-2025 12:=
21:46","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005766636","Jou=
vence Mbenda","","26-08-2025 12:18:22","26-08-2025 12:16:00","26-08-2025 13=
:36:39","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and manually start the gen","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // He added water and manually start the gen","loic.noum=
si@matech-cameroun.com","144","26-08-2025 12:18:22","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005766586","Men=
dong3","","26-08-2025 12:10:44","26-08-2025 12:02:36","26-08-2025 17:36:12"=
,"Grid Outage No space to deploy a MDGE//Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Outage No space to d=
eploy a MDGE//Grid return","loic.noumsi@matech-cameroun.com","489","26-08-2=
025 12:10:44","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005766570","Car=
refour Simbock","","26-08-2025 12:09:04","26-08-2025 12:02:59","26-08-2025 =
17:40:23","Site went down due to Gen overload (17kva //180A) SS HIS Felix Z=
ambe is informed and confirmed//Grid return","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen ove=
rload (17kva //180A) SS HIS Felix Zambe is informed and confirmed//Grid ret=
urn","loic.noumsi@matech-cameroun.com","366","26-08-2025 12:09:04","MATECH =
CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005766513","D=
amas","IHS_YND_518","26-08-2025 11:54:07","26-08-2025 11:50:53","26-08-2025=
 12:05:52","Site impacted by Nsimeyon (	Grid outage, Gen stopped due to Hig=
h temp, // Door opened the generator has cooled down and Gen card reset and=
 Gen start manually)","MINKA NICOLAS","Equipment Repair","Passive","ACDG Ge=
n","Gen Temp High","Grid outage, Gen stopped due to High temp, // Door open=
ed the generator has cooled down and Gen card reset and Gen start manually"=
,"vanel.mbiada@matech-cameroun.com","195","26-08-2025 11:54:07","MATECH CMR=
"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005766479","Nsi=
meyong","","26-08-2025 11:48:14","26-08-2025 11:44:08","26-08-2025 12:03:35=
","Grid outage, Gen stopped due to High temp, // Door opened the generator =
has cooled down and Gen card reset and Gen start manually","MINKA NICOLAS",=
"Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, Gen s=
topped due to High temp, // Door opened the generator has cooled down and G=
en card reset and Gen start manually","loic.noumsi@matech-cameroun.com","24=
7","26-08-2025 11:48:14","MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0005766436","Abo=
me","","26-08-2025 11:41:40","26-08-2025 11:37:34","26-08-2025 11:55:25","G=
rid outage, Site went down before Gen start due to poor backup// Gen Automa=
tically Started","MINKA NICOLAS","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup// Gen Automatically Started","loic.noumsi@matech-cam=
eroun.com","248","26-08-2025 11:41:40","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005766265","Jou=
vence Mbenda","","26-08-2025 11:13:50","26-08-2025 11:09:35","26-08-2025 11=
:37:57","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and manually start the gen","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // He added water and manually start the gen","loic.noum=
si@matech-cameroun.com","257","26-08-2025 11:13:50","MATECH CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0005766226","M=
ontee-Jouvence","","26-08-2025 11:06:57","26-08-2025 10:41:25","26-08-2025 =
12:08:24","grid outage,site went down because gen failed to start due to co=
ntactor gen faulty//he byppassed the contactor and started the gen manually=
","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Load Con=
tactor","grid outage,site went down because gen failed to start due to cont=
actor gen faulty//he byppassed the contactor and started the gen manually",=
"vanel.mbiada@matech-cameroun.com","1533","26-08-2025 11:06:57","MATECH CMR=
"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0005766123","Men=
dong Maeture","","26-08-2025 10:45:20","26-08-2025 10:42:51","26-08-2025 11=
:52:59","Site went down due to fuel shortage // Refuelling done, site on GE=
N","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Site =
went down due to fuel shortage // Refuelling done, site on GEN","loic.noums=
i@matech-cameroun.com","150","26-08-2025 10:45:20","MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0005766112","Abo=
me","","26-08-2025 10:41:12","26-08-2025 10:39:06","26-08-2025 11:21:45","G=
rid outage, Gen failed to start due to Alarm Low Oil pressure // Gen Card r=
eset and Gen start manually","MINKA NICOLAS","Equipment Repair","Passive","=
ACDG Gen","ACDG - Low Oil Pressure","Grid outage, Gen failed to start due t=
o Alarm Low Oil pressure // Gen Card reset and Gen start manually","loic.no=
umsi@matech-cameroun.com","128","26-08-2025 10:41:12","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005766083","C=
omplexe-BEAC","","26-08-2025 10:35:52","26-08-2025 10:33:44","26-08-2025 10=
:51:38","Grid outage, Gen failed to start due to Startup order disconnected=
 // Startup order reconnected and Gen start manually","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen=
 failed to start due to Startup order disconnected // Startup order reconne=
cted and Gen start manually","vanel.mbiada@matech-cameroun.com","130","26-0=
8-2025 10:35:52","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005766070","M=
endong","","26-08-2025 10:32:47","26-08-2025 10:14:38","26-08-2025 12:31:27=
"," grid outage, site went down due to DG overload (15KVA//130A) // He redu=
ced load, site on gen","Hyemafo Gildas","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload"," grid outage, site went down due to DG overload (15=
KVA//130A) // He reduced load, site on gen","vanel.mbiada@matech-cameroun.c=
om","1090","26-08-2025 10:32:47","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005765954","Jou=
vence Mbenda","","26-08-2025 10:09:05","26-08-2025 10:06:00","26-08-2025 10=
:44:13","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and manually start the gen","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // He added water and manually start the gen","loic.noum=
si@matech-cameroun.com","186","26-08-2025 10:09:05","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005765913","D=
amas","IHS_YND_518","26-08-2025 10:01:51","26-08-2025 09:54:41","26-08-2025=
 10:29:02","(Site impacted by Nsimeyom) Grid outage, Gen stopped due to Hig=
h temp, // Door opened the generator has cooled down and Gen card reset and=
 Gen start manually","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen=
","Gen Temp High","	Grid outage, Gen stopped due to High temp, // Door open=
ed the generator has cooled down and Gen card reset and Gen start manually"=
,"vanel.mbiada@matech-cameroun.com","431","26-08-2025 10:01:51","MATECH CMR=
"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005765902","M=
ontee-Jouvence-II","","26-08-2025 09:59:53","26-08-2025 09:54:41","26-08-20=
25 12:05:52","	Grid outage, Gen stopped due to High temp, // Door opened th=
e generator has cooled down and Gen card reset and Gen start manually","Hye=
mafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"	Grid outage, Gen stopped due to High temp, // Door opened the generator =
has cooled down and Gen card reset and Gen start manually","vanel.mbiada@ma=
tech-cameroun.com","14361","26-08-2025 09:59:53","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005765898","Aha=
la Echangeur","","26-08-2025 09:59:14","26-08-2025 09:52:08","26-08-2025 10=
:24:17","Grid outage, site went down because Gen failed to start due to oil=
 leakage at the level of casing joint // He added oil, site on GEN","MINKA =
NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure",=
"Grid outage, site went down because Gen failed to start due to oil leakage=
 at the level of casing joint // He added oil, site on GEN","vanel.mbiada@m=
atech-cameroun.com","427","26-08-2025 09:59:14","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0005765836","Men=
dong vallee","","26-08-2025 09:48:14","26-08-2025 09:43:10","26-08-2025 10:=
01:44"," Grid outage, site went down because Gen failed to start due to PWC=
 dysfunctionning // He reset it and started Gen manually","Fanda Brice","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded"," Grid =
outage, site went down because Gen failed to start due to PWC dysfunctionni=
ng // He reset it and started Gen manually","loic.noumsi@matech-cameroun.co=
m","306","26-08-2025 09:48:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_147","NOCINC0005765737","Club Fra=
nce","","26-08-2025 09:30:20","26-08-2025 08:44:14","26-08-2025 09:23:32","=
Cascaded Incident from TTO5975457","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage, Gen stopped due to High temp, // Do=
or opened the generator has cooled down and Gen card reset and Gen start ma=
nually","loic.noumsi@matech-cameroun.com","2766","26-08-2025 09:30:20","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0005765735","MEFOU AS=
SI","","26-08-2025 09:30:19","26-08-2025 08:44:14","26-08-2025 09:23:32","C=
ascaded Incident from TTO5975457","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to High t=
emp, // Door opened the generator has cooled down and Gen card reset and Ge=
n start manually","loic.noumsi@matech-cameroun.com","2765","26-08-2025 09:3=
0:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_771","NOCINC0005765736","Jouvence=
 Mbenda","","26-08-2025 09:30:19","26-08-2025 08:44:14","26-08-2025 09:23:3=
2","Cascaded Incident from TTO5975457","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due t=
o High temp, // Door opened the generator has cooled down and Gen card rese=
t and Gen start manually","loic.noumsi@matech-cameroun.com","2765","26-08-2=
025 09:30:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0005765734","Afanoya"=
,"","26-08-2025 09:30:19","26-08-2025 08:44:14","26-08-2025 09:23:32","Casc=
aded Incident from TTO5975457","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to High t=
emp, // Door opened the generator has cooled down and Gen card reset and Ge=
n start manually","loic.noumsi@matech-cameroun.com","2765","26-08-2025 09:3=
0:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005765731","Eto koss=
 Yde","","26-08-2025 09:30:18","26-08-2025 08:44:14","26-08-2025 09:23:32",=
"Cascaded Incident from TTO5975457","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to High=
 temp, // Door opened the generator has cooled down and Gen card reset and =
Gen start manually","loic.noumsi@matech-cameroun.com","2764","26-08-2025 09=
:30:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005765732","ELOUMDEM=
 CARRIERE 2","","26-08-2025 09:30:18","26-08-2025 08:44:14","26-08-2025 09:=
23:32","Cascaded Incident from TTO5975457","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due =
to High temp, // Door opened the generator has cooled down and Gen card res=
et and Gen start manually","loic.noumsi@matech-cameroun.com","2764","26-08-=
2025 09:30:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0005765733","Barriere=
 IHS","","26-08-2025 09:30:18","26-08-2025 08:44:14","26-08-2025 09:23:32",=
"Cascaded Incident from TTO5975457","Hyemafo Gildas","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to H=
igh temp, // Door opened the generator has cooled down and Gen card reset a=
nd Gen start manually","loic.noumsi@matech-cameroun.com","2764","26-08-2025=
 09:30:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_150","NOCINC0005765728","Nkol-Mba=
nda","","26-08-2025 09:30:17","26-08-2025 08:44:14","26-08-2025 09:23:32","=
Cascaded Incident from TTO5975457","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to Hig=
h temp, // Door opened the generator has cooled down and Gen card reset and=
 Gen start manually","loic.noumsi@matech-cameroun.com","2763","26-08-2025 0=
9:30:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_282","NOCINC0005765729","Meyo",""=
,"26-08-2025 09:30:17","26-08-2025 08:44:14","26-08-2025 09:23:32","Cascade=
d Incident from TTO5975457","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Gen stopped due to High temp=
, // Door opened the generator has cooled down and Gen card reset and Gen s=
tart manually","loic.noumsi@matech-cameroun.com","2763","26-08-2025 09:30:1=
7","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_260","NOCINC0005765730","Simbock =
Maetur","","26-08-2025 09:30:17","26-08-2025 08:44:14","26-08-2025 09:23:32=
","Cascaded Incident from TTO5975457","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to=
 High temp, // Door opened the generator has cooled down and Gen card reset=
 and Gen start manually","loic.noumsi@matech-cameroun.com","2763","26-08-20=
25 09:30:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0005765727","ELOUMDEM=
 CARRIERE","","26-08-2025 09:30:16","26-08-2025 08:44:14","26-08-2025 09:23=
:32","Cascaded Incident from TTO5975457","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to=
 High temp, // Door opened the generator has cooled down and Gen card reset=
 and Gen start manually","loic.noumsi@matech-cameroun.com","2762","26-08-20=
25 09:30:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005765726","EBOM",""=
,"26-08-2025 09:30:16","26-08-2025 08:44:14","26-08-2025 09:23:32","Cascade=
d Incident from TTO5975457","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Gen stopped due to High temp=
, // Door opened the generator has cooled down and Gen card reset and Gen s=
tart manually","loic.noumsi@matech-cameroun.com","2762","26-08-2025 09:30:1=
6","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005765531","M=
ontee-Jouvence-II","","26-08-2025 09:07:05","26-08-2025 08:44:14","26-08-20=
25 09:23:32","Site impacted by Nsymeyon /T0351/IHS_YND_146 (	Grid outage, G=
en stopped due to High temp, // Door opened the generator has cooled down a=
nd Gen card reset and Gen start manually)","Hyemafo Gildas","Equipment Repa=
ir","Passive","ACDG Gen","Gen Temp High","	Grid outage, Gen stopped due to =
High temp, // Door opened the generator has cooled down and Gen card reset =
and Gen start manually","vanel.mbiada@matech-cameroun.com","1373","26-08-20=
25 09:07:05","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005765525","Men=
dong NB","","26-08-2025 09:06:35","26-08-2025 09:03:31","26-08-2025 20:01:0=
3","Grid Only, No space to deploy MDG//Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid Only, No space to depl=
oy MDG//Grid return","loic.noumsi@matech-cameroun.com","185","26-08-2025 09=
:06:35","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005765443","D=
amas","","26-08-2025 09:02:21","26-08-2025 08:52:28","26-08-2025 09:21:26",=
"Site impacted by Nsymeyon /T0351/IHS_YND_146 	(Grid outage, Gen stopped du=
e to High temp, // Door opened the generator has cooled down and Gen card r=
eset and Gen start manually)","MINKA NICOLAS","Equipment Repair","Passive",=
"ACDG Gen","Gen Temp High","	Grid outage, Gen stopped due to High temp, // =
Door opened the generator has cooled down and Gen card reset and Gen start =
manually","vanel.mbiada@matech-cameroun.com","594","26-08-2025 09:02:21","M=
ATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005765300","Nsi=
meyong","IHS_YND_698, IHS_YND_520, IHS_YND_257, IHS_YND_767, IHS_YND_150, I=
HS_YND_282, IHS_YND_260, IHS_YND_261, IHS_YND_518, IHS_YND_737, IHS_YND_768=
, IHS_YND_696, IHS_YND_313, IHS_YND_537, IHS_YND_771, IHS_YND_147","26-08-2=
025 08:45:19","26-08-2025 08:44:14","26-08-2025 09:23:32","Grid outage, Gen=
 stopped due to High temp, // Door opened the generator has cooled down and=
 Gen card reset and Gen start manually","MINKA NICOLAS","Equipment Repair",=
"Passive","ACDG Gen","Gen Temp High","Grid outage, Gen stopped due to High =
temp, // Door opened the generator has cooled down and Gen card reset and G=
en start manually","loic.noumsi@matech-cameroun.com","65","26-08-2025 08:45=
:19","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005765249","Elo=
umdem stade","","26-08-2025 08:33:11","26-08-2025 08:05:57","26-08-2025 09:=
09:15","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, site went down because Gen failed to start due to=
 fuel filter issue // He fixed it, site on GEN","loic.noumsi@matech-camerou=
n.com","1765","26-08-2025 08:33:11","MATECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0005765227","ODZ=
A CITE MBIA","","26-08-2025 08:27:10","26-08-2025 08:20:04","26-08-2025 08:=
52:29","Grid outage, Gen failed to start due Alarm oil pressure // Gen card=
 reset and Gen start manually","Albran Byorel","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage, Gen failed to start due Al=
arm oil pressure // Gen card reset and Gen start manually","loic.noumsi@mat=
ech-cameroun.com","427","26-08-2025 08:27:10","MATECH CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0005765139","Sim=
bock MTN","IHS_YND_793","26-08-2025 08:11:03","26-08-2025 08:05:57","26-08-=
2025 09:09:15","Grid outage, site went down because Gen failed to start due=
 to fuel filter issue // He fixed it, site on GEN","Fanda Brice","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Fuel Filter","Grid outage, site went =
down because Gen failed to start due to fuel filter issue // He fixed it, s=
ite on GEN","loic.noumsi@matech-cameroun.com","307","26-08-2025 08:11:03","=
MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005765037","MBA=
LNGONG LYCEE","","26-08-2025 07:42:34","26-08-2025 07:41:30","26-08-2025 07=
:42:26","Active//No power Issue Site on Grid Ubai =3D53.8V, The FME The TX =
FME Fulbert(654266068)   is informed.","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power Issue Site on Grid Ubai =3D53.8V, The FME The TX FME Fulbert(6542660=
68)   is informed.","loic.noumsi@matech-cameroun.com","66","26-08-2025 07:4=
2:34","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005764907","Mok=
olo Yaounde","","26-08-2025 07:22:28","26-08-2025 07:19:23","26-08-2025 07:=
21:18","	Active // No power issue Ubaie: 54.7 V site on grid. TX FME Brice =
Tsague (650214096) from HUAWEI is informed","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","	Active // No po=
wer issue Ubaie: 54.7 V site on grid. TX FME Brice Tsague (650214096) from =
HUAWEI is informed","loic.noumsi@matech-cameroun.com","187","26-08-2025 07:=
22:28","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005764840","SIM=
BOCK BONAMBAPE","","26-08-2025 07:08:22","26-08-2025 07:03:08","26-08-2025 =
09:23:32","Grid outage, Site went down before Gen start due to poor backup/=
 // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup/ // Gen start automatically","loic.noum=
si@matech-cameroun.com","316","26-08-2025 07:08:22","MATECH CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0005764783","Nko=
lfon Cimencam","","26-08-2025 06:56:44","26-08-2025 06:53:37","26-08-2025 0=
7:00:55","Grid outage, Site went down before Gen start due to poor backup//=
Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup//Grid return","loic.noumsi@matech-cameroun.com","188","=
26-08-2025 06:56:44","MATECH CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0005764757","Aha=
la","","26-08-2025 06:51:35","26-08-2025 06:48:30","26-08-2025 09:23:32","A=
ctive// No power isssue on site Ubaie 54.3 V site on Grid,","Hyemafo Gildas=
","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid outa=
ge, Gen stopped due to High temp, // Door opened the generator has cooled d=
own and Gen card reset and Gen start manually","loic.noumsi@matech-cameroun=
.com","187","26-08-2025 06:51:35","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005764644","Bar=
riere","","26-08-2025 06:31:01","26-08-2025 05:53:03","26-08-2025 09:23:32"=
,"Site up, awaiting feedback","Hyemafo Gildas","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to High te=
mp, // Door opened the generator has cooled down and Gen card reset and Gen=
 start manually","franck.nkomot@matech-cameroun.com","30245","26-08-2025 06=
:31:01","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005764522","Nsi=
meyong","IHS_YND_261","26-08-2025 05:56:19","26-08-2025 05:53:03","26-08-20=
25 06:40:03","Grid outage, Gen stopped due to High temp, // Door opened the=
 generator has cooled down and Gen card reset and Gen start manually","MINK=
A NICOLAS","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid ou=
tage, Gen stopped due to High temp, // Door opened the generator has cooled=
 down and Gen card reset and Gen start manually","franck.nkomot@matech-came=
roun.com","197","26-08-2025 05:56:19","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005764332","Ona=
ngondi (melen bikop)","","26-08-2025 04:37:06","26-08-2025 04:34:55","26-08=
-2025 04:54:55","Grid outage,Site went down because Gen failed to start due=
 to relay starter faulty//Grid return","Fanda Brice","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Kick Starter","Grid outage,Site went down because=
 Gen failed to start due to relay starter faulty//Grid return","franck.nkom=
ot@matech-cameroun.com","132","26-08-2025 04:37:06","MATECH CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0005764301","M=
balla 4","","26-08-2025 04:24:47","26-08-2025 04:20:31","26-08-2025 05:31:3=
1","Grid outage site went down because Gen failed to start due PWC ZTE  dys=
function // He reset the PWC and Gen manually started","Delor Telezing","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid o=
utage site went down because Gen failed to start due PWC ZTE  dysfunction /=
/ He reset the PWC and Gen manually started","franck.nkomot@matech-cameroun=
.com","257","26-08-2025 04:24:47","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005764156","N=
kolbong","","26-08-2025 03:37:13","26-08-2025 03:34:06","26-08-2025 04:44:0=
6","Grid outage. Gen failed to start due to priming pump faulty//Grid retur=
n on site","Delor Telezing","Fuel Outage (Probable)","Passive","ACDG Gen","=
ACDG - Injector Pump","Grid outage. Gen failed to start due to priming pump=
 faulty//Grid return on site","franck.nkomot@matech-cameroun.com","189","26=
-08-2025 03:37:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0005764097","Boga-Mah=
ole","","26-08-2025 03:05:00","26-08-2025 02:04:21","26-08-2025 04:11:52","=
Cascaded Incident from TTO5973978","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because the CB(63A=
) of PWC faulty due to load increased // He replaced the Cb(63A) by a CB(80=
A)","alexandre.kamal@ihstowers.com","3639","26-08-2025 03:05:00","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0005764094","Eseka OC=
M","","26-08-2025 03:04:59","26-08-2025 02:04:21","26-08-2025 04:11:52","Ca=
scaded Incident from TTO5973978","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because the CB(63A) =
of PWC faulty due to load increased // He replaced the Cb(63A) by a CB(80A)=
","alexandre.kamal@ihstowers.com","3638","26-08-2025 03:04:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0005764096","Mamb",""=
,"26-08-2025 03:04:59","26-08-2025 02:04:21","26-08-2025 04:11:52","Cascade=
d Incident from TTO5973978","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down because the CB(63A) of PW=
C faulty due to load increased // He replaced the Cb(63A) by a CB(80A)","al=
exandre.kamal@ihstowers.com","3638","26-08-2025 03:04:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005764095","Song-bon=
g","","26-08-2025 03:04:59","26-08-2025 02:04:21","26-08-2025 04:11:52","Ca=
scaded Incident from TTO5973978","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because the CB(63A) =
of PWC faulty due to load increased // He replaced the Cb(63A) by a CB(80A)=
","alexandre.kamal@ihstowers.com","3638","26-08-2025 03:04:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0005764093","Boumnyeb=
el","","26-08-2025 03:04:59","26-08-2025 02:04:21","26-08-2025 04:11:52","C=
ascaded Incident from TTO5973978","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because the CB(63A)=
 of PWC faulty due to load increased // He replaced the Cb(63A) by a CB(80A=
)","alexandre.kamal@ihstowers.com","3638","26-08-2025 03:04:59","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005764089","Eseka To=
wn","","26-08-2025 03:04:58","26-08-2025 02:04:21","26-08-2025 04:11:52","C=
ascaded Incident from TTO5973978","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because the CB(63A)=
 of PWC faulty due to load increased // He replaced the Cb(63A) by a CB(80A=
)","alexandre.kamal@ihstowers.com","3637","26-08-2025 03:04:58","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0005764092","Ngog Map=
ubi","","26-08-2025 03:04:58","26-08-2025 02:04:21","26-08-2025 04:11:52","=
Cascaded Incident from TTO5973978","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because the CB(63A=
) of PWC faulty due to load increased // He replaced the Cb(63A) by a CB(80=
A)","alexandre.kamal@ihstowers.com","3637","26-08-2025 03:04:58","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0005764090","Ndogbess=
ol","","26-08-2025 03:04:58","26-08-2025 02:04:21","26-08-2025 04:11:52","C=
ascaded Incident from TTO5973978","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because the CB(63A)=
 of PWC faulty due to load increased // He replaced the Cb(63A) by a CB(80A=
)","alexandre.kamal@ihstowers.com","3637","26-08-2025 03:04:58","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0005764088","Boumnyeb=
el OCM","","26-08-2025 03:04:57","26-08-2025 02:04:21","26-08-2025 04:11:52=
","Cascaded Incident from TTO5973978","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down because the CB(=
63A) of PWC faulty due to load increased // He replaced the Cb(63A) by a CB=
(80A)","alexandre.kamal@ihstowers.com","3636","26-08-2025 03:04:57","MATECH=
 CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005763908","Par=
adis Hotel","","26-08-2025 01:48:55","26-08-2025 01:46:40","26-08-2025 01:5=
0:40","Grid Outage, site went down because Gen Overload (12.5Kva, 100A) SS =
IHS BLAISE RAOUL confirmed//Grid return","Siligap Boris","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid Outage, site went down becaus=
e Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL confirmed//Grid return",=
"franck.nkomot@matech-cameroun.com","136","26-08-2025 01:48:55","MATECH CMR=
"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005763456","E=
toudi","","25-08-2025 23:25:11","25-08-2025 23:21:59","25-08-2025 23:25:59"=
,"Grid Fluctuation, site went down before Gen start due to poor battery bac=
kup // Grid restoration","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went dow=
n before Gen start due to poor battery backup // Grid restoration","loic.no=
umsi@matech-cameroun.com","193","25-08-2025 23:25:11","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0005763444","A=
battoir","","25-08-2025 23:19:11","25-08-2025 23:16:01","25-08-2025 23:26:0=
1","Grid outage, site went down due to poor backup // Gen started automatic=
ally","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, site went down due to poor backup // =
Gen started automatically","loic.noumsi@matech-cameroun.com","191","25-08-2=
025 23:19:11","MATECH CMR"
"Closed Complete","Site Down","T1557","IHS_YND_313","NOCINC0005763379","Afa=
noya","","25-08-2025 23:00:30","25-08-2025 22:56:58","26-08-2025 01:57:58",=
"No power issue on site , Ubaie=3D54.3V site On Grid The FME TX Samba /6551=
45055/ from Huawei is informed","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site , Ubaie=3D54.3V site On Grid The FME TX Samba /655145055/ from Hua=
wei is informed","loic.noumsi@matech-cameroun.com","213","25-08-2025 23:00:=
30","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005763103","O=
LAMA","","25-08-2025 22:11:21","25-08-2025 22:07:03","25-08-2025 23:30:03",=
"Active // No power issue on site Ubaie: 54.6V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue on site Ubaie: 54.6V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","vanel.mbiada@matech-cameroun.com","260","25-08-2=
025 22:11:21","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0005763089","Nko=
zoa","","25-08-2025 22:07:42","25-08-2025 22:05:34","25-08-2025 22:14:12","=
Site went down due to CB(125A)in PWC that tripped MTN //He rearmed it (Noti=
ced that SS IHS Felix BATEU was on site for work (installation of DC BOX) a=
nd says he is going to normelised it tomorrow)","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue"=
,"Site went down due to CB(125A)in PWC that tripped MTN //He rearmed it (No=
ticed that SS IHS Felix BATEU was on site for work (installation of DC BOX)=
 and says he is going to normelised it tomorrow)","cedric.tiani@matech-came=
roun.com","130","25-08-2025 22:07:42","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005762885","Mai=
son komkana New","","25-08-2025 21:37:47","25-08-2025 21:35:39","25-08-2025=
 22:52:39","Acces issue during the night. Site went down due to insufficien=
cy of rectifiers on site//SITE STABILISED","Mboua Thierry","Access Denial",=
"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Acce=
s issue during the night. Site went down due to insufficiency of rectifiers=
 on site//SITE STABILISED","cedric.tiani@matech-cameroun.com","129","25-08-=
2025 21:37:47","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0005762812","Nko=
zoa","","25-08-2025 21:23:55","25-08-2025 21:19:48","25-08-2025 21:35:50","=
Site went down due to CB(125A)in PWC that tripped MTN //He rearmed it (Noti=
ced that SS IHS Felix BATEU was on site for work (installation of DC BOX) a=
nd says he is going to normelised it tomorrow)","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue"=
,"Site went down due to CB(125A)in PWC that tripped MTN //He rearmed it (No=
ticed that SS IHS Felix BATEU was on site for work (installation of DC BOX)=
 and says he is going to normelised it tomorrow)","cedric.tiani@matech-came=
roun.com","249","25-08-2025 21:23:55","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005762799","Mai=
son komkana New","","25-08-2025 21:19:57","25-08-2025 21:17:49","25-08-2025=
 21:21:56","Site went down due to insufficient rectifiers on site//SITE STA=
BILISED","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficient rectifiers on site//SITE STAB=
ILISED","cedric.tiani@matech-cameroun.com","129","25-08-2025 21:19:57","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005762582","O=
LAMA","","25-08-2025 20:36:36","25-08-2025 20:31:19","25-08-2025 20:43:09",=
"Active // No power issue on site Ubaie: 54.6V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue on site Ubaie: 54.6V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","vanel.mbiada@matech-cameroun.com","319","25-08-2=
025 20:36:36","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005762475","S=
IMBOCK BONAMBAPE","","25-08-2025 20:17:05","25-08-2025 20:12:28","25-08-202=
5 20:17:43","Active//No power issue Ubaie: 54.15V site on Grid.The FME TX M=
bah Hosiah (674007438/699699694) from Huawei is informed.","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue Ubaie: 54.15V site on Grid.The FME TX M=
bah Hosiah (674007438/699699694) from Huawei is informed.","vanel.mbiada@ma=
tech-cameroun.com","278","25-08-2025 20:17:05","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0005762256","Nko=
zoa","","25-08-2025 19:33:34","25-08-2025 19:28:25","25-08-2025 20:50:47","=
Site went down due to CB(125A)in PWC that tripped MTN //He rearmed it (Noti=
ced that  SS IHS Felix BATEU was on site for work (installation of DC BOX) =
and says he is going to normelised it tomorrow)","Fabrice Pouakam","Equipme=
nt Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue=
","Site went down due to CB(125A)in PWC that tripped MTN //He rearmed it (N=
oticed that  SS IHS Felix BATEU was on site for work (installation of DC BO=
X) and says he is going to normelised it tomorrow)","cedric.tiani@matech-ca=
meroun.com","311","25-08-2025 19:33:34","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005762077","Mai=
son komkana New","","25-08-2025 18:52:28","25-08-2025 18:49:20","25-08-2025=
 20:42:20","Site went down due to 01/03 rectifiers faulty //He replaced it =
and site on Gen","Mboua Thierry","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to 01/03 rectifiers faulty //He repla=
ced it and site on Gen","cedric.tiani@matech-cameroun.com","189","25-08-202=
5 18:52:28","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005761742","Fou=
da Quarter","","25-08-2025 17:40:27","25-08-2025 17:35:16","25-08-2025 18:1=
5:24","Grid fluctuation site went down because Gen failed to start due to G=
rid Contactor faulty //Gen manually  started","Delor Telezing","Equipment R=
epair","Passive","Control Panel","ATS-AMF Issue","Grid fluctuation site wen=
t down because Gen failed to start due to Grid Contactor faulty //Gen manua=
lly  started","cedric.tiani@matech-cameroun.com","312","25-08-2025 17:40:27=
","MATECH CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0005761208","H=
-Deputes","","25-08-2025 16:18:29","25-08-2025 16:16:13","25-08-2025 17:29:=
31","Grid Outage, No space to deploy a mobile Gen//Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No=
 space to deploy a mobile Gen//Grid return","vanel.mbiada@matech-cameroun.c=
om","137","25-08-2025 16:18:29","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005761145","M=
eyo","","25-08-2025 16:02:11","25-08-2025 15:59:49","25-08-2025 16:05:07","=
ACTIVE // No power issue Ubaie: 54,3V Site on Grid The Tx Fme Georges /6974=
661814 from huawei is informed","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE // No p=
ower issue Ubaie: 54,3V Site on Grid The Tx Fme Georges /6974661814 from hu=
awei is informed","vanel.mbiada@matech-cameroun.com","143","25-08-2025 16:0=
2:11","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005760453","N=
koabang Ebolmedjock","","25-08-2025 14:33:48","25-08-2025 14:23:59","25-08-=
2025 14:44:53","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Gen. Notice that it is impacted b=
y Nkolmesseng-Abom(CTR-711) Not Manager By IHS","gerard.tchangoue@matech-ca=
meroun.com","591","25-08-2025 14:33:48","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0005760404","Nko=
zoa","","25-08-2025 14:25:27","25-08-2025 14:23:55","25-08-2025 15:00:53","=
Site down because SS IHS Felix BATEU is on site for work (installation of D=
C BOX)//End of work","Fabrice Pouakam","Installation Activity","Passive","P=
lanned Activity","Installation Activity","Site down because SS IHS Felix BA=
TEU is on site for work (installation of DC BOX)//End of work","loic.noumsi=
@matech-cameroun.com","94","25-08-2025 14:25:27","MATECH CMR"
"Closed Complete","Warning","T0341","IHS_YND_270","NOCINC0005760274","Santa=
 Barbara Yde","","25-08-2025 14:14:47","","","Site alarming due to Grid flu=
ctuation // Grid return","Delor Telezing","Warning","Warning","POWER","Warn=
ing - National Grid - Unstable Grid Supply Issue","Site alarming due to Gri=
d fluctuation // Grid return","loic.noumsi@matech-cameroun.com","2","25-08-=
2025 14:14:47","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005760124","N=
koabang Ebolmedjock","","25-08-2025 13:45:06","25-08-2025 13:35:56","25-08-=
2025 13:46:35","	Site impacted by Nkolmesseng-Abom(CTR-711) Not Manager By =
IHS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","	Site impacted by Nkolmesseng-Abom(CTR-=
711) Not Manager By IHS","gerard.tchangoue@matech-cameroun.com","552","25-0=
8-2025 13:45:06","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005760069","Ona=
ngondi (melen bikop)","","25-08-2025 13:36:32","25-08-2025 13:34:27","25-08=
-2025 13:53:58","hybrid gen site. Site went down due to automation malfunct=
ioning//Gen manually started","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","hybrid gen site. Site went down due to aut=
omation malfunctioning//Gen manually started","loic.noumsi@matech-cameroun.=
com","127","25-08-2025 13:36:32","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005759440","N=
koabang2","","25-08-2025 11:49:42","25-08-2025 11:46:32","25-08-2025 12:00:=
27","Grid fluctuations, site went down due to gen overload (22KVA, 330A), S=
S Blaise IHS is informed // Grid stabilised","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, site wen=
t down due to gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid=
 stabilised","gerard.tchangoue@matech-cameroun.com","192","25-08-2025 11:49=
:42","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0005759348","Tsi=
nga village","","25-08-2025 11:40:00","25-08-2025 11:39:58","25-08-2025 12:=
00:04","Site went down because Gen failed to start due to Grid bad voltage =
(RCP faulty) // he bypass the Grid and Gen manually started","Delor Telezin=
g","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Site went down because Gen failed to start due to Grid bad voltage (RCP f=
aulty) // he bypass the Grid and Gen manually started","loic.noumsi@matech-=
cameroun.com","3","25-08-2025 11:40:00","MATECH CMR"
"Closed Complete","Warning","T1613","IHS_YND_301","NOCINC0005759033","Tsing=
a village","","25-08-2025 10:40:30","","","Site went down because Gen faile=
d to start due to Grid bad voltage (RCP faulty) // he bypass the Grid and G=
en manually started","Delor Telezing","Warning","Warning","POWER","Warning =
- National Grid - Grid Incomplete Phase","Site went down because Gen failed=
 to start due to Grid bad voltage (RCP faulty) // he bypass the Grid and Ge=
n manually started","loic.noumsi@matech-cameroun.com","3","25-08-2025 10:40=
:30","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005758998","M=
ambine","","25-08-2025 10:31:16","25-08-2025 10:23:08","25-08-2025 10:43:35=
","Grid outage, Site went down because Gen failed to start due Air-intake",=
"Fanda Brice","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Air Int=
ake","Grid outage, Site went down because Gen failed to start due Air-intak=
e","gerard.tchangoue@matech-cameroun.com","490","25-08-2025 10:31:16","MATE=
CH CMR"
"Closed Complete","Warning","T0139","IHS_YND_381","NOCINC0005758514","Boumn=
yebel","","25-08-2025 09:01:22","","","Site went in alarm due to rectifier =
issue // He reset it, site on Grid","Kemeni Franklin","Warning","Warning","=
POWER","Warning - Rectifier Module","Site went in alarm due to rectifier is=
sue // He reset it, site on Grid","loic.noumsi@matech-cameroun.com","2","25=
-08-2025 09:01:22","MATECH CMR"
"Closed Complete","Warning","T1573","IHS_YND_378","NOCINC0005758507","Eseka=
 Town","","25-08-2025 08:59:01","","","Site alarming due to Grid outage // =
Gen start manually","Kemeni Franklin","Warning","Warning","POWER","Warning =
- National Grid - Grid Outage Issue","Site alarming due to Grid outage // G=
en start manually","loic.noumsi@matech-cameroun.com","5","25-08-2025 08:59:=
01","MATECH CMR"
"Closed Complete","Site Down","T0139","IHS_YND_381","NOCINC0005758500","Bou=
mnyebel","","25-08-2025 08:56:36","25-08-2025 08:56:34","25-08-2025 08:57:1=
1","error ticket","Kemeni Franklin","Incorrectly Logged Tickets","Error","E=
rror","Error","error ticket","loic.noumsi@matech-cameroun.com","4","25-08-2=
025 08:56:36","MATECH CMR"
"Closed Complete","Site Down","T0920","IHS_YND_416","NOCINC0005758172","Ngw=
opi Boga","","25-08-2025 07:41:47","25-08-2025 07:40:41","25-08-2025 10:42:=
16","No power issue, site is on grid with Ubaie=3D54.9V; TX FME Etienne Fop=
a (693961474) from HUAWEI is informed","Kemeni Franklin","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue, site is on grid with Ubaie=3D54.9V; TX FME Etienne Fopa (69396147=
4) from HUAWEI is informed","loic.noumsi@matech-cameroun.com","67","25-08-2=
025 07:41:47","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005757795","L=
abogenie","IHS_YND_568","25-08-2025 06:00:53","25-08-2025 05:54:33","25-08-=
2025 06:07:43","Active // No power issue U =3D54,6V site on Grid. The Tx FM=
E Eloundou (693212405 )from Huawei is informed.","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue U =3D54,6V site on Grid. The Tx FME Eloundou (693212405 )from=
 Huawei is informed.","gerard.tchangoue@matech-cameroun.com","382","25-08-2=
025 06:00:53","MATECH CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0005757783","A=
nguissa New","","25-08-2025 05:57:09","25-08-2025 05:54:33","25-08-2025 06:=
07:43","Site impacted by Labogenie","MINKA NICOLAS","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active // No power issue U =3D54,6V s=
ite on Grid. The Tx FME Eloundou (693212405 )from Huawei is informed.","ger=
ard.tchangoue@matech-cameroun.com","443","25-08-2025 05:57:09","MATECH CMR"
"Closed Complete","Warning","CTR_213","IHS_YND_247","NOCINC0005757380","Oko=
lo","","25-08-2025 01:29:31","","","Site went down because Gen started and =
stopped due to  Gen CB tripped / He rearmed Gen  CB (investigation ongoing)=
","Fabrice Pouakam","Warning","Warning","POWER","Warning - Site on Battery"=
,"Site went down because Gen started and stopped due to  Gen CB tripped / H=
e rearmed Gen  CB (investigation ongoing)","edwige.kapawo@matech-cameroun.c=
om","11","25-08-2025 01:29:31","MATECH CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0005756793","M=
asque","","24-08-2025 22:35:05","24-08-2025 22:32:48","25-08-2025 00:33:57"=
," No power issue on site. Site on Gen with Ubaie=3D49.9V The TX FME Elound=
ou // 693212405// From Huawei is informed.","Fabrice Pouakam","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," =
No power issue on site. Site on Gen with Ubaie=3D49.9V The TX FME Eloundou =
// 693212405// From Huawei is informed.","gerard.tchangoue@matech-cameroun.=
com","139","24-08-2025 22:35:05","MATECH CMR"
"Closed Complete","Site Down","T1832","IHS_YND_216","NOCINC0005755699","Ele=
veur","","24-08-2025 18:39:49","24-08-2025 18:30:59","24-08-2025 18:31:59",=
"no power issue on site U=3D50.5V site on Grid THE TX FME SYMPHORIEN (65025=
7151) from HUAWEI is informed","Siligap Boris","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue o=
n site U=3D50.5V site on Grid THE TX FME SYMPHORIEN (650257151) from HUAWEI=
 is informed","franck.nkomot@matech-cameroun.com","531","24-08-2025 18:39:4=
9","MATECH CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0005755491","N=
sam Sofavinc T0","","24-08-2025 17:49:36","24-08-2025 17:46:29","24-08-2025=
 18:29:21","Site went down because gen start an stopped due to water infilt=
ration in tank // He purged The tank and Gen manually started","MINKA NICOL=
AS","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water=
 In The Fuel","Site went down because gen start an stopped due to water inf=
iltration in tank // He purged The tank and Gen manually started","gerard.t=
changoue@matech-cameroun.com","188","24-08-2025 17:49:36","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005753218","Nsa=
m Sofavinc","","24-08-2025 09:18:14","24-08-2025 09:12:52","24-08-2025 09:1=
8:30","Grid outage, Site went down before Gen start due to poor backup/ // =
Gen automatically started","MINKA NICOLAS","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup/ // Gen automatically started","vanel.mbia=
da@matech-cameroun.com","323","24-08-2025 09:18:14","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005753200","SIM=
BOCK BONAMBAPE","","24-08-2025 09:15:47","24-08-2025 09:12:39","24-08-2025 =
09:16:08","	Site went down because Gen overload(20KVA//300A )SS HIS Felix B=
ateu is informed // Grid return","Hyemafo Gildas","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","	Site went down because Gen overload(20KV=
A//300A )SS HIS Felix Bateu is informed // Grid return","vanel.mbiada@matec=
h-cameroun.com","190","24-08-2025 09:15:47","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005752412","Ona=
ngondi (melen bikop)","","24-08-2025 06:10:50","24-08-2025 06:07:30","24-08=
-2025 06:31:54","site went down because gen start an stopped due to water i=
nfiltration in tank // He purged The tank and Gen manually started","Fanda =
Brice","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Wa=
ter In The Fuel","site went down because gen start an stopped due to water =
infiltration in tank // He purged The tank and Gen manually started","gerar=
d.tchangoue@matech-cameroun.com","202","24-08-2025 06:10:50","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005752363","N=
kozoa","","24-08-2025 05:55:50","24-08-2025 05:52:43","24-08-2025 06:27:38"=
,"Grid outage, site went down because gen failed to start due to PWC malfun=
ction // He reset controller and gen manually started","Fabrice Pouakam","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage, site went down because gen failed to start due to PWC malfunction /=
/ He reset controller and gen manually started","gerard.tchangoue@matech-ca=
meroun.com","190","24-08-2025 05:55:50","MATECH CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0005751790","San=
ta Barbara Yde","IHS_YND_743, IHS_YND_301, IHS_YND_745, IHS_YND_277, IHS_YN=
D_275, IHS_YND_242, IHS_YND_740","24-08-2025 00:55:12","24-08-2025 00:52:02=
","24-08-2025 01:13:01","site went down because Gen failed to start due to =
Grid bad voltage ( RCP faulty) // Grid bypassed and gen manually started","=
Delor Telezing","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","site went down because Gen failed to start due to Grid bad v=
oltage ( RCP faulty) // Grid bypassed and gen manually started","gerard.tch=
angoue@matech-cameroun.com","191","24-08-2025 00:55:12","MATECH CMR"
"Closed Complete","Warning","T0341","IHS_YND_270","NOCINC0005751729","Santa=
 Barbara Yde","","24-08-2025 00:24:16","","","site went down because Gen fa=
iled to start due to Grid bad voltage ( RCP faulty) // Grid bypassed and ge=
n manually started","Delor Telezing","Warning","Warning","POWER","Warning -=
 National Grid - Grid Incomplete Phase","site went down because Gen failed =
to start due to Grid bad voltage ( RCP faulty) // Grid bypassed and gen man=
ually started","gerard.tchangoue@matech-cameroun.com","499","24-08-2025 00:=
24:16","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0005750946","Nko=
zoa","","23-08-2025 20:49:26","23-08-2025 20:47:16","23-08-2025 20:54:16","=
Grid outage, site went down due to Gen overload(30kva,350 A) SS Felix MBATE=
U Confirmed // We reduced load, site stabilized","Fabrice Pouakam","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went d=
own due to Gen overload(30kva,350 A) SS Felix MBATEU Confirmed // We reduce=
d load, site stabilized","franck.nkomot@matech-cameroun.com","132","23-08-2=
025 20:49:26","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0005750730","Nko=
zoa","","23-08-2025 19:49:50","23-08-2025 19:42:41","23-08-2025 20:41:41","=
Grid outage, site went down due to Gen overload(30kva,350 A) SS Felix MBATE=
U Confirmed // We reduced load, site stabilized","Fabrice Pouakam","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went d=
own due to Gen overload(30kva,350 A) SS Felix MBATEU Confirmed // We reduce=
d load, site stabilized","franck.nkomot@matech-cameroun.com","484","23-08-2=
025 19:49:50","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005750368","N=
kozoa","","23-08-2025 18:56:49","23-08-2025 18:53:33","23-08-2025 19:17:33"=
,"Grid outage, site went down due to Gen overload(30kva,350 A) SS Felix MBA=
TEU Confirmed // We reduced load, site stabilized","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went=
 down due to Gen overload(30kva,350 A) SS Felix MBATEU Confirmed // We redu=
ced load, site stabilized","vanel.mbiada@matech-cameroun.com","198","23-08-=
2025 18:56:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005749790","MBIMBIM"=
,"","23-08-2025 17:06:11","23-08-2025 16:45:59","23-08-2025 18:49:33","Casc=
aded Incident from TTO5958119","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Starter fuse cut // FME bypassed fuse a=
nd started GEN manually","olivier.kwedi@ihstowers.com","1212","23-08-2025 1=
7:06:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005749788","Yoko OCM=
","","23-08-2025 17:06:11","23-08-2025 16:45:59","23-08-2025 18:49:33","Cas=
caded Incident from TTO5958119","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Starter fuse cut // FME bypassed fuse =
and started GEN manually","olivier.kwedi@ihstowers.com","1212","23-08-2025 =
17:06:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005749787","Matsari"=
,"","23-08-2025 17:06:10","23-08-2025 16:45:59","23-08-2025 18:49:33","Casc=
aded Incident from TTO5958119","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Starter fuse cut // FME bypassed fuse a=
nd started GEN manually","olivier.kwedi@ihstowers.com","1211","23-08-2025 1=
7:06:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005749786","Ngoum","=
","23-08-2025 17:06:10","23-08-2025 16:45:59","23-08-2025 18:49:33","Cascad=
ed Incident from TTO5958119","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Starter fuse cut // FME bypassed fuse and=
 started GEN manually","olivier.kwedi@ihstowers.com","1211","23-08-2025 17:=
06:10","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005749384","Crf=
-Mbankolo-IHS","","23-08-2025 15:43:11","23-08-2025 15:38:01","23-08-2025 1=
6:43:00","No power issue, site is on Grid with Ubaie=3D51,11V, TX Brice Tsa=
gue (650214096) from Huawei is informed","Mboua Thierry","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue, site is on Grid with Ubaie=3D51,11V, TX Brice Tsague (650214096) =
from Huawei is informed","franck.nkomot@matech-cameroun.com","312","23-08-2=
025 15:43:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005749260","Melen Ba=
'aba","","23-08-2025 15:17:06","23-08-2025 15:12:39","23-08-2025 15:44:51",=
"","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage, site down due to gen overload 300 A /20 KVA // Gen cha=
rge reduced and Gen manually started","franck.nkomot@matech-cameroun.com","=
786","23-08-2025 15:17:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005749261","TSINGA V=
ILLAGE 2","","23-08-2025 15:17:06","23-08-2025 15:12:39","23-08-2025 15:44:=
51","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, site down due to gen overload 300 A /20 KVA // Ge=
n charge reduced and Gen manually started","franck.nkomot@matech-cameroun.c=
om","764","23-08-2025 15:17:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005749259","Nkolfoul=
ou 2","","23-08-2025 15:17:05","23-08-2025 15:12:39","23-08-2025 15:44:51",=
"","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage, site down due to gen overload 300 A /20 KVA // Gen cha=
rge reduced and Gen manually started","franck.nkomot@matech-cameroun.com","=
809","23-08-2025 15:17:05","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0005749244","Nko=
lfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","23-08-2025 15:14:47","23-=
08-2025 15:12:39","23-08-2025 15:46:39","Grid outage, site down due to gen =
overload 300 A /20 KVA // Gen charge reduced and Gen manually started","Sil=
igap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, site down due to gen overload 300 A /20 KVA // Gen charge reduced =
and Gen manually started","franck.nkomot@matech-cameroun.com","129","23-08-=
2025 15:14:47","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005749184","S=
IMBOCK BONAMBAPE","","23-08-2025 15:01:02","23-08-2025 14:58:27","23-08-202=
5 15:04:27","Site went down because Gen overload(20KVA//300A )SS HIS Felix =
Bateu is informed // Grid return","Hyemafo Gildas","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Site went down because Gen overload(20KV=
A//300A )SS HIS Felix Bateu is informed // Grid return","vanel.mbiada@matec=
h-cameroun.com","157","23-08-2025 15:01:02","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005748966","Ona=
ngondi (melen bikop)","","23-08-2025 14:37:59","23-08-2025 14:30:20","23-08=
-2025 15:24:20","Grid outage, site went down because gen ran until fuel sho=
rtage // He tilted the tank (Refueling ongoing)","Fanda Brice","Fuel Outage=
","Passive","Diesel","Diesel Outage","Grid outage, site went down because g=
en ran until fuel shortage // He tilted the tank (Refueling ongoing)","fran=
ck.nkomot@matech-cameroun.com","460","23-08-2025 14:37:59","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005748770","Eto=
ug ebe Carrefour","","23-08-2025 14:15:10","23-08-2025 14:10:02","23-08-202=
5 14:28:02","Grid outage site went down before gen started due to poor batt=
ery backup// Grid returned","Hyemafo Gildas","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage site went down be=
fore gen started due to poor battery backup// Grid returned","edwige.kapawo=
@matech-cameroun.com","309","23-08-2025 14:15:10","MATECH CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0005748741","M=
volye-New","","23-08-2025 14:07:31","23-08-2025 14:03:20","23-08-2025 14:13=
:07","Active// No power Issue Site on Grid Ubaie =3D51.8V, The TX FME Mbah =
Hosiah (674007438) is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site=
 on Grid Ubaie =3D51.8V, The TX FME Mbah Hosiah (674007438) is informed","v=
anel.mbiada@matech-cameroun.com","253","23-08-2025 14:07:31","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005748519","Ona=
ngondi (melen bikop)","","23-08-2025 13:44:32","23-08-2025 13:42:21","23-08=
-2025 14:08:50","Grid outage, site went down because gen ran until fuel sho=
rtage // He tilted the tank (Refueling ongoing)","Fanda Brice","Fuel Outage=
","Passive","Diesel","Diesel Outage","Grid outage, site went down because g=
en ran until fuel shortage // He tilted the tank (Refueling ongoing)","edwi=
ge.kapawo@matech-cameroun.com","132","23-08-2025 13:44:32","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005748273","N=
koabang2","","23-08-2025 13:07:51","23-08-2025 13:04:21","23-08-2025 13:37:=
59","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed// Grid return","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen=
 overload (22KVA, 330A), SS Blaise IHS is informed// Grid return","vanel.mb=
iada@matech-cameroun.com","212","23-08-2025 13:07:51","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005748200","A=
fanoya","","23-08-2025 12:48:33","23-08-2025 12:45:18","23-08-2025 12:47:33=
","Grid outage , site went down before Gen started due to poor battery back=
up// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage , site went down before Gen=
 started due to poor battery backup// Grid return","vanel.mbiada@matech-cam=
eroun.com","197","23-08-2025 12:48:33","MATECH CMR"
"Closed Complete","Site Down","CTR_122","IHS_YND_230","NOCINC0005748128","M=
eyong-Meyeme","","23-08-2025 12:30:48","23-08-2025 12:17:22","23-08-2025 12=
:20:35","Active//No power issue site is on Gen with Ubaie=3D53,89V. TX FME =
Mohamadou // 699949072 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active//No power issue site is on Gen with Ubaie=3D53,89V. TX F=
ME Mohamadou // 699949072 from Huawei is informed","vanel.mbiada@matech-cam=
eroun.com","807","23-08-2025 12:30:48","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005747930","Sim=
e Building","","23-08-2025 11:42:59","23-08-2025 11:36:53","23-08-2025 11:4=
2:23","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","edwige.kapaw=
o@matech-cameroun.com","367","23-08-2025 11:42:59","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005747798","T=
SINGA VILLAGE 2","","23-08-2025 11:16:23","23-08-2025 11:14:04","23-08-2025=
 11:22:41","No power issue on site Ubaie=3D51,4V site on Grid. The Tx FME A=
rmand Ngetsa //691144412 from Huawei is informed","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Ubaie=3D51,4V site on Grid. The Tx FME Armand Ng=
etsa //691144412 from Huawei is informed","vanel.mbiada@matech-cameroun.com=
","141","23-08-2025 11:16:23","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005747727","C=
NR","","23-08-2025 11:01:06","23-08-2025 10:56:44","23-08-2025 11:39:35","S=
ite went down because gen failed to start due to grid bad voltage and no RC=
P // Grid stabilized","Mboua Thierry","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","Site went down because gen failed to s=
tart due to grid bad voltage and no RCP // Grid stabilized","vanel.mbiada@m=
atech-cameroun.com","263","23-08-2025 11:01:06","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005747721","Sim=
e Building","","23-08-2025 10:59:36","23-08-2025 10:56:28","23-08-2025 11:0=
2:50","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","edwige.kapaw=
o@matech-cameroun.com","189","23-08-2025 10:59:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005747371","MBIMBIM"=
,"","23-08-2025 09:58:37","23-08-2025 09:53:01","23-08-2025 09:54:01","Casc=
aded Incident from TTO5955470","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid Gen, Hybrid system malfunction /=
/ Hybrid module reset and Gen started","vanel.mbiada@matech-cameroun.com","=
2172","23-08-2025 09:58:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005747368","Ngoum","=
","23-08-2025 09:58:36","23-08-2025 09:53:01","23-08-2025 09:54:01","Cascad=
ed Incident from TTO5955470","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Hybrid Gen, Hybrid system malfunction // =
Hybrid module reset and Gen started","vanel.mbiada@matech-cameroun.com","22=
43","23-08-2025 09:58:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005747370","Ngouetou=
","","23-08-2025 09:58:36","23-08-2025 09:53:01","23-08-2025 09:54:01","Cas=
caded Incident from TTO5955470","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen, Hybrid system malfunction =
// Hybrid module reset and Gen started","vanel.mbiada@matech-cameroun.com",=
"2266","23-08-2025 09:58:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005747369","Yoko OCM=
","","23-08-2025 09:58:36","23-08-2025 09:53:01","23-08-2025 09:54:01","Cas=
caded Incident from TTO5955470","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen, Hybrid system malfunction =
// Hybrid module reset and Gen started","vanel.mbiada@matech-cameroun.com",=
"2214","23-08-2025 09:58:36","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005747361","M=
atsari","","23-08-2025 09:57:02","23-08-2025 09:53:01","23-08-2025 09:54:01=
","FME parker is informed he is conducting investigations","Parker Tchoup",=
"Cascade Outage","Passive","Cascade Passive","Cascade Passive","Hybrid Gen,=
 Hybrid system malfunction // Hybrid module reset and Gen started","vanel.m=
biada@matech-cameroun.com","2043","23-08-2025 09:57:02","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005747308","E=
mombo","","23-08-2025 09:45:31","23-08-2025 09:32:23","23-08-2025 09:35:36"=
,"site went down due to CB of battery backup down)//We rearmed the CB","Mba=
 Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Circuit Breaker Issue","site went down due to CB of battery backup down)/=
/We rearmed the CB","vanel.mbiada@matech-cameroun.com","789","23-08-2025 09=
:45:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0005747257","Kondengu=
i","","23-08-2025 09:34:14","23-08-2025 09:30:25","23-08-2025 21:37:25","Ca=
scaded Incident from TTO5955352","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, no space to deploy MGE /=
/ grid power return","vanel.mbiada@matech-cameroun.com","229","23-08-2025 0=
9:34:14","MATECH CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0005747251","E=
mombo-Tchad","IHS_YND_114","23-08-2025 09:32:38","23-08-2025 09:30:25","23-=
08-2025 21:37:25","Grid outage, no space to deploy MGE // grid power return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage, no space to deploy MGE // grid power return","vanel.mbiada@matec=
h-cameroun.com","134","23-08-2025 09:32:38","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005747243","E=
mombo","","23-08-2025 09:29:43","23-08-2025 09:26:04","23-08-2025 09:31:37"=
,"ACTIVE No power issue site on Grid U=3D 54,9V site on Grid the TX FME Lio=
nel /694693436 from huawei is inform","Mba Lazare Herve","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE=
 No power issue site on Grid U=3D 54,9V site on Grid the TX FME Lionel /694=
693436 from huawei is inform","vanel.mbiada@matech-cameroun.com","220","23-=
08-2025 09:29:43","MATECH CMR"
"Resolved","Warning","T0183","IHS_YND_184","NOCINC0005747206","Nkolmesseng"=
,"","23-08-2025 09:15:51","","","Dg start and stop due to grid bad voltages=
 // grid stabilized","Siligap Boris","Warning","Warning","POWER","Warning -=
 AC Phase 1 Current Low","Dg start and stop due to grid bad voltages // gri=
d stabilized","vanel.mbiada@matech-cameroun.com","7","23-08-2025 09:15:51",=
"MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005746761","Cit=
e des nations","","23-08-2025 07:25:52","23-08-2025 07:22:47","23-08-2025 0=
7:28:22","Grid fluctuations, site went down before Gen started due to Poor =
battery backup ( Notice that MPR faulty)// Grid stabilised","Paul BIBOUM","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","=
Grid fluctuations, site went down before Gen started due to Poor battery ba=
ckup ( Notice that MPR faulty)// Grid stabilised","edwige.kapawo@matech-cam=
eroun.com","187","23-08-2025 07:25:52","MATECH CMR"
"Closed Complete","Site Down","T0292","IHS_YND_231","NOCINC0005746406","Nko=
lso","","23-08-2025 06:31:36","23-08-2025 06:30:19","23-08-2025 07:42:03","=
FME Gael is on site","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went Down b=
ecauseThe circuit breaker supplying power to the eneo contactor was turned =
off. //He took his power directly from the 48V rail.","loic.noumsi@matech-c=
ameroun.com","78","23-08-2025 06:31:36","MATECH CMR"
"Closed Complete","Warning","T0292","IHS_YND_231","NOCINC0005746332","Nkols=
o","","23-08-2025 06:11:13","","","Grid outage, site went down because gen =
started and stopped due to grid bad voltage // He bypassed Grid and started=
 Gen manually","TIENTCHEU NZETCHIEU GAEL","Warning","Warning","POWER","Warn=
ing - National Grid - Unstable Grid Supply Issue","Grid outage, site went d=
own because gen started and stopped due to grid bad voltage // He bypassed =
Grid and started Gen manually","loic.noumsi@matech-cameroun.com","13","23-0=
8-2025 06:11:13","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005746077","Fla=
menco","","23-08-2025 05:06:23","23-08-2025 05:04:17","23-08-2025 06:34:59"=
,"Grid outage.gen start and stopped due to alarm""high temp""//We added wat=
er and gen manually started","Mboua Thierry","Equipment Repair","Passive","=
ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.gen =
start and stopped due to alarm""high temp""//We added water and gen manuall=
y started","loic.noumsi@matech-cameroun.com","127","23-08-2025 05:06:23","M=
ATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005746032","Cit=
e des nations","","23-08-2025 04:50:33","23-08-2025 04:47:22","23-08-2025 0=
4:53:03","Grid outage, site went down before Gen started due to Poor batter=
y backup // Grid stabilised","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen started due to Poor battery backup // Grid stabilised","loic.noumsi=
@matech-cameroun.com","192","23-08-2025 04:50:33","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005745969","Cit=
e des nations","","23-08-2025 03:59:18","23-08-2025 03:56:12","23-08-2025 0=
4:02:46","Grid outage, site went down before Gen started due to Poor batter=
y backup // Grid stabilised","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen started due to Poor battery backup // Grid stabilised","loic.noumsi=
@matech-cameroun.com","187","23-08-2025 03:59:18","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005745946","Cit=
e des nations","","23-08-2025 03:44:06","23-08-2025 03:39:57","23-08-2025 0=
3:45:17","Grid outage, site went down before Gen started due to Poor batter=
y backup // Grid stabilised","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen started due to Poor battery backup // Grid stabilised","loic.noumsi=
@matech-cameroun.com","250","23-08-2025 03:44:06","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005745875","Cit=
e des nations","","23-08-2025 02:58:36","23-08-2025 02:56:29","23-08-2025 0=
3:02:24","Grid outage, site went down before Gen started due to Poor batter=
y backup // Grid stabilised","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen started due to Poor battery backup // Grid stabilised","loic.noumsi=
@matech-cameroun.com","128","23-08-2025 02:58:36","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005745757","Cit=
e des nations","","23-08-2025 01:45:49","23-08-2025 01:43:40","23-08-2025 0=
1:49:52","Grid outage, site went down before Gen started due to Poor batter=
y backup // Grid stabilised","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen started due to Poor battery backup // Grid stabilised","loic.noumsi=
@matech-cameroun.com","130","23-08-2025 01:45:49","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005745701","Cit=
e des nations","","23-08-2025 01:20:08","23-08-2025 01:16:55","23-08-2025 0=
1:22:52","Grid outage, site went down before Gen started due to Poor batter=
y backup // Grid stabilised","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen started due to Poor battery backup // Grid stabilised","loic.noumsi=
@matech-cameroun.com","195","23-08-2025 01:20:08","MATECH CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0005745628","Lab=
oratoire  Meka","","23-08-2025 00:55:16","23-08-2025 00:52:11","23-08-2025 =
06:38:25","Grid Only, No space to deploy MGE // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No spac=
e to deploy MGE // Grid return","loic.noumsi@matech-cameroun.com","186","23=
-08-2025 00:55:16","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005745626","Cit=
e des nations","","23-08-2025 00:54:30","23-08-2025 00:51:24","23-08-2025 0=
0:57:46","Grid outage, site went down before Gen started due to Poor batter=
y backup // Grid return","Paul BIBOUM","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
Gen started due to Poor battery backup // Grid return","loic.noumsi@matech-=
cameroun.com","187","23-08-2025 00:54:30","MATECH CMR"
"Closed Complete","Site Down","T0107","IHS_YND_271","NOCINC0005745541","Yon=
a Hotel","","23-08-2025 00:08:03","23-08-2025 00:04:37","23-08-2025 00:24:3=
4","site went down due to Grid contactor faulty // Grid baypass and site pu=
t on Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control =
Panel","ATS-AMF Issue","site went down due to Grid contactor faulty // Grid=
 baypass and site put on Gen","loic.noumsi@matech-cameroun.com","207","23-0=
8-2025 00:08:03","MATECH CMR"
"Closed Complete","Warning","T0543","IHS_YND_135","NOCINC0005745447","Nlong=
kak","","22-08-2025 23:34:24","","","Grid-only site, Site alarming due to g=
rid outage // Grid return                                                  =
                                           ","Delor Telezing","Warning","Wa=
rning","POWER","Warning - National Grid - Grid Outage Issue","Grid-only sit=
e, Site alarming due to grid outage // Grid return        ","loic.noumsi@ma=
tech-cameroun.com","18","22-08-2025 23:34:24","MATECH CMR"
"Closed Complete","Site Down","T0107","IHS_YND_271","NOCINC0005745266","Yon=
a Hotel","","22-08-2025 22:46:34","22-08-2025 22:45:27","22-08-2025 22:47:5=
7","Access issue during the Night because it is a school. // Site stabilise=
d","TIENTCHEU NZETCHIEU GAEL","Access Denial","Lease Or Legal","Landlord Re=
lated Issues","Access Issue - Land Lord","Access issue during the Night bec=
ause it is a school. // Site stabilised","loic.noumsi@matech-cameroun.com",=
"68","22-08-2025 22:46:34","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005745183","Cit=
e des nations","","22-08-2025 22:26:45","22-08-2025 22:21:39","22-08-2025 2=
2:27:42","Grid outage, site went down before Gen started due to Poor batter=
y backup // Grid return","Paul BIBOUM","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
Gen started due to Poor battery backup // Grid return","loic.noumsi@matech-=
cameroun.com","307","22-08-2025 22:26:45","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005744714","Nko=
abang Ebolmedjock","","22-08-2025 21:06:56","22-08-2025 21:04:49","22-08-20=
25 21:29:22","Grid outage, site went down because Gen started and stopped d=
ue to High temp alarm // He added water and started Gen manually","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Grid outage, site went down because Gen started and=
 stopped due to High temp alarm // He added water and started Gen manually"=
,"gerard.tchangoue@matech-cameroun.com","181","22-08-2025 21:06:56","MATECH=
 CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005744665","Cit=
e des nations","","22-08-2025 21:01:29","22-08-2025 20:56:08","22-08-2025 2=
1:02:54","Grid outage, site went down before Gen started due to Poor batter=
y backup//Grid return","Paul BIBOUM","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before Ge=
n started due to Poor battery backup//Grid return","franck.nkomot@matech-ca=
meroun.com","322","22-08-2025 21:01:29","MATECH CMR"
"Closed Complete","Site Down","T1085","IHS_YND_130","NOCINC0005744555","Bas=
tos usine","","22-08-2025 20:44:07","22-08-2025 20:39:46","22-08-2025 22:07=
:46","Grid fluctuation, site went down because Gen failed to start due to g=
rid bad voltage // He bypassed Grid and put Site on Gen","Mboua Thierry","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d fluctuation, site went down because Gen failed to start due to grid bad v=
oltage // He bypassed Grid and put Site on Gen","franck.nkomot@matech-camer=
oun.com","261","22-08-2025 20:44:07","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005744478","Nko=
abang Ebolmedjock","","22-08-2025 20:32:10","22-08-2025 20:29:57","22-08-20=
25 20:58:00","Grid outage, site went down because Gen started and stopped d=
ue to High temp alarm // He added water and started Gen manually","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Grid outage, site went down because Gen started and=
 stopped due to High temp alarm // He added water and started Gen manually"=
,"franck.nkomot@matech-cameroun.com","135","22-08-2025 20:32:10","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005744426","Bastos-N=
ylon","","22-08-2025 20:23:51","22-08-2025 20:17:36","23-08-2025 06:27:31",=
"Cascaded Incident from TTO5952237","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Only, No space to deploy MGE =
// Grid return","gerard.tchangoue@matech-cameroun.com","375","22-08-2025 20=
:23:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005744427","Bastos B=
ethesda","","22-08-2025 20:23:51","22-08-2025 20:17:36","23-08-2025 06:27:3=
1","Cascaded Incident from TTO5952237","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Only, No space to deploy M=
GE // Grid return","gerard.tchangoue@matech-cameroun.com","375","22-08-2025=
 20:23:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0005744428","Tsinga",=
"","22-08-2025 20:23:51","22-08-2025 20:17:36","23-08-2025 06:27:31","Casca=
ded Incident from TTO5952237","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid Only, No space to deploy MGE // Gri=
d return","gerard.tchangoue@matech-cameroun.com","375","22-08-2025 20:23:51=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005744424","Golf Qua=
ter","","22-08-2025 20:23:50","22-08-2025 20:17:36","23-08-2025 06:27:31","=
Cascaded Incident from TTO5952237","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Only, No space to deploy MGE /=
/ Grid return","gerard.tchangoue@matech-cameroun.com","374","22-08-2025 20:=
23:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0005744425","Nkomkana=
 2","","22-08-2025 20:23:50","22-08-2025 20:17:36","23-08-2025 06:27:31","C=
ascaded Incident from TTO5952237","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Only, No space to deploy MGE //=
 Grid return","gerard.tchangoue@matech-cameroun.com","374","22-08-2025 20:2=
3:50","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0005744406","N=
komkana","IHS_YND_220, IHS_YND_138, IHS_YND_126, IHS_YND_563, IHS_YND_127",=
"22-08-2025 20:20:45","22-08-2025 20:17:36","23-08-2025 06:29:49","Grid Onl=
y, No space to deploy MGE // Grid return","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid Only, No space to deploy MGE // =
Grid return","gerard.tchangoue@matech-cameroun.com","191","22-08-2025 20:20=
:45","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005744343","Cit=
e des nations","","22-08-2025 20:16:31","22-08-2025 20:13:04","22-08-2025 2=
0:19:04","Grid outage, site went down before Gen started due to Poor batter=
y backup//Grid return","Paul BIBOUM","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before Ge=
n started due to Poor battery backup//Grid return","franck.nkomot@matech-ca=
meroun.com","208","22-08-2025 20:16:31","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005744289","Nko=
abang Ebolmedjock","","22-08-2025 20:08:08","22-08-2025 20:04:02","22-08-20=
25 20:17:02","Gen stopped due to Alarm high temp // Water add in the radiat=
or and Gen start manually","Mba Lazare Herve","Equipment Repair","Passive",=
"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gen stopped due=
 to Alarm high temp // Water add in the radiator and Gen start manually","f=
ranck.nkomot@matech-cameroun.com","248","22-08-2025 20:08:08","MATECH CMR"
"Closed Complete","Warning","T0462","IHS_YND_123","NOCINC0005744152","Nkomo=
 II","","22-08-2025 19:48:10","","","Site Alarming due to Grid outage // Gr=
id return","Albran Byorel","Warning","Warning","POWER","Warning - Site on B=
attery","Site Alarming due to Grid outage // Grid return","franck.nkomot@ma=
tech-cameroun.com","551","22-08-2025 19:48:10","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005744083","Ebo=
go","","22-08-2025 19:38:19","22-08-2025 19:26:59","22-08-2025 20:23:59","G=
rid fluctuation, site went down because Gen failed to start due to grid bad=
 voltage // Site stabilized","Siligap Boris","Grid Supply","Passive","Grid"=
,"National Grid - Phase Controller Faulty","Grid fluctuation, site went dow=
n because Gen failed to start due to grid bad voltage // Site stabilized","=
franck.nkomot@matech-cameroun.com","728","22-08-2025 19:38:19","MATECH CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0005744049","M=
asque","","22-08-2025 19:30:06","22-08-2025 19:20:56","22-08-2025 19:44:28"=
,"Grid outage site went dow due to bad grid voltage causing by eneo cable b=
urnt//We bypass grid and gen manually started","Fabrice Pouakam","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","Grid outage=
 site went dow due to bad grid voltage causing by eneo cable burnt//We bypa=
ss grid and gen manually started","gerard.tchangoue@matech-cameroun.com","5=
53","22-08-2025 19:30:06","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005743885","Cit=
e des nations","","22-08-2025 19:06:47","22-08-2025 19:01:41","22-08-2025 1=
9:07:41","Grid outage, site went down before Gen started due to Poor batter=
y backup//Grid return","Paul BIBOUM","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before Ge=
n started due to Poor battery backup//Grid return","franck.nkomot@matech-ca=
meroun.com","307","22-08-2025 19:06:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005743879","Nsam esc=
ale LP","","22-08-2025 19:05:20","22-08-2025 19:00:38","22-08-2025 19:06:38=
","Cascaded Incident from TTO5951668","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, Site went down before Gen start =
due to poor backup/ // Grid return","franck.nkomot@matech-cameroun.com","28=
2","22-08-2025 19:05:20","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005743875","Nsa=
m Sofavinc","IHS_YND_732","22-08-2025 19:04:48","22-08-2025 19:00:38","22-0=
8-2025 19:06:38","Grid outage, Site went down before Gen start due to poor =
backup/ // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup/ // Grid return","franck.nkomot@matech-camero=
un.com","251","22-08-2025 19:04:48","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005743713","TON=
GOLO SNEC","","22-08-2025 18:36:22","22-08-2025 18:31:10","22-08-2025 19:24=
:16","Site went down due to PSC3 dysfunctionning //He reset  PSC3, site on =
Grid (More investigation on going toomorrow)","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Site went down due to =
PSC3 dysfunctionning //He reset  PSC3, site on Grid (More investigation on =
going toomorrow)","franck.nkomot@matech-cameroun.com","313","22-08-2025 18:=
36:22","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005743573","M=
ontee-Des-Soeurs","","22-08-2025 18:14:17","22-08-2025 18:06:11","22-08-202=
5 18:21:08","Active // No power issue, site is on Grid with Ubaie: 54.5V, M=
bah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active // No power issue, site is on Grid with Ubaie: 54.5V, Mbah hosiah(6=
99699694) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","=
488","22-08-2025 18:14:17","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005743488","TON=
GOLO SNEC","","22-08-2025 17:57:40","22-08-2025 17:53:32","22-08-2025 18:25=
:52","Grid outage, site went down because Gen failed to start due to poor b=
attery backup // site stabilised","Fabrice Pouakam","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down because Gen failed to start due to poor battery backup // site stabil=
ised","franck.nkomot@matech-cameroun.com","249","22-08-2025 17:57:40","MATE=
CH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005743413","TSI=
NGA VILLAGE 2","","22-08-2025 17:45:39","22-08-2025 17:42:31","22-08-2025 1=
8:26:57"," site went down due to priming pump faulty // He replace priming =
pump with the pear","Delor Telezing","Fuel Outage (Probable)","Passive","Di=
esel","Fuel Line Issue"," site went down due to priming pump faulty // He r=
eplace priming pump with the pear","franck.nkomot@matech-cameroun.com","190=
","22-08-2025 17:45:39","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005743327","TON=
GOLO SNEC","","22-08-2025 17:26:25","22-08-2025 17:21:15","22-08-2025 17:48=
:15","Grid outage, site went down because Gen failed to start due to poor b=
attery backup // site stabilised","Fabrice Pouakam","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down because Gen failed to start due to poor battery backup // site stabil=
ised","franck.nkomot@matech-cameroun.com","311","22-08-2025 17:26:25","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0005743289","B=
astos Ekoudou","","22-08-2025 17:15:11","22-08-2025 17:04:41","22-08-2025 1=
7:37:51","Site impacted by china embassy yde","Mboua Thierry","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","Active//No power issue site=
 on grid with U=3D52.4V The Tx FME Eloundou Bertrand from Huawei is informe=
d","gerard.tchangoue@matech-cameroun.com","1591","22-08-2025 17:15:11","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0005743282","c=
hina embassy yde","IHS_YND_193","22-08-2025 17:13:46","22-08-2025 17:04:41"=
,"22-08-2025 17:37:51","Active//No power issue site on grid with U=3D52.4V =
The Tx FME Eloundou Bertrand from Huawei is informed","","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue site on grid with U=3D52.4V The Tx FME Eloundou Bertrand f=
rom Huawei is informed","gerard.tchangoue@matech-cameroun.com","546","22-08=
-2025 17:13:46","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005743276","Cit=
e des nations","","22-08-2025 17:11:58","22-08-2025 17:07:46","22-08-2025 1=
7:13:46","Grid outage, site went down before Gen started due to Poor batter=
y backup//Grid return","Paul BIBOUM","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before Ge=
n started due to Poor battery backup//Grid return","franck.nkomot@matech-ca=
meroun.com","253","22-08-2025 17:11:58","MATECH CMR"
"Closed Complete","Warning","CTR_056","IHS_YND_100","NOCINC0005743154","She=
ll-Nsimeyong","","22-08-2025 16:48:30","","","site alarming due to Grid out=
age // Grid return","MINKA NICOLAS","Warning","Warning","POWER","Warning - =
Site on Battery","site alarming due to Grid outage // Grid return","franck.=
nkomot@matech-cameroun.com","566","22-08-2025 16:48:30","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0005743117","N=
komkana 2","","22-08-2025 16:40:39","22-08-2025 16:35:31","22-08-2025 17:06=
:42","Grid Only, No space to deploy MGE // Grid return","Mboua Thierry","Ca=
scade Outage","Passive","Cascade Passive","Cascade Passive","Grid Only, No =
space to deploy MGE // Grid return","gerard.tchangoue@matech-cameroun.com",=
"656","22-08-2025 16:40:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005743111","Bastos B=
ethesda","","22-08-2025 16:39:48","22-08-2025 16:32:03","22-08-2025 16:43:3=
1","Cascaded Incident from TTO5950774","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Site impacted by CNDH (not manage =
by IHS)","gerard.tchangoue@matech-cameroun.com","465","22-08-2025 16:39:48"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0005743112","Tsinga",=
"","22-08-2025 16:39:48","22-08-2025 16:32:03","22-08-2025 16:43:31","Casca=
ded Incident from TTO5950774","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Site impacted by CNDH (not manage by IHS)",=
"gerard.tchangoue@matech-cameroun.com","465","22-08-2025 16:39:48","MATECH =
CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0005743109","Nko=
mkana","IHS_YND_138","22-08-2025 16:39:37","22-08-2025 16:35:31","22-08-202=
5 17:07:16","Grid Only, No space to deploy MGE // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No sp=
ace to deploy MGE // Grid return","franck.nkomot@matech-cameroun.com","248"=
,"22-08-2025 16:39:37","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005743088","B=
astos-Nylon","IHS_YND_563, IHS_YND_127","22-08-2025 16:37:27","22-08-2025 1=
6:32:03","22-08-2025 16:43:31","Site impacted by CNDH (not manage by IHS)",=
"Mboua Thierry","Customer Equipment Failure","Active","Active Equipment Fai=
lure","Affected by 3rd Party Site","Site impacted by CNDH (not manage by IH=
S)","gerard.tchangoue@matech-cameroun.com","325","22-08-2025 16:37:27","MAT=
ECH CMR"
"Closed Complete","Warning","T2570","IHS_YND_749","NOCINC0005743085","ODZA =
MINKAN EDIBI ASSI","","22-08-2025 16:36:47","","","Site on Grit at 49V due =
to Grid bad voltage // Grid stabilized","Albran Byorel","Warning","Warning"=
,"POWER","Warning - National Grid - Unstable Grid Supply Issue","Site on Gr=
it at 49V due to Grid bad voltage // Grid stabilized","franck.nkomot@matech=
-cameroun.com","369","22-08-2025 16:36:47","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005743040","Sim=
e Building","","22-08-2025 16:28:53","22-08-2025 16:21:47","22-08-2025 16:2=
9:47","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","franck.nkomo=
t@matech-cameroun.com","427","22-08-2025 16:28:53","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005743035","Hop=
ital Central","","22-08-2025 16:28:09","22-08-2025 16:23:30","22-08-2025 17=
:06:30","Grid outage No Space to deploy a MDG,//Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No Spa=
ce to deploy a MDG,//Grid return","franck.nkomot@matech-cameroun.com","280"=
,"22-08-2025 16:28:09","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005743031","Mok=
olo Yaounde","","22-08-2025 16:27:06","22-08-2025 16:23:59","22-08-2025 17:=
06:59","Active // No power issue Ubaie: 54.6 V site on grid. TX FME Brice T=
sague (650214096) from HUAWEI is informed","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No powe=
r issue Ubaie: 54.6 V site on grid. TX FME Brice Tsague (650214096) from HU=
AWEI is informed","franck.nkomot@matech-cameroun.com","189","22-08-2025 16:=
27:06","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005743025","N=
kolfon Cimencam","","22-08-2025 16:26:17","22-08-2025 16:17:11","22-08-2025=
 16:29:46","No power issue, Site is impacted by Afanoya II (Not manage by I=
HS)","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipme=
nt Failure","Affected by 3rd Party Site","No power issue, Site is impacted =
by Afanoya II (Not manage by IHS)","gerard.tchangoue@matech-cameroun.com","=
547","22-08-2025 16:26:17","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005742906","TON=
GOLO SNEC","","22-08-2025 16:02:44","22-08-2025 16:00:30","22-08-2025 16:18=
:27","Grid outage, site went down because Gen failed to start due to poor b=
attery backup // site stabilised","Fabrice Pouakam","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down because Gen failed to start due to poor battery backup // site stabil=
ised","franck.nkomot@matech-cameroun.com","135","22-08-2025 16:02:44","MATE=
CH CMR"
"Closed Complete","Warning","CTR_109","IHS_YND_037","NOCINC0005742795","Nko=
lndongo","","22-08-2025 15:47:37","","","High temps alarm. FME is on site f=
or PM. He report that the air conditioning is faulty // Shelter open","MINK=
A NICOLAS","Warning","Warning","ENVIRONMENT","Warning - High Temperature","=
High temps alarm. FME is on site for PM. He report that the air conditionin=
g is faulty // Shelter open","franck.nkomot@matech-cameroun.com","569","22-=
08-2025 15:47:37","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005742771","TSI=
NGA VILLAGE 2","","22-08-2025 15:44:31","22-08-2025 15:40:26","22-08-2025 1=
6:02:37","FME Delor is on site for Work (PM) // End of Work","Delor Telezin=
g","Installation Activity","Passive","Planned Activity","Installation Activ=
ity","FME Delor is on site for Work (PM) // End of Work","franck.nkomot@mat=
ech-cameroun.com","318","22-08-2025 15:44:31","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005741857","TON=
GOLO SNEC","","22-08-2025 12:58:17","22-08-2025 12:55:06","22-08-2025 13:31=
:20","Grid fluctuation, Site went down because gen fails to start due to gr=
id bad voltage// Grid power stabilized","Fabrice Pouakam","Grid Supply","Pa=
ssive","Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuatio=
n, Site went down because gen fails to start due to grid bad voltage// Grid=
 power stabilized","cedric.tiani@matech-cameroun.com","192","22-08-2025 12:=
58:17","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005741628","T=
SINGA VILLAGE 2","","22-08-2025 12:17:05","22-08-2025 12:16:57","22-08-2025=
 15:09:26","Active//No power issue on site, Site on Gen UBAIE=3D48.7V TX FM=
E Julien (693095849) From Huawei is informed","Delor Telezing","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Gen UBAIE=3D48.7V TX FME Julien (69=
3095849) From Huawei is informed","edwige.kapawo@matech-cameroun.com","9","=
22-08-2025 12:17:05","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005740647","M=
ontee-Jouvence-II","","22-08-2025 09:40:51","22-08-2025 09:38:44","22-08-20=
25 10:52:59","Site went Down due to work Abena (677793603 /Grato) was on si=
te for work (standardization of cables after bay swap) // End of work","Hye=
mafo Gildas","Equipment Replacement","Passive","Planned Activity","Planned =
Activity - Passive","Site went Down due to work  Abena (677793603 /Grato) w=
as on site for work (Swap of PWC) // End of work","edwige.kapawo@matech-cam=
eroun.com","130","22-08-2025 09:40:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005740521","Messassi=
 okolo","","22-08-2025 09:14:30","22-08-2025 06:31:28","22-08-2025 08:43:29=
","Cascaded Incident from TTO5947175","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issue in the site at ni=
ght. Grid outage, site went down because site behaves as Grid only site (Ge=
n Noise) // Grid return","edwige.kapawo@matech-cameroun.com","9782","22-08-=
2025 09:14:30","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005739878","E=
MANA BILICK CITY","IHS_YND_279","22-08-2025 06:54:34","22-08-2025 06:31:28"=
,"22-08-2025 08:50:16","Access issue in the site at night. Grid outage, sit=
e went down because site behaves as Grid only site (Gen Noise) // Grid retu=
rn","Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord Related Is=
sues","Access Issue - Land Lord","Access issue in the site at night. Grid o=
utage, site went down because site behaves as Grid only site (Gen Noise) //=
 Grid return","cedric.tiani@matech-cameroun.com","1388","22-08-2025 06:54:3=
4","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0005739869","Mes=
sassi Ngonlonk","","22-08-2025 06:51:50","22-08-2025 06:31:12","22-08-2025 =
08:01:38","Grid outage gen start and stopped due to oil sensor issue // We =
fixed oil sensor and gen manually started","Fabrice Pouakam","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Oil Sensor Switch","Grid outage gen start=
 and stopped due to oil sensor issue // We fixed oil sensor and gen manuall=
y started","ludivine.ngamaleu@ihstowers.com","1239","22-08-2025 06:51:50","=
MATECH CMR"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0005739825","Ngo=
g Mapubi","","22-08-2025 06:36:54","22-08-2025 06:35:42","22-08-2025 07:22:=
49"," Grid outage, Site went down because gen fails to start due to automat=
ism system dysfunctionning // He reset it and manually start the gen","Keme=
ni Franklin","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","=
 Grid outage, Site went down because gen fails to start due to automatism s=
ystem dysfunctionning // He reset it and manually start the gen","cedric.ti=
ani@matech-cameroun.com","73","22-08-2025 06:36:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005739692","Carrefou=
r Ayissi Ele","","22-08-2025 05:46:37","22-08-2025 05:31:32","22-08-2025 06=
:38:32","Cascaded Incident from TTO5946951","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site wen=
t down because Gen failed to start due to grid bad voltage,no RCP  // Gen m=
anually started","cedric.tiani@matech-cameroun.com","905","22-08-2025 05:46=
:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005739693","Nkol-Meb=
anga","","22-08-2025 05:46:37","22-08-2025 05:31:32","22-08-2025 06:38:32",=
"Cascaded Incident from TTO5946951","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause Gen failed to start due to grid bad voltage,no RCP  // Gen manually =
started","cedric.tiani@matech-cameroun.com","905","22-08-2025 05:46:37","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005739672","S=
aa","IHS_YND_810, IHS_YND_809","22-08-2025 05:39:47","22-08-2025 05:31:32",=
"22-08-2025 06:38:32","Grid fluctuation, site went down because Gen failed =
to start due to grid bad voltage,no RCP  // Gen manually started","Parker T=
choup","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, site went down because Gen failed to start due to g=
rid bad voltage,no RCP  // Gen manually started","cedric.tiani@matech-camer=
oun.com","497","22-08-2025 05:39:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0005738736","Odza II =
OCM","","22-08-2025 00:15:46","22-08-2025 00:09:42","22-08-2025 00:13:09","=
Cascaded Incident from TTO5945917","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power Ubaie=3D53,4V site on GRID Th=
e Tx FME Rodrigue (651319438 // 655102999) from Huawei is informed","cedric=
.tiani@matech-cameroun.com","364","22-08-2025 00:15:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005738735","MEHANDAN=
","","22-08-2025 00:15:45","22-08-2025 00:09:42","22-08-2025 00:13:09","Cas=
caded Incident from TTO5945917","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power Ubaie=3D53,4V site on GRID The T=
x FME Rodrigue (651319438 // 655102999) from Huawei is informed","cedric.ti=
ani@matech-cameroun.com","363","22-08-2025 00:15:45","MATECH CMR"
"Closed Complete","Site Down","T1071","IHS_YND_343","NOCINC0005738730","Mbe=
doumou - Ekali","IHS_YND_528, IHS_YND_527","22-08-2025 00:14:51","22-08-202=
5 00:09:42","22-08-2025 00:50:09","No power Ubaie=3D53,4V site on GRID The =
Tx FME Rodrigue (651319438 // 655102999) from Huawei is informed","Albran B=
yorel","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power Ubaie=3D53,4V site on GRID The Tx FME Rodrigue =
(651319438 // 655102999) from Huawei is informed","cedric.tiani@matech-came=
roun.com","310","22-08-2025 00:14:51","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005738469","Mon=
tee-Jouvence-II","","21-08-2025 22:46:29","21-08-2025 22:41:17","22-08-2025=
 00:15:45","Site went down due to CB(80A) in PWC that feeds MTN //He rearme=
d it and made a bridge with a 125A","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went d=
own due to CB(80A) in PWC that feeds MTN //He rearmed it and made a bridge =
with a 125A","cedric.tiani@matech-cameroun.com","313","21-08-2025 22:46:29"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005738174","S=
aa","","21-08-2025 21:46:57","21-08-2025 21:42:48","21-08-2025 21:48:03","	=
No power issue on site ,site on Gen with Ubaie =3D50.5V The Tx Technician f=
rom Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site ,site on Gen with Ubaie =3D50.5V The Tx Technician fr=
om Huawei Gr=E9goire//654547479 is informed","gerard.tchangoue@matech-camer=
oun.com","251","21-08-2025 21:46:57","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005738028","Mon=
tee-Jouvence-II","","21-08-2025 21:25:54","21-08-2025 21:22:42","21-08-2025=
 21:35:10","Site went down because FME Abena (677793603) from Grato was on =
site for work (Swap of PWC) // End of work","Hyemafo Gildas","Installation =
Activity","Passive","Planned Activity","Installation Activity","Site went d=
own because FME Abena (677793603) from Grato was on site for work (Swap of =
PWC) // End of work","loic.noumsi@matech-cameroun.com","193","21-08-2025 21=
:25:54","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005737727","S=
IMBOCK BONAMBAPE","","21-08-2025 20:33:31","21-08-2025 20:29:18","21-08-202=
5 20:56:49","	Site went down because Gen overload(20KVA//300A )SS HIS Felix=
 Bateu is informed // Grid return","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","	Site went down because Gen overload(20=
KVA//300A )SS HIS Felix Bateu is informed // Grid return","gerard.tchangoue=
@matech-cameroun.com","255","21-08-2025 20:33:31","MATECH CMR"
"Closed Complete","Site Down","T0836","IHS_YND_109","NOCINC0005737637","Mob=
il-Essos","","21-08-2025 20:12:29","21-08-2025 20:10:24","21-08-2025 22:03:=
35"," Grid outage, Gen stopped due to air intake cause by  priming pump mal=
function // Gen purged and Gen started manually (the site is on permanent G=
en and more investigation on going)","Siligap Boris","Fuel Outage (Probable=
)","Passive","ACDG Gen","ACDG - Air Intake","
Grid outage, Gen stopped due to air intake cause by  priming pump malfuncti=
on // Gen purged and Gen started manually (the site is on permanent Gen and=
 more investigation on going)
","loic.noumsi@matech-cameroun.com","126","21-08-2025 20:12:29","MATECH CMR=
"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005737623","E=
lig-Edzoa","","21-08-2025 20:10:15","21-08-2025 20:09:06","21-08-2025 22:36=
:00","Grid only site,No mobile gen available ","","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","Grid only site,No mobile gen ava=
ilable // Grid restored","gerard.tchangoue@matech-cameroun.com","70","21-08=
-2025 20:10:15","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005737604","Mon=
tee-Jouvence-II","","21-08-2025 20:07:55","21-08-2025 20:04:53","21-08-2025=
 20:59:46","Site went down because FME Abena (677793603) from Grato was on =
site for work (Swap of PWC) // End of work","Hyemafo Gildas","Installation =
Activity","Passive","Planned Activity","Installation Activity","Site went d=
own because FME Abena (677793603) from Grato was on site for work (Swap of =
PWC) // End of work","loic.noumsi@matech-cameroun.com","183","21-08-2025 20=
:07:55","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005737552","S=
IMBOCK BONAMBAPE","","21-08-2025 19:57:39","21-08-2025 19:54:47","21-08-202=
5 20:00:17","Site went down because Gen overload(20KVA//300A )SS HIS Felix =
Bateu is informed // Grid return","Hyemafo Gildas","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Site went down because Gen overload(20KV=
A//300A )SS HIS Felix Bateu is informed // Grid return","gerard.tchangoue@m=
atech-cameroun.com","174","21-08-2025 19:57:39","MATECH CMR"
"Closed Complete","Site Down","T0292","IHS_YND_231","NOCINC0005737375","Nko=
lso","","21-08-2025 19:27:59","21-08-2025 19:23:26","21-08-2025 20:55:06","=
Grid outage, site went down because gen started and stopped due to grid bad=
 voltage // He bypassed Grid and started Gen manually","TIENTCHEU NZETCHIEU=
 GAEL","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid outage, site went down because gen started and stopped due to gr=
id bad voltage // He bypassed Grid and started Gen manually","loic.noumsi@m=
atech-cameroun.com","274","21-08-2025 19:27:59","MATECH CMR"
"Closed Complete","Warning","T0292","IHS_YND_231","NOCINC0005737280","Nkols=
o","","21-08-2025 19:03:00","","","Grid outage, site went down because gen =
started and stopped due to grid bad voltage // He bypassed Grid and started=
 Gen manually","TIENTCHEU NZETCHIEU GAEL","Warning","Warning","POWER","Warn=
ing - Site on Battery","Grid outage, site went down because gen started and=
 stopped due to grid bad voltage // He bypassed Grid and started Gen manual=
ly","loic.noumsi@matech-cameroun.com","3","21-08-2025 19:03:00","MATECH CMR=
"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0005736908","O=
KOA Peage","IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_350=
, IHS_YND_335, IHS_YND_349","21-08-2025 17:43:15","21-08-2025 17:34:08","21=
-08-2025 17:36:16","	No power issue on site Ubaie =3D55,3V site on Grid Ful=
bert(654266068) of huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	No power =
issue on site Ubaie =3D55,3V site on Grid Fulbert(654266068) of huawei is i=
nformed","gerard.tchangoue@matech-cameroun.com","548","21-08-2025 17:43:15"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005736897","Nkongtoc=
k","","21-08-2025 17:40:36","21-08-2025 17:34:08","21-08-2025 17:36:16","",=
"Kemeni Franklin","Cascade Outage","Active","Cascade Active","Cascade Activ=
e","	No power issue on site Ubaie =3D55,3V site on Grid Fulbert(654266068) =
of huawei is informed","gerard.tchangoue@matech-cameroun.com","1062","21-08=
-2025 17:40:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005736896","Angongo"=
,"","21-08-2025 17:40:36","21-08-2025 17:34:08","21-08-2025 17:36:16","Casc=
aded Incident from TTO5943824 - Cascade Removed From TTO5943824","Fanda Bri=
ce","Cascade Outage","Active","Cascade Active","Cascade Active","	No power =
issue on site Ubaie =3D55,3V site on Grid Fulbert(654266068) of huawei is i=
nformed","gerard.tchangoue@matech-cameroun.com","862","21-08-2025 17:40:36"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0005736893","Nkenglik=
ok","","21-08-2025 17:40:35","21-08-2025 17:34:08","21-08-2025 17:36:16","C=
ascaded Incident from TTO5943824 - Cascade Removed From TTO5943824","Kemeni=
 Franklin","Cascade Outage","Active","Cascade Active","Cascade Active","	No=
 power issue on site Ubaie =3D55,3V site on Grid Fulbert(654266068) of huaw=
ei is informed","gerard.tchangoue@matech-cameroun.com","817","21-08-2025 17=
:40:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005736895","Mambine"=
,"","21-08-2025 17:40:35","21-08-2025 17:34:08","21-08-2025 17:36:16","","F=
anda Brice","Cascade Outage","Active","Cascade Active","Cascade Active","	N=
o power issue on site Ubaie =3D55,3V site on Grid Fulbert(654266068) of hua=
wei is informed","gerard.tchangoue@matech-cameroun.com","1029","21-08-2025 =
17:40:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005736894","Ebeba","=
","21-08-2025 17:40:35","21-08-2025 17:34:08","21-08-2025 17:36:16","","Fan=
da Brice","Cascade Outage","Active","Cascade Active","Cascade Active","	No =
power issue on site Ubaie =3D55,3V site on Grid Fulbert(654266068) of huawe=
i is informed","gerard.tchangoue@matech-cameroun.com","991","21-08-2025 17:=
40:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0005736892","Mandoumb=
a OCM","","21-08-2025 17:40:34","21-08-2025 17:34:08","21-08-2025 17:36:16"=
,"Cascaded Incident from TTO5943824 - Cascade Removed From TTO5943824","Kem=
eni Franklin","Cascade Outage","Active","Cascade Active","Cascade Active","=
	No power issue on site Ubaie =3D55,3V site on Grid Fulbert(654266068) of h=
uawei is informed","gerard.tchangoue@matech-cameroun.com","780","21-08-2025=
 17:40:34","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005736874","M=
arche Odza","","21-08-2025 17:36:49","21-08-2025 17:32:44","21-08-2025 19:2=
4:42","Our SS is on site for work (swap of MPR) with SS IHS Pascaline // En=
d of work","Albran Byorel","Equipment Replacement","Passive","Planned Activ=
ity","Planned Activity - Passive","Site went down due to work of Our SS wit=
h SS IHS Pascaline  (swap of MPR) with SS IHS Pascaline // End of work","ge=
rard.tchangoue@matech-cameroun.com","248","21-08-2025 17:36:49","MATECH CMR=
"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0005736860","M=
bankomo IHS","","21-08-2025 17:35:13","21-08-2025 17:34:08","21-08-2025 17:=
36:16","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade=
 Active","	No power issue on site Ubaie =3D55,3V site on Grid Fulbert(65426=
6068) of huawei is informed","gerard.tchangoue@matech-cameroun.com","951","=
21-08-2025 17:35:13","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005736644","Cit=
e des nations","","21-08-2025 16:59:47","21-08-2025 16:59:42","21-08-2025 1=
9:45:47","Site went down because SS IHS Fran=E7ois Ndoungou was on site for=
 work (SWAP of MPR) // End of work","Paul BIBOUM","Installation Activity","=
Passive","Planned Activity","Installation Activity","Site went down because=
 SS IHS Fran=E7ois Ndoungou was on site for work (SWAP of MPR) // End of wo=
rk","loic.noumsi@matech-cameroun.com","6","21-08-2025 16:59:47","MATECH CMR=
"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005736506","M=
vog-Ada_OCM","","21-08-2025 16:32:44","21-08-2025 16:29:03","21-08-2025 19:=
03:29","Grid only on site, No space on site to deploy MDGE  // Grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d only on site, No space on site to deploy MDGE  // Grid return","gerard.tc=
hangoue@matech-cameroun.com","222","21-08-2025 16:32:44","MATECH CMR"
"Closed Complete","Site Down","T0401","IHS_YND_205","NOCINC0005736371","Ton=
golo MTN","","21-08-2025 16:15:15","21-08-2025 16:13:10","21-08-2025 16:35:=
02","Grid outage site went down because Gen failed to start due to Gen card=
 faulty // he reset and started Gen manually","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went =
down because Gen failed to start due to Gen card faulty // he reset and sta=
rted Gen manually","loic.noumsi@matech-cameroun.com","125","21-08-2025 16:1=
5:15","MATECH CMR"
"Closed Complete","Warning","T0401","IHS_YND_205","NOCINC0005736310","Tongo=
lo MTN","","21-08-2025 16:04:30","","","Grid outage site went down because =
Gen failed to start due to Gen card faulty // he reset and started Gen manu=
ally","Fabrice Pouakam","Warning","Warning","POWER","Warning - Site on Batt=
ery","Grid outage site went down because Gen failed to start due to Gen car=
d faulty // he reset and started Gen manually","loic.noumsi@matech-cameroun=
.com","1","21-08-2025 16:04:30","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005736240","M=
vog-Ada_OCM","","21-08-2025 15:51:21","21-08-2025 15:49:11","21-08-2025 16:=
02:34","Grid only on site, No space on site to deploy MDGE // Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 only on site, No space on site to deploy MDGE // Grid return","gerard.tcha=
ngoue@matech-cameroun.com","131","21-08-2025 15:51:21","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005736237","S=
atcom","","21-08-2025 15:50:38","21-08-2025 15:46:32","21-08-2025 15:57:40"=
,"No power issue on site, Site impacted by Etoa-meki-II_CTR_682 not managed=
 by IHS","Delor Telezing","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site, Site impacted=
 by Etoa-meki-II_CTR_682 not managed by IHS","gerard.tchangoue@matech-camer=
oun.com","248","21-08-2025 15:50:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0005736160","Ekekam",=
"","21-08-2025 15:35:08","21-08-2025 15:32:44","21-08-2025 16:42:01","Casca=
ded Incident from TTO5943042","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuations, site went =
down due to grid bad voltage and no rcp on site // he bypassed Grid and sta=
rted Gen manually","loic.noumsi@matech-cameroun.com","144","21-08-2025 15:3=
5:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0005736161","NKONGKAR=
AK","","21-08-2025 15:35:08","21-08-2025 15:32:44","21-08-2025 16:42:01","C=
ascaded Incident from TTO5943042","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid fluctuations, site w=
ent down due to grid bad voltage and no rcp on site // he bypassed Grid and=
 started Gen manually","loic.noumsi@matech-cameroun.com","144","21-08-2025 =
15:35:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0005736159","Lobo 2",=
"","21-08-2025 15:35:08","21-08-2025 15:32:44","21-08-2025 16:42:01","Casca=
ded Incident from TTO5943042","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuations, site went =
down due to grid bad voltage and no rcp on site // he bypassed Grid and sta=
rted Gen manually","loic.noumsi@matech-cameroun.com","144","21-08-2025 15:3=
5:08","MATECH CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0005736153","LOB=
O MTN","IHS_YND_783, IHS_YND_714, IHS_YND_713","21-08-2025 15:33:49","21-08=
-2025 15:32:44","21-08-2025 16:51:40","Grid fluctuations, site went down du=
e to grid bad voltage and no rcp on site // he bypassed Grid and started Ge=
n manually","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","Grid fluctuations, site went down due=
 to grid bad voltage and no rcp on site // he bypassed Grid and started Gen=
 manually","loic.noumsi@matech-cameroun.com","66","21-08-2025 15:33:49","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005735893","N=
simalen OCM","","21-08-2025 14:51:04","21-08-2025 14:50:58","21-08-2025 17:=
06:56","	FME Ronix (695934760) From Grato is on site for work (swap of MPR)=
 // End of work","Albran Byorel","Equipment Replacement","Passive","Planned=
 Activity","Planned Activity - Passive","	FME Ronix (695934760) From Grato =
is on site for work (swap of MPR) // End of work","gerard.tchangoue@matech-=
cameroun.com","7","21-08-2025 14:51:04","MATECH CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0005735624","O=
bobogo","","21-08-2025 13:55:56","21-08-2025 13:46:50","21-08-2025 14:55:41=
","Site went down due to disjunction plus burns circuit breaker (100A) in t=
he orange BTS // changed the 100A circuit breaker which burned with a 125A"=
,"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier - Circ=
uit Breaker","Site went down due to disjunction plus burns circuit breaker =
(100A) in the orange BTS // changed the 100A circuit breaker which burned w=
ith a 125A","gerard.tchangoue@matech-cameroun.com","548","21-08-2025 13:55:=
56","MATECH CMR"
"Closed Complete","Warning","T3220","IHS_YND_765","NOCINC0005735466","MBALN=
GONG LYCEE","","21-08-2025 13:18:34","","","FME is on site  work (Swap Gen)=
 // End of work","Fanda Brice","Warning","Warning","POWER","Warning - Site =
on Battery","FME is on site  work (Swap Gen) // End of work","gerard.tchang=
oue@matech-cameroun.com","3","21-08-2025 13:18:34","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005734988","Lad=
a I Yde","","21-08-2025 11:55:39","21-08-2025 11:54:11","21-08-2025 12:27:0=
8","Site down due to 03/05 Rectifier dysfuntionning // Site stabilised and =
site on grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site down due to 03/05 Rectifier dysfuntionning // Site =
stabilised and site on grid","loic.noumsi@matech-cameroun.com","90","21-08-=
2025 11:55:39","MATECH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0005734739","O=
ssombe","","21-08-2025 11:02:01","21-08-2025 10:58:45","21-08-2025 12:36:39=
","Grid outage, site went down because gen start and stopped due to high te=
mp caused by broken radiator // the radiator has been changed and Gen manua=
lly started","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG =
- Radiator","Grid outage, site went down because gen start and stopped due =
to high temp caused by broken radiator // the radiator has been changed and=
 Gen manually started","gerard.tchangoue@matech-cameroun.com","197","21-08-=
2025 11:02:01","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005734625","N=
kolso","","21-08-2025 10:40:34","21-08-2025 10:35:28","21-08-2025 11:42:48"=
,"Grid outage gen failed to start due to automation malfunctionning//Gen ma=
nually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Co=
ntrol Panel","ATS-AMF Issue","Grid outage gen failed to start due to automa=
tion malfunctionning//Gen manually started","gerard.tchangoue@matech-camero=
un.com","308","21-08-2025 10:40:34","MATECH CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0005734402","Oss=
ombe","","21-08-2025 09:50:37","21-08-2025 09:45:28","21-08-2025 10:37:34",=
"Grid outage, site went down because gen stopped with under voltage alarm /=
/ Reset done and gen started","Parker Tchoup","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen =
stopped with under voltage alarm // Reset done and gen started","gerard.tch=
angoue@matech-cameroun.com","310","21-08-2025 09:50:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0005733496","Emana ly=
cee 2","","21-08-2025 05:51:38","20-08-2025 13:23:38","20-08-2025 13:24:56"=
,"Cascaded Incident from TTO5935307","Fabrice Pouakam","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","ACTIVE// No power issue site Ubaie=
=3D51.8V site on Gen, The tx Fme Symphorien(650257151)from Huawei is inform=
ed.","Mahesh.Kumar@quintica.com","59280","21-08-2025 05:51:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005733495","Emana Ly=
cee","","21-08-2025 05:51:37","20-08-2025 13:23:38","20-08-2025 13:24:56","=
Cascaded Incident from TTO5935307","Fabrice Pouakam","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","ACTIVE// No power issue site Ubaie=
=3D51.8V site on Gen, The tx Fme Symphorien(650257151)from Huawei is inform=
ed.","Mahesh.Kumar@quintica.com","59279","21-08-2025 05:51:37","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005732690","Lad=
a I Yde","","21-08-2025 00:49:04","21-08-2025 00:45:57","21-08-2025 00:46:5=
9","Site down due to 03/05 Rectifier dysfuntionning // Site stabilised and =
 site on grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site down due to 03/05 Rectifier dysfuntionning // Site=
 stabilised and  site on grid","cedric.tiani@matech-cameroun.com","188","21=
-08-2025 00:49:04","MATECH CMR"
"Closed Complete","Site Down","T1071","IHS_YND_343","NOCINC0005732522","Mbe=
doumou - Ekali","IHS_YND_553, IHS_YND_410, IHS_YND_595, IHS_EBO_015, IHS_YN=
D_344, IHS_YND_411","20-08-2025 23:43:26","20-08-2025 23:35:14","20-08-2025=
 23:40:17","No power Ubaie=3D53,4V site on GRID The Tx FME Rodrigue (651319=
438 // 655102999) from Huawei is informed","Albran Byorel","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower Ubaie=3D53,4V site on GRID The Tx FME Rodrigue (651319438 // 655102999=
) from Huawei is informed","cedric.tiani@matech-cameroun.com","493","20-08-=
2025 23:43:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_005","NOCINC0005732400","Imm-Olym=
pique","","20-08-2025 23:02:58","20-08-2025 22:41:02","20-08-2025 23:06:49"=
,"Cascaded Incident from TTO5938779","Paul BIBOUM","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active: No power issue, site is on gri=
d with Ubaie=3D54V, NOTICE site impacted by CBC ","vanel.mbiada@matech-came=
roun.com","1316","20-08-2025 23:02:58","MATECH CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0005732382","M=
ontee-Anne-Rouge","","20-08-2025 22:58:35","20-08-2025 22:41:02","20-08-202=
5 23:06:49","","","Cascade Outage","Active","Cascade Active","Cascade Activ=
e","Active: No power issue, site is on grid with Ubaie=3D54V, NOTICE site i=
mpacted by CBC ","vanel.mbiada@matech-cameroun.com","1277","20-08-2025 22:5=
8:35","MATECH CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0005732340","Y=
de-M-Central","","20-08-2025 22:46:44","20-08-2025 22:41:02","20-08-2025 23=
:06:49","","","Cascade Outage","Active","Cascade Active","Cascade Active","=
Active: No power issue, site is on grid with Ubaie=3D54V, NOTICE site impac=
ted by CBC ","gerard.tchangoue@matech-cameroun.com","1256","20-08-2025 22:4=
6:44","MATECH CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0005732337","E=
lig-Essono","IHS_YND_007, IHS_YND_003, IHS_YND_005, IHS_YND_002","20-08-202=
5 22:46:13","20-08-2025 22:41:02","20-08-2025 23:06:49","Active: No power i=
ssue, site is on grid with Ubaie=3D54V, NOTICE site impacted by CBC ","Paul=
 BIBOUM","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active: No power issue, site is on grid with Ubaie=3D5=
4V, NOTICE site impacted by CBC ","gerard.tchangoue@matech-cameroun.com","3=
12","20-08-2025 22:46:13","MATECH CMR"
"Closed Complete","Site Down","CTR_014","IHS_YND_003","NOCINC0005732334","M=
ercure","","20-08-2025 22:45:37","20-08-2025 22:41:02","20-08-2025 23:06:49=
","","","Cascade Outage","Active","Cascade Active","Cascade Active","Active=
: No power issue, site is on grid with Ubaie=3D54V, NOTICE site impacted by=
 CBC ","gerard.tchangoue@matech-cameroun.com","1222","20-08-2025 22:45:37",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005731712","N=
simalen OCM","","20-08-2025 20:57:04","20-08-2025 20:54:58","20-08-2025 21:=
10:01","FME Ronix (695934760) From Grato is on site for work (swap of gen) =
// End of work","Albran Byorel","Equipment Replacement","Passive","Planned =
Activity","Planned Activity - ACDG Replacement","FME Ronix (695934760) From=
 Grato is on site for work (swap of gen) // End of work","gerard.tchangoue@=
matech-cameroun.com","128","20-08-2025 20:57:04","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005731703","Nsi=
malen MTN","","20-08-2025 20:56:02","20-08-2025 20:52:48","20-08-2025 21:20=
:37","Site went down because FME Ronix (695934760) From Grato was on site f=
or work (swap of gen) // End of work","Albran Byorel","Installation Activit=
y","Passive","Planned Activity","Installation Activity","Site went down bec=
ause FME Ronix (695934760) From Grato was on site for work (swap of gen) //=
 End of work","loic.noumsi@matech-cameroun.com","195","20-08-2025 20:56:02"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0005731482","Nkolfoul=
ou Tsinga Village","","20-08-2025 20:14:50","20-08-2025 20:11:37","20-08-20=
25 20:27:18","Cascaded Incident from TTO5937809","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, Site wen=
t down because gen failed to start due DG card dysfunctionning // He reset =
it, site on Gen","loic.noumsi@matech-cameroun.com","193","20-08-2025 20:14:=
50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005731480","SOA VILL=
AGE","","20-08-2025 20:14:50","20-08-2025 20:11:37","20-08-2025 20:27:18","=
Cascaded Incident from TTO5937809","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 gen failed to start due DG card dysfunctionning // He reset it, site on Ge=
n","loic.noumsi@matech-cameroun.com","193","20-08-2025 20:14:50","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_296","NOCINC0005731481","Nkolfoul=
ou","","20-08-2025 20:14:50","20-08-2025 20:11:37","20-08-2025 20:27:18","C=
ascaded Incident from TTO5937809","Siligap Boris","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
gen failed to start due DG card dysfunctionning // He reset it, site on Gen=
","loic.noumsi@matech-cameroun.com","193","20-08-2025 20:14:50","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005731479","TSINGA V=
ILLAGE 2","","20-08-2025 20:14:49","20-08-2025 20:11:37","20-08-2025 20:27:=
18","Cascaded Incident from TTO5937809","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
ecause gen failed to start due DG card dysfunctionning // He reset it, site=
 on Gen","loic.noumsi@matech-cameroun.com","192","20-08-2025 20:14:49","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005731477","FOUGEROL=
E","","20-08-2025 20:14:49","20-08-2025 20:11:37","20-08-2025 20:27:18","Ca=
scaded Incident from TTO5937809","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down because g=
en failed to start due DG card dysfunctionning // He reset it, site on Gen"=
,"loic.noumsi@matech-cameroun.com","192","20-08-2025 20:14:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005731478","Mvog-Eba=
nda","","20-08-2025 20:14:49","20-08-2025 20:11:37","20-08-2025 20:27:18","=
Cascaded Incident from TTO5937809","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 gen failed to start due DG card dysfunctionning // He reset it, site on Ge=
n","loic.noumsi@matech-cameroun.com","192","20-08-2025 20:14:49","MATECH CM=
R"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0005731465","Nko=
lfoulou 2","IHS_YND_561, IHS_YND_269, IHS_YND_719, IHS_YND_323, IHS_YND_758=
, IHS_YND_296, IHS_YND_759","20-08-2025 20:12:45","20-08-2025 20:11:37","20=
-08-2025 20:27:18","Grid outage, Site went down because gen failed to start=
 due DG card dysfunctionning // He reset it, site on Gen","Siligap Boris","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
 Site went down because gen failed to start due DG card dysfunctionning // =
He reset it, site on Gen","loic.noumsi@matech-cameroun.com","69","20-08-202=
5 20:12:45","MATECH CMR"
"Closed Complete","Warning","T0319","IHS_YND_278","NOCINC0005731455","Nkolf=
oulou 2","","20-08-2025 20:10:02","","","Grid outage, Site went down becaus=
e gen failed to start due DG card dysfunctionning // He reset it, site on G=
en","Siligap Boris","Warning","Warning","POWER","Warning - Site on Battery"=
,"Grid outage, Site went down because gen failed to start due DG card dysfu=
nctionning // He reset it, site on Gen","loic.noumsi@matech-cameroun.com","=
2","20-08-2025 20:10:02","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005731411","NKO=
MKANA ELIZA HOTEL","","20-08-2025 20:00:08","20-08-2025 19:57:39","20-08-20=
25 20:31:45","Grid outage, No space to deploy a MGE // Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, No space to deploy a MGE // Grid return","loic.noumsi@matech-cameroun.com=
","151","20-08-2025 20:00:08","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005731283","Nko=
lfoulou CSD MTN","","20-08-2025 19:38:53","20-08-2025 20:11:37","20-08-2025=
 20:27:18","cascaded site","Siligap Boris","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","cascaded site","loic.noumsi@matech-cameroun=
.com","4166","20-08-2025 19:38:53","MATECH CMR"
"Closed Complete","Warning","CTR_031","IHS_YND_319","NOCINC0005731249","SOA=
 2","","20-08-2025 19:31:41","","","High temp // Site alarming due to the  =
Absence of an Eneo phase // Bridge made and door open","Siligap Boris","War=
ning","Warning","POWER","Warning - National Grid - Grid Incomplete Phase","=
High temp // Site alarming due to the  Absence of an Eneo phase // Bridge m=
ade and door open","loic.noumsi@matech-cameroun.com","223","20-08-2025 19:3=
1:41","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005731198","N=
simalen OCM","","20-08-2025 19:19:40","20-08-2025 19:14:35","20-08-2025 20:=
40:28","FME Ronix (695934760) From Grato is on site for work (swap of gen) =
// End of work","Albran Byorel","Equipment Replacement","Passive","Planned =
Activity","Planned Activity - ACDG Replacement","FME Ronix (695934760) From=
 Grato is on site for work (swap of gen) // End of work","gerard.tchangoue@=
matech-cameroun.com","307","20-08-2025 19:19:40","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005731183","Nko=
mo stade","","20-08-2025 19:16:57","20-08-2025 19:13:49","20-08-2025 19:19:=
10","Grid outage, Site went down before Gen start due to poor backup/ // Gr=
id return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup/ // Grid return","loic.noumsi@matech-cameroun.com","189=
","20-08-2025 19:16:57","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005731175","Nsi=
malen MTN","","20-08-2025 19:14:32","20-08-2025 19:00:22","20-08-2025 20:40=
:28"," Site went down because FME Ronix (695934760) From Grato was on site =
for work (swap of gen) // End of work","Albran Byorel","Installation Activi=
ty","Passive","Planned Activity","Installation Activity"," Site went down b=
ecause FME Ronix (695934760) From Grato was on site for work (swap of gen) =
// End of work","loic.noumsi@matech-cameroun.com","851","20-08-2025 19:14:3=
2","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005731154","Sim=
e Building","","20-08-2025 19:10:00","20-08-2025 19:03:56","20-08-2025 19:1=
1:46","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","loic.noumsi@=
matech-cameroun.com","365","20-08-2025 19:10:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005731000","Messassi=
 okolo","","20-08-2025 18:40:49","20-08-2025 18:39:58","21-08-2025 21:08:18=
","Cascaded Incident from TTO5937291","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage and LL inhibits us=
 to start the GEN due to noise //grid return","gerard.tchangoue@matech-came=
roun.com","51","20-08-2025 18:40:49","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005730997","E=
MANA BILICK CITY","IHS_YND_279","20-08-2025 18:40:14","20-08-2025 18:39:58"=
,"22-08-2025 06:20:31","Grid outage and LL inhibits us to start the GEN due=
 to noise //grid return","Fabrice Pouakam","Access Denial","Lease Or Legal"=
,"Landlord Related Issues","Access Issue - Land Lord","Grid outage and LL i=
nhibits us to start the GEN due to noise //grid return","gerard.tchangoue@m=
atech-cameroun.com","19","20-08-2025 18:40:14","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005730987","C=
rf Cornier","","20-08-2025 18:37:58","20-08-2025 18:32:53","20-08-2025 19:1=
5:32","ACTIVE //No power issue Ubaie: 54.6V site on Grid Armand NGUETSA // =
699949553// from huawei is informed,","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE //=
No power issue Ubaie: 54.6V site on Grid Armand NGUETSA // 699949553// from=
 huawei is informed,","gerard.tchangoue@matech-cameroun.com","307","20-08-2=
025 18:37:58","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005730908","Mok=
olo Yaounde","","20-08-2025 18:25:36","20-08-2025 18:24:30","20-08-2025 18:=
25:08","Active // No power issue Ubaie: 54.7 V site on grid. TX FME Brice T=
sague (650214096) from HUAWEI is informed","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No powe=
r issue Ubaie: 54.7 V site on grid. TX FME Brice Tsague (650214096) from HU=
AWEI is informed","loic.noumsi@matech-cameroun.com","68","20-08-2025 18:25:=
36","MATECH CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0005730803","MAN=
GUIERS CHAPELLE","","20-08-2025 18:01:06","20-08-2025 17:58:59","20-08-2025=
 18:00:28","No power issue on site ,site on Grid with Ubaie=3D53.2 V The Tx=
 FME Armand Nguetsa (699949553 // Huawei) is informed","Fabrice Pouakam","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site ,site on Grid with Ubaie=3D53.2 V The Tx F=
ME Armand Nguetsa (699949553 // Huawei) is informed","loic.noumsi@matech-ca=
meroun.com","128","20-08-2025 18:01:06","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005730563","Nsi=
malen MTN","","20-08-2025 17:16:04","20-08-2025 17:15:59","20-08-2025 18:41=
:11","Site went down because FME Ronix (695934760) From Grato was on site f=
or work (swap of gen) // End of work","Albran Byorel","Installation Activit=
y","Passive","Planned Activity","Installation Activity","Site went down bec=
ause FME Ronix (695934760) From Grato was on site for work (swap of gen) //=
 End of work","loic.noumsi@matech-cameroun.com","7","20-08-2025 17:16:04","=
MATECH CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0005730226","Oss=
ombe","","20-08-2025 16:36:53","20-08-2025 16:34:47","20-08-2025 16:36:49",=
"Active //No power issue, site on Gen with Ubaie=3D48V, The TX FME Gregoire=
 (654547479) from Huawei is informed.","Parker Tchoup","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/No power issue, site on Gen with Ubaie=3D48V, The TX FME Gregoire (6545474=
79) from Huawei is informed.","gerard.tchangoue@matech-cameroun.com","126",=
"20-08-2025 16:36:53","MATECH CMR"
"Closed Complete","Site Down","T1107-1","IHS_YND_217","NOCINC0005729642","A=
bom","","20-08-2025 15:10:19","20-08-2025 15:04:15","20-08-2025 15:20:50","=
site went down because Team Grato(Abena//699999625) was on site for work (s=
wap of PWC) // End of work","Siligap Boris","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","site went down because Team =
Grato(Abena//699999625) was on site for work (swap of PWC) // End of work",=
"loic.noumsi@matech-cameroun.com","365","20-08-2025 15:10:19","MATECH CMR"
"Closed Complete","Warning","T0183","IHS_YND_184","NOCINC0005729597","Nkolm=
esseng","","20-08-2025 15:00:09","","","HIgh temp//Shelter door open","Sili=
gap Boris","Warning","Warning","ENVIRONMENT","Warning - High Temperature","=
HIgh temp//Shelter door open","loic.noumsi@matech-cameroun.com","2","20-08-=
2025 15:00:09","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005729553","Par=
adis Hotel","","20-08-2025 14:49:32","20-08-2025 14:47:28","20-08-2025 16:4=
3:21","Site went down because our SS Anselme was on site with IHS SS Fran=
=E7ois for work (swap of MPR) // End of work","Siligap Boris","Installation=
 Activity","Passive","Planned Activity","Installation Activity","Site went =
down because our SS Anselme was on site with IHS SS Fran=E7ois for work (sw=
ap of MPR) // End of work","loic.noumsi@matech-cameroun.com","125","20-08-2=
025 14:49:32","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005729449","SIM=
BOCK BONAMBAPE","","20-08-2025 14:28:48","20-08-2025 14:25:44","20-08-2025 =
14:43:32","Site went down because Gen overload(20KVA//300A )SS HIS Felix Ba=
teu is informed // Grid return","Hyemafo Gildas","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Site went down because Gen overload(20KVA/=
/300A )SS HIS Felix Bateu is informed // Grid return","loic.noumsi@matech-c=
ameroun.com","185","20-08-2025 14:28:48","MATECH CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0005729186","O=
kolo","IHS_YND_274, IHS_YND_685","20-08-2025 13:28:45","20-08-2025 13:23:38=
","20-08-2025 13:24:56","ACTIVE// No power issue site Ubaie=3D51.8V site on=
 Gen, The tx Fme Symphorien(650257151)from Huawei is informed.","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE// No power issue site Ubaie=3D51.8V site on Gen, =
The tx Fme Symphorien(650257151)from Huawei is informed.","gerard.tchangoue=
@matech-cameroun.com","626","20-08-2025 13:28:45","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0005728041","A=
battoir","","20-08-2025 10:50:28","20-08-2025 10:48:20","20-08-2025 10:53:4=
9","Our FME Fabrice is on site for work (PM) // End Work","Fabrice Pouakam"=
,"Installation Activity","Passive","Planned Activity","Installation Activit=
y","Our FME Fabrice is on site for work (PM) // End Work","gerard.tchangoue=
@matech-cameroun.com","129","20-08-2025 10:50:28","MATECH CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0005727478","O=
bobogo","","20-08-2025 09:17:22","20-08-2025 09:12:13","20-08-2025 09:56:13=
","Site went down because CB (100A) disjuncted in PWC // CB put back on sit=
e on gen ","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Circuit Breaker Issue","Site went down because CB (100A) disj=
uncted in PWC // CB put back on site on gen ","gerard.tchangoue@matech-came=
roun.com","310","20-08-2025 09:17:22","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005726634","O=
mnisport-Rail","","20-08-2025 05:47:42","20-08-2025 05:42:34","20-08-2025 0=
6:57:32","Grid outage.site went down due to CB gen dishuncted causing by sh=
ort-ciricuit in ATS//We bypass it and reamed Circuit breaker ","Delor Telez=
ing","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid out=
age.site went down due to CB gen dishuncted causing by short-ciricuit in AT=
S//We bypass it and reamed Circuit breaker ","olivier.kwedi@ihstowers.com",=
"310","20-08-2025 05:47:42","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0005726150","Val=
lee Bastos MTN","","20-08-2025 02:22:50","20-08-2025 02:19:42","20-08-2025 =
10:13:04","Access issue during the night  Grid outage caused by neutral dis=
conection and gen ran until fuel shortage//Grid return by connecting the ne=
utral","Mboua Thierry","Access Denial","Lease Or Legal","Landlord Related I=
ssues","Access Issue - Land Lord","Access issue during the night  Grid outa=
ge caused by neutral disconection and gen ran until fuel shortage//Grid ret=
urn by connecting the neutral","edwige.kapawo@matech-cameroun.com","188","2=
0-08-2025 02:22:50","MATECH CMR"
"Cancelled","Warning","","IHS_YND_748","NOCINC0005725928","Nkoabang Alembe"=
,"","20-08-2025 01:35:50","","","Cascaded Incident from TTO5931799 - Cascad=
e Removed From TTO5931799","Mba Lazare Herve","","","","","","ludivine.ngam=
aleu@ihstowers.com","513","20-08-2025 01:35:50","MATECH CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0005725725","Mat=
sari","","20-08-2025 00:42:16","20-08-2025 00:37:10","20-08-2025 00:50:21",=
"Active // No power issue on site with Ubaie=3D53.8V site on Gen ,The Tx Fm=
e Gregoire( 652070658)from Huawei is informed","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue on site with Ubaie=3D53.8V site on Gen ,The Tx Fme=
 Gregoire( 652070658)from Huawei is informed","edwige.kapawo@matech-camerou=
n.com","308","20-08-2025 00:42:16","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0005725718","SAA=
 2","","20-08-2025 00:41:28","20-08-2025 00:39:22","20-08-2025 00:48:17","A=
ctive // No power issue on site ,site on Grid with Ubaie =3D53.6V. Tx Techn=
ician from Gr=E9goire (654547479 / Huawei ) is informed.","Parker Tchoup","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active // No power issue on site ,site on Grid with Ubaie =3D53.=
6V. Tx Technician from Gr=E9goire (654547479 / Huawei ) is informed.","edwi=
ge.kapawo@matech-cameroun.com","128","20-08-2025 00:41:28","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005725435","B=
arriere","","19-08-2025 23:31:24","19-08-2025 23:30:59","19-08-2025 23:32:3=
5","Active // No power issue on site Ubay: 53.5V site on Gen .TX Fme Fluber=
t (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue on site Ubay: 53.5V site on Gen .TX Fme Flubert (654266068/Hua=
wei) is informed","edwige.kapawo@matech-cameroun.com","27","19-08-2025 23:3=
1:24","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005725244","Man=
guiers Dispensaire","","19-08-2025 22:45:38","19-08-2025 22:41:27","19-08-2=
025 23:41:09","Site went down due to bad grid voltage  // He  bypass grid  =
and Gen manually started","Fabrice Pouakam","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Site went down due to bad grid v=
oltage  // He  bypass grid  and Gen manually started","edwige.kapawo@matech=
-cameroun.com","252","19-08-2025 22:45:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005724536","Messassi=
 okolo","","19-08-2025 20:31:25","19-08-2025 20:26:47","19-08-2025 21:08:22=
","Cascaded Incident from TTO5930236","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issue . Grid outage,sit=
e behaves as Grid only site (Gen Noise)  // grid return","vanel.mbiada@mate=
ch-cameroun.com","278","19-08-2025 20:31:25","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005724510","E=
MANA BILICK CITY","IHS_YND_279","19-08-2025 20:28:03","19-08-2025 20:26:47"=
,"19-08-2025 21:16:34","Access issue . Grid outage,site behaves as Grid onl=
y site (Gen Noise)  // grid return","Fabrice Pouakam","Access Denial","Leas=
e Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access is=
sue . Grid outage,site behaves as Grid only site (Gen Noise)  // grid retur=
n","vanel.mbiada@matech-cameroun.com","78","19-08-2025 20:28:03","MATECH CM=
R"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005724005","S=
IMBOCK BONAMBAPE","","19-08-2025 18:39:43","19-08-2025 18:36:47","19-08-202=
5 19:10:59","Site went down because Gen overload(20KVA//300A )SS HIS Felix =
Bateu is informed // Grid return","Hyemafo Gildas","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Site went down because Gen overload(20KV=
A//300A )SS HIS Felix Bateu is informed // Grid return","vanel.mbiada@matec=
h-cameroun.com","178","19-08-2025 18:39:43","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005723849","M=
essassi 2","","19-08-2025 18:17:34","19-08-2025 18:16:25","19-08-2025 18:56=
:35","Grid outage site went down because Gen failed to start due PWC ZTE dy=
sfonctionned // Gen manually started","Fabrice Pouakam","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Grid outage site went =
down because Gen failed to start due PWC ZTE dysfonctionned // Gen manually=
 started","vanel.mbiada@matech-cameroun.com","71","19-08-2025 18:17:34","MA=
TECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005723631","Lad=
a I Yde","","19-08-2025 17:28:42","19-08-2025 17:27:33","19-08-2025 17:29:4=
9","Site went down because SS IHS & SS Anselme are on site for work (swap o=
f MPR)//End of work","Mba Lazare Herve","Installation Activity","Passive","=
Planned Activity","Installation Activity","Site went down because SS IHS & =
SS Anselme are on site for work (swap of MPR)//End of work","cedric.tiani@m=
atech-cameroun.com","70","19-08-2025 17:28:42","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005723418","N=
YOM 2 IHS","","19-08-2025 16:45:02","19-08-2025 16:40:53","19-08-2025 16:51=
:06","Active//No power issue on site ,site on Grid with Ubaie=3D52,2 V Synu=
phorien 675295205 Huawei is informed","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue on site ,site on Grid with Ubaie=3D52,2 V Synuphorien 67529=
5205 Huawei is informed","vanel.mbiada@matech-cameroun.com","251","19-08-20=
25 16:45:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0005723382","Abattoir=
","","19-08-2025 16:37:08","19-08-2025 16:32:29","19-08-2025 16:40:52","Cas=
caded Incident from TTO5928990","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work of SS HIS=
 Bernard Atangana on site(securing Transmission) //End of work","cedric.tia=
ni@matech-cameroun.com","279","19-08-2025 16:37:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005723384","Etoudi 2=
","","19-08-2025 16:37:08","19-08-2025 16:32:29","19-08-2025 16:40:52","Cas=
caded Incident from TTO5928990","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work of SS HIS=
 Bernard Atangana on site(securing Transmission) //End of work","cedric.tia=
ni@matech-cameroun.com","279","19-08-2025 16:37:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005723383","ETOUDI C=
HAPELLE","","19-08-2025 16:37:08","19-08-2025 16:32:29","19-08-2025 16:40:5=
2","Cascaded Incident from TTO5928990","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work of =
SS HIS Bernard Atangana on site(securing Transmission) //End of work","cedr=
ic.tiani@matech-cameroun.com","279","19-08-2025 16:37:08","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005723365","E=
toudi","IHS_YND_244, IHS_YND_694, IHS_YND_211","19-08-2025 16:34:40","19-08=
-2025 16:32:29","19-08-2025 16:40:52","Site went down due to work of SS HIS=
 Bernard Atangana on site(securing Transmission) //End of work","Fabrice Po=
uakam","Installation Activity","Passive","Planned Activity","Installation A=
ctivity","Site went down due to work of SS HIS Bernard Atangana on site(sec=
uring Transmission) //End of work","vanel.mbiada@matech-cameroun.com","132"=
,"19-08-2025 16:34:40","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005722996","Lad=
a I Yde","","19-08-2025 15:34:44","19-08-2025 15:33:34","19-08-2025 15:44:4=
7","Site went down because SS IHS & SS Anselme are on site for work (swap o=
f MPR) //End of work","Mba Lazare Herve","Installation Activity","Passive",=
"Planned Activity","Installation Activity","Site went down because SS IHS &=
 SS Anselme are on site for work (swap of MPR) //End of work","cedric.tiani=
@matech-cameroun.com","71","19-08-2025 15:34:44","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005722483","Sim=
e Building","","19-08-2025 14:09:09","19-08-2025 14:07:42","19-08-2025 14:1=
5:10","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","loic.noumsi@=
matech-cameroun.com","88","19-08-2025 14:09:09","MATECH CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0005721828","B=
ISCUITERIE","","19-08-2025 12:06:16","19-08-2025 12:03:08","19-08-2025 12:0=
6:34","No power issue, site is on Grid with Ubaie=3D51.8 V The TX FME Mbah =
Hosiah (674007438) from Huawei is informed","Paul BIBOUM","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue, site is on Grid with Ubaie=3D51.8 V The TX FME Mbah Hosiah (6740=
07438) from Huawei is informed","loic.noumsi@matech-cameroun.com","190","19=
-08-2025 12:06:16","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005721822","O=
bili Carrefour","","19-08-2025 12:04:37","19-08-2025 12:03:15","19-08-2025 =
12:06:05","Grid outage site went down due to grid fluctuation and no RCP//g=
rid power stabilized","Paul BIBOUM","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Grid outage site went down due to grid f=
luctuation and no RCP//grid power stabilized","loic.noumsi@matech-cameroun.=
com","83","19-08-2025 12:04:37","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005721754","Lad=
a I Yde","","19-08-2025 11:49:37","19-08-2025 11:48:32","19-08-2025 13:54:2=
7","Site went down because SS IHS & SS Anselme were on site for work (swap =
of MPR) // End of work","Mba Lazare Herve","Installation Activity","Passive=
","Planned Activity","Installation Activity","Site went down because SS IHS=
 & SS Anselme were on site for work (swap of MPR) // End of work","loic.nou=
msi@matech-cameroun.com","67","19-08-2025 11:49:37","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0005721591","E=
koumdoum","","19-08-2025 11:27:33","19-08-2025 11:22:22","19-08-2025 12:19:=
21","site went down due to work of Aristide Mbida//657236711 (TSA) they wer=
e performing a Swap a radio // End of work","Albran Byorel","Installation A=
ctivity","Passive","Planned Activity","Installation Activity","site went do=
wn due to work of Aristide Mbida//657236711 (TSA) they were performing a Sw=
ap a radio // End of work","loic.noumsi@matech-cameroun.com","313","19-08-2=
025 11:27:33","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005721291","NKO=
NGKARAK","","19-08-2025 10:26:05","19-08-2025 10:25:00","19-08-2025 21:57:1=
6","Site Went Down due to High temp because pierced radiator, PELLET pierce=
d, and cut cylinder head gasket // Radiator, head gasket, cylinder head rep=
laced","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","=
ACDG - Radiator","Site Went Down due to High temp because pierced radiator,=
 PELLET pierced, and cut cylinder head gasket // Radiator, head gasket, cyl=
inder head replaced","loic.noumsi@matech-cameroun.com","66","19-08-2025 10:=
26:05","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005721255","Sim=
e Building","","19-08-2025 10:16:43","19-08-2025 10:15:37","19-08-2025 10:2=
3:09","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","loic.noumsi@=
matech-cameroun.com","67","19-08-2025 10:16:43","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005720604","NKO=
NGKARAK","","19-08-2025 07:44:36","19-08-2025 07:36:30","19-08-2025 08:08:1=
7","Site went down because Gen started and stopped due to pierced pellet //=
 he glued the Pellet and Manually Started The Gen","TIENTCHEU NZETCHIEU GAE=
L","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","Site went dow=
n because Gen started and stopped due to pierced pellet // he glued the Pel=
let and Manually Started The Gen","loic.noumsi@matech-cameroun.com","487","=
19-08-2025 07:44:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0005720484","LOBO MTN=
","IHS_YND_783, IHS_YND_714, IHS_YND_713","19-08-2025 07:12:36","19-08-2025=
 01:22:59","19-08-2025 07:18:44","Backtracking//Site went down because gen =
started and stopped due to alarm ""undervoltage"" // He reset it, site on G=
en","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Backtracking//Site went down because gen started and st=
opped due to alarm ""undervoltage"" // He reset it, site on Gen","franck.nk=
omot@matech-cameroun.com","20977","19-08-2025 07:12:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0005720482","Lobo 2",=
"","19-08-2025 07:12:35","19-08-2025 01:22:59","19-08-2025 07:18:44","Casca=
ded Incident from TTO5924749 - Cascade Removed From TTO5924749","TIENTCHEU =
NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Cascade Passi=
ve","Cascaded Incident from TTO5924749 - Cascade Removed From TTO5924749","=
franck.nkomot@matech-cameroun.com","20976","19-08-2025 07:12:35","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0005720483","Ekekam",=
"","19-08-2025 07:12:35","19-08-2025 01:22:59","19-08-2025 07:18:44","Casca=
ded Incident from TTO5924749 - Cascade Removed From TTO5924749","TIENTCHEU =
NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Cascade Passi=
ve","Cascaded Incident from TTO5924749 - Cascade Removed From TTO5924749","=
franck.nkomot@matech-cameroun.com","20976","19-08-2025 07:12:35","MATECH CM=
R"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005720262","Nsi=
malen MTN","","19-08-2025 06:14:32","19-08-2025 06:04:59","19-08-2025 07:05=
:59","Grid outage, site went down because gen failed to started due to pear=
 faulty // He changed pear and gen manually started","Albran Byorel","Fuel =
Outage (Probable)","Passive","Diesel","Fuel Line Issue","Grid outage, site =
went down because gen failed to started due to pear faulty // He changed pe=
ar and gen manually started","franck.nkomot@matech-cameroun.com","3588","19=
-08-2025 06:14:32","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005719535","NKO=
NGKARAK","","19-08-2025 01:32:17","19-08-2025 01:22:59","19-08-2025 07:18:4=
4","cascaded site ","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","cascaded site ","franck.nkomot@matech-c=
ameroun.com","559","19-08-2025 01:32:17","MATECH CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0005719437","F=
ebe Village","","19-08-2025 01:08:31","19-08-2025 00:09:59","19-08-2025 01:=
57:59","The technician of DOWEN (679161144) is on site for work (SWAP OF BA=
Y) // End of work","Mboua Thierry","Installation Activity","Passive","Plann=
ed Activity","Installation Activity","The technician of DOWEN (679161144) i=
s on site for work (SWAP OF BAY) // End of work","franck.nkomot@matech-came=
roun.com","3513","19-08-2025 01:08:31","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005719155","Mim=
boman4","","18-08-2025 23:13:54","18-08-2025 23:08:49","18-08-2025 23:14:49=
","Grid fluctuations, site went down because Gen failed to start due to gri=
d bad voltage // Site stabilized","Mba Lazare Herve","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuations, site=
 went down because Gen failed to start due to grid bad voltage // Site stab=
ilized","franck.nkomot@matech-cameroun.com","307","18-08-2025 23:13:54","MA=
TECH CMR"
"Closed Complete","Warning","CTR_242","IHS_YND_059","NOCINC0005719110","E-P=
oste 2","","18-08-2025 22:53:48","","","HIGH TEMP // The technician opened =
the shelter","Paul BIBOUM","Warning","Warning","ENVIRONMENT","Warning - Hig=
h Temperature","HIGH TEMP // The technician opened the shelter","franck.nko=
mot@matech-cameroun.com","589","18-08-2025 22:53:48","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005718885","NYO=
M FACE MAETUR","","18-08-2025 21:58:04","18-08-2025 21:57:57","18-08-2025 2=
2:48:57","Site went down due to insufficiency of rectifiers on site // He a=
dded 01 rectifier, site stabilized on Grid","Fabrice Pouakam","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down due to insuf=
ficiency of rectifiers on site // He added 01 rectifier, site stabilized on=
 Grid","cedric.tiani@matech-cameroun.com","9","18-08-2025 21:58:04","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0005718837","N=
kolmesseng","IHS_YND_190","18-08-2025 21:45:19","18-08-2025 21:39:12","18-0=
8-2025 22:25:12","Site went down due do disjunction at PWC//We made a bridg=
e with CB (125A) and site on Grid","Siligap Boris","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went dow=
n due do disjunction at PWC//We made a bridge with CB (125A) and site on Gr=
id","vanel.mbiada@matech-cameroun.com","368","18-08-2025 21:45:19","MATECH =
CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0005718819","N=
gousso-II","","18-08-2025 21:40:39","18-08-2025 21:39:12","18-08-2025 22:25=
:12","","MFOUAGUEGUE MATHIEU","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Site went down due do disjunction at PWC//We made a brid=
ge with CB (125A) and site on Grid","vanel.mbiada@matech-cameroun.com","702=
","18-08-2025 21:40:39","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005718776","Nko=
abang2","","18-08-2025 21:32:58","18-08-2025 21:27:48","18-08-2025 23:29:48=
","Grid outage, site went down due to Gen overload (22KVA, 330A), SS Blaise=
 IHS is informed// He reduced the load and put site on GE","Mba Lazare Herv=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, =
site went down due to Gen overload (22KVA, 330A), SS Blaise IHS is informed=
// He reduced the load and put site on GE","cedric.tiani@matech-cameroun.co=
m","312","18-08-2025 21:32:58","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005718745","N=
kolondom","","18-08-2025 21:27:01","18-08-2025 21:25:54","18-08-2025 22:11:=
42","Grid fluctuation, site went down because Gen failed to start due to gr=
id bad voltage // He bypass Grid, Site stabilized","Fabrice Pouakam","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation, site went down because Gen failed to start due to grid bad volta=
ge // He bypass Grid, Site stabilized","vanel.mbiada@matech-cameroun.com","=
69","18-08-2025 21:27:01","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005718714","NYO=
M FACE MAETUR","","18-08-2025 21:17:56","18-08-2025 21:17:45","18-08-2025 2=
1:32:10","Site went down due to rectifiers Alarming on site //He reset it a=
nd site on Grid ","Fabrice Pouakam","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down due to rectifiers Alarming on site //H=
e reset it and site on Grid ","cedric.tiani@matech-cameroun.com","12","18-0=
8-2025 21:17:56","MATECH CMR"
"Closed Complete","Site Down","T0573","IHS_YND_387","NOCINC0005718611","Tal=
la Monatele","","18-08-2025 20:58:54","18-08-2025 20:50:43","18-08-2025 21:=
01:19","Grid outage, Site went down before Gen start due to poor backup// G=
en automatically started","Parker Tchoup","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup// Gen automatically started","cedric.tiani@=
matech-cameroun.com","492","18-08-2025 20:58:54","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005718497","Nko=
lnda","","18-08-2025 20:41:52","18-08-2025 20:39:41","18-08-2025 21:53:41",=
"Grid fluctuation, site went down before Gen start due to poor battery back=
up // Grid return","Albran Byorel","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid fluctuation, site went down before=
 Gen start due to poor battery backup // Grid return","cedric.tiani@matech-=
cameroun.com","132","18-08-2025 20:41:52","MATECH CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0005718458","F=
ebe Village","","18-08-2025 20:34:32","18-08-2025 20:32:26","18-08-2025 20:=
35:58","Site went down sue to work of FME  BIGANCE (679161144 ) of DOWEN se=
rvice on site (SWAPP OF PWC and GEN)//End of work","Mboua Thierry","Install=
ation Activity","Passive","Planned Activity","Installation Activity","Site =
went down sue to work of FME  BIGANCE (679161144 ) of DOWEN service on site=
 (SWAPP OF PWC and GEN)//End of work","vanel.mbiada@matech-cameroun.com","1=
27","18-08-2025 20:34:32","MATECH CMR"
"Closed Complete","Site Down","T0107","IHS_YND_271","NOCINC0005717994","Yon=
a Hotel","","18-08-2025 18:54:11","18-08-2025 18:52:04","18-08-2025 19:08:2=
7","Access Issue during the night due to Landlord (Grid outage,Site went be=
cause Gen failed to start (investigation ongoing)//Grid return) ","TIENTCHE=
U NZETCHIEU GAEL","Access Denial","Lease Or Legal","Landlord Related Issues=
","Access Issue - Land Lord","Access Issue during the night due to Landlord=
 (Grid outage,Site went because Gen failed to start (investigation ongoing)=
//Grid return) ","cedric.tiani@matech-cameroun.com","128","18-08-2025 18:54=
:11","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005717964","Hop=
ital Central","","18-08-2025 18:45:59","18-08-2025 18:45:00","18-08-2025 18=
:45:59","site went down due to insufficient rectifiers on site//Site stabil=
ised","","Equipment Repair","Passive","Rectifier","Rectifier Module","site =
went down due to insufficient rectifiers on site//Site stabilised","cedric.=
tiani@matech-cameroun.com","60","18-08-2025 18:45:59","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0005717849","E=
koumdoum","","18-08-2025 18:23:27","18-08-2025 18:16:15","18-08-2025 18:54:=
42","TX Issue, Ubaie50V site in Grid ; site went down due to work of Charke=
 Tchamou ZTE // End of work.","Albran Byorel","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","TX Issue, site we=
nt down due to work of Charke Tchamou ZTE // End of work","vanel.mbiada@mat=
ech-cameroun.com","433","18-08-2025 18:23:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005717643","ETOUDI C=
HAPELLE","","18-08-2025 17:48:32","18-08-2025 17:46:00","18-08-2025 17:48:5=
9","Cascaded Incident from TTO5922599","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active // No power issue site on =
grid with Ubaie: 52.9V, TX Fme Armand Nguetsa (699949553 /Huawei) is inform=
ed. Notice that it is a repetitive issue.","cedric.tiani@matech-cameroun.co=
m","152","18-08-2025 17:48:32","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005717642","Aba=
ttoir","IHS_YND_694","18-08-2025 17:48:13","18-08-2025 17:46:00","18-08-202=
5 17:48:59","Active // No power issue site on grid with Ubaie: 52.9V, TX Fm=
e Armand Nguetsa (699949553 /Huawei) is informed. Notice that it is a repet=
itive issue.","Fabrice Pouakam","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active // No power issue site o=
n grid with Ubaie: 52.9V, TX Fme Armand Nguetsa (699949553 /Huawei) is info=
rmed. Notice that it is a repetitive issue.","cedric.tiani@matech-cameroun.=
com","135","18-08-2025 17:48:13","MATECH CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0005717494","S=
cience","","18-08-2025 17:16:58","18-08-2025 17:13:49","18-08-2025 17:26:38=
","No power issue Ubaie=3D 56.2 V site on Grid The TX FME Mohamadou 6911444=
35// from huawei is informed. ","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue Ubaie=3D 56.2 V site on Grid The TX FME Mohamadou 691144435// fr=
om huawei is informed. ","vanel.mbiada@matech-cameroun.com","190","18-08-20=
25 17:16:58","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005717454","Feb=
e Village","","18-08-2025 17:08:31","18-08-2025 17:04:16","18-08-2025 17:10=
:51","Site went down sue to work of FME  BIGANCE (679161144 ) of DOWEN serv=
ice on site (SWAPP OF PWC and GEN)//End of work","Mboua Thierry","Installat=
ion Activity","Passive","Planned Activity","Installation Activity","Site we=
nt down sue to work of FME  BIGANCE (679161144 ) of DOWEN service on site (=
SWAPP OF PWC and GEN)//End of work","cedric.tiani@matech-cameroun.com","347=
","18-08-2025 17:08:31","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005717110","Nsi=
malen MTN","","18-08-2025 16:06:21","18-08-2025 16:04:13","18-08-2025 16:40=
:59","Grid outage gen failed to start due to water infiltration in the tank=
 // He purged it  and gen manually started","Albran Byorel","Fuel Outage (P=
robable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","Grid=
 outage gen failed to start due to water infiltration in the tank // He pur=
ged it  and gen manually started","cedric.tiani@matech-cameroun.com","129",=
"18-08-2025 16:06:21","MATECH CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0005716836","E=
kounou","","18-08-2025 15:19:04","18-08-2025 15:07:44","18-08-2025 15:47:25=
","No power issue U =3D53,5V site on Grid. The Tx FME Brice Tsague (6502140=
96 )from Huawei is informed.","Albran Byorel","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue U =3D54,5V site on Grid. The=
 Tx FME Brice Tsague (650214096 )from Huawei is informed.","vanel.mbiada@ma=
tech-cameroun.com","1037","18-08-2025 15:19:04","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0005716825","G=
SO","IHS_YND_067","18-08-2025 15:16:52","18-08-2025 15:07:44","18-08-2025 1=
6:47:25","No power issue U =3D54,5V site on Grid. The Tx FME Brice Tsague (=
650214096 )from Huawei is informed.","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue U =3D54,5V site on Grid. The Tx FME Brice Tsague (650214096 )from Huaw=
ei is informed.","olivier.kwedi@ihstowers.com","549","18-08-2025 15:16:52",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0005716823","N=
koa Ayos","","18-08-2025 15:16:41","18-08-2025 15:07:44","18-08-2025 15:47:=
25","","MINKA NICOLAS","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue U =3D54,5V site on Grid. The Tx FME Brice Tsague (6=
50214096 )from Huawei is informed.","vanel.mbiada@matech-cameroun.com","979=
","18-08-2025 15:16:41","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005716621","O=
LAMA","","18-08-2025 14:55:48","18-08-2025 14:46:59","18-08-2025 15:23:37",=
"Site went down due to refueling (Poor battery backup) // End of refueling"=
,"Fanda Brice","Equipment Replacement","Passive","Planned Activity","Planne=
d Activity - Passive","Site went down due to refueling (Poor battery backup=
) // End of refueling","vanel.mbiada@matech-cameroun.com","531","18-08-2025=
 14:55:48","MATECH CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0005716327","EBO=
M","","18-08-2025 14:03:58","18-08-2025 14:00:53","18-08-2025 14:12:11","Si=
te went down due to work of the Technician Rodrigue/695934760 (GRATO) on si=
te : Swapp pwc // End of work","Hyemafo Gildas","Installation Activity","Pa=
ssive","Planned Activity","Installation Activity","Site went down due to wo=
rk of the Technician Rodrigue/695934760 (GRATO) on site : Swapp pwc // End =
of work","loic.noumsi@matech-cameroun.com","186","18-08-2025 14:03:58","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0005716131","E=
BOM","","18-08-2025 13:32:36","18-08-2025 13:29:26","18-08-2025 13:39:46","=
Site went down due to work: Our Technician Rodrigue/695934760 (GRATO) worki=
ng Swapp pwc// End of Work","Hyemafo Gildas","Installation Activity","Passi=
ve","Planned Activity","Installation Activity","Site went down due to work:=
 Our Technician Rodrigue/695934760 (GRATO) working Swapp pwc// End of Work"=
,"vanel.mbiada@matech-cameroun.com","191","18-08-2025 13:32:36","MATECH CMR=
"
"Closed Complete","Warning","T0843","IHS_YND_719","NOCINC0005715882","TSING=
A VILLAGE 2","","18-08-2025 12:49:34","","","Site went down due to fuel sho=
rtage // refuelling done","Delor Telezing","Warning","Warning","DIESEL","Wa=
rning - Low Fuel Level","Site went down due to fuel shortage // refuelling =
done","loic.noumsi@matech-cameroun.com","2","18-08-2025 12:49:34","MATECH C=
MR"
"Closed Complete","Warning","T1287","IHS_YND_223","NOCINC0005715835","Febe =
Village","","18-08-2025 12:41:47","","","Site Alarming due to Grid outage /=
/ Gen start automatically","Mboua Thierry","Warning","Warning","POWER","War=
ning - Site on Battery","Site Alarming due to Grid outage // Gen start auto=
matically","vanel.mbiada@matech-cameroun.com","7","18-08-2025 12:41:47","MA=
TECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005715651","Aba=
ttoir","IHS_YND_694, IHS_YND_211","18-08-2025 12:14:11","18-08-2025 11:58:5=
7","18-08-2025 12:00:36","Active // No power issue site on grid with Ubaie:=
 52.9V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. Notice that =
it is a repetitive issue.","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power=
 issue site on grid with Ubaie: 52.9V, TX Fme Armand Nguetsa (699949553 /Hu=
awei) is informed. Notice that it is a repetitive issue.","loic.noumsi@mate=
ch-cameroun.com","916","18-08-2025 12:14:11","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0005715465","Ole=
mbe MTN","","18-08-2025 11:38:54","11-08-2025 04:38:53","11-08-2025 11:58:2=
5","Bactracking Site sent down due to insufficiency of rectifiers //We rese=
t rectifiers site on grid ","Fabrice Pouakam","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","Bactracking Site sent down due to insuffici=
ency of rectifiers //We reset rectifiers site on grid ","mouliom.anselme@ma=
tech-cameroun.com","630002","18-08-2025 11:38:54","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005715379","Mon=
tee-Jouvence-II","","18-08-2025 11:26:35","11-08-2025 20:06:05","11-08-2025=
 20:44:26","Bactracking No power issue site on grid with U=3D53.6v.site up =
at 08:44 PM","Hyemafo Gildas","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Bactracking No power issue site o=
n grid with U=3D53.6v.site up at 08:44 PM","mouliom.anselme@matech-cameroun=
.com","573632","18-08-2025 11:26:35","MATECH CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0005715323","Nko=
mo II","","18-08-2025 11:16:47","13-08-2025 08:35:52","13-08-2025 08:50:58"=
,"Bactracking No power issue site on grid with U=3D53.5v site up  up at 08:=
50 AM","Albran Byorel","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Bactracking No power issue site on grid =
with U=3D53.5v site up  up at 08:50 AM","mouliom.anselme@matech-cameroun.co=
m","441656","18-08-2025 11:16:47","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005715313","TON=
GOLO SNEC","","18-08-2025 11:14:25","18-08-2025 11:13:16","18-08-2025 11:52=
:56","Site went down due to rectifiers dysfunctionning //He reset rectifier=
s, site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to rectifiers dysfunctionning //He =
reset rectifiers, site on Grid","loic.noumsi@matech-cameroun.com","70","18-=
08-2025 11:14:25","MATECH CMR"
"Closed Complete","Site Down","T1591","IHS_YND_172","NOCINC0005715292","Tra=
dex-Nkomo","","18-08-2025 11:11:04","13-08-2025 08:42:43","13-08-2025 08:48=
:22","Bactracking(No power issue site on grid with U=3D53.5V .Site up at 08=
:48 AM)","Albran Byorel","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Bactracking(No power issue site on gri=
d with U=3D53.5V .Site up at 08:48 AM)","mouliom.anselme@matech-cameroun.co=
m","440902","18-08-2025 11:11:04","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005715168","Mok=
olo Yaounde","","18-08-2025 11:00:23","18-08-2025 10:58:14","18-08-2025 11:=
00:33","Active // No power issue Ubaie: 54.7 V site on grid. TX FME Brice T=
sague (650214096) from HUAWEI is informed","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No powe=
r issue Ubaie: 54.7 V site on grid. TX FME Brice Tsague (650214096) from HU=
AWEI is informed","loic.noumsi@matech-cameroun.com","131","18-08-2025 11:00=
:23","MATECH CMR"
"Closed Complete","Warning","T1625","IHS_YND_204","NOCINC0005715161","TONGO=
LO SNEC","","18-08-2025 10:59:20","","","Site went down due to rectifiers d=
ysfunctionning //He reset rectifiers, site on Grid","Fabrice Pouakam","Warn=
ing","Warning","POWER","Warning - Rectifier Module","Site went down due to =
rectifiers dysfunctionning //He reset rectifiers, site on Grid","loic.noums=
i@matech-cameroun.com","2","18-08-2025 10:59:20","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005715089","Tou=
ring Club International","","18-08-2025 10:53:59","13-08-2025 11:21:27","13=
-08-2025 11:28:23","Bactracking  No power issue site on grid with U=3D53.2v=
 site up at 11:28 AM","Albran Byorel","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Bactracking  No power iss=
ue site on grid with U=3D53.2v site up at 11:28 AM","mouliom.anselme@matech=
-cameroun.com","430353","18-08-2025 10:53:59","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005715068","Par=
adis Hotel","","18-08-2025 10:50:32","16-08-2025 08:44:35","16-08-2025 08:5=
0:44","(Bactracking) Site went down due to iinsuffisency of rectifiers //We=
 add one recrtifier and site on grid ","Siligap Boris","Equipment Repair","=
Passive","Rectifier","Rectifier Module","(Bactracking) Site went down due t=
o iinsuffisency of rectifiers //We add one recrtifier and site on grid ","m=
ouliom.anselme@matech-cameroun.com","180358","18-08-2025 10:50:32","MATECH =
CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0005715033","Bas=
tos Ekoudou","","18-08-2025 10:44:37","17-08-2025 17:30:37","17-08-2025 18:=
00:03","Grid outage.gen failed to start due to poor backup//Gen start autom=
atically(Bactracking)","Mboua Thierry","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage.gen failed to start due=
 to poor backup//Gen start automatically(Bactracking)","mouliom.anselme@mat=
ech-cameroun.com","62041","18-08-2025 10:44:37","MATECH CMR"
"Closed Complete","Warning","T0183","IHS_YND_184","NOCINC0005715021","Nkolm=
esseng","","18-08-2025 10:41:24","",""," High temp alarm // Door shelter op=
en","Siligap Boris","Warning","Warning","ENVIRONMENT","Warning - High Tempe=
rature"," High temp alarm // Door shelter open","loic.noumsi@matech-camerou=
n.com","10","18-08-2025 10:41:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_804","NOCINC0005714957","BEATITUD=
E ENTR=C9E PAVE","","18-08-2025 10:23:05","18-08-2025 10:16:03","18-08-2025=
 11:15:17","Cascaded Incident from TTO5919590","TIENTCHEU NZETCHIEU GAEL","=
Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage,=
 site went down because Gen failed to start due to fuel shortage // Refuell=
ing done","loic.noumsi@matech-cameroun.com","422","18-08-2025 10:23:05","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_223","NOCINC0005714958","Febe Vil=
lage","","18-08-2025 10:23:05","18-08-2025 10:16:03","18-08-2025 11:15:17",=
"Cascaded Incident from TTO5919590","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e Gen failed to start due to fuel shortage // Refuelling done","loic.noumsi=
@matech-cameroun.com","422","18-08-2025 10:23:05","MATECH CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0005714928","L=
eboudi","IHS_YND_804, IHS_YND_223","18-08-2025 10:17:32","18-08-2025 10:16:=
03","18-08-2025 11:15:17","Grid outage, site went down because Gen failed t=
o start due to fuel shortage // Refuelling done","TIENTCHEU NZETCHIEU GAEL"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, site went d=
own because Gen failed to start due to fuel shortage // Refuelling done","v=
anel.mbiada@matech-cameroun.com","90","18-08-2025 10:17:32","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005714504","Nko=
lfoulou CSD MTN","","18-08-2025 09:06:23","18-08-2025 09:04:12","18-08-2025=
 09:08:42","Active//No power issue site with Ubaie=3D50,5V site on gen. The=
 Tx FME Julien //693095849 from Huawei is informed","Siligap Boris","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue site with Ubaie=3D50,5V site on gen. The Tx FME=
 Julien //693095849 from Huawei is informed","loic.noumsi@matech-cameroun.c=
om","132","18-08-2025 09:06:23","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005714495","Ron=
d Point Express1114","","18-08-2025 09:04:33","18-08-2025 09:00:26","18-08-=
2025 09:03:07"," disjunction of PWC CB (63A) // He rearmed it ","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active: No power issue, site is on grid with Ubaie=3D54,7=
V, Mbah hosiah(699699694) from Huawei is informed","loic.noumsi@matech-came=
roun.com","248","18-08-2025 09:04:33","MATECH CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0005713968","BEA=
TITUDE ENTR=C9E PAVE","","18-08-2025 07:04:50","18-08-2025 07:03:45","18-08=
-2025 08:09:44","Grid outage, Site went down because Gen started and stoppe=
d due to ""High temp"" caused by the silencer // he opened the doors, site =
on GEN","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen",=
"ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site went dow=
n because Gen started and stopped due to ""High temp"" caused by the silenc=
er // he opened the doors","loic.noumsi@matech-cameroun.com","65","18-08-20=
25 07:04:50","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005713710","Nko=
lfoulou CSD MTN","","18-08-2025 05:45:06","18-08-2025 05:39:58","18-08-2025=
 07:06:17","Grid outage, site went down due to Grid bad voltage (lack of 02=
 phases) // He bypassed Grid and started Gen manually","Siligap Boris","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
outage, site went down due to Grid bad voltage (lack of 02 phases) // He by=
passed Grid and started Gen manually","gerard.tchangoue@matech-cameroun.com=
","309","18-08-2025 05:45:06","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005713697","N=
koabang Ebolmedjock","","18-08-2025 05:41:43","18-08-2025 05:32:33","18-08-=
2025 08:33:19","Grid outage site went down because Gen failed to start due =
to Gen battery discharged causing by charging alternator faulty // Gen manu=
ally started with external battery","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - Charging Alternator","Grid outage site went dow=
n because Gen failed to start due to Gen battery discharged causing by char=
ging alternator faulty // Gen manually started with external battery","gera=
rd.tchangoue@matech-cameroun.com","552","18-08-2025 05:41:43","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0005713092","Mam=
bine","","18-08-2025 01:16:38","18-08-2025 01:08:26","18-08-2025 01:33:24",=
"Grid outage, site went down because gen ran until fuel shortage // Refueli=
ng done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage, site went down because gen ran until fuel shortage // Refuelling=
 done","gerard.tchangoue@matech-cameroun.com","493","18-08-2025 01:16:38","=
MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005713048","N=
kolso","","18-08-2025 01:05:44","18-08-2025 01:00:29","18-08-2025 03:06:46"=
,"Site went down because CB rectifiers tripped // CB put back on ","TIENTCH=
EU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier","Rectifier - Ci=
rcuit Breaker","Site went down because CB rectifiers tripped // CB put back=
 on ","gerard.tchangoue@matech-cameroun.com","317","18-08-2025 01:05:44","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0005712814","Y=
ona Hotel","","17-08-2025 23:18:57","17-08-2025 23:12:52","18-08-2025 00:05=
:04","Access issue during the Night because it is a school.Site went down b=
ecause Gen failed to start due to Grid bad voltage on site // Eneo stabilis=
ed","TIENTCHEU NZETCHIEU GAEL","Access Denial","Lease Or Legal","Landlord R=
elated Issues","Access Issue - Land Lord","Access issue during the Night be=
cause it is a school.Site went down because Gen failed to start due to Grid=
 bad voltage on site // Eneo stabilised","gerard.tchangoue@matech-cameroun.=
com","366","17-08-2025 23:18:57","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005712361","Ona=
ngondi (melen bikop)","","17-08-2025 21:16:31","17-08-2025 18:14:22","17-08=
-2025 21:34:38","Site went down because Gen failed to start due to Hybrid s=
ystem dysfunctioning// He reset it and Gen manually started","Fanda Brice",=
"Equipment Repair","Passive","Hybrid","Hybrid Module","Site went down becau=
se Gen failed to start due to Hybrid system dysfonction// He reset it and G=
en manually started","edwige.kapawo@matech-cameroun.com","10930","17-08-202=
5 21:16:31","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005712252","C=
NR","","17-08-2025 20:52:35","17-08-2025 20:52:31","17-08-2025 20:53:34","G=
rid outage, Site went down before Gen start due to poor backup // Grid retu=
rn","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Battery Low","Grid outage, Site went down before Gen start due to po=
or backup // Grid return","edwige.kapawo@matech-cameroun.com","5","17-08-20=
25 20:52:35","MATECH CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0005712251","Nko=
lbisson","","17-08-2025 20:52:27","17-08-2025 20:47:12","17-08-2025 22:18:2=
2","Site went down because Gen failed to start due to Grid bad voltage on s=
ite // Eneo stabilised","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Site went down because Ge=
n failed to start due to Grid bad voltage on site // Eneo stabilised","fran=
ck.nkomot@matech-cameroun.com","316","17-08-2025 20:52:27","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005712206","Bit=
eng-Maetur","","17-08-2025 20:42:01","17-08-2025 20:35:52","17-08-2025 21:1=
9:22","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","edwige.=
kapawo@matech-cameroun.com","371","17-08-2025 20:42:01","MATECH CMR"
"Closed Complete","Site Down","T0107","IHS_YND_271","NOCINC0005712170","Yon=
a Hotel","","17-08-2025 20:34:16","17-08-2025 20:33:10","17-08-2025 23:06:1=
9","Site went down because Gen failed to start due to Grid bad voltage on s=
ite // Eneo stabilised","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Site went down because Ge=
n failed to start due to Grid bad voltage on site // Eneo stabilised","edwi=
ge.kapawo@matech-cameroun.com","67","17-08-2025 20:34:16","MATECH CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0005712126","N=
kolkoumou OCM","","17-08-2025 20:25:26","17-08-2025 20:17:16","17-08-2025 2=
2:18:16","Site went down because Gen failed to start due to Grid bad voltag=
e and No RCP on site // He bypass the Grid and Gen manaually started","TIEN=
TCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Site went down because Gen failed to start due to Grid=
 bad voltage and No RCP on site // He bypass the Grid and Gen manaually sta=
rted","edwige.kapawo@matech-cameroun.com","491","17-08-2025 20:25:26","MATE=
CH CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0005712116","Nko=
lbisson","IHS_YND_763","17-08-2025 20:21:38","17-08-2025 20:18:33","17-08-2=
025 20:25:33","Site went down because Gen failed to start due to Grid bad v=
oltage on site // He bypass the Grid and Gen manually started","TIENTCHEU N=
ZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Site went down because Gen failed to start due to Grid bad vo=
ltage on site // He bypass the Grid and Gen manually started","franck.nkomo=
t@matech-cameroun.com","186","17-08-2025 20:21:38","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005711840","N=
kolbi-Boss","","17-08-2025 19:30:26","17-08-2025 19:21:59","17-08-2025 21:5=
5:57","Active//No power issue on site Ubaie:53.3 V site on GRID. The FME TX=
 Mohamadou (691144435)from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site Ubaie:53.3 V site on GRID. The FM=
E TX Mohamadou (691144435)from Huawei is informed","edwige.kapawo@matech-ca=
meroun.com","508","17-08-2025 19:30:26","MATECH CMR"
"Closed Complete","Warning","T0292","IHS_YND_231","NOCINC0005711766","Nkols=
o","","17-08-2025 19:18:49","","","HIGH TEMP // The technician opened the s=
helter","TIENTCHEU NZETCHIEU GAEL","Warning","Warning","ENVIRONMENT","Warni=
ng - High Temperature","HIGH TEMP // The technician opened the shelter","fr=
anck.nkomot@matech-cameroun.com","2883","17-08-2025 19:18:49","MATECH CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0005711627","N=
kolbisson usine des eaux","","17-08-2025 18:47:34","17-08-2025 18:46:59","1=
7-08-2025 18:53:17","Site went down because Gen failed to start due to Grid=
 bad voltage and No RCP on site // He bypass the Grid and Gen manaually sta=
rted","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Site went down because Gen failed to start =
due to Grid bad voltage and No RCP on site // He bypass the Grid and Gen ma=
naually started","edwige.kapawo@matech-cameroun.com","35","17-08-2025 18:47=
:34","MATECH CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0005711598","N=
kolkoumou OCM","","17-08-2025 18:44:58","17-08-2025 18:43:59","17-08-2025 1=
9:01:00","Site went down because Gen failed to start due to Grid bad voltag=
e and No RCP on site // He bypass the Grid and Gen manaually started","TIEN=
TCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Site went down because Gen failed to start due to Grid=
 bad voltage and No RCP on site // He bypass the Grid and Gen manaually sta=
rted","edwige.kapawo@matech-cameroun.com","60","17-08-2025 18:44:58","MATEC=
H CMR"
"Closed Complete","Site Down","T0537","IHS_YND_225","NOCINC0005711494","Sci=
ence","","17-08-2025 18:25:30","17-08-2025 18:21:08","17-08-2025 19:23:36",=
"Site went down because Gen failed to start due to Grid bad //He bypassed G=
rid and manual. Power issue resolved at OCM but remains down at OCM Mohamad=
ou (691144435/Huawei) is informed.","TIENTCHEU NZETCHIEU GAEL","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Site went dow=
n because Gen failed to start due to Grid bad //He bypassed Grid and manual=
. Power issue resolved at OCM but remains down at OCM. Mohamadou (691144435=
/Huawei) is informed.","franck.nkomot@matech-cameroun.com","262","17-08-202=
5 18:25:30","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005711313","C=
NR","","17-08-2025 17:50:29","17-08-2025 17:47:22","17-08-2025 17:49:29","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
 automatically","Mboua Thierry","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup // Gen start automatically","edwige.kapawo@matech-cam=
eroun.com","188","17-08-2025 17:50:29","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005711264","NKO=
NGKARAK","","17-08-2025 17:40:40","17-08-2025 17:38:30","17-08-2025 17:51:3=
0","Grid outage, Site went down because Gen started and stopped due to High=
 temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, Site went down because Gen started and stop=
ped due to High temp alarm //He added water and Gen start manually","franck=
.nkomot@matech-cameroun.com","131","17-08-2025 17:40:40","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005711258","Mok=
olo Yaounde","","17-08-2025 17:39:45","17-08-2025 17:33:31","17-08-2025 17:=
51:31","Grid only, Grid Outage on site, no space to deploy MDGE // Grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid only, Grid Outage on site, no space to deploy MDGE // Grid return","f=
ranck.nkomot@matech-cameroun.com","376","17-08-2025 17:39:45","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005711254","Hop=
ital Central","","17-08-2025 17:39:05","17-08-2025 17:33:28","17-08-2025 17=
:50:28","Grid outage No Space to deploy a MDG,//Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No Spa=
ce to deploy a MDG,//Grid return","franck.nkomot@matech-cameroun.com","338"=
,"17-08-2025 17:39:05","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005711249","Sim=
e Building","","17-08-2025 17:37:41","17-08-2025 17:31:32","17-08-2025 17:3=
9:32","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","franck.nkomo=
t@matech-cameroun.com","370","17-08-2025 17:37:41","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005711240","Cit=
e des nations","","17-08-2025 17:37:02","17-08-2025 17:31:54","17-08-2025 1=
7:37:54","Grid outage, site went down before Gen started due to Poor batter=
y backup//Grid return","Paul BIBOUM","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before Ge=
n started due to Poor battery backup//Grid return","franck.nkomot@matech-ca=
meroun.com","309","17-08-2025 17:37:02","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0005711186","Nko=
lbisson usines des eaux 2","","17-08-2025 17:23:11","17-08-2025 17:13:59","=
17-08-2025 20:25:33","Grid fluctuation, Site went down because Gen failed t=
o start due to Grid bad voltage //He bypassed Grid and started Gen manually=
","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Grid fluctuation, Site went down because Gen fa=
iled to start due to Grid bad voltage //He bypassed Grid and started Gen ma=
nually","franck.nkomot@matech-cameroun.com","553","17-08-2025 17:23:11","MA=
TECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005710805","NKO=
NGKARAK","","17-08-2025 16:10:24","17-08-2025 16:05:14","17-08-2025 16:35:1=
4","Grid outage, Site went down because Gen started and stopped due to High=
 temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, Site went down because Gen started and stop=
ped due to High temp alarm //He added water and Gen start manually","franck=
.nkomot@matech-cameroun.com","311","17-08-2025 16:10:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0005710670","AFEME NO=
RD","","17-08-2025 15:41:13","17-08-2025 15:39:45","17-08-2025 16:51:45","A=
ctive; no power issue site on Grid with U=3D54,6 V;The fme TX Mohammadou 69=
1144435 of huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e; no power issue site on Grid with U=3D54,6 V;The fme TX Mohammadou 691144=
435 of huawei is informed","edwige.kapawo@matech-cameroun.com","88","17-08-=
2025 15:41:13","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005710666","N=
kolso","","17-08-2025 15:40:54","17-08-2025 15:39:45","17-08-2025 16:25:45"=
,"Site went down because Gen failed to start due to Grid bad voltage on sit=
e // Eneo stabilised","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Site went down because Gen =
failed to start due to Grid bad voltage on site // Eneo stabilised","edwige=
.kapawo@matech-cameroun.com","70","17-08-2025 15:40:54","MATECH CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0005710488","S=
cience","","17-08-2025 15:02:46","17-08-2025 14:58:35","17-08-2025 15:10:54=
","Active // No power issue, site is on grid with Ubaie=3D53.8V, Mohamadou(=
691144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active // No power issue, site is on grid with Ubaie=3D53.8V, Mohamadou(69=
1144435) from Huawei is informed.","edwige.kapawo@matech-cameroun.com","252=
","17-08-2025 15:02:46","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005710180","AKA=
K Nkozoa","","17-08-2025 13:55:08","17-08-2025 13:52:02","17-08-2025 14:57:=
55","Grid outage, site went down due to insufficiency of 01/03 rectifiers /=
/ He added one rectifier,","Fabrice Pouakam","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Grid outage, site went down due to insuffici=
ency of 01/03 rectifiers // He added one rectifier,","vanel.mbiada@matech-c=
ameroun.com","186","17-08-2025 13:55:08","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005710080","Aba=
ttoir","IHS_YND_694","17-08-2025 13:32:27","17-08-2025 13:30:19","17-08-202=
5 13:37:43","Active // No power issue site on grid with Ubaie: 53.4V, TX Fm=
e Armand Nguetsa (699949553 /Huawei) is informed. Notice that it is a repet=
itive issue.","Fabrice Pouakam","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active // No power issue site o=
n grid with Ubaie: 53.4V, TX Fme Armand Nguetsa (699949553 /Huawei) is info=
rmed. Notice that it is a repetitive issue.","vanel.mbiada@matech-cameroun.=
com","130","17-08-2025 13:32:27","MATECH CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0005710066","ETO=
UDI CHAPELLE","","17-08-2025 13:29:45","17-08-2025 13:30:19","17-08-2025 13=
:37:43","","Delor Telezing","Cascade Outage","Active","Cascade Active","Cas=
cade Active","Active // No power issue site on grid with Ubaie: 53.4V, TX F=
me Armand Nguetsa (699949553 /Huawei) is informed. Notice that it is a repe=
titive issue.","vanel.mbiada@matech-cameroun.com","163","17-08-2025 13:29:4=
5","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005709993","E=
SSOS OASIS 1111","","17-08-2025 13:13:46","17-08-2025 13:10:11","17-08-2025=
 13:15:15","Site went down due to work: Our Technician Bigans /696909086/DO=
WEN working on site (SWAP PWC,GENERATOR and DC BOX)// End WORK","Siligap Bo=
ris","Installation Activity","Passive","Planned Activity","Installation Act=
ivity","Site went down due to work: Our Technician Bigans /696909086/DOWEN =
working on site (SWAP PWC,GENERATOR and DC BOX)// End WORK","vanel.mbiada@m=
atech-cameroun.com","216","17-08-2025 13:13:46","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005709986","AKA=
K Nkozoa","","17-08-2025 13:12:34","17-08-2025 13:10:14","17-08-2025 13:30:=
01","Grid fluctuation, site went down because Gen failed to start due to gr=
id bad voltage // Grid stabilize","Fabrice Pouakam","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site w=
ent down because Gen failed to start due to grid bad voltage // Grid stabil=
ize","vanel.mbiada@matech-cameroun.com","140","17-08-2025 13:12:34","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005709852","MEHANDAN=
","","17-08-2025 12:57:26","17-08-2025 12:28:20","17-08-2025 13:29:49","Cas=
caded Incident from TTO5913990","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n ran until fuel shortage due to spillage // Refueling done","vanel.mbiada@=
matech-cameroun.com","1746","17-08-2025 12:57:26","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005709786","E=
SSOS OASIS 1111","","17-08-2025 12:43:34","17-08-2025 12:38:15","17-08-2025=
 12:57:11","Site went down due to work: Our Technician Bigans /696909086/DO=
WEN working on site (SWAP PWC,GENERATOR and DC BOX)//End of work","Siligap =
Boris","Installation Activity","Passive","Planned Activity","Installation A=
ctivity","Site went down due to work: Our Technician Bigans /696909086/DOWE=
N working on site (SWAP PWC,GENERATOR and DC BOX)//End of work","vanel.mbia=
da@matech-cameroun.com","320","17-08-2025 12:43:34","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005709734","Lad=
a I Yde","","17-08-2025 12:33:13","17-08-2025 12:31:47","17-08-2025 12:33:4=
4","Site down due to 03/05 Rectifier dysfuntionning // He reset it: site on=
 grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site down due to 03/05 Rectifier dysfuntionning // He reset it:=
 site on grid","vanel.mbiada@matech-cameroun.com","87","17-08-2025 12:33:13=
","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005709725","Odz=
a II OCM","IHS_YND_528","17-08-2025 12:30:59","17-08-2025 12:28:20","17-08-=
2025 13:30:12","Grid outage, site went down because gen ran until fuel shor=
tage due to spillage // Refueling done","Albran Byorel","Fuel Outage","Pass=
ive","Diesel","Diesel Outage","Grid outage, site went down because gen ran =
until fuel shortage due to spillage // Refueling done","vanel.mbiada@matech=
-cameroun.com","161","17-08-2025 12:30:59","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005709605","Lad=
a I Yde","","17-08-2025 12:02:35","17-08-2025 12:00:12","17-08-2025 12:02:1=
6","Site down due to 03/05 Rectifier dysfuntionning // He reset it: site on=
 grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site down due to 03/05 Rectifier dysfuntionning // He reset it:=
 site on grid","vanel.mbiada@matech-cameroun.com","144","17-08-2025 12:02:3=
5","MATECH CMR"
"Closed Complete","Warning","T1111","IHS_YND_118","NOCINC0005709480","ESSOS=
 OASIS 1111","","17-08-2025 11:35:10","","","Site alarming due to Grid fluc=
tuation // Grid stabilized","Siligap Boris","Warning","Warning","POWER","Wa=
rning - Site on Battery","Site alarming due to Grid fluctuation // Grid sta=
bilized","vanel.mbiada@matech-cameroun.com","4","17-08-2025 11:35:10","MATE=
CH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005709478","Aba=
ttoir","","17-08-2025 11:34:29","17-08-2025 11:29:04","17-08-2025 11:37:03"=
,"Active // No power issue site on grid with Ubaie: 52.9V, TX Fme Armand Ng=
uetsa (699949553 /Huawei) is informed. Notice that it is a repetitive issue=
.","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active // No power issue site on grid with=
 Ubaie: 52.9V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. Notic=
e that it is a repetitive issue.","vanel.mbiada@matech-cameroun.com","326",=
"17-08-2025 11:34:29","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005709072","Lad=
a I Yde","","17-08-2025 10:22:00","17-08-2025 10:17:53","17-08-2025 11:07:3=
0","Grid outage, site went down because gen failed to start due to Grid con=
tactor faulty // He bypass the Grid contactor and Site is on Gen","Mba Laza=
re Herve","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gri=
d outage, site went down because gen failed to start due to Grid contactor =
faulty // He bypass the Grid contactor and Site is on Gen","vanel.mbiada@ma=
tech-cameroun.com","248","17-08-2025 10:22:00","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005709063","ODZ=
A MINKAN EDIBI ASSI","","17-08-2025 10:18:33","17-08-2025 10:15:05","17-08-=
2025 10:23:39","ACTIVE//No power issue on site ,site on Grid with Ubaie=3D =
53V The Tx FME Leonel Adjep /655184876/From HUAWEI is informed","Albran Byo=
rel","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","ACTIVE//No power issue on site ,site on Grid with Ubaie=3D=
 53V The Tx FME Leonel Adjep /655184876/From HUAWEI is informed","vanel.mbi=
ada@matech-cameroun.com","210","17-08-2025 10:18:33","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005708661","Cit=
e des nations","","17-08-2025 09:02:14","17-08-2025 08:57:48","17-08-2025 0=
9:07:29","Grid outage and backup null // Gen started manually","Paul BIBOUM=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","ACTIVE//no power issue on site U=3D53.4V site on Grid, hosiah=
 674007438 of Huawei is informed","vanel.mbiada@matech-cameroun.com","267",=
"17-08-2025 09:02:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0005708515","Nsimalen=
 OCM","","17-08-2025 08:20:30","17-08-2025 08:12:40","17-08-2025 08:24:46",=
"Cascaded Incident from TTO5912613","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active // No power issue on site Ubai=
e =3D56V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei is =
informed","vanel.mbiada@matech-cameroun.com","470","17-08-2025 08:20:30","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0005708514","N=
kolda","IHS_YND_327","17-08-2025 08:20:00","17-08-2025 08:12:40","17-08-202=
5 08:24:46","Active // No power issue on site Ubaie =3D56V site on Grid. Th=
e TX FME Lionnel Adhex (655184876) from Huawei is informed","Albran Byorel"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active // No power issue on site Ubaie =3D56V site on Grid. Th=
e TX FME Lionnel Adhex (655184876) from Huawei is informed","vanel.mbiada@m=
atech-cameroun.com","441","17-08-2025 08:20:00","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005708215","Lad=
a I Yde","","17-08-2025 07:05:02","17-08-2025 07:03:28","17-08-2025 08:36:5=
2","Grid outage, site went down because gen failed to start due to Grid con=
tactor faulty // He bypass the Grid contactor and Site is on Grid","Mba Laz=
are Herve","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gr=
id outage, site went down because gen failed to start due to Grid contactor=
 faulty // He bypass the Grid contactor and Site is on Grid","vanel.mbiada@=
matech-cameroun.com","95","17-08-2025 07:05:02","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005707515","ESS=
OS OASIS 1111","","17-08-2025 03:13:05","17-08-2025 03:07:58","17-08-2025 0=
4:03:58","Grid outage, Site went down because Gen overload (17kva, 250A)// =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (17kva, 250A)=
// Grid return","gerard.tchangoue@matech-cameroun.com","308","17-08-2025 03=
:13:05","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005707307","ESS=
OS OASIS 1111","","17-08-2025 01:35:13","17-08-2025 01:25:59","17-08-2025 0=
1:47:59","Grid outage, Site went down because Gen overload (17kva, 250A)// =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (17kva, 250A)=
// Grid return","gerard.tchangoue@matech-cameroun.com","557","17-08-2025 01=
:35:13","MATECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0005707166","N=
koa Ayos","","17-08-2025 00:45:44","17-08-2025 00:45:35","17-08-2025 07:02:=
48","Grid bad voltage, Site went down because Gen failed to start due to AT=
S disfunction// He bypass the ATS and started Gen manualy","MINKA NICOLAS",=
"Equipment Repair","Passive","Control Panel","ATS Relay Faulty","Grid bad v=
oltage, Site went down because Gen failed to start due to ATS disfunction//=
 He bypass the ATS and started Gen manualy","gerard.tchangoue@matech-camero=
un.com","10","17-08-2025 00:45:44","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005707010","ESS=
OS OASIS 1111","","16-08-2025 23:44:58","16-08-2025 23:40:53","16-08-2025 2=
3:46:53","Grid outage, Site went down because Gen overload (17kva, 250A)// =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (17kva, 250A)=
// Grid return","gerard.tchangoue@matech-cameroun.com","246","16-08-2025 23=
:44:58","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005706829","N=
koabang Ebolmedjock","","16-08-2025 22:52:26","16-08-2025 22:46:10","16-08-=
2025 22:53:47","Site impacted by Nkolmesseng-Abom(CTR-711) Not Manager By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","Site impacted by Nkolmesseng-Abo=
m(CTR-711) Not Manager By IHS","gerard.tchangoue@matech-cameroun.com","378"=
,"16-08-2025 22:52:26","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005706820","Bit=
eng-Maetur","","16-08-2025 22:50:48","16-08-2025 22:46:41","16-08-2025 23:0=
3:54","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","gerard.=
tchangoue@matech-cameroun.com","249","16-08-2025 22:50:48","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0005706715","N=
kolda","IHS_YND_327","16-08-2025 22:23:24","16-08-2025 22:16:15","16-08-202=
5 22:57:04","Active // No power issue on site Ubaie =3D53.4V site on Grid. =
The TX FME Lionnel Adhex (655184876) from Huawei is informed","Albran Byore=
l","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active // No power issue on site Ubaie =3D53.4V site on Grid=
. The TX FME Lionnel Adhex (655184876) from Huawei is informed","gerard.tch=
angoue@matech-cameroun.com","430","16-08-2025 22:23:24","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005706284","Lad=
a I Yde","","16-08-2025 20:52:24","16-08-2025 20:42:59","16-08-2025 21:32:5=
9","Grid outage, site went down due to gen Overload(09KVA, 105A) // Site st=
abilized","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, site went down due to gen Overload(09KVA, 105A) /=
/ Site stabilized","franck.nkomot@matech-cameroun.com","3430","16-08-2025 2=
0:52:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0005705932","Nsimalen=
 OCM","","16-08-2025 19:21:47","16-08-2025 19:12:42","16-08-2025 20:58:44",=
"Cascaded Incident from TTO5909831","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active // No power issue on site Ubai=
e =3D54.4V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei i=
s informed","edwige.kapawo@matech-cameroun.com","545","16-08-2025 19:21:47"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0005705927","N=
kolda","IHS_YND_327","16-08-2025 19:20:28","16-08-2025 19:12:42","16-08-202=
5 20:58:44","Active // No power issue on site Ubaie =3D54.4V site on Grid. =
The TX FME Lionnel Adhex (655184876) from Huawei is informed","Albran Byore=
l","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active // No power issue on site Ubaie =3D54.4V site on Grid=
. The TX FME Lionnel Adhex (655184876) from Huawei is informed","edwige.kap=
awo@matech-cameroun.com","467","16-08-2025 19:20:28","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005705837","E=
SSOS OASIS 1111","","16-08-2025 19:04:23","16-08-2025 19:03:16","16-08-2025=
 19:05:49","Grid outage, Site went down because Gen overload (17kva, 250A)/=
/ Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage, Site went down because Gen overload (17kva, 250=
A)// Grid return","edwige.kapawo@matech-cameroun.com","68","16-08-2025 19:0=
4:23","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005705762","C=
NR","","16-08-2025 18:45:43","16-08-2025 18:43:36","16-08-2025 19:09:47","G=
rid outage, Site went down because Gen failed to start due to gen contactor=
 no excited // He excited gen contactor, and Grid return","Mboua Thierry","=
Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage=
, Site went down because Gen failed to start due to gen contactor no excite=
d // He excited gen contactor, and Grid return","edwige.kapawo@matech-camer=
oun.com","128","16-08-2025 18:45:43","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005705403","M=
arche Odza","","16-08-2025 17:47:24","16-08-2025 17:37:59","16-08-2025 18:0=
1:59","Site went down due to 3/4 rectifiers dysfunction//He reset hit, site=
 on Grid","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to 3/4 rectifiers dysfunction//He reset hit,=
 site on Grid","franck.nkomot@matech-cameroun.com","2975","16-08-2025 17:47=
:24","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005705278","Mam=
ch Building","","16-08-2025 17:25:19","16-08-2025 17:21:11","16-08-2025 17:=
37:11","Site went down because FME Herman (from GRATO/677 79 36 03) was on =
site for work (SWAP of BAY) // End of work","Mboua Thierry","Installation A=
ctivity","Passive","Planned Activity","Installation Activity","Site went do=
wn because FME Herman (from GRATO/677 79 36 03) was on site for work (SWAP =
of BAY) // End of work","franck.nkomot@matech-cameroun.com","249","16-08-20=
25 17:25:19","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005705082","M=
arche Odza","","16-08-2025 16:49:39","16-08-2025 16:37:29","16-08-2025 17:2=
7:39","Site went down due to 3/4 rectifiers dysfunction//He reset hit, site=
 on Grid","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to 3/4 rectifiers dysfunction//He reset hit,=
 site on Grid","edwige.kapawo@matech-cameroun.com","884","16-08-2025 16:49:=
39","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005704860","Sim=
e Building","","16-08-2025 16:04:01","16-08-2025 16:00:49","16-08-2025 16:0=
8:56","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","franck.nkomo=
t@matech-cameroun.com","193","16-08-2025 16:04:01","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005704853","C=
NR","","16-08-2025 16:02:57","16-08-2025 16:00:50","16-08-2025 17:57:50","G=
rid outage, Site went down because Gen failed to start due to gen contactor=
 no excited // He excited gen contactor, and Grid return","Mboua Thierry","=
Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage=
, Site went down because Gen failed to start due to gen contactor no excite=
d // He excited gen contactor, and Grid return","edwige.kapawo@matech-camer=
oun.com","128","16-08-2025 16:02:57","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005704545","E=
mombo","","16-08-2025 15:03:46","16-08-2025 15:01:40","16-08-2025 18:03:30"=
,"No power issue, site is on Grid with Ubaie=3D54,3V, TX FME Henri (6911450=
55) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue,=
 site is on Grid with Ubaie=3D54,3V, TX FME Henri (691145055) from Huawei i=
s informed","edwige.kapawo@matech-cameroun.com","127","16-08-2025 15:03:46"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005704534","F=
ouda-New","","16-08-2025 15:03:04","16-08-2025 14:57:59","16-08-2025 15:34:=
58","Site Went down due to  Rectifier dysfuntionning // He reset it: site o=
n grid","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site Went down due to  Rectifier dysfuntionning // He reset it: =
site on grid","edwige.kapawo@matech-cameroun.com","306","16-08-2025 15:03:0=
4","MATECH CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0005703760","B=
ISCUITERIE","","16-08-2025 12:27:38","16-08-2025 12:23:24","16-08-2025 12:3=
1:32","No power issue, site is on Grid with Ubaie=3D52 V The TX FME Mbah Ho=
siah (674007438) from Huawei is informed","Paul BIBOUM","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue, site is on Grid with Ubaie=3D52 V The TX FME Mbah Hosiah (67400743=
8) from Huawei is informed","vanel.mbiada@matech-cameroun.com","255","16-08=
-2025 12:27:38","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005703755","O=
bili Carrefour","","16-08-2025 12:26:26","16-08-2025 12:23:15","16-08-2025 =
12:34:13","Active//No power issue,site on Gen with Ubaie=3D47.3V The Tx Fme=
 Hosiah Mbah (674007438) of Huawei is informed.","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue,site on Gen with Ubaie=3D47.3V The Tx Fme Hosiah Mba=
h (674007438) of Huawei is informed.","vanel.mbiada@matech-cameroun.com","1=
92","16-08-2025 12:26:26","MATECH CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0005703580","BEA=
TITUDE ENTR=C9E PAVE","","16-08-2025 11:50:03","16-08-2025 11:48:50","16-08=
-2025 13:11:51","Grid outage, Site went down because Gen start and stopped =
due to ""High temp ""// he opened the doors","TIENTCHEU NZETCHIEU GAEL","Eq=
uipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, Site wen=
t down because Gen start and stopped due to ""High temp ""// he opened the =
doors","vanel.mbiada@matech-cameroun.com","74","16-08-2025 11:50:03","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005703496","N=
kolfon Cimencam","","16-08-2025 11:36:21","16-08-2025 11:33:06","16-08-2025=
 11:37:52","Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Grid return","vanel.mbiada@matech-cameroun.com",=
"198","16-08-2025 11:36:21","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005703440","Lad=
a I Yde","","16-08-2025 11:26:26","16-08-2025 11:24:12","16-08-2025 11:58:5=
0","grid outage, site went down due to gen Overload(09KVA, 105A) // Grid re=
turn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","grid outage, site went down due to gen Overload(09KVA, 105A) // Gr=
id return","vanel.mbiada@matech-cameroun.com","135","16-08-2025 11:26:26","=
MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005703264","E=
mombo","","16-08-2025 10:54:32","16-08-2025 10:30:20","16-08-2025 10:58:26"=
,"Grid outage, site went down because gen fails to start due to AVR faulty =
// He replaced AVR and gen manually started","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - AVR","Grid outage, site went down beca=
use gen fails to start due to AVR faulty // He replaced AVR and gen manuall=
y started.","vanel.mbiada@matech-cameroun.com","1453","16-08-2025 10:54:32"=
,"MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005703132","Aba=
ttoir","","16-08-2025 10:30:52","16-08-2025 10:23:16","16-08-2025 10:58:53"=
,"Active // No power issue site on grid with Ubaie: 53.4V, TX Fme Armand Ng=
uetsa (699949553 /Huawei) is informed. Notice that it is a repetitive issue=
.","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active // No power issue site on grid with=
 Ubaie: 53.4V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. Notic=
e that it is a repetitive issue.","vanel.mbiada@matech-cameroun.com","458",=
"16-08-2025 10:30:52","MATECH CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0005703054","ETO=
UDI CHAPELLE","","16-08-2025 10:16:02","16-08-2025 10:14:48","16-08-2025 10=
:16:29","ACTIVE No power issue Ubaie=3D51.2V site on Grid Armand Nguetsa (6=
99949553)from Huawei is informed,","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No p=
ower issue Ubaie=3D51.2V site on Grid Armand Nguetsa (699949553)from Huawei=
 is informed,","vanel.mbiada@matech-cameroun.com","76","16-08-2025 10:16:02=
","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005702714","E=
vodoula OCM","","16-08-2025 09:15:55","16-08-2025 09:14:45","16-08-2025 09:=
36:29","Grid outage, gen failed to start due to relay (12V) Ge faulty // He=
 bypass it and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","Control Panel","Relay","Grid Outage Site went down becau=
se Gen Failed to Start due to Relay 12V faulty // He bypass Relay and Manua=
lly Started the Gen","vanel.mbiada@matech-cameroun.com","71","16-08-2025 09=
:15:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_178","NOCINC0005702651","Emombo",=
"","16-08-2025 09:00:24","16-08-2025 08:57:33","16-08-2025 10:29:05","Grid =
outage, site went down because gen fails to start due to AVR faulty // He r=
eplaced AVR and gen manually started","Mba Lazare Herve","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen failed to start due to PWC ZTE malfunction // He reset controlle=
r and gen manually started","vanel.mbiada@matech-cameroun.com","171","16-08=
-2025 09:00:24","MATECH CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0005702639","Mim=
boman3","","16-08-2025 08:57:49","16-08-2025 08:57:33","16-08-2025 10:29:05=
","Grid outage, site went down because gen failed to start due to PWC ZTE m=
alfunction // He reset controller and gen manually started","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid outage, site went down because gen failed to start due to PWC ZTE mal=
function // He reset controller and gen manually started","vanel.mbiada@mat=
ech-cameroun.com","17","16-08-2025 08:57:49","MATECH CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0005701397","NYA=
NON/DEMBO","","16-08-2025 01:54:50","16-08-2025 01:49:40","16-08-2025 08:07=
:59","Grid outage, Site went down because Gen failed due to fuse of contact=
or gen faulty// He made a brigde of fuse, Site on gen","TIENTCHEU NZETCHIEU=
 GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid =
outage, Site went down because Gen failed due to fuse of contactor gen faul=
ty// He made a brigde of fuse, Site on gen","gerard.tchangoue@matech-camero=
un.com","311","16-08-2025 01:54:50","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005700617","Lad=
a I Yde","","15-08-2025 21:40:20","15-08-2025 21:39:59","15-08-2025 21:41:4=
0","site went down due to 02/4 rectifiers malfunction // rectifiers reset",=
"Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","site went down due to 02/4 rectifiers malfunction // rectifiers reset"=
,"edwige.kapawo@matech-cameroun.com","22","15-08-2025 21:40:20","MATECH CMR=
"
"Closed Complete","Site Down","T0210","IHS_YND_206","NOCINC0005700304","ARM=
P","","15-08-2025 20:43:21","15-08-2025 20:40:11","15-08-2025 21:20:22","Ac=
cess issues due to landlord Grid outage, Grid Ouatage (investigation ongoin=
g) // Grid return","Mboua Thierry","Access Denial","Lease Or Legal","Landlo=
rd Related Issues","Access Issue - Land Lord","Access issues due to landlor=
d Grid outage, Grid Ouatage (investigation ongoing) // Grid return","edwige=
.kapawo@matech-cameroun.com","191","15-08-2025 20:43:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0005699886","Dragage"=
,"","15-08-2025 19:24:21","15-08-2025 19:20:26","15-08-2025 21:06:54","Casc=
aded Incident from TTO5903137","Mboua Thierry","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Access issues due to landlord Grid outa=
ge, site went down because Gen failed to start (investigation ongoing) // G=
rid return","edwige.kapawo@matech-cameroun.com","235","15-08-2025 19:24:21"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0005699882","Bastos-B=
AT","","15-08-2025 19:22:31","15-08-2025 19:20:26","15-08-2025 21:06:54","C=
ascaded Incident from TTO5903137","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Access issues due to landlord Grid o=
utage, site went down because Gen failed to start (investigation ongoing) /=
/ Grid return","edwige.kapawo@matech-cameroun.com","125","15-08-2025 19:22:=
31","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005699878","ARM=
P Building","IHS_YND_192, IHS_YND_129","15-08-2025 19:21:32","15-08-2025 19=
:20:26","15-08-2025 21:06:54","Access issues due to landlord Grid outage, s=
ite went down because Gen failed to start (investigation ongoing) // Grid r=
eturn","Mboua Thierry","Access Denial","Lease Or Legal","Landlord Related I=
ssues","Access Issue - Land Lord","Access issues due to landlord Grid outag=
e, site went down because Gen failed to start (investigation ongoing) // Gr=
id return","edwige.kapawo@matech-cameroun.com","67","15-08-2025 19:21:32","=
MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005699480","N=
koabang2","","15-08-2025 18:12:23","15-08-2025 18:08:13","15-08-2025 19:58:=
13","Grid outage, Site went down due to Gen overload (22KVA, 330A), SS Blai=
se IHS is informed// Grid return","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to Gen=
 overload (22KVA, 330A), SS Blaise IHS is informed// Grid return","gerard.t=
changoue@matech-cameroun.com","252","15-08-2025 18:12:23","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005699343","M=
ambine","","15-08-2025 17:54:37","15-08-2025 17:13:06","15-08-2025 18:47:56=
","Site went down due to 01/03 Rectifier dysfuntionning // He reset it: Sit=
e on Gen","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down due to 01/03 Rectifier dysfuntionning // He reset =
it: Site on Gen","gerard.tchangoue@matech-cameroun.com","3139","15-08-2025 =
17:54:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005698682","Eseka To=
wn","","15-08-2025 15:52:46","15-08-2025 13:23:59","15-08-2025 14:23:17","C=
ascaded Incident from TTO5900817","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen start and stopped due to high temp caused by by pierced radator // He=
 added water and manually start the gen(Radiator to be repaired)","kouoh.je=
an@ihstowers.com","8927","15-08-2025 15:52:46","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005698371","Aba=
ttoir","IHS_YND_694, IHS_YND_211","15-08-2025 15:10:06","15-08-2025 15:04:0=
0","15-08-2025 15:10:46","Active // No power issue site on grid with Ubaie:=
 53.4V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. Notice that =
it is a repetitive issue.","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power=
 issue site on grid with Ubaie: 53.4V, TX Fme Armand Nguetsa (699949553 /Hu=
awei) is informed. Notice that it is a repetitive issue.","gerard.tchangoue=
@matech-cameroun.com","368","15-08-2025 15:10:06","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005698328","Lad=
a I Yde","","15-08-2025 15:02:02","15-08-2025 14:52:59","15-08-2025 16:11:1=
8","Active//No power issue on site ,site on Grid with Ubaie=3D54,3V The Tx =
FME Leonel Steve (655184876) from Huawei is informed.","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site ,site on Grid with Ubaie=3D54,3V =
The Tx FME Leonel Steve (655184876) from Huawei is informed.","franck.nkomo=
t@matech-cameroun.com","544","15-08-2025 15:02:02","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005697893","N=
koabang Ebolmedjock","","15-08-2025 13:55:03","15-08-2025 13:46:59","16-08-=
2025 13:47:22","Site impacted by Nkolmesseng-Abom(CTR-711) Not Manager By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","Site impacted by Nkolmesseng-Abo=
m(CTR-711) Not Manager By IHS","franck.nkomot@matech-cameroun.com","485","1=
5-08-2025 13:55:03","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005697804","E=
seka OCM","IHS_YND_378","15-08-2025 13:33:14","15-08-2025 13:23:59","15-08-=
2025 14:23:17","Grid outage, site went down because gen start and stopped d=
ue to high temp caused by by pierced radator // He added water and manually=
 start the gen(Radiator to be repaired)","Kemeni Franklin","Equipment Repai=
r","Passive","ACDG Gen","ACDG - High Engine Temp - Radiator Leakage","Grid =
outage, site went down because gen start and stopped due to high temp cause=
d by by pierced radator // He added water and manually start the gen(Radiat=
or to be repaired)","franck.nkomot@matech-cameroun.com","556","15-08-2025 1=
3:33:14","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005697666","Mok=
olo Yaounde","","15-08-2025 13:03:06","15-08-2025 12:59:51","15-08-2025 13:=
11:51","Grid only, Grid Outage on site, no space to deploy MDGE // Grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid only, Grid Outage on site, no space to deploy MDGE // Grid return","f=
ranck.nkomot@matech-cameroun.com","197","15-08-2025 13:03:06","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005696266","C=
NR","","15-08-2025 08:53:36","15-08-2025 08:48:14","15-08-2025 08:54:14","N=
o power issue site on Grid with U=3D54.3V Mohamadou from Huawei is informed=
","Mboua Thierry","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","No power issue site on Gen with U=3D54.8V Moh=
amadou from Huawei is informed","franck.nkomot@matech-cameroun.com","323","=
15-08-2025 08:53:36","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005696175","Mok=
olo Yaounde","","15-08-2025 08:40:40","15-08-2025 08:36:28","15-08-2025 09:=
54:28","Grid only, Grid Outage on site, no space to deploy MDGE // Grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid only, Grid Outage on site, no space to deploy MDGE // Grid return","f=
ranck.nkomot@matech-cameroun.com","254","15-08-2025 08:40:40","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005695858","Mvo=
g-Manga","","15-08-2025 07:36:02","15-08-2025 07:34:48","15-08-2025 08:28:4=
8","Site went down because Gen failed to start due to Grid bad voltage // H=
e reset ATS Grid and started Gen manually","Albran Byorel","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Site went down be=
cause Gen failed to start due to Grid bad voltage // He reset ATS and start=
ed Gen manually","franck.nkomot@matech-cameroun.com","76","15-08-2025 07:36=
:02","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005695667","N=
kolbi-Boss","","15-08-2025 06:55:13","15-08-2025 06:52:00","15-08-2025 07:0=
8:00","Grid outage, site went down before gen start due to poor battery bac=
kup // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before gen start due to poor battery backup // gen start autom=
atically","vanel.mbiada@matech-cameroun.com","195","15-08-2025 06:55:13","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005695080","N=
koabang Ebolmedjock","","15-08-2025 04:00:52","15-08-2025 03:56:39","15-08-=
2025 04:07:59","Grid outage, site went down because Gen started and stopped=
 due to Low oil pressure alarm // He reset gen card and gen manually starte=
d","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Grid outage, site went down because Gen started and stopped due =
to Low oil pressure alarm // He reset gen card and gen manually started","v=
anel.mbiada@matech-cameroun.com","255","15-08-2025 04:00:52","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005694664","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","15-08-2025 01:22:16","15-08-20=
25 01:19:06","15-08-2025 01:29:21","Active//No power issue on site ubaie=3D=
54,6V site on Gen The TX FME Mouhamadou //691144435// from Huawei is inform=
ed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site u=
baie=3D54,6V site on Gen The TX FME Mouhamadou //691144435// from Huawei is=
 informed","cedric.tiani@matech-cameroun.com","191","15-08-2025 01:22:16","=
MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005694445","O=
LAMA","","15-08-2025 00:35:12","15-08-2025 00:31:53","15-08-2025 00:41:35",=
"Active // No power issue on site Ubaie: 54.6V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue on site Ubaie: 54.6V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","vanel.mbiada@matech-cameroun.com","201","15-08-2=
025 00:35:12","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005694336","NKO=
NGKARAK","","15-08-2025 00:24:41","15-08-2025 00:20:24","15-08-2025 00:53:0=
2","Grid outage, Site went down because Gen started and stopped due to High=
 temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, Site went down because Gen started and stop=
ped due to High temp alarm //He added water and Gen start manually","cedric=
.tiani@matech-cameroun.com","258","15-08-2025 00:24:41","MATECH CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0005694170","M=
imboman-Village","IHS_YND_709","14-08-2025 23:31:03","14-08-2025 23:29:50",=
"15-08-2025 00:54:52","Grid outage, site went down because gen failed to st=
art due to PWC ZTE malfunction // He reset the PWC","Mba Lazare Herve","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid ou=
tage, site went down because gen failed to start due to PWC ZTE malfunction=
 // He reset the PWC","vanel.mbiada@matech-cameroun.com","74","14-08-2025 2=
3:31:03","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0005694155","N=
kolo II New","","14-08-2025 23:26:53","14-08-2025 23:29:50","15-08-2025 00:=
54:52","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // He reset the PWC","vanel.mbiada@matech-camerou=
n.com","469","14-08-2025 23:26:53","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005693565","Bit=
eng-Maetur","","14-08-2025 21:26:56","14-08-2025 21:17:49","14-08-2025 22:1=
0:29","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","loic.no=
umsi@matech-cameroun.com","549","14-08-2025 21:26:56","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005693165","Mim=
boman4","","14-08-2025 20:27:41","14-08-2025 20:25:32","14-08-2025 20:31:37=
","Site went down due to 01/03 rectifiers alarming on site //He reset it ",=
"Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site went down due to 01/03 rectifiers alarming on site //He reset it =
","loic.noumsi@matech-cameroun.com","131","14-08-2025 20:27:41","MATECH CMR=
"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005693023","Mai=
son komkana New","","14-08-2025 20:03:07","14-08-2025 20:00:01","15-08-2025=
 09:21:01","Access issue at night due to landlord. Site went down due 1/3 r=
ectifier faulty // He replace hit, site on Grid","Mboua Thierry","Access De=
nial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord"=
,"Access issue at night due to landlord. Site went down due 1/3 rectifier f=
aulty // He replace hit, site on Grid","loic.noumsi@matech-cameroun.com","1=
87","14-08-2025 20:03:07","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005692983","Nko=
lnda","","14-08-2025 19:54:05","14-08-2025 19:45:59","14-08-2025 20:02:02",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Grid return","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, site went down before Gen start=
 due to poor battery backup // Grid return","loic.noumsi@matech-cameroun.co=
m","488","14-08-2025 19:54:05","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005692636","MBA=
LNGONG LYCEE","","14-08-2025 18:55:57","14-08-2025 18:53:50","14-08-2025 20=
:01:38","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down=
 due Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed =
// Grid return","edwige.kapawo@matech-cameroun.com","130","14-08-2025 18:55=
:57","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005692481","E=
vodoula OCM","","14-08-2025 18:34:34","14-08-2025 18:26:28","14-08-2025 18:=
41:35","grid outage,gen failed to start due to grid bad voltage,no rcp// Gr=
id return","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","	grid outage,gen failed to start due t=
o grid bad voltage,no rcp// Grid return","edwige.kapawo@matech-cameroun.com=
","488","14-08-2025 18:34:34","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005692458","Sim=
e Building","","14-08-2025 18:29:44","14-08-2025 18:25:32","14-08-2025 18:3=
3:37","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","	Grid outage, Site went down bef=
ore Gen start due to poor backup // Gen automatically started","edwige.kapa=
wo@matech-cameroun.com","253","14-08-2025 18:29:44","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0005692210","C=
RF Nkoabang","","14-08-2025 17:36:43","14-08-2025 17:26:59","14-08-2025 17:=
37:47","Grid-solar site, Grid outage, site down due to sunset, // Grid retu=
rn","Mba Lazare Herve","Equipment Repair","Passive","Solar","Solar Panel Is=
sue","	Grid-solar site, Grid outage, site down due to sunset, // Grid retur=
n","edwige.kapawo@matech-cameroun.com","586","14-08-2025 17:36:43","MATECH =
CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0005691816","Mba=
lla 4","","14-08-2025 16:37:31","14-08-2025 16:34:19","14-08-2025 17:04:50"=
,"Site went Down because Hermann ABENA (699999625/Grato) was on site for wo=
rk (SWAP PWC and Gen) // End of work","Delor Telezing","Installation Activi=
ty","Passive","Planned Activity","Installation Activity","Site went Down be=
cause Hermann ABENA (699999625/Grato) was on site for work (SWAP PWC and Ge=
n) // End of work","loic.noumsi@matech-cameroun.com","193","14-08-2025 16:3=
7:31","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005691701","Mai=
son komkana New","","14-08-2025 16:16:37","14-08-2025 16:15:31","14-08-2025=
 16:49:20","	(Site Unstable)Site went down due to insufficient rectifiers o=
n site //Site stablised","Mboua Thierry","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","	(Site Unstable)Site went down due to insufficie=
nt rectifiers on site //Site stablised","loic.noumsi@matech-cameroun.com","=
66","14-08-2025 16:16:37","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005691527","O=
dza II OCM","","14-08-2025 15:38:23","14-08-2025 15:34:18","14-08-2025 15:3=
8:56","	Active: No power issue on site Ubaie =3D54.4V site on Grid. The TX =
FME Lionnel Adhex (655184876) from Huawei is informe","Albran Byorel","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","	Active: No power issue on site Ubaie =3D54.4V site on Grid. The TX =
FME Lionnel Adhex (655184876) from Huawei is informe","edwige.kapawo@matech=
-cameroun.com","250","14-08-2025 15:38:23","MATECH CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0005691444","H=
-Deputes","","14-08-2025 15:28:34","14-08-2025 15:25:27","14-08-2025 15:29:=
32","Grid Outage, No space to deploy a mobile Gen // Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, =
No space to deploy a mobile Gen // Grid return","edwige.kapawo@matech-camer=
oun.com","188","14-08-2025 15:28:34","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005691419","N=
koabang2","","14-08-2025 15:21:09","14-08-2025 15:16:00","14-08-2025 17:52:=
15","Grid outage, Site went down due to Gen overload (22KVA, 330A), SS Blai=
se IHS is informed// Grid return","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Grid outag=
e, Site went down due to Gen overload (22KVA, 330A), SS Blaise IHS is infor=
med // Site stabilised","loic.noumsi@matech-cameroun.com","311","14-08-2025=
 15:21:09","MATECH CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0005691297","Mba=
lla 4","","14-08-2025 15:02:54","14-08-2025 15:01:48","14-08-2025 16:12:43"=
,"Site went Down because Hermann ABENA (699999625/Grato) was on site for wo=
rk (SWAP PWC and Gen) // End of work","Delor Telezing","Installation Activi=
ty","Passive","Planned Activity","Installation Activity","Site went Down be=
cause Hermann ABENA (699999625/Grato) was on site for work (SWAP PWC and Ge=
n) // End of work","loic.noumsi@matech-cameroun.com","67","14-08-2025 15:02=
:54","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005691235","N=
koabang Ebolmedjock","","14-08-2025 14:50:44","14-08-2025 14:46:35","14-08-=
2025 14:53:22","	Site impacted by Nkolmesseng-Abom(CTR-711) Not Manager By =
IHS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","	Site impacted by Nkolmesseng-Abom(CTR-=
711) Not Manager By IHS","edwige.kapawo@matech-cameroun.com","251","14-08-2=
025 14:50:44","MATECH CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0005691233","B=
ISCUITERIE","","14-08-2025 14:50:04","14-08-2025 14:46:57","14-08-2025 14:4=
8:03","No power issue, site is on Grid with Ubaie=3D52 V The TX FME Mbah Ho=
siah (674007438) from Huawei is informed ","Paul BIBOUM","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue, site is on Grid with Ubaie=3D52 V The TX FME Mbah Hosiah (6740074=
38) from Huawei is informed ","edwige.kapawo@matech-cameroun.com","189","14=
-08-2025 14:50:04","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005691228","Mok=
olo Yaounde","","14-08-2025 14:49:19","14-08-2025 14:46:12","14-08-2025 16:=
49:35","Grid only, Grid Outage on site, no space to deploy MDGE // Grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid only, Grid Outage on site, no space to deploy MDGE // Grid return","e=
dwige.kapawo@matech-cameroun.com","189","14-08-2025 14:49:19","MATECH CMR"
"Closed Complete","Site Down","T0467","IHS_YND_077","NOCINC0005691222","Obi=
li Carrefour","","14-08-2025 14:48:28","14-08-2025 13:40:23","14-08-2025 15=
:16:19","Grid outage, site went down because Gen started and stopped due to=
 high temp alarm // Grid return","Paul BIBOUM","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, s=
ite went down because Gen started and stopped due to high temp alarm // Gri=
d return","edwige.kapawo@matech-cameroun.com","5577","14-08-2025 14:48:28",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005691173","N=
YOM 2 IHS","","14-08-2025 14:39:03","14-08-2025 14:29:57","14-08-2025 14:36=
:42","Active // No power issue Ubaie:53.2 V site on Gen, site up without in=
tervention. TX fme symphorien /650257151 from huawei is informed.","Fabrice=
 Pouakam","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active // No power issue Ubaie:53.2 V site on Gen, si=
te up without intervention. TX fme symphorien /650257151 from huawei is inf=
ormed.","edwige.kapawo@matech-cameroun.com","548","14-08-2025 14:39:03","MA=
TECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005691087","MBA=
LNGONG LYCEE","","14-08-2025 14:19:01","14-08-2025 14:09:54","14-08-2025 14=
:19:26","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down=
 due Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed =
// Grid return","gerard.tchangoue@matech-cameroun.com","549","14-08-2025 14=
:19:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005691055","MEHANDAN=
","","14-08-2025 14:15:42","14-08-2025 14:12:59","14-08-2025 14:14:36","Cas=
caded Incident from TTO5893392","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active: No power issue on site Ubaie =3D5=
4.4V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei is info=
rmed","edwige.kapawo@matech-cameroun.com","163","14-08-2025 14:15:42","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0005691054","Odza II =
OCM","","14-08-2025 14:15:42","14-08-2025 14:12:59","14-08-2025 14:14:36","=
Cascaded Incident from TTO5893392","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active: No power issue on site Ubaie =
=3D54.4V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei is =
informed","edwige.kapawo@matech-cameroun.com","163","14-08-2025 14:15:42","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0005691056","Nsimalen=
 OCM","","14-08-2025 14:15:42","14-08-2025 14:12:59","14-08-2025 14:14:36",=
"Cascaded Incident from TTO5893392","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active: No power issue on site Ubaie =
=3D54.4V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei is =
informed","edwige.kapawo@matech-cameroun.com","163","14-08-2025 14:15:42","=
MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0005691050","N=
kolda","IHS_YND_527, IHS_YND_528, IHS_YND_327","14-08-2025 14:13:56","14-08=
-2025 14:12:59","14-08-2025 14:14:36","Active: No power issue on site Ubaie=
 =3D54.4V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei is=
 informed","Albran Byorel","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active: No power issue on site Ubaie=
 =3D54.4V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei is=
 informed","edwige.kapawo@matech-cameroun.com","58","14-08-2025 14:13:56","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005690827","ETOUDI C=
HAPELLE","","14-08-2025 13:35:15","14-08-2025 13:33:18","14-08-2025 13:36:3=
2","Cascaded Incident from TTO5893137","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active // No power issue site on =
grid with Ubaie: 53.4V, TX Fme Armand Nguetsa (699949553 /Huawei) is inform=
ed. Notice that it is a repetitive issue.","gerard.tchangoue@matech-camerou=
n.com","117","14-08-2025 13:35:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005690828","Etoudi 2=
","","14-08-2025 13:35:15","14-08-2025 13:33:18","14-08-2025 13:36:32","Cas=
caded Incident from TTO5893137","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active // No power issue site on grid w=
ith Ubaie: 53.4V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. No=
tice that it is a repetitive issue.","gerard.tchangoue@matech-cameroun.com"=
,"117","14-08-2025 13:35:15","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005690821","Aba=
ttoir","IHS_YND_694, IHS_YND_211","14-08-2025 13:34:27","14-08-2025 13:33:1=
8","14-08-2025 13:36:32","Active // No power issue site on grid with Ubaie:=
 53.4V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. Notice that =
it is a repetitive issue.","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power=
 issue site on grid with Ubaie: 53.4V, TX Fme Armand Nguetsa (699949553 /Hu=
awei) is informed. Notice that it is a repetitive issue.","gerard.tchangoue=
@matech-cameroun.com","71","14-08-2025 13:34:27","MATECH CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0005690784","H=
-Deputes","","14-08-2025 13:26:42","14-08-2025 13:22:30","14-08-2025 14:13:=
35","Grid Outage, No space to deploy a mobile Gen // Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, =
No space to deploy a mobile Gen // Grid return","edwige.kapawo@matech-camer=
oun.com","253","14-08-2025 13:26:42","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005690752","A=
wae Escalier","","14-08-2025 13:19:12","14-08-2025 13:18:05","14-08-2025 14=
:11:49","Grid outage site went down because Gen failed to start due to Gen =
card faulty // Gen Manually Started","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage site went down becaus=
e Gen failed to start due to Gen card faulty // Gen Manually Started","edwi=
ge.kapawo@matech-cameroun.com","68","14-08-2025 13:19:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005690539","Ngoum","=
","14-08-2025 12:39:45","14-08-2025 12:32:03","14-08-2025 12:40:58","Cascad=
ed Incident from TTO5892800","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because SS IHS Felix BATEU=
 was on site for working (TRANSMISSION SECURE and TEST) // End of work","ge=
rard.tchangoue@matech-cameroun.com","724","14-08-2025 12:39:45","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005690540","Yoko MTN=
","","14-08-2025 12:39:45","14-08-2025 12:32:03","14-08-2025 12:40:58","Cas=
caded Incident from TTO5892800","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because SS IHS Felix BA=
TEU was on site for working (TRANSMISSION SECURE and TEST) // End of work",=
"gerard.tchangoue@matech-cameroun.com","725","14-08-2025 12:39:45","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005690502","MBIMBIM"=
,"","14-08-2025 12:32:03","14-08-2025 12:27:03","14-08-2025 12:46:39","Casc=
aded Incident from TTO5892773","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because SS IHS Felix BAT=
EU was on site for working (TRANSMISSION SECURE and TEST) // End of work","=
edwige.kapawo@matech-cameroun.com","300","14-08-2025 12:32:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005690501","Ngouetou=
","","14-08-2025 12:32:03","14-08-2025 12:27:03","14-08-2025 12:46:39","Cas=
caded Incident from TTO5892773","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because SS IHS Felix BA=
TEU was on site for working (TRANSMISSION SECURE and TEST) // End of work",=
"edwige.kapawo@matech-cameroun.com","300","14-08-2025 12:32:03","MATECH CMR=
"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005690497","M=
atsari","IHS_YND_475, IHS_YND_454, IHS_YND_473, IHS_YND_456","14-08-2025 12=
:31:12","14-08-2025 12:27:03","14-08-2025 12:46:39","Site went down because=
 SS IHS Felix BATEU was on site for working (TRANSMISSION SECURE and TEST) =
// End of work","Parker Tchoup","Installation Activity","Passive","Planned =
Activity","Installation Activity","Site went down because SS IHS Felix BATE=
U was on site for working (TRANSMISSION SECURE and TEST) // End of work","e=
dwige.kapawo@matech-cameroun.com","251","14-08-2025 12:31:12","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005690171","M=
arche Odza","","14-08-2025 11:30:00","14-08-2025 11:29:56","14-08-2025 11:3=
0:01","Grid fluctuation,site went down due to poor batterie backup// Grid s=
tabilisation","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid fluctuation,site went down due to poor =
batterie backup// Grid stabilisation","edwige.kapawo@matech-cameroun.com","=
6","14-08-2025 11:30:00","MATECH CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0005690160","B=
ATA-Mokolo","","14-08-2025 11:28:24","14-08-2025 11:26:17","14-08-2025 12:0=
3:53","Active// No power issue on site Ubaie=3D55,9V site on Grid Brice Tsa=
gue (650214096) from Huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power i=
ssue on site Ubaie=3D55,9V site on Grid Brice Tsague (650214096) from Huawe=
i is informed","edwige.kapawo@matech-cameroun.com","129","14-08-2025 11:28:=
24","MATECH CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0005690106","H=
-Deputes","","14-08-2025 11:26:45","14-08-2025 11:17:59","14-08-2025 11:48:=
10","Grid Outage,  No space to deploy a mobile Gen // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage,=
  No space to deploy a mobile Gen // Grid return","edwige.kapawo@matech-cam=
eroun.com","527","14-08-2025 11:26:45","MATECH CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0005689790","Mba=
lla 4","","14-08-2025 10:43:46","14-08-2025 10:40:42","14-08-2025 12:48:01"=
,"Site went Down because Hermann ABENA (699999625/Grato) was on site for wo=
rk (SWAP PWC and Gen)  // End of work","Delor Telezing","Installation Activ=
ity","Passive","Planned Activity","Installation Activity","Site went Down b=
ecause Hermann ABENA (699999625/Grato) was on site for work (SWAP PWC and G=
en)  // End of work","gerard.tchangoue@matech-cameroun.com","185","14-08-20=
25 10:43:46","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005689612","C=
-Supreme","","14-08-2025 10:09:30","14-08-2025 10:04:22","14-08-2025 11:07:=
16","Active // No power issue, site on Grid with Ubaie=3D54.5V, TX FME Bric=
e Tsague (650 21 40 96 / Huawei) is informed","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No p=
ower issue, site on Grid with Ubaie=3D54.5V, TX FME Brice Tsague (650 21 40=
 96 / Huawei) is informed","edwige.kapawo@matech-cameroun.com","310","14-08=
-2025 10:09:30","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005689063","E=
vodoula OCM","","14-08-2025 09:04:28","14-08-2025 09:01:17","14-08-2025 09:=
41:13","Grid outage, Site went down because gen stopped due to belt cut // =
He changed belt and Gen manually started","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Fan Belt","Grid outage, Site went=
 down because gen stopped due to belt cut // He changed belt and Gen manual=
ly started","edwige.kapawo@matech-cameroun.com","192","14-08-2025 09:04:28"=
,"MATECH CMR"
"Closed Complete","Site Down","T1430","IHS_YND_790","NOCINC0005688754","TRB=
 Centre ville","","14-08-2025 07:56:36","14-08-2025 06:35:23","14-08-2025 1=
1:28:50","Access issue due to landlord site went down and not managing by M=
ATECH but authorization will be given by IHS today  and  SS Bernard Atangan=
ana is informed ","Yamen Herman","Access Denial","Lease Or Legal","Landlord=
 Related Issues","Access Issue - Land Lord","Access issue due to landlord s=
ite went down and not managing by MATECH but authorization will be given by=
 IHS today  and  SS Bernard Atanganana is informed ","gerard.tchangoue@mate=
ch-cameroun.com","4873","14-08-2025 07:56:36","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005688116","A=
fanoya","","14-08-2025 03:42:44","14-08-2025 03:39:32","14-08-2025 03:41:53=
","Grid outage , site went down before Gen started due to poor battery back=
up// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage , site went down before Gen=
 started due to poor battery backup// Grid return","vanel.mbiada@matech-cam=
eroun.com","193","14-08-2025 03:42:44","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005687867","Sim=
e Building","","14-08-2025 02:14:02","14-08-2025 02:11:38","14-08-2025 02:1=
9:54","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","cedric.tiani=
@matech-cameroun.com","145","14-08-2025 02:14:02","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005687816","Crf=
-Mbankolo-IHS","","14-08-2025 01:42:24","14-08-2025 01:39:16","14-08-2025 0=
2:15:47","Site went down due to work done by Ronny    Grato  695934760 (swa=
pp of PWC) SS HIS Bernard Atangana is informed and confirmed//End of work",=
"Mboua Thierry","Installation Activity","Passive","Planned Activity","Insta=
llation Activity","Site went down due to work done by RONY from GRATO (swap=
p of PWC) SS HIS Bernard Atangana is informed and confirmed//End of work","=
cedric.tiani@matech-cameroun.com","190","14-08-2025 01:42:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0005687670","Monatele=
","","14-08-2025 00:45:29","14-08-2025 00:43:59","14-08-2025 00:53:36","Cas=
caded Incident from TTO5889647","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site ,site on G=
RID with Ubaie=3D54.2V The TX FME Gregoire(654547479) from Huawei is inform=
ed","cedric.tiani@matech-cameroun.com","90","14-08-2025 00:45:29","MATECH C=
MR"
"Closed Complete","Site Down","T0053","IHS_YND_407","NOCINC0005687668","Mon=
atele MTN","IHS_YND_406","14-08-2025 00:45:07","14-08-2025 00:43:59","14-08=
-2025 00:53:36","Active//No power issue on site ,site on GRID with Ubaie=3D=
54.2V The TX FME Gregoire(654547479) from Huawei is informed","Parker Tchou=
p","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issue on site ,site on GRID with Ubaie=3D54=
.2V The TX FME Gregoire(654547479) from Huawei is informed","cedric.tiani@m=
atech-cameroun.com","69","14-08-2025 00:45:07","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005687650","Mai=
son komkana New","","14-08-2025 00:35:11","14-08-2025 00:33:59","14-08-2025=
 01:01:59","Site went down due to insufficient rectifiers on site //Site st=
ablised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficient rectifiers on site //Site sta=
blised","cedric.tiani@matech-cameroun.com","72","14-08-2025 00:35:11","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0005687606","LOBO MTN=
","","14-08-2025 00:15:13","14-08-2025 00:04:01","14-08-2025 00:14:05","Cas=
caded Incident from TTO5889543","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D49,=
9v site on battery Tx fme Etienne of huawei is informed","cedric.tiani@mate=
ch-cameroun.com","672","14-08-2025 00:15:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0005687604","Ngog Map=
ubi","","14-08-2025 00:15:12","14-08-2025 00:04:01","14-08-2025 00:14:05","=
Cascaded Incident from TTO5889543","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site U=3D49,9v sit=
e on battery Tx fme Etienne of huawei is informed","cedric.tiani@matech-cam=
eroun.com","671","14-08-2025 00:15:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005687605","Mambine"=
,"","14-08-2025 00:15:12","14-08-2025 00:04:01","14-08-2025 00:14:05","Casc=
aded Incident from TTO5889543","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site U=3D49,9v site on bat=
tery Tx fme Etienne of huawei is informed","cedric.tiani@matech-cameroun.co=
m","671","14-08-2025 00:15:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0005687603","Nkeng li=
kok","","14-08-2025 00:15:12","14-08-2025 00:04:01","14-08-2025 00:14:05","=
Cascaded Incident from TTO5889543","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site U=3D49,9v sit=
e on battery Tx fme Etienne of huawei is informed","cedric.tiani@matech-cam=
eroun.com","671","14-08-2025 00:15:12","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0005687580","Ebe=
ba","IHS_YND_347, IHS_YND_419, IHS_YND_350, IHS_YND_342","14-08-2025 00:11:=
10","14-08-2025 00:04:01","14-08-2025 01:52:20","No power issue on site U=
=3D49,9v site on battery Tx fme Etienne of huawei is informed","Fanda Brice=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site U=3D49,9v site on battery Tx fme Etien=
ne of huawei is informed","cedric.tiani@matech-cameroun.com","430","14-08-2=
025 00:11:10","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005687504","N=
KOLMEKONG YDE","IHS_YND_304","13-08-2025 23:43:07","13-08-2025 23:40:55","1=
3-08-2025 23:52:43","Grid outage,Site went because Gen failed to start (Dee=
p investigation on going)//Gen maunually started","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,Site w=
ent because Gen failed to start (Deep investigation on going)//Gen maunuall=
y started","cedric.tiani@matech-cameroun.com","134","13-08-2025 23:43:07","=
MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005687500","N=
kolondom","","13-08-2025 23:42:02","13-08-2025 23:40:55","13-08-2025 23:47:=
43","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage,Site went because Gen failed to start (Deep inves=
tigation on going)//Gen maunually started","cedric.tiani@matech-cameroun.co=
m","534","13-08-2025 23:42:02","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005687460","Crf=
-Mbankolo-IHS","","13-08-2025 23:30:42","13-08-2025 23:29:29","13-08-2025 2=
3:37:45","Site went down due to work done by   Rony   Grato  695934760 (swa=
pp of PWC) SS HIS Bernard Atangana is informed and confirmed//End of work",=
"Mboua Thierry","Installation Activity","Passive","Planned Activity","Insta=
llation Activity","Site went down due to work done by   Rony   Grato  69593=
4760 (swapp of PWC) SS HIS Bernard Atangana is informed and confirmed//End =
of work","cedric.tiani@matech-cameroun.com","75","13-08-2025 23:30:42","MAT=
ECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005687447","Mai=
son komkana New","","13-08-2025 23:26:06","13-08-2025 23:24:56","14-08-2025=
 00:25:28","(Site Unstable)Site went down due to insufficient rectifiers on=
 site //Site stablised","Mboua Thierry","Equipment Repair","Passive","Recti=
fier","Rectifier Module","(Site Unstable)Site went down due to insufficient=
 rectifiers on site //Site stablised","cedric.tiani@matech-cameroun.com","7=
1","13-08-2025 23:26:06","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005687410","Mai=
son komkana New","","13-08-2025 23:12:22","13-08-2025 23:08:12","13-08-2025=
 23:16:15","Site went down due to insufficient rectifiers on site//Site sta=
bilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficient rectifiers on site//Site stab=
ilised","cedric.tiani@matech-cameroun.com","251","13-08-2025 23:12:22","MAT=
ECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005687104","Mai=
son komkana New","","13-08-2025 21:58:37","13-08-2025 21:56:23","13-08-2025=
 22:11:09","Grid outage, Site went down before Gen start due to poor backup=
 // Site stabilised","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Site stabilised","loic.noumsi@matech-cameroun=
.com","135","13-08-2025 21:58:37","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005687044","Bit=
eng-Maetur","","13-08-2025 21:47:38","13-08-2025 21:44:33","13-08-2025 21:5=
6:31","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","loic.no=
umsi@matech-cameroun.com","186","13-08-2025 21:47:38","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005686815","E=
mombo","","13-08-2025 21:14:36","13-08-2025 21:10:30","13-08-2025 21:11:55"=
,"No power issue, site is on Grid with Ubaie=3D54,2V, TX FME Henri (6911450=
55) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue,=
 site is on Grid with Ubaie=3D54,2V, TX FME Henri (691145055) from Huawei i=
s informed","loic.noumsi@matech-cameroun.com","247","13-08-2025 21:14:36","=
MATECH CMR"
"Closed Complete","Warning","CTR_213","IHS_YND_247","NOCINC0005686669","Oko=
lo","","13-08-2025 20:48:26","","","SIte went in alarm because ENEO Grid me=
ter burnt // He deployed new Gen on site","Fabrice Pouakam","Warning","Warn=
ing","POWER","Warning - National Grid - Grid Outage Issue","SIte went in al=
arm because ENEO Grid meter burnt // He deployed Gen on site","gerard.tchan=
goue@matech-cameroun.com","3","13-08-2025 20:48:26","MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005686597","Mvo=
g Betsi Hospital","","13-08-2025 20:34:17","13-08-2025 20:30:12","13-08-202=
5 20:36:34","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","loic.noumsi@matech-cameroun.com",=
"245","13-08-2025 20:34:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005686583","Etoudi 2=
","","13-08-2025 20:32:10","13-08-2025 20:23:23","13-08-2025 20:24:38","Cas=
caded Incident from TTO5888427","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active // No power issue site on grid w=
ith Ubaie: 53.4V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. No=
tice that it is a repetitive issue.","loic.noumsi@matech-cameroun.com","527=
","13-08-2025 20:32:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005686582","ETOUDI C=
HAPELLE","","13-08-2025 20:32:09","13-08-2025 20:23:23","13-08-2025 20:24:3=
8","Cascaded Incident from TTO5888427","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active // No power issue site on =
grid with Ubaie: 53.4V, TX Fme Armand Nguetsa (699949553 /Huawei) is inform=
ed. Notice that it is a repetitive issue.","loic.noumsi@matech-cameroun.com=
","526","13-08-2025 20:32:09","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005686581","Aba=
ttoir","IHS_YND_694, IHS_YND_211","13-08-2025 20:31:36","13-08-2025 20:23:2=
3","13-08-2025 20:24:38","Active // No power issue site on grid with Ubaie:=
 53.4V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. Notice that =
it is a repetitive issue.","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power=
 issue site on grid with Ubaie: 53.4V, TX Fme Armand Nguetsa (699949553 /Hu=
awei) is informed. Notice that it is a repetitive issue.","loic.noumsi@mate=
ch-cameroun.com","495","13-08-2025 20:31:36","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005686531","Mai=
son komkana New","","13-08-2025 20:21:15","13-08-2025 20:19:10","13-08-2025=
 20:51:20","Grid outage, Site went down before Gen start due to poor backup=
 // Site stabilised","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Site stabilised","loic.noumsi@matech-cameroun=
.com","126","13-08-2025 20:21:15","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005686470","Nko=
abang2","","13-08-2025 20:12:48","13-08-2025 20:10:43","14-08-2025 07:15:16=
","Grid outage, Site went down due to Gen overload (22KVA, 330A), SS Blaise=
 IHS is informed// Grid return","Mba Lazare Herve","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to Gen o=
verload (22KVA, 330A), SS Blaise IHS is informed// Grid return","loic.noums=
i@matech-cameroun.com","127","13-08-2025 20:12:48","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0005686459","Imm=
-Olympique","","13-08-2025 20:11:39","13-08-2025 20:09:35","13-08-2025 21:2=
1:13","Grid outage,site went down because Gen failed to start due to Gen ov=
erload(20KVA//295A) SS HIS Raoul is informed // Gen restarted manually","Pa=
ul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage,site went down because Gen failed to start due to Gen overload(20KVA=
//295A) SS HIS Raoul is informed // Gen restarted manually","loic.noumsi@ma=
tech-cameroun.com","126","13-08-2025 20:11:39","MATECH CMR"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0005686330","E=
zezang","","13-08-2025 19:50:04","13-08-2025 19:46:51","13-08-2025 20:19:57=
","Grid Outage, Gen stoped due to alarm emergency stop // Gen card reset an=
d Gen start manually","Parker Tchoup","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Emergency Stop","Grid Outage, Gen stoped due to alarm emergency =
stop // Gen card reset and Gen start manually","edwige.kapawo@matech-camero=
un.com","194","13-08-2025 19:50:04","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005686186","N=
koabang2","","13-08-2025 19:21:26","13-08-2025 19:20:05","13-08-2025 19:24:=
04","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed ","Mba Lazare Herve","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","	Grid outage, site went down due to gen overload (2=
2KVA, 330A), SS Blaise IHS is informed // Site stabilised","edwige.kapawo@m=
atech-cameroun.com","83","13-08-2025 19:21:26","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005686108","Mai=
son komkana New","","13-08-2025 19:08:30","13-08-2025 19:05:27","13-08-2025=
 20:13:21","Grid outage, Site went down before Gen start due to poor backup=
 // Grid stabilised","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Grid stabilised","loic.noumsi@matech-cameroun=
.com","184","13-08-2025 19:08:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005686033","Nsam esc=
ale LP","","13-08-2025 18:52:43","13-08-2025 18:39:12","13-08-2025 18:45:32=
","Cascaded Incident from TTO5887780","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, Site went down before Gen start =
due to poor backup/ // Grid return","loic.noumsi@matech-cameroun.com","811"=
,"13-08-2025 18:52:43","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005685991","Nsa=
m Sofavinc","IHS_YND_732","13-08-2025 18:43:18","13-08-2025 18:39:12","13-0=
8-2025 18:45:32","Grid outage, Site went down before Gen start due to poor =
backup/ // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup/ // Grid return","loic.noumsi@matech-cameroun=
.com","247","13-08-2025 18:43:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005685907","Nkolondo=
m","","13-08-2025 18:28:28","13-08-2025 18:15:31","13-08-2025 19:46:34","Ca=
scaded Incident from TTO5887683","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down sue to =
fuel shortage // Refueling done","loic.noumsi@matech-cameroun.com","777","1=
3-08-2025 18:28:28","MATECH CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0005685834","NKO=
LMEKONG YDE","IHS_YND_304","13-08-2025 18:17:35","13-08-2025 18:15:31","13-=
08-2025 19:52:44","Grid outage, Site went down sue to fuel shortage // Refu=
eling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, Site went down sue to fuel shortage // Refueling done","l=
oic.noumsi@matech-cameroun.com","125","13-08-2025 18:17:35","MATECH CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0005685715","V=
allee-Bastos OCM","","13-08-2025 17:57:04","13-08-2025 17:52:57","13-08-202=
5 18:49:45","Grid only site, no MDGE to deploy // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site, =
no MDGE to deploy // Grid return","edwige.kapawo@matech-cameroun.com","248"=
,"13-08-2025 17:57:04","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005685703","Mai=
son komkana New","","13-08-2025 17:55:24","13-08-2025 17:52:18","13-08-2025=
 17:56:55","Grid outage, Site went down before Gen start due to poor backup=
 // site stabilised","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // site stabilised","gerard.tchangoue@matech-cam=
eroun.com","187","13-08-2025 17:55:24","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005685598","A=
kak-Nkozoa-MTN-IHS","","13-08-2025 17:32:11","13-08-2025 17:30:05","13-08-2=
025 19:00:26","Grid outage, Site went down because Gen start and stopped wi=
th ""High temp ""alarm // he added water and manually start the Gen	","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Te=
mp - Coolant Level Issue","Grid outage, Site went down because Gen start an=
d stopped with ""High temps ""alarm // he added water and manually start th=
e Gen	","edwige.kapawo@matech-cameroun.com","129","13-08-2025 17:32:11","MA=
TECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005685475","Mvo=
g-Manga","","13-08-2025 17:02:01","13-08-2025 16:59:38","13-08-2025 17:20:1=
1","Site down because Biganstil(679161144/Dowen) is on site for work (Swap =
PWC, DC Box and Gen Battery) // End of work","Albran Byorel","Installation =
Activity","Passive","Planned Activity","Installation Activity","Site down b=
ecause Biganstil(679161144/Dowen) is on site for work (Swap PWC, DC Box and=
 Gen Battery) // End of work","loic.noumsi@matech-cameroun.com","145","13-0=
8-2025 17:02:01","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005685442","Mai=
son komkana New","","13-08-2025 16:56:53","13-08-2025 16:54:49","13-08-2025=
 17:09:30","Grid outage, Site went down before Gen start due to poor backup=
 // site stabilised","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // site stabilised","loic.noumsi@matech-cameroun=
.com","125","13-08-2025 16:56:53","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005685265","M=
vog-Manga","","13-08-2025 16:28:07","13-08-2025 16:26:18","13-08-2025 16:40=
:12","Site down because Biganstil(679161144/Dowen) is on site for work (Swa=
p PWC, DC Box and Gen Battery) // End of work","Albran Byorel","Installatio=
n Activity","Passive","Planned Activity","Installation Activity","Site down=
 because Biganstil(679161144/Dowen) is on site for work (Swap PWC, DC Box a=
nd Gen Battery) // End of work","edwige.kapawo@matech-cameroun.com","112","=
13-08-2025 16:28:07","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005685220","Mok=
olo Yaounde","","13-08-2025 16:22:42","13-08-2025 16:20:34","13-08-2025 17:=
53:47","site went down due to disjunction of Grid CB (30A) // Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Circuit Breaker","site w=
ent down due to disjunction of Grid CB (30A) // Grid return","loic.noumsi@m=
atech-cameroun.com","130","13-08-2025 16:22:42","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005685088","T=
SINGA VILLAGE 2","","13-08-2025 16:00:08","13-08-2025 15:58:58","13-08-2025=
 16:04:50","Site went down because FME was working on site (Hybrid system i=
nstallation) // END of work","Delor Telezing","Installation Activity","Pass=
ive","Planned Activity","Installation Activity","Site went down because FME=
 was working on site (Hybrid system installation) // END of work","edwige.k=
apawo@matech-cameroun.com","71","13-08-2025 16:00:08","MATECH CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0005684772","H=
-Deputes","","13-08-2025 15:08:55","13-08-2025 15:04:31","13-08-2025 16:36:=
50","Grid Outage No space to deploy a mobile Gen // Grid retun","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No =
space to deploy a mobile Gen // Grid retun","edwige.kapawo@matech-cameroun.=
com","265","13-08-2025 15:08:55","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005684771","Mai=
son komkana New","","13-08-2025 15:08:50","13-08-2025 15:07:45","13-08-2025=
 15:21:47","Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","loic.noumsi@matech-cameroun.com","6=
6","13-08-2025 15:08:50","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005684314","Mai=
son komkana New","","13-08-2025 14:01:42","13-08-2025 13:59:31","13-08-2025=
 14:33:17","Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.co=
m","132","13-08-2025 14:01:42","MATECH CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0005684117","H=
-Deputes","","13-08-2025 13:26:55","13-08-2025 13:21:46","13-08-2025 14:56:=
54","Grid Outage No space to deploy a mobile Gen // Grid retun","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no=
 space to deploy a mobil Gen // Grid return","edwige.kapawo@matech-cameroun=
.com","309","13-08-2025 13:26:55","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0005683955","Yok=
o MTN","","13-08-2025 13:07:27","13-08-2025 13:04:20","13-08-2025 13:30:53"=
,"Site went Down due to work SS IHS Felix BATEU was on site for work ( prot=
ect transmission) // End of wok","Parker Tchoup","Equipment Replacement","P=
assive","Planned Activity","Planned Activity - Passive","Site went Down due=
 to work SS IHS Felix BATEU was on site for work ( protect transmission) //=
 End of wok","gerard.tchangoue@matech-cameroun.com","188","13-08-2025 13:07=
:27","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005683872","M=
vog-Manga","","13-08-2025 12:52:24","13-08-2025 12:50:17","13-08-2025 12:56=
:04","Grid outage, Site went down because Gen failed to start due to Gen ba=
ttery  faulty// Grid return","Albran Byorel","Equipment Repair","Passive","=
ACDG Gen","ACDG - Generator Battery","Grid outage, Site went down because G=
en failed to start due to Gen battery  faulty// Grid return","edwige.kapawo=
@matech-cameroun.com","130","13-08-2025 12:52:24","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005683771","Mai=
son komkana New","","13-08-2025 12:37:00","13-08-2025 12:33:53","13-08-2025=
 12:40:53","Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","edwige.kapawo@matech-cameroun.com",=
"187","13-08-2025 12:37:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005683764","Bastos-N=
ylon","","13-08-2025 12:36:27","13-08-2025 12:30:52","13-08-2025 14:16:45",=
"Cascaded Incident from TTO5885321","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 disjunction of PWC CB (125A) // He added 01 CB (63A) and did bridge, site =
on Grid","edwige.kapawo@matech-cameroun.com","335","13-08-2025 12:36:27","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005683765","Bastos B=
ethesda","","13-08-2025 12:36:27","13-08-2025 12:30:52","13-08-2025 14:16:4=
5","Cascaded Incident from TTO5885321","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to disjunction of PWC CB (125A) // He added 01 CB (63A) and did bridge, si=
te on Grid","edwige.kapawo@matech-cameroun.com","335","13-08-2025 12:36:27"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005683763","Golf Qua=
ter","","13-08-2025 12:36:26","13-08-2025 12:30:52","13-08-2025 14:16:45","=
Cascaded Incident from TTO5885321","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
disjunction of PWC CB (125A) // He added 01 CB (63A) and did bridge, site o=
n Grid","edwige.kapawo@matech-cameroun.com","334","13-08-2025 12:36:26","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005683757","T=
singa","IHS_YND_220, IHS_YND_126, IHS_YND_563","13-08-2025 12:34:59","13-08=
-2025 12:30:52","13-08-2025 14:16:45","Grid outage, site went down due to d=
isjunction of PWC CB (125A) // He added 01 CB (63A) and did bridge, site on=
 Grid","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Circuit Breaker Issue","Grid outage, site went down due to disjun=
ction of PWC CB (125A) // He added 01 CB (63A) and did bridge, site on Grid=
","edwige.kapawo@matech-cameroun.com","249","13-08-2025 12:34:59","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005683449","ETOUDI C=
HAPELLE","","13-08-2025 11:46:38","13-08-2025 11:40:16","13-08-2025 11:48:3=
1","Cascaded Incident from TTO5884962","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active // No power issue site on =
grid with Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is inform=
ed. Notice that it is a repetitive issue.","gerard.tchangoue@matech-camerou=
n.com","382","13-08-2025 11:46:38","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005683436","Aba=
ttoir","IHS_YND_694","13-08-2025 11:45:30","13-08-2025 11:40:16","13-08-202=
5 11:48:31","Active // No power issue site on grid with Ubaie: 53.1V, TX Fm=
e Armand Nguetsa (699949553 /Huawei) is informed. Notice that it is a repet=
itive issue.","Fabrice Pouakam","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active // No power issue site o=
n grid with Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is info=
rmed. Notice that it is a repetitive issue.","gerard.tchangoue@matech-camer=
oun.com","316","13-08-2025 11:45:30","MATECH CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0005683402","Eto=
udi 2","IHS_YND_694","13-08-2025 11:40:57","13-08-2025 11:40:46","13-08-202=
5 11:42:20","Active // No power issue site on grid with Ubaie: 53.1V, TX Fm=
e Armand Nguetsa (699949553 /Huawei) is informed. Notice that it is a repet=
itive issue.. Site impacted by Abattoir","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve // No power issue site on grid with Ubaie: 53.1V, TX Fme Armand Nguetsa =
(699949553 /Huawei) is informed. Notice that it is a repetitive issue.. Sit=
e impacted by Abattoir","gerard.tchangoue@matech-cameroun.com","13","13-08-=
2025 11:40:57","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0005683163","Nlo=
ngkak","","13-08-2025 11:03:53","13-08-2025 11:01:35","13-08-2025 13:25:49"=
,"Grid outage, site went down due to 01/03 rectifiers faulty // He replaced=
 it, site on Gen","Delor Telezing","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Grid outage, site went down due to 01/03 rectifiers fa=
ulty // He replaced it, site on Gen","gerard.tchangoue@matech-cameroun.com"=
,"140","13-08-2025 11:03:53","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005683145","Mai=
son komkana New","","13-08-2025 11:02:13","13-08-2025 10:59:04","13-08-2025=
 11:03:44","Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.co=
m","190","13-08-2025 11:02:13","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005682981","T=
singa","","13-08-2025 10:33:57","13-08-2025 10:32:59","13-08-2025 11:24:27"=
,"Grid fluctuations, Site went Down due to  PWC Huawei Dysfunction // Site =
Stabilized","Mboua Thierry","Equipment Repair","Passive","Rectifier","Recti=
fier Module Overloaded","Grid fluctuations, Site went Down due to  PWC Huaw=
ei Dysfunction // Site Stabilized","edwige.kapawo@matech-cameroun.com","59"=
,"13-08-2025 10:33:57","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0005682895","Y=
oko OCM","","13-08-2025 10:19:00","13-08-2025 10:17:49","13-08-2025 10:48:2=
9","Site went Down due to work SS IHS Felix BATEU was  on site for work ( p=
rotect transmission) // End of wok","Parker Tchoup","Equipment Replacement"=
,"Passive","Planned Activity","Planned Activity - Passive","Site went Down =
due to work SS IHS Felix BATEU was  on site for work ( protect transmission=
) // End of wok","edwige.kapawo@matech-cameroun.com","73","13-08-2025 10:19=
:00","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005682893","Mai=
son komkana New","","13-08-2025 10:18:48","13-08-2025 10:17:40","13-08-2025=
 10:21:19","Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.co=
m","69","13-08-2025 10:18:48","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005682534","Mai=
son komkana New","","13-08-2025 09:14:06","13-08-2025 09:06:01","13-08-2025=
 09:34:23","Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.co=
m","485","13-08-2025 09:14:06","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005682479","Fla=
menco","","13-08-2025 09:03:27","13-08-2025 08:59:18","13-08-2025 09:33:15"=
,"Site went down because Gen failed to start due to Gen battery stolen // H=
e started with an external battery","Mboua Thierry","Site Asset Theft","The=
ft","Theft","Generator Battery Theft","Site went down because Gen failed to=
 start due to Gen battery stolen // He started with an external battery","g=
erard.tchangoue@matech-cameroun.com","250","13-08-2025 09:03:27","MATECH CM=
R"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0005682408","Nko=
mkana","","13-08-2025 08:48:58","13-08-2025 08:41:51","13-08-2025 09:29:59"=
,"Grid Only, No space to deploy MGE // Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid Only, No space to depl=
oy MGE // Grid return","gerard.tchangoue@matech-cameroun.com","428","13-08-=
2025 08:48:58","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005682403","NKO=
MKANA ELIZA HOTEL","","13-08-2025 08:47:03","13-08-2025 08:41:58","13-08-20=
25 09:29:23","Grid outage, No space to deploy a MGE // Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, No space to deploy a MGE // Grid return","gerard.tchangoue@matech-camerou=
n.com","307","13-08-2025 08:47:03","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005682328","Mai=
son komkana New","","13-08-2025 08:25:12","13-08-2025 08:24:01","13-08-2025=
 08:54:01","Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","edwige.kapawo@matech-cameroun.com",=
"72","13-08-2025 08:25:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0005682273","Nkomkana=
 2","","13-08-2025 08:10:51","13-08-2025 08:00:07","13-08-2025 08:19:09","C=
ascaded Incident from TTO5883624","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Only, No space to deploy MGE //=
 Grid return","edwige.kapawo@matech-cameroun.com","644","13-08-2025 08:10:5=
1","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0005682224","N=
komkana","IHS_YND_138","13-08-2025 08:02:15","13-08-2025 08:00:07","13-08-2=
025 08:20:25","Grid Only, No space to deploy MGE // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No =
space to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","13=
0","13-08-2025 08:02:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005681977","Bastos-N=
ylon","","13-08-2025 06:50:44","13-08-2025 06:48:44","13-08-2025 08:46:24",=
"Cascaded Incident from TTO5883346","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage, Site went down becaus=
e the PWC OF Huawei  dysfonction // He reset the PWC","edwige.kapawo@matech=
-cameroun.com","120","13-08-2025 06:50:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005681978","Bastos B=
ethesda","","13-08-2025 06:50:44","13-08-2025 06:48:44","13-08-2025 08:46:2=
4","Cascaded Incident from TTO5883346","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, Site went down bec=
ause the PWC OF Huawei  dysfonction // He reset the PWC","edwige.kapawo@mat=
ech-cameroun.com","120","13-08-2025 06:50:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005681976","Golf Qua=
ter","","13-08-2025 06:50:43","13-08-2025 06:48:44","13-08-2025 08:46:24","=
Cascaded Incident from TTO5883346","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site went down because=
 the PWC OF Huawei  dysfonction // He reset the PWC","edwige.kapawo@matech-=
cameroun.com","119","13-08-2025 06:50:43","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005681971","T=
singa","IHS_YND_220, IHS_YND_126, IHS_YND_563","13-08-2025 06:49:53","13-08=
-2025 06:48:44","13-08-2025 08:46:24","Awaiting feedback","Mboua Thierry","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 Outage, Site went down because the PWC OF Huawei  dysfonction // He reset =
the PWC","edwige.kapawo@matech-cameroun.com","71","13-08-2025 06:49:53","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0005681904","Saa","",=
"13-08-2025 06:29:23","13-08-2025 06:14:47","13-08-2025 06:29:47","Cascaded=
 Incident from TTO5883254","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by NTUI T187 not managed by IHS"=
,"franck.nkomot@matech-cameroun.com","876","13-08-2025 06:29:23","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005681905","Yoko MTN=
","","13-08-2025 06:29:23","13-08-2025 06:14:47","13-08-2025 06:29:47","Cas=
caded Incident from TTO5883254","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Site impacted by NTUI T187 not managed by=
 IHS","franck.nkomot@matech-cameroun.com","876","13-08-2025 06:29:23","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005681900","Ngouetou=
","","13-08-2025 06:29:22","13-08-2025 06:14:47","13-08-2025 06:29:47","Cas=
caded Incident from TTO5883254","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Site impacted by NTUI T187 not managed by=
 IHS","franck.nkomot@matech-cameroun.com","875","13-08-2025 06:29:22","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0005681902","Dong",""=
,"13-08-2025 06:29:22","13-08-2025 06:14:47","13-08-2025 06:29:47","Cascade=
d Incident from TTO5883254","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Site impacted by NTUI T187 not managed by IHS=
","franck.nkomot@matech-cameroun.com","875","13-08-2025 06:29:22","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0005681901","Donga","=
","13-08-2025 06:29:22","13-08-2025 06:14:47","13-08-2025 06:29:47","Cascad=
ed Incident from TTO5883254","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by NTUI T187 not managed by IH=
S","franck.nkomot@matech-cameroun.com","875","13-08-2025 06:29:22","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0005681903","NTUI TOW=
N","","13-08-2025 06:29:22","13-08-2025 06:14:47","13-08-2025 06:29:47","Ca=
scaded Incident from TTO5883254","Parker Tchoup","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Site impacted by NTUI T187 not managed b=
y IHS","franck.nkomot@matech-cameroun.com","875","13-08-2025 06:29:22","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005681898","SAA 2","=
","13-08-2025 06:29:21","13-08-2025 06:14:47","13-08-2025 06:29:47","Cascad=
ed Incident from TTO5883254","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by NTUI T187 not managed by IH=
S","franck.nkomot@matech-cameroun.com","874","13-08-2025 06:29:21","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005681897","Matsari"=
,"","13-08-2025 06:29:21","13-08-2025 06:14:47","13-08-2025 06:29:47","Casc=
aded Incident from TTO5883254","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by NTUI T187 not managed by =
IHS","franck.nkomot@matech-cameroun.com","874","13-08-2025 06:29:21","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005681899","Ngoum","=
","13-08-2025 06:29:21","13-08-2025 06:14:47","13-08-2025 06:29:47","Cascad=
ed Incident from TTO5883254","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by NTUI T187 not managed by IH=
S","franck.nkomot@matech-cameroun.com","874","13-08-2025 06:29:21","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005681896","MBIMBIM"=
,"","13-08-2025 06:29:20","13-08-2025 06:14:47","13-08-2025 06:29:47","Casc=
aded Incident from TTO5883254","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by NTUI T187 not managed by =
IHS","franck.nkomot@matech-cameroun.com","873","13-08-2025 06:29:20","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0005681855","O=
ssombe","IHS_YND_456, IHS_YND_460, IHS_YND_404, IHS_YND_475, IHS_YND_454, I=
HS_YND_434, IHS_YND_444, IHS_YND_403, IHS_YND_405, IHS_YND_473","13-08-2025=
 06:16:15","13-08-2025 06:14:47","13-08-2025 06:29:47","Site impacted by NT=
UI T187 not managed by IHS","Parker Tchoup","Customer Equipment Failure","A=
ctive","Active Equipment Failure","Affected by 3rd Party Site","Site impact=
ed by NTUI T187 not managed by IHS","vanel.mbiada@matech-cameroun.com","89"=
,"13-08-2025 06:16:15","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005681841","Eto=
ug ebe biscuiterie","","13-08-2025 06:14:34","13-08-2025 06:09:28","13-08-2=
025 06:27:05","Grid outage, Gen failed to start due to poor backup // Grid =
return","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, Gen failed to start due to poor back=
up // Grid return","franck.nkomot@matech-cameroun.com","307","13-08-2025 06=
:14:34","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005681762","Fla=
menco","","13-08-2025 05:47:06","13-08-2025 05:43:01","13-08-2025 08:53:19"=
,"Access issue at this hour due to landlord,// Site went down because Gen f=
ailed to start due to Gen battery stolen // He started with an external bat=
tery, site on Gen","Mboua Thierry","Access Denial","Lease Or Legal","Landlo=
rd Related Issues","Access Issue - Land Lord","Access issue at this hour du=
e to landlord,// Site went down because Gen failed to start due to Gen batt=
ery stolen // He started with an external battery, site on Gen","franck.nko=
mot@matech-cameroun.com","247","13-08-2025 05:47:06","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005681702","NKO=
MKANA ELIZA HOTEL","","13-08-2025 05:26:58","13-08-2025 05:17:32","13-08-20=
25 08:20:53","Grid outage, No space to deploy a MGE //  Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e, No space to deploy a MGE //  Grid return","franck.nkomot@matech-cameroun=
.com","1720","13-08-2025 05:26:58","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005681637","N=
kolso","","13-08-2025 04:58:07","13-08-2025 04:53:58","13-08-2025 05:56:39"=
,"Grid outage, Site went down before Gen start due to poor backup/ // Gen m=
anually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup/ // Gen manually started","vanel.mbiada@m=
atech-cameroun.com","250","13-08-2025 04:58:07","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005680913","Mba=
nkolo petit paris","","13-08-2025 00:06:53","12-08-2025 23:59:38","13-08-20=
25 00:08:38","No power issue, site is on gen with Ubaie=3D54.3V, Brice Tsag=
ue (650 21 40 96) from Huawei is informed.","Mboua Thierry","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue, site is on gen with Ubaie=3D54.3V, Brice Tsague (650 21 40 96)=
 from Huawei is informed.","franck.nkomot@matech-cameroun.com","436","13-08=
-2025 00:06:53","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005679926","Bit=
eng-Maetur","","12-08-2025 20:30:05","12-08-2025 20:28:54","12-08-2025 22:4=
1:57","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","Site went down due to disjunction o=
f CB (125A) in the PWC // He rearmed it, site on GRID","cedric.tiani@matech=
-cameroun.com","73","12-08-2025 20:30:05","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0005679701","Sac=
re Coeur Catholic Church","","12-08-2025 19:51:01","12-08-2025 19:49:54","1=
2-08-2025 19:51:46","Active//No power issue, site is on Grid with Ubaie 1=
=3D48.2V and Ubaie 2=3D50.9V.. The Tx FME Brice Tsague (650214096) from Hua=
wei is informed.","Mboua Thierry","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, site =
is on Grid with Ubaie 1=3D48.2V and Ubaie 2=3D50.9V.. The Tx FME Brice Tsag=
ue (650214096) from Huawei is informed.","cedric.tiani@matech-cameroun.com"=
,"68","12-08-2025 19:51:01","MATECH CMR"
"Closed Complete","Warning","CTR_441","IHS_YND_687","NOCINC0005679615","OLA=
MA","","12-08-2025 19:32:38","","","Grid outage, site Alarm because gen sta=
rt and stopped due to high temp // He added water and manually start the ge=
n","Fanda Brice","Warning","Warning","POWER","Warning - Gen Temp High","Gri=
d outage, site Alarm because gen start and stopped due to high temp // He a=
dded water and manually start the gen","vanel.mbiada@matech-cameroun.com","=
23198","12-08-2025 19:32:38","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005679204","AKA=
K Nkozoa","","12-08-2025 18:14:43","12-08-2025 18:05:59","12-08-2025 18:37:=
13","Active// No power issue, site is on Grid with Ubaie=3D50,4 V TX FME Sy=
mphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power issue, site is on Grid with Ubaie=3D50,4 V TX FME Sympho=
rien (650257151) from Huawei is informed","vanel.mbiada@matech-cameroun.com=
","690","12-08-2025 18:14:43","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005679188","S=
ous Prefecture","","12-08-2025 18:11:38","12-08-2025 18:08:13","12-08-2025 =
19:17:52","No power issue site on Grid Ubaie =3D54.5V, The tx Huawei Fulber=
t (654266068) is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 Grid Ubaie =3D54.5V, The tx Huawei Fulbert (654266068) is informed","vanel=
.mbiada@matech-cameroun.com","207","12-08-2025 18:11:38","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0005678640","A=
battoir","","12-08-2025 16:20:07","12-08-2025 16:16:53","12-08-2025 16:55:2=
0","Grid outage, site went down because gen start and stopped due to high t=
emp // He added water and manually start the gen","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Grid outage, site went down because gen start and stopped due to hig=
h temp // He added water and manually start the gen","vanel.mbiada@matech-c=
ameroun.com","195","12-08-2025 16:20:07","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005678459","O=
dza","","12-08-2025 15:44:01","12-08-2025 15:37:48","12-08-2025 15:45:04","=
Grid outage, site went down due to Grid bad voltage (lack of 01 phases) // =
He did bridge on good phase, site on Grid","Albran Byorel","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid outage, site=
 went down due to Grid bad voltage (lack of 01 phases) // He did bridge on =
good phase, site on Grid","vanel.mbiada@matech-cameroun.com","375","12-08-2=
025 15:44:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0005678437","Nkolanga=
a","","12-08-2025 15:39:58","12-08-2025 15:36:30","12-08-2025 15:39:31","Ca=
scaded Incident from TTO5879387","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went because 01/06 rectifiers=
 on site is faulty//He reset it and site on Grid(Replacement Ongoing )","ce=
dric.tiani@matech-cameroun.com","208","12-08-2025 15:39:58","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0005678433","Aba=
ng","IHS_YND_794, IHS_YND_289","12-08-2025 15:39:39","12-08-2025 15:36:30",=
"12-08-2025 15:39:31","Site went because 01/06 rectifiers on site is faulty=
//He reset it and site on Grid(Replacement Ongoing )","Mba Lazare Herve","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went becaus=
e 01/06 rectifiers on site is faulty//He reset it and site on Grid(Replacem=
ent Ongoing )","cedric.tiani@matech-cameroun.com","190","12-08-2025 15:39:3=
9","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005678429","Fou=
da Quarter","","12-08-2025 15:38:38","12-08-2025 15:37:30","12-08-2025 15:5=
9:43","Site went because 01/04 rectifiers on site is faulty//He reset it an=
d site on Grid","Delor Telezing","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went because 01/04 rectifiers on site is faulty//He=
 reset it and site on Grid","cedric.tiani@matech-cameroun.com","69","12-08-=
2025 15:38:38","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005678422","Nko=
ulou Carriere carrefourt","","12-08-2025 15:38:14","12-08-2025 15:36:30","1=
2-08-2025 15:39:31","","Mba Lazare Herve","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Site went because 01/06 rectifiers on site i=
s faulty//He reset it and site on Grid(Replacement Ongoing )","cedric.tiani=
@matech-cameroun.com","567","12-08-2025 15:38:14","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005678309","N=
komo","","12-08-2025 15:16:44","12-08-2025 15:14:25","12-08-2025 15:20:40",=
"Site went down due to work Biganstile DJANKO (650631358-DOWEN) is working =
on site (SWAP GE& DC BOX)// End of work","Mba Lazare Herve","Installation A=
ctivity","Passive","Planned Activity","Installation Activity","Site went do=
wn due to work Biganstile DJANKO (650631358-DOWEN) is working on site (SWAP=
 GE& DC BOX)// End of work","vanel.mbiada@matech-cameroun.com","140","12-08=
-2025 15:16:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005678165","Carrefou=
rt Nkomo","","12-08-2025 14:44:58","12-08-2025 14:30:45","12-08-2025 14:47:=
05","Cascaded Incident from TTO5878972","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to work =
Biganstile DJANKO (650631358-DOWEN) is working on site (SWAP GE& DC BOX)//E=
nd of work","vanel.mbiada@matech-cameroun.com","853","12-08-2025 14:44:58",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005678039","N=
komo","IHS_YND_174","12-08-2025 14:32:52","12-08-2025 14:30:45","12-08-2025=
 14:47:05","Site went down due to work Biganstile DJANKO (650631358-DOWEN) =
is working on site (SWAP GE& DC BOX)//End of work","Mba Lazare Herve","Inst=
allation Activity","Passive","Planned Activity","Installation Activity","Si=
te went down due to work Biganstile DJANKO (650631358-DOWEN) is working on =
site (SWAP GE& DC BOX)//End of work","vanel.mbiada@matech-cameroun.com","12=
8","12-08-2025 14:32:52","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005677927","E=
foulan","","12-08-2025 14:10:22","12-08-2025 14:07:13","12-08-2025 14:12:41=
","Grid outage, site went down Gen failed to start due to ATS dysfunctionin=
g on Site // He reset it and Site is on Grid","MINKA NICOLAS","Equipment Re=
pair","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went dow=
n Gen failed to start due to ATS dysfunctioning on Site // He reset it and =
Site is on Grid","vanel.mbiada@matech-cameroun.com","191","12-08-2025 14:10=
:22","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005677839","F=
ouda-New","","12-08-2025 13:54:08","12-08-2025 13:52:00","12-08-2025 13:55:=
11","Grid outage, site went down before Gen start due to Poor battery backu=
p // Grid return","Delor Telezing","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before Gen =
start due to Poor battery backup // Grid return","vanel.mbiada@matech-camer=
oun.com","943","12-08-2025 13:54:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005677680","SOA VILL=
AGE","","12-08-2025 13:28:40","12-08-2025 13:24:12","12-08-2025 13:51:02","=
Cascaded Incident from TTO5878558","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 Gen failed to start due to Hybrid system malfonction // /He reset it and s=
tarted the Gen manually","mouliom.anselme@matech-cameroun.com","268","12-08=
-2025 13:28:40","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005677676","S=
OA TOWN","IHS_YND_323","12-08-2025 13:27:18","12-08-2025 13:24:12","12-08-2=
025 13:51:46","Grid outage, site went down because Gen failed to start due =
to Hybrid system malfunction // /He reset it and started the Gen manually",=
"Siligap Boris","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid=
 outage, site went down because Gen failed to start due to Hybrid system ma=
lfonction // /He reset it and started the Gen manually","vanel.mbiada@matec=
h-cameroun.com","188","12-08-2025 13:27:18","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005677627","AKA=
K Nkozoa","","12-08-2025 13:16:01","12-08-2025 13:15:56","12-08-2025 13:24:=
15","Active// No power issue, site is on Grid with Ubaie=3D50,4 V TX FME Sy=
mphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power issue, site is on Grid with Ubaie=3D50,4 V TX FME Sympho=
rien (650257151) from Huawei is informed","mouliom.anselme@matech-cameroun.=
com","7","12-08-2025 13:16:01","MATECH CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0005677558","N=
goum","","12-08-2025 13:13:23","12-08-2025 13:08:11","12-08-2025 13:37:46",=
"site went down due to work (PM & emptying),// End of work","Parker Tchoup"=
,"Equipment Replacement","Passive","Planned Activity","Planned Activity - P=
assive","site went down due to work (PM & emptying),// End of work","vanel.=
mbiada@matech-cameroun.com","314","12-08-2025 13:13:23","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005677033","Hop=
ital Central","","12-08-2025 11:50:23","12-08-2025 11:48:17","12-08-2025 11=
:49:13","(Unstable) site went down due to insufficient rectifiers on site//=
Site stabilised","","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","(Unstable) site went down due to insufficient rectifiers on site//Sit=
e stabilised","mouliom.anselme@matech-cameroun.com","127","12-08-2025 11:50=
:23","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005676945","Mey=
o","","12-08-2025 11:38:26","12-08-2025 11:32:21","12-08-2025 11:50:21","Si=
te went down because SS IHS Felix BATEU was on site to deploy a transition =
to a secondary connection //End of work","Hyemafo Gildas","Installation Act=
ivity","Passive","Planned Activity","Installation Activity","Site went down=
 because SS IHS Felix BATEU was on site to deploy a transition to a seconda=
ry connection //End of work","mouliom.anselme@matech-cameroun.com","366","1=
2-08-2025 11:38:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0005676833","SOA UNIV=
ERSITY STADIUM","","12-08-2025 11:18:22","12-08-2025 11:12:48","12-08-2025 =
12:06:28","Cascaded Incident from TTO5877555","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage, Gen ran unt=
il  fuel shortage // Refueling done ","vanel.mbiada@matech-cameroun.com","3=
34","12-08-2025 11:18:22","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005676769","S=
oa-Sofamac","IHS_YND_720","12-08-2025 11:13:54","12-08-2025 11:12:48","12-0=
8-2025 12:06:28","Grid outage, Gen ran until  fuel shortage // Refueling do=
ne ","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outage","Grid=
 outage, Gen ran until  fuel shortage // Refueling done ","vanel.mbiada@mat=
ech-cameroun.com","67","12-08-2025 11:13:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0005676508","ARMP",""=
,"12-08-2025 10:25:38","12-08-2025 10:19:56","12-08-2025 10:36:59","Cascade=
d Incident from TTO5877249","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down because SS IHS Bernard Atangana was on s=
ite to secure transmission // End of work
","vanel.mbiada@matech-cameroun.com","342","12-08-2025 10:25:38","MATECH CM=
R"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0005676503","D=
ragage","IHS_YND_208","12-08-2025 10:24:03","12-08-2025 10:19:56","12-08-20=
25 10:36:59","Site went down because SS IHS Bernard Atangana was on site to=
 secure transmission // End of work","Mboua Thierry","Installation Activity=
","Passive","Planned Activity","Installation Activity","Site went down beca=
use SS IHS Bernard Atangana was on site to secure transmission // End of wo=
rk
","vanel.mbiada@matech-cameroun.com","248","12-08-2025 10:24:03","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0005676300","Bastos-B=
AT","","12-08-2025 09:51:55","12-08-2025 09:49:58","12-08-2025 09:52:11","C=
ascaded Incident from TTO5877030","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue site,site on Gri=
d, with Ubaie=3D54,3V V The Tx FME Eloundou Bertrand (652586578) from Huawe=
i is informed.","mouliom.anselme@matech-cameroun.com","117","12-08-2025 09:=
51:55","MATECH CMR"
"Closed Complete","Site Down","T0046","IHS_YND_191","NOCINC0005676298","Mba=
lla II","IHS_YND_129","12-08-2025 09:51:36","12-08-2025 09:49:58","12-08-20=
25 09:52:11","Active//No power issue site,site on Grid, with Ubaie=3D54,3V =
V The Tx FME Eloundou Bertrand (652586578) from Huawei is informed.","Delor=
 Telezing","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","Active//No power issue site,site on Grid, with Ubaie=
=3D54,3V V The Tx FME Eloundou Bertrand (652586578) from Huawei is informed=
.","mouliom.anselme@matech-cameroun.com","98","12-08-2025 09:51:36","MATECH=
 CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005675918","Eki=
e sud","","12-08-2025 08:42:45","12-08-2025 08:41:33","12-08-2025 09:19:01"=
,"Grid outage. Gen failed to start due to Hybrid systhem malfunctioning // =
Grid return","Albran Byorel","Equipment Repair","Passive","Hybrid","Hybrid =
Module","Grid outage. Gen failed to start due to Hybrid systhem malfunction=
ing // Grid return","vanel.mbiada@matech-cameroun.com","73","12-08-2025 08:=
42:45","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005675865","NKO=
MKANA ELIZA HOTEL","","12-08-2025 08:31:02","12-08-2025 08:27:51","12-08-20=
25 08:34:14","Grid outage, No space to deploy a MG // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 No space to deploy a MG // Grid return","vanel.mbiada@matech-cameroun.com"=
,"193","12-08-2025 08:31:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005675858","Bastos-N=
ylon","","12-08-2025 08:29:50","12-08-2025 08:25:53","12-08-2025 08:31:53",=
"Cascaded Incident from TTO5876514","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to PWC dysfunct=
ionning // Grid stabilised","vanel.mbiada@matech-cameroun.com","237","12-08=
-2025 08:29:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005675857","Golf Qua=
ter","","12-08-2025 08:29:50","12-08-2025 08:25:53","12-08-2025 08:31:53","=
Cascaded Incident from TTO5876514","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to PWC dysfuncti=
onning // Grid stabilised","vanel.mbiada@matech-cameroun.com","237","12-08-=
2025 08:29:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005675859","Bastos B=
ethesda","","12-08-2025 08:29:50","12-08-2025 08:25:53","12-08-2025 08:31:5=
3","Cascaded Incident from TTO5876514","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to PWC dysfu=
nctionning // Grid stabilised","vanel.mbiada@matech-cameroun.com","237","12=
-08-2025 08:29:50","MATECH CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0005675840","Tsi=
nga","IHS_YND_220, IHS_YND_126, IHS_YND_563","12-08-2025 08:27:58","12-08-2=
025 08:25:53","12-08-2025 08:39:35","Site went down due to PWC dysfunctionn=
ing // Grid stabilised","Mboua Thierry","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Site went down due to PWC dysfunctionn=
ing // Grid stabilised","vanel.mbiada@matech-cameroun.com","127","12-08-202=
5 08:27:58","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005675417","Nko=
abang Alembe","","12-08-2025 06:55:29","12-08-2025 06:53:20","12-08-2025 07=
:00:38","Site went down due to 02/03 rectifiers on site alarming//He reset =
it and site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down due to 02/03 rectifiers on site al=
arming//He reset it and site on Grid","vanel.mbiada@matech-cameroun.com","1=
30","12-08-2025 06:55:29","MATECH CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0005675401","NYO=
M","","12-08-2025 06:47:21","12-08-2025 06:42:11","12-08-2025 10:00:01","Po=
wer grid failure, generator shutdown due to high temperature alarm caused b=
y  the water temperature sensor faulty // disconnect water temperature sens=
or, reset generator board and manually start gen","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Power grid failure, generator shutdown due to high temperature alarm=
 caused by  the water temperature sensor faulty // disconnect water tempera=
ture sensor, reset generator board and manually start generator.","vanel.mb=
iada@matech-cameroun.com","311","12-08-2025 06:47:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005675288","Ngoum","=
","12-08-2025 06:12:53","12-08-2025 05:57:59","12-08-2025 07:05:39","Cascad=
ed Incident from TTO5875869","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down and gen failed to start du=
e to alarm oil pressure // Gen card reset and gen manually started","franck=
.nkomot@matech-cameroun.com","894","12-08-2025 06:12:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005675283","Yoko MTN=
","","12-08-2025 06:12:13","12-08-2025 05:57:59","12-08-2025 07:05:39","Cas=
caded Incident from TTO5875869","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down and gen failed to start=
 due to alarm oil pressure // Gen card reset and gen manually started","fra=
nck.nkomot@matech-cameroun.com","854","12-08-2025 06:12:13","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005675222","M=
atsari","IHS_YND_456, IHS_YND_475, IHS_YND_473","12-08-2025 06:02:08","12-0=
8-2025 05:57:59","12-08-2025 07:05:39","site went down and gen failed to st=
art due to alarm oil pressure // Gen card reset and gen manually started","=
Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","site went down and gen failed to start due to alarm oil pressure // Gen=
 card reset and gen manually started","vanel.mbiada@matech-cameroun.com","2=
50","12-08-2025 06:02:08","MATECH CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0005675220","M=
BIMBIM","","12-08-2025 06:01:33","12-08-2025 05:57:59","12-08-2025 07:05:39=
","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","site went down and gen failed to start due to alarm oil pressure =
// Gen card reset and gen manually started","vanel.mbiada@matech-cameroun.c=
om","767","12-08-2025 06:01:33","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005675217","N=
gouetou","","12-08-2025 05:59:56","12-08-2025 05:57:59","12-08-2025 06:57:5=
6","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","site went down and gen failed to start due to alarm oil pressure=
 // Gen card reset and gen manually started","vanel.mbiada@matech-cameroun.=
com","330","12-08-2025 05:59:56","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005674151","M=
EHANDAN","","12-08-2025 00:22:35","12-08-2025 00:13:23","12-08-2025 01:23:4=
5","Grid bad voltage, Site went down because gen fails to start due to grid=
 bad voltage // He bypass grid and manually start the gen	","Albran Byorel"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid bad voltage, Site went down because gen fails to start due to grid bad=
 voltage // He bypass grid and manually start the gen	","vanel.mbiada@matec=
h-cameroun.com","556","12-08-2025 00:22:35","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005673921","M=
vog-Manga","","11-08-2025 23:11:43","11-08-2025 23:10:37","11-08-2025 23:49=
:40","Grid fluctuations, site went down because  4/9 rectifiers  malfonctio=
n // Rectifiers reseted","Albran Byorel","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Grid fluctuations, site went down because  4/9 r=
ectifiers  malfonction // Rectifiers reseted","vanel.mbiada@matech-cameroun=
.com","69","11-08-2025 23:11:43","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005673711","Bit=
eng-Maetur","","11-08-2025 22:26:14","11-08-2025 22:24:03","11-08-2025 22:3=
8:42","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","cedric.=
tiani@matech-cameroun.com","133","11-08-2025 22:26:14","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005673237","Bit=
eng-Maetur","","11-08-2025 20:42:41","11-08-2025 20:38:30","11-08-2025 21:1=
2:25","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","cedric.=
tiani@matech-cameroun.com","253","11-08-2025 20:42:41","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005673171","N=
koabang2","","11-08-2025 20:24:57","11-08-2025 20:22:44","11-08-2025 20:24:=
26","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Site stabilised","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due t=
o gen overload (22KVA, 330A), SS Blaise IHS is informed // Site stabilised"=
,"cedric.tiani@matech-cameroun.com","135","11-08-2025 20:24:57","MATECH CMR=
"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0005672949","Av =
Kennedy","","11-08-2025 20:02:53","11-08-2025 20:00:45","11-08-2025 20:32:2=
8","Grid outage.no space to deploy mobile gen //Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no spa=
ce to deploy mobile gen //Grid return","cedric.tiani@matech-cameroun.com","=
129","11-08-2025 20:02:53","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005672932","E=
mombo","","11-08-2025 19:58:55","11-08-2025 19:56:46","11-08-2025 19:59:15"=
,"No power issue, site is on Grid with Ubaie=3D54,2V, TX FME Eloundou (6525=
86578) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue, site is on Grid with Ubaie=3D54,2V, TX FME Eloundou (652586578) from Hu=
awei is informed","vanel.mbiada@matech-cameroun.com","130","11-08-2025 19:5=
8:55","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005672504","M=
essassi 2","","11-08-2025 18:23:42","11-08-2025 18:22:21","11-08-2025 19:02=
:00","Grid otage,site went down because Gen failed to start due to *Unknown=
 Alarm*//He reset the Gen card and manually started Gen","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid otage,=
site went down because Gen failed to start due to *Unknown Alarm*//He reset=
 the Gen card and manually started Gen","vanel.mbiada@matech-cameroun.com",=
"84","11-08-2025 18:23:42","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005672322","Mey=
o","","11-08-2025 17:52:47","11-08-2025 17:50:37","11-08-2025 18:49:22","Si=
te went down due to CB(125A) in PWC that tripped MTN //He rearmed it and si=
te on Grid","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Circuit Breaker Issue","Site went down due to CB(125A) in P=
WC that tripped MTN //He rearmed it and site on Grid","cedric.tiani@matech-=
cameroun.com","131","11-08-2025 17:52:47","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005672212","Nko=
abang Alembe","","11-08-2025 17:34:27","11-08-2025 17:32:17","11-08-2025 17=
:40:27","Site went down due to 02/04 rectifiers on site alarming//He reset =
it and site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down due to 02/04 rectifiers on site al=
arming//He reset it and site on Grid","cedric.tiani@matech-cameroun.com","1=
31","11-08-2025 17:34:27","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005672122","Cit=
e des nations","","11-08-2025 17:14:16","11-08-2025 17:12:05","11-08-2025 1=
7:18:42","Grid outage,site went down before Gen started due to Poor battery=
 backup//Grid return","Paul BIBOUM","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage,site went down before Gen =
started due to Poor battery backup//Grid return","cedric.tiani@matech-camer=
oun.com","132","11-08-2025 17:14:16","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005672019","Hop=
ital Central","","11-08-2025 16:50:45","11-08-2025 16:48:38","11-08-2025 18=
:33:37","Grid outage No Space to deploy a MDG,//Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No Spa=
ce to deploy a MDG,//Grid return","cedric.tiani@matech-cameroun.com","128",=
"11-08-2025 16:50:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005671964","Nsam esc=
ale LP","","11-08-2025 16:38:57","11-08-2025 16:37:44","11-08-2025 16:43:34=
","Cascaded Incident from TTO5872264","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, Site went down before Gen start =
due to poor backup/ // Grid return","cedric.tiani@matech-cameroun.com","73"=
,"11-08-2025 16:38:57","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005671955","Nsa=
m Sofavinc","IHS_YND_732","11-08-2025 16:37:51","11-08-2025 16:37:44","11-0=
8-2025 16:43:34","Grid outage, Site went down before Gen start due to poor =
backup/ // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup/ // Grid return","cedric.tiani@matech-camerou=
n.com","8","11-08-2025 16:37:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005671696","ETOUDI C=
HAPELLE","","11-08-2025 15:49:59","11-08-2025 15:45:20","11-08-2025 15:51:2=
3","Cascaded Incident from TTO5871956","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Fluctuation, site went do=
wn before Gen start due to poor battery backup // Grid restoration","cedric=
.tiani@matech-cameroun.com","279","11-08-2025 15:49:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0005671695","Abattoir=
","","11-08-2025 15:49:58","11-08-2025 15:45:20","11-08-2025 15:51:23","Cas=
caded Incident from TTO5871956","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Fluctuation, site went down bef=
ore Gen start due to poor battery backup // Grid restoration","cedric.tiani=
@matech-cameroun.com","278","11-08-2025 15:49:58","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005671682","N=
koabang Ebolmedjock","","11-08-2025 15:49:04","11-08-2025 15:44:45","11-08-=
2025 15:52:44","Site impacted by Nkolmesseng-Abom(CTR-711) Not Manager By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Site impacted by Nkolmesseng-Abom(CTR-71=
1) Not Manager By IHS","vanel.mbiada@matech-cameroun.com","260","11-08-2025=
 15:49:04","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005671680","Eto=
udi","IHS_YND_244, IHS_YND_694","11-08-2025 15:48:29","11-08-2025 15:45:20"=
,"11-08-2025 15:51:23","Grid Fluctuation, site went down before Gen start d=
ue to poor battery backup // Grid restoration","Fabrice Pouakam","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid Fluc=
tuation, site went down before Gen start due to poor battery backup // Grid=
 restoration","cedric.tiani@matech-cameroun.com","190","11-08-2025 15:48:29=
","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005671676","Ngo=
usso Vallee","","11-08-2025 15:48:02","11-08-2025 15:46:38","11-08-2025 15:=
48:51","No power issue UBaie =3D54,2V site on Grid. The FME TX SYMPHORIEN (=
675295205) From Huawei is informed","Siligap Boris","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue UBaie =3D54,2V site on Grid. The FME TX SYMPHORIEN (675295205) From Hua=
wei is informed","cedric.tiani@matech-cameroun.com","85","11-08-2025 15:48:=
02","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005671495","N=
kolbong","","11-08-2025 15:20:06","11-08-2025 15:19:57","11-08-2025 15:37:1=
9","Grid outage, site went down because gen failed to start due to starter =
faulty//He replacced the starter and site on Grid","Delor Telezing","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid outage, site w=
ent down because gen failed to start due to starter faulty//He replacced th=
e starter and site on Grid","vanel.mbiada@matech-cameroun.com","11","11-08-=
2025 15:20:06","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0005671186","Val=
lee Bastos MTN","","11-08-2025 14:30:39","11-08-2025 14:29:27","11-08-2025 =
14:59:58","Site went down due to insufficient rectifiers (03)  on site //He=
 reset it and site on Gen","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficient rectifiers =
(03)  on site //He reset it and site on Gen","edwige.kapawo@matech-cameroun=
.com","73","11-08-2025 14:30:39","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005671015","N=
kolbong","","11-08-2025 14:18:05","11-08-2025 14:14:58","11-08-2025 15:10:2=
2","Grid outage, site went down because gen failed to start due to starter =
faulty// Grid Return","Delor Telezing","Equipment Repair","Passive","ACDG G=
en","ACDG - Kick Starter","Grid outage, site went down because gen failed t=
o start due to starter faulty// Grid Return","gerard.tchangoue@matech-camer=
oun.com","189","11-08-2025 14:18:05","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0005670848","N=
kolo II New","","11-08-2025 13:52:13","11-08-2025 13:49:30","11-08-2025 14:=
50:23","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage,site went down because Gen failed to start du=
e to PWC ZTE dysfunction//Grid return","gerard.tchangoue@matech-cameroun.co=
m","499","11-08-2025 13:52:13","MATECH CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0005670838","M=
imboman-Village","IHS_YND_709","11-08-2025 13:51:37","11-08-2025 13:49:30",=
"11-08-2025 14:50:23","Grid outage,site went down because Gen failed to sta=
rt due to PWC ZTE dysfunction//Grid return","Mba Lazare Herve","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage,sit=
e went down because Gen failed to start due to PWC ZTE dysfunction//Grid re=
turn","gerard.tchangoue@matech-cameroun.com","128","11-08-2025 13:51:37","M=
ATECH CMR"
"Closed Complete","Warning","T0058","IHS_YND_293","NOCINC0005670776","Nkoab=
ang MTN","","11-08-2025 13:43:36","","","site alarmin high temp due to evap=
orator faulty (Remplacement on going) // Shelter open","Mba Lazare Herve","=
Warning","Warning","POWER","Warning - AC Failure","site alarmin high temp d=
ue to evaporator faulty (Remplacement on going) // Shelter open","gerard.tc=
hangoue@matech-cameroun.com","703938","11-08-2025 13:43:36","MATECH CMR"
"Closed Complete","Warning","T0468","IHS_YND_120","NOCINC0005670749","Sapeu=
r Mimboman","","11-08-2025 13:39:26","","","Our FME Aboubakar manage and sa=
ys that, the connections need to be changed // Shelter open","Mba Lazare He=
rve","Warning","Warning","POWER","Warning - AC Failure","Our FME Aboubakar =
manage and says that, the connections need to be changed // Shelter open","=
gerard.tchangoue@matech-cameroun.com","597493","11-08-2025 13:39:26","MATEC=
H CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005670699","Nko=
lnda","","11-08-2025 13:30:00","08-08-2025 10:32:48","08-08-2025 11:08:24",=
"ticket error / site alrming High temp, Our FME Aboubakar was on site","Alb=
ran Byorel","Incorrectly Logged Tickets","Error","Error","Error","ticket er=
ror / site alrming High temp, Our FME Aboubakar was on site","gerard.tchang=
oue@matech-cameroun.com","269834","11-08-2025 13:30:00","MATECH CMR"
"Cancelled","Warning","T0210","IHS_YND_206","NOCINC0005670679","ARMP","","1=
1-08-2025 13:28:30","","","ticket error / site alrming High temp, Sadeu is =
inform and he is manage to open the door because Air-con is HS","Mboua Thie=
rry","","","","","","gerard.tchangoue@matech-cameroun.com","6082","11-08-20=
25 13:28:30","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005670494","N=
koabang2","","11-08-2025 13:01:44","11-08-2025 12:57:29","11-08-2025 14:11:=
04","	Grid outage, site went down due to gen overload (22KVA, 330A), SS Bla=
ise IHS is informed // Site stabilised","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","	Grid outage, site went down due=
 to gen overload (22KVA, 330A), SS Blaise IHS is informed // Site stabilise=
d","gerard.tchangoue@matech-cameroun.com","257","11-08-2025 13:01:44","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005670487","N=
koabang Ebolmedjock","","11-08-2025 13:00:50","11-08-2025 12:58:36","11-08-=
2025 13:08:35","Site impacted by Nkolmesseng-Abom(CTR-711) Not Manager By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Site impacted by Nkolmesseng-Abom(CTR-71=
1) Not Manager By IHS","gerard.tchangoue@matech-cameroun.com","136","11-08-=
2025 13:00:50","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005670014","Cit=
e des nations","","11-08-2025 11:59:50","11-08-2025 11:57:44","11-08-2025 1=
2:17:47","site went down because FME Roberto (674715333/GAUO) is on site fo=
r maintenance work // End of work","Paul BIBOUM","Installation Activity","P=
assive","Planned Activity","Installation Activity","site went down because =
FME Roberto (674715333/GAUO) is on site for maintenance work // End of work=
","edwige.kapawo@matech-cameroun.com","127","11-08-2025 11:59:50","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005669898","OTELE MT=
N","","11-08-2025 11:36:51","11-08-2025 11:32:06","11-08-2025 11:35:11","Ca=
scaded Incident from TTO5869965","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by Ngoumou who is not managi=
ng by IHS. ","edwige.kapawo@matech-cameroun.com","285","11-08-2025 11:36:51=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005669897","OLAMA","=
","11-08-2025 11:36:51","11-08-2025 11:32:06","11-08-2025 11:35:11","Cascad=
ed Incident from TTO5869965","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by Ngoumou who is not managing b=
y IHS. ","edwige.kapawo@matech-cameroun.com","285","11-08-2025 11:36:51","M=
ATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005669881","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371","11-08-2025 11:34:17","11-08-20=
25 11:32:06","11-08-2025 11:35:11","Site impacted by Ngoumou who is not man=
aging by IHS. ","Fanda Brice","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Site impacted by Ngoumou who is n=
ot managing by IHS. ","edwige.kapawo@matech-cameroun.com","133","11-08-2025=
 11:34:17","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005669863","Mim=
boman4","","11-08-2025 11:29:10","11-08-2025 11:22:05","11-08-2025 12:44:20=
","Grid outage, site went down because Gen started and stopped due to GEN b=
attery faulty // He restarted Gen with an external battery, site on Gen","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator =
Battery","Grid outage, site went down because Gen started and stopped due t=
o GEN battery faulty // He restarted Gen with an external battery, site on =
Gen","gerard.tchangoue@matech-cameroun.com","427","11-08-2025 11:29:10","MA=
TECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005669738","Nko=
lbong","","11-08-2025 11:09:51","11-08-2025 11:06:45","11-08-2025 13:14:04"=
,"Grid outage, site went down because gen failed to start due to starter fa=
ulty // Grid return","Delor Telezing","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Kick Starter","Grid outage, site went down because gen failed to=
 start due to starter faulty // Grid return","gerard.tchangoue@matech-camer=
oun.com","243","11-08-2025 11:09:51","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005669420","MBA=
LNGONG LYCEE","","11-08-2025 10:20:31","11-08-2025 10:20:24","11-08-2025 10=
:27:34","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down=
 due Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed =
// Grid return","edwige.kapawo@matech-cameroun.com","10","11-08-2025 10:20:=
31","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0005668980","SAA=
 2","","11-08-2025 09:06:07","11-08-2025 09:05:57","11-08-2025 09:19:08","s=
ite went down due to  Grid Contactor open because the relay that powers it =
was disconnected. // We just tighten the Siemens relay that powers it at 48=
V and the contactor closed, then the site came ba","Parker Tchoup","Equipme=
nt Repair","Passive","Control Panel","ATS Relay Faulty","site went down due=
 to  Grid Contactor open because the relay that powers it was disconnected.=
 // We just tighten the Siemens relay that powers it at 48V and the contact=
or closed, then the site came back up.","edwige.kapawo@matech-cameroun.com"=
,"12","11-08-2025 09:06:07","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005668820","Mim=
boman","","11-08-2025 08:37:39","11-08-2025 08:36:34","11-08-2025 10:09:20"=
,"Grid outage, Site went down due to Gen overload (120A, 12kva, AC 24 btu) =
// He reduced LOAD, site on GEN","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to Gen =
overload (120A, 12kva, AC 24 btu) // He reduced LOAD, site on GEN","edwige.=
kapawo@matech-cameroun.com","66","11-08-2025 08:37:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005668818","ETOUDI C=
HAPELLE","","11-08-2025 08:36:57","11-08-2025 08:32:10","11-08-2025 08:35:1=
7","Cascaded Incident from TTO5868749","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active // No power issue site on =
grid with Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is inform=
ed. Notice that it is a repetitive issue.","edwige.kapawo@matech-cameroun.c=
om","287","11-08-2025 08:36:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005668819","Etoudi 2=
","","11-08-2025 08:36:57","11-08-2025 08:32:10","11-08-2025 08:35:17","Cas=
caded Incident from TTO5868749","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active // No power issue site on grid w=
ith Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. No=
tice that it is a repetitive issue.","edwige.kapawo@matech-cameroun.com","2=
87","11-08-2025 08:36:57","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005668814","Aba=
ttoir","IHS_YND_694, IHS_YND_211","11-08-2025 08:36:16","11-08-2025 08:32:1=
0","11-08-2025 08:35:17","Active // No power issue site on grid with Ubaie:=
 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. Notice that =
it is a repetitive issue.","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power=
 issue site on grid with Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Hu=
awei) is informed. Notice that it is a repetitive issue.","edwige.kapawo@ma=
tech-cameroun.com","249","11-08-2025 08:36:16","MATECH CMR"
"Closed Complete","Site Down","T2292","IHS_YND_453","NOCINC0005668531","Son=
g-bong","","11-08-2025 07:24:07","11-08-2025 07:23:01","11-08-2025 09:51:46=
","Site went down because Gen started and stopped due to disjunction of Gen=
 CB (30A) // He rearmed CB, site on GEN","Kemeni Franklin","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Load Breaker","Site went down because Gen s=
tarted and stopped due to disjunction of Gen CB (30A) // He rearmed CB, sit=
e on GEN","edwige.kapawo@matech-cameroun.com","67","11-08-2025 07:24:07","M=
ATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005668313","Mim=
boman","","11-08-2025 06:31:39","11-08-2025 06:25:32","11-08-2025 08:03:51"=
,"Grid outage, Site went down due to Gen overload (120A, 12kva, AC 24 btu) =
// He reduced LOAD, site on GEN","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to Gen =
overload (120A, 12kva, AC 24 btu) // He reduced LOAD, site on GEN","edwige.=
kapawo@matech-cameroun.com","367","11-08-2025 06:31:39","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0005667972","Eto=
ug-Ebe 2","","11-08-2025 04:43:44","11-08-2025 04:41:33","11-08-2025 09:24:=
15","Grid outage no space to deploy a mobil gen // grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no =
space to deploy a mobil gen // grid return","edwige.kapawo@matech-cameroun.=
com","132","11-08-2025 04:43:44","MATECH CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0005667351","N=
koabang","","11-08-2025 00:32:49","11-08-2025 00:31:01","11-08-2025 01:08:5=
4","FME Roland (695942704/CDS Technologie) is on site for Work (Migration O=
range services) // End of work","Mba Lazare Herve","Installation Activity",=
"Passive","Planned Activity","Installation Activity","FME Roland (695942704=
/CDS Technologie) is on site for Work (Migration Orange services) // End of=
 work","gerard.tchangoue@matech-cameroun.com","109","11-08-2025 00:32:49","=
MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005667248","Mim=
boman","","10-08-2025 23:44:09","10-08-2025 22:48:01","11-08-2025 06:04:23"=
,"Site went down due to Gen overload (120A, 12kva) // Site stabilized","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","S=
ite went down due to Gen overload (120A, 12kva) // Site stabilized","stepha=
ne.nkamwa@ihstowers.com","3396","10-08-2025 23:44:09","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005667067","N=
kolbong","","10-08-2025 23:07:27","10-08-2025 23:06:19","11-08-2025 10:42:2=
6","Grid outage, site went down because gen failed to start due to starter =
faulty // Grid return","Delor Telezing","Equipment Repair","Passive","ACDG =
Gen","ACDG - Kick Starter","Grid outage, site went down because gen failed =
to start due to starter faulty // Grid return","gerard.tchangoue@matech-cam=
eroun.com","70","10-08-2025 23:07:27","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005667061","Mim=
boman4","","10-08-2025 23:05:05","10-08-2025 23:02:55","10-08-2025 23:20:00=
","Grid fluctuations, site went down because Gen failed to start due to gri=
d bad voltage // He bypassed Grid and started Gen manually","Mba Lazare Her=
ve","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuations, site went down because Gen failed to start due to gri=
d bad voltage // He bypassed Grid and started Gen manually","edwige.kapawo@=
matech-cameroun.com","132","10-08-2025 23:05:05","MATECH CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0005667056","M=
imboman-Village","","10-08-2025 23:03:53","10-08-2025 22:58:39","11-08-2025=
 01:08:31","Grid fluctuations, site went down due to Grid bad voltage // He=
  bypassed Grid and started Gen manually","Mba Lazare Herve","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
ns, site went down due to Grid bad voltage // He  bypassed Grid and started=
 Gen manually","gerard.tchangoue@matech-cameroun.com","315","10-08-2025 23:=
03:53","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005667000","N=
koabang2","","10-08-2025 22:49:58","10-08-2025 22:47:53","10-08-2025 23:18:=
46","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Site stabilised","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due t=
o gen overload (22KVA, 330A), SS Blaise IHS is informed // Site stabilised"=
,"gerard.tchangoue@matech-cameroun.com","126","10-08-2025 22:49:58","MATECH=
 CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005666965","Bit=
eng-Maetur","","10-08-2025 22:41:51","10-08-2025 22:37:41","11-08-2025 00:3=
9:18","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","edwige.=
kapawo@matech-cameroun.com","252","10-08-2025 22:41:51","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005666966","N=
GONA","","10-08-2025 22:41:51","10-08-2025 22:32:44","10-08-2025 23:19:52",=
"Grid fluctuations, site went down because Gen failed to start due to grid =
bad voltage // He bypassed Grid and started Gen manually","Mba Lazare Herve=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuations, site went down because Gen failed to start due to grid =
bad voltage // He bypassed Grid and started Gen manually","gerard.tchangoue=
@matech-cameroun.com","549","10-08-2025 22:41:51","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005666944","Mim=
boman4","","10-08-2025 22:37:31","10-08-2025 22:27:59","10-08-2025 22:40:21=
","Grid fluctuations, site went down because Gen failed to start due to gri=
d bad voltage // He bypassed Grid and started Gen manually","Mba Lazare Her=
ve","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuations, site went down because Gen failed to start due to gri=
d bad voltage // He bypassed Grid and started Gen manually","edwige.kapawo@=
matech-cameroun.com","574","10-08-2025 22:37:31","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005666687","L=
abogenie","IHS_YND_568","10-08-2025 21:51:14","10-08-2025 21:51:10","11-08-=
2025 13:00:23","Grid only site , Grid outage.no space to deploy mobile gen =
// Grid return","","Grid Supply","Passive","Grid","National Grid - Grid Out=
age Issue","Grid only site , Grid outage.no space to deploy mobile gen // G=
rid return","vanel.mbiada@matech-cameroun.com","6","10-08-2025 21:51:14","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0005666677","A=
nguissa New","","10-08-2025 21:49:22","10-08-2025 21:51:10","11-08-2025 13:=
00:23","Grid only site , Grid outage.no space to deploy mobile gen //  Grid=
 Return","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid only site , Grid outage.no space to deploy mobile gen //=
  Grid Return","vanel.mbiada@matech-cameroun.com","313","10-08-2025 21:49:2=
2","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0005666662","C=
RF Nkoabang","","10-08-2025 21:46:38","10-08-2025 21:43:32","10-08-2025 23:=
21:32","Grid-solar site, Grid outage, site down due to sunset, // Grid retu=
rn","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Grid=
 Outage Issue","Grid-solar site, Grid outage, site down due to sunset, // G=
rid return","vanel.mbiada@matech-cameroun.com","187","10-08-2025 21:46:38",=
"MATECH CMR"
"Closed Complete","Warning","T0652","IHS_YND_222","NOCINC0005666638","Jean =
Vespa","","10-08-2025 21:41:49","","","Grid fluctuation site went down beca=
use Gen failed to start due to Grid bad voltage and No RCP on site // Grid =
Return","Mboua Thierry","Warning","Warning","POWER","Warning - Grid Voltage=
 Failure","Grid fluctuation site went down because Gen failed to start due =
to Grid bad voltage and No RCP on site // Grid Return","franck.nkomot@matec=
h-cameroun.com","611","10-08-2025 21:41:49","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0005666553","N=
kolo II New","","10-08-2025 21:27:16","10-08-2025 21:25:40","11-08-2025 00:=
02:47","Grid outage, site went down due to Grid bad voltage // He bypassed =
Grid and started Gen manually","Mba Lazare Herve","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Grid outage, site went dow=
n due to Grid bad voltage // He bypassed Grid and started Gen manually","va=
nel.mbiada@matech-cameroun.com","98","10-08-2025 21:27:16","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005666468","O=
dza","","10-08-2025 21:09:39","10-08-2025 21:03:32","10-08-2025 21:20:11","=
Grid outage, site went down due to Grid bad voltage (lack of 02 phases) // =
He did bridge on good phase, site on Grid","Albran Byorel","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid outage, site=
 went down due to Grid bad voltage (lack of 02 phases) // He did bridge on =
good phase, site on Grid","vanel.mbiada@matech-cameroun.com","368","10-08-2=
025 21:09:39","MATECH CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0005666427","N=
koabang","IHS_YND_526","10-08-2025 21:01:17","10-08-2025 20:58:11","10-08-2=
025 23:20:32","Grid outage, site went down due to Grid bad voltage // He by=
passed Grid and started Gen manually","Mba Lazare Herve","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid outage, site w=
ent down due to Grid bad voltage // He bypassed Grid and started Gen manual=
ly","vanel.mbiada@matech-cameroun.com","187","10-08-2025 21:01:17","MATECH =
CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005666316","Bit=
eng-Maetur","","10-08-2025 20:38:12","10-08-2025 20:28:59","10-08-2025 21:2=
0:59","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","franck.=
nkomot@matech-cameroun.com","3329","10-08-2025 20:38:12","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005666142","E=
mombo","","10-08-2025 20:02:14","10-08-2025 20:00:07","10-08-2025 20:03:30"=
,"No power issue, site is on Grid with Ubaie=3D54,2V, TX FME Eloundou (6525=
86578) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue, site is on Grid with Ubaie=3D54,2V, TX FME Eloundou (652586578) from Hu=
awei is informed","vanel.mbiada@matech-cameroun.com","128","10-08-2025 20:0=
2:14","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005666104","NYO=
M FACE MAETUR","","10-08-2025 19:53:27","10-08-2025 19:51:11","10-08-2025 2=
1:41:11","Grid fluctuations , site went down because Gen failed to start du=
e to Grid bad voltage // He made a bridge with the Good phase","Fabrice Pou=
akam","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuations , site went down because Gen failed to start due to =
Grid bad voltage // He made a bridge with the Good phase","franck.nkomot@ma=
tech-cameroun.com","138","10-08-2025 19:53:27","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005666054","N=
koabang2","","10-08-2025 19:40:13","10-08-2025 19:37:04","10-08-2025 22:43:=
13","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Site stabilised","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due t=
o Gen overload (22KVA, 330A), SS Blaise IHS is informed// Grid return (","v=
anel.mbiada@matech-cameroun.com","192","10-08-2025 19:40:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005665859","Nkolfon =
Cimencam","","10-08-2025 19:00:14","10-08-2025 18:39:59","10-08-2025 18:50:=
20","Cascaded Incident from TTO5865359","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site down because of work ( S=
wap of GE ) // End of work","vanel.mbiada@matech-cameroun.com","1215","10-0=
8-2025 19:00:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005665858","Ahala","=
","10-08-2025 19:00:13","10-08-2025 18:39:59","10-08-2025 18:50:20","Cascad=
ed Incident from TTO5865359","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site down because of work ( Swap of GE )=
 // End of work","vanel.mbiada@matech-cameroun.com","1214","10-08-2025 19:0=
0:13","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005665829","Mey=
o","IHS_YND_257, IHS_YND_762","10-08-2025 18:49:32","10-08-2025 18:39:59","=
10-08-2025 18:56:38","Site down because of work ( Swap of GE ) // End of wo=
rk","Hyemafo Gildas","Equipment Replacement","Passive","Planned Activity","=
Generator Servicing","Site down because of work ( Swap of GE ) // End of wo=
rk","franck.nkomot@matech-cameroun.com","574","10-08-2025 18:49:32","MATECH=
 CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005665702","Mim=
boman","","10-08-2025 18:26:22","10-08-2025 18:24:13","10-08-2025 22:04:28"=
,"Site went down due to Gen overload (120A, 12kva) // Site stabilized","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","S=
ite went down due to Gen overload (120A, 12kva) // Site stabilized","franck=
.nkomot@matech-cameroun.com","130","10-08-2025 18:26:22","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005665527","S=
tade-Abega","","10-08-2025 18:07:07","10-08-2025 18:01:00","10-08-2025 18:0=
9:11","No power issue, site is on grid with Ubaie=3D53.6V, Lionel adjep(655=
184876) from Huawei is informed.","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53.6V, Lionel adjep(655184876) from Huaw=
ei is informed.","vanel.mbiada@matech-cameroun.com","368","10-08-2025 18:07=
:07","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005665364","N=
koabang Ebolmedjock","","10-08-2025 17:31:00","10-08-2025 17:27:36","10-08-=
2025 18:57:01","Grid outage,site went down because Gen started and stopped =
 due to Alarm*Memory corruption*//He reset the Gen Card and started the Gen=
 manually","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Grid outage,site went down because Gen started and stopp=
ed  due to Alarm*Memory corruption*//He reset the Gen Card and started the =
Gen manually","vanel.mbiada@matech-cameroun.com","206","10-08-2025 17:31:00=
","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0005665235","Ole=
mbe MTN","","10-08-2025 17:08:45","10-08-2025 17:04:35","10-08-2025 17:44:3=
5","Site went down because Gen failed to start due to Grid bad voltage // G=
rid return","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid=
 - Phase Controller Faulty","Site went down because Gen failed to start due=
 to Grid bad voltage // Grid return","franck.nkomot@matech-cameroun.com","2=
51","10-08-2025 17:08:45","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0005665080","Men=
dong vallee","","10-08-2025 16:40:18","10-08-2025 16:36:02","10-08-2025 16:=
54:02","Grid outage, site went down because gen failed to start due to PWC =
ZTE malfunction // He reset the controller, Site on Grid","Fanda Brice","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid o=
utage, site went down because gen failed to start due to PWC ZTE malfunctio=
n // He reset the controller, Site on Grid","franck.nkomot@matech-cameroun.=
com","257","10-08-2025 16:40:18","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005664956","N=
kozoa","","10-08-2025 16:19:36","10-08-2025 16:15:22","10-08-2025 16:27:07"=
,"Site went down due to disjunction of CB (125A) in the Huawei PWC // He re=
armed it, site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to =
disjunction of CB (125A) in the Huawei PWC // He rearmed it, site on Grid",=
"vanel.mbiada@matech-cameroun.com","256","10-08-2025 16:19:36","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005664911","M=
endong vallee","","10-08-2025 16:10:41","10-08-2025 16:07:33","10-08-2025 1=
6:15:00","Grid outage, site went down because gen failed to start due to PW=
C ZTE malfunction // He reset the controller, Site on Grid","Fanda Brice","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage, site went down because gen failed to start due to PWC ZTE malfunct=
ion // He reset the controller, Site on Grid","vanel.mbiada@matech-cameroun=
.com","189","10-08-2025 16:10:41","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005664904","Mim=
boman","","10-08-2025 16:08:43","10-08-2025 16:07:30","10-08-2025 16:13:30"=
,"Site went down due to Gen overload (120A, 12kva) // Site stabilized","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","S=
ite went down due to Gen overload (120A, 12kva) // Site stabilized","franck=
.nkomot@matech-cameroun.com","74","10-08-2025 16:08:43","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0005664882","Nko=
zoa","","10-08-2025 16:05:06","10-08-2025 16:01:01","10-08-2025 16:10:01","=
Site went down due to disjunction of CB (125A) in the Huawei PWC // He rear=
med it, site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to di=
sjunction of CB (125A) in the Huawei PWC // He rearmed it, site on Grid","f=
ranck.nkomot@matech-cameroun.com","247","10-08-2025 16:05:06","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005664863","Elo=
umdem stade","","10-08-2025 16:02:30","10-08-2025 15:59:20","10-08-2025 17:=
07:20","Grid outage, site went down because gen fails to start due to batte=
ry ge faulty // Gen start with battery backup","Fanda Brice","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, site wen=
t down because gen fails to start due to battery ge faulty // Gen start wit=
h battery backup","franck.nkomot@matech-cameroun.com","191","10-08-2025 16:=
02:30","MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0005664675","B=
astos Bir","","10-08-2025 15:31:11","10-08-2025 12:46:16","10-08-2025 15:12=
:37","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid bad voltage,site down because,gen fails to start due to g=
rid bad voltage // Grid bypass. site left on gen","kouoh.jean@ihstowers.com=
","9922","10-08-2025 15:31:11","MATECH CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0005664419","B=
ondjock","","10-08-2025 14:54:24","10-08-2025 14:47:20","10-08-2025 15:00:2=
9","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Act=
ive","Site impacted by Ngoumou who is not managing by IHS. ","vanel.mbiada@=
matech-cameroun.com","639","10-08-2025 14:54:24","MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0005664416","M=
beng","","10-08-2025 14:53:56","10-08-2025 14:47:20","10-08-2025 15:00:29",=
"","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active=
","Site impacted by Ngoumou who is not managing by IHS. ","vanel.mbiada@mat=
ech-cameroun.com","663","10-08-2025 14:53:56","MATECH CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0005664410","M=
inka","","10-08-2025 14:53:13","10-08-2025 14:47:20","11-08-2025 11:35:11",=
"","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active=
","Site impacted by Ngoumou who is not managing by IHS. ","vanel.mbiada@mat=
ech-cameroun.com","615","10-08-2025 14:53:13","MATECH CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0005664405","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_372","10-08-2025 14:52:30","10-08-20=
25 14:47:20","11-08-2025 11:35:11","Grid outage gen failed to start due to =
card GE dysfunctionning//We reset card GE and gen manually started ","Fanda=
 Brice","Cascade Outage","Active","Cascade Active","Cascade Active","Site i=
mpacted by Ngoumou who is not managing by IHS. ","vanel.mbiada@matech-camer=
oun.com","311","10-08-2025 14:52:30","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005663988","E=
mombo","","10-08-2025 14:13:34","10-08-2025 14:12:26","10-08-2025 15:27:26"=
,"Grid outage, Site  down because  03/05 rectifiers malfunctioning on site =
// He reset rectifiers, Site on Grid","Mba Lazare Herve","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Grid outage, Site  down because =
 03/05 rectifiers malfunctioning on site // He reset rectifiers, Site on Gr=
id","cedric.tiani@matech-cameroun.com","69","10-08-2025 14:13:34","MATECH C=
MR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005663938","M=
arche Odza","","10-08-2025 13:59:31","10-08-2025 13:56:00","10-08-2025 15:0=
7:18","Grid fluctuation,site down due to rectifiers dysfunction//Grid stabi=
lisation","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Grid fluctuation,site down due to rectifiers dysfunc=
tion//Grid stabilisation","vanel.mbiada@matech-cameroun.com","212","10-08-2=
025 13:59:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0005663561","ARMP",""=
,"10-08-2025 12:50:11","10-08-2025 12:46:16","10-08-2025 15:12:37","Cascade=
d Incident from TTO5862727","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid bad voltage,site down because,gen fails to start d=
ue to grid bad voltage // Grid bypass. site left on gen","vanel.mbiada@mate=
ch-cameroun.com","235","10-08-2025 12:50:11","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0005663557","D=
ragage","IHS_YND_704, IHS_YND_208","10-08-2025 12:48:38","10-08-2025 12:46:=
16","10-08-2025 15:19:43","Grid bad voltage,site down because,gen fails to =
start due to grid bad voltage // Grid bypass. site left on gen","Mboua Thie=
rry","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid bad voltage,site down because,gen fails to start due to grid bad v=
oltage // Grid bypass. site left on gen","vanel.mbiada@matech-cameroun.com"=
,"144","10-08-2025 12:48:38","MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0005663433","Nko=
lmvack","","10-08-2025 12:26:45","10-08-2025 12:24:35","10-08-2025 13:33:09=
","Grid outage, Site went down because Gen start and stopped with ""High te=
mp""alarm // he added water and manually started the Gen","Parker Tchoup","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, Site went down because Gen start and stopped with=
 ""High temp""alarm // he added water and manually started the Gen","cedric=
.tiani@matech-cameroun.com","132","10-08-2025 12:26:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005663369","OLAMA","=
","10-08-2025 12:12:50","10-08-2025 12:09:06","10-08-2025 12:12:26","Cascad=
ed Incident from TTO5862493","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue, Site impacted by Ngoumou Camra=
il not managed by IHS","cedric.tiani@matech-cameroun.com","224","10-08-2025=
 12:12:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0005663371","Akono","=
","10-08-2025 12:12:50","10-08-2025 12:09:06","10-08-2025 12:12:26","Cascad=
ed Incident from TTO5862493","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue, Site impacted by Ngoumou Camra=
il not managed by IHS","cedric.tiani@matech-cameroun.com","224","10-08-2025=
 12:12:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005663370","Mom","",=
"10-08-2025 12:12:50","10-08-2025 12:09:06","10-08-2025 12:12:26","Cascaded=
 Incident from TTO5862493","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue, Site impacted by Ngoumou Camrail=
 not managed by IHS","cedric.tiani@matech-cameroun.com","224","10-08-2025 1=
2:12:50","MATECH CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0005663367","B=
astos-BAT","","10-08-2025 12:12:17","10-08-2025 12:10:10","10-08-2025 12:32=
:52","FME Thierry report access issue during the weekend//Grid return","Mbo=
ua Thierry","Access Denial","Lease Or Legal","Landlord Related Issues","Acc=
ess Issue - Land Lord","FME Thierry report access issue during the weekend/=
/Grid return","vanel.mbiada@matech-cameroun.com","128","10-08-2025 12:12:17=
","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0005663360","Min=
ka","IHS_YND_687, IHS_YND_370, IHS_YND_365","10-08-2025 12:11:50","10-08-20=
25 12:09:06","10-08-2025 12:12:26","No power issue, Site impacted by Ngoumo=
u Camrail not managed by IHS","Fanda Brice","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, Sit=
e impacted by Ngoumou Camrail not managed by IHS","cedric.tiani@matech-came=
roun.com","165","10-08-2025 12:11:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005663071","MEHANDAN=
","","10-08-2025 10:57:44","10-08-2025 10:39:42","10-08-2025 11:50:04","Cas=
caded Incident from TTO5862164","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active: No power issue on site Ubaie =3D5=
4.4V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei is info=
rme","vanel.mbiada@matech-cameroun.com","1082","10-08-2025 10:57:44","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005663070","O=
dza II OCM","IHS_YND_528","10-08-2025 10:57:11","10-08-2025 10:39:42","10-0=
8-2025 11:50:04","Active: No power issue on site Ubaie =3D54.4V site on Gri=
d. The TX FME Lionnel Adhex (655184876) from Huawei is informe","Albran Byo=
rel","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active: No power issue on site Ubaie =3D54.4V site on Grid=
. The TX FME Lionnel Adhex (655184876) from Huawei is informe","vanel.mbiad=
a@matech-cameroun.com","1052","10-08-2025 10:57:11","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005663069","AKA=
K Nkozoa","","10-08-2025 10:56:55","10-08-2025 10:54:23","10-08-2025 11:06:=
49","Grid outage, site went down baecause gen failed to start due to batter=
y Gen faulty // Gen manually start with external battery","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid o=
utage, site went down baecause gen failed to start due to battery Gen fault=
y // Gen manually start with external battery","cedric.tiani@matech-camerou=
n.com","153","10-08-2025 10:56:55","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005663043","Men=
dong NB","","10-08-2025 10:50:54","10-08-2025 08:47:22","10-08-2025 17:13:2=
5","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Si=
te went down due to Gen overload (17kva //180A) SS HIS Felix Zambe is infor=
med and confirmed//Grid return","cedric.tiani@matech-cameroun.com","7625","=
10-08-2025 10:50:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0005662977","Nsimalen=
 OCM","","10-08-2025 10:42:35","10-08-2025 10:39:29","10-08-2025 11:49:25",=
"Cascaded Incident from TTO5862026","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down baecau=
se gen failed to start due to battery Gen discharge // Gen manually start w=
ith external battery","vanel.mbiada@matech-cameroun.com","186","10-08-2025 =
10:42:35","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0005662946","N=
kolda","IHS_YND_327","10-08-2025 10:41:13","10-08-2025 10:39:29","10-08-202=
5 11:49:25","Grid outage, site went down baecause gen failed to start due t=
o battery Gen discharge // Gen manually start with external battery","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery=
","Grid outage, site went down baecause gen failed to start due to battery =
Gen discharge // Gen manually start with external battery","vanel.mbiada@ma=
tech-cameroun.com","106","10-08-2025 10:41:13","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005662286","AKA=
K Nkozoa","","10-08-2025 09:18:38","10-08-2025 09:16:25","10-08-2025 09:58:=
15","Grid outage, site went down baecause gen failed to start due to batter=
y Gen faulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Generator Battery","Grid outage, site went down baecaus=
e gen failed to start due to battery Gen faulty // Grid return","cedric.tia=
ni@matech-cameroun.com","134","10-08-2025 09:18:38","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005662231","M=
ambine","","10-08-2025 09:09:59","10-08-2025 09:07:50","10-08-2025 10:37:34=
","Grid outage, site went down because gen ran until fuel shortage // Refue=
ling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, site went down because gen ran until fuel shortage // Refuelin=
g done","vanel.mbiada@matech-cameroun.com","131","10-08-2025 09:09:59","MAT=
ECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005662153","Car=
refour Simbock","IHS_YND_742","10-08-2025 08:54:29","10-08-2025 08:47:22","=
10-08-2025 17:13:25","Site went down due to Gen overload (17kva //180A) SS =
HIS Felix Zambe is informed and confirmed//Grid return","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down due=
 to Gen overload (17kva //180A) SS HIS Felix Zambe is informed and confirme=
d//Grid return","cedric.tiani@matech-cameroun.com","428","10-08-2025 08:54:=
29","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005661919","ODZ=
A BORNE 10","","10-08-2025 07:58:51","10-08-2025 07:51:42","10-08-2025 11:2=
2:41","Grid outage, Site went down due to Gen overload (12.5 kva, 180A)//Gr=
id return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, Site went down due to Gen overload (12.5 kva, 180A)=
//Grid return","cedric.tiani@matech-cameroun.com","430","10-08-2025 07:58:5=
1","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005661314","Nko=
l-Mebanga","","10-08-2025 05:38:02","10-08-2025 05:33:47","10-08-2025 08:18=
:07","Solar only site, Site went Down due to low Solar//Solar return","Park=
er Tchoup","Equipment Repair","Passive","Solar","Solar Panel Issue","Solar =
only site, Site went Down due to low Solar//Solar return","ludivine.ngamale=
u@ihstowers.com","256","10-08-2025 05:38:02","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005661167","N=
kolso","","10-08-2025 04:49:32","10-08-2025 04:46:02","10-08-2025 04:50:30"=
,"Grid outage, Site went down before Gen start due to poor backup/ // Grid =
return	","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Grid return	","gerard.tchangoue@matech-camero=
un.com","211","10-08-2025 04:49:32","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005660928","M=
EHANDAN","","10-08-2025 03:17:21","10-08-2025 03:12:23","10-08-2025 04:07:5=
7","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Site went down because Gen failed to start due Grid bad voltage =
// Grid baypass and site on Gen.","gerard.tchangoue@matech-cameroun.com","1=
618","10-08-2025 03:17:21","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005660926","O=
dza-PK10","IHS_YND_527, IHS_YND_528","10-08-2025 03:15:40","10-08-2025 03:1=
2:23","10-08-2025 04:07:57","Site went down because Gen failed to start due=
 Grid bad voltage // Grid baypass and site on Gen.","Albran Byorel","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Site wen=
t down because Gen failed to start due Grid bad voltage // Grid baypass and=
 site on Gen.","gerard.tchangoue@matech-cameroun.com","198","10-08-2025 03:=
15:40","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005660893","O=
dza II OCM","","10-08-2025 03:14:05","10-08-2025 03:12:23","10-08-2025 04:0=
7:57","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Site went down because Gen failed to start due Grid bad volta=
ge // Grid baypass and site on Gen.","gerard.tchangoue@matech-cameroun.com"=
,"1658","10-08-2025 03:14:05","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005660815","C=
hapelle-Nsimeyong","","10-08-2025 02:43:09","10-08-2025 02:41:38","10-08-20=
25 02:46:50","Grid outage, Site went down because Gen failed to start due t=
o Alarm Low oil pressure // Gen card reset and Gen start manually","MINKA N=
ICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","=
Grid outage, Site went down because Gen failed to start due to Alarm Low oi=
l pressure // Gen card reset and Gen start manually","gerard.tchangoue@mate=
ch-cameroun.com","91","10-08-2025 02:43:09","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005660639","ODZ=
A BORNE 10","","10-08-2025 01:33:51","10-08-2025 01:26:41","10-08-2025 04:3=
3:16","Grid outage, Site went down due to Gen overload (12.5 kva, 180A) // =
 Charge reduced and gen manually started","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due t=
o Gen overload (12.5 kva, 180A) //  Charge reduced and gen manually started=
","edwige.kapawo@matech-cameroun.com","431","10-08-2025 01:33:51","MATECH C=
MR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005660559","Lad=
a I Yde","","10-08-2025 01:09:15","10-08-2025 00:59:47","10-08-2025 03:34:4=
6","Site went down due to distion of CB(125 A)  causing by vandalism // We =
rearmed the CB ","Mba Lazare Herve","Equipment Repair","Passive","Rectifier=
","Rectifier - Circuit Breaker","Site went down due to distion of CB(125 A)=
  causing by vandalism // We rearmed the CB ","edwige.kapawo@matech-camerou=
n.com","570","10-08-2025 01:09:15","MATECH CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0005660081","N=
omayos","","09-08-2025 22:56:17","09-08-2025 22:51:58","09-08-2025 23:29:10=
","Grid outage, site went down due to CB that tripped rectifier and 01/07 r=
ectifiers faulty on site //He rearemed the CB and start Gen manually","Fand=
a Brice","Equipment Repair","Passive","Rectifier","Rectifier Module","Grid =
outage, site went down due to CB that tripped rectifier and 01/07 rectifier=
s faulty on site //He rearemed the CB and start Gen manually","gerard.tchan=
goue@matech-cameroun.com","261","09-08-2025 22:56:17","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005660013","M=
ontee-Des-Soeurs","","09-08-2025 22:43:39","09-08-2025 22:42:24","09-08-202=
5 22:47:48","Active // No power issue, site is on grid with Ubaie: 54.6V, M=
bah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active // No power issue, site is on grid with Ubaie: 54.6V, Mbah hosiah(6=
99699694) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","=
77","09-08-2025 22:43:39","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005659975","MBA=
LNGONG LYCEE","","09-08-2025 22:32:53","09-08-2025 22:11:47","09-08-2025 23=
:21:34","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed // Grid return","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Felix Zamb=
e is informed and confirmed","edwige.kapawo@matech-cameroun.com","1269","09=
-08-2025 22:32:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_195","NOCINC0005659466","china em=
bassy yde","","09-08-2025 21:01:33","09-08-2025 20:56:22","10-08-2025 11:57=
:12","Cascaded Incident from TTO5858103","","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","FME Thierry report access issue during the=
 weekend//Grid return","gerard.tchangoue@matech-cameroun.com","311","09-08-=
2025 21:01:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0005659465","Bastos E=
koudou","","09-08-2025 21:01:32","09-08-2025 20:56:22","10-08-2025 11:57:12=
","Cascaded Incident from TTO5858103","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","FME Thierry report access issue =
during the weekend//Grid return","gerard.tchangoue@matech-cameroun.com","31=
0","09-08-2025 21:01:32","MATECH CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0005659455","B=
astos-BAT","IHS_YND_193, IHS_YND_195","09-08-2025 21:00:33","09-08-2025 20:=
56:22","10-08-2025 12:01:25","FME Thierry report access issue during the we=
ekend//Grid return","Mboua Thierry","Access Denial","Lease Or Legal","Landl=
ord Related Issues","Access Issue - Land Lord","FME Thierry report access i=
ssue during the weekend//Grid return","gerard.tchangoue@matech-cameroun.com=
","251","09-08-2025 21:00:33","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005658825","Nko=
abang2","","09-08-2025 19:18:46","09-08-2025 19:11:07","09-08-2025 23:57:31=
","Grid outage, Site went down due to Gen overload (22KVA, 330A), SS Blaise=
 IHS is informed// Grid return	(","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to Gen=
 overload (22KVA, 330A), SS Blaise IHS is informed// Grid return	(","franck=
.nkomot@matech-cameroun.com","461","09-08-2025 19:18:46","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005658641","N=
koabang2","","09-08-2025 18:47:25","09-08-2025 18:46:03","09-08-2025 18:48:=
47","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Site stabilised","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due t=
o gen overload (22KVA, 330A), SS Blaise IHS is informed // Site stabilised"=
,"gerard.tchangoue@matech-cameroun.com","84","09-08-2025 18:47:25","MATECH =
CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005658615","Nko=
lbong","","09-08-2025 18:44:33","09-08-2025 18:40:22","10-08-2025 00:12:15"=
,"Grid outage, site went down because gen failed to start due to starter fa=
ulty // Grid return","Delor Telezing","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Kick Starter","Grid outage, site went down because gen failed to=
 start due to starter faulty // Grid return","franck.nkomot@matech-cameroun=
.com","253","09-08-2025 18:44:33","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005658335","B=
arriere","","09-08-2025 17:52:57","09-08-2025 17:50:49","09-08-2025 18:39:4=
9","Site went down because the FME (650631658/Dowen) was on site for work (=
 Swapp of Gen ) // End of work","Hyemafo Gildas","Installation Activity","P=
assive","Planned Activity","Installation Activity","Site went down because =
the FME (650631658/Dowen) was on site for work ( Swapp of Gen ) // End of w=
ork","gerard.tchangoue@matech-cameroun.com","130","09-08-2025 17:52:57","MA=
TECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005657974","Nko=
abang Alembe","","09-08-2025 16:50:54","09-08-2025 16:47:46","09-08-2025 16=
:51:46","Grid outage, site went down due to Grid bad voltage and no rcp on =
site // Grid stabilised","Mba Lazare Herve","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid outage, site went down due =
to Grid bad voltage and no rcp on site // Grid stabilised","franck.nkomot@m=
atech-cameroun.com","189","09-08-2025 16:50:54","MATECH CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0005657729","M=
volye-New","","09-08-2025 16:12:05","09-08-2025 16:06:52","09-08-2025 18:15=
:39","Site went Down due to Grid outage (No space to deploy) // grid power =
restored","","Grid Supply","Passive","Grid","National Grid - Grid Outage Is=
sue","Site went Down due to Grid outage (No space to deploy) // grid power =
restored","gerard.tchangoue@matech-cameroun.com","314","09-08-2025 16:12:05=
","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005657413","O=
LAMA","","09-08-2025 15:39:42","09-08-2025 15:30:37","09-08-2025 15:43:06",=
"Grid outage, site went down  due to poor battery backup // Grid return","F=
anda Brice","Equipment Repair","Passive","Control Panel","Power Cabinet - B=
attery Low","Grid outage, site went down  due to poor battery backup // Gri=
d return","gerard.tchangoue@matech-cameroun.com","546","09-08-2025 15:39:42=
","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005657039","Aba=
ttoir","IHS_YND_694, IHS_YND_211","09-08-2025 14:51:18","09-08-2025 14:43:1=
0","09-08-2025 14:51:59","Active // No power issue site on grid with Ubaie:=
 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. Notice that =
it is a repetitive issue.","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power=
 issue site on grid with Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Hu=
awei) is informed. Notice that it is a repetitive issue.","gerard.tchangoue=
@matech-cameroun.com","490","09-08-2025 14:51:18","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005656448","N=
kolbong","","09-08-2025 14:00:26","09-08-2025 13:58:12","09-08-2025 17:22:1=
9","Grid outage, Site Down because Gen started and stopped due to Gen overl=
oad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage, Site Down because Gen started=
 and stopped due to Gen overload(22kva//350A) //Grid return","edwige.kapawo=
@matech-cameroun.com","136","09-08-2025 14:00:26","MATECH CMR"
"Closed Complete","Site Down","T0629","IHS_YND_058","NOCINC0005655763","Mvo=
lye","","09-08-2025 12:39:03","09-08-2025 12:34:55","09-08-2025 13:30:39","=
Site went down because CB of rectifier tripped // CB of rectifier rearmed",=
"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier - Circu=
it Breaker","Site went down because CB of rectifier tripped // CB of rectif=
ier rearmed","edwige.kapawo@matech-cameroun.com","249","09-08-2025 12:39:03=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005655705","Etoudi 2=
","","09-08-2025 12:30:22","09-08-2025 12:28:59","09-08-2025 12:32:57","Cas=
caded Incident from TTO5853900","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active // No power issue site on grid w=
ith Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. No=
tice that it is a repetitive issue.","edwige.kapawo@matech-cameroun.com","2=
64679","09-08-2025 12:30:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005655704","ETOUDI C=
HAPELLE","","09-08-2025 12:30:22","09-08-2025 12:28:59","09-08-2025 12:32:5=
7","Cascaded Incident from TTO5853900","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active // No power issue site on =
grid with Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is inform=
ed. Notice that it is a repetitive issue.","edwige.kapawo@matech-cameroun.c=
om","264680","09-08-2025 12:30:22","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005655702","Aba=
ttoir","IHS_YND_694, IHS_YND_211","09-08-2025 12:29:30","09-08-2025 12:28:5=
9","09-08-2025 12:32:57","Active // No power issue site on grid with Ubaie:=
 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. Notice that =
it is a repetitive issue.","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power=
 issue site on grid with Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Hu=
awei) is informed. Notice that it is a repetitive issue.","edwige.kapawo@ma=
tech-cameroun.com","33","09-08-2025 12:29:30","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005654108","Cit=
e des nations","","09-08-2025 08:53:40","09-08-2025 08:49:29","09-08-2025 0=
8:55:05","Grid outage,site went down before Gen started due to Poor battery=
 backup//Gen automatically started","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage,site went do=
wn before Gen started due to Poor battery backup//Gen automatically started=
","edwige.kapawo@matech-cameroun.com","252","09-08-2025 08:53:40","MATECH C=
MR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0005654101","Nko=
londom","","09-08-2025 08:52:24","09-08-2025 08:46:14","09-08-2025 09:00:51=
","Site went down due to PWC ZTE dysfunction//Site stabilised","Fabrice Pou=
akam","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Site went down due to PWC ZTE dysfunction//Site stabilised","edwige.kapa=
wo@matech-cameroun.com","371","09-08-2025 08:52:24","MATECH CMR"
"Closed Complete","Site Down","T2434","IHS_YND_812","NOCINC0005653959","Ntu=
i Prison","","09-08-2025 08:24:14","09-08-2025 08:22:06","09-08-2025 13:04:=
40","Site went Down because Gen ran until fuel shortage // Refueling done",=
"Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Site went=
 Down because Gen ran until fuel shortage // Refueling done","edwige.kapawo=
@matech-cameroun.com","129","09-08-2025 08:24:14","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005653864","HOP=
ITAL DE LA CAISSE","","09-08-2025 07:57:24","09-08-2025 07:56:17","09-08-20=
25 07:59:14","Grid Outage, Site went down before Gen start due to poor back=
up // Gen Started Automatically","Delor Telezing","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site went d=
own before Gen start due to poor backup // Gen Started Automatically","edwi=
ge.kapawo@matech-cameroun.com","68","09-08-2025 07:57:24","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005653624","MBA=
LNGONG LYCEE","","09-08-2025 07:10:02","09-08-2025 06:59:59","09-08-2025 09=
:46:33","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed//Grid return","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//G=
rid return","edwige.kapawo@matech-cameroun.com","605","09-08-2025 07:10:02"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0005653253","NKONGKAR=
AK","","09-08-2025 05:32:03","09-08-2025 05:30:47","09-08-2025 07:54:59","C=
ascaded Incident from TTO5851197","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage.gen ran until=
 fuel shortage//Refueling done","loic.noumsi@matech-cameroun.com","290219",=
"09-08-2025 05:32:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0005653252","Ekekam",=
"","09-08-2025 05:32:02","09-08-2025 05:30:47","09-08-2025 07:54:59","Casca=
ded Incident from TTO5851197","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage.gen ran until fue=
l shortage//Refueling done","loic.noumsi@matech-cameroun.com","290219","09-=
08-2025 05:32:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0005653251","Lobo 2",=
"","09-08-2025 05:32:02","09-08-2025 05:30:47","09-08-2025 07:54:59","Casca=
ded Incident from TTO5851197","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage.gen ran until fue=
l shortage//Refueling done","loic.noumsi@matech-cameroun.com","290218","09-=
08-2025 05:32:02","MATECH CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0005653248","LOB=
O MTN","IHS_YND_783, IHS_YND_714, IHS_YND_713","09-08-2025 05:30:55","09-08=
-2025 05:30:47","09-08-2025 07:54:59","Grid outage.gen ran until fuel short=
age//Refueling done","TIENTCHEU NZETCHIEU GAEL","Fuel Outage","Passive","Di=
esel","Diesel Outage","Grid outage.gen ran until fuel shortage//Refueling d=
one","loic.noumsi@matech-cameroun.com","9","09-08-2025 05:30:55","MATECH CM=
R"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005652990","O=
kola OCM","","09-08-2025 03:33:15","09-08-2025 03:09:05","09-08-2025 06:53:=
49","Grid outage, gen failed to start because Gen Battery discharged due to=
 Ge battery faulty // Gen started with external battery","TIENTCHEU NZETCHI=
EU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery"=
,"Grid outage, gen failed to start because Gen Battery discharged due to Ge=
 battery faulty // Gen started with external battery","loic.noumsi@matech-c=
ameroun.com","1452","09-08-2025 03:33:15","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0005652490","Nko=
londom","","09-08-2025 00:09:51","09-08-2025 00:08:45","09-08-2025 00:18:02=
","No power issue site on Grid , with U=3D57 V The Tx Fme symphorien //6913=
16854 is informed","Fabrice Pouakam","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on Gri=
d , with U=3D57 V The Tx Fme symphorien //691316854 is informed","loic.noum=
si@matech-cameroun.com","67","09-08-2025 00:09:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005652290","Nkol-Meb=
anga","","08-08-2025 23:12:52","08-08-2025 22:40:16","08-08-2025 23:12:42",=
"Cascaded Incident from TTO5850006","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site was on Gen but G=
rid return and Grid contactor  did not stick because the coil that powers i=
t was loose.
 // Tightening the contactor power supply coil and site on Grid","loic.noum=
si@matech-cameroun.com","293011","08-08-2025 23:12:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005652289","Carrefou=
r Ayissi Ele","","08-08-2025 23:12:52","08-08-2025 22:40:16","08-08-2025 23=
:12:42","Cascaded Incident from TTO5850006","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site was on G=
en but Grid return and Grid contactor  did not stick because the coil that =
powers it was loose.
 // Tightening the contactor power supply coil and site on Grid","loic.noum=
si@matech-cameroun.com","293010","08-08-2025 23:12:52","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005652187","S=
aa","IHS_YND_810, IHS_YND_809","08-08-2025 22:47:24","08-08-2025 22:40:16",=
"08-08-2025 23:12:42","Grid outage, site was on Gen but Grid return and Gri=
d contactor  did not stick because the coil that powers it was loose.  // T=
ightening the contactor power supply coil and site on Grid","Parker Tchoup"=
,"Grid Supply","Passive","Grid","National Grid - Circuit Breaker","Grid out=
age, site was on Gen but Grid return and Grid contactor  did not stick beca=
use the coil that powers it was loose.
 // Tightening the contactor power supply coil and site on Grid","edwige.ka=
pawo@matech-cameroun.com","507","08-08-2025 22:47:24","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005651827","ESS=
OS OASIS 1111","","08-08-2025 21:41:06","08-08-2025 21:40:57","08-08-2025 2=
1:56:12","Grid outage, Site went down because Gen overload (17kva, 250A)// =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (17kva, 250A)=
// Grid return","gerard.tchangoue@matech-cameroun.com","10","08-08-2025 21:=
41:06","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005651679","Bit=
eng-Maetur","","08-08-2025 21:20:24","08-08-2025 21:16:18","08-08-2025 21:3=
6:59","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","gerard.=
tchangoue@matech-cameroun.com","249","08-08-2025 21:20:24","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0005651631","SAA=
 2","","08-08-2025 21:12:06","08-08-2025 21:10:53","08-08-2025 21:16:08","G=
rid outage,Site went down because Gen failed to start due to Grid bad volta=
ge and no rcp on site // Grid stabilised","Parker Tchoup","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid outage,Site w=
ent down because Gen failed to start due to Grid bad voltage and no rcp on =
site // Grid stabilised","gerard.tchangoue@matech-cameroun.com","74","08-08=
-2025 21:12:06","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005651515","ESS=
OS OASIS 1111","","08-08-2025 20:47:54","08-08-2025 20:46:46","08-08-2025 2=
1:02:23","Grid outage, Site went down because Gen overload (17kva, 250A)// =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (17kva, 250A)=
// Grid return","gerard.tchangoue@matech-cameroun.com","69","08-08-2025 20:=
47:54","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005651320","E=
mombo","","08-08-2025 20:25:52","08-08-2025 20:24:45","08-08-2025 22:02:03"=
,"Grid outage, Site went down due to rectifiers malfunctioning on site // H=
e reset rectifiers, Site on Grid","Mba Lazare Herve","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","Grid outage, Site went down due to r=
ectifiers malfunctioning on site // He reset rectifiers, Site on Grid","edw=
ige.kapawo@matech-cameroun.com","68","08-08-2025 20:25:52","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005651160","ESS=
OS OASIS 1111","","08-08-2025 20:02:51","08-08-2025 20:01:43","08-08-2025 2=
0:15:19","Grid outage, Site went down because Gen overload (17kva, 250A)// =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (17kva, 250A)=
// Grid return","gerard.tchangoue@matech-cameroun.com","69","08-08-2025 20:=
02:51","MATECH CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0005650896","Ntu=
i administration","","08-08-2025 19:18:32","08-08-2025 19:17:26","08-08-202=
5 19:48:37","(Unstable) site went down due to insufficient rectifiers on si=
te//Site stabilised","Parker Tchoup","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","(Unstable) site went down due to insufficient rectif=
iers on site//Site stabilised","gerard.tchangoue@matech-cameroun.com","67",=
"08-08-2025 19:18:32","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005650813","ESS=
OS OASIS 1111","","08-08-2025 19:07:15","08-08-2025 19:06:05","08-08-2025 1=
9:20:49","Grid outage, Site went down because Gen overload (17kva, 250A)// =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (17kva, 250A)=
// Grid return","gerard.tchangoue@matech-cameroun.com","71","08-08-2025 19:=
07:15","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0005650691","Min=
ka","IHS_YND_687, IHS_YND_531, IHS_YND_370, IHS_YND_365","08-08-2025 18:43:=
38","08-08-2025 18:42:31","08-08-2025 18:45:51","No power issue, Site impac=
ted by Ngoumou Camrail not managed by IHS","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","Affected by 3rd Party Site"=
,"No power issue, Site impacted by Ngoumou Camrail not managed by IHS","ger=
ard.tchangoue@matech-cameroun.com","69","08-08-2025 18:43:38","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005650421","ESS=
OS OASIS 1111","","08-08-2025 18:08:46","08-08-2025 18:07:36","08-08-2025 1=
8:19:29","Grid outage, Site went down because Gen overload (17kva, 250A)// =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (17kva, 250A)=
// Grid return","gerard.tchangoue@matech-cameroun.com","71","08-08-2025 18:=
08:46","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005650399","Hop=
ital Central","","08-08-2025 18:05:36","08-08-2025 18:02:27","08-08-2025 18=
:33:27","(Unstable) site went down due to insufficient rectifiers on site//=
Site stabilised","","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","(Unstable) site went down due to insufficient rectifiers on site//Sit=
e stabilised","gerard.tchangoue@matech-cameroun.com","190","08-08-2025 18:0=
5:36","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005650273","Mey=
o","","08-08-2025 17:42:44","08-08-2025 17:39:26","08-08-2025 17:58:15","AC=
TIVE // No power issue Ubaie: 54,3V Site on Grid The Tx Fme Georges /697466=
1814 from huawei is informed","Hyemafo Gildas","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE // No pow=
er issue Ubaie: 54,3V Site on Grid The Tx Fme Georges /6974661814 from huaw=
ei is informed","edwige.kapawo@matech-cameroun.com","199","08-08-2025 17:42=
:44","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005650146","B=
arriere IHS","","08-08-2025 17:22:08","08-08-2025 17:22:05","08-08-2025 17:=
36:03","No power issue, Site impacted  by Simbock-chefferie-MTN not managed=
 by IHS","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equ=
ipment Failure","Affected by 3rd Party Site","No power issue, Site impacted=
  by Simbock-chefferie-MTN not managed by IHS","edwige.kapawo@matech-camero=
un.com","5","08-08-2025 17:22:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0005650051","AWAE OCM=
","","08-08-2025 17:03:48","08-08-2025 16:58:46","08-08-2025 17:40:30","Cas=
caded Incident from TTO5847577","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen started and stopped with ""low oil pressure"" alarm// He reset card GE=
 and gen manually started","ludivine.ngamaleu@ihstowers.com","263184","08-0=
8-2025 17:03:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0005650050","Tradex-N=
komo","","08-08-2025 17:03:47","08-08-2025 16:58:46","08-08-2025 17:40:30",=
"Cascaded Incident from TTO5847577","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen started and stopped with ""low oil pressure"" alarm// He reset card G=
E and gen manually started","ludivine.ngamaleu@ihstowers.com","263184","08-=
08-2025 17:03:47","MATECH CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0005650033","Nko=
mo II","IHS_YND_172, IHS_YND_173","08-08-2025 17:02:56","08-08-2025 16:58:4=
6","08-08-2025 17:40:30","Grid outage, Site went down because Gen started a=
nd stopped with ""low oil pressure"" alarm// He reset card GE and gen manua=
lly started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- Low Oil Pressure","Grid outage, Site went down because Gen started and st=
opped with ""low oil pressure"" alarm// He reset card GE and gen manually s=
tarted","edwige.kapawo@matech-cameroun.com","251","08-08-2025 17:02:56","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005649952","E=
SSOS OASIS 1111","","08-08-2025 16:49:54","08-08-2025 16:48:36","08-08-2025=
 17:04:42","Grid outage, Site went down because Gen overload (17kva, 250A)/=
/ Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage, Site went down because Gen overload (17kva, 250=
A)// Grid return","edwige.kapawo@matech-cameroun.com","80","08-08-2025 16:4=
9:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0005649771","Barriere=
 IHS","","08-08-2025 16:22:41","08-08-2025 16:18:07","08-08-2025 16:18:38",=
"Cascaded Incident from TTO5847255","Hyemafo Gildas","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down due to=
 PWC Huawei dysfunction//Site stabilised","edwige.kapawo@matech-cameroun.co=
m","265716","08-08-2025 16:22:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_258","NOCINC0005649770","Mefou-As=
si","","08-08-2025 16:22:40","08-08-2025 16:18:07","08-08-2025 16:18:38","C=
ascaded Incident from TTO5847255","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site went down due to PWC =
Huawei dysfunction//Site stabilised","edwige.kapawo@matech-cameroun.com","2=
65715","08-08-2025 16:22:40","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005649757","M=
EFOU ASSI","IHS_YND_258, IHS_YND_696","08-08-2025 16:21:22","08-08-2025 16:=
18:07","08-08-2025 16:18:38","Grid outage,site went down due to PWC Huawei =
dysfunction//Site stabilised","Fanda Brice","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","Grid outage,site went down due to =
PWC Huawei dysfunction//Site stabilised","edwige.kapawo@matech-cameroun.com=
","197","08-08-2025 16:21:22","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005649462","E=
SSOS OASIS 1111","","08-08-2025 15:42:34","08-08-2025 15:36:03","08-08-2025=
 15:52:44","Grid outage, Site went down because Gen overload (17kva, 250A)/=
/ Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage, Site went down because Gen overload (17kva, 250=
A)// Grid return","edwige.kapawo@matech-cameroun.com","393","08-08-2025 15:=
42:34","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0005649307","Ngo=
um","","08-08-2025 15:27:26","08-08-2025 15:18:54","08-08-2025 15:57:43","S=
ite went down because FME IHS Williams stopped Gen for TEST of Fuel, SS IHS=
 Felix Bateu has confirmed // GEn restarted, End of work","Parker Tchoup","=
Installation Activity","Passive","Planned Activity","Installation Activity"=
,"Site went down because FME IHS Williams stopped Gen for TEST of Fuel, SS =
IHS Felix Bateu has confirmed // GEn restarted, End of work","ludivine.ngam=
aleu@ihstowers.com","24461","08-08-2025 15:27:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005648999","Etoudi 2=
","","08-08-2025 15:08:59","08-08-2025 15:06:34","08-08-2025 15:12:03","Cas=
caded Incident from TTO5846407","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D53=
.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. Notice that =
it is a repetitive issue.","gerard.tchangoue@matech-cameroun.com","262509",=
"08-08-2025 15:08:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005648998","ETOUDI C=
HAPELLE","","08-08-2025 15:08:58","08-08-2025 15:06:34","08-08-2025 15:12:0=
3","Cascaded Incident from TTO5846407","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on grid with =
U=3D53.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. Notice=
 that it is a repetitive issue.","gerard.tchangoue@matech-cameroun.com","26=
2510","08-08-2025 15:08:58","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005648990","Aba=
ttoir","IHS_YND_694, IHS_YND_211","08-08-2025 15:07:47","08-08-2025 15:06:3=
4","08-08-2025 15:12:03","No power issue site on grid with U=3D53.1V, TX Fm=
e Armand Nguetsa /699949553 from Huawei is informed. Notice that it is a re=
petitive issue.","Fabrice Pouakam","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D53.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. N=
otice that it is a repetitive issue.","gerard.tchangoue@matech-cameroun.com=
","75","08-08-2025 15:07:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0005648852","Tradex-N=
komo","","08-08-2025 14:40:30","08-08-2025 14:35:38","08-08-2025 15:37:44",=
"Cascaded Incident from TTO5846236","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went Down due to work  Albran=
 (657108542/Matech) was on site for work (swap of belt fan) // End of work"=
,"franck.nkomot@matech-cameroun.com","271550","08-08-2025 14:40:30","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0005648853","AWAE OCM=
","","08-08-2025 14:40:30","08-08-2025 14:35:38","08-08-2025 15:37:44","Cas=
caded Incident from TTO5846236","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went Down due to work  Albran =
(657108542/Matech) was on site for work (swap of belt fan) // End of work",=
"franck.nkomot@matech-cameroun.com","271551","08-08-2025 14:40:30","MATECH =
CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0005648842","Nko=
mo II","IHS_YND_172, IHS_YND_173","08-08-2025 14:38:47","08-08-2025 14:35:3=
8","08-08-2025 15:37:44","Site went Down due to work  Albran (657108542/Mat=
ech) was on site for work (swap of belt fan) // End of work","Albran Byorel=
","Equipment Replacement","Passive","Planned Activity","Planned Activity - =
Passive","Site went Down due to work  Albran (657108542/Matech) was on site=
 for work (swap of belt fan) // End of work","franck.nkomot@matech-cameroun=
.com","189","08-08-2025 14:38:47","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005648694","E=
SSOS OASIS 1111","","08-08-2025 14:13:12","08-08-2025 14:10:59","08-08-2025=
 14:26:28","Grid outage, Site went down because Gen overload (17kva, 250A) =
// Grid returned	","Siligap Boris","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage, Site went down because Gen overload (17kva,=
 250A) // Grid returned	","vanel.mbiada@matech-cameroun.com","134","08-08-2=
025 14:13:12","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005648376","Nsa=
m Sofavinc","","08-08-2025 13:12:06","08-08-2025 13:08:01","08-08-2025 13:1=
4:01","Grid outage, Site went down before Gen start due to poor backup/ // =
Gen automatically started","MINKA NICOLAS","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup/ // Gen automatically started","franck.nko=
mot@matech-cameroun.com","246","08-08-2025 13:12:06","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005648352","Aka=
k-Nkozoa-MTN-IHS","","08-08-2025 13:05:57","08-08-2025 13:02:52","08-08-202=
5 13:58:52","Site went down because FME Giresse was on site for plan work (=
Draining the Gen) // End of work","Fabrice Pouakam","Installation Activity"=
,"Passive","Planned Activity","Installation Activity","Site went down becau=
se FME Giresse was on site for plan work (Draining the Gen) // End of work"=
,"franck.nkomot@matech-cameroun.com","255","08-08-2025 13:05:57","MATECH CM=
R"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005648333","ESS=
OS OASIS 1111","","08-08-2025 13:01:22","08-08-2025 12:56:13","08-08-2025 1=
3:12:14","Grid outage, Site went down because Gen overload (17kva, 250A)// =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (17kva, 250A)=
// Grid return","franck.nkomot@matech-cameroun.com","310","08-08-2025 13:01=
:22","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005648028","N=
koabang Ebolmedjock","","08-08-2025 12:07:20","08-08-2025 12:05:35","08-08-=
2025 12:39:35","Grid outage, site went down because Gen started and stopped=
 due to High temp alarm // He reset gen card and gen manually started","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine =
Temp - Coolant Level Issue","Grid outage, site went down because Gen starte=
d and stopped due to High temp alarm // He reset gen card and gen manually =
started","vanel.mbiada@matech-cameroun.com","107","08-08-2025 12:07:20","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005647584","S=
atcom","","08-08-2025 10:58:49","08-08-2025 10:53:40","08-08-2025 11:05:51"=
," Site impacted by Etoa-meki-II_CTR_682 not managed by IHS","Delor Telezin=
g","Customer Equipment Failure","Active","Active Equipment Failure","Affect=
ed by 3rd Party Site"," Site impacted by Etoa-meki-II_CTR_682 not managed b=
y IHS","vanel.mbiada@matech-cameroun.com","311","08-08-2025 10:58:49","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005647577","M=
vog-Ada_OCM","","08-08-2025 10:57:14","08-08-2025 10:53:08","08-08-2025 11:=
06:27","Grid only on site, No space on site to deploy MDGE // Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 only on site, No space on site to deploy MDGE // Grid return","vanel.mbiad=
a@matech-cameroun.com","248","08-08-2025 10:57:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005647488","OTELE MT=
N","","08-08-2025 10:46:20","08-08-2025 10:37:51","08-08-2025 10:45:51","Ca=
scaded Incident from TTO5844647","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on grid with U=3D51.9V=
 Site is impacted by Ngoumou who is not managing by IHS. Henri (699949693) =
from Huawei is informed.","franck.nkomot@matech-cameroun.com","264344","08-=
08-2025 10:46:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005647490","Mom","",=
"08-08-2025 10:46:20","08-08-2025 10:37:51","08-08-2025 10:45:51","Cascaded=
 Incident from TTO5844647","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on grid with U=3D51.9V Site =
is impacted by Ngoumou who is not managing by IHS. Henri (699949693) from H=
uawei is informed.","franck.nkomot@matech-cameroun.com","264347","08-08-202=
5 10:46:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005647489","Minka","=
","08-08-2025 10:46:20","08-08-2025 10:37:51","08-08-2025 10:45:51","Cascad=
ed Incident from TTO5844647","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D51.9V Sit=
e is impacted by Ngoumou who is not managing by IHS. Henri (699949693) from=
 Huawei is informed.","franck.nkomot@matech-cameroun.com","264345","08-08-2=
025 10:46:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005647487","OLAMA","=
","08-08-2025 10:46:19","08-08-2025 10:37:51","08-08-2025 10:45:51","Cascad=
ed Incident from TTO5844647","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D51.9V Sit=
e is impacted by Ngoumou who is not managing by IHS. Henri (699949693) from=
 Huawei is informed.","franck.nkomot@matech-cameroun.com","264346","08-08-2=
025 10:46:19","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005647459","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","08-08-2025 10:43:=
59","08-08-2025 10:37:51","08-08-2025 10:45:51","Site impacted by Ngoumou w=
ho is not managing by IHS. Henri (699949693) from Huawei is informed.","Fan=
da Brice","Customer Equipment Failure","Active","Active Equipment Failure",=
"Affected by 3rd Party Site","No power issue on site. Site on Grid with U=
=3D51.9V. Site is impacted by Ngoumou who is not managing by IHS. Henri (69=
9949693) from Huawei is informed.","franck.nkomot@matech-cameroun.com","369=
","08-08-2025 10:43:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_213","NOCINC0005646736","Nkolmess=
eng","","08-08-2025 08:54:13","08-08-2025 08:42:26","08-08-2025 08:50:26","=
Cascaded Incident from TTO5843788","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
poor backup battery // Gen automatically started","franck.nkomot@matech-cam=
eroun.com","263952","08-08-2025 08:54:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_739","NOCINC0005646722","NKOLMESS=
ING rue Manguier","","08-08-2025 08:52:12","08-08-2025 08:42:26","08-08-202=
5 08:50:26","Cascaded Incident from TTO5843788","Siligap Boris","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid outage, site went=
 down due to poor backup battery // Gen automatically started","franck.nkom=
ot@matech-cameroun.com","263951","08-08-2025 08:52:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_214","NOCINC0005646723","Nkolmess=
eng-II","","08-08-2025 08:52:12","08-08-2025 08:42:26","08-08-2025 08:50:26=
","Cascaded Incident from TTO5843788","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, site went down due =
to poor backup battery // Gen automatically started","franck.nkomot@matech-=
cameroun.com","263950","08-08-2025 08:52:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_215","NOCINC0005646721","Eleveurs=
","","08-08-2025 08:52:12","08-08-2025 08:42:26","08-08-2025 08:50:26","Cas=
caded Incident from TTO5843788","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to poo=
r backup battery // Gen automatically started","franck.nkomot@matech-camero=
un.com","263949","08-08-2025 08:52:12","MATECH CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0005646689","Nko=
lmesseng","IHS_YND_215, IHS_YND_213, IHS_YND_739, IHS_YND_214","08-08-2025 =
08:48:37","08-08-2025 08:42:26","08-08-2025 08:50:26","Grid outage, site we=
nt down due to poor backup battery // Gen automatically started","Siligap B=
oris","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery=
 Low","Grid outage, site went down due to poor backup battery // Gen automa=
tically started","franck.nkomot@matech-cameroun.com","372","08-08-2025 08:4=
8:37","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0005646614","Val=
lee Bastos MTN","","08-08-2025 08:35:57","08-08-2025 08:29:34","08-08-2025 =
10:00:34","Site went down because 01/04 rectifier dysfunction on site due t=
o Grid bad voltage // He reset the rectifier, site on Gen","Mboua Thierry",=
"Equipment Repair","Passive","Rectifier","Rectifier Module","Site went down=
 because 01/04 rectifier dysfunction on site due to Grid bad voltage // He =
reset the rectifier, site on Gen","franck.nkomot@matech-cameroun.com","384"=
,"08-08-2025 08:35:57","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005646504","Eki=
e sud","","08-08-2025 08:19:00","08-08-2025 08:14:38","08-08-2025 08:58:49"=
,"Grid outage. Gen failed to start due to automation malfunctioning//Grid r=
eturn","Albran Byorel","Equipment Repair","Passive","Control Panel","ATS-AM=
F Issue","Grid outage. Gen failed to start due to automation malfunctioning=
//Grid return","franck.nkomot@matech-cameroun.com","263","08-08-2025 08:19:=
00","MATECH CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0005645573","N=
kongtock","","08-08-2025 04:25:36","08-08-2025 04:20:09","08-08-2025 05:56:=
27","Site went down because gen failed to start due to Fuse Gen card cut//H=
e made a bridge and manually started the Gen","Kemeni Franklin","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Site went down because=
 gen failed to start due to Fuse Gen card cut//He made a bridge and manuall=
y started the Gen","vanel.mbiada@matech-cameroun.com","329","08-08-2025 04:=
25:36","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005645375","MBA=
LNGONG LYCEE","","08-08-2025 03:09:33","08-08-2025 03:07:23","08-08-2025 03=
:13:04","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed//Grid return","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//G=
rid return","cedric.tiani@matech-cameroun.com","133","08-08-2025 03:09:33",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0005644984","NGONA","=
","08-08-2025 00:48:37","08-08-2025 00:43:53","08-08-2025 00:51:11","Cascad=
ed Incident from TTO5841900","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on grid with U=3D56.7=
v Lionnel Steeve(655184876) from Huawei is informed","vanel.mbiada@matech-c=
ameroun.com","263856","08-08-2025 00:48:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0005644985","Nkoabang=
2","","08-08-2025 00:48:37","08-08-2025 00:43:53","08-08-2025 00:51:11","Ca=
scaded Incident from TTO5841900","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
56.7v Lionnel Steeve(655184876) from Huawei is informed","vanel.mbiada@mate=
ch-cameroun.com","263855","08-08-2025 00:48:37","MATECH CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0005644982","N=
koabang","IHS_YND_295, IHS_YND_526","08-08-2025 00:47:33","08-08-2025 00:43=
:53","08-08-2025 00:51:11","No power issue site on grid with U=3D56.7v Lion=
nel Steeve(655184876) from Huawei is informed","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue site on grid with U=3D56.7v Lionnel Steeve(655184876) fro=
m Huawei is informed","vanel.mbiada@matech-cameroun.com","221","08-08-2025 =
00:47:33","MATECH CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0005644913","B=
iteng","","08-08-2025 00:24:46","08-08-2025 00:21:21","08-08-2025 00:27:50"=
,"Site went down due to work of FME STEVE Onana ( 699944736) of  ingenierie=
  orange CMR ( migration Ip ran)","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site U=3D54,5v site on grid Lionel steve 655184876 of Huawei is inf=
ormed","vanel.mbiada@matech-cameroun.com","207","08-08-2025 00:24:46","MATE=
CH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005644576","Eki=
e sud","","07-08-2025 22:48:28","07-08-2025 22:47:02","07-08-2025 23:43:17"=
,"Grid outage,site went down because Gen failed to start (investigation ong=
oing)//He started the Gen manually","Albran Byorel","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down because=
 Gen failed to start (investigation ongoing)//He started the Gen manually",=
"cedric.tiani@matech-cameroun.com","87","07-08-2025 22:48:28","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005644410","M=
vog-Ebanda","","07-08-2025 22:17:07","07-08-2025 22:08:58","07-08-2025 22:2=
4:37","Grid outage,Site went down because Gen failed to start(Investigation=
 ongoing)//He manually started the Gen","Siligap Boris","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage,Site went down bec=
ause Gen failed to start(Investigation ongoing)//He manually started the Ge=
n","edwige.kapawo@matech-cameroun.com","490","07-08-2025 22:17:07","MATECH =
CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0005644394","Nko=
lmesseng","IHS_YND_215, IHS_YND_739, IHS_YND_269, IHS_YND_214, IHS_YND_217"=
,"07-08-2025 22:13:57","07-08-2025 22:10:52","07-08-2025 22:18:42","Grid ou=
tage, site went down due to poor backup battery // Site stabilised","Siliga=
p Boris","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","Grid outage, site went down due to poor backup battery // Site st=
abilised","loic.noumsi@matech-cameroun.com","185","07-08-2025 22:13:57","MA=
TECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005644390","ESS=
OS OASIS 1111","","07-08-2025 22:13:11","07-08-2025 22:10:05","07-08-2025 2=
2:20:38","Grid outage, Site went down because Gen overload (17kva, 250A)// =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (17kva, 250A)=
// Grid return","loic.noumsi@matech-cameroun.com","187","07-08-2025 22:13:1=
1","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005644288","Nko=
langaa","","07-08-2025 22:01:53","07-08-2025 21:58:45","08-08-2025 00:34:51=
","ACTIVE//no power issue on site Ubaie=3D52:7 V site on Grid Lionel Tchatc=
hou (694693436) from Huawei is informedNoticed disjunction at the BTS MTN",=
"Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","ACTIVE//no power issue on site Ubaie=3D52:7 =
V site on Grid Lionel Tchatchou (694693436) from Huawei is informedNoticed =
disjunction at the BTS MTN","loic.noumsi@matech-cameroun.com","190","07-08-=
2025 22:01:53","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005644160","Ngo=
usso Vallee","","07-08-2025 21:48:14","07-08-2025 21:45:07","07-08-2025 21:=
49:50","Grid outage, Site went down before Gen start due to poor backup// G=
rid return","Siligap Boris","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage, Site went down before Gen start d=
ue to poor backup// Grid return","loic.noumsi@matech-cameroun.com","188","0=
7-08-2025 21:48:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005644150","Etoudi 2=
","","07-08-2025 21:46:38","07-08-2025 21:42:54","07-08-2025 21:55:20","Cas=
caded Incident from TTO5840937","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Fluctuation, site went down bef=
ore Gen start due to poor battery backup // Grid restoration","loic.noumsi@=
matech-cameroun.com","224","07-08-2025 21:46:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005644149","ETOUDI C=
HAPELLE","","07-08-2025 21:46:37","07-08-2025 21:42:54","07-08-2025 21:55:2=
0","Cascaded Incident from TTO5840937","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Fluctuation, site went do=
wn before Gen start due to poor battery backup // Grid restoration","loic.n=
oumsi@matech-cameroun.com","223","07-08-2025 21:46:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0005644129","Abattoir=
","","07-08-2025 21:45:44","07-08-2025 21:42:54","07-08-2025 21:55:20","Cas=
caded Incident from TTO5840936","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Fluctuation, site went down bef=
ore Gen start due to poor battery backup // Grid restoration","loic.noumsi@=
matech-cameroun.com","267770","07-08-2025 21:45:44","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005644126","E=
toudi","IHS_YND_694, IHS_YND_211, IHS_YND_244","07-08-2025 21:45:01","07-08=
-2025 21:42:54","07-08-2025 21:55:20","Grid Fluctuation, site went down bef=
ore Gen start due to poor battery backup // Grid restoration","Fabrice Poua=
kam","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Grid Fluctuation, site went down before Gen start due to poor battery=
 backup // Grid restoration","loic.noumsi@matech-cameroun.com","128","07-08=
-2025 21:45:01","MATECH CMR"
"Closed Complete","Site Down","T1622","IHS_YND_186","NOCINC0005643915","Ngo=
usso Carrefour","","07-08-2025 21:06:26","07-08-2025 21:00:19","08-08-2025 =
08:24:19","Grid outage, site Down due to Gen Overload (20KVA, 280A)//Grid r=
eturn","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, site Down due to Gen Overload (20KVA, 280A)//Grid retur=
n","loic.noumsi@matech-cameroun.com","368","07-08-2025 21:06:26","MATECH CM=
R"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005643851","ESS=
OS OASIS 1111","","07-08-2025 20:55:44","07-08-2025 20:53:34","07-08-2025 2=
1:05:53","Grid outage, Site went down due to Gen overload (17kva, 250A) // =
Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down due to Gen overload (17kva, 250A) =
// Grid return","loic.noumsi@matech-cameroun.com","132","07-08-2025 20:55:4=
4","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005643824","Mim=
boman","","07-08-2025 20:50:56","07-08-2025 20:50:53","07-08-2025 21:53:44"=
,"Site went down due to Gen overload (120A, 12kva) and indoor site // He re=
duced load, site on Gen","Mba Lazare Herve","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Site went down due to Gen overload (120A, 12kva=
) and indoor site // He reduced load, site on Gen","loic.noumsi@matech-came=
roun.com","4","07-08-2025 20:50:56","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005643450","Bit=
eng-Maetur","","07-08-2025 19:48:26","07-08-2025 19:45:21","07-08-2025 21:2=
3:49","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","loic.no=
umsi@matech-cameroun.com","186","07-08-2025 19:48:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_739","NOCINC0005643325","NKOLMESS=
ING rue Manguier","","07-08-2025 19:24:42","07-08-2025 19:21:22","07-08-202=
5 20:55:58","Cascaded Incident from TTO5840033","Siligap Boris","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","disjonction du disjonc=
teur du g=E9n=E9rateur ","loic.noumsi@matech-cameroun.com","269083","07-08-=
2025 19:24:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_214","NOCINC0005643326","Nkolmess=
eng-II","","07-08-2025 19:24:42","07-08-2025 19:21:22","07-08-2025 20:55:58=
","Cascaded Incident from TTO5840033","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","disjonction du disjoncteur du g=
=E9n=E9rateur ","loic.noumsi@matech-cameroun.com","269084","07-08-2025 19:2=
4:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_213","NOCINC0005643324","Nkolmess=
eng","","07-08-2025 19:24:41","07-08-2025 19:21:22","07-08-2025 20:55:58","=
Cascaded Incident from TTO5840033","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","disjonction du disjoncteur du g=E9n=
=E9rateur ","loic.noumsi@matech-cameroun.com","269082","07-08-2025 19:24:41=
","MATECH CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0005643318","Nko=
lmesseng","IHS_YND_213, IHS_YND_739, IHS_YND_214, IHS_YND_217","07-08-2025 =
19:22:28","07-08-2025 19:21:22","07-08-2025 20:55:58","Site went down becau=
se Gen started and stopped due to disjunction of CB Gen (32A) // He rearmed=
 CB Gen, Site on Gen","Siligap Boris","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Load Breaker","Site went down because Gen started and stopped du=
e to disjunction of CB Gen (32A) // He rearmed CB Gen, Site on Gen","loic.n=
oumsi@matech-cameroun.com","67","07-08-2025 19:22:28","MATECH CMR"
"Closed Complete","Warning","T0183","IHS_YND_184","NOCINC0005643316","Nkolm=
esseng","","07-08-2025 19:21:40","","","Site went down because Gen started =
and stopped due to disjunction of CB Gen (32A) // He rearmed CB Gen, Site o=
n Gen","Siligap Boris","Warning","Warning","POWER","Warning - ACDG - Load B=
reaker","Site went down because Gen started and stopped due to disjunction =
of CB Gen (32A) // He rearmed CB Gen, Site on Gen","loic.noumsi@matech-came=
roun.com","22","07-08-2025 19:21:40","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0005643307","B=
itoto","","07-08-2025 19:19:10","07-08-2025 19:14:59","07-08-2025 19:40:36"=
,"No power issue on site , Tx Issue : site on Grid ,Ubai: 51.8V; The fme Tx=
 Henri (699949693) From huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site , Tx Issue : site on Grid ,Ubai: 51.8V; The fme Tx H=
enri (699949693) From huawei is informed","edwige.kapawo@matech-cameroun.co=
m","252","07-08-2025 19:19:10","MATECH CMR"
"Closed Complete","Site Down","T1431","IHS_YND_561","NOCINC0005643246","FOU=
GEROLE","","07-08-2025 19:08:36","07-08-2025 19:02:30","07-08-2025 19:18:28=
","Grid outage, site went down due to Gen Overload (20Kva, Iload 300 A )IHS=
 SS Alphonse is informed // Site stabilised","Siligap Boris","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down du=
e to Gen Overload (20Kva, Iload 300 A )IHS SS Alphonse is informed // Site =
stabilised","loic.noumsi@matech-cameroun.com","367","07-08-2025 19:08:36","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005643226","Mvog-Eba=
nda","","07-08-2025 19:03:57","07-08-2025 18:59:02","07-08-2025 19:14:53","=
Cascaded Incident from TTO5839930","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen failed to start due to Gen Overload (16KVA /300A) // Grid return","loi=
c.noumsi@matech-cameroun.com","262969","07-08-2025 19:03:57","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005643225","A=
bom","IHS_YND_269","07-08-2025 19:03:14","07-08-2025 18:59:02","07-08-2025 =
19:14:53","Grid outage, Site went down because Gen failed to start due to G=
en Overload (16KVA /300A) // Grid return","Siligap Boris","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen failed to start due to Gen Overload (16KVA /300A) // Grid return","l=
oic.noumsi@matech-cameroun.com","253","07-08-2025 19:03:14","MATECH CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0005643147","Ele=
veurs","","07-08-2025 18:52:32","07-08-2025 18:51:26","07-08-2025 20:00:06"=
,"Grid outage, site went down because Gen failed to start due to disjunctio=
n of Gen CB (32A) // He rearmed Gen CB, SITE ON gen","Siligap Boris","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Grid outage, site =
went down because Gen failed to start due to disjunction of Gen CB (32A) //=
 He rearmed Gen CB, SITE ON gen","loic.noumsi@matech-cameroun.com","67","07=
-08-2025 18:52:32","MATECH CMR"
"Closed Complete","Site Down","T1431","IHS_YND_561","NOCINC0005642771","FOU=
GEROLE","","07-08-2025 17:57:50","07-08-2025 17:54:43","07-08-2025 18:12:33=
","Grid outage, site went down due to Gen Overload (20Kva, Iload 300 A )IHS=
 SS Alphonse is informed // Site stabilised","Siligap Boris","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down du=
e to Gen Overload (20Kva, Iload 300 A )IHS SS Alphonse is informed // Site =
stabilised","loic.noumsi@matech-cameroun.com","188","07-08-2025 17:57:50","=
MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005642153","F=
OUGEROLE","","07-08-2025 16:37:27","07-08-2025 16:36:16","07-08-2025 17:08:=
24","Grid outage, site went down due to Gen Overload (20Kva, Iload 300 A )I=
HS SS Alphonse is informed // Reduced charge and left site on gen","Siligap=
 Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, site went down due to Gen Overload (20Kva, Iload 300 A )IHS SS Alphons=
e is informed // Reduced charge and left site on gen","edwige.kapawo@matech=
-cameroun.com","72","07-08-2025 16:37:27","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005641974","E=
MANA BILICK CITY","","07-08-2025 16:09:08","07-08-2025 16:08:59","07-08-202=
5 16:32:26","	Access issue . Grid outage,site behaves as Grid only site (Ge=
n Noise) //  Grid return","Fabrice Pouakam","Access Denial","Lease Or Legal=
","Landlord Related Issues","Access Issue - Land Lord","	Access issue . Gri=
d outage,site behaves as Grid only site (Gen Noise) //  Grid return","edwig=
e.kapawo@matech-cameroun.com","11","07-08-2025 16:09:08","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005641895","Ako=
no","","07-08-2025 15:54:11","07-08-2025 15:52:06","07-08-2025 15:54:54","S=
ite impacted by T0169 Ngoumou not manage by IHS","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Site impacted by T0169 Ngoumou not manage by IHS","loic.noumsi@matech-camer=
oun.com","127","07-08-2025 15:54:11","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005641811","F=
OUGEROLE","","07-08-2025 15:43:33","07-08-2025 13:43:27","07-08-2025 16:07:=
43","Grid outage, site went down due to Gen Overload (20Kva, Iload 300 A )I=
HS SS Alphonse is informed // Reduced charge and left site on gen","Siligap=
 Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, site went down due to Gen Overload (20Kva, Iload 300 A )IHS SS Alphons=
e is informed // Reduced charge and left site on gen","loic.noumsi@matech-c=
ameroun.com","9915","07-08-2025 15:43:33","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005641600","N=
koabang Ebolmedjock","","07-08-2025 15:12:26","07-08-2025 15:08:14","07-08-=
2025 15:10:48","Site impacted by Nkolmesseng-Abom(CTR-711) Not Manager By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Site impacted by Nkolmesseng-Abom(CTR-71=
1) Not Manager By IHS","loic.noumsi@matech-cameroun.com","254","07-08-2025 =
15:12:26","MATECH CMR"
"Closed Complete","Site Down","T0638","IHS_YND_318","NOCINC0005641513","SOA=
 University","","07-08-2025 14:59:12","07-08-2025 14:58:04","07-08-2025 15:=
05:38","Grid Outage, Site went down because Gen Failed to Start due to Rela=
y 48V faulty // He bypassed Relay and Manually Started the Gen","Siligap Bo=
ris","Equipment Repair","Passive","Control Panel","ATS Relay Faulty","Grid =
Outage, Site went down because Gen Failed to Start due to Relay 48V faulty =
// He bypassed Relay and Manually Started the Gen","loic.noumsi@matech-came=
roun.com","69","07-08-2025 14:59:12","MATECH CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0005641508","Ngo=
ulmekong-Nord","","07-08-2025 14:58:18","07-08-2025 14:57:12","07-08-2025 1=
6:11:14","Grid outage, site went down because gen started and stopped with =
Alarm low oil pressure // He added oil and gen manually started","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Gr=
id outage, site went down because gen started and stopped with Alarm low oi=
l pressure // He added oil and gen manually started","loic.noumsi@matech-ca=
meroun.com","67","07-08-2025 14:58:18","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005641154","Fla=
menco","","07-08-2025 13:41:52","07-08-2025 13:40:43","07-08-2025 13:46:17"=
,"Grid outage, site went down due to poor backup battery // Gen started aut=
omatically","Mboua Thierry","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage, site went down due to poor backup=
 battery // Gen started automatically","edwige.kapawo@matech-cameroun.com",=
"71","07-08-2025 13:41:52","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005641086","Mok=
olo Yaounde","","07-08-2025 13:27:05","07-08-2025 13:19:58","07-08-2025 16:=
03:20","Grid only, Grid Outage on site, no space to deploy MDGE // Grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid only, Grid Outage on site, no space to deploy MDGE // Grid return","l=
udivine.ngamaleu@ihstowers.com","429","07-08-2025 13:27:05","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0005641045","Min=
ka","IHS_YND_531, IHS_YND_370, IHS_YND_365","07-08-2025 13:20:12","07-08-20=
25 13:17:05","07-08-2025 13:21:52","No power issue, Site impacted by Ngoumo=
u Camrail not managed by IHS","Fanda Brice","Customer Equipment Failure","A=
ctive","Active Equipment Failure","Affected by 3rd Party Site","No power is=
sue, Site impacted by Ngoumou Camrail not managed by IHS","gerard.tchangoue=
@matech-cameroun.com","189","07-08-2025 13:20:12","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005641018","ODZ=
A MINKAN EDIBI ASSI","","07-08-2025 13:11:18","07-08-2025 13:06:10","07-08-=
2025 18:43:47","Grid outage,site went down because Gen failed to start due =
toGen overload(12.5 kva //180A )SS HIS Francois is informed//Grid return","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid outage,site went down because Gen failed to start due toGen overload(12=
.5 kva //180A )SS HIS Francois is informed//Grid return","gerard.tchangoue@=
matech-cameroun.com","310","07-08-2025 13:11:18","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005640974","F=
OUGEROLE","","07-08-2025 13:01:30","07-08-2025 12:52:59","07-08-2025 13:42:=
53","Grid outage, site went down due to Gen Overload (20Kva, Iload 300 A )I=
HS SS Alphonse is informed // Reduced charge and left site on gen","Siligap=
 Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, site went down due to Gen Overload (20Kva, Iload 300 A )IHS SS Alphons=
e is informed // Reduced charge and left site on gen","edwige.kapawo@matech=
-cameroun.com","513","07-08-2025 13:01:30","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005640764","S=
atcom","","07-08-2025 12:28:27","07-08-2025 12:22:17","07-08-2025 12:31:01"=
,"No power issue on site, Site impacted by Etoa-meki-II_CTR_682 not managed=
 by IHS","Delor Telezing","Customer Equipment Failure","Active","Active Equ=
ipment Failure","Affected by 3rd Party Site","No power issue on site, Site =
impacted by Etoa-meki-II_CTR_682 not managed by IHS","edwige.kapawo@matech-=
cameroun.com","372","07-08-2025 12:28:27","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005639959","ODZ=
A BORNE 10","","07-08-2025 10:30:20","07-08-2025 10:27:14","07-08-2025 19:0=
3:54","Grid outage, Site went down due to Gen overload (12.5 kva, 180A) // =
Grid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down due to Gen overload (12.5 kva, 180=
A) // Grid return","gerard.tchangoue@matech-cameroun.com","187","07-08-2025=
 10:30:20","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005639906","M=
arche Odza","","07-08-2025 10:20:55","07-08-2025 10:20:52","07-08-2025 11:1=
5:59","Grid fluctuation,site went down due to rectifiers dysfunction//Grid =
stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Grid fluctuation,site went down due to rectifiers dysfunction=
//Grid stabilized","edwige.kapawo@matech-cameroun.com","6","07-08-2025 10:2=
0:55","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005639448","M=
EFOU ASSI","","07-08-2025 09:20:08","07-08-2025 09:17:02","07-08-2025 09:26=
:10","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Fanda Brice","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, Site went down before Gen start due =
to poor backup // Grid return","edwige.kapawo@matech-cameroun.com","189","0=
7-08-2025 09:20:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005639398","ETOUDI C=
HAPELLE","","07-08-2025 09:11:27","07-08-2025 09:05:37","07-08-2025 09:11:3=
1","Cascaded Incident from TTO5835665","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on grid with =
U=3D53.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. Notice=
 that it is a repetitive issue.","gerard.tchangoue@matech-cameroun.com","28=
4274","07-08-2025 09:11:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005639399","Etoudi 2=
","","07-08-2025 09:11:27","07-08-2025 09:05:37","07-08-2025 09:11:31","Cas=
caded Incident from TTO5835665","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D53=
.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. Notice that =
it is a repetitive issue.","gerard.tchangoue@matech-cameroun.com","284274",=
"07-08-2025 09:11:27","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005639385","Aba=
ttoir","IHS_YND_694, IHS_YND_211","07-08-2025 09:09:44","07-08-2025 09:05:3=
7","07-08-2025 09:06:31","No power issue site on grid with U=3D53.1V, TX Fm=
e Armand Nguetsa /699949553 from Huawei is informed. Notice that it is a re=
petitive issue.","Fabrice Pouakam","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D53.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. N=
otice that it is a repetitive issue.","gerard.tchangoue@matech-cameroun.com=
","249","07-08-2025 09:09:44","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005639172","Mok=
olo Yaounde","","07-08-2025 08:56:29","07-08-2025 08:52:23","07-08-2025 12:=
00:20","Grid only. Site went down due to Grid Outage on site, no space to d=
eploy MDGE // Grid returned","","Grid Supply","Passive","Grid","National Gr=
id - Grid Outage Issue","Grid only. Site went down due to Grid Outage on si=
te, no space to deploy MDGE // Grid returned","gerard.tchangoue@matech-came=
roun.com","248","07-08-2025 08:56:29","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005639148","Nko=
abang Alembe","","07-08-2025 08:51:24","07-08-2025 08:46:45","07-08-2025 08=
:58:45","Site went down due to insufficiency of rectifiers IHS SS Alphonse =
is informed//Site stabilised","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to insufficiency of r=
ectifiers IHS SS Alphonse is informed//Site stabilised","gerard.tchangoue@m=
atech-cameroun.com","280","07-08-2025 08:51:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005639094","ELOUMDEM=
 CARRIERE 2","","07-08-2025 08:40:27","07-08-2025 08:34:19","07-08-2025 08:=
38:34","Cascaded Incident from TTO5835361","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid return","gerard.tchangoue@matech=
-cameroun.com","286269","07-08-2025 08:40:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005639093","Eto koss=
 Yde","","07-08-2025 08:40:27","07-08-2025 08:34:19","07-08-2025 08:38:34",=
"Cascaded Incident from TTO5835361","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Grid return","gerard.tchangoue@matech-camero=
un.com","286270","07-08-2025 08:40:27","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005639090","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","07-08-2025 08:39:37","07-08-2025 08:34=
:19","07-08-2025 08:38:34","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","Fanda Brice","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor backup // Grid return","gerard.tchangoue@mate=
ch-cameroun.com","321","07-08-2025 08:39:37","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0005639027","Eke=
kam","","07-08-2025 08:23:38","07-08-2025 08:18:28","07-08-2025 09:36:28","=
Site went down because gen failed to start due hybrid system malfunction //=
 He reset hybrid system and gen manually started","TIENTCHEU NZETCHIEU GAEL=
","Equipment Repair","Passive","Hybrid","Hybrid Module","Site went down bec=
ause gen failed to start due hybrid system malfunction // He reset hybrid s=
ystem and gen manually started","edwige.kapawo@matech-cameroun.com","312","=
07-08-2025 08:23:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005638912","TSINGA V=
ILLAGE 2","","07-08-2025 07:56:46","07-08-2025 07:49:47","07-08-2025 08:04:=
08","Cascaded Incident from TTO5835148","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site down due to=
 gen overload 300 A /20 KVA // Gen charge reduced and manual start of gen",=
"edwige.kapawo@matech-cameroun.com","267140","07-08-2025 07:56:46","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005638911","Melen Ba=
'aba","","07-08-2025 07:56:46","07-08-2025 07:49:47","07-08-2025 08:04:08",=
"Cascaded Incident from TTO5835148","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to gen =
overload 300 A /20 KVA // Gen charge reduced and manual start of gen","edwi=
ge.kapawo@matech-cameroun.com","267140","07-08-2025 07:56:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005638910","Nkolfoul=
ou 2","","07-08-2025 07:56:45","07-08-2025 07:49:47","07-08-2025 08:04:08",=
"Cascaded Incident from TTO5835148","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to gen =
overload 300 A /20 KVA // Gen charge reduced and manual start of gen","edwi=
ge.kapawo@matech-cameroun.com","267139","07-08-2025 07:56:45","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005638893","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","07-08-2025 07:52:56","0=
7-08-2025 07:49:47","07-08-2025 08:06:29","Grid outage, site down due to ge=
n overload 300 A /20 KVA // Gen charge reduced and manual start of gen","Si=
ligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gri=
d outage, site down due to gen overload 300 A /20 KVA // Gen charge reduced=
 and manual start of gen","edwige.kapawo@matech-cameroun.com","190","07-08-=
2025 07:52:56","MATECH CMR"
"Closed Complete","Site Down","T0638","IHS_YND_318","NOCINC0005638777","SOA=
 University","","07-08-2025 07:27:49","07-08-2025 07:22:40","07-08-2025 07:=
31:15","Site went down due to 01/02 Rectifier dysfuntionning // He reset it=
: site on battery","Siligap Boris","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to 01/02 Rectifier dysfuntionning /=
/ He reset it: site on battery","gerard.tchangoue@matech-cameroun.com","310=
","07-08-2025 07:27:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005638767","Messassi=
 okolo","","07-08-2025 07:24:51","07-08-2025 07:20:34","07-08-2025 13:42:58=
","Cascaded Incident from TTO5834986","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issue . Grid outage,sit=
e behaves as Grid only site (Gen Noise) // Grid return","gerard.tchangoue@m=
atech-cameroun.com","290533","07-08-2025 07:24:51","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005638747","EMA=
NA BILICK CITY","IHS_YND_279","07-08-2025 07:22:40","07-08-2025 07:20:34","=
07-08-2025 13:50:37","Access issue . Grid outage,site behaves as Grid only =
site (Gen Noise) // Grid return","Fabrice Pouakam","Access Denial","Lease O=
r Legal","Landlord Related Issues","Access Issue - Land Lord","Access issue=
 . Grid outage,site behaves as Grid only site (Gen Noise) // Grid return","=
gerard.tchangoue@matech-cameroun.com","128","07-08-2025 07:22:40","MATECH C=
MR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005638492","Nko=
l-Mebanga","","07-08-2025 06:40:30","07-08-2025 06:36:09","07-08-2025 08:06=
:00","Solar only site, Site went Down due to low Solar// Solar return","Par=
ker Tchoup","Equipment Repair","Passive","Solar","Solar Panel Issue","Solar=
 only site, Site went Down due to low Solar// Solar return","franck.nkomot@=
matech-cameroun.com","262","07-08-2025 06:40:30","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0005637887","Mes=
sassi Ngonlonk","","07-08-2025 04:20:44","07-08-2025 04:16:34","07-08-2025 =
05:06:34","Grid outage site went down because Gen failed to start due to Ge=
n card dysfuntion // He reset it and Gen Manually Started","Fabrice Pouakam=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge site went down because Gen failed to start due to Gen card dysfuntion //=
 He reset it and Gen Manually Started","franck.nkomot@matech-cameroun.com",=
"251","07-08-2025 04:20:44","MATECH CMR"
"Closed Complete","Site Down","T0920","IHS_YND_416","NOCINC0005637678","Ngw=
opi Boga","","07-08-2025 03:22:00","07-08-2025 03:14:59","07-08-2025 03:20:=
59","No power issue, site is on grid with Ubaie=3D54.5V; TX FME Etienne Fop=
a (693961474) from HUAWEI is informed","Kemeni Franklin","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue, site is on grid with Ubaie=3D54.5V; TX FME Etienne Fopa (69396147=
4) from HUAWEI is informed","franck.nkomot@matech-cameroun.com","555","07-0=
8-2025 03:22:00","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005636637","Bit=
eng-Maetur","","06-08-2025 22:01:23","06-08-2025 21:53:10","06-08-2025 22:3=
3:10","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","cedric.=
tiani@matech-cameroun.com","495","06-08-2025 22:01:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005636544","Akak-Nko=
zoa-MTN-IHS","","06-08-2025 21:43:28","06-08-2025 21:33:27","06-08-2025 21:=
40:27","Cascaded Incident from TTO5832613","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
: 50.1V site on Grid. Symphorien (675295205/Huawei) is informed. Site up wi=
thout intervention","christian.fonkou@ihstowers.com","268256","06-08-2025 2=
1:43:28","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0005636197","NKO=
ABANG NKOLO 3","","06-08-2025 20:48:57","06-08-2025 20:40:51","06-08-2025 2=
1:47:20","Grid outage,Gen stopped with alarm low oil pressure// He added oi=
l and started the Gen","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - Low Oil Pressure","Grid outage,Gen stopped with alarm low oi=
l pressure// He added oil and started the Gen","cedric.tiani@matech-camerou=
n.com","487","06-08-2025 20:48:57","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005636174","Bit=
eng-Maetur","","06-08-2025 20:47:03","06-08-2025 20:41:51","06-08-2025 20:5=
7:56","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","cedric.=
tiani@matech-cameroun.com","314","06-08-2025 20:47:03","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0005636104","N=
kolo II New","","06-08-2025 20:37:41","06-08-2025 20:34:27","06-08-2025 20:=
41:18","Grid outage, site went down because Gen started and stopped due to =
Ge Battery faulty // He started Gen with an external battery","Mba Lazare H=
erve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","G=
rid outage, site went down because Gen started and stopped due to Ge Batter=
y faulty // He started Gen with an external battery","vanel.mbiada@matech-c=
ameroun.com","195","06-08-2025 20:37:41","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005635945","NYO=
M FACE MAETUR","","06-08-2025 20:04:56","06-08-2025 20:03:36","06-08-2025 2=
0:54:53","Grid fluctuations , site went down because Gen failed to start du=
e to Grid bad voltage // He made a bridge with the Good phase","Fabrice Pou=
akam","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuations , site went down because Gen failed to start due to =
Grid bad voltage // He made a bridge with the Good phase","cedric.tiani@mat=
ech-cameroun.com","82","06-08-2025 20:04:56","MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0005635574","Nko=
abang MTN","","06-08-2025 19:11:45","06-08-2025 19:03:38","06-08-2025 19:38=
:57","Grid outage,Site went down because Gen failed to start due to Gen in =
stop mode//He manually started the Gen","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,Site went down =
because Gen failed to start due to Gen in stop mode//He manually started th=
e Gen","cedric.tiani@matech-cameroun.com","488","06-08-2025 19:11:45","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005635520","N=
koabang2","","06-08-2025 19:03:50","06-08-2025 18:58:32","06-08-2025 20:38:=
44","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed// He reduced load, Site on Gen","Mba Lazare Herve","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site wen=
t down due to gen overload (22KVA, 330A), SS Blaise IHS is informed// He re=
duced load, Site on Gen","vanel.mbiada@matech-cameroun.com","320","06-08-20=
25 19:03:50","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005635490","EKI=
E","","06-08-2025 18:56:28","06-08-2025 18:55:15","06-08-2025 19:30:33","Gr=
id fluctuations, Site went down because gen failed to start due to grid bad=
 voltage and no rcp on site // He made a bridge with a Good phase","Albran =
Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuations, Site went down because gen failed to start due to=
 grid bad voltage and no rcp on site // He made a bridge with a Good phase"=
,"cedric.tiani@matech-cameroun.com","74","06-08-2025 18:56:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005635110","MEHANDAN=
","","06-08-2025 18:16:26","06-08-2025 18:02:29","06-08-2025 20:31:22","Cas=
caded Incident from TTO5831067","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because gen failed to s=
tart due to grid bad voltage // Gen manually started","vanel.mbiada@matech-=
cameroun.com","273605","06-08-2025 18:16:26","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005635088","Odz=
a II OCM","IHS_YND_528","06-08-2025 18:10:35","06-08-2025 18:02:29","06-08-=
2025 20:44:15","Site went down because gen failed to start due to grid bad =
voltage // Gen manually started","Albran Byorel","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Site went down because gen =
failed to start due to grid bad voltage // Gen manually started","vanel.mbi=
ada@matech-cameroun.com","488","06-08-2025 18:10:35","MATECH CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0005634317","M=
volye-New","","06-08-2025 16:11:42","06-08-2025 16:09:21","06-08-2025 16:20=
:30","Active// No power Issue Site on Grid Ubaie =3D52V, The TX FME Mbah Ho=
siah (674007438) is informed","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site o=
n Grid Ubaie =3D52V, The TX FME Mbah Hosiah (674007438) is informed","vanel=
.mbiada@matech-cameroun.com","143","06-08-2025 16:11:42","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005634083","MBA=
LNGONG LYCEE","","06-08-2025 15:38:50","06-08-2025 15:37:42","06-08-2025 15=
:45:07","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//He reduiced the loa=
d and started Gen manually","Fanda Brice","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Grid outage, Site went down because Gen stopped d=
ue to overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//He=
 reduiced the load and started Gen manually","cedric.tiani@matech-cameroun.=
com","70","06-08-2025 15:38:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005634074","Nsam esc=
ale LP","","06-08-2025 15:36:45","06-08-2025 15:33:00","06-08-2025 15:39:59=
","Cascaded Incident from TTO5829937","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, Site went down before Gen start =
due to poor backup/ // Gen automatically started","cedric.tiani@matech-came=
roun.com","268106","06-08-2025 15:36:45","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005634071","Nsa=
m Sofavinc","IHS_YND_732","06-08-2025 15:36:11","06-08-2025 15:33:00","06-0=
8-2025 15:39:59","Grid outage, Site went down before Gen start due to poor =
backup/ // Gen automatically started","MINKA NICOLAS","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site we=
nt down before Gen start due to poor backup/ // Gen automatically started",=
"cedric.tiani@matech-cameroun.com","193","06-08-2025 15:36:11","MATECH CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0005633924","Eto=
udi 2","","06-08-2025 15:15:20","06-08-2025 15:11:13","06-08-2025 15:20:45"=
,"Active//No power issue, site is on Grid with Ubaie=3D53,7V The Tx FME Arm=
and Nguetsa / 691144412/ from Huawei is informed","Fabrice Pouakam","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue, site is on Grid with Ubaie=3D53,7V The Tx FME =
Armand Nguetsa / 691144412/ from Huawei is informed","vanel.mbiada@matech-c=
ameroun.com","248","06-08-2025 15:15:20","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005633903","N=
koabang Ebolmedjock","","06-08-2025 15:12:33","06-08-2025 15:08:19","06-08-=
2025 15:20:32","Site impacted by Nkolmesseng-Abom(CTR-711) Not Managed By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Site impacted by Nkolmesseng-Abom(CTR-71=
1) Not Managed By IHS","vanel.mbiada@matech-cameroun.com","255","06-08-2025=
 15:12:33","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005633860","MBA=
LNGONG LYCEE","","06-08-2025 15:04:05","06-08-2025 15:03:55","06-08-2025 15=
:09:39","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//He reduiced the loa=
d and started Gen manually","Fanda Brice","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Grid outage, Site went down because Gen stopped d=
ue to overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//He=
 reduiced the load and started Gen manually","cedric.tiani@matech-cameroun.=
com","12","06-08-2025 15:04:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0005633799","Lobo OCM=
","","06-08-2025 14:56:49","06-08-2025 14:40:14","06-08-2025 15:53:15","Cas=
caded Incident from TTO5829567","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage,site went down =
because Gen failed to start //She manually started Gen (SS HIS Pascaline) (=
Deep investigation ongoing)","vanel.mbiada@matech-cameroun.com","995","06-0=
8-2025 14:56:49","MATECH CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0005633766","N=
kolkoumou OCM","","06-08-2025 14:51:11","06-08-2025 14:40:14","06-08-2025 1=
5:53:15","No power issue on site ,site on Grid with Ubaie=3D53,9 V The Tx F=
ME Mouahamadou (691144435) of Huawei is informed.","TIENTCHEU NZETCHIEU GAE=
L","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue on site ,site on Grid with Ubaie=3D53,9 V The=
 Tx FME Mouahamadou (691144435) of Huawei is informed.","vanel.mbiada@matec=
h-cameroun.com","903","06-08-2025 14:51:11","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0005633710","NKO=
MEKUI OCM","IHS_YND_341","06-08-2025 14:42:27","06-08-2025 14:40:14","06-08=
-2025 15:53:15","Grid outage,site went down because Gen failed to start //S=
he manually started Gen (SS HIS Pascaline) (Deep investigation ongoing)","T=
IENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid outage,site went down because Gen failed to start //She =
manually started Gen (SS HIS Pascaline) (Deep investigation ongoing)","cedr=
ic.tiani@matech-cameroun.com","134","06-08-2025 14:42:27","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0005633645","B=
ATA Mokolo OCM","","06-08-2025 14:37:55","06-08-2025 14:33:48","06-08-2025 =
16:17:39","Grid Only, No space to deploy MGE //Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space=
 to deploy MGE //Grid return","cedric.tiani@matech-cameroun.com","248","06-=
08-2025 14:37:55","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005633502","C=
omplexe-BEAC","","06-08-2025 14:15:51","06-08-2025 14:11:40","06-08-2025 14=
:28:40","Site went down due to work Sylvain/691901615 (Dowen) is working on=
 site (SWAP PWC) // End of work","Albran Byorel","Installation Activity","P=
assive","Planned Activity","Installation Activity","Site went down due to w=
ork Sylvain/691901615 (Dowen) is working on site (SWAP PWC) // End of work"=
,"gerard.tchangoue@matech-cameroun.com","252","06-08-2025 14:15:51","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0005633472","E=
TOUDI CHAPELLE","","06-08-2025 14:11:05","06-08-2025 14:07:01","06-08-2025 =
15:02:43","ACTIVE No power issue Ubaie=3D51.2V site on Grid Armand Nguetsa =
(699949553)from Huawei is informed,","Delor Telezing","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No=
 power issue Ubaie=3D51.2V site on Grid Armand Nguetsa (699949553)from Huaw=
ei is informed,","loic.noumsi@matech-cameroun.com","246","06-08-2025 14:11:=
05","MATECH CMR"
"Closed Complete","Site Down","T0288","IHS_YND_001","NOCINC0005633328","Roy=
al Hotel Yde","","06-08-2025 13:53:43","06-08-2025 13:50:37","06-08-2025 14=
:13:31","Site went down because FME was on site for PM // End of work","Pau=
l BIBOUM","Installation Activity","Passive","Planned Activity","Installatio=
n Activity","Site went down because FME was on site for PM // End of work",=
"loic.noumsi@matech-cameroun.com","186","06-08-2025 13:53:43","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005633183","N=
koabang2","","06-08-2025 13:45:36","06-08-2025 13:42:29","06-08-2025 14:15:=
51"," Grid outage, Site went down due to Gen overload (22KVA, 330A), SS Bla=
ise IHS is informed// Grid return","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload"," Grid outage, Site went down due to G=
en overload (22KVA, 330A), SS Blaise IHS is informed// Grid return","gerard=
.tchangoue@matech-cameroun.com","190","06-08-2025 13:45:36","MATECH CMR"
"Closed Complete","Site Down","T1431","IHS_YND_561","NOCINC0005632984","FOU=
GEROLE","","06-08-2025 13:20:06","06-08-2025 13:18:49","06-08-2025 13:20:54=
","No power issue on site U=3D52,5V site on Grid TX FME Julien 693095849 Fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D52,5V site on Grid TX FME Julien 693095849 From Huawei is informed","loi=
c.noumsi@matech-cameroun.com","78","06-08-2025 13:20:06","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005632689","Nko=
abang Alembe","","06-08-2025 12:23:42","06-08-2025 12:21:37","06-08-2025 12=
:23:59","Grid outage, Site went down due to 01/03 Rectifiers dysfunctionnin=
g //  Grid stabilised","Mba Lazare Herve","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Grid outage, Site went down due to 01/03 Rectif=
iers dysfunctionning //  Grid stabilised","loic.noumsi@matech-cameroun.com"=
,"126","06-08-2025 12:23:42","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0005632463","B=
ATA Mokolo OCM","","06-08-2025 11:57:35","06-08-2025 11:54:27","06-08-2025 =
13:39:40"," Grid Only, No space to deploy MDGE  // grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue"," Grid Only, No =
space to deploy MDGE  // grid return","gerard.tchangoue@matech-cameroun.com=
","189","06-08-2025 11:57:35","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005632432","Nko=
abang Alembe","","06-08-2025 11:52:12","06-08-2025 11:50:02","06-08-2025 11=
:54:40","Grid outage, site went down due to Grid bad voltage and no rcp on =
site // He bypassed Grid and started Gen manually","Mba Lazare Herve","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid o=
utage, site went down due to Grid bad voltage and no rcp on site // He bypa=
ssed Grid and started Gen manually","loic.noumsi@matech-cameroun.com","131"=
,"06-08-2025 11:52:12","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005632389","N=
kolso","","06-08-2025 11:44:29","06-08-2025 11:43:21","06-08-2025 11:46:38"=
,"Site went down because Our fme Gael (Matech) was on site for work (PM) //=
 End of work","TIENTCHEU NZETCHIEU GAEL","Installation Activity","Passive",=
"Planned Activity","Installation Activity","Site went down because Our fme =
Gael (Matech) was on site for work (PM) // End of work","gerard.tchangoue@m=
atech-cameroun.com","69","06-08-2025 11:44:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005632325","Mvog-Eba=
nda","","06-08-2025 11:32:33","06-08-2025 11:28:18","06-08-2025 11:36:25","=
Cascaded Incident from TTO5828046","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
Alarm Overload (16KVA /250A) // Grid return","gerard.tchangoue@matech-camer=
oun.com","261385","06-08-2025 11:32:33","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005632320","A=
bom","IHS_YND_269","06-08-2025 11:31:26","06-08-2025 11:28:18","06-08-2025 =
11:36:25","Grid outage, Site went down due to Alarm Overload (16KVA /250A) =
// Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down due to Alarm Overload (16KVA /2=
50A) // Grid return","gerard.tchangoue@matech-cameroun.com","190","06-08-20=
25 11:31:26","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005632195","M=
arche Odza","","06-08-2025 11:08:35","06-08-2025 11:06:24","06-08-2025 11:0=
7:08","Grid fluctuation,site went down due to rectifiers dysfunction//Grid =
stabilisation","Albran Byorel","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Grid fluctuation,site went down due to rectifiers dysfunct=
ion//Grid stabilisation","loic.noumsi@matech-cameroun.com","133","06-08-202=
5 11:08:35","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005632005","N=
koabang2","","06-08-2025 10:43:11","06-08-2025 10:40:06","06-08-2025 10:47:=
53","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Site stabilised","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due t=
o gen overload (22KVA, 330A), SS Blaise IHS is informed // Site stabilised"=
,"loic.noumsi@matech-cameroun.com","187","06-08-2025 10:43:11","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005631960","Mon=
tee-Jouvence-II","","06-08-2025 10:34:08","06-08-2025 10:32:04","06-08-2025=
 10:34:34","Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Grid return","loic.noumsi@matech-cameroun.com","=
125","06-08-2025 10:34:08","MATECH CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0005631737","N=
yanon","","06-08-2025 09:48:51","06-08-2025 09:45:07","06-08-2025 14:53:07"=
,"Site went down due to relay 12V is faulty //He replaced  it and site on G=
en","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACD=
G - Relay Faulty","Site went down due to relay 12V is faulty //He replaced =
 it and site on Gen","gerard.tchangoue@matech-cameroun.com","226","06-08-20=
25 09:48:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005631051","Etoudi 2=
","","06-08-2025 07:58:51","06-08-2025 07:54:00","06-08-2025 07:55:57","Cas=
caded Incident from TTO5826644","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D53=
.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. Notice that =
it is a repetitive issue.","loic.noumsi@matech-cameroun.com","267040","06-0=
8-2025 07:58:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005631049","ETOUDI C=
HAPELLE","","06-08-2025 07:58:51","06-08-2025 07:54:00","06-08-2025 07:55:5=
7","Cascaded Incident from TTO5826644","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on grid with =
U=3D53.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. Notice=
 that it is a repetitive issue.","loic.noumsi@matech-cameroun.com","267039"=
,"06-08-2025 07:58:51","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005631043","Aba=
ttoir","IHS_YND_694, IHS_YND_211","06-08-2025 07:58:04","06-08-2025 07:54:0=
0","06-08-2025 07:55:57","No power issue site on grid with U=3D53.1V, TX Fm=
e Armand Nguetsa /699949553 from Huawei is informed. Notice that it is a re=
petitive issue.","Fabrice Pouakam","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D53.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. N=
otice that it is a repetitive issue.","loic.noumsi@matech-cameroun.com","24=
6","06-08-2025 07:58:04","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005630525","EKI=
E","","06-08-2025 05:31:44","06-08-2025 05:29:34","06-08-2025 05:39:44","Gr=
id fluctuations, Site went down because gen failed to start due to grid bad=
 voltage and no rcp on site // He bypassed grid and manually started the ge=
n","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuations, Site went down because gen failed to s=
tart due to grid bad voltage and no rcp on site // He bypassed grid and man=
ually started the gen","cedric.tiani@matech-cameroun.com","131","06-08-2025=
 05:31:44","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005630297","Nko=
l-Mebanga","","06-08-2025 03:50:56","06-08-2025 03:45:50","06-08-2025 08:57=
:40","Solar only site, Site went Down due to low Solar// Solar return","Par=
ker Tchoup","Equipment Repair","Passive","Solar","Solar Panel Issue","Solar=
 only site, Site went Down due to low Solar// Solar return","cedric.tiani@m=
atech-cameroun.com","307","06-08-2025 03:50:56","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005629993","MBA=
LNGONG LYCEE","","06-08-2025 01:39:07","06-08-2025 01:35:53","06-08-2025 02=
:01:16","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed//Grid return","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//G=
rid return","cedric.tiani@matech-cameroun.com","197","06-08-2025 01:39:07",=
"MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005629642","Mfa=
ndena","","05-08-2025 23:26:44","05-08-2025 23:23:38","05-08-2025 23:39:04"=
,"Grid outage, site went down due to insufficiency of rectifiers //Site sta=
bilised","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Grid outage, site went down due to insufficiency of rectifiers =
//Site stabilised","cedric.tiani@matech-cameroun.com","186","05-08-2025 23:=
26:44","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005629585","EKI=
E","","05-08-2025 23:12:37","05-08-2025 23:08:30","06-08-2025 00:36:51","Gr=
id bad voltage, Site down because gen fail to start due to grid PCF faulty =
// Gen manually started","Albran Byorel","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","Grid bad voltage, Site down because=
 gen fail to start due to grid PCF faulty // Gen manually started","cedric.=
tiani@matech-cameroun.com","248","05-08-2025 23:12:37","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005629419","Bit=
eng-Maetur","","05-08-2025 22:31:11","05-08-2025 22:22:03","05-08-2025 22:5=
0:11","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","cedric.=
tiani@matech-cameroun.com","550","05-08-2025 22:31:11","MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005629167","Mfa=
ndena","","05-08-2025 21:45:20","05-08-2025 21:43:10","05-08-2025 22:01:51"=
,"Grid outage, site went down due to insufficiency of rectifiers //Site sta=
bilised","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Grid outage, site went down due to insufficiency of rectifiers =
//Site stabilised","cedric.tiani@matech-cameroun.com","131","05-08-2025 21:=
45:20","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005628862","Bit=
eng-Maetur","","05-08-2025 20:56:03","05-08-2025 20:54:53","05-08-2025 21:0=
9:05","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","cedric.=
tiani@matech-cameroun.com","71","05-08-2025 20:56:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005628775","ELOUMDEM=
 CARRIERE 2","","05-08-2025 20:45:18","05-08-2025 20:42:21","05-08-2025 20:=
47:00","Cascaded Incident from TTO5824121","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage,site went down du=
e to PWC Huawei dysfunction//Site stabilised","cedric.tiani@matech-cameroun=
.com","263931","05-08-2025 20:45:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005628774","Eto koss=
 Yde","","05-08-2025 20:45:18","05-08-2025 20:42:21","05-08-2025 20:47:00",=
"Cascaded Incident from TTO5824121","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,site went down due to PW=
C Huawei dysfunction//Site stabilised","cedric.tiani@matech-cameroun.com","=
263931","05-08-2025 20:45:18","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005628772","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","05-08-2025 20:44:28","05-08-2025 20:42=
:21","05-08-2025 20:47:00","Grid outage,site went down due to PWC Huawei dy=
sfunction//Site stabilised","Fanda Brice","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","Grid outage,site went down due to PW=
C Huawei dysfunction//Site stabilised","cedric.tiani@matech-cameroun.com","=
130","05-08-2025 20:44:28","MATECH CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0005628622","Nsi=
meyong Terre Rouge","","05-08-2025 20:22:26","05-08-2025 20:21:17","05-08-2=
025 20:24:13","Grid outage, Site went downt before Gen start due to poor ba=
ttery backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, Site went downt =
before Gen start due to poor battery backup // Grid return","cedric.tiani@m=
atech-cameroun.com","70","05-08-2025 20:22:26","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005628435","OTE=
LE MTN","","05-08-2025 19:49:01","05-08-2025 19:40:53","05-08-2025 19:50:52=
","site went down due to relay Q11 of behind the rectifiers barette disfunc=
tionning//he bypassed it","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Relay","site went down due to relay Q11 of behind the rectifiers=
 barette disfunctionning//he bypassed it","cedric.tiani@matech-cameroun.com=
","490","05-08-2025 19:49:01","MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005628249","Mfa=
ndena","","05-08-2025 19:13:42","05-08-2025 19:08:32","05-08-2025 19:26:37"=
,"Grid outage, site went down due to insufficiency of rectifiers //Site sta=
bilised","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Grid outage, site went down due to insufficiency of rectifiers =
//Site stabilised","cedric.tiani@matech-cameroun.com","311","05-08-2025 19:=
13:42","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005628128","ODZ=
A BORNE 10","","05-08-2025 18:51:47","05-08-2025 18:45:40","06-08-2025 01:1=
2:10","Grid outage, Site went down due to Gen overload (12.5 kva, 180A) // =
Charge reduced and gen manually started","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to=
 Gen overload (12.5 kva, 180A) // Charge reduced and gen manually started",=
"cedric.tiani@matech-cameroun.com","368","05-08-2025 18:51:47","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005627646","B=
arriere","","05-08-2025 17:33:40","05-08-2025 17:32:28","05-08-2025 18:20:4=
7","Site went down due to work Giress is working on site (PM) // End of wor=
k","Hyemafo Gildas","Installation Activity","Passive","Planned Activity","I=
nstallation Activity","Site went down due to work Giress is working on site=
 (PM) // End of work","vanel.mbiada@matech-cameroun.com","75","05-08-2025 1=
7:33:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005627424","Nsam esc=
ale LP","","05-08-2025 17:04:15","05-08-2025 17:01:29","05-08-2025 17:07:50=
","Cascaded Incident from TTO5822637","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Grid return","cedric.tiani@matech-cameroun.com","2629=
77","05-08-2025 17:04:15","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005627420","Nsa=
m Sofavinc","IHS_YND_732","05-08-2025 17:03:39","05-08-2025 17:01:29","05-0=
8-2025 17:07:50","Grid Outage, Site went down before Gen start due to poor =
backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before =
Gen start due to poor backup // Grid return","cedric.tiani@matech-cameroun.=
com","131","05-08-2025 17:03:39","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005627046","S=
atcom","","05-08-2025 16:01:51","05-08-2025 15:53:39","05-08-2025 16:07:39"=
,"No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand ngu=
etsa(691144412) From huawei is informed.","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand nguetsa(6=
91144412) From huawei is informed.","vanel.mbiada@matech-cameroun.com","494=
","05-08-2025 16:01:51","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005626980","E=
mombo","","05-08-2025 15:49:53","05-08-2025 15:47:35","05-08-2025 16:33:02"=
,"Site went down due to CB(100A) that tripped  battery in PWC//He rearmed i=
t and site on Grid ","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to CB=
(100A) that tripped  battery in PWC//He rearmed it and site on Grid ","vane=
l.mbiada@matech-cameroun.com","138","05-08-2025 15:49:53","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005626819","Nsi=
malen MTN","","05-08-2025 15:15:58","05-08-2025 15:14:39","05-08-2025 15:44=
:13","Grid outage . landlord stopped the generator because it was making to=
o noise//Gen manually started","Albran Byorel","Access Denial","Lease Or Le=
gal","Landlord Related Issues","Access Issue - Land Lord","Grid outage . la=
ndlord stopped the generator because it was making too noise//Gen manually =
started","cedric.tiani@matech-cameroun.com","80","05-08-2025 15:15:58","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005626768","E=
lig Edzoa","","05-08-2025 15:06:59","05-08-2025 15:06:48","05-08-2025 15:14=
:57","Grid outage, site down because generator did not start due to flood a=
fter the rain. // Grid return","Delor Telezing","Fuel Outage (Probable)","P=
assive","Diesel","Tank Sealing Issue - Water In The Fuel","Grid outage, sit=
e down because generator did not start due to flood after the rain. // Grid=
 return","vanel.mbiada@matech-cameroun.com","12","05-08-2025 15:06:59","MAT=
ECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005626760","Mai=
son komkana New","","05-08-2025 15:04:54","05-08-2025 15:02:46","05-08-2025=
 15:06:02","Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","cedric.tiani@matech-cameroun.com","=
128","05-08-2025 15:04:54","MATECH CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0005626590","Sap=
eur","","05-08-2025 14:30:38","05-08-2025 14:27:28","05-08-2025 14:35:46","=
Site went down due to Fme Silvin ( 671881683) from BTR who is on site (SWAP=
P of PWC)//End of work","Mboua Thierry","Installation Activity","Passive","=
Planned Activity","Installation Activity","Site went down due to Fme Silvin=
 ( 671881683) from BTR who is on site (SWAPP of PWC)//End of work","vanel.m=
biada@matech-cameroun.com","191","05-08-2025 14:30:38","MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0005626256","Nko=
lmvack","","05-08-2025 13:31:31","05-08-2025 13:29:24","05-08-2025 13:45:17=
","Grid outage, Site went down because Gen start and stopped with ""High te=
mp""alarm // he added water and manually started the Gen","Parker Tchoup","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, Site went down because Gen start and stopped with=
 ""High temp""alarm // he added water and manually started the Gen","loic.n=
oumsi@matech-cameroun.com","128","05-08-2025 13:31:31","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005626136","Nsi=
malen MTN","","05-08-2025 13:10:06","05-08-2025 13:07:02","05-08-2025 13:19=
:39","Grid outage, Site went down because landlord stopped the generator du=
e to noise it is making //Gen manually started","Albran Byorel","Access Den=
ial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord",=
"Grid outage, Site went down because landlord stopped the generator due noi=
se it is making //Gen manually started","loic.noumsi@matech-cameroun.com","=
185","05-08-2025 13:10:06","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005625936","S=
atcom","","05-08-2025 12:33:30","05-08-2025 12:29:14","05-08-2025 12:30:10"=
,"No power issue on site, Site impacted by Etoa meki II which is not manage=
d by IHS","Delor Telezing","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue on site, Site impacte=
d by Etoa meki II which is not managed by IHS","edwige.kapawo@matech-camero=
un.com","258","05-08-2025 12:33:30","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005625847","Eli=
g Edzoa","","05-08-2025 12:15:31","05-08-2025 12:13:25","05-08-2025 12:17:3=
3","Grid outage, site down because generator did not start due to flood aft=
er the rain. // he started the generator with a can of fuel.","Delor Telezi=
ng","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water=
 In The Fuel","Grid outage, site down because generator did not start due t=
o flood after the rain. // he started the generator with a can of fuel.","l=
oic.noumsi@matech-cameroun.com","127","05-08-2025 12:15:31","MATECH CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0005625781","Sap=
eur","","05-08-2025 12:05:08","05-08-2025 12:03:58","05-08-2025 12:13:20","=
Site went down due to Fme Silvin ( 671881683) from BTR who is on site (SWAP=
P of PWC) // End of work","Mboua Thierry","Installation Activity","Passive"=
,"Planned Activity","Installation Activity","Site went down due to Fme Silv=
in ( 671881683) from BTR who is on site (SWAPP of PWC) // End of work","loi=
c.noumsi@matech-cameroun.com","71","05-08-2025 12:05:08","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005625588","T=
SINGA VILLAGE 2","","05-08-2025 11:30:57","05-08-2025 11:28:49","05-08-2025=
 11:33:27","Site went down because SS IHS Bernard ATANGANA was on site for =
work (PM) // End of work","Delor Telezing","Installation Activity","Passive=
","Planned Activity","Installation Activity","Site went down because SS IHS=
 Bernard ATANGANA was on site for work (PM) // End of work","edwige.kapawo@=
matech-cameroun.com","130","05-08-2025 11:30:57","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005625577","O=
lembe","","05-08-2025 11:27:34","05-08-2025 11:26:22","05-08-2025 11:49:56"=
,"Site went down because fme Fabrice is on site to work (PM) // End of work=
","Fabrice Pouakam","Installation Activity","Passive","Planned Activity","I=
nstallation Activity","Site went down because our fme was on site to work (=
PM) // End of work","edwige.kapawo@matech-cameroun.com","74","05-08-2025 11=
:27:34","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005625513","O=
LAMA","","05-08-2025 11:20:54","05-08-2025 11:19:45","05-08-2025 11:29:50",=
"Active // No power issue on site Ubaie: 54.6V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue on site Ubaie: 54.6V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","edwige.kapawo@matech-cameroun.com","71","05-08-2=
025 11:20:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0005625431","Anguissa=
 New","","05-08-2025 11:06:27","05-08-2025 11:05:46","05-08-2025 11:09:53",=
"Cascaded Incident from TTO5820424","MINKA NICOLAS","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active // No power issue U =3D54,6V s=
ite on Grid. The Tx FME Eloundou (693212405 )from Huawei is informed.","edw=
ige.kapawo@matech-cameroun.com","262554","05-08-2025 11:06:27","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005625426","L=
abogenie","IHS_YND_568","05-08-2025 11:05:51","05-08-2025 11:05:46","05-08-=
2025 11:09:53","Active // No power issue U =3D54,6V site on Grid. The Tx FM=
E Eloundou (693212405 )from Huawei is informed.","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue U =3D54,6V site on Grid. The Tx FME Eloundou (693212405 )from=
 Huawei is informed.","edwige.kapawo@matech-cameroun.com","7","05-08-2025 1=
1:05:51","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005625292","E=
lig Edzoa","","05-08-2025 10:44:57","05-08-2025 10:42:50","05-08-2025 11:44=
:31","Grid outage, site down because generator did not start due to flood a=
fter the rain. // he started the generator with a can of fuel.","Delor Tele=
zing","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Wat=
er In The Fuel","Grid outage, site down because generator did not start due=
 to flood after the rain. // he started the generator with a can of fuel.",=
"edwige.kapawo@matech-cameroun.com","128","05-08-2025 10:44:57","MATECH CMR=
"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005625238","N=
kolfon Cimencam","","05-08-2025 10:34:57","05-08-2025 10:31:52","05-08-2025=
 10:32:34","Site is impacted by Afanoya II (Not manage by IHS)","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Site is impacted by Afanoya II (Not manage by IHS)","loic=
.noumsi@matech-cameroun.com","187","05-08-2025 10:34:57","MATECH CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0005625202","N=
KONGKARAK","","05-08-2025 10:29:31","05-08-2025 10:25:18","05-08-2025 11:25=
:24","Grid outage, Site went down because Gen started and stopped due to Hi=
gh temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU=
 GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Grid outage, Site went down because Gen started and st=
opped due to High temp alarm //He added water and Gen start manually","edwi=
ge.kapawo@matech-cameroun.com","254","05-08-2025 10:29:31","MATECH CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0005625192","Sap=
eur","","05-08-2025 10:28:01","05-08-2025 10:25:57","05-08-2025 10:45:46","=
Site went down due to Fme Silvin ( 671881683) from BTR who is on site (SWAP=
P of PWC) // End of work","Mboua Thierry","Installation Activity","Passive"=
,"Planned Activity","Installation Activity","Site went down due to Fme Silv=
in ( 671881683) from BTR who is on site (SWAPP of PWC) // End of work","loi=
c.noumsi@matech-cameroun.com","126","05-08-2025 10:28:01","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005625133","Aka=
k-Nkozoa-MTN-IHS","","05-08-2025 10:14:35","05-08-2025 10:10:28","05-08-202=
5 10:20:39","Site went down due to to work, Giress (696720528 / Matech) was=
 on site for work (PM) // End of work","Fabrice Pouakam","Equipment Replace=
ment","Passive","Planned Activity","Planned Activity - Passive","Site went =
down due to to work, Giress (696720528 / Matech) was on site for work (PM) =
// End of work","edwige.kapawo@matech-cameroun.com","250","05-08-2025 10:14=
:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005625050","Melen Ba=
'aba","","05-08-2025 10:03:19","05-08-2025 09:58:26","05-08-2025 10:26:40",=
"Cascaded Incident from TTO5819976","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to gen =
overload 300 A /20 KVA // Gen charge reduced and manual start of gen","edwi=
ge.kapawo@matech-cameroun.com","266759","05-08-2025 10:03:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005625051","TSINGA V=
ILLAGE 2","","05-08-2025 10:03:19","05-08-2025 09:58:26","05-08-2025 10:26:=
40","Cascaded Incident from TTO5819976","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site down due to=
 gen overload 300 A /20 KVA // Gen charge reduced and manual start of gen",=
"edwige.kapawo@matech-cameroun.com","266760","05-08-2025 10:03:19","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005625049","Nkolfoul=
ou 2","","05-08-2025 10:03:18","05-08-2025 09:58:26","05-08-2025 10:26:40",=
"Cascaded Incident from TTO5819976","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to gen =
overload 300 A /20 KVA // Gen charge reduced and manual start of gen","edwi=
ge.kapawo@matech-cameroun.com","266761","05-08-2025 10:03:18","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005625035","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","05-08-2025 10:01:37","0=
5-08-2025 09:58:26","05-08-2025 10:28:36","Grid outage, site down due to ge=
n overload 300 A /20 KVA // Gen charge reduced and manual start of gen","Si=
ligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gri=
d outage, site down due to gen overload 300 A /20 KVA // Gen charge reduced=
 and manual start of gen","edwige.kapawo@matech-cameroun.com","193","05-08-=
2025 10:01:37","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005624932","MBA=
LNGONG LYCEE","","05-08-2025 09:44:12","05-08-2025 09:41:03","05-08-2025 19=
:42:59","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//He reduiced the loa=
d and started Gen manually","Fanda Brice","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Grid outage, Site went down because Gen stopped d=
ue to overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//He=
 reduiced the load and started Gen manually","edwige.kapawo@matech-cameroun=
.com","192","05-08-2025 09:44:12","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005624729","OTE=
LE MTN","","05-08-2025 09:06:24","05-08-2025 09:04:17","05-08-2025 09:07:55=
","Grid Fluctuation, site went down before Gen start due to poor battery ba=
ckup // Grid stabilised","Fanda Brice","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went down be=
fore Gen start due to poor battery backup // Grid stabilised","loic.noumsi@=
matech-cameroun.com","128","05-08-2025 09:06:24","MATECH CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0005624703","P=
olytechnique","","05-08-2025 09:01:02","05-08-2025 08:58:54","05-08-2025 17=
:50:54","Grid Only:  Site went down because  Power cable has been  stolen o=
n site //He replaced the cable and site on Grid","","Site Asset Theft","The=
ft","Theft","DC Cable Stolen","  Site went down because  Power cable has be=
en  stolen on site //He replaced the cable and site on Grid","loic.noumsi@m=
atech-cameroun.com","130","05-08-2025 09:01:02","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005624601","Eli=
g Edzoa","","05-08-2025 08:41:10","05-08-2025 08:39:58","05-08-2025 09:42:2=
7","Grid outage, site down because generator did not start due to flood aft=
er the rain. // he started the generator with a can of fuel.","Delor Telezi=
ng","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water=
 In The Fuel","Grid outage, site down because generator did not start due t=
o flood after the rain. // he started the generator with a can of fuel.","l=
oic.noumsi@matech-cameroun.com","74","05-08-2025 08:41:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005624553","Etoudi 2=
","","05-08-2025 08:28:20","05-08-2025 08:24:23","05-08-2025 08:37:58","Cas=
caded Incident from TTO5819444","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active // No power issue site on grid w=
ith Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. No=
tice that it is a repetitive issue.","edwige.kapawo@matech-cameroun.com","2=
65182","05-08-2025 08:28:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005624552","ETOUDI C=
HAPELLE","","05-08-2025 08:28:19","05-08-2025 08:24:23","05-08-2025 08:37:5=
8","Cascaded Incident from TTO5819444","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active // No power issue site on =
grid with Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is inform=
ed. Notice that it is a repetitive issue.","edwige.kapawo@matech-cameroun.c=
om","265181","05-08-2025 08:28:19","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005624549","Aba=
ttoir","IHS_YND_694, IHS_YND_211","05-08-2025 08:27:30","05-08-2025 08:24:2=
3","05-08-2025 08:37:58","Active // No power issue site on grid with Ubaie:=
 53.1V, TX Fme Armand Nguetsa (699949553 /Huawei) is informed. Notice that =
it is a repetitive issue.","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power=
 issue site on grid with Ubaie: 53.1V, TX Fme Armand Nguetsa (699949553 /Hu=
awei) is informed. Notice that it is a repetitive issue.","edwige.kapawo@ma=
tech-cameroun.com","189","05-08-2025 08:27:30","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005624334","OTE=
LE MTN","","05-08-2025 07:30:41","05-08-2025 07:28:33","05-08-2025 07:30:28=
","Grid Fluctuation, site went down before Gen start due to poor battery ba=
ckup // Grid restoration","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went down b=
efore Gen start due to poor battery backup // Grid restoration","loic.noums=
i@matech-cameroun.com","129","05-08-2025 07:30:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005624153","Elig-Edz=
oa","","05-08-2025 06:42:38","05-08-2025 06:39:50","05-08-2025 08:19:47","C=
ascaded Incident from TTO5819009","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Site went down because Gen failed to start due to=
 CB Gen tripped // He rearmed CB and site on gen","vanel.mbiada@matech-came=
roun.com","292904","05-08-2025 06:42:38","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005624149","N=
taba","IHS_YND_133","05-08-2025 06:41:57","05-08-2025 06:39:50","05-08-2025=
 08:23:54","Site went down because Gen failed to start due to CB Gen trippe=
d // He rearmed CB and site on gen","Delor Telezing","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Load Breaker","Site went down because Gen failed =
to start due to CB Gen tripped // He rearmed CB and site on gen","vanel.mbi=
ada@matech-cameroun.com","129","05-08-2025 06:41:57","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005624053","Nko=
l-Mebanga","","05-08-2025 06:06:27","05-08-2025 05:56:59","05-08-2025 08:40=
:17","Solar only site, Site went Down due to low Solar// Solar return","Par=
ker Tchoup","Equipment Repair","Passive","Solar","Solar Panel Issue","Solar=
 only site, Site went Down due to low Solar// Solar return","franck.nkomot@=
matech-cameroun.com","1111","05-08-2025 06:06:27","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005622996","N=
koabang2","","04-08-2025 23:17:31","04-08-2025 23:15:25","05-08-2025 08:12:=
10","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed// He reduced load, Site on Gen","Mba Lazare Herve","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site wen=
t down due to gen overload (22KVA, 330A), SS Blaise IHS is informed// He re=
duced load, Site on Gen","vanel.mbiada@matech-cameroun.com","129","04-08-20=
25 23:17:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005622955","MBIMBIM"=
,"","04-08-2025 23:03:01","04-08-2025 22:37:04","05-08-2025 00:13:57","Casc=
aded Incident from TTO5817583","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybride Module malfunction. // Reset an=
d Manual start of Gen ( module to be replaced )","olivier.kwedi@ihstowers.c=
om","1557","04-08-2025 23:03:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005622954","Ngoum","=
","04-08-2025 23:03:01","04-08-2025 22:37:04","05-08-2025 00:13:57","Cascad=
ed Incident from TTO5817583","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Hybride Module malfunction. // Reset and =
Manual start of Gen ( module to be replaced )","olivier.kwedi@ihstowers.com=
","1557","04-08-2025 23:03:01","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005622952","N=
kolfon Cimencam","","04-08-2025 23:02:55","04-08-2025 22:57:43","04-08-2025=
 23:04:56","Site is impacted by Afanoya II (Not manage by IHS)","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","Aff=
ected by 3rd Party Site","Site is impacted by Afanoya II (Not manage by IHS=
)","vanel.mbiada@matech-cameroun.com","314","04-08-2025 23:02:55","MATECH C=
MR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005622883","M=
atsari","","04-08-2025 22:42:20","04-08-2025 22:37:04","05-08-2025 00:13:57=
","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Hybride Module malfunction. // Reset and Manual start of Gen ( mo=
dule to be replaced )","vanel.mbiada@matech-cameroun.com","1034","04-08-202=
5 22:42:20","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0005622878","Y=
oko OCM","","04-08-2025 22:41:54","04-08-2025 22:37:04","05-08-2025 00:13:5=
7","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Hybride Module malfunction. // Reset and Manual start of Gen ( m=
odule to be replaced )","vanel.mbiada@matech-cameroun.com","1071","04-08-20=
25 22:41:54","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005622663","Bit=
eng-Maetur","","04-08-2025 21:53:09","04-08-2025 21:48:43","04-08-2025 22:1=
8:08","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","cedric.=
tiani@matech-cameroun.com","268","04-08-2025 21:53:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005622567","Melen Ba=
'aba","","04-08-2025 21:36:23","04-08-2025 21:29:30","04-08-2025 22:04:44",=
"Cascaded Incident from TTO5817244","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down b=
ecause Gen failed to start due to PWC dysfunctionning // Site stabilised","=
vanel.mbiada@matech-cameroun.com","268493","04-08-2025 21:36:23","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005622566","Nkolfoul=
ou 2","","04-08-2025 21:36:22","04-08-2025 21:29:30","04-08-2025 22:04:44",=
"Cascaded Incident from TTO5817244","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down b=
ecause Gen failed to start due to PWC dysfunctionning // Site stabilised","=
vanel.mbiada@matech-cameroun.com","268493","04-08-2025 21:36:22","MATECH CM=
R"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005622554","N=
kolfoulou","IHS_YND_278, IHS_YND_308","04-08-2025 21:34:41","04-08-2025 21:=
29:30","04-08-2025 22:04:44","Grid fluctuation, Site went down because Gen =
failed to start due to PWC dysfunctionning // Site stabilised","Siligap Bor=
is","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply Is=
sue","Grid fluctuation, Site went down because Gen failed to start due to P=
WC dysfunctionning // Site stabilised","vanel.mbiada@matech-cameroun.com","=
312","04-08-2025 21:34:41","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005622481","E=
mombo","","04-08-2025 21:24:51","04-08-2025 21:24:46","04-08-2025 21:48:48"=
,"No power issue, site is on Grid with Ubaie=3D53,8V, TX FME Eloundou (6525=
86578) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue, site is on Grid with Ubaie=3D53,8V, TX FME Eloundou (652586578) from Hu=
awei is informed","vanel.mbiada@matech-cameroun.com","6","04-08-2025 21:24:=
51","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005622125","E=
mombo","","04-08-2025 20:19:23","04-08-2025 20:17:14","04-08-2025 20:19:58"=
,"No power issue, site is on Grid with Ubaie=3D53,8V, TX FME Eloundou (6525=
86578) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue, site is on Grid with Ubaie=3D53,8V, TX FME Eloundou (652586578) from Hu=
awei is informedNo power issue, site is on Grid with Ubaie=3D53,8V, TX FME =
Eloundou (652586578) from Huawei is informed","vanel.mbiada@matech-cameroun=
.com","130","04-08-2025 20:19:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0005622074","Anguissa=
 New","","04-08-2025 20:09:01","04-08-2025 20:03:11","04-08-2025 20:38:58",=
"Cascaded Incident from TTO5816717","MINKA NICOLAS","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue U =3D54,6V site on Gri=
d. The Tx FME Eloundou (693212405 )from Huawei is informed.","vanel.mbiada@=
matech-cameroun.com","266527","04-08-2025 20:09:01","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005622073","L=
abogenie","IHS_YND_568","04-08-2025 20:08:20","04-08-2025 20:03:11","04-08-=
2025 20:38:58","No power issue U =3D54,6V site on Grid. The Tx FME Eloundou=
 (693212405 )from Huawei is informed.","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D5=
4,6V site on Grid. The Tx FME Eloundou (693212405 )from Huawei is informed.=
","vanel.mbiada@matech-cameroun.com","311","04-08-2025 20:08:20","MATECH CM=
R"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005622065","Nko=
lbisson IITA LP","","04-08-2025 20:05:09","04-08-2025 20:02:02","04-08-2025=
 20:07:26","No power issue site on grid with U=3D53.8v Mohamadou(69114435) =
from Huawei is informed. Noticed that it is impacted by Nkolbisson 2 ocm no=
t managed by IHS","","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.8v=
 Mohamadou(69114435) from Huawei is informed. Noticed that it is impacted b=
y Nkolbisson 2 ocm not managed by IHS","cedric.tiani@matech-cameroun.com","=
188","04-08-2025 20:05:09","MATECH CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0005622007","Sap=
eur","","04-08-2025 19:56:16","04-08-2025 19:50:06","04-08-2025 20:27:41","=
Site went down due to Fme Silvin ( 671881683) from BTR is on site (SWAPP of=
 PWC and GEN)//End of work","Mboua Thierry","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to Fme Si=
lvin ( 671881683) from BTR is on site (SWAPP of PWC and GEN)//End of work",=
"cedric.tiani@matech-cameroun.com","371","04-08-2025 19:56:16","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005621596","N=
kolbong","","04-08-2025 18:35:49","04-08-2025 18:33:38","04-08-2025 18:52:0=
1","Grid outage, site went down because gen ran untill fuel shortage // Ref=
ueling Done","Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran untill fuel shortage // Re=
fueling Done","vanel.mbiada@matech-cameroun.com","133","04-08-2025 18:35:49=
","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005621472","OTE=
LE MTN","","04-08-2025 18:05:04","04-08-2025 18:03:57","04-08-2025 18:06:57=
","Grid Fluctuation, site went down before Gen start due to poor battery ba=
ckup // Grid restoration","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went down b=
efore Gen start due to poor battery backup // Grid restoration","cedric.tia=
ni@matech-cameroun.com","69","04-08-2025 18:05:04","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005621217","Eto=
udi","","04-08-2025 17:17:38","04-08-2025 17:10:30","04-08-2025 17:18:48","=
Grid Fluctuation, site went down before Gen start due to poor battery backu=
p // Grid restoration","Fabrice Pouakam","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went down =
before Gen start due to poor battery backup // Grid restoration","cedric.ti=
ani@matech-cameroun.com","430","04-08-2025 17:17:38","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005621080","E=
toudi","","04-08-2025 16:52:52","04-08-2025 16:50:32","04-08-2025 16:52:52"=
,"Grid Fluctuation, site went down before Gen start due to poor battery bac=
kup // Grid restoration","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went dow=
n before Gen start due to poor battery backup // Grid restoration","vanel.m=
biada@matech-cameroun.com","141","04-08-2025 16:52:52","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0005621034","Nko=
lfoulou","","04-08-2025 16:41:31","04-08-2025 16:39:21","04-08-2025 16:41:4=
5","Site went down because Gen failed to start due to PWC dysfunctionning /=
/ Site stabilised","Siligap Boris","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module Overloaded","Site went down because Gen failed to start =
due to PWC dysfunctionning // Site stabilised","cedric.tiani@matech-camerou=
n.com","131","04-08-2025 16:41:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_078","NOCINC0005620948","An-March=
e-Melen","","04-08-2025 16:26:55","04-08-2025 16:18:50","04-08-2025 16:26:3=
0","Cascaded Incident from TTO5815458","","Cascade Outage","Active","Cascad=
e Active","Cascade Active","Site impacteced by Nkolbisson nodal ","vanel.mb=
iada@matech-cameroun.com","265640","04-08-2025 16:26:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0005620949","Dagobert=
","","04-08-2025 16:26:55","04-08-2025 16:18:50","04-08-2025 16:26:30","Cas=
caded Incident from TTO5815458","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Site impacteced by Nkolbisson =
nodal ","vanel.mbiada@matech-cameroun.com","265641","04-08-2025 16:26:55","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0005620947","Nkolbi-B=
oss","","04-08-2025 16:26:54","04-08-2025 16:18:50","04-08-2025 16:26:30","=
Cascaded Incident from TTO5815458","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","Site impacteced by Nkolbiss=
on nodal ","vanel.mbiada@matech-cameroun.com","265640","04-08-2025 16:26:54=
","MATECH CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0005620933","N=
kolbisson usine des eaux","IHS_YND_273, IHS_YND_078, IHS_YND_286","04-08-20=
25 16:24:59","04-08-2025 16:18:50","04-08-2025 16:26:30","Site impacteced b=
y( Nkolbisson nodal) site not managed by IHS","TIENTCHEU NZETCHIEU GAEL","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Site impacteced by( Nkolbisson nodal) site not managed by IHS","v=
anel.mbiada@matech-cameroun.com","370","04-08-2025 16:24:59","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005620870","Cit=
e des nations","","04-08-2025 16:09:28","04-08-2025 16:04:20","04-08-2025 1=
6:10:01","Grid outage,site went down before Gen started due to Poor battery=
 backup//Gen automatically started","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage,site went do=
wn before Gen started due to Poor battery backup//Gen automatically started=
","cedric.tiani@matech-cameroun.com","310","04-08-2025 16:09:28","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_030","NOCINC0005620856","E-Police=
","","04-08-2025 16:07:09","04-08-2025 16:04:03","04-08-2025 17:20:38","Cas=
caded Incident from TTO5815351","","Cascade Outage","Active","Cascade Activ=
e","Cascade Active"," No power issue site on grid with U=3D53.3V, site on g=
rid Mbah osiah(674007438) from Huawei is informed","vanel.mbiada@matech-cam=
eroun.com","273690","04-08-2025 16:07:09","MATECH CMR"
"Closed Complete","Site Down","CTR_323","IHS_YND_043","NOCINC0005620848","E=
mia","IHS_YND_030","04-08-2025 16:06:10","04-08-2025 16:04:03","04-08-2025 =
17:20:38","(Grid outage no space to deploy mobile gen//Grid return)","","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm"," No power issue site on grid with U=3D53.3V, site on grid Mbah osi=
ah(674007438) from Huawei is informed","vanel.mbiada@matech-cameroun.com","=
128","04-08-2025 16:06:10","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005620844","N=
kolbong","","04-08-2025 16:05:23","04-08-2025 16:01:07","04-08-2025 17:57:0=
1","Grid outage, site went down because gen ran untill fuel shortage // Ref=
ueling Done","Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran untill fuel shortage // Re=
fueling Done","vanel.mbiada@matech-cameroun.com","258","04-08-2025 16:05:23=
","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005620775","N=
koabang Ebolmedjock","","04-08-2025 15:53:32","04-08-2025 15:50:15","04-08-=
2025 16:00:35","Site went down because Our Fme Herve Mbah (655999779) was o=
n site doing PM//End of work","Mba Lazare Herve","Installation Activity","P=
assive","Planned Activity","Installation Activity","Site went down because =
Our Fme Herve Mbah (655999779) was on site doing PM//End of work","vanel.mb=
iada@matech-cameroun.com","199","04-08-2025 15:53:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005620733","Angongo"=
,"","04-08-2025 15:46:35","04-08-2025 15:43:51","04-08-2025 16:19:06","Casc=
aded Incident from TTO5815205","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because Our Fme Brice  (65=
9906648) was on site doing PM//End of work","vanel.mbiada@matech-cameroun.c=
om","267381","04-08-2025 15:46:35","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0005620725","E=
beba","IHS_YND_335","04-08-2025 15:46:05","04-08-2025 15:43:51","04-08-2025=
 16:19:06","Site went down because Our Fme Brice  (659906648) was on site d=
oing PM//End of work","Fanda Brice","Installation Activity","Passive","Plan=
ned Activity","Installation Activity","Site went down because Our Fme Brice=
  (659906648) was on site doing PM//End of work","vanel.mbiada@matech-camer=
oun.com","135","04-08-2025 15:46:05","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005620567","N=
koabang2","","04-08-2025 15:22:11","04-08-2025 15:21:02","04-08-2025 17:31:=
14","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed//Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed// Grid return","vanel.mbi=
ada@matech-cameroun.com","71","04-08-2025 15:22:11","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005620546","OTE=
LE MTN","","04-08-2025 15:18:15","04-08-2025 15:16:34","04-08-2025 15:23:14=
","Grid Fluctuation, site went down before Gen start due to poor battery ba=
ckup // Grid restoration","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went down b=
efore Gen start due to poor battery backup // Grid restoration","cedric.tia=
ni@matech-cameroun.com","103","04-08-2025 15:18:15","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005620484","N=
kolso","","04-08-2025 15:09:07","04-08-2025 15:07:56","04-08-2025 15:13:24"=
,"fme repport william Djomo (IHS) is on site for work// End Work","TIENTCHE=
U NZETCHIEU GAEL","Installation Activity","Passive","Planned Activity","Ins=
tallation Activity","fme repport william Djomo (IHS) is on site for work// =
End Work","vanel.mbiada@matech-cameroun.com","72","04-08-2025 15:09:07","MA=
TECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005620481","Nko=
abang Ebolmedjock","","04-08-2025 15:08:42","04-08-2025 15:08:36","04-08-20=
25 15:42:55","Site went down because Our Fme Herve Mbah (655999779) was on =
site doing PM//End of work","Mba Lazare Herve","Installation Activity","Pas=
sive","Planned Activity","Installation Activity","Site went down because Ou=
r Fme Herve Mbah (655999779) was on site doing PM//End of work","cedric.tia=
ni@matech-cameroun.com","7","04-08-2025 15:08:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005620290","Etoudi 2=
","","04-08-2025 14:41:59","04-08-2025 14:35:48","04-08-2025 14:41:07","Cas=
caded Incident from TTO5814709","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
Gen stopped with ""Under frequency"" alarm // He balanced the Load  and sta=
rted Gen manualy","cedric.tiani@matech-cameroun.com","271533","04-08-2025 1=
4:41:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005620289","ETOUDI C=
HAPELLE","","04-08-2025 14:41:58","04-08-2025 14:35:48","04-08-2025 14:41:0=
7","Cascaded Incident from TTO5814709","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
cause Gen stopped with ""Under frequency"" alarm // He balanced the Load  a=
nd started Gen manualy","cedric.tiani@matech-cameroun.com","271534","04-08-=
2025 14:41:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0005620288","Abattoir=
","","04-08-2025 14:41:58","04-08-2025 14:35:48","04-08-2025 14:41:07","Cas=
caded Incident from TTO5814709","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
Gen stopped with ""Under frequency"" alarm // He balanced the Load  and sta=
rted Gen manualy","cedric.tiani@matech-cameroun.com","271533","04-08-2025 1=
4:41:58","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005620280","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","04-08-2025 14:40:58","04-08-2=
025 14:35:48","04-08-2025 14:41:07","Grid Fluctuation, site went down befor=
e Gen start due to poor battery backup // Grid restoration","Fabrice Pouaka=
m","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid Fluctuation, site went down before Gen start due to poor battery b=
ackup // Grid restoration","cedric.tiani@matech-cameroun.com","311","04-08-=
2025 14:40:58","MATECH CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0005620195","O=
kolo","","04-08-2025 14:33:15","04-08-2025 14:32:54","04-08-2025 14:51:06",=
"Grid outage, Site went down because Gen stopped with ""Under frequency"" a=
larm // He balanced the Load  and started Gen manualy","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Under Frequency","Grid outage=
, Site went down because Gen stopped with ""Under frequency"" alarm // He b=
alanced the Load  and started Gen manualy","vanel.mbiada@matech-cameroun.co=
m","22","04-08-2025 14:33:15","MATECH CMR"
"Closed Complete","Site Down","T2222","IHS_YND_697","NOCINC0005620166","Nom=
ayos-IHS","","04-08-2025 14:28:16","04-08-2025 14:23:57","04-08-2025 14:37:=
47","Site went down due to CB( 63A ) disjunction in PWC that feeds MTN//He =
rearmed it","Fanda Brice","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Circuit Breaker Issue","Site went down due to CB( 63A ) disjun=
ction in PWC that feeds MTN//He rearmed it","cedric.tiani@matech-cameroun.c=
om","260","04-08-2025 14:28:16","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005620063","N=
koabang2","","04-08-2025 14:14:32","04-08-2025 14:08:21","04-08-2025 14:20:=
34","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed//Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed//Grid return","loic.noums=
i@matech-cameroun.com","374","04-08-2025 14:14:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0005619987","Anguissa=
 New","","04-08-2025 14:07:47","04-08-2025 14:03:07","04-08-2025 14:33:22",=
"Cascaded Incident from TTO5814390","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","access issues due to the Landloord=
( ALPHOSE DEFFO is informed ),// grid return","edwige.kapawo@matech-camerou=
n.com","273738","04-08-2025 14:07:47","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005619983","L=
abogenie","IHS_YND_568","04-08-2025 14:07:16","04-08-2025 14:03:07","04-08-=
2025 14:33:22","access issues due to the Landloord( ALPHOSE DEFFO is inform=
ed ),// grid return","","Access Denial","Lease Or Legal","Landlord Related =
Issues","Access Issue - Land Lord","access issues due to the Landloord( ALP=
HOSE DEFFO is informed ),// grid return","edwige.kapawo@matech-cameroun.com=
","251","04-08-2025 14:07:16","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005619858","N=
koabang2","","04-08-2025 13:38:56","04-08-2025 13:38:51","04-08-2025 14:01:=
47","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed//Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed//Grid return","loic.noums=
i@matech-cameroun.com","7","04-08-2025 13:38:56","MATECH CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0005619563","S=
apeur","","04-08-2025 12:54:05","04-08-2025 12:52:56","04-08-2025 17:20:28"=
,"Site went down due to Fme Silvin ( 671881683)  from BTR is on site (SWAPP=
 of PWC and GEN)//End of Work","Mboua Thierry","Installation Activity","Pas=
sive","Planned Activity","Installation Activity","Site went down due to Fme=
 Silvin ( 671881683)  from BTR is on site (SWAPP of PWC and GEN)//End of Wo=
rk","edwige.kapawo@matech-cameroun.com","70","04-08-2025 12:54:05","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005619409","Song-bon=
g","","04-08-2025 12:23:55","04-08-2025 12:19:04","04-08-2025 12:39:43","Ca=
scaded Incident from TTO5813744","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work Franklin=
 (657108612/matech) was on site for work (PM) // End of work, Power issue r=
esolved  but remains down Tx FME Etienne (695033981/huawei ) is informed","=
edwige.kapawo@matech-cameroun.com","265547","04-08-2025 12:23:55","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005619400","Eseka To=
wn","","04-08-2025 12:21:47","04-08-2025 12:19:04","04-08-2025 12:39:43","C=
ascaded Incident from TTO5813744","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work Frankli=
n (657108612/matech) was on site for work (PM) // End of work, Power issue =
resolved  but remains down Tx FME Etienne (695033981/huawei ) is informed",=
"edwige.kapawo@matech-cameroun.com","265548","04-08-2025 12:21:47","MATECH =
CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005619395","E=
seka OCM","IHS_YND_378, IHS_YND_453","04-08-2025 12:21:17","04-08-2025 12:1=
9:04","04-08-2025 12:41:43","Site went down due to work Franklin (657108612=
/matech) was on site for work (PM) // End of work, Power issue resolved  bu=
t remains down Tx FME Etienne (695033981/huawei ) is informed","Kemeni Fran=
klin","Equipment Replacement","Passive","Planned Activity","Planned Activit=
y - Passive","Site went down due to work Franklin (657108612/matech) was on=
 site for work (PM) // End of work, Power issue resolved  but remains down =
Tx FME Etienne (695033981/huawei ) is informed","edwige.kapawo@matech-camer=
oun.com","135","04-08-2025 12:21:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005619390","ELOUMDEM=
 CARRIERE 2","","04-08-2025 12:19:41","04-08-2025 12:17:36","04-08-2025 12:=
21:19","Cascaded Incident from TTO5813724","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","edwige.ka=
pawo@matech-cameroun.com","265706","04-08-2025 12:19:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005619389","Eto koss=
 Yde","","04-08-2025 12:19:41","04-08-2025 12:17:36","04-08-2025 12:21:19",=
"Cascaded Incident from TTO5813724","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","edwige.kapawo@ma=
tech-cameroun.com","265706","04-08-2025 12:19:41","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005619369","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","04-08-2025 12:16:45","04-08-2025 12:=
15:36","04-08-2025 12:21:19","Grid outage, Site went down before Gen start =
due to poor backup // Gen started automatically","Fanda Brice","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
, Site went down before Gen start due to poor backup // Gen started automat=
ically","edwige.kapawo@matech-cameroun.com","72","04-08-2025 12:16:45","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0005619285","O=
kolo","","04-08-2025 12:02:57","04-08-2025 12:00:48","04-08-2025 12:10:46",=
"Site went down due to PM (DRAINING of Gen) done by our FME // End of work"=
,"Fabrice Pouakam","Installation Activity","Passive","Planned Activity","In=
stallation Activity","Site went down due to PM (DRAINING of Gen) done by ou=
r FME // End of work","edwige.kapawo@matech-cameroun.com","130","04-08-2025=
 12:02:57","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005619279","N=
koabang2","","04-08-2025 12:01:16","04-08-2025 11:58:08","04-08-2025 12:01:=
06","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed//Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed//Grid return","loic.noums=
i@matech-cameroun.com","191","04-08-2025 12:01:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0005619221","Dagobert=
","","04-08-2025 11:48:46","04-08-2025 11:44:26","04-08-2025 12:39:50","Cas=
caded Incident from TTO5813536","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active//No power issue on site=
 Ubaie:53 V site on GRID. The FME TX Mohamadou (691144435)from Huawei is in=
formed","loic.noumsi@matech-cameroun.com","267723","04-08-2025 11:48:46","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0005619220","Crf-Nkol=
bisson","","04-08-2025 11:48:46","04-08-2025 11:44:26","04-08-2025 12:39:50=
","Cascaded Incident from TTO5813536","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","Active//No power issue o=
n site Ubaie:53 V site on GRID. The FME TX Mohamadou (691144435)from Huawei=
 is informed","loic.noumsi@matech-cameroun.com","267722","04-08-2025 11:48:=
46","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005619210","N=
kolbi-Boss","IHS_YND_232, IHS_YND_286","04-08-2025 11:47:30","04-08-2025 11=
:44:26","04-08-2025 11:50:49","Active//No power issue on site Ubaie:53 V si=
te on GRID. The FME TX Mohamadou (691144435)from Huawei is informed","TIENT=
CHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie:53 V =
site on GRID. The FME TX Mohamadou (691144435)from Huawei is informed","loi=
c.noumsi@matech-cameroun.com","185","04-08-2025 11:47:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005619125","ELOUMDEM=
 CARRIERE 2","","04-08-2025 11:34:11","04-08-2025 11:29:42","04-08-2025 11:=
37:14","Cascaded Incident from TTO5813431","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","edwige.ka=
pawo@matech-cameroun.com","261218","04-08-2025 11:34:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005619124","Eto koss=
 Yde","","04-08-2025 11:34:10","04-08-2025 11:29:42","04-08-2025 11:37:14",=
"Cascaded Incident from TTO5813431","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","edwige.kapawo@ma=
tech-cameroun.com","261217","04-08-2025 11:34:11","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005619108","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","04-08-2025 11:31:54","04-08-2025 11:=
29:42","04-08-2025 11:37:14","Grid outage, Site went down before Gen start =
due to poor backup","Fanda Brice","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Gen started automatically","edwige.kapawo@matech=
-cameroun.com","135","04-08-2025 11:31:54","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005619088","C=
NR","","04-08-2025 11:27:45","04-08-2025 11:23:32","04-08-2025 12:34:33","G=
rid outage, site went down because Gen failed to start due to High temp ala=
rm // He added WATER and started Gen manually","Mboua Thierry","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"Grid outage, site went down because Gen failed to start due to High temp =
alarm // He added WATER and started Gen manually","edwige.kapawo@matech-cam=
eroun.com","254","04-08-2025 11:27:45","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005618991","F=
OUGEROLE","","04-08-2025 11:06:38","04-08-2025 11:04:30","04-08-2025 11:34:=
31","Grid outage site went down due to Gen Overload (20Kva, Iload 300 A )IH=
S SS Alphonse is informed // Reduced charge and left site on gen","Siligap =
Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge site went down due to Gen Overload (20Kva, Iload 300 A )IHS SS Alphonse =
is informed // Reduced charge and left site on gen","edwige.kapawo@matech-c=
ameroun.com","130","04-08-2025 11:06:38","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005618985","E=
toudi","","04-08-2025 11:05:20","04-08-2025 11:04:13","04-08-2025 11:05:39"=
,"Grid Fluctuation, site went down before Gen start due to poor battery bac=
kup // Grid restoration","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went dow=
n before Gen start due to poor battery backup // Grid restoration","edwige.=
kapawo@matech-cameroun.com","69","04-08-2025 11:05:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005618923","Eto koss=
 Yde","","04-08-2025 10:58:23","04-08-2025 10:55:21","04-08-2025 11:00:26",=
"Cascaded Incident from TTO5813209","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","loic.noumsi@mate=
ch-cameroun.com","263318","04-08-2025 10:58:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005618924","ELOUMDEM=
 CARRIERE 2","","04-08-2025 10:58:23","04-08-2025 10:55:21","04-08-2025 11:=
00:26","Cascaded Incident from TTO5813209","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","loic.noum=
si@matech-cameroun.com","263317","04-08-2025 10:58:23","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005618917","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","04-08-2025 10:57:26","04-08-2025 10:55=
:21","04-08-2025 11:00:26","Grid outage, Site went down before Gen start du=
e to poor backup // Gen started automatically","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","loic.noumsi@matech-cameroun.com","128","04-08-2025 10:57:26","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005618908","Nkolfoul=
ou 2","","04-08-2025 10:56:31","04-08-2025 10:52:33","04-08-2025 11:14:51",=
"Cascaded Incident from TTO5813189","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 gen overload 300 A /20 KVA // Gen charge reduced and manual start of gen",=
"loic.noumsi@matech-cameroun.com","238","04-08-2025 10:56:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005618909","Melen Ba=
'aba","","04-08-2025 10:56:31","04-08-2025 10:52:33","04-08-2025 11:14:51",=
"Cascaded Incident from TTO5813189","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 gen overload 300 A /20 KVA // Gen charge reduced and manual start of gen",=
"loic.noumsi@matech-cameroun.com","238","04-08-2025 10:56:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005618910","TSINGA V=
ILLAGE 2","","04-08-2025 10:56:31","04-08-2025 10:52:33","04-08-2025 11:14:=
51","Cascaded Incident from TTO5813189","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to gen overload 300 A /20 KVA // Gen charge reduced and manual start of =
gen","loic.noumsi@matech-cameroun.com","238","04-08-2025 10:56:31","MATECH =
CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005618900","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","04-08-2025 10:54:42","0=
4-08-2025 10:52:33","04-08-2025 11:16:54","Grid outage, site went down due =
to gen overload (300 A /20 KVA) // Gen charge reduced and manual start of g=
en","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Grid outage, site went down due to gen overload 300 A /20 KVA // Gen ch=
arge reduced and manual start of gen","loic.noumsi@matech-cameroun.com","13=
1","04-08-2025 10:54:42","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005618649","C=
NR","","04-08-2025 10:16:42","04-08-2025 10:06:31","04-08-2025 11:15:37","G=
rid outage, site went down because Gen failed to start due to High temp ala=
rm // He added WATER and started Gen manually","Mboua Thierry","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"Grid outage, site went down because Gen failed to start due to High temp =
alarm // He added WATER and started Gen manually","loic.noumsi@matech-camer=
oun.com","612","04-08-2025 10:16:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005618521","ETOUDI C=
HAPELLE","","04-08-2025 09:54:52","04-08-2025 09:50:09","04-08-2025 09:52:5=
5","Cascaded Incident from TTO5812762","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on grid with =
U=3D53.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. Notice=
 that it is a repetitive issue.","loic.noumsi@matech-cameroun.com","267237"=
,"04-08-2025 09:54:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005618522","Etoudi 2=
","","04-08-2025 09:54:52","04-08-2025 09:50:09","04-08-2025 09:52:55","Cas=
caded Incident from TTO5812762","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D53=
.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. Notice that =
it is a repetitive issue.","loic.noumsi@matech-cameroun.com","267238","04-0=
8-2025 09:54:52","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005618518","Aba=
ttoir","IHS_YND_694, IHS_YND_211","04-08-2025 09:54:16","04-08-2025 09:50:0=
9","04-08-2025 09:52:55","No power issue site on grid with U=3D53.1V, TX Fm=
e Armand Nguetsa /699949553 from Huawei is informed. Notice that it is a re=
petitive issue.","Fabrice Pouakam","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D53.1V, TX Fme Armand Nguetsa /699949553 from Huawei is informed. N=
otice that it is a repetitive issue.","loic.noumsi@matech-cameroun.com","24=
8","04-08-2025 09:54:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0005618416","Nkolkoum=
ou OCM","","04-08-2025 09:38:59","04-08-2025 09:35:10","04-08-2025 09:42:52=
","Cascaded Incident from TTO5812637","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down because gen failed to start due to grid bad voltage and no Rcp // He=
 bypassed Grid and started Gen manually","loic.noumsi@matech-cameroun.com",=
"260813","04-08-2025 09:38:59","MATECH CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0005618408","N=
kolbisson usine des eaux","IHS_YND_712","04-08-2025 09:38:23","04-08-2025 0=
9:35:10","04-08-2025 09:42:52","Grid outage, site went down because gen fai=
led to start due to grid bad voltage and no Rcp // He bypassed Grid and sta=
rted Gen manually","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid outage, site went down be=
cause gen failed to start due to grid bad voltage and no Rcp // He bypassed=
 Grid and started Gen manually","loic.noumsi@matech-cameroun.com","194","04=
-08-2025 09:38:23","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005618037","N=
kolso","","04-08-2025 08:36:34","04-08-2025 08:34:17","04-08-2025 08:37:57"=
,"Grid outage, Site went down before Gen start due to poor backup/ // Gen a=
utomatically started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup/ // Gen automatically started","edwi=
ge.kapawo@matech-cameroun.com","138","04-08-2025 08:36:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0005617745","Crf Corn=
ier","","04-08-2025 07:31:17","03-08-2025 18:35:39","04-08-2025 07:55:33","=
Cascaded Incident from TTO5808757","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,no space to deploy MGE =
// Grid returned","kouoh.jean@ihstowers.com","314905","04-08-2025 07:31:17"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005617700","O=
dza","","04-08-2025 07:16:20","04-08-2025 07:14:13","04-08-2025 07:31:28","=
Grid outage, site went down due to Grid bad voltage (lack of 02 phases) // =
He did bridge on good phase, site on Grid","Albran Byorel","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid outage, site=
 went down due to Grid bad voltage (lack of 02 phases) // He did bridge on =
good phase, site on Grid","edwige.kapawo@matech-cameroun.com","128","04-08-=
2025 07:16:20","MATECH CMR"
"Closed Complete","Site Down","CTR_063","IHS_YND_365","NOCINC0005617372","A=
kono","","04-08-2025 05:33:58","04-08-2025 05:06:40","04-08-2025 05:51:48",=
"Grid outage, site went down because gen start and stopped due to low oil p=
ressure // He added oil and manually start the gen","Fanda Brice","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage, site=
 went down because gen start and stopped due to low oil pressure // He adde=
d oil and manually start the gen","gerard.tchangoue@matech-cameroun.com","3=
090","04-08-2025 05:33:58","MATECH CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0005617253","O=
kolo","","04-08-2025 05:05:52","04-08-2025 05:04:45","04-08-2025 06:22:40",=
"Grid outage gen failed to start due to belt cut //we replace belt and gen =
manually started","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Fan Belt","Grid outage gen failed to start due to belt cut //we re=
place belt and gen manually started","gerard.tchangoue@matech-cameroun.com"=
,"68","04-08-2025 05:05:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0005616968","Nkolkoum=
ou OCM","","04-08-2025 03:20:15","04-08-2025 02:57:17","04-08-2025 04:29:37=
","Cascaded Incident from TTO5811025","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down because gen failed to start due to grid bad voltage and no Rcp // He=
 bypassed Grid and started Gen manually","gerard.tchangoue@matech-cameroun.=
com","270404","04-08-2025 03:20:15","MATECH CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0005616957","N=
kolbisson usine des eaux","IHS_YND_712","04-08-2025 03:16:57","04-08-2025 0=
2:57:17","04-08-2025 04:29:37","Grid outage, site went down because gen fai=
led to start due to grid bad voltage and no Rcp // He bypassed Grid and sta=
rted Gen manually","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid outage, site went down be=
cause gen failed to start due to grid bad voltage and no Rcp // He bypassed=
 Grid and started Gen manually","gerard.tchangoue@matech-cameroun.com","118=
1","04-08-2025 03:16:57","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005616672","MBA=
LNGONG LYCEE","","04-08-2025 01:24:37","04-08-2025 01:15:31","04-08-2025 08=
:10:57","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed//Grid return","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//G=
rid return","gerard.tchangoue@matech-cameroun.com","548","04-08-2025 01:24:=
37","MATECH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005616491","N=
omayos-IHS","","04-08-2025 00:30:09","04-08-2025 00:25:02","04-08-2025 04:3=
9:36","Site went down due to insufficient rectifiers on site//Site stabiliz=
ed","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficient rectifiers on site//Site stabilized"=
,"gerard.tchangoue@matech-cameroun.com","309","04-08-2025 00:30:09","MATECH=
 CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005616486","NKO=
NGKARAK","","04-08-2025 00:29:13","04-08-2025 00:25:06","04-08-2025 00:33:5=
3","Grid outage, Site went down because Gen started and stopped due to High=
 temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, Site went down because Gen started and stop=
ped due to High temp alarm //He added water and Gen start manually","gerard=
.tchangoue@matech-cameroun.com","249","04-08-2025 00:29:13","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005616394","B=
arriere","","04-08-2025 00:06:22","03-08-2025 18:46:07","04-08-2025 10:25:5=
3","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed // He reduced load and power reset","Hyemafo Gildas","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site=
 went down because Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed =
// He reduced load and power reset","gerard.tchangoue@matech-cameroun.com",=
"19218","04-08-2025 00:06:22","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005616364","A=
kak-Nkozoa-MTN-IHS","","03-08-2025 23:53:25","03-08-2025 23:46:16","03-08-2=
025 23:52:23","Site impacted by AKAK IHS (CTR_513)","Fabrice Pouakam","Casc=
ade Outage","Active","Cascade Active","Cascade Active","No power issue on s=
ite Ubaie: 54V site on Grid. Symphorien (675295205/ Huawei) is informed .",=
"gerard.tchangoue@matech-cameroun.com","267473","03-08-2025 23:53:25","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005615976","N=
omayos-IHS","","03-08-2025 22:22:14","03-08-2025 22:19:06","03-08-2025 23:1=
7:24","Site went down due to insufficient rectifiers on site//Site stabiliz=
ed	","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site went down due to insufficient rectifiers on site//Site stabilized=
	","vanel.mbiada@matech-cameroun.com","189","03-08-2025 22:22:14","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0005615857","Ndogbess=
ol","","03-08-2025 21:57:02","03-08-2025 21:25:04","03-08-2025 22:30:55","C=
ascaded Incident from TTO5809644","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down due to =
Gen overload(20KVA, 180A) SS IHS Cyril Ngoufou confirm //Gen manaually star=
ted","christian.fonkou@ihstowers.com","268525","03-08-2025 21:57:02","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005615780","Song-bon=
g","","03-08-2025 21:44:10","03-08-2025 21:25:04","03-08-2025 22:30:55","Ca=
scaded Incident from TTO5809644","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down due to G=
en overload(20KVA, 180A) SS IHS Cyril Ngoufou confirm //Gen manaually start=
ed","christian.fonkou@ihstowers.com","268528","03-08-2025 21:44:10","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0005615781","Mamb",""=
,"03-08-2025 21:44:10","03-08-2025 21:25:04","03-08-2025 22:30:55","Cascade=
d Incident from TTO5809644","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage site went down due to Gen ov=
erload(20KVA, 180A) SS IHS Cyril Ngoufou confirm //Gen manaually started","=
christian.fonkou@ihstowers.com","268531","03-08-2025 21:44:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0005615782","Boga-Mah=
ole","","03-08-2025 21:44:10","03-08-2025 21:25:04","03-08-2025 22:30:55","=
Cascaded Incident from TTO5809644","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage site went down due to=
 Gen overload(20KVA, 180A) SS IHS Cyril Ngoufou confirm //Gen manaually sta=
rted","christian.fonkou@ihstowers.com","268524","03-08-2025 21:44:10","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0005615778","Boumnyeb=
el","","03-08-2025 21:44:09","03-08-2025 21:25:04","03-08-2025 22:30:55","C=
ascaded Incident from TTO5809644","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down due to =
Gen overload(20KVA, 180A) SS IHS Cyril Ngoufou confirm //Gen manaually star=
ted","christian.fonkou@ihstowers.com","268527","03-08-2025 21:44:09","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005615776","Eseka To=
wn","","03-08-2025 21:44:09","03-08-2025 21:25:04","03-08-2025 22:30:55","C=
ascaded Incident from TTO5809644","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down due to =
Gen overload(20KVA, 180A) SS IHS Cyril Ngoufou confirm //Gen manaually star=
ted","christian.fonkou@ihstowers.com","268534","03-08-2025 21:44:09","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0005615777","Ngog Map=
ubi","","03-08-2025 21:44:09","03-08-2025 21:25:04","03-08-2025 22:30:55","=
Cascaded Incident from TTO5809644","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage site went down due to=
 Gen overload(20KVA, 180A) SS IHS Cyril Ngoufou confirm //Gen manaually sta=
rted","christian.fonkou@ihstowers.com","268533","03-08-2025 21:44:09","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0005615779","Eseka OC=
M","","03-08-2025 21:44:09","03-08-2025 21:25:04","03-08-2025 22:30:55","Ca=
scaded Incident from TTO5809644","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down due to G=
en overload(20KVA, 180A) SS IHS Cyril Ngoufou confirm //Gen manaually start=
ed","christian.fonkou@ihstowers.com","268532","03-08-2025 21:44:09","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0005615775","Boumnyeb=
el OCM","","03-08-2025 21:44:08","03-08-2025 21:25:04","03-08-2025 22:30:55=
","Cascaded Incident from TTO5809644","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down due=
 to Gen overload(20KVA, 180A) SS IHS Cyril Ngoufou confirm //Gen manaually =
started","christian.fonkou@ihstowers.com","268526","03-08-2025 21:44:08","M=
ATECH CMR"
"Closed Complete","Site Down","T0217","IHS_YND_018","NOCINC0005615713","P&T=
 Building","IHS_YND_026","03-08-2025 21:28:47","03-08-2025 21:09:34","04-08=
-2025 20:02:02","Grid Outage No Space to deploy a MDG, //Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outa=
ge No Space to deploy a MDG, //Grid return","ludivine.ngamaleu@ihstowers.co=
m","1154","03-08-2025 21:28:47","MATECH CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0005615709","ENA=
M","","03-08-2025 21:27:40","03-08-2025 21:09:34","04-08-2025 20:02:02","",=
"","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid Out=
age No Space to deploy a MDG, //Grid return","ludivine.ngamaleu@ihstowers.c=
om","348664","03-08-2025 21:27:40","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005615615","M=
arche Odza","","03-08-2025 21:10:54","03-08-2025 21:09:45","03-08-2025 22:1=
2:10","Grid fluctuation,site went down due to rectifiers dysfunction//Grid =
stabilisation","Albran Byorel","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Grid fluctuation,site went down due to rectifiers dysfunct=
ion//Grid stabilisation","vanel.mbiada@matech-cameroun.com","70","03-08-202=
5 21:10:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0005615037","Nsimalen=
 OCM","","03-08-2025 18:55:32","03-08-2025 18:48:42","03-08-2025 20:00:41",=
"Cascaded Incident from TTO5808829","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because to (2/5)Rec=
tifier dysfunctionning because  //  Rectifiers reseted  , site on Grid","va=
nel.mbiada@matech-cameroun.com","270995","03-08-2025 18:55:32","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0005615007","N=
kolda","IHS_YND_327","03-08-2025 18:49:48","03-08-2025 18:48:42","03-08-202=
5 20:00:41","Site went down because to (2/5)Rectifiers dysfunction  //  Rec=
tifiers reseted  , site on Grid","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Site went down because to (2/=
5)Rectifiers dysfunction  //  Rectifiers reseted  , site on Grid","vanel.mb=
iada@matech-cameroun.com","67","03-08-2025 18:49:48","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005614966","B=
arriere","","03-08-2025 18:40:26","03-08-2025 18:36:19","03-08-2025 18:42:4=
8","No power issue on site Ubay: 53.5V site on Gen .TX Fme Flubert (6542660=
68/Huawei) is informed","Hyemafo Gildas","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 Ubay: 53.5V site on Gen .TX Fme Flubert (654266068/Huawei) is informed","v=
anel.mbiada@matech-cameroun.com","249","03-08-2025 18:40:26","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005614951","S=
apeur Mimboman","","03-08-2025 18:37:48","03-08-2025 18:35:39","04-08-2025 =
07:55:33","Active//No power issue on site Ubaie=3D48.8V and Ubaie2=3D51.8V =
site on Grid. The TX FME Lionel adjep//655 18 48 76// from huawei is inform=
ed","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Active//No power issue on site Ubaie=3D48.8V and Ubaie2=3D51.8V=
 site on Grid. The TX FME Lionel adjep//655 18 48 76// from huawei is infor=
med","vanel.mbiada@matech-cameroun.com","50977","03-08-2025 18:37:48","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_112","NOCINC0005614943","Madison"=
,"IHS_YND_120, IHS_YND_566","03-08-2025 18:35:45","03-08-2025 18:35:39","04=
-08-2025 07:55:33","Grid outage,no space to deploy MGE // Grid returned","M=
FOUAGUEGUE MATHIEU","Grid Supply","Passive","Grid","National Grid - Grid Ou=
tage Issue","Grid outage,no space to deploy MGE // Grid returned","vanel.mb=
iada@matech-cameroun.com","7","03-08-2025 18:35:45","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005614746","Nko=
abang2","","03-08-2025 17:50:12","03-08-2025 17:46:03","03-08-2025 18:20:03=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed//Grid return","Mba Lazare Herve","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen ov=
erload (22KVA, 330A), SS Blaise IHS is informed//Grid return","franck.nkomo=
t@matech-cameroun.com","274","03-08-2025 17:50:12","MATECH CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0005614694","S=
apeur","","03-08-2025 17:36:51","03-08-2025 17:32:34","03-08-2025 19:36:34"=
,"Grid outage, site went down due to gen overload (20 kva,300 A). Site stab=
ilized","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, site went down due to gen overload (20 kva,300 A). Sit=
e stabilized","franck.nkomot@matech-cameroun.com","259","03-08-2025 17:36:5=
1","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_739","NOCINC0005614690","NKOLMESS=
ING rue Manguier","","03-08-2025 17:36:42","03-08-2025 12:59:59","03-08-202=
5 13:45:38","Cascaded Incident from TTO5807012","Siligap Boris","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid outage.gen starte=
d and stopped due to fuel filter flushed//we clean fuel filter and gen manu=
ally started","ludivine.ngamaleu@ihstowers.com","270211","03-08-2025 17:36:=
42","MATECH CMR"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0005614535","COR=
NIERS","","03-08-2025 17:06:55","03-08-2025 16:56:59","03-08-2025 17:44:42"=
,"Grid outage,no space to deploy mobile gen // Grid returned","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no sp=
ace to deploy mobile gen // Grid returned","ludivine.ngamaleu@ihstowers.com=
","1787","03-08-2025 17:06:55","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005614342","Fou=
da Quarter","","03-08-2025 16:31:27","03-08-2025 16:24:15","03-08-2025 16:5=
0:15","Site went down because Gen failed to start due to Grid bad voltage /=
/He bypassed Grid and started Gen manually","Delor Telezing","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Site went down because Gen fai=
led to start due to Grid bad voltage //He bypassed Grid and started Gen man=
ually","franck.nkomot@matech-cameroun.com","432","03-08-2025 16:31:27","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005614162","M=
imboman-Ecole","","03-08-2025 15:56:40","03-08-2025 15:45:18","03-08-2025 1=
7:38:18","Grid outage, site went down because gen ran until fuel shortage /=
/ Refueling done","Mba Lazare Herve","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen ran until=
 fuel shortage // Refueling done","franck.nkomot@matech-cameroun.com","2674=
84","03-08-2025 15:56:40","MATECH CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0005614121","Mim=
boman3","IHS_YND_512","03-08-2025 15:50:25","03-08-2025 15:45:18","03-08-20=
25 17:46:18","Grid outage, site went down because gen ran until fuel shorta=
ge // Refueling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","=
Diesel Outage","Grid outage, site went down because gen ran until fuel shor=
tage // Refueling done","franck.nkomot@matech-cameroun.com","308","03-08-20=
25 15:50:25","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005614110","E=
lig Edzoa","","03-08-2025 15:47:19","03-08-2025 15:39:03","03-08-2025 16:21=
:03","Grid outage gen failed to start due to water infiltration in the tank=
 // We connected a new tank and gen manually started","Delor Telezing","Fue=
l Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The =
Fuel","Grid outage gen failed to start due to water infiltration in the tan=
k // We connected a new tank and gen manually started","franck.nkomot@matec=
h-cameroun.com","498","03-08-2025 15:47:19","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005614028","Hop=
ital Central","","03-08-2025 15:30:20","03-08-2025 15:20:59","04-08-2025 20=
:00:16","Grid outage No Space to deploy a MDG, //Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No Sp=
ace to deploy a MDG, //Grid return","ludivine.ngamaleu@ihstowers.com","8497=
","03-08-2025 15:30:20","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005613871","E=
mombo","","03-08-2025 15:01:59","03-08-2025 14:57:45","03-08-2025 14:59:45"=
,"No power issue, site is on Grid with Ubaie=3D53,8V, TX FME Eloundou (6525=
86578) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue, site is on Grid with Ubaie=3D53,8V, TX FME Eloundou (652586578) from Hu=
awei is informed","franck.nkomot@matech-cameroun.com","254","03-08-2025 15:=
01:59","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005613858","Aba=
ttoir","","03-08-2025 14:58:16","03-08-2025 14:52:00","03-08-2025 15:30:00"=
,"No power issue site on grid with U=3D52.9V, TX fme Armand Nguetsa /699949=
553 from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on grid with U=3D52.9V, TX fme Armand Nguetsa /699949553 from Huawei is=
 informed","ludivine.ngamaleu@ihstowers.com","378","03-08-2025 14:58:16","M=
ATECH CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0005613826","Av =
Kennedy","","03-08-2025 14:50:11","03-08-2025 14:41:58","03-08-2025 17:45:5=
8","Grid outage.no space to deploy mobile gen // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no sp=
ace to deploy mobile gen // Grid return","ludivine.ngamaleu@ihstowers.com",=
"494","03-08-2025 14:50:11","MATECH CMR"
"Closed Complete","Site Down","T0470","IHS_YND_022","NOCINC0005613817","Mvo=
g Ada","","03-08-2025 14:48:30","03-08-2025 14:41:23","03-08-2025 17:49:23"=
,"Grid only site, no space to deploy MGE // Grid returned","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid only site, no s=
pace to deploy MGE // Grid returned","franck.nkomot@matech-cameroun.com","4=
28","03-08-2025 14:48:30","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005613803","ODZ=
A MINKAN EDIBI ASSI","","03-08-2025 14:44:52","03-08-2025 14:34:59","03-08-=
2025 15:36:59","Grid outage,site went down because Gen failed to start due =
toGen overload(12.5 kva //180A )SS HIS Francois is informed//Grid return","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid outage,site went down because Gen failed to start due toGen overload(12=
.5 kva //180A )SS HIS Francois is informed//Grid return","ludivine.ngamaleu=
@ihstowers.com","680","03-08-2025 14:44:52","MATECH CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0005613614","Av-=
Germaine","","03-08-2025 14:04:50","03-08-2025 14:00:43","03-08-2025 17:43:=
43","Grid only site, no space on site to deploy MGE // Grid returned","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only=
 site, no space on site to deploy MGE // Grid returned","cedric.tiani@matec=
h-cameroun.com","247","03-08-2025 14:04:50","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005613613","S=
oa-Sofamac","","03-08-2025 14:04:38","03-08-2025 13:57:21","03-08-2025 14:4=
0:21","Grid Outage Site went down because Gen failed To start due to Alarms=
 Underfrequency//He Manually Started the Gen","Siligap Boris","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Under Frequency","Grid Outage Site went =
down because Gen failed To start due to Alarms Underfrequency//He Manually =
Started the Gen","vanel.mbiada@matech-cameroun.com","438","03-08-2025 14:04=
:38","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005613608","O=
lembe-Terminus","","03-08-2025 14:03:49","03-08-2025 13:57:11","03-08-2025 =
14:36:11","Grid outage, site went down because gen failed to start due to P=
WC ZTE malfunction //He reset it and started the Gen manually","Fabrice Pou=
akam","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, site went down because gen failed to start due to PWC ZTE m=
alfunction //He reset it and started the Gen manually","vanel.mbiada@matech=
-cameroun.com","400","03-08-2025 14:03:49","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005613557","E=
lig Edzoa","","03-08-2025 13:53:45","03-08-2025 13:45:38","03-08-2025 14:44=
:38","Grid outage gen failed to start due to water infiltration in the tank=
 // We connected a new tank and gen manually started","Delor Telezing","Fue=
l Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The =
Fuel","Grid outage gen failed to start due to water infiltration in the tan=
k // We connected a new tank and gen manually started","vanel.mbiada@matech=
-cameroun.com","488","03-08-2025 13:53:45","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005613530","Eto=
udi","","03-08-2025 13:48:57","03-08-2025 13:43:42","03-08-2025 13:51:49","=
Grid outage,site went down due to gen overload(20kva,300 A) SS HIS Bernard =
Atangana is informed // Site stabilised","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage,site went down due t=
o gen overload(20kva,300 A) SS HIS Bernard Atangana is informed // Site sta=
bilised","cedric.tiani@matech-cameroun.com","316","03-08-2025 13:48:57","MA=
TECH CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0005613460","Ess=
os Marche","","03-08-2025 13:28:41","03-08-2025 13:28:34","03-08-2025 18:02=
:34","Grid outage, No MDGE to deploy // Grid return","Delor Telezing","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 No MDGE to deploy // Grid return","cedric.tiani@matech-cameroun.com","8","=
03-08-2025 13:28:41","MATECH CMR"
"Closed Complete","Site Down","T0287","IHS_YND_038","NOCINC0005613451","Sia=
ntou Inferieur","","03-08-2025 13:26:49","03-08-2025 13:23:42","03-08-2025 =
17:05:42","Grid outage, no space to deploy // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spac=
e to deploy // Grid return","cedric.tiani@matech-cameroun.com","188","03-08=
-2025 13:26:49","MATECH CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0005613379","Nko=
lmesseng","IHS_YND_215, IHS_EBO_104, IHS_YND_739, IHS_EBO_011, IHS_YND_361,=
 IHS_EBO_102, IHS_EBO_014, IHS_YND_410, IHS_YND_217, IHS_EBO_024, IHS_SGM_1=
09","03-08-2025 13:09:22","03-08-2025 12:59:59","03-08-2025 13:45:38","Grid=
 outage.gen started and stopped due to fuel filter flushed//we clean fuel f=
ilter and gen manually started","Siligap Boris","Equipment Repair","Passive=
","ACDG Gen","ACDG - Fuel Filter","Grid outage.gen started and stopped due =
to fuel filter flushed//we clean fuel filter and gen manually started","ced=
ric.tiani@matech-cameroun.com","564","03-08-2025 13:09:22","MATECH CMR"
"Closed Complete","Site Down","T1107-1","IHS_YND_217","NOCINC0005613363","A=
bom","","03-08-2025 13:06:44","03-08-2025 12:59:59","03-08-2025 13:45:38","=
","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Grid outage.gen started and stopped due to fuel filter flushed//we c=
lean fuel filter and gen manually started","cedric.tiani@matech-cameroun.co=
m","270207","03-08-2025 13:06:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0005613349","Kondengu=
i","","03-08-2025 13:05:42","03-08-2025 13:01:16","03-08-2025 17:58:16","Ca=
scaded Incident from TTO5806974","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, no space to deploy MGE /=
/ grid power return","vanel.mbiada@matech-cameroun.com","284591","03-08-202=
5 13:05:42","MATECH CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0005613344","E=
mombo-Tchad","IHS_YND_114","03-08-2025 13:04:27","03-08-2025 13:01:16","03-=
08-2025 17:58:16","Grid outage, no space to deploy MGE // grid power return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage, no space to deploy MGE // grid power return","vanel.mbiada@matec=
h-cameroun.com","192","03-08-2025 13:04:27","MATECH CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0005613340","Ele=
veurs","","03-08-2025 13:03:50","03-08-2025 12:59:59","03-08-2025 13:45:38"=
,"","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage.gen started and stopped due to fuel filter flushed//we=
 clean fuel filter and gen manually started","cedric.tiani@matech-cameroun.=
com","270215","03-08-2025 13:03:50","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0005613327","H=
-Paradis","","03-08-2025 13:01:14","03-08-2025 13:00:57","03-08-2025 13:43:=
57","Grid Outage, No space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No space =
to deploy MGE // Grid return","vanel.mbiada@matech-cameroun.com","18","03-0=
8-2025 13:01:14","MATECH CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0005613305","M=
ontee-Anne-Rouge","","03-08-2025 12:57:13","03-08-2025 12:56:02","03-08-202=
5 13:48:37","Grid outage, No space to deploy MDG  // Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
No space to deploy MDG  // Grid return","vanel.mbiada@matech-cameroun.com",=
"72","03-08-2025 12:57:13","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005613278","S=
tade-Abega","","03-08-2025 12:48:33","03-08-2025 12:46:27","03-08-2025 13:4=
5:48","Grid outage, site went down because gen failed to start due to Pwc Z=
TE dysfunction // Grid return","Mba Lazare Herve","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Grid outage, site went down =
because gen failed to start due to Pwc ZTE dysfunction // Grid return","van=
el.mbiada@matech-cameroun.com","127","03-08-2025 12:48:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005613265","MEHANDAN=
","","03-08-2025 12:46:44","03-08-2025 12:40:39","03-08-2025 12:44:55","Cas=
caded Incident from TTO5806881","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Site stabilized","van=
el.mbiada@matech-cameroun.com","264291","03-08-2025 12:46:44","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005613257","O=
dza II OCM","IHS_YND_528","03-08-2025 12:43:49","03-08-2025 12:40:39","03-0=
8-2025 12:44:55","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Site stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Site stabilized","vanel.mbiada@matech-cameroun.com","194","03-08-202=
5 12:43:49","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005613224","E=
lig-Edzoa","","03-08-2025 12:38:46","03-08-2025 12:34:38","03-08-2025 13:41=
:38","Grid only site,No mobile gen available // Grid restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site,N=
o mobile gen available // Grid restored","vanel.mbiada@matech-cameroun.com"=
,"250","03-08-2025 12:38:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_187","NOCINC0005613216","NTEMASSI=
","","03-08-2025 12:37:43","03-08-2025 12:35:08","03-08-2025 15:47:08","Cas=
caded Incident from TTO5806838","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, no access to deploy mobi=
le gen // Grid return","cedric.tiani@matech-cameroun.com","293129","03-08-2=
025 12:37:43","MATECH CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0005613214","Ngo=
usso MTN","IHS_YND_187","03-08-2025 12:37:18","03-08-2025 12:35:08","03-08-=
2025 15:47:08","Grid outage, no access to deploy mobile gen // Grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d outage, no access to deploy mobile gen // Grid return","cedric.tiani@mate=
ch-cameroun.com","131","03-08-2025 12:37:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005613127","Messassi=
 okolo","","03-08-2025 12:18:04","03-08-2025 12:14:09","03-08-2025 13:42:04=
","Cascaded Incident from TTO5806728","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issue . Grid outage, si=
te down because site behaves as Grid only site (Gen Noise)//Grid return","v=
anel.mbiada@matech-cameroun.com","265855","03-08-2025 12:18:04","MATECH CMR=
"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005613124","E=
MANA BILICK CITY","IHS_YND_279","03-08-2025 12:17:26","03-08-2025 12:14:09"=
,"03-08-2025 13:49:09","Access issue . Grid outage, site down because site =
behaves as Grid only site (Gen Noise)//Grid return","Fabrice Pouakam","Acce=
ss Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land =
Lord","Access issue . Grid outage, site down because site behaves as Grid o=
nly site (Gen Noise)//Grid return","vanel.mbiada@matech-cameroun.com","199"=
,"03-08-2025 12:17:26","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005613103","A=
fanoya","","03-08-2025 12:13:48","03-08-2025 12:08:36","03-08-2025 12:27:53=
","No power issue on site , Ubaie=3D54.3V site On Grid The FME TX Samba /65=
5145055/ from Huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site , Ubaie=3D54.3V site On Grid The FME TX Samba /655145055/ from H=
uawei is informed","vanel.mbiada@matech-cameroun.com","313","03-08-2025 12:=
13:48","MATECH CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0005613059","M=
adison","","03-08-2025 12:05:19","03-08-2025 11:58:04","03-08-2025 18:05:58=
","Grid outage,no space to deploy MGE // Grid returned","MFOUAGUEGUE MATHIE=
U","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage,no space to deploy MGE // Grid returned","vanel.mbiada@matech-camer=
oun.com","437","03-08-2025 12:05:19","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005612979","E=
lig Edzoa","","03-08-2025 11:54:03","03-08-2025 11:50:51","03-08-2025 12:14=
:07","Grid outage gen failed to start due to water infiltration in the tank=
 // We connected a new tank and gen manually started","Delor Telezing","Fue=
l Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The =
Fuel","Grid outage gen failed to start due to water infiltration in the tan=
k // We connected a new tank and gen manually started","vanel.mbiada@matech=
-cameroun.com","193","03-08-2025 11:54:03","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005612965","Evo=
doula MTN","","03-08-2025 11:50:43","03-08-2025 11:45:33","03-08-2025 11:55=
:17","Site went down due to work of our Fme Gael on site doing PM//End of w=
ork","TIENTCHEU NZETCHIEU GAEL","Installation Activity","Passive","Planned =
Activity","Installation Activity","Site went down due to work of our Fme Ga=
el on site doing PM//End of work","cedric.tiani@matech-cameroun.com","311",=
"03-08-2025 11:50:43","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005612961","O=
lembe-Terminus","","03-08-2025 11:50:02","03-08-2025 11:45:54","03-08-2025 =
12:44:19","Grid outage, site went down because gen failed to start due to P=
WC ZTE malfunction //He reset it and started the Gen manually","Fabrice Pou=
akam","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, site went down because gen failed to start due to PWC ZTE m=
alfunction //He reset it and started the Gen manually","vanel.mbiada@matech=
-cameroun.com","250","03-08-2025 11:50:02","MATECH CMR"
"Closed Complete","Site Down","CTR_068","IHS_YND_109","NOCINC0005612936","M=
obil-Essos","","03-08-2025 11:43:29","03-08-2025 11:41:20","04-08-2025 08:0=
5:41","(ACCESS ISSUE due to Landlord) Grid outage, Site went down because G=
en failed to start due to undervoltage Alarm // He reset and started Gen ma=
nualy","Siligap Boris","Access Denial","Lease Or Legal","Landlord Related I=
ssues","Access Issue - Land Lord","(ACCESS ISSUE due to Landlord) Grid outa=
ge, Site went down because Gen failed to start due to ATS disfunction// He =
reset ATS and started Gen manualy","vanel.mbiada@matech-cameroun.com","130"=
,"03-08-2025 11:43:29","MATECH CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0005612929","E=
toudi 2","","03-08-2025 11:42:20","03-08-2025 11:37:39","03-08-2025 11:38:4=
4","Active//No power issue, site is on Grid with Ubaie=3D53,7V The Tx FME A=
rmand Nguetsa / 691144412/ from Huawei is informed","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue, site is on Grid with Ubaie=3D53,7V The Tx FM=
E Armand Nguetsa / 691144412/ from Huawei is informed","vanel.mbiada@matech=
-cameroun.com","282","03-08-2025 11:42:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005612918","SOA VILL=
AGE","","03-08-2025 11:38:20","03-08-2025 11:36:34","03-08-2025 12:13:35","=
Cascaded Incident from TTO5806494","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen failed to start due to battery Gen faulty// He started Gen with extern=
al battery","cedric.tiani@matech-cameroun.com","268088","03-08-2025 11:38:2=
0","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005612913","SOA=
 TOWN","IHS_YND_323","03-08-2025 11:37:43","03-08-2025 11:34:56","03-08-202=
5 12:13:56","Grid outage, Site went down because Gen failed to start due to=
 battery Gen faulty// He started Gen with external battery","Siligap Boris"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid o=
utage, Site went down because Gen failed to start due to battery Gen faulty=
// He started Gen with external battery","cedric.tiani@matech-cameroun.com"=
,"3300","03-08-2025 11:37:43","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005612909","E=
mana Lycee","","03-08-2025 11:37:15","03-08-2025 11:32:06","03-08-2025 12:2=
3:15","Site went down because Gen started and stopped with ""low oil pressu=
re"" alarm// He added oil and started Gen manualy","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down=
 because Gen started and stopped with ""low oil pressure"" alarm// He added=
 oil and started Gen manualy","vanel.mbiada@matech-cameroun.com","311","03-=
08-2025 11:37:15","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005612906","C=
rf Cornier","","03-08-2025 11:34:42","03-08-2025 11:32:11","03-08-2025 11:4=
5:38","ACTIVE //No power issue Ubaie: 54.6V site on Grid Armand NGUETSA // =
699949553// from huawei is informed,","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE //=
No power issue Ubaie: 54.6V site on Grid Armand NGUETSA // 699949553// from=
 huawei is informed,","vanel.mbiada@matech-cameroun.com","152","03-08-2025 =
11:34:42","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005612875","M=
vog-Manga","","03-08-2025 11:22:16","03-08-2025 11:19:54","03-08-2025 12:07=
:54","Site went down because Gen overload(22kva,380A) IHS SS Pascaline is i=
nformed//He reduiced the load an site on Gen","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Site went down because Gen ov=
erload(22kva,380A) IHS SS Pascaline is informed//He reduiced the load an si=
te on Gen","vanel.mbiada@matech-cameroun.com","145","03-08-2025 11:22:16","=
MATECH CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0005612860","BEA=
TITUDE ENTR=C9E PAVE","","03-08-2025 11:17:19","03-08-2025 11:14:11","03-08=
-2025 14:36:11","Grid outage, site went down because Gen started and stoppe=
d due to Ge Battery faulty // He started Gen with an external battery","TIE=
NTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Battery","Grid outage, site went down because Gen started and stopped=
 due to Ge Battery faulty // He started Gen with an external battery","cedr=
ic.tiani@matech-cameroun.com","189","03-08-2025 11:17:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0005612843","MONTEE N=
KONDENGUI","","03-08-2025 11:14:43","03-08-2025 11:09:13","04-08-2025 00:28=
:02","Cascaded Incident from TTO5806403","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid only site, no space to d=
eploy MDG // grid returned","vanel.mbiada@matech-cameroun.com","327285","03=
-08-2025 11:14:43","MATECH CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0005612836","M=
obil-Kondengui","IHS_YND_682","03-08-2025 11:13:38","03-08-2025 11:09:13","=
04-08-2025 00:28:02","Grid only site, no space to deploy MDG // grid return=
ed","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid only site, no space to deploy MDG // grid returned","vanel.mbiada@mate=
ch-cameroun.com","266","03-08-2025 11:13:38","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005612771","M=
imboman-Ecole","","03-08-2025 10:54:03","03-08-2025 10:48:51","03-08-2025 1=
2:18:50","Grid outage, site went down because Gen started and stopped due t=
o Ge Battery faulty // He started Gen with an external battery","Mba Lazare=
 Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery",=
"Grid outage, site went down because Gen started and stopped due to Ge Batt=
ery faulty // He started Gen with an external battery","vanel.mbiada@matech=
-cameroun.com","313","03-08-2025 10:54:03","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0005612753","Mes=
sassi Ngonlonk","","03-08-2025 10:50:07","03-08-2025 10:47:01","03-08-2025 =
11:59:37","Site went down because Gen  failed to start due to CB(125A) that=
 tripped Gen Battery   //He rearmed it  and started the Gen manually","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker",=
"Site went down because Gen  failed to start due to CB(125A) that tripped G=
en Battery   //He rearmed it  and started the Gen manually","cedric.tiani@m=
atech-cameroun.com","187","03-08-2025 10:50:07","MATECH CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0005612710","Sap=
eur Mimboman","","03-08-2025 10:40:59","03-08-2025 10:37:45","03-08-2025 18=
:00:45","Grid outage, site went down due to gen overload(22 kva,318 A) // G=
rid return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage, site went down due to gen overload(22 kva,318 A=
) // Grid return","cedric.tiani@matech-cameroun.com","195","03-08-2025 10:4=
0:59","MATECH CMR"
"Closed Complete","Site Down","CTR_546","IHS_YND_419","NOCINC0005612704","N=
gog Mapubi","","03-08-2025 10:39:36","03-08-2025 10:39:19","03-08-2025 10:4=
4:25","Active// No power issue on site ,site on Grid with Ubaie=3D 54,8V Th=
e fme TX Etienne fopa // 695033981// of huawei is informed.","Kemeni Frankl=
in","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// No power issue on site ,site on Grid with Ubaie=3D=
 54,8V The fme TX Etienne fopa // 695033981// of huawei is informed.","vane=
l.mbiada@matech-cameroun.com","18","03-08-2025 10:39:36","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0005612690","Mes=
sassi Ngonlonk","","03-08-2025 10:37:24","03-08-2025 10:35:13","03-08-2025 =
10:37:59","Grid outage site went down because Gen failed to start due to Ge=
n card dysfuntion // He reset it and Gen Manually Started","Fabrice Pouakam=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge site went down because Gen failed to start due to Gen card dysfuntion //=
 He reset it and Gen Manually Started","cedric.tiani@matech-cameroun.com","=
132","03-08-2025 10:37:24","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005612678","O=
dza","","03-08-2025 10:32:27","03-08-2025 10:30:17","03-08-2025 11:50:56","=
Grid outage, Site went down because Gen started and stopped with ""low oil =
pressure"" alarm// He reset card GE and gen manually started","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, Site went down because Gen started and stopped with ""low oil pressure=
"" alarm// He reset card GE and gen manually started","vanel.mbiada@matech-=
cameroun.com","131","03-08-2025 10:32:27","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0005612628","H=
-General-Yde","","03-08-2025 10:25:37","03-08-2025 10:21:26","03-08-2025 10=
:53:06","Grid outage, Site went down because Gen failed to start due to ATS=
 faulty // He bypassed ATS and started Gen manually","Siligap Boris","Equip=
ment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site w=
ent down because Gen failed to start due to ATS faulty // He bypassed ATS a=
nd started Gen manually","vanel.mbiada@matech-cameroun.com","252","03-08-20=
25 10:25:37","MATECH CMR"
"Closed Complete","Site Down","T1431","IHS_YND_561","NOCINC0005612503","FOU=
GEROLE","","03-08-2025 09:55:37","03-08-2025 09:53:29","03-08-2025 10:17:50=
","Grid outage, site went down because gen start and stopped due to alarm""=
high temp"" due to Gen OVERLOAD//We added water and gen manually started","=
Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine =
Temp - Coolant Level Issue","Grid outage, site went down because gen start =
and stopped due to alarm""high temp"" due to Gen OVERLOAD//We added water a=
nd gen manually started","cedric.tiani@matech-cameroun.com","129","03-08-20=
25 09:55:37","MATECH CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0005612499","Eko=
unou","","03-08-2025 09:54:40","03-08-2025 09:53:31","03-08-2025 11:47:05",=
"Grid outage, site went down because gen failed to ATS dysfunctionning // H=
e reset it and gen manually started","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","Grid outage, site went down because=
 gen failed to ATS dysfunctionning // He reset it and gen manually started"=
,"cedric.tiani@matech-cameroun.com","71","03-08-2025 09:54:40","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005612494","M=
vog-Ebanda","","03-08-2025 09:53:48","03-08-2025 09:52:52","03-08-2025 10:0=
5:29","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, Site went down because Gen failed to start due t=
o Gen Overload (16KVA /300A) //He reduiced the load and manually started th=
e Gen","vanel.mbiada@matech-cameroun.com","266956","03-08-2025 09:53:48","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005612488","A=
bom","IHS_YND_269","03-08-2025 09:53:08","03-08-2025 09:52:52","03-08-2025 =
10:05:29","Grid outage, Site went down because Gen failed to start due to G=
en Overload (16KVA /300A) //He reduiced the load and manually started the G=
en","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Grid outage, Site went down because Gen failed to start due to Gen Over=
load (16KVA /300A) //He reduiced the load and manually started the Gen","va=
nel.mbiada@matech-cameroun.com","17","03-08-2025 09:53:08","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0005612471","N=
kolo II New","","03-08-2025 09:51:26","03-08-2025 09:46:50","03-08-2025 10:=
01:59","Grid outage, site went down because Gen started and stopped due to =
Ge Battery faulty // He started Gen with an external battery","Mba Lazare H=
erve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","G=
rid outage, site went down because Gen started and stopped due to Ge Batter=
y faulty // He started Gen with an external battery","vanel.mbiada@matech-c=
ameroun.com","278","03-08-2025 09:51:26","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005612469","Eko=
umdoum OCM","","03-08-2025 09:50:48","03-08-2025 09:48:34","03-08-2025 10:3=
0:19","Grid outage, site went down because Gen failed to start due to ''unk=
now '' alarm // He reset  DG card  and Gen manually started","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge, site went down because Gen failed to start due to ''unknow '' alarm // =
He reset  DG card  and Gen manually started","cedric.tiani@matech-cameroun.=
com","135","03-08-2025 09:50:48","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0005612441","Mes=
sassi Ngonlonk","","03-08-2025 09:43:50","03-08-2025 09:41:58","03-08-2025 =
10:25:00","Grid outage site went down because Gen failed to start due to Ge=
n card dysfuntion // He reset it and Gen Manually Started","Fabrice Pouakam=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge site went down because Gen failed to start due to Gen card dysfuntion //=
 He reset it and Gen Manually Started","cedric.tiani@matech-cameroun.com","=
113","03-08-2025 09:43:50","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005612414","Mim=
boman","","03-08-2025 09:37:17","03-08-2025 09:35:01","03-08-2025 10:33:24"=
,"Site went down due to Gen overload (120A, 12kva) and indoor site // He re=
duced load, site on Gen","Mba Lazare Herve","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Site went down due to Gen overload (120A, 12kva=
) and indoor site // He reduced load, site on Gen","cedric.tiani@matech-cam=
eroun.com","137","03-08-2025 09:37:17","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005612413","E=
mombo","","03-08-2025 09:37:04","03-08-2025 09:34:56","03-08-2025 10:52:19"=
,"Grid outage, Site went down due to 03/05 rectifiers malfunctioning on sit=
e // He reset rectifiers, Site on Grid","Mba Lazare Herve","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Grid outage, Site went down du=
e to 03/05 rectifiers malfunctioning on site // He reset rectifiers, Site o=
n Grid","vanel.mbiada@matech-cameroun.com","128","03-08-2025 09:37:04","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005612370","N=
taba","IHS_YND_133","03-08-2025 09:25:05","03-08-2025 09:19:56","03-08-2025=
 10:05:26","Grid outage, site went down because gen failed to start due to =
Pwc ZTE dysfunction // He reset and manual start of Gen","Delor Telezing","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage, site went down because gen failed to start due to Pwc ZTE dysfunct=
ion // He reset and manual start of Gen","vanel.mbiada@matech-cameroun.com"=
,"310","03-08-2025 09:25:05","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0005612368","Tsi=
nga village","","03-08-2025 09:24:28","03-08-2025 09:23:06","03-08-2025 10:=
59:12","Grid outage, site went down because Gen failed to start due to batt=
ery charger faulty // Gen manually started with external battery","Delor Te=
lezing","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator=
","Grid outage, site went down because Gen failed to start due to battery c=
harger faulty // Gen manually started with external battery","cedric.tiani@=
matech-cameroun.com","83","03-08-2025 09:24:28","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005612328","M=
vog-Ada_OCM","","03-08-2025 09:13:02","03-08-2025 09:08:52","03-08-2025 17:=
47:16","Grid only on site, No space on site to deploy MDGE  // Grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d only on site, No space on site to deploy MDGE  // Grid return","vanel.mbi=
ada@matech-cameroun.com","251","03-08-2025 09:13:02","MATECH CMR"
"Cancelled","Warning","T1742","IHS_YND_042","NOCINC0005612329","Mvog-Ada_OC=
M","","03-08-2025 09:13:02","","","Grid only on site, No space on site to d=
eploy MDGE awaiting Grid return","","","","","","","cedric.tiani@matech-cam=
eroun.com","189","03-08-2025 09:13:02","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005612322","E=
lig-Edzoa","","03-08-2025 09:10:43","03-08-2025 09:19:56","03-08-2025 10:00=
:33","Grid only site,No mobile gen available ","","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen failed to start due to Pwc ZTE dysfunction // He reset and manual start=
 of Gen","vanel.mbiada@matech-cameroun.com","341268","03-08-2025 09:10:43",=
"MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005612321","Tou=
ring Club International","","03-08-2025 09:10:11","03-08-2025 09:03:02","03=
-08-2025 09:19:30","Grid outage,site went down because Gen failed to start =
due to Alarm *Under voltage*//He reset the Gen card and manually started Ge=
n","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid outage,site went down because Gen failed to start due to Alarm=
 *Under voltage*//He reset the Gen card and manually started Gen","cedric.t=
iani@matech-cameroun.com","430","03-08-2025 09:10:11","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005612318","N=
taba","","03-08-2025 09:08:44","03-08-2025 09:05:33","03-08-2025 09:15:27",=
"Grid outage, site went down because gen failed to start due to Pwc ZTE dys=
function // He reset and manual start of Gen","Delor Telezing","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, si=
te went down because gen failed to start due to Pwc ZTE dysfunction // He r=
eset and manual start of Gen","vanel.mbiada@matech-cameroun.com","193","03-=
08-2025 09:08:44","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005612299","Lad=
a I Yde","","03-08-2025 09:03:43","03-08-2025 08:57:33","03-08-2025 09:24:5=
6","Grid outage, site went down due to gen Overload(09KVA, 105A) // He redu=
iced The load and Manually Started the Gen","Mba Lazare Herve","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down =
due to gen Overload(09KVA, 105A) // He reduiced The load and Manually Start=
ed the Gen","cedric.tiani@matech-cameroun.com","372","03-08-2025 09:03:43",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005612290","Mom","",=
"03-08-2025 09:02:36","03-08-2025 08:57:21","03-08-2025 09:10:35","Cascaded=
 Incident from TTO5805787","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by IHS=
","cedric.tiani@matech-cameroun.com","263270","03-08-2025 09:02:36","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005612287","OLAMA","=
","03-08-2025 09:02:35","03-08-2025 08:57:21","03-08-2025 09:10:35","Cascad=
ed Incident from TTO5805787","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by I=
HS","cedric.tiani@matech-cameroun.com","263269","03-08-2025 09:02:35","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005612289","Minka","=
","03-08-2025 09:02:35","03-08-2025 08:57:21","03-08-2025 09:10:35","Cascad=
ed Incident from TTO5805787","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by I=
HS","cedric.tiani@matech-cameroun.com","263268","03-08-2025 09:02:35","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005612288","OTELE MT=
N","","03-08-2025 09:02:35","03-08-2025 08:57:21","03-08-2025 09:10:35","Ca=
scaded Incident from TTO5805787","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by T0169 Ngoumou not manage =
by IHS","cedric.tiani@matech-cameroun.com","263268","03-08-2025 09:02:35","=
MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005612281","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","03-08-2025 09:01:=
31","03-08-2025 08:57:21","03-08-2025 09:10:35","Site impacted by T0169 Ngo=
umou not manage by IHS","Fanda Brice","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Site impacted by T0169 Ng=
oumou not manage by IHS","cedric.tiani@matech-cameroun.com","251","03-08-20=
25 09:01:31","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0005612277","C=
rf-Nkolbisson","","03-08-2025 09:00:08","03-08-2025 08:57:04","03-08-2025 0=
9:01:31","Active// No power issue, site is on grid with Ubaie=3D55,4 V, Moh=
amadou(691144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue, site is on grid with Ubaie=3D55,4 V, Mohama=
dou(691144435) from Huawei is informed","vanel.mbiada@matech-cameroun.com",=
"186","03-08-2025 09:00:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0005612164","Tradex-N=
komo","","03-08-2025 08:39:35","03-08-2025 08:33:36","03-08-2025 09:21:06",=
"Cascaded Incident from TTO5805651","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen failed to start due to battery Gen faulty// He started Gen with exter=
nal battery","cedric.tiani@matech-cameroun.com","264795","03-08-2025 08:39:=
35","MATECH CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0005612157","Nko=
mo II","IHS_YND_172, IHS_YND_173","03-08-2025 08:37:44","03-08-2025 08:33:3=
6","03-08-2025 09:21:06","Grid outage, Site went down because Gen failed to=
 start due to battery Gen faulty// He started Gen with external battery","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Bat=
tery","Grid outage, Site went down because Gen failed to start due to batte=
ry Gen faulty// He started Gen with external battery","cedric.tiani@matech-=
cameroun.com","248","03-08-2025 08:37:44","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0005612150","AWA=
E OCM","","03-08-2025 08:35:39","03-08-2025 08:33:36","03-08-2025 09:21:06"=
,"","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid outage, Site went down because Gen failed to start due to =
battery Gen faulty// He started Gen with external battery","vanel.mbiada@ma=
tech-cameroun.com","264795","03-08-2025 08:35:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005612149","Mvog-Eba=
nda","","03-08-2025 08:34:26","03-08-2025 08:31:05","03-08-2025 09:34:52","=
Cascaded Incident from TTO5805624","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen failed to start due to Gen Overload (16KVA /220A) Blaise Raoul confirm=
ed // He reduced load and site on Gen","vanel.mbiada@matech-cameroun.com","=
271748","03-08-2025 08:34:26","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005612131","A=
bom","IHS_YND_269","03-08-2025 08:32:11","03-08-2025 08:31:05","03-08-2025 =
09:34:52","Grid outage, Site went down because Gen failed to start due to G=
en Overload (16KVA /220A) Blaise Raoul confirmed // He reduced load and sit=
e on Gen","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen failed to start due to Ge=
n Overload (16KVA /220A) Blaise Raoul confirmed // He reduced load and site=
 on Gen","vanel.mbiada@matech-cameroun.com","67","03-08-2025 08:32:11","MAT=
ECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0005612065","HOP=
ITAL GENERAL RAIL YDE","","03-08-2025 08:17:36","03-08-2025 08:14:56","03-0=
8-2025 09:56:01","","Delor Telezing","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen failed to=
 start due to gen card faulty // Gen started manually","cedric.tiani@matech=
-cameroun.com","273085","03-08-2025 08:17:36","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005612061","Pha=
rmacie Bleue","IHS_YND_801","03-08-2025 08:17:08","03-08-2025 08:14:56","03=
-08-2025 09:56:01","Grid outage, site went down because gen failed to start=
 due to gen card faulty // Gen started manually","Siligap Boris","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site wen=
t down because gen failed to start due to gen card faulty // Gen started ma=
nually","cedric.tiani@matech-cameroun.com","133","03-08-2025 08:17:08","MAT=
ECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005612046","Mam=
ch Building","","03-08-2025 08:10:22","03-08-2025 08:09:10","03-08-2025 09:=
01:28","Grid fluctuation, Site went down because gen fails to start due to =
grid bad voltage,no rcp// He bypasse the Grid and site on Gen","Mboua Thier=
ry","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, Site went down because gen fails to start due to grid =
bad voltage,no rcp// He bypasse the Grid and site on Gen","cedric.tiani@mat=
ech-cameroun.com","73","03-08-2025 08:10:22","MATECH CMR"
"Closed Complete","Site Down","T1622","IHS_YND_186","NOCINC0005612043","Ngo=
usso Carrefour","","03-08-2025 08:08:04","03-08-2025 08:04:53","03-08-2025 =
10:34:13","Grid  outage, site Down due to Gen Overloadd(20KVA, 280A)//Grid =
return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid  outage, site Down due to Gen Overloadd(20KVA, 280A)//Grid ret=
urn","cedric.tiani@matech-cameroun.com","191","03-08-2025 08:08:04","MATECH=
 CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005612039","Aka=
k-Nkozoa-MTN-IHS","","03-08-2025 08:07:34","03-08-2025 07:59:23","03-08-202=
5 09:04:03","Grid outage, Site went down because Gen start and stopped with=
 ""High temps ""alarm // he added water and manually start the Gen","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp=
 - Coolant Level Issue","Grid outage, Site went down because Gen start and =
stopped with ""High temps ""alarm // he added water and manually start the =
Gen","cedric.tiani@matech-cameroun.com","493","03-08-2025 08:07:34","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0005612021","N=
gousso-II","","03-08-2025 08:06:29","03-08-2025 08:04:21","03-08-2025 10:29=
:49","Access issue due to landlord//Site went down due to GEN overload (20 =
KVA, 300A) // He reduced load, site on GEN","MFOUAGUEGUE MATHIEU","Access D=
enial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord=
","Access issue due to landlord//Site went down due to GEN overload (20 KVA=
, 300A) // He reduced load, site on GEN","vanel.mbiada@matech-cameroun.com"=
,"129","03-08-2025 08:06:29","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005611945","N=
koabang2","","03-08-2025 07:49:53","03-08-2025 07:47:41","03-08-2025 08:36:=
06","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed//Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed//Grid return","vanel.mbia=
da@matech-cameroun.com","134","03-08-2025 07:49:53","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005611924","Tou=
ring Club International","","03-08-2025 07:44:24","03-08-2025 07:43:16","03=
-08-2025 08:27:00","Grid outage,site went down because Gen failed to start =
due to Alarm *Under voltage*//He reset the Gen card and manually started Ge=
n","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid outage,site went down because Gen failed to start due to Alarm=
 *Under voltage*//He reset the Gen card and manually started Gen","cedric.t=
iani@matech-cameroun.com","69","03-08-2025 07:44:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0005611918","Garbati =
building","","03-08-2025 07:43:20","03-08-2025 07:41:50","03-08-2025 07:43:=
55","Cascaded Incident from TTO5805399","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down be=
fore Gen started due to poor battery back up // GEN automatically starte	",=
"cedric.tiani@matech-cameroun.com","260684","03-08-2025 07:43:20","MATECH C=
MR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005611917","HOP=
ITAL DE LA CAISSE","IHS_YND_024","03-08-2025 07:42:58","03-08-2025 07:41:50=
","03-08-2025 07:43:55","Grid outage site went down before Gen started due =
to poor battery back up // GEN automatically starte	","Delor Telezing","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage site went down before Gen started due to poor battery back up // G=
EN automatically starte	","cedric.tiani@matech-cameroun.com","68","03-08-20=
25 07:42:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0005611912","Abattoir=
","","03-08-2025 07:41:33","03-08-2025 07:33:56","03-08-2025 07:41:02","Cas=
caded Incident from TTO5805373","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,site went down due to ge=
n overload(20kva,300 A) SS HIS Bernard Atangana is informed // Site stabili=
sed","cedric.tiani@matech-cameroun.com","304238","03-08-2025 07:41:33","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005611913","ETOUDI C=
HAPELLE","","03-08-2025 07:41:33","03-08-2025 07:33:56","03-08-2025 07:41:0=
2","Cascaded Incident from TTO5805373","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,site went down due=
 to gen overload(20kva,300 A) SS HIS Bernard Atangana is informed // Site s=
tabilised","cedric.tiani@matech-cameroun.com","304237","03-08-2025 07:41:33=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005611914","Etoudi 2=
","","03-08-2025 07:41:33","03-08-2025 07:33:56","03-08-2025 07:41:02","Cas=
caded Incident from TTO5805373","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,site went down due to ge=
n overload(20kva,300 A) SS HIS Bernard Atangana is informed // Site stabili=
sed","cedric.tiani@matech-cameroun.com","304237","03-08-2025 07:41:33","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005611910","S=
atcom","","03-08-2025 07:41:23","03-08-2025 07:39:13","03-08-2025 08:11:49"=
,"No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand ngu=
etsa(691144412) From huawei is informed.","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand nguetsa(6=
91144412) From huawei is informed.","vanel.mbiada@matech-cameroun.com","131=
","03-08-2025 07:41:23","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005611890","Ngo=
usso Vallee","","03-08-2025 07:37:51","03-08-2025 07:36:42","03-08-2025 07:=
38:36","Grid outage, Site went down before Gen start due to poor backup// G=
rid retrn","Siligap Boris","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup// Grid retrn","cedric.tiani@matech-cameroun.com","70","03-=
08-2025 07:37:51","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005611889","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","03-08-2025 07:37:07","03-08-2=
025 07:33:56","03-08-2025 07:41:02","Grid outage,site went down due to gen =
overload(20kva,300 A) SS HIS Bernard Atangana is informed // Site stabilise=
d","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overlo=
ad","Grid outage,site went down due to gen overload(20kva,300 A) SS HIS Ber=
nard Atangana is informed // Site stabilised","cedric.tiani@matech-cameroun=
.com","192","03-08-2025 07:37:07","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005611886","ODZ=
A BORNE 10","","03-08-2025 07:36:11","03-08-2025 07:30:00","03-08-2025 13:0=
4:35","Grid outage, Site went down due to Gen overload (12.5 kva, 180A)//Gr=
id return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, Site went down due to Gen overload (12.5 kva, 180A)=
//Grid return","cedric.tiani@matech-cameroun.com","372","03-08-2025 07:36:1=
1","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005611855","ODZ=
A MINKAN EDIBI ASSI","","03-08-2025 07:24:37","03-08-2025 07:22:28","03-08-=
2025 12:43:30","Grid outage,site went down because Gen failed to start due =
toGen overload(12.5 kva //180A )SS HIS Francois is informed//Grid return","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid outage,site went down because Gen failed to start due toGen overload(12=
.5 kva //180A )SS HIS Francois is informed//Grid return","cedric.tiani@mate=
ch-cameroun.com","131","03-08-2025 07:24:37","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005611366","ODZ=
A BORNE 10","","03-08-2025 04:34:08","03-08-2025 04:32:59","03-08-2025 07:1=
6:32","Grid outage, Site went down due to Gen overload (12.5 kva, 180A)//Gr=
id return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, Site went down due to Gen overload (12.5 kva, 180A)=
//Grid return","franck.nkomot@matech-cameroun.com","70","03-08-2025 04:34:0=
8","MATECH CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0005611353","Ele=
veurs","","03-08-2025 04:25:45","03-08-2025 04:21:39","03-08-2025 06:23:39"=
,"Grid outage.gen failed to start due alrm ""low oil pressure""// He reset =
card GE and gen manually started","Siligap Boris","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to start due =
alrm ""low oil pressure""//He reset card GE and gen manually started","fran=
ck.nkomot@matech-cameroun.com","247","03-08-2025 04:25:45","MATECH CMR"
"Closed Complete","Site Down","T1622","IHS_YND_186","NOCINC0005611120","Ngo=
usso Carrefour","","03-08-2025 02:33:23","03-08-2025 02:18:16","03-08-2025 =
06:34:16","Eneo outage, site Down due to Gen Overloadd(20KVA, 280A) // Eneo=
 return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Eneo outage, site Down due to Gen Overloadd(20KVA, 280A) // Eneo r=
eturn","franck.nkomot@matech-cameroun.com","908","03-08-2025 02:33:23","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005611115","O=
dza","","03-08-2025 02:32:08","03-08-2025 02:29:50","03-08-2025 02:46:50","=
Grid fluctuation, Site went down because Gen failed to start due to Grid ba=
d voltage // he bypassed the Grid and site on Gen","Albran Byorel","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation, Site went down because Gen failed to start due to Grid bad voltage=
 // he bypassed the Grid and site on Gen","gerard.tchangoue@matech-cameroun=
.com","139","03-08-2025 02:32:08","MATECH CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0005611097","N=
gousso-II","","03-08-2025 02:23:15","03-08-2025 02:18:06","03-08-2025 06:30=
:44","Access issue during the night due to landlord//Site went down due to =
GEN overload (20 KVA, 300A) // He reduced load, site on GEN","MFOUAGUEGUE M=
ATHIEU","Access Denial","Lease Or Legal","Landlord Related Issues","Access =
Issue - Land Lord","Access issue during the night due to landlord//Site wen=
t down due to GEN overload (20 KVA, 300A) // He reduced load, site on GEN",=
"gerard.tchangoue@matech-cameroun.com","310","03-08-2025 02:23:15","MATECH =
CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005610958","S=
atcom","","03-08-2025 01:18:34","03-08-2025 01:16:13","03-08-2025 01:17:13"=
,"No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand ngu=
etsa(691144412) From huawei is informed.","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand nguetsa(6=
91144412) From huawei is informed.","gerard.tchangoue@matech-cameroun.com",=
"142","03-08-2025 01:18:34","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005610949","Fou=
da Quarter","","03-08-2025 01:16:22","03-08-2025 01:14:16","03-08-2025 02:1=
6:16","Grid bad voltage , site down because gen fails to start due to grid =
bad voltage // Gen manually started","Delor Telezing","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid bad voltage , sit=
e down because gen fails to start due to grid bad voltage // Gen manually s=
tarted","franck.nkomot@matech-cameroun.com","127","03-08-2025 01:16:22","MA=
TECH CMR"
"Closed Complete","Site Down","T2585","IHS_YND_744","NOCINC0005610876","Ele=
veur Meec Bon Berger","","03-08-2025 00:40:26","03-08-2025 00:35:15","03-08=
-2025 01:07:15","Grid outage gen failed to start due to alarm undervoltage =
// He reset Gen card and started Gen manually","Siligap Boris","Equipment R=
epair","Passive","ACDG Gen","ACDG - Under Voltage","Grid outage gen failed =
to start due to alarm undervoltage // He reset Gen card and started Gen man=
ually","franck.nkomot@matech-cameroun.com","312","03-08-2025 00:40:26","MAT=
ECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005610829","Nko=
abang Ebolmedjock","","03-08-2025 00:26:56","03-08-2025 00:24:44","03-08-20=
25 02:25:44","Grid outage, site went down because gen failed to start with =
alarm Over voltaged // He reset gen card and gen manually started","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","G=
rid outage, site went down because gen failed to start with alarm Over volt=
aged // He reset gen card and gen manually started","franck.nkomot@matech-c=
ameroun.com","133","03-08-2025 00:26:56","MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005610801","Mfa=
ndena","","03-08-2025 00:14:56","03-08-2025 00:09:48","03-08-2025 02:11:48"=
,"Grid outage, site went down due to insufficiency of rectifiers // Site st=
abilized","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Grid outage, site went down due to insufficiency of rectifiers=
 // Site stabilized","franck.nkomot@matech-cameroun.com","309","03-08-2025 =
00:14:56","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005610750","O=
LAMA","","03-08-2025 00:01:15","02-08-2025 23:51:53","02-08-2025 23:52:48",=
"Active // No power issue on site Ubaie: 54.6V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue on site Ubaie: 54.6V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","gerard.tchangoue@matech-cameroun.com","2713","03=
-08-2025 00:01:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_801","NOCINC0005610740","HOPITAL =
GENERAL RAIL YDE","","02-08-2025 23:58:56","02-08-2025 23:47:59","03-08-202=
5 01:25:59","Cascaded Incident from TTO5804117","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down because gen failed to start due to gen card faulty // Grid restorati=
on","franck.nkomot@matech-cameroun.com","267411","02-08-2025 23:58:56","MAT=
ECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005610734","Pha=
rmacie Bleue","IHS_YND_801","02-08-2025 23:57:11","02-08-2025 23:47:59","03=
-08-2025 01:25:59","Grid outage, site went down because gen failed to start=
 due to gen card faulty // Grid restoration","Siligap Boris","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went do=
wn because gen failed to start due to gen card faulty // Grid restoration",=
"franck.nkomot@matech-cameroun.com","553","02-08-2025 23:57:11","MATECH CMR=
"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005610705","M=
vog-Ebanda","","02-08-2025 23:41:48","02-08-2025 23:15:53","03-08-2025 01:2=
7:53","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, Site went down because Gen failed to start due t=
o Gen Overload (16KVA /300A) // Grid return","gerard.tchangoue@matech-camer=
oun.com","269063","02-08-2025 23:41:48","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005610679","M=
elen Ba'aba","","02-08-2025 23:35:15","02-08-2025 23:25:59","02-08-2025 23:=
26:59","No power issue, site is on Gen with Ubaie: 54.3V, FME TX Julien (69=
3095849) from Huawei is informed.","Siligap Boris","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue, site is on Gen with Ubaie: 54.3V, FME TX Julien (693095849) from Huawei=
 is informed.","franck.nkomot@matech-cameroun.com","558","02-08-2025 23:35:=
15","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005610674","N=
koabang2","","02-08-2025 23:33:05","02-08-2025 23:30:54","03-08-2025 01:21:=
54","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","franck=
.nkomot@matech-cameroun.com","133","02-08-2025 23:33:05","MATECH CMR"
"Closed Complete","Site Down","CTR_621","IHS_YND_278","NOCINC0005610651","N=
kolfoulou 2","","02-08-2025 23:27:07","02-08-2025 23:20:20","03-08-2025 02:=
27:20","No power issue, site is on Grid with Ubaie: 52.5V, FME TX Julien (6=
93095849) from Huawei is informed.","Siligap Boris","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue, site is on Grid with Ubaie: 52.5V, FME TX Julien (693095849) from Huaw=
ei is informed.","franck.nkomot@matech-cameroun.com","408","02-08-2025 23:2=
7:07","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0005610638","Nko=
lfoulou","","02-08-2025 23:22:15","02-08-2025 23:12:59","02-08-2025 23:30:5=
9","Grid outage, site down due to gen overload 300 A /20 KVA // Gen charge =
reduced and manual start of gen","Siligap Boris","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage, site down due to gen overload=
 300 A /20 KVA // Gen charge reduced and manual start of gen","franck.nkomo=
t@matech-cameroun.com","557","02-08-2025 23:22:15","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005610636","A=
bom","IHS_YND_269","02-08-2025 23:22:12","02-08-2025 23:15:53","03-08-2025 =
01:27:53","Grid outage, Site went down because Gen failed to start due to G=
en Overload (16KVA /300A) // Grid return","Siligap Boris","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen failed to start due to Gen Overload (16KVA /300A) // Grid return","g=
erard.tchangoue@matech-cameroun.com","380","02-08-2025 23:22:12","MATECH CM=
R"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005610600","T=
SINGA VILLAGE 2","","02-08-2025 23:09:59","02-08-2025 23:04:59","03-08-2025=
 00:10:51","Active//No power issue on site, Site on Gen UBAIE=3D54.5V TX FM=
E Julien (693095849) From Huawei is informed","Delor Telezing","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Gen UBAIE=3D54.5V TX FME Julien (69=
3095849) From Huawei is informed","gerard.tchangoue@matech-cameroun.com","6=
456","02-08-2025 23:09:59","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005610521","AKA=
K Nkozoa","","02-08-2025 22:52:49","02-08-2025 22:44:34","02-08-2025 22:53:=
34","Active// No power issue, site is on Grid with Ubaie=3D50,4 V TX FME Sy=
mphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power issue, site is on Grid with Ubaie=3D50,4 V TX FME Sympho=
rien (650257151) from Huawei is informed","franck.nkomot@matech-cameroun.co=
m","496","02-08-2025 22:52:49","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005610518","Ebo=
go","","02-08-2025 22:52:13","02-08-2025 22:44:26","02-08-2025 23:04:26","N=
o power issue on site U=3D52,2V site on Grid. Synphorien 675295205 of Huawe=
i is informed","Siligap Boris","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52,2V=
 site on Grid. Synphorien 675295205 of Huawei is informed","franck.nkomot@m=
atech-cameroun.com","468","02-08-2025 22:52:13","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005610291","MBA=
LNGONG LYCEE","","02-08-2025 22:00:39","02-08-2025 21:50:59","03-08-2025 00=
:30:59","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed//Grid return","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//G=
rid return","franck.nkomot@matech-cameroun.com","582","02-08-2025 22:00:39"=
,"MATECH CMR"
"Closed Complete","Site Down","T2222","IHS_YND_697","NOCINC0005610170","Nom=
ayos-IHS","","02-08-2025 21:34:43","02-08-2025 21:25:25","03-08-2025 03:04:=
25","Site went down due to insufficient rectifiers on site//Site stabilized=
","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to insufficient rectifiers on site//Site stabilized","=
franck.nkomot@matech-cameroun.com","559","02-08-2025 21:34:43","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005609999","MBA=
LNGONG LYCEE","","02-08-2025 21:06:15","02-08-2025 20:56:59","02-08-2025 21=
:09:59","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed//Grid return","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//G=
rid return","franck.nkomot@matech-cameroun.com","558","02-08-2025 21:06:15"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005609702","B=
arriere","","02-08-2025 20:02:51","02-08-2025 20:02:44","02-08-2025 20:08:4=
1","Active // No power issue on site Ubay: 53.5V site on Gen .TX Fme Fluber=
t (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue on site Ubay: 53.5V site on Gen .TX Fme Flubert (654266068/Hua=
wei) is informed","gerard.tchangoue@matech-cameroun.com","10","02-08-2025 2=
0:02:51","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005608684","Hop=
ital Central","","02-08-2025 16:11:54","02-08-2025 16:03:45","02-08-2025 16=
:55:45","site went down due to insufficient rectifiers on site//Site stabil=
ised","","Equipment Repair","Passive","Rectifier","Rectifier Module","site =
went down due to insufficient rectifiers on site//Site stabilised","franck.=
nkomot@matech-cameroun.com","490","02-08-2025 16:11:54","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005608679","Mok=
olo Yaounde","","02-08-2025 16:11:09","02-08-2025 16:03:03","02-08-2025 16:=
15:03","Grid only site, no space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e, no space to deploy MDGE // Grid returned","franck.nkomot@matech-cameroun=
.com","488","02-08-2025 16:11:09","MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0005608664","K=
amajou Building","","02-08-2025 16:08:09","02-08-2025 16:06:02","02-08-2025=
 17:29:55","Grid outage, site went down because Gen failed to start due to =
Gen battery faulty //  He started Gen with external battery","Paul BIBOUM",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid ou=
tage, site went down because Gen failed to start due to Gen battery faulty =
//  He started Gen with external battery","gerard.tchangoue@matech-cameroun=
.com","128","02-08-2025 16:08:09","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005608582","Eto=
ug ebe Carrefour","","02-08-2025 15:50:17","02-08-2025 15:43:08","02-08-202=
5 16:31:08","Site went down because gen fails to start due to grid bad volt=
age // He bypass grid and manually start the gen","Hyemafo Gildas","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Site went=
 down because gen fails to start due to grid bad voltage // He bypass grid =
and manually start the gen","franck.nkomot@matech-cameroun.com","430","02-0=
8-2025 15:50:17","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005608508","C=
NR","","02-08-2025 15:36:41","02-08-2025 15:27:31","02-08-2025 19:27:48","N=
o power issue site on Gen with U=3D54.8V Mohamadou from Huawei is informed"=
,"Mboua Thierry","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue site on Gen with U=3D54.8V Moha=
madou from Huawei is informed","gerard.tchangoue@matech-cameroun.com","551"=
,"02-08-2025 15:36:41","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0005608476","Val=
lee Bastos MTN","","02-08-2025 15:27:52","02-08-2025 15:23:45","02-08-2025 =
15:29:45","Site went down because insufficient of rectifier //site stabiliz=
ed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down because insufficient of rectifier //site stabilized","=
franck.nkomot@matech-cameroun.com","248","02-08-2025 15:27:52","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005608463","Hop=
ital Central","","02-08-2025 15:25:26","02-08-2025 15:18:16","02-08-2025 15=
:28:16","site went down due to insufficient rectifiers on site//Site stabil=
ised","","Equipment Repair","Passive","Rectifier","Rectifier Module","site =
went down due to insufficient rectifiers on site//Site stabilised","franck.=
nkomot@matech-cameroun.com","430","02-08-2025 15:25:26","MATECH CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0005608204","Ngo=
a Ekelle","","02-08-2025 14:36:50","02-08-2025 14:27:43","02-08-2025 15:22:=
32","Grid outage,DG started and stopped due with alarm ""oil pressure""( un=
prouven Alarm ) // He reset DG card and started DG manually","Paul BIBOUM",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
,DG started and stopped due with alarm ""oil pressure""( unprouven Alarm ) =
// He reset DG card and started DG manually","gerard.tchangoue@matech-camer=
oun.com","548","02-08-2025 14:36:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005607949","Bastos B=
ethesda","","02-08-2025 13:52:28","02-08-2025 13:40:20","02-08-2025 13:49:0=
9","Cascaded Incident from TTO5800935","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Site impacted by CNDH (not manage =
by IHS)","gerard.tchangoue@matech-cameroun.com","260700","02-08-2025 13:52:=
28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005607948","Golf Qua=
ter","","02-08-2025 13:52:28","02-08-2025 13:40:20","02-08-2025 13:49:09","=
Cascaded Incident from TTO5800935","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","Site impacted by CNDH (not manage by I=
HS)","gerard.tchangoue@matech-cameroun.com","260699","02-08-2025 13:52:28",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_010","NOCINC0005607936","CNR","",=
"02-08-2025 13:49:01","02-08-2025 13:40:20","02-08-2025 13:49:09","Cascaded=
 Incident from TTO5800935","Mboua Thierry","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by CNDH (not manage by IHS)","ge=
rard.tchangoue@matech-cameroun.com","260700","02-08-2025 13:49:01","MATECH =
CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005607929","Mok=
olo Yaounde","","02-08-2025 13:48:07","02-08-2025 13:43:00","02-08-2025 13:=
53:20","Grid only site, no space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e, no space to deploy MDGE // Grid returned","edwige.kapawo@matech-cameroun=
.com","309","02-08-2025 13:48:07","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005607923","Hop=
ital Central","","02-08-2025 13:47:22","02-08-2025 13:42:12","02-08-2025 13=
:52:47","site went down due to insufficient rectifiers on site//Site stabil=
ised","","Equipment Repair","Passive","Rectifier","Rectifier Module","site =
went down due to insufficient rectifiers on site//Site stabilised","edwige.=
kapawo@matech-cameroun.com","310","02-08-2025 13:47:22","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005607922","Cit=
e des nations","","02-08-2025 13:46:46","02-08-2025 13:41:40","02-08-2025 1=
3:47:43","Grid outage,site went down before Gen started due to Poor battery=
 backup//Gen automatically started","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage,site went do=
wn before Gen started due to Poor battery backup//Gen automatically started=
","edwige.kapawo@matech-cameroun.com","307","02-08-2025 13:46:46","MATECH C=
MR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0005607918","Tsi=
nga","","02-08-2025 13:46:07","02-08-2025 13:40:20","02-08-2025 13:55:03","=
","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically starte","edwige.kapawo@matech-cameroun.com","267898","02-0=
8-2025 13:46:07","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005607915","Sim=
e Building","IHS_YND_127","02-08-2025 13:45:38","02-08-2025 13:41:30","02-0=
8-2025 13:55:03","Grid outage, Site went down before Gen start due to poor =
backup // Gen automatically starte","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen automatically starte","edw=
ige.kapawo@matech-cameroun.com","249","02-08-2025 13:45:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005607914","Bastos-N=
ylon","IHS_YND_220, IHS_YND_563, IHS_YND_010, IHS_YND_127","02-08-2025 13:4=
5:27","02-08-2025 13:40:20","02-08-2025 13:49:09","Site impacted by CNDH (n=
ot manage by IHS)","Mboua Thierry","Customer Equipment Failure","Active","A=
ctive Equipment Failure","Affected by 3rd Party Site","Site impacted by CND=
H (not manage by IHS)","gerard.tchangoue@matech-cameroun.com","308","02-08-=
2025 13:45:27","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005607844","M=
vog-Ada_OCM","","02-08-2025 13:28:02","02-08-2025 13:26:54","02-08-2025 14:=
23:32","Grid only on site, No space on site to deploy MDGE // Grid return	"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d only on site, No space on site to deploy MDGE // Grid return	","edwige.ka=
pawo@matech-cameroun.com","69","02-08-2025 13:28:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005607532","MEHANDAN=
","","02-08-2025 12:50:28","02-08-2025 12:46:42","02-08-2025 13:41:49","Cas=
caded Incident from TTO5800512","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to  2 CB faulty in =
the DC Box   // CB remplaced  and site on Grid","gerard.tchangoue@matech-ca=
meroun.com","270844","02-08-2025 12:50:28","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005607525","O=
dza-PK10","IHS_YND_527, IHS_YND_528","02-08-2025 12:48:48","02-08-2025 12:4=
6:42","02-08-2025 13:41:49","Site went down due to  2 CB faulty in the DC B=
ox   // CB remplaced  and site on Grid","Albran Byorel","Equipment Repair",=
"Passive","Control Panel","ATS-AMF Issue","Site went down due to  2 CB faul=
ty in the DC Box   // CB remplaced  and site on Grid","gerard.tchangoue@mat=
ech-cameroun.com","127","02-08-2025 12:48:48","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005607521","O=
dza II OCM","","02-08-2025 12:47:47","02-08-2025 12:46:42","02-08-2025 13:4=
1:49","	Cascaded Incident from TTO5800512","Albran Byorel","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to  2 CB=
 faulty in the DC Box   // CB remplaced  and site on Grid","gerard.tchangou=
e@matech-cameroun.com","270844","02-08-2025 12:47:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005607492","ETOUDI C=
HAPELLE","","02-08-2025 12:45:50","02-08-2025 12:44:09","02-08-2025 14:24:5=
8","Cascaded Incident from TTO5800476","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on grid with =
U=3D52.9V, TX fme Armand Nguetsa /699949553 from Huawei is informed","edwig=
e.kapawo@matech-cameroun.com","271050","02-08-2025 12:45:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005607493","Etoudi 2=
","","02-08-2025 12:45:50","02-08-2025 12:44:09","02-08-2025 14:24:58","Cas=
caded Incident from TTO5800476","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D52=
.9V, TX fme Armand Nguetsa /699949553 from Huawei is informed","edwige.kapa=
wo@matech-cameroun.com","271049","02-08-2025 12:45:50","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005607491","Aba=
ttoir","IHS_YND_694, IHS_YND_211","02-08-2025 12:45:17","02-08-2025 12:44:0=
9","02-08-2025 14:24:58","No power issue site on grid with U=3D52.9V, TX fm=
e Armand Nguetsa /699949553 from Huawei is informed","Fabrice Pouakam","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue site on grid with U=3D52.9V, TX fme Armand Nguetsa /=
699949553 from Huawei is informed","edwige.kapawo@matech-cameroun.com","69"=
,"02-08-2025 12:45:17","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005606753","L=
abogenie","IHS_YND_568","02-08-2025 10:04:35","02-08-2025 09:58:24","02-08-=
2025 10:18:20","No power issue U =3D54,6V site on Grid. The Tx FME Eloundou=
 (693212405 )from Huawei is informed.","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D5=
4,6V site on Grid. The Tx FME Eloundou (693212405 )from Huawei is informed.=
","gerard.tchangoue@matech-cameroun.com","373","02-08-2025 10:04:35","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0005606729","A=
nguissa New","","02-08-2025 10:00:43","02-08-2025 09:58:24","02-08-2025 10:=
18:20","","MINKA NICOLAS","Cascade Outage","Active","Cascade Active","Casca=
de Active","No power issue U =3D54,6V site on Grid. The Tx FME Eloundou (69=
3212405 )from Huawei is informed.","gerard.tchangoue@matech-cameroun.com","=
266566","02-08-2025 10:00:43","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005606238","O=
kola OCM","","02-08-2025 08:02:39","02-08-2025 07:42:25","02-08-2025 09:20:=
58","Grid bad voltage , site down because gen fails to start due to bad gri=
d voltage // Grid bypass and Gen manually started  ","TIENTCHEU NZETCHIEU G=
AEL","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid bad voltage , site down because gen fails to start due to bad grid=
 voltage // Grid bypass and Gen manually started  ","edwige.kapawo@matech-c=
ameroun.com","2272","02-08-2025 08:02:39","MATECH CMR"
"Closed Complete","Site Down","T3446","IHS_YND_712","NOCINC0005606162","Nko=
lkoumou OCM","","02-08-2025 07:48:44","02-08-2025 07:43:02","02-08-2025 07:=
46:12","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen failed to=
 start due to grid bad voltage and no Rcp // He bypassed Grid and started G=
en manually","edwige.kapawo@matech-cameroun.com","260358","02-08-2025 07:48=
:44","MATECH CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0005606150","N=
kolbisson usine des eaux","IHS_YND_712","02-08-2025 07:46:31","02-08-2025 0=
7:43:02","02-08-2025 07:50:12","Grid outage, site went down because gen fai=
led to start due to grid bad voltage and no Rcp // He bypassed Grid and sta=
rted Gen manually","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid outage, site went down be=
cause gen failed to start due to grid bad voltage and no Rcp // He bypassed=
 Grid and started Gen manually","edwige.kapawo@matech-cameroun.com","210","=
02-08-2025 07:46:31","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005606128","N=
kolfon Cimencam","","02-08-2025 07:41:46","02-08-2025 07:40:38","02-08-2025=
 07:43:04","Site is impacted by Afanoya II (Not manage by IHS)","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","Aff=
ected by 3rd Party Site","Site is impacted by Afanoya II (Not manage by IHS=
)","edwige.kapawo@matech-cameroun.com","70","02-08-2025 07:41:46","MATECH C=
MR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0005606095","Omn=
isport-Rail","","02-08-2025 07:31:56","02-08-2025 07:29:48","02-08-2025 07:=
35:03","Site went down because gen fails to start due to grid bad voltage /=
/ He bypass grid and manually start the gen","Delor Telezing","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Site went down=
 because gen fails to start due to grid bad voltage // He bypass grid and m=
anually start the gen","edwige.kapawo@matech-cameroun.com","414","02-08-202=
5 07:31:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005605759","Nkol-Meb=
anga","","02-08-2025 05:56:44","02-08-2025 05:48:43","02-08-2025 06:27:29",=
"Cascaded Incident from TTO5798598","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e Gen started and stopped due to alarm undervoltage // He reset DG card, Ge=
n started manually","loic.noumsi@matech-cameroun.com","267517","02-08-2025 =
05:56:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005605758","Carrefou=
r Ayissi Ele","","02-08-2025 05:56:44","02-08-2025 05:48:43","02-08-2025 06=
:27:29","Cascaded Incident from TTO5798598","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n because Gen started and stopped due to alarm undervoltage // He reset DG =
card, Gen started manually","loic.noumsi@matech-cameroun.com","267517","02-=
08-2025 05:56:44","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005605737","S=
aa","IHS_YND_810, IHS_YND_809","02-08-2025 05:50:49","02-08-2025 05:48:43",=
"02-08-2025 06:27:29","Grid outage, site went down because Gen started and =
stopped due to alarm undervoltage // He reset DG card, Gen started manually=
","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid outage, site went down because Gen started and stopped due to a=
larm undervoltage // He reset DG card, Gen started manually","loic.noumsi@m=
atech-cameroun.com","127","02-08-2025 05:50:49","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005605673","A=
fanoya","","02-08-2025 05:27:49","02-08-2025 05:26:38","02-08-2025 07:14:56=
","Grid outage, site down because gen fail to start due to his faulty relay=
 started // Gen relay starter changed,site left on Gen","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - Relay Faulty","Grid outage, s=
ite down because gen fail to start due to his faulty relay started // Gen r=
elay starter changed,site left on Gen","loic.noumsi@matech-cameroun.com","7=
3","02-08-2025 05:27:49","MATECH CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0005605506","M=
atomb","","02-08-2025 04:22:06","02-08-2025 04:17:59","02-08-2025 04:28:21"=
,"Grid outage, Site went down because gen stopped due to belt cut and poor =
backup // He changed belt and Gen manually started ","Kemeni Franklin","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Fan Belt","Grid outage, Site we=
nt down because gen stopped due to belt cut // He changed belt and Gen manu=
ally started ","loic.noumsi@matech-cameroun.com","248","02-08-2025 04:22:06=
","MATECH CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0005605427","B=
otmakak","","02-08-2025 03:43:31","02-08-2025 02:15:43","02-08-2025 04:13:0=
7","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","cascaded site","loic.noumsi@matech-cameroun.com","272675","02-=
08-2025 03:43:31","MATECH CMR"
"Closed Complete","Site Down","CTR_360","IHS_YND_373","NOCINC0005605420","M=
aloun","","02-08-2025 03:38:31","02-08-2025 02:15:43","02-08-2025 04:13:07"=
,"","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, Site went down because gen stopped due to belt cut =
// He changed belt and Gen manually started ","loic.noumsi@matech-cameroun.=
com","272674","02-08-2025 03:38:31","MATECH CMR"
"Closed Complete","Site Down","CTR_115","IHS_YND_375","NOCINC0005605416","N=
goung","","02-08-2025 03:35:44","02-08-2025 02:15:43","02-08-2025 04:13:07"=
,"","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","cascaded site","loic.noumsi@matech-cameroun.com","272675","02-08=
-2025 03:35:44","MATECH CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0005605398","N=
kolbisson usine des eaux","IHS_YND_712","02-08-2025 03:24:36","02-08-2025 0=
3:24:30","02-08-2025 04:40:22","Grid outage, site went down because gen fai=
led to start due to grid bad voltage and no Rcp // He bypassed Grid and sta=
rted Gen manually","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid outage, site went down be=
cause gen failed to start due to grid bad voltage and no Rcp // He bypassed=
 Grid and started Gen manually","loic.noumsi@matech-cameroun.com","7","02-0=
8-2025 03:24:36","MATECH CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0005605395","N=
kolkoumou OCM","","02-08-2025 03:23:34","02-08-2025 03:24:30","02-08-2025 0=
4:40:22","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","Grid outage, site went down because gen failed =
to start due to grid bad voltage and no Rcp // He bypassed Grid and started=
 Gen manually","loic.noumsi@matech-cameroun.com","268799","02-08-2025 03:23=
:34","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005605123","NKO=
NGKARAK","","02-08-2025 02:34:13","02-08-2025 02:32:07","02-08-2025 05:25:0=
6","Grid outage, Site went down because Gen started and stopped due to High=
 temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, Site went down because Gen started and stop=
ped due to High temp alarm //He added water and Gen start manually","loic.n=
oumsi@matech-cameroun.com","127","02-08-2025 02:34:13","MATECH CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0005605106","M=
atomb","IHS_YND_373, IHS_YND_375, IHS_YND_422","02-08-2025 02:24:48","02-08=
-2025 02:15:43","02-08-2025 04:13:07","Grid outage, Site went down because =
gen stopped due to belt cut and poor backup // He changed belt and Gen manu=
ally started ","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","A=
CDG - Fan Belt","Grid outage, Site went down because gen stopped due to bel=
t cut // He changed belt and Gen manually started ","loic.noumsi@matech-cam=
eroun.com","546","02-08-2025 02:24:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005605100","OTELE MT=
N","","02-08-2025 02:22:22","02-08-2025 02:16:53","02-08-2025 02:17:38","Ca=
scaded Incident from TTO5797899","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by T0169 Ngoumou not manage =
by IHS","loic.noumsi@matech-cameroun.com","272820","02-08-2025 02:22:22","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005605102","Mom","",=
"02-08-2025 02:22:22","02-08-2025 02:16:53","02-08-2025 02:17:38","Cascaded=
 Incident from TTO5797899","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by IHS=
","loic.noumsi@matech-cameroun.com","272821","02-08-2025 02:22:22","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005605101","Minka","=
","02-08-2025 02:22:22","02-08-2025 02:16:53","02-08-2025 02:17:38","Cascad=
ed Incident from TTO5797899","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by I=
HS","loic.noumsi@matech-cameroun.com","272819","02-08-2025 02:22:22","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005605099","OLAMA","=
","02-08-2025 02:22:21","02-08-2025 02:16:53","02-08-2025 02:17:38","Cascad=
ed Incident from TTO5797899","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by I=
HS","loic.noumsi@matech-cameroun.com","272820","02-08-2025 02:22:21","MATEC=
H CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005605094","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","02-08-2025 02:18:=
02","02-08-2025 02:16:53","02-08-2025 02:17:38","Site impacted by T0169 Ngo=
umou not manage by IHS","Fanda Brice","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Site impacted by T0169 Ng=
oumou not manage by IHS","loic.noumsi@matech-cameroun.com","70","02-08-2025=
 02:18:02","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005604568","M=
ontee-Jouvence-II","","01-08-2025 23:14:56","01-08-2025 23:11:51","01-08-20=
25 23:18:45","Grid outage, Site went down before Gen start due to poor back=
up // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Site stabilised","loic.noumsi@matech-camer=
oun.com","187","01-08-2025 23:14:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005604253","Minka","=
","01-08-2025 22:12:15","01-08-2025 22:06:21","01-08-2025 22:15:29","Cascad=
ed Incident from TTO5796930","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability.Henri (699949693) from=
 Huawei is informed.","gerard.tchangoue@matech-cameroun.com","266148","01-0=
8-2025 22:12:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_368","NOCINC0005604251","Otele","=
","01-08-2025 22:12:15","01-08-2025 22:06:21","01-08-2025 22:15:29","Cascad=
ed Incident from TTO5796930","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability.Henri (699949693) from=
 Huawei is informed.","gerard.tchangoue@matech-cameroun.com","266147","01-0=
8-2025 22:12:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005604252","OLAMA","=
","01-08-2025 22:12:15","01-08-2025 22:06:21","01-08-2025 22:15:29","Cascad=
ed Incident from TTO5796930","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability.Henri (699949693) from=
 Huawei is informed.","gerard.tchangoue@matech-cameroun.com","266146","01-0=
8-2025 22:12:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005604250","Mom","",=
"01-08-2025 22:12:15","01-08-2025 22:06:21","01-08-2025 22:15:29","Cascaded=
 Incident from TTO5796930","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on grid with U=3D54v Site is=
 impacted by Ngoumou who is not our responsability.Henri (699949693) from H=
uawei is informed.","gerard.tchangoue@matech-cameroun.com","266147","01-08-=
2025 22:12:15","MATECH CMR"
"Closed Complete","Site Down","CTR_063","IHS_YND_365","NOCINC0005604201","A=
kono","IHS_YND_370, IHS_YND_368, IHS_YND_687, IHS_YND_371","01-08-2025 22:0=
7:26","01-08-2025 22:06:21","01-08-2025 22:15:29","No power issue site on g=
rid with U=3D54v Site is impacted by Ngoumou who is not our responsability.=
Henri (699949693) from Huawei is informed.","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","Affected by 3rd Party Site=
","No power issue site on grid with U=3D54v Site is impacted by Ngoumou who=
 is not our responsability.Henri (699949693) from Huawei is informed.","ger=
ard.tchangoue@matech-cameroun.com","66","01-08-2025 22:07:26","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005604153","N=
kozoa","","01-08-2025 21:57:51","01-08-2025 21:48:41","01-08-2025 23:18:04"=
,"Site went down due to disjunction of CB (125A) in the Huawei PWC // He re=
armed it, site on Grid ","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to=
 disjunction of CB (125A) in the Huawei PWC // He rearmed it, site on Grid =
","gerard.tchangoue@matech-cameroun.com","552","01-08-2025 21:57:51","MATEC=
H CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005604121","Eto=
ug ebe Carrefour","","01-08-2025 21:51:52","01-08-2025 21:44:35","01-08-202=
5 22:02:04","Grid outage site went down before gen started due to poor batt=
ery backup// Grid returned","Hyemafo Gildas","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage site went down be=
fore gen started due to poor battery backup// Grid returned","cedric.tiani@=
matech-cameroun.com","438","01-08-2025 21:51:52","MATECH CMR"
"Closed Complete","Site Down","T2222","IHS_YND_697","NOCINC0005604039","Nom=
ayos-IHS","","01-08-2025 21:37:12","01-08-2025 21:30:59","01-08-2025 21:51:=
33","Site went down due to insufficient rectifiers on site//Grid return","F=
anda Brice","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to insufficient rectifiers on site//Grid return","cedric.t=
iani@matech-cameroun.com","374","01-08-2025 21:37:12","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0005603976","Bar=
riere IHS","","01-08-2025 21:29:06","01-08-2025 21:27:55","01-08-2025 21:36=
:47","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS F=
ELIX ZAMBE is informed //Grid return","Hyemafo Gildas","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to G=
en overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed //Grid return","ced=
ric.tiani@matech-cameroun.com","72","01-08-2025 21:29:06","MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005603680","Mvo=
g Betsi Hospital","","01-08-2025 20:33:19","01-08-2025 20:30:10","01-08-202=
5 20:35:47","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","cedric.tiani@matech-cameroun.com"=
,"190","01-08-2025 20:33:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005603489","Nkolfon =
Cimencam","","01-08-2025 19:57:56","01-08-2025 19:53:14","01-08-2025 19:57:=
23","Cascaded Incident from TTO5796142","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirm=
ed // Grid return","gerard.tchangoue@matech-cameroun.com","266913","01-08-2=
025 19:57:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005603488","Ahala","=
","01-08-2025 19:57:55","01-08-2025 19:53:14","01-08-2025 19:57:23","Cascad=
ed Incident from TTO5796142","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Gen o=
verload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid =
return","gerard.tchangoue@matech-cameroun.com","266914","01-08-2025 19:57:5=
5","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005603482","NYO=
M FACE MAETUR","","01-08-2025 19:56:12","01-08-2025 19:48:01","01-08-2025 1=
9:49:59","Grid fluctuations , site went down because Gen failed to start du=
e to Grid bad voltage // Grid stabilisation ","Fabrice Pouakam","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tions , site went down because Gen failed to start due to Grid bad voltage =
// Grid stabilisation ","cedric.tiani@matech-cameroun.com","493","01-08-202=
5 19:56:12","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005603479","M=
eyo","IHS_YND_257, IHS_YND_762","01-08-2025 19:55:24","01-08-2025 19:53:14"=
,"01-08-2025 20:03:32","Grid outage, site went down due to Gen overload (17=
KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid return","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix Za=
mbe is informed and confirmed // Grid return","gerard.tchangoue@matech-came=
roun.com","131","01-08-2025 19:55:24","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005603461","B=
arriere IHS","","01-08-2025 19:52:04","01-08-2025 19:47:58","01-08-2025 19:=
58:58","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed //Grid return","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to=
 Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed //Grid return","g=
erard.tchangoue@matech-cameroun.com","248","01-08-2025 19:52:04","MATECH CM=
R"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005603368","Eto=
ug ebe Carrefour","","01-08-2025 19:39:20","01-08-2025 19:33:07","01-08-202=
5 19:39:45","Grid outage, Site went down before Gen start due to poor backu=
p/ // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Grid return","cedric.tiani@matech-cameroun.co=
m","374","01-08-2025 19:39:20","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005603195","M=
ontee-Jouvence-II","","01-08-2025 19:14:59","01-08-2025 19:10:50","01-08-20=
25 19:26:00","Grid outage, Site went down before Gen start due to poor back=
up/ // Gen automatically started","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup/ // Gen automatically started","ge=
rard.tchangoue@matech-cameroun.com","251","01-08-2025 19:14:59","MATECH CMR=
"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005602789","Eto=
ug ebe Carrefour","","01-08-2025 18:03:35","01-08-2025 18:02:25","01-08-202=
5 18:08:02","Grid outage site went down before gen started due to poor batt=
ery backup // Grid stabilised","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before gen started due to poor battery backup // Grid stabilised","cedric.=
tiani@matech-cameroun.com","71","01-08-2025 18:03:35","MATECH CMR"
"Closed Complete","Site Down","T2222","IHS_YND_697","NOCINC0005602764","Nom=
ayos-IHS","","01-08-2025 18:00:56","01-08-2025 17:56:31","01-08-2025 18:10:=
46","Site went down due to insufficient rectifiers on site //He reduiced th=
e load and site on Gen","Fanda Brice","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Grid fluctuations , site went down because Gen fail=
ed to start due to Grid bad voltage // Grid stabilisation ","cedric.tiani@m=
atech-cameroun.com","266","01-08-2025 18:00:56","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0005602759","Bar=
riere IHS","","01-08-2025 17:59:14","01-08-2025 17:55:05","01-08-2025 18:19=
:54","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS F=
ELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to =
Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return","g=
erard.tchangoue@matech-cameroun.com","252","01-08-2025 17:59:14","MATECH CM=
R"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005602749","Aha=
la Echangeur","","01-08-2025 17:56:41","01-08-2025 17:47:59","01-08-2025 18=
:19:59","Grid outage, site went down because Gen failed to start due to GE =
contactor not excited  // He excited  GEN contactor and manually started th=
e Gen","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Load=
 Contactor","Grid outage, site went down because Gen failed to start due to=
 GE contactor not excited  // He excited  GEN contactor and manually starte=
d the Gen","cedric.tiani@matech-cameroun.com","523","01-08-2025 17:56:41","=
MATECH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005602498","N=
omayos-IHS","","01-08-2025 17:16:25","01-08-2025 17:14:08","01-08-2025 17:3=
7:43","Site went down due to insufficient rectifiers on site //He reduced t=
he load and site on Gen","Fanda Brice","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to insufficient rectifiers on s=
ite //He reduced the load and site on Gen","gerard.tchangoue@matech-camerou=
n.com","139","01-08-2025 17:16:25","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005602466","Hop=
ital Central","","01-08-2025 17:11:41","01-08-2025 17:08:31","01-08-2025 17=
:50:38","(Unstable)Site went down due to 03/05 rectifiers faulty//Site stab=
ilised","","Equipment Repair","Passive","Rectifier","Rectifier Module","(Un=
stable)Site went down due to 03/05 rectifiers faulty//Site stabilised","ced=
ric.tiani@matech-cameroun.com","191","01-08-2025 17:11:41","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005602249","Feb=
e Village","","01-08-2025 16:34:38","01-08-2025 16:31:30","01-08-2025 16:36=
:08","Grid outage, site went down because Gen failed to start due to PWC ov=
erload//Site stabilised","Mboua Thierry","Equipment Repair","Passive","Rect=
ifier","Rectifier Module Overloaded","Grid outage, site went down because G=
en failed to start due to PWC overload//Site stabilised","cedric.tiani@mate=
ch-cameroun.com","189","01-08-2025 16:34:38","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005602156","N=
kolfon Cimencam","","01-08-2025 16:18:22","01-08-2025 16:04:12","01-08-2025=
 18:17:58","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down due to Gen overload (17KVA,=
 260A) SS HIS Felix Zambe is informed and confirmed // Grid return","cedric=
.tiani@matech-cameroun.com","273614","01-08-2025 16:18:22","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005602107","A=
hala","","01-08-2025 16:11:30","01-08-2025 16:04:12","01-08-2025 18:17:58",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down due to Gen overload (17KVA, 260A) SS H=
IS Felix Zambe is informed and confirmed // Grid return","gerard.tchangoue@=
matech-cameroun.com","273614","01-08-2025 16:11:30","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005602085","M=
eyo","IHS_YND_257, IHS_YND_762","01-08-2025 16:08:25","01-08-2025 16:04:12"=
,"01-08-2025 18:23:52","Grid outage, site went down due to Gen overload (17=
KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid return","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix Za=
mbe is informed and confirmed // Grid return","gerard.tchangoue@matech-came=
roun.com","255","01-08-2025 16:08:25","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005601822","Feb=
e Village","","01-08-2025 15:41:15","01-08-2025 15:40:06","01-08-2025 15:44=
:30","Grid outage, site went down because Gen failed to start due to PWC ov=
erload//Site stabilised","Mboua Thierry","Equipment Repair","Passive","Rect=
ifier","Rectifier Module Overloaded","Grid outage, site went down because G=
en failed to start due to PWC overload//Site stabilised","cedric.tiani@mate=
ch-cameroun.com","70","01-08-2025 15:41:15","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005601789","Mon=
tee-Jouvence-II","","01-08-2025 15:33:11","01-08-2025 15:28:47","01-08-2025=
 17:21:11","Grid fluctuation, site went down because Gen failed to start du=
e to grid bad voltage No Rcp // He bypassed  grid and started Gen manually"=
,"Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation, site went down because Gen failed to sta=
rt due to grid bad voltage No Rcp // He bypassed  grid and started Gen manu=
ally","cedric.tiani@matech-cameroun.com","265","01-08-2025 15:33:11","MATEC=
H CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0005601762","Nsi=
meyong Terre Rouge","","01-08-2025 15:26:49","01-08-2025 15:25:38","01-08-2=
025 15:27:04","Grid outage, Site went down before Gen start due to poor bac=
kup/ // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup/ // Grid return","cedric.tiani@matech-cameroun.c=
om","72","01-08-2025 15:26:49","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005601755","B=
arriere","","01-08-2025 15:25:53","01-08-2025 15:24:43","01-08-2025 15:26:4=
3","Active // No power issue on site Ubay: 53.5V site on Gen .TX Fme Fluber=
t (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue on site Ubay: 53.5V site on Gen .TX Fme Flubert (654266068/Hua=
wei) is informed","gerard.tchangoue@matech-cameroun.com","73","01-08-2025 1=
5:25:53","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005601737","A=
fanoya","","01-08-2025 15:18:45","01-08-2025 15:11:36","01-08-2025 18:12:32=
","Site went down because Gen started and stopped due AVR faulty // He repl=
aced AVR and started Gen manually","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - AVR","Site went down because Gen started and stopp=
ed due AVR faulty // He replaced AVR and started Gen manually","gerard.tcha=
ngoue@matech-cameroun.com","431","01-08-2025 15:18:45","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005601706","Mon=
tee-Jouvence-II","","01-08-2025 15:11:27","01-08-2025 15:06:04","01-08-2025=
 15:13:27","Grid outage, Site went down before Gen start due to poor backup=
/ // Gen automatically started","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup/ // Gen automatically started","cedr=
ic.tiani@matech-cameroun.com","456","01-08-2025 15:11:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005601696","Nsam esc=
ale LP","","01-08-2025 15:09:19","01-08-2025 15:06:26","01-08-2025 15:12:24=
","Cascaded Incident from TTO5794209","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Gen Started Automatically","cedric.tiani@matech-camer=
oun.com","262664","01-08-2025 15:09:19","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005601694","Nsa=
m Sofavinc","IHS_YND_732","01-08-2025 15:08:41","01-08-2025 15:06:26","01-0=
8-2025 15:12:24","Grid Outage, Site went down before Gen start due to poor =
backup // Gen Started Automatically","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site wen=
t down before Gen start due to poor backup // Gen Started Automatically","c=
edric.tiani@matech-cameroun.com","136","01-08-2025 15:08:41","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005601689","M=
arche Odza","","01-08-2025 15:08:08","01-08-2025 15:07:01","01-08-2025 15:0=
9:34","Grid fluctuation,site went down due to poor batterie backup// Grid s=
tabilisation","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid fluctuation,site went down due to poor =
batterie backup// Grid stabilisation","gerard.tchangoue@matech-cameroun.com=
","69","01-08-2025 15:08:08","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005601545","Sim=
e Building","","01-08-2025 14:32:43","01-08-2025 14:30:36","01-08-2025 14:3=
8:43","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","cedric.tiani=
@matech-cameroun.com","128","01-08-2025 14:32:43","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005601512","Nsi=
malen MTN","","01-08-2025 14:24:46","01-08-2025 14:20:38","01-08-2025 15:04=
:41","Site went down due to 01/03  rectifier faulty on site //He need to ad=
d 01 and site on Gen","Albran Byorel","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down due to 01/03  rectifier faulty on si=
te //He need to add 01 and site on Gen","gerard.tchangoue@matech-cameroun.c=
om","249","01-08-2025 14:24:46","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005601338","MBA=
LNGONG LYCEE","","01-08-2025 13:52:48","01-08-2025 13:47:39","02-08-2025 07=
:22:19","Grid outage,Site went down due Gen overload(9kva, 130A) SS IHS Fel=
ix Zambe is informed and confirmed//Grid return","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//G=
rid return","franck.nkomot@matech-cameroun.com","311","01-08-2025 13:52:48"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005601202","Angongo"=
,"","01-08-2025 13:23:04","01-08-2025 13:15:08","01-08-2025 14:19:02","Casc=
aded Incident from TTO5793646","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because Gen started and st=
opped with ""low oil pressure"" alarm// He added oil and started Gen manual=
y","edwige.kapawo@matech-cameroun.com","269265","01-08-2025 13:23:04","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0005601195","F=
ebe Village","","01-08-2025 13:20:37","01-08-2025 13:19:59","01-08-2025 13:=
25:06","Grid outage, site went down because Gen failed to start due to PWC =
overload//Site stabilised","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Grid outage, site went down because=
 Gen failed to start due to PWC overload//Site stabilised","edwige.kapawo@m=
atech-cameroun.com","39","01-08-2025 13:20:37","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0005601172","Ebe=
ba","IHS_YND_335","01-08-2025 13:14:14","01-08-2025 13:12:08","01-08-2025 1=
4:19:02","Site went down because Gen started and stopped with ""low oil pre=
ssure"" alarm// He added oil and started Gen manualy","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down =
because Gen started and stopped with ""low oil pressure"" alarm// He added =
oil and started Gen manualy","edwige.kapawo@matech-cameroun.com","127","01-=
08-2025 13:14:14","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005600095","Eki=
e sud","","01-08-2025 10:04:26","01-08-2025 10:00:56","01-08-2025 10:20:09"=
,"Grid outage, Site went because Gen ran until fuel shortage//Refueling Don=
e","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid o=
utage, Site went because Gen ran until fuel shortage//Refueling Done","fran=
ck.nkomot@matech-cameroun.com","211","01-08-2025 10:04:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005599829","ELOUMDEM=
 CARRIERE 2","","01-08-2025 09:19:56","01-08-2025 09:17:35","01-08-2025 09:=
21:35","Cascaded Incident from TTO5792178","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","franck.nk=
omot@matech-cameroun.com","262109","01-08-2025 09:19:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005599828","Eto koss=
 Yde","","01-08-2025 09:19:56","01-08-2025 09:17:35","01-08-2025 09:21:35",=
"Cascaded Incident from TTO5792178","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","franck.nkomot@ma=
tech-cameroun.com","262108","01-08-2025 09:19:56","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005599808","B=
arriere","","01-08-2025 09:17:40","01-08-2025 09:15:30","01-08-2025 10:48:3=
3","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed // He reduced load","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // He reduced lo=
ad","edwige.kapawo@matech-cameroun.com","133","01-08-2025 09:17:40","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005599803","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","01-08-2025 09:16:45","01-08-2025 09:=
15:35","01-08-2025 09:21:35","Grid outage, Site went down before Gen start =
due to poor backup // Gen started automatically","Fanda Brice","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
, Site went down before Gen start due to poor backup // Gen started automat=
ically","edwige.kapawo@matech-cameroun.com","73","01-08-2025 09:16:45","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005599697","M=
vog-Ada_OCM","","01-08-2025 08:54:35","01-08-2025 08:53:26","01-08-2025 11:=
17:52","Grid only on site, No space on site to deploy MDGE // Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 only on site, No space on site to deploy MDGE // Grid return","edwige.kapa=
wo@matech-cameroun.com","71","01-08-2025 08:54:35","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005599474","N=
kolondom","","01-08-2025 07:51:19","01-08-2025 07:49:10","01-08-2025 08:05:=
16","Grid outage.gen failed to start due to battery GE disconned causing by=
 battery  terminals not well tighted//Grid return","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage.g=
en failed to start due to battery GE disconned causing by battery  terminal=
s not well tighted//Grid return","edwige.kapawo@matech-cameroun.com","131",=
"01-08-2025 07:51:19","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005599468","Eto=
udi2","","01-08-2025 07:49:21","01-08-2025 07:46:11","01-08-2025 08:14:49",=
"Site went down because Gen failed to start due to Grid bad voltage // He b=
ypass the Grid and Gen manually Started","Delor Telezing","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Site went down bec=
ause Gen failed to start due to Grid bad voltage // He bypass the Grid and =
Gen manually Started","franck.nkomot@matech-cameroun.com","192","01-08-2025=
 07:49:21","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005599344","N=
kolondom","","01-08-2025 07:23:44","01-08-2025 07:18:33","01-08-2025 07:32:=
47","Grid outage.gen failed to start due to battery GE disconned causing by=
 battery  terminals not well tighted//Grid return","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage.g=
en failed to start due to battery GE disconned causing by battery  terminal=
s not well tighted//Grid return","edwige.kapawo@matech-cameroun.com","314",=
"01-08-2025 07:23:44","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005599339","MEF=
OU ASSI","","01-08-2025 07:22:32","01-08-2025 07:19:08","01-08-2025 07:40:2=
1","Grid outage, Site went down before Gen start due to poor backup // Gen =
started automatically","Fanda Brice","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Gen started automatically","franck.nkomot@mat=
ech-cameroun.com","207","01-08-2025 07:22:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005599270","Eto koss=
 Yde","","01-08-2025 07:00:42","01-08-2025 06:58:45","01-08-2025 07:06:45",=
"Cascaded Incident from TTO5791571","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","franck.nkomot@ma=
tech-cameroun.com","117","01-08-2025 07:00:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005599271","ELOUMDEM=
 CARRIERE 2","","01-08-2025 07:00:42","01-08-2025 06:58:45","01-08-2025 07:=
06:45","Cascaded Incident from TTO5791571","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","franck.nk=
omot@matech-cameroun.com","117","01-08-2025 07:00:42","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005599269","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","01-08-2025 06:59:55","01-08-2025 06:58=
:45","01-08-2025 07:06:45","Grid outage, Site went down before Gen start du=
e to poor backup // Gen started automatically","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","franck.nkomot@matech-cameroun.com","73","01-08-2025 06:59:55","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005599122","A=
wae Escalier","","01-08-2025 05:59:38","01-08-2025 05:57:06","01-08-2025 07=
:02:39","Grid outage, site went down due to gen Overload(20KVA, 300A) // He=
 reduced LOAD, SITE on Gen","Albran Byorel","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, site went down due to gen Overload=
(20KVA, 300A) // He reduced LOAD, SITE on Gen","vanel.mbiada@matech-camerou=
n.com","154","01-08-2025 05:59:38","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005599121","Eki=
e sud","","01-08-2025 05:59:11","01-08-2025 05:57:52","01-08-2025 06:13:36"=
,"Grid outage,site went down because Gen failed to start due to Gen battery=
 cover not well tightened//He tightened it and started the Gen manually","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Bat=
tery","Grid outage,site went down because Gen failed to start due to Gen ba=
ttery cover not well tightened//He tightened it and started the Gen manuall=
y","cedric.tiani@matech-cameroun.com","80","01-08-2025 05:59:11","MATECH CM=
R"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005598897","Eki=
e sud","","01-08-2025 04:11:46","01-08-2025 04:06:25","01-08-2025 05:42:56"=
,"Grid outage,site went down because Gen failed to start due to Gen  batter=
y cover not well tightened//He tightened it and started the Gen manually","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Ba=
ttery","Grid outage,site went down because Gen failed to start due to Gen  =
battery cover not well tightened//He tightened it and started the Gen manua=
lly","vanel.mbiada@matech-cameroun.com","3535","01-08-2025 04:11:46","MATEC=
H CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0005598533","NYA=
NON/DEMBO","","01-08-2025 01:28:01","01-08-2025 01:23:51","01-08-2025 06:22=
:05","Site went down due to relay 12v faulry//We replace relay 12 v and gen=
 manually started ","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Relay Faulty","Site went down due to relay 12v faulry//=
We replace relay 12 v and gen manually started ","cedric.tiani@matech-camer=
oun.com","251","01-08-2025 01:28:01","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005598521","Evo=
doula MTN","","01-08-2025 01:24:06","01-08-2025 01:21:58","01-08-2025 02:51=
:06","Grid outage, site went down because Gen failed to start due to genera=
tor rack faulty which is dysfunctionning solenoid //Gen manually started","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - S=
olenoid Coil","Grid outage, site went down because Gen failed to start due =
to generator rack faulty which is dysfunctionning solenoid //Gen manually s=
tarted","cedric.tiani@matech-cameroun.com","129","01-08-2025 01:24:06","MAT=
ECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0005598447","Nko=
londom","","01-08-2025 01:02:10","01-08-2025 00:56:30","01-08-2025 01:12:16=
","Grid outage, Site went down because Gen failed to start due to ATS dysfu=
nction// Grid return","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","ATS-AMF Issue","Grid outage, Site went down because Gen failed t=
o start due to ATS dysfunction// Grid return","cedric.tiani@matech-cameroun=
.com","342","01-08-2025 01:02:10","MATECH CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0005597923","NYA=
NON/DEMBO","","31-07-2025 22:22:10","31-07-2025 22:20:06","01-08-2025 00:15=
:45","Grid outage .gen failed to start due to priming pump faulty//We repla=
ce priming pump and gen manually started ","TIENTCHEU NZETCHIEU GAEL","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Fuel Lifting Pump Faulty","Grid =
outage .gen failed to start due to priming pump faulty//We replace priming =
pump and gen manually started ","loic.noumsi@matech-cameroun.com","125","31=
-07-2025 22:22:10","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005597909","Feb=
e Village","","31-07-2025 22:19:13","31-07-2025 22:13:07","31-07-2025 23:38=
:54","Grid outage, site went down because Gen failed to start due to PWC ov=
erload//Site stabilised","Mboua Thierry","Equipment Repair","Passive","Rect=
ifier","Rectifier Module Overloaded","Grid outage, site went down because G=
en failed to start due to PWC overload//Site stabilised","loic.noumsi@matec=
h-cameroun.com","367","31-07-2025 22:19:13","MATECH CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0005597836","F=
ebe Village","","31-07-2025 22:04:22","31-07-2025 21:59:06","31-07-2025 21:=
59:53","Grid outage, site went down because Gen failed to start due to PWC =
overload // Site stabilised","Mboua Thierry","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Grid outage, site went down becau=
se Gen failed to start due to PWC overload // Site stabilised","gaelle.njio=
fack@matech-cameroun.com","318","31-07-2025 22:04:22","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005597737","Eto=
ug ebe Carrefour","","31-07-2025 21:43:53","31-07-2025 21:35:47","31-07-202=
5 21:56:31","Grid outage site went down before gen started due to poor batt=
ery backup // Grid stabilised","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before gen started due to poor battery backup // Grid stabilised","loic.no=
umsi@matech-cameroun.com","487","31-07-2025 21:43:53","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0005597704","SAA=
 2","","31-07-2025 21:34:27","31-07-2025 21:33:19","31-07-2025 21:35:34","N=
o power issue on site Ubay 52.9V site on Grid,  TX FME Gr=E9goire // 654547=
479 from Huawei is informed.","Parker Tchoup","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubay 52.9V site on Grid,  TX FME Gr=E9goire // 654547479 from Huawei =
is informed.","loic.noumsi@matech-cameroun.com","69","31-07-2025 21:34:27",=
"MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005597581","Feb=
e Village","","31-07-2025 21:11:58","31-07-2025 21:10:50","31-07-2025 21:38=
:26","	Grid outage, site went down because Gen failed to start due to PWC o=
verload // Site stabilised","Mboua Thierry","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","	Grid outage, site went down becau=
se Gen failed to start due to PWC overload // Site stabilised","loic.noumsi=
@matech-cameroun.com","70","31-07-2025 21:11:58","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005597533","Bit=
eng-Maetur","","31-07-2025 21:03:48","31-07-2025 21:02:42","31-07-2025 21:5=
6:22","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","loic.no=
umsi@matech-cameroun.com","68","31-07-2025 21:03:48","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005597520","Eto=
ug ebe Carrefour","","31-07-2025 21:00:39","31-07-2025 20:57:25","31-07-202=
5 21:14:10","Grid outage site went down before gen started due to poor batt=
ery backup // Grid stabilised","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before gen started due to poor battery backup // Grid stabilised","loic.no=
umsi@matech-cameroun.com","196","31-07-2025 21:00:39","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005597400","M=
arche Odza","","31-07-2025 20:40:47","31-07-2025 20:38:38","31-07-2025 20:4=
7:16","Grid fluctuation,site went down due to poor batterie backup// Grid s=
tabilisation","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid fluctuation,site went down due to poor =
batterie backup// Grid stabilisation","gaelle.njiofack@matech-cameroun.com"=
,"131","31-07-2025 20:40:47","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005597328","Hop=
ital Central","","31-07-2025 20:26:04","31-07-2025 20:20:56","31-07-2025 20=
:21:31","(Unstable)Site went down due to 03/05 rectifiers faulty // Site st=
abilised","","Equipment Repair","Passive","Rectifier","Rectifier Module","(=
Unstable)Site went down due to 03/05 rectifiers faulty // Site stabilised",=
"loic.noumsi@matech-cameroun.com","309","31-07-2025 20:26:04","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005597277","Feb=
e Village","","31-07-2025 20:16:09","31-07-2025 20:14:04","31-07-2025 20:22=
:04","Grid outage, site went down because Gen failed to start due to PWC ov=
erload // Site stabilised","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Grid outage, site went down because=
 Gen failed to start due to PWC overload // Site stabilised","loic.noumsi@m=
atech-cameroun.com","127","31-07-2025 20:16:09","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005597226","Eto=
ug ebe Carrefour","","31-07-2025 20:14:52","31-07-2025 20:12:47","31-07-202=
5 20:18:27","Grid outage site went down before gen started due to poor batt=
ery backup // Grid stabilised","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before gen started due to poor battery backup // Grid stabilised","loic.no=
umsi@matech-cameroun.com","126","31-07-2025 20:14:52","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005597073","M=
arche Odza","","31-07-2025 20:02:40","31-07-2025 20:00:33","31-07-2025 20:0=
9:11","Grid fluctuation,site went down due to poor batterie backup// Grid s=
tabilisation","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid fluctuation,site went down due to poor =
batterie backup// Grid stabilisation","gaelle.njiofack@matech-cameroun.com"=
,"129","31-07-2025 20:02:40","MATECH CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0005595631","E=
BOM","","31-07-2025 18:29:49","31-07-2025 18:25:42","31-07-2025 19:10:26","=
Active//No power issue on site U=3D54.6V. site on Grid  Henry//699949693 of=
 huawei is informed.","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue o=
n site U=3D54.6V. site on Grid  Henry//699949693 of huawei is informed.","g=
aelle.njiofack@matech-cameroun.com","248","31-07-2025 18:29:49","MATECH CMR=
"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0005595536","N=
kolbisson usine des eaux","","31-07-2025 18:11:05","31-07-2025 18:08:57","3=
1-07-2025 18:49:15","Grid outage, site went down because gen failed to star=
t due to grid bad voltage and no Rcp // He bypassed Grid and started Gen ma=
nually","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Grid outage, site went down because gen f=
ailed to start due to grid bad voltage and no Rcp // He bypassed Grid and s=
tarted Gen manually","loic.noumsi@matech-cameroun.com","129","31-07-2025 18=
:11:05","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005595488","E=
toudi","","31-07-2025 18:07:11","31-07-2025 13:24:51","31-07-2025 14:06:13"=
,"Backtracking// Grid outage,site went down due to gen overload(20kva,300 A=
) SS HIS Bernard Atangana is informed // Site stabilised","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Backtracking// =
Grid outage,site went down due to gen overload(20kva,300 A) SS HIS Bernard =
Atangana is informed // Site stabilised","gaelle.njiofack@matech-cameroun.c=
om","16941","31-07-2025 18:07:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0005595298","Nkolkoum=
ou OCM","","31-07-2025 17:40:40","31-07-2025 17:38:37","31-07-2025 17:42:07=
","Cascaded Incident from TTO5787221","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down because gen failed to start due to grid bad voltage and no Rcp // He=
 bypassed Grid and started Gen manually","loic.noumsi@matech-cameroun.com",=
"274951","31-07-2025 17:40:40","MATECH CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0005595292","Nko=
lbisson usine des eaux","IHS_YND_712","31-07-2025 17:39:42","31-07-2025 17:=
38:37","31-07-2025 17:42:07","Grid outage, site went down because gen faile=
d to start due to grid bad voltage and no Rcp // He bypassed Grid and start=
ed Gen manually","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid outage, site went down beca=
use gen failed to start due to grid bad voltage and no Rcp // He bypassed G=
rid and started Gen manually","loic.noumsi@matech-cameroun.com","66","31-07=
-2025 17:39:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005595231","Etoudi 2=
","","31-07-2025 17:31:24","31-07-2025 17:28:47","31-07-2025 17:30:35","Cas=
caded Incident from TTO5787151","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D52=
.9V, TX fme Armand Nguetsa /699949553 from Huawei is informed","loic.noumsi=
@matech-cameroun.com","268636","31-07-2025 17:31:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005595230","ETOUDI C=
HAPELLE","","31-07-2025 17:31:24","31-07-2025 17:28:47","31-07-2025 17:30:3=
5","Cascaded Incident from TTO5787151","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on grid with =
U=3D52.9V, TX fme Armand Nguetsa /699949553 from Huawei is informed","loic.=
noumsi@matech-cameroun.com","268635","31-07-2025 17:31:24","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005595226","Aba=
ttoir","IHS_YND_694, IHS_YND_211","31-07-2025 17:30:52","31-07-2025 17:28:4=
7","31-07-2025 17:30:35","No power issue site on grid with U=3D52.9V, TX fm=
e Armand Nguetsa /699949553 from Huawei is informed","Fabrice Pouakam","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue site on grid with U=3D52.9V, TX fme Armand Nguetsa /=
699949553 from Huawei is informed","loic.noumsi@matech-cameroun.com","127",=
"31-07-2025 17:30:52","MATECH CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0005595201","Bri=
quetterie","","31-07-2025 17:26:47","31-07-2025 17:24:42","02-08-2025 14:35=
:54","Grid outage, no space to deploy a mobile gen // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 no space to deploy a mobile gen // Grid return","loic.noumsi@matech-camero=
un.com","126","31-07-2025 17:26:47","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0005595121","B=
riqueterie","","31-07-2025 17:16:59","31-07-2025 17:06:59","04-08-2025 14:2=
5:47","Grid Only SITE, No space to deploy MDGE // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only SITE, =
No space to deploy MDGE // Grid return","gaelle.njiofack@matech-cameroun.co=
m","602","31-07-2025 17:16:59","MATECH CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0005595074","E=
lobi Mokolo","","31-07-2025 17:07:27","31-07-2025 17:06:20","31-07-2025 17:=
32:17","Active//No power issue on site, site on Grid with U=3D53,5V. The TX=
 FME Brice (650214096) from huawei is informed.","Mboua Thierry","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site, site on Grid with U=3D53,5V. The TX FME B=
rice (650214096) from huawei is informed.","gaelle.njiofack@matech-cameroun=
.com","68","31-07-2025 17:07:27","MATECH CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0005594849","Bri=
quetterie","","31-07-2025 16:25:39","31-07-2025 16:10:34","31-07-2025 16:55=
:56","Grid outage, no space to deploy a mobile gen // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 no space to deploy a mobile gen // Grid return","loic.noumsi@matech-camero=
un.com","907","31-07-2025 16:25:39","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0005594845","B=
riqueterie","","31-07-2025 16:24:49","31-07-2025 16:19:44","31-07-2025 16:5=
5:34","Grid Only SITE, No space to deploy MDGE // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only SITE, =
No space to deploy MDGE // Grid return","loic.noumsi@matech-cameroun.com","=
306","31-07-2025 16:24:49","MATECH CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0005594841","E=
lobi Mokolo","","31-07-2025 16:23:53","31-07-2025 16:19:48","31-07-2025 16:=
20:16","Active//No power issue on site, site on Grid with U=3D53,5V. The TX=
 FME Brice (650214096) from huawei is informed.","Mboua Thierry","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site, site on Grid with U=3D53,5V. The TX FME B=
rice (650214096) from huawei is informed.","loic.noumsi@matech-cameroun.com=
","246","31-07-2025 16:23:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005594236","Nsam esc=
ale LP","","31-07-2025 14:56:46","31-07-2025 14:52:18","31-07-2025 14:59:28=
","Cascaded Incident from TTO5786074","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Site stabilised","loic.noumsi@matech-cameroun.com","2=
63492","31-07-2025 14:56:46","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005594233","Nsa=
m Sofavinc","IHS_YND_732","31-07-2025 14:56:22","31-07-2025 14:52:18","31-0=
7-2025 14:59:28","Grid Outage, Site went down before Gen start due to poor =
backup // Site stabilised","MINKA NICOLAS","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid Outage, Site went down bef=
ore Gen start due to poor backup // Site stabilised","loic.noumsi@matech-ca=
meroun.com","245","31-07-2025 14:56:22","MATECH CMR"
"Closed Complete","Site Down","T1665","IHS_YND_014","NOCINC0005593989","ELI=
g-Essono","","31-07-2025 14:16:46","31-07-2025 14:14:39","31-07-2025 15:44:=
13","Grid outage, site went down because Gen started and stopped due to Gri=
d bad voltage (lack of 01 phase) // He did bridge on the good phases, site =
on GRID","Delor Telezing","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","Grid outage, site went down because Gen started an=
d stopped due to Grid bad voltage (lack of 01 phase) // He did bridge on th=
e good phases, site on GRID","edwige.kapawo@matech-cameroun.com","128","31-=
07-2025 14:16:46","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0005593836","BAT=
A Mokolo OCM","","31-07-2025 13:51:51","31-07-2025 13:50:44","05-08-2025 16=
:39:08","fme report that Grid Only, No space to deploy MDGE awaiting // gri=
d return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Is=
sue","fme report that Grid Only, No space to deploy MDGE awaiting // grid r=
eturn","edwige.kapawo@matech-cameroun.com","69","31-07-2025 13:51:51","MATE=
CH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005593583","NYO=
M FACE MAETUR","","31-07-2025 13:15:23","31-07-2025 13:14:16","31-07-2025 1=
3:15:10","Site went down because Gen failed to start due to Grid bad voltag=
e // Grid stabilised","Fabrice Pouakam","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","Site went down because Gen failed to=
 start due to Grid bad voltage // Grid stabilised","edwige.kapawo@matech-ca=
meroun.com","69","31-07-2025 13:15:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0005593520","Abang","=
","31-07-2025 13:07:21","31-07-2025 13:02:53","31-07-2025 14:17:08","Cascad=
ed Incident from TTO5785295","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active // No power issue on site Ubay =3D=
 53.1V Site on Grid. TX FME Henri (699949693/Huawei) is on site for works",=
"gerard.tchangoue@matech-cameroun.com","269915","31-07-2025 13:07:21","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0005593503","N=
kolangaa","IHS_YND_290","31-07-2025 13:05:58","31-07-2025 13:02:53","31-07-=
2025 14:17:08","Active // No power issue on site Ubay =3D 53.1V Site on Gri=
d. TX FME Henri (699949693/Huawei) is on site for works","Mba Lazare Herve"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active // No power issue on site Ubay =3D 53.1V Site on Grid. =
TX FME Henri (699949693/Huawei) is on site for works","gerard.tchangoue@mat=
ech-cameroun.com","186","31-07-2025 13:05:58","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005593462","N=
kozoa","","31-07-2025 12:58:00","31-07-2025 12:56:53","31-07-2025 13:06:34"=
,"Grid outage, site went down because Gen started and stopped due to alarm =
""overcurrent"" // He reset DG card and started gen manually","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage, site went down because Gen started and stopped due to alarm ""overcu=
rrent"" // He reset DG card and started gen manually","gerard.tchangoue@mat=
ech-cameroun.com","69","31-07-2025 12:58:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005593446","Nsam esc=
ale LP","","31-07-2025 12:56:51","31-07-2025 12:55:13","31-07-2025 13:01:36=
","Cascaded Incident from TTO5785234","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, Site went down before Gen start =
due to poor backup/ // Gen automatically started","edwige.kapawo@matech-cam=
eroun.com","263434","31-07-2025 12:56:51","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005593444","Nsa=
m Sofavinc","IHS_YND_732","31-07-2025 12:56:23","31-07-2025 12:55:13","31-0=
7-2025 13:01:36","Grid outage, Site went down before Gen start due to poor =
backup/ // Gen automatically started","MINKA NICOLAS","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site we=
nt down before Gen start due to poor backup/ // Gen automatically started",=
"edwige.kapawo@matech-cameroun.com","71","31-07-2025 12:56:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005593137","ELOUMDEM=
 CARRIERE 2","","31-07-2025 12:08:49","31-07-2025 12:04:37","31-07-2025 12:=
05:37","Cascaded Incident from TTO5784882","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid returned","edwige.kapawo@matech-=
cameroun.com","266431","31-07-2025 12:08:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005593136","Eto koss=
 Yde","","31-07-2025 12:08:48","31-07-2025 12:04:37","31-07-2025 12:05:37",=
"Cascaded Incident from TTO5784882","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Grid returned","edwige.kapawo@matech-camerou=
n.com","266431","31-07-2025 12:08:48","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005593124","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","31-07-2025 12:04:52","31-07-2025 12:04=
:37","31-07-2025 12:10:47","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","Fanda Brice","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Grid returned","gerard.tchangoue@=
matech-cameroun.com","335","31-07-2025 12:04:52","MATECH CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0005592916","Ngo=
ulmekong-Nord","","31-07-2025 11:34:33","31-07-2025 11:33:25","31-07-2025 1=
1:40:04","Site went down due to PSC3 Controller dysfunctionning // Site sta=
bilized","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Site went down due to PSC3 Controller dysfunctionning // Site=
 stabilized","edwige.kapawo@matech-cameroun.com","69","31-07-2025 11:34:33"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005592321","A=
wae Escalier","","31-07-2025 09:39:22","31-07-2025 09:32:16","31-07-2025 10=
:11:38","Grid outage, site went down due to gen Overload(20KVA, 300A) // He=
 reduced LOAD, SITE on Gen","Albran Byorel","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, site went down due to gen Overload=
(20KVA, 300A) // He reduced LOAD, SITE on Gen","gerard.tchangoue@matech-cam=
eroun.com","428","31-07-2025 09:39:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005592302","Angongo"=
,"","31-07-2025 09:36:58","31-07-2025 09:29:01","31-07-2025 09:48:35","Casc=
aded Incident from TTO5783972","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubaie =3D55,3V site o=
n Grid Fulbert(654266068) of huawei is informed","gerard.tchangoue@matech-c=
ameroun.com","261326","31-07-2025 09:36:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005592301","Mambine"=
,"","31-07-2025 09:36:58","31-07-2025 09:29:01","31-07-2025 09:48:35","Casc=
aded Incident from TTO5783972","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubaie =3D55,3V site o=
n Grid Fulbert(654266068) of huawei is informed","gerard.tchangoue@matech-c=
ameroun.com","261325","31-07-2025 09:36:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005592303","Nkongtoc=
k","","31-07-2025 09:36:58","31-07-2025 09:29:01","31-07-2025 09:48:35","Ca=
scaded Incident from TTO5783972","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site Ubaie =3D55,3V =
site on Grid Fulbert(654266068) of huawei is informed","gerard.tchangoue@ma=
tech-cameroun.com","261326","31-07-2025 09:36:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005592300","Ebeba","=
","31-07-2025 09:36:58","31-07-2025 09:29:01","31-07-2025 09:48:35","Cascad=
ed Incident from TTO5783972","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site Ubaie =3D55,3V site on =
Grid Fulbert(654266068) of huawei is informed","gerard.tchangoue@matech-cam=
eroun.com","261324","31-07-2025 09:36:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0005592299","Mbankomo=
 IHS","","31-07-2025 09:36:57","31-07-2025 09:29:01","31-07-2025 09:48:35",=
"Cascaded Incident from TTO5783972","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site Ubaie =3D55,3V s=
ite on Grid Fulbert(654266068) of huawei is informed","gerard.tchangoue@mat=
ech-cameroun.com","261324","31-07-2025 09:36:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0005592298","Sous Pre=
fecture","","31-07-2025 09:36:57","31-07-2025 09:29:01","31-07-2025 09:48:3=
5","Cascaded Incident from TTO5783972","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site Ubaie =3D55,3=
V site on Grid Fulbert(654266068) of huawei is informed","gerard.tchangoue@=
matech-cameroun.com","261323","31-07-2025 09:36:57","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0005592280","O=
KOA Peage","IHS_YND_314, IHS_YND_695, IHS_YND_339, IHS_YND_697, IHS_YND_350=
, IHS_YND_335, IHS_YND_349","31-07-2025 09:31:35","31-07-2025 09:29:01","31=
-07-2025 09:48:35","No power issue on site Ubaie =3D55,3V site on Grid Fulb=
ert(654266068) of huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site Ubaie =3D55,3V site on Grid Fulbert(654266068) of huawei is inf=
ormed","gerard.tchangoue@matech-cameroun.com","155","31-07-2025 09:31:35","=
MATECH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005592230","N=
omayos-IHS","","31-07-2025 09:20:13","31-07-2025 09:29:01","31-07-2025 09:4=
8:35","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue on site Ubaie =3D55,3V site on Grid Fulbert(6542660=
68) of huawei is informed","gerard.tchangoue@matech-cameroun.com","261323",=
"31-07-2025 09:20:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_393","NOCINC0005592224","Ezezang"=
,"","31-07-2025 09:19:29","31-07-2025 08:57:28","31-07-2025 08:58:28","Casc=
aded Incident from TTO5783803","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power Issue on Site, U=3D54.4V site on =
GEN -- TX FME Gregoire 654547479 of Huawei is informed	","christian.fonkou@=
ihstowers.com","270428","31-07-2025 09:19:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_051","NOCINC0005592223","Nyanon",=
"","31-07-2025 09:19:29","31-07-2025 08:57:28","31-07-2025 08:58:28","Casca=
ded Incident from TTO5783803","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","No Power Issue on Site, U=3D54.4=
V site on GEN -- TX FME Gregoire 654547479 of Huawei is informed	","christi=
an.fonkou@ihstowers.com","270435","31-07-2025 09:19:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005592219","SAA 2","=
","31-07-2025 09:19:28","31-07-2025 08:57:28","31-07-2025 08:58:28","Cascad=
ed Incident from TTO5783803","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power Issue on Site, U=3D54.4V site on GE=
N -- TX FME Gregoire 654547479 of Huawei is informed	","christian.fonkou@ih=
stowers.com","270431","31-07-2025 09:19:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0005592221","Monatele=
 MTN","","31-07-2025 09:19:28","31-07-2025 08:57:28","31-07-2025 08:58:28",=
"Cascaded Incident from TTO5783803","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No Power Issue on Site, U=3D54.4V sit=
e on GEN -- TX FME Gregoire 654547479 of Huawei is informed	","christian.fo=
nkou@ihstowers.com","270426","31-07-2025 09:19:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0005592213","Saa","",=
"31-07-2025 09:19:26","31-07-2025 08:57:28","31-07-2025 08:58:28","Cascaded=
 Incident from TTO5783803","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","No Power Issue on Site, U=3D54.4V site on GEN =
-- TX FME Gregoire 654547479 of Huawei is informed	","christian.fonkou@ihst=
owers.com","270435","31-07-2025 09:19:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0005592212","Okola OC=
M","","31-07-2025 09:19:26","31-07-2025 08:57:28","31-07-2025 08:58:28","Ca=
scaded Incident from TTO5783803","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Active","Cascade Active","Cascade Active","No Power Issue on Site, U=3D5=
4.4V site on GEN -- TX FME Gregoire 654547479 of Huawei is informed	","chri=
stian.fonkou@ihstowers.com","270429","31-07-2025 09:19:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0005592211","Talla Mo=
natele","","31-07-2025 09:19:25","31-07-2025 08:57:28","31-07-2025 08:58:28=
","Cascaded Incident from TTO5783803","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No Power Issue on Site, U=3D54.4V s=
ite on GEN -- TX FME Gregoire 654547479 of Huawei is informed	","christian.=
fonkou@ihstowers.com","270429","31-07-2025 09:19:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0005592202","Monatele=
","","31-07-2025 09:19:23","31-07-2025 08:57:28","31-07-2025 08:58:28","Cas=
caded Incident from TTO5783803","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power Issue on Site, U=3D54.4V site on=
 GEN -- TX FME Gregoire 654547479 of Huawei is informed	","christian.fonkou=
@ihstowers.com","270431","31-07-2025 09:19:23","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005591785","M=
imboman-Ecole","","31-07-2025 07:37:29","31-07-2025 07:32:20","31-07-2025 0=
9:08:31","Site went down  because FME was on site with IHS for PM (SWAP of =
PWC) // End of work","Mba Lazare Herve","Installation Activity","Passive","=
Planned Activity","Installation Activity","Site went down  because FME was =
on site with IHS for PM (SWAP of PWC) // End of work","gerard.tchangoue@mat=
ech-cameroun.com","310","31-07-2025 07:37:29","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005591643","Bit=
eng-Maetur","","31-07-2025 06:58:03","31-07-2025 06:54:56","31-07-2025 07:3=
7:17","Site went down because CB  tripped in PWC who feeds equipments MTN d=
ue to load increase// CB rearmed","Mba Lazare Herve","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went d=
own because CB  tripped in PWC who feeds equipments MTN due to load increas=
e// CB rearmed","edwige.kapawo@matech-cameroun.com","189","31-07-2025 06:58=
:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005591528","Melen Ba=
'aba","","31-07-2025 06:23:20","30-07-2025 20:32:09","31-07-2025 06:23:31",=
"No power issue, site is on Gen with Ubaie: 54.3V, FME TX Julien (693095849=
) from Huawei is informed.","Siligap Boris","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, sit=
e is on Gen with Ubaie: 54.3V, FME TX Julien (693095849) from Huawei is inf=
ormed.","gerard.tchangoue@matech-cameroun.com","35473","31-07-2025 06:23:20=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005591441","Ngoum","=
","31-07-2025 05:49:29","31-07-2025 05:37:07","31-07-2025 06:47:02","Cascad=
ed Incident from TTO5783068","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","GEN overload // Load reduced ","stephane.=
nkamwa@ihstowers.com","268123","31-07-2025 05:49:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005591443","Ngouetou=
","","31-07-2025 05:49:29","31-07-2025 05:37:07","31-07-2025 06:47:02","Cas=
caded Incident from TTO5783068","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","GEN overload // Load reduced ","stepha=
ne.nkamwa@ihstowers.com","268121","31-07-2025 05:49:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005591444","MBIMBIM"=
,"","31-07-2025 05:49:29","31-07-2025 05:37:07","31-07-2025 06:47:02","Casc=
aded Incident from TTO5783068","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","GEN overload // Load reduced ","stephan=
e.nkamwa@ihstowers.com","268122","31-07-2025 05:49:29","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005591431","OTE=
LE MTN","","31-07-2025 05:45:03","31-07-2025 05:40:56","31-07-2025 20:25:14=
","Grid outage,Site went down because Gen failed to start due to Generator =
faulty//Grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Generator Faulty","Grid outage,Site went down because Gen failed to=
 start due to Generator faulty//Grid return","vanel.mbiada@matech-cameroun.=
com","248","31-07-2025 05:45:03","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005591388","ODZ=
A BORNE 10","","31-07-2025 05:28:07","31-07-2025 05:26:56","31-07-2025 12:2=
0:45","Grid outage, Site went down due to Gen overload (12.5 kva, 180A) // =
Grid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down due to Gen overload (12.5 kva, 180=
A) // Grid return","vanel.mbiada@matech-cameroun.com","72","31-07-2025 05:2=
8:07","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005591385","N=
kolondom","","31-07-2025 05:27:15","31-07-2025 05:26:08","31-07-2025 06:15:=
22","Grid outage, Site went down because Gen failed to start due to ATS dys=
function// He reset ATS and started Gen manualy","Fabrice Pouakam","Equipme=
nt Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site wen=
t down because Gen failed to start due to ATS dysfunction// He reset ATS an=
d started Gen manualy","gerard.tchangoue@matech-cameroun.com","70","31-07-2=
025 05:27:15","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005591094","Evo=
doula MTN","","31-07-2025 03:43:50","31-07-2025 03:37:35","31-07-2025 04:19=
:52","Grid outage, site went down because Gen failed to start due to genera=
tor rack faulty which is dysfunctionning solenoid //Gen manually started","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - S=
olenoid Coil","Grid outage, site went down because Gen failed to start due =
to generator rack faulty which is dysfunctionning solenoid //Gen manually s=
tarted","vanel.mbiada@matech-cameroun.com","376","31-07-2025 03:43:50","MAT=
ECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005590988","Oko=
la","","31-07-2025 03:05:34","31-07-2025 03:00:56","31-07-2025 03:02:16","G=
rid outage, site went down before Gen start due to poor battery backup // G=
en automatically started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down before Gen start due to poor battery backup // Gen automatically sta=
rted","vanel.mbiada@matech-cameroun.com","279","31-07-2025 03:05:34","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005590916","N=
kolfon Cimencam","","31-07-2025 02:32:48","31-07-2025 02:29:39","31-07-2025=
 02:33:23"," Site is impacted by Afanoya II (Not manage by IHS)","Hyemafo G=
ildas","Customer Equipment Failure","Active","Active Equipment Failure","Af=
fected by 3rd Party Site"," Site is impacted by Afanoya II (Not manage by I=
HS)","gerard.tchangoue@matech-cameroun.com","190","31-07-2025 02:32:48","MA=
TECH CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0005590784","Nko=
lo II New","","31-07-2025 01:27:14","31-07-2025 01:25:48","31-07-2025 02:24=
:06","Grid disjonction , site down because gen fails due to his battery dis=
charge // Grid CB rearmed","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid disjonction , site down=
 because gen fails due to his battery discharge // Grid CB rearmed","vanel.=
mbiada@matech-cameroun.com","87","31-07-2025 01:27:14","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005590359","Eto=
ug ebe Carrefour","","30-07-2025 23:07:10","30-07-2025 23:00:02","30-07-202=
5 23:18:57","Grid outage site went down before gen started due to poor batt=
ery backup//Grid return","Hyemafo Gildas","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage site went down befor=
e gen started due to poor battery backup//Grid return","vanel.mbiada@matech=
-cameroun.com","429","30-07-2025 23:07:10","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005590349","Feb=
e Village","","30-07-2025 23:04:27","30-07-2025 23:00:12","30-07-2025 23:04=
:34","Grid outage, site went down before gen start due to poor battery back=
up // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before gen =
start due to poor battery backup // Grid return","vanel.mbiada@matech-camer=
oun.com","257","30-07-2025 23:04:27","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005590256","S=
atcom","","30-07-2025 22:43:57","30-07-2025 22:40:49","30-07-2025 22:44:57"=
,"No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand ngu=
etsa(691144412) From huawei is informed.","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand nguetsa(6=
91144412) From huawei is informed.","gerard.tchangoue@matech-cameroun.com",=
"189","30-07-2025 22:43:57","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0005590215","Nlo=
ngkak","","30-07-2025 22:36:06","30-07-2025 22:32:53","30-07-2025 23:46:33"=
,"Grid fluctuation , Site went down because Gen started and stopped due to =
Grid bad voltage and poor backup// Grid stabilized","Delor Telezing","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation , Site went down because Gen started and stopped due to Grid bad =
voltage and poor backup// Grid stabilized","vanel.mbiada@matech-cameroun.co=
m","194","30-07-2025 22:36:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005590047","Bastos B=
ethesda","","30-07-2025 22:03:30","30-07-2025 21:50:54","30-07-2025 21:58:5=
7","Cascaded Incident from TTO5781422","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid, outage , No MG to deploy =
on site // Grid return","loic.noumsi@matech-cameroun.com","267249","30-07-2=
025 22:03:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0005590046","Meyong-M=
eyeme","","30-07-2025 22:03:30","30-07-2025 21:50:54","30-07-2025 21:58:57"=
,"Cascaded Incident from TTO5781422","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid, outage , No MG t=
o deploy on site // Grid return","loic.noumsi@matech-cameroun.com","267247"=
,"30-07-2025 22:03:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0005590048","Tsinga",=
"","30-07-2025 22:03:30","30-07-2025 21:50:54","30-07-2025 21:58:57","Casca=
ded Incident from TTO5781422","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid, outage , No MG to deploy on site /=
/ Grid return","loic.noumsi@matech-cameroun.com","267248","30-07-2025 22:03=
:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0005590044","Nkomkana=
","","30-07-2025 22:03:29","30-07-2025 21:50:54","30-07-2025 21:58:57","Cas=
caded Incident from TTO5781422","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid, outage , No MG to deploy on site // Grid retu=
rn","loic.noumsi@matech-cameroun.com","267249","30-07-2025 22:03:29","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005590042","Golf Qua=
ter","","30-07-2025 22:03:29","30-07-2025 21:50:54","30-07-2025 21:58:57","=
Cascaded Incident from TTO5781422","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid, outage , No MG to deploy on s=
ite // Grid return","loic.noumsi@matech-cameroun.com","267246","30-07-2025 =
22:03:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0005590043","Nkomkana=
 2","","30-07-2025 22:03:29","30-07-2025 21:50:54","30-07-2025 21:58:57","C=
ascaded Incident from TTO5781422","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid, outage , No MG to deploy on si=
te // Grid return","loic.noumsi@matech-cameroun.com","267247","30-07-2025 2=
2:03:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005590045","Bastos-N=
ylon","","30-07-2025 22:03:29","30-07-2025 21:50:54","30-07-2025 21:58:57",=
"Cascaded Incident from TTO5781422","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid, outage , No MG to deploy on =
site // Grid return","loic.noumsi@matech-cameroun.com","267248","30-07-2025=
 22:03:29","MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0005589968","C=
ite-Verte","IHS_YND_220, IHS_YND_138, IHS_YND_200, IHS_YND_126, IHS_YND_230=
, IHS_YND_563, IHS_YND_127","30-07-2025 21:53:06","30-07-2025 21:50:54","30=
-07-2025 21:58:57","Grid, outage , No MG to deploy on site // Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
, outage , No MG to deploy on site // Grid return","loic.noumsi@matech-came=
roun.com","134","30-07-2025 21:53:06","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005589853","NYO=
M FACE MAETUR","","30-07-2025 21:34:22","30-07-2025 21:31:09","30-07-2025 2=
1:37:14","Site went down because Gen failed to start due to Grid bad voltag=
e // Grid stabilised","Fabrice Pouakam","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","Site went down because Gen failed to=
 start due to Grid bad voltage // Grid stabilised","cedric.tiani@matech-cam=
eroun.com","195","30-07-2025 21:34:22","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005589767","Eto=
ug ebe Carrefour","","30-07-2025 21:20:06","30-07-2025 21:16:57","30-07-202=
5 21:22:22","Grid outage site went down before gen started due to poor batt=
ery backup//Grid return","Hyemafo Gildas","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage site went down befor=
e gen started due to poor battery backup//Grid return","loic.noumsi@matech-=
cameroun.com","190","30-07-2025 21:20:06","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005589763","Bit=
eng-Maetur","","30-07-2025 21:19:19","30-07-2025 21:15:11","30-07-2025 21:3=
5:44","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","loic.no=
umsi@matech-cameroun.com","250","30-07-2025 21:19:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005589468","Etoudi 2=
","","30-07-2025 20:32:01","30-07-2025 20:22:32","30-07-2025 20:34:39","Cas=
caded Incident from TTO5780873","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D52=
.9V Symphorien(691316854) from Huawei is informed","cedric.tiani@matech-cam=
eroun.com","265143","30-07-2025 20:32:01","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005589462","Aba=
ttoir","IHS_YND_694, IHS_YND_211","30-07-2025 20:30:19","30-07-2025 20:22:3=
2","30-07-2025 20:34:39","No power issue site on grid with U=3D52.9V Sympho=
rien(691316854) from Huawei is informed","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue site on grid with U=3D52.9V Symphorien(691316854) from Huawei is=
 informed","cedric.tiani@matech-cameroun.com","468","30-07-2025 20:30:19","=
MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005589416","Nko=
lbisson IITA LP","","30-07-2025 20:20:51","30-07-2025 20:17:41","30-07-2025=
 20:25:11","No power issue site on grid with U=3D53.8v Mohamadou(69114435) =
from Huawei is informed. Noticed that it is impacted by Nkolbisson 2 ocm no=
t managed by IHS","","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.8v=
 Mohamadou(69114435) from Huawei is informed. Noticed that it is impacted b=
y Nkolbisson 2 ocm not managed by IHS","cedric.tiani@matech-cameroun.com","=
191","30-07-2025 20:20:51","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005589391","Bit=
eng-Maetur","","30-07-2025 20:14:50","30-07-2025 20:13:42","30-07-2025 20:3=
0:07","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","loic.no=
umsi@matech-cameroun.com","69","30-07-2025 20:14:50","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0005589379","NKO=
MEKUI OCM","","30-07-2025 20:13:00","30-07-2025 20:10:43","30-07-2025 20:15=
:26","No power issue site on Gen with U=3D54.5 V The Tx Fme Mohamadou mouam=
 // 691144435 from Huawei is informed site impacted by Mbankolo camtel	","T=
IENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue site on Gen with U=3D54=
.5 V The Tx Fme Mohamadou mouam // 691144435 from Huawei is informed site i=
mpacted by Mbankolo camtel	","cedric.tiani@matech-cameroun.com","139","30-0=
7-2025 20:13:00","MATECH CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0005589363","Mel=
en Ba'aba","","30-07-2025 20:10:28","30-07-2025 20:06:03","30-07-2025 20:30=
:46","Grid outage, Site went down due to insufficiency of rectifiers(04) on=
 site  //  One  rectifier added  and site  left site on gen.","Siligap Bori=
s","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Grid outage, Site went down due to insufficiency of rectifiers(04) on site =
 //  One  rectifier added  and site  left site on gen.","cedric.tiani@matec=
h-cameroun.com","266","30-07-2025 20:10:28","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005589283","Eto=
ug ebe Carrefour","","30-07-2025 19:56:33","30-07-2025 19:53:23","30-07-202=
5 19:59:28","Grid outage site went down before gen started due to poor batt=
ery backup// Grid returned","Hyemafo Gildas","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage site went down be=
fore gen started due to poor battery backup// Grid returned","cedric.tiani@=
matech-cameroun.com","191","30-07-2025 19:56:33","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005588996","M=
elen Ba'aba","","30-07-2025 19:03:03","30-07-2025 19:00:55","30-07-2025 19:=
03:04","Grid outage, Site went down due to insufficiency of rectifiers on s=
ite // Site stabilised","Siligap Boris","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Grid outage, Site went down due to insufficiency =
of rectifiers on site // Site stabilised","loic.noumsi@matech-cameroun.com"=
,"130","30-07-2025 19:03:03","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005588898","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","30-07-2025 18:50:45","30-07-2025 18:=
49:38","30-07-2025 18:55:10","Grid outage,site went down due to PWC Huawei =
dysfunction//Site stabilised","Fanda Brice","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","Grid outage,site went down due to =
PWC Huawei dysfunction//Site stabilised","loic.noumsi@matech-cameroun.com",=
"70","30-07-2025 18:50:45","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005588890","Car=
refour Simbock","","30-07-2025 18:49:37","30-07-2025 18:47:23","30-07-2025 =
18:59:04","Site went down due to Gen overload (17kva //180A) SS HIS Felix Z=
ambe is informed and confirmed//Grid return","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen ove=
rload (17kva //180A) SS HIS Felix Zambe is informed and confirmed//Grid ret=
urn","cedric.tiani@matech-cameroun.com","135","30-07-2025 18:49:37","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005588847","M=
ontee-Jouvence-II","","30-07-2025 18:41:16","30-07-2025 18:40:10","30-07-20=
25 18:42:18","Grid outage, Site went down before Gen start due to poor back=
up/ // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup/ // Grid return","loic.noumsi@matech-cameroun.co=
m","68","30-07-2025 18:41:16","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005588820","Jou=
vence Mbenda","","30-07-2025 18:30:59","30-07-2025 18:22:51","30-07-2025 18=
:43:16","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and manually start the gen	","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid outage, site went down because gen start and stopped w=
ith high temp alarm // He added water and manually start the gen	","cedric.=
tiani@matech-cameroun.com","490","30-07-2025 18:30:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005588681","Eto koss=
 Yde","","30-07-2025 18:03:00","30-07-2025 18:00:09","30-07-2025 18:04:46",=
"Cascaded Incident from TTO5780015","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,site went down due to PW=
C Huawei dysfunction//Site on Gen","cedric.tiani@matech-cameroun.com","2665=
28","30-07-2025 18:03:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005588682","ELOUMDEM=
 CARRIERE 2","","30-07-2025 18:03:00","30-07-2025 18:00:09","30-07-2025 18:=
04:46","Cascaded Incident from TTO5780015","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage,site went down du=
e to PWC Huawei dysfunction//Site on Gen","cedric.tiani@matech-cameroun.com=
","266527","30-07-2025 18:03:00","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005588679","C=
omplexe-BEAC","","30-07-2025 18:02:44","30-07-2025 17:58:20","30-07-2025 18=
:02:10","Grid outage, Site went down before Gen start due to Poor battery b=
ackup // Grid returned","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to Poor battery backup // Grid returned","loic.noumsi@matech=
-cameroun.com","265","30-07-2025 18:02:44","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005588677","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","30-07-2025 18:02:22","30-07-2025 18:00=
:09","30-07-2025 18:04:46","Grid outage,site went down due to PWC Huawei dy=
sfunction//Site on Gen","Fanda Brice","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Grid outage,site went down due to PWC Hu=
awei dysfunction//Site on Gen","cedric.tiani@matech-cameroun.com","136","30=
-07-2025 18:02:22","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005588673","Mon=
tee-Jouvence-II","","30-07-2025 18:01:48","30-07-2025 17:59:32","30-07-2025=
 18:01:02","Grid outage, Site went down before Gen start due to poor backup=
/ // Gen automatically started","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup/ // Gen automatically started","cedr=
ic.tiani@matech-cameroun.com","137","30-07-2025 18:01:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005588670","Nsam esc=
ale LP","","30-07-2025 18:01:15","30-07-2025 17:57:41","30-07-2025 18:04:41=
","Cascaded Incident from TTO5780005","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, Site went down before Gen start =
due to poor backup/ // Gen automatically started","cedric.tiani@matech-came=
roun.com","266947","30-07-2025 18:01:15","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005588668","Nsa=
m Sofavinc","IHS_YND_732","30-07-2025 18:00:50","30-07-2025 17:57:41","30-0=
7-2025 18:04:41","Grid outage, Site went down before Gen start due to poor =
backup/ // Gen automatically started","MINKA NICOLAS","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site we=
nt down before Gen start due to poor backup/ // Gen automatically started",=
"cedric.tiani@matech-cameroun.com","190","30-07-2025 18:00:50","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005588664","SIM=
BOCK BONAMBAPE","","30-07-2025 18:00:08","30-07-2025 17:57:55","30-07-2025 =
18:01:53","Grid outage, Site went down before Gen start due to poor backup =
// Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Site stabilised","cedric.tiani@matech-camerou=
n.com","135","30-07-2025 18:00:08","MATECH CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0005588661","Nsi=
meyong Terre Rouge","","30-07-2025 17:59:34","30-07-2025 17:57:26","30-07-2=
025 18:01:00","Grid outage, Site went down before Gen start due to poor bac=
kup/ // Gen automatically started","MINKA NICOLAS","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup/ // Gen automatically started","ce=
dric.tiani@matech-cameroun.com","129","30-07-2025 17:59:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005588334","OLAMA","=
","30-07-2025 17:05:46","30-07-2025 17:00:30","30-07-2025 17:06:37","Cascad=
ed Incident from TTO5779636","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by I=
HS","cedric.tiani@matech-cameroun.com","263151","30-07-2025 17:05:46","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005588336","Mom","",=
"30-07-2025 17:05:46","30-07-2025 17:00:30","30-07-2025 17:06:37","Cascaded=
 Incident from TTO5779636","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by IHS=
","cedric.tiani@matech-cameroun.com","263150","30-07-2025 17:05:46","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005588335","Minka","=
","30-07-2025 17:05:46","30-07-2025 17:00:30","30-07-2025 17:06:37","Cascad=
ed Incident from TTO5779636","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by I=
HS","cedric.tiani@matech-cameroun.com","263150","30-07-2025 17:05:46","MATE=
CH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005588324","Ako=
no","IHS_YND_687, IHS_YND_371, IHS_YND_370","30-07-2025 17:04:45","30-07-20=
25 17:00:30","30-07-2025 17:06:37","Site impacted by T0169 Ngoumou not mana=
ge by IHS","Fanda Brice","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Site impacted by T0169 Ngoumou not man=
age by IHS","cedric.tiani@matech-cameroun.com","256","30-07-2025 17:04:45",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005588238","O=
bili Carrefour","","30-07-2025 16:48:08","30-07-2025 15:51:54","30-07-2025 =
17:22:55","Active//No power issue,site on Gen with Ubaie=3D47.3V The Tx Fme=
 Hosiah Mbah (674007438) of Huawei is informed.","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue,site on Gen with Ubaie=3D47.3V The Tx Fme Hosiah Mba=
h (674007438) of Huawei is informed.","loic.noumsi@matech-cameroun.com","33=
75","30-07-2025 16:48:08","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005588175","M=
imboman-Ecole","","30-07-2025 16:35:17","30-07-2025 16:31:12","30-07-2025 1=
7:35:13","Site went down FME was on site with IHS for PM (SWAP of Gen) // E=
nd of work","Mba Lazare Herve","Installation Activity","Passive","Planned A=
ctivity","Installation Activity","Site went down FME was on site with IHS f=
or PM (SWAP of Gen) // End of work","loic.noumsi@matech-cameroun.com","247"=
,"30-07-2025 16:35:17","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0005587974","Bar=
riere IHS","","30-07-2025 16:08:02","30-07-2025 16:06:52","31-07-2025 15:27=
:58","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS F=
ELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to =
Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return","c=
edric.tiani@matech-cameroun.com","72","30-07-2025 16:08:02","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005587873","O=
bili Carrefour","","30-07-2025 15:49:13","30-07-2025 15:45:02","30-07-2025 =
15:50:21","Grid outage, site went down due to fuel shortage // Refuelling d=
one","Paul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid o=
utage, site went down due to fuel shortage // Refuelling done","loic.noumsi=
@matech-cameroun.com","252","30-07-2025 15:49:13","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005587832","Nko=
g-Edzen","","30-07-2025 15:42:51","30-07-2025 15:36:42","31-07-2025 19:02:2=
0","ACCESS issue due to resident prohibit technician intervention on the si=
te/ site went down due to fuel shortage // Refuelling done","Parker Tchoup"=
,"Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue -=
 Land Lord","ACCESS issue due to resident prohibit technician intervention =
on the site/ site went down due to fuel shortage // Refuelling done","cedri=
c.tiani@matech-cameroun.com","371","30-07-2025 15:42:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005587700","Melen Ba=
'aba","","30-07-2025 15:30:15","30-07-2025 15:24:50","30-07-2025 15:27:34",=
"Cascaded Incident from TTO5778888","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen failed =
to start due to PWC dysfunctionning // Site stabilised","loic.noumsi@matech=
-cameroun.com","268522","30-07-2025 15:30:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005587701","TSINGA V=
ILLAGE 2","","30-07-2025 15:30:15","30-07-2025 15:24:50","30-07-2025 15:27:=
34","Cascaded Incident from TTO5778888","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because Gen fa=
iled to start due to PWC dysfunctionning // Site stabilised","loic.noumsi@m=
atech-cameroun.com","268524","30-07-2025 15:30:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005587699","Nkolfoul=
ou 2","","30-07-2025 15:30:14","30-07-2025 15:24:50","30-07-2025 15:27:34",=
"Cascaded Incident from TTO5778888","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen failed =
to start due to PWC dysfunctionning // Site stabilised","loic.noumsi@matech=
-cameroun.com","268523","30-07-2025 15:30:14","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005587646","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","30-07-2025 15:27:12","3=
0-07-2025 15:24:50","30-07-2025 15:30:48","Site went down because Gen faile=
d to start due to PWC dysfunctionning // Site stabilised","Siligap Boris","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site=
 went down because Gen failed to start due to PWC dysfunctionning // Site s=
tabilised","loic.noumsi@matech-cameroun.com","144","30-07-2025 15:27:12","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0005587591","N=
goulmekong-Nord","","30-07-2025 15:17:35","30-07-2025 15:16:30","30-07-2025=
 15:24:50","Site went down due to PSC3 Controller dysfunctionning// He bypa=
ssed it and site on Grid","Siligap Boris","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Site went down due to PSC3 Controller dysfun=
ctionning// He bypassed it and site on Grid","loic.noumsi@matech-cameroun.c=
om","67","30-07-2025 15:17:35","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005587423","Eto=
udi2","","30-07-2025 14:43:26","30-07-2025 14:40:18","30-07-2025 16:15:23",=
"No power issue site on Grid with U=3D48.9V. The FME Tx Armand Nguetsa 6911=
44412/ from Huawei is informed.","Delor Telezing","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e site on Grid with U=3D48.9V. The FME Tx Armand Nguetsa 691144412/ from Hu=
awei is informed.","cedric.tiani@matech-cameroun.com","189","30-07-2025 14:=
43:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005587385","Mom","",=
"30-07-2025 14:36:25","30-07-2025 14:33:23","30-07-2025 14:35:32","Cascaded=
 Incident from TTO5778586","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by IHS=
","cedric.tiani@matech-cameroun.com","264576","30-07-2025 14:36:25","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005587383","OLAMA","=
","30-07-2025 14:36:24","30-07-2025 14:33:23","30-07-2025 14:35:32","Cascad=
ed Incident from TTO5778586","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by I=
HS","cedric.tiani@matech-cameroun.com","264575","30-07-2025 14:36:24","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005587384","Minka","=
","30-07-2025 14:36:24","30-07-2025 14:33:23","30-07-2025 14:35:32","Cascad=
ed Incident from TTO5778586","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by I=
HS","cedric.tiani@matech-cameroun.com","264576","30-07-2025 14:36:24","MATE=
CH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005587373","Ako=
no","IHS_YND_687, IHS_YND_371, IHS_YND_370","30-07-2025 14:34:37","30-07-20=
25 14:33:23","30-07-2025 14:35:32","Site impacted by T0169 Ngoumou not mana=
ge by IHS","Fanda Brice","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Site impacted by T0169 Ngoumou not man=
age by IHS","cedric.tiani@matech-cameroun.com","76","30-07-2025 14:34:37","=
MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0005587353","N=
goulmekong-Nord","","30-07-2025 14:32:04","30-07-2025 14:24:57","30-07-2025=
 14:55:27","Site went down due to PSC3 Controller dysfunctionning// He bypa=
ssed it and site on Grid","Siligap Boris","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Site went down due to PSC3 Controller dysfun=
ctionning// He bypassed it and site on Grid","gerard.tchangoue@matech-camer=
oun.com","428","30-07-2025 14:32:04","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005587245","A=
hala","","30-07-2025 14:17:11","30-07-2025 14:06:16","30-07-2025 16:50:19",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down due to Gen overload (17KVA, 260A) SS H=
IS Felix Zambe is informed and confirmed // Grid return","gerard.tchangoue@=
matech-cameroun.com","273577","30-07-2025 14:17:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005587234","Nkolfon =
Cimencam","","30-07-2025 14:15:17","30-07-2025 14:06:16","30-07-2025 16:50:=
19","Cascaded Incident from TTO5778429","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirm=
ed // Grid return","gerard.tchangoue@matech-cameroun.com","273578","30-07-2=
025 14:15:17","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005587226","M=
eyo","IHS_YND_257, IHS_YND_762","30-07-2025 14:13:27","30-07-2025 14:06:16"=
,"30-07-2025 16:56:51","Grid outage, site went down due to Gen overload (17=
KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid return","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix Za=
mbe is informed and confirmed // Grid return","gerard.tchangoue@matech-came=
roun.com","432","30-07-2025 14:13:27","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005587190","E=
mombo","","30-07-2025 14:07:53","30-07-2025 13:58:44","30-07-2025 14:13:24"=
,"Grid outage, Site went down due to 03/05 rectifiers malfunctionning on si=
te // He reset rectifiers, Site on Grid","Mba Lazare Herve","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module","Grid outage, Site went down d=
ue to 03/05 rectifiers malfunctionning on site // He reset rectifiers, Site=
 on Grid","gerard.tchangoue@matech-cameroun.com","550","30-07-2025 14:07:53=
","MATECH CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0005587123","B=
ISCUITERIE","","30-07-2025 13:55:34","30-07-2025 13:52:25","30-07-2025 13:5=
8:30","No power issue, site is on Grid with Ubaie=3D51.8 V The TX FME Mbah =
Hosiah (674007438) from Huawei is informed and up at 01:48 PM.","Paul BIBOU=
M","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue, site is on Grid with Ubaie=3D51.8 V The TX F=
ME Mbah Hosiah (674007438) from Huawei is informed and up at 01:48 PM.","ge=
rard.tchangoue@matech-cameroun.com","190","30-07-2025 13:55:34","MATECH CMR=
"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005587030","Djo=
nassi-Yde","","30-07-2025 13:40:25","30-07-2025 13:35:19","30-07-2025 15:59=
:43","Site went down due to 03 rectifiers dyfunction on site//He replaced 0=
1 and reset 02 ","Fabrice Pouakam","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to 03 rectifiers dyfunction on site=
//He replaced 01 and reset 02 ","gaelle.njiofack@matech-cameroun.com","307"=
,"30-07-2025 13:40:25","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005586935","M=
imboman-Ecole","","30-07-2025 13:19:48","30-07-2025 13:13:35","30-07-2025 1=
6:04:23","Grid outage, site went down because Gen started and stopped due t=
o Ge Battery faulty // He started Gen with an external battery,","Mba Lazar=
e Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery"=
,"Grid outage, site went down because Gen started and stopped due to Ge Bat=
tery faulty // He started Gen with an external battery,","gerard.tchangoue@=
matech-cameroun.com","374","30-07-2025 13:19:48","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005586921","E=
mombo","","30-07-2025 13:16:00","30-07-2025 13:13:54","30-07-2025 13:16:28"=
,"Grid outage, Site went down due to 03/05 rectifiers malfunctionning on si=
te // He reset rectifiers, Site on Grid","Mba Lazare Herve","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module","Grid outage, Site went down d=
ue to 03/05 rectifiers malfunctionning on site // He reset rectifiers, Site=
 on Grid","gerard.tchangoue@matech-cameroun.com","127","30-07-2025 13:16:00=
","MATECH CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0005586892","ETO=
UDI CHAPELLE","","30-07-2025 13:08:35","30-07-2025 13:02:31","30-07-2025 20=
:34:39","","Delor Telezing","Cascade Outage","Active","Cascade Active","Cas=
cade Active","No power issue site on grid with U=3D52.9V Symphorien(6913168=
54) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","291543"=
,"30-07-2025 13:08:35","MATECH CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0005586888","Eto=
udi 2","IHS_YND_694","30-07-2025 13:07:38","30-07-2025 13:02:31","30-07-202=
5 13:08:11","Active//No power issue, site is on Grid with Ubaie=3D53,7V The=
 Tx FME Armand Nguetsa / 691144412/ from Huawei is informed","Fabrice Pouak=
am","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue, site is on Grid with Ubaie=3D53,7V =
The Tx FME Armand Nguetsa / 691144412/ from Huawei is informed","gaelle.nji=
ofack@matech-cameroun.com","308","30-07-2025 13:07:38","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005586884","Aba=
ttoir","","30-07-2025 13:07:01","30-07-2025 13:02:31","30-07-2025 13:08:11"=
,"","Fabrice Pouakam","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","Active//No power issue, site is on Grid with Ubaie=3D53,7V The Tx F=
ME Armand Nguetsa / 691144412/ from Huawei is informed","gaelle.njiofack@ma=
tech-cameroun.com","799","30-07-2025 13:07:01","MATECH CMR"
"Closed Complete","Site Down","T0370","IHS_YND_227","NOCINC0005586867","Mvo=
g Betsi","IHS_YND_741, IHS_YND_143, IHS_YND_515, IHS_YND_747","30-07-2025 1=
3:00:51","30-07-2025 12:58:37","30-07-2025 14:10:50","Grid outage, Site wen=
t down because Gen failed to start due to HIGH TEMP alarm // He added water=
 and started Gen manually","Hyemafo Gildas","Equipment Repair","Passive","A=
CDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site=
 went down because Gen failed to start due to HIGH TEMP alarm // He added w=
ater and started Gen manually","gaelle.njiofack@matech-cameroun.com","135",=
"30-07-2025 13:00:51","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005586808","Eto=
ug ebe Meweulo","","30-07-2025 12:48:54","30-07-2025 12:58:37","30-07-2025 =
14:10:50","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, Site went down because Gen failed to start =
due to HIGH TEMP alarm // He added water and started Gen manually","gaelle.=
njiofack@matech-cameroun.com","277313","30-07-2025 12:48:54","MATECH CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0005586794","Bye=
massi Carrefour","","30-07-2025 12:47:52","30-07-2025 12:58:37","30-07-2025=
 14:10:50","","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid outage, Site went down because Gen failed to start du=
e to HIGH TEMP alarm // He added water and started Gen manually","gaelle.nj=
iofack@matech-cameroun.com","277313","30-07-2025 12:47:52","MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005586777","Mvo=
g Betsi Hospital","","30-07-2025 12:46:17","30-07-2025 12:58:37","30-07-202=
5 14:10:50","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Grid outage, Site went down because Gen failed to star=
t due to HIGH TEMP alarm // He added water and started Gen manually","gaell=
e.njiofack@matech-cameroun.com","277312","30-07-2025 12:46:17","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005586769","Ako=
k Ndoe Yde","","30-07-2025 12:44:57","30-07-2025 12:58:37","30-07-2025 14:1=
0:50","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage, Site went down because Gen failed to start due =
to HIGH TEMP alarm // He added water and started Gen manually","gerard.tcha=
ngoue@matech-cameroun.com","277311","30-07-2025 12:44:57","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005586651","Djo=
nassi-Yde","","30-07-2025 12:24:14","30-07-2025 12:21:06","30-07-2025 12:44=
:39","site went down due to relay 12 v faulty//We replace by the new relay =
and site on gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Relay Faulty","site went down due to relay 12 v faulty//We replace =
by the new relay and site on gen","gerard.tchangoue@matech-cameroun.com","1=
89","30-07-2025 12:24:14","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005586534","NYO=
M FACE MAETUR","","30-07-2025 12:06:24","30-07-2025 12:05:15","30-07-2025 1=
2:06:58","Grid fluctuations, site went down due Grid bad voltage and no RCP=
 on site // Grid stabilised","Fabrice Pouakam","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Grid fluctuations, site went =
down due Grid bad voltage and no RCP on site // Grid stabilised","gaelle.nj=
iofack@matech-cameroun.com","71","30-07-2025 12:06:24","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005586446","OTE=
LE MTN","","30-07-2025 11:50:36","30-07-2025 11:46:22","30-07-2025 17:19:28=
","Grid outage,Site went down because Gen failed to start due to Generator =
starter faulty//Grid return","Fanda Brice","Equipment Repair","Passive","AC=
DG Gen","ACDG - Kick Starter","Grid outage,Site went down because Gen faile=
d to start due to Generator starter faulty//Grid return","gaelle.njiofack@m=
atech-cameroun.com","255","30-07-2025 11:50:36","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0005586444","N=
goulmekong-Nord","","30-07-2025 11:49:55","30-07-2025 11:42:50","30-07-2025=
 14:11:21","Site went down due to PSC3 Controller dysfunctionning// He bypa=
ssed it and site on Grid","Siligap Boris","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Site went down due to PSC3 Controller dysfun=
ctionning// He bypassed it and site on Grid","gaelle.njiofack@matech-camero=
un.com","426","30-07-2025 11:49:55","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005586337","Nko=
g-Edzen","","30-07-2025 11:31:52","30-07-2025 11:27:43","30-07-2025 12:20:5=
4"," Acces issue due to Landlord //Grid outage gen failed to start due to a=
irintake//We purged and gen manually started ","Parker Tchoup","Access Deni=
al","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","=
 Acces issue due to Landlord //Grid outage gen failed to start due to airin=
take//We purged and gen manually started ","gaelle.njiofack@matech-cameroun=
.com","250","30-07-2025 11:31:52","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005586162","Nko=
lnda","","30-07-2025 11:01:43","30-07-2025 10:59:15","30-07-2025 11:01:50",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Grid return	","Albran Byorel","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before Gen star=
t due to poor battery backup // Grid return	","gaelle.njiofack@matech-camer=
oun.com","149","30-07-2025 11:01:43","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005586155","A=
hala","","30-07-2025 11:00:45","30-07-2025 09:56:30","30-07-2025 11:20:52",=
"No power issue site on grid with U=3D54v Flubert(654266068) from Huawei is=
 working on site","MINKA NICOLAS","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid w=
ith U=3D54v Flubert(654266068) from Huawei is working on site","gerard.tcha=
ngoue@matech-cameroun.com","3856","30-07-2025 11:00:45","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005585516","Man=
guiers Dispensaire","","30-07-2025 09:11:34","30-07-2025 09:09:26","30-07-2=
025 09:15:44","Site went down due to work: Our Technician Fabrice (65710861=
3/ Matech) is working on site (replacement Eneo Contactor) // End work","Fa=
brice Pouakam","Installation Activity","Passive","Planned Activity","Instal=
lation Activity","Site went down due to work: Our Technician Fabrice (65710=
8613/ Matech) is working on site (replacement Eneo Contactor) // End work",=
"gerard.tchangoue@matech-cameroun.com","129","30-07-2025 09:11:34","MATECH =
CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005585107","O=
mnisport-Rail","","30-07-2025 07:36:14","30-07-2025 07:32:05","30-07-2025 0=
9:02:16","No power issue site on grid with U=3D53.4v,Armand Nguetsa from Hu=
aei is informed.Notice that we have disjunction at OCM Equipements","Delor =
Telezing","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue site on grid with U=3D53.4v,Armand Ngu=
etsa from Huaei is informed.Notice that we have disjunction at OCM Equipeme=
nts","gerard.tchangoue@matech-cameroun.com","251","30-07-2025 07:36:14","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005585043","M=
elen Ba'aba","","30-07-2025 07:25:04","30-07-2025 07:23:58","30-07-2025 08:=
14:59","Grid outage, Site went down because Gen start and stopped with ""Hi=
gh temps ""alarm // he added water and manually start the Gen","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid outage, Site went down because Gen start and stopped=
 with ""High temps ""alarm // he added water and manually start the Gen","g=
erard.tchangoue@matech-cameroun.com","68","30-07-2025 07:25:04","MATECH CMR=
"
"Closed Complete","Site Down","T2222","IHS_YND_697","NOCINC0005584807","Nom=
ayos-IHS","","30-07-2025 06:21:23","30-07-2025 06:13:08","30-07-2025 06:29:=
42","Grid outage, site went down due to 01/04 rectifier dysfunctionning // =
He reset it, site on Gen","Fanda Brice","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Grid outage, site went down due to 01/04 rectifie=
r dysfunctionning // He reset it, site on Gen","gerard.tchangoue@matech-cam=
eroun.com","496","30-07-2025 06:21:23","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005584648","MBA=
LNGONG LYCEE","","30-07-2025 05:40:37","30-07-2025 05:31:30","30-07-2025 06=
:19:32","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid stabilised",=
"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, Site went down because Gen stopped due to overload(9kva, 130A) S=
S IHS Felix Zambe is informed and confirmed // Grid stabilised","gerard.tch=
angoue@matech-cameroun.com","549","30-07-2025 05:40:37","MATECH CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0005584638","Nom=
ayos","","30-07-2025 05:32:52","30-07-2025 05:23:42","30-07-2025 05:57:27",=
"Grid outage, site went down because Gen failed to start due to The manual =
mode of the Gen has been activated. // The automatically mode reactivated a=
nd site on Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Grid outage, site went down because Gen failed to start =
due to The manual mode of the Gen has been activated. // The automatically =
mode reactivated and site on Gen","gerard.tchangoue@matech-cameroun.com","5=
52","30-07-2025 05:32:52","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005584411","N=
koabang Ebolmedjock","","30-07-2025 03:58:07","30-07-2025 03:52:58","30-07-=
2025 03:59:18","Site impacted by Nkolmesseng-Abom(CTR-711) Not Managed By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","Site impacted by Nkolmesseng-Abo=
m(CTR-711) Not Managed By IHS","gerard.tchangoue@matech-cameroun.com","311"=
,"30-07-2025 03:58:07","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005584356","Aba=
ttoir","","30-07-2025 03:38:15","30-07-2025 03:31:07","30-07-2025 03:45:22"=
,"Grid outage, site went down due to poor backup // Gen started automatical=
ly","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, site went down due to poor backup // Ge=
n started automatically","gerard.tchangoue@matech-cameroun.com","430","30-0=
7-2025 03:38:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0005584323","AWAE OCM=
","","30-07-2025 03:21:22","30-07-2025 03:10:02","30-07-2025 04:13:53","Cas=
caded Incident from TTO5775278","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because Gen failed t=
o start due to Grid fluctuation // Grid stabilised","gerard.tchangoue@matec=
h-cameroun.com","269457","30-07-2025 03:21:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0005584322","Tradex-N=
komo","","30-07-2025 03:21:21","30-07-2025 03:10:02","30-07-2025 04:13:53",=
"Cascaded Incident from TTO5775278","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen failed =
to start due to Grid fluctuation // Grid stabilised","gerard.tchangoue@mate=
ch-cameroun.com","269458","30-07-2025 03:21:21","MATECH CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0005584320","Nko=
mo II","IHS_YND_172, IHS_YND_173","30-07-2025 03:19:36","30-07-2025 03:10:0=
2","30-07-2025 04:13:53","Site went down because Gen failed to start due to=
 Grid fluctuation // Grid stabilised","Albran Byorel","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Site went down because=
 Gen failed to start due to Grid fluctuation // Grid stabilised","gerard.tc=
hangoue@matech-cameroun.com","574","30-07-2025 03:19:36","MATECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0005584305","HOP=
ITAL GENERAL RAIL YDE","","30-07-2025 03:16:44","30-07-2025 03:10:36","30-0=
7-2025 04:00:19","Grid outage.gen failed to start due to grid fluctuations/=
/Grid power stabilized","Delor Telezing","Grid Supply","Passive","Grid","Na=
tional Grid - Unstable Grid Supply Issue","Grid outage.gen failed to start =
due to grid fluctuations//Grid power stabilized","gerard.tchangoue@matech-c=
ameroun.com","369","30-07-2025 03:16:44","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005584295","Pha=
rmacie Bleue","","30-07-2025 03:13:14","30-07-2025 03:10:02","30-07-2025 04=
:00:11","Grid outage, site went down because gen failed to start due to gen=
 card faulty // Grid restoration","Siligap Boris","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
gen failed to start due to gen card faulty // Grid restoration","gerard.tch=
angoue@matech-cameroun.com","193","30-07-2025 03:13:14","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005584231","Evo=
doula MTN","","30-07-2025 02:59:15","30-07-2025 02:55:06","30-07-2025 03:13=
:21","Grid outage, Site went down before Gen start due to poor backup//Gen =
Automatically Started	","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup//Gen Automatically Started	","gera=
rd.tchangoue@matech-cameroun.com","250","30-07-2025 02:59:15","MATECH CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0005584223","Ntu=
i administration","","30-07-2025 02:54:52","30-07-2025 02:52:42","30-07-202=
5 04:48:13","Site went down due to 1/2 retifier disfunction // he reset it =
and site is up","Parker Tchoup","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to 1/2 retifier disfunction // he rese=
t it and site is up","gerard.tchangoue@matech-cameroun.com","131","30-07-20=
25 02:54:52","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0005584214","Nlo=
ngkak","","30-07-2025 02:49:00","30-07-2025 02:39:52","30-07-2025 03:59:16"=
,"Grid outage,site went down due to Grid fluctuations // Grid stabilised","=
Delor Telezing","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid outage,site went down due to Grid fluctuations // Grid =
stabilised","gerard.tchangoue@matech-cameroun.com","549","30-07-2025 02:49:=
00","MATECH CMR"
"Closed Complete","Site Down","T0219","IHS_YND_024","NOCINC0005584186","Gar=
bati building","","30-07-2025 02:33:42","30-07-2025 02:24:29","30-07-2025 0=
3:57:12","Grid outage gen failed to start due to automation failure//Gen ma=
nually started ","Delor Telezing","Equipment Repair","Passive","Control Pan=
el","ATS-AMF Issue","Grid outage gen failed to start due to automation fail=
ure//Gen manually started ","gerard.tchangoue@matech-cameroun.com","554","3=
0-07-2025 02:33:42","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005584185","Man=
guiers Dispensaire","","30-07-2025 02:31:44","30-07-2025 02:22:30","30-07-2=
025 03:57:29","Grid outage.site went due to grid contactor dysfunctionned//=
We bypass grid contactor and gen manually started","Fabrice Pouakam","Equip=
ment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage.site we=
nt due to grid contactor dysfunctionned//We bypass grid contactor and gen m=
anually started","gerard.tchangoue@matech-cameroun.com","555","30-07-2025 0=
2:31:44","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005584183","M=
imboman-Ecole","","30-07-2025 02:29:02","30-07-2025 02:19:56","30-07-2025 0=
5:39:34","(access issue at night due to landlord) Site went down because re=
ctifier dysfunctioned on site // He reset the rectifier","Mba Lazare Herve"=
,"Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue -=
 Land Lord","(access issue at night due to landlord) Site went down because=
 rectifier dysfunctioned on site // He reset the rectifier","gerard.tchango=
ue@matech-cameroun.com","547","30-07-2025 02:29:02","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005584182","E=
toudi","","30-07-2025 02:28:35","30-07-2025 02:19:03","30-07-2025 03:59:22"=
,"Grid outage .site went down due to gen overload(20kva,300 A) SS HIS Berna=
rd Atangana is informed //we reduce load and gen manually started","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage .site went down due to gen overload(20kva,300 A) SS HIS Bernard Atang=
ana is informed //we reduce load and gen manually started","gerard.tchangou=
e@matech-cameroun.com","574","30-07-2025 02:28:35","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005584179","S=
atcom","","30-07-2025 02:24:57","30-07-2025 02:17:47","30-07-2025 05:18:31"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","gerard.tchangoue@matec=
h-cameroun.com","431","30-07-2025 02:24:57","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005584176","N=
koabang2","","30-07-2025 02:23:24","30-07-2025 02:16:07","30-07-2025 03:53:=
45","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","gerard=
.tchangoue@matech-cameroun.com","439","30-07-2025 02:23:24","MATECH CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0005583913","NYA=
NON/DEMBO","","30-07-2025 01:03:20","30-07-2025 00:57:46","30-07-2025 01:06=
:54","Active// no power issue on site ,site on Gen with Ubaie=3D49.7V The T=
x FME Gregroire (654547479) from Hauawei is informed,","TIENTCHEU NZETCHIEU=
 GAEL","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active// no power issue on site ,site on Gen with Ubaie=
=3D49.7V The Tx FME Gregroire (654547479) from Hauawei is informed,","gerar=
d.tchangoue@matech-cameroun.com","336","30-07-2025 01:03:20","MATECH CMR"
"Closed Complete","Warning","T0601","IHS_YND_098","NOCINC0005583499","Ekoun=
ou","","29-07-2025 22:46:37","","","	Grid outage, site went down because ge=
n failed to ATS dysfunctionning // He reset it and gen manually started","A=
lbran Byorel","Warning","Warning","POWER","Warning - ATS-AMF Issue","	Grid =
outage, site went down because gen failed to ATS dysfunctionning // He rese=
t it and gen manually started","cedric.tiani@matech-cameroun.com","3369","2=
9-07-2025 22:46:37","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005583279","Nko=
langaa","","29-07-2025 22:06:16","29-07-2025 22:00:59","29-07-2025 23:21:59=
","Site went down because CB (125A) tripped in DC Box // DC box CB reamed, =
site on grid.","Mba Lazare Herve","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","Site went down because CB (125=
A) tripped in DC Box // DC box CB reamed, site on grid.","cedric.tiani@mate=
ch-cameroun.com","318","29-07-2025 22:06:16","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005583254","Bit=
eng-Maetur","","29-07-2025 22:01:31","29-07-2025 21:53:15","29-07-2025 22:1=
2:57","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","ludivin=
e.ngamaleu@ihstowers.com","498","29-07-2025 22:01:31","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005583235","C=
omplexe-BEAC","","29-07-2025 21:56:44","29-07-2025 21:51:33","29-07-2025 23=
:48:40","Site down due to Disjonction of the OCM CB //Site on Grid and CB r=
earmed","Albran Byorel","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Circuit Breaker Issue","Site down due to Disjonction of the OCM =
CB //Site on Grid and CB rearmed","vanel.mbiada@matech-cameroun.com","312",=
"29-07-2025 21:56:44","MATECH CMR"
"Closed Complete","Warning","","IHS_YND_098","NOCINC0005583180","Ekounou","=
","29-07-2025 21:44:35","","","	Grid outage, site went down because gen fai=
led to ATS dysfunctionning // He reset it and gen manually started","Albran=
 Byorel","Warning","Warning","POWER","Warning - ATS-AMF Issue","	Grid outag=
e, site went down because gen failed to ATS dysfunctionning // He reset it =
and gen manually started","vanel.mbiada@matech-cameroun.com","8069","29-07-=
2025 21:44:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0005583143","Awae Ewo=
nkan","","29-07-2025 21:36:25","29-07-2025 16:58:13","29-07-2025 22:26:22",=
"Backtraking Power issue resolved :  No power issue on site Tx issue U=3D51=
.3V site on Grid , the FME TX Leonel Steve //655184876 from Huawei is infor=
med","Albran Byorel","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Backtraking Power issue resolved :  No pow=
er issue on site Tx issue U=3D51.3V site on Grid , the FME TX Leonel Steve =
//655184876 from Huawei is informed","vanel.mbiada@matech-cameroun.com","16=
694","29-07-2025 21:36:25","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005583109","Eto=
ug ebe Carrefour","","29-07-2025 21:30:20","29-07-2025 21:28:06","29-07-202=
5 21:44:06","Grid outage site went down before gen started due to poor batt=
ery backup // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before gen started due to poor battery backup // Site stabilised","cedric.=
tiani@matech-cameroun.com","135","29-07-2025 21:30:20","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005583071","N=
gouetou","","29-07-2025 21:26:27","29-07-2025 21:22:20","29-07-2025 21:32:2=
0","Active // No power issue site on Gen, with Ubay: 55.5V. The Tx Fme Greg=
oire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e // No power issue site on Gen, with Ubay: 55.5V. The Tx Fme Gregoire (654=
547479) from Huawei is informed","vanel.mbiada@matech-cameroun.com","249","=
29-07-2025 21:26:27","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005582911","Eto=
ug ebe Carrefour","","29-07-2025 20:57:56","29-07-2025 20:53:34","29-07-202=
5 20:59:58","Grid outage site went down before gen started due to poor batt=
ery backup // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before gen started due to poor battery backup // Site stabilised","cedric.=
tiani@matech-cameroun.com","263","29-07-2025 20:57:56","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005582773","T=
SINGA VILLAGE 2","","29-07-2025 20:37:48","29-07-2025 20:34:41","29-07-2025=
 20:36:59","Site went down due to FME work on the bay controller // End wor=
k","Delor Telezing","Installation Activity","Passive","Planned Activity","I=
nstallation Activity","Site went down due to FME work on the bay controller=
 // End work","vanel.mbiada@matech-cameroun.com","189","29-07-2025 20:37:48=
","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005582772","Bit=
eng-Maetur","","29-07-2025 20:37:41","29-07-2025 20:36:29","29-07-2025 21:0=
0:29","Active//No power issue on site Ubaie =3D53.5V site on Grid The TX FM=
E Henri (699949693) from Huawei is informed","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site Ubaie =3D53.5V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","cedric.tiani@matech-cameroun.com","=
74","29-07-2025 20:37:41","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005582680","NYO=
M FACE MAETUR","","29-07-2025 20:15:48","29-07-2025 20:09:38","29-07-2025 2=
1:10:38","Grid outage, Site went down because Gen failed to start due to Gr=
id bad voltage (Lack of phases) //He made a bridge. Power issue resolve at =
09 :10 PM but site remains down after","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid outage, Site w=
ent down because Gen failed to start due to Grid bad voltage (Lack of phase=
s) //He made a bridge. Power issue resolve at 09 :10 PM but site remains do=
wn after","cedric.tiani@matech-cameroun.com","373","29-07-2025 20:15:48","M=
ATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005582489","Eto=
ug ebe Carrefour","","29-07-2025 19:38:10","29-07-2025 19:36:02","29-07-202=
5 19:42:06","Grid outage, Site went down before Gen start due to poor backu=
p/ // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Grid return","cedric.tiani@matech-cameroun.co=
m","129","29-07-2025 19:38:10","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005582487","Mon=
tee-Jouvence-II","","29-07-2025 19:37:34","29-07-2025 19:36:08","29-07-2025=
 19:38:26","Grid outage, Site went down before Gen start due to poor backup=
/ // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup/ // Grid return","cedric.tiani@matech-cameroun.com=
","87","29-07-2025 19:37:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005582369","Nkolfoul=
ou 2","","29-07-2025 19:14:11","29-07-2025 19:08:38","29-07-2025 20:11:11",=
"Cascaded Incident from TTO5773075","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to gen =
overload 300 A /20 KVA // Gen charge reduced and manual start of gen.","van=
el.mbiada@matech-cameroun.com","269521","29-07-2025 19:14:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005582371","TSINGA V=
ILLAGE 2","","29-07-2025 19:14:11","29-07-2025 19:08:38","29-07-2025 20:11:=
11","Cascaded Incident from TTO5773075","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site down due to=
 gen overload 300 A /20 KVA // Gen charge reduced and manual start of gen."=
,"vanel.mbiada@matech-cameroun.com","269521","29-07-2025 19:14:11","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005582370","Melen Ba=
'aba","","29-07-2025 19:14:11","29-07-2025 19:08:38","29-07-2025 20:11:11",=
"Cascaded Incident from TTO5773075","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to gen =
overload 300 A /20 KVA // Gen charge reduced and manual start of gen.","van=
el.mbiada@matech-cameroun.com","269520","29-07-2025 19:14:11","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0005582355","Nko=
lfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","29-07-2025 19:10:52","29-=
07-2025 19:08:38","29-07-2025 20:24:30","Grid outage, site down due to gen =
overload 300 A /20 KVA // Gen charge reduced and manual start of gen.","Sil=
igap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, site down due to gen overload 300 A /20 KVA // Gen charge reduced =
and manual start of gen.","cedric.tiani@matech-cameroun.com","135","29-07-2=
025 19:10:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005582055","Song-bon=
g","","29-07-2025 18:09:22","29-07-2025 14:31:55","29-07-2025 17:58:36","Ca=
scaded Incident from TTO5772390","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","  No power issue U=3D57.2V site on Gri=
d The Tx FME Etienne FOPA /695033981/ From HUAWEI is informed","vanel.mbiad=
a@matech-cameroun.com","279185","29-07-2025 18:09:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005582054","Eseka To=
wn","","29-07-2025 18:09:21","29-07-2025 14:31:55","29-07-2025 17:58:36","C=
ascaded Incident from TTO5772390","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","  No power issue U=3D57.2V site on Gr=
id The Tx FME Etienne FOPA /695033981/ From HUAWEI is informed","vanel.mbia=
da@matech-cameroun.com","279185","29-07-2025 18:09:21","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005581850","M=
ambine","","29-07-2025 17:28:59","29-07-2025 17:25:47","29-07-2025 18:05:15=
","Hybrid gen site.gen failed to start due to oil sensor disconnected//We f=
ixed oil sensor and gen manually started","Fanda Brice","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Oil Sensor Switch","Hybrid gen site.gen failed=
 to start due to oil sensor disconnected//We fixed oil sensor and gen manua=
lly started","vanel.mbiada@matech-cameroun.com","194","29-07-2025 17:28:59"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005581777","C=
NR","","29-07-2025 17:18:35","29-07-2025 17:10:24","29-07-2025 17:18:48","S=
ite impacted by CNDH wish is not IHS site","Mboua Thierry","Customer Equipm=
ent Failure","Active","Active Equipment Failure","Affected by 3rd Party Sit=
e","Site impacted by CNDH wish is not IHS site","vanel.mbiada@matech-camero=
un.com","492","29-07-2025 17:18:35","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005581762","Mok=
olo Yaounde","","29-07-2025 17:16:10","29-07-2025 17:12:02","29-07-2025 17:=
35:58","Grid only site, no space to deploy MDGE //  Grid returned","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only si=
te, no space to deploy MDGE //  Grid returned","cedric.tiani@matech-camerou=
n.com","249","29-07-2025 17:16:10","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005581733","E=
seka OCM","IHS_YND_378, IHS_YND_453","29-07-2025 17:11:17","29-07-2025 14:3=
1:55","29-07-2025 17:58:36","Backtraking, power issue resolved:  No power i=
ssue U=3D57.2V site on Grid The Tx FME Etienne FOPA /695033981/ From HUAWEI=
 is informed","Kemeni Franklin","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","  No power issue U=3D57.2V site=
 on Grid The Tx FME Etienne FOPA /695033981/ From HUAWEI is informed","vane=
l.mbiada@matech-cameroun.com","9563","29-07-2025 17:11:17","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005581695","Hop=
ital Central","","29-07-2025 17:03:46","29-07-2025 17:02:38","29-07-2025 19=
:36:37","(Unstable)Site went down due to 03/05 rectifiers faulty // Site st=
abilised","","Equipment Repair","Passive","Rectifier","Rectifier Module","(=
Unstable)Site went down due to 03/05 rectifiers faulty // Site stabilised",=
"cedric.tiani@matech-cameroun.com","69","29-07-2025 17:03:46","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005581685","Eto=
udi2","","29-07-2025 17:01:32","29-07-2025 17:00:25","29-07-2025 17:28:05",=
"Grid outage site went down before gen started due to poor battery backup /=
/ Grid return","Delor Telezing","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage site went down before gen star=
ted due to poor battery backup // Grid return","cedric.tiani@matech-camerou=
n.com","68","29-07-2025 17:01:32","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005581682","E=
toudi","","29-07-2025 17:00:27","29-07-2025 16:59:18","29-07-2025 18:40:13"=
,"Grid outage,site went down due to gen overload(20kva,300 A) SS HIS Bernar=
d Atangana is informed //  Site stabilised	","Fabrice Pouakam","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,site went down d=
ue to gen overload(20kva,300 A) SS HIS Bernard Atangana is informed //  Sit=
e stabilised	","vanel.mbiada@matech-cameroun.com","70","29-07-2025 17:00:27=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005581600","Nkol-Meb=
anga","","29-07-2025 16:50:11","29-07-2025 16:48:26","29-07-2025 16:50:08",=
"Cascaded Incident from TTO5772243","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site ,site on Gen w=
ith Ubaie =3D49.7V The Tx Technician from Huawei Gr=E9goire//654547479 is i=
nformed","cedric.tiani@matech-cameroun.com","263871","29-07-2025 16:50:11",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005581599","Carrefou=
r Ayissi Ele","","29-07-2025 16:50:10","29-07-2025 16:48:26","29-07-2025 16=
:50:08","Cascaded Incident from TTO5772243","Parker Tchoup","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue on site ,site =
on Gen with Ubaie =3D49.7V The Tx Technician from Huawei Gr=E9goire//654547=
479 is informed","cedric.tiani@matech-cameroun.com","263871","29-07-2025 16=
:50:10","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005581598","Saa=
","IHS_YND_810, IHS_YND_809","29-07-2025 16:49:36","29-07-2025 16:48:26","2=
9-07-2025 16:50:08","No power issue on site ,site on Gen with Ubaie =3D49.7=
V The Tx Technician from Huawei Gr=E9goire//654547479 is informed","Parker =
Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site ,site on Gen with Ubaie =3D49.7V=
 The Tx Technician from Huawei Gr=E9goire//654547479 is informed","cedric.t=
iani@matech-cameroun.com","71","29-07-2025 16:49:36","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005581590","Eto=
udi2","","29-07-2025 16:47:25","29-07-2025 16:45:16","29-07-2025 16:50:14",=
"Grid outage site went down before gen started due to poor battery backup /=
/ Grid return","Delor Telezing","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage site went down before gen star=
ted due to poor battery backup // Grid return","cedric.tiani@matech-camerou=
n.com","130","29-07-2025 16:47:25","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005581529","Eto=
udi2","","29-07-2025 16:34:41","29-07-2025 16:31:32","29-07-2025 16:40:18",=
"Grid outage site went down before gen started due to poor battery backup /=
/ Site stabilised","Delor Telezing","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage site went down before gen =
started due to poor battery backup // Site stabilised","cedric.tiani@matech=
-cameroun.com","190","29-07-2025 16:34:41","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005581462","Eto=
udi2","","29-07-2025 16:23:20","29-07-2025 16:17:32","29-07-2025 16:30:10",=
"Grid outage site went down before gen started due to poor battery backup /=
/ Site stabilised","Delor Telezing","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage site went down before gen =
started due to poor battery backup // Site stabilised","cedric.tiani@matech=
-cameroun.com","349","29-07-2025 16:23:20","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005581427","Hop=
ital Central","","29-07-2025 16:18:28","29-07-2025 16:17:21","29-07-2025 16=
:42:21","site went down due to insufficient rectifiers on site//Site stabil=
ised","","Equipment Repair","Passive","Rectifier","Rectifier Module","site =
went down due to insufficient rectifiers on site//Site stabilised","cedric.=
tiani@matech-cameroun.com","68","29-07-2025 16:18:28","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005581390","A=
wae Ewonkan","","29-07-2025 16:06:49","29-07-2025 15:46:39","29-07-2025 16:=
56:41","Site went down due to work of  BIGANS(650631358) DOWEN (SWAPP OF PW=
C and GEN)//End of work","Albran Byorel","Installation Activity","Passive",=
"Planned Activity","Installation Activity","Site went down due to work of  =
BIGANS(650631358) DOWEN (SWAPP OF PWC and GEN)//End of work","vanel.mbiada@=
matech-cameroun.com","3738","29-07-2025 16:06:49","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005581301","E=
toudi","","29-07-2025 15:52:47","29-07-2025 15:51:41","29-07-2025 15:57:21"=
,"Grid outage,site went down due to gen overload(20kva,300 A) SS HIS Bernar=
d Atangana is informed ","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Grid outage,site went down due to gen overload(2=
0kva,300 A) SS HIS Bernard Atangana is informed // Site stabilised","vanel.=
mbiada@matech-cameroun.com","67","29-07-2025 15:52:47","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005581221","Eto=
udi2","","29-07-2025 15:41:07","29-07-2025 15:35:56","29-07-2025 15:57:12",=
"Grid outage site went down before gen started due to poor battery backup /=
/ Site stabilised","Delor Telezing","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage site went down before gen =
started due to poor battery backup // Site stabilised","cedric.tiani@matech=
-cameroun.com","312","29-07-2025 15:41:07","MATECH CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0005581213","Eko=
unou","","29-07-2025 15:40:24","29-07-2025 15:36:16","29-07-2025 16:28:38",=
"Grid outage, site went down because gen failed to ATS dysfunctionning // H=
e reset it and gen manually started","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","Grid outage, site went down because=
 gen failed to ATS dysfunctionning // He reset it and gen manually started"=
,"cedric.tiani@matech-cameroun.com","251","29-07-2025 15:40:24","MATECH CMR=
"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005581210","Eto=
ug ebe Carrefour","","29-07-2025 15:40:01","29-07-2025 15:38:54","29-07-202=
5 15:56:37","Grid outage site went down before gen started due to poor batt=
ery backup // Grid return","Hyemafo Gildas","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage site went down bef=
ore gen started due to poor battery backup // Grid return","cedric.tiani@ma=
tech-cameroun.com","68","29-07-2025 15:40:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_422","NOCINC0005581177","Botmakak=
","","29-07-2025 15:35:10","29-07-2025 14:48:21","29-07-2025 16:38:43","Cas=
caded Incident from TTO5771573","Kemeni Franklin","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to insufficient r=
ectifiers on site // Fault Rectifier reseted","vanel.mbiada@matech-cameroun=
.com","271074","29-07-2025 15:35:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_373","NOCINC0005581175","Maloun",=
"","29-07-2025 15:35:10","29-07-2025 14:48:21","29-07-2025 16:38:43","Casca=
ded Incident from TTO5771573","Kemeni Franklin","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to insufficient rec=
tifiers on site // Fault Rectifier reseted","vanel.mbiada@matech-cameroun.c=
om","271073","29-07-2025 15:35:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0005581176","Ngoung",=
"","29-07-2025 15:35:10","29-07-2025 14:48:21","29-07-2025 16:38:43","Casca=
ded Incident from TTO5771573","Kemeni Franklin","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to insufficient rec=
tifiers on site // Fault Rectifier reseted","vanel.mbiada@matech-cameroun.c=
om","271072","29-07-2025 15:35:10","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005581011","TON=
GOLO SNEC","","29-07-2025 14:59:40","29-07-2025 14:57:30","29-07-2025 15:43=
:51","No power Issue Site on Grid Ubai =3D54.5 V. The TX FME Armand Nguetsa=
 (699949553) is informed.Noticed disjunction at the BTS MTN","Fabrice Pouak=
am","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power Issue Site on Grid Ubai =3D54.5 V. The TX FME Arma=
nd Nguetsa (699949553) is informed.Noticed disjunction at the BTS MTN","ced=
ric.tiani@matech-cameroun.com","131","29-07-2025 14:59:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005581005","Etoudi 2=
","","29-07-2025 14:58:50","29-07-2025 14:56:34","29-07-2025 15:04:36","Cas=
caded Incident from TTO5771582","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,site went down due to Ge=
n overload (20KVA//340A) SS HIS Bernard Atagana is informed//He reduced the=
 load and site on GEN","cedric.tiani@matech-cameroun.com","263256","29-07-2=
025 14:58:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0005581003","Abattoir=
","","29-07-2025 14:58:50","29-07-2025 14:56:34","29-07-2025 15:04:36","Cas=
caded Incident from TTO5771582","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,site went down due to Ge=
n overload (20KVA//340A) SS HIS Bernard Atagana is informed//He reduced the=
 load and site on GEN","cedric.tiani@matech-cameroun.com","263257","29-07-2=
025 14:58:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005581004","ETOUDI C=
HAPELLE","","29-07-2025 14:58:50","29-07-2025 14:56:34","29-07-2025 15:04:3=
6","Cascaded Incident from TTO5771582","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,site went down due=
 to Gen overload (20KVA//340A) SS HIS Bernard Atagana is informed//He reduc=
ed the load and site on GEN","cedric.tiani@matech-cameroun.com","263256","2=
9-07-2025 14:58:50","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005580999","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","29-07-2025 14:57:41","29-07-2=
025 14:56:34","29-07-2025 15:04:36","Grid outage,site went down due to Gen =
overload (20KVA//340A) SS HIS Bernard Atagana is informed//He reduced the l=
oad and site on GEN","Fabrice Pouakam","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Grid outage,site went down due to Gen overload (20KV=
A//340A) SS HIS Bernard Atagana is informed//He reduced the load and site o=
n GEN","cedric.tiani@matech-cameroun.com","68","29-07-2025 14:57:41","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0005580990","M=
atomb","IHS_YND_373, IHS_YND_375, IHS_EDA_101, IHS_YND_422","29-07-2025 14:=
56:41","29-07-2025 14:48:21","29-07-2025 16:38:43","Site went down due to i=
nsufficient of rectifiers , 01 rectifier over 04 tripped // Fault Rectifier=
 reseted.","Kemeni Franklin","Equipment Repair","Passive","Rectifier","Rect=
ifier Module Overloaded","Site went down due to insufficient rectifiers , 0=
1 rectifier over 04 tripped // Fault Rectifier reseted.","vanel.mbiada@mate=
ch-cameroun.com","500","29-07-2025 14:56:41","MATECH CMR"
"Cancelled","Warning","CTR_973","IHS_YND_796","NOCINC0005580896","Nkoabang =
Ebolmedjock","","29-07-2025 14:40:05","","","Rongly logged ticket","Mba Laz=
are Herve","","","","","","vanel.mbiada@matech-cameroun.com","15","29-07-20=
25 14:40:05","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005580840","N=
koabang Ebolmedjock","","29-07-2025 14:25:10","29-07-2025 14:19:04","29-07-=
2025 14:21:48","Site impacted by Nkolmesseng-Abom(CTR-711) Not Managed By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Site impacted by Nkolmesseng-Abom(CTR-71=
1) Not Managed By IHS","loic.noumsi@matech-cameroun.com","368","29-07-2025 =
14:25:10","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005580756","S=
ous Prefecture","","29-07-2025 14:15:36","29-07-2025 14:12:30","29-07-2025 =
14:15:45","No power issue site on Grid Ubaie =3D54.5V, The tx Huawei Fulber=
t (654266068) is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 Grid Ubaie =3D54.5V, The tx Huawei Fulbert (654266068) is informed","vanel=
.mbiada@matech-cameroun.com","187","29-07-2025 14:15:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005580669","Song-bon=
g","","29-07-2025 13:58:21","29-07-2025 13:53:52","29-07-2025 14:30:21","Ca=
scaded Incident from TTO5771210","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid  contactor faulty , site down =
because, gen fails to start due to grid contactor faulty  // Grid contactor=
 bypass ,site on grid.","vanel.mbiada@matech-cameroun.com","281563","29-07-=
2025 13:58:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005580668","Eseka To=
wn","","29-07-2025 13:58:21","29-07-2025 13:53:52","29-07-2025 14:30:21","C=
ascaded Incident from TTO5771210","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid  contactor faulty , site down=
 because, gen fails to start due to grid contactor faulty  // Grid contacto=
r bypass ,site on grid.","vanel.mbiada@matech-cameroun.com","281563","29-07=
-2025 13:58:21","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005580664","E=
seka OCM","IHS_YND_378, IHS_YND_453","29-07-2025 13:57:01","29-07-2025 13:5=
3:52","29-07-2025 14:30:21","Grid  contactor faulty , site down because, ge=
n fails to start due to grid contactor faulty  // Grid contactor bypass ,si=
te on grid.","Kemeni Franklin","Equipment Repair","Passive","Control Panel"=
,"ATS-AMF Issue","Grid  contactor faulty , site down because, gen fails to =
start due to grid contactor faulty  // Grid contactor bypass ,site on grid.=
","vanel.mbiada@matech-cameroun.com","190","29-07-2025 13:57:01","MATECH CM=
R"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005580601","F=
ouda-New","","29-07-2025 13:51:35","29-07-2025 13:50:49","29-07-2025 13:53:=
58","Grid outage, site went down before Gen start due to Poor battery backu=
p // Grid return","Delor Telezing","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before Gen =
start due to Poor battery backup // Grid return","vanel.mbiada@matech-camer=
oun.com","47","29-07-2025 13:51:35","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005580566","Eto=
udi","","29-07-2025 13:46:16","29-07-2025 13:38:10","29-07-2025 13:46:21","=
Grid outage,site went down due to gen overload(20kva,300 A) SS HIS Bernard =
Atangana is informed // Site stabilised","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage,site went down due t=
o gen overload(20kva,300 A) SS HIS Bernard Atangana is informed // Site sta=
bilised","loic.noumsi@matech-cameroun.com","487","29-07-2025 13:46:16","MAT=
ECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0005580553","Nlo=
ngkak","","29-07-2025 13:42:24","29-07-2025 13:34:19","29-07-2025 13:44:05"=
,"Grid outage, Site down due to poor battery backup // Gen start automatica=
lly","Delor Telezing","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, Site down due to poor battery backup //=
 Gen start automatically","loic.noumsi@matech-cameroun.com","486","29-07-20=
25 13:42:24","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005580523","Men=
dong Plateau","","29-07-2025 13:39:02","29-07-2025 13:30:55","29-07-2025 13=
:31:51","Grid fluctuation, Site went down because Gen failed to start due t=
o Grid bad voltage //Grid power stabilized","Hyemafo Gildas","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
n, Site went down because Gen failed to start due to Grid bad voltage //Gri=
d power stabilized","loic.noumsi@matech-cameroun.com","517","29-07-2025 13:=
39:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005580455","ELOUMDEM=
 CARRIERE 2","","29-07-2025 13:31:52","29-07-2025 13:26:31","29-07-2025 13:=
30:06","Cascaded Incident from TTO5770982","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid returned","loic.noumsi@matech-ca=
meroun.com","261519","29-07-2025 13:31:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005580454","Eto koss=
 Yde","","29-07-2025 13:31:52","29-07-2025 13:26:31","29-07-2025 13:30:06",=
"Cascaded Incident from TTO5770982","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Grid returned","loic.noumsi@matech-cameroun.=
com","261519","29-07-2025 13:31:52","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005580451","S=
atcom","","29-07-2025 13:30:59","29-07-2025 13:24:50","29-07-2025 15:24:23"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","vanel.mbiada@matech-ca=
meroun.com","371","29-07-2025 13:30:59","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005580449","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","29-07-2025 13:30:52","29-07-2025 13:26=
:31","29-07-2025 13:30:06","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","Fanda Brice","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Grid returned","loic.noumsi@matec=
h-cameroun.com","264","29-07-2025 13:30:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005580434","Nsam esc=
ale LP","","29-07-2025 13:28:55","29-07-2025 13:24:02","29-07-2025 13:30:26=
","Cascaded Incident from TTO5770955","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Site stabilised","loic.noumsi@matech-cameroun.com","2=
68594","29-07-2025 13:28:55","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005580427","Nsa=
m Sofavinc","IHS_YND_732","29-07-2025 13:28:16","29-07-2025 13:24:02","29-0=
7-2025 13:30:26","Grid Outage, Site went down before Gen start due to poor =
backup // Site stabilised","MINKA NICOLAS","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid Outage, Site went down bef=
ore Gen start due to poor backup // Site stabilised","loic.noumsi@matech-ca=
meroun.com","256","29-07-2025 13:28:16","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005580422","SIM=
BOCK BONAMBAPE","","29-07-2025 13:26:47","29-07-2025 13:23:40","29-07-2025 =
13:31:25","Grid outage, Site went down before Gen start due to poor backup =
// Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Site stabilised","loic.noumsi@matech-cameroun=
.com","188","29-07-2025 13:26:47","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005580340","Eto=
ug ebe Carrefour","","29-07-2025 13:08:44","29-07-2025 13:02:38","29-07-202=
5 13:10:49","Grid outage site went down before gen started due to poor batt=
ery backup // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before gen started due to poor battery backup // Site stabilised","loic.no=
umsi@matech-cameroun.com","367","29-07-2025 13:08:44","MATECH CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0005580339","Tsi=
nga","","29-07-2025 13:07:52","29-07-2025 13:06:45","29-07-2025 13:16:54","=
Site went down due to PWC dysfunctionning // Grid stabilised","Mboua Thierr=
y","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Site went down due to PWC dysfunctionning // Grid stabilised","loic.noumsi@=
matech-cameroun.com","69","29-07-2025 13:07:52","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005580305","Eto=
udi","","29-07-2025 13:00:20","29-07-2025 12:58:06","29-07-2025 13:25:38","=
Grid outage,site went down due to gen overload(20kva,300 A) SS HIS Bernard =
Atangana is informed//we reduced load and gen manually started.","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age,site went down due to gen overload(20kva,300 A) SS HIS Bernard Atangana=
 is informed//we reduced load and gen manually started.","loic.noumsi@matec=
h-cameroun.com","136","29-07-2025 13:00:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005580236","MEHANDAN=
","","29-07-2025 12:48:04","29-07-2025 12:42:28","29-07-2025 14:01:41","Cas=
caded Incident from TTO5770671","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, Site went down becau=
se gen fails to start due to grid bad voltage,// site on Grid","vanel.mbiad=
a@matech-cameroun.com","278518","29-07-2025 12:48:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005580165","Nkol-Meb=
anga","","29-07-2025 12:39:55","29-07-2025 12:30:42","29-07-2025 12:43:21",=
"Cascaded Incident from TTO5770649","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down and gen failed to s=
tart due to high temperature// We reduce two rack of batteries and site on =
gen","loic.noumsi@matech-cameroun.com","1214232","29-07-2025 12:39:55","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005580164","Carrefou=
r Ayissi Ele","","29-07-2025 12:39:54","29-07-2025 12:30:42","29-07-2025 12=
:43:21","Cascaded Incident from TTO5770649","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down and gen fai=
led to start due to high temperature// We reduce two rack of batteries and =
site on gen","loic.noumsi@matech-cameroun.com","1214231","29-07-2025 12:39:=
54","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005580136","S=
aa","IHS_YND_810, IHS_YND_809","29-07-2025 12:35:08","29-07-2025 12:30:42",=
"29-07-2025 12:43:21","Site went down and gen failed to start due to high t=
emperature// We reduce two rack of batteries and site on gen","Parker Tchou=
p","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Site went down =
and gen failed to start due to high temperature// We reduce two rack of bat=
teries and site on gen","vanel.mbiada@matech-cameroun.com","267","29-07-202=
5 12:35:08","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005580132","Odz=
a II OCM","IHS_YND_528","29-07-2025 12:34:33","29-07-2025 12:32:28","29-07-=
2025 14:14:09","Grid fluctuation, Site went down because gen fails to start=
 due to grid bad voltage,// site on Grid","Albran Byorel","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, =
Site went down because gen fails to start due to grid bad voltage,// site o=
n Grid","loic.noumsi@matech-cameroun.com","127","29-07-2025 12:34:33","MATE=
CH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005580078","Eto=
ug ebe Carrefour","","29-07-2025 12:26:07","29-07-2025 12:23:59","29-07-202=
5 12:33:23","Grid outage site went down before gen started due to poor batt=
ery backup // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before gen started due to poor battery backup // Site stabilised","loic.no=
umsi@matech-cameroun.com","129","29-07-2025 12:26:07","MATECH CMR"
"Closed Complete","Site Down","T0532","IHS_YND_239","NOCINC0005580057","Men=
dong2","","29-07-2025 12:23:07","29-07-2025 12:21:52","29-07-2025 12:33:51"=
,"Grid fluctuation site went down because Gen failed to start sue to poor b=
attery backup//Grid return","Hyemafo Gildas","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid fluctuation site went do=
wn because Gen failed to start sue to poor battery backup//Grid return","lo=
ic.noumsi@matech-cameroun.com","75","29-07-2025 12:23:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0005580050","SOA UNIV=
ERSITY STADIUM","","29-07-2025 12:21:32","29-07-2025 12:18:12","29-07-2025 =
12:24:21","Cascaded Incident from TTO5770516","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage.gen failed t=
o started sue to alarm ''underfrequency''//We reajust frquency and gen manu=
ally started","vanel.mbiada@matech-cameroun.com","265556","29-07-2025 12:21=
:32","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005580038","S=
oa-Sofamac","IHS_YND_720","29-07-2025 12:19:24","29-07-2025 12:18:12","29-0=
7-2025 12:24:21","Grid outage.gen failed to started sue to alarm ''underfre=
quency''//We reajust frquency and gen manually started","Siligap Boris","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.ge=
n failed to started sue to alarm ''underfrequency''//We reajust frquency an=
d gen manually started","vanel.mbiada@matech-cameroun.com","73","29-07-2025=
 12:19:24","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005579922","TON=
GOLO SNEC","","29-07-2025 11:57:58","29-07-2025 11:55:55","29-07-2025 14:35=
:29","Grid outage, site went down because Gen failed to start due to poor b=
attery backup // Gen manually started ","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down because Gen failed to start due to poor battery backup // Gen m=
anually started ","loic.noumsi@matech-cameroun.com","124","29-07-2025 11:57=
:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005579902","Mfou EPC=
","","29-07-2025 11:56:06","29-07-2025 11:50:44","29-07-2025 12:02:53","Cas=
caded Incident from TTO5770357","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to PM ( Q11 bypa=
ssed) done by our FME // end of work","vanel.mbiada@matech-cameroun.com","2=
67256","29-07-2025 11:56:06","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0005579894","Ngo=
usso-Savana","","29-07-2025 11:55:01","29-07-2025 11:53:55","29-07-2025 15:=
24:49","Active // No power issue, site is on grid with Ubaie: 55.2V, Sympho=
rien (650257151/691316854) from Huawei is informed.","Siligap Boris","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active // No power issue, site is on grid with Ubaie: 55.2V, Symphori=
en (650257151/691316854) from Huawei is informed.","loic.noumsi@matech-came=
roun.com","67","29-07-2025 11:55:01","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005579889","M=
fou OCM","IHS_YND_674","29-07-2025 11:54:00","29-07-2025 11:50:44","29-07-2=
025 12:02:53","Site went down due to PM ( Q11 bypassed) done by our FME // =
end of work","Mba Lazare Herve","Installation Activity","Passive","Planned =
Activity","Installation Activity","Site went down due to PM ( Q11 bypassed)=
 done by our FME // end of work","vanel.mbiada@matech-cameroun.com","198","=
29-07-2025 11:54:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0005579845","Nkolfoul=
ou Tsinga Village","","29-07-2025 11:46:11","29-07-2025 11:39:34","29-07-20=
25 11:53:18","Cascaded Incident from TTO5770284","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, Site wen=
t down because Gen failed to start due to ATS dysfunctioning // He configur=
ed ATS, Site on GRID","loic.noumsi@matech-cameroun.com","267686","29-07-202=
5 11:46:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005579842","Mvog-Eba=
nda","","29-07-2025 11:46:10","29-07-2025 11:39:34","29-07-2025 11:53:18","=
Cascaded Incident from TTO5770284","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen failed to start due to ATS dysfunctioning // He configured ATS, Site o=
n GRID","loic.noumsi@matech-cameroun.com","267689","29-07-2025 11:46:10","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005579844","SOA VILL=
AGE","","29-07-2025 11:46:10","29-07-2025 11:39:34","29-07-2025 11:53:18","=
Cascaded Incident from TTO5770284","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen failed to start due to ATS dysfunctioning // He configured ATS, Site o=
n GRID","loic.noumsi@matech-cameroun.com","267688","29-07-2025 11:46:10","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005579843","TSINGA V=
ILLAGE 2","","29-07-2025 11:46:10","29-07-2025 11:39:34","29-07-2025 11:53:=
18","Cascaded Incident from TTO5770284","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
ecause Gen failed to start due to ATS dysfunctioning // He configured ATS, =
Site on GRID","loic.noumsi@matech-cameroun.com","267685","29-07-2025 11:46:=
10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005579841","FOUGEROL=
E","","29-07-2025 11:46:09","29-07-2025 11:39:34","29-07-2025 11:53:18","Ca=
scaded Incident from TTO5770284","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down because G=
en failed to start due to ATS dysfunctioning // He configured ATS, Site on =
GRID","loic.noumsi@matech-cameroun.com","267690","29-07-2025 11:46:09","MAT=
ECH CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0005579819","Nko=
lfoulou 2","IHS_YND_561, IHS_YND_269, IHS_YND_719, IHS_YND_323, IHS_YND_296=
, IHS_YND_759","29-07-2025 11:42:39","29-07-2025 11:39:34","29-07-2025 11:5=
3:18","Grid outage, Site went down because Gen failed to start due to ATS d=
ysfunctioning // He configured ATS, Site on GRID","Siligap Boris","Equipmen=
t Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site went=
 down because Gen failed to start due to ATS dysfunctioning // He configure=
d ATS, Site on GRID","loic.noumsi@matech-cameroun.com","186","29-07-2025 11=
:42:39","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0005579812","Nko=
lfoulou","","29-07-2025 11:41:53","29-07-2025 11:39:34","29-07-2025 12:07:1=
6","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, Site went down because Gen failed to start due to A=
TS dysfunctioning // He configured ATS, Site on GRID","loic.noumsi@matech-c=
ameroun.com","267687","29-07-2025 11:41:53","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0005579799","Tsi=
nga village","","29-07-2025 11:39:14","29-07-2025 11:37:06","29-07-2025 11:=
39:21","Site went down due to poor backup battery // Site stabilised","Delo=
r Telezing","Equipment Repair","Passive","Control Panel","Power Cabinet - B=
attery Low","Site went down due to poor backup battery // Site stabilised",=
"loic.noumsi@matech-cameroun.com","129","29-07-2025 11:39:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005579790","Carrefou=
r Ayissi Ele","","29-07-2025 11:37:36","29-07-2025 11:31:19","29-07-2025 11=
:37:53","Cascaded Incident from TTO5770229","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage,site sent down=
 due to both conctators faulties //we bypass these contactors and put site =
on gen","loic.noumsi@matech-cameroun.com","268234","29-07-2025 11:37:36","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005579791","Nkol-Meb=
anga","","29-07-2025 11:37:36","29-07-2025 11:31:19","29-07-2025 11:37:53",=
"Cascaded Incident from TTO5770229","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,site sent down due to =
both conctators faulties //we bypass these contactors and put site on gen",=
"loic.noumsi@matech-cameroun.com","268233","29-07-2025 11:37:36","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0005579778","ETOUDI C=
HAPELLE","","29-07-2025 11:35:49","29-07-2025 11:27:45","29-07-2025 12:50:2=
4","Cascaded Incident from TTO5770173","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,site went down due=
 to gen overload(20kva,300 A) SS HIS Bernard Atangana is informed //we redu=
ced load and gen manually started. ","loic.noumsi@matech-cameroun.com","268=
552","29-07-2025 11:35:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0005579779","Etoudi 2=
","","29-07-2025 11:35:49","29-07-2025 11:27:45","29-07-2025 12:50:24","Cas=
caded Incident from TTO5770173","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,site went down due to ge=
n overload(20kva,300 A) SS HIS Bernard Atangana is informed //we reduced lo=
ad and gen manually started. ","loic.noumsi@matech-cameroun.com","268551","=
29-07-2025 11:35:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0005579777","Abattoir=
","","29-07-2025 11:35:48","29-07-2025 11:27:45","29-07-2025 12:50:24","Cas=
caded Incident from TTO5770173","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,site went down due to ge=
n overload(20kva,300 A) SS HIS Bernard Atangana is informed //we reduced lo=
ad and gen manually started. ","loic.noumsi@matech-cameroun.com","268551","=
29-07-2025 11:35:48","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005579768","Saa=
","IHS_YND_810, IHS_YND_809","29-07-2025 11:34:25","29-07-2025 11:31:19","2=
9-07-2025 11:37:53","Grid outage,site sent down due to both conctators faul=
ties //we bypass these contactors and put site on gen","Parker Tchoup","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,sit=
e sent down due to both conctators faulties //we bypass these contactors an=
d put site on gen","loic.noumsi@matech-cameroun.com","189","29-07-2025 11:3=
4:25","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005579720","E=
toudi","IHS_YND_244, IHS_YND_694, IHS_YND_211","29-07-2025 11:29:55","29-07=
-2025 11:27:45","29-07-2025 12:50:24","Grid outage,site went down due to ge=
n overload(20kva,300 A) SS HIS Bernard Atangana is informed //we reduced lo=
ad and gen manually started. ","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage,site went down due to gen over=
load(20kva,300 A) SS HIS Bernard Atangana is informed //we reduced load and=
 gen manually started. ","vanel.mbiada@matech-cameroun.com","131","29-07-20=
25 11:29:55","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005579571","A=
wae Ewonkan","","29-07-2025 11:16:00","29-07-2025 11:12:48","29-07-2025 11:=
20:31","Grid fluctuation, and Gen Overload (20Kva, Iload 320A)IHS SS Alphon=
se is informed// site stabilised","Albran Byorel","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid fluctuation, and Gen Overload (20Kva=
, Iload 320A)IHS SS Alphonse is informed// site stabilised","vanel.mbiada@m=
atech-cameroun.com","195","29-07-2025 11:16:00","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005579559","S=
oa-Sofamac","","29-07-2025 11:13:41","29-07-2025 11:10:50","29-07-2025 11:1=
4:10","Grid outage.gen failed to started sue to alarm ''underfrequency''//W=
e reajust frquency and gen manually started","Siligap Boris","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to=
 started sue to alarm ''underfrequency''//We reajust frquency and gen manua=
lly started","vanel.mbiada@matech-cameroun.com","172","29-07-2025 11:13:41"=
,"MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005579552","Eto=
ug ebe Carrefour","","29-07-2025 11:12:36","29-07-2025 11:11:32","29-07-202=
5 11:29:24","Grid outage site went down before gen started due to poor batt=
ery backup // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before gen started due to poor battery backup // Site stabilised","loic.no=
umsi@matech-cameroun.com","65","29-07-2025 11:12:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005579527","Messassi=
 okolo","","29-07-2025 11:07:05","29-07-2025 11:04:43","31-07-2025 00:45:58=
","Cascaded Incident from TTO5769953","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issue in the site at ni=
ght. Grid outage, site down because site behaves as Grid only site (Gen Noi=
se) // Grid return","vanel.mbiada@matech-cameroun.com","399605","29-07-2025=
 11:07:05","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005579520","E=
MANA BILICK CITY","IHS_YND_279","29-07-2025 11:05:53","29-07-2025 11:04:43"=
,"31-07-2025 00:54:59","Access issue in the site at night. Grid outage, sit=
e down because site behaves as Grid only site (Gen Noise) // Grid return","=
Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord Related Issues"=
,"Access Issue - Land Lord","Access issue in the site at night. Grid outage=
, site down because site behaves as Grid only site (Gen Noise) // Grid retu=
rn","vanel.mbiada@matech-cameroun.com","72","29-07-2025 11:05:53","MATECH C=
MR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005579185","E=
toudi","","29-07-2025 10:05:57","29-07-2025 10:04:34","29-07-2025 10:27:49"=
,"Site went down due to Circuit breaker (125A) dysfunctionned in PWC //We r=
earmed CB and site on gen","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down due =
to Circuit breaker (125A) dysfunctionned in PWC //We rearmed CB and site on=
 gen","vanel.mbiada@matech-cameroun.com","85","29-07-2025 10:05:57","MATECH=
 CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005579175","Hop=
ital Central","","29-07-2025 10:02:44","29-07-2025 10:01:39","29-07-2025 10=
:02:49","Site went down due to 03/05 rectifiers faulty // Site stabilised",=
"","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went d=
own due to 03/05 rectifiers faulty // Site stabilised","loic.noumsi@matech-=
cameroun.com","66","29-07-2025 10:02:44","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005579102","Evo=
doula MTN","","29-07-2025 09:49:25","29-07-2025 09:48:19","29-07-2025 10:06=
:17","Grid outage, site went down because Gen failed to start due to genera=
tor rack faulty which is dysfunctionning solenoid //Gen manually started","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - S=
olenoid Coil","Grid outage, site went down because Gen failed to start due =
to generator rack faulty which is dysfunctionning solenoid //Gen manually s=
tarted","loic.noumsi@matech-cameroun.com","67","29-07-2025 09:49:25","MATEC=
H CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005579037","TSI=
NGA VILLAGE 2","","29-07-2025 09:39:43","29-07-2025 09:34:39","29-07-2025 0=
9:44:06","Active//No power issue on site, Site on Gen UBAIE=3D54.5V TX FME =
Julien (693095849) From Huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue on site, Site on Battery UBAIE=3D54.5V TX FME Julien (=
693095849) From Huawei is informed","loic.noumsi@matech-cameroun.com","306"=
,"29-07-2025 09:39:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0005579025","Mendong =
Maeture","","29-07-2025 09:38:13","29-07-2025 09:30:55","29-07-2025 10:14:1=
1","Cascaded Incident from TTO5769361","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down due to =
Gen overload (15KVA//130A) // He reduced the load and started Gen manually"=
,"vanel.mbiada@matech-cameroun.com","268449","29-07-2025 09:38:13","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005579019","ELOUMDEM=
 CARRIERE 2","","29-07-2025 09:37:50","29-07-2025 09:32:24","29-07-2025 09:=
37:38","Cascaded Incident from TTO5769400","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid returned","loic.noumsi@matech-ca=
meroun.com","261224","29-07-2025 09:37:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005579018","Eto koss=
 Yde","","29-07-2025 09:37:50","29-07-2025 09:32:24","29-07-2025 09:37:38",=
"Cascaded Incident from TTO5769400","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Grid returned","loic.noumsi@matech-cameroun.=
com","261223","29-07-2025 09:37:50","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005579009","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","29-07-2025 09:36:31","29-07-2025 09:32=
:24","29-07-2025 09:37:38","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","Fanda Brice","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Grid returned","loic.noumsi@matec=
h-cameroun.com","249","29-07-2025 09:36:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005578999","Montee-J=
ouvence","","29-07-2025 09:34:41","29-07-2025 09:30:55","29-07-2025 10:14:1=
1","Cascaded Incident from TTO5769361","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down due to =
Gen overload (15KVA//130A) // He reduced the load and started Gen manually"=
,"vanel.mbiada@matech-cameroun.com","268449","29-07-2025 09:34:41","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0005578998","Mendong =
vallee","","29-07-2025 09:34:41","29-07-2025 09:30:55","29-07-2025 10:14:11=
","Cascaded Incident from TTO5769361","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to Gen =
overload (15KVA//130A) // He reduced the load and started Gen manually","va=
nel.mbiada@matech-cameroun.com","268450","29-07-2025 09:34:41","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005578976","M=
endong","IHS_YND_692, IHS_YND_569, IHS_YND_236","29-07-2025 09:33:02","29-0=
7-2025 09:30:55","29-07-2025 10:14:11","Grid outage, site down due to Gen o=
verload (15KVA//130A) // He reduced the load and started Gen manually","Hye=
mafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gri=
d outage, site down due to Gen overload (15KVA//130A) // He reduced the loa=
d and started Gen manually","vanel.mbiada@matech-cameroun.com","129","29-07=
-2025 09:33:02","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005578939","A=
wae Ewonkan","","29-07-2025 09:28:37","29-07-2025 09:26:27","29-07-2025 09:=
40:41","Grid fluctuation, and Gen Overload (20Kva, Iload 320A)IHS SS Alphon=
se is informed // site stabilised","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid fluctuation, and Gen Overload (20Kv=
a, Iload 320A)IHS SS Alphonse is informed // site stabilised","vanel.mbiada=
@matech-cameroun.com","133","29-07-2025 09:28:37","MATECH CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0005578937","Awa=
e Escalier","","29-07-2025 09:28:07","29-07-2025 09:25:02","29-07-2025 09:2=
9:40","grid outage, site went down due to gen Overload(20KVA, 300A) // Site=
 stabilised","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","grid outage, site went down due to gen Overload(20KVA, 300A) /=
/ Site stabilised","loic.noumsi@matech-cameroun.com","187","29-07-2025 09:2=
8:07","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005578886","Oko=
la","","29-07-2025 09:21:34","29-07-2025 09:20:27","29-07-2025 09:22:04","G=
rid outage, site went down before Gen start due to poor battery backup // G=
en automatically started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down before Gen start due to poor battery backup // Gen automatically sta=
rted","loic.noumsi@matech-cameroun.com","68","29-07-2025 09:21:34","MATECH =
CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0005578747","B=
riqueterie","","29-07-2025 08:53:17","29-07-2025 08:52:05","29-07-2025 08:5=
4:51","Active// No power issue, site is on Grid with Ubaie=3D53,4V, Brice T=
sague(650214096) from Huawei is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power =
issue, site is on Grid with Ubaie=3D53,4V, Brice Tsague(650214096) from Hua=
wei is informed","vanel.mbiada@matech-cameroun.com","74","29-07-2025 08:53:=
17","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005578724","A=
wae Ewonkan","","29-07-2025 08:47:16","29-07-2025 08:45:06","29-07-2025 08:=
53:25","Grid fluctuation, and Gen Overload (20Kva, Iload 320A)IHS SS Alphon=
se is informed // site stabilised","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid fluctuation, and Gen Overload (20Kv=
a, Iload 320A)IHS SS Alphonse is informed // site stabilised","vanel.mbiada=
@matech-cameroun.com","133","29-07-2025 08:47:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0005578679","Anguissa=
 New","","29-07-2025 08:39:37","29-07-2025 08:27:47","29-07-2025 08:59:01",=
"Cascaded Incident from TTO5768996","MINKA NICOLAS","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue U =3D54,6V site on Gri=
d. The Tx FME Eloundou (693212405 )from Huawei is informed","vanel.mbiada@m=
atech-cameroun.com","264955","29-07-2025 08:39:37","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005578651","L=
abogenie","IHS_YND_568","29-07-2025 08:35:10","29-07-2025 08:27:47","29-07-=
2025 08:59:01","No power issue U =3D54,6V site on Grid. The Tx FME Eloundou=
 (693212405 )from Huawei is informed","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D54=
,6V site on Grid. The Tx FME Eloundou (693212405 )from Huawei is informed",=
"vanel.mbiada@matech-cameroun.com","447","29-07-2025 08:35:10","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005578505","Nko=
lfoulou CSD MTN","","29-07-2025 08:03:50","29-07-2025 08:00:42","29-07-2025=
 08:04:31","Active//No power issue site with Ubaie=3D54,1V site on gen. The=
 Tx FME Symphorien //675295205 from Huawei is informed","Siligap Boris","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue site with Ubaie=3D54,1V site on gen. The Tx=
 FME Symphorien //675295205 from Huawei is informed","vanel.mbiada@matech-c=
ameroun.com","192","29-07-2025 08:03:50","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005578384","Mim=
boman","","29-07-2025 07:39:05","29-07-2025 07:35:59","29-07-2025 08:06:44"=
,"Grid outage, site went down because gen failed to start due to 1/3 rectif=
ier faulty // He replaced it, site on Grid","Mba Lazare Herve","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Grid outage, site went dow=
n because gen failed to start due to 1/3 rectifier faulty // He replaced it=
, site on Grid","loic.noumsi@matech-cameroun.com","187","29-07-2025 07:39:0=
5","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005578318","A=
wae Ewonkan","","29-07-2025 07:26:16","29-07-2025 07:24:05","29-07-2025 07:=
29:54","Grid fluctuation, and Gen Overload (20Kva, Iload 320A)IHS SS Alphon=
se is informed// grid return","Albran Byorel","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid fluctuation, and Gen Overload (20Kva, Il=
oad 320A)IHS SS Alphonse is informed// grid return","vanel.mbiada@matech-ca=
meroun.com","134","29-07-2025 07:26:16","MATECH CMR"
"Closed Complete","Site Down","T0292","IHS_YND_231","NOCINC0005578099","Nko=
lso","","29-07-2025 06:28:00","29-07-2025 06:26:51","29-07-2025 06:28:55","=
Grid outage, Site went down before Gen start due to poor backup/ // Gen aut=
omatically started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor backup/ // Gen automatically started","loic.n=
oumsi@matech-cameroun.com","70","29-07-2025 06:28:00","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005577376","Oko=
la","","29-07-2025 01:58:21","29-07-2025 01:53:10","29-07-2025 01:55:10","G=
rid outage, site went down before Gen start due to poor battery backup // G=
rid power return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen start due to poor battery backup // Grid power return","edwige.ka=
pawo@matech-cameroun.com","313","29-07-2025 01:58:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0005577370","AFEME NO=
RD","","29-07-2025 01:54:19","29-07-2025 01:44:54","29-07-2025 01:56:17","C=
ascaded Incident from TTO5767608","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
=3D53.8V site on grid Mohamadou (691144435/ huawei) is informed, Site impac=
ted by oyomabang_ctr_340","system","267549","29-07-2025 01:54:19","MATECH C=
MR"
"Closed Complete","Site Down","CTR_553","IHS_YND_686","NOCINC0005577358","O=
yomabang Ecole","IHS_YND_519, IHS_YND_232","29-07-2025 01:48:07","29-07-202=
5 01:44:54","29-07-2025 01:56:17","No power issue on site Ubaie=3D53.8V sit=
e on grid Mohamadou (691144435/ huawei) is informed, Site impacted by oyoma=
bang_ctr_340","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","Affected by 3rd Party Site","No power issue=
 on site Ubaie=3D53.8V site on grid Mohamadou (691144435/ huawei) is inform=
ed, Site impacted by oyomabang_ctr_340","edwige.kapawo@matech-cameroun.com"=
,"194","29-07-2025 01:48:07","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0005577351","C=
rf-Nkolbisson","","29-07-2025 01:46:34","29-07-2025 01:44:54","29-07-2025 0=
1:56:17","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue on site Ubaie=3D53.8V site on grid =
Mohamadou (691144435/ huawei) is informed, Site impacted by oyomabang_ctr_3=
40","edwige.kapawo@matech-cameroun.com","267548","29-07-2025 01:46:34","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0005577265","O=
yomabang OCM","","29-07-2025 00:56:07","29-07-2025 00:52:59","29-07-2025 01=
:01:56","Active // No power issue on site Ubaie=3D53.8V site on grid Mohama=
dou (691144435/ huawei) is informed","TIENTCHEU NZETCHIEU GAEL","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active // No power issue on site Ubaie=3D53.8V site on grid Mohamadou (691=
144435/ huawei) is informed","edwige.kapawo@matech-cameroun.com","189","29-=
07-2025 00:56:07","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005576996","O=
kola OCM","","28-07-2025 22:59:17","28-07-2025 22:51:06","29-07-2025 01:38:=
47","Grid outage, Site went down because Gen started and stopped with ""low=
 oil pressure"" alarm// He added oil and started Gen manualy","TIENTCHEU NZ=
ETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Press=
ure","Grid outage, Site went down because Gen started and stopped with ""lo=
w oil pressure"" alarm// He added oil and started Gen manualy","edwige.kapa=
wo@matech-cameroun.com","492","28-07-2025 22:59:17","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005576770","Eto=
ug ebe Carrefour","","28-07-2025 22:11:53","28-07-2025 22:08:46","28-07-202=
5 22:14:36","Grid outage site went down before gen started due to poor batt=
ery backup// Grid returned","Hyemafo Gildas","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage site went down be=
fore gen started due to poor battery backup// Grid returned","gerard.tchang=
oue@matech-cameroun.com","188","28-07-2025 22:11:53","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005576501","Eki=
e sud","","28-07-2025 21:26:52","28-07-2025 21:23:40","28-07-2025 21:39:05"=
,"Hybrid Gen, site went down because Gen failed to start due to disjunction=
 of CB (80A) in the PWC // He replaced with CB (125A), site on Gen","Albran=
 Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet - Circ=
uit Breaker Issue","Hybrid Gen, site went down because Gen failed to start =
due to disjunction of CB (80A) in the PWC // He replaced with CB (125A), si=
te on Gen","gerard.tchangoue@matech-cameroun.com","193","28-07-2025 21:26:5=
2","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005576498","Bit=
eng-Maetur","","28-07-2025 21:25:51","28-07-2025 21:17:44","28-07-2025 21:5=
5:56","Site went down due to disjunction of CB (125A) in the PWC // He rear=
med it, site on GRID","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of CB (125A) in the PWC // He rearmed it, site on GRID","gerard.=
tchangoue@matech-cameroun.com","489","28-07-2025 21:25:51","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005576436","TSI=
NGA VILLAGE 2","","28-07-2025 21:17:53","28-07-2025 21:11:46","28-07-2025 2=
2:18:50","Site went down due to disjunction of Cb(125A) in PWC // He reamed=
 Cb(125A), site on Gen","Delor Telezing","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of Cb(125A) in PWC // He reamed Cb(125A), site on Gen","gerard.t=
changoue@matech-cameroun.com","368","28-07-2025 21:17:53","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005576399","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","28-07-2025 21:13:52","28-07-2025 21:08=
:45","28-07-2025 21:12:25","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","Fanda Brice","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Grid returned","gerard.tchangoue@=
matech-cameroun.com","310","28-07-2025 21:13:52","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005576384","ELO=
UMDEM CARRIERE 2","","28-07-2025 21:13:03","28-07-2025 21:08:45","28-07-202=
5 21:12:25","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, Site went down before Gen start due to poor =
backup // Grid returned","gerard.tchangoue@matech-cameroun.com","269850","2=
8-07-2025 21:13:03","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0005576375","Eto=
 koss Yde","","28-07-2025 21:11:03","28-07-2025 21:08:45","28-07-2025 21:12=
:25","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, Site went down before Gen start due to poor backup =
// Grid returned","gerard.tchangoue@matech-cameroun.com","269851","28-07-20=
25 21:11:03","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005576340","Men=
dong NB","","28-07-2025 21:03:52","28-07-2025 19:13:53","28-07-2025 21:11:0=
3","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Si=
te went down due to Gen overload (17kva //180A) SS HIS Felix Zambe is infor=
med and confirmed // Grid stabilised","gerard.tchangoue@matech-cameroun.com=
","276488","28-07-2025 21:03:52","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005576333","Mim=
boman","","28-07-2025 21:03:11","28-07-2025 20:59:59","29-07-2025 06:55:54"=
,"Grid outage, site went down because gen failed to start due to 1/3 rectif=
ier faulty // He replaced it, site on Grid","Mba Lazare Herve","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Grid outage, site went dow=
n because gen failed to start due to 1/3 rectifier faulty // He replaced it=
, site on Grid","gerard.tchangoue@matech-cameroun.com","193","28-07-2025 21=
:03:11","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005576267","Eki=
e sud","","28-07-2025 20:50:28","28-07-2025 20:47:22","28-07-2025 21:15:29"=
,"Hybrid Gen, site went down because Gen failed to start due to disjunction=
 of CB (80A) in the PWC // He replaced with CB (125A), site on Gen","Albran=
 Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet - Circ=
uit Breaker Issue","Hybrid Gen, site went down because Gen failed to start =
due to disjunction of CB (80A) in the PWC // He replaced with CB (125A), si=
te on Gen","gerard.tchangoue@matech-cameroun.com","187","28-07-2025 20:50:2=
8","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0005576029","Val=
lee Bastos MTN","","28-07-2025 20:05:28","28-07-2025 20:00:12","29-07-2025 =
10:01:28","Grid outage, site went down due to insufficiency of rectifiers /=
/ he added 02 RECTIFIERS, site on GRID","Mboua Thierry","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","Grid outage, site went down due t=
o insufficiency of rectifiers // he added 02 RECTIFIERS, site on GRID","ger=
ard.tchangoue@matech-cameroun.com","317","28-07-2025 20:05:28","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005575824","ELO=
UMDEM CARRIERE","","28-07-2025 19:28:37","28-07-2025 19:27:26","28-07-2025 =
19:47:17","No power issue , Site on Grid and Ubaie=3D54.5V.site on gen. The=
 Tx Fme Fulbert //654266068 from Huawei is informed","Fanda Brice","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue , Site on Grid and Ubaie=3D54.5V.site on gen. The Tx Fme=
 Fulbert //654266068 from Huawei is informed","gerard.tchangoue@matech-came=
roun.com","73","28-07-2025 19:28:37","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005575737","Car=
refour Simbock","IHS_YND_742","28-07-2025 19:17:58","28-07-2025 19:13:53","=
28-07-2025 21:11:03","Site went down due to Gen overload (17kva //180A) SS =
HIS Felix Zambe is informed and confirmed // Grid stabilised","Hyemafo Gild=
as","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went do=
wn due to Gen overload (17kva //180A) SS HIS Felix Zambe is informed and co=
nfirmed // Grid stabilised","gerard.tchangoue@matech-cameroun.com","246","2=
8-07-2025 19:17:58","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005575724","N=
koabang2","","28-07-2025 19:15:27","28-07-2025 19:14:21","28-07-2025 19:19:=
25","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","gaelle=
.njiofack@matech-cameroun.com","68","28-07-2025 19:15:27","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005575690","Eto=
ug ebe Carrefour","","28-07-2025 19:10:33","28-07-2025 19:00:58","28-07-202=
5 19:18:29","No power issue on site Ubaie 53.4V site on Gen.TX FME Mouamado=
u(691144435) from hauwei is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site Ubaie 53.4V site on Gen.TX FME Mouamadou(691144435) from hau=
wei is informed","gaelle.njiofack@matech-cameroun.com","576","28-07-2025 19=
:10:33","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005575630","A=
wae Ewonkan","","28-07-2025 19:07:23","28-07-2025 19:06:16","28-07-2025 19:=
45:40","Grid fluctuation, and Gen Overload (20Kva, Iload 320A)IHS SS Alphon=
se is informed; // grid return","Albran Byorel","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid fluctuation, and Gen Overload (20Kva, =
Iload 320A)IHS SS Alphonse is informed; // grid return","gaelle.njiofack@ma=
tech-cameroun.com","69","28-07-2025 19:07:23","MATECH CMR"
"Closed Complete","Site Down","T2183","IHS_YND_089","NOCINC0005575483","H-P=
rince","","28-07-2025 18:44:18","28-07-2025 18:37:11","28-07-2025 19:18:09"=
,"Grid outage, site went down because gen failed to start due to grid conta=
ctor faulty // He bypassed it and He connected Grid directly.","Mboua Thier=
ry","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outa=
ge, site went down because gen failed to start due to grid contactor faulty=
 // He bypassed it and He connected Grid directly.","gerard.tchangoue@matec=
h-cameroun.com","428","28-07-2025 18:44:18","MATECH CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0005575478","Eko=
unou","","28-07-2025 18:43:03","28-07-2025 18:36:56","28-07-2025 20:02:43",=
"Grid outage, site went down because gen failed to ATS dysfunctionning // H=
e reset it and gen manually started","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","Grid outage, site went down because=
 gen failed to ATS dysfunctionning // He reset it and gen manually started"=
,"gerard.tchangoue@matech-cameroun.com","370","28-07-2025 18:43:03","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005575477","S=
IMBOCK BONAMBAPE","","28-07-2025 18:42:36","28-07-2025 18:40:58","28-07-202=
5 18:44:29","Grid outage, Site went down before Gen start due to poor backu=
p/ // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Grid return","gaelle.njiofack@matech-cameroun=
.com","100","28-07-2025 18:42:36","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0005575437","Val=
lee Bastos MTN","","28-07-2025 18:35:48","28-07-2025 18:31:38","28-07-2025 =
19:33:54","Site went down because insufficient of rectifier //site stabiliz=
ed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down because insufficient of rectifier //site st=
abilized","gerard.tchangoue@matech-cameroun.com","251","28-07-2025 18:35:48=
","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005575325","B=
arriere IHS","","28-07-2025 18:16:49","28-07-2025 18:16:44","28-07-2025 20:=
30:00","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due t=
o Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return",=
"gaelle.njiofack@matech-cameroun.com","7","28-07-2025 18:16:49","MATECH CMR=
"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0005575298","MAN=
GUIERS CHAPELLE","","28-07-2025 18:13:10","28-07-2025 18:12:03","28-07-2025=
 20:02:16","No power issue on site ,site on Grid with Ubaie=3D53.1 V The Tx=
 FME Symphorien (650257151 / Huawei) is informed","Fabrice Pouakam","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power issue on site ,site on Grid with Ubaie=3D53.1 V The Tx FME Sy=
mphorien (650257151 / Huawei) is informed","gerard.tchangoue@matech-camerou=
n.com","69","28-07-2025 18:13:10","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005575205","Hop=
ital Central","","28-07-2025 17:54:07","28-07-2025 17:52:32","28-07-2025 19=
:11:24","Grid fluctuation No Space to deploy a MDG // Grid restoration","",=
"Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue"=
,"Grid fluctuation No Space to deploy a MDG // Grid restoration","gaelle.nj=
iofack@matech-cameroun.com","96","28-07-2025 17:54:07","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005574972","M=
arche Odza","","28-07-2025 17:13:08","28-07-2025 17:06:01","28-07-2025 17:3=
6:35","No power issue on site Ubaie: 54 V site on Grid   The TX Lionel Stev=
e (655184876 /Huawei)) is informed.","Albran Byorel","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site Ubaie: 54 V site on Grid=20

The TX Lionel Steve (655184876 /Huawei)) is informed.
","gaelle.njiofack@matech-cameroun.com","429","28-07-2025 17:13:08","MATECH=
 CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0005574772","Tsi=
nga village","","28-07-2025 16:35:24","28-07-2025 16:31:18","28-07-2025 16:=
35:53","No power issue UBaie =3D55.2V site on Grid. The FME TX SYMPHORIEN (=
675295205) From Huawei is informed.","Delor Telezing","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue UBaie =3D55.2V site on Grid. The FME TX SYMPHORIEN (675295205) From H=
uawei is informed.","gaelle.njiofack@matech-cameroun.com","246","28-07-2025=
 16:35:24","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005574707","A=
hala","","28-07-2025 16:22:56","28-07-2025 16:19:04","28-07-2025 20:28:27",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","	Grid outage, site went down due to Gen overload (17KVA, 260A) SS =
HIS Felix Zambe is informed and confirmed // Grid return","gaelle.njiofack@=
matech-cameroun.com","279935","28-07-2025 16:22:56","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005574704","M=
eyo","IHS_YND_257","28-07-2025 16:22:13","28-07-2025 16:19:04","28-07-2025 =
20:35:55","	Grid outage, site went down due to Gen overload (17KVA, 260A) S=
S HIS Felix Zambe is informed and confirmed // Grid return","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","	Grid outage, =
site went down due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is info=
rmed and confirmed // Grid return","gaelle.njiofack@matech-cameroun.com","1=
90","28-07-2025 16:22:13","MATECH CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0005574697","Eto=
udi 2","","28-07-2025 16:20:27","28-07-2025 16:14:31","28-07-2025 16:57:12"=
,"","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid Fluctuation, Site went down because Gen failed to start due=
 to grid bad voltage // Grid stabilized","gerard.tchangoue@matech-cameroun.=
com","287462","28-07-2025 16:20:27","MATECH CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0005574694","ETO=
UDI CHAPELLE","","28-07-2025 16:19:55","28-07-2025 16:14:31","28-07-2025 16=
:57:12","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid Fluctuation, Site went down because Gen failed to sta=
rt due to grid bad voltage // Grid stabilized","gerard.tchangoue@matech-cam=
eroun.com","287460","28-07-2025 16:19:55","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005574692","Aba=
ttoir","","28-07-2025 16:19:24","28-07-2025 16:14:31","28-07-2025 16:57:12"=
,"","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid Fluctuation, Site went down because Gen failed to start due=
 to grid bad voltage // Grid stabilized","gerard.tchangoue@matech-cameroun.=
com","287461","28-07-2025 16:19:24","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005574683","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","28-07-2025 16:18:37","28-07-2=
025 16:14:31","28-07-2025 16:57:12","Grid Fluctuation, Site went down becau=
se Gen failed to start due to grid bad voltage // Grid stabilized","Fabrice=
 Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid Fluctuation, Site went down because Gen failed to start due t=
o grid bad voltage // Grid stabilized","gerard.tchangoue@matech-cameroun.co=
m","247","28-07-2025 16:18:37","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005574670","Lad=
a I Yde","","28-07-2025 16:16:43","28-07-2025 16:12:36","28-07-2025 17:16:5=
7","site went down due to 03/4 rectifiers malfunction // rectifiers reset",=
"Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Cabi=
net","site went down due to 03/4 rectifiers malfunction // rectifiers reset=
","gaelle.njiofack@matech-cameroun.com","248","28-07-2025 16:16:43","MATECH=
 CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005574528","Odz=
a II OCM","","28-07-2025 16:01:53","28-07-2025 15:53:42","28-07-2025 16:04:=
10","Site Went Down due to work , Judicael(656072620/Matech) wass on for wo=
rk(swap PWC)  // En of work","Albran Byorel","Equipment Replacement","Passi=
ve","Planned Activity","Planned Activity - Passive","Site Went Down due to =
work , Judicael(656072620/Matech) wass on for work(swap PWC)  // En of work=
","gerard.tchangoue@matech-cameroun.com","494","28-07-2025 16:01:53","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005574412","A=
fanoya","","28-07-2025 15:39:51","28-07-2025 15:37:33","28-07-2025 16:20:25=
","Grid outage,  generator did not start due to faulty battery // Gen start=
 with an external battery","Hyemafo Gildas","Equipment Repair","Passive","A=
CDG Gen","ACDG - Generator Battery","Grid outage,  generator did not start =
due to faulty battery // Gen start with an external battery","gaelle.njiofa=
ck@matech-cameroun.com","139","28-07-2025 15:39:51","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005574361","TON=
GOLO SNEC","","28-07-2025 15:32:09","28-07-2025 15:27:01","28-07-2025 17:09=
:39","Grid fluctuations, site went down due to Grid bad voltage and no rcp =
on site // He bypassed Grid and started Gen manually","Fabrice Pouakam","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuations, site went down due to Grid bad voltage and no rcp on site //=
 He bypassed Grid and started Gen manually","gerard.tchangoue@matech-camero=
un.com","309","28-07-2025 15:32:09","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005574085","Mok=
olo Yaounde","","28-07-2025 14:47:04","28-07-2025 14:37:53","28-07-2025 16:=
28:49"," No power issue Ubay: 54.V site on grid. The Tx FME Eloundou Bertra=
nd (693212405) from Huawei is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm"," No power issue Ubay=
: 54.V site on grid. The Tx FME Eloundou Bertrand (693212405) from Huawei i=
s informed","cedric.tiani@matech-cameroun.com","553","28-07-2025 14:47:04",=
"MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0005574083","Hop=
ital Central","","28-07-2025 14:46:32","28-07-2025 14:37:59","28-07-2025 15=
:01:26","Grid Outage No Space to deploy a MDG // Grid Restored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No =
Space to deploy a MDG // Grid Restored","cedric.tiani@matech-cameroun.com",=
"514","28-07-2025 14:46:32","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005574043","C=
NR","","28-07-2025 14:41:27","28-07-2025 14:39:18","28-07-2025 14:41:02","G=
rid outage, Site went down before Gen start due to poor backup// Gen automa=
tically started","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup// Gen automatically started","loic.noumsi@matech-cam=
eroun.com","130","28-07-2025 14:41:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005574032","Bastos-N=
ylon","","28-07-2025 14:40:11","28-07-2025 14:32:52","28-07-2025 14:40:08",=
"Cascaded Incident from TTO5763749","Mboua Thierry","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site Ubaie=3D51.V s=
ite on Grid The Tx Brice Tsgaue //650214096 of Huawei is informed.","system=
","439","28-07-2025 14:40:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005574033","Bastos B=
ethesda","","28-07-2025 14:40:11","28-07-2025 14:32:52","28-07-2025 14:40:0=
8","Cascaded Incident from TTO5763749","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site Ubaie=3D51.=
V site on Grid The Tx Brice Tsgaue //650214096 of Huawei is informed.","sys=
tem","439","28-07-2025 14:40:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005574031","Golf Qua=
ter","","28-07-2025 14:40:10","28-07-2025 14:32:52","28-07-2025 14:40:08","=
Cascaded Incident from TTO5763749","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site Ubaie=3D51.V si=
te on Grid The Tx Brice Tsgaue //650214096 of Huawei is informed.","system"=
,"438","28-07-2025 14:40:10","MATECH CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0005573890","Tsi=
nga","IHS_YND_220, IHS_YND_126, IHS_YND_563","28-07-2025 14:34:03","28-07-2=
025 14:32:52","28-07-2025 14:48:31","No power issue on site Ubaie=3D49.9.V =
site on Grid The Tx Brice Tsgaue //650214096 of Huawei is informed.","Mboua=
 Thierry","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue on site Ubaie=3D51.V site on Grid The =
Tx Brice Tsgaue //650214096 of Huawei is informed.","cedric.tiani@matech-ca=
meroun.com","73","28-07-2025 14:34:03","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005573878","Cit=
e des nations","","28-07-2025 14:33:31","28-07-2025 14:32:22","28-07-2025 1=
4:49:47","Grid outage,site went down before Gen started due to Poor battery=
 backup // Gen automatically started","Paul BIBOUM","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage,site went =
down before Gen started due to Poor battery backup // Gen automatically sta=
rted","cedric.tiani@matech-cameroun.com","70","28-07-2025 14:33:31","MATECH=
 CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005573624","Sim=
e Building","","28-07-2025 14:12:03","28-07-2025 14:10:54","28-07-2025 14:1=
8:36","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","cedric.tiani=
@matech-cameroun.com","70","28-07-2025 14:12:03","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005573309","Mok=
olo Yaounde","","28-07-2025 13:27:04","28-07-2025 13:25:31","28-07-2025 13:=
31:46","Active // No power issue Ubay: 54.6 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.6 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","cedric.tiani@matech-cameroun.com","95","=
28-07-2025 13:27:04","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005573041","N=
kolfon Cimencam","","28-07-2025 12:41:32","28-07-2025 12:39:21","28-07-2025=
 12:42:33","No power issue, Site is impacted by Afanoya II (Not manage by I=
HS)","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power issue, Site is impacted by Afano=
ya II (Not manage by IHS)","loic.noumsi@matech-cameroun.com","133","28-07-2=
025 12:41:32","MATECH CMR"
"Closed Complete","Warning","T1071","IHS_YND_343","NOCINC0005572778","Mbedo=
umou - Ekali","","28-07-2025 11:58:43","","","Site on battery FME is on sit=
e for PM // End of work","Albran Byorel","Warning","Warning","POWER","Warni=
ng - Planned Activity - Passive","Site on battery FME is on site for PM // =
End of work","loic.noumsi@matech-cameroun.com","8","28-07-2025 11:58:43","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005572550","N=
koabang Ebolmedjock","","28-07-2025 11:23:36","28-07-2025 11:22:20","28-07-=
2025 11:23:30","Site impacted by Nkolmesseng-Abom(CTR-711) Not Managed By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Site impacted by Nkolmesseng-Abom(CTR-71=
1) Not Managed By IHS","loic.noumsi@matech-cameroun.com","77","28-07-2025 1=
1:23:36","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005572403","E=
toudi","","28-07-2025 11:00:02","28-07-2025 10:58:34","28-07-2025 11:04:39"=
,"ACTIVE//No power issue on site, site is on Grid Ubaie =3D 53.8V TX FME Ar=
mand Nguetsa (699949553) from Huawei is informed","Fabrice Pouakam","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","ACTIVE//No power issue on site, site is on Grid Ubaie =3D 53.8V TX FME=
 Armand Nguetsa (699949553) from Huawei is informed","loic.noumsi@matech-ca=
meroun.com","91","28-07-2025 11:00:02","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005571502","O=
dza","","28-07-2025 08:33:37","28-07-2025 08:30:25","28-07-2025 08:35:51","=
Active/ No power issue on site, site on Grid, UbaIe 52.7V Lionel Adjep //65=
5184876 from Huawei is informed","Albran Byorel","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/ No pow=
er issue on site, site on Grid, UbaIe 52.7V Lionel Adjep //655184876 from H=
uawei is informed","cedric.tiani@matech-cameroun.com","193","28-07-2025 08:=
33:37","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005570920","NKO=
NGKARAK","","28-07-2025 05:40:01","28-07-2025 05:28:50","28-07-2025 07:10:0=
1","Grid outage, Gen started and stopped due to High temp alarm //He added =
water and Gen start manually","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid=
 outage, Gen started and stopped due to High temp alarm //He added water an=
d Gen start manually","gaelle.njiofack@matech-cameroun.com","4303","28-07-2=
025 05:40:01","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005570915","MBA=
LNGONG LYCEE","","28-07-2025 05:36:10","28-07-2025 04:43:56","28-07-2025 06=
:45:36","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid stabilised",=
"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, Site went down because Gen stopped due to overload(9kva, 130A) S=
S IHS Felix Zambe is informed and confirmed // Grid stabilised","gaelle.nji=
ofack@matech-cameroun.com","3136","28-07-2025 05:36:10","MATECH CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0005570584","M=
volye-New","","28-07-2025 03:08:22","28-07-2025 02:59:39","28-07-2025 04:14=
:50","Active// No power Issue Site on Grid Ubaie =3D52V, The TX FME Mbah Ho=
siah (674007438) is informed","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site o=
n Grid Ubaie =3D52V, The TX FME Mbah Hosiah (674007438) is informed","gaell=
e.njiofack@matech-cameroun.com","906","28-07-2025 03:08:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005570325","OTELE MT=
N","","28-07-2025 01:08:21","28-07-2025 01:00:44","28-07-2025 01:09:38","Ca=
scaded Incident from TTO5759843","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue, Site impacted by Ngoumou C=
amrail not managed by IHS","system","269982","28-07-2025 01:08:21","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005570326","Mom","",=
"28-07-2025 01:08:21","28-07-2025 01:00:44","28-07-2025 01:09:38","Cascaded=
 Incident from TTO5759843","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue, Site impacted by Ngoumou Camrail=
 not managed by IHS","system","269983","28-07-2025 01:08:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0005570327","Akono","=
","28-07-2025 01:08:21","28-07-2025 01:00:44","28-07-2025 01:09:38","Cascad=
ed Incident from TTO5759843","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue, Site impacted by Ngoumou Camra=
il not managed by IHS","system","269984","28-07-2025 01:08:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005570324","OLAMA","=
","28-07-2025 01:08:20","28-07-2025 01:00:44","28-07-2025 01:09:38","Cascad=
ed Incident from TTO5759843","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue, Site impacted by Ngoumou Camra=
il not managed by IHS","system","269981","28-07-2025 01:08:20","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0005570315","Min=
ka","IHS_YND_687, IHS_YND_531, IHS_YND_370, IHS_YND_365","28-07-2025 01:04:=
53","28-07-2025 01:00:44","28-07-2025 01:09:38","No power issue, Site impac=
ted by Ngoumou Camrail not managed by IHS","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","Affected by 3rd Party Site"=
,"No power issue, Site impacted by Ngoumou Camrail not managed by IHS","ger=
ard.tchangoue@matech-cameroun.com","250","28-07-2025 01:04:53","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005570073","Nko=
g-Edzen","","27-07-2025 23:41:07","27-07-2025 23:32:56","28-07-2025 00:31:3=
1","Grid outage. Gen started and stopped due to ""high temp"" alarm // He a=
dded water and Gen manually started","Parker Tchoup","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age. Gen started and stopped due to ""high temp"" alarm // He added water a=
nd Gen manually started","gerard.tchangoue@matech-cameroun.com","492","27-0=
7-2025 23:41:07","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005569962","Lad=
a I Yde","","27-07-2025 23:03:30","27-07-2025 22:56:04","27-07-2025 23:37:2=
7","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","gerard.tchangoue@matech-cameroun.com","447","27-07-2025 23:03:30","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005569934","M=
ontee-Des-Soeurs","","27-07-2025 22:49:51","27-07-2025 22:42:40","27-07-202=
5 22:56:42","Active // No power issue, site is on grid with Ubaie: 54.6V, M=
bah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active // No power issue, site is on grid with Ubaie: 54.6V, Mbah hosiah(6=
99699694) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","4=
33","27-07-2025 22:49:51","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005569233","A=
wae Ewonkan","","27-07-2025 20:38:04","27-07-2025 20:37:56","27-07-2025 21:=
37:08","Grid fluctuation, and Gen Overload (20Kva, Iload 320A)IHS SS Alphon=
se is informed; waiting grid return // Grid stabilized","Albran Byorel","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuation, a=
nd Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed; waiting gri=
d return // Grid stabilized","gaelle.njiofack@matech-cameroun.com","11","27=
-07-2025 20:38:04","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005569180","O=
dza II OCM","","27-07-2025 20:26:59","27-07-2025 20:25:49","27-07-2025 21:2=
1:38","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Site stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Site=
 stabilized","gaelle.njiofack@matech-cameroun.com","74","27-07-2025 20:26:5=
9","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005569138","MEHANDAN=
","","27-07-2025 20:17:31","27-07-2025 20:14:22","27-07-2025 20:17:18","Cas=
caded Incident from TTO5758532","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Site stabilized","sys=
tem","1215170","27-07-2025 20:17:31","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005569134","O=
dza II OCM","IHS_YND_528","27-07-2025 20:16:30","27-07-2025 20:14:22","27-0=
7-2025 20:17:18","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Site stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Site stabilized","gaelle.njiofack@matech-cameroun.com","132","27-07-=
2025 20:16:30","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005569001","Eli=
g Edzoa","","27-07-2025 19:44:30","27-07-2025 19:35:23","27-07-2025 19:47:4=
2","No power issue site on Grid with Ubay: 51.9V Tx Fme Armand Ngestsa (691=
144412 / huawei) is informed","Delor Telezing","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on Grid with Ubay: 51.9V Tx Fme Armand Ngestsa (691144412 / huawei) is =
informed","gerard.tchangoue@matech-cameroun.com","573","27-07-2025 19:44:30=
","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0005568967","A=
battoir","","27-07-2025 19:40:23","27-07-2025 19:38:10","27-07-2025 19:40:2=
9","Grid outage, site went down due to poor backup // Grid stabilised","Fab=
rice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Battery Low","Grid outage, site went down due to poor backup // Grid stabi=
lised","gaelle.njiofack@matech-cameroun.com","134","27-07-2025 19:40:23","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005568844","Messassi=
 okolo","","27-07-2025 19:16:10","27-07-2025 19:11:11","27-07-2025 19:26:27=
","Cascaded Incident from TTO5758203","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive"," Grid outage, site down becaus=
e due to grid outage // Grid restoration","system","269375","27-07-2025 19:=
16:10","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005568838","EMA=
NA BILICK CITY","IHS_YND_279","27-07-2025 19:14:17","27-07-2025 19:11:11","=
27-07-2025 19:32:57"," Grid only site , Grid outage, site down  due to grid=
 outage // Grid restoration","Fabrice Pouakam","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue"," Grid only site , Grid outage, site=
 down  due to grid outage // Grid restoration","gerard.tchangoue@matech-cam=
eroun.com","187","27-07-2025 19:14:17","MATECH CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0005568780","M=
bedoumou - Ekali","","27-07-2025 19:08:20","27-07-2025 14:06:12","27-07-202=
5 19:34:54","Backtracking // No power Ubaie=3D53,4V site on GRID The Tx FME=
 Rodrigue (651319438 // 655102999) from Huawei is informed and repport that=
, he will on site tomorrow in the morning.","Albran Byorel","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Bac=
ktracking // No power Ubaie=3D53,4V site on GRID The Tx FME Rodrigue (65131=
9438 // 655102999) from Huawei is informed and repport that, he will on sit=
e tomorrow in the morning.","gaelle.njiofack@matech-cameroun.com","18129","=
27-07-2025 19:08:20","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005568669","B=
arriere","","27-07-2025 18:49:41","27-07-2025 18:45:30","27-07-2025 18:51:5=
4","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed // Grid return","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because G=
en overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // Grid return","gae=
lle.njiofack@matech-cameroun.com","254","27-07-2025 18:49:41","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005568585","Aba=
ttoir","","27-07-2025 18:38:53","27-07-2025 18:37:46","27-07-2025 18:39:26"=
,"Grid outage, site went down due to poor backup // Grid stabilised","Fabri=
ce Pouakam","Equipment Repair","Passive","Control Panel","Power Cabinet - B=
attery Low","Grid outage, site went down due to poor backup // Grid stabili=
sed","gerard.tchangoue@matech-cameroun.com","68","27-07-2025 18:38:53","MAT=
ECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0005568262","Emo=
mbo Esssomba","","27-07-2025 17:39:06","27-07-2025 17:36:59","27-07-2025 19=
:25:36","Grid circuit breaker and site battery  stolen , site down because =
gen did not start due to battery stollen // Gen started with a backup batte=
ry","Mba Lazare Herve","Site Asset Theft","Theft","Theft","Generator Batter=
y Theft","Grid circuit breaker and site battery  stolen , site down because=
 gen did not start due to battery stollen // Gen started with a backup batt=
ery","gerard.tchangoue@matech-cameroun.com","128","27-07-2025 17:39:06","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0005568181","Akono","=
","27-07-2025 17:35:21","27-07-2025 17:25:51","27-07-2025 17:32:23","Cascad=
ed Incident from TTO5757418","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T169 Ngoumou not manage by IH=
S","system","261413","27-07-2025 17:35:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005568180","Mom","",=
"27-07-2025 17:35:21","27-07-2025 17:25:51","27-07-2025 17:32:23","Cascaded=
 Incident from TTO5757418","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Site impacted by T169 Ngoumou not manage by IHS"=
,"system","261412","27-07-2025 17:35:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005568179","Minka","=
","27-07-2025 17:35:20","27-07-2025 17:25:51","27-07-2025 17:32:23","Cascad=
ed Incident from TTO5757418","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T169 Ngoumou not manage by IH=
S","system","261414","27-07-2025 17:35:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005568178","OTELE MT=
N","","27-07-2025 17:35:20","27-07-2025 17:25:51","27-07-2025 17:32:23","Ca=
scaded Incident from TTO5757418","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by T169 Ngoumou not manage b=
y IHS","system","261412","27-07-2025 17:35:20","MATECH CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0005568125","OLA=
MA","IHS_YND_531, IHS_YND_371, IHS_YND_370, IHS_YND_365","27-07-2025 17:32:=
10","27-07-2025 17:25:51","27-07-2025 17:32:23","Site impacted by T169 Ngou=
mou not manage by IHS","Fanda Brice","Customer Equipment Failure","Active",=
"Active Equipment Failure","Affected by 3rd Party Site","Site impacted by T=
169 Ngoumou not manage by IHS","gerard.tchangoue@matech-cameroun.com","381"=
,"27-07-2025 17:32:10","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005568017","Par=
adis Hotel","","27-07-2025 17:22:16","27-07-2025 16:40:57","27-07-2025 18:3=
6:39","Site down at OWS Backtraking :Grid Outage, site went down because Ge=
n Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL ETCHEU is confirmed//Grid re=
turn","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Site down at OWS Backtraking :Grid Outage, site went down because Gen=
 Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL ETCHEU is confirmed//Grid ret=
urn","gerard.tchangoue@matech-cameroun.com","2480","27-07-2025 17:22:16","M=
ATECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0005567980","HOP=
ITAL GENERAL RAIL YDE","","27-07-2025 17:14:08","27-07-2025 17:09:36","27-0=
7-2025 18:39:31","","Delor Telezing","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen failed to=
 start due to gen card faulty // Grid restoration","gerard.tchangoue@matech=
-cameroun.com","269680","27-07-2025 17:14:08","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005567978","Pha=
rmacie Bleue","IHS_YND_801","27-07-2025 17:13:42","27-07-2025 17:09:36","27=
-07-2025 18:39:31","Grid outage, site went down because gen failed to start=
 due to gen card faulty // Grid restoration","Siligap Boris","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went do=
wn because gen failed to start due to gen card faulty // Grid restoration",=
"gerard.tchangoue@matech-cameroun.com","247","27-07-2025 17:13:42","MATECH =
CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005567854","Ngo=
usso Vallee","","27-07-2025 16:42:08","27-07-2025 16:39:02","27-07-2025 16:=
45:39","Grid outage, Site went down before Gen start due to poor backup// G=
en manally started","Siligap Boris","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup// Gen manally started","gerard.tchangoue@matech-c=
ameroun.com","186","27-07-2025 16:42:08","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005567851","Eli=
g Edzoa","","27-07-2025 16:41:27","27-07-2025 16:39:21","27-07-2025 16:52:5=
9","No power issue site on Grid with Ubay: 51.9V Tx Fme Armand Ngestsa (691=
144412 / huawei) is informed","Delor Telezing","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on Grid with Ubay: 51.9V Tx Fme Armand Ngestsa (691144412 / huawei) is =
informed","gerard.tchangoue@matech-cameroun.com","128","27-07-2025 16:41:27=
","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005567847","E=
toudi","","27-07-2025 16:40:48","27-07-2025 16:38:25","27-07-2025 16:41:11"=
,"Grid Fluctuation, site went down before Gen start due to poor battery bac=
kup // Gen Start automatically","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid Fluctuation, site w=
ent down before Gen start due to poor battery backup // Gen Start automatic=
ally","gaelle.njiofack@matech-cameroun.com","144","27-07-2025 16:40:48","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005567649","N=
koabang2","","27-07-2025 16:01:30","27-07-2025 15:58:03","27-07-2025 18:57:=
42","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","gaelle=
.njiofack@matech-cameroun.com","209","27-07-2025 16:01:30","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005567201","Nko=
lbong","","27-07-2025 14:34:29","27-07-2025 14:29:07","27-07-2025 14:35:46"=
,"Site went Down because Sylvain kamdem (BTR / 691901615) was on the way fo=
r work ( swap PWC and Generator) // End of work","Delor Telezing","Equipmen=
t Replacement","Passive","Planned Activity","Planned Activity - ACDG Replac=
ement","Site went Down because Sylvain kamdem (BTR / 691901615) was on the =
way for work ( swap PWC and Generator) // End of work","gaelle.njiofack@mat=
ech-cameroun.com","386","27-07-2025 14:34:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005567060","ELOUMDEM=
 CARRIERE 2","","27-07-2025 14:03:31","27-07-2025 13:57:58","27-07-2025 14:=
03:42","Cascaded Incident from TTO5756216","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid returned","system","266658","27-=
07-2025 14:03:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005567059","Eto koss=
 Yde","","27-07-2025 14:03:30","27-07-2025 13:57:58","27-07-2025 14:03:42",=
"Cascaded Incident from TTO5756216","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Grid returned","system","266659","27-07-2025=
 14:03:30","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005567031","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","27-07-2025 13:58:04","27-07-2025 13:=
57:58","27-07-2025 14:03:42","Grid outage, Site went down before Gen start =
due to poor backup // Grid returned","Fanda Brice","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup // Grid returned","edwige.kapawo@m=
atech-cameroun.com","9","27-07-2025 13:58:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005566566","MEHANDAN=
","","27-07-2025 12:23:00","27-07-2025 12:20:59","27-07-2025 12:23:52","Cas=
caded Incident from TTO5755655","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Site stabilized","sys=
tem","1214869","27-07-2025 12:23:00","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005566561","O=
dza II OCM","IHS_YND_528","27-07-2025 12:21:18","27-07-2025 12:20:59","27-0=
7-2025 12:23:52","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Site stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Site stabilized","edwige.kapawo@matech-cameroun.com","24","27-07-202=
5 12:21:18","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005566393","Evo=
doula MTN","","27-07-2025 11:57:04","27-07-2025 11:56:56","27-07-2025 12:16=
:04","Grid outage, Gen failed to start due to generator engine malfunction =
// Gen put on forced mode","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","P=
assive","ACDG Gen","ACDG - Priming Motor Faulty","Grid outage, Gen failed t=
o start due to generator engine malfunction // Gen put on forced mode","ced=
ric.tiani@matech-cameroun.com","9","27-07-2025 11:57:04","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005566291","ODZ=
A BORNE 10","","27-07-2025 11:47:22","27-07-2025 11:46:11","27-07-2025 11:5=
5:54","Grid outage, Site went down due to Gen overload (12.5 kva, 180A)//Gr=
id return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, Site went down due to Gen overload (12.5 kva, 180A)=
//Grid return","cedric.tiani@matech-cameroun.com","72","27-07-2025 11:47:22=
","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005566281","SIM=
BOCK BONAMBAPE","","27-07-2025 11:46:00","27-07-2025 11:37:41","27-07-2025 =
12:44:25","Active // No power issue site on grid with Ubaie: 54.4V TX FME F=
lubert (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue site on grid with Ubaie: 54.4V TX FME Flubert (654266068/=
Huawei) is informed","cedric.tiani@matech-cameroun.com","500","27-07-2025 1=
1:46:00","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005566150","Mon=
tee-Jouvence-II","","27-07-2025 11:14:13","27-07-2025 11:10:03","27-07-2025=
 11:16:23","Grid outage, Site went down before Gen start due to poor backup=
/ // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup/ // Grid return","cedric.tiani@matech-cameroun.com=
","251","27-07-2025 11:14:13","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005566138","SIM=
BOCK BONAMBAPE","","27-07-2025 11:12:07","27-07-2025 11:08:58","27-07-2025 =
11:14:39","Grid outage, Site went down before Gen start due to poor backup/=
 // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup/ // Grid return","cedric.tiani@matech-cameroun.com"=
,"191","27-07-2025 11:12:07","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005566134","C=
omplexe-BEAC","","27-07-2025 11:11:29","27-07-2025 11:09:21","27-07-2025 11=
:12:14","Grid outage, Site went down before Gen start due to Poor battery b=
ackup // Grid returned","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to Poor battery backup // Grid returned","edwige.kapawo@mate=
ch-cameroun.com","129","27-07-2025 11:11:29","MATECH CMR"
"Closed Complete","Site Down","T0715","IHS_YND_406","NOCINC0005565992","Mon=
atele","","27-07-2025 10:43:40","27-07-2025 10:42:29","27-07-2025 11:02:26"=
,"Site went down due to 01/03 rectifiers faulty on site SS HIS Felix Bateu =
is informed //He need to add 01","Parker Tchoup","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to 01/03 rectifiers f=
aulty on site SS HIS Felix Bateu is informed //He need to add 01","cedric.t=
iani@matech-cameroun.com","72","27-07-2025 10:43:40","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005565853","N=
koabang Ebolmedjock","","27-07-2025 10:28:32","27-07-2025 10:28:26","27-07-=
2025 11:29:31","Site impacted by Nkolmesseng-Abom(CTR-711) Not Managed By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","Site impacted by Nkolmesseng-Abo=
m(CTR-711) Not Managed By IHS","edwige.kapawo@matech-cameroun.com","8","27-=
07-2025 10:28:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005565658","OTELE MT=
N","","27-07-2025 09:44:39","27-07-2025 09:39:29","27-07-2025 09:43:55","Ca=
scaded Incident from TTO5754643","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by T0169 Ngoumou not manage =
by IHS","system","260809","27-07-2025 09:44:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005565649","Minka","=
","27-07-2025 09:43:20","27-07-2025 09:39:29","27-07-2025 09:43:55","Cascad=
ed Incident from TTO5754643","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by I=
HS","system","260810","27-07-2025 09:43:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005565650","Mom","",=
"27-07-2025 09:43:20","27-07-2025 09:39:29","27-07-2025 09:43:55","Cascaded=
 Incident from TTO5754643","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by IHS=
","system","260810","27-07-2025 09:43:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005565648","OLAMA","=
","27-07-2025 09:43:19","27-07-2025 09:39:29","27-07-2025 09:43:55","Cascad=
ed Incident from TTO5754643","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by T0169 Ngoumou not manage by I=
HS","system","260808","27-07-2025 09:43:19","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005565642","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","27-07-2025 09:41:=
39","27-07-2025 09:39:29","27-07-2025 09:43:55","Site impacted by T0169 Ngo=
umou not manage by IHS","Fanda Brice","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Site impacted by T0169 Ng=
oumou not manage by IHS","cedric.tiani@matech-cameroun.com","131","27-07-20=
25 09:41:39","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005565397","Eli=
g Edzoa","","27-07-2025 09:07:04","27-07-2025 09:03:57","27-07-2025 11:18:3=
3","Active // No power issue site on Grid with Ubay: 51.9V Tx Fme Armand Ng=
estsa (691144412 / huawei) is informed","Delor Telezing","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue site on Grid with Ubay: 51.9V Tx Fme Armand Ngestsa (691=
144412 / huawei) is informed","edwige.kapawo@matech-cameroun.com","188","27=
-07-2025 09:07:04","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005565289","N=
koabang2","","27-07-2025 08:54:09","27-07-2025 08:48:59","27-07-2025 09:49:=
50","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // He reduced load, Gen started manually","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
, site went down due to gen overload (22KVA, 330A), SS Blaise IHS is inform=
ed // He reduced load, Gen started manually","edwige.kapawo@matech-cameroun=
.com","312","27-07-2025 08:54:09","MATECH CMR"
"Closed Complete","Site Down","T0715","IHS_YND_406","NOCINC0005565208","Mon=
atele","","27-07-2025 08:38:20","27-07-2025 08:33:20","27-07-2025 10:07:32"=
,"Site went down due to 01/03 rectifiers faulty on site SS HIS Felix Bateu =
is informed //He need to add 01","Parker Tchoup","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to 01/03 rectifiers f=
aulty on site SS HIS Felix Bateu is informed //He need to add 01","cedric.t=
iani@matech-cameroun.com","301","27-07-2025 08:38:20","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005565188","Oko=
la","","27-07-2025 08:32:46","27-07-2025 08:31:59","27-07-2025 08:33:18","A=
ctive//No power issue on site ubaie=3D54,6V site on Gen The TX FME Mouhamad=
ou //691144435// from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue on site ubaie=3D54,6V site on Gen The TX FME M=
ouhamadou //691144435// from Huawei is informed","edwige.kapawo@matech-came=
roun.com","48","27-07-2025 08:32:46","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005565182","O=
dza","","27-07-2025 08:31:50","27-07-2025 08:30:59","27-07-2025 13:10:33","=
Active//No power issue on site Ubaie: 53 V site on Grid The TX Lionel steve=
 (655184876 /Huawei)) is informed","Albran Byorel","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue on site Ubaie: 53 V site on Grid The TX Lionel steve (655184876 =
/Huawei)) is informed","edwige.kapawo@matech-cameroun.com","52","27-07-2025=
 08:31:50","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005565116","ODZ=
A BORNE 10","","27-07-2025 08:12:50","27-07-2025 08:09:42","27-07-2025 10:4=
5:19","Grid outage, Site went down due to Gen overload (12.5 kva, 180A)//Gr=
id return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, Site went down due to Gen overload (12.5 kva, 180A)=
//Grid return","edwige.kapawo@matech-cameroun.com","189","27-07-2025 08:12:=
50","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005565093","M=
arche Odza","","27-07-2025 08:04:18","27-07-2025 07:58:04","27-07-2025 08:2=
5:24","Grid outage, site went down because gen start and stopped with over =
voltage alarm // He reset it and manually start the gen","Albran Byorel","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, =
site went down because gen start and stopped with over voltage alarm // He =
reset it and manually start the gen","edwige.kapawo@matech-cameroun.com","3=
78","27-07-2025 08:04:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005565061","MEHANDAN=
","","27-07-2025 07:55:10","27-07-2025 07:50:35","27-07-2025 08:29:12","Cas=
caded Incident from TTO5754013","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because Gen failed to s=
tart because ATS dysfunction//He reset it and site on Grid","system","12167=
22","27-07-2025 07:55:10","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005565036","B=
arriere","","27-07-2025 07:50:08","27-07-2025 07:47:57","27-07-2025 08:53:2=
3","Grid outage, site went down because gen start and stopped with Gen over=
 voltage alarm // He reset it and manually start the gen","Hyemafo Gildas",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
, site went down because gen start and stopped with Gen over voltage alarm =
// He reset it and manually start the gen","edwige.kapawo@matech-cameroun.c=
om","135","27-07-2025 07:50:08","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005564913","Odz=
a II OCM","IHS_YND_528","27-07-2025 07:21:44","27-07-2025 07:15:35","27-07-=
2025 08:35:43","Site went down because Gen failed to start because ATS dysf=
unction//He reset it and site on Grid","Albran Byorel","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Site went down because Gen failed=
 to start because ATS dysfunction//He reset it and site on Grid","cedric.ti=
ani@matech-cameroun.com","371","27-07-2025 07:21:44","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005564764","E=
koumdoum OCM","","27-07-2025 06:26:44","27-07-2025 06:16:59","27-07-2025 07=
:15:23","Grid outage, site went down because Gen failed to start due to ''u=
nknow '' alarm // MTN prefilter bypass & DG card reseted and Gen manually s=
tarted","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","Grid outage, site went down because Gen failed to start due to=
 ''unknow '' alarm // MTN prefilter bypass & DG card reseted and Gen manual=
ly started","gaelle.njiofack@matech-cameroun.com","587","27-07-2025 06:26:4=
4","MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0005564496","B=
astos Bir","","27-07-2025 04:22:00","27-07-2025 03:57:26","27-07-2025 04:34=
:35","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid bad voltage,site down because,gen fails to start due to g=
rid bad voltage // Grid bypass. site left on gen","alexandre.kamal@ihstower=
s.com","317283","27-07-2025 04:22:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0005564473","ARMP",""=
,"27-07-2025 04:07:50","27-07-2025 03:57:26","27-07-2025 04:34:35","Cascade=
d Incident from TTO5753347","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid bad voltage,site down because,gen fails to start d=
ue to grid bad voltage // Grid bypass. site left on gen","system","317282",=
"27-07-2025 04:07:50","MATECH CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0005564463","Dra=
gage","IHS_YND_704, IHS_YND_208","27-07-2025 04:03:38","27-07-2025 03:57:26=
","27-07-2025 06:47:32","Grid bad voltage,site down because,gen fails to st=
art due to grid bad voltage // Grid bypass. site left on gen","Mboua Thierr=
y","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid bad voltage,site down because,gen fails to start due to grid bad vol=
tage // Grid bypass. site left on gen","gerard.tchangoue@matech-cameroun.co=
m","373","27-07-2025 04:03:38","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005563653","Car=
refour Simbock","","26-07-2025 22:40:59","26-07-2025 22:37:40","26-07-2025 =
22:50:06","Site went down due to Gen overload (17kva //180A) SS HIS Felix Z=
ambe is informed and confirmed // Grid stabilised","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Site went down due to G=
en overload (17kva //180A) SS HIS Felix Zambe is informed and confirmed // =
Grid stabilised","vanel.mbiada@matech-cameroun.com","199","26-07-2025 22:40=
:59","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005563507","MEF=
OU ASSI","","26-07-2025 22:07:15","26-07-2025 22:02:22","26-07-2025 22:07:3=
8","Grid outage, Site went down before Gen start due to poor backup // Grid=
 returned","Fanda Brice","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, Site went down before Gen start due =
to poor backup // Grid returned","vanel.mbiada@matech-cameroun.com","295","=
26-07-2025 22:07:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005563308","MEHANDAN=
","","26-07-2025 21:26:20","26-07-2025 21:16:20","26-07-2025 21:19:45","Cas=
caded Incident from TTO5752063","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site down because gen fai=
led to start due to Pwc ZTE dysfunction// he reset it and started Gen manua=
ly","system","262205","26-07-2025 21:26:20","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005563305","O=
dza II OCM","IHS_YND_528","26-07-2025 21:25:30","26-07-2025 21:16:20","26-0=
7-2025 21:19:45","Grid outage, site down because gen failed to start due to=
 Pwc ZTE dysfunction// he reset it and started Gen manualy","Albran Byorel"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage, site down because gen failed to start due to Pwc ZTE dysfunction=
// he reset it and started Gen manualy","gaelle.njiofack@matech-cameroun.co=
m","553","26-07-2025 21:25:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0005563151","Nkenglik=
ok","","26-07-2025 20:55:00","26-07-2025 20:37:48","26-07-2025 20:55:05","C=
ascaded Incident from TTO5751833","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V si=
te on Grid; TX FME Flubert (654266068/Huawei) is informed","system","264498=
","26-07-2025 20:55:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_010","NOCINC0005563134","CNR","",=
"26-07-2025 20:51:40","26-07-2025 20:37:48","26-07-2025 20:56:36","Error lo=
gger ticket","Mboua Thierry","Incorrectly Logged Tickets","Error","Error","=
Error","No power issue on site Ubaie 54.5V site on Grid; TX FME Flubert (65=
4266068/Huawei) is informed","system","832","26-07-2025 20:51:40","MATECH C=
MR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005563093","N=
omayos-IHS","IHS_YND_314, IHS_YND_348","26-07-2025 20:46:03","26-07-2025 20=
:37:48","26-07-2025 20:55:05","No power issue on site Ubaie 54.5V site on G=
rid; TX FME Flubert (654266068/Huawei) is informed","Fanda Brice","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site Ubaie 54.5V site on Grid; TX FME Flubert (6542660=
68/Huawei) is informed","gaelle.njiofack@matech-cameroun.com","497","26-07-=
2025 20:46:03","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005563012","Nko=
lbisson IITA LP","","26-07-2025 20:31:52","26-07-2025 20:29:36","26-07-2025=
 20:37:27","No power issue site on grid with U=3D53.8v Mohamadou(69114435) =
from Huawei is informed.Noticed that it is impacted by Nkolbisson 2 ocm not=
 manage by IHS","","Customer Equipment Failure","Active","Active Equipment =
Failure","Affected by 3rd Party Site","No power issue site on grid with U=
=3D53.8v Mohamadou(69114435) from Huawei is informed.Noticed that it is imp=
acted by Nkolbisson 2 ocm not manage by IHS","vanel.mbiada@matech-cameroun.=
com","137","26-07-2025 20:31:52","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005562988","M=
EFOU ASSI","","26-07-2025 20:28:27","26-07-2025 20:21:21","26-07-2025 20:29=
:30","Grid outage, Site went down before Gen start due to poor backup // Gr=
id returned","Fanda Brice","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","gaelle.njiofack@matech-cameroun.com","4=
28","26-07-2025 20:28:27","MATECH CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0005562933","N=
kongtock","","26-07-2025 20:20:25","26-07-2025 20:14:17","26-07-2025 20:21:=
12","No power issue on site Ubaie=3D50.9V site on Gen The Tx FME Etienne//6=
95033981 from Huawei is informed","Kemeni Franklin","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site Ubaie=3D50.9V site on Gen The Tx FME Etienne//695033981 from Hu=
awei is informed","gaelle.njiofack@matech-cameroun.com","370","26-07-2025 2=
0:20:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005562886","MEHANDAN=
","","26-07-2025 20:13:59","26-07-2025 20:10:29","26-07-2025 20:13:42","Cas=
caded Incident from TTO5751587","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site down because gen fai=
led to start due to Pwc ZTE dysfunction// he reset it and started Gen manua=
ly","system","266109","26-07-2025 20:13:59","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005562876","O=
dza II OCM","IHS_YND_528","26-07-2025 20:12:36","26-07-2025 20:10:29","26-0=
7-2025 20:13:42","Grid outage, site down because gen failed to start due to=
 Pwc ZTE dysfunction// he reset it and started Gen manualy","Albran Byorel"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage, site down because gen failed to start due to Pwc ZTE dysfunction=
// he reset it and started Gen manualy","gaelle.njiofack@matech-cameroun.co=
m","130","26-07-2025 20:12:36","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005562825","Bar=
riere","","26-07-2025 20:03:46","26-07-2025 20:00:37","26-07-2025 21:15:05"=
,"Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS Fel=
ix ZAMBE confirmed// Grid return","Hyemafo Gildas","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen =
overload (30kva, 410A) SS IHS Felix ZAMBE confirmed// Grid return","vanel.m=
biada@matech-cameroun.com","190","26-07-2025 20:03:46","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005562767","N=
kolbong","","26-07-2025 19:51:35","26-07-2025 19:47:27","27-07-2025 10:13:1=
5","Site went Down because Sylvain kamdem (BTR / 691901615) was on the way =
for work ( swap PWC and Generator) // End of work","Delor Telezing","Equipm=
ent Replacement","Passive","Planned Activity","Planned Activity - Passive",=
"Site went Down because Sylvain kamdem (BTR / 691901615) was on the way for=
 work ( swap PWC and Generator) // End of work","vanel.mbiada@matech-camero=
un.com","250","26-07-2025 19:51:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005562685","MEHANDAN=
","","26-07-2025 19:36:50","26-07-2025 19:31:17","26-07-2025 19:34:45","Cas=
caded Incident from TTO5751343","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site down because gen fai=
led to start due to Pwc ZTE dysfunction// he reset it and started Gen manua=
ly","system","261342","26-07-2025 19:36:50","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005562683","Car=
refour Simbock","","26-07-2025 19:36:21","26-07-2025 19:35:10","26-07-2025 =
20:34:23","Site went down due to Gen overload (17kva //180A) SS HIS Felix Z=
ambe is informed and confirmed// Grid stabilised","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Site went down due to Ge=
n overload (17kva //180A) SS HIS Felix Zambe is informed and confirmed// Gr=
id stabilised","vanel.mbiada@matech-cameroun.com","72","26-07-2025 19:36:21=
","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005562658","O=
dza II OCM","IHS_YND_528","26-07-2025 19:35:26","26-07-2025 19:31:17","26-0=
7-2025 19:34:45","Grid outage, site down because gen failed to start due to=
 Pwc ZTE dysfunction// he reset it and started Gen manualy","Albran Byorel"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage, site down because gen failed to start due to Pwc ZTE dysfunction=
// he reset it and started Gen manualy","gaelle.njiofack@matech-cameroun.co=
m","252","26-07-2025 19:35:26","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005562637","S=
IMBOCK BONAMBAPE","","26-07-2025 19:30:02","26-07-2025 19:26:56","26-07-202=
5 20:28:20","Grid outage, Site went down before Gen start due to poor backu=
p/ //  Awaiting Grid return","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup/ //  Awaiting Grid return","gaelle.njio=
fack@matech-cameroun.com","189","26-07-2025 19:30:02","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005562617","Jou=
vence Mbenda","","26-07-2025 19:26:41","26-07-2025 19:23:58","26-07-2025 20=
:04:06","Grid outage.gen start and stopped due to alarm""high temp""//Grid =
return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Hi=
gh Engine Temp - Coolant Level Issue","Grid outage.gen start and stopped du=
e to alarm""high temp""//Grid return","vanel.mbiada@matech-cameroun.com","1=
64","26-07-2025 19:26:41","MATECH CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0005562587","Sim=
bock MTN","IHS_YND_793","26-07-2025 19:23:07","26-07-2025 19:19:56","26-07-=
2025 19:45:28","Grid outage, Site went down because Gen failed to start due=
 to battery Gen Faulty// He started Gen with external battery","Fanda Brice=
","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator","Gri=
d outage, Site went down because Gen failed to start due to battery Gen Fau=
lty// He started Gen with external battery","vanel.mbiada@matech-cameroun.c=
om","192","26-07-2025 19:23:07","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005562578","A=
wae Ewonkan","","26-07-2025 19:22:19","26-07-2025 19:20:00","26-07-2025 19:=
23:08","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid returned","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due=
 to Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid ret=
urned","gaelle.njiofack@matech-cameroun.com","141","26-07-2025 19:22:19","M=
ATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005562573","Elo=
umdem stade","","26-07-2025 19:21:44","26-07-2025 19:19:56","26-07-2025 19:=
45:28","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, Site went down because Gen failed to start due to=
 battery Gen Faulty// He started Gen with external battery","vanel.mbiada@m=
atech-cameroun.com","269105","26-07-2025 19:21:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005562542","MEHANDAN=
","","26-07-2025 19:15:51","26-07-2025 19:09:58","26-07-2025 19:12:37","Cas=
caded Incident from TTO5751211","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site  down because gen fa=
iled to start due to Pwc ZTE dysfunction// he reset it and started Gen manu=
aly","system","262612","26-07-2025 19:15:51","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005562537","O=
dza II OCM","IHS_YND_528","26-07-2025 19:15:04","26-07-2025 19:09:58","26-0=
7-2025 19:12:37","Grid outage, site  down because gen failed to start due t=
o Pwc ZTE dysfunction// he reset it and started Gen manualy","Albran Byorel=
","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","G=
rid outage, site  down because gen failed to start due to Pwc ZTE dysfuncti=
on// he reset it and started Gen manualy","gaelle.njiofack@matech-cameroun.=
com","310","26-07-2025 19:15:04","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0005562472","Mon=
tee-Jouvence-II","","26-07-2025 19:04:00","26-07-2025 19:01:01","26-07-2025=
 19:49:01","Grid outage gen failed to start due to battery GE discharged ca=
using by battery charger faulty// He started Gen with an external batttery"=
,"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Generator=
 Battery","Grid outage gen failed to start due to battery GE discharged cau=
sing by battery charger faulty// He started Gen with an external batttery",=
"vanel.mbiada@matech-cameroun.com","181","26-07-2025 19:04:00","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005562440","SIM=
BOCK BONAMBAPE","","26-07-2025 19:00:02","26-07-2025 18:59:58","26-07-2025 =
19:09:12","Grid outage, Site went down before Gen start due to poor backup/=
 // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup/ // Grid return","vanel.mbiada@matech-cameroun.com"=
,"6","26-07-2025 19:00:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005562317","Mfou EPC=
","","26-07-2025 18:34:50","26-07-2025 18:32:47","26-07-2025 18:38:04","Cas=
caded Incident from TTO5750957","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Grid return","system","264808","26-07-2025 18:=
34:50","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005562312","M=
fou OCM","IHS_YND_674","26-07-2025 18:33:55","26-07-2025 18:32:47","26-07-2=
025 18:38:04","Grid Outage, Site Down before gen Started due to poor backup=
 // Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Star=
ted due to poor backup // Grid return","gaelle.njiofack@matech-cameroun.com=
","69","26-07-2025 18:33:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005561929","Mfou EPC=
","","26-07-2025 17:23:30","26-07-2025 17:17:57","26-07-2025 17:23:30","Cas=
caded Incident from TTO5750503","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Grid return","system","262087","26-07-2025 17:=
23:30","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005561905","M=
fou OCM","IHS_YND_674","26-07-2025 17:19:03","26-07-2025 17:17:57","26-07-2=
025 17:23:30","Grid Outage, Site Down before gen Started due to poor backup=
 // Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Star=
ted due to poor backup // Grid return","gaelle.njiofack@matech-cameroun.com=
","67","26-07-2025 17:19:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005561882","Nkolfon =
Cimencam","","26-07-2025 17:14:50","26-07-2025 17:09:52","26-07-2025 19:02:=
09","Cascaded Incident from TTO5750445","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirm=
ed // Grid return","system","269720","26-07-2025 17:14:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005561881","Ahala","=
","26-07-2025 17:14:50","26-07-2025 17:09:52","26-07-2025 19:02:09","Cascad=
ed Incident from TTO5750445","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Gen o=
verload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid =
return","system","269721","26-07-2025 17:14:50","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005561854","M=
eyo","IHS_YND_257, IHS_YND_762","26-07-2025 17:12:11","26-07-2025 17:09:52"=
,"26-07-2025 19:09:21","Grid outage, site went down due to Gen overload (17=
KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid return","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix Za=
mbe is informed and confirmed // Grid return","gaelle.njiofack@matech-camer=
oun.com","141","26-07-2025 17:12:11","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005561841","E=
toudi","","26-07-2025 17:08:47","26-07-2025 17:06:40","26-07-2025 17:08:36"=
,"Grid Fluctuation, site went down before Gen start due to poor battery bac=
kup // Grid restoration","Fabrice Pouakam","Grid Supply","Passive","Grid","=
National Grid - Unstable Grid Supply Issue","Grid Fluctuation, site went do=
wn before Gen start due to poor battery backup // Grid restoration","gaelle=
.njiofack@matech-cameroun.com","128","26-07-2025 17:08:47","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005561799","Mvo=
g-Manga","","26-07-2025 16:57:41","26-07-2025 16:54:31","26-07-2025 18:51:5=
6","Site went down because Gen overload(22kva,380A) IHS SS Pascaline is inf=
ormed // Grid return","Albran Byorel","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","Site went down because Gen overload(22kva,380A) IHS S=
S Pascaline is informed // Grid return","vanel.mbiada@matech-cameroun.com",=
"241","26-07-2025 16:57:41","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005561666","Eto=
udi2","","26-07-2025 16:31:01","26-07-2025 16:28:39","26-07-2025 16:32:02",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Grid return","Delor Telezing","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage , site went down before Gen s=
tarted due to poor battery backup// Grid return","vanel.mbiada@matech-camer=
oun.com","143","26-07-2025 16:31:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005561661","Mfou EPC=
","","26-07-2025 16:30:00","26-07-2025 16:24:17","26-07-2025 16:30:05","Cas=
caded Incident from TTO5750220","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Grid return","system","265282","26-07-2025 16:=
30:01","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005561655","M=
fou OCM","IHS_YND_674","26-07-2025 16:29:23","26-07-2025 16:24:17","26-07-2=
025 16:30:05","Grid Outage, Site Down before gen Started due to poor backup=
 // Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Star=
ted due to poor backup // Grid return","gaelle.njiofack@matech-cameroun.com=
","307","26-07-2025 16:29:23","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005561649","Nko=
lbong","","26-07-2025 16:28:18","26-07-2025 16:27:09","26-07-2025 17:17:40"=
,"Grid outage, Site Down because Gen started and stopped due to Gen overloa=
d(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage, Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A) //Grid return","vanel.mbiada@ma=
tech-cameroun.com","71","26-07-2025 16:28:18","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0005561611","Bar=
riere IHS","","26-07-2025 16:19:11","26-07-2025 16:10:03","27-07-2025 12:44=
:23","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS F=
ELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to =
Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return","v=
anel.mbiada@matech-cameroun.com","633","26-07-2025 16:19:11","MATECH CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0005561555","Car=
refour Ayissi Ele","","26-07-2025 16:11:49","26-07-2025 15:55:43","26-07-20=
25 16:17:40","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","
Grid outage, Site down because Gen start and stopped with "" under frequenc=
y"" alarm,diesel was not passing well in the circuit// diesel circuit  clea=
ned and Gen manually restated.
","vanel.mbiada@matech-cameroun.com","281313","26-07-2025 16:11:49","MATECH=
 CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005561520","Nko=
l-Mebanga","","26-07-2025 16:04:25","26-07-2025 15:55:43","26-07-2025 16:17=
:40","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","
Grid outage, Site down because Gen start and stopped with "" under frequenc=
y"" alarm,diesel was not passing well in the circuit// diesel circuit  clea=
ned and Gen manually restated.
","vanel.mbiada@matech-cameroun.com","281312","26-07-2025 16:04:25","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005561509","N=
kolbong","","26-07-2025 16:02:39","26-07-2025 15:58:29","26-07-2025 16:10:3=
1","Grid outage, Site Down because Gen started and stopped due to Gen overl=
oad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage, Site Down because Gen started=
 and stopped due to Gen overload(22kva//350A) //Grid return","gaelle.njiofa=
ck@matech-cameroun.com","252","26-07-2025 16:02:39","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005561440","S=
aa","IHS_YND_810, IHS_YND_809","26-07-2025 15:52:50","26-07-2025 15:51:43",=
"26-07-2025 16:17:40","Grid outage, Site down because Gen start and stopped=
 with "" under frequency"" alarm,diesel was not passing well in the circuit=
// diesel circuit  cleaned and Gen manually restated.","Parker Tchoup","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Fuel Filter","
Grid outage, Site down because Gen start and stopped with "" under frequenc=
y"" alarm,diesel was not passing well in the circuit// diesel circuit  clea=
ned and Gen manually restated.
","gaelle.njiofack@matech-cameroun.com","68","26-07-2025 15:52:50","MATECH =
CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0005561422","Dra=
gage","","26-07-2025 15:50:46","26-07-2025 15:44:09","26-07-2025 16:02:45",=
"","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Access issue due to landlord, Site went down due to Grid outage // =
Grid returned","vanel.mbiada@matech-cameroun.com","282005","26-07-2025 15:5=
0:46","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0005561417","Bas=
tos-BAT","","26-07-2025 15:49:14","26-07-2025 15:44:09","26-07-2025 16:02:4=
5","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Access issue due to landlord, Site went down due to Grid outage =
// Grid returned","vanel.mbiada@matech-cameroun.com","282005","26-07-2025 1=
5:49:14","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005561402","ARM=
P Building","IHS_YND_192, IHS_YND_129","26-07-2025 15:47:21","26-07-2025 15=
:44:09","26-07-2025 16:02:45","Access issue due to landlord, Site went down=
 due to Grid outage // Grid returned","Mboua Thierry","Access Denial","Leas=
e Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access is=
sue due to landlord, Site went down due to Grid outage // Grid returned","v=
anel.mbiada@matech-cameroun.com","192","26-07-2025 15:47:21","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005561247","Eli=
g Edzoa","","26-07-2025 15:15:00","26-07-2025 15:12:55","26-07-2025 15:34:2=
5","site went down due to abasence of one Eneo phase // bridge make between=
 the two remaining phases","Delor Telezing","Grid Supply","Passive","Grid",=
"National Grid - Grid Incomplete Phase","site went down due to abasence of =
one Eneo phase // bridge make between the two remaining phases","gaelle.nji=
ofack@matech-cameroun.com","127","26-07-2025 15:15:00","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005561228","Nko=
lbong","","26-07-2025 15:09:25","26-07-2025 15:05:16","26-07-2025 15:43:42"=
,"Grid outage, Site Down because Gen started and stopped due to Gen overloa=
d(22kva//350A)// site stabilisation","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, Site Down because Gen st=
arted and stopped due to Gen overload(22kva//350A)// site stabilisation","v=
anel.mbiada@matech-cameroun.com","250","26-07-2025 15:09:25","MATECH CMR"
"Closed Complete","Site Down","T1323","IHS_YND_288","NOCINC0005561127","Mey=
ong Plateau","","26-07-2025 14:55:28","26-07-2025 14:35:37","26-07-2025 14:=
37:34","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Active//No power issue on site ,site on Grid with Ub=
aie=3D V The Tx FME Mouahamadou (691144435) of Huawei is informe","vanel.mb=
iada@matech-cameroun.com","1235372","26-07-2025 14:55:28","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0005561126","O=
KOA Peage","","26-07-2025 14:55:25","26-07-2025 14:53:18","26-07-2025 14:58=
:54","No power issue on site Ubaie =3D55,3V site on Grid Fulbert(654266068)=
 of huawei is informed","Fanda Brice","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ub=
aie =3D55,3V site on Grid Fulbert(654266068) of huawei is informed","gaelle=
.njiofack@matech-cameroun.com","129","26-07-2025 14:55:25","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005561091","NKO=
MKANA ELIZA HOTEL","","26-07-2025 14:48:49","26-07-2025 14:46:33","26-07-20=
25 15:36:59","Grid outage, No space to deploy a MG // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 No space to deploy a MG // Grid return","vanel.mbiada@matech-cameroun.com"=
,"137","26-07-2025 14:48:49","MATECH CMR"
"Closed Complete","Site Down","T0292","IHS_YND_231","NOCINC0005561019","Nko=
lso","IHS_YND_288","26-07-2025 14:37:46","26-07-2025 14:35:37","26-07-2025 =
14:37:34","Active//No power issue on site ,site on Grid with Ubaie=3D V The=
 Tx FME Mouahamadou (691144435) of Huawei is informed","TIENTCHEU NZETCHIEU=
 GAEL","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No power issue on site ,site on Grid with Ubaie=
=3D V The Tx FME Mouahamadou (691144435) of Huawei is informe","vanel.mbiad=
a@matech-cameroun.com","129","26-07-2025 14:37:46","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005561017","Fla=
menco","","26-07-2025 14:37:11","26-07-2025 14:34:55","26-07-2025 15:38:16"=
,"fme thierry is on the way ETA 04:30 PM","Mboua Thierry","Site Asset Theft=
","Theft","Theft","Generator Battery Theft","Site went down because Gen fai=
led to start due to Gen battery stolen //He started with an external batter=
y","vanel.mbiada@matech-cameroun.com","137","26-07-2025 14:37:11","MATECH C=
MR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005560989","E=
toudi","","26-07-2025 14:33:07","26-07-2025 14:31:01","26-07-2025 14:32:36"=
,"Grid Fluctuation, site went down before Gen start due to poor battery bac=
kup // Grid restoration","Fabrice Pouakam","Grid Supply","Passive","Grid","=
National Grid - Unstable Grid Supply Issue","Grid Fluctuation, site went do=
wn before Gen start due to poor battery backup // Grid restoration","gaelle=
.njiofack@matech-cameroun.com","127","26-07-2025 14:33:07","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005560903","Tou=
ring Club International","","26-07-2025 14:20:53","26-07-2025 14:15:28","26=
-07-2025 14:27:55","Grid outage, site went down because gen start and stopp=
ed with Alarm Under frequency // He reset gen card and gen manually started=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, site went down because gen start and stopped with Alarm Unde=
r frequency // He reset gen card and gen manually started","vanel.mbiada@ma=
tech-cameroun.com","326","26-07-2025 14:20:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0005560750","Mvog-Man=
ga","","26-07-2025 13:58:20","26-07-2025 13:19:43","26-07-2025 14:16:52","C=
ascaded Incident from TTO5748995","Albran Byorel","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site Ubaie: 58.9 V si=
te on gen.  TX fme  Lionel steve (655184876 /Huawei)) is informed.","system=
","283471","26-07-2025 13:58:20","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005560734","Eli=
g Edzoa","","26-07-2025 13:56:46","26-07-2025 13:55:36","26-07-2025 14:49:4=
6","site went down due to abasence of one Eneo phase // bridge make between=
 the two remaining phases","Delor Telezing","Grid Supply","Passive","Grid",=
"National Grid - Grid Incomplete Phase","site went down due to abasence of =
one Eneo phase // bridge make between the two remaining phases","edwige.kap=
awo@matech-cameroun.com","71","26-07-2025 13:56:46","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005560661","Tou=
ring Club International","","26-07-2025 13:38:59","26-07-2025 13:31:51","26=
-07-2025 14:06:25","Grid outage, site went down because gen start and stopp=
ed with Alarm Under frequency // He reset gen card and gen manually started=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Under Fre=
quency","Grid outage, site went down because gen start and stopped with Ala=
rm Under frequency // He reset gen card and gen manually started","edwige.k=
apawo@matech-cameroun.com","430","26-07-2025 13:38:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0005560518","Marche O=
dza","","26-07-2025 13:21:59","26-07-2025 13:19:43","26-07-2025 14:16:52","=
Cascaded Incident from TTO5748995","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site Ubaie: 58.9 V s=
ite on gen.  TX fme  Lionel steve (655184876 /Huawei)) is informed.","syste=
m","283470","26-07-2025 13:21:59","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005560516","O=
dza","IHS_YND_254, IHS_YND_580","26-07-2025 13:20:58","26-07-2025 13:19:43"=
,"26-07-2025 13:20:43","No power issue on site Ubaie: 48.9 V site on gen.  =
TX fme  Lionel steve (655184876 /Huawei)) is informed.","Albran Byorel","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue on site Ubaie: 58.9 V site on gen.  TX fme  Lionel =
steve (655184876 /Huawei)) is informed.","gaelle.njiofack@matech-cameroun.c=
om","76","26-07-2025 13:20:58","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005560421","M=
imboman-Ecole","","26-07-2025 13:05:45","26-07-2025 12:14:35","26-07-2025 1=
4:37:49","Grid outage, site went down due to 01/04 rectifiers dysfunctionin=
g // 01 rectifier added site left on grid ","Mba Lazare Herve","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, si=
te went down due to 01/04 rectifiers dysfunctioning // 01 rectifier added s=
ite left on grid ","gaelle.njiofack@matech-cameroun.com","3072","26-07-2025=
 13:05:45","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005560298","C=
-Supreme","","26-07-2025 12:41:30","26-07-2025 12:32:53","26-07-2025 13:41:=
23","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","S=
ite down because rectifier disfunctionning // He reset it: Site on grid","g=
aelle.njiofack@matech-cameroun.com","286276","26-07-2025 12:41:30","MATECH =
CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005560293","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","26-07-2025 12:40:59",=
"26-07-2025 12:32:53","26-07-2025 13:41:23","Site down because rectifier di=
sfunctionning // He reset it: Site on grid","MINKA NICOLAS","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module","Site down because rectifier d=
isfunctionning // He reset it: Site on grid","gaelle.njiofack@matech-camero=
un.com","487","26-07-2025 12:40:59","MATECH CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0005560291","O=
lezoa OCM","","26-07-2025 12:40:29","26-07-2025 12:32:53","26-07-2025 13:41=
:23","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Site down because rectifier disfunctionning // He reset it: Site on grid","=
gaelle.njiofack@matech-cameroun.com","286276","26-07-2025 12:40:29","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0005560287","A=
cropole","","26-07-2025 12:39:51","26-07-2025 12:32:53","26-07-2025 13:41:2=
3","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Site down because rectifier disfunctionning // He reset it: Site=
 on grid","gaelle.njiofack@matech-cameroun.com","286277","26-07-2025 12:39:=
51","MATECH CMR"
"Closed Complete","Site Down","T1591","IHS_YND_172","NOCINC0005560197","Tra=
dex-Nkomo","","26-07-2025 12:23:32","26-07-2025 12:19:22","26-07-2025 13:32=
:20","Grid outage,site went down because Gen failed to start//Grid return (=
Deep investigation ongoing)","Albran Byorel","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage,site went down because Gen fa=
iled to start//Grid return (Deep investigation ongoing)","edwige.kapawo@mat=
ech-cameroun.com","251","26-07-2025 12:23:32","MATECH CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0005560188","Eko=
unou","","26-07-2025 12:22:45","26-07-2025 12:19:33","26-07-2025 13:19:48",=
"Grid outage, site went down because gen failed to ATS dysfunctionning  // =
He reset it and gen manually started","Albran Byorel","Equipment Repair","P=
assive","Control Panel","ATS-AMF Issue","Grid outage, site went down becaus=
e gen failed to ATS dysfunctionning  // He reset it and gen manually starte=
d","edwige.kapawo@matech-cameroun.com","194","26-07-2025 12:22:45","MATECH =
CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005560158","Feb=
e Village","","26-07-2025 12:16:58","26-07-2025 12:14:52","26-07-2025 12:20=
:31","Grid outage, gen Stopped due to alarm""high temp""//We added water an=
d gen manually started","Mboua Thierry","Equipment Repair","Passive","ACDG =
Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, gen Stop=
ped due to alarm""high temp""//We added water and gen manually started","ed=
wige.kapawo@matech-cameroun.com","127","26-07-2025 12:16:58","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005560016","S=
ous Prefecture","","26-07-2025 11:55:48","26-07-2025 11:52:34","26-07-2025 =
20:55:05","ACTIVE//No power issue site on Grid Ubaie =3D54.5V, The tx Huawe=
i Fulbert (654266068) is informed","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V site =
on Grid; TX FME Flubert (654266068/Huawei) is informed","gaelle.njiofack@ma=
tech-cameroun.com","196","26-07-2025 11:55:48","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005559975","Mon=
tee Jouvence","","26-07-2025 11:50:24","26-07-2025 11:49:13","26-07-2025 11=
:51:04","Grid outage gen failed to start due to battery GE discharged causi=
ng by static charger faulty// He started Gen with an external batttery","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Bat=
tery","Grid outage gen failed to start due to battery GE discharged causing=
 by static charger faulty// He started Gen with an external batttery","edwi=
ge.kapawo@matech-cameroun.com","72","26-07-2025 11:50:24","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005559900","N=
simalen OCM","","26-07-2025 11:39:32","26-07-2025 11:31:16","27-07-2025 02:=
00:34","Grid outage, gen failed to start due to GE faulty // He replaced GE=
 (22KVA)","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - G=
enerator Faulty","Grid outage, gen failed to start due to GE faulty // He r=
eplaced GE (22KVA)","gaelle.njiofack@matech-cameroun.com","497","26-07-2025=
 11:39:32","MATECH CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0005559693","F=
ebe Village","","26-07-2025 11:04:48","26-07-2025 10:46:36","26-07-2025 11:=
58:21","Grid outage, gen Stopped due to alarm""high temp""//We added water =
and gen manually started","Mboua Thierry","Equipment Repair","Passive","ACD=
G Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, gen St=
opped due to alarm""high temp""//We added water and gen manually started","=
gaelle.njiofack@matech-cameroun.com","1093","26-07-2025 11:04:48","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005559368","Angongo"=
,"","26-07-2025 10:14:00","26-07-2025 10:08:39","26-07-2025 10:58:26","Casc=
aded Incident from TTO5747706","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive"," hybrid gen site.site went down due to fu=
se of starter faulty //We bypass it and gen manually started","system","123=
0043","26-07-2025 10:14:00","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0005559347","E=
beba","IHS_YND_335","26-07-2025 10:11:45","26-07-2025 10:08:39","26-07-2025=
 10:58:26"," hybrid gen site.site went down due to fuse of starter faulty /=
/We bypass it and gen manually started","Fanda Brice","Equipment Repair","P=
assive","ACDG Gen","ACDG - Kick Starter"," hybrid gen site.site went down d=
ue to fuse of starter faulty //We bypass it and gen manually started","gael=
le.njiofack@matech-cameroun.com","187","26-07-2025 10:11:45","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005559115","B=
arriere IHS","","26-07-2025 09:30:31","26-07-2025 09:26:25","26-07-2025 16:=
05:35","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed//Grid return	","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to=
 Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed//Grid return=09
","gaelle.njiofack@matech-cameroun.com","248","26-07-2025 09:30:31","MATECH=
 CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005559037","Nsi=
malen MTN","","26-07-2025 09:15:16","26-07-2025 09:09:05","27-07-2025 01:30=
:07","Grid outage, Site Down because gen failed to start due to GE faulty /=
/ He replaced GE (22KVA)","Albran Byorel","Equipment Repair","Passive","ACD=
G Gen","ACDG - Generator Faulty","Grid outage, Site Down because gen failed=
 to start due to GE faulty // He replaced GE (22KVA)","edwige.kapawo@matech=
-cameroun.com","372","26-07-2025 09:15:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0005559010","AWAE OCM=
","","26-07-2025 09:09:11","26-07-2025 09:00:48","26-07-2025 09:38:45","Cas=
caded Incident from TTO5747327","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because Gen failed t=
o start due to Grid fluctuation // disjunction of Grid and Gen start manual=
ly","system","263212","26-07-2025 09:09:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0005559009","Tradex-N=
komo","","26-07-2025 09:09:10","26-07-2025 09:00:48","26-07-2025 09:38:45",=
"Cascaded Incident from TTO5747327","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen failed =
to start due to Grid fluctuation // disjunction of Grid and Gen start manua=
lly","system","263212","26-07-2025 09:09:10","MATECH CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0005559003","Nko=
mo II","IHS_YND_172, IHS_YND_173","26-07-2025 09:07:55","26-07-2025 09:00:4=
8","26-07-2025 09:38:45","Site went down because Gen failed to start due to=
 Grid fluctuation // disjunction of Grid and Gen start manually","Albran By=
orel","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Site went down because Gen failed to start due to Grid fluctuation // =
disjunction of Grid and Gen start manually","edwige.kapawo@matech-cameroun.=
com","428","26-07-2025 09:07:55","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005558872","Oko=
la","","26-07-2025 08:37:50","26-07-2025 08:36:41","26-07-2025 09:27:58","A=
ctive//No power issue on site ubaie=3D54,6V site on Gen The TX FME Mouhamad=
ou //691144435// from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue on site ubaie=3D54,6V site on Gen The TX FME M=
ouhamadou //691144435// from Huawei is informed","edwige.kapawo@matech-came=
roun.com","70","26-07-2025 08:37:50","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005558756","M=
fou OCM","","26-07-2025 08:02:33","26-07-2025 07:55:55","26-07-2025 08:00:4=
1","Grid Outage, Site Down before gen Started due to poor backup // Grid re=
turn","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid Outage, Site Down before gen Started due to =
poor backup // Grid return","gaelle.njiofack@matech-cameroun.com","399","26=
-07-2025 08:02:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005558706","Nsam esc=
ale LP","","26-07-2025 07:50:40","26-07-2025 07:45:36","26-07-2025 07:51:56=
","Cascaded Incident from TTO5746984","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Grid return","system","267678","26-07-2025 07:50:40",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005558703","Mfou EPC=
","","26-07-2025 07:50:29","26-07-2025 07:40:42","26-07-2025 07:46:31","Cas=
caded Incident from TTO5746972","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Gen start automatically","system","1217135","26=
-07-2025 07:50:29","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005558699","Nsa=
m Sofavinc","IHS_YND_732","26-07-2025 07:49:44","26-07-2025 07:45:36","26-0=
7-2025 07:51:56","Grid Outage, Site went down before Gen start due to poor =
backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before =
Gen start due to poor backup // Grid return","edwige.kapawo@matech-cameroun=
.com","249","26-07-2025 07:49:44","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005558688","M=
fou OCM","IHS_YND_674","26-07-2025 07:46:47","26-07-2025 07:40:42","26-07-2=
025 07:46:31","Grid Outage, Site Down before gen Started due to poor backup=
 //Gen start automatically","Mba Lazare Herve","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down befo=
re gen Started due to poor backup //Gen start automatically","gaelle.njiofa=
ck@matech-cameroun.com","367","26-07-2025 07:46:47","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005558683","A=
wae Ewonkan","","26-07-2025 07:45:48","26-07-2025 07:44:41","26-07-2025 08:=
31:43","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid reurn","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid reurn"=
,"gaelle.njiofack@matech-cameroun.com","69","26-07-2025 07:45:48","MATECH C=
MR"
"Closed Complete","Site Down","T0920","IHS_YND_416","NOCINC0005557736","Ngw=
opi Boga","","26-07-2025 03:39:46","26-07-2025 03:37:12","26-07-2025 03:40:=
01","No power issue, site is on grid with Ubaie=3D54.5V; TX FME Etienne Fop=
a (693961474) from HUAWEI is informed","Kemeni Franklin","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue, site is on grid with Ubaie=3D54.5V; TX FME Etienne Fopa (69396147=
4) from HUAWEI is informed","loic.noumsi@matech-cameroun.com","155","26-07-=
2025 03:39:46","MATECH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0005557417","O=
ssombe","","26-07-2025 01:16:55","26-07-2025 01:14:47","26-07-2025 04:18:13=
","Hybrid GEN, site went down due to fuel shortage // Refuelling done","Par=
ker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Hybrid GEN, s=
ite went down due to fuel shortage // Refuelling done","loic.noumsi@matech-=
cameroun.com","129","26-07-2025 01:16:55","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005557150","N=
kolbong","","25-07-2025 23:23:33","25-07-2025 23:21:29","25-07-2025 23:42:1=
2","Grid outage, Site Down because Gen started and stopped due to Gen overl=
oad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage, Site Down because Gen started=
 and stopped due to Gen overload(22kva//350A) //Grid return","loic.noumsi@m=
atech-cameroun.com","126","25-07-2025 23:23:33","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005557030","Nsi=
malen MTN","","25-07-2025 22:54:56","25-07-2025 22:52:51","25-07-2025 23:06=
:24","Grid outage, site went down because Gen failed to start with alarm hi=
gh temp // He added water in the radiator and Gen manually started","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp -=
 Coolant Level Issue","Grid outage, site went down because Gen failed to st=
art with alarm high temp // He added water in the radiator and Gen manually=
 started","loic.noumsi@matech-cameroun.com","126","25-07-2025 22:54:56","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_115","NOCINC0005556431","Labogeni=
e","IHS_YND_568","25-07-2025 21:11:40","25-07-2025 21:02:32","25-07-2025 21=
:20:59","No power issue U =3D54,6V site on Grid. The Tx FME Eloundou (69321=
2405 )from Huawei is informed.","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D54,6V si=
te on Grid. The Tx FME Eloundou (693212405 )from Huawei is informed.","syst=
em","548","25-07-2025 21:11:40","MATECH CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0005556427","A=
nguissa New","","25-07-2025 21:10:45","25-07-2025 21:02:32","25-07-2025 21:=
20:59","Site impacted by Labogenie","MINKA NICOLAS","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue U =3D54,6V site on Gri=
d. The Tx FME Eloundou (693212405 )from Huawei is informed.","gerard.tchang=
oue@matech-cameroun.com","263018","25-07-2025 21:10:45","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005556417","NYO=
M FACE MAETUR","","25-07-2025 21:08:42","25-07-2025 21:04:35","26-07-2025 0=
0:07:34","Active//No power issue on site, site on Grid Ubaie =3D 54.59V, TX=
 FME Symphorien (691316854/650257151) from HUAWEI is informed","Fabrice Pou=
akam","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active//No power issue on site, site on Grid Ubaie =3D 54=
.59V, TX FME Symphorien (691316854/650257151) from HUAWEI is informed","van=
el.mbiada@matech-cameroun.com","249","25-07-2025 21:08:42","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005556396","Men=
dong NB","","25-07-2025 21:04:40","25-07-2025 19:04:30","25-07-2025 22:04:3=
7","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Si=
te went down due to Gen overload (17kva //180A) SS HIS Felix Zambe is infor=
med and confirmed // Grid stabilised","vanel.mbiada@matech-cameroun.com","2=
77186","25-07-2025 21:04:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005555962","Mfou EPC=
","","25-07-2025 19:27:40","25-07-2025 19:06:09","25-07-2025 19:28:09","Cas=
caded Incident from TTO5743865","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid return","system","1219153","25-07-2025 19:=
27:40","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005555907","N=
kolfon Cimencam","","25-07-2025 19:16:13","25-07-2025 19:08:48","25-07-2025=
 21:08:49","Site impacted by Meyo","Hyemafo Gildas","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed //=
 Grid return","vanel.mbiada@matech-cameroun.com","276930","25-07-2025 19:16=
:13","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005555902","A=
hala","","25-07-2025 19:15:17","25-07-2025 19:08:48","25-07-2025 21:08:49",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down due to Gen overload (17KVA, 260A) SS H=
IS Felix Zambe is informed and confirmed // Grid return","vanel.mbiada@mate=
ch-cameroun.com","276931","25-07-2025 19:15:17","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005555896","M=
eyo","IHS_YND_257, IHS_YND_762","25-07-2025 19:14:20","25-07-2025 19:08:48"=
,"25-07-2025 21:16:49","Grid outage, site went down due to Gen overload (17=
KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid return","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix Za=
mbe is informed and confirmed // Grid return","vanel.mbiada@matech-cameroun=
.com","333","25-07-2025 19:14:20","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005555890","M=
fou OCM","IHS_YND_674","25-07-2025 19:12:16","25-07-2025 19:06:09","25-07-2=
025 19:28:09","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Start=
ed due to poor backup //Grid return","vanel.mbiada@matech-cameroun.com","36=
8","25-07-2025 19:12:16","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005555851","Car=
refour Simbock","IHS_YND_742","25-07-2025 19:05:38","25-07-2025 19:04:30","=
25-07-2025 22:04:37","Site went down due to Gen overload (17kva //180A) SS =
HIS Felix Zambe is informed and confirmed // Grid stabilised","Hyemafo Gild=
as","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went do=
wn due to Gen overload (17kva //180A) SS HIS Felix Zambe is informed and co=
nfirmed // Grid stabilised","vanel.mbiada@matech-cameroun.com","69","25-07-=
2025 19:05:38","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005555763","M=
atsari","","25-07-2025 18:50:26","25-07-2025 18:36:39","25-07-2025 19:17:07=
","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Gen card hanging due ligthning // FME reset Gen card and start Ge=
n manually","vanel.mbiada@matech-cameroun.com","271697","25-07-2025 18:50:2=
6","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005555744","A=
fanoya","","25-07-2025 18:45:34","25-07-2025 18:43:25","25-07-2025 18:46:25=
","Grid outage , site went down before Gen started due to poor battery back=
up// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage , site went down before Gen=
 started due to poor battery backup// Grid return","vanel.mbiada@matech-cam=
eroun.com","131","25-07-2025 18:45:34","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005555741","N=
gouetou","","25-07-2025 18:44:50","25-07-2025 18:36:39","25-07-2025 19:17:0=
7","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Gen card hanging due ligthning // FME reset Gen card and start G=
en manually","vanel.mbiada@matech-cameroun.com","271703","25-07-2025 18:44:=
50","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005555673","ELO=
UMDEM CARRIERE 2","","25-07-2025 18:32:19","25-07-2025 18:27:59","25-07-202=
5 18:32:25","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, Site went down before Gen start due to poor =
backup // Grid returned","vanel.mbiada@matech-cameroun.com","279373","25-07=
-2025 18:32:19","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0005555669","Eto=
 koss Yde","","25-07-2025 18:31:45","25-07-2025 18:27:59","25-07-2025 18:32=
:25","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, Site went down before Gen start due to poor backup =
// Grid returned","vanel.mbiada@matech-cameroun.com","279374","25-07-2025 1=
8:31:45","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005555667","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","25-07-2025 18:31:07","25-07-2025 18:27=
:59","25-07-2025 18:32:25","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","Fanda Brice","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Grid returned","vanel.mbiada@mate=
ch-cameroun.com","191","25-07-2025 18:31:07","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005555661","SIM=
BOCK BONAMBAPE","","25-07-2025 18:30:25","25-07-2025 18:25:51","25-07-2025 =
18:31:05","Grid outage, Site went down before Gen start due to poor backup/=
 // Grid return	","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup/ // Grid return	","vanel.mbiada@matech-cameroun.co=
m","275","25-07-2025 18:30:25","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005555490","Eli=
g Edzoa","","25-07-2025 18:00:55","25-07-2025 17:55:28","25-07-2025 18:04:2=
1","Active // No power issue site on Grid with Ubay: 52.1V Tx Fme Armand Ng=
estsa (691144412 / huawei) is informed","Delor Telezing","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue site on Grid with Ubay: 52.1V Tx Fme Armand Ngestsa (691=
144412 / huawei) is informed","vanel.mbiada@matech-cameroun.com","328","25-=
07-2025 18:00:55","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005555403","Eto=
udi2","","25-07-2025 17:47:56","25-07-2025 17:46:42","25-07-2025 18:16:42",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Grid return","Delor Telezing","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage , site went down before Gen s=
tarted due to poor battery backup// Grid return","vanel.mbiada@matech-camer=
oun.com","75","25-07-2025 17:47:56","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005555136","E=
toudi","","25-07-2025 17:08:30","25-07-2025 17:06:06","25-07-2025 17:08:28"=
,"Active: no power issue, site is on grid with Ubaie Ubaie=3D53.1V, Armand =
Nguetsa(691144412) from Huawei is informed","Fabrice Pouakam","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive: no power issue, site is on grid with Ubaie Ubaie=3D51V, Armand Nguet=
sa(691144412) from Huawei is informed","vanel.mbiada@matech-cameroun.com","=
145","25-07-2025 17:08:30","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005554728","NKO=
NGKARAK","","25-07-2025 16:01:56","25-07-2025 16:00:41","25-07-2025 16:07:1=
8","Grid outage, Site went down because Gen start and stopped with ""High t=
emps ""alarm // he added water and manually start the Gen","TIENTCHEU NZETC=
HIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp=
 - Coolant Level Issue","Grid outage, Site went down because Gen start and =
stopped with ""High temps ""alarm // he added water and manually start the =
Gen","vanel.mbiada@matech-cameroun.com","76","25-07-2025 16:01:56","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005554708","MEHANDAN=
","","25-07-2025 15:58:11","25-07-2025 15:54:42","25-07-2025 16:19:01","Cas=
caded Incident from TTO5742545","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to Pwc ZTE dysfunction// he reset it and started Gen =
manualy","system","267031","25-07-2025 15:58:11","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005554707","O=
dza II OCM","IHS_YND_528","25-07-2025 15:57:04","25-07-2025 15:54:42","25-0=
7-2025 16:19:01","Grid outage, site went down because gen failed to start d=
ue to Pwc ZTE dysfunction// he reset it and started Gen manualy","Albran By=
orel","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, site went down because gen failed to start due to Pwc ZTE d=
ysfunction// he reset it and started Gen manualy","gerard.tchangoue@matech-=
cameroun.com","146","25-07-2025 15:57:04","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005554650","NKO=
NGKARAK","","25-07-2025 15:44:25","25-07-2025 15:37:03","25-07-2025 15:55:0=
3","Grid outage, Site went down because Gen start and stopped with ""High t=
emps ""alarm // he added water and manually start the Gen","TIENTCHEU NZETC=
HIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp=
 - Coolant Level Issue","Grid outage, Site went down because Gen start and =
stopped with ""High temps ""alarm // he added water and manually start the =
Gen","vanel.mbiada@matech-cameroun.com","6505","25-07-2025 15:44:25","MATEC=
H CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005554557","Eki=
e sud","","25-07-2025 15:32:18","25-07-2025 15:31:04","25-07-2025 16:19:10"=
,"Site went down because disjnuction Cb in DC BOX OCM // He reamed CB, site=
 on grid","Albran Byorel","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Circuit Breaker Issue","Site went down because disjnuction Cb =
in DC BOX OCM // He reamed CB, site on grid","vanel.mbiada@matech-cameroun.=
com","75","25-07-2025 15:32:18","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005553913","A=
wae Ewonkan","","25-07-2025 13:59:49","25-07-2025 13:58:42","25-07-2025 14:=
01:22","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed// Grid Return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed// Grid Return"=
,"edwige.kapawo@matech-cameroun.com","70","25-07-2025 13:59:49","MATECH CMR=
"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005553909","B=
arriere","","25-07-2025 13:59:10","25-07-2025 13:56:03","25-07-2025 15:24:0=
9","Site went down because Fme Gildas was on the site for PM work (drain th=
e generator) // End of work","Hyemafo Gildas","Installation Activity","Pass=
ive","Planned Activity","Installation Activity","Site went down because Fme=
 Gildas was on the site for PM work (drain the generator) // End of work","=
edwige.kapawo@matech-cameroun.com","191","25-07-2025 13:59:10","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005553610","O=
bili Carrefour","","25-07-2025 13:15:36","25-07-2025 13:13:22","25-07-2025 =
15:18:05","Grid outage site went down due to grid fluctuation and no RCP//g=
rid power stabilized","Paul BIBOUM","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Grid outage site went down due to grid f=
luctuation and no RCP//grid power stabilized","edwige.kapawo@matech-camerou=
n.com","135","25-07-2025 13:15:36","MATECH CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0005552720","N=
KONGKARAK","","25-07-2025 10:56:40","25-07-2025 10:55:27","25-07-2025 11:07=
:37","site went down because gen stopped with alarm high temp // he added w=
ater and Gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","sit=
e went down because gen stopped with alarm high temp // he added water and =
Gen manually started","edwige.kapawo@matech-cameroun.com","74","25-07-2025 =
10:56:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_140","NOCINC0005552260","BISCUITE=
RIE","","25-07-2025 10:00:20","25-07-2025 09:56:47","25-07-2025 10:01:03","=
Cascaded Incident from TTO5739912","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuation, site went down beca=
use Gen started and stopped due to Grid bad voltage// Grid stabilized","sys=
tem","267021","25-07-2025 10:00:20","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005552251","O=
bili Carrefour","IHS_YND_140","25-07-2025 09:58:55","25-07-2025 09:56:47","=
25-07-2025 10:01:03","Grid fluctuation, site went down because Gen started =
and stopped due to Grid bad voltage// Grid stabilized","Paul BIBOUM","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation, site went down because Gen started and stopped due to Grid bad v=
oltage// Grid stabilized","edwige.kapawo@matech-cameroun.com","129","25-07-=
2025 09:58:55","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005552039","Eto=
udi2","","25-07-2025 09:21:25","25-07-2025 09:19:15","25-07-2025 09:24:19",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Grid return","Delor Telezing","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage , site went down before Gen s=
tarted due to poor battery backup// Grid return","edwige.kapawo@matech-came=
roun.com","131","25-07-2025 09:21:25","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005551700","E=
toudi","","25-07-2025 08:29:50","25-07-2025 08:24:38","25-07-2025 08:30:45"=
,"Site went down because failed to start due to grid bad voltage // Grid st=
abilized","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Site went down because failed to start due to gr=
id bad voltage // Grid stabilized","edwige.kapawo@matech-cameroun.com","313=
","25-07-2025 08:29:50","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005551467","S=
IMBOCK BONAMBAPE","","25-07-2025 07:39:16","25-07-2025 07:38:59","25-07-202=
5 07:40:22","Grid outage, Site went down before Gen start due to poor backu=
p/ // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Grid return","edwige.kapawo@matech-cameroun.c=
om","19","25-07-2025 07:39:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005551164","MEHANDAN=
","","25-07-2025 06:33:10","25-07-2025 06:29:23","25-07-2025 08:48:40","Cas=
caded Incident from TTO5738728","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to Pwc ZTE dysfunction// he reset it and started Gen =
manualy","system","272186","25-07-2025 06:33:10","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005551163","O=
dza II OCM","IHS_YND_528","25-07-2025 06:32:31","25-07-2025 06:29:23","25-0=
7-2025 08:48:40","Grid outage, site went down because gen failed to start d=
ue to Pwc ZTE dysfunction// he reset it and started Gen manualy","Albran By=
orel","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, site went down because gen failed to start due to Pwc ZTE d=
ysfunction// he reset it and started Gen manualy","loic.noumsi@matech-camer=
oun.com","192","25-07-2025 06:32:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005550686","MEHANDAN=
","","25-07-2025 04:39:20","25-07-2025 04:36:25","25-07-2025 04:40:59","Cas=
caded Incident from TTO5738210","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Site stabilized","sys=
tem","264559","25-07-2025 04:39:20","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005550684","O=
dza II OCM","IHS_YND_528","25-07-2025 04:38:32","25-07-2025 04:36:25","25-0=
7-2025 04:40:59","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Site stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Site stabilized","loic.noumsi@matech-cameroun.com","130","25-07-2025=
 04:38:32","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005550467","M=
elen Ba'aba","","25-07-2025 02:57:13","25-07-2025 02:54:06","25-07-2025 02:=
57:05","No power issue, site is on Gen with Ubaie: 54.3V,   FME TX Julien (=
693095849) from Huawei is informed.","Siligap Boris","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on Gen with Ubaie: 54.3V,   FME TX Julien (693095849) from Hu=
awei is informed.","loic.noumsi@matech-cameroun.com","189","25-07-2025 02:5=
7:13","MATECH CMR"
"Closed Complete","Site Down","CTR_621","IHS_YND_278","NOCINC0005550419","N=
kolfoulou 2","","25-07-2025 02:39:48","25-07-2025 02:34:21","25-07-2025 02:=
38:16","No power issue, site is on Grid with Ubaie: 52.2V,  FME TX Julien (=
693095849) from Huawei is informed.","Siligap Boris","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on Grid with Ubaie: 52.2V,  FME TX Julien (693095849) from Hu=
awei is informed.","loic.noumsi@matech-cameroun.com","328","25-07-2025 02:3=
9:48","MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0005550335","B=
astos Bir","","25-07-2025 02:19:29","25-07-2025 02:10:20","25-07-2025 05:37=
:03","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, site went down due to Grid bad voltage (lack of 0=
1 phase) // He did bridge on the good phase, site on grid ","loic.noumsi@ma=
tech-cameroun.com","280522","25-07-2025 02:19:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0005550317","ARMP",""=
,"25-07-2025 02:17:20","25-07-2025 02:10:20","25-07-2025 05:37:03","Cascade=
d Incident from TTO5737802","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down due to Grid bad voltage (la=
ck of 01 phase) // He did bridge on the good phase, site on grid ","system"=
,"280523","25-07-2025 02:17:20","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0005550311","D=
ragage","IHS_YND_704, IHS_YND_208","25-07-2025 02:13:27","25-07-2025 02:10:=
20","25-07-2025 05:45:25","Grid outage, site went down due to Grid bad volt=
age (lack of 01 phase) // He did bridge on the good phase, site on grid ","=
Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid outage, site went down due to Grid bad voltage (lack of =
01 phase) // He did bridge on the good phase, site on grid ","loic.noumsi@m=
atech-cameroun.com","188","25-07-2025 02:13:27","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005550278","N=
kolfoulou","","25-07-2025 01:49:54","25-07-2025 01:46:45","25-07-2025 01:50=
:47","Site went down due to Gen overload (20 KVA, 300A) // Site stabilised"=
,"Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Site went down due to Gen overload (20 KVA, 300A) // Site stabilised","loi=
c.noumsi@matech-cameroun.com","190","25-07-2025 01:49:54","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005550174","E=
mombo","","25-07-2025 01:29:26","25-07-2025 01:25:09","25-07-2025 01:40:24"=
,"Active// No power issue, site is on Grid with Ubaie=3D54,6V, TX FME Eloun=
dou (652586578) from Huawei is informed","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive// No power issue, site is on Grid with Ubaie=3D54,2V, TX FME Eloundou (=
652586578) from Huawei is informed","loic.noumsi@matech-cameroun.com","258"=
,"25-07-2025 01:29:26","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005549719","MBA=
LNGONG LYCEE","","24-07-2025 23:50:28","24-07-2025 23:46:18","25-07-2025 09=
:12:21","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, Site went down because Gen stopped due to overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed//Grid return","cedric.tiani@matech-ca=
meroun.com","253","24-07-2025 23:50:28","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005549646","N=
kolbong","","24-07-2025 23:29:33","24-07-2025 23:26:27","24-07-2025 23:46:4=
1","Grid outage, Site Down because Gen started and stopped due to Gen overl=
oad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage, Site Down because Gen started=
 and stopped due to Gen overload(22kva//350A) //Grid return","loic.noumsi@m=
atech-cameroun.com","188","24-07-2025 23:29:33","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005549408","N=
kolbong","","24-07-2025 22:24:48","24-07-2025 22:19:39","24-07-2025 22:39:3=
9","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) // Grid stabilised","Delor Telezing","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen star=
ted and stopped due to Gen overload(22kva//350A) // Grid stabilised","gerar=
d.tchangoue@matech-cameroun.com","311","24-07-2025 22:24:48","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005548744","Eto=
udi2","","24-07-2025 20:24:42","24-07-2025 20:21:36","24-07-2025 20:25:23",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Gen automatically started","Delor Telezing","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage , site went dow=
n before Gen started due to poor battery backup// Gen automatically started=
","gerard.tchangoue@matech-cameroun.com","186","24-07-2025 20:24:42","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005548629","N=
kolbong","","24-07-2025 19:59:17","24-07-2025 19:57:11","24-07-2025 21:47:1=
9","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A) //Grid return","gerard.tchangou=
e@matech-cameroun.com","129","24-07-2025 19:59:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005548518","Messassi=
 okolo","","24-07-2025 19:37:41","24-07-2025 19:32:19","24-07-2025 20:06:15=
","Cascaded Incident from TTO5735813","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issue in the site at ni=
ght. Grid outage, site down because site behaves as Grid only site (Gen Noi=
se) // Grid return","system","268325","24-07-2025 19:37:41","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005548514","E=
MANA BILICK CITY","IHS_YND_279","24-07-2025 19:36:42","24-07-2025 19:32:19"=
,"24-07-2025 20:11:46","Access issue in the site at night. Grid outage, sit=
e down because site behaves as Grid only site (Gen Noise) // Grid return","=
Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord Related Issues"=
,"Access Issue - Land Lord","Access issue in the site at night. Grid outage=
, site down because site behaves as Grid only site (Gen Noise) // Grid retu=
rn","gerard.tchangoue@matech-cameroun.com","265","24-07-2025 19:36:42","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005548479","A=
hala","","24-07-2025 19:24:13","24-07-2025 19:17:04","24-07-2025 19:44:12",=
"Active //No power issue, site is on Grid and with Ubaie=3D55,9 V , TX Fme =
SAMBA (655145055/Huawei) is informed.","MINKA NICOLAS","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/No power issue, site is on Grid and with Ubaie=3D55,9 V , TX Fme SAMBA (65=
5145055/Huawei) is informed.","gerard.tchangoue@matech-cameroun.com","430",=
"24-07-2025 19:24:13","MATECH CMR"
"Closed Complete","Site Down","CTR_339","IHS_YND_073","NOCINC0005548474","C=
hapelle-Obili","","24-07-2025 19:22:24","24-07-2025 19:13:13","24-07-2025 1=
9:59:49","Joseph Kamdem 671881683 / BTR for PWC swap with micro impact // E=
nd of Work","Paul BIBOUM","Installation Activity","Passive","Planned Activi=
ty","Installation Activity","Joseph Kamdem 671881683 / BTR for PWC swap wit=
h micro impact // End of Work","gerard.tchangoue@matech-cameroun.com","551"=
,"24-07-2025 19:22:24","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005547890","N=
kolbong","","24-07-2025 17:31:36","24-07-2025 17:30:30","24-07-2025 19:27:0=
0","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A) //Grid return","gerard.tchangou=
e@matech-cameroun.com","68","24-07-2025 17:31:36","MATECH CMR"
"Closed Complete","Site Down","T1665","IHS_YND_014","NOCINC0005547866","ELI=
g-Essono","","24-07-2025 17:28:30","24-07-2025 17:23:20","24-07-2025 19:07:=
33","Grid fluctuation, site went down because Gen started and stopped to st=
art due to grid bad voltage // He did a bridge on the good phase","Delor Te=
lezing","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, site went down because Gen started and stopped to =
start due to grid bad voltage // He did a bridge on the good phase","gerard=
.tchangoue@matech-cameroun.com","310","24-07-2025 17:28:30","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005547787","Eto=
udi2","","24-07-2025 17:16:36","24-07-2025 17:14:31","24-07-2025 17:18:31",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Gen automatically started","Delor Telezing","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage , site went dow=
n before Gen started due to poor battery backup// Gen automatically started=
","gerard.tchangoue@matech-cameroun.com","126","24-07-2025 17:16:36","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005547707","O=
bili Carrefour","","24-07-2025 17:05:48","24-07-2025 16:56:40","24-07-2025 =
19:04:23","Grid fluctuation, site went down because Gen started and stopped=
 due to Grid bad voltage // Grid stabilized","Paul BIBOUM","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","24-07-2025 19:04:=
23","gerard.tchangoue@matech-cameroun.com","549","24-07-2025 17:05:48","MAT=
ECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005547448","SIM=
BOCK BONAMBAPE","","24-07-2025 16:26:26","24-07-2025 16:22:19","24-07-2025 =
16:28:19","Grid outage, Site went down before Gen start due to poor backup/=
 // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup/ // Grid return","gerard.tchangoue@matech-cameroun.=
com","248","24-07-2025 16:26:26","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005547311","Men=
dong NB","","24-07-2025 16:05:24","24-07-2025 13:03:21","24-07-2025 19:45:5=
2","Site impacted by Carrefour Simbock","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to Gen overload (17kva /=
/180A) SS HIS Felix Zambe is informed and confirmed // Grid return","gerard=
.tchangoue@matech-cameroun.com","291618","24-07-2025 16:05:24","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005547250","E=
toudi","","24-07-2025 15:56:39","24-07-2025 15:47:33","24-07-2025 16:29:59"=
,"Site went down due to  disjunction of OCM circuit breaker in the PWC // C=
B switch on, site on Grid ","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down due=
 to  disjunction of OCM circuit breaker in the PWC // CB switch on, site on=
 Grid ","gerard.tchangoue@matech-cameroun.com","547","24-07-2025 15:56:39",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005547055","N=
kolbong","","24-07-2025 15:25:28","24-07-2025 15:16:17","24-07-2025 15:37:5=
1","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A) //Grid return","edwige.kapawo@m=
atech-cameroun.com","555","24-07-2025 15:25:28","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005546917","Nsi=
malen MTN","","24-07-2025 15:08:37","24-07-2025 15:07:28","24-07-2025 15:51=
:50","Grid outage, site went down because Gen failed to start due to High t=
emp alarm // He added water and started Gen manually","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because Gen failed to start due to Hig=
h temp alarm // He added water and started Gen manually","vanel.mbiada@mate=
ch-cameroun.com","71","24-07-2025 15:08:37","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005546392","Fla=
menco","","24-07-2025 14:08:37","24-07-2025 14:06:43","24-07-2025 14:20:11"=
,"Active//No power issue on site Ubaie =3D54,3V site on Grid TX Fme Tsague =
Brice (650214096) from Huawei is informed","Mboua Thierry","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site Ubaie =3D54,3V site on Grid TX Fme Tsague Brice =
(650214096) from Huawei is informed","vanel.mbiada@matech-cameroun.com","11=
5","24-07-2025 14:08:37","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005546322","Eto=
udi2","","24-07-2025 13:56:18","24-07-2025 13:54:06","24-07-2025 13:58:59",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Gen automatically started","Delor Telezing","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage , site went dow=
n before Gen started due to poor battery backup// Gen automatically started=
","vanel.mbiada@matech-cameroun.com","133","24-07-2025 13:56:18","MATECH CM=
R"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0005546252","Ngo=
usso-Savana","","24-07-2025 13:43:16","24-07-2025 13:41:03","24-07-2025 13:=
47:45","Our FME Boris says that, Sylvain kamdem 671881683/691901615 (entrep=
rise BTR) is on site for swap of Bay// End of work","Siligap Boris","Instal=
lation Activity","Passive","Planned Activity","Installation Activity","Our =
FME Boris says that, Sylvain kamdem 671881683/691901615 (entreprise BTR) is=
 on site for swap of Bay// End of work","vanel.mbiada@matech-cameroun.com",=
"134","24-07-2025 13:43:16","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005546205","Eto=
udi2","","24-07-2025 13:35:07","24-07-2025 13:32:58","24-07-2025 13:36:39",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Gen automatically started","Delor Telezing","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage , site went dow=
n before Gen started due to poor battery backup// Gen automatically started=
","vanel.mbiada@matech-cameroun.com","130","24-07-2025 13:35:07","MATECH CM=
R"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005546052","Eto=
udi2","","24-07-2025 13:08:55","24-07-2025 13:06:17","24-07-2025 13:10:18",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Gen automatically started","Delor Telezing","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage , site went dow=
n before Gen started due to poor battery backup// Gen automatically started=
","vanel.mbiada@matech-cameroun.com","159","24-07-2025 13:08:55","MATECH CM=
R"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005546013","Car=
refour Simbock","IHS_YND_742","24-07-2025 13:04:44","24-07-2025 13:03:21","=
24-07-2025 19:45:52","Site went down due to Gen overload (17kva //180A) SS =
HIS Felix Zambe is informed and confirmed // Grid return","Hyemafo Gildas",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down d=
ue to Gen overload (17kva //180A) SS HIS Felix Zambe is informed and confir=
med // Grid return","vanel.mbiada@matech-cameroun.com","84","24-07-2025 13:=
04:44","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005545871","Eto=
udi2","","24-07-2025 12:40:30","24-07-2025 12:37:14","24-07-2025 12:42:02",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Gen automatically started","Delor Telezing","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage , site went dow=
n before Gen started due to poor battery backup// Gen automatically started=
","vanel.mbiada@matech-cameroun.com","197","24-07-2025 12:40:30","MATECH CM=
R"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005545851","ELO=
UMDEM CARRIERE 2","","24-07-2025 12:37:36","24-07-2025 12:33:27","24-07-202=
5 12:37:05","No power issue Ubaie:49.8V site on Gen. TX fme Flubert (654266=
068) from Huawei is informed","Fanda Brice","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ubai=
e:49.8V site on Gen. TX fme Flubert (654266068) from Huawei is informed","v=
anel.mbiada@matech-cameroun.com","251","24-07-2025 12:37:36","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0005545846","Eto=
 koss Yde","","24-07-2025 12:36:24","24-07-2025 12:31:15","24-07-2025 12:34=
:13","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, Site went down before Gen start due to poor backup =
// Grid returned","vanel.mbiada@matech-cameroun.com","1081","24-07-2025 12:=
36:24","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005545828","M=
EFOU ASSI","IHS_YND_737","24-07-2025 12:33:23","24-07-2025 12:31:15","24-07=
-2025 12:34:13","Grid outage, Site went down before Gen start due to poor b=
ackup // Grid returned","Fanda Brice","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Grid returned","edwige.kapawo@matech-camerou=
n.com","130","24-07-2025 12:33:23","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005545490","S=
atcom","","24-07-2025 11:37:26","24-07-2025 11:27:17","24-07-2025 11:42:52"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","edwige.kapawo@matech-c=
ameroun.com","610","24-07-2025 11:37:26","MATECH CMR"
"Closed Complete","Site Down","T0290","IHS_YND_067","NOCINC0005545404","Nko=
a Ayos","","24-07-2025 11:23:46","24-07-2025 11:22:35","24-07-2025 11:30:02=
","Site down due to work done by Albran (657108542): Changing the Section C=
able //End of work","MINKA NICOLAS","Equipment Replacement","Passive","Plan=
ned Activity","Planned Activity - Passive","Site down due to work done by A=
lbran (657108542): Changing the Section Cable //End of work","vanel.mbiada@=
matech-cameroun.com","72","24-07-2025 11:23:46","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005545269","N=
koabang Ebolmedjock","","24-07-2025 11:01:00","24-07-2025 10:57:45","24-07-=
2025 11:02:38","Site impacted by Nkolmesseng-Abom(CTR-711) Not Managed By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","Site impacted by Nkolmesseng-Abo=
m(CTR-711) Not Managed By IHS","edwige.kapawo@matech-cameroun.com","197","2=
4-07-2025 11:01:00","MATECH CMR"
"Closed Complete","Site Down","T0287","IHS_YND_038","NOCINC0005545243","Sia=
ntou Inferieur","","24-07-2025 10:56:07","24-07-2025 10:51:59","24-07-2025 =
11:06:38","No power issue on site U=3D53v site on grid Eloundou of huawei i=
s informed","","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","No power issue on site U=3D53v site on grid Elou=
ndou of huawei is informed","vanel.mbiada@matech-cameroun.com","249","24-07=
-2025 10:56:07","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005544917","Eto=
udi2","","24-07-2025 10:11:01","24-07-2025 10:09:43","24-07-2025 10:11:14",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Gen automatically started","Delor Telezing","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage , site went dow=
n before Gen started due to poor battery backup// Gen automatically started=
","vanel.mbiada@matech-cameroun.com","79","24-07-2025 10:11:01","MATECH CMR=
"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005544881","Evo=
doula MTN","","24-07-2025 10:02:41","24-07-2025 10:00:00","24-07-2025 10:28=
:09","Grid outage, Site went down because gen failed to start due to alarm =
""undervoltage"" //We reset card GE and gen manually started","TIENTCHEU NZ=
ETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Under Voltage=
","Grid outage, Site went down because gen failed to start due to alarm ""u=
ndervoltage"" //We reset card GE and gen manually started","vanel.mbiada@ma=
tech-cameroun.com","162","24-07-2025 10:02:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005544849","FOUGEROL=
E","","24-07-2025 09:55:21","24-07-2025 09:52:18","24-07-2025 10:00:52","Ca=
scaded Incident from TTO5731764","Siligap Boris","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active // No power issue, site is on gri=
d with Ubaie: 53.2V, Symphorien(650257151) from Huawei is informed. Sylvain=
 kamdem (671881683/691901615/BTR) is on site for swap of Bay","system","267=
208","24-07-2025 09:55:21","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005544840","N=
gousso-Savana","IHS_YND_561","24-07-2025 09:54:30","24-07-2025 09:52:18","2=
4-07-2025 10:00:52","Active // No power issue, site is on grid with Ubaie: =
53.2V, Symphorien(650257151) from Huawei is informed. Sylvain kamdem (67188=
1683/691901615/BTR) is on site for swap of Bay","Siligap Boris","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active // No power issue, site is on grid with Ubaie: 53.2V, Symphorien(65=
0257151) from Huawei is informed. Sylvain kamdem (671881683/691901615/BTR) =
is on site for swap of Bay","edwige.kapawo@matech-cameroun.com","133","24-0=
7-2025 09:54:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005544704","TSINGA V=
ILLAGE 2","","24-07-2025 09:27:01","24-07-2025 09:24:28","24-07-2025 09:27:=
03","Cascaded Incident from TTO5731602","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went Down due to battery=
 backup cb disjuncted due to Grid fluctuation // cb rearmed","system","2688=
64","24-07-2025 09:27:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005544703","Melen Ba=
'aba","","24-07-2025 09:27:01","24-07-2025 09:24:28","24-07-2025 09:27:03",=
"Cascaded Incident from TTO5731602","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went Down due to battery back=
up cb disjuncted due to Grid fluctuation // cb rearmed","system","268863","=
24-07-2025 09:27:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005544702","Nkolfoul=
ou 2","","24-07-2025 09:27:00","24-07-2025 09:24:28","24-07-2025 09:27:03",=
"Cascaded Incident from TTO5731602","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went Down due to battery back=
up cb disjuncted due to Grid fluctuation // cb rearmed","system","268864","=
24-07-2025 09:27:00","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005544692","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","24-07-2025 09:25:38","2=
4-07-2025 09:24:28","24-07-2025 09:27:03","Site went Down due to battery ba=
ckup cb disjuncted due to Grid fluctuation // cb rearmed","Siligap Boris","=
Equipment Repair","Passive","Control Panel","Circuit Breaker Tripped","Site=
 went Down due to battery backup cb disjuncted due to Grid fluctuation // c=
b rearmed","edwige.kapawo@matech-cameroun.com","72","24-07-2025 09:25:38","=
MATECH CMR"
"Closed Complete","Warning","SUD_016","IHS_YND_332","NOCINC0005544440","NKO=
MEKUI OCM","","24-07-2025 08:38:59","","","site alarming due to incomplete =
phase // return of the Phase","TIENTCHEU NZETCHIEU GAEL","Warning","Warning=
","POWER","Warning - AC Phase 3 Voltage low","site alarming due to incomple=
te phase // return of the Phase","vanel.mbiada@matech-cameroun.com","3767",=
"24-07-2025 08:38:59","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005544430","S=
apeur Mimboman","","24-07-2025 08:35:26","24-07-2025 08:34:18","24-07-2025 =
08:42:58","Grid outage, site went down due to gen overload(22 kva,318 A) //=
 Grid return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, site went down due to gen overload(22 kva,318=
 A) // Grid return","edwige.kapawo@matech-cameroun.com","70","24-07-2025 08=
:35:26","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005544368","NKO=
NGKARAK","","24-07-2025 08:21:05","24-07-2025 08:15:56","24-07-2025 08:40:4=
4","site went down because gen stopped with alarm high temp // he added wat=
er and Gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair",=
"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","site =
went down because gen stopped with alarm high temp // he added water and Ge=
n manually started","edwige.kapawo@matech-cameroun.com","310","24-07-2025 0=
8:21:05","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005544343","Man=
guiers Dispensaire","","24-07-2025 08:14:13","24-07-2025 08:11:54","24-07-2=
025 08:13:46","Active // No power issue site on grid with U=3D54,8 V Tx Fme=
 Armand Ngestsa (691144412) of huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active // No power issue site on grid with U=3D54,8 V Tx Fme Armand N=
gestsa (691144412) of huawei is informed","vanel.mbiada@matech-cameroun.com=
","141","24-07-2025 08:14:13","MATECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0005544142","Emo=
mbo Esssomba","","24-07-2025 07:29:48","24-07-2025 06:45:33","24-07-2025 08=
:11:14","Grid outage,site went down because Gen failed to start due to Gen =
battery discharge //he started with an external battery","Mba Lazare Herve"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid o=
utage,site went down because Gen failed to start due to Gen battery dischar=
ge //he started with an external battery","edwige.kapawo@matech-cameroun.co=
m","2656","24-07-2025 07:29:48","MATECH CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0005544124","Sap=
eur Mimboman","","24-07-2025 07:25:50","24-07-2025 07:20:43","24-07-2025 08=
:26:43","Grid outage, site went down due to gen overload(22 kva,318 A) // G=
rid return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage, site went down due to gen overload(22 kva,318 A=
) // Grid return","vanel.mbiada@matech-cameroun.com","308","24-07-2025 07:2=
5:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005544051","Ebeba","=
","24-07-2025 07:09:20","24-07-2025 05:10:16","24-07-2025 07:03:40","Cascad=
ed Incident from TTO5730539","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive"," Access issue at night,  Site went down due=
 to insufficiency of rectifiers on site SS IHS Pascaline is confirmed // He=
 reduced the load","system","276862","24-07-2025 07:09:20","MATECH CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0005544036","Nke=
ng likok","","24-07-2025 07:06:54","24-07-2025 07:04:09","24-07-2025 07:38:=
17","Grid outage.gen failed to start due to automation malfunctionning//Gen=
 manually started","Kemeni Franklin","Equipment Repair","Passive","Control =
Panel","ATS-AMF Issue","Grid outage.gen failed to start due to automation m=
alfunctionning//Gen manually started","vanel.mbiada@matech-cameroun.com","1=
66","24-07-2025 07:06:54","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005543895","Eto=
udi2","","24-07-2025 06:29:52","24-07-2025 06:11:14","24-07-2025 07:21:37",=
"Site went down because Gen failed to start due to Grid bad voltage  // He =
bypass the Grid and Gen manually Started","Delor Telezing","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Site went down be=
cause Gen failed to start due to Grid bad voltage  // He bypass the Grid an=
d Gen manually Started","franck.nkomot@matech-cameroun.com","1142","24-07-2=
025 06:29:52","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005543703","C=
rf Cornier","IHS_YND_339","24-07-2025 05:10:23","24-07-2025 05:08:16","24-0=
7-2025 07:03:40"," Access issue at night,  Site went down due to insufficie=
ncy of rectifiers on site SS IHS Pascaline is confirmed // He reduced the l=
oad","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule"," Access issue at night,  Site went down due to insufficiency of rect=
ifiers on site SS IHS Pascaline is confirmed // He reduced the load","gaell=
e.njiofack@matech-cameroun.com","128","24-07-2025 05:10:23","MATECH CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0005543701","T=
ongolo OCM","","24-07-2025 05:09:00","24-07-2025 05:02:54","24-07-2025 06:1=
9:56","Site went down because gen failed to start due to grid bad voltage /=
/ He bypass grid and manually start the gen","Delor Telezing","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Site went down=
 because gen failed to start due to grid bad voltage // He bypass grid and =
manually start the gen","gaelle.njiofack@matech-cameroun.com","367","24-07-=
2025 05:09:00","MATECH CMR"
"Acknowledge","Site Down","","IHS_YND_758","NOCINC0005543682","Nkolfoulou C=
SD MTN","","24-07-2025 04:59:29","24-07-2025 04:43:00","24-07-2025 04:57:10=
","Cascaded Incident from TTO5730480","Siligap Boris","Cascade Outage","","=
","","","system","989","24-07-2025 04:59:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005543655","Melen Ba=
'aba","","24-07-2025 04:50:30","24-07-2025 04:41:00","24-07-2025 04:50:25",=
"Cascaded Incident from TTO5730466","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen failed =
to start due to PWC malfunctioning // He reset the PWC and Gen manually sta=
rted","system","570","24-07-2025 04:50:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005543654","Nkolfoul=
ou 2","","24-07-2025 04:50:30","24-07-2025 04:41:00","24-07-2025 04:50:25",=
"Cascaded Incident from TTO5730466","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen failed =
to start due to PWC malfunctioning // He reset the PWC and Gen manually sta=
rted","system","570","24-07-2025 04:50:30","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005543645","N=
kolfoulou","IHS_YND_278, IHS_YND_308","24-07-2025 04:47:59","24-07-2025 04:=
41:00","24-07-2025 04:57:10","Site went down because Gen failed to start du=
e to PWC malfunctioning // He reset the PWC and Gen manually started","Sili=
gap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module Overl=
oaded","Site went down because Gen failed to start due to PWC malfunctionin=
g // He reset the PWC and Gen manually started","gaelle.njiofack@matech-cam=
eroun.com","420","24-07-2025 04:47:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005543642","Mfou EPC=
","","24-07-2025 04:47:20","24-07-2025 04:43:39","24-07-2025 04:49:49","Cas=
caded Incident from TTO5730457","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid return","system","264085","24-07-2025 04:4=
7:20","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005543636","M=
fou OCM","IHS_YND_674","24-07-2025 04:45:50","24-07-2025 04:43:39","24-07-2=
025 04:49:49","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Start=
ed due to poor backup //Grid return","gaelle.njiofack@matech-cameroun.com",=
"132","24-07-2025 04:45:50","MATECH CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0005543422","OLA=
MA","","24-07-2025 03:17:36","24-07-2025 03:11:19","24-07-2025 03:23:58",""=
,"Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active",=
"Site impacted by T0169 Ngoumou not manage by IHS","gaelle.njiofack@matech-=
cameroun.com","262502","24-07-2025 03:17:36","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0005543419","Min=
ka","","24-07-2025 03:17:04","24-07-2025 03:11:19","24-07-2025 03:23:58",""=
,"Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active",=
"Site impacted by T0169 Ngoumou not manage by IHS","gaelle.njiofack@matech-=
cameroun.com","262501","24-07-2025 03:17:04","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005543417","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","24-07-2025 03:16:=
25","24-07-2025 03:11:19","24-07-2025 03:23:58","Site impacted by T0169 Ngo=
umou not manage by IHS","Fanda Brice","Customer Equipment Failure","Active"=
,"Active Equipment Failure","Affected by 3rd Party Site","Site impacted by =
T0169 Ngoumou not manage by IHS","gaelle.njiofack@matech-cameroun.com","308=
","24-07-2025 03:16:25","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0005543415","Mom=
","","24-07-2025 03:15:11","24-07-2025 03:11:19","24-07-2025 03:23:58","","=
Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active","S=
ite impacted by T0169 Ngoumou not manage by IHS","gaelle.njiofack@matech-ca=
meroun.com","262502","24-07-2025 03:15:11","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005543410","OTE=
LE MTN","","24-07-2025 03:14:28","24-07-2025 03:11:19","24-07-2025 03:23:58=
","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","Site impacted by T0169 Ngoumou not manage by IHS","gaelle.njiofack@mat=
ech-cameroun.com","262503","24-07-2025 03:14:28","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005543028","Fou=
da Quarter","","24-07-2025 01:07:21","24-07-2025 01:01:12","24-07-2025 02:0=
9:47","Grid bad voltage , site down because gen fails to start due to grid =
bad voltage // Gen manually started","Delor Telezing","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid bad voltage , sit=
e down because gen fails to start due to grid bad voltage // Gen manually s=
tarted","franck.nkomot@matech-cameroun.com","370","24-07-2025 01:07:21","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005543011","E=
koumdoum OCM","","24-07-2025 01:03:34","24-07-2025 01:02:26","24-07-2025 01=
:52:26","Grid outage, site went down because Gen failed to start due to ''u=
nknow '' alarm // MTN prefilter  bypass &  DG card reseted and  Gen manuall=
y started ","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","Grid outage, site went down because Gen failed to start du=
e to ''unknow '' alarm // MTN prefilter  bypass &  DG card reseted and  Gen=
 manually started ","gaelle.njiofack@matech-cameroun.com","70","24-07-2025 =
01:03:34","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005542798","A=
wae Ewonkan","","24-07-2025 00:30:30","24-07-2025 00:30:27","24-07-2025 00:=
34:30","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Site stabilised","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Site s=
tabilised","gaelle.njiofack@matech-cameroun.com","6","24-07-2025 00:30:30",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005542795","E=
MANA BILICK CITY","IHS_YND_279","24-07-2025 00:29:44","24-07-2025 00:27:30"=
,"24-07-2025 02:15:15","Access issue in the site at night. Grid outage, sit=
e down because site behaves as Grid only site (Gen Noise) // Grid return","=
Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord Related Issues"=
,"Access Issue - Land Lord","Access issue in the site at night. Grid outage=
, site down because site behaves as Grid only site (Gen Noise) // Grid retu=
rn","gaelle.njiofack@matech-cameroun.com","137","24-07-2025 00:29:44","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005542771","M=
essassi okolo","","24-07-2025 00:28:59","24-07-2025 00:27:30","24-07-2025 0=
2:10:22","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Access issue in the site at night. Grid outage, site dow=
n because site behaves as Grid only site (Gen Noise) // Grid return","gaell=
e.njiofack@matech-cameroun.com","272261","24-07-2025 00:28:59","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005542760","S=
atcom","","24-07-2025 00:28:20","24-07-2025 00:24:12","24-07-2025 00:32:00"=
,"No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand ngu=
etsa(691144412) From huawei is informed.","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand nguetsa(6=
91144412) From huawei is informed.","gaelle.njiofack@matech-cameroun.com","=
249","24-07-2025 00:28:20","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005542738","N=
koabang2","","24-07-2025 00:27:46","24-07-2025 00:24:39","24-07-2025 00:36:=
39","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","gaelle=
.njiofack@matech-cameroun.com","189","24-07-2025 00:27:46","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005542244","Odz=
a Minkan IHS","","23-07-2025 23:47:54","23-07-2025 23:40:47","24-07-2025 00=
:55:47","Grid fluctuations, Site went down because Gen failed to start due =
to Grid bad voltage(Unstable phases)// He bypassed Grid and started Gen man=
ually","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuations, Site went down because Gen failed =
to start due to Grid bad voltage(Unstable phases)// He bypassed Grid and st=
arted Gen manually","franck.nkomot@matech-cameroun.com","428","23-07-2025 2=
3:47:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005542222","Yoko MTN=
","","23-07-2025 23:42:09","23-07-2025 23:36:40","23-07-2025 23:37:40","Cas=
caded Incident from TTO5728934","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active // No power issue on site with Uba=
ie=3D54.1V site on Gen ,The Tx Fme Gregoire( 652070658) from Huawei is info=
rmed","system","268095","23-07-2025 23:42:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005542220","MBIMBIM"=
,"","23-07-2025 23:42:09","23-07-2025 23:36:40","23-07-2025 23:37:40","Casc=
aded Incident from TTO5728934","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active // No power issue on site with Ubai=
e=3D54.1V site on Gen ,The Tx Fme Gregoire( 652070658) from Huawei is infor=
med","system","268094","23-07-2025 23:42:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005542221","Ngoum","=
","23-07-2025 23:42:09","23-07-2025 23:36:40","23-07-2025 23:37:40","Cascad=
ed Incident from TTO5728934","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active // No power issue on site with Ubaie=
=3D54.1V site on Gen ,The Tx Fme Gregoire( 652070658) from Huawei is inform=
ed","system","268094","23-07-2025 23:42:09","MATECH CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0005542214","Mat=
sari","IHS_YND_456, IHS_YND_475, IHS_YND_473","23-07-2025 23:40:51","23-07-=
2025 23:36:40","23-07-2025 23:37:40","Active // No power issue on site with=
 Ubaie=3D54.1V site on Gen ,The Tx Fme Gregoire( 652070658) from Huawei is =
informed","Parker Tchoup","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Active // No power issue on site with=
 Ubaie=3D54.1V site on Gen ,The Tx Fme Gregoire( 652070658) from Huawei is =
informed","franck.nkomot@matech-cameroun.com","253","23-07-2025 23:40:51","=
MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005542201","M=
vog-Manga","","23-07-2025 23:36:36","23-07-2025 23:35:31","23-07-2025 23:39=
:00","Site went down because Gen overload(22kva,380A) IHS SS Pascaline is i=
nformed // Grid return","Albran Byorel","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","Site went down because Gen overload(22kva,380A) IHS=
 SS Pascaline is informed // Grid return","gaelle.njiofack@matech-cameroun.=
com","68","23-07-2025 23:36:36","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005542186","N=
kolbong","","23-07-2025 23:34:04","23-07-2025 23:32:57","24-07-2025 14:06:4=
5","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A) //Grid return","gaelle.njiofack=
@matech-cameroun.com","69","23-07-2025 23:34:04","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005542013","Fou=
da Quarter","","23-07-2025 22:54:26","23-07-2025 22:52:17","24-07-2025 00:0=
2:17","grid bad voltage, site went down because gen fails to start due to l=
ack of 01 phase on site // he did a brdge with a good phase","Delor Telezin=
g","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"grid bad voltage, site went down because gen fails to start due to lack o=
f 01 phase on site // he did a brdge with a good phase","franck.nkomot@mate=
ch-cameroun.com","129","23-07-2025 22:54:26","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005541987","T=
SINGA VILLAGE 2","","23-07-2025 22:45:27","23-07-2025 22:38:11","23-07-2025=
 22:56:49","Site impacted by CTR_954 Nkolfoulou 3 Not under IHS ","Delor Te=
lezing","Customer Equipment Failure","Active","Active Equipment Failure","A=
ffected by 3rd Party Site","Site impacted by CTR_954 Nkolfoulou 3 Not under=
 IHS ","gaelle.njiofack@matech-cameroun.com","438","23-07-2025 22:45:27","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005541923","N=
kolbong","","23-07-2025 22:32:02","23-07-2025 22:24:55","23-07-2025 22:46:1=
3","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started =
and stopped due to Gen overload(22kva//350A) // Grid return","loic.noumsi@m=
atech-cameroun.com","429","23-07-2025 22:32:02","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005541840","M=
elen Ba'aba","","23-07-2025 22:14:33","23-07-2025 22:12:23","23-07-2025 23:=
12:30","Active// No power issue, site is on GEN with Ubaie=3D54,3 V TX FME =
Julien(693095849) from Huawei is informed","Siligap Boris","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power issue, site is on GEN with Ubaie=3D54,3 V TX FME Julien(69309=
5849) from Huawei is informed","loic.noumsi@matech-cameroun.com","131","23-=
07-2025 22:14:33","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005541821","E=
toudi","","23-07-2025 22:12:33","23-07-2025 22:08:27","23-07-2025 23:23:16"=
,"Site went down because Gen failed to start due to grid bad voltage// He p=
ut site on Gen","Fabrice Pouakam","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","Site went down because Gen failed to start=
 due to grid bad voltage// He put site on Gen","loic.noumsi@matech-cameroun=
.com","247","23-07-2025 22:12:33","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005541809","Eko=
umdoum OCM","","23-07-2025 22:10:47","23-07-2025 22:05:40","23-07-2025 22:3=
9:34","Grid outage, site went down because Gen failed to start due to ''ove=
r voltage '' alarm // He reset DG card and manually started the Gen","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Gr=
id outage, site went down because Gen failed to start due to ''over voltage=
 '' alarm // He reset DG card and manually started the Gen","loic.noumsi@ma=
tech-cameroun.com","308","23-07-2025 22:10:47","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005541720","E=
toudi","","23-07-2025 21:56:46","23-07-2025 21:50:17","23-07-2025 21:53:23"=
,"Grid Fluctuation, site went down before Gen start due to poor battery bac=
kup // Site stabilised","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went down=
 before Gen start due to poor battery backup // Site stabilised","loic.noum=
si@matech-cameroun.com","390","23-07-2025 21:56:46","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005541688","N=
koabang2","","23-07-2025 21:50:55","23-07-2025 21:49:40","23-07-2025 22:04:=
58","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","gaelle=
.njiofack@matech-cameroun.com","77","23-07-2025 21:50:55","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005541613","Bit=
eng-Maetur","","23-07-2025 21:37:51","23-07-2025 21:35:47","23-07-2025 21:4=
8:19","Grid outage site went down because Gen failed to start due PWC ZTE d=
ysfunctioned // Grid return","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Grid outage site went down bec=
ause Gen failed to start due PWC ZTE dysfunctioned // Grid return","loic.no=
umsi@matech-cameroun.com","126","23-07-2025 21:37:51","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005541565","C=
omplexe-BEAC","","23-07-2025 21:28:26","23-07-2025 21:25:21","23-07-2025 21=
:28:43","No power issue on site ,site on Grid with U=3D55.2V Tx FME Lionnel=
// 655184876 from Huawei is informed","Albran Byorel","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site ,site on Grid with U=3D55.2V Tx FME Lionnel// 655184876 from =
Huawei is informed","loic.noumsi@matech-cameroun.com","186","23-07-2025 21:=
28:26","MATECH CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0005541456","V=
allee-Bastos OCM","","23-07-2025 21:04:28","23-07-2025 21:02:23","23-07-202=
5 21:31:39","Grid only site, no MDGE to deploy // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site, =
no MDGE to deploy // Grid return","loic.noumsi@matech-cameroun.com","126","=
23-07-2025 21:04:28","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005541382","S=
atcom","","23-07-2025 20:47:29","23-07-2025 20:43:24","23-07-2025 20:45:21"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","loic.noumsi@matech-cam=
eroun.com","247","23-07-2025 20:47:29","MATECH CMR"
"Closed Complete","Site Down","T2795","IHS_YND_070","NOCINC0005541337","Efo=
ulan","","23-07-2025 20:40:37","23-07-2025 20:34:28","23-07-2025 21:48:55",=
"Site went down due to disjunction of Cb(80A) in PWC // He reamed Cb(80A), =
site on grid","MINKA NICOLAS","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Circuit Breaker Issue","Site went down due to disjunction =
of Cb(80A) in PWC // He reamed Cb(80A), site on grid","gaelle.njiofack@mate=
ch-cameroun.com","369","23-07-2025 20:40:37","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005541243","A=
wae Ewonkan","","23-07-2025 20:23:10","23-07-2025 20:19:57","23-07-2025 21:=
19:58","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Site stabilised","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Site s=
tabilised","gaelle.njiofack@matech-cameroun.com","195","23-07-2025 20:23:10=
","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005541151","O=
lembe","","23-07-2025 20:06:57","23-07-2025 20:04:52","23-07-2025 20:11:24"=
,"Site went down due to refueling // End of work","Fabrice Pouakam","Equipm=
ent Replacement","Passive","Planned Activity","Planned Activity - Passive",=
"Site went down due to refueling // End of work","loic.noumsi@matech-camero=
un.com","127","23-07-2025 20:06:57","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005541015","Eki=
e sud","","23-07-2025 19:40:15","23-07-2025 19:08:58","23-07-2025 20:26:48"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage// He bypasse the Grid and site on Gen","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","	Grid fluc=
tuation, Site went down because gen fails to start due to grid bad voltage/=
/ He bypasse the Grid and site on Gen","loic.noumsi@matech-cameroun.com","1=
878","23-07-2025 19:40:15","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005540909","C=
rf Cornier","","23-07-2025 19:16:16","23-07-2025 19:13:10","23-07-2025 19:3=
8:30","Site went down due to insuficiency of rectifier // Grid stabilised",=
"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to insuficiency of rectifier // Grid stabilised","loic=
.noumsi@matech-cameroun.com","187","23-07-2025 19:16:16","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005540860","B=
arriere","","23-07-2025 19:03:50","23-07-2025 18:55:40","23-07-2025 19:02:2=
8","Gen overload // Load balanced","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","	Gen overload // Load balanced","gaelle=
.njiofack@matech-cameroun.com","492","23-07-2025 19:03:50","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0005540723","ETO=
UDI Entree du palais","","23-07-2025 18:37:16","23-07-2025 18:31:11","23-07=
-2025 19:11:23","Grid outage, site went down because Gen failed to start du=
e to PWC ZTE dysfunctioning //e reset it, and site on Grid","Fabrice Pouaka=
m","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Grid outage, site went down because Gen failed to start due to PWC ZTE dysf=
unctioning //e reset it, and site on Grid","loic.noumsi@matech-cameroun.com=
","367","23-07-2025 18:37:16","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005540338","N=
gousso-Savana","","23-07-2025 17:19:18","23-07-2025 17:12:08","23-07-2025 1=
9:51:12","Our FME Boris says that, Sylvain kamdem  671881683/691901615 (ent=
reprise BTR) is on site for swap of Bay // End of work","Siligap Boris","In=
stallation Activity","Passive","Planned Activity","Installation Activity","=
site went down due to work of Sylvain kamdem  671881683/691901615 (entrepri=
se BTR) is on site for swap of Bay // End of work","gaelle.njiofack@matech-=
cameroun.com","431","23-07-2025 17:19:18","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005540299","Pha=
rmacie Bleue","IHS_YND_801","23-07-2025 17:10:38","23-07-2025 17:03:27","23=
-07-2025 18:07:00","Grid outage, site went down because gen failed to start=
 due to gen card faulty // Gen started manually","Siligap Boris","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site wen=
t down because gen failed to start due to gen card faulty // Gen started ma=
nually","loic.noumsi@matech-cameroun.com","432","23-07-2025 17:10:38","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0005540086","H=
-General-Yde","","23-07-2025 16:35:14","23-07-2025 16:32:06","23-07-2025 17=
:38:41","Grid outage, Site went down because Gen failed to start due to ATS=
 faulty // He bypassed ATS and started Gen manually ","Siligap Boris","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site =
went down because Gen failed to start due to ATS faulty // He bypassed ATS =
and started Gen manually ","gaelle.njiofack@matech-cameroun.com","189","23-=
07-2025 16:35:14","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005540082","Aba=
ttoir","","23-07-2025 16:33:27","23-07-2025 16:31:23","23-07-2025 16:33:55"=
,"Grid outage, site went down due to poor backup // Grid stabilised","Fabri=
ce Pouakam","Equipment Repair","Passive","Control Panel","Power Cabinet - B=
attery Low","Grid outage, site went down due to poor backup // Grid stabili=
sed","loic.noumsi@matech-cameroun.com","126","23-07-2025 16:33:27","MATECH =
CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0005540051","M=
amch Building","","23-07-2025 16:26:14","23-07-2025 16:20:01","23-07-2025 1=
7:29:00","Grid outage, site went down due to Gen Card malfunction ( Gen sto=
pped with ''Underfrequency & Undervoltage'' ALARM) // Gen Card reseted & ma=
nually started","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","AC=
DG - Control Panel","Grid outage, site went down due to Gen Card malfunctio=
n ( Gen stopped with ''Underfrequency & Undervoltage'' ALARM) // Gen Card r=
eseted & manually started","gaelle.njiofack@matech-cameroun.com","376","23-=
07-2025 16:26:14","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005540020","N=
taba","","23-07-2025 16:18:05","23-07-2025 16:16:51","23-07-2025 16:36:09",=
"Grid outage site went down because Gen stopped with ''Undervoltage' ALARM =
// he reset the Gen Card and manually started Gen","Delor Telezing","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","	Grid outage site =
went down because Gen stopped with ''Undervoltage' ALARM // he reset the Ge=
n Card and manually started Gen","gaelle.njiofack@matech-cameroun.com","75"=
,"23-07-2025 16:18:05","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005539945","N=
kolfoulou","","23-07-2025 16:04:35","23-07-2025 13:38:43","23-07-2025 13:42=
:09","	Grid outage Site went down due to Gen overload (300 A /20 KVA) // Gr=
id return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","	Grid outage Site went down due to Gen overload (300 A /20 KVA) =
// Grid return","gaelle.njiofack@matech-cameroun.com","8754","23-07-2025 16=
:04:35","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005539882","S=
oa-Sofamac","","23-07-2025 15:51:24","23-07-2025 15:48:11","23-07-2025 16:0=
6:36","hybrid Grid-gen site .site went down due to hybrid system malfunctio=
n // gen manually started","Siligap Boris","Equipment Repair","Passive","Hy=
brid","Hybrid Module","hybrid Grid-gen site .site went down due to hybrid s=
ystem malfunction // gen manually started","gaelle.njiofack@matech-cameroun=
.com","194","23-07-2025 15:51:24","MATECH CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0005539873","Sap=
eur Mimboman","","23-07-2025 15:50:19","23-07-2025 15:47:12","23-07-2025 16=
:05:37","Grid outage, site went down due to gen overload(22 kva,318 A) // G=
rid return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage, site went down due to gen overload(22 kva,318 A=
) // Grid return","loic.noumsi@matech-cameroun.com","188","23-07-2025 15:50=
:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005539820","Elig-Edz=
oa","","23-07-2025 15:39:11","23-07-2025 15:28:00","23-07-2025 16:07:03","C=
ascaded Incident from TTO5726247","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","	Grid outage site went down because Gen stopped w=
ith ''Undervoltage' ALARM // he reset the Gen Card and manually started Gen=
","system","282970","23-07-2025 15:39:11","MATECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0005539797","Emo=
mbo Esssomba","","23-07-2025 15:35:01","23-07-2025 15:26:55","23-07-2025 16=
:06:02","Grid outage, site went down because Gen started and stopped due to=
 Battery Gen stolen // He started Gen with an external battery ","Mba Lazar=
e Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery"=
,"Grid outage, site went down because Gen started and stopped due to Batter=
y Gen stolen // He started Gen with an external battery ","loic.noumsi@mate=
ch-cameroun.com","487","23-07-2025 15:35:01","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005539786","Nta=
ba","IHS_YND_133","23-07-2025 15:32:12","23-07-2025 15:28:00","23-07-2025 1=
6:10:35","Grid outage site went down because Gen stopped with ''Undervoltag=
e' ALARM // he reset the Gen Card and manually started Gen","Delor Telezing=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","	Grid out=
age site went down because Gen stopped with ''Undervoltage' ALARM // he res=
et the Gen Card and manually started Gen","loic.noumsi@matech-cameroun.com"=
,"253","23-07-2025 15:32:12","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005539735","Mim=
boman","","23-07-2025 15:24:07","23-07-2025 15:20:58","23-07-2025 16:01:50"=
,"Grid outage, site went down because gen started and stopped due to alarm*=
low oil pressure* // he reset DG card and started the gen manually","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, site went down because gen started and stopped due to alarm*l=
ow oil pressure* // he reset DG card and started the gen manually","loic.no=
umsi@matech-cameroun.com","190","23-07-2025 15:24:07","MATECH CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0005539724","Awa=
e Escalier","","23-07-2025 15:20:59","23-07-2025 15:20:53","23-07-2025 15:2=
4:12","grid outage, site went down due to gen Overload(20KVA, 300A) // He r=
educed LOAD, SITE on Gen","Albran Byorel","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","grid outage, site went down due to gen Overload(2=
0KVA, 300A) // He reduced LOAD, SITE on Gen","loic.noumsi@matech-cameroun.c=
om","7","23-07-2025 15:20:59","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005539568","Lad=
a I Yde","","23-07-2025 15:00:58","23-07-2025 14:56:50","23-07-2025 16:20:0=
1","grid outage, site went down due to gen Overload(09KVA, 105A) // Grid re=
turn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","grid outage, site went down due to gen Overload(09KVA, 105A) // Gr=
id return","loic.noumsi@matech-cameroun.com","250","23-07-2025 15:00:58","M=
ATECH CMR"
"Closed Complete","Site Down","T0219","IHS_YND_024","NOCINC0005539549","Gar=
bati building","","23-07-2025 14:57:06","23-07-2025 14:55:01","23-07-2025 1=
6:24:55","Grid outage site went down before Gen started due to alarm ''Fail=
ed to Stop'' // Gen cart reset and Gen started manually","Delor Telezing","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage =
site went down before Gen started due to alarm ''Failed to Stop'' // Gen ca=
rd reset and Gen started manually","loic.noumsi@matech-cameroun.com","126",=
"23-07-2025 14:57:06","MATECH CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0005539459","Av =
Kennedy","","23-07-2025 14:44:21","23-07-2025 14:41:15","23-07-2025 15:54:3=
0","Grid outage.no space to deploy mobile gen // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no sp=
ace to deploy mobile gen // Grid return","cedric.tiani@matech-cameroun.com"=
,"187","23-07-2025 14:44:21","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005539409","M=
essassi okolo","","23-07-2025 14:31:13","23-07-2025 13:40:25","23-07-2025 1=
6:17:04","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site down because site behaves as Grid only=
 site (Gen Noise) // Grid return","vanel.mbiada@matech-cameroun.com","27505=
7","23-07-2025 14:31:13","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0005539407","Imm=
-Olympique","","23-07-2025 14:30:53","23-07-2025 14:26:40","23-07-2025 16:3=
9:28","Grid outage,site went down because Gen failed to start due to Gen ov=
erload(20KVA//295A) SS HIS Raoul is informed//Grid return","Paul BIBOUM","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","	Grid outage,site =
went down because Gen failed to start due to Gen overload(20KVA//295A) SS H=
IS Raoul is informed//Grid return","cedric.tiani@matech-cameroun.com","255"=
,"23-07-2025 14:30:53","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005539353","ESS=
OS OASIS 1111","","23-07-2025 14:20:26","23-07-2025 14:17:51","23-07-2025 1=
5:16:55","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned	","Siligap Boris","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, Site went down because Gen overload (17kva, 2=
50A) // Grid returned	","cedric.tiani@matech-cameroun.com","156","23-07-202=
5 14:20:26","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005539339","Mam=
ch Building","","23-07-2025 14:14:47","23-07-2025 14:12:34","23-07-2025 16:=
09:39","Grid outage, site went down due to Gen Card malfunction ( Gen stopp=
ed with ''Underfrequency & Undervoltage'' ALARM) // Gen Card reseted & manu=
ally started","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Grid outage, site went down due to Gen Card malfunction =
( Gen stopped with ''Underfrequency & Undervoltage'' ALARM) // Gen Card res=
eted & manually started","cedric.tiani@matech-cameroun.com","135","23-07-20=
25 14:14:47","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005539307","S=
oa-Sofamac","IHS_YND_720","23-07-2025 14:08:35","23-07-2025 14:02:26","23-0=
7-2025 15:20:27","hybrid Grid-gen site .site went down due to hybrid system=
 malfunction // gen manually started","Siligap Boris","Equipment Repair","P=
assive","Hybrid","Hybrid Module","hybrid Grid-gen site .site went down due =
to hybrid system malfunction //gen manually started","vanel.mbiada@matech-c=
ameroun.com","370","23-07-2025 14:08:35","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0005539304","B=
riqueterie","","23-07-2025 14:08:02","23-07-2025 14:02:52","23-07-2025 14:1=
6:29","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Grid outage, site went down because Gen failed to start due to Gen battery=
 faulty // Grid return","vanel.mbiada@matech-cameroun.com","288072","23-07-=
2025 14:08:02","MATECH CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0005539297","E=
lobi Mokolo","","23-07-2025 14:06:39","23-07-2025 14:02:30","23-07-2025 17:=
56:15","Active//No power issue on site Ubaie=3D56,4 V; site on Grid tx fme =
BRICE Tsague/ 650214096 from huawie is informed","Mboua Thierry","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site Ubaie=3D56,4 V; site on Grid tx fme BRICE =
Tsague/ 650214096 from huawie is informed","vanel.mbiada@matech-cameroun.co=
m","250","23-07-2025 14:06:39","MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0005539294","K=
amajou Building","IHS_YND_085","23-07-2025 14:06:00","23-07-2025 14:02:52",=
"23-07-2025 14:20:35","Grid outage, site went down because Gen failed to st=
art due to Gen battery faulty // Grid return","Paul BIBOUM","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, site went=
 down because Gen failed to start due to Gen battery faulty // Grid return"=
,"vanel.mbiada@matech-cameroun.com","189","23-07-2025 14:06:00","MATECH CMR=
"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005539293","Pha=
rmacie Bleue","IHS_YND_801","23-07-2025 14:05:39","23-07-2025 14:02:29","23=
-07-2025 14:52:10","	Grid outage, site went down because gen failed to star=
t due to gen card faulty // Gen started manually","Siligap Boris","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","	Grid outage, site w=
ent down because gen failed to start due to gen card faulty // Gen started =
manually","cedric.tiani@matech-cameroun.com","191","23-07-2025 14:05:39","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0005539290","S=
OA UNIVERSITY STADIUM","","23-07-2025 14:05:27","23-07-2025 14:02:26","23-0=
7-2025 15:20:27","","Siligap Boris","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","hybrid Grid-gen site .site went down due to hybrid=
 system malfunction //gen manually started","vanel.mbiada@matech-cameroun.c=
om","266611","23-07-2025 14:05:27","MATECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0005539288","HOP=
ITAL GENERAL RAIL YDE","","23-07-2025 14:04:59","23-07-2025 14:02:29","23-0=
7-2025 18:07:00","Site up awaititng feedback","Delor Telezing","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","	Grid outage, site went=
 down because gen failed to start due to gen card faulty // Gen started man=
ually","cedric.tiani@matech-cameroun.com","280923","23-07-2025 14:04:59","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005539286","A=
WAE OCM","","23-07-2025 14:04:42","23-07-2025 14:02:29","23-07-2025 15:01:1=
9","No power issue site on Grid with U=3D56.4V ,The FME TX Henry (699949693=
) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on Grid with U=3D56.4V ,The FME TX Henry (699949693) from Huawei is info=
rmed","vanel.mbiada@matech-cameroun.com","135","23-07-2025 14:04:42","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005539280","M=
imboman-Ecole","","23-07-2025 14:03:47","23-07-2025 13:57:33","23-07-2025 1=
4:05:15","Grid outage, site went down due to 01/04 rectifiers dysfunctionin=
g // Grid stabilised","Mba Lazare Herve","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Grid outage, site went down due to 01/04 rectifi=
ers dysfunctioning // Grid stabilised","vanel.mbiada@matech-cameroun.com","=
375","23-07-2025 14:03:47","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005539276","Mok=
olo Yaounde","","23-07-2025 14:02:45","23-07-2025 13:59:33","23-07-2025 14:=
07:30","Active // No power issue Ubay: 54.7V site on grid. The Tx FME Eloun=
dou Bertrand (693212405) from Huawei is informed","","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // =
No power issue Ubay: 54.7V site on grid. The Tx FME Eloundou Bertrand (6932=
12405) from Huawei is informed","cedric.tiani@matech-cameroun.com","194","2=
3-07-2025 14:02:45","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005539268","Sim=
e Building","","23-07-2025 14:00:50","23-07-2025 13:57:41","23-07-2025 14:0=
5:30","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","cedric.tiani=
@matech-cameroun.com","191","23-07-2025 14:00:50","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005539267","C=
NR","","23-07-2025 14:00:48","23-07-2025 13:57:37","23-07-2025 14:05:35","G=
rid outage, Site went down before Gen start due to poor backup// Gen automa=
tically started","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup// Gen automatically started","vanel.mbiada@matech-ca=
meroun.com","192","23-07-2025 14:00:48","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005539260","Cit=
e des nations","","23-07-2025 13:58:55","23-07-2025 13:57:35","23-07-2025 1=
4:05:30","Grid outage,site went down before Gen started due to Poor battery=
 backup//Gen automatically started","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage,site went do=
wn before Gen started due to Poor battery backup//Gen automatically started=
","cedric.tiani@matech-cameroun.com","81","23-07-2025 13:58:55","MATECH CMR=
"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005539218","Man=
guiers Dispensaire","","23-07-2025 13:51:04","23-07-2025 13:50:59","23-07-2=
025 14:48:37","Grid outage, site went down because gen failed to start due =
to grid contactor faulty // He bypassed grid contactor and gen manually sta=
rted","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Loa=
d Contactor","Grid outage, site went down because gen failed to start due t=
o grid contactor faulty // He bypassed grid contactor and gen manually star=
ted","cedric.tiani@matech-cameroun.com","7","23-07-2025 13:51:04","MATECH C=
MR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005539208","N=
koabang2","","23-07-2025 13:48:54","23-07-2025 13:46:25","23-07-2025 15:46:=
01","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Site stabilised","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due t=
o gen overload (22KVA, 330A), SS Blaise IHS is informed // Site stabilised"=
,"vanel.mbiada@matech-cameroun.com","152","23-07-2025 13:48:54","MATECH CMR=
"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005539202","Nko=
lfoulou CSD MTN","","23-07-2025 13:47:08","23-07-2025 13:44:02","23-07-2025=
 16:16:26","Active//No power issue site is on Grid with Ubaie=3D53,4 V site=
 on gen The Tx FME Symphorien //675295205 from Huawei is informed","Siligap=
 Boris","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No power issue site is on Grid with Ubaie=3D53,=
4 V site on gen The Tx FME Symphorien //675295205 from Huawei is informed",=
"cedric.tiani@matech-cameroun.com","187","23-07-2025 13:47:08","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005539199","E=
MANA BILICK CITY","IHS_YND_279","23-07-2025 13:46:36","23-07-2025 13:40:25"=
,"23-07-2025 16:22:25","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid return","Fabrice Pouakam","Access Denial","L=
ease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid o=
utage, site down because site behaves as Grid only site (Gen Noise) // Grid=
 return","vanel.mbiada@matech-cameroun.com","373","23-07-2025 13:46:36","MA=
TECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005539191","Nko=
lbong","","23-07-2025 13:44:06","23-07-2025 13:41:58","23-07-2025 16:07:34"=
,"Grid outage,Site Down because Gen started and stopped due to Gen overload=
(22kva//350A)  // Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A)  // Grid return","cedric.tiani@=
matech-cameroun.com","130","23-07-2025 13:44:06","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005539184","M=
vog-Ada_OCM","","23-07-2025 13:42:40","23-07-2025 13:38:13","23-07-2025 16:=
05:26","Grid only on site, No space on site to deploy MDGE // Grid return	"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d only on site, No space on site to deploy MDGE // Grid return	","vanel.mbi=
ada@matech-cameroun.com","268","23-07-2025 13:42:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0005539174","Garbati =
building","","23-07-2025 13:41:20","23-07-2025 13:36:43","23-07-2025 13:39:=
18","Cascaded Incident from TTO5725511","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down be=
fore Gen started due to poor battery back up // GEN automatically starte","=
system","260961","23-07-2025 13:41:20","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005539161","Awa=
e Ewonkan","","23-07-2025 13:38:46","23-07-2025 13:36:40","23-07-2025 13:38=
:40","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)IHS=
 SS Alphonse is informed// Grid Return","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to G=
en Overload (20Kva, Iload 320A)IHS SS Alphonse is informed// Grid Return","=
cedric.tiani@matech-cameroun.com","128","23-07-2025 13:38:46","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005539156","HOP=
ITAL DE LA CAISSE","IHS_YND_024","23-07-2025 13:37:52","23-07-2025 13:36:43=
","23-07-2025 13:39:18","Grid outage site went down before Gen started due =
to poor battery back up // GEN automatically starte","Delor Telezing","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 outage site went down before Gen started due to poor battery back up // GE=
N automatically starte","cedric.tiani@matech-cameroun.com","70","23-07-2025=
 13:37:52","MATECH CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0005539120","Av =
Kennedy","","23-07-2025 13:29:00","23-07-2025 13:27:51","23-07-2025 13:29:5=
1","Grid , only site ,No psace for mobile gen // grid restoration","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid , only =
site ,No psace for mobile gen // grid restoration","cedric.tiani@matech-cam=
eroun.com","70","23-07-2025 13:29:00","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0005539078","NKO=
MEKUI OCM","","23-07-2025 13:20:56","23-07-2025 13:18:42","23-07-2025 13:26=
:48","No power issue site on gen with U=3D54.5v Notice that site is impacte=
d by Mbankolo Camtel","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 site on gen with U=3D54.5v Notice that site is impacted by Mbankolo Camtel=
","cedric.tiani@matech-cameroun.com","136","23-07-2025 13:20:56","MATECH CM=
R"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0005538993","J=
-Vespa","","23-07-2025 13:07:41","23-07-2025 13:04:34","23-07-2025 13:05:27=
","Grid fluctuation site went down because Gen failed to start due to Grid =
bad voltage and No RCP on site // Grid Return","Mboua Thierry","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion site went down because Gen failed to start due to Grid bad voltage and =
No RCP on site // Grid Return","cedric.tiani@matech-cameroun.com","188","23=
-07-2025 13:07:41","MATECH CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0005538984","Jea=
n Vespa","","23-07-2025 13:06:48","23-07-2025 13:04:38","23-07-2025 13:22:1=
6","Grid fluctuation site went down because Gen failed to start due to Grid=
 bad voltage and No RCP on site // Grid Return","Mboua Thierry","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tion site went down because Gen failed to start due to Grid bad voltage and=
 No RCP on site // Grid Return","cedric.tiani@matech-cameroun.com","131","2=
3-07-2025 13:06:48","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005538894","E=
toudi","","23-07-2025 12:52:21","23-07-2025 12:49:02","23-07-2025 14:01:05"=
,"Grid Fluctuation, site went down before Gen start due to poor battery bac=
kup // He put Site on Gen","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went d=
own before Gen start due to poor battery backup // He put Site on Gen","van=
el.mbiada@matech-cameroun.com","200","23-07-2025 12:52:21","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005538823","E=
toudi","","23-07-2025 12:39:38","23-07-2025 12:38:20","23-07-2025 12:42:12"=
,"Grid Fluctuation, site went down before Gen start due to poor battery bac=
kup // Site stabilised","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went down=
 before Gen start due to poor battery backup // He put Site on Gen","vanel.=
mbiada@matech-cameroun.com","79","23-07-2025 12:39:38","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005538811","Aba=
ttoir","","23-07-2025 12:38:31","23-07-2025 12:35:17","23-07-2025 12:37:44"=
,"Grid outage, site went down due to poor backup // Gen started automatical=
ly","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, site went down due to poor backup // Ge=
n started automatically","cedric.tiani@matech-cameroun.com","195","23-07-20=
25 12:38:31","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0005538796","Val=
lee Bastos MTN","","23-07-2025 12:36:19","23-07-2025 12:35:04","23-07-2025 =
12:36:58","Site went down because insufficient of rectifier //site stabiliz=
ed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down because insufficient of rectifier //site stabilized","=
cedric.tiani@matech-cameroun.com","76","23-07-2025 12:36:19","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005538764","Nko=
lfoulou CSD MTN","","23-07-2025 12:30:22","23-07-2025 12:26:11","23-07-2025=
 12:34:45","Active//No power issue site is on Grid with Ubaie=3D53,4 V site=
 on gen The Tx FME Syphorien //675295205 from Huawei is informed","Siligap =
Boris","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No power issue site is on Grid with Ubaie=3D53,4=
 V site on gen The Tx FME Syphorien //675295205 from Huawei is informed","c=
edric.tiani@matech-cameroun.com","252","23-07-2025 12:30:22","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005538725","S=
apeur Mimboman","","23-07-2025 12:25:24","23-07-2025 12:24:17","23-07-2025 =
12:31:41","Grid outage, site went down due to gen overload(22 kva,318 A) //=
 Grid return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, site went down due to gen overload(22 kva,318=
 A) // Grid returned","vanel.mbiada@matech-cameroun.com","68","23-07-2025 1=
2:25:24","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005538601","A=
wae Ewonkan","","23-07-2025 12:19:57","23-07-2025 12:18:48","23-07-2025 12:=
20:01","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed// Grid Return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed// Grid Return"=
,"vanel.mbiada@matech-cameroun.com","72","23-07-2025 12:19:57","MATECH CMR"
"Closed Complete","Site Down","T1746","IHS_YND_178","NOCINC0005538598","Emo=
mbo","","23-07-2025 12:18:40","23-07-2025 12:11:17","23-07-2025 12:15:25","=
Active// No power issue, site is on Grid with Ubaie=3D54,2V, Lionel Adjep(6=
55184876) from Huawei is informed","Mba Lazare Herve","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// =
No power issue, site is on Grid with Ubaie=3D54,2V, Lionel Adjep(655184876)=
 from Huawei is informed","cedric.tiani@matech-cameroun.com","444","23-07-2=
025 12:18:40","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005538593","M=
essassi okolo","","23-07-2025 12:18:08","23-07-2025 12:14:09","23-07-2025 1=
2:35:38","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site down because site behaves as Grid only=
 site (Gen Noise)//Grid return","vanel.mbiada@matech-cameroun.com","265869"=
,"23-07-2025 12:18:08","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005538591","Nko=
abang2","","23-07-2025 12:17:54","23-07-2025 12:14:39","23-07-2025 12:43:47=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","cedric.t=
iani@matech-cameroun.com","197","23-07-2025 12:17:54","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005538590","EMA=
NA BILICK CITY","IHS_YND_279","23-07-2025 12:17:17","23-07-2025 12:14:09","=
23-07-2025 12:41:03","Grid outage, site down because site behaves as Grid o=
nly site (Gen Noise)//Grid return","Fabrice Pouakam","Access Denial","Lease=
 Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid outag=
e, site down because site behaves as Grid only site (Gen Noise)//Grid retur=
n","cedric.tiani@matech-cameroun.com","190","23-07-2025 12:17:17","MATECH C=
MR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005538583","Nko=
lbong","","23-07-2025 12:16:32","23-07-2025 12:11:18","23-07-2025 12:35:44"=
,"Grid outage,Site Down because Gen started and stopped due to Gen overload=
(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started and =
stopped due to Gen overload(22kva//350A)//Grid return","cedric.tiani@matech=
-cameroun.com","318","23-07-2025 12:16:32","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005538582","Mvo=
g-Manga","","23-07-2025 12:15:49","23-07-2025 12:11:43","23-07-2025 14:03:0=
3","Site went down because Gen overload(22kva,380A) IHS SS Pascaline is inf=
ormed // Grid return","Albran Byorel","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","Site went down because Gen overload(22kva,380A) IHS S=
S Pascaline is informed // Grid return","cedric.tiani@matech-cameroun.com",=
"251","23-07-2025 12:15:49","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005538580","S=
atcom","","23-07-2025 12:15:32","23-07-2025 12:09:19","23-07-2025 12:27:21"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","vanel.mbiada@matech-ca=
meroun.com","375","23-07-2025 12:15:32","MATECH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0005538576","Mvo=
g-Ada_OCM","","23-07-2025 12:15:14","23-07-2025 12:11:55","23-07-2025 12:32=
:38","Grid Only site, No space to deploy MDGE// Grid returned","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only site, =
No space to deploy MDGE// Grid returned","cedric.tiani@matech-cameroun.com"=
,"201","23-07-2025 12:15:14","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005538329","N=
kolfoulou","","23-07-2025 11:39:09","23-07-2025 11:37:56","23-07-2025 11:37=
:57","No power issue on site, Site on Grid UBAIE=3D53V synphorien (67529520=
5) From huawei is informed","Siligap Boris","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite, Site on Grid UBAIE=3D54V synphorien (675295205) From huawei is informe=
d","vanel.mbiada@matech-cameroun.com","74","23-07-2025 11:39:09","MATECH CM=
R"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005538201","T=
SINGA VILLAGE 2","","23-07-2025 11:15:48","23-07-2025 11:09:35","23-07-2025=
 11:25:43","Active//No power issue on site, Site on Battery UBAIE=3D54.5V s=
ynphorien (675295205) From huawei is informed","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site, Site on Battery UBAIE=3D54.5V synphorien (=
675295205) From huawei is informed","vanel.mbiada@matech-cameroun.com","375=
","23-07-2025 11:15:48","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005537949","SIM=
BOCK BONAMBAPE","","23-07-2025 10:37:24","23-07-2025 10:33:15","23-07-2025 =
10:39:42"," Site went down because  Gen overload(20KVA//300A )SS HIS Felix =
Bateu  is informed // Grid return","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload"," Site went down because  Gen overload(2=
0KVA//300A )SS HIS Felix Bateu  is informed // Grid return","cedric.tiani@m=
atech-cameroun.com","250","23-07-2025 10:37:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0005537928","Eloumdem=
 stade","","23-07-2025 10:33:20","23-07-2025 10:28:49","23-07-2025 10:37:18=
","Cascaded Incident from TTO5724113","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen failed to start due to Gen card faulty // Grid return","system","26508=
5","23-07-2025 10:33:20","MATECH CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0005537911","Sim=
bock MTN","IHS_YND_793","23-07-2025 10:31:10","23-07-2025 10:28:49","23-07-=
2025 10:37:18","Grid outage site went down because Gen failed to start due =
to Gen card faulty // Grid return","Fanda Brice","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage site went down because Ge=
n failed to start due to Gen card faulty // Grid return","cedric.tiani@mate=
ch-cameroun.com","142","23-07-2025 10:31:10","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005537906","Jou=
vence Mbenda","","23-07-2025 10:29:15","23-07-2025 10:28:05","23-07-2025 10=
:35:12","Grid outage.gen start and stopped due to alarm""high temp""//Grid =
return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Hi=
gh Engine Temp - Coolant Level Issue","Grid outage.gen start and stopped du=
e to alarm""high temp""//Grid return","cedric.tiani@matech-cameroun.com","7=
1","23-07-2025 10:29:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005537902","MEHANDAN=
","","23-07-2025 10:28:20","23-07-2025 10:26:36","23-07-2025 10:28:58","Cas=
caded Incident from TTO5724095","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Site stabilized","sys=
tem","265215","23-07-2025 10:28:20","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005537897","O=
dza II OCM","IHS_YND_528","23-07-2025 10:27:48","23-07-2025 10:26:36","23-0=
7-2025 10:28:58","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Site stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Site stabilized","vanel.mbiada@matech-cameroun.com","76","23-07-2025=
 10:27:48","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005537890","M=
EFOU ASSI","","23-07-2025 10:26:00","23-07-2025 10:22:52","23-07-2025 10:30=
:47","Grid outage, site went down because gen failed to start due to Gen in=
 manual mode //Grid return","Fanda Brice","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage, site went down because gen fail=
ed to start due to Gen in manual mode //Grid return","vanel.mbiada@matech-c=
ameroun.com","191","23-07-2025 10:26:00","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005537877","M=
arche Odza","","23-07-2025 10:23:12","23-07-2025 10:18:58","23-07-2025 10:4=
0:36","Grid outage, site went down because gen start and stopped with over =
voltage alarm // He reset it and manually start the gen","Albran Byorel","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, =
site went down because gen start and stopped with over voltage alarm // He =
reset it and manually start the gen","vanel.mbiada@matech-cameroun.com","25=
6","23-07-2025 10:23:12","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005537866","M=
ontee-Jouvence-II","","23-07-2025 10:20:24","23-07-2025 10:16:18","23-07-20=
25 10:35:11","Grid outage, Site went down before Gen start due to poor back=
up // Gen started automatically","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen started automatically","vane=
l.mbiada@matech-cameroun.com","248","23-07-2025 10:20:24","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005537838","MEF=
OU ASSI","IHS_YND_768","23-07-2025 10:13:57","23-07-2025 10:12:47","23-07-2=
025 10:15:46","Grid outage, site went down because gen failed to start due =
to Gen in manual mode //Grid return","Fanda Brice","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because=
 gen failed to start due to Gen in manual mode //Grid return","vanel.mbiada=
@matech-cameroun.com","574","23-07-2025 10:13:57","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005537828","ELO=
UMDEM CARRIERE 2","","23-07-2025 10:12:23","23-07-2025 10:12:47","23-07-202=
5 10:15:46","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, site went down because gen failed to start d=
ue to Gen in manual mode //Grid return","vanel.mbiada@matech-cameroun.com",=
"273087","23-07-2025 10:12:23","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005537822","Nsa=
m Sofavinc","","23-07-2025 10:11:16","23-07-2025 10:06:26","23-07-2025 10:1=
2:43","Grid Outage, Site went down before Gen start due to poor backup // G=
rid return","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid Outage, Site went down before Gen start d=
ue to poor backup // Grid return","vanel.mbiada@matech-cameroun.com","291",=
"23-07-2025 10:11:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005537813","Mfou EPC=
","","23-07-2025 10:09:19","23-07-2025 10:03:29","23-07-2025 10:13:29","Cas=
caded Incident from TTO5723997","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","266585","23-07-2025 10=
:09:19","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005537805","M=
fou OCM","IHS_YND_674","23-07-2025 10:08:38","23-07-2025 10:03:29","23-07-2=
025 10:13:29","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","vanel.mbiada@matech-cameroun.com"=
,"310","23-07-2025 10:08:38","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005537750","Bit=
eng-Maetur","","23-07-2025 09:59:05","23-07-2025 09:56:54","23-07-2025 10:4=
2:05","Site went down due to disjunction of CB (125A) in the DCBOX MTN // H=
e rearmed it, Site on Grid","Mba Lazare Herve","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down du=
e to disjunction of CB (125A) in the DCBOX MTN // He rearmed it, Site on Gr=
id","cedric.tiani@matech-cameroun.com","134","23-07-2025 09:59:05","MATECH =
CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005537747","A=
kak-Nkozoa-MTN-IHS","","23-07-2025 09:58:20","23-07-2025 09:56:33","23-07-2=
025 10:14:08","Site went down due to work of our FME Giress on site ( doing=
 PM)//End work","Fabrice Pouakam","Installation Activity","Passive","Planne=
d Activity","Installation Activity","Site went down due to work of our FME =
Giress on site ( doing PM)//End work","vanel.mbiada@matech-cameroun.com","1=
10","23-07-2025 09:58:20","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005537697","E=
koumdoum OCM","","23-07-2025 09:49:51","23-07-2025 09:47:34","23-07-2025 10=
:05:47","Grid outage.gen started and stopped due to fuel filter flushed//we=
 clean fuel filter and gen manually started","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Fuel Filter","Grid outage.gen started and=
 stopped due to fuel filter flushed//we clean fuel filter and gen manually =
started","vanel.mbiada@matech-cameroun.com","139","23-07-2025 09:49:51","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0005537540","Crf-Mban=
kolo-IHS","","23-07-2025 09:19:10","23-07-2025 09:10:21","23-07-2025 09:54:=
33","Cascaded Incident from TTO5723594","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation site went dow=
n because Gen failed to start due to Grid bad voltage and No RCP on site //=
 Grid Return","system","276821","23-07-2025 09:19:10","MATECH CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0005537452","Jea=
n Vespa","IHS_YND_574","23-07-2025 09:12:35","23-07-2025 09:10:21","23-07-2=
025 09:54:33","Grid fluctuation site went down because Gen failed to start =
due to Grid bad voltage and No RCP on site // Grid Return","Mboua Thierry",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid fluctuation site went down because Gen failed to start due to Grid bad =
voltage and No RCP on site // Grid Return","cedric.tiani@matech-cameroun.co=
m","135","23-07-2025 09:12:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005537199","MEHANDAN=
","","23-07-2025 08:24:40","23-07-2025 08:16:22","23-07-2025 08:20:43","Cas=
caded Incident from TTO5723306","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Site stabilized","sys=
tem","265763","23-07-2025 08:24:40","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005537197","Odz=
a II OCM","IHS_YND_528","23-07-2025 08:23:42","23-07-2025 08:16:22","23-07-=
2025 08:25:07","Grid fluctuations, site went down because gen failed to sta=
rt due to PWC ZTE malfunction // Site stabilized","Albran Byorel","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctua=
tions, site went down because gen failed to start due to PWC ZTE malfunctio=
n // Site stabilized","cedric.tiani@matech-cameroun.com","468","23-07-2025 =
08:23:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0005537120","Jean Ves=
pa 2","","23-07-2025 08:05:41","23-07-2025 08:00:41","23-07-2025 09:53:29",=
"Cascaded Incident from TTO5723202","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation site went down be=
cause Gen failed to start due to Grid bad voltage and No RCP on site // Gri=
d Return","system","280994","23-07-2025 08:05:41","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0005537099","J=
-Vespa","IHS_YND_544","23-07-2025 08:02:03","23-07-2025 08:00:41","23-07-20=
25 09:53:29","Grid fluctuation site went down because Gen failed to start d=
ue to Grid bad voltage and No RCP on site // Grid Return","Mboua Thierry","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation site went down because Gen failed to start due to Grid bad v=
oltage and No RCP on site // Grid Return","vanel.mbiada@matech-cameroun.com=
","84","23-07-2025 08:02:03","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005536826","Evo=
doula MTN","","23-07-2025 07:14:21","23-07-2025 07:13:57","23-07-2025 07:19=
:42","Grid outage, Site went down before Gen start due to poor backup // Ge=
n Automaticaly started	","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen Automaticaly started	","ce=
dric.tiani@matech-cameroun.com","26","23-07-2025 07:14:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005536613","MEHANDAN=
","","23-07-2025 06:32:10","23-07-2025 06:27:17","23-07-2025 06:36:17","Cas=
caded Incident from TTO5722674","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Site stabilized","sys=
tem","265173","23-07-2025 06:32:10","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005536612","O=
dza II OCM","IHS_YND_528","23-07-2025 06:31:28","23-07-2025 06:27:17","23-0=
7-2025 06:36:17","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Site stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Site stabilized","franck.nkomot@matech-cameroun.com","255","23-07-20=
25 06:31:28","MATECH CMR"
"Closed Complete","Site Down","CTR_360","IHS_YND_373","NOCINC0005536428","M=
aloun","","23-07-2025 05:28:31","23-07-2025 05:18:59","23-07-2025 05:20:59"=
,"No power issue on site U=3D54,8V site on Gen , The Tx FME Etienne/6513201=
88/ from Huawei is informed","Kemeni Franklin","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D54,8V site on Gen , The Tx FME Etienne/651320188/ from Huawei is=
 informed","franck.nkomot@matech-cameroun.com","573","23-07-2025 05:28:31",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005536425","E=
vodoula OCM","","23-07-2025 05:26:41","23-07-2025 05:16:59","23-07-2025 05:=
17:59","No power issue site and with Ubaie=3D54.4 V site on Gen The FME TX =
Mouamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue site and with Ubaie=3D54.4 V site on Gen The FME =
TX Mouamadou/658791013 //From Huawei is informed","franck.nkomot@matech-cam=
eroun.com","583","23-07-2025 05:26:41","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005536082","O=
dza II OCM","","23-07-2025 02:35:50","23-07-2025 02:32:29","23-07-2025 02:4=
0:29","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","franck.nkomot@matech-cameroun.com","204","23-07-2025 02:35:50=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005536064","MEHANDAN=
","","23-07-2025 02:23:01","23-07-2025 02:14:19","23-07-2025 02:21:19","Cas=
caded Incident from TTO5722087","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","265858","23-07-2025 02:23:01","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005536062","O=
dza II OCM","IHS_YND_528","23-07-2025 02:22:27","23-07-2025 02:14:19","23-0=
7-2025 02:21:19","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","franck.nkomot@matech-cameroun.com","492","23-07-20=
25 02:22:27","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005535937","Ona=
ngondi (melen bikop)","","23-07-2025 01:24:31","23-07-2025 01:14:59","23-07=
-2025 02:56:59","FGrid outage, site went down because Gen failed to start d=
ue to Hybrid system dysfunctionning // He reset the hybrid system and Gen m=
anually started","Fanda Brice","Equipment Repair","Passive","Hybrid","Hybri=
d Module","Grid outage, site went down because Gen failed to start due to H=
ybrid system dysfunctionning // He reset the hybrid system and Gen manually=
 started","franck.nkomot@matech-cameroun.com","573","23-07-2025 01:24:31","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_052","NOCINC0005535858","Nyahoo",=
"","23-07-2025 01:08:01","23-07-2025 00:57:16","23-07-2025 01:01:16","Casca=
ded Incident from TTO5721851","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue, site is on grid =
with Ubaie=3D55.2V, TX FME Gregoir (654547479) from Huawei is informed","sy=
stem","263274","23-07-2025 01:08:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_532","NOCINC0005535859","NKOLOSSA=
N OKOK","","23-07-2025 01:08:01","23-07-2025 00:57:16","23-07-2025 01:01:16=
","Cascaded Incident from TTO5721851","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue, site is on grid wit=
h Ubaie=3D55.2V, TX FME Gregoir (654547479) from Huawei is informed","syste=
m","263272","23-07-2025 01:08:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_408","NOCINC0005535857","Evodoula=
 MTN","","23-07-2025 01:08:00","23-07-2025 00:57:16","23-07-2025 01:01:16",=
"Cascaded Incident from TTO5721851","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue, site is on=
 grid with Ubaie=3D55.2V, TX FME Gregoir (654547479) from Huawei is informe=
d","system","263272","23-07-2025 01:08:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0005535856","NYANON/D=
EMBO","","23-07-2025 01:08:00","23-07-2025 00:57:16","23-07-2025 01:01:16",=
"Cascaded Incident from TTO5721851","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue, site is on=
 grid with Ubaie=3D55.2V, TX FME Gregoir (654547479) from Huawei is informe=
d","system","263273","23-07-2025 01:08:00","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005535848","M=
ontee-Des-Soeurs","","23-07-2025 01:02:47","23-07-2025 00:52:59","23-07-202=
5 00:53:59","Active // No power issue, site is on grid with Ubaie: 54.6V, M=
bah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active // No power issue, site is on grid with Ubaie: 54.6V, Mbah hosiah(6=
99699694) from Huawei is informed","franck.nkomot@matech-cameroun.com","590=
","23-07-2025 01:02:47","MATECH CMR"
"Closed Complete","Site Down","T0573","IHS_YND_387","NOCINC0005535843","Tal=
la Monatele","IHS_EDA_102, IHS_YND_408, IHS_EDA_049, IHS_EDA_048, IHS_YND_4=
72, IHS_EDA_052, IHS_YND_532","23-07-2025 01:01:30","23-07-2025 00:57:16","=
23-07-2025 01:01:16","No power issue, site is on grid with Ubaie=3D55.2V, T=
X FME Gregoir (654547479) from Huawei is informed","Parker Tchoup","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue, site is on grid with Ubaie=3D55.2V, TX FME Gregoir (654=
547479) from Huawei is informed","franck.nkomot@matech-cameroun.com","255",=
"23-07-2025 01:01:30","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005535490","N=
kolbong","","22-07-2025 23:19:05","22-07-2025 23:17:44","22-07-2025 23:48:4=
4","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A) // Site stabilized","Delor Telezing","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down becaus=
e Gen started and stopped due to Gen overload(22kva//350A) // Site stabiliz=
ed","franck.nkomot@matech-cameroun.com","83","22-07-2025 23:19:05","MATECH =
CMR"
"Closed Complete","Site Down","T2183","IHS_YND_089","NOCINC0005535297","H-P=
rince","","22-07-2025 22:30:05","22-07-2025 22:28:00","22-07-2025 23:48:00"=
,"Site went down due to Disjunction of CB (25A) in the TGBT // CB rearm","M=
boua Thierry","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Circuit Breaker Issue","Site went down due to Disjunction of CB (25A) in t=
he TGBT // CB rearm","loic.noumsi@matech-cameroun.com","126","22-07-2025 22=
:30:05","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005535271","Nko=
lbong","","22-07-2025 22:24:56","22-07-2025 22:21:41","22-07-2025 22:43:41"=
,"Grid outage,Site went Down because Gen started and stopped due to Gen ove=
rload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A) // Grid return","loic.=
noumsi@matech-cameroun.com","197","22-07-2025 22:24:56","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005535052","SIM=
BOCK BONAMBAPE","","22-07-2025 21:34:25","22-07-2025 21:31:20","22-07-2025 =
21:33:39","Grid outage, Site went down before Gen start due to poor backup/=
 // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup/ // Grid return","loic.noumsi@matech-cameroun.com",=
"186","22-07-2025 21:34:25","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005535041","Nko=
lbong","","22-07-2025 21:32:44","22-07-2025 21:31:38","22-07-2025 21:51:35"=
,"Grid outage,Site went Down because Gen started and stopped due to Gen ove=
rload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A) // Grid return","loic.=
noumsi@matech-cameroun.com","68","22-07-2025 21:32:44","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005535031","C=
omplexe-BEAC","","22-07-2025 21:28:57","22-07-2025 21:24:50","22-07-2025 22=
:08:53","Site went down due to disjunction of CB (125A) in the PWC // He re=
armed it, Site on Grid","Albran Byorel","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Site went down due to d=
isjunction of CB (125A) in the OCM BTS // He rearmed it, Site on Grid","gae=
lle.njiofack@matech-cameroun.com","248","22-07-2025 21:28:57","MATECH CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0005534914","H=
-Prince","","22-07-2025 21:01:40","22-07-2025 21:00:34","22-07-2025 21:55:3=
2","Site went down due to Disjunction of CB (25A) in the TGBT // CB rearm",=
"Mboua Thierry","Equipment Repair","Passive","Control Panel","Power Cabinet=
 - Circuit Breaker Issue","Site went down due to Disjunction of CB (25A) in=
 the TGBT // CB rearm","gaelle.njiofack@matech-cameroun.com","68","22-07-20=
25 21:01:40","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005534772","B=
arriere","","22-07-2025 20:42:56","22-07-2025 18:12:36","23-07-2025 07:19:1=
7","Gen overload // Load balanced","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue on site Ubay: 52.7V site on Gen .TX Fme Flubert (654266068/Hu=
awei) is informed","gaelle.njiofack@matech-cameroun.com","9023","22-07-2025=
 20:42:56","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005534758","N=
kolbong","","22-07-2025 20:40:54","22-07-2025 20:39:49","22-07-2025 21:01:2=
2","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) // Site stabilised","Delor Telezing","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen star=
ted and stopped due to Gen overload(22kva//350A) // Site stabilised","gaell=
e.njiofack@matech-cameroun.com","67","22-07-2025 20:40:54","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005534548","SIM=
BOCK BONAMBAPE","","22-07-2025 20:00:34","22-07-2025 19:58:27","22-07-2025 =
20:00:16","Grid outage, Site went down before Gen start due to poor backup/=
 // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup/ // Grid return","loic.noumsi@matech-cameroun.com",=
"128","22-07-2025 20:00:34","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005534364","Lad=
a I Yde","","22-07-2025 19:39:24","22-07-2025 19:37:19","22-07-2025 21:04:2=
8","Grid outage, Site went down because 01 rectifier dysfunctionning // He =
reset it, Site on grid","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Grid outage, Site went down because 01 rectifi=
er dysfunctionning // He reset it, Site on grid","loic.noumsi@matech-camero=
un.com","126","22-07-2025 19:39:24","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005533980","Lad=
a I Yde","","22-07-2025 18:54:16","22-07-2025 18:52:10","22-07-2025 18:54:2=
8","Grid outage, Site went down due to insufficiency of rectifiers // Grid =
stabilised","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Grid outage, Site went down due to insufficiency of rectif=
iers // Grid stabilised","loic.noumsi@matech-cameroun.com","127","22-07-202=
5 18:54:16","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005533961","A=
wae Ewonkan","","22-07-2025 18:50:02","22-07-2025 18:48:54","22-07-2025 19:=
51:52","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid retur=
n","gaelle.njiofack@matech-cameroun.com","70","22-07-2025 18:50:02","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005533933","M=
ontee-Jouvence-II","","22-07-2025 18:45:12","22-07-2025 18:41:03","22-07-20=
25 20:15:13","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive"," Sie went down due to disjunction of circuit breaker =
(63A*125A) In the DC box OCM // Circuit breaker rearm","gaelle.njiofack@mat=
ech-cameroun.com","271415","22-07-2025 18:45:12","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005533923","D=
amas","IHS_YND_518","22-07-2025 18:43:11","22-07-2025 18:41:03","22-07-2025=
 20:15:13"," Sie went down due to disjunction of circuit breaker (63A*125A)=
 In the DC box OCM // Circuit breaker rearm","MINKA NICOLAS","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue"," Si=
e went down due to disjunction of circuit breaker (63A*125A) In the DC box =
OCM // Circuit breaker rearm","gaelle.njiofack@matech-cameroun.com","129","=
22-07-2025 18:43:11","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005533818","Djo=
nassi-Yde","","22-07-2025 18:15:08","22-07-2025 18:06:00","22-07-2025 19:10=
:45","Site went down due to 02/03 rectifiers Faulty // He replaced them and=
 added another one; site on Grid","Fabrice Pouakam","Equipment Repair","Pas=
sive","Rectifier","Rectifier Cabinet","Site went down due to 02/03 rectifie=
rs Faulty // He replaced them and added another one; site on Grid","gaelle.=
njiofack@matech-cameroun.com","549","22-07-2025 18:15:08","MATECH CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0005533498","D=
ong","","22-07-2025 17:51:07","22-07-2025 17:46:27","22-07-2025 17:48:48","=
Acttve// No power issue on site Ubaie =3D 51.1V site on Battery, The TX FME=
 Gr=E9goire //654547479// from huawei is informed,","Parker Tchoup","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Acttve// No power issue on site Ubaie =3D 51.1V site on Battery, The T=
X FME Gr=E9goire //654547479// from huawei is informed,","gaelle.njiofack@m=
atech-cameroun.com","281","22-07-2025 17:51:07","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005533122","B=
arriere","","22-07-2025 16:57:20","22-07-2025 16:54:12","22-07-2025 18:05:1=
0","Active // No power issue on site Ubay: 52.7V site on Gen .TX Fme Fluber=
t (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue on site Ubay: 52.7V site on Gen .TX Fme Flubert (654266068/Hua=
wei) is informed","gaelle.njiofack@matech-cameroun.com","191","22-07-2025 1=
6:57:20","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005533008","B=
arriere","","22-07-2025 16:38:07","21-07-2025 18:57:32","21-07-2025 19:47:4=
9","Backtracking; 	Active // No power issue on site Ubay: 52.7V site on Gen=
 .TX Fme Flubert (654266068/Huawei) is informed","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Backtracking; 	Active // No power issue on site Ubay: 52.7V site on Gen =
.TX Fme Flubert (654266068/Huawei) is informed","gaelle.njiofack@matech-cam=
eroun.com","78038","22-07-2025 16:38:07","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005532801","S=
oa-Sofamac","","22-07-2025 16:12:12","22-07-2025 16:09:17","22-07-2025 16:1=
6:13","hybrid Grid-gen site .site went down due to hybrid system malfunctio=
n //gen manually started","Siligap Boris","Equipment Repair","Passive","Hyb=
rid","Hybrid Module","hybrid Grid-gen site .site went down due to hybrid sy=
stem malfunction //gen manually started","gaelle.njiofack@matech-cameroun.c=
om","176","22-07-2025 16:12:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0005532661","Garbati =
building","","22-07-2025 15:42:31","22-07-2025 15:38:59","22-07-2025 15:40:=
57","Cascaded Incident from TTO5718409","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down be=
fore Gen started due to poor battery back up // Grid stabilised","system","=
260937","22-07-2025 15:42:31","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005532658","HOP=
ITAL DE LA CAISSE","IHS_YND_024","22-07-2025 15:42:07","22-07-2025 15:38:59=
","22-07-2025 15:40:57","Grid outage site went down before Gen started due =
to poor battery back up // Grid stabilised","Delor Telezing","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage s=
ite went down before Gen started due to poor battery back up // Grid stabil=
ised","loic.noumsi@matech-cameroun.com","189","22-07-2025 15:42:07","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005532633","Matsari"=
,"","22-07-2025 15:39:40","22-07-2025 15:27:19","22-07-2025 15:59:53","Casc=
aded Incident from TTO5718336","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because gen stopped due =
to unknown alarm in the card // He reset Gen card and manually start the ge=
n, SS Ihs Felix Bateu is informed","system","268670","22-07-2025 15:39:40",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005532635","Yoko MTN=
","","22-07-2025 15:39:40","22-07-2025 15:27:19","22-07-2025 15:59:53","Cas=
caded Incident from TTO5718336","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because gen stopped due=
 to unknown alarm in the card // He reset Gen card and manually start the g=
en, SS Ihs Felix Bateu is informed","system","268670","22-07-2025 15:39:40"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005532634","Ngoum","=
","22-07-2025 15:39:40","22-07-2025 15:27:19","22-07-2025 15:59:53","Cascad=
ed Incident from TTO5718336","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because gen stopped due to=
 unknown alarm in the card // He reset Gen card and manually start the gen,=
 SS Ihs Felix Bateu is informed","system","268671","22-07-2025 15:39:40","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005532632","MBIMBIM"=
,"","22-07-2025 15:39:39","22-07-2025 15:27:19","22-07-2025 15:59:53","Casc=
aded Incident from TTO5718336","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because gen stopped due =
to unknown alarm in the card // He reset Gen card and manually start the ge=
n, SS Ihs Felix Bateu is informed","system","268669","22-07-2025 15:39:39",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005532598","N=
gouetou","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_473","22-07-2025 1=
5:33:28","22-07-2025 15:27:19","22-07-2025 16:03:36","Site went down becaus=
e gen stopped due to unknown alarm in the card // He reset Gen card and man=
ually start the gen, SS Ihs Felix Bateu is informed","Parker Tchoup","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Site went down be=
cause gen stopped due to unknown alarm in the card // He reset Gen card and=
 manually start the gen, SS Ihs Felix Bateu is informed","loic.noumsi@matec=
h-cameroun.com","372","22-07-2025 15:33:28","MATECH CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0005532504","S=
OA UNIVERSITY STADIUM","","22-07-2025 15:14:57","22-07-2025 15:10:10","22-0=
7-2025 15:49:31","","Siligap Boris","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","hybrid Grid-gen site .site went down due to hybrid sy=
stem malfunction //gen manually started","gaelle.njiofack@matech-cameroun.c=
om","269686","22-07-2025 15:14:57","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005532500","S=
oa-Sofamac","IHS_YND_720","22-07-2025 15:14:15","22-07-2025 15:10:10","22-0=
7-2025 15:49:31","hybrid Grid-gen site .site went down due to hybrid system=
 malfunction //gen manually started","Siligap Boris","Equipment Repair","Pa=
ssive","Hybrid","Hybrid Module","hybrid Grid-gen site .site went down due t=
o hybrid system malfunction //gen manually started","gaelle.njiofack@matech=
-cameroun.com","246","22-07-2025 15:14:15","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005532459","O=
dza","IHS_YND_580","22-07-2025 15:07:25","22-07-2025 15:04:15","22-07-2025 =
15:22:28","Active//No power issue on site Ubaie: 53 V site on Grid The TX L=
ionel steve (655184876 /Huawei)) is informed.	","Albran Byorel","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site Ubaie: 53 V site on Grid The TX Lionel stev=
e (655184876 /Huawei)) is informed.	","gaelle.njiofack@matech-cameroun.com"=
,"192","22-07-2025 15:07:25","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005532454","M=
arche Odza","","22-07-2025 15:06:50","22-07-2025 15:04:15","22-07-2025 15:2=
2:28","","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Active//No power issue on site Ubaie: 53 V site on Grid The TX L=
ionel steve (655184876 /Huawei)) is informed.	","gaelle.njiofack@matech-cam=
eroun.com","262998","22-07-2025 15:06:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005532440","Melen Ba=
'aba","","22-07-2025 15:04:40","22-07-2025 14:57:06","22-07-2025 15:00:02",=
"Cascaded Incident from TTO5718143","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen failed =
to start due to PWC dysfunctionning // He reset the PWC and Gen manually st=
arted","system","1219885","22-07-2025 15:04:40","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0005532426","Nko=
lfoulou","IHS_YND_308, IHS_YND_719","22-07-2025 15:00:14","22-07-2025 14:57=
:06","22-07-2025 15:00:47","Site went down because Gen failed to start due =
to PWC malfunctioning // He reset the PWC and Gen manually started","Siliga=
p Boris","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Site went down because Gen failed to start due to PWC malfunctioning =
// He reset the PWC and Gen manually started","loic.noumsi@matech-cameroun.=
com","189","22-07-2025 15:00:14","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005532418","T=
SINGA VILLAGE 2","","22-07-2025 14:58:23","22-07-2025 14:57:06","22-07-2025=
 15:00:02","","Delor Telezing","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down because Gen failed to start due to PWC d=
ysfunctionning // He reset the PWC and Gen manually started","gaelle.njiofa=
ck@matech-cameroun.com","1219886","22-07-2025 14:58:23","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005532413","N=
gousso-Savana","IHS_YND_561","22-07-2025 14:57:06","22-07-2025 14:46:59","2=
2-07-2025 15:10:53","No power issue, site is on Grid with Ubaie: 52.4V, NIE=
MEC PIERRE ROLAND  693767710 of CDS Technologie is on site for work on the =
aerial fibre optic who connecting Fandena to Ngousso-Savana. ","Siligap Bor=
is","Customer Equipment Failure","Active","Active Equipment Failure","Fibre=
 Failure","No power issue, site is on grid with Ubaie: 52.4V, NIEMEC PIERRE=
 ROLAND  693767710 of CDS Technologie is on site for work on fibre optics. =
Armand Nguetsa (699949553) from Huawei is informed. ","gaelle.njiofack@mate=
ch-cameroun.com","608","22-07-2025 14:57:06","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005532410","F=
OUGEROLE","","22-07-2025 14:56:32","22-07-2025 14:46:59","22-07-2025 15:10:=
53","","Siligap Boris","Cascade Outage","Active","Cascade Active","Cascade =
Active","NIEMEC PIERRE ROLAND  693767710 of CDS Technologie is on site for =
work on fibre optics.","gaelle.njiofack@matech-cameroun.com","271065","22-0=
7-2025 14:56:32","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005531903","Nko=
lbisson IITA LP","","22-07-2025 13:20:52","22-07-2025 13:11:59","22-07-2025=
 13:20:40","No power issue site on grid with U=3D53.8v Mohamadou(69114435) =
from Huawei is informed.Noticed that it is impacted by Nkolbisson 2 ocm not=
 manage by IHS","","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.8v M=
ohamadou(69114435) from Huawei is informed.Noticed that it is impacted by N=
kolbisson 2 ocm not manage by IHS","cedric.tiani@matech-cameroun.com","535"=
,"22-07-2025 13:20:52","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005531624","Mvo=
g-Manga","","22-07-2025 12:26:16","22-07-2025 12:22:00","22-07-2025 13:16:5=
9","Site went down because Gen overload(22kva,380A) IHS SS  Pascaline  is i=
nformed // Site stabilised","Albran Byorel","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Site went down because Gen overload(22kva,380A)=
 IHS SS  Pascaline  is informed // Site stabilised","cedric.tiani@matech-ca=
meroun.com","258","22-07-2025 12:26:16","MATECH CMR"
"Closed Complete","Site Down","T0288","IHS_YND_001","NOCINC0005531422","Roy=
al Hotel Yde","","22-07-2025 11:52:02","22-07-2025 11:50:36","22-07-2025 12=
:08:15","Grid outage.gen ran until fuel shortage//Refueling done","Paul BIB=
OUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran =
until fuel shortage//Refueling done","cedric.tiani@matech-cameroun.com","87=
","22-07-2025 11:52:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005531392","FOUGEROL=
E","","22-07-2025 11:46:10","22-07-2025 11:34:08","22-07-2025 11:48:45","Ca=
scaded Incident from TTO5716999","Siligap Boris","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue, site is on grid with Uba=
ie: 52.4V, Armand Nguetsa (699949553) from Huawei is informed.","system","2=
61205","22-07-2025 11:46:10","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005531383","N=
gousso-Savana","IHS_YND_561","22-07-2025 11:43:20","22-07-2025 11:34:08","2=
2-07-2025 11:48:45","No power issue, site is on grid with Ubaie: 52.4V, Arm=
and Nguetsa (699949553) from Huawei is informed.","Siligap Boris","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue, site is on grid with Ubaie: 52.4V, Armand Nguetsa (69994=
9553) from Huawei is informed.","vanel.mbiada@matech-cameroun.com","553","2=
2-07-2025 11:43:20","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005531263","Evo=
doula MTN","","22-07-2025 11:09:33","22-07-2025 11:06:22","22-07-2025 11:32=
:31","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","cedr=
ic.tiani@matech-cameroun.com","192","22-07-2025 11:09:33","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005530915","M=
elen Ba'aba","","22-07-2025 10:09:04","22-07-2025 10:06:55","22-07-2025 10:=
31:57","Grid outage, Site went down because Gen start and stopped with ""Hi=
gh temps ""alarm // he added water and manually start the Gen","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid outage, Site went down because Gen start and stopped=
 with ""High temps ""alarm // he added water and manually start the Gen","v=
anel.mbiada@matech-cameroun.com","131","22-07-2025 10:09:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0005530812","Tradex-N=
komo","","22-07-2025 09:43:50","22-07-2025 09:37:38","22-07-2025 10:13:13",=
"Cascaded Incident from TTO5716335","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen failed to start due to battery Gen discharged caused by Static charge=
r faulty// He started Gen with external battery","system","282427","22-07-2=
025 09:43:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0005530813","AWAE OCM=
","","22-07-2025 09:43:50","22-07-2025 09:37:38","22-07-2025 10:13:13","Cas=
caded Incident from TTO5716335","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen failed to start due to battery Gen discharged caused by Static charger=
 faulty// He started Gen with external battery","system","282428","22-07-20=
25 09:43:50","MATECH CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0005530794","Nko=
mo II","IHS_YND_172, IHS_YND_173","22-07-2025 09:39:55","22-07-2025 09:37:3=
8","22-07-2025 10:13:13","Grid outage, Site went down because Gen failed to=
 start due to battery Gen discharged caused by Static charger faulty// He s=
tarted Gen with external battery","Albran Byorel","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Generator Battery","Grid outage, Site went down beca=
use Gen failed to start due to battery Gen discharged caused by Static char=
ger faulty// He started Gen with external battery","cedric.tiani@matech-cam=
eroun.com","138","22-07-2025 09:39:55","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005530767","M=
ambine","","22-07-2025 09:34:26","22-07-2025 09:31:35","22-07-2025 10:39:34=
","Grid outage, site went down because gen ran untill fuel shortage // Refu=
elling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"	Grid outage, site went down because gen ran untill fuel shortage // Refu=
elling done","vanel.mbiada@matech-cameroun.com","173","22-07-2025 09:34:26"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005530741","E=
koumdoum OCM","","22-07-2025 09:28:24","22-07-2025 09:24:11","22-07-2025 10=
:41:07","Grid outage, site went down because Gen failed to start due to ''o=
ver voltage '' alarm // He reset DG card and manually started the Gen","Alb=
ran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, site went down because Gen failed to start due to ''over volt=
age '' alarm // He reset DG card and manually started the Gen","vanel.mbiad=
a@matech-cameroun.com","254","22-07-2025 09:28:24","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005530552","E=
koumdoum OCM","","22-07-2025 08:47:18","22-07-2025 08:44:51","22-07-2025 09=
:14:00","Grid outage, site went down because Gen failed to start due to ''o=
ver voltage '' alarm // He reset DG card and manually started the Gen","Alb=
ran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, site went down because Gen failed to start due to ''over volt=
age '' alarm // He reset DG card and manually started the Gen","vanel.mbiad=
a@matech-cameroun.com","149","22-07-2025 08:47:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0005530530","Eseka OC=
M","","22-07-2025 08:44:21","22-07-2025 08:17:58","22-07-2025 09:06:07","Ca=
scaded Incident from TTO5715934","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to Disjunction o=
f CB(125A) tripped in ATS causing by Lightning // CB put back on","system",=
"272854","22-07-2025 08:44:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0005530533","Boga-Mah=
ole","","22-07-2025 08:44:21","22-07-2025 08:17:58","22-07-2025 09:06:07","=
Cascaded Incident from TTO5715934","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to Disjunction=
 of CB(125A) tripped in ATS causing by Lightning // CB put back on","system=
","272847","22-07-2025 08:44:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0005530532","Mamb",""=
,"22-07-2025 08:44:21","22-07-2025 08:17:58","22-07-2025 09:06:07","Cascade=
d Incident from TTO5715934","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to Disjunction of CB(=
125A) tripped in ATS causing by Lightning // CB put back on","system","2728=
53","22-07-2025 08:44:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005530531","Song-bon=
g","","22-07-2025 08:44:21","22-07-2025 08:17:58","22-07-2025 09:06:07","Ca=
scaded Incident from TTO5715934","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to Disjunction o=
f CB(125A) tripped in ATS causing by Lightning // CB put back on","system",=
"272845","22-07-2025 08:44:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005530528","Eseka To=
wn","","22-07-2025 08:44:20","22-07-2025 08:17:58","22-07-2025 09:06:07","C=
ascaded Incident from TTO5715934","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to Disjunction =
of CB(125A) tripped in ATS causing by Lightning // CB put back on","system"=
,"272851","22-07-2025 08:44:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0005530529","Boumnyeb=
el","","22-07-2025 08:44:20","22-07-2025 08:17:58","22-07-2025 09:06:07","C=
ascaded Incident from TTO5715934","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to Disjunction =
of CB(125A) tripped in ATS causing by Lightning // CB put back on","system"=
,"272852","22-07-2025 08:44:20","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005530325","M=
ontee-Des-Soeurs","","22-07-2025 07:53:36","22-07-2025 07:52:26","22-07-202=
5 07:58:47","Active // No power issue, site is on grid with Ubaie: 53.96V, =
Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue, site is on grid with Ubaie: 53.96V, Mbah hosiah=
(699699694) from Huawei is informed","vanel.mbiada@matech-cameroun.com","72=
","22-07-2025 07:53:36","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005530207","Evo=
doula MTN","","22-07-2025 07:23:48","22-07-2025 07:21:40","22-07-2025 07:29=
:48","Grid outage, Site went down before Gen start due to poor backup//Gen =
Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup//Gen Automatically Started","cedric=
.tiani@matech-cameroun.com","130","22-07-2025 07:23:48","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005529921","Nko=
g-Edzen","","22-07-2025 06:10:10","22-07-2025 06:01:00","22-07-2025 06:22:3=
5","Grid outage. Gen started and stopped due to ""high temp"" alarm // He a=
dded water and Gen manually started","Parker Tchoup","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age. Gen started and stopped due to ""high temp"" alarm // He added water a=
nd Gen manually started","gerard.tchangoue@matech-cameroun.com","551","22-0=
7-2025 06:10:10","MATECH CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0005529914","Av =
Kennedy","","22-07-2025 06:07:50","22-07-2025 05:58:39","23-07-2025 11:15:4=
6"," Grid outage,site went down due to POWER cable stolen (Eneo meter cable=
s stolen)//Eneo meter cables replaced","","Site Asset Theft","Theft","Theft=
","AC Cable Stolen"," Grid outage,site went down due to POWER cable stolen =
(Eneo meter cables stolen)//Eneo meter cables replaced","gerard.tchangoue@m=
atech-cameroun.com","552","22-07-2025 06:07:50","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005529094","O=
dza II OCM","IHS_YND_528","22-07-2025 01:34:30","22-07-2025 01:29:12","22-0=
7-2025 01:36:00","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","gerard.tchangoue@matech-cameroun.com","322","22-07=
-2025 01:34:30","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005529081","M=
EHANDAN","","22-07-2025 01:31:56","22-07-2025 01:29:12","22-07-2025 01:36:0=
0","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid fluctuations, site went down because gen failed to start du=
e to PWC ZTE malfunction // Grid stabilized","gerard.tchangoue@matech-camer=
oun.com","275713","22-07-2025 01:31:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005528985","MEHANDAN=
","","22-07-2025 01:21:55","22-07-2025 01:14:43","22-07-2025 01:21:55","Cas=
caded Incident from TTO5714326","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","262281","22-07-2025 01:21:55","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005528973","O=
dza II OCM","IHS_YND_528","22-07-2025 01:19:30","22-07-2025 01:14:43","22-0=
7-2025 01:21:55","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","gerard.tchangoue@matech-cameroun.com","290","22-07=
-2025 01:19:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005528594","Yoko MTN=
","","22-07-2025 00:25:01","22-07-2025 00:17:07","22-07-2025 04:59:07","Cas=
caded Incident from TTO5713917","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because gen stopped due=
 to unknow alarm in the card // He reset Gen card and manually start the ge=
n","system","1236651","22-07-2025 00:25:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005528591","MBIMBIM"=
,"","22-07-2025 00:25:00","22-07-2025 00:17:07","22-07-2025 04:59:07","Casc=
aded Incident from TTO5713917","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because gen stopped due =
to unknow alarm in the card // He reset Gen card and manually start the gen=
","system","1236653","22-07-2025 00:25:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005528592","Matsari"=
,"","22-07-2025 00:25:00","22-07-2025 00:17:07","22-07-2025 04:59:07","Casc=
aded Incident from TTO5713917","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because gen stopped due =
to unknow alarm in the card // He reset Gen card and manually start the gen=
","system","1236654","22-07-2025 00:25:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005528593","Ngoum","=
","22-07-2025 00:25:00","22-07-2025 00:17:07","22-07-2025 04:59:07","Cascad=
ed Incident from TTO5713917","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because gen stopped due to=
 unknow alarm in the card // He reset Gen card and manually start the gen",=
"system","1236652","22-07-2025 00:25:00","MATECH CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0005528582","Ngo=
uetou","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_473","22-07-2025 00:=
23:15","22-07-2025 00:17:07","22-07-2025 05:17:07","Site went down because =
gen stopped due to unknow alarm in the card // He reset Gen card and manual=
ly start the gen","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Site went down because gen stopped due to unknow ala=
rm in the card // He reset Gen card and manually start the gen","franck.nko=
mot@matech-cameroun.com","370","22-07-2025 00:23:15","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005528343","Nko=
lbong","","21-07-2025 23:03:16","21-07-2025 23:01:57","21-07-2025 23:20:57"=
,"Grid outage,Site Down because Gen started and stopped due to Gen overload=
(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started and=
 stopped due to Gen overload(22kva//350A) //Grid return","franck.nkomot@mat=
ech-cameroun.com","81","21-07-2025 23:03:16","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0005528113","Ngo=
usso-Savana","","21-07-2025 22:08:46","21-07-2025 21:59:59","21-07-2025 22:=
12:59","Grid Outage, site went down because Gen Overload (20Kva, 300A) SS I=
HS BLAISE RAOUL ETCHEU is confirmed // Site stabilized","Siligap Boris","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, site w=
ent down because Gen Overload (20Kva, 300A) SS IHS BLAISE RAOUL ETCHEU is c=
onfirmed // Site stabilized","franck.nkomot@matech-cameroun.com","527","21-=
07-2025 22:08:46","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005528001","Eko=
umdoum OCM","","21-07-2025 21:44:51","21-07-2025 21:34:59","21-07-2025 21:5=
7:41","Site went down because Gen failed to start due to Grid bad voltage /=
/ Grid stabilized","Albran Byorel","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Site went down because Gen failed to star=
t due to Grid bad voltage // Grid stabilized","franck.nkomot@matech-camerou=
n.com","2732","21-07-2025 21:44:51","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005527940","C=
omplexe-BEAC","","21-07-2025 21:33:57","21-07-2025 21:27:50","21-07-2025 22=
:17:07","Eneo fluctuations, site down due to Disjonction of the OCM CB //Si=
te on GEN and CB rearmed","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","BTS Breaker Tripped","Eneo fluctuations, site down due to Disj=
onction of the OCM CB //Site on GEN and CB rearmed","gaelle.njiofack@matech=
-cameroun.com","368","21-07-2025 21:33:57","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005527877","TSI=
NGA VILLAGE 2","","21-07-2025 21:23:23","21-07-2025 21:17:16","21-07-2025 2=
2:30:16","Site went down due to disjunction of Cb(125A) in PWC // He reamed=
 Cb(125A), site on Gen","Delor Telezing","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of Cb(125A) in PWC // He reamed Cb(125A), site on Gen","franck.n=
komot@matech-cameroun.com","368","21-07-2025 21:23:23","MATECH CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0005527855","M=
balla 4","","21-07-2025 21:17:47","21-07-2025 21:15:41","21-07-2025 22:38:4=
1","Grid Outage Site went down because Gen Failed to Start due to Relay 12V=
 faulty // He bypass Relay and Site on Grid","Delor Telezing","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Relay Faulty","Grid Outage Site went dow=
n because Gen Failed to Start due to Relay 12V faulty // He bypass Relay an=
d Site on Grid","gaelle.njiofack@matech-cameroun.com","127","21-07-2025 21:=
17:47","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0005527850","Ngo=
usso-Savana","","21-07-2025 21:16:19","21-07-2025 21:09:08","21-07-2025 21:=
25:08","Grid Outage, site went down because Gen Overload (20Kva, 300A) SS I=
HS BLAISE RAOUL ETCHEU is confirmed // Site stabilized","Siligap Boris","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, site w=
ent down because Gen Overload (20Kva, 300A) SS IHS BLAISE RAOUL ETCHEU is c=
onfirmed // Site stabilized","franck.nkomot@matech-cameroun.com","432","21-=
07-2025 21:16:19","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005527817","N=
kolbong","","21-07-2025 21:11:10","21-07-2025 21:03:04","21-07-2025 22:23:0=
3","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A) //Grid return","gaelle.njiofack=
@matech-cameroun.com","3877","21-07-2025 21:11:10","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005527773","NYO=
M 2 IHS","","21-07-2025 21:02:44","21-07-2025 20:58:30","21-07-2025 22:18:2=
9","Site went down because CB (80A) tripped in PWC who feeds equipments MTN=
 due to load increase// CB put back on","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site w=
ent down because CB (80A) tripped in PWC who feeds equipments MTN due to lo=
ad increase// CB put back on","franck.nkomot@matech-cameroun.com","255","21=
-07-2025 21:02:44","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005527712","O=
mnisport-Rail","","21-07-2025 20:51:18","21-07-2025 20:48:08","21-07-2025 2=
1:15:08","Active // No power issue on site Ubaie: 50.2V site on Grid The TX=
 FME Armand Nguetsa (699949553) from huawei is informed. (Back traking)","D=
elor Telezing","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active // No power issue on site Ubaie: 50.2V si=
te on Grid The TX FME Armand Nguetsa (699949553) from huawei is informed. (=
Back traking)","gaelle.njiofack@matech-cameroun.com","192","21-07-2025 20:5=
1:18","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005527668","Par=
adis Hotel","","21-07-2025 20:48:05","21-07-2025 20:45:48","21-07-2025 23:1=
3:48","Grid Outage, site went down because Gen Overload (12.5Kva, 100A) SS =
IHS BLAISE RAOUL ETCHEU is confirmed//Grid return","Siligap Boris","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, site went d=
own because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL ETCHEU is conf=
irmed//Grid return","franck.nkomot@matech-cameroun.com","138","21-07-2025 2=
0:48:05","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005527538","Eko=
umdoum OCM","","21-07-2025 20:33:03","21-07-2025 20:29:54","21-07-2025 21:2=
7:54","Site went down because Gen failed to start due to Grid bad voltage /=
/ Grid stabilized","Albran Byorel","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Site went down because Gen failed to star=
t due to Grid bad voltage // Grid stabilized","franck.nkomot@matech-camerou=
n.com","294","21-07-2025 20:33:03","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0005527535","Ngo=
usso-Savana","","21-07-2025 20:31:54","21-07-2025 20:27:34","21-07-2025 20:=
44:18","Grid Outage, site went down because Gen Overload (20Kva, 300A) SS I=
HS BLAISE RAOUL ETCHEU is confirmed // Site stabilized","Siligap Boris","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, site w=
ent down because Gen Overload (20Kva, 300A) SS IHS BLAISE RAOUL ETCHEU is c=
onfirmed // Site stabilized","franck.nkomot@matech-cameroun.com","261","21-=
07-2025 20:31:54","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0005527405","Ngo=
usso-Savana","","21-07-2025 20:05:31","21-07-2025 19:55:59","21-07-2025 20:=
08:21","Grid Outage, site went down because Gen Overload (20Kva, 300A) SS I=
HS BLAISE RAOUL ETCHEU is confirmed // Site stabilized","Siligap Boris","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, site w=
ent down because Gen Overload (20Kva, 300A) SS IHS BLAISE RAOUL ETCHEU is c=
onfirmed // Site stabilized","franck.nkomot@matech-cameroun.com","573","21-=
07-2025 20:05:31","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0005527395","H=
-Paradis","","21-07-2025 20:02:29","21-07-2025 19:54:14","21-07-2025 22:15:=
27","Grid Outage, No space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No space =
to deploy MGE // Grid return","gaelle.njiofack@matech-cameroun.com","496","=
21-07-2025 20:02:29","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0005527205","A=
battoir","","21-07-2025 19:19:35","21-07-2025 19:14:28","21-07-2025 21:42:3=
4","Grid Outage, site went down because Gen Overload (22Kva, 280 A) SS IHS =
BLAISE RAOUL ETCHEU is confirmed // load redced and site on gen","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Out=
age, site went down because Gen Overload (22Kva, 280 A) SS IHS BLAISE RAOUL=
 ETCHEU is confirmed // load redced and site on gen","gaelle.njiofack@matec=
h-cameroun.com","309","21-07-2025 19:19:35","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005526968","O=
mnisport-Rail","","21-07-2025 18:22:04","21-07-2025 18:20:57","21-07-2025 1=
9:20:01","Grid outage,Site went down because Gen failed to start due to PSC=
3 Faulty// He started the Gen manually","Delor Telezing","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage,Site went down be=
cause Gen failed to start due to PSC3 Faulty// He started the Gen manually"=
,"gaelle.njiofack@matech-cameroun.com","69","21-07-2025 18:22:04","MATECH C=
MR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0005526965","E=
toudi 2","","21-07-2025 18:21:18","21-07-2025 18:16:08","21-07-2025 19:42:0=
5","Grid  outage, Site down because  gen started but it diesel pre-filter  =
was clog // diesel pre-filter unclog, site left on grid","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Filter","Grid  outage,=
 Site down because  gen started but it diesel pre-filter  was clog // diese=
l pre-filter unclog, site left on grid","gaelle.njiofack@matech-cameroun.co=
m","311","21-07-2025 18:21:18","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005526962","N=
koabang Ebolmedjock","","21-07-2025 18:20:29","21-07-2025 18:13:21","21-07-=
2025 18:24:00","Site  impacted by Nkolmesseng-Abom(CTR-711) Not Manager By =
IHS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equip=
ment Failure","Affected by 3rd Party Site","Site  impacted by Nkolmesseng-A=
bom(CTR-711) Not Manager By IHS","gaelle.njiofack@matech-cameroun.com","430=
","21-07-2025 18:20:29","MATECH CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0005526878","E=
toudi 2","","21-07-2025 18:00:01","21-07-2025 17:57:38","21-07-2025 17:58:3=
3","Grid outage, site down due to poor backup // Gen started automatically"=
,"Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Battery Low","Grid outage, site down due to poor backup // Gen starte=
d automatically","gaelle.njiofack@matech-cameroun.com","145","21-07-2025 18=
:00:01","MATECH CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0005526838","A=
nguissa New","","21-07-2025 17:52:30","21-07-2025 17:47:23","21-07-2025 17:=
54:37","No power issue, site is on grid with Ubaie=3D53V, Eloundou bertrant=
(652586578) from Huawei is informed","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53V, Eloundou bertrant(652586578) from H=
uawei is informed","gaelle.njiofack@matech-cameroun.com","309","21-07-2025 =
17:52:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0005526827","Dragage"=
,"","21-07-2025 17:49:10","21-07-2025 17:34:59","21-07-2025 18:26:55","Casc=
aded Incident from TTO5711943","Mboua Thierry","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Access issue due to landlord, Site went=
 down due to Grid outage // Grid returned","system","289746","21-07-2025 17=
:49:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0005526823","Bastos-B=
AT","","21-07-2025 17:48:20","21-07-2025 17:34:59","21-07-2025 18:26:55","C=
ascaded Incident from TTO5711943","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Access issue due to landlord, Site w=
ent down due to Grid outage // Grid returned","system","289746","21-07-2025=
 17:48:20","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005526803","ARM=
P Building","IHS_YND_192, IHS_YND_129","21-07-2025 17:44:31","21-07-2025 17=
:34:59","21-07-2025 18:26:55","Access issue due to landlord, Site went down=
 due to Grid outage // Grid returned","Mboua Thierry","Access Denial","Leas=
e Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access is=
sue due to landlord, Site went down due to Grid outage // Grid returned","f=
ranck.nkomot@matech-cameroun.com","572","21-07-2025 17:44:31","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005526733","A=
wae Ewonkan","","21-07-2025 17:30:25","21-07-2025 17:28:46","21-07-2025 20:=
13:20","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Reduced charge and  left site on gen","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage site went down due to Gen Overload (20Kva, Iload 320A)IHS SS Alphonse =
is informed // Reduced charge and  left site on gen","gaelle.njiofack@matec=
h-cameroun.com","102","21-07-2025 17:30:25","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005526540","B=
arriere","","21-07-2025 16:50:01","21-07-2025 16:49:55","21-07-2025 18:26:5=
6","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed// Grid return","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Ge=
n overload (30kva, 410A) SS IHS Felix ZAMBE confirmed// Grid return","gaell=
e.njiofack@matech-cameroun.com","9","21-07-2025 16:50:01","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005526527","OBA=
M NGOLA OCM","","21-07-2025 16:47:49","21-07-2025 11:35:00","21-07-2025 12:=
01:29","BACKTRACKING, No power issue on site. Site on Gen with Ubaie=3D49,6=
 on Grid The TX FME SAMBA (654266048) of Huawei is informed","MINKA NICOLAS=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","BACKTRACKING, No power issue on site. Site on Gen with Ubaie=
=3D49,6 on Grid The TX FME SAMBA (654266048) of Huawei is informed","franck=
.nkomot@matech-cameroun.com","18771","21-07-2025 16:47:49","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005526468","O=
lembe","","21-07-2025 16:37:36","21-07-2025 16:34:29","21-07-2025 16:44:34"=
,"IHS Fme Felix Bateu is on site for work // End of work","Fabrice Pouakam"=
,"Installation Activity","Passive","Planned Activity","Installation Activit=
y","IHS Fme Felix Bateu is on site for work // End of work","gaelle.njiofac=
k@matech-cameroun.com","189","21-07-2025 16:37:36","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005526400","E=
lig-Edzoa","","21-07-2025 16:24:59","21-07-2025 16:20:51","21-07-2025 19:41=
:34","Grid only site,No mobile gen available // Grid restoration","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e,No mobile gen available // Grid restoration","gaelle.njiofack@matech-came=
roun.com","251","21-07-2025 16:24:59","MATECH CMR"
"Closed Complete","Site Down","T1431","IHS_YND_561","NOCINC0005526377","FOU=
GEROLE","","21-07-2025 16:18:17","21-07-2025 16:14:05","21-07-2025 16:31:42=
","Grid outage site went down due to Gen Overload (20Kva, Iload 300 A )IHS =
SS Alphonse is informed // Reduced charge and left site on gen","Siligap Bo=
ris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
 site went down due to Gen Overload (20Kva, Iload 300 A )IHS SS Alphonse is=
 informed // Reduced charge and left site on gen","franck.nkomot@matech-cam=
eroun.com","253","21-07-2025 16:18:17","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005526315","E=
toudi","","21-07-2025 16:09:53","21-07-2025 16:00:36","21-07-2025 16:37:16"=
,"Grid outage .site went down due to gen overload(20kva,300 A) SS HIS Berna=
rd Atangana is informed  //we reduce load and gen manually started","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage .site went down due to gen overload(20kva,300 A) SS HIS Bernard Atan=
gana is informed  //we reduce load and gen manually started","gaelle.njiofa=
ck@matech-cameroun.com","559","21-07-2025 16:09:53","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005526251","S=
oa-Sofamac","IHS_YND_720","21-07-2025 15:54:22","21-07-2025 15:50:15","21-0=
7-2025 16:33:22","Grid outage, site went down because gen failed to start w=
ith alarm overvoltage // He reset gen card and gen manually started","Silig=
ap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, site went down because gen failed to start with alarm overvolta=
ge // He reset gen card and gen manually started","gaelle.njiofack@matech-c=
ameroun.com","248","21-07-2025 15:54:22","MATECH CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0005526240","S=
OA UNIVERSITY STADIUM","","21-07-2025 15:52:51","21-07-2025 15:50:15","21-0=
7-2025 16:33:22","","Siligap Boris","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, site went down because gen failed to =
start with alarm overvoltage // He reset gen card and gen manually started"=
,"gaelle.njiofack@matech-cameroun.com","296026","21-07-2025 15:52:51","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005526103","O=
dza II OCM","IHS_YND_528","21-07-2025 15:28:47","21-07-2025 15:20:39","21-0=
7-2025 15:24:21","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","gaelle.njiofack@matech-cameroun.com","492","21-07-=
2025 15:28:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_801","NOCINC0005526084","HOPITAL =
GENERAL RAIL YDE","","21-07-2025 15:24:50","21-07-2025 15:18:27","21-07-202=
5 16:38:27","Cascaded Incident from TTO5711141","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down because gen failed to start due to gen card faulty // Gen started ma=
nually","system","276347","21-07-2025 15:24:50","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005526072","Pha=
rmacie Bleue","IHS_YND_801","21-07-2025 15:23:34","21-07-2025 15:18:27","21=
-07-2025 16:38:27","Grid outage, site went down because gen failed to start=
 due to gen card faulty // Gen started manually","Siligap Boris","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site wen=
t down because gen failed to start due to gen card faulty // Gen started ma=
nually","franck.nkomot@matech-cameroun.com","308","21-07-2025 15:23:34","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005526069","M=
EHANDAN","","21-07-2025 15:23:21","21-07-2025 15:20:39","21-07-2025 15:24:2=
1","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid fluctuations, site went down because gen failed to start du=
e to PWC ZTE malfunction // Grid stabilized","gaelle.njiofack@matech-camero=
un.com","261944","21-07-2025 15:23:21","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005525906","B=
arriere","","21-07-2025 14:50:09","21-07-2025 14:46:02","21-07-2025 16:32:1=
2","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed// Grid return","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Ge=
n overload (30kva, 410A) SS IHS Felix ZAMBE confirmed// Grid return","gaell=
e.njiofack@matech-cameroun.com","251","21-07-2025 14:50:09","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005525552","M=
EFOU ASSI","","21-07-2025 13:29:48","21-07-2025 13:25:43","21-07-2025 13:43=
:04","Site went down due to insufficiency of rectifiers on site SS IHS Feli=
x ZAMBE // SS IHS Felix ZAMBE added one rectifier on site","Fanda Brice","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went down d=
ue to insufficiency of rectifiers on site SS IHS Felix ZAMBE // SS IHS Feli=
x ZAMBE added one rectifier on site","loic.noumsi@matech-cameroun.com","247=
","21-07-2025 13:29:48","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005525511","Sim=
e Building","","21-07-2025 13:18:54","21-07-2025 13:17:49","21-07-2025 13:2=
5:01","Grid outage, Site went down before Gen start due to poor backup // G=
rid return","Mboua Thierry","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage, Site went down before Gen start d=
ue to poor backup // Grid return","loic.noumsi@matech-cameroun.com","66","2=
1-07-2025 13:18:54","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005525501","B=
arriere","","21-07-2025 13:17:12","21-07-2025 13:14:50","21-07-2025 13:15:0=
8","	Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS =
Felix ZAMBE confirmed// Grid return","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","	Grid outage, Site went down because =
Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed// Grid return","gae=
lle.njiofack@matech-cameroun.com","145","21-07-2025 13:17:12","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005525452","F=
ouda-New","","21-07-2025 13:09:19","21-07-2025 13:04:54","21-07-2025 13:05:=
32","Grid outage, site went down before Gen start due to Poor battery backu=
p // Grid return","Delor Telezing","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before Gen =
start due to Poor battery backup // Grid return","loic.noumsi@matech-camero=
un.com","266","21-07-2025 13:09:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005525328","Angongo"=
,"","21-07-2025 12:41:40","21-07-2025 12:09:40","21-07-2025 13:29:54","Casc=
aded Incident from TTO5710210","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage Gen failed to start due to fu=
el shortage // Refueling done","system","266173","21-07-2025 12:41:40","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005525295","ELOUMDEM=
 CARRIERE 2","","21-07-2025 12:31:50","21-07-2025 12:25:43","21-07-2025 12:=
33:58","Cascaded Incident from TTO5710267","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to insuffi=
ciency of rectifiers on site SS IHS Felix ZAMBE // SS IHS Felix ZAMBE added=
 one rectifier on site","system","279524","21-07-2025 12:31:50","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005525294","Eto koss=
 Yde","","21-07-2025 12:31:50","21-07-2025 12:25:43","21-07-2025 12:33:58",=
"Cascaded Incident from TTO5710267","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to insufficiency =
of rectifiers on site SS IHS Felix ZAMBE // SS IHS Felix ZAMBE added one re=
ctifier on site","system","279524","21-07-2025 12:31:50","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005525280","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","21-07-2025 12:28:48","21-07-2025 12:=
25:43","21-07-2025 12:33:58","Site went down due to insufficiency of rectif=
iers on site SS IHS Felix ZAMBE // SS IHS Felix ZAMBE added one rectifier o=
n site","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Site went down due to insufficiency of rectifiers on site SS IHS Fe=
lix ZAMBE // SS IHS Felix ZAMBE added one rectifier on site","loic.noumsi@m=
atech-cameroun.com","188","21-07-2025 12:28:48","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0005525223","Ebe=
ba","IHS_YND_335","21-07-2025 12:17:23","21-07-2025 12:07:40","21-07-2025 1=
3:29:54","Grid outage Gen failed to start due to fuel shortage // Refueling=
 done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid=
 outage Gen failed to start due to fuel shortage // Refueling done","loic.n=
oumsi@matech-cameroun.com","584","21-07-2025 12:17:23","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005525013","M=
vog-Ada_OCM","","21-07-2025 11:56:52","21-07-2025 11:51:47","21-07-2025 11:=
59:55","Grid outage No space to deploy a MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No spa=
ce to deploy a MDG // Grid return","loic.noumsi@matech-cameroun.com","306",=
"21-07-2025 11:56:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_509","NOCINC0005525012","MANGUIER=
S CHAPELLE","","21-07-2025 11:56:40","21-07-2025 11:54:48","21-07-2025 11:5=
8:23","Cascaded Incident from TTO5709961","Fabrice Pouakam","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage,gen failed to =
start due to alarm undervoltage // he reseted it and started the gen","syst=
em","310147","21-07-2025 11:56:40","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005525006","M=
anguier","IHS_YND_509","21-07-2025 11:55:55","21-07-2025 11:54:48","21-07-2=
025 11:58:23","Grid outage,gen failed to start due to alarm undervoltage //=
 he reseted it and started the gen","Fabrice Pouakam","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to start =
due to alarm undervoltage // he reseted it and started the gen","gaelle.nji=
ofack@matech-cameroun.com","68","21-07-2025 11:55:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005524736","Bastos-N=
ylon","","21-07-2025 11:10:11","21-07-2025 11:01:46","21-07-2025 11:33:50",=
"Cascaded Incident from TTO5709641 - Cascade Removed From TTO5709641","Mbou=
a Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Cascaded Incident from TTO5709641 - Cascade Removed From TTO5709641","syste=
m","270185","21-07-2025 11:10:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005524737","Bastos B=
ethesda","","21-07-2025 11:10:11","21-07-2025 11:01:46","21-07-2025 11:33:5=
0","Cascaded Incident from TTO5709641 - Cascade Removed From TTO5709641","M=
boua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","site went down due to 12V relay disconnected due to vibrations from the =
generator // tightening of the relay and site on Gen","system","270189","21=
-07-2025 11:10:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005524734","Golf Qua=
ter","","21-07-2025 11:10:10","21-07-2025 11:01:46","21-07-2025 11:33:50","=
Cascaded Incident from TTO5709641 - Cascade Removed From TTO5709641","Mboua=
 Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","C=
ascaded Incident from TTO5709641 - Cascade Removed From TTO5709641","system=
","270186","21-07-2025 11:10:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0005524735","Nkomkana=
 2","","21-07-2025 11:10:10","21-07-2025 11:01:46","21-07-2025 11:33:50","C=
ascaded Incident from TTO5709641 - Cascade Removed From TTO5709641","Mboua =
Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Ca=
scaded Incident from TTO5709641 - Cascade Removed From TTO5709641","system"=
,"270188","21-07-2025 11:10:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0005524725","Nkomkana=
","","21-07-2025 11:08:00","21-07-2025 11:01:46","21-07-2025 11:33:50","Cas=
caded Incident from TTO5709638","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","site went down due to 12V relay disconnected due to=
 vibrations from the generator // tightening of the relay and site on Gen",=
"system","270188","21-07-2025 11:08:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0005524724","Cite-Ver=
te","","21-07-2025 11:08:00","21-07-2025 11:01:46","21-07-2025 11:33:50","C=
ascaded Incident from TTO5709638","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","site went down due to 12V relay disconnected due =
to vibrations from the generator // tightening of the relay and site on Gen=
","system","270186","21-07-2025 11:08:00","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005524716","T=
singa","","21-07-2025 11:05:41","21-07-2025 11:01:46","21-07-2025 11:33:50"=
,"","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","cascaded site","gaelle.njiofack@matech-cameroun.com","270187","21-=
07-2025 11:05:41","MATECH CMR"
"Closed Complete","Site Down","CTR_122","IHS_YND_230","NOCINC0005524713","M=
eyong-Meyeme","IHS_YND_220, IHS_YND_138, IHS_YND_202, IHS_YND_200, IHS_YND_=
126, IHS_YND_563, IHS_YND_127","21-07-2025 11:04:53","21-07-2025 11:01:46",=
"21-07-2025 11:33:50","site went down due to 12V relay disconnected // We c=
onnected very  welll the relay and site on Gen","TIENTCHEU NZETCHIEU GAEL",=
"Equipment Repair","Passive","ACDG Gen","ACDG - 12V Relay Faulty","site wen=
t down due to 12V relay disconnected // We connected very  welll the relay =
and site on Gen","gaelle.njiofack@matech-cameroun.com","188","21-07-2025 11=
:04:53","MATECH CMR"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0005524437","Ngo=
g Mapubi","","21-07-2025 10:10:52","21-07-2025 10:08:45","21-07-2025 10:11:=
03","Active// No power issue on site ,site on Grid with Ubaie=3D 54,8V The =
fme TX Etienne fopa // 695033981// of huawei is informed.","Kemeni Franklin=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","Active// No power issue on site ,site on Grid with Ubaie=3D 5=
4,8V The fme TX Etienne fopa // 695033981// of huawei is informed.","loic.n=
oumsi@matech-cameroun.com","128","21-07-2025 10:10:52","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005524089","Aba=
ttoir","","21-07-2025 08:58:25","21-07-2025 08:54:10","21-07-2025 08:59:20"=
,"Grid outage, site went down due to poor backup // Grid return","Fabrice P=
ouakam","Equipment Repair","Passive","Control Panel","Power Cabinet - Batte=
ry Low","Grid outage, site went down due to poor backup // Grid return","ga=
elle.njiofack@matech-cameroun.com","1018","21-07-2025 08:58:25","MATECH CMR=
"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005523821","S=
OA TOWN","","21-07-2025 07:40:32","21-07-2025 07:39:14","21-07-2025 07:42:3=
1","Grid outage, site went down because Gen failed to start due to Hybrid s=
ystem malfonction // Grid return","Siligap Boris","Equipment Repair","Passi=
ve","Hybrid","Hybrid Module","Grid outage, site went down because Gen faile=
d to start due to Hybrid system malfonction // Grid return","gaelle.njiofac=
k@matech-cameroun.com","79","21-07-2025 07:40:32","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005523588","NYO=
M FACE MAETUR","","21-07-2025 06:48:53","21-07-2025 06:45:47","21-07-2025 0=
7:43:34","Grid outage, site went down due to fuel shortage // Refuelling do=
ne","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Gri=
d outage, site went downdue to fuel shortage // Refuelling done","loic.noum=
si@matech-cameroun.com","187","21-07-2025 06:48:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005523582","MEHANDAN=
","","21-07-2025 06:47:50","21-07-2025 06:44:59","21-07-2025 06:50:00","Cas=
caded Incident from TTO5708406","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","264198","21-07-2025 06:47:50","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005523575","Odz=
a II OCM","IHS_YND_528","21-07-2025 06:47:05","21-07-2025 06:44:59","21-07-=
2025 06:50:15","Grid fluctuations, site went down because gen failed to sta=
rt due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctua=
tions, site went down because gen failed to start due to PWC ZTE malfunctio=
n // Grid stabilized","loic.noumsi@matech-cameroun.com","128","21-07-2025 0=
6:47:05","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005523556","M=
ontee-Des-Soeurs","","21-07-2025 06:32:50","21-07-2025 06:22:59","21-07-202=
5 07:34:36","Grid outage ,site went down due to Gen overload (15 KVA/210 A)=
 // Grid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Grid outage ,site went down due to Gen overload (15 KVA/2=
10 A) // Grid return","loic.noumsi@matech-cameroun.com","593","21-07-2025 0=
6:32:50","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005523476","M=
ontee-Des-Soeurs","","21-07-2025 06:10:21","21-07-2025 06:02:11","21-07-202=
5 06:10:47","Grid outage ,site down due to Gen overload (15 KVA/210 A)// Gr=
id return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A)// Gri=
d return","gerard.tchangoue@matech-cameroun.com","492","21-07-2025 06:10:21=
","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005523370","NKO=
NGKARAK","","21-07-2025 05:33:21","21-07-2025 05:28:14","21-07-2025 06:10:0=
9","Hybrid gen site, site went down because gen stopped with alarm high tem=
p // he added water in radiator and Gen manually started","TIENTCHEU NZETCH=
IEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Hybrid gen site, site went down because gen stopped=
 with alarm high temp // he added water in radiator and Gen manually starte=
d","edwige.kapawo@matech-cameroun.com","308","21-07-2025 05:33:21","MATECH =
CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005522978","O=
LAMA","","21-07-2025 02:19:54","21-07-2025 02:16:44","21-07-2025 02:30:52",=
"Active // No power issue on site Ubaie: 54.5V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue on site Ubaie: 54.5V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","gerard.tchangoue@matech-cameroun.com","192","21-=
07-2025 02:19:54","MATECH CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0005522958","A=
FEME NORD","","21-07-2025 02:06:06","21-07-2025 01:56:18","21-07-2025 02:10=
:03","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","Active// No power issue, site is on grid with Ubaie=3D=
55,4 V, Mohamadou(691144435) from Huawei is informed","gerard.tchangoue@mat=
ech-cameroun.com","266884","21-07-2025 02:06:06","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0005522955","C=
rf-Nkolbisson","IHS_YND_519","21-07-2025 02:05:30","21-07-2025 01:56:18","2=
1-07-2025 02:10:03","Active// No power issue, site is on grid with Ubaie=3D=
55,4 V, Mohamadou(691144435) from Huawei is informed","TIENTCHEU NZETCHIEU =
GAEL","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active// No power issue, site is on grid with Ubaie=3D55,=
4 V, Mohamadou(691144435) from Huawei is informed","gerard.tchangoue@matech=
-cameroun.com","553","21-07-2025 02:05:30","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005522735","E=
lig-Edzoa","","21-07-2025 00:46:31","21-07-2025 00:40:44","21-07-2025 01:54=
:21","Grid only site,No mobile gen available // Grid restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site,N=
o mobile gen available // Grid restored","gerard.tchangoue@matech-cameroun.=
com","349","21-07-2025 00:46:31","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005522725","N=
YOM 2 IHS","","21-07-2025 00:42:45","21-07-2025 00:38:36","21-07-2025 02:02=
:07","Grid outage,gen stopped with alarm high temp//he added water in radia=
tor","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High=
 Engine Temp - Coolant Level Issue","Grid outage,gen stopped with alarm hig=
h temp//he added water in radiator","gerard.tchangoue@matech-cameroun.com",=
"251","21-07-2025 00:42:45","MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005522562","Mfa=
ndena","","20-07-2025 23:46:30","20-07-2025 23:39:23","21-07-2025 07:05:58"=
,"Grid outage, site went down due to insufficiency of rectifiers // He adde=
d 01 rectifier, site on grid","Delor Telezing","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module","Grid outage, site went down due to insuffi=
ciency of rectifiers // He added 01 rectifier, site on grid","edwige.kapawo=
@matech-cameroun.com","428","20-07-2025 23:46:30","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005522549","S=
atcom","","20-07-2025 23:42:30","20-07-2025 23:39:23","20-07-2025 23:47:15"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","gerard.tchangoue@matec=
h-cameroun.com","188","20-07-2025 23:42:30","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005522417","A=
wae Ewonkan","","20-07-2025 23:07:04","20-07-2025 23:04:44","20-07-2025 23:=
06:44","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid retur=
n","gerard.tchangoue@matech-cameroun.com","143","20-07-2025 23:07:04","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005522256","Ngouetou=
","","20-07-2025 22:23:51","20-07-2025 22:12:39","20-07-2025 23:16:30","Cas=
caded Incident from TTO5706895","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down due =
to Grid bad voltage // Grid stabilised","system","301920","20-07-2025 22:23=
:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005522257","MBIMBIM"=
,"","20-07-2025 22:23:51","20-07-2025 22:12:39","20-07-2025 23:16:30","Casc=
aded Incident from TTO5706895","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid fluctuations, site went down due t=
o Grid bad voltage // Grid stabilised","system","301919","20-07-2025 22:23:=
51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005522255","Matsari"=
,"","20-07-2025 22:23:50","20-07-2025 22:12:39","20-07-2025 23:16:30","Casc=
aded Incident from TTO5706895","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid fluctuations, site went down due t=
o Grid bad voltage // Grid stabilised","system","301921","20-07-2025 22:23:=
50","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0005522236","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","20-07-2025 22:21:52","20-=
07-2025 22:12:39","20-07-2025 23:16:30","Grid fluctuations, site went down =
due to Grid bad voltage // Grid stabilised","Parker Tchoup","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation=
s, site went down due to Grid bad voltage // Grid stabilised","gerard.tchan=
goue@matech-cameroun.com","554","20-07-2025 22:21:52","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005522220","N=
kolbong","","20-07-2025 22:18:36","20-07-2025 22:18:30","20-07-2025 23:39:2=
4","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A) //Grid return","gerard.tchangou=
e@matech-cameroun.com","8","20-07-2025 22:18:36","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005522010","A=
wae Ewonkan","","20-07-2025 21:32:28","20-07-2025 21:25:37","20-07-2025 22:=
32:58","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid retur=
n","franck.nkomot@matech-cameroun.com","413","20-07-2025 21:32:28","MATECH =
CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0005521954","Oss=
ombe","","20-07-2025 21:24:46","20-07-2025 21:16:55","20-07-2025 22:04:43",=
"Hybrid gen site, Site went down because Gen failed to start due to Huawei =
PWC malfunctioning // Grid return","Parker Tchoup","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Hybrid gen site, Site went =
down because Gen failed to start due to Huawei PWC malfunctioning // Grid r=
eturn","franck.nkomot@matech-cameroun.com","472","20-07-2025 21:24:46","MAT=
ECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005521929","Nko=
lbong","","20-07-2025 21:22:42","20-07-2025 21:20:23","20-07-2025 21:44:23"=
,"Grid outage,Site Down because Gen started and stopped due to Gen overload=
(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started and=
 stopped due to Gen overload(22kva//350A) //Grid return","franck.nkomot@mat=
ech-cameroun.com","161","20-07-2025 21:22:42","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005521900","Nko=
abang2","","20-07-2025 21:17:24","20-07-2025 21:09:53","20-07-2025 21:23:53=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed// Grid returned","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen=
 overload (22KVA, 330A), SS Blaise IHS is informed// Grid returned","franck=
.nkomot@matech-cameroun.com","453","20-07-2025 21:17:24","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005521889","S=
atcom","","20-07-2025 21:15:11","20-07-2025 21:06:27","20-07-2025 21:07:27"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","franck.nkomot@matech-c=
ameroun.com","525","20-07-2025 21:15:11","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005521759","Nko=
lbong","","20-07-2025 20:44:22","20-07-2025 20:34:59","20-07-2025 20:51:59"=
,"Grid outage,Site Down because Gen started and stopped due to Gen overload=
(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started and=
 stopped due to Gen overload(22kva//350A) //Grid return","franck.nkomot@mat=
ech-cameroun.com","565","20-07-2025 20:44:22","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005521403","Nko=
lbong","","20-07-2025 19:38:04","20-07-2025 19:33:52","20-07-2025 19:55:52"=
,"Grid outage,Site Down because Gen started and stopped due to Gen overload=
(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started and=
 stopped due to Gen overload(22kva//350A) //Grid return","franck.nkomot@mat=
ech-cameroun.com","275","20-07-2025 19:38:04","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005521077","Nko=
lbong","","20-07-2025 18:38:15","20-07-2025 18:30:58","20-07-2025 18:55:58"=
,"Grid outage,Site Down because Gen started and stopped due to Gen overload=
(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started and=
 stopped due to Gen overload(22kva//350A) //Grid return","franck.nkomot@mat=
ech-cameroun.com","461","20-07-2025 18:38:15","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005520756","Nko=
lbong","","20-07-2025 17:32:31","20-07-2025 17:31:23","20-07-2025 17:49:23"=
,"Grid outage,Site Down because Gen started and stopped due to Gen overload=
(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started and=
 stopped due to Gen overload(22kva//350A) //Grid return","franck.nkomot@mat=
ech-cameroun.com","70","20-07-2025 17:32:31","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005520709","B=
arriere","","20-07-2025 17:22:23","20-07-2025 17:20:17","20-07-2025 17:25:1=
7","Active // No power issue on site Ubay: 52.9V site on Gen .TX Fme Fluber=
t (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue on site Ubay: 52.9V site on Gen .TX Fme Flubert (654266068/Hua=
wei) is informed","franck.nkomot@matech-cameroun.com","128","20-07-2025 17:=
22:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0005520124","Montee-J=
ouvence-II","","20-07-2025 15:19:30","20-07-2025 15:12:47","20-07-2025 15:2=
8:47","Cascaded Incident from TTO5704555","Hyemafo Gildas","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power Issue Site on Grid Ub=
ai =3D53,8 V, The FME The TX FME Mbah Hosiah (674007438) is informed.","sys=
tem","269527","20-07-2025 15:19:30","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005520122","D=
amas","IHS_YND_518","20-07-2025 15:18:58","20-07-2025 15:12:47","20-07-2025=
 15:28:47","No power Issue Site on Grid Ubai =3D53,8 V, The FME The TX FME =
Mbah Hosiah (674007438) is informed.","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
Issue Site on Grid Ubai =3D53,8 V, The FME The TX FME Mbah Hosiah (67400743=
8) is informed.","franck.nkomot@matech-cameroun.com","372","20-07-2025 15:1=
8:58","MATECH CMR"
"Closed Complete","Site Down","T0050","IHS_YND_039","NOCINC0005519770","Sia=
ntou Radio TV","","20-07-2025 14:12:36","20-07-2025 09:11:39","20-07-2025 1=
4:49:39"," Backtracking// Grid only, Site went down because cables which fe=
ed MTN BTS burnt with CB (125A) //We fixed the cable and Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue"," Backtrac=
king// Grid only, Site went down because cables which feed MTN BTS burnt wi=
th CB (125A) //We fixed the cable and Grid return","loic.noumsi@matech-came=
roun.com","18698","20-07-2025 14:12:36","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005519634","Fla=
menco","","20-07-2025 13:49:17","20-07-2025 13:47:06","20-07-2025 13:57:51"=
,"Grid outage, site went down due to poor backup battery // Gen started aut=
omatically","Mboua Thierry","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage, site went down due to poor backup=
 battery // Gen started automatically","loic.noumsi@matech-cameroun.com","1=
32","20-07-2025 13:49:17","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005519161","E=
lig-Edzoa","","20-07-2025 12:32:12","20-07-2025 12:29:05","20-07-2025 16:26=
:05","Grid only site,No mobile gen available // Grid restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site,N=
o mobile gen available // Grid restored","gaelle.njiofack@matech-cameroun.c=
om","189","20-07-2025 12:32:12","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005519141","Eto=
udi","","20-07-2025 12:27:17","20-07-2025 12:24:10","20-07-2025 13:01:51","=
Grid outage, site went down because Gen started and stopped due to oil pres=
sure alarm // He reset DG card and started Gen manually","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
, site went down because Gen started and stopped due to oil pressure alarm =
// He reset DG card and started Gen manually","loic.noumsi@matech-cameroun.=
com","188","20-07-2025 12:27:17","MATECH CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0005518894","A=
nguissa New","","20-07-2025 11:44:41","20-07-2025 11:38:34","20-07-2025 12:=
00:28","No power issue, site is on grid with Ubaie=3D53V, Eloundou bertrant=
(652586578) from Huawei is informed","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53V, Eloundou bertrant(652586578) from H=
uawei is informed","gaelle.njiofack@matech-cameroun.com","368","20-07-2025 =
11:44:41","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005518859","B=
arriere","","20-07-2025 11:37:39","20-07-2025 11:36:32","20-07-2025 11:40:0=
5","Active // No power issue on site Ubay: 52.8V site on Gen .TX Fme Fluber=
t (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue on site Ubay: 52.8V site on Gen .TX Fme Flubert (654266068/Hua=
wei) is informed","gaelle.njiofack@matech-cameroun.com","69","20-07-2025 11=
:37:39","MATECH CMR"
"Closed Complete","Warning","T1071","IHS_YND_343","NOCINC0005518849","Mbedo=
umou - Ekali","","20-07-2025 11:35:33","","","Grid outage.gen start and sto=
pped due to alarm""high temp""//We added coolant and gen manually started",=
"Albran Byorel","Warning","Warning","POWER","Warning - ACDG - Radiator","Gr=
id outage.gen start and stopped due to alarm""high temp""//We added coolant=
 and gen manually started","loic.noumsi@matech-cameroun.com","33","20-07-20=
25 11:35:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_509","NOCINC0005518706","MANGUIER=
S CHAPELLE","","20-07-2025 11:11:40","20-07-2025 11:09:47","20-07-2025 12:3=
2:42","Cascaded Incident from TTO5702958","Fabrice Pouakam","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Gen failed to=
 start due to GE card sabotaged by rodents // GE card standardises, and Gen=
 start manually","system","269716","20-07-2025 11:11:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0005518705","Omnispor=
t-Rail","","20-07-2025 11:11:40","20-07-2025 11:09:47","20-07-2025 12:32:42=
","Cascaded Incident from TTO5702958","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Gen failed to star=
t due to GE card sabotaged by rodents // GE card standardises, and Gen star=
t manually","system","269715","20-07-2025 11:11:40","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005518694","M=
anguier","IHS_YND_506, IHS_YND_509","20-07-2025 11:09:54","20-07-2025 11:09=
:47","20-07-2025 12:32:42","Grid outage, Gen failed to start due to GE card=
 sabotaged by rodents // GE card standardises, and Gen start manually","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","Grid outage, Gen failed to start due to GE card sabotaged by rodents // =
GE card standardises, and Gen start manually","gaelle.njiofack@matech-camer=
oun.com","8","20-07-2025 11:09:54","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005518676","ODZ=
A BORNE 10","","20-07-2025 11:05:18","20-07-2025 10:57:11","20-07-2025 16:5=
2:11","Grid outage, Site went down due to Gen overload (12.5 kva, 180A) // =
Site stabilized","Albran Byorel","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, Site went down due to Gen overload (12.5 kva,=
 180A) // Site stabilized","loic.noumsi@matech-cameroun.com","488","20-07-2=
025 11:05:18","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005518545","Nko=
g-Edzen","","20-07-2025 10:34:28","20-07-2025 10:31:23","20-07-2025 10:55:5=
7","Grid outage. Gen started and stopped due to ""high temp"" alarm // He a=
dded water and Gen manually started","Parker Tchoup","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age. Gen started and stopped due to ""high temp"" alarm // He added water a=
nd Gen manually started","loic.noumsi@matech-cameroun.com","187","20-07-202=
5 10:34:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_087","NOCINC0005518523","Camp-Sic=
-Tsinga","","20-07-2025 10:31:51","20-07-2025 09:38:58","20-07-2025 10:18:0=
3","Cascaded Incident from TTO5702537","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid outage, site went down because Gen fail=
ed to start due to automation malfunctionning // He reset it and started Ge=
n manually","system","268062","20-07-2025 10:31:51","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005518417","Nko=
lnda","","20-07-2025 10:06:19","20-07-2025 10:04:57","20-07-2025 10:24:07",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Grid return","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, site went down before Gen start=
 due to poor battery backup // Grid return","loic.noumsi@matech-cameroun.co=
m","84","20-07-2025 10:06:19","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005518378","O=
bili Carrefour","","20-07-2025 09:57:13","20-07-2025 09:55:08","20-07-2025 =
10:00:23","Active//No power issue on site ,site on Gen with Ubaie=3D53,4V T=
he Tx FME Mbah Hosiah//674007438 is informed,","Paul BIBOUM","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue on site ,site on Gen with Ubaie=3D53,4V The Tx FME Mba=
h Hosiah//674007438 is informed,","gaelle.njiofack@matech-cameroun.com","12=
6","20-07-2025 09:57:13","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005518370","Nsi=
malen MTN","","20-07-2025 09:55:54","20-07-2025 09:54:45","20-07-2025 11:02=
:39","Grid outage, site went down because Gen failed to start due to High t=
emp alarm // He added water and started Gen manually","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because Gen failed to start due to Hig=
h temp alarm // He added water and started Gen manually","loic.noumsi@matec=
h-cameroun.com","70","20-07-2025 09:55:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0005518349","SOA TOWN=
","","20-07-2025 09:50:22","20-07-2025 09:38:58","20-07-2025 10:18:03","Cas=
caded Incident from TTO5702537","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because Ge=
n failed to start due to automation malfunctionning // He reset it and star=
ted Gen manually","system","268076","20-07-2025 09:50:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0005518347","SOA UNIV=
ERSITY STADIUM","","20-07-2025 09:50:21","20-07-2025 09:38:58","20-07-2025 =
10:18:03","Cascaded Incident from TTO5702537","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage, site went d=
own because Gen failed to start due to automation malfunctionning // He res=
et it and started Gen manually","system","268064","20-07-2025 09:50:21","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_322","NOCINC0005518348","Soa-II",=
"","20-07-2025 09:50:21","20-07-2025 09:38:58","20-07-2025 10:18:03","Casca=
ded Incident from TTO5702537","Siligap Boris","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because Gen =
failed to start due to automation malfunctionning // He reset it and starte=
d Gen manually","system","268066","20-07-2025 09:50:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005518346","Akak-Nko=
zoa-MTN-IHS","","20-07-2025 09:50:21","20-07-2025 09:38:58","20-07-2025 10:=
18:03","Cascaded Incident from TTO5702537","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site went do=
wn because Gen failed to start due to automation malfunctionning // He rese=
t it and started Gen manually","system","268071","20-07-2025 09:50:21","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0005518345","Ebogo","=
","20-07-2025 09:50:20","20-07-2025 09:38:58","20-07-2025 10:18:03","Cascad=
ed Incident from TTO5702537","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because Gen f=
ailed to start due to automation malfunctionning // He reset it and started=
 Gen manually","system","268069","20-07-2025 09:50:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_321","NOCINC0005518343","Soa","",=
"20-07-2025 09:50:20","20-07-2025 09:38:58","20-07-2025 10:18:03","Cascaded=
 Incident from TTO5702537","Siligap Boris","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because Gen fai=
led to start due to automation malfunctionning // He reset it and started G=
en manually","system","268067","20-07-2025 09:50:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_317","NOCINC0005518344","Soa-Sofa=
mac","","20-07-2025 09:50:20","20-07-2025 09:38:58","20-07-2025 10:18:03","=
Cascaded Incident from TTO5702537","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 Gen failed to start due to automation malfunctionning // He reset it and s=
tarted Gen manually","system","268075","20-07-2025 09:50:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0005518342","NYOM 2 I=
HS","","20-07-2025 09:50:20","20-07-2025 09:38:58","20-07-2025 10:18:03","C=
ascaded Incident from TTO5702537","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e Gen failed to start due to automation malfunctionning // He reset it and =
started Gen manually","system","268073","20-07-2025 09:50:20","MATECH CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0005518313","S=
OA 2","IHS_YND_703, IHS_YND_707, IHS_YND_321, IHS_YND_317, IHS_YND_725, IHS=
_YND_390, IHS_YND_552, IHS_YND_307, IHS_YND_316, IHS_YND_351, IHS_YND_720, =
IHS_YND_326, IHS_YND_087, IHS_YND_324, IHS_YND_322, IHS_YND_320","20-07-202=
5 09:42:05","20-07-2025 09:38:58","20-07-2025 10:18:03","Grid outage, site =
went down because Gen failed to start due to automation malfunctionning // =
He reset it and started Gen manually","Siligap Boris","Equipment Repair","P=
assive","Control Panel","ATS-AMF Issue","Grid outage, site went down becaus=
e Gen failed to start due to automation malfunctionning // He reset it and =
started Gen manually","gaelle.njiofack@matech-cameroun.com","187","20-07-20=
25 09:42:05","MATECH CMR"
"Closed Complete","Site Down","T0050","IHS_YND_039","NOCINC0005518163","Sia=
ntou Radio TV","","20-07-2025 09:09:53","20-07-2025 09:08:48","20-07-2025 0=
9:10:26","Active//No power issue on site; site is on Grid  with Ubaie=3D53,=
2V, TX FME Brice Tsague (650 21 40 96) from Huawei is informed.","","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site; site is on Grid  with Ubaie=3D53,2V, T=
X FME Brice Tsague (650 21 40 96) from Huawei is informed.","loic.noumsi@ma=
tech-cameroun.com","66","20-07-2025 09:09:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005518127","Bondjock=
","","20-07-2025 08:59:10","20-07-2025 08:47:33","20-07-2025 08:54:31","Cas=
caded Incident from TTO5702288","Fanda Brice","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active//No power issue on site Ubaie=3D56.4=
 V site on Gen. The Tx FME Etienne/651320188/ from Huawei is informed","sys=
tem","285398","20-07-2025 08:59:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005518126","Minka","=
","20-07-2025 08:59:10","20-07-2025 08:47:33","20-07-2025 08:54:31","Cascad=
ed Incident from TTO5702288","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue on site Ubaie=3D56.4 V =
site on Gen. The Tx FME Etienne/651320188/ from Huawei is informed","system=
","285397","20-07-2025 08:59:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005518123","Mom","",=
"20-07-2025 08:59:09","20-07-2025 08:47:33","20-07-2025 08:54:31","Cascaded=
 Incident from TTO5702288","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Active//No power issue on site Ubaie=3D56.4 V si=
te on Gen. The Tx FME Etienne/651320188/ from Huawei is informed","system",=
"285399","20-07-2025 08:59:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005518124","Mbeng","=
","20-07-2025 08:59:09","20-07-2025 08:47:33","20-07-2025 08:54:31","Cascad=
ed Incident from TTO5702288","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue on site Ubaie=3D56.4 V =
site on Gen. The Tx FME Etienne/651320188/ from Huawei is informed","system=
","285397","20-07-2025 08:59:09","MATECH CMR"
"Closed Complete","Site Down","CTR_201","IHS_YND_368","NOCINC0005518080","O=
tele","IHS_YND_370, IHS_YND_369, IHS_YND_371, IHS_YND_554, IHS_YND_553, IHS=
_YND_451, IHS_YND_372","20-07-2025 08:51:44","20-07-2025 08:47:33","20-07-2=
025 08:54:31","Active//No power issue on site Ubaie=3D55.2 V site on Gen. T=
he Tx FME Etienne/651320188/ from Huawei is informed","Fanda Brice","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site Ubaie=3D55.2 V site on Gen. The Tx FME =
Etienne/651320188/ from Huawei is informed","gaelle.njiofack@matech-camerou=
n.com","252","20-07-2025 08:51:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_241","NOCINC0005517871","Etoudi",=
"","20-07-2025 08:22:54","20-07-2025 08:11:15","20-07-2025 08:13:25","Casca=
ded Incident from TTO5702041","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down due =
to Grid bad voltage and poor backup // Gen started automatically","system",=
"273268","20-07-2025 08:22:54","MATECH CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0005517837","Eto=
udi 2","IHS_YND_241","20-07-2025 08:12:24","20-07-2025 08:11:15","20-07-202=
5 08:13:25","Grid fluctuations, site went down due to Grid bad voltage and =
poor backup // Gen started automatically","Fabrice Pouakam","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation=
s, site went down due to Grid bad voltage and poor backup // Gen started au=
tomatically","loic.noumsi@matech-cameroun.com","70","20-07-2025 08:12:24","=
MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005517817","Nko=
lnda","","20-07-2025 08:06:49","20-07-2025 08:04:42","20-07-2025 08:52:39",=
"Grid outage, site went down because Gen failed to start due to alarm ''Und=
ervoltage'' // He reset DG card and started Gen manually","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
 site went down because Gen failed to start due to alarm ''Undervoltage'' /=
/ He reset DG card and started Gen manually","loic.noumsi@matech-cameroun.c=
om","129","20-07-2025 08:06:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005517787","MEHANDAN=
","","20-07-2025 07:56:30","20-07-2025 07:54:37","20-07-2025 08:01:23","Cas=
caded Incident from TTO5701985","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction// Site stabilised","system","2=
67037","20-07-2025 07:56:30","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005517783","Odz=
a II OCM","IHS_YND_528","20-07-2025 07:55:44","20-07-2025 07:54:37","20-07-=
2025 08:01:23","Grid outage, site went down because gen failed to start due=
 to PWC ZTE malfunction// Site stabilised","Albran Byorel","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site w=
ent down because gen failed to start due to PWC ZTE malfunction// Site stab=
ilised","loic.noumsi@matech-cameroun.com","69","20-07-2025 07:55:44","MATEC=
H CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005517536","Ona=
ngondi (melen bikop)","","20-07-2025 06:30:24","20-07-2025 06:28:47","20-07=
-2025 06:48:55","Grid outage, site went down because Gen failed to start du=
e to Hybrid system dysfunctionning // He reset the hybrid system and Gen ma=
nually started","Fanda Brice","Equipment Repair","Passive","Hybrid","Hybrid=
 Module","Grid outage, site went down because Gen failed to start due to Hy=
brid system dysfunctionning // He reset the hybrid system and Gen manually =
started","gerard.tchangoue@matech-cameroun.com","99","20-07-2025 06:30:24",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0005517230","Bastos-B=
AT","","20-07-2025 04:23:10","20-07-2025 04:13:29","20-07-2025 04:22:35","C=
ascaded Incident from TTO5701363","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to Grid outage //=
 He deploy 20KVA","system","273173","20-07-2025 04:23:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0005517229","Dragage"=
,"","20-07-2025 04:23:10","20-07-2025 04:13:29","20-07-2025 04:22:35","Casc=
aded Incident from TTO5701363","Mboua Thierry","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down due to Grid outage // He=
 deploy 20KVA","system","273172","20-07-2025 04:23:10","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005517227","ARM=
P Building","IHS_YND_192, IHS_YND_129","20-07-2025 04:20:38","20-07-2025 04=
:13:29","20-07-2025 06:03:32","Site went down due to Grid outage // He depl=
oy 20KVA","Mboua Thierry","Grid Supply","Passive","Grid","National Grid - G=
rid Outage Issue","Site went down due to Grid outage // He deploy 20KVA","g=
erard.tchangoue@matech-cameroun.com","429","20-07-2025 04:20:38","MATECH CM=
R"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0005516839","H=
-General-Yde","","20-07-2025 01:02:45","20-07-2025 01:02:35","20-07-2025 01=
:04:37","Site went down Gen failed to start due to Grid bad voltage(lack of=
 02 phases on site)//He did a bridge on the Good phase","Siligap Boris","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site=
 went down Gen failed to start due to Grid bad voltage(lack of 02 phases on=
 site)//He did a bridge on the Good phase","vanel.mbiada@matech-cameroun.co=
m","11","20-07-2025 01:02:45","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005516339","N=
kolbong","","19-07-2025 22:57:50","19-07-2025 22:54:37","19-07-2025 23:18:4=
3","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) //Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A) //Grid return","vanel.mbiada@ma=
tech-cameroun.com","194","19-07-2025 22:57:50","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005516069","Bit=
eng-Maetur","","19-07-2025 22:01:12","19-07-2025 21:54:49","19-07-2025 22:0=
4:04","Grid outage site went down because Gen failed to start due PWC ZTE d=
ysfunctioned // He reset the PWC and site on Grid","Mba Lazare Herve","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid out=
age site went down because Gen failed to start due PWC ZTE dysfunctioned //=
 He reset the PWC and site on Grid","ludivine.ngamaleu@ihstowers.com","384"=
,"19-07-2025 22:01:12","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005516013","N=
kolbong","","19-07-2025 21:57:29","19-07-2025 21:53:23","19-07-2025 22:17:1=
7","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started an=
d stopped due to Gen overload(22kva//350A)//Grid return","edwige.kapawo@mat=
ech-cameroun.com","247","19-07-2025 21:57:29","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005515749","N=
kolbong","","19-07-2025 21:05:50","19-07-2025 20:59:41","19-07-2025 21:23:4=
5","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started an=
d stopped due to Gen overload(22kva//350A)//Grid return","edwige.kapawo@mat=
ech-cameroun.com","371","19-07-2025 21:05:50","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005515562","A=
wae Ewonkan","","19-07-2025 20:31:43","19-07-2025 20:29:35","19-07-2025 20:=
48:43","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid retur=
n","edwige.kapawo@matech-cameroun.com","130","19-07-2025 20:31:43","MATECH =
CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005515441","A=
wae Ewonkan","","19-07-2025 20:09:06","19-07-2025 20:07:00","19-07-2025 20:=
10:44","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid retur=
n","edwige.kapawo@matech-cameroun.com","129","19-07-2025 20:09:06","MATECH =
CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005515397","N=
kolbong","","19-07-2025 20:02:40","19-07-2025 19:59:27","19-07-2025 20:22:2=
0","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started an=
d stopped due to Gen overload(22kva//350A)//Grid return","edwige.kapawo@mat=
ech-cameroun.com","194","19-07-2025 20:02:40","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0005515243","H=
-General-Yde","","19-07-2025 19:26:15","19-07-2025 19:24:07","19-07-2025 19=
:29:54","Site went down Gen failed to start due to Grid bad voltage(lack of=
 02 phases on site)//He did a bridge on the Good phase","Siligap Boris","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site=
 went down Gen failed to start due to Grid bad voltage(lack of 02 phases on=
 site)//He did a bridge on the Good phase","edwige.kapawo@matech-cameroun.c=
om","129","19-07-2025 19:26:15","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005515039","N=
kolbong","","19-07-2025 19:01:03","19-07-2025 18:57:54","19-07-2025 19:19:2=
9","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started an=
d stopped due to Gen overload(22kva//350A)//Grid return","edwige.kapawo@mat=
ech-cameroun.com","190","19-07-2025 19:01:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005514961","Carrefou=
rt Nkomo","","19-07-2025 18:45:40","19-07-2025 18:40:52","19-07-2025 19:16:=
53","Cascaded Incident from TTO5698833","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage site went down =
because Gen failed to start due to Gen battery discharged // Gen manually s=
tarted with external battery","system","264344","19-07-2025 18:45:40","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005514959","N=
komo","IHS_YND_174","19-07-2025 18:45:01","19-07-2025 18:40:52","19-07-2025=
 19:20:04","Grid outage site went down because Gen failed to start due to G=
en battery discharged // Gen manually started with external battery","Mba L=
azare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batt=
ery","Grid outage site went down because Gen failed to start due to Gen bat=
tery discharged // Gen manually started with external battery","edwige.kapa=
wo@matech-cameroun.com","251","19-07-2025 18:45:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005514954","Mfou EPC=
","","19-07-2025 18:44:10","19-07-2025 18:38:07","19-07-2025 18:55:46","Cas=
caded Incident from TTO5698827","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid return","system","264508","19-07-2025 18:4=
4:10","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005514952","M=
fou OCM","IHS_YND_674","19-07-2025 18:43:16","19-07-2025 18:38:07","19-07-2=
025 18:55:46","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Start=
ed due to poor backup //Grid return","edwige.kapawo@matech-cameroun.com","3=
11","19-07-2025 18:43:16","MATECH CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0005514789","S=
apeur","","19-07-2025 18:06:02","19-07-2025 18:05:55","19-07-2025 18:06:03"=
,"Grid outage, site down due to poor backup// eneo return","Mboua Thierry",=
"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low",=
"Grid outage, site down due to poor backup// eneo return","edwige.kapawo@ma=
tech-cameroun.com","8","19-07-2025 18:06:02","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0005514764","NTE=
MASSI","","19-07-2025 18:01:24","19-07-2025 17:59:02","19-07-2025 18:47:18"=
,"site went down because Gen failed to start due to Grid contacteur faulty =
// He started the Gen manually","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","ATS-AMF Issue","site went down because Gen failed to st=
art due to Grid contacteur faulty // He started the Gen manually","edwige.k=
apawo@matech-cameroun.com","143","19-07-2025 18:01:24","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005514695","Par=
adis Hotel","","19-07-2025 17:47:58","19-07-2025 17:45:47","19-07-2025 17:5=
3:02","Grid Outage, site went down because Gen Overload (12.5Kva, 100A) SS =
IHS BLAISE RAOUL ETCHEU is confirmed//Grid return","Siligap Boris","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, site went d=
own because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL ETCHEU is conf=
irmed//Grid return","cedric.tiani@matech-cameroun.com","132","19-07-2025 17=
:47:58","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005514662","A=
wae Ewonkan","","19-07-2025 17:40:29","19-07-2025 17:36:15","19-07-2025 18:=
47:41","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid retur=
n","edwige.kapawo@matech-cameroun.com","257","19-07-2025 17:40:29","MATECH =
CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005514567","A=
wae Escalier","","19-07-2025 17:26:06","19-07-2025 17:24:59","19-07-2025 17=
:59:57","Grid outage, site went down because gen start and stopped with ala=
rm overcurrent // He reset gen card and gen manually started","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, site went down because gen start and stopped with alarm overcurrent //=
 He reset gen card and gen manually started","edwige.kapawo@matech-cameroun=
.com","69","19-07-2025 17:26:06","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0005514545","H=
-Paradis","","19-07-2025 17:24:10","19-07-2025 17:21:00","19-07-2025 18:00:=
42","Grid Outage, No space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No space =
to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","191","19=
-07-2025 17:24:10","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005514346","Men=
dong NB","","19-07-2025 16:53:55","19-07-2025 16:42:44","19-07-2025 16:50:1=
2","Active:No power issue on site, Ubaie: 53.5V Site on Grid with The Tx Fm=
e Mbah hosiah (?+237 6 99 69 96 94) from Huawei is informed","","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active:No power issue on site, Ubaie: 53.5V Site on Grid with The Tx Fme M=
bah hosiah (?+237 6 99 69 96 94) from Huawei is informed","cedric.tiani@mat=
ech-cameroun.com","672","19-07-2025 16:53:55","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005514341","Car=
refour Simbock","","19-07-2025 16:52:14","19-07-2025 16:45:07","19-07-2025 =
18:30:52","Site went down due to Gen overload (17kva //180A) SS HIS Felix Z=
ambe is informed and confirmed // Grid return","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen o=
verload (17kva //180A) SS HIS Felix Zambe is informed and confirmed // Grid=
 return","cedric.tiani@matech-cameroun.com","427","19-07-2025 16:52:14","MA=
TECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005514230","Eto=
udi","","19-07-2025 16:32:09","19-07-2025 16:28:35","19-07-2025 16:54:17","=
Grid outage, site went down because Gen failed to start due to Alarm *Under=
frequency*//He reset the Gen card and started the Gen manually","Fabrice Po=
uakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage, site went down because Gen failed to start due to Alarm *Underfreq=
uency*//He reset the Gen card and started the Gen manually","cedric.tiani@m=
atech-cameroun.com","216","19-07-2025 16:32:09","MATECH CMR"
"Closed Complete","Warning","T1071","IHS_YND_343","NOCINC0005514054","Mbedo=
umou - Ekali","","19-07-2025 15:59:15","","","Grid outage.gen start and sto=
pped due to alarm""high temp""//We added coolant and gen manually started",=
"Albran Byorel","Warning","Warning","POWER","Warning - ACDG - Radiator","Gr=
id outage.gen start and stopped due to alarm""high temp""//We added coolant=
 and gen manually started","cedric.tiani@matech-cameroun.com","9325","19-07=
-2025 15:59:15","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0005514016","Aba=
ttoir","","19-07-2025 15:52:31","19-07-2025 15:50:10","19-07-2025 17:29:36"=
,"Grid outage.gen started and stopped due to diesel pump broken // He repla=
ced Diesel pump","Fabrice Pouakam","Fuel Outage (Probable)","Passive","ACDG=
 Gen","ACDG - Fuel Pump","Grid outage.gen started and stopped due to diesel=
 pump broken // He replaced Diesel pump","cedric.tiani@matech-cameroun.com"=
,"143","19-07-2025 15:52:31","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005513983","NKO=
NGKARAK","","19-07-2025 15:47:51","19-07-2025 15:44:39","19-07-2025 16:54:1=
8","Grid outage, Site went down because Gen started and stopped due to High=
 temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, Site went down because Gen started and stop=
ped due to High temp alarm //He added water and Gen start manually","cedric=
.tiani@matech-cameroun.com","193","19-07-2025 15:47:51","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0005513927","NTE=
MASSI","","19-07-2025 15:40:02","19-07-2025 15:35:59","19-07-2025 16:54:44"=
,"site went down because Gen failed to start due to Grid contacteur faulty =
// He started the Gen manually","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","ATS-AMF Issue","site went down because Gen failed to st=
art due to Grid contacteur faulty // He started the Gen manually","cedric.t=
iani@matech-cameroun.com","244","19-07-2025 15:40:02","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005513907","B=
arriere","","19-07-2025 15:33:51","18-07-2025 18:06:24","19-07-2025 19:17:3=
6","Active // No power issue on site Ubay: 52.8V site on Gen .TX Fme Fluber=
t (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue on site Ubay: 52.8V site on Gen .TX Fme Flubert (654266068/Hua=
wei) is informed","cedric.tiani@matech-cameroun.com","77249","19-07-2025 15=
:33:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005513846","Mfou EPC=
","","19-07-2025 15:26:21","19-07-2025 15:19:33","19-07-2025 15:40:52","Cas=
caded Incident from TTO5697592","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid return","system","269151","19-07-2025 15:2=
6:21","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005513843","M=
fou OCM","IHS_YND_674","19-07-2025 15:25:41","19-07-2025 15:19:33","19-07-2=
025 15:40:52","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Start=
ed due to poor backup //Grid return","edwige.kapawo@matech-cameroun.com","3=
69","19-07-2025 15:25:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005513827","Carrefou=
rt Nkomo","","19-07-2025 15:22:40","19-07-2025 15:17:40","19-07-2025 17:05:=
35","Cascaded Incident from TTO5697564","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage site went down =
because Gen failed to start due to Gen battery discharged  // Gen manually =
started with external battery","system","1218709","19-07-2025 15:22:40","MA=
TECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005513816","Nko=
mo","IHS_YND_174","19-07-2025 15:19:01","19-07-2025 15:17:40","19-07-2025 1=
7:07:18","Grid outage site went down because Gen failed to start due to Gen=
 battery discharged  // Gen manually started with external battery","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batte=
ry","Grid outage site went down because Gen failed to start due to Gen batt=
ery discharged  // Gen manually started with external battery","cedric.tian=
i@matech-cameroun.com","82","19-07-2025 15:19:01","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0005513767","H=
-General-Yde","","19-07-2025 15:11:58","19-07-2025 15:06:52","19-07-2025 17=
:22:50","Grid outage, Site went down because Gen failed to start due to ATS=
 faulty// Grid return","Siligap Boris","Equipment Repair","Passive","Contro=
l Panel","ATS-AMF Issue","	Grid outage, Site went down because Gen failed t=
o start due to ATS faulty// Grid return","edwige.kapawo@matech-cameroun.com=
","307","19-07-2025 15:11:58","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005513650","N=
koabang Ebolmedjock","","19-07-2025 14:53:45","19-07-2025 14:45:39","19-07-=
2025 14:50:58","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Gen. Notice that it is impacted b=
y Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matech-camero=
un.com","488","19-07-2025 14:53:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005512978","SOA VILL=
AGE","","19-07-2025 13:37:11","19-07-2025 13:32:59","19-07-2025 13:59:59","=
Cascaded Incident from TTO5696616","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due to Gen battery discharged causing by charging alter=
nator faulty // Gen manually started with external battery","system","28268=
4","19-07-2025 13:37:11","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005512964","SOA=
 TOWN","IHS_YND_323","19-07-2025 13:35:05","19-07-2025 13:30:59","19-07-202=
5 13:59:59","Grid outage site went down because Gen failed to start due to =
Gen battery discharged caused by faulty charging alternator // Gen manually=
 started with external battery","Siligap Boris","Equipment Repair","Passive=
","ACDG Gen","ACDG - Generator Battery","Grid outage site went down because=
 Gen failed to start due to Gen battery discharged caused by faulty chargin=
g alternator // Gen manually started with external battery","franck.nkomot@=
matech-cameroun.com","302","19-07-2025 13:35:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005512920","FOUGEROL=
E","","19-07-2025 13:25:41","19-07-2025 13:20:59","19-07-2025 14:48:41","Ca=
scaded Incident from TTO5696546","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down because g=
en start and stopped with Under voltage alarm // he Reset the Gen card and =
gen started","system","283401","19-07-2025 13:25:41","MATECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0005512859","HOP=
ITAL GENERAL RAIL YDE","","19-07-2025 13:11:17","19-07-2025 13:01:27","19-0=
7-2025 14:11:27","","Delor Telezing","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","	Grid outage, site went down because gen failed t=
o start due to gen card faulty //Grid return","franck.nkomot@matech-camerou=
n.com","284574","19-07-2025 13:11:17","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005512849","Pha=
rmacie Bleue","IHS_YND_801","19-07-2025 13:08:37","19-07-2025 13:01:27","19=
-07-2025 14:11:27","	Grid outage, site went down because gen failed to star=
t due to gen card faulty //Grid return","Siligap Boris","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","	Grid outage, site went down b=
ecause gen failed to start due to gen card faulty //Grid return","franck.nk=
omot@matech-cameroun.com","431","19-07-2025 13:08:37","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005512829","Men=
dong NB","","19-07-2025 13:06:11","19-07-2025 12:59:56","19-07-2025 16:18:3=
8","Active:No power issue on site, Ubaie: 53.5V Site on Grid with The Tx Fm=
e Mbah hosiah (?+237 6 99 69 96 94) from Huawei is informed","","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active:No power issue on site, Ubaie: 53.5V Site on Grid with The Tx Fme M=
bah hosiah (?+237 6 99 69 96 94) from Huawei is informed","franck.nkomot@ma=
tech-cameroun.com","376","19-07-2025 13:06:11","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0005512803","Ngo=
usso-Savana","IHS_YND_561","19-07-2025 13:02:10","19-07-2025 12:52:59","19-=
07-2025 14:54:22","Grid outage, site went down because gen start and stoppe=
d with Under voltage alarm // he Reset the Gen card and gen started","Silig=
ap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, site went down because gen start and stopped with Under voltage=
 alarm // he Reset the Gen card and gen started","franck.nkomot@matech-came=
roun.com","552","19-07-2025 13:02:10","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005512696","Ngo=
usso Vallee","","19-07-2025 12:37:56","19-07-2025 12:27:59","19-07-2025 13:=
33:38","Grid outage, Site went down before Gen start due to poor backup// h=
e manual start Gen","Siligap Boris","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup// he manual start Gen","franck.nkomot@matech-came=
roun.com","598","19-07-2025 12:37:56","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005512259","Car=
refour Simbock","","19-07-2025 11:34:50","19-07-2025 11:26:38","19-07-2025 =
16:33:42","Site went down due to Gen overload (17kva //180A) SS HIS Felix Z=
ambe is informed and confirmed // Grid return","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen o=
verload (17kva //180A) SS HIS Felix Zambe is informed and confirmed // Grid=
 return","franck.nkomot@matech-cameroun.com","493","19-07-2025 11:34:50","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0005511584","M=
atomb","","19-07-2025 10:03:50","19-07-2025 09:53:59","19-07-2025 10:08:59"=
,"Site went down due to insufficient rectifiers on site//Site stabilized","=
Kemeni Franklin","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient rectifiers on site//Site stabilized",=
"franck.nkomot@matech-cameroun.com","592","19-07-2025 10:03:50","MATECH CMR=
"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005511535","Car=
refour Simbock","","19-07-2025 09:55:34","19-07-2025 09:49:08","19-07-2025 =
10:06:08","Grid outage.site went down due to bad grid voltage//We bypass gr=
id and gen manually started","Hyemafo Gildas","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid outage.site went down due=
 to bad grid voltage//We bypass grid and gen manually started","franck.nkom=
ot@matech-cameroun.com","386","19-07-2025 09:55:34","MATECH CMR"
"Closed Complete","Warning","T1545","IHS_YND_237","NOCINC0005511448","Carre=
four Simbock","","19-07-2025 09:35:44","","","Site went down due to Gen ove=
rload (17kva //180A) SS HIS Felix Zambe is informed and confirmed // Grid r=
eturn","Hyemafo Gildas","Warning","Warning","POWER","Warning - ACDG - Overl=
oad","Site went down due to Gen overload (17kva //180A) SS HIS Felix Zambe =
is informed and confirmed // Grid return","franck.nkomot@matech-cameroun.co=
m","585","19-07-2025 09:35:44","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0005511292","E=
kombitie","","19-07-2025 08:59:51","19-07-2025 08:59:35","19-07-2025 09:00:=
35","Active// No power issue on site ,site on Grid with Ubaie=3D54.6 V The =
Tx FME Synphorien /691316854//from huawei is informed","Fabrice Pouakam","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active// No power issue on site ,site on Grid with Ubaie=3D54.6 V=
 The Tx FME Synphorien /691316854//from huawei is informed","franck.nkomot@=
matech-cameroun.com","18","19-07-2025 08:59:51","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005511173","Lad=
a I Yde","","19-07-2025 08:40:26","19-07-2025 08:34:47","19-07-2025 10:02:4=
7","Grid outage, site went down because gen failed to start with alarm unde=
rvoltage // He reduced load and gen manually started","Mba Lazare Herve","E=
quipment Repair","Passive","ACDG Gen","ACDG - Under Voltage","Grid outage, =
site went down because gen failed to start with alarm undervoltage // He re=
duced load and gen manually started","franck.nkomot@matech-cameroun.com","3=
40","19-07-2025 08:40:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005510530","Nkolondo=
m","","19-07-2025 06:27:02","19-07-2025 06:19:38","19-07-2025 07:16:38","Ca=
scaded Incident from TTO5693873","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen started and stopped=
 due to fuel filter flushed//we clean fuel filter and gen manually started"=
,"system","1222154","19-07-2025 06:27:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0005510529","Messassi=
 2","","19-07-2025 06:27:01","19-07-2025 06:19:38","19-07-2025 07:16:38","C=
ascaded Incident from TTO5693873","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen started and stoppe=
d due to fuel filter flushed//we clean fuel filter and gen manually started=
","system","1222153","19-07-2025 06:27:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0005510526","Messassi=
","","19-07-2025 06:27:01","19-07-2025 06:19:38","19-07-2025 07:16:38","Cas=
caded Incident from TTO5693873","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen started and stopped =
due to fuel filter flushed//we clean fuel filter and gen manually started",=
"system","1222152","19-07-2025 06:27:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0005510528","Nyom OCM=
","","19-07-2025 06:27:01","19-07-2025 06:19:38","19-07-2025 07:16:38","Cas=
caded Incident from TTO5693873","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen started and stopped =
due to fuel filter flushed//we clean fuel filter and gen manually started",=
"system","1222154","19-07-2025 06:27:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0005510527","Nkozoa",=
"","19-07-2025 06:27:01","19-07-2025 06:19:38","19-07-2025 07:16:38","Casca=
ded Incident from TTO5693873","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage.gen started and stopped du=
e to fuel filter flushed//we clean fuel filter and gen manually started","s=
ystem","1222151","19-07-2025 06:27:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0005510525","Olembe-T=
erminus","","19-07-2025 06:27:00","19-07-2025 06:19:38","19-07-2025 07:16:3=
8","Cascaded Incident from TTO5693873","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage.gen started and s=
topped due to fuel filter flushed//we clean fuel filter and gen manually st=
arted","system","1222151","19-07-2025 06:27:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0005510524","NKOLMEKO=
NG YDE","","19-07-2025 06:27:00","19-07-2025 06:19:38","19-07-2025 07:16:38=
","Cascaded Incident from TTO5693873","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage.gen started and st=
opped due to fuel filter flushed//we clean fuel filter and gen manually sta=
rted","system","1222153","19-07-2025 06:27:00","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005510504","O=
lembe","IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IHS_YND_303, IH=
S_YND_280, IHS_YND_304","19-07-2025 06:21:45","19-07-2025 06:19:38","19-07-=
2025 07:16:38","Fuel outage // refueling done ","Fabrice Pouakam","Fuel Out=
age","Passive","Diesel","Diesel Outage","Fuel outage // refueling done ","v=
anel.mbiada@matech-cameroun.com","129","19-07-2025 06:21:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005510007","Mfou EPC=
","","19-07-2025 01:59:30","19-07-2025 01:50:37","19-07-2025 02:01:22","Cas=
caded Incident from TTO5693322","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issues iste on Grid w=
ith Ubay=3D54.9V ,The FME TX Fulbert (654266068) from Huawei is informed.",=
"system","267231","19-07-2025 01:59:30","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005509984","M=
fou OCM","IHS_YND_674","19-07-2025 01:53:45","19-07-2025 01:50:37","19-07-2=
025 02:01:22","Active//No power issues iste on Grid with Ubay=3D54.9V ,The =
FME TX Fulbert (654266068) from Huawei is informed.","Mba Lazare Herve","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issues iste on Grid with Ubay=3D54.9V ,The FME TX=
 Fulbert (654266068) from Huawei is informed.","vanel.mbiada@matech-camerou=
n.com","189","19-07-2025 01:53:45","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005509776","N=
kolbong","","19-07-2025 00:01:30","19-07-2025 00:00:14","19-07-2025 00:20:3=
7","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started =
and stopped due to Gen overload(22kva//350A) // Grid return","vanel.mbiada@=
matech-cameroun.com","78","19-07-2025 00:01:30","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005509474","N=
kolbong","","18-07-2025 22:31:54","18-07-2025 22:30:46","18-07-2025 22:52:2=
4","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started =
and stopped due to Gen overload(22kva//350A) // Grid return","vanel.mbiada@=
matech-cameroun.com","69","18-07-2025 22:31:54","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005509320","TSI=
NGA VILLAGE 2","","18-07-2025 22:04:59","18-07-2025 22:02:53","18-07-2025 2=
2:58:56","Site went down due to CB(125A)in PWC that tripped MTN //He rearme=
d it","Delor Telezing","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Circuit Breaker Issue","Site went down due to CB(125A)in PWC that=
 tripped MTN //He rearmed it","gerard.tchangoue@matech-cameroun.com","128",=
"18-07-2025 22:04:59","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005509205","SIM=
BOCK BONAMBAPE","","18-07-2025 21:49:24","18-07-2025 21:47:18","18-07-2025 =
21:49:18","Grid outage, Site went down before Gen start due to poor backup =
// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.co=
m","127","18-07-2025 21:49:24","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005509178","Nko=
lbong","","18-07-2025 21:44:54","18-07-2025 21:42:45","18-07-2025 22:01:10"=
,"Grid outage,Site Down because Gen started and stopped due to Gen overload=
(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started an=
d stopped due to Gen overload(22kva//350A) // Grid return","gerard.tchangou=
e@matech-cameroun.com","130","18-07-2025 21:44:54","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0005508675","Yok=
o MTN","IHS_YND_475","18-07-2025 20:07:37","18-07-2025 19:58:23","18-07-202=
5 20:34:56","Grid outage gen failed to start due to automation malfuncttion=
ning//Gen manually started","Parker Tchoup","Equipment Repair","Passive","C=
ontrol Panel","ATS-AMF Issue","Grid outage gen failed to start due to autom=
ation malfuncttionning//Gen manually started","gerard.tchangoue@matech-came=
roun.com","555","18-07-2025 20:07:37","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0005508638","Ngo=
um","","18-07-2025 19:58:14","18-07-2025 19:58:23","18-07-2025 20:34:56","S=
ite impacted  by Yoko","Parker Tchoup","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","Grid outage gen failed to start due to automati=
on malfuncttionning//Gen manually started","gerard.tchangoue@matech-camerou=
n.com","309988","18-07-2025 19:58:14","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0005508618","NKO=
MEKUI OCM","","18-07-2025 19:51:41","18-07-2025 19:47:35","18-07-2025 19:56=
:56","No power issue site on Gen with U=3D54.5 V The Tx Fme Mohamadou mouam=
 // 691144435 from Huawei is informed site impacted by Mbankolo camtel","TI=
ENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue site on Gen with U=3D54.=
5 V The Tx Fme Mohamadou mouam // 691144435 from Huawei is informed site im=
pacted by Mbankolo camtel","gerard.tchangoue@matech-cameroun.com","248","18=
-07-2025 19:51:41","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005508529","E=
toudi","","18-07-2025 19:34:09","18-07-2025 19:30:00","18-07-2025 20:15:38"=
,"Site went down because  rectifiers CB faulty // He replaced rectifier CB"=
,"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier - Ci=
rcuit Breaker","Site went down because  rectifiers CB faulty // He replaced=
 rectifier CB","edwige.kapawo@matech-cameroun.com","250","18-07-2025 19:34:=
09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005508405","Mfou EPC=
","","18-07-2025 19:10:00","18-07-2025 19:04:14","18-07-2025 19:09:37","Cas=
caded Incident from TTO5691555","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid return","system","262928","18-07-2025 19:1=
0:00","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005508402","M=
fou OCM","IHS_YND_674","18-07-2025 19:09:23","18-07-2025 19:04:14","18-07-2=
025 19:18:15","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Start=
ed due to poor backup //Grid return","edwige.kapawo@matech-cameroun.com","3=
11","18-07-2025 19:09:23","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005508060","M=
fou OCM","","18-07-2025 18:04:39","18-07-2025 18:01:29","18-07-2025 18:21:3=
6","Grid Outage, Site Down before gen Started due to poor backup //Grid ret=
urn","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid Outage, Site Down before gen Started due to p=
oor backup //Grid return","edwige.kapawo@matech-cameroun.com","191","18-07-=
2025 18:04:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005507878","Mfou EPC=
","","18-07-2025 17:36:50","18-07-2025 17:34:11","18-07-2025 17:55:28","Cas=
caded Incident from TTO5690992","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid return","system","268269","18-07-2025 17:3=
6:50","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005507877","M=
fou OCM","IHS_YND_674","18-07-2025 17:36:20","18-07-2025 17:34:11","18-07-2=
025 17:55:28","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Start=
ed due to poor backup //Grid return","edwige.kapawo@matech-cameroun.com","1=
30","18-07-2025 17:36:20","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005507855","B=
arriere","","18-07-2025 17:32:17","18-07-2025 17:31:59","18-07-2025 17:35:4=
3","Active // No power issue on site Ubay: 52.8V site on Gen .TX Fme Fluber=
t (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue on site Ubay: 52.8V site on Gen .TX Fme Flubert (654266068/Hua=
wei) is informed","edwige.kapawo@matech-cameroun.com","20","18-07-2025 17:3=
2:17","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005507801","Eto=
udi","","18-07-2025 17:27:34","18-07-2025 17:24:26","18-07-2025 18:33:25","=
Grid Fluctuation, site went down before Gen start due to poor battery backu=
p // He put Site on Gen ","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went do=
wn before Gen start due to poor battery backup // He put Site on Gen ","ger=
ard.tchangoue@matech-cameroun.com","189","18-07-2025 17:27:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0005507648","Dong",""=
,"18-07-2025 17:04:40","18-07-2025 16:54:20","18-07-2025 17:04:43","Cascade=
d Incident from TTO5690721","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Site impacted by Bandjock-CAMRAIL not managed=
 by IHS","system","263654","18-07-2025 17:04:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0005507647","Nguila",=
"","18-07-2025 17:04:39","18-07-2025 16:54:20","18-07-2025 17:04:43","Casca=
ded Incident from TTO5690721","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Site impacted by Bandjock-CAMRAIL not manag=
ed by IHS","system","263653","18-07-2025 17:04:39","MATECH CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0005507636","D=
onga","IHS_YND_433, IHS_YND_444","18-07-2025 17:00:33","18-07-2025 16:54:20=
","18-07-2025 17:04:43","Site impacted by Bandjock-CAMRAIL not managed by I=
HS","Parker Tchoup","Customer Equipment Failure","Active","Active Equipment=
 Failure","Affected by 3rd Party Site","Site impacted by Bandjock-CAMRAIL n=
ot managed by IHS","edwige.kapawo@matech-cameroun.com","374","18-07-2025 17=
:00:33","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005507611","F=
ouda-New","","18-07-2025 16:56:22","18-07-2025 16:52:07","18-07-2025 18:32:=
18","Grid Outage, Gen failed to start due to Poor battery backup // Gen sta=
rted manually","Delor Telezing","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid Outage, Gen failed to start due to Po=
or battery backup // Gen started manually","edwige.kapawo@matech-cameroun.c=
om","256","18-07-2025 16:56:22","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005507378","Eto=
udi","","18-07-2025 16:29:13","18-07-2025 16:28:06","18-07-2025 17:06:46","=
Grid outage, site went down before Gen start due to poor battery backup // =
Grid returned","Fabrice Pouakam","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, site went down before Gen st=
art due to poor battery backup // Grid returned","gerard.tchangoue@matech-c=
ameroun.com","68","18-07-2025 16:29:13","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005507184","Mey=
o","","18-07-2025 16:07:49","18-07-2025 16:07:44","18-07-2025 16:09:49","AC=
TIVE //No power issue Ubaie: 54,8V Site on Grid The Tx Fme Georges (6974661=
814 / huawei) is on site for work","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE //No=
 power issue Ubaie: 54,8V Site on Grid The Tx Fme Georges (6974661814 / hua=
wei) is on site for work","edwige.kapawo@matech-cameroun.com","6","18-07-20=
25 16:07:49","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005507165","Eto=
udi","","18-07-2025 16:06:43","18-07-2025 16:01:36","18-07-2025 16:09:47","=
Grid outage, site went down before Gen start due to poor battery backup // =
Grid returned","Fabrice Pouakam","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, site went down before Gen st=
art due to poor battery backup // Grid returned","gerard.tchangoue@matech-c=
ameroun.com","308","18-07-2025 16:06:43","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005506995","Eto=
udi","","18-07-2025 15:34:11","18-07-2025 15:32:03","18-07-2025 15:43:30","=
Grid outage, site went down before Gen start due to poor battery backup // =
Grid returned","Fabrice Pouakam","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, site went down before Gen st=
art due to poor battery backup // Grid returned","gerard.tchangoue@matech-c=
ameroun.com","129","18-07-2025 15:34:11","MATECH CMR"
"Closed Complete","Site Down","T1071","IHS_YND_343","NOCINC0005505667","Mbe=
doumou - Ekali","IHS_YND_723, IHS_YND_385, IHS_YND_553, IHS_YND_410, IHS_YN=
D_595, IHS_EBO_015, IHS_YND_344, IHS_YND_411","18-07-2025 13:07:21","18-07-=
2025 12:59:13","18-07-2025 13:29:13","Grid Outage, site went down because G=
en start and stopped with ""high temp"" alarm  // He oppened the doors and =
manually start the gen ","Albran Byorel","Equipment Repair","Passive","ACDG=
 Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid Outage, site we=
nt down because Gen start and stopped with ""high temp"" alarm  // He oppen=
ed the doors and manually start the gen ","ludivine.ngamaleu@ihstowers.com"=
,"488","18-07-2025 13:07:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0005505475","Ekekam",=
"","18-07-2025 12:39:35","18-07-2025 12:30:31","18-07-2025 14:35:42","Casca=
ded Incident from TTO5688379","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to hybrid =
syst=E8m dysfunctionning //he reset it and started the gen","system","36561=
7","18-07-2025 12:39:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0005505474","Lobo 2",=
"","18-07-2025 12:39:35","18-07-2025 12:30:31","18-07-2025 14:35:42","Casca=
ded Incident from TTO5688379","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to hybrid =
syst=E8m dysfunctionning //he reset it and started the gen","system","36561=
8","18-07-2025 12:39:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0005505476","NKONGKAR=
AK","","18-07-2025 12:39:35","18-07-2025 12:30:31","18-07-2025 14:35:42","C=
ascaded Incident from TTO5688379","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down due to hyb=
rid syst=E8m dysfunctionning //he reset it and started the gen","system","3=
65617","18-07-2025 12:39:35","MATECH CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0005505468","LOB=
O MTN","IHS_YND_783, IHS_YND_714, IHS_YND_713","18-07-2025 12:38:52","18-07=
-2025 12:30:31","18-07-2025 14:35:42","Site went down due to hybrid syst=E8=
m dysfunctionning //he reset it and started the gen","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","Hybrid","Hybrid Module","Site went down =
due to hybrid syst=E8m dysfunctionning //he reset it and started the gen","=
ludivine.ngamaleu@ihstowers.com","502","18-07-2025 12:38:52","MATECH CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0005505176","Ele=
veurs","","18-07-2025 12:14:31","18-07-2025 12:06:08","18-07-2025 12:22:08"=
,"Grid Outage, Site Down before gen Started due to poor backup //Grid retur=
ned","Siligap Boris","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Battery Low","Grid Outage, Site Down before gen Started due to poor=
 backup //Grid returned","franck.nkomot@matech-cameroun.com","504","18-07-2=
025 12:14:31","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005504707","B=
arriere IHS","","18-07-2025 10:53:23","18-07-2025 10:50:42","18-07-2025 14:=
06:24","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed//Grid return","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to =
Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed//Grid return","fra=
nck.nkomot@matech-cameroun.com","163","18-07-2025 10:53:23","MATECH CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0005504633","N=
ew-Marche-Melen","","18-07-2025 10:39:06","18-07-2025 08:36:59","18-07-2025=
 21:31:36","","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Cascade outage","franck.nkomot@matech-cameroun.com","30759=
6","18-07-2025 10:39:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005504193","Nkolfon =
Cimencam","","18-07-2025 09:17:02","18-07-2025 09:03:37","18-07-2025 14:00:=
57","Cascaded Incident from TTO5686921","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirm=
ed // Grid return","system","291642","18-07-2025 09:17:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005504192","Ahala","=
","18-07-2025 09:17:01","18-07-2025 09:03:37","18-07-2025 14:00:57","Cascad=
ed Incident from TTO5686921","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Gen o=
verload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid =
return","system","291642","18-07-2025 09:17:01","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005504147","Mey=
o","IHS_YND_257, IHS_YND_762","18-07-2025 09:09:51","18-07-2025 09:03:37","=
18-07-2025 14:00:57","Grid outage, site went down due to Gen overload (17KV=
A, 260A) SS HIS Felix Zambe is informed and confirmed // Grid return","Hyem=
afo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix Zamb=
e is informed and confirmed // Grid return","ludivine.ngamaleu@ihstowers.co=
m","375","18-07-2025 09:09:51","MATECH CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0005504051","An-=
Marche-Melen","IHS_YND_141","18-07-2025 08:46:54","18-07-2025 08:36:59","18=
-07-2025 21:31:36","Grid outage,no space to deploy mobile gen //Grid return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage,no space to deploy mobile gen //Grid return","franck.nkomot@matec=
h-cameroun.com","899","18-07-2025 08:46:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005504026","Mfou EPC=
","","18-07-2025 08:42:30","18-07-2025 08:39:38","18-07-2025 08:55:38","Cas=
caded Incident from TTO5686746","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","1213628","18-07-2025 0=
8:42:30","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005504023","M=
fou OCM","IHS_YND_674","18-07-2025 08:41:47","18-07-2025 08:39:38","18-07-2=
025 08:55:38","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","olivier.kwedi@ihstowers.com","130=
","18-07-2025 08:41:47","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005503835","Evo=
doula MTN","","18-07-2025 07:54:52","18-07-2025 07:52:43","18-07-2025 08:49=
:43","Grid outage, Site went down because gen failed to start due to alarm =
""undervoltage"" //We reset card GE and gen manually started","TIENTCHEU NZ=
ETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Under Voltage=
","Grid outage, Site went down because gen failed to start due to alarm ""u=
ndervoltage"" //We reset card GE and gen manually started","franck.nkomot@m=
atech-cameroun.com","130","18-07-2025 07:54:52","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0005503720","Mam=
bine","","18-07-2025 07:35:59","18-07-2025 07:28:46","18-07-2025 08:08:46",=
"Grid issue, fuse disconnect, Gen turn until fuel shortage // Tank tilt and=
 site on Gen (Refueling on going)","Fanda Brice","Fuel Outage","Passive","D=
iesel","Diesel Outage","Grid issue, fuse disconnect, Gen turn until fuel sh=
ortage // Tank tilt and site on Gen (Refueling on going)","ludivine.ngamale=
u@ihstowers.com","434","18-07-2025 07:35:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0005503202","BATA Mok=
olo OCM","","18-07-2025 04:23:30","18-07-2025 04:06:04","18-07-2025 04:10:2=
3","Cascaded Incident from TTO5685824","","Cascade Outage","Active","Cascad=
e Active","Cascade Active","Active//No power issue on site U=3D53.4v site o=
n Grid. TX FME Brice Tsague (650214096) of Huawei is informed.","system","2=
66333","18-07-2025 04:23:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0005503200","Tsinga",=
"","18-07-2025 04:22:11","18-07-2025 04:06:04","18-07-2025 04:10:23","Casca=
ded Incident from TTO5685824","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active//No power issue on site U=3D53.4v si=
te on Grid. TX FME Brice Tsague (650214096) of Huawei is informed.","system=
","266330","18-07-2025 04:22:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005503199","Bastos B=
ethesda","","18-07-2025 04:22:11","18-07-2025 04:06:04","18-07-2025 04:10:2=
3","Cascaded Incident from TTO5685824","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue on site U=
=3D53.4v site on Grid. TX FME Brice Tsague (650214096) of Huawei is informe=
d.","system","266329","18-07-2025 04:22:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005503198","Bastos-N=
ylon","","18-07-2025 04:22:10","18-07-2025 04:06:04","18-07-2025 04:10:23",=
"Cascaded Incident from TTO5685824","Mboua Thierry","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue on site U=3D53=
.4v site on Grid. TX FME Brice Tsague (650214096) of Huawei is informed.","=
system","266332","18-07-2025 04:22:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005503197","Golf Qua=
ter","","18-07-2025 04:22:10","18-07-2025 04:06:04","18-07-2025 04:10:23","=
Cascaded Incident from TTO5685824","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue on site U=3D53.=
4v site on Grid. TX FME Brice Tsague (650214096) of Huawei is informed.","s=
ystem","266332","18-07-2025 04:22:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0005503196","Entree C=
ite Verte","","18-07-2025 04:19:40","18-07-2025 04:06:04","18-07-2025 04:10=
:23","Cascaded Incident from TTO5685824","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue on site U=
=3D53.4v site on Grid. TX FME Brice Tsague (650214096) of Huawei is informe=
d.","system","266331","18-07-2025 04:19:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0005503195","Nkomkana=
 2","","18-07-2025 04:19:40","18-07-2025 04:06:04","18-07-2025 04:10:23","C=
ascaded Incident from TTO5685824","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue on site U=3D53.4=
v site on Grid. TX FME Brice Tsague (650214096) of Huawei is informed.","sy=
stem","266330","18-07-2025 04:19:40","MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0005503193","C=
ite-Verte","IHS_YND_220, IHS_YND_138, IHS_YND_200, IHS_YND_126, IHS_YND_559=
, IHS_YND_563, IHS_YND_127, IHS_YND_543","18-07-2025 04:16:14","18-07-2025 =
04:06:04","18-07-2025 04:10:23","Active//No power issue on site U=3D53.4v s=
ite on Grid. TX FME Brice Tsague (650214096) of Huawei is informed.","","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site U=3D53.4v site on Grid. TX FME Bric=
e Tsague (650214096) of Huawei is informed.","loic.noumsi@matech-cameroun.c=
om","611","18-07-2025 04:16:14","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0005503187","N=
komkana","","18-07-2025 04:09:15","18-07-2025 04:06:04","18-07-2025 04:10:2=
3","CASCADED SITE","","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","CASCADED SITE","loic.noumsi@matech-cameroun.com","266328","18-07-20=
25 04:09:15","MATECH CMR"
"Closed Complete","Site Down","CTR_122","IHS_YND_230","NOCINC0005503018","M=
eyong-Meyeme","","18-07-2025 03:15:09","18-07-2025 03:10:02","18-07-2025 03=
:13:31","No power issue site on Grid with U=3D53.9V.Tx FME Mohamadou (65879=
1013) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue site on Grid with U=3D53.9V.Tx FME Mohamadou (658791013) from Hu=
awei is informed.","loic.noumsi@matech-cameroun.com","308","18-07-2025 03:1=
5:09","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005502935","T=
singa","","18-07-2025 02:33:41","18-07-2025 02:30:31","18-07-2025 02:35:58"=
,"Active// No power issue on site Ubaie=3D51.8V site on Grid The Tx Brice T=
sgaue //650214096 of Huawei is informed","Mboua Thierry","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue on site Ubaie=3D51.8V site on Grid The Tx Brice Tsgaue //=
650214096 of Huawei is informed","loic.noumsi@matech-cameroun.com","192","1=
8-07-2025 02:33:41","MATECH CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0005502800","O=
yomabang OCM","","18-07-2025 01:24:00","18-07-2025 01:18:54","18-07-2025 01=
:25:29","No power issue on site U=3D54V site on Grid, TX FME Mohamadou (691=
144435) of Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site U=3D54V site on Grid, TX FME Mohamadou (691144435) of Hu=
awei is informed.","loic.noumsi@matech-cameroun.com","307","18-07-2025 01:2=
4:00","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005502466","N=
kolbong","","18-07-2025 00:17:19","18-07-2025 00:12:13","18-07-2025 00:32:1=
3","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A)// Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A)// Grid return","loic.noumsi@mat=
ech-cameroun.com","308","18-07-2025 00:17:19","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005502173","N=
kolbong","","17-07-2025 22:40:04","17-07-2025 22:38:33","17-07-2025 23:00:5=
4","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A)// Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A)// Grid return","vanel.mbiada@ma=
tech-cameroun.com","92","17-07-2025 22:40:04","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005501923","N=
kolbong","","17-07-2025 21:45:52","17-07-2025 21:43:43","17-07-2025 22:05:1=
8","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A)// Grid return","Delor Telezing","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started a=
nd stopped due to Gen overload(22kva//350A)// Grid return","vanel.mbiada@ma=
tech-cameroun.com","130","17-07-2025 21:45:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005501058","Mfou EPC=
","","17-07-2025 18:54:19","17-07-2025 18:51:21","17-07-2025 21:01:48","Cas=
caded Incident from TTO5683436","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","270797","17-07-2025 18=
:54:19","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005501051","M=
fou OCM","IHS_YND_674","17-07-2025 18:53:29","17-07-2025 18:51:21","17-07-2=
025 21:01:48","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","vanel.mbiada@matech-cameroun.com"=
,"129","17-07-2025 18:53:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005500769","MEHANDAN=
","","17-07-2025 18:09:09","17-07-2025 18:06:59","17-07-2025 18:10:44","Cas=
caded Incident from TTO5683122","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction// Site stabilised","system","2=
66315","17-07-2025 18:09:09","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005500762","O=
dza II OCM","IHS_YND_528","17-07-2025 18:08:25","17-07-2025 18:06:59","17-0=
7-2025 18:10:44","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction// Site stabilised","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down because gen failed to start due to PWC ZTE malfunction// Site st=
abilised","vanel.mbiada@matech-cameroun.com","90","17-07-2025 18:08:25","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005500753","E=
seka OCM","","17-07-2025 18:06:35","17-07-2025 18:03:20","17-07-2025 18:15:=
34","No power issue U=3D55.4V site on Grid The Tx FME Etienne FOPA /6950339=
81/ From HUAWEI is informed","Kemeni Franklin","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=
=3D55.4V site on Grid The Tx FME Etienne FOPA /695033981/ From HUAWEI is in=
formed","vanel.mbiada@matech-cameroun.com","196","17-07-2025 18:06:35","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_141","NOCINC0005500696","New-Marc=
he-Melen","","17-07-2025 17:57:59","17-07-2025 13:58:37","18-07-2025 08:11:=
37","Cascaded Incident from TTO5681959","Paul BIBOUM","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,no space to deploy m=
obile gen //Grid return","system","331593","17-07-2025 17:57:59","MATECH CM=
R"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0005500511","Tsi=
nga","","17-07-2025 17:27:14","17-07-2025 17:21:07","17-07-2025 17:31:49","=
Site went down due to PWC Dysfunction//He bypassed it and site on Grid","Mb=
oua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module Ove=
rloaded","Site went down due to PWC Dysfunction//He bypassed it and site on=
 Grid","cedric.tiani@matech-cameroun.com","369","17-07-2025 17:27:14","MATE=
CH CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0005500471","Ngu=
ila","","17-07-2025 17:22:15","17-07-2025 17:20:59","17-07-2025 17:23:42","=
Active // No Power issue, site on battery Ubay =3D 49V Hybrid Site, Tx Fme =
Gregoire (654547479) from Huawei is informed and confirmed","Parker Tchoup"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active // No Power issue, site on battery Ubay =3D 49V Hybrid =
Site, Tx Fme Gregoire (654547479) from Huawei is informed and confirmed","c=
edric.tiani@matech-cameroun.com","77","17-07-2025 17:22:15","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005499905","T=
singa","","17-07-2025 15:41:49","17-07-2025 15:40:39","17-07-2025 17:20:44"=
,"Site went down due to PWC Dysfunction//He bypassed it and site on Grid","=
Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Site went down due to PWC Dysfunction//He bypassed it and site =
on Grid","vanel.mbiada@matech-cameroun.com","72","17-07-2025 15:41:49","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005499617","T=
singa","","17-07-2025 15:00:50","17-07-2025 14:59:23","17-07-2025 15:23:24"=
,"Grid outage, Site went down before Gen start due to poor backup // Grid s=
tabilised","Mboua Thierry","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid stabilised","vanel.mbiada@matech-cameroun.com","89=
","17-07-2025 15:00:50","MATECH CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0005499543","Kon=
dengui MTN","","17-07-2025 14:39:33","17-07-2025 14:31:24","17-07-2025 14:4=
9:31","Grid outage, Site went because Gen ran until fuel shortage//Refuelin=
g Done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage, Site went because Gen ran until fuel shortage//Refueling Done",=
"cedric.tiani@matech-cameroun.com","490","17-07-2025 14:39:33","MATECH CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0005499338","An-=
Marche-Melen","IHS_YND_141","17-07-2025 14:07:53","17-07-2025 13:58:37","18=
-07-2025 08:11:37","Grid outage,no space to deploy mobile gen //Grid return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage,no space to deploy mobile gen //Grid return","gerard.tchangoue@ma=
tech-cameroun.com","557","17-07-2025 14:07:53","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005498964","C=
rf Cornier","","17-07-2025 13:07:15","17-07-2025 13:05:56","17-07-2025 13:0=
9:49","ACTIVE //No power issue Ubaie: 54.6V site on Grid Armand NGUETSA // =
699949553// from huawei is informed,","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE //=
No power issue Ubaie: 54.6V site on Grid Armand NGUETSA // 699949553// from=
 huawei is informed,","edwige.kapawo@matech-cameroun.com","80","17-07-2025 =
13:07:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005498957","MEHANDAN=
","","17-07-2025 13:05:00","17-07-2025 13:00:38","17-07-2025 13:07:47","Cas=
caded Incident from TTO5681148","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction// Site stabilised","system","2=
63111","17-07-2025 13:05:00","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005498955","O=
dza II OCM","IHS_YND_528","17-07-2025 13:03:56","17-07-2025 13:00:38","17-0=
7-2025 13:07:47","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction// Site stabilised","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down because gen failed to start due to PWC ZTE malfunction// Site st=
abilised","edwige.kapawo@matech-cameroun.com","201","17-07-2025 13:03:56","=
MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005498737","Eto=
ug ebe biscuiterie","","17-07-2025 12:24:02","17-07-2025 12:20:56","17-07-2=
025 13:08:02","Grid fluctuations, site went down due to Grid bad voltage  o=
n site // He bypassed Grid and started Gen manually","Hyemafo Gildas","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid f=
luctuations, site went down due to Grid bad voltage  on site // He bypassed=
 Grid and started Gen manually","edwige.kapawo@matech-cameroun.com","187","=
17-07-2025 12:24:02","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005498602","Eto=
ug ebe Meweulo","","17-07-2025 11:58:42","17-07-2025 11:56:33","17-07-2025 =
12:38:33"," Grid outage site went down because Gen failed to start due PWC =
ZTE dysfonction // He bypassed it and started the Gen manually","Hyemafo Gi=
ldas","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
"," Grid outage site went down because Gen failed to start due PWC ZTE dysf=
onction // He bypassed it and started the Gen manually","gerard.tchangoue@m=
atech-cameroun.com","130","17-07-2025 11:58:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005498558","Acropole=
","","17-07-2025 11:54:10","17-07-2025 11:47:59","17-07-2025 11:50:24","Cas=
caded Incident from TTO5680658","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Site impacted by Mvog-Ada-New_ctr_347 not=
 managed by IHS","system","260370","17-07-2025 11:54:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005498559","C-Suprem=
e","","17-07-2025 11:54:10","17-07-2025 11:47:59","17-07-2025 11:50:24","Ca=
scaded Incident from TTO5680658","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","Site impacted by Mvog-Ada-New_ctr_347 not managed by =
IHS","system","260373","17-07-2025 11:54:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005498557","Olezoa O=
CM","","17-07-2025 11:54:10","17-07-2025 11:47:59","17-07-2025 11:50:24","C=
ascaded Incident from TTO5680658","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Site impacted by Mvog-Ada-New_ctr_347 not managed by=
 IHS","system","260368","17-07-2025 11:54:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_564","NOCINC0005498555","Mvog Mbi=
 New","","17-07-2025 11:54:09","17-07-2025 11:47:59","17-07-2025 11:50:24",=
"Cascaded Incident from TTO5680658","MINKA NICOLAS","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Site impacted by Mvog-Ada-New_ctr_347=
 not managed by IHS","system","260369","17-07-2025 11:54:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0005498556","MONTEE N=
KONDENGUI","","17-07-2025 11:54:09","17-07-2025 11:47:59","17-07-2025 11:50=
:24","Cascaded Incident from TTO5680658","Albran Byorel","Cascade Outage","=
Active","Cascade Active","Cascade Active","Site impacted by Mvog-Ada-New_ct=
r_347 not managed by IHS","system","260371","17-07-2025 11:54:09","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_023","NOCINC0005498538","Montesqu=
ieux","","17-07-2025 11:52:20","17-07-2025 11:47:59","17-07-2025 11:50:24",=
"Cascaded Incident from TTO5680658","Paul BIBOUM","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Site impacted by Mvog-Ada-New_ctr_347 n=
ot managed by IHS","system","260373","17-07-2025 11:52:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_063","NOCINC0005498536","Av-Germa=
ine","","17-07-2025 11:52:20","17-07-2025 11:47:59","17-07-2025 11:50:24","=
Cascaded Incident from TTO5680658","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","Site impacted by Mvog-Ada-New_ctr_347 not managed b=
y IHS","system","260372","17-07-2025 11:52:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0005498539","Nkoa Ayo=
s","","17-07-2025 11:52:20","17-07-2025 11:47:59","17-07-2025 11:50:24","Ca=
scaded Incident from TTO5680658","MINKA NICOLAS","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Site impacted by Mvog-Ada-New_ctr_347 no=
t managed by IHS","system","260370","17-07-2025 11:52:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_066","NOCINC0005498537","GSO","",=
"17-07-2025 11:52:20","17-07-2025 11:47:59","17-07-2025 11:50:24","Cascaded=
 Incident from TTO5680658","MINKA NICOLAS","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by Mvog-Ada-New_ctr_347 not mana=
ged by IHS","system","260371","17-07-2025 11:52:20","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005498516","M=
vog-Ada_OCM","IHS_YND_564, IHS_YND_063, IHS_YND_682, IHS_YND_055, IHS_YND_0=
36, IHS_YND_066, IHS_YND_023, IHS_YND_067, IHS_YND_021","17-07-2025 11:50:0=
5","17-07-2025 11:47:59","17-07-2025 11:50:24","Site impacted by Mvog-Ada-N=
ew_ctr_347 not managed by IHS","","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","Affected by 3rd Party Site","Site impacted by Mvog=
-Ada-New_ctr_347 not managed by IHS","edwige.kapawo@matech-cameroun.com","1=
28","17-07-2025 11:50:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005498463","MEHANDAN=
","","17-07-2025 11:41:39","17-07-2025 11:29:58","17-07-2025 11:53:35","Cas=
caded Incident from TTO5680546","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to Pwc ZTE dysfunction// he reset it and started Gen =
manualy","system","261443","17-07-2025 11:41:39","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005498423","O=
dza II OCM","IHS_YND_528","17-07-2025 11:32:10","17-07-2025 11:29:58","17-0=
7-2025 11:53:36","Grid outage, site went down because gen failed to start d=
ue to Pwc ZTE dysfunction// he reset it and started Gen manualy","Albran By=
orel","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, site went down because gen failed to start due to Pwc ZTE d=
ysfunction// he reset it and started Gen manualy","edwige.kapawo@matech-cam=
eroun.com","135","17-07-2025 11:32:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005498072","Akak-Nko=
zoa-MTN-IHS","","17-07-2025 10:25:00","17-07-2025 10:09:58","17-07-2025 10:=
15:06","Cascaded Incident from TTO5680072","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
: 53,9V site on Grid. Symphorien (675295205/Huawei) is informed.","system",=
"266189","17-07-2025 10:25:00","MATECH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0005497923","Lob=
o 2","","17-07-2025 09:57:06","17-07-2025 09:55:59","17-07-2025 22:42:58","=
Site went down due to PM (Swap of Gen) done by our FME with our team // End=
 of work","TIENTCHEU NZETCHIEU GAEL","Installation Activity","Passive","Pla=
nned Activity","Installation Activity","Site went down due to PM (Swap of G=
en) done by our FME with our team // End of work","gerard.tchangoue@matech-=
cameroun.com","68","17-07-2025 09:57:06","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005497916","B=
arriere","","17-07-2025 09:55:50","17-07-2025 09:54:37","17-07-2025 10:33:4=
1","Active // No power issue on site Ubay: 52.6V site on Gen .TX Fme Fluber=
t (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue on site Ubay: 52.6V site on Gen .TX Fme Flubert (654266068/Hua=
wei) is informed","edwige.kapawo@matech-cameroun.com","75","17-07-2025 09:5=
5:50","MATECH CMR"
"Closed Complete","Site Down","T1652","IHS_YND_273","NOCINC0005497559","Nko=
lbi-Boss","","17-07-2025 08:53:44","17-07-2025 08:52:35","17-07-2025 09:49:=
22","Site went down because gen fails to start due to grid bad voltage // H=
e bypass grid and manually start the gen","TIENTCHEU NZETCHIEU GAEL","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site we=
nt down because gen fails to start due to grid bad voltage // He bypass gri=
d and manually start the gen","gerard.tchangoue@matech-cameroun.com","70","=
17-07-2025 08:53:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005497556","Messassi=
 okolo","","17-07-2025 08:52:44","17-07-2025 08:50:59","17-07-2025 09:26:26=
","Cascaded Incident from TTO5679593","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issues due to landlord(=
Landlord has forbidden to start the Gen due to noise)//Grid return","system=
","263684","17-07-2025 08:52:44","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005497554","E=
MANA BILICK CITY","IHS_YND_279","17-07-2025 08:51:30","17-07-2025 08:50:59"=
,"17-07-2025 09:30:39","Access issues due to landlord(Landlord has forbidde=
n to start the Gen due to noise)//Grid return","Fabrice Pouakam","Access De=
nial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord"=
,"Access issues due to landlord(Landlord has forbidden to start the Gen due=
 to noise)//Grid return","edwige.kapawo@matech-cameroun.com","32","17-07-20=
25 08:51:30","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005497543","N=
kolbong","","17-07-2025 08:50:16","17-07-2025 08:48:10","17-07-2025 09:26:4=
8","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started =
and stopped due to Gen overload(22kva//350A) // Grid return","edwige.kapawo=
@matech-cameroun.com","127","17-07-2025 08:50:16","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005497426","Nko=
lbisson IITA LP","","17-07-2025 08:27:47","17-07-2025 08:20:34","17-07-2025=
 08:33:28","Site impacted by Nkolbisson 2 ocm not manage by IHS","","Custom=
er Equipment Failure","Active","Active Equipment Failure","Affected by 3rd =
Party Site","Site impacted by Nkolbisson 2 ocm not manage by IHS","edwige.k=
apawo@matech-cameroun.com","435","17-07-2025 08:27:47","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005497333","Nko=
lnda","","17-07-2025 08:06:47","17-07-2025 08:00:36","17-07-2025 08:50:20",=
"Grid outage, Site went down because Gen failed to start due to battery Gen=
 faulty// He started Gen with external battery","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, Site =
went down because Gen failed to start due to battery Gen faulty// He starte=
d Gen with external battery","edwige.kapawo@matech-cameroun.com","373","17-=
07-2025 08:06:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005497273","MEHANDAN=
","","17-07-2025 07:51:30","17-07-2025 07:44:29","17-07-2025 09:13:23","Cas=
caded Incident from TTO5679276","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to Pwc ZTE dysfunction// he reset it and started Gen =
manualy","system","1216969","17-07-2025 07:51:30","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005497269","O=
dza II OCM","IHS_YND_528","17-07-2025 07:50:37","17-07-2025 07:44:29","17-0=
7-2025 09:13:55","Grid outage, site went down because gen failed to start d=
ue to Pwc ZTE dysfunction// he reset it and started Gen manualy","Albran By=
orel","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, site went down because gen failed to start due to Pwc ZTE d=
ysfunction// he reset it and started Gen manualy","edwige.kapawo@matech-cam=
eroun.com","371","17-07-2025 07:50:37","MATECH CMR"
"Closed Complete","Site Down","T1652","IHS_YND_273","NOCINC0005497225","Nko=
lbi-Boss","","17-07-2025 07:40:00","17-07-2025 07:37:54","17-07-2025 07:46:=
30","Site went down because gen fails to start due to grid bad voltage // H=
e bypass grid and manually start the gen","TIENTCHEU NZETCHIEU GAEL","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site we=
nt down because gen fails to start due to grid bad voltage // He bypass gri=
d and manually start the gen","gerard.tchangoue@matech-cameroun.com","127",=
"17-07-2025 07:40:00","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005497210","Evo=
doula MTN","","17-07-2025 07:37:46","17-07-2025 07:31:18","17-07-2025 07:37=
:15","Grid outage, Site went down before Gen start due to poor backup // Ge=
n Automaticaly started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup // Gen Automaticaly started","gera=
rd.tchangoue@matech-cameroun.com","389","17-07-2025 07:37:46","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005497086","N=
kolbi-Boss","","17-07-2025 07:02:07","17-07-2025 07:00:00","17-07-2025 07:0=
4:21","Site went down because gen fails to start due to grid bad voltage //=
 He bypass grid and manually start the gen","TIENTCHEU NZETCHIEU GAEL","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site =
went down because gen fails to start due to grid bad voltage // He bypass g=
rid and manually start the gen","edwige.kapawo@matech-cameroun.com","129","=
17-07-2025 07:02:07","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005497070","S=
IMBOCK BONAMBAPE","","17-07-2025 06:57:02","17-07-2025 06:55:56","17-07-202=
5 07:07:32","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","edwige.kapawo@matech-cameroun.com=
","67","17-07-2025 06:57:02","MATECH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0005497051","Lob=
o 2","","17-07-2025 06:52:17","17-07-2025 06:46:59","17-07-2025 07:24:53","=
Grid outage.gen start and stopped due to alarm""high temp""//We added water=
 and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","P=
assive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid ou=
tage.gen start and stopped due to alarm""high temp""//We added water and ge=
n manually started","edwige.kapawo@matech-cameroun.com","318","17-07-2025 0=
6:52:17","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005497018","Oko=
la","","17-07-2025 06:43:08","17-07-2025 06:42:03","17-07-2025 07:22:58","G=
rid outage, Site went down due to Gen faulty // Grid return","TIENTCHEU NZE=
TCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faul=
ty","Grid outage, Gen failed to start due to battery Gen faulty, // Grid re=
turn","loic.noumsi@matech-cameroun.com","66","17-07-2025 06:43:08","MATECH =
CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005496509","M=
essassi 2","","17-07-2025 03:05:53","17-07-2025 03:01:42","17-07-2025 11:47=
:39","Site went down due to site vandalised( radio  cables  cut  )//He reco=
nnected the cables","Fabrice Pouakam","Site Asset Theft","Theft","Theft","C=
ustomer Equipment","Site went down due to site vandalised( radio  cables  c=
ut  )//He reconnected the cables","gaelle.njiofack@matech-cameroun.com","25=
3","17-07-2025 03:05:53","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005496461","M=
essassi 2","","17-07-2025 02:38:07","17-07-2025 02:34:00","17-07-2025 02:51=
:12","Site went down due to site vandalised( radio  cables  cut  )//He reco=
nnected the cables","Fabrice Pouakam","Site Asset Theft","Theft","Theft","C=
ustomer Equipment","Site went down due to site vandalised( radio  cables  c=
ut  )//He reconnected the cables","gaelle.njiofack@matech-cameroun.com","25=
0","17-07-2025 02:38:07","MATECH CMR"
"Closed Complete","Site Down","CTR_553","IHS_YND_686","NOCINC0005496403","O=
yomabang Ecole","","17-07-2025 02:16:42","17-07-2025 02:09:35","17-07-2025 =
02:49:20","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mo=
uhamadou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","	Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mou=
hamadou (6144435) from Huawei is informed.","gaelle.njiofack@matech-camerou=
n.com","428","17-07-2025 02:16:42","MATECH CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0005496400","A=
FEME NORD","","17-07-2025 02:14:04","17-07-2025 02:09:57","17-07-2025 02:31=
:17","Active; no power issue site on Grid with U=3D54,1 V;The fme TX Mohamm=
adou 691144435 of huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active; no power issue site on Grid with U=3D54,1 V;The fme TX Mohammadou=
 691144435 of huawei is informed","gaelle.njiofack@matech-cameroun.com","24=
8","17-07-2025 02:14:04","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0005496397","C=
rf-Nkolbisson","","17-07-2025 02:10:33","17-07-2025 02:07:24","17-07-2025 0=
2:10:17","Active// No power issue, site is on grid with Ubaie=3D55,4 V, Moh=
amadou(691144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue, site is on grid with Ubaie=3D55,4 V, Mohama=
dou(691144435) from Huawei is informed","gaelle.njiofack@matech-cameroun.co=
m","190","17-07-2025 02:10:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005495984","MBIMBIM"=
,"","16-07-2025 23:51:21","16-07-2025 23:36:08","16-07-2025 23:42:16","","P=
arker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active","=
cascaded site","system","275271","16-07-2025 23:51:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005495986","Yoko MTN=
","","16-07-2025 23:51:21","16-07-2025 23:36:08","16-07-2025 23:42:16","","=
Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active",=
"cascaded site","system","275269","16-07-2025 23:51:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005495985","Ngoum","=
","16-07-2025 23:51:21","16-07-2025 23:36:08","16-07-2025 23:42:16","","Par=
ker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active","CA=
SCADED SITE","system","275270","16-07-2025 23:51:21","MATECH CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0005495980","Ngo=
uetou","","16-07-2025 23:49:59","16-07-2025 23:39:43","17-07-2025 04:39:07"=
,"Site went down because Gen failed to start  due to the power pin that was=
 poorly connected at the GE board//He reconnected it","Parker Tchoup","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Site went down b=
ecause Gen failed to start  due to the power pin that was poorly connected =
at the GE board//He reconnected it","loic.noumsi@matech-cameroun.com","617"=
,"16-07-2025 23:49:59","MATECH CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0005495964","Mat=
sari","IHS_YND_456, IHS_YND_475, IHS_YND_473","16-07-2025 23:41:18","16-07-=
2025 23:36:08","16-07-2025 23:42:16","Active // No power issue on site with=
 Ubaie=3D51.2V site on Gen ,The Tx Fme Gregoire( 652070658)from Huawei is i=
nformed","Parker Tchoup","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active // No power issue on site with =
Ubaie=3D51.2V site on Gen ,The Tx Fme Gregoire( 652070658)from Huawei is in=
formed","loic.noumsi@matech-cameroun.com","311","16-07-2025 23:41:18","MATE=
CH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005495805","NYO=
M FACE MAETUR","","16-07-2025 23:03:13","16-07-2025 23:02:07","16-07-2025 2=
3:11:21","ACCESS ISSUE Grid fluctuations , site went down because Gen faile=
d to start due to Grid bad voltage // Grid stabilisation note that :(the la=
ndlord refuses that we deploy the MG)","Fabrice Pouakam","Access Denial","L=
ease Or Legal","Landlord Related Issues","Access Issue - Land Lord","ACCESS=
 ISSUE Grid fluctuations , site went down because Gen failed to start due t=
o Grid bad voltage // Grid stabilisation note that :(the landlord refuses t=
hat we deploy the MG)","loic.noumsi@matech-cameroun.com","68","16-07-2025 2=
3:03:13","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005495790","B=
arriere","","16-07-2025 22:56:14","16-07-2025 22:54:09","17-07-2025 00:08:2=
0","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed","Hyemafo Gildas","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Grid outage, Site went down because Gen overload (30=
kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised","loic.noumsi@mate=
ch-cameroun.com","127","16-07-2025 22:56:14","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005495549","N=
kolbong","","16-07-2025 22:01:55","16-07-2025 21:57:45","16-07-2025 23:11:3=
2","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A//Grid return","Delor Telezing","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started and=
 stopped due to Gen overload(22kva//350A//Grid return","vanel.mbiada@matech=
-cameroun.com","252","16-07-2025 22:01:55","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005495508","N=
simalen OCM","","16-07-2025 21:54:32","16-07-2025 21:53:11","16-07-2025 21:=
55:18","Site went down because 01/03 rectifiers went faulty// Grid stabiliz=
ed","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down because 01/03 rectifiers went faulty// Grid stabilized=
","vanel.mbiada@matech-cameroun.com","82","16-07-2025 21:54:32","MATECH CMR=
"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005495486","NYO=
M FACE MAETUR","","16-07-2025 21:49:00","16-07-2025 21:47:40","16-07-2025 2=
1:48:50","Grid fluctuation, Site went down before Gen start due to poor bac=
kup //Grid return","Fabrice Pouakam","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid fluctuation, Site went down befo=
re Gen start due to poor backup //Grid return","cedric.tiani@matech-camerou=
n.com","82","16-07-2025 21:49:00","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005495186","N=
simalen OCM","","16-07-2025 20:54:33","16-07-2025 20:53:22","16-07-2025 20:=
58:23","Site went down because 01/03 rectifiers went faulty// Grid stabiliz=
ed","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down because 01/03 rectifiers went faulty// Grid stabilized=
","vanel.mbiada@matech-cameroun.com","72","16-07-2025 20:54:33","MATECH CMR=
"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005495176","N=
kolbong","","16-07-2025 20:53:06","16-07-2025 20:49:57","16-07-2025 21:24:0=
7","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A//Grid return","Delor Telezing","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started and=
 stopped due to Gen overload(22kva//350A//Grid return","vanel.mbiada@matech=
-cameroun.com","191","16-07-2025 20:53:06","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005494990","TON=
GOLO SNEC","","16-07-2025 20:17:30","16-07-2025 20:15:20","16-07-2025 20:25=
:56","Site went down due to insufficient rectifiers//Site stabilised","Fabr=
ice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","S=
ite went down due to insufficient rectifiers//Site stabilised","cedric.tian=
i@matech-cameroun.com","131","16-07-2025 20:17:30","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005494945","N=
simalen OCM","","16-07-2025 20:09:24","16-07-2025 20:08:16","16-07-2025 20:=
15:01","Site went down because 01/03 rectifiers went faulty// Grid stabiliz=
ed","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down because 01/03 rectifiers went faulty// Grid stabilized=
","vanel.mbiada@matech-cameroun.com","70","16-07-2025 20:09:24","MATECH CMR=
"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005494879","N=
kolbong","","16-07-2025 19:58:09","16-07-2025 19:56:10","16-07-2025 20:19:0=
4","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started an=
d stopped due to Gen overload(22kva//350A)//Grid return","vanel.mbiada@mate=
ch-cameroun.com","121","16-07-2025 19:58:09","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005494446","B=
arriere","","16-07-2025 18:25:18","16-07-2025 18:21:15","16-07-2025 21:08:5=
2","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"vanel.mbiada@matech-cameroun.com","246","16-07-2025 18:25:18","MATECH CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0005494393","Don=
g","","16-07-2025 18:19:35","16-07-2025 18:18:24","16-07-2025 18:19:33","No=
 power issue on site U=3D50V site on Battery, The TX FME Gr=E9goire //65454=
7479// from huawei is informed,","Parker Tchoup","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site U=3D50V site on Battery, The TX FME Gr=E9goire //654547479// from =
huawei is informed,","cedric.tiani@matech-cameroun.com","72","16-07-2025 18=
:19:35","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005494062","TON=
GOLO SNEC","","16-07-2025 17:33:29","16-07-2025 17:31:22","16-07-2025 17:41=
:33","Site went down due to insufficient rectifiers (03)//site stablilsed",=
"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficient rectifiers (03)//site stablilsed","c=
edric.tiani@matech-cameroun.com","128","16-07-2025 17:33:29","MATECH CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0005493960","San=
ta Barbara Gottam","","16-07-2025 17:17:49","16-07-2025 17:15:25","16-07-20=
25 17:21:50","Site went down due to work of Jule Stev from PICCARDI SARL on=
 site (swapp of PWC and Gen)//End of work","Delor Telezing","Installation A=
ctivity","Passive","Planned Activity","Installation Activity","Site went do=
wn due to work of Jule Stev from PICCARDI SARL on site (swapp of PWC and Ge=
n)//End of work","cedric.tiani@matech-cameroun.com","145","16-07-2025 17:17=
:49","MATECH CMR"
"Closed Complete","Site Down","CTR_546","IHS_YND_419","NOCINC0005493854","N=
gog Mapubi","","16-07-2025 16:59:56","16-07-2025 16:51:58","16-07-2025 17:0=
2:40","No power issue on site ,site on Gen with Ubaie=3D 54,8V The fme tx E=
tienne fopa // 695033981 of huawei is informed","Kemeni Franklin","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site ,site on Gen with Ubaie=3D 54,8V The fme tx Etien=
ne fopa // 695033981 of huawei is informed","vanel.mbiada@matech-cameroun.c=
om","479","16-07-2025 16:59:56","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005493803","M=
atsari","","16-07-2025 16:52:01","16-07-2025 16:36:55","16-07-2025 17:23:21=
","Active // No power issue on site with Ubaie=3D53.8V site on Gen ,The Tx =
Fme Gregoire( 652070658)from Huawei is informed","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue on site with Ubaie=3D53.8V site on Gen ,The Tx F=
me Gregoire( 652070658)from Huawei is informed","vanel.mbiada@matech-camero=
un.com","908","16-07-2025 16:52:01","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005493427","TON=
GOLO SNEC","","16-07-2025 15:49:14","16-07-2025 15:46:07","16-07-2025 16:04=
:30","Site went down due to insufficient rectifiers (03)//site stablilsed",=
"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficient rectifiers (03)//site stablilsed","v=
anel.mbiada@matech-cameroun.com","188","16-07-2025 15:49:14","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005493065","TON=
GOLO SNEC","","16-07-2025 14:53:37","16-07-2025 14:50:29","16-07-2025 15:00=
:26","Site went down due to insufficient rectifiers (03)//He need to add 01=
 ","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficient rectifiers (03)//He need to add 0=
1 ","cedric.tiani@matech-cameroun.com","189","16-07-2025 14:53:37","MATECH =
CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005492918","E=
seka OCM","","16-07-2025 14:36:45","16-07-2025 14:33:11","16-07-2025 14:54:=
30","No power issue U=3D55.4V site on Grid The Tx FME Etienne FOPA /6950339=
81/ From HUAWEI is informed","Kemeni Franklin","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=
=3D55.4V site on Grid The Tx FME Etienne FOPA /695033981/ From HUAWEI is in=
formed","vanel.mbiada@matech-cameroun.com","215","16-07-2025 14:36:45","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005492440","N=
simalen OCM","","16-07-2025 13:51:39","16-07-2025 13:34:23","16-07-2025 14:=
58:26","Site went down due to work done by ALBRAN(657108542)(Maintenance of=
 generator)//End of work","Albran Byorel","Installation Activity","Passive"=
,"Planned Activity","Installation Activity","Site went down due to work don=
e by ALBRAN(657108542)(Maintenance of generator)//End of work","edwige.kapa=
wo@matech-cameroun.com","1037","16-07-2025 13:51:39","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005492293","TON=
GOLO SNEC","","16-07-2025 13:25:38","16-07-2025 13:18:32","16-07-2025 13:36=
:32","Site went down due to insufficiency (1/4) of rectifiers, SS IHS Berna=
rd Atangana is informed // Site stabilised","Fabrice Pouakam","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down due to insuf=
ficiency (1/4) of rectifiers, SS IHS Bernard Atangana is informed // Site s=
tabilised","gerard.tchangoue@matech-cameroun.com","427","16-07-2025 13:25:3=
8","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005492286","Nko=
lbong","","16-07-2025 13:21:52","16-07-2025 13:19:37","16-07-2025 13:36:45"=
,"Grid outage,Site Down because Gen started and stopped due to Gen overload=
(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started and =
stopped due to Gen overload(22kva//350A)//Grid return","gerard.tchangoue@ma=
tech-cameroun.com","136","16-07-2025 13:21:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005492224","C-Suprem=
e","","16-07-2025 13:08:51","16-07-2025 13:02:02","16-07-2025 17:15:19","Ca=
scaded Incident from TTO5673707","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site down due to PWC overload, =
(210A ,12kva)//Site stabilised","system","298904","16-07-2025 13:08:51","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005492223","Acropole=
","","16-07-2025 13:08:50","16-07-2025 13:02:02","16-07-2025 17:15:19","Cas=
caded Incident from TTO5673707","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site down due to PW=
C overload, (210A ,12kva)//Site stabilised","system","298905","16-07-2025 1=
3:08:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005492222","Olezoa O=
CM","","16-07-2025 13:08:50","16-07-2025 13:02:02","16-07-2025 17:15:19","C=
ascaded Incident from TTO5673707","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid fluctuations ,Site down due to PWC overload,=
 (210A ,12kva)//Site stabilised","system","298904","16-07-2025 13:08:50","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005492216","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","16-07-2025 13:07:11",=
"16-07-2025 13:02:02","16-07-2025 17:15:37","Grid fluctuations ,Site down d=
ue to PWC overload, (210A ,12kva)//Site stabilised","MINKA NICOLAS","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations ,Site down due to PWC overload, (210A ,12kva)//Site stabilised","ed=
wige.kapawo@matech-cameroun.com","310","16-07-2025 13:07:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0005492159","Abang","=
","16-07-2025 12:57:00","16-07-2025 12:44:59","16-07-2025 12:59:15","Cascad=
ed Incident from TTO5673587","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE//no power issue on site Ubaie=3D52=
:7 V site on Grid Lionel Tchatchou (694693436) from Huawei is informed","sy=
stem","264068","16-07-2025 12:57:00","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0005492104","N=
kolangaa","IHS_YND_290","16-07-2025 12:54:10","16-07-2025 12:44:59","16-07-=
2025 12:59:15","ACTIVE//no power issue on site Ubaie=3D52:7 V site on Grid =
Lionel Tchatchou (694693436) from Huawei is informed","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE//no power issue on site Ubaie=3D52:7 V site on Grid Lionel=
 Tchatchou (694693436) from Huawei is informed","edwige.kapawo@matech-camer=
oun.com","553","16-07-2025 12:54:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005491928","Acropole=
","","16-07-2025 12:23:21","16-07-2025 10:24:19","16-07-2025 12:56:56","Cas=
caded Incident from TTO5672623","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site down due to PW=
C overload, (210A ,12k) // Site stabilised","system","272411","16-07-2025 1=
2:23:21","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005491682","Nsi=
malen MTN","","16-07-2025 11:43:14","16-07-2025 11:40:08","16-07-2025 12:20=
:26","Site went down due to work done by ALBRAN(657108542)(Maintenance of g=
enerator)","Albran Byorel","Installation Activity","Passive","Planned Activ=
ity","Installation Activity","Site went down due to work done by ALBRAN(657=
108542)(Maintenance of generator)//End of work","gerard.tchangoue@matech-ca=
meroun.com","187","16-07-2025 11:43:14","MATECH CMR"
"Cancelled","Site Down","CTR_476","IHS_YND_520","NOCINC0005491667","SIMBOCK=
 BONAMBAPE","","16-07-2025 11:40:50","","","Active // No power issue site o=
n grid with Ubaie: 54.5V TX FME Flubert (654266068) from Huawei is informed=
","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active // No power issue site on grid with U=
baie: 54.5V TX FME Flubert (654266068) from Huawei is informed","edwige.kap=
awo@matech-cameroun.com","0","16-07-2025 11:40:50","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005491666","SIM=
BOCK BONAMBAPE","","16-07-2025 11:40:50","16-07-2025 11:38:31","16-07-2025 =
11:41:27","Grid outage, Site went down before Gen start due to poor backup =
// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.co=
m","141","16-07-2025 11:40:50","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005491502","Saa=
","IHS_YND_810, IHS_YND_809","16-07-2025 11:07:41","16-07-2025 11:05:35","1=
6-07-2025 11:44:10","Grid outage .gen failed to start due to unproven alarm=
 ''high temp''//We reset card GE and gen manually started ","Parker Tchoup"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e .gen failed to start due to unproven alarm ''high temp''//We reset card G=
E and gen manually started ","gerard.tchangoue@matech-cameroun.com","128","=
16-07-2025 11:07:41","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005491311","L=
abogenie","IHS_YND_568","16-07-2025 10:40:54","16-07-2025 10:35:45","16-07-=
2025 13:33:56","Wrongly logged  ticket ","","Incorrectly Logged Tickets","E=
rror","Error","Error","Wrongly logged  ticket ","edwige.kapawo@matech-camer=
oun.com","311","16-07-2025 10:40:54","MATECH CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0005491273","A=
nguissa New","","16-07-2025 10:36:04","16-07-2025 10:35:45","16-07-2025 13:=
33:56","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Wrongly logged  ticket ","edwige.kapawo@matech-cameroun.com"=
,"1228417","16-07-2025 10:36:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005491241","C-Suprem=
e","","16-07-2025 10:27:20","16-07-2025 10:24:19","16-07-2025 12:56:56","Ca=
scaded Incident from TTO5672623","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site down due to PWC overload, =
(210A ,12k) // Site stabilised","system","272411","16-07-2025 10:27:20","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005491238","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","16-07-2025 10:26:26","16-07-2025 1=
0:24:19","16-07-2025 12:56:56","Grid fluctuations ,Site down due to PWC ove=
rload, (210A ,12k) // Site stabilised","MINKA NICOLAS","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations ,Site=
 down due to PWC overload, (210A ,12k) // Site stabilised","edwige.kapawo@m=
atech-cameroun.com","129","16-07-2025 10:26:26","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005491231","B=
arriere","","16-07-2025 10:25:22","16-07-2025 10:24:14","16-07-2025 16:54:2=
4","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"edwige.kapawo@matech-cameroun.com","71","16-07-2025 10:25:22","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0005491177","Bar=
riere IHS","","16-07-2025 10:13:25","16-07-2025 10:09:14","16-07-2025 13:13=
:21","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS F=
ELIX ZAMBE is informed//Grid return	","Hyemafo Gildas","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to G=
en overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed//Grid return	","ger=
ard.tchangoue@matech-cameroun.com","252","16-07-2025 10:13:25","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005491152","SIM=
BOCK BONAMBAPE","","16-07-2025 10:08:54","16-07-2025 10:06:46","16-07-2025 =
10:08:25","Grid outage, Site went down before Gen start due to poor backup =
// Grid return","Hyemafo Gildas","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active // No power issue site =
on grid with Ubaie: 54.4V TX FME Flubert (654266068) from Huawei is informe=
d","gerard.tchangoue@matech-cameroun.com","130","16-07-2025 10:08:54","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0005491063","Y=
de-M-Central","","16-07-2025 09:54:56","16-07-2025 09:46:29","16-07-2025 11=
:00:02","Site went down due to disjunction of Cb(125A) in PWC // He reamed =
Cb(125A), site on grid","","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Circuit Breaker Issue","Site went down due to disjunction of =
Cb(125A) in PWC // He reamed Cb(125A), site on grid","edwige.kapawo@matech-=
cameroun.com","508","16-07-2025 09:54:56","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005490967","A=
wae Ewonkan","","16-07-2025 09:37:14","16-07-2025 09:36:59","16-07-2025 09:=
52:18","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid retur=
n","edwige.kapawo@matech-cameroun.com","17","16-07-2025 09:37:14","MATECH C=
MR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005490940","M=
atsari","","16-07-2025 09:32:20","16-07-2025 09:31:12","16-07-2025 10:12:36=
","Active // No power issue on site with Ubaie=3D53.8V site on Gen ,The Tx =
Fme Gregoire( 652070658)from Huawei is informed","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue on site with Ubaie=3D53.8V site on Gen ,The Tx F=
me Gregoire( 652070658)from Huawei is informed","edwige.kapawo@matech-camer=
oun.com","69","16-07-2025 09:32:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005490601","Carrefou=
r Ayissi Ele","","16-07-2025 08:34:14","16-07-2025 08:16:59","16-07-2025 11=
:44:10","Site impacted by Saa","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, Site went down because gen=
 failed to start due to automatism system dysfunctionning // He reset it an=
d manually start the gen","system","1379","16-07-2025 08:34:14","MATECH CMR=
"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005490592","Nko=
l-Mebanga","","16-07-2025 08:33:11","16-07-2025 08:16:59","16-07-2025 11:44=
:10","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, Site went down because gen failed to start due to=
 automatism system dysfunctionning // He reset it and manually start the ge=
n","gerard.tchangoue@matech-cameroun.com","1179","16-07-2025 08:33:11","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005490580","Nkolfon =
Cimencam","","16-07-2025 08:27:41","16-07-2025 08:23:33","16-07-2025 13:11:=
47","Cascaded Incident from TTO5671861","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirm=
ed // Grid return","system","1229156","16-07-2025 08:27:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005490579","Ahala","=
","16-07-2025 08:27:41","16-07-2025 08:23:33","16-07-2025 13:11:47","Cascad=
ed Incident from TTO5671861","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Gen o=
verload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid =
return","system","1229155","16-07-2025 08:27:41","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005490568","M=
eyo","IHS_YND_257, IHS_YND_762","16-07-2025 08:25:41","16-07-2025 08:23:33"=
,"16-07-2025 13:18:59","Grid outage, site went down due to Gen overload (17=
KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid return","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix Za=
mbe is informed and confirmed // Grid return","edwige.kapawo@matech-camerou=
n.com","129","16-07-2025 08:25:41","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005490531","S=
aa","IHS_YND_810, IHS_YND_809","16-07-2025 08:18:09","16-07-2025 08:16:59",=
"16-07-2025 08:41:26","Grid outage, Site went down because gen failed to st=
art due to automatism system dysfunctionning // He reset it and manually st=
art the gen","Parker Tchoup","Equipment Repair","Passive","Control Panel","=
ATS-AMF Issue","Grid outage, Site went down because gen failed to start due=
 to automatism system dysfunctionning // He reset it and manually start the=
 gen","edwige.kapawo@matech-cameroun.com","72","16-07-2025 08:18:09","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005490399","A=
fanoya","","16-07-2025 07:49:51","16-07-2025 07:40:59","16-07-2025 10:51:58=
","Grid outage site went down because Gen failed to start due to Gen batter=
y discharged causing by charging alternator faulty// He replaced  alternato=
r and  belt","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Charging Alternator","Grid outage site went down because Gen failed to s=
tart due to Gen battery discharged causing by charging alternator faulty// =
He replaced  alternator and  belt","edwige.kapawo@matech-cameroun.com","534=
","16-07-2025 07:49:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005490382","Ngoum","=
","16-07-2025 07:45:41","16-07-2025 07:37:45","16-07-2025 08:57:31","Cascad=
ed Incident from TTO5671652","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down and gen failed to start du=
e to alarm undervoltave causing by fuel filter dirty//We clean fuel fliter =
and purged and gen manually started","system","289573","16-07-2025 07:45:41=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005490383","Yoko MTN=
","","16-07-2025 07:45:41","16-07-2025 07:37:45","16-07-2025 08:57:31","Cas=
caded Incident from TTO5671652","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down and gen failed to start=
 due to alarm undervoltave causing by fuel filter dirty//We clean fuel flit=
er and purged and gen manually started","system","289574","16-07-2025 07:45=
:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005490373","MBIMBIM"=
,"","16-07-2025 07:44:29","16-07-2025 07:37:45","16-07-2025 09:00:43","Casc=
aded Incident from TTO5671649","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site went down and gen failed to start =
due to alarm undervoltave causing by fuel filter dirty//We clean fuel flite=
r and purged and gen manually started","system","289575","16-07-2025 07:44:=
29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005490372","Ngouetou=
","","16-07-2025 07:44:29","16-07-2025 07:37:45","16-07-2025 09:00:43","Cas=
caded Incident from TTO5671649","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down and gen failed to start=
 due to alarm undervoltave causing by fuel filter dirty//We clean fuel flit=
er and purged and gen manually started","system","404","16-07-2025 07:44:29=
","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005490363","M=
atsari","IHS_YND_475, IHS_YND_454, IHS_YND_473, IHS_YND_456","16-07-2025 07=
:42:54","16-07-2025 07:37:45","16-07-2025 09:00:43","site went down and gen=
 failed to start due to alarm undervoltave causingby fuel filter dirty//We =
clean fuel fliter and purged and gen manually started","Parker Tchoup","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Fuel Filter","site went down an=
d gen failed to start due to alarm undervoltave causing by fuel filter dirt=
y//We clean fuel fliter and purged and gen manually started","edwige.kapawo=
@matech-cameroun.com","311","16-07-2025 07:42:54","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005490361","Mey=
o","","16-07-2025 07:41:58","16-07-2025 07:22:30","16-07-2025 07:50:39","Gr=
id outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix Za=
mbe is informed and confirmed // Grid return","Hyemafo Gildas","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down =
due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and confir=
med // Grid return","edwige.kapawo@matech-cameroun.com","1169","16-07-2025 =
07:41:58","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005490264","Sim=
e Building","","16-07-2025 07:24:19","16-07-2025 07:16:14","16-07-2025 07:3=
6:38","Grid outage, Site went down before Gen start due to poor backup// Ge=
n automatically started","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Gen automatically started","gerard.tchango=
ue@matech-cameroun.com","486","16-07-2025 07:24:19","MATECH CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0005490144","NYA=
NON/DEMBO","","16-07-2025 07:04:35","16-07-2025 06:23:20","16-07-2025 08:45=
:43","Site went down due to CB gen disjuncted //We rearmed CB and site on g=
en ","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel=
","Circuit Breaker Tripped","Site went down due to CB gen disjuncted //We r=
earmed CB and site on gen ","joelle.ekessi@ihstowers.com","2476","16-07-202=
5 07:04:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005490060","Acropole=
","","16-07-2025 06:49:21","16-07-2025 06:30:57","16-07-2025 10:14:45","Cas=
caded Incident from TTO5671245","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site down due to PW=
C overload, (210A ,12k) // Site stabilised","system","279232","16-07-2025 0=
6:49:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005490059","Olezoa O=
CM","","16-07-2025 06:49:21","16-07-2025 06:30:57","16-07-2025 10:14:45","C=
ascaded Incident from TTO5671245","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid fluctuations ,Site down due to PWC overload,=
 (210A ,12k) // Site stabilised","system","279232","16-07-2025 06:49:21","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005490054","B=
arriere","","16-07-2025 06:47:51","16-07-2025 06:46:34","16-07-2025 10:15:2=
1","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","gaelle.njiofack@matech-cameroun.com","79","16-07-2025 06:47:51","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005490013","C-Suprem=
e","","16-07-2025 06:33:05","16-07-2025 06:30:57","16-07-2025 10:14:45","Ca=
scaded Incident from TTO5671245","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site down due to PWC overload, =
(210A ,12k) // Site stabilised","system","279233","16-07-2025 06:33:05","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005489997","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","16-07-2025 06:31:01",=
"16-07-2025 06:30:57","16-07-2025 10:14:45","Grid fluctuations ,Site down d=
ue to PWC overload, (210A ,12k) // Site stabilised","MINKA NICOLAS","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations ,Site down due to PWC overload, (210A ,12k) // Site stabilised","ga=
elle.njiofack@matech-cameroun.com","5","16-07-2025 06:31:01","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005489758","Evo=
doula MTN","","16-07-2025 05:07:43","16-07-2025 05:02:33","16-07-2025 05:22=
:56","Grid outage, Site went down before Gen start due to poor backup // Ge=
n Automaticaly started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup // Gen Automaticaly started","fran=
ck.nkomot@matech-cameroun.com","311","16-07-2025 05:07:43","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005489744","Oko=
la","","16-07-2025 05:01:11","16-07-2025 04:59:49","16-07-2025 05:24:57","G=
rid outage. Site down because ,gen started and stopped due to alarm""high t=
emp""//water added  and gen manually started","TIENTCHEU NZETCHIEU GAEL","E=
quipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Le=
vel Issue","Grid outage. Site down because ,gen started and stopped due to =
alarm""high temp""//water added  and gen manually started","gaelle.njiofack=
@matech-cameroun.com","83","16-07-2025 05:01:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005489512","Ngouetou=
","","16-07-2025 03:42:30","16-07-2025 03:40:23","16-07-2025 03:49:16","Cas=
caded Incident from TTO5670733","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site with Ubaie=3D54.5V=
 site on Gen ,The Tx Fme Gregoire( 652070658)from Huawei is informed","syst=
em","260675","16-07-2025 03:42:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005489513","MBIMBIM"=
,"","16-07-2025 03:42:30","16-07-2025 03:40:23","16-07-2025 03:49:16","Casc=
aded Incident from TTO5670733","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site with Ubaie=3D54.5V =
site on Gen ,The Tx Fme Gregoire( 652070658)from Huawei is informed","syste=
m","260674","16-07-2025 03:42:30","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005489507","M=
atsari","IHS_YND_454, IHS_YND_456","16-07-2025 03:41:32","16-07-2025 03:40:=
23","16-07-2025 03:49:16","No power issue on site with Ubaie=3D54.5V site o=
n Gen ,The Tx Fme Gregoire( 652070658)from Huawei is informed","Parker Tcho=
up","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site with Ubaie=3D54.5V site on Gen ,The =
Tx Fme Gregoire( 652070658)from Huawei is informed","gaelle.njiofack@matech=
-cameroun.com","70","16-07-2025 03:41:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005488881","Olezoa O=
CM","","16-07-2025 00:03:34","15-07-2025 22:50:38","16-07-2025 00:13:57","C=
ascaded Incident from TTO5669759","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid fluctuations ,Site  down due to PWC overload=
, (210A ,12k)//Site stabilised","system","270828","16-07-2025 00:03:34","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005488882","Acropole=
","","16-07-2025 00:03:34","15-07-2025 22:50:38","16-07-2025 00:13:57","Cas=
caded Incident from TTO5669759","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site  down due to P=
WC overload, (210A ,12k)//Site stabilised","system","270827","16-07-2025 00=
:03:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005488813","Ngoum","=
","15-07-2025 23:43:44","15-07-2025 23:37:24","16-07-2025 01:37:30","","Par=
ker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Hybrid gen site ,Gen fail to start due to fuel shortage  //Refueling done =
by  EDONDE ","system","275219","15-07-2025 23:43:44","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0005488806","Yok=
o MTN","","15-07-2025 23:42:50","15-07-2025 23:37:24","16-07-2025 01:37:30"=
,"","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Hybrid gen site ,Gen fail to start due to fuel shortage  //Refueli=
ng done by  EDONDE ","franck.nkomot@matech-cameroun.com","275219","15-07-20=
25 23:42:50","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005488790","N=
gouetou","","15-07-2025 23:40:35","15-07-2025 23:33:01","16-07-2025 01:38:1=
7","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Hybrid gen site ,Gen fail to start due to fuel shortage  //Refue=
ling done by  EDONDE ","gaelle.njiofack@matech-cameroun.com","275483","15-0=
7-2025 23:40:35","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005488785","M=
atsari","IHS_YND_475, IHS_YND_454, IHS_YND_473, IHS_YND_456","15-07-2025 23=
:39:31","15-07-2025 23:33:01","16-07-2025 01:42:30","Hybrid Gen site,  site=
 down because,Gen ran till  fuel shortage  //Refueling done by  EDONDE ","P=
arker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Hybrid gen =
site ,Gen fail to start due to fuel shortage  //Refueling done by  EDONDE "=
,"gaelle.njiofack@matech-cameroun.com","8126","15-07-2025 23:39:31","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0005488782","M=
BIMBIM","","15-07-2025 23:38:59","15-07-2025 23:33:01","16-07-2025 01:38:17=
","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Hybrid gen site ,Gen fail to start due to fuel shortage  //Refuel=
ing done by  EDONDE ","gaelle.njiofack@matech-cameroun.com","275483","15-07=
-2025 23:38:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005488638","C-Suprem=
e","","15-07-2025 23:00:41","15-07-2025 22:50:38","16-07-2025 00:13:57","Ca=
scaded Incident from TTO5669759","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site  down due to PWC overload,=
 (210A ,12k)//Site stabilised","system","270827","15-07-2025 23:00:41","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005488620","M=
ontee-Des-Soeurs","","15-07-2025 22:52:38","15-07-2025 22:50:30","16-07-202=
5 07:02:26","Grid outage ,site down due to Gen overload (15 KVA/210 A)// Gr=
id return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A)// Gri=
d return","gaelle.njiofack@matech-cameroun.com","130","15-07-2025 22:52:38"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005488618","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","15-07-2025 22:51:54",=
"15-07-2025 22:50:38","16-07-2025 00:13:57","Grid fluctuations ,Site down d=
ue to PWC overload, (210A ,12k)//Site stabilised","MINKA NICOLAS","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctua=
tions ,Site  down due to PWC overload, (210A ,12k)//Site stabilised","gaell=
e.njiofack@matech-cameroun.com","77","15-07-2025 22:51:54","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005488613","N=
kolbong","","15-07-2025 22:49:42","15-07-2025 22:44:34","15-07-2025 23:08:5=
2","Grid outage,Site Down because Gen started and stopped due to Gen overlo=
ad(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage,Site Down because Gen started an=
d stopped due to Gen overload(22kva//350A)//Grid return","gaelle.njiofack@m=
atech-cameroun.com","310","15-07-2025 22:49:42","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005488525","B=
arriere","","15-07-2025 22:26:45","15-07-2025 22:24:40","16-07-2025 00:06:2=
2","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","loic.noumsi@matech-cameroun.com","127","15-07-2025 22:26:45","MATECH CMR=
"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005488173","Bit=
eng-Maetur","","15-07-2025 21:25:35","15-07-2025 21:22:29","15-07-2025 21:3=
8:42","Site went down due to disjunction of CB (125A) in the DCBOX MTN // H=
e rearmed it, Site on Grid","Mba Lazare Herve","Equipment Repair","Passive"=
,"Control Panel","ATS-AMF Issue","Site went down due to disjunction of CB (=
125A) in the DCBOX MTN // He rearmed it, Site on Grid","loic.noumsi@matech-=
cameroun.com","188","15-07-2025 21:25:35","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005488000","N=
kolbong","","15-07-2025 20:55:59","15-07-2025 20:50:53","15-07-2025 22:09:0=
7","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","307","15-07-2025 20:55:59","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005487954","M=
vog Mbi New","","15-07-2025 20:50:24","15-07-2025 20:48:05","15-07-2025 21:=
29:20","	Grid fluctuations ,Site Went down due to PWC overload, (210A ,12k)=
//Site stabilised","MINKA NICOLAS","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module Overloaded","	Grid fluctuations ,Site Went down due to P=
WC overload, (210A ,12k)//Site stabilised","gaelle.njiofack@matech-cameroun=
.com","141","15-07-2025 20:50:24","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005487816","N=
KOLMEKONG YDE","","15-07-2025 20:21:46","15-07-2025 20:19:33","15-07-2025 2=
0:33:16","Active// No power issue on site Ubaie =3D52V site on Grid The TX =
FME Synphorien (650257151) from Huawei is informed.","Fabrice Pouakam","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active//No power issue on site Ubaie =3D52V site on Grid The TX FME=
 Synphorien (650257151) from Huawei is informed","gaelle.njiofack@matech-ca=
meroun.com","135","15-07-2025 20:21:46","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005487804","NYO=
M FACE MAETUR","","15-07-2025 20:18:54","15-07-2025 20:16:50","15-07-2025 2=
3:12:01","Site down due to dysfuncion of 4 rectifiers  // rectifiers  reset=
ed ","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site down due to dysfuncion of 4 rectifiers  // rectifiers  resete=
d ","loic.noumsi@matech-cameroun.com","126","15-07-2025 20:18:54","MATECH C=
MR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005487800","TON=
GOLO SNEC","","15-07-2025 20:18:05","15-07-2025 20:13:01","15-07-2025 20:24=
:14","Site went down due to insufficiency (1/4) of rectifiers, SS IHS Berna=
rd Atangana is informed // Site stabilised","Fabrice Pouakam","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down due to insuf=
ficiency (1/4) of rectifiers, SS IHS Bernard Atangana is informed // Site s=
tabilised","loic.noumsi@matech-cameroun.com","305","15-07-2025 20:18:05","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005487759","B=
arriere","","15-07-2025 20:10:18","15-07-2025 20:09:05","15-07-2025 21:47:4=
0","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","gaelle.njiofack@matech-cameroun.com","76","15-07-2025 20:10:18","MATECH =
CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005487575","M=
vog Mbi New","","15-07-2025 19:30:33","15-07-2025 19:29:15","15-07-2025 19:=
30:51","Grid fluctuations ,Site Went down due to PWC overload, (210A ,12kva=
)","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","Grid fluctuations ,Site Went down due to PWC overload, (210A ,12k) // Si=
te stabilised","gaelle.njiofack@matech-cameroun.com","79","15-07-2025 19:30=
:33","MATECH CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0005487244","Don=
ga","","15-07-2025 18:33:34","15-07-2025 18:32:29","15-07-2025 20:02:01","H=
ybrid gen, site went down because Gen failed to start due to Gen battery fa=
ulty // He started Gen with an external battery, site on GEN","Parker Tchou=
p","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Hybr=
id gen, site went down because Gen failed to start due to Gen battery fault=
y // He started Gen with an external battery, site on GEN","loic.noumsi@mat=
ech-cameroun.com","66","15-07-2025 18:33:34","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005487242","N=
kolbong","","15-07-2025 18:32:52","15-07-2025 18:29:42","15-07-2025 20:12:5=
2","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","192","15-07-2025 18:32:52","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005486752","TON=
GOLO SNEC","","15-07-2025 17:08:52","15-07-2025 17:08:48","15-07-2025 18:20=
:04","Site went down due to insufficiency (1/4) of rectifiers, SS IHS Berna=
rd Atangana is informed // Site stabilised","Fabrice Pouakam","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down due to insuf=
ficiency (1/4) of rectifiers, SS IHS Bernard Atangana is informed // Site s=
tabilised","loic.noumsi@matech-cameroun.com","5","15-07-2025 17:08:52","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005486746","B=
arriere","","15-07-2025 17:07:55","15-07-2025 17:04:49","15-07-2025 18:05:3=
3","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","loic.noumsi@matech-cameroun.com","189","15-07-2025 17:07:55","MATECH CMR=
"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005486608","M=
vog Mbi New","","15-07-2025 16:39:16","15-07-2025 16:36:11","15-07-2025 18:=
02:30","Grid fluctuations ,Site Went down due to PWC overload, (210A ,12k)/=
/Site stabilised","MINKA NICOLAS","Equipment Repair","Passive","Rectifier",=
"Rectifier Module Overloaded","Grid fluctuations ,Site Went down due to PWC=
 overload, (210A ,12k)//Site stabilised","loic.noumsi@matech-cameroun.com",=
"186","15-07-2025 16:39:16","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005486605","N=
kolbong","","15-07-2025 16:38:05","15-07-2025 16:34:58","15-07-2025 17:03:4=
2","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","loic.no=
umsi@matech-cameroun.com","189","15-07-2025 16:38:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005486520","Mfou EPC=
","","15-07-2025 16:34:29","15-07-2025 16:28:44","15-07-2025 16:34:11","Cas=
caded Incident from TTO5667391","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","265049","15-07-2025 16=
:34:29","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005486514","M=
fou OCM","IHS_YND_674","15-07-2025 16:33:53","15-07-2025 16:28:44","15-07-2=
025 16:34:11","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","loic.noumsi@matech-cameroun.com",=
"310","15-07-2025 16:33:53","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005486307","TON=
GOLO SNEC","","15-07-2025 16:14:09","15-07-2025 16:09:02","15-07-2025 16:19=
:28","Site went down due to insufficiency (1/4) of rectifiers, SS IHS Berna=
rd Atangana is informed // Site stabilised","Fabrice Pouakam","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down due to insuf=
ficiency (1/4) of rectifiers, SS IHS Bernard Atangana is informed // Site s=
tabilised","loic.noumsi@matech-cameroun.com","308","15-07-2025 16:14:09","M=
ATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005486184","AKA=
K Nkozoa","","15-07-2025 15:48:16","15-07-2025 15:46:08","15-07-2025 15:54:=
18","Active// No power issue, site is on Grid with Ubaie=3D50,4 V TX FME Sy=
mphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Symphor=
ien (650257151) from Huawei is informed","loic.noumsi@matech-cameroun.com",=
"129","15-07-2025 15:48:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_322","NOCINC0005486152","Soa-II",=
"","15-07-2025 15:45:01","15-07-2025 15:37:24","15-07-2025 15:40:35","Casca=
ded Incident from TTO5666950","Siligap Boris","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active: No Power Issue site on grid,Ubaie:5=
4,3V. TX FME JULIEN (693095849/HUAWEI) is informed","system","268074","15-0=
7-2025 15:45:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0005486151","SOA UNIV=
ERSITY STADIUM","","15-07-2025 15:45:01","15-07-2025 15:37:24","15-07-2025 =
15:40:35","Cascaded Incident from TTO5666950","Siligap Boris","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","Active: No Power Issue site=
 on grid,Ubaie:54,3V. TX FME JULIEN (693095849/HUAWEI) is informed","system=
","268071","15-07-2025 15:45:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0005486153","SOA TOWN=
","","15-07-2025 15:45:01","15-07-2025 15:37:24","15-07-2025 15:40:35","Cas=
caded Incident from TTO5666950","Siligap Boris","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active: No Power Issue site on grid,Ubaie=
:54,3V. TX FME JULIEN (693095849/HUAWEI) is informed","system","268069","15=
-07-2025 15:45:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005486150","Akak-Nko=
zoa-MTN-IHS","","15-07-2025 15:45:01","15-07-2025 15:37:24","15-07-2025 15:=
40:35","Cascaded Incident from TTO5666950","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active: No Power Issue site =
on grid,Ubaie:54,3V. TX FME JULIEN (693095849/HUAWEI) is informed","system"=
,"268068","15-07-2025 15:45:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_317","NOCINC0005486148","Soa-Sofa=
mac","","15-07-2025 15:45:00","15-07-2025 15:37:24","15-07-2025 15:40:35","=
Cascaded Incident from TTO5666950","Siligap Boris","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active: No Power Issue site on grid,Ub=
aie:54,3V. TX FME JULIEN (693095849/HUAWEI) is informed","system","268073",=
"15-07-2025 15:45:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0005486149","Ebogo","=
","15-07-2025 15:45:00","15-07-2025 15:37:24","15-07-2025 15:40:35","Cascad=
ed Incident from TTO5666950","Siligap Boris","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active: No Power Issue site on grid,Ubaie:54=
,3V. TX FME JULIEN (693095849/HUAWEI) is informed","system","268068","15-07=
-2025 15:45:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0005486146","NYOM 2 I=
HS","","15-07-2025 15:45:00","15-07-2025 15:37:24","15-07-2025 15:40:35","C=
ascaded Incident from TTO5666950","Fabrice Pouakam","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active: No Power Issue site on grid,U=
baie:54,3V. TX FME JULIEN (693095849/HUAWEI) is informed","system","268075"=
,"15-07-2025 15:45:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_321","NOCINC0005486147","Soa","",=
"15-07-2025 15:45:00","15-07-2025 15:37:24","15-07-2025 15:40:35","Cascaded=
 Incident from TTO5666950","Siligap Boris","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active: No Power Issue site on grid,Ubaie:54,3=
V. TX FME JULIEN (693095849/HUAWEI) is informed","system","268070","15-07-2=
025 15:45:00","MATECH CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0005486118","S=
OA 2","IHS_YND_707, IHS_YND_321, IHS_YND_317, IHS_YND_307, IHS_YND_316, IHS=
_YND_720, IHS_YND_326, IHS_YND_324, IHS_YND_322, IHS_YND_320","15-07-2025 1=
5:41:30","15-07-2025 15:37:24","15-07-2025 15:40:35","Active: No Power Issu=
e site on Grid,Ubaie:54,3V. TX FME JULIEN (693095849/HUAWEI) is informed","=
Siligap Boris","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active: No Power Issue site on grid,Ubaie:54,3V.=
 TX FME JULIEN (693095849/HUAWEI) is informed","loic.noumsi@matech-cameroun=
.com","247","15-07-2025 15:41:30","MATECH CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0005486111","N=
gousso OCM","","15-07-2025 15:40:41","15-07-2025 15:35:28","15-07-2025 15:3=
7:10","No power issue on site U=3D56,5V , Site is on Grid and The FME TX Ar=
mand Nguetsa (699949553) From Huawei is informed","Siligap Boris","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site U=3D56,5V , Site is on Grid and The FME TX Armand=
 Nguetsa (699949553) From Huawei is informed","loic.noumsi@matech-cameroun.=
com","314","15-07-2025 15:40:41","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005486041","NKO=
MKANA ELIZA HOTEL","","15-07-2025 15:31:19","15-07-2025 15:27:10","15-07-20=
25 15:35:32","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed//Grid stabilised","","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module Overloaded","Site went down due to PWC Overloaded and SS=
 IHS Bernard Atangana confirmed//Grid stabilised","loic.noumsi@matech-camer=
oun.com","251","15-07-2025 15:31:19","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005486021","Fla=
menco","","15-07-2025 15:28:37","15-07-2025 15:26:32","15-07-2025 15:36:15"=
,"Grid outage, site went down because Gen failed to start due to poor backu=
p // Site stabilised","Mboua Thierry","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, site went down because =
Gen failed to start due to poor backup // Site stabilised","loic.noumsi@mat=
ech-cameroun.com","126","15-07-2025 15:28:37","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005485994","C=
-Supreme","","15-07-2025 15:25:40","15-07-2025 15:18:32","15-07-2025 15:20:=
51","No power issue, site on Grid with Ubaie=3D54.5V, TX FME Brice Tsague (=
650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site on =
Grid with Ubaie=3D54.5V, TX FME Brice Tsague (650 21 40 96 / Huawei) is inf=
ormed. Noticed that it is a repetitive issue.","loic.noumsi@matech-cameroun=
.com","429","15-07-2025 15:25:40","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005485806","TON=
GOLO SNEC","","15-07-2025 15:03:24","15-07-2025 15:02:19","15-07-2025 15:12=
:06","Site went down due to insufficiency (1/4) of rectifiers, SS IHS Berna=
rd Atangana is informed.// Site stabilised","Fabrice Pouakam","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down due to insuf=
ficiency (1/4) of rectifiers, SS IHS Bernard Atangana is informed.// Site s=
tabilised","loic.noumsi@matech-cameroun.com","65","15-07-2025 15:03:24","MA=
TECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005485750","OTE=
LE MTN","","15-07-2025 14:54:17","15-07-2025 14:51:11","15-07-2025 14:55:56=
","Site went down due to PM done by our FME brice // END OF WORK","Fanda Br=
ice","Installation Activity","Passive","Planned Activity","Installation Act=
ivity","Site went down due to PM done by our FME brice // END OF WORK","loi=
c.noumsi@matech-cameroun.com","187","15-07-2025 14:54:17","MATECH CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0005485415","Y=
de-M-Central","","15-07-2025 14:10:23","15-07-2025 14:07:09","15-07-2025 19=
:41:58","Grid Outage No Space to deploy a MDG // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Sp=
ace to deploy a MDG // Grid return","vanel.mbiada@matech-cameroun.com","195=
","15-07-2025 14:10:23","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005485261","Oko=
la","","15-07-2025 13:39:35","15-07-2025 13:38:27","15-07-2025 14:48:29","S=
ite went down due to PM (securing Transmission) done by SS IHS Felix BATEU =
// End of work","TIENTCHEU NZETCHIEU GAEL","Installation Activity","Passive=
","Planned Activity","Installation Activity","Site went down due to PM (sec=
uring Transmission) done by SS IHS Felix BATEU // End of work","cedric.tian=
i@matech-cameroun.com","68","15-07-2025 13:39:35","MATECH CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0005485195","CLE=
 Building","","15-07-2025 13:29:37","15-07-2025 13:20:22","15-07-2025 19:46=
:10","Grid outage, no space to deploy a mobil gen // grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
no space to deploy a mobil gen // grid return","cedric.tiani@matech-camerou=
n.com","556","15-07-2025 13:29:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0005485159","Garbati =
building","","15-07-2025 13:24:49","15-07-2025 13:19:22","15-07-2025 13:22:=
22","Cascaded Incident from TTO5665887","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Outage, Site went down b=
efore Gen start due to poor backup // Gen Started Automatically","system","=
1211265","15-07-2025 13:24:49","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005485150","HOP=
ITAL DE LA CAISSE","IHS_YND_024","15-07-2025 13:23:30","15-07-2025 13:19:22=
","15-07-2025 13:22:22","Grid Outage, Site went down before Gen start due t=
o poor backup // Gen Started Automatically","Delor Telezing","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, =
Site went down before Gen start due to poor backup // Gen Started Automatic=
ally","cedric.tiani@matech-cameroun.com","249","15-07-2025 13:23:30","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0005485018","N=
goum","","15-07-2025 12:57:44","15-07-2025 12:55:56","15-07-2025 12:59:39",=
"Active: No power issue, site is on gen with Ubaie=3D52.9V.  The Tx FME Gre=
goire  (654547479) from Huawei is informed.","Parker Tchoup","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue, site is on grid with Ubaie=3D52.9V.

The Tx FME Gregoire  (654547479) from Huawei is informed.

","vanel.mbiada@matech-cameroun.com","110","15-07-2025 12:57:44","MATECH CM=
R"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005484792","NKO=
MKANA ELIZA HOTEL","","15-07-2025 12:20:46","15-07-2025 12:20:40","15-07-20=
25 12:28:38","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed//Grid stabilised","","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module Overloaded","Site went down due to PWC Overloaded and SS=
 IHS Bernard Atangana confirmed//Grid stabilised","cedric.tiani@matech-came=
roun.com","7","15-07-2025 12:20:46","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005484492","C=
-Supreme","","15-07-2025 11:31:40","15-07-2025 11:24:30","15-07-2025 11:34:=
23","No power issue, site on Grid with Ubaie=3D54.5V, Brice Tsague (650 21 =
40 96 / Huawei) is informed","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue, site on Grid wi=
th Ubaie=3D54.5V, Brice Tsague (650 21 40 96 / Huawei) is informed","vanel.=
mbiada@matech-cameroun.com","431","15-07-2025 11:31:40","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005484333","M=
ontee-Des-Soeurs","","15-07-2025 11:01:02","15-07-2025 10:59:31","15-07-202=
5 11:16:47","Grid outage ,site down due to Gen overload (15 KVA/210 A)// Gr=
id return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A)// Gri=
d return","vanel.mbiada@matech-cameroun.com","95","15-07-2025 11:01:02","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005484019","MEHANDAN=
","","15-07-2025 10:03:40","15-07-2025 09:59:07","15-07-2025 10:06:48","Cas=
caded Incident from TTO5664633","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction// Site stabilised","system","2=
66844","15-07-2025 10:03:40","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005484014","O=
dza II OCM","IHS_YND_528","15-07-2025 10:02:23","15-07-2025 09:59:07","15-0=
7-2025 10:06:48","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction// Site stabilised","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down because gen failed to start due to PWC ZTE malfunction// Site st=
abilised","vanel.mbiada@matech-cameroun.com","202","15-07-2025 10:02:23","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005483919","N=
kolbong","","15-07-2025 09:40:46","15-07-2025 09:39:33","15-07-2025 14:23:0=
7","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","vanel.m=
biada@matech-cameroun.com","75","15-07-2025 09:40:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005483916","Ngoum","=
","15-07-2025 09:39:50","15-07-2025 09:36:30","15-07-2025 10:11:18","Cascad=
ed Incident from TTO5664503","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site down because gen failed=
 to start due to it battery charger faulty , Waiting for IHS SS to validate=
 the alternator charger // Grid return","system","296845","15-07-2025 09:39=
:50","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0005483898","Yok=
o MTN","IHS_YND_475","15-07-2025 09:37:42","15-07-2025 09:36:30","15-07-202=
5 10:11:18","Grid outage, site down because gen failed to start due to it b=
attery charger faulty , Waiting for IHS SS to validate the alternator charg=
er // Grid return","Parker Tchoup","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Charging Alternator","Grid outage, site down because gen failed to =
start due to it battery charger faulty , Waiting for IHS SS to validate the=
 alternator charger // Grid return","cedric.tiani@matech-cameroun.com","73"=
,"15-07-2025 09:37:42","MATECH CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0005483662","A=
nguissa New","","15-07-2025 08:53:17","15-07-2025 08:52:06","15-07-2025 08:=
56:33","No power issue, site is on grid with Ubaie=3D53V, Eloundou bertrant=
(652586578) from Huawei is informed","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53V, Eloundou bertrant(652586578) from H=
uawei is informed","vanel.mbiada@matech-cameroun.com","73","15-07-2025 08:5=
3:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005483596","Messassi=
 okolo","","15-07-2025 08:39:25","15-07-2025 08:38:37","15-07-2025 14:57:27=
","Cascaded Incident from TTO5664155","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
cause LL inhibited the start of GEN due to noise // Grid return","system","=
285933","15-07-2025 08:39:25","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005483591","E=
MANA BILICK CITY","IHS_YND_279","15-07-2025 08:38:49","15-07-2025 08:38:37"=
,"15-07-2025 15:02:17","Grid outage, Site went down because LL inhibited th=
e start of GEN due to noise // Grid return","Fabrice Pouakam","Access Denia=
l","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","G=
rid outage, Site went down because LL inhibited the start of GEN due to noi=
se // Grid return","vanel.mbiada@matech-cameroun.com","14","15-07-2025 08:3=
8:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005483526","Mfou EPC=
","","15-07-2025 08:26:30","15-07-2025 08:18:13","15-07-2025 08:23:22","Cas=
caded Incident from TTO5664067","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","265668","15-07-2025 08=
:26:30","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005483508","M=
fou OCM","IHS_YND_674","15-07-2025 08:23:24","15-07-2025 08:18:13","15-07-2=
025 08:23:22","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","vanel.mbiada@matech-cameroun.com"=
,"313","15-07-2025 08:23:24","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005483507","Awa=
e Ewonkan","","15-07-2025 08:23:18","15-07-2025 08:15:06","15-07-2025 08:23=
:27","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)IHS=
 SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to =
Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid return"=
,"cedric.tiani@matech-cameroun.com","494","15-07-2025 08:23:18","MATECH CMR=
"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005483416","N=
kolso","","15-07-2025 08:04:03","15-07-2025 08:02:57","15-07-2025 08:08:34"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage(No Neutral)// He bypassed the Grid and site on Gen","TIENTCHEU N=
ZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, Site went down because gen fails to start d=
ue to grid bad voltage(No Neutral)// He bypassed the Grid and site on Gen",=
"vanel.mbiada@matech-cameroun.com","68","15-07-2025 08:04:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005483263","MEHANDAN=
","","15-07-2025 07:26:10","15-07-2025 07:22:15","15-07-2025 07:30:52","Cas=
caded Incident from TTO5663788","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
269000","15-07-2025 07:26:10","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005483259","O=
dza II OCM","IHS_YND_528","15-07-2025 07:25:28","15-07-2025 07:22:15","15-0=
7-2025 07:30:52","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","vanel.mbiada@matech-cameroun.com","197","15-07-2025 07:25:28",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005483158","B=
arriere","","15-07-2025 06:58:31","15-07-2025 06:56:38","15-07-2025 07:02:0=
7","No power issue on site Ubay: 53.2V site on Gen .TX Fme Flubert (6542660=
68/Huawei) is informed","Hyemafo Gildas","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 Ubay: 53.2V site on Gen .TX Fme Flubert (654266068/Huawei) is informed","v=
anel.mbiada@matech-cameroun.com","115","15-07-2025 06:58:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005482986","C-Suprem=
e","","15-07-2025 06:12:50","15-07-2025 06:09:29","15-07-2025 07:01:34","Ca=
scaded Incident from TTO5663482","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k)//Site stabilised","system","287676","15-07-2025 06:12:50",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005482984","M=
vog Mbi New","IHS_YND_021","15-07-2025 06:11:54","15-07-2025 06:09:29","15-=
07-2025 07:01:34","Grid fluctuations ,Site Went down due to PWC overload, (=
210A ,12k)//Site stabilised","MINKA NICOLAS","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Grid fluctuations ,Site Went down=
 due to PWC overload, (210A ,12k)//Site stabilised","gaelle.njiofack@matech=
-cameroun.com","146","15-07-2025 06:11:54","MATECH CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0005482657","N=
KONGKARAK","","15-07-2025 03:48:31","15-07-2025 03:40:24","15-07-2025 06:10=
:10","Grid outage, Site went down because Gen started and stopped due to Hi=
gh temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU=
 GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Grid outage, Site went down because Gen started and st=
opped due to High temp alarm //He added water and Gen start manually","gael=
le.njiofack@matech-cameroun.com","488","15-07-2025 03:48:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005482469","Ngoum","=
","15-07-2025 02:04:21","15-07-2025 02:00:27","15-07-2025 03:21:59","Cascad=
ed Incident from TTO5662925","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site down because gen fails =
to start due to it  battery charger faulty , Waiting for IHS SS  to validat=
e the alternator charger  // Grid return","system","273853","15-07-2025 02:=
04:21","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0005482465","Yok=
o MTN","IHS_YND_475","15-07-2025 02:03:33","15-07-2025 02:00:27","15-07-202=
5 03:21:59","Grid outage, site down because gen fails to start due to it  b=
attery charger faulty , Waiting for IHS SS  to validate the alternator char=
ger  // Grid return","Parker Tchoup","Equipment Repair","Passive","ACDG Gen=
","ACDG - Charging Alternator","Grid outage, site down because gen fails to=
 start due to it  battery charger faulty , Waiting for IHS SS  to validate =
the alternator charger  // Grid return","franck.nkomot@matech-cameroun.com"=
,"187","15-07-2025 02:03:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005482378","C-Suprem=
e","","15-07-2025 01:17:11","15-07-2025 00:56:03","15-07-2025 01:54:48","Ca=
scaded Incident from TTO5662755","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","( Very unstable site ) Grid fluctuations ,Site Wen=
t down due to PWC overload, (210A ,12k).// Grid stabilised","system","27770=
8","15-07-2025 01:17:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005482377","Olezoa O=
CM","","15-07-2025 01:17:10","15-07-2025 00:56:03","15-07-2025 01:54:48","C=
ascaded Incident from TTO5662755","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","( Very unstable site ) Grid fluctuations ,Site We=
nt down due to PWC overload, (210A ,12k).// Grid stabilised","system","2777=
09","15-07-2025 01:17:10","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005482306","M=
vog Mbi New","IHS_YND_055, IHS_YND_021","15-07-2025 00:59:10","15-07-2025 0=
0:56:03","15-07-2025 01:54:48","( Very unstable site ) Grid fluctuations ,S=
ite Went down due to PWC overload, (210A ,12k).// Grid stabilised","MINKA N=
ICOLAS","Grid Supply","Passive","Grid","National Grid - Unstable Grid Suppl=
y Issue","( Very unstable site ) Grid fluctuations ,Site Went down due to P=
WC overload, (210A ,12k).// Grid stabilised","gaelle.njiofack@matech-camero=
un.com","188","15-07-2025 00:59:10","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005482076","N=
kolbong","","14-07-2025 23:44:56","14-07-2025 23:44:52","15-07-2025 00:08:0=
0","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","6","14-07-2025 23:44:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005482026","Acropole=
","","14-07-2025 23:26:41","14-07-2025 22:48:39","15-07-2025 00:41:48","Cas=
caded Incident from TTO5662291","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","( Very unstable site ) Grid fluctuatio=
ns ,Site Went down due to PWC overload, (210A ,12k).// Grid stabilised","sy=
stem","270972","14-07-2025 23:26:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005482025","Olezoa O=
CM","","14-07-2025 23:26:40","14-07-2025 22:48:39","15-07-2025 00:41:48","C=
ascaded Incident from TTO5662291","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","( Very unstable site ) Grid fluctuations ,Site We=
nt down due to PWC overload, (210A ,12k).// Grid stabilised","system","2709=
73","14-07-2025 23:26:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005482004","MBIMBIM"=
,"","14-07-2025 23:21:42","14-07-2025 22:42:15","15-07-2025 00:40:15","Casc=
aded Incident from TTO5662274","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybride Module malfunction. // Reset an=
d Manual start of Gen.","system","271356","14-07-2025 23:21:42","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005482003","Ngouetou=
","","14-07-2025 23:21:42","14-07-2025 22:42:15","15-07-2025 00:40:15","Cas=
caded Incident from TTO5662274","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybride Module malfunction. // Reset a=
nd Manual start of Gen.","system","271356","14-07-2025 23:21:42","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005482000","Ngoum","=
","14-07-2025 23:21:41","14-07-2025 22:42:15","15-07-2025 00:40:15","Cascad=
ed Incident from TTO5662274","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Hybride Module malfunction. // Reset and =
Manual start of Gen.","system","271358","14-07-2025 23:21:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005482001","Matsari"=
,"","14-07-2025 23:21:41","14-07-2025 22:42:15","15-07-2025 00:40:15","Casc=
aded Incident from TTO5662274","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybride Module malfunction. // Reset an=
d Manual start of Gen.","system","271357","14-07-2025 23:21:41","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005482002","Yoko OCM=
","","14-07-2025 23:21:41","14-07-2025 22:42:15","15-07-2025 00:40:15","Cas=
caded Incident from TTO5662274","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybride Module malfunction. // Reset a=
nd Manual start of Gen.","system","271355","14-07-2025 23:21:41","MATECH CM=
R"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005481892","B=
arriere","","14-07-2025 22:57:26","14-07-2025 22:53:21","14-07-2025 23:00:4=
4"," No power issue on site Ubay: 53.2V site on Gen .TX Fme Flubert (654266=
068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm"," No power issue on si=
te Ubay: 53.2V site on Gen .TX Fme Flubert (654266068/Huawei) is informed",=
"gaelle.njiofack@matech-cameroun.com","247","14-07-2025 22:57:26","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005481884","C-Suprem=
e","","14-07-2025 22:54:00","14-07-2025 22:48:39","15-07-2025 00:41:48","Ca=
scaded Incident from TTO5662291","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","( Very unstable site ) Grid fluctuations ,Site Wen=
t down due to PWC overload, (210A ,12k).// Grid stabilised","system","27097=
1","14-07-2025 22:54:00","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005481878","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","14-07-2025 22:52:52",=
"14-07-2025 22:48:39","15-07-2025 00:41:48","( Very unstable site ) Grid fl=
uctuations ,Site Went down due to PWC overload, (210A ,12k).// Grid stabili=
sed","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Unstab=
le Grid Supply Issue","( Very unstable site ) Grid fluctuations ,Site Went =
down due to PWC overload, (210A ,12k).// Grid stabilised","gaelle.njiofack@=
matech-cameroun.com","254","14-07-2025 22:52:52","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005481783","N=
kolbong","","14-07-2025 22:27:54","14-07-2025 22:27:44","14-07-2025 22:46:5=
9","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","loic.no=
umsi@matech-cameroun.com","12","14-07-2025 22:27:54","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005481612","TON=
GOLO SNEC","","14-07-2025 21:54:28","14-07-2025 21:49:23","14-07-2025 21:59=
:30","Grid outage, site went down because Gen failed to start due to poor b=
attery backup // site stabilised","Fabrice Pouakam","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down because Gen failed to start due to poor battery backup // site stabil=
ised","loic.noumsi@matech-cameroun.com","305","14-07-2025 21:54:28","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_553","IHS_YND_686","NOCINC0005481500","O=
yomabang Ecole","","14-07-2025 21:36:37","14-07-2025 21:34:26","14-07-2025 =
23:50:23","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mo=
uhamadou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mouh=
amadou (6144435) from Huawei is informed.","gaelle.njiofack@matech-cameroun=
.com","132","14-07-2025 21:36:37","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005481447","N=
kolbong","","14-07-2025 21:31:23","14-07-2025 21:30:12","14-07-2025 21:50:3=
8","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)","Delor Telezing","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","	Grid outage,Site went Down because Gen started and =
stopped due to Gen overload(22kva//350A)//Grid return","loic.noumsi@matech-=
cameroun.com","73","14-07-2025 21:31:23","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005481427","NKO=
MKANA ELIZA HOTEL","","14-07-2025 21:29:43","14-07-2025 21:25:35","14-07-20=
25 21:33:25","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed //Site stabilised","","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site went down due to PWC Overloaded and S=
S IHS Bernard Atangana confirmed //Site stabilised","loic.noumsi@matech-cam=
eroun.com","249","14-07-2025 21:29:43","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005481262","N=
KOLMEKONG YDE","","14-07-2025 21:01:18","14-07-2025 20:58:02","14-07-2025 2=
1:49:56","Active//No power issue on site Ubaie =3D52V site on Grid The TX F=
ME Synphorien (650257151) from Huawei is informed and he will be on site to=
morrow with  our FME Giresse for more investigation","Fabrice Pouakam","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active//No power issue on site Ubaie =3D52V site on Grid The TX FME=
 Synphorien (650257151) from Huawei is informed and he will be on site tomo=
rrow with  our FME Giresse for more investigation","gaelle.njiofack@matech-=
cameroun.com","197","14-07-2025 21:01:18","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005481240","M=
vog Mbi New","","14-07-2025 20:54:29","14-07-2025 20:51:23","14-07-2025 20:=
53:17","( Very unstable site ) Grid fluctuations ,Site Went down due to PWC=
 overload, (210A ,12k).// Grid stabilised","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","( Very unstable site ) Grid fluc=
tuations ,Site Went down due to PWC overload, (210A ,12k).// Grid stabilise=
d","loic.noumsi@matech-cameroun.com","188","14-07-2025 20:54:29","MATECH CM=
R"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005481137","N=
kolbong","","14-07-2025 20:36:23","14-07-2025 20:34:14","14-07-2025 20:57:5=
3","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","131","14-07-2025 20:36:23","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005481127","Bit=
eng-Maetur","","14-07-2025 20:33:56","14-07-2025 20:31:51","14-07-2025 20:5=
2:33","Grid outage site went down because Gen failed to start due PWC ZTE d=
ysfunctioned // Grid return","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Grid outage site went down bec=
ause Gen failed to start due PWC ZTE dysfunctioned // Grid return","loic.no=
umsi@matech-cameroun.com","126","14-07-2025 20:33:56","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005481061","M=
ontee-Des-Soeurs","","14-07-2025 20:21:35","14-07-2025 20:19:27","14-07-202=
5 20:47:20","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","gaelle.njiofack@matech-cameroun.com","130","14-07-2025 20:21:3=
5","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005480590","M=
vog Mbi New","","14-07-2025 19:07:33","14-07-2025 19:04:28","14-07-2025 19:=
42:31","( Very unstable site ) Grid fluctuations ,Site Went down due to PWC=
 overload, (210A ,12k).// Grid stabilised","MINKA NICOLAS","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","( Very unstable sit=
e ) Grid fluctuations ,Site Went down due to PWC overload, (210A ,12k).// G=
rid stabilised","loic.noumsi@matech-cameroun.com","187","14-07-2025 19:07:3=
3","MATECH CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0005480332","CLE=
 Building","","14-07-2025 18:37:36","14-07-2025 18:35:30","14-07-2025 19:43=
:52","Grid outage, no space to deploy MDGE // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spac=
e to deploy MDGE // Grid return","loic.noumsi@matech-cameroun.com","127","1=
4-07-2025 18:37:36","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005480211","NKO=
MKANA ELIZA HOTEL","","14-07-2025 18:22:31","14-07-2025 18:20:25","14-07-20=
25 18:22:21","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed //Site stabilised","","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site went down due to PWC Overloaded and S=
S IHS Bernard Atangana confirmed //Site stabilised","loic.noumsi@matech-cam=
eroun.com","127","14-07-2025 18:22:31","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005480198","TON=
GOLO SNEC","","14-07-2025 18:20:03","14-07-2025 18:17:55","14-07-2025 18:35=
:25","Grid fluctuations, site went down due to grid bad voltage and no rcp =
on site // He bypassed Grid and started Gen manually","Fabrice Pouakam","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuations, site went down due to grid bad voltage and no rcp on site //=
 He bypassed Grid and started Gen manually","loic.noumsi@matech-cameroun.co=
m","129","14-07-2025 18:20:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005480009","MEHANDAN=
","","14-07-2025 17:43:50","14-07-2025 17:40:02","14-07-2025 17:43:09","Cas=
caded Incident from TTO5660321","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction//Site stabilised","system","26=
0875","14-07-2025 17:43:50","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005480003","O=
dza II OCM","IHS_YND_528","14-07-2025 17:43:07","14-07-2025 17:40:02","14-0=
7-2025 17:43:40","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction//Site st=
abilised","loic.noumsi@matech-cameroun.com","188","14-07-2025 17:43:07","MA=
TECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005479982","NKO=
MKANA ELIZA HOTEL","","14-07-2025 17:38:34","14-07-2025 17:36:29","14-07-20=
25 17:38:01","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed //Site stabilised","","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site went down due to PWC Overloaded and S=
S IHS Bernard Atangana confirmed //Site stabilised","loic.noumsi@matech-cam=
eroun.com","127","14-07-2025 17:38:34","MATECH CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0005479881","A=
nguissa New","","14-07-2025 17:15:11","14-07-2025 17:10:04","14-07-2025 17:=
30:59","No power issue, site is on grid with Ubaie=3D53V, Eloundou bertrant=
(652586578) from Huawei is informed","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53V, Eloundou bertrant(652586578) from H=
uawei is informed","gaelle.njiofack@matech-cameroun.com","309","14-07-2025 =
17:15:11","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005479868","L=
abogenie","","14-07-2025 17:10:43","14-07-2025 17:07:21","14-07-2025 17:10:=
21","No power issue U =3D54,5V site on Grid. The Tx FME Eloundou (693212405=
 )from Huawei is informed.","","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D54,5V site o=
n Grid. The Tx FME Eloundou (693212405 )from Huawei is informed.","gaelle.n=
jiofack@matech-cameroun.com","203","14-07-2025 17:10:43","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005479848","TON=
GOLO SNEC","","14-07-2025 17:05:30","14-07-2025 17:02:21","14-07-2025 17:12=
:47","Grid fluctuations, site went down due to grid bad voltage and no rcp =
on site // He bypassed Grid and started Gen manually","Fabrice Pouakam","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuations, site went down due to grid bad voltage and no rcp on site //=
 He bypassed Grid and started Gen manually","loic.noumsi@matech-cameroun.co=
m","190","14-07-2025 17:05:30","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005479645","M=
vog Mbi New","","14-07-2025 16:32:07","14-07-2025 16:29:00","14-07-2025 17:=
50:12","( Very unstable site ) Grid fluctuations ,Site Went down due to PWC=
 overload, (210A ,12k).// Grid stabilised","MINKA NICOLAS","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","( Very unstable sit=
e ) Grid fluctuations ,Site Went down due to PWC overload, (210A ,12k).// G=
rid stabilised","loic.noumsi@matech-cameroun.com","189","14-07-2025 16:32:0=
7","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005479601","C=
NR","","14-07-2025 16:22:05","14-07-2025 16:20:59","14-07-2025 16:37:45","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed automatically","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","	Grid outage, Site went down before Gen =
start due to poor backup // Gen started automatically","gaelle.njiofack@mat=
ech-cameroun.com","67","14-07-2025 16:22:05","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005479573","A=
kak-Nkozoa-MTN-IHS","","14-07-2025 16:18:10","14-07-2025 16:14:04","14-07-2=
025 17:28:28","Grid outage,Site went down because Gen started and stopped d=
ue to alarm ""oil pressure""// He reset DG card and started Gen manually","=
Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage,Site went down because Gen started and stopped due to ala=
rm ""oil pressure""// He reset DG card and started Gen manually","gaelle.nj=
iofack@matech-cameroun.com","249","14-07-2025 16:18:10","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005479437","Eto=
ug ebe Meweulo","","14-07-2025 16:11:12","14-07-2025 16:10:08","14-07-2025 =
17:17:47","Grid outage, site went down due to Grid fluctuations on site and=
 no rcp // He bypassed GRID and started Gen manually","Hyemafo Gildas","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
outage, site went down due to Grid fluctuations on site and no rcp // He by=
passed GRID and started Gen manually","loic.noumsi@matech-cameroun.com","65=
","14-07-2025 16:11:12","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005479234","B=
arriere","","14-07-2025 15:28:47","14-07-2025 15:26:42","14-07-2025 20:44:1=
6","Active // No power issue on site Ubay: 53.45V site on Gen .TX Fme Flube=
rt (654266068/Huawei) is informed","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue on site Ubay: 53.45V site on Gen .TX Fme Flubert (654266068/H=
uawei) is informed","gaelle.njiofack@matech-cameroun.com","128","14-07-2025=
 15:28:47","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005479188","F=
ouda-New","","14-07-2025 15:20:17","14-07-2025 15:18:08","14-07-2025 15:54:=
40","Grid Fluctuation, site went down before Gen start due to Poor battery =
backup // Gen start automatically","Delor Telezing","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuation, site=
 went down before Gen start due to Poor battery backup // Gen start automat=
ically","gaelle.njiofack@matech-cameroun.com","130","14-07-2025 15:20:17","=
MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005479111","N=
kolbong","","14-07-2025 15:08:41","14-07-2025 15:06:32","14-07-2025 19:56:4=
6","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","131","14-07-2025 15:08:41","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005479077","Mok=
olo Yaounde","","14-07-2025 15:02:13","14-07-2025 14:59:59","14-07-2025 15:=
03:03","Grid only site, no space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e, no space to deploy MDGE // Grid returned","loic.noumsi@matech-cameroun.c=
om","136","14-07-2025 15:02:13","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005478904","C=
-Supreme","","14-07-2025 14:41:22","14-07-2025 14:39:14","14-07-2025 14:43:=
43","No power issue, site on Grid with Ubaie=3D54.5V, Brice Tsague (650 21 =
40 96 / Huawei) is informed","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue, site on Grid wi=
th Ubaie=3D54.5V, Brice Tsague (650 21 40 96 / Huawei) is informed","gaelle=
.njiofack@matech-cameroun.com","129","14-07-2025 14:41:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005478852","Messassi=
 okolo","","14-07-2025 14:30:50","14-07-2025 14:26:43","14-07-2025 19:54:38=
","Cascaded Incident from TTO5659013","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
cause LL inhibited the start of GEN due to noise // Grid return","system","=
279507","14-07-2025 14:30:50","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005478843","EMA=
NA BILICK CITY","IHS_YND_279","14-07-2025 14:29:15","14-07-2025 14:26:43","=
14-07-2025 20:00:19","Grid outage, Site went down because LL inhibited the =
start of GEN due to noise // Grid return","Fabrice Pouakam","Access Denial"=
,"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Gri=
d outage, Site went down because LL inhibited the start of GEN due to noise=
 // Grid return","gaelle.njiofack@matech-cameroun.com","154","14-07-2025 14=
:29:15","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005478218","Bar=
riere","","14-07-2025 13:26:28","14-07-2025 13:23:09","14-07-2025 13:26:09"=
,"Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS Fel=
ix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because =
Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised",=
"cedric.tiani@matech-cameroun.com","201","14-07-2025 13:26:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005477959","MEHANDAN=
","","14-07-2025 12:50:20","14-07-2025 12:44:48","14-07-2025 12:52:07","Cas=
caded Incident from TTO5658186","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction//Site stabilised","system","26=
4159","14-07-2025 12:50:20","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005477939","O=
dza II OCM","IHS_YND_528","14-07-2025 12:49:02","14-07-2025 12:44:48","14-0=
7-2025 12:52:07","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction//Site stabilised","Albran Byorel","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site =
went down because gen failed to start due to PWC ZTE malfunction//Site stab=
ilised","vanel.mbiada@matech-cameroun.com","258","14-07-2025 12:49:02","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_632","IHS_YND_721","NOCINC0005477918","V=
OIRIE MUNICIPALE YAOUNDE","","14-07-2025 12:45:10","14-07-2025 12:44:42","1=
4-07-2025 13:06:04","Site went down due to work: Duclaire(GAIO TELEMETRIE) =
680685526 working on site // end of work","Paul BIBOUM","Installation Activ=
ity","Passive","Planned Activity","Installation Activity","Site went down d=
ue to work: Duclaire(GAIO TELEMETRIE) 680685526 working on site // end of w=
ork","vanel.mbiada@matech-cameroun.com","29","14-07-2025 12:45:10","MATECH =
CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005477649","Fla=
menco","","14-07-2025 12:01:02","14-07-2025 11:54:46","14-07-2025 12:10:35"=
,"Grid outage, site went down because Gen failed to start due to poor backu=
p // / Gen start automatically","Mboua Thierry","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n because Gen failed to start due to poor backup // / Gen start automatical=
ly","cedric.tiani@matech-cameroun.com","377","14-07-2025 12:01:02","MATECH =
CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005477647","Men=
dong Plateau","","14-07-2025 12:00:31","14-07-2025 11:57:16","14-07-2025 12=
:06:02","No power issue site on grid with U=3D50.7v Mbah Osiah(674007438) f=
rom Huaweio is informed","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site o=
n grid with U=3D50.7v Mbah Osiah(674007438) from Huaweio is informed","cedr=
ic.tiani@matech-cameroun.com","196","14-07-2025 12:00:31","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005477643","NKO=
MKANA ELIZA HOTEL","","14-07-2025 11:59:55","14-07-2025 11:55:45","14-07-20=
25 12:07:20","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed //Site stabilised","","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site went down due to PWC Overloaded and S=
S IHS Bernard Atangana confirmed //Site stabilised","cedric.tiani@matech-ca=
meroun.com","251","14-07-2025 11:59:55","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005477598","C=
NR","","14-07-2025 11:51:45","14-07-2025 11:50:35","14-07-2025 11:56:03","N=
o power issue site on grid with U=3D53.8V Brice (650214096) from Huaie is i=
nformed","Mboua Thierry","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D5=
3.8V Brice (650214096) from Huaie is informed","vanel.mbiada@matech-camerou=
n.com","71","14-07-2025 11:51:45","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005477277","NKO=
MKANA ELIZA HOTEL","","14-07-2025 11:04:01","14-07-2025 11:02:06","14-07-20=
25 11:04:28","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","cedric.tiani@matech-=
cameroun.com","116","14-07-2025 11:04:01","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005477255","A=
kak-Nkozoa-MTN-IHS","","14-07-2025 11:00:34","14-07-2025 10:59:11","14-07-2=
025 11:05:12","","Fabrice Pouakam","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","No power issue on site Ubaie: 53,7V site on Grid. Symp=
horien (675295205/Huawei) is informed.","vanel.mbiada@matech-cameroun.com",=
"277529","14-07-2025 11:00:34","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005477160","E=
bogo","","14-07-2025 10:48:48","14-07-2025 10:46:23","14-07-2025 11:25:37",=
"Site went down due to PWC dysunction//He reset it and site on Gen","Siliga=
p Boris","Equipment Repair","Passive","Rectifier","Rectifier Module","Site =
went down due to PWC dysunction//He reset it and site on Gen","vanel.mbiada=
@matech-cameroun.com","146","14-07-2025 10:48:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005477011","MEHANDAN=
","","14-07-2025 10:27:30","14-07-2025 10:24:46","14-07-2025 10:26:11","Cas=
caded Incident from TTO5657124","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction //Site stabilised","system","2=
65330","14-07-2025 10:27:30","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005477001","O=
dza II OCM","IHS_YND_528","14-07-2025 10:25:44","14-07-2025 10:24:46","14-0=
7-2025 10:26:11","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction //Site stabilised","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down because gen failed to start due to PWC ZTE malfunction //Site st=
abilised","vanel.mbiada@matech-cameroun.com","62","14-07-2025 10:25:44","MA=
TECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005476981","NYO=
M FACE MAETUR","","14-07-2025 10:24:00","14-07-2025 10:22:47","14-07-2025 1=
0:24:59","Grid outage, Site went down before Gen start due to poor backup /=
/ Grid return","Fabrice Pouakam","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","cedric.tiani@matech-cameroun.com","=
76","14-07-2025 10:24:00","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005476939","Odz=
a II OCM","","14-07-2025 10:18:54","14-07-2025 10:18:44","14-07-2025 10:19:=
12","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction /Site stabilised","Albran Byorel","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage, site went down bec=
ause gen failed to start due to PWC ZTE malfunction /Site stabilised","cedr=
ic.tiani@matech-cameroun.com","12","14-07-2025 10:18:54","MATECH CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0005476691","S=
apeur","","14-07-2025 09:47:45","14-07-2025 09:45:34","14-07-2025 09:48:00"=
,"No power issue on site U=3D53.5V site on grid Tx Fme BRICE (650214096) of=
 huawei is informed","Mboua Thierry","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53.5V site on grid Tx Fme BRICE (650214096) of huawei is informed","vane=
l.mbiada@matech-cameroun.com","134","14-07-2025 09:47:45","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005476587","C=
-Supreme","","14-07-2025 09:36:00","14-07-2025 09:34:50","14-07-2025 09:37:=
02","No power issue, site on Grid with Ubaie=3D54.5V, Brice Tsague (650 21 =
40 96 / Huawei) is informed","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue, site on Grid wi=
th Ubaie=3D54.5V, Brice Tsague (650 21 40 96 / Huawei) is informed","vanel.=
mbiada@matech-cameroun.com","71","14-07-2025 09:36:00","MATECH CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0005476574","E=
seka Town","","14-07-2025 09:32:19","14-07-2025 09:30:52","14-07-2025 09:33=
:10","Active// No power issue, Site on Gen Ubaie:50V, The FME Tx Etienne/69=
5033981 From Huawei is informed","Kemeni Franklin","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No =
power issue, Site on Gen Ubaie:50V, The FME Tx Etienne/695033981 From Huawe=
i is informed","vanel.mbiada@matech-cameroun.com","89","14-07-2025 09:32:19=
","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005476479","NYO=
M FACE MAETUR","","14-07-2025 09:11:00","14-07-2025 09:09:47","14-07-2025 0=
9:11:22","Grid outage, Site went down before Gen start due to poor backup /=
/ Gen started Manually","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen started Manually","cedric.tiani@mate=
ch-cameroun.com","75","14-07-2025 09:11:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005476288","Mfou EPC=
","","14-07-2025 08:28:59","14-07-2025 08:24:45","14-07-2025 08:29:10","Cas=
caded Incident from TTO5656322","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","265297","14-07-2025 08=
:28:59","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005476282","M=
fou OCM","IHS_YND_674","14-07-2025 08:27:54","14-07-2025 08:24:45","14-07-2=
025 08:29:10","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","vanel.mbiada@matech-cameroun.com"=
,"190","14-07-2025 08:27:54","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005476057","E=
bogo","","14-07-2025 07:22:54","14-07-2025 07:21:42","14-07-2025 07:41:29",=
"Site went down due to PWC dysunction//He reset it and site on Grid","Silig=
ap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module Overlo=
aded","Site went down due to PWC dysunction//He reset it and site on Grid",=
"vanel.mbiada@matech-cameroun.com","73","14-07-2025 07:22:54","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005476033","B=
arriere","","14-07-2025 07:19:39","14-07-2025 07:18:23","14-07-2025 07:21:1=
0","Grid fluctuations, Site went down because Gen overload (30kva, 410A) SS=
 IHS Felix ZAMBE confirmed // Grid stabilized","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, Site wen=
t down because Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // G=
rid stabilized","vanel.mbiada@matech-cameroun.com","79","14-07-2025 07:19:3=
9","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005475833","B=
arriere","","14-07-2025 06:34:20","14-07-2025 06:32:07","14-07-2025 06:51:4=
8","Grid fluctuations, Site went down because Gen overload (30kva, 410A) SS=
 IHS Felix ZAMBE confirmed // Grid stabilized","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, Site wen=
t down because Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // G=
rid stabilized","edwige.kapawo@matech-cameroun.com","136","14-07-2025 06:34=
:20","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005475655","M=
ontee-Des-Soeurs","","14-07-2025 06:07:26","14-07-2025 06:02:17","14-07-202=
5 13:45:37","Grid outage ,site down due to Gen overload (15 KVA/210 A)  // =
Grid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A)  //=
 Grid return","edwige.kapawo@matech-cameroun.com","311","14-07-2025 06:07:2=
6","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005475090","M=
ontee-Des-Soeurs","","14-07-2025 04:12:30","14-07-2025 04:10:24","14-07-202=
5 05:56:40","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","edwige.kapawo@matech-cameroun.com","128","14-07-2025 04:12:30"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005475065","O=
dza II OCM","","14-07-2025 04:08:35","14-07-2025 04:02:20","14-07-2025 04:0=
5:50","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction//Site stabilised","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, site went down b=
ecause gen failed to start due to PWC ZTE malfunction//Site stabilised","ed=
wige.kapawo@matech-cameroun.com","379","14-07-2025 04:08:35","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005475063","A=
wae Ewonkan","","14-07-2025 04:07:25","14-07-2025 03:57:59","14-07-2025 04:=
07:10","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid retur=
n","edwige.kapawo@matech-cameroun.com","568","14-07-2025 04:07:25","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005475003","Mfou EPC=
","","14-07-2025 03:59:20","14-07-2025 03:51:05","14-07-2025 04:06:20","Cas=
caded Incident from TTO5655380","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","267204","14-07-2025 03=
:59:20","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005474972","M=
fou OCM","IHS_YND_674","14-07-2025 03:57:15","14-07-2025 03:51:05","14-07-2=
025 04:06:20","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","edwige.kapawo@matech-cameroun.com=
","371","14-07-2025 03:57:15","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005473242","N=
kolbong","","13-07-2025 23:18:02","13-07-2025 23:16:50","13-07-2025 23:46:2=
5","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid returnurn","edwi=
ge.kapawo@matech-cameroun.com","74","13-07-2025 23:18:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005473067","C-Suprem=
e","","13-07-2025 22:42:41","13-07-2025 22:41:50","13-07-2025 23:56:08","Ca=
scaded Incident from TTO5654410","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","( Very unstable site ) Grid fluctuations ,Site Wen=
t down due to PWC overload, (210A ,12k).// Grid stabilised","system","27136=
7","13-07-2025 22:42:41","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005473059","M=
vog Mbi New","IHS_YND_021","13-07-2025 22:41:55","13-07-2025 22:41:50","13-=
07-2025 23:56:08","( Very unstable site ) Grid fluctuations ,Site Went down=
 due to PWC overload, (210A ,12k).// Grid stabilised","MINKA NICOLAS","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","( Very u=
nstable site ) Grid fluctuations ,Site Went down due to PWC overload, (210A=
 ,12k).// Grid stabilised","edwige.kapawo@matech-cameroun.com","7","13-07-2=
025 22:41:55","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005472607","N=
kolbong","","13-07-2025 21:24:31","13-07-2025 21:18:24","13-07-2025 22:36:2=
4","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","369","13-07-2025 21:24:31","MATECH CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0005472602","O=
kolo","","13-07-2025 21:23:56","13-07-2025 21:18:49","13-07-2025 23:02:39",=
"Site went down due to PSC3 Controller dysfunctionning// He reset it","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Site went down due to PSC3 Controller dysfunctionning// He reset it","gae=
lle.njiofack@matech-cameroun.com","308","13-07-2025 21:23:56","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005472414","SIM=
BOCK BONAMBAPE","","13-07-2025 20:56:38","13-07-2025 20:47:59","13-07-2025 =
20:48:59","Active // No power issue site on grid with Ubaie: 49.5V TX FME F=
lubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive // No power issue site on grid with Ubaie: 49.5V TX FME Flubert (65426=
6068) from Huawei is informed","franck.nkomot@matech-cameroun.com","520","1=
3-07-2025 20:56:38","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005472366","M=
EFOU ASSI","","13-07-2025 20:49:49","13-07-2025 20:47:43","13-07-2025 20:49=
:22","Grid outage, Site went down before Gen start due to poor backup // Gr=
id returned","Fanda Brice","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","gaelle.njiofack@matech-cameroun.com","1=
28","13-07-2025 20:49:49","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005472333","E=
bogo","","13-07-2025 20:43:19","13-07-2025 20:38:10","13-07-2025 21:18:54",=
"Grid outage, site down because gen ran until fuel shortage // tank incline=
, refueling in progress","Siligap Boris","Fuel Outage","Passive","Diesel","=
Diesel Outage","Grid outage, site down because gen ran until fuel shortage =
// tank incline, refueling in progress","gaelle.njiofack@matech-cameroun.co=
m","310","13-07-2025 20:43:19","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005472266","N=
kolbong","","13-07-2025 20:30:08","13-07-2025 20:26:01","13-07-2025 20:48:5=
1","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","249","13-07-2025 20:30:08","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005472242","Nko=
langaa","","13-07-2025 20:26:11","13-07-2025 20:20:00","13-07-2025 22:11:33=
","Site down due to disjonction in the DC Box // DC box CB reamed, site on =
grid.","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Cir=
cuit Breaker Tripped","Site down due to disjonction in the DC Box // DC box=
 CB reamed, site on grid.","franck.nkomot@matech-cameroun.com","372","13-07=
-2025 20:26:11","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005472236","T=
singa","","13-07-2025 20:25:01","13-07-2025 20:17:30","13-07-2025 21:27:17"=
,"","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid Only, No space to deploy MDGE // Grid returned","gaelle.njiof=
ack@matech-cameroun.com","1234","13-07-2025 20:25:01","MATECH CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0005472233","G=
olf Quater","","13-07-2025 20:24:22","13-07-2025 20:17:30","13-07-2025 21:2=
7:17","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid Only, No space to deploy MDGE // Grid returned","gaelle.=
njiofack@matech-cameroun.com","1311","13-07-2025 20:24:22","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005472225","B=
astos-Nylon","","13-07-2025 20:23:34","13-07-2025 20:17:30","13-07-2025 21:=
27:17","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Only, No space to deploy MDGE // Grid returned","gaelle=
.njiofack@matech-cameroun.com","1287","13-07-2025 20:23:34","MATECH CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0005472216","B=
astos Bethesda","","13-07-2025 20:22:38","13-07-2025 20:17:30","13-07-2025 =
21:27:17","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid Only, No space to deploy MDGE // Grid returned","gae=
lle.njiofack@matech-cameroun.com","1260","13-07-2025 20:22:38","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0005472210","N=
komkana 2","","13-07-2025 20:21:21","13-07-2025 20:17:30","13-07-2025 21:27=
:17","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid Only, No space to deploy MDGE // Grid returned","gaelle.n=
jiofack@matech-cameroun.com","1440","13-07-2025 20:21:21","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0005472204","N=
komkana","IHS_YND_220, IHS_YND_138, IHS_YND_126, IHS_YND_563, IHS_YND_127",=
"13-07-2025 20:20:37","13-07-2025 20:17:30","13-07-2025 22:37:50","Grid Onl=
y, No space to deploy MDGE // Grid returned","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid Only, No space to deploy MDGE=
 // Grid returned","gaelle.njiofack@matech-cameroun.com","189","13-07-2025 =
20:20:37","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005472180","Fla=
menco","","13-07-2025 20:15:15","13-07-2025 20:05:59","13-07-2025 20:28:59"=
,"Site went down because Gen failed to start due to Gen battery stolen //He=
 started with an external battery","Mboua Thierry","Site Asset Theft","Thef=
t","Theft","Generator Battery Theft","Site went down because Gen failed to =
start due to Gen battery stolen //He started with an external battery","fra=
nck.nkomot@matech-cameroun.com","557","13-07-2025 20:15:15","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005472177","NKO=
MKANA ELIZA HOTEL","","13-07-2025 20:14:45","13-07-2025 20:05:49","13-07-20=
25 20:25:49","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","franck.nkomot@matech=
-cameroun.com","537","13-07-2025 20:14:45","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005472070","A=
wae Ewonkan","","13-07-2025 19:52:29","13-07-2025 19:49:10","13-07-2025 22:=
11:58","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid retur=
n","gaelle.njiofack@matech-cameroun.com","201","13-07-2025 19:52:29","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005471967","N=
KOLMEKONG YDE","","13-07-2025 19:37:55","13-07-2025 19:28:44","13-07-2025 1=
9:57:32","Active//No power issue on site Ubaie =3D50V site on Grid The TX F=
ME Synphorien (650257151) from Huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue on site Ubaie =3D50V site on Grid The TX FME S=
ynphorien (650257151) from Huawei is informed","gaelle.njiofack@matech-came=
roun.com","553","13-07-2025 19:37:55","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005471956","Nsi=
meyong","","13-07-2025 19:36:24","13-07-2025 19:29:14","13-07-2025 20:37:14=
","Site went down due to disjuction CB(63A)PWC that feed MTN//He rearmed th=
e CB","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power C=
abinet - Circuit Breaker Issue","Site went down due to disjuction CB(63A)PW=
C that feed MTN//He rearmed the CB","franck.nkomot@matech-cameroun.com","43=
1","13-07-2025 19:36:24","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005471955","N=
kolbong","","13-07-2025 19:36:10","13-07-2025 19:30:00","13-07-2025 19:52:4=
2","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","372","13-07-2025 19:36:10","MATECH CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0005471657","S=
oa-II","","13-07-2025 18:40:19","13-07-2025 18:34:09","13-07-2025 19:03:15"=
,"Site went down due to dysfonction of PWC OF ZTE  // PWC reseted","Siligap=
 Boris","Equipment Repair","Passive","Rectifier","Rectifier Module Overload=
ed","Site went down due to dysfonction of PWC OF ZTE  // PWC reseted","gael=
le.njiofack@matech-cameroun.com","371","13-07-2025 18:40:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005471628","C-Suprem=
e","","13-07-2025 18:37:19","13-07-2025 18:27:51","13-07-2025 21:09:46","Ca=
scaded Incident from TTO5652841","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","( Very unstable site ) Grid fluctuations ,Site Wen=
t down due to PWC overload, (210A ,12k).// Grid stabilised","system","27222=
3","13-07-2025 18:37:19","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005471617","M=
vog Mbi New","IHS_YND_021","13-07-2025 18:35:02","13-07-2025 18:27:51","13-=
07-2025 21:09:46","( Very unstable site ) Grid fluctuations ,Site Went down=
 due to PWC overload, (210A ,12k).// Grid stabilised","MINKA NICOLAS","Grid=
 Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue","( V=
ery unstable site ) Grid fluctuations ,Site Went down due to PWC overload, =
(210A ,12k).// Grid stabilised","gaelle.njiofack@matech-cameroun.com","433"=
,"13-07-2025 18:35:02","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005471591","N=
kolbong","","13-07-2025 18:29:19","13-07-2025 18:26:07","13-07-2025 18:51:0=
2","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","193","13-07-2025 18:29:19","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005471569","B=
arriere","","13-07-2025 18:24:32","13-07-2025 18:17:26","14-07-2025 01:18:2=
2","Active // No power issue on site Ubay: 53.4V site on Gen .TX Fme SAMBA =
(654266058/Huawei) is informed","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No p=
ower issue on site Ubay: 53.4V site on Gen .TX Fme SAMBA (654266058/Huawei)=
 is informed","gaelle.njiofack@matech-cameroun.com","429","13-07-2025 18:24=
:32","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005471404","S=
aa","","13-07-2025 17:45:40","13-07-2025 17:42:21","13-07-2025 18:07:47","G=
rid outage, Site went down because Gen start and stopped with ""High temp""=
 alarm // he added water in the radiator and manually started the Gen manua=
lly","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","Grid outage, Site went down because Gen =
start and stopped with ""High temp"" alarm // he added water in the radiato=
r and manually started the Gen manually","gaelle.njiofack@matech-cameroun.c=
om","201","13-07-2025 17:45:40","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005470979","NKO=
MKANA ELIZA HOTEL","","13-07-2025 16:49:16","13-07-2025 16:39:59","13-07-20=
25 18:29:11","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","franck.nkomot@matech=
-cameroun.com","558","13-07-2025 16:49:16","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005470895","Fla=
menco","","13-07-2025 16:31:02","13-07-2025 16:25:49","13-07-2025 18:31:26"=
,"Site went down because Gen failed to start due to Gen battery stolen //He=
 started with an external battery ","Mboua Thierry","Site Asset Theft","The=
ft","Theft","Generator Battery Theft","Site went down because Gen failed to=
 start due to Gen battery stolen //He started with an external battery ","f=
ranck.nkomot@matech-cameroun.com","314","13-07-2025 16:31:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005470848","C-Suprem=
e","","13-07-2025 16:19:11","13-07-2025 16:17:58","13-07-2025 18:17:05","Ca=
scaded Incident from TTO5652030","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","( Very unstable site ) Grid fluctuations ,Site Wen=
t down due to PWC overload, (210A ,12k).// Grid stabilised	","system","2727=
79","13-07-2025 16:19:11","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005470845","M=
vog Mbi New","IHS_YND_021","13-07-2025 16:18:34","13-07-2025 16:17:58","13-=
07-2025 18:17:05","( Very unstable site ) Grid fluctuations ,Site Went down=
 due to PWC overload, (210A ,12k).// Grid stabilised	","MINKA NICOLAS","Gri=
d Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue","( =
Very unstable site ) Grid fluctuations ,Site Went down due to PWC overload,=
 (210A ,12k).// Grid stabilised	","gaelle.njiofack@matech-cameroun.com","37=
","13-07-2025 16:18:34","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005470681","S=
aa","","13-07-2025 15:51:27","13-07-2025 15:47:15","13-07-2025 16:24:51","G=
rid outage, Site went down because Gen start and stopped with ""High temp""=
 alarm // he added water in the radiator and manually started the Gen manua=
lly","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","Grid outage, Site went down because Gen =
start and stopped with ""High temp"" alarm // he added water in the radiato=
r and manually started the Gen manually","gaelle.njiofack@matech-cameroun.c=
om","254","13-07-2025 15:51:27","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005470538","M=
vog Mbi New","","13-07-2025 15:28:49","13-07-2025 15:28:45","13-07-2025 15:=
29:26"," Grid fluctuations ,Site Went down due to PWC overload, (210A ,12k)=
. // Grid stabilised","MINKA NICOLAS","Grid Supply","Passive","Grid","Natio=
nal Grid - Unstable Grid Supply Issue"," Grid fluctuations ,Site Went down =
due to PWC overload, (210A ,12k). // Grid stabilised","gaelle.njiofack@mate=
ch-cameroun.com","6","13-07-2025 15:28:49","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005470422","C=
-Supreme","","13-07-2025 15:09:34","13-07-2025 15:08:27","13-07-2025 15:40:=
34","No power issue, site on Grid with Ubaie=3D54.5V, Brice Tsague (650 21 =
40 96 / Huawei) is informed","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue, site on Grid wi=
th Ubaie=3D54.5V, Brice Tsague (650 21 40 96 / Huawei) is informed","gaelle=
.njiofack@matech-cameroun.com","68","13-07-2025 15:09:34","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005470405","Fou=
da Quarter","","13-07-2025 15:07:40","13-07-2025 15:03:25","13-07-2025 16:0=
3:07","Grid outage , site went down because gen fails to start due to grid =
bad voltage // Gen manually started","Delor Telezing","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid outage , site wen=
t down because gen fails to start due to grid bad voltage // Gen manually s=
tarted","franck.nkomot@matech-cameroun.com","256","13-07-2025 15:07:40","MA=
TECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005469725","Cit=
e des nations","","13-07-2025 12:50:10","13-07-2025 12:47:04","13-07-2025 1=
2:53:08","Grid outage,site went down before Gen started due to Poor battery=
 backup // Site stabilised","Paul BIBOUM","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","rid outage,site went down before=
 Gen started due to Poor battery backup // Site stabilised","loic.noumsi@ma=
tech-cameroun.com","187","13-07-2025 12:50:10","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005469584","B=
arriere","","13-07-2025 12:17:12","13-07-2025 12:14:55","13-07-2025 13:52:0=
9","Grid fluctuations, Site went down because Gen overload (30kva, 410A) SS=
 IHS Felix ZAMBE confirmed // Grid stabilized","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, Site wen=
t down because Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // G=
rid stabilized","loic.noumsi@matech-cameroun.com","139","13-07-2025 12:17:1=
2","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005469343","Mfou EPC=
","","13-07-2025 11:28:40","13-07-2025 11:17:51","13-07-2025 11:22:28","Cas=
caded Incident from TTO5650311","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","262179","13-07-2025 11=
:28:40","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005469273","M=
fou OCM","IHS_YND_674","13-07-2025 11:19:58","13-07-2025 11:17:51","13-07-2=
025 11:22:28","	Grid Outage, Site Down before gen Started due to poor backu=
p //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen St=
arted due to poor backup //Grid returned","gaelle.njiofack@matech-cameroun.=
com","128","13-07-2025 11:19:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005469244","MEHANDAN=
","","13-07-2025 11:12:50","13-07-2025 11:02:36","13-07-2025 11:06:30","Cas=
caded Incident from TTO5650252","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to PWC ZTE malfunction//Site stabilised","system","2=
63085","13-07-2025 11:12:50","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005469240","NYO=
M FACE MAETUR","","13-07-2025 11:11:54","13-07-2025 11:10:46","13-07-2025 1=
1:12:23","Grid fluctuation , site went down because Gen failed to start due=
 to Grid bad voltage; landlord refuses that we deploy the MGE (gen Noise) /=
/ Grid stabilised","Fabrice Pouakam","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","Grid fluctuation , site went down becau=
se Gen failed to start due to Grid bad voltage; landlord refuses that we de=
ploy the MGE (gen Noise) // Grid stabilised","loic.noumsi@matech-cameroun.c=
om","70","13-07-2025 11:11:54","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005469226","M=
ontee-Des-Soeurs","","13-07-2025 11:08:54","13-07-2025 11:03:47","13-07-202=
5 11:21:41","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","gaelle.njiofack@matech-cameroun.com","309","13-07-2025 11:08:5=
4","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005469221","Awa=
e Ewonkan","","13-07-2025 11:08:17","13-07-2025 11:05:13","13-07-2025 11:21=
:39","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)IHS=
 SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to =
Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid return"=
,"loic.noumsi@matech-cameroun.com","186","13-07-2025 11:08:17","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005469214","O=
dza II OCM","IHS_YND_528","13-07-2025 11:07:42","13-07-2025 11:02:36","13-0=
7-2025 11:06:30","	Grid outage, site went down because gen failed to start =
due to PWC ZTE malfunction//Site stabilised","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","	Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction//Site st=
abilised","gaelle.njiofack@matech-cameroun.com","739","13-07-2025 11:07:42"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005469209","Mfou EPC=
","","13-07-2025 11:06:10","13-07-2025 11:00:06","13-07-2025 11:06:04","Cas=
caded Incident from TTO5650241","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Gen start automatically","system","263233","13=
-07-2025 11:06:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005469208","Nsam esc=
ale LP","","13-07-2025 11:06:04","13-07-2025 11:03:39","13-07-2025 11:09:55=
","Cascaded Incident from TTO5650244","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Grid return","system","263020","13-07-2025 11:06:04",=
"MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005469206","Nsa=
m Sofavinc","IHS_YND_732","13-07-2025 11:05:44","13-07-2025 11:03:39","13-0=
7-2025 11:09:55","Grid Outage, Site went down before Gen start due to poor =
backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before =
Gen start due to poor backup // Grid return","loic.noumsi@matech-cameroun.c=
om","126","13-07-2025 11:05:44","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005469203","M=
fou OCM","IHS_YND_674","13-07-2025 11:05:12","13-07-2025 11:00:06","13-07-2=
025 11:06:04","	Grid Outage, Site Down before gen Started due to poor backu=
p // Gen start automatically","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down be=
fore gen Started due to poor backup // Gen start automatically","gaelle.nji=
ofack@matech-cameroun.com","307","13-07-2025 11:05:12","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005469069","B=
arriere","","13-07-2025 10:32:55","13-07-2025 10:30:50","13-07-2025 11:49:4=
3","Grid fluctuations, Site went down because Gen overload (30kva, 410A) SS=
 IHS Felix ZAMBE confirmed // Grid stabilized ","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, Site we=
nt down because Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // =
Grid stabilized ","loic.noumsi@matech-cameroun.com","128","13-07-2025 10:32=
:55","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005468922","Cit=
e des nations","","13-07-2025 10:04:42","13-07-2025 10:03:27","13-07-2025 1=
0:09:33","Grid outage,site went down before Gen started due to Poor battery=
 backup // Site stabilised","Paul BIBOUM","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage,site went down befor=
e Gen started due to Poor battery backup // Site stabilised","loic.noumsi@m=
atech-cameroun.com","76","13-07-2025 10:04:42","MATECH CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0005468351","S=
oa-II","","13-07-2025 07:59:24","13-07-2025 07:56:15","13-07-2025 08:28:33"=
,"Grid outage, Gen stopped tue to fuel shortage // Refueling done","Siligap=
 Boris","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, Gen =
stopped tue to fuel shortage // Refueling done","gaelle.njiofack@matech-cam=
eroun.com","190","13-07-2025 07:59:24","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005468260","B=
arriere","","13-07-2025 07:40:29","13-07-2025 07:38:18","13-07-2025 09:38:1=
0","Grid fluctuations, Site went down because Gen overload (30kva, 410A) SS=
 IHS Felix ZAMBE confirmed // Grid stabilized","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, Site wen=
t down because Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // G=
rid stabilized","gaelle.njiofack@matech-cameroun.com","133","13-07-2025 07:=
40:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005467388","Ngoum","=
","13-07-2025 02:22:30","13-07-2025 02:18:36","13-07-2025 03:12:13","Cascad=
ed Incident from TTO5648347","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen f=
ailed to start due to battery Ge discharged causing by Charging alternator =
faulty//Gen manually started with external battery","system","280000","13-0=
7-2025 02:22:30","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0005467387","Yok=
o MTN","IHS_YND_475","13-07-2025 02:21:45","13-07-2025 02:18:36","13-07-202=
5 03:12:13","Grid outage, site went down because gen failed to start due to=
 battery Ge discharged causing by Charging alternator faulty//Gen manually =
started with external battery","Parker Tchoup","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Charging Alternator","Grid outage, site went down becau=
se gen failed to start due to battery Ge discharged causing by Charging alt=
ernator faulty//Gen manually started with external battery","edwige.kapawo@=
matech-cameroun.com","190","13-07-2025 02:21:45","MATECH CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0005467268","N=
KONGKARAK","","13-07-2025 01:28:53","13-07-2025 01:25:41","13-07-2025 01:55=
:36","Grid outage, Site went down because Gen started and stopped due to Hi=
gh temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU=
 GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Grid outage, Site went down because Gen started and st=
opped due to High temp alarm //He added water and Gen start manually","edwi=
ge.kapawo@matech-cameroun.com","193","13-07-2025 01:28:53","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005466845","B=
arriere","","12-07-2025 23:23:16","12-07-2025 23:22:59","13-07-2025 00:40:1=
7","Grid fluctuations, Site went down because Gen overload (30kva, 410A) SS=
 IHS Felix ZAMBE confirmed // Grid stabilized","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, Site wen=
t down because Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // G=
rid stabilized","edwige.kapawo@matech-cameroun.com","20","12-07-2025 23:23:=
16","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005466832","N=
kolbong","","12-07-2025 23:20:18","12-07-2025 23:19:10","12-07-2025 23:45:0=
9","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","edwige.=
kapawo@matech-cameroun.com","69","12-07-2025 23:20:18","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005466757","B=
arriere","","12-07-2025 22:58:57","12-07-2025 22:58:52","12-07-2025 23:01:3=
9","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","edwige.kapawo@matech-cameroun.com","8","12-07-2025 22:58:57","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005466697","MEHANDAN=
","","12-07-2025 22:47:31","12-07-2025 22:17:59","13-07-2025 00:00:37","Cas=
caded Incident from TTO5647597","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to Pwc ZTE dysfunction// he reset it and started Gen =
manualy","system","272767","12-07-2025 22:47:31","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005466653","M=
fou OCM","","12-07-2025 22:40:34","12-07-2025 22:36:24","12-07-2025 22:55:2=
7","Grid Outage, Site Down before gen Started due to poor backup //Grid ret=
urned","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid Outage, Site Down before gen Started due to=
 poor backup //Grid returned","edwige.kapawo@matech-cameroun.com","251","12=
-07-2025 22:40:34","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005466592","Odz=
a II OCM","IHS_YND_528","12-07-2025 22:26:44","12-07-2025 22:17:59","13-07-=
2025 00:01:23","Grid outage, site went down because gen failed to start due=
 to Pwc ZTE dysfunction// he reset it and started Gen manualy","Albran Byor=
el","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid outage, site went down because gen failed to start due to Pwc ZTE dys=
function// he reset it and started Gen manualy","franck.nkomot@matech-camer=
oun.com","527","12-07-2025 22:26:44","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005466579","Men=
dong Plateau","","12-07-2025 22:25:00","12-07-2025 22:19:41","12-07-2025 22=
:38:05","Grid fluctuation, Site went down because Gen failed to start due t=
o Grid bad voltage //Grid power stabilized","Hyemafo Gildas","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
n, Site went down because Gen failed to start due to Grid bad voltage //Gri=
d power stabilized","franck.nkomot@matech-cameroun.com","320","12-07-2025 2=
2:25:00","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005466569","Awa=
e Ewonkan","","12-07-2025 22:23:18","12-07-2025 22:17:08","12-07-2025 22:43=
:08","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)IHS=
 SS Alphonse is informed//Grid return","Albran Byorel","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to Ge=
n Overload (20Kva, Iload 320A)IHS SS Alphonse is informed//Grid return","fr=
anck.nkomot@matech-cameroun.com","372","12-07-2025 22:23:18","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005466506","N=
kolbong","","12-07-2025 22:11:58","12-07-2025 22:09:44","12-07-2025 22:33:4=
4","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","135","12-07-2025 22:11:58","MATECH CMR"
"Closed Complete","Site Down","CTR_323","IHS_YND_043","NOCINC0005466485","E=
mia","","12-07-2025 22:07:49","12-07-2025 21:01:36","12-07-2025 22:10:12","=
Backtraking: No power issue site on grid with U=3D53.3V, site on grid Mbah =
osiah(674007438) from Huawei is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Backtraking: No po=
wer issue site on grid with U=3D53.3V, site on grid Mbah osiah(674007438) f=
rom Huawei is informed","gaelle.njiofack@matech-cameroun.com","3974","12-07=
-2025 22:07:49","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005466200","N=
kolbong","","12-07-2025 21:16:47","12-07-2025 21:12:34","12-07-2025 21:36:3=
6","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","255","12-07-2025 21:16:47","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005466056","B=
arriere","","12-07-2025 20:49:26","12-07-2025 20:47:15","12-07-2025 21:53:0=
2","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","gaelle.njiofack@matech-cameroun.com","133","12-07-2025 20:49:26","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005465956","Mfou EPC=
","","12-07-2025 20:32:41","12-07-2025 20:29:40","12-07-2025 20:34:10","Cas=
caded Incident from TTO5646784","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid unstable, Site Down before gen=
 Started due to poor backup //Grid stabilised","system","264931","12-07-202=
5 20:32:41","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005465941","M=
fou OCM","IHS_YND_674","12-07-2025 20:30:48","12-07-2025 20:29:40","12-07-2=
025 20:34:10","Grid unstable, Site Down before gen Started due to poor back=
up //Grid stabilised","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid unstable, Site Down before g=
en Started due to poor backup //Grid stabilised","gaelle.njiofack@matech-ca=
meroun.com","69","12-07-2025 20:30:48","MATECH CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0005465849","SOA=
 UNIVERSITY STADIUM","","12-07-2025 20:14:49","12-07-2025 20:04:59","12-07-=
2025 21:09:31","Grid bad voltage, site went down because Gen failed to star=
t due to lack of  02 phase // He did a bridge on the good phase","Siligap B=
oris","Grid Supply","Passive","Grid","National Grid - Grid Incomplete Phase=
","Grid bad voltage, site went down because Gen failed to start due to lack=
 of  02 phase // He did a bridge on the good phase","franck.nkomot@matech-c=
ameroun.com","591","12-07-2025 20:14:49","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005465848","N=
kolbong","","12-07-2025 20:14:37","12-07-2025 20:12:26","12-07-2025 20:34:4=
9","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","132","12-07-2025 20:14:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005465638","SOA VILL=
AGE","","12-07-2025 19:41:40","12-07-2025 19:36:29","12-07-2025 20:21:29","=
Cascaded Incident from TTO5646437","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage , site down because gen=
 stopped due to fuel shortage // tank tilt refueling will be done tomorrow"=
,"system","275260","12-07-2025 19:41:40","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005465628","S=
OA TOWN","IHS_YND_323","12-07-2025 19:39:34","12-07-2025 19:34:29","12-07-2=
025 20:21:29","Grid outage , site down because gen stopped due to fuel shor=
tage // tank tilt ,refueling will be done tomorrow","Siligap Boris","Fuel O=
utage","Passive","Diesel","Diesel Outage","Grid outage , site down because =
gen stopped due to fuel shortage // tank tilt refueling will be done tomorr=
ow","gaelle.njiofack@matech-cameroun.com","307","12-07-2025 19:39:34","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005465603","Mfou EPC=
","","12-07-2025 19:36:51","12-07-2025 19:27:51","12-07-2025 19:33:41","Cas=
caded Incident from TTO5646395","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Gen automatically started","system","261541","=
12-07-2025 19:36:51","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005465593","M=
fou OCM","IHS_YND_674","12-07-2025 19:35:58","12-07-2025 19:27:51","12-07-2=
025 19:33:41","Grid Outage, Site Down before gen Started due to poor backup=
 // Gen automatically started","Mba Lazare Herve","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down b=
efore gen Started due to poor backup // Gen automatically started","gaelle.=
njiofack@matech-cameroun.com","488","12-07-2025 19:35:58","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005465505","N=
kolbong","","12-07-2025 19:16:39","12-07-2025 19:02:32","12-07-2025 19:27:5=
6","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","848","12-07-2025 19:16:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_322","NOCINC0005465502","Soa-II",=
"","12-07-2025 19:15:52","12-07-2025 18:54:49","12-07-2025 19:21:49","Casca=
ded Incident from TTO5646183","Siligap Boris","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site was on gen after grid outage, Grid =
 return site down during the Huawei bay switchover due to poor backup.// Gr=
id restoration","system","263510","12-07-2025 19:15:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0005465499","Ebogo","=
","12-07-2025 19:15:51","12-07-2025 18:54:49","12-07-2025 19:21:49","Cascad=
ed Incident from TTO5646183","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site was on gen after grid outage, Grid  =
return site down during the Huawei bay switchover due to poor backup.// Gri=
d restoration","system","263512","12-07-2025 19:15:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0005465501","SOA UNIV=
ERSITY STADIUM","","12-07-2025 19:15:51","12-07-2025 18:54:49","12-07-2025 =
19:21:49","Cascaded Incident from TTO5646183","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","site was on gen after gr=
id outage, Grid  return site down during the Huawei bay switchover due to p=
oor backup.// Grid restoration","system","263507","12-07-2025 19:15:51","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005465500","Akak-Nko=
zoa-MTN-IHS","","12-07-2025 19:15:51","12-07-2025 18:54:49","12-07-2025 19:=
21:49","Cascaded Incident from TTO5646183","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","site was on gen after gri=
d outage, Grid  return site down during the Huawei bay switchover due to po=
or backup.// Grid restoration","system","263511","12-07-2025 19:15:51","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_317","NOCINC0005465498","Soa-Sofa=
mac","","12-07-2025 19:15:51","12-07-2025 18:54:49","12-07-2025 19:21:49","=
Cascaded Incident from TTO5646183","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site was on gen after grid outage, =
Grid  return site down during the Huawei bay switchover due to poor backup.=
// Grid restoration","system","263509","12-07-2025 19:15:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_321","NOCINC0005465497","Soa","",=
"12-07-2025 19:15:50","12-07-2025 18:54:49","12-07-2025 19:21:49","Cascaded=
 Incident from TTO5646183","Siligap Boris","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site was on gen after grid outage, Grid  re=
turn site down during the Huawei bay switchover due to poor backup.// Grid =
restoration","system","263508","12-07-2025 19:15:50","MATECH CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0005465389","S=
OA 2","IHS_YND_703, IHS_YND_321, IHS_YND_317, IHS_YND_390, IHS_YND_552, IHS=
_YND_307, IHS_YND_316, IHS_YND_351, IHS_YND_720, IHS_YND_322","12-07-2025 1=
8:55:56","12-07-2025 18:54:49","12-07-2025 19:21:49","site was on gen after=
 grid outage, Grid  return site down during the Huawei bay switchover due t=
o poor backup.// Grid restoration","Siligap Boris","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","site was on gen after g=
rid outage, Grid  return site down during the Huawei bay switchover due to =
poor backup.// Grid restoration","gaelle.njiofack@matech-cameroun.com","68"=
,"12-07-2025 18:55:56","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005465182","C=
-Supreme","","12-07-2025 18:15:32","12-07-2025 18:14:25","12-07-2025 18:16:=
48","No power issue, site on Grid with Ubaie=3D54.7V, Brice Tsague (650 21 =
40 96 / Huawei) is informed","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue, site on Grid wi=
th Ubaie=3D54.7V, Brice Tsague (650 21 40 96 / Huawei) is informed","gaelle=
.njiofack@matech-cameroun.com","68","12-07-2025 18:15:32","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005465176","B=
arriere","","12-07-2025 18:14:08","12-07-2025 18:13:01","12-07-2025 20:20:3=
0","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","gaelle.njiofack@matech-cameroun.com","70","12-07-2025 18:14:08","MATECH =
CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005465003","Ona=
ngondi (melen bikop)","","12-07-2025 17:40:01","12-07-2025 17:25:59","12-07=
-2025 17:41:59","Hybrid gen site .site went down due to hybrid malfunctionn=
ing//Gen manually started","Fanda Brice","Equipment Repair","Passive","Hybr=
id","Hybrid Module","Hybrid gen site .site went down due to hybrid malfunct=
ionning//Gen manually started","franck.nkomot@matech-cameroun.com","861","1=
2-07-2025 17:40:01","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005464917","N=
kolbong","","12-07-2025 17:24:26","12-07-2025 17:21:19","12-07-2025 17:47:1=
9","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","188","12-07-2025 17:24:26","MATECH CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0005464882","BEA=
TITUDE ENTR=C9E PAVE","","12-07-2025 17:18:02","12-07-2025 17:12:55","12-07=
-2025 18:04:20","Grid outage, Site went down because Gen failed to start du=
e to battery Gen Faulty// He started Gen with external battery","TIENTCHEU =
NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Generator B=
attery","Grid outage, Site went down because Gen failed to start due to bat=
tery Gen Faulty// He started Gen with external battery","franck.nkomot@mate=
ch-cameroun.com","307","12-07-2025 17:18:02","MATECH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0005464732","Com=
plex Beac II","","12-07-2025 16:55:25","12-07-2025 16:49:54","12-07-2025 17=
:27:31"," Double disjonction in the inverter box due to a probable overvolt=
age during Grid return, site down because gen fails to start due to disjonc=
tion in the inverter  // Inverter box CB rearmed","Albran Byorel","Equipmen=
t Repair","Passive","Control Panel","ATS Relay Faulty"," Double disjonction=
 in the inverter box due to a probable overvoltage during Grid return, site=
 down because gen fails to start due to disjonction in the inverter  // Inv=
erter box CB rearmed","franck.nkomot@matech-cameroun.com","332","12-07-2025=
 16:55:25","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005464580","Bit=
eng-Maetur","","12-07-2025 16:32:43","12-07-2025 16:28:37","12-07-2025 17:2=
4:14","Grid outage site went down because Gen failed to start due PWC ZTE d=
ysfunctioned // Grid return","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Grid outage site went down bec=
ause Gen failed to start due PWC ZTE dysfunctioned // Grid return","franck.=
nkomot@matech-cameroun.com","248","12-07-2025 16:32:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005464423","Mfou EPC=
","","12-07-2025 15:55:20","12-07-2025 15:50:13","12-07-2025 16:32:43","Cas=
caded Incident from TTO5645124","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Gen automatically started","system","1216747",=
"12-07-2025 15:55:20","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005464417","M=
fou OCM","IHS_YND_674","12-07-2025 15:54:19","12-07-2025 15:50:13","12-07-2=
025 16:32:43","Grid Outage, Site Down before gen Started due to poor backup=
 // Gen automatically started","Mba Lazare Herve","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down b=
efore gen Started due to poor backup // Gen automatically started","gaelle.=
njiofack@matech-cameroun.com","247","12-07-2025 15:54:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005464166","C-Suprem=
e","","12-07-2025 15:18:31","12-07-2025 15:14:23","12-07-2025 16:48:16","Ca=
scaded Incident from TTO5644807","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k) // Grid returned","system","290963","12-07-2025 15:18:31",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005464164","Olezoa O=
CM","","12-07-2025 15:18:30","12-07-2025 15:14:23","12-07-2025 16:48:16","C=
ascaded Incident from TTO5644807","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC over=
load, (210A ,12k) // Grid returned","system","290964","12-07-2025 15:18:30"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005464165","Acropole=
","","12-07-2025 15:18:30","12-07-2025 15:14:23","12-07-2025 16:48:16","Cas=
caded Incident from TTO5644807","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site Went down due =
to PWC overload, (210A ,12k) // Grid returned","system","290964","12-07-202=
5 15:18:30","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005464137","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","12-07-2025 15:16:39",=
"12-07-2025 15:14:23","12-07-2025 16:48:16","Grid fluctuations ,Site Went d=
own due to PWC overload, (210A ,12k) // Grid returned","MINKA NICOLAS","Gri=
d Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue","Gr=
id fluctuations ,Site Went down due to PWC overload, (210A ,12k) // Grid re=
turned","gaelle.njiofack@matech-cameroun.com","137","12-07-2025 15:16:39","=
MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005464114","B=
arriere","","12-07-2025 15:15:04","12-07-2025 15:14:56","12-07-2025 17:25:1=
0","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","gaelle.njiofack@matech-cameroun.com","10","12-07-2025 15:15:04","MATECH =
CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005464048","Aka=
k-Nkozoa-MTN-IHS","","12-07-2025 15:04:46","12-07-2025 14:58:33","12-07-202=
5 17:43:10","No power issue on site Ubaie: 53.1 V site on Grid. Sephorien (=
691316854/Huawei) is informed.","Fabrice Pouakam","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site Ubaie: 53.1 V site on Grid. Sephorien (691316854/Huawei) is infor=
med.","franck.nkomot@matech-cameroun.com","635","12-07-2025 15:04:46","MATE=
CH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005463542","Odz=
a II OCM","","12-07-2025 13:50:48","12-07-2025 12:57:56","12-07-2025 14:06:=
00","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction // Grid stabilized","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, site went down b=
ecause gen failed to start due to PWC ZTE malfunction // Grid stabilized","=
loic.noumsi@matech-cameroun.com","3174","12-07-2025 13:50:48","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005463515","M=
ontee-Des-Soeurs","","12-07-2025 13:45:36","12-07-2025 13:39:29","12-07-202=
5 13:47:32","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","gaelle.njiofack@matech-cameroun.com","369","12-07-2025 13:45:3=
6","MATECH CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0005463355","A=
FEME NORD","","12-07-2025 13:22:03","12-07-2025 13:17:55","12-07-2025 14:28=
:51","Grid  bad voltage and  1 open fuse ,site down because gen fails to st=
art due to grid bad voltage // Gen manually started","TIENTCHEU NZETCHIEU G=
AEL","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid  bad voltage and  1 open fuse ,site down because gen fails to star=
t due to grid bad voltage // Gen manually started","loic.noumsi@matech-came=
roun.com","249","12-07-2025 13:22:03","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005463159","B=
arriere","","12-07-2025 12:59:34","12-07-2025 12:57:28","12-07-2025 13:56:4=
2","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","gaelle.njiofack@matech-cameroun.com","128","12-07-2025 12:59:34","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005463147","O=
dza-PK10","IHS_YND_527","12-07-2025 12:57:03","12-07-2025 12:57:56","12-07-=
2025 14:06:00","Site went down due to disjunction of 2 CBs (125 A) in the D=
C BOX OCM // He rearmed CBs and site on Grid","Albran Byorel","Equipment Re=
pair","Passive","Control Panel","ATS-AMF Issue","Site went down due to disj=
unction of 2 CBs (125 A) in the DC BOX OCM // He rearmed CBs and site on Gr=
id","gaelle.njiofack@matech-cameroun.com","4423","12-07-2025 12:57:03","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005463144","N=
kolbong","","12-07-2025 12:56:33","12-07-2025 12:51:18","12-07-2025 14:39:1=
8","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","gaelle.=
njiofack@matech-cameroun.com","316","12-07-2025 12:56:33","MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0005462870","Abo=
me","","12-07-2025 12:37:01","12-07-2025 12:33:53","12-07-2025 13:01:09","G=
rid outage, site went down because Gen failed to start due to Gen card dysf=
unctionning // He reset Ge card and started Gen manually","MINKA NICOLAS","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
 site went down because Gen failed to start due to Gen card dysfunctionning=
 // He reset Ge card and started Gen manually","loic.noumsi@matech-cameroun=
.com","190","12-07-2025 12:37:01","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005462859","A=
wae Ewonkan","","12-07-2025 12:35:50","12-07-2025 12:32:21","12-07-2025 12:=
35:36","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed//Grid return","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to =
Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed//Grid return","=
loic.noumsi@matech-cameroun.com","1108","12-07-2025 12:35:50","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005462776","M=
eyo","IHS_YND_257","12-07-2025 12:21:57","12-07-2025 12:14:50","12-07-2025 =
12:39:33","Grid outage, site went down due to Gen overload (17KVA, 260A) SS=
 HIS Felix Zambe is informed and confirmed//Grid return","Hyemafo Gildas","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site=
 went down due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed=
 and confirmed//Grid return","loic.noumsi@matech-cameroun.com","428","12-07=
-2025 12:21:57","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005462763","E=
MANA BILICK CITY","IHS_YND_279","12-07-2025 12:20:35","12-07-2025 12:11:21"=
,"12-07-2025 14:00:31","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid returned	","Fabrice Pouakam","Access Denial"=
,"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Gri=
d outage, site down because site behaves as Grid only site (Gen Noise) // G=
rid returned	","loic.noumsi@matech-cameroun.com","556","12-07-2025 12:20:35=
","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005462754","M=
essassi okolo","","12-07-2025 12:19:45","12-07-2025 12:11:21","12-07-2025 1=
3:55:02","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site down because site behaves as Grid only=
 site (Gen Noise) // Grid returned	","loic.noumsi@matech-cameroun.com","273=
257","12-07-2025 12:19:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005462747","MEHANDAN=
","","12-07-2025 12:19:10","12-07-2025 12:12:35","12-07-2025 12:56:41","Cas=
caded Incident from TTO5643277","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction//Site stabilised","system","12=
15444","12-07-2025 12:19:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_517","NOCINC0005462745","Montee-D=
es-Soeurs","","12-07-2025 12:19:10","12-07-2025 12:12:35","12-07-2025 12:30=
:04","Grid outage ,site down due to Gen overload (15 KVA/210 A) // Grid ret=
urn","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Grid outage ,site down due to Gen overload (15 KVA/210 A) // Grid ret=
urn","system","395","12-07-2025 12:19:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_050","NOCINC0005462746","Satcom",=
"","12-07-2025 12:19:10","12-07-2025 12:12:35","12-07-2025 12:17:47","ACTIV=
E//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand ng=
uetsa(691144412) From huawei is informed.","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACT=
IVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand =
nguetsa(691144412) From huawei is informed.","system","395","12-07-2025 12:=
19:10","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005462730","O=
dza II OCM","IHS_YND_528","12-07-2025 12:17:41","12-07-2025 12:12:35","12-0=
7-2025 12:56:41","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction//Site st=
abilised","loic.noumsi@matech-cameroun.com","309","12-07-2025 12:17:41","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005462718","Nsam esc=
ale LP","","12-07-2025 12:16:01","12-07-2025 12:11:03","12-07-2025 12:17:54=
","Cascaded Incident from TTO5643255","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Grid return","system","266083","12-07-2025 12:16:01",=
"MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005462714","Nsa=
m Sofavinc","IHS_YND_732","12-07-2025 12:15:06","12-07-2025 12:11:03","12-0=
7-2025 12:17:54","Grid Outage, Site went down before Gen start due to poor =
backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before =
Gen start due to poor backup // Grid return","loic.noumsi@matech-cameroun.c=
om","244","12-07-2025 12:15:06","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005462472","D=
amas","IHS_YND_518","12-07-2025 11:37:38","12-07-2025 11:28:30","12-07-2025=
 12:27:51","Site went down due to double disjunction of Cb(63A*125A) in DC =
Box // He reamed Cb(63A*125A), site on grid","MINKA NICOLAS","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Sit=
e went down due to double disjunction of Cb(63A*125A) in DC Box // He reame=
d Cb(63A*125A), site on grid","loic.noumsi@matech-cameroun.com","549","12-0=
7-2025 11:37:38","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005462466","M=
ontee-Jouvence-II","","12-07-2025 11:36:14","12-07-2025 11:28:30","12-07-20=
25 12:27:51","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Site went down due to double disjunction of Cb(63A*12=
5A) in DC Box // He reamed Cb(63A*125A), site on grid","loic.noumsi@matech-=
cameroun.com","268608","12-07-2025 11:36:14","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005462378","M=
EFOU ASSI","","12-07-2025 11:18:57","12-07-2025 11:15:51","12-07-2025 11:17=
:13","Grid outage, Site went down before Gen start due to poor backup // Gr=
id returned","Fanda Brice","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","loic.noumsi@matech-cameroun.com","188",=
"12-07-2025 11:18:57","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005462374","Evo=
doula MTN","","12-07-2025 11:18:05","12-07-2025 11:15:59","12-07-2025 11:39=
:44","Grid outage, Site went down because gen failed to start due to alarm =
""undervoltage"" //We reset card GE and gen manually started","TIENTCHEU NZ=
ETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","Grid outage, Site went down because gen failed to start due to alarm ""u=
ndervoltage"" //We reset card GE and gen manually started","loic.noumsi@mat=
ech-cameroun.com","127","12-07-2025 11:18:05","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005461512","B=
arriere","","12-07-2025 09:24:44","12-07-2025 09:20:37","12-07-2025 11:19:4=
7","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","loic.noumsi@matech-cameroun.com","249","12-07-2025 09:24:44","MATECH CMR=
"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0005461411","Nko=
lfon Cimencam","","12-07-2025 09:10:15","12-07-2025 09:00:50","12-07-2025 1=
0:09:41","Grid outage, Site went down because Gen started and stopped with =
''low oil pressure'' alarm // he added oil and manually started Gen","Hyema=
fo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure=
","Grid outage, Site went down because Gen started and stopped with ''low o=
il pressure'' alarm // he added oil and manually started Gen","loic.noumsi@=
matech-cameroun.com","566","12-07-2025 09:10:15","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005460879","B=
arriere","","12-07-2025 07:01:44","12-07-2025 06:58:39","12-07-2025 08:59:1=
0","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","gaelle.njiofack@matech-cameroun.com","213","12-07-2025 07:01:44","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005460873","MEHANDAN=
","","12-07-2025 07:01:00","12-07-2025 06:56:38","12-07-2025 07:04:41","Cas=
caded Incident from TTO5641278","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction//Site stabilised","system","26=
3878","12-07-2025 07:01:00","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005460869","O=
dza II OCM","IHS_YND_528","12-07-2025 06:59:46","12-07-2025 06:56:38","12-0=
7-2025 07:04:41","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction//Site stabilised","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down bec=
ause gen failed to start due to PWC ZTE malfunction//Site stabilised","gael=
le.njiofack@matech-cameroun.com","191","12-07-2025 06:59:46","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005460851","B=
arriere IHS","","12-07-2025 06:55:44","12-07-2025 06:54:26","12-07-2025 15:=
23:26","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed//Grid return	","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to=
 Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed//Grid return	","g=
aelle.njiofack@matech-cameroun.com","80","12-07-2025 06:55:44","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005460748","N=
kolfon Cimencam","","12-07-2025 06:20:03","12-07-2025 05:01:36","12-07-2025=
 07:39:54","BACKTRACKING No power issue on site U=3D54,5v site on Gen The T=
X fme George(697461814) from huawei is informed. Noticed that site is impac=
ted by Afanoya II(Not manage by HIS)","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","BACKTRAC=
KING No power issue on site U=3D54,5v site on Gen The TX fme George(6974618=
14) from huawei is informed. Noticed that site is impacted by Afanoya II(No=
t manage by HIS)","cedric.tiani@matech-cameroun.com","4709","12-07-2025 06:=
20:03","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005460738","Nko=
g-Edzen","","12-07-2025 06:15:14","12-07-2025 06:06:40","12-07-2025 06:50:3=
7","No power issue on site, Site on Gen Ubay =3D 54.6V The Tx Fme Gregoire =
(654547479) from Huawei is informed","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site, Site on Gen Ubay =3D 54.6V The Tx Fme Gregoire (654547479) fr=
om Huawei is informed","cedric.tiani@matech-cameroun.com","515","12-07-2025=
 06:15:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0005460716","Boumnyeb=
el","","12-07-2025 05:59:40","12-07-2025 04:04:56","12-07-2025 05:59:50","C=
ascaded Incident from TTO5640727","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 Gen overload (20kva, 225A) SS IHS RENAULD is inform ","system","274010","1=
2-07-2025 05:59:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0005460709","Boga-Mah=
ole","","12-07-2025 05:56:12","12-07-2025 04:04:56","12-07-2025 05:59:50","=
Cascaded Incident from TTO5640727","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down due t=
o Gen overload (20kva, 225A) SS IHS RENAULD is inform ","system","274025","=
12-07-2025 05:56:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005460707","Song-bon=
g","","12-07-2025 05:56:12","12-07-2025 04:04:56","12-07-2025 05:59:50","Ca=
scaded Incident from TTO5640727","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
Gen overload (20kva, 225A) SS IHS RENAULD is inform ","system","274019","12=
-07-2025 05:56:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0005460708","Mamb",""=
,"12-07-2025 05:56:12","12-07-2025 04:04:56","12-07-2025 05:59:50","Cascade=
d Incident from TTO5640727","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, Site went down due to Gen o=
verload (20kva, 225A) SS IHS RENAULD is inform ","system","274017","12-07-2=
025 05:56:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0005460706","Eseka OC=
M","","12-07-2025 05:56:11","12-07-2025 04:04:56","12-07-2025 05:59:50","Ca=
scaded Incident from TTO5640727","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
Gen overload (20kva, 225A) SS IHS RENAULD is inform ","system","274023","12=
-07-2025 05:56:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005460703","Eseka To=
wn","","12-07-2025 05:56:11","12-07-2025 04:04:56","12-07-2025 05:59:50","C=
ascaded Incident from TTO5640727","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 Gen overload (20kva, 225A) SS IHS RENAULD is inform ","system","274032","1=
2-07-2025 05:56:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0005460705","Ngog Map=
ubi","","12-07-2025 05:56:11","12-07-2025 04:04:56","12-07-2025 05:59:50","=
Cascaded Incident from TTO5640727","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down due t=
o Gen overload (20kva, 225A) SS IHS RENAULD is inform ","system","274013","=
12-07-2025 05:56:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0005460704","Ndogbess=
ol","","12-07-2025 05:56:11","12-07-2025 04:04:56","12-07-2025 05:59:50","C=
ascaded Incident from TTO5640727","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 Gen overload (20kva, 225A) SS IHS RENAULD is inform ","system","274021","1=
2-07-2025 05:56:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0005460702","Boumnyeb=
el OCM","","12-07-2025 05:56:10","12-07-2025 04:04:56","12-07-2025 05:59:50=
","Cascaded Incident from TTO5640727","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down du=
e to Gen overload (20kva, 225A) SS IHS RENAULD is inform ","system","274015=
","12-07-2025 05:56:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005460549","Ahala","=
","12-07-2025 05:05:50","12-07-2025 03:04:33","12-07-2025 12:32:58","Cascad=
ed Incident from TTO5640948","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Gen o=
verload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed//Grid re=
turn","system","1248130","12-07-2025 05:05:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0005460486","Boumnyeb=
el","","12-07-2025 04:42:35","12-07-2025 00:55:16","12-07-2025 04:00:34","C=
ascaded Incident from TTO5640164","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 Gen overload (20kva, 225A) SS IHS RENAULD is inform // he reduce the load"=
,"system","277743","12-07-2025 04:42:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0005460484","Boumnyeb=
el OCM","","12-07-2025 04:42:34","12-07-2025 00:55:16","12-07-2025 04:00:34=
","Cascaded Incident from TTO5640164","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down du=
e to Gen overload (20kva, 225A) SS IHS RENAULD is inform // he reduce the l=
oad","system","277735","12-07-2025 04:42:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0005460485","Ndogbess=
ol","","12-07-2025 04:42:34","12-07-2025 00:55:16","12-07-2025 04:00:34","C=
ascaded Incident from TTO5640164","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 Gen overload (20kva, 225A) SS IHS RENAULD is inform // he reduce the load"=
,"system","277746","12-07-2025 04:42:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0005460473","Mamb",""=
,"12-07-2025 04:39:23","12-07-2025 00:55:16","12-07-2025 04:00:34","Cascade=
d Incident from TTO5640164","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, Site went down due to Gen o=
verload (20kva, 225A) SS IHS RENAULD is inform // he reduce the load","syst=
em","277741","12-07-2025 04:39:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0005460474","Boga-Mah=
ole","","12-07-2025 04:39:23","12-07-2025 00:55:16","12-07-2025 04:00:34","=
Cascaded Incident from TTO5640164","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down due t=
o Gen overload (20kva, 225A) SS IHS RENAULD is inform // he reduce the load=
","system","277738","12-07-2025 04:39:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005460471","Song-bon=
g","","12-07-2025 04:39:22","12-07-2025 00:55:16","12-07-2025 04:00:34","Ca=
scaded Incident from TTO5640164","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
Gen overload (20kva, 225A) SS IHS RENAULD is inform // he reduce the load",=
"system","277737","12-07-2025 04:39:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0005460469","Eseka OC=
M","","12-07-2025 04:39:22","12-07-2025 00:55:16","12-07-2025 04:00:34","Ca=
scaded Incident from TTO5640164","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
Gen overload (20kva, 225A) SS IHS RENAULD is inform // he reduce the load",=
"system","277740","12-07-2025 04:39:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0005460466","Ngog Map=
ubi","","12-07-2025 04:39:21","12-07-2025 00:55:16","12-07-2025 04:00:34","=
Cascaded Incident from TTO5640164","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down due t=
o Gen overload (20kva, 225A) SS IHS RENAULD is inform // he reduce the load=
","system","277739","12-07-2025 04:39:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005460464","Eseka To=
wn","","12-07-2025 04:39:21","12-07-2025 00:55:16","12-07-2025 04:00:34","C=
ascaded Incident from TTO5640164","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 Gen overload (20kva, 225A) SS IHS RENAULD is inform // he reduce the load"=
,"system","277744","12-07-2025 04:39:21","MATECH CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0005460293","H=
-Prince","","12-07-2025 03:41:43","12-07-2025 03:39:26","12-07-2025 03:41:1=
0","FME Biganst (650631358) from Dowen was on site for work (swap of Bay an=
d Gen)// end of work","Mboua Thierry","Installation Activity","Passive","Pl=
anned Activity","Installation Activity","FME Biganst (650631358) from Dowen=
 was on site for work (swap of Bay and Gen)// end of work","vanel.mbiada@ma=
tech-cameroun.com","138","12-07-2025 03:41:43","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005460187","A=
fanoya","","12-07-2025 03:08:07","12-07-2025 03:06:56","12-07-2025 04:31:54=
","Grid outage site went down because Gen failed to start due to Gen batter=
y discharged causing by charging alternator faulty// Gen manually started w=
ith external battery","Hyemafo Gildas","Equipment Repair","Passive","ACDG G=
en","ACDG - Generator Battery","Grid outage site went down because Gen fail=
ed to start due to Gen battery discharged causing by charging alternator fa=
ulty// Gen manually started with external battery","vanel.mbiada@matech-cam=
eroun.com","72","12-07-2025 03:08:07","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005460181","B=
arriere","","12-07-2025 03:05:47","12-07-2025 03:04:38","12-07-2025 03:08:4=
1","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed //Site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed //Site stabilised=
","vanel.mbiada@matech-cameroun.com","72","12-07-2025 03:05:47","MATECH CMR=
"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005460179","Mey=
o","IHS_YND_257","12-07-2025 03:05:40","12-07-2025 03:04:33","12-07-2025 11=
:53:05","Grid outage, site went down due to Gen overload (17KVA, 260A) SS H=
IS Felix Zambe is informed and confirmed//Grid return","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site w=
ent down due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed a=
nd confirmed//Grid return","cedric.tiani@matech-cameroun.com","68","12-07-2=
025 03:05:40","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005460132","OTE=
LE MTN","","12-07-2025 02:47:26","12-07-2025 02:44:13","12-07-2025 03:14:32=
","Site went down due to 01/02 rectifiers faulty on site//He reset it and r=
eplacement ongoing","Fanda Brice","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site went down due to 01/02 rectifiers faulty on site//=
He reset it and replacement ongoing","cedric.tiani@matech-cameroun.com","19=
4","12-07-2025 02:47:26","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005459989","Oko=
la","","12-07-2025 02:05:04","12-07-2025 02:01:46","12-07-2025 06:30:54","G=
rid outage.gen start and stopped due to alarm""high temp""//We added water =
and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age.gen start and stopped due to alarm""high temp""//We added water and gen=
 manually started","cedric.tiani@matech-cameroun.com","199","12-07-2025 02:=
05:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_030","NOCINC0005459578","E-Police=
","","12-07-2025 01:14:51","12-07-2025 01:12:51","12-07-2025 21:00:53","Cas=
caded Incident from TTO5640198","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage, Site down because Grid distributor had=
 burned, No space to deploy mobile gen , // eneo team resolve the issue. ",=
"system","370290","12-07-2025 01:14:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0005459580","Sapeur",=
"","12-07-2025 01:14:51","12-07-2025 01:12:51","12-07-2025 21:00:53","Casca=
ded Incident from TTO5640198","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, Site down because Grid dist=
ributor had burned, No space to deploy mobile gen , // eneo team resolve th=
e issue. ","system","370289","12-07-2025 01:14:51","MATECH CMR"
"Closed Complete","Site Down","CTR_323","IHS_YND_043","NOCINC0005459540","E=
mia","IHS_YND_030, IHS_YND_029","12-07-2025 01:14:00","12-07-2025 01:12:51"=
,"12-07-2025 21:00:53","Grid outage, Site down because Grid distributor had=
 burned, No space to deploy mobile gen , // eneo team resolve the issue. ",=
"","Grid Supply","Passive","Grid","National Grid - Equipment Burnt","Grid o=
utage, Site down because Grid distributor had burned, No space to deploy mo=
bile gen , // eneo team resolve the issue. ","vanel.mbiada@matech-cameroun.=
com","69","12-07-2025 01:14:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0005459451","Eseka OC=
M","","12-07-2025 00:50:00","12-07-2025 00:03:47","12-07-2025 00:34:40","Ca=
scaded Incident from TTO5639933","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
Gen overload (20kva, 225A) SS IHS RENAULD is inform //  he reduce the load"=
,"system","266506","12-07-2025 00:50:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0005459450","Ndogbess=
ol","","12-07-2025 00:50:00","12-07-2025 00:03:47","12-07-2025 00:34:40","C=
ascaded Incident from TTO5639933","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 Gen overload (20kva, 225A) SS IHS RENAULD is inform //  he reduce the load=
","system","266505","12-07-2025 00:50:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0005459453","Boga-Mah=
ole","","12-07-2025 00:50:00","12-07-2025 00:03:47","12-07-2025 00:34:40","=
Cascaded Incident from TTO5639933","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down due t=
o Gen overload (20kva, 225A) SS IHS RENAULD is inform //  he reduce the loa=
d","system","266499","12-07-2025 00:50:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0005459452","Mamb",""=
,"12-07-2025 00:50:00","12-07-2025 00:03:47","12-07-2025 00:34:40","Cascade=
d Incident from TTO5639933","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, Site went down due to Gen o=
verload (20kva, 225A) SS IHS RENAULD is inform //  he reduce the load","sys=
tem","266501","12-07-2025 00:50:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005459449","Eseka To=
wn","","12-07-2025 00:49:59","12-07-2025 00:03:47","12-07-2025 00:34:40","C=
ascaded Incident from TTO5639933","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 Gen overload (20kva, 225A) SS IHS RENAULD is inform //  he reduce the load=
","system","266496","12-07-2025 00:49:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005459402","Song-bon=
g","","12-07-2025 00:38:41","12-07-2025 00:03:47","12-07-2025 00:34:40","Ca=
scaded Incident from TTO5639933","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
Gen overload (20kva, 225A) SS IHS RENAULD is inform //  he reduce the load"=
,"system","266501","12-07-2025 00:38:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0005459401","Boumnyeb=
el","","12-07-2025 00:38:41","12-07-2025 00:03:47","12-07-2025 00:34:40","C=
ascaded Incident from TTO5639933","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 Gen overload (20kva, 225A) SS IHS RENAULD is inform //  he reduce the load=
","system","266506","12-07-2025 00:38:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0005459400","Ngog Map=
ubi","","12-07-2025 00:38:40","12-07-2025 00:03:47","12-07-2025 00:34:40","=
Cascaded Incident from TTO5639933","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down due t=
o Gen overload (20kva, 225A) SS IHS RENAULD is inform //  he reduce the loa=
d","system","266497","12-07-2025 00:38:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0005459399","Boumnyeb=
el OCM","","12-07-2025 00:38:40","12-07-2025 00:03:47","12-07-2025 00:34:40=
","Cascaded Incident from TTO5639933","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down du=
e to Gen overload (20kva, 225A) SS IHS RENAULD is inform //  he reduce the =
load","system","266504","12-07-2025 00:38:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0005459376","Garbati =
building","","12-07-2025 00:31:01","12-07-2025 00:24:23","12-07-2025 00:26:=
53","Cascaded Incident from TTO5639999","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Outage, Site went down b=
efore Gen start due to poor backup // Gen Started Automatically","system","=
265268","12-07-2025 00:31:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005459364","Nsam esc=
ale LP","","12-07-2025 00:29:21","12-07-2025 00:22:24","12-07-2025 00:28:20=
","Cascaded Incident from TTO5639990","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Gen Started Automatically","system","265387","12-07-2=
025 00:29:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005459363","MEHANDAN=
","","12-07-2025 00:29:19","12-07-2025 00:21:49","12-07-2025 00:43:25","Cas=
caded Incident from TTO5640000","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction//Site stabilised","system","26=
5423","12-07-2025 00:29:19","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005459357","M=
ontee-Des-Soeurs","","12-07-2025 00:28:36","12-07-2025 00:22:12","12-07-202=
5 04:55:45","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","vanel.mbiada@matech-cameroun.com","386","12-07-2025 00:28:36",=
"MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005459352","Awa=
e Ewonkan","","12-07-2025 00:26:53","12-07-2025 00:23:41","12-07-2025 00:29=
:42","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)IHS=
 SS Alphonse is informed//Grid return","Albran Byorel","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to Ge=
n Overload (20Kva, Iload 320A)IHS SS Alphonse is informed//Grid return","ce=
dric.tiani@matech-cameroun.com","194","12-07-2025 00:26:53","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005459348","O=
dza II OCM","IHS_YND_528","12-07-2025 00:25:58","12-07-2025 00:21:49","12-0=
7-2025 00:43:25","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction//Site stabilised","Albran Byorel","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site =
went down because gen failed to start due to PWC ZTE malfunction//Site stab=
ilised","vanel.mbiada@matech-cameroun.com","252","12-07-2025 00:25:58","MAT=
ECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005459346","HOP=
ITAL DE LA CAISSE","IHS_YND_024","12-07-2025 00:25:32","12-07-2025 00:24:23=
","12-07-2025 00:26:53","Grid Outage, Site went down before Gen start due t=
o poor backup // Gen Started Automatically","Delor Telezing","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, =
Site went down before Gen start due to poor backup // Gen Started Automatic=
ally","cedric.tiani@matech-cameroun.com","69","12-07-2025 00:25:32","MATECH=
 CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005459340","Nsa=
m Sofavinc","IHS_YND_732","12-07-2025 00:23:33","12-07-2025 00:22:24","12-0=
7-2025 00:28:20","Grid Outage, Site went down before Gen start due to poor =
backup // Gen Started Automatically","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site wen=
t down before Gen start due to poor backup // Gen Started Automatically","c=
edric.tiani@matech-cameroun.com","70","12-07-2025 00:23:33","MATECH CMR"
"Closed Complete","Site Down","T2183","IHS_YND_089","NOCINC0005459066","H-P=
rince","","11-07-2025 23:03:26","11-07-2025 22:56:14","11-07-2025 23:18:45"=
,"FME Biganst (650631358) from Dowen was on site for work (swap of Bay and =
Gen)// end of work","Mboua Thierry","Installation Activity","Passive","Plan=
ned Activity","Installation Activity","FME Biganst (650631358) from Dowen w=
as on site for work (swap of Bay and Gen)// end of work","cedric.tiani@mate=
ch-cameroun.com","433","11-07-2025 23:03:26","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005458612","N=
kolbong","","11-07-2025 21:46:14","11-07-2025 21:42:06","11-07-2025 23:18:4=
7","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)//Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A)//Grid return","edwige.=
kapawo@matech-cameroun.com","249","11-07-2025 21:46:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0005458531","MEFOU AS=
SI","","11-07-2025 21:31:54","11-07-2025 21:26:41","11-07-2025 21:30:14","C=
ascaded Incident from TTO5639086","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down before Gen=
 start due to poor backup // Grid return","system","1218124","11-07-2025 21=
:31:54","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005458522","S=
IMBOCK BONAMBAPE","IHS_YND_537","11-07-2025 21:30:48","11-07-2025 21:26:41"=
,"11-07-2025 21:30:14","Grid outage, Site went down before Gen start due to=
 poor backup // Grid return","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup // Grid return","edwige.kapawo@matech-c=
ameroun.com","248","11-07-2025 21:30:48","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005458354","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","11-07-2025 20:57:54","11-07-20=
25 20:57:47","11-07-2025 23:55:11","Grid outage.gen start and stopped due t=
o alarm""high temp""//We added water and gen manually started","TIENTCHEU N=
ZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine =
Temp - Coolant Level Issue","Grid outage.gen start and stopped due to alarm=
""high temp""//We added water and gen manually started","gerard.tchangoue@m=
atech-cameroun.com","8","11-07-2025 20:57:54","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005458305","N=
kolbong","","11-07-2025 20:46:32","11-07-2025 20:42:26","11-07-2025 21:07:2=
1","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Ge=
n started and stopped due to Gen overload(22kva//350A) // Grid return","edw=
ige.kapawo@matech-cameroun.com","248","11-07-2025 20:46:32","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005458175","Ona=
ngondi (melen bikop)","","11-07-2025 20:24:29","11-07-2025 20:19:24","11-07=
-2025 20:50:44","Hybrid gen site .site went down due to hybrid malfunctionn=
ing//Gen manually started","Fanda Brice","Equipment Repair","Passive","Hybr=
id","Hybrid Module","Hybrid gen site .site went down due to hybrid malfunct=
ionning//Gen manually started","gerard.tchangoue@matech-cameroun.com","307"=
,"11-07-2025 20:24:29","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005457847","N=
kolbong","","11-07-2025 19:37:10","11-07-2025 19:36:59","11-07-2025 20:00:3=
1","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Ge=
n started and stopped due to Gen overload(22kva//350A) // Grid return","edw=
ige.kapawo@matech-cameroun.com","12","11-07-2025 19:37:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005457470","C-Suprem=
e","","11-07-2025 18:36:51","11-07-2025 15:50:59","12-07-2025 15:01:15","Ca=
scaded Incident from TTO5636627","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive"," Grid fluctuations ,Site Went down due to PWC over=
load, (210A ,12k) // Grid  returned","system","346387","11-07-2025 18:36:51=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005457469","Acropole=
","","11-07-2025 18:36:50","11-07-2025 15:50:59","12-07-2025 15:01:15","Cas=
caded Incident from TTO5636627","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive"," Grid fluctuations ,Site Went down due=
 to PWC overload, (210A ,12k) // Grid  returned","system","346388","11-07-2=
025 18:36:50","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005457410","N=
kolbong","","11-07-2025 18:25:01","11-07-2025 18:15:59","11-07-2025 18:37:2=
3","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Ge=
n started and stopped due to Gen overload(22kva//350A) // Grid return","edw=
ige.kapawo@matech-cameroun.com","544","11-07-2025 18:25:01","MATECH CMR"
"Closed Complete","Site Down","CTR_286","IHS_YND_381","NOCINC0005456745","B=
oumnyebel","IHS_YND_379, IHS_YND_378","11-07-2025 17:03:39","11-07-2025 17:=
02:33","11-07-2025 18:15:05","Grid fluctuation, Site went down because Gen =
failed to start due to Grid bad voltage(LACK OF 02 PHASES ) //He bypassed G=
rid and started Gen manualy","Kemeni Franklin","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Grid fluctuation, Site went d=
own because Gen failed to start due to Grid bad voltage(LACK OF 02 PHASES )=
 //He bypassed Grid and started Gen manualy","edwige.kapawo@matech-cameroun=
.com","67","11-07-2025 17:03:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005456684","Eseka To=
wn","","11-07-2025 16:52:50","11-07-2025 17:02:33","11-07-2025 17:25:57","C=
ascaded Incident from TTO5637036 - Cascade Removed From TTO5637036","Kemeni=
 Franklin","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid fluctuation, Site went down because Gen failed to start due to Grid ba=
d voltage(LACK OF 02 PHASES ) //He bypassed Grid and started Gen manualy","=
system","270122","11-07-2025 16:52:50","MATECH CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0005456679","Ese=
ka MTN","","11-07-2025 16:51:50","11-07-2025 17:02:33","11-07-2025 17:25:57=
","FME Franklin will managed ETA 5:35 PM","Kemeni Franklin","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid fluctuation, Site wen=
t down because Gen failed to start due to Grid bad voltage(LACK OF 02 PHASE=
S ) //He bypassed Grid and started Gen manualy","gerard.tchangoue@matech-ca=
meroun.com","270122","11-07-2025 16:51:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005456441","MEHANDAN=
","","11-07-2025 16:17:10","11-07-2025 16:14:07","11-07-2025 16:22:54","Cas=
caded Incident from TTO5636760","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction /Site stabilised","system","27=
3014","11-07-2025 16:17:10","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005456435","O=
dza II OCM","IHS_YND_528","11-07-2025 16:16:15","11-07-2025 16:14:07","11-0=
7-2025 16:22:54","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction /Site stabilised","Albran Byorel","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site =
went down because gen failed to start due to PWC ZTE malfunction /Site stab=
ilised","edwige.kapawo@matech-cameroun.com","131","11-07-2025 16:16:15","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005456388","Olezoa O=
CM","","11-07-2025 16:10:10","11-07-2025 15:50:59","12-07-2025 15:01:15","C=
ascaded Incident from TTO5636627","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive"," Grid fluctuations ,Site Went down due to PWC ove=
rload, (210A ,12k) // Grid  returned","system","346389","11-07-2025 16:10:1=
0","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005456343","B=
arriere","","11-07-2025 16:02:31","11-07-2025 16:00:59","11-07-2025 20:51:0=
1","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"edwige.kapawo@matech-cameroun.com","95","11-07-2025 16:02:31","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005456310","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","11-07-2025 15:59:51",=
"11-07-2025 15:50:59","12-07-2025 15:01:15"," Grid fluctuations ,Site Went =
down due to PWC overload, (210A ,12k) // Grid  returned","MINKA NICOLAS","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded"," Grid=
 fluctuations ,Site Went down due to PWC overload, (210A ,12k) // Grid  ret=
urned","edwige.kapawo@matech-cameroun.com","533","11-07-2025 15:59:51","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0005455824","Mendong =
Maeture","","11-07-2025 15:17:00","11-07-2025 15:07:31","11-07-2025 16:29:0=
4","Cascaded Incident from TTO5636087","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down due to =
Gen overload (15KVA//130A) // He reduce the load and started DG","system","=
276996","11-07-2025 15:17:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005455825","Montee-J=
ouvence","","11-07-2025 15:17:00","11-07-2025 15:07:31","11-07-2025 16:29:0=
4","Cascaded Incident from TTO5636087","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down due to =
Gen overload (15KVA//130A) // He reduce the load and started DG","system","=
276997","11-07-2025 15:17:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0005455823","Mendong =
vallee","","11-07-2025 15:16:59","11-07-2025 15:07:31","11-07-2025 16:29:04=
","Cascaded Incident from TTO5636087","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to Gen =
overload (15KVA//130A) // He reduce the load and started DG","system","2769=
96","11-07-2025 15:16:59","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005455813","M=
endong","IHS_YND_692, IHS_YND_569, IHS_YND_236","11-07-2025 15:14:38","11-0=
7-2025 15:07:31","11-07-2025 16:29:24","Grid outage, site down due to Gen o=
verload (15KVA//130A) // He reduce the load and started DG","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, s=
ite down due to Gen overload (15KVA//130A) // He reduce the load and starte=
d DG","edwige.kapawo@matech-cameroun.com","428","11-07-2025 15:14:38","MATE=
CH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005455266","Evo=
doula MTN","","11-07-2025 13:48:23","11-07-2025 13:40:14","11-07-2025 13:49=
:14","Grid outage, Site went down before Gen start due to poor backup // Ge=
n Automaticaly started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup // Gen Automaticaly started","fran=
ck.nkomot@matech-cameroun.com","490","11-07-2025 13:48:23","MATECH CMR"
"Closed Complete","Site Down","CTR_546","IHS_YND_419","NOCINC0005455095","N=
gog Mapubi","","11-07-2025 13:18:38","11-07-2025 13:09:30","11-07-2025 13:1=
8:04","	No power issue on site ,site on Gen with Ubaie=3D 54,8V The fme tx =
Etienne fopa // 695033981 of huawei is informed","Kemeni Franklin","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","	No power issue on site ,site on Gen with Ubaie=3D 54,8V The fme tx Eti=
enne fopa // 695033981 of huawei is informed","vanel.mbiada@matech-cameroun=
.com","549","11-07-2025 13:18:38","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005455036","E=
lig-Edzoa","","11-07-2025 13:10:46","11-07-2025 13:06:38","11-07-2025 13:50=
:13","Grid only site,No mobile gen available // grid restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site,N=
o mobile gen available // grid restored","vanel.mbiada@matech-cameroun.com"=
,"249","11-07-2025 13:10:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005455010","MEHANDAN=
","","11-07-2025 13:07:31","11-07-2025 13:01:41","11-07-2025 13:34:44","Cas=
caded Incident from TTO5635185","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction /Site stabilised","system","12=
19469","11-07-2025 13:07:31","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005455000","O=
dza II OCM","IHS_YND_528","11-07-2025 13:05:49","11-07-2025 13:01:41","11-0=
7-2025 13:34:44","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction /Site stabilised","Albran Byorel","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site =
went down because gen failed to start due to PWC ZTE malfunction /Site stab=
ilised","vanel.mbiada@matech-cameroun.com","251","11-07-2025 13:05:49","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005454717","N=
kolbong","","11-07-2025 12:18:13","11-07-2025 12:06:05","11-07-2025 15:27:3=
8","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Ge=
n started and stopped due to Gen overload(22kva//350A) // Grid return","van=
el.mbiada@matech-cameroun.com","730","11-07-2025 12:18:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005454682","C-Suprem=
e","","11-07-2025 12:15:11","11-07-2025 12:10:41","11-07-2025 14:01:09","Ca=
scaded Incident from TTO5634800","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","( Unstable site ) Grid fluctuations ,Site Went dow=
n due to PWC overload, (210A ,12k). // Grid stabilised","system","287578","=
11-07-2025 12:15:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005454681","Acropole=
","","11-07-2025 12:15:10","11-07-2025 12:10:41","11-07-2025 14:01:09","Cas=
caded Incident from TTO5634800","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","( Unstable site ) Grid fluctuations ,S=
ite Went down due to PWC overload, (210A ,12k). // Grid stabilised","system=
","287578","11-07-2025 12:15:10","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005454669","Oko=
la","IHS_YND_530, IHS_YND_390","11-07-2025 12:13:00","11-07-2025 12:10:17",=
"11-07-2025 14:55:30","Grid outage .gen failed to start due to alarm high t=
emp//We add water and Grid return","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue",=
"Grid outage .gen failed to start due to alarm high temp//We add water and =
Grid return","franck.nkomot@matech-cameroun.com","165","11-07-2025 12:13:00=
","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005454662","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","11-07-2025 12:11:49","11-07-2025 1=
2:10:41","11-07-2025 14:01:09","( Unstable site ) Grid fluctuations ,Site W=
ent down due to PWC overload, (210A ,12k). // Grid stabilised","MINKA NICOL=
AS","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"( Unstable site ) Grid fluctuations ,Site Went down due to PWC overload, (=
210A ,12k). // Grid stabilised","vanel.mbiada@matech-cameroun.com","69","11=
-07-2025 12:11:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005454624","Akak-Nko=
zoa-MTN-IHS","","11-07-2025 12:05:50","11-07-2025 11:54:04","11-07-2025 11:=
56:51","Cascaded Incident from TTO5634689","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
: 53.9V site on Grid. Symphorien (675295205/Huawei) is informed.","system",=
"259988","11-07-2025 12:05:50","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005454602","B=
arriere","","11-07-2025 12:01:24","11-07-2025 11:58:11","11-07-2025 13:58:0=
1","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"vanel.mbiada@matech-cameroun.com","195","11-07-2025 12:01:24","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0005454408","M=
fou EPC","","11-07-2025 11:30:14","11-07-2025 11:17:06","11-07-2025 13:28:1=
8","Grid outage, site down because gen fails to start due to dijonction in =
the ocm BTS  //  OCM BTS CB rearmed and Grid restoration","Mba Lazare Herve=
","Equipment Repair","Passive","Control Panel","BTS Breaker Tripped","Grid =
outage, site down because gen fails to start due to dijonction in the ocm B=
TS  //  OCM BTS CB rearmed and Grid restoration","vanel.mbiada@matech-camer=
oun.com","790","11-07-2025 11:30:14","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005454267","E=
MANA BILICK CITY","IHS_YND_279","11-07-2025 11:12:34","11-07-2025 11:09:25"=
,"11-07-2025 15:16:28","Access issues due to landlord(Landlord has forbidde=
n to start the Gen due to noise)//Grid return","Fabrice Pouakam","Access De=
nial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord"=
,"Access issues due to landlord(Landlord has forbidden to start the Gen due=
 to noise)//Grid return","vanel.mbiada@matech-cameroun.com","191","11-07-20=
25 11:12:34","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005454258","M=
essassi okolo","","11-07-2025 11:11:45","11-07-2025 11:09:25","11-07-2025 1=
1:16:17","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site down because site behaves as Grid only=
 site (Gen Noise) // Grid returned","vanel.mbiada@matech-cameroun.com","276=
887","11-07-2025 11:11:45","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005454239","ELO=
UMDEM CARRIERE","","11-07-2025 11:09:45","11-07-2025 11:03:50","11-07-2025 =
11:16:15","No power issue , Site on Grid and Ubaie=3D54.5V The Tx Fme Fulbe=
rt //654266068 from Huawei is informed","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue , Site on Grid and Ubaie=3D54.5V The Tx Fme Fulbert //654266068 from =
Huawei is informed","vanel.mbiada@matech-cameroun.com","356","11-07-2025 11=
:09:45","MATECH CMR"
"Closed Complete","Site Down","T2183","IHS_YND_089","NOCINC0005453831","H-P=
rince","","11-07-2025 10:00:17","11-07-2025 09:51:40","11-07-2025 13:10:40"=
,"FME Biganst (650631358) from Dowen was on site for work (swap of Bay and =
Gen) // End of work","Mboua Thierry","Installation Activity","Passive","Pla=
nned Activity","Installation Activity","FME Biganst (650631358) from Dowen =
was on site for work (swap of Bay and Gen) // End of work","franck.nkomot@m=
atech-cameroun.com","862","11-07-2025 10:00:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005453669","Acropole=
","","11-07-2025 09:29:50","11-07-2025 09:19:20","11-07-2025 11:42:14","Cas=
caded Incident from TTO5633688","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","( Very unstable site ) Grid fluctuatio=
ns ,Site Went down due to PWC overload, (210A ,12k).// Grid stabilised","sy=
stem","269177","11-07-2025 09:29:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005453670","C-Suprem=
e","","11-07-2025 09:29:50","11-07-2025 09:19:20","11-07-2025 11:42:14","Ca=
scaded Incident from TTO5633688","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","( Very unstable site ) Grid fluctuations ,Site Wen=
t down due to PWC overload, (210A ,12k).// Grid stabilised","system","26917=
8","11-07-2025 09:29:50","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005453644","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","11-07-2025 09:27:29","11-07-2025 0=
9:19:20","11-07-2025 11:42:14","( Very unstable site ) Grid fluctuations ,S=
ite Went down due to PWC overload, (210A ,12k).// Grid stabilised","MINKA N=
ICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module Overload=
ed","( Very unstable site ) Grid fluctuations ,Site Went down due to PWC ov=
erload, (210A ,12k).// Grid stabilised","vanel.mbiada@matech-cameroun.com",=
"490","11-07-2025 09:27:29","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005453630","B=
arriere","","11-07-2025 09:25:23","11-07-2025 09:24:16","11-07-2025 11:49:5=
2","( Very unstable site ) Grid outage, Site went down because Gen overload=
 (30kva, 410A) SS IHS Felix ZAMBE confirmed","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","( Very unstable site ) Grid o=
utage, Site went down because Gen overload (30kva, 410A) SS IHS Felix ZAMBE=
 confirmed","vanel.mbiada@matech-cameroun.com","70","11-07-2025 09:25:23","=
MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005453559","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","11-07-2025 09:09:37","11-07-20=
25 09:04:30","11-07-2025 10:36:45","Grid outage .gen failed to start due to=
 alarm high temp//We add water and gen manually started ","TIENTCHEU NZETCH=
IEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Grid outage .gen failed to start due to alarm high =
temp//We add water and gen manually started ","franck.nkomot@matech-camerou=
n.com","308","11-07-2025 09:09:37","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005453243","Evo=
doula MTN","","11-07-2025 08:10:58","11-07-2025 08:07:44","11-07-2025 08:47=
:22","Grid outage, Site went down before Gen start due to poor backup // Ge=
n Automaticaly started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup // Gen Automaticaly started","vane=
l.mbiada@matech-cameroun.com","195","11-07-2025 08:10:58","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005453144","B=
arriere","","11-07-2025 07:45:34","11-07-2025 07:42:20","11-07-2025 09:14:1=
7","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"vanel.mbiada@matech-cameroun.com","196","11-07-2025 07:45:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005453091","C-Suprem=
e","","11-07-2025 07:30:22","11-07-2025 07:21:22","11-07-2025 08:56:50","Ca=
scaded Incident from TTO5633038","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","( Unstable site ) Grid fluctuations ,Site Went dow=
n due to PWC overload, (210A ,12k). // Grid stabilised","system","269069","=
11-07-2025 07:30:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005453090","Acropole=
","","11-07-2025 07:30:22","11-07-2025 07:21:22","11-07-2025 08:56:50","Cas=
caded Incident from TTO5633038","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","( Unstable site ) Grid fluctuations ,S=
ite Went down due to PWC overload, (210A ,12k). // Grid stabilised","system=
","269068","11-07-2025 07:30:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005453089","Olezoa O=
CM","","11-07-2025 07:30:21","11-07-2025 07:21:22","11-07-2025 08:56:50","C=
ascaded Incident from TTO5633038","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","( Unstable site ) Grid fluctuations ,Site Went do=
wn due to PWC overload, (210A ,12k). // Grid stabilised","system","269067",=
"11-07-2025 07:30:21","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005453053","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","11-07-2025 07:22:30",=
"11-07-2025 07:21:22","11-07-2025 08:56:50","( Unstable site ) Grid fluctua=
tions ,Site Went down due to PWC overload, (210A ,12k). // Grid stabilised"=
,"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","( Unstable site ) Grid fluctuations ,Site Went down due to PW=
C overload, (210A ,12k). // Grid stabilised","vanel.mbiada@matech-cameroun.=
com","69","11-07-2025 07:22:30","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005452986","M=
EFOU ASSI","","11-07-2025 07:05:00","11-07-2025 06:59:44","11-07-2025 11:09=
:38","No power issue on site U=3D54.4v site on grid The Tx lionel tchatchou=
 //694693436 from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site U=3D54.4v site on grid The Tx lionel tchatchou //694693436 from=
 Huawei is informed","vanel.mbiada@matech-cameroun.com","318","11-07-2025 0=
7:05:00","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005452803","Mok=
olo Yaounde","","11-07-2025 06:18:10","11-07-2025 06:16:48","11-07-2025 06:=
36:30","Active // No power issue Ubaie: 54.6 V site on grid. The Tx FME Elo=
undou Bertrand (693212405) from Huawei is informed","","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/ No power issue Ubaie: 54.6 V site on grid. The Tx FME Eloundou Bertrand (=
693212405) from Huawei is informed","vanel.mbiada@matech-cameroun.com","83"=
,"11-07-2025 06:18:10","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005452680","A=
wae Ewonkan","","11-07-2025 05:26:40","11-07-2025 05:25:26","11-07-2025 05:=
27:55","No power issue on site Tx issue U=3D51.3V site on Grid , the FME TX=
 Leonel Steve //655184876 from Huawei is informed","Albran Byorel","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Tx issue U=3D51.3V site on Grid , the FME TX Leo=
nel Steve //655184876 from Huawei is informed","vanel.mbiada@matech-camerou=
n.com","76","11-07-2025 05:26:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005452647","MEHANDAN=
","","11-07-2025 05:13:19","11-07-2025 05:10:07","11-07-2025 05:19:42","Cas=
caded Incident from TTO5632578","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction//Site stabilised","system","26=
2473","11-07-2025 05:13:19","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005452645","O=
dza II OCM","IHS_YND_528","11-07-2025 05:12:42","11-07-2025 05:10:07","11-0=
7-2025 05:19:42","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction//Site stabilised","Albran Byorel","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site =
went down because gen failed to start due to PWC ZTE malfunction//Site stab=
ilised","vanel.mbiada@matech-cameroun.com","158","11-07-2025 05:12:42","MAT=
ECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005452591","Sim=
e Building","","11-07-2025 04:54:46","11-07-2025 04:52:28","11-07-2025 05:0=
1:50","Grid outage, Site went down before Gen start due to poor backup// Ge=
n automatically started","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Gen automatically started","vanel.mbiada@m=
atech-cameroun.com","138","11-07-2025 04:54:46","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005452132","Odz=
a Minkan IHS","","11-07-2025 01:04:03","11-07-2025 01:00:52","11-07-2025 01=
:47:38","Grid fluctuations, Site went down because Gen failed to start due =
to Grid bad voltage(Unstable phases)// He bypassed Grid and started Gen man=
ually","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuations, Site went down because Gen failed =
to start due to Grid bad voltage(Unstable phases)// He bypassed Grid and st=
arted Gen manually","cedric.tiani@matech-cameroun.com","192","11-07-2025 01=
:04:03","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005451663","E=
seka OCM","","10-07-2025 23:27:28","10-07-2025 23:25:16","10-07-2025 23:31:=
53","No power issue U=3D55.4V site on Grid The Tx FME Etienne FOPA /6950339=
81/ From HUAWEI is informed","Kemeni Franklin","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=
=3D55.4V site on Grid The Tx FME Etienne FOPA /695033981/ From HUAWEI is in=
formed","vanel.mbiada@matech-cameroun.com","133","10-07-2025 23:27:28","MAT=
ECH CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0005451543","Nya=
hoo","IHS_EDA_102, IHS_EDA_049","10-07-2025 23:04:26","10-07-2025 22:58:08"=
,"11-07-2025 08:05:46","No power issue on site Ubaie : 53,7V site on Gen an=
d The FME TX Gregoire From huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue on site Ubaie : 53,7V site on Gen and The FME TX =
Gregoire From huawei is informed","cedric.tiani@matech-cameroun.com","379",=
"10-07-2025 23:04:26","MATECH CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0005451539","NYA=
NON/DEMBO","","10-07-2025 23:03:47","10-07-2025 22:58:08","11-07-2025 07:05=
:46","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","No power issue on site Ubaie : 53,7V site on Gen and T=
he FME TX Gregoire From huawei is informed","cedric.tiani@matech-cameroun.c=
om","299223","10-07-2025 23:03:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0005451106","Montee-J=
ouvence-II","","10-07-2025 21:31:09","10-07-2025 21:22:05","10-07-2025 21:5=
4:57","Cascaded Incident from TTO5630869","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to doubl=
e disjunction of Cb(63A*125A) in DC Box  // He reamed Cb(63A*125A), site on=
 grid","system","1232615","10-07-2025 21:31:09","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005451073","D=
amas","IHS_YND_518","10-07-2025 21:24:12","10-07-2025 21:22:05","10-07-2025=
 21:54:57","Site went down due to double disjunction of Cb(63A*125A) in DC =
Box  // He reamed Cb(63A*125A), site on grid","MINKA NICOLAS","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Si=
te went down due to double disjunction of Cb(63A*125A) in DC Box  // He rea=
med Cb(63A*125A), site on grid","edwige.kapawo@matech-cameroun.com","128","=
10-07-2025 21:24:12","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005451026","B=
arriere","","10-07-2025 21:16:03","10-07-2025 21:15:52","10-07-2025 23:46:2=
6","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"edwige.kapawo@matech-cameroun.com","13","10-07-2025 21:16:03","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005450731","SAA=
 Entrance","","10-07-2025 20:30:31","10-07-2025 20:29:23","10-07-2025 20:36=
:44","Active: No power issue, site is on Gen with Ubaie=3D54.5V, The FME Gr=
egoire /654547479 Huawei is informed","Parker Tchoup","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: N=
o power issue, site is on Gen with Ubaie=3D54.5V, The FME Gregoire /6545474=
79 Huawei is informed","gerard.tchangoue@matech-cameroun.com","70","10-07-2=
025 20:30:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005450326","C-Suprem=
e","","10-07-2025 19:13:40","10-07-2025 19:12:53","11-07-2025 01:17:21","Ca=
scaded Incident from TTO5630029","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k)  // Grid stabilised","system","291054","10-07-2025 19:13:4=
0","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005450317","M=
vog Mbi New","IHS_YND_021","10-07-2025 19:12:58","10-07-2025 19:12:53","11-=
07-2025 01:17:21","Grid fluctuations ,Site Went down due to PWC overload, (=
210A ,12k)  // Grid stabilised","MINKA NICOLAS","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Grid fluctuations ,Site Went d=
own due to PWC overload, (210A ,12k)  // Grid stabilised","edwige.kapawo@ma=
tech-cameroun.com","6","10-07-2025 19:12:58","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005450080","M=
ambine","","10-07-2025 18:24:05","10-07-2025 18:17:47","10-07-2025 19:01:22=
","Grid outage.gen ran until fuel shortage // Refueling done","Fanda Brice"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unti=
l fuel shortage // Refueling done","edwige.kapawo@matech-cameroun.com","380=
","10-07-2025 18:24:05","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005450066","NKO=
MKANA ELIZA HOTEL","","10-07-2025 18:21:53","10-07-2025 18:20:46","10-07-20=
25 18:22:31","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","68","10-07-2025 18:21:53","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005450050","Evo=
doula MTN","","10-07-2025 18:19:18","10-07-2025 18:17:12","10-07-2025 18:19=
:20","Grid outage, Site went down before Gen start due to poor backup// GRI=
D return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// GRID return","gerard.tchangoue@matech-cameroun=
.com","127","10-07-2025 18:19:18","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005449710","A=
kak-Nkozoa-MTN-IHS","","10-07-2025 17:18:18","10-07-2025 17:16:11","10-07-2=
025 18:10:15","Grid outage, Site went down because Gen started and stopped =
with ""low oil pressure"" alarm// He reset card GE and gen manually started=
","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil=
 Pressure","Site went down because gen failed to start due to low oil press=
ure // He added oil and gen manually started","edwige.kapawo@matech-camerou=
n.com","129","10-07-2025 17:18:18","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005449685","F=
ouda-New","","10-07-2025 17:13:23","10-07-2025 17:12:18","10-07-2025 17:15:=
02","Grid Outage, site went down before Gen start due to Poor battery backu=
p // Grid returned","Delor Telezing","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, site went down before Ge=
n start due to Poor battery backup // Grid returned","edwige.kapawo@matech-=
cameroun.com","66","10-07-2025 17:13:23","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005449566","Lad=
a I Yde","","10-07-2025 16:53:48","10-07-2025 16:52:38","10-07-2025 17:02:2=
4","Active//No power issue site on Grid with U=3D54.9V Henri  (691145055 ) =
from Huawei is informed.","Mba Lazare Herve","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue site on Grid with U=3D54.9V Henri  (691145055 ) from Huawei is informe=
d.","gerard.tchangoue@matech-cameroun.com","71","10-07-2025 16:53:48","MATE=
CH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005449484","NKO=
MKANA ELIZA HOTEL","","10-07-2025 16:41:22","10-07-2025 16:39:15","10-07-20=
25 16:42:01","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed //Site stabilised","","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site went down due to PWC Overloaded and S=
S IHS Bernard Atangana confirmed //Site stabilised","gerard.tchangoue@matec=
h-cameroun.com","129","10-07-2025 16:41:22","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005449256","Oko=
la","","10-07-2025 16:01:38","10-07-2025 16:00:16","10-07-2025 18:29:29","G=
rid outage.gen start and stopped due to alarm""high temp""//We added water =
and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age.gen start and stopped due to alarm""high temp""//We added water and gen=
 manually started","gerard.tchangoue@matech-cameroun.com","83","10-07-2025 =
16:01:38","MATECH CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0005449071","Eto=
udi 2","","10-07-2025 15:35:53","10-07-2025 15:34:46","10-07-2025 15:36:46"=
,"Grid fluctuation, site went down because Gen failed to start due to grid =
bad voltage // Site stabilised","Fabrice Pouakam","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site wen=
t down because Gen failed to start due to grid bad voltage // Site stabilis=
ed","gerard.tchangoue@matech-cameroun.com","68","10-07-2025 15:35:53","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005449044","S=
IMBOCK BONAMBAPE","","10-07-2025 15:30:52","10-07-2025 15:30:48","10-07-202=
5 15:32:52","Grid outage, Site went down before Gen start due to poor backu=
p // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup // Site stabilised","edwige.kapawo@matech-came=
roun.com","6","10-07-2025 15:30:52","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005448312","N=
kolondom","","10-07-2025 13:49:44","10-07-2025 13:41:38","10-07-2025 14:03:=
10","Grid outage,gen failed to start due to ATS disfunction //He reconfigur=
ated ATS and put site and mode auto","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid outage,gen failed to start d=
ue to ATS disfunction //He reconfigurated ATS and put site and mode auto","=
gaelle.njiofack@matech-cameroun.com","488","10-07-2025 13:49:44","MATECH CM=
R"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005448249","E=
foulan","","10-07-2025 13:37:29","10-07-2025 13:28:14","10-07-2025 15:00:04=
","Active// No power issue site on grid with Ubaie=3D53V, Site on GRID The =
TX Fme Hosiah  (674007438/huawei) is informed","MINKA NICOLAS","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power issue site on grid with Ubaie=3D53V, Site on GRID The TX =
Fme Hosiah  (674007438/huawei) is informed","gaelle.njiofack@matech-camerou=
n.com","556","10-07-2025 13:37:29","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005448234","Ona=
ngondi (melen bikop)","","10-07-2025 13:33:05","10-07-2025 13:25:49","10-07=
-2025 13:28:49","ACTIVE// No power issue on site U=3D 55.5V site on Grid, T=
he TX Rodrigue Moungan (651319438) from Huawei is working on site","Fanda B=
rice","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","ACTIVE// No power issue on site U=3D 55.5V site on Grid, =
The TX Rodrigue Moungan (651319438) from Huawei is working on site","franck=
.nkomot@matech-cameroun.com","438","10-07-2025 13:33:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005448065","C-Suprem=
e","","10-07-2025 13:09:01","10-07-2025 13:06:05","10-07-2025 15:10:37","Ca=
scaded Incident from TTO5627493","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k) // Grid stabilised","system","284275","10-07-2025 13:09:01=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005448064","Acropole=
","","10-07-2025 13:09:00","10-07-2025 13:06:05","10-07-2025 15:10:37","Cas=
caded Incident from TTO5627493","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site Went down due =
to PWC overload, (210A ,12k) // Grid stabilised","system","284275","10-07-2=
025 13:09:00","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005448055","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","10-07-2025 13:07:11","10-07-2025 1=
3:06:05","10-07-2025 15:10:37","Grid fluctuations ,Site Went down due to PW=
C overload, (210A ,12k) // Grid stabilised","MINKA NICOLAS","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations =
,Site Went down due to PWC overload, (210A ,12k) // Grid stabilised","gaell=
e.njiofack@matech-cameroun.com","67","10-07-2025 13:07:11","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005448042","Aka=
k-Nkozoa-MTN-IHS","","10-07-2025 13:04:34","10-07-2025 12:55:59","10-07-202=
5 14:27:20","Grid outage, Site went down because Gen started and stopped wi=
th ""low oil pressure"" alarm// He reset card GE and gen manually started",=
"Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid outage, Site went down because Gen started and stopped with ""l=
ow oil pressure"" alarm// He reset card GE and gen manually started","franc=
k.nkomot@matech-cameroun.com","518","10-07-2025 13:04:34","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005447941","O=
lembe","","10-07-2025 12:45:43","10-07-2025 12:44:34","10-07-2025 13:16:18"=
,"Site down due to work ( PM ) // End of work","Fabrice Pouakam","Installat=
ion Activity","Passive","Planned Activity","Installation Activity","Site do=
wn due to work ( PM ) // End of work","gaelle.njiofack@matech-cameroun.com"=
,"70","10-07-2025 12:45:43","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005447909","A=
fanoya","","10-07-2025 12:38:23","10-07-2025 12:12:14","10-07-2025 12:43:50=
","Grid outage .gen failed to start ue to battery GE discharged causing by =
charging alternator faulty//Gen manually started with external battery","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alte=
rnator","Grid outage .gen failed to start ue to battery GE discharged causi=
ng by charging alternator faulty//Gen manually started with external batter=
y","gaelle.njiofack@matech-cameroun.com","1608","10-07-2025 12:38:23","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_546","IHS_YND_419","NOCINC0005447625","N=
gog Mapubi","","10-07-2025 11:59:57","10-07-2025 11:36:48","10-07-2025 12:0=
8:04"," No power issue on site ,site on Gen with Ubaie=3D 54,8V The fme tx =
Etienne fopa // 695033981 of huawei is informed","Kemeni Franklin","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m"," No power issue on site ,site on Gen with Ubaie=3D 54,8V The fme tx Eti=
enne fopa // 695033981 of huawei is informed","gaelle.njiofack@matech-camer=
oun.com","1390","10-07-2025 11:59:57","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005447611","B=
arriere","","10-07-2025 11:57:25","10-07-2025 11:53:15","10-07-2025 13:40:3=
3","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"gaelle.njiofack@matech-cameroun.com","252","10-07-2025 11:57:25","MATECH C=
MR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0005447317","Lob=
o 2","","10-07-2025 11:06:16","10-07-2025 10:51:48","10-07-2025 13:38:48","=
Grid outage.gen start and stopped due to alarm""high temp""//We added water=
 and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","P=
assive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid ou=
tage.gen start and stopped due to alarm""high temp""//We added water and ge=
n manually started","franck.nkomot@matech-cameroun.com","869","10-07-2025 1=
1:06:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0005447245","Mbankolo=
 petit paris","","10-07-2025 10:55:08","10-07-2025 10:14:08","10-07-2025 11=
:50:08","Cascaded Incident from TTO5626363","Mboua Thierry","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage.site went down=
 due to bad grid fluctuations//We bypass grid and gen manually started ","s=
ystem","1222264","10-07-2025 10:55:08","MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0005447226","M=
beng","","10-07-2025 10:52:32","10-07-2025 10:35:18","10-07-2025 13:48:22",=
"Grid outage, Site went down because Gen started and stopped with ""high te=
mp"" alarm casing b radiator leakage// He fixed radiator and gen manually s=
tarted ","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Radi=
ator Leakage","Grid outage, Site went down because Gen started and stopped =
with ""high temp"" alarm casing b radiator leakage// He fixed radiator and =
gen manually started ","gaelle.njiofack@matech-cameroun.com","1036","10-07-=
2025 10:52:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005447131","SAA 2","=
","10-07-2025 10:38:35","10-07-2025 10:24:17","10-07-2025 11:10:52","","Par=
ker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active","	N=
o power issue on site ,site on Gen with Ubaie =3D54.7V The Tx Technician fr=
om Huawei Gr=E9goire//654547479 is informed","system","1221664","10-07-2025=
 10:38:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0005447130","Saa","IH=
S_YND_404","10-07-2025 10:38:35","10-07-2025 10:24:17","10-07-2025 11:10:52=
","	No power issue on site ,site on Gen with Ubaie =3D54.7V The Tx Technici=
an from Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","	No power issue on site ,site on Gen with Ubaie =3D54.7V The Tx Technici=
an from Huawei Gr=E9goire//654547479 is informed","system","858","10-07-202=
5 10:38:35","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005447082","O=
kola OCM","","10-07-2025 10:30:28","10-07-2025 10:24:17","10-07-2025 13:28:=
53","Grid outage, gen fails to start  due to Ge battery faulty // Gen start=
ed with external battery","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Generator Battery","Grid outage, Site down due to=
 Gen battery faulty // Gen started with external battery","gaelle.njiofack@=
matech-cameroun.com","373","10-07-2025 10:30:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0005447039","Montee-J=
ouvence-II","","10-07-2025 10:22:21","10-07-2025 10:09:00","10-07-2025 10:2=
4:08","Cascaded Incident from TTO5626324","Hyemafo Gildas","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Site impacted by Nkolzie CTR_6=
72 not manage by IHS","system","266307","10-07-2025 10:22:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0005447038","Accacia =
New","","10-07-2025 10:22:20","10-07-2025 10:09:00","10-07-2025 10:24:08","=
Cascaded Incident from TTO5626324","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","Site impacted by Nkolzie CTR_672 not manage by IHS"=
,"system","266308","10-07-2025 10:22:20","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0005447011","Oko=
lo Kilombo","","10-07-2025 10:19:47","10-07-2025 10:12:40","10-07-2025 10:1=
5:40","Active //no power issue Ubaie:55V site on Grid The TX FME Symphorien=
 (675295205) from Huawei is informed.","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 //no power issue Ubaie:55V site on Grid The TX FME Symphorien (675295205) =
from Huawei is informed.","franck.nkomot@matech-cameroun.com","428","10-07-=
2025 10:19:47","MATECH CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0005447008","A=
FEME NORD","IHS_YND_808","10-07-2025 10:19:14","10-07-2025 10:14:08","10-07=
-2025 11:50:08","Grid outage.site went down due to bad grid fluctuations//W=
e bypass grid and gen manually started ","TIENTCHEU NZETCHIEU GAEL","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid out=
age.site went down due to bad grid fluctuations//We bypass grid and gen man=
ually started ","gaelle.njiofack@matech-cameroun.com","307","10-07-2025 10:=
19:14","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005446974","D=
amas","IHS_YND_562, IHS_YND_518","10-07-2025 10:14:09","10-07-2025 10:09:00=
","10-07-2025 10:24:08","Site impacted by Nkolzie CTR_672 not manage by IHS=
","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment F=
ailure","Affected by 3rd Party Site","Site impacted by Nkolzie CTR_672 not =
manage by IHS","gaelle.njiofack@matech-cameroun.com","310","10-07-2025 10:1=
4:09","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005446973","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","10-07-2025 10:13:56","10-07-20=
25 10:08:48","10-07-2025 13:17:48","Grid outage, Site went down because Gen=
 start and stopped with ""High temps ""alarm // he added water and manually=
 start the Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","AC=
DG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site =
went down because Gen start and stopped with ""High temps ""alarm // he add=
ed water and manually start the Gen","franck.nkomot@matech-cameroun.com","3=
09","10-07-2025 10:13:56","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0005446962","Yok=
o MTN","IHS_YND_475","10-07-2025 10:12:17","10-07-2025 10:02:59","10-07-202=
5 10:14:59","Grid outage, Site went down because gen failed to start due to=
 automatism system dysfunctionning // Grid return","Parker Tchoup","Equipme=
nt Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site wen=
t down because gen failed to start due to automatism system dysfunctionning=
 // Grid return","franck.nkomot@matech-cameroun.com","559","10-07-2025 10:1=
2:17","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0005446958","Ngo=
um","","10-07-2025 10:11:25","10-07-2025 10:02:59","10-07-2025 10:14:59",""=
,"Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage, Site went down because gen failed to start due to automa=
tism system dysfunctionning // Grid return","franck.nkomot@matech-cameroun.=
com","295244","10-07-2025 10:11:25","MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0005446947","Abo=
me","","10-07-2025 10:10:21","10-07-2025 10:00:59","10-07-2025 11:03:59","G=
rid outage.gen failed to start due to automation malfunctonning//Gen manual=
ly started ","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","=
ATS-AMF Issue","Grid outage.gen failed to start due to automation malfuncto=
nning//Gen manually started ","franck.nkomot@matech-cameroun.com","565","10=
-07-2025 10:10:21","MATECH CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0005446919","I=
mm-Olympique","","10-07-2025 10:06:23","10-07-2025 10:01:17","10-07-2025 10=
:18:17","Grid outage,site went down because Gen failed to start due to Gen =
overload(20KVA//295A) SS HIS Raoul is informed//Grid return","Paul BIBOUM",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,site=
 went down because Gen failed to start due to Gen overload(20KVA//295A) SS =
HIS Raoul is informed//Grid return","gaelle.njiofack@matech-cameroun.com","=
307","10-07-2025 10:06:23","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005446896","A=
wae Ewonkan","","10-07-2025 10:03:22","10-07-2025 09:55:50","10-07-2025 10:=
11:46","( unstable ) Grid outage site went down due to Gen Overload (20Kva,=
 Iload 320A)IHS SS Alphonse is informed // Grid stabilised","Albran Byorel"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","( unstable ) Gr=
id outage site went down due to Gen Overload (20Kva, Iload 320A)IHS SS Alph=
onse is informed // Grid stabilised","gaelle.njiofack@matech-cameroun.com",=
"454","10-07-2025 10:03:22","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005446849","M=
ontee-Des-Soeurs","","10-07-2025 09:56:33","10-07-2025 09:53:27","10-07-202=
5 10:00:47","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","gaelle.njiofack@matech-cameroun.com","188","10-07-2025 09:56:3=
3","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005446790","Acropole=
","","10-07-2025 09:47:19","10-07-2025 09:36:08","10-07-2025 11:10:11","Cas=
caded Incident from TTO5626095","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site Went down due =
to PWC overload, (210A ,12k) // Grid stabilised","system","268244","10-07-2=
025 09:47:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005446789","Olezoa O=
CM","","10-07-2025 09:47:19","10-07-2025 09:36:08","10-07-2025 11:10:11","C=
ascaded Incident from TTO5626095","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC over=
load, (210A ,12k) // Grid stabilised","system","268242","10-07-2025 09:47:1=
9","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005446791","C-Suprem=
e","","10-07-2025 09:47:19","10-07-2025 09:36:08","10-07-2025 11:10:11","Ca=
scaded Incident from TTO5626095","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k) // Grid stabilised","system","268243","10-07-2025 09:47:19=
","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005446757","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","10-07-2025 09:41:34",=
"10-07-2025 09:36:08","10-07-2025 11:10:11","Grid fluctuations ,Site Went d=
own due to PWC overload, (210A ,12k) // Grid stabilised","MINKA NICOLAS","G=
rid Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue","=
Grid fluctuations ,Site Went down due to PWC overload, (210A ,12k) // Grid =
stabilised","gaelle.njiofack@matech-cameroun.com","327","10-07-2025 09:41:3=
4","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005446605","C-Suprem=
e","","10-07-2025 09:20:05","10-07-2025 09:16:07","10-07-2025 09:16:35","Ca=
scaded Incident from TTO5625913","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k) // Grid  stabilised","system","262176","10-07-2025 09:20:0=
5","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005446604","Acropole=
","","10-07-2025 09:20:05","10-07-2025 09:16:07","10-07-2025 09:16:35","Cas=
caded Incident from TTO5625913","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site Went down due =
to PWC overload, (210A ,12k) // Grid  stabilised","system","262175","10-07-=
2025 09:20:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005446603","Olezoa O=
CM","","10-07-2025 09:20:04","10-07-2025 09:16:07","10-07-2025 09:16:35","C=
ascaded Incident from TTO5625913","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC over=
load, (210A ,12k) // Grid  stabilised","system","262174","10-07-2025 09:20:=
04","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005446588","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","10-07-2025 09:18:21",=
"10-07-2025 09:16:07","10-07-2025 09:16:35","Grid fluctuations ,Site Went d=
own due to PWC overload, (210A ,12k) // Grid  stabilised","MINKA NICOLAS","=
Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue",=
"Grid fluctuations ,Site Went down due to PWC overload, (210A ,12k) // Grid=
  stabilised","gaelle.njiofack@matech-cameroun.com","135","10-07-2025 09:18=
:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005446497","C-Suprem=
e","","10-07-2025 09:00:31","10-07-2025 08:56:06","10-07-2025 08:56:59","Ca=
scaded Incident from TTO5625796","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k) // Site stabilised","system","263367","10-07-2025 09:00:31=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005446495","Olezoa O=
CM","","10-07-2025 09:00:30","10-07-2025 08:56:06","10-07-2025 08:56:59","C=
ascaded Incident from TTO5625796","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC over=
load, (210A ,12k) // Site stabilised","system","263367","10-07-2025 09:00:3=
0","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005446496","Acropole=
","","10-07-2025 09:00:30","10-07-2025 08:56:06","10-07-2025 08:56:59","Cas=
caded Incident from TTO5625796","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site Went down due =
to PWC overload, (210A ,12k) // Site stabilised","system","263366","10-07-2=
025 09:00:30","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005446482","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","10-07-2025 08:58:45",=
"10-07-2025 08:56:06","10-07-2025 08:56:59","Grid fluctuations ,Site Went d=
own due to PWC overload, (210A ,12k) // Site stabilised","MINKA NICOLAS","G=
rid Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue","=
Grid fluctuations ,Site Went down due to PWC overload, (210A ,12k) // Site =
stabilised","gaelle.njiofack@matech-cameroun.com","471","10-07-2025 08:58:4=
5","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005446319","Evo=
doula MTN","","10-07-2025 08:28:52","10-07-2025 08:24:45","10-07-2025 09:02=
:45","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","fran=
ck.nkomot@matech-cameroun.com","248","10-07-2025 08:28:52","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005446197","B=
arriere","","10-07-2025 07:58:38","10-07-2025 07:54:27","10-07-2025 11:43:1=
6","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"gaelle.njiofack@matech-cameroun.com","253","10-07-2025 07:58:38","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005445963","MBIMBIM"=
,"","10-07-2025 07:02:30","10-07-2025 05:41:59","10-07-2025 07:59:40","Casc=
aded Incident from TTO5624853","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","GRID outage, water pump faulty // water=
 repaired and GEN manually started","system","289310","10-07-2025 07:02:30"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005445962","Ngouetou=
","","10-07-2025 07:02:30","10-07-2025 05:41:59","10-07-2025 07:59:40","Cas=
caded Incident from TTO5624853","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","GRID outage, water pump faulty // wate=
r repaired and GEN manually started","system","289313","10-07-2025 07:02:30=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005445960","Matsari"=
,"","10-07-2025 07:02:29","10-07-2025 05:41:59","10-07-2025 07:59:40","Casc=
aded Incident from TTO5624853","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","GRID outage, water pump faulty // water=
 repaired and GEN manually started","system","289314","10-07-2025 07:02:29"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005445961","Yoko OCM=
","","10-07-2025 07:02:29","10-07-2025 05:41:59","10-07-2025 07:59:40","Cas=
caded Incident from TTO5624853","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","GRID outage, water pump faulty // wate=
r repaired and GEN manually started","system","289312","10-07-2025 07:02:29=
","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005445886","B=
arriere","","10-07-2025 06:45:20","10-07-2025 06:44:13","10-07-2025 06:48:4=
3","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","	Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised"=
,"gaelle.njiofack@matech-cameroun.com","69","10-07-2025 06:45:20","MATECH C=
MR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005445879","A=
wae Ewonkan","","10-07-2025 06:44:21","10-07-2025 06:42:12","10-07-2025 06:=
43:12","No power issue on site Tx issue U=3D51.3V site on Grid , the FME TX=
 Leonel Steve //655184876 from Huawei is informed","Albran Byorel","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Tx issue U=3D51.3V site on Grid , the FME TX Leo=
nel Steve //655184876 from Huawei is informed","gaelle.njiofack@matech-came=
roun.com","131","10-07-2025 06:44:21","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005445607","M=
ambine","","10-07-2025 05:38:31","10-07-2025 05:31:22","10-07-2025 05:40:54=
","Grid issue, fuse disconnect, Gen turn until fuel shortage // Tank tilt a=
nd site on Gen (Refueling on going)","Fanda Brice","Fuel Outage","Passive",=
"Diesel","Diesel Outage","Grid issue, fuse disconnect, Gen turn until fuel =
shortage // Tank tilt and site on Gen (Refueling on going)","gaelle.njiofac=
k@matech-cameroun.com","431","10-07-2025 05:38:31","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005445605","M=
vog Mbi New","","10-07-2025 05:37:16","10-07-2025 05:34:10","10-07-2025 05:=
38:26","Grid fluctuations ,Site Went down due to PWC overload, (210A ,12k) =
// Site stabilised","MINKA NICOLAS","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Grid fluctuations ,Site Went down due to P=
WC overload, (210A ,12k) // Site stabilised","loic.noumsi@matech-cameroun.c=
om","187","10-07-2025 05:37:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005445134","Ngoum","=
","10-07-2025 02:59:50","10-07-2025 02:57:58","10-07-2025 03:19:36","Cascad=
ed Incident from TTO5624318","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down due to Grid f=
luctuations and no rcp on site // He bypassed Grid and started Gen manually=
","system","277648","10-07-2025 02:59:50","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0005445133","Yok=
o MTN","IHS_YND_475","10-07-2025 02:59:04","10-07-2025 02:57:58","10-07-202=
5 03:19:36","Grid outage, site went down due to Grid fluctuations and no rc=
p on site // He bypassed Grid and started Gen manually","Parker Tchoup","Gr=
id Supply","Passive","Grid","National Grid - Poles Failed","Grid outage, si=
te went down due to Grid fluctuations and no rcp on site // He bypassed Gri=
d and started Gen manually","loic.noumsi@matech-cameroun.com","68","10-07-2=
025 02:59:04","MATECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0005445055","HOP=
ITAL GENERAL RAIL YDE","","10-07-2025 02:34:13","10-07-2025 02:29:44","10-0=
7-2025 05:19:30","","Delor Telezing","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because Gen failed to=
 start due to CARD GE dysfunctionning // Grid return","loic.noumsi@matech-c=
ameroun.com","279337","10-07-2025 02:34:13","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005445049","Pha=
rmacie Bleue","IHS_YND_801","10-07-2025 02:32:49","10-07-2025 02:29:44","10=
-07-2025 05:19:30","Grid outage, site went down because Gen failed to start=
 due to CARD GE dysfunctionning // Grid return","Siligap Boris","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went=
 down because Gen failed to start due to CARD GE dysfunctionning // Grid re=
turn","loic.noumsi@matech-cameroun.com","186","10-07-2025 02:32:49","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005444920","E=
toudi","","10-07-2025 01:36:40","10-07-2025 01:33:25","10-07-2025 02:15:59"=
,"Grid outage, site went down because Gen started and stopped due to disjun=
ction of Gen CB (100A) // He rearmed it, site on GEN","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Grid outage, si=
te went down because Gen started and stopped due to disjunction of Gen CB (=
100A) // He rearmed it, site on GEN","loic.noumsi@matech-cameroun.com","196=
","10-07-2025 01:36:40","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005444810","Evo=
doula MTN","","10-07-2025 01:05:31","10-07-2025 01:02:33","10-07-2025 01:04=
:42","Grid outage, Site went down before Gen start due to poor backup// GRI=
D stabilised","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// GRID stabilised","loic.noumsi@matech-camer=
oun.com","179","10-07-2025 01:05:31","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005444394","B=
arriere","","10-07-2025 00:05:15","10-07-2025 00:02:00","10-07-2025 00:31:5=
3","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"gaelle.njiofack@matech-cameroun.com","196","10-07-2025 00:05:15","MATECH C=
MR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005444216","S=
aa","","09-07-2025 23:14:45","09-07-2025 23:11:38","09-07-2025 23:18:11","I=
ncorrectly logget tickets","Parker Tchoup","Incorrectly Logged Tickets","Er=
ror","Error","Error","Incorrectly logget tickets","gaelle.njiofack@matech-c=
ameroun.com","188","09-07-2025 23:14:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0005444163","NYANON/D=
EMBO","","09-07-2025 23:02:31","09-07-2025 22:59:01","09-07-2025 23:00:55",=
"Cascaded Incident from TTO5623220","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","Active//No power issue on =
site Ubaie :  55,5V site on Gen and The FME TX Gregoire From huawei is info=
rmed ","system","291953","09-07-2025 23:02:31","MATECH CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0005444157","Nya=
hoo","IHS_EDA_102","09-07-2025 23:01:14","09-07-2025 22:59:01","09-07-2025 =
23:00:55","Active//No power issue on site Ubaie :  55,5V site on Gen and Th=
e FME TX Gregoire From huawei is informed ","TIENTCHEU NZETCHIEU GAEL","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active//No power issue on site Ubaie :  55,5V site on Gen and The F=
ME TX Gregoire From huawei is informed ","loic.noumsi@matech-cameroun.com",=
"134","09-07-2025 23:01:14","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005444147","C=
-Supreme","","09-07-2025 22:57:21","09-07-2025 22:56:15","09-07-2025 23:06:=
16","	Active // No power issue, site on Grid with Ubaie=3D54.2V, Brice Tsag=
ue (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power i=
ssue, site on Grid with Ubaie=3D54.2V, Brice Tsague (650 21 40 96 / Huawei)=
 is informed","gaelle.njiofack@matech-cameroun.com","67","09-07-2025 22:57:=
21","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005444144","A=
wae Ewonkan","","09-07-2025 22:57:01","09-07-2025 22:52:56","10-07-2025 01:=
02:51","No power issue on site Tx issue U=3D51.3V site on Grid , the FME TX=
 Leonel Steve //655184876 from Huawei is informed","Albran Byorel","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Tx issue U=3D51.3V site on Grid , the FME TX Leo=
nel Steve //655184876 from Huawei is informed","loic.noumsi@matech-cameroun=
.com","247","09-07-2025 22:57:01","MATECH CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0005443893","N=
ew-Marche-Melen","","09-07-2025 22:06:07","09-07-2025 22:02:46","10-07-2025=
 11:25:29","","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid outage,no space to deploy mobile gen // GRID RESTORAT=
ION","vanel.mbiada@matech-cameroun.com","316854","09-07-2025 22:06:07","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0005443886","A=
n-Marche-Melen","IHS_YND_141","09-07-2025 22:05:08","09-07-2025 22:02:46","=
10-07-2025 11:25:29","Grid outage,no space to deploy mobile gen // GRID RES=
TORATION","","Grid Supply","Passive","Grid","National Grid - Grid Outage Is=
sue","Grid outage,no space to deploy mobile gen // GRID RESTORATION","vanel=
.mbiada@matech-cameroun.com","143","09-07-2025 22:05:08","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005443568","A=
wae Ewonkan","","09-07-2025 21:14:07","09-07-2025 21:08:00","09-07-2025 21:=
35:51","No power issue on site Tx issue U=3D54.2V site on Grid , the FME TX=
 Leonel Steve //655184876 from Huawei is informed","Albran Byorel","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Tx issue U=3D54.2V site on Grid , the FME TX Leo=
nel Steve //655184876 from Huawei is informed","vanel.mbiada@matech-camerou=
n.com","368","09-07-2025 21:14:07","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005443502","SIM=
BOCK BONAMBAPE","","09-07-2025 21:04:13","09-07-2025 21:02:03","09-07-2025 =
21:04:03","Active // No power issue site on grid with Ubaie: 54.5V TX FME F=
lubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive // No power issue site on grid with Ubaie: 54.5V TX FME Flubert (65426=
6068) from Huawei is informed","cedric.tiani@matech-cameroun.com","131","09=
-07-2025 21:04:13","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005443365","C=
-Supreme","","09-07-2025 20:43:21","09-07-2025 20:42:14","09-07-2025 20:48:=
59","Active // No power issue, site on Grid with Ubaie=3D54.2V, Brice Tsagu=
e (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power is=
sue, site on Grid with Ubaie=3D54.2V, Brice Tsague (650 21 40 96 / Huawei) =
is informed","vanel.mbiada@matech-cameroun.com","68","09-07-2025 20:43:21",=
"MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005443345","Nko=
langaa","","09-07-2025 20:37:46","09-07-2025 20:28:36","09-07-2025 21:41:27=
","Site went down because CB(125A) tripped in DC BOX who feeds equipments M=
TN  due to load increase// CB put back on","Mba Lazare Herve","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Si=
te went down because CB(125A) tripped in DC BOX who feeds equipments MTN  d=
ue to load increase// CB put back on","cedric.tiani@matech-cameroun.com","5=
51","09-07-2025 20:37:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0005443291","Leboudi"=
,"","09-07-2025 20:27:40","09-07-2025 20:20:36","09-07-2025 21:50:43","Casc=
aded Incident from TTO5622185","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down =
because Gen failed to start due to PWC ZTE disfunction// He bypassed it, Si=
te on Gen","system","1222081","09-07-2025 20:27:40","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0005443271","N=
kolafeme","IHS_YND_309","09-07-2025 20:22:51","09-07-2025 20:20:36","09-07-=
2025 21:55:08","Grid fluctuation,site went down because Gen failed to start=
 due to Grid bad voltage,no rcp on it //He bypassed it and manually started=
 the Gen	","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","Grid outage, Site went down because Ge=
n failed to start due to PWC ZTE disfunction// He bypassed it, Site on Gen"=
,"vanel.mbiada@matech-cameroun.com","137","09-07-2025 20:22:51","MATECH CMR=
"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005442971","B=
arriere","","09-07-2025 19:30:54","09-07-2025 19:28:48","09-07-2025 22:05:0=
5","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"vanel.mbiada@matech-cameroun.com","128","09-07-2025 19:30:54","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005442786","SIM=
BOCK BONAMBAPE","","09-07-2025 18:50:29","09-07-2025 18:49:19","09-07-2025 =
19:12:58","Active // No power issue site on grid with Ubaie: 54.5V TX FME F=
lubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive // No power issue site on grid with Ubaie: 54.5V TX FME Flubert (65426=
6068) from Huawei is informed","cedric.tiani@matech-cameroun.com","72","09-=
07-2025 18:50:29","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0005442706","B=
itoto","","09-07-2025 18:36:28","09-07-2025 18:27:59","09-07-2025 19:28:49"=
,"Grid outage, Site went down because Gen failed to start due to PWC dysfun=
ctionning// He reset PWC, Site on Grid","Mba Lazare Herve","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, Site w=
ent down because Gen failed to start due to PWC dysfunctionning// He reset =
PWC, Site on Grid","cedric.tiani@matech-cameroun.com","510","09-07-2025 18:=
36:28","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0005442332","S=
AA 2","","09-07-2025 17:54:28","09-07-2025 17:50:14","09-07-2025 18:04:12",=
"Grid outage, site went down because gen start and stopped with high temp a=
larm // He oppened the doors and Gen manually started","Parker Tchoup","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Leve=
l Issue","Grid outage, site went down because gen start and stopped with hi=
gh temp alarm // He oppened the doors and Gen manually started","vanel.mbia=
da@matech-cameroun.com","255","09-07-2025 17:54:28","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005442324","A=
kak-Nkozoa-MTN-IHS","","09-07-2025 17:53:05","09-07-2025 17:51:00","09-07-2=
025 17:57:09","","Fabrice Pouakam","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","No power issue on site Ubaie: 54V site on Grid. Sympho=
rien (691316854/Huawei) is informed.","vanel.mbiada@matech-cameroun.com","1=
216646","09-07-2025 17:53:05","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005442279","B=
arriere IHS","","09-07-2025 17:49:57","09-07-2025 17:48:01","09-07-2025 20:=
02:25","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed//Grid return","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to =
Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed//Grid return","van=
el.mbiada@matech-cameroun.com","118","09-07-2025 17:49:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005442093","Nkolfon =
Cimencam","","09-07-2025 17:16:21","09-07-2025 17:08:39","09-07-2025 19:57:=
53","Cascaded Incident from TTO5620829","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirm=
ed//Grid return","system","276914","09-07-2025 17:16:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005442070","Ahala","=
","09-07-2025 17:12:20","09-07-2025 17:08:39","09-07-2025 19:57:53","Cascad=
ed Incident from TTO5620829","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Gen o=
verload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed//Grid re=
turn","system","276915","09-07-2025 17:12:20","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005442060","M=
eyo","IHS_YND_257, IHS_YND_762","09-07-2025 17:11:49","09-07-2025 17:08:39"=
,"09-07-2025 20:03:37","Grid outage, site went down due to Gen overload (17=
KVA, 260A) SS HIS Felix Zambe is informed and confirmed//Grid return","Hyem=
afo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix Zamb=
e is informed and confirmed//Grid return","vanel.mbiada@matech-cameroun.com=
","192","09-07-2025 17:11:49","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005442015","A=
wae Ewonkan","","09-07-2025 17:04:26","09-07-2025 17:01:19","09-07-2025 17:=
10:57","No power issue on site Tx issue U=3D54.2V site on Grid , the FME TX=
 Leonel Steve //655184876 from Huawei is informed","Albran Byorel","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Tx issue U=3D54.2V site on Grid , the FME TX Leo=
nel Steve //655184876 from Huawei is informed","vanel.mbiada@matech-camerou=
n.com","189","09-07-2025 17:04:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005441891","Acropole=
","","09-07-2025 16:44:39","09-07-2025 16:42:32","09-07-2025 16:47:50","Cas=
caded Incident from TTO5620631","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site Went down due =
to PWC overload, (210A ,12k) // Site stabilised","system","264216","09-07-2=
025 16:44:39","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005441884","M=
vog Mbi New","IHS_YND_036","09-07-2025 16:43:43","09-07-2025 16:42:32","09-=
07-2025 16:47:50","Grid fluctuations ,Site Went down due to PWC overload, (=
210A ,12k) // Site stabilised","MINKA NICOLAS","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid fluctuations ,Site Went do=
wn due to PWC overload, (210A ,12k) // Site stabilised","vanel.mbiada@matec=
h-cameroun.com","72","09-07-2025 16:43:43","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005441867","Evo=
doula MTN","","09-07-2025 16:39:22","09-07-2025 16:38:12","09-07-2025 16:39=
:12","Grid outage, Site went down before Gen start due to poor backup// GRI=
D return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// GRID return","cedric.tiani@matech-cameroun.com=
","71","09-07-2025 16:39:22","MATECH CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0005441827","San=
ta Barbara Yde","","09-07-2025 16:28:06","09-07-2025 16:26:33","09-07-2025 =
16:28:58","Active//No power issue on site; Ubaie: 54.8 V site on Grid The F=
ME Synphorien//691316854// from Huawei is informed.","Delor Telezing","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site; Ubaie: 54.8 V site on Grid The FME S=
ynphorien//691316854// from Huawei is informed.","cedric.tiani@matech-camer=
oun.com","93","09-07-2025 16:28:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005441803","C-Suprem=
e","","09-07-2025 16:25:49","09-07-2025 16:22:46","09-07-2025 16:28:14","Ca=
scaded Incident from TTO5620532","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k) // Site stabilised","system","265392","09-07-2025 16:25:49=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005441802","Acropole=
","","09-07-2025 16:25:49","09-07-2025 16:22:46","09-07-2025 16:28:14","Cas=
caded Incident from TTO5620532","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site Went down due =
to PWC overload, (210A ,12k) // Site stabilised","system","265392","09-07-2=
025 16:25:49","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005441799","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","09-07-2025 16:24:58","09-07-2025 1=
6:22:46","09-07-2025 16:28:14","	Grid fluctuations ,Site Went down due to P=
WC overload, (210A ,12k) // Site stabilised","MINKA NICOLAS","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations=
 ,Site Went down due to PWC overload, (210A ,12k) // Site stabilised","vane=
l.mbiada@matech-cameroun.com","133","09-07-2025 16:24:58","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005441745","B=
arriere","","09-07-2025 16:20:32","09-07-2025 16:18:23","09-07-2025 18:04:5=
7","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"vanel.mbiada@matech-cameroun.com","131","09-07-2025 16:20:32","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005441652","N=
kolfon Cimencam","","09-07-2025 16:06:32","09-07-2025 16:02:23","09-07-2025=
 16:08:04","Grid outage, Site went down before Gen start due to poor backup=
//Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup//Grid return","vanel.mbiada@matech-cameroun.com","250=
","09-07-2025 16:06:32","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005441592","O=
LAMA","","09-07-2025 15:59:32","09-07-2025 15:54:31","09-07-2025 16:01:12",=
"Active // No power issue on site Ubaie: 54.5V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue on site Ubaie: 54.5V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","vanel.mbiada@matech-cameroun.com","303","09-07-2=
025 15:59:32","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005441538","Evo=
doula MTN","","09-07-2025 15:50:22","09-07-2025 15:48:46","09-07-2025 16:13=
:27","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","cedr=
ic.tiani@matech-cameroun.com","97","09-07-2025 15:50:22","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005441494","M=
vog-Ada_OCM","","09-07-2025 15:43:50","09-07-2025 15:41:43","09-07-2025 16:=
04:59","Grid Only, No space to deploy MGE// Grid Return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to=
 deploy MGE// Grid Return","vanel.mbiada@matech-cameroun.com","129","09-07-=
2025 15:43:50","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005441151","NTU=
I TOWN","","09-07-2025 14:41:54","09-07-2025 14:39:14","09-07-2025 15:13:05=
","Site went down due to work of SS HIS Felix Bateu  on site (securing tran=
smission)//End of work","Parker Tchoup","Installation Activity","Passive","=
Planned Activity","Installation Activity","Site went down due to work of SS=
 HIS Felix Bateu  on site (securing transmission)//End of work","cedric.tia=
ni@matech-cameroun.com","161","09-07-2025 14:41:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_508","NOCINC0005440821","Crf-Nsam=
","","09-07-2025 13:54:31","09-07-2025 13:44:43","09-07-2025 15:05:15","Cas=
caded Incident from TTO5619358","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to Gen=
 overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed// Grid=
 return","system","267684","09-07-2025 13:54:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_165","NOCINC0005440820","Ahala","=
","09-07-2025 13:54:30","09-07-2025 13:44:43","09-07-2025 16:03:08","Active=
//No power issue on site, Site on Grid UBAIE=3D53V FME  ZTE (Marc 659152679=
) is on site for working","MINKA NICOLAS","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issu=
e on site, Site on Grid UBAIE=3D53V FME  ZTE (Marc 659152679) is on site fo=
r working","system","587","09-07-2025 13:54:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005440819","Nkolfon =
Cimencam","","09-07-2025 13:54:30","09-07-2025 13:44:43","09-07-2025 15:05:=
15","Cascaded Incident from TTO5619358","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirm=
ed// Grid return","system","267685","09-07-2025 13:54:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005440817","Ahala","=
","09-07-2025 13:54:30","09-07-2025 13:44:43","09-07-2025 15:05:15","Cascad=
ed Incident from TTO5619358","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Gen o=
verload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed// Grid r=
eturn","system","267685","09-07-2025 13:54:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005440818","EBOM",""=
,"09-07-2025 13:54:30","09-07-2025 13:44:43","09-07-2025 16:05:40","Active/=
/No power issue on site U=3D54,4V site on Grid FME TX Leonel//655184876 fro=
m Huawei is informed	","Hyemafo Gildas","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue =
on site U=3D54,4V site on Grid FME TX Leonel//655184876 from Huawei is info=
rmed	","system","587","09-07-2025 13:54:30","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005440792","Mey=
o","IHS_YND_257, IHS_YND_762, IHS_YND_508","09-07-2025 13:51:08","09-07-202=
5 13:44:43","09-07-2025 15:12:13","Grid outage, site went down due to Gen o=
verload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed// Grid r=
eturn","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, site went down due to Gen overload (17KVA, 260A) SS HI=
S Felix Zambe is informed and confirmed// Grid return","gerard.tchangoue@ma=
tech-cameroun.com","386","09-07-2025 13:51:08","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005440682","SIM=
BOCK BONAMBAPE","","09-07-2025 13:34:08","09-07-2025 13:27:02","09-07-2025 =
14:29:54","Active // No power issue site on grid with Ubaie: 54.5V TX FME F=
lubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive // No power issue site on grid with Ubaie: 54.5V TX FME Flubert (65426=
6068) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","428"=
,"09-07-2025 13:34:08","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005440446","N=
kolfon Cimencam","","09-07-2025 12:58:38","09-07-2025 12:55:22","09-07-2025=
 13:31:47","Grid outage, Gen stopped with high temp alarm  // he added wate=
r in radiator and manual start of Gen","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - High Engine Temp - Clogged Radiator","Grid out=
age, Gen stopped with high temp alarm  // he added water in radiator and ma=
nual start of Gen","edwige.kapawo@matech-cameroun.com","198","09-07-2025 12=
:58:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005440218","C-Suprem=
e","","09-07-2025 12:18:54","09-07-2025 12:15:40","09-07-2025 12:16:23","Ca=
scaded Incident from TTO5618691","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k) // Site stabilised","system","1215194","09-07-2025 12:18:5=
4","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005440214","M=
vog Mbi New","IHS_YND_021","09-07-2025 12:17:50","09-07-2025 12:15:40","09-=
07-2025 12:16:23","Grid fluctuations ,Site Went down due to PWC overload, (=
210A ,12k) // Site stabilised","MINKA NICOLAS","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid fluctuations ,Site Went do=
wn due to PWC overload, (210A ,12k) // Site stabilised","edwige.kapawo@mate=
ch-cameroun.com","132","09-07-2025 12:17:50","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005439808","NKO=
MKANA ELIZA HOTEL","","09-07-2025 11:07:48","09-07-2025 11:06:43","09-07-20=
25 11:08:00","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed //Site stabilised","","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site went down due to PWC Overloaded and S=
S IHS Bernard Atangana confirmed //Site stabilised","gerard.tchangoue@matec=
h-cameroun.com","67","09-07-2025 11:07:48","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005439755","B=
arriere","","09-07-2025 11:01:08","09-07-2025 10:53:47","09-07-2025 11:58:0=
1","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed","edwige.kapawo@ma=
tech-cameroun.com","445","09-07-2025 11:01:08","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005439707","Lad=
a I Yde","","09-07-2025 10:50:45","09-07-2025 10:46:40","09-07-2025 11:06:5=
5","Active//No power issue on site ,site on Grid with Ubaie=3D54,3V The Tx =
FME Leonel Steve (655184876) from Huawei is informed.","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site ,site on Grid with Ubaie=3D54,3V =
The Tx FME Leonel Steve (655184876) from Huawei is informed.","gerard.tchan=
goue@matech-cameroun.com","246","09-07-2025 10:50:45","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005439698","S=
imbock OCM","","09-07-2025 10:48:01","09-07-2025 10:38:49","09-07-2025 10:4=
9:17","Site impacted by Nkolzie-II CTR_672 not managed by IHS","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","Site impacted by Nkolzie-II CTR_672 not managed by=
 IHS","edwige.kapawo@matech-cameroun.com","553","09-07-2025 10:48:01","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005439599","O=
LAMA","","09-07-2025 10:34:33","09-07-2025 10:24:59","09-07-2025 10:41:35",=
"Active // No power issue on site Ubaie: 54.5V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed.","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // =
No power issue on site Ubaie: 54.5V site on Gen The TX FME Henri (699949693=
) from Huawei is informed.","edwige.kapawo@matech-cameroun.com","576","09-0=
7-2025 10:34:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0005439579","Boumnyeb=
el","","09-07-2025 10:32:33","09-07-2025 10:13:22","09-07-2025 10:40:24","C=
ascaded Incident from TTO5617840","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because gen failed =
to start due to grid bad voltage no RCP // He bypass grid and manually star=
t the gen","system","265995","09-07-2025 10:32:33","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005439518","Evo=
doula MTN","","09-07-2025 10:26:03","09-07-2025 10:23:57","09-07-2025 10:46=
:58","Grid outage, Site went down before Gen start due to poor backup//Grid=
 return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup//Grid return","gerard.tchangoue@matech-cameroun.c=
om","127","09-07-2025 10:26:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0005439478","Mamb",""=
,"09-07-2025 10:18:25","09-07-2025 10:13:22","09-07-2025 10:40:24","Cascade=
d Incident from TTO5617840","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down because gen failed to sta=
rt due to grid bad voltage no RCP // He bypass grid and manually start the =
gen","system","265996","09-07-2025 10:18:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0005439476","Ndogbess=
ol","","09-07-2025 10:18:24","09-07-2025 10:13:22","09-07-2025 10:40:24","C=
ascaded Incident from TTO5617840","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because gen failed =
to start due to grid bad voltage no RCP // He bypass grid and manually star=
t the gen","system","265996","09-07-2025 10:18:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0005439477","Ngog Map=
ubi","","09-07-2025 10:18:24","09-07-2025 10:13:22","09-07-2025 10:40:24","=
Cascaded Incident from TTO5617840","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because gen failed=
 to start due to grid bad voltage no RCP // He bypass grid and manually sta=
rt the gen","system","265997","09-07-2025 10:18:24","MATECH CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0005439471","B=
oumnyebel OCM","IHS_EDA_056, IHS_YND_419, IHS_YND_381, IHS_YND_376","09-07-=
2025 10:17:26","09-07-2025 10:13:22","09-07-2025 10:40:24","Site went down =
because gen failed to start due to grid bad voltage no RCP // He bypass gri=
d and manually start the gen","Kemeni Franklin","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","Site went down because gen f=
ailed to start due to grid bad voltage no RCP // He bypass grid and manuall=
y start the gen","gerard.tchangoue@matech-cameroun.com","246","09-07-2025 1=
0:17:26","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005439253","Evo=
doula MTN","","09-07-2025 09:42:37","09-07-2025 09:38:19","09-07-2025 09:46=
:48","Grid outage, Site went down before Gen start due to poor backup//Grid=
 return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup//Grid return","gerard.tchangoue@matech-cameroun.c=
om","259","09-07-2025 09:42:37","MATECH CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0005439151","Ese=
ka Town","","09-07-2025 09:28:55","09-07-2025 09:22:40","09-07-2025 10:32:1=
0","Grid outage, Gen stopped with  high temp alarm // he added water in rad=
iator and manual start of Gen","Kemeni Franklin","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - High Engine Temp - Clogged Radiator","Grid outage, Ge=
n stopped with  high temp alarm // he added water in radiator and manual st=
art of Gen","gerard.tchangoue@matech-cameroun.com","510","09-07-2025 09:28:=
55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005438729","Acropole=
","","09-07-2025 08:15:50","09-07-2025 07:22:59","09-07-2025 09:17:36","Cas=
caded Incident from TTO5616736","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations ,Site Went down due =
to PWC overload, (210A ,12k) // Site stabilised","system","276129","09-07-2=
025 08:15:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005438491","C-Suprem=
e","","09-07-2025 07:24:51","09-07-2025 07:22:59","09-07-2025 09:17:36","Ca=
scaded Incident from TTO5616736","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k) // Site stabilised","system","276129","09-07-2025 07:24:51=
","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005438487","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","09-07-2025 07:24:25","09-07-2025 0=
7:22:59","09-07-2025 09:17:36","Grid fluctuations ,Site Went down due to PW=
C overload, (210A ,12k) // Site stabilised","MINKA NICOLAS","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations =
,Site Went down due to PWC overload, (210A ,12k) // Site stabilised","edwig=
e.kapawo@matech-cameroun.com","88","09-07-2025 07:24:25","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005438434","B=
arriere","","09-07-2025 07:09:11","09-07-2025 07:08:18","09-07-2025 07:08:4=
6","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"edwige.kapawo@matech-cameroun.com","386","09-07-2025 07:09:11","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005438398","Ngouetou=
","","09-07-2025 07:03:06","09-07-2025 06:37:11","09-07-2025 07:04:04","Cas=
caded Incident from TTO5616571","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Huawei controller hanging // Level 0 r=
eset controller and started GEN manually","system","1213829","09-07-2025 07=
:03:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005438399","MBIMBIM"=
,"","09-07-2025 07:03:06","09-07-2025 06:37:11","09-07-2025 07:04:04","Casc=
aded Incident from TTO5616571","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Huawei controller hanging // Level 0 re=
set controller and started GEN manually","system","1213830","09-07-2025 07:=
03:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005438397","Yoko OCM=
","","09-07-2025 07:03:06","09-07-2025 06:37:11","09-07-2025 07:04:04","Cas=
caded Incident from TTO5616571","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Huawei controller hanging // Level 0 r=
eset controller and started GEN manually","system","1213829","09-07-2025 07=
:03:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005438396","Matsari"=
,"","09-07-2025 07:03:06","09-07-2025 06:37:11","09-07-2025 07:04:04","Casc=
aded Incident from TTO5616571","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Huawei controller hanging // Level 0 re=
set controller and started GEN manually","system","1213831","09-07-2025 07:=
03:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005438395","Ngoum","=
","09-07-2025 07:03:05","09-07-2025 06:37:11","09-07-2025 07:04:04","Cascad=
ed Incident from TTO5616571","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Huawei controller hanging // Level 0 rese=
t controller and started GEN manually","system","1213831","09-07-2025 07:03=
:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005438362","C-Suprem=
e","","09-07-2025 06:55:40","09-07-2025 06:54:59","09-07-2025 06:55:03","Ca=
scaded Incident from TTO5616590","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations ,Site Went down due to PWC overl=
oad, (210A ,12k) // Site stabilised","system","263769","09-07-2025 06:55:40=
","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005438359","M=
vog Mbi New","IHS_YND_021","09-07-2025 06:55:17","09-07-2025 06:54:59","09-=
07-2025 06:55:03","Grid fluctuations ,Site Went down due to PWC overload, (=
210A ,12k) // Site stabilised","MINKA NICOLAS","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid fluctuations ,Site Went do=
wn due to PWC overload, (210A ,12k) // Site stabilised","edwige.kapawo@mate=
ch-cameroun.com","19","09-07-2025 06:55:17","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005438326","B=
arriere","","09-07-2025 06:48:41","09-07-2025 06:46:32","09-07-2025 06:50:1=
8","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"edwige.kapawo@matech-cameroun.com","131","09-07-2025 06:48:41","MATECH CMR=
"
"Cancelled","Warning","","IHS_YND_460","NOCINC0005438299","Matsari","","09-=
07-2025 06:45:21","","","Cascaded Incident from TTO5616512","Parker Tchoup"=
,"","","","","","system","499","09-07-2025 06:45:21","MATECH CMR"
"Cancelled","Warning","","IHS_YND_454","NOCINC0005438301","Ngouetou","","09=
-07-2025 06:45:21","","","Cascaded Incident from TTO5616512","Parker Tchoup=
","","","","","","system","499","09-07-2025 06:45:21","MATECH CMR"
"Cancelled","Warning","","IHS_YND_474","NOCINC0005438300","Yoko OCM","","09=
-07-2025 06:45:21","","","Cascaded Incident from TTO5616512","Parker Tchoup=
","","","","","","system","499","09-07-2025 06:45:21","MATECH CMR"
"Cancelled","Warning","","IHS_YND_456","NOCINC0005438302","MBIMBIM","","09-=
07-2025 06:45:21","","","Cascaded Incident from TTO5616512","Parker Tchoup"=
,"","","","","","system","499","09-07-2025 06:45:21","MATECH CMR"
"Cancelled","Warning","CTR_367","IHS_YND_475","NOCINC0005438288","Ngoum","I=
HS_YND_460, IHS_YND_474, IHS_YND_454, IHS_YND_456","09-07-2025 06:44:09",""=
,"","","Parker Tchoup","","","","","","edwige.kapawo@matech-cameroun.com","=
427","09-07-2025 06:44:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005438027","Akak-Nko=
zoa-MTN-IHS","","09-07-2025 05:20:30","09-07-2025 05:13:02","09-07-2025 05:=
15:31","Cascaded Incident from TTO5616207","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
: 53.5V site on Grid. Symphorien (691316854/Huawei) is informed.","system",=
"262355","09-07-2025 05:20:30","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005437388","Lad=
a I Yde","","09-07-2025 01:56:14","09-07-2025 01:53:08","09-07-2025 02:00:0=
3","Active//No power issue on site ,site on Grid with Ubaie=3D54,4V (THEFT =
OF TX CABLES). The Tx FME Henri (691145055) from Huawei is informed.","Mba =
Lazare Herve","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid with=
 Ubaie=3D54,4V (THEFT OF TX CABLES). The Tx FME Henri (691145055) from Huaw=
ei is informed.","loic.noumsi@matech-cameroun.com","187","09-07-2025 01:56:=
14","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005436910","N=
koabang Ebolmedjock","","08-07-2025 23:42:04","08-07-2025 23:37:52","08-07-=
2025 23:47:39","Site went down because  generator was running and  did not =
supply the site because the voltage of the bay was lower than the load of t=
he site // increase the power limitation of the bay","Mba Lazare Herve","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Site went down=
 because  generator was running and  did not supply the site because the vo=
ltage of the bay was lower than the load of the site // increase the power =
limitation of the bay","gaelle.njiofack@matech-cameroun.com","254","08-07-2=
025 23:42:04","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0005436723","A=
battoir","","08-07-2025 23:10:46","08-07-2025 23:02:31","08-07-2025 23:03:4=
6","Grid outage, site went down due to Grid bad voltage (lack of 01 phase) =
// He did bridge on the good phase, Site on GRID","Fabrice Pouakam","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid out=
age, site went down due to Grid bad voltage (lack of 01 phase) // He did br=
idge on the good phase, Site on GRID","gaelle.njiofack@matech-cameroun.com"=
,"497","08-07-2025 23:10:46","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005436719","M=
vog Mbi New","","08-07-2025 23:07:40","08-07-2025 23:06:30","09-07-2025 00:=
32:39","Grid outage ,site down due to PWC overload, (210A ,12k) // Site sta=
bilised","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Grid outage ,site down due to PWC overload, (210A ,12=
k) // Site stabilised","gaelle.njiofack@matech-cameroun.com","71","08-07-20=
25 23:07:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0005436705","NYANON/D=
EMBO","","08-07-2025 23:03:51","08-07-2025 22:58:29","09-07-2025 07:09:59",=
"Cascaded Incident from TTO5614751","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","Active//No power issue on =
site U=3D55,5V site on Gen and The FME TX Gregoire From huawei is informed"=
,"system","299140","08-07-2025 23:03:51","MATECH CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0005436703","Nya=
hoo","IHS_EDA_102","08-07-2025 23:02:42","08-07-2025 22:58:29","09-07-2025 =
07:09:59","Active//No power issue on site U=3D55,5V site on Gen and The FME=
 TX Gregoire From huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site U=3D55,5V site on Gen and The FME TX Grego=
ire From huawei is informed","loic.noumsi@matech-cameroun.com","254","08-07=
-2025 23:02:42","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005436598","C=
-Supreme","","08-07-2025 22:45:22","08-07-2025 22:44:17","08-07-2025 22:59:=
55","Active // No power issue, site on Grid with Ubaie=3D54.2V, Brice Tsagu=
e (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power is=
sue, site on Grid with Ubaie=3D54.2V, Brice Tsague (650 21 40 96 / Huawei) =
is informed","gaelle.njiofack@matech-cameroun.com","67","08-07-2025 22:45:2=
2","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005436544","S=
imbock OCM","","08-07-2025 22:39:14","08-07-2025 22:37:58","08-07-2025 22:5=
1:43","Site impacted by Nkolzie CTR_672 not manage by IHS","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Site impacted by Nkolzie CTR_672 not manage by IHS","gaelle.nj=
iofack@matech-cameroun.com","77","08-07-2025 22:39:14","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005436542","M=
ontee-Des-Soeurs","","08-07-2025 22:38:24","08-07-2025 22:36:16","08-07-202=
5 22:41:22","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","gaelle.njiofack@matech-cameroun.com","130","08-07-2025 22:38:2=
4","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005436173","Lad=
a I Yde","","08-07-2025 21:29:53","08-07-2025 21:28:31","08-07-2025 21:29:2=
6","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","cedric.tiani@matech-cameroun.com","83","08-07-2025 21:29:53","MATECH CMR=
"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005436007","SIM=
BOCK BONAMBAPE","","08-07-2025 21:03:09","08-07-2025 21:01:57","08-07-2025 =
21:03:24","Grid outage, Site went down before Gen start due to poor backup =
// Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Site stabilised","cedric.tiani@matech-camerou=
n.com","73","08-07-2025 21:03:09","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005435992","B=
arriere","","08-07-2025 21:02:03","08-07-2025 21:00:47","08-07-2025 23:48:3=
9","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"cedric.tiani@matech-cameroun.com","78","08-07-2025 21:02:03","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005435988","A=
wae Ewonkan","","08-07-2025 21:00:46","08-07-2025 20:58:05","08-07-2025 23:=
00:11","No power issue on site Tx issue U=3D54.2V site on Grid , the FME TX=
 Leonel Steve //655184876 from Huawei is informed","Albran Byorel","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Tx issue U=3D54.2V site on Grid , the FME TX Leo=
nel Steve //655184876 from Huawei is informed","cedric.tiani@matech-camerou=
n.com","163","08-07-2025 21:00:46","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005435810","Lad=
a I Yde","","08-07-2025 20:34:09","08-07-2025 20:08:03","08-07-2025 21:14:2=
8","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","vanel.mbiada@matech-cameroun.com","1567","08-07-2025 20:34:09","MATECH C=
MR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005435575","Lad=
a I Yde","","08-07-2025 19:53:46","08-07-2025 19:52:38","08-07-2025 19:54:2=
4","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage //Site stabilised","Mba Lazare Herve","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation =
site went down because Gen and started and stopped due to Grid bad voltage =
//Site stabilised","cedric.tiani@matech-cameroun.com","70","08-07-2025 19:5=
3:46","MATECH CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0005435373","Nya=
hoo","","08-07-2025 19:18:09","08-07-2025 19:16:30","08-07-2025 19:23:19","=
SS HIS Pascaline  is on site working//End of work","TIENTCHEU NZETCHIEU GAE=
L","Installation Activity","Passive","Planned Activity","Installation Activ=
ity","SS HIS Pascaline  is on site working//End of work","cedric.tiani@mate=
ch-cameroun.com","100","08-07-2025 19:18:09","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005435225","M=
vog Mbi New","","08-07-2025 18:49:59","08-07-2025 18:45:51","08-07-2025 18:=
50:48","Grid outage ,site down due to PWC overload, (210A ,12k) // Site sta=
bilisation","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Recti=
fier Module Overloaded","Grid outage ,site down due to PWC overload, (210A =
,12k) // Site stabilisation","vanel.mbiada@matech-cameroun.com","249","08-0=
7-2025 18:49:59","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005435222","Evo=
doula MTN","","08-07-2025 18:49:30","08-07-2025 18:45:00","08-07-2025 18:49=
:40","Grid outage, Site went down before Gen start due to poor backup//Grid=
 return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup//Grid return","vanel.mbiada@matech-cameroun.com",=
"271","08-07-2025 18:49:30","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005435056","O=
dza II OCM","","08-07-2025 18:21:38","08-07-2025 18:20:27","08-07-2025 18:2=
3:24","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction//Site stabilised","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, site went down b=
ecause gen failed to start due to PWC ZTE malfunction//Site stabilised","va=
nel.mbiada@matech-cameroun.com","74","08-07-2025 18:21:38","MATECH CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0005434908","B=
astos-BAT","","08-07-2025 17:54:44","08-07-2025 17:52:29","08-07-2025 17:55=
:13","Active// No power issue, site is on Grid with Ubaie=3D55V The Tx Fme,=
 Eloundou(652586578) from Huawei is informed","Mboua Thierry","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive// No power issue, site is on Grid with Ubaie=3D55V The Tx Fme, Elound=
ou(652586578) from Huawei is informed","vanel.mbiada@matech-cameroun.com","=
136","08-07-2025 17:54:44","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005434850","A=
kak-Nkozoa-MTN-IHS","","08-07-2025 17:44:16","08-07-2025 17:39:38","08-07-2=
025 17:45:58","","Fabrice Pouakam","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","No power issue on site Ubaie: 53.5V site on Grid. Sinp=
horien (691316854/Huawei) is informed.","vanel.mbiada@matech-cameroun.com",=
"267969","08-07-2025 17:44:16","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005434794","Nko=
lbisson IITA LP","","08-07-2025 17:41:37","08-07-2025 17:37:28","08-07-2025=
 17:44:17","No power issue site on grid with U=3D53.8v Mohamadou(69114435) =
from Huawei is informed.Noticed that it is impacted by Nkolbisson 2 ocm not=
 manage by IHS","","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.8v M=
ohamadou(69114435) from Huawei is informed.Noticed that it is impacted by N=
kolbisson 2 ocm not manage by IHS","cedric.tiani@matech-cameroun.com","250"=
,"08-07-2025 17:41:37","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005434773","N=
kolfon Cimencam","","08-07-2025 17:39:35","08-07-2025 17:31:25","08-07-2025=
 17:42:48","	Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","	Grid outage, Site went down before Gen=
 start due to poor backup // Grid return","vanel.mbiada@matech-cameroun.com=
","492","08-07-2025 17:39:35","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005434452","NKO=
MKANA ELIZA HOTEL","","08-07-2025 16:44:52","08-07-2025 16:44:44","08-07-20=
25 16:46:03","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed //Site stabilised","","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site went down due to PWC Overloaded and S=
S IHS Bernard Atangana confirmed //Site stabilised","cedric.tiani@matech-ca=
meroun.com","9","08-07-2025 16:44:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005434198","Mfou EPC=
","","08-07-2025 16:16:26","08-07-2025 16:13:34","08-07-2025 16:19:27","Cas=
caded Incident from TTO5611881","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Gen automatically started","system","265935","=
08-07-2025 16:16:26","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005434192","M=
fou OCM","IHS_YND_674","08-07-2025 16:15:43","08-07-2025 16:13:34","08-07-2=
025 16:19:27","Grid Outage, Site Down before gen Started due to poor backup=
 // Gen automatically started","Mba Lazare Herve","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down b=
efore gen Started due to poor backup // Gen automatically started","vanel.m=
biada@matech-cameroun.com","130","08-07-2025 16:15:43","MATECH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0005434135","Com=
plex Beac II","","08-07-2025 16:09:54","08-07-2025 16:08:42","08-07-2025 17=
:30:09","Site went down Gen failed to start due to neutral usage burned at =
the powercom level // He bypass the  neutral with a circuit breaker","Albra=
n Byorel","Equipment Repair","Passive","Control Panel","Panel Distribution =
Board","Site went down Gen failed to start due to neutral usage burned at t=
he powercom level // He bypass the  neutral with a circuit breaker","cedric=
.tiani@matech-cameroun.com","73","08-07-2025 16:09:54","MATECH CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0005434095","E=
kie-Elegance","IHS_YND_159","08-07-2025 16:07:48","08-07-2025 16:00:40","08=
-07-2025 17:39:49","Access issues due to landord( site went down because ge=
n start and stopped with emergency stop alarm // He manually start the gen)=
","Albran Byorel","Access Denial","Lease Or Legal","Landlord Related Issues=
","Access Issue - Land Lord","Access issues due to landord( site went down =
because gen start and stopped with emergency stop alarm // He manually star=
t the gen)","vanel.mbiada@matech-cameroun.com","429","08-07-2025 16:07:48",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005434076","C=
omplexe-BEAC","","08-07-2025 16:04:21","08-07-2025 16:00:40","08-07-2025 17=
:39:49","Access issues due to landord( site went down because gen start and=
 stopped with emergency stop alarm // He manually start the gen)","Albran B=
yorel","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Acce=
ss issues due to landord( site went down because gen start and stopped with=
 emergency stop alarm // He manually start the gen)","vanel.mbiada@matech-c=
ameroun.com","273854","08-07-2025 16:04:21","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005434048","M=
vog Mbi New","","08-07-2025 16:01:20","08-07-2025 15:59:10","08-07-2025 16:=
03:35","Grid outage ,site down due to Power Cabinet overload, (210A ,12k) /=
/ Site stabilisation","MINKA NICOLAS","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Grid outage ,site down due to Power Cabi=
net overload, (210A ,12k) // Site stabilisation","vanel.mbiada@matech-camer=
oun.com","131","08-07-2025 16:01:20","MATECH CMR"
"Closed Complete","Warning","CTR_195","IHS_YND_165","NOCINC0005433800","Aha=
la","","08-07-2025 15:27:03","","","Grid fluctuation,site went down because=
 gen failed to start due to Grid bad voltage(lack of one phase)//He did a b=
ridge with the Good phase","MINKA NICOLAS","Warning","Warning","POWER","War=
ning - National Grid - Grid Incomplete Phase","Grid fluctuation,site went d=
own because gen failed to start due to Grid bad voltage(lack of one phase)/=
/He did a bridge with the Good phase","cedric.tiani@matech-cameroun.com","6=
83","08-07-2025 15:27:03","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005433684","C=
-Supreme","","08-07-2025 15:12:29","08-07-2025 15:10:16","08-07-2025 15:40:=
39","Active // No power issue, site on Grid with Ubaie=3D54.2V, Brice Tsagu=
e (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power is=
sue, site on Grid with Ubaie=3D54.2V, Brice Tsague (650 21 40 96 / Huawei) =
is informed","vanel.mbiada@matech-cameroun.com","134","08-07-2025 15:12:29"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005433313","N=
koabang Ebolmedjock","","08-07-2025 14:32:10","08-07-2025 14:28:35","08-07-=
2025 14:38:36","Site went down due to work (Mba Herve  / MATECH, doing PM) =
// En of work","Mba Lazare Herve","Installation Activity","Passive","Planne=
d Activity","Installation Activity","Site went down due to work (Mba Herve =
 / MATECH, doing PM) // En of work","vanel.mbiada@matech-cameroun.com","216=
","08-07-2025 14:32:10","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005433174","Nko=
lnda","","08-07-2025 14:10:05","08-07-2025 14:09:57","08-07-2025 14:35:09",=
"Grid fluctuation, Site went down before Gen start due to poor backup//Grid=
 return","Albran Byorel","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid fluctuation, Site went down before Gen start=
 due to poor backup//Grid return","gerard.tchangoue@matech-cameroun.com","9=
","08-07-2025 14:10:05","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005433164","Odz=
a II OCM","","08-07-2025 14:07:17","08-07-2025 14:03:05","08-07-2025 14:09:=
52","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction//Site stabilised","Albran Byorel","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage, site went down bec=
ause gen failed to start due to PWC ZTE malfunction//Site stabilised","gera=
rd.tchangoue@matech-cameroun.com","255","08-07-2025 14:07:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005433043","Mfou EPC=
","","08-07-2025 13:48:30","08-07-2025 13:40:17","08-07-2025 14:10:42","Cas=
caded Incident from TTO5610617","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Grid stabilised","system","267929","08-07-2025=
 13:48:30","MATECH CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0005433037","Awa=
e Escalier","","08-07-2025 13:47:56","08-07-2025 13:40:48","08-07-2025 14:5=
8:56","Site went down due to Cb(63A) disjuncted in TGBT // He reamed cb(63A=
), site on grid","Albran Byorel","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Circuit Breaker Issue","Site went down due to Cb(63A) d=
isjuncted in TGBT // He reamed cb(63A), site on grid","gerard.tchangoue@mat=
ech-cameroun.com","429","08-07-2025 13:47:56","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005433036","M=
fou OCM","IHS_YND_674","08-07-2025 13:47:45","08-07-2025 13:40:17","08-07-2=
025 14:10:42","Grid Outage, Site Down before gen Started due to poor backup=
 // Grid stabilised","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen =
Started due to poor backup // Grid stabilised","edwige.kapawo@matech-camero=
un.com","449","08-07-2025 13:47:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0005432798","Marche O=
dza","","08-07-2025 13:16:01","08-07-2025 13:08:08","08-07-2025 13:19:27","=
Cascaded Incident from TTO5610336","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue on site Ubaie: =
53 V site on Grid The TX Lionel steve (655184876 /Huawei)) is informed.","s=
ystem","262763","08-07-2025 13:16:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0005432797","Mvog-Man=
ga","","08-07-2025 13:16:00","08-07-2025 13:08:08","08-07-2025 13:19:27","C=
ascaded Incident from TTO5610336","Albran Byorel","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue on site Ubaie: 5=
3 V site on Grid The TX Lionel steve (655184876 /Huawei)) is informed.","sy=
stem","262762","08-07-2025 13:16:00","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005432786","O=
dza","IHS_YND_254, IHS_YND_580","08-07-2025 13:15:14","08-07-2025 13:08:08"=
,"08-07-2025 13:19:27","Active//No power issue on site Ubaie: 53 V site on =
Grid The TX Lionel steve (655184876 /Huawei)) is informed.","Albran Byorel"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue on site Ubaie: 53 V site on Grid The TX=
 Lionel steve (655184876 /Huawei)) is informed.","edwige.kapawo@matech-came=
roun.com","427","08-07-2025 13:15:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_393","NOCINC0005432734","Ezezang"=
,"","08-07-2025 13:04:52","08-07-2025 12:57:52","08-07-2025 13:06:40","Casc=
aded Incident from TTO5610243","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue, Site impacted by Nkog-Edze=
ng_ctr_041","system","263390","08-07-2025 13:04:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_051","NOCINC0005432733","Nyanon",=
"","08-07-2025 13:04:52","08-07-2025 12:57:52","08-07-2025 13:06:40","Casca=
ded Incident from TTO5610243","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue, Site impacted by=
 Nkog-Edzeng_ctr_041","system","263371","08-07-2025 13:04:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0005432732","Monatele=
 MTN","","08-07-2025 13:04:52","08-07-2025 12:57:52","08-07-2025 13:06:40",=
"Cascaded Incident from TTO5610243","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue, Site impacted by Nkog=
-Edzeng_ctr_041","system","263368","08-07-2025 13:04:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0005432730","Saa","",=
"08-07-2025 13:04:51","08-07-2025 12:57:52","08-07-2025 13:06:40","Cascaded=
 Incident from TTO5610243","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue, Site impacted by Nkog-Edzeng_c=
tr_041","system","263386","08-07-2025 13:04:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0005432729","Okola OC=
M","","08-07-2025 13:04:51","08-07-2025 12:57:52","08-07-2025 13:06:40","Ca=
scaded Incident from TTO5610243","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue, Site impacted=
 by Nkog-Edzeng_ctr_041","system","263379","08-07-2025 13:04:51","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005432731","SAA 2","=
","08-07-2025 13:04:51","08-07-2025 12:57:52","08-07-2025 13:06:40","Cascad=
ed Incident from TTO5610243","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue, Site impacted by Nkog-Edzeng=
_ctr_041","system","263386","08-07-2025 13:04:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0005432727","Monatele=
","","08-07-2025 13:04:50","08-07-2025 12:57:52","08-07-2025 13:06:40","Cas=
caded Incident from TTO5610243","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue, Site impacted by Nkog-Edz=
eng_ctr_041","system","263385","08-07-2025 13:04:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0005432728","Talla Mo=
natele","","08-07-2025 13:04:50","08-07-2025 12:57:52","08-07-2025 13:06:40=
","Cascaded Incident from TTO5610243","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue, Site impacted by Nk=
og-Edzeng_ctr_041","system","263383","08-07-2025 13:04:51","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005432702","E=
vodoula OCM","IHS_YND_389, IHS_YND_406, IHS_YND_438, IHS_YND_468, IHS_YND_7=
05, IHS_YND_430, IHS_YND_386, IHS_YND_427, IHS_YND_472, IHS_EDA_050, IHS_YN=
D_400, IHS_YND_550, IHS_YND_387, IHS_YND_338, IHS_YND_405, IHS_YND_426, IHS=
_YND_466, IHS_YND_726, IHS_YND_549, IHS_YND_423, IHS_YND_401, IHS_YND_425, =
IHS_YND_404, IHS_YND_448, IHS_YND_429, IHS_YND_407, IHS_YND_354, IHS_EDA_05=
1, IHS_YND_393, IHS_YND_439","08-07-2025 13:02:03","08-07-2025 12:57:52","0=
8-07-2025 13:06:40","No power issue, Site impacted by Nkog-Edzeng_ctr_041 n=
ot managed by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure",=
"Active","Active Equipment Failure","Affected by 3rd Party Site","No power =
issue, Site impacted by Nkog-Edzeng_ctr_041","edwige.kapawo@matech-cameroun=
.com","252","08-07-2025 13:02:03","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005432658","Aha=
la Echangeur","","08-07-2025 12:53:23","08-07-2025 12:46:12","08-07-2025 13=
:07:30","Site went down because gen stopped with low oil pressure // he add=
ed oil and started the gen","MINKA NICOLAS","Equipment Repair","Passive","A=
CDG Gen","ACDG - Low Oil Pressure","Site went down because gen stopped with=
 low oil pressure//he added oil and started the gen","gerard.tchangoue@mate=
ch-cameroun.com","432","08-07-2025 12:53:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005432425","Mfou EPC=
","","08-07-2025 12:24:50","08-07-2025 12:18:59","08-07-2025 12:36:26","Cas=
caded Incident from TTO5609917","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","265656","08-07-2025 12=
:24:50","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005432414","M=
fou OCM","IHS_YND_674","08-07-2025 12:24:08","08-07-2025 12:18:59","08-07-2=
025 12:36:26","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","edwige.kapawo@matech-cameroun.com=
","310","08-07-2025 12:24:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005431982","Nsam esc=
ale LP","","08-07-2025 11:12:20","08-07-2025 11:02:29","08-07-2025 11:08:49=
","Cascaded Incident from TTO5609403","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Gen Started Automatically","system","1212382","08-07-=
2025 11:12:20","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005431978","Nsa=
m Sofavinc","IHS_YND_732","08-07-2025 11:11:36","08-07-2025 11:02:29","08-0=
7-2025 11:08:49","Grid Outage, Site went down before Gen start due to poor =
backup // Gen Started Automatically","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site wen=
t down before Gen start due to poor backup // Gen Started Automatically","g=
erard.tchangoue@matech-cameroun.com","548","08-07-2025 11:11:36","MATECH CM=
R"
"Closed Complete","Site Down","T2585","IHS_YND_744","NOCINC0005431776","Ele=
veur Meec Bon Berger","","08-07-2025 10:51:42","08-07-2025 10:43:15","08-07=
-2025 10:55:15","Grid outage gen failed to start due to alarm underfrequenc=
y // He reset Gen card and started Gen manualy","Siligap Boris","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed=
 to start due to alarm underfrequency // He reset Gen card and started Gen =
manualy","ludivine.ngamaleu@ihstowers.com","508","08-07-2025 10:51:42","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005431713","A=
wae Ewonkan","","08-07-2025 10:42:06","08-07-2025 10:40:59","08-07-2025 10:=
56:45","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid retur=
n","edwige.kapawo@matech-cameroun.com","69","08-07-2025 10:42:06","MATECH C=
MR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005431678","C=
omplexe-BEAC","","08-07-2025 10:37:25","08-07-2025 10:35:14","08-07-2025 10=
:38:19","Grid outage, Site went down before Gen start due to Poor battery b=
ackup // Gen started automatically","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to Poor battery backup // Gen started automatica=
lly","edwige.kapawo@matech-cameroun.com","132","08-07-2025 10:37:25","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005431582","Akak-Nko=
zoa-MTN-IHS","","08-07-2025 10:23:10","08-07-2025 10:01:45","08-07-2025 10:=
05:44","Cascaded Incident from TTO5608816","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
: 49.9V site on Grid. Sinphorien (691316854/Huawei) is informed.","system",=
"266773","08-07-2025 10:23:10","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005431507","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","08-07-2025 10:11:20","08-07-20=
25 10:07:13","08-07-2025 11:36:19","Grid outage, Site went down because Gen=
 start and stopped with ""High temps ""alarm // he added water and manually=
 start the Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","AC=
DG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site =
went down because Gen start and stopped with ""High temps ""alarm // he add=
ed water and manually start the Gen","gerard.tchangoue@matech-cameroun.com"=
,"248","08-07-2025 10:11:20","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005431384","Nko=
lfoulou CSD MTN","","08-07-2025 09:48:40","08-07-2025 09:46:31","08-07-2025=
 13:40:47","Active//No power issue site is on Grid with Ubaie=3D50,9 V site=
 on gen The Tx FME Syphorien //675295205 from Huawei is informed","Siligap =
Boris","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No power issue site is on Grid with Ubaie=3D50,9=
 V site on gen The Tx FME Syphorien //675295205 from Huawei is informed","g=
erard.tchangoue@matech-cameroun.com","130","08-07-2025 09:48:40","MATECH CM=
R"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005431148","Evo=
doula MTN","","08-07-2025 09:10:42","08-07-2025 09:08:09","08-07-2025 09:22=
:22","Grid outage, Site went down before Gen start due to poor backup// GRI=
D return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// GRID return","gerard.tchangoue@matech-cameroun=
.com","154","08-07-2025 09:10:42","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005431073","A=
wae Ewonkan","","08-07-2025 08:57:57","08-07-2025 08:55:49","08-07-2025 10:=
36:15","( unstable ) Grid outage site went down due to Gen Overload (20Kva,=
 Iload 320A)IHS SS Alphonse is informed // Grid stabilized","Albran Byorel"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","( unstable ) Gr=
id outage site went down due to Gen Overload (20Kva, Iload 320A)IHS SS Alph=
onse is informed // Grid stabilized","edwige.kapawo@matech-cameroun.com","1=
30","08-07-2025 08:57:57","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005430698","B=
arriere","","08-07-2025 07:39:53","08-07-2025 07:34:40","08-07-2025 17:16:0=
4","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed//Site stabilised",=
"edwige.kapawo@matech-cameroun.com","314","08-07-2025 07:39:53","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0005430629","NYANON/D=
EMBO","","08-07-2025 07:27:10","08-07-2025 07:24:17","08-07-2025 13:36:59",=
"Cascaded Incident from TTO5607861","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Hybrid gen site .Gen st=
art and stopped due to low oil pressure  cause  by crankcase gasket faulty/=
/We add oil and gen manually started","system","311979","08-07-2025 07:27:1=
0","MATECH CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0005430624","Nya=
hoo","IHS_EDA_102, IHS_EDA_049","08-07-2025 07:26:23","08-07-2025 07:24:17"=
,"08-07-2025 13:36:59","Hybrid gen site .Gen start and stopped due to low o=
il pressure  cause  by crankcase gasket faulty//We add oil and gen manually=
 started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen=
","ACDG - Low Oil Pressure","Hybrid gen site .Gen start and stopped due to =
low oil pressure  cause  by crankcase gasket faulty//We add oil and gen man=
ually started","gaelle.njiofack@matech-cameroun.com","127","08-07-2025 07:2=
6:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005430560","Bondjock=
","","08-07-2025 07:12:51","08-07-2025 07:01:59","08-07-2025 07:15:32","Cas=
caded Incident from TTO5607764","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage gen failed to start due to c=
ard GE dysfunctionned // We reset card GE and gen manually started","system=
","284549","08-07-2025 07:12:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005430559","Minka","=
","08-07-2025 07:12:51","08-07-2025 07:01:59","08-07-2025 07:15:32","Cascad=
ed Incident from TTO5607764","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage gen failed to start due to card=
 GE dysfunctionned // We reset card GE and gen manually started","system","=
284550","08-07-2025 07:12:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005430558","Mbeng","=
","08-07-2025 07:12:50","08-07-2025 07:01:59","08-07-2025 07:15:32","Cascad=
ed Incident from TTO5607764","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage gen failed to start due to card=
 GE dysfunctionned // We reset card GE and gen manually started","system","=
284551","08-07-2025 07:12:50","MATECH CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0005430548","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_372","08-07-2025 07:11:04","08-07-20=
25 07:01:59","08-07-2025 07:15:52","Grid outage gen failed to start due to =
card GE dysfunctionned // We reset card GE and gen manually started","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage gen failed to start due to card GE dysfunctionned // We reset card=
 GE and gen manually started","edwige.kapawo@matech-cameroun.com","546","08=
-07-2025 07:11:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_368","NOCINC0005430251","Otele","=
","08-07-2025 06:21:40","08-07-2025 06:13:30","08-07-2025 06:39:29","Cascad=
ed Incident from TTO5607432","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue, Site impacted by Ngoumou Camra=
il not managed by IHS","system","266060","08-07-2025 06:21:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005430250","Mom","",=
"08-07-2025 06:21:40","08-07-2025 06:13:30","08-07-2025 06:39:29","Cascaded=
 Incident from TTO5607432","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue, Site impacted by Ngoumou Camrail=
 not managed by IHS","system","266061","08-07-2025 06:21:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005430252","Mbeng","=
","08-07-2025 06:21:40","08-07-2025 06:13:30","08-07-2025 06:39:29","Cascad=
ed Incident from TTO5607432","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue, Site impacted by Ngoumou Camra=
il not managed by IHS","system","266059","08-07-2025 06:21:40","MATECH CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0005430242","M=
inka","IHS_YND_370, IHS_YND_368, IHS_YND_369","08-07-2025 06:18:47","08-07-=
2025 06:13:30","08-07-2025 06:39:29","No power issue, Site impacted by Ngou=
mou Camrail not managed by IHS","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","Affected by 3rd Party Site","No power =
issue, Site impacted by Ngoumou Camrail not managed by IHS","gaelle.njiofac=
k@matech-cameroun.com","318","08-07-2025 06:18:47","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005429899","Odz=
a Minkan IHS","","08-07-2025 04:41:12","08-07-2025 04:37:03","08-07-2025 05=
:43:17","Grid outage, Gen failed to start due to false alarm oil pressure /=
/ Gen card reset and Gen start manually","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage, Gen failed to=
 start due to false alarm oil pressure // Gen card reset and Gen start manu=
ally","gaelle.njiofack@matech-cameroun.com","250","08-07-2025 04:41:12","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005429715","A=
wae Ewonkan","","08-07-2025 03:22:32","08-07-2025 03:20:24","08-07-2025 03:=
22:42","( unstable ) Grid outage site went down due to Gen Overload (20Kva,=
 Iload 320A)IHS SS Alphonse is informed // Grid stabilised","Albran Byorel"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","( unstable ) Gr=
id outage site went down due to Gen Overload (20Kva, Iload 320A)IHS SS Alph=
onse is informed // Grid stabilised","gaelle.njiofack@matech-cameroun.com",=
"130","08-07-2025 03:22:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005429681","MEHANDAN=
","","08-07-2025 03:05:19","08-07-2025 03:02:29","08-07-2025 03:05:31","Cas=
caded Incident from TTO5606823","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to PWC ZTE malfunction// site stabilised","system","=
262902","08-07-2025 03:05:19","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005429674","O=
dza II OCM","IHS_YND_528","08-07-2025 03:03:40","08-07-2025 03:02:29","08-0=
7-2025 03:05:31","	Grid outage, site went down because gen failed to start =
due to PWC ZTE malfunction// site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","	Grid outage, si=
te went down because gen failed to start due to PWC ZTE malfunction// site =
stabilised","gaelle.njiofack@matech-cameroun.com","74","08-07-2025 03:03:40=
","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005429207","S=
aa","","08-07-2025 00:42:13","08-07-2025 00:39:03","08-07-2025 00:42:44","N=
o power issue on site ,site on Gen with Ubaie =3D54.1V The Tx Technician fr=
om Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site ,site on Gen with Ubaie =3D54.1V The Tx Technician fro=
m Huawei Gr=E9goire//654547479 is informed","gaelle.njiofack@matech-camerou=
n.com","192","08-07-2025 00:42:13","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005428973","A=
wae Ewonkan","","07-07-2025 23:18:14","07-07-2025 23:12:04","07-07-2025 23:=
31:09","( unstable ) Grid outage site went down due to Gen Overload (20Kva,=
 Iload 320A)IHS SS Alphonse is informed // Grid stabilised","Albran Byorel"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","( unstable ) Gr=
id outage site went down due to Gen Overload (20Kva, Iload 320A)IHS SS Alph=
onse is informed // Grid stabilised","gaelle.njiofack@matech-cameroun.com",=
"371","07-07-2025 23:18:14","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005428626","E=
mana lycee 2","","07-07-2025 21:45:58","07-07-2025 21:45:49","07-07-2025 21=
:46:26","Grid fluctuations, site went down due to Grid bad voltage and no r=
cp // Grid stabilised","Fabrice Pouakam","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","Grid fluctuations, site went down d=
ue to Grid bad voltage and no rcp // Grid stabilised","gaelle.njiofack@mate=
ch-cameroun.com","11","07-07-2025 21:45:58","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005428606","SIM=
BOCK BONAMBAPE","","07-07-2025 21:42:21","07-07-2025 21:39:38","07-07-2025 =
21:41:08","Grid outage, Site went down before Gen start due to poor backup =
// Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Site stabilised","loic.noumsi@matech-cameroun=
.com","164","07-07-2025 21:42:21","MATECH CMR"
"Closed Complete","Site Down","CTR_553","IHS_YND_686","NOCINC0005428586","O=
yomabang Ecole","","07-07-2025 21:39:15","07-07-2025 21:37:07","07-07-2025 =
21:48:11","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mo=
uhamadou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mouh=
amadou (6144435) from Huawei is informed.","gaelle.njiofack@matech-cameroun=
.com","129","07-07-2025 21:39:15","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005428496","Mai=
son komkana New","","07-07-2025 21:20:02","07-07-2025 21:16:57","07-07-2025=
 21:20:51","Active//No power issue on site Ubaie =3D 52.1V Site on Grid. TX=
 FME Brice TSAGUE (650214096/HUAWEI) is informed","Mboua Thierry","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site Ubaie =3D 52.1V Site on Grid. TX FME Bric=
e TSAGUE (650214096/HUAWEI) is informed","loic.noumsi@matech-cameroun.com",=
"186","07-07-2025 21:20:02","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005428466","Bit=
eng-Maetur","","07-07-2025 21:14:27","07-07-2025 21:11:22","07-07-2025 21:1=
5:59","Active//No power issue on site Ubaie =3D53V site on Grid The TX FME =
Henri (699949693) from Huawei is informed (awaiting evidences)","Mba Lazare=
 Herve","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No power issue on site Ubaie =3D53V site on Gri=
d The TX FME Henri (699949693) from Huawei is informed (awaiting evidences)=
","loic.noumsi@matech-cameroun.com","187","07-07-2025 21:14:27","MATECH CMR=
"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005428263","A=
wae Ewonkan","","07-07-2025 20:43:52","07-07-2025 20:40:47","07-07-2025 22:=
08:51","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid stabilised","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid s=
tabilised","loic.noumsi@matech-cameroun.com","187","07-07-2025 20:43:52","M=
ATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005428209","MBA=
LNGONG LYCEE","","07-07-2025 20:31:49","07-07-2025 20:28:42","07-07-2025 21=
:03:53","Grid outage,Site went down because Gen stopped due to overload(9kv=
a, 130A) SS IHS Felix Zambe is informed and confirmed // Site stabilised","=
Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gri=
d outage,Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Site stabilised","loic.noumsi@=
matech-cameroun.com","189","07-07-2025 20:31:49","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005427981","A=
wae Ewonkan","","07-07-2025 19:46:08","07-07-2025 19:43:01","07-07-2025 20:=
30:58","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid stabilised","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid s=
tabilised","loic.noumsi@matech-cameroun.com","189","07-07-2025 19:46:08","M=
ATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005427841","Cit=
e des nations","","07-07-2025 19:24:53","07-07-2025 19:18:47","07-07-2025 1=
9:36:38","Grid outage,site went down before Gen started due to Poor battery=
 backup // Site stabilised","Paul BIBOUM","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage,site went down befor=
e Gen started due to Poor battery backup // Site stabilised","loic.noumsi@m=
atech-cameroun.com","367","07-07-2025 19:24:53","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005427772","A=
wae Ewonkan","","07-07-2025 19:15:19","07-07-2025 19:12:09","07-07-2025 19:=
14:54","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid stabilised","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid s=
tabilised","gaelle.njiofack@matech-cameroun.com","192","07-07-2025 19:15:19=
","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005427766","Bar=
riere","","07-07-2025 19:13:27","07-07-2025 19:10:21","07-07-2025 20:11:54"=
,"Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS Fel=
ix ZAMBE confirmed // Site stabilised","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // Site stabilised=
","loic.noumsi@matech-cameroun.com","188","07-07-2025 19:13:27","MATECH CMR=
"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0005427598","Nko=
lmvack","","07-07-2025 18:47:25","07-07-2025 18:20:20","07-07-2025 18:55:04=
","Grid outage, Site went down because Gen start and stopped with ""High te=
mp""alarm // he added water and manually started the Gen","Parker Tchoup","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
 Site went down because Gen start and stopped with ""High temp""alarm // he=
 added water and manually started the Gen","loic.noumsi@matech-cameroun.com=
","1626","07-07-2025 18:47:25","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005427279","E=
mana Lycee","","07-07-2025 18:03:21","07-07-2025 18:01:10","07-07-2025 18:0=
3:52","Grid outage, Site went down doe to Gen Over load (20KVA : 220A) // R=
eduction of the site load, and site on Gen","Fabrice Pouakam","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down d=
oe to Gen Over load (20KVA : 220A) // Reduction of the site load, and site =
on Gen","gaelle.njiofack@matech-cameroun.com","133","07-07-2025 18:03:21","=
MATECH CMR"
"Closed Complete","Site Down","T2222","IHS_YND_697","NOCINC0005427082","Nom=
ayos-IHS","","07-07-2025 17:36:55","07-07-2025 17:32:48","07-07-2025 18:05:=
01","Grid outage, site went down due to 01/04 rectifier dysfunctionning // =
He reset it, site on Gen","Fanda Brice","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Grid outage, site went down due to 01/04 rectifie=
r dysfunctionning // He reset it, site on Gen","loic.noumsi@matech-cameroun=
.com","248","07-07-2025 17:36:55","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005426955","E=
koumdoum OCM","","07-07-2025 17:15:12","07-07-2025 17:10:02","07-07-2025 17=
:54:18","Grid outage, site went down because Gen failed to start due to ''o=
vercurrent'' alarm // He reset DG card and started Gen manually","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
outage, site went down because Gen failed to start due to ''overcurrent'' a=
larm // He reset DG card and started Gen manually","loic.noumsi@matech-came=
roun.com","312","07-07-2025 17:15:12","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005426939","Eki=
e sud","","07-07-2025 17:13:07","07-07-2025 17:08:02","07-07-2025 18:36:59"=
,"Grid outage, site went down because Gen started and stopped due to alarm =
""High temp"" (unprouven alarm) // He reset DG card and started Gen manuall=
y","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid outage, site went down because Gen started and stopped due to =
alarm ""High temp"" (unprouven alarm) // He reset DG card and started Gen m=
anually","loic.noumsi@matech-cameroun.com","306","07-07-2025 17:13:07","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005426834","N=
kolbong","","07-07-2025 16:57:50","07-07-2025 16:53:39","07-07-2025 23:25:2=
3","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A) // Grid restoration","Delor Telezing","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down becau=
se Gen started and stopped due to Gen overload(22kva//350A) // Grid restora=
tion","gaelle.njiofack@matech-cameroun.com","252","07-07-2025 16:57:50","MA=
TECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0005426801","Mes=
sassi Ngonlonk","","07-07-2025 16:52:09","07-07-2025 16:50:01","07-07-2025 =
18:47:55","Grid outage site went down because Gen failed to start due to Ge=
n card faulty // He reset it and he Manually Started Gen","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e site went down because Gen failed to start due to Gen card faulty // He r=
eset it and he Manually Started Gen","loic.noumsi@matech-cameroun.com","129=
","07-07-2025 16:52:09","MATECH CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0005426741","Bye=
massi Carrefour","","07-07-2025 16:42:31","07-07-2025 16:38:24","07-07-2025=
 18:44:58","Grid outage, Site went down because Gen failed to start due to =
leak of oil,// Grid return","Paul BIBOUM","Equipment Repair","Passive","ACD=
G Gen","ACDG - Low Oil Pressure","Grid outage, Site went down because Gen f=
ailed to start due to leak of oil,// Grid return","loic.noumsi@matech-camer=
oun.com","248","07-07-2025 16:42:31","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005426708","B=
arriere","","07-07-2025 16:36:00","07-07-2025 16:35:56","07-07-2025 18:38:5=
2","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed // Site stabilised","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // Site stabilis=
ed","gaelle.njiofack@matech-cameroun.com","6","07-07-2025 16:36:00","MATECH=
 CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005426682","Nko=
abang2","","07-07-2025 16:32:38","03-07-2025 16:38:35","03-07-2025 16:56:23=
","Bactracking Grid outage, site went down due to gen overload (22KVA, 330A=
), SS Blaise IHS is informed // He reduced load, Gen started manually","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","B=
actracking Grid outage, site went down due to gen overload (22KVA, 330A), S=
S Blaise IHS is informed // He reduced load, Gen started manually","mouliom=
.anselme@matech-cameroun.com","345243","07-07-2025 16:32:38","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005426642","A=
fanoya","","07-07-2025 16:26:54","03-07-2025 16:51:50","03-07-2025 17:06:16=
","Backtracking No power issue on site , Ubaie=3D54.3V site On Grid The FME=
 TX Samba /655145055/ from Huawei is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Backtracking No power issue on site , Ubaie=3D54.3V site On Grid The FME T=
X Samba /655145055/ from Huawei is informed","mouliom.anselme@matech-camero=
un.com","344104","07-07-2025 16:26:54","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005426588","M=
ontee-Jouvence-II","","07-07-2025 16:23:14","03-07-2025 13:54:48","04-07-20=
25 14:09:33","Bactracking No power issue on site, site on Grid with Ubaie=
=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyem=
afo Gildas","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Bactracking No power issue on site, site on Grid wi=
th Ubaie=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informe=
d","mouliom.anselme@matech-cameroun.com","354506","07-07-2025 16:23:14","MA=
TECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0005426558","Ema=
na Lycee","","07-07-2025 16:20:00","07-07-2025 16:13:55","07-07-2025 17:39:=
18","Grid outage, Site went down doe to Gen Overload (20KVA : 220A) // Redu=
ction of the site load, and site on Gen","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down doe =
to Gen Overload (20KVA : 220A) // Reduction of the site load, and site on G=
en","loic.noumsi@matech-cameroun.com","367","07-07-2025 16:20:00","MATECH C=
MR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005426553","S=
IMBOCK BONAMBAPE","","07-07-2025 16:19:21","03-07-2025 19:41:17","03-07-202=
5 20:18:03","Bactracking Grid outage, Site went down before Gen start due t=
o poor backup // Site stabilised","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Bactracking Grid outage=
, Site went down before Gen start due to poor backup // Site stabilised","m=
ouliom.anselme@matech-cameroun.com","333484","07-07-2025 16:19:21","MATECH =
CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005426544","Evo=
doula MTN","","07-07-2025 16:18:15","07-07-2025 16:16:08","07-07-2025 16:18=
:45","	Grid outage, Site went down before Gen start due to poor backup// GR=
ID return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup// GRID return","gaelle.njiofack@matech-cameroun=
.com","128","07-07-2025 16:18:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005426471","Messassi=
 okolo","","07-07-2025 16:09:11","07-07-2025 16:04:16","07-07-2025 21:58:40=
","Cascaded Incident from TTO5603208","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","	Grid outage, site down becaus=
e site behaves as Grid only site (Gen Noise) // Grid returned","system","28=
7976","07-07-2025 16:09:11","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005426461","EMA=
NA BILICK CITY","IHS_YND_279","07-07-2025 16:08:20","07-07-2025 16:04:16","=
07-07-2025 22:04:49","	Grid outage, site down because site behaves as Grid =
only site (Gen Noise) // Grid returned","Fabrice Pouakam","Access Denial","=
Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","	Grid=
 outage, site down because site behaves as Grid only site (Gen Noise) // Gr=
id returned","loic.noumsi@matech-cameroun.com","246","07-07-2025 16:08:20",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_509","NOCINC0005426414","MANGUIER=
S CHAPELLE","","07-07-2025 15:58:09","07-07-2025 15:49:20","07-07-2025 16:1=
9:01","Cascaded Incident from TTO5603132","Fabrice Pouakam","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Gen failed to=
 start due to Water infiltration in the tank // tank purged, filter replace=
d and Gen start manually","system","288871","07-07-2025 15:58:09","MATECH C=
MR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005426404","M=
anguier","IHS_YND_506, IHS_YND_509","07-07-2025 15:56:27","07-07-2025 15:49=
:20","07-07-2025 17:14:01","Grid outage, Gen failed to start due to Water i=
nfiltration in the tank // tank purged, filter replaced and Gen start manua=
lly","Fabrice Pouakam","Fuel Outage (Probable)","Passive","Diesel","Tank Se=
aling Issue - Water In The Fuel","Grid outage, Gen failed to start due to W=
ater infiltration in the tank // tank purged, filter replaced and Gen start=
 manually","gaelle.njiofack@matech-cameroun.com","428","07-07-2025 15:56:27=
","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005426387","S=
imbock OCM","","07-07-2025 15:54:41","07-07-2025 15:48:34","07-07-2025 16:0=
9:20","	Active // No power issue Ubaie:53.5V site on Grid The Tx Fme Hosiah=
 Mbah (674007438) of Huawei is informed","Hyemafo Gildas","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Acti=
ve // No power issue Ubaie:53.5V site on Grid The Tx Fme Hosiah Mbah (67400=
7438) of Huawei is informed","gaelle.njiofack@matech-cameroun.com","368","0=
7-07-2025 15:54:41","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005426377","O=
mnisport-Rail","","07-07-2025 15:52:54","07-07-2025 15:49:20","07-07-2025 1=
6:19:01","cascaded site","Delor Telezing","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","cascaded site","gaelle.njiofack@matech-camer=
oun.com","288871","07-07-2025 15:52:54","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005426362","MBA=
LNGONG LYCEE","","07-07-2025 15:50:48","07-07-2025 15:45:42","07-07-2025 18=
:36:32","Grid outage,Site went down because Gen stopped due to overload(9kv=
a, 130A) SS IHS Felix Zambe is informed and confirmed // Site stabilised","=
Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gri=
d outage,Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Site stabilised","loic.noumsi@=
matech-cameroun.com","309","07-07-2025 15:50:48","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005426260","NKO=
MKANA ELIZA HOTEL","","07-07-2025 15:35:12","07-07-2025 15:31:06","07-07-20=
25 15:57:25","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","loic.noumsi@matech-c=
ameroun.com","248","07-07-2025 15:35:12","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005426172","A=
kak-Nkozoa-MTN-IHS","","07-07-2025 15:21:10","07-07-2025 15:16:58","07-07-2=
025 17:05:08","site went down because Gen stopped with failse alarm Oil pre=
ssure (malfunction of Gen card) // Resetting the generator card and site on=
 the generator","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","site went down because Gen stopped with failse alarm=
 Oil pressure (malfunction of Gen card) // Resetting the generator card and=
 site on the generator","gaelle.njiofack@matech-cameroun.com","254","07-07-=
2025 15:21:10","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005426008","NKO=
NGKARAK","","07-07-2025 15:05:37","07-07-2025 15:04:31","07-07-2025 15:38:1=
2","Grid outage, Site went down because Gen started and stopped due to High=
 temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, Site went down because Gen started and stop=
ped due to High temp alarm //He added water and Gen start manually","loic.n=
oumsi@matech-cameroun.com","67","07-07-2025 15:05:37","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005425820","Evo=
doula MTN","","07-07-2025 14:52:40","07-07-2025 14:42:33","07-07-2025 15:02=
:08","Grid outage, Site went down before Gen start due to poor backup // Ge=
n Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen Automatically Started","ga=
elle.njiofack@matech-cameroun.com","608","07-07-2025 14:52:40","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0005425817","Ole=
mbe MTN","","07-07-2025 14:52:07","07-07-2025 14:47:01","07-07-2025 15:36:1=
4","Site went down due to Disjunction of rectifiers // Rectifiers reset","F=
abrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Distrib=
ution","Site went down due to Disjunction of rectifiers // Rectifiers reset=
","gaelle.njiofack@matech-cameroun.com","307","07-07-2025 14:52:07","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005425609","B=
arriere","","07-07-2025 14:14:13","07-07-2025 14:09:03","07-07-2025 16:27:3=
3","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed // Site stabilised","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // Site stabilis=
ed","vanel.mbiada@matech-cameroun.com","313","07-07-2025 14:14:13","MATECH =
CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005425523","Eto=
ug ebe biscuiterie","","07-07-2025 14:02:24","07-07-2025 13:55:10","07-07-2=
025 14:50:25","Grid outage, and Grid return but Grid contactor Did not stic=
k // contactor set to forced mode","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","Giress will on site after Akak-Nkozo=
a","cedric.tiani@matech-cameroun.com","435","07-07-2025 14:02:24","MATECH C=
MR"
"Closed Complete","Site Down","CTR_066","IHS_YND_367","NOCINC0005425480","M=
andoumba OCM","","07-07-2025 13:54:02","07-07-2025 13:53:47","07-07-2025 13=
:55:39","Active// No power issue on site, Ubaie =3D 52.5 V Site on Grid. TX=
 FME ETIENNE Fopa (695033981/Huawei) is informed","Kemeni Franklin","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power issue on site, Ubaie =3D 52.5 V Site on Grid. TX FME=
 ETIENNE Fopa (695033981/Huawei) is informed","vanel.mbiada@matech-cameroun=
.com","47","07-07-2025 13:54:02","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005425459","A=
kak-Nkozoa-MTN-IHS","","07-07-2025 13:50:58","07-07-2025 13:44:46","07-07-2=
025 15:02:59","site went down because Gen stopped with failse alarm Oil pre=
ssure (malfunction of Gen card) // Resetting the generator card and site on=
 the generator","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","site went down because Gen stopped with failse alarm=
 Oil pressure (malfunction of Gen card) // Resetting the generator card and=
 site on the generator","vanel.mbiada@matech-cameroun.com","376","07-07-202=
5 13:50:58","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0005425345","Ole=
mbe MTN","","07-07-2025 13:31:56","07-07-2025 13:31:40","07-07-2025 13:32:1=
8","Site went down due to Disjunction of rectifiers // Rectifiers reset","F=
abrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Cabinet=
","	Site went down due to Disjunction of rectifiers // Rectifiers reset","c=
edric.tiani@matech-cameroun.com","17","07-07-2025 13:31:56","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0005425210","Ole=
mbe MTN","","07-07-2025 13:13:09","07-07-2025 13:10:59","07-07-2025 13:15:3=
6","Site went down due to Disjunction of rectifiers // Rectifiers reset","F=
abrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Cabinet=
","	Site went down due to Disjunction of rectifiers // Rectifiers reset","c=
edric.tiani@matech-cameroun.com","132","07-07-2025 13:13:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005425055","Messassi=
 okolo","","07-07-2025 12:53:31","07-07-2025 12:52:51","07-07-2025 14:40:42=
","Cascaded Incident from TTO5601615","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (Gen Noise) // Grid returned","system","270=
749","07-07-2025 12:53:31","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005425051","E=
MANA BILICK CITY","IHS_YND_279","07-07-2025 12:52:58","07-07-2025 12:52:51"=
,"07-07-2025 14:46:05","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid returned","Fabrice Pouakam","Access Denial",=
"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid=
 outage, site down because site behaves as Grid only site (Gen Noise) // Gr=
id returned","vanel.mbiada@matech-cameroun.com","9","07-07-2025 12:52:58","=
MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005424667","N=
koabang Ebolmedjock","","07-07-2025 12:07:43","07-07-2025 12:06:32","07-07-=
2025 12:12:44","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Gen. Notice that it is impacted b=
y Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matech-camero=
un.com","72","07-07-2025 12:07:43","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005424620","NKO=
MKANA ELIZA HOTEL","","07-07-2025 11:56:30","07-07-2025 11:49:11","07-07-20=
25 11:51:07","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","cedric.tiani@matech-=
cameroun.com","440","07-07-2025 11:56:30","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005424601","A=
kak-Nkozoa-MTN-IHS","","07-07-2025 11:51:49","07-07-2025 11:49:40","07-07-2=
025 12:45:27","site went down because Gen stopped with failse alarm Oil pre=
ssure (malfunction of Gen card) // Resetting the generator card and site on=
 the generator","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","site went down because Gen stopped with failse alarm=
 Oil pressure (malfunction of Gen card) // Resetting the generator card and=
 site on the generator","vanel.mbiada@matech-cameroun.com","133","07-07-202=
5 11:51:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005424532","Minka","=
","07-07-2025 11:43:22","07-07-2025 11:39:00","07-07-2025 11:45:24","Cascad=
ed Incident from TTO5600974","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability.Henri (699949693) from=
 Huawei is informed.","system","267986","07-07-2025 11:43:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005424533","Mom","",=
"07-07-2025 11:43:22","07-07-2025 11:39:00","07-07-2025 11:45:24","Cascaded=
 Incident from TTO5600974","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on grid with U=3D54v Site is=
 impacted by Ngoumou who is not our responsability.Henri (699949693) from H=
uawei is informed.","system","267985","07-07-2025 11:43:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005424530","OLAMA","=
","07-07-2025 11:43:21","07-07-2025 11:39:00","07-07-2025 11:45:24","Cascad=
ed Incident from TTO5600974","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability.Henri (699949693) from=
 Huawei is informed.","system","267984","07-07-2025 11:43:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005424531","OTELE MT=
N","","07-07-2025 11:43:21","07-07-2025 11:39:00","07-07-2025 11:45:24","Ca=
scaded Incident from TTO5600974","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on grid with U=3D54v S=
ite is impacted by Ngoumou who is not our responsability.Henri (699949693) =
from Huawei is informed.","system","267984","07-07-2025 11:43:21","MATECH C=
MR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005424490","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","07-07-2025 11:40:=
12","07-07-2025 11:39:00","07-07-2025 11:45:24","No power issue site on gri=
d with U=3D54v Site is impacted by Ngoumou who is not our responsability.He=
nri (699949693) from Huawei is informed.","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on grid with U=3D54v Site is impacted by Ngoumou who is not ou=
r responsability.Henri (699949693) from Huawei is informed.","cedric.tiani@=
matech-cameroun.com","74","07-07-2025 11:40:12","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005424432","A=
wae Ewonkan","","07-07-2025 11:31:01","07-07-2025 11:30:57","07-07-2025 11:=
32:52","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed// // Site stabilised","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down=
 due to Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed// // Si=
te stabilised","vanel.mbiada@matech-cameroun.com","7","07-07-2025 11:31:01"=
,"MATECH CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0005423715","OKO=
A Peage","","07-07-2025 09:52:12","07-07-2025 09:49:49","07-07-2025 10:25:1=
8","Grid outage, Site went because Gen ran until fuel shortage//Refueling D=
one","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid o=
utage, Site went because Gen ran until fuel shortage//Refueling Done","cedr=
ic.tiani@matech-cameroun.com","144","07-07-2025 09:52:12","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005423684","M=
EHANDAN","","07-07-2025 09:48:48","07-07-2025 09:41:33","07-07-2025 11:00:5=
8","	No power issue on site ,site on Grid with Ubaie=3D54 V the TX fme Lion=
el /655184876 from huawei is Informed site Impacted by Odza 2","Albran Byor=
el","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","	No power issue on site ,site on Grid with Ubaie=3D54 V the=
 TX fme Lionel /655184876 from huawei is Informed site Impacted by Odza 2",=
"vanel.mbiada@matech-cameroun.com","438","07-07-2025 09:48:48","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005423651","O=
dza II OCM","","07-07-2025 09:45:54","07-07-2025 09:40:42","07-07-2025 09:4=
9:42","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction// site stabilised","Albran Byorel","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Grid outage, site went down =
because gen failed to start due to PWC ZTE malfunction// site stabilised","=
vanel.mbiada@matech-cameroun.com","315","07-07-2025 09:45:54","MATECH CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0005423395","N=
kenglikok","","07-07-2025 09:06:41","07-07-2025 09:03:28","07-07-2025 09:06=
:00","No power issue on site U=3D53.2v site on battery The fme Tx Etienne 6=
95033981 of huawei is informed","Kemeni Franklin","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site U=3D53.2v site on battery The fme Tx Etienne 695033981 of huawei =
is informed","vanel.mbiada@matech-cameroun.com","194","07-07-2025 09:06:41"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005423269","B=
arriere","","07-07-2025 08:46:02","07-07-2025 08:40:52","07-07-2025 11:23:2=
5","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed/// He reduced the load and site on Gen","Hyemafo Gilda=
s","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, =
Site went down because Gen overload (30kva, 410A) SS IHS Felix ZAMBE confir=
med/// He reduced the load","vanel.mbiada@matech-cameroun.com","313","07-07=
-2025 08:46:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005423231","MEHANDAN=
","","07-07-2025 08:37:40","07-07-2025 08:34:49","07-07-2025 08:43:44","Cas=
caded Incident from TTO5599549","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Grid stabilized","system","=
278982","07-07-2025 08:37:40","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005423227","O=
dza II OCM","IHS_YND_528","07-07-2025 08:36:57","07-07-2025 08:34:49","07-0=
7-2025 08:43:44","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Grid =
stabilized","vanel.mbiada@matech-cameroun.com","132","07-07-2025 08:36:57",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005423049","B=
arriere","","07-07-2025 07:57:48","07-07-2025 07:52:39","07-07-2025 08:08:5=
1","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed// Site stabilized","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed","stephane.nkamwa=
@ihstowers.com","312","07-07-2025 07:57:48","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005423028","C=
-Supreme","","07-07-2025 07:52:44","07-07-2025 07:48:28","07-07-2025 08:01:=
57","Active // No power issue, site on Grid with Ubaie=3D54.2V, Brice Tsagu=
e (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power is=
sue, site on Grid with Ubaie=3D54.2V, Brice Tsague (650 21 40 96 / Huawei) =
is informed","vanel.mbiada@matech-cameroun.com","257","07-07-2025 07:52:44"=
,"MATECH CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0005422926","Eko=
unou","","07-07-2025 07:25:10","07-07-2025 07:22:00","07-07-2025 08:08:52",=
"Grid outage, site went down because gen failed to start with alarm undervo=
ltage // He reset gen card and gen manually started","Albran Byorel","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site=
 went down because gen failed to start with alarm undervoltage // He reset =
gen card and gen manually started","cedric.tiani@matech-cameroun.com","192"=
,"07-07-2025 07:25:10","MATECH CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0005422681","Av =
Kennedy","","07-07-2025 06:16:35","07-07-2025 05:21:59","07-07-2025 08:50:4=
1","BACKTRACKING. Grid outage.no space to deploy mobile gen // Grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d outage.no space to deploy mobile gen // Grid return","franck.nkomot@matec=
h-cameroun.com","3916","07-07-2025 06:16:35","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005422653","M=
vog-Manga","","07-07-2025 06:08:12","07-07-2025 06:04:15","07-07-2025 07:19=
:55","No power Issue","Albran Byorel","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","Active//No power issue on site Ubaie: 53 V site on =
Grid The TX Lionel steve (655184876 /Huawei)) is informed.","loic.noumsi@ma=
tech-cameroun.com","273640","07-07-2025 06:08:12","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005422640","O=
dza","IHS_YND_254, IHS_YND_580","07-07-2025 06:07:30","07-07-2025 06:04:15"=
,"07-07-2025 08:27:01","Active//No power issue on site Ubaie: 53 V site on =
Grid The TX Lionel steve (655184876 /Huawei)) is informed.","Albran Byorel"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue on site Ubaie: 53 V site on Grid The TX=
 Lionel steve (655184876 /Huawei)) is informed.","loic.noumsi@matech-camero=
un.com","197","07-07-2025 06:07:30","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005422638","M=
arche Odza","","07-07-2025 06:06:51","07-07-2025 06:04:15","07-07-2025 07:1=
9:55","","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Active//No power issue on site Ubaie: 53 V site on Grid The TX L=
ionel steve (655184876 /Huawei)) is informed.","loic.noumsi@matech-cameroun=
.com","273639","07-07-2025 06:06:51","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005422635","Evo=
doula MTN","","07-07-2025 06:05:22","07-07-2025 05:59:07","07-07-2025 06:09=
:16","Grid outage, Site went down before Gen start due to poor backup// GRI=
D return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// GRID return","franck.nkomot@matech-cameroun.co=
m","376","07-07-2025 06:05:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005422566","Akak-Nko=
zoa-MTN-IHS","","07-07-2025 05:41:50","07-07-2025 05:31:38","07-07-2025 06:=
39:38","Cascaded Incident from TTO5598818","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
: 50.6V site on Grid. Sinphorien (691316854/Huawei) is informed.","system",=
"275593","07-07-2025 05:41:50","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0005422554","C=
RF Nkoabang","","07-07-2025 05:35:02","07-07-2025 03:22:50","07-07-2025 07:=
40:14","Grid-solar site, Grid outage, site down due to sunset, // Grid retu=
rn","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Grid=
 Outage Issue","Grid-solar site, Grid outage, site down due to sunset, // G=
rid return","loic.noumsi@matech-cameroun.com","7934","07-07-2025 05:35:02",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005421684","B=
arriere","","06-07-2025 22:28:27","06-07-2025 19:08:42","06-07-2025 23:56:1=
6","Backtracking//No power issue on site Ubay: 53.3V site on Gen TX Fme SAM=
BA (654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Backtracki=
ng//No power issue on site Ubay: 53.3V site on Gen TX Fme SAMBA (654266058/=
Huawei) is informed.","loic.noumsi@matech-cameroun.com","11988","06-07-2025=
 22:28:27","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005421419","N=
KOLMEKONG YDE","","06-07-2025 21:26:45","06-07-2025 21:21:36","06-07-2025 2=
3:08:59","  Site down due to Disjonction  in the power bay // CB reamed","F=
abrice Pouakam","Equipment Repair","Passive","Control Panel","Circuit Break=
er Tripped","  Site down due to Disjonction  in the power bay // CB reamed"=
,"loic.noumsi@matech-cameroun.com","312","06-07-2025 21:26:45","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005421382","A=
wae Ewonkan","","06-07-2025 21:18:38","06-07-2025 21:13:31","06-07-2025 21:=
54:51","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid stabilised","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid s=
tabilised","loic.noumsi@matech-cameroun.com","310","06-07-2025 21:18:38","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0005421164","N=
R-Omnisport","","06-07-2025 20:47:56","06-07-2025 20:41:45","06-07-2025 21:=
56:52","Grid outage,site went down because Gen failed to start due to stati=
c battery charger faulty//Grid return","Delor Telezing","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Charging Alternator","Grid outage,site went do=
wn because Gen failed to start due to static battery charger faulty//Grid r=
eturn","loic.noumsi@matech-cameroun.com","372","06-07-2025 20:47:56","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0005421102","Lobo 2",=
"","06-07-2025 20:35:50","06-07-2025 20:28:12","06-07-2025 21:12:38","Casca=
ded Incident from TTO5597165","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage , Site down becau=
se alternator charger is faulty // battery charger connected direct ","syst=
em","286529","06-07-2025 20:35:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0005421096","LOBO MTN=
","","06-07-2025 20:35:12","06-07-2025 20:28:12","06-07-2025 21:12:38","Cas=
caded Incident from TTO5597165","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage , Site down bec=
ause alternator charger is faulty // battery charger connected direct ","sy=
stem","286530","06-07-2025 20:35:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0005421095","Ekekam",=
"","06-07-2025 20:35:12","06-07-2025 20:28:12","06-07-2025 21:12:38","Casca=
ded Incident from TTO5597165","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage , Site down becau=
se alternator charger is faulty // battery charger connected direct ","syst=
em","286525","06-07-2025 20:35:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0005421097","NKONGKAR=
AK","","06-07-2025 20:35:12","06-07-2025 20:28:12","06-07-2025 21:12:38","C=
ascaded Incident from TTO5597165","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage , Site down b=
ecause alternator charger is faulty // battery charger connected direct ","=
system","286528","06-07-2025 20:35:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0005421091","Ngog Map=
ubi","","06-07-2025 20:35:11","06-07-2025 20:28:12","06-07-2025 21:12:38","=
Cascaded Incident from TTO5597165","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , Site down because a=
lternator charger is faulty // battery charger connected direct ","system",=
"286529","06-07-2025 20:35:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005421092","Ebeba","=
","06-07-2025 20:35:11","06-07-2025 20:28:12","06-07-2025 21:12:38","Cascad=
ed Incident from TTO5597165","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage , Site down because alternator =
charger is faulty // battery charger connected direct ","system","286527","=
06-07-2025 20:35:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0005421093","Bot Maka=
k","","06-07-2025 20:35:11","06-07-2025 20:28:12","06-07-2025 21:12:38","Ca=
scaded Incident from TTO5597165","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage , Site down because alternator charger=
 is faulty // battery charger connected direct ","system","286526","06-07-2=
025 20:35:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005421094","Mambine"=
,"","06-07-2025 20:35:11","06-07-2025 20:28:12","06-07-2025 21:12:38","Casc=
aded Incident from TTO5597165","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage , Site down because alternato=
r charger is faulty // battery charger connected direct ","system","286525"=
,"06-07-2025 20:35:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0005421090","Nkeng li=
kok","","06-07-2025 20:35:10","06-07-2025 20:28:12","06-07-2025 21:12:38","=
Cascaded Incident from TTO5597165","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , Site down because a=
lternator charger is faulty // battery charger connected direct ","system",=
"286527","06-07-2025 20:35:10","MATECH CMR"
"Closed Complete","Site Down","T0236","IHS_YND_373","NOCINC0005421066","Mal=
oun","IHS_YND_783, IHS_YND_347, IHS_YND_419, IHS_YND_339, IHS_YND_421, IHS_=
YND_350, IHS_YND_714, IHS_YND_342, IHS_YND_713","06-07-2025 20:31:21","06-0=
7-2025 20:28:12","06-07-2025 21:53:30","Grid outage , Site down because alt=
ernator charger is faulty // battery charger connected direct ","Kemeni Fra=
nklin","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator"=
,"Grid outage , Site down because alternator charger is faulty // battery c=
harger connected direct ","cedric.tiani@matech-cameroun.com","190","06-07-2=
025 20:31:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005420757","Mfou EPC=
","","06-07-2025 19:23:50","06-07-2025 19:15:05","06-07-2025 19:36:21","Cas=
caded Incident from TTO5596808","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Grid stabilised","system","269359","06-07-2025=
 19:23:50","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005420751","M=
fou OCM","IHS_YND_674","06-07-2025 19:23:11","06-07-2025 19:15:05","06-07-2=
025 19:36:21","Grid Outage, Site Down before gen Started due to poor backup=
 // Grid stabilised","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen =
Started due to poor backup // Grid stabilised","loic.noumsi@matech-cameroun=
.com","487","06-07-2025 19:23:11","MATECH CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0005420742","OKO=
A Peage","","06-07-2025 19:19:53","06-07-2025 19:17:37","06-07-2025 20:04:3=
0","Grid outage.site went down due to relay 220v dysfunctionning// He recon=
nected it, site on Gen","Fanda Brice","Equipment Repair","Passive","Control=
 Panel","ATS Relay Faulty","Grid outage.site went down due to relay 220v dy=
sfunctionning// He reconnected it, site on Gen","cedric.tiani@matech-camero=
un.com","137","06-07-2025 19:19:53","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005420706","MBA=
LNGONG LYCEE","","06-07-2025 19:14:37","06-07-2025 19:13:23","07-07-2025 14=
:59:52","Grid outage,Site went down because Gen stopped due to overload(9kv=
a, 130A) SS IHS Felix Zambe is informed and confirmed // Grid returned","Fa=
nda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage,Site went down because Gen stopped due to overload(9kva, 130A) SS IH=
S Felix Zambe is informed and confirmed // Grid returned","cedric.tiani@mat=
ech-cameroun.com","76","06-07-2025 19:14:37","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005420702","Mvo=
g-Manga","","06-07-2025 19:13:43","06-07-2025 19:12:29","06-07-2025 20:17:1=
3","Grid fluctuations, site went down due to rectifier issue // He reset it=
 ","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Grid fluctuations, site went down due to rectifier issue // He reset i=
t ","cedric.tiani@matech-cameroun.com","76","06-07-2025 19:13:43","MATECH C=
MR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005420690","NKO=
MKANA ELIZA HOTEL","","06-07-2025 19:10:53","06-07-2025 19:08:42","06-07-20=
25 19:10:46","(Unstable )Site went down due to PWC Overloaded and SS IHS Be=
rnard Atangana confirmed // Grid return","","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","(Unstable )Site went down due to P=
WC Overloaded and SS IHS Bernard Atangana confirmed // Grid return","cedric=
.tiani@matech-cameroun.com","132","06-07-2025 19:10:53","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005420625","A=
wae Ewonkan","","06-07-2025 18:58:29","06-07-2025 18:56:22","06-07-2025 19:=
10:25","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Site stabilised","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Site s=
tabilised","loic.noumsi@matech-cameroun.com","130","06-07-2025 18:58:29","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005420588","MEHANDAN=
","","06-07-2025 18:52:00","06-07-2025 18:42:19","06-07-2025 18:53:46","Cas=
caded Incident from TTO5596617","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Grid stabilized","system","=
1213403","06-07-2025 18:52:00","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005420581","O=
dza II OCM","IHS_YND_528","06-07-2025 18:50:26","06-07-2025 18:42:19","06-0=
7-2025 18:53:46","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Grid =
stabilized","loic.noumsi@matech-cameroun.com","490","06-07-2025 18:50:26","=
MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005419849","M=
ANGUIERS CHAPELLE","","06-07-2025 16:55:13","06-07-2025 16:53:49","06-07-20=
25 17:57:05","Active//No power issue on site ,site on Grid with Ubaie=3D53.=
3 V The Tx FME Symphorien (650257151 / Huawei) is informed ","Fabrice Pouak=
am","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue on site ,site on Grid with Ubaie=3D5=
3.3 V The Tx FME Symphorien (650257151 / Huawei) is informed ","loic.noumsi=
@matech-cameroun.com","86","06-07-2025 16:55:13","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005419838","NKO=
MKANA ELIZA HOTEL","","06-07-2025 16:54:18","06-07-2025 16:52:10","06-07-20=
25 17:17:52","(Unstable )Site went down due to PWC Overloaded and SS IHS Be=
rnard Atangana confirmed // Grid return","","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","(Unstable )Site went down due to P=
WC Overloaded and SS IHS Bernard Atangana confirmed // Grid return","cedric=
.tiani@matech-cameroun.com","129","06-07-2025 16:54:18","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005419795","SIM=
BOCK BONAMBAPE","","06-07-2025 16:49:28","06-07-2025 16:47:15","06-07-2025 =
16:49:14","Grid outage, Site went down before Gen start due to poor backup =
// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","cedric.tiani@matech-cameroun.com","=
135","06-07-2025 16:49:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005419780","Mfou EPC=
","","06-07-2025 16:46:59","06-07-2025 16:45:20","06-07-2025 16:57:21","Cas=
caded Incident from TTO5595707","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Gen automatically  started","system","264238",=
"06-07-2025 16:46:59","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005419763","M=
fou OCM","IHS_YND_674","06-07-2025 16:46:28","06-07-2025 16:45:20","06-07-2=
025 16:57:21","Grid Outage, Site Down before gen Started due to poor backup=
 // Gen automatically  started","Mba Lazare Herve","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down =
before gen Started due to poor backup // Gen automatically  started","loic.=
noumsi@matech-cameroun.com","70","06-07-2025 16:46:28","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005419553","Lad=
a I Yde","","06-07-2025 16:10:45","06-07-2025 16:08:35","06-07-2025 16:25:2=
3","Site went down because gen fails to start due to grid bad voltage // He=
 bypass grid and manually start the gen","Mba Lazare Herve","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Site went down b=
ecause gen fails to start due to grid bad voltage // He bypass grid and man=
ually start the gen","cedric.tiani@matech-cameroun.com","132","06-07-2025 1=
6:10:45","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005419307","B=
arriere","","06-07-2025 15:32:21","06-07-2025 15:28:10","06-07-2025 16:02:5=
1","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed//He reduiced the load and manually started the Gen","H=
yemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid outage, Site went down because Gen overload (30kva, 410A) SS IHS Felix =
ZAMBE confirmed//He reduiced the load and manually started the Gen","loic.n=
oumsi@matech-cameroun.com","254","06-07-2025 15:32:21","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005419252","C=
-Supreme","","06-07-2025 15:25:58","06-07-2025 15:21:50","06-07-2025 15:25:=
37","Active // No power issue, site on Grid with Ubaie=3D54.5V, Brice Tsagu=
e (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power is=
sue, site on Grid with Ubaie=3D54.5V, Brice Tsague (650 21 40 96 / Huawei) =
is informed","loic.noumsi@matech-cameroun.com","249","06-07-2025 15:25:58",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005419202","B=
arriere","","06-07-2025 15:16:21","06-07-2025 15:14:16","06-07-2025 15:20:0=
3","Site unstable : No power issue on site Ubay: 53.3V site on Gen TX Fme S=
AMBA (654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Site uns=
table : No power issue on site Ubay: 53.3V site on Gen TX Fme SAMBA (654266=
058/Huawei) is informed.","loic.noumsi@matech-cameroun.com","128","06-07-20=
25 15:16:21","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005419126","Nsi=
malen MTN","","06-07-2025 15:02:22","06-07-2025 14:59:10","06-07-2025 15:55=
:50","Site went down because Gen started and stopped with ""low oil pressur=
e"" alarm// He added oil and started Gen manualy","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down be=
cause Gen started and stopped with ""low oil pressure"" alarm// He added oi=
l and started Gen manualy","cedric.tiani@matech-cameroun.com","193","06-07-=
2025 15:02:22","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005419105","Evo=
doula MTN","","06-07-2025 14:55:53","06-07-2025 14:47:41","06-07-2025 15:21=
:05","Grid outage, Site went down before Gen start due to poor backup// Gen=
 manually  Started	","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup// Gen manually  Started	","cedric.tia=
ni@matech-cameroun.com","493","06-07-2025 14:55:53","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005418978","Lad=
a I Yde","","06-07-2025 14:32:43","06-07-2025 14:28:35","06-07-2025 16:03:3=
2","Site went down because gen fails to start due to grid bad voltage // He=
 bypass grid and manually start the gen","Mba Lazare Herve","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Site went down b=
ecause gen fails to start due to grid bad voltage // He bypass grid and man=
ually start the gen","cedric.tiani@matech-cameroun.com","249","06-07-2025 1=
4:32:43","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005418818","O=
dza II OCM","","06-07-2025 14:05:26","06-07-2025 14:04:49","06-07-2025 14:0=
8:18","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction//He reset it and site on Grid","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction//He rese=
t it and site on Grid","vanel.mbiada@matech-cameroun.com","40","06-07-2025 =
14:05:26","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005418728","M=
ANGUIERS CHAPELLE","","06-07-2025 13:50:35","06-07-2025 13:47:19","06-07-20=
25 13:55:02","Active//No power issue on site ,site on Grid with Ubaie=3D53.=
6 V The Tx FME Symphorien (650257151 / Huawei) is informed","Fabrice Pouaka=
m","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issue on site ,site on Grid with Ubaie=3D53=
.6 V The Tx FME Symphorien (650257151 / Huawei) is informed","vanel.mbiada@=
matech-cameroun.com","198","06-07-2025 13:50:35","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005418424","N=
kolondom","","06-07-2025 12:56:28","06-07-2025 12:54:20","06-07-2025 13:08:=
30","Grid fluctuation,Site went down because GEN failed to start due to gri=
d bad voltage// site on grid on 02 phases","Fabrice Pouakam","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
n,Site went down because GEN failed to start due to grid bad voltage// site=
 on grid on 02 phases","vanel.mbiada@matech-cameroun.com","130","06-07-2025=
 12:56:28","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005418422","Evo=
doula MTN","","06-07-2025 12:55:55","06-07-2025 12:52:45","06-07-2025 13:09=
:12","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","gael=
le.njiofack@matech-cameroun.com","191","06-07-2025 12:55:55","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005418414","B=
arriere","","06-07-2025 12:55:10","06-07-2025 12:50:56","06-07-2025 14:06:4=
3","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed// Grid return","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Ge=
n overload (30kva, 410A) SS IHS Felix ZAMBE confirmed// Grid return","vanel=
.mbiada@matech-cameroun.com","256","06-07-2025 12:55:10","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005418305","Awa=
e Ewonkan","","06-07-2025 12:40:20","06-07-2025 12:37:03","06-07-2025 12:38=
:13","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)IHS=
 SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to =
Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed // Grid return"=
,"gaelle.njiofack@matech-cameroun.com","199","06-07-2025 12:40:20","MATECH =
CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005418287","M=
elen Ba'aba","","06-07-2025 12:36:23","06-07-2025 12:35:10","06-07-2025 12:=
42:43","Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME =
Julien(693095849) from Huawei is informed","Siligap Boris","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Julien(69309=
5849) from Huawei is informed","vanel.mbiada@matech-cameroun.com","75","06-=
07-2025 12:36:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005418084","Carrefou=
rt Nkomo","","06-07-2025 12:05:40","06-07-2025 11:56:59","06-07-2025 12:41:=
51","Cascaded Incident from TTO5593802","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid fluctuations, site wen=
t down because gen failed to start due to PWC ZTE malfunction // He reset i=
t and manally started the Gen=09
","system","1216367","06-07-2025 12:05:40","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005418041","Nko=
mo","IHS_YND_174","06-07-2025 11:58:10","06-07-2025 11:56:59","06-07-2025 1=
2:44:16","Grid fluctuations, site went down because gen failed to start due=
 to PWC ZTE malfunction // He reset it and manally started the Gen	","Mba L=
azare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module Ove=
rloaded","Grid fluctuations, site went down because gen failed to start due=
 to PWC ZTE malfunction // He reset it and manally started the Gen=09
","gaelle.njiofack@matech-cameroun.com","72","06-07-2025 11:58:10","MATECH =
CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0005417817","M=
atomb","","06-07-2025 11:19:24","06-07-2025 11:13:13","06-07-2025 15:52:42"=
,"Site went down due to insufficient rectifiers on site (03)//He added 1 re=
ctifier","Kemeni Franklin","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficient rectifiers on site (03)//He=
 added 1 rectifier","vanel.mbiada@matech-cameroun.com","372","06-07-2025 11=
:19:24","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005417602","NKO=
MKANA ELIZA HOTEL","","06-07-2025 10:42:46","06-07-2025 10:41:36","06-07-20=
25 10:43:46","Grid outage, no space to deploy mobile gen // Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy mobile gen // Grid return","gaelle.njiofack@matec=
h-cameroun.com","71","06-07-2025 10:42:46","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005417555","N=
koabang Ebolmedjock","","06-07-2025 10:35:12","06-07-2025 10:33:04","06-07-=
2025 10:37:32","Site impacted by CTR_711 Nkolmesseng Abom not ihs site","Mb=
a Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fai=
lure","Affected by 3rd Party Site","Site impacted by CTR_711 Nkolmesseng Ab=
om not ihs site","gaelle.njiofack@matech-cameroun.com","129","06-07-2025 10=
:35:12","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005417544","O=
lembe","","06-07-2025 10:33:16","06-07-2025 10:32:00","06-07-2025 10:42:18"=
,"Grid bad voltage , Site down because gen fails to start due to grid bad v=
oltage// gen manually started","Fabrice Pouakam","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Grid bad voltage , Site dow=
n because gen fails to start due to grid bad voltage// gen manually started=
","vanel.mbiada@matech-cameroun.com","78","06-07-2025 10:33:16","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005417413","MEHANDAN=
","","06-07-2025 10:10:50","06-07-2025 10:06:59","06-07-2025 11:49:44","Cas=
caded Incident from TTO5593041","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction//He reset it and site on Gen",=
"system","280654","06-07-2025 10:10:50","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005417401","O=
dza II OCM","IHS_YND_528","06-07-2025 10:10:11","06-07-2025 10:06:59","06-0=
7-2025 11:49:44","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction//He reset it and site on Gen","Albran Byorel","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid o=
utage, site went down because gen failed to start due to PWC ZTE malfunctio=
n//He reset it and site on Gen","vanel.mbiada@matech-cameroun.com","196","0=
6-07-2025 10:10:11","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005417374","T=
SINGA VILLAGE 2","","06-07-2025 10:04:22","06-07-2025 10:02:10","06-07-2025=
 10:39:38","Active//No power issue on site, Site on Battery UBAIE=3D54.5V s=
ynphorien (675295205) From huawei is informed","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site, Site on Battery UBAIE=3D54.5V synphorien (=
675295205) From huawei is informed","vanel.mbiada@matech-cameroun.com","134=
","06-07-2025 10:04:22","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005417280","Lad=
a I Yde","","06-07-2025 09:46:20","06-07-2025 09:44:13","06-07-2025 09:57:2=
7","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","gaelle.njiofack@matech-cameroun.com","129","06-07-2025 09:46:20","MATECH=
 CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005416969","Nko=
mo stade","","06-07-2025 08:41:23","06-07-2025 08:38:17","06-07-2025 09:12:=
08","Grid outage, Site went down because Gen Stopped due to alarm Under vol=
tage ( impacted by AVR malfunction) //  adjustment of AVR and manually star=
t generator ","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Under Voltage","Grid outage, Site went down because Gen Stopped due t=
o alarm Under voltage ( impacted by AVR malfunction) //  adjustment of AVR =
and manually start generator ","gaelle.njiofack@matech-cameroun.com","187",=
"06-07-2025 08:41:23","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005416928","A=
wae Ewonkan","","06-07-2025 08:30:34","06-07-2025 08:25:19","06-07-2025 12:=
23:52","Grid outage site went down due to Gen Overload (20Kva, Iload 320A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 320A)IHS SS Alphonse is informed//Grid return"=
,"vanel.mbiada@matech-cameroun.com","317","06-07-2025 08:30:34","MATECH CMR=
"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005416891","B=
arriere","","06-07-2025 08:16:18","06-07-2025 08:14:05","06-07-2025 11:10:4=
8","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed// Grid return","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Ge=
n overload (30kva, 410A) SS IHS Felix ZAMBE confirmed// Grid return","vanel=
.mbiada@matech-cameroun.com","136","06-07-2025 08:16:18","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005416828","A=
kak-Nkozoa-MTN-IHS","","06-07-2025 08:00:55","06-07-2025 07:58:42","06-07-2=
025 11:07:10","Site impacted by AKAK IHS (ctr_513) //No power issue on site=
 Ubaie: 53V site on Grd. Sephorien (691316854/Huawei) is informed.","Fabric=
e Pouakam","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","Site impacted by AKAK IHS (ctr_513) //No power issue=
 on site Ubaie: 53V site on Grd. Sephorien (691316854/Huawei) is informed."=
,"vanel.mbiada@matech-cameroun.com","137","06-07-2025 08:00:55","MATECH CMR=
"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005416710","A=
wae Ewonkan","","06-07-2025 07:36:28","06-07-2025 07:34:40","06-07-2025 07:=
39:11","No power issue on site Tx issue U=3D54.1V site on Grid , the fme tx=
 Leonel Steve//655184876 from Huawei is informed","Albran Byorel","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site Tx issue U=3D54.1V site on Grid , the fme tx Leon=
el Steve//655184876 from Huawei is informed","vanel.mbiada@matech-cameroun.=
com","110","06-07-2025 07:36:28","MATECH CMR"
"Closed Complete","Warning","T0351","IHS_YND_146","NOCINC0005416629","Nsime=
yong","","06-07-2025 07:13:37","","","Our technican Nicolas, Our RM Willy a=
nd Ihs RM Armel are on site for work // End of work","MINKA NICOLAS","Warni=
ng","Warning","POWER","Warning - Site on Battery","Our technican Nicolas, O=
ur RM Willy and Ihs RM Armel are on site for work // End of work","gaelle.n=
jiofack@matech-cameroun.com","3323","06-07-2025 07:13:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005416054","MEHANDAN=
","","06-07-2025 04:57:41","06-07-2025 04:50:53","06-07-2025 04:55:22","Cas=
caded Incident from TTO5591537","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Grid stabilized","system","=
263639","06-07-2025 04:57:41","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005416030","Odz=
a II OCM","IHS_YND_528","06-07-2025 04:51:01","06-07-2025 04:50:53","06-07-=
2025 04:55:22","Grid outage, site went down because gen failed to start due=
 to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site =
went down because gen failed to start due to PWC ZTE malfunction // Grid st=
abilized","edwige.kapawo@matech-cameroun.com","10","06-07-2025 04:51:01","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005415912","Nkol-Meb=
anga","","06-07-2025 04:19:00","06-07-2025 04:06:17","06-07-2025 04:37:21",=
"Cascaded Incident from TTO5591389","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause Gen failed to start due to grid bad voltage No Rcp// He bypassed gri=
d and started Gen manually","system","266299","06-07-2025 04:19:00","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005415910","Carrefou=
r Ayissi Ele","","06-07-2025 04:19:00","06-07-2025 04:06:17","06-07-2025 04=
:37:21","Cascaded Incident from TTO5591389","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site wen=
t down because Gen failed to start due to grid bad voltage No Rcp// He bypa=
ssed grid and started Gen manually","system","266299","06-07-2025 04:19:00"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005415893","S=
aa","IHS_YND_810, IHS_YND_809","06-07-2025 04:12:26","06-07-2025 04:06:17",=
"06-07-2025 04:37:21","Grid fluctuation, site went down because Gen failed =
to start due to grid bad voltage No Rcp// He bypassed grid and started Gen =
manually","Parker Tchoup","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","Grid fluctuation, site went down because Gen faile=
d to start due to grid bad voltage No Rcp// He bypassed grid and started Ge=
n manually","gerard.tchangoue@matech-cameroun.com","371","06-07-2025 04:12:=
26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005415854","Melen Ba=
'aba","","06-07-2025 03:55:40","06-07-2025 03:50:34","06-07-2025 05:33:00",=
"Cascaded Incident from TTO5591318","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site, Site on Grid =
UBAIE=3D53V ,  Stive ONANA (Orange Cameroun /699944736) is on site for work=
 ","system","267236","06-07-2025 03:55:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005415853","Nkolfoul=
ou 2","","06-07-2025 03:55:40","06-07-2025 03:50:34","06-07-2025 05:33:00",=
"Cascaded Incident from TTO5591318","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site, Site on Grid =
UBAIE=3D53V ,  Stive ONANA (Orange Cameroun /699944736) is on site for work=
 ","system","267236","06-07-2025 03:55:40","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005415843","N=
kolfoulou","IHS_YND_278, IHS_YND_308","06-07-2025 03:52:40","06-07-2025 03:=
50:34","06-07-2025 05:33:00","No power issue on site, Site on Grid UBAIE=3D=
53V ,  Stive ONANA (Orange Cameroun /699944736) is on site for work","Silig=
ap Boris","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue on site, Site on Grid UBAIE=3D53V ,  S=
tive ONANA (Orange Cameroun /699944736) is on site for work ","gerard.tchan=
goue@matech-cameroun.com","127","06-07-2025 03:52:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005415521","Nkongtoc=
k","","06-07-2025 01:44:12","06-07-2025 01:30:34","06-07-2025 01:33:03","Ca=
scaded Incident from TTO5590939","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V sit=
e on Grid; TX FME Flubert (654266068/Huawei) is informed","system","268419"=
,"06-07-2025 01:44:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005415520","Mambine"=
,"","06-07-2025 01:44:12","06-07-2025 01:30:34","06-07-2025 01:33:03","Casc=
aded Incident from TTO5590939","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubaie 54.5V site on G=
rid; TX FME Flubert (654266068/Huawei) is informed","system","268422","06-0=
7-2025 01:44:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0005415516","Mandoumb=
a OCM","","06-07-2025 01:44:11","06-07-2025 01:30:34","06-07-2025 01:33:03"=
,"Cascaded Incident from TTO5590939","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V=
 site on Grid; TX FME Flubert (654266068/Huawei) is informed","system","268=
420","06-07-2025 01:44:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0005415517","Mbankomo=
 IHS","","06-07-2025 01:44:11","06-07-2025 01:30:34","06-07-2025 01:33:03",=
"Cascaded Incident from TTO5590939","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V site=
 on Grid; TX FME Flubert (654266068/Huawei) is informed","system","268421",=
"06-07-2025 01:44:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005415518","Ebeba","=
","06-07-2025 01:44:11","06-07-2025 01:30:34","06-07-2025 01:33:03","Cascad=
ed Incident from TTO5590939","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site Ubaie 54.5V site on Gri=
d; TX FME Flubert (654266068/Huawei) is informed","system","268418","06-07-=
2025 01:44:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0005415519","OKOA Pea=
ge","","06-07-2025 01:44:11","06-07-2025 01:30:34","06-07-2025 01:33:03","C=
ascaded Incident from TTO5590939","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V site o=
n Grid; TX FME Flubert (654266068/Huawei) is informed","system","268420","0=
6-07-2025 01:44:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0005415515","Sous Pre=
fecture","","06-07-2025 01:44:10","06-07-2025 01:30:34","06-07-2025 01:33:0=
3","Cascaded Incident from TTO5590939","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V s=
ite on Grid; TX FME Flubert (654266068/Huawei) is informed","system","26841=
7","06-07-2025 01:44:10","MATECH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005415498","N=
omayos-IHS","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_33=
9, IHS_YND_330, IHS_YND_350, IHS_YND_349","06-07-2025 01:36:50","06-07-2025=
 01:30:34","06-07-2025 01:33:03","No power issue on site Ubaie 54.5V site o=
n Grid; TX FME Flubert (654266068/Huawei) is informed","Fanda Brice","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site Ubaie 54.5V site on Grid; TX FME Flubert (6542=
66068/Huawei) is informed","gerard.tchangoue@matech-cameroun.com","377","06=
-07-2025 01:36:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005415092","SOA VILL=
AGE","","05-07-2025 23:14:10","05-07-2025 23:12:59","05-07-2025 23:42:41","=
Cascaded Incident from TTO5590461","Siligap Boris","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active //  No power issue on site, sit=
e on Grid with Ubaie=3D54.3V The TX FME SYNPHORIEN /615295205 of Huawei is =
informed.","system","269489","05-07-2025 23:14:10","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005415091","SOA=
 TOWN","IHS_YND_323","05-07-2025 23:13:27","05-07-2025 23:12:59","05-07-202=
5 23:42:41","Active //  No power issue on site, site on Grid with Ubaie=3D5=
4.3V The TX FME SYNPHORIEN /615295205 of Huawei is informed.","Siligap Bori=
s","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active //  No power issue on site, site on Grid with Ubaie=
=3D54.3V The TX FME SYNPHORIEN /615295205 of Huawei is informed.","edwige.k=
apawo@matech-cameroun.com","29","05-07-2025 23:13:27","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005414996","N=
kolso","","05-07-2025 22:50:11","05-07-2025 22:42:51","06-07-2025 00:07:49"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage,RCP faulty// He bypassed the Grid and site on Gen","TIENTCHEU NZ=
ETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, Site went down because gen fails to start du=
e to grid bad voltage,RCP faulty// He bypassed the Grid and site on Gen","g=
erard.tchangoue@matech-cameroun.com","441","05-07-2025 22:50:11","MATECH CM=
R"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005414989","Lad=
a I Yde","","05-07-2025 22:48:06","05-07-2025 22:27:01","05-07-2025 23:31:2=
4","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","ludivine.ngamaleu@ihstowers.com","1267","05-07-2025 22:48:06","MATECH CM=
R"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005414515","Efo=
ulan MTN","","05-07-2025 21:25:13","05-07-2025 21:19:04","05-07-2025 22:31:=
15","Site went down due to insufficient rectifiers on site // Site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifiers on site // Site stabili=
sed","franck.nkomot@matech-cameroun.com","370","05-07-2025 21:25:13","MATEC=
H CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005414347","Efo=
ulan MTN","","05-07-2025 20:56:05","05-07-2025 20:51:59","05-07-2025 21:09:=
59","Site went down due to insufficient rectifiers on site // Site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifiers on site // Site stabili=
sed","franck.nkomot@matech-cameroun.com","247","05-07-2025 20:56:05","MATEC=
H CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005414251","Bit=
eng-Maetur","","05-07-2025 20:41:34","05-07-2025 20:36:22","05-07-2025 21:1=
4:22","Active//No power issue on site Ubaie =3D50.6V site on Grid The TX FM=
E Henri (699949693) from Huawei is informed","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site Ubaie =3D50.6V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","franck.nkomot@matech-cameroun.com",=
"314","05-07-2025 20:41:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005414238","Akak-Nko=
zoa-MTN-IHS","","05-07-2025 20:39:40","05-07-2025 20:25:12","05-07-2025 20:=
47:29","Cascaded Incident from TTO5589457","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","DG failed to start due to=
 bad voltage eneo // eneo disjonction, site on Gen","system","265190","05-0=
7-2025 20:39:40","MATECH CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0005414083","B=
ATA-Mokolo","","05-07-2025 20:10:47","05-07-2025 20:07:34","05-07-2025 20:0=
9:57","Grid fluctuation, No space to deploy MGE// Grid restoration","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid fluctu=
ation, No space to deploy MGE// Grid restoration","gaelle.njiofack@matech-c=
ameroun.com","195","05-07-2025 20:10:47","MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005414077","Mfa=
ndena","","05-07-2025 20:10:03","05-07-2025 20:05:54","05-07-2025 20:23:54"=
,"Grid outage, site went down due to insufficiency of rectifiers // Site st=
abilized","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Grid outage, site went down due to insufficiency of rectifiers=
 // Site stabilized","franck.nkomot@matech-cameroun.com","250","05-07-2025 =
20:10:03","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005413951","Efo=
ulan MTN","","05-07-2025 19:41:18","05-07-2025 19:34:08","05-07-2025 19:52:=
10","Site went down due to insufficient rectifiers on site // Site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifiers on site // Site stabili=
sed","franck.nkomot@matech-cameroun.com","431","05-07-2025 19:41:18","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005413947","A=
wae Ewonkan","","05-07-2025 19:40:03","05-07-2025 19:34:56","05-07-2025 20:=
35:26","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed//Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Grid return"=
,"gaelle.njiofack@matech-cameroun.com","309","05-07-2025 19:40:03","MATECH =
CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005413910","O=
lembe","","05-07-2025 19:34:21","05-07-2025 19:32:15","05-07-2025 19:46:47"=
,"Grid bad voltage , Site down because gen fails to start due to grid bad v=
oltage //  gen manually started","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Grid bad voltage , Site d=
own because gen fails to start due to grid bad voltage // gen manually star=
ted","gaelle.njiofack@matech-cameroun.com","128","05-07-2025 19:34:21","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005413790","Bastos-N=
ylon","","05-07-2025 19:14:31","05-07-2025 18:59:25","05-07-2025 19:16:43",=
"Cascaded Incident from TTO5588949","Mboua Thierry","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","TX issue No power issue CMS : Tbay=3D=
53.5 V ,   awaiting evidences","system","997","05-07-2025 19:14:31","MATECH=
 CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005413773","Fla=
menco","","05-07-2025 19:13:34","05-07-2025 19:05:25","05-07-2025 19:23:25"=
,"Grid outage, site went down because Gen failed to start due to poor backu=
p // Site stabilised","Mboua Thierry","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, site went down because =
Gen failed to start due to poor backup // Site stabilised","franck.nkomot@m=
atech-cameroun.com","490","05-07-2025 19:13:34","MATECH CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0005413766","G=
olf Quater","","05-07-2025 19:11:57","05-07-2025 18:59:25","05-07-2025 19:1=
6:43","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Cascad=
e Active","TX issue No power issue CMS : Tbay=3D53.5 V ,   awaiting evidenc=
es","gaelle.njiofack@matech-cameroun.com","1020","05-07-2025 19:11:57","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0005413763","B=
astos Bethesda","","05-07-2025 19:11:33","05-07-2025 18:59:25","05-07-2025 =
19:16:43","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Ca=
scade Active","TX issue No power issue CMS : Tbay=3D53.5 V ,   awaiting evi=
dences","gaelle.njiofack@matech-cameroun.com","1051","05-07-2025 19:11:33",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0005413760","N=
komkana 2","","05-07-2025 19:10:51","05-07-2025 18:59:25","05-07-2025 19:16=
:43","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Cascade=
 Active","TX issue No power issue CMS : Tbay=3D53.5 V ,   awaiting evidence=
s","gaelle.njiofack@matech-cameroun.com","1074","05-07-2025 19:10:51","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005413749","T=
singa","","05-07-2025 19:09:35","05-07-2025 18:59:25","05-07-2025 19:16:43"=
,"","Mboua Thierry","Cascade Outage","Active","Cascade Active","Cascade Act=
ive","TX issue No power issue CMS : Tbay=3D53.5 V ,   awaiting evidences","=
gaelle.njiofack@matech-cameroun.com","1106","05-07-2025 19:09:35","MATECH C=
MR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0005413742","N=
komkana","IHS_YND_220, IHS_YND_138, IHS_YND_126, IHS_YND_563, IHS_YND_127",=
"05-07-2025 19:08:34","05-07-2025 18:59:25","05-07-2025 20:16:43","TX issue=
 No power issue CMS : Tbay=3D53.5 V ,   awaiting evidences","","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
TX issue No power issue CMS : Tbay=3D53.5 V ,   awaiting evidences","gaelle=
.njiofack@matech-cameroun.com","551","05-07-2025 19:08:34","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005413737","NKO=
MKANA ELIZA HOTEL","","05-07-2025 19:07:23","05-07-2025 18:57:59","05-07-20=
25 19:19:15","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Grid return","","Equipment Repair","Passive","Rectifier","=
Rectifier Module Overloaded","Site went down due to PWC Overloaded and SS I=
HS Bernard Atangana confirmed // Grid return","franck.nkomot@matech-camerou=
n.com","565","05-07-2025 19:07:23","MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005413678","Mfa=
ndena","","05-07-2025 18:54:23","05-07-2025 18:44:59","05-07-2025 19:02:59"=
,"Grid outage, site went down due to insufficiency of rectifiers // Site st=
abilized","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Grid outage, site went down due to insufficiency of rectifiers=
 // Site stabilized","franck.nkomot@matech-cameroun.com","564","05-07-2025 =
18:54:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005413643","Mfou EPC=
","","05-07-2025 18:50:11","05-07-2025 18:47:20","05-07-2025 18:53:42","Cas=
caded Incident from TTO5588828","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Gen manually started","system","263952","05-07=
-2025 18:50:11","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005413636","M=
fou OCM","IHS_YND_674","05-07-2025 18:49:27","05-07-2025 18:47:20","05-07-2=
025 18:53:42","Grid Outage, Site Down before gen Started due to poor backup=
 // Gen manually started","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before=
 gen Started due to poor backup // Gen manually started","gaelle.njiofack@m=
atech-cameroun.com","128","05-07-2025 18:49:27","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005413624","S=
apeur Mimboman","","05-07-2025 18:48:00","05-07-2025 18:45:50","05-07-2025 =
19:31:29","No power issue on site Ubaie=3D54.3V and Ubaie2=3D51.8V site on =
Grid The TX FME Lionel adjep//655 18 48 76// from huawei is informed, await=
ing evidences from fme","Mba Lazare Herve","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on si=
te Ubaie=3D54.3V and Ubaie2=3D51.8V site on Grid The TX FME Lionel adjep//6=
55 18 48 76// from huawei is informed, awaiting evidences from fme","gaelle=
.njiofack@matech-cameroun.com","165","05-07-2025 18:48:00","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005413466","O=
lembe","","05-07-2025 18:20:32","05-07-2025 18:02:14","05-07-2025 18:15:22"=
,"Grid bad voltage , Site down because gen fails to start due to grid bad v=
oltage // Grid stabilisation","Fabrice Pouakam","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","Grid bad voltage , Site down=
 because gen fails to start due to grid bad voltage // Grid stabilisation",=
"gaelle.njiofack@matech-cameroun.com","1099","05-07-2025 18:20:32","MATECH =
CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005413178","A=
hala","","05-07-2025 17:28:40","05-07-2025 17:26:33","05-07-2025 18:50:26",=
"Grid outage, Site down because gen  battery  has been stolen // Gen starte=
d with external battery","Hyemafo Gildas","Site Asset Theft","Theft","Theft=
","Generator Battery Theft","Grid outage, Site down because gen  battery  h=
as been stolen // Gen started we external battery","gaelle.njiofack@matech-=
cameroun.com","128","05-07-2025 17:28:40","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0005413166","Sac=
re Coeur Catholic Church","","05-07-2025 17:24:25","05-07-2025 17:21:13","0=
5-07-2025 17:48:42","Grid outage, site went down due to insufficiency of re=
ctifiers // Site stabilized","Mboua Thierry","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Grid outage, site went down due to insuffici=
ency of rectifiers // Site stabilized","franck.nkomot@matech-cameroun.com",=
"192","05-07-2025 17:24:25","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005413151","A=
wae Ewonkan","","05-07-2025 17:20:23","05-07-2025 17:15:43","05-07-2025 17:=
20:54","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed//Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Grid return"=
,"gaelle.njiofack@matech-cameroun.com","436","05-07-2025 17:20:23","MATECH =
CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005413130","Nko=
mo stade","","05-07-2025 17:14:23","05-07-2025 17:08:12","05-07-2025 17:16:=
12","Grid outage, Site went down before Gen start due to poor backup/ // Gr=
id return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup/ // Grid return","franck.nkomot@matech-cameroun.com","3=
72","05-07-2025 17:14:23","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005413117","M=
fou OCM","","05-07-2025 17:11:22","05-07-2025 17:07:15","05-07-2025 17:14:5=
2","	Grid Outage, Site Down before gen Started due to poor backup // Grid s=
tabilised","Mba Lazare Herve","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","	Grid Outage, Site Down before gen Started d=
ue to poor backup // Grid stabilised","gaelle.njiofack@matech-cameroun.com"=
,"248","05-07-2025 17:11:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005413112","Nsam esc=
ale LP","","05-07-2025 17:09:28","05-07-2025 17:02:49","05-07-2025 17:08:49=
","Cascaded Incident from TTO5588233","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Grid return","system","263017","05-07-2025 17:09:28",=
"MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005413100","Nsa=
m Sofavinc","IHS_YND_732","05-07-2025 17:07:58","05-07-2025 17:02:49","05-0=
7-2025 17:08:49","Grid Outage, Site went down before Gen start due to poor =
backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before =
Gen start due to poor backup // Grid return","franck.nkomot@matech-cameroun=
.com","310","05-07-2025 17:07:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005412792","MEHANDAN=
","","05-07-2025 16:15:51","05-07-2025 16:11:07","05-07-2025 17:35:34","Cas=
caded Incident from TTO5587890","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Grid stabilized","system","=
1251373","05-07-2025 16:15:51","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005412785","O=
dza II OCM","IHS_YND_528","05-07-2025 16:15:17","05-07-2025 16:11:07","05-0=
7-2025 17:36:44","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Grid =
stabilized","gaelle.njiofack@matech-cameroun.com","253","05-07-2025 16:15:1=
7","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005412779","Mfou EPC=
","","05-07-2025 16:14:01","05-07-2025 16:07:53","05-07-2025 16:16:59","Cas=
caded Incident from TTO5587876","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Grid stabilised","system","266264","05-07-2025=
 16:14:01","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005412774","M=
fou OCM","IHS_YND_674","05-07-2025 16:13:04","05-07-2025 16:07:53","05-07-2=
025 16:16:59","Grid Outage, Site Down before gen Started due to poor backup=
 // Grid stabilised","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen =
Started due to poor backup // Grid stabilised","gaelle.njiofack@matech-came=
roun.com","312","05-07-2025 16:13:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005412588","C-Suprem=
e","","05-07-2025 15:38:01","05-07-2025 15:34:15","05-07-2025 17:04:42","Ca=
scaded Incident from TTO5587644","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive"," Grid outage ,site down due to  Power Cabinet  ove=
rload, (200A ,12k) // Site stabilisation","system","282570","05-07-2025 15:=
38:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005412587","Acropole=
","","05-07-2025 15:38:00","05-07-2025 15:34:15","05-07-2025 17:04:42","Cas=
caded Incident from TTO5587644","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive"," Grid outage ,site down due to  Power =
Cabinet  overload, (200A ,12k) // Site stabilisation","system","282570","05=
-07-2025 15:38:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005412586","Olezoa O=
CM","","05-07-2025 15:38:00","05-07-2025 15:34:15","05-07-2025 17:04:42","C=
ascaded Incident from TTO5587644","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive"," Grid outage ,site down due to  Power Cabinet  ov=
erload, (200A ,12k) // Site stabilisation","system","282571","05-07-2025 15=
:38:00","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005412576","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","05-07-2025 15:35:21",=
"05-07-2025 15:34:15","05-07-2025 17:04:42"," Grid outage ,site down due to=
  Power Cabinet  overload, (200A ,12k) // Site stabilisation","MINKA NICOLA=
S","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
 Grid outage ,site down due to  Power Cabinet  overload, (200A ,12k) // Sit=
e stabilisation","gaelle.njiofack@matech-cameroun.com","68","05-07-2025 15:=
35:21","MATECH CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0005412562","B=
ATA-Mokolo","","05-07-2025 15:33:35","05-07-2025 15:30:21","05-07-2025 19:1=
9:50","(Unstable),Grid Only, No space to deploy MGE // Grid restoration",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","(Unsta=
ble),Grid Only, No space to deploy MGE // Grid restoration","gaelle.njiofac=
k@matech-cameroun.com","196","05-07-2025 15:33:35","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005412441","N=
koabang2","","05-07-2025 15:18:42","05-07-2025 15:17:35","05-07-2025 15:19:=
06","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed// Grid returned","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to g=
en overload (22KVA, 330A), SS Blaise IHS is informed// Grid returned","gael=
le.njiofack@matech-cameroun.com","69","05-07-2025 15:18:42","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005412004","Nko=
mo stade","","05-07-2025 13:51:31","05-07-2025 13:45:25","05-07-2025 14:03:=
49","Grid outage, Site went down before Gen start due to poor backup/ // Gr=
id return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup/ // Grid return","loic.noumsi@matech-cameroun.com","367=
","05-07-2025 13:51:31","MATECH CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0005411981","N=
kenglikok","","05-07-2025 13:45:51","05-07-2025 13:42:36","06-07-2025 01:33=
:03","No power issue on site U=3D49v site on battery The fme Tx Etienne 695=
033981 of huawei is informed","Kemeni Franklin","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site U=3D49v site on battery The fme Tx Etienne 695033981 of huawei is i=
nformed","loic.noumsi@matech-cameroun.com","196","05-07-2025 13:45:51","MAT=
ECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005411847","Nko=
mo stade","","05-07-2025 13:22:46","05-07-2025 13:18:37","05-07-2025 13:24:=
36","Grid outage, Site went down before Gen start due to poor backup/ // Gr=
id return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup/ // Grid return","loic.noumsi@matech-cameroun.com","250=
","05-07-2025 13:22:46","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005411688","M=
vog Mbi New","","05-07-2025 12:43:17","05-07-2025 12:39:10","05-07-2025 12:=
43:54","Grid outage, Site went down before Gen start due to poor backup // =
Grid return","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup // Grid return","loic.noumsi@matech-cameroun.com","248",=
"05-07-2025 12:43:17","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005411684","S=
imbock OCM","","05-07-2025 12:42:40","05-07-2025 12:33:59","05-07-2025 12:5=
0:18","Site impacted by Nkolzie CTR_672 not manage by IHS","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","Affected=
 by 3rd Party Site","	Site impacted by Nkolzie CTR_672 not manage by IHS","=
gaelle.njiofack@matech-cameroun.com","523","05-07-2025 12:42:40","MATECH CM=
R"
"Closed Complete","Warning","T0105","IHS_YND_321","NOCINC0005411656","Soa",=
"","05-07-2025 12:38:49","","","Grid outage, site went in alarm site on bat=
tery bevause Gen failed to start due to alarm Emergency Stop // He reset DG=
 card, site on GEN","Siligap Boris","Warning","Warning","POWER","Warning - =
ACDG - Emergency Stop","Grid outage, site went in alarm site on battery bev=
ause Gen failed to start due to alarm Emergency Stop // He reset DG card, s=
ite on GEN","loic.noumsi@matech-cameroun.com","2","05-07-2025 12:38:49","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0005411594","B=
ATA-Mokolo","","05-07-2025 12:28:50","05-07-2025 12:24:42","05-07-2025 14:4=
4:48","	Grid Only, No space to deploy MGE // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","	Grid Only, No space =
to deploy MGE // Grid return","gaelle.njiofack@matech-cameroun.com","250","=
05-07-2025 12:28:50","MATECH CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0005411551","E=
ntree Cite Verte","","05-07-2025 12:23:19","05-07-2025 12:07:11","05-07-202=
5 14:03:59","Grid outage,site down due to disjonction in the OCM BTS // CB =
rearmed ","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Circu=
it Breaker Tripped","Grid outage,site down due to disjonction in the OCM BT=
S // CB rearmed ","loic.noumsi@matech-cameroun.com","970","05-07-2025 12:23=
:19","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0005411375","H=
-Progres","","05-07-2025 11:53:20","05-07-2025 11:50:12","05-07-2025 12:12:=
38","Grid Only, No space to deploy MGE // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to d=
eploy MGE // Grid return","gaelle.njiofack@matech-cameroun.com","189","05-0=
7-2025 11:53:20","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005411362","M=
vog Mbi New","","05-07-2025 11:49:52","05-07-2025 11:47:37","05-07-2025 11:=
52:08","Grid outage, Site went down before Gen start due to poor backup // =
Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen start automatically","gaelle.njiofack=
@matech-cameroun.com","136","05-07-2025 11:49:52","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005411358","C=
-Supreme","","05-07-2025 11:48:57","05-07-2025 11:46:47","05-07-2025 11:51:=
53","Active // No power issue, site on Grid with Ubaie=3D54.5V, Brice Tsagu=
e (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power is=
sue, site on Grid with Ubaie=3D54.5V, Brice Tsague (650 21 40 96 / Huawei) =
is informed","loic.noumsi@matech-cameroun.com","132","05-07-2025 11:48:57",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0005411131","B=
ATA Mokolo OCM","","05-07-2025 11:07:47","05-07-2025 10:36:40","05-07-2025 =
14:50:11","Grid Only, No space to deploy MDGE // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No spa=
ce to deploy MDGE // Grid return","gaelle.njiofack@matech-cameroun.com","18=
68","05-07-2025 11:07:47","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005411041","A=
wae Ewonkan","","05-07-2025 11:02:03","05-07-2025 10:53:42","05-07-2025 10:=
55:42","No power issue on site Tx issue U=3D54.1V site on Grid , the fme tx=
 Leonel Steve//655184876 from Huawei is informed","Albran Byorel","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site Tx issue U=3D54.1V site on Grid , the fme tx Leon=
el Steve//655184876 from Huawei is informed","gaelle.njiofack@matech-camero=
un.com","503","05-07-2025 11:02:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005410924","Mfou EPC=
","","05-07-2025 10:44:40","05-07-2025 10:34:40","05-07-2025 10:59:15","Cas=
caded Incident from TTO5585794","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Fluctuation, Site Down before =
gen Started due to poor backup // Grid baypass and site on GEN","system","2=
64732","05-07-2025 10:44:41","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005410909","M=
fou OCM","IHS_YND_674","05-07-2025 10:43:49","05-07-2025 10:34:40","05-07-2=
025 10:59:15","Grid Fluctuation, Site Down before gen Started due to poor b=
ackup // Grid baypass and site on GEN","Mba Lazare Herve","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuation=
, Site Down before gen Started due to poor backup // Grid baypass and site =
on GEN","gaelle.njiofack@matech-cameroun.com","550","05-07-2025 10:43:49","=
MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005410674","A=
wae Escalier","","05-07-2025 10:02:55","05-07-2025 09:59:35","05-07-2025 10=
:30:27","Grid outage, Site went down due to Absence of an Eneo phase //  he=
 made a bridge between the two remaining phases","Albran Byorel","Grid Supp=
ly","Passive","Grid","National Grid - Grid Incomplete Phase","Grid outage, =
Site went down due to Absence of an Eneo phase //  he made a bridge between=
 the two remaining phases","gaelle.njiofack@matech-cameroun.com","202","05-=
07-2025 10:02:55","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005410632","N=
koabang Ebolmedjock","","05-07-2025 09:52:34","05-07-2025 09:48:28","05-07-=
2025 11:31:25","Grid outage, Gen stopped due to Water infiltration in the t=
ank // Tank purged and Gen started manually","Mba Lazare Herve","Fuel Outag=
e (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","=
Grid outage, Gen stopped due to Water infiltration in the tank // Tank purg=
ed and Gen started manually","loic.noumsi@matech-cameroun.com","248","05-07=
-2025 09:52:34","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005409981","N=
koabang Ebolmedjock","","05-07-2025 08:04:24","05-07-2025 08:02:18","05-07-=
2025 08:55:07","Grid outage, site went down because Gen started and stopped=
 due to High temp alarm // He added water and started Gen manually","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Tem=
p - Coolant Level Issue","Grid outage, site went down because Gen started a=
nd stopped due to High temp alarm // He added water and started Gen manuall=
y","loic.noumsi@matech-cameroun.com","127","05-07-2025 08:04:24","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0005409521","Mendong =
vallee","","05-07-2025 06:52:18","05-07-2025 06:47:12","05-07-2025 06:49:05=
","Cascaded Incident from TTO5584260","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down b=
ecause Gen failed to start due to Grid bad voltage // Grid stabilized","sys=
tem","271082","05-07-2025 06:52:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0005409522","Mendong =
Maeture","","05-07-2025 06:52:18","05-07-2025 06:47:12","05-07-2025 06:49:0=
5","Cascaded Incident from TTO5584260","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation, Site went do=
wn because Gen failed to start due to Grid bad voltage // Grid stabilized",=
"system","271084","05-07-2025 06:52:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005409523","Montee-J=
ouvence","","05-07-2025 06:52:18","05-07-2025 06:47:12","05-07-2025 06:49:0=
5","Cascaded Incident from TTO5584260","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation, Site went do=
wn because Gen failed to start due to Grid bad voltage // Grid stabilized",=
"system","271083","05-07-2025 06:52:18","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005409494","M=
endong","IHS_YND_692, IHS_YND_569, IHS_YND_236","05-07-2025 06:48:21","05-0=
7-2025 06:47:12","05-07-2025 06:49:05","Grid fluctuation, Site went down be=
cause Gen failed to start due to Grid bad voltage // Grid stabilized","Hyem=
afo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation, Site went down because Gen failed to start due=
 to Grid bad voltage // Grid stabilized","gaelle.njiofack@matech-cameroun.c=
om","70","05-07-2025 06:48:21","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005409323","A=
kak-Nkozoa-MTN-IHS","","05-07-2025 05:35:16","05-07-2025 04:14:35","05-07-2=
025 05:20:04","Site impacted by AKAK IHS (ctr_513) //No power issue on site=
 Ubaie: 53V site on Grd. Sephorien (691316854/Huawei) is informed.","Fabric=
e Pouakam","Cascade Outage","Active","Cascade Active","Cascade Active","Sit=
e impacted by AKAK IHS (ctr_513) //No power issue on site Ubaie: 53V site o=
n Grd. Sephorien (691316854/Huawei) is informed.","gerard.tchangoue@matech-=
cameroun.com","265838","05-07-2025 05:35:16","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005408498","N=
kolbong","","04-07-2025 23:10:44","04-07-2025 23:09:35","04-07-2025 23:22:4=
0","Active/ No power issue on site Ubaie; 53.5V site on Grid, The FME TX Ju=
lien (+237 6 93 09 58 49) from Huawei is inform, Site went down due to disj=
unction of Cb in the OCM BTS/ CB rearmament with the a","Delor Telezing","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active/ No power issue on site Ubaie; 53.5V site on Grid, The FME=
 TX Julien (+237 6 93 09 58 49) from Huawei is inform, Site went down due t=
o disjunction of Cb in the OCM BTS/ CB rearmament with the agreement of FME=
 TX","gerard.tchangoue@matech-cameroun.com","71","04-07-2025 23:10:44","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005408422","A=
wae Ewonkan","","04-07-2025 22:50:17","04-07-2025 22:48:12","04-07-2025 22:=
55:12","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed//Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Grid return"=
,"gerard.tchangoue@matech-cameroun.com","128","04-07-2025 22:50:17","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005408340","OLAMA","=
","04-07-2025 22:26:14","04-07-2025 21:44:06","04-07-2025 22:05:13","No pow=
er issue on site Ubaie =3D54.5V site on Gen The TX FME Henri (699949693) fr=
om Huawei is informed.","Fanda Brice","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ub=
aie =3D54.5V site on Gen The TX FME Henri (699949693) from Huawei is inform=
ed.","gerard.tchangoue@matech-cameroun.com","2530","04-07-2025 22:26:14","M=
ATECH CMR"
"Closed Complete","Warning","","IHS_YND_312","NOCINC0005408032","Nkolnda","=
","04-07-2025 21:35:28","","","Site alarming because site on battery due to=
 Grid outage and poor battery backup //Gen started automatically","Albran B=
yorel","Warning","Warning","POWER","Warning - Site on Battery","Site alarmi=
ng because site on battery due to Grid outage and poor battery backup //Gen=
 started automatically","franck.nkomot@matech-cameroun.com","1034","04-07-2=
025 21:35:28","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005407934","N=
koabang2","","04-07-2025 21:24:49","04-07-2025 21:21:43","04-07-2025 21:36:=
01","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed// Grid returned","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to g=
en overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ger=
ard.tchangoue@matech-cameroun.com","188","04-07-2025 21:24:49","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005407876","ELO=
UMDEM CARRIERE 2","","04-07-2025 21:15:53","04-07-2025 21:10:46","04-07-202=
5 21:29:46","Site went down due to insufficiency of rectifiers on site (Nee=
d to add one rectifier on site) // He put site on Gen","Fanda Brice","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down due t=
o insufficiency of rectifiers on site (Need to add one rectifier on site) /=
/ He put site on Gen","franck.nkomot@matech-cameroun.com","309","04-07-2025=
 21:15:53","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005407848","B=
arriere","","04-07-2025 21:10:53","04-07-2025 21:08:23","04-07-2025 21:16:1=
5","Site unstable : No power issue on site Ubay: 53.3V site on Gen TX Fme S=
AMBA (654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Site uns=
table : No power issue on site Ubay: 53.3V site on Gen TX Fme SAMBA (654266=
058/Huawei) is informed.","gerard.tchangoue@matech-cameroun.com","196","04-=
07-2025 21:10:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005407798","MEHANDAN=
","","04-07-2025 21:01:00","04-07-2025 20:54:40","04-07-2025 20:58:35","Cas=
caded Incident from TTO5582326","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Grid stabilized","system","=
263450","04-07-2025 21:01:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005407762","Mfou EPC=
","","04-07-2025 20:56:20","04-07-2025 20:52:43","04-07-2025 21:04:22","Cas=
caded Incident from TTO5582315","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Grid returned","system","263566","04-07-2025 2=
0:56:20","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005407760","O=
dza II OCM","IHS_YND_528","04-07-2025 20:55:46","04-07-2025 20:54:40","04-0=
7-2025 21:04:45","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Grid =
stabilized","gaelle.njiofack@matech-cameroun.com","69","04-07-2025 20:55:46=
","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005407751","M=
fou OCM","IHS_YND_674","04-07-2025 20:54:53","04-07-2025 20:52:43","04-07-2=
025 21:04:22","Grid Outage, Site Down before gen Started due to poor backup=
 // Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen St=
arted due to poor backup // Grid returned","gaelle.njiofack@matech-cameroun=
.com","131","04-07-2025 20:54:53","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005407735","A=
wae Ewonkan","","04-07-2025 20:51:17","04-07-2025 20:05:03","04-07-2025 22:=
38:43","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed//Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Grid return"=
,"gaelle.njiofack@matech-cameroun.com","2902","04-07-2025 20:51:17","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005407579","C-Suprem=
e","","04-07-2025 20:29:11","04-07-2025 20:19:04","04-07-2025 20:22:35","Ca=
scaded Incident from TTO5582105","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, Site went down before Gen start due t=
o poor backup // Grid return","system","265570","04-07-2025 20:29:11","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005407577","Acropole=
","","04-07-2025 20:29:11","04-07-2025 20:19:04","04-07-2025 20:22:35","Cas=
caded Incident from TTO5582105","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down before Gen=
 start due to poor backup // Grid return","system","265571","04-07-2025 20:=
29:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005407578","C-Suprem=
e","","04-07-2025 20:29:11","04-07-2025 20:19:04","04-07-2025 20:22:35","Ca=
scaded Incident from TTO5582105","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, Site went down before Gen start due t=
o poor backup // Grid return","system","265569","04-07-2025 20:29:11","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0005407575","Olezoa O=
CM","","04-07-2025 20:29:10","04-07-2025 20:19:04","04-07-2025 20:22:35","C=
ascaded Incident from TTO5582105","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, Site went down before Gen start due =
to poor backup // Grid return","system","265571","04-07-2025 20:29:10","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005407576","Acropole=
","","04-07-2025 20:29:10","04-07-2025 20:19:04","04-07-2025 20:22:35","Cas=
caded Incident from TTO5582105","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down before Gen=
 start due to poor backup // Grid return","system","265569","04-07-2025 20:=
29:10","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005407560","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","04-07-2025 20:25:11",=
"04-07-2025 20:19:04","04-07-2025 20:22:35","Grid outage, Site went down be=
fore Gen start due to poor backup // Grid return","MINKA NICOLAS","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, Site went down before Gen start due to poor backup // Grid return","ga=
elle.njiofack@matech-cameroun.com","368","04-07-2025 20:25:11","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005407458","N=
kolbong","","04-07-2025 20:06:09","04-07-2025 20:00:24","04-07-2025 22:04:1=
5","Site went down due to disjunction of Cb(80A) in PWC // He reamed Cb(80A=
), site on grid","Delor Telezing","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","Site went down due to disjunct=
ion of Cb(80A) in PWC // He reamed Cb(80A), site on grid","gaelle.njiofack@=
matech-cameroun.com","346","04-07-2025 20:06:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005407173","SOA VILL=
AGE","","04-07-2025 19:20:10","04-07-2025 19:12:51","04-07-2025 20:12:18","=
Cascaded Incident from TTO5581641","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 Gen failed to start due to charger Gen battery faulty // He started Gen wi=
th an external battery","system","269504","04-07-2025 19:20:10","MATECH CMR=
"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005407142","S=
OA TOWN","IHS_YND_323","04-07-2025 19:16:24","04-07-2025 19:12:51","04-07-2=
025 20:12:18","Grid outage, site went down because Gen failed to start due =
to charger Gen battery faulty // He started Gen with an external battery","=
Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Ba=
ttery","Grid outage, site went down because Gen failed to start due to char=
ger Gen battery faulty // He started Gen with an external battery","gaelle.=
njiofack@matech-cameroun.com","215","04-07-2025 19:16:24","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005407054","A=
wae Ewonkan","","04-07-2025 19:01:29","04-07-2025 18:59:07","04-07-2025 19:=
32:37","No power issue on site Tx issue U=3D54.2V site on Grid , the fme tx=
 Leonel Steve//655184876 from Huawei is informed","Albran Byorel","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site Tx issue U=3D54.2V site on Grid , the fme tx Leon=
el Steve//655184876 from Huawei is informed","gaelle.njiofack@matech-camero=
un.com","144","04-07-2025 19:01:29","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005406982","O=
LAMA","","04-07-2025 18:48:24","04-07-2025 18:43:10","04-07-2025 18:57:22",=
"No power issue on site Ubaie =3D54.5V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.5V site on Gen The TX FME Henri (699949693) from Huawei is=
 informed.","gaelle.njiofack@matech-cameroun.com","316","04-07-2025 18:48:2=
4","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005406938","A=
ccacia New","","04-07-2025 18:38:55","04-07-2025 18:34:34","04-07-2025 18:4=
9:26","","","Cascade Outage","Active","Cascade Active","Cascade Active","Si=
te impacted by Nkolzie CTR_672 not manage by IHS","gaelle.njiofack@matech-c=
ameroun.com","264706","04-07-2025 18:38:55","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005406934","M=
ontee-Jouvence-II","","04-07-2025 18:38:10","04-07-2025 18:34:34","04-07-20=
25 18:49:26","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active"=
,"Cascade Active","Site impacted by Nkolzie CTR_672 not manage by IHS","gae=
lle.njiofack@matech-cameroun.com","264706","04-07-2025 18:38:10","MATECH CM=
R"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005406931","D=
amas","IHS_YND_562, IHS_YND_518","04-07-2025 18:37:42","04-07-2025 18:34:34=
","04-07-2025 18:49:26","Site impacted by Nkolzie CTR_672 not manage by IHS=
","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment F=
ailure","Affected by 3rd Party Site","Site impacted by Nkolzie CTR_672 not =
manage by IHS","gaelle.njiofack@matech-cameroun.com","189","04-07-2025 18:3=
7:42","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005406890","Eki=
e sud","","04-07-2025 18:31:03","04-07-2025 18:23:44","04-07-2025 19:01:44"=
,"No power issue on site//U=3D48.53V site on gen. Lionel/655 18 48 76/HUAWE=
I is informed.","Albran Byorel","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site//U=3D48.=
53V site on gen. Lionel/655 18 48 76/HUAWEI is informed.","ludivine.ngamale=
u@ihstowers.com","440","04-07-2025 18:31:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005406704","Akak-Nko=
zoa-MTN-IHS","","04-07-2025 17:52:21","04-07-2025 17:45:38","04-07-2025 17:=
47:38","Cascaded Incident from TTO5581119","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
, CMS no comm. (Site impacted by CTR_714  Soa vallee) Raoul (691144462/Huaw=
ei) is informed.","system","267602","04-07-2025 17:52:21","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005406402","S=
imbock OCM","","04-07-2025 16:53:04","04-07-2025 16:45:57","04-07-2025 16:5=
7:05","Site impacted by Nkolzie CTR_672 not manage by IHS","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","Affected=
 by 3rd Party Site","Site impacted by Nkolzie CTR_672 not manage by IHS","g=
aelle.njiofack@matech-cameroun.com","428","04-07-2025 16:53:04","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005406173","Mfou EPC=
","","04-07-2025 16:23:40","04-07-2025 16:16:18","04-07-2025 16:22:45","Cas=
caded Incident from TTO5580521","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Grid stabilised","system","265791","04-07-2025=
 16:23:40","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005406157","M=
fou OCM","IHS_YND_674","04-07-2025 16:20:26","04-07-2025 16:16:18","04-07-2=
025 16:22:45","Grid Outage, Site Down before gen Started due to poor backup=
 // Grid stabilised","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen =
Started due to poor backup // Grid stabilised","gaelle.njiofack@matech-came=
roun.com","249","04-07-2025 16:20:26","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005405853","B=
arriere","","04-07-2025 15:47:41","04-07-2025 15:41:33","04-07-2025 17:03:3=
9","Grid outage, site down due to work ( Generator drain ) // End of work",=
"Hyemafo Gildas","Installation Activity","Passive","Planned Activity","Inst=
allation Activity","Grid outage, site down due to work ( Generator drain ) =
// End of work","gaelle.njiofack@matech-cameroun.com","370","04-07-2025 15:=
47:41","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005405736","Evo=
doula MTN","","04-07-2025 15:25:04","04-07-2025 15:21:58","04-07-2025 15:23=
:58","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","fran=
ck.nkomot@matech-cameroun.com","187","04-07-2025 15:25:04","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005405599","Evo=
doula MTN","","04-07-2025 15:08:03","04-07-2025 15:02:53","04-07-2025 15:14=
:53","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","fran=
ck.nkomot@matech-cameroun.com","311","04-07-2025 15:08:03","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005405448","OTE=
LE MTN","","04-07-2025 14:45:23","04-07-2025 14:38:08","04-07-2025 14:54:08=
","Grid outage site went down because Gen failed to start due to Gen card f=
aulty // Gen Manually Started","Fanda Brice","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen fa=
iled to start due to Gen card faulty // Gen Manually Started","franck.nkomo=
t@matech-cameroun.com","437","04-07-2025 14:45:23","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005405063","A=
fanoya","","04-07-2025 13:42:00","04-07-2025 13:27:47","04-07-2025 16:07:43=
","No power issue on site , Ubaie=3D54.3V site On Grid The FME TX Samba /65=
5145055/ from Huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site , Ubaie=3D54.3V site On Grid The FME TX Samba /655145055/ from H=
uawei is informed","gaelle.njiofack@matech-cameroun.com","855","04-07-2025 =
13:42:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005404503","Ahala","=
","04-07-2025 11:57:34","04-07-2025 09:40:58","04-07-2025 11:36:56","Cascad=
ed Incident from TTO5577698","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","	Grid outage, Site went down due to Gen =
overload (15KVA, 350A) // Grid return","system","267936","04-07-2025 11:57:=
34","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005404470","B=
arriere","","04-07-2025 11:53:11","04-07-2025 11:49:58","04-07-2025 13:38:3=
4","Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS F=
elix ZAMBE confirmed // Grid return","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because G=
en overload (30kva, 410A) SS IHS Felix ZAMBE confirmed // Grid return","gae=
lle.njiofack@matech-cameroun.com","195","04-07-2025 11:53:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005404347","Mfou EPC=
","","04-07-2025 11:35:23","04-07-2025 11:25:28","04-07-2025 11:32:04","Cas=
caded Incident from TTO5578510","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup // Grid stabilised","system","268808","04-07-2025=
 11:35:23","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005404337","Nsi=
meyong","","04-07-2025 11:33:35","04-07-2025 11:30:28","04-07-2025 11:33:55=
","Grid outage, site went down due to PM (SWAP of PWC) done by Styve (69814=
0002/Picardi) // End of work","MINKA NICOLAS","Installation Activity","Pass=
ive","Planned Activity","Installation Activity","Grid outage, site went dow=
n due to PM (SWAP of PWC) done by Styve (698140002/Picardi) // End of work"=
,"loic.noumsi@matech-cameroun.com","187","04-07-2025 11:33:35","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005404326","A=
fanoya","","04-07-2025 11:30:28","04-07-2025 11:28:17","04-07-2025 12:27:00=
","Our FME Gildas is on site for work (Swap of Gen card and installation of=
 battery charger) // End of work","Hyemafo Gildas","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Our FME Gildas is on =
site for work (Swap of Gen card and installation of battery charger) // End=
 of work","gaelle.njiofack@matech-cameroun.com","133","04-07-2025 11:30:28"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005404322","M=
fou OCM","IHS_YND_674","04-07-2025 11:29:41","04-07-2025 11:25:28","04-07-2=
025 11:32:04","Grid Outage, Site Down before gen Started due to poor backup=
 // Grid stabilised","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen =
Started due to poor backup // Grid stabilised","gaelle.njiofack@matech-came=
roun.com","254","04-07-2025 11:29:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005404315","Nkolfon =
Cimencam","","04-07-2025 11:27:43","04-07-2025 09:40:58","04-07-2025 11:36:=
56","Cascaded Incident from TTO5577698","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","	Grid outage, Site went down =
due to Gen overload (15KVA, 350A) // Grid return","system","267938","04-07-=
2025 11:27:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_282","NOCINC0005404314","Meyo",""=
,"04-07-2025 11:27:42","04-07-2025 09:40:58","04-07-2025 11:36:56","Cascade=
d Incident from TTO5577698","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","	Grid outage, Site went down due to Gen o=
verload (15KVA, 350A) // Grid return","system","267937","04-07-2025 11:27:4=
2","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005404304","MEHANDAN=
","","04-07-2025 11:26:01","04-07-2025 11:21:33","04-07-2025 11:30:19","Cas=
caded Incident from TTO5578482","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Grid stabilized","system","=
269042","04-07-2025 11:26:01","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005404299","O=
dza II OCM","IHS_YND_528","04-07-2025 11:25:01","04-07-2025 11:21:33","04-0=
7-2025 11:30:19","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Grid =
stabilized","loic.noumsi@matech-cameroun.com","212","04-07-2025 11:25:01","=
MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005404263","A=
wae Ewonkan","","04-07-2025 11:18:12","04-07-2025 11:17:04","04-07-2025 11:=
18:55","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed//Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Grid return"=
,"gaelle.njiofack@matech-cameroun.com","70","04-07-2025 11:18:12","MATECH C=
MR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0005403972","H=
-Progres","","04-07-2025 10:38:19","04-07-2025 10:32:13","04-07-2025 14:57:=
13","Grid Only, No space to deploy MGE //Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to de=
ploy MGE //Grid return","gaelle.njiofack@matech-cameroun.com","368","04-07-=
2025 10:38:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005403965","Mfou EPC=
","","04-07-2025 10:37:31","04-07-2025 10:25:29","04-07-2025 10:43:43","Cas=
caded Incident from TTO5577967","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","	Grid Outage, Site Down before gen =
Started due to poor backup // Grid return","system","265304","04-07-2025 10=
:37:31","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005403838","M=
fou OCM","IHS_YND_674","04-07-2025 10:29:35","04-07-2025 10:25:29","04-07-2=
025 10:43:43","	Grid Outage, Site Down before gen Started due to poor backu=
p // Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","	Grid Outage, Site Down before gen St=
arted due to poor backup // Grid return","gaelle.njiofack@matech-cameroun.c=
om","247","04-07-2025 10:29:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_508","NOCINC0005403837","Crf-Nsam=
","","04-07-2025 10:29:19","04-07-2025 09:40:58","04-07-2025 11:36:56","Cas=
caded Incident from TTO5577698","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, Site went down due to Ge=
n overload (15KVA, 350A) // Grid return","system","267935","04-07-2025 10:2=
9:19","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005403786","Nko=
lbisson IITA LP","","04-07-2025 10:22:31","04-07-2025 10:20:25","04-07-2025=
 10:22:14","No power issue site on grid with U=3D53.8v Mohamadou(69114435) =
from Huawei is informed. Noticed that it is impacted by Nkolbisson 2 ocm no=
t managed by IHS","","Customer Equipment Failure","Active","Active Equipmen=
t Failure","Affected by 3rd Party Site","No power issue site on grid with U=
=3D53.8v Mohamadou(69114435) from Huawei is informed. Noticed that it is im=
pacted by Nkolbisson 2 ocm not managed by IHS","loic.noumsi@matech-cameroun=
.com","128","04-07-2025 10:22:31","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005403595","A=
hala","IHS_YND_257, IHS_YND_282, IHS_YND_762, IHS_YND_508","04-07-2025 09:4=
9:58","04-07-2025 09:40:58","04-07-2025 11:36:56","	Grid outage, Site went =
down due to Gen overload (15KVA, 350A) // Grid return","MINKA NICOLAS","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","	Grid outage, Site w=
ent down due to Gen overload (15KVA, 350A) // Grid return","gaelle.njiofack=
@matech-cameroun.com","541","04-07-2025 09:49:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0005403580","Bastos-B=
AT","","04-07-2025 09:46:53","04-07-2025 09:41:45","04-07-2025 10:14:47","C=
ascaded Incident from TTO5577611","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Access issue due to landlord, Site w=
ent down due to Grid outage // Grid returned","system","267885","04-07-2025=
 09:46:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0005403579","Dragage"=
,"","04-07-2025 09:46:53","04-07-2025 09:41:45","04-07-2025 10:14:47","Casc=
aded Incident from TTO5577611","Mboua Thierry","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Access issue due to landlord, Site went=
 down due to Grid outage // Grid returned","system","267884","04-07-2025 09=
:46:53","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005403518","ARM=
P Building","IHS_YND_192, IHS_YND_129","04-07-2025 09:42:54","04-07-2025 09=
:41:45","04-07-2025 10:14:47","Access issue due to landlord, Site went down=
 due to Grid outage // Grid returned","Mboua Thierry","Access Denial","Leas=
e Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access is=
sue due to landlord, Site went down due to Grid outage // Grid returned","l=
oic.noumsi@matech-cameroun.com","70","04-07-2025 09:42:54","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005403493","MBA=
LNGONG LYCEE","","04-07-2025 09:38:11","04-07-2025 09:37:06","04-07-2025 10=
:53:07","Grid outage,Site went down because Gen stopped due to overload(9kv=
a, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda =
Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge,Site went down because Gen stopped due to overload(9kva, 130A) SS IHS Fe=
lix Zambe is informed and confirmed//Grid return","loic.noumsi@matech-camer=
oun.com","67","04-07-2025 09:38:11","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005403343","N=
koabang2","","04-07-2025 09:18:50","04-07-2025 09:15:40","04-07-2025 09:32:=
36","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ga=
elle.njiofack@matech-cameroun.com","192","04-07-2025 09:18:50","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005402972","N=
kolfon Cimencam","","04-07-2025 08:15:25","04-07-2025 07:50:16","04-07-2025=
 09:15:06","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, Site went down due to Gen overload (15KVA,=
 350A) //Site stabilized	","gaelle.njiofack@matech-cameroun.com","267392","=
04-07-2025 08:15:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005402948","Ahala","=
","04-07-2025 08:08:31","04-07-2025 07:50:16","04-07-2025 09:15:06","Cascad=
ed Incident from TTO5576920","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Cascaded Incident from TTO5576920","syst=
em","267388","04-07-2025 08:08:31","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005402925","Eki=
e sud","","04-07-2025 08:02:06","04-07-2025 07:05:53","04-07-2025 08:59:29"=
,"Grid outage, site went down because Gen started and stopped due to alarm =
""oil pressure""( unprouven Alarm ) // He reset DG card and started Gen man=
ually","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid outage, site went down because Gen started and stopped due=
 to alarm ""oil pressure""( unprouven Alarm ) // He reset DG card and start=
ed Gen manually","gaelle.njiofack@matech-cameroun.com","3375","04-07-2025 0=
8:02:06","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005402915","B=
arriere","","04-07-2025 07:59:48","04-07-2025 07:56:42","04-07-2025 08:13:5=
3","Site unstable : No power issue on site Ubay: 53.4V site on Gen TX Fme S=
AMBA (654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Site uns=
table : No power issue on site Ubay: 53.4V site on Gen TX Fme SAMBA (654266=
058/Huawei) is informed.","gaelle.njiofack@matech-cameroun.com","189","04-0=
7-2025 07:59:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005402913","EBOM",""=
,"04-07-2025 07:59:23","04-07-2025 07:50:16","04-07-2025 09:15:06","Cascade=
d Incident from TTO5576920","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down due to Gen ov=
erload (15KVA, 350A) //Site stabilized	","system","267389","04-07-2025 07:5=
9:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_508","NOCINC0005402914","Crf-Nsam=
","","04-07-2025 07:59:23","04-07-2025 07:50:16","04-07-2025 09:15:06","Cas=
caded Incident from TTO5576920","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down due to Gen=
 overload (15KVA, 350A) //Site stabilized	","system","267391","04-07-2025 0=
7:59:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_282","NOCINC0005402912","Meyo",""=
,"04-07-2025 07:59:23","04-07-2025 07:50:16","04-07-2025 09:15:06","Cascade=
d Incident from TTO5576920","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down due to Gen ov=
erload (15KVA, 350A) //Site stabilized	","system","267390","04-07-2025 07:5=
9:23","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005402906","A=
hala","IHS_YND_257, IHS_YND_282, IHS_YND_698, IHS_YND_762, IHS_YND_508","04=
-07-2025 07:57:22","04-07-2025 07:50:16","04-07-2025 09:15:06","Grid outage=
, Site went down due to Gen overload (15KVA, 350A) //Site stabilized	","MIN=
KA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down due to Gen overload (15KVA, 350A) //Site stabilized=
	","gaelle.njiofack@matech-cameroun.com","427","04-07-2025 07:57:22","MATEC=
H CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005402110","Evo=
doula MTN","","04-07-2025 05:35:33","04-07-2025 05:34:19","04-07-2025 05:37=
:07","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","cedr=
ic.tiani@matech-cameroun.com","75","04-07-2025 05:35:33","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005401205","S=
aa","","04-07-2025 01:28:10","04-07-2025 01:21:57","04-07-2025 01:38:26","A=
ctive // No power issue on site ,site on Gen with Ubaie =3D51.5V The Tx Tec=
hnician from Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active // No power issue on site ,site on Gen with Ubaie =3D51.5V T=
he Tx Technician from Huawei Gr=E9goire//654547479 is informed","vanel.mbia=
da@matech-cameroun.com","375","04-07-2025 01:28:10","MATECH CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0005401194","M=
inka","","04-07-2025 01:25:08","04-07-2025 01:20:50","04-07-2025 02:18:30",=
"Hybrid gen site, Site went down because gen failed to start due to hybrid =
system disfunctionning//he reset it and started the gen manually","Fanda Br=
ice","Equipment Repair","Passive","Hybrid","Hybrid Module","Hybrid gen site=
, Site went down because gen failed to start due to hybrid system disfuncti=
onning//he reset it and started the gen manually","vanel.mbiada@matech-came=
roun.com","259","04-07-2025 01:25:08","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005401097","N=
kolso","","04-07-2025 01:14:19","04-07-2025 01:12:08","04-07-2025 01:17:53"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage,RCP faulty// He bypassed the Grid and site on Gen","TIENTCHEU NZ=
ETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, Site went down because gen fails to start du=
e to grid bad voltage,RCP faulty// He bypassed the Grid and site on Gen","v=
anel.mbiada@matech-cameroun.com","132","04-07-2025 01:14:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0005400998","Mendong =
Maeture","","04-07-2025 00:59:04","04-07-2025 00:51:25","04-07-2025 00:56:0=
7","Cascaded Incident from TTO5574806","Hyemafo Gildas","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue on site U=3D49v si=
te on Grid The Tx FME HOSIAH//699699694 from Huawei is informed.","system",=
"263658","04-07-2025 00:59:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005400999","Montee-J=
ouvence","","04-07-2025 00:59:04","04-07-2025 00:51:25","04-07-2025 00:56:0=
7","Cascaded Incident from TTO5574806","Hyemafo Gildas","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue on site U=3D49v si=
te on Grid The Tx FME HOSIAH//699699694 from Huawei is informed.","system",=
"263659","04-07-2025 00:59:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0005400997","Mendong =
vallee","","04-07-2025 00:59:03","04-07-2025 00:51:25","04-07-2025 00:56:07=
","Cascaded Incident from TTO5574806","Fanda Brice","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D49v site o=
n Grid The Tx FME HOSIAH//699699694 from Huawei is informed.","system","263=
658","04-07-2025 00:59:03","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005400979","M=
endong","IHS_YND_692, IHS_YND_569, IHS_YND_236","04-07-2025 00:53:33","04-0=
7-2025 00:51:25","04-07-2025 00:56:07","No power issue on site U=3D49v site=
 on Grid The Tx FME HOSIAH//699699694 from Huawei is informed.","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site U=3D49v site on Grid The Tx FME HO=
SIAH//699699694 from Huawei is informed.","vanel.mbiada@matech-cameroun.com=
","129","04-07-2025 00:53:33","MATECH CMR"
"Closed Complete","Site Down","CTR_542","IHS_YND_182","NOCINC0005400968","T=
iti Garage","","04-07-2025 00:50:37","04-07-2025 00:42:29","04-07-2025 01:1=
7:10","Active//No power issue on site U=3D51.5 V site on Grid The TX FME Ar=
mand // 691144412 from Huawei is informed.","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue on site U=3D51.5 V site on Grid The TX FME Armand // 6=
91144412 from Huawei is informed.","vanel.mbiada@matech-cameroun.com","489"=
,"04-07-2025 00:50:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005400868","Nkolfon =
Cimencam","","04-07-2025 00:15:10","04-07-2025 00:06:03","04-07-2025 00:39:=
33","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","Cascade=
 Active","ACTIVE //No power issue Ubaie: 54,8V Site on Grid The Tx Fme Geor=
ges /6974661814 from huawei is informed","system","266365","04-07-2025 00:1=
5:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005400867","EBOM",""=
,"04-07-2025 00:15:10","04-07-2025 00:06:03","04-07-2025 00:39:33","","Hyem=
afo Gildas","Cascade Outage","Active","Cascade Active","Cascade Active","AC=
TIVE //No power issue Ubaie: 54,8V Site on Grid The Tx Fme Georges /6974661=
814 from huawei is informed","system","266364","04-07-2025 00:15:10","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_508","NOCINC0005400869","Crf-Nsam=
","","04-07-2025 00:15:10","04-07-2025 00:06:03","04-07-2025 00:39:33","","=
MINKA NICOLAS","Cascade Outage","Active","Cascade Active","Cascade Active",=
"ACTIVE //No power issue Ubaie: 54,8V Site on Grid The Tx Fme Georges /6974=
661814 from huawei is informed","system","266366","04-07-2025 00:15:10","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_282","NOCINC0005400866","Meyo","I=
HS_YND_257, IHS_YND_698, IHS_YND_762, IHS_YND_165, IHS_YND_508","04-07-2025=
 00:15:09","04-07-2025 00:06:03","04-07-2025 01:39:33","ACTIVE //No power i=
ssue Ubaie: 54,8V Site on Grid The Tx Fme Georges /6974661814 from huawei i=
s informed","Hyemafo Gildas","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","ACTIVE //No power issue Ubaie: 54,=
8V Site on Grid The Tx Fme Georges /6974661814 from huawei is informed","sy=
stem","546","04-07-2025 00:15:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005400865","Ahala","=
","04-07-2025 00:15:09","04-07-2025 00:06:03","04-07-2025 00:39:33","","Hye=
mafo Gildas","Cascade Outage","Active","Cascade Active","Cascade Active","A=
CTIVE //No power issue Ubaie: 54,8V Site on Grid The Tx Fme Georges /697466=
1814 from huawei is informed","system","266366","04-07-2025 00:15:09","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005400849","A=
hala","","04-07-2025 00:10:22","04-07-2025 00:06:03","04-07-2025 00:39:33",=
"","MINKA NICOLAS","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","ACTIVE //No power issue Ubaie: 54,8V Site on Grid The Tx Fme Georges /=
6974661814 from huawei is informed","vanel.mbiada@matech-cameroun.com","266=
364","04-07-2025 00:10:22","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005400632","N=
kolso","","03-07-2025 23:21:08","03-07-2025 23:20:52","04-07-2025 00:56:46"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage,RCP faulty// He bypassed  the Grid and site on Gen","TIENTCHEU N=
ZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, Site went down because gen fails to start d=
ue to grid bad voltage,RCP faulty// He bypassed  the Grid and site on Gen",=
"vanel.mbiada@matech-cameroun.com","17","03-07-2025 23:21:08","MATECH CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0005400344","B=
ATA-Mokolo","","03-07-2025 22:29:29","03-07-2025 22:28:21","05-07-2025 12:1=
5:21","Grid Only, No space to deploy MDGE // Grid returned","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space=
 to deploy MDGE // Grid returned","vanel.mbiada@matech-cameroun.com","69","=
03-07-2025 22:29:29","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005400277","O=
dza II OCM","","03-07-2025 22:16:17","03-07-2025 22:12:49","03-07-2025 22:1=
6:16","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Grid stabilized","Albran Byorel","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Grid outage, site went down=
 because gen failed to start due to PWC ZTE malfunction // Grid stabilized"=
,"gerard.tchangoue@matech-cameroun.com","211","03-07-2025 22:16:17","MATECH=
 CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005400253","OBA=
M NGOLA OCM","","03-07-2025 22:07:39","03-07-2025 21:58:30","03-07-2025 21:=
59:31","WRONGLY CREATED TICKET(SITE DISMANTLE)","MINKA NICOLAS","Incorrectl=
y Logged Tickets","Error","Error","Error","WRONGLY CREATED TICKET(SITE DISM=
ANTLE)","christian.fonkou@ihstowers.com","550","03-07-2025 22:07:39","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005400194","M=
EHANDAN","","03-07-2025 21:58:43","03-07-2025 13:36:29","03-07-2025 14:36:4=
7","(Backtraking)  Site went down because gen fails to start due to grid ba=
d voltage // He bypass grid and manually start the gen","Albran Byorel","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","(Bac=
ktraking)  Site went down because gen fails to start due to grid bad voltag=
e // He bypass grid and manually start the gen","edwige.kapawo@matech-camer=
oun.com","30137","03-07-2025 21:58:43","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005400008","SIM=
BOCK BONAMBAPE","","03-07-2025 21:31:19","03-07-2025 21:29:04","03-07-2025 =
21:31:26","Grid outage, Site went down before Gen start due to poor backup =
// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","edwige.kapawo@matech-cameroun.com",=
"136","03-07-2025 21:31:19","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005399426","A=
wae Ewonkan","","03-07-2025 19:54:24","03-07-2025 19:49:15","03-07-2025 22:=
47:26","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed//Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Grid return"=
,"gerard.tchangoue@matech-cameroun.com","311","03-07-2025 19:54:24","MATECH=
 CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005399412","Eki=
e sud","","03-07-2025 19:52:28","03-07-2025 19:46:21","03-07-2025 20:28:11"=
,"Site went down because disjnuction Cb in DC BOX MTN // He reamed CB, site=
 on grid","Albran Byorel","Equipment Repair","Passive","Control Panel","BTS=
 Breaker Tripped","Site went down because disjnuction Cb in DC BOX MTN // H=
e reamed CB, site on grid","edwige.kapawo@matech-cameroun.com","368","03-07=
-2025 19:52:28","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005398976","Tou=
ring Club International","","03-07-2025 18:26:27","02-07-2025 07:37:52","02=
-07-2025 08:13:52","Grid outage, Gen failed to start due to Alarm Undervolt=
age // Gen card reset, and Gen start manually","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen failed=
 to start due to Alarm Undervoltage // Gen card reset, and Gen start manual=
ly","gerard.tchangoue@matech-cameroun.com","125316","03-07-2025 18:26:27","=
MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005398955","NKO=
MKANA ELIZA HOTEL","","03-07-2025 18:20:55","02-07-2025 13:46:44","02-07-20=
25 14:44:44","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","102852","03-07-2025 18:20:55","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005398879","B=
arriere","","03-07-2025 18:04:13","03-07-2025 18:03:01","03-07-2025 18:13:0=
1","Site unstable : No power issue on site Ubay: 53.3V site on Gen TX Fme S=
AMBA (654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Site uns=
table : No power issue on site Ubay: 53.3V site on Gen TX Fme SAMBA (654266=
058/Huawei) is informed.","gerard.tchangoue@matech-cameroun.com","74","03-0=
7-2025 18:04:13","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005398856","MBA=
LNGONG LYCEE","","03-07-2025 18:00:09","03-07-2025 17:55:58","03-07-2025 18=
:43:54","Grid outage,Site went down because Gen stopped due to overload(9kv=
a, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda =
Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge,Site went down because Gen stopped due to overload(9kva, 130A) SS IHS Fe=
lix Zambe is informed and confirmed//Grid return","edwige.kapawo@matech-cam=
eroun.com","253","03-07-2025 18:00:09","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005398835","N=
koabang2","","03-07-2025 17:56:39","03-07-2025 17:52:24","03-07-2025 17:55:=
59","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ge=
rard.tchangoue@matech-cameroun.com","257","03-07-2025 17:56:39","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005398284","Montee-J=
ouvence","","03-07-2025 16:31:57","03-07-2025 16:25:04","03-07-2025 16:31:1=
7","Cascaded Incident from TTO5571718","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
fore Gen start due to poor backup // Grid return","system","286722","03-07-=
2025 16:31:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0005398283","Mendong =
vallee","","03-07-2025 16:31:57","03-07-2025 16:25:04","03-07-2025 16:31:17=
","Cascaded Incident from TTO5571718","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down before=
 Gen start due to poor backup // Grid return","system","286721","03-07-2025=
 16:31:57","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005398267","M=
endong","IHS_YND_692, IHS_YND_236","03-07-2025 16:28:15","03-07-2025 16:25:=
04","03-07-2025 16:31:17","Grid outage, Site went down before Gen start due=
 to poor backup // Grid return","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Grid return","gerard.tchangoue@ma=
tech-cameroun.com","192","03-07-2025 16:28:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_261","NOCINC0005397593","Barriere=
","","03-07-2025 14:49:56","03-07-2025 14:46:47","03-07-2025 17:35:58","Gri=
d outage, Site went down because Gen overload (30kva, 410A) SS IHS Felix ZA=
MBE confirmed // Grid return","Hyemafo Gildas","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen over=
load (30kva, 410A) SS IHS Felix ZAMBE confirmed // Grid return","edwige.kap=
awo@matech-cameroun.com","191","03-07-2025 14:49:56","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0005397531","Mfo=
u EPC","","03-07-2025 14:41:19","03-07-2025 14:33:05","03-07-2025 15:10:21"=
,"Site went down due to work:Herve (655999779 //Matech) was on site for wor=
k (PM)// End of work","Mba Lazare Herve","Equipment Replacement","Passive",=
"Planned Activity","Planned Activity - Passive","Site went down due to work=
:Herve (655999779 //Matech) was on site for work (PM)// End of work","edwig=
e.kapawo@matech-cameroun.com","535","03-07-2025 14:41:19","MATECH CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0005397147","Oss=
ombe","","03-07-2025 13:41:10","25-06-2025 23:35:21","26-06-2025 00:01:58",=
"Bactracking  NO power issue on site.Hybrid gen site on gen with u=3D54.6V"=
,"Parker Tchoup","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Bactracking  NO power issue on site.Hybrid gen=
 site on gen with u=3D54.6V","mouliom.anselme@matech-cameroun.com","655549"=
,"03-07-2025 13:41:10","MATECH CMR"
"Cancelled","Warning","T1869","IHS_YND_528","NOCINC0005397130","MEHANDAN","=
","03-07-2025 13:37:03","","","Site went down because gen start and stopped=
 due to grid bad voltage // He bypass grid and Gen manually Started","Albra=
n Byorel","","","","","","christelle.ngonga@matech-cameroun.com","4","03-07=
-2025 13:37:03","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0005397082","Yok=
o MTN","","03-07-2025 13:27:53","25-06-2025 23:01:08","25-06-2025 23:40:58"=
," Bactracking Active// No power issue on site, Site on gen  54 V, The FME =
TX Gr=E9goire(65547479) From Huawei is informed ","Parker Tchoup","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
"," Bactracking Active// No power issue on site, Site on gen  54 V, The FME=
 TX Gr=E9goire(65547479) From Huawei is informed ","mouliom.anselme@matech-=
cameroun.com","656805","03-07-2025 13:27:53","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005397051","C=
harles-Atangana","","03-07-2025 13:19:39","25-06-2025 22:30:31","25-06-2025=
 22:43:31","Bactracking Grid outage.no space to deploy mobile gen//Grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Bactracking Grid outage.no space to deploy mobile gen//Grid return","mouli=
om.anselme@matech-cameroun.com","658148","03-07-2025 13:19:39","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005397050","Evo=
doula MTN","","03-07-2025 13:19:31","03-07-2025 13:15:21","03-07-2025 13:31=
:17","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","chri=
stelle.ngonga@matech-cameroun.com","251","03-07-2025 13:19:31","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005397043","A=
wae Ewonkan","","03-07-2025 13:17:48","03-07-2025 13:16:40","03-07-2025 13:=
18:17","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed// Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed// Grid retur=
n","christelle.ngonga@matech-cameroun.com","70","03-07-2025 13:17:48","MATE=
CH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005397038","OTE=
LE MTN","","03-07-2025 13:17:07","03-07-2025 13:11:00","03-07-2025 14:49:44=
","Site went down due to work: Maxime(693835849 //Matech) was on site for w=
ork (fuel line issue)// End of work","Fanda Brice","Equipment Replacement",=
"Passive","Planned Activity","Planned Activity - Passive","Site went down d=
ue to work: Maxime(693835849 //Matech) was on site for work (fuel line issu=
e)// End of work","christelle.ngonga@matech-cameroun.com","369","03-07-2025=
 13:17:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005396901","Mfou EPC=
","","03-07-2025 12:52:14","03-07-2025 12:47:19","03-07-2025 12:52:23","Cas=
caded Incident from TTO5570140","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","263881","03-07-2025 12=
:52:14","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005396897","M=
fou OCM","IHS_YND_674","03-07-2025 12:51:28","03-07-2025 12:47:19","03-07-2=
025 12:52:23","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid Outage, Site Down before gen Started due to poor =
backup //Grid returned","christelle.ngonga@matech-cameroun.com","251","03-0=
7-2025 12:51:28","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005396844","M=
ontee-Des-Soeurs","","03-07-2025 12:39:01","03-07-2025 12:34:54","03-07-202=
5 13:38:54","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","christelle.ngonga@matech-cameroun.com","249","03-07-2025 12:39=
:01","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005396826","Ebo=
go","","03-07-2025 12:35:41","03-07-2025 12:32:50","03-07-2025 12:42:14","G=
rid fluctuation, site went down because Gen failed to start due to grid bad=
 voltag // Site stabilised","Siligap Boris","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid fluctuation, site went down=
 because Gen failed to start due to grid bad voltag // Site stabilised","ch=
ristelle.ngonga@matech-cameroun.com","174","03-07-2025 12:35:41","MATECH CM=
R"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005396761","M=
ontee-Des-Soeurs","","03-07-2025 12:23:25","03-07-2025 12:20:13","03-07-202=
5 12:27:03","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","christelle.ngonga@matech-cameroun.com","194","03-07-2025 12:23=
:25","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005396621","Bar=
riere","","03-07-2025 12:03:11","03-07-2025 12:00:04","03-07-2025 12:20:46"=
,"Grid outage, Site went down because Gen overload (30kva, 410A) SS IHS Fel=
ix ZAMBE confirmed// Site stabilized","Hyemafo Gildas","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because =
Gen overload (30kva, 410A) SS IHS Felix ZAMBE confirmed// Site stabilized",=
"christelle.ngonga@matech-cameroun.com","231","03-07-2025 12:03:11","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0005396198","A=
bang","","03-07-2025 11:06:58","03-07-2025 11:01:51","03-07-2025 11:13:10",=
"No power issue site on Grid with U=3D54.9V ,The FME TX Henri (691145055) f=
rom Huawei is working on site ","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on Grid with U=3D54.9V ,The FME TX Henri (691145055) from Huawei is=
 working on site ","christelle.ngonga@matech-cameroun.com","309","03-07-202=
5 11:06:58","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005395929","A=
kak-Nkozoa-MTN-IHS","","03-07-2025 10:34:39","03-07-2025 10:32:14","03-07-2=
025 10:35:15","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","DG failed to start due to bad voltage eneo // eneo =
disjonction, site on Gen","christelle.ngonga@matech-cameroun.com","264848",=
"03-07-2025 10:34:39","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005395686","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","03-07-2025 09:53:02","03-07-20=
25 09:49:55","03-07-2025 10:57:57","Grid outage, Site went down because Gen=
 start and stopped with ""High temps"" alarm // he added water and manually=
 start the Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","AC=
DG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site =
went down because Gen start and stopped with ""High temps"" alarm // he add=
ed water and manually start the Gen","christelle.ngonga@matech-cameroun.com=
","188","03-07-2025 09:53:02","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005395495","Evo=
doula MTN","","03-07-2025 09:15:37","03-07-2025 09:13:48","03-07-2025 09:33=
:38","	Grid outage, Site went down before Gen start due to poor backup// Ge=
n Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","	Grid outage, Site wen=
t down before Gen start due to poor backup// Gen Automatically Started","ch=
ristelle.ngonga@matech-cameroun.com","110","03-07-2025 09:15:37","MATECH CM=
R"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005395342","B=
arriere","","03-07-2025 08:52:13","03-07-2025 08:48:05","03-07-2025 08:52:5=
2","Site unstable :	 No power issue on site Ubay: 53.5V site on Gen TX Fme =
SAMBA (654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Site un=
stable :	 No power issue on site Ubay: 53.5V site on Gen TX Fme SAMBA (6542=
66058/Huawei) is informed.","christelle.ngonga@matech-cameroun.com","250","=
03-07-2025 08:52:13","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005394440","OTE=
LE MTN","","03-07-2025 04:48:59","03-07-2025 04:47:42","03-07-2025 05:01:43=
","Site went down because gen failed to start due alarm ""low oil pressure"=
"//We add oil and gen manually started","Fanda Brice","Equipment Repair","P=
assive","ACDG Gen","ACDG - Low Oil Pressure","Site went down because gen fa=
iled to start due alarm ""low oil pressure""//We add oil and gen manually s=
tarted","cedric.tiani@matech-cameroun.com","78","03-07-2025 04:48:59","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0005394235","N=
omayos","","03-07-2025 04:04:11","03-07-2025 04:02:48","03-07-2025 04:04:48=
","Active//No power issues site on Grid with U=3D54V ,The FME TX Fulbert (6=
54266068) from Huawei is informed","Fanda Brice","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issues iste on Grid with U=3D54.1V ,The FME TX Fulbert (654266068) from =
Huawei is informed","vanel.mbiada@matech-cameroun.com","84","03-07-2025 04:=
04:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005394183","Angongo"=
,"","03-07-2025 03:39:59","03-07-2025 03:29:14","03-07-2025 03:41:34","Casc=
aded Incident from TTO5567114","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubaie 54.5V site on G=
rid; TX FME Flubert (654266068/Huawei) is informed","system","261318","03-0=
7-2025 03:39:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0005394179","Nkenglik=
ok","","03-07-2025 03:39:58","03-07-2025 03:29:14","03-07-2025 03:41:34","C=
ascaded Incident from TTO5567114","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V si=
te on Grid; TX FME Flubert (654266068/Huawei) is informed","system","261317=
","03-07-2025 03:39:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0005394181","OKOA Pea=
ge","","03-07-2025 03:39:58","03-07-2025 03:29:14","03-07-2025 03:41:34","C=
ascaded Incident from TTO5567114","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V site o=
n Grid; TX FME Flubert (654266068/Huawei) is informed","system","261320","0=
3-07-2025 03:39:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005394182","Mambine"=
,"","03-07-2025 03:39:58","03-07-2025 03:29:14","03-07-2025 03:41:34","Casc=
aded Incident from TTO5567114","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubaie 54.5V site on G=
rid; TX FME Flubert (654266068/Huawei) is informed","system","261318","03-0=
7-2025 03:39:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005394180","Ebeba","=
","03-07-2025 03:39:58","03-07-2025 03:29:14","03-07-2025 03:41:34","Cascad=
ed Incident from TTO5567114","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site Ubaie 54.5V site on Gri=
d; TX FME Flubert (654266068/Huawei) is informed","system","261319","03-07-=
2025 03:39:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0005394177","Sous Pre=
fecture","","03-07-2025 03:39:57","03-07-2025 03:29:14","03-07-2025 03:41:3=
4","Cascaded Incident from TTO5567114","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V s=
ite on Grid; TX FME Flubert (654266068/Huawei) is informed","system","26131=
9","03-07-2025 03:39:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0005394178","Mandoumb=
a OCM","","03-07-2025 03:39:57","03-07-2025 03:29:14","03-07-2025 03:41:34"=
,"Cascaded Incident from TTO5567114","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site Ubaie 54.5V=
 site on Grid; TX FME Flubert (654266068/Huawei) is informed","system","261=
317","03-07-2025 03:39:57","MATECH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005394166","N=
omayos-IHS","IHS_YND_314, IHS_YND_367, IHS_YND_348, IHS_YND_339, IHS_YND_33=
0, IHS_YND_350, IHS_YND_335","03-07-2025 03:36:27","03-07-2025 03:29:14","0=
3-07-2025 03:41:34","No power issue on site Ubaie 54.5V site on Grid; TX FM=
E Flubert (654266068/Huawei) is informed","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site Ubaie 54.5V site on Grid; TX FME Flubert (654266068/Huawei)=
 is informed","vanel.mbiada@matech-cameroun.com","434","03-07-2025 03:36:27=
","MATECH CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0005394067","Nko=
ngtock","","03-07-2025 02:57:05","03-07-2025 02:43:57","03-07-2025 03:15:20=
","Site went down because gen failed to start due alrm ""low oil pressure""=
//We add oil and gen manually started","Kemeni Franklin","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down because gen=
 failed to start due alrm ""low oil pressure""//We add oil and gen manually=
 started","vanel.mbiada@matech-cameroun.com","789","03-07-2025 02:57:05","M=
ATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005394062","OTE=
LE MTN","","03-07-2025 02:55:33","03-07-2025 02:43:15","03-07-2025 03:29:26=
","	Site went down because gen failed to start due alarm ""low oil pressure=
""//We add oil and gen manually started","Fanda Brice","Equipment Repair","=
Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down because gen f=
ailed to start due alarm ""low oil pressure""//We add oil and gen manually =
started","vanel.mbiada@matech-cameroun.com","739","03-07-2025 02:55:33","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005393992","A=
fanoya","","03-07-2025 02:16:09","03-07-2025 02:14:53","03-07-2025 03:29:24=
","Grid outage,site went down because Gen failed to start due to Gen card f=
aulty //He started the Gen manually","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down becau=
se Gen failed to start due to Gen card faulty //He started the Gen manually=
","vanel.mbiada@matech-cameroun.com","77","03-07-2025 02:16:09","MATECH CMR=
"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005393951","Ngo=
usso Vallee","","03-07-2025 02:08:15","03-07-2025 02:04:58","03-07-2025 03:=
16:18","Access Issue during the night due to Landlord .(Grid outage,site we=
nt down because Gen failed to start(investigation ongoing)","Siligap Boris"=
,"Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue -=
 Land Lord","Access Issue during the night due to Landlord .(Grid outage,si=
te went down because Gen failed to start(investigation ongoing)","vanel.mbi=
ada@matech-cameroun.com","198","03-07-2025 02:08:15","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005393943","M=
anguier","","03-07-2025 02:06:06","03-07-2025 02:03:58","03-07-2025 05:56:1=
3","Site went down due to work: Our Technician Alex Notsawo /692288751/EPIT=
ECH working on site (Swapp pwc)//End of work","Fabrice Pouakam","Installati=
on Activity","Passive","Planned Activity","Installation Activity","Site wen=
t down due to work: Our Technician Alex Notsawo /692288751/EPITECH working =
on site (Swapp pwc)//End of work","vanel.mbiada@matech-cameroun.com","129",=
"03-07-2025 02:06:06","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005393916","M=
anguier","","03-07-2025 01:51:05","03-07-2025 01:49:54","03-07-2025 01:51:1=
2","Site went down due to work: Our Technician Alex Notsawo /692288751/EPIT=
ECH working on site (Swapp pwc)//End of work","Fabrice Pouakam","Installati=
on Activity","Passive","Planned Activity","Installation Activity","Site wen=
t down due to work: Our Technician Alex Notsawo /692288751/EPITECH working =
on site (Swapp pwc)//End of work","vanel.mbiada@matech-cameroun.com","72","=
03-07-2025 01:51:05","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005393839","M=
anguier","","03-07-2025 01:29:28","03-07-2025 01:26:47","03-07-2025 01:30:2=
2","Site went down due to work: Our Technician Alex Notsawo /692288751/EPIT=
ECH working on site (Swapp pwc)//End of work	","Fabrice Pouakam","Installat=
ion Activity","Passive","Planned Activity","Installation Activity","Site we=
nt down due to work: Our Technician Alex Notsawo /692288751/EPITECH working=
 on site (Swapp pwc)//End of work	","vanel.mbiada@matech-cameroun.com","162=
","03-07-2025 01:29:28","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005393161","A=
wae Ewonkan","","02-07-2025 22:14:24","02-07-2025 22:10:19","02-07-2025 22:=
51:05"," Grid outage site went down due to Gen Overload (20Kva, Iload 225 A=
)IHS SS Alphonse is informed// Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload"," Grid outage site went down due=
 to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed// Grid Ret=
urn","gerard.tchangoue@matech-cameroun.com","247","02-07-2025 22:14:24","MA=
TECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005393157","Men=
dong NB","","02-07-2025 22:13:09","02-07-2025 22:05:59","02-07-2025 23:13:2=
3","Site went down because gen fails to start due to grid bad voltage( Lack=
 of 2 phase on site) // He did a bridge with a good phase","","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Site went down=
 because gen fails to start due to grid bad voltage( Lack of 2 phase on sit=
e) // He did a bridge with a good phase","franck.nkomot@matech-cameroun.com=
","432","02-07-2025 22:13:09","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005393155","M=
ontee-Des-Soeurs","","02-07-2025 22:12:45","02-07-2025 22:06:33","03-07-202=
5 10:51:30","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","gerard.tchangoue@matech-cameroun.com","374","02-07-2025 22:12:=
45","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005392827","A=
wae Escalier","","02-07-2025 21:13:43","02-07-2025 21:12:33","02-07-2025 21=
:17:33","Grid fluctuation,site went down because Gen failed to start due to=
 Grid bad voltage//He bypassed the Grid and started gen manually","Albran B=
yorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation,site went down because Gen failed to start due to Gr=
id bad voltage//He bypassed the Grid and started gen manually","gerard.tcha=
ngoue@matech-cameroun.com","71","02-07-2025 21:13:43","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005392776","E=
vodoula OCM","","02-07-2025 21:04:38","02-07-2025 20:14:24","03-07-2025 07:=
05:31","Site went down due to (1/3) rectifiers faulty//We replace rectifier=
 and site on gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Site went down due to (1/3) rectifiers fault=
y//We replace rectifier and site on grid ","gerard.tchangoue@matech-camerou=
n.com","3015","02-07-2025 21:04:38","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005392725","S=
imbock OCM","","02-07-2025 20:57:56","02-07-2025 20:48:46","02-07-2025 20:5=
8:23","Site impacted by Nkolzie CTR_672 not manage by IHS","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","Affected=
 by 3rd Party Site","Site impacted by Nkolzie CTR_672 not manage by IHS","g=
erard.tchangoue@matech-cameroun.com","551","02-07-2025 20:57:56","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005392720","C-Suprem=
e","","02-07-2025 20:56:25","02-07-2025 20:47:20","02-07-2025 20:49:20","Ca=
scaded Incident from TTO5565466","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, Site went down before Gen start due t=
o poor backup // Grid return","system","263894","02-07-2025 20:56:25","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005392712","M=
vog Mbi New","IHS_YND_021","02-07-2025 20:55:42","02-07-2025 20:47:20","02-=
07-2025 20:49:20","Grid outage, Site went down before Gen start due to poor=
 backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Grid return","gerard.tchangoue@matech-came=
roun.com","503","02-07-2025 20:55:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005392695","MEHANDAN=
","","02-07-2025 20:54:28","02-07-2025 20:46:18","02-07-2025 20:50:18","Cas=
caded Incident from TTO5565443","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Grid stabilized","system","=
263953","02-07-2025 20:54:28","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005392689","O=
dza II OCM","IHS_YND_528","02-07-2025 20:53:29","02-07-2025 20:46:18","02-0=
7-2025 20:50:18","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Grid =
stabilized","gerard.tchangoue@matech-cameroun.com","434","02-07-2025 20:53:=
29","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005392684","M=
ontee-Des-Soeurs","","02-07-2025 20:52:07","02-07-2025 20:46:56","02-07-202=
5 20:54:32","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","gerard.tchangoue@matech-cameroun.com","313","02-07-2025 20:52:=
07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005392679","Nsam esc=
ale LP","","02-07-2025 20:51:22","02-07-2025 20:46:41","02-07-2025 20:52:41=
","Cascaded Incident from TTO5565426","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Grid return","system","263928","02-07-2025 20:51:22",=
"MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005392674","Nsa=
m Sofavinc","IHS_YND_732","02-07-2025 20:50:53","02-07-2025 20:46:41","02-0=
7-2025 20:52:41","Grid Outage, Site went down before Gen start due to poor =
backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before =
Gen start due to poor backup // Grid return","franck.nkomot@matech-cameroun=
.com","253","02-07-2025 20:50:53","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005392484","A=
wae Escalier","","02-07-2025 20:11:49","02-07-2025 20:04:30","02-07-2025 20=
:19:33","Grid fluctuation,site went down because Gen failed to start due to=
 Grid bad voltage//Grid stabilized","Albran Byorel","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation,site we=
nt down because Gen failed to start due to Grid bad voltage//Grid stabilize=
d","franck.nkomot@matech-cameroun.com","441","02-07-2025 20:11:49","MATECH =
CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005392409","Men=
dong NB","","02-07-2025 19:51:30","02-07-2025 19:47:24","02-07-2025 20:59:2=
4","Site went down due to grid bad voltage // He disconnected two phases","=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Site went down due to grid bad voltage // He disconnected two phases","fra=
nck.nkomot@matech-cameroun.com","247","02-07-2025 19:51:30","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005392405","OTE=
LE MTN","","02-07-2025 19:50:59","02-07-2025 19:47:47","02-07-2025 22:01:05=
","Site went down because gen failed to start due alarm ""low oil pressure"=
"//We add oil and gen manually started","Fanda Brice","Equipment Repair","P=
assive","ACDG Gen","ACDG - Low Oil Pressure","Site went down because gen fa=
iled to start due alarm ""low oil pressure""//We add oil and gen manually s=
tarted","franck.nkomot@matech-cameroun.com","194","02-07-2025 19:50:59","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005392070","A=
wae Ewonkan","","02-07-2025 18:40:39","02-07-2025 18:39:34","02-07-2025 21:=
56:25","(Unstable site) Grid outage site went down due to Gen Overload (20K=
va, Iload 225 A)IHS SS Alphonse is informed//Site stabilised","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","(Unstable sit=
e) Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IHS S=
S Alphonse is informed//Site stabilised","gerard.tchangoue@matech-cameroun.=
com","67","02-07-2025 18:40:39","MATECH CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0005391784","N=
KONGKARAK","","02-07-2025 17:55:20","02-07-2025 17:52:08","02-07-2025 18:25=
:20","Grid outage, Site went down because Gen started and stopped due to Hi=
gh temp alarm //He added water and Gen start manually	","TIENTCHEU NZETCHIE=
U GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - =
Coolant Level Issue","Grid outage, Site went down because Gen started and s=
topped due to High temp alarm //He added water and Gen start manually	","ge=
rard.tchangoue@matech-cameroun.com","194","02-07-2025 17:55:20","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005391721","Nkol-Meb=
anga","","02-07-2025 17:46:18","02-07-2025 17:42:46","02-07-2025 18:17:13",=
"Cascaded Incident from TTO5564280","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation gen failed to sta=
rt due to automatism malfuncttionning // Grid return","system","267743","02=
-07-2025 17:46:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005391720","Carrefou=
r Ayissi Ele","","02-07-2025 17:46:17","02-07-2025 17:42:46","02-07-2025 18=
:17:13","Cascaded Incident from TTO5564280","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid fluctuation gen faile=
d to start due to automatism malfuncttionning // Grid return","system","267=
742","02-07-2025 17:46:17","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005391649","S=
aa","IHS_YND_810, IHS_YND_809","02-07-2025 17:39:56","02-07-2025 17:37:46",=
"02-07-2025 18:17:13","Grid fluctuation gen failed to start due to automati=
sm malfuncttionning // Grid return","Parker Tchoup","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","Grid fluctuation gen failed to start=
 due to automatism malfuncttionning // Grid return","gerard.tchangoue@matec=
h-cameroun.com","131","02-07-2025 17:39:56","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005391547","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","02-07-2025 17:29:54","02-07-20=
25 17:26:49","02-07-2025 18:09:49","Grid outage, Site went down because Gen=
 start and stopped with ""High temps"" alarm // he added water and manually=
 start the Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","AC=
DG Gen","Gen Temp High","Grid outage, Site went down because Gen start and =
stopped with ""High temps"" alarm // he added water and manually start the =
Gen","franck.nkomot@matech-cameroun.com","186","02-07-2025 17:29:54","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005391265","B=
arriere","","02-07-2025 17:10:59","02-07-2025 17:10:50","02-07-2025 17:12:1=
9","Active// No power issue on site Ubay: 53.4V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 53.4V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","gerard.tchangoue@matech-cameroun.com","11","02-07-2025 17:10:5=
9","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005390971","A=
wae Escalier","","02-07-2025 16:30:41","02-07-2025 16:27:25","02-07-2025 17=
:32:07","Grid outage, Site went down because Gen failed to start due to ala=
rm""low oil pressure""//He added oil and Gen started","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage, =
Site went down because Gen failed to start due to alarm""low oil pressure""=
//He added oil and Gen started","gerard.tchangoue@matech-cameroun.com","198=
","02-07-2025 16:30:41","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005390933","OTE=
LE MTN","","02-07-2025 16:22:37","02-07-2025 16:18:30","02-07-2025 16:51:30=
","Grid outage,site went because Gen started and stopped due to alarm low o=
il pressure //He added oil and manually started with an external battery","=
Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressu=
re","Grid outage,site went because Gen started and stopped due to alarm low=
 oil pressure //He added oil and manually started with an external battery"=
,"franck.nkomot@matech-cameroun.com","249","02-07-2025 16:22:37","MATECH CM=
R"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005390824","A=
wae Ewonkan","","02-07-2025 16:03:20","01-07-2025 18:08:42","01-07-2025 18:=
26:42","Bactracking(Unstable site) Grid outage site went down due to Gen Ov=
erload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Site stabilised","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Ba=
ctracking(Unstable site) Grid outage site went down due to Gen Overload (20=
Kva, Iload 225 A)IHS SS Alphonse is informed//Site stabilised","mouliom.ans=
elme@matech-cameroun.com","78878","02-07-2025 16:03:20","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005390690","A=
wae Ewonkan","","02-07-2025 15:45:31","02-07-2025 15:44:21","02-07-2025 18:=
29:40","(Unstable site) Grid outage site went down due to Gen Overload (20K=
va, Iload 225 A)IHS SS Alphonse is informed//Site stabilised","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","(Unstable sit=
e) Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IHS S=
S Alphonse is informed//Site stabilised","gerard.tchangoue@matech-cameroun.=
com","72","02-07-2025 15:45:31","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005389916","C=
arrefourt Nkomo","","02-07-2025 14:14:19","02-07-2025 14:02:12","02-07-2025=
 14:42:12","Grid outage,Site went down because Gen failed to start due to G=
rid contactor malfunctioning // He bypassed Grid and started Gen manualy","=
Mba Lazare Herve","Equipment Repair","Passive","Control Panel","ATS-AMF Iss=
ue","Grid outage,Site went down because Gen failed to start due to Grid con=
tactor malfunctioning // He bypassed Grid and started Gen manualy","christe=
lle.ngonga@matech-cameroun.com","729","02-07-2025 14:14:19","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005389912","A=
WAE OCM","","02-07-2025 14:13:40","02-07-2025 14:02:30","02-07-2025 15:00:3=
2","Grid outage, site went down because gen failed to start due to PWC ZTE =
malfunction, // He reset and gen manually started","Mba Lazare Herve","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid out=
age, site went down because gen failed to start due to PWC ZTE malfunction,=
 // He reset and gen manually started","christelle.ngonga@matech-cameroun.c=
om","672","02-07-2025 14:13:40","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005389858","Nko=
mo","","02-07-2025 14:06:22","02-07-2025 14:03:02","02-07-2025 14:45:02","G=
rid fluctuations, site went down because gen failed to start due to PWC ZTE=
 malfunction // Eneo return","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Grid fluctuations, site went d=
own because gen failed to start due to PWC ZTE malfunction // Eneo return",=
"edwige.kapawo@matech-cameroun.com","202","02-07-2025 14:06:22","MATECH CMR=
"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005389783","B=
arriere","","02-07-2025 14:03:04","02-07-2025 14:02:14","02-07-2025 15:03:2=
6","Active// No power issue on site Ubay: 53.4V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 53.4V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","christelle.ngonga@matech-cameroun.com","52","02-07-2025 14:03:=
04","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005389756","A=
wae Ewonkan","","02-07-2025 13:57:50","02-07-2025 13:56:43","02-07-2025 14:=
48:58","(Unstable site) Grid outage site went down due to Gen Overload (20K=
va, Iload 225 A)IHS SS Alphonse is informed//Site stabilised","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","(Unstable sit=
e) Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IHS S=
S Alphonse is informed//Site stabilised","christelle.ngonga@matech-cameroun=
.com","69","02-07-2025 13:57:50","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005389365","Lad=
a I Yde","","02-07-2025 12:54:06","02-07-2025 12:51:57","02-07-2025 13:12:0=
9","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","edwige.kapawo@matech-cameroun.com","131","02-07-2025 12:54:06","MATECH C=
MR"
"Closed Complete","Site Down","T3206","IHS_YND_759","NOCINC0005389200","Nko=
lfoulou Tsinga Village","","02-07-2025 12:30:46","02-07-2025 12:24:35","02-=
07-2025 14:43:30","Grid outage .gen failed to start due to AVR faulty//Grid=
 return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - AV=
R","Grid outage .gen failed to start due to AVR faulty//Grid return","edwig=
e.kapawo@matech-cameroun.com","372","02-07-2025 12:30:46","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005389185","C=
omplexe-BEAC","","02-07-2025 12:29:49","02-07-2025 12:25:42","02-07-2025 12=
:29:08","Grid outage, Site went down before Gen start due to Poor battery b=
ackup // Grid returned","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to Poor battery backup // Grid returned","christelle.ngonga@=
matech-cameroun.com","249","02-07-2025 12:29:49","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005389129","N=
koabang Ebolmedjock","","02-07-2025 12:19:08","02-07-2025 12:18:00","02-07-=
2025 12:21:48","Site impacted by CTR_711 Nkolmesseng Abom not ihs site","Mb=
a Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fai=
lure","Affected by 3rd Party Site","Site impacted by CTR_711 Nkolmesseng Ab=
om not ihs site","christelle.ngonga@matech-cameroun.com","69","02-07-2025 1=
2:19:08","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005389065","Bar=
riere","","02-07-2025 12:12:48","02-07-2025 12:10:44","02-07-2025 13:01:17"=
,"Grid outage, site went down because gen start and stopped with high temp =
// Doors  opened  and gen manually started .","Hyemafo Gildas","Equipment R=
epair","Passive","ACDG Gen","Gen Temp High","Grid outage, site went down be=
cause gen start and stopped with high temp // Doors  opened  and gen manual=
ly started .","edwige.kapawo@matech-cameroun.com","224","02-07-2025 12:12:4=
8","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005389042","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","02-07-2025 12:10:34","02-07-20=
25 12:08:24","02-07-2025 14:26:07","Grid outage.gen failed to start due to =
alarm high temp causing by radiator dirty // We clean radiator and gen manu=
ally started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG=
 Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.gen fail=
ed to start due to alarm high temp causing by radiator dirty // We clean ra=
diator and gen manually started","edwige.kapawo@matech-cameroun.com","131",=
"02-07-2025 12:10:34","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005388909","A=
wae Ewonkan","","02-07-2025 11:45:04","02-07-2025 11:37:56","02-07-2025 13:=
52:15","(Unstable site) Grid outage site went down due to Gen Overload (20K=
va, Iload 225 A)IHS SS Alphonse is informed//Site stabilised","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","(Unstable sit=
e) Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IHS S=
S Alphonse is informed//Site stabilised","christelle.ngonga@matech-cameroun=
.com","430","02-07-2025 11:45:04","MATECH CMR"
"Closed Complete","Site Down","T0401","IHS_YND_205","NOCINC0005388902","Ton=
golo MTN","","02-07-2025 11:43:41","02-07-2025 11:41:35","02-07-2025 12:39:=
40","Grid outage site went down because Gen failed to start due to  GE batt=
ery stolen  //Gen manually started with external battery","Fabrice Pouakam"=
,"Site Asset Theft","Theft","Theft","Generator Battery Theft","Grid outage =
site went down because Gen failed to start due to  GE battery stolen  //Gen=
 manually started with external battery","edwige.kapawo@matech-cameroun.com=
","127","02-07-2025 11:43:41","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005388839","Nko=
mo stade","","02-07-2025 11:36:09","02-07-2025 11:27:56","02-07-2025 14:00:=
48","Grid outage gen failed to start due to alarm ''undervoltage'//We reset=
 card GE and gen manually started ","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to start=
 due to alarm ''undervoltage'//We reset card GE and gen manually started ",=
"edwige.kapawo@matech-cameroun.com","494","02-07-2025 11:36:09","MATECH CMR=
"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0005388695","Nko=
lndom","","02-07-2025 11:17:26","02-07-2025 11:13:13","02-07-2025 12:55:06"=
,"Grid outage.gen ran until fuel shortage//Refueling done","Fabrice Pouakam=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unt=
il fuel shortage//Refueling done","edwige.kapawo@matech-cameroun.com","254"=
,"02-07-2025 11:17:26","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005388647","Lad=
a I Yde","","02-07-2025 11:10:05","02-07-2025 11:04:54","02-07-2025 12:15:5=
3","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","edwige.kapawo@matech-cameroun.com","312","02-07-2025 11:10:05","MATECH C=
MR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005388579","S=
ous Prefecture","","02-07-2025 10:55:11","02-07-2025 10:52:02","02-07-2025 =
13:30:16","Site went down due to work done by IHS SS Felix Zambe(657108641)=
(work on automation) //End of work ","Fanda Brice","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Site went down due to=
 work done by IHS SS Felix Zambe(657108641)(work on automation) //End of wo=
rk ","christelle.ngonga@matech-cameroun.com","191","02-07-2025 10:55:11","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005388557","M=
ambine","","02-07-2025 10:50:39","02-07-2025 10:47:32","02-07-2025 11:32:02=
","Grid outage site went down because Gen failed to start due to Hybride sy=
stem dysfonction // He reset the hybrid system and Gen manually started","F=
anda Brice","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid out=
age site went down because Gen failed to start due to Hybride system dysfon=
ction // He reset the hybrid system and Gen manually started","christelle.n=
gonga@matech-cameroun.com","189","02-07-2025 10:50:39","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005388526","C=
harles-Atangana","","02-07-2025 10:44:24","29-06-2025 22:48:28","29-06-2025=
 23:04:52","Bactracking Grid outage no space to deploy mobile gen //Grid re=
turn ","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Bactracking Grid outage no space to deploy mobile gen //Grid return ","m=
ouliom.anselme@matech-cameroun.com","215756","02-07-2025 10:44:24","MATECH =
CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005388504","M=
ontee-Jouvence-II","","02-07-2025 10:37:19","29-06-2025 22:27:46","29-06-20=
25 22:41:02","Bactracking Grid fluctuation, Site went down because gen fail=
s to start due to grid bad voltage// Eneo Stabilised","Hyemafo Gildas","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Bactr=
acking Grid fluctuation, Site went down because gen fails to start due to g=
rid bad voltage// Eneo Stabilised","mouliom.anselme@matech-cameroun.com","2=
16573","02-07-2025 10:37:19","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005388460","Par=
adis Hotel","","02-07-2025 10:29:04","02-07-2025 10:19:59","02-07-2025 11:1=
2:22","Grid fluctuations, site went down because Gen Overload (12.5Kva, 100=
A) SS IHS BLAISE RAOUL ETCHEU is confirmed // Grid stabilised","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctua=
tions, site went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RA=
OUL ETCHEU is confirmed // Grid stabilised","edwige.kapawo@matech-cameroun.=
com","547","02-07-2025 10:29:04","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005388309","Lad=
a I Yde","","02-07-2025 09:57:26","30-06-2025 00:36:36","30-06-2025 00:40:3=
6","Bactracking Grid fluctuation site went down because Gen and started and=
 stopped due to Grid bad voltage // He bypassed the Grid and Gen manually s=
tarted","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","Bactracking Grid fluctuation site went down becau=
se Gen and started and stopped due to Grid bad voltage // He bypassed the G=
rid and Gen manually started","mouliom.anselme@matech-cameroun.com","206450=
","02-07-2025 09:57:26","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005388110","N=
koabang2","","02-07-2025 09:26:22","02-07-2025 09:22:00","02-07-2025 09:25:=
36","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ch=
ristelle.ngonga@matech-cameroun.com","264","02-07-2025 09:26:22","MATECH CM=
R"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005388078","NYO=
M FACE MAETUR","","02-07-2025 09:23:49","02-07-2025 09:23:41","02-07-2025 0=
9:24:04","Grid outage, Site went down because Gen failed to start due to Gr=
id bad voltage(LACK OF PHASE ) //He made a bridge","Fabrice Pouakam","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid ou=
tage, Site went down because Gen failed to start due to Grid bad voltage(LA=
CK OF PHASE ) //He made a bridge","christelle.ngonga@matech-cameroun.com","=
10","02-07-2025 09:23:49","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005387927","NYO=
M FACE MAETUR","","02-07-2025 08:55:39","02-07-2025 08:54:14","02-07-2025 0=
8:55:58","Grid outage, Site went down because Gen failed to start due to Gr=
id bad voltage(LACK OF PHASE ) //He made a bridge","Fabrice Pouakam","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid ou=
tage, Site went down because Gen failed to start due to Grid bad voltage(LA=
CK OF PHASE ) //He made a bridge","edwige.kapawo@matech-cameroun.com","87",=
"02-07-2025 08:55:39","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005387925","O=
LAMA","","02-07-2025 08:55:16","02-07-2025 08:52:07","02-07-2025 10:42:09",=
"No power issue on site Ubaie =3D54.5V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.5V site on Gen The TX FME Henri (699949693) from Huawei is=
 informed.","christelle.ngonga@matech-cameroun.com","190","02-07-2025 08:55=
:16","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005387804","Par=
adis Hotel","","02-07-2025 08:28:53","02-07-2025 08:28:48","02-07-2025 09:5=
9:37","Grid fluctuations, site went down because Gen Overload (12.5Kva, 100=
A) SS IHS BLAISE RAOUL ETCHEU is confirmed // Grid stabilised","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctua=
tions, site went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RA=
OUL ETCHEU is confirmed // Grid stabilised","edwige.kapawo@matech-cameroun.=
com","6","02-07-2025 08:28:53","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005387655","Par=
adis Hotel","","02-07-2025 07:44:43","02-07-2025 07:43:59","02-07-2025 07:4=
5:18","Grid fluctuations, site went down because Gen Overload (12.5Kva, 100=
A) SS IHS BLAISE RAOUL ETCHEU is confirmed // Grid stabilised","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctua=
tions, site went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RA=
OUL ETCHEU is confirmed // Grid stabilised","edwige.kapawo@matech-cameroun.=
com","45","02-07-2025 07:44:43","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005387489","NYO=
M FACE MAETUR","","02-07-2025 07:12:25","02-07-2025 07:11:19","02-07-2025 0=
8:10:44","Grid outage, Site went down because Gen failed to start due to Gr=
id bad voltage(LACK OF PHASE ) //He made a bridge","Fabrice Pouakam","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid ou=
tage, Site went down because Gen failed to start due to Grid bad voltage(LA=
CK OF PHASE ) //He made a bridge","edwige.kapawo@matech-cameroun.com","68",=
"02-07-2025 07:12:25","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005386632","Bar=
riere","","02-07-2025 02:58:26","01-07-2025 22:02:14","01-07-2025 22:05:06"=
,"Backtracking//No power issue on site Ubaie: 48.7V site on Gen TX Fme SAMB=
A (654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Backtrackin=
g//No power issue on site Ubaie: 48.7V site on Gen TX Fme SAMBA (654266058/=
Huawei) is informed.","loic.noumsi@matech-cameroun.com","17773","02-07-2025=
 02:58:26","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005385952","S=
ous Prefecture","","02-07-2025 01:17:39","02-07-2025 01:10:27","02-07-2025 =
02:10:50","Grid outage, Site went down due to cable which powered PWC has b=
urned //we reconnected the cable and site on gen","Fanda Brice","Equipment =
Repair","Passive","Infrastructure","Armoured Cable","Grid outage, Site went=
 down due to cable which powered PWC has burned //we reconnected the cable =
and site on gen","gaelle.njiofack@matech-cameroun.com","434","02-07-2025 01=
:17:39","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005385919","Mvo=
g-Manga","","02-07-2025 01:06:10","02-07-2025 01:04:56","02-07-2025 01:06:3=
7","Grid outage, Site went due to rectifiers dysfunctionning // He reset re=
ctifiers, site on GRID","Albran Byorel","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Grid outage, Site went due to rectifiers dysfunct=
ionning // He reset rectifiers, site on GRID","loic.noumsi@matech-cameroun.=
com","76","02-07-2025 01:06:10","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005385602","Mvo=
g-Manga","","01-07-2025 23:57:01","01-07-2025 23:54:08","02-07-2025 00:55:2=
9","Grid outage, Site went due to rectifiers dysfunctionning // He reset re=
ctifiers","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Grid outage, Site went due to rectifiers dysfunctionning // He =
reset rectifiers","loic.noumsi@matech-cameroun.com","175","01-07-2025 23:57=
:01","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005385553","Par=
adis Hotel","","01-07-2025 23:35:46","01-07-2025 23:33:41","01-07-2025 23:3=
5:32","Grid fluctuations, site went down because Gen Overload (12.5Kva, 100=
A) SS IHS BLAISE RAOUL ETCHEU is confirmed // Site stabilised","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctua=
tions, site went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RA=
OUL ETCHEU is confirmed // Site stabilised","loic.noumsi@matech-cameroun.co=
m","127","01-07-2025 23:35:46","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0005385462","Mfo=
u EPC","","01-07-2025 23:04:51","01-07-2025 23:00:41","02-07-2025 01:58:48"=
,"Grid outage.gen failed to start due to priming pump faulty//We fixed prim=
ing pump and gen manually started (replacement ongoing)","Mba Lazare Herve"=
,"Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Fuel Pump","Grid out=
age.gen failed to start due to priming pump faulty//We fixed priming pump a=
nd gen manually started (replacement ongoing)","loic.noumsi@matech-cameroun=
.com","251","01-07-2025 23:04:51","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005385301","Par=
adis Hotel","","01-07-2025 22:28:09","01-07-2025 22:26:53","01-07-2025 23:1=
2:02","Grid fluctuations, site went down because Gen Overload (12.5Kva, 100=
A) SS IHS BLAISE RAOUL ETCHEU is confirmed // Site stabilised","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctua=
tions, site went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RA=
OUL ETCHEU is confirmed // Site stabilised","loic.noumsi@matech-cameroun.co=
m","77","01-07-2025 22:28:09","MATECH CMR"
"Closed Complete","Site Down","CTR_122","IHS_YND_230","NOCINC0005385117","M=
eyong-Meyeme","","01-07-2025 21:49:51","01-07-2025 21:47:40","01-07-2025 21=
:50:36","Active//No power issue site is on Gen with Ubaie=3D51,5V. TX FME M=
ohamadou // 699949072 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue site is on Gen with Ubaie=3D51,5V. TX FME=
 Mohamadou // 699949072 from Huawei is informed","vanel.mbiada@matech-camer=
oun.com","132","01-07-2025 21:49:51","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005385115","Bit=
eng-Maetur","","01-07-2025 21:49:25","01-07-2025 21:40:14","01-07-2025 21:5=
9:28","Active//No power issue on site Ubaie =3D53.1V site on Grid The TX FM=
E Henri (699949693) from Huawei is informed","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site Ubaie =3D53.1V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","gerard.tchangoue@matech-cameroun.co=
m","552","01-07-2025 21:49:25","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005384965","M=
fou OCM","","01-07-2025 21:21:57","01-07-2025 21:19:20","01-07-2025 21:27:5=
5","Active//No power issues site on Grid with Ubay=3D54.9V ,The FME TX Fulb=
ert (654266068) from Huawei is informed.","Mba Lazare Herve","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issues site on Grid with Ubay=3D54.9V ,The FME TX Fulbert (6=
54266068) from Huawei is informed.","vanel.mbiada@matech-cameroun.com","158=
","01-07-2025 21:21:57","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005384837","NYO=
M FACE MAETUR","","01-07-2025 21:01:44","01-07-2025 21:01:41","01-07-2025 2=
1:02:41","Grid fluctuation , site went down because Gen failed to start due=
 to Grid bad voltage; landlord refuses that we deploy the MGE (gen Noise) /=
/ Grid stabilised","Fabrice Pouakam","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","Grid fluctuation , site went down becau=
se Gen failed to start due to Grid bad voltage; landlord refuses that we de=
ploy the MGE (gen Noise) // Grid stabilised","gerard.tchangoue@matech-camer=
oun.com","5","01-07-2025 21:01:44","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005384608","SIM=
BOCK BONAMBAPE","","01-07-2025 20:35:39","01-07-2025 20:34:32","01-07-2025 =
20:36:40","Grid outage, Site went down before Gen start due to poor backup =
// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.co=
m","69","01-07-2025 20:35:39","MATECH CMR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0005384474","Sou=
s Prefecture","","01-07-2025 20:20:56","01-07-2025 20:19:25","01-07-2025 20=
:48:04","Grid outage, Site went down due to cable which powered PWC has bur=
ned //we reconnected the cable and site on grid ","Fanda Brice","Equipment =
Repair","Passive","Infrastructure","Armoured Cable","Grid outage, Site went=
 down due to cable which powered PWC has burned //we reconnected the cable =
and site on grid ","gerard.tchangoue@matech-cameroun.com","92","01-07-2025 =
20:20:56","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005384141","Par=
adis Hotel","","01-07-2025 19:21:28","01-07-2025 19:19:21","01-07-2025 22:1=
6:34","Grid fluctuations, site went down because Gen Overload (12.5Kva, 100=
A) SS IHS BLAISE RAOUL ETCHEU is confirmed // Site stabilised","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctua=
tions, site went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RA=
OUL ETCHEU is confirmed // Site stabilised","gerard.tchangoue@matech-camero=
un.com","128","01-07-2025 19:21:28","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0005384121","M=
fou EPC","","01-07-2025 19:15:05","01-07-2025 19:12:53","01-07-2025 22:26:1=
0","Grid outage, site went down because gen started and stopped due to wate=
r infiltration in injection pump // He purged the injection pump and Gen ma=
nually started","Mba Lazare Herve","Fuel Outage (Probable)","Passive","ACDG=
 Gen","ACDG - Injector Pump","Grid outage, site went down because gen start=
ed and stopped due to water infiltration in injection pump // He purged the=
 injection pump and Gen manually started","vanel.mbiada@matech-cameroun.com=
","134","01-07-2025 19:15:05","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005384100","B=
arriere","","01-07-2025 19:09:14","01-07-2025 19:05:08","01-07-2025 19:25:0=
0","Grid outage, site went down because gen start and stopped with high tem=
p alarm // He opened the doors and manually started the gen","Hyemafo Gilda=
s","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, si=
te went down because gen start and stopped with high temp alarm // He opene=
d the doors and manually started the gen","vanel.mbiada@matech-cameroun.com=
","248","01-07-2025 19:09:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005383706","Mambine"=
,"","01-07-2025 18:06:22","01-07-2025 17:57:52","01-07-2025 18:37:47","Casc=
aded Incident from TTO5555386","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because Gen s=
tarted and stopped with ""low oil pressure"" alarm// He added oil and start=
ed Gen manualy","system","266868","01-07-2025 18:06:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005383707","Nkongtoc=
k","","01-07-2025 18:06:22","01-07-2025 17:57:52","01-07-2025 18:37:47","Ca=
scaded Incident from TTO5555386","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen started and stopped with ""low oil pressure"" alarm// He added oil and=
 started Gen manualy","system","266868","01-07-2025 18:06:22","MATECH CMR"
"Closed Complete","Site Down","CTR_066","IHS_YND_367","NOCINC0005383669","M=
andoumba OCM","IHS_YND_350, IHS_YND_349","01-07-2025 18:05:15","01-07-2025 =
17:57:52","01-07-2025 18:37:47","Grid outage, Site went down because Gen st=
arted and stopped with ""low oil pressure"" alarm// He added oil and starte=
d Gen manualy","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","A=
CDG - Oil Pressure Sensor Faulty","Grid outage, Site went down because Gen =
started and stopped with ""low oil pressure"" alarm// He added oil and star=
ted Gen manualy","gerard.tchangoue@matech-cameroun.com","444","01-07-2025 1=
8:05:15","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005383662","N=
GONA","","01-07-2025 18:03:41","01-07-2025 17:58:28","01-07-2025 18:31:00",=
"Active//No power issue Site is on Grid and Ubaie =3D55.8V The Tx FME Lione=
l Adjep (655184876)from Huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue Site is on Grid and Ubaie =3D55.8V The Tx FME Lionel=
 Adjep (655184876)from Huawei is informed","gerard.tchangoue@matech-camerou=
n.com","315","01-07-2025 18:03:41","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005383566","N=
kolbi-Boss","","01-07-2025 17:52:25","01-07-2025 17:50:15","01-07-2025 18:1=
5:13","Grid outage, site went down before gen start due to poor battery bac=
kup // gen start manually","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down before gen start due to poor battery backup // gen start manually",=
"vanel.mbiada@matech-cameroun.com","131","01-07-2025 17:52:25","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005383539","MBA=
LNGONG LYCEE","","01-07-2025 17:52:03","01-07-2025 17:47:53","01-07-2025 18=
:03:58","Grid outage,Site went down because Gen stopped due to overload(9kv=
a, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda =
Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge,Site went down because Gen stopped due to overload(9kva, 130A) SS IHS Fe=
lix Zambe is informed and confirmed//Grid return","gerard.tchangoue@matech-=
cameroun.com","252","01-07-2025 17:52:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0005383468","Garbati =
building","","01-07-2025 17:36:03","01-07-2025 17:33:12","01-07-2025 17:35:=
22","Cascaded Incident from TTO5555155","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","system","=
268324","01-07-2025 17:36:03","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005383464","HOP=
ITAL DE LA CAISSE","IHS_YND_024","01-07-2025 17:35:19","01-07-2025 17:33:12=
","01-07-2025 17:35:22","Grid outage, Site went down before Gen start due t=
o poor backup // Gen started automatically","Delor Telezing","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","gerard.tchangoue@matech-cameroun.com","128","01-07-2025 17:35:19","M=
ATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005383338","Evo=
doula MTN","","01-07-2025 17:24:03","01-07-2025 17:23:57","01-07-2025 18:05=
:41","Grid outage, Site went down before Gen start due to poor backup// GRI=
D return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// GRID return","gerard.tchangoue@matech-cameroun=
.com","7","01-07-2025 17:24:03","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005383099","B=
arriere IHS","","01-07-2025 16:46:44","01-07-2025 16:44:33","01-07-2025 19:=
33:21","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed","Hyemafo Gildas","Equipment Repair","Passive","DC=
DG Gen","DCDG - Overload","Grid outage; Site went Down due to Gen overload(=
15Kva, 200A) SS IHS FELIX ZAMBE is informed","vanel.mbiada@matech-cameroun.=
com","133","01-07-2025 16:46:44","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005382979","Aka=
k-Nkozoa-MTN-IHS","","01-07-2025 16:27:16","01-07-2025 16:26:00","01-07-202=
5 17:58:03","Site went down due to plan work (secures the transmission) on =
site done by Felix Bateu (IHS) // End of work","Fabrice Pouakam","Installat=
ion Activity","Passive","Planned Activity","Installation Activity","Site we=
nt down due to plan work (secures the transmission) on site done by Felix B=
ateu (IHS) // End of work","gerard.tchangoue@matech-cameroun.com","78","01-=
07-2025 16:27:16","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005382787","OBA=
M NGOLA OCM","","01-07-2025 15:46:26","01-07-2025 15:44:16","01-07-2025 16:=
51:54","(Unstable site) Grid outage,site went down due to Gen overload(15kv=
a//340A)SS IHS Francois is informed // SIte stabilised","MINKA NICOLAS","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","(Unstable site) Gri=
d outage,site went down due to Gen overload(15kva//340A)SS IHS Francois is =
informed // SIte stabilised","gerard.tchangoue@matech-cameroun.com","132","=
01-07-2025 15:46:26","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005382590","OBA=
M NGOLA OCM","","01-07-2025 15:20:48","01-07-2025 15:18:40","01-07-2025 15:=
24:18","Grid outage,site went down due to Gen overload(15kva//340A)SS IHS F=
rancois is informed // SIte stabilised","MINKA NICOLAS","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage,site went down due to G=
en overload(15kva//340A)SS IHS Francois is informed // SIte stabilised","ge=
rard.tchangoue@matech-cameroun.com","130","01-07-2025 15:20:48","MATECH CMR=
"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005382531","Par=
adis Hotel","","01-07-2025 15:15:26","01-07-2025 15:14:21","01-07-2025 18:5=
8:58","Site went down due to Theft of AC cable (Access security work is in =
progress) Blaise Raoul IHS supervisor on site. //  He replaced the AC cable=
 and site is on Grid","Siligap Boris","Site Asset Theft","Theft","Theft","A=
C Cable Stolen","Site went down due to Theft of AC cable (Access security w=
ork is in progress) Blaise Raoul IHS supervisor on site. //  He replaced th=
e AC cable and site is on Grid","gerard.tchangoue@matech-cameroun.com","67"=
,"01-07-2025 15:15:26","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005382427","ESS=
OS OASIS 1111","","01-07-2025 14:54:30","01-07-2025 14:53:22","01-07-2025 1=
6:57:32","(Unstable site) Grid outage,Site went down because Gen overload (=
17kva, 250A)// Grid return","Siligap Boris","Equipment Repair","Passive","D=
CDG Gen","DCDG - Overload","(Unstable site) Grid outage,Site went down beca=
use Gen overload (17kva, 250A)// Grid return","gerard.tchangoue@matech-came=
roun.com","70","01-07-2025 14:54:30","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005382419","Ebo=
go","","01-07-2025 14:52:38","01-07-2025 14:50:31","01-07-2025 14:55:27","A=
ctive// No Power issue on site Ubaie 56V site on Grid, Julien /693095849 fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issue =
on site Ubaie 56V site on Grid, Julien /693095849 from Huawei is informed",=
"gerard.tchangoue@matech-cameroun.com","129","01-07-2025 14:52:38","MATECH =
CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005382365","M=
eyo","IHS_YND_257, IHS_YND_762","01-07-2025 14:44:51","01-07-2025 14:42:43"=
,"01-07-2025 19:38:46","Grid outage, site went down due to Gen overload (17=
KVA, 260A) SS HIS Felix Zambe is informed and confirmed","Hyemafo Gildas","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site=
 went down due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed=
 and confirmed","vanel.mbiada@matech-cameroun.com","130","01-07-2025 14:44:=
51","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005382364","A=
hala","","01-07-2025 14:44:20","01-07-2025 14:42:43","01-07-2025 19:32:42",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down due to Gen overload (17KVA, 260A) SS H=
IS Felix Zambe is informed and confirmed","vanel.mbiada@matech-cameroun.com=
","285665","01-07-2025 14:44:20","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005382360","N=
kolfon Cimencam","","01-07-2025 14:43:40","01-07-2025 14:42:43","01-07-2025=
 19:32:42","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down due to Gen overload (17KVA,=
 260A) SS HIS Felix Zambe is informed and confirmed","vanel.mbiada@matech-c=
ameroun.com","285665","01-07-2025 14:43:40","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005382184","ESS=
OS OASIS 1111","","01-07-2025 14:17:30","01-07-2025 14:16:22","01-07-2025 1=
4:31:43","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) // Grid returned","cedric.tiani@matech-cameroun.com","69","01-07-2025 1=
4:17:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_052","NOCINC0005381857","Nyahoo",=
"","01-07-2025 13:33:27","01-07-2025 13:14:00","01-07-2025 13:37:05","Casca=
ded Incident from TTO5553272","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue, site is on Grid =
with Ubaie=3D55.1V, Gregoire (654547479) from Huawei is informed.Noticed th=
at Gregoire Appiah is working on site at EZEZANG(T0211)","system","262356",=
"01-07-2025 13:33:27","MATECH CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0005381821","Mel=
en Ba'aba","","01-07-2025 13:24:09","01-07-2025 13:16:01","01-07-2025 13:35=
:16","Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Ju=
lien(693095849) from Huawei is informed","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Julien(6930958=
49) from Huawei is informed","cedric.tiani@matech-cameroun.com","491","01-0=
7-2025 13:24:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_532","NOCINC0005381820","NKOLOSSA=
N OKOK","","01-07-2025 13:23:52","01-07-2025 13:14:00","01-07-2025 13:37:05=
","Cascaded Incident from TTO5553272","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue, site is on Grid wit=
h Ubaie=3D55.1V, Gregoire (654547479) from Huawei is informed.Noticed that =
Gregoire Appiah is working on site at EZEZANG(T0211)","system","262356","01=
-07-2025 13:23:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_408","NOCINC0005381819","Evodoula=
 MTN","","01-07-2025 13:23:52","01-07-2025 13:14:00","01-07-2025 13:37:05",=
"Cascaded Incident from TTO5553272","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue, site is on=
 Grid with Ubaie=3D55.1V, Gregoire (654547479) from Huawei is informed.Noti=
ced that Gregoire Appiah is working on site at EZEZANG(T0211)","system","26=
2355","01-07-2025 13:23:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0005381818","NYANON/D=
EMBO","","01-07-2025 13:23:51","01-07-2025 13:14:00","01-07-2025 13:37:05",=
"Cascaded Incident from TTO5553272","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue, site is on=
 Grid with Ubaie=3D55.1V, Gregoire (654547479) from Huawei is informed.Noti=
ced that Gregoire Appiah is working on site at EZEZANG(T0211)","system","26=
2357","01-07-2025 13:23:51","MATECH CMR"
"Closed Complete","Site Down","T0573","IHS_YND_387","NOCINC0005381788","Tal=
la Monatele","IHS_EDA_102, IHS_YND_408, IHS_EDA_052, IHS_YND_532","01-07-20=
25 13:18:09","01-07-2025 13:14:00","01-07-2025 13:37:05","No power issue, s=
ite is on Grid with Ubaie=3D55.1V, Gregoire (654547479) from Huawei is info=
rmed.Noticed that Gregoire Appiah is working on site at EZEZANG(T0211)","Pa=
rker Tchoup","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","No power issue, site is on Grid with Ubaie=3D55.1V=
, Gregoire (654547479) from Huawei is informed.Noticed that Gregoire Appiah=
 is working on site at EZEZANG(T0211)","cedric.tiani@matech-cameroun.com","=
250","01-07-2025 13:18:09","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005381722","ESS=
OS OASIS 1111","","01-07-2025 13:05:15","01-07-2025 13:03:59","01-07-2025 1=
3:52:26","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned	","Siligap Boris","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, Site went down because Gen overload (17kva, 2=
50A) // Grid returned	","cedric.tiani@matech-cameroun.com","78","01-07-2025=
 13:05:15","MATECH CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0005381635","M=
atomb","","01-07-2025 12:57:06","01-07-2025 12:53:48","01-07-2025 13:00:04"=
,"No power issue on site.Site on grid with Ubaie=3D54.2 V site on gen ,The =
TX FME Etienne(695033981) from Huawei is informed.","Kemeni Franklin","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site.Site on grid with Ubaie=3D54.2 V site on gen =
,The TX FME Etienne(695033981) from Huawei is informed.","edwige.kapawo@mat=
ech-cameroun.com","198","01-07-2025 12:57:06","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005381467","E=
SSOS OASIS 1111","","01-07-2025 12:27:42","01-07-2025 12:26:59","01-07-2025=
 12:42:27","Grid outage, Site went down because Gen overload (17kva, 250A) =
// Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Grid outage, Site went down because Gen overload (17kva, =
250A) // Grid returned","edwige.kapawo@matech-cameroun.com","45","01-07-202=
5 12:27:42","MATECH CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0005381227","B=
otmakak","","01-07-2025 11:48:36","01-07-2025 11:46:59","01-07-2025 11:53:5=
2","Active// No power issue, Site on Gen Ubai=3D 54V, The Tx Etienne (69503=
3981/Huawei) is informed","Kemeni Franklin","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power i=
ssue, Site on Gen Ubai=3D 54V, The Tx Etienne (695033981/Huawei) is informe=
d","edwige.kapawo@matech-cameroun.com","98","01-07-2025 11:48:36","MATECH C=
MR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005381219","N=
koabang2","","01-07-2025 11:47:12","01-07-2025 11:44:05","01-07-2025 12:00:=
55","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // He reduced load, Gen started manually","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
, site went down due to gen overload (22KVA, 330A), SS Blaise IHS is inform=
ed // He reduced load, Gen started manually","edwige.kapawo@matech-cameroun=
.com","189","01-07-2025 11:47:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005381216","Akak-Nko=
zoa-MTN-IHS","","01-07-2025 11:47:04","01-07-2025 11:39:28","01-07-2025 11:=
44:22","Cascaded Incident from TTO5552621","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","BATE  ( IHS Supervisor / =
677549887 ) it's in the site to protect transmission  //  End Of Work ","sy=
stem","275154","01-07-2025 11:47:04","MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0005381012","Nko=
lmvack","","01-07-2025 11:17:43","01-07-2025 11:10:33","01-07-2025 11:32:06=
","Site went down because gen start and stopped with alarm low oil pressure=
//he added 2L oil and started the gen","Parker Tchoup","Equipment Repair","=
Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down because gen s=
tart and stopped with alarm low oil pressure//he added 2L oil and started t=
he gen","cedric.tiani@matech-cameroun.com","431","01-07-2025 11:17:43","MAT=
ECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005380968","Lad=
a I Yde","","01-07-2025 11:15:53","01-07-2025 11:09:37","01-07-2025 13:02:2=
1","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypassed the Grid and Gen manually started","Mba=
 Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation site went down because Gen and started and s=
topped due to Grid bad voltage // He bypassed the Grid and Gen manually sta=
rted","cedric.tiani@matech-cameroun.com","378","01-07-2025 11:15:53","MATEC=
H CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0005380729","Nko=
lmvack","","01-07-2025 10:37:27","01-07-2025 10:31:18","01-07-2025 10:59:54=
","Site went down because gen start and stopped with alarm low oil pressure=
//he added 2L oil and started the gen","Parker Tchoup","Equipment Repair","=
Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down because gen s=
tart and stopped with alarm low oil pressure//he added 2L oil and started t=
he gen","cedric.tiani@matech-cameroun.com","370","01-07-2025 10:37:27","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005380653","Melen Ba=
'aba","","01-07-2025 10:23:04","01-07-2025 10:20:25","01-07-2025 12:33:11",=
"Grid outage,site went down because Gen failed to start due to Generator be=
lt cut//He replaced and site on Gen","Siligap Boris","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Fan Belt","Grid outage,site went down because Gen=
 failed to start due to Generator belt cut//He replaced and site on Gen","s=
ystem","159","01-07-2025 10:23:04","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005380645","M=
EHANDAN","","01-07-2025 10:21:35","01-07-2025 10:20:25","01-07-2025 12:49:3=
7","Grid outage, site went down because gen ran until fuel shortage // Refu=
eling done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid outage, site went down because gen ran until fuel shortage // Refue=
ling done","edwige.kapawo@matech-cameroun.com","75","01-07-2025 10:21:35","=
MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005380559","Nko=
abang2","","01-07-2025 10:00:55","01-07-2025 09:56:42","01-07-2025 11:32:20=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // He reduced load, Gen started manually","Mba Lazare Herv=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, =
site went down due to gen overload (22KVA, 330A), SS Blaise IHS is informed=
 // He reduced load, Gen started manually","cedric.tiani@matech-cameroun.co=
m","258","01-07-2025 10:00:55","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005380504","M=
vog-Ebanda","","01-07-2025 09:56:02","01-07-2025 09:41:59","01-07-2025 09:5=
5:29","Cascaded site ","Siligap Boris","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","Cascaded site ","edwige.kapawo@matech-cameroun.com=
","325297","01-07-2025 09:56:02","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005380464","A=
bom","IHS_YND_269","01-07-2025 09:51:12","01-07-2025 09:41:59","01-07-2025 =
09:55:33","Active//No power issue, site is on Grid with Ubaie=3D53,0V The T=
X Symphorien / 675295205/ Huawei is informed","Siligap Boris","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue, site is on Grid with Ubaie=3D53,0V The TX Symphorien=
 / 675295205/ Huawei is informed","edwige.kapawo@matech-cameroun.com","554"=
,"01-07-2025 09:51:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005380275","Mfou EPC=
","","01-07-2025 09:22:24","01-07-2025 09:13:52","01-07-2025 09:36:54","Cas=
caded Incident from TTO5551559","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //GEN automatically started","system","269559","0=
1-07-2025 09:22:24","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005380267","M=
fou OCM","IHS_YND_674","01-07-2025 09:21:26","01-07-2025 09:13:52","01-07-2=
025 09:36:54","Grid Outage, Site Down before gen Started due to poor backup=
 //GEN automatically started","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down be=
fore gen Started due to poor backup //GEN automatically started","edwige.ka=
pawo@matech-cameroun.com","455","01-07-2025 09:21:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0005380231","Garbati =
building","","01-07-2025 09:13:49","01-07-2025 09:09:41","01-07-2025 09:11:=
48","Cascaded Incident from TTO5551508","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","system","=
262737","01-07-2025 09:13:49","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005380224","HOP=
ITAL DE LA CAISSE","IHS_YND_024","01-07-2025 09:12:57","01-07-2025 09:09:41=
","01-07-2025 09:11:48","Grid outage, Site went down before Gen start due t=
o poor backup // Gen started automatically","Delor Telezing","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","cedric.tiani@matech-cameroun.com","197","01-07-2025 09:12:57","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005380176","M=
ontee-Des-Soeurs","","01-07-2025 09:09:51","01-07-2025 09:07:41","01-07-202=
5 09:14:46","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","edwige.kapawo@matech-cameroun.com","132","01-07-2025 09:09:51"=
,"MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005380157","Ron=
d Point Express1114","","01-07-2025 09:05:50","01-07-2025 09:04:39","01-07-=
2025 09:19:03","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Grid return","cedric.tiani@matech-cameroun.c=
om","73","01-07-2025 09:05:50","MATECH CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0005380148","Nsi=
meyong Terre Rouge","","01-07-2025 09:04:34","01-07-2025 09:03:23","01-07-2=
025 09:05:38","Grid outage, Site went downt before Gen start due to poor ba=
ttery backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, Site went downt =
before Gen start due to poor battery backup // Grid return","cedric.tiani@m=
atech-cameroun.com","73","01-07-2025 09:04:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_393","NOCINC0005380130","Ezezang"=
,"","01-07-2025 08:59:22","01-07-2025 08:48:18","01-07-2025 08:59:12","Casc=
aded Incident from TTO5551380","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue, Site impacted by Nkog-Edze=
n_ctr_041 not managed by IHS","system","264001","01-07-2025 08:59:22","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_409","NOCINC0005380131","Evodoula=
 OCM","","01-07-2025 08:59:22","01-07-2025 08:48:18","01-07-2025 08:59:12",=
"Cascaded Incident from TTO5551380","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue, Site impac=
ted by Nkog-Edzen_ctr_041 not managed by IHS","system","264005","01-07-2025=
 08:59:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0005380127","Okola OC=
M","","01-07-2025 08:59:21","01-07-2025 08:48:18","01-07-2025 08:59:12","Ca=
scaded Incident from TTO5551380","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue, Site impacted=
 by Nkog-Edzen_ctr_041 not managed by IHS","system","264006","01-07-2025 08=
:59:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005380129","SAA 2","=
","01-07-2025 08:59:21","01-07-2025 08:48:18","01-07-2025 08:59:12","Cascad=
ed Incident from TTO5551380","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue, Site impacted by Nkog-Edzen_=
ctr_041 not managed by IHS","system","264004","01-07-2025 08:59:21","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0005380128","Saa","",=
"01-07-2025 08:59:21","01-07-2025 08:48:18","01-07-2025 08:59:12","Cascaded=
 Incident from TTO5551380","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue, Site impacted by Nkog-Edzen_ct=
r_041 not managed by IHS","system","264003","01-07-2025 08:59:21","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0005380126","Talla Mo=
natele","","01-07-2025 08:59:21","01-07-2025 08:48:18","01-07-2025 08:59:12=
","Cascaded Incident from TTO5551380","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue, Site impacted by Nk=
og-Edzen_ctr_041 not managed by IHS","system","264007","01-07-2025 08:59:21=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0005380125","Monatele=
","","01-07-2025 08:59:20","01-07-2025 08:48:18","01-07-2025 08:59:12","Cas=
caded Incident from TTO5551380","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue, Site impacted by Nkog-Edz=
en_ctr_041 not managed by IHS","system","264002","01-07-2025 08:59:20","MAT=
ECH CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0005380107","N=
yanon","IHS_YND_406, IHS_YND_387, IHS_YND_338, IHS_YND_405, IHS_YND_404, IH=
S_YND_393, IHS_YND_409","01-07-2025 08:55:30","01-07-2025 08:48:18","01-07-=
2025 08:59:12","No power issue, Site impacted by Nkog-Edzen_ctr_041 not man=
aged by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Activ=
e","Active Equipment Failure","Affected by 3rd Party Site","No power issue,=
 Site impacted by Nkog-Edzen_ctr_041 not managed by IHS","edwige.kapawo@mat=
ech-cameroun.com","435","01-07-2025 08:55:30","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005380086","NYO=
M FACE MAETUR","","01-07-2025 08:52:33","01-07-2025 08:50:15","01-07-2025 0=
9:26:48","ACCESS ISSUES Grid fluctuation , site went down because Gen faile=
d to start due to Grid bad voltage // Grid stabilisation note that :( the l=
andlord refuses that we deploy the MG; DO is informed)","Fabrice Pouakam","=
Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue - L=
and Lord","Grid fluctuation , site went down because Gen failed to start du=
e to Grid bad voltage // Grid stabilisation note that :( the landlord refus=
es that we deploy the MG; DO is informed)","cedric.tiani@matech-cameroun.co=
m","141","01-07-2025 08:52:33","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0005380085","H=
-Paradis","","01-07-2025 08:52:05","01-07-2025 08:42:59","01-07-2025 09:31:=
29","Grid Outage, No space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No space =
to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","547","01=
-07-2025 08:52:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_088","NOCINC0005379977","Elobi Mo=
kolo","","01-07-2025 08:29:46","01-07-2025 08:20:59","01-07-2025 08:30:01",=
"Cascaded Incident from TTO5551205","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran until fuel shortage // Refueling done","system","287014","01-07-2=
025 08:29:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_085","NOCINC0005379978","Briquete=
rie","","01-07-2025 08:29:46","01-07-2025 08:20:59","01-07-2025 08:30:01","=
Cascaded Incident from TTO5551205","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage, site went down because gen ran unti=
l fuel shortage // Refueling done","system","287014","01-07-2025 08:29:46",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0005379947","K=
amajou Building","IHS_YND_088, IHS_YND_085","01-07-2025 08:21:13","01-07-20=
25 08:20:59","01-07-2025 08:30:01","Grid outage, site went down because gen=
 ran until fuel shortage // Refueling done","Paul BIBOUM","Fuel Outage","Pa=
ssive","Diesel","Diesel Outage","Grid outage, site went down because gen ra=
n until fuel shortage // Refueling done","edwige.kapawo@matech-cameroun.com=
","16","01-07-2025 08:21:13","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005379587","Evo=
doula MTN","","01-07-2025 07:37:36","01-07-2025 07:36:27","01-07-2025 07:59=
:58","Grid outage, Site went down before Gen start due to poor backup// GRI=
D return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// GRID return","cedric.tiani@matech-cameroun.com=
","70","01-07-2025 07:37:36","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005379464","A=
wae Ewonkan","","01-07-2025 07:06:24","01-07-2025 07:04:15","01-07-2025 09:=
20:59","(Unstable site)	Grid outage site went down due to Gen Overload (20K=
va, Iload 225 A)IHS SS Alphonse is informed//Site stabilised","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","(Unstable sit=
e)	Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IHS S=
S Alphonse is informed//Site stabilised","edwige.kapawo@matech-cameroun.com=
","131","01-07-2025 07:06:24","MATECH CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0005379227","M=
volye-New","","01-07-2025 05:47:21","01-07-2025 05:44:15","01-07-2025 05:49=
:31","Active// No power Issue Site on Grid Ubaie =3D51.6V, The TX FME Mbah =
Hosiah (674007438) is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","ctive// No power Issue Site =
on Grid Ubaie =3D51.6V, The TX FME Mbah Hosiah (674007438) is informed","lo=
ic.noumsi@matech-cameroun.com","188","01-07-2025 05:47:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005379216","MEHANDAN=
","","01-07-2025 05:38:56","01-07-2025 05:34:31","01-07-2025 07:34:19","Cas=
caded Incident from TTO5550406","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction //He reset it and started the =
Gen manually","system","265","01-07-2025 05:38:56","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005379208","O=
dza II OCM","IHS_YND_528","01-07-2025 05:37:39","01-07-2025 05:34:31","01-0=
7-2025 07:36:28","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction //He reset it and started the Gen manually","Albr=
an Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overl=
oaded","Grid outage, site went down because gen failed to start due to PWC =
ZTE malfunction //He reset it and started the Gen manually","loic.noumsi@ma=
tech-cameroun.com","192","01-07-2025 05:37:39","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005378917","Men=
dong3","","01-07-2025 03:52:59","01-07-2025 03:51:46","01-07-2025 09:43:53"=
,"Grid Outage No space to deploy a MDGE //Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid Outage No space to =
deploy a MDGE //Grid return","loic.noumsi@matech-cameroun.com","75","01-07-=
2025 03:52:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005378645","EBOM",""=
,"01-07-2025 02:00:06","01-07-2025 01:55:20","01-07-2025 02:08:23","Cascade=
d Incident from TTO5549775","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down due to Gen ov=
erload (15KVA, 350A) //Site stabilized","system","266960","01-07-2025 02:00=
:06","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005378642","A=
hala","IHS_YND_698","01-07-2025 01:59:26","01-07-2025 01:55:20","01-07-2025=
 02:08:23","Grid outage, Site went down due to Gen overload (15KVA, 350A) /=
/Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Grid outage, Site went down due to Gen overload (15KVA, 3=
50A) //Site stabilized","loic.noumsi@matech-cameroun.com","247","01-07-2025=
 01:59:26","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005378628","C=
rf-Nsam","","01-07-2025 01:57:51","01-07-2025 01:55:59","01-07-2025 01:58:4=
0","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","loic.noumsi@matech-cameroun.com","114","0=
1-07-2025 01:57:51","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005378083","Evo=
doula MTN","","30-06-2025 23:19:11","30-06-2025 23:16:03","30-06-2025 23:22=
:42","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Grid return","loic.noumsi@matech-cameroun.co=
m","189","30-06-2025 23:19:11","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005378021","NYO=
M FACE MAETUR","","30-06-2025 23:07:30","30-06-2025 23:06:23","30-06-2025 2=
3:07:39","Grid fluctuation , site went down because Gen failed to start due=
 to Grid bad voltage; landlord refuses that we deploy the MGE (gen Noise) /=
/ Grid stabilised","Fabrice Pouakam","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","Grid fluctuation , site went down becau=
se Gen failed to start due to Grid bad voltage; landlord refuses that we de=
ploy the MGE (gen Noise) // Grid stabilised","loic.noumsi@matech-cameroun.c=
om","70","30-06-2025 23:07:30","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005377776","SIM=
BOCK BONAMBAPE","","30-06-2025 22:08:07","30-06-2025 22:07:59","30-06-2025 =
22:11:57","Grid outage, Site went down before Gen start due to poor backup =
// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","cedric.tiani@matech-cameroun.com","=
9","30-06-2025 22:08:07","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005377645","S=
IMBOCK BONAMBAPE","","30-06-2025 21:46:42","30-06-2025 21:44:03","30-06-202=
5 21:47:52","Grid outage, Site went down before Gen start due to poor backu=
p // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Grid outage, Site went down before Gen =
start due to poor backup // Site stabilised","vanel.mbiada@matech-cameroun.=
com","160","30-06-2025 21:46:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005377510","MEHANDAN=
","","30-06-2025 21:21:16","30-06-2025 21:19:09","30-06-2025 21:25:23","Cas=
caded Incident from TTO5548508","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Grid stabilized","system","=
127","30-06-2025 21:21:16","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005377506","O=
dza II OCM","IHS_YND_528","30-06-2025 21:20:29","30-06-2025 21:19:09","30-0=
6-2025 21:25:23","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Grid =
stabilized","vanel.mbiada@matech-cameroun.com","83","30-06-2025 21:20:29","=
MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005377278","E=
foulan","","30-06-2025 20:28:59","30-06-2025 20:26:49","30-06-2025 20:39:46=
","	Site went down due to work of BIGANCE (650631358) of DOWEN  on site (Sw=
app of PWC)// end of work","MINKA NICOLAS","Installation Activity","Passive=
","Planned Activity","Installation Activity","	Site went down due to work o=
f BIGANCE (650631358) of DOWEN  on site (Swapp of PWC)// end of work","vane=
l.mbiada@matech-cameroun.com","131","30-06-2025 20:28:59","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005377260","S=
IMBOCK BONAMBAPE","","30-06-2025 20:25:15","30-06-2025 20:22:05","30-06-202=
5 20:27:19","Grid outage, Site went down before Gen start due to poor backu=
p // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Grid outage, Site went down before Gen =
start due to poor backup // Site stabilised","vanel.mbiada@matech-cameroun.=
com","191","30-06-2025 20:25:15","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005377193","C=
omplexe-BEAC","","30-06-2025 20:11:56","30-06-2025 20:07:41","30-06-2025 20=
:13:58","	No power issue on site ,site on Grid with U=3D54V Tx FME Lionnel/=
/ 655184876 from Huawei is informed.Noticed dysjuction at BTS OCM","Albran =
Byorel","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","	No power issue on site ,site on Grid with U=3D54V Tx F=
ME Lionnel// 655184876 from Huawei is informed.Noticed dysjuction at BTS OC=
M","vanel.mbiada@matech-cameroun.com","256","30-06-2025 20:11:56","MATECH C=
MR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005377170","S=
IMBOCK BONAMBAPE","","30-06-2025 20:03:33","30-06-2025 20:02:11","30-06-202=
5 20:05:44","Grid outage, Site went down before Gen start due to poor backu=
p // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Grid outage, Site went down before Gen =
start due to poor backup // Site stabilised","vanel.mbiada@matech-cameroun.=
com","84","30-06-2025 20:03:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005376916","MEHANDAN=
","","30-06-2025 19:42:40","30-06-2025 19:25:37","30-06-2025 20:34:09","Cas=
caded Incident from TTO5547828","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction //He reset it and started the =
Gen manually","system","1218002","30-06-2025 19:42:40","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005376882","Odz=
a II OCM","IHS_YND_528","30-06-2025 19:35:00","30-06-2025 19:25:37","30-06-=
2025 20:34:46","Grid outage, site went down because gen failed to start due=
 to PWC ZTE malfunction //He reset it and started the Gen manually","Albran=
 Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Grid outage, site went down because gen failed to start due to PWC ZT=
E malfunction //He reset it and started the Gen manually","cedric.tiani@mat=
ech-cameroun.com","566","30-06-2025 19:35:00","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005376798","C=
omplexe-BEAC","","30-06-2025 19:17:54","30-06-2025 19:11:29","30-06-2025 19=
:27:12","No power issue on site ,site on Grid with U=3D51V Tx FME Lionnel//=
 655184876 from Huawei is informed.Noticed dysjuction at BTS OCM","Albran B=
yorel","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site ,site on Grid with U=3D51V Tx FME=
 Lionnel// 655184876 from Huawei is informed.Noticed dysjuction at BTS OCM"=
,"vanel.mbiada@matech-cameroun.com","387","30-06-2025 19:17:54","MATECH CMR=
"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005376562","B=
arriere","","30-06-2025 18:29:55","30-06-2025 18:29:46","30-06-2025 19:08:5=
3","Grid outage, site went down because gen start and stopped with high tem=
p alarm // He opened the doors  and manually started  the gen","Hyemafo Gil=
das","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, site went down because gen start and stoppe=
d with high temp alarm // He opened the doors  and manually started  the ge=
n","vanel.mbiada@matech-cameroun.com","10","30-06-2025 18:29:55","MATECH CM=
R"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005376544","E=
SSOS OASIS 1111","","30-06-2025 18:26:33","30-06-2025 18:24:13","30-06-2025=
 18:37:50","Grid outage, Site went down because Gen overload (17kva, 250A) =
//Grid return	","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) //Grid return	","vanel.mbiada@matech-cameroun.com","142","30-06-2025 18=
:26:33","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005376456","Nko=
mo stade","","30-06-2025 18:08:13","30-06-2025 18:07:02","30-06-2025 18:13:=
31","Grid outage, Site went down before Gen start due to poor backup/ // Gr=
id return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup/ // Grid return","cedric.tiani@matech-cameroun.com","73=
","30-06-2025 18:08:13","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005376380","E=
SSOS OASIS 1111","","30-06-2025 17:52:00","30-06-2025 17:50:45","30-06-2025=
 18:05:19","Grid outage, Site went down because Gen overload (17kva, 250A)/=
/ Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage, Site went down because Gen overload (17kva, 250=
A)// Grid return","vanel.mbiada@matech-cameroun.com","77","30-06-2025 17:52=
:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0005376304","Mamch Bu=
ilding","","30-06-2025 17:42:56","30-06-2025 17:39:53","30-06-2025 17:50:42=
","Cascaded Incident from TTO5547160","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, no space to deploy =
MGE// Grid return","system","260852","30-06-2025 17:42:56","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005376298","C=
harles-Atangana","IHS_YND_051","30-06-2025 17:42:06","30-06-2025 17:39:53",=
"30-06-2025 17:59:23","Grid outage, no space to deploy MGE// Grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage, no space to deploy MGE// Grid return","vanel.mbiada@matech-cameroun=
.com","135","30-06-2025 17:42:06","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005375815","A=
wae Ewonkan","","30-06-2025 16:43:28","30-06-2025 16:42:21","30-06-2025 16:=
44:55","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed","Albran Byorel","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage site went down due to Gen Overload=
 (20Kva, Iload 225 A)IHS SS Alphonse is informed","vanel.mbiada@matech-came=
roun.com","69","30-06-2025 16:43:28","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005375792","Acc=
acia New","","30-06-2025 16:39:34","30-06-2025 16:34:21","30-06-2025 17:42:=
04","Grid outage, no space to deploy MGE //Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage, no space t=
o deploy MGE //Grid return","cedric.tiani@matech-cameroun.com","315","30-06=
-2025 16:39:34","MATECH CMR"
"Closed Complete","Site Down","T2795","IHS_YND_070","NOCINC0005375631","Efo=
ulan","","30-06-2025 16:10:16","30-06-2025 16:07:04","30-06-2025 16:55:03",=
"Site went down due to work of BIGANCE (650631358) of DOWEN on site (Swapp =
of PWC)// end of work","MINKA NICOLAS","Installation Activity","Passive","P=
lanned Activity","Installation Activity","Site went down due to work of BIG=
ANCE (650631358) of DOWEN on site (Swapp of PWC)// end of work","cedric.tia=
ni@matech-cameroun.com","193","30-06-2025 16:10:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_157","NOCINC0005375565","MVAN",""=
,"30-06-2025 15:57:27","30-06-2025 15:48:32","30-06-2025 16:27:28","Cascade=
d Incident from TTO5546329","MINKA NICOLAS","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site U=3D54,5v site on Grid=
 Tx FME Lionel (655184876) of huawei is informed","system","267423","30-06-=
2025 15:57:27","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005375546","A=
wae Ewonkan","","30-06-2025 15:53:43","30-06-2025 15:52:31","30-06-2025 15:=
55:42","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","vanel.mbiada@matech-cameroun.com","74","30-06-2025 15:53:43","MATECH =
CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0005375520","M=
VAN SACEL","IHS_YND_157","30-06-2025 15:50:17","30-06-2025 15:48:32","30-06=
-2025 16:27:28","No power issue on site U=3D54,5v site on Grid Tx FME Lione=
l (655184876) of huawei is informed","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site U=3D54,5v site on Grid Tx FME Lionel (655184876) of huawei is =
informed","vanel.mbiada@matech-cameroun.com","107","30-06-2025 15:50:17","M=
ATECH CMR"
"Closed Complete","Site Down","T0920","IHS_YND_416","NOCINC0005375472","Ngw=
opi Boga","","30-06-2025 15:39:33","30-06-2025 15:30:59","30-06-2025 16:46:=
27","No power issue, site is on grid with Ubaie=3D54.9V; TX FME Etienne Fop=
a (693961474) from HUAWEI is informed","Kemeni Franklin","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue, site is on grid with Ubaie=3D54.9V; TX FME Etienne Fopa (69396147=
4) from HUAWEI is informed","cedric.tiani@matech-cameroun.com","515","30-06=
-2025 15:39:33","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005375388","Par=
adis Hotel","","30-06-2025 15:22:26","30-06-2025 10:42:11","01-07-2025 11:1=
8:10","Grid outage,site went down because  Gen  Cable that leaves the Gen t=
o the Shelter is  stolen//He replaced it .Noticed that  Gen Overload (12.5K=
va, 100A) SS IHS BLAISE RAOUL ETCHEU is confirmed","Siligap Boris","Site As=
set Theft","Theft","Theft","AC Cable Stolen","Grid outage,site went down be=
cause  Gen  Cable that leaves the Gen to the Shelter is  stolen//He replace=
d it .Noticed that  Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL ETCHEU=
 is confirmed","cedric.tiani@matech-cameroun.com","16816","30-06-2025 15:22=
:26","MATECH CMR"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0005375271","E=
zezang","","30-06-2025 15:00:31","30-06-2025 14:50:59","30-06-2025 15:03:36=
","Grid outage, site went down because gen failed to start due to battery g=
en faulty // Gen manually with external battery","Parker Tchoup","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, site=
 went down because gen failed to start due to battery gen faulty // Gen man=
ually with external battery","vanel.mbiada@matech-cameroun.com","573","30-0=
6-2025 15:00:31","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0005375109","SAA=
 2","","30-06-2025 14:25:01","30-06-2025 14:19:46","30-06-2025 14:21:37","G=
rid outage, site went down because gen start and stopped with high temp ala=
rm // He oppened the doors and Gen manually started","Parker Tchoup","Equip=
ment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level =
Issue","Grid outage, site went down because gen start and stopped with high=
 temp alarm // He oppened the doors and Gen manually started","cedric.tiani=
@matech-cameroun.com","317","30-06-2025 14:25:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005374948","ELOUMDEM=
 CARRIERE 2","","30-06-2025 13:52:41","30-06-2025 13:48:09","30-06-2025 13:=
54:41","Cascaded Incident from TTO5545696","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid returned","system","1216773","30=
-06-2025 13:52:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005374947","Eto koss=
 Yde","","30-06-2025 13:52:41","30-06-2025 13:48:09","30-06-2025 13:54:41",=
"Cascaded Incident from TTO5545696","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Grid returned","system","1216773","30-06-202=
5 13:52:41","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005374942","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","30-06-2025 13:51:18","30-06-2025 13:48=
:09","30-06-2025 13:54:41","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","Fanda Brice","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Grid returned","edwige.kapawo@mat=
ech-cameroun.com","192","30-06-2025 13:51:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0005374726","Talla Mo=
natele","","30-06-2025 13:14:13","30-06-2025 12:51:46","30-06-2025 13:13:00=
","Cascaded Incident from TTO5545443","Parker Tchoup","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site went down due to work of Fe=
lix BATEU SS IHS is on site( secure the transmission) //End of work","syste=
m","1220016","30-06-2025 13:14:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_409","NOCINC0005374728","Evodoula=
 OCM","","30-06-2025 13:14:13","30-06-2025 12:51:46","30-06-2025 13:13:00",=
"Cascaded Incident from TTO5545443","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Site went down due to w=
ork of Felix BATEU SS IHS is on site( secure the transmission) //End of wor=
k","system","1220016","30-06-2025 13:14:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0005374727","Monatele=
 MTN","","30-06-2025 13:14:13","30-06-2025 12:51:46","30-06-2025 13:13:00",=
"Cascaded Incident from TTO5545443","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work of Feli=
x BATEU SS IHS is on site( secure the transmission) //End of work","system"=
,"1220017","30-06-2025 13:14:13","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0005374691","B=
iyemassi LAC","","30-06-2025 13:08:55","30-06-2025 13:00:44","30-06-2025 13=
:09:57","Grid only site, no space to deploy MDGE// grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site,=
 no space to deploy MDGE// grid return","gerard.tchangoue@matech-cameroun.c=
om","493","30-06-2025 13:08:55","MATECH CMR"
"Closed Complete","Site Down","T0715","IHS_YND_406","NOCINC0005374612","Mon=
atele","IHS_YND_387, IHS_YND_407, IHS_YND_409","30-06-2025 12:54:00","30-06=
-2025 12:51:46","30-06-2025 13:45:14","Site went down due to work of Felix =
BATEU SS IHS is on site( secure the transmission) //End of work","Parker Tc=
houp","Installation Activity","Passive","Planned Activity","Installation Ac=
tivity","Site went down due to work of Felix BATEU SS IHS is on site( secur=
e the transmission) //End of work","edwige.kapawo@matech-cameroun.com","135=
","30-06-2025 12:54:00","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005374490","M=
ontee-Jouvence-II","","30-06-2025 12:37:39","30-06-2025 12:36:29","30-06-20=
25 13:28:36","(Very unstable) Site went down due to insuffuciency of rectif=
ier//He added one rectifier","Hyemafo Gildas","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","(Very unstable) Site went down due to insuf=
fuciency of rectifier//He added one rectifier","gerard.tchangoue@matech-cam=
eroun.com","73","30-06-2025 12:37:39","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005374449","Nko=
lfoulou CSD MTN","","30-06-2025 12:31:05","30-06-2025 12:27:58","30-06-2025=
 13:18:57","Active//No power issue site is on Grid with Ubaie=3D53,4 V site=
 on gen The Tx FME Syphorien //675295205 from Huawei is informed","Siligap =
Boris","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No power issue site is on Grid with Ubaie=3D53,4=
 V site on gen The Tx FME Syphorien //675295205 from Huawei is informed","e=
dwige.kapawo@matech-cameroun.com","188","30-06-2025 12:31:05","MATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0005374351","BIY=
EMASSI NIKI","","30-06-2025 12:17:36","30-06-2025 12:15:25","30-06-2025 13:=
09:34","Grid outage,Site went down because Gen failed to start due to Grid =
contactor not excited//He excited the Grid contactor and site on Grid","Hye=
mafo Gildas","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","=
Grid outage,Site went down because Gen failed to start due to Grid contacto=
r not excited//He excited the Grid contactor and site on Grid","edwige.kapa=
wo@matech-cameroun.com","132","30-06-2025 12:17:36","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005374117","C=
rf-Nsam","","30-06-2025 11:42:03","30-06-2025 11:32:47","30-06-2025 11:48:0=
1","Active//No power issue on site Ubaie =3D56.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D56.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","55=
8","30-06-2025 11:42:03","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005374035","Ron=
d Point Express1114","","30-06-2025 11:32:14","30-06-2025 11:28:59","30-06-=
2025 11:46:11","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Grid returned","edwige.kapawo@matech-camer=
oun.com","196","30-06-2025 11:32:14","MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0005373757","B=
astos Bir","","30-06-2025 10:48:57","30-06-2025 10:45:53","30-06-2025 11:01=
:48","No power issue, site is on Gen with Ubaie=3D53.2 V site on grid ,TX f=
me Eloundou bertrant(652586578) from Huawei is informed","Mboua Thierry","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue, site is on Gen with Ubaie=3D53.2 V site on grid ,=
TX fme Eloundou bertrant(652586578) from Huawei is informed","gerard.tchang=
oue@matech-cameroun.com","186","30-06-2025 10:48:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005373751","Nsam esc=
ale LP","","30-06-2025 10:47:34","30-06-2025 10:22:59","30-06-2025 10:28:44=
","Cascaded Incident from TTO5544240","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Grid return","system","265539","30-06-2025 10:47:34",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0005373730","H=
-Paradis","","30-06-2025 10:43:07","30-06-2025 10:37:39","30-06-2025 11:23:=
10","Grid outage// He deployed MDG of 13KVA","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid outage// He deployed MDG of 1=
3KVA","gerard.tchangoue@matech-cameroun.com","329","30-06-2025 10:43:07","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005373636","M=
ontee-Jouvence-II","","30-06-2025 10:27:13","30-06-2025 10:26:03","30-06-20=
25 10:27:43","Grid fluctuation, Site went down because gen fails to start d=
ue to grid bad voltage// Eneo Stabilised","Hyemafo Gildas","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,=
 Site went down because gen fails to start due to grid bad voltage// Eneo S=
tabilised","gerard.tchangoue@matech-cameroun.com","71","30-06-2025 10:27:13=
","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005373613","Nsa=
m Sofavinc","IHS_YND_732","30-06-2025 10:25:43","30-06-2025 10:22:59","30-0=
6-2025 10:28:44","Grid Outage, Site went down before Gen start due to poor =
backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before =
Gen start due to poor backup // Grid return","edwige.kapawo@matech-cameroun=
.com","165","30-06-2025 10:25:43","MATECH CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0005373206","R=
d-Pt-Express","","30-06-2025 09:20:14","30-06-2025 09:14:55","30-06-2025 11=
:32:59","Grid only, Site wen Down due to Eneo Outage (no space to deployed =
MGE) // Grid returned","","Grid Supply","Passive","Grid","National Grid - G=
rid Outage Issue","Grid only, Site wen Down due to Eneo Outage (no space to=
 deployed MGE) // Grid returned","edwige.kapawo@matech-cameroun.com","320",=
"30-06-2025 09:20:14","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005373004","Par=
adis Hotel","","30-06-2025 08:40:34","30-06-2025 08:39:59","30-06-2025 10:3=
1:55","Grid fluctuations, site went down because Gen Overload (12.5Kva, 100=
A) SS IHS BLAISE RAOUL ETCHEU is confirmed//Site stabilised","Siligap Boris=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuati=
ons, site went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOU=
L ETCHEU is confirmed//Site stabilised","edwige.kapawo@matech-cameroun.com"=
,"36","30-06-2025 08:40:34","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005372978","NYO=
M FACE MAETUR","","30-06-2025 08:31:17","30-06-2025 08:30:10","30-06-2025 0=
8:51:59","Grid fluctuation , site went down because Gen failed to start due=
 to Grid bad voltage; landlord refuses that we deploy the MGE (gen Noise) /=
/ Grid return","Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord=
 Related Issues","Access Issue - Land Lord","Grid fluctuation , site went d=
own because Gen failed to start due to Grid bad voltage; landlord refuses t=
hat we deploy the MGE (gen Noise) // Grid return","edwige.kapawo@matech-cam=
eroun.com","69","30-06-2025 08:31:17","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0005372966","B=
iyemassi LAC","","30-06-2025 08:28:30","30-06-2025 08:25:21","30-06-2025 11=
:31:31","Grid only site, no space to deploy MDGE // Grid returned","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only si=
te, no space to deploy MDGE // Grid returned","gerard.tchangoue@matech-came=
roun.com","191","30-06-2025 08:28:30","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0005372748","Nko=
zoa","","30-06-2025 07:45:08","30-06-2025 07:43:00","30-06-2025 08:50:33","=
Grid outage,gen failed to start due to card Ge faulty//He reset gen card an=
d gen manually started","Fabrice Pouakam","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage,gen failed to start due to card =
Ge faulty//He reset gen card and gen manually started","edwige.kapawo@matec=
h-cameroun.com","131","30-06-2025 07:45:08","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005372730","N=
kolfon Cimencam","","30-06-2025 07:42:05","30-06-2025 07:39:57","30-06-2025=
 07:44:33","Site is impacted by Afanoya II(Not manage by HIS)","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","Site is impacted by Afanoya II(Not manage by HIS)"=
,"gerard.tchangoue@matech-cameroun.com","130","30-06-2025 07:42:05","MATECH=
 CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005372651","Evo=
doula MTN","","30-06-2025 07:18:22","30-06-2025 07:15:11","30-06-2025 07:36=
:06"," Grid outage, Site went down before Gen start due to poor backup// Ge=
n Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low"," Grid outage, Site wen=
t down before Gen start due to poor backup// Gen Automatically Started","ed=
wige.kapawo@matech-cameroun.com","193","30-06-2025 07:18:22","MATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0005372593","BIY=
EMASSI NIKI","","30-06-2025 07:02:57","30-06-2025 07:01:49","30-06-2025 07:=
08:21","Site went down because Gen started and stopped due to CB Gen (32A) =
tripped due to Grid bad voltage// He rearmed CB Gen, Site on Gen","Hyemafo =
Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Site=
 went down because Gen started and stopped due to CB Gen (32A) tripped due =
to Grid bad voltage// He rearmed CB Gen, Site on Gen","edwige.kapawo@matech=
-cameroun.com","70","30-06-2025 07:02:57","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0005372592","B=
iyemassi LAC","","30-06-2025 07:02:12","30-06-2025 06:59:51","30-06-2025 07=
:06:23","Grid only site, no space to deploy MDGE // Grid returned","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only si=
te, no space to deploy MDGE // Grid returned","gerard.tchangoue@matech-came=
roun.com","143","30-06-2025 07:02:12","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0005372543","Clu=
b France","","30-06-2025 06:48:31","30-06-2025 06:47:24","30-06-2025 11:32:=
29","Grid only site, no space to deploy MGE // Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid only site, no =
space to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","68=
","30-06-2025 06:48:31","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005372350","Par=
adis Hotel","","30-06-2025 05:50:45","30-06-2025 05:48:35","30-06-2025 07:3=
0:42","Grid fluctuations, site went down because Gen Overload (12.5Kva, 100=
A) SS IHS BLAISE RAOUL ETCHEU is confirmed // Grid stabilized","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctua=
tions, site went down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RA=
OUL ETCHEU is confirmed // Grid stabilized","christelle.ngonga@matech-camer=
oun.com","131","30-06-2025 05:50:45","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005372275","Ron=
d Point Express1114","","30-06-2025 05:25:38","30-06-2025 05:19:30","30-06-=
2025 06:45:14","Grid outage.gen start and stopped due to alarm""high temp""=
//We added water and gen manually started","Hyemafo Gildas","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","G=
rid outage.gen start and stopped due to alarm""high temp""//We added water =
and gen manually started","christelle.ngonga@matech-cameroun.com","369","30=
-06-2025 05:25:38","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005372216","NKO=
MKANA ELIZA HOTEL","","30-06-2025 04:59:39","28-06-2025 16:44:18","28-06-20=
25 17:16:04","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","christelle.ngonga@ma=
tech-cameroun.com","130521","30-06-2025 04:59:39","MATECH CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0005372188","E=
mombo-Tchad","IHS_YND_114","30-06-2025 04:50:54","30-06-2025 04:42:39","30-=
06-2025 05:06:56","No power issue on site Ubaie=3D54,1V site on Grid , The =
Tx FME Leonel/ 694693436/ from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site Ubaie=3D54,1V site on Grid , The Tx FME Leonel/ 694693436/ fr=
om Huawei is informed","christelle.ngonga@matech-cameroun.com","497","30-06=
-2025 04:50:54","MATECH CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0005372185","K=
ondengui","","30-06-2025 04:50:05","30-06-2025 04:42:39","30-06-2025 05:06:=
56","","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascade =
Active","Grid outage, no space to deploy MGE // grid power return","christe=
lle.ngonga@matech-cameroun.com","264192","30-06-2025 04:50:05","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0005372158","Y=
oko OCM","","30-06-2025 04:37:33","26-06-2025 01:04:34","28-06-2025 07:45:0=
7","Batracking  No power issue on site U =3D 53.7 V site on Grid TX FME Gre=
goire / 654547479 is informed.","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Batracking  No =
power issue on site U =3D 53.7 V site on Grid TX FME Gregoire / 654547479 i=
s informed.","christelle.ngonga@matech-cameroun.com","358381","30-06-2025 0=
4:37:33","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005372147","O=
dza II OCM","","30-06-2025 04:32:26","28-06-2025 13:46:20","28-06-2025 18:5=
5:57","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","christelle.ngonga@matech-cameroun.com","139566","30-06-2025 0=
4:32:26","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005372101","O=
dza II OCM","","30-06-2025 04:14:14","28-06-2025 19:01:42","28-06-2025 19:1=
9:04","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","christelle.ngonga@matech-cameroun.com","119556","30-06-2025 0=
4:14:14","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005372062","Ron=
d Point Express1114","","30-06-2025 03:46:56","30-06-2025 03:44:48","30-06-=
2025 03:52:42","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen start automatically","christ=
elle.ngonga@matech-cameroun.com","129","30-06-2025 03:46:56","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005371508","N=
simalen OCM","","30-06-2025 00:27:46","30-06-2025 00:26:34","30-06-2025 01:=
00:40","Grid outage, Site connected on the DG MTN . site went down because =
Gen stopped with high temp alarm due to radiator drilled // Gen radiator gl=
ued and water added, Gen manually started.","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - High Engine Temp - Radiator Leakage","Grid=
 outage, Site connected on the DG MTN . site went down because Gen stopped =
with high temp alarm due to radiator drilled // Gen radiator glued and wate=
r added, Gen manually started.","christelle.ngonga@matech-cameroun.com","73=
","30-06-2025 00:27:46","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005371446","Nko=
lbisson IITA LP","","30-06-2025 00:08:52","29-06-2025 23:59:35","30-06-2025=
 00:15:19","Site  impacted by Nkolbisson 2 ocm not manage by IHS","","Custo=
mer Equipment Failure","Active","Active Equipment Failure","Affected by 3rd=
 Party Site","Site  impacted by Nkolbisson 2 ocm not manage by IHS","christ=
elle.ngonga@matech-cameroun.com","558","30-06-2025 00:08:52","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005371432","Nsi=
malen MTN","","30-06-2025 00:03:24","29-06-2025 23:59:58","30-06-2025 01:06=
:45","Grid outage, site went down because Gen stopped with  high temp alarm=
 due to radiator drilled  //  Gen radiator glued and  water added,  Gen man=
ually started.","Albran Byorel","Equipment Repair","Passive","ACDG Gen","AC=
DG - High Engine Temp - Radiator Leakage","Grid outage, site went down beca=
use Gen stopped with  high temp alarm due to radiator drilled  //  Gen radi=
ator glued and  water added,  Gen manually started.","christelle.ngonga@mat=
ech-cameroun.com","322","30-06-2025 00:03:24","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005371319","A=
kak-Nkozoa-MTN-IHS","","29-06-2025 23:34:51","29-06-2025 22:09:59","29-06-2=
025 23:35:03","Backtraking : No power issue Ubaie:53.5V site on Grid, TX fm=
e symphorien /650257151 from huawei is informed.","Fabrice Pouakam","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Backtraking : No power issue Ubaie:53.5V site on Grid, TX fme symphori=
en /650257151 from huawei is informed.","christelle.ngonga@matech-cameroun.=
com","5095","29-06-2025 23:34:51","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005371159","Nko=
abang2","","29-06-2025 22:45:54","29-06-2025 22:41:27","30-06-2025 05:55:09=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed //  All load  reduced  and Gen started manually","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, site went down due to gen overload (22KVA, 330A), SS Blaise IHS is i=
nformed //  All load  reduced  and Gen started manually","christelle.ngonga=
@matech-cameroun.com","269","29-06-2025 22:45:54","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005370858","NYO=
M FACE MAETUR","","29-06-2025 21:42:08","29-06-2025 21:39:11","29-06-2025 2=
3:08:45","Grid fluctuation , site went down because Gen failed to start due=
 to Grid bad voltage  // Grid stabilisation  note that :( the landlord refu=
ses that we deploy the MG; DO is informed)","Fabrice Pouakam","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on , site went down because Gen failed to start due to Grid fluctuation  //=
 Grid stabilisation  note that :( the landlord refuses that we deploy the M=
G; DO is informed)","loic.noumsi@matech-cameroun.com","179","29-06-2025 21:=
42:08","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005370742","A=
kak-Nkozoa-MTN-IHS","","29-06-2025 21:26:51","29-06-2025 21:20:42","29-06-2=
025 22:08:38","Grid fluctuations, site went down because Gen failed to star=
t due to Grid bad voltage // Site stabilised","Fabrice Pouakam","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tions, site went down because Gen failed to start due to Grid bad voltage /=
/ Site stabilised","loic.noumsi@matech-cameroun.com","371","29-06-2025 21:2=
6:51","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005370583","Nko=
abang2","","29-06-2025 20:58:28","29-06-2025 20:53:15","29-06-2025 22:03:47=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // He reduced load, Gen started manually","Mba Lazare Herv=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, =
site went down due to gen overload (22KVA, 330A), SS Blaise IHS is informed=
 // He reduced load, Gen started manually","loic.noumsi@matech-cameroun.com=
","315","29-06-2025 20:58:28","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005370536","M=
ontee-Des-Soeurs","","29-06-2025 20:53:45","29-06-2025 20:53:37","29-06-202=
5 21:53:42","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","gaelle.njiofack@matech-cameroun.com","10","29-06-2025 20:53:45=
","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005370440","Nsi=
malen MTN","","29-06-2025 20:39:02","29-06-2025 20:37:53","29-06-2025 21:11=
:04","Grid outage, site went down because Gen failed to start with alarm hi=
gh temp // He added water in the radiator and Gen manually started","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp -=
 Coolant Level Issue","Grid outage, site went down because Gen failed to st=
art with alarm high temp // He added water in the radiator and Gen manually=
 started","loic.noumsi@matech-cameroun.com","70","29-06-2025 20:39:02","MAT=
ECH CMR"
"Closed Complete","Warning","T0055","IHS_YND_328","NOCINC0005370369","Nsima=
len MTN","","29-06-2025 20:23:27","","","Grid outage, site went down becaus=
e Gen failed to start with alarm high temp // He added water in the radiato=
r and Gen manually started","Albran Byorel","Warning","Warning","POWER","Wa=
rning - Gen Temp High","Grid outage, site went down because Gen failed to s=
tart with alarm high temp // He added water in the radiator and Gen manuall=
y started","loic.noumsi@matech-cameroun.com","3","29-06-2025 20:23:27","MAT=
ECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005370289","NYO=
M FACE MAETUR","","29-06-2025 20:03:04","29-06-2025 20:00:58","29-06-2025 2=
1:08:17","Grid fluctuation , site went down because Gen failed to start due=
 to Grid bad voltage; waiting Grid return because the landlord refuses that=
 we deploy the MG; DO is informed","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuation , site=
 went down because Gen failed to start due to Grid bad voltage; waiting Gri=
d return because the landlord refuses that we deploy the MG; DO is informed=
","loic.noumsi@matech-cameroun.com","127","29-06-2025 20:03:04","MATECH CMR=
"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005370234","NYO=
M FACE MAETUR","","29-06-2025 19:53:01","29-06-2025 19:28:51","29-06-2025 1=
9:29:14","Grid outage, Site went down because Gen failed to start due to Gr=
id bad voltage //Grid stabilised","Fabrice Pouakam","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid outage, Site went d=
own because Gen failed to start due to Grid bad voltage //Grid stabilised",=
"loic.noumsi@matech-cameroun.com","1452","29-06-2025 19:53:01","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005370217","NYO=
M FACE MAETUR","","29-06-2025 19:50:39","29-06-2025 18:11:30","29-06-2025 1=
8:50:54","Eneo fluctuations, Site went down because gen fails to start due =
to Grid fluctuations //Grid stabilisation","Fabrice Pouakam","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Eneo fluctuatio=
ns, Site went down because gen fails to start due to Grid fluctuations //Gr=
id stabilisation","loic.noumsi@matech-cameroun.com","5950","29-06-2025 19:5=
0:39","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005370198","NYO=
M FACE MAETUR","","29-06-2025 19:47:27","29-06-2025 17:40:09","29-06-2025 1=
7:42:41","Backtracking//Grid outage, Site went down because Gen failed to s=
tart due to Grid bad voltage //Grid stabilised","Fabrice Pouakam","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Backtracki=
ng//Grid outage, Site went down because Gen failed to start due to Grid bad=
 voltage //Grid stabilised","loic.noumsi@matech-cameroun.com","7640","29-06=
-2025 19:47:27","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005370103","SIM=
BOCK BONAMBAPE","","29-06-2025 19:27:20","29-06-2025 19:25:12","29-06-2025 =
19:27:40","Grid outage, Site went down before Gen start due to poor backup =
// Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Site stabilised","loic.noumsi@matech-cameroun=
.com","129","29-06-2025 19:27:20","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005369805","N=
koabang2","","29-06-2025 18:30:34","29-06-2025 18:29:21","29-06-2025 19:14:=
00","Site went down due to Absence of one eneo phase // Bridge made between=
 the two remaining phases","Mba Lazare Herve","Grid Supply","Passive","Grid=
","National Grid - Grid Incomplete Phase","Site went down due to Absence of=
 one eneo phase // Bridge made between the two remaining phases","gaelle.nj=
iofack@matech-cameroun.com","75","29-06-2025 18:30:34","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005369781","Ebo=
go","","29-06-2025 18:24:53","29-06-2025 18:20:44","29-06-2025 18:23:10","A=
ctive// No Power issue on site Ubaie 56.2V site on Grid, Julien /693095849 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issu=
e on site Ubaie 56.2V site on Grid, Julien /693095849 from Huawei is inform=
ed","loic.noumsi@matech-cameroun.com","251","29-06-2025 18:24:53","MATECH C=
MR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005369574","M=
ontee-Des-Soeurs","","29-06-2025 18:02:03","29-06-2025 18:00:57","29-06-202=
5 18:38:53","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site went down due to Gen overload (15 KVA/210 A)=
 // Grid return","gaelle.njiofack@matech-cameroun.com","68","29-06-2025 18:=
02:03","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005369564","NKO=
NGKARAK","","29-06-2025 17:59:55","29-06-2025 17:56:51","29-06-2025 18:02:1=
2","Grid outage, Site went down because Gen started and stopped due to High=
 temp alarm //He added water and Gen start manually","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, Site went down because Gen started and stop=
ped due to High temp alarm //He added water and Gen start manually","loic.n=
oumsi@matech-cameroun.com","185","29-06-2025 17:59:55","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005369221","Evo=
doula MTN","","29-06-2025 16:53:15","29-06-2025 16:51:08","29-06-2025 17:03=
:54"," Grid outage, Site went down before Gen start due to poor backup // G=
rid return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low"," Grid outage, Site went down before=
 Gen start due to poor backup // Grid return","gaelle.njiofack@matech-camer=
oun.com","128","29-06-2025 16:53:15","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0005369100","O=
mnisport 3","","29-06-2025 16:33:28","29-06-2025 16:30:20","29-06-2025 16:3=
8:41","Grid outage, site went down because Gen failed to start due to ''Und=
erfrequency'' alarm // He reset card and started Gen manually","Delor Telez=
ing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage, site went down because Gen failed to start due to ''Underfrequency''=
 alarm // He reset card and started Gen manually","loic.noumsi@matech-camer=
oun.com","189","29-06-2025 16:33:28","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005368947","NYO=
M FACE MAETUR","","29-06-2025 16:14:29","29-06-2025 16:12:15","29-06-2025 1=
7:11:41","Eneo fluctuations, Site went down because gen failed to start due=
 to Grid fluctuations //Grid stabilisation","Fabrice Pouakam","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Eneo fluctuati=
ons, Site went down because gen failed to start due to Grid fluctuations //=
Grid stabilisation","loic.noumsi@matech-cameroun.com","136","29-06-2025 16:=
14:29","MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005368858","Mvo=
g Betsi Hospital","","29-06-2025 15:55:12","29-06-2025 15:50:05","29-06-202=
5 15:56:20","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","loic.noumsi@matech-cameroun.com",=
"307","29-06-2025 15:55:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005368828","Eto koss=
 Yde","","29-06-2025 15:49:09","29-06-2025 15:46:25","29-06-2025 15:53:35",=
"Cascaded Incident from TTO5538831","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before G=
en started due poor battery backup // Gen Started Automatically	","system",=
"1217064","29-06-2025 15:49:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005368829","ELOUMDEM=
 CARRIERE 2","","29-06-2025 15:49:09","29-06-2025 15:46:25","29-06-2025 15:=
53:35","Cascaded Incident from TTO5538831","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
efore Gen started due poor battery backup // Gen Started Automatically	","s=
ystem","1217063","29-06-2025 15:49:10","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005368821","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","29-06-2025 15:47:31","29-06-2025 15:46=
:25","29-06-2025 15:53:35","Grid outage, site went down before Gen started =
due poor battery backup // Gen Started Automatically	","Fanda Brice","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down before Gen started due poor battery backup // Gen St=
arted Automatically	","loic.noumsi@matech-cameroun.com","69","29-06-2025 15=
:47:31","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005368588","O=
bili Carrefour","","29-06-2025 15:05:11","29-06-2025 14:52:04","29-06-2025 =
17:00:12","	Grid fluctuation, site went down because Gen started and stoppe=
d due to Grid bad voltage // Grid stabilized","Paul BIBOUM","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","	Grid fluctuatio=
n, site went down because Gen started and stopped due to Grid bad voltage /=
/ Grid stabilized","olivier.kwedi@ihstowers.com","788","29-06-2025 15:05:11=
","MATECH CMR"
"Closed Complete","Site Down","T1113","IHS_YND_105","NOCINC0005368547","Omn=
isport 3","","29-06-2025 14:53:15","29-06-2025 14:52:10","29-06-2025 15:36:=
12","Grid outage, site went down because Gen failed to start due to ''Under=
frequency'' alarm // He reset card and started Gen manually","Delor Telezin=
g","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, site went down because Gen failed to start due to ''Underfrequency'' a=
larm // He reset card and started Gen manually","loic.noumsi@matech-camerou=
n.com","66","29-06-2025 14:53:15","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005368541","Nom=
ayos montee Meche","","29-06-2025 14:52:21","29-06-2025 14:50:14","29-06-20=
25 15:48:30","Grid outage site went down before gen start due to poor batte=
ry backup // Grid return","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage site went down before =
gen start due to poor battery backup // Grid return","loic.noumsi@matech-ca=
meroun.com","128","29-06-2025 14:52:21","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005368320","Ako=
k Ndoe Yde","","29-06-2025 14:14:09","29-06-2025 14:12:04","29-06-2025 14:1=
5:34","Grid outage site went down before gen start due to poor battery back=
up // Geen auatomatically started","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage site went =
down before gen start due to poor battery backup // Geen auatomatically sta=
rted","loic.noumsi@matech-cameroun.com","126","29-06-2025 14:14:09","MATECH=
 CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0005368039","Mvo=
g-Betsi","","29-06-2025 13:22:52","29-06-2025 13:18:33","29-06-2025 14:00:0=
8","Grid outage, site went down due to PWC ZTE dysfunctionning // Grid retu=
rned","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier =
Module Overloaded","Grid outage, site went down due to PWC ZTE dysfunctionn=
ing // Grid returned","cedric.tiani@matech-cameroun.com","260","29-06-2025 =
13:22:52","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005368025","Fla=
menco","","29-06-2025 13:18:19","29-06-2025 13:09:10","29-06-2025 14:42:17"=
,"Grid outage, site went down due to insufficiency of rectifier // He added=
 01 rectifier, Site on GEN","Mboua Thierry","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Grid outage, site went down due to insufficie=
ncy of rectifier // He added 01 rectifier, Site on GEN","cedric.tiani@matec=
h-cameroun.com","550","29-06-2025 13:18:19","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005367965","Ako=
k Ndoe Yde","","29-06-2025 13:03:48","29-06-2025 13:00:20","29-06-2025 13:0=
3:18","Grid outage, Site went down before Gen start due to poor backup// Ge=
n automatically Started","Hyemafo Gildas","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup// Gen automatically Started","cedric.tiani@=
matech-cameroun.com","209","29-06-2025 13:03:48","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005367796","Odz=
a Minkan IHS","","29-06-2025 12:25:46","29-06-2025 12:23:36","29-06-2025 14=
:47:57","Grid outage, site went down because Gen failed to start due to wat=
er infiltration in the tank//We purged and gen manually started","Albran By=
orel","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Wat=
er In The Fuel","Grid outage, site went down because Gen failed to start du=
e to water infiltration in the tank//We purged and gen manually started","c=
edric.tiani@matech-cameroun.com","131","29-06-2025 12:25:46","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005367676","S=
IMBOCK BONAMBAPE","","29-06-2025 11:56:13","29-06-2025 11:54:04","29-06-202=
5 11:59:23","Grid outage, Site went down before Gen start due to poor backu=
p // Gen started automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Gen started automatically","vanel=
.mbiada@matech-cameroun.com","130","29-06-2025 11:56:13","MATECH CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0005367674","M=
vog-Betsi","","29-06-2025 11:55:21","29-06-2025 11:53:09","29-06-2025 11:59=
:19","Grid outage site went down because Gen failed to start due PWC ZTE dy=
sfonction //He bypassed it and started the Gen manuallly","Hyemafo Gildas",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gri=
d outage site went down because Gen failed to start due PWC ZTE dysfonction=
 //He bypassed it and started the Gen manuallly","vanel.mbiada@matech-camer=
oun.com","133","29-06-2025 11:55:21","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005367567","O=
bili Carrefour","","29-06-2025 11:31:39","29-06-2025 11:30:25","29-06-2025 =
11:32:42","Grid fluctuation, site went down because Gen started and stopped=
 due to Grid bad voltage// Grid stabilized","Paul BIBOUM","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, =
site went down because Gen started and stopped due to Grid bad voltage// Gr=
id stabilized","vanel.mbiada@matech-cameroun.com","75","29-06-2025 11:31:39=
","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005367562","Mai=
son komkana New","","29-06-2025 11:29:47","29-06-2025 11:23:40","29-06-2025=
 12:09:39","Grid outage,site went down because gen failed to start due to n=
o battery GE //Gen manually started with external battery","Mboua Thierry",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid ou=
tage,site went down because gen failed to start due to no battery GE //Gen =
manually started with external battery","cedric.tiani@matech-cameroun.com",=
"368","29-06-2025 11:29:47","MATECH CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0005367543","M=
vog-Betsi","","29-06-2025 11:23:20","29-06-2025 11:20:13","29-06-2025 11:45=
:27","Grid outage site went down because Gen failed to start due PWC ZTE dy=
sfonction //He bypassed it and started the Gen manuallly","Hyemafo Gildas",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gri=
d outage site went down because Gen failed to start due PWC ZTE dysfonction=
 //He bypassed it and started the Gen manuallly","vanel.mbiada@matech-camer=
oun.com","188","29-06-2025 11:23:20","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005367524","Evo=
doula MTN","","29-06-2025 11:19:11","29-06-2025 11:13:01","29-06-2025 11:21=
:34","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","cedr=
ic.tiani@matech-cameroun.com","371","29-06-2025 11:19:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0005367472","Bastos-B=
AT","","29-06-2025 11:10:36","29-06-2025 11:04:46","29-06-2025 13:06:17","C=
ascaded Incident from TTO5537295","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","
Access issues due to landlord Grid outage, site went down because Gen faile=
d to start (investigation ongoing) // Grid return
","system","270031","29-06-2025 11:10:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0005367471","Dragage"=
,"","29-06-2025 11:10:36","29-06-2025 11:04:46","29-06-2025 13:06:17","Casc=
aded Incident from TTO5537295","Mboua Thierry","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","
Access issues due to landlord Grid outage, site went down because Gen faile=
d to start (investigation ongoing) // Grid return
","system","270030","29-06-2025 11:10:36","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005367458","M=
ontee-Des-Soeurs","","29-06-2025 11:07:03","29-06-2025 10:59:52","29-06-202=
5 15:52:27","Grid outage ,site down due to Gen overload (15 KVA/210 A)","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage ,site down due to Gen overload (15 KVA/210 A) // grid return","va=
nel.mbiada@matech-cameroun.com","433","29-06-2025 11:07:03","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005367456","Odz=
a Minkan IHS","","29-06-2025 11:06:47","29-06-2025 11:01:29","29-06-2025 11=
:53:18","Grid fluctuations, Site went down because Gen failed to start due =
to Grid bad voltage,no rcp // He bypassed Grid and started Gen manually","A=
lbran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuations, Site went down because Gen failed to start =
due to Grid bad voltage,no rcp // He bypassed Grid and started Gen manually=
","cedric.tiani@matech-cameroun.com","319","29-06-2025 11:06:47","MATECH CM=
R"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005367451","ARM=
P Building","IHS_YND_192, IHS_YND_129","29-06-2025 11:05:54","29-06-2025 11=
:04:46","29-06-2025 13:06:17","Access issues due to landlord Grid outage, s=
ite went down because Gen failed to start (investigation ongoing) // Grid r=
eturn","Mboua Thierry","Access Denial","Lease Or Legal","Landlord Related I=
ssues","Access Issue - Land Lord","
Access issues due to landlord Grid outage, site went down because Gen faile=
d to start (investigation ongoing) // Grid return
","cedric.tiani@matech-cameroun.com","69","29-06-2025 11:05:54","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005367413","ELOUMDEM=
 CARRIERE 2","","29-06-2025 10:55:40","29-06-2025 10:53:38","29-06-2025 10:=
59:23","Cascaded Incident from TTO5537249","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
efore Gen started due poor battery backup // Gen Started Automatically","sy=
stem","263625","29-06-2025 10:55:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005367412","Eto koss=
 Yde","","29-06-2025 10:55:40","29-06-2025 10:53:38","29-06-2025 10:59:23",=
"Cascaded Incident from TTO5537249","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before G=
en started due poor battery backup // Gen Started Automatically","system","=
263626","29-06-2025 10:55:40","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005367407","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","29-06-2025 10:54:46","29-06-2025 10:53=
:38","29-06-2025 10:59:23","Grid outage, site went down before Gen started =
due poor battery backup // Gen Started Automatically","Fanda Brice","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage, site went down before Gen started due poor battery backup // Gen Sta=
rted Automatically","cedric.tiani@matech-cameroun.com","71","29-06-2025 10:=
54:46","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005367399","Nom=
ayos montee Meche","","29-06-2025 10:54:18","29-06-2025 10:53:09","29-06-20=
25 10:56:43","Grid outage, site went down before Gen started due poor batte=
ry backup // Gen Started Automatically","Fanda Brice","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down before Gen started due poor battery backup // Gen Started Automatic=
ally","cedric.tiani@matech-cameroun.com","71","29-06-2025 10:54:18","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0005367197","B=
astos Bir","","29-06-2025 10:13:29","29-06-2025 10:07:14","29-06-2025 11:19=
:00","No power issue, site is on Gen with Ubaie=3D53.3 V site on grid ,TX f=
me Eloundou bertrant(652586578) from Huawei is informed","Mboua Thierry","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue, site is on Gen with Ubaie=3D53.3 V site on grid ,=
TX fme Eloundou bertrant(652586578) from Huawei is informed","vanel.mbiada@=
matech-cameroun.com","377","29-06-2025 10:13:29","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005367064","Fla=
menco","","29-06-2025 09:43:48","29-06-2025 09:35:26","29-06-2025 11:59:17"=
,"Grid outage gen failed to start due to card GEN faulty/He started gen man=
ually","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid outage gen failed to start due to card GEN faulty/He start=
ed gen manually","cedric.tiani@matech-cameroun.com","503","29-06-2025 09:43=
:48","MATECH CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0005367038","Nko=
mkana","IHS_YND_517, IHS_YND_138, IHS_YND_126, IHS_YND_127","29-06-2025 09:=
42:35","29-06-2025 09:37:23","29-06-2025 15:51:00","Grid Only, No space to =
deploy MDGE // Grid return","","Grid Supply","Passive","Grid","National Gri=
d - Grid Outage Issue","Grid Only, No space to deploy MDGE // Grid return",=
"cedric.tiani@matech-cameroun.com","314","29-06-2025 09:42:35","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005367032","NKO=
MKANA ELIZA HOTEL","","29-06-2025 09:41:58","29-06-2025 09:37:49","29-06-20=
25 15:51:49","Grid outage, no space to deploy mobile gen // Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy mobile gen // Grid return","cedric.tiani@matech-c=
ameroun.com","250","29-06-2025 09:41:58","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005367012","M=
ontee-Des-Soeurs","","29-06-2025 09:40:49","29-06-2025 09:37:23","29-06-202=
5 09:43:06","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Grid Only, No space to deploy MDGE // Grid return","va=
nel.mbiada@matech-cameroun.com","289602","29-06-2025 09:40:49","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005367011","Ako=
k Ndoe Yde","","29-06-2025 09:40:45","29-06-2025 09:37:26","29-06-2025 09:4=
0:05","Grid outage site went down before gen start due to poor battery back=
up // Grid return	","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage site went down before gen=
 start due to poor battery backup // Grid return	","cedric.tiani@matech-cam=
eroun.com","200","29-06-2025 09:40:45","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005367009","B=
astos-Nylon","","29-06-2025 09:40:09","29-06-2025 09:37:23","29-06-2025 15:=
48:38","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Only, No space to deploy MDGE // Grid return","vanel.mb=
iada@matech-cameroun.com","289602","29-06-2025 09:40:09","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005367007","T=
singa","","29-06-2025 09:39:05","29-06-2025 09:37:23","29-06-2025 15:48:38"=
,"","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid Only, No space to deploy MDGE // Grid return","vanel.mbiada@m=
atech-cameroun.com","289604","29-06-2025 09:39:05","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0005366999","N=
komkana 2","","29-06-2025 09:38:24","29-06-2025 09:37:23","29-06-2025 15:48=
:38","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid Only, No space to deploy MDGE // Grid return","vanel.mbia=
da@matech-cameroun.com","289603","29-06-2025 09:38:24","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005366832","N=
gousso-Savana","","29-06-2025 08:57:12","29-06-2025 08:54:02","29-06-2025 0=
8:58:10","No power issue, site is on grid with Ubaie: 52.4V, Armand Nguetsa=
 (699949553) from Huawei is informed.","Siligap Boris","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue, site is on grid with Ubaie: 52.4V, Armand Nguetsa (699949553) from =
Huawei is informed.","vanel.mbiada@matech-cameroun.com","191","29-06-2025 0=
8:57:12","MATECH CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0005366680","B=
IYEMASSI NIKI","IHS_YND_546","29-06-2025 08:31:13","29-06-2025 08:20:59","2=
9-06-2025 09:31:54","Grid outage, Site went down because Gen failed to star=
t due to Grid bad voltage(LACK OF PHASE ) //He made a bridge","Hyemafo Gild=
as","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid outage, Site went down because Gen failed to start due to Grid bad =
voltage(LACK OF PHASE ) //He made a bridge","vanel.mbiada@matech-cameroun.c=
om","614","29-06-2025 08:31:13","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0005366625","B=
iyemassi LAC","","29-06-2025 08:23:23","29-06-2025 08:20:59","29-06-2025 09=
:31:54","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","Grid outage, Site went down because Gen failed to start due to Grid bad =
voltage(LACK OF PHASE ) //He made a bridge","vanel.mbiada@matech-cameroun.c=
om","272682","29-06-2025 08:23:23","MATECH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005366265","N=
omayos-IHS","","29-06-2025 07:20:27","29-06-2025 07:09:16","29-06-2025 07:5=
2:37","Grid outage,site went down because gen failed to start due to starte=
r relay has moved  // He fixed  it and gen manually started","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Relay Faulty","Grid outage,=
site went down because gen failed to start due to starter relay has moved  =
// He fixed  it and gen manually started","vanel.mbiada@matech-cameroun.com=
","672","29-06-2025 07:20:27","MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005366254","Mfa=
ndena","","29-06-2025 07:16:57","29-06-2025 07:11:47","29-06-2025 07:31:04"=
,"Grid outage,Site went down because GEN failed to start due to Alarm *Unde=
r frequency*//He reset the Gen card and manually started Gen","Delor Telezi=
ng","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage,Site went down because GEN failed to start due to Alarm *Under frequen=
cy*//He reset the Gen card and manually started Gen","vanel.mbiada@matech-c=
ameroun.com","311","29-06-2025 07:16:57","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0005366251","NTE=
MASSI","","29-06-2025 07:16:17","29-06-2025 07:10:15","29-06-2025 07:58:29"=
,"","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Grid outage, no access to deploy mobile gen // Grid return","vane=
l.mbiada@matech-cameroun.com","276906","29-06-2025 07:16:17","MATECH CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0005366248","Ngo=
usso MTN","IHS_YND_187","29-06-2025 07:15:21","29-06-2025 07:10:15","29-06-=
2025 07:58:29","Grid outage, no access to deploy mobile gen // Grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d outage, no access to deploy mobile gen // Grid return","vanel.mbiada@mate=
ch-cameroun.com","307","29-06-2025 07:15:21","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005366229","E=
vodoula OCM","","29-06-2025 07:10:30","29-06-2025 07:08:21","29-06-2025 07:=
50:41"," No power issue site and with Ubaie=3D54.4 V site on Gen The FME TX=
 Mouamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm"," No power issue site and with Ubaie=3D54.4 V site on Gen The FM=
E TX Mouamadou/658791013 //From Huawei is informed","vanel.mbiada@matech-ca=
meroun.com","130","29-06-2025 07:10:30","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005366058","Ako=
k Ndoe Yde","","29-06-2025 06:42:15","29-06-2025 06:40:04","29-06-2025 06:4=
3:07","Grid outage site went down before gen start due to poor battery back=
up // Geen auatomatically started","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage site went =
down before gen start due to poor battery backup // Geen auatomatically sta=
rted","cedric.tiani@matech-cameroun.com","132","29-06-2025 06:42:15","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0005366038","N=
R-Omnisport","","29-06-2025 06:38:38","29-06-2025 06:07:25","29-06-2025 07:=
04:50","	Site went down because the PWC OF ZTE dysfonction // He reset the =
PWC","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","	Site went down because the PWC OF ZTE dysfonction // He=
 reset the PWC","vanel.mbiada@matech-cameroun.com","1874","29-06-2025 06:38=
:38","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005366031","Eli=
g Edzoa","","29-06-2025 06:36:50","29-06-2025 06:08:35","29-06-2025 08:36:4=
3","site went down because gen start an stopped due to water infiltration i=
n tank // He purged The tank and Gen manually started","Delor Telezing","Fu=
el Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The=
 Fuel","site went down because gen start an stopped due to water infiltrati=
on in tank // He purged The tank and Gen manually started","vanel.mbiada@ma=
tech-cameroun.com","1696","29-06-2025 06:36:50","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005366015","MBA=
LNGONG LYCEE","","29-06-2025 06:35:13","29-06-2025 05:24:56","29-06-2025 08=
:01:36","	Grid outage,Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age,Site went down because Gen stopped due to overload(9kva, 130A) SS IHS F=
elix Zambe is informed and confirmed//Grid return","vanel.mbiada@matech-cam=
eroun.com","4219","29-06-2025 06:35:13","MATECH CMR"
"Closed Complete","Site Down","T1113","IHS_YND_105","NOCINC0005366008","Omn=
isport 3","","29-06-2025 06:33:59","29-06-2025 05:11:35","29-06-2025 07:31:=
24","Grid outage gen failed to start due to battery GE discharged causing b=
y static charger faulty// He started Gen with an external batttery","Delor =
Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery=
","Grid outage gen failed to start due to battery GE discharged causing by =
static charger faulty// He started Gen with an external batttery","vanel.mb=
iada@matech-cameroun.com","4945","29-06-2025 06:33:59","MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005365996","Mfa=
ndena","","29-06-2025 06:32:46","29-06-2025 02:45:36","29-06-2025 06:09:14"=
,"( backtrcking)  Grid outage,Site went down because GEN failed to start du=
e to Alarm *Under frequency*//He reset the Gen card and manually started Ge=
n","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","Grid outage,Site went down because GEN failed to start due to Alar=
m *Under frequency*//He reset the Gen card and manually started Gen","vanel=
.mbiada@matech-cameroun.com","13631","29-06-2025 06:32:46","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005365870","Evo=
doula MTN","","29-06-2025 06:25:15","29-06-2025 06:22:10","29-06-2025 06:27=
:10","Grid outage, Site went down before Gen start due to poor backup","TIE=
NTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage, Site went down before Gen start due to=
 poor backup","gerard.tchangoue@matech-cameroun.com","186","29-06-2025 06:2=
5:15","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005365616","Fou=
da Quarter","","29-06-2025 01:32:00","29-06-2025 01:22:44","29-06-2025 02:4=
3:24","Grid outage , site went down because gen fails to start due to grid =
bad voltage // Gen manually started","Delor Telezing","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid outage , site wen=
t down because gen fails to start due to grid bad voltage // Gen manually s=
tarted","gerard.tchangoue@matech-cameroun.com","557","29-06-2025 01:32:00",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005365503","Mfou EPC=
","","29-06-2025 00:49:14","29-06-2025 00:41:23","29-06-2025 00:53:57","Cas=
caded Incident from TTO5535202","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup//Gen automatically started","system","285824","29=
-06-2025 00:49:14","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005365502","M=
fou OCM","IHS_YND_674","29-06-2025 00:48:30","29-06-2025 00:41:23","29-06-2=
025 00:53:57","Grid Outage, Site Down before gen Started due to poor backup=
//Gen automatically started","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down bef=
ore gen Started due to poor backup//Gen automatically started","christelle.=
ngonga@matech-cameroun.com","549","29-06-2025 00:48:30","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005365181","NYO=
M FACE MAETUR","","28-06-2025 22:58:52","28-06-2025 22:58:49","28-06-2025 2=
2:59:49","Grid outage, Site went down because Gen failed to start due to Gr=
id bad voltage ","Fabrice Pouakam","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Grid outage, Site went down because Gen f=
ailed to start due to Grid bad voltage ","gerard.tchangoue@matech-cameroun.=
com","4","28-06-2025 22:58:52","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005365005","M=
vog-Manga","","28-06-2025 22:18:21","28-06-2025 22:16:12","28-06-2025 22:20=
:41","Grid outage, site went down due to Grid bad voltage and no rcp on sit=
e // Site stabilised","Albran Byorel","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","Grid outage, site went down due to Gri=
d bad voltage and no rcp on site // Site stabilised","gaelle.njiofack@matec=
h-cameroun.com","131","28-06-2025 22:18:21","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005364688","A=
wae Ewonkan","","28-06-2025 21:22:40","28-06-2025 21:16:32","28-06-2025 21:=
32:26","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","loic.noumsi@matech-cameroun.com","370","28-06-2025 21:22:40","MATECH =
CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005364602","M=
arche Odza","","28-06-2025 21:07:00","28-06-2025 21:04:50","28-06-2025 21:2=
0:11","Grid fluctuation,site went down due to Grid bad voltage // Site stab=
ilised","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid fluctuation,site went down due to Grid bad volt=
age // Site stabilised","gaelle.njiofack@matech-cameroun.com","132","28-06-=
2025 21:07:00","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005364545","S=
IMBOCK BONAMBAPE","","28-06-2025 20:56:46","28-06-2025 20:50:44","28-06-202=
5 20:55:44","Grid outage, site went down due to Gen Overload (20kva, 350A) =
SS IHS Felix ZAMBE confirmed // Site stabilised","Hyemafo Gildas","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went do=
wn due to Gen Overload (20kva, 350A) SS IHS Felix ZAMBE confirmed // Site s=
tabilised","loic.noumsi@matech-cameroun.com","363","28-06-2025 20:56:46","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005364539","M=
arche Odza","","28-06-2025 20:55:52","27-06-2025 08:50:58","27-06-2025 09:0=
9:00","Backtracking, site went Down due to Grid fluctuation // Grid stabili=
zed","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Backtracking, site went Down due to Grid fluctuation //=
 Grid stabilized","gaelle.njiofack@matech-cameroun.com","129894","28-06-202=
5 20:55:52","MATECH CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0005364374","M=
amch Building","","28-06-2025 20:28:20","28-06-2025 20:21:20","28-06-2025 2=
0:40:13","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid Only, No space to Deploy MDGE // Grid returned","loic=
.noumsi@matech-cameroun.com","265418","28-06-2025 20:28:20","MATECH CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0005364371","Cha=
rles-Atangana","IHS_YND_051","28-06-2025 20:26:30","28-06-2025 20:21:20","2=
8-06-2025 20:42:01","Grid Only, No space to Deploy MDGE // Grid returned","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
Only, No space to Deploy MDGE // Grid returned","loic.noumsi@matech-camerou=
n.com","312","28-06-2025 20:26:30","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005364328","Mok=
olo Yaounde","","28-06-2025 20:20:40","28-06-2025 20:19:31","28-06-2025 20:=
25:31","Active // No power issue Ubaie: 54.6 V site on grid. The Tx FME Elo=
undou Bertrand (693212405) from Huawei is informed","","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/ No power issue Ubaie: 54.6 V site on grid. The Tx FME Eloundou Bertrand (=
693212405) from Huawei is informed","loic.noumsi@matech-cameroun.com","70",=
"28-06-2025 20:20:40","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005364323","M=
ontee-Jouvence-II","","28-06-2025 20:19:38","27-06-2025 12:09:16","27-06-20=
25 12:24:14","Backtracking No power issue on site, site on Grid with Ubaie=
=3D51.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyem=
afo Gildas","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Backtracking No power issue on site, site on Grid w=
ith Ubaie=3D51.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is inform=
ed","gaelle.njiofack@matech-cameroun.com","115823","28-06-2025 20:19:38","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0005364309","N=
komkana","","28-06-2025 20:18:01","27-06-2025 11:10:43","27-06-2025 11:16:4=
3","	Backtracking Grid Only, No space to deploy MDGE// Grid returned","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid Onl=
y, No space to deploy MDGE// Grid returned","gaelle.njiofack@matech-camerou=
n.com","119238","28-06-2025 20:18:01","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005364217","C=
harles-Atangana","","28-06-2025 20:04:06","27-06-2025 11:03:44","27-06-2025=
 11:18:27","	Backtracking	Grid Only, No space to Deploy MGE // grid restora=
tion","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"	Grid Only, No space to Deploy MGE // grid restoration","gaelle.njiofack@=
matech-cameroun.com","118822","28-06-2025 20:04:06","MATECH CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0005364201","Cha=
rles-Atangana","","28-06-2025 19:59:10","28-06-2025 19:52:05","28-06-2025 2=
0:02:24","Grid Only, No space to Deploy MDGE // grid restoration","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No=
 space to Deploy MDGE // grid restoration","loic.noumsi@matech-cameroun.com=
","427","28-06-2025 19:59:10","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0005364175","H=
-Progres","","28-06-2025 19:56:08","27-06-2025 11:03:44","27-06-2025 11:14:=
11","	Backtracking Grid outage, no space to deploy MGE,// Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","	Backtra=
cking	Grid outage, no space to deploy MGE,// Grid return","gaelle.njiofack@=
matech-cameroun.com","118345","28-06-2025 19:56:08","MATECH CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0005364171","S=
apeur","","28-06-2025 19:54:45","27-06-2025 12:07:31","27-06-2025 12:13:41"=
,"Backtraking No power issue on site U=3D53.5V site on grid Tx Fme BRICE (6=
50214096) of huawei is informed","Mboua Thierry","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","	No power issu=
e on site U=3D53.5V site on grid Tx Fme BRICE (650214096) of huawei is info=
rmed","gaelle.njiofack@matech-cameroun.com","114434","28-06-2025 19:54:45",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0005364162","S=
apeur","","28-06-2025 19:50:07","27-06-2025 13:40:42","27-06-2025 13:49:44"=
,"Backtraking No power issue on site U=3D53.5V site on grid Tx Fme BRICE (6=
50214096) of huawei is informed","Mboua Thierry","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Backtraking No=
 power issue on site U=3D53.5V site on grid Tx Fme BRICE (650214096) of hua=
wei is informed","gaelle.njiofack@matech-cameroun.com","108566","28-06-2025=
 19:50:07","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005363879","Evo=
doula MTN","","28-06-2025 18:48:09","28-06-2025 18:44:58","28-06-2025 18:56=
:57","Grid outage, Site went down before Gen start due to poor backup// GRI=
D return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// GRID return","loic.noumsi@matech-cameroun.com"=
,"192","28-06-2025 18:48:09","MATECH CMR"
"Closed Complete","Site Down","T0532","IHS_YND_239","NOCINC0005363741","Men=
dong2","","28-06-2025 18:16:07","28-06-2025 18:10:02","28-06-2025 18:23:39"=
,"Grid outage, site went down due to Grid bad voltage (lack of 01 phase) //=
 He did bridge on the good phases, site on grid","Hyemafo Gildas","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid outag=
e, site went down due to Grid bad voltage (lack of 01 phase) // He did brid=
ge on the good phases, site on grid","loic.noumsi@matech-cameroun.com","366=
","28-06-2025 18:16:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0005363605","Mvog-Man=
ga","","28-06-2025 17:49:53","28-06-2025 17:47:01","28-06-2025 18:06:30","C=
ascaded Incident from TTO5533076","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down bec=
ause Gen failed to start due to Grid bad voltage // he bypassed the Grid an=
d site on Gen","system","281802","28-06-2025 17:49:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0005363606","Marche O=
dza","","28-06-2025 17:49:53","28-06-2025 17:47:01","28-06-2025 18:06:30","=
Cascaded Incident from TTO5533076","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down be=
cause Gen failed to start due to Grid bad voltage // he bypassed the Grid a=
nd site on Gen","system","281801","28-06-2025 17:49:53","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005363582","O=
dza","IHS_YND_254, IHS_YND_580","28-06-2025 17:48:12","28-06-2025 17:47:01"=
,"28-06-2025 18:06:30","Grid fluctuation, Site went down because Gen failed=
 to start due to Grid bad voltage // he bypassed the Grid and site on Gen",=
"Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid fluctuation, Site went down because Gen failed to start=
 due to Grid bad voltage // he bypassed the Grid and site on Gen","gaelle.n=
jiofack@matech-cameroun.com","72","28-06-2025 17:48:12","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005363441","Tou=
ring Club International","","28-06-2025 17:18:15","28-06-2025 17:13:08","28=
-06-2025 17:23:05","Grid outage, Gen failed to start due to Alarm Undervolt=
age // Gen card reset, and Gen start manually","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen failed=
 to start due to Alarm Undervoltage // Gen card reset, and Gen start manual=
ly","loic.noumsi@matech-cameroun.com","308","28-06-2025 17:18:15","MATECH C=
MR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005363308","N=
koabang2","","28-06-2025 16:59:21","28-06-2025 16:56:10","28-06-2025 17:11:=
29","	Grid outage, site went down due to gen overload (22KVA, 330A), SS Bla=
ise IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","	Grid outage, site went down due t=
o gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","=
loic.noumsi@matech-cameroun.com","193","28-06-2025 16:59:21","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005363218","Bar=
riere","","28-06-2025 16:39:50","28-06-2025 16:37:44","28-06-2025 16:51:32"=
,"Grid fluctuations, site went down due to Grid bad voltage // Site stabili=
sed","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid fluctuations, site went down due to Grid bad volt=
age // Site stabilised","loic.noumsi@matech-cameroun.com","127","28-06-2025=
 16:39:50","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005363194","Tou=
ring Club International","","28-06-2025 16:33:30","28-06-2025 16:30:22","28=
-06-2025 17:03:22","Grid outage, Gen failed to start due to Alarm Undervolt=
age // Gen card reset, and Gen start manually","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen failed=
 to start due to Alarm Undervoltage // Gen card reset, and Gen start manual=
ly","loic.noumsi@matech-cameroun.com","189","28-06-2025 16:33:30","MATECH C=
MR"
"Closed Complete","Warning","T0033","IHS_YND_167","NOCINC0005363168","Touri=
ng Club International","","28-06-2025 16:29:24","","","Grid outage, Gen fai=
led to start due to Alarm Undervoltage // Gen card reset, and Gen start man=
ually","Albran Byorel","Warning","Warning","POWER","Warning - ACDG - Under =
Voltage","Grid outage, Gen failed to start due to Alarm Undervoltage // Gen=
 card reset, and Gen start manually","loic.noumsi@matech-cameroun.com","433=
","28-06-2025 16:29:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005363087","Nkol-Meb=
anga","","28-06-2025 16:11:15","28-06-2025 15:50:13","28-06-2025 16:26:26",=
"Cascaded Incident from TTO5532435","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","	Grid outage, Site went down becau=
se Gen start and stopped with ""High temp"" alarm // he added water in the =
radiator and manually started the Gen manually","system","267335","28-06-20=
25 16:11:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005363086","Carrefou=
r Ayissi Ele","","28-06-2025 16:11:14","28-06-2025 15:50:13","28-06-2025 16=
:26:26","Cascaded Incident from TTO5532435","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","	Grid outage, Site went do=
wn because Gen start and stopped with ""High temp"" alarm // he added water=
 in the radiator and manually started the Gen manually","system","267336","=
28-06-2025 16:11:14","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005363000","S=
aa","IHS_YND_810, IHS_YND_809","28-06-2025 15:57:18","28-06-2025 15:50:13",=
"28-06-2025 16:26:26","	Grid outage, Site went down because Gen start and s=
topped with ""High temp"" alarm // he added water in the radiator and manua=
lly started the Gen manually","Parker Tchoup","Equipment Repair","Passive",=
"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","	Grid outage, S=
ite went down because Gen start and stopped with ""High temp"" alarm // he =
added water in the radiator and manually started the Gen manually","gaelle.=
njiofack@matech-cameroun.com","427","28-06-2025 15:57:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005362696","Eto koss=
 Yde","","28-06-2025 15:00:05","28-06-2025 14:39:57","28-06-2025 14:45:54",=
"Cascaded Incident from TTO5531964","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Grid returned","system","264405","28-06-2025=
 15:00:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005362697","ELOUMDEM=
 CARRIERE 2","","28-06-2025 15:00:05","28-06-2025 14:39:57","28-06-2025 14:=
45:54","Cascaded Incident from TTO5531964","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid returned","system","264406","28-=
06-2025 15:00:05","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005362682","Mvo=
g-Manga","","28-06-2025 14:57:46","28-06-2025 14:51:37","28-06-2025 16:04:5=
4","Grid outage, site went down due to Grid bad voltage and no rcp on site =
// He bypassed Grid and started Gen manually","Albran Byorel","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid outage, s=
ite went down due to Grid bad voltage and no rcp on site // He bypassed Gri=
d and started Gen manually","loic.noumsi@matech-cameroun.com","371","28-06-=
2025 14:57:46","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005362632","Men=
dong NB","","28-06-2025 14:49:44","28-06-2025 14:45:38","28-06-2025 14:55:0=
6","Grid outage, site went down due to Grid fluctuations // Site stabilised=
","","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid outage, site went down due to Grid fluctuations // Site stabilised=
","loic.noumsi@matech-cameroun.com","247","28-06-2025 14:49:44","MATECH CMR=
"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0005362611","Sim=
bock Maetur","","28-06-2025 14:44:42","28-06-2025 14:41:36","28-06-2025 14:=
53:27","Grid outage, site went down due to poor battery backup // Grid retu=
rned","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage, site went down due to poor battery bac=
kup // Grid returned","loic.noumsi@matech-cameroun.com","187","28-06-2025 1=
4:44:42","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005362580","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","28-06-2025 14:43:07","28-06-2025 14:39=
:57","28-06-2025 14:45:54","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","Fanda Brice","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Grid returned","loic.noumsi@matec=
h-cameroun.com","192","28-06-2025 14:43:07","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005362495","Eko=
umdoum OCM","","28-06-2025 14:26:05","28-06-2025 14:17:51","28-06-2025 16:4=
4:13","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction// FME is on site","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","	Grid outage,site went down b=
ecause Gen failed to start due to PWC ZTE dysfunction//He reset itand start=
ed the Gen manually","cedric.tiani@matech-cameroun.com","495","28-06-2025 1=
4:26:05","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005362434","Men=
dong3","","28-06-2025 14:13:10","28-06-2025 14:11:01","28-06-2025 14:38:15"=
,"Grid Outage No space to deploy a MDG // Grid returned ","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No space =
to deploy a MDG // Grid returned ","cedric.tiani@matech-cameroun.com","129"=
,"28-06-2025 14:13:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0005362417","MEFOU AS=
SI","","28-06-2025 14:11:02","28-06-2025 12:54:39","28-06-2025 14:09:00","C=
ascaded Incident from TTO5531268","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is i=
nformed // Grid return","system","277787","28-06-2025 14:11:02","MATECH CMR=
"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0005362326","Com=
plex Beac II","","28-06-2025 13:52:22","28-06-2025 13:49:15","28-06-2025 14=
:44:01","Site went down due to disjunction of rectifer CB (32A) // He rearm=
ed it ","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier=
 - Circuit Breaker","Site went down due to disjunction of rectifer CB (32A)=
 // He rearmed it ","cedric.tiani@matech-cameroun.com","188","28-06-2025 13=
:52:22","MATECH CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0005362290","Hot=
el de Ville Yde","","28-06-2025 13:43:55","28-06-2025 13:38:14","28-06-2025=
 14:10:34","Active//No power issue on site ,site on Grid wiith Ubaie=3D54.1=
 V .Noticed that SYNCLAY (677550019) of MTN is on site working","Paul BIBOU=
M","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issue on site ,site on Grid wiith Ubaie=3D5=
4.1 V .Noticed that Regional Manager SYNCLAY of Huawei is on site working."=
,"cedric.tiani@matech-cameroun.com","342","28-06-2025 13:43:55","MATECH CMR=
"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005362206","Evo=
doula MTN","","28-06-2025 13:32:08","28-06-2025 13:28:58","28-06-2025 13:32=
:32","Grid Outage, Site Down before gen Started due to poor backup//Grid re=
turn","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Started=
 due to poor backup//Grid return","cedric.tiani@matech-cameroun.com","190",=
"28-06-2025 13:32:08","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005362169","C=
rf Cornier","","28-06-2025 13:26:57","28-06-2025 13:18:42","28-06-2025 13:3=
0:26","ACTIVE //No power issue Ubaie=3D 54V site on Grid . the fme TX Arman=
d NGUETSA (699949553 / huawei) is informed,","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","AC=
TIVE //No power issue Ubaie=3D 54V site on Grid . the fme TX Armand NGUETSA=
 (699949553 / huawei) is informed,","vanel.mbiada@matech-cameroun.com","496=
","28-06-2025 13:26:57","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005362091","E=
koumdoum OCM","","28-06-2025 13:16:23","28-06-2025 13:12:18","28-06-2025 13=
:50:36","Grid outage,site went down because Gen failed to start due to PWC =
ZTE dysfunction//He reset it and started the Gen manually","Albran Byorel",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gri=
d outage,site went down because Gen failed to start due to PWC ZTE dysfunct=
ion//He reset it and started the Gen manually","vanel.mbiada@matech-camerou=
n.com","246","28-06-2025 13:16:23","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005361954","M=
efou-Assi","IHS_YND_537","28-06-2025 12:56:12","28-06-2025 12:54:39","28-06=
-2025 14:09:00","	Grid outage, site went down because gen failed to start d=
ue to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid retu=
rn","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"	Grid outage, site went down because gen failed to start due to gen overl=
oad(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return","vanel.mbia=
da@matech-cameroun.com","94","28-06-2025 12:56:12","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005361925","E=
seka OCM","IHS_YND_378","28-06-2025 12:51:56","28-06-2025 12:44:34","28-06-=
2025 12:54:38","No power issue U=3D57.2V site on Grid  The Tx FME Etienne F=
OPA /695033981/ From HUAWEI is informed","Kemeni Franklin","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue U=3D57.2V site on Grid  The Tx FME Etienne FOPA /695033981/ From=
 HUAWEI is informed","vanel.mbiada@matech-cameroun.com","443","28-06-2025 1=
2:51:56","MATECH CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0005361839","E=
BOM","","28-06-2025 12:39:35","28-06-2025 12:36:12","28-06-2025 13:54:57","=
Grid outage, site went down because gen start and stopped with high temp al=
arm // He added water and manually start the gen	","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Grid outage, site went down because gen start and stopped with high =
temp alarm // He added water and manually start the gen	","vanel.mbiada@mat=
ech-cameroun.com","204","28-06-2025 12:39:35","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005361745","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","28-06-2025 12:25:02","28-06-20=
25 12:23:48","28-06-2025 15:15:23","Grid outage, Site went down because Gen=
 start and stopped with ""High temps ""alarm // he added water and manually=
 start the Gen	(","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","=
ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Sit=
e went down because Gen start and stopped with ""High temps ""alarm // he a=
dded water and manually start the Gen	(","cedric.tiani@matech-cameroun.com"=
,"74","28-06-2025 12:25:02","MATECH CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0005361730","E=
seka Town","","28-06-2025 12:22:11","28-06-2025 12:44:34","28-06-2025 12:54=
:38","Active// No power issue, Site on Gen Ubaie:50V, The FME Tx Etienne/69=
5033981 From Huawei is informed","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active// No power issue, Site on Gen U=
baie:50V, The FME Tx Etienne/695033981 From Huawei is informed","vanel.mbia=
da@matech-cameroun.com","10796","28-06-2025 12:22:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005361715","Mfou EPC=
","","28-06-2025 12:19:56","28-06-2025 12:13:41","28-06-2025 12:21:19","Cas=
caded Incident from TTO5530996","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup//Gen automatically started ","system","265995","2=
8-06-2025 12:19:56","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005361711","M=
fou OCM","IHS_YND_674","28-06-2025 12:19:12","28-06-2025 12:13:41","28-06-2=
025 12:21:19","Grid Outage, Site Down before gen Started due to poor backup=
//Gen automatically started ","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down be=
fore gen Started due to poor backup//Gen automatically started ","vanel.mbi=
ada@matech-cameroun.com","331","28-06-2025 12:19:12","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0005361683","Imm=
-Olympique","","28-06-2025 12:14:50","28-06-2025 11:47:31","28-06-2025 13:2=
5:21","Grid outage,site went down because Gen failed to start due to Gen ov=
erload(20KVA//295A) SS HIS Raoul is informed//Grid return","Paul BIBOUM","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,site w=
ent down because Gen failed to start due to Gen overload(20KVA//295A) SS HI=
S Raoul is informed//Grid return","cedric.tiani@matech-cameroun.com","1640"=
,"28-06-2025 12:14:50","MATECH CMR"
"Cancelled","Site Down","T1737","IHS_YND_005","NOCINC0005361676","Imm-Olymp=
ique","","28-06-2025 12:13:19","28-06-2025 01:12:32","28-06-2025 10:02:13",=
"Wrongly created ticket","Paul BIBOUM","Incorrectly Logged Tickets","Error"=
,"Error","Error","Wrongly created ticket","cedric.tiani@matech-cameroun.com=
","39647","28-06-2025 12:13:19","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005361673","B=
arriere IHS","","28-06-2025 12:12:25","28-06-2025 12:06:15","28-06-2025 14:=
39:09","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed // Grid returned","Hyemafo Gildas","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due=
 to Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return=
ed","vanel.mbiada@matech-cameroun.com","372","28-06-2025 12:12:25","MATECH =
CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005361667","E=
koumdoum OCM","","28-06-2025 12:11:52","28-06-2025 12:06:46","28-06-2025 13=
:06:47","Grid outage,site went down because Gen failed to start due to PWC =
ZTE dysfunction//He reset it and started the Gen manually","Albran Byorel",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gri=
d outage,site went down because Gen failed to start due to PWC ZTE dysfunct=
ion//He reset it and started the Gen manually","vanel.mbiada@matech-camerou=
n.com","307","28-06-2025 12:11:52","MATECH CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0005361652","Eko=
unou","","28-06-2025 12:08:17","28-06-2025 11:59:03","28-06-2025 14:00:24",=
"Grid outage,site went down because Gen failed to start due to PWC ZTE dysf=
unction//He reset it and started the Gen manually","Albran Byorel","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage=
,site went down because Gen failed to start due to PWC ZTE dysfunction//He =
reset it and started the Gen manually","cedric.tiani@matech-cameroun.com","=
556","28-06-2025 12:08:17","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005361567","B=
arriere","","28-06-2025 11:52:33","28-06-2025 11:46:18","28-06-2025 14:39:4=
7","Grid Outage, Site went down because Gen failed To start due to Alarm ""=
high temp' // He added water in the radiator","Hyemafo Gildas","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"Grid Outage, Site went down because Gen failed To start due to Alarm ""hi=
gh temp' // He added water in the radiator","vanel.mbiada@matech-cameroun.c=
om","377","28-06-2025 11:52:33","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005361488","S=
IMBOCK BONAMBAPE","","28-06-2025 11:38:24","28-06-2025 11:34:51","28-06-202=
5 14:44:47","Grid outage, site went down due to Gen Overload (20kva, 350A) =
SS IHS Felix ZAMBE confirmed // He reduced the load and site on Gen","Hyema=
fo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage, site went down due to Gen Overload (20kva, 350A) SS IHS Felix ZAMBE=
 confirmed // He reduced the load and site on Gen","vanel.mbiada@matech-cam=
eroun.com","214","28-06-2025 11:38:24","MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0005361342","B=
astos Bir","","28-06-2025 11:07:52","28-06-2025 11:04:45","28-06-2025 11:16=
:03","No power issue, site is on Gen with Ubaie=3D53.3 V site on grid ,TX f=
me Eloundou bertrant(652586578) from Huawei is informed","Mboua Thierry","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue, site is on Gen with Ubaie=3D53.3 V site on grid ,=
TX fme Eloundou bertrant(652586578) from Huawei is informed","vanel.mbiada@=
matech-cameroun.com","188","28-06-2025 11:07:52","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005361271","Men=
dong NB","","28-06-2025 10:57:28","28-06-2025 10:49:12","28-06-2025 11:35:3=
8","Grid Only, No space to deploy // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid Only, No space to deploy=
 // Grid return","ludivine.ngamaleu@ihstowers.com","497","28-06-2025 10:57:=
28","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005361123","N=
kolfon Cimencam","","28-06-2025 10:27:20","28-06-2025 10:23:11","28-06-2025=
 10:41:01","site impacted by Afanoya II","Hyemafo Gildas","Customer Equipme=
nt Failure","Active","Active Equipment Failure","Affected by 3rd Party Site=
","site impacted by Afanoya II","vanel.mbiada@matech-cameroun.com","250","2=
8-06-2025 10:27:20","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005361117","M=
eyo","","28-06-2025 10:26:40","28-06-2025 10:23:25","28-06-2025 14:44:37","=
Grid outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix =
Zambe is informed and confirmed // Grid return","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went dow=
n due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and conf=
irmed // Grid return","vanel.mbiada@matech-cameroun.com","196","28-06-2025 =
10:26:40","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005361112","A=
hala","","28-06-2025 10:26:02","28-06-2025 10:23:47","28-06-2025 10:45:41",=
"Active// No power isssue on site Ubaie 54.3 V site on Grid, the FME Fluber=
t (654266058) of Hauwei is informed. Noticed that, ZTE group working on sit=
e","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active// No power isssue on site Ubaie 54.3=
 V site on Grid, the FME Flubert (654266058) of Hauwei is informed. Noticed=
 that, ZTE group working on site","vanel.mbiada@matech-cameroun.com","137",=
"28-06-2025 10:26:02","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0005360967","Imm=
-Olympique","","28-06-2025 10:05:25","28-06-2025 10:02:14","28-06-2025 11:3=
8:44","Grid outage,site went down because Gen failed to start due to Gen ov=
erload(20KVA//295A) SS HIS Raoul is informed//Grid return","Paul BIBOUM","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,site w=
ent down because Gen failed to start due to Gen overload(20KVA//295A) SS HI=
S Raoul is informed//Grid return","cedric.tiani@matech-cameroun.com","192",=
"28-06-2025 10:05:25","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005360913","S=
IMBOCK BONAMBAPE","","28-06-2025 09:59:27","28-06-2025 09:56:02","28-06-202=
5 11:17:15","Grid outage, site went down due to Gen Overload (20kva, 350A) =
SS IHS Felix ZAMBE confirmed // He reduced the load and site on Gen","Hyema=
fo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage, site went down due to Gen Overload (20kva, 350A) SS IHS Felix ZAMBE=
 confirmed // He reduced the load and site on Gen","vanel.mbiada@matech-cam=
eroun.com","207","28-06-2025 09:59:27","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005360826","Mon=
tee Jouvence","","28-06-2025 09:43:59","28-06-2025 09:42:51","28-06-2025 11=
:54:50","Grid outage gen failed to start due to battery GE discharged causi=
ng by static charger faulty// He started Gen with an external batttery","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Bat=
tery","Grid outage gen failed to start due to battery GE discharged causing=
 by static charger faulty// He started Gen with an external batttery","cedr=
ic.tiani@matech-cameroun.com","69","28-06-2025 09:43:59","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005360814","A=
fanoya","","28-06-2025 09:41:47","28-06-2025 09:39:16","28-06-2025 10:51:58=
","Grid outage,site went down because Gen failed to start due to  Gen card =
faulty //He started the Gen manually","Hyemafo Gildas","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down beca=
use Gen failed to start due to  Gen card faulty //He started the Gen manual=
ly","vanel.mbiada@matech-cameroun.com","152","28-06-2025 09:41:47","MATECH =
CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005360799","Nom=
ayos montee Meche","","28-06-2025 09:41:02","28-06-2025 09:37:55","28-06-20=
25 09:39:48","Grid outage, Site went down before Gen start due to poor back=
up // Gen started automatically","Fanda Brice","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor backup // Gen started automatically","cedric.=
tiani@matech-cameroun.com","188","28-06-2025 09:41:02","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005360750","Jou=
vence Mbenda","","28-06-2025 09:33:37","28-06-2025 09:30:25","28-06-2025 11=
:33:42"," Grid outage, site went down because gen start and stopped with hi=
gh temp alarm // He added water and manually start the gen","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"," Grid outage, =
site went down because gen start and stopped with high temp alarm // He add=
ed water and manually start the gen","cedric.tiani@matech-cameroun.com","19=
3","28-06-2025 09:33:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005360744","ELOUMDEM=
 CARRIERE 2","","28-06-2025 09:31:15","28-06-2025 09:27:17","28-06-2025 09:=
33:49","Cascaded Incident from TTO5529915","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","system","=
261606","28-06-2025 09:31:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005360743","Eto koss=
 Yde","","28-06-2025 09:31:14","28-06-2025 09:27:17","28-06-2025 09:33:49",=
"Cascaded Incident from TTO5529915","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","system","261607"=
,"28-06-2025 09:31:14","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005360739","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","28-06-2025 09:30:23","28-06-2025 09:27=
:17","28-06-2025 09:33:49","Grid outage, Site went down before Gen start du=
e to poor backup // Gen started automatically","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","cedric.tiani@matech-cameroun.com","188","28-06-2025 09:30:23","MATEC=
H CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005360517","Nko=
lfoulou CSD MTN","","28-06-2025 08:48:04","28-06-2025 08:46:54","28-06-2025=
 08:53:19","Active//No power issue site is on Grid with Ubaie=3D53,4 V site=
 on gen The Tx FME Syphorien //675295205 from Huawei is informed","Siligap =
Boris","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No power issue site is on Grid with Ubaie=3D53,4=
 V site on gen The Tx FME Syphorien //675295205 from Huawei is informed","c=
edric.tiani@matech-cameroun.com","71","28-06-2025 08:48:04","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005360496","O=
lembe-Terminus","","28-06-2025 08:43:01","28-06-2025 08:41:01","28-06-2025 =
09:23:12","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage.gen ran until fuel shortage//Refueling done=
","vanel.mbiada@matech-cameroun.com","285788","28-06-2025 08:43:01","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005360495","O=
lembe","IHS_YND_300","28-06-2025 08:42:06","28-06-2025 08:41:01","28-06-202=
5 09:23:12","Grid outage.gen ran until fuel shortage//Refueling done","Fabr=
ice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.=
gen ran until fuel shortage//Refueling done","vanel.mbiada@matech-cameroun.=
com","66","28-06-2025 08:42:06","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005360488","B=
arriere","","28-06-2025 08:40:44","28-06-2025 08:38:34","28-06-2025 09:38:5=
1","Grid Outage, Site went down because Gen failed To start due to Alarm ""=
high temp' // He added water in the radiator ","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","Grid Outage, Site went down because Gen failed To start due to Alarm ""h=
igh temp' // He added water in the radiator ","vanel.mbiada@matech-cameroun=
.com","132","28-06-2025 08:40:44","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005360438","Nsa=
m Sofavinc","IHS_YND_732","28-06-2025 08:32:06","28-06-2025 08:26:48","28-0=
6-2025 09:10:33","Site went down due to disjunction of Cb(50A) Rectifiers i=
n PWC // He reamed Cb(50A), site on grid","MINKA NICOLAS","Equipment Repair=
","Passive","Rectifier","Rectifier - Circuit Breaker","Site went down due t=
o disjunction of Cb(50A) Rectifiers in PWC // He reamed Cb(50A), site on gr=
id","vanel.mbiada@matech-cameroun.com","319","28-06-2025 08:32:06","MATECH =
CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0005360435","Nsa=
m escale LP","","28-06-2025 08:31:16","28-06-2025 08:26:48","28-06-2025 09:=
10:33","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"Site went down due to disjunction of Cb(50A) Rectifiers in PWC // He ream=
ed Cb(50A), site on grid","vanel.mbiada@matech-cameroun.com","272321","28-0=
6-2025 08:31:16","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005360216","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","28-06-2025 07:40:51","28-06-20=
25 07:37:29","28-06-2025 08:52:46","Grid outage, Site went down because Gen=
 start and stopped with ""High temps ""alarm // he added water and manually=
 start the Gen	","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","A=
CDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site=
 went down because Gen start and stopped with ""High temps ""alarm // he ad=
ded water and manually start the Gen	","cedric.tiani@matech-cameroun.com","=
203","28-06-2025 07:40:51","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005359960","OBA=
M NGOLA OCM","","28-06-2025 06:57:23","28-06-2025 06:55:46","28-06-2025 14:=
40:22","Grid outage,site went down due to Gen overload(15kva//250A)SS HIS F=
rancois 'is informed // SIte stabilised","MINKA NICOLAS","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage,site went down due to =
Gen overload(15kva//250A)SS HIS Francois 'is informed // SIte stabilised","=
cedric.tiani@matech-cameroun.com","99","28-06-2025 06:57:23","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005359929","Evo=
doula MTN","","28-06-2025 06:44:31","28-06-2025 06:37:23","28-06-2025 06:50=
:45","Grid outage, Site went down before Gen start due to poor backup// GRI=
D return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// GRID return","cedric.tiani@matech-cameroun.com=
","429","28-06-2025 06:44:31","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005359847","Evo=
doula MTN","","28-06-2025 06:21:11","28-06-2025 06:18:01","28-06-2025 06:30=
:51","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","fran=
ck.nkomot@matech-cameroun.com","191","28-06-2025 06:21:11","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005359460","OBA=
M NGOLA OCM","","28-06-2025 04:13:57","28-06-2025 01:45:32","28-06-2025 03:=
43:26","(Backtracking) Site went down due to PWC overload //Site stabilised=
","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e Overloaded","Site went down due to PWC overload //Site stabilised","gaell=
e.njiofack@matech-cameroun.com","8906","28-06-2025 04:13:57","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005359420","Mok=
olo Yaounde","","28-06-2025 04:00:28","28-06-2025 03:55:15","28-06-2025 07:=
56:05","Active // No power issue Ubay: 52.2 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 52.2 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","edwige.kapawo@matech-cameroun.com","314"=
,"28-06-2025 04:00:28","MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0005359098","Mes=
sassi okolo","","28-06-2025 01:48:10","28-06-2025 01:41:01","28-06-2025 01:=
51:01","site went down due to work of Biganstil (679161144/650631358/696909=
086/Dowen-services); Swap of PWC // end of work","Fabrice Pouakam","Install=
ation Activity","Passive","Planned Activity","Installation Activity","site =
went down due to work of Biganstil (679161144/650631358/696909086/Dowen-ser=
vices); Swap of PWC // end of work","franck.nkomot@matech-cameroun.com","43=
0","28-06-2025 01:48:10","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0005359013","MEH=
ANDAN","","28-06-2025 01:18:04","28-06-2025 01:08:53","28-06-2025 03:12:52"=
,"Grid fluctuation,Site went down because GEN failed to start due to grid b=
ad voltage(lack of 01 phase)// He did a bridge on the good phase","Albran B=
yorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation,Site went down because GEN failed to start due to gr=
id bad voltage(lack of 01 phase)// He did a bridge on the good phase","fran=
ck.nkomot@matech-cameroun.com","552","28-06-2025 01:18:04","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005358897","A=
wae Ewonkan","","28-06-2025 00:32:00","28-06-2025 00:26:42","28-06-2025 00:=
30:52","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","edwige.kapawo@matech-cameroun.com","320","28-06-2025 00:32:00","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005358892","O=
dza II OCM","","28-06-2025 00:30:38","28-06-2025 00:26:30","28-06-2025 00:2=
9:59","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","edwige.kapawo@matech-cameroun.com","250","28-06-2025 00:30:38=
","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005358861","O=
dza II OCM","IHS_YND_528","28-06-2025 00:21:53","28-06-2025 00:12:59","28-0=
6-2025 00:15:32","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","edwige.kapawo@matech-cameroun.com","537","28-06-20=
25 00:21:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005358857","Acropole=
","","28-06-2025 00:21:14","28-06-2025 00:12:55","28-06-2025 00:16:00","Cas=
caded Incident from TTO5527856","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down before Gen=
 start due to poor backup // Grid return","system","265908","28-06-2025 00:=
21:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005358848","C-Suprem=
e","","28-06-2025 00:19:44","28-06-2025 00:12:55","28-06-2025 00:16:00","Ca=
scaded Incident from TTO5527856","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, Site went down before Gen start due t=
o poor backup // Grid return","system","265908","28-06-2025 00:19:44","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005358845","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","28-06-2025 00:19:02","28-06-2025 0=
0:12:55","28-06-2025 00:16:00","Grid outage, Site went down before Gen star=
t due to poor backup // Grid return","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site wen=
t down before Gen start due to poor backup // Grid return","edwige.kapawo@m=
atech-cameroun.com","368","28-06-2025 00:19:02","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005358836","M=
ontee-Des-Soeurs","","28-06-2025 00:16:50","28-06-2025 00:12:44","28-06-202=
5 00:17:11","Grid outage ,site down due to Gen overload (15 KVA/210 A) // g=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // g=
rid return","edwige.kapawo@matech-cameroun.com","248","28-06-2025 00:16:50"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_063","IHS_YND_365","NOCINC0005358818","A=
kono","","28-06-2025 00:10:55","28-06-2025 00:06:40","28-06-2025 01:51:47",=
"Grid outage, Gen stopped because engine is already very old // Gen Start m=
anually (this site need a new Gen)","Fanda Brice","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Generator Faulty","Grid outage, Gen stopped because =
engine is already very old // Gen Start manually (this site need a new Gen)=
","edwige.kapawo@matech-cameroun.com","255","28-06-2025 00:10:55","MATECH C=
MR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005358807","S=
aa","","28-06-2025 00:07:29","28-06-2025 00:04:16","28-06-2025 00:19:43","A=
ctive // No power issue on site ,site on Gen with Ubaie =3D51.5V The Tx Tec=
hnician from Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active // No power issue on site ,site on Gen with Ubaie =3D51.5V T=
he Tx Technician from Huawei Gr=E9goire//654547479 is informed","edwige.kap=
awo@matech-cameroun.com","195","28-06-2025 00:07:29","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005358582","C=
rf Cornier","","27-06-2025 23:07:38","27-06-2025 22:57:59","27-06-2025 23:1=
2:08","ACTIVE //No power issue Ubaie=3D 50.2V site on Grid . the fme TX Arm=
and NGUETSA (699949553 / huawei) is informed,","MINKA NICOLAS","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE //No power issue Ubaie=3D 50.2V site on Grid . the fme TX Armand NGU=
ETSA (699949553 / huawei) is informed,","edwige.kapawo@matech-cameroun.com"=
,"580","27-06-2025 23:07:38","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005358559","OBA=
M NGOLA OCM","","27-06-2025 22:59:17","27-06-2025 22:50:56","28-06-2025 01:=
24:59","Site went down due to PWC overload //Site stabilised","MINKA NICOLA=
S","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Site went down due to PWC overload //Site stabilised","landry.etame@ihstowe=
rs.com","503","27-06-2025 22:59:17","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005358533","M=
vog-Manga","","27-06-2025 22:48:47","27-06-2025 22:46:29","27-06-2025 22:50=
:07","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","edwige.kapawo@matech-cameroun.com","140",=
"27-06-2025 22:48:47","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005358485","B=
arriere","","27-06-2025 22:40:00","27-06-2025 22:39:50","27-06-2025 23:50:0=
3","Grid outage, site went down because gen failed to start due to PWC ZTE =
malfunction // He reset controller and gen manually started","Hyemafo Gilda=
s","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Grid outage, site went down because gen failed to start due to PWC ZTE malf=
unction // He reset controller and gen manually started","edwige.kapawo@mat=
ech-cameroun.com","221","27-06-2025 22:40:00","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005358458","Evo=
doula MTN","","27-06-2025 22:35:05","27-06-2025 22:26:56","27-06-2025 22:54=
:56","Backtracking Grid outage, Site went down before Gen start due to poor=
 backup// Gen Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Backtracki=
ng Grid outage, Site went down before Gen start due to poor backup// Gen Au=
tomatically Started","franck.nkomot@matech-cameroun.com","489","27-06-2025 =
22:35:05","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005358411","A=
wae Ewonkan","","27-06-2025 22:21:29","27-06-2025 22:19:18","27-06-2025 22:=
22:42","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","edwige.kapawo@matech-cameroun.com","133","27-06-2025 22:21:29","MATEC=
H CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005358402","Bit=
eng-Maetur","","27-06-2025 22:18:45","27-06-2025 22:08:59","28-06-2025 07:5=
7:09","Active//No power issue on site Ubaie =3D49.5V site on Grid The TX FM=
E Henri (699949693) from Huawei is informed","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site Ubaie =3D50.3V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","franck.nkomot@matech-cameroun.com",=
"587","27-06-2025 22:18:45","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005357826","M=
essassi okolo","","27-06-2025 20:30:22","27-06-2025 20:21:01","27-06-2025 2=
3:15:19","Site went Down because Biganstile (650631358/Dowen) was on site f=
or work (SWAP of PWC) // End of work","Fabrice Pouakam","Equipment Replacem=
ent","Passive","Planned Activity","Planned Activity - Passive","Site went D=
own because Biganstile (650631358/Dowen) was on site for work (SWAP of PWC)=
 // End of work","christelle.ngonga@matech-cameroun.com","563","27-06-2025 =
20:30:22","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005357555","B=
arriere","","27-06-2025 19:40:45","27-06-2025 19:39:30","27-06-2025 21:43:0=
9","Grid outage, site went down because gen failed to start due to PWC ZTE =
malfunction // He reset controller and gen manually started","Hyemafo Gilda=
s","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Grid outage, site went down because gen failed to start due to PWC ZTE malf=
unction // He reset controller and gen manually started","christelle.ngonga=
@matech-cameroun.com","77","27-06-2025 19:40:45","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005357479","E=
SSOS OASIS 1111","","27-06-2025 19:23:28","27-06-2025 19:22:39","27-06-2025=
 19:24:22","Grid outage, Site went down because Gen overload (17kva, 250A) =
// Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Grid outage, Site went down because Gen overload (17kva, =
250A) // Grid returned","christelle.ngonga@matech-cameroun.com","50","27-06=
-2025 19:23:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0005357391","Mamch Bu=
ilding","","27-06-2025 19:01:50","27-06-2025 19:00:28","27-06-2025 19:01:32=
","Cascaded Incident from TTO5526243","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid Only, No space to Deploy MG=
E // grid restoration","system","277400","27-06-2025 19:01:50","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005357387","C=
harles-Atangana","IHS_YND_051","27-06-2025 19:00:35","27-06-2025 19:00:28",=
"27-06-2025 19:01:32","Grid Only, No space to Deploy MGE // grid restoratio=
n","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid Only, No space to Deploy MGE // grid restoration","christelle.ngonga@ma=
tech-cameroun.com","9","27-06-2025 19:00:35","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005357102","Aka=
k-Nkozoa-MTN-IHS","","27-06-2025 18:10:30","27-06-2025 18:01:59","27-06-202=
5 18:12:59"," Grid outage .gen failed to start due to AVR faulty//We replac=
e AVR and site on gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG=
 Gen","ACDG - AVR","Grid outage .gen failed to start due to AVR faulty//We =
replace AVR and site on gen","franck.nkomot@matech-cameroun.com","565","27-=
06-2025 18:10:30","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005356897","B=
arriere","","27-06-2025 17:37:49","27-06-2025 17:28:43","27-06-2025 17:57:2=
2","Site down due to plan work  ( Normalisation of ATS ) // End of work","H=
yemafo Gildas","Installation Activity","Passive","Planned Activity","Instal=
lation Activity","Site down due to plan work  ( Normalisation of ATS ) // E=
nd of work","christelle.ngonga@matech-cameroun.com","548","27-06-2025 17:37=
:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005356876","Mfou EPC=
","","27-06-2025 17:29:23","27-06-2025 17:16:04","27-06-2025 17:21:05","Cas=
caded Incident from TTO5525638","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","269354","27-06-2025 17=
:29:23","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005356849","M=
fou OCM","IHS_YND_674","27-06-2025 17:22:11","27-06-2025 17:16:04","27-06-2=
025 17:21:05","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","christelle.ngonga@matech-cameroun=
.com","368","27-06-2025 17:22:11","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005356825","N=
kozoa","","27-06-2025 17:16:32","27-06-2025 17:12:00","27-06-2025 18:03:00"=
,"Grid outage,site went down due to PWC  HUAWEI dysfunction //He reset it a=
nd site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectifier",=
"Rectifier Module Overloaded","Grid outage,site went down due to PWC  HUAWE=
I dysfunction //He reset it and site on Gen","christelle.ngonga@matech-came=
roun.com","274","27-06-2025 17:16:32","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005356596","Evo=
doula MTN","","27-06-2025 16:49:32","27-06-2025 16:43:21","27-06-2025 17:29=
:21","Grid fluctuation. Site went down because Gen failed to start due to G=
rid bad voltage //Grid power stabilized","TIENTCHEU NZETCHIEU GAEL","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid flu=
ctuation. Site went down because Gen failed to start due to Grid bad voltag=
e //Grid power stabilized","franck.nkomot@matech-cameroun.com","371","27-06=
-2025 16:49:32","MATECH CMR"
"Closed Complete","Site Down","CTR_356","IHS_YND_376","NOCINC0005356565","M=
amb","","27-06-2025 16:49:01","27-06-2025 16:44:25","27-06-2025 16:46:59","=
No power issue, Site on Grid Ubaie: 54.3 V, The FME Tx Etienne/695033981 Fr=
om Huawei is informed.","Kemeni Franklin","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, Site =
on Grid Ubaie: 54.3 V, The FME Tx Etienne/695033981 From Huawei is informed=
.","christelle.ngonga@matech-cameroun.com","277","27-06-2025 16:49:01","MAT=
ECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005356440","Eko=
umdoum OCM","","27-06-2025 16:34:09","27-06-2025 16:26:05","27-06-2025 18:1=
7:05","Grid outage,site went down because Gen failed to start due to PWC ZT=
E dysfunction//He reset it and started the Gen manually","Albran Byorel","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage,site went down because Gen failed to start due to PWC ZTE dysfunctio=
n//He reset it and started the Gen manually","franck.nkomot@matech-cameroun=
.com","485","27-06-2025 16:34:09","MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0005356432","B=
astos Bir","","27-06-2025 16:32:16","27-06-2025 16:31:06","27-06-2025 17:37=
:31","No power issue, site is on Gen with Ubaie=3D53.3 V site on grid ,TX f=
me Eloundou bertrant(652586578) from Huawei is informed","Mboua Thierry","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue, site is on Gen with Ubaie=3D53.3 V site on grid ,=
TX fme Eloundou bertrant(652586578) from Huawei is informed","christelle.ng=
onga@matech-cameroun.com","71","27-06-2025 16:32:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005356195","MEHANDAN=
","","27-06-2025 15:55:37","27-06-2025 15:51:53","28-06-2025 00:15:32","Cas=
caded Incident from TTO5524919","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","224","27-06-2025 15:55:37","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005356188","O=
dza II OCM","IHS_YND_528","27-06-2025 15:55:01","27-06-2025 15:51:53","27-0=
6-2025 15:59:05","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","christelle.ngonga@matech-cameroun.com","190","27-0=
6-2025 15:55:01","MATECH CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0005356045","N=
sam Sofavinc T0","","27-06-2025 15:28:34","27-06-2025 15:22:26","27-06-2025=
 15:58:26","No power issue on site Ub: 52.6 V site on gen,TX Fme Henry ( 69=
1145055/ Huawei ) is informed","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site Ub: 52.6 V site on gen,TX Fme Henry ( 691145055/ Huawei ) is informe=
d","christelle.ngonga@matech-cameroun.com","369","27-06-2025 15:28:34","MAT=
ECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005356008","ELO=
UMDEM CARRIERE 2","","27-06-2025 15:21:41","27-06-2025 14:40:59","27-06-202=
5 17:49:12","Grid outage. Gen failed to start due to AVR faulty//We replace=
 AVR and site on Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - AVR","Grid outage. Gen failed to start due to AVR faulty//We repla=
ce AVR and site on Gen","franck.nkomot@matech-cameroun.com","26279","27-06-=
2025 15:21:41","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0005355978","Eto=
 koss Yde","","27-06-2025 15:15:00","27-06-2025 15:05:39","27-06-2025 15:11=
:39","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, Site went down before Gen start due to poor backup =
// Grid returned","franck.nkomot@matech-cameroun.com","262947","27-06-2025 =
15:15:00","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005355968","MEF=
OU ASSI","IHS_YND_737","27-06-2025 15:13:12","27-06-2025 15:05:39","27-06-2=
025 15:11:39","Grid outage, Site went down before Gen start due to poor bac=
kup // Grid returned","Fanda Brice","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Grid returned","franck.nkomot@matech-cameroun.=
com","455","27-06-2025 15:13:12","MATECH CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0005355816","Nko=
mkana","","27-06-2025 14:58:01","27-06-2025 14:52:44","27-06-2025 15:00:45"=
,"Grid Only, No space to deploy MDGE// Grid returned","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to de=
ploy MDGE// Grid returned","franck.nkomot@matech-cameroun.com","462","27-06=
-2025 14:58:01","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005355811","Fla=
menco","","27-06-2025 14:57:04","27-06-2025 14:52:12","27-06-2025 15:04:12"=
,"Active//No power issue on site Ubaie =3D54,3V site on Grid TX Fme Tsague =
Brice (650214096) from Huawei is informed","Mboua Thierry","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site Ubaie =3D54,3V site on Grid TX Fme Tsague Brice =
(650214096) from Huawei is informed","franck.nkomot@matech-cameroun.com","2=
93","27-06-2025 14:57:04","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005355598","Car=
refour Simbock","","27-06-2025 14:14:57","27-06-2025 14:08:50","27-06-2025 =
14:59:26","Grid outage, site went down because gen failed to start with ala=
rm overvoltage // He reset gen card and gen manually started","Hyemafo Gild=
as","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Grid out=
age, site went down because gen failed to start with alarm overvoltage // H=
e reset gen card and gen manually started","loic.noumsi@matech-cameroun.com=
","368","27-06-2025 14:14:57","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005355574","Elo=
umdem stade","","27-06-2025 14:09:07","27-06-2025 14:00:42","27-06-2025 14:=
38:14","Grid fluctuations, site went down because Gen failed to start due t=
o Grid bad voltage // Grid power stabilised","Fanda Brice","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid fluctuations=
, site went down because Gen failed to start due to Grid bad voltage // Gri=
d power stabilised","loic.noumsi@matech-cameroun.com","506","27-06-2025 14:=
09:07","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005355572","A=
kak-Nkozoa-MTN-IHS","","27-06-2025 14:08:50","27-06-2025 14:00:41","27-06-2=
025 17:20:41","Grid fluctuations, site went down because Gen failed to star=
t due to Grid bad voltage // Site stabilised","Fabrice Pouakam","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tions, site went down because Gen failed to start due to Grid bad voltage /=
/ Site stabilised","gaelle.njiofack@matech-cameroun.com","491","27-06-2025 =
14:08:50","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005355549","Evo=
doula MTN","","27-06-2025 14:03:24","27-06-2025 13:56:12","27-06-2025 14:07=
:10","Grid fluctuation. Site went down because Gen failed to start due to G=
rid bad voltage //Grid power stabilized","TIENTCHEU NZETCHIEU GAEL","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid flu=
ctuation. Site went down because Gen failed to start due to Grid bad voltag=
e //Grid power stabilized","loic.noumsi@matech-cameroun.com","433","27-06-2=
025 14:03:24","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005355501","A=
bome","","27-06-2025 13:51:16","27-06-2025 13:43:08","27-06-2025 13:59:37",=
"	Grid outage, site went down because Gen failed to start due to Gen card f=
aulty caused by lightning // Grid return","MINKA NICOLAS","Force Majeure","=
Natural Disaster","Thunderstrike","Equipment Damaged","	Grid outage, site w=
ent down because Gen failed to start due to Gen card faulty caused by light=
ning // Grid return","gaelle.njiofack@matech-cameroun.com","489","27-06-202=
5 13:51:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005355292","Montee-J=
ouvence","","27-06-2025 13:11:19","27-06-2025 12:48:40","27-06-2025 13:54:1=
7","Cascaded Incident from TTO5523812","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuations, Site went d=
own due to Gen overload (15KVA//130A) // grid stabilized","system","271052"=
,"27-06-2025 13:11:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0005355290","Mendong =
vallee","","27-06-2025 13:11:18","27-06-2025 12:48:40","27-06-2025 13:54:17=
","Cascaded Incident from TTO5523812","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuations, Site went down =
due to Gen overload (15KVA//130A) // grid stabilized","system","271051","27=
-06-2025 13:11:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0005355291","Mendong =
Maeture","","27-06-2025 13:11:18","27-06-2025 12:48:40","27-06-2025 13:54:1=
7","Cascaded Incident from TTO5523812","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuations, Site went d=
own due to Gen overload (15KVA//130A) // grid stabilized","system","271053"=
,"27-06-2025 13:11:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005355288","Minka","=
","27-06-2025 13:11:16","27-06-2025 12:59:07","27-06-2025 13:02:31","Cascad=
ed Incident from TTO5523902","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No powwer issue on site Ubaie=3D51.7 V=
 site on Gen. site impacted by Ngoumou which is not managing by IHS","syste=
m","263220","27-06-2025 13:11:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005355289","Mom","",=
"27-06-2025 13:11:16","27-06-2025 12:59:07","27-06-2025 13:02:31","Cascaded=
 Incident from TTO5523902","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Active//No powwer issue on site Ubaie=3D51.7 V s=
ite on Gen. site impacted by Ngoumou which is not managing by IHS","system"=
,"263222","27-06-2025 13:11:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005355287","OTELE MT=
N","","27-06-2025 13:11:16","27-06-2025 12:59:07","27-06-2025 13:02:31","Ca=
scaded Incident from TTO5523902","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No powwer issue on site Ubaie=3D51=
.7 V site on Gen. site impacted by Ngoumou which is not managing by IHS","s=
ystem","263221","27-06-2025 13:11:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005355286","OLAMA","=
","27-06-2025 13:11:15","27-06-2025 12:59:07","27-06-2025 13:02:31","Cascad=
ed Incident from TTO5523902","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No powwer issue on site Ubaie=3D51.7 V=
 site on Gen. site impacted by Ngoumou which is not managing by IHS","syste=
m","263219","27-06-2025 13:11:15","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005355269","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","27-06-2025 13:07:=
37","27-06-2025 12:59:07","27-06-2025 13:02:31","Active//No powwer issue on=
 site Ubaie=3D51.7 V site on Gen. site impacted by Ngoumou which is not man=
aging by IHS","Fanda Brice","Customer Equipment Failure","Active","Active E=
quipment Failure","Affected by 3rd Party Site","Active//No powwer issue on =
site Ubaie=3D51.7 V site on Gen. site impacted by Ngoumou which is not mana=
ging by IHS","loic.noumsi@matech-cameroun.com","512","27-06-2025 13:07:37",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005355241","ELOUMDEM=
 CARRIERE 2","","27-06-2025 13:03:20","27-06-2025 12:50:04","27-06-2025 13:=
56:23","Cascaded Incident from TTO5523843","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down d=
ue to poor batteries backup before Gen start // Grid return","system","2852=
36","27-06-2025 13:03:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005355240","Eto koss=
 Yde","","27-06-2025 13:03:19","27-06-2025 12:50:04","27-06-2025 13:56:23",=
"Cascaded Incident from TTO5523843","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down due to p=
oor batteries backup before Gen start // Grid return","system","285237","27=
-06-2025 13:03:19","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005355220","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","27-06-2025 12:58:11","27-06-2025 12:50=
:04","27-06-2025 13:56:23","Grid outage, Site went down due to poor batteri=
es backup before Gen start // Grid return","Fanda Brice","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site=
 went down due to poor batteries backup before Gen start // Grid return","l=
oic.noumsi@matech-cameroun.com","489","27-06-2025 12:58:11","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005355198","Lad=
a I Yde","","27-06-2025 12:52:49","27-06-2025 12:43:36","27-06-2025 14:58:3=
4","Site went Down due to insufficient of rectifiers // He added 01 rectifi=
er","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went Down due to insufficient of rectifiers // He added 01 re=
ctifier","loic.noumsi@matech-cameroun.com","554","27-06-2025 12:52:49","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005355197","M=
endong","IHS_YND_692, IHS_YND_569, IHS_YND_236","27-06-2025 12:52:48","27-0=
6-2025 12:48:40","27-06-2025 13:54:17","Grid fluctuations, Site went down d=
ue to Gen overload (15KVA//130A) // grid stabilized","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuations, Si=
te went down due to Gen overload (15KVA//130A) // grid stabilized","gaelle.=
njiofack@matech-cameroun.com","249","27-06-2025 12:52:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005355074","Nsam esc=
ale LP","","27-06-2025 12:34:06","27-06-2025 12:24:19","27-06-2025 12:57:23=
","Cascaded Incident from TTO5523659","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Site went down due to disjunction of Rectifie=
rs CB (50A) in the PWC // He rearmed it, site on Grid","system","1221797","=
27-06-2025 12:34:06","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005355058","Nsa=
m Sofavinc","IHS_YND_732","27-06-2025 12:31:28","27-06-2025 12:24:19","27-0=
6-2025 12:57:23","Site went down due to disjunction of Rectifiers CB (50A) =
in the PWC // He rearmed it, site on Grid","MINKA NICOLAS","Equipment Repai=
r","Passive","Rectifier","Rectifier - Circuit Breaker","Site went down due =
to disjunction of Rectifiers CB (50A) in the PWC // He rearmed it, site on =
Grid","loic.noumsi@matech-cameroun.com","430","27-06-2025 12:31:28","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_625","IHS_YND_181","NOCINC0005355020","M=
imboman3","IHS_YND_512","27-06-2025 12:26:35","27-06-2025 12:20:27","27-06-=
2025 12:50:45","Grid outage.gen failed to start due to alarm overcurrent//G=
rid return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Grid outage.gen failed to start due to alarm overcurren=
t//Grid return","gaelle.njiofack@matech-cameroun.com","370","27-06-2025 12:=
26:35","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005354841","M=
imboman-Ecole","","27-06-2025 11:59:27","27-06-2025 12:20:27","27-06-2025 1=
2:40:20","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage.gen failed to start due to alarm overcurren=
t//Grid return","gaelle.njiofack@matech-cameroun.com","265514","27-06-2025 =
11:59:27","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005354740","M=
vog Mbi New","","27-06-2025 11:45:13","27-06-2025 11:43:04","27-06-2025 12:=
29:40","SS IHS Francoit was on site for work , and confirm us that, site we=
nt down due to PWC Overload // site Stabilized","MINKA NICOLAS","Equipment =
Repair","Passive","Rectifier","Rectifier Module Overloaded","site went down=
 due to PWC Overload // site Stabilized","gaelle.njiofack@matech-cameroun.c=
om","130","27-06-2025 11:45:13","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005354737","A=
hala","","27-06-2025 11:44:05","27-06-2025 11:41:55","27-06-2025 12:17:02",=
"Grid outage, site went down due to fuel shortage // Refuelling done","Hyem=
afo Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, =
site went down due to fuel shortage // Refuelling done","gaelle.njiofack@ma=
tech-cameroun.com","132","27-06-2025 11:44:05","MATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0005354731","S=
ofavinc","","27-06-2025 11:43:24","27-06-2025 11:35:17","27-06-2025 12:47:1=
1","Grid outage, Gen start but did not feeding the site because his contact=
or is faulty // Contactor bay-pass and site on Gen","MINKA NICOLAS","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Load Contactor","
Grid outage, Gen start but did not feeding the site because his contactor i=
s faulty // Contactor bay-pass and site on Gen","gaelle.njiofack@matech-cam=
eroun.com","488","27-06-2025 11:43:24","MATECH CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0005354638","Nom=
ayos","","27-06-2025 11:31:08","27-06-2025 11:22:02","27-06-2025 11:33:20",=
"Site down because SS IHS (Felix ZAMBE) is on site for PM (test activity)//=
 End of work","Fanda Brice","Installation Activity","Passive","Planned Acti=
vity","Installation Activity","Site down because SS IHS (Felix ZAMBE) is on=
 site for PM (test activity)// End of work","loic.noumsi@matech-cameroun.co=
m","547","27-06-2025 11:31:08","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005354623","B=
arriere IHS","","27-06-2025 11:27:43","27-06-2025 11:21:17","27-06-2025 15:=
14:59","Grid outage, Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went Down due t=
o Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return",=
"gaelle.njiofack@matech-cameroun.com","388","27-06-2025 11:27:43","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005354613","Mvog-Eba=
nda","","27-06-2025 11:25:43","27-06-2025 11:16:33","27-06-2025 11:46:00","=
Cascaded Incident from TTO5523164","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
fuel shortage // Refuelling done","system","276520","27-06-2025 11:25:43","=
MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005354605","A=
bom","IHS_YND_269","27-06-2025 11:23:44","27-06-2025 11:16:33","27-06-2025 =
11:46:00","Grid outage, site went down due to fuel shortage // Refuelling d=
one","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outage","Grid=
 outage, site went down due to fuel shortage // Refuelling done","gaelle.nj=
iofack@matech-cameroun.com","433","27-06-2025 11:23:44","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005354574","Fla=
menco","","27-06-2025 11:18:28","27-06-2025 11:10:15","27-06-2025 11:22:02"=
,"Grid outage, site went down because Gen failed to start due to poor backu=
p // Site stabilised","Mboua Thierry","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, site went down because =
Gen failed to start due to poor backup // Site stabilised","loic.noumsi@mat=
ech-cameroun.com","494","27-06-2025 11:18:28","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005354557","NKO=
MKANA ELIZA HOTEL","","27-06-2025 11:16:38","27-06-2025 11:10:30","27-06-20=
25 11:18:35","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Site went down due to PWC Overloaded =
and SS IHS Bernard Atangana confirmed // Site stabilised","loic.noumsi@mate=
ch-cameroun.com","369","27-06-2025 11:16:38","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0005354434","Mes=
sassi Ngonlonk","","27-06-2025 10:56:19","27-06-2025 10:54:07","27-06-2025 =
11:26:03","Grid outage site went down because Gen failed to start due to Ge=
n card faulty // He reset it and he Manually Started Gen","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e site went down because Gen failed to start due to Gen card faulty // He r=
eset it and he Manually Started Gen","loic.noumsi@matech-cameroun.com","133=
","27-06-2025 10:56:19","MATECH CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0005354222","N=
kolndongo","","27-06-2025 10:19:28","27-06-2025 10:15:21","27-06-2025 13:39=
:25","Site went down due to MPR burnt // MPR replacement ","MINKA NICOLAS",=
"Equipment Repair","Passive","Rectifier","Rectifier Cabinet","Site went dow=
n due to MPR burnt // MPR replacement ","gaelle.njiofack@matech-cameroun.co=
m","248","27-06-2025 10:19:28","MATECH CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0005354218","Ema=
na","","27-06-2025 10:18:06","27-06-2025 10:17:00","27-06-2025 12:41:00","S=
ite went down due to PSC3 dysfunctionning//We reset psc3 controller and sit=
e on grid","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","=
ATS-AMF Issue","Site went down due to PSC3 dysfunctionning//We reset psc3 c=
ontroller and site on grid","loic.noumsi@matech-cameroun.com","68","27-06-2=
025 10:18:06","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005354205","Lad=
a I Yde","","27-06-2025 10:14:18","27-06-2025 10:06:10","27-06-2025 12:23:5=
1","Grid outage, site went down due to (1/3) rectifier dysfunctionning // H=
e reset it","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Grid outage, site went down due to (1/3) rectifier dysfunc=
tionning // He reset it","gaelle.njiofack@matech-cameroun.com","490","27-06=
-2025 10:14:18","MATECH CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0005354166","C=
lge-Advantiste","","27-06-2025 10:06:02","27-06-2025 10:05:58","27-06-2025 =
11:57:21","Site went down due to disjunction of CB (80A) in the OCM BTS // =
He rearmed it, site on Grid","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","BTS Breaker Tripped","Site went down due to disjunction of =
CB (80A) in the OCM BTS // He rearmed it, site on Grid","gaelle.njiofack@ma=
tech-cameroun.com","6","27-06-2025 10:06:02","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005354025","M=
fou OCM","","27-06-2025 09:40:29","24-06-2025 22:55:44","24-06-2025 23:10:5=
8","Bactracking Grid Outage, Site Down before gen Started due to poor backu=
p //GEN automatically started","Mba Lazare Herve","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Bactracking Grid Outage,=
 Site Down before gen Started due to poor backup //GEN automatically starte=
d","mouliom.anselme@matech-cameroun.com","211485","27-06-2025 09:40:29","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005353940","B=
arriere","","27-06-2025 09:29:13","24-06-2025 22:04:05","24-06-2025 22:13:0=
4","Backtracking No power issue on site Ubay: 54.6V site on Grid  TX Fme SA=
MBA (654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Backtrack=
ing No power issue on site Ubay: 54.6V site on Grid  TX Fme SAMBA (65426605=
8/Huawei) is informed.","mouliom.anselme@matech-cameroun.com","213908","27-=
06-2025 09:29:13","MATECH CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0005353872","B=
astos Ekoudou","","27-06-2025 09:21:47","24-06-2025 22:52:02","24-06-2025 2=
3:07:06","Bactracking Grid outage.gen failed to start due to poor backup//G=
rid return","Mboua Thierry","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Bactracking Grid outage.gen failed to start du=
e to poor backup//Grid return","mouliom.anselme@matech-cameroun.com","21058=
6","27-06-2025 09:21:47","MATECH CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0005353801","K=
ondengui","","27-06-2025 09:12:31","24-06-2025 22:07:43","24-06-2025 22:10:=
48","Bactracking Active//No power issue, site is on battery  with Ubaie=3D4=
9.9V, Eloundou bertrand(652586578) from Huawei is informed","Albran Byorel"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Bactracking Active//No power issue, site is on battery  with U=
baie=3D49.9V, Eloundou bertrand(652586578) from Huawei is informed","moulio=
m.anselme@matech-cameroun.com","212690","27-06-2025 09:12:31","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005353771","C=
-Supreme","","27-06-2025 09:04:48","27-06-2025 08:56:30","27-06-2025 09:53:=
04","	Active // No power issue, site on Battery with Ubaie=3D55V, Brice Tsa=
gue (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","	Active // No power=
 issue, site on Battery with Ubaie=3D55V, Brice Tsague (650 21 40 96 / Huaw=
ei) is informed","gaelle.njiofack@matech-cameroun.com","499","27-06-2025 09=
:04:48","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005353722","Sof=
avinc","","27-06-2025 08:52:36","27-06-2025 08:48:30","27-06-2025 09:40:43"=
,"Grid outage, Gen start but did not feeding the site because his contactor=
 is faulty // Contactor bay-pass and site on Gen","MINKA NICOLAS","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Load Contactor","27-06-2025 09:40:43=
","loic.noumsi@matech-cameroun.com","247","27-06-2025 08:52:36","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005353709","Messassi=
 okolo","","27-06-2025 08:51:07","27-06-2025 08:46:12","27-06-2025 11:40:04=
","Cascaded Incident from TTO5522159","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (Gen Noise) // Grid returned","system","285=
505","27-06-2025 08:51:07","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005353705","E=
MANA BILICK CITY","IHS_YND_279","27-06-2025 08:50:24","27-06-2025 08:46:12"=
,"27-06-2025 11:45:12","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid returned","Fabrice Pouakam","Access Denial",=
"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid=
 outage, site down because site behaves as Grid only site (Gen Noise) // Gr=
id returned","gaelle.njiofack@matech-cameroun.com","254","27-06-2025 08:50:=
24","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005353632","Evo=
doula MTN","","27-06-2025 08:35:31","27-06-2025 08:34:23","27-06-2025 10:40=
:02","Grid outage, site went down because gen started and stopped due to ''=
low oil pressure'' alarm // He Reset the Gen card and gen started Manually"=
,"TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","Grid outage, site went down because gen started and stoppe=
d due to ''undervoltage'' alarm // He Reset the Gen card and gen started Ma=
nually","loic.noumsi@matech-cameroun.com","69","27-06-2025 08:35:31","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0005353626","C=
lge-Advantiste","","27-06-2025 08:33:46","27-06-2025 08:28:40","27-06-2025 =
09:17:03","Site went down due to disjunction of CB (80A) in the OCM BTS // =
He rearmed it, site on Grid","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","BTS Breaker Tripped","Site went down due to disjunction of =
CB (80A) in the OCM BTS // He rearmed it, site on Grid","loic.noumsi@matech=
-cameroun.com","307","27-06-2025 08:33:46","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005353548","Aka=
k-Nkozoa-MTN-IHS","","27-06-2025 08:11:35","27-06-2025 08:03:17","27-06-202=
5 13:32:59","Grid fluctuations, site went down due to Grid bad voltage // S=
ite stabilised","Fabrice Pouakam","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","Grid fluctuations, site went down due to G=
rid bad voltage // Site stabilised","loic.noumsi@matech-cameroun.com","500"=
,"27-06-2025 08:11:35","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005353403","B=
arriere","","27-06-2025 07:45:54","27-06-2025 07:45:40","27-06-2025 08:05:1=
9","	Active// No power issue on site Ubay: 54.5V site on Gen TX Fme SAMBA (=
654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Active// No p=
ower issue on site Ubay: 54.5V site on Gen TX Fme SAMBA (654266058/Huawei) =
is informed.","gaelle.njiofack@matech-cameroun.com","16","27-06-2025 07:45:=
54","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005353397","E=
SSOS OASIS 1111","","27-06-2025 07:44:34","27-06-2025 07:42:27","27-06-2025=
 17:54:27","Grid outage, Site went down because Gen overload (17kva, 250A) =
// Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Grid outage, Site went down because Gen overload (17kva, =
250A) // Grid returned","gaelle.njiofack@matech-cameroun.com","128","27-06-=
2025 07:44:34","MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0005353336","Abo=
me","","27-06-2025 07:25:49","27-06-2025 07:17:42","27-06-2025 08:51:50","	=
Grid outage, site went down because Gen failed to start due to Gen card fau=
lty caused by lightning //  Gen started manually","MINKA NICOLAS","Force Ma=
jeure","Natural Disaster","Thunderstrike","Equipment Damaged","	Grid outage=
, site went down because Gen failed to start due to Gen card faulty caused =
by lightning //  Gen started manually","loic.noumsi@matech-cameroun.com","4=
89","27-06-2025 07:25:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0005353320","Odza II =
OCM","","27-06-2025 07:21:44","27-06-2025 07:14:21","27-06-2025 08:49:32","=
Cascaded Incident from TTO5521704","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to CB(32 A)disju=
ncted causing by lightning//We rearmed the CB site on gen","system","291008=
","27-06-2025 07:21:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005353321","MEHANDAN=
","","27-06-2025 07:21:44","27-06-2025 07:14:21","27-06-2025 08:49:32","Cas=
caded Incident from TTO5521704","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to CB(32 A)disjunct=
ed causing by lightning//We rearmed the CB site on gen","system","291009","=
27-06-2025 07:21:44","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005353304","O=
dza-PK10","IHS_YND_527, IHS_YND_528","27-06-2025 07:18:27","27-06-2025 07:1=
4:21","27-06-2025 08:49:32","Site went down due to CB(32 A)disjuncted causi=
ng by lightning//We rearmed the CB site on gen","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Load Contactor","Site went down due to=
 CB(32 A)disjuncted causing by lightning//We rearmed the CB site on gen","g=
aelle.njiofack@matech-cameroun.com","247","27-06-2025 07:18:27","MATECH CMR=
"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005353225","Jou=
vence Mbenda","","27-06-2025 06:57:43","27-06-2025 06:51:39","27-06-2025 07=
:43:37","Grid outage.site went down due to grid fluctuations//We bypass gri=
d and gen manually started ","Hyemafo Gildas","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid outage.site went down due=
 to grid fluctuations//We bypass grid and gen manually started ","loic.noum=
si@matech-cameroun.com","365","27-06-2025 06:57:43","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005353165","C=
rf-Nsam","","27-06-2025 06:45:33","27-06-2025 06:41:23","27-06-2025 07:56:3=
9","Active// No power issue on site Ubaie =3D53.6V site on Grid The TX FME =
Henri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (69=
9949693) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","25=
2","27-06-2025 06:45:33","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005352985","Eko=
umdoum OCM","","27-06-2025 05:38:07","27-06-2025 05:32:00","27-06-2025 07:5=
8:17","Grid outage,gen failed to start due to ATS dysfunctionning //He rese=
t it and site on GEN Power issue resolved at MTN but remains down at OCM Em=
ail of soft reset has done Lionnel from H","Albran Byorel","Equipment Repai=
r","Passive","Control Panel","ATS-AMF Issue","Grid outage,gen failed to sta=
rt due to ATS dysfunctionning //He reset it and site on GEN Power issue res=
olved at MTN but remains down at OCM Email of soft reset has done Lionne(65=
5184876)l from Huawei is working on site for solve the issue ","franck.nkom=
ot@matech-cameroun.com","388","27-06-2025 05:38:07","MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0005352928","Abo=
me","","27-06-2025 05:25:51","27-06-2025 05:22:42","27-06-2025 06:27:13","G=
rid outage, site went down because Gen failed to start due to Gen card faul=
ty caused by lightning // He reset it and started Gen manually","MINKA NICO=
LAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage, site went down because Gen failed to start due to Gen card faulty ca=
used by lightning // He reset it and started Gen manually","edwige.kapawo@m=
atech-cameroun.com","191","27-06-2025 05:25:51","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005352847","N=
kolso","","27-06-2025 05:01:20","27-06-2025 04:55:08","27-06-2025 07:39:51"=
,"Grid fluctuation, Site went down because gen failed to start due to grid =
bad voltage// He bypassed the Grid and started Gen manually","TIENTCHEU NZE=
TCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation, Site went down because gen failed to start du=
e to grid bad voltage// He bypassed the Grid and started Gen manually","edw=
ige.kapawo@matech-cameroun.com","373","27-06-2025 05:01:20","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005352748","C=
rf-Nsam","","27-06-2025 04:11:48","27-06-2025 04:02:59","27-06-2025 04:03:5=
9","Active//No power issue on site Ubaie =3D56.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D56.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","franck.nkomot@matech-cameroun.com","530",=
"27-06-2025 04:11:48","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005352632","M=
eyo","IHS_YND_257","27-06-2025 03:07:07","27-06-2025 03:04:58","27-06-2025 =
03:09:05","ACTIVE //No power issue Ubaie: 54,8V Site on Grid The Tx Fme Geo=
rges /6974661814 from huawei is informed","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTI=
VE //No power issue Ubaie: 54,8V Site on Grid The Tx Fme Georges /697466181=
4 from huawei is informed","edwige.kapawo@matech-cameroun.com","129","27-06=
-2025 03:07:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_583","NOCINC0005352615","Nsam Sof=
avinc T0","","27-06-2025 02:53:31","27-06-2025 02:50:27","27-06-2025 02:58:=
47","Cascaded Incident from TTO5520918","MINKA NICOLAS","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active // No power issue, site is=
 on Gen with Ubaie=3D54.6V, TX Henri (699949693) from Huawei is informed","=
system","263731","27-06-2025 02:53:31","MATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0005352611","S=
ofavinc","IHS_YND_583","27-06-2025 02:52:38","27-06-2025 02:50:27","27-06-2=
025 02:58:47","Active // No power issue, site is on Gen with Ubaie=3D54.6V,=
 TX Henri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue, site is on Gen with Ubaie=3D54.6V, TX Henri (6999=
49693) from Huawei is informed","edwige.kapawo@matech-cameroun.com","132","=
27-06-2025 02:52:38","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005352587","A=
hala","","27-06-2025 02:43:20","27-06-2025 03:04:58","27-06-2025 03:09:05",=
"","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","Cascade Act=
ive","ACTIVE //No power issue Ubaie: 54,8V Site on Grid The Tx Fme Georges =
/6974661814 from huawei is informed","edwige.kapawo@matech-cameroun.com","1=
212224","27-06-2025 02:43:20","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005352569","N=
kolfon Cimencam","","27-06-2025 02:33:32","27-06-2025 02:32:18","27-06-2025=
 02:34:45","Site is impacted by Afanoya II(Not manage by HIS)","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","Site is impacted by Afanoya II(Not manage by HIS)"=
,"edwige.kapawo@matech-cameroun.com","75","27-06-2025 02:33:32","MATECH CMR=
"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005351994","A=
bome","","27-06-2025 01:06:20","27-06-2025 01:04:12","27-06-2025 01:10:02",=
"Active// No power issue on site Ubay 53.7V site on Grid and The TX FME Leo=
nel Steve (655184876) from huawei is informed","MINKA NICOLAS","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power issue on site Ubay 53.7V site on Grid and The TX FME Leon=
el Steve (655184876) from huawei is informed","edwige.kapawo@matech-camerou=
n.com","129","27-06-2025 01:06:20","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005351723","ESS=
OS OASIS 1111","","27-06-2025 00:04:46","27-06-2025 00:00:32","27-06-2025 0=
0:16:32","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) // Grid returned","franck.nkomot@matech-cameroun.com","255","27-06-2025=
 00:04:46","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005351715","Lad=
a I Yde","","27-06-2025 00:01:47","26-06-2025 23:58:46","27-06-2025 01:54:4=
6","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","franck.nkomot@matech-cameroun.com","182","27-06-2025 00:01:47","MATECH C=
MR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005351531","Lad=
a I Yde","","26-06-2025 23:07:42","26-06-2025 22:57:59","26-06-2025 23:33:5=
9","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","franck.nkomot@matech-cameroun.com","584","26-06-2025 23:07:42","MATECH C=
MR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005351510","Evo=
doula MTN","","26-06-2025 23:02:48","26-06-2025 22:54:29","26-06-2025 23:22=
:29","Site went down because Gen failed to start due to Grid bad voltage //=
Grid power stabilized","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Site went down because Gen=
 failed to start due to Grid bad voltage //Grid power stabilized","franck.n=
komot@matech-cameroun.com","500","26-06-2025 23:02:48","MATECH CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0005351484","C=
lge-Advantiste","","26-06-2025 22:53:44","26-06-2025 22:08:15","27-06-2025 =
00:01:15","Site went down due to CB 125A disjuncted in PWC//he reamed the C=
B","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Circuit Breaker Issue","Site went down due to CB 125A disjuncted in P=
WC//he reamed the CB","franck.nkomot@matech-cameroun.com","2729","26-06-202=
5 22:53:44","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005351379","ESS=
OS OASIS 1111","","26-06-2025 22:31:56","26-06-2025 22:26:24","26-06-2025 2=
2:38:24","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) // Grid returned","franck.nkomot@matech-cameroun.com","333","26-06-2025=
 22:31:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005351310","MEHANDAN=
","","26-06-2025 22:15:15","26-06-2025 22:07:03","26-06-2025 22:12:10","Cas=
caded Incident from TTO5519466","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","280639","26-06-2025 22:15:15","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005351289","Odz=
a II OCM","IHS_YND_528","26-06-2025 22:11:21","26-06-2025 22:07:03","26-06-=
2025 22:12:49","Grid fluctuations, site went down because gen failed to sta=
rt due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctua=
tions, site went down because gen failed to start due to PWC ZTE malfunctio=
n // Grid stabilized","gerard.tchangoue@matech-cameroun.com","260","26-06-2=
025 22:11:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_141","NOCINC0005351275","New-Marc=
he-Melen","","26-06-2025 22:09:03","26-06-2025 20:52:22","27-06-2025 09:42:=
57","Cascaded Incident from TTO5519433","Paul BIBOUM","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,no space to deploy m=
obile gen //Grid return","system","1277870","26-06-2025 22:09:03","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0005351170","Awae Ewo=
nkan","","26-06-2025 21:50:12","26-06-2025 13:08:00","26-06-2025 15:54:31",=
"Backtraking No power issue on site U:54.2 v Tx Fme Henri  (691145055 ) of =
Huawei is informed","Albran Byorel","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","Backtraking No power issue =
on site U:54.2 v Tx Fme Henri  (691145055 ) of Huawei is informed","christe=
lle.ngonga@matech-cameroun.com","31334","26-06-2025 21:50:12","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005350987","M=
fou OCM","","26-06-2025 21:34:04","26-06-2025 21:18:23","26-06-2025 22:09:2=
3","Grid outage.gen started and stoped due to alarm ""low oil pressure""//H=
e reset card GE and gen manually started","Mba Lazare Herve","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen started a=
nd stoped due to alarm ""low oil pressure""//He reset card GE and gen manua=
lly started","christelle.ngonga@matech-cameroun.com","942","26-06-2025 21:3=
4:04","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005350941","ELO=
UMDEM CARRIERE 2","","26-06-2025 21:25:30","26-06-2025 21:25:11","26-06-202=
5 21:34:02","Site went down due to CB (63A)dysjucnted in the DC box// He re=
amed CB( 63A), site on grid","Fanda Brice","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to=
 CB (63A)dysjucnted in the DC box// He reamed CB( 63A), site on grid","gera=
rd.tchangoue@matech-cameroun.com","20","26-06-2025 21:25:30","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005350879","Bit=
eng-Maetur","","26-06-2025 21:17:25","26-06-2025 21:10:16","26-06-2025 22:1=
4:16","Active//No power issue on site Ubaie =3D50V site on Grid The TX FME =
Henri (699949693) from Huawei is informed","Mba Lazare Herve","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site Ubaie =3D50V site on Grid The TX FME Henri (6=
99949693) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","=
430","26-06-2025 21:17:25","MATECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0005350861","Soa=
","","26-06-2025 21:14:31","26-06-2025 21:10:26","26-06-2025 22:06:57","Gri=
d outage, site went down because gen failed to start and stopped with alarm=
 over current due to load // He reduced the load, site on gen","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage, site went down because gen failed to start and stopped with alarm ove=
r current due to load // He reduced the load, site on gen","gerard.tchangou=
e@matech-cameroun.com","3907","26-06-2025 21:14:31","MATECH CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0005350825","Mel=
en Ba'aba","","26-06-2025 21:09:43","26-06-2025 21:08:31","26-06-2025 23:28=
:31","Site went down due to insufficiency of rectifiers on site // He reset=
 rectifiers, site on Grid","Siligap Boris","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficiency of rectifi=
ers on site // He reset rectifiers, site on Grid","gerard.tchangoue@matech-=
cameroun.com","73","26-06-2025 21:09:43","MATECH CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0005350781","An-=
Marche-Melen","IHS_YND_141","26-06-2025 21:00:31","26-06-2025 20:52:22","27=
-06-2025 09:44:46","Grid outage,no space to deploy mobile gen //Grid return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage,no space to deploy mobile gen //Grid return","gerard.tchangoue@ma=
tech-cameroun.com","490","26-06-2025 21:00:31","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005350700","SOA=
 TOWN","","26-06-2025 20:50:31","26-06-2025 20:47:24","26-06-2025 22:16:45"=
,"Grid outage, site went down because Gen failed to start due to charger Ge=
n battery faulty // He started Gen with an external battery","Siligap Boris=
","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid =
outage, site went down because Gen failed to start due to charger Gen batte=
ry faulty // He started Gen with an external battery","gerard.tchangoue@mat=
ech-cameroun.com","188","26-06-2025 20:50:31","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005350574","NYO=
M FACE MAETUR","","26-06-2025 20:31:57","26-06-2025 20:30:47","26-06-2025 2=
0:32:47","Grid outage, Site went down because Gen failed to start due to Gr=
id bad voltage //Grid stabilised)","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid outage, Site went =
down because Gen failed to start due to Grid bad voltage //Grid stabilised)=
","gerard.tchangoue@matech-cameroun.com","71","26-06-2025 20:31:57","MATECH=
 CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005350525","TSI=
NGA VILLAGE 2","","26-06-2025 20:24:27","26-06-2025 20:21:22","26-06-2025 2=
1:01:30","Site went down due to disjunction of Cb(125A) in PWC // He reamed=
 Cb(125A), site on Gen","Delor Telezing","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of Cb(125A) in PWC // He reamed Cb(125A), site on Gen","gerard.t=
changoue@matech-cameroun.com","186","26-06-2025 20:24:27","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005350439","Par=
adis Hotel","","26-06-2025 20:08:19","26-06-2025 20:02:11","27-06-2025 02:0=
3:12","site Down because vandalized (the power cable theft supplying the sh=
elter. About 15m) // He replaced cable ","Siligap Boris","Site Intrusion","=
Intrusion On Site","Intrusion On Site","Intrusion - Vandalism/Sabotage","si=
te Down because vandalized (the power cable theft supplying the shelter. Ab=
out 15m) // He replaced cable ","gerard.tchangoue@matech-cameroun.com","369=
","26-06-2025 20:08:19","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005350341","Par=
adis Hotel","","26-06-2025 19:46:48","26-06-2025 19:33:40","26-06-2025 19:4=
9:05","site went down due to to relay Q11 dysfunctionning in IPT / / We dis=
connected relay Q11 and site on gen(replacement relay ongoing)","Siligap Bo=
ris","Equipment Repair","Passive","Control Panel","Relay","site went down d=
ue to to relay Q11 dysfunctionning in IPT / / We disconnected relay Q11 and=
 site on gen(replacement relay ongoing)","gerard.tchangoue@matech-cameroun.=
com","789","26-06-2025 19:46:48","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005350300","M=
fou OCM","","26-06-2025 19:36:05","26-06-2025 19:28:58","26-06-2025 19:35:1=
7","Grid Outage, Site Down before gen Started due to poor backup //GEN auto=
matically started","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen St=
arted due to poor backup //GEN automatically started","christelle.ngonga@ma=
tech-cameroun.com","428","26-06-2025 19:36:05","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005350295","SIM=
BOCK BONAMBAPE","","26-06-2025 19:34:55","26-06-2025 19:33:44","26-06-2025 =
19:35:48","Grid Outage, Site went down before Gen start due to poor backup =
// Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site went down before Gen =
start due to poor backup // Grid returned","gerard.tchangoue@matech-camerou=
n.com","72","26-06-2025 19:34:55","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005350287","T=
SINGA VILLAGE 2","","26-06-2025 19:32:58","26-06-2025 19:30:50","26-06-2025=
 19:52:50","Grid outage, site went down because gen failed to start with al=
arm undervoltage // He reset gen card and gen manually started","Delor Tele=
zing","Equipment Repair","Passive","ACDG Gen","ACDG - Under Voltage","Grid =
outage, site went down because gen failed to start with alarm undervoltage =
// He reset gen card and gen manually started","christelle.ngonga@matech-ca=
meroun.com","129","26-06-2025 19:32:58","MATECH CMR"
"Closed Complete","Site Down","T1112","IHS_YND_074","NOCINC0005350202","Obi=
li Chapelle","","26-06-2025 19:12:23","26-06-2025 19:03:13","26-06-2025 20:=
25:45"," Grid outage, site went down because gen ran until fuel shortage //=
 Refueling done","Paul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Out=
age"," Grid outage, site went down because gen ran until fuel shortage // R=
efueling done","gerard.tchangoue@matech-cameroun.com","551","26-06-2025 19:=
12:23","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0005350178","Nko=
lbisson usines des eaux 2","","26-06-2025 19:04:13","26-06-2025 18:57:01","=
26-06-2025 21:37:49","Grid Outage Site went down because Gen Overload (20KV=
A, 250A) SS IHS Felix Pascaline confirmed// He reduced The load","TIENTCHEU=
 NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid Outage Site went down because Gen Overload (20KVA, 250A) SS IHS Felix=
 Pascaline confirmed// He reduced The load","gerard.tchangoue@matech-camero=
un.com","433","26-06-2025 19:04:13","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005350148","OBA=
M NGOLA OCM","","26-06-2025 18:56:12","26-06-2025 18:49:57","26-06-2025 20:=
38:12","Site went down due to PWC overload //Site stabilised","MINKA NICOLA=
S","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Site went down due to PWC overload //Site stabilised","landry.etame@ihstowe=
rs.com","376","26-06-2025 18:56:12","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005350143","Ron=
d Point Express1114","","26-06-2025 18:55:50","26-06-2025 18:51:44","26-06-=
2025 19:11:58","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Grid returned","gerard.tchangoue@matech-ca=
meroun.com","247","26-06-2025 18:55:50","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0005350078","Mfo=
u EPC","","26-06-2025 18:45:16","26-06-2025 18:28:08","26-06-2025 22:12:49"=
,"Grid outage, Site went down because Gen started and stopped with ""low oi=
l pressure"" alarm// He reset card GE and gen manually started","Mba Lazare=
 Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage, Site went down because Gen started and stopped with ""low oil pre=
ssure"" alarm// He reset card GE and gen manually started","gerard.tchangou=
e@matech-cameroun.com","1164","26-06-2025 18:45:16","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005349973","NKO=
NGKARAK","","26-06-2025 18:27:13","26-06-2025 18:19:50","26-06-2025 19:04:5=
0","Grid outage, site went down because gen start and stopped due to high t=
emp caused by pierced radiator // He added water and manually start the gen=
(Radiator to be repaired)","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","P=
assive","ACDG Gen","ACDG - High Engine Temp - Radiator Leakage","Grid outag=
e, site went down because gen start and stopped due to high temp caused by =
pierced radiator // He added water and manually start the gen(Radiator to b=
e repaired)","gerard.tchangoue@matech-cameroun.com","444","26-06-2025 18:27=
:13","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005349844","Sof=
avinc","","26-06-2025 18:06:10","26-06-2025 18:01:02","26-06-2025 18:37:04"=
,"Grid outage, Gen start but did not feeding the site because his contactor=
 is faulty // Contactor bay-pass and site on Gen","MINKA NICOLAS","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, Gen st=
art but did not feeding the site because his contactor is faulty // Contact=
or bay-pass and site on Gen","gerard.tchangoue@matech-cameroun.com","308","=
26-06-2025 18:06:10","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005349785","ESS=
OS OASIS 1111","","26-06-2025 17:58:15","26-06-2025 17:56:06","26-06-2025 2=
1:47:33","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned	","Siligap Boris","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, Site went down because Gen overload (17kva, 2=
50A) // Grid returned	","gerard.tchangoue@matech-cameroun.com","129","26-06=
-2025 17:58:15","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005349694","Nko=
g-Edzen","","26-06-2025 17:41:13","26-06-2025 17:39:07","26-06-2025 17:40:5=
6","No power issue on site, Site on Battery Ubay =3D 54V The Tx Fme Gregoir=
e (654547479) from Huawei is informed","Parker Tchoup","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site, Site on Battery Ubay =3D 54V The Tx Fme Gregoire (654547479=
) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","128","26=
-06-2025 17:41:13","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005349594","Ebo=
go","","26-06-2025 17:22:37","26-06-2025 17:15:30","26-06-2025 17:26:46","G=
rid fluctuation, site went down because Gen failed to start due to grid bad=
 voltag // Site stabilised","Siligap Boris","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid fluctuation, site went down=
 because Gen failed to start due to grid bad voltag // Site stabilised","ge=
rard.tchangoue@matech-cameroun.com","428","26-06-2025 17:22:37","MATECH CMR=
"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005349547","Aka=
k-Nkozoa-MTN-IHS","","26-06-2025 17:19:14","26-06-2025 17:12:08","26-06-202=
5 17:34:58","Site went down because our FME Fabrice was on site For PM // E=
n of Work","Fabrice Pouakam","Installation Activity","Passive","Planned Act=
ivity","Installation Activity","Site went down because our FME Fabrice was =
on site For PM // En of Work","gerard.tchangoue@matech-cameroun.com","604",=
"26-06-2025 17:19:14","MATECH CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0005349526","SOA=
 VILLAGE","","26-06-2025 17:16:34","26-06-2025 17:14:25","26-06-2025 20:55:=
49","No power issue on site ,site on Grid with Ubaie=3D54.2 V The Tx FME Sy=
nphorien//691316854 from Huawei is informed","Siligap Boris","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site ,site on Grid with Ubaie=3D54.2 V The Tx FME Synphorie=
n//691316854 from Huawei is informed","gerard.tchangoue@matech-cameroun.com=
","130","26-06-2025 17:16:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005349417","Nsam esc=
ale LP","","26-06-2025 17:04:21","26-06-2025 16:53:22","26-06-2025 18:23:03=
","Cascaded Incident from TTO5517342","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Site went down due to disjunction of Rectifie=
rs CB (50A) in the PWC // He rearmed it, site on Grid","system","285057","2=
6-06-2025 17:04:21","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005349375","Nsa=
m Sofavinc","IHS_YND_732","26-06-2025 16:59:32","26-06-2025 16:53:22","26-0=
6-2025 18:23:03","Site went down due to disjunction of Rectifiers CB (50A) =
in the PWC // He rearmed it, site on Grid","MINKA NICOLAS","Equipment Repai=
r","Passive","Rectifier","Rectifier - Circuit Breaker","Site went down due =
to disjunction of Rectifiers CB (50A) in the PWC // He rearmed it, site on =
Grid","gerard.tchangoue@matech-cameroun.com","370","26-06-2025 16:59:32","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0005349308","S=
ofavinc","","26-06-2025 16:50:28","26-06-2025 16:49:18","26-06-2025 17:34:5=
0","Grid outage, Gen start but did not feeding the site because his contact=
or is faulty // Contactor bay-pass and site on Gen","MINKA NICOLAS","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, Gen =
start but did not feeding the site because his contactor is faulty // Conta=
ctor bay-pass and site on Gen","christelle.ngonga@matech-cameroun.com","70"=
,"26-06-2025 16:50:28","MATECH CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0005349279","M=
ontee-Jouvence","","26-06-2025 16:45:35","26-06-2025 16:42:25","26-06-2025 =
16:58:32","No power issue u=3D53.4V site on GRID,The Tx FME Hosiah//6996996=
94 is informed","Hyemafo Gildas","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue u=3D53.4V site =
on GRID,The Tx FME Hosiah//699699694 is informed","christelle.ngonga@matech=
-cameroun.com","191","26-06-2025 16:45:35","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005349274","M=
ontee-Des-Soeurs","","26-06-2025 16:44:14","26-06-2025 16:42:01","26-06-202=
5 18:10:27"," Grid outage ,site down due to Gen overload (15 KVA/210 A) // =
Grid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload"," Grid outage ,site down due to Gen overload (15 KVA/210 A) //=
 Grid return","christelle.ngonga@matech-cameroun.com","134","26-06-2025 16:=
44:14","MATECH CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0005349269","C=
lge-Advantiste","","26-06-2025 16:43:11","26-06-2025 15:59:59","26-06-2025 =
17:43:28","No power issue site on grid with U=3D53.7V Lionnel Steeve(655184=
876) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on grid with U=3D53.7V Lionnel Steeve(655184876) from Huawei is informed=
","christelle.ngonga@matech-cameroun.com","3250","26-06-2025 16:43:11","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0005349265","E=
BOM","","26-06-2025 16:42:22","26-06-2025 15:59:42","26-06-2025 16:02:10","=
26-06-2025 16:02:10","Hyemafo Gildas","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54.4V. site on Grid Lionel//694693436 of huawei is informe","christelle.=
ngonga@matech-cameroun.com","2561","26-06-2025 16:42:22","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005349257","Mey=
o","","26-06-2025 16:41:20","26-06-2025 16:35:13","26-06-2025 16:43:05","Gr=
id Outage, Site went Down due to Gen overload (17KVA, 260A) SS HIS Felix Za=
mbe is informed // Grid returned","Hyemafo Gildas","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid Outage, Site went Down due to Gen o=
verload (17KVA, 260A) SS HIS Felix Zambe is informed // Grid returned","ger=
ard.tchangoue@matech-cameroun.com","368","26-06-2025 16:41:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005349138","Eto koss=
 Yde","","26-06-2025 16:26:35","26-06-2025 16:20:15","26-06-2025 16:27:15",=
"Cascaded Incident from TTO5517051","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down due to p=
oor batteries backup before Gen start // Grid return","system","265579","26=
-06-2025 16:26:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005349139","ELOUMDEM=
 CARRIERE 2","","26-06-2025 16:26:35","26-06-2025 16:20:15","26-06-2025 16:=
27:15","Cascaded Incident from TTO5517051","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down d=
ue to poor batteries backup before Gen start // Grid return","system","2655=
80","26-06-2025 16:26:35","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005349122","N=
omayos montee Meche","","26-06-2025 16:24:54","26-06-2025 15:59:59","26-06-=
2025 16:41:28","Grid outage.gen failed to start  due to PSC3 Controller dys=
functionning//Grid return","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage.gen failed to start  due to PSC3 =
Controller dysfunctionning//Grid return","christelle.ngonga@matech-cameroun=
.com","1639","26-06-2025 16:24:54","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005349112","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","26-06-2025 16:23:21","26-06-2025 16:20=
:15","26-06-2025 16:27:15","Grid outage, Site went down due to poor batteri=
es backup before Gen start // Grid return","Fanda Brice","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site=
 went down due to poor batteries backup before Gen start // Grid return","g=
erard.tchangoue@matech-cameroun.com","188","26-06-2025 16:23:21","MATECH CM=
R"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005349074","NKO=
MKANA ELIZA HOTEL","","26-06-2025 16:17:18","26-06-2025 16:10:10","26-06-20=
25 16:12:49","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","429","26-06-2025 16:17:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005349059","ELOUMDEM=
 CARRIERE 2","","26-06-2025 16:13:45","26-06-2025 16:04:20","26-06-2025 16:=
10:47","Cascaded Incident from TTO5516968","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down d=
ue to poor batteries backup before Gen start // Grid return","system","2665=
25","26-06-2025 16:13:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005349058","Eto koss=
 Yde","","26-06-2025 16:13:44","26-06-2025 16:04:20","26-06-2025 16:10:47",=
"Cascaded Incident from TTO5516968","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down due to p=
oor batteries backup before Gen start // Grid return","system","266524","26=
-06-2025 16:13:44","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005349047","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","26-06-2025 16:12:28","26-06-2025 16:04=
:20","26-06-2025 16:10:47","Grid outage, Site went down due to poor batteri=
es backup before Gen start // Grid return","Fanda Brice","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site=
 went down due to poor batteries backup before Gen start // Grid return","g=
erard.tchangoue@matech-cameroun.com","490","26-06-2025 16:12:28","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005349043","Mambine"=
,"","26-06-2025 16:12:13","26-06-2025 15:59:59","26-06-2025 16:41:28","Casc=
aded Incident from TTO5516913","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage.gen failed to start  due to P=
SC3 Controller dysfunctionning//Grid return","system","331502","26-06-2025 =
16:12:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005349045","Nkongtoc=
k","","26-06-2025 16:12:13","26-06-2025 15:59:59","26-06-2025 16:41:28","Ca=
scaded Incident from TTO5516913","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen failed to start  du=
e to PSC3 Controller dysfunctionning//Grid return","system","331505","26-06=
-2025 16:12:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005349044","Angongo"=
,"","26-06-2025 16:12:13","26-06-2025 15:59:59","26-06-2025 16:41:28","Casc=
aded Incident from TTO5516913","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage.gen failed to start  due to P=
SC3 Controller dysfunctionning//Grid return","system","331504","26-06-2025 =
16:12:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005349041","Ebeba","=
","26-06-2025 16:12:12","26-06-2025 15:59:59","26-06-2025 16:41:28","Cascad=
ed Incident from TTO5516913","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen failed to start  due to PSC=
3 Controller dysfunctionning//Grid return","system","331503","26-06-2025 16=
:12:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0005349042","OKOA Pea=
ge","","26-06-2025 16:12:12","26-06-2025 15:59:59","26-06-2025 16:41:28","C=
ascaded Incident from TTO5516913","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage.gen failed to start  due t=
o PSC3 Controller dysfunctionning//Grid return","system","331500","26-06-20=
25 16:12:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0005349040","Nkenglik=
ok","","26-06-2025 16:12:12","26-06-2025 15:59:59","26-06-2025 16:41:28","C=
ascaded Incident from TTO5516913","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start  d=
ue to PSC3 Controller dysfunctionning//Grid return","system","331501","26-0=
6-2025 16:12:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0005349039","Mbankomo=
 IHS","","26-06-2025 16:12:12","26-06-2025 15:59:59","26-06-2025 16:41:28",=
"Cascaded Incident from TTO5516913","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen failed to start  due=
 to PSC3 Controller dysfunctionning//Grid return","system","331497","26-06-=
2025 16:12:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0005349037","Sous Pre=
fecture","","26-06-2025 16:12:11","26-06-2025 15:59:59","26-06-2025 16:41:2=
8","Cascaded Incident from TTO5516913","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage.gen failed to start  =
due to PSC3 Controller dysfunctionning//Grid return","system","331498","26-=
06-2025 16:12:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0005349038","Mandoumb=
a OCM","","26-06-2025 16:12:11","26-06-2025 15:59:59","26-06-2025 16:41:28"=
,"Cascaded Incident from TTO5516913","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage.gen failed to start=
  due to PSC3 Controller dysfunctionning//Grid return","system","331499","2=
6-06-2025 16:12:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005348999","Nsam esc=
ale LP","","26-06-2025 16:08:05","26-06-2025 15:59:40","26-06-2025 16:05:52=
","Cascaded Incident from TTO5516880","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Gen Started Automatically","system","1216216","26-06-=
2025 16:08:05","MATECH CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0005348997","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_791, I=
HS_YND_339, IHS_YND_330, IHS_YND_350, IHS_YND_335, IHS_YND_349","26-06-2025=
 16:07:18","26-06-2025 15:59:59","26-06-2025 16:41:28","Grid outage.gen fai=
led to start  due to PSC3 Controller dysfunctionning//Grid return","Fanda B=
rice","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid ou=
tage.gen failed to start  due to PSC3 Controller dysfunctionning//Grid retu=
rn","christelle.ngonga@matech-cameroun.com","440","26-06-2025 16:07:18","MA=
TECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005348971","Nsa=
m Sofavinc","IHS_YND_732","26-06-2025 16:04:59","26-06-2025 15:59:40","26-0=
6-2025 16:05:52","Grid Outage, Site went down before Gen start due to poor =
backup // Gen Started Automatically","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site wen=
t down before Gen start due to poor backup // Gen Started Automatically","g=
erard.tchangoue@matech-cameroun.com","320","26-06-2025 16:04:59","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005348964","C-Suprem=
e","","26-06-2025 16:02:50","26-06-2025 15:56:21","26-06-2025 16:02:45","Ca=
scaded Incident from TTO5516844","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive"," Grid outage, Site went down before Gen start due =
to poor backup // Gen started automatically","system","324519","26-06-2025 =
16:02:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005348963","Acropole=
","","26-06-2025 16:02:50","26-06-2025 15:56:21","26-06-2025 16:02:45","Cas=
caded Incident from TTO5516844","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive"," Grid outage, Site went down before Ge=
n start due to poor backup // Gen started automatically","system","324520",=
"26-06-2025 16:02:50","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005348943","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","26-06-2025 15:58:38","26-06-2025 1=
5:56:21","26-06-2025 16:02:45"," Grid outage, Site went down before Gen sta=
rt due to poor backup // Gen started automatically","MINKA NICOLAS","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low"," Grid =
outage, Site went down before Gen start due to poor backup // Gen started a=
utomatically","christelle.ngonga@matech-cameroun.com","138","26-06-2025 15:=
58:38","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005348926","A=
bome","","26-06-2025 15:55:10","26-06-2025 15:49:38","26-06-2025 16:22:51",=
" No power issue on site Ubay 53.7V site on Grid and The TX FME Leonel Stev=
e (655184876) from huawei is informed","MINKA NICOLAS","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No powe=
r issue on site Ubay 53.7V site on Grid and The TX FME Leonel Steve (655184=
876) from huawei is informed","christelle.ngonga@matech-cameroun.com","333"=
,"26-06-2025 15:55:10","MATECH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005348861","N=
omayos-IHS","","26-06-2025 15:46:48","26-06-2025 15:42:41","26-06-2025 16:0=
3:41","Site went down because 01/04 rectifiers dysfunction//He reset rectif=
ier,site on Grid.","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down because 01/04 rectifiers dysfunction//He =
reset rectifier,site on Grid.","christelle.ngonga@matech-cameroun.com","248=
","26-06-2025 15:46:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005348706","MEHANDAN=
","","26-06-2025 15:35:11","26-06-2025 15:32:32","26-06-2025 16:13:35","Cas=
caded Incident from TTO5516580","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","289897","26-06-2025 15:35:11","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005348700","O=
dza II OCM","IHS_YND_528","26-06-2025 15:34:40","26-06-2025 15:32:32","26-0=
6-2025 16:13:35","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","christelle.ngonga@matech-cameroun.com","130","26-0=
6-2025 15:34:40","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005348693","OBA=
M NGOLA OCM","","26-06-2025 15:33:31","26-06-2025 15:29:26","26-06-2025 15:=
35:14","Site went down due to PWC overload //Site stabilised","MINKA NICOLA=
S","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Site went down due to PWC overload //Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","246","26-06-2025 15:33:31","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0005348662","M=
fou EPC","","26-06-2025 15:27:08","26-06-2025 15:18:02","26-06-2025 16:43:0=
2","Grid outage, Site went down because Gen started and stopped with ""low =
oil pressure"" alarm// He reset card GE and gen manually started","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, Site went down because Gen started and stopped with ""low oil p=
ressure"" alarm// He reset card GE and gen manually started","christelle.ng=
onga@matech-cameroun.com","548","26-06-2025 15:27:08","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005348607","Evo=
doula MTN","","26-06-2025 15:19:54","26-06-2025 15:14:48","26-06-2025 16:44=
:21","Grid outage, siyte went down due to Grid bad voltage // He bypassed G=
rid and started Gen manually","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid outage, siyte =
went down due to Grid bad voltage // He bypassed Grid and started Gen manua=
lly","gerard.tchangoue@matech-cameroun.com","307","26-06-2025 15:19:54","MA=
TECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005348586","Odz=
a Minkan IHS","","26-06-2025 15:14:46","26-06-2025 15:13:38","26-06-2025 15=
:16:38","Grid fluctuations, Site went down because Gen failed to start due =
to Grid bad voltage// Grid stabilised","Albran Byorel","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid fluctuations, Si=
te went down because Gen failed to start due to Grid bad voltage// Grid sta=
bilised","gerard.tchangoue@matech-cameroun.com","69","26-06-2025 15:14:46",=
"MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0005348543","Nlo=
ngkak","","26-06-2025 15:07:43","26-06-2025 15:03:36","26-06-2025 15:09:36"=
,"Grid outage, Site down due to poor battery backup // Grid return","Delor =
Telezing","Equipment Repair","Passive","Control Panel","Power Cabinet - Bat=
tery Low","Grid outage, Site down due to poor battery backup // Grid return=
","gerard.tchangoue@matech-cameroun.com","248","26-06-2025 15:07:43","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0005348508","Mamch Bu=
ilding","","26-06-2025 15:03:18","26-06-2025 15:01:23","26-06-2025 15:20:50=
","Cascaded Incident from TTO5516358","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid Only, No space to Deploy MG=
E // grid restoration","system","291761","26-06-2025 15:03:18","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005348504","C=
harles-Atangana","IHS_YND_051","26-06-2025 15:02:29","26-06-2025 15:01:23",=
"26-06-2025 15:28:12","Grid Only, No space to Deploy MGE // grid restoratio=
n","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid Only, No space to Deploy MGE // grid restoration","christelle.ngonga@ma=
tech-cameroun.com","68","26-06-2025 15:02:29","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005348469","Sim=
e Building","","26-06-2025 14:57:31","26-06-2025 14:52:22","26-06-2025 15:2=
2:27","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","gerard.tchan=
goue@matech-cameroun.com","311","26-06-2025 14:57:31","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005348462","O=
LAMA","","26-06-2025 14:56:25","26-06-2025 14:50:14","26-06-2025 14:58:38",=
"No power issue on site Ubaie =3D54.5V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.5V site on Gen The TX FME Henri (699949693) from Huawei is=
 informed.","christelle.ngonga@matech-cameroun.com","373","26-06-2025 14:56=
:25","MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0005348456","M=
beng","","26-06-2025 14:55:02","26-06-2025 14:53:57","26-06-2025 14:59:49",=
"No power issue, site is on gen with Ubaie =3D 54.8V, The Tx FME Etienne 69=
5033981 of huawei is informed.","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, s=
ite is on gen with Ubaie =3D 54.8V, The Tx FME Etienne 695033981 of huawei =
is informed.","christelle.ngonga@matech-cameroun.com","67","26-06-2025 14:5=
5:02","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005348439","E=
foulan","","26-06-2025 14:52:31","26-06-2025 14:48:25","26-06-2025 14:53:25=
","Site impacted by CTR_773_Z_Efoulan-Pont(CTR-773) Not manage by IHS","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","Affected by 3rd Party Site","Site impacted by CTR_773_Z_Efoulan-Pont(CTR=
-773) Not manage by IHS","christelle.ngonga@matech-cameroun.com","247","26-=
06-2025 14:52:31","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005348432","Awa=
e Ewonkan","","26-06-2025 14:51:56","26-06-2025 12:43:42","26-06-2025 13:05=
:12","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IH=
S SS Alphonse is informed//Site stabilised","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Site stabi=
lised","gerard.tchangoue@matech-cameroun.com","7696","26-06-2025 14:51:56",=
"MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005348095","ESS=
OS OASIS 1111","","26-06-2025 14:03:49","26-06-2025 13:55:34","26-06-2025 1=
6:57:50","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned	","Siligap Boris","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, Site went down because Gen overload (17kva, 2=
50A) // Grid returned	","loic.noumsi@matech-cameroun.com","496","26-06-2025=
 14:03:49","MATECH CMR"
"Closed Complete","Site Down","T2564","IHS_YND_739","NOCINC0005348032","NKO=
LMESSING rue Manguier","","26-06-2025 13:52:58","26-06-2025 13:44:49","26-0=
6-2025 14:06:07","Site went down due to cable which powered OCM equipements=
 is burnt //We normalize the cable and site on grid ","Siligap Boris","Equi=
pment Repair","Passive","Infrastructure","Armoured Cable","Site went down d=
ue to cable which powered OCM equipements is burnt //We normalize the cable=
 and site on grid ","loic.noumsi@matech-cameroun.com","490","26-06-2025 13:=
52:58","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005347923","OBA=
M NGOLA OCM","","26-06-2025 13:37:30","26-06-2025 13:29:23","26-06-2025 13:=
37:00","Grid outage, Site went down due to PM (working on PWC) done by BROA=
D (690864572) // End of work","MINKA NICOLAS","Installation Activity","Pass=
ive","Planned Activity","Installation Activity","Grid outage, Site went dow=
n due to PM (working on PWC) done by BROAD (690864572) // End of work","loi=
c.noumsi@matech-cameroun.com","488","26-06-2025 13:37:30","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005347819","E=
koumdoum OCM","","26-06-2025 13:23:35","26-06-2025 13:18:29","26-06-2025 15=
:21:41","Site went down because Gen failed to start due to Grid fluctuation=
 // He started the Gen manually","Albran Byorel","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Site went down because Gen =
failed to start due to Grid fluctuation // He started the Gen manually","ga=
elle.njiofack@matech-cameroun.com","307","26-06-2025 13:23:35","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005347748","E=
foulan","","26-06-2025 13:12:32","26-06-2025 13:09:21","26-06-2025 13:13:54=
","	Site impacted by CTR_773_Z_Efoulan-Pont(CTR-773) Not manage by IHS","MI=
NKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failur=
e","Affected by 3rd Party Site","	Site impacted by CTR_773_Z_Efoulan-Pont(C=
TR-773) Not manage by IHS","gaelle.njiofack@matech-cameroun.com","192","26-=
06-2025 13:12:32","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0005347745","B=
itoto","","26-06-2025 13:11:53","26-06-2025 13:04:45","26-06-2025 14:31:07"=
,"No power issue on site , Tx Issue : site on Grid ,Ubai: 49V; The fme Tx H=
enri (699949693) From huawei is informed","Mba Lazare Herve","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site , Tx Issue : site on Grid ,Ubai: 49V; The fme Tx Henri=
 (699949693) From huawei is informed","gaelle.njiofack@matech-cameroun.com"=
,"429","26-06-2025 13:11:53","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005347696","M=
EHANDAN","","26-06-2025 13:04:19","26-06-2025 12:58:59","26-06-2025 13:29:3=
5","Grid outage, site went down because gen failed to start due to ATS malf=
unction // He resert the ATS, grid return","Albran Byorel","Equipment Repai=
r","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down b=
ecause gen failed to start due to ATS malfunction // He resert the ATS, gri=
d return","gaelle.njiofack@matech-cameroun.com","323","26-06-2025 13:04:19"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005347506","S=
IMBOCK BONAMBAPE","","26-06-2025 12:47:27","26-06-2025 12:43:20","26-06-202=
5 12:48:22","Grid Outage, Site went down before Gen start due to poor backu=
p // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before Ge=
n start due to poor backup // Grid returned","loic.noumsi@matech-cameroun.c=
om","249","26-06-2025 12:47:27","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005347371","Sim=
e Building","","26-06-2025 12:32:43","26-06-2025 12:25:37","26-06-2025 12:3=
9:58","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","loic.noumsi@=
matech-cameroun.com","427","26-06-2025 12:32:43","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005347283","Jou=
vence Mbenda","","26-06-2025 12:21:15","26-06-2025 12:17:03","26-06-2025 12=
:57:04","Grid fluctuations, site went down due to Grid bad voltage and Rcp =
faulty // He bypassed Grid and started Gen manually","Hyemafo Gildas","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid f=
luctuations, site went down due to Grid bad voltage and Rcp faulty // He by=
passed Grid and started Gen manually","loic.noumsi@matech-cameroun.com","25=
3","26-06-2025 12:21:15","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005347194","O=
dza II OCM","","26-06-2025 12:07:07","26-06-2025 12:00:59","26-06-2025 12:0=
9:27","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","gaelle.njiofack@matech-cameroun.com","371","26-06-2025 12:07:=
07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005347151","Eseka To=
wn","","26-06-2025 11:57:11","26-06-2025 11:49:57","26-06-2025 12:05:54","C=
ascaded Incident from TTO5514844","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Our FME Francklin is =
on site for work (Replacement cylimblock of radiator) // End of work","syst=
em","274505","26-06-2025 11:57:11","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005347135","E=
seka OCM","IHS_YND_378","26-06-2025 11:56:18","26-06-2025 11:49:57","26-06-=
2025 12:05:54","Grid outage, Our FME Francklin is on site for work (Replace=
ment cylimblock of radiator) // End of work","Kemeni Franklin","Equipment R=
eplacement","Passive","Planned Activity","Planned Activity - Passive","Grid=
 outage, Our FME Francklin is on site for work (Replacement cylimblock of r=
adiator) // End of work","gaelle.njiofack@matech-cameroun.com","382","26-06=
-2025 11:56:18","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005347094","C=
arrefourt Nkomo","","26-06-2025 11:48:41","26-06-2025 11:40:35","26-06-2025=
 14:13:42","Grid outage,Site went down because Gen failed to start due to G=
rid contactor malfunctioning // He bypassed it site on Grid","Mba Lazare He=
rve","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid out=
age,Site went down because Gen failed to start due to Grid contactor malfun=
ctioning // He bypassed it site on Grid","gaelle.njiofack@matech-cameroun.c=
om","487","26-06-2025 11:48:41","MATECH CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0005346943","N=
kol-Mbanda","","26-06-2025 11:33:35","26-06-2025 00:58:14","26-06-2025 01:0=
2:05","Backtraking Active// No power Issue Site on Grid Ubai =3D49V, The FM=
E The TX FME Mbah Hosiah (674007438) is informed.","MINKA NICOLAS","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Backtraking Active// No power Issue Site on Grid Ubai =3D49V, The FME T=
he TX FME Mbah Hosiah (674007438) is informed.","gaelle.njiofack@matech-cam=
eroun.com","38123","26-06-2025 11:33:35","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005346900","M=
ontee-Des-Soeurs","","26-06-2025 11:26:35","26-06-2025 01:03:48","26-06-202=
5 01:17:34","(Backtraking) Grid outage ,site down due to Gen overload (15 K=
VA/210 A) // Grid return","Hyemafo Gildas","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","(Backtraking) Grid outage ,site down due to Gen =
overload (15 KVA/210 A) // Grid return","gaelle.njiofack@matech-cameroun.co=
m","37369","26-06-2025 11:26:35","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005346886","M=
vog Mbi New","","26-06-2025 11:23:39","26-06-2025 09:25:28","26-06-2025 10:=
03:37","Backtraking Grid outage, Site went down before Gen start due to poo=
r backup // Gen start automatically","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site wen=
t down before Gen start due to poor backup // Gen start automatically","gae=
lle.njiofack@matech-cameroun.com","7091","26-06-2025 11:23:39","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005346848","A=
wae Ewonkan","","26-06-2025 11:20:01","25-06-2025 12:33:52","25-06-2025 12:=
50:37","	Bactracking Grid outage site went down due to Gen Overload (20Kva,=
 Iload 225 A)IHS SS Alphonse is informed//Site stabilised","Albran Byorel",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","	Bactracking Gri=
d outage site went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alph=
onse is informed//Site stabilised","gaelle.njiofack@matech-cameroun.com","8=
1969","26-06-2025 11:20:01","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005346843","A=
WAE OCM","","26-06-2025 11:18:04","26-06-2025 11:11:55","26-06-2025 12:57:5=
3","Grid outage site went down because Gen failed to start due PWC ZTE dysf=
unctioning // He reset the PWC and site on Grid","Mba Lazare Herve","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outag=
e site went down because Gen failed to start due PWC ZTE dysfunctioning // =
He reset the PWC and site on Grid","loic.noumsi@matech-cameroun.com","371",=
"26-06-2025 11:18:04","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005346832","Nko=
abang2","","26-06-2025 11:16:53","26-06-2025 11:10:48","26-06-2025 12:30:46=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // He reduced load and site on GEN","Mba Lazare Herve","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site w=
ent down due to gen overload (22KVA, 330A), SS Blaise IHS is informed // He=
 reduced load and site on GEN","loic.noumsi@matech-cameroun.com","367","26-=
06-2025 11:16:53","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005346811","A=
wae Ewonkan","","26-06-2025 11:15:30","26-06-2025 11:12:19","26-06-2025 12:=
43:28","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed//Site stabilisedd ","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down =
due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Site s=
tabilised","loic.noumsi@matech-cameroun.com","193","26-06-2025 11:15:30","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005346803","Elig-Edz=
oa","","26-06-2025 11:14:23","26-06-2025 10:50:30","26-06-2025 12:59:27","C=
ascaded Incident from TTO5514321","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen failed to=
 start due to Pwc ZTE dysfunction // He reset and manual start of Gen","sys=
tem","278050","26-06-2025 11:14:23","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005346717","Odz=
a Minkan IHS","","26-06-2025 11:04:13","26-06-2025 11:01:06","26-06-2025 11=
:45:40","Grid fluctuations, Site went down because Gen failed to start due =
to Grid bad voltage// He bypassed Grid and started Gen manually","Albran By=
orel","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuations, Site went down because Gen failed to start due to G=
rid bad voltage// He bypassed Grid and started Gen manually","loic.noumsi@m=
atech-cameroun.com","188","26-06-2025 11:04:13","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005346673","Sof=
avinc","","26-06-2025 10:55:40","26-06-2025 10:50:14","26-06-2025 11:02:57"=
,"	Grid outage, Gen start but did not feeding the site because his contacto=
r is faulty // Contactor bay-pass and site on Gen","MINKA NICOLAS","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Load Contactor","	Grid outage, Gen =
start but did not feeding the site because his contactor is faulty // Conta=
ctor bay-pass and site on Gen","loic.noumsi@matech-cameroun.com","327","26-=
06-2025 10:55:40","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005346667","N=
taba","IHS_YND_133","26-06-2025 10:54:54","26-06-2025 10:50:01","26-06-2025=
 13:03:54","Grid outage, site went down because gen failed to start due to =
Pwc ZTE dysfunction // He reset and manual start of Gen","Delor Telezing","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage, site went down because gen failed to start due to Pwc ZTE dysfunct=
ion // He reset and manual start of Gen","gaelle.njiofack@matech-cameroun.c=
om","655","26-06-2025 10:54:54","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005346445","A=
bome","","26-06-2025 10:15:55","26-06-2025 10:14:43","26-06-2025 10:19:35",=
"Active/ No power issue on site Ubay 53.7V site on Grid and The TX FME Leon=
el Steve (655184876) from huawei is informed","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive/ No power issue on site Ubay 53.7V site on Grid and The TX FME Leonel=
 Steve (655184876) from huawei is informed","gaelle.njiofack@matech-camerou=
n.com","73","26-06-2025 10:15:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005346436","Elig-Edz=
oa","","26-06-2025 10:14:44","26-06-2025 10:10:28","26-06-2025 10:26:18","C=
ascaded Incident from TTO5514057","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen failed to=
 start due to Pwc ZTE dysfunction // He reset and manual start of Gen","sys=
tem","256","26-06-2025 10:14:44","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005346428","Nta=
ba","IHS_YND_133","26-06-2025 10:13:33","26-06-2025 10:10:28","26-06-2025 1=
0:30:52","Grid outage, site went down because gen failed to start due to Pw=
c ZTE dysfunction // He reset and manual start of Gen","Delor Telezing","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid o=
utage, site went down because gen failed to start due to Pwc ZTE dysfunctio=
n // He reset and manual start of Gen","loic.noumsi@matech-cameroun.com","1=
87","26-06-2025 10:13:33","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005346404","M=
vog Mbi New","","26-06-2025 10:09:43","26-06-2025 10:03:38","26-06-2025 10:=
08:45","Grid outage, Site went down before Gen start due to poor backup // =
Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen start automatically","loic.noumsi@mat=
ech-cameroun.com","366","26-06-2025 10:09:43","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005346358","C=
-Supreme","","26-06-2025 10:00:21","26-06-2025 09:56:05","26-06-2025 11:23:=
44","	Active // No power issue, site on Battery with Ubaie=3D55V, Brice Tsa=
gue (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","	Active // No power=
 issue, site on Battery with Ubaie=3D55V, Brice Tsague (650 21 40 96 / Huaw=
ei) is informed","gaelle.njiofack@matech-cameroun.com","258","26-06-2025 10=
:00:21","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0005346325","N=
komkana","","26-06-2025 09:55:31","26-06-2025 09:50:28","26-06-2025 09:54:0=
2","Grid Only, No space to deploy MDGE// Grid returned","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to =
deploy MDGE// Grid returned","loic.noumsi@matech-cameroun.com","305","26-06=
-2025 09:55:31","MATECH CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0005346201","S=
cience","","26-06-2025 09:37:25","26-06-2025 09:33:56","26-06-2025 09:53:56=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage and no rcp on site // Grid stabilized","TIENTCHEU NZETCHIEU =
GAEL","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, site went down because gen start and stopped due to =
grid bad voltage and no rcp on site // Grid stabilized","gaelle.njiofack@ma=
tech-cameroun.com","210","26-06-2025 09:37:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005346188","MEHANDAN=
","","26-06-2025 09:35:11","26-06-2025 09:31:40","26-06-2025 09:41:17","Cas=
caded Incident from TTO5513771","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","282768","26-06-2025 09:35:11","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005346181","O=
dza II OCM","IHS_YND_528","26-06-2025 09:33:48","26-06-2025 09:31:40","26-0=
6-2025 09:41:17","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","gaelle.njiofack@matech-cameroun.com","131","26-06-=
2025 09:33:48","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0005346105","H=
-Progres","","26-06-2025 09:23:43","26-06-2025 09:18:37","26-06-2025 14:30:=
49","Grid Only, No space to deploy MGE //Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to de=
ploy MGE //Grid return","gaelle.njiofack@matech-cameroun.com","308","26-06-=
2025 09:23:43","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005345904","ESS=
OS OASIS 1111","","26-06-2025 08:53:20","26-06-2025 08:51:12","26-06-2025 1=
3:04:34","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) // Grid returned","gerard.tchangoue@matech-cameroun.com","129","26-06-2=
025 08:53:20","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005345860","M=
elen Ba'aba","","26-06-2025 08:47:43","26-06-2025 08:43:32","26-06-2025 10:=
15:26","Grid outage, site went down because gen ran until fuel shortage//Re=
fuelling done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, site went down because gen ran until fuel shortage//Refu=
elling done","gaelle.njiofack@matech-cameroun.com","253","26-06-2025 08:47:=
43","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005345689","E=
SSOS OASIS 1111","","26-06-2025 08:17:33","26-06-2025 08:15:23","26-06-2025=
 08:30:34","Grid outage, Site went down because Gen overload (17kva, 250A) =
// Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) // Grid return","gaelle.njiofack@matech-cameroun.com","23033","26-06-20=
25 08:17:33","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005345654","M=
fou OCM","","26-06-2025 08:10:12","26-06-2025 08:03:41","26-06-2025 08:10:2=
6","	Grid Outage, Site Down before gen Started due to poor backup //Grid re=
turned","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","	Grid Outage, Site Down before gen Started due =
to poor backup //Grid returned","gaelle.njiofack@matech-cameroun.com","392"=
,"26-06-2025 08:10:12","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005345594","N=
GONA","","26-06-2025 07:57:46","26-06-2025 07:53:38","26-06-2025 11:00:35",=
"Active//No power issue Site is on Grid and Ubaie =3D55.8V The Tx FME Lione=
l Adjep (655184876)from Huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue Site is on Grid and Ubaie =3D55.8V The Tx FME Lionel=
 Adjep (655184876)from Huawei is informed","loic.noumsi@matech-cameroun.com=
","249","26-06-2025 07:57:46","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005345530","Sof=
avinc","","26-06-2025 07:46:29","26-06-2025 07:45:23","26-06-2025 08:16:30"=
,"	Grid outage, Gen start but did not feeding the site because his contacto=
r is faulty // Contactor bay-pass and site on Gen","MINKA NICOLAS","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Load Contactor","	Grid outage, Gen =
start but did not feeding the site because his contactor is faulty // Conta=
ctor bay-pass and site on Gen","loic.noumsi@matech-cameroun.com","67","26-0=
6-2025 07:46:29","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0005345392","C=
RF Nkoabang","","26-06-2025 07:25:58","26-06-2025 07:17:38","26-06-2025 07:=
34:33","Solar Only, site down due to sunset // Sun shine return","Mba Lazar=
e Herve","Equipment Repair","Passive","Solar","Solar Panel Issue","Solar On=
ly, site down due to sunset // Sun shine return","loic.noumsi@matech-camero=
un.com","501","26-06-2025 07:25:58","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005345349","M=
fou OCM","","26-06-2025 07:18:38","26-06-2025 06:58:19","26-06-2025 07:52:5=
2","	Grid Fluctuation, Site Down before gen Started due to poor backup // G=
rid baypass and site on GEN ","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","	Grid Fluctuation, Site D=
own before gen Started due to poor backup // Grid baypass and site on GEN "=
,"gaelle.njiofack@matech-cameroun.com","1219","26-06-2025 07:18:38","MATECH=
 CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005345216","Eto=
ug ebe biscuiterie","","26-06-2025 06:52:09","26-06-2025 06:44:03","26-06-2=
025 09:16:22","Grid outage, Site went down because Gen started and stopped =
due to belt cut off // He replaced Belt, site on Grid","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Fan Belt","Grid outage, Site w=
ent down because Gen started and stopped due to belt cut off // He replaced=
 Belt, site on Grid","loic.noumsi@matech-cameroun.com","486","26-06-2025 06=
:52:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005345191","Yoko MTN=
","","26-06-2025 06:46:21","26-06-2025 06:31:59","26-06-2025 06:40:19","Cas=
caded Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","NO power issue on site. Site impacted by =
Ntui that is not managed by IHS","system","265087","26-06-2025 06:46:21","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0005345190","Saa","",=
"26-06-2025 06:46:20","26-06-2025 06:31:59","26-06-2025 06:40:19","Cascaded=
 Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","NO power issue on site. Site impacted by Ntui =
that is not managed by IHS","system","265084","26-06-2025 06:46:20","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0005345189","NTUI TOW=
N","","26-06-2025 06:46:20","26-06-2025 06:31:59","26-06-2025 06:40:19","Ca=
scaded Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active",=
"Cascade Active","Cascade Active","NO power issue on site. Site impacted by=
 Ntui that is not managed by IHS","system","265075","26-06-2025 06:46:20","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0005345187","Donga","=
","26-06-2025 06:46:20","26-06-2025 06:31:59","26-06-2025 06:40:19","Cascad=
ed Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","NO power issue on site. Site impacted by Ntu=
i that is not managed by IHS","system","265076","26-06-2025 06:46:20","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0005345188","Dong",""=
,"26-06-2025 06:46:20","26-06-2025 06:31:59","26-06-2025 06:40:19","Cascade=
d Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","NO power issue on site. Site impacted by Ntui=
 that is not managed by IHS","system","265085","26-06-2025 06:46:20","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_690","NOCINC0005345184","Ntui adm=
inistration","","26-06-2025 06:46:19","26-06-2025 06:31:59","26-06-2025 06:=
40:19","Cascaded Incident from TTO5512635","Parker Tchoup","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","NO power issue on site. Site i=
mpacted by Ntui that is not managed by IHS","system","265073","26-06-2025 0=
6:46:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005345186","Nkol-Meb=
anga","","26-06-2025 06:46:19","26-06-2025 06:31:59","26-06-2025 06:40:19",=
"Cascaded Incident from TTO5512635","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","NO power issue on site. Site impacted=
 by Ntui that is not managed by IHS","system","265086","26-06-2025 06:46:19=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0005345185","SAA Entr=
ance","","26-06-2025 06:46:19","26-06-2025 06:31:59","26-06-2025 06:40:19",=
"Cascaded Incident from TTO5512635","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","NO power issue on site. Site impacted=
 by Ntui that is not managed by IHS","system","265078","26-06-2025 06:46:19=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005345183","Ngouetou=
","","26-06-2025 06:46:19","26-06-2025 06:31:59","26-06-2025 06:40:19","Cas=
caded Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","NO power issue on site. Site impacted by =
Ntui that is not managed by IHS","system","265083","26-06-2025 06:46:19","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005345180","SAA 2","=
","26-06-2025 06:46:18","26-06-2025 06:31:59","26-06-2025 06:40:19","Cascad=
ed Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","NO power issue on site. Site impacted by Ntu=
i that is not managed by IHS","system","265082","26-06-2025 06:46:18","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005345182","Ngoum","=
","26-06-2025 06:46:18","26-06-2025 06:31:59","26-06-2025 06:40:19","Cascad=
ed Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","NO power issue on site. Site impacted by Ntu=
i that is not managed by IHS","system","265081","26-06-2025 06:46:18","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005345179","Matsari"=
,"","26-06-2025 06:46:18","26-06-2025 06:31:59","26-06-2025 06:40:19","Casc=
aded Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","NO power issue on site. Site impacted by N=
tui that is not managed by IHS","system","265077","26-06-2025 06:46:18","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005345181","Carrefou=
r Ayissi Ele","","26-06-2025 06:46:18","26-06-2025 06:31:59","26-06-2025 06=
:40:19","Cascaded Incident from TTO5512635","Parker Tchoup","Cascade Outage=
","Active","Cascade Active","Cascade Active","NO power issue on site. Site =
impacted by Ntui that is not managed by IHS","system","265074","26-06-2025 =
06:46:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0005345177","Nguila",=
"","26-06-2025 06:46:17","26-06-2025 06:31:59","26-06-2025 06:40:19","Casca=
ded Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","NO power issue on site. Site impacted by Nt=
ui that is not managed by IHS","system","265080","26-06-2025 06:46:17","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005345178","MBIMBIM"=
,"","26-06-2025 06:46:17","26-06-2025 06:31:59","26-06-2025 06:40:19","Casc=
aded Incident from TTO5512635","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","NO power issue on site. Site impacted by N=
tui that is not managed by IHS","system","265079","26-06-2025 06:46:17","MA=
TECH CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0005345159","Oss=
ombe","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_404, IHS_YND_810, IHS=
_YND_475, IHS_YND_454, IHS_YND_690, IHS_YND_542, IHS_YND_809, IHS_YND_434, =
IHS_YND_444, IHS_YND_403, IHS_YND_405, IHS_YND_473","26-06-2025 06:41:12","=
26-06-2025 06:31:59","26-06-2025 06:40:19","NO power issue on site. Site im=
pacted by Ntui that is not managed by IHS","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","Affected by 3rd Party Sit=
e","NO power issue on site. Site impacted by Ntui that is not managed by IH=
S","gerard.tchangoue@matech-cameroun.com","579","26-06-2025 06:41:12","MATE=
CH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005344808","Sim=
e Building","","26-06-2025 05:32:08","26-06-2025 05:25:01","26-06-2025 05:3=
7:43","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started	","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup // Gen automatically started	","cedric.tia=
ni@matech-cameroun.com","427","26-06-2025 05:32:08","MATECH CMR"
"Cancelled","Warning","T0209","IHS_YND_197","NOCINC0005344799","Palais Des =
Congres","","26-06-2025 05:30:02","","","Wrongly created ticket","Mboua Thi=
erry","","","","","","cedric.tiani@matech-cameroun.com","248","26-06-2025 0=
5:30:02","MATECH CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0005344551","B=
otmakak","IHS_EDA_101","26-06-2025 04:46:49","26-06-2025 04:45:39","26-06-2=
025 05:00:59","No power issue, Site on Grid Ubai=3D 53.8 V, The Tx Etienne =
(695033981/Huawei) is informed","Kemeni Franklin","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","	No power iss=
ue, Site on Grid Ubai=3D 53.8 V, The Tx Etienne (695033981/Huawei) is infor=
med","vanel.mbiada@matech-cameroun.com","71","26-06-2025 04:46:49","MATECH =
CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005344510","O=
LAMA","","26-06-2025 04:34:40","26-06-2025 04:31:26","26-06-2025 04:45:02",=
"Active // No power issue on site Ubaie =3D54.5V site on Gen The TX FME Hen=
ri (699949693) from Huawei is informed.","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/ No power issue on site Ubaie =3D54.5V site on Gen The TX FME Henri (69994=
9693) from Huawei is informed.","vanel.mbiada@matech-cameroun.com","195","2=
6-06-2025 04:34:40","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005344501","O=
kola OCM","","26-06-2025 04:31:17","26-06-2025 04:23:54","26-06-2025 09:52:=
13","Grid outage gen start and stopped due to radiator pierced//We fixed in=
 seal radiator and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Radiator","Grid outage gen start a=
nd stopped due to radiator pierced//We fixed in seal radiator and gen manua=
lly started","vanel.mbiada@matech-cameroun.com","444","26-06-2025 04:31:17"=
,"MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005344448","Ebo=
go","","26-06-2025 04:15:09","26-06-2025 04:06:47","26-06-2025 04:20:53","N=
o power issue on site U=3D50,3v site on grid Synphorien 675295205 of Huawei=
 is informed","Siligap Boris","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D50,3v =
site on grid Synphorien 675295205 of Huawei is informed","cedric.tiani@mate=
ch-cameroun.com","503","26-06-2025 04:15:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005344307","Mfou EPC=
","","26-06-2025 03:10:44","26-06-2025 02:33:23","26-06-2025 03:10:03","Cas=
caded Incident from TTO5511555","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","267582","26-06-2025 03=
:10:44","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005344233","O=
dza II OCM","","26-06-2025 03:01:27","26-06-2025 02:58:08","26-06-2025 03:0=
2:27","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","vanel.mbiada@matech-cameroun.com","201","26-06-2025 03:01:27"=
,"MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005344211","Ngo=
usso Vallee","","26-06-2025 02:56:03","26-06-2025 02:54:43","26-06-2025 02:=
56:08","	Site went down because insufficient of rectifier on site //site st=
abilized","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","	Site went down because insufficient of rectifier on site //sit=
e stabilized","cedric.tiani@matech-cameroun.com","80","26-06-2025 02:56:03"=
,"MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0005344178","Dag=
obert","","26-06-2025 02:45:01","26-06-2025 02:37:52","26-06-2025 02:56:49"=
,"Active: No power issue, site is on Grid with Ubaie=3D54,6V, FME TX Mohama=
dou//691144435 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active: No power issue, site is on Grid with Ubaie=3D54,6V, FME TX Moha=
madou//691144435 from Huawei is informed","cedric.tiani@matech-cameroun.com=
","430","26-06-2025 02:45:01","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005344168","M=
fou OCM","IHS_YND_674","26-06-2025 02:40:31","26-06-2025 02:33:23","26-06-2=
025 03:10:03","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","vanel.mbiada@matech-cameroun.com"=
,"429","26-06-2025 02:40:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0005344160","Leboudi"=
,"","26-06-2025 02:36:50","26-06-2025 02:34:02","26-06-2025 02:48:44","Casc=
aded Incident from TTO5511542","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","Active//No power issue, Site on=
 Grid Ubaie=3D 54.8V The TX Mouhamadou (6144435) from Huawei is informed.",=
"system","267543","26-06-2025 02:36:50","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0005344157","N=
kolafeme","IHS_YND_309","26-06-2025 02:36:14","26-06-2025 02:34:02","26-06-=
2025 04:14:24","Active//No power issue, Site on Grid Ubaie=3D 54.8V The TX =
Mouhamadou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue, Site on Grid Ubaie=3D 54.8V The TX Mouha=
madou (6144435) from Huawei is informed.","vanel.mbiada@matech-cameroun.com=
","133","26-06-2025 02:36:14","MATECH CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0005344137","Mat=
sari","","26-06-2025 02:29:07","26-06-2025 02:25:53","26-06-2025 04:13:37",=
"No power issue on site with Ubaie=3D53.8V site on Gen ,The Tx Fme Gregoire=
( 652070658)from Huawei is informed","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site with Ubaie=3D53.8V site on Gen ,The Tx Fme Gregoire( 652070658=
)from Huawei is informed","cedric.tiani@matech-cameroun.com","195","26-06-2=
025 02:29:07","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005344116","Man=
guiers Dispensaire","","26-06-2025 02:23:50","26-06-2025 02:18:35","26-06-2=
025 04:14:40","Active // No power issue site on grid with U=3D54,8 V Tx Fme=
 Armand Ngestsa (691144412) of huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active // No power issue site on grid with U=3D54,8 V Tx Fme Armand N=
gestsa (691144412) of huawei is informed","ludivine.ngamaleu@ihstowers.com"=
,"316","26-06-2025 02:23:50","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005344050","ODZ=
A MINKAN EDIBI ASSI","","26-06-2025 02:13:27","26-06-2025 02:06:18","26-06-=
2025 07:10:23","Grid outage,site went down because Gen failed to start due =
toGen overload(12.5 kva //180A )SS HIS Francois is informed // Grid return"=
,"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage,site went down because Gen failed to start due toGen overload(=
12.5 kva //180A )SS HIS Francois is informed // Grid return","cedric.tiani@=
matech-cameroun.com","430","26-06-2025 02:13:27","MATECH CMR"
"Closed Complete","Site Down","T0104","IHS_YND_113","NOCINC0005343920","Emo=
mbo 2","","26-06-2025 01:23:11","26-06-2025 01:22:03","26-06-2025 01:32:52"=
,"Site went down because Mr.MVOGO(698529863)  from SFM is on site (swap of =
PWC)//End of work","MINKA NICOLAS","Installation Activity","Passive","Plann=
ed Activity","Installation Activity","Site went down because Mr.MVOGO(69852=
9863)  from SFM is on site (swap of PWC)//End of work","cedric.tiani@matech=
-cameroun.com","69","26-06-2025 01:23:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005343731","Mfou EPC=
","","26-06-2025 00:52:49","26-06-2025 00:49:48","26-06-2025 00:54:17","Cas=
caded Incident from TTO5511070","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //GEN automatically started","system","273748","2=
6-06-2025 00:52:49","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005343726","M=
fou OCM","IHS_YND_674","26-06-2025 00:51:06","26-06-2025 00:49:48","26-06-2=
025 00:54:17","Grid Outage, Site Down before gen Started due to poor backup=
 //GEN automatically started","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down be=
fore gen Started due to poor backup //GEN automatically started","vanel.mbi=
ada@matech-cameroun.com","79","26-06-2025 00:51:06","MATECH CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0005343593","E=
kounou","","26-06-2025 00:24:02","26-06-2025 00:22:42","26-06-2025 01:03:30=
","Site went down due to Biganstil (679161144//Dowen) is on site for swap P=
WC//End of work","Albran Byorel","Installation Activity","Passive","Planned=
 Activity","Installation Activity","Site went down due to Biganstil (679161=
144//Dowen) is on site for swap PWC//End of work","vanel.mbiada@matech-came=
roun.com","81","26-06-2025 00:24:02","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005343589","ESS=
OS OASIS 1111","","26-06-2025 00:22:54","26-06-2025 00:15:40","26-06-2025 0=
0:29:12","Grid outage, Site went down because Gen overload (17kva, 250A) //=
  Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage, Site went down because Gen overload (17kva, 250=
A) //  Grid return","cedric.tiani@matech-cameroun.com","435","26-06-2025 00=
:22:54","MATECH CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0005343579","Mim=
boman3","","26-06-2025 00:17:37","26-06-2025 00:15:26","26-06-2025 01:33:02=
","Grid outage, Site went down because PWC ZTE dysfunctionning// He reset P=
WC and Site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Grid outage, Site went down because PW=
C ZTE dysfunctionning// He reset PWC and Site on Grid","cedric.tiani@matech=
-cameroun.com","132","26-06-2025 00:17:37","MATECH CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0005343539","O=
dza II","","26-06-2025 00:06:50","26-06-2025 00:04:42","26-06-2025 01:38:39=
","Site went down due to ATS malfunction due to grid bad voltage// he resse=
t it and site on Gen ","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","ATS-AMF Issue","Site went down due to ATS malfunction due to grid=
 bad voltage// he resset it and site on Gen ","vanel.mbiada@matech-cameroun=
.com","130","26-06-2025 00:06:50","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005343537","N=
komo","","26-06-2025 00:06:10","26-06-2025 00:03:47","26-06-2025 00:09:11",=
"Grid fluctuations, site went down because gen failed to start due to PWC Z=
TE malfunction // Site stabilised","Mba Lazare Herve","Equipment Repair","P=
assive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, site =
went down because gen failed to start due to PWC ZTE malfunction // Site st=
abilised","vanel.mbiada@matech-cameroun.com","144","26-06-2025 00:06:10","M=
ATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005343465","ODZ=
A MINKAN EDIBI ASSI","","25-06-2025 23:51:34","25-06-2025 23:50:26","26-06-=
2025 00:08:32","Grid outage,site went down because Gen failed to start due =
toGen overload(12.5 kva //180A )SS HIS Francois is informed//He reduiced th=
e load and manually started the Gen","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage,site went down because Gen=
 failed to start due toGen overload(12.5 kva //180A )SS HIS Francois is inf=
ormed//He reduiced the load and manually started the Gen","cedric.tiani@mat=
ech-cameroun.com","69","25-06-2025 23:51:34","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005342925","OBA=
M NGOLA OCM","","25-06-2025 21:56:56","25-06-2025 21:50:50","25-06-2025 22:=
14:17"," Site went down due to PWC overload//Site stabilised","MINKA NICOLA=
S","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
 Site went down due to PWC overload//Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","368","25-06-2025 21:56:56","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005342888","E=
SSOS OASIS 1111","","25-06-2025 21:47:38","25-06-2025 21:44:29","25-06-2025=
 23:15:51","(Unstable site) Grid outage,Site went down because Gen overload=
 (17kva, 250A) //Site stabilised","Siligap Boris","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","(Unstable site) Grid outage,Site went dow=
n because Gen overload (17kva, 250A) //Site stabilised","edwige.kapawo@mate=
ch-cameroun.com","190","25-06-2025 21:47:38","MATECH CMR"
"Closed Complete","Site Down","T0292","IHS_YND_231","NOCINC0005342887","Nko=
lso","","25-06-2025 21:47:33","25-06-2025 21:46:27","25-06-2025 21:48:25","=
Grid fluctuation,site went down because Gen started and stopped due to Grid=
 bad voltage//Grid return","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,site =
went down because Gen started and stopped due to Grid bad voltage//Grid ret=
urn","gerard.tchangoue@matech-cameroun.com","66","25-06-2025 21:47:33","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005342886","S=
IMBOCK BONAMBAPE","","25-06-2025 21:47:03","25-06-2025 21:42:46","25-06-202=
5 21:46:56","Grid Outage, Site went down before Gen start due to poor backu=
p // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before Ge=
n start due to poor backup // Grid returned","edwige.kapawo@matech-cameroun=
.com","258","25-06-2025 21:47:03","MATECH CMR"
"Closed Complete","Site Down","T0535","IHS_YND_234","NOCINC0005342703","Oyo=
mabang MTN","","25-06-2025 21:16:55","25-06-2025 21:09:49","26-06-2025 08:4=
0:08","Grid outage, site went down due to insufficient (02/04) of rectifier=
s // He added rectifiers and site on Grid","TIENTCHEU NZETCHIEU GAEL","Equi=
pment Repair","Passive","Rectifier","Rectifier Module","Grid outage, site w=
ent down due to insufficient (02/04) of rectifiers // He added rectifiers a=
nd site on Grid","gerard.tchangoue@matech-cameroun.com","427","25-06-2025 2=
1:16:55","MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005342606","Mvo=
g Betsi Hospital","","25-06-2025 21:05:37","25-06-2025 21:05:33","25-06-202=
5 21:10:33","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.=
com","5","25-06-2025 21:05:37","MATECH CMR"
"Closed Complete","Site Down","T1622","IHS_YND_186","NOCINC0005342582","Ngo=
usso Carrefour","","25-06-2025 21:01:55","25-06-2025 20:58:42","25-06-2025 =
22:00:56","Eneo outage, site Down due to Gen Overloadd(20KVA, 280A) // Eneo=
 return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Eneo outage, site Down due to Gen Overloadd(20KVA, 280A) // Eneo r=
eturn","gerard.tchangoue@matech-cameroun.com","194","25-06-2025 21:01:55","=
MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005342483","A=
bome","","25-06-2025 20:50:20","25-06-2025 19:38:09","25-06-2025 21:15:05",=
"Grid outage, Site went down before Gen start due to poor backup// Gen Auto=
matically Started","MINKA NICOLAS","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen Automatically Started","edwige.kapawo@matech=
-cameroun.com","4333","25-06-2025 20:50:20","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005342479","Odz=
a Minkan IHS","","25-06-2025 20:49:51","25-06-2025 20:49:39","25-06-2025 22=
:58:07","Site on Gen due to Grid outage, site went down because Gen stopped=
 due to infiltration of water in the tank// He purge water and manally star=
ted the Gen","Albran Byorel","Fuel Outage (Probable)","Passive","Diesel","T=
ank Sealing Issue - Water In The Fuel","Site on Gen due to Grid outage, sit=
e went down because Gen stopped due to infiltration of water in the tank// =
He purge water and manally started the Gen","gerard.tchangoue@matech-camero=
un.com","13","25-06-2025 20:49:51","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005342467","E=
foulan","","25-06-2025 20:46:06","25-06-2025 20:43:59","25-06-2025 20:47:56=
","Site impacted by CTR_773_Z_Efoulan-Pont(CTR-773) Not manage by IHS","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Site impacted by CTR_773_Z_Efoulan-Pont(CTR-773) No=
t manage by IHS","edwige.kapawo@matech-cameroun.com","128","25-06-2025 20:4=
6:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_217","NOCINC0005342430","Abom",""=
,"25-06-2025 20:42:09","25-06-2025 20:33:00","25-06-2025 20:59:46","Cascade=
d Incident from TTO5509560","Siligap Boris","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, gen failed to start due to al=
arm ""low oil pressure""//We reset card GE and gen manually started","syste=
m","1214096","25-06-2025 20:42:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_214","NOCINC0005342429","Nkolmess=
eng-II","","25-06-2025 20:42:09","25-06-2025 20:33:00","25-06-2025 20:59:46=
","Cascaded Incident from TTO5509560","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, gen failed to start=
 due to alarm ""low oil pressure""//We reset card GE and gen manually start=
ed","system","1214096","25-06-2025 20:42:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_215","NOCINC0005342426","Eleveurs=
","","25-06-2025 20:42:08","25-06-2025 20:33:00","25-06-2025 20:59:46","Cas=
caded Incident from TTO5509560","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, gen failed to start due t=
o alarm ""low oil pressure""//We reset card GE and gen manually started","s=
ystem","1214095","25-06-2025 20:42:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_739","NOCINC0005342428","NKOLMESS=
ING rue Manguier","","25-06-2025 20:42:08","25-06-2025 20:33:00","25-06-202=
5 20:59:46","Cascaded Incident from TTO5509560","Siligap Boris","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid outage, gen faile=
d to start due to alarm ""low oil pressure""//We reset card GE and gen manu=
ally started","system","1214094","25-06-2025 20:42:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_213","NOCINC0005342427","Nkolmess=
eng","","25-06-2025 20:42:08","25-06-2025 20:33:00","25-06-2025 20:59:46","=
Cascaded Incident from TTO5509560","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, gen failed to start du=
e to alarm ""low oil pressure""//We reset card GE and gen manually started"=
,"system","1214095","25-06-2025 20:42:08","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005342419","N=
GONA","","25-06-2025 20:40:44","25-06-2025 20:32:35","25-06-2025 22:37:22",=
"Site went down because Gen started and stopped with ""low oil pressure"" a=
larm// He added oil and started Gen manualy","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down beca=
use Gen started and stopped with ""low oil pressure"" alarm// He added oil =
and started Gen manualy","edwige.kapawo@matech-cameroun.com","490","25-06-2=
025 20:40:44","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005342396","E=
SSOS OASIS 1111","","25-06-2025 20:37:47","25-06-2025 20:36:37","25-06-2025=
 20:51:55","(Unstable site) Grid outage,Site went down because Gen overload=
 (17kva, 250A) // Grid return","Siligap Boris","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","(Unstable site) Grid outage,Site went down b=
ecause Gen overload (17kva, 250A) // Grid return","edwige.kapawo@matech-cam=
eroun.com","70","25-06-2025 20:37:47","MATECH CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0005342392","Nko=
lmesseng","IHS_YND_215, IHS_YND_213, IHS_YND_739, IHS_YND_214, IHS_YND_217"=
,"25-06-2025 20:36:08","25-06-2025 20:33:00","25-06-2025 20:59:46","Grid ou=
tage, gen failed to start due to alarm ""low oil pressure""//We reset card =
GE and gen manually started","Siligap Boris","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage, gen failed to start due to a=
larm ""low oil pressure""//We reset card GE and gen manually started","gera=
rd.tchangoue@matech-cameroun.com","189","25-06-2025 20:36:08","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005342339","M=
elen Ba'aba","","25-06-2025 20:28:20","25-06-2025 20:23:11","25-06-2025 20:=
57:18","Grid outage, site went down because gen ran until fuel shortage//Re=
fueling done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran until fuel shortage//Refue=
ling done","edwige.kapawo@matech-cameroun.com","311","25-06-2025 20:28:20",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005342330","M=
imboman-Ecole","","25-06-2025 20:25:42","25-06-2025 20:22:33","25-06-2025 2=
1:33:58","Active // No power issue on site Ubaie: 54.2 V,site on gen The FM=
E TX Eloundou Bertrant (693212405) From Huawei is Informed.","Mba Lazare He=
rve","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active // No power issue on site Ubaie: 54.2 V,site on gen=
 The FME TX Eloundou Bertrant (693212405) From Huawei is Informed.","edwige=
.kapawo@matech-cameroun.com","190","25-06-2025 20:25:42","MATECH CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0005342314","Mim=
boman3","","25-06-2025 20:22:19","25-06-2025 20:20:11","25-06-2025 21:18:18=
","Grid outage, site went down because gen failed to start due to PWC ZTE m=
alfunction // He reset controller and gen manually started","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid outage, site went down because gen failed to start due to PWC ZTE mal=
function // He reset controller and gen manually started","gerard.tchangoue=
@matech-cameroun.com","129","25-06-2025 20:22:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005342261","Messassi=
 okolo","","25-06-2025 20:13:02","25-06-2025 20:10:07","25-06-2025 20:55:47=
","Cascaded Incident from TTO5509405","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (Gen Noise) // Grid return","system","26610=
0","25-06-2025 20:13:02","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005342256","E=
MANA BILICK CITY","IHS_YND_279","25-06-2025 20:12:20","25-06-2025 20:10:07"=
,"25-06-2025 21:01:40","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid return","Fabrice Pouakam","Access Denial","L=
ease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid o=
utage, site down because site behaves as Grid only site (Gen Noise) // Grid=
 return","edwige.kapawo@matech-cameroun.com","135","25-06-2025 20:12:20","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005342252","S=
IMBOCK BONAMBAPE","","25-06-2025 20:11:10","25-06-2025 20:04:01","25-06-202=
5 20:10:03","Grid Outage, Site went down before Gen start due to poor backu=
p // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before Ge=
n start due to poor backup // Grid returned","edwige.kapawo@matech-cameroun=
.com","430","25-06-2025 20:11:10","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005342207","A=
wae Ewonkan","","25-06-2025 20:02:47","25-06-2025 20:02:38","25-06-2025 20:=
42:52","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed //Grid rreturn","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed //Grid rret=
urn","edwige.kapawo@matech-cameroun.com","10","25-06-2025 20:02:47","MATECH=
 CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0005342169","Eko=
unou","","25-06-2025 19:57:54","25-06-2025 19:56:47","25-06-2025 20:46:07",=
"Site went down due to Biganstil (679161144//Dowen) is on site for swap PWC=
//End of work","Albran Byorel","Installation Activity","Passive","Planned A=
ctivity","Installation Activity","Site went down due to Biganstil (67916114=
4//Dowen) is on site for swap PWC//End of work","gerard.tchangoue@matech-ca=
meroun.com","68","25-06-2025 19:57:54","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005342161","E=
bogo","","25-06-2025 19:56:19","25-06-2025 19:54:12","25-06-2025 20:40:59",=
"Grid fluctuation, site went down because Gen failed to start due to grid b=
ad voltag // He bypassed the grid and started Gen manually","Siligap Boris"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid fluctuation, site went down because Gen failed to start due to grid ba=
d voltag // He bypassed the grid and started Gen manually","edwige.kapawo@m=
atech-cameroun.com","129","25-06-2025 19:56:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005342127","MEHANDAN=
","","25-06-2025 19:51:19","25-06-2025 19:46:32","25-06-2025 19:53:02","Cas=
caded Incident from TTO5509258","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","267501","25-06-2025 19:51:19","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005342125","O=
dza II OCM","IHS_YND_528","25-06-2025 19:50:44","25-06-2025 19:46:32","25-0=
6-2025 19:53:35","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","edwige.kapawo@matech-cameroun.com","254","25-06-20=
25 19:50:44","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0005342014","Nko=
zoa","","25-06-2025 19:36:59","25-06-2025 19:30:54","26-06-2025 13:34:54","=
Grid outage.gen failed to start due to priming pump faulty//We replace prim=
ing pump and gen manually started","Fabrice Pouakam","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Priming Motor Faulty","Grid outage.gen failed to =
start due to priming pump faulty//We replace priming pump and gen manually =
started","gerard.tchangoue@matech-cameroun.com","444","25-06-2025 19:36:59"=
,"MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005341410","ODZ=
A MINKAN EDIBI ASSI","","25-06-2025 18:37:50","25-06-2025 18:36:41","25-06-=
2025 22:14:18","Grid outage,site went down because Gen failed to start due =
toGen overload(12.5 kva //180A )SS HIS Francois is informed//He reduiced th=
e load and manually started the Gen","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage,site went down because Gen=
 failed to start due toGen overload(12.5 kva //180A )SS HIS Francois is inf=
ormed//He reduiced the load and manually started the Gen","gerard.tchangoue=
@matech-cameroun.com","70","25-06-2025 18:37:50","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0005341381","H=
-Progres","","25-06-2025 18:34:03","25-06-2025 18:28:44","25-06-2025 20:13:=
43","Grid Only, No space to deploy MGE //Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to de=
ploy MGE //Grid return","edwige.kapawo@matech-cameroun.com","321","25-06-20=
25 18:34:03","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005341373","NKO=
MKANA ELIZA HOTEL","","25-06-2025 18:31:33","25-06-2025 18:30:27","25-06-20=
25 19:27:53","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","67","25-06-2025 18:31:33","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005341014","OBA=
M NGOLA OCM","","25-06-2025 17:43:59","25-06-2025 17:43:51","25-06-2025 21:=
10:36","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down due to PWC overload //Site s=
tabilised","gerard.tchangoue@matech-cameroun.com","10","25-06-2025 17:43:59=
","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005340971","Nko=
lnda","","25-06-2025 17:36:41","25-06-2025 17:34:37","25-06-2025 17:37:37",=
"Grid fluctuation, site went down because Gen failed to start due to grid b=
ad voltage No Rcp// He bypassed grid and started Gen manually","Albran Byor=
el","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because Gen failed to start due to grid=
 bad voltage No Rcp// He bypassed grid and started Gen manually","gerard.tc=
hangoue@matech-cameroun.com","125","25-06-2025 17:36:41","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005340962","O=
LAMA","","25-06-2025 17:35:42","25-06-2025 17:34:34","25-06-2025 18:00:26",=
"Active // No power issue on site Ubaie =3D54.5V site on Gen The TX FME Hen=
ri (699949693) from Huawei is informed.","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/ No power issue on site Ubaie =3D54.5V site on Gen The TX FME Henri (69994=
9693) from Huawei is informed.","edwige.kapawo@matech-cameroun.com","69","2=
5-06-2025 17:35:42","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005340884","A=
bome","","25-06-2025 17:27:59","25-06-2025 17:17:59","25-06-2025 17:46:30",=
"Active/ No power issue on site Ubay 53.7V site on Grid and The TX FME Leon=
el Steve (655184876) from huawei is informed ","MINKA NICOLAS","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active/ No power issue on site Ubay 53.7V site on Grid and The TX FME Leone=
l Steve (655184876) from huawei is informed ","edwige.kapawo@matech-camerou=
n.com","601","25-06-2025 17:27:59","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005340877","B=
arriere","","25-06-2025 17:26:57","25-06-2025 17:18:50","25-06-2025 17:35:0=
7"," Active// No power issue on site Ubay: 54.5V site on Gen TX Fme SAMBA (=
654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm"," Active// No p=
ower issue on site Ubay: 54.5V site on Gen TX Fme SAMBA (654266058/Huawei) =
is informed.","edwige.kapawo@matech-cameroun.com","489","25-06-2025 17:26:5=
7","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005340753","Mfou EPC=
","","25-06-2025 17:08:35","25-06-2025 17:00:34","25-06-2025 17:28:39","Cas=
caded Incident from TTO5507745","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //GEN automatically started","system","270233","2=
5-06-2025 17:08:35","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005340750","M=
fou OCM","IHS_YND_674","25-06-2025 17:07:43","25-06-2025 17:00:34","25-06-2=
025 17:28:39","Grid Outage, Site Down before gen Started due to poor backup=
 //GEN automatically started","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down be=
fore gen Started due to poor backup //GEN automatically started","edwige.ka=
pawo@matech-cameroun.com","430","25-06-2025 17:07:43","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005340720","C=
NR","","25-06-2025 17:03:19","23-06-2025 12:41:08","23-06-2025 12:43:08","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed automatically","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Gen started automatically","gerard.tchangoue@mat=
ech-cameroun.com","188532","25-06-2025 17:03:19","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005340697","O=
bili Carrefour","","25-06-2025 17:00:46","23-06-2025 12:41:22","23-06-2025 =
12:46:22","Grid fluctuation, site went down because Gen started and stopped=
 due to Grid bad voltage// Grid stabilized","Paul BIBOUM","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, =
site went down because Gen started and stopped due to Grid bad voltage// Gr=
id stabilized","gerard.tchangoue@matech-cameroun.com","188364","25-06-2025 =
17:00:46","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005340609","A=
hala","","25-06-2025 16:45:21","25-06-2025 16:36:59","25-06-2025 20:06:52",=
"Grid fluctuations , Site went down due to PWC overload (15KVA, 360A) Site =
stabilizer","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Recti=
fier Module Overloaded","Unstable site) Grid fluctuations , Site went down =
due to PWC overload (15KVA, 360A)","edwige.kapawo@matech-cameroun.com","502=
","25-06-2025 16:45:21","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005340595","Nko=
lnda","","25-06-2025 16:42:13","25-06-2025 16:36:36","25-06-2025 17:25:11",=
"Grid fluctuation, site went down because Gen failed to start due to grid b=
ad voltage No Rcp// He bypassed grid and started Gen manually","Albran Byor=
el","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because Gen failed to start due to grid=
 bad voltage No Rcp// He bypassed grid and started Gen manually","gerard.tc=
hangoue@matech-cameroun.com","338","25-06-2025 16:42:13","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005340570","F=
ouda-New","","25-06-2025 16:38:40","24-06-2025 14:02:22","25-06-2025 14:07:=
36","Grid Outage, site went down before Gen start due to Poor battery backu=
p // Grid returned","Delor Telezing","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, site went down before Ge=
n start due to Poor battery backup // Grid returned","gerard.tchangoue@mate=
ch-cameroun.com","95779","25-06-2025 16:38:40","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005340525","T=
singa","","25-06-2025 16:32:02","24-06-2025 15:29:37","24-06-2025 15:34:37"=
,"Grid Outage, Site went down due to PWC overload // Grid return","Mboua Th=
ierry","Equipment Repair","Passive","Rectifier","Rectifier Module Overloade=
d","Grid Outage, Site went down due to PWC overload // Grid return","gerard=
.tchangoue@matech-cameroun.com","90146","25-06-2025 16:32:02","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005340405","N=
kozoa","","25-06-2025 16:15:11","25-06-2025 16:13:02","25-06-2025 17:41:41"=
,"Grid outage, site went down because Gen fail to start due to diesel circu=
it blocked by mud // He unblocked the circuit and put site on Gen","Fabrice=
 Pouakam","Fuel Outage (Probable)","Passive","Diesel","Fuel Line Issue","Gr=
id outage, site went down because Gen fail to start due to diesel circuit b=
locked by mud // He unblocked the circuit and put site on Gen
","edwige.kapawo@matech-cameroun.com","131","25-06-2025 16:15:11","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005340331","Elig-Edz=
oa","","25-06-2025 15:59:21","25-06-2025 15:27:11","25-06-2025 18:10:12","C=
ascaded Incident from TTO5507108","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen failed to=
 start due to Pwc ZTE dysfunction // He reset and manual start of Gen","sys=
tem","275800","25-06-2025 15:59:21","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005340324","NKO=
MKANA ELIZA HOTEL","","25-06-2025 15:58:21","25-06-2025 15:57:13","25-06-20=
25 17:03:13","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","69","25-06-2025 15:58:21","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005340139","Nta=
ba","IHS_YND_133","25-06-2025 15:31:20","25-06-2025 15:27:11","25-06-2025 1=
8:14:57","Grid outage, site went down because gen failed to start due to Pw=
c ZTE dysfunction // He reset and manual start of Gen","Delor Telezing","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module","Grid outage, site=
 went down because gen failed to start due to Pwc ZTE dysfunction // He res=
et and manual start of Gen","gerard.tchangoue@matech-cameroun.com","250","2=
5-06-2025 15:31:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005340125","Mfou EPC=
","","25-06-2025 15:29:26","25-06-2025 15:16:59","25-06-2025 15:25:16","Cas=
caded Incident from TTO5507031","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //GEN automatically started","system","1218885","=
25-06-2025 15:29:26","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005340105","M=
fou OCM","IHS_YND_674","25-06-2025 15:26:47","25-06-2025 15:16:59","25-06-2=
025 15:25:16","Grid Outage, Site Down before gen Started due to poor backup=
 //GEN automatically started","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down be=
fore gen Started due to poor backup //GEN automatically started","edwige.ka=
pawo@matech-cameroun.com","588","25-06-2025 15:26:47","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005340035","M=
ontee-Des-Soeurs","","25-06-2025 15:17:48","25-06-2025 13:55:35","25-06-202=
5 14:21:56","(Backtraking) Grid outage ,site down due to Gen overload (15 K=
VA/210 A) // Grid return","Hyemafo Gildas","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","(Backtraking) Grid outage ,site down due to Gen =
overload (15 KVA/210 A) // Grid return","edwige.kapawo@matech-cameroun.com"=
,"4935","25-06-2025 15:17:48","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005339904","M=
vog-Ebanda","","25-06-2025 14:53:06","25-06-2025 14:45:50","25-06-2025 15:0=
3:59","Active // No power issue on site,  Ubaie =3D52V site on Grid. Armand=
 Nguetsa(691144412) from Huawei is informed. ","Siligap Boris","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue on site,  Ubaie =3D52V site on Grid. Armand Nguets=
a(691144412) from Huawei is informed. ","edwige.kapawo@matech-cameroun.com"=
,"437","25-06-2025 14:53:06","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005339757","Ebo=
go","","25-06-2025 14:28:05","25-06-2025 14:26:58","25-06-2025 14:28:12","G=
rid fluctuation, site went down because Gen failed to start due to grid bad=
 voltag // Site stabilised","Siligap Boris","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid fluctuation, site went down=
 because Gen failed to start due to grid bad voltag // He bypassed the grid=
 and started Gen manually","gerard.tchangoue@matech-cameroun.com","68","25-=
06-2025 14:28:05","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005339718","OBA=
M NGOLA OCM","","25-06-2025 14:20:56","25-06-2025 14:20:51","25-06-2025 17:=
29:14","(Unstable site) Site went down due to PWC overload","MINKA NICOLAS"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","(U=
nstable site) Site went down due to PWC overload //Site stabilised","gerard=
.tchangoue@matech-cameroun.com","6","25-06-2025 14:20:56","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005339475","EKI=
E","","25-06-2025 13:47:06","25-06-2025 13:40:47","25-06-2025 13:48:33","Si=
te went down because rectifier disfunctionning // He reset it: Site on grid=
","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down because rectifier disfunctionning // He reset it: Site o=
n grid","franck.nkomot@matech-cameroun.com","379","25-06-2025 13:47:06","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005339411","S=
IMBOCK BONAMBAPE","","25-06-2025 13:32:30","25-06-2025 13:26:13","25-06-202=
5 13:29:23","Grid Outage, Site went down before Gen start due to poor backu=
p // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before Ge=
n start due to poor backup // Grid returned","christelle.ngonga@matech-came=
roun.com","378","25-06-2025 13:32:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005339289","ELOUMDEM=
 CARRIERE 2","","25-06-2025 13:11:19","25-06-2025 13:07:05","25-06-2025 13:=
25:05","Cascaded Incident from TTO5506082","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started manually by FME","system"=
,"269859","25-06-2025 13:11:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005339287","Eto koss=
 Yde","","25-06-2025 13:11:19","25-06-2025 13:07:05","25-06-2025 13:25:05",=
"Cascaded Incident from TTO5506082","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started manually by FME","system","26985=
9","25-06-2025 13:11:19","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005339277","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","25-06-2025 13:10:11","25-06-2025 13:07=
:05","25-06-2025 13:25:05","Grid outage, Site went down before Gen start du=
e to poor backup // Gen started manually by FME","Fanda Brice","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
, Site went down before Gen start due to poor backup // Gen started manuall=
y by FME","franck.nkomot@matech-cameroun.com","188","25-06-2025 13:10:11","=
MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005339257","N=
koabang Ebolmedjock","","25-06-2025 13:06:50","25-06-2025 13:06:45","25-06-=
2025 13:15:45","Site impacted by CTR_711 Nkolmesseng Abom not ihs site ","M=
ba Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","Affected by 3rd Party Site","Site impacted by CTR_711 Nkolmesseng A=
bom not ihs site ","christelle.ngonga@matech-cameroun.com","6","25-06-2025 =
13:06:50","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005339244","N=
koabang2","","25-06-2025 13:04:37","25-06-2025 13:02:31","25-06-2025 13:07:=
05","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ch=
ristelle.ngonga@matech-cameroun.com","127","25-06-2025 13:04:37","MATECH CM=
R"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005339225","N=
koabang2","","25-06-2025 13:00:46","25-06-2025 12:29:08","25-06-2025 12:31:=
35","Backtraking: Grid outage, site went down due to gen overload (22KVA, 3=
30A), SS Blaise IHS is informed // Grid return","Mba Lazare Herve","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Backtraking: Grid outage=
, site went down due to gen overload (22KVA, 330A), SS Blaise IHS is inform=
ed // Grid return","christelle.ngonga@matech-cameroun.com","1900","25-06-20=
25 13:00:46","MATECH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0005339126","Com=
plex Beac II","","25-06-2025 12:42:43","25-06-2025 12:32:59","25-06-2025 13=
:18:31","Grid outage , site down due to gen battery discharge // gen start =
with and  external battery,  ( investigation will be done after grid restor=
ation).","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Ge=
nerator Battery","Grid outage , site down due to gen battery discharge // g=
en start with and  external battery,  ( investigation will be done after gr=
id restoration).","franck.nkomot@matech-cameroun.com","586","25-06-2025 12:=
42:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005339016","Elig-Edz=
oa","","25-06-2025 12:31:19","25-06-2025 12:29:54","25-06-2025 13:40:01","C=
ascaded Incident from TTO5505794 - Cascade Removed From TTO5505794 - Cascad=
e Removed From TTO5505794","","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","impacted by Ntaba_CTR_380 (grid o=
utage, grid return)","system","85","25-06-2025 12:31:19","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005339012","N=
taba","","25-06-2025 12:29:59","25-06-2025 12:29:54","25-06-2025 13:45:48",=
"Grid outage, site went down because gen failed to start due to Pwc ZTE dys=
function // He reset and manual start of Gen","Delor Telezing","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, si=
te went down because gen failed to start due to Pwc ZTE dysfunction // He r=
eset and manual start of Gen","christelle.ngonga@matech-cameroun.com","6","=
25-06-2025 12:29:59","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005338953","EKI=
E","","25-06-2025 12:22:41","25-06-2025 12:15:53","25-06-2025 13:29:53","Si=
te went down because Gen failed to start due to Alarm *Under frequency*//He=
 reset the Gen card and manually started the Gen","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Site went down becau=
se Gen failed to start due to Alarm *Under frequency*//He reset the Gen car=
d and manually started the Gen","franck.nkomot@matech-cameroun.com","409","=
25-06-2025 12:22:41","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005338761","Bar=
riere","","25-06-2025 11:53:12","25-06-2025 11:45:05","25-06-2025 12:53:58"=
,"Site went down because Gen failed to start due to Grid Bad voltage // He =
bypassed Grid and started Gen manually","Hyemafo Gildas","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Site went down beca=
use Gen failed to start due to Grid Bad voltage // He bypassed Grid and sta=
rted Gen manually","franck.nkomot@matech-cameroun.com","545","25-06-2025 11=
:53:12","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005338716","OBA=
M NGOLA OCM","","25-06-2025 11:47:09","25-06-2025 11:30:51","25-06-2025 14:=
03:26","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down due to PWC overload //Site s=
tabilised","franck.nkomot@matech-cameroun.com","980","25-06-2025 11:47:09",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005338705","M=
ontee-Des-Soeurs","","25-06-2025 11:45:19","25-06-2025 11:42:11","25-06-202=
5 12:57:55","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","christelle.ngonga@matech-cameroun.com","189","25-06-2025 11:45=
:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005338663","EBOM",""=
,"25-06-2025 11:40:01","25-06-2025 11:30:49","25-06-2025 13:24:15","Cascade=
d Incident from TTO5505406","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","(Unstable site) Grid fluctuations , Site =
went down due to PWC overload (15KVA, 360A) // Site stabilised","system","2=
82776","25-06-2025 11:40:01","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005338657","A=
hala","IHS_YND_698","25-06-2025 11:38:56","25-06-2025 11:30:49","25-06-2025=
 13:24:15","(Unstable site) Grid fluctuations , Site went down due to PWC o=
verload (15KVA, 360A) // Site stabilised","MINKA NICOLAS","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","(Unstable site) Grid=
 fluctuations , Site went down due to PWC overload (15KVA, 360A) // Site st=
abilised","christelle.ngonga@matech-cameroun.com","488","25-06-2025 11:38:5=
6","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005338601","S=
aa","","25-06-2025 11:33:22","25-06-2025 11:30:11","25-06-2025 11:38:11","N=
o power issue on site ,site on Gen with Ubaie =3D51.5V The Tx Technician fr=
om Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site ,site on Gen with Ubaie =3D51.5V The Tx Technician fro=
m Huawei Gr=E9goire//654547479 is informed","christelle.ngonga@matech-camer=
oun.com","2207","25-06-2025 11:33:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005338403","C-Suprem=
e","","25-06-2025 11:06:38","25-06-2025 10:52:20","25-06-2025 10:56:33","Ca=
scaded Incident from TTO5505043","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage , site went down before Gen failed to =
started due to poor battery backup // Grid restoration","system","263699","=
25-06-2025 11:06:38","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005338332","M=
vog Mbi New","IHS_YND_021","25-06-2025 10:54:28","25-06-2025 10:52:20","25-=
06-2025 10:56:33","Grid outage , site went down before Gen failed to starte=
d due to poor battery backup // Grid restoration","MINKA NICOLAS","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age , site went down before Gen failed to started due to poor battery backu=
p // Grid restoration","christelle.ngonga@matech-cameroun.com","129","25-06=
-2025 10:54:28","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005338158","M=
vog Mbi New","IHS_YND_021","25-06-2025 10:26:51","25-06-2025 10:25:19","25-=
06-2025 10:26:39","Grid outage , site went down before Gen failed to starte=
d due to poor battery backup // Grid restoration","MINKA NICOLAS","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age , site went down before Gen failed to started due to poor battery backu=
p // Grid restoration","christelle.ngonga@matech-cameroun.com","93","25-06-=
2025 10:26:51","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005338127","C=
-Supreme","","25-06-2025 10:19:24","25-06-2025 10:25:19","25-06-2025 10:26:=
39","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage , site went down before Gen failed to started due to poor batter=
y backup // Grid restoration","christelle.ngonga@matech-cameroun.com","2653=
02","25-06-2025 10:19:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005338046","Montee-J=
ouvence","","25-06-2025 10:00:44","25-06-2025 08:14:58","25-06-2025 08:17:5=
3","Cascaded Incident from TTO5503977","Hyemafo Gildas","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Site impacted by Nkolzie CTR_672 =
not manage by IHS","system","265865","25-06-2025 10:00:44","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005337887","S=
IMBOCK BONAMBAPE","","25-06-2025 09:38:36","25-06-2025 09:34:23","25-06-202=
5 09:39:42","Grid Outage, Site went down before Gen start due to poor backu=
p // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before Ge=
n start due to poor backup // Grid returned","christelle.ngonga@matech-came=
roun.com","255","25-06-2025 09:38:36","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005337368","S=
imbock OCM","IHS_YND_236","25-06-2025 08:22:05","25-06-2025 08:14:58","25-0=
6-2025 08:17:53","Site impacted by Nkolzie CTR_672 not manage by IHS","Hyem=
afo Gildas","Customer Equipment Failure","Active","Active Equipment Failure=
","Affected by 3rd Party Site","Site impacted by Nkolzie CTR_672 not manage=
 by IHS","christelle.ngonga@matech-cameroun.com","428","25-06-2025 08:22:05=
","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005337324","C=
omplexe-BEAC","","25-06-2025 08:07:49","25-06-2025 08:05:31","25-06-2025 08=
:07:51","Grid outage, Site went down before Gen start due to Poor battery b=
ackup // Grid return","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to Poor battery backup // Grid return","christelle.ngonga@mate=
ch-cameroun.com","139","25-06-2025 08:07:49","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005337158","N=
kozoa","","25-06-2025 07:44:40","25-06-2025 07:42:12","25-06-2025 10:24:20"=
,"Grid outage, site went down because Gen fail to start due to diesel circu=
it blocked by mud // He unblocked the circuit and put site on Gen","Fabrice=
 Pouakam","Fuel Outage (Probable)","Passive","Diesel","Fuel Line Issue","Gr=
id outage, site went down because Gen fail to start due to diesel circuit b=
locked by mud // He unblocked the circuit and put site on Gen","christelle.=
ngonga@matech-cameroun.com","150","25-06-2025 07:44:40","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005337031","A=
bome","","25-06-2025 07:15:25","25-06-2025 07:09:17","25-06-2025 07:10:13",=
"No power issue on site Ubay 53.7V site on Grid and The TX FME Leonel Steve=
 (655184876) from huawei is informed","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site Ubay 53.7V site on Grid and The TX FME Leonel Steve (65518487=
6) from huawei is informed","christelle.ngonga@matech-cameroun.com","369","=
25-06-2025 07:15:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005336990","EBOM",""=
,"25-06-2025 06:57:48","25-06-2025 05:25:28","25-06-2025 11:10:15","Cascade=
d Incident from TTO5503192","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","(Unstable site)Site went down due to PWC =
overload (15KVA, 360A) // Site stabilised","system","283186","25-06-2025 06=
:57:48","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0005336899","Nko=
zoa","","25-06-2025 06:32:08","25-06-2025 06:27:57","25-06-2025 07:33:14","=
Grid outage, Site went down because Gen fail to start due to Huawei control=
ler faulty // He reset the controller","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","ATS Relay Faulty","Grid outage, Site went down =
due to Huawei controller faulty // He reset the controller","gerard.tchango=
ue@matech-cameroun.com","252","25-06-2025 06:32:08","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005336659","A=
hala","IHS_YND_698","25-06-2025 05:31:38","25-06-2025 05:25:28","25-06-2025=
 11:10:15","(Unstable site)Site went down due to PWC overload (15KVA, 360A)=
 // Site stabilised","MINKA NICOLAS","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","(Unstable site)Site went down due to PWC =
overload (15KVA, 360A) // Site stabilised","gerard.tchangoue@matech-camerou=
n.com","371","25-06-2025 05:31:38","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005336656","Par=
adis Hotel","","25-06-2025 05:30:41","25-06-2025 05:28:34","25-06-2025 09:3=
3:05","site went down due to to relay Q11 dysfunctionning in IPT   / /  We =
disconnected relay Q11 and site on gen(relacement relay ongoing)","Siligap =
Boris","Equipment Repair","Passive","Control Panel","Relay","site went down=
 due to to relay Q11 dysfunctionning in IPT   / /  We disconnected relay Q1=
1 and site on gen(relacement relay ongoing)","gerard.tchangoue@matech-camer=
oun.com","128","25-06-2025 05:30:41","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005336486","Nko=
l-Mebanga","","25-06-2025 04:38:22","23-06-2025 21:27:52","23-06-2025 21:59=
:52","Backtracking  Active//No power issue on site Ubaie=3D50V site on Sola=
r site Tx FME Gregoire /654547479/Huawei is informed","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site Ubaie=3D50V site on Solar site Tx FME=
 Gregoire /654547479/Huawei is informed","gerard.tchangoue@matech-cameroun.=
com","112230","25-06-2025 04:38:22","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005336477","S=
imbock OCM","","25-06-2025 04:33:52","25-06-2025 04:26:36","25-06-2025 05:0=
1:39","Active // No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah M=
bah (674007438) of Huawei is informed","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah Mbah (674007438=
) of Huawei is informed","gerard.tchangoue@matech-cameroun.com","437","25-0=
6-2025 04:33:52","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0005336468","NKO=
ABANG NKOLO 3","","25-06-2025 04:30:12","23-06-2025 16:26:43","23-06-2025 1=
6:35:19","Backtracking Grid outage,Site went down due to gen overload(10KVA=
, 130A) // he reduced the load and started Gen manually","Mba Lazare Herve"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Sit=
e went down due to gen overload(10KVA, 130A) // he reduced the load and sta=
rted Gen manually","gerard.tchangoue@matech-cameroun.com","129809","25-06-2=
025 04:30:12","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005336456","NKO=
MKANA ELIZA HOTEL","","25-06-2025 04:26:23","23-06-2025 19:00:28","23-06-20=
25 19:31:02","Backtracking Site went down due to PWC Overloaded and SS IHS =
Bernard Atangana confirmed // Site stabilised","","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due to PWC Ov=
erloaded and SS IHS Bernard Atangana confirmed // Site stabilised","gerard.=
tchangoue@matech-cameroun.com","120355","25-06-2025 04:26:23","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005336433","Evo=
doula MTN","","25-06-2025 04:10:34","23-06-2025 20:15:39","23-06-2025 20:43=
:50","Backtracking Grid outage, Site went down before Gen start due to poor=
 backup// Gen Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outag=
e, Site went down before Gen start due to poor backup// Gen Automatically S=
tarted","gerard.tchangoue@matech-cameroun.com","114895","25-06-2025 04:10:3=
4","MATECH CMR"
"Closed Complete","Site Down","T1746","IHS_YND_178","NOCINC0005336377","Emo=
mbo","","25-06-2025 04:00:16","23-06-2025 21:55:18","23-06-2025 22:29:02","=
Backtracking Active// No power issue, site is on Grid with Ubaie=3D54,6V, L=
ionel Adjep(655184876) from Huawei is informed","Mba Lazare Herve","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active// No power issue, site is on Grid with Ubaie=3D54,6V, Lionel Adj=
ep(655184876) from Huawei is informed","gerard.tchangoue@matech-cameroun.co=
m","108298","25-06-2025 04:00:16","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0005336362","Clu=
b France","","25-06-2025 03:52:22","23-06-2025 21:22:32","24-06-2025 15:20:=
59","Bactracking No power issue on site Ubaie: 48V site On GRID The Tx FME =
JULIEN (693095849) of Huawei is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie: 48V site On GRID The Tx FME JULIEN (693095849) of Huawei is inf=
ormed","gerard.tchangoue@matech-cameroun.com","109791","25-06-2025 03:52:22=
","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005336340","Nko=
abang2","","25-06-2025 03:40:32","25-06-2025 03:37:00","25-06-2025 04:49:53=
","Grid outage, site went down because gen start and stopped with high temp=
 alarm // He added water and manually start the gen","Mba Lazare Herve","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Grid outage, site went down because gen start and stopped with h=
igh temp alarm // He added water and manually start the gen","gerard.tchang=
oue@matech-cameroun.com","213","25-06-2025 03:40:32","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005336324","O=
dza II OCM","","25-06-2025 03:34:22","23-06-2025 16:57:03","23-06-2025 17:0=
3:57","Bactracking. Grid fluctuations, site went down because gen failed to=
 start due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","Bactrack=
ing. Grid fluctuations, site went down because gen failed to start due to P=
WC ZTE malfunction // Grid stabilized","gerard.tchangoue@matech-cameroun.co=
m","124639","25-06-2025 03:34:22","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005336320","B=
arriere","","25-06-2025 03:32:02","23-06-2025 15:45:04","23-06-2025 15:50:2=
4","Backtracking No power issue on site Ubay: 54.6V site on Gen TX Fme SAMB=
A (654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is info=
rmed.","gerard.tchangoue@matech-cameroun.com","128818","25-06-2025 03:32:02=
","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005336312","S=
IMBOCK BONAMBAPE","","25-06-2025 03:28:26","23-06-2025 19:14:28","23-06-202=
5 19:44:49","Backtracking Active // No power issue site on grid with Ubaie:=
 54.5V TX FME Flubert (654266068) from Huawei is informed","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active // No power issue site on grid with Ubaie: 54.5V TX FME=
 Flubert (654266068) from Huawei is informed","gerard.tchangoue@matech-came=
roun.com","116038","25-06-2025 03:28:26","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005336297","A=
wae Ewonkan","","25-06-2025 03:25:03","23-06-2025 14:15:06","23-06-2025 14:=
34:37","Bactracking Grid outage site went down due to Gen Overload (20Kva, =
Iload 225 A)IHS SS Alphonse is informed//Site stabilised","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site =
went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is inform=
ed//Site stabilised","gerard.tchangoue@matech-cameroun.com","133797","25-06=
-2025 03:25:03","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005336291","A=
wae Ewonkan","","25-06-2025 03:22:31","23-06-2025 19:22:38","23-06-2025 19:=
40:14","Bactracking Grid outage site went down due to Gen Overload (20Kva, =
Iload 225 A)IHS SS Alphonse is informed//Site stabilised","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site =
went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is inform=
ed//Site stabilised","gerard.tchangoue@matech-cameroun.com","115193","25-06=
-2025 03:22:31","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005336249","OBA=
M NGOLA OCM","","25-06-2025 03:01:25","25-06-2025 03:00:10","25-06-2025 11:=
12:10","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","	(Unstable site) Site went down due to PWC overload //Site =
stabilised","gerard.tchangoue@matech-cameroun.com","76","25-06-2025 03:01:2=
5","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005336245","Ngouetou=
","","25-06-2025 02:58:09","25-06-2025 02:33:59","25-06-2025 02:34:59","Cas=
caded Incident from TTO5502715","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue U =3D 50.1V, site on batte=
ry (hybrid site and starts at U =3D 47.3V) TX FME Abdouraman of Huawei is i=
nformed.","system","264712","25-06-2025 02:58:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005336246","MBIMBIM"=
,"","25-06-2025 02:58:09","25-06-2025 02:33:59","25-06-2025 02:34:59","Casc=
aded Incident from TTO5502715","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue U =3D 50.1V, site on batter=
y (hybrid site and starts at U =3D 47.3V) TX FME Abdouraman of Huawei is in=
formed.","system","264713","25-06-2025 02:58:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005336243","Matsari"=
,"","25-06-2025 02:58:08","25-06-2025 02:33:59","25-06-2025 02:34:59","Casc=
aded Incident from TTO5502715","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue U =3D 50.1V, site on batter=
y (hybrid site and starts at U =3D 47.3V) TX FME Abdouraman of Huawei is in=
formed.","system","264711","25-06-2025 02:58:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005336242","Ngoum","=
","25-06-2025 02:58:08","25-06-2025 02:33:59","25-06-2025 02:34:59","Cascad=
ed Incident from TTO5502715","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue U =3D 50.1V, site on battery =
(hybrid site and starts at U =3D 47.3V) TX FME Abdouraman of Huawei is info=
rmed.","system","264711","25-06-2025 02:58:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005336244","Yoko OCM=
","","25-06-2025 02:58:08","25-06-2025 02:33:59","25-06-2025 02:34:59","Cas=
caded Incident from TTO5502715","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue U =3D 50.1V, site on batte=
ry (hybrid site and starts at U =3D 47.3V) TX FME Abdouraman of Huawei is i=
nformed.","system","264710","25-06-2025 02:58:08","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005336160","Nko=
lbisson IITA LP","","25-06-2025 02:08:47","25-06-2025 02:06:37","25-06-2025=
 02:10:54","No power issue site on grid with U=3D53.8v Mohamadou(69114435) =
from Huawei is informed.Noticed that it is impacted by Nkolbisson 2 ocm not=
 manage by IHS","","Customer Equipment Failure","Active","Active Equipment =
Failure","Affected by 3rd Party Site","No power issue site on grid with U=
=3D53.8v Mohamadou(69114435) from Huawei is informed.Noticed that it is imp=
acted by Nkolbisson 2 ocm not manage by IHS","gerard.tchangoue@matech-camer=
oun.com","131","25-06-2025 02:08:47","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005336013","NKO=
NGKARAK","","25-06-2025 01:29:45","25-06-2025 01:26:33","25-06-2025 03:06:0=
9","Grid outage, Gen started and stopped due to High temp alarm //He  added=
 water  and Gen start manually","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gr=
id outage, Gen started and stopped due to High temp alarm //He  added water=
  and Gen start manually","gerard.tchangoue@matech-cameroun.com","193","25-=
06-2025 01:29:45","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005335952","Par=
adis Hotel","","25-06-2025 01:07:24","25-06-2025 01:03:14","25-06-2025 03:5=
0:26","Very unstable) Site went down due to Insufficient rectifiers on site=
 //Site stabilised	","Siligap Boris","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to Insufficient rectifiers on sit=
e //Site stabilised	","gerard.tchangoue@matech-cameroun.com","251","25-06-2=
025 01:07:24","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005335734","N=
kolfon Cimencam","","24-06-2025 23:59:14","24-06-2025 23:57:43","25-06-2025=
 00:50:03","No power issue on site U=3D54,5v site on Gen The TX fme George(=
697461814) from huawei is informed. Noticed that site is impacted by Afanoy=
a II(Not manage by HIS)","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","Affected by 3rd Party Site","No power issu=
e on site U=3D54,5v site on Gen The TX fme George(697461814) from huawei is=
 informed. Noticed that site is impacted by Afanoya II(Not manage by HIS)",=
"gerard.tchangoue@matech-cameroun.com","92","24-06-2025 23:59:14","MATECH C=
MR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005335644","Aka=
k-Nkozoa-MTN-IHS","","24-06-2025 23:36:23","24-06-2025 23:28:01","24-06-202=
5 23:35:37"," Site went down because Gen started and stopped due AVR faulty=
 //He replaced AVR ","Fabrice Pouakam","Equipment Repair","Passive","ACDG G=
en","ACDG - AVR"," Site went down because Gen started and stopped due AVR f=
aulty //He replaced AVR ","gerard.tchangoue@matech-cameroun.com","504","24-=
06-2025 23:36:23","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005335641","Ebo=
go","","24-06-2025 23:34:17","24-06-2025 23:26:07","24-06-2025 23:43:57","G=
rid outage, site went down because Gen failed to start due to grid bad volt=
age // He bypassed the Grid and manually started the Gen","Siligap Boris","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id outage, site went down because Gen failed to start due to grid bad volta=
ge // He bypassed the Grid and manually started the Gen","gerard.tchangoue@=
matech-cameroun.com","491","24-06-2025 23:34:17","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005335524","A=
bome","","24-06-2025 23:07:32","24-06-2025 23:00:19","24-06-2025 23:10:52",=
"Active // No power issue on site Ubay 53.7V site on Grid and The TX FME Le=
onel Steve (655184876) from huawei is informed ","MINKA NICOLAS","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue on site Ubay 53.7V site on Grid and The TX FME L=
eonel Steve (655184876) from huawei is informed ","gerard.tchangoue@matech-=
cameroun.com","434","24-06-2025 23:07:32","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005335507","Nko=
l-Mbanda","","24-06-2025 23:04:08","24-06-2025 23:00:49","24-06-2025 23:11:=
18","	Active// No power Issue Site on Grid Ubai =3D49V, The FME The TX FME =
Mbah Hosiah (674007438) is informed.","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Active//=
 No power Issue Site on Grid Ubai =3D49V, The FME The TX FME Mbah Hosiah (6=
74007438) is informed.","gerard.tchangoue@matech-cameroun.com","200","24-06=
-2025 23:04:08","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005335431","N=
koabang Ebolmedjock","","24-06-2025 22:47:47","24-06-2025 22:40:32","24-06-=
2025 22:45:58","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","gerard.tchangoue@m=
atech-cameroun.com","436","24-06-2025 22:47:47","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005335423","A=
hala","","24-06-2025 22:44:46","24-06-2025 22:40:37","25-06-2025 00:37:35",=
"(Unstable site)Site went down due to PWC overload (15KVA, 360A)//Site stab=
ilised","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier=
 Module Overloaded","(Unstable site)Site went down due to PWC overload (15K=
VA, 360A)//Site stabilised","gerard.tchangoue@matech-cameroun.com","250","2=
4-06-2025 22:44:46","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005335235","Ebo=
go","","24-06-2025 22:06:13","24-06-2025 22:02:28","24-06-2025 23:06:22","G=
rid outage, site went down because Gen failed to start due to grid bad volt=
age // Grid stabilised (investigation ongoing)","Siligap Boris","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid outage,=
 site went down because Gen failed to start due to grid bad voltage // Grid=
 stabilised (investigation ongoing)","gerard.tchangoue@matech-cameroun.com"=
,"414","24-06-2025 22:06:13","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005335129","N=
KOLMEKONG YDE","","24-06-2025 21:48:13","24-06-2025 21:40:05","24-06-2025 2=
2:00:06","Active//No power issue on site Ubaie =3D50V site on Grid The TX F=
ME Synphorien (650257151) from Huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue on site Ubaie =3D50V site on Grid The TX FME S=
ynphorien (650257151) from Huawei is informed","edwige.kapawo@matech-camero=
un.com","490","24-06-2025 21:48:13","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005335113","A=
wae Ewonkan","","24-06-2025 21:44:48","24-06-2025 21:41:15","24-06-2025 22:=
19:56","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed//Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Site sta=
bilised","edwige.kapawo@matech-cameroun.com","214","24-06-2025 21:44:48","M=
ATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005335067","Nko=
langaa","","24-06-2025 21:38:28","24-06-2025 21:36:22","24-06-2025 23:03:21=
","Grid outage, site went down because gen ran untill fuel shortage // Refu=
eling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, site went down because gen ran untill fuel shortage // R=
efueling done","gerard.tchangoue@matech-cameroun.com","127","24-06-2025 21:=
38:28","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005335066","O=
dza","","24-06-2025 21:38:26","24-06-2025 21:36:17","24-06-2025 22:24:56","=
Grid fluctuation, Site went down because Gen failed to start due to Grid ba=
d voltage (lack of 02 phase) and poor backup// He did a bridge on the good =
phase","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation, Site went down because Gen failed t=
o start due to Grid bad voltage (lack of 02 phase) and poor backup// He did=
 a bridge on the good phase","edwige.kapawo@matech-cameroun.com","130","24-=
06-2025 21:38:26","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005335041","Djo=
nassi-Yde","","24-06-2025 21:34:40","24-06-2025 21:29:35","24-06-2025 22:08=
:59","Site went down due to 03/04 rectifiers dysfonction//He reset it and s=
ite on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down due to 03/04 rectifiers dysfonction//He res=
et it and site on Grid","gerard.tchangoue@matech-cameroun.com","305","24-06=
-2025 21:34:40","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005334889","OBA=
M NGOLA OCM","","24-06-2025 21:10:51","24-06-2025 21:08:45","25-06-2025 00:=
40:08","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down due to PWC overload //Site s=
tabilised","gerard.tchangoue@matech-cameroun.com","127","24-06-2025 21:10:5=
1","MATECH CMR"
"Closed Complete","Site Down","T1746","IHS_YND_178","NOCINC0005334636","Emo=
mbo","","24-06-2025 20:26:52","24-06-2025 20:24:46","24-06-2025 21:33:20","=
(Unstable site ) Site went down due to insufficient rectifiers on site(05)/=
/He need to add 01","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","(Unstable site ) Site went down due to insufficien=
t rectifiers on site(05)//He need to add 01","gerard.tchangoue@matech-camer=
oun.com","127","24-06-2025 20:26:52","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005334588","Par=
adis Hotel","","24-06-2025 20:16:52","24-06-2025 20:15:46","24-06-2025 21:3=
3:39","Site went down due to Insufficient rectifiers on site //Site stabili=
sed","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to Insufficient rectifiers on site //Site stabili=
sed","gerard.tchangoue@matech-cameroun.com","67","24-06-2025 20:16:52","MAT=
ECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005334543","TSI=
NGA VILLAGE 2","","24-06-2025 20:02:41","24-06-2025 19:05:33","24-06-2025 2=
0:37:08","Site went down due to disjunction of Cb(125A) in PWC // He reamed=
 Cb(125A), site on Gen	","Delor Telezing","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to =
disjunction of Cb(125A) in PWC // He reamed Cb(125A), site on Gen	","gerard=
.tchangoue@matech-cameroun.com","3429","24-06-2025 20:02:41","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005334535","E=
mombo","","24-06-2025 20:02:18","24-06-2025 19:59:03","24-06-2025 20:03:46"=
,"(Unstable site ) Site went down due to insufficient rectifiers on site(05=
)//Site stabilised","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","(Unstable site ) Site went down due to insufficien=
t rectifiers on site(05)//Site stabilised","edwige.kapawo@matech-cameroun.c=
om","195","24-06-2025 20:02:18","MATECH CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0005334518","Don=
g","","24-06-2025 19:58:36","24-06-2025 19:49:29","24-06-2025 23:34:16","Si=
te went down because CHE KOLDE of Tele Infra was on site working and he dys=
juncted the CB of the Generator(Confirm with felix Bateu)//End of work ","P=
arker Tchoup","Installation Activity","Passive","Planned Activity","Install=
ation Activity","Site went down because CHE KOLDE of Tele Infra was on site=
 working and he dysjuncted the CB of the Generator(Confirm with felix Bateu=
)//End of work ","gerard.tchangoue@matech-cameroun.com","548","24-06-2025 1=
9:58:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0005334450","Mamch Bu=
ilding","","24-06-2025 19:46:54","24-06-2025 19:44:45","24-06-2025 21:57:07=
","Cascaded Incident from TTO5500737","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid Only, No space to Deploy MG=
E // Grid return","system","274772","24-06-2025 19:46:54","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005334446","C=
harles-Atangana","IHS_YND_051","24-06-2025 19:45:55","24-06-2025 19:44:45",=
"24-06-2025 22:04:43","Grid Only, No space to Deploy MGE // Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid O=
nly, No space to Deploy MGE // Grid return","edwige.kapawo@matech-cameroun.=
com","71","24-06-2025 19:45:55","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005334374","S=
imbock OCM","","24-06-2025 19:36:59","24-06-2025 19:34:49","24-06-2025 19:4=
1:34","Site impacted by Nkolzie CTR_672 not manage by IHS","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","Affected=
 by 3rd Party Site","Site impacted by Nkolzie CTR_672 not manage by IHS","e=
dwige.kapawo@matech-cameroun.com","131","24-06-2025 19:36:59","MATECH CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0005334325","H=
-Prince","","24-06-2025 19:29:20","24-06-2025 19:27:07","24-06-2025 19:43:0=
0","Grid fluctuation, Site went down because Gen failed to start due to Gri=
d bad voltage No RCP //He bypassed Grid and started Gen manualy","Mboua Thi=
erry","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, Site went down because Gen failed to start due to Gr=
id bad voltage No RCP //He bypassed Grid and started Gen manualy","edwige.k=
apawo@matech-cameroun.com","134","24-06-2025 19:29:20","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005334276","S=
IMBOCK BONAMBAPE","","24-06-2025 19:13:16","24-06-2025 19:10:10","24-06-202=
5 19:26:09","Grid Outage, Site went down before Gen start due to poor backu=
p // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before Ge=
n start due to poor backup // Grid returned","gerard.tchangoue@matech-camer=
oun.com","187","24-06-2025 19:13:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005334273","EBOM",""=
,"24-06-2025 19:12:27","24-06-2025 19:04:26","24-06-2025 22:25:24","Cascade=
d Incident from TTO5500554","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","(Unstable site)Site went down due to PWC =
overload (15KVA, 360A)//Site stablilsed","system","277186","24-06-2025 19:1=
2:27","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005334269","A=
hala","IHS_YND_698","24-06-2025 19:11:37","24-06-2025 19:04:26","24-06-2025=
 22:25:24","(Unstable site)Site went down due to PWC overload (15KVA, 360A)=
//Site stablilsed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module Overloaded","(Unstable site)Site went down due to PWC ov=
erload (15KVA, 360A)//Site stablilsed","gerard.tchangoue@matech-cameroun.co=
m","432","24-06-2025 19:11:37","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005334130","Bar=
riere","","24-06-2025 18:47:58","24-06-2025 18:44:49","24-06-2025 20:07:56"=
,"Grid outage, site went down because gen failed to start with alarm underv=
oltage // He reset gen card and gen manually started","Hyemafo Gildas","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, si=
te went down because gen failed to start with alarm undervoltage // He rese=
t gen card and gen manually started","gerard.tchangoue@matech-cameroun.com"=
,"190","24-06-2025 18:47:58","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005334067","OBA=
M NGOLA OCM","","24-06-2025 18:35:19","24-06-2025 18:29:13","24-06-2025 20:=
56:08","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down due to PWC overload //Site s=
tabilised","gerard.tchangoue@matech-cameroun.com","367","24-06-2025 18:35:1=
9","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005334063","Mok=
olo Yaounde","","24-06-2025 18:34:24","24-06-2025 18:28:17","24-06-2025 19:=
44:27","Grid only site, no space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e, no space to deploy MDGE // Grid returned","gerard.tchangoue@matech-camer=
oun.com","368","24-06-2025 18:34:24","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005334057","Sim=
e Building","","24-06-2025 18:33:07","24-06-2025 18:27:01","24-06-2025 18:5=
3:01","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","gerard.tchan=
goue@matech-cameroun.com","367","24-06-2025 18:33:07","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005334051","Cit=
e des nations","","24-06-2025 18:31:42","24-06-2025 18:26:34","24-06-2025 1=
8:33:16","Grid outage,site went down before Gen started due to Poor battery=
 backup // Grid returned","Paul BIBOUM","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage,site went down before =
Gen started due to Poor battery backup // Grid returned","gerard.tchangoue@=
matech-cameroun.com","309","24-06-2025 18:31:42","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005334044","Ron=
d Point Express1114","","24-06-2025 18:30:18","24-06-2025 18:26:12","24-06-=
2025 18:40:12","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Grid returned","gerard.tchangoue@matech-ca=
meroun.com","247","24-06-2025 18:30:18","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005334014","Par=
adis Hotel","","24-06-2025 18:23:59","24-06-2025 18:21:53","24-06-2025 20:1=
1:23","Site went down due to Insufficient rectifiers on site //Site stabili=
sed","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to Insufficient rectifiers on site //Site stabili=
sed","gerard.tchangoue@matech-cameroun.com","127","24-06-2025 18:23:59","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005333859","S=
IMBOCK BONAMBAPE","","24-06-2025 17:55:57","24-06-2025 17:50:50","24-06-202=
5 17:55:51","Grid Outage, Site went down before Gen start due to poor backu=
p // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before Ge=
n start due to poor backup // Grid returned","edwige.kapawo@matech-cameroun=
.com","309","24-06-2025 17:55:57","MATECH CMR"
"Closed Complete","Site Down","T0530","IHS_YND_252","NOCINC0005333839","Kow=
eit City","","24-06-2025 17:53:41","24-06-2025 17:47:20","24-06-2025 22:25:=
36","Site went down due to KWONTCHOU Yves  (659026587//epitec)  is on site =
for swap PWC//End of work","Albran Byorel","Installation Activity","Passive=
","Planned Activity","Installation Activity","Site went down due to KWONTCH=
OU Yves  (659026587//epitec)  is on site for swap PWC//End of work","ludivi=
ne.ngamaleu@ihstowers.com","382","24-06-2025 17:53:41","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005333627","NKO=
MKANA ELIZA HOTEL","","24-06-2025 17:26:09","24-06-2025 17:24:03","24-06-20=
25 17:26:44","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","127","24-06-2025 17:26:09","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005333595","Aka=
k-Nkozoa-MTN-IHS","","24-06-2025 17:22:50","24-06-2025 17:20:37","24-06-202=
5 21:45:46","(Unstable site)Site went down de to  AVR Faulty //Site stabili=
sed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - AVR"=
,"(Unstable site)Site went down de to  AVR Faulty //Site stabilised","edwig=
e.kapawo@matech-cameroun.com","215","24-06-2025 17:22:50","MATECH CMR"
"Closed Complete","Site Down","T2222","IHS_YND_697","NOCINC0005333578","Nom=
ayos-IHS","","24-06-2025 17:20:38","24-06-2025 17:18:30","24-06-2025 17:20:=
59","(Unstable) Site went down because Gen started and stopped due AVR faul=
ty //Site stabilised (AVR to be replaced)","Fanda Brice","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - AVR","(Unstable) Site went down because Gen s=
tarted and stopped due AVR faulty //Site stabilised (AVR to be replaced)","=
gerard.tchangoue@matech-cameroun.com","128","24-06-2025 17:20:38","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005333228","Mfou EPC=
","","24-06-2025 16:11:23","24-06-2025 16:06:37","24-06-2025 16:35:34","Cas=
caded Incident from TTO5499356","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","266309","24-06-2025 16=
:11:23","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005333225","M=
fou OCM","IHS_YND_674","24-06-2025 16:10:47","24-06-2025 16:06:37","24-06-2=
025 16:35:34","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","edwige.kapawo@matech-cameroun.com=
","251","24-06-2025 16:10:47","MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0005333148","c=
hina embassy yde","","24-06-2025 16:00:55","24-06-2025 15:58:42","24-06-202=
5 17:23:26","Grid outage, No space to deploy MGE // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","=
134","24-06-2025 16:00:55","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005333031","Mok=
olo Yaounde","","24-06-2025 15:41:14","24-06-2025 15:34:08","24-06-2025 15:=
46:49","Grid only site, no space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e, no space to deploy MDGE // Grid returned","gerard.tchangoue@matech-camer=
oun.com","428","24-06-2025 15:41:14","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005333027","Ron=
d Point Express1114","","24-06-2025 15:40:11","24-06-2025 15:32:54","24-06-=
2025 15:48:19","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Grid returned","gerard.tchangoue@matech-ca=
meroun.com","438","24-06-2025 15:40:11","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005333002","Sim=
e Building","","24-06-2025 15:35:59","24-06-2025 15:32:24","24-06-2025 15:4=
6:18","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","gerard.tchan=
goue@matech-cameroun.com","216","24-06-2025 15:35:59","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005332940","A=
kak-Nkozoa-MTN-IHS","","24-06-2025 15:25:54","24-06-2025 15:22:59","24-06-2=
025 16:46:34"," Site went down because Gen started and stopped due AVR faul=
ty //Site stabilised (AVR to be replaced)","Fabrice Pouakam","Equipment Rep=
air","Passive","ACDG Gen","ACDG - AVR"," Site went down because Gen started=
 and stopped due AVR faulty //Site stabilised (AVR to be replaced)","edwige=
.kapawo@matech-cameroun.com","177","24-06-2025 15:25:54","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005332881","OBA=
M NGOLA OCM","","24-06-2025 15:19:38","24-06-2025 15:18:32","24-06-2025 18:=
20:47","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down due to PWC overload //Site s=
tabilised","gerard.tchangoue@matech-cameroun.com","67","24-06-2025 15:19:38=
","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005332880","A=
bome","","24-06-2025 15:19:17","24-06-2025 15:11:59","24-06-2025 16:23:25",=
"Active // No power issue on site Ubay 53.7V site on Grid and The TX FME Le=
onel Steve (655184876) from huawei is informed , site up without interventi=
on","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active // No power issue on site Ubay 53.7V=
 site on Grid and The TX FME Leonel Steve (655184876) from huawei is inform=
ed , site up without intervention","edwige.kapawo@matech-cameroun.com","440=
","24-06-2025 15:19:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0005332805","NKOLMEKO=
NG YDE","","24-06-2025 15:08:14","24-06-2025 14:44:09","24-06-2025 15:21:40=
","Cascaded Incident from TTO5498717","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause gen failed to start with alarm undervoltage // He reset gen card and =
gen manually started","system","271206","24-06-2025 15:08:14","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005332779","Par=
adis Hotel","","24-06-2025 15:03:46","24-06-2025 15:02:39","24-06-2025 18:1=
2:51","Site went down due to Insufficient rectifiers on site //Site stabili=
sed","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to Insufficient rectifiers on site //Site stabili=
sed","gerard.tchangoue@matech-cameroun.com","68","24-06-2025 15:03:46","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005332767","O=
LAMA","","24-06-2025 15:01:49","24-06-2025 14:55:14","24-06-2025 19:17:36",=
"Active // No power issue on site Ubaie =3D54.5V site on Grid The TX FME He=
nri (699949693) from Huawei is informed.","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","
Active // No power issue on site Ubaie =3D54.5V site on Grid The TX FME Hen=
ri (699949693) from Huawei is informed.
","edwige.kapawo@matech-cameroun.com","396","24-06-2025 15:01:49","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005332697","Nkolondo=
m","","24-06-2025 14:51:10","24-06-2025 14:44:09","24-06-2025 15:21:40","Ca=
scaded Incident from TTO5498717","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen failed to start with alarm undervoltage // He reset gen card and gen m=
anually started","system","271205","24-06-2025 14:51:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0005332693","Messassi=
","","24-06-2025 14:51:09","24-06-2025 14:44:09","24-06-2025 15:21:40","Cas=
caded Incident from TTO5498717","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen failed to start with alarm undervoltage // He reset gen card and gen ma=
nually started","system","271210","24-06-2025 14:51:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0005332695","Nyom OCM=
","","24-06-2025 14:51:09","24-06-2025 14:44:09","24-06-2025 15:21:40","Cas=
caded Incident from TTO5498717","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen failed to start with alarm undervoltage // He reset gen card and gen ma=
nually started","system","271206","24-06-2025 14:51:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0005332694","Nkozoa",=
"","24-06-2025 14:51:09","24-06-2025 14:44:09","24-06-2025 15:21:40","Casca=
ded Incident from TTO5498717","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start with alarm undervoltage // He reset gen card and gen manu=
ally started","system","271209","24-06-2025 14:51:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0005332696","Messassi=
 2","","24-06-2025 14:51:09","24-06-2025 14:44:09","24-06-2025 15:21:40","C=
ascaded Incident from TTO5498717","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen failed to start with alarm undervoltage // He reset gen card and gen =
manually started","system","271208","24-06-2025 14:51:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0005332692","Olembe-T=
erminus","","24-06-2025 14:51:08","24-06-2025 14:44:09","24-06-2025 15:21:4=
0","Cascaded Incident from TTO5498717","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen failed to start with alarm undervoltage // He reset gen card and=
 gen manually started","system","271207","24-06-2025 14:51:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0005332691","Ekombiti=
e","","24-06-2025 14:51:08","24-06-2025 14:44:09","24-06-2025 15:21:40","Ca=
scaded Incident from TTO5498717","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen failed to start with alarm undervoltage // He reset gen card and gen m=
anually started","system","271210","24-06-2025 14:51:08","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005332666","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_280, IHS_YND_304","24-06-2025 14:48:20","24-06-2025 14:4=
4:09","24-06-2025 15:21:40","Grid outage, site went down because gen failed=
 to start with alarm undervoltage // He reset gen card and gen manually sta=
rted","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","Grid outage, site went down because gen failed to start with a=
larm undervoltage // He reset gen card and gen manually started","edwige.ka=
pawo@matech-cameroun.com","252","24-06-2025 14:48:20","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0005332517","Imm=
-Olympique","","24-06-2025 14:22:32","24-06-2025 14:20:25","24-06-2025 14:3=
8:40","Grid outage,site went down because Gen failed to start due to Gen ov=
erload(20KVA//295A) SS HIS Raoul is informed//Grid returned","Paul BIBOUM",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,site=
 went down because Gen failed to start due to Gen overload(20KVA//295A) SS =
HIS Raoul is informed//Grid returned","franck.nkomot@matech-cameroun.com","=
129","24-06-2025 14:22:32","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005332208","Evo=
doula MTN","","24-06-2025 13:40:01","24-06-2025 13:36:51","24-06-2025 13:51=
:51","Grid outage, Site went down before Gen start due to poor backup// Gen=
 Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup// Gen Automatically Started","fran=
ck.nkomot@matech-cameroun.com","191","24-06-2025 13:40:01","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005332193","O=
LAMA","","24-06-2025 13:35:58","24-06-2025 13:35:49","24-06-2025 13:37:12",=
"No power issue on site Ubaie =3D54.5V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.5V site on Gen The TX FME Henri (699949693) from Huawei is=
 informed.","christelle.ngonga@matech-cameroun.com","11","24-06-2025 13:35:=
58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005332181","Mfou EPC=
","","24-06-2025 13:34:46","24-06-2025 13:29:05","24-06-2025 14:04:09","Cas=
caded Incident from TTO5498177","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //GEN automatically started","system","268557","2=
4-06-2025 13:34:46","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005332179","M=
fou OCM","IHS_YND_674","24-06-2025 13:33:18","24-06-2025 13:29:05","24-06-2=
025 14:04:09","Grid Outage, Site Down before gen Started due to poor backup=
 //GEN automatically started","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down be=
fore gen Started due to poor backup //GEN automatically started","christell=
e.ngonga@matech-cameroun.com","253","24-06-2025 13:33:18","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0005331948","B=
riqueterie","","24-06-2025 12:57:18","24-06-2025 12:50:58","24-06-2025 13:2=
4:02","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Grid outage, site went down because gen failed to start with alarm undervo=
ltage // He reduced the air conditioning load and gen manually started","ch=
ristelle.ngonga@matech-cameroun.com","1220243","24-06-2025 12:57:18","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0005331933","E=
lobi Mokolo","","24-06-2025 12:55:51","24-06-2025 12:50:58","24-06-2025 13:=
24:02","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage, site went down because gen failed to start with=
 alarm undervoltage // He reduced the air conditioning load and gen manuall=
y started","christelle.ngonga@matech-cameroun.com","1220242","24-06-2025 12=
:55:51","MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0005331930","K=
amajou Building","IHS_YND_088, IHS_YND_085","24-06-2025 12:55:07","24-06-20=
25 12:50:58","24-06-2025 13:28:58","Grid outage, site went down because gen=
 failed to start with alarm undervoltage // He reduced the air conditioning=
 load and gen manually started","Paul BIBOUM","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Under Voltage","Grid outage, site went down because gen =
failed to start with alarm undervoltage // He reduced the air conditioning =
load and gen manually started","christelle.ngonga@matech-cameroun.com","250=
","24-06-2025 12:55:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005331915","Montee-J=
ouvence","","24-06-2025 12:53:43","24-06-2025 12:44:36","24-06-2025 12:50:5=
9","Cascaded Incident from TTO5497865","Hyemafo Gildas","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Site impacted by Nkolzie CTR_672 =
not manage by IHS","system","271205","24-06-2025 12:53:43","MATECH CMR"
"Closed Complete","Warning","CTR_211","IHS_YND_248","NOCINC0005331897","Bit=
eng","","24-06-2025 12:50:50","","","site on battery due to grid outage//ge=
n started","Mba Lazare Herve","Warning","Warning","POWER","Warning - Site o=
n Battery","site on battery due to grid outage//gen started","franck.nkomot=
@matech-cameroun.com","591","24-06-2025 12:50:50","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005331895","S=
imbock OCM","IHS_YND_236","24-06-2025 12:50:47","24-06-2025 12:44:36","24-0=
6-2025 12:50:59","Site impacted by Nkolzie CTR_672 not manage by IHS","Hyem=
afo Gildas","Customer Equipment Failure","Active","Active Equipment Failure=
","Affected by 3rd Party Site","Site impacted by Nkolzie CTR_672 not manage=
 by IHS","christelle.ngonga@matech-cameroun.com","372","24-06-2025 12:50:47=
","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005331824","OBA=
M NGOLA OCM","","24-06-2025 12:39:54","24-06-2025 12:20:42","24-06-2025 15:=
08:35","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down due to PWC overload //Site s=
tabilised","christelle.ngonga@matech-cameroun.com","1153","24-06-2025 12:39=
:54","MATECH CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0005331693","B=
ISCUITERIE","","24-06-2025 12:18:28","24-06-2025 12:12:19","24-06-2025 14:0=
3:42","Grid outage site went down because Gen failed to start due ZTE PWC d=
ysfonction // He reset and gen manually started","Paul BIBOUM","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage sit=
e went down because Gen failed to start due ZTE PWC dysfonction // He reset=
 and gen manually started","christelle.ngonga@matech-cameroun.com","370","2=
4-06-2025 12:18:28","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005331562","Par=
adis Hotel","","24-06-2025 11:52:11","24-06-2025 11:51:00","24-06-2025 14:4=
1:26","Site went down due to Insufficient rectifiers on site //Site stabili=
sed	","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Site went down due to Insufficient rectifiers on site //Site stabil=
ised	","franck.nkomot@matech-cameroun.com","72","24-06-2025 11:52:11","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005331445","E=
ssomba","","24-06-2025 11:31:04","24-06-2025 11:30:57","24-06-2025 11:38:15=
","Site down due to work  done by Willy Kamga 699003823 / Matech RM  (  Con=
figuration of Power Cabinet ) // End of work.","Mba Lazare Herve","Installa=
tion Activity","Passive","Planned Activity","Installation Activity","Site d=
own due to work  done by Willy Kamga 699003823 / Matech RM  (  Configuratio=
n of Power Cabinet ) // End of work.","christelle.ngonga@matech-cameroun.co=
m","9","24-06-2025 11:31:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005331334","EBOM",""=
,"24-06-2025 11:11:43","24-06-2025 11:05:42","24-06-2025 13:58:42","Cascade=
d Incident from TTO5497201","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","(Unstable site)Site went down due to PWC =
overload (15KVA, 360A) //Site stabilized","system","291470","24-06-2025 11:=
11:43","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005331320","A=
hala","IHS_YND_698","24-06-2025 11:09:52","24-06-2025 11:05:42","24-06-2025=
 13:58:42","(Unstable site)Site went down due to PWC overload (15KVA, 360A)=
 //Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","(Unstable site)Site went down due to PWC o=
verload (15KVA, 360A) //Site stabilized","christelle.ngonga@matech-cameroun=
.com","251","24-06-2025 11:09:52","MATECH CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0005331256","B=
ISCUITERIE","","24-06-2025 10:59:41","24-06-2025 10:52:33","24-06-2025 11:4=
9:03"," Grid outage , Site down due to disfonction of  ZTE bay // charge re=
duced and gen manually started","Paul BIBOUM","Equipment Repair","Passive",=
"Rectifier","Rectifier Module"," Grid outage , Site down due to disfonction=
 of  ZTE bay // charge reduced and gen manually started","christelle.ngonga=
@matech-cameroun.com","429","24-06-2025 10:59:41","MATECH CMR"
"Cancelled","Warning","CTR_326","IHS_YND_236","NOCINC0005331222","Montee-Jo=
uvence","","24-06-2025 10:54:56","","","ERROR LOGGED Ticket","Hyemafo Gilda=
s","","","","","","christelle.ngonga@matech-cameroun.com","140","24-06-2025=
 10:54:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005331155","Montee-J=
ouvence","","24-06-2025 10:45:39","24-06-2025 09:40:12","24-06-2025 10:45:4=
8","Cascaded Incident from TTO5496491","Hyemafo Gildas","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Site impacted by Nkolzie  CTR_672=
 not manage by IHS","system","275082","24-06-2025 10:45:39","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005330684","C=
hapelle-Nsimeyong","","24-06-2025 09:45:42","24-06-2025 09:40:12","24-06-20=
25 10:45:48","","MINKA NICOLAS","Cascade Outage","Active","Cascade Active",=
"Cascade Active","Site impacted by Nkolzie  CTR_672 not manage by IHS","chr=
istelle.ngonga@matech-cameroun.com","275083","24-06-2025 09:45:42","MATECH =
CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005330672","A=
ccacia New","IHS_YND_148, IHS_YND_236","24-06-2025 09:43:27","24-06-2025 09=
:40:12","24-06-2025 10:45:48","Site impacted by Nkolzie  CTR_672 not manage=
 by IHS","","Customer Equipment Failure","Active","Active Equipment Failure=
","Affected by 3rd Party Site","Site impacted by Nkolzie  CTR_672 not manag=
e by IHS","christelle.ngonga@matech-cameroun.com","197","24-06-2025 09:43:2=
7","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005330549","Nko=
l-Mbanda","","24-06-2025 09:22:53","24-06-2025 09:16:23","24-06-2025 11:10:=
23","Grid outage.gen ran until fuel shortage//Refueling done","MINKA NICOLA=
S","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran un=
til fuel shortage//Refueling done","franck.nkomot@matech-cameroun.com","391=
","24-06-2025 09:22:53","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005330546","N=
GONA","","24-06-2025 09:21:54","24-06-2025 09:14:45","24-06-2025 09:41:58",=
"No power issue Site is on Grid and Ubaie =3D54.8V The Tx FME Lionel Adjep =
(655184876)from Huawei is informed","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue Site is on Grid and Ubaie =3D54.8V The Tx FME Lionel Adjep (65518487=
6)from Huawei is informed","christelle.ngonga@matech-cameroun.com","430","2=
4-06-2025 09:21:54","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005330529","S=
imbock OCM","","24-06-2025 09:19:35","24-06-2025 09:00:26","24-06-2025 09:1=
0:01"," No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah Mbah (6740=
07438) of Huawei is informed","Hyemafo Gildas","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm"," No power issue =
Ubaie:52.5V site on Gen The Tx Fme Hosiah Mbah (674007438) of Huawei is inf=
ormed","christelle.ngonga@matech-cameroun.com","1151","24-06-2025 09:19:35"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005330520","Mfou EPC=
","","24-06-2025 09:17:30","24-06-2025 09:04:01","24-06-2025 09:25:08","Cas=
caded Incident from TTO5496299","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //GEN automatically started","system","1212188","=
24-06-2025 09:17:30","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005330502","M=
fou OCM","IHS_YND_674","24-06-2025 09:14:11","24-06-2025 09:04:01","24-06-2=
025 09:25:08","Grid Outage, Site Down before gen Started due to poor backup=
 //GEN automatically started","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down be=
fore gen Started due to poor backup //GEN automatically started","christell=
e.ngonga@matech-cameroun.com","611","24-06-2025 09:14:11","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005330386","ESS=
OS OASIS 1111","","24-06-2025 08:53:51","24-06-2025 08:46:29","24-06-2025 1=
3:43:29","(Unstable site) Grid outage,Site went down because Gen overload (=
17kva, 250A)//Site stabilised","Siligap Boris","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","(Unstable site) Grid outage,Site went down b=
ecause Gen overload (17kva, 250A)//Site stabilised","franck.nkomot@matech-c=
ameroun.com","442","24-06-2025 08:53:51","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005330346","B=
arriere","","24-06-2025 08:48:39","24-06-2025 08:10:25","24-06-2025 08:15:3=
3","No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/=
Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
bay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is informed.","chris=
telle.ngonga@matech-cameroun.com","2296","24-06-2025 08:48:39","MATECH CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0005329977","B=
astos Ekoudou","","24-06-2025 07:38:32","24-06-2025 07:29:24","24-06-2025 1=
3:08:55","Grid outage, Gen ran until fuel shortage // Refueling done","Mbou=
a Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, G=
en ran until fuel shortage // Refueling done","franck.nkomot@matech-camerou=
n.com","549","24-06-2025 07:38:32","MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0005329976","c=
hina embassy yde","","24-06-2025 07:37:54","24-06-2025 07:29:24","24-06-202=
5 14:06:24","Grid outage, No space to deploy MGE // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MGE // Grid return","franck.nkomot@matech-cameroun.com","=
4442","24-06-2025 07:37:54","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0005329911","NKO=
ABANG NKOLO 3","","24-06-2025 07:22:36","24-06-2025 07:17:20","24-06-2025 0=
7:48:20","Grid outage,Gen stopped with alarm low oil pressure// He added oi=
l and started the Gen","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - Low Oil Pressure","Grid outage,Gen stopped with alarm low oi=
l pressure// He added oil and started the Gen","loic.noumsi@matech-cameroun=
.com","317","24-06-2025 07:22:36","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005329826","M=
fou OCM","","24-06-2025 06:55:04","24-06-2025 06:51:59","24-06-2025 07:06:3=
3","Grid Outage, Site Down before gen Started due to poor backup //GEN auto=
matically started","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen St=
arted due to poor backup //GEN automatically started","gaelle.njiofack@mate=
ch-cameroun.com","212","24-06-2025 06:55:04","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005329822","N=
kolbong","","24-06-2025 06:53:25","24-06-2025 06:49:13","24-06-2025 10:32:1=
3","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Ge=
n started and stopped due to Gen overload(22kva//350A) // Grid return","gae=
lle.njiofack@matech-cameroun.com","253","24-06-2025 06:53:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005329745","EBOM",""=
,"24-06-2025 06:37:06","24-06-2025 06:22:18","24-06-2025 09:25:18","Cascade=
d Incident from TTO5495415","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","(Unstable site)Site went down due to PWC =
overload (15KVA, 360A) //Site stabilized","system","280613","24-06-2025 06:=
37:06","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005329709","OBA=
M NGOLA OCM","","24-06-2025 06:29:20","24-06-2025 06:24:13","24-06-2025 06:=
42:03","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down due to PWC overload //Site s=
tabilised","loic.noumsi@matech-cameroun.com","308","24-06-2025 06:29:20","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005329695","A=
hala","IHS_YND_698","24-06-2025 06:27:55","24-06-2025 06:22:18","24-06-2025=
 09:25:18","(Unstable site)Site went down due to PWC overload (15KVA, 360A)=
 //Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","(Unstable site)Site went down due to PWC o=
verload (15KVA, 360A) //Site stabilized","gaelle.njiofack@matech-cameroun.c=
om","338","24-06-2025 06:27:55","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005329626","A=
fanoya","","24-06-2025 06:01:26","24-06-2025 05:53:10","24-06-2025 09:04:10=
","Grid outage.gen ran until fuel shortage//Refueling done","Hyemafo Gildas=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unt=
il fuel shortage//Refueling done","gaelle.njiofack@matech-cameroun.com","49=
7","24-06-2025 06:01:26","MATECH CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0005329578","Lab=
oratoire  Meka","","24-06-2025 05:47:56","24-06-2025 05:42:05","25-06-2025 =
10:05:29","Grid Only, No space to deploy MDG//Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space =
to deploy MDG//Grid return","loic.noumsi@matech-cameroun.com","352","24-06-=
2025 05:47:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005329507","Nkolondo=
m","","24-06-2025 05:24:54","24-06-2025 05:18:01","24-06-2025 06:06:53","Ca=
scaded Incident from TTO5495188","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
Grid bad voltage and no RCP on site / He bypassed Grid and started Gen manu=
ally","system","284431","24-06-2025 05:24:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0005329506","Messassi=
 2","","24-06-2025 05:24:54","24-06-2025 05:18:01","24-06-2025 06:06:53","C=
ascaded Incident from TTO5495188","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 Grid bad voltage and no RCP on site / He bypassed Grid and started Gen man=
ually","system","284432","24-06-2025 05:24:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0005329504","Nkozoa",=
"","24-06-2025 05:24:53","24-06-2025 05:18:01","24-06-2025 06:06:53","Casca=
ded Incident from TTO5495188","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to Gri=
d bad voltage and no RCP on site / He bypassed Grid and started Gen manuall=
y","system","284428","24-06-2025 05:24:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0005329502","Olembe-T=
erminus","","24-06-2025 05:24:53","24-06-2025 05:18:01","24-06-2025 06:06:5=
3","Cascaded Incident from TTO5495188","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to Grid bad voltage and no RCP on site / He bypassed Grid and started Ge=
n manually","system","284427","24-06-2025 05:24:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0005329505","Nyom OCM=
","","24-06-2025 05:24:53","24-06-2025 05:18:01","24-06-2025 06:06:53","Cas=
caded Incident from TTO5495188","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to G=
rid bad voltage and no RCP on site / He bypassed Grid and started Gen manua=
lly","system","284429","24-06-2025 05:24:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0005329503","Messassi=
","","24-06-2025 05:24:53","24-06-2025 05:18:01","24-06-2025 06:06:53","Cas=
caded Incident from TTO5495188","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to G=
rid bad voltage and no RCP on site / He bypassed Grid and started Gen manua=
lly","system","284434","24-06-2025 05:24:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0005329501","NKOLMEKO=
NG YDE","","24-06-2025 05:24:52","24-06-2025 05:18:01","24-06-2025 06:06:53=
","Cascaded Incident from TTO5495188","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down du=
e to Grid bad voltage and no RCP on site / He bypassed Grid and started Gen=
 manually","system","284433","24-06-2025 05:24:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0005329500","Ekombiti=
e","","24-06-2025 05:24:52","24-06-2025 05:18:01","24-06-2025 06:06:53","Ca=
scaded Incident from TTO5495188","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
Grid bad voltage and no RCP on site / He bypassed Grid and started Gen manu=
ally","system","284430","24-06-2025 05:24:52","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005329495","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_280, IHS_YND_304","24-06-2025 05:19:15","24-06-2025 05:1=
8:01","24-06-2025 06:06:53","Grid outage, site went down due to Grid bad vo=
ltage and no RCP on site / He bypassed Grid and started Gen manually","Fabr=
ice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid outage, site went down due to Grid bad voltage and no RCP =
on site / He bypassed Grid and started Gen manually","gaelle.njiofack@matec=
h-cameroun.com","76","24-06-2025 05:19:15","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005329376","OBA=
M NGOLA OCM","","24-06-2025 04:42:51","24-06-2025 04:36:43","24-06-2025 04:=
54:09","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down due to PWC overload //Site s=
tabilised","loic.noumsi@matech-cameroun.com","369","24-06-2025 04:42:51","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005329372","A=
hala","","24-06-2025 04:41:37","24-06-2025 04:36:23","24-06-2025 04:54:38",=
"(Unstable site)Site went down due to PWC overload (15KVA, 360A) //Site sta=
bilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","(Unstable site)Site went down due to PWC overload (15=
KVA, 360A) //Site stabilized","loic.noumsi@matech-cameroun.com","314","24-0=
6-2025 04:41:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005329361","MEHANDAN=
","","24-06-2025 04:39:53","24-06-2025 04:32:58","24-06-2025 04:40:54","Cas=
caded Incident from TTO5495044","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","1221306","24-06-2025 04:39:53","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005329360","O=
dza II OCM","IHS_YND_528","24-06-2025 04:39:08","24-06-2025 04:32:58","24-0=
6-2025 04:40:54","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","loic.noumsi@matech-cameroun.com","373","24-06-2025=
 04:39:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005328982","Carrefou=
r Ayissi Ele","","24-06-2025 02:04:34","24-06-2025 01:55:00","24-06-2025 02=
:47:45","Cascaded Incident from TTO5494623","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n because Gen start and stopped with ""High temp"" alarm // he added water =
in the radiator and manually started the Gen manually","system","1216350","=
24-06-2025 02:04:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005328983","Nkol-Meb=
anga","","24-06-2025 02:04:34","24-06-2025 01:55:00","24-06-2025 02:47:45",=
"Cascaded Incident from TTO5494623","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen start and stopped with ""High temp"" alarm // he added water in the r=
adiator and manually started the Gen manually","system","1216350","24-06-20=
25 02:04:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005328979","SAA 2","=
","24-06-2025 02:03:40","24-06-2025 01:55:00","24-06-2025 02:47:31","Cascad=
ed Incident from TTO5494622","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because Gen s=
tart and stopped with ""High temp"" alarm // he added water in the radiator=
 and manually started the Gen manually","system","1216350","24-06-2025 02:0=
3:40","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005328974","S=
aa","IHS_YND_810, IHS_YND_809, IHS_YND_401, IHS_YND_404","24-06-2025 02:02:=
11","24-06-2025 01:55:00","24-06-2025 02:47:45","Grid outage, Site went dow=
n because Gen start and stopped with ""High temp"" alarm // he added water =
in the radiator and manually started the Gen manually","Parker Tchoup","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Leve=
l Issue","Grid outage, Site went down because Gen start and stopped with ""=
High temp"" alarm // he added water in the radiator and manually started th=
e Gen manually","gaelle.njiofack@matech-cameroun.com","432","24-06-2025 02:=
02:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005328911","EBOM",""=
,"24-06-2025 01:40:52","24-06-2025 01:31:37","24-06-2025 01:50:25","Cascade=
d Incident from TTO5494549","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","(Unstable site)Site went down due to PWC =
overload (15KVA, 360A) //Site stabilized","system","297877","24-06-2025 01:=
40:52","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005328908","A=
hala","IHS_YND_698","24-06-2025 01:39:45","24-06-2025 01:31:37","24-06-2025=
 01:50:25","(Unstable site)Site went down due to PWC overload (15KVA, 360A)=
 //Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","(Unstable site)Site went down due to PWC o=
verload (15KVA, 360A) //Site stabilized","loic.noumsi@matech-cameroun.com",=
"488","24-06-2025 01:39:45","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005328899","OBA=
M NGOLA OCM","","24-06-2025 01:37:28","24-06-2025 01:31:13","24-06-2025 01:=
49:13","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down due to PWC overload //Site s=
tabilised","loic.noumsi@matech-cameroun.com","376","24-06-2025 01:37:28","M=
ATECH CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0005328526","Lab=
oratoire  Meka","","24-06-2025 00:17:13","24-06-2025 00:11:00","24-06-2025 =
05:37:39","Grid Only, No space to deploy MDGE // Grid returned","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No s=
pace to deploy MDGE // Grid returned","gaelle.njiofack@matech-cameroun.com"=
,"374","24-06-2025 00:17:13","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005328353","S=
aa","","23-06-2025 23:21:05","23-06-2025 23:15:24","23-06-2025 23:30:32","	=
No power issue on site ,site on Gen with Ubaie =3D53.8V The Tx Technician f=
rom Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	=
No power issue on site ,site on Gen with Ubaie =3D53.8V The Tx Technician f=
rom Huawei Gr=E9goire//654547479 is informed","gaelle.njiofack@matech-camer=
oun.com","343","23-06-2025 23:21:05","MATECH CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0005328297","N=
gousso-II","","23-06-2025 23:00:18","23-06-2025 20:03:06","24-06-2025 07:28=
:06","Access issuedue to landlord Site went down due to disjunction of CB(1=
25A) at PWC//CB rearmed ","MFOUAGUEGUE MATHIEU","Access Denial","Lease Or L=
egal","Landlord Related Issues","Access Issue - Land Lord","Access issuedue=
 to landlord Site went down due to disjunction of CB(125A) at PWC//CB rearm=
ed ","gaelle.njiofack@matech-cameroun.com","10633","23-06-2025 23:00:18","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005328214","EBOM",""=
,"23-06-2025 22:36:19","23-06-2025 21:41:14","24-06-2025 00:43:10","Cascade=
d Incident from TTO5493492","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","(Unstable site)Site went down due to PWC =
overload (15KVA, 360A) //Site stabilized","system","311477","23-06-2025 22:=
36:19","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005328204","S=
imbock OCM","","23-06-2025 22:34:27","23-06-2025 22:28:19","23-06-2025 22:4=
4:06","Active // No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah M=
bah (674007438) of Huawei is informed","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah Mbah (674007438=
) of Huawei is informed","edwige.kapawo@matech-cameroun.com","369","23-06-2=
025 22:34:27","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005328189","Fou=
da Quarter","","23-06-2025 22:31:35","23-06-2025 22:17:26","24-06-2025 00:0=
3:40","Grid outage, site went down because gen failed to start due to grid =
bad voltage and no RCP// He bypassed Grid and started Gen manually","Delor =
Telezing","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid outage, site went down because gen failed to start due to gri=
d bad voltage and no RCP// He bypassed Grid and started Gen manually","gera=
rd.tchangoue@matech-cameroun.com","850","23-06-2025 22:31:35","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005328027","ESS=
OS OASIS 1111","","23-06-2025 21:55:39","23-06-2025 21:50:34","24-06-2025 0=
0:10:35","(Unstable site) Grid outage,Site went down because Gen overload (=
17kva, 250A)//Site stabilised","Siligap Boris","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","(Unstable site) Grid outage,Site went down b=
ecause Gen overload (17kva, 250A)//Site stabilised","cedric.tiani@matech-ca=
meroun.com","307","23-06-2025 21:55:39","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005327968","Mok=
olo Yaounde","","23-06-2025 21:48:09","23-06-2025 21:43:04","23-06-2025 22:=
52:56","Active // No power issue Ubay: 54.7V site on grid. The Tx FME Eloun=
dou Bertrand (693212405) from Huawei is informed","","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // =
No power issue Ubay: 54.7V site on grid. The Tx FME Eloundou Bertrand (6932=
12405) from Huawei is informed","cedric.tiani@matech-cameroun.com","307","2=
3-06-2025 21:48:09","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005327958","A=
hala","IHS_YND_698","23-06-2025 21:46:22","23-06-2025 21:41:14","24-06-2025=
 00:43:10","(Unstable site)Site went down due to PWC overload (15KVA, 360A)=
 //Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","(Unstable site)Site went down due to PWC o=
verload (15KVA, 360A) //Site stabilized","cedric.tiani@matech-cameroun.com"=
,"309","23-06-2025 21:46:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005327952","Nsam esc=
ale LP","","23-06-2025 21:45:22","23-06-2025 21:14:39","23-06-2025 23:04:41=
","Cascaded Incident from TTO5493358","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Site went down due to disjunction of Rectifie=
rs CB (50A) in the PWC // He rearmed it, site on Grid","system","313047","2=
3-06-2025 21:45:22","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005327841","Nsa=
m Sofavinc","IHS_YND_732","23-06-2025 21:24:53","23-06-2025 21:14:39","23-0=
6-2025 23:04:41","Site went down due to disjunction of Rectifiers CB (50A) =
in the PWC // He rearmed it, site on Grid","MINKA NICOLAS","Equipment Repai=
r","Passive","Rectifier","Rectifier - Circuit Breaker","Site went down due =
to disjunction of Rectifiers CB (50A) in the PWC // He rearmed it, site on =
Grid","cedric.tiani@matech-cameroun.com","615","23-06-2025 21:24:53","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005327693","E=
bogo","","23-06-2025 20:57:23","23-06-2025 20:50:04","23-06-2025 22:00:59",=
"Grid outage, site went down because Gen failed to start due to grid bad vo=
ltage // He bypassed the grid and started Gen manually","Siligap Boris","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 outage, site went down because Gen failed to start due to grid bad voltage=
 // He bypassed the grid and started Gen manually","cedric.tiani@matech-cam=
eroun.com","440","23-06-2025 20:57:23","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005327602","NYO=
M FACE MAETUR","","23-06-2025 20:39:03","22-06-2025 08:07:18","22-06-2025 0=
8:38:08","Backtracking(Grid outage, Site went down because Gen failed to st=
art due to Grid bad voltage //Grid stabilised)","Fabrice Pouakam","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Backtracki=
ng(Grid outage, Site went down because Gen failed to start due to Grid bad =
voltage //Grid stabilised)","cedric.tiani@matech-cameroun.com","131505","23=
-06-2025 20:39:03","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005327363","C=
omplexe-BEAC","","23-06-2025 20:09:13","22-06-2025 11:58:12","22-06-2025 12=
:03:24","Bactracking Grid outage, Site went down before Gen start due to Po=
or battery backup // Grid return","Albran Byorel","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to Poor battery backup // Grid return","cedric.tia=
ni@matech-cameroun.com","115861","23-06-2025 20:09:13","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005327339","B=
arriere","","23-06-2025 20:04:41","22-06-2025 12:33:17","22-06-2025 12:38:4=
8","Bactracking Active// No power issue on site Ubay: 52.4V site on Gen TX =
Fme SAMBA (654266058/Huawei) is informed.	","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ba=
ctracking Active// No power issue on site Ubay: 52.4V site on Gen TX Fme SA=
MBA (654266058/Huawei) is informed.	","cedric.tiani@matech-cameroun.com","1=
13486","23-06-2025 20:04:41","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005327120","C=
arrefourt Nkomo","","23-06-2025 19:49:26","23-06-2025 19:41:19","23-06-2025=
 20:09:24","Grid outage, Site went down because Gen failed to start due to =
Grid bad voltage //He bypassed Grid and started Gen manualy","Mba Lazare He=
rve","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid outage, Site went down because Gen failed to start due to Grid bad=
 voltage //He bypassed Grid and started Gen manualy","cedric.tiani@matech-c=
ameroun.com","488","23-06-2025 19:49:26","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005326982","ESS=
OS OASIS 1111","","23-06-2025 19:33:49","23-06-2025 19:28:45","23-06-2025 2=
1:28:47","(Unstable site) Grid outage,Site went down because Gen overload (=
17kva, 250A)//Site stabilised","Siligap Boris","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","(Unstable site) Grid outage,Site went down b=
ecause Gen overload (17kva, 250A)//Site stabilised","cedric.tiani@matech-ca=
meroun.com","305","23-06-2025 19:33:49","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005326972","OBA=
M NGOLA OCM","","23-06-2025 19:32:46","23-06-2025 19:27:39","24-06-2025 00:=
47:41","(Unstable site) Site went down due to PWC overload //Site stabilise=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down due to PWC overload //Site s=
tabilised","cedric.tiani@matech-cameroun.com","308","23-06-2025 19:32:46","=
MATECH CMR"
"Closed Complete","Site Down","T0292","IHS_YND_231","NOCINC0005326911","Nko=
lso","","23-06-2025 19:19:28","23-06-2025 19:13:43","23-06-2025 20:18:04","=
Active//No power issue on site ,site on Grid with Ubaie=3D48.9 V The Tx FME=
 Mouahamadou (691144435) of Huawei is informed ","TIENTCHEU NZETCHIEU GAEL"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue on site ,site on Grid with Ubaie=3D48.9=
 V The Tx FME Mouahamadou (691144435) of Huawei is informed ","cedric.tiani=
@matech-cameroun.com","345","23-06-2025 19:19:28","MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005326904","Mvo=
g Betsi Hospital","","23-06-2025 19:17:29","23-06-2025 19:11:21","23-06-202=
5 19:17:17","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","cedric.tiani@matech-cameroun.com"=
,"369","23-06-2025 19:17:29","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0005326698","B=
iteng-Maetur","","23-06-2025 18:33:03","23-06-2025 18:20:55","23-06-2025 18=
:24:09","Our RM Willy kamga MATECH was on site (configuration of PWC ZTE)//=
End of work","Mba Lazare Herve","Installation Activity","Passive","Planned =
Activity","Installation Activity","Our RM Willy kamga MATECH was on site (c=
onfiguration of PWC ZTE)//End of work","cedric.tiani@matech-cameroun.com","=
730","23-06-2025 18:33:03","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005326551","S=
imbock OCM","","23-06-2025 18:02:32","23-06-2025 17:56:45","23-06-2025 18:1=
0:26","Active // No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah M=
bah (674007438) of Huawei is informed","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah Mbah (674007438=
) of Huawei is informed","cedric.tiani@matech-cameroun.com","348","23-06-20=
25 18:02:32","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005326489","N=
GONA","","23-06-2025 17:51:15","23-06-2025 17:46:09","23-06-2025 18:58:41",=
"Site went down because Gen started and stopped with ""low oil pressure"" a=
larm// He added oil and started Gen manualy","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down beca=
use Gen started and stopped with ""low oil pressure"" alarm// He added oil =
and started Gen manualy","cedric.tiani@matech-cameroun.com","307","23-06-20=
25 17:51:15","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005326375","ELO=
UMDEM CARRIERE","","23-06-2025 17:26:32","23-06-2025 17:13:14","23-06-2025 =
17:20:05","No power issue , Site on Grid and Ubaie=3D54.8V The Tx Fme Fulbe=
rt //654266068 from Huawei is informed","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue , Site on Grid and Ubaie=3D54.8V The Tx Fme Fulbert //654266068 from =
Huawei is informed","cedric.tiani@matech-cameroun.com","799","23-06-2025 17=
:26:32","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005326309","Eko=
umdoum OCM","","23-06-2025 17:12:16","23-06-2025 17:06:04","23-06-2025 18:0=
8:15","Grid outage,gen failed to start due to ATS disfunction//He reset it =
 and site on GEN","Albran Byorel","Equipment Repair","Passive","Control Pan=
el","ATS-AMF Issue","Grid outage,gen failed to start due to ATS disfunction=
//He reset it  and site on GEN","cedric.tiani@matech-cameroun.com","373","2=
3-06-2025 17:12:16","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005326284","Man=
guiers Dispensaire","","23-06-2025 17:06:35","23-06-2025 17:01:27","23-06-2=
025 17:20:26","Active // No power issue site on grid with U=3D54,8 V Tx Fme=
 Armand Ngestsa (691144412) of huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active // No power issue site on grid with U=3D54,8 V Tx Fme Armand N=
gestsa (691144412) of huawei is informed","cedric.tiani@matech-cameroun.com=
","309","23-06-2025 17:06:35","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005326244","Eto=
ug ebe Meweulo","","23-06-2025 16:58:08","23-06-2025 16:52:00","23-06-2025 =
17:30:37","SS HIS Francois was on site working//End of work","Hyemafo Gilda=
s","Installation Activity","Passive","Planned Activity","Installation Activ=
ity","SS HIS Francois was on site working//End of work","cedric.tiani@matec=
h-cameroun.com","369","23-06-2025 16:58:08","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005326020","ODZ=
A MINKAN EDIBI ASSI","","23-06-2025 16:26:57","23-06-2025 16:20:42","23-06-=
2025 18:51:58","Site went because Gen failed due to Gen overload(12.5 kva /=
/180A )SS HIS Francois is informed//He reduiced the load and site on Gen","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","S=
ite went because Gen failed due to Gen overload(12.5 kva //180A )SS HIS Fra=
ncois is informed//He reduiced the load and site on Gen","cedric.tiani@mate=
ch-cameroun.com","376","23-06-2025 16:26:57","MATECH CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0005325942","N=
guila","","23-06-2025 16:13:43","17-06-2025 14:14:15","17-06-2025 15:00:44"=
,"backtracking  No Power issue, site on battery Ubay =3D 48.2V Hybrid Site,=
 Tx Fme Gregoire (654547479) from Huawei is informed and confirmed","Parker=
 Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","backtracking  No Power issue, site on battery Ubay =3D=
 48.2V Hybrid Site, Tx Fme Gregoire (654547479) from Huawei is informed and=
 confirmed","mouliom.anselme@matech-cameroun.com","525569","23-06-2025 16:1=
3:43","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005325902","ESS=
OS OASIS 1111","","23-06-2025 16:06:20","23-06-2025 15:57:04","23-06-2025 1=
7:59:27","(Unstable site)Grid outage, Site went down because Gen overload (=
17kva, 250A)//site stabilised","Siligap Boris","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","(Unstable site)Grid outage, Site went down b=
ecause Gen overload (17kva, 250A)//site stabilised","cedric.tiani@matech-ca=
meroun.com","557","23-06-2025 16:06:20","MATECH CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0005325780","Aha=
la","","23-06-2025 15:48:37","23-06-2025 15:42:23","23-06-2025 16:23:51","S=
ite went down due to 01/08 rectifiers dysfunction on site//He reset it and =
site on Grid","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down due to 01/08 rectifiers dysfunction on site=
//He reset it and site on Grid","cedric.tiani@matech-cameroun.com","375","2=
3-06-2025 15:48:37","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005325756","A=
hala","","23-06-2025 15:44:51","23-06-2025 15:39:44","23-06-2025 19:03:49",=
"(Unstable site)Site went down due to PWC overload (15KVA, 360A) //Site sta=
bilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","(Unstable site)Site went down due to PWC overload (15=
KVA, 360A) //Site stabilized","cedric.tiani@matech-cameroun.com","308","23-=
06-2025 15:44:51","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005325469","Nko=
lnda","","23-06-2025 14:50:28","23-06-2025 14:46:21","23-06-2025 15:14:57",=
"Grid outage, site went down because gen failed to start with alarm undervo=
ltage // He reset gen card and gen manually started","Albran Byorel","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site=
 went down because gen failed to start with alarm undervoltage // He reset =
gen card and gen manually started","cedric.tiani@matech-cameroun.com","249"=
,"23-06-2025 14:50:28","MATECH CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0005325414","RUE=
 FOE","","23-06-2025 14:41:17","23-06-2025 14:35:10","23-06-2025 15:07:12",=
"Grid outage, site went down because Gen stopped with 'Over-Voltage' alarm =
// He reset the Gen card and Gen manually started","Delor Telezing","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site =
went down because Gen stopped with 'Over-Voltage' alarm // He reset the Gen=
 card and Gen manually started","cedric.tiani@matech-cameroun.com","368","2=
3-06-2025 14:41:17","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005325403","M=
endong","","23-06-2025 14:39:08","23-06-2025 14:36:59","23-06-2025 14:40:58=
","Site went Down because Achile Fotso (694271069/ SFM) was on site for swa=
p PWC //End of work","Hyemafo Gildas","Installation Activity","Passive","Pl=
anned Activity","Installation Activity","Site went Down because Achile Fots=
o (694271069/ SFM) was on site for swap PWC //End of work","cedric.tiani@ma=
tech-cameroun.com","130","23-06-2025 14:39:08","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005325395","Par=
adis Hotel","","23-06-2025 14:37:24","23-06-2025 14:35:14","23-06-2025 14:3=
7:30","site went down due to cable which powered PWC has been stolen //We f=
ixed the cable and site on battery( replacement cable ongoing)","Siligap Bo=
ris","Site Asset Theft","Theft","Theft","AC Cable Stolen","site went down d=
ue to cable which powered PWC has been stolen //We fixed the cable and site=
 on battery( replacement cable ongoing)","cedric.tiani@matech-cameroun.com"=
,"131","23-06-2025 14:37:24","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005325364","MEF=
OU ASSI","","23-06-2025 14:30:14","23-06-2025 14:28:06","23-06-2025 14:34:1=
3","Site went down due to work done by Laurent Kenfack (656177673) from TEL=
EINFRA(swapp equipement of TX)//End of work","Fanda Brice","Installation Ac=
tivity","Passive","Planned Activity","Installation Activity","Site went dow=
n due to work done by Laurent Kenfack (656177673) from TELEINFRA(swapp equi=
pement of TX)//End of work","gerard.tchangoue@matech-cameroun.com","130","2=
3-06-2025 14:30:14","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005325248","Nko=
mo stade","","23-06-2025 14:12:17","23-06-2025 14:06:38","23-06-2025 14:38:=
20","Grid outage.gen failed to start due to alarm high temp//We add water a=
nd gen manually started","Mba Lazare Herve","Equipment Repair","Passive","A=
CDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.gen f=
ailed to start due to alarm high temp//We add water and gen manually starte=
d","gerard.tchangoue@matech-cameroun.com","340","23-06-2025 14:12:17","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005325243","ELOUMDEM=
 CARRIERE 2","","23-06-2025 14:11:29","23-06-2025 14:02:17","23-06-2025 14:=
08:11","Cascaded Incident from TTO5490471","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work do=
ne by Laurent Kenfack(656177673) of TELEINFRA(swapp of equipements tx of Ca=
mtel)//End of work","system","332397","23-06-2025 14:11:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005325242","Eto koss=
 Yde","","23-06-2025 14:11:28","23-06-2025 14:02:17","23-06-2025 14:08:11",=
"Cascaded Incident from TTO5490471","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work done by L=
aurent Kenfack(656177673) of TELEINFRA(swapp of equipements tx of Camtel)//=
End of work","system","332398","23-06-2025 14:11:28","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005325224","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","23-06-2025 14:10:02","23-06-2025 14:02=
:17","23-06-2025 14:08:11","Site went down due to work done by Laurent Kenf=
ack(656177673) of TELEINFRA(swapp of equipements tx of Camtel)//End of work=
","Fanda Brice","Installation Activity","Passive","Planned Activity","Insta=
llation Activity","Site went down due to work done by Laurent Kenfack(65617=
7673) of TELEINFRA(swapp of equipements tx of Camtel)//End of work","gerard=
.tchangoue@matech-cameroun.com","467","23-06-2025 14:10:02","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005325047","ODZ=
A MINKAN EDIBI ASSI","","23-06-2025 13:54:27","23-06-2025 13:52:57","23-06-=
2025 15:42:58","Site went because Gen failed due to Gen overload(12.5 kva /=
/180A )SS HIS Francois is informed//He reduiced the load and manually start=
ed the GEN","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Site went because Gen failed due to Gen overload(12.5 kva //180=
A )SS HIS Francois is informed//He reduiced the load and manually started t=
he GEN","gerard.tchangoue@matech-cameroun.com","91","23-06-2025 13:54:27","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005324976","Mfou EPC=
","","23-06-2025 13:44:01","23-06-2025 13:39:40","23-06-2025 14:09:11","Gri=
d Outage, Site Down before gen Started due to poor backup //GEN automatical=
ly started","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid Outage, Site Down before gen Started due to poor b=
ackup //GEN automatically started","system","333705","23-06-2025 13:44:01",=
"MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005324969","Aha=
la Echangeur","","23-06-2025 13:42:50","23-06-2025 13:35:38","23-06-2025 14=
:12:18","Grid outage.site went down due to bad grid voltage//We bypass grid=
 and gen manually started ","MINKA NICOLAS","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid outage.site went down due t=
o bad grid voltage//We bypass grid and gen manually started ","ludivine.nga=
maleu@ihstowers.com","433","23-06-2025 13:42:50","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005324966","M=
fou OCM","IHS_YND_674","23-06-2025 13:41:50","23-06-2025 13:39:40","23-06-2=
025 14:09:11","Grid Outage, Site Down before gen Started due to poor backup=
 //GEN automatically started","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site Down be=
fore gen Started due to poor backup //GEN automatically started","edwige.ka=
pawo@matech-cameroun.com","131","23-06-2025 13:41:50","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005324924","Nko=
ulou Carriere carrefourt","","23-06-2025 13:32:52","23-06-2025 13:23:24","2=
3-06-2025 13:42:27","Site impacted by Nkolangaa","Mba Lazare Herve","Cascad=
e Outage","Active","Cascade Active","Cascade Active","noticed that heavy ra=
in on the area . No power issue on site U=3D52.7V site on Grid Lionel Tchat=
chou (694693436) from Huawei is informed","gerard.tchangoue@matech-cameroun=
.com","334678","23-06-2025 13:32:52","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005324912","Nko=
langaa","IHS_YND_794, IHS_YND_290","23-06-2025 13:30:49","23-06-2025 13:23:=
24","23-06-2025 13:42:27","noticed that heavy rain on the area . No power i=
ssue on site U=3D52.7V site on Grid Lionel Tchatchou (694693436) from Huawe=
i is informed","Mba Lazare Herve","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","noticed that heavy rain on th=
e area . No power issue on site U=3D52.7V site on Grid Lionel Tchatchou (69=
4693436) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","4=
46","23-06-2025 13:30:49","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0005324899","Aba=
ng","","23-06-2025 13:28:33","23-06-2025 13:23:24","23-06-2025 13:42:27","S=
ite impacted by Nkolangaa","Mba Lazare Herve","Cascade Outage","Active","Ca=
scade Active","Cascade Active","noticed that heavy rain on the area . No po=
wer issue on site U=3D52.7V site on Grid Lionel Tchatchou (694693436) from =
Huawei is informed","gerard.tchangoue@matech-cameroun.com","334678","23-06-=
2025 13:28:33","MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0005324874","c=
hina embassy yde","","23-06-2025 13:26:18","23-06-2025 13:20:01","23-06-202=
5 14:36:24","Grid outage, No space to deploy MGE // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","=
378","23-06-2025 13:26:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0005324872","Awae Esc=
alier","","23-06-2025 13:25:40","23-06-2025 13:17:12","23-06-2025 13:26:38"=
,"Cascaded Incident from TTO5490084","Albran Byorel","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","
Active // No power issue on site ,site on Grid with Ubaie=3D55.3 V The TX H=
enry/699949693// From Huawei is Informed. noticed that heavy rain on the ar=
ea
","system","1218643","23-06-2025 13:25:40","MATECH CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0005324868","A=
wae-Yde","IHS_YND_171","23-06-2025 13:24:24","23-06-2025 13:17:12","23-06-2=
025 13:26:38","Active // No power issue on site ,site on Grid with Ubaie=3D=
55.3 V The TX Henry/699949693// From Huawei is Informed. noticed that heavy=
 rain on the area","Albran Byorel","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","
Active // No power issue on site ,site on Grid with Ubaie=3D55.3 V The TX H=
enry/699949693// From Huawei is Informed. noticed that heavy rain on the ar=
ea
","edwige.kapawo@matech-cameroun.com","433","23-06-2025 13:24:24","MATECH C=
MR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005324855","Par=
adis Hotel","","23-06-2025 13:22:04","23-06-2025 13:18:40","23-06-2025 14:0=
6:18","site went down due to cable which powered PWC has been stolen //We f=
ixed the cable and site on battery( replacement cable ongoing)","Siligap Bo=
ris","Site Asset Theft","Theft","Theft","AC Cable Stolen","site went down d=
ue to cable which powered PWC has been stolen //We fixed the cable and site=
 on battery( replacement cable ongoing)","gerard.tchangoue@matech-cameroun.=
com","205","23-06-2025 13:22:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0005324780","Nkomkana=
 2","","23-06-2025 13:05:26","23-06-2025 12:57:27","23-06-2025 14:15:02","C=
ascaded Incident from TTO5489981 - Cascade Removed From TTO5489981","Mboua =
Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Gr=
id Only, No space to deploy MDGE// Grid returned","system","336214","23-06-=
2025 13:05:26","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005324776","T=
singa","","23-06-2025 13:04:28","23-06-2025 12:57:27","23-06-2025 14:15:02"=
,"","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid Only, No space to deploy MDGE// Grid returned","edwige.kapawo=
@matech-cameroun.com","336212","23-06-2025 13:04:28","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0005324768","N=
komkana","IHS_YND_220, IHS_YND_138, IHS_YND_126, IHS_YND_563, IHS_YND_127",=
"23-06-2025 13:02:49","23-06-2025 12:57:27","23-06-2025 14:15:41","Grid Onl=
y, No space to deploy MDGE// Grid returned","","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue","Grid Only, No space to deploy MDGE/=
/ Grid returned","edwige.kapawo@matech-cameroun.com","324","23-06-2025 13:0=
2:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005324752","Golf Qua=
ter","","23-06-2025 13:00:42","23-06-2025 12:57:27","23-06-2025 14:15:02","=
Cascaded Incident from TTO5489949 - Cascade Removed From TTO5489949","Mboua=
 Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid Only, No space to deploy MDGE// Grid returned","system","336215","23-06=
-2025 13:00:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005324753","Bastos B=
ethesda","","23-06-2025 13:00:42","23-06-2025 12:57:27","23-06-2025 14:15:0=
2","Cascaded Incident from TTO5489949 - Cascade Removed From TTO5489949","M=
boua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","Grid Only, No space to deploy MDGE// Grid returned","system","336213","2=
3-06-2025 13:00:42","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005324749","B=
astos-Nylon","","23-06-2025 12:59:48","23-06-2025 12:57:27","23-06-2025 14:=
15:02","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Only, No space to deploy MDGE// Grid returned","edwige.=
kapawo@matech-cameroun.com","336214","23-06-2025 12:59:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0005324726","Mbankolo=
 petit paris","","23-06-2025 12:55:34","23-06-2025 12:46:26","23-06-2025 12=
:59:31","Cascaded Incident from TTO5489918","Mboua Thierry","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue on site ,site =
on Gen with Ubaie=3D 54 V THE fme Tx Mouamadou /691 144 435/ Huawei is info=
rmed","system","336870","23-06-2025 12:55:34","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0005324722","AFE=
ME NORD","IHS_YND_808","23-06-2025 12:54:45","23-06-2025 12:46:26","23-06-2=
025 12:59:31","No power issue on site ,site on Gen with Ubaie=3D 54 V THE f=
me Tx Mouamadou /691 144 435/ Huawei is informed","TIENTCHEU NZETCHIEU GAEL=
","Customer Equipment Failure","Active","Active Equipment Failure","Affecte=
d by 3rd Party Site","No power issue on site ,site on Gen with Ubaie=3D 54 =
V THE fme Tx Mouamadou /691 144 435/ Huawei is informed","gerard.tchangoue@=
matech-cameroun.com","500","23-06-2025 12:54:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0005324716","Leboudi"=
,"","23-06-2025 12:54:00","23-06-2025 12:49:00","23-06-2025 12:58:30","Casc=
aded Incident from TTO5489891","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","Active//No power issue, Site on=
 Grid Ubaie=3D 54.8V The TX Mouhamadou (6144435) from Huawei is informed.",=
"system","336713","23-06-2025 12:54:00","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0005324695","N=
kolafeme","IHS_YND_309","23-06-2025 12:52:14","23-06-2025 12:49:00","23-06-=
2025 12:58:30","Active//No power issue, Site on Grid Ubaie=3D 54.8V The TX =
Mouhamadou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue, Site on Grid Ubaie=3D 54.8V The TX Mouha=
madou (6144435) from Huawei is informed.","edwige.kapawo@matech-cameroun.co=
m","195","23-06-2025 12:52:14","MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0005324665","Dag=
obert","","23-06-2025 12:46:31","23-06-2025 12:43:14","23-06-2025 12:53:20"=
,"Active: No power issue, site is on Grid with Ubaie=3D54,6V, FME TX Mohama=
dou//691144435 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active: No power issue, site is on Grid with Ubaie=3D54,6V, FME TX Moha=
madou//691144435 from Huawei is informed","gerard.tchangoue@matech-cameroun=
.com","198","23-06-2025 12:46:31","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0005324622","S=
AA 2","","23-06-2025 12:43:47","21-06-2025 01:39:14","21-06-2025 01:54:14",=
"Bactracking. No power issue on site ,site on Gen with Ubaie =3D53.6V. Tx T=
echnician from Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Bactracking. No power issue on site ,site on Gen with Ubaie =3D53=
.6V. Tx Technician from Huawei Gr=E9goire//654547479 is informed","gerard.t=
changoue@matech-cameroun.com","212674","23-06-2025 12:43:47","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005324614","O=
dza II OCM","","23-06-2025 12:42:08","20-06-2025 22:25:57","20-06-2025 22:3=
8:57","Bactracking. Grid fluctuations, site went down because gen failed to=
 start due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","Bactrack=
ing. Grid fluctuations, site went down because gen failed to start due to P=
WC ZTE malfunction // Grid stabilized","gerard.tchangoue@matech-cameroun.co=
m","224171","23-06-2025 12:42:08","MATECH CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0005324584","M=
ontee-Jouvence","","23-06-2025 12:37:38","20-06-2025 22:07:39","20-06-2025 =
22:24:39","Backtracking. ACTIVE//No power issue u=3D53.3V site on GRID,The =
Tx FME Hosiah//699699694 is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Backtrac=
king. ACTIVE//No power issue u=3D53.3V site on GRID,The Tx FME Hosiah//6996=
99694 is informed","gerard.tchangoue@matech-cameroun.com","224999","23-06-2=
025 12:37:38","MATECH CMR"
"Closed Complete","Site Down","T0920","IHS_YND_416","NOCINC0005324576","Ngw=
opi Boga","","23-06-2025 12:36:12","20-06-2025 23:35:32","20-06-2025 23:38:=
25","Grid outage , site went down before Gen started due to poor battery ba=
ckup // Grid return Power","Kemeni Franklin","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage , site went down =
before Gen started due to poor battery backup // Grid return Power","edwige=
.kapawo@matech-cameroun.com","219641","23-06-2025 12:36:12","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005324553","Mai=
son komkana New","","23-06-2025 12:32:44","23-06-2025 12:28:25","23-06-2025=
 12:50:25","Grid outage,gen failed to start due to no battery GE //Gen manu=
ally started with external battery","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Generator Battery","Grid outage,gen failed to star=
t due to no battery GE //Gen manually started with external battery","gerar=
d.tchangoue@matech-cameroun.com","260","23-06-2025 12:32:44","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005324534","Eto=
ug ebe biscuiterie","","23-06-2025 12:29:57","20-06-2025 22:12:25","21-06-2=
025 01:41:43","Backtraking   Grid fluctuations, site went down due to Grid =
bad voltage and no rcp on site // Grid Stabilised","Hyemafo Gildas","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Backtrak=
ing   Grid fluctuations, site went down due to Grid bad voltage and no rcp =
on site // Grid Stabilised","edwige.kapawo@matech-cameroun.com","224253","2=
3-06-2025 12:29:57","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005324532","B=
arriere","","23-06-2025 12:29:29","20-06-2025 22:17:57","20-06-2025 22:41:5=
7","Bactracking. Active// No power issue on site Ubay: 54.6V site on Gen TX=
 Fme SAMBA (654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6542660=
58/Huawei) is informed.","gerard.tchangoue@matech-cameroun.com","223894","2=
3-06-2025 12:29:29","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005324506","E=
SSOS OASIS 1111","","23-06-2025 12:25:56","23-06-2025 12:24:41","23-06-2025=
 13:51:57"," Site went down because Gen overload (17kva, 250A) // Grid retu=
rn","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d"," Site went down because Gen overload (17kva, 250A) // Grid return","edw=
ige.kapawo@matech-cameroun.com","76","23-06-2025 12:25:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0005324407","Mendong =
vallee","","23-06-2025 12:09:31","23-06-2025 11:59:03","23-06-2025 13:55:53=
","Cascaded Incident from TTO5489555","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went Down because Achile Fots=
o  (694271069/ SFM) was  on site for swap PWC // End of work","system","339=
663","23-06-2025 12:09:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005324409","Montee-J=
ouvence","","23-06-2025 12:09:31","23-06-2025 11:59:03","23-06-2025 13:55:5=
3","Cascaded Incident from TTO5489555","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went Down because Achile =
Fotso  (694271069/ SFM) was  on site for swap PWC // End of work","system",=
"339663","23-06-2025 12:09:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0005324408","Mendong =
Maeture","","23-06-2025 12:09:31","23-06-2025 11:59:03","23-06-2025 13:55:5=
3","Cascaded Incident from TTO5489555","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went Down because Achile =
Fotso  (694271069/ SFM) was  on site for swap PWC // End of work","system",=
"339662","23-06-2025 12:09:31","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005324401","M=
endong","IHS_YND_692, IHS_YND_569, IHS_YND_236","23-06-2025 12:07:18","23-0=
6-2025 11:59:03","23-06-2025 13:55:53","Site went Down because Achile Fotso=
  (694271069/ SFM) was  on site for swap PWC // End of work","Hyemafo Gilda=
s","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Site went Down because Achile Fotso  (694271069/ SFM) was  on site for swap=
 PWC // End of work","edwige.kapawo@matech-cameroun.com","496","23-06-2025 =
12:07:18","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005324312","Nko=
abang2","","23-06-2025 11:52:25","23-06-2025 11:48:31","23-06-2025 12:46:31=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","gerard.t=
changoue@matech-cameroun.com","236","23-06-2025 11:52:25","MATECH CMR"
"Closed Complete","Site Down","T1085","IHS_YND_130","NOCINC0005324115","Bas=
tos usine","","23-06-2025 11:20:22","23-06-2025 11:14:16","23-06-2025 11:36=
:16","Grid outage,gen failed to start due Gen battery Faulty //Gen manually=
 started with external battery","Mboua Thierry","Equipment Repair","Passive=
","ACDG Gen","ACDG - Generator Battery","Grid outage,gen failed to start du=
e Gen battery Faulty //Gen manually started with external battery","gerard.=
tchangoue@matech-cameroun.com","367","23-06-2025 11:20:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005324092","Bastos B=
ethesda","","23-06-2025 11:14:19","23-06-2025 11:12:06","23-06-2025 11:33:0=
1","Cascaded Incident from TTO5489194","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage,gen failed to start=
 due Gen battery Faulty //Gen manually started with external battery","syst=
em","1211593","23-06-2025 11:14:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005324091","Golf Qua=
ter","","23-06-2025 11:14:19","23-06-2025 11:12:06","23-06-2025 11:33:01","=
Cascaded Incident from TTO5489194","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,gen failed to start due=
 Gen battery Faulty //Gen manually started with external battery","system",=
"1211594","23-06-2025 11:14:19","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005324088","B=
astos-Nylon","IHS_YND_220, IHS_YND_563","23-06-2025 11:13:16","23-06-2025 1=
1:12:06","23-06-2025 11:33:01","Grid outage,gen failed to start due Gen bat=
tery Faulty //Gen manually started with external battery","Mboua Thierry","=
Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid out=
age,gen failed to start due Gen battery Faulty //Gen manually started with =
external battery","edwige.kapawo@matech-cameroun.com","70","23-06-2025 11:1=
3:16","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005324072","N=
koabang Ebolmedjock","","23-06-2025 11:09:17","23-06-2025 11:02:54","23-06-=
2025 11:03:20","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","edwige.kapawo@mate=
ch-cameroun.com","385","23-06-2025 11:09:17","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005324010","Fla=
menco","","23-06-2025 10:55:25","23-06-2025 10:52:19","23-06-2025 12:36:35"=
,"Grid outage .gen failed to start due to card GE dysfunctionning//We reset=
 card GE and gen manually started","Mboua Thierry","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage .gen failed to start du=
e to card GE dysfunctionning//We reset card GE and gen manually started","g=
erard.tchangoue@matech-cameroun.com","187","23-06-2025 10:55:25","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005323992","MEHANDAN=
","","23-06-2025 10:51:29","23-06-2025 10:48:23","23-06-2025 10:55:11","Cas=
caded Incident from TTO5489080","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","1213101","23-06-2025 10:51:29","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005323990","NKO=
MKANA ELIZA HOTEL","","23-06-2025 10:51:20","23-06-2025 10:45:05","23-06-20=
25 14:16:23","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","376","23-06-2025 10:51:20","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005323978","O=
dza II OCM","IHS_YND_528","23-06-2025 10:50:35","23-06-2025 10:48:23","23-0=
6-2025 10:55:30","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","edwige.kapawo@matech-cameroun.com","135","23-06-20=
25 10:50:35","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005323943","OBA=
M NGOLA OCM","","23-06-2025 10:42:35","23-06-2025 10:41:30","23-06-2025 15:=
24:33","(Unstable site)  Site went down due to PWC overload //Site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","(Unstable site)  Site went down due to PWC overload //Site=
 stabilised","gerard.tchangoue@matech-cameroun.com","67","23-06-2025 10:42:=
35","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005323756","Awa=
e Ewonkan","","23-06-2025 10:11:53","23-06-2025 10:11:48","23-06-2025 13:03=
:21","(Unstable site)Grid outage site went down due to Gen Overload (20Kva,=
 Iload 225 A)IHS SS Alphonse is informed // site stabilised","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","(Unstable site=
)Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IHS SS =
Alphonse is informed // site stabilised","gerard.tchangoue@matech-cameroun.=
com","6","23-06-2025 10:11:53","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005323702","E=
toug ebe Meweulo","","23-06-2025 10:04:51","23-06-2025 10:02:43","23-06-202=
5 10:10:53","Grid outage site went down because Gen failed to start due PWC=
 ZTE dysfonction // Grid return","Hyemafo Gildas","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Grid outage site went down b=
ecause Gen failed to start due PWC ZTE dysfonction // Grid return","edwige.=
kapawo@matech-cameroun.com","129","23-06-2025 10:04:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005323622","Acropole=
","","23-06-2025 09:50:10","23-06-2025 07:20:54","23-06-2025 09:54:08","Cas=
caded Incident from TTO5487831","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to insufficient of =
rectifier on site//Site stabilised","system","700791","23-06-2025 09:50:10"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005323414","E=
SSOS OASIS 1111","","23-06-2025 09:04:30","23-06-2025 08:54:59","23-06-2025=
 12:09:48","Grid outage, Site went down because Gen overload (17kva, 250A) =
// Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) // Grid return","edwige.kapawo@matech-cameroun.com","572","23-06-2025 0=
9:04:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005323257","Messassi=
 okolo","","23-06-2025 08:31:18","23-06-2025 08:21:43","25-06-2025 15:44:18=
","Cascaded Incident from TTO5488246","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (Gen Noise) // Grid returned	","system","14=
16628","23-06-2025 08:31:18","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005323246","E=
SSOS OASIS 1111","","23-06-2025 08:27:19","23-06-2025 08:18:59","23-06-2025=
 08:34:33","Grid outage, Site went down because Gen overload (17kva, 250A) =
// Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) // Grid return","edwige.kapawo@matech-cameroun.com","501","23-06-2025 0=
8:27:19","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005323236","EMA=
NA BILICK CITY","IHS_YND_279","23-06-2025 08:24:56","23-06-2025 08:21:43","=
25-06-2025 15:49:58","Grid outage, site down because site behaves as Grid o=
nly site (Gen Noise) // Grid returned	","Fabrice Pouakam","Access Denial","=
Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid =
outage, site down because site behaves as Grid only site (Gen Noise) // Gri=
d returned	","gerard.tchangoue@matech-cameroun.com","247","23-06-2025 08:24=
:56","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005323097","M=
ontee-Des-Soeurs","","23-06-2025 07:59:30","22-06-2025 20:16:02","23-06-202=
5 09:11:58","(Backtraking) Grid outage ,site down due to Gen overload (15 K=
VA/210 A) // Grid return","Hyemafo Gildas","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","(Backtraking) Grid outage ,site down due to Gen =
overload (15 KVA/210 A) // Grid return","edwige.kapawo@matech-cameroun.com"=
,"42210","23-06-2025 07:59:30","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005322877","A=
wae Ewonkan","","23-06-2025 07:31:14","23-06-2025 07:30:06","23-06-2025 10:=
02:01"," site went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alph=
onse is informed // Site stabilised","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload"," site went down due to Gen Overload (2=
0Kva, Iload 225 A)IHS SS Alphonse is informed // Site stabilised","edwige.k=
apawo@matech-cameroun.com","70","23-06-2025 07:31:14","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005322852","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","23-06-2025 07:25:01","23-06-2025 0=
7:20:54","23-06-2025 07:56:08","Site went down due to insufficient of recti=
fier on site//Site stabilised","MINKA NICOLAS","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module","Site went down due to insufficient of rect=
ifier on site//Site stabilised","edwige.kapawo@matech-cameroun.com","248","=
23-06-2025 07:25:01","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005322840","C=
-Supreme","","23-06-2025 07:23:43","23-06-2025 07:20:54","23-06-2025 09:54:=
08","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","S=
ite went down due to insufficient of rectifier on site//Site stabilised","e=
dwige.kapawo@matech-cameroun.com","700790","23-06-2025 07:23:43","MATECH CM=
R"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005322788","OBA=
M NGOLA OCM","","23-06-2025 07:06:23","23-06-2025 07:05:17","23-06-2025 10:=
22:32","Grid outage, Site went down due to PWC overload //Site stabilised",=
"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","Grid outage, Site went down due to PWC overload //Site stabili=
sed","gerard.tchangoue@matech-cameroun.com","67","23-06-2025 07:06:23","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005322757","C-Suprem=
e","","23-06-2025 06:58:10","23-06-2025 06:56:53","23-06-2025 06:57:35","Ca=
scaded Incident from TTO5487722","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage , site went down before Gen failed to =
started due to poor battery backup // Gen automaticaly started","system","3=
57593","23-06-2025 06:58:10","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005322751","M=
vog Mbi New","IHS_YND_021","23-06-2025 06:57:24","23-06-2025 06:56:53","23-=
06-2025 06:57:35","Grid outage , site went down before Gen failed to starte=
d due to poor battery backup // Gen automaticaly started","MINKA NICOLAS","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","=
Grid outage , site went down before Gen failed to started due to poor batte=
ry backup // Gen automaticaly started","edwige.kapawo@matech-cameroun.com",=
"69","23-06-2025 06:57:24","MATECH CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0005322482","Mim=
boman3","","23-06-2025 06:14:53","23-06-2025 06:10:47","23-06-2025 08:04:56=
","Grid outage, site went down because gen failed to start due to PWC ZTE m=
alfunction // He reset controller and gen manually started","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid outage, site went down because gen failed to start due to PWC ZTE mal=
function // He reset controller and gen manually started","loic.noumsi@mate=
ch-cameroun.com","247","23-06-2025 06:14:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005322376","EBOM",""=
,"23-06-2025 05:54:57","23-06-2025 05:42:12","23-06-2025 14:43:18","Cascade=
d Incident from TTO5487260","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to PWC overload (15KVA=
, 360A) //Site stabilized","system","361923","23-06-2025 05:54:57","MATECH =
CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005322326","A=
hala","IHS_YND_698","23-06-2025 05:45:35","23-06-2025 05:42:12","23-06-2025=
 14:43:18","Site went down due to PWC overload (15KVA, 360A) //Site stabili=
zed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","Site went down due to PWC overload (15KVA, 360A) //Site s=
tabilized","loic.noumsi@matech-cameroun.com","204","23-06-2025 05:45:35","M=
ATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005322320","OBA=
M NGOLA OCM","","23-06-2025 05:44:07","23-06-2025 05:42:01","23-06-2025 06:=
45:54","Grid outage, Site went down due to PWC overload //Site stabilised",=
"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","Grid outage, Site went down due to PWC overload //Site stabili=
sed","loic.noumsi@matech-cameroun.com","127","23-06-2025 05:44:07","MATECH =
CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005322301","O=
LAMA","","23-06-2025 05:37:02","23-06-2025 05:31:56","23-06-2025 06:30:46",=
"Active // No power issue on site Ubaie =3D54.5V site on Gen The TX FME Hen=
ri (699949693) from Huawei is informed.","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/ No power issue on site Ubaie =3D54.5V site on Gen The TX FME Henri (69994=
9693) from Huawei is informed.","loic.noumsi@matech-cameroun.com","307","23=
-06-2025 05:37:02","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005322043","OBA=
M NGOLA OCM","","23-06-2025 04:43:48","23-06-2025 04:35:40","23-06-2025 04:=
51:53","Grid outage, Site went down due to PWC overload //Site stabilised",=
"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","Grid outage, Site went down due to PWC overload //Site stabili=
sed","loic.noumsi@matech-cameroun.com","489","23-06-2025 04:43:48","MATECH =
CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005321816","OBA=
M NGOLA OCM","","23-06-2025 03:00:32","23-06-2025 02:56:55","23-06-2025 03:=
15:10","Grid outage, Site went down due to PWC overload //Site stabilised",=
"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","Grid outage, Site went down due to PWC overload //Site stabili=
sed","loic.noumsi@matech-cameroun.com","218","23-06-2025 03:00:32","MATECH =
CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005321748","Mok=
olo Yaounde","","23-06-2025 02:24:59","23-06-2025 02:21:20","23-06-2025 02:=
25:29","Active // No power issue Ubay: 54.6 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.6 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","loic.noumsi@matech-cameroun.com","220","=
23-06-2025 02:24:59","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005321498","M=
imboman-Ecole","","23-06-2025 01:00:56","23-06-2025 00:54:47","23-06-2025 0=
8:20:35","(access issue at night due to landlord) Site went down because re=
ctifier dysfunctioned on site // He reset the rectifie","Mba Lazare Herve",=
"Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue - =
Land Lord","(access issue at night due to landlord) Site went down because =
rectifier dysfunctioned on site // He reset the rectifie","loic.noumsi@mate=
ch-cameroun.com","370","23-06-2025 01:00:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0005321478","Ngoulmek=
ong-Nord","","23-06-2025 00:53:56","23-06-2025 00:46:23","23-06-2025 01:35:=
00","Cascaded Incident from TTO5486331","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down du=
e to Gen overload (20 Kva, 290A) // Grid returned","system","379166","23-06=
-2025 00:53:56","MATECH CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0005321477","E=
leveur","IHS_YND_277","23-06-2025 00:53:31","23-06-2025 00:46:23","23-06-20=
25 01:35:00","Grid outage, site went down due to Gen overload (20 Kva, 290A=
) // Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage, site went down due to Gen overload (20 Kva=
, 290A) // Grid returned","loic.noumsi@matech-cameroun.com","429","23-06-20=
25 00:53:31","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005321391","S=
imbock OCM","","23-06-2025 00:20:47","23-06-2025 00:14:43","23-06-2025 07:4=
9:39","(Access issue at night) Grid outage, Site went down because Gen stop=
ped due to Gen overload(20kva, 170A) SS IHS Felix Zambe is informed and con=
firmed//  He reduiced the load and started gen manualy","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","(Access issue at n=
ight) Grid outage, Site went down because Gen stopped due to Gen overload(2=
0kva, 170A) SS IHS Felix Zambe is informed and confirmed//  He reduiced the=
 load and started gen manualy","loic.noumsi@matech-cameroun.com","365","23-=
06-2025 00:20:47","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005321283","S=
tade-Abega","","22-06-2025 23:45:11","22-06-2025 23:38:01","22-06-2025 23:4=
2:58","Active // No power issue, site is on grid with Ubaie=3D53.4V, Lionel=
 adjep(655184876) from Huawei is on site.Impacted by EKOUNOU II","Mba Lazar=
e Herve","Customer Equipment Failure","Active","Active Equipment Failure","=
Affected by 3rd Party Site","Active // No power issue, site is on grid with=
 Ubaie=3D53.4V, Lionel adjep(655184876) from Huawei is on site.Impacted by =
EKOUNOU II","loic.noumsi@matech-cameroun.com","431","22-06-2025 23:45:11","=
MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0005321280","UPA=
C LP","","22-06-2025 23:43:44","22-06-2025 23:37:38","22-06-2025 23:40:59",=
"Active, no power issue, site on grid with U=3D54.3V Tx FME Armand Nguetsa =
(??699949553??) From Huawei is informed.","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power i=
ssue, site on grid with U=3D54.3V Tx FME Armand Nguetsa (??699949553??) Fro=
m Huawei is informed.","loic.noumsi@matech-cameroun.com","367","22-06-2025 =
23:43:44","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005321266","E=
mombo","","22-06-2025 23:37:48","22-06-2025 23:34:38","22-06-2025 23:40:48"=
,"Site went down due to battery circuit breaker dysjuncted//We rearmed CB a=
nd site on gen","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Circuit Breaker Tripped","Site went down due to battery circuit break=
er dysjuncted//We rearmed CB and site on gen","loic.noumsi@matech-cameroun.=
com","191","22-06-2025 23:37:48","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005321254","ESS=
OS OASIS 1111","","22-06-2025 23:34:55","22-06-2025 23:33:24","22-06-2025 2=
3:45:54","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) // Grid returned","loic.noumsi@matech-cameroun.com","92","22-06-2025 23=
:34:55","MATECH CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0005321134","Ele=
veurs","","22-06-2025 22:57:55","22-06-2025 22:54:50","23-06-2025 00:25:00"=
,"Grid outage,site went down because Gen start and stopped with alarm*Short=
 circuit*//He reset the Gen card and start the Gen manually","Siligap Boris=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge,site went down because Gen start and stopped with alarm*Short circuit*//=
He reset the Gen card and start the Gen manually","loic.noumsi@matech-camer=
oun.com","185","22-06-2025 22:57:55","MATECH CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0005321133","M=
ontee-Jouvence","","22-06-2025 22:57:13","22-06-2025 22:54:45","22-06-2025 =
23:05:56","ACTIVE//No power issue u=3D53.3V site on GRID,The Tx FME Hosiah/=
/699699694 is informed","Hyemafo Gildas","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue=
 u=3D53.3V site on GRID,The Tx FME Hosiah//699699694 is informed","loic.nou=
msi@matech-cameroun.com","149","22-06-2025 22:57:13","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005321111","A=
wae Ewonkan","","22-06-2025 22:52:37","22-06-2025 22:50:02","23-06-2025 00:=
20:39","(Unstable Site ) site went down due to Gen Overload (20Kva, Iload 2=
25 A)IHS SS Alphonse is informed // Site stabilised","Albran Byorel","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","(Unstable Site ) site =
went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is inform=
ed // Site stabilised","loic.noumsi@matech-cameroun.com","157","22-06-2025 =
22:52:37","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0005321035","Eke=
kam","","22-06-2025 22:32:03","22-06-2025 22:22:57","23-06-2025 01:07:24","=
Hybrid Gen Site: Site went down due to hybrid system dysfunctionning // He =
reset PSC3 and Gen manually started .","TIENTCHEU NZETCHIEU GAEL","Equipmen=
t Repair","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: Site went do=
wn due to hybrid system dysfunctionning // He reset PSC3 and Gen manually s=
tarted .","gerard.tchangoue@matech-cameroun.com","547","22-06-2025 22:32:03=
","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005320854","OBA=
M NGOLA OCM","","22-06-2025 22:03:37","22-06-2025 21:59:24","23-06-2025 01:=
28:49","Grid outage, Site went down due to PWC overload //Site stabilised",=
"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","Grid outage, Site went down due to PWC overload //Site stabili=
sed","cedric.tiani@matech-cameroun.com","254","22-06-2025 22:03:37","MATECH=
 CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005320837","ESS=
OS OASIS 1111","","22-06-2025 22:01:09","22-06-2025 21:54:59","22-06-2025 2=
2:44:27","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) // Grid returned","cedric.tiani@matech-cameroun.com","371","22-06-2025 =
22:01:09","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005320745","Nko=
l-Mbanda","","22-06-2025 21:38:38","22-06-2025 21:35:27","22-06-2025 22:35:=
13","Grid outage.gen ran until fuel shortage//Refueling done","MINKA NICOLA=
S","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran un=
til fuel shortage//Refueling done","cedric.tiani@matech-cameroun.com","192"=
,"22-06-2025 21:38:38","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005320651","ESS=
OS OASIS 1111","","22-06-2025 21:21:13","22-06-2025 21:15:05","22-06-2025 2=
1:27:52","Grid outage, Site went down because Gen overload (17kva, 250A) //=
Site stabilised","Siligap Boris","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, Site went down because Gen overload (17kva, 2=
50A) //Site stabilised","cedric.tiani@matech-cameroun.com","369","22-06-202=
5 21:21:13","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005320507","Par=
adis Hotel","","22-06-2025 20:56:15","22-06-2025 20:53:50","22-06-2025 20:5=
5:01","Site went down due to Insufficient rectifiers on site //Site stabili=
sed","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to Insufficient rectifiers on site //Site stabili=
sed","cedric.tiani@matech-cameroun.com","146","22-06-2025 20:56:15","MATECH=
 CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005320359","OBA=
M NGOLA OCM","","22-06-2025 20:44:42","22-06-2025 20:43:33","22-06-2025 21:=
34:52","Grid outage, Site went down due to PWC overload //Site stabilised",=
"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","Grid outage, Site went down due to PWC overload //Site stabili=
sed","cedric.tiani@matech-cameroun.com","70","22-06-2025 20:44:42","MATECH =
CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005320340","NYO=
M FACE MAETUR","","22-06-2025 20:42:23","22-06-2025 20:39:09","22-06-2025 2=
0:40:57","Grid fluctuation, Site went down because gen fails to start due t=
o grid bad voltage//Site stabilised","Fabrice Pouakam","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Sit=
e went down because gen fails to start due to grid bad voltage//Site stabil=
ised","cedric.tiani@matech-cameroun.com","195","22-06-2025 20:42:23","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005320318","E=
SSOS OASIS 1111","","22-06-2025 20:37:41","22-06-2025 20:35:21","22-06-2025=
 20:51:11","Grid outage, Site went down because Gen overload (17kva, 250A) =
a//Site stabilised","Siligap Boris","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage, Site went down because Gen overload (17kva=
, 250A) a//Site stabilised","vanel.mbiada@matech-cameroun.com","141","22-06=
-2025 20:37:41","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005320290","Djo=
nassi-Yde","","22-06-2025 20:28:52","22-06-2025 20:21:40","22-06-2025 21:40=
:51","Site down because 04/05 rectifiers on site dyfunction//He reset it an=
d site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site down because 04/05 rectifiers on site dyfunction//=
He reset it and site on Grid","cedric.tiani@matech-cameroun.com","432","22-=
06-2025 20:28:52","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005320274","C=
omplexe-BEAC","","22-06-2025 20:23:38","22-06-2025 20:19:25","22-06-2025 21=
:06:22","Site went down due to dysjunction of  CB(20A) in PWC//He rearmed i=
t  ","Albran Byorel","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Circuit Breaker Issue","Site went down due to dysjunction of  CB(20=
A) in PWC//He rearmed it  ","vanel.mbiada@matech-cameroun.com","254","22-06=
-2025 20:23:38","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005320238","Nko=
mo","","22-06-2025 20:14:16","22-06-2025 20:11:05","22-06-2025 20:35:02","G=
rid fluctuations, site went down because gen failed to start due to PWC ZTE=
 malfunction // He reset it and manally started the Gen","Mba Lazare Herve"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id fluctuations, site went down because gen failed to start due to PWC ZTE =
malfunction // He reset it and manally started the Gen","cedric.tiani@matec=
h-cameroun.com","192","22-06-2025 20:14:16","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005320220","OBA=
M NGOLA OCM","","22-06-2025 20:13:37","22-06-2025 20:09:27","22-06-2025 20:=
27:22","Grid outage, Site went down due to PWC overload //Site stablised","=
MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Grid outage, Site went down due to PWC overload //Site stablise=
d","cedric.tiani@matech-cameroun.com","251","22-06-2025 20:13:37","MATECH C=
MR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005320136","ESS=
OS OASIS 1111","","22-06-2025 19:59:26","22-06-2025 19:58:15","22-06-2025 2=
0:13:23","Grid outage, Site went down because Gen overload (17kva, 250A) //=
Site stabilised","Siligap Boris","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, Site went down because Gen overload (17kva, 2=
50A) //Site stabilised","cedric.tiani@matech-cameroun.com","72","22-06-2025=
 19:59:26","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005320069","Mok=
olo Yaounde","","22-06-2025 19:45:57","22-06-2025 19:39:41","22-06-2025 20:=
03:28","Active // No power issue Ubay: 54.6 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.6 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","cedric.tiani@matech-cameroun.com","377",=
"22-06-2025 19:45:57","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0005320037","Clu=
b France","","22-06-2025 19:41:52","22-06-2025 19:37:43","22-06-2025 19:39:=
14","Grid only site, no space to deploy MDGE // Grid returned","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site, =
no space to deploy MDGE // Grid returned","cedric.tiani@matech-cameroun.com=
","250","22-06-2025 19:41:52","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005319929","M=
vog-Manga","","22-06-2025 19:19:41","22-06-2025 19:16:29","22-06-2025 20:52=
:25","Active// No power issue on site. Site on Grid Ubai=3D54.3 V, The FME =
TX Lionel Adjep/655184876/ From Huawei is informed.","Albran Byorel","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue on site. Site on Grid Ubai=3D54.3 V, The FME =
TX Lionel Adjep/655184876/ From Huawei is informed.Noticed dysjunction at t=
he BTS OCM","vanel.mbiada@matech-cameroun.com","194","22-06-2025 19:19:41",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005319924","Mvog-Eba=
nda","","22-06-2025 19:18:28","22-06-2025 19:14:56","22-06-2025 22:27:01","=
Cascaded Incident from TTO5484602","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to fuel shortage=
 // Refuelling done","system","392752","22-06-2025 19:18:28","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005319923","A=
bom","IHS_YND_269","22-06-2025 19:17:06","22-06-2025 19:14:56","22-06-2025 =
22:27:01","Site went down due to fuel shortage // Refuelling done","Siligap=
 Boris","Fuel Outage","Passive","Diesel","Diesel Outage","Site went down du=
e to fuel shortage // Refuelling done","vanel.mbiada@matech-cameroun.com","=
131","22-06-2025 19:17:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_190","NOCINC0005319918","Ngousso-=
II","","22-06-2025 19:16:12","22-06-2025 19:12:12","22-06-2025 19:56:22","C=
ascaded Incident from TTO5484594","MFOUAGUEGUE MATHIEU","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","ACTIVE No power issue Ubaie=3D 54=
,6V site on Gen.The TX Fme Armand Nguetsa (699949553) from Huawei is inform=
ed .","system","392912","22-06-2025 19:16:12","MATECH CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0005319916","N=
kolmesseng","IHS_YND_190","22-06-2025 19:15:25","22-06-2025 19:12:12","22-0=
6-2025 19:58:43","ACTIVE No power issue Ubaie=3D 54,6V site on Gen.The TX F=
me Armand Nguetsa (699949553) from Huawei is informed .","Siligap Boris","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE No power issue Ubaie=3D 54,6V site on Gen.The TX Fme Arman=
d Nguetsa (699949553) from Huawei is informed .","vanel.mbiada@matech-camer=
oun.com","193","22-06-2025 19:15:25","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005319875","C=
-Supreme","","22-06-2025 19:03:52","22-06-2025 18:55:27","22-06-2025 21:29:=
49","(Unstable site)Site went down due to 03/05 rectifiers dysfunctionning =
on site//Site stabilised","","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","(Unstable site)Site went down due to 03/05 rectifiers dysfun=
ctionning on site//Site stabilised","vanel.mbiada@matech-cameroun.com","506=
","22-06-2025 19:03:52","MATECH CMR"
"Closed Complete","Site Down","T0538","IHS_YND_036","NOCINC0005319831","Acr=
opole","","22-06-2025 18:53:39","22-06-2025 18:50:20","22-06-2025 19:29:32"=
,"Grid outage, site went down because gen ran untill fuel shortage // Refue=
ling done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage, site went down because gen ran untill fuel shortage // Refue=
ling done","cedric.tiani@matech-cameroun.com","200","22-06-2025 18:53:39","=
MATECH CMR"
"Closed Complete","Site Down","T0219","IHS_YND_024","NOCINC0005319791","Gar=
bati building","","22-06-2025 18:47:53","22-06-2025 18:43:03","22-06-2025 1=
8:45:03","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","	Grid outage, Site went down before Gen start due to poor=
 backup// Gen automatically Started","cedric.tiani@matech-cameroun.com","39=
4631","22-06-2025 18:47:53","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005319783","HOP=
ITAL DE LA CAISSE","IHS_YND_024","22-06-2025 18:46:12","22-06-2025 18:43:03=
","22-06-2025 18:45:03","	Grid outage, Site went down before Gen start due =
to poor backup// Gen automatically Started","Delor Telezing","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","	Grid outage,=
 Site went down before Gen start due to poor backup// Gen automatically Sta=
rted","cedric.tiani@matech-cameroun.com","189","22-06-2025 18:46:12","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005319513","A=
wae Ewonkan","","22-06-2025 17:50:27","22-06-2025 17:49:09","22-06-2025 17:=
51:32","(Unstable Site ) site went down due to Gen Overload (20Kva, Iload 2=
25 A)IHS SS Alphonse is informed //Site Stabilised","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","(Unstable Site ) site w=
ent down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informe=
d //Site Stabilised","vanel.mbiada@matech-cameroun.com","80","22-06-2025 17=
:50:27","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005319268","Nko=
mo","","22-06-2025 17:02:17","22-06-2025 16:55:02","22-06-2025 17:54:08","G=
rid fluctuations, site went down because gen failed to start due to PWC ZTE=
 malfunction // He reset it and manally started the Gen","Mba Lazare Herve"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id fluctuations, site went down because gen failed to start due to PWC ZTE =
malfunction // He reset it and manally started the Gen","cedric.tiani@matec=
h-cameroun.com","436","22-06-2025 17:02:17","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0005319157","Val=
lee Bastos MTN","","22-06-2025 16:41:29","22-06-2025 16:38:07","22-06-2025 =
17:54:56","Site went down due to insfficient rectifiers on site (04)//He re=
set it  and  need to add 01","Mboua Thierry","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Site went down due to insfficient rectifiers=
 on site (04)//He reset it  and  need to add 01","cedric.tiani@matech-camer=
oun.com","202","22-06-2025 16:41:29","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005319107","S=
imbock OCM","","22-06-2025 16:30:50","22-06-2025 16:28:38","22-06-2025 17:1=
9:52","Grid outage,Gen failed to start because Gen does not support the loa=
d on the site //He removed all the batterries and started the GEN manually"=
,"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage,Gen failed to start because Gen does not support the load on =
the site //He removed all the batterries and started the GEN manually","van=
el.mbiada@matech-cameroun.com","133","22-06-2025 16:30:50","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005319047","C=
arrefourt Nkomo","","22-06-2025 16:23:53","22-06-2025 15:58:38","22-06-2025=
 16:36:15","Reported No power issue site on Grid with Ubaie : 52.8 V ,The F=
ME TX Henry (699949693) from Huawei is informed","Mba Lazare Herve","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Reported No power issue site on Grid with Ubaie : 52.8 V ,The FME TX H=
enry (699949693) from Huawei is informed","vanel.mbiada@matech-cameroun.com=
","1516","22-06-2025 16:23:53","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005319044","S=
IMBOCK BONAMBAPE","","22-06-2025 16:22:56","22-06-2025 16:19:45","22-06-202=
5 16:42:09","Active // No power issue site on grid with Ubaie: 54.5V TX FME=
 Flubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue site on grid with Ubaie: 54.5V TX FME Flubert (654=
266068) from Huawei is informed","vanel.mbiada@matech-cameroun.com","192","=
22-06-2025 16:22:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005319002","C-Suprem=
e","","22-06-2025 16:16:49","22-06-2025 16:10:42","22-06-2025 16:14:36","Ca=
scaded Incident from TTO5483562","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, Site went down before Gen start due t=
o poor backup // Gen start automatically","system","403568","22-06-2025 16:=
16:49","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005318993","M=
vog Mbi New","IHS_YND_021","22-06-2025 16:13:51","22-06-2025 16:10:42","22-=
06-2025 16:14:36","Grid outage, Site went down before Gen start due to poor=
 backup // Gen start automatically","MINKA NICOLAS","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen start automatically","vane=
l.mbiada@matech-cameroun.com","190","22-06-2025 16:13:51","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005318936","Nko=
mo","","22-06-2025 16:04:29","22-06-2025 15:58:53","22-06-2025 16:30:21","G=
rid fluctuations, site went down because gen failed to start due to PWC ZTE=
 malfunction // He reset it and manally started the Gen","Mba Lazare Herve"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id fluctuations, site went down because gen failed to start due to PWC ZTE =
malfunction // He reset it and manally started the Gen","cedric.tiani@matec=
h-cameroun.com","337","22-06-2025 16:04:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0005318885","Kondengu=
i","","22-06-2025 15:52:32","22-06-2025 15:41:59","22-06-2025 16:11:58","Ca=
scaded Incident from TTO5483382","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down because Gen started an=
d stopped due AVR faulty // He replaced  AVR  and started Gen manually","sy=
stem","405252","22-06-2025 15:52:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_065","NOCINC0005318886","Essos DC=
S","","22-06-2025 15:52:32","22-06-2025 15:41:59","22-06-2025 16:11:58","Ca=
scaded Incident from TTO5483382","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because Gen started a=
nd stopped due AVR faulty // He replaced  AVR  and started Gen manually","s=
ystem","405255","22-06-2025 15:52:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0005318882","Mobil-Es=
sos","","22-06-2025 15:52:31","22-06-2025 15:41:59","22-06-2025 16:11:58","=
Cascaded Incident from TTO5483382","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because Gen started =
and stopped due AVR faulty // He replaced  AVR  and started Gen manually","=
system","405262","22-06-2025 15:52:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0005318883","Anguissa=
 New","","22-06-2025 15:52:31","22-06-2025 15:41:59","22-06-2025 16:11:58",=
"Cascaded Incident from TTO5483382","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen started=
 and stopped due AVR faulty // He replaced  AVR  and started Gen manually",=
"system","405255","22-06-2025 15:52:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_113","NOCINC0005318881","Emombo 2=
","","22-06-2025 15:52:31","22-06-2025 15:41:59","22-06-2025 16:11:58","Cas=
caded Incident from TTO5483382","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because Gen started and=
 stopped due AVR faulty // He replaced  AVR  and started Gen manually","sys=
tem","405257","22-06-2025 15:52:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_178","NOCINC0005318884","Emombo",=
"","22-06-2025 15:52:31","22-06-2025 15:41:59","22-06-2025 16:11:58","Casca=
ded Incident from TTO5483382","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down because Gen started an=
d stopped due AVR faulty // He replaced  AVR  and started Gen manually","sy=
stem","405258","22-06-2025 15:52:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_120","NOCINC0005318880","Sapeur M=
imboman","","22-06-2025 15:52:31","22-06-2025 15:41:59","22-06-2025 16:11:5=
8","Cascaded Incident from TTO5483382","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down because Gen s=
tarted and stopped due AVR faulty // He replaced  AVR  and started Gen manu=
ally","system","405256","22-06-2025 15:52:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_797","NOCINC0005318876","Fouda ru=
e des g=E9n=E9raux","","22-06-2025 15:52:30","22-06-2025 15:41:59","22-06-2=
025 16:11:58","Cascaded Incident from TTO5483382","Delor Telezing","Cascade=
 Outage","Passive","Cascade Passive","Cascade Passive","Site went down beca=
use Gen started and stopped due AVR faulty // He replaced  AVR  and started=
 Gen manually","system","405254","22-06-2025 15:52:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_122","NOCINC0005318877","Emombo E=
sssomba","","22-06-2025 15:52:30","22-06-2025 15:41:59","22-06-2025 16:11:5=
8","Cascaded Incident from TTO5483382","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down because Gen s=
tarted and stopped due AVR faulty // He replaced  AVR  and started Gen manu=
ally","system","405259","22-06-2025 15:52:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_108","NOCINC0005318878","RUE FOE"=
,"","22-06-2025 15:52:30","22-06-2025 15:41:59","22-06-2025 16:11:58","Casc=
aded Incident from TTO5483382","Delor Telezing","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because Gen started and=
 stopped due AVR faulty // He replaced  AVR  and started Gen manually","sys=
tem","405261","22-06-2025 15:52:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_189","NOCINC0005318879","Paradis =
Hotel","","22-06-2025 15:52:30","22-06-2025 15:41:59","22-06-2025 16:11:58"=
,"Cascaded Incident from TTO5483382","Siligap Boris","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because Gen starte=
d and stopped due AVR faulty // He replaced  AVR  and started Gen manually"=
,"system","405251","22-06-2025 15:52:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_111","NOCINC0005318874","Essos Ma=
rche","","22-06-2025 15:52:29","22-06-2025 15:41:59","22-06-2025 16:11:58",=
"Cascaded Incident from TTO5483382","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because Gen starte=
d and stopped due AVR faulty // He replaced  AVR  and started Gen manually"=
,"system","405260","22-06-2025 15:52:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_180","NOCINC0005318875","Mimboman=
","","22-06-2025 15:52:29","22-06-2025 15:41:59","22-06-2025 16:11:58","Cas=
caded Incident from TTO5483382","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because Gen started =
and stopped due AVR faulty // He replaced  AVR  and started Gen manually","=
system","405263","22-06-2025 15:52:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0005318873","MONTEE N=
KONDENGUI","","22-06-2025 15:52:29","22-06-2025 15:41:59","22-06-2025 16:11=
:58","Cascaded Incident from TTO5483382","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because Gen st=
arted and stopped due AVR faulty // He replaced  AVR  and started Gen manua=
lly","system","405253","22-06-2025 15:52:29","MATECH CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0005318834","Cam=
p-Sonel","IHS_YND_682, IHS_YND_111, IHS_YND_180, IHS_YND_797, IHS_YND_122, =
IHS_YND_108, IHS_YND_189, IHS_YND_120, IHS_YND_113, IHS_YND_109, IHS_YND_56=
8, IHS_YND_178, IHS_YND_114, IHS_YND_065","22-06-2025 15:43:09","22-06-2025=
 15:41:59","22-06-2025 16:11:58","Site went down because Gen started and st=
opped due AVR faulty // He replaced  AVR  and started Gen manually","Siliga=
p Boris","Equipment Repair","Passive","ACDG Gen","ACDG - AVR","Site went do=
wn because Gen started and stopped due AVR faulty // He replaced  AVR  and =
started Gen manually","cedric.tiani@matech-cameroun.com","70","22-06-2025 1=
5:43:09","MATECH CMR"
"Closed Complete","Warning","T0103","IHS_YND_110","NOCINC0005318704","Camp-=
Sonel","","22-06-2025 15:17:16","","","Site went down because Gen started a=
nd stopped due AVR faulty // He replaced  AVR  and started Gen manually","S=
iligap Boris","Warning","Warning","POWER","Warning - ACDG - AVR","Site went=
 down because Gen started and stopped due AVR faulty // He replaced  AVR  a=
nd started Gen manually","cedric.tiani@matech-cameroun.com","7937","22-06-2=
025 15:17:16","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0005318622","Eto=
ug-Ebe 2","","22-06-2025 14:57:33","22-06-2025 14:55:20","22-06-2025 18:53:=
09","Grid outage no space to deploy a mobil gen // grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no =
space to deploy a mobil gen // grid return","cedric.tiani@matech-cameroun.c=
om","133","22-06-2025 14:57:33","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005318533","N=
koabang Ebolmedjock","","22-06-2025 14:39:00","22-06-2025 14:35:51","22-06-=
2025 14:57:43","Site impacted by Nkolmesseng-Abom(CTR-711) Not Managed By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Site impacted by Nkolmesseng-Abom(CTR-71=
1) Not Managed By IHS","vanel.mbiada@matech-cameroun.com","190","22-06-2025=
 14:39:00","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005318492","M=
vog-Ada_OCM","","22-06-2025 14:30:22","22-06-2025 14:27:11","22-06-2025 17:=
22:55","Grid Only, No space to deploy MGE // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space t=
o deploy MGE // Grid return","vanel.mbiada@matech-cameroun.com","192","22-0=
6-2025 14:30:22","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005318479","O=
dza II OCM","","22-06-2025 14:27:58","22-06-2025 14:22:50","22-06-2025 14:3=
1:52","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction //Site stabilised","Albran Byorel","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, sit=
e went down because gen failed to start due to PWC ZTE malfunction //Site s=
tabilised","vanel.mbiada@matech-cameroun.com","310","22-06-2025 14:27:58","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005318281","MEHANDAN=
","","22-06-2025 13:43:00","22-06-2025 13:37:31","22-06-2025 13:45:01","Cas=
caded Incident from TTO5482771","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","329","22-06-2025 13:43:00","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005318276","O=
dza II OCM","IHS_YND_528","22-06-2025 13:41:37","22-06-2025 13:37:31","22-0=
6-2025 13:45:01","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","edwige.kapawo@matech-cameroun.com","249","22-06-20=
25 13:41:37","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005318195","ODZ=
A BORNE 10","","22-06-2025 13:26:20","18-06-2025 14:33:06","18-06-2025 14:3=
4:06","site went down due to dysfunctioning of rectifiers // SIte stabilise=
d","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","site went down due to dysfunctioning of rectifiers // SIte stabilised"=
,"gerard.tchangoue@matech-cameroun.com","341594","22-06-2025 13:26:20","MAT=
ECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0005318164","SAA=
 2","","22-06-2025 13:20:03","18-06-2025 19:21:32","18-06-2025 19:38:32","N=
o power issue on site ,site on Gen with Ubaie =3D53.6V.  Tx Technician from=
 Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site ,site on Gen with Ubaie =3D53.6V.  Tx Technician from Hu=
awei Gr=E9goire//654547479 is informed","gerard.tchangoue@matech-cameroun.c=
om","323911","22-06-2025 13:20:03","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005318139","O=
LAMA","","22-06-2025 13:15:13","22-06-2025 13:06:55","22-06-2025 13:23:50",=
"Active // No power issue on site Ubaie =3D54.9V site on Gen The TX FME Hen=
ri (699949693) from Huawei is informed.Noticed that it is a repetitve issue=
","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active // No power issue on site Ubaie =3D54.9V=
 site on Gen The TX FME Henri (699949693) from Huawei is informed.Noticed t=
hat it is a repetitve issue","edwige.kapawo@matech-cameroun.com","500","22-=
06-2025 13:15:13","MATECH CMR"
"Closed Complete","Site Down","T0287","IHS_YND_038","NOCINC0005318101","Sia=
ntou Inferieur","","22-06-2025 13:08:56","22-06-2025 13:01:51","22-06-2025 =
19:57:47","Grid outage, no space to deploy // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spac=
e to deploy // Grid return","gerard.tchangoue@matech-cameroun.com","425","2=
2-06-2025 13:08:56","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005318050","Nko=
mo","","22-06-2025 12:53:44","22-06-2025 12:49:35","22-06-2025 14:15:15","G=
rid fluctuations, site went down because gen failed to start due to PWC ZTE=
 malfunction // He reset it and manally started the Gen","Mba Lazare Herve"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id fluctuations, site went down because gen failed to start due to PWC ZTE =
malfunction // He reset it and manally started the Gen","gerard.tchangoue@m=
atech-cameroun.com","250","22-06-2025 12:53:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005317976","Song-bon=
g","","22-06-2025 12:37:17","22-06-2025 11:30:40","22-06-2025 12:42:28","Ca=
scaded Incident from TTO5482402","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Grid outage,Site went down because Gen=
 failed to start due to Grid contactor dysfunctionning //He excited the Gri=
d contactor and site on Grid./ End of work Power issue resolved at OCM but =
remains down","system","420097","22-06-2025 12:37:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005317975","Eseka To=
wn","","22-06-2025 12:37:17","22-06-2025 11:30:40","22-06-2025 12:42:28","C=
ascaded Incident from TTO5482402","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Grid outage,Site went down because Ge=
n failed to start due to Grid contactor dysfunctionning //He excited the Gr=
id contactor and site on Grid./ End of work Power issue resolved at OCM but=
 remains down","system","420096","22-06-2025 12:37:17","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005317946","E=
seka OCM","IHS_YND_378, IHS_YND_453","22-06-2025 12:30:46","22-06-2025 11:3=
0:40","22-06-2025 12:42:28","Grid outage,Site went down because Gen failed =
to start due to Grid contactor dysfunctionning //He excited the Grid contac=
tor and site on Grid./ End of work Power issue resolved at OCM but remains =
down","Kemeni Franklin","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Grid outage,Site went down because Gen =
failed to start due to Grid contactor dysfunctionning //He excited the Grid=
 contactor and site on Grid./ End of work Power issue resolved at OCM but r=
emains down. The Tx FME Etienne (695033981 / huawei) is informed","edwige.k=
apawo@matech-cameroun.com","3607","22-06-2025 12:30:46","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005317884","MBA=
LNGONG LYCEE","","22-06-2025 12:17:42","22-06-2025 12:08:28","27-06-2025 08=
:54:05","Grid outage, landlord stopped the Gen because it's too noisy// Gri=
d return Power issue reolved but site remains down at 08:54 AM Email of sof=
 reset has done Fulbert of Huawei is informed and working o","Fanda Brice",=
"Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue - =
Land Lord","Acces issue due to landlord Grid outage, landlord stopped the G=
en because it's too noisy// Grid return Power issue reolved but site remain=
s down at 08:54 AM Email of sof reset has done Fulbert(654266068) of Huawei=
 is informed and working on site","gerard.tchangoue@matech-cameroun.com","5=
56","22-06-2025 12:17:42","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005317856","S=
IMBOCK BONAMBAPE","","22-06-2025 12:11:11","22-06-2025 12:06:59","22-06-202=
5 12:16:20","Active // No power issue site on grid with Ubaie: 54.5V TX FME=
 Flubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue site on grid with Ubaie: 54.5V TX FME Flubert (654=
266068) from Huawei is informed","edwige.kapawo@matech-cameroun.com","254",=
"22-06-2025 12:11:11","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005317658","A=
wae Ewonkan","","22-06-2025 11:41:20","22-06-2025 11:39:14","22-06-2025 14:=
25:00","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed //Grid rreturn","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed //Grid rret=
urn","edwige.kapawo@matech-cameroun.com","128","22-06-2025 11:41:20","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005317419","N=
koabang Ebolmedjock","","22-06-2025 10:55:21","22-06-2025 10:46:59","22-06-=
2025 11:36:31","Site impacted by Nkolmesseng-Abom wich is not managed by IH=
S","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipme=
nt Failure","Affected by 3rd Party Site","Site impacted by Nkolmesseng-Abom=
 wich is not managed by IHS","edwige.kapawo@matech-cameroun.com","504","22-=
06-2025 10:55:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005317089","Song-bon=
g","","22-06-2025 10:08:09","22-06-2025 09:53:25","22-06-2025 11:29:47","Ca=
scaded Incident from TTO5481373","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,Site went down because =
Gen failed to start due to Grid contactor dysfunctionning //He excited the =
Grid contactor and site on Grid","system","425691","22-06-2025 10:08:09","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005317033","Eseka To=
wn","","22-06-2025 09:58:19","22-06-2025 09:53:25","22-06-2025 11:29:47","C=
ascaded Incident from TTO5481373","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,Site went down because=
 Gen failed to start due to Grid contactor dysfunctionning //He excited the=
 Grid contactor and site on Grid","system","425690","22-06-2025 09:58:19","=
MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005317016","E=
seka OCM","IHS_YND_378, IHS_YND_453","22-06-2025 09:55:40","22-06-2025 09:5=
3:25","22-06-2025 11:29:47","Grid outage,Site went down because Gen failed =
to start due to Grid contactor dysfunctionning //He excited the Grid contac=
tor and site on Grid","Kemeni Franklin","Equipment Repair","Passive","Contr=
ol Panel","ATS-AMF Issue","Grid outage,Site went down because Gen failed to=
 start due to Grid contactor dysfunctionning //He excited the Grid contacto=
r and site on Grid","edwige.kapawo@matech-cameroun.com","136","22-06-2025 0=
9:55:40","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0005316971","Ngo=
um","","22-06-2025 09:48:33","22-06-2025 09:38:26","22-06-2025 11:24:26","G=
rid outage, site went down because gen ran untill fuel shortage // Refuelin=
g done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage, site went down because gen ran untill fuel shortage // Refuelin=
g done","gerard.tchangoue@matech-cameroun.com","608","22-06-2025 09:48:33",=
"MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005316871","NKO=
MKANA ELIZA HOTEL","","22-06-2025 09:32:16","22-06-2025 09:30:03","22-06-20=
25 09:32:28","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","134","22-06-2025 09:32:16","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005316746","E=
ssomba","","22-06-2025 09:01:42","22-06-2025 09:00:59","22-06-2025 09:46:26=
","Grid outage,Site went down because Gen failed to start due to PWC ZTE dy=
sfonction //He reset it and site on Gen","Mba Lazare Herve","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage,Site w=
ent down because Gen failed to start due to PWC ZTE dysfonction //He reset =
it and site on Gen","edwige.kapawo@matech-cameroun.com","45","22-06-2025 09=
:01:42","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005316534","Saa=
","","22-06-2025 08:11:25","22-06-2025 08:04:11","22-06-2025 08:36:19"," Gr=
id outage.sitz went eown due to grid contactor dysfonctionning//we activate=
d manually grid contactor to restore=A0the=A0site","Parker Tchoup","Equipme=
nt Repair","Passive","Control Panel","ATS-AMF Issue"," Grid outage.sitz wen=
t eown due to grid contactor dysfonctionning//we activated manually grid co=
ntactor to restore=A0the=A0site","edwige.kapawo@matech-cameroun.com","435",=
"22-06-2025 08:11:25","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005316503","HOP=
ITAL DE LA CAISSE","IHS_YND_024","22-06-2025 08:02:00","22-06-2025 07:52:49=
","22-06-2025 10:22:39","Site went down due to 1/3 Rectifiers Dysfunctionni=
ng // He reset it: Site on grid","Delor Telezing","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to 1/3 Rectifiers Dy=
sfunctionning // He reset it: Site on grid","gerard.tchangoue@matech-camero=
un.com","552","22-06-2025 08:02:00","MATECH CMR"
"Closed Complete","Site Down","T0219","IHS_YND_024","NOCINC0005316499","Gar=
bati building","","22-06-2025 08:00:54","22-06-2025 07:52:49","22-06-2025 1=
0:05:39","Site impacted by HOPITAL DE LA CAISSE	","Delor Telezing","Cascade=
 Outage","Passive","Cascade Passive","Cascade Passive","Site went down due =
to 1/3 Rectifiers Dysfunctionning // He reset it: Site on grid","gerard.tch=
angoue@matech-cameroun.com","432786","22-06-2025 08:00:54","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005316488","OBA=
M NGOLA OCM","","22-06-2025 07:57:18","22-06-2025 07:48:09","22-06-2025 19:=
57:39","Grid outage, Site went down due to PWC overload // Site stabilised"=
,"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","Grid outage, Site went down due to PWC overload // Site stabi=
lised","gerard.tchangoue@matech-cameroun.com","550","22-06-2025 07:57:18","=
MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005316475","M=
ontee-Des-Soeurs","","22-06-2025 07:53:20","22-06-2025 07:49:13","22-06-202=
5 09:38:08","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","edwige.kapawo@matech-cameroun.com","248","22-06-2025 07:53:20"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005316472","S=
atcom","","22-06-2025 07:51:51","22-06-2025 07:41:59","22-06-2025 08:26:01"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","edwige.kapawo@matech-c=
ameroun.com","593","22-06-2025 07:51:51","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005316463","S=
imbock OCM","","22-06-2025 07:49:21","22-06-2025 07:40:59","22-06-2025 07:5=
9:48","Active // No power issue Ubaie:49.6V site on Battery The Tx Fme Hosi=
ah Mbah (674007438 / Huawei) is informed","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve // No power issue Ubaie:49.6V site on Battery The Tx Fme Hosiah Mbah (67=
4007438 / Huawei) is informed","edwige.kapawo@matech-cameroun.com","503","2=
2-06-2025 07:49:21","MATECH CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0005316426","Car=
refour Ayissi Ele","","22-06-2025 07:40:49","22-06-2025 07:25:21","22-06-20=
25 07:58:42","Site impacted by Saa","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel sho=
rtage// Tank inclined (refueling ongoing)","gerard.tchangoue@matech-camerou=
n.com","427627","22-06-2025 07:40:49","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005316392","Nko=
l-Mebanga","","22-06-2025 07:35:15","22-06-2025 07:25:21","22-06-2025 07:58=
:42","Site impacted by Saa","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage.gen ran until fuel shortage// =
Tank inclined (refueling ongoing)","rouselle.schoune@ihstowers.com","427626=
","22-06-2025 07:35:15","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005316378","S=
aa","IHS_YND_810, IHS_YND_809","22-06-2025 07:29:31","22-06-2025 07:25:21",=
"22-06-2025 07:58:42","Grid outage.gen ran until fuel shortage// Tank incli=
ned (refueling ongoing)","Parker Tchoup","Fuel Outage","Passive","Diesel","=
Diesel Outage","Grid outage.gen ran until fuel shortage// Tank inclined (re=
fueling ongoing)","edwige.kapawo@matech-cameroun.com","251","22-06-2025 07:=
29:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005315621","EBOM",""=
,"22-06-2025 01:46:35","21-06-2025 23:21:33","23-06-2025 04:49:55","Cascade=
d Incident from TTO5479433","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to PWC overload (15KVA=
, 360A) //Site stabilized","system","456379","22-06-2025 01:46:35","MATECH =
CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005315609","S=
aa","","22-06-2025 01:35:49","22-06-2025 01:33:42","22-06-2025 01:36:42","N=
o power issue on site ,site on Gen with Ubaie =3D53.8V The Tx Technician fr=
om Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site ,site on Gen with Ubaie =3D53.8V The Tx Technician fro=
m Huawei Gr=E9goire//654547479 is informed","gaelle.njiofack@matech-camerou=
n.com","128","22-06-2025 01:35:49","MATECH CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0005315446","Kon=
dengui MTN","","22-06-2025 00:19:12","21-06-2025 23:59:54","22-06-2025 01:2=
6:54","Grid outage, site went down because gen ran untill fuel shortage // =
Refueling done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage, site went down because gen ran untill fuel shortage // =
Refueling done","franck.nkomot@matech-cameroun.com","10823","22-06-2025 00:=
19:12","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005315436","ODZ=
A MINKAN EDIBI ASSI","","22-06-2025 00:16:19","22-06-2025 00:13:11","22-06-=
2025 07:05:05","Grid outage, Site went down due to Gen overload // Grid ret=
urn","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overlo=
ad","Grid outage, Site went down due to Gen overload // Grid return","franc=
k.nkomot@matech-cameroun.com","189","22-06-2025 00:16:19","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005315267","A=
hala","IHS_YND_698","21-06-2025 23:25:48","21-06-2025 23:21:33","23-06-2025=
 04:49:55","Site went down due to PWC overload (15KVA, 360A) //Site stabili=
zed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","Site went down due to PWC overload (15KVA, 360A) //Site s=
tabilized","franck.nkomot@matech-cameroun.com","256","21-06-2025 23:25:48",=
"MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005315188","TSI=
NGA VILLAGE 2","","21-06-2025 22:58:57","21-06-2025 22:55:48","21-06-2025 2=
3:27:48","Site went down due to disjunction of Cb(125A) in PWC // He reamed=
 Cb(125A), site on Gen","Delor Telezing","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to d=
isjunction of Cb(125A) in PWC // He reamed Cb(125A), site on Gen","franck.n=
komot@matech-cameroun.com","190","21-06-2025 22:58:57","MATECH CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0005315178","E=
BOM","","21-06-2025 22:55:34","21-06-2025 22:48:28","21-06-2025 22:50:28","=
Active No power issue on site U=3D54.4V. site on Grid Lionel//694693436 of =
huawei is informe","Hyemafo Gildas","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","Active No power issue on si=
te U=3D54.4V. site on Grid Lionel//694693436 of huawei is informe","franck.=
nkomot@matech-cameroun.com","427","21-06-2025 22:55:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005315132","MEHANDAN=
","","21-06-2025 22:45:35","21-06-2025 22:35:35","22-06-2025 01:15:35","Cas=
caded Incident from TTO5479260","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction //He reset it and started the =
Gen manually","system","459097","21-06-2025 22:45:35","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005315114","Odz=
a II OCM","IHS_YND_528","21-06-2025 22:40:46","21-06-2025 22:35:35","22-06-=
2025 01:15:35","Grid outage, site went down because gen failed to start due=
 to PWC ZTE malfunction //He reset it and started the Gen manually","Albran=
 Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Grid outage, site went down because gen failed to start due to PWC ZT=
E malfunction //He reset it and started the Gen manually","franck.nkomot@ma=
tech-cameroun.com","347","21-06-2025 22:40:46","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005314974","TSI=
NGA VILLAGE 2","","21-06-2025 22:14:46","21-06-2025 22:05:34","21-06-2025 2=
2:15:42","Grid outage, site went down because Gen started and stopped due t=
o low oil pressure alarm // He reset it and started Gen manually","Delor Te=
lezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage, site went down because Gen started and stopped due to low oil pre=
ssure alarm // He reset it and started Gen manually","loic.noumsi@matech-ca=
meroun.com","553","21-06-2025 22:14:46","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005314794","M=
vog-Manga","","21-06-2025 21:44:32","21-06-2025 21:34:59","21-06-2025 23:35=
:59","Active// No power issue on site. Site on Grid Ubai=3D50.2 V, The FME =
TX Lionel Adjep/655184876/ From Huawei is informed.","Albran Byorel","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue on site. Site on Grid Ubai=3D50.2 V, The FME =
TX Lionel Adjep/655184876/ From Huawei is informed.","loic.noumsi@matech-ca=
meroun.com","574","21-06-2025 21:44:32","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005314711","ELO=
UMDEM CARRIERE 2","","21-06-2025 21:29:04","21-06-2025 21:24:58","21-06-202=
5 21:46:18","Grid fluctuation, Site went down because Gen failed to start d=
ue to Grid bad voltage //He bypassed Grid and started Gen manualy","Fanda B=
rice","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, Site went down because Gen failed to start due to Gr=
id bad voltage //He bypassed Grid and started Gen manualy","loic.noumsi@mat=
ech-cameroun.com","248","21-06-2025 21:29:04","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005314624","Nko=
abang2","","21-06-2025 21:13:34","21-06-2025 21:06:25","21-06-2025 23:27:51=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","loic.nou=
msi@matech-cameroun.com","430","21-06-2025 21:13:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005314558","Mfou EPC=
","","21-06-2025 20:58:04","21-06-2025 20:38:14","21-06-2025 21:04:31","Cas=
caded Incident from TTO5478649","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","465996","21-06-2025 20=
:58:04","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005314553","M=
fou OCM","IHS_YND_674","21-06-2025 20:57:22","21-06-2025 20:38:14","21-06-2=
025 21:04:31","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","gaelle.njiofack@matech-cameroun.c=
om","1149","21-06-2025 20:57:22","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005314532","OBA=
M NGOLA OCM","","21-06-2025 20:55:07","21-06-2025 20:39:03","22-06-2025 07:=
24:15","Grid outage, Site went down due to PWC overload // Grid return","MI=
NKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module Ove=
rloaded","Grid outage, Site went down due to PWC overload // Grid return","=
loic.noumsi@matech-cameroun.com","965","21-06-2025 20:55:07","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005314455","A=
hala","","21-06-2025 20:45:54","21-06-2025 20:39:44","21-06-2025 23:03:44",=
"Site went down due to PWC overload (15KVA, 360A) //Site stabilized","MINKA=
 NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module Overlo=
aded","Site went down due to PWC overload (15KVA, 360A) //Site stabilized",=
"gaelle.njiofack@matech-cameroun.com","371","21-06-2025 20:45:54","MATECH C=
MR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005314385","A=
wae Ewonkan","","21-06-2025 20:31:26","21-06-2025 20:29:12","21-06-2025 22:=
04:29","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid returned","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid r=
eturned","loic.noumsi@matech-cameroun.com","135","21-06-2025 20:31:26","MAT=
ECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005314353","TSI=
NGA VILLAGE 2","","21-06-2025 20:23:21","21-06-2025 20:18:13","21-06-2025 2=
1:16:47","Grid outage, site went down because Gen started and stopped due t=
o low oil pressure alarm // He reset it and started Gen manually","Delor Te=
lezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage, site went down because Gen started and stopped due to low oil pre=
ssure alarm // He reset it and started Gen manually","loic.noumsi@matech-ca=
meroun.com","309","21-06-2025 20:23:21","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005314205","Nko=
langaa","","21-06-2025 19:53:58","21-06-2025 19:49:52","21-06-2025 21:35:50=
","No power issue on site U=3D53.3V site on Grid Lionel Tchatchou (69469343=
6) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D53.3V site on Grid Lionel Tchatchou (694693436) from Huawei is i=
nformed","loic.noumsi@matech-cameroun.com","247","21-06-2025 19:53:58","MAT=
ECH CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0005314191","Ako=
no","","21-06-2025 19:51:44","","","grid bad voltage,no rcp on site// He by=
passe the Grid and site on Gen","Fanda Brice","Warning","Warning","POWER","=
Warning - Site on Battery","grid bad voltage,no rcp on site// He bypasse th=
e Grid and site on Gen","loic.noumsi@matech-cameroun.com","1212","21-06-202=
5 19:51:44","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005314176","Nko=
mo","","21-06-2025 19:46:20","21-06-2025 19:43:13","21-06-2025 20:31:57","S=
ite went down due to Power Cabinet overloaded ( PWC of 12 k and iload of 20=
0A)//He reset it and site on Grid","Mba Lazare Herve","Equipment Repair","P=
assive","Rectifier","Rectifier Module Overloaded","Site went down due to Po=
wer Cabinet overloaded ( PWC of 12 k and iload of 200A)//He reset it and si=
te on Grid","loic.noumsi@matech-cameroun.com","188","21-06-2025 19:46:20","=
MATECH CMR"
"Closed Complete","Site Down","CTR_063","IHS_YND_365","NOCINC0005314141","A=
kono","","21-06-2025 19:42:16","21-06-2025 19:31:08","21-06-2025 19:49:49",=
"error ticket","Fanda Brice","Incorrectly Logged Tickets","Error","Error","=
Error","error ticket","loic.noumsi@matech-cameroun.com","669","21-06-2025 1=
9:42:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005314099","MEHANDAN=
","","21-06-2025 19:32:55","21-06-2025 19:22:38","21-06-2025 21:13:14","Cas=
caded Incident from TTO5478121","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction //He reset it and started the =
Gen manually","system","463768","21-06-2025 19:32:55","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005314079","O=
dza II OCM","IHS_YND_528","21-06-2025 19:28:48","21-06-2025 19:22:38","21-0=
6-2025 21:14:00","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction //He reset it and started the Gen manually","Albr=
an Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overl=
oaded","Grid outage, site went down because gen failed to start due to PWC =
ZTE malfunction //He reset it and started the Gen manually","loic.noumsi@ma=
tech-cameroun.com","372","21-06-2025 19:28:48","MATECH CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0005313889","N=
ew-Marche-Melen","","21-06-2025 18:48:56","21-06-2025 16:05:19","21-06-2025=
 16:59:26","Backtracking// No power Issue Site on Grid Ubai =3D54.4 V. The =
TX FME Mbah Hosiah (674007438) is informed	","Paul BIBOUM","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Back=
tracking// No power Issue Site on Grid Ubai =3D54.4 V. The TX FME Mbah Hosi=
ah (674007438) is informed	","loic.noumsi@matech-cameroun.com","9818","21-0=
6-2025 18:48:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005313856","Mfou EPC=
","","21-06-2025 18:46:23","21-06-2025 18:31:25","21-06-2025 18:37:46","Cas=
caded Incident from TTO5477835","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","466781","21-06-2025 18=
:46:23","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005313822","M=
fou OCM","IHS_YND_674","21-06-2025 18:38:33","21-06-2025 18:31:25","21-06-2=
025 18:37:46","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","gaelle.njiofack@matech-cameroun.c=
om","429","21-06-2025 18:38:33","MATECH CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0005313769","Nsi=
meyong Shell","","21-06-2025 18:26:00","21-06-2025 18:13:54","21-06-2025 18=
:41:56","Grid outage, site went down due to no MDGE //He deployed MDGE, and=
 Grid returned","MINKA NICOLAS","Grid Supply","Passive","Grid","National Gr=
id - Grid Outage Issue","Grid outage, site went down due to no MDGE //He de=
ployed MDGE, and Grid returned","gaelle.njiofack@matech-cameroun.com","727"=
,"21-06-2025 18:26:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_070","NOCINC0005313733","Efoulan"=
,"","21-06-2025 18:20:42","21-06-2025 18:13:34","21-06-2025 18:37:45","Casc=
aded Incident from TTO5477699","MINKA NICOLAS","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down due to no M=
DGE //He deployed MDGE, and Grid returned","system","467821","21-06-2025 18=
:20:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0005313735","Scalom",=
"","21-06-2025 18:20:42","21-06-2025 18:13:34","21-06-2025 18:37:45","Casca=
ded Incident from TTO5477699","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, site went down due to no MDGE=
 //He deployed MDGE, and Grid returned","system","467823","21-06-2025 18:20=
:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0005313734","Scalom-I=
HS","","21-06-2025 18:20:42","21-06-2025 18:13:34","21-06-2025 18:37:45","C=
ascaded Incident from TTO5477699","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down due to no MDGE //He d=
eployed MDGE, and Grid returned","system","467822","21-06-2025 18:20:42","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0005313702","S=
hell-Nsimeyong","IHS_YND_070, IHS_YND_505, IHS_YND_071","21-06-2025 18:17:4=
9","21-06-2025 18:13:34","21-06-2025 18:37:45","Grid outage, site went down=
 due to no MG //He deployed MG, and Grid returned","MINKA NICOLAS","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, si=
te went down due to no MG //He deployed MG, and Grid returned","gaelle.njio=
fack@matech-cameroun.com","256","21-06-2025 18:17:49","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005313515","MBA=
LNGONG LYCEE","","21-06-2025 17:49:41","21-06-2025 17:44:35","22-06-2025 08=
:37:29","Grid outage, landlord stopped the Gen because it's too noisy// Gri=
d return","Fanda Brice","Access Denial","Lease Or Legal","Landlord Related =
Issues","Access Issue - Land Lord","Grid outage, landlord stopped the Gen b=
ecause it's too noisy// Grid return","loic.noumsi@matech-cameroun.com","307=
","21-06-2025 17:49:41","MATECH CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0005313492","S=
calom-IHS","","21-06-2025 17:44:56","21-06-2025 16:52:37","21-06-2025 17:38=
:39","Grid outage;no space to deploy mobil Gen //Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage;no sp=
ace to deploy mobil Gen //Grid return","gaelle.njiofack@matech-cameroun.com=
","3141","21-06-2025 17:44:56","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005313335","A=
hala","IHS_YND_698","21-06-2025 17:19:03","21-06-2025 17:10:58","21-06-2025=
 18:30:10","Grid outage ,site went down because Gen failed to start due to =
ALARM *High temp*//He reset the Gen card and manually started the Gen","MIN=
KA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage ,site went down because Gen failed to start due to ALARM *High=
 temp*//He reset the Gen card and manually started the Gen","gaelle.njiofac=
k@matech-cameroun.com","486","21-06-2025 17:19:03","MATECH CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0005313334","E=
BOM","","21-06-2025 17:18:31","21-06-2025 17:10:58","21-06-2025 18:30:10","=
","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage ,site went down because Gen failed to start due to ALAR=
M *High temp*//He reset the Gen card and manually started the Gen","gaelle.=
njiofack@matech-cameroun.com","471493","21-06-2025 17:18:31","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005313104","N=
kolbong","","21-06-2025 16:43:29","21-06-2025 16:36:19","21-06-2025 17:41:5=
5","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Ge=
n started and stopped due to Gen overload(22kva//350A) // Grid return","gae=
lle.njiofack@matech-cameroun.com","431","21-06-2025 16:43:29","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005313067","M=
vog-Manga","","21-06-2025 16:35:42","21-06-2025 16:31:37","21-06-2025 16:36=
:40","Active// No power issue on site. Site on Grid Ubai=3D54.3 V, The FME =
TX Lionel Adjep/655184876/ From Huawei is informed. ","Albran Byorel","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue on site. Site on Grid Ubai=3D54.3 V, The FME=
 TX Lionel Adjep/655184876/ From Huawei is informed. ","gaelle.njiofack@mat=
ech-cameroun.com","247","21-06-2025 16:35:42","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005313054","M=
essassi 2","","21-06-2025 16:33:58","21-06-2025 16:26:44","21-06-2025 17:50=
:15","Grid outage site went down because Gen failed to start due PWC ZTE dy=
sfonctionned // He bypassed ATS and started Gen manually","Fabrice Pouakam"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage site went down because Gen failed to start due PWC ZTE dysfonctio=
nned // He bypassed ATS and started Gen manually","gaelle.njiofack@matech-c=
ameroun.com","436","21-06-2025 16:33:58","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005313029","Bit=
eng-Maetur","","21-06-2025 16:29:20","21-06-2025 16:22:14","21-06-2025 19:0=
8:25","Grid outage site went down because Gen failed to start due PWC ZTE d=
ysfunctioned // He reset the PWC and site on Grid","Mba Lazare Herve","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid out=
age site went down because Gen failed to start due PWC ZTE dysfunctioned //=
 He reset the PWC and site on Grid","loic.noumsi@matech-cameroun.com","427"=
,"21-06-2025 16:29:20","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005312985","Ron=
d Point Express1114","","21-06-2025 16:22:54","21-06-2025 16:14:41","21-06-=
2025 16:32:48","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Grid returned","loic.noumsi@matech-camerou=
n.com","494","21-06-2025 16:22:54","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005312861","E=
lig Edzoa","","21-06-2025 15:59:45","21-06-2025 15:54:31","21-06-2025 16:25=
:57","Grid outage, site down because generator did not start due to flood a=
fter the rain. // he started the MG (20KVA) with a can of fuel.","Delor Tel=
ezing","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage, site down because generator did not start due to flood after t=
he rain. // he started the MG (20KVA) with a can of fuel.","gaelle.njiofack=
@matech-cameroun.com","315","21-06-2025 15:59:45","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005312832","TON=
GOLO SNEC","","21-06-2025 15:56:06","21-06-2025 15:49:59","21-06-2025 16:27=
:40","Grid outage, site went down because gen failed to start due to gen co=
ntactor faulty // He bypassed it and site on Grid","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, sit=
e went down because gen failed to start due to gen contactor faulty // He b=
ypassed it and site on Grid","loic.noumsi@matech-cameroun.com","368","21-06=
-2025 15:56:06","MATECH CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0005312765","Bas=
tos Bir","","21-06-2025 15:45:47","21-06-2025 15:40:43","21-06-2025 17:58:1=
9","Site went down because Team SFM (694271069) is on site for PM (Swap of =
PWC) // End of work","Mboua Thierry","Installation Activity","Passive","Pla=
nned Activity","Installation Activity","Site went down because Team SFM (69=
4271069) is on site for PM (Swap of PWC) // End of work","loic.noumsi@matec=
h-cameroun.com","305","21-06-2025 15:45:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005312756","Emana Ly=
cee","","21-06-2025 15:43:18","21-06-2025 15:36:48","21-06-2025 19:24:22","=
Cascaded Incident from TTO5476612","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down due t=
o Gen overload(20kva, 260A) //Grid return","system","1332555","21-06-2025 1=
5:43:18","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005312739","E=
mana lycee 2","IHS_YND_274","21-06-2025 15:41:55","21-06-2025 15:36:48","21=
-06-2025 19:24:22","Grid outage, Site went down due to Gen overload(20kva, =
260A) //Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Grid outage, Site went down due to Gen overload(20kv=
a, 260A) //Grid return","gaelle.njiofack@matech-cameroun.com","308","21-06-=
2025 15:41:55","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005312694","E=
toudi","","21-06-2025 15:40:27","21-06-2025 15:32:21","21-06-2025 15:47:56"=
,"	Grid outage, site went down before Gen start due to poor battery backup =
// Grid returned","Fabrice Pouakam","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","	Grid outage, site went down before Ge=
n start due to poor battery backup // Grid returned","gaelle.njiofack@matec=
h-cameroun.com","487","21-06-2025 15:40:27","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005312683","N=
yom OCM","","21-06-2025 15:38:46","21-06-2025 15:31:39","21-06-2025 15:56:2=
5","Our FME Fabrice confirm us that Biganstile (650631358/Dowen) is on site=
 For Swap of PWC // End of work","Fabrice Pouakam","Equipment Replacement",=
"Passive","Planned Activity","Planned Activity - Passive","site down due to=
 work of Biganstile (650631358/Dowen) who is on site For Swap of PWC // End=
 of work","gaelle.njiofack@matech-cameroun.com","428","21-06-2025 15:38:46"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005312425","Mfou EPC=
","","21-06-2025 15:23:29","21-06-2025 15:13:59","21-06-2025 15:25:59","Cas=
caded Incident from TTO5476278","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","1226225","21-06-2025 1=
5:23:29","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005312417","M=
fou OCM","IHS_YND_674","21-06-2025 15:22:39","21-06-2025 15:13:59","21-06-2=
025 15:25:59","Grid Outage, Site Down before gen Started due to poor backup=
 ","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid Outage, Site Down before gen Started due to poo=
r backup //Grid returned","gaelle.njiofack@matech-cameroun.com","520","21-0=
6-2025 15:22:39","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005312385","M=
ontee-Des-Soeurs","","21-06-2025 15:16:13","21-06-2025 15:14:57","21-06-202=
5 16:12:52","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid stabilised","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) =
// Grid stabilised","gaelle.njiofack@matech-cameroun.com","78","21-06-2025 =
15:16:13","MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0005312331","Mes=
sassi okolo","","21-06-2025 15:07:09","21-06-2025 15:00:03","21-06-2025 17:=
21:30","Grid outage, site went down because Gen failed to start due to Gen =
card faulty // He reset it, site on GRID","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went dow=
n because Gen failed to start due to Gen card faulty // He reset it, site o=
n GRID","gaelle.njiofack@matech-cameroun.com","427","21-06-2025 15:07:09","=
MATECH CMR"
"Closed Complete","Site Down","T1590","IHS_YND_141","NOCINC0005312261","New=
-Marche-Melen","","21-06-2025 14:54:25","21-06-2025 14:48:20","21-06-2025 1=
6:04:34","Site went down because Gen failed to start due to Grid fluctuatio=
ns // He bypassed Grid  and started Gen manually","Paul BIBOUM","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Site went do=
wn because Gen failed to start due to Grid fluctuations // He bypassed Grid=
  and started Gen manually","gaelle.njiofack@matech-cameroun.com","366","21=
-06-2025 14:54:25","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005312241","Awa=
e Ewonkan","","21-06-2025 14:51:07","21-06-2025 14:47:55","21-06-2025 14:52=
:41","	Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)I=
HS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","	Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","gaelle.njiofack@matech-cameroun.com","193","21-06-2025 14:51:07","MAT=
ECH CMR"
"Closed Complete","Site Down","T0217","IHS_YND_018","NOCINC0005312075","P&T=
 Building","","21-06-2025 14:28:54","21-06-2025 14:23:46","21-06-2025 20:13=
:31","Grid Outage No Space to deploy a MDG // Grid returned","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spa=
ce to deploy a MDG // Grid returned","gaelle.njiofack@matech-cameroun.com",=
"308","21-06-2025 14:28:54","MATECH CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0005312066","ENA=
M","","21-06-2025 14:27:34","21-06-2025 14:21:27","21-06-2025 20:17:14","Gr=
id Outage No Space to deploy a MDG // Grid returned","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space to de=
ploy a MDG // Grid returned","gaelle.njiofack@matech-cameroun.com","368","2=
1-06-2025 14:27:34","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005312046","TON=
GOLO SNEC","","21-06-2025 14:23:49","21-06-2025 14:16:37","21-06-2025 15:12=
:38","Grid outage, site went down because gen failed to start due to gen co=
ntactor faulty // He bypassed it and site on Grid","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, sit=
e went down because gen failed to start due to gen contactor faulty // He b=
ypassed it and site on Grid","gaelle.njiofack@matech-cameroun.com","433","2=
1-06-2025 14:23:49","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005312001","ESS=
OS OASIS 1111","","21-06-2025 14:12:44","21-06-2025 14:10:23","21-06-2025 1=
6:20:11","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A) // Grid returned","cedric.tiani@matech-cameroun.com","142","21-06-2025 =
14:12:44","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005311813","Par=
adis Hotel","","21-06-2025 13:42:52","21-06-2025 13:37:35","21-06-2025 15:3=
5:44","Site went down due to  01/04 rectier faulty // he reset rectifiers a=
nd removed what was faulty","Siligap Boris","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down due to  01/04 rectier faulty /=
/ he reset rectifiers and removed what was faulty","cedric.tiani@matech-cam=
eroun.com","318","21-06-2025 13:42:52","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005311804","EMA=
NA BILICK CITY","","21-06-2025 13:41:33","21-06-2025 13:38:26","21-06-2025 =
18:11:50","Grid outage, site down because site behaves as Grid only site (G=
en Noise) // Grid returned","Fabrice Pouakam","Access Denial","Lease Or Leg=
al","Landlord Related Issues","Access Issue - Land Lord","Grid outage, site=
 down because site behaves as Grid only site (Gen Noise) // Grid returned",=
"cedric.tiani@matech-cameroun.com","188","21-06-2025 13:41:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005311685","Matsari"=
,"","21-06-2025 13:20:10","21-06-2025 13:15:21","21-06-2025 13:20:11","Casc=
aded Incident from TTO5475452","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by Ngoum not manage by IHS",=
"system","478400","21-06-2025 13:20:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005311686","Yoko MTN=
","","21-06-2025 13:20:10","21-06-2025 13:15:21","21-06-2025 13:20:11","Cas=
caded Incident from TTO5475452","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Site impacted by Ngoum not manage by IHS"=
,"system","478400","21-06-2025 13:20:10","MATECH CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0005311682","MBI=
MBIM","IHS_YND_460, IHS_YND_473","21-06-2025 13:18:51","21-06-2025 13:15:21=
","21-06-2025 13:20:11","Site impacted by Ngoum not manage by IHS","Parker =
Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","A=
ffected by 3rd Party Site","Site impacted by Ngoum not manage by IHS","cedr=
ic.tiani@matech-cameroun.com","211","21-06-2025 13:18:51","MATECH CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0005311673","Ngo=
uetou","","21-06-2025 13:15:34","21-06-2025 13:13:24","21-06-2025 13:15:40"=
,"Active // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Grego=
ire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gregoire (654=
547479) from Huawei is informed","cedric.tiani@matech-cameroun.com","131","=
21-06-2025 13:15:34","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005311629","A=
hala","","21-06-2025 13:06:18","21-06-2025 13:03:02","21-06-2025 13:06:02",=
"Grid outage ,site went down because Gen failed to start due to ALARM *High=
 temp*//He reset the Gen card and manually started the Gen","MINKA NICOLAS"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e ,site went down because Gen failed to start due to ALARM *High temp*//He =
reset the Gen card and manually started the Gen","cedric.tiani@matech-camer=
oun.com","196","21-06-2025 13:06:18","MATECH CMR"
"Closed Complete","Site Down","CTR_255","IHS_YND_286","NOCINC0005311603","D=
agobert","","21-06-2025 13:03:23","21-06-2025 12:56:12","21-06-2025 13:03:2=
8","	Active: No power issue, site is on Grid with Ubaie=3D54,6V, FME TX Moh=
amadou//691144435 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active: No power issue, site is on Grid with Ubaie=3D54,6V, FME TX M=
ohamadou//691144435 from Huawei is informed","cedric.tiani@matech-cameroun.=
com","432","21-06-2025 13:03:23","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005311304","Eto=
udi2","","21-06-2025 12:38:29","21-06-2025 12:33:14","21-06-2025 13:04:09",=
"Grid outage , site went down before Gen started due to poor battery backup=
// Gen automatically started","Delor Telezing","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage , site went dow=
n before Gen started due to poor battery backup// Gen automatically started=
","cedric.tiani@matech-cameroun.com","316","21-06-2025 12:38:29","MATECH CM=
R"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005311259","Nko=
l-Mbanda","","21-06-2025 12:31:27","21-06-2025 12:26:04","21-06-2025 13:39:=
04","Site went down due to disjuction CB(125A) that tripped MTN //He rearme=
d it","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power C=
abinet - Circuit Breaker Issue","Site went down due to disjuction CB(125A) =
that tripped MTN //He rearmed it","cedric.tiani@matech-cameroun.com","324",=
"21-06-2025 12:31:27","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005311129","E=
ssomba","","21-06-2025 12:11:54","21-06-2025 11:54:37","21-06-2025 12:39:19=
","Grid outage,Site went down because Gen failed to start due to PWC ZTE dy=
sfonction //He reset it and site on Gen","Mba Lazare Herve","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage,Site w=
ent down because Gen failed to start due to PWC ZTE dysfonction //He reset =
it and site on Gen","cedric.tiani@matech-cameroun.com","1039","21-06-2025 1=
2:11:54","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005311027","A=
hala","","21-06-2025 11:53:52","21-06-2025 11:52:41","21-06-2025 12:16:59",=
"Grid outage ,site went down because Gen failed to start due to ALARM *High=
 temp*//He reset the Gen card and manually started the Gen","MINKA NICOLAS"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e ,site went down because Gen failed to start due to ALARM *High temp*//He =
reset the Gen card and manually started the Gen","cedric.tiani@matech-camer=
oun.com","72","21-06-2025 11:53:52","MATECH CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0005310985","R=
d-Pt-Express","","21-06-2025 11:48:30","21-06-2025 11:41:16","21-06-2025 16=
:19:33","Grid only site.no space to deploy mobile gen // grid power restore=
d","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid only site.no space to deploy mobile gen // grid power restored","cedric=
.tiani@matech-cameroun.com","435","21-06-2025 11:48:30","MATECH CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0005310953","Nsi=
meyong Shell","","21-06-2025 11:46:28","21-06-2025 11:36:59","21-06-2025 16=
:54:48","Grid outage, site went down due to no MDGE //He deployed MDGE, SIT=
E on GEN","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - G=
rid Outage Issue","Grid outage, site went down due to no MDGE //He deployed=
 MDGE, SITE on GEN","cedric.tiani@matech-cameroun.com","570","21-06-2025 11=
:46:28","MATECH CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0005310914","S=
hell-Nsimeyong","IHS_YND_070, IHS_YND_505, IHS_YND_071","21-06-2025 11:40:5=
7","21-06-2025 11:36:45","21-06-2025 16:50:08","Grid outage, site went down=
 due to no MG //He deployed MG, SITE on GEN","MINKA NICOLAS","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, site wen=
t down due to no MDGE //He deployed MDGE, SITE on GEN","cedric.tiani@matech=
-cameroun.com","253","21-06-2025 11:40:57","MATECH CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0005310902","S=
calom-IHS","","21-06-2025 11:38:16","21-06-2025 11:36:45","21-06-2025 16:50=
:08","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid outage, site went down due to no MDGE //He deployed MDGE, SITE on GEN"=
,"cedric.tiani@matech-cameroun.com","484131","21-06-2025 11:38:16","MATECH =
CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005310900","E=
foulan","","21-06-2025 11:37:39","21-06-2025 11:36:45","21-06-2025 16:50:08=
","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Grid outage, site went down due to no MDGE //He deployed MDGE, SI=
TE on GEN","cedric.tiani@matech-cameroun.com","484132","21-06-2025 11:37:39=
","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0005310895","S=
calom","","21-06-2025 11:36:42","21-06-2025 11:36:45","21-06-2025 16:50:08"=
,"","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Grid outage, site went down due to no MDGE //He deployed MDGE, SITE =
on GEN","cedric.tiani@matech-cameroun.com","484131","21-06-2025 11:36:42","=
MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0005310876","Clu=
b France","","21-06-2025 11:33:15","21-06-2025 11:32:04","21-06-2025 16:18:=
44","Grid only site, No space to deploy a MDG // Grd return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid only site, No=
 space to deploy a MDG // Grd return","cedric.tiani@matech-cameroun.com","7=
2","21-06-2025 11:33:15","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005310847","M=
anguier","","21-06-2025 11:30:51","21-06-2025 11:16:35","21-06-2025 11:53:5=
6","Grid outage, site went down before gen start due to poor battery backup=
 // Gen Started Automatically","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen Started Automatically=
","cedric.tiani@matech-cameroun.com","857","21-06-2025 11:30:51","MATECH CM=
R"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005310772","Nko=
lbisson IITA LP","","21-06-2025 11:16:17","21-06-2025 11:15:08","21-06-2025=
 11:30:49","No power issue site on grid with U=3D53.2v Mohamadou(69114435) =
from Huawei is informed","","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D53.2v Mohamadou(69114435) from Huawei is informed","cedric.tiani@matech-=
cameroun.com","70","21-06-2025 11:16:17","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0005310762","B=
iyemassi LAC","","21-06-2025 11:15:27","21-06-2025 11:12:08","22-06-2025 08=
:04:29","Grid only site, no space to deploy MDGE // rid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e, no space to deploy MDGE // rid returned","cedric.tiani@matech-cameroun.c=
om","200","21-06-2025 11:15:27","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005310742","Acc=
acia New","","21-06-2025 11:13:01","21-06-2025 11:11:39","21-06-2025 16:27:=
00","Grid only site, no space to deploy MDG // Grid returned","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid only site, n=
o space to deploy MDG // Grid returned","cedric.tiani@matech-cameroun.com",=
"84","21-06-2025 11:13:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0005310733","Ekoumdou=
m OCM","","21-06-2025 11:11:55","21-06-2025 11:06:24","21-06-2025 11:47:24"=
,"Cascaded Incident from TTO5474355","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,Site went down becaus=
e Gen failed to start due to Hybrid system dysfunction//He reset it and man=
ually started Gen","system","485901","21-06-2025 11:11:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005310732","MEHANDAN=
","","21-06-2025 11:11:55","21-06-2025 11:06:24","21-06-2025 11:47:24","Cas=
caded Incident from TTO5474355","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,Site went down because Gen=
 failed to start due to Hybrid system dysfunction//He reset it and manually=
 started Gen","system","485900","21-06-2025 11:11:55","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005310712","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","21-06-2025 11:09:36","21=
-06-2025 11:06:24","21-06-2025 11:47:24","Grid outage,Site went down becaus=
e Gen failed to start due to Hybrid system dysfunction//He reset it and man=
ually started Gen","Albran Byorel","Equipment Repair","Passive","Hybrid","H=
ybrid Module","Grid outage,Site went down because Gen failed to start due t=
o Hybrid system dysfunction//He reset it and manually started Gen","cedric.=
tiani@matech-cameroun.com","193","21-06-2025 11:09:36","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005310705","O=
dza II OCM","","21-06-2025 11:08:32","21-06-2025 11:06:24","21-06-2025 11:4=
7:24","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage,Site went down because Gen failed to start due to=
 Hybrid system dysfunction//He reset it and manually started Gen","cedric.t=
iani@matech-cameroun.com","485901","21-06-2025 11:08:32","MATECH CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0005310380","M=
ontee-Jouvence","","21-06-2025 10:27:22","21-06-2025 10:26:12","21-06-2025 =
10:27:37","ACTIVE//No power issue u=3D54.2V site on GRID,The Tx FME Hosiah/=
/699699694 is informed","Hyemafo Gildas","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue=
 u=3D54.2V site on GRID,The Tx FME Hosiah//699699694 is informed","cedric.t=
iani@matech-cameroun.com","71","21-06-2025 10:27:22","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005310285","NKO=
MKANA ELIZA HOTEL","","21-06-2025 10:13:39","21-06-2025 10:12:28","21-06-20=
25 16:02:13","Site went down due to PWC Overloaded(9Kilo//140A) and SS IHS =
Bernard Atangana confirmed // Grid stabilised","","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due to PWC Ov=
erloaded(9Kilo//140A) and SS IHS Bernard Atangana confirmed // Grid stabili=
sed","cedric.tiani@matech-cameroun.com","72","21-06-2025 10:13:39","MATECH =
CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005310269","E=
mana lycee 2","","21-06-2025 10:09:21","21-06-2025 10:07:10","21-06-2025 10=
:10:33","Grid Outage, Site went down before Gen start due to poor backup //=
 GRID RETURN","Fabrice Pouakam","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid Outage, Site went down before Gen sta=
rt due to poor backup // GRID RETURN","cedric.tiani@matech-cameroun.com","1=
33","21-06-2025 10:09:21","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005310241","M=
ontee-Des-Soeurs","","21-06-2025 10:03:53","21-06-2025 09:59:31","21-06-202=
5 11:10:08","Grid outage ,site down due to Gen overload (15 KVA/210 A)// Gr=
id return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A)// Gri=
d return","cedric.tiani@matech-cameroun.com","263","21-06-2025 10:03:53","M=
ATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005310160","ESS=
OS OASIS 1111","","21-06-2025 09:49:50","21-06-2025 09:44:42","21-06-2025 0=
9:59:41","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 Grid returned	","Siligap Boris","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","
Grid outage, Site went down because Gen overload (17kva, 250A) // Grid retu=
rned=09
","cedric.tiani@matech-cameroun.com","309","21-06-2025 09:49:50","MATECH CM=
R"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005310050","Beh=
ind P T school Yde","","21-06-2025 09:31:40","21-06-2025 09:02:55","21-06-2=
025 13:26:59","Grid outage ,site went down due to AVR faulty // Grid return=
ed","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - AVR","Gri=
d outage ,site went down due to AVR faulty // Grid returned","cedric.tiani@=
matech-cameroun.com","1726","21-06-2025 09:31:40","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005309999","M=
ontee-Des-Soeurs","","21-06-2025 09:25:13","21-06-2025 09:22:56","21-06-202=
5 09:42:50","Grid outage ,site down due to Gen overload (15 KVA/210 A) //Gr=
id returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) //G=
rid returned","cedric.tiani@matech-cameroun.com","138","21-06-2025 09:25:13=
","MATECH CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0005309930","SOA=
 UNIVERSITY STADIUM","","21-06-2025 09:14:31","21-06-2025 09:13:18","21-06-=
2025 09:23:57","Grid outage,Site went down because Gen failed to start due =
to  PWC  ZTE dysfonction // Grid return","Siligap Boris","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid outage,Site went=
 down because Gen failed to start due to PWC ZTE dysfonction // Grid return=
","cedric.tiani@matech-cameroun.com","74","21-06-2025 09:14:31","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005309887","Elig-Edz=
oa","","21-06-2025 09:05:12","21-06-2025 08:53:33","21-06-2025 10:17:13","C=
ascaded Incident from TTO5473397","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage gen failed to start due to battery GE=
 discharged causing by static charger faulty//Gen manually started with ext=
ernal battery","system","486973","21-06-2025 09:05:12","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005309860","Nta=
ba","IHS_YND_133","21-06-2025 08:58:45","21-06-2025 08:53:33","21-06-2025 1=
0:21:37","Grid outage gen failed to start due to battery GE discharged caus=
ing by static charger faulty//Gen manually started with external battery","=
Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Generator B=
attery","Grid outage gen failed to start due to battery GE discharged causi=
ng by static charger faulty//Gen manually started with external battery","c=
edric.tiani@matech-cameroun.com","313","21-06-2025 08:58:45","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005309837","Nsi=
malen MTN","","21-06-2025 08:54:51","21-06-2025 08:52:39","21-06-2025 10:18=
:22","Grid outage, site went down because Gen failed to start with alarm Lo=
w oil pressure  // He added oil nd Gen manually started","Albran Byorel","E=
quipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outag=
e, site went down because Gen failed to start with alarm Low oil pressure  =
// He added oil nd Gen manually started","cedric.tiani@matech-cameroun.com"=
,"133","21-06-2025 08:54:51","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005309830","ESS=
OS OASIS 1111","","21-06-2025 08:53:16","21-06-2025 08:52:03","21-06-2025 0=
9:07:49","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 GRid power return","Siligap Boris","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage, Site went down because Gen overload (17kva=
, 250A) // GRid power return","cedric.tiani@matech-cameroun.com","73","21-0=
6-2025 08:53:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005309825","Emana Ly=
cee","","21-06-2025 08:52:44","21-06-2025 08:49:40","21-06-2025 08:52:16","=
Cascaded Incident from TTO5473350","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, Site went down befor=
e Gen start due to poor backup // Gen Started Automatically","system","4871=
96","21-06-2025 08:52:44","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005309818","E=
mana lycee 2","IHS_YND_274","21-06-2025 08:52:02","21-06-2025 08:49:40","21=
-06-2025 08:52:16","Grid Outage, Site went down before Gen start due to poo=
r backup // Gen Started Automatically","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site=
 went down before Gen start due to poor backup // Gen Started Automatically=
","cedric.tiani@matech-cameroun.com","144","21-06-2025 08:52:02","MATECH CM=
R"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005309771","M=
essassi okolo","","21-06-2025 08:41:56","21-06-2025 08:19:39","21-06-2025 0=
9:28:26","Grid fluctuation , site went down before Gen started due to poor =
battery backup// Gen manually started","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid fluctuation =
, site went down before Gen started due to poor battery backup// Gen manual=
ly started","cedric.tiani@matech-cameroun.com","1339","21-06-2025 08:41:56"=
,"MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005309754","Nsa=
m Sofavinc","IHS_YND_732","21-06-2025 08:39:44","21-06-2025 08:35:37","21-0=
6-2025 08:41:08","Grid Outage, Site went down before Gen start due to poor =
backup // Gen Started Automatically","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site wen=
t down before Gen start due to poor backup // Gen Started Automatically","c=
edric.tiani@matech-cameroun.com","247","21-06-2025 08:39:44","MATECH CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0005309746","Nsa=
m escale LP","","21-06-2025 08:38:16","21-06-2025 08:35:37","21-06-2025 08:=
41:08","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"Grid Outage, Site went down before Gen start due to poor backup // Gen St=
arted Automatically","cedric.tiani@matech-cameroun.com","488023","21-06-202=
5 08:38:16","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005309692","EMA=
NA BILICK CITY","","21-06-2025 08:27:40","21-06-2025 08:23:06","21-06-2025 =
09:29:32","Access issues due to landlord(Landlord has forbidden to start th=
e Gen due to noise // grid return","Fabrice Pouakam","Access Denial","Lease=
 Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access iss=
ues due to landlord(Landlord has forbidden to start the Gen due to noise //=
 grid return","cedric.tiani@matech-cameroun.com","275","21-06-2025 08:27:40=
","MATECH CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0005309664","Eto=
udi 2","","21-06-2025 08:19:17","21-06-2025 08:18:04","21-06-2025 08:20:52"=
,"Grid outage , site went down before Gen started due to poor battery backu=
p// Gen automatically  started","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage , site went =
down before Gen started due to poor battery backup// Gen automatically  sta=
rted","cedric.tiani@matech-cameroun.com","74","21-06-2025 08:19:17","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005309628","O=
dza-PK10","","21-06-2025 08:09:47","21-06-2025 07:59:59","21-06-2025 10:22:=
06","Grid outage,Site went down because Gen failed to start due to Hybrid s=
ystem dysfunction//He reset it and manually started Gen","Albran Byorel","E=
quipment Repair","Passive","Hybrid","Hybrid Module","Grid outage,Site went =
down because Gen failed to start due to Hybrid system dysfunction//He reset=
 it and manually started Gen","cedric.tiani@matech-cameroun.com","589","21-=
06-2025 08:09:47","MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005309620","Mfa=
ndena","","21-06-2025 08:09:01","21-06-2025 08:07:49","21-06-2025 09:05:10"=
,"Grid outage,Site went down because GEN failed to start  due to Alarm *Und=
er frequency*//He reset the Gen card and manually started Gen","Delor Telez=
ing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage,Site went down because GEN failed to start  due to Alarm *Under frequ=
ency*//He reset the Gen card and manually started Gen","cedric.tiani@matech=
-cameroun.com","73","21-06-2025 08:09:01","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005309536","C=
arrefourt Nkomo","","21-06-2025 07:48:54","21-06-2025 07:39:42","21-06-2025=
 10:52:42","Reported No power issue site on Grid with Ubaie : 51.7 V ,The F=
ME TX Henry (699949693) from Huawei is informed","Mba Lazare Herve","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Reported No power issue site on Grid with Ubaie : 51.7 V ,The FME TX H=
enry (699949693) from Huawei is informed","cedric.tiani@matech-cameroun.com=
","553","21-06-2025 07:48:54","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005309384","Ron=
d Point Express1114","","21-06-2025 07:15:06","21-06-2025 07:13:54","21-06-=
2025 07:21:58","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen start automatically","cedric=
.tiani@matech-cameroun.com","73","21-06-2025 07:15:06","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005309381","O=
lembe-Terminus","","21-06-2025 07:14:15","21-06-2025 07:05:44","21-06-2025 =
07:48:41","Grid outage site went down because Gen failed to start due to Ge=
n card faulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen=
 failed to start due to Gen card faulty // Grid return","cedric.tiani@matec=
h-cameroun.com","513","21-06-2025 07:14:15","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005309360","Nko=
lfoulou CSD MTN","","21-06-2025 07:08:35","21-06-2025 07:02:06","21-06-2025=
 09:17:55","No power issue on site U=3D53v site on gen synphorien 675295205=
 of huawei is informed","Siligap Boris","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D53v site on gen synphorien 675295205 of huawei is informed","cedric.tia=
ni@matech-cameroun.com","389","21-06-2025 07:08:35","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005309114","Ebo=
go","","21-06-2025 06:00:37","21-06-2025 05:55:10","21-06-2025 06:00:10","N=
o power issue on site U=3D52,2V site on Grid. Synphorien 675295205 of Huawe=
i is informed","Siligap Boris","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52,2V=
 site on Grid. Synphorien 675295205 of Huawei is informed","franck.nkomot@m=
atech-cameroun.com","328","21-06-2025 06:00:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_175","NOCINC0005308757","Nkomo","=
","21-06-2025 03:28:58","21-06-2025 01:10:46","21-06-2025 02:38:12","Backtr=
aking:  No power issue site on grid with U=3D53.5V Lionel Adjeck (655184876=
) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Backtraking:  No =
power issue site on grid with U=3D53.5V Lionel Adjeck (655184876) from Huaw=
ei is informed","cedric.tiani@matech-cameroun.com","8293","21-06-2025 03:28=
:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005308603","Carrefou=
r Ayissi Ele","","21-06-2025 02:43:05","21-06-2025 02:36:07","21-06-2025 03=
:07:07","Cascaded Incident from TTO5472020","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage , site down be=
cause Gen CB was down // Gen CB rearmed site left on Gen.","system","509308=
","21-06-2025 02:43:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005308604","Nkol-Meb=
anga","","21-06-2025 02:43:05","21-06-2025 02:36:07","21-06-2025 03:07:07",=
"Cascaded Incident from TTO5472020","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage , site down because Ge=
n CB was down // Gen CB rearmed site left on Gen.","system","509307","21-06=
-2025 02:43:05","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005308561","S=
aa","IHS_YND_810, IHS_YND_809","21-06-2025 02:40:17","21-06-2025 02:31:07",=
"21-06-2025 03:07:07","Grid outage , site down because Gen CB was down // G=
en CB rearmed site left on Gen.","Parker Tchoup","Equipment Repair","Passiv=
e","Control Panel","Circuit Breaker - Off By Unknown","Grid outage , site d=
own because Gen CB was down // Gen CB rearmed site left on Gen.","cedric.ti=
ani@matech-cameroun.com","551","21-06-2025 02:40:17","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005308224","Djo=
nassi-Yde","","21-06-2025 00:26:56","21-06-2025 00:21:40","21-06-2025 01:53=
:40","Access issue at night due to landlord. Site went down due to 03/04 re=
ctifier faulty on site. Site stabilized","Fabrice Pouakam","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Access issue at night due to l=
andlord. Site went down due to 03/04 rectifier faulty on site. Site stabili=
zed","ludivine.ngamaleu@ihstowers.com","317","21-06-2025 00:26:56","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005308211","Mfou EPC=
","","21-06-2025 00:22:30","21-06-2025 00:19:39","21-06-2025 00:40:46","Cas=
caded Incident from TTO5471578","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","1214940","21-06-2025 0=
0:22:30","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005308206","M=
fou OCM","IHS_YND_674","21-06-2025 00:21:49","21-06-2025 00:19:39","21-06-2=
025 00:40:46","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","cedric.tiani@matech-cameroun.com"=
,"131","21-06-2025 00:21:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005308085","Mfou EPC=
","","20-06-2025 23:57:48","20-06-2025 23:27:50","20-06-2025 23:36:50","Cas=
caded Incident from TTO5471369","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","513673","20-06-2025 23=
:57:48","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005308009","M=
fou OCM","IHS_YND_674","20-06-2025 23:31:03","20-06-2025 23:27:50","20-06-2=
025 23:36:50","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","cedric.tiani@matech-cameroun.com"=
,"193","20-06-2025 23:31:03","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005308004","Nko=
lnda","","20-06-2025 23:29:15","20-06-2025 23:26:05","20-06-2025 23:44:05",=
"Grid outage, site went down because gen start and stopped with high temp a=
larm // He added water and manually started the gen","Albran Byorel","Equip=
ment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level =
Issue","Grid outage, site went down because gen start and stopped with high=
 temp alarm // He added water and manually started the gen","ludivine.ngama=
leu@ihstowers.com","191","20-06-2025 23:29:15","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005307876","ODZ=
A BORNE 10","","20-06-2025 22:53:37","20-06-2025 22:43:59","21-06-2025 07:3=
8:44","Grid outage,site went down because Gen  started and stooped  with  A=
larm *OVER CURRENT*//He reset the Gen card and manually started Gen","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage,site went down because Gen  started and stooped  with  Alarm *OV=
ER CURRENT*//He reset the Gen card and manually started Gen","franck.nkomot=
@matech-cameroun.com","579","20-06-2025 22:53:37","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005307870","O=
LAMA","","20-06-2025 22:52:51","20-06-2025 22:47:44","20-06-2025 22:50:57",=
"No power issue on site Ubaie =3D54.5V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.5V site on Gen The TX FME Henri (699949693) from Huawei is=
 informed.","cedric.tiani@matech-cameroun.com","308","20-06-2025 22:52:51",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005307769","Mfou EPC=
","","20-06-2025 22:32:24","20-06-2025 22:25:18","20-06-2025 22:40:13","Cas=
caded Incident from TTO5471088","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","1214526","20-06-2025 2=
2:32:24","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005307763","M=
fou OCM","IHS_YND_674","20-06-2025 22:31:43","20-06-2025 22:25:18","20-06-2=
025 22:40:13","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","cedric.tiani@matech-cameroun.com"=
,"385","20-06-2025 22:31:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005307457","Eseka To=
wn","","20-06-2025 21:51:43","20-06-2025 21:44:19","20-06-2025 23:13:26","C=
ascaded Incident from TTO5470747","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage , site down because ,G=
en contactor did not stick // Gen contactor stuck ,site on gen","system","5=
19771","20-06-2025 21:51:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005307458","Song-bon=
g","","20-06-2025 21:51:43","20-06-2025 21:44:19","20-06-2025 23:13:26","Ca=
scaded Incident from TTO5470747","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage , site down because ,Ge=
n contactor did not stick // Gen contactor stuck ,site on gen","system","51=
9770","20-06-2025 21:51:43","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005307449","E=
seka OCM","IHS_YND_378, IHS_YND_453","20-06-2025 21:50:25","20-06-2025 21:4=
4:19","20-06-2025 23:13:26","Grid outage , site down because ,Gen contactor=
 did not stick // Gen contactor stuck ,site on gen","Kemeni Franklin","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage , s=
ite down because ,Gen contactor did not stick // Gen contactor stuck ,site =
on gen","gaelle.njiofack@matech-cameroun.com","367","20-06-2025 21:50:25","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0005307121","Nyom OCM=
","","20-06-2025 21:02:45","20-06-2025 20:50:42","20-06-2025 21:11:39","Cas=
caded Incident from TTO5470310","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D51=
.8V TX FME Symphorien (650257151) from Huawei is informed.","system","52291=
7","20-06-2025 21:02:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0005307122","Messassi=
 2","","20-06-2025 21:02:45","20-06-2025 20:50:42","20-06-2025 21:11:39","C=
ascaded Incident from TTO5470310","Fabrice Pouakam","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
51.8V TX FME Symphorien (650257151) from Huawei is informed.","system","522=
918","20-06-2025 21:02:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005307123","Nkolondo=
m","","20-06-2025 21:02:45","20-06-2025 20:50:42","20-06-2025 21:11:39","Ca=
scaded Incident from TTO5470310","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue site on grid with U=3D5=
1.8V TX FME Symphorien (650257151) from Huawei is informed.","system","5229=
16","20-06-2025 21:02:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0005307119","Messassi=
","","20-06-2025 21:02:44","20-06-2025 20:50:42","20-06-2025 21:11:39","Cas=
caded Incident from TTO5470310","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D51=
.8V TX FME Symphorien (650257151) from Huawei is informed.","system","52291=
5","20-06-2025 21:02:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0005307117","NKOLMEKO=
NG YDE","","20-06-2025 21:02:44","20-06-2025 20:50:42","20-06-2025 21:11:39=
","Cascaded Incident from TTO5470310","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on grid with =
U=3D51.8V TX FME Symphorien (650257151) from Huawei is informed.","system",=
"522912","20-06-2025 21:02:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0005307120","Nkozoa",=
"","20-06-2025 21:02:44","20-06-2025 20:50:42","20-06-2025 21:11:39","Casca=
ded Incident from TTO5470310","Fabrice Pouakam","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on grid with U=3D51.8=
V TX FME Symphorien (650257151) from Huawei is informed.","system","522915"=
,"20-06-2025 21:02:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0005307116","Ekombiti=
e","","20-06-2025 21:02:44","20-06-2025 20:50:42","20-06-2025 21:11:39","Ca=
scaded Incident from TTO5470310","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue site on grid with U=3D5=
1.8V TX FME Symphorien (650257151) from Huawei is informed.","system","5229=
14","20-06-2025 21:02:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0005307118","Olembe-T=
erminus","","20-06-2025 21:02:44","20-06-2025 20:50:42","20-06-2025 21:11:3=
9","Cascaded Incident from TTO5470310","Fabrice Pouakam","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue site on grid with=
 U=3D51.8V TX FME Symphorien (650257151) from Huawei is informed.","system"=
,"522913","20-06-2025 21:02:44","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005307055","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_280, IHS_YND_304","20-06-2025 20:53:49","20-06-2025 20:5=
0:42","21-06-2025 01:18:59","No power issue Ubaie:54.5V site on Grid,  TX F=
ME Symphorien (650257151) from Huawei is informed.","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue Ubaie:54.5V site on Grid,

TX FME Symphorien (650257151) from Huawei is informed.

","loic.noumsi@matech-cameroun.com","188","20-06-2025 20:53:49","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005306965","Matsari"=
,"","20-06-2025 20:44:56","20-06-2025 20:32:59","20-06-2025 20:57:44","Casc=
aded Incident from TTO5470148","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid Gen, Site went down due to fuel =
shortage// Refueling done by Edonde","system","523948","20-06-2025 20:44:56=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005306967","Yoko MTN=
","","20-06-2025 20:44:56","20-06-2025 20:32:59","20-06-2025 20:57:44","Cas=
caded Incident from TTO5470148","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen, Site went down due to fuel=
 shortage// Refueling done by Edonde","system","523946","20-06-2025 20:44:5=
6","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005306966","Ngoum","=
","20-06-2025 20:44:56","20-06-2025 20:32:59","20-06-2025 20:57:44","Cascad=
ed Incident from TTO5470148","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Hybrid Gen, Site went down due to fuel sh=
ortage// Refueling done by Edonde","system","523947","20-06-2025 20:44:56",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005306896","N=
gouetou","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_473","20-06-2025 2=
0:39:06","20-06-2025 20:32:59","20-06-2025 21:17:49","Hybrid Gen, Site went=
 down due to fuel shortage// Refueling done by Edonde","Parker Tchoup","Fue=
l Outage","Passive","Diesel","Diesel Outage","Hybrid Gen, Site went down du=
e to fuel shortage// Refueling done by Edonde","gaelle.njiofack@matech-came=
roun.com","369","20-06-2025 20:39:06","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005306773","S=
ous Prefecture","","20-06-2025 20:13:31","20-06-2025 20:06:20","20-06-2025 =
20:10:57","ACTIVE//No power issue site on Gen Ubaie =3D54.7V, The tx Huawei=
 Fulbert (654266068) is informed","Fanda Brice","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No powe=
r issue site on Gen Ubaie =3D54.7V, The tx Huawei Fulbert (654266068) is in=
formed","loic.noumsi@matech-cameroun.com","432","20-06-2025 20:13:31","MATE=
CH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005306597","Mvo=
g Betsi Hospital","","20-06-2025 19:54:52","20-06-2025 19:50:45","20-06-202=
5 19:56:57","Grid outage, Site went down before Gen start due to poor backu=
p // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Grid returned","loic.noumsi@matech-cameroun.c=
om","248","20-06-2025 19:54:52","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005305855","O=
dza II OCM","","20-06-2025 17:40:52","20-06-2025 17:38:45","20-06-2025 17:4=
1:17","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction//Site stabilised","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, site=
 went down because gen failed to start due to PWC ZTE malfunction//Site sta=
bilised","gaelle.njiofack@matech-cameroun.com","130","20-06-2025 17:40:52",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005305818","Ngouetou=
","","20-06-2025 17:36:14","20-06-2025 17:27:24","20-06-2025 18:35:38","Cas=
caded Incident from TTO5468936","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,Gen failed to start due t=
o fuel outage(Refueling have to be done by Edonde)//Grid returned","system"=
,"528136","20-06-2025 17:36:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005305817","Matsari"=
,"","20-06-2025 17:36:14","20-06-2025 17:27:24","20-06-2025 18:35:38","Casc=
aded Incident from TTO5468936","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage ,Gen failed to start due to=
 fuel outage(Refueling have to be done by Edonde)//Grid returned","system",=
"528136","20-06-2025 17:36:14","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0005305810","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","20-06-2025 17:34:30","20-=
06-2025 17:27:24","20-06-2025 18:35:38","Grid outage ,Gen failed to start d=
ue to fuel outage(Refueling have to be done by Edonde)//Grid returned","Par=
ker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage ,=
Gen failed to start due to fuel outage(Refueling have to be done by Edonde)=
//Grid returned","gaelle.njiofack@matech-cameroun.com","427","20-06-2025 17=
:34:30","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005305496","MBA=
LNGONG LYCEE","","20-06-2025 16:40:13","20-06-2025 16:36:05","21-06-2025 08=
:17:23","Grid outage, landlord stopped the Gen because it's too noisy// Gri=
d return","Fanda Brice","Access Denial","Lease Or Legal","Landlord Related =
Issues","Access Issue - Land Lord","Grid outage, landlord stopped the Gen b=
ecause it's too noisy// Grid return","loic.noumsi@matech-cameroun.com","250=
","20-06-2025 16:40:13","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005305480","Tou=
ring Club International","","20-06-2025 16:37:45","20-06-2025 16:34:35","20=
-06-2025 17:18:16","Grid outage, site went down due to poor backup battery =
// He reset it, site on Grid","Albran Byorel","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
due to poor backup battery // He reset it, site on Grid","loic.noumsi@matec=
h-cameroun.com","190","20-06-2025 16:37:45","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005305184","E=
foulan","","20-06-2025 15:57:10","20-06-2025 15:50:45","20-06-2025 16:08:11=
","	Site impacted by Efoulan Pont which is not managed by IHS","MINKA NICOL=
AS","Customer Equipment Failure","Active","Active Equipment Failure","Affec=
ted by 3rd Party Site","	Site impacted by Efoulan Pont which is not managed=
 by IHS","gaelle.njiofack@matech-cameroun.com","386","20-06-2025 15:57:10",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0005305036","ODZA MIN=
KAN EDIBI ASSI","","20-06-2025 15:43:23","20-06-2025 15:31:24","20-06-2025 =
16:03:47","Cascaded Incident from TTO5468024","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage, site went d=
own due to poor backup battery // He reset it, site on Grid","system","5349=
12","20-06-2025 15:43:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0005305035","Awae Ewo=
nkan","","20-06-2025 15:43:23","20-06-2025 15:31:24","20-06-2025 16:03:47",=
"Cascaded Incident from TTO5468024","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 poor backup battery // He reset it, site on Grid","system","534909","20-06=
-2025 15:43:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_253","NOCINC0005305034","Clge-Adv=
antiste","","20-06-2025 15:43:23","20-06-2025 15:31:24","20-06-2025 16:03:4=
7","Cascaded Incident from TTO5468024","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to poor backup battery // He reset it, site on Grid","system","534911","20=
-06-2025 15:43:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_807","NOCINC0005305032","Ahala Ec=
hangeur","","20-06-2025 15:43:22","20-06-2025 15:31:24","20-06-2025 16:03:4=
7","Cascaded Incident from TTO5468024","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to poor backup battery // He reset it, site on Grid","system","534925","20=
-06-2025 15:43:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_281","NOCINC0005305031","Odza II"=
,"","20-06-2025 15:43:22","20-06-2025 15:31:24","20-06-2025 16:03:47","Casc=
aded Incident from TTO5468024","Albran Byorel","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down due to poor=
 backup battery // He reset it, site on Grid","system","534917","20-06-2025=
 15:43:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0005305030","Odza Min=
kan IHS","","20-06-2025 15:43:22","20-06-2025 15:31:24","20-06-2025 16:03:4=
7","Cascaded Incident from TTO5468024","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to poor backup battery // He reset it, site on Grid","system","534926","20=
-06-2025 15:43:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_312","NOCINC0005305033","Nkolnda"=
,"","20-06-2025 15:43:22","20-06-2025 15:31:24","20-06-2025 16:03:47","Casc=
aded Incident from TTO5468024","Albran Byorel","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down due to poor=
 backup battery // He reset it, site on Grid","system","534920","20-06-2025=
 15:43:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0005305025","Mehanda =
1","","20-06-2025 15:43:21","20-06-2025 15:31:24","20-06-2025 16:03:47","Ca=
scaded Incident from TTO5468024","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down due to po=
or backup battery // He reset it, site on Grid","system","534919","20-06-20=
25 15:43:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_524","NOCINC0005305029","ODZA BOR=
NE 10","","20-06-2025 15:43:21","20-06-2025 15:31:24","20-06-2025 16:03:47"=
,"Cascaded Incident from TTO5468024","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down due t=
o poor backup battery // He reset it, site on Grid","system","534908","20-0=
6-2025 15:43:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_336","NOCINC0005305028","EKIE",""=
,"20-06-2025 15:43:21","20-06-2025 15:31:24","20-06-2025 16:03:47","Cascade=
d Incident from TTO5468024","Albran Byorel","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, site went down due to poor ba=
ckup battery // He reset it, site on Grid","system","534917","20-06-2025 15=
:43:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_256","NOCINC0005305026","MESSAME =
NDONGO 1162","","20-06-2025 15:43:21","20-06-2025 15:31:24","20-06-2025 16:=
03:47","Cascaded Incident from TTO5468024","MINKA NICOLAS","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 due to poor backup battery // He reset it, site on Grid","system","534915"=
,"20-06-2025 15:43:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0005305027","Nkolanga=
a","","20-06-2025 15:43:21","20-06-2025 15:31:24","20-06-2025 16:03:47","Ca=
scaded Incident from TTO5468024","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 poor backup battery // He reset it, site on Grid","system","534916","20-06=
-2025 15:43:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_160","NOCINC0005305024","Complex =
Beac II","","20-06-2025 15:43:20","20-06-2025 15:31:24","20-06-2025 16:03:4=
7","Cascaded Incident from TTO5468024","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to poor backup battery // He reset it, site on Grid","system","534924","20=
-06-2025 15:43:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_730","NOCINC0005305020","Odza pet=
it marche new","","20-06-2025 15:43:20","20-06-2025 15:31:24","20-06-2025 1=
6:03:47","Cascaded Incident from TTO5468024","Albran Byorel","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site went do=
wn due to poor backup battery // He reset it, site on Grid","system","53491=
4","20-06-2025 15:43:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_252","NOCINC0005305021","Koweit C=
ity","","20-06-2025 15:43:20","20-06-2025 15:31:24","20-06-2025 16:03:47","=
Cascaded Incident from TTO5468024","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
poor backup battery // He reset it, site on Grid","system","534908","20-06-=
2025 15:43:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_328","NOCINC0005305022","Nsimalen=
 MTN","","20-06-2025 15:43:20","20-06-2025 15:31:24","20-06-2025 16:03:47",=
"Cascaded Incident from TTO5468024","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 poor backup battery // He reset it, site on Grid","system","534924","20-06=
-2025 15:43:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0005305023","Nkoulou =
Carriere carrefourt","","20-06-2025 15:43:20","20-06-2025 15:31:24","20-06-=
2025 16:03:47","Cascaded Incident from TTO5468024","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage, sit=
e went down due to poor backup battery // He reset it, site on Grid","syste=
m","534925","20-06-2025 15:43:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_161","NOCINC0005305019","Sofavinc=
","","20-06-2025 15:43:19","20-06-2025 15:31:24","20-06-2025 16:03:47","Cas=
caded Incident from TTO5468024","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to poo=
r backup battery // He reset it, site on Grid","system","534919","20-06-202=
5 15:43:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_800","NOCINC0005305018","ODZA CIT=
E MBIA","","20-06-2025 15:43:19","20-06-2025 15:31:24","20-06-2025 16:03:47=
","Cascaded Incident from TTO5468024","Albran Byorel","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, site went down due =
to poor backup battery // He reset it, site on Grid","system","534923","20-=
06-2025 15:43:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0005305017","Mbedoumo=
u - Ekali","","20-06-2025 15:43:19","20-06-2025 15:31:24","20-06-2025 16:03=
:47","Cascaded Incident from TTO5468024","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to poor backup battery // He reset it, site on Grid","system","534914","=
20-06-2025 15:43:19","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005304981","Tou=
ring Club International","IHS_YND_343, IHS_YND_800, IHS_YND_161, IHS_YND_73=
0, IHS_YND_252, IHS_YND_723, IHS_YND_328, IHS_YND_794, IHS_YND_160, IHS_YND=
_385, IHS_YND_528, IHS_YND_746, IHS_YND_553, IHS_YND_256, IHS_YND_289, IHS_=
YND_336, IHS_YND_524, IHS_YND_527, IHS_YND_410, IHS_YND_715, IHS_YND_281, I=
HS_YND_595, IHS_YND_807, IHS_YND_312, IHS_YND_253, IHS_YND_535, IHS_YND_749=
, IHS_EBO_015, IHS_YND_344, IHS_YND_411","20-06-2025 15:37:34","20-06-2025 =
15:31:24","20-06-2025 16:03:47","Grid outage, site went down due to poor ba=
ckup battery // He reset it, site on Grid","Albran Byorel","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Grid =
outage, site went down due to poor backup battery // He reset it, site on G=
rid","loic.noumsi@matech-cameroun.com","371","20-06-2025 15:37:34","MATECH =
CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005304945","C=
arrefourt Nkomo","","20-06-2025 15:31:37","16-06-2025 15:09:55","21-06-2025=
 02:08:18","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Site down due to PWC overload ( PWC of 12 k and iload=
 of 200A) // PWC swapped ","gaelle.njiofack@matech-cameroun.com","1607801",=
"20-06-2025 15:31:37","MATECH CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0005304911","SOA=
 UNIVERSITY STADIUM","","20-06-2025 15:24:42","20-06-2025 15:20:31","20-06-=
2025 15:43:34","Grid outage,Site went down due to PWC ZTE dysfunction//He r=
eset it and site on Gen","Siligap Boris","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Grid outage,Site went down due to PWC ZTE dysfun=
ction//He reset it and site on Gen","loic.noumsi@matech-cameroun.com","252"=
,"20-06-2025 15:24:42","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005304898","N=
gousso-Savana","","20-06-2025 15:23:03","20-06-2025 15:14:57","20-06-2025 1=
5:20:49","No power issue, site is on grid with Ubaie: 52.4V, Armand Nguetsa=
 (699949553) from Huawei is informed.","Siligap Boris","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue, site is on grid with Ubaie: 52.4V, Armand Nguetsa (699949553) from =
Huawei is informed.","loic.noumsi@matech-cameroun.com","487","20-06-2025 15=
:23:03","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0005304740","S=
AA 2","","20-06-2025 14:55:23","20-06-2025 14:50:15","20-06-2025 15:43:05",=
"site impacted by Ombessa ","Parker Tchoup","Customer Equipment Failure","A=
ctive","Active Equipment Failure","Affected by 3rd Party Site","site impact=
ed by Ombessa ","gaelle.njiofack@matech-cameroun.com","309","20-06-2025 14:=
55:23","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005304715","Mvo=
g-Manga","","20-06-2025 14:51:19","20-06-2025 14:47:14","20-06-2025 18:53:0=
3","Grid outage, site went down because Matech FME Albran was on site for P=
M (Swap of MPR) // End of work","Albran Byorel","Installation Activity","Pa=
ssive","Planned Activity","Installation Activity","Grid outage, site went d=
own because Matech FME Albran was on site for PM (Swap of MPR) // End of wo=
rk","loic.noumsi@matech-cameroun.com","247","20-06-2025 14:51:19","MATECH C=
MR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005304684","B=
arriere","","20-06-2025 14:46:56","20-06-2025 14:38:50","20-06-2025 16:43:5=
7","Active// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","loic.noumsi@matech-cameroun.com","487","20-06-2025 14:46:56","=
MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005304463","Beh=
ind P T school Yde","","20-06-2025 14:06:15","20-06-2025 14:01:04","20-06-2=
025 14:54:50","Active: No power issue, site is on Grid with Ubaie=3D53.4V. =
 TX Fme Hosiah / 674007438 from huawei is informed.","Paul BIBOUM","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active: No power issue, site is on Grid with Ubaie=3D53.4V.  TX Fme Hos=
iah / 674007438 from huawei is informed.","cedric.tiani@matech-cameroun.com=
","312","20-06-2025 14:06:15","MATECH CMR"
"Closed Complete","Site Down","CTR_546","IHS_YND_419","NOCINC0005304231","N=
gog Mapubi","","20-06-2025 13:26:17","20-06-2025 13:20:10","20-06-2025 13:2=
3:56","Grid outage, site went down due to poor battery backup // Grid retur=
ned","Kemeni Franklin","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage, site went down due to poor battery bac=
kup // Grid returned","cedric.tiani@matech-cameroun.com","367","20-06-2025 =
13:26:17","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0005303924","MEH=
ANDAN","","20-06-2025 12:47:27","20-06-2025 12:43:13","20-06-2025 16:03:47"=
,"Grid outage, site went down because gen failed to start due to PWC ZTE dy=
sfunctionning // He configured PWC ZTE","Albran Byorel","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site went=
 down because gen failed to start due to PWC ZTE dysfunctionning // He conf=
igured PWC ZTE","cedric.tiani@matech-cameroun.com","255","20-06-2025 12:47:=
27","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005303517","NKO=
MKANA ELIZA HOTEL","","20-06-2025 11:57:11","18-06-2025 14:22:53","18-06-20=
25 14:55:06","Bactracking Grid outage.no space to deploy mobile gen//Grid r=
eturn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Bactracking Grid outage.no space to deploy mobile gen//Grid return","mou=
liom.anselme@matech-cameroun.com","164058","20-06-2025 11:57:11","MATECH CM=
R"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0005303220","Ole=
mbe MTN","","20-06-2025 11:31:19","20-06-2025 11:28:08","20-06-2025 11:31:3=
4","Site went down due to 02/05 rectifiers faulty on site//He needed to add=
 02","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down due to 02/05 rectifiers faulty on site//He needed t=
o add 02","cedric.tiani@matech-cameroun.com","192","20-06-2025 11:31:19","M=
ATECH CMR"
"Closed Complete","Warning","CTR_256","IHS_YND_232","NOCINC0005303207","Crf=
-Nkolbisson","","20-06-2025 11:28:47","","","Our FME was on site doing PM",=
"TIENTCHEU NZETCHIEU GAEL","Warning","Warning","Unlisted RCA","Warning - Ot=
hers","Our FME is on site doing PM","cedric.tiani@matech-cameroun.com","127=
","20-06-2025 11:28:47","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0005303178","C=
rf-Nkolbisson","","20-06-2025 11:26:24","20-06-2025 11:26:15","20-06-2025 1=
1:26:38","Wrongly created ticket","TIENTCHEU NZETCHIEU GAEL","Incorrectly L=
ogged Tickets","Error","Error","Error","Wrongly created ticket","cedric.tia=
ni@matech-cameroun.com","10","20-06-2025 11:26:24","MATECH CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0005303149","M=
volye-New","","20-06-2025 11:21:15","20-06-2025 11:18:04","20-06-2025 23:29=
:52","Active// No power Issue Site on Grid Ubaie =3D51.8V, The TX FME Mbah =
Hosiah (674007438) is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site=
 on Grid Ubaie =3D51.8V, The TX FME Mbah Hosiah (674007438) is informed","c=
edric.tiani@matech-cameroun.com","192","20-06-2025 11:21:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0005303144","Marche O=
dza","","20-06-2025 11:20:46","20-06-2025 11:16:06","20-06-2025 11:26:47","=
Cascaded Incident from TTO5465984","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue on site Ubaie: =
53 V site on Grid The TX Lionel steve (655184876 /Huawei)) is informed","sy=
stem","543047","20-06-2025 11:20:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0005303143","Mvog-Man=
ga","","20-06-2025 11:20:46","20-06-2025 11:16:06","20-06-2025 11:26:47","C=
ascaded Incident from TTO5465984","Albran Byorel","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue on site Ubaie: 5=
3 V site on Grid The TX Lionel steve (655184876 /Huawei)) is informed","sys=
tem","543047","20-06-2025 11:20:46","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005303132","O=
dza","IHS_YND_254, IHS_YND_580","20-06-2025 11:19:20","20-06-2025 11:16:06"=
,"20-06-2025 11:26:47","Active//No power issue on site Ubaie: 53 V site on =
Grid The TX Lionel steve (655184876 /Huawei)) is informed","Albran Byorel",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active//No power issue on site Ubaie: 53 V site on Grid The TX =
Lionel steve (655184876 /Huawei)) is informed","cedric.tiani@matech-camerou=
n.com","195","20-06-2025 11:19:20","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005302936","MBA=
LNGONG LYCEE","","20-06-2025 10:55:34","20-06-2025 10:51:24","20-06-2025 11=
:47:19","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed //He reduced the load and manuall=
y started the Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Site went down because Gen stopped due to overload(9kva, 1=
30A) SS IHS Felix Zambe is informed and confirmed //He reduced the load and=
 manually started the Gen","cedric.tiani@matech-cameroun.com","252","20-06-=
2025 10:55:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005302888","MEHANDAN=
","","20-06-2025 10:46:28","20-06-2025 10:27:01","20-06-2025 12:30:24","Cas=
caded Incident from TTO5465671","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction //He reset it and started the =
Gen manually","system","545910","20-06-2025 10:46:28","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005302759","N=
GONA","","20-06-2025 10:27:13","20-06-2025 10:26:46","20-06-2025 10:33:29",=
"No power issue Site is on Grid and Ubaie =3D55.5V The Tx FME Lionel Adjep =
(655184876)from Huawei is informed","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue Site is on Grid and Ubaie =3D57V The Tx FME Lionel Adjep (655184876)=
from Huawei is informed","cedric.tiani@matech-cameroun.com","28","20-06-202=
5 10:27:13","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005302725","Odz=
a II OCM","IHS_YND_528","20-06-2025 10:25:10","20-06-2025 10:22:01","20-06-=
2025 16:03:47","Grid outage, site went down because gen failed to start due=
 to PWC ZTE malfunction //He reset it and started the Gen manually","Albran=
 Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Grid outage, site went down because gen failed to start due to PWC ZT=
E malfunction //He reset it and started the Gen manually","cedric.tiani@mat=
ech-cameroun.com","190","20-06-2025 10:25:10","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005302703","SIM=
BOCK BONAMBAPE","","20-06-2025 10:20:24","20-06-2025 10:14:16","20-06-2025 =
14:13:56","Grid outage, Site went down because 01/07 rectifiers faulty // H=
e added 01 rectifier on site, site on Grid","Hyemafo Gildas","Equipment Rep=
air","Passive","Rectifier","Rectifier Module","Grid outage, Site went down =
because 01/07 rectifiers faulty // He added 01 rectifier on site, site on G=
rid","cedric.tiani@matech-cameroun.com","369","20-06-2025 10:20:24","MATECH=
 CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005302640","NKO=
MKANA ELIZA HOTEL","","20-06-2025 10:06:56","20-06-2025 10:05:48","20-06-20=
25 10:07:30","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","cedric.tiani@matech-=
cameroun.com","69","20-06-2025 10:06:56","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005302602","S=
aa","","20-06-2025 09:54:51","20-06-2025 09:49:44","20-06-2025 10:10:34","A=
ctive// No power issue on site ,site on Gen with Ubaie =3D53.8V The Tx Tech=
nician from Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue on site ,site on Gen with Ubaie =3D53.8V The=
 Tx Technician from Huawei Gr=E9goire//654547479 is informed","cedric.tiani=
@matech-cameroun.com","309","20-06-2025 09:54:51","MATECH CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0005302487","Nsi=
meyong Terre Rouge","","20-06-2025 09:44:19","20-06-2025 09:40:10","20-06-2=
025 09:42:36","Grid outage, Site went downt before Gen start due to poor ba=
ttery backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, Site went downt =
before Gen start due to poor battery backup // Grid return","cedric.tiani@m=
atech-cameroun.com","250","20-06-2025 09:44:19","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005302404","NYO=
M FACE MAETUR","","20-06-2025 09:36:29","20-06-2025 09:34:20","20-06-2025 0=
9:36:51","Grid fluctuation,Site went down because Gen failed to start due t=
o Grid bad voltage // Grid stabilized","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,Si=
te went down because Gen failed to start due to Grid bad voltage // Grid st=
abilized","cedric.tiani@matech-cameroun.com","131","20-06-2025 09:36:29","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005302359","O=
lembe","","20-06-2025 09:29:42","20-06-2025 09:28:32","20-06-2025 09:36:18"=
,"Our FME Giress is on site working (configure the PWC ZTE )//End of work",=
"Fabrice Pouakam","Installation Activity","Passive","Planned Activity","Ins=
tallation Activity","Our FME Giress is on site working (configure the PWC Z=
TE )//End of work","cedric.tiani@matech-cameroun.com","71","20-06-2025 09:2=
9:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005302250","Nsam esc=
ale LP","","20-06-2025 09:05:18","20-06-2025 09:00:18","20-06-2025 09:06:03=
","Cascaded Incident from TTO5464979","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Gen Started Automatically","system","551013","20-06-2=
025 09:05:18","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005302237","Nsa=
m Sofavinc","IHS_YND_732","20-06-2025 09:03:31","20-06-2025 09:00:18","20-0=
6-2025 09:06:03","Grid Outage, Site went down before Gen start due to poor =
backup // Gen Started Automatically","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site wen=
t down before Gen start due to poor backup // Gen Started Automatically","c=
edric.tiani@matech-cameroun.com","194","20-06-2025 09:03:31","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0005302171","Ole=
mbe MTN","","20-06-2025 08:53:10","20-06-2025 08:51:01","20-06-2025 08:54:3=
2","Site went down due to 02/05 rectifiers faulty on site//He needed to add=
 02","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down due to 02/05 rectifiers faulty on site//He needed t=
o add 02","cedric.tiani@matech-cameroun.com","130","20-06-2025 08:53:10","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005302160","B=
arriere","","20-06-2025 08:47:41","20-06-2025 08:46:17","20-06-2025 08:47:2=
1","Active// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","cedric.tiani@matech-cameroun.com","86","20-06-2025 08:47:41","=
MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005302122","SIM=
BOCK BONAMBAPE","","20-06-2025 08:40:53","20-06-2025 08:38:41","20-06-2025 =
10:09:29","(Very Unstable) Site went down because 01/07 rectifiers faulty//=
Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","(Very Unstable) Site went down because 01/07 rectifiers=
 faulty//Site stabilised","cedric.tiani@matech-cameroun.com","133","20-06-2=
025 08:40:53","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005301987","Nko=
lnda","","20-06-2025 08:19:46","20-06-2025 08:15:32","20-06-2025 09:07:02",=
"Grid outage, site went down because gen failed to start with alarm undervo=
ltage // He reset gen card and gen manually started","Albran Byorel","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site=
 went down because gen failed to start with alarm undervoltage // He reset =
gen card and gen manually started","loic.noumsi@matech-cameroun.com","255",=
"20-06-2025 08:19:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005301902","Mfou EPC=
","","20-06-2025 08:08:19","20-06-2025 08:03:20","20-06-2025 08:13:48","Cas=
caded Incident from TTO5464587","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","547562","20-06-2025 08=
:08:19","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005301898","M=
fou OCM","IHS_YND_674","20-06-2025 08:07:30","20-06-2025 08:03:20","20-06-2=
025 08:13:48"," Site Down before gen Started due to poor backup","Mba Lazar=
e Herve","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","Grid Outage, Site Down before gen Started due to poor backup //Gr=
id returned","cedric.tiani@matech-cameroun.com","251","20-06-2025 08:07:30"=
,"MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005301888","ODZ=
A BORNE 10","","20-06-2025 08:04:23","20-06-2025 08:03:10","20-06-2025 09:4=
6:31","Site went down due to 02/04 rectifiers faulty//He reset it","Albran =
Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","Site w=
ent down due to 02/04 rectifiers faulty//He reset it","cedric.tiani@matech-=
cameroun.com","74","20-06-2025 08:04:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005301886","MEHANDAN=
","","20-06-2025 08:03:47","20-06-2025 08:00:54","20-06-2025 08:04:07","Cas=
caded Incident from TTO5464565","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction//Site stabilised","syste=
m","547705","20-06-2025 08:03:47","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005301879","O=
dza II OCM","IHS_YND_528","20-06-2025 08:03:02","20-06-2025 08:00:54","20-0=
6-2025 08:04:07","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction//Site stabilised","Albran Byorel","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctua=
tions, site went down because gen failed to start due to PWC ZTE malfunctio=
n//Site stabilised","cedric.tiani@matech-cameroun.com","131","20-06-2025 08=
:03:02","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005301864","Eto=
ug ebe Meweulo","","20-06-2025 08:00:59","20-06-2025 07:59:45","20-06-2025 =
09:17:49","Grid outage site went down because Gen failed to start due PWC Z=
TE dysfonction // He bypassed the it and started the Gen manually","Hyemafo=
 Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Grid outage site went down because Gen failed to start due PWC ZTE dy=
sfonction // He bypassed the it and started the Gen manually","cedric.tiani=
@matech-cameroun.com","75","20-06-2025 08:00:59","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005301455","SIM=
BOCK BONAMBAPE","","20-06-2025 06:13:29","20-06-2025 06:03:21","20-06-2025 =
08:01:44","(Very Unstable) Site went down because 01/07 rectifiers faulty//=
Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","(Very Unstable) Site went down because 01/07 rectifiers=
 faulty//Site stabilised","loic.noumsi@matech-cameroun.com","609","20-06-20=
25 06:13:29","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005301108","Eto=
ug ebe Meweulo","","20-06-2025 03:37:13","18-06-2025 17:45:09","18-06-2025 =
23:31:09","Backtracking // Grid outage site went down because Gen failed to=
 start due PWC ZTE dysfonction // He bypassed it and started the Gen manual=
ly","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","Backtracking // Grid outage site went down because Gen fa=
iled to start due PWC ZTE dysfonction // He bypassed the it and started the=
 Gen manually","gerard.tchangoue@matech-cameroun.com","121925","20-06-2025 =
03:37:13","MATECH CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0005301085","Don=
g","","20-06-2025 03:28:31","18-06-2025 19:37:29","18-06-2025 20:10:29","Ba=
cktracking  Active: No power issue, site on battery With Ubaie=3D48.9V, The=
 Tx FME Gregoire (654547479) from Huawei is informed","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Backtracking  Active: No power issue, site on battery With Ubaie=3D4=
8.9V, The Tx FME Gregoire (654547479) from Huawei is informed","gerard.tcha=
ngoue@matech-cameroun.com","114879","20-06-2025 03:28:31","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005301040","SIM=
BOCK BONAMBAPE","","20-06-2025 03:15:30","20-06-2025 03:09:24","20-06-2025 =
05:09:43","(Very Unstable) Site went down because 01/07 rectifiers faulty /=
/ Grid stabilised","Hyemafo Gildas","Equipment Repair","Passive","Rectifier=
","Rectifier Module","(Very Unstable) Site went down because 01/07 rectifie=
rs faulty // Grid stabilised","loic.noumsi@matech-cameroun.com","367","20-0=
6-2025 03:15:30","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005300214","M=
EHANDAN","","20-06-2025 00:16:42","20-06-2025 00:10:28","20-06-2025 01:47:5=
1","SIte impacted by Odza II OCM","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuations, site went down be=
cause gen failed to start due to PWC ZTE malfunction // Grid stabilized","g=
erard.tchangoue@matech-cameroun.com","575601","20-06-2025 00:16:42","MATECH=
 CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005300213","Odz=
a II OCM","IHS_YND_528","20-06-2025 00:16:36","20-06-2025 00:10:28","20-06-=
2025 00:17:51","Grid fluctuations, site went down because gen failed to sta=
rt due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctua=
tions, site went down because gen failed to start due to PWC ZTE malfunctio=
n // Grid stabilized","loic.noumsi@matech-cameroun.com","369","20-06-2025 0=
0:16:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005300205","Mfou EPC=
","","20-06-2025 00:14:13","20-06-2025 00:05:54","20-06-2025 00:22:39","Cas=
caded Incident from TTO5462686","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid returned","system","575871","20-06-2025 00=
:14:13","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005300196","M=
fou OCM","IHS_YND_674","20-06-2025 00:13:05","20-06-2025 00:05:54","20-06-2=
025 00:22:39","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Sta=
rted due to poor backup //Grid returned","gerard.tchangoue@matech-cameroun.=
com","432","20-06-2025 00:13:05","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0005300182","S=
AA 2","","20-06-2025 00:09:58","20-06-2025 00:04:49","20-06-2025 00:34:00",=
"No power issue on site Ubay 54.2 V site on Gen, Gregoire / from huawei is =
informed.","Parker Tchoup","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue on site Ubay 54.2 V s=
ite on Gen, Gregoire / from huawei is informed.","gerard.tchangoue@matech-c=
ameroun.com","310","20-06-2025 00:09:58","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005300023","Tou=
ring Club International","","19-06-2025 23:41:11","19-06-2025 23:38:05","19=
-06-2025 23:46:01","Grid outage, site went down due to poor backup battery =
// Site stabilised","Albran Byorel","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Grid outage, site went down due to poor ba=
ckup battery // Site stabilised","loic.noumsi@matech-cameroun.com","187","1=
9-06-2025 23:41:11","MATECH CMR"
"Closed Complete","Warning","T0033","IHS_YND_167","NOCINC0005300004","Touri=
ng Club International","","19-06-2025 23:35:25","","","poor backup // Gen s=
tarted automatically","Albran Byorel","Warning","Warning","POWER","Warning =
- Site on Battery","poor backup // Gen started automatically","loic.noumsi@=
matech-cameroun.com","488","19-06-2025 23:35:25","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005299778","A=
ccacia New","","19-06-2025 22:46:13","19-06-2025 22:38:01","19-06-2025 23:0=
2:51","No power issue on site, site on Grid with Ubaie=3D52.4V The Tx Fme M=
bah Hosiah //674007438/ from HUAWEI is informed","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site, site on Grid with Ubaie=3D52.4V The Tx Fme Mbah Hosiah //67400=
7438/ from HUAWEI is informed","gerard.tchangoue@matech-cameroun.com","493"=
,"19-06-2025 22:46:13","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005299769","D=
amas","","19-06-2025 22:44:46","19-06-2025 22:38:35","19-06-2025 23:07:26",=
"No power Issue Site on Grid Ubai =3D53,5 V, The FME The TX FME Mbah Hosiah=
 (674007438) is informed.","MINKA NICOLAS","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power Issue Site =
on Grid Ubai =3D53,5 V, The FME The TX FME Mbah Hosiah (674007438) is infor=
med.","gerard.tchangoue@matech-cameroun.com","372","19-06-2025 22:44:46","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005299759","M=
ontee-Jouvence-II","","19-06-2025 22:43:01","19-06-2025 22:38:46","19-06-20=
25 22:54:56","No power issue on site, site on Grid with Ubaie=3D54.1V The T=
x Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site, site on Grid with Ubaie=3D54.1V The Tx Fm=
e Mbah Hosiah //674007438/ from HUAWEI is informed","gerard.tchangoue@matec=
h-cameroun.com","257","19-06-2025 22:43:01","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005299669","SIM=
BOCK BONAMBAPE","","19-06-2025 22:28:16","19-06-2025 22:25:12","20-06-2025 =
03:05:30","(Very Unstable) Site went down because 01/07 rectifiers faulty /=
/ Grid stabilised","Hyemafo Gildas","Equipment Repair","Passive","Rectifier=
","Rectifier Module","(Very Unstable) Site went down because 01/07 rectifie=
rs faulty // Grid stabilised","loic.noumsi@matech-cameroun.com","185","19-0=
6-2025 22:28:16","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005299478","Ako=
k Ndoe Yde","","19-06-2025 22:10:30","19-06-2025 22:08:23","19-06-2025 22:1=
0:23","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started automatically","Hyemafo Gildas","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup// Gen started automatically","franck.nkomot=
@matech-cameroun.com","127","19-06-2025 22:10:30","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005299377","SIM=
BOCK BONAMBAPE","","19-06-2025 21:52:58","19-06-2025 21:50:50","19-06-2025 =
21:52:50","Site went down because 01/07 rectifiers faulty // He reset recti=
fier,site on Grid","Hyemafo Gildas","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down because 01/07 rectifiers faulty // He =
reset rectifier,site on Grid","franck.nkomot@matech-cameroun.com","129","19=
-06-2025 21:52:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0005299257","Awae Esc=
alier","","19-06-2025 21:31:53","19-06-2025 20:07:33","19-06-2025 20:08:05"=
,"   No power issue site on Grid with U=3D53.8V ,The FME TX Henry (69994969=
3) from Huawei is informed .Power issue has been resolved since 19-06-2025 =
20:05:47 but site remain down.","Albran Byorel","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","  No power issu=
e site on Grid with U=3D53.8V ,The FME TX Henry (699949693) from Huawei is =
informed .Power issue has been resolved since 19-06-2025 20:05:47 but site =
remain down.","edwige.kapawo@matech-cameroun.com","5061","19-06-2025 21:31:=
53","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005298903","OTE=
LE MTN","","19-06-2025 20:43:24","19-06-2025 20:36:12","19-06-2025 21:50:12=
","Grid outage,site went because Gen failed to start due to disjunction of =
Generator CB //He rearmed and manually started the Gen","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Grid outage,site =
went because Gen failed to start due to disjunction of Generator CB //He re=
armed and manually started the Gen","franck.nkomot@matech-cameroun.com","43=
3","19-06-2025 20:43:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0005298738","Mamch Bu=
ilding","","19-06-2025 20:16:27","19-06-2025 20:14:36","24-06-2025 10:50:21=
","Cascaded Incident from TTO5460992","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid only site Site down because=
 Grid meter has burned// Grid return witn replacement grid meter","system",=
"676147","19-06-2025 20:16:27","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005298689","C=
harles-Atangana","IHS_YND_051","19-06-2025 20:15:44","19-06-2025 20:14:36",=
"24-06-2025 10:50:21","Grid only site Site down because Grid meter has burn=
ed// Grid return witn replacement grid meter","","Grid Supply","Passive","G=
rid","National Grid - Grid Outage Issue","Grid only site Site down because =
Grid meter has burned// Grid return witn replacement grid meter","edwige.ka=
pawo@matech-cameroun.com","69","19-06-2025 20:15:44","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005298537","M=
endong vallee","","19-06-2025 19:59:28","19-06-2025 19:55:20","19-06-2025 2=
1:12:02","Grid Outage, Site went Down due to Gen overload (20KVA; 300A) IHS=
 F=E9lix Zamb=E9 is informed and confirmed // Grid return","Fanda Brice","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, Site =
went Down due to Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed=
 and confirmed // Grid return","edwige.kapawo@matech-cameroun.com","249","1=
9-06-2025 19:59:28","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005298351","A=
wae Escalier","","19-06-2025 19:42:07","19-06-2025 19:40:01","19-06-2025 20=
:05:47","Grid low voltage , Site down because, Gen fail to start due to gri=
d low voltage // Grid stabilisation  ","Albran Byorel","Grid Supply","Passi=
ve","Grid","National Grid - Low Current Supply","Grid low voltage , Site do=
wn because, Gen fail to start due to grid low voltage // Grid stabilisation=
  ","edwige.kapawo@matech-cameroun.com","127","19-06-2025 19:42:07","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005298330","A=
wae Ewonkan","","19-06-2025 19:38:51","19-06-2025 19:36:33","19-06-2025 19:=
44:18","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","edwige.kapawo@matech-cameroun.com","139","19-06-2025 19:38:51","MATEC=
H CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005298073","MBA=
LNGONG LYCEE","","19-06-2025 18:51:54","19-06-2025 18:43:43","20-06-2025 08=
:18:33","Grid outage, landlord stopped the Gen because it's too noisy//Grid=
 return","Fanda Brice","Access Denial","Lease Or Legal","Landlord Related I=
ssues","Access Issue - Land Lord","Grid outage, landlord stopped the Gen be=
cause it's too noisy//Grid return","franck.nkomot@matech-cameroun.com","492=
","19-06-2025 18:51:54","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005297924","A=
fanoya","","19-06-2025 18:32:42","19-06-2025 18:30:35","19-06-2025 18:31:52=
","Error logged ticket","Hyemafo Gildas","Incorrectly Logged Tickets","Erro=
r","Error","Error","Error logged ticket","edwige.kapawo@matech-cameroun.com=
","129","19-06-2025 18:32:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005297882","SAA 2","=
","19-06-2025 18:20:46","19-06-2025 18:34:57","19-06-2025 18:40:57","No pow=
er issue site on grid with U=3D54v site up at 06:40 PM ","Parker Tchoup","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue site on grid with U=3D54v site up at 06:40 PM ","s=
ystem","3848","19-06-2025 18:20:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0005297881","Saa","",=
"19-06-2025 18:20:45","19-06-2025 18:34:57","19-06-2025 18:40:57","No power=
 issue site on grid with U=3D54v site up at 06:40 PM","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue site on grid with U=3D54v site up at 06:40 PM","syste=
m","3855","19-06-2025 18:20:45","MATECH CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0005297778","M=
inka","","19-06-2025 18:08:58","19-06-2025 17:59:43","19-06-2025 18:07:00",=
"Grid hybrid Gen : Grid outage, site went down because Gen failed to start =
due to PWC dysfunctioning // Grid restoration","Fanda Brice","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid hybrid Gen :=
 Grid outage, site went down because Gen failed to start due to PWC dysfunc=
tioning // Grid restoration","edwige.kapawo@matech-cameroun.com","556","19-=
06-2025 18:08:58","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005297683","ODZ=
A BORNE 10","","19-06-2025 17:56:44","19-06-2025 17:51:32","19-06-2025 18:5=
4:32","site went down due to dysfunctioning of rectifiers // He reset recti=
fiers, site on grid","Albran Byorel","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","site went down due to dysfunctioning of rectifiers /=
/ He reset rectifiers, site on grid","franck.nkomot@matech-cameroun.com","3=
13","19-06-2025 17:56:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005297657","MEHANDAN=
","","19-06-2025 17:52:57","19-06-2025 17:49:45","19-06-2025 18:52:45","Cas=
caded Incident from TTO5459838","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","1223725","19-06-2025 17:52:57","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005297650","O=
dza II OCM","IHS_YND_528","19-06-2025 17:51:55","19-06-2025 17:49:45","19-0=
6-2025 18:52:45","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","edwige.kapawo@matech-cameroun.com","133","19-06-20=
25 17:51:55","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005297497","Tou=
ring Club International","","19-06-2025 17:26:58","19-06-2025 17:22:47","19=
-06-2025 18:10:47","Grid outage, site went down due to poor backup battery =
// Site stabilised","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down due to poo=
r backup battery // Site stabilised","franck.nkomot@matech-cameroun.com","2=
52","19-06-2025 17:26:58","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005297453","Mvo=
g-Manga","","19-06-2025 17:19:19","19-06-2025 17:15:04","20-06-2025 01:28:0=
6","Site went down due to MPR DYSFONNCTION on site //He reset the MPR and s=
ite on Grid","Albran Byorel","Equipment Repair","Passive","Rectifier","Rect=
ifier Cabinet","Site went down due to MPR DYSFONNCTION on site //He reset t=
he MPR and site on Grid","franck.nkomot@matech-cameroun.com","538","19-06-2=
025 17:19:19","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005297394","E=
toudi","","19-06-2025 17:10:47","19-06-2025 17:10:43","19-06-2025 17:12:28"=
,"Grid outage, site went down before Gen start due to poor battery backup /=
/ Grid returned","Fabrice Pouakam","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before Gen =
start due to poor battery backup // Grid returned","edwige.kapawo@matech-ca=
meroun.com","5","19-06-2025 17:10:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0005297376","Garbati =
building","","19-06-2025 17:07:13","19-06-2025 16:57:36","19-06-2025 17:59:=
36","Cascaded Incident from TTO5459514","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down be=
fore Gen started due to poor battery back up // GEN automatically started",=
"system","587525","19-06-2025 17:07:13","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005297368","HOP=
ITAL DE LA CAISSE","IHS_YND_024","19-06-2025 17:05:55","19-06-2025 16:57:36=
","19-06-2025 17:59:36","Grid outage site went down before Gen started due =
to poor battery back up // GEN automatically started","Delor Telezing","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage site went down before Gen started due to poor battery back up // G=
EN automatically started","ludivine.ngamaleu@ihstowers.com","500","19-06-20=
25 17:05:55","MATECH CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0005297334","M=
IMBOMAN LIBERTE","","19-06-2025 16:58:50","19-06-2025 16:56:38","19-06-2025=
 20:24:48","Site down due to PM work of ( Fotso achille / 694271069 / SFM  =
) for  ( swapp of  bay ) // End of work","Mba Lazare Herve","Installation A=
ctivity","Passive","Planned Activity","Installation Activity","Site down du=
e to PM work of ( Fotso achille / 694271069 / SFM  ) for  ( swapp of  bay )=
 // End of work","edwige.kapawo@matech-cameroun.com","133","19-06-2025 16:5=
8:50","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005297287","S=
atcom","","19-06-2025 16:49:11","19-06-2025 16:47:04","19-06-2025 16:50:46"=
,"	No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand ng=
uetsa(691144412) From huawei is informed.","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	No=
 power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand nguetsa=
(691144412) From huawei is informed.","edwige.kapawo@matech-cameroun.com","=
128","19-06-2025 16:49:11","MATECH CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0005297246","C=
hapelle-Essos","","19-06-2025 16:43:36","19-06-2025 16:41:17","19-06-2025 2=
0:42:48","No power issue on site U=3D54,1 V site on Grid The TX FME Armand =
Nguetsa /691144412 from huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site U=3D54,1 V site on Grid The TX FME Armand Nguetsa /691=
144412 from huawei is informed","edwige.kapawo@matech-cameroun.com","140","=
19-06-2025 16:43:36","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005297158","O=
lembe","","19-06-2025 16:28:38","19-06-2025 16:24:30","19-06-2025 16:36:40"=
,"Grid outage ,site down because Gen turbo failed // Gen loads  reduced whi=
le waiting for turbo replacement.","Fabrice Pouakam","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage ,site down because Ge=
n turbo failed // Gen loads  reduced while waiting for turbo replacement.",=
"edwige.kapawo@matech-cameroun.com","249","19-06-2025 16:28:38","MATECH CMR=
"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005296787","Par=
adis Hotel","","19-06-2025 15:37:17","19-06-2025 15:28:59","19-06-2025 18:1=
5:59","Site went down due to MPR DYSFONNCTION on site / Site stabilised","S=
iligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site / Site stabilised","franck.=
nkomot@matech-cameroun.com","499","19-06-2025 15:37:17","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005296755","M=
vog-Manga","","19-06-2025 15:33:26","19-06-2025 15:31:18","19-06-2025 16:39=
:55","Site went down due to MPR DYSFONNCTION on site // Site stabilised","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site // Site stabilised","edwige=
.kapawo@matech-cameroun.com","129","19-06-2025 15:33:26","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005296643","A=
ccacia New","","19-06-2025 15:15:33","19-06-2025 15:09:26","19-06-2025 15:1=
7:27","No power issue on site, site on Grid with Ubaie=3D52.4V The Tx Fme M=
bah Hosiah //674007438/ from HUAWEI is informed","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site, site on Grid with Ubaie=3D52.4V The Tx Fme Mbah Hosiah //67400=
7438/ from HUAWEI is informed","edwige.kapawo@matech-cameroun.com","369","1=
9-06-2025 15:15:33","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005296636","M=
ontee-Jouvence-II","","19-06-2025 15:14:43","19-06-2025 15:09:35","19-06-20=
25 15:24:25","No power issue on site, site on Grid with Ubaie=3D54.1V The T=
x Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site, site on Grid with Ubaie=3D54.1V The Tx Fm=
e Mbah Hosiah //674007438/ from HUAWEI is informed","edwige.kapawo@matech-c=
ameroun.com","309","19-06-2025 15:14:43","MATECH CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005296537","TON=
GOLO SNEC","","19-06-2025 15:00:36","19-06-2025 14:45:12","19-06-2025 17:09=
:12","Site went down because relay 48 faulty // He replaced it, Site on Gri=
d","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Relay","=
Site went down because relay 48 faulty // He replaced it, Site on Grid","lu=
divine.ngamaleu@ihstowers.com","925","19-06-2025 15:00:36","MATECH CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0005296495","E=
toudi 2","","19-06-2025 14:58:06","19-06-2025 14:50:58","19-06-2025 16:04:5=
7","Site went down due to disjunction of rectifiers in the ATS // He reset =
it, Site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier=
","Rectifier - Circuit Breaker","Site went down due to disjunction of recti=
fiers in the ATS // He reset it, Site on Grid","edwige.kapawo@matech-camero=
un.com","429","19-06-2025 14:58:06","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005296385","D=
amas","","19-06-2025 14:44:50","19-06-2025 14:37:43","19-06-2025 15:36:04",=
"No power Issue Site on Grid Ubai =3D53,5 V, The FME The TX FME Mbah Hosiah=
 (674007438) is informed.","MINKA NICOLAS","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power Issue Site =
on Grid Ubai =3D53,5 V, The FME The TX FME Mbah Hosiah (674007438) is infor=
med.","edwige.kapawo@matech-cameroun.com","428","19-06-2025 14:44:50","MATE=
CH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005296321","Ngo=
usso Vallee","","19-06-2025 14:34:56","19-06-2025 14:24:59","19-06-2025 16:=
14:59","Site went down because insufficient of rectifier on site //site sta=
bilized","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down because insufficient of rectifier on site //site =
stabilized","franck.nkomot@matech-cameroun.com","598","19-06-2025 14:34:56"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005296232","M=
anguier","","19-06-2025 14:21:34","19-06-2025 14:20:25","19-06-2025 14:20:5=
1","Grid outage, site went down before gen start due to poor battery backup=
 // Gen Started Automatically","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen Started Automatically=
","edwige.kapawo@matech-cameroun.com","70","19-06-2025 14:21:34","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005295945","Nkolondo=
m","","19-06-2025 13:38:34","19-06-2025 13:35:46","19-06-2025 14:56:46","Ca=
scaded Incident from TTO5457935","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because our fme Gire=
sse was on site for plan work ( installation of  ATS) // End of work","syst=
em","592485","19-06-2025 13:38:34","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005295942","N=
KOLMEKONG YDE","IHS_YND_304","19-06-2025 13:37:52","19-06-2025 13:35:46","1=
9-06-2025 14:57:46","Site went down because our fme Giresse was on site for=
 plan work ( installation of  ATS) // End of work","Fabrice Pouakam","Insta=
llation Activity","Passive","Planned Activity","Installation Activity","Sit=
e went down because our fme Giresse was on site for plan work ( installatio=
n of  ATS) // End of work","edwige.kapawo@matech-cameroun.com","128","19-06=
-2025 13:37:52","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005295918","Tou=
ring Club International","","19-06-2025 13:29:44","19-06-2025 13:24:16","19=
-06-2025 14:02:23","Grid outage, site went down due to poor backup battery =
// Site stabilised","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down due to poo=
r backup battery // Site stabilised","gaelle.njiofack@matech-cameroun.com",=
"330","19-06-2025 13:29:44","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005295910","Mvo=
g-Manga","","19-06-2025 13:28:35","19-06-2025 13:20:22","19-06-2025 13:29:2=
5","Site went down due to MPR DYSFONNCTION on site // Site stabilised","Alb=
ran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","S=
ite went down due to MPR DYSFONNCTION on site // Site stabilised","gaelle.n=
jiofack@matech-cameroun.com","495","19-06-2025 13:28:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005295906","Nsam esc=
ale LP","","19-06-2025 13:26:44","19-06-2025 13:19:36","19-06-2025 13:25:58=
","Cascaded Incident from TTO5457888","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Gen Started Automatically","system","593447","19-06-2=
025 13:26:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005295904","MEHANDAN=
","","19-06-2025 13:26:01","19-06-2025 13:18:18","19-06-2025 13:26:34","Cas=
caded Incident from TTO5457893","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","1218713","19-06-2025 13:26:01","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005295903","O=
dza II OCM","IHS_YND_528","19-06-2025 13:25:25","19-06-2025 13:18:18","19-0=
6-2025 13:26:34","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","edwige.kapawo@matech-cameroun.com","429","19-06-20=
25 13:25:25","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005295898","Nsa=
m Sofavinc","IHS_YND_732","19-06-2025 13:24:48","19-06-2025 13:19:36","19-0=
6-2025 13:25:58","Grid Outage, Site went down before Gen start due to poor =
backup // Gen Started Automatically","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site wen=
t down before Gen start due to poor backup // Gen Started Automatically","g=
aelle.njiofack@matech-cameroun.com","313","19-06-2025 13:24:48","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005295884","Mfou EPC=
","","19-06-2025 13:22:51","19-06-2025 13:16:44","19-06-2025 13:40:51","Cas=
caded Incident from TTO5457862","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid return","system","593612","19-06-2025 13:2=
2:51","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005295875","M=
fou OCM","IHS_YND_674","19-06-2025 13:21:55","19-06-2025 13:16:44","19-06-2=
025 13:40:51","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Start=
ed due to poor backup //Grid return","edwige.kapawo@matech-cameroun.com","3=
11","19-06-2025 13:21:55","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005295858","N=
simalen OCM","","19-06-2025 13:18:24","19-06-2025 13:13:17","19-06-2025 17:=
47:51","No power issue, site on grid U=3D52.8V on grid tx FME Lionel Steve =
ADJEP/655184876/ From huawei is informed","Albran Byorel","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue, site on grid U=3D52.8V on grid tx FME Lionel Steve ADJEP/6551848=
76/ From huawei is informed","edwige.kapawo@matech-cameroun.com","308","19-=
06-2025 13:18:24","MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0005295727","c=
hina embassy yde","","19-06-2025 12:55:59","19-06-2025 12:54:48","19-06-202=
5 13:28:55","Grid outage, No space to deploy MGE // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","=
72","19-06-2025 12:55:59","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005295007","Par=
adis Hotel","","19-06-2025 11:10:04","18-06-2025 06:15:04","18-06-2025 06:2=
5:16","Bactracking Site went down due to MPR DYSFONNCTION on site / Site st=
abilised","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifi=
er Cabinet","Bactracking Site went down due to MPR DYSFONNCTION on site / S=
ite stabilised","mouliom.anselme@matech-cameroun.com","104100","19-06-2025 =
11:10:04","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005295000","Sof=
avinc","","19-06-2025 11:09:21","19-06-2025 11:06:07","19-06-2025 12:56:38"=
,"Grid outage, Gen start but did not feeding the site because his contactor=
 is faulty // Contactor bay-pass and site on Gen","MINKA NICOLAS","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, Gen st=
art but did not feeding the site because his contactor is faulty // Contact=
or bay-pass and site on Gen","gaelle.njiofack@matech-cameroun.com","194","1=
9-06-2025 11:09:21","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005294967","NKO=
MKANA ELIZA HOTEL","","19-06-2025 11:05:25","18-06-2025 11:35:14","18-06-20=
25 11:40:14","Bactracking Grid outage .no space to deploy mobile gen//Grid =
return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Bactracking Grid outage .no space to deploy mobile gen//Grid return","m=
ouliom.anselme@matech-cameroun.com","84611","19-06-2025 11:05:25","MATECH C=
MR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0005294907","O=
lezoa OCM","","19-06-2025 10:58:48","18-06-2025 09:56:46","18-06-2025 09:58=
:13","Bactracking No power issue Ubaie=3D53.6V site on Grid, Lionel Steve (=
655184876)of HUAWEI is informed.","","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Bactracking No power issue=
 Ubaie=3D53.6V site on Grid, Lionel Steve (655184876)of HUAWEI is informed.=
","mouliom.anselme@matech-cameroun.com","90123","19-06-2025 10:58:48","MATE=
CH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005294720","Eto=
udi2","","19-06-2025 10:35:22","19-06-2025 10:33:49","19-06-2025 11:09:35",=
"Our FME Delor is on site and repport that, CHARLES NGOULEU (698939066/GAIO=
) is on site for work // End of work","Delor Telezing","Equipment Replaceme=
nt","Passive","Planned Activity","Planned Activity - Passive","Our FME Delo=
r is on site and repport that, CHARLES NGOULEU (698939066/GAIO) is on site =
for work // End of work","gaelle.njiofack@matech-cameroun.com","93","19-06-=
2025 10:35:22","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005294649","NKO=
MKANA ELIZA HOTEL","","19-06-2025 10:23:14","19-06-2025 10:15:07","19-06-20=
25 11:57:20","	Grid outage .no space to deploy mobile gen//Grid return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid o=
utage .no space to deploy mobile gen//Grid return","gaelle.njiofack@matech-=
cameroun.com","488","19-06-2025 10:23:14","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005294604","Fla=
menco","","19-06-2025 10:19:15","19-06-2025 10:16:55","19-06-2025 11:58:18"=
,"Grid outage .gen failed to start due to card GE dysfunctionning//We reset=
 card GE and gen manually started","Mboua Thierry","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage .gen failed to start du=
e to card GE dysfunctionning//We reset card GE and gen manually started","g=
aelle.njiofack@matech-cameroun.com","141","19-06-2025 10:19:15","MATECH CMR=
"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005294570","Par=
adis Hotel","","19-06-2025 10:14:37","19-06-2025 06:57:19","19-06-2025 14:2=
3:19","(Backtracking) fme report that 02/03 rectiers faulty // Site stabili=
zed","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","(Backtracking) fme report that 02/03 rectiers faulty // Site stabili=
zed","edwige.kapawo@matech-cameroun.com","11839","19-06-2025 10:14:37","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005294562","S=
imbock OCM","","19-06-2025 10:13:21","18-06-2025 07:01:44","19-06-2025 07:0=
5:38","Bactracking Active // No power issue Ubaie:52.5V site on grid The Tx=
 Fme Hosiah Mbah (674007438 / Huawei) is informed","Hyemafo Gildas","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Bactracking Active // No power issue Ubaie:52.5V site on grid The Tx F=
me Hosiah Mbah (674007438 / Huawei) is informed","mouliom.anselme@matech-ca=
meroun.com","97898","19-06-2025 10:13:21","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005294502","O=
LAMA","","19-06-2025 10:02:52","18-06-2025 13:31:39","18-06-2025 13:35:35",=
"Bactraking : No power issue on site Ubaie =3D54.9V site on Gen The TX FME =
Henri (699949693) from Huawei is informed.","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Bactr=
aking : No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri =
(699949693) from Huawei is informed.","mouliom.anselme@matech-cameroun.com"=
,"73873","19-06-2025 10:02:52","MATECH CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0005294451","M=
atomb","","19-06-2025 09:55:28","18-06-2025 12:36:13","18-06-2025 12:58:57"=
,"Bactracking No power issue on site.Site on grid with Ubaie=3D54.2 V site =
on gen ,The TX FME Etienne(695033981) from Huawei is informed.","Kemeni Fra=
nklin","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Bactracking No power issue on site.Site on grid with Uba=
ie=3D54.2 V site on gen ,The TX FME Etienne(695033981) from Huawei is infor=
med.","mouliom.anselme@matech-cameroun.com","76756","19-06-2025 09:55:28","=
MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005294447","S=
ous Prefecture","","19-06-2025 09:54:46","19-06-2025 09:52:33","19-06-2025 =
10:21:23","ACTIVE//No power issue site on Grid Ubaie =3D55.7 V, The tx fme =
Fulbert (654266068/ Huawei) is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//=
No power issue site on Grid Ubaie =3D55.7 V, The tx fme Fulbert (654266068/=
 Huawei) is informed","edwige.kapawo@matech-cameroun.com","134","19-06-2025=
 09:54:46","MATECH CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0005294427","A=
cropole","","19-06-2025 09:53:33","18-06-2025 09:56:47","18-06-2025 09:58:1=
8","Bactracking Active // No power issue, Ubay=3D53. 8V Site on Grid The TX=
 FME Armand (691144412) from Huawei is informed","MINKA NICOLAS","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Bactracking Active // No power issue, Ubay=3D53. 8V Site on Grid The TX F=
ME Armand (691144412) from Huawei is informed","mouliom.anselme@matech-came=
roun.com","86206","19-06-2025 09:53:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005294422","C-Suprem=
e","","19-06-2025 09:52:44","19-06-2025 09:50:25","19-06-2025 10:32:39","Ca=
scaded Incident from TTO5456230","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site went down due to insufficient of rectifier on=
 site//Site stabilised","system","605670","19-06-2025 09:52:44","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005294421","Acropole=
","","19-06-2025 09:52:43","19-06-2025 09:50:25","19-06-2025 10:32:39","Cas=
caded Incident from TTO5456230","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to insufficient of =
rectifier on site//Site stabilised","system","605670","19-06-2025 09:52:43"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005294414","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","19-06-2025 09:51:34","19-06-2025 0=
9:50:25","19-06-2025 10:32:39","Site went down due to insufficient of recti=
fier on site//Site stabilised","MINKA NICOLAS","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module","Site went down due to insufficient of rect=
ifier on site//Site stabilised","edwige.kapawo@matech-cameroun.com","70","1=
9-06-2025 09:51:34","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005294229","M=
eyo","","19-06-2025 09:23:27","19-06-2025 09:20:18","19-06-2025 17:17:18","=
Grid Outage, Site went Down due to Gen overload (17KVA, 260A) SS HIS Felix =
Zambe is informed // Grid returned","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid Outage, Site went Down due to Gen=
 overload (17KVA, 260A) SS HIS Felix Zambe is informed // Grid returned","e=
dwige.kapawo@matech-cameroun.com","190","19-06-2025 09:23:27","MATECH CMR"
"Closed Complete","Site Down","CTR_068","IHS_YND_109","NOCINC0005294224","M=
obil-Essos","","19-06-2025 09:22:12","19-06-2025 09:19:00","19-06-2025 11:1=
9:58","Site went Down due to works, abena herman (699999625/Grato) Wass on =
site for Swap PWC // End of works","Siligap Boris","Equipment Replacement",=
"Passive","Planned Activity","Planned Activity - Passive","Site went Down d=
ue to works, abena herman (699999625/Grato) Wass on site for Swap PWC // En=
d of works","edwige.kapawo@matech-cameroun.com","192","19-06-2025 09:22:12"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005293050","OTELE MT=
N","","19-06-2025 04:23:48","19-06-2025 04:15:40","19-06-2025 05:20:07","Ca=
scaded Incident from TTO5454745","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage , site went down because th=
e controler did not send the starter order // controler reseted and Gen sta=
rted manually, gen left on manual mode","system","1243886","19-06-2025 04:2=
3:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005293051","Mom","",=
"19-06-2025 04:23:48","19-06-2025 04:15:40","19-06-2025 05:20:07","Cascaded=
 Incident from TTO5454745","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage , site went down because the cont=
roler did not send the starter order // controler reseted and Gen started m=
anually, gen left on manual mode","system","1243886","19-06-2025 04:23:48",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005293048","Mbeng","=
","19-06-2025 04:23:18","19-06-2025 04:15:40","19-06-2025 05:30:40","Cascad=
ed Incident from TTO5454744","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage , site went down because the co=
ntroler did not send the starter order // controler reseted and Gen started=
 manually, gen left on manual mode","system","619197","19-06-2025 04:23:18"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005293049","Bondjock=
","","19-06-2025 04:23:18","19-06-2025 04:15:40","19-06-2025 05:30:40","Cas=
caded Incident from TTO5454744","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage , site went down because the=
 controler did not send the starter order // controler reseted and Gen star=
ted manually, gen left on manual mode","system","619195","19-06-2025 04:23:=
18","MATECH CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0005293044","M=
inka","IHS_YND_369, IHS_YND_531, IHS_YND_370, IHS_YND_372","19-06-2025 04:2=
1:59","19-06-2025 04:15:40","19-06-2025 05:30:40","Grid outage , site went =
down because the controler did not send the starter order // controler rese=
ted and Gen started manually, gen left on manual mode","Fanda Brice","Equip=
ment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage , site =
went down because the controler did not send the starter order // controler=
 reseted and Gen started manually, gen left on manual mode","edwige.kapawo@=
matech-cameroun.com","380","19-06-2025 04:21:59","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005292967","S=
ous Prefecture","","19-06-2025 03:31:02","19-06-2025 03:22:59","19-06-2025 =
03:52:29","ACTIVE//No power issue site on Grid Ubaie =3D55.7 V, The tx fme =
Fulbert (654266068/ Huawei) is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//=
No power issue site on Grid Ubaie =3D55.7 V, The tx fme Fulbert (654266068/=
 Huawei) is informed","edwige.kapawo@matech-cameroun.com","484","19-06-2025=
 03:31:02","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005292224","A=
fanoya","","18-06-2025 22:48:22","18-06-2025 22:46:16","18-06-2025 23:01:31=
","Site went Down due to  insufficients of rectifiers // Site Stabilized","=
Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went Down due to  insufficients of rectifiers // Site Stabilized","e=
dwige.kapawo@matech-cameroun.com","127","18-06-2025 22:48:22","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005292223","MBA=
LNGONG LYCEE","","18-06-2025 22:48:14","18-06-2025 22:43:02","19-06-2025 08=
:44:15","Grid outage, landlord stopped the Gen because it's too noisy // we=
 have started the generator in the morning","Fanda Brice","Access Denial","=
Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid =
outage, landlord stopped the Gen because it's too noisy // we have started =
the generator in the morning","gerard.tchangoue@matech-cameroun.com","314",=
"18-06-2025 22:48:14","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005292010","Nko=
langaa","","18-06-2025 21:52:34","18-06-2025 21:43:13","18-06-2025 21:45:13=
","ACTIVE//no power issue on site U=3D52:6 V site on Grid Lionel Tchatchou =
(694693436) from Huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE/=
/no power issue on site U=3D52:6 V site on Grid Lionel Tchatchou (694693436=
) from Huawei is informed","franck.nkomot@matech-cameroun.com","562","18-06=
-2025 21:52:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005291989","Acropole=
","","18-06-2025 21:45:02","18-06-2025 21:42:57","18-06-2025 22:00:24","Cas=
caded Incident from TTO5453516","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to insufficient of =
rectifier on site // Site stabilized","system","635258","18-06-2025 21:45:0=
2","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005291990","C-Suprem=
e","","18-06-2025 21:45:02","18-06-2025 21:42:57","18-06-2025 22:00:24","Ca=
scaded Incident from TTO5453516","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site went down due to insufficient of rectifier on=
 site // Site stabilized","system","635259","18-06-2025 21:45:02","MATECH C=
MR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005291982","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","18-06-2025 21:44:03","18-06-2025 2=
1:42:57","18-06-2025 22:00:24","Site went down due to insufficient of recti=
fier on site // Site stabilized","MINKA NICOLAS","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to insufficient of re=
ctifier on site // Site stabilized","gaelle.njiofack@matech-cameroun.com","=
67","18-06-2025 21:44:03","MATECH CMR"
"Closed Complete","Site Down","T0395","IHS_YND_065","NOCINC0005291908","Ess=
os DCS","","18-06-2025 21:30:47","18-06-2025 17:19:39","18-06-2025 21:28:39=
","BACKTACKING. Active// No power issue, Site on Grid Ubai 52,9 V Technicia=
ns working on site. The Tx FME Armand Nguetsa/691144412 From HUAWEI is info=
rmed","Delor Telezing","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","BACKTACKING. Active// No power issue, Si=
te on Grid Ubai 52,9 V Technicians working on site. The Tx FME Armand Nguet=
sa/691144412 From HUAWEI is informed","franck.nkomot@matech-cameroun.com","=
15068","18-06-2025 21:30:47","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005291862","B=
arriere","","18-06-2025 21:20:40","18-06-2025 21:14:33","19-06-2025 00:07:4=
9","Active// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","gaelle.njiofack@matech-cameroun.com","368","18-06-2025 21:20:4=
0","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0005291245","Mendong =
vallee","","18-06-2025 19:47:50","18-06-2025 19:46:40","18-06-2025 23:48:40=
","Grid Outage, Site went Down due to Gen overload (20KVA; 300A) IHS F=E9li=
x Zamb=E9 is informed and confirmed // Grid return","Fanda Brice","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, Site went Do=
wn due to Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed and co=
nfirmed // Grid return","gaelle.njiofack@matech-cameroun.com","71","18-06-2=
025 19:47:50","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005291191","M=
vog-Manga","","18-06-2025 19:35:42","18-06-2025 19:30:19","18-06-2025 19:35=
:20","Site went down due to MPR DYSFONNCTION on site // Site stabilised","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site // Site stabilised","gaelle=
.njiofack@matech-cameroun.com","324","18-06-2025 19:35:42","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005291187","A=
bom","","18-06-2025 19:33:55","18-06-2025 19:32:48","18-06-2025 19:33:06","=
Grid outage, Site went down because Gen failed to start due to Gen Overload=
 (16KVA /300A) // Grid return","Siligap Boris","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen fail=
ed to start due to Gen Overload (16KVA /300A) // Grid return","gaelle.njiof=
ack@matech-cameroun.com","68","18-06-2025 19:33:55","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005291178","N=
KOLMEKONG YDE","","18-06-2025 19:30:41","18-06-2025 19:27:34","18-06-2025 1=
9:42:34","Site down due to IHS Fme Felix Mbateu work (changing bay battery)=
 // End of work","Fabrice Pouakam","Equipment Replacement","Passive","Plann=
ed Activity","Planned Activity - Passive","Site down due to IHS Fme Felix M=
bateu work (changing bay battery) // End of work","gaelle.njiofack@matech-c=
ameroun.com","189","18-06-2025 19:30:41","MATECH CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0005291165","Car=
refour Ayissi Ele","","18-06-2025 19:28:19","18-06-2025 18:40:09","18-06-20=
25 18:46:31","","Parker Tchoup","Cascade Outage","Active","Cascade Active",=
"Cascade Active","TX ISSUE (CMS: NO COM) AWAITING EVIDENCES","gaelle.njiofa=
ck@matech-cameroun.com","645975","18-06-2025 19:28:19","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005291158","NTU=
I TOWN","","18-06-2025 19:27:33","18-06-2025 19:23:26","18-06-2025 19:39:15=
","No power issue, Site impacted by Afambassi","Parker Tchoup","3RD Party P=
ower Failure","Passive","Power Provided By 3RD Party","Power Provided By 3R=
D Party","No power issue, Site impacted by Afambassi","gaelle.njiofack@mate=
ch-cameroun.com","248","18-06-2025 19:27:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_564","NOCINC0005291064","Mvog Mbi=
 New","","18-06-2025 19:04:36","17-06-2025 11:06:00","17-06-2025 11:08:21",=
"Backtraking Site went down due to insufficient of rectifier on site // Sit=
e stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down due to insufficient of rectifier on site // =
Site stabilized","gaelle.njiofack@matech-cameroun.com","115116","18-06-2025=
 19:04:36","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005291063","Eko=
umdoum OCM","","18-06-2025 19:04:35","18-06-2025 19:00:25","18-06-2025 19:3=
8:25","Grid outage,site went down because Gen failed to start due to PWC ZT=
E dysfunction//He reset it and started the Gen manually","Albran Byorel","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage,site went down because Gen failed to start due to PWC ZTE dysfunctio=
n//He reset it and started the Gen manually","franck.nkomot@matech-cameroun=
.com","544","18-06-2025 19:04:35","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005290899","Saa=
","IHS_YND_810","18-06-2025 18:46:17","18-06-2025 18:40:09","18-06-2025 18:=
46:31","Active// No power issue on site ,site on Gen with Ubaie =3D53.8V Th=
e Tx Technician from Huawei Gr=E9goire//654547479 is informed","Parker Tcho=
up","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// No power issue on site ,site on Gen with Ubaie =3D=
53.8V The Tx Technician from Huawei Gr=E9goire//654547479 is informed","fra=
nck.nkomot@matech-cameroun.com","369","18-06-2025 18:46:17","MATECH CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0005290895","Ngo=
uetou","","18-06-2025 18:45:08","18-06-2025 18:37:24","18-06-2025 18:48:24"=
,"Active // No power issue site on Gen, with Ubay: 52.3V. The Tx Fme Gregoi=
re (654547479) from Huawei is informed","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue site on Gen, with Ubay: 52.3V. The Tx Fme Gregoire (65454=
7479) from Huawei is informed","franck.nkomot@matech-cameroun.com","465","1=
8-06-2025 18:45:08","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005290687","O=
LAMA","","18-06-2025 17:56:47","18-06-2025 14:04:36","18-06-2025 17:58:56",=
"Bactraking : No power issue on site Ubaie =3D54.9V site on Gen The TX FME =
Henri (699949693) from Huawei is informed.","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Bactr=
aking : No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri =
(699949693) from Huawei is informed.","gaelle.njiofack@matech-cameroun.com"=
,"13932","18-06-2025 17:56:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005290682","Acropole=
","","18-06-2025 17:55:00","18-06-2025 17:50:43","18-06-2025 18:08:50","Cas=
caded Incident from TTO5452035","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Site went down due to insufficient of=
 rectifier on site // Site stabilized","system","1216705","18-06-2025 17:55=
:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005290683","C-Suprem=
e","","18-06-2025 17:55:00","18-06-2025 17:50:43","18-06-2025 18:08:50","Ca=
scaded Incident from TTO5452035","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","	Site went down due to insufficient of rectifier o=
n site // Site stabilized","system","1216704","18-06-2025 17:55:00","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005290679","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","18-06-2025 17:53:50","18-06-2025 1=
7:50:43","18-06-2025 18:08:50","	Site went down due to insufficient of rect=
ifier on site // Site stabilized","MINKA NICOLAS","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","	Site went down due to insufficient of =
rectifier on site // Site stabilized","gaelle.njiofack@matech-cameroun.com"=
,"188","18-06-2025 17:53:50","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005290580","N=
omayos montee Meche","","18-06-2025 17:33:51","18-06-2025 17:32:45","18-06-=
2025 17:34:53","Grid outage, site went down before Gen started due rectifie=
rs issue and poor battery backup // Grid returned","Fanda Brice","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge, site went down before Gen started due rectifiers issue and poor battery=
 backup // Grid returned","gaelle.njiofack@matech-cameroun.com","67","18-06=
-2025 17:33:51","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005290501","C=
-Supreme","","18-06-2025 17:21:56","18-06-2025 17:19:49","18-06-2025 17:24:=
57","No power issue, site on Battery with Ubaie=3D54.5V, Brice Tsague (650 =
21 40 96 / Huawei) is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue, site on Batt=
ery with Ubaie=3D54.5V, Brice Tsague (650 21 40 96 / Huawei) is informed","=
gaelle.njiofack@matech-cameroun.com","128","18-06-2025 17:21:56","MATECH CM=
R"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005290469","A=
wae Ewonkan","","18-06-2025 17:15:52","18-06-2025 17:14:46","18-06-2025 17:=
15:59","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","gaelle.njiofack@matech-cameroun.com","67","18-06-2025 17:15:52","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005290379","M=
vog-Manga","","18-06-2025 16:54:35","18-06-2025 16:50:28","18-06-2025 16:55=
:08","Site went down due to MPR DYSFONNCTION on site // Site stabilised","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site // Site stabilised","gaelle=
.njiofack@matech-cameroun.com","249","18-06-2025 16:54:35","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005290376","E=
mombo","","18-06-2025 16:54:08","18-06-2025 16:52:03","18-06-2025 16:58:03"=
,"Active// No power issue, site is on Grid with Ubaie=3D54,2V, Lionel Adjep=
(655184876) from Huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power issue, site is on Grid with Ubaie=3D54,2V, Lionel Adjep(65518487=
6) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","126","18=
-06-2025 16:54:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005290337","Nkolondo=
m","","18-06-2025 16:49:34","18-06-2025 16:44:42","18-06-2025 17:24:54","Ca=
scaded Incident from TTO5451643","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site down due to IHS Fme Felix Mbat=
eu work (changing bay battery) // end of work","system","652768","18-06-202=
5 16:49:34","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005290335","N=
KOLMEKONG YDE","IHS_YND_304","18-06-2025 16:48:48","18-06-2025 16:44:42","1=
8-06-2025 17:26:03","Site down due to IHS Fme Felix Mbateu work (changing b=
ay battery) // end of work","Fabrice Pouakam","Equipment Replacement","Pass=
ive","Planned Activity","Planned Activity - Passive","Site down due to IHS =
Fme Felix Mbateu work (changing bay battery) // end of work","gaelle.njiofa=
ck@matech-cameroun.com","248","18-06-2025 16:48:48","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005290243","ESS=
OS OASIS 1111","","18-06-2025 16:30:06","18-06-2025 16:27:37","18-06-2025 1=
7:23:23","Grid outage, Site went down because Gen overload (17kva, 250A)//G=
rid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, Site went down because Gen overload (17kva, 250A=
)//Grid returned","franck.nkomot@matech-cameroun.com","150","18-06-2025 16:=
30:06","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005290067","Ngo=
usso Vallee","","18-06-2025 15:57:26","18-06-2025 15:52:57","18-06-2025 16:=
00:57","Site went down because insufficient of rectifier on site //site sta=
bilized","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down because insufficient of rectifier on site //site =
stabilized","franck.nkomot@matech-cameroun.com","270","18-06-2025 15:57:26"=
,"MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005290062","Par=
adis Hotel","","18-06-2025 15:56:25","18-06-2025 15:52:17","18-06-2025 15:5=
8:17","Site went down due to MPR DYSFONNCTION on site / Site stabilised","S=
iligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site / Site stabilised","franck.=
nkomot@matech-cameroun.com","249","18-06-2025 15:56:25","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005289851","M=
vog-Manga","","18-06-2025 15:24:23","18-06-2025 15:22:15","18-06-2025 15:27=
:15","Site went down due to MPR DYSFONNCTION on site // Site stabilised","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site // Site stabilised","gaelle=
.njiofack@matech-cameroun.com","129","18-06-2025 15:24:23","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005289844","N=
KOLMEKONG YDE","IHS_YND_304","18-06-2025 15:23:30","18-06-2025 15:18:23","1=
8-06-2025 15:26:53"," Site down due to IHS Fme Felix Mbateu  work (changing=
 bay battery) // end of work","Fabrice Pouakam","Equipment Replacement","Pa=
ssive","Planned Activity","Planned Activity - Passive"," Site down due to I=
HS Fme Felix Mbateu  work (changing bay battery) // end of work","gaelle.nj=
iofack@matech-cameroun.com","309","18-06-2025 15:23:30","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005289831","N=
kolondom","","18-06-2025 15:22:32","18-06-2025 15:18:23","18-06-2025 15:26:=
53","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive"," Site down due to IHS Fme Felix Mbateu  work (changing bay ba=
ttery) // end of work","gaelle.njiofack@matech-cameroun.com","651070","18-0=
6-2025 15:22:32","MATECH CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0005289516","M=
ontee-Jouvence","","18-06-2025 14:42:52","18-06-2025 14:42:48","18-06-2025 =
14:58:48","No power issue u=3D53.3V site on GRID,The Tx FME Hosiah//6996996=
94 is informed","Hyemafo Gildas","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue u=3D53.3V site =
on GRID,The Tx FME Hosiah//699699694 is informed","gaelle.njiofack@matech-c=
ameroun.com","5","18-06-2025 14:42:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_215","NOCINC0005289421","Eleveurs=
","","18-06-2025 14:30:01","18-06-2025 14:18:59","18-06-2025 14:32:59","Cas=
caded Incident from TTO5450609","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because SS IHS is on si=
te for plan work (secure transmission) // End of work","system","1215071","=
18-06-2025 14:30:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_739","NOCINC0005289422","NKOLMESS=
ING rue Manguier","","18-06-2025 14:30:01","18-06-2025 14:18:59","18-06-202=
5 15:12:59","Grid outage, Gen turn but did not feeding the site due to GE c=
ircuit breaker disjunct // Circuit Breaker Rearm","Siligap Boris","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Load Breaker","Grid outage, Gen turn=
 but did not feeding the site due to GE circuit breaker disjunct // Circuit=
 Breaker Rearm","system","662","18-06-2025 14:30:01","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005289417","E=
SSOS OASIS 1111","","18-06-2025 14:29:43","18-06-2025 14:26:37","18-06-2025=
 16:07:37","Grid outage, Site went down because Gen overload (17kva, 250A)/=
/Grid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down because Gen overload (17kva, 25=
0A)//Grid returned","gaelle.njiofack@matech-cameroun.com","187","18-06-2025=
 14:29:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005289411","C-Suprem=
e","","18-06-2025 14:28:49","18-06-2025 14:22:19","18-06-2025 14:26:33","Ca=
scaded Incident from TTO5450603","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site went down due to insufficient of rectifier on=
 site // Site stabilized","system","654357","18-06-2025 14:28:49","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005289410","Acropole=
","","18-06-2025 14:28:49","18-06-2025 14:22:19","18-06-2025 14:26:33","Cas=
caded Incident from TTO5450603","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to insufficient of =
rectifier on site // Site stabilized","system","654357","18-06-2025 14:28:4=
9","MATECH CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0005289408","Nko=
lmesseng","IHS_YND_215","18-06-2025 14:28:41","18-06-2025 14:18:59","18-06-=
2025 14:32:59","Site went down because SS IHS is on site for plan work (sec=
ure transmission) // End of work","Siligap Boris","Installation Activity","=
Passive","Planned Activity","Installation Activity","Site went down because=
 SS IHS is on site for plan work (secure transmission) // End of work","fra=
nck.nkomot@matech-cameroun.com","582","18-06-2025 14:28:41","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005289404","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","18-06-2025 14:27:26","18-06-2025 1=
4:22:19","18-06-2025 14:26:33","Site went down due to insufficient of recti=
fier on site // Site stabilized","MINKA NICOLAS","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to insufficient of re=
ctifier on site // Site stabilized","gaelle.njiofack@matech-cameroun.com","=
308","18-06-2025 14:27:26","MATECH CMR"
"Closed Complete","Site Down","CTR_356","IHS_YND_376","NOCINC0005289169","M=
amb","","18-06-2025 13:49:23","18-06-2025 13:10:14","18-06-2025 13:30:40","=
No power issue, Site on Grid Ubaie: 54.5 V, The FME Tx Etienne/695033981 Fr=
om Huawei is informed.","Kemeni Franklin","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, Site =
on Grid Ubaie: 54.5 V, The FME Tx Etienne/695033981 From Huawei is informed=
.","gaelle.njiofack@matech-cameroun.com","2350","18-06-2025 13:49:23","MATE=
CH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005289073","Man=
guiers Dispensaire","","18-06-2025 13:32:33","18-06-2025 13:29:16","18-06-2=
025 14:25:16","Fme Fabrice has been informed and reported rectifier issue (=
3/5 faulty rectifiers), SS IHS Bernard is informed // He reset rectifiers, =
site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Fme Fabrice has been informed and reported rectifier issu=
e (3/5 faulty rectifiers), SS IHS Bernard is informed // He reset rectifier=
s, site on Grid","loic.noumsi@matech-cameroun.com","198","18-06-2025 13:32:=
33","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005289016","N=
KOLMEKONG YDE","IHS_YND_304","18-06-2025 13:20:51","18-06-2025 12:19:17","1=
8-06-2025 12:23:00","Backtraking // Site went down due to work (changing ba=
y battery) // end of work","Fabrice Pouakam","Equipment Replacement","Passi=
ve","Planned Activity","Planned Activity - Passive","Site went down due to =
work (changing bay battery) // end of work","gaelle.njiofack@matech-camerou=
n.com","3696","18-06-2025 13:20:51","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005288966","M=
imboman-Ecole","","18-06-2025 13:11:11","18-06-2025 13:02:00","18-06-2025 1=
3:34:48","Grid outage, Gen  stopped due to Alarm Oil pressure // We reset c=
ard GE and genmanually started","Mba Lazare Herve","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage, Gen  stopped due to=
 Alarm Oil pressure // We reset card GE and genmanually started","gaelle.nj=
iofack@matech-cameroun.com","552","18-06-2025 13:11:11","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005288947","N=
GONA","","18-06-2025 13:10:04","18-06-2025 12:56:56","18-06-2025 14:51:56",=
"Grid outage,site went down because Gen failed to start due to battery GE f=
aulty //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - Generator Battery","Grid outage,site went down because Gen f=
ailed to start due to battery GE faulty //Grid returned","gaelle.njiofack@m=
atech-cameroun.com","790","18-06-2025 13:10:04","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005288941","M=
ontee-Des-Soeurs","","18-06-2025 13:09:05","18-06-2025 13:07:00","18-06-202=
5 20:09:57","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) //=
 Grid returned","gaelle.njiofack@matech-cameroun.com","126","18-06-2025 13:=
09:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_217","NOCINC0005288893","Abom",""=
,"18-06-2025 13:02:19","18-06-2025 12:52:38","18-06-2025 13:12:30","Cascade=
d Incident from TTO5449976","Siligap Boris","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, gen failed to start due to al=
arm ""low oil pressure""//We reset card GE and gen manually started","syste=
m","1212941","18-06-2025 13:02:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_739","NOCINC0005288890","NKOLMESS=
ING rue Manguier","","18-06-2025 13:02:18","18-06-2025 12:52:38","18-06-202=
5 13:12:30","Cascaded Incident from TTO5449976","Siligap Boris","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid outage, gen faile=
d to start due to alarm ""low oil pressure""//We reset card GE and gen manu=
ally started","system","1212940","18-06-2025 13:02:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_214","NOCINC0005288892","Nkolmess=
eng-II","","18-06-2025 13:02:18","18-06-2025 12:52:38","18-06-2025 13:12:30=
","Cascaded Incident from TTO5449976","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, gen failed to start=
 due to alarm ""low oil pressure""//We reset card GE and gen manually start=
ed","system","1212943","18-06-2025 13:02:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_213","NOCINC0005288889","Nkolmess=
eng","","18-06-2025 13:02:17","18-06-2025 12:52:38","18-06-2025 13:12:30","=
Cascaded Incident from TTO5449976","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, gen failed to start du=
e to alarm ""low oil pressure""//We reset card GE and gen manually started"=
,"system","1212942","18-06-2025 13:02:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_215","NOCINC0005288888","Eleveurs=
","","18-06-2025 13:02:17","18-06-2025 12:52:38","18-06-2025 13:12:30","Cas=
caded Incident from TTO5449976","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, gen failed to start due t=
o alarm ""low oil pressure""//We reset card GE and gen manually started","s=
ystem","1212944","18-06-2025 13:02:17","MATECH CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0005288850","Nko=
lmesseng","IHS_YND_215, IHS_YND_213, IHS_YND_739, IHS_YND_214, IHS_YND_217"=
,"18-06-2025 12:55:46","18-06-2025 12:52:38","18-06-2025 13:12:30","Grid ou=
tage, gen failed to start due to alarm ""low oil pressure""//We reset card =
GE and gen manually started","Siligap Boris","Equipment Repair","Passive","=
ACDG Gen","ACDG - Low Oil Pressure","Grid outage, gen failed to start due t=
o alarm ""low oil pressure""//We reset card GE and gen manually started","g=
aelle.njiofack@matech-cameroun.com","189","18-06-2025 12:55:46","MATECH CMR=
"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005288793","Ron=
d Point Express1114","","18-06-2025 12:47:14","18-06-2025 12:44:08","18-06-=
2025 12:46:32","Active: No power issue, site is on grid with Ubaie=3D54,7V,=
 Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active: No power issue, site is on grid with Ubaie=3D54,7V, Mbah hosiah(=
699699694) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","=
187","18-06-2025 12:47:14","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005288786","Beh=
ind P T school Yde","","18-06-2025 12:45:43","18-06-2025 12:42:33","18-06-2=
025 14:50:33","Site went down due to plan work (swap of MPR) done by our FM=
E Paul on site // End of work","Paul BIBOUM","Installation Activity","Passi=
ve","Planned Activity","Installation Activity","Site went down due to plan =
work (swap of MPR) done by our FME Paul on site // End of work","loic.noums=
i@matech-cameroun.com","191","18-06-2025 12:45:43","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005288766","OBA=
M NGOLA OCM","","18-06-2025 12:42:25","18-06-2025 12:36:18","21-06-2025 18:=
33:29","Site went down due to PM (taking apart or relocation of site) done =
by KAKOK (Clean_IT/671619506) // End of work","MINKA NICOLAS","Installation=
 Activity","Passive","Planned Activity","Installation Activity","Site went =
down due to PM (taking apart or relocation of site) done by KAKOK (Clean_IT=
/671619506) // End of work","loic.noumsi@matech-cameroun.com","368","18-06-=
2025 12:42:25","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0005288736","NKO=
ABANG NKOLO 3","","18-06-2025 12:36:23","18-06-2025 12:30:17","18-06-2025 1=
4:20:17","Grid outage,Site went down due to gen overload(10KVA, 130A) // he=
 reduced the load and started Gen manually","Mba Lazare Herve","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue to gen overload(10KVA, 130A) // he reduced the load and started Gen manu=
ally","loic.noumsi@matech-cameroun.com","367","18-06-2025 12:36:23","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005288664","C=
hapelle-Nsimeyong","","18-06-2025 12:27:36","18-06-2025 12:24:26","18-06-20=
25 18:11:19","Site went down because Achille FOTSO (694271069/SS IHS) is on=
 site for Plan work (SWAP IPT et GEN) // END of work","MINKA NICOLAS","Equi=
pment Replacement","Passive","Planned Activity","Planned Activity - Passive=
","Site went down because Achille FOTSO (694271069/SS IHS) is on site for P=
lan work (SWAP IPT et GEN) // END of work","loic.noumsi@matech-cameroun.com=
","191","18-06-2025 12:27:36","MATECH CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0005288652","E=
mombo","","18-06-2025 12:25:11","18-06-2025 12:22:02","18-06-2025 13:17:08"=
,"Site went down due to disjunction of CB(32A) Gen // he rearmed the CB and=
 site on Gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Load Breaker","Site went down due to disjunction of CB(32A) Gen // he=
 rearmed the CB and site on Gen","gaelle.njiofack@matech-cameroun.com","190=
","18-06-2025 12:25:11","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005288648","N=
yom OCM","","18-06-2025 12:24:35","18-06-2025 12:06:22","18-06-2025 12:30:0=
0","Site went down due to PWC ZTE dysfunctionned // site stabilized","Fabri=
ce Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Over=
loaded","Site went down due to PWC ZTE dysfunctionned // site stabilized","=
gaelle.njiofack@matech-cameroun.com","1095","18-06-2025 12:24:35","MATECH C=
MR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005288644","N=
kolondom","","18-06-2025 12:23:59","18-06-2025 12:19:17","18-06-2025 12:23:=
00","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Site went down due to work (changing bay battery) // end of w=
ork","gaelle.njiofack@matech-cameroun.com","661666","18-06-2025 12:23:59","=
MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005288494","F=
ouda-New","","18-06-2025 12:16:01","18-06-2025 12:11:53","18-06-2025 12:20:=
47","	Grid Outage, site went down before Gen start due to Poor battery back=
up // Grid returned","Delor Telezing","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","	Grid Outage, site went down before =
Gen start due to Poor battery backup // Grid returned","gaelle.njiofack@mat=
ech-cameroun.com","248","18-06-2025 12:16:01","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005288415","M=
anguier","","18-06-2025 12:06:59","18-06-2025 12:03:36","18-06-2025 12:13:1=
1","	Grid outage, site went down before gen start due to poor battery backu=
p // Gen Started Automatically","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","	Grid outage, site went =
down before gen start due to poor battery backup // Gen Started Automatical=
ly","gaelle.njiofack@matech-cameroun.com","203","18-06-2025 12:06:59","MATE=
CH CMR"
"Closed Complete","Site Down","T1549","IHS_YND_295","NOCINC0005288357","NGO=
NA","","18-06-2025 11:56:46","18-06-2025 11:55:38","18-06-2025 12:17:31","G=
rid outage,site went down because Gen failed to start due to battery GE fau=
lty //Grid returned","Mba Lazare Herve","Equipment Repair","Passive","ACDG =
Gen","ACDG - Generator Battery","Grid outage,site went down because Gen fai=
led to start due to battery GE faulty //Grid returned","loic.noumsi@matech-=
cameroun.com","69","18-06-2025 11:56:46","MATECH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0005288343","Mvo=
g-Ada_OCM","","18-06-2025 11:54:44","18-06-2025 11:51:39","18-06-2025 12:18=
:12","Grid only on site, No space on site to deploy MDGE//Grid returned",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
nly on site, No space on site to deploy MDGE//Grid returned","loic.noumsi@m=
atech-cameroun.com","186","18-06-2025 11:54:44","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005288336","C=
omplexe-BEAC","","18-06-2025 11:53:43","18-06-2025 11:52:36","18-06-2025 11=
:53:39","Grid fluctuation, site went down because Gen failed to due Grid fl=
uctuatuion // Grid stabilized","Albran Byorel","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Grid fluctuation, site went d=
own because Gen failed to due Grid fluctuatuion // Grid stabilized","gaelle=
.njiofack@matech-cameroun.com","67","18-06-2025 11:53:43","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005288169","ESS=
OS OASIS 1111","","18-06-2025 11:16:43","18-06-2025 11:15:26","18-06-2025 1=
4:06:50","Grid outage, Site went down because Gen overload (17kva, 250A)//G=
rid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, Site went down because Gen overload (17kva, 250A=
)//Grid returned","loic.noumsi@matech-cameroun.com","78","18-06-2025 11:16:=
43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_334","NOCINC0005288114","Mfou OCM=
","","18-06-2025 11:12:38","18-06-2025 09:44:18","18-06-2025 11:28:18","Cas=
caded Incident from TTO5448983","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to Fui=
l shortage // Refueling done.","system","663813","18-06-2025 11:12:38","MAT=
ECH CMR"
"Closed Complete","Site Down","T2564","IHS_YND_739","NOCINC0005287944","NKO=
LMESSING rue Manguier","","18-06-2025 10:45:45","18-06-2025 10:28:07","18-0=
6-2025 11:28:36","Grid outage, Gen turn but did not feeding the site due to=
 GE circuit breaker disjunct // Circuit Breaker Rearm","Siligap Boris","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Grid outage, Gen=
 turn but did not feeding the site due to GE circuit breaker disjunct // Ci=
rcuit Breaker Rearm","ludivine.ngamaleu@ihstowers.com","1059","18-06-2025 1=
0:45:45","MATECH CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0005287897","Ele=
veurs","","18-06-2025 10:35:17","18-06-2025 10:29:11","18-06-2025 11:41:46"=
,"Grid outage, site went down because Gen failed to start due to contactor =
Gen faulty//  We manually activated Gen contactor and site on Gen","Siligap=
 Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Gr=
id outage, site went down because Gen failed to start due to contactor Gen =
faulty//  We manually activated Gen contactor and site on Gen","gaelle.njio=
fack@matech-cameroun.com","367","18-06-2025 10:35:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005287870","Mbeng","=
","18-06-2025 10:29:06","18-06-2025 10:15:33","18-06-2025 11:00:12","Cascad=
ed Incident from TTO5448783","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid hybrid Gen : Grid outage, site went do=
wn because Gen failed to start due to PWC dysfunctioning // Gen started man=
ually","system","1222470","18-06-2025 10:29:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005287872","Bondjock=
","","18-06-2025 10:29:06","18-06-2025 10:15:33","18-06-2025 11:00:12","Cas=
caded Incident from TTO5448783","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid hybrid Gen : Grid outage, site went=
 down because Gen failed to start due to PWC dysfunctioning // Gen started =
manually","system","1222469","18-06-2025 10:29:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005287843","OTELE MT=
N","","18-06-2025 10:23:38","18-06-2025 10:17:33","18-06-2025 10:54:53","Ca=
scaded Incident from TTO5448784","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid hybrid Gen : Grid outage, site wen=
t down because Gen failed to start due to PWC dysfunctioning // Gen started=
 manually","system","1222349","18-06-2025 10:23:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005287844","Mom","",=
"18-06-2025 10:23:38","18-06-2025 10:17:33","18-06-2025 10:54:53","Cascaded=
 Incident from TTO5448784","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid hybrid Gen : Grid outage, site went down=
 because Gen failed to start due to PWC dysfunctioning // Gen started manua=
lly","system","1222350","18-06-2025 10:23:38","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0005287801","Min=
ka","IHS_YND_369, IHS_YND_531, IHS_YND_370, IHS_YND_372","18-06-2025 10:19:=
55","18-06-2025 10:15:33","18-06-2025 11:00:12","Grid hybrid Gen : Grid out=
age, site went down because Gen failed to start due to PWC dysfunctioning /=
/ Gen started manually","Fanda Brice","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Grid hybrid Gen : Grid outage, site went=
 down because Gen failed to start due to PWC dysfunctioning // Gen started =
manually","gaelle.njiofack@matech-cameroun.com","447","18-06-2025 10:19:55"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005287728","M=
vog Mbi New","","18-06-2025 10:12:29","18-06-2025 10:06:45","18-06-2025 10:=
11:02","Site went down due to insufficient of rectifier on site // Site sta=
bilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficient of rectifier on site // Site =
stabilized","gaelle.njiofack@matech-cameroun.com","345","18-06-2025 10:12:2=
9","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005287658","M=
ontee-Des-Soeurs","","18-06-2025 10:04:08","18-06-2025 09:59:00","18-06-202=
5 12:55:17","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) //=
 Grid returned","gaelle.njiofack@matech-cameroun.com","310","18-06-2025 10:=
04:08","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005287651","M=
eyo","","18-06-2025 10:02:54","18-06-2025 10:00:44","18-06-2025 10:35:57","=
Grid Outage, Site went Down due to Gen overload (17KVA, 260A) SS HIS Felix =
Zambe is informed // Grid returned","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid Outage, Site went Down due to Gen=
 overload (17KVA, 260A) SS HIS Felix Zambe is informed // Grid returned","g=
aelle.njiofack@matech-cameroun.com","131","18-06-2025 10:02:54","MATECH CMR=
"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0005287553","Mfo=
u EPC","IHS_YND_334","18-06-2025 09:47:23","18-06-2025 09:44:18","18-06-202=
5 11:28:18","Grid outage, Gen stopped due to Fuil shortage // Refueling don=
e.","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage, Gen stopped due to Fuil shortage // Refueling done.","loic.noums=
i@matech-cameroun.com","186","18-06-2025 09:47:23","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005287532","C=
-Supreme","","18-06-2025 09:43:09","18-06-2025 09:40:01","18-06-2025 10:14:=
01","	Active // No power issue, site on Battery with Ubaie=3D55V, Brice Tsa=
gue (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","	Active // No power=
 issue, site on Battery with Ubaie=3D55V, Brice Tsague (650 21 40 96 / Huaw=
ei) is informed","gaelle.njiofack@matech-cameroun.com","189","18-06-2025 09=
:43:09","MATECH CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0005287482","M=
ontee-Jouvence","","18-06-2025 09:35:18","18-06-2025 09:32:12","18-06-2025 =
12:28:09","	ACTIVE//No power issue u=3D54.2V site on GRID,The Tx FME Hosiah=
//699699694 is informed","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","	ACTIVE//No power iss=
ue u=3D54.2V site on GRID,The Tx FME Hosiah//699699694 is informed","gaelle=
.njiofack@matech-cameroun.com","187","18-06-2025 09:35:18","MATECH CMR"
"Closed Complete","Site Down","T1085","IHS_YND_130","NOCINC0005287342","Bas=
tos usine","","18-06-2025 09:14:35","18-06-2025 09:11:33","18-06-2025 09:59=
:02","Grid outage, site went down due to Fuel shortage // Refuelling done",=
"Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge, site went down due to Fuel shortage // Refuelling done","loic.noumsi@ma=
tech-cameroun.com","182","18-06-2025 09:14:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005287332","Golf Qua=
ter","","18-06-2025 09:12:57","18-06-2025 09:09:38","18-06-2025 09:57:15","=
Cascaded Incident from TTO5448263","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
Fuel shortage // Refuelling done","system","665848","18-06-2025 09:12:57","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005287333","Bastos B=
ethesda","","18-06-2025 09:12:57","18-06-2025 09:09:38","18-06-2025 09:57:1=
5","Cascaded Incident from TTO5448263","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to Fuel shortage // Refuelling done","system","665848","18-06-2025 09:12:5=
7","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005287330","B=
astos-Nylon","IHS_YND_220, IHS_YND_563","18-06-2025 09:11:48","18-06-2025 0=
9:09:38","18-06-2025 09:57:15","Grid outage, site went down due to Fuel sho=
rtage // Refuelling done","Mboua Thierry","Fuel Outage","Passive","Diesel",=
"Diesel Outage","Grid outage, site went down due to Fuel shortage // Refuel=
ling done","gaelle.njiofack@matech-cameroun.com","131","18-06-2025 09:11:48=
","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005286753","S=
OA TOWN","","18-06-2025 07:06:40","18-06-2025 07:01:32","18-06-2025 07:42:5=
0","Site went down due to work of Bigans (679161144//Dowen) is on site ( sw=
ap of PWC )//End of work","Siligap Boris","Installation Activity","Passive"=
,"Planned Activity","Installation Activity","Site went down due to work of =
Bigans (679161144//Dowen) is on site ( swap of PWC )//End of work","loic.no=
umsi@matech-cameroun.com","309","18-06-2025 07:06:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005286710","Nkolondo=
m","","18-06-2025 06:52:33","18-06-2025 06:48:55","18-06-2025 10:01:49","Ca=
scaded Incident from TTO5447582","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due to battery GE faulty //Gen manually started with ex=
ternal battery","system","674159","18-06-2025 06:52:33","MATECH CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0005286706","NKO=
LMEKONG YDE","IHS_YND_304","18-06-2025 06:51:49","18-06-2025 06:48:55","18-=
06-2025 10:04:40","Grid outage site went down because Gen failed to start d=
ue to battery GE faulty //Gen manually started with external battery","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batt=
ery","Grid outage site went down because Gen failed to start due to battery=
 GE faulty //Gen manually started with external battery","loic.noumsi@matec=
h-cameroun.com","175","18-06-2025 06:51:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0005286539","Jean Ves=
pa 2","","18-06-2025 06:08:58","18-06-2025 06:06:44","18-06-2025 06:47:09",=
"Cascaded Incident from TTO5447396","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause Gen failed to start due to grid bad voltage No crcp // He bypassed t=
he grid and started Gen manually","system","676652","18-06-2025 06:08:58","=
MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0005286537","J=
-Vespa","IHS_YND_544","18-06-2025 06:07:56","18-06-2025 06:06:44","18-06-20=
25 06:47:09","Grid fluctuation, site went down because Gen failed to start =
due to grid bad voltage No crcp // He bypassed the grid and started Gen man=
ually","Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation, site went down because Gen failed t=
o start due to grid bad voltage No crcp // He bypassed the grid and started=
 Gen manually","vanel.mbiada@matech-cameroun.com","72","18-06-2025 06:07:56=
","MATECH CMR"
"Closed Complete","Site Down","T1085","IHS_YND_130","NOCINC0005286411","Bas=
tos usine","","18-06-2025 05:19:15","18-06-2025 05:12:57","18-06-2025 05:26=
:29","Grid outage, Gen failed to start due to unknow raison because we have=
 Access issues during the Night due to lanlord (FME will be on site fore mo=
re investigation) // Grid return","Mboua Thierry","Access Denial","Lease Or=
 Legal","Landlord Related Issues","Access Issue - Land Lord","Access issues=
 during the Night due to lanlord","cedric.tiani@matech-cameroun.com","378",=
"18-06-2025 05:19:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005286401","Bastos B=
ethesda","","18-06-2025 05:14:04","18-06-2025 05:10:03","18-06-2025 05:25:4=
3","Cascaded Incident from TTO5447230","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Acces issue during the Night//G=
rid return","system","680019","18-06-2025 05:14:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005286400","Golf Qua=
ter","","18-06-2025 05:14:04","18-06-2025 05:10:03","18-06-2025 05:25:43","=
Cascaded Incident from TTO5447230","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Acces issue during the Night//Grid =
return","system","680020","18-06-2025 05:14:04","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005286387","B=
astos-Nylon","IHS_YND_220, IHS_YND_563","18-06-2025 05:13:16","18-06-2025 0=
5:10:03","18-06-2025 05:25:43","Acces issue during the Night//Grid return",=
"Mboua Thierry","Access Denial","Lease Or Legal","Landlord Related Issues",=
"Access Issue - Land Lord","Acces issue during the Night//Grid return","van=
el.mbiada@matech-cameroun.com","194","18-06-2025 05:13:16","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005286302","Fla=
menco","","18-06-2025 04:35:05","18-06-2025 04:31:45","18-06-2025 05:19:24"=
,"Access issues during the Night due to LANDLORD ,Site went dowm because Ge=
n failed to start (investigation ongoing) //Grid return","Mboua Thierry","A=
ccess Denial","Lease Or Legal","Landlord Related Issues","Access Issue - La=
nd Lord","Access issues during the Night due to LANDLORD ,Site went dowm be=
cause Gen failed to start (investigation ongoing)","cedric.tiani@matech-cam=
eroun.com","201","18-06-2025 04:35:05","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005286299","NKO=
MKANA ELIZA HOTEL","","18-06-2025 04:33:53","18-06-2025 04:25:44","18-06-20=
25 05:17:00","Grid outage .no space to deploy mobile gen//Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age .no space to deploy mobile gen//Grid return","cedric.tiani@matech-camer=
oun.com","490","18-06-2025 04:33:53","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005285693","O=
LAMA","","18-06-2025 01:40:08","18-06-2025 01:32:52","18-06-2025 01:45:38",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.9V site on Gen The TX FME Henri (699949693) from Huawei is=
 informed.","vanel.mbiada@matech-cameroun.com","437","18-06-2025 01:40:08",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005284920","M=
vog-Manga","","17-06-2025 22:30:05","17-06-2025 22:26:50","17-06-2025 23:29=
:50","Site went down due to MPR DYSFONNCTION on site // Site stabilised","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site // Site stabilised","vanel.=
mbiada@matech-cameroun.com","196","17-06-2025 22:30:05","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005284857","Ako=
k Ndoe Yde","","17-06-2025 22:18:25","17-06-2025 22:16:15","17-06-2025 22:1=
9:39","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started automatically","Hyemafo Gildas","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup// Gen started automatically","gerard.tchang=
oue@matech-cameroun.com","131","17-06-2025 22:18:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005284616","MEHANDAN=
","","17-06-2025 21:30:34","17-06-2025 21:26:21","17-06-2025 21:35:40","Cas=
caded Incident from TTO5445262","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","700674","17-06-2025 21:30:34","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005284607","O=
dza II OCM","IHS_YND_528","17-06-2025 21:29:31","17-06-2025 21:26:21","17-0=
6-2025 21:35:40","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","edwige.kapawo@matech-cameroun.com","192","17-06-20=
25 21:29:31","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005284548","O=
dza-PK10","","17-06-2025 21:18:42","17-06-2025 21:12:36","17-06-2025 22:54:=
22","site went down due to insuficient rectifier on site (03)//he need to a=
dd 02 rectifiers","Albran Byorel","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","site went down due to insuficient rectifier on site (03=
)//he need to add 02 rectifiers","edwige.kapawo@matech-cameroun.com","367",=
"17-06-2025 21:18:42","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005284295","ODZ=
A BORNE 10","","17-06-2025 20:41:49","17-06-2025 20:41:46","17-06-2025 21:3=
2:08","Site wet down due to insufficient (03) rectifiers on site //He need =
to add one or two","Albran Byorel","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site wet down due to insufficient (03) rectifiers on s=
ite //He need to add one or two","gerard.tchangoue@matech-cameroun.com","3"=
,"17-06-2025 20:41:49","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005284205","Mes=
sassi 2","","17-06-2025 20:25:10","17-06-2025 20:20:03","17-06-2025 22:50:2=
5","Site went down due to CB(125A)in PWC that feeds MTN //He rearmed it","F=
abrice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabinet=
 - Circuit Breaker Issue","Site went down due to CB(125A)in PWC that feeds =
MTN //He rearmed it","gerard.tchangoue@matech-cameroun.com","309","17-06-20=
25 20:25:10","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005284202","B=
arriere","","17-06-2025 20:24:52","17-06-2025 20:21:47","17-06-2025 20:26:1=
6","Active// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","edwige.kapawo@matech-cameroun.com","187","17-06-2025 20:24:52"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005284185","O=
dza II OCM","","17-06-2025 20:21:42","17-06-2025 20:16:34","17-06-2025 20:2=
0:53","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","edwige.kapawo@matech-cameroun.com","310","17-06-2025 20:21:42=
","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005284142","M=
ontee-Des-Soeurs","","17-06-2025 20:13:06","17-06-2025 20:09:49","17-06-202=
5 22:39:56","Access issue during the  night due to landlord. Grid Fluctuati=
on ,site down due to Gen overload (15 KVA/210 A) // Grid returned","Hyemafo=
 Gildas","Access Denial","Lease Or Legal","Landlord Related Issues","Access=
 Issue - Land Lord","Access issue during the  night due to landlord. Grid F=
luctuation ,site down due to Gen overload (15 KVA/210 A) // Grid returned",=
"edwige.kapawo@matech-cameroun.com","198","17-06-2025 20:13:06","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005283830","SOA VILL=
AGE","","17-06-2025 19:20:44","17-06-2025 19:17:12","17-06-2025 22:18:21","=
Cascaded Incident from TTO5444395","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work of Bigan=
s  (679161144//Dowen) is on site ( swap of  PWC )//End of work","system","7=
01417","17-06-2025 19:20:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005283828","Mfou EPC=
","","17-06-2025 19:19:50","17-06-2025 19:17:10","17-06-2025 19:39:41","Cas=
caded Incident from TTO5444394","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid return","system","701419","17-06-2025 19:1=
9:50","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005283825","SOA=
 TOWN","IHS_YND_323","17-06-2025 19:19:22","17-06-2025 19:15:12","17-06-202=
5 22:18:21","Site went down due to work of Bigans  (679161144//Dowen) is on=
 site ( swap of  PWC )//End of work","Siligap Boris","Installation Activity=
","Passive","Planned Activity","Installation Activity","Site went down due =
to work of Bigans  (679161144//Dowen) is on site ( swap of  PWC )//End of w=
ork","gerard.tchangoue@matech-cameroun.com","499","17-06-2025 19:19:22","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005283824","M=
fou OCM","IHS_YND_674","17-06-2025 19:19:17","17-06-2025 19:17:10","17-06-2=
025 19:39:41","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Start=
ed due to poor backup //Grid return","edwige.kapawo@matech-cameroun.com","1=
28","17-06-2025 19:19:17","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005283614","A=
fanoya","","17-06-2025 18:43:51","17-06-2025 18:36:19","17-06-2025 19:06:20=
","Grid outage,site went down because Gen failed to start due to Fuse Gen c=
ard faulty // Site on Grid","Hyemafo Gildas","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage,site went down because Gen fa=
iled to start due to Fuse Gen card faulty // Site on Grid","edwige.kapawo@m=
atech-cameroun.com","453","17-06-2025 18:43:51","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005283581","Ron=
d Point Express1114","","17-06-2025 18:36:56","17-06-2025 18:33:50","17-06-=
2025 18:41:56","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen start automatically","gerard=
.tchangoue@matech-cameroun.com","187","17-06-2025 18:36:56","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005283459","Nko=
abang2","","17-06-2025 18:15:52","17-06-2025 18:10:47","17-06-2025 19:13:14=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","gerard.t=
changoue@matech-cameroun.com","307","17-06-2025 18:15:52","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005283173","NYO=
M 2 IHS","","17-06-2025 17:39:04","17-06-2025 17:30:48","17-06-2025 19:53:1=
9","Site went down due to work: Our RM Willy Kamga (699003823//Matech) with=
 IHS is on site for swap PWC // End of work","Fabrice Pouakam","Installatio=
n Activity","Passive","Planned Activity","Installation Activity","Site went=
 down due to work: Our RM Willy Kamga (699003823//Matech) with IHS is on si=
te for swap PWC // End of work","gerard.tchangoue@matech-cameroun.com","498=
","17-06-2025 17:39:04","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005283127","Nko=
lbisson IITA LP","","17-06-2025 17:28:17","17-06-2025 17:21:06","17-06-2025=
 17:50:39","No power issue site on grid with U=3D53.8v Mohamadou(69114435) =
from Huawei is informed	","","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D53.8v Mohamadou(69114435) from Huawei is informed	","gerard.tchangoue@ma=
tech-cameroun.com","432","17-06-2025 17:28:17","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005283075","Fou=
da Quarter","","17-06-2025 17:24:03","17-06-2025 17:14:57","17-06-2025 18:3=
8:38","grid bad voltage, site went down because gen fails to start due to l=
ack of 01 phase on site // he did a brdge with a good phase","Delor Telezin=
g","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"grid bad voltage, site went down because gen fails to start due to lack o=
f 01 phase on site // he did a brdge with a good phase","gerard.tchangoue@m=
atech-cameroun.com","547","17-06-2025 17:24:03","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005283009","E=
vodoula OCM","","17-06-2025 17:11:27","17-06-2025 17:08:19","17-06-2025 19:=
05:35","grid outage,gen failed to start due to grid bad voltage,no rcp// Gr=
id return","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","grid outage,gen failed to start due to=
 grid bad voltage,no rcp// Grid return","edwige.kapawo@matech-cameroun.com"=
,"189","17-06-2025 17:11:27","MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0005282997","Dag=
obert","","17-06-2025 17:08:51","17-06-2025 17:03:39","17-06-2025 17:57:53"=
,"Active: No power issue, site is on Grid with Ubaie=3D54,9V, mohamadou//69=
1144435 from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue, site is on Grid with Ubaie=3D54,9V, mohamadou//691144=
435 from Huawei is informed.","gerard.tchangoue@matech-cameroun.com","313",=
"17-06-2025 17:08:51","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005282914","SIM=
BOCK BONAMBAPE","","17-06-2025 16:55:50","17-06-2025 16:50:38","17-06-2025 =
16:56:47","Grid outage, site went down because gen fails to start due to gr=
id contactor faulty // He change it","Hyemafo Gildas","Equipment Repair","P=
assive","Control Panel","ATS-AMF Issue","Grid outage, site went down becaus=
e gen fails to start due to grid contactor faulty // He change it","gerard.=
tchangoue@matech-cameroun.com","313","17-06-2025 16:55:50","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005282637","Mim=
boman4","","17-06-2025 16:11:02","17-06-2025 16:04:55","17-06-2025 16:24:07=
","Grid outage.gen failed to start due to air intake//We purged and gen man=
ually started","Mba Lazare Herve","Fuel Outage (Probable)","Passive","ACDG =
Gen","ACDG - Air Intake","Grid outage.gen failed to start due to air intake=
//We purged and gen manually started","gerard.tchangoue@matech-cameroun.com=
","368","17-06-2025 16:11:02","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0005282590","Tam=
tam Weekend","","17-06-2025 16:01:14","17-06-2025 15:57:59","17-06-2025 16:=
11:20","Grid Outage Site went down because Gen Overload (20KVA, 300A) // Gr=
id returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid Outage Site went down because Gen Overload (20KVA, 300A)=
 // Grid returned","gerard.tchangoue@matech-cameroun.com","196","17-06-2025=
 16:01:14","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005282549","M=
anguier","","17-06-2025 15:55:40","17-06-2025 15:54:27","17-06-2025 17:30:4=
6","Site Went Down because  Delor (Matech/659906652) was on site for work (=
swap Gen contactor) // End of work","Fabrice Pouakam","Equipment Replacemen=
t","Passive","Planned Activity","Planned Activity - Passive","Site Went Dow=
n because  Delor (Matech/659906652) was on site for work (swap Gen contacto=
r) // End of work","edwige.kapawo@matech-cameroun.com","74","17-06-2025 15:=
55:40","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005282407","Mes=
sassi 2","","17-06-2025 15:35:02","17-06-2025 15:31:56","17-06-2025 16:06:4=
7","Grid outage, Gen failed to start due to Bay ZTE malfunction // Gen star=
t manually","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Grid outage, Gen failed to start due to Bay ZTE =
malfunction // Gen start manually","gerard.tchangoue@matech-cameroun.com","=
188","17-06-2025 15:35:02","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005282403","S=
IMBOCK BONAMBAPE","","17-06-2025 15:34:18","17-06-2025 12:48:30","17-06-202=
5 16:44:21","Grid outage, site went down because gen fails to start due to =
grid contactor faulty // He change it","Hyemafo Gildas","Equipment Repair",=
"Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down beca=
use gen fails to start due to grid contactor faulty // He change it","edwig=
e.kapawo@matech-cameroun.com","9949","17-06-2025 15:34:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0005282389","Biyemass=
i LAC","","17-06-2025 15:32:19","17-06-2025 14:09:14","17-06-2025 15:44:08"=
,"Cascaded Incident from TTO5442810","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Site went down because gen failed to start due=
 to grid bad voltage // He bypassed the grid and gen manually started","sys=
tem","712757","17-06-2025 15:32:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0005282282","Dragage"=
,"","17-06-2025 15:12:20","17-06-2025 14:52:26","17-06-2025 15:12:29","Casc=
aded Incident from TTO5442601","Mboua Thierry","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down due to Grid outage // gr=
id return","system","710228","17-06-2025 15:12:20","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0005282222","J=
-Vespa","","17-06-2025 15:02:46","17-06-2025 14:54:36","17-06-2025 15:10:49=
","Grid Outage, Site went Down because Gen failed to start due to poor back=
up // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site went Down because Gen=
 failed to start due to poor backup // Grid return","edwige.kapawo@matech-c=
ameroun.com","491","17-06-2025 15:02:46","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0005282217","Bas=
tos-BAT","","17-06-2025 15:00:58","17-06-2025 14:52:26","17-06-2025 15:12:2=
9","Site impacted by ARMP Building","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to Grid outage =
// grid return","gerard.tchangoue@matech-cameroun.com","710228","17-06-2025=
 15:00:58","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005282199","ARM=
P Building","IHS_YND_192, IHS_YND_129","17-06-2025 14:56:37","17-06-2025 14=
:52:26","17-06-2025 15:12:29","Site went down due to Grid outage // grid re=
turn","Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Grid =
Outage Issue","Site went down due to Grid outage // grid return","gerard.tc=
hangoue@matech-cameroun.com","251","17-06-2025 14:56:37","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005282163","M=
anguier","","17-06-2025 14:53:38","17-06-2025 13:05:23","17-06-2025 13:23:4=
2","Grid outage, site went down before gen start due to poor battery backup=
 // Gen Started Automatically","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen Started Automatically=
","edwige.kapawo@matech-cameroun.com","6496","17-06-2025 14:53:38","MATECH =
CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005282143","Mvo=
g-Manga","","17-06-2025 14:49:51","17-06-2025 14:49:07","17-06-2025 15:10:4=
6","Site went down due to MPR DYSFONNCTION on site // Site stabilised","Alb=
ran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","S=
ite went down due to MPR DYSFONNCTION on site // Site stabilised","gerard.t=
changoue@matech-cameroun.com","45","17-06-2025 14:49:51","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005282041","Nko=
abang2","","17-06-2025 14:34:16","17-06-2025 14:25:11","17-06-2025 16:42:36=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // He reduiced the load and site on Gen","Mba Lazare Herve=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, s=
ite went down due to gen overload (22KVA, 330A), SS Blaise IHS is informed =
// He reduiced the load and site on Gen","gerard.tchangoue@matech-cameroun.=
com","547","17-06-2025 14:34:16","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005281968","Mes=
sassi 2","","17-06-2025 14:21:49","17-06-2025 14:14:19","17-06-2025 14:49:1=
9","Grid outage, Gen failed to start due to Bay ZTE malfunction // Gen star=
t manually","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Grid outage, Gen failed to start due to Bay ZTE =
malfunction // Gen start manually","gerard.tchangoue@matech-cameroun.com","=
452","17-06-2025 14:21:49","MATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0005281925","BIY=
EMASSI NIKI","IHS_YND_546","17-06-2025 14:13:21","17-06-2025 14:09:14","17-=
06-2025 15:44:08","Site went down because gen failed to start due to grid b=
ad voltage // He bypassed the grid and gen manually started","Hyemafo Gilda=
s","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Site went down because gen failed to start due to grid bad voltage // He =
bypassed the grid and gen manually started","franck.nkomot@matech-cameroun.=
com","248","17-06-2025 14:13:21","MATECH CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0005281755","D=
onga","","17-06-2025 13:48:58","17-06-2025 13:40:36","17-06-2025 13:53:25",=
"","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","No Power issue, site on battery Ubay =3D 50.4V Hybrid Site, Tx Fme Gre=
goire (654547479) from Huawei is informed and confirmed","edwige.kapawo@mat=
ech-cameroun.com","714442","17-06-2025 13:48:58","MATECH CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0005281745","N=
guila","IHS_YND_434, IHS_YND_444","17-06-2025 13:47:54","17-06-2025 13:40:3=
6","17-06-2025 13:53:25","No Power issue, site on battery Ubay =3D 50.4V Hy=
brid Site, Tx Fme Gregoire (654547479) from Huawei is informed and confirme=
d","Parker Tchoup","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No Power issue, site on battery Ubay =3D 50.=
4V Hybrid Site, Tx Fme Gregoire (654547479) from Huawei is informed and con=
firmed","edwige.kapawo@matech-cameroun.com","439","17-06-2025 13:47:54","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0005281727","D=
ong","","17-06-2025 13:47:01","17-06-2025 13:40:36","17-06-2025 13:53:25","=
","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Activ=
e","No Power issue, site on battery Ubay =3D 50.4V Hybrid Site, Tx Fme Greg=
oire (654547479) from Huawei is informed and confirmed","edwige.kapawo@mate=
ch-cameroun.com","714442","17-06-2025 13:47:01","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005281719","Nko=
l-Mbanda","","17-06-2025 13:46:22","17-06-2025 13:43:17","17-06-2025 15:48:=
57","Grid outage site site went because Gen failed to started due to PWC dy=
sfunction // He reset it","MINKA NICOLAS","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","Grid outage site site went because G=
en failed to started due to PWC dysfunction // He reset it","franck.nkomot@=
matech-cameroun.com","186","17-06-2025 13:46:22","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005281672","Ron=
d Point Express1114","","17-06-2025 13:42:12","17-06-2025 13:37:02","17-06-=
2025 15:49:57","Grid outage site went down because Gen stopped with alarm H=
IGH temp due to Radiator pierced // He  added water Gen manually started","=
Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine=
 Temp - Radiator Leakage","Grid outage site went down because Gen stopped w=
ith alarm HIGH temp due to Radiator pierced // He  added water Gen manually=
 started","franck.nkomot@matech-cameroun.com","310","17-06-2025 13:42:12","=
MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005281613","S=
atcom","","17-06-2025 13:35:49","17-06-2025 13:32:42","17-06-2025 13:35:53"=
,"No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand ngu=
etsa(691144412) From huawei is informed.","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Armand nguetsa(6=
91144412) From huawei is informed.","edwige.kapawo@matech-cameroun.com","18=
8","17-06-2025 13:35:49","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005281565","Ron=
d Point Express1114","","17-06-2025 13:27:09","17-06-2025 13:24:52","17-06-=
2025 13:32:52","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Grid return","franck.nkomot@matech-cameroun.=
com","138","17-06-2025 13:27:09","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0005281547","S=
AA 2","","17-06-2025 13:20:40","17-06-2025 13:18:41","17-06-2025 13:19:28",=
"","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Error logged ticket","edwige.kapawo@matech-cameroun.com","715713","=
17-06-2025 13:20:40","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005281543","S=
aa","IHS_YND_404","17-06-2025 13:19:48","17-06-2025 13:18:41","17-06-2025 1=
3:19:28","Error logged ticket","Parker Tchoup","Incorrectly Logged Tickets"=
,"Error","Error","Error","Error logged ticket","edwige.kapawo@matech-camero=
un.com","68","17-06-2025 13:19:48","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005281506","NYO=
M 2 IHS","","17-06-2025 13:09:55","17-06-2025 07:12:08","17-06-2025 08:39:5=
3","Backtracking Site went down because Gen failed to start due to PWC ZTE =
dysfunction due to grid fluctuation//He reset it and site on GEN","Fabrice =
Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Backtracking Site went down because Gen failed to start due to PWC ZT=
E dysfunction due to grid fluctuation//He reset it and site on GEN","moulio=
m.anselme@matech-cameroun.com","25644","17-06-2025 13:09:55","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005281501","N=
koabang Ebolmedjock","","17-06-2025 13:07:22","17-06-2025 13:00:04","17-06-=
2025 13:07:37","Site impacted by Nkolmesseng-Abom(CTR-711) Not Managed By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","Site impacted by Nkolmesseng-Abo=
m(CTR-711) Not Managed By IHS","edwige.kapawo@matech-cameroun.com","439","1=
7-06-2025 13:07:22","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005281423","ODZ=
A BORNE 10","","17-06-2025 12:56:36","17-06-2025 07:05:44","17-06-2025 07:2=
5:57","site went down due to disfunctionning of rectifiers // he reset rect=
ifiers, site on grid","Albran Byorel","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","site went down due to disfunctionning of rectifiers=
 // he reset rectifiers, site on grid","mouliom.anselme@matech-cameroun.com=
","21053","17-06-2025 12:56:36","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005281397","SIM=
BOCK BONAMBAPE","","17-06-2025 12:50:30","17-06-2025 12:46:24","17-06-2025 =
12:48:24","Active // No power issue site on grid with Ubaie: 54.5V TX FME F=
lubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive // No power issue site on grid with Ubaie: 54.5V TX FME Flubert (65426=
6068) from Huawei is informed","franck.nkomot@matech-cameroun.com","247","1=
7-06-2025 12:50:30","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005281305","D=
amas","","17-06-2025 12:35:14","17-06-2025 03:55:28","17-06-2025 03:59:00",=
"Acces issue duuring at Night . Site went down because the PWC OF ZTE dysfu=
nction // He reset the PWC, Site on Grid","MINKA NICOLAS","Access Denial","=
Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Acces=
 issue duuring at Night . Site went down because the PWC OF ZTE dysfunction=
 // He reset the PWC, Site on Grid","mouliom.anselme@matech-cameroun.com","=
31186","17-06-2025 12:35:14","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005281175","N=
KOLMEKONG YDE","","17-06-2025 12:25:07","17-06-2025 06:20:17","17-06-2025 0=
6:44:24","Grid outage, Site went down before Gen start due to poor backup/ =
// Gen automatically started","Fabrice Pouakam","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup/ // Gen automatically started","mouli=
om.anselme@matech-cameroun.com","21890","17-06-2025 12:25:07","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005281120","N=
GONA","","17-06-2025 12:16:42","17-06-2025 12:10:36","17-06-2025 12:25:19",=
"No power issue Site is on Grid and Ubaie =3D57V The Tx FME Lionel Adjep (6=
55184876)from Huawei is informed.","Mba Lazare Herve","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue Site is on Grid and Ubaie =3D57V The Tx FME Lionel Adjep (655184876)f=
rom Huawei is informed.","edwige.kapawo@matech-cameroun.com","367","17-06-2=
025 12:16:42","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005281063","Mes=
sassi 2","","17-06-2025 12:03:30","17-06-2025 12:00:18","17-06-2025 12:49:1=
8","Grid outage, Gen failed to start due to Bay ZTE malfunction // Gen star=
t manually","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Grid outage, Gen failed to start due to Bay ZTE =
malfunction // Gen start manually","franck.nkomot@matech-cameroun.com","308=
","17-06-2025 12:03:30","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005281007","B=
arriere","","17-06-2025 11:54:21","16-06-2025 19:36:53","16-06-2025 19:37:1=
0","Active// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","mouliom.anselme@matech-cameroun.com","58648","17-06-2025 11:54=
:21","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005280841","N=
koabang2","","17-06-2025 11:48:07","16-06-2025 18:48:01","16-06-2025 18:50:=
58","Bactraking Grid outage, site went down due to gen overload (22KVA, 330=
A), SS Blaise IHS is informed // Grid return","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Bactraking Grid outage, si=
te went down due to gen overload (22KVA, 330A), SS Blaise IHS is informed /=
/ Grid return","mouliom.anselme@matech-cameroun.com","61206","17-06-2025 11=
:48:07","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005280731","N=
yom OCM","","17-06-2025 11:30:58","17-06-2025 11:30:54","17-06-2025 11:36:4=
3","Site went down due to PWC ZTE dysfunctionned // site stabilized","Fabri=
ce Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Over=
loaded","Site went down due to PWC ZTE dysfunctionned // site stabilized","=
edwige.kapawo@matech-cameroun.com","6","17-06-2025 11:30:58","MATECH CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0005280729","I=
mm-Olympique","","17-06-2025 11:30:15","17-06-2025 11:24:07","17-06-2025 11=
:50:57","Grid outage,site went down because Gen failed to start due to Gen =
overload(20KVA//295A) SS HIS Raoul is informed//Grid returned","Paul BIBOUM=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,si=
te went down because Gen failed to start due to Gen overload(20KVA//295A) S=
S HIS Raoul is informed//Grid returned","edwige.kapawo@matech-cameroun.com"=
,"591","17-06-2025 11:30:15","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005280680","F=
ouda-New","","17-06-2025 11:26:49","17-06-2025 11:26:45","17-06-2025 11:36:=
54","Grid Outage, site went down before Gen start due to Poor battery backu=
p // Grid returned","Delor Telezing","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, site went down before Ge=
n start due to Poor battery backup // Grid returned","edwige.kapawo@matech-=
cameroun.com","5","17-06-2025 11:26:49","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005280670","E=
mana lycee 2","IHS_YND_274","17-06-2025 11:26:18","17-06-2025 11:24:12","17=
-06-2025 11:27:29","Grid outage, Site went down due to Gen overload(20kva, =
260A) //Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Grid outage, Site went down due to Gen overload(20kv=
a, 260A) //Grid return","edwige.kapawo@matech-cameroun.com","128","17-06-20=
25 11:26:18","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005280666","Mim=
boman4","","17-06-2025 11:25:53","17-06-2025 11:23:26","17-06-2025 11:41:26=
","Grid outage.gen failed to start due to air intake//We purged and gen man=
ually started","Mba Lazare Herve","Fuel Outage (Probable)","Passive","ACDG =
Gen","ACDG - Air Intake","Grid outage.gen failed to start due to air intake=
//We purged and gen manually started","franck.nkomot@matech-cameroun.com","=
148","17-06-2025 11:25:53","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005280662","E=
mana Lycee","","17-06-2025 11:25:44","17-06-2025 11:24:12","17-06-2025 11:2=
7:29","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, Site went down due to Gen overload(20kva, 260A=
) //Grid return","edwige.kapawo@matech-cameroun.com","722410","17-06-2025 1=
1:25:44","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005280658","N=
GONA","","17-06-2025 11:24:50","17-06-2025 11:22:43","17-06-2025 11:37:34",=
"	Grid outage,site went down because Gen failed to start due to battery GE =
faulty //he started with an external battery","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage,site =
went down because Gen failed to start due to battery GE faulty //he started=
 with an external battery","edwige.kapawo@matech-cameroun.com","128","17-06=
-2025 11:24:50","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005280629","Par=
adis Hotel","","17-06-2025 11:19:34","17-06-2025 11:13:26","17-06-2025 11:3=
7:26","Grid outage, site went down because Gen Overload (12.5Kva, 100A) SS =
IHS BLAISE RAOUL ETCHEU is confirmed // Grid return","Siligap Boris","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went=
 down because Gen Overload (12.5Kva, 100A) SS IHS BLAISE RAOUL ETCHEU is co=
nfirmed // Grid return","franck.nkomot@matech-cameroun.com","369","17-06-20=
25 11:19:34","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005280617","M=
anguier","","17-06-2025 11:16:05","17-06-2025 11:14:58","17-06-2025 12:53:3=
4","Grid Outage, Site went Down because Gen contactor faulty // He manually=
 activated Gen contactor","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","ACDG - Load Contactor","Grid Outage, Site went Down because Gen c=
ontactor faulty // He manually activated Gen contactor","edwige.kapawo@mate=
ch-cameroun.com","68","17-06-2025 11:16:05","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005280612","E=
MANA BILICK CITY","","17-06-2025 11:15:26","17-06-2025 11:12:16","17-06-202=
5 11:44:16","Grid outage, site down because site behaves as Grid only site =
(Gen Noise) // Grid return","Fabrice Pouakam","Access Denial","Lease Or Leg=
al","Landlord Related Issues","Access Issue - Land Lord","Grid outage, site=
 down because site behaves as Grid only site (Gen Noise) // Grid return","e=
dwige.kapawo@matech-cameroun.com","192","17-06-2025 11:15:26","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005280608","M=
vog-Ada_OCM","","17-06-2025 11:14:51","17-06-2025 11:11:43","17-06-2025 11:=
39:59","Grid only on site, No space on site to deploy MDGE//Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
nly on site, No space on site to deploy MDGE//Grid return","edwige.kapawo@m=
atech-cameroun.com","189","17-06-2025 11:14:51","MATECH CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0005280594","NKO=
LMEKONG YDE","","17-06-2025 11:11:36","17-06-2025 11:07:25","17-06-2025 11:=
41:25","Site went down because FME Will on site for PM // End of work","Fab=
rice Pouakam","Installation Activity","Passive","Planned Activity","Install=
ation Activity","Site went down because FME Will on site for PM // End of w=
ork","franck.nkomot@matech-cameroun.com","252","17-06-2025 11:11:36","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005280570","S=
ous Prefecture","","17-06-2025 11:06:11","17-06-2025 11:04:04","17-06-2025 =
11:07:24","No power issue site on Grid Ubaie =3D55.2 V, The tx fme Fulbert =
(654266068/ Huawei) is informed","Fanda Brice","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on Grid Ubaie =3D55.2 V, The tx fme Fulbert (654266068/ Huawei) is info=
rmed","edwige.kapawo@matech-cameroun.com","128","17-06-2025 11:06:11","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0005280388","M=
atomb","","17-06-2025 10:34:22","17-06-2025 10:32:03","17-06-2025 10:36:15"=
,"No power issue on site.Site on grid with Ubaie=3D54.2 V  site on gen ,The=
 TX FME Etienne(695033981) from Huawei is informed.","Kemeni Franklin","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue on site.Site on grid with Ubaie=3D54.2 V  site on ge=
n ,The TX FME Etienne(695033981) from Huawei is informed.","edwige.kapawo@m=
atech-cameroun.com","140","17-06-2025 10:34:22","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005280279","TSI=
NGA VILLAGE 2","","17-06-2025 10:18:24","17-06-2025 10:14:35","17-06-2025 1=
0:15:35","Active//No power issue on site, Site on Battery UBAIE=3D54.5V syn=
phorien (675295205) From huawei is informed","Delor Telezing","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site, Site on Battery UBAIE=3D54.5V synphorien (67=
5295205) From huawei is informed","franck.nkomot@matech-cameroun.com","230"=
,"17-06-2025 10:18:24","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005280121","Mvo=
g-Manga","","17-06-2025 10:08:29","17-06-2025 10:04:15","17-06-2025 13:34:0=
1","Site went down due to MPR DYSFONNCTION on site // Site stabilised","Alb=
ran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","S=
ite went down due to MPR DYSFONNCTION on site // Site stabilised","franck.n=
komot@matech-cameroun.com","524","17-06-2025 10:08:29","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005279949","N=
koabang2","","17-06-2025 09:46:46","17-06-2025 09:44:40","17-06-2025 10:37:=
40","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ed=
wige.kapawo@matech-cameroun.com","128","17-06-2025 09:46:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005279827","ELOUMDEM=
 CARRIERE 2","","17-06-2025 09:24:36","17-06-2025 09:20:32","17-06-2025 09:=
55:32","Cascaded Incident from TTO5439932","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation,Site went do=
wn because Gen failed to start due to Grid bad voltage, on site//He bypasse=
d the Grid and gen manually started","system","722899","17-06-2025 09:24:36=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005279826","Eto koss=
 Yde","","17-06-2025 09:24:35","17-06-2025 09:20:32","17-06-2025 09:55:32",=
"Cascaded Incident from TTO5439932","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation,Site went down beca=
use Gen failed to start due to Grid bad voltage, on site//He bypassed the G=
rid and gen manually started","system","722898","17-06-2025 09:24:35","MATE=
CH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005279816","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","17-06-2025 09:23:42","17-06-2025 09:20=
:32","17-06-2025 09:55:32","Grid fluctuation,Site went down because Gen fai=
led to start due to Grid bad voltage, on site//He bypassed the Grid and gen=
 manually started","Fanda Brice","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation,Site went down because Gen=
 failed to start due to Grid bad voltage, on site//He bypassed the Grid and=
 gen manually started","franck.nkomot@matech-cameroun.com","192","17-06-202=
5 09:23:42","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005279813","N=
gousso-Savana","","17-06-2025 09:22:28","17-06-2025 09:21:21","17-06-2025 0=
9:23:42","Grid Outage, site went down before Gen start due to Poor battery =
backup// Grid return ","Siligap Boris","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Outage, site went down before =
Gen start due to Poor battery backup// Grid return ","edwige.kapawo@matech-=
cameroun.com","68","17-06-2025 09:22:28","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005279568","Mvo=
g-Manga","","17-06-2025 08:38:30","17-06-2025 08:36:22","17-06-2025 09:01:2=
2","Site went down due to MPR DYSFONNCTION on site // Site stabilised","Alb=
ran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","S=
ite went down due to MPR DYSFONNCTION on site // Site stabilised","franck.n=
komot@matech-cameroun.com","130","17-06-2025 08:38:30","MATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0005279432","BIY=
EMASSI NIKI","","17-06-2025 08:08:26","17-06-2025 07:30:59","17-06-2025 08:=
24:42","Grid fluctuation, Site went down because gen fails to start due to =
grid bad voltage // He bypassed the Grid and site on Gen","Hyemafo Gildas",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid fluctuation, Site went down because gen fails to start due to grid bad =
voltage // He bypassed the Grid and site on Gen","franck.nkomot@matech-came=
roun.com","4723","17-06-2025 08:08:26","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005279370","Nko=
lbisson IITA LP","","17-06-2025 08:01:40","17-06-2025 07:55:29","17-06-2025=
 15:35:17","Grid only site, no space to deploy MDGE // Grid returned","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only=
 site, no space to deploy MDGE // Grid returned","franck.nkomot@matech-came=
roun.com","373","17-06-2025 08:01:40","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005279265","N=
omayos montee Meche","","17-06-2025 07:39:49","17-06-2025 07:37:42","17-06-=
2025 08:07:42","Grid outage, site went down before Gen started due rectifie=
rs issue and poor battery backup // Grid returned","Fanda Brice","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge, site went down before Gen started due rectifiers issue and poor battery=
 backup // Grid returned","vanel.mbiada@matech-cameroun.com","128","17-06-2=
025 07:39:49","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0005279230","B=
iyemassi LAC","","17-06-2025 07:34:41","17-06-2025 07:28:35","17-06-2025 08=
:26:28","Grid Only, No space to deploy MGE // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no space=
 to deploy MDGE // Grid returned","vanel.mbiada@matech-cameroun.com","368",=
"17-06-2025 07:34:41","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005279108","M=
ontee-Jouvence-II","","17-06-2025 07:17:22","17-06-2025 07:10:14","17-06-20=
25 09:42:14","No power issue on site, site on Grid with Ubaie=3D53.9V The T=
x Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site, site on Grid with Ubaie=3D53.9V The Tx Fm=
e Mbah Hosiah //674007438/ from HUAWEI is informed","vanel.mbiada@matech-ca=
meroun.com","429","17-06-2025 07:17:22","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005278776","Nom=
ayos montee Meche","","17-06-2025 06:21:40","17-06-2025 06:19:27","17-06-20=
25 06:21:33","Grid outage site went down before Gen started due to poor bat=
tery back up // Eneo return","Fanda Brice","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage site went down befo=
re Gen started due to poor battery back up // Eneo return","cedric.tiani@ma=
tech-cameroun.com","134","17-06-2025 06:21:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005278580","MEHANDAN=
","","17-06-2025 05:38:23","17-06-2025 03:04:50","17-06-2025 03:11:46","Cas=
caded Incident from TTO5437960","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","738257","17-06-2025 05:38:23","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005278476","ODZ=
A BORNE 10","","17-06-2025 05:09:24","17-06-2025 05:00:57","17-06-2025 05:2=
0:20","Grid fluctuation, Site went down because Gen failed to start due to =
Grid bad voltage No RCP //He bypassed Grid and started Gen manualy","Albran=
 Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation, Site went down because Gen failed to start due to=
 Grid bad voltage No RCP //He bypassed Grid and started Gen manualy","cedri=
c.tiani@matech-cameroun.com","508","17-06-2025 05:09:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005278421","Mfou EPC=
","","17-06-2025 05:02:28","17-06-2025 04:52:05","17-06-2025 05:13:09","Cas=
caded Incident from TTO5438387","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid return","system","738693","17-06-2025 05:0=
2:28","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005278376","M=
fou OCM","IHS_YND_674","17-06-2025 04:55:16","17-06-2025 04:52:05","17-06-2=
025 05:13:09","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Start=
ed due to poor backup //Grid return","vanel.mbiada@matech-cameroun.com","19=
2","17-06-2025 04:55:16","MATECH CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0005278332","Mae=
tur","","17-06-2025 04:44:17","17-06-2025 04:04:25","17-06-2025 06:04:51","=
Grid outage, Gen failed to start due to alarm ''short circuit'' // Gen card=
 reset and Gen manually start","Mboua Thierry","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage, Gen failed to start due to=
 alarm ''short circuit'' // Gen card reset and Gen manually start","cedric.=
tiani@matech-cameroun.com","2393","17-06-2025 04:44:17","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005278191","A=
ccacia New","","17-06-2025 04:05:20","17-06-2025 03:59:01","17-06-2025 07:3=
6:01","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Acces issue duuring at Night  . Site went down because the PWC OF ZTE dysf=
unction // He reset the PWC, Site on Grid","vanel.mbiada@matech-cameroun.co=
m","735057","17-06-2025 04:05:20","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005278187","D=
amas","IHS_YND_562","17-06-2025 04:04:13","17-06-2025 03:59:01","17-06-2025=
 07:36:01","Acces issue duuring at Night  . Site went down because the PWC =
OF ZTE dysfunction // He reset the PWC, Site on Grid","MINKA NICOLAS","Acce=
ss Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land =
Lord","Acces issue duuring at Night  . Site went down because the PWC OF ZT=
E dysfunction // He reset the PWC, Site on Grid","vanel.mbiada@matech-camer=
oun.com","313","17-06-2025 04:04:13","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005278182","M=
ontee-Jouvence-II","","17-06-2025 04:02:10","17-06-2025 03:59:52","17-06-20=
25 05:14:14","No power issue on site, site on Grid with Ubaie=3D54.1V The T=
x Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site, site on Grid with Ubaie=3D54.1V The Tx Fm=
e Mbah Hosiah //674007438/ from HUAWEI is informed","vanel.mbiada@matech-ca=
meroun.com","139","17-06-2025 04:02:10","MATECH CMR"
"Closed Complete","Site Down","CTR_621","IHS_YND_278","NOCINC0005278062","N=
kolfoulou 2","","17-06-2025 03:32:51","17-06-2025 03:12:38","17-06-2025 03:=
38:27","Site went down due to work: NDOGMO Auremien (SFM /656179911) is on =
Site for SWAP PWC ZTE & BAT // En of work","Siligap Boris","Installation Ac=
tivity","Passive","Planned Activity","Installation Activity","Site went dow=
n due to work: NDOGMO Auremien (SFM /656179911) is on Site for SWAP PWC ZTE=
 & BAT // En of work","vanel.mbiada@matech-cameroun.com","1214","17-06-2025=
 03:32:51","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005278054","Par=
adis Hotel","","17-06-2025 03:30:08","17-06-2025 02:35:43","17-06-2025 02:5=
1:19","Site went down due to MPR DYSFONNCTION on site / Site stabilised","S=
iligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site / Site stabilised","cedric.=
tiani@matech-cameroun.com","3266","17-06-2025 03:30:08","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005277972","Odz=
a II OCM","IHS_YND_528","17-06-2025 03:11:09","17-06-2025 03:04:50","17-06-=
2025 03:11:46","Grid fluctuations, site went down because gen failed to sta=
rt due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctua=
tions, site went down because gen failed to start due to PWC ZTE malfunctio=
n // Grid stabilized","cedric.tiani@matech-cameroun.com","380","17-06-2025 =
03:11:09","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005277958","T=
singa","","17-06-2025 03:08:22","16-06-2025 21:53:58","17-06-2025 16:48:35"=
,"Grid Outage, Site went down due to PWC overload // Grid return","Mboua Th=
ierry","Equipment Repair","Passive","Rectifier","Rectifier Module Overloade=
d","Grid Outage, Site went down due to PWC overload // Grid return","cedric=
.tiani@matech-cameroun.com","18865","17-06-2025 03:08:22","MATECH CMR"
"Closed Complete","Site Down","T0219","IHS_YND_024","NOCINC0005277834","Gar=
bati building","","17-06-2025 02:46:52","17-06-2025 02:41:46","17-06-2025 0=
2:43:23","Grid outage site went down before Gen started due to poor battery=
 back up // GEN automatically started","Delor Telezing","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site w=
ent down before Gen started due to poor battery back up // GEN automaticall=
y started","cedric.tiani@matech-cameroun.com","307","17-06-2025 02:46:52","=
MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005277825","HOP=
ITAL DE LA CAISSE","","17-06-2025 02:43:21","17-06-2025 02:41:13","17-06-20=
25 02:43:24","Grid outage site went down before Gen started due to poor bat=
tery back up // GEN automatically started","Delor Telezing","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage si=
te went down before Gen started due to poor battery back up // GEN automati=
cally started","cedric.tiani@matech-cameroun.com","129","17-06-2025 02:43:2=
1","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005277824","S=
atcom","","17-06-2025 02:43:14","17-06-2025 02:39:02","17-06-2025 02:47:20"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","vanel.mbiada@matech-ca=
meroun.com","253","17-06-2025 02:43:14","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005277799","Mam=
ch Building","","17-06-2025 02:40:54","17-06-2025 02:35:40","17-06-2025 04:=
36:49","wrongly created ticket","Mboua Thierry","Incorrectly Logged Tickets=
","Error","Error","Error","wrongly created ticket","cedric.tiani@matech-cam=
eroun.com","315","17-06-2025 02:40:54","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005277661","Nko=
langaa","","17-06-2025 02:05:22","17-06-2025 01:57:04","17-06-2025 03:17:27=
","Site went down due to CB(125A)in PWC that tripped MTN //He rearmed it","=
Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Circuit Breaker Issue","Site went down due to CB(125A)in PWC that trip=
ped MTN //He rearmed it","cedric.tiani@matech-cameroun.com","499","17-06-20=
25 02:05:22","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005277610","Crf=
-Mbankolo-IHS","","17-06-2025 02:02:37","17-06-2025 01:55:26","17-06-2025 0=
7:29:26","Fme Thierry Mboua informs us that access issue due to insecurity =
Zone. Site went down due to insufficient rectifiers on site //He reduced th=
e load and site on Grid","Mboua Thierry","Access Denial","Lease Or Legal","=
Landlord Related Issues","Access Issue - Land Lord","Fme Thierry Mboua info=
rms us that access issue due to insecurity Zone. Site went down due to insu=
fficient rectifiers on site //He reduced the load and site on Grid","cedric=
.tiani@matech-cameroun.com","432","17-06-2025 02:02:37","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0005277570","S=
AA 2","","17-06-2025 01:46:11","17-06-2025 01:42:55","17-06-2025 01:45:16",=
"No power issue on site Ubay 54.2 V site on Gen, Gregoire / from huawei is =
informed. ","Parker Tchoup","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site Ubay 54.2 V =
site on Gen, Gregoire / from huawei is informed. Site","vanel.mbiada@matech=
-cameroun.com","197","17-06-2025 01:46:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0005277527","Dragage"=
,"","17-06-2025 01:31:12","17-06-2025 01:28:59","17-06-2025 02:38:40","Casc=
aded Incident from TTO5437484","Mboua Thierry","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage//He deploy 20KVA","system",=
"743916","17-06-2025 01:31:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0005277523","Bastos-B=
AT","","17-06-2025 01:29:52","17-06-2025 01:28:59","17-06-2025 02:38:40","C=
ascaded Incident from TTO5437484","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage//He deploy 20KVA","syste=
m","743916","17-06-2025 01:29:52","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005277521","ARM=
P Building","IHS_YND_192, IHS_YND_129","17-06-2025 01:29:07","17-06-2025 01=
:28:59","17-06-2025 02:38:40","Grid outage//He deploy 20KVA","Mboua Thierry=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage//He deploy 20KVA","cedric.tiani@matech-cameroun.com","8","17-06-2025=
 01:29:07","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005277490","Eto=
ug ebe Meweulo","","17-06-2025 01:23:01","17-06-2025 01:19:49","17-06-2025 =
01:38:37","Active: No power issue, site on grid with Ubaie=3D53V, Hosiah(67=
4007438) from Huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No p=
ower issue, site on grid with Ubaie=3D53V, Hosiah(674007438) from Huawei is=
 informed","cedric.tiani@matech-cameroun.com","193","17-06-2025 01:23:01","=
MATECH CMR"
"Closed Complete","Site Down","T1431","IHS_YND_561","NOCINC0005277460","FOU=
GEROLE","","17-06-2025 01:15:54","17-06-2025 01:14:41","17-06-2025 01:39:04=
","No power issue on site U=3D54,4v site on grid Synphorien 675295205 of hu=
awei is informed","Siligap Boris","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54=
,4v site on grid Synphorien 675295205 of huawei is informed","cedric.tiani@=
matech-cameroun.com","73","17-06-2025 01:15:54","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005277455","N=
kolondom","","17-06-2025 01:12:50","17-06-2025 01:00:53","17-06-2025 01:32:=
43","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, Site went down before Gen start due to poor back=
up/ // Gen automatically started","vanel.mbiada@matech-cameroun.com","12197=
58","17-06-2025 01:12:50","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005277443","Nom=
ayos montee Meche","","17-06-2025 01:05:08","17-06-2025 01:02:48","17-06-20=
25 01:04:54","Grid outage, Site went down before Gen start due to poor back=
up // GRID return","Fanda Brice","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // GRID return","cedric.tiani@matech-cameroun.com","=
141","17-06-2025 01:05:08","MATECH CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0005277435","NKO=
LMEKONG YDE","IHS_YND_304","17-06-2025 01:02:06","17-06-2025 01:00:53","17-=
06-2025 01:34:58","Grid outage, Site went down before Gen start due to poor=
 backup/ // Gen automatically started","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site=
 went down before Gen start due to poor backup/ // Gen automatically starte=
d","cedric.tiani@matech-cameroun.com","74","17-06-2025 01:02:06","MATECH CM=
R"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005277247","M=
vog-Manga","","17-06-2025 00:00:50","16-06-2025 23:58:31","17-06-2025 00:03=
:35","Site went down due to MPR DYSFONNCTION on site // Site stabilised","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site // Site stabilised","vanel.=
mbiada@matech-cameroun.com","141","17-06-2025 00:00:50","MATECH CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0005277242","A=
bang","","16-06-2025 23:59:53","16-06-2025 23:57:05","17-06-2025 00:46:03",=
"","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","ACTIVE//no power issue on site U=3D52:9 V site on Grid Lionnel Tcha=
tchou//694693436 from Huawei is informed","vanel.mbiada@matech-cameroun.com=
","749369","16-06-2025 23:59:53","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0005277240","N=
kolangaa","IHS_YND_290","16-06-2025 23:59:19","16-06-2025 23:57:05","17-06-=
2025 00:46:03","ACTIVE//no power issue on site U=3D52:9 V site on Grid Lion=
nel Tchatchou//694693436 from Huawei is informed","Mba Lazare Herve","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","ACTIVE//no power issue on site U=3D52:9 V site on Grid Lionnel Tchatc=
hou//694693436 from Huawei is informed","vanel.mbiada@matech-cameroun.com",=
"135","16-06-2025 23:59:19","MATECH CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0005277182","B=
IYEMASSI NIKI","IHS_YND_546","16-06-2025 23:42:30","16-06-2025 23:34:23","1=
6-06-2025 23:45:13","Grid fluctuation, Site went down because gen fails to =
start due to grid bad voltage,// He bypasse the Grid and site on Gen","Hyem=
afo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation, Site went down because gen fails to start due =
to grid bad voltage,// He bypasse the Grid and site on Gen","vanel.mbiada@m=
atech-cameroun.com","487","16-06-2025 23:42:30","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0005277153","B=
iyemassi LAC","","16-06-2025 23:36:24","16-06-2025 23:36:23","16-06-2025 23=
:45:13","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","Grid fluctuation, Site went down because gen fails to start due to grid =
bad voltage,// He bypasse the Grid and site on Gen","vanel.mbiada@matech-ca=
meroun.com","750597","16-06-2025 23:36:24","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005277071","Nom=
ayos montee Meche","","16-06-2025 23:25:16","16-06-2025 23:24:06","16-06-20=
25 23:26:25","Grid outage, Site went down before Gen start due to poor back=
up // Gen started automatically","Fanda Brice","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor backup // Gen started automatically","cedric.=
tiani@matech-cameroun.com","71","16-06-2025 23:25:16","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005277034","TSI=
NGA VILLAGE 2","","16-06-2025 23:15:41","16-06-2025 23:06:33","16-06-2025 2=
3:37:33","Site went down due to CB(125A)in PWC that tripped MTN //He rearme=
d it","Delor Telezing","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Circuit Breaker Issue","Site went down due to CB(125A)in PWC that=
 tripped MTN //He rearmed it","vanel.mbiada@matech-cameroun.com","549","16-=
06-2025 23:15:41","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005276758","S=
IMBOCK BONAMBAPE","","16-06-2025 22:26:00","16-06-2025 22:20:35","16-06-202=
5 22:24:53","Grid Outage, Site went down before Gen start due to poor backu=
p // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before Ge=
n start due to poor backup // Grid returned","edwige.kapawo@matech-cameroun=
.com","327","16-06-2025 22:26:00","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005276482","N=
omayos montee Meche","","16-06-2025 21:29:54","16-06-2025 21:27:41","16-06-=
2025 21:42:21","Grid outage, site went down before Gen started due to poor =
backup battery // Grid returned","Fanda Brice","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before Gen started due to poor backup battery // Grid returned","edwige.ka=
pawo@matech-cameroun.com","134","16-06-2025 21:29:54","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005276443","TSI=
NGA VILLAGE 2","","16-06-2025 21:24:06","16-06-2025 21:16:59","16-06-2025 2=
2:11:30","Site went down due to CB(125A)in PWC that tripped MTN //He rearme=
d it","Delor Telezing","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Circuit Breaker Issue","Site went down due to CB(125A)in PWC that=
 tripped MTN //He rearmed it","gerard.tchangoue@matech-cameroun.com","428",=
"16-06-2025 21:24:06","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005276370","B=
arriere","","16-06-2025 21:06:23","16-06-2025 21:04:11","16-06-2025 21:09:3=
6","Active// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","edwige.kapawo@matech-cameroun.com","134","16-06-2025 21:06:23"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005276358","C=
omplexe-BEAC","","16-06-2025 21:03:49","16-06-2025 20:55:27","16-06-2025 23=
:35:40","No power issue on site ,site on Grid with U=3D49 v Tx FME Lionnel/=
/ 655184876 from Huawei is informed.Noticed dysjuction at BTS OCM","Albran =
Byorel","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site ,site on Grid with U=3D49 v Tx F=
ME Lionnel// 655184876 from Huawei is informed.Noticed dysjuction at BTS OC=
M","edwige.kapawo@matech-cameroun.com","503","16-06-2025 21:03:49","MATECH =
CMR"
"Closed Complete","Site Down","T1557","IHS_YND_313","NOCINC0005276191","Afa=
noya","","16-06-2025 20:32:35","16-06-2025 18:57:27","16-06-2025 22:49:43",=
"Grid outage,site went down because Gen failed to start due to Fuse Gen car=
d faulty //He made a Bridge and started the Gen manually","Hyemafo Gildas",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
,site went down because Gen failed to start due to Fuse Gen card faulty //H=
e made a Bridge and started the Gen manually","gerard.tchangoue@matech-came=
roun.com","5850","16-06-2025 20:32:35","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005276163","Nko=
l-Mebanga","","16-06-2025 20:26:34","16-06-2025 20:24:26","16-06-2025 20:29=
:21","WRONGLY TICKET","Parker Tchoup","Incorrectly Logged Tickets","Error",=
"Error","Error","WRONGLY TICKET","gerard.tchangoue@matech-cameroun.com","12=
8","16-06-2025 20:26:34","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005276089","Aha=
la Echangeur","","16-06-2025 20:10:17","16-06-2025 20:01:59","16-06-2025 20=
:42:14","Site went down because gen stopped with low oil pressure//he added=
 oil and started the gen","MINKA NICOLAS","Equipment Repair","Passive","ACD=
G Gen","ACDG - Low Oil Pressure","Site went down because gen stopped with l=
ow oil pressure//he added oil and started the gen","gerard.tchangoue@matech=
-cameroun.com","499","16-06-2025 20:10:17","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005276058","N=
koabang2","","16-06-2025 20:00:43","16-06-2025 19:51:59","16-06-2025 22:43:=
19","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed//He reduiced the load and started the Gen manually","Mba=
 Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Grid outage, site went down due to gen overload (22KVA, 330A), =
SS Blaise IHS is informed","edwige.kapawo@matech-cameroun.com","600","16-06=
-2025 20:00:43","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005275929","C=
omplexe-BEAC","","16-06-2025 19:36:48","16-06-2025 19:29:39","16-06-2025 19=
:38:32","Grid outage, Site went down before Gen start due to Poor battery b=
ackup // Grid return","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to Poor battery backup // Grid return","edwige.kapawo@matech-c=
ameroun.com","430","16-06-2025 19:36:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005275779","SOA VILL=
AGE","","16-06-2025 19:09:12","16-06-2025 18:54:38","16-06-2025 19:08:31","=
Cascaded Incident from TTO5435492","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work: NDOGMO =
Auremien (SFM /656179911) is on Site for SWAP PWC ZTE & BAT // En of work",=
"system","760422","16-06-2025 19:09:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005275778","TSINGA V=
ILLAGE 2","","16-06-2025 19:09:12","16-06-2025 18:54:38","16-06-2025 19:08:=
31","Cascaded Incident from TTO5435492","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work: N=
DOGMO Auremien (SFM /656179911) is on Site for SWAP PWC ZTE & BAT // En of =
work","system","760420","16-06-2025 19:09:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0005275780","Nkolfoul=
ou Tsinga Village","","16-06-2025 19:09:12","16-06-2025 18:54:38","16-06-20=
25 19:08:31","Cascaded Incident from TTO5435492","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Site went down due to=
 work: NDOGMO Auremien (SFM /656179911) is on Site for SWAP PWC ZTE & BAT /=
/ En of work","system","760419","16-06-2025 19:09:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005275777","Mvog-Eba=
nda","","16-06-2025 19:09:12","16-06-2025 18:54:38","16-06-2025 19:08:31","=
Cascaded Incident from TTO5435492","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work: NDOGMO =
Auremien (SFM /656179911) is on Site for SWAP PWC ZTE & BAT // En of work",=
"system","760418","16-06-2025 19:09:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005275776","FOUGEROL=
E","","16-06-2025 19:09:11","16-06-2025 18:54:38","16-06-2025 19:08:31","Ca=
scaded Incident from TTO5435492","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to work: NDOGMO Au=
remien (SFM /656179911) is on Site for SWAP PWC ZTE & BAT // En of work","s=
ystem","760421","16-06-2025 19:09:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0005275746","Afanoya"=
,"","16-06-2025 19:02:48","16-06-2025 16:59:36","16-06-2025 18:25:38","Casc=
aded Incident from TTO5434679","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, Site went Down due to Gen=
 overload (17KVA, 260A) SS HIS Felix Zambe is informed // Grid return","sys=
tem","767155","16-06-2025 19:02:48","MATECH CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0005275715","Nko=
lfoulou 2","IHS_YND_561, IHS_YND_269, IHS_YND_719, IHS_YND_323, IHS_YND_296=
, IHS_YND_759","16-06-2025 18:57:48","16-06-2025 18:54:38","16-06-2025 19:0=
8:31","Site went down due to work: NDOGMO Auremien (SFM /656179911) is on S=
ite for SWAP PWC ZTE & BAT // En of work","Siligap Boris","Equipment Replac=
ement","Passive","Planned Activity","Planned Activity - Passive","Site went=
 down due to work: NDOGMO Auremien (SFM /656179911) is on Site for SWAP PWC=
 ZTE & BAT // En of work","gerard.tchangoue@matech-cameroun.com","191","16-=
06-2025 18:57:48","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005275702","N=
gouetou","","16-06-2025 18:55:46","16-06-2025 18:28:39","16-06-2025 19:15:2=
1","Active // No power issue site on Gen, with Ubay: 52.3V. The Tx Fme Greg=
oire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e // No power issue site on Gen, with Ubay: 52.3V. The Tx Fme Gregoire (654=
547479) from Huawei is informed","edwige.kapawo@matech-cameroun.com","1889"=
,"16-06-2025 18:55:46","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005275649","Nko=
lfoulou CSD MTN","","16-06-2025 18:49:01","16-06-2025 18:39:53","16-06-2025=
 20:33:09","Grid outage, site went down gen start and stopped with alarm ov=
er current // He reset gen card and gen manually","Siligap Boris","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site we=
nt down gen start and stopped with alarm over current // He reset gen card =
and gen manually","gerard.tchangoue@matech-cameroun.com","549","16-06-2025 =
18:49:01","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005275452","Nko=
lbisson IITA LP","","16-06-2025 18:20:30","16-06-2025 18:18:20","16-06-2025=
 18:21:38","No power issue site on grid with U=3D53.8v Mohamadou(69114435) =
from Huawei is informed	","","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D53.8v Mohamadou(69114435) from Huawei is informed	","gerard.tchangoue@ma=
tech-cameroun.com","131","16-06-2025 18:20:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005275430","OTELE MT=
N","","16-06-2025 18:17:27","16-06-2025 18:06:48","16-06-2025 18:19:21","Ca=
scaded Incident from TTO5435178","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue site on Grid with U=
=3D54V The FME TX Etienne(695033981) From Huawei is informed. Site impacted=
 by Ngoumou(T0169) not manage by IHS","system","763220","16-06-2025 18:17:2=
7","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0005275431","Akono","=
","16-06-2025 18:17:27","16-06-2025 18:06:48","16-06-2025 18:19:21","Cascad=
ed Incident from TTO5435178","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
4V The FME TX Etienne(695033981) From Huawei is informed. Site impacted by =
Ngoumou(T0169) not manage by IHS","system","763219","16-06-2025 18:17:27","=
MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0005275421","Mom=
","IHS_YND_531, IHS_YND_365","16-06-2025 18:15:57","16-06-2025 18:06:48","1=
6-06-2025 18:19:21","Active//No power issue site on Grid with U=3D54V The F=
ME TX Etienne(695033981) From Huawei is informed. Site impacted by Ngoumou(=
T0169) not manage by IHS","Fanda Brice","Customer Equipment Failure","Activ=
e","Active Equipment Failure","Affected by 3rd Party Site","Active//No powe=
r issue site on Grid with U=3D54V The FME TX Etienne(695033981) From Huawei=
 is informed. Site impacted by Ngoumou(T0169) not manage by IHS","gerard.tc=
hangoue@matech-cameroun.com","551","16-06-2025 18:15:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005275295","Bastos B=
ethesda","","16-06-2025 17:58:55","16-06-2025 17:53:39","16-06-2025 18:01:2=
2","Cascaded Incident from TTO5435035","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active// No power issue on site Ub=
aie:53.4V site on Grid The Tx Eloundou Bertrand (693212405/Huawei) is infor=
med","system","763981","16-06-2025 17:58:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005275294","Golf Qua=
ter","","16-06-2025 17:58:54","16-06-2025 17:53:39","16-06-2025 18:01:22","=
Cascaded Incident from TTO5435035","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active// No power issue on site Ubaie:=
53.4V site on Grid The Tx Eloundou Bertrand (693212405/Huawei) is informed"=
,"system","763982","16-06-2025 17:58:54","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005275289","B=
astos-Nylon","IHS_YND_220, IHS_YND_563","16-06-2025 17:57:50","16-06-2025 1=
7:53:39","16-06-2025 18:01:22","Active// No power issue on site Ubaie:53.4V=
 site on Grid The Tx Eloundou Bertrand (693212405/Huawei) is informed","Mbo=
ua Thierry","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active// No power issue on site Ubaie:53.4V site on=
 Grid The Tx Eloundou Bertrand (693212405/Huawei) is informed","edwige.kapa=
wo@matech-cameroun.com","251","16-06-2025 17:57:50","MATECH CMR"
"Closed Complete","Site Down","T0537","IHS_YND_225","NOCINC0005275199","Sci=
ence","","16-06-2025 17:47:15","16-06-2025 17:46:51","16-06-2025 18:10:43",=
"Site went down because the PWC OF ZTE dysfunction // He reset the PWC, Sit=
e on Grid","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down because the PWC OF ZTE dy=
sfunction // He reset the PWC, Site on Grid","gerard.tchangoue@matech-camer=
oun.com","25","16-06-2025 17:47:15","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005275169","Ron=
d Point Express1114","","16-06-2025 17:39:28","16-06-2025 17:34:18","16-06-=
2025 18:10:39","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Grid return","gerard.tchangoue@matech-camero=
un.com","311","16-06-2025 17:39:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005275126","Mfou EPC=
","","16-06-2025 17:34:06","16-06-2025 17:32:03","16-06-2025 17:51:01","Cas=
caded Incident from TTO5434847","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, Site Down before gen S=
tarted due to poor backup //Grid return","system","765237","16-06-2025 17:3=
4:06","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005275121","M=
fou OCM","IHS_YND_674","16-06-2025 17:33:14","16-06-2025 17:32:03","16-06-2=
025 17:51:01","Grid Outage, Site Down before gen Started due to poor backup=
 //Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site Down before gen Start=
ed due to poor backup //Grid return","edwige.kapawo@matech-cameroun.com","7=
2","16-06-2025 17:33:14","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005275010","S=
ous Prefecture","","16-06-2025 17:11:27","16-06-2025 17:01:59","16-06-2025 =
17:15:49","ACTIVE//No power issue site on Grid Ubaie =3D55.5 V, The tx fme =
 Fulbert (654266068/ Huawei) is informed","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE/=
/No power issue site on Grid Ubaie =3D55.5 V, The tx fme  Fulbert (65426606=
8/ Huawei) is informed","edwige.kapawo@matech-cameroun.com","569","16-06-20=
25 17:11:27","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005275001","M=
anguier","","16-06-2025 17:09:57","16-06-2025 17:08:47","16-06-2025 17:10:3=
0","Grid outage, site went down before gen start due to poor battery backup=
 // Gen Manually Started","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen Manually Started","edwige.=
kapawo@matech-cameroun.com","71","16-06-2025 17:09:57","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005274965","Mey=
o","IHS_YND_313","16-06-2025 17:02:53","16-06-2025 16:59:36","16-06-2025 18=
:32:01","Grid Outage, Site went Down due to Gen overload (17KVA, 260A) SS H=
IS Felix Zambe is informed // Grid return","Hyemafo Gildas","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid Outage, Site went Down due=
 to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed // Grid retur=
n","gerard.tchangoue@matech-cameroun.com","198","16-06-2025 17:02:53","MATE=
CH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0005274667","Men=
dong vallee","","16-06-2025 16:44:11","16-06-2025 16:42:05","16-06-2025 17:=
31:16","Grid Outage, Site went Down due to Gen overload (20KVA; 300A) IHS F=
=E9lix Zamb=E9 is informed and confirmed ","Fanda Brice","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid Outage, Site went Down due to=
 Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed and confirmed "=
,"gerard.tchangoue@matech-cameroun.com","127","16-06-2025 16:44:11","MATECH=
 CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005274651","Eto=
ug ebe Carrefour","","16-06-2025 16:41:25","16-06-2025 16:38:19","16-06-202=
5 17:28:13","Grid outage, site went down because gen start and stopped with=
 alarm ""high temp"" // he added water and manually start the Gen","Hyemafo=
 Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp -=
 Coolant Level Issue","Grid outage, site went down because gen start and st=
opped with alarm ""high temp"" // he added water and manually start the Gen=
","gerard.tchangoue@matech-cameroun.com","186","16-06-2025 16:41:25","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005274476","M=
ANGUIERS CHAPELLE","IHS_YND_506","16-06-2025 16:19:23","16-06-2025 16:10:15=
","16-06-2025 16:54:59","Active//No power issue on site ,site on Grid with =
Ubaie=3D53.6 V The Tx FME Symphorien (650257151 / Huawei) is informed","Fab=
rice Pouakam","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid with=
 Ubaie=3D53.6 V The Tx FME Symphorien (650257151 / Huawei) is informed","ed=
wige.kapawo@matech-cameroun.com","549","16-06-2025 16:19:23","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005274436","Nko=
lbisson IITA LP","","16-06-2025 16:16:04","16-06-2025 16:14:54","16-06-2025=
 16:29:59","No power issue site on grid with U=3D53.8v Mohamadou(69114435) =
from Huawei is informed","","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D53.8v Mohamadou(69114435) from Huawei is informed","gerard.tchangoue@mat=
ech-cameroun.com","71","16-06-2025 16:16:04","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005274352","OBA=
M NGOLA OCM","","16-06-2025 16:04:15","16-06-2025 16:01:04","16-06-2025 16:=
11:04","Grid Outage, Gen Failed to start due to Gen Card Faulty// Grid retu=
rn","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","Grid Outage, Gen Failed to start due to Gen Card Faulty// Grid ret=
urn","gerard.tchangoue@matech-cameroun.com","192","16-06-2025 16:04:15","MA=
TECH CMR"
"Closed Complete","Site Down","T1570","IHS_YND_140","NOCINC0005274330","BIS=
CUITERIE","","16-06-2025 16:00:13","16-06-2025 15:53:48","16-06-2025 17:07:=
24","Grid outage site went down because Gen failed to start due PWC dysfonc=
tion // He reset the PWC, gen manually started","Paul BIBOUM","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage site=
 went down because Gen failed to start due PWC dysfonction // He reset the =
PWC, gen manually started","gerard.tchangoue@matech-cameroun.com","475","16=
-06-2025 16:00:13","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005274286","T=
singa","","16-06-2025 15:54:09","16-06-2025 15:52:02","16-06-2025 21:52:02"=
,"Site went down due to PWC overload // Site stabilised","Mboua Thierry","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site =
went down due to PWC overload // Site stabilised","edwige.kapawo@matech-cam=
eroun.com","129","16-06-2025 15:54:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005274257","Bastos B=
ethesda","","16-06-2025 15:51:44","16-06-2025 15:33:59","16-06-2025 16:08:4=
8","Cascaded Incident from TTO5433787","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bef=
ore Gen start due to poor backup // Grid return","system","765522","16-06-2=
025 15:51:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005274256","Golf Qua=
ter","","16-06-2025 15:51:43","16-06-2025 15:33:59","16-06-2025 16:08:48","=
Cascaded Incident from TTO5433787","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down before =
Gen start due to poor backup // Grid return","system","765521","16-06-2025 =
15:51:43","MATECH CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0005274205","S=
OA UNIVERSITY STADIUM","","16-06-2025 15:44:39","16-06-2025 15:36:28","16-0=
6-2025 16:31:51","Grid bad voltage, site went down because Gen failed to st=
art due to lack of 01 phase // He did a bridge on the good phase","Siligap =
Boris","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid bad voltage, site went down because Gen failed to start due to l=
ack of 01 phase // He did a bridge on the good phase","edwige.kapawo@matech=
-cameroun.com","492","16-06-2025 15:44:39","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005274161","B=
astos-Nylon","IHS_YND_220, IHS_YND_563","16-06-2025 15:42:49","16-06-2025 1=
5:33:59","16-06-2025 15:48:48","Grid outage, Site went down before Gen star=
t due to poor backup // Grid return","Mboua Thierry","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site wen=
t down before Gen start due to poor backup // Grid return","edwige.kapawo@m=
atech-cameroun.com","531","16-06-2025 15:42:49","MATECH CMR"
"Closed Complete","Site Down","T1085","IHS_YND_130","NOCINC0005274147","Bas=
tos usine","","16-06-2025 15:40:08","16-06-2025 15:35:01","16-06-2025 15:49=
:01","	Grid outage, Site went down before Gen start due to poor backup // G=
rid return","Mboua Thierry","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","	Grid outage, Site went down before Gen start =
due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.com","=
308","16-06-2025 15:40:08","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005274002","E=
mana lycee 2","","16-06-2025 15:31:31","16-06-2025 15:26:10","16-06-2025 17=
:15:04","Grid bad voltage, site went down because Gen failed to start due t=
o lack of 01 phase // He did a bridge on the good phase","Fabrice Pouakam",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid bad voltage, site went down because Gen failed to start due to lack of =
01 phase // He did a bridge on the good phase","edwige.kapawo@matech-camero=
un.com","323","16-06-2025 15:31:31","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005273669","M=
essassi okolo","","16-06-2025 15:18:29","16-06-2025 15:13:16","16-06-2025 1=
6:52:30","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Access issues due to landlord(Landlord has forbidden to =
start the Gen due to noise // Grid return","edwige.kapawo@matech-cameroun.c=
om","1233260","16-06-2025 15:18:29","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005273597","E=
MANA BILICK CITY","IHS_YND_279","16-06-2025 15:16:25","16-06-2025 15:13:16"=
,"16-06-2025 16:55:48","Access issues due to landlord(Landlord has forbidde=
n to start the Gen due to noise // Grid return","Fabrice Pouakam","Access D=
enial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord=
","Access issues due to landlord(Landlord has forbidden to start the Gen du=
e to noise // Grid return","edwige.kapawo@matech-cameroun.com","191","16-06=
-2025 15:16:25","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005273567","Eto=
ug ebe biscuiterie","","16-06-2025 15:13:44","16-06-2025 15:05:25","16-06-2=
025 15:37:25","Grid fluctuations, site went down due to Grid bad voltage an=
d no rcp on site // Grid Stabilised","Hyemafo Gildas","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid fluctuations, sit=
e went down due to Grid bad voltage and no rcp on site // Grid Stabilised",=
"gerard.tchangoue@matech-cameroun.com","499","16-06-2025 15:13:44","MATECH =
CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005273482","N=
kolbong","","16-06-2025 15:12:46","16-06-2025 15:10:27","18-06-2025 15:46:5=
5","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Ge=
n started and stopped due to Gen overload(22kva//350A) // Grid return","edw=
ige.kapawo@matech-cameroun.com","140","16-06-2025 15:12:46","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005273444","S=
OA TOWN","","16-06-2025 15:11:14","16-06-2025 15:06:03","16-06-2025 16:10:2=
0","Grid outage gen failed to start due to alarm high temp//We add water an=
d gen manually started","Siligap Boris","Equipment Repair","Passive","ACDG =
Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage gen faile=
d to start due to alarm high temp//We add water and gen manually started","=
edwige.kapawo@matech-cameroun.com","312","16-06-2025 15:11:14","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005273411","Fla=
menco","","16-06-2025 15:10:09","16-06-2025 15:01:59","16-06-2025 15:44:34"=
,"Grid outage .gen failed to start due to card GE Faulty //Grid return","Mb=
oua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage .gen failed to start due to card GE Faulty //Grid return","ge=
rard.tchangoue@matech-cameroun.com","491","16-06-2025 15:10:09","MATECH CMR=
"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005273409","O=
mnisport-Rail","","16-06-2025 15:10:05","16-06-2025 16:10:15","16-06-2025 1=
6:54:59","","Delor Telezing","Cascade Outage","Active","Cascade Active","Ca=
scade Active","Active//No power issue on site ,site on Grid with Ubaie=3D53=
.6 V The Tx FME Symphorien (650257151 / Huawei) is informed","edwige.kapawo=
@matech-cameroun.com","770008","16-06-2025 15:10:05","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005273293","M=
ontee-Des-Soeurs","","16-06-2025 15:09:20","16-06-2025 15:03:11","16-06-202=
5 16:22:44","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","edwige.kapawo@matech-cameroun.com","371","16-06-2025 15:09:20"=
,"MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005273158","NKO=
MKANA ELIZA HOTEL","","16-06-2025 15:05:54","16-06-2025 14:56:43","16-06-20=
25 15:41:43","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to PWC Overloaded and SS IHS Bern=
ard Atangana confirmed // Site stabilised","gerard.tchangoue@matech-camerou=
n.com","552","16-06-2025 15:05:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_287","NOCINC0005273064","Nkolafem=
e","IHS_YND_309","16-06-2025 15:05:02","16-06-2025 15:02:08","16-06-2025 15=
:04:29","Active//No power issue, Site on Grid Ubai=3D 55,9V The TX Mouhamad=
ou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue, Site on Grid Ubai=3D 55,9V The TX Mouhamadou (61=
44435) from Huawei is informed.","system","174","16-06-2025 15:05:02","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0005272903","L=
eboudi","","16-06-2025 15:04:16","16-06-2025 15:02:08","16-06-2025 15:04:29=
","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade Active",=
"Cascade Active","Active//No power issue, Site on Grid Ubai=3D 55,9V The TX=
 Mouhamadou (6144435) from Huawei is informed.","edwige.kapawo@matech-camer=
oun.com","767211","16-06-2025 15:04:16","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005272827","S=
imbock OCM","","16-06-2025 15:02:45","16-06-2025 14:56:37","16-06-2025 16:0=
0:09","Active // No power issue Ubaie:49.6V site on Battery The Tx Fme Hosi=
ah Mbah (674007438 / Huawei) is informed","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve // No power issue Ubaie:49.6V site on Battery The Tx Fme Hosiah Mbah (67=
4007438 / Huawei) is informed","edwige.kapawo@matech-cameroun.com","369","1=
6-06-2025 15:02:45","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005272817","Ebo=
go","","16-06-2025 15:00:18","16-06-2025 14:54:06","16-06-2025 15:34:03","A=
ctive// No Power issue on site Ubaie 48.3V site on Batt, Julien /693095849 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issu=
e on site Ubaie 48.3V site on Batt, Julien /693095849 from Huawei is inform=
ed","gerard.tchangoue@matech-cameroun.com","373","16-06-2025 15:00:18","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_758","NOCINC0005272640","Nkolfoul=
ou CSD MTN","","16-06-2025 14:46:47","16-06-2025 14:31:25","16-06-2025 14:5=
2:25","Cascaded Incident from TTO5432125","Siligap Boris","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down due to work: =
NDOGMO Auremien  (SFM /656179911) is on Site for  SWAP PWC ZTE & BAT // En =
of work","system","768808","16-06-2025 14:46:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0005272641","Nkolfoul=
ou Tsinga Village","","16-06-2025 14:46:47","16-06-2025 14:31:25","16-06-20=
25 14:52:25","Cascaded Incident from TTO5432125","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Site went down due to=
 work: NDOGMO Auremien  (SFM /656179911) is on Site for  SWAP PWC ZTE & BAT=
 // En of work","system","768809","16-06-2025 14:46:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005272639","SOA VILL=
AGE","","16-06-2025 14:46:46","16-06-2025 14:31:25","16-06-2025 14:52:25","=
Cascaded Incident from TTO5432125","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work: NDOGMO =
Auremien  (SFM /656179911) is on Site for  SWAP PWC ZTE & BAT // En of work=
","system","768806","16-06-2025 14:46:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005272638","TSINGA V=
ILLAGE 2","","16-06-2025 14:46:46","16-06-2025 14:31:25","16-06-2025 14:52:=
25","Cascaded Incident from TTO5432125","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work: N=
DOGMO Auremien  (SFM /656179911) is on Site for  SWAP PWC ZTE & BAT // En o=
f work","system","768807","16-06-2025 14:46:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005272637","Mvog-Eba=
nda","","16-06-2025 14:46:46","16-06-2025 14:31:25","16-06-2025 14:52:25","=
Cascaded Incident from TTO5432125","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work: NDOGMO =
Auremien  (SFM /656179911) is on Site for  SWAP PWC ZTE & BAT // En of work=
","system","768811","16-06-2025 14:46:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005272636","FOUGEROL=
E","","16-06-2025 14:46:46","16-06-2025 14:31:25","16-06-2025 14:52:25","Ca=
scaded Incident from TTO5432125","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to work: NDOGMO Au=
remien  (SFM /656179911) is on Site for  SWAP PWC ZTE & BAT // En of work",=
"system","768805","16-06-2025 14:46:46","MATECH CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0005272583","Nko=
lfoulou 2","IHS_YND_561, IHS_YND_269, IHS_YND_719, IHS_YND_323, IHS_YND_758=
, IHS_YND_296, IHS_YND_759","16-06-2025 14:40:36","16-06-2025 14:31:25","16=
-06-2025 14:52:25","Site went down due to work: NDOGMO Auremien  (SFM /6561=
79911) is on Site for  SWAP PWC ZTE & BAT // En of work","Siligap Boris","I=
nstallation Activity","Passive","Planned Activity","Installation Activity",=
"Site went down due to work: NDOGMO Auremien  (SFM /656179911) is on Site f=
or  SWAP PWC ZTE & BAT // En of work","loic.noumsi@matech-cameroun.com","55=
2","16-06-2025 14:40:36","MATECH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0005272571","O=
ssombe","","16-06-2025 14:36:03","16-06-2025 14:34:49","16-06-2025 14:52:45=
","Active //No power issue, site on Gen with Ubaie=3D48V, The TX FME Gregoi=
re (654547479) from Huawei is informed.","Parker Tchoup","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 //No power issue, site on Gen with Ubaie=3D48V, The TX FME Gregoire (65454=
7479) from Huawei is informed.","edwige.kapawo@matech-cameroun.com","75","1=
6-06-2025 14:36:03","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0005272553","Nko=
lfoulou","","16-06-2025 14:33:32","16-06-2025 14:31:25","16-06-2025 19:08:3=
1","Site impacted by Nkolfoulou 2","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work: NDOGMO =
Auremien  (SFM /656179911) is on Site for  SWAP PWC ZTE & BAT // En of work=
","loic.noumsi@matech-cameroun.com","776210","16-06-2025 14:33:32","MATECH =
CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005272538","Nko=
l-Mbanda","","16-06-2025 14:30:08","16-06-2025 14:21:56","16-06-2025 16:47:=
18","Grid outage site site went because Gen failed to started due to PWC dy=
sfunction // He reset it and manually started the GEN","MINKA NICOLAS","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid ou=
tage site site went because Gen failed to started due to PWC dysfunction //=
 He reset it and manually started the GEN","loic.noumsi@matech-cameroun.com=
","493","16-06-2025 14:30:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005272486","MEHANDAN=
","","16-06-2025 14:19:21","16-06-2025 14:17:33","16-06-2025 14:20:59","Cas=
caded Incident from TTO5432025","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction //Grid return","system",=
"769607","16-06-2025 14:19:21","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005272484","O=
dza II OCM","IHS_YND_528","16-06-2025 14:18:39","16-06-2025 14:17:33","16-0=
6-2025 14:20:59","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction //Grid return","Albran Byorel","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuatio=
ns, site went down because gen failed to start due to PWC ZTE malfunction /=
/Grid return","gaelle.njiofack@matech-cameroun.com","68","16-06-2025 14:18:=
39","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005272341","Jou=
vence Mbenda","","16-06-2025 13:55:49","16-06-2025 13:50:42","16-06-2025 14=
:00:42","Grid outage, Site went down because Gen failed to start due to sur=
ged protector  causing by Lightning// He bypassed it and started Gen manual=
y","Hyemafo Gildas","Force Majeure","Natural Disaster","Thunderstrike","Equ=
ipment Damaged","Grid outage, Site went down because Gen failed to start du=
e to surged protector  causing by Lightning// He bypassed it and started Ge=
n manualy","franck.nkomot@matech-cameroun.com","308","16-06-2025 13:55:49",=
"MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005272236","Nom=
ayos montee Meche","","16-06-2025 13:38:41","16-06-2025 13:34:34","16-06-20=
25 13:51:39","Grid outage, site went down before Gen started due  poor batt=
ery backup // Gen Started Automatically","Fanda Brice","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before Gen started due  poor battery backup // Gen Started Automat=
ically","franck.nkomot@matech-cameroun.com","266","16-06-2025 13:38:41","MA=
TECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005272139","Eto=
ug ebe Carrefour","","16-06-2025 13:19:11","16-06-2025 13:11:55","16-06-202=
5 13:21:55","Grid outage site went down before gen started due to poor batt=
ery backup // Grid returned","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage site went down b=
efore gen started due to poor battery backup // Grid returned","franck.nkom=
ot@matech-cameroun.com","437","16-06-2025 13:19:11","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005272100","O=
lembe","","16-06-2025 13:12:46","16-06-2025 13:10:40","16-06-2025 18:00:14"=
,"Hermane ( 699999625 /Grato ) is on site for work (  Swap of bay IPT )","F=
abrice Pouakam","Installation Activity","Passive","Planned Activity","Insta=
llation Activity","Hermane ( 699999625 /Grato ) is on site for work (  Swap=
 of bay IPT ) // End of work","gaelle.njiofack@matech-cameroun.com","127","=
16-06-2025 13:12:46","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005271829","C=
hapelle-Nsimeyong","","16-06-2025 12:38:56","16-06-2025 12:36:26","16-06-20=
25 12:42:30","Grid outage, Site went down because Gen failed to start due t=
o Gen card disfunction// Grid restoration","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down=
 because Gen failed to start due to Gen card disfunction// Grid restoration=
","gaelle.njiofack@matech-cameroun.com","151","16-06-2025 12:38:56","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005271529","N=
komo","IHS_YND_174","16-06-2025 11:58:18","16-06-2025 11:56:11","21-06-2025=
 01:08:54","Site down due to PWC overload ( PWC of 12 k and iload of 200A) =
// PWC swapped ","Mba Lazare Herve","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site down due to PWC overload ( PWC of 12 =
k and iload of 200A) // PWC swapped ","gaelle.njiofack@matech-cameroun.com"=
,"128","16-06-2025 11:58:18","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005271379","Eto=
ug ebe biscuiterie","","16-06-2025 11:36:12","16-06-2025 11:31:04","16-06-2=
025 11:55:04","Grid outage,Site went down because Gen failed to start due t=
o battery GE discharged causing by static charger faulty // He started Gen =
manually with external battery","Hyemafo Gildas","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Generator Battery","Grid outage,Site went down becaus=
e Gen failed to start due to battery GE discharged causing by static charge=
r faulty // He started Gen manually with external battery","franck.nkomot@m=
atech-cameroun.com","309","16-06-2025 11:36:12","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005270905","Mey=
o","IHS_YND_313","16-06-2025 10:34:23","16-06-2025 10:29:14","16-06-2025 16=
:02:49","Grid outage, site went down due to Gen overload (17KVA, 260A) SS H=
IS Felix Zambe is informed and confirmed // Grid returned","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, si=
te went down due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is inform=
ed and confirmed // Grid returned","franck.nkomot@matech-cameroun.com","310=
","16-06-2025 10:34:23","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005270895","Eki=
e sud","","16-06-2025 10:32:06","16-06-2025 10:26:57","16-06-2025 11:00:57"=
,"  Site down due to Disjonction of CB (125 A ) in the  DC BOX // CB reamed=
","Albran Byorel","Equipment Repair","Passive","Control Panel","Circuit Bre=
aker Tripped","  Site down due to Disjonction of CB (125 A ) in the  DC BOX=
 // CB reamed","franck.nkomot@matech-cameroun.com","310","16-06-2025 10:32:=
06","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005270894","A=
fanoya","","16-06-2025 10:31:56","16-06-2025 10:29:14","16-06-2025 14:02:26=
","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, site went down due to Gen overload (17KVA, 260A) SS=
 HIS Felix Zambe is informed and confirmed // Grid returned","gaelle.njiofa=
ck@matech-cameroun.com","776205","16-06-2025 10:31:56","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005270757","M=
fou OCM","IHS_YND_674","16-06-2025 10:08:01","16-06-2025 10:00:53","16-06-2=
025 10:16:48","Grid fluctuation, Gen fail to start due to grid fluctuation =
// Grid stabilize","Mba Lazare Herve","Grid Supply","Passive","Grid","Natio=
nal Grid - Grid Outage Issue","Grid fluctuation, Gen fail to start due to g=
rid fluctuation // Grid stabilize","gaelle.njiofack@matech-cameroun.com","4=
29","16-06-2025 10:08:01","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0005270751","M=
fou EPC","","16-06-2025 10:07:28","16-06-2025 10:00:53","16-06-2025 10:16:4=
8","Grid fluctuation, Gen fail to start due to grid fluctuation // Grid sta=
bilize","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid fluctuation, Gen fail to start due to grid fluctuation=
 // Grid stabilize","gaelle.njiofack@matech-cameroun.com","777862","16-06-2=
025 10:07:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0005270677","Tamtam W=
eekend","","16-06-2025 09:53:53","16-06-2025 09:44:18","16-06-2025 14:54:55=
","Cascaded Incident from TTO5430066","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to insuffici=
ency of rectifiers // He reset Rectifier and reduced load","system","778837=
","16-06-2025 09:53:53","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005270654","M=
vog Mbi New","IHS_YND_151, IHS_YND_021","16-06-2025 09:50:36","16-06-2025 0=
9:44:18","16-06-2025 14:11:55","( unstable )Site went down due to insuffici=
ency of rectifiers ","MINKA NICOLAS","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to insufficiency of rectifiers //=
 He reset Rectifier and reduced load","gaelle.njiofack@matech-cameroun.com"=
,"379","16-06-2025 09:50:36","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005270619","Nom=
ayos montee Meche","","16-06-2025 09:44:05","16-06-2025 09:40:53","16-06-20=
25 13:28:53","Grid outage, site went down before Gen started due rectifiers=
 issue and poor battery backup // Grid returned","Fanda Brice","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
, site went down before Gen started due rectifiers issue and poor battery b=
ackup // Grid returned","franck.nkomot@matech-cameroun.com","471","16-06-20=
25 09:44:05","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005270548","B=
arriere","","16-06-2025 09:33:52","16-06-2025 09:32:28","16-06-2025 09:35:2=
8","Active// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","gaelle.njiofack@matech-cameroun.com","86","16-06-2025 09:33:52=
","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005270540","M=
eyo","","16-06-2025 09:32:29","16-06-2025 09:29:19","16-06-2025 10:22:51","=
Grid outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix =
Zambe is informed and confirmed // Grid returned","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went d=
own due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and co=
nfirmed // Grid returned","gaelle.njiofack@matech-cameroun.com","191","16-0=
6-2025 09:32:29","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005270513","C=
-Supreme","","16-06-2025 09:28:05","16-06-2025 09:44:18","16-06-2025 14:54:=
55","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","S=
ite went down due to insufficiency of rectifiers // He reset Rectifier and =
reduced load","gaelle.njiofack@matech-cameroun.com","778837","16-06-2025 09=
:28:05","MATECH CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0005270500","Y=
de-M-Central","","16-06-2025 09:25:24","16-06-2025 09:24:38","16-06-2025 11=
:05:58","Site down due to double  disonction in the PWC bay / / CB rearmed =
","","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit =
Breaker Issue","Site down due to double  disonction in the PWC bay / / CB r=
earmed ","gaelle.njiofack@matech-cameroun.com","47","16-06-2025 09:25:24","=
MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005270440","N=
omayos montee Meche","","16-06-2025 09:15:26","16-06-2025 09:14:15","16-06-=
2025 09:35:15","Grid outage, site went down before Gen started due to poor =
backup battery // Grid returned","Fanda Brice","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before Gen started due to poor backup battery // Grid returned","gaelle.nj=
iofack@matech-cameroun.com","72","16-06-2025 09:15:26","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0005270344","S=
AA 2","","16-06-2025 08:59:30","16-06-2025 08:55:14","16-06-2025 08:55:15",=
"","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve"," Team of LEC 694391842 (Mouafo) is on site for work (MICROWAVES ALIGME=
NTS)","gaelle.njiofack@matech-cameroun.com","775089","16-06-2025 08:59:30",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005270333","S=
aa","","16-06-2025 08:58:24","16-06-2025 08:55:14","16-06-2025 08:55:15",""=
,"Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active=
"," Team of LEC 694391842 (Mouafo) is on site for work (MICROWAVES ALIGMENT=
S)","gaelle.njiofack@matech-cameroun.com","775086","16-06-2025 08:58:24","M=
ATECH CMR"
"Closed Complete","Site Down","T0460","IHS_YND_201","NOCINC0005270325","Cit=
e Verte","","16-06-2025 08:55:38","16-06-2025 08:48:26","16-06-2025 10:07:3=
4","Grid outage, No MG to deploy site. // Grid restauration","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No MG=
 to deploy site. // Grid restauration","franck.nkomot@matech-cameroun.com",=
"432","16-06-2025 08:55:38","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005270195","Nko=
lbisson IITA LP","","16-06-2025 08:28:34","16-06-2025 08:25:24","16-06-2025=
 08:28:21","No power issue site on grid with U=3D53.2v Mohamadou(69114435) =
from Huawei is informed","","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D53.2v Mohamadou(69114435) from Huawei is informed","franck.nkomot@matech=
-cameroun.com","191","16-06-2025 08:28:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005270170","Nsam esc=
ale LP","","16-06-2025 08:19:28","16-06-2025 08:13:40","16-06-2025 08:19:40=
","Cascaded Incident from TTO5429543","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, site went down before Gen starte=
d due to poor backup // Grid returned","system","1215371","16-06-2025 08:19=
:28","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005270166","Nsa=
m Sofavinc","IHS_YND_732","16-06-2025 08:18:48","16-06-2025 08:13:40","16-0=
6-2025 08:19:40","Grid outage, site went down before Gen started due to poo=
r backup // Grid returned","MINKA NICOLAS","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen started due to poor backup // Grid returned","franck.nkomot@matech-=
cameroun.com","309","16-06-2025 08:18:48","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005270162","Sim=
e Building","","16-06-2025 08:18:02","16-06-2025 08:09:52","16-06-2025 08:2=
7:58","Grid outage, site went down because Gen failed to start due to GE ba=
ttery faulty//Grid restoration","Mboua Thierry","Equipment Repair","Passive=
","ACDG Gen","ACDG - Generator Battery","Grid outage, site went down becaus=
e Gen failed to start due to GE battery faulty//Grid restoration","franck.n=
komot@matech-cameroun.com","490","16-06-2025 08:18:02","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005270159","Ron=
d Point Express1114","","16-06-2025 08:17:36","16-06-2025 08:10:22","16-06-=
2025 08:28:22","Active: No power issue, site is on grid with Ubaie=3D54,5V,=
 Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active: No power issue, site is on grid with Ubaie=3D54,5V, Mbah hosiah(=
699699694) from Huawei is informed","franck.nkomot@matech-cameroun.com","43=
5","16-06-2025 08:17:36","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005270142","E=
seka OCM","","16-06-2025 08:10:59","16-06-2025 08:09:58","16-06-2025 08:13:=
35","Grid outage,Site went down because Gen start and stopped due to Gen ca=
rd dysfunction // Grid restoration","Kemeni Franklin","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage,Site went down becau=
se Gen start and stopped due to Gen card dysfunction // Grid restoration","=
gaelle.njiofack@matech-cameroun.com","61","16-06-2025 08:10:59","MATECH CMR=
"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0005270135","T=
ongolo OCM","","16-06-2025 08:09:06","16-06-2025 08:08:00","16-06-2025 10:3=
3:29","Grid outage .gen failed to start due to grid contactor faulty//We by=
pass grid contactor and gen manually started ","Delor Telezing","Equipment =
Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage .gen failed =
to start due to grid contactor faulty//We bypass grid contactor and gen man=
ually started ","gaelle.njiofack@matech-cameroun.com","67","16-06-2025 08:0=
9:06","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005270134","N=
omayos montee Meche","","16-06-2025 08:08:29","16-06-2025 08:04:09","16-06-=
2025 08:21:18","Grid outage, site went down before Gen started due to poor =
backup battery // Grid returned","Fanda Brice","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before Gen started due to poor backup battery // Grid returned","gaelle.nj=
iofack@matech-cameroun.com","1145","16-06-2025 08:08:29","MATECH CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0005269929","Mae=
tur","","16-06-2025 07:41:16","16-06-2025 07:34:01","16-06-2025 07:54:12","=
Grid outage, site down due to GE circuit breaker (32 A) disjunction // CB r=
earmed","Mboua Thierry","Equipment Repair","Passive","Control Panel","Circu=
it Breaker Tripped","Grid outage, site down due to GE circuit breaker (32 A=
) disjunction // CB rearmed","franck.nkomot@matech-cameroun.com","436","16-=
06-2025 07:41:16","MATECH CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0005269686","M=
amch Building","","16-06-2025 06:58:55","16-06-2025 06:52:44","16-06-2025 0=
7:44:37","Grid outage, site went down due to  Gen Card malfunction  ( Gen s=
topped with ''Underfrequency' ALARM) // Gen Card reseted  & manually starte=
d","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid outage, site went down due to  Gen Card malfunction  ( Gen sto=
pped with ''Underfrequency' ALARM) // Gen Card reseted  & manually started"=
,"loic.noumsi@matech-cameroun.com","372","16-06-2025 06:58:55","MATECH CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0005269517","Don=
ga","","16-06-2025 06:21:31","16-06-2025 06:19:24","16-06-2025 06:23:48","A=
ctive//No power issue with U=3D51.4V // site on Gen THe fme tx Gregoire 652=
070658 from Huawei is informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue with U=3D51.4V // site on Gen THe fme tx Gregoire 652070658 from Hu=
awei is informed","gaelle.njiofack@matech-cameroun.com","128","16-06-2025 0=
6:21:31","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005269468","Mam=
ch Building","","16-06-2025 06:03:16","16-06-2025 06:01:11","16-06-2025 06:=
11:34","Grid outage site went down because Gen stopped with ''Underfrequenc=
y' ALARM // he reset the Gen Card and manually started Gen","Mboua Thierry"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e site went down because Gen stopped with ''Underfrequency' ALARM // he res=
et the Gen Card and manually started Gen","loic.noumsi@matech-cameroun.com"=
,"126","16-06-2025 06:03:16","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0005269349","Eto=
 koss Yde","","16-06-2025 05:27:04","16-06-2025 05:24:56","16-06-2025 06:11=
:44","Grid outage, Site went down because Gen failed to start due to gen co=
ntactor faulty // He bypassed contactor and connected Gen directly on load"=
,"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contact=
or","Grid outage, Site went down because Gen failed to start due to gen con=
tactor faulty // He bypassed contactor and connected Gen directly on load",=
"gaelle.njiofack@matech-cameroun.com","129","16-06-2025 05:27:04","MATECH C=
MR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005269341","Sim=
e Building","","16-06-2025 05:24:39","16-06-2025 05:21:03","16-06-2025 07:4=
3:38","Grid outage, site went down because Gen failed to start due to GE ba=
ttery faulty // Grid restoration","Mboua Thierry","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Generator Battery","Grid outage, site went down beca=
use Gen failed to start due to GE battery faulty // Grid restoration","loic=
.noumsi@matech-cameroun.com","217","16-06-2025 05:24:39","MATECH CMR"
"Closed Complete","Site Down","T0460","IHS_YND_201","NOCINC0005269201","Cit=
e Verte","","16-06-2025 04:17:25","16-06-2025 04:16:17","16-06-2025 08:26:1=
7","Grid outage, No MG to deploy site // Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, No MG to dep=
loy site // Grid return","loic.noumsi@matech-cameroun.com","69","16-06-2025=
 04:17:25","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0005269130","Men=
dong vallee","","16-06-2025 03:38:09","16-06-2025 03:36:56","16-06-2025 06:=
26:50","Grid outage site went down because Gen over load (20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed and confirmed //Grid returned","Fanda Brice","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site w=
ent down because Gen over load (20KVA; 300A) IHS F=E9lix Zamb=E9 is informe=
d and confirmed //Grid returned","loic.noumsi@matech-cameroun.com","74","16=
-06-2025 03:38:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005268907","MEHANDAN=
","","16-06-2025 02:11:03","16-06-2025 02:01:22","16-06-2025 02:04:17","Cas=
caded Incident from TTO5428183","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","799551","16-06-2025 02:11:03","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005268890","O=
dza II OCM","IHS_YND_528","16-06-2025 02:04:33","16-06-2025 02:01:22","16-0=
6-2025 02:04:17","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","gaelle.njiofack@matech-cameroun.com","193","16-06-=
2025 02:04:33","MATECH CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0005268750","NKO=
LOSSAN OKOK","","16-06-2025 01:15:33","16-06-2025 01:07:27","16-06-2025 06:=
54:33","Grid outage, Gen stopped due to alarm under voltage // Gen card res=
et, Gen purged and gen start manually.","Parker Tchoup","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen stopped due t=
o alarm under voltage // Gen card reset, Gen purged and gen start manually.=
","loic.noumsi@matech-cameroun.com","487","16-06-2025 01:15:33","MATECH CMR=
"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005268664","M=
eyo","","16-06-2025 00:50:48","16-06-2025 00:47:26","16-06-2025 05:53:57","=
Grid outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix =
Zambe is informed and confirmed // Grid returned","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went d=
own due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and co=
nfirmed // Grid returned","gaelle.njiofack@matech-cameroun.com","203","16-0=
6-2025 00:50:48","MATECH CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0005268489","D=
ong","","16-06-2025 00:04:51","15-06-2025 23:57:32","16-06-2025 03:45:15","=
Hybrid Gen site, Site went down because Gen started and stopped due to high=
 temp alarm // He added water and Gen manually started","Parker Tchoup","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Hybrid Gen site, Site went down because Gen started and stopped =
due to high temp alarm // He added water and Gen manually started","loic.no=
umsi@matech-cameroun.com","441","16-06-2025 00:04:51","MATECH CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0005268225","An-=
Marche-Melen","","15-06-2025 23:17:56","15-06-2025 23:15:50","15-06-2025 23=
:47:24","Grid outage,no space to deploy mobile gen // Grid returned","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e,no space to deploy mobile gen // Grid returned","loic.noumsi@matech-camer=
oun.com","127","15-06-2025 23:17:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005267986","Mom","",=
"15-06-2025 22:57:30","15-06-2025 22:40:20","15-06-2025 23:24:22","Cascaded=
 Incident from TTO5427140","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Hybrid gen site, Site went down because gen f=
ailed to start due to hybrid system disfunctionning//he started the gen man=
ually","system","804221","15-06-2025 22:57:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005267985","OTELE MT=
N","","15-06-2025 22:57:30","15-06-2025 22:40:20","15-06-2025 23:24:22","Ca=
scaded Incident from TTO5427140","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid gen site, Site went down because=
 gen failed to start due to hybrid system disfunctionning//he started the g=
en manually","system","804221","15-06-2025 22:57:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005267948","Mbeng","=
","15-06-2025 22:48:42","15-06-2025 22:40:20","15-06-2025 23:23:17","Cascad=
ed Incident from TTO5427139","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Hybrid gen site, Site went down because gen=
 failed to start due to hybrid system disfunctionning//he started the gen m=
anually","system","804224","15-06-2025 22:48:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005267949","Bondjock=
","","15-06-2025 22:48:42","15-06-2025 22:40:20","15-06-2025 23:23:17","Cas=
caded Incident from TTO5427139","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Hybrid gen site, Site went down because =
gen failed to start due to hybrid system disfunctionning//he started the ge=
n manually","system","804224","15-06-2025 22:48:42","MATECH CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0005267938","M=
inka","IHS_YND_369, IHS_YND_531, IHS_YND_554, IHS_YND_553, IHS_YND_370, IHS=
_YND_372","15-06-2025 22:46:27","15-06-2025 22:40:20","15-06-2025 23:24:22"=
,"Hybrid gen site, Site went down because gen failed to start due to hybrid=
 system disfunctionning//he started the gen manually","Fanda Brice","Equipm=
ent Repair","Passive","Hybrid","Hybrid Module","Hybrid gen site, Site went =
down because gen failed to start due to hybrid system disfunctionning//he s=
tarted the gen manually","loic.noumsi@matech-cameroun.com","369","15-06-202=
5 22:46:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005267395","Nsam esc=
ale LP","","15-06-2025 22:21:07","15-06-2025 22:15:36","15-06-2025 22:47:50=
","Cascaded Incident from TTO5426560","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Site went Down due to disjunction of rectifie=
r circuit breaker // He rearmed CB, ","system","798652","15-06-2025 22:21:0=
7","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005267378","Nsa=
m Sofavinc","IHS_YND_732","15-06-2025 22:19:43","15-06-2025 22:15:36","15-0=
6-2025 22:47:50","Site went Down due to disjunction of rectifier circuit br=
eaker // He rearmed CB, ","MINKA NICOLAS","Equipment Repair","Passive","Rec=
tifier","Rectifier - Circuit Breaker","Site went Down due to disjunction of=
 rectifier circuit breaker // He rearmed CB, ","gerard.tchangoue@matech-cam=
eroun.com","248","15-06-2025 22:19:43","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005267255","Ako=
k Ndoe Yde","","15-06-2025 22:15:36","15-06-2025 22:12:24","15-06-2025 22:5=
4:17","Grid outage site went down before gen start due to poor battery back=
up // Geen auatomatically started","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage site went =
down before gen start due to poor battery backup // Geen auatomatically sta=
rted","gerard.tchangoue@matech-cameroun.com","193","15-06-2025 22:15:36","M=
ATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0005266777","Ole=
mbe MTN","","15-06-2025 21:48:24","15-06-2025 21:46:17","15-06-2025 22:20:4=
4","Grid outage, Gen failed to start due to his CB disjunct // Grid return =
and CB Rearm.","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Load Breaker","Grid outage, Gen failed to start due to his CB disjunc=
t // Grid return and CB Rearm.","gerard.tchangoue@matech-cameroun.com","129=
","15-06-2025 21:48:24","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005266210","Mey=
o","","15-06-2025 21:19:51","15-06-2025 21:18:44","15-06-2025 22:04:07","Gr=
id outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix Za=
mbe is informed and confirmed // Grid returned","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went dow=
n due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and conf=
irmed // Grid returned","gerard.tchangoue@matech-cameroun.com","68","15-06-=
2025 21:19:51","MATECH CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0005266163","M=
aison-Blanche-IHS","","15-06-2025 21:18:29","15-06-2025 21:16:18","16-06-20=
25 00:35:25","Grid outage.no space to deploy mobile // Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.no space to deploy mobile // Grid return","vanel.mbiada@matech-cameroun.co=
m","132","15-06-2025 21:18:29","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005265884","Nko=
lbisson IITA LP","","15-06-2025 21:06:24","15-06-2025 21:02:18","15-06-2025=
 22:10:52","Access issues during the weekend due to Lanlord (Grid Only, No =
space to deploy awaiting Grid restored)// Grid returned","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Access issues during t=
he weekend due to Lanlord (Grid Only, No space to deploy awaiting Grid rest=
ored)// Grid returned","gerard.tchangoue@matech-cameroun.com","247","15-06-=
2025 21:06:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005265564","Carrefou=
rt Nkomo","","15-06-2025 20:49:46","15-06-2025 19:52:10","16-06-2025 08:52:=
19","Cascaded Incident from TTO5423754","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to Power=
 Cabinet overloaded ( PWC of 12 k and iload of 200A)//Grid return","system"=
,"1266999","15-06-2025 20:49:46","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005265377","Beh=
ind P T school Yde","","15-06-2025 20:41:34","15-06-2025 20:38:28","16-06-2=
025 10:04:36","Access issue during the night Grid Outage, Site went down be=
cause The rectifiers are not powered due to malfunctioning of MPR on site /=
/ We reset rectifiers","Paul BIBOUM","Access Denial","Lease Or Legal","Land=
lord Related Issues","Access Issue - Land Lord","Access issue during the ni=
ght Grid Outage, Site went down because The rectifiers are not powered due =
to malfunctioning of MPR on site // We reset rectifiers","gerard.tchangoue@=
matech-cameroun.com","187","15-06-2025 20:41:34","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005265337","Nko=
lbisson IITA LP","","15-06-2025 20:38:15","15-06-2025 20:37:09","15-06-2025=
 20:55:06","Access issues during the weekend due to Lanlord (Grid Only, No =
space to deploy awaiting Grid restored) // Grid return","","Access Denial",=
"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Acce=
ss issues during the weekend due to Lanlord (Grid Only, No space to deploy =
awaiting Grid restored) // Grid return","gerard.tchangoue@matech-cameroun.c=
om","67","15-06-2025 20:38:15","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005265188","Nom=
ayos montee Meche","","15-06-2025 20:31:51","15-06-2025 20:29:36","15-06-20=
25 20:31:02","Grid outage, site went down before Gen started due to poor ba=
ckup battery // Grid returned","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen started due to poor backup battery // Grid returned","gerard.tcha=
ngoue@matech-cameroun.com","136","15-06-2025 20:31:51","MATECH CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0005264732","N=
yanon","","15-06-2025 20:16:29","15-06-2025 19:25:19","15-06-2025 21:23:11"=
,"Site went down because Gen failed to start due to Alarm low oil pressure =
// Oil Add and Gen start manually","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down becaus=
e Gen failed to start due to Alarm low oil pressure // Oil Add and Gen star=
t manually","vanel.mbiada@matech-cameroun.com","3072","15-06-2025 20:16:29"=
,"MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005264653","Eto=
ug ebe Carrefour","","15-06-2025 20:05:57","15-06-2025 19:58:45","15-06-202=
5 20:16:35","Grid outage, site went down because gen start and stopped with=
 alarm ""high temp"" // he added water and manually start the Gen	","Hyemaf=
o Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Grid outage, site went down because gen start and s=
topped with alarm ""high temp"" // he added water and manually start the Ge=
n	","gerard.tchangoue@matech-cameroun.com","433","15-06-2025 20:05:57","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005264635","E=
foulan","","15-06-2025 20:03:53","15-06-2025 19:42:41","15-06-2025 23:27:00=
","Active: no power issue, site is on Grid with Ubaie=3D55V.Site impacted b=
y Efoulan Pont which is not managed by IHS","MINKA NICOLAS","Customer Equip=
ment Failure","Active","Active Equipment Failure","Affected by 3rd Party Si=
te","Active: no power issue, site is on Grid with Ubaie=3D55V.Site impacted=
 by Efoulan Pont which is not managed by IHS","vanel.mbiada@matech-cameroun=
.com","1272","15-06-2025 20:03:53","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005264585","Nko=
mo","IHS_YND_174","15-06-2025 19:57:21","15-06-2025 19:52:10","16-06-2025 0=
8:54:54","Site went down due to Power Cabinet overloaded ( PWC of 12 k and =
iload of 200A)//Grid return","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Site went down due to Power Ca=
binet overloaded ( PWC of 12 k and iload of 200A)//Grid return","gerard.tch=
angoue@matech-cameroun.com","311","15-06-2025 19:57:21","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005264537","N=
gousso-Savana","IHS_YND_561","15-06-2025 19:54:01","15-06-2025 19:47:44","1=
5-06-2025 20:33:21","Grid Outage, site went down before Gen start due to Po=
or battery backup (Grid return but we have disjunction in the BTS OCM ) // =
Grid return and Disjunctor rearmed","Siligap Boris","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid Outage, site went=
 down before Gen start due to Poor battery backup (Grid return but we have =
disjunction in the BTS OCM ) // Grid return and Disjunctor rearmed","vanel.=
mbiada@matech-cameroun.com","377","15-06-2025 19:54:01","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005264531","F=
OUGEROLE","","15-06-2025 19:53:16","15-06-2025 19:47:44","15-06-2025 20:33:=
21","fme boris is in formed ETA 09:00 PM","Siligap Boris","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid Outage, site went down =
before Gen start due to Poor battery backup (Grid return but we have disjun=
ction in the BTS OCM ) // Grid return and Disjunctor rearmed","vanel.mbiada=
@matech-cameroun.com","771389","15-06-2025 19:53:16","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0005264500","Bar=
riere IHS","","15-06-2025 19:48:15","15-06-2025 19:40:09","17-06-2025 11:07=
:09","Grid outage, Site went Down due to Gen overload(15Kva, 200A) SS IHS F=
ELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went Down due to =
Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return","g=
erard.tchangoue@matech-cameroun.com","487","15-06-2025 19:48:15","MATECH CM=
R"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005264462","N=
KOLMEKONG YDE","","15-06-2025 19:39:56","15-06-2025 19:36:40","15-06-2025 1=
9:40:38","Grid outage, Site went down before Gen start due to poor backup/ =
// Gen automatically started","Fabrice Pouakam","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup/ // Gen automatically started","vanel=
.mbiada@matech-cameroun.com","197","15-06-2025 19:39:56","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005264391","M=
eyo","","15-06-2025 19:29:22","15-06-2025 19:26:14","15-06-2025 21:06:26","=
Grid outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix =
Zambe is informed and confirmed // Grid return","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went dow=
n due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and conf=
irmed // Grid return","vanel.mbiada@matech-cameroun.com","189","15-06-2025 =
19:29:22","MATECH CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0005264382","CRH=
-Etoug-Ebe","","15-06-2025 19:26:16","15-06-2025 19:25:48","15-06-2025 20:3=
6:43","Grid outage, Gen stopped due High temp impacted by Low level of wate=
r in the radiator // Water add and Gen start manually","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, Gen stop=
ped due Low level of water in the radiator // Water add and Gen start manua=
lly","gerard.tchangoue@matech-cameroun.com","29","15-06-2025 19:26:16","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005264314","C=
omplexe-BEAC","","15-06-2025 19:20:08","15-06-2025 19:14:57","15-06-2025 20=
:39:23","Site went down due to Circuit breaker (100A) of battery disjuncted=
 //We rearmed CB ","Albran Byorel","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Circuit Breaker Issue","Site went down due to Circuit=
 breaker (100A) of battery disjuncted //We rearmed CB ","vanel.mbiada@matec=
h-cameroun.com","312","15-06-2025 19:20:08","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005264277","Ebo=
go","","15-06-2025 19:11:22","15-06-2025 19:05:11","15-06-2025 19:25:01","N=
o power issue on site U=3D49,7v site on batterie Synphorien 675295205 of Hu=
awei is informed","Siligap Boris","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D49=
,7v site on batterie Synphorien 675295205 of Huawei is informed","gerard.tc=
hangoue@matech-cameroun.com","372","15-06-2025 19:11:22","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005264255","Ron=
d Point Express1114","","15-06-2025 19:08:08","15-06-2025 18:58:58","15-06-=
2025 19:15:17","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen start automatically","gerard=
.tchangoue@matech-cameroun.com","550","15-06-2025 19:08:08","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005264213","D=
amas","","15-06-2025 19:02:55","15-06-2025 18:59:43","15-06-2025 19:39:28",=
"Site went down due to CB(125A) in PWC that tripped ocm Bay //He rearmed it=
","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Circuit Breaker Issue","Site went down due to CB(125A) in PWC that tri=
pped ocm Bay //He rearmed it","vanel.mbiada@matech-cameroun.com","193","15-=
06-2025 19:02:55","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005264195","S=
imbock OCM","","15-06-2025 18:58:05","15-06-2025 18:54:55","15-06-2025 19:1=
2:01","Active//No power issue on site, Site on Grid UBAIE=3D54.5V The RM Ma=
rtial (650252214) from Huawei is informed. ","Hyemafo Gildas","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site, Site on Grid UBAIE=3D54.5V The RM Martial (6=
50252214) from Huawei is informed. ","vanel.mbiada@matech-cameroun.com","19=
1","15-06-2025 18:58:05","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005264191","Par=
adis Hotel","","15-06-2025 18:57:44","15-06-2025 18:47:59","15-06-2025 20:4=
7:53","Site went down due to MPR DYSFONNCTION on site / He reset the MPR","=
Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Cabinet"=
,"Site went down due to MPR DYSFONNCTION on site / He reset the MPR","gerar=
d.tchangoue@matech-cameroun.com","586","15-06-2025 18:57:44","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005264178","Nko=
lbong","","15-06-2025 18:54:07","15-06-2025 18:47:49","15-06-2025 20:29:31"=
,"Grid outage,Site went Down because Gen started and stopped due to Gen ove=
rload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A) // Grid return","gerar=
d.tchangoue@matech-cameroun.com","379","15-06-2025 18:54:07","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0005264161","Clu=
b France","","15-06-2025 18:51:31","15-06-2025 18:44:26","15-06-2025 19:00:=
09","grid outage,no space to deploy a mobil gen // grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no =
space to deploy a mobil gen // grid return","gerard.tchangoue@matech-camero=
un.com","426","15-06-2025 18:51:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005264154","Messassi=
 okolo","","15-06-2025 18:50:24","15-06-2025 18:48:20","15-06-2025 20:27:05=
","Cascaded Incident from TTO5423126","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issues due to landlord(=
Landlord has forbidden to start the Gen due to noise //  grid return","syst=
em","767744","15-06-2025 18:50:24","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005264145","E=
MANA BILICK CITY","IHS_YND_279","15-06-2025 18:49:34","15-06-2025 18:48:20"=
,"15-06-2025 20:33:09","Access issues due to landlord(Landlord has forbidde=
n to start the Gen due to noise //  grid return","Fabrice Pouakam","Access =
Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lor=
d","Access issues due to landlord(Landlord has forbidden to start the Gen d=
ue to noise //  grid return","vanel.mbiada@matech-cameroun.com","76","15-06=
-2025 18:49:34","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005264124","C=
-Supreme","","15-06-2025 18:47:24","15-06-2025 18:44:16","15-06-2025 18:47:=
40","Site went down due to 02/04 rectifiers dysfunctionning on site//Site s=
tabilised","","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down due to 02/04 rectifiers dysfunctionning on site//Site stabil=
ised","vanel.mbiada@matech-cameroun.com","189","15-06-2025 18:47:24","MATEC=
H CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005264121","Ngo=
usso Vallee","","15-06-2025 18:47:00","15-06-2025 18:44:22","15-06-2025 18:=
48:38","Site went down because insufficient of rectifier on site //site sta=
bilized","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down because insufficient of rectifier on site //site =
stabilized","gerard.tchangoue@matech-cameroun.com","158","15-06-2025 18:47:=
00","MATECH CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0005264102","M=
ontee-Jouvence","","15-06-2025 18:43:09","15-06-2025 18:35:04","15-06-2025 =
18:44:57","Grid bad voltage, site went down because Gen failed to start due=
 to Grid bad voltage // Grid stabilized","Hyemafo Gildas","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid bad voltage, =
site went down because Gen failed to start due to Grid bad voltage // Grid =
stabilized","vanel.mbiada@matech-cameroun.com","486","15-06-2025 18:43:09",=
"MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005264069","Eto=
ug ebe biscuiterie","","15-06-2025 18:38:52","15-06-2025 18:36:43","15-06-2=
025 20:30:42","Grid outage, site went down because gen failed to start with=
 alarm overvoltage // He reset gen card and gen manually started","Hyemafo =
Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Grid=
 outage, site went down because gen failed to start with alarm overvoltage =
// He reset gen card and gen manually started","gerard.tchangoue@matech-cam=
eroun.com","129","15-06-2025 18:38:52","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0005264042","M=
fou EPC","","15-06-2025 18:34:21","15-06-2025 18:28:05","15-06-2025 18:31:3=
2","Active//No power issue on site, Site on Grid UBAIE=3D54.5V The RM Marti=
al (650252214) from Huawei is informed.","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue on site, Site on Grid UBAIE=3D54.5V The RM Martial (650=
252214) from Huawei is informed.","vanel.mbiada@matech-cameroun.com","378",=
"15-06-2025 18:34:21","MATECH CMR"
"Closed Complete","Site Down","T3446","IHS_YND_712","NOCINC0005264031","Nko=
lkoumou OCM","","15-06-2025 18:31:07","15-06-2025 18:29:00","15-06-2025 18:=
31:33","No power issue on site ,site on Grid with Ubaie=3D54,5 V he Tx FME =
Mouahamadou (691144435) of Huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue on site ,site on Grid with Ubaie=3D54,5 V he Tx F=
ME Mouahamadou (691144435) of Huawei is informed","gerard.tchangoue@matech-=
cameroun.com","128","15-06-2025 18:31:07","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005264030","C=
omplexe-BEAC","","15-06-2025 18:30:23","15-06-2025 18:26:11","15-06-2025 18=
:30:15","Site went down due to Circuit breaker (100A) of battery disjuncted=
 //We rearmed CB","Albran Byorel","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","Site went down due to Circuit =
breaker (100A) of battery disjuncted //We rearmed CB","vanel.mbiada@matech-=
cameroun.com","254","15-06-2025 18:30:23","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005264028","M=
anguier","IHS_YND_506, IHS_YND_509","15-06-2025 18:29:38","15-06-2025 18:24=
:30","15-06-2025 19:12:54","Grid outage, site went down before gen start du=
e to poor battery backup // Gen  Start Automatically","Fabrice Pouakam","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","	G=
rid outage, site went down before gen start due to poor battery backup // G=
en  Start Automatically","vanel.mbiada@matech-cameroun.com","309","15-06-20=
25 18:29:38","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005264024","O=
mnisport-Rail","","15-06-2025 18:28:46","15-06-2025 18:24:30","15-06-2025 1=
9:12:54","fme delors will manage after manguier","Delor Telezing","Cascade =
Outage","Passive","Cascade Passive","Cascade Passive","	Grid outage, site w=
ent down before gen start due to poor battery backup // Gen Manually Starte=
d","vanel.mbiada@matech-cameroun.com","769149","15-06-2025 18:28:46","MATEC=
H CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005264022","OBA=
M NGOLA OCM","","15-06-2025 18:28:41","15-06-2025 18:19:36","15-06-2025 21:=
09:23","Grid Outage, Gen Failed to start due to Gen Card Faulty// Grid retu=
rn","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","Grid Outage, Gen Failed to start due to Gen Card Faulty// Grid ret=
urn","gerard.tchangoue@matech-cameroun.com","546","15-06-2025 18:28:41","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005264016","N=
kolfon Cimencam","","15-06-2025 18:27:39","15-06-2025 18:24:21","15-06-2025=
 18:40:34","No power issue on site U=3D54,5v site on Gen FME Fulbert (65426=
6068) of huawei is informed.","Hyemafo Gildas","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D54,5v site on Gen FME Fulbert (654266068) of huawei is informed.=
","vanel.mbiada@matech-cameroun.com","199","15-06-2025 18:27:39","MATECH CM=
R"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005263990","M=
ANGUIERS CHAPELLE","","15-06-2025 18:26:49","15-06-2025 18:24:30","15-06-20=
25 19:12:54","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","	Grid outage, site went down before gen start due to=
 poor battery backup // Gen Manually Started","vanel.mbiada@matech-cameroun=
.com","769149","15-06-2025 18:26:49","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005263939","Nko=
mo","","15-06-2025 18:14:23","15-06-2025 18:07:15","15-06-2025 18:26:01","S=
ite went down due to Power Cabinet overloaded ( PWC of 12 k and iload of 20=
0A)//Grid return","Mba Lazare Herve","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to Power Cabinet overl=
oaded ( PWC of 12 k and iload of 200A)//Grid return","gerard.tchangoue@mate=
ch-cameroun.com","429","15-06-2025 18:14:23","MATECH CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0005263882","Bye=
massi Carrefour","","15-06-2025 18:11:53","15-06-2025 18:05:45","15-06-2025=
 19:01:34","Grid outage.gen started and stopped due to low oil pressure//We=
 add oil and gen manually started","Paul BIBOUM","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Low Oil Pressure","Grid outage.gen started and stoppe=
d due to low oil pressure//We add oil and gen manually started","gerard.tch=
angoue@matech-cameroun.com","369","15-06-2025 18:11:53","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005263797","Beh=
ind P T school Yde","","15-06-2025 18:00:40","15-06-2025 17:54:32","15-06-2=
025 19:36:47","Grid Outage, Site went down because The rectifiers are not p=
owered due to malfunctioning of MPR on site // Grid restoration","Paul BIBO=
UM","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid Outage, Site went down because The rectifiers are not powered due to =
malfunctioning of MPR on site // Grid restoration","gerard.tchangoue@matech=
-cameroun.com","368","15-06-2025 18:00:40","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005263778","M=
elen Ba'aba","","15-06-2025 17:56:37","15-06-2025 17:51:29","15-06-2025 18:=
27:18","Grid outage, site went down because gen ran until fuel shortage//Re=
fueling done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran until fuel shortage//Refue=
ling done","vanel.mbiada@matech-cameroun.com","309","15-06-2025 17:56:37","=
MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005263777","Cit=
e des nations","","15-06-2025 17:56:29","15-06-2025 17:51:24","15-06-2025 1=
7:57:38","Grid outage,site went down before Gen started due to Poor battery=
 backup//Gen automatically started","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage,site went do=
wn before Gen started due to Poor battery backup//Gen automatically started=
","gerard.tchangoue@matech-cameroun.com","306","15-06-2025 17:56:29","MATEC=
H CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005263730","Ron=
d Point Express1114","","15-06-2025 17:48:34","15-06-2025 17:40:28","15-06-=
2025 17:48:47","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen start automatically","gerard=
.tchangoue@matech-cameroun.com","486","15-06-2025 17:48:34","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0005263721","Tam=
tam Weekend","","15-06-2025 17:45:04","15-06-2025 17:40:06","15-06-2025 18:=
30:40","Grid Outage Site went down because Gen Overload (20KVA, 300A) // Gr=
id returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid Outage Site went down because Gen Overload (20KVA, 300A)=
 // Grid returned","gerard.tchangoue@matech-cameroun.com","298","15-06-2025=
 17:45:04","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005263663","Eto=
ug ebe Carrefour","","15-06-2025 17:32:48","15-06-2025 17:31:43","15-06-202=
5 19:49:52","Grid outage, site went down because gen start and stopped with=
 alarm ""high temp"" // he added water and manually start the Gen","Hyemafo=
 Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp -=
 Coolant Level Issue","Grid outage, site went down because gen start and st=
opped with alarm ""high temp"" // he added water and manually start the Gen=
","gerard.tchangoue@matech-cameroun.com","66","15-06-2025 17:32:48","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005263628","M=
ontee-Des-Soeurs","","15-06-2025 17:30:19","15-06-2025 17:25:05","15-06-202=
5 17:32:25","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","vanel.mbiada@matech-cameroun.com","315","15-06-2025 17:30:19",=
"MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005263573","Mvo=
g Betsi Hospital","","15-06-2025 17:21:18","15-06-2025 17:20:11","15-06-202=
5 17:26:11","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.=
com","67","15-06-2025 17:21:18","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005263521","OBA=
M NGOLA OCM","","15-06-2025 17:16:03","15-06-2025 17:06:51","15-06-2025 17:=
10:29","Grid Outage, Gen Failed to start due to Gen Card Faulty// Grid retu=
rn","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","Grid Outage, Gen Failed to start due to Gen Card Faulty// Grid ret=
urn","gerard.tchangoue@matech-cameroun.com","553","15-06-2025 17:16:03","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005263494","S=
imbock OCM","","15-06-2025 17:11:28","15-06-2025 17:09:20","15-06-2025 17:1=
7:45","Active // No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah M=
bah (674007438) of Huawei is informed","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah Mbah (674007438=
) of Huawei is informed","vanel.mbiada@matech-cameroun.com","128","15-06-20=
25 17:11:28","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005263483","M=
ontee-Des-Soeurs","","15-06-2025 17:10:14","15-06-2025 17:07:36","15-06-202=
5 17:14:14","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","vanel.mbiada@matech-cameroun.com","160","15-06-2025 17:10:14",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0005263470","Leboudi"=
,"","15-06-2025 17:08:23","15-06-2025 17:02:33","15-06-2025 17:21:03","Casc=
aded Incident from TTO5422364","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","Active//No power issue, Site on=
 Grid Ubai=3D 55,9V The TX Mouhamadou (6144435) from Huawei is informed.","=
system","1212161","15-06-2025 17:08:23","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0005263456","N=
kolafeme","IHS_YND_309","15-06-2025 17:05:44","15-06-2025 17:02:33","15-06-=
2025 17:21:03","Active//No power issue, Site on Grid Ubai=3D 55,9V The TX M=
ouhamadou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Grid Ubai=3D 55,9V The TX Mouhama=
dou (6144435) from Huawei is informed.","vanel.mbiada@matech-cameroun.com",=
"192","15-06-2025 17:05:44","MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0005263423","Dag=
obert","","15-06-2025 17:00:47","15-06-2025 16:55:40","15-06-2025 17:08:51"=
,"Active: No power issue, site is on Grid with Ubaie=3D54,7V, mohamadou//69=
1144435 from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue, site is on Grid with Ubaie=3D54,7V, mohamadou//691144=
435 from Huawei is informed.","gerard.tchangoue@matech-cameroun.com","308",=
"15-06-2025 17:00:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0005263413","Mbankolo=
 petit paris","","15-06-2025 16:58:06","15-06-2025 16:53:12","15-06-2025 16=
:55:12","Cascaded Incident from TTO5422296","Mboua Thierry","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue on site ,site =
on Gen with Ubaie=3D 54,6 V THE fme Tx Mouamadou /691 144 435/ Huawei is in=
formed","system","760306","15-06-2025 16:58:06","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0005263392","AFE=
ME NORD","IHS_YND_808","15-06-2025 16:55:21","15-06-2025 16:53:12","15-06-2=
025 16:55:12","No power issue on site ,site on Gen with Ubaie=3D 54,6 V THE=
 fme Tx Mouamadou /691 144 435/ Huawei is informed","TIENTCHEU NZETCHIEU GA=
EL","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site ,site on Gen with Ubaie=3D 54,6 V TH=
E fme Tx Mouamadou /691 144 435/ Huawei is informed","gerard.tchangoue@mate=
ch-cameroun.com","130","15-06-2025 16:55:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005263364","Carrefou=
rt Nkomo","","15-06-2025 16:50:10","15-06-2025 16:47:42","15-06-2025 17:53:=
55","Cascaded Incident from TTO5422258","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to Power=
 Cabinet overloaded ( PWC of 12 k and iload of 200A)//He reduiced the Iload=
.","system","760628","15-06-2025 16:50:10","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005263356","N=
komo","IHS_YND_174","15-06-2025 16:48:56","15-06-2025 16:47:42","15-06-2025=
 17:53:55","Site went down due to Power Cabinet overloaded ( PWC of 12 k an=
d iload of 200A)//He reduiced the Iload.","Mba Lazare Herve","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Site went down du=
e to Power Cabinet overloaded ( PWC of 12 k and iload of 200A)//He reduiced=
 the Iload.","vanel.mbiada@matech-cameroun.com","75","15-06-2025 16:48:56",=
"MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005263217","Ron=
d Point Express1114","","15-06-2025 16:22:18","15-06-2025 16:20:13","15-06-=
2025 16:41:18","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen start automatically","gerard=
.tchangoue@matech-cameroun.com","126","15-06-2025 16:22:18","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005263101","NKO=
MKANA ELIZA HOTEL","","15-06-2025 16:01:03","15-06-2025 15:58:32","15-06-20=
25 16:00:39","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","151","15-06-2025 16:01:03","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005262964","Nom=
ayos montee Meche","","15-06-2025 15:44:27","15-06-2025 15:42:17","15-06-20=
25 15:44:17","Grid outage, site went down before Gen started due to poor ba=
ckup battery // Grid returned","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen started due to poor backup battery // Grid returned","gerard.tcha=
ngoue@matech-cameroun.com","131","15-06-2025 15:44:27","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005262847","O=
LAMA","","15-06-2025 15:28:38","15-06-2025 15:08:26","15-06-2025 15:30:30",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.9V site on Gen The TX FME Henri (699949693) from Huawei is=
 informed.","vanel.mbiada@matech-cameroun.com","1213","15-06-2025 15:28:38"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005262705","Carrefou=
rt Nkomo","","15-06-2025 15:04:33","15-06-2025 14:37:18","15-06-2025 16:34:=
18","Cascaded Incident from TTO5421483","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to Power=
 Cabinet overloaded ( PWC of 12 k and iload of 200A) // Eneo return","syste=
m","754089","15-06-2025 15:04:33","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005262503","Nko=
mo","IHS_YND_174","15-06-2025 14:43:29","15-06-2025 14:37:18","15-06-2025 1=
6:37:18","Site went down due to Power Cabinet overloaded ( PWC of 12 k and =
iload of 200A) // Eneo return","Mba Lazare Herve","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due to Power =
Cabinet overloaded ( PWC of 12 k and iload of 200A) // Eneo return","gerard=
.tchangoue@matech-cameroun.com","372","15-06-2025 14:43:29","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005262493","A=
wae Escalier","","15-06-2025 14:42:07","15-06-2025 14:40:38","15-06-2025 14=
:58:50","Grid outage, site went down because gen failed to start due to gri=
d contactor faulty // He bypassed grid contactor and gen manually started",=
"Albran Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue=
","Grid outage, site went down because gen failed to start due to grid cont=
actor faulty // He bypassed grid contactor and gen manually started","vanel=
.mbiada@matech-cameroun.com","91","15-06-2025 14:42:07","MATECH CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0005262390","E=
seka Town","","15-06-2025 14:29:31","15-06-2025 14:26:54","15-06-2025 14:38=
:20","Active// No power issue, Site on Gen Ubaie:50V, The FME Tx Etienne/69=
5033981 From Huawei is informed","Kemeni Franklin","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No =
power issue, Site on Gen Ubaie:50V, The FME Tx Etienne/695033981 From Huawe=
i is informed","vanel.mbiada@matech-cameroun.com","158","15-06-2025 14:29:3=
1","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005262384","Nom=
ayos montee Meche","","15-06-2025 14:27:09","15-06-2025 14:26:04","15-06-20=
25 14:28:55","Grid outage, site went down before Gen started due to poor ba=
ckup battery // Grid returned","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen started due to poor backup battery // Grid returned","gerard.tcha=
ngoue@matech-cameroun.com","66","15-06-2025 14:27:09","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005262365","Nko=
mo","","15-06-2025 14:22:34","15-06-2025 14:21:18","15-06-2025 14:27:18","S=
ite went down due to Power Cabinet overloaded ( PWC of 12 k and iload of 20=
0A)//Grid return","Mba Lazare Herve","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to Power Cabinet overl=
oaded ( PWC of 12 k and iload of 200A)//Grid return","gerard.tchangoue@mate=
ch-cameroun.com","77","15-06-2025 14:22:34","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005262221","Nko=
abang Alembe","","15-06-2025 14:05:46","15-06-2025 14:04:37","15-06-2025 15=
:20:43","Grid fluctuation,site went down due to rectifiers dysfunction on s=
ite // He reset it","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Grid fluctuation,site went down due to rectifiers =
dysfunction on site // He reset it","cedric.tiani@matech-cameroun.com","70"=
,"15-06-2025 14:05:46","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0005262162","MEH=
ANDAN","","15-06-2025 14:00:55","15-06-2025 13:51:59","15-06-2025 15:55:09"=
,"Grid outage, Gen stopped due to Air intake, // Purge of Gen, and Gen Star=
t manually","Albran Byorel","Fuel Outage (Probable)","Passive","ACDG Gen","=
ACDG - Air Intake","Grid outage, Gen stopped due to Air intake, // Purge of=
 Gen, and Gen Start manually","cedric.tiani@matech-cameroun.com","538","15-=
06-2025 14:00:55","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005262156","Ron=
d Point Express1114","","15-06-2025 13:59:55","15-06-2025 13:53:48","15-06-=
2025 14:07:05","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen start automatically","cedric=
.tiani@matech-cameroun.com","368","15-06-2025 13:59:55","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005261706","M=
anguier","","15-06-2025 13:25:27","15-06-2025 13:24:16","15-06-2025 13:27:4=
1","Grid outage, site went down before gen start due to poor battery backup=
 // Gen Manually Started","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen Manually Started","edwige.=
kapawo@matech-cameroun.com","71","15-06-2025 13:25:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005261445","Nkolondo=
m","","15-06-2025 13:09:53","15-06-2025 13:04:32","15-06-2025 13:07:30","Ca=
scaded Incident from TTO5420167","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down before =
Gen start due to poor backup/ // Gen automatically started","system","75233=
7","15-06-2025 13:09:53","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005261416","N=
KOLMEKONG YDE","IHS_YND_304","15-06-2025 13:08:45","15-06-2025 13:04:32","1=
5-06-2025 13:07:30","Grid outage, Site went down before Gen start due to po=
or backup/ // Gen automatically started","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Si=
te went down before Gen start due to poor backup/ // Gen automatically star=
ted","edwige.kapawo@matech-cameroun.com","254","15-06-2025 13:08:45","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005261000","B=
arriere","","15-06-2025 12:46:13","15-06-2025 12:38:00","15-06-2025 12:49:2=
9","Active// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","edwige.kapawo@matech-cameroun.com","494","15-06-2025 12:46:13"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005260958","A=
wae Ewonkan","","15-06-2025 12:44:58","15-06-2025 12:43:50","15-06-2025 13:=
04:13","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // =
He reduced the load","edwige.kapawo@matech-cameroun.com","69","15-06-2025 1=
2:44:58","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005260372","M=
vog-Manga","","15-06-2025 12:19:28","15-06-2025 12:17:21","15-06-2025 12:22=
:59","Grid ouatage,Site went down due to 01 rectifier HS // He reduced the =
load, site on gen","Albran Byorel","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Grid ouatage,Site went down due to 01 rectifier HS // =
He reduced the load, site on gen","edwige.kapawo@matech-cameroun.com","129"=
,"15-06-2025 12:19:28","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005260003","Acc=
acia New","","15-06-2025 12:05:37","15-06-2025 12:03:27","15-06-2025 13:31:=
26","	Grid outage ,no space to deploy a mobil gen // grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid outage =
,no space to deploy a mobil gen // grid return","cedric.tiani@matech-camero=
un.com","132","15-06-2025 12:05:37","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005259884","NKO=
MKANA ELIZA HOTEL","","15-06-2025 11:41:41","15-06-2025 11:39:23","15-06-20=
25 11:41:56","Site went down due to PWC Overloaded(9Kilo//140A) and SS IHS =
Bernard Atangana confirmed // Site stabilised","","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due to PWC Ov=
erloaded(9Kilo//140A) and SS IHS Bernard Atangana confirmed // Site stabili=
sed","cedric.tiani@matech-cameroun.com","139","15-06-2025 11:41:41","MATECH=
 CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0005259824","Mba=
nkomo CAF","","15-06-2025 11:28:57","15-06-2025 11:26:48","15-06-2025 12:02=
:09","Grid outage.gen ran until fuel shortage//Refueling done","Fanda Brice=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unt=
il fuel shortage//Refueling done","cedric.tiani@matech-cameroun.com","130",=
"15-06-2025 11:28:57","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005259269","M=
endong vallee","","15-06-2025 10:41:01","15-06-2025 10:39:51","15-06-2025 1=
3:52:01"," Grid outage site went down because Gen over load (20KVA; 300A) I=
HS F=E9lix Zamb=E9 is informed and confirmed//He reduced the load and start=
ed the Gen manually ","Fanda Brice","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage site went down because Gen over load (20KVA=
; 300A) IHS F=E9lix Zamb=E9 is informed and confirmed//He reduced the load =
and started the Gen manually ","edwige.kapawo@matech-cameroun.com","71","15=
-06-2025 10:41:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005259191","Mvog-Eba=
nda","","15-06-2025 10:29:16","15-06-2025 10:24:26","15-06-2025 11:33:47","=
Cascaded Incident from TTO5417874","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen failed to start due to Gen Overload (16KVA /220A)  Blaise Raoul confir=
med // He reduced load","system","725984","15-06-2025 10:29:16","MATECH CMR=
"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005259183","NKO=
MKANA ELIZA HOTEL","","15-06-2025 10:28:31","15-06-2025 10:26:21","15-06-20=
25 10:28:42","Site went down due to PWC Overloaded(9Kilo//140A) and SS IHS =
Bernard Atangana confirmed // Site stabilised","","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due to PWC Ov=
erloaded(9Kilo//140A) and SS IHS Bernard Atangana confirmed // Site stabili=
sed","cedric.tiani@matech-cameroun.com","130","15-06-2025 10:28:31","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005259181","A=
bom","IHS_YND_269","15-06-2025 10:27:35","15-06-2025 10:24:26","15-06-2025 =
11:33:47","Grid outage, Site went down because Gen failed to start due to G=
en Overload (16KVA /220A)  Blaise Raoul confirmed // He reduced load","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage, Site went down because Gen failed to start due to Gen Overload (16K=
VA /220A)  Blaise Raoul confirmed // He reduced load","edwige.kapawo@matech=
-cameroun.com","190","15-06-2025 10:27:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005259073","Messassi=
 okolo","","15-06-2025 10:11:31","15-06-2025 10:10:45","15-06-2025 10:26:50=
","Cascaded Incident from TTO5417743","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issues due to landlord(=
Landlord has forbidden to start the Gen due to noise) // grid return","syst=
em","1215373","15-06-2025 10:11:31","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005259071","E=
MANA BILICK CITY","IHS_YND_279","15-06-2025 10:10:55","15-06-2025 10:10:45"=
,"15-06-2025 10:31:15","Access issues due to landlord(Landlord has forbidde=
n to start the Gen due to noise) // grid return","Fabrice Pouakam","Access =
Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lor=
d","Access issues due to landlord(Landlord has forbidden to start the Gen d=
ue to noise) // grid return","edwige.kapawo@matech-cameroun.com","12","15-0=
6-2025 10:10:55","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005259062","N=
kolbong","","15-06-2025 10:10:11","15-06-2025 10:07:55","15-06-2025 10:17:3=
5","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A) // Grid return","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Ge=
n started and stopped due to Gen overload(22kva//350A) // Grid return","edw=
ige.kapawo@matech-cameroun.com","137","15-06-2025 10:10:11","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0005259034","B=
itoto","","15-06-2025 10:06:44","15-06-2025 09:57:59","15-06-2025 11:14:28"=
,"Site went down due to CB(125A) in DC BOX in PWC that feeds ocm due to cha=
rge//He rearmed it","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier - Circuit Breaker","Site went down due to CB(125A) in DC BO=
X in PWC that feeds ocm due to charge//He rearmed it","edwige.kapawo@matech=
-cameroun.com","527","15-06-2025 10:06:44","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005258901","ODZ=
A MINKAN EDIBI ASSI","","15-06-2025 09:48:50","14-06-2025 23:18:26","15-06-=
2025 02:20:03","Backtacking Grid outage,Site went down because Gen failed t=
o start due to Grid contactor not excited//He excited the Grid contactor an=
d site on Grid","Albran Byorel","Equipment Repair","Passive","Control Panel=
","ATS-AMF Issue","Grid outage,Site went down because Gen failed to start d=
ue to Grid contactor not excited//He excited the Grid contactor and site on=
 Grid","cedric.tiani@matech-cameroun.com","37825","15-06-2025 09:48:50","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005258639","Carrefou=
rt Nkomo","","15-06-2025 09:02:33","15-06-2025 09:00:41","15-06-2025 10:47:=
26","Cascaded Incident from TTO5417274","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage site went down =
because Gen failed to start due to Gen Battery Faulty  //He started Gen man=
ualy with external battery","system","723787","15-06-2025 09:02:33","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005258633","N=
komo","IHS_YND_174","15-06-2025 09:01:50","15-06-2025 09:00:41","15-06-2025=
 10:59:28","Grid outage site went down because Gen failed to start due to G=
en Battery Faulty  //He started Gen manualy with external battery","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batter=
y","Grid outage site went down because Gen failed to start due to Gen Batte=
ry Faulty  //He started Gen manualy with external battery","edwige.kapawo@m=
atech-cameroun.com","70","15-06-2025 09:01:50","MATECH CMR"
"Closed Complete","Warning","CTR_337","IHS_YND_280","NOCINC0005258550","Mes=
sassi 2","","15-06-2025 08:52:45","","","site went on Alarming Gen failed t=
o start due PWC ZTE dysfonctionned // He bypassed ATS and started Gen manua=
lly","Fabrice Pouakam","Warning","Warning","POWER","Warning - Rectifier Mod=
ule Overloaded","site went on Alarming Gen failed to start due PWC ZTE dysf=
onctionned // He bypassed ATS and started Gen manually","cedric.tiani@matec=
h-cameroun.com","129","15-06-2025 08:52:45","MATECH CMR"
"Closed Complete","Warning","T1505","IHS_YND_681","NOCINC0005258545","NKOLM=
EKONG YDE","","15-06-2025 08:51:25","","","Grid outage, Site Alarming  befo=
re Gen start due to poor backup/ // Gen automatically started","Fabrice Pou=
akam","Warning","Warning","POWER","Warning - Battery Low Voltage","Grid out=
age, Site Alarming  before Gen start due to poor backup/ // Gen automatical=
ly started","cedric.tiani@matech-cameroun.com","495","15-06-2025 08:51:25",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005258539","N=
omayos montee Meche","","15-06-2025 08:51:00","15-06-2025 08:48:46","15-06-=
2025 08:52:53","Grid outage site went down before Gen started due to poor b=
attery back up // Eneo return","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage site went down be=
fore Gen started due to poor battery back up // Eneo return","edwige.kapawo=
@matech-cameroun.com","135","15-06-2025 08:51:00","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005258360","Ron=
d Point Express1114","","15-06-2025 08:11:21","15-06-2025 08:03:12","15-06-=
2025 08:37:39","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","ce=
dric.tiani@matech-cameroun.com","490","15-06-2025 08:11:21","MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0005258336","M=
beng","IHS_YND_553","15-06-2025 08:04:36","15-06-2025 06:04:19","15-06-2025=
 10:01:12","site went down because gen start an stopped due to water infilt=
ration in tank // He purged The tank and Gen manually started","Fanda Brice=
","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water I=
n The Fuel","site went down because gen start an stopped due to water infil=
tration in tank // He purged The tank and Gen manually started","edwige.kap=
awo@matech-cameroun.com","7219","15-06-2025 08:04:36","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005258277","S=
imbock OCM","","15-06-2025 07:56:01","15-06-2025 07:46:59","15-06-2025 07:4=
7:59","Active // No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah M=
bah (674007438) of Huawei is informed","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue Ubaie:52.5V site on Gen The Tx Fme Hosiah Mbah (674007438=
) of Huawei is informed","edwige.kapawo@matech-cameroun.com","596","15-06-2=
025 07:56:01","MATECH CMR"
"Cancelled","Warning","CTR_385","IHS_YND_369","NOCINC0005258235","Mbeng",""=
,"15-06-2025 07:45:53","","","fme Brice is on the way ETA 08:30 AM","Fanda =
Brice","","","","","","edwige.kapawo@matech-cameroun.com","6081","15-06-202=
5 07:45:53","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005258179","N=
koabang2","","15-06-2025 07:31:41","15-06-2025 07:25:33","15-06-2025 09:18:=
47","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // He  reduced  load, Gen started manually","Mba Lazare =
Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge, site went down due to gen overload (22KVA, 330A), SS Blaise IHS is info=
rmed // He  reduced  load, Gen started manually","edwige.kapawo@matech-came=
roun.com","531","15-06-2025 07:31:41","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005258148","A=
wae Ewonkan","","15-06-2025 07:25:45","15-06-2025 07:22:31","15-06-2025 10:=
43:04","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","edwige.kapawo@matech-cameroun.com","195","15-06-2025 07:25:45","MATEC=
H CMR"
"Closed Complete","Warning","CTR_080","IHS_YND_298","NOCINC0005258074","Ole=
mbe","","15-06-2025 07:09:09","","","Site alarm because 02 rectifiers on si=
te alarming //He reset it and site on Gen","Fabrice Pouakam","Warning","War=
ning","POWER","Warning - Rectifier Module","Site alarm because 02 rectifier=
s on site alarming //He reset it and site on Gen","cedric.tiani@matech-came=
roun.com","2287","15-06-2025 07:09:09","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0005258012","B=
itoto","","15-06-2025 06:51:53","15-06-2025 06:25:40","15-06-2025 09:30:09"=
,"Site went down because disjnuction Cb in DC BOX OCM // He reamed CB, site=
 on grid","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Circuit Breaker Issue","Site went down because disjnuction =
Cb in DC BOX OCM // He reamed CB, site on grid","edwige.kapawo@matech-camer=
oun.com","1574","15-06-2025 06:51:53","MATECH CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0005257994","Bon=
djock","IHS_YND_554","15-06-2025 06:45:30","15-06-2025 06:07:50","15-06-202=
5 07:23:43","Grid outage,Site went down because Gen failed to start due to =
Grid contactor not excited//He excited the Grid contactor and site on Gen",=
"Fanda Brice","Equipment Repair","Passive","Control Panel","ATS-AMF Issue",=
"Grid outage,Site went down because Gen failed to start due to Grid contact=
or not excited//He excited the Grid contactor and site on Gen","cedric.tian=
i@matech-cameroun.com","2261","15-06-2025 06:45:30","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0005257989","M=
bankomo IHS","","15-06-2025 06:42:26","15-06-2025 06:36:17","15-06-2025 07:=
15:19","Site went down due to 02/03 rectifier dysfunction//He reset it","Fa=
nda Brice","Equipment Repair","Passive","Rectifier","Rectifier Module","Sit=
e went down due to 02/03 rectifier dysfunction//He reset it","edwige.kapawo=
@matech-cameroun.com","370","15-06-2025 06:42:26","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005257971","N=
kolfon Cimencam","","15-06-2025 06:39:15","15-06-2025 06:35:05","15-06-2025=
 06:41:49","Site impacted by Afanoya_II ","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","Affected by 3rd Party Sit=
e","Site impacted by Afanoya_II ","edwige.kapawo@matech-cameroun.com","251"=
,"15-06-2025 06:39:15","MATECH CMR"
"Closed Complete","Site Down","T0535","IHS_YND_234","NOCINC0005257560","Oyo=
mabang MTN","","15-06-2025 04:45:38","15-06-2025 03:38:27","15-06-2025 07:0=
4:47","Grid Outage Site went down because Gen Failed to Start due to RCP fa=
ulty // He replace relay by Relay 220V  and manual start of GE","TIENTCHEU =
NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Relay Fault=
y","Grid Outage Site went down because Gen Failed to Start due to RCP fault=
y // He replace relay by Relay 220V  and manual start of GE","gerard.tchang=
oue@matech-cameroun.com","4031","15-06-2025 04:45:38","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005257502","C=
arrefourt Nkomo","","15-06-2025 04:08:42","15-06-2025 04:02:35","15-06-2025=
 04:26:29","Grid outage,Site went down because Gen failed to start due to G=
rid contactor faulty // He bypassed it site on GE","Mba Lazare Herve","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage,Sit=
e went down because Gen failed to start due to Grid contactor faulty // He =
bypassed it site on GE","gaelle.njiofack@matech-cameroun.com","368","15-06-=
2025 04:08:42","MATECH CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0005257440","NKO=
LMEKONG YDE","IHS_YND_304","15-06-2025 03:46:48","15-06-2025 03:16:28","15-=
06-2025 07:43:27","Grid outage site went down because Gen failed to start d=
ue to battery GE faulty //Gen manually started with external battery","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batt=
ery","Grid outage site went down because Gen failed to start due to battery=
 GE faulty //Gen manually started with external battery","gerard.tchangoue@=
matech-cameroun.com","1822","15-06-2025 03:46:48","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005257429","N=
kolondom","","15-06-2025 03:43:25","15-06-2025 03:16:28","15-06-2025 07:40:=
07","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage site went down because Gen failed to start due to=
 battery GE faulty //Gen manually started with external battery","gaelle.nj=
iofack@matech-cameroun.com","722944","15-06-2025 03:43:25","MATECH CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0005257415","B=
IYEMASSI NIKI","","15-06-2025 03:39:02","15-06-2025 03:14:51","15-06-2025 0=
3:16:47","ticket error","Hyemafo Gildas","Incorrectly Logged Tickets","Erro=
r","Error","Error","ticket error","gaelle.njiofack@matech-cameroun.com","14=
52","15-06-2025 03:39:02","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005257396","S=
tade-Abega","","15-06-2025 03:38:20","15-06-2025 03:26:06","15-06-2025 03:5=
5:54","	Site impacted by EKounou_II","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Site i=
mpacted by EKounou_II","gaelle.njiofack@matech-cameroun.com","735","15-06-2=
025 03:38:20","MATECH CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0005257231","NKO=
LMEKONG YDE","","15-06-2025 02:24:32","15-06-2025 02:18:08","15-06-2025 02:=
40:46","Grid outage, Site went down before Gen start due to poor backup// G=
rid power return","Fabrice Pouakam","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup// Grid power return","gerard.tchangoue@matech-cam=
eroun.com","385","15-06-2025 02:24:32","MATECH CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0005257056","F=
ebe Village","","15-06-2025 01:10:14","15-06-2025 01:00:57","15-06-2025 07:=
16:25","Site went down because Gen failed to start due to Grid bad voltage =
and RCP on site // He bypass the Grid and Gen manually Started","Mboua Thie=
rry","Grid Supply","Passive","Grid","National Grid - Grid Incomplete Phase"=
,"Site went down because Gen failed to start due to Grid bad voltage and RC=
P on site // He bypass the Grid and Gen manually Started","gaelle.njiofack@=
matech-cameroun.com","558","15-06-2025 01:10:14","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005256991","Eko=
umdoum OCM","","15-06-2025 00:53:55","15-06-2025 00:46:49","15-06-2025 01:5=
0:07","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // He resert the controller, grid return","Albran Byorel","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage, site went down because gen failed to start due to PWC ZTE malfuncti=
on // He resert the controller, grid return","gerard.tchangoue@matech-camer=
oun.com","427","15-06-2025 00:53:55","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0005256973","MEH=
ANDAN","","15-06-2025 00:47:55","15-06-2025 00:40:43","15-06-2025 02:02:13"=
,"Grid outage, site went down because gen failed to start due to PWC ZTE ma=
lfunction // He resert the controller, grid return","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outag=
e, site went down because gen failed to start due to PWC ZTE malfunction //=
 He resert the controller, grid return","gerard.tchangoue@matech-cameroun.c=
om","433","15-06-2025 00:47:55","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005256953","ODZ=
A BORNE 10","","15-06-2025 00:36:28","15-06-2025 00:26:59","15-06-2025 01:5=
4:20"," Grid outage, Gen failed to star due to presence of water in the fee=
d // Water remove and Gen start Manually.","Albran Byorel","Fuel Outage (Pr=
obable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel"," Grid=
 outage, Gen failed to star due to presence of water in the feed // Water r=
emove and Gen start Manually.","gerard.tchangoue@matech-cameroun.com","570"=
,"15-06-2025 00:36:28","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0005256885","AWA=
E OCM","","15-06-2025 00:23:13","15-06-2025 00:15:04","15-06-2025 03:45:37"=
,"Grid outage site went down because the PWC malfunctions //he reset the PW=
C and manually started","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Grid outage site went down because =
the PWC malfunctions //he reset the PWC and manually started","gerard.tchan=
goue@matech-cameroun.com","490","15-06-2025 00:23:13","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005256794","HOP=
ITAL DE LA CAISSE","","15-06-2025 00:04:41","14-06-2025 23:51:01","14-06-20=
25 23:53:01","Grid outage site went down before Gen started due to poor bat=
tery back up // Gen automatically started","Delor Telezing","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage si=
te went down before Gen started due to poor battery back up // Gen automati=
cally started","gerard.tchangoue@matech-cameroun.com","916","15-06-2025 00:=
04:41","MATECH CMR"
"Closed Complete","Site Down","T0290","IHS_YND_067","NOCINC0005256778","Nko=
a Ayos","","15-06-2025 00:00:58","14-06-2025 23:54:27","15-06-2025 00:06:58=
","Grid outage, Site went down because Gen failed to start due to ATS fault=
y// Grid Restored","MINKA NICOLAS","Equipment Repair","Passive","Control Pa=
nel","ATS-AMF Issue","Grid outage, Site went down because Gen failed to sta=
rt due to ATS faulty// Grid Restored","gerard.tchangoue@matech-cameroun.com=
","391","15-06-2025 00:00:58","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005256755","S=
imbock OCM","","14-06-2025 23:56:28","14-06-2025 21:57:15","14-06-2025 22:1=
2:18","Backtracking// No power issue U=3D52.5V site on Grid The Tx Fme Hosi=
ah Mbah (674007438) of Huawei is informed","Hyemafo Gildas","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue U=3D52.5V site on Grid The Tx Fme Hosiah Mbah (674007438) of Hu=
awei is informed","gaelle.njiofack@matech-cameroun.com","7154","14-06-2025 =
23:56:28","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005256752","S=
atcom","","14-06-2025 23:55:13","14-06-2025 23:49:06","15-06-2025 00:09:08"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","Affected by 3rd P=
arty Site","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The=
 Tx Fme Armand nguetsa(691144412) From huawei is informed.","gaelle.njiofac=
k@matech-cameroun.com","368","14-06-2025 23:55:13","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005256629","B=
arriere IHS","","14-06-2025 23:30:28","14-06-2025 23:20:59","15-06-2025 08:=
05:50"," Grid outage, Site went Down due to Gen overload(15Kva, 200A) SS IH=
S FELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload"," Grid outage, Site went Down due=
 to Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return=
","gaelle.njiofack@matech-cameroun.com","570","14-06-2025 23:30:28","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005256623","A=
wae Ewonkan","","14-06-2025 23:29:42","14-06-2025 23:24:35","15-06-2025 01:=
45:37","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Reducing the load and site is on Gen","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage site went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphons=
e is informed // Reducing the load and site is on Gen","gaelle.njiofack@mat=
ech-cameroun.com","308","14-06-2025 23:29:42","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0005256506","B=
itoto","","14-06-2025 23:02:31","14-06-2025 22:30:20","15-06-2025 00:47:26"=
,"Grid outage, site went down because gen failed to start due to PWC ZTE ma=
lfunction // He reset controller and gen manually started","Mba Lazare Herv=
e","Equipment Repair","Passive","Rectifier","Rectifier Module","Grid outage=
, site went down because gen failed to start due to PWC ZTE malfunction // =
He reset controller and gen manually started","gaelle.njiofack@matech-camer=
oun.com","1932","14-06-2025 23:02:31","MATECH CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0005256495","BEA=
TITUDE ENTR=C9E PAVE","","14-06-2025 22:57:54","14-06-2025 22:49:48","15-06=
-2025 01:48:13","Grid outage.gen failed to start due to card Ge Dysfunction=
ning//We reset card GE and gen manually started","TIENTCHEU NZETCHIEU GAEL"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e.gen failed to start due to card Ge Dysfunctionning//We reset card GE and =
gen manually started","gerard.tchangoue@matech-cameroun.com","487","14-06-2=
025 22:57:54","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0005256484","Eko=
mbitie","","14-06-2025 22:53:32","14-06-2025 22:47:24","15-06-2025 01:45:58=
","Grid fluctuation, Site went down because gen failed to start due to grid=
 bad voltage // He bypassed the Grid and site on Gen","Fabrice Pouakam","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuation, Site went down because gen failed to start due to grid bad vo=
ltage // He bypassed the Grid and site on Gen","gerard.tchangoue@matech-cam=
eroun.com","369","14-06-2025 22:53:32","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005256386","Ebo=
go","","14-06-2025 22:32:57","14-06-2025 22:27:47","15-06-2025 02:37:47","N=
o power issue on site U=3D50,3v site on grid Synphorien 675295205 of Huawei=
 is informed","Siligap Boris","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D50,3v =
site on grid Synphorien 675295205 of Huawei is informed","cedric.tiani@mate=
ch-cameroun.com","311","14-06-2025 22:32:57","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005256317","ODZ=
A MINKAN EDIBI ASSI","","14-06-2025 22:22:29","14-06-2025 22:13:21","14-06-=
2025 23:07:17","site went down because gen start an stopped due to water in=
filtration in tank // He purged The tank and Gen manually started","Albran =
Byorel","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - W=
ater In The Fuel","site went down because gen start an stopped due to water=
 infiltration in tank // He purged The tank and Gen manually started","cedr=
ic.tiani@matech-cameroun.com","549","14-06-2025 22:22:29","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005256260","Mey=
o","","14-06-2025 22:08:02","14-06-2025 21:59:45","15-06-2025 00:11:27","Gr=
id outage, site went down because Gen overload (17kva, 250A) SS IHS Felix Z=
AMBE confirmed// He reduiced load and started Gen manualy","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, si=
te went down because Gen overload (17kva, 250A) SS IHS Felix ZAMBE confirme=
d// He reduiced load and started Gen manualy","ludivine.ngamaleu@ihstowers.=
com","497","14-06-2025 22:08:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0005256257","Bastos-B=
AT","","14-06-2025 22:06:24","14-06-2025 21:59:38","15-06-2025 01:17:16","C=
ascaded Incident from TTO5414587","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","	Site went down due to Grid outage /=
/ He deploy 20KVA","system","273855","14-06-2025 22:06:24","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005256247","ARM=
P Building","IHS_YND_129","14-06-2025 22:05:51","14-06-2025 21:59:38","15-0=
6-2025 01:17:16"," Site went down due to Grid outage // He deploy 20KVA","M=
boua Thierry","Grid Supply","Passive","Grid","National Grid - Grid Outage I=
ssue","	Site went down due to Grid outage // He deploy 20KVA","cedric.tiani=
@matech-cameroun.com","373","14-06-2025 22:05:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005256228","Minka","=
","14-06-2025 22:03:43","14-06-2025 21:56:19","14-06-2025 22:00:30","Cascad=
ed Incident from TTO5414534","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No powwer issue on site Ubaie=3D53.7 V=
 site on Gen. site impacted by Ngoumou which is not managing by IHS","syste=
m","266960","14-06-2025 22:03:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005256227","OTELE MT=
N","","14-06-2025 22:03:43","14-06-2025 21:56:19","14-06-2025 22:00:30","Ca=
scaded Incident from TTO5414534","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No powwer issue on site Ubaie=3D53=
.7 V site on Gen. site impacted by Ngoumou which is not managing by IHS","s=
ystem","266959","14-06-2025 22:03:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005256229","Mom","",=
"14-06-2025 22:03:43","14-06-2025 21:56:19","14-06-2025 22:00:30","Cascaded=
 Incident from TTO5414534","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Active//No powwer issue on site Ubaie=3D53.7 V s=
ite on Gen. site impacted by Ngoumou which is not managing by IHS","system"=
,"266960","14-06-2025 22:03:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005256226","OLAMA","=
","14-06-2025 22:03:42","14-06-2025 21:56:19","14-06-2025 22:00:30","Cascad=
ed Incident from TTO5414534","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No powwer issue on site Ubaie=3D53.7 V=
 site on Gen. site impacted by Ngoumou which is not managing by IHS","syste=
m","266959","14-06-2025 22:03:42","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005256195","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","14-06-2025 22:02:=
37","14-06-2025 21:56:19","14-06-2025 22:00:30","Active//No powwer issue on=
 site Ubaie=3D53.7 V site on Gen. site impacted by Ngoumou which is not man=
aging by IHS","Fanda Brice","Customer Equipment Failure","Active","Active E=
quipment Failure","Affected by 3rd Party Site","Active//No powwer issue on =
site Ubaie=3D53.7 V site on Gen. site impacted by Ngoumou which is not mana=
ging by IHS","cedric.tiani@matech-cameroun.com","379","14-06-2025 22:02:37"=
,"MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005256183","Nko=
lbisson IITA LP","","14-06-2025 22:01:08","14-06-2025 21:53:24","15-06-2025=
 08:57:34","Access issues during the weekend due to Lanlord (Grid Only, No =
space to deploy awaiting  Grid restored)// Grid return","","Access Denial",=
"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Acce=
ss issues during the weekend due to Lanlord (Grid Only, No space to deploy =
awaiting  Grid restored)// Grid return","cedric.tiani@matech-cameroun.com",=
"465","14-06-2025 22:01:08","MATECH CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0005256132","E=
seka Town","","14-06-2025 21:54:34","14-06-2025 21:41:22","14-06-2025 21:57=
:12","Active// No power issue, Site on Gen Ubaie:53V, The FME Tx Etienne/69=
5033981 From Huawei is informed","Kemeni Franklin","Customer Equipment Fail=
ure","Active","Active Equipment Failure","Affected by 3rd Party Site","Acti=
ve// No power issue, Site on Gen Ubaie:53V, The FME Tx Etienne/695033981 Fr=
om Huawei is informed","vanel.mbiada@matech-cameroun.com","793","14-06-2025=
 21:54:34","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005256045","Mey=
o","","14-06-2025 21:39:47","14-06-2025 21:38:35","14-06-2025 21:46:54","	G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed automatically ","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","	Grid outage, Site went down before Ge=
n start due to poor backup // Gen started automatically ","cedric.tiani@mat=
ech-cameroun.com","72","14-06-2025 21:39:47","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005256040","C=
omplexe-BEAC","","14-06-2025 21:38:59","14-06-2025 21:34:49","14-06-2025 21=
:43:00","Grid Outage site went down because Gen start but did not feeding t=
he site due to CB(100A) of Battery Disjuncted // he Reamed it and site on G=
en.","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Ba=
ttery","Grid Outage site went down because Gen start but did not feeding th=
e site due to CB(100A) of Battery Disjuncted // he Reamed it and site on Ge=
n.","vanel.mbiada@matech-cameroun.com","251","14-06-2025 21:38:59","MATECH =
CMR"
"Closed Complete","Site Down","T1549","IHS_YND_295","NOCINC0005256037","NGO=
NA","","14-06-2025 21:38:42","14-06-2025 21:34:31","14-06-2025 21:38:59","G=
rid outage,site went down because Gen failed to start due to battery GE fau=
lty //Grid return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Generator Battery","Grid outage,site went down because Gen faile=
d to start due to battery GE faulty //Grid return","cedric.tiani@matech-cam=
eroun.com","252","14-06-2025 21:38:42","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005256035","F=
ouda-New","","14-06-2025 21:38:22","14-06-2025 21:33:00","14-06-2025 23:30:=
57","Site went down due to disjunction of CB in the PWC // CB rearm","Delor=
 Telezing","Equipment Repair","Passive","Control Panel","Power Cabinet - Ci=
rcuit Breaker Issue","Site went down due to disjunction of CB in the PWC //=
 CB rearm","vanel.mbiada@matech-cameroun.com","323","14-06-2025 21:38:22","=
MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005256011","Nko=
abang2","","14-06-2025 21:35:52","14-06-2025 21:25:59","14-06-2025 21:38:57=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ludi=
vine.ngamaleu@ihstowers.com","594","14-06-2025 21:35:52","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005256003","S=
tade-Abega","","14-06-2025 21:34:35","14-06-2025 21:18:17","14-06-2025 21:3=
0:40","Active // No pwer issus, site is on grid with Ubaie=3D53.4V, Lionel =
adjep(655184876) from Huawei is on site.Impacted by EKOUNOU II","Mba Lazare=
 Herve","Customer Equipment Failure","Active","Active Equipment Failure","A=
ffected by 3rd Party Site","Active // No pwer issus, site is on grid with U=
baie=3D53.4V, Lionel adjep(655184876) from Huawei is on site.Impacted by EK=
OUNOU II","vanel.mbiada@matech-cameroun.com","979","14-06-2025 21:34:35","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005255915","E=
vodoula OCM","","14-06-2025 21:15:26","14-06-2025 21:13:17","14-06-2025 21:=
14:50","Grid outage,gen failed to start due to grid bad voltage,no rcp//he =
bypassed the Grid and site on Gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid outage,ge=
n failed to start due to grid bad voltage,no rcp//he bypassed the Grid and =
site on Gen","vanel.mbiada@matech-cameroun.com","130","14-06-2025 21:15:26"=
,"MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005255901","Mvo=
g Betsi Hospital","","14-06-2025 21:14:21","14-06-2025 21:07:11","14-06-202=
5 21:13:35","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","cedric.tiani@matech-cameroun.com"=
,"431","14-06-2025 21:14:21","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005255863","M=
elen Ba'aba","","14-06-2025 21:08:33","14-06-2025 20:56:20","14-06-2025 20:=
56:21","Site impacted by Nkolfoulou","Siligap Boris","Incorrectly Logged Ti=
ckets","Error","Error","Error","Error TT","vanel.mbiada@matech-cameroun.com=
","734","14-06-2025 21:08:33","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005255848","B=
arriere","","14-06-2025 21:04:35","14-06-2025 20:45:22","14-06-2025 21:00:2=
8","Active// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","vanel.mbiada@matech-cameroun.com","1155","14-06-2025 21:04:35"=
,"MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005255792","Mes=
sassi 2","","14-06-2025 20:56:40","14-06-2025 20:49:26","14-06-2025 21:02:1=
9","Grid outage, Gen failed to start due to Bay ZTE malfunction // Gen star=
t manually","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Grid outage, Gen failed to start due to Bay ZTE =
malfunction // Gen start manually","ludivine.ngamaleu@ihstowers.com","435",=
"14-06-2025 20:56:40","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005255790","M=
anguier","IHS_YND_509","14-06-2025 20:55:42","14-06-2025 20:32:34","15-06-2=
025 02:07:52","	Grid outage, Site went down due to Gen overload (17KVA ; 16=
0A) //He reduce load and site on Gen","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","	Grid outage, Site went down due to=
 Gen overload (17KVA ; 160A) //He reduce load and site on Gen","olivier.kwe=
di@ihstowers.com","1388","14-06-2025 20:55:42","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0005255789","Imm=
-Olympique","","14-06-2025 20:55:38","14-06-2025 20:50:22","14-06-2025 21:2=
8:22","Grid outage,site went down because Gen failed to start due to Gen ov=
erload(20KVA//295A) SS HIS Raoul is informed//Grid returned","Paul BIBOUM",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,site=
 went down because Gen failed to start due to Gen overload(20KVA//295A) SS =
HIS Raoul is informed//Grid returned","cedric.tiani@matech-cameroun.com","3=
17","14-06-2025 20:55:38","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005255786","TSI=
NGA VILLAGE 2","","14-06-2025 20:54:33","14-06-2025 20:50:21","14-06-2025 2=
3:45:44","Site went down because gen stopped due to water ingress into the =
tank // water remove, fuel add and gen start manually.","Delor Telezing","F=
uel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In Th=
e Fuel","Site went down because gen stopped due to water ingress into the t=
ank // water remove, fuel add and gen start manually.","cedric.tiani@matech=
-cameroun.com","253","14-06-2025 20:54:33","MATECH CMR"
"Closed Complete","Site Down","T1652","IHS_YND_273","NOCINC0005255761","Nko=
lbi-Boss","","14-06-2025 20:52:20","14-06-2025 20:49:08","14-06-2025 21:53:=
11","Grid outage, site went down before gen start due to poor battery backu=
p // gen start manually","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // gen start manually","c=
edric.tiani@matech-cameroun.com","193","14-06-2025 20:52:20","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005255718","S=
ous Prefecture","","14-06-2025 20:44:27","14-06-2025 20:37:15","14-06-2025 =
20:50:24","ACTIVE//No power issue site on Grid Ubaie =3D50 V, The tx Huawei=
 Fulbert (654266068) is informed","Fanda Brice","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No powe=
r issue site on Grid Ubaie =3D50 V, The tx Huawei Fulbert (654266068) is in=
formed","vanel.mbiada@matech-cameroun.com","433","14-06-2025 20:44:27","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_063","IHS_YND_365","NOCINC0005255708","A=
kono","","14-06-2025 20:43:05","14-06-2025 20:36:53","14-06-2025 21:55:39",=
"No power issue site on grid with U=3D54v Site is impacted by Ngoumou who i=
s not our responsability.Henri (699949693) from Huawei is informed.","Fanda=
 Brice","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue site on grid with U=3D54v Site is impact=
ed by Ngoumou who is not our responsability.Henri (699949693) from Huawei i=
s informed.","vanel.mbiada@matech-cameroun.com","373","14-06-2025 20:43:05"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005255678","O=
mnisport-Rail","","14-06-2025 20:39:50","14-06-2025 20:21:29","14-06-2025 2=
2:22:28","","Delor Telezing","Cascade Outage","Active","Cascade Active","Ca=
scade Active","No power issue, site is on grid with Ubaie: 54.4V, Symphorie=
n(650257151) from Huawei is informed","vanel.mbiada@matech-cameroun.com","2=
72595","14-06-2025 20:39:50","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005255673","Nom=
ayos montee Meche","","14-06-2025 20:39:04","14-06-2025 20:31:43","14-06-20=
25 20:38:11","	Grid outage site went down before Gen started due to poor ba=
ttery back up // Eneo return","Fanda Brice","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","	Grid outage site went down be=
fore Gen started due to poor battery back up // Eneo return","cedric.tiani@=
matech-cameroun.com","442","14-06-2025 20:39:04","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005255670","M=
ANGUIERS CHAPELLE","","14-06-2025 20:38:53","14-06-2025 20:32:34","15-06-20=
25 02:07:52","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","	Grid outage, Site went down due to Gen overload (17=
KVA ; 160A) //He reduce load and site on Gen","vanel.mbiada@matech-cameroun=
.com","739976","14-06-2025 20:38:53","MATECH CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0005255643","Mba=
nkomo CAF","","14-06-2025 20:37:17","14-06-2025 20:35:59","14-06-2025 20:37=
:17","	No power issue site on Gen with U=3D53v Flubert(654266068) from Huaw=
ei is informed","Fanda Brice","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","	No power issue site on Gen with =
U=3D53v Flubert(654266068) from Huawei is informed","cedric.tiani@matech-ca=
meroun.com","79","14-06-2025 20:37:17","MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0005255635","Dag=
obert","","14-06-2025 20:36:21","14-06-2025 20:35:12","14-06-2025 20:39:19"=
,"Active: No power issue, site is on Grid with Ubaie=3D54,7V, mohamadou//69=
1144435 from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue, site is on Grid with Ubaie=3D54,7V, mohamadou//691144=
435 from Huawei is informed.","cedric.tiani@matech-cameroun.com","70","14-0=
6-2025 20:36:21","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0005255629","NTE=
MASSI","","14-06-2025 20:35:36","14-06-2025 20:31:30","14-06-2025 21:11:47"=
,"Grid outage, Gen failed to start due to ATS malfunction  // Gen Start Man=
ually","Delor Telezing","Equipment Repair","Passive","Control Panel","ATS-A=
MF Issue","Grid outage, Gen failed to start due to ATS malfunction  // Gen =
Start Manually","cedric.tiani@matech-cameroun.com","247","14-06-2025 20:35:=
36","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005255623","Ebo=
go","","14-06-2025 20:33:20","14-06-2025 20:29:09","14-06-2025 21:12:17","G=
rid fluctuation, site went down because Gen failed to start due to grid bad=
 voltag // He bypassed the grid and started Gen manually","Siligap Boris","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, site went down because Gen failed to start due to grid bad =
voltag // He bypassed the grid and started Gen manually","cedric.tiani@mate=
ch-cameroun.com","252","14-06-2025 20:33:20","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005255616","T=
SINGA VILLAGE 2","","14-06-2025 20:32:24","14-06-2025 20:28:43","14-06-2025=
 20:44:54","Grid ouage, Site went down because gen stopped due to water ing=
ress into the tank // Grid return","Delor Telezing","Fuel Outage (Probable)=
","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","Grid ouage, =
Site went down because gen stopped due to water ingress into the tank // Gr=
id return","vanel.mbiada@matech-cameroun.com","223","14-06-2025 20:32:24","=
MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0005255615","Abo=
me","","14-06-2025 20:32:17","14-06-2025 20:30:11","14-06-2025 20:33:49","G=
rid outage, Site went down before Gen start due to poor backup// Gen Automa=
tically Started","MINKA NICOLAS","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup// Gen Automatically Started","cedric.tiani@matech-ca=
meroun.com","127","14-06-2025 20:32:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0005255610","Mbankolo=
 petit paris","","14-06-2025 20:31:13","14-06-2025 20:28:33","14-06-2025 20=
:36:28","Cascaded Incident from TTO5413879","Mboua Thierry","Cascade Outage=
","Active","Cascade Active","Cascade Active","Active; no power issue site o=
n Grid with U=3D54,1 V;The fme TX Mohammadou 691144435 of huawei is informe=
d","system","740206","14-06-2025 20:31:13","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005255609","M=
elen Ba'aba","","14-06-2025 20:31:08","14-06-2025 20:12:18","14-06-2025 20:=
43:04","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage Site went down due to Gen overload (300 A /20 KV=
A) // Grid return","vanel.mbiada@matech-cameroun.com","273144","14-06-2025 =
20:31:08","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0005255603","AFE=
ME NORD","IHS_YND_808","14-06-2025 20:30:49","14-06-2025 20:28:33","14-06-2=
025 20:36:28","Active; no power issue site on Grid with U=3D54,1 V;The fme =
TX Mohammadou 691144435 of huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active; no power issue site on Grid with U=3D54,1 V;The fme TX M=
ohammadou 691144435 of huawei is informed","cedric.tiani@matech-cameroun.co=
m","137","14-06-2025 20:30:49","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005255596","Mok=
olo Yaounde","","14-06-2025 20:29:16","14-06-2025 20:25:17","14-06-2025 21:=
04:24","Site went down due to insufficient of rectifier on site SS IHS Bern=
ard is informed // Site stabilised","","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to insufficient of rectifier on=
 site SS IHS Bernard is informed // Site stabilised","cedric.tiani@matech-c=
ameroun.com","241","14-06-2025 20:29:16","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005255593","O=
dza II OCM","","14-06-2025 20:28:22","14-06-2025 20:12:13","14-06-2025 20:3=
1:13","	Grid outage site went down before Gen started due to poor battery b=
ack up // Gen automatically started","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage site went=
 down before Gen started due to poor battery back up // Gen automatically s=
tarted","vanel.mbiada@matech-cameroun.com","971","14-06-2025 20:28:22","MAT=
ECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005255591","Ron=
d Point Express1114","","14-06-2025 20:27:11","14-06-2025 20:23:52","14-06-=
2025 21:08:48","Grid outage site went down before Gen started due to poor b=
attery back up // Grid return","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before Gen started due to poor battery back up // Grid return","cedric.tia=
ni@matech-cameroun.com","200","14-06-2025 20:27:11","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005255590","N=
GONA","","14-06-2025 20:27:09","14-06-2025 20:26:59","14-06-2025 21:06:47",=
"Grid outage,site went down because Gen failed to start due to battery Gen =
faulty  //Grid return","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - Generator Battery","Grid outage,site went down because Gen f=
ailed to start due to battery Gen faulty  //Grid return","vanel.mbiada@mate=
ch-cameroun.com","11","14-06-2025 20:27:09","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005255588","Tou=
ring Club International","","14-06-2025 20:26:14","14-06-2025 20:23:00","14=
-06-2025 20:57:10","	Grid outage, Site went down before Gen start due to po=
or backup // Gen started automatically ","Albran Byorel","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","	Grid outage, Sit=
e went down before Gen start due to poor backup // Gen started automaticall=
y ","cedric.tiani@matech-cameroun.com","195","14-06-2025 20:26:14","MATECH =
CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0005255586","H=
-Paradis","IHS_YND_506","14-06-2025 20:25:34","14-06-2025 20:21:29","14-06-=
2025 22:22:28","No power issue, site is on grid with Ubaie: 54.4V, Symphori=
en(650257151) from Huawei is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site =
is on grid with Ubaie: 54.4V, Symphorien(650257151) from Huawei is informed=
","vanel.mbiada@matech-cameroun.com","245","14-06-2025 20:25:34","MATECH CM=
R"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0005255585","SOA=
 UNIVERSITY STADIUM","","14-06-2025 20:25:31","14-06-2025 20:19:10","14-06-=
2025 21:08:04","Grid fluctuation,Site went down due to PWC ZTE dysfunction/=
/He reset it and site on Grid","Siligap Boris","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid fluctuation,Site went down=
 due to PWC ZTE dysfunction//He reset it and site on Grid","cedric.tiani@ma=
tech-cameroun.com","382","14-06-2025 20:25:31","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005255580","C=
-Supreme","","14-06-2025 20:24:27","14-06-2025 20:20:19","14-06-2025 20:24:=
58","Site went down due to 02/04 rectifiers dysfunctionning on site//Site s=
tabilised","","Equipment Repair","Passive","Rectifier","Rectifier Module","=
	Site went down due to 02/04 rectifiers dysfunctionning on site//Site stabi=
lised","vanel.mbiada@matech-cameroun.com","249","14-06-2025 20:24:27","MATE=
CH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005255579","HOP=
ITAL DE LA CAISSE","","14-06-2025 20:24:15","14-06-2025 20:19:05","14-06-20=
25 20:21:46","Grid outage site went down before Gen started due to poor bat=
tery back up // Gen automatically started","Delor Telezing","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage si=
te went down before Gen started due to poor battery back up // Gen automati=
cally started","cedric.tiani@matech-cameroun.com","311","14-06-2025 20:24:1=
5","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0005255577","Nkolanga=
a","","14-06-2025 20:23:28","14-06-2025 20:15:00","14-06-2025 20:21:39","Ca=
scaded Incident from TTO5413846","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down before =
Gen started due to poor battery back up // GEN automatically started","syst=
em","265768","14-06-2025 20:23:28","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0005255574","Aba=
ng","IHS_YND_289","14-06-2025 20:23:01","14-06-2025 20:15:00","14-06-2025 2=
0:21:39","Grid outage site went down before Gen started due to poor battery=
 back up // GEN automatically started","Mba Lazare Herve","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site=
 went down before Gen started due to poor battery back up // GEN automatica=
lly started","cedric.tiani@matech-cameroun.com","482","14-06-2025 20:23:01"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005255573","S=
tade-Abega","","14-06-2025 20:22:35","14-06-2025 20:18:24","14-06-2025 20:2=
7:03","	Site impacted by EKounou_II","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Site i=
mpacted by EKounou_II","vanel.mbiada@matech-cameroun.com","253","14-06-2025=
 20:22:35","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005255569","S=
atcom","","14-06-2025 20:21:48","14-06-2025 20:17:36","14-06-2025 21:16:28"=
,"No power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144=
412) of huawei is informed","Delor Telezing","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144412) of huawei is in=
formed","vanel.mbiada@matech-cameroun.com","253","14-06-2025 20:21:48","MAT=
ECH CMR"
"Closed Complete","Site Down","T0219","IHS_YND_024","NOCINC0005255566","Gar=
bati building","","14-06-2025 20:21:20","14-06-2025 20:19:14","14-06-2025 2=
0:21:45","Grid outage site went down before Gen started due to poor battery=
 back up // GEN automatically started","Delor Telezing","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site w=
ent down before Gen started due to poor battery back up // GEN automaticall=
y started","cedric.tiani@matech-cameroun.com","126","14-06-2025 20:21:20","=
MATECH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0005255563","Mvo=
g-Ada_OCM","","14-06-2025 20:20:20","14-06-2025 20:19:00","14-06-2025 20:21=
:58","Grid only on site, No space on site to deploy MDGE//Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid onl=
y on site, No space on site to deploy MDGE//Grid return","cedric.tiani@mate=
ch-cameroun.com","81","14-06-2025 20:20:20","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005255560","Awa=
e Ewonkan","","14-06-2025 20:19:22","14-06-2025 20:16:12","14-06-2025 21:17=
:43","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IH=
S SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid retur=
n","cedric.tiani@matech-cameroun.com","191","14-06-2025 20:19:22","MATECH C=
MR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005255559","A=
bom","","14-06-2025 20:19:20","14-06-2025 20:15:08","14-06-2025 20:30:46","=
	Grid outage, Site went down because Gen failed to start due to Gen Overloa=
d (16KVA /300A) // Grid return","Siligap Boris","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","	Grid outage, Site went down because Gen fa=
iled to start due to Gen Overload (16KVA /300A) // Grid return","vanel.mbia=
da@matech-cameroun.com","253","14-06-2025 20:19:20","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005255542","N=
kolfoulou","IHS_YND_308","14-06-2025 20:17:29","14-06-2025 20:12:18","14-06=
-2025 21:14:18","Grid outage Site went down due to Gen overload (300 A /20 =
KVA) // Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid outage Site went down due to Gen overload (300 A =
/20 KVA) // Grid return","vanel.mbiada@matech-cameroun.com","312","14-06-20=
25 20:17:29","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005255537","Nko=
abang2","","14-06-2025 20:16:45","14-06-2025 20:14:23","14-06-2025 21:05:53=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","cedr=
ic.tiani@matech-cameroun.com","143","14-06-2025 20:16:45","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005255411","N=
KOLMEKONG YDE","","14-06-2025 19:54:04","14-06-2025 19:49:43","14-06-2025 1=
9:54:11","Grid outage , Gen did not start due to poor battery backup // Gri=
d return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage , Gen did not start due to poor ba=
ttery backup // Grid return","vanel.mbiada@matech-cameroun.com","262","14-0=
6-2025 19:54:04","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005255255","Elo=
umdem stade","","14-06-2025 19:24:21","14-06-2025 19:22:12","14-06-2025 19:=
30:52","	Grid outage, Site went down before Gen start due to poor backup //=
 Gen started automatically","Fanda Brice","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","	Grid outage, Site went down bef=
ore Gen start due to poor backup // Gen started automatically","cedric.tian=
i@matech-cameroun.com","130","14-06-2025 19:24:21","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005255241","E=
mana lycee 2","","14-06-2025 19:20:25","14-06-2025 19:18:15","14-06-2025 19=
:53:10","Grid outage, Site went down due to Gen overload(20kva, 260A) // Gr=
id return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down due to Gen overload(20kva, 260A) /=
/ Grid return","vanel.mbiada@matech-cameroun.com","131","14-06-2025 19:20:2=
5","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005255102","C=
NR","","14-06-2025 18:52:28","14-06-2025 18:50:18","14-06-2025 18:53:58","	=
Grid outage, Site went down before Gen start due to poor backup // Gen star=
ted automatically","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","	Grid outage, Site went down before Gen=
 start due to poor backup // Gen started automatically","vanel.mbiada@matec=
h-cameroun.com","131","14-06-2025 18:52:28","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005255040","Ngo=
usso Vallee","","14-06-2025 18:34:42","14-06-2025 18:32:07","14-06-2025 20:=
21:07","Site went down because insufficient of rectifier on site //site sta=
bilized","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down because insufficient of rectifier on site //site =
stabilized","cedric.tiani@matech-cameroun.com","156","14-06-2025 18:34:42",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005254877","E=
toudi","","14-06-2025 18:03:17","14-06-2025 18:01:07","14-06-2025 18:03:01"=
,"Grid outage, site went down before Gen start due to poor battery backup",=
"Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Battery Low","Grid outage, site went down before Gen start due to poor=
 battery backup","vanel.mbiada@matech-cameroun.com","130","14-06-2025 18:03=
:17","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0005254863","Bas=
tos-BAT","","14-06-2025 17:58:48","14-06-2025 06:48:00","14-06-2025 17:50:2=
0","","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Gener=
ator Battery","Grid outage, site went down because Gen failed to start due =
to Ge Battery faulty // He started Gen manually with an external battery","=
etienne.itondo@ihstowers.com","40249","14-06-2025 17:58:48","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005254860","M=
essassi 2","","14-06-2025 17:57:22","14-06-2025 17:54:04","14-06-2025 18:56=
:50","Grid outage, Gen failed to start due to Bay ZTE malfunction // Gen st=
art manually","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","R=
ectifier Module Overloaded","Grid outage, Gen failed to start due to Bay ZT=
E malfunction // Gen start manually","vanel.mbiada@matech-cameroun.com","20=
0","14-06-2025 17:57:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005254752","Carrefou=
r Ayissi Ele","","14-06-2025 17:40:49","14-06-2025 17:37:58","14-06-2025 17=
:39:59","Cascaded Incident from TTO5412915","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down because our=
 FME  Parker is on site (Replacing Radiator)//End of work","system","268053=
","14-06-2025 17:40:49","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005254747","Saa=
","IHS_YND_810","14-06-2025 17:39:42","14-06-2025 17:37:58","14-06-2025 17:=
39:59","Site went down because our FME  Parker is on site (Replacing Radiat=
or)//End of work","Parker Tchoup","Installation Activity","Passive","Planne=
d Activity","Installation Activity","Site went down because our FME  Parker=
 is on site (Replacing Radiator)//End of work","cedric.tiani@matech-camerou=
n.com","105","14-06-2025 17:39:42","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005254723","Nsa=
m Sofavinc","IHS_YND_732","14-06-2025 17:37:09","14-06-2025 17:32:59","14-0=
6-2025 18:04:19","Site went down because CB(50A) of  RECTIFIERS in PWC disj=
uncted//He rearmed it","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier - Circuit Breaker","Site went down because CB(50A) of  RECT=
IFIERS in PWC disjuncted//He rearmed it","cedric.tiani@matech-cameroun.com"=
,"251","14-06-2025 17:37:09","MATECH CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0005254715","Nsa=
m escale LP","","14-06-2025 17:34:01","14-06-2025 17:32:59","14-06-2025 18:=
04:19","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"Site went down because CB(50A) of  RECTIFIERS in PWC disjuncted//He rearm=
ed it","cedric.tiani@matech-cameroun.com","268346","14-06-2025 17:34:01","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0005254656","Dragage"=
,"","14-06-2025 17:22:38","14-06-2025 17:18:10","14-06-2025 17:50:20","Casc=
aded Incident from TTO5412809","Mboua Thierry","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down due to Grid outage // gr=
id return","system","297998","14-06-2025 17:22:38","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005254649","ARM=
P Building","IHS_YND_192","14-06-2025 17:21:18","14-06-2025 17:18:10","14-0=
6-2025 17:50:20","Site went down due to Grid outage // grid return","Mboua =
Thierry","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Site went down due to Grid outage // grid return","cedric.tiani@matech-ca=
meroun.com","189","14-06-2025 17:21:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005254633","Emana Ly=
cee","","14-06-2025 17:20:00","14-06-2025 17:16:56","14-06-2025 17:19:09","=
Cascaded Incident from TTO5412788","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation,Site went down b=
ecause gen start and stopped due to grid bad voltage // He bypass grid and =
Gen manually Started","system","276402","14-06-2025 17:20:00","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005254629","E=
mana lycee 2","IHS_YND_274","14-06-2025 17:19:15","14-06-2025 17:16:56","14=
-06-2025 17:19:09","Grid fluctuation,Site went down because gen start and s=
topped due to grid bad voltage // He bypass grid and Gen manually Started",=
"Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation,Site went down because gen start and stop=
ped due to grid bad voltage // He bypass grid and Gen manually Started","ol=
ivier.kwedi@ihstowers.com","140","14-06-2025 17:19:15","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0005254015","E=
kombitie","","14-06-2025 15:59:11","14-06-2025 15:57:44","14-06-2025 16:32:=
41","Site went down because 02/05 rectifiers faulty //he replaced","Fabrice=
 Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site=
 went down because 02/05 rectifiers faulty //he replaced","vanel.mbiada@mat=
ech-cameroun.com","89","14-06-2025 15:59:11","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005253924","E=
MANA BILICK CITY","IHS_YND_279","14-06-2025 15:45:11","14-06-2025 15:43:48"=
,"14-06-2025 19:23:08","Access issues due to landlord(Landlord has forbidde=
n to start the Gen due to noise)//Grid return","Fabrice Pouakam","Access De=
nial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord"=
,"Access issues due to landlord(Landlord has forbidden to start the Gen due=
 to noise)//Grid return","vanel.mbiada@matech-cameroun.com","85","14-06-202=
5 15:45:11","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005253900","M=
essassi okolo","","14-06-2025 15:43:49","14-06-2025 15:43:48","14-06-2025 1=
9:18:52","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Access issues due to landlord(Landlord has forbidden to =
start the Gen due to noise)//Grid return","vanel.mbiada@matech-cameroun.com=
","274846","14-06-2025 15:43:49","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005253897","N=
kolbong","","14-06-2025 15:43:13","14-06-2025 15:40:55","14-06-2025 19:17:4=
0","Grid outage,Site went Down because Gen started and stopped due to Gen o=
verload(22kva//350A)// Grid return","Delor Telezing","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen=
 started and stopped due to Gen overload(22kva//350A)// Grid return","vanel=
.mbiada@matech-cameroun.com","139","14-06-2025 15:43:13","MATECH CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0005253887","Ese=
ka Town","","14-06-2025 15:40:45","14-06-2025 15:38:35","14-06-2025 15:42:3=
9","Grid outage,site went down because Gen failed to start due to Gen card =
dysfunction//Grid return","Kemeni Franklin","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage,site went down because Gen fai=
led to start due to Gen card dysfunction//Grid return","cedric.tiani@matech=
-cameroun.com","131","14-06-2025 15:40:45","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005253689","Nom=
ayos montee Meche","","14-06-2025 14:57:56","14-06-2025 14:51:46","14-06-20=
25 14:54:37","Grid fluctuation, Site went down before Gen start due to poor=
 backup// GEN started automatically","Fanda Brice","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid fluctuation, Site =
went down before Gen start due to poor backup// GEN started automatically",=
"cedric.tiani@matech-cameroun.com","371","14-06-2025 14:57:56","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005253357","Ema=
na lycee 2","","14-06-2025 13:59:46","13-06-2025 12:43:18","13-06-2025 13:4=
0:35","Backtracking//Grid outage, Site went down because Gen started and st=
opped due to Gen overload(20kva, 260A) // He reduced the load","Fabrice Pou=
akam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Backtracki=
ng//Grid outage, Site went down because Gen started and stopped due to Gen =
overload(20kva, 260A) // He reduced the load","loic.noumsi@matech-cameroun.=
com","90989","14-06-2025 13:59:46","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005253041","ELO=
UMDEM CARRIERE 2","","14-06-2025 13:34:15","14-06-2025 13:27:07","14-06-202=
5 14:27:36"," Site went down because Gen ran until fuel shortage// Refuelin=
g Done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage"," Si=
te went down because Gen ran until fuel shortage// Refueling Done","loic.no=
umsi@matech-cameroun.com","429","14-06-2025 13:34:15","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005253032","B=
arriere","","14-06-2025 13:31:44","14-06-2025 13:30:35","14-06-2025 13:30:5=
1","Active// No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (6=
54266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is=
 informed.","edwige.kapawo@matech-cameroun.com","70","14-06-2025 13:31:44",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005252894","E=
koumdoum OCM","","14-06-2025 13:05:18","14-06-2025 13:02:10","14-06-2025 13=
:26:10","Site went down because RM Willy KAMGA and SS Alphonse Deffo IHS ar=
e on Site for work ( configures the PWC ZTE)//End of work","Albran Byorel",=
"Installation Activity","Passive","Planned Activity","Installation Activity=
","Grid fluctuation, Site went down before Gen start due to poor backup// G=
EN started automatically","edwige.kapawo@matech-cameroun.com","190","14-06-=
2025 13:05:18","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005252466","M=
vog-Manga","","14-06-2025 12:07:42","14-06-2025 12:06:32","14-06-2025 12:29=
:21","Active// No power issue on site. Site on Grid Ubai=3D54.3 V, The FME =
TX Lionel Adjep/655184876/ From Huawei is informed. Notice that Disjunction=
 in OCM bay","Albran Byorel","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active// No power issue on site. S=
ite on Grid Ubai=3D54.3 V, The FME TX Lionel Adjep/655184876/ From Huawei i=
s informed. Notice that Disjunction in OCM bay","edwige.kapawo@matech-camer=
oun.com","72","14-06-2025 12:07:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0005252462","Crf Corn=
ier","","14-06-2025 12:06:32","14-06-2025 11:58:14","14-06-2025 13:57:48","=
Cascaded Incident from TTO5410430","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,no space to deploy MDGE=
 // Grid returned","system","273995","14-06-2025 12:06:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0005252461","Mobil-Es=
sos","","14-06-2025 12:06:32","14-06-2025 11:58:14","14-06-2025 13:57:48","=
Cascaded Incident from TTO5410430","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,no space to deploy MDGE=
 // Grid returned","system","273994","14-06-2025 12:06:32","MATECH CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0005252458","M=
adison","IHS_YND_109, IHS_YND_566","14-06-2025 12:05:32","14-06-2025 11:58:=
14","14-06-2025 13:57:48","Grid outage,no space to deploy MDGE // Grid retu=
rned","MFOUAGUEGUE MATHIEU","Grid Supply","Passive","Grid","National Grid -=
 Grid Outage Issue","Grid outage,no space to deploy MDGE // Grid returned",=
"edwige.kapawo@matech-cameroun.com","439","14-06-2025 12:05:32","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005252180","Nkolondo=
m","","14-06-2025 11:31:30","14-06-2025 11:26:45","14-06-2025 11:31:52","Ca=
scaded Incident from TTO5410117","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage , Gen did not start due=
 to poor battery backup // Grid restoration","system","268683","14-06-2025 =
11:31:30","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005252172","N=
KOLMEKONG YDE","IHS_YND_304","14-06-2025 11:30:53","14-06-2025 11:26:45","1=
4-06-2025 11:31:52","Grid outage , Gen did not start due to poor battery ba=
ckup // Grid restoration","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage , Gen did not star=
t due to poor battery backup // Grid restoration","edwige.kapawo@matech-cam=
eroun.com","249","14-06-2025 11:30:53","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005252145","O=
lembe-Terminus","","14-06-2025 11:25:50","14-06-2025 11:24:41","14-06-2025 =
12:16:25","Grid outage site went down because Gen failed to start due to Ge=
n card faulty // he forced the startutp","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down =
because Gen failed to start due to Gen card faulty // he forced the startup=
","edwige.kapawo@matech-cameroun.com","70","14-06-2025 11:25:50","MATECH CM=
R"
"Closed Complete","Site Down","T1739","IHS_YND_691","NOCINC0005251793","Mba=
lla 2 REGIE","","14-06-2025 10:33:17","14-06-2025 10:28:12","14-06-2025 11:=
12:36","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage // He bypassed the Grid and manually started the Gen","De=
lor Telezing","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because Gen failed to start d=
ue to grid bad voltage // He bypassed the Grid and manually started the Gen=
","loic.noumsi@matech-cameroun.com","306","14-06-2025 10:33:17","MATECH CMR=
"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005251735","Eto=
udi2","","14-06-2025 10:23:08","14-06-2025 09:45:17","14-06-2025 11:47:18",=
"Grid fluctuations, Site went down because gen fails to start due to grid b=
ad voltage and no RCP // He bypassed the Grid and site on Gen","Delor Telez=
ing","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuations, Site went down because gen fails to start due to gri=
d bad voltage and no RCP // He bypassed the Grid and site on Gen","loic.nou=
msi@matech-cameroun.com","2272","14-06-2025 10:23:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0005251706","Omnispor=
t-Rail","","14-06-2025 10:17:40","14-06-2025 10:14:51","14-06-2025 10:47:05=
","Cascaded Incident from TTO5409605","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen Manually Started","system",=
"265879","14-06-2025 10:17:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_509","NOCINC0005251707","MANGUIER=
S CHAPELLE","","14-06-2025 10:17:40","14-06-2025 10:14:51","14-06-2025 10:4=
7:05","Cascaded Incident from TTO5409605","Fabrice Pouakam","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen Manually Started","sys=
tem","265879","14-06-2025 10:17:40","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005251703","M=
anguier","IHS_YND_506, IHS_YND_509","14-06-2025 10:17:00","14-06-2025 10:14=
:51","14-06-2025 10:47:05","Grid outage, site went down before gen start du=
e to poor battery backup // Gen Manually Started","Fabrice Pouakam","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage, site went down before gen start due to poor battery backup // Gen Ma=
nually Started","edwige.kapawo@matech-cameroun.com","130","14-06-2025 10:17=
:00","MATECH CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0005251695","E=
seka Town","","14-06-2025 10:14:37","14-06-2025 10:05:59","14-06-2025 12:07=
:50","Active// No power issue, Site on Gen  Ubaie:53V, The FME Tx Etienne/6=
95033981 From Huawei is informed ","Kemeni Franklin","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// N=
o power issue, Site on Gen  Ubaie:53V, The FME Tx Etienne/695033981 From Hu=
awei is informed ","edwige.kapawo@matech-cameroun.com","519","14-06-2025 10=
:14:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005251363","Nkolondo=
m","","14-06-2025 09:22:27","14-06-2025 08:18:47","14-06-2025 08:21:53","Ca=
scaded Incident from TTO5408943","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage , Gen did not start due=
 to poor battery backup // Gen started Automatically","system","265628","14=
-06-2025 09:22:27","MATECH CMR"
"Closed Complete","Site Down","T0210","IHS_YND_206","NOCINC0005251354","ARM=
P","","14-06-2025 09:19:19","14-06-2025 09:15:12","14-06-2025 10:09:20","Gr=
id outage .gen failed to start due to battery terminals not well tighted//W=
e fixed very well battery terminals and site on gen","Mboua Thierry","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage .=
gen failed to start due to battery terminals not well tighted//We fixed ver=
y well battery terminals and site on gen","loic.noumsi@matech-cameroun.com"=
,"247","14-06-2025 09:19:19","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005251095","N=
KOLMEKONG YDE","IHS_YND_304","14-06-2025 08:23:16","14-06-2025 08:18:47","1=
4-06-2025 08:21:53","Grid outage , Gen did not start due to poor battery ba=
ckup // Gen started Automatically","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage , Gen did=
 not start due to poor battery backup // Gen started Automatically","loic.n=
oumsi@matech-cameroun.com","271","14-06-2025 08:23:16","MATECH CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0005250829","Nsa=
m escale LP","","14-06-2025 07:46:35","14-06-2025 07:40:28","14-06-2025 07:=
46:18","Active// No power issue on site ,site on Grid with Ubaie=3D53,5 V T=
he Tx FME HENRI//699949693 is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power is=
sue on site ,site on Grid with Ubaie=3D53,5 V The Tx FME HENRI//691145055 i=
s informed","loic.noumsi@matech-cameroun.com","368","14-06-2025 07:46:35","=
MATECH CMR"
"Cancelled","Warning","","IHS_YND_129","NOCINC0005250682","Bastos-BAT","","=
14-06-2025 07:19:07","","","Cascaded Incident from TTO5408141 - Cascade Rem=
oved From TTO5408141","Mboua Thierry","","","","","","system","3407","14-06=
-2025 07:19:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005250635","Nkolondo=
m","","14-06-2025 07:10:26","14-06-2025 07:04:08","14-06-2025 07:09:11","Ca=
scaded Incident from TTO5408416","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage , Gen did not start due=
 to poor battery backup // Gen started Automatically","system","1212212","1=
4-06-2025 07:10:26","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005250633","N=
KOLMEKONG YDE","IHS_YND_304","14-06-2025 07:09:35","14-06-2025 07:04:08","1=
4-06-2025 07:09:11","Grid outage , Gen did not start due to poor battery ba=
ckup // Gen started Automatically","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage , Gen did=
 not start due to poor battery backup // Gen started Automatically","edwige=
.kapawo@matech-cameroun.com","328","14-06-2025 07:09:35","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005250466","Mam=
ch Building","","14-06-2025 06:39:51","14-06-2025 06:30:43","14-06-2025 08:=
13:29","Grid outage, site went down because Gen failed to start due to high=
 temp alarm // He added water in the radiator, site on Gen","Mboua Thierry"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","Grid outage, site went down because Gen failed to start due =
to high temp alarm // He added water in the radiator, site on Gen","loic.no=
umsi@matech-cameroun.com","549","14-06-2025 06:39:51","MATECH CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0005250413","Dra=
gage","","14-06-2025 06:31:34","14-06-2025 06:24:27","14-06-2025 12:58:52",=
"Active//No power issue, site is on Grid with Ubaie=3D48.99 V, TX FME Eloun=
dou bertrand (652586578) from Huawei is informed","Mboua Thierry","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue, site is on Grid with Ubaie=3D48.99 V, TX FME Elo=
undou bertrand (652586578) from Huawei is informed","loic.noumsi@matech-cam=
eroun.com","428","14-06-2025 06:31:34","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0005250387","Bas=
tos-BAT","","14-06-2025 06:26:32","14-06-2025 06:22:25","14-06-2025 06:47:2=
4","Active// No power issue, site is on Grid  with Ubaie=3D55V The Tx Fme, =
Eloundou(652586578) from Huawei is informed","Mboua Thierry","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue, site is on Grid  with Ubaie=3D55V The Tx Fme, Elound=
ou(652586578) from Huawei is informed","loic.noumsi@matech-cameroun.com","2=
48","14-06-2025 06:26:32","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005250381","ARM=
P Building","","14-06-2025 06:24:32","14-06-2025 06:22:20","14-06-2025 07:5=
8:50","Grid outage, site went down because Gen failed to start due to Ge Ba=
ttery faulty // He started Gen manually with an external battery","Mboua Th=
ierry","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","=
Grid outage, site went down because Gen failed to start due to Ge Battery f=
aulty // He started Gen manually with an external battery","loic.noumsi@mat=
ech-cameroun.com","133","14-06-2025 06:24:32","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005250222","Mam=
ch Building","","14-06-2025 05:49:24","14-06-2025 05:39:59","14-06-2025 06:=
09:59","Grid outage site went down because Gen stopped with ''Undervoltage'=
 ALARM // he reset the Gen Card and manually started Gen","Mboua Thierry","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage =
site went down because Gen stopped with ''Undervoltage' ALARM // he reset t=
he Gen Card and manually started Gen","gaelle.njiofack@matech-cameroun.com"=
,"1885","14-06-2025 05:49:24","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005249959","Eto=
udi2","","14-06-2025 04:39:25","14-06-2025 04:36:04","14-06-2025 09:34:13",=
"Grid fluctuation, Site went down because gen fails to start due to grid ba=
d voltage// He bypassed the Grid and started Gen manually","Delor Telezing"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid fluctuation, Site went down because gen fails to start due to grid bad=
 voltage// He bypassed the Grid and started Gen manually","franck.nkomot@ma=
tech-cameroun.com","201","14-06-2025 04:39:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005249871","OTELE MT=
N","","14-06-2025 04:19:06","14-06-2025 04:10:46","14-06-2025 05:08:36","Ca=
scaded Incident from TTO5407582","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Gen only site , site went down because =
the controler did not send the start order // controler reset and Gen start=
 manually","system","266028","14-06-2025 04:19:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005249872","Mom","",=
"14-06-2025 04:19:06","14-06-2025 04:10:46","14-06-2025 05:08:36","Cascaded=
 Incident from TTO5407582","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Gen only site , site went down because the co=
ntroler did not send the start order // controler reset and Gen start manua=
lly","system","266028","14-06-2025 04:19:06","MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0005249853","M=
beng","","14-06-2025 04:13:45","14-06-2025 04:06:46","14-06-2025 05:07:17",=
"","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Gen only site , site went down because the controler did not send the=
 start order // controler reset and Gen start manually","gaelle.njiofack@ma=
tech-cameroun.com","266269","14-06-2025 04:13:45","MATECH CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0005249850","B=
ondjock","","14-06-2025 04:12:47","14-06-2025 04:06:46","14-06-2025 05:07:1=
7","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Gen only site , site went down because the controler did not send =
the start order // controler reset and Gen start manually","gaelle.njiofack=
@matech-cameroun.com","266269","14-06-2025 04:12:47","MATECH CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0005249848","M=
inka","IHS_YND_369, IHS_YND_531, IHS_YND_370, IHS_YND_372","14-06-2025 04:1=
1:56","14-06-2025 04:06:46","14-06-2025 05:08:36","Grid outage , site went =
down because the controler did not send the starter order // controler rese=
ted and Gen started manually, gen left on manual mode","Fanda Brice","Equip=
ment Repair","Passive","Control Panel","ATS-AMF Issue","Gen only site , sit=
e went down because the controler did not send the starter order // control=
er reseted and Gen started manually, gen left on manual mode","gaelle.njiof=
ack@matech-cameroun.com","311","14-06-2025 04:11:56","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005249812","Eto=
udi2","","14-06-2025 03:59:39","14-06-2025 03:55:29","14-06-2025 04:27:29",=
"Grid fluctuation, Site went down because gen fails to start due to grid ba=
d voltage// He bypasse the Grid and site on Gen","Delor Telezing","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, Site went down because gen fails to start due to grid bad voltage//=
 He bypasse the Grid and site on Gen","franck.nkomot@matech-cameroun.com","=
250","14-06-2025 03:59:39","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005249767","Nko=
lbisson IITA LP","","14-06-2025 03:52:57","14-06-2025 03:50:41","14-06-2025=
 12:16:23","Grid only site, no space to deploy MDGE // Grid returned","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only=
 site, no space to deploy MDGE // Grid returned","franck.nkomot@matech-came=
roun.com","137","14-06-2025 03:52:57","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005249724","Beh=
ind P T school Yde","","14-06-2025 03:34:59","14-06-2025 03:32:51","14-06-2=
025 05:17:07","Grid Outage, Site went down because The rectifiers are not p=
owered due to malfunctioning of MPR on site // Grid restoration","Paul BIBO=
UM","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid Outage, Site went down because The rectifiers are not powered due to =
malfunctioning of MPR on site // Grid restoration","franck.nkomot@matech-ca=
meroun.com","129","14-06-2025 03:34:59","MATECH CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0005249571","NKO=
LOSSAN OKOK","","14-06-2025 02:29:14","14-06-2025 02:26:05","14-06-2025 03:=
01:05","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage no Rcp // he bypassed grid and Gen automatically started"=
,"Parker Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid fluctuation, site went down because Gen failed to star=
t due to grid bad voltage no Rcp // he bypassed grid and Gen automatically =
started","franck.nkomot@matech-cameroun.com","190","14-06-2025 02:29:14","M=
ATECH CMR"
"Closed Complete","Warning","","IHS_YND_167","NOCINC0005249471","Touring Cl=
ub International","","14-06-2025 02:00:14","","","Grid outage, site went do=
wn due to poor backup battery // Site stabilised","Albran Byorel","Warning"=
,"Warning","POWER","Warning - Battery Low Voltage","Grid outage, site went =
down due to poor backup battery // Site stabilised","gaelle.njiofack@matech=
-cameroun.com","613","14-06-2025 02:00:14","MATECH CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0005249361","Ess=
os Marche","","14-06-2025 01:24:21","14-06-2025 01:19:06","14-06-2025 11:38=
:11","Grid outage, No MDGE to deploy  // Grid return","Delor Telezing","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, No MDGE to deploy  // Grid return","franck.nkomot@matech-cameroun.com","3=
16","14-06-2025 01:24:21","MATECH CMR"
"Closed Complete","Site Down","T2104","IHS_YND_711","NOCINC0005249239","H-F=
ranco New","","14-06-2025 00:48:32","14-06-2025 00:41:24","14-06-2025 00:53=
:25","Site went down because FME MiganceTANKO (650631368) from DOWEM SERVIC=
E is on site for plan work (SWAP of bay). Awaiting end of work","Delor Tele=
zing","Installation Activity","Passive","Planned Activity","Installation Ac=
tivity","Site went down because FME MiganceTANKO (650631368) from DOWEM SER=
VICE was on site for plan work (SWAP of bay) // End of work","franck.nkomot=
@matech-cameroun.com","428","14-06-2025 00:48:32","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0005249237","UPA=
C LP","","14-06-2025 00:47:14","14-06-2025 00:41:06","14-06-2025 00:42:06",=
"Active, no power issue, site on grid with U=3D54.3V Tx FME mand Ngetsa (??=
699949553??) From Huawei is informed.","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issu=
e, site on grid with U=3D54.3V Tx FME mand Ngetsa (??699949553??) From Huaw=
ei is informed.","franck.nkomot@matech-cameroun.com","370","14-06-2025 00:4=
7:14","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0005249217","MEH=
ANDAN","","14-06-2025 00:39:20","14-06-2025 00:36:54","14-06-2025 02:33:54"=
,"Site up, awaiting feedback","Albran Byorel","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Solenoid Coil","Grid outage, site went down because gen =
failed to start due to solenoid valve faulty // He bypassed solenoid valve =
and Gen manually started","franck.nkomot@matech-cameroun.com","147","14-06-=
2025 00:39:20","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005249158","Eto=
udi2","","14-06-2025 00:26:40","14-06-2025 00:17:59","14-06-2025 02:55:59",=
"Grid fluctuation, Site went down because gen fails to start due to grid ba=
d voltage// He bypasse the Grid and site on Gen","Delor Telezing","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, Site went down because gen fails to start due to grid bad voltage//=
 He bypasse the Grid and site on Gen","franck.nkomot@matech-cameroun.com","=
522","14-06-2025 00:26:40","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005248992","C=
rf Cornier","","13-06-2025 23:49:22","13-06-2025 23:45:13","14-06-2025 11:4=
0:02","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage,no space to deploy MGE // grid restora","gaelle.n=
jiofack@matech-cameroun.com","310703","13-06-2025 23:49:22","MATECH CMR"
"Closed Complete","Site Down","CTR_068","IHS_YND_109","NOCINC0005248989","M=
obil-Essos","","13-06-2025 23:48:50","13-06-2025 23:45:13","14-06-2025 11:4=
0:02","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage,no space to deploy MGE // grid restora","gaelle.n=
jiofack@matech-cameroun.com","310703","13-06-2025 23:48:50","MATECH CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0005248984","M=
adison","IHS_YND_109, IHS_YND_566","13-06-2025 23:48:21","13-06-2025 23:45:=
13","14-06-2025 11:44:02","Grid outage,no space to deploy MGE // grid resto=
ration","MFOUAGUEGUE MATHIEU","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","Grid outage,no space to deploy MGE // grid restora",=
"gaelle.njiofack@matech-cameroun.com","189","13-06-2025 23:48:21","MATECH C=
MR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005248932","N=
KOLMEKONG YDE","","13-06-2025 23:34:03","13-06-2025 23:32:56","13-06-2025 2=
3:39:56","Grid outage , Gen did not start due to poor battery backup  // Gr=
id restoration","Fabrice Pouakam","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage , Gen did not start due to p=
oor battery backup  // Grid restoration","gaelle.njiofack@matech-cameroun.c=
om","68","13-06-2025 23:34:03","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005248930","N=
kolondom","","13-06-2025 23:33:31","13-06-2025 23:32:54","14-06-2025 02:34:=
16","No power issue site on Grid , with U=3D57 V The Tx Fme symphorien //69=
1316854 is informed","Fabrice Pouakam","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on G=
rid , with U=3D57 V The Tx Fme symphorien //691316854 is informed","gaelle.=
njiofack@matech-cameroun.com","39","13-06-2025 23:33:31","MATECH CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0005248793","H=
-Franco New","","13-06-2025 23:00:49","13-06-2025 22:59:20","13-06-2025 23:=
15:38","Site went down because FME MiganceTANKO (650631368) from DOWEM SERV=
ICE was on site for plan work (SWAP of bay and GE) //  end of work","Delor =
Telezing","Equipment Replacement","Passive","Planned Activity","Planned Act=
ivity - Passive","Site went down because FME MiganceTANKO (650631368) from =
DOWEM SERVICE was on site for plan work (SWAP of bay and GE) //  end of wor=
k","gaelle.njiofack@matech-cameroun.com","89","13-06-2025 23:00:49","MATECH=
 CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005248496","Mim=
boman4","","13-06-2025 22:02:30","13-06-2025 21:55:43","13-06-2025 22:01:43=
","Site went down due to insufficiency of rectifiers on site // Site stabil=
ized","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficiency of rectifiers on site // Sit=
e stabilized","rouselle.schoune@ihstowers.com","408","13-06-2025 22:02:30",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005248313","MEHANDAN=
","","13-06-2025 21:20:50","13-06-2025 21:10:59","13-06-2025 21:25:59","Cas=
caded Incident from TTO5405842","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","269616","13-06-2025 21:20:50","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005248309","O=
dza II OCM","IHS_YND_528","13-06-2025 21:19:13","13-06-2025 21:10:59","13-0=
6-2025 21:25:59","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","gaelle.njiofack@matech-cameroun.com","496","13-06-=
2025 21:19:13","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005248303","Tou=
ring Club International","","13-06-2025 21:18:26","13-06-2025 21:10:19","13=
-06-2025 21:54:11","Grid outage, site went down due to poor backup battery =
// Site stabilised","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down due to poo=
r backup battery // Site stabilised","loic.noumsi@matech-cameroun.com","488=
","13-06-2025 21:18:26","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005248284","ODZ=
A BORNE 10","","13-06-2025 21:15:05","13-06-2025 21:05:44","13-06-2025 21:2=
0:45","Grid outage, site went down because Gen started and stopped due to h=
igh temp alarm // He added water in the radiator, site on Gen","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid outage, site went down because Gen started and stopp=
ed due to high temp alarm // He added water in the radiator, site on Gen","=
loic.noumsi@matech-cameroun.com","562","13-06-2025 21:15:05","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005248257","Eko=
umdoum OCM","","13-06-2025 21:09:37","13-06-2025 21:03:31","13-06-2025 22:1=
9:31","Grid outage,site went down because Gen failed to start due to PWC ZT=
E dysfunction//He reset it and started the Gen manually","Albran Byorel","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage,site went down because Gen failed to start due to PWC ZTE dysfunctio=
n//He reset it and started the Gen manually","loic.noumsi@matech-cameroun.c=
om","367","13-06-2025 21:09:37","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005248250","SIM=
BOCK BONAMBAPE","","13-06-2025 21:08:49","13-06-2025 21:06:40","13-06-2025 =
21:10:44","Grid Outage, Site went down before Gen start due to poor backup =
// Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid Outage, Site went down before Gen =
start due to poor backup // Grid returned","loic.noumsi@matech-cameroun.com=
","130","13-06-2025 21:08:49","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005248233","Aka=
k-Nkozoa-MTN-IHS","","13-06-2025 21:05:44","13-06-2025 20:55:38","13-06-202=
5 22:01:38","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid outage , Site down due to Air intake in the gene=
rator // generator purged","loic.noumsi@matech-cameroun.com","277690","13-0=
6-2025 21:05:44","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0005248216","Mes=
sassi Ngonlonk","","13-06-2025 21:03:55","13-06-2025 20:57:47","13-06-2025 =
22:00:47","Grid outage, Gen failed to start due to generator card malfuncti=
on // Grid return (Gen Card will be replace)","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen faile=
d to start due to generator card malfunction // Grid return (Gen Cart will =
be replace)","loic.noumsi@matech-cameroun.com","369","13-06-2025 21:03:55",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005248203","N=
KOLMEKONG YDE","","13-06-2025 21:01:06","13-06-2025 20:55:19","13-06-2025 2=
1:54:19","Grid outage, site went down because Gen failed to started due to =
Gen card faullty //He reset card and put site on Gen","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, s=
ite went down because Gen failed to started due to Gen card faullty //He re=
set card and put site on Gen","gaelle.njiofack@matech-cameroun.com","348","=
13-06-2025 21:01:06","MATECH CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0005248197","M=
essassi","IHS_YND_316","13-06-2025 20:59:44","13-06-2025 20:55:38","13-06-2=
025 22:01:38","Grid outage , Site down due to Air intake in the generator /=
/ generator purged","Fabrice Pouakam","Fuel Outage (Probable)","Passive","A=
CDG Gen","ACDG - Air Intake","Grid outage , Site down due to Air intake in =
the generator // generator purged","gaelle.njiofack@matech-cameroun.com","2=
47","13-06-2025 20:59:44","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005248189","N=
kolondom","","13-06-2025 20:57:29","13-06-2025 20:55:24","13-06-2025 21:54:=
24","No power issue site on Grid , with U=3D57 V The Tx Fme symphorien //69=
1316854 is informed","Fabrice Pouakam","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on G=
rid , with U=3D57 V The Tx Fme symphorien //691316854 is informed","gaelle.=
njiofack@matech-cameroun.com","127","13-06-2025 20:57:29","MATECH CMR"
"Closed Complete","Warning","CTR_049","IHS_YND_209","NOCINC0005248102","Man=
guier","","13-06-2025 20:41:03","","","Grid outage, Site went down due to G=
en overload (17KVA ; 160A) //He reduce load and site on Gen","Fabrice Pouak=
am","Warning","Warning","POWER","Warning - ACDG - Overload","Grid outage, S=
ite went down due to Gen overload (17KVA ; 160A) //He reduce load and site =
on Gen","loic.noumsi@matech-cameroun.com","505","13-06-2025 20:41:03","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_869","IHS_YND_407","NOCINC0005247978","M=
onatele MTN","","13-06-2025 20:25:19","12-06-2025 12:24:08","12-06-2025 12:=
39:49","Backtracking// Active//No power issue on site ,site on GRID with Ub=
aie=3D54.4V The TX FME Gregoire(654547479) from Huawei is informed.","Parke=
r Tchoup","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Backtracking// Active//No power issue on site ,site o=
n GRID with Ubaie=3D54.4V The TX FME Gregoire(654547479) from Huawei is inf=
ormed.","gaelle.njiofack@matech-cameroun.com","115272","13-06-2025 20:25:19=
","MATECH CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0005247803","M=
obil-Kondengui","IHS_YND_682","13-06-2025 19:59:35","13-06-2025 19:54:28","=
13-06-2025 20:51:28","Grid only site, no space to deploy MDG // Grid return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id only site, no space to deploy MDG // Grid return","gaelle.njiofack@matec=
h-cameroun.com","308","13-06-2025 19:59:35","MATECH CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0005247801","MES=
SAME NDONGO 1162","","13-06-2025 19:59:10","13-06-2025 19:57:03","13-06-202=
5 21:23:24","Grid outage,site went down because gen failed to start due to =
Gen card Faulty// He started Gen manually","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down =
because gen failed to start due to Gen card Faulty// He started Gen manuall=
y","loic.noumsi@matech-cameroun.com","128","13-06-2025 19:59:10","MATECH CM=
R"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0005247800","M=
ONTEE NKONDENGUI","","13-06-2025 19:59:07","13-06-2025 19:54:28","13-06-202=
5 20:51:28","","Albran Byorel","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid only site, no space to deploy MDG // Grid return",=
"gaelle.njiofack@matech-cameroun.com","281352","13-06-2025 19:59:07","MATEC=
H CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005247782","Ron=
d Point Express1114","","13-06-2025 19:57:01","13-06-2025 19:55:55","13-06-=
2025 20:03:06","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Grid returned","loic.noumsi@matech-camerou=
n.com","67","13-06-2025 19:57:01","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005247711","Beh=
ind P T school Yde","","13-06-2025 19:44:45","13-06-2025 19:41:38","13-06-2=
025 22:03:38","Grid Outage, Site went down because The rectifiers are not p=
owered due to malfunctioning of MPR on site // He reset the MPR","Paul BIBO=
UM","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid Outage, Site went down because The rectifiers are not powered due to =
malfunctioning of MPR on site // He reset the MPR","loic.noumsi@matech-came=
roun.com","188","13-06-2025 19:44:45","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005247701","E=
vodoula OCM","","13-06-2025 19:42:31","12-06-2025 12:24:04","12-06-2025 12:=
39:04"," Backtracking// No power issue site and with Ubaie=3D54.4 V site on=
 Gen The FME TX Mouamadou/658791013 //From Huawei is informed","TIENTCHEU N=
ZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm"," Backtracking// No power issue site and with Uba=
ie=3D54.4 V site on Gen The FME TX Mouamadou/658791013 //From Huawei is inf=
ormed","gaelle.njiofack@matech-cameroun.com","112708","13-06-2025 19:42:31"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005247675","N=
kolfon Cimencam","","13-06-2025 19:37:01","13-06-2025 19:29:50","13-06-2025=
 19:38:08","Site is impacted by Afanoya II(Not manage by HIS)","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Site is impacted by Afanoya II(Not manage by HIS)","gaelle=
.njiofack@matech-cameroun.com","433","13-06-2025 19:37:01","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005247579","Nko=
mo stade","","13-06-2025 19:16:10","13-06-2025 19:13:47","13-06-2025 19:33:=
28","Grid outage, site went down due to grid fluctuations // He bypassed Gr=
id and started Gen manually","Mba Lazare Herve","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","Grid outage, site went down =
due to grid fluctuations // He bypassed Grid and started Gen manually","gae=
lle.njiofack@matech-cameroun.com","144","13-06-2025 19:16:10","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005247425","N=
YOM 2 IHS","","13-06-2025 18:40:20","13-06-2025 14:18:10","13-06-2025 14:32=
:26","Backtracking//Site went down due to Plan work ( Refuelling Gen) done =
by FME Giresse (MATECH) // End of work","Fabrice Pouakam","Installation Act=
ivity","Passive","Planned Activity","Installation Activity","Backtracking//=
Site went down due to Plan work ( Refuelling Gen) done by FME Giresse (MATE=
CH) // End of work","loic.noumsi@matech-cameroun.com","15731","13-06-2025 1=
8:40:20","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0005247274","S=
calom","","13-06-2025 18:18:26","13-06-2025 18:14:15","13-06-2025 19:59:47"=
,"Grid fluctuations, site went down because Gen start but didn't powered th=
e site due to ATS Dysfunction // He bypassed ATS and site PUT on Gen manual=
ly","Paul BIBOUM","Equipment Repair","Passive","Control Panel","ATS-AMF Iss=
ue","Grid fluctuations, site went down because Gen start but didn't powered=
 the site due to ATS Dysfunction // He bypassed ATS and site PUT on Gen man=
ually","gaelle.njiofack@matech-cameroun.com","252","13-06-2025 18:18:26","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0005247267","S=
cience","","13-06-2025 18:15:14","13-06-2025 18:08:02","13-06-2025 19:02:58=
","Site went down because the PWC OF ZTE dysfunction // He reset the PWC, S=
ite on Grid","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Site went down because the PWC OF ZTE =
dysfunction // He reset the PWC, Site on Grid","loic.noumsi@matech-cameroun=
.com","433","13-06-2025 18:15:14","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005247188","O=
dza II OCM","IHS_YND_528","13-06-2025 18:00:42","13-06-2025 17:56:30","13-0=
6-2025 18:00:46","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","gaelle.njiofack@matech-cameroun.com","254","13-06-=
2025 18:00:42","MATECH CMR"
"Closed Complete","Site Down","T1333","IHS_YND_174","NOCINC0005247174","Car=
refourt Nkomo","","13-06-2025 17:59:53","13-06-2025 17:45:44","13-06-2025 2=
1:28:44","Grid outage,Site went down because Gen failed to start due to Gri=
d contactor malfunctioning // He bypassed it site on Grid","Mba Lazare Herv=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid ou=
tage,Site went down because Gen failed to start due to Grid contactor malfu=
nctioning // He bypassed it site on Grid","loic.noumsi@matech-cameroun.com"=
,"850","13-06-2025 17:59:53","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005247042","ESS=
OS OASIS 1111","","13-06-2025 17:46:20","13-06-2025 17:38:07","13-06-2025 1=
9:10:30","Grid outage, Site went down because Gen overload (17kva, 250A)//G=
rid returned","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, Site went down because Gen overload (17kva, 250A=
)//Grid returned","loic.noumsi@matech-cameroun.com","494","13-06-2025 17:46=
:20","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005247010","Acc=
acia New","","13-06-2025 17:42:57","13-06-2025 17:38:51","13-06-2025 18:52:=
49","Grid only site, no space to deploy MDGE // Grid returned","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site, =
no space to deploy MDGE // Grid returned","loic.noumsi@matech-cameroun.com"=
,"248","13-06-2025 17:42:57","MATECH CMR"
"Closed Complete","Warning","T0292","IHS_YND_231","NOCINC0005246946","Nkols=
o","","13-06-2025 17:33:48","","","High temp // Alarm cleared","TIENTCHEU N=
ZETCHIEU GAEL","Warning","Warning","ENVIRONMENT","Warning - High Temperatur=
e","High temp // Alarm cleared","loic.noumsi@matech-cameroun.com","8906","1=
3-06-2025 17:33:48","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005246889","S=
tade-Abega","","13-06-2025 17:28:11","13-06-2025 17:26:40","13-06-2025 17:3=
3:11","Site impacted by EKounou_II","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","Affected by 3rd Party Site","=
Site impacted by EKounou_II","gaelle.njiofack@matech-cameroun.com","92","13=
-06-2025 17:28:11","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005246861","Ebo=
go","","13-06-2025 17:20:42","13-06-2025 17:15:37","13-06-2025 19:14:04","N=
o power issue on site U=3D52,1V site on grid Synphorien 675295205 of Huawei=
 is informed","Siligap Boris","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52,1V =
site on grid Synphorien 675295205 of Huawei is informed","loic.noumsi@matec=
h-cameroun.com","307","13-06-2025 17:20:42","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005246834","A=
WAE OCM","","13-06-2025 17:19:45","13-06-2025 17:14:39","13-06-2025 17:43:4=
7","Grid outage site went down because Gen failed to start due PWC ZTE dysf=
unction // He reset the PWC and site on Grid","Mba Lazare Herve","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage s=
ite went down because Gen failed to start due PWC ZTE dysfunction // He res=
et the PWC and site on Grid","gaelle.njiofack@matech-cameroun.com","307","1=
3-06-2025 17:19:45","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005246833","N=
omayos montee Meche","","13-06-2025 17:18:56","13-06-2025 17:16:44","13-06-=
2025 17:20:19","	Grid outage site went down before gen start due to poor ba=
ttery backup // Grid return","Fanda Brice","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","	Grid outage site went down bef=
ore gen start due to poor battery backup // Grid return","gaelle.njiofack@m=
atech-cameroun.com","132","13-06-2025 17:18:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0005246802","AFEME NO=
RD","","13-06-2025 17:14:34","13-06-2025 16:55:46","13-06-2025 16:57:59","C=
ascaded Incident from TTO5404173","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active"," No power issue, site is on =
gen with Ubaie=3D54.4V, Brice Tsague (650 21 40 96) from Huawei is informed=
.","system","277668","13-06-2025 17:14:34","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005246800","Mba=
nkolo petit paris","IHS_YND_519","13-06-2025 17:14:06","13-06-2025 16:55:46=
","13-06-2025 20:07:59","BACKTRACKING: No power issue, site is on gen with =
Ubaie=3D54.4V, Brice Tsague (650 21 40 96) from Huawei is informed.","Mboua=
 Thierry","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm"," No power issue, site is on gen with Ubaie=3D54.4V, B=
rice Tsague (650 21 40 96) from Huawei is informed.","loic.noumsi@matech-ca=
meroun.com","1101","13-06-2025 17:14:06","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005246762","Sim=
e Building","","13-06-2025 17:06:12","13-06-2025 16:57:01","13-06-2025 17:4=
9:54","Grid outage, site went down because Gen failed to start due to GE ba=
ttery faulty // he put site on Grid","Mboua Thierry","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Generator Battery","Grid outage, site went down b=
ecause Gen failed to start due to GE battery faulty // he put site on Grid"=
,"loic.noumsi@matech-cameroun.com","551","13-06-2025 17:06:12","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005246733","Eko=
umdoum OCM","","13-06-2025 17:02:09","13-06-2025 15:55:02","13-06-2025 17:2=
1:45","	Grid outage,site went down because Gen failed to start due to PWC Z=
TE dysfunction//He reset itand started the Gen manually","Albran Byorel","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","	Grid=
 outage,site went down because Gen failed to start due to PWC ZTE dysfuncti=
on//He reset itand started the Gen manually","loic.noumsi@matech-cameroun.c=
om","4028","13-06-2025 17:02:09","MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0005246711","Dag=
obert","","13-06-2025 16:58:25","13-06-2025 16:52:19","13-06-2025 19:10:09"=
,"Active: No power issue, site is on Grid with Ubaie=3D51,7V, FME TX Mohama=
dou//691144435 from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: No power issue, site is on Grid with Ubaie=3D51,7V, FME TX Moh=
amadou//691144435 from Huawei is informed.","loic.noumsi@matech-cameroun.co=
m","367","13-06-2025 16:58:25","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0005246703","N=
goulmekong-Nord","","13-06-2025 16:56:04","13-06-2025 16:44:28","13-06-2025=
 17:05:26","","Siligap Boris","Cascade Outage","Active","Cascade Active","C=
ascade Active","No power issue on site U=3D54,4 V site on grid The TX FME S=
YMPHORIEN (650257151) from HUAWEI is informed	","gaelle.njiofack@matech-cam=
eroun.com","271194","13-06-2025 16:56:04","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005246685","A=
wae Ewonkan","","13-06-2025 16:54:07","13-06-2025 16:48:54","13-06-2025 22:=
20:54","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid returned","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid r=
eturned","gaelle.njiofack@matech-cameroun.com","314","13-06-2025 16:54:07",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0005246672","E=
leveur","IHS_YND_277","13-06-2025 16:52:34","13-06-2025 16:44:28","13-06-20=
25 18:05:26","No power issue on site U=3D54,4 V site on grid The TX FME SYM=
PHORIEN (650257151) from HUAWEI is informed	","Siligap Boris","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site U=3D54,4 V site on grid The TX FME SYMPHORIEN (650257=
151) from HUAWEI is informed	","gaelle.njiofack@matech-cameroun.com","487",=
"13-06-2025 16:52:34","MATECH CMR"
"Closed Complete","Warning","CTR_079","IHS_YND_306","NOCINC0005246633","Nko=
zoa","","13-06-2025 16:46:06","","","Refuelling done","Fabrice Pouakam","Wa=
rning","Warning","DIESEL","Warning - Refuel","Refuelling done","loic.noumsi=
@matech-cameroun.com","4","13-06-2025 16:46:06","MATECH CMR"
"Closed Complete","Warning","CTR_086","IHS_YND_211","NOCINC0005246581","Eto=
udi 2","","13-06-2025 16:38:29","","","Refuelling done","Fabrice Pouakam","=
Warning","Warning","DIESEL","Warning - Refuel","Refuelling done","loic.noum=
si@matech-cameroun.com","4","13-06-2025 16:38:29","MATECH CMR"
"Closed Complete","Site Down","CTR_273","IHS_YND_214","NOCINC0005246559","N=
kolmesseng-II","","13-06-2025 16:35:20","13-06-2025 16:31:10","13-06-2025 1=
7:01:57","No power issue on site U=3D52,4 V site on grid The TX FME Armand =
Nguetsa /691144412 from huawei is informed","Siligap Boris","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site U=3D54,4 V site on grid The TX FME Armand Nguetsa /6911=
44412 from huawei is informed","gaelle.njiofack@matech-cameroun.com","250",=
"13-06-2025 16:35:20","MATECH CMR"
"Closed Complete","Warning","CTR_529","IHS_YND_316","NOCINC0005246558","Aka=
k-Nkozoa-MTN-IHS","","13-06-2025 16:35:12","","","Refuelling done","Fabrice=
 Pouakam","Warning","Warning","DIESEL","Warning - Refuel","Refuelling done"=
,"loic.noumsi@matech-cameroun.com","5","13-06-2025 16:35:12","MATECH CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0005246543","C=
hapelle-Essos","","13-06-2025 16:34:15","13-06-2025 16:29:07","13-06-2025 1=
8:05:22","No power issue on site U=3D54,1 V site on Grid The TX FME Armand =
Nguetsa /691144412 from huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site U=3D54,1 V site on Grid The TX FME Armand Nguetsa /691=
144412 from huawei is informed","gaelle.njiofack@matech-cameroun.com","309"=
,"13-06-2025 16:34:15","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005246539","N=
kozoa","","13-06-2025 16:33:51","13-06-2025 16:33:42","13-06-2025 16:34:45"=
,"Error ticket","Fabrice Pouakam","Incorrectly Logged Tickets","Error","Err=
or","Error","Error ticket","loic.noumsi@matech-cameroun.com","10","13-06-20=
25 16:33:51","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0005246456","S=
calom","","13-06-2025 16:26:24","13-06-2025 16:18:14","13-06-2025 16:59:54"=
,"Grid fluctuation, site went down because Gen start but didn't powered the=
 site due to ATS Dysfunction // ATS reset and site still on Gen","Paul BIBO=
UM","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid fluc=
tuation, site went down because Gen start but didn't powered the site due t=
o ATS Dysfunction // ATS reset and site still on Gen","gaelle.njiofack@mate=
ch-cameroun.com","491","13-06-2025 16:26:24","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005246432","Odz=
a Minkan IHS","","13-06-2025 16:22:43","13-06-2025 16:10:34","13-06-2025 16=
:30:09","Grid fluctuation, Site went down because Gen failed to start due t=
o Grid bad voltage// Grid return, site stabilised","Albran Byorel","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation, Site went down because Gen failed to start due to Grid bad voltage=
// Grid return, site stabilised","loic.noumsi@matech-cameroun.com","730","1=
3-06-2025 16:22:43","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005246023","N=
komo","","13-06-2025 15:36:15","13-06-2025 15:34:05","13-06-2025 21:28:05",=
"Grid outage,site went down because Gen failed to start due to PWC Overload=
(12k//280A)SS HIS Bateu is informed//He reduced the load and manually start=
ed the Gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage,site went down because Gen failed to start due t=
o PWC Overload(12k//280A)SS HIS Bateu is informed//He reduced the load and =
manually started the Gen","gaelle.njiofack@matech-cameroun.com","131","13-0=
6-2025 15:36:15","MATECH CMR"
"Closed Complete","Site Down","T1333","IHS_YND_174","NOCINC0005245955","Car=
refourt Nkomo","","13-06-2025 15:24:13","13-06-2025 15:14:59","13-06-2025 1=
7:30:54","Grid outage,Site went down because Gen failed to start due to Gri=
d contactor faulty // He bypassed it site on GE","Mba Lazare Herve","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage,Site =
went down because Gen failed to start due to Grid contactor malfunctioning =
// He bypassed it site on Grid","loic.noumsi@matech-cameroun.com","555","13=
-06-2025 15:24:13","MATECH CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0005245837","S=
calom-IHS","","13-06-2025 15:13:59","13-06-2025 15:07:05","13-06-2025 15:24=
:22","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Site went down due to disjunction of Circuit Breaker in the PWC // Circuit =
breaker rearm","gaelle.njiofack@matech-cameroun.com","262860","13-06-2025 1=
5:13:59","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0005245808","Sca=
lom","IHS_YND_505","13-06-2025 15:12:13","13-06-2025 15:07:05","13-06-2025 =
15:29:20","Site went down due to disjunction of Circuit Breaker in the PWC =
// Circuit breaker rearm","Paul BIBOUM","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to di=
sjunction of Circuit Breaker in the PWC // Circuit breaker rearm","loic.nou=
msi@matech-cameroun.com","309","13-06-2025 15:12:13","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005245581","M=
EHANDAN","","13-06-2025 14:43:47","13-06-2025 14:36:38","13-06-2025 18:00:4=
6","Site went down due to planne work (bay ZTE configuration) // End of wor=
k","Albran Byorel","Equipment Replacement","Passive","Planned Activity","Pl=
anned Activity - Passive","Site went down due to planne work (bay ZTE confi=
guration) // End of work","vanel.mbiada@matech-cameroun.com","432","13-06-2=
025 14:43:47","MATECH CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0005245534","I=
mm-Olympique","","13-06-2025 14:33:42","13-06-2025 14:20:33","13-06-2025 15=
:39:22","Grid outage,site went down because Gen failed to start due to Gen =
overload(20KVA//295A) SS HIS Raoul is informed//Grid returned","Paul BIBOUM=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,si=
te went down because Gen failed to start due to Gen overload(20KVA//295A) S=
S HIS Raoul is informed//Grid returned","vanel.mbiada@matech-cameroun.com",=
"790","13-06-2025 14:33:42","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005245472","Tou=
ring Club International","","13-06-2025 14:18:00","13-06-2025 14:16:44","13=
-06-2025 14:40:58","Grid outage, site went down due to poor backup battery =
// Site stabilised","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down due to poo=
r backup battery // Site stabilised","cedric.tiani@matech-cameroun.com","77=
","13-06-2025 14:18:00","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005245362","Odz=
a Minkan IHS","","13-06-2025 14:14:41","13-06-2025 14:11:33","13-06-2025 15=
:48:49","Grid bad voltage, Gen failed to start due to alarm oil pressure //=
 Gen card reset and Gen start manually","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid bad voltage, Gen faile=
d to start due to alarm oil pressure // Gen card reset and Gen start manual=
ly","cedric.tiani@matech-cameroun.com","190","13-06-2025 14:14:41","MATECH =
CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005245344","Ako=
k Ndoe Yde","","13-06-2025 14:09:39","13-06-2025 14:08:31","13-06-2025 14:1=
1:40","Grid outage site went down before gen start due to poor battery back=
up // Geen auatomatically started","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage site went =
down before gen start due to poor battery backup // Geen auatomatically sta=
rted","cedric.tiani@matech-cameroun.com","69","13-06-2025 14:09:39","MATECH=
 CMR"
"Closed Complete","Site Down","T1333","IHS_YND_174","NOCINC0005245309","Car=
refourt Nkomo","","13-06-2025 14:04:33","13-06-2025 13:58:12","13-06-2025 1=
4:10:48","Grid outage.site went don due to grid contactor dysfunctionned //=
We bypass it and gen manually started ","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage.site went don =
due to grid contactor dysfunctionned //We bypass it and gen manually starte=
d ","ludivine.ngamaleu@ihstowers.com","382","13-06-2025 14:04:33","MATECH C=
MR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005245257","M=
ANGUIERS CHAPELLE","","13-06-2025 13:56:25","13-06-2025 13:47:08","13-06-20=
25 14:40:39","fme is on the way ETA 14:40","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went do=
wn due to Gen overload (17KVA ; 160A) //He reduce load and site on Gen","va=
nel.mbiada@matech-cameroun.com","296174","13-06-2025 13:56:25","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005245237","M=
anguier","IHS_YND_509","13-06-2025 13:51:33","13-06-2025 13:47:08","13-06-2=
025 14:40:39","Grid outage, Site went down due to Gen overload (17KVA ; 160=
A) //He reduce load and site on Gen","Fabrice Pouakam","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to G=
en overload (17KVA ; 160A) //He reduce load and site on Gen","vanel.mbiada@=
matech-cameroun.com","630","13-06-2025 13:51:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_085","NOCINC0005245167","Briquete=
rie","","13-06-2025 13:40:22","13-06-2025 13:09:04","13-06-2025 13:44:03","=
Cascaded Incident from TTO5402184","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage .site went down and gen failed to st=
art due to gen overload(20kva,108A)//We reduce load and gen manually starte=
d ","system","298455","13-06-2025 13:40:22","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005245049","M=
anguier","IHS_YND_509","13-06-2025 13:18:16","13-06-2025 12:42:38","13-06-2=
025 13:30:04","Grid outage, Site went down due to Gen overload (17KVA ; 160=
A) //He reduce load and site on Gen","Fabrice Pouakam","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to G=
en overload (17KVA ; 160A) //He reduce load and site on Gen","vanel.mbiada@=
matech-cameroun.com","2138","13-06-2025 13:18:16","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005245023","GSO=
","","13-06-2025 13:14:54","13-06-2025 13:05:59","13-06-2025 14:09:30","Gri=
d outage.gen ran until fuel shortage//Refueling done","MINKA NICOLAS","Fuel=
 Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until fuel=
 shortage//Refueling done","cedric.tiani@matech-cameroun.com","536","13-06-=
2025 13:14:54","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005245004","Mey=
o","","13-06-2025 13:13:01","13-06-2025 13:08:51","13-06-2025 13:16:10","Gr=
id outage site went down due to Gen overload (17KVA, 240A) // Grid return",=
"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage site went down due to Gen overload (17KVA, 240A) // Grid retur=
n","cedric.tiani@matech-cameroun.com","251","13-06-2025 13:13:01","MATECH C=
MR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0005245002","E=
lobi Mokolo","","13-06-2025 13:12:48","13-06-2025 13:09:33","13-06-2025 13:=
10:20","Active//No power issue on site Ubaie=3D54,4 V; site on Grid tx fme =
BRICE Tsague/ 650214096 from huawie is informed","Mboua Thierry","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site Ubaie=3D55,2 V; site on Grid tx fme BRICE =
Tsague/ 650214096 from huawie is informed","vanel.mbiada@matech-cameroun.co=
m","196","13-06-2025 13:12:48","MATECH CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0005245000","N=
kolndongo","","13-06-2025 13:11:40","13-06-2025 13:00:27","13-06-2025 13:15=
:14","Grid outage site went down and gen failed to start //Grid return(inve=
stigation ongoing)","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage site went down and gen failed to start=
 //Grid return(investigation ongoing)","vanel.mbiada@matech-cameroun.com","=
674","13-06-2025 13:11:40","MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0005244991","K=
amajou Building","IHS_YND_085","13-06-2025 13:10:17","13-06-2025 13:09:04",=
"13-06-2025 14:02:03","Grid outage .site went down and gen failed to start =
due to gen overload(20kva,108A)//We reduce load and gen manually started ",=
"Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage .site went down and gen failed to start due to gen overload(20kva=
,108A)//We reduce load and gen manually started ","vanel.mbiada@matech-came=
roun.com","74","13-06-2025 13:10:17","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005244912","Mim=
boman4","","13-06-2025 13:00:34","13-06-2025 12:34:06","13-06-2025 13:00:13=
","Grid outage.site went down due to bad grid voltage//We bypass grid and g=
en manually started ","Mba Lazare Herve","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","Grid outage.site went down due to b=
ad grid voltage//We bypass grid and gen manually started ","cedric.tiani@ma=
tech-cameroun.com","1590","13-06-2025 13:00:34","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005244907","NKO=
MKANA ELIZA HOTEL","","13-06-2025 12:59:11","13-06-2025 12:31:57","13-06-20=
25 13:10:09","Grid outage .no space to deploy mobile gen//Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age .no space to deploy mobile gen//Grid return","ludivine.ngamaleu@ihstowe=
rs.com","1635","13-06-2025 12:59:11","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005244885","Nom=
ayos montee Meche","","13-06-2025 12:57:17","13-06-2025 12:56:02","13-06-20=
25 12:58:36","Grid outage site went down before gen start due to poor batte=
ry backup // Geen auatomatically started","Fanda Brice","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site w=
ent down before gen start due to poor battery backup // Geen auatomatically=
 started","cedric.tiani@matech-cameroun.com","76","13-06-2025 12:57:17","MA=
TECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005244881","Ako=
k Ndoe Yde","","13-06-2025 12:56:27","13-06-2025 12:55:13","13-06-2025 12:5=
7:33","Grid outage site went down before gen start due to poor battery back=
up // Geen auatomatically started","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage site went =
down before gen start due to poor battery backup // Geen auatomatically sta=
rted","cedric.tiani@matech-cameroun.com","75","13-06-2025 12:56:27","MATECH=
 CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005244874","Mok=
olo Yaounde","","13-06-2025 12:54:22","13-06-2025 12:31:08","13-06-2025 13:=
06:02","Site went down due to insufficient of rectifier on site SS IHS Bern=
ard is informed//He reset it and site on Grid","","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to insufficient of r=
ectifier on site SS IHS Bernard is informed//He reset it and site on Grid",=
"ludivine.ngamaleu@ihstowers.com","1396","13-06-2025 12:54:22","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005244873","O=
mnisport-Rail","","13-06-2025 12:53:52","13-06-2025 12:43:43","13-06-2025 1=
3:32:53","Grid outage.site went down due to gen overload(20kva,220 A)//We r=
educe load and gen manually started ","Delor Telezing","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage.site went down due to ge=
n overload(20kva,220 A)//We reduce load and gen manually started ","vanel.m=
biada@matech-cameroun.com","611","13-06-2025 12:53:52","MATECH CMR"
"Closed Complete","Site Down","T1549","IHS_YND_295","NOCINC0005244863","NGO=
NA","","13-06-2025 12:52:48","13-06-2025 12:45:42","13-06-2025 12:58:42","G=
rid outage, Site went down because Gen failed to start due to battery Gen f=
aulty// He started Gen with external battery","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, Site=
 went down because Gen failed to start due to battery Gen faulty// He start=
ed Gen with external battery","cedric.tiani@matech-cameroun.com","427","13-=
06-2025 12:52:48","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005244862","M=
ANGUIERS CHAPELLE","","13-06-2025 12:52:07","13-06-2025 12:42:38","13-06-20=
25 13:30:04","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Grid outage, Site went down due to Gen overload (17K=
VA ; 160A) //He reduce load and site on Gen","vanel.mbiada@matech-cameroun.=
com","271401","13-06-2025 12:52:07","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005244855","Fla=
menco","","13-06-2025 12:50:08","13-06-2025 12:45:54","13-06-2025 13:11:54"=
,"Grid outage .gen failed to start due to card GE dysfunctionning//We reset=
 card GE and gen manually started ","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage .gen failed to start d=
ue to card GE dysfunctionning//We reset card GE and gen manually started ",=
"cedric.tiani@matech-cameroun.com","255","13-06-2025 12:50:08","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0005244826","K=
oweit City","","13-06-2025 12:43:48","13-06-2025 12:41:38","13-06-2025 13:1=
1:51","Site went down due to planne work done by EPITECH(692288751)(Swapp o=
f PWC)//End of work ","Albran Byorel","Installation Activity","Passive","Pl=
anned Activity","Installation Activity","Site went down due to planne work =
done by EPITECH(692288751)(Swapp of PWC)//End of work ","vanel.mbiada@matec=
h-cameroun.com","131","13-06-2025 12:43:48","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0005244813","E=
kombitie","","13-06-2025 12:43:09","13-06-2025 12:39:00","13-06-2025 13:23:=
39","Grid outage,site went down CB(125A) of battery in PWC disjuncted due t=
o charge //He rearmed it  (Deep investigation ongoing)","Fabrice Pouakam","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breake=
r Issue","Grid outage,site went down CB(125A) of battery in PWC disjuncted =
due to charge //He rearmed it  (Deep investigation ongoing)","vanel.mbiada@=
matech-cameroun.com","251","13-06-2025 12:43:09","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0005244806","Imm=
-Olympique","","13-06-2025 12:41:57","13-06-2025 12:32:49","13-06-2025 13:3=
7:00","Grid outage,site went down because Gen failed to start due to Gen ov=
erload(20KVA//295A) SS HIS Raoul is informed//Grid return","Paul BIBOUM","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,site w=
ent down because Gen failed to start due to Gen overload(20KVA//295A) SS HI=
S Raoul is informed//Grid return","cedric.tiani@matech-cameroun.com","549",=
"13-06-2025 12:41:57","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005244805","A=
bom","IHS_YND_269","13-06-2025 12:41:49","13-06-2025 12:35:37","13-06-2025 =
13:05:21","Grid outage, Site went down because Gen failed to start due to G=
en Overload (16KVA /300A) // Grid return","Siligap Boris","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen failed to start due to Gen Overload (16KVA /300A) // Grid return","v=
anel.mbiada@matech-cameroun.com","373","13-06-2025 12:41:49","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005244801","M=
endong vallee","","13-06-2025 12:41:13","13-06-2025 12:35:02","13-06-2025 1=
2:59:02","Grid outage site went down because Gen over load (20KVA; 300A) IH=
S F=E9lix Zamb=E9 is informed and confirmed //Grid return","Fanda Brice","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site w=
ent down because Gen over load (20KVA; 300A) IHS F=E9lix Zamb=E9 is informe=
d and confirmed //Grid return","vanel.mbiada@matech-cameroun.com","373","13=
-06-2025 12:41:13","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005244797","Nko=
lbong","","13-06-2025 12:41:10","13-06-2025 12:31:52","13-06-2025 13:09:41"=
,"Grid outage,Site went Down because Gen started and stopped due to Gen ove=
rload(22kva//350A) //Grid returned","Delor Telezing","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen=
 started and stopped due to Gen overload(22kva//350A) //Grid returned","ced=
ric.tiani@matech-cameroun.com","559","13-06-2025 12:41:10","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005244789","F=
ouda-New","","13-06-2025 12:40:39","13-06-2025 12:35:29","13-06-2025 14:06:=
06","Grid outage.gen failed to start due to solenoid faulty//Gen manually s=
tarted ","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - S=
olenoid Coil","Grid outage.gen failed to start due to solenoid faulty//Gen =
manually started ","vanel.mbiada@matech-cameroun.com","311","13-06-2025 12:=
40:39","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005244780","M=
vog-Ebanda","","13-06-2025 12:39:49","13-06-2025 12:35:37","13-06-2025 13:0=
5:21","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, Site went down because Gen failed to start due t=
o Gen Overload (16KVA /300A) // Grid return","vanel.mbiada@matech-cameroun.=
com","264596","13-06-2025 12:39:49","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005244776","C=
omplexe-BEAC","","13-06-2025 12:38:57","13-06-2025 12:31:43","13-06-2025 13=
:30:11","Site went down due to Circuit breaker of battery disjuncted //We r=
earmed CB and site on grid ","Albran Byorel","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down due =
to Circuit breaker of battery disjuncted //We rearmed CB and site on grid "=
,"vanel.mbiada@matech-cameroun.com","435","13-06-2025 12:38:57","MATECH CMR=
"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005244775","OBA=
M NGOLA OCM","","13-06-2025 12:38:29","13-06-2025 12:30:50","13-06-2025 12:=
58:02","Grid outage.gen failed to start due to card GE dysfunctionning //We=
 rest card GE and gen manually started ","MINKA NICOLAS","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to sta=
rt due to card GE dysfunctionning //We rest card GE and gen manually starte=
d ","cedric.tiani@matech-cameroun.com","460","13-06-2025 12:38:29","MATECH =
CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005244770","M=
vog-Ada_OCM","","13-06-2025 12:38:02","13-06-2025 12:31:54","13-06-2025 12:=
57:58","Grid Only site, No space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only sit=
e, No space to deploy MDGE // Grid returned","vanel.mbiada@matech-cameroun.=
com","369","13-06-2025 12:38:02","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005244765","E=
MANA BILICK CITY","","13-06-2025 12:37:32","13-06-2025 12:31:11","13-06-202=
5 13:12:56","Access issues due to landlord(Landlord has forbidden to start =
the Gen due to noise)//Grid return","Fabrice Pouakam","Access Denial","Leas=
e Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access is=
sues due to landlord(Landlord has forbidden to start the Gen due to noise)/=
/Grid return","vanel.mbiada@matech-cameroun.com","382","13-06-2025 12:37:32=
","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005244754","M=
ontee-Des-Soeurs","","13-06-2025 12:36:30","13-06-2025 12:30:19","13-06-202=
5 13:02:32","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) //=
 Grid returned","vanel.mbiada@matech-cameroun.com","372","13-06-2025 12:36:=
30","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005244753","Cit=
e des nations","","13-06-2025 12:36:23","13-06-2025 12:29:10","13-06-2025 1=
2:35:27","Grid outage,site went down before Gen started due to Poor battery=
 backup//Gen automatically started","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage,site went do=
wn before Gen started due to Poor battery backup//Gen automatically started=
","cedric.tiani@matech-cameroun.com","434","13-06-2025 12:36:23","MATECH CM=
R"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005244751","M=
essassi okolo","","13-06-2025 12:35:55","13-06-2025 12:30:46","13-06-2025 1=
3:09:27","Grid outage gen start and stopped due to low oil pressure //We ad=
d oil and gen manually started","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Low Oil Pressure","Grid outage gen start and stopped=
 due to low oil pressure //We add oil and gen manually started","vanel.mbia=
da@matech-cameroun.com","310","13-06-2025 12:35:55","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005244747","N=
koabang2","","13-06-2025 12:35:22","13-06-2025 12:29:15","13-06-2025 12:57:=
34","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","va=
nel.mbiada@matech-cameroun.com","369","13-06-2025 12:35:22","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005244744","Sim=
e Building","","13-06-2025 12:34:42","13-06-2025 12:29:28","13-06-2025 13:1=
1:58","Grid outage; site went down due to Poor battery backup // Gen starte=
d automatically","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage; site went down due to Poor b=
attery backup // Gen started automatically","cedric.tiani@matech-cameroun.c=
om","315","13-06-2025 12:34:42","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005244714","Eto=
udi","","13-06-2025 12:31:46","13-06-2025 12:30:37","13-06-2025 12:31:57","=
Grid fluctuation,site went down because Gen failed to start due to grid bad=
 voltage//Grid return","Fabrice Pouakam","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","Grid fluctuation,site went down bec=
ause Gen failed to start due to grid bad voltage//Grid return","cedric.tian=
i@matech-cameroun.com","70","13-06-2025 12:31:46","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005244710","Ron=
d Point Express1114","","13-06-2025 12:31:10","13-06-2025 12:29:58","13-06-=
2025 13:11:49","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","ce=
dric.tiani@matech-cameroun.com","72","13-06-2025 12:31:10","MATECH CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0005244691","Nsi=
meyong Terre Rouge","","13-06-2025 12:29:50","13-06-2025 12:29:44","13-06-2=
025 12:31:46","Grid outage, site went down before gen start due to poor bat=
tery backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Grid return","cedric.tiani@mat=
ech-cameroun.com","7","13-06-2025 12:29:50","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0005244674","Meh=
anda 1","","13-06-2025 12:25:37","13-06-2025 12:24:26","13-06-2025 15:04:20=
","Grid outage gen failed to start due to alarm ""undervoltage""//We reset =
card GE and gen manually started ","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to start due=
 to alarm ""undervoltage""//We reset card GE and gen manually started ","ce=
dric.tiani@matech-cameroun.com","72","13-06-2025 12:25:37","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005244525","Eki=
e sud","","13-06-2025 12:02:28","13-06-2025 11:58:09","13-06-2025 12:46:40"=
,"Grid outage ,Site went down due to PWC ZTE dysfunction//He reset it and s=
ite on Grid","Albran Byorel","Equipment Repair","Passive","Rectifier","Rect=
ifier Module Overloaded","Grid outage ,Site went down due to PWC ZTE dysfun=
ction//He reset it and site on Grid","cedric.tiani@matech-cameroun.com","26=
0","13-06-2025 12:02:28","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005244517","Mim=
boman4","","13-06-2025 12:01:15","13-06-2025 11:55:05","13-06-2025 12:01:37=
","No power issue U=3D52.8V site on Grid. TX FME Leonel Steve// 655184876//=
 / from huawei is informed.Site up 12:01 PM","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue U=3D52.8V site on Grid. TX FME Leonel Steve// 655184876// /=
 from huawei is informed.Site up 12:01 PM","cedric.tiani@matech-cameroun.co=
m","371","13-06-2025 12:01:15","MATECH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005244215","N=
omayos-IHS","","13-06-2025 11:20:26","13-06-2025 11:18:16","13-06-2025 11:3=
1:11","No power issue on site Ubaie 54.5V site on Grid; TX FME Flubert (654=
266068/Huawei) is informed ","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on si=
te Ubaie 54.5V site on Grid; TX FME Flubert (654266068/Huawei) is informed =
","vanel.mbiada@matech-cameroun.com","131","13-06-2025 11:20:26","MATECH CM=
R"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005243802","M=
essassi okolo","","13-06-2025 10:03:19","13-06-2025 09:16:51","13-06-2025 1=
0:26:14","Grid outage gen start and stopped due to low oil pressure //We ad=
d oil and gen manually started ","Fabrice Pouakam","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage gen start and stoppe=
d due to low oil pressure //We add oil and gen manually started ","vanel.mb=
iada@matech-cameroun.com","2790","13-06-2025 10:03:19","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005243768","M=
endong vallee","","13-06-2025 09:57:28","13-06-2025 09:54:39","13-06-2025 1=
1:47:48","Grid outage,Site went down due to Gen overload (20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed and confirmed // Grid return","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site we=
nt down due to Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed a=
nd confirmed // Grid return","vanel.mbiada@matech-cameroun.com","171","13-0=
6-2025 09:57:28","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005243642","S=
atcom","","13-06-2025 09:33:21","13-06-2025 09:15:12","13-06-2025 09:45:56"=
,"	Active // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand=
 Ngestsa (691144412) of huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	A=
ctive // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand Nge=
stsa (691144412) of huawei is informed","vanel.mbiada@matech-cameroun.com",=
"1090","13-06-2025 09:33:21","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0005243627","E=
kombitie","","13-06-2025 09:31:50","13-06-2025 09:29:29","13-06-2025 10:43:=
24","Grid outage,site went down CB(125A) of battery in PWC disjuncted due t=
o charge //He rearmed it  (Deep investigation ongoing)","Fabrice Pouakam","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breake=
r Issue","Grid outage,site went down CB(125A) of battery in PWC disjuncted =
due to charge //He rearmed it  (Deep investigation ongoing)","vanel.mbiada@=
matech-cameroun.com","142","13-06-2025 09:31:50","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005243577","Tou=
ring Club International","","13-06-2025 09:27:07","13-06-2025 09:22:55","13=
-06-2025 09:36:13","Grid outage,gen ran till fuel shortage//Refueling done"=
,"Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age,gen ran till fuel shortage//Refueling done","cedric.tiani@matech-camero=
un.com","253","13-06-2025 09:27:07","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005243571","O=
dza II OCM","","13-06-2025 09:26:21","13-06-2025 09:23:00","13-06-2025 09:2=
6:29","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","vanel.mbiada@matech-cameroun.com","203","13-06-2025 09:26:21"=
,"MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005243570","Ako=
k Ndoe Yde","","13-06-2025 09:26:15","13-06-2025 09:24:09","13-06-2025 09:2=
7:14","Grid outage, Site went down before Gen start due to poor backup// Ge=
n automatically  Started","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen automatically  Started","cedric.tian=
i@matech-cameroun.com","127","13-06-2025 09:26:15","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005243558","HOP=
ITAL DE LA CAISSE","","13-06-2025 09:25:01","13-06-2025 09:18:16","13-06-20=
25 09:20:17","Grid outage, Site went down before Gen start due to poor back=
up// Gen automatically  Started","Delor Telezing","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup// Gen automatically  Started","cedr=
ic.tiani@matech-cameroun.com","405","13-06-2025 09:25:01","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0005243539","Imm=
-Olympique","","13-06-2025 09:23:09","13-06-2025 09:21:46","13-06-2025 10:4=
3:38","Grid outage,site went down because Gen failed to start due to Gen ov=
erload(20KVA//295A) SS HIS Raoul is informed//Grid return","Paul BIBOUM","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,site w=
ent down because Gen failed to start due to Gen overload(20KVA//295A) SS HI=
S Raoul is informed//Grid return","cedric.tiani@matech-cameroun.com","84","=
13-06-2025 09:23:09","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005243534","EMA=
NA BILICK CITY","","13-06-2025 09:22:17","13-06-2025 09:21:09","13-06-2025 =
10:31:10","Access issues due to landlord(Landlord has forbidden to start th=
e Gen due to noise)//  Grid return","Fabrice Pouakam","Access Denial","Leas=
e Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access is=
sues due to landlord(Landlord has forbidden to start the Gen due to noise)/=
/  Grid return","cedric.tiani@matech-cameroun.com","69","13-06-2025 09:22:1=
7","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005243532","Men=
dong Plateau","","13-06-2025 09:21:51","13-06-2025 09:19:42","13-06-2025 09=
:21:18","No power issue site on grid with U=3D51.2v site up at 09:21 AM Mba=
h Osiah from Huawei was informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on grid with U=3D51.2v site up at 09:21 AM Mbah Osiah from Huawei w=
as informed","cedric.tiani@matech-cameroun.com","129","13-06-2025 09:21:51"=
,"MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005243529","Eko=
umdoum OCM","","13-06-2025 09:21:27","13-06-2025 09:19:19","13-06-2025 09:5=
9:06","Grid outage,site went down because Gen failed to start due to PWC ZT=
E dysfunction//He reset itand  started the Gen manually","Albran Byorel","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage,site went down because Gen failed to start due to PWC ZTE dysfunctio=
n//He reset itand  started the Gen manually","cedric.tiani@matech-cameroun.=
com","129","13-06-2025 09:21:27","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005243528","Nko=
lbong","","13-06-2025 09:20:57","13-06-2025 09:17:39","13-06-2025 10:26:47"=
,"Grid outage,Site went Down because Gen started and stopped due to Gen ove=
rload(22kva//350A) //Grid returned","Delor Telezing","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage,Site went Down because Gen=
 started and stopped due to Gen overload(22kva//350A) //Grid returned","ced=
ric.tiani@matech-cameroun.com","199","13-06-2025 09:20:57","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005243526","OBA=
M NGOLA OCM","","13-06-2025 09:20:14","13-06-2025 09:17:06","13-06-2025 09:=
59:36","Grid outage,site went down because Gen failed to start due to Gen c=
ard faulty//Grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid outage,site went down because Gen failed=
 to start due to Gen card faulty//Grid return","cedric.tiani@matech-camerou=
n.com","190","13-06-2025 09:20:14","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0005243524","Nko=
mo","","13-06-2025 09:19:50","13-06-2025 09:16:41","13-06-2025 09:22:36","G=
rid outage,site went down because Gen failed to start due to PWC Overload(1=
2k//280A)SS HIS Bateu is informed//He reduiced the load and manually starte=
d the Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Grid outage,site went down because Gen failed to=
 start due to PWC Overload(12k//280A)SS HIS Bateu is informed//He reduiced =
the load and manually started the Gen","cedric.tiani@matech-cameroun.com","=
190","13-06-2025 09:19:50","MATECH CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0005243506","Nsi=
meyong Terre Rouge","","13-06-2025 09:17:34","13-06-2025 09:15:22","13-06-2=
025 09:17:43","Grid outage, Site went downt before Gen start due to poor ba=
ttery backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, Site went downt =
before Gen start due to poor battery backup // Grid return","cedric.tiani@m=
atech-cameroun.com","133","13-06-2025 09:17:34","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005243353","C=
arrefourt Nkomo","","13-06-2025 08:55:19","13-06-2025 08:54:10","13-06-2025=
 08:55:57","No power issue site on grid with U=3D54.7 v Lionnel Steeve from=
 Huawei is informed","Mba Lazare Herve","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D54.7 v Lionnel Steeve from Huawei is informed","vanel.mbiada@=
matech-cameroun.com","70","13-06-2025 08:55:19","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0005243250","Tou=
ring Club International","","13-06-2025 08:38:47","13-06-2025 08:34:29","13=
-06-2025 08:58:07","Grid outage,gen ran till fuel shortage//Refueling done"=
,"Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age,gen ran till fuel shortage//Refueling done","cedric.tiani@matech-camero=
un.com","259","13-06-2025 08:38:47","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005242950","C=
-Supreme","","13-06-2025 07:21:31","13-06-2025 07:19:17","13-06-2025 07:21:=
48","Site went down due to 02/04 rectifiers dysfunctionning on site//Site s=
tabilised","","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down due to 02/04 rectifiers dysfunctionning on site//Site stabil=
ised","vanel.mbiada@matech-cameroun.com","135","13-06-2025 07:21:31","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005242816","ELOUMDEM=
 CARRIERE 2","","13-06-2025 06:43:35","13-06-2025 06:41:05","13-06-2025 06:=
47:55","Cascaded Incident from TTO5399741","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","system","=
264391","13-06-2025 06:43:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005242815","Eto koss=
 Yde","","13-06-2025 06:43:35","13-06-2025 06:41:05","13-06-2025 06:47:55",=
"Cascaded Incident from TTO5399741","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","system","264392"=
,"13-06-2025 06:43:35","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005242813","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","13-06-2025 06:42:32","13-06-2025 06:41=
:05","13-06-2025 06:47:55","Grid outage, Site went down before Gen start du=
e to poor backup // Gen started automatically","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","cedric.tiani@matech-cameroun.com","89","13-06-2025 06:42:32","MATECH=
 CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0005242064","Meh=
anda 1","","13-06-2025 03:57:38","13-06-2025 03:48:59","13-06-2025 07:41:05=
","Access issue at night due to landlord. Grid outage.site went down becaus=
e Gen failed to start due to grid bad voltage //We bypass grid and gen manu=
ally started","Albran Byorel","Access Denial","Lease Or Legal","Landlord Re=
lated Issues","Access Issue - Land Lord","Access issue at night due to land=
lord. Grid outage.site went down because Gen failed to start due to grid ba=
d voltage //We bypass grid and gen manually started","franck.nkomot@matech-=
cameroun.com","519","13-06-2025 03:57:38","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005241883","Nko=
g-Edzen","","13-06-2025 02:52:40","13-06-2025 02:42:59","13-06-2025 02:45:5=
9","Active//No power issue on site, Site on Grid Ubay =3D 56.4V The Tx Fme =
Gregoire (654547479) from Huawei is informed","Parker Tchoup","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site, Site on Grid Ubay =3D 56.4V The Tx Fme Grego=
ire (654547479) from Huawei is informed","franck.nkomot@matech-cameroun.com=
","831","13-06-2025 02:52:40","MATECH CMR"
"Closed Complete","Warning","T1259","IHS_YND_424","NOCINC0005241707","Ossom=
be","","13-06-2025 01:52:06","","","The site was in alarm due to the startu=
p failure at its threshold // The Gen has started","Parker Tchoup","Warning=
","Warning","POWER","Warning - Site on Battery","The site was in alarm due =
to the startup failure at its threshold // The Gen has started","franck.nko=
mot@matech-cameroun.com","268","13-06-2025 01:52:06","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005241423","M=
endong vallee","","13-06-2025 00:25:53","13-06-2025 00:24:07","13-06-2025 0=
0:53:01","Grid outage,Site went down due to Gen overload (20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed and confirmed  // Grid returned","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site=
 went down due to Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informe=
d and confirmed  // Grid returned","gaelle.njiofack@matech-cameroun.com","1=
07","13-06-2025 00:25:53","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005241295","O=
LAMA","","12-06-2025 23:58:05","12-06-2025 23:50:56","12-06-2025 23:54:55",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.9V site on Gen The TX FME Henri (699949693) from Huawei is=
 informed.","gaelle.njiofack@matech-cameroun.com","430","12-06-2025 23:58:0=
5","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005241243","Aha=
la Echangeur","","12-06-2025 23:42:54","12-06-2025 23:40:24","13-06-2025 07=
:00:32","Access issue at night due to landlord.Grid fluctuation,site went d=
own because Gen failed to start due to grid bad voltage//He made a bridge w=
ith the good phase","MINKA NICOLAS","Access Denial","Lease Or Legal","Landl=
ord Related Issues","Access Issue - Land Lord","Access issue at night due t=
o landlord.Grid fluctuation,site went down because Gen failed to start due =
to grid bad voltage//He made a bridge with the good phase","franck.nkomot@m=
atech-cameroun.com","151","12-06-2025 23:42:54","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005240973","Eki=
e sud","","12-06-2025 22:47:24","12-06-2025 22:37:59","12-06-2025 22:44:59"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage// Site stabilized","Albran Byorel","Grid Supply","Passive","Grid=
","National Grid - Grid Outage Issue","Grid fluctuation, Site went down bec=
ause gen fails to start due to grid bad voltage// Site stabilized","franck.=
nkomot@matech-cameroun.com","566","12-06-2025 22:47:24","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005240907","M=
endong vallee","","12-06-2025 22:30:55","12-06-2025 22:29:23","12-06-2025 2=
3:24:17","Grid outage,Site went down due to Gen overload (20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed and confirmed  // Grid returned","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site=
 went down due to Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informe=
d and confirmed  // Grid returned","gaelle.njiofack@matech-cameroun.com","9=
4","12-06-2025 22:30:55","MATECH CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0005240794","N=
gousso-II","","12-06-2025 22:02:23","12-06-2025 21:55:11","12-06-2025 22:36=
:31","site went down due to disjunction at PWC //  CB rearmed","MFOUAGUEGUE=
 MATHIEU","Equipment Repair","Passive","Control Panel","Circuit Breaker Tri=
pped","site went down due to disjunction at PWC //  CB rearmed","gaelle.nji=
ofack@matech-cameroun.com","432","12-06-2025 22:02:23","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005240689","Mam=
ch Building","","12-06-2025 21:40:23","12-06-2025 21:33:11","12-06-2025 22:=
30:11","Site went down because gen stopped with low oil pressure//he added =
oil and started the gen","Mboua Thierry","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Low Oil Pressure","Site went down because gen stopped with lo=
w oil pressure//he added oil and started the gen","gaelle.njiofack@matech-c=
ameroun.com","433","12-06-2025 21:40:23","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005240680","A=
wae Ewonkan","","12-06-2025 21:38:14","12-06-2025 21:36:43","12-06-2025 21:=
52:29","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid returned","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid r=
eturned","gaelle.njiofack@matech-cameroun.com","93","12-06-2025 21:38:14","=
MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005240595","Aha=
la Echangeur","","12-06-2025 21:22:34","12-06-2025 21:00:26","12-06-2025 22=
:46:26","Site went down because gen stopped with low oil pressure//he added=
 oil and started the gen","MINKA NICOLAS","Equipment Repair","Passive","ACD=
G Gen","ACDG - Low Oil Pressure","Site went down because gen stopped with l=
ow oil pressure//he added oil and started the gen","gaelle.njiofack@matech-=
cameroun.com","1329","12-06-2025 21:22:34","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005240577","Eki=
e sud","","12-06-2025 21:21:11","12-06-2025 21:06:01","12-06-2025 22:14:20"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage// He bypasse the Grid and site on Gen","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, Site went down because gen fails to start due to grid bad voltage//=
 He bypasse the Grid and site on Gen","gaelle.njiofack@matech-cameroun.com"=
,"911","12-06-2025 21:21:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005240399","Carrefou=
r Ayissi Ele","","12-06-2025 20:53:27","12-06-2025 20:42:25","12-06-2025 20=
:56:45","Cascaded Incident from TTO5397096","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n due to work (reset of relay siemens)  // End of work","system","264158","=
12-06-2025 20:53:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005240400","Nkol-Meb=
anga","","12-06-2025 20:53:27","12-06-2025 20:42:25","12-06-2025 20:56:45",=
"Cascaded Incident from TTO5397096","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 work (reset of relay siemens)  // End of work","system","264158","12-06-20=
25 20:53:27","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005240372","S=
aa","IHS_YND_810, IHS_YND_809, IHS_YND_404","12-06-2025 20:49:31","12-06-20=
25 20:42:25","12-06-2025 20:56:57","Grid outage, Site went down due to work=
 (reset of relay siemens)  // End of work","Parker Tchoup","Equipment Repla=
cement","Passive","Planned Activity","Planned Activity - Passive","Grid out=
age, Site went down due to work (reset of relay siemens)  // End of work","=
gaelle.njiofack@matech-cameroun.com","427","12-06-2025 20:49:31","MATECH CM=
R"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0005240357","S=
AA 2","","12-06-2025 20:46:08","12-06-2025 20:42:25","12-06-2025 20:56:57",=
"","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage, Site went down due to work (reset of relay siemens)  /=
/ End of work","gaelle.njiofack@matech-cameroun.com","1220621","12-06-2025 =
20:46:08","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005240300","OBA=
M NGOLA OCM","","12-06-2025 20:37:40","12-06-2025 20:32:33","12-06-2025 20:=
40:35","Grid outage, site went down because Gen failed to started due to Ge=
n card faulty // Site stabilised","MINKA NICOLAS","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
Gen failed to started due to Gen card faulty // Site stabilised","loic.noum=
si@matech-cameroun.com","308","12-06-2025 20:37:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005240073","FOUGEROL=
E","","12-06-2025 20:10:18","12-06-2025 20:06:30","12-06-2025 22:07:19","Ca=
scaded Incident from TTO5396758","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to disjuncted in t=
he PWC,  Second C80 departure replaced by a C125. //  CB  rearmed ","system=
","295019","12-06-2025 20:10:18","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005240066","N=
gousso-Savana","IHS_YND_561","12-06-2025 20:09:35","12-06-2025 20:06:30","1=
2-06-2025 22:11:17","Site went down due to disjuncted in the PWC,  Second C=
80 departure replaced by a C125. //  CB  rearmed ","Siligap Boris","Equipme=
nt Repair","Passive","Control Panel","Circuit Breaker Tripped","Site went d=
own due to disjuncted in the PWC,  Second C80 departure replaced by a C125.=
 //  CB  rearmed ","loic.noumsi@matech-cameroun.com","186","12-06-2025 20:0=
9:35","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0005239896","Eto=
 koss Yde","","12-06-2025 19:36:09","12-06-2025 19:31:04","12-06-2025 20:32=
:36","Grid outage, Site went down because Gen failed to start due to gen co=
ntactor faulty // He bypassed contactor and connected Gen directly on load"=
,"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contact=
or","Grid outage, Site went down because Gen failed to start due to gen con=
tactor faulty // He bypassed contactor and connected Gen directly on load",=
"loic.noumsi@matech-cameroun.com","307","12-06-2025 19:36:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0005239892","Donga","=
","12-06-2025 19:35:40","12-06-2025 19:23:17","12-06-2025 19:30:01","Cascad=
ed Incident from TTO5396557","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Batchenga that it's not man=
aged by IHS","system","261800","12-06-2025 19:35:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0005239893","Dong",""=
,"12-06-2025 19:35:40","12-06-2025 19:23:17","12-06-2025 19:30:01","Cascade=
d Incident from TTO5396557","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Site impacted by Batchenga that it's not mana=
ged by IHS","system","261799","12-06-2025 19:35:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0005239891","Nguila",=
"","12-06-2025 19:35:39","12-06-2025 19:23:17","12-06-2025 19:30:01","Casca=
ded Incident from TTO5396557","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Site impacted by Batchenga that it's not ma=
naged by IHS","system","261800","12-06-2025 19:35:39","MATECH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0005239872","O=
ssombe","IHS_YND_433, IHS_YND_434, IHS_YND_444","12-06-2025 19:32:27","12-0=
6-2025 19:23:17","12-06-2025 19:30:01","Site impacted by Batchenga that it'=
s not managed by IHS","Parker Tchoup","Customer Equipment Failure","Active"=
,"Active Equipment Failure","Affected by 3rd Party Site","Site impacted by =
Batchenga that it's not managed by IHS","loic.noumsi@matech-cameroun.com","=
551","12-06-2025 19:32:27","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005239636","NKO=
MKANA ELIZA HOTEL","","12-06-2025 18:46:04","12-06-2025 18:44:58","12-06-20=
25 18:46:28","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","loic.noumsi@matech-c=
ameroun.com","67","12-06-2025 18:46:04","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005239631","O=
dza II OCM","","12-06-2025 18:44:19","12-06-2025 18:42:06","12-06-2025 18:5=
0:52","	Grid fluctuations, site went down because gen failed to start due t=
o PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","	Grid fluctuations, =
site went down because gen failed to start due to PWC ZTE malfunction // Gr=
id stabilized","gaelle.njiofack@matech-cameroun.com","135","12-06-2025 18:4=
4:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005239482","Emana Ly=
cee","","12-06-2025 18:25:14","12-06-2025 18:20:56","12-06-2025 20:27:59","=
Cascaded Incident from TTO5396101","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down becau=
se Gen started and stopped due to Gen overload(20kva, 260A) // He reduced t=
he load","system","279754","12-06-2025 18:25:14","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005239477","E=
mana lycee 2","IHS_YND_274","12-06-2025 18:24:07","12-06-2025 18:20:56","12=
-06-2025 20:27:59","Grid outage, Site went down because Gen started and sto=
pped due to Gen overload(20kva, 260A) // He reduced the load","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
, Site went down because Gen started and stopped due to Gen overload(20kva,=
 260A) // He reduced the load","loic.noumsi@matech-cameroun.com","193","12-=
06-2025 18:24:07","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005239142","A=
wae Escalier","","12-06-2025 17:39:59","12-06-2025 17:30:52","12-06-2025 18=
:14:35","Grid outage, site went down because Gen failed to start due to Gri=
d contactor faulty // He activated Grid contactor , site on Gen","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid=
 outage, site went down because Gen failed to start due to Grid contactor f=
aulty // He activated Grid contactor , site on Gen","loic.noumsi@matech-cam=
eroun.com","548","12-06-2025 17:39:59","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005239034","S=
atcom","","12-06-2025 17:24:09","12-06-2025 17:19:01","12-06-2025 19:27:35"=
,"Active // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand =
Ngestsa (691144412) of huawei is informed","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand Ngest=
sa (691144412) of huawei is informed","loic.noumsi@matech-cameroun.com","30=
9","12-06-2025 17:24:09","MATECH CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0005238724","BIY=
EM ASSI LYCEE","","12-06-2025 16:30:26","12-06-2025 16:26:36","12-06-2025 1=
9:33:16","Active//No power issue on site U=3D54.8V site on grid Tx Fme MBAH=
 osiah (674007438) of huawei is informed","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site U=3D54.8V site on grid Tx Fme MBAH osiah (674007=
438) of huawei is informed","loic.noumsi@matech-cameroun.com","230","12-06-=
2025 16:30:26","MATECH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005238683","N=
omayos-IHS","","12-06-2025 16:21:48","12-06-2025 16:07:37","12-06-2025 18:1=
0:27","No power issue on site Ubaie 54.5V site on Grid; TX FME Flubert (654=
266068/Huawei) is informed and was on site for PM","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site Ubaie 54.5V site on Grid; TX FME Flubert (65426606=
8/Huawei) is informed and was on site for PM","gaelle.njiofack@matech-camer=
oun.com","852","12-06-2025 16:21:48","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005238679","O=
LAMA","","12-06-2025 16:20:23","12-06-2025 16:14:18","12-06-2025 18:31:16",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.9V site on Gen The TX FME Henri (699949693) from Huawei is=
 informed.","gaelle.njiofack@matech-cameroun.com","366","12-06-2025 16:20:2=
3","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0005238616","Obobogo"=
,"","12-06-2025 16:13:15","12-06-2025 16:06:08","12-06-2025 16:13:00","Casc=
aded Incident from TTO5395128","MINKA NICOLAS","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by Efoulan Pont which is not=
 managed by IHS","system","266334","12-06-2025 16:13:15","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005238604","E=
foulan","IHS_YND_155","12-06-2025 16:12:18","12-06-2025 16:06:08","12-06-20=
25 16:13:00","Site impacted by Efoulan Pont which is not managed by IHS","M=
INKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failu=
re","Affected by 3rd Party Site","Site impacted by Efoulan Pont which is no=
t managed by IHS","gaelle.njiofack@matech-cameroun.com","370","12-06-2025 1=
6:12:18","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0005238575","Men=
dong vallee","","12-06-2025 16:06:49","12-06-2025 15:59:39","12-06-2025 17:=
21:46","Grid outage,Site went down due to Gen overload (20KVA; 300A) IHS F=
=E9lix Zamb=E9 is informed and confirmed//He reduced the load and manually =
started the Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage,Site went down due to Gen overload (20KVA; 300A)=
 IHS F=E9lix Zamb=E9 is informed and confirmed//He reduced the load and man=
ually started the Gen","loic.noumsi@matech-cameroun.com","431","12-06-2025 =
16:06:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005238429","MEHANDAN=
","","12-06-2025 15:46:14","12-06-2025 15:38:16","12-06-2025 15:52:59","Cas=
caded Incident from TTO5394912","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to PWC=
 ZTE dysfunctionment // He reset it and reduced load, site on Gen","system"=
,"267989","12-06-2025 15:46:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0005238428","Odza II =
OCM","","12-06-2025 15:46:14","12-06-2025 15:38:16","12-06-2025 15:52:59","=
Cascaded Incident from TTO5394912","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
PWC ZTE dysfunctionment // He reset it and reduced load, site on Gen","syst=
em","267989","12-06-2025 15:46:14","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005238419","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","12-06-2025 15:44:27","12=
-06-2025 15:38:16","12-06-2025 15:52:59","Grid outage, site went down due t=
o PWC ZTE dysfunctionment // He reset it and reduced load, site on Gen","Al=
bran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Ove=
rloaded","Grid outage, site went down due to PWC ZTE dysfunctionment // He =
reset it and reduced load, site on Gen","gaelle.njiofack@matech-cameroun.co=
m","372","12-06-2025 15:44:27","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005238409","E=
koumdoum OCM","","12-06-2025 15:43:28","12-06-2025 15:38:16","12-06-2025 15=
:52:59","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, site went down due to PWC ZTE dysfunctionment =
// He reset it and reduced load, site on Gen","loic.noumsi@matech-cameroun.=
com","267988","12-06-2025 15:43:28","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005237992","OBA=
M NGOLA OCM","","12-06-2025 14:52:05","12-06-2025 14:46:00","12-06-2025 15:=
48:07","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty // He reset gen card and gen manually started","MINKA NICOLA=
S","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, site went down because Gen failed to started due to Gen card faullty /=
/ He reset gen card and gen manually started","cedric.tiani@matech-cameroun=
.com","366","12-06-2025 14:52:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_163","NOCINC0005237989","Nsam Sof=
avinc","IHS_YND_732","12-06-2025 14:51:44","12-06-2025 14:45:07","12-06-202=
5 14:51:31","Grid outage, site went down before Gen started due to poor bac=
kup // Grid returned","MINKA NICOLAS","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, site went down before G=
en started due to poor backup // Grid returned","system","397","12-06-2025 =
14:51:44","MATECH CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0005237987","Nsa=
m escale LP","","12-06-2025 14:51:14","12-06-2025 14:45:07","12-06-2025 14:=
51:31","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"cascaded site","cedric.tiani@matech-cameroun.com","264051","12-06-2025 14=
:51:14","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005237981","O=
dza II OCM","","12-06-2025 14:49:26","12-06-2025 14:46:17","12-06-2025 14:5=
0:29","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","gaelle.njiofack@matech-cameroun.com","192","12-06-2025 14:49:=
26","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005237720","Nko=
lbisson IITA LP","","12-06-2025 14:22:51","12-06-2025 14:19:42","12-06-2025=
 19:35:09","Grid only site, no space to deploy MDGE // Grid returned","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only=
 site, no space to deploy MDGE // Grid returned","cedric.tiani@matech-camer=
oun.com","190","12-06-2025 14:22:51","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005237719","F=
ouda-New","","12-06-2025 14:22:40","12-06-2025 14:20:30","12-06-2025 14:22:=
49","Grid outage, Site went down due to Grid bad voltage and Gen failed to =
start automatically // He did bridge on the good phase, site on Grid","Delo=
r Telezing","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid outage, Site went down because Gen failed to start automati=
cally and Grid bad voltage // He did bridge on the good phase, site on Grid=
","vanel.mbiada@matech-cameroun.com","130","12-06-2025 14:22:40","MATECH CM=
R"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0005237718","Nsi=
meyong Terre Rouge","","12-06-2025 14:22:20","12-06-2025 14:21:11","12-06-2=
025 14:23:08","Grid outage, Site went downt before Gen start due to poor ba=
ttery backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, Site went downt =
before Gen start due to poor battery backup // Grid return","cedric.tiani@m=
atech-cameroun.com","70","12-06-2025 14:22:20","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005237115","A=
wae Ewonkan","","12-06-2025 12:59:32","12-06-2025 12:58:09","12-06-2025 13:=
01:53","	Grid outage site went down due to Gen Overload (20Kva, Iload 225 A=
)IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","	Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid r=
eturn","vanel.mbiada@matech-cameroun.com","85","12-06-2025 12:59:32","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005236857","SAA 2","=
","12-06-2025 12:36:01","12-06-2025 12:19:49","12-06-2025 12:30:21","Cascad=
ed Incident from TTO5393137","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubaie1: 54.2 V site o=
n GEN. GREGLOIRE  (652070658/Huawei) is informed. Site up wthout interventi=
on","system","265683","12-06-2025 12:36:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0005236856","Saa","",=
"12-06-2025 12:36:01","12-06-2025 12:19:49","12-06-2025 12:30:21","Cascaded=
 Incident from TTO5393137","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site Ubaie1: 54.2 V site on =
GEN. GREGLOIRE  (652070658/Huawei) is informed. Site up wthout intervention=
","system","265681","12-06-2025 12:36:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0005236853","Okola OC=
M","","12-06-2025 12:36:00","12-06-2025 12:19:49","12-06-2025 12:30:21","Ca=
scaded Incident from TTO5393137","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue on site Ubaie1=
: 54.2 V site on GEN. GREGLOIRE  (652070658/Huawei) is informed. Site up wt=
hout intervention","system","265681","12-06-2025 12:36:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0005236848","Monatele=
","","12-06-2025 12:36:00","12-06-2025 12:19:49","12-06-2025 12:30:21","Cas=
caded Incident from TTO5393137","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubaie1: 54.2 V sit=
e on GEN. GREGLOIRE  (652070658/Huawei) is informed. Site up wthout interve=
ntion","system","265678","12-06-2025 12:36:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0005236850","Talla Mo=
natele","","12-06-2025 12:36:00","12-06-2025 12:19:49","12-06-2025 12:30:21=
","Cascaded Incident from TTO5393137","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue on site Ubaie1: 54.2=
 V site on GEN. GREGLOIRE  (652070658/Huawei) is informed. Site up wthout i=
ntervention","system","265680","12-06-2025 12:36:00","MATECH CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0005236671","N=
yanon","","12-06-2025 12:17:45","09-06-2025 21:55:17","09-06-2025 22:00:05"=
,"Backtracking No power issues on site U=3D55.5V Site on Gen","TIENTCHEU NZ=
ETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","No power issues on site U=3D55.5V Site on Gen","c=
edric.tiani@matech-cameroun.com","224548","12-06-2025 12:17:45","MATECH CMR=
"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005236339","NYO=
M 2 IHS","","12-06-2025 11:40:27","09-06-2025 22:04:49","10-06-2025 00:13:5=
2","Backtracking Site went down because Gen failed to start due to PWC ZTE =
 dysfunction due to grid fluctuation//He reset it and site on GEN","Fabrice=
 Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Overlo=
aded","Site went down because Gen failed to start due to PWC ZTE  dysfuncti=
on due to grid fluctuation//He reset it and site on GEN","cedric.tiani@mate=
ch-cameroun.com","221738","12-06-2025 11:40:27","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005236140","E=
mana lycee 2","","12-06-2025 11:16:51","12-06-2025 11:14:37","12-06-2025 11=
:16:54","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 260A) // He reduced the load","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Grid outage, Site =
went down because Gen started and stopped due to Gen overload(20kva, 260A) =
// He reduced the load","vanel.mbiada@matech-cameroun.com","136","12-06-202=
5 11:16:51","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005236035","NTU=
I TOWN","","12-06-2025 11:00:14","12-06-2025 10:58:27","12-06-2025 11:00:24=
","Active: No power issue, site is on grid with Ubaie=3D54.1V, Gregoire (65=
2070658) from Huawei is informed","Parker Tchoup","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No po=
wer issue, site is on grid with Ubaie=3D54.1V, Gregoire (652070658) from Hu=
awei is informed","cedric.tiani@matech-cameroun.com","110","12-06-2025 11:0=
0:14","MATECH CMR"
"Closed Complete","Site Down","T1085","IHS_YND_130","NOCINC0005235953","Bas=
tos usine","","12-06-2025 10:51:34","11-06-2025 07:03:08","11-06-2025 09:31=
:13","Backtracking  No power issue, site is on grid with Ubaie=3D53.3V;Elou=
ndou(652586578) from Huawei is informed","Mboua Thierry","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No po=
wer issue, site is on grid with Ubaie=3D53.3V;Eloundou(652586578) from Huaw=
ei is informed","cedric.tiani@matech-cameroun.com","100106","12-06-2025 10:=
51:34","MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0005235928","Nko=
lmvack","","12-06-2025 10:47:07","12-06-2025 10:44:59","12-06-2025 11:42:20=
","Grid outage, Site went down because Gen start and stopped with ""High te=
mps ""alarm due to radiator pierced // he added water and manually start th=
e Gen","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High=
 Engine Temp - Coolant Level Issue","Grid outage, Site went down because Ge=
n start and stopped with ""High temps ""alarm due to radiator pierced // he=
 added water and manually start the Gen","cedric.tiani@matech-cameroun.com"=
,"129","12-06-2025 10:47:07","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005235908","Mam=
ch Building","","12-06-2025 10:42:32","12-06-2025 10:35:15","12-06-2025 11:=
10:09","Grid outage, site went down because gen start and stopper with alar=
m * Overcurrent* // He reduiced the battery frames and manually started Gen=
 ","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid outage, site went down because gen start and stopper with alar=
m * Overcurrent* // He reduiced the battery frames and manually started Gen=
 ","cedric.tiani@matech-cameroun.com","438","12-06-2025 10:42:32","MATECH C=
MR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005235861","S=
atcom","","12-06-2025 10:34:45","12-06-2025 10:32:36","12-06-2025 10:41:57"=
,"Active // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand =
Ngestsa (691144412) of huawei is informed","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand Ngest=
sa (691144412) of huawei is informed","vanel.mbiada@matech-cameroun.com","1=
30","12-06-2025 10:34:45","MATECH CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0005235728","A=
RMP","","12-06-2025 10:18:30","12-06-2025 10:14:22","12-06-2025 10:21:55","=
Site went down due to plan work (swap of Ubaie) done by FME Migance TANKO (=
650631368/DOWEN SERVICE) // End of work","","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to plan w=
ork (swap of Ubaie) done by FME Migance TANKO (650631368/DOWEN SERVICE) // =
End of work","vanel.mbiada@matech-cameroun.com","249","12-06-2025 10:18:30"=
,"MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005235498","Mok=
olo Yaounde","","12-06-2025 09:29:16","12-06-2025 09:27:07","12-06-2025 11:=
08:53","(Unsatable site)site went down due to MPR dysfunction and one recti=
fier alarming//Site stabilised","","Equipment Repair","Passive","Rectifier"=
,"Rectifier Cabinet",")site went down due to MPR dysfunction and one rectif=
ier alarming//Site stabilised","cedric.tiani@matech-cameroun.com","130","12=
-06-2025 09:29:16","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005235248","E=
ssomba","","12-06-2025 08:36:48","12-06-2025 08:34:20","12-06-2025 22:27:20=
","(Unstable site) Site went down because PWC overload // Grid returned","M=
ba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","(Unstable site) Site went down because PWC overload // Grid r=
eturned","vanel.mbiada@matech-cameroun.com","149","12-06-2025 08:36:48","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005235210","M=
elen Ba'aba","","12-06-2025 08:27:24","12-06-2025 08:25:11","12-06-2025 09:=
00:30","Grid outage.gen ran until fuel shortage//Refueling done","Siligap B=
oris","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran=
 until fuel shortage//Refueling done","vanel.mbiada@matech-cameroun.com","1=
34","12-06-2025 08:27:24","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005234795","O=
dza II OCM","","12-06-2025 06:45:20","12-06-2025 06:38:14","12-06-2025 06:4=
6:19","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","vanel.mbiada@matech-cameroun.com","428","12-06-2025 06:45:20"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005234718","N=
koabang Ebolmedjock","","12-06-2025 06:16:11","12-06-2025 06:13:03","12-06-=
2025 07:00:06","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Gen. Notice that it is impacted b=
y Nkolmesseng-Abom(CTR-711) Not Manager By IHS","edwige.kapawo@matech-camer=
oun.com","189","12-06-2025 06:16:11","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005234619","ELO=
UMDEM CARRIERE","","12-06-2025 05:47:47","12-06-2025 05:40:32","12-06-2025 =
06:21:04","Grid outage,site went down because Gen failed to start de to Gen=
 overload(9KVA)//He reduced the battery frames and manually started the Gen=
","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage,site went down because Gen failed to start de to Gen overload(9=
KVA)//He reduced the battery frames and manually started the Gen","edwige.k=
apawo@matech-cameroun.com","436","12-06-2025 05:47:47","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005234433","ELO=
UMDEM CARRIERE","","12-06-2025 04:42:55","12-06-2025 04:33:38","12-06-2025 =
05:30:14","Grid outage,site went down because Gen failed to start de to Gen=
 overload(9KVA)//Grid return","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage,site went down because Gen failed t=
o start de to Gen overload(9KVA)//Grid return","gerard.tchangoue@matech-cam=
eroun.com","558","12-06-2025 04:42:55","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005234321","S=
tade-Abega","","12-06-2025 03:48:33","12-06-2025 03:47:20","12-06-2025 03:5=
2:25","Site impacted by EKounou_II","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","Affected by 3rd Party Site","=
Site impacted by EKounou_II","edwige.kapawo@matech-cameroun.com","198","12-=
06-2025 03:48:33","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005234174","N=
koabang2","","12-06-2025 02:44:39","12-06-2025 02:42:33","12-06-2025 02:45:=
42","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Site stabilised","Mba Lazare Herve","Equipment Repair=
","Passive","Rectifier","Rectifier Module","Grid outage, site went down due=
 to gen overload (22KVA, 330A), SS Blaise IHS is informed // Site stabilise=
d","edwige.kapawo@matech-cameroun.com","128","12-06-2025 02:44:39","MATECH =
CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0005234154","Mes=
sassi okolo","","12-06-2025 02:36:11","12-06-2025 02:34:03","12-06-2025 02:=
44:57","Grid outage , site went down before Gen started due to poor battery=
 backup// Grid power return","Fabrice Pouakam","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage , site went dow=
n before Gen started due to poor battery backup// Grid power return","gerar=
d.tchangoue@matech-cameroun.com","129","12-06-2025 02:36:11","MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0005234081","Mes=
sassi okolo","","12-06-2025 02:12:42","12-06-2025 02:10:35","12-06-2025 02:=
22:07","Grid outage , site went down before Gen started due to poor battery=
 backup// Grid power return","Fabrice Pouakam","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage , site went dow=
n before Gen started due to poor battery backup// Grid power return","gerar=
d.tchangoue@matech-cameroun.com","128","12-06-2025 02:12:42","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005234041","Eki=
e sud","","12-06-2025 01:52:43","12-06-2025 01:51:34","12-06-2025 02:49:48"=
,"Site went Down due to Gen Overvoltage // He Reset it and reduced battery =
charge","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
r Voltage","Site went Down due to Gen Overvoltage // He Reset it and reduce=
d battery charge","gerard.tchangoue@matech-cameroun.com","70","12-06-2025 0=
1:52:43","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005233893","EKI=
E","","12-06-2025 00:55:52","12-06-2025 00:52:39","12-06-2025 02:03:26","Si=
te went down because gen fails to start due to grid bad voltage // He bypas=
s grid and manually start the gen","Albran Byorel","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Site went down because ge=
n fails to start due to grid bad voltage // He bypass grid and manually sta=
rt the gen","gerard.tchangoue@matech-cameroun.com","193","12-06-2025 00:55:=
52","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0005233744","Eto=
 koss Yde","","11-06-2025 23:56:13","11-06-2025 23:52:05","12-06-2025 01:30=
:06","Grid outage, Site went down because Gen failed to start due to gen co=
ntactor not excited // He excited gen contactor ad manually started the  ge=
n","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Load Conta=
ctor","Grid outage, Site went down because Gen failed to start due to gen c=
ontactor not excited // He excited gen contactor ad manually started the  g=
en","gerard.tchangoue@matech-cameroun.com","250","11-06-2025 23:56:13","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005233741","M=
endong vallee","","11-06-2025 23:55:53","11-06-2025 23:50:45","12-06-2025 1=
0:20:23","Grid outage,Site went down due to Gen overload (20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed and confirmed//He reduiced the load and manuall=
y started the Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage,Site went down due to Gen overload (20KVA; 300=
A) IHS F=E9lix Zamb=E9 is informed and confirmed//He reduiced the load and =
manually started the Gen","edwige.kapawo@matech-cameroun.com","309","11-06-=
2025 23:55:53","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005233677","OBA=
M NGOLA OCM","","11-06-2025 23:34:34","11-06-2025 23:29:26","11-06-2025 23:=
35:26","Site went down due to insufficient of rectifier on site//Site stabi=
lized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down due to insufficient of rectifier on site//Site stab=
ilized","gerard.tchangoue@matech-cameroun.com","309","11-06-2025 23:34:34",=
"MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005233516","NYO=
M FACE MAETUR","","11-06-2025 22:54:40","11-06-2025 22:54:33","11-06-2025 2=
2:56:33","Site went down because Gen failed to start due to Relay (220V) fa=
ulty // He replaced it and Gen manually started","Fabrice Pouakam","Equipme=
nt Repair","Passive","Control Panel","ATS Relay Faulty","Site went down bec=
ause Gen failed to start due to Relay (220V) faulty // He replaced it and G=
en manually started","gerard.tchangoue@matech-cameroun.com","8","11-06-2025=
 22:54:40","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005233437","Eto=
ug ebe biscuiterie","","11-06-2025 22:36:23","11-06-2025 22:35:18","12-06-2=
025 01:05:36","Grid outage, site went down because gen start and stopped wi=
th Under voltage alarm // he Reset the Gen card and gen started","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Under Voltage","Grid=
 outage, site went down because gen start and stopped with Under voltage al=
arm // he Reset the Gen card and gen started","gerard.tchangoue@matech-came=
roun.com","66","11-06-2025 22:36:23","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005233262","ODZ=
A MINKAN EDIBI ASSI","","11-06-2025 22:24:51","11-06-2025 22:15:39","12-06-=
2025 00:38:35","Grid outage, Site went down before Gen start due to poor ba=
ckup// Gen Manually Started","Albran Byorel","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down b=
efore Gen start due to poor backup// Gen Manually Started","gerard.tchangou=
e@matech-cameroun.com","553","11-06-2025 22:24:51","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005233152","M=
eyo","","11-06-2025 22:08:06","11-06-2025 22:07:57","11-06-2025 22:36:19","=
Grid outage, site went down due to Gen overload (17KVA, 260A) SS HIS Felix =
Zambe is informed and confirmed // Grid return","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went dow=
n due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and conf=
irmed // Grid return","christelle.ngonga@matech-cameroun.com","10","11-06-2=
025 22:08:06","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005233117","ELO=
UMDEM CARRIERE 2","","11-06-2025 22:02:51","11-06-2025 20:22:33","11-06-202=
5 23:08:46","Site went down due to disjunction of Cb(125A) in PWC // He rea=
med Cb(125A), site on grid","Fanda Brice","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to =
disjunction of Cb(125A) in PWC // He reamed Cb(125A), site on grid","franck=
.nkomot@matech-cameroun.com","6020","11-06-2025 22:02:51","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005233085","O=
dza-PK10","","11-06-2025 21:58:10","11-06-2025 21:56:04","11-06-2025 22:22:=
04","Site went down because Gen stopped due to disfunction of PWC // He res=
et gen and started manualy","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","Site went down because Gen stopped=
 due to disfunction of PWC // He reset gen and started manualy","christelle=
.ngonga@matech-cameroun.com","127","11-06-2025 21:58:10","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005233077","Odz=
a Minkan IHS","","11-06-2025 21:56:39","11-06-2025 21:47:31","12-06-2025 00=
:49:13","Site went down due to Cb(50A) in PWC malfunction // He reamed Cb(5=
0A) , site on grid","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Circuit Breaker Issue","Site went down due to Cb(50A=
) in PWC malfunction // He reamed Cb(50A) , site on grid","franck.nkomot@ma=
tech-cameroun.com","549","11-06-2025 21:56:39","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0005233071","Nko=
lbisson usines des eaux 2","","11-06-2025 21:56:03","11-06-2025 21:46:59","=
11-06-2025 23:20:14","Access issue during the night , Grid Outage // Grid r=
eturn","TIENTCHEU NZETCHIEU GAEL","Access Denial","Lease Or Legal","Landlor=
d Related Issues","Access Issue - Land Lord","Access issue during the night=
 , Grid Outage // Grid return","franck.nkomot@matech-cameroun.com","545","1=
1-06-2025 21:56:03","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005233062","Mes=
sassi 2","","11-06-2025 21:53:06","11-06-2025 21:11:59","12-06-2025 00:21:5=
8","Grid outage site went down because Gen failed to start due PWC ZTE dysf=
onctionned // He reset the PWC and Gen manually started","Fabrice Pouakam",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gri=
d outage site went down because Gen failed to start due PWC ZTE dysfonction=
ned // He reset the PWC and Gen manually started","franck.nkomot@matech-cam=
eroun.com","2469","11-06-2025 21:53:06","MATECH CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0005233044","S=
OA UNIVERSITY STADIUM","","11-06-2025 21:49:24","11-06-2025 21:48:18","11-0=
6-2025 22:28:10","Grid Outage. Site went down because Gen failed to start  =
due to Gen card Malfuction // he Reset the Gen Card and Manually Started th=
e Gen","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid outage, site went down because gen failed to start due to =
Pwc ZTE dysfunction// Grid return","christelle.ngonga@matech-cameroun.com",=
"67","11-06-2025 21:49:24","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005233031","M=
EHANDAN","","11-06-2025 21:46:17","11-06-2025 21:15:10","12-06-2025 00:44:5=
7","Site went down because Gen stopped due to disfunction of PWC // He rese=
t gen and started manualy","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because Gen stopped =
due to disfunction of PWC // He reset gen and started manualy","christelle.=
ngonga@matech-cameroun.com","1868","11-06-2025 21:46:17","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005233028","MBA=
LNGONG LYCEE","","11-06-2025 21:45:25","11-06-2025 21:41:18","12-06-2025 11=
:33:55","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed //He reduced the loaad and manual=
ly started the Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Site went down because Gen stopped due to overload(9kva, =
130A) SS IHS Felix Zambe is informed and confirmed //He reduced the loaad a=
nd manually started the Gen","franck.nkomot@matech-cameroun.com","249","11-=
06-2025 21:45:25","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005232994","C=
hapelle-Nsimeyong","","11-06-2025 21:39:31","11-06-2025 21:39:26","11-06-20=
25 22:42:48","Grid outage, Site went down because Gen failed to start due t=
o Gen card disfunction// He reset Gen card and started Gen manually","MINKA=
 NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, Site went down because Gen failed to start due to Gen card disf=
unction// He reset Gen card and started Gen manually","christelle.ngonga@ma=
tech-cameroun.com","6","11-06-2025 21:39:31","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005232967","N=
omayos montee Meche","","11-06-2025 21:33:35","11-06-2025 21:32:29","11-06-=
2025 22:44:52","Grid outage, site went down before gen start due to poor ba=
ttery backup // Gen start automatically","Fanda Brice","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup // Gen start automatic=
ally","christelle.ngonga@matech-cameroun.com","67","11-06-2025 21:33:35","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0005232944","N=
omayos","","11-06-2025 21:29:16","11-06-2025 21:28:11","11-06-2025 21:29:14=
","Grid outage, Site went down before Gen start due to poor backup // Gen s=
tarted automatically","Fanda Brice","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen started automatically","christelle.ngonga@=
matech-cameroun.com","66","11-06-2025 21:29:16","MATECH CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0005232935","L=
eboudi","","11-06-2025 21:27:32","11-06-2025 21:23:36","11-06-2025 21:32:41=
","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade Active",=
"Cascade Active","No power issue site on grid zith U=3D54v Mohamadou from H=
uawei is informed","christelle.ngonga@matech-cameroun.com","1268595","11-06=
-2025 21:27:32","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0005232926","N=
kolafeme","IHS_YND_309","11-06-2025 21:26:42","11-06-2025 21:23:36","11-06-=
2025 21:32:41","No power issue site on grid zith U=3D54v Mohamadou from Hua=
wei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on grid zith U=3D54v Mohamadou from Huawei is informed","christelle.ngonga=
@matech-cameroun.com","187","11-06-2025 21:26:42","MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0005232919","Dag=
obert","","11-06-2025 21:25:35","11-06-2025 21:23:29","11-06-2025 23:10:30"=
,"Active: No power issue, site is on Grid with Ubaie=3D54,9V, FME TX Mohama=
dou//691144435 from Huawei is informed. ","TIENTCHEU NZETCHIEU GAEL","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active: No power issue, site is on Grid with Ubaie=3D54,9V, FME TX Mo=
hamadou//691144435 from Huawei is informed. ","franck.nkomot@matech-camerou=
n.com","126","11-06-2025 21:25:35","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005232908","SIM=
BOCK BONAMBAPE","","11-06-2025 21:24:25","11-06-2025 21:21:13","11-06-2025 =
21:25:56","Grid Outage, Site went down before Gen start due to poor backup =
// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid Outage, Site went down before Gen st=
art due to poor backup // Grid return","franck.nkomot@matech-cameroun.com",=
"192","11-06-2025 21:24:25","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0005232888","Aba=
ng","","11-06-2025 21:22:50","11-06-2025 21:16:34","11-06-2025 23:07:05","A=
ctive//No power issue site on Grid with U=3D54.9V ,The FME TX Henri (691145=
055) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue site on Grid with U=3D54.9V ,The FME TX Henri (691145055) from Hua=
wei is informed","franck.nkomot@matech-cameroun.com","377","11-06-2025 21:2=
2:50","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005232881","Nko=
langaa","","11-06-2025 21:21:14","11-06-2025 21:16:40","11-06-2025 21:26:40=
","ACTIVE//no power issue on site U=3D52:9 V site on Grid Lionnel Tchatchou=
//694693436 from Huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","Affected by 3rd Party Site",=
"ACTIVE//no power issue on site U=3D52:9 V site on Grid Lionnel Tchatchou//=
694693436 from Huawei is informed","franck.nkomot@matech-cameroun.com","275=
","11-06-2025 21:21:14","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005232872","Nko=
ulou Carriere carrefourt","","11-06-2025 21:20:18","11-06-2025 21:17:02","1=
1-06-2025 21:32:24","Grid outage, Site went down due to insufficiency of re=
ctifiers//Grid return","Mba Lazare Herve","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Grid outage, Site went down due to insufficienc=
y of rectifiers//Grid return","franck.nkomot@matech-cameroun.com","197","11=
-06-2025 21:20:18","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005232870","S=
tade-Abega","","11-06-2025 21:20:09","11-06-2025 21:19:02","11-06-2025 21:3=
9:18","Grid outage, site went down because gen failed to start due to Pwc Z=
TE dysfunction // Grid return","Mba Lazare Herve","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Grid outage, site went down =
because gen failed to start due to Pwc ZTE dysfunction // Grid return","chr=
istelle.ngonga@matech-cameroun.com","68","11-06-2025 21:20:09","MATECH CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0005232867","C=
hapelle-Essos","","11-06-2025 21:19:16","11-06-2025 21:17:09","11-06-2025 2=
1:20:29","Active // No power issue on site ,site on Grid with Ubaie=3D53.1 =
V The Tx FME Armand Nguetsa /699949553// from huawei is informed","Delor Te=
lezing","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active // No power issue on site ,site on Grid with Uba=
ie=3D53.1 V The Tx FME Armand Nguetsa /699949553// from huawei is informed"=
,"christelle.ngonga@matech-cameroun.com","127","11-06-2025 21:19:16","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005232858","C=
omplexe-BEAC","","11-06-2025 21:17:41","11-06-2025 21:14:35","11-06-2025 22=
:38:58","Grid Outage site went down because gen failed to start due to  CB(=
100A) of Battery Disjuncted //  he Reamed it and Manually started the Gen",=
"Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet=
 - Circuit Breaker Issue","Grid Outage site went down because gen failed to=
 start due to  CB(100A) of Battery Disjuncted //  he Reamed it and Manually=
 started the Gen","christelle.ngonga@matech-cameroun.com","187","11-06-2025=
 21:17:41","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005232855","E=
mana lycee 2","","11-06-2025 21:17:09","11-06-2025 21:14:03","11-06-2025 22=
:17:34","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 260A) // He reduced the load","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went=
 down because Gen started and stopped due to Gen overload(20kva, 260A) // H=
e reduced the load","christelle.ngonga@matech-cameroun.com","187","11-06-20=
25 21:17:09","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005232850","E=
koumdoum OCM","","11-06-2025 21:16:19","11-06-2025 21:12:12","11-06-2025 23=
:04:33","Grid outage, Site went down because Gen failed to start due to PWC=
 dysfunctionning // Grid return","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, Site went down b=
ecause Gen failed to start due to PWC dysfunctionning // Grid return","chri=
stelle.ngonga@matech-cameroun.com","248","11-06-2025 21:16:19","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0005232840","Ema=
na Lycee","","11-06-2025 21:14:32","11-06-2025 21:12:26","11-06-2025 21:18:=
26","Active //  No power issue site on grid with U=3D54v TX FME Symphorien(=
691316854) from Huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
  No power issue site on grid with U=3D54v TX FME Symphorien(691316854) fro=
m Huawei is informed","franck.nkomot@matech-cameroun.com","127","11-06-2025=
 21:14:32","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005232821","Mok=
olo Yaounde","","11-06-2025 21:11:53","11-06-2025 21:08:41","11-06-2025 21:=
16:50","Active // No power issue Ubay: 52.2 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 52.2 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","franck.nkomot@matech-cameroun.com","193"=
,"11-06-2025 21:11:53","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005232809","Ron=
d Point Express1114","","11-06-2025 21:10:07","11-06-2025 21:06:46","11-06-=
2025 21:24:46","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Grid return","franck.nkomot@matech-cameroun.=
com","202","11-06-2025 21:10:07","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005232806","N=
YOM 2 IHS","","11-06-2025 21:09:47","11-06-2025 21:08:40","11-06-2025 21:14=
:35","Site went down because the PWC OF ZTE dysfonction // He reset the PWC=
","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down because the PWC OF ZTE dysfonction // He re=
set the PWC","christelle.ngonga@matech-cameroun.com","68","11-06-2025 21:09=
:47","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005232805","A=
wae Ewonkan","","11-06-2025 21:09:21","11-06-2025 21:08:01","12-06-2025 02:=
43:12","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","christelle.ngonga@matech-cameroun.com","82","11-06-2025 21:09:21","MA=
TECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005232802","Ebo=
go","","11-06-2025 21:09:03","11-06-2025 21:01:51","11-06-2025 21:11:51","N=
o power issue on site U=3D52,1V site on grid Synphorien 675295205 of Huawei=
 is informed","Siligap Boris","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52,1V =
site on grid Synphorien 675295205 of Huawei is informed","franck.nkomot@mat=
ech-cameroun.com","433","11-06-2025 21:09:03","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0005232799","Eko=
mbitie","","11-06-2025 21:08:02","11-06-2025 21:03:56","11-06-2025 21:10:48=
","Active// No power issue on site ,site on Grid with Ubaie=3D52.1 V The Tx=
 FME Synphorien /691316854//from huawei is informed","Fabrice Pouakam","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active// No power issue on site ,site on Grid with Ubaie=3D52.1 V T=
he Tx FME Synphorien /691316854//from huawei is informed","franck.nkomot@ma=
tech-cameroun.com","248","11-06-2025 21:08:02","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005232788","E=
MANA BILICK CITY","IHS_YND_279","11-06-2025 21:06:45","11-06-2025 21:03:39"=
,"11-06-2025 22:30:15","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid returned","Fabrice Pouakam","Access Denial",=
"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid=
 outage, site down because site behaves as Grid only site (Gen Noise) // Gr=
id returned","christelle.ngonga@matech-cameroun.com","187","11-06-2025 21:0=
6:45","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005232787","N=
kolbong","","11-06-2025 21:06:01","11-06-2025 21:01:54","11-06-2025 22:25:0=
8","Grid outage, Site went down due to Gen overload(22kva//350A) // Grid re=
turn","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, Site went down due to Gen overload(22kva//350A) // Grid=
 return","christelle.ngonga@matech-cameroun.com","248","11-06-2025 21:06:01=
","MATECH CMR"
"Closed Complete","Warning","CTR_599","IHS_YND_279","NOCINC0005232784","Mes=
sassi okolo","","11-06-2025 21:05:21","","","Grid fluctuation,site went dow=
n because Gen failed to start due to bad voltage//He started the Gen manual=
ly","Fabrice Pouakam","Warning","Warning","POWER","Warning - National Grid =
- Grid Incomplete Phase","Grid outage , site went down before Gen started d=
ue to poor battery backup // Grid return","christelle.ngonga@matech-camerou=
n.com","254","11-06-2025 21:05:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005232727","Eseka To=
wn","","11-06-2025 20:52:39","11-06-2025 05:44:36","11-06-2025 05:58:00","C=
ascaded Incident from TTO5388572","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue U=3D53.27V site on Gen=
 The Tx FME Etienne FOPA /695033981/ From HUAWEI is informed","system","325=
176","11-06-2025 20:52:39","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005232723","E=
seka OCM","IHS_YND_378","11-06-2025 20:51:49","11-06-2025 05:44:36","11-06-=
2025 05:58:00","No power issue U=3D53.27V site on Gen The Tx FME Etienne FO=
PA /695033981/ From HUAWEI is informed","Kemeni Franklin","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue U=3D53.27V site on Gen The Tx FME Etienne FOPA /695033981/ From H=
UAWEI is informed","christelle.ngonga@matech-cameroun.com","54433","11-06-2=
025 20:51:49","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005232682","C=
-Supreme","","11-06-2025 20:45:01","10-06-2025 10:59:48","10-06-2025 11:07:=
21","Active // No power issue, site on Battery with Ubaie=3D56.9V, Brice Ts=
ague (650 21 40 96 / Huawei) is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power=
 issue, site on Battery with Ubaie=3D56.9V, Brice Tsague (650 21 40 96 / Hu=
awei) is informed","christelle.ngonga@matech-cameroun.com","121514","11-06-=
2025 20:45:01","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005232523","N=
gousso-Savana","IHS_YND_561","11-06-2025 20:22:58","11-06-2025 20:14:51","1=
1-06-2025 23:36:42","Active // No power issue, site is on grid with Ubaie: =
52.4V, Armand Nguetsa (699949553) from Huawei is informed.a C125 circuit br=
eaker burned out in the BTS OCM.","Siligap Boris","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No =
power issue, site is on grid with Ubaie: 52.4V, Armand Nguetsa (699949553) =
from Huawei is informed.a C125 circuit breaker burned out in the BTS OCM.",=
"christelle.ngonga@matech-cameroun.com","488","11-06-2025 20:22:58","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005232518","F=
OUGEROLE","","11-06-2025 20:22:11","11-06-2025 20:14:51","11-06-2025 22:26:=
42","","Siligap Boris","Cascade Outage","Active","Cascade Active","Cascade =
Active","Active // No power issue, site is on grid with Ubaie: 52.4V, Arman=
d Nguetsa (699949553) from Huawei is informed.a C125 circuit breaker burned=
 out in the BTS OCM.","christelle.ngonga@matech-cameroun.com","280157","11-=
06-2025 20:22:11","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005231988","O=
dza-PK10","","11-06-2025 18:43:12","11-06-2025 18:38:04","11-06-2025 18:59:=
47","Grid outage, site went down due to PWC ZTE dysfunctionment // Grid res=
toration","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Grid outage, site went down due to PWC ZTE dysfuncti=
onment // Grid restoration","christelle.ngonga@matech-cameroun.com","308","=
11-06-2025 18:43:12","MATECH CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0005231965","BIY=
EM ASSI LYCEE","","11-06-2025 18:38:52","11-06-2025 18:30:45","11-06-2025 1=
8:32:45","No power issue on site U=3D54.8V site on grid Tx Fme MBAH osiah (=
674007438) of huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site U=3D54.8V site on grid Tx Fme MBAH osiah (674007438) of huawei i=
s informed","franck.nkomot@matech-cameroun.com","488","11-06-2025 18:38:52"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0005231958","A=
RMP","","11-06-2025 18:37:33","11-06-2025 18:34:26","11-06-2025 18:41:26","=
No power issue on site Ubaie=3D54.5V site on Grid The Tx Fme Eloundou/69321=
2405 of huawei is informed.","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie=3D=
54.5V site on Grid The Tx Fme Eloundou/693212405 of huawei is informed.","c=
hristelle.ngonga@matech-cameroun.com","188","11-06-2025 18:37:33","MATECH C=
MR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005231930","NYO=
M 2 IHS","","11-06-2025 18:32:31","11-06-2025 18:22:59","11-06-2025 18:25:5=
9","Active // No power issue Ubaie:52.7 V site on Gen, site up without inte=
rvention. TX fme symphorien /650257151 from huawei is informed.","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active // No power issue Ubaie:52.7 V site on Gen, site=
 up without intervention. TX fme symphorien /650257151 from huawei is infor=
med.","franck.nkomot@matech-cameroun.com","573","11-06-2025 18:32:31","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005231915","A=
wae Ewonkan","","11-06-2025 18:27:02","11-06-2025 18:26:57","11-06-2025 18:=
27:33","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed//Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed//Site sta=
bilised","christelle.ngonga@matech-cameroun.com","6","11-06-2025 18:27:02",=
"MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005231851","Odz=
a II OCM","","11-06-2025 18:12:27","11-06-2025 18:04:13","11-06-2025 18:50:=
18","Grid Outage, site went down because gen failed to start due to PWC ZTE=
 malfunction // Grid return","Albran Byorel","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Grid Outage, site went down becau=
se gen failed to start due to PWC ZTE malfunction // Grid return","franck.n=
komot@matech-cameroun.com","496","11-06-2025 18:12:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005231836","MEHANDAN=
","","11-06-2025 18:07:49","11-06-2025 17:03:55","11-06-2025 20:27:23","Sit=
e went down because Gen stopped due to disfunction of PWC // He reset gen a=
nd started manualy","Albran Byorel","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site went down because Gen stopped due to =
disfunction of PWC // He reset gen and started manualy","system","4121","11=
-06-2025 18:07:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0005231533","Nsimalen=
 OCM","","11-06-2025 17:33:08","11-06-2025 17:30:42","11-06-2025 18:22:09",=
"Cascaded Incident from TTO5387221","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage, site is up without an=
y intervation, fme could not access the site due to landlord // Grid return=
","system","297195","11-06-2025 17:33:08","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0005231514","N=
kolda","IHS_YND_327","11-06-2025 17:30:46","11-06-2025 17:30:42","11-06-202=
5 18:22:09","Grid Outage, site is up without any intervation, fme could not=
 access the site due to landlord // Grid return","Albran Byorel","Access De=
nial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord"=
,"Grid Outage, site is up without any intervation, fme could not access the=
 site due to landlord // Grid return","christelle.ngonga@matech-cameroun.co=
m","5","11-06-2025 17:30:46","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005231501","O=
dza II OCM","","11-06-2025 17:28:01","11-06-2025 17:26:55","11-06-2025 17:3=
2:55","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction //  Grid stabilized","Albran Byorel","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, s=
ite went down because gen failed to start due to PWC ZTE malfunction //  Gr=
id stabilized","christelle.ngonga@matech-cameroun.com","68","11-06-2025 17:=
28:01","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005231434","Odz=
a II OCM","","11-06-2025 17:13:30","11-06-2025 17:09:45","11-06-2025 17:13:=
45","Grid fluctuations, site went down because gen failed to start due to P=
WC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, site=
 went down because gen failed to start due to PWC ZTE malfunction // Grid s=
tabilized","franck.nkomot@matech-cameroun.com","654","11-06-2025 17:13:30",=
"MATECH CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0005231414","MES=
SAME NDONGO 1162","","11-06-2025 17:07:09","11-06-2025 17:01:20","11-06-202=
5 17:11:30","Grid outage,site went down because gen failed to start due to =
Gen card Faulty// He started Gen manually","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down =
because gen failed to start due to Gen card Faulty// He started Gen manuall=
y","franck.nkomot@matech-cameroun.com","349","11-06-2025 17:07:09","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005231312","Carrefou=
r Ayissi Ele","","11-06-2025 16:48:41","11-06-2025 16:46:45","11-06-2025 17=
:07:05","Cascaded Incident from TTO5386982","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n because Gen start and stopped with ""High temps ""alarm // he added water=
 and manually start the Gen","system","271088","11-06-2025 16:48:41","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005231314","Nkol-Meb=
anga","","11-06-2025 16:48:41","11-06-2025 16:46:45","11-06-2025 17:07:05",=
"Cascaded Incident from TTO5386982","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen start and stopped with ""High temps ""alarm // he added water and man=
ually start the Gen","system","271088","11-06-2025 16:48:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005231305","SAA 2","=
","11-06-2025 16:47:39","11-06-2025 16:41:45","11-06-2025 17:19:44","Cascad=
ed Incident from TTO5386945","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because Gen s=
tart and stopped with ""High temps ""alarm // he added water and manually s=
tart the Gen","system","271387","11-06-2025 16:47:39","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005231275","S=
aa","IHS_YND_810, IHS_YND_809, IHS_YND_726, IHS_YND_401, IHS_YND_404","11-0=
6-2025 16:43:52","11-06-2025 16:41:45","11-06-2025 17:19:44","Grid outage, =
Site went down because Gen start and stopped with ""High temps ""alarm // h=
e added water and manually start the Gen","Parker Tchoup","Equipment Repair=
","Passive","ACDG Gen","Gen Temp High","Grid outage, Site went down because=
 Gen start and stopped with ""High temps ""alarm // he added water and manu=
ally start the Gen","christelle.ngonga@matech-cameroun.com","128","11-06-20=
25 16:43:52","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005231239","Bar=
riere","","11-06-2025 16:37:51","11-06-2025 16:29:51","11-06-2025 19:05:51"=
,"Grid Outage, Site went down because Gen failed To start due to Alarm ""Ov=
ervoltage' // He reset card and Manually Started the Gen","Hyemafo Gildas",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage=
, Site went down because Gen failed To start due to Alarm ""Overvoltage' //=
 He reset card and Manually Started the Gen","franck.nkomot@matech-cameroun=
.com","513","11-06-2025 16:37:51","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005231060","M=
imboman-Ecole","","11-06-2025 16:09:50","11-06-2025 16:06:45","11-06-2025 1=
6:14:36","No power issue on site U:52 V,site on grid The FME TX Eloundou Be=
rtrant (693212405) From Huawei is Informed.","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site U:52 V,site on grid The FME TX Eloundou Bertrant (6=
93212405) From Huawei is Informed.","christelle.ngonga@matech-cameroun.com"=
,"186","11-06-2025 16:09:50","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005231050","S=
atcom","","11-06-2025 16:07:02","11-06-2025 16:01:56","11-06-2025 16:07:16"=
,"No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand Ngestsa (6=
91144412) of huawei is informed. Noticed that is a repetitive issue","Delor=
 Telezing","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","No power issue site on Grid with Ubaie=3D53,02 V Tx =
Fme Armand Ngestsa (691144412) of huawei is informed. Noticed that is a rep=
etitive issue","christelle.ngonga@matech-cameroun.com","307","11-06-2025 16=
:07:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005230984","Nkol-Meb=
anga","","11-06-2025 15:56:02","11-06-2025 15:45:22","11-06-2025 16:08:22",=
"Cascaded Incident from TTO5386610","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","	Grid outage, Site went down becau=
se Gen start and stopped with ""High temps ""alarm // he added water and ma=
nually start the Gen","system","267591","11-06-2025 15:56:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005230983","Carrefou=
r Ayissi Ele","","11-06-2025 15:56:02","11-06-2025 15:45:22","11-06-2025 16=
:08:22","Cascaded Incident from TTO5386610","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","	Grid outage, Site went do=
wn because Gen start and stopped with ""High temps ""alarm // he added wate=
r and manually start the Gen","system","267591","11-06-2025 15:56:02","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005230949","SAA 2","=
","11-06-2025 15:48:36","11-06-2025 15:45:22","11-06-2025 16:11:22","Cascad=
ed Incident from TTO5386569","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","	Grid outage, Site went down because Gen =
start and stopped with ""High temps ""alarm // he added water and manually =
start the Gen","system","267592","11-06-2025 15:48:36","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005230940","S=
aa","IHS_YND_810, IHS_YND_809, IHS_YND_726, IHS_YND_401, IHS_YND_404","11-0=
6-2025 15:47:30","11-06-2025 15:45:22","11-06-2025 16:19:22","Grid outage, =
Site went down because Gen start and stopped with ""High temps ""alarm // h=
e added water and manually start the Gen","Parker Tchoup","Equipment Repair=
","Passive","ACDG Gen","Gen Temp High","Grid outage, Site went down because=
 Gen start and stopped with ""High temps ""alarm // he added water and manu=
ally start the Gen","christelle.ngonga@matech-cameroun.com","129","11-06-20=
25 15:47:30","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005230738","N=
koabang Ebolmedjock","","11-06-2025 15:09:42","11-06-2025 15:06:31","11-06-=
2025 15:09:54","Site impacted by Nkolmesseng-Abom(CTR-711) Not Managed By I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","Site impacted by Nkolmesseng-Abo=
m(CTR-711) Not Managed By IHS","christelle.ngonga@matech-cameroun.com","192=
","11-06-2025 15:09:42","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0005230729","H=
-General-Yde","","11-06-2025 15:08:21","11-06-2025 15:02:02","11-06-2025 15=
:13:13","Site Down because  Tchientche Evic (692105769/ Epitech ) is on sit=
e for a swap on  gen // End of work","Siligap Boris","Installation Activity=
","Passive","Planned Activity","Installation Activity","Site Down because  =
Tchientche Evic (692105769/ Epitech ) is on site for a swap on  gen // End =
of work","christelle.ngonga@matech-cameroun.com","379","11-06-2025 15:08:21=
","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005230717","Aka=
k-Nkozoa-MTN-IHS","","11-06-2025 15:05:32","11-06-2025 14:53:00","11-06-202=
5 16:03:00","Site went down because Christian was on site For plan work (Te=
lemetry) // End of work","Fabrice Pouakam","Installation Activity","Passive=
","Planned Activity","Installation Activity","Site went down because Christ=
ian was on site For plan work (Telemetry) // End of work","franck.nkomot@ma=
tech-cameroun.com","3116","11-06-2025 15:05:32","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005230342","S=
apeur Mimboman","","11-06-2025 14:12:57","11-06-2025 14:06:49","11-06-2025 =
14:32:25","	Grid outage, site went down due to gen overload(22 kva,318 A) /=
/ Grid returned","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","	Grid outage, site went down due to gen overload(22 kva=
,318 A) // Grid returned","gaelle.njiofack@matech-cameroun.com","369","11-0=
6-2025 14:12:57","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005230281","A=
kak-Nkozoa-MTN-IHS","","11-06-2025 14:06:32","11-06-2025 14:02:20","11-06-2=
025 14:33:20","Site went down because our FME Girresse was on site For PM /=
/ End of work","Fabrice Pouakam","Installation Activity","Passive","Planned=
 Activity","Installation Activity","Site went down because our FME Girresse=
 was on site For PM // End of work","gaelle.njiofack@matech-cameroun.com","=
254","11-06-2025 14:06:32","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005230265","NTU=
I TOWN","","11-06-2025 14:04:28","11-06-2025 13:58:16","11-06-2025 14:32:47=
","Grid outage.gen failed to start due to air intake//We purged and gen man=
ually started","Parker Tchoup","Fuel Outage (Probable)","Passive","ACDG Gen=
","ACDG - Air Intake","Grid outage.gen failed to start due to air intake//W=
e purged and gen manually started","loic.noumsi@matech-cameroun.com","373",=
"11-06-2025 14:04:28","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005230178","C=
rf-Nsam","","11-06-2025 13:53:51","11-06-2025 02:10:10","11-06-2025 03:20:1=
0","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no po=
wer issue","mouliom.anselme@matech-cameroun.com","42221","11-06-2025 13:53:=
51","MATECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0005230118","ODZ=
A CITE MBIA","","11-06-2025 13:48:00","11-06-2025 13:41:53","11-06-2025 14:=
43:22","Grid outage,DG started and stopped due with alarm ""oil pressure""(=
 unproven Alarm ) // He reset DG card and started DG manually","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage,DG started and stopped due with alarm ""oil pressure""( unproven Alarm=
 ) // He reset DG card and started DG manually","loic.noumsi@matech-camerou=
n.com","368","11-06-2025 13:48:00","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005229974","E=
toug ebe Meweulo","","11-06-2025 13:22:29","11-06-2025 13:19:22","11-06-202=
5 13:39:44","Our FME Gildas is on site for work (he was putting in the seco=
nd start) // End of work","Hyemafo Gildas","Equipment Replacement","Passive=
","Planned Activity","Planned Activity - Passive","Our FME Gildas is on sit=
e for work (he was putting in the second start) // End of work","gaelle.nji=
ofack@matech-cameroun.com","188","11-06-2025 13:22:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_088","NOCINC0005229919","Elobi Mo=
kolo","","11-06-2025 13:14:43","11-06-2025 13:10:58","11-06-2025 14:07:00",=
"Cascaded Incident from TTO5385404","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to insufficienc=
y of rectifiers on site // He reduced the load","system","305556","11-06-20=
25 13:14:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_085","NOCINC0005229920","Briquete=
rie","","11-06-2025 13:14:43","11-06-2025 13:10:58","11-06-2025 14:07:00","=
Cascaded Incident from TTO5385404","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Site went down due to insufficiency of rectifier=
s on site // He reduced the load","system","305556","11-06-2025 13:14:43","=
MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0005229912","K=
amajou Building","IHS_YND_088, IHS_YND_085","11-06-2025 13:13:14","11-06-20=
25 13:10:58","11-06-2025 14:07:00","Site went down due to insufficiency of =
rectifiers on site // He reduced the load","Paul BIBOUM","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down due to insufficie=
ncy of rectifiers on site // He reduced the load","gaelle.njiofack@matech-c=
ameroun.com","137","11-06-2025 13:13:14","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005229850","M=
anguier","","11-06-2025 13:01:32","11-06-2025 12:56:22","11-06-2025 14:19:0=
6","Grid outage, Site went down due to Gen overload (17KVA ; 160A) //He red=
uce load and site on Gen","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, Site went down due to Gen overload=
 (17KVA ; 160A) //He reduce load and site on Gen","gaelle.njiofack@matech-c=
ameroun.com","311","11-06-2025 13:01:32","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005229519","E=
koumdoum OCM","","11-06-2025 12:21:51","11-06-2025 12:14:44","11-06-2025 12=
:34:37","Site went down because Gen failed to start due to Grid fluctuation=
 // Grid Stabilized","Albran Byorel","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","Site went down because Gen failed to st=
art due to Grid fluctuation // Grid Stabilized","gaelle.njiofack@matech-cam=
eroun.com","428","11-06-2025 12:21:51","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005229434","N=
taba","IHS_YND_133","11-06-2025 12:10:55","11-06-2025 12:06:43","11-06-2025=
 13:38:47","Grid outage, site went down because gen failed to start due to =
Pwc ZTE dysfunction // He reset and manual start of Gen","Delor Telezing","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage, site went down because gen failed to start due to Pwc ZTE dysfunct=
ion // He reset and manual start of Gen","gaelle.njiofack@matech-cameroun.c=
om","253","11-06-2025 12:10:55","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005229433","E=
lig-Edzoa","","11-06-2025 12:10:08","11-06-2025 12:06:43","11-06-2025 13:34=
:41","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid outage, site went down because gen failed to start due to Pwc ZTE dysf=
unction // He reset and manual start of Gen","gaelle.njiofack@matech-camero=
un.com","309408","11-06-2025 12:10:08","MATECH CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0005229428","N=
ew-Marche-Melen","","11-06-2025 12:09:29","11-06-2025 12:05:16","11-06-2025=
 12:19:44","Site went down because Gen failed to start due to Grid fluctuat=
ion // Grid disjunct and site on Gen","Paul BIBOUM","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Site went down because G=
en failed to start due to Grid fluctuation // Grid disjunct and site on Gen=
","gaelle.njiofack@matech-cameroun.com","254","11-06-2025 12:09:29","MATECH=
 CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005229239","Sim=
e Building","","11-06-2025 11:38:58","11-06-2025 11:32:48","11-06-2025 11:4=
0:52","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","loic.noumsi@=
matech-cameroun.com","370","11-06-2025 11:38:58","MATECH CMR"
"Closed Complete","Site Down","T0629","IHS_YND_058","NOCINC0005229226","Mvo=
lye","","11-06-2025 11:37:51","11-06-2025 11:32:44","11-06-2025 11:53:33","=
Grid outage,Site went down due to insufficiency of rectifiers // Site stabi=
lized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Grid outage,Site went down due to insufficiency of rectifiers // S=
ite stabilized","loic.noumsi@matech-cameroun.com","308","11-06-2025 11:37:5=
1","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005229223","Ron=
d Point Express1114","","11-06-2025 11:37:12","11-06-2025 11:32:02","11-06-=
2025 12:05:15","Active: No power issue, site is on grid with Ubaie=3D50,8V,=
 Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active: No power issue, site is on grid with Ubaie=3D50,8V, Mbah hosiah(=
699699694) from Huawei is informed","loic.noumsi@matech-cameroun.com","310"=
,"11-06-2025 11:37:12","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005229210","Cit=
e des nations","","11-06-2025 11:35:09","11-06-2025 11:28:02","11-06-2025 1=
1:40:03","Active //No power issue ,site on Grid on site with Ubaie:51.5V X =
Fme Hosiah / 674007438 from huawei is informed","Paul BIBOUM","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive //No power issue ,site on Grid on site with Ubaie:51.5V X Fme Hosiah =
/ 674007438 from huawei is informed","loic.noumsi@matech-cameroun.com","428=
","11-06-2025 11:35:09","MATECH CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0005229027","Nko=
lo II New","","11-06-2025 11:06:22","11-06-2025 11:05:16","11-06-2025 12:55=
:05","Site went down because Fme Herve was on site with TX FME Lionel,  for=
 PM (Swap of DC BOX MTN) // End of work","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Sit=
e went down because Fme Herve was on site with TX FME Lionel,  for PM (Swap=
 of DC BOX MTN) // End of work","loic.noumsi@matech-cameroun.com","67","11-=
06-2025 11:06:22","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005228777","F=
ouda-New","","11-06-2025 10:24:30","11-06-2025 10:14:59","11-06-2025 11:26:=
29","Grid outage,site went down due to relay 12 v faulty//We Bypassed relay=
 and gen manually started","Delor Telezing","Equipment Repair","Passive","A=
CDG Gen","ACDG - 12V Relay Faulty","Grid outage,site went down due to relay=
 12 v faulty//We Bypassed relay and gen manually started","gaelle.njiofack@=
matech-cameroun.com","572","11-06-2025 10:24:30","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005228736","N=
YOM 2 IHS","","11-06-2025 10:18:42","11-06-2025 10:16:53","11-06-2025 12:35=
:43","Site went down because the PWC OF ZTE dysfonction // He reset the PWC=
","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down because the PWC OF ZTE dysfonction // He re=
set the PWC","gaelle.njiofack@matech-cameroun.com","110","11-06-2025 10:18:=
42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_509","NOCINC0005228612","MANGUIER=
S CHAPELLE","","11-06-2025 10:02:55","11-06-2025 09:50:57","11-06-2025 10:3=
6:09","Cascaded Incident from TTO5383893","Fabrice Pouakam","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n due to Gen overload (17KVA  ; 160A) // air conditioner shutdown to reduce=
 site load and site on Gen","system","274404","11-06-2025 10:02:55","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0005228611","Omnispor=
t-Rail","","11-06-2025 10:02:54","11-06-2025 09:50:57","11-06-2025 10:36:09=
","Cascaded Incident from TTO5383893","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down due=
 to Gen overload (17KVA  ; 160A) // air conditioner shutdown to reduce site=
 load and site on Gen","system","274404","11-06-2025 10:02:54","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005228592","M=
anguier","IHS_YND_506, IHS_YND_509","11-06-2025 10:00:03","11-06-2025 09:50=
:57","11-06-2025 11:00:09","Grid outage, Site went down due to Gen overload=
 (17KVA  ; 160A) // air conditioner shutdown to reduce site load and site o=
n Gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage, Site went down due to Gen overload (17KVA  ; 160A) //=
 air conditioner shutdown to reduce site load and site on Gen","gaelle.njio=
fack@matech-cameroun.com","547","11-06-2025 10:00:03","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005227959","Mam=
ch Building","","11-06-2025 08:43:38","11-06-2025 08:37:33","11-06-2025 09:=
47:12","Grid outage, Gen stopped due to  overcurrent alarm// Gen card reset=
 and Gen start manually","Mboua Thierry","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid outage, Gen stopped due to  overcurrent =
alarm// Gen card reset and Gen start manually","gaelle.njiofack@matech-came=
roun.com","366","11-06-2025 08:43:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005227918","MBIMBIM"=
,"","11-06-2025 08:36:35","11-06-2025 08:07:28","20-06-2025 20:57:44","Grid=
 outage ,Gen failed to start due to fuel outage(Refueling have to be done b=
y Edonde)//Grid returned","Parker Tchoup","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid outage ,Gen failed to start due to fuel=
 outage(Refueling have to be done by Edonde)//Grid returned","system","1747=
","11-06-2025 08:36:35","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_474","NOCINC0005227917","=
Yoko OCM","","11-06-2025 08:36:35","11-06-2025 08:07:28","11-06-2025 08:51:=
57","Cascaded Incident from TTO5383023 - Cascade Removed From TTO5383023","=
Parker Tchoup","","","","","Site went down due to plan work (SWAP of BATTER=
Y) done by SS IHS Felix Bateu // End of work","system","1747","11-06-2025 0=
8:36:35","MATECH CMR"
"External Reconciliation","Site Down","","IHS_YND_475","NOCINC0005227916","=
Ngoum","","11-06-2025 08:36:35","11-06-2025 08:07:28","11-06-2025 08:51:57"=
,"Cascaded Incident from TTO5383023 - Cascade Removed From TTO5383023","Par=
ker Tchoup","","Passive","Cascade Passive","Cascade Passive","Site went dow=
n due to plan work (SWAP of BATTERY) done by SS IHS Felix Bateu // End of w=
ork","system","1747","11-06-2025 08:36:35","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005227869","M=
atsari","","11-06-2025 08:26:31","11-06-2025 08:07:28","11-06-2025 08:51:57=
","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Site went down due to plan work (SWAP of BATTERY) done by SS IHS =
Felix Bateu // End of work","gaelle.njiofack@matech-cameroun.com","1852","1=
1-06-2025 08:26:31","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005227839","N=
gouetou","","11-06-2025 08:21:52","11-06-2025 08:07:28","11-06-2025 08:51:5=
7","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Site went down due to plan work (SWAP of BATTERY) done by SS IHS=
 Felix Bateu // End of work","gaelle.njiofack@matech-cameroun.com","472256"=
,"11-06-2025 08:21:52","MATECH CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0005227802","N=
ew-Marche-Melen","","11-06-2025 08:14:45","11-06-2025 08:10:27","11-06-2025=
 09:12:36","Grid outage, Gen turn until fuel shortage, // Refueling done","=
Paul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,=
 Gen turn until fuel shortage, // Refueling done","loic.noumsi@matech-camer=
oun.com","259","11-06-2025 08:14:45","MATECH CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0005227796","Oss=
ombe","IHS_YND_454","11-06-2025 08:13:33","11-06-2025 08:07:28","11-06-2025=
 08:51:57","hybrid gen site .site went down due to hybrid system module//ge=
n manually started","Parker Tchoup","Equipment Repair","Passive","Hybrid","=
Hybrid Module","hybrid gen site .site went down due to hybrid system module=
//gen manually started","loic.noumsi@matech-cameroun.com","366","11-06-2025=
 08:13:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005227783","Emana Ly=
cee","","11-06-2025 08:11:06","11-06-2025 08:04:53","11-06-2025 09:41:07","=
Cascaded Incident from TTO5383002","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down becau=
se Gen started and stopped due to Gen overload(20kva, 260A) // Grid stabili=
sed","system","287933","11-06-2025 08:11:06","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005227779","E=
mana lycee 2","IHS_YND_274","11-06-2025 08:10:00","11-06-2025 08:04:53","11=
-06-2025 09:41:07","Grid outage, Site went down because Gen started and sto=
pped due to Gen overload(20kva, 260A) // Grid stabilised","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Si=
te went down because Gen started and stopped due to Gen overload(20kva, 260=
A) // Grid stabilised","loic.noumsi@matech-cameroun.com","308","11-06-2025 =
08:10:00","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005227768","S=
atcom","","11-06-2025 08:08:30","11-06-2025 08:03:24","11-06-2025 10:10:24"=
,"Active // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand =
Ngestsa (691144412) of huawei is informed. Noticed that is a repetitive iss=
ue","Delor Telezing","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active // No power issue site on Grid with=
 Ubaie=3D53,02 V Tx Fme Armand Ngestsa (691144412) of huawei is informed. N=
oticed that is a repetitive issue","loic.noumsi@matech-cameroun.com","307",=
"11-06-2025 08:08:30","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005227465","C=
rf-Nsam","","11-06-2025 07:09:55","11-06-2025 06:04:07","11-06-2025 10:24:4=
3","Backtracking//  Active//No power issue on site Ubaie =3D53.6V site on G=
rid The TX FME Henri (699949693) from Huawei is informed","MINKA NICOLAS","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Backtracking//  Active//No power issue on site Ubaie =3D53.6V si=
te on Grid The TX FME Henri (699949693) from Huawei is informed","gaelle.nj=
iofack@matech-cameroun.com","3990","11-06-2025 07:09:55","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0005227266","Mes=
sassi Ngonlonk","","11-06-2025 06:36:15","11-06-2025 06:34:07","11-06-2025 =
08:03:31","Grid outage, Gen failed to start due to generator card malfuncti=
on // Grid return (Gen Cart will be replace)","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen faile=
d to start due to generator card malfunction // Grid return (Gen Cart will =
be replace)","gerard.tchangoue@matech-cameroun.com","129","11-06-2025 06:36=
:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005227240","Mom","",=
"11-06-2025 06:28:12","11-06-2025 06:23:24","11-06-2025 06:29:10","Cascaded=
 Incident from TTO5382375","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue on site ,site on Gen with Ubaie=
=3D50,7 V Etienne//695033981 is informed.Site impacted by Ngoummou","system=
","265381","11-06-2025 06:28:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0005227241","Akono","=
","11-06-2025 06:28:12","11-06-2025 06:23:24","11-06-2025 06:29:10","Cascad=
ed Incident from TTO5382375","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site ,site on Gen with Ubaie=
=3D50,7 V Etienne//695033981 is informed.Site impacted by Ngoummou","system=
","265383","11-06-2025 06:28:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005227239","OTELE MT=
N","","11-06-2025 06:28:12","11-06-2025 06:23:24","11-06-2025 06:29:10","Ca=
scaded Incident from TTO5382375","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site ,site on Gen with U=
baie=3D50,7 V Etienne//695033981 is informed.Site impacted by Ngoummou","sy=
stem","265382","11-06-2025 06:28:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005227238","OLAMA","=
","11-06-2025 06:28:12","11-06-2025 06:23:24","11-06-2025 06:29:10","Cascad=
ed Incident from TTO5382375","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site ,site on Gen with Ubaie=
=3D50,7 V Etienne//695033981 is informed.Site impacted by Ngoummou","system=
","265381","11-06-2025 06:28:12","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0005227227","Min=
ka","IHS_YND_687, IHS_YND_531, IHS_YND_370, IHS_YND_365","11-06-2025 06:26:=
35","11-06-2025 06:23:24","11-06-2025 06:29:10","No power issue on site ,si=
te on Gen with Ubaie=3D50,7 V Etienne//695033981 is informed.Site impacted =
by Ngoummou","Fanda Brice","Customer Equipment Failure","Active","Active Eq=
uipment Failure","Affected by 3rd Party Site","No power issue on site ,site=
 on Gen with Ubaie=3D50,7 V Etienne//695033981 is informed.Site impacted by=
 Ngoummou","gerard.tchangoue@matech-cameroun.com","192","11-06-2025 06:26:3=
5","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005226986","O=
dza-PK10","","11-06-2025 05:46:52","11-06-2025 05:37:40","11-06-2025 06:36:=
01","Grid outage, site went down due to PWC ZTE dysfunctionment // He reset=
 it and put site on gen","Albran Byorel","Equipment Repair","Passive","Rect=
ifier","Rectifier Module Overloaded","Grid outage, site went down due to PW=
C ZTE dysfunctionment // He reset it and put site on gen","edwige.kapawo@ma=
tech-cameroun.com","553","11-06-2025 05:46:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_283","NOCINC0005226780","Abome","=
","11-06-2025 04:53:23","11-06-2025 04:24:46","11-06-2025 04:49:45","Cascad=
ed Incident from TTO5381768","MINKA NICOLAS","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Messamendongo","system","26=
5195","11-06-2025 04:53:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005226761","Nkongtoc=
k","","11-06-2025 04:46:06","11-06-2025 04:24:46","11-06-2025 04:49:45","Ca=
scaded Incident from TTO5381768","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Site impacted by Messamendongo","syste=
m","265199","11-06-2025 04:46:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005226760","Angongo"=
,"","11-06-2025 04:46:05","11-06-2025 04:24:46","11-06-2025 04:49:45","Casc=
aded Incident from TTO5381768","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Messamendongo","system","26=
5192","11-06-2025 04:46:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0005226757","Nkenglik=
ok","","11-06-2025 04:46:05","11-06-2025 04:24:46","11-06-2025 04:49:45","C=
ascaded Incident from TTO5381768","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Site impacted by Messamendongo","syst=
em","265187","11-06-2025 04:46:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005226758","Ebeba","=
","11-06-2025 04:46:05","11-06-2025 04:24:46","11-06-2025 04:49:45","Cascad=
ed Incident from TTO5381768","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by Messamendongo","system","2651=
97","11-06-2025 04:46:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0005226756","Mbankomo=
 IHS","","11-06-2025 04:46:05","11-06-2025 04:24:46","11-06-2025 04:49:45",=
"Cascaded Incident from TTO5381768","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Site impacted by Messamendongo","system=
","265199","11-06-2025 04:46:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005226759","Mambine"=
,"","11-06-2025 04:46:05","11-06-2025 04:24:46","11-06-2025 04:49:45","Casc=
aded Incident from TTO5381768","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Messamendongo","system","26=
5189","11-06-2025 04:46:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_334","NOCINC0005226752","Mfou OCM=
","","11-06-2025 04:46:04","11-06-2025 04:24:46","11-06-2025 04:49:45","Cas=
caded Incident from TTO5381768","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","Site impacted by Messamendongo","syste=
m","265186","11-06-2025 04:46:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0005226751","Sous Pre=
fecture","","11-06-2025 04:46:04","11-06-2025 04:24:46","11-06-2025 04:49:4=
5","Cascaded Incident from TTO5381768","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Site impacted by Messamendongo","sys=
tem","265196","11-06-2025 04:46:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0005226754","Afanoya"=
,"","11-06-2025 04:46:04","11-06-2025 04:24:46","11-06-2025 04:49:45","Casc=
aded Incident from TTO5381768","Hyemafo Gildas","Cascade Outage","Active","=
Cascade Active","Cascade Active","Site impacted by Messamendongo","system",=
"265186","11-06-2025 04:46:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0005226753","Mandoumb=
a OCM","","11-06-2025 04:46:04","11-06-2025 04:24:46","11-06-2025 04:49:45"=
,"Cascaded Incident from TTO5381768","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Site impacted by Messamendongo","s=
ystem","265196","11-06-2025 04:46:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005226755","Mfou EPC=
","","11-06-2025 04:46:04","11-06-2025 04:24:46","11-06-2025 04:49:45","Cas=
caded Incident from TTO5381768","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","Site impacted by Messamendongo","syste=
m","265195","11-06-2025 04:46:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0005226732","Nomayos-=
IHS","","11-06-2025 04:40:33","11-06-2025 04:24:46","11-06-2025 04:49:45","=
Cascaded Incident from TTO5381768","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Site impacted by Messamendongo","system"=
,"265192","11-06-2025 04:40:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_165","NOCINC0005226719","Ahala","=
","11-06-2025 04:38:47","11-06-2025 04:24:46","11-06-2025 04:49:45","Cascad=
ed Incident from TTO5381768","MINKA NICOLAS","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Messamendongo","system","26=
5198","11-06-2025 04:38:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0005226720","Nsimalen=
 OCM","","11-06-2025 04:38:47","11-06-2025 04:24:46","11-06-2025 04:49:45",=
"Cascaded Incident from TTO5381768","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Site impacted by Messamendongo","syst=
em","265201","11-06-2025 04:38:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_253","NOCINC0005226721","Clge-Adv=
antiste","","11-06-2025 04:38:47","11-06-2025 04:24:46","11-06-2025 04:49:4=
5","Cascaded Incident from TTO5381768","MINKA NICOLAS","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Site impacted by Messamendongo","s=
ystem","265191","11-06-2025 04:38:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_311","NOCINC0005226722","Nkolda",=
"","11-06-2025 04:38:47","11-06-2025 04:24:46","11-06-2025 04:49:45","Casca=
ded Incident from TTO5381768","Albran Byorel","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Site impacted by Messamendongo","system","2=
65194","11-06-2025 04:38:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005226716","EBOM",""=
,"11-06-2025 04:38:46","11-06-2025 04:24:46","11-06-2025 04:49:45","Cascade=
d Incident from TTO5381768","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Messamendongo","system","26=
5200","11-06-2025 04:38:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005226717","Nkolfon =
Cimencam","","11-06-2025 04:38:46","11-06-2025 04:24:46","11-06-2025 04:49:=
45","Cascaded Incident from TTO5381768","Hyemafo Gildas","Cascade Outage","=
Active","Cascade Active","Cascade Active","Site impacted by Messamendongo",=
"system","265190","11-06-2025 04:38:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_255","NOCINC0005226714","Odza-PK1=
0","","11-06-2025 04:38:46","11-06-2025 04:24:46","11-06-2025 04:49:45","Ca=
scaded Incident from TTO5381768","Albran Byorel","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Site impacted by Messamendongo","system"=
,"265194","11-06-2025 04:38:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_583","NOCINC0005226715","Nsam Sof=
avinc T0","","11-06-2025 04:38:46","11-06-2025 04:24:46","11-06-2025 04:49:=
45","Cascaded Incident from TTO5381768","MINKA NICOLAS","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Site impacted by Messamendongo","=
system","265197","11-06-2025 04:38:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_252","NOCINC0005226718","Koweit C=
ity","","11-06-2025 04:38:46","11-06-2025 04:24:46","11-06-2025 04:49:45","=
Cascaded Incident from TTO5381768","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Site impacted by Messamendongo","syste=
m","265193","11-06-2025 04:38:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_157","NOCINC0005226710","MVAN",""=
,"11-06-2025 04:38:45","11-06-2025 04:24:46","11-06-2025 04:49:45","Cascade=
d Incident from TTO5381768","MINKA NICOLAS","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Site impacted by Messamendongo","system","265=
188","11-06-2025 04:38:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_281","NOCINC0005226709","Odza II"=
,"","11-06-2025 04:38:45","11-06-2025 04:24:46","11-06-2025 04:49:45","Casc=
aded Incident from TTO5381768","Albran Byorel","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by Messamendongo","system","=
265189","11-06-2025 04:38:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0005226713","Nomayos =
montee Meche","","11-06-2025 04:38:45","11-06-2025 04:24:46","11-06-2025 04=
:49:45","Cascaded Incident from TTO5381768","Fanda Brice","Cascade Outage",=
"Active","Cascade Active","Cascade Active","Site impacted by Messamendongo"=
,"system","265191","11-06-2025 04:38:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_161","NOCINC0005226712","Sofavinc=
","","11-06-2025 04:38:45","11-06-2025 04:24:46","11-06-2025 04:49:45","Cas=
caded Incident from TTO5381768","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Site impacted by Messamendongo","system",=
"265201","11-06-2025 04:38:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0005226711","MVAN SAC=
EL","","11-06-2025 04:38:45","11-06-2025 04:24:46","11-06-2025 04:49:45","C=
ascaded Incident from TTO5381768","MINKA NICOLAS","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Site impacted by Messamendongo","system=
","265198","11-06-2025 04:38:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005226707","Ahala","=
","11-06-2025 04:38:44","11-06-2025 04:24:46","11-06-2025 04:49:45","Cascad=
ed Incident from TTO5381768","Hyemafo Gildas","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Site impacted by Messamendongo","system","2=
65200","11-06-2025 04:38:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_282","NOCINC0005226708","Meyo",""=
,"11-06-2025 04:38:44","11-06-2025 04:24:46","11-06-2025 04:49:45","Cascade=
d Incident from TTO5381768","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Messamendongo","system","26=
5188","11-06-2025 04:38:44","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005226706","OBA=
M NGOLA OCM","","11-06-2025 04:38:31","11-06-2025 04:30:25","11-06-2025 04:=
49:58","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty // He reset gen card and gen manually started","MINKA NICOLA=
S","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, site went down because Gen failed to started due to Gen card faullty /=
/ He reset gen card and gen manually started","gerard.tchangoue@matech-came=
roun.com","487","11-06-2025 04:38:31","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005226683","Eko=
umdoum OCM","","11-06-2025 04:34:29","11-06-2025 04:24:46","11-06-2025 04:4=
9:45","Grid outage,site went down because Gen failed to start due to Hybrid=
 system malfunction // Grid return","Albran Byorel","Equipment Repair","Pas=
sive","Hybrid","Hybrid Module","Grid outage,site went down because Gen fail=
ed to start due to Hybrid system malfunction // Grid return","gerard.tchang=
oue@matech-cameroun.com","584","11-06-2025 04:34:29","MATECH CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0005226681","N=
omayos","IHS_YND_314, IHS_YND_257, IHS_YND_334, IHS_YND_367, IHS_YND_282, I=
HS_YND_283, IHS_YND_281, IHS_YND_313, IHS_YND_674, IHS_YND_157, IHS_YND_695=
, IHS_YND_348, IHS_YND_510, IHS_YND_161, IHS_YND_791, IHS_YND_339, IHS_YND_=
255, IHS_YND_697, IHS_YND_583, IHS_YND_698, IHS_YND_291, IHS_YND_762, IHS_Y=
ND_252, IHS_YND_350, IHS_YND_335, IHS_YND_165, IHS_YND_327, IHS_YND_349, IH=
S_YND_253, IHS_YND_311","11-06-2025 04:32:54","11-06-2025 04:24:46","11-06-=
2025 04:49:45","Site impacted by Messamendongo","Fanda Brice","Customer Equ=
ipment Failure","Active","Active Equipment Failure","Affected by 3rd Party =
Site","Site impacted by Messamendongo","edwige.kapawo@matech-cameroun.com",=
"489","11-06-2025 04:32:54","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005226621","B=
arriere","","11-06-2025 04:12:43","11-06-2025 04:08:36","11-06-2025 05:32:0=
7","Grid Outage, Site went down because Gen failed To start due to Alarm ""=
Overvoltage' // He reset card and Manually Started the Gen","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outa=
ge, Site went down because Gen failed To start due to Alarm ""Overvoltage' =
// He reset card and Manually Started the Gen","edwige.kapawo@matech-camero=
un.com","249","11-06-2025 04:12:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005226605","MEHANDAN=
","","11-06-2025 04:09:56","11-06-2025 04:05:19","11-06-2025 08:18:21","Cas=
caded Incident from TTO5381683 ","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Cascaded Incident from TTO5381683","s=
ystem","277","11-06-2025 04:09:56","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005226598","Odz=
a II OCM","IHS_YND_528","11-06-2025 04:07:49","11-06-2025 04:05:19","11-06-=
2025 08:20:12","site went down due to malfunction of ATS // ATS reseted","A=
lbran Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue",=
"site went down due to malfunction of ATS // ATS reseted","gerard.tchangoue=
@matech-cameroun.com","152","11-06-2025 04:07:49","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005226596","S=
tade-Abega","","11-06-2025 04:07:22","11-06-2025 04:03:09","11-06-2025 04:1=
9:31","Active // No pwer issus, site is on grid with Ubaie=3D53.4V, Lionel =
adjep(655184876) from Huawei is on site","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No pwer issus, site is on grid with Ubaie=3D53.4V, Lionel adjep(6551=
84876) from Huawei is on site","edwige.kapawo@matech-cameroun.com","254","1=
1-06-2025 04:07:22","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005226555","E=
MANA BILICK CITY","IHS_YND_279","11-06-2025 03:48:22","11-06-2025 03:47:09"=
,"11-06-2025 08:03:20","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid Return","Fabrice Pouakam","Access Denial","L=
ease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid o=
utage, site down because site behaves as Grid only site (Gen Noise) // Grid=
 Return","edwige.kapawo@matech-cameroun.com","74","11-06-2025 03:48:22","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005226549","N=
kolbong","","11-06-2025 03:45:11","11-06-2025 03:44:03","11-06-2025 07:59:4=
5","Grid outage, Site went down due to  Gen overload(22kva//350A) // Grid r=
eturn","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, Site went down due to  Gen overload(22kva//350A) // Gr=
id return","edwige.kapawo@matech-cameroun.com","70","11-06-2025 03:45:11","=
MATECH CMR"
"Closed Complete","Site Down","T0036","IHS_YND_076","NOCINC0005226535","Le =
Flamboyant","","11-06-2025 03:43:10","11-06-2025 03:34:05","11-06-2025 05:1=
7:39","Grid outage, site went down because gen ran untill fuel shortage // =
Refuelling done","Paul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, site went down because gen ran untill fuel shortage // R=
efuelling done","ludivine.ngamaleu@ihstowers.com","546","11-06-2025 03:43:1=
0","MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0005226373","Mes=
sassi okolo","","11-06-2025 02:53:01","11-06-2025 02:50:48","11-06-2025 07:=
57:21","Site went down due to insufficiency of rectifiers. SS IHS Felix Zam=
be confirmed // He reset it","Fabrice Pouakam","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module","Site went down due to insufficiency of rec=
tifiers. SS IHS Felix Zambe confirmed // He reset it","gerard.tchangoue@mat=
ech-cameroun.com","134","11-06-2025 02:53:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005226255","SAA 2","=
","11-06-2025 02:08:55","11-06-2025 01:42:14","11-06-2025 03:19:16","Cascad=
ed Incident from TTO5381242","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because Gen s=
tart and stopped with ""High temps"" alarm // he reset it and manually star=
t the Gen	","system","267757","11-06-2025 02:08:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005226197","Carrefou=
r Ayissi Ele","","11-06-2025 01:52:04","11-06-2025 01:42:14","11-06-2025 03=
:19:43","Cascaded Incident from TTO5381189","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n because Gen start and stopped with ""High temps"" alarm // he reset it an=
d manually start the Gen	","system","1216998","11-06-2025 01:52:04","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005226198","Nkol-Meb=
anga","","11-06-2025 01:52:04","11-06-2025 01:42:14","11-06-2025 03:19:43",=
"Cascaded Incident from TTO5381189","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen start and stopped with ""High temps"" alarm // he reset it and manual=
ly start the Gen	","system","1216998","11-06-2025 01:52:04","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005226181","Saa=
","IHS_YND_810, IHS_YND_809, IHS_YND_401, IHS_YND_404","11-06-2025 01:47:37=
","11-06-2025 01:42:14","11-06-2025 03:19:43","Grid outage, Site went down =
because Gen start and stopped with ""High temps"" alarm // he reset it and =
manually start the Gen	","Parker Tchoup","Equipment Repair","Passive","ACDG=
 Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Site we=
nt down because Gen start and stopped with ""High temps"" alarm // he reset=
 it and manually start the Gen	","gerard.tchangoue@matech-cameroun.com","32=
4","11-06-2025 01:47:37","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005226147","Odz=
a II OCM","","11-06-2025 01:39:29","11-06-2025 01:37:23","11-06-2025 01:43:=
57","Grid fluctuations, site went down because gen failed to start due to P=
WC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, site=
 went down because gen failed to start due to PWC ZTE malfunction // Grid s=
tabilized","gerard.tchangoue@matech-cameroun.com","127","11-06-2025 01:39:2=
9","MATECH CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0005226045","E=
lig-Essono","","11-06-2025 01:15:24","11-06-2025 01:12:18","11-06-2025 02:0=
4:31","Site went down due to Cb(32A) disjuncted in TGBT // He reamed cb(32A=
), site on grid","Paul BIBOUM","Equipment Repair","Passive","Control Panel"=
,"Circuit Breaker Tripped","Site went down due to Cb(32A) disjuncted in TGB=
T // He reamed cb(32A), site on grid","edwige.kapawo@matech-cameroun.com","=
187","11-06-2025 01:15:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0005225870","Nkoa Ayo=
s","","11-06-2025 00:32:34","11-06-2025 00:28:44","11-06-2025 01:09:20","Ca=
scaded Incident from TTO5380829","MINKA NICOLAS","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down  because =
Gen failed to start due to High temp alarm // He added water in the radiato=
r, site on Gen","system","308096","11-06-2025 00:32:34","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005225849","S=
atcom","","11-06-2025 00:28:46","11-06-2025 00:26:39","11-06-2025 00:33:54"=
,"Active // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand =
Ngestsa (691144412) of huawei is informed","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand Ngest=
sa (691144412) of huawei is informed","edwige.kapawo@matech-cameroun.com","=
128","11-06-2025 00:28:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005225810","MEHANDAN=
","","11-06-2025 00:22:23","11-06-2025 00:19:00","11-06-2025 00:28:02","Cas=
caded Incident from TTO5380756","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","1214987","11-06-2025 00:22:23","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005225802","O=
dza II OCM","IHS_YND_528","11-06-2025 00:21:23","11-06-2025 00:19:00","11-0=
6-2025 00:28:02","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","gerard.tchangoue@matech-cameroun.com","146","11-06=
-2025 00:21:23","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005225789","GSO=
","IHS_YND_067","11-06-2025 00:18:09","11-06-2025 00:15:44","11-06-2025 01:=
21:49","Grid outage, site went down  because Gen failed to start due to Hig=
h temp alarm // He added water in the radiator, site on Gen","MINKA NICOLAS=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid outage, site went down  because Gen failed to start du=
e to High temp alarm // He added water in the radiator, site on Gen","gerar=
d.tchangoue@matech-cameroun.com","146","11-06-2025 00:18:09","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005225437","B=
arriere","","10-06-2025 23:15:40","10-06-2025 22:21:43","11-06-2025 00:27:4=
6","Grid Outage Site went down because Gen FAILED To start due to Alarms ""=
Underfrequency // He reset it and Manually Started the Gen","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outa=
ge Site went down because Gen FAILED To start due to Alarms ""Underfrequenc=
y // He reset it and Manually Started the Gen","edwige.kapawo@matech-camero=
un.com","3238","10-06-2025 23:15:40","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005225380","NYO=
M FACE MAETUR","","10-06-2025 23:01:03","10-06-2025 22:59:51","10-06-2025 2=
3:28:51","Site went down due to insufficiency of rectifiers, SS IHS Bernard=
 Atangana confirmed. // Grid return","Fabrice Pouakam","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down due to insufficienc=
y of rectifiers, SS IHS Bernard Atangana confirmed. // Grid return","gerard=
.tchangoue@matech-cameroun.com","73","10-06-2025 23:01:03","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005225198","C=
rf-Nsam","","10-06-2025 22:25:26","10-06-2025 22:15:59","10-06-2025 22:45:5=
0","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","christelle.ngonga@matech-cameroun.com","5=
68","10-06-2025 22:25:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005224825","MBIMBIM"=
,"","10-06-2025 21:25:17","10-06-2025 20:36:46","10-06-2025 20:45:11","Casc=
aded Incident from TTO5379348","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 51.8V. TX FME Willy Ngouni 699759164 of Huawei is informed.	","system",=
"264515","10-06-2025 21:25:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005224823","Ngouetou=
","","10-06-2025 21:25:17","10-06-2025 20:36:46","10-06-2025 20:45:11","Cas=
caded Incident from TTO5379348","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 51.8V. TX FME Willy Ngouni 699759164 of Huawei is informed.	","system"=
,"264514","10-06-2025 21:25:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005224822","Yoko OCM=
","","10-06-2025 21:25:16","10-06-2025 20:36:46","10-06-2025 20:45:11","Cas=
caded Incident from TTO5379348","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 51.8V. TX FME Willy Ngouni 699759164 of Huawei is informed.	","system"=
,"264517","10-06-2025 21:25:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005224821","Matsari"=
,"","10-06-2025 21:25:16","10-06-2025 20:36:46","10-06-2025 20:45:11","Casc=
aded Incident from TTO5379348","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 51.8V. TX FME Willy Ngouni 699759164 of Huawei is informed.	","system",=
"264515","10-06-2025 21:25:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005224819","Ngoum","=
","10-06-2025 21:25:16","10-06-2025 20:36:46","10-06-2025 20:45:11","Cascad=
ed Incident from TTO5379348","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 51.8V. TX FME Willy Ngouni 699759164 of Huawei is informed.	","system",=
"264517","10-06-2025 21:25:16","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005224755","E=
ssomba","","10-06-2025 21:14:45","10-06-2025 18:36:55","12-06-2025 08:30:30=
","Bactraking : (Unstable site) Site went down because PWC overload (12Kw, =
250A) SS IHS Alphonse DEFFO confirmed // Site stabilised","Mba Lazare Herve=
","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","B=
actraking : (Unstable site) Site went down because PWC overload","christell=
e.ngonga@matech-cameroun.com","9472","10-06-2025 21:14:45","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005224620","C=
arrefourt Nkomo","","10-06-2025 20:53:50","10-06-2025 20:47:42","10-06-2025=
 20:54:29","No power issue site on grid with U=3D54.7 v Lionnel Steeve from=
 Huawei is informed","Mba Lazare Herve","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D54.7 v Lionnel Steeve from Huawei is informed","christelle.ng=
onga@matech-cameroun.com","369","10-06-2025 20:53:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005224602","MEHANDAN=
","","10-06-2025 20:50:16","10-06-2025 20:22:58","10-06-2025 20:30:58","Cas=
caded Incident from TTO5379161","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","1221812","10-06-2025 20:50:16","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005224525","Crf=
-Mbankolo-IHS","","10-06-2025 20:39:34","10-06-2025 20:34:28","10-06-2025 2=
1:34:28","Site went down due to insufficient rectifiers on site //He reduce=
d the load and site on Grid","Mboua Thierry","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Site went down due to insufficient rectifier=
s on site //He reduced the load and site on Grid","franck.nkomot@matech-cam=
eroun.com","308","10-06-2025 20:39:34","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005224481","TSI=
NGA VILLAGE 2","","10-06-2025 20:36:25","10-06-2025 20:32:52","10-06-2025 2=
2:13:53","Site went down due to water leaking into tank // tank drained and=
 gen manually started","Delor Telezing","Fuel Outage","Passive","Diesel","D=
iesel Quality","Site went down due to water leaking into tank // tank drain=
ed and gen manually started","franck.nkomot@matech-cameroun.com","214","10-=
06-2025 20:36:25","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005224409","O=
dza II OCM","IHS_YND_528","10-06-2025 20:27:09","10-06-2025 20:22:58","10-0=
6-2025 20:30:58","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","christelle.ngonga@matech-cameroun.com","253","10-06-2025 20:2=
7:09","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0005224209","Nko=
lbisson usines des eaux 2","","10-06-2025 19:54:58","10-06-2025 19:49:19","=
10-06-2025 20:17:19","Grid outage,site went down because Gen failed to star=
t due due GEN battery Faulty//He replaced battery. Site on Grid","TIENTCHEU=
 NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Generator =
Battery","Grid outage,site went down because Gen failed to start due due GE=
N battery Faulty//He replaced battery. Site on Grid","franck.nkomot@matech-=
cameroun.com","340","10-06-2025 19:54:58","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005224119","E=
mana lycee 2","","10-06-2025 19:44:41","10-06-2025 19:43:35","10-06-2025 19=
:45:57","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 260A) // site stabilisation","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen started and stopped due to Gen overload(20kva, 260A) // si=
te stabilisation","christelle.ngonga@matech-cameroun.com","68","10-06-2025 =
19:44:41","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005224101","N=
komo","","10-06-2025 19:43:51","10-06-2025 19:42:45","10-06-2025 19:52:16",=
"Grid outage,site went down because Gen failed to start due to PWC Overload=
(12k//280A)SS HIS Bateu is informed//Site stabilised","Mba Lazare Herve","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage,site went down because Gen failed to start due to PWC Overload(12k//=
280A)SS HIS Bateu is informed//Site stabilised","christelle.ngonga@matech-c=
ameroun.com","67","10-06-2025 19:43:51","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005224047","N=
gousso-Savana","IHS_YND_561","10-06-2025 19:37:16","10-06-2025 19:30:00","1=
0-06-2025 20:03:03","No power issue, site is on grid with Ubaie: 52.7V, Arm=
and Nguetsa (699949553) from Huawei is informed. Noticed that is a repetiti=
ve issue","Siligap Boris","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue, site is on grid with =
Ubaie: 52.7V, Armand Nguetsa (699949553) from Huawei is informed. Noticed t=
hat is a repetitive issue","christelle.ngonga@matech-cameroun.com","436","1=
0-06-2025 19:37:16","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005224043","F=
OUGEROLE","","10-06-2025 19:36:34","10-06-2025 19:30:00","10-06-2025 20:03:=
03","","Siligap Boris","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue, site is on grid with Ubaie: 52.7V, Armand Nguetsa =
(699949553) from Huawei is informed. Noticed that is a repetitive issue","c=
hristelle.ngonga@matech-cameroun.com","1217877","10-06-2025 19:36:34","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0005223994","N=
guila","","10-06-2025 19:29:11","10-06-2025 19:23:26","10-06-2025 19:51:10"=
,"","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Act=
ive","Site impacted by Batchenga (CAMRAIL) wich is not manage by IHS","chri=
stelle.ngonga@matech-cameroun.com","1218223","10-06-2025 19:29:11","MATECH =
CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0005223986","O=
ssombe","","10-06-2025 19:28:13","10-06-2025 19:23:26","10-06-2025 19:51:10=
","","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Ac=
tive","Site impacted by Batchenga (CAMRAIL) wich is not manage by IHS","chr=
istelle.ngonga@matech-cameroun.com","1218223","10-06-2025 19:28:13","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0005223980","D=
ong","","10-06-2025 19:27:32","10-06-2025 19:23:26","10-06-2025 19:51:10","=
","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Activ=
e","Site impacted by Batchenga (CAMRAIL) wich is not manage by IHS","christ=
elle.ngonga@matech-cameroun.com","1218224","10-06-2025 19:27:32","MATECH CM=
R"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0005223972","D=
onga","IHS_YND_424, IHS_YND_433, IHS_YND_444","10-06-2025 19:26:34","10-06-=
2025 19:23:26","10-06-2025 19:51:10","Site impacted by Batchenga (CAMRAIL) =
wich is not manage by IHS","Parker Tchoup","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","Affected by 3rd Party Site","Site impacte=
d by Batchenga (CAMRAIL) wich is not manage by IHS","christelle.ngonga@mate=
ch-cameroun.com","189","10-06-2025 19:26:34","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005223788","A=
wae Escalier","","10-06-2025 19:02:00","10-06-2025 18:56:49","10-06-2025 20=
:15:10","No power issue site on Grid with U=3D56.7V ,The FME TX Henry (6999=
49693) from Huawei is informed","Albran Byorel","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
site on Grid with U=3D56.7V ,The FME TX Henry (699949693) from Huawei is in=
formed","christelle.ngonga@matech-cameroun.com","312","10-06-2025 19:02:00"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005223784","C=
arrefourt Nkomo","","10-06-2025 19:01:19","10-06-2025 18:56:09","10-06-2025=
 19:02:00","Grid low voltage, Site went down because gen failed to start du=
e to grid bad voltage // Grid stabilisation","Mba Lazare Herve","Grid Suppl=
y","Passive","Grid","National Grid - Low Current Supply","Grid low voltage,=
 Site went down because gen failed to start due to grid bad voltage // Grid=
 stabilisation","christelle.ngonga@matech-cameroun.com","311","10-06-2025 1=
9:01:19","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005223771","O=
dza II OCM","","10-06-2025 18:58:37","10-06-2025 18:52:31","10-06-2025 19:4=
8:31","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","christelle.ngonga@matech-cameroun.com","369","10-06-2025 18:5=
8:37","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005223770","OBA=
M NGOLA OCM","","10-06-2025 18:58:27","10-06-2025 18:56:20","10-06-2025 19:=
06:20","Grid outage, site went down because Gen failed to started due to Ge=
n card faulty // // He reset gen card and gen manually started","MINKA NICO=
LAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage, site went down because Gen failed to started due to Gen card faulty =
// // He reset gen card and gen manually started","franck.nkomot@matech-cam=
eroun.com","128","10-06-2025 18:58:27","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005223750","T=
SINGA VILLAGE 2","","10-06-2025 18:55:40","10-06-2025 18:50:34","10-06-2025=
 19:48:34","Site went down due to water leaking into tank // tank drained a=
nd gen manually started","Delor Telezing","Fuel Outage","Passive","Diesel",=
"Diesel Quality","Site down due to water leaking into tank // tank drained =
and gen manually started","christelle.ngonga@matech-cameroun.com","307","10=
-06-2025 18:55:40","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005223742","M=
ontee-Des-Soeurs","","10-06-2025 18:54:40","10-06-2025 18:52:34","10-06-202=
5 18:59:04","Site went Down due to Gen Overload // Grid return","Hyemafo Gi=
ldas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went =
Down due to Gen Overload // Grid return","christelle.ngonga@matech-cameroun=
.com","127","10-06-2025 18:54:40","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005223739","A=
wae Ewonkan","","10-06-2025 18:54:04","10-06-2025 18:52:57","10-06-2025 19:=
02:18","	Grid outage site went down due to Gen Overload (20Kva, Iload 225 A=
)IHS SS Alphonse is informed //Site stabilised","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","	Grid outage site went down=
 due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed //Site=
 stabilised","christelle.ngonga@matech-cameroun.com","68","10-06-2025 18:54=
:04","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005223326","Mok=
olo Yaounde","","10-06-2025 17:52:19","10-06-2025 17:42:59","10-06-2025 19:=
22:59","Active // No power issue Ubay: 54.6 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.6 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","franck.nkomot@matech-cameroun.com","561"=
,"10-06-2025 17:52:19","MATECH CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0005223266","Ngo=
ulmekong-Nord","","10-06-2025 17:42:26","10-06-2025 17:36:04","10-06-2025 1=
7:44:04","Site went down because SS IHS was on site for plan work (swap of =
batteries) // End of work","Siligap Boris","Installation Activity","Passive=
","Planned Activity","Installation Activity","Site went down because SS IHS=
 was on site for plan work (swap of batteries) // End of work","franck.nkom=
ot@matech-cameroun.com","383","10-06-2025 17:42:26","MATECH CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0005223140","D=
ong","","10-06-2025 17:30:25","10-06-2025 17:27:18","10-06-2025 17:59:58","=
 No power issue on site U=3D49 V site on Gen, The TX FME Gr=E9goire //65454=
7479// from huawei is informed,","Parker Tchoup","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No power issu=
e on site U=3D49 V site on Gen, The TX FME Gr=E9goire //654547479// from hu=
awei is informed,","christelle.ngonga@matech-cameroun.com","189","10-06-202=
5 17:30:25","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005223094","S=
tade-Abega","","10-06-2025 17:23:52","10-06-2025 17:22:31","10-06-2025 17:3=
2:28","No pwer issus, site is on grid with Ubaie=3D53.4V, Lionel adjep(6551=
84876) from Huawei is on site ","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pwer issu=
s, site is on grid with Ubaie=3D53.4V, Lionel adjep(655184876) from Huawei =
is on site ","christelle.ngonga@matech-cameroun.com","82","10-06-2025 17:23=
:52","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005222914","Mok=
olo Yaounde","","10-06-2025 17:00:09","10-06-2025 13:46:00","10-06-2025 17:=
34:00","BACKTRACKING. Site went down due to insufficient of rectifier on si=
te SS IHS Bernard is informed // he added one rectifier, Site stabilised","=
","Equipment Repair","Passive","Rectifier","Rectifier Module","BACKTRACKING=
. Site went down due to insufficient of rectifier on site SS IHS Bernard is=
 informed // he added one rectifier, Site stabilised","franck.nkomot@matech=
-cameroun.com","11651","10-06-2025 17:00:09","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005222859","N=
koabang Ebolmedjock","","10-06-2025 16:53:10","10-06-2025 16:49:59","10-06-=
2025 16:55:48","Site  impacted by Nkolmesseng-Abom(CTR-711) Not Managed By =
IHS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equip=
ment Failure","Affected by 3rd Party Site","Site  impacted by Nkolmesseng-A=
bom(CTR-711) Not Manager By IHS","christelle.ngonga@matech-cameroun.com","1=
92","10-06-2025 16:53:10","MATECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0005222826","ODZ=
A CITE MBIA","","10-06-2025 16:47:46","10-06-2025 16:39:33","10-06-2025 18:=
13:33","Grid outage,DG started and stopped due with alarm ""oil pressure""(=
 unproven Alarm ) // He reset DG card and started DG manually","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage,DG started and stopped due with alarm ""oil pressure""( unproven Alarm=
 ) // He reset DG card and started DG manually","franck.nkomot@matech-camer=
oun.com","495","10-06-2025 16:47:46","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005222770","AKA=
K Nkozoa","","10-06-2025 16:40:28","10-06-2025 16:35:17","10-06-2025 18:21:=
17","Site went down because Gen started and stopped to start due to grid ba=
d voltage // He bypassed Grid and started Gen manually","Fabrice Pouakam","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Si=
te went down because Gen started and stopped to start due to grid bad volta=
ge // He bypassed Grid and started Gen manually","franck.nkomot@matech-came=
roun.com","312","10-06-2025 16:40:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005222705","SAA 2","=
","10-06-2025 16:29:53","10-06-2025 16:23:54","10-06-2025 16:30:34","Cascad=
ed Incident from TTO5377229","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because FME Parker was on =
site for work (he replaced the thermostat so that the generator no longer g=
oes into high temperature) // End of work","system","279582","10-06-2025 16=
:29:53","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005222700","S=
aa","IHS_YND_404","10-06-2025 16:29:01","10-06-2025 16:23:54","10-06-2025 1=
6:30:34","Site went down because FME Parker was on site for work (he replac=
ed the thermostat so that the generator no longer goes into high temperatur=
e) // End of work","Parker Tchoup","Installation Activity","Passive","Plann=
ed Activity","Installation Activity","Site went down because FME Parker was=
 on site for work (he replaced the thermostat so that the generator no long=
er goes into high temperature) // End of work","christelle.ngonga@matech-ca=
meroun.com","308","10-06-2025 16:29:01","MATECH CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0005222667","N=
yanon","","10-06-2025 16:24:16","10-06-2025 12:36:06","10-06-2025 16:37:49"=
,"Backtraking : Down at Othin :  No power issue , site on Gen Ubaie=3D55.1 =
V ,TX FMEGr=E9goire //654547479// from huawei is informed","TIENTCHEU NZETC=
HIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","Backtraking : Down at Othin :  No power issue , site=
 on Gen Ubaie=3D55.1 V ,TX FMEGr=E9goire //654547479// from huawei is infor=
med","christelle.ngonga@matech-cameroun.com","13722","10-06-2025 16:24:16",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005222494","T=
SINGA VILLAGE 2","","10-06-2025 15:53:53","10-06-2025 15:52:46","10-06-2025=
 16:34:44","Site down due to water leaking into tank // tank drained and ge=
n manually started","Delor Telezing","Fuel Outage","Passive","Diesel","Dies=
el Quality","Site down due to water leaking into tank // tank drained and g=
en manually started","christelle.ngonga@matech-cameroun.com","68","10-06-20=
25 15:53:53","MATECH CMR"
"Closed Complete","Warning","","IHS_YND_749","NOCINC0005222448","ODZA MINKA=
N EDIBI ASSI","","10-06-2025 15:44:26","","","Grid outage, Site went down b=
efore Gen start due to poor backup// Grid return","Albran Byorel","Warning"=
,"Warning","POWER","Warning - National Grid - Grid Outage Issue","Grid outa=
ge, Site went down before Gen start due to poor backup// Grid return","chri=
stelle.ngonga@matech-cameroun.com","516","10-06-2025 15:44:26","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005222440","Ebo=
go","","10-06-2025 15:43:42","10-06-2025 15:39:00","10-06-2025 15:46:00","S=
ite went down because SS IHS was on site for plan work (swap of batteries) =
// End of work","Siligap Boris","Installation Activity","Passive","Planned =
Activity","Installation Activity","Site went down because SS IHS was on sit=
e for plan work (swap of batteries) // End of work","franck.nkomot@matech-c=
ameroun.com","307","10-06-2025 15:43:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005222406","Nsam esc=
ale LP","","10-06-2025 15:37:30","10-06-2025 15:31:25","10-06-2025 15:39:25=
","Cascaded Incident from TTO5376886","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid Outage, Site went down before Gen start =
due to poor backup // Gen Started Automatically","system","261425","10-06-2=
025 15:37:30","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005222400","Nsa=
m Sofavinc","IHS_YND_732","10-06-2025 15:36:50","10-06-2025 15:31:25","10-0=
6-2025 15:39:25","Grid Outage, Site went down before Gen start due to poor =
backup","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid Outage, Site went down before Gen start due t=
o poor backup // Gen Started Automatically","franck.nkomot@matech-cameroun.=
com","326","10-06-2025 15:36:50","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005222388","B=
arriere","","10-06-2025 15:35:01","10-06-2025 15:32:52","10-06-2025 16:16:0=
1","Site went Down because Gildas (656040578/Matech) was on site for Work (=
PM) // End of works","Hyemafo Gildas","Equipment Replacement","Passive","Pl=
anned Activity","Planned Activity - Passive","Site went Down because Gildas=
 (656040578/Matech) was on site for Work (PM) // End of works","christelle.=
ngonga@matech-cameroun.com","131","10-06-2025 15:35:01","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005222222","E=
bogo","","10-06-2025 15:16:25","10-06-2025 15:13:16","10-06-2025 15:21:16",=
"Grid outage,site went down before gen starts due to poor battery backup //=
 Grid return","Siligap Boris","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage,site went down before gen starts=
 due to poor battery backup // Grid return","christelle.ngonga@matech-camer=
oun.com","190","10-06-2025 15:16:25","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005222030","E=
ssomba","","10-06-2025 14:55:51","10-06-2025 14:55:46","10-06-2025 18:32:48=
","(Unstable site) Site went down because PWC overload // Grid returned","M=
ba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","(Unstable site) Site went down because PWC overload // Grid r=
eturned","christelle.ngonga@matech-cameroun.com","6","10-06-2025 14:55:51",=
"MATECH CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0005222013","BIY=
EM ASSI LYCEE","","10-06-2025 14:52:33","10-06-2025 14:33:23","10-06-2025 1=
6:58:08","No power issue on site U=3D54.8V site on grid Tx Fme MBAH osiah (=
674007438) of huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site U=3D54.8V site on grid Tx Fme MBAH osiah (674007438) of huawei i=
s informed","franck.nkomot@matech-cameroun.com","1151","10-06-2025 14:52:33=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005221992","SAA 2","=
","10-06-2025 14:49:25","10-06-2025 14:32:12","10-06-2025 15:19:30","Cascad=
ed Incident from TTO5376377","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because Gen s=
tart and stopped with ""High temps"" alarm // he added water and manually s=
tart the Gen","system","264956","10-06-2025 14:49:25","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005221980","Acc=
acia New","","10-06-2025 14:47:18","10-06-2025 14:40:12","10-06-2025 21:50:=
11","Grid outage, no space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy MGE // Grid return","franck.nkomot@matech-cameroun.com","428","10=
-06-2025 14:47:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005221948","Nkol-Meb=
anga","","10-06-2025 14:40:52","10-06-2025 14:37:12","10-06-2025 15:11:12",=
"Cascaded Incident from TTO5376371","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen start and stopped with ""High temps"" alarm // he added water and man=
ually start the Gen","system","264657","10-06-2025 14:40:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005221947","Carrefou=
r Ayissi Ele","","10-06-2025 14:40:51","10-06-2025 14:37:12","10-06-2025 15=
:11:12","Cascaded Incident from TTO5376371","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n because Gen start and stopped with ""High temps"" alarm // he added water=
 and manually start the Gen","system","264657","10-06-2025 14:40:51","MATEC=
H CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005221944","Saa=
","IHS_YND_810, IHS_YND_809, IHS_YND_404","10-06-2025 14:40:18","10-06-2025=
 14:32:12","10-06-2025 15:19:30","Grid outage, Site went down because Gen s=
tart and stopped with ""High temps"" alarm // he added water and manually s=
tart the Gen","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","Gen =
Temp High","Grid outage, Site went down because Gen start and stopped with =
""High temps"" alarm // he added water and manually start the Gen","loic.no=
umsi@matech-cameroun.com","614","10-06-2025 14:40:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005221831","Emana Ly=
cee","","10-06-2025 14:23:21","10-06-2025 14:12:17","10-06-2025 14:22:25","=
Cascaded Incident from TTO5376225","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","	Grid outage, Site went down beca=
use Gen started and stopped due to Gen overload(20kva, 260A) // site stabil=
isation","system","280302","10-06-2025 14:23:21","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005221819","Ema=
na lycee 2","IHS_YND_274","10-06-2025 14:21:25","10-06-2025 14:12:17","10-0=
6-2025 14:23:34","	Grid outage, Site went down because Gen started and stop=
ped due to Gen overload(20kva, 260A) // site stabilisation","Fabrice Pouaka=
m","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","	Grid outage,=
 Site went down because Gen started and stopped due to Gen overload(20kva, =
260A) // site stabilisation","loic.noumsi@matech-cameroun.com","549","10-06=
-2025 14:21:25","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005221642","E=
bogo","","10-06-2025 13:58:17","10-06-2025 13:55:11","10-06-2025 14:02:10",=
"	Grid outage,site went down before gen starts due to poor battery backup /=
/ Grid return","Siligap Boris","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","	Grid outage,site went down before gen star=
ts due to poor battery backup // Grid return","gaelle.njiofack@matech-camer=
oun.com","188","10-06-2025 13:58:17","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005221589","S=
atcom","","10-06-2025 13:45:41","10-06-2025 13:41:28","10-06-2025 13:55:38"=
,"	Active // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand=
 Ngestsa (691144412) of huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	A=
ctive // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand Nge=
stsa (691144412) of huawei is informed","gaelle.njiofack@matech-cameroun.co=
m","254","10-06-2025 13:45:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0005221505","ARMP",""=
,"10-06-2025 13:33:16","10-06-2025 12:39:08","10-06-2025 18:27:41","Cascade=
d Incident from TTO5375209","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site down due to work ( fotso /GRATO /SWAP DE BAY 12KIL=
O/ 694271069)  // End of work","system","293049","10-06-2025 13:33:16","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005221302","T=
SINGA VILLAGE 2","","10-06-2025 13:14:19","10-06-2025 13:08:13","10-06-2025=
 14:48:13","site went down due to disjunction of Gen CB // CB rearmed","Del=
or Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Main Breaker T=
ripped","site went down due to disjunction of Gen CB // CB rearmed","loic.n=
oumsi@matech-cameroun.com","368","10-06-2025 13:14:19","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005221036","O=
dza II OCM","","10-06-2025 13:06:01","10-06-2025 13:04:53","10-06-2025 13:0=
7:52","Grid fluctuations, site went down because gen failed to start due to=
 PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, si=
te went down because gen failed to start due to PWC ZTE malfunction // Grid=
 stabilized","gaelle.njiofack@matech-cameroun.com","70","10-06-2025 13:06:0=
1","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005220998","N=
omayos montee Meche","","10-06-2025 12:59:32","10-06-2025 12:56:25","10-06-=
2025 13:08:15","Grid outage, site went down before gen start due to poor ba=
ttery backup // Gen start automatically","Fanda Brice","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup // Gen start automatic=
ally","gaelle.njiofack@matech-cameroun.com","188","10-06-2025 12:59:32","MA=
TECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005220966","OBA=
M NGOLA OCM","","10-06-2025 12:54:15","10-06-2025 12:53:06","10-06-2025 13:=
07:25","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty // // He reset gen card and gen manually started","MINKA NIC=
OLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
outage, site went down because Gen failed to started due to Gen card faullt=
y // // He reset gen card and gen manually started","loic.noumsi@matech-cam=
eroun.com","70","10-06-2025 12:54:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005220932","MEHANDAN=
","","10-06-2025 12:48:22","10-06-2025 12:46:38","10-06-2025 12:50:02","Err=
or ticket","Albran Byorel","Incorrectly Logged Tickets","Error","Error","Er=
ror","Error ticket","system","104","10-06-2025 12:48:22","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005220930","E=
mana lycee 2","","10-06-2025 12:47:47","10-06-2025 12:46:38","10-06-2025 12=
:50:17","ticket error","Fabrice Pouakam","Incorrectly Logged Tickets","Erro=
r","Error","Error","ticket error","gaelle.njiofack@matech-cameroun.com","70=
","10-06-2025 12:47:47","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0005220909","D=
ragage","IHS_YND_208","10-06-2025 12:43:15","10-06-2025 12:39:08","10-06-20=
25 18:37:04","Site down due to work ( fotso /GRATO /SWAP DE BAY 12KILO/ 694=
271069)  // End of work","Mboua Thierry","Equipment Replacement","Passive",=
"Planned Activity","Planned Activity - Passive","Site down due to work ( fo=
tso /GRATO /SWAP DE BAY 12KILO/ 694271069)  // End of work","gaelle.njiofac=
k@matech-cameroun.com","248","10-06-2025 12:43:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0005220853","Nkoa Ayo=
s","","10-06-2025 12:34:11","10-06-2025 12:29:23","10-06-2025 13:31:45","Ca=
scaded Incident from TTO5375135","MINKA NICOLAS","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site down due to grid flu=
ctuation//Grid power stabilized","system","279272","10-06-2025 12:34:11","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0005220846","G=
SO","IHS_YND_067","10-06-2025 12:33:32","10-06-2025 12:29:23","10-06-2025 1=
3:31:45","Grid outage site down due to grid fluctuation//Grid power stabili=
zed","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Unstab=
le Grid Supply Issue","Grid outage site down due to grid fluctuation//Grid =
power stabilized","gaelle.njiofack@matech-cameroun.com","249","10-06-2025 1=
2:33:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0005220797","Crf Corn=
ier","","10-06-2025 12:25:22","10-06-2025 12:18:08","10-06-2025 18:33:17","=
Cascaded Incident from TTO5375034","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
disjunction in the energy bay  //Circuit breaker rearm ,site on grid","syst=
em","287133","10-06-2025 12:25:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0005220796","Mobil-Es=
sos","","10-06-2025 12:25:22","10-06-2025 12:18:08","10-06-2025 18:33:17","=
Cascaded Incident from TTO5375034","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
disjunction in the energy bay  //Circuit breaker rearm ,site on grid","syst=
em","287133","10-06-2025 12:25:22","MATECH CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0005220754","M=
adison","IHS_YND_109, IHS_YND_566","10-06-2025 12:19:14","10-06-2025 12:18:=
08","10-06-2025 18:33:17","Grid outage, Site went down due to disjunction i=
n the energy bay  //Circuit breaker rearm ,site on grid","MFOUAGUEGUE MATHI=
EU","Equipment Repair","Passive","Control Panel","Rectifier Battery Breaker=
 Tripped","Grid outage, Site went down due to disjunction in the energy bay=
  //Circuit breaker rearm ,site on grid","gaelle.njiofack@matech-cameroun.c=
om","67","10-06-2025 12:19:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005220563","MEHANDAN=
","","10-06-2025 11:55:22","10-06-2025 11:51:18","10-06-2025 12:00:58","Cas=
caded Incident from TTO5374806","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","267225","10-06-2025 11:55:22","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005220557","O=
dza II OCM","IHS_YND_528","10-06-2025 11:54:27","10-06-2025 11:51:18","10-0=
6-2025 12:00:58","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","gaelle.njiofack@matech-cameroun.com","191","10-06-=
2025 11:54:27","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005220519","E=
koumdoum OCM","","10-06-2025 11:45:49","10-06-2025 11:41:33","10-06-2025 12=
:17:35","Site down due to worck (bay configuration) // End of work","Albran=
 Byorel","Equipment Replacement","Passive","Planned Activity","Planned Acti=
vity - Passive","Site down due to worck (bay configuration) // End of work"=
,"gaelle.njiofack@matech-cameroun.com","257","10-06-2025 11:45:49","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005220497","FOUGEROL=
E","","10-06-2025 11:42:40","10-06-2025 11:40:26","10-06-2025 11:54:45","Ca=
scaded Incident from TTO5374726","Siligap Boris","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active // No power issue, site is on gri=
d with Ubaie: 52.6V, Symphorien(650257151) from Huawei is informed. Noticed=
 that is a repetitive issue","system","275052","10-06-2025 11:42:40","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005220487","N=
gousso-Savana","IHS_YND_561","10-06-2025 11:41:32","10-06-2025 11:40:26","1=
0-06-2025 11:54:45","Active // No power issue, site is on grid with Ubaie: =
52.6V, Armand Nguetsa  (699949553) from Huawei is informed. Noticed that is=
 a repetitive issue","Siligap Boris","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active // No power issue, =
site is on grid with Ubaie: 52.6V, Symphorien(650257151) from Huawei is inf=
ormed. Noticed that is a repetitive issue","gaelle.njiofack@matech-cameroun=
.com","67","10-06-2025 11:41:32","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005220472","S=
apeur Mimboman","","10-06-2025 11:40:12","10-06-2025 11:39:00","10-06-2025 =
17:49:00","Grid outage, site went down due to gen overload(22 kva,318 A) //=
 He reduced load and gen manually started","Mba Lazare Herve","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down d=
ue to gen overload(22 kva,318 A) // He reduced load and gen manually starte=
d","gaelle.njiofack@matech-cameroun.com","73","10-06-2025 11:40:12","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_068","IHS_YND_109","NOCINC0005220130","M=
obil-Essos","","10-06-2025 11:07:30","10-06-2025 10:59:54","10-06-2025 11:5=
4:41","grid outage,no space to deploy a mobil gen // Grid return","Siligap =
Boris","Cascade Outage","Passive","Cascade Passive","Cascade Passive","grid=
 outage,no space to deploy a mobil gen // Grid return","gaelle.njiofack@mat=
ech-cameroun.com","270285","10-06-2025 11:07:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0005220121","Crf Corn=
ier","","10-06-2025 11:05:50","10-06-2025 10:59:54","10-06-2025 11:54:41","=
Cascaded Incident from TTO5374292","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage,no space to deploy a mo=
bil gen // Grid return","system","270284","10-06-2025 11:05:50","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005220108","Melen Ba=
'aba","","10-06-2025 11:03:44","10-06-2025 10:57:11","10-06-2025 11:00:31",=
"Cascaded Incident from TTO5374260","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","bad Grid voltage, Site went down b=
ecause Gen Failed to start due to bad Grid Votage // Grid Disjunction and s=
ite on Gen","system","1212623","10-06-2025 11:03:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005220107","Nkolfoul=
ou 2","","10-06-2025 11:03:43","10-06-2025 10:57:11","10-06-2025 11:00:31",=
"Cascaded Incident from TTO5374260","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","bad Grid voltage, Site went down b=
ecause Gen Failed to start due to bad Grid Votage // Grid Disjunction and s=
ite on Gen","system","1212624","10-06-2025 11:03:43","MATECH CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0005220102","M=
adison","IHS_YND_109, IHS_YND_566","10-06-2025 11:03:06","10-06-2025 10:59:=
54","10-06-2025 11:54:41","grid outage,no space to deploy a mobil gen // Gr=
id return","MFOUAGUEGUE MATHIEU","Grid Supply","Passive","Grid","National G=
rid - Grid Outage Issue","grid outage,no space to deploy a mobil gen // Gri=
d return","loic.noumsi@matech-cameroun.com","193","10-06-2025 11:03:06","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005220072","N=
kolfoulou","IHS_YND_278, IHS_YND_308","10-06-2025 11:00:25","10-06-2025 10:=
57:11","10-06-2025 11:13:31","bad Grid voltage, Site went down because Gen =
Failed to start due to bad Grid Votage // Grid Disjunction and site on Gen"=
,"Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","bad Grid voltage, Site went down because Gen Failed to star=
t due to bad Grid Votage // Grid Disjunction and site on Gen","gaelle.njiof=
ack@matech-cameroun.com","195","10-06-2025 11:00:25","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005220038","E=
ssomba","","10-06-2025 10:51:39","10-06-2025 10:48:29","10-06-2025 14:19:59=
","(Unstable site) Site went down because PWC overload // Grid returned","M=
ba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","(Unstable site) Site went down because PWC overload // Grid r=
eturned","gaelle.njiofack@matech-cameroun.com","192","10-06-2025 10:51:39",=
"MATECH CMR"
"Closed Complete","Warning","CTR_214","IHS_YND_296","NOCINC0005219941","Nko=
lfoulou","","10-06-2025 10:35:58","","","Grid outage, Site went down becaus=
e Gen Failed to start due to bad Grid Votage // He  bypassed Grid and site =
on Gen","Siligap Boris","Warning","Warning","POWER","Warning - National Gri=
d - Grid Incomplete Phase","Grid outage, Site went down because Gen Failed =
to start due to bad Grid Votage // He  bypassed Grid and site on Gen","loic=
.noumsi@matech-cameroun.com","400","10-06-2025 10:35:58","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005219832","M=
vog Mbi New","","10-06-2025 10:21:47","10-06-2025 10:19:34","10-06-2025 11:=
05:06","Site went down due to insufficiency of rectifiers // He reset Recti=
fier and reduced load","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to insufficiency of rectifiers =
// He reset Rectifier and reduced load","loic.noumsi@matech-cameroun.com","=
134","10-06-2025 10:21:47","MATECH CMR"
"Closed Complete","Warning","CTR_211","IHS_YND_248","NOCINC0005219777","Bit=
eng","","10-06-2025 10:13:09","","","Grid outage site went down because Gen=
 failed to start due PWC dysfonction // He reset the PWC, grid return","Mba=
 Lazare Herve","Warning","Warning","POWER","Warning - Site on Battery","Gri=
d outage site went down because Gen failed to start due PWC dysfonction // =
He reset the PWC, grid return","loic.noumsi@matech-cameroun.com","132","10-=
06-2025 10:13:09","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005219607","E=
koumdoum OCM","","10-06-2025 09:48:40","10-06-2025 09:44:31","10-06-2025 11=
:13:29","Site down due to worck (bay configuration) // End of work","Albran=
 Byorel","Equipment Replacement","Passive","Planned Activity","Planned Acti=
vity - Passive","Site down due to worck (bay configuration) // End of work"=
,"gaelle.njiofack@matech-cameroun.com","250","10-06-2025 09:48:40","MATECH =
CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005219524","S=
apeur Mimboman","","10-06-2025 09:34:53","10-06-2025 09:29:45","10-06-2025 =
10:15:42","Grid outage, site went down due to gen overload(22 kva,318 A) //=
 He reduced load and gen manually started","Mba Lazare Herve","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down d=
ue to gen overload(22 kva,318 A) // He reduced load and gen manually starte=
d","loic.noumsi@matech-cameroun.com","309","10-06-2025 09:34:53","MATECH CM=
R"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005219366","N=
koabang Ebolmedjock","","10-06-2025 09:09:47","10-06-2025 09:04:41","10-06-=
2025 09:58:59","	Active//No power issue, Site on Gen. Notice that it is imp=
acted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","Affected b=
y 3rd Party Site","	Active//No power issue, Site on Gen. Notice that it is =
impacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","gaelle.njiofack@=
matech-cameroun.com","307","10-06-2025 09:09:47","MATECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0005219342","Emo=
mbo Esssomba","","10-06-2025 09:07:03","10-06-2025 09:04:55","10-06-2025 10=
:52:49","Grid outage, Gen failed to Alarm oil pressure // Gen card reset an=
d Gen start manually","Mba Lazare Herve","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Low Oil Pressure","Grid outage, Gen failed to Alarm oil press=
ure // Gen card reset and Gen start manually","loic.noumsi@matech-cameroun.=
com","129","10-06-2025 09:07:03","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005219319","C=
rf-Nsam","","10-06-2025 09:02:28","10-06-2025 08:54:18","10-06-2025 09:37:0=
6","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informe","MINKA NICOLAS","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (6999=
49693) from Huawei is informe","gaelle.njiofack@matech-cameroun.com","491",=
"10-06-2025 09:02:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005219113","MEHANDAN=
","","10-06-2025 08:22:42","10-06-2025 08:16:07","10-06-2025 08:27:08","Cas=
caded Incident from TTO5373147","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid returned","syste=
m","1222164","10-06-2025 08:22:42","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005219110","O=
dza II OCM","IHS_YND_528","10-06-2025 08:21:22","10-06-2025 08:16:07","10-0=
6-2025 08:27:08","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid returned","Albran Byorel","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctua=
tions, site went down because gen failed to start due to PWC ZTE malfunctio=
n // Grid returned","loic.noumsi@matech-cameroun.com","318","10-06-2025 08:=
21:22","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005218878","C=
-Supreme","","10-06-2025 07:28:32","10-06-2025 07:25:25","10-06-2025 07:30:=
53","Active: No power issue, site on Battery with Ubaie=3D54.7V, Brice Tsag=
ue (650 21 40 96) from Huawei is informed","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power =
issue, site on Battery with Ubaie=3D54.7V, Brice Tsague (650 21 40 96) from=
 Huawei is informed","loic.noumsi@matech-cameroun.com","188","10-06-2025 07=
:28:32","MATECH CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0005218774","K=
ondengui","","10-06-2025 07:08:31","10-06-2025 07:04:23","10-06-2025 07:37:=
23","Grid outage, site went down because gen failed to start due to ""under=
voltage"""" alarm // We reset card  and gen manually started","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, site went down because gen failed to start due to ""undervoltage"""" a=
larm // We reset card  and gen manually started","loic.noumsi@matech-camero=
un.com","249","10-06-2025 07:08:31","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005218697","B=
arriere","","10-06-2025 06:48:56","10-06-2025 06:46:37","10-06-2025 09:20:0=
4","Grid outage, site went down because Gen failed to start due to Grid Bad=
 voltage // He bypassed Grid and started Gen manually","Hyemafo Gildas","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 outage, site went down because Gen failed to start due to Grid Bad voltage=
 // He bypassed Grid and started Gen manually","loic.noumsi@matech-cameroun=
.com","140","10-06-2025 06:48:56","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005218487","Nko=
abang Alembe","","10-06-2025 05:49:07","10-06-2025 05:47:33","10-06-2025 09=
:28:00","Site went down due to Rectifier dysfunctionning // He reset it: si=
te on grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down due to Rectifier dysfunctionning // He rese=
t it: site on grid","cedric.tiani@matech-cameroun.com","94","10-06-2025 05:=
49:07","MATECH CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0005218173","D=
ong","","10-06-2025 03:57:40","10-06-2025 03:55:33","10-06-2025 06:51:24","=
site down due to High temp on Gen, // door open, generator cooled, and gen =
restarted manually. ","Parker Tchoup","Equipment Repair","Passive","ACDG Ge=
n","Gen Temp High","site down due to High temp on Gen, // door open, genera=
tor cooled, and gen restarted manually. ","vanel.mbiada@matech-cameroun.com=
","128","10-06-2025 03:57:40","MATECH CMR"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0005217552","M=
ONTEE NKONDENGUI","","10-06-2025 00:38:39","08-06-2025 19:58:27","08-06-202=
5 20:01:33","Backtracking No power issue U =3D53.1V site on Grid. The Tx FM=
E Eloundou (693212405 )from Huawei is informed","Albran Byorel","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue U =3D53.1V site on Grid. The Tx FME Eloundou (693212405 )fr=
om Huawei is informed","cedric.tiani@matech-cameroun.com","103213","10-06-2=
025 00:38:39","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005217514","M=
ontee-Jouvence-II","","10-06-2025 00:25:16","08-06-2025 16:54:27","08-06-20=
25 16:54:32","Backtracking ACTIVE// No power issue on site, site on Grid wi=
th Ubaie=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informe=
d","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","ACTIVE// No power issue on site, site on Gr=
id with Ubaie=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is in=
formed","cedric.tiani@matech-cameroun.com","113450","10-06-2025 00:25:16","=
MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005217511","O=
kola OCM","","10-06-2025 00:23:38","08-06-2025 14:58:46","08-06-2025 18:54:=
26","Backtracking Site went down because 02/03 rectifiers dysfunctionned// =
He reset rectifiers","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down because 02/03 rectifiers d=
ysfunctionned// He reset rectifiers","cedric.tiani@matech-cameroun.com","12=
0292","10-06-2025 00:23:38","MATECH CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0005217459","Awa=
e Escalier","","10-06-2025 00:07:02","09-06-2025 23:59:43","10-06-2025 01:0=
1:16","Grid fluctuation, Site went down because gen fails to start due to g=
rid bad voltage // He bypass grid and manually start the gen","Albran Byore=
l","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fructuation, Site went down because gen fails to start due to grid b=
ad voltage // He bypass grid and manually start the gen","cedric.tiani@mate=
ch-cameroun.com","440","10-06-2025 00:07:02","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005217442","C=
-Supreme","","10-06-2025 00:01:19","08-06-2025 15:06:14","08-06-2025 15:14:=
51","Backtracking Active: No power issue, site on Battery  with Ubaie=3D48V=
, Brice Tsague (650 21 40 96) from Huawei is informed","","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue, site on Battery  with Ubaie=3D48V, Brice Tsague (650 21 =
40 96) from Huawei is informed","cedric.tiani@matech-cameroun.com","118505"=
,"10-06-2025 00:01:19","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005217433","C=
rf-Nsam","","09-06-2025 23:57:34","09-06-2025 23:49:25","10-06-2025 00:00:5=
1","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informe","MINKA NICOLAS","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (6999=
49693) from Huawei is informe","vanel.mbiada@matech-cameroun.com","490","09=
-06-2025 23:57:34","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005217432","B=
arriere","","09-06-2025 23:56:28","09-06-2025 23:54:20","09-06-2025 23:59:1=
4","Grid fluctuation, Site went down because gen fails to start due to grid=
 bad voltage // site stabilized","Hyemafo Gildas","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site wen=
t down because gen fails to start due to grid bad voltage // site stabilize=
d","vanel.mbiada@matech-cameroun.com","129","09-06-2025 23:56:28","MATECH C=
MR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005217358","Ron=
d Point Express1114","","09-06-2025 23:33:57","09-06-2025 23:24:59","09-06-=
2025 23:39:56","Grid outage, Site went down before Gen start due to poor ba=
ckup // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Grid return","cedric.tiani@matech-cameroun.c=
om","539","09-06-2025 23:33:57","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005217219","Acc=
acia New","","09-06-2025 23:05:20","09-06-2025 23:03:54","10-06-2025 00:59:=
42","Access issue during the Night","","Access Denial","Lease Or Legal","La=
ndlord Related Issues","Access Issue - Land Lord","Access issue during the =
Night","cedric.tiani@matech-cameroun.com","87","09-06-2025 23:05:20","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_621","IHS_YND_278","NOCINC0005217154","N=
kolfoulou 2","","09-06-2025 22:47:26","09-06-2025 22:38:54","10-06-2025 00:=
12:30","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage Site went down because CB (32A) in the PWC that =
supplies rectifiers // he rearmed it","vanel.mbiada@matech-cameroun.com","2=
93151","09-06-2025 22:47:26","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005217143","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","09-06-2025 22:46:08","0=
9-06-2025 22:38:54","10-06-2025 00:14:26","Grid outage Site went down becau=
se CB (32A) in the PWC that supplies rectifiers // he rearmed it","Siligap =
Boris","Equipment Repair","Passive","Rectifier","Rectifier - Circuit Breake=
r","Grid outage Site went down because CB (32A) in the PWC that supplies re=
ctifiers // he rearmed it","vanel.mbiada@matech-cameroun.com","435","09-06-=
2025 22:46:08","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005217139","T=
SINGA VILLAGE 2","","09-06-2025 22:44:55","09-06-2025 22:38:54","10-06-2025=
 00:12:30","","Delor Telezing","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage Site went down because CB (32A) in the PWC =
that supplies rectifiers // he rearmed it","vanel.mbiada@matech-cameroun.co=
m","293150","09-06-2025 22:44:55","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005217136","M=
elen Ba'aba","","09-06-2025 22:44:01","09-06-2025 22:38:54","10-06-2025 00:=
12:30","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage Site went down because CB (32A) in the PWC that =
supplies rectifiers // he rearmed it","vanel.mbiada@matech-cameroun.com","2=
93150","09-06-2025 22:44:01","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005216887","Crf=
-Mbankolo-IHS","","09-06-2025 21:59:22","09-06-2025 21:56:16","09-06-2025 2=
3:47:19","Site went down due to insufficient rectifiers on site //He reduce=
d the load and site on Grid","Mboua Thierry","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Site went down due to insufficient rectifier=
s on site //He reduced the load and site on Grid","edwige.kapawo@matech-cam=
eroun.com","188","09-06-2025 21:59:22","MATECH CMR"
"Closed Complete","Site Down","CTR_553","IHS_YND_686","NOCINC0005216869","O=
yomabang Ecole","","09-06-2025 21:56:47","09-06-2025 21:47:32","09-06-2025 =
21:55:17","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mo=
uhamadou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mouh=
amadou (6144435) from Huawei is informed.","edwige.kapawo@matech-cameroun.c=
om","556","09-06-2025 21:56:47","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005216865","C=
rf-Nsam","","09-06-2025 21:56:02","09-06-2025 21:53:52","09-06-2025 21:59:5=
2","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","edwige.kapawo@matech-cameroun.com","131",=
"09-06-2025 21:56:02","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005216751","Efo=
ulan MTN","","09-06-2025 21:42:46","09-06-2025 21:37:38","09-06-2025 21:55:=
54","Site went down due to insufficient recfiers on site //Site stabilised"=
,"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient recfiers on site //Site stabilised","=
gerard.tchangoue@matech-cameroun.com","309","09-06-2025 21:42:46","MATECH C=
MR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005216686","Beh=
ind P T school Yde","","09-06-2025 21:33:48","09-06-2025 21:28:41","09-06-2=
025 22:42:54","Access Issue during the night  due to the Landlord","Paul BI=
BOUM","Access Denial","Lease Or Legal","Landlord Related Issues","Access Is=
sue - Land Lord","Access Issue during the night  due to the Landlord","gera=
rd.tchangoue@matech-cameroun.com","308","09-06-2025 21:33:48","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0005216535","N=
goulmekong-Nord","","09-06-2025 21:12:18","09-06-2025 21:09:12","09-06-2025=
 21:54:40","Site went down because CB (125A)  in the PWC  that supplies OCM=
 faulty// he replaced it with another 125A","Siligap Boris","Equipment Repa=
ir","Passive","Rectifier","Rectifier - Circuit Breaker","Site went down bec=
ause CB (125A)  in the PWC  that supplies OCM faulty// he replaced it with =
another 125A","edwige.kapawo@matech-cameroun.com","187","09-06-2025 21:12:1=
8","MATECH CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0005216467","E=
kie sud","","09-06-2025 21:01:20","09-06-2025 20:58:11","09-06-2025 22:56:0=
3","Grid outage ,Site went down due to PWC ZTE dysfunction//He reset it and=
 site on Grid","Albran Byorel","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Grid outage ,Site went down due to PWC ZTE dysf=
unction//He reset it and site on Grid","edwige.kapawo@matech-cameroun.com",=
"190","09-06-2025 21:01:20","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005216456","Nom=
ayos montee Meche","","09-06-2025 20:59:30","09-06-2025 20:56:23","09-06-20=
25 23:28:07","Site went down because CB (63A) in the PWC that supplies OCM =
faulty// he rearmed it","Fanda Brice","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Circuit Breaker Issue","Site went down because CB =
(63A) in the PWC that supplies OCM faulty// he rearmed it","edwige.kapawo@m=
atech-cameroun.com","188","09-06-2025 20:59:30","MATECH CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0005216390","R=
d-Pt-Express","","09-06-2025 20:50:46","09-06-2025 20:40:59","09-06-2025 23=
:26:01","Grid Only, No space to deploy MGE","","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue","Grid Only, No space to deploy MGE",=
"edwige.kapawo@matech-cameroun.com","588","09-06-2025 20:50:46","MATECH CMR=
"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005216371","Odz=
a petit marche new","","09-06-2025 20:49:16","09-06-2025 20:47:46","09-06-2=
025 21:05:18","Site went down due to insufficient rectifiers on site //Site=
 stabilised","Albran Byorel","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to insufficient rectifiers on site //Site=
 stabilised","gerard.tchangoue@matech-cameroun.com","90","09-06-2025 20:49:=
16","MATECH CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0005216362","Sim=
bock Maetur","","09-06-2025 20:46:27","05-06-2025 22:32:12","05-06-2025 22:=
42:12","Backtracking Active//No power Issue Site on Grid Ubai =3D54.3V, The=
 FME The TX FME Mbah Hosiah (674007438) is informed.","Hyemafo Gildas","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Backtracking Active//No power Issue Site on Grid Ubai =3D54.3V, The=
 FME The TX FME Mbah Hosiah (674007438) is informed.","gerard.tchangoue@mat=
ech-cameroun.com","339256","09-06-2025 20:46:27","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005216360","N=
gouetou","","09-06-2025 20:46:19","09-06-2025 20:45:12","09-06-2025 20:53:0=
0","Active // No power issue site on Gen, with Ubay: 51.9V. The Tx Fme Greg=
oire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e // No power issue site on Gen, with Ubay: 51.9V. The Tx Fme Gregoire (654=
547479) from Huawei is informed","edwige.kapawo@matech-cameroun.com","68","=
09-06-2025 20:46:19","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0005216343","Pha=
rmacie Bleue","","09-06-2025 20:43:28","05-06-2025 22:21:13","05-06-2025 22=
:31:13","Active No power issue U=3D 56,3 V site on Grid Tx fme symphorien /=
650257151 from huawei is informed .	","Siligap Boris","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active No=
 power issue U=3D 56,3 V site on Grid Tx fme symphorien /650257151 from hua=
wei is informed .	","gerard.tchangoue@matech-cameroun.com","339735","09-06-=
2025 20:43:28","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005216316","N=
koabang2","","09-06-2025 20:38:45","09-06-2025 20:34:33","09-06-2025 20:37:=
56","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ed=
wige.kapawo@matech-cameroun.com","253","09-06-2025 20:38:45","MATECH CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0005216265","Nko=
ngtock","","09-06-2025 20:24:18","05-06-2025 23:13:20","06-06-2025 00:51:20=
","Backtracking Active: No power issue on site Ubaie=3D48,7V site on Gen Th=
e Tx FME Etienne//695033981 from Huawei is informed","Kemeni Franklin","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Backtracking Active: No power issue on site Ubaie=3D48,7V site on G=
en The Tx FME Etienne//695033981 from Huawei is informed","gerard.tchangoue=
@matech-cameroun.com","335459","09-06-2025 20:24:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005216251","Nsam esc=
ale LP","","09-06-2025 20:19:39","09-06-2025 20:15:01","09-06-2025 20:37:41=
","Cascaded Incident from TTO5369842","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Site went Down due to disjunction of rectifie=
r circuit breaker // He rearmed CB, Site on Grid","system","265810","09-06-=
2025 20:19:39","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005216249","Nsa=
m Sofavinc","IHS_YND_732","09-06-2025 20:19:08","09-06-2025 20:15:01","09-0=
6-2025 20:37:41","Site went Down due to disjunction of rectifier circuit br=
eaker // He rearmed CB, Site on Grid","MINKA NICOLAS","Equipment Repair","P=
assive","Rectifier","Rectifier - Circuit Breaker","Site went Down due to di=
sjunction of rectifier circuit breaker // He rearmed CB, Site on Grid","ger=
ard.tchangoue@matech-cameroun.com","248","09-06-2025 20:19:08","MATECH CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0005216161","Nko=
mo II","","09-06-2025 20:06:31","06-06-2025 00:05:08","06-06-2025 02:32:08"=
,"Backtracking No power issue site on grid with U=3D53 v Lionnel Steeve fro=
m Huawei is informed","Albran Byorel","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Backtracking No power iss=
ue site on grid with U=3D53 v Lionnel Steeve from Huawei is informed","gera=
rd.tchangoue@matech-cameroun.com","331283","09-06-2025 20:06:31","MATECH CM=
R"
"Closed Complete","Site Down","T0051","IHS_YND_297","NOCINC0005216110","Mes=
sassi","","09-06-2025 19:57:54","05-06-2025 22:06:27","05-06-2025 22:23:27"=
,"Active, No power issue on site ,site on Grid with Ubaie=3D54.5 V The Tx F=
ME Synphorien /691316854//from huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active, No power issue on site ,site on Grid with Ubaie=3D54.5 V The =
Tx FME Synphorien /691316854//from huawei is informed","gerard.tchangoue@ma=
tech-cameroun.com","337888","09-06-2025 19:57:54","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005216051","OBA=
M NGOLA OCM","","09-06-2025 19:53:11","09-06-2025 19:44:05","09-06-2025 20:=
30:48","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty // He reset gen card and gen manually started","MINKA NICOLA=
S","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, site went down because Gen failed to started due to Gen card faullty /=
/ He reset gen card and gen manually started","gerard.tchangoue@matech-came=
roun.com","548","09-06-2025 19:53:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005216045","MEHANDAN=
","","09-06-2025 19:52:10","09-06-2025 19:44:03","09-06-2025 20:01:46","Cas=
caded Incident from TTO5369613","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid return","system"=
,"267651","09-06-2025 19:52:10","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005216038","O=
dza II OCM","IHS_YND_528","09-06-2025 19:51:20","09-06-2025 19:44:03","09-0=
6-2025 20:01:46","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid return","Albran Byorel","Equipment =
Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuati=
ons, site went down because gen failed to start due to PWC ZTE malfunction =
// Grid return","edwige.kapawo@matech-cameroun.com","439","09-06-2025 19:51=
:20","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005216029","Ron=
d Point Express1114","","09-06-2025 19:49:49","09-06-2025 19:41:45","09-06-=
2025 21:59:18","Grid outage, Site went down because Gen start and stopped w=
ith ""High temps ""alarm // he added water and manually start the Gen","Hye=
mafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Te=
mp - Coolant Level Issue","Grid outage, Site went down because Gen start an=
d stopped with ""High temps ""alarm // he added water and manually start th=
e Gen","gerard.tchangoue@matech-cameroun.com","485","09-06-2025 19:49:49","=
MATECH CMR"
"Closed Complete","Site Down","T0532","IHS_YND_239","NOCINC0005215930","Men=
dong2","","09-06-2025 19:38:55","06-06-2025 04:23:09","06-06-2025 04:35:09"=
,"Backtracking Active// No power issue on site Ubaie=3D54,2V site on Grid ,=
 The TX FME Mbah Oiah //699699694 from Huawei is informed","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Backtracking Active// No power issue on site Ubaie=3D54,2V sit=
e on Grid , The TX FME Mbah Oiah //699699694 from Huawei is informed","gera=
rd.tchangoue@matech-cameroun.com","314147","09-06-2025 19:38:55","MATECH CM=
R"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0005215834","BIY=
EMASSI NIKI","IHS_YND_546","09-06-2025 19:22:57","09-06-2025 19:16:38","09-=
06-2025 21:29:41","Grid outage, gen ran until fuel shortage//Refueling done=
","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid o=
utage, gen ran until fuel shortage//Refueling done","edwige.kapawo@matech-c=
ameroun.com","380","09-06-2025 19:22:57","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0005215806","B=
iyemassi LAC","","09-06-2025 19:18:25","09-06-2025 19:16:38","09-06-2025 21=
:29:06","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","Grid outage, gen ran until fuel shortage//Refueling done","edwige.kapawo=
@matech-cameroun.com","269285","09-06-2025 19:18:25","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005215790","MEF=
OU ASSI","","09-06-2025 19:16:36","06-06-2025 02:49:11","06-06-2025 02:59:1=
1","Backtracking ACTIVE// No power issue on site U=3D53,1v site on grid The=
 Tx lionel tchatchou //694693436 from Huawei is informed","Fanda Brice","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Backtracking ACTIVE// No power issue on site U=3D53,6v site on gri=
d The Tx lionel tchatchou //694693436 from Huawei is informed","gerard.tcha=
ngoue@matech-cameroun.com","318447","09-06-2025 19:16:36","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005215677","Fou=
da Quarter","","09-06-2025 18:56:05","09-06-2025 18:48:50","09-06-2025 18:5=
8:46","Grid outage, site went down because gen failed to start due to grid =
bad voltage and no RCP// He bypassed Grid and started Gen manually","Delor =
Telezing","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid outage, site went down because gen failed to start due to gri=
d bad voltage and no RCP// He bypassed Grid and started Gen manually","ludi=
vine.ngamaleu@ihstowers.com","436","09-06-2025 18:56:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005215658","SOA VILL=
AGE","","09-06-2025 18:52:40","09-06-2025 18:47:37","09-06-2025 19:21:11","=
Cascaded Incident from TTO5369169","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage gen failed to start due=
 to alarm high temp//We add water and gen manually started","system","12203=
70","09-06-2025 18:52:41","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005215655","SOA=
 TOWN","IHS_YND_323","09-06-2025 18:51:58","09-06-2025 18:47:37","09-06-202=
5 19:21:46","Grid outage gen failed to start due to alarm high temp//We add=
 water and gen manually started","Siligap Boris","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage =
gen failed to start due to alarm high temp//We add water and gen manually s=
tarted","gerard.tchangoue@matech-cameroun.com","262","09-06-2025 18:51:58",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005215538","MEHANDAN=
","","09-06-2025 18:39:27","09-06-2025 18:36:36","09-06-2025 18:38:01","Cas=
caded Incident from TTO5369037","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Grid stabilized","sys=
tem","171","09-06-2025 18:39:27","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005215534","O=
dza II OCM","IHS_YND_528","09-06-2025 18:38:42","09-06-2025 18:36:36","09-0=
6-2025 18:38:01","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Grid stabilized","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Grid stabilized","edwige.kapawo@matech-cameroun.com","128","09-06-20=
25 18:38:42","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0005215529","H=
-Paradis","","09-06-2025 18:38:11","09-06-2025 18:32:06","09-06-2025 20:23:=
29","Active// no power issue, site is on grid with Ubaie: 54.5V, Symphorien=
(650257151) from Huawei is informed","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active// no power issue=
, site is on grid with Ubaie: 54.5V, Symphorien(650257151) from Huawei is i=
nformed","edwige.kapawo@matech-cameroun.com","366","09-06-2025 18:38:11","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005215527","N=
gousso-Savana","IHS_YND_561","09-06-2025 18:37:33","09-06-2025 18:32:13","0=
9-06-2025 19:16:01","Active // No power issue, site is on grid with Ubaie: =
52.6V, Symphorien(650257151) from Huawei is informed. Notice that  (we have=
 disjunction in the BTS OCM / Disjunctor rearmed)","Siligap Boris","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active // No power issue, site is on grid with Ubaie: 52.6V, Symphorien=
(650257151) from Huawei is informed. Notice that  (we have disjunction in t=
he BTS OCM / Disjunctor rearmed)","edwige.kapawo@matech-cameroun.com","321"=
,"09-06-2025 18:37:33","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0005215487","Ona=
ngondi (melen bikop)","","09-06-2025 18:33:59","09-06-2025 18:11:25","09-06=
-2025 21:42:15","Grid outage, site went down because gen failed to start du=
e to battery gen faulty // Gen manually with external battery","Fanda Brice=
","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid =
outage, site went down because gen failed to start due to battery gen fault=
y // Gen manually with external battery","ludivine.ngamaleu@ihstowers.com",=
"1355","09-06-2025 18:33:59","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005215472","A=
wae Escalier","","09-06-2025 18:30:44","09-06-2025 18:21:38","09-06-2025 20=
:21:02","Active//No power issue site on Grid with U=3D51.4V ,The FME TX Hen=
ry (699949693) from Huawei is informed","Albran Byorel","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue site on Grid with U=3D51.4V ,The FME TX Henry (699949693) f=
rom Huawei is informed","gerard.tchangoue@matech-cameroun.com","547","09-06=
-2025 18:30:44","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0005215460","Clu=
b France","","09-06-2025 18:28:01","09-06-2025 18:22:55","09-06-2025 19:33:=
55","Grid only site, No space to deploy a MDG // Grid restored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site,=
 No space to deploy a MDG // Grid restored","gerard.tchangoue@matech-camero=
un.com","306","09-06-2025 18:28:01","MATECH CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0005215428","Av =
Kennedy","","09-06-2025 18:22:18","06-06-2025 05:54:50","06-06-2025 05:55:5=
0","Backtracking Active//No power issue, site is on Grid with Ubaie=3D56 V,=
 Eloundou bertrant(652586578) from Huawei is informed","","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Backt=
racking Active//No power issue, site is on Grid with Ubaie=3D56 V, Eloundou=
 bertrant(652586578) from Huawei is informed","gerard.tchangoue@matech-came=
roun.com","304049","09-06-2025 18:22:18","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005215348","NKO=
MKANA ELIZA HOTEL","","09-06-2025 18:12:21","09-06-2025 18:11:10","09-06-20=
25 18:36:04","Site went down due to PWC Overloaded and SS IHS Bernard Atang=
ana confirmed // Site stabilised","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overloaded and =
SS IHS Bernard Atangana confirmed // Site stabilised","gerard.tchangoue@mat=
ech-cameroun.com","72","09-06-2025 18:12:21","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005215341","Odz=
a petit marche new","","09-06-2025 18:10:51","09-06-2025 18:03:43","09-06-2=
025 20:25:35","(Very Unstable site) Site went down due to insufficient rect=
ifiers on site //Site stabilised","Albran Byorel","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","(Very Unstable site) Site went down due=
 to insufficient rectifiers on site //Site stabilised","gerard.tchangoue@ma=
tech-cameroun.com","428","09-06-2025 18:10:51","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005215313","Ron=
d Point Express1114","","09-06-2025 18:06:56","09-06-2025 18:02:26","09-06-=
2025 18:44:50","Grid outage,gen failed to start due to alarm ""high temp"" =
//We add water and gen manually started","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gri=
d outage,gen failed to start due to alarm ""high temp"" //We add water and =
gen manually started","gerard.tchangoue@matech-cameroun.com","271","09-06-2=
025 18:06:56","MATECH CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0005215185","Av =
Kennedy","","09-06-2025 17:47:49","06-06-2025 02:35:07","06-06-2025 02:36:3=
0","Backtracking Active//No power issue, site is on Grid with Ubaie=3D56 V,=
 Eloundou bertrant(652586578) from Huawei is informed","","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Backt=
racking Active//No power issue, site is on Grid with Ubaie=3D56 V, Eloundou=
 bertrant(652586578) from Huawei is informed","gerard.tchangoue@matech-came=
roun.com","313963","09-06-2025 17:47:49","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005215098","Efo=
ulan MTN","","09-06-2025 17:33:04","09-06-2025 17:28:54","09-06-2025 17:48:=
30","Site went down due to insufficient recfiers on site //Site stabilised"=
,"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient recfiers on site //Site stabilised","=
gerard.tchangoue@matech-cameroun.com","251","09-06-2025 17:33:04","MATECH C=
MR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0005214996","S=
AA 2","","09-06-2025 17:15:56","05-06-2025 22:09:43","05-06-2025 22:24:58",=
"Bactracking No power issue site on grid with U=3D54v//site up at 10:24 PM"=
,"Parker Tchoup","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Bactracking No power issue site on grid with U=
=3D54v//site up at 10:24 PM","mouliom.anselme@matech-cameroun.com","327973"=
,"09-06-2025 17:15:56","MATECH CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0005214982","OLA=
MA","","09-06-2025 17:11:45","09-06-2025 17:02:59","09-06-2025 17:42:11","G=
rid outage, site went down due to Grid bad voltage and no RCP on site // He=
 bypassed Grid and started Gen manually","Fanda Brice","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid outage, site wen=
t down due to Grid bad voltage and no RCP on site // He bypassed Grid and s=
tarted Gen manually","gerard.tchangoue@matech-cameroun.com","527","09-06-20=
25 17:11:45","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0005214956","Fou=
da Quarter","","09-06-2025 17:08:19","09-06-2025 16:57:02","09-06-2025 18:2=
5:23","Grid outage,site went down because Gen failed to start due to RCP on=
 site faulty//He added a 220V RELAY on site","Delor Telezing","Equipment Re=
pair","Passive","Control Panel","ATS Relay Faulty","Grid outage,site went d=
own because Gen failed to start due to RCP on site faulty//He added a 220V =
RELAY on site","ludivine.ngamaleu@ihstowers.com","678","09-06-2025 17:08:19=
","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0005214904","Y=
oko OCM","","09-06-2025 16:59:09","05-06-2025 22:17:44","05-06-2025 22:19:2=
4","Batracking No power issue site on grid with U=3D54V//Site up at 10:31 P=
M","Parker Tchoup","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Batracking No power issue site on grid with =
U=3D54V//Site up at 10:31 PM","mouliom.anselme@matech-cameroun.com","326486=
","09-06-2025 16:59:09","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005214539","E=
ssomba","","09-06-2025 16:06:02","09-06-2025 16:01:57","09-06-2025 19:17:52=
","(Unstable site) Site went down because PWC overload  // Grid return","Mb=
a Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","(Unstable site) Site went down because PWC overload  // Grid r=
eturn","edwige.kapawo@matech-cameroun.com","247","09-06-2025 16:06:02","MAT=
ECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005214421","Mok=
olo Yaounde","","09-06-2025 15:47:18","09-06-2025 15:46:07","09-06-2025 17:=
11:18","Site went down due to insufficient of rectifier on site SS IHS Bern=
ard is informed // Site stabilised","","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to insufficient of rectifier on=
 site SS IHS Bernard is informed // Site stabilised","gerard.tchangoue@mate=
ch-cameroun.com","73","09-06-2025 15:47:18","MATECH CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0005214393","Ole=
mbe","","09-06-2025 15:43:10","09-06-2025 15:42:03","09-06-2025 15:44:43","=
Site went down due to insufficiency of rectifiers on site  // He added 01 r=
ectifier (01/07)","Fabrice Pouakam","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down due to insufficiency of rectifiers on =
site  // He added 01 rectifier (01/07)","gerard.tchangoue@matech-cameroun.c=
om","69","09-06-2025 15:43:10","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005214175","M=
eyo","","09-06-2025 15:08:51","09-06-2025 15:06:44","09-06-2025 15:18:38","=
Site went Down because SS IHS Felix ZAMBE was on site for work // End of wo=
rks","Hyemafo Gildas","Equipment Replacement","Passive","Planned Activity",=
"Planned Activity - Passive","Site went Down because SS IHS Felix ZAMBE was=
 on site for work // End of works","edwige.kapawo@matech-cameroun.com","128=
","09-06-2025 15:08:51","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005213944","Odz=
a petit marche new","","09-06-2025 14:36:54","09-06-2025 14:36:36","09-06-2=
025 17:53:42","Site went down due to insufficient rectifiers on site //Site=
 stabilised","Albran Byorel","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to insufficient rectifiers on site //Site=
 stabilised","gerard.tchangoue@matech-cameroun.com","18","09-06-2025 14:36:=
54","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005213938","M=
ontee-Des-Soeurs","","09-06-2025 14:36:44","09-06-2025 14:28:37","09-06-202=
5 14:58:26","Site went Down due to Gen Overload // Grid return","Hyemafo Gi=
ldas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went =
Down due to Gen Overload // Grid return","edwige.kapawo@matech-cameroun.com=
","488","09-06-2025 14:36:44","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005213853","N=
gousso-Savana","IHS_YND_561","09-06-2025 14:24:50","09-06-2025 14:22:45","0=
9-06-2025 17:54:09","Active // No power issue, site is on grid with Ubaie: =
52.6V, Symphorien(650257151) from Huawei is informed. Notice that  (we have=
 disjunction in the BTS OCM / Disjunctor rearmed)","Siligap Boris","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active // No power issue, site is on grid with Ubaie: 52.6V, Symphorien=
(650257151) from Huawei is informed. Notice that  (we have disjunction in t=
he BTS OCM / Disjunctor rearmed)","christelle.ngonga@matech-cameroun.com","=
126","09-06-2025 14:24:50","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005213839","F=
OUGEROLE","","09-06-2025 14:23:02","09-06-2025 14:22:45","09-06-2025 19:16:=
01","","Siligap Boris","Cascade Outage","Active","Cascade Active","Cascade =
Active","Active // No power issue, site is on grid with Ubaie: 52.6V, Symph=
orien(650257151) from Huawei is informed","christelle.ngonga@matech-camerou=
n.com","279793","09-06-2025 14:23:02","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005213272","A=
WAE OCM","","09-06-2025 12:52:16","09-06-2025 12:51:00","09-06-2025 13:22:4=
3","Grid outage site went down because Gen failed to start due PWC ZTE dysf=
unction // He reset the PWC and site on Grid","Mba Lazare Herve","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage s=
ite went down because Gen failed to start due PWC ZTE dysfunction // He res=
et the PWC and site on Grid","christelle.ngonga@matech-cameroun.com","77","=
09-06-2025 12:52:16","MATECH CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005213212","Mey=
o","","09-06-2025 12:46:49","09-06-2025 12:41:59","09-06-2025 13:25:18","AC=
TIVE //No power issue U=3D 54,6v Site on Grid The Tx Fme Georges /697466181=
4 from huawei is informed","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE //No power i=
ssue U=3D 54,6v Site on Grid The Tx Fme Georges /6974661814 from huawei is =
informed","franck.nkomot@matech-cameroun.com","560","09-06-2025 12:46:49","=
MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005213022","M=
vog-Ada_OCM","","09-06-2025 12:21:47","09-06-2025 12:20:40","09-06-2025 12:=
49:40","Grid Only site, No space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only sit=
e, No space to deploy MDGE // Grid returned","christelle.ngonga@matech-came=
roun.com","68","09-06-2025 12:21:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005212849","Acropole=
","","09-06-2025 12:01:45","09-06-2025 11:42:05","09-06-2025 15:47:37","Cas=
caded Incident from TTO5365812","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Site went down due to insufficient of rec=
tifier on site //Site stabilised","system","332509","09-06-2025 12:01:45","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005212841","C-Suprem=
e","","09-06-2025 12:00:58","09-06-2025 11:42:05","09-06-2025 15:47:37","Ca=
scaded Incident from TTO5365812","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","Site went down due to insufficient of rectifier on si=
te //Site stabilised","system","332509","09-06-2025 12:00:58","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005212740","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","09-06-2025 11:43:11","09-06-2025 1=
1:42:05","09-06-2025 15:47:37","(  Site very  unstable  )   Site went down =
due to insufficient of rectifier on site ","MINKA NICOLAS","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Site=
 went down due to insufficient of rectifier on site //Site stabilised","chr=
istelle.ngonga@matech-cameroun.com","67","09-06-2025 11:43:11","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005212727","Men=
dong Plateau","","09-06-2025 11:42:04","09-06-2025 11:37:58","09-06-2025 13=
:06:58","Site went down because the fuel was not reaching the GE injectors =
// he removed and purged them, Grid returned","Hyemafo Gildas","Fuel Outage=
 (Probable)","Passive","ACDG Gen","ACDG - Injector Pump","Site went down be=
cause the fuel was not reaching the GE injectors // he removed and purged t=
hem, Grid returned","franck.nkomot@matech-cameroun.com","247","09-06-2025 1=
1:42:04","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005212696","M=
ontee-Des-Soeurs","","09-06-2025 11:35:47","09-06-2025 11:32:41","09-06-202=
5 13:17:19","Site Went Down due to Gen Overload // Grid return ","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site Went=
 Down due to Gen Overload // Grid return ","christelle.ngonga@matech-camero=
un.com","187","09-06-2025 11:35:47","MATECH CMR"
"Closed Complete","Site Down","CTR_419","IHS_YND_227","NOCINC0005212521","M=
vog Betsi","","09-06-2025 11:12:56","09-06-2025 11:12:52","09-06-2025 11:23=
:52","Grid-Gen, eneo fluctuation, site down due to poor backup // Grid retu=
rn","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Grid O=
utage Issue","Grid-Gen, eneo fluctuation, site down due to poor backup // G=
rid return","christelle.ngonga@matech-cameroun.com","4","09-06-2025 11:12:5=
6","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005212516","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","09-06-2025 11:12:00","09-06-2025 1=
1:08:52","09-06-2025 11:11:30","Grid outage , site went down before Gen fai=
led to started due to poor battery backup // Grid restoration","MINKA NICOL=
AS","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery L=
ow","Grid outage , site went down before Gen failed to started due to poor =
battery backup // Grid restoration","christelle.ngonga@matech-cameroun.com"=
,"189","09-06-2025 11:12:00","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005212514","Odz=
a petit marche new","","09-06-2025 11:11:35","09-06-2025 11:09:13","09-06-2=
025 14:30:51","Site went down due to insufficient rectifiers on site //Site=
 stabilised","Albran Byorel","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to insufficient rectifiers on site //Site=
 stabilised","franck.nkomot@matech-cameroun.com","143","09-06-2025 11:11:35=
","MATECH CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0005212513","A=
cropole","","09-06-2025 11:11:22","09-06-2025 11:08:52","09-06-2025 11:11:3=
0","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage , site went down before Gen failed to started due to=
 poor battery backup // Grid restoration","christelle.ngonga@matech-camerou=
n.com","262665","09-06-2025 11:11:22","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005212506","C=
omplexe-BEAC","","09-06-2025 11:10:19","09-06-2025 11:08:12","09-06-2025 11=
:11:33","Site went down due malfunction of rectifier // Site stabilized","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down due malfunction of rectifier // Site stabilized","christelle=
.ngonga@matech-cameroun.com","128","09-06-2025 11:10:19","MATECH CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0005212444","H=
-Franco New","","09-06-2025 10:56:24","09-06-2025 10:53:17","09-06-2025 12:=
22:34","Site went down due to disjunction of CB (125A) in the PWC ZTE // He=
 rearmed it","Delor Telezing","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Circuit Breaker Issue","Site went down due to disjunction =
of CB (125A) in the PWC ZTE // He rearmed it","christelle.ngonga@matech-cam=
eroun.com","187","09-06-2025 10:56:24","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005212427","A=
wae Ewonkan","","09-06-2025 10:55:08","09-06-2025 10:53:54","09-06-2025 13:=
58:10","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed //Site stabilised","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed //Site s=
tabilised","christelle.ngonga@matech-cameroun.com","75","09-06-2025 10:55:0=
8","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005212404","C=
-Supreme","","09-06-2025 10:52:21","09-06-2025 11:08:52","09-06-2025 11:11:=
30","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage , site went down before Gen failed to started due to poor batter=
y backup // Grid restoration","christelle.ngonga@matech-cameroun.com","2626=
65","09-06-2025 10:52:21","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005212028","C=
rf-Nsam","","09-06-2025 09:54:28","09-06-2025 09:51:21","09-06-2025 09:59:4=
8","No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (69=
9949693) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site Ubaie =3D53.6V site on Grid The TX FME Henri (699949693) from Hua=
wei is informed","christelle.ngonga@matech-cameroun.com","188","09-06-2025 =
09:54:28","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005212003","Mok=
olo Yaounde","","09-06-2025 09:46:54","09-06-2025 09:44:13","09-06-2025 09:=
49:13","Active // No power issue Ubay: 52.5 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 52.5 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","franck.nkomot@matech-cameroun.com","162"=
,"09-06-2025 09:46:54","MATECH CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0005211974","N=
gousso OCM","","09-06-2025 09:44:05","09-06-2025 09:41:49","09-06-2025 10:0=
1:37","No power issue on site U=3D54,5V , Site is on Grid and The FME TX Ar=
mand Nguesta (699949553) From Huawei is informed","Siligap Boris","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site U=3D54,5V , Site is on Grid and The FME TX Armand=
 Nguesta (699949553) From Huawei is informed","christelle.ngonga@matech-cam=
eroun.com","137","09-06-2025 09:44:05","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005211898","C=
NR","","09-06-2025 09:31:53","09-06-2025 09:24:47","09-06-2025 09:36:02","S=
ite impacted by CNDH wish is not  IHS site","Mboua Thierry","Customer Equip=
ment Failure","Active","Active Equipment Failure","Affected by 3rd Party Si=
te","Site impacted by CNDH wish is not  IHS site","christelle.ngonga@matech=
-cameroun.com","426","09-06-2025 09:31:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005211696","Mom","",=
"09-06-2025 08:58:06","09-06-2025 08:49:36","09-06-2025 09:27:36","Cascaded=
 Incident from TTO5364571","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, Site went down because Gen start=
 and stopped with ""High temps ""alarm // he added water and manually start=
 the Gen","system","1212927","09-06-2025 08:58:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005211695","OTELE MT=
N","","09-06-2025 08:58:06","09-06-2025 08:49:36","09-06-2025 09:27:36","Ca=
scaded Incident from TTO5364571","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, Site went down because Gen=
 start and stopped with ""High temps ""alarm // he added water and manually=
 start the Gen","system","1212927","09-06-2025 08:58:06","MATECH CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0005211646","M=
inka","IHS_YND_369, IHS_YND_531, IHS_YND_370, IHS_YND_372","09-06-2025 08:4=
9:42","09-06-2025 08:44:36","09-06-2025 09:30:36","Grid outage, Site went d=
own because Gen start and stopped with ""High temps ""alarm // he added wat=
er and manually start the Gen","Fanda Brice","Equipment Repair","Passive","=
ACDG Gen","Gen Temp High","Grid outage, Site went down because Gen start an=
d stopped with ""High temps ""alarm // he added water and manually start th=
e Gen","christelle.ngonga@matech-cameroun.com","307","09-06-2025 08:49:42",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0005211643","B=
ondjock","","09-06-2025 08:48:19","09-06-2025 08:44:36","09-06-2025 09:30:3=
6","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, Site went down because Gen start and stopped with ""H=
igh temps ""alarm // he added water and manually start the Gen","christelle=
.ngonga@matech-cameroun.com","1485","09-06-2025 08:48:19","MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0005211634","M=
beng","","09-06-2025 08:46:59","09-06-2025 08:44:36","09-06-2025 09:30:36",=
"","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage, Site went down because Gen start and stopped with ""High=
 temps ""alarm // he added water and manually start the Gen","christelle.ng=
onga@matech-cameroun.com","1545","09-06-2025 08:46:59","MATECH CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0005211556","Oko=
la","","09-06-2025 08:33:53","09-06-2025 08:24:00","09-06-2025 08:40:00","G=
rid outage, Site went down because Gen start and stopped with ""High temps =
""alarm // he added water and manually start the Gen","TIENTCHEU NZETCHIEU =
GAEL","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage,=
 Site went down because Gen start and stopped with ""High temps ""alarm // =
he added water and manually start the Gen","franck.nkomot@matech-cameroun.c=
om","594","09-06-2025 08:33:53","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005211299","Odz=
a petit marche new","","09-06-2025 07:49:59","09-06-2025 07:41:00","09-06-2=
025 10:59:00","(Very Unstable site) Site went down due to insufficient rect=
ifiers on site //Site stabilised","Albran Byorel","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","(Very Unstable site) Site went down due=
 to insufficient rectifiers on site //Site stabilised","franck.nkomot@matec=
h-cameroun.com","540","09-06-2025 07:49:59","MATECH CMR"
"Cancelled","Warning","CTR_554","IHS_YND_174","NOCINC0005211059","Carrefour=
t Nkomo","","09-06-2025 06:54:01","","","Error ticket logged","Mba Lazare H=
erve","","","","","","christelle.ngonga@matech-cameroun.com","68","09-06-20=
25 06:54:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005210656","MEHANDAN=
","","09-06-2025 05:11:04","09-06-2025 05:06:49","09-06-2025 06:29:48","Cas=
caded Incident from TTO5363420","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to PWC=
 ZTE dysfunctionment //He reset  , site on Gen","system","269908","09-06-20=
25 05:11:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0005210655","Odza II =
OCM","","09-06-2025 05:11:04","09-06-2025 05:06:49","09-06-2025 06:29:48","=
Cascaded Incident from TTO5363420","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
PWC ZTE dysfunctionment //He reset  , site on Gen","system","269908","09-06=
-2025 05:11:04","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005210648","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","09-06-2025 05:09:25","09=
-06-2025 05:06:49","09-06-2025 06:29:48","Grid outage, site went down due t=
o PWC ZTE dysfunctionment //He reset  , site on Gen","Albran Byorel","Equip=
ment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outa=
ge, site went down due to PWC ZTE dysfunctionment //He reset  , site on Gen=
","vanel.mbiada@matech-cameroun.com","157","09-06-2025 05:09:25","MATECH CM=
R"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005210155","Odz=
a petit marche new","","09-06-2025 02:02:20","09-06-2025 02:00:12","09-06-2=
025 06:21:24","(Unstable site)Site went down due to insufficient rectifiers=
 on site //Site stabilised","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down due to insufficient rectifiers=
 on site //Site stabilised","cedric.tiani@matech-cameroun.com","129","09-06=
-2025 02:02:20","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005209984","Mam=
ch Building","","09-06-2025 00:57:51","09-06-2025 00:49:42","09-06-2025 01:=
35:48","Grid outage, Site went down because Gen ran until fuel shortage// R=
efueling Done","Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, Site went down because Gen ran until fuel shortage// Ref=
ueling Done","cedric.tiani@matech-cameroun.com","490","09-06-2025 00:57:51"=
,"MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0005209978","Mam=
bine","","09-06-2025 00:55:14","09-06-2025 00:45:59","09-06-2025 01:19:33",=
"Grid outage, Site went down because Gen ran until fuel shortage// Refuelin=
g Done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Gri=
d outage, Site went down because Gen ran until fuel shortage// Refueling Do=
ne","cedric.tiani@matech-cameroun.com","556","09-06-2025 00:55:14","MATECH =
CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005209975","O=
lembe-Terminus","","09-06-2025 00:53:56","09-06-2025 00:49:47","09-06-2025 =
01:37:31","Acces issues during the night(FME Fabrice report insecurity)","F=
abrice Pouakam","Access Denial","Lease Or Legal","Landlord Related Issues",=
"Access Issue - Land Lord","Acces issues during the night(FME Fabrice repor=
t insecurity)","vanel.mbiada@matech-cameroun.com","251","09-06-2025 00:53:5=
6","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005209972","M=
vog-Manga","","09-06-2025 00:52:38","09-06-2025 00:44:55","09-06-2025 01:00=
:11","Grid outage site went down due to PWC dysunction//Site stabilised","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Ov=
erloaded","Grid outage site went down due to PWC dysunction//Site stabilise=
d","vanel.mbiada@matech-cameroun.com","464","09-06-2025 00:52:38","MATECH C=
MR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005209964","O=
kola OCM","","09-06-2025 00:46:57","09-06-2025 00:13:27","09-06-2025 05:44:=
22","Site went down because 02/03 rectifiers dysfunctionned// He reset rect=
ifiers","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down because 02/03 rectifiers dysfunctionned=
// He reset rectifiers","vanel.mbiada@matech-cameroun.com","2011","09-06-20=
25 00:46:57","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005209856","S=
atcom","","09-06-2025 00:15:00","09-06-2025 00:09:48","09-06-2025 00:41:32"=
,"Active // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand =
Ngestsa (691144412) of huawei is informed","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand Ngest=
sa (691144412) of huawei is informed","vanel.mbiada@matech-cameroun.com","3=
14","09-06-2025 00:15:00","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005209854","C=
rf-Nsam","","09-06-2025 00:14:14","09-06-2025 00:06:54","09-06-2025 00:39:2=
0","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","vanel.mbiada@matech-cameroun.com","441","=
09-06-2025 00:14:14","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0005209774","Meh=
anda 1","","08-06-2025 23:57:23","08-06-2025 23:51:06","09-06-2025 08:49:06=
","Access issue due to landlord .Grid outage.site went down due to grid flu=
ctuations//We bypass grid and gen manually started ","Albran Byorel","Acces=
s Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land L=
ord","Access issue due to landlord .Grid outage.site went down due to grid =
fluctuations//We bypass grid and gen manually started ","cedric.tiani@matec=
h-cameroun.com","378","08-06-2025 23:57:23","MATECH CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0005209767","Ole=
mbe","","08-06-2025 23:56:14","08-06-2025 23:53:57","09-06-2025 01:19:31","=
Grid outage, Site went down because Gen ran until fuel shortage// Refueling=
 Done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, Site went down because Gen ran until fuel shortage// Refueling=
 Done","cedric.tiani@matech-cameroun.com","138","08-06-2025 23:56:14","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005209764","O=
dza II OCM","","08-06-2025 23:55:29","08-06-2025 23:46:28","09-06-2025 01:0=
8:22","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, site went down due to PWC ZTE dysfunctionment //=
He reset it and site on Gen","vanel.mbiada@matech-cameroun.com","267472","0=
8-06-2025 23:55:29","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005209755","O=
dza-PK10","IHS_YND_527","08-06-2025 23:51:06","08-06-2025 23:46:28","09-06-=
2025 01:08:22","Grid outage, site went down due to PWC ZTE dysfunctionment =
//He reset it and site on Gen","Albran Byorel","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage, site went down due=
 to PWC ZTE dysfunctionment //He reset it and site on Gen","vanel.mbiada@ma=
tech-cameroun.com","279","08-06-2025 23:51:06","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0005209738","Tsi=
nga village","","08-06-2025 23:46:26","08-06-2025 23:42:20","09-06-2025 00:=
30:02","Site went down because Gen failed to start due to Grid bad voltage =
// he bypass the Grid and Gen manually started","Delor Telezing","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","Site went d=
own because Gen failed to start due to Grid bad voltage // he bypass the Gr=
id and Gen manually started","cedric.tiani@matech-cameroun.com","247","08-0=
6-2025 23:46:26","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005209591","O=
dza II OCM","","08-06-2025 23:13:07","08-06-2025 23:10:53","08-06-2025 23:2=
4:08","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Gri stabilize","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, site went down b=
ecause gen failed to start due to PWC ZTE malfunction // Gri stabilize","va=
nel.mbiada@matech-cameroun.com","136","08-06-2025 23:13:07","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005209508","M=
EHANDAN","","08-06-2025 22:54:26","08-06-2025 22:50:54","09-06-2025 01:48:4=
2","Grid outage,Site went down because Gen failed to start due to PWC ZTE d=
ysfunction//He reset it and site on Grid","Albran Byorel","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","Grid outage,Site wen=
t down because Gen failed to start due to PWC ZTE dysfunction//He reset it =
and site on Grid","vanel.mbiada@matech-cameroun.com","214","08-06-2025 22:5=
4:26","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0005209462","N=
goulmekong-Nord","","08-06-2025 22:44:32","08-06-2025 22:42:10","08-06-2025=
 22:45:07","Site went down due to 01/06 rectifiers alarming on site//He res=
et it and site on Grid","Siligap Boris","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down due to 01/06 rectifiers alarming o=
n site//He reset it and site on Grid","vanel.mbiada@matech-cameroun.com","1=
43","08-06-2025 22:44:32","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005209450","C=
omplexe-BEAC","","08-06-2025 22:40:01","08-06-2025 22:31:54","09-06-2025 01=
:41:49","No power issue on site ,site on Grid with U=3D48 v  Tx FME Lionnel=
// 655184876 from Huawei is informed","Albran Byorel","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site ,site on Grid with U=3D48 v  Tx FME Lionnel// 655184876 from =
Huawei is informed","vanel.mbiada@matech-cameroun.com","488","08-06-2025 22=
:40:01","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005209448","Odz=
a petit marche new","","08-06-2025 22:39:52","08-06-2025 22:38:42","09-06-2=
025 01:57:24","Site went down due to insufficient rectifiers on site //Site=
 stabilised","Albran Byorel","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to insufficient rectifiers on site //Site=
 stabilised","cedric.tiani@matech-cameroun.com","71","08-06-2025 22:39:52",=
"MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005209371","ODZ=
A MINKAN EDIBI ASSI","","08-06-2025 22:26:25","08-06-2025 22:25:00","09-06-=
2025 01:07:42","Grid Outage, site went down because gen failed to start due=
 to PWC ZTE malfunction // He reset it and started the Gen manually","Albra=
n Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overlo=
aded","Grid Outage, site went down because gen failed to start due to PWC Z=
TE malfunction // He reset it and started the Gen manually","franck.nkomot@=
matech-cameroun.com","86","08-06-2025 22:26:25","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005209261","Eko=
umdoum OCM","","08-06-2025 22:15:30","08-06-2025 22:13:23","09-06-2025 06:2=
9:48","Grid outage,site went down because Gen failed to start due to PWC ZT=
E not configured//He started the Gen manually","Albran Byorel","Equipment R=
epair","Passive","Control Panel","ATS-AMF Issue","Grid outage,site went dow=
n because Gen failed to start due to PWC ZTE not configured//He started the=
 Gen manually","franck.nkomot@matech-cameroun.com","128","08-06-2025 22:15:=
30","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005209163","SIM=
BOCK BONAMBAPE","","08-06-2025 22:00:18","08-06-2025 21:58:04","08-06-2025 =
22:00:04","Grid Outage, Site went down before Gen start due to poor backup =
// Gen Started Automatically","Hyemafo Gildas","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid Outage, Site went down=
 before Gen start due to poor backup // Gen Started Automatically","franck.=
nkomot@matech-cameroun.com","135","08-06-2025 22:00:18","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005209139","OBA=
M NGOLA OCM","","08-06-2025 21:54:23","08-06-2025 21:20:58","08-06-2025 22:=
56:21","Grid outage, site went down baecause gen failed to start due to Gen=
 card faulty // Gen manually started","MINKA NICOLAS","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down baec=
ause gen failed to start due to Gen card faulty // Gen manually started","f=
ranck.nkomot@matech-cameroun.com","2006","08-06-2025 21:54:23","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005209114","Eki=
e sud","","08-06-2025 21:49:19","08-06-2025 21:47:14","08-06-2025 22:56:40"=
,"Site went down due to PWC ZTE dysfunction//He reset it and site on Grid",=
"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","Site went down due to PWC ZTE dysfunction//He reset it and sit=
e on Grid","franck.nkomot@matech-cameroun.com","126","08-06-2025 21:49:19",=
"MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005209105","Efo=
ulan MTN","","08-06-2025 21:47:38","08-06-2025 21:40:30","08-06-2025 21:58:=
07","Site went down due to insufficient recfiers on site //Site stabilised"=
,"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient recfiers on site //Site stabilised","=
franck.nkomot@matech-cameroun.com","428","08-06-2025 21:47:38","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0005209022","A=
battoir","","08-06-2025 21:33:31","08-06-2025 21:23:59","08-06-2025 22:28:5=
6","Grid outage, site went down baecause gen failed to start due to battery=
 Gen faulty // Gen manually start with external battery","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid ou=
tage, site went down baecause gen failed to start due to battery Gen faulty=
 // Gen manually start with external battery","edwige.kapawo@matech-camerou=
n.com","573","08-06-2025 21:33:31","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005208824","Men=
dong NB","","08-06-2025 21:13:00","08-06-2025 21:08:50","09-06-2025 12:42:5=
0","Access issue at night due to landlord. Site went down due to Rectifier =
circuit breaker faulty//he replaced the rectifier circuit breaker","","Acce=
ss Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land =
Lord","Access issue at night due to landlord. Site went down due to Rectifi=
er circuit breaker faulty//he replaced the rectifier circuit breaker","fran=
ck.nkomot@matech-cameroun.com","251","08-06-2025 21:13:00","MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0005208697","Abo=
me","","08-06-2025 20:50:03","08-06-2025 20:44:52","08-06-2025 21:00:25","G=
rid outage, Site went down before Gen start due to poor backup// Gen Automa=
tically Started","MINKA NICOLAS","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup// Gen Automatically Started","franck.nkomot@matech-c=
ameroun.com","312","08-06-2025 20:50:03","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0005208575","C=
RH-Etoug-Ebe","","08-06-2025 20:24:47","08-06-2025 20:19:36","08-06-2025 20=
:35:24","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen start automatically=
","edwige.kapawo@matech-cameroun.com","312","08-06-2025 20:24:47","MATECH C=
MR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005208572","M=
ontee-Des-Soeurs","","08-06-2025 20:23:45","08-06-2025 20:13:59","08-06-202=
5 21:55:09","Site Went Down due to Gen Overload // Grid return","Hyemafo Gi=
ldas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site Went =
Down due to Gen Overload // Grid return","edwige.kapawo@matech-cameroun.com=
","588","08-06-2025 20:23:45","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005208561","Mon=
tee Jouvence","","08-06-2025 20:20:20","08-06-2025 16:38:41","08-06-2025 20=
:46:41","BACKTRACKING: Grid outage, site went down because gen failed to st=
art due to grid contactor faulty // He bypassed grid contactor and gen manu=
ally started","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACD=
G - Load Contactor","BACKTRACKING: Grid outage, site went down because gen =
failed to start due to grid contactor faulty // He bypassed grid contactor =
and gen manually started","franck.nkomot@matech-cameroun.com","13300","08-0=
6-2025 20:20:20","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005208516","E=
toug ebe Meweulo","","08-06-2025 20:09:31","08-06-2025 20:02:25","08-06-202=
5 22:27:16","Grid outage, site went down due to insufficiency of rectifiers=
 // He reset rectifers and site on Gen","Hyemafo Gildas","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Grid outage, site went down due =
to insufficiency of rectifiers // He reset rectifers and site on Gen","edwi=
ge.kapawo@matech-cameroun.com","427","08-06-2025 20:09:31","MATECH CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0005208492","M=
obil-Kondengui","","08-06-2025 20:04:47","08-06-2025 20:01:37","08-06-2025 =
22:10:55","Site went down due to disjunction of CB(60A) TGBT that aliment P=
WC due to charge  //He rearmed it","","Equipment Repair","Passive","Rectifi=
er","Rectifier - Circuit Breaker","Site went down due to disjunction of CB(=
60A) TGBT that aliment PWC due to charge  //He rearmed it","edwige.kapawo@m=
atech-cameroun.com","191","08-06-2025 20:04:47","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005208363","Bar=
riere","","08-06-2025 19:29:27","08-06-2025 19:23:16","08-06-2025 21:53:49"=
,"Site went down due to PWC ZTE dysfunction the ss IHS Felix is informed //=
He reset it and site on Gen","Hyemafo Gildas","Equipment Repair","Passive",=
"Rectifier","Rectifier Module Overloaded","Site went down due to PWC ZTE dy=
sfunction the ss IHS Felix is informed //He reset it and site on Gen","fran=
ck.nkomot@matech-cameroun.com","372","08-06-2025 19:29:27","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005208181","MBA=
LNGONG LYCEE","","08-06-2025 18:57:16","08-06-2025 18:11:08","10-06-2025 19=
:12:06","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // He reduced load, =
site on Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, Site went down because Gen stopped due to overload(=
9kva, 130A) SS IHS Felix Zambe is informed and confirmed // He reduced load=
, site on Gen","franck.nkomot@matech-cameroun.com","2770","08-06-2025 18:57=
:16","MATECH CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0005208068","M=
vog-Betsi","","08-06-2025 18:34:31","08-06-2025 18:25:12","08-06-2025 19:02=
:56","Site Went Down due to work PAUL (676216525/ Matech) is on the site fo=
r work (swap of bay) // End of work","Hyemafo Gildas","Equipment Replacemen=
t","Passive","Planned Activity","Planned Activity - Passive","Site Went Dow=
n due to work PAUL (676216525/ Matech) is on the site for work (swap of bay=
) // End of work","edwige.kapawo@matech-cameroun.com","560","08-06-2025 18:=
34:31","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005208037","N=
koabang2","","08-06-2025 18:30:24","08-06-2025 18:27:13","08-06-2025 18:31:=
16","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ed=
wige.kapawo@matech-cameroun.com","193","08-06-2025 18:30:24","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005207960","O=
dza II OCM","","08-06-2025 18:15:43","08-06-2025 18:12:30","08-06-2025 19:0=
3:43","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Gri stabilized","Albran Byorel","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Grid outage, site went down =
because gen failed to start due to PWC ZTE malfunction // Gri stabilized","=
edwige.kapawo@matech-cameroun.com","195","08-06-2025 18:15:43","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005207946","Nko=
abang Alembe","","08-06-2025 18:12:20","08-06-2025 17:48:50","08-06-2025 20=
:56:00","Site down due to 02/04 Rectifier dysfuntionning // He reset it: si=
te on grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site down due to 02/04 Rectifier dysfuntionning // He rese=
t it: site on grid","franck.nkomot@matech-cameroun.com","1411","08-06-2025 =
18:12:20","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005207920","Eki=
e sud","","08-06-2025 18:08:43","08-06-2025 17:56:31","08-06-2025 19:02:36"=
,"Grid outage, site went down because gen start and stopped with over volta=
ge alarm // He reset it and manually start the gen","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site =
went down because gen start and stopped with over voltage alarm // He reset=
 it and manually start the gen","franck.nkomot@matech-cameroun.com","733","=
08-06-2025 18:08:43","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005207749","A=
bom","IHS_YND_269","08-06-2025 17:39:29","08-06-2025 17:30:20","08-06-2025 =
17:49:51","Grid outage, site went down due to poor backup // Grid return","=
Siligap Boris","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Battery Low","Grid outage, site went down due to poor backup // Grid retu=
rn","edwige.kapawo@matech-cameroun.com","550","08-06-2025 17:39:29","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005207742","M=
vog-Ebanda","","08-06-2025 17:38:38","08-06-2025 17:30:20","08-06-2025 17:4=
9:51","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, site went down due to poor backup // Grid return=
","edwige.kapawo@matech-cameroun.com","268535","08-06-2025 17:38:38","MATEC=
H CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005207700","Ron=
d Point Express1114","","08-06-2025 17:34:19","08-06-2025 17:30:12","08-06-=
2025 17:48:43","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","fr=
anck.nkomot@matech-cameroun.com","248","08-06-2025 17:34:19","MATECH CMR"
"Closed Complete","Site Down","T0217","IHS_YND_018","NOCINC0005207697","P&T=
 Building","","08-06-2025 17:33:22","08-06-2025 17:27:09","08-06-2025 17:34=
:50","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space=
 to deploy a MDG//Grid Restored","franck.nkomot@matech-cameroun.com","373",=
"08-06-2025 17:33:22","MATECH CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0005207694","ENA=
M","","08-06-2025 17:32:50","08-06-2025 17:25:43","08-06-2025 17:37:19","Gr=
id outage, no space to deploy MGE // Grid returned","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage, no space to de=
ploy MGE // Grid returned","franck.nkomot@matech-cameroun.com","428","08-06=
-2025 17:32:50","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005207655","N=
komo","","08-06-2025 17:29:11","08-06-2025 16:42:50","09-06-2025 06:56:52",=
"No power issue site on grid with U=3D53.5V Lionel Adjeck (655184876) from =
Huawei is informed","Mba Lazare Herve","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D53.5V Lionel Adjeck (655184876) from Huawei is informed","edwi=
ge.kapawo@matech-cameroun.com","2781","08-06-2025 17:29:11","MATECH CMR"
"Closed Complete","Site Down","T0539","IHS_YND_034","NOCINC0005207577","EMI=
A MTN","","08-06-2025 17:17:35","08-06-2025 17:15:29","08-06-2025 17:37:25"=
,"Grid outage, Site went Down due to No space to deploy // Grid return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage, Site went Down due to No space to deploy // Grid return","franck.nkom=
ot@matech-cameroun.com","126","08-06-2025 17:17:35","MATECH CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0005207510","NKO=
LOSSAN OKOK","","08-06-2025 17:07:50","08-06-2025 17:06:39","08-06-2025 20:=
37:39","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage no Rcp // he bypass grid and manually start the gen","Par=
ker Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation, site went down because Gen failed to start due=
 to grid bad voltage no Rcp // he bypass grid and manually start the gen","=
franck.nkomot@matech-cameroun.com","71","08-06-2025 17:07:50","MATECH CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0005207503","P=
olytechnique","","08-06-2025 17:06:19","08-06-2025 16:56:59","08-06-2025 17=
:33:02","Grid Only, No space to deploy MGE // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space =
to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","561","08=
-06-2025 17:06:19","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005207491","Nko=
ulou Carriere carrefourt","","08-06-2025 17:05:38","08-06-2025 17:02:33","0=
8-06-2025 18:26:43","Grid outage, Site went down due to insufficiency of re=
ctifiers//He reset it and site on Gen","Mba Lazare Herve","Equipment Repair=
","Passive","Rectifier","Rectifier Module","Grid outage, Site went down due=
 to insufficiency of rectifiers//He reset it and site on Gen","franck.nkomo=
t@matech-cameroun.com","187","08-06-2025 17:05:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005207441","SAA 2","=
","08-06-2025 16:58:04","08-06-2025 16:51:12","08-06-2025 17:39:57","Cascad=
ed Incident from TTO5359724","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because Gen s=
tart and stopped with ""High temps"" alarm // he added water and manually s=
tart the Gen","system","1220123","08-06-2025 16:58:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005207411","Nkol-Meb=
anga","","08-06-2025 16:54:44","08-06-2025 16:51:12","08-06-2025 17:25:47",=
"Cascaded Incident from TTO5359715","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen start and stopped with ""High temps"" alarm // he added water and man=
ually start the Gen","system","270844","08-06-2025 16:54:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005207410","Carrefou=
r Ayissi Ele","","08-06-2025 16:54:43","08-06-2025 16:51:12","08-06-2025 17=
:25:47","Cascaded Incident from TTO5359715","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n because Gen start and stopped with ""High temps"" alarm // he added water=
 and manually start the Gen","system","270844","08-06-2025 16:54:43","MATEC=
H CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005207409","Saa=
","IHS_YND_810, IHS_YND_809, IHS_YND_404","08-06-2025 16:54:18","08-06-2025=
 16:51:12","08-06-2025 17:39:57","Grid outage, Site went down because Gen s=
tart and stopped with ""High temps"" alarm // he added water and manually s=
tart the Gen","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG=
 - High Engine Temp - Coolant Level Issue","Grid outage, Site went down bec=
ause Gen start and stopped with ""High temps"" alarm // he added water and =
manually start the Gen","franck.nkomot@matech-cameroun.com","187","08-06-20=
25 16:54:18","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005207398","M=
ontee-Des-Soeurs","","08-06-2025 16:52:21","08-06-2025 16:45:14","08-06-202=
5 17:30:33","Site Went Down due to  Gen Overload // grid return","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site Went=
 Down due to  Gen Overload // grid return","edwige.kapawo@matech-cameroun.c=
om","429","08-06-2025 16:52:21","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005207392","N=
YOM 2 IHS","","08-06-2025 16:51:17","08-06-2025 16:41:59","08-06-2025 19:08=
:41","Active // No power issue Ubaie:52.7 V site on Gen, site up without in=
tervention. TX fme symphorien /650257151 from huawei is informed.","Fabrice=
 Pouakam","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active // No power issue Ubaie:52.7 V site on Gen, si=
te up without intervention. TX fme symphorien /650257151 from huawei is inf=
ormed.","edwige.kapawo@matech-cameroun.com","559","08-06-2025 16:51:17","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0005207389","M=
endong Maeture","","08-06-2025 16:50:22","08-06-2025 16:36:09","08-06-2025 =
17:46:43","Grid outage, site went down because gen failed to start due to g=
rid contactor faulty // He bypassed ATS and Gen manually started","Hyemafo =
Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Gr=
id outage, site went down because gen failed to start due to grid contactor=
 faulty // He bypassed ATS and Gen manually started","edwige.kapawo@matech-=
cameroun.com","853","08-06-2025 16:50:22","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005207383","O=
lembe-Terminus","","08-06-2025 16:49:37","08-06-2025 16:39:59","08-06-2025 =
21:01:06","Grid outage, site went down because Gen failed to start due to P=
WC ZTE malfunction //He reset it and site on  Grid","Fabrice Pouakam","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid out=
age, site went down because Gen failed to start due to PWC ZTE malfunction =
//He reset it and site on  Grid","edwige.kapawo@matech-cameroun.com","580",=
"08-06-2025 16:49:37","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005207378","E=
koumdoum OCM","","08-06-2025 16:48:51","08-06-2025 16:29:44","08-06-2025 16=
:54:34","Grid outage,site went down because Gen failed to start due to Hybr=
id system malfunction // Grid return","Albran Byorel","Equipment Repair","P=
assive","Hybrid","Hybrid Module","Grid outage,site went down because Gen fa=
iled to start due to Hybrid system malfunction // Grid return","edwige.kapa=
wo@matech-cameroun.com","1148","08-06-2025 16:48:51","MATECH CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0005207373","M=
ini-Ferme","","08-06-2025 16:47:45","08-06-2025 16:20:32","08-06-2025 17:31=
:49","Grid Only, No space to deploy MGE // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to =
deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","1634","08-0=
6-2025 16:47:45","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005207364","B=
arriere","","08-06-2025 16:46:08","08-06-2025 16:36:51","08-06-2025 17:03:5=
4","Active// No power issue on site Ubay: 54.6V site on Grid TX Fme SAMBA (=
654266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No po=
wer issue on site Ubay: 54.6V site on Grid TX Fme SAMBA (654266058/Huawei) =
is informed.","edwige.kapawo@matech-cameroun.com","558","08-06-2025 16:46:0=
8","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0005207344","Obobogo"=
,"","08-06-2025 16:43:44","08-06-2025 14:44:04","08-06-2025 18:45:49","Casc=
aded Incident from TTO5358552","MINKA NICOLAS","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage gen failed to start due to =
priiming pump faulty // Grid return","system","285566","08-06-2025 16:43:44=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0005207343","Scalom-I=
HS","","08-06-2025 16:43:43","08-06-2025 14:44:04","08-06-2025 18:45:49","C=
ascaded Incident from TTO5358552","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage gen failed to start due to priiming p=
ump faulty // Grid return","system","285564","08-06-2025 16:43:43","MATECH =
CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005207122","Efo=
ulan MTN","","08-06-2025 16:21:07","08-06-2025 16:18:58","08-06-2025 16:28:=
58","Grid outage site went down because Gen failed to start due to Gen card=
 faulty // Gen Manually Started","MINKA NICOLAS","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage site went down because Ge=
n failed to start due to Gen card faulty // Gen Manually Started","franck.n=
komot@matech-cameroun.com","130","08-06-2025 16:21:07","MATECH CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0005207016","R=
d-Pt-Express","","08-06-2025 16:05:42","08-06-2025 15:48:10","08-06-2025 17=
:33:19","Grid Only, No space to deploy MGE // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space =
to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","1053","0=
8-06-2025 16:05:42","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005206963","Odz=
a petit marche new","","08-06-2025 15:56:11","08-06-2025 15:54:57","08-06-2=
025 17:31:53","Site went down due to insufficient rectifers on site//He res=
et it  ","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficient rectifers on site//He reset i=
t  ","franck.nkomot@matech-cameroun.com","75","08-06-2025 15:56:11","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0005206933","B=
ATA-Mokolo","","08-06-2025 15:52:25","08-06-2025 15:45:16","08-06-2025 17:3=
3:21","Grid Only, No space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to=
 deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","430","08-0=
6-2025 15:52:25","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005206875","E=
toug ebe Meweulo","","08-06-2025 15:43:48","08-06-2025 14:37:39","08-06-202=
5 16:30:42","Grid outage, site went down due to insufficiency of rectifiers=
 // He reset rectifers","Hyemafo Gildas","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Grid outage, site went down due to insufficiency=
 of rectifiers // He reset rectifers","edwige.kapawo@matech-cameroun.com","=
3970","08-06-2025 15:43:48","MATECH CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0005206871","S=
apeur","","08-06-2025 15:42:35","08-06-2025 14:00:55","08-06-2025 18:51:41"=
,"Grid outage ,site down due to Gen Overload (20KVA,195A) SS IHS Francois i=
s informed // Grid return","Mboua Thierry","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Grid outage ,site down due to Gen Overload (20KV=
A,195A) SS IHS Francois is informed // Grid return","edwige.kapawo@matech-c=
ameroun.com","6101","08-06-2025 15:42:35","MATECH CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0005206856","S=
cience","","08-06-2025 15:40:05","08-06-2025 15:31:59","08-06-2025 17:01:25=
","Site went down because the PWC OF ZTE dysfunction // He reset the PWC, S=
ite on Grid","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Site went down because the PWC OF ZTE =
dysfunction // He reset the PWC, Site on Grid","edwige.kapawo@matech-camero=
un.com","487","08-06-2025 15:40:05","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0005206778","H=
-Progres","","08-06-2025 15:35:49","08-06-2025 15:26:59","08-06-2025 17:31:=
38","Grid Only, No space to deploy MGE // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to d=
eploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","531","08-06-=
2025 15:35:49","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005206579","Men=
dong NB","","08-06-2025 15:16:07","08-06-2025 15:13:59","08-06-2025 18:25:3=
3"," Grid outage no space to deployed a mobile Gen awaiting // Grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"," Gr=
id outage no space to deployed a mobile Gen awaiting // Grid return","franc=
k.nkomot@matech-cameroun.com","129","08-06-2025 15:16:07","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0005206497","BAT=
A Mokolo OCM","","08-06-2025 15:07:02","08-06-2025 14:53:44","08-06-2025 17=
:38:27","Grid Only, No space to deploy MGE // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space =
to deploy MGE // Grid return","franck.nkomot@matech-cameroun.com","800","08=
-06-2025 15:07:02","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005206465","Mvo=
g-Manga","","08-06-2025 15:00:50","08-06-2025 14:58:41","08-06-2025 16:30:4=
1","Grid outage site went down due to PWC dysfunction//He reset it and site=
 on Gen","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Grid outage site went down due to PWC dysfunction//He=
 reset it and site on Gen","franck.nkomot@matech-cameroun.com","130","08-06=
-2025 15:00:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_070","NOCINC0005206397","Efoulan"=
,"","08-06-2025 14:50:13","08-06-2025 14:44:04","08-06-2025 18:45:49","Casc=
aded Incident from TTO5358552","MINKA NICOLAS","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage gen failed to start due to =
priiming pump faulty // Grid return","system","285565","08-06-2025 14:50:13=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0005206398","Scalom",=
"","08-06-2025 14:50:13","08-06-2025 14:44:04","08-06-2025 18:45:49","Casca=
ded Incident from TTO5358552","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage gen failed to start due to pri=
iming pump faulty // Grid return","system","285564","08-06-2025 14:50:13","=
MATECH CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0005206384","S=
hell-Nsimeyong","IHS_YND_070, IHS_YND_505, IHS_YND_071, IHS_YND_155","08-06=
-2025 14:47:10","08-06-2025 14:44:04","08-06-2025 18:45:49","Grid outage ge=
n failed to start due to priiming pump faulty // Grid return","MINKA NICOLA=
S","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Fuel Pump","Grid o=
utage gen failed to start due to priiming pump faulty // Grid return","edwi=
ge.kapawo@matech-cameroun.com","187","08-06-2025 14:47:10","MATECH CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0005206380","Nsi=
meyong Shell","","08-06-2025 14:46:27","08-06-2025 14:44:22","08-06-2025 20=
:01:24","Grid outage gen failed to start due to priiming pump faulty // Gri=
d return","MINKA NICOLAS","Fuel Outage (Probable)","Passive","ACDG Gen","AC=
DG - Fuel Pump","Grid outage gen failed to start due to priiming pump fault=
y // Grid return","franck.nkomot@matech-cameroun.com","126","08-06-2025 14:=
46:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_159","NOCINC0005206324","Complexe=
-BEAC","","08-06-2025 14:38:53","08-06-2025 14:24:00","08-06-2025 15:51:59"=
,"Cascaded Incident from TTO5358482","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to CB of TGBT =
disjuncted//We bypass CB and site on gen ","system","337191","08-06-2025 14=
:38:53","MATECH CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0005206321","E=
kie-Elegance","IHS_YND_159","08-06-2025 14:38:09","08-06-2025 14:24:00","08=
-06-2025 17:22:22","Site went down due to CB of TGBT disjuncted//We bypass =
CB and site on gen ","Albran Byorel","Equipment Repair","Passive","Control =
Panel","Faulty Circuit Breaker","Site went down due to CB of TGBT disjuncte=
d//We bypass CB and site on gen ","edwige.kapawo@matech-cameroun.com","850"=
,"08-06-2025 14:38:09","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0005206303","B=
iyemassi LAC","","08-06-2025 14:36:23","08-06-2025 14:34:14","08-06-2025 17=
:38:53","Grid Only, No space to deploy MGE // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space =
to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","130","08=
-06-2025 14:36:23","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0005206013","Mes=
sassi Ngonlonk","","08-06-2025 13:54:44","08-06-2025 12:45:35","08-06-2025 =
14:10:29","Grid outage site went down because Gen failed to start due to Ge=
n card faulty // Gen Manually Started","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down be=
cause Gen failed to start due to Gen card faulty // Gen Manually Started","=
etienne.itondo@ihstowers.com","4150","08-06-2025 13:54:44","MATECH CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0005205924","S=
cience","","08-06-2025 13:42:28","08-06-2025 13:24:20","08-06-2025 15:14:31=
","Site went down because the PWC OF ZTE dysfunction // He reset the PWC","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Site went down because the PWC OF ZTE dysfunction //=
 He reset the PWC","edwige.kapawo@matech-cameroun.com","1088","08-06-2025 1=
3:42:28","MATECH CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0005205786","M=
obil-Kondengui","IHS_YND_682","08-06-2025 13:22:02","08-06-2025 13:18:55","=
08-06-2025 19:11:37","Grid only site, no space to deploy MDG // Grid return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id only site, no space to deploy MDG // Grid return","edwige.kapawo@matech-=
cameroun.com","188","08-06-2025 13:22:02","MATECH CMR"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0005205777","M=
ONTEE NKONDENGUI","","08-06-2025 13:21:01","08-06-2025 13:18:55","08-06-202=
5 19:11:37","","Albran Byorel","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid only site, no space to deploy MDG // Grid return",=
"edwige.kapawo@matech-cameroun.com","290669","08-06-2025 13:21:01","MATECH =
CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005205775","E=
koumdoum OCM","","08-06-2025 13:20:08","08-06-2025 13:14:58","08-06-2025 13=
:38:05","Grid outage,site went down because Gen failed to start due to Hybr=
id system malfunction // Grid return","Albran Byorel","Equipment Repair","P=
assive","Hybrid","Hybrid Module","Grid outage,site went down because Gen fa=
iled to start due to Hybrid system malfunction // Grid return","edwige.kapa=
wo@matech-cameroun.com","311","08-06-2025 13:20:08","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0005205693","Clu=
b France","","08-06-2025 13:05:56","08-06-2025 12:57:40","08-06-2025 17:34:=
46","Grid only site, No space to deploy a MDG //Grid restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site, =
No space to deploy a MDG //Grid restored","gerard.tchangoue@matech-cameroun=
.com","497","08-06-2025 13:05:56","MATECH CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0005205566","Mae=
tur","","08-06-2025 12:50:36","08-06-2025 12:42:12","08-06-2025 13:33:26","=
Grid outage,Gen failed to start due to Gen CB 32A tripped//he reamed the CB=
","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Load Brea=
ker","Grid outage,Gen failed to start due to Gen CB 32A tripped//he reamed =
the CB","gerard.tchangoue@matech-cameroun.com","505","08-06-2025 12:50:36",=
"MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0005205543","Men=
dong vallee","","08-06-2025 12:46:42","08-06-2025 12:28:26","08-06-2025 13:=
36:21","Grid outage site went down due to Gen overload (20KVA; 300A) IHS F=
=E9lix Zamb=E9 is informed and confirmed // Grid returned","Fanda Brice","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site w=
ent down due to Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed =
and confirmed // Grid returned","ludivine.ngamaleu@ihstowers.com","1098","0=
8-06-2025 12:46:42","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005205512","E=
koumdoum OCM","","08-06-2025 12:37:28","08-06-2025 12:37:16","08-06-2025 12=
:44:52","Grid outage,site went down because Gen failed to start due to PWC =
ZTE not configured//Grid return","Albran Byorel","Equipment Repair","Passiv=
e","Control Panel","ATS-AMF Issue","Grid outage,site went down because Gen =
failed to start due to PWC ZTE not configured//Grid return","edwige.kapawo@=
matech-cameroun.com","14","08-06-2025 12:37:28","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005205481","Acc=
acia New","","08-06-2025 12:30:05","08-06-2025 12:22:55","08-06-2025 17:42:=
55","Grid outage, no space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy MGE // Grid return","gerard.tchangoue@matech-cameroun.com","432",=
"08-06-2025 12:30:05","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005205247","Mon=
tee Jouvence","","08-06-2025 11:48:14","08-06-2025 11:42:08","08-06-2025 12=
:08:10","grid outage; gen ran until fuel shortage//Refueling done","Hyemafo=
 Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage; gen=
 ran until fuel shortage//Refueling done","gerard.tchangoue@matech-cameroun=
.com","367","08-06-2025 11:48:14","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005205215","Efo=
ulan MTN","","08-06-2025 11:42:48","08-06-2025 11:37:40","08-06-2025 13:23:=
29","Grid outage site went down because Gen failed to start due to Gen card=
 faulty // Gen Manually Started","MINKA NICOLAS","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage site went down because Ge=
n failed to start due to Gen card faulty // Gen Manually Started","gerard.t=
changoue@matech-cameroun.com","309","08-06-2025 11:42:48","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005205212","O=
dza II OCM","IHS_YND_528","08-06-2025 11:42:12","08-06-2025 11:39:56","08-0=
6-2025 13:55:57","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Gri stabilized","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down because gen failed to start due to PWC ZTE malfunction // Gri st=
abilized","edwige.kapawo@matech-cameroun.com","160","08-06-2025 11:42:12","=
MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005205199","Ron=
d Point Express1114","","08-06-2025 11:40:46","08-06-2025 11:34:40","08-06-=
2025 14:35:20","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","ge=
rard.tchangoue@matech-cameroun.com","367","08-06-2025 11:40:46","MATECH CMR=
"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005205153","Nko=
ulou Carriere carrefourt","","08-06-2025 11:30:05","08-06-2025 11:23:49","0=
8-06-2025 16:33:49","Grid outage, Site went down due to insufficiency of re=
ctifiers//Site stablilsed","Mba Lazare Herve","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","Grid outage, Site went down due to insuffic=
iency of rectifiers//Site stablilsed","gerard.tchangoue@matech-cameroun.com=
","377","08-06-2025 11:30:05","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005205144","Cit=
e des nations","","08-06-2025 11:26:22","08-06-2025 11:21:13","08-06-2025 1=
1:34:53","Active //No power issue ,site on Grid on site with Ubaie:53.7 V X=
 Fme Hosiah / 674007438 from huawei is informed","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active //No power issue ,site on Grid on site with Ubaie:53.7 V X Fme Hosia=
h / 674007438 from huawei is informed","gerard.tchangoue@matech-cameroun.co=
m","310","08-06-2025 11:26:22","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005205132","Sim=
e Building","","08-06-2025 11:23:37","08-06-2025 11:20:30","08-06-2025 11:2=
8:17","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","gerard.tchan=
goue@matech-cameroun.com","188","08-06-2025 11:23:37","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0005205117","MEH=
ANDAN","","08-06-2025 11:19:44","08-06-2025 11:13:37","08-06-2025 19:03:43"=
,"","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down because gen failed to start due to PWC=
 ZTE malfunction // Gri stabilized","gerard.tchangoue@matech-cameroun.com",=
"368","08-06-2025 11:19:44","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005205105","B=
arriere","","08-06-2025 11:14:52","08-06-2025 11:14:47","08-06-2025 13:10:0=
6","(Ats on baypass mode and site sur GE permanent) / Site went down becaus=
e gen stopped due to Air-intake // Gen purge and Gen start manually","Hyema=
fo Gildas","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Air Intake=
","(Ats on baypass mode and site sur GE permanent) / Site went down because=
 gen stopped due to Air-intake // Gen purge and Gen start manually","edwige=
.kapawo@matech-cameroun.com","6","08-06-2025 11:14:52","MATECH CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0005205101","M=
imboman-Village","","08-06-2025 11:13:49","08-06-2025 11:04:41","08-06-2025=
 11:45:30","Grid outage,site went down because Gen failed to start due to P=
WC ZTE dysfunction//He started the Gen manually","Mba Lazare Herve","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outag=
e,site went down because Gen failed to start due to PWC ZTE dysfunction//He=
 started the Gen manually","edwige.kapawo@matech-cameroun.com","549","08-06=
-2025 11:13:49","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005205018","GSO=
","IHS_YND_067","08-06-2025 10:56:28","08-06-2025 10:51:20","08-06-2025 11:=
09:01","Site went due to Huawei controller dysfunctionnning//He reset it ",=
"MINKA NICOLAS","Equipment Repair","Passive","Control Panel","ATS-AMF Issue=
","Site went due to Huawei controller dysfunctionnning//He reset it ","gera=
rd.tchangoue@matech-cameroun.com","309","08-06-2025 10:56:28","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005205006","E=
MANA BILICK CITY","IHS_YND_279","08-06-2025 10:54:05","08-06-2025 10:44:57"=
,"08-06-2025 16:37:57","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid return","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, site down be=
cause site behaves as Grid only site (Gen Noise) // Grid return","gaelle.nj=
iofack@matech-cameroun.com","550","08-06-2025 10:54:05","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005205005","M=
essassi okolo","","08-06-2025 10:53:31","08-06-2025 10:44:57","08-06-2025 1=
6:32:57","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site down because site behaves as Grid only=
 site (Gen Noise) // Grid return","gaelle.njiofack@matech-cameroun.com","12=
35000","08-06-2025 10:53:31","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005204873","ODZ=
A BORNE 10","","08-06-2025 10:39:04","08-06-2025 10:33:56","08-06-2025 12:3=
5:32","Site went down due to 1/4 rectifiers faulty on site // He remove the=
 faulty one ","Albran Byorel","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down due to 1/4 rectifiers faulty on site // He r=
emove the faulty one ","gerard.tchangoue@matech-cameroun.com","308","08-06-=
2025 10:39:04","MATECH CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0005204852","MES=
SAME NDONGO 1162","","08-06-2025 10:36:07","08-06-2025 10:31:56","08-06-202=
5 10:39:45","Grid outage,site went down because gen failed to start due to =
Gen card Faulty// He started Gen manually","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down =
because gen failed to start due to Gen card Faulty// He started Gen manuall=
y","gerard.tchangoue@matech-cameroun.com","252","08-06-2025 10:36:07","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0005204818","K=
oweit City","","08-06-2025 10:28:21","08-06-2025 10:26:14","08-06-2025 19:5=
6:55","Site went down due to insufficiency of rectifiers on site SS IHS Pas=
caline is confirm // He added 01/05 rectifier","Albran Byorel","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down due to insu=
fficiency of rectifiers on site SS IHS Pascaline is confirm // He added 01/=
05 rectifier","gaelle.njiofack@matech-cameroun.com","128","08-06-2025 10:28=
:21","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005204747","O=
dza-PK10","","08-06-2025 10:12:48","08-06-2025 10:07:37","08-06-2025 13:47:=
46","Grid outage, site went down due to PWC ZTE dysfunctionment // He bypas=
s and put site on gen","Albran Byorel","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Grid outage, site went down due to PWC =
ZTE dysfunctionment // He bypass and put site on gen","gaelle.njiofack@mate=
ch-cameroun.com","312","08-06-2025 10:12:48","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0005204745","N=
kolo II New","","08-06-2025 10:12:15","08-06-2025 10:00:07","08-06-2025 11:=
50:55","Grid outage,gen ran till fuel shortage//Refueling done","Mba Lazare=
 Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen r=
an till fuel shortage//Refueling done","gaelle.njiofack@matech-cameroun.com=
","729","08-06-2025 10:12:15","MATECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0005204588","N=
koa Ayos","","08-06-2025 09:36:45","08-06-2025 10:51:20","08-06-2025 11:09:=
01","Site impacted by GSO","MINKA NICOLAS","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went due to Huawei controller dysfunct=
ionnning//He reset it ","gaelle.njiofack@matech-cameroun.com","306717","08-=
06-2025 09:36:45","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005204484","M=
imboman-Ecole","","08-06-2025 09:17:30","08-06-2025 09:17:23","08-06-2025 1=
2:28:06","Site went down due to insufficient rectifiers issues on site//He =
reset it and site on Grid","Mba Lazare Herve","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","Site went down due to insufficient rectifie=
rs issues on site//He reset it and site on Grid","gaelle.njiofack@matech-ca=
meroun.com","8","08-06-2025 09:17:30","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005204460","E=
koumdoum OCM","","08-06-2025 09:15:01","08-06-2025 09:11:54","08-06-2025 10=
:52:17","Grid outage,site went down because Gen failed to start due to PWC =
ZTE not configured//He started the Gen manually","Albran Byorel","Equipment=
 Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,site went d=
own because Gen failed to start due to PWC ZTE not configured//He started t=
he Gen manually","gaelle.njiofack@matech-cameroun.com","188","08-06-2025 09=
:15:01","MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005204420","N=
GONA","","08-06-2025 09:06:25","08-06-2025 09:00:18","08-06-2025 09:08:52",=
"Grid outage, Site went down because Gen failed to start due to battery Gen=
 faulty// He started Gen with external battery","Mba Lazare Herve","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, Si=
te went down because Gen failed to start due to battery Gen faulty// He sta=
rted Gen with external battery","gaelle.njiofack@matech-cameroun.com","368"=
,"08-06-2025 09:06:25","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005204406","C=
rf-Nsam","","08-06-2025 09:03:20","08-06-2025 08:56:07","08-06-2025 12:28:1=
2","Active//No power issue on site Ubaie =3D56.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D56.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","434=
","08-06-2025 09:03:20","MATECH CMR"
"Closed Complete","Site Down","T2564","IHS_YND_739","NOCINC0005204363","NKO=
LMESSING rue Manguier","","08-06-2025 08:55:04","08-06-2025 08:46:57","08-0=
6-2025 09:24:00","Grid outage, Site went down because Gen failed to start d=
ue to battery Gen Faulty// He started Gen with external battery","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","G=
rid outage, Site went down because Gen failed to start due to battery Gen F=
aulty// He started Gen with external battery","gerard.tchangoue@matech-came=
roun.com","488","08-06-2025 08:55:04","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005204356","GSO=
","","08-06-2025 08:53:26","08-06-2025 08:44:16","08-06-2025 10:14:39","Gri=
d outage,site went down because Gen started and stopped with alarm ""Overvo=
ltage""//Grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Over Voltage","Grid outage,site went down because Gen started an=
d stopped with alarm ""Overvoltage""//Grid return","gerard.tchangoue@matech=
-cameroun.com","551","08-06-2025 08:53:26","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0005204308","B=
iteng-Maetur","","08-06-2025 08:42:56","08-06-2025 08:30:48","08-06-2025 15=
:03:28","Grid outage site went down because Gen failed to start due PWC ZTE=
 dysfunctioned // Grid return","Mba Lazare Herve","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Grid outage site went down b=
ecause Gen failed to start due PWC ZTE dysfunctioned // Grid return","gaell=
e.njiofack@matech-cameroun.com","730","08-06-2025 08:42:56","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005204243","Ron=
d Point Express1114","","08-06-2025 08:27:11","08-06-2025 08:14:58","08-06-=
2025 08:32:57","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","lu=
divine.ngamaleu@ihstowers.com","734","08-06-2025 08:27:11","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005204230","C=
arrefourt Nkomo","","08-06-2025 08:23:40","08-06-2025 08:20:31","08-06-2025=
 10:09:31","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid outage,site went down because Gen failed to star=
t due to PWC Overload(12k//280A)SS HIS Bateu is informed//Site stabilised",=
"gaelle.njiofack@matech-cameroun.com","315763","08-06-2025 08:23:40","MATEC=
H CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005204228","Cit=
e des nations","","08-06-2025 08:23:31","08-06-2025 08:17:24","08-06-2025 0=
8:27:24","Active //No power issue ,site on Grid on site with Ubaie:53.7 V X=
 Fme Hosiah / 674007438 from huawei is informed","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active //No power issue ,site on Grid on site with Ubaie:53.7 V X Fme Hosia=
h / 674007438 from huawei is informed","gerard.tchangoue@matech-cameroun.co=
m","368","08-06-2025 08:23:31","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005204226","N=
komo","IHS_YND_174","08-06-2025 08:22:37","08-06-2025 08:20:31","08-06-2025=
 10:10:10","Grid outage,site went down because Gen failed to start due to P=
WC Overload(12k//280A)SS HIS Bateu is informed//Site stabilised","Mba Lazar=
e Herve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Grid outage,site went down because Gen failed to start due to PWC Ove=
rload(12k//280A)SS HIS Bateu is informed//Site stabilised","gaelle.njiofack=
@matech-cameroun.com","127","08-06-2025 08:22:37","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005204214","A=
wae Ewonkan","","08-06-2025 08:20:17","08-06-2025 08:19:11","08-06-2025 11:=
47:42","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed //Site stabilised","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed //Site s=
tabilised","gaelle.njiofack@matech-cameroun.com","68","08-06-2025 08:20:17"=
,"MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005204174","Eto=
ug ebe Carrefour","","08-06-2025 08:11:50","08-06-2025 08:05:37","08-06-202=
5 08:23:26","Grid outage site went down before gen started due to poor batt=
ery backup // Grid returned	","Hyemafo Gildas","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage site went down =
before gen started due to poor battery backup // Grid returned	","gerard.tc=
hangoue@matech-cameroun.com","374","08-06-2025 08:11:50","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005204128","Eki=
e sud","","08-06-2025 08:06:04","08-06-2025 08:04:42","08-06-2025 09:50:14"=
,"Grid outage,site went down due to PWC ZTE dysfunctionning//He reset it an=
d started the GEN manually","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","Grid outage,site went down due to =
PWC ZTE dysfunctionning//He reset it and started the GEN manually","gerard.=
tchangoue@matech-cameroun.com","83","08-06-2025 08:06:04","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0005204113","Imm=
-Olympique","","08-06-2025 08:03:09","08-06-2025 07:58:59","08-06-2025 08:2=
8:24","Grid outage, site went down because gen stopped with under voltage a=
larm // Reset done and gen started","Paul BIBOUM","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
gen stopped with under voltage alarm // Reset done and gen started","gerard=
.tchangoue@matech-cameroun.com","956","08-06-2025 08:03:09","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005204110","C=
hapelle-Nsimeyong","","08-06-2025 08:02:52","08-06-2025 07:54:38","08-06-20=
25 08:26:55","Grid outage , Site down due to malfunction of the gen card //=
 Gen card reseted  and restarted gen manually ","MINKA NICOLAS","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage , Site dow=
n due to malfunction of the gen card / reset and restart gen manually ","ga=
elle.njiofack@matech-cameroun.com","495","08-06-2025 08:02:52","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005204106","MBA=
LNGONG LYCEE","","08-06-2025 08:02:12","08-06-2025 07:59:03","08-06-2025 17=
:39:03","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down be=
cause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informe=
d and confirmed // Grid returned","gerard.tchangoue@matech-cameroun.com","1=
91","08-06-2025 08:02:12","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005204104","E=
mana Lycee","","08-06-2025 08:02:01","08-06-2025 07:42:36","08-06-2025 08:2=
1:35","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, Site went down because Gen started and stopped=
 due to Gen overload(20kva, 260A) // He reduced the load","gaelle.njiofack@=
matech-cameroun.com","3413","08-06-2025 08:02:01","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005204087","Fla=
menco","","08-06-2025 08:00:28","08-06-2025 07:57:19","08-06-2025 08:25:31"=
,"Grid outage gen failed to start due to card GE dysfunctionning//We reset =
card GE and gen manually started ","Mboua Thierry","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to start due=
 to card GE dysfunctionning//We reset card GE and gen manually started ","g=
erard.tchangoue@matech-cameroun.com","190","08-06-2025 08:00:28","MATECH CM=
R"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0005204050","Kon=
dengui MTN","","08-06-2025 07:58:13","08-06-2025 07:50:52","08-06-2025 08:2=
1:05","Grid outage.gen failed to start due to card GE dysfunctionned//We re=
set card GE and gen manually started ","Albran Byorel","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to start=
 due to card GE dysfunctionned//We reset card GE and gen manually started "=
,"ludivine.ngamaleu@ihstowers.com","442","08-06-2025 07:58:13","MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0005204048","Abo=
me","","08-06-2025 07:57:51","08-06-2025 07:52:29","08-06-2025 09:58:44","G=
rid outage site went down because Gen failed to start due to Gen card fault=
y // Gen Manually Started","MINKA NICOLAS","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage site went down because Gen fail=
ed to start due to Gen card faulty // Gen Manually Started","gerard.tchango=
ue@matech-cameroun.com","529","08-06-2025 07:57:51","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005204046","M=
anguier","","08-06-2025 07:57:28","08-06-2025 07:50:20","08-06-2025 09:42:1=
7","Grid outage,gen Stopped due to Alarm High temp // Water Add in radiator=
 and Gen start manually.","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","Gen Temp High","Grid outage,gen Stopped due to Alarm High temp //=
 Water Add in radiator and Gen start manually.","gaelle.njiofack@matech-cam=
eroun.com","429","08-06-2025 07:57:28","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005204043","Efo=
ulan MTN","","08-06-2025 07:56:44","08-06-2025 07:53:35","08-06-2025 08:27:=
51","Grid outage site went down because Gen failed to start due to Gen card=
 faulty // Gen Manually Started","MINKA NICOLAS","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage site went down because Ge=
n failed to start due to Gen card faulty // Gen Manually Started","gerard.t=
changoue@matech-cameroun.com","190","08-06-2025 07:56:44","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005204042","O=
mnisport-Rail","","08-06-2025 07:56:25","08-06-2025 07:50:17","08-06-2025 1=
0:36:15","Site went down due to DC BOX burnt on site //He bypasssed it ","D=
elor Telezing","Fire on Site","Passive","Infrastructure","Fire - Burned","S=
ite went down due to DC BOX burnt on site //He bypasssed it ","gaelle.njiof=
ack@matech-cameroun.com","369","08-06-2025 07:56:25","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005204039","M=
ANGUIERS CHAPELLE","","08-06-2025 07:55:50","08-06-2025 07:49:31","08-06-20=
25 10:52:04","No power issue site on gen with U=3D56.1v Armand Nguetsa from=
 Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
en with U=3D56.1v Armand Nguetsa from Huawei is informed","gaelle.njiofack@=
matech-cameroun.com","380","08-06-2025 07:55:50","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005204021","Mon=
tee Jouvence","","08-06-2025 07:51:20","08-06-2025 07:50:03","08-06-2025 09=
:10:34","Grid outage.gen failed to start due to ""high temp"" alarm//We add=
 water and gen manually started","Hyemafo Gildas","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage=
.gen failed to start due to ""high temp"" alarm//We add water and gen manua=
lly started","ludivine.ngamaleu@ihstowers.com","78","08-06-2025 07:51:20","=
MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005204014","Mvo=
g Betsi Hospital","","08-06-2025 07:48:12","08-06-2025 07:44:05","08-06-202=
5 07:50:44","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","gerard.tchangoue@matech-cameroun.=
com","247","08-06-2025 07:48:12","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005204011","Mam=
ch Building","","08-06-2025 07:46:46","08-06-2025 07:44:37","08-06-2025 08:=
21:13","Grid outage.site went down due to bad grid voltage//We bypass grid =
and gen manually started ","Mboua Thierry","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","Grid outage.site went down due to=
 bad grid voltage//We bypass grid and gen manually started ","gerard.tchang=
oue@matech-cameroun.com","130","08-06-2025 07:46:46","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005203999","E=
mana lycee 2","IHS_YND_274","08-06-2025 07:44:43","08-06-2025 07:42:36","08=
-06-2025 08:21:35","Grid outage, Site went down because Gen started and sto=
pped due to Gen overload(20kva, 260A) // He reduced the load","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
, Site went down because Gen started and stopped due to Gen overload(20kva,=
 260A) // He reduced the load","edwige.kapawo@matech-cameroun.com","129","0=
8-06-2025 07:44:43","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005203990","Acc=
acia New","","08-06-2025 07:42:27","08-06-2025 07:40:14","08-06-2025 08:25:=
44","Grid outage, no space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy MGE // Grid return","gerard.tchangoue@matech-cameroun.com","134",=
"08-06-2025 07:42:27","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005203985","M=
ontee-Des-Soeurs","","08-06-2025 07:40:32","08-06-2025 07:37:24","08-06-202=
5 08:11:31","Site Went Down due to Gen Overload // grid return","Hyemafo Gi=
ldas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site Went =
Down due to Gen Overload // grid return","edwige.kapawo@matech-cameroun.com=
","190","08-06-2025 07:40:32","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005203982","Jou=
vence Mbenda","","08-06-2025 07:39:28","08-06-2025 07:29:59","08-06-2025 09=
:45:21","site went down because gen start and stopped with high temp alarm =
// He added water and manually start the gen","Hyemafo Gildas","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"site went down because gen start and stopped with high temp alarm // He a=
dded water and manually start the gen","gerard.tchangoue@matech-cameroun.co=
m","570","08-06-2025 07:39:28","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005203974","EMA=
NA BILICK CITY","","08-06-2025 07:38:23","08-06-2025 07:28:59","08-06-2025 =
08:30:37","Grid outage, site down because site behaves as Grid only site (G=
en Noise) Grid return","Fabrice Pouakam","Access Denial","Lease Or Legal","=
Landlord Related Issues","Access Issue - Land Lord","Grid outage, site down=
 because site behaves as Grid only site (Gen Noise) Grid return","gerard.tc=
hangoue@matech-cameroun.com","565","08-06-2025 07:38:23","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005203962","NKO=
MKANA ELIZA HOTEL","","08-06-2025 07:36:47","08-06-2025 07:26:59","08-06-20=
25 08:21:50","Grid outage, no space to deploy MDGE on site // Grid returned=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage, no space to deploy MDGE on site // Grid returned","gerard.tchang=
oue@matech-cameroun.com","589","08-06-2025 07:36:47","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005203956","Mok=
olo Yaounde","","08-06-2025 07:35:51","08-06-2025 07:25:59","08-06-2025 08:=
20:57","Site went down due to insufficient of rectifier on site SS IHS Bern=
ard is informed // Site stabilised","","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to insufficient of rectifier on=
 site SS IHS Bernard is informed // Site stabilised","gerard.tchangoue@mate=
ch-cameroun.com","594","08-06-2025 07:35:51","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005203951","Bar=
riere","","08-06-2025 07:34:48","08-06-2025 07:25:40","08-06-2025 10:37:29"=
,"Site went down due to PWC ZTE dysfunction the ss IHS Felix is informed //=
He reset it and site on grid","Hyemafo Gildas","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Site went down due to PWC ZTE d=
ysfunction the ss IHS Felix is informed //He reset it and site on grid","ge=
rard.tchangoue@matech-cameroun.com","549","08-06-2025 07:34:48","MATECH CMR=
"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005203927","M=
essassi okolo","","08-06-2025 07:30:15","08-06-2025 07:23:08","08-06-2025 0=
8:30:28","Grid outage,gen ran till fuel shortage//Refueling done","Fabrice =
Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen =
ran till fuel shortage//Refueling done","edwige.kapawo@matech-cameroun.com"=
,"429","08-06-2025 07:30:15","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005203892","N=
kolbong","","08-06-2025 07:21:57","08-06-2025 07:20:47","08-06-2025 08:25:5=
4","Site went Down because Gen started and stopped due to Gen overload(22kv=
a//350A) // Grid returned","Delor Telezing","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Site went Down because Gen started and stopped =
due to Gen overload(22kva//350A) // Grid returned","edwige.kapawo@matech-ca=
meroun.com","71","08-06-2025 07:21:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005203883","MEHANDAN=
","","08-06-2025 07:21:15","08-06-2025 07:19:11","08-06-2025 07:26:59","Cas=
caded Incident from TTO5355586","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to PWC ZTE malfunction // Gri stabilized","system","=
291640","08-06-2025 07:21:15","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005203880","O=
dza II OCM","IHS_YND_528","08-06-2025 07:20:29","08-06-2025 07:19:11","08-0=
6-2025 07:26:59","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Gri stabilized","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","	Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Gri s=
tabilized","edwige.kapawo@matech-cameroun.com","80","08-06-2025 07:20:29","=
MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005203871","GSO=
","","08-06-2025 07:17:31","08-06-2025 07:08:15","08-06-2025 07:26:58","Gri=
d fluctuation , Site went down due to grid bad voltage and no rcp on site /=
/He bypassed the Grid, site on GEN","MINKA NICOLAS","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation , Site =
went down due to grid bad voltage and no rcp on site //He bypassed the Grid=
, site on GEN","gerard.tchangoue@matech-cameroun.com","557","08-06-2025 07:=
17:31","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005203492","Bar=
riere","","08-06-2025 05:50:45","08-06-2025 05:40:59","08-06-2025 07:05:55"=
,"(Ats on baypass mode and site sur GE permanent) / Site went down because =
gen stopped due to Air-intake // Gen purge and Gen start manually","Hyemafo=
 Gildas","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Air Intake",=
"(Ats on baypass mode and site sur GE permanent) / Site went down because g=
en stopped due to Air-intake // Gen purge and Gen start manually","loic.nou=
msi@matech-cameroun.com","642","08-06-2025 05:50:45","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005203467","Nko=
ulou Carriere carrefourt","","08-06-2025 05:42:21","08-06-2025 05:36:13","0=
8-06-2025 10:17:03","Grid outage, Site went down due to insufficiency of re=
ctifiers//Site stablilsed","Mba Lazare Herve","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","Grid outage, Site went down due to insuffic=
iency of rectifiers//Site stablilsed","loic.noumsi@matech-cameroun.com","37=
0","08-06-2025 05:42:21","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005203064","Eto=
ug ebe Meweulo","","08-06-2025 03:13:48","08-06-2025 03:12:44","08-06-2025 =
08:12:00","Site went down due to GEN CB disjuncted//We rearmed CB and site =
on gen","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Circuit Breaker Issue","Site went down due to GEN CB disjuncted=
//We rearmed CB and site on gen","gerard.tchangoue@matech-cameroun.com","65=
","08-06-2025 03:13:48","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0005202859","A=
battoir","","08-06-2025 01:19:05","08-06-2025 01:05:55","08-06-2025 01:25:0=
7","Grid outage gen failed to start due to battery GE faulty//Gen manually =
started with external battery","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Generator Battery","Grid outage gen failed to start d=
ue to battery GE faulty//Gen manually started with external battery","gaell=
e.njiofack@matech-cameroun.com","791","08-06-2025 01:19:05","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005202691","B=
arriere","","08-06-2025 00:15:09","08-06-2025 00:10:03","08-06-2025 00:17:2=
4","(Ats on baypass mode and site sur GE permanent) / Site went down becaus=
e gen stopped due to Air-intake // Gen purge and Gen start manually","Hyema=
fo Gildas","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Air Intake=
","(Ats on baypass mode and site sur GE permanent) / Site went down because=
 gen stopped due to Air-intake // Gen purge and Gen start manually","loic.n=
oumsi@matech-cameroun.com","308","08-06-2025 00:15:09","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005202636","Eto=
ug ebe Meweulo","","08-06-2025 00:02:34","08-06-2025 00:01:28","08-06-2025 =
02:26:06","Grid outage, site went down due to insufficiency of rectifiers /=
/ He reset rectifers","Hyemafo Gildas","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Grid outage, site went down due to insufficiency o=
f rectifiers // He reset rectifers","loic.noumsi@matech-cameroun.com","66",=
"08-06-2025 00:02:34","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005202560","E=
ssomba","","07-06-2025 23:38:30","07-06-2025 23:36:22","08-06-2025 01:30:41=
","(Unstable site) Site went down because PWC overload // Grid return","Mba=
 Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","(Unstable site) Site went down because PWC overload // Grid ret=
urn","gaelle.njiofack@matech-cameroun.com","130","07-06-2025 23:38:30","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005202556","C=
rf-Nsam","","07-06-2025 23:35:54","07-06-2025 23:27:44","07-06-2025 23:32:4=
8","Active//No power issue on site Ubaie =3D50.9V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D50.9V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","491=
","07-06-2025 23:35:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005202552","MEHANDAN=
","","07-06-2025 23:35:05","07-06-2025 23:26:07","07-06-2025 23:35:39","Cas=
caded Incident from TTO5354032","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Gri stabilized","system","3=
19728","07-06-2025 23:35:05","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005202550","O=
dza II OCM","IHS_YND_528","07-06-2025 23:34:27","07-06-2025 23:26:07","07-0=
6-2025 23:35:39","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Gri stabilized","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down because gen failed to start due to PWC ZTE malfunction // Gri st=
abilized","gaelle.njiofack@matech-cameroun.com","502","07-06-2025 23:34:27"=
,"MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005202420","ODZ=
A MINKAN EDIBI ASSI","","07-06-2025 23:16:15","07-06-2025 20:20:05","07-06-=
2025 22:41:05","Backtracking // Grid Outage, site went down because gen fai=
led to start due to PWC ZTE malfunction // He reset it and started the Gen =
manually","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Grid Outage, site went down because gen failed to st=
art due to PWC ZTE malfunction // He reset it and started the Gen manually"=
,"gaelle.njiofack@matech-cameroun.com","10631","07-06-2025 23:16:15","MATEC=
H CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005202272","Mon=
tee Jouvence","","07-06-2025 22:43:37","07-06-2025 22:42:23","07-06-2025 22=
:48:21","Grid outage, Site went down before Gen start due to poor backup //=
 Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid returned","loic.noumsi@matech-cameroun.com",=
"75","07-06-2025 22:43:37","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005202140","GSO=
","","07-06-2025 22:04:19","07-06-2025 21:55:10","08-06-2025 05:59:59","Gri=
d outage,site went down because Gen started and stopped with alarm ""Overvo=
ltage""//Grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Over Voltage","Grid outage,site went down because Gen started an=
d stopped with alarm ""Overvoltage""//Grid return","gerard.tchangoue@matech=
-cameroun.com","550","07-06-2025 22:04:19","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005202132","Acc=
acia New","","07-06-2025 22:02:41","07-06-2025 21:56:34","08-06-2025 06:50:=
48","Grid outage, no space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy MGE // Grid return`","gerard.tchangoue@matech-cameroun.com","369"=
,"07-06-2025 22:02:41","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005202061","D=
amas","","07-06-2025 21:48:45","07-06-2025 21:37:28","08-06-2025 07:00:03",=
"Acces issue due to landloard,Site went down due to CB(125A) in PWC that tr=
ipped ocm//He rearmed it","MINKA NICOLAS","Access Denial","Lease Or Legal",=
"Landlord Related Issues","Access Issue - Land Lord","Acces issue due to la=
ndloard,Site went down due to CB(125A) in PWC that tripped ocm//He rearmed =
it","vanel.mbiada@matech-cameroun.com","678","07-06-2025 21:48:45","MATECH =
CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0005201920","B=
iteng-Maetur","","07-06-2025 21:18:55","07-06-2025 19:31:12","07-06-2025 21=
:59:25","Grid outage site went down because Gen failed to start due PWC ZTE=
 dysfunctioned // He reset the PWC and site on Grid","Mba Lazare Herve","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid o=
utage site went down because Gen failed to start due PWC ZTE dysfunctioned =
// He reset the PWC and site on Grid","vanel.mbiada@matech-cameroun.com","6=
464","07-06-2025 21:18:55","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0005201908","Nko=
lfoulou CSD MTN","","07-06-2025 21:15:44","07-06-2025 21:06:38","07-06-2025=
 22:23:42","Site went down due to GE CB (32A) DOWN // He rearmed it and red=
uced 01 rectifier","Siligap Boris","Equipment Repair","Passive","Control Pa=
nel","Circuit Breaker Tripped","Site went down due to GE CB (32A) DOWN // H=
e rearmed it and reduced 01 rectifier","gerard.tchangoue@matech-cameroun.co=
m","546","07-06-2025 21:15:44","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005201716","M=
anguier","","07-06-2025 20:44:33","07-06-2025 19:38:06","07-06-2025 21:17:5=
2","Grid outage,gen Stopped due to Alarm High temp // Water Add in radiator=
 and Gen start manually.","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","Gen Temp High","Grid outage,gen Stopped due to Alarm High temp //=
 Water Add in radiator and Gen start manually.","vanel.mbiada@matech-camero=
un.com","3988","07-06-2025 20:44:33","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005201709","Nko=
lnda","","07-06-2025 20:43:18","07-06-2025 20:38:07","07-06-2025 22:17:52",=
"Grid outage, the GE stopped due to an under voltage alarm caused by the lo=
ad imbalance during the switching over // Gen car reset and Gen start manua=
lly","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Under =
Voltage","Grid outage, the GE stopped due to an under voltage alarm caused =
by the load imbalance during the switching over // Gen car reset and Gen st=
art manually","gerard.tchangoue@matech-cameroun.com","312","07-06-2025 20:4=
3:18","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005201645","N=
koabang Ebolmedjock","","07-06-2025 20:26:59","07-06-2025 20:14:18","07-06-=
2025 20:55:18","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matec=
h-cameroun.com","763","07-06-2025 20:26:59","MATECH CMR"
"Closed Complete","Site Down","CTR_553","IHS_YND_686","NOCINC0005201637","O=
yomabang Ecole","","07-06-2025 20:21:30","07-06-2025 20:19:21","07-06-2025 =
20:29:21","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mo=
uhamadou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mouh=
amadou (6144435) from Huawei is informed.","vanel.mbiada@matech-cameroun.co=
m","129","07-06-2025 20:21:30","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005201635","B=
arriere","","07-06-2025 20:21:00","07-06-2025 19:59:32","07-06-2025 22:34:5=
3","(Ats on baypass mode and site sur GE permanent) / Site went down becaus=
e gen stopped due to Air-intake // Gen purge and Gen start manually","Hyema=
fo Gildas","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Air Intake=
","Site went down because gen stopped due to Air-intake // Gen purge and Ge=
n start manually","vanel.mbiada@matech-cameroun.com","1289","07-06-2025 20:=
21:00","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005201582","A=
bome","","07-06-2025 20:04:40","07-06-2025 19:55:23","07-06-2025 21:31:13",=
"Grid outage,site went down because Gen Stopped due to Unknow Alarm (more i=
nvestigation on going) // Gen card reset and site on Gen.","MINKA NICOLAS",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
,site went down because Gen Stopped due to Unknow Alarm (more investigation=
 on going) // Gen card reset and site on Gen.","vanel.mbiada@matech-camerou=
n.com","559","07-06-2025 20:04:40","MATECH CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0005201539","C=
lge-Advantiste","","07-06-2025 19:57:45","07-06-2025 19:50:27","07-06-2025 =
20:01:41","Active/ No power issue site on grid with U=3D50.8V Lionnel Steev=
e(655184876) from Huawei is informed","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/ N=
o power issue site on grid with U=3D50.8V Lionnel Steeve(655184876) from Hu=
awei is informed","vanel.mbiada@matech-cameroun.com","439","07-06-2025 19:5=
7:45","MATECH CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0005201527","E=
lobi Mokolo","","07-06-2025 19:55:33","07-06-2025 19:47:44","07-06-2025 19:=
56:48","Active//No power issue on site, site on Grid with U=3D53,2 V The TX=
 FME Brice (650214096) from huawei is informed.","Mboua Thierry","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site, site on Grid with U=3D53,2 V The TX FME B=
rice (650214096) from huawei is informed.","vanel.mbiada@matech-cameroun.co=
m","470","07-06-2025 19:55:33","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005201477","O=
mnisport-Rail","","07-06-2025 19:45:04","07-06-2025 19:41:42","07-06-2025 2=
1:19:30","Grid outage,Site went down because Gen failed to start due to PSC=
3 Faulty// He started the Gen manually","Delor Telezing","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage,Site went down du=
e to PSC3 Faulty// He started the Gen manually","vanel.mbiada@matech-camero=
un.com","203","07-06-2025 19:45:04","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005201434","C=
rf-Nsam","","07-06-2025 19:43:06","07-06-2025 19:42:02","07-06-2025 20:02:5=
9","Active//No power issue on site Ubaie =3D50.9V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D50.9V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","vanel.mbiada@matech-cameroun.com","65","0=
7-06-2025 19:43:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0005201378","Nkolbiss=
on usines des eaux 2","","07-06-2025 19:33:54","07-06-2025 14:40:43","07-06=
-2025 19:30:54","Cascaded Incident from TTO5351496","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Backtra=
cking Grid outage, ACCESS ISSUE due to Landlord // Grid returned","system",=
"1249597","07-06-2025 19:33:54","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005201371","N=
gousso-Savana","IHS_YND_561","07-06-2025 19:32:59","07-06-2025 19:30:48","0=
7-06-2025 19:37:11","No power issue, site is on grid with Ubaie=3D53.4V, Sy=
mphorien(650257151) from Huawei is informed		","Siligap Boris","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue, site is on grid with Ubaie=3D53.4V, Symphorien(650257151) f=
rom Huawei is informed		","vanel.mbiada@matech-cameroun.com","132","07-06-2=
025 19:32:59","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005201367","F=
OUGEROLE","","07-06-2025 19:32:12","07-06-2025 19:30:48","07-06-2025 19:37:=
11","","Siligap Boris","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue, site is on grid with Ubaie=3D53.4V, Symphorien(650=
257151) from Huawei is informed		","vanel.mbiada@matech-cameroun.com","3335=
47","07-06-2025 19:32:12","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005201317","C=
omplexe-BEAC","","07-06-2025 19:26:32","07-06-2025 19:24:19","07-06-2025 19=
:28:42","Site went down due malfunction of rectifier // Site stabilized","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down due malfunction of rectifier // Site stabilized","vanel.mbia=
da@matech-cameroun.com","134","07-06-2025 19:26:32","MATECH CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0005201293","M=
IMBOMAN LIBERTE","","07-06-2025 19:23:15","07-06-2025 18:52:54","07-06-2025=
 20:00:34","Grid fluctuation, disjunction of Gen circuit breaker due to Gri=
d fluctuation // Gen circuit breaker rearm and site on Gen.","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid =
fluctuation, disjunction of Gen circuit breaker due to Grid fluctuation // =
Gen circuit breaker rearm and site on Gen.","vanel.mbiada@matech-cameroun.c=
om","1822","07-06-2025 19:23:15","MATECH CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0005201115","Jou=
vence 2000","","07-06-2025 18:47:10","07-06-2025 14:05:01","07-06-2025 20:3=
5:09","Backtracking Site went down due all rectifiers on site alarming//He =
reset it ","Delor Telezing","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due all rectifiers on site alarming//He reset =
it ","gerard.tchangoue@matech-cameroun.com","16930","07-06-2025 18:47:10","=
MATECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005201068","N=
GONA","","07-06-2025 18:40:24","07-06-2025 18:36:11","07-06-2025 20:28:14",=
"Grid outage,site went down because Gen failed to start due to battery ge d=
ischarge //he started with an external battery","Mba Lazare Herve","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage,sit=
e went down because Gen failed to start due to battery ge discharge //he st=
arted with an external battery","vanel.mbiada@matech-cameroun.com","254","0=
7-06-2025 18:40:24","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005201064","S=
atcom","","07-06-2025 18:39:30","07-06-2025 18:20:17","07-06-2025 18:22:17"=
,"Active // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand =
Ngestsa (691144412) of huawei is informed","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand Ngest=
sa (691144412) of huawei is informed","vanel.mbiada@matech-cameroun.com","1=
154","07-06-2025 18:39:30","MATECH CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0005201034","Ngo=
ulmekong-Nord","","07-06-2025 18:33:26","07-06-2025 15:08:04","07-06-2025 1=
7:28:11","Site impacted by Santa barbara","Siligap Boris","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
because gen ran untill fuel shortage // refuelling done","gerard.tchangoue@=
matech-cameroun.com","348988","07-06-2025 18:33:26","MATECH CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0005201024","Mba=
lla 4","","07-06-2025 18:29:52","07-06-2025 15:08:04","07-06-2025 17:28:11"=
,"Site impacted by Santa barbara","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen ran untill fuel shortage // refuelling done","gerard.tchangoue@matech-=
cameroun.com","348989","07-06-2025 18:29:52","MATECH CMR"
"Closed Complete","Site Down","T0629","IHS_YND_058","NOCINC0005201016","Mvo=
lye","","07-06-2025 18:25:36","07-06-2025 15:49:27","07-06-2025 20:07:01","=
Site went down due to absence of 2 phase eneo and the site is on 2 rectifie=
rs and there is no phase controller; the site operates on a 220v relay //  =
bridge made","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Site went down due to absence of 2 phase eneo a=
nd the site is on 2 rectifiers and there is no phase controller; the site o=
perates on a 220v relay //  bridge made","gerard.tchangoue@matech-cameroun.=
com","9369","07-06-2025 18:25:36","MATECH CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0005201003","Omn=
isport-Rail","","07-06-2025 18:22:20","07-06-2025 15:04:09","07-06-2025 19:=
37:22","Grid outage,Site went down because Geen failed to start due to PSC3=
 Faulty// He started the Gen manually","Delor Telezing","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage,Site went down bec=
ause Geen failed to start due to PSC3 Faulty// He started the Gen manually"=
,"gerard.tchangoue@matech-cameroun.com","12471","07-06-2025 18:22:20","MATE=
CH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0005200995","Eto=
udi2","","07-06-2025 18:20:11","07-06-2025 16:47:00","07-06-2025 21:05:01",=
"Site went down due to insufficiency of rectifier (01 /04 Rectifier is faut=
y )  // Site load reduction","Delor Telezing","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","Site went down due to insufficiency of rect=
ifier (01 /04 Rectifier is fauty )  // Site load reduction","gerard.tchango=
ue@matech-cameroun.com","5591","07-06-2025 18:20:11","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005200948","M=
anguier","","07-06-2025 18:11:38","07-06-2025 18:02:59","07-06-2025 19:02:1=
5","Grid outage,gen Stopped due to Alarm High temp // Water Add in radiator=
 and Gen start manually.","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","Gen Temp High","Grid outage,gen Stopped due to Alarm High temp //=
 Water Add in radiator and Gen start manually.","vanel.mbiada@matech-camero=
un.com","520","07-06-2025 18:11:38","MATECH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0005200936","Mvo=
g-Ada_OCM","","07-06-2025 18:10:11","07-06-2025 17:26:56","07-06-2025 21:36=
:34","Grid Only site, No space to deploy MDGE // Grid returned","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only site,=
 No space to deploy MDGE // Grid returned","gerard.tchangoue@matech-camerou=
n.com","2596","07-06-2025 18:10:11","MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0005200929","K=
amajou Building","","07-06-2025 18:08:37","07-06-2025 17:17:25","07-06-2025=
 18:30:34","Site went down due to insufficiency of rectifiers on site  // H=
e reduced the load","Paul BIBOUM","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site went down due to insufficiency of rectifiers on si=
te  // He reduced the load","vanel.mbiada@matech-cameroun.com","3073","07-0=
6-2025 18:08:37","MATECH CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0005200867","Bye=
massi Carrefour","","07-06-2025 17:58:07","07-06-2025 17:48:59","07-06-2025=
 18:10:01","Grid outage, site went down due to Grid fluctuactions and Poor =
backup battery on site // Grid stabilised","Paul BIBOUM","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down due to Grid fluctuactions and Poor backup battery on site // Gri=
d stabilised","gerard.tchangoue@matech-cameroun.com","549","07-06-2025 17:5=
8:07","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005200845","Men=
dong3","","07-06-2025 17:54:22","07-06-2025 17:45:15","08-06-2025 17:38:16"=
,"Grid Outage No space to deploy MGE. // Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Outage No space to d=
eploy MGE. // Grid return","gerard.tchangoue@matech-cameroun.com","548","07=
-06-2025 17:54:22","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005200837","Sim=
e Building","","07-06-2025 17:52:29","07-06-2025 17:48:05","07-06-2025 18:0=
8:17","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","gerard.tchan=
goue@matech-cameroun.com","265","07-06-2025 17:52:29","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0005200792","M=
bankomo IHS","","07-06-2025 17:44:14","07-06-2025 17:17:03","07-06-2025 17:=
33:21","No power issue on site, site on Gen with U=3D55.6V Tx FME FULBERT /=
654266068/ from huawei is informed, ","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site, site on Gen with U=3D55.6V Tx FME FULBERT /654266068/ from hua=
wei is informed, ","vanel.mbiada@matech-cameroun.com","1632","07-06-2025 17=
:44:14","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005200776","E=
SSOS OASIS 1111","","07-06-2025 17:40:49","07-06-2025 17:26:34","07-06-2025=
 17:41:59","Grid outage, Site went down due to Gen overload // Grid return"=
,"Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage, Site went down due to Gen overload // Grid return","vanel.mbi=
ada@matech-cameroun.com","856","07-06-2025 17:40:49","MATECH CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0005200772","M=
IMBOMAN LIBERTE","","07-06-2025 17:39:02","07-06-2025 17:25:25","07-06-2025=
 17:46:53","Grid fluctuation, disjunction of Gen circuit breaker due to Gri=
d fluctuation // Gen circuit breaker rearm and site on Gen.","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid =
fluctuation, disjunction of Gen circuit breaker due to Grid fluctuation // =
Gen circuit breaker rearm and site on Gen.","vanel.mbiada@matech-cameroun.c=
om","819","07-06-2025 17:39:02","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005200745","Sim=
e Building","","07-06-2025 17:34:35","07-06-2025 17:25:25","07-06-2025 17:4=
4:15","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","gerard.tchan=
goue@matech-cameroun.com","551","07-06-2025 17:34:35","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005200739","N=
koabang2","","07-06-2025 17:33:15","07-06-2025 17:17:09","07-06-2025 17:20:=
01","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // He reduced load","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due t=
o gen overload (22KVA, 330A), SS Blaise IHS is informed // He reduced load"=
,"vanel.mbiada@matech-cameroun.com","968","07-06-2025 17:33:15","MATECH CMR=
"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0005200737","Sap=
eur Mimboman","","07-06-2025 17:32:57","07-06-2025 17:23:36","07-06-2025 17=
:34:36","Grid outage site went down due to gen overload(22 kva,318 A)// He =
reduce load and gen manually started","Mba Lazare Herve","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to =
gen overload(22 kva,318 A)// He reduce load and gen manually started","gera=
rd.tchangoue@matech-cameroun.com","562","07-06-2025 17:32:57","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0005200732","B=
riqueterie","","07-06-2025 17:32:18","07-06-2025 17:17:06","07-06-2025 18:2=
5:26","Grid Only SITE, No space to deploy MDGE // Grid returned","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only SITE=
, No space to deploy MDGE // Grid returned","vanel.mbiada@matech-cameroun.c=
om","913","07-06-2025 17:32:18","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0005200725","Eko=
mbitie","","07-06-2025 17:31:40","07-06-2025 17:22:27","07-06-2025 18:37:15=
","Active, No power issue on site ,site on Grid with Ubaie=3D54.5 V The Tx =
FME Synphorien /691316854//from huawei is informed","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active, No power issue on site ,site on Grid with Ubaie=3D54.5 V The=
 Tx FME Synphorien /691316854//from huawei is informed","gerard.tchangoue@m=
atech-cameroun.com","554","07-06-2025 17:31:40","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005200717","HOP=
ITAL DE LA CAISSE","","07-06-2025 17:30:05","07-06-2025 17:20:56","07-06-20=
25 17:23:56","Grid outage, Site went down before Gen start due to poor back=
up // Gen started automatically","Delor Telezing","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen started automatically","gera=
rd.tchangoue@matech-cameroun.com","549","07-06-2025 17:30:05","MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0005200700","C=
ite-Verte","","07-06-2025 17:26:39","07-06-2025 17:16:29","07-06-2025 17:55=
:56","Grid only site, Grid outage // MG deployed","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid only site, Grid outage /=
/ MG deployed","vanel.mbiada@matech-cameroun.com","612","07-06-2025 17:26:3=
9","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005200647","NKO=
MKANA ELIZA HOTEL","","07-06-2025 17:20:57","07-06-2025 17:15:52","07-06-20=
25 17:41:37","Active//No power issue, Site on Grid Ubaie: 49.4V. The Tx FME=
 Brice Tsague(650214096) from Huawei is informed.","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue, Site on Grid Ubaie: 53.2V. The Tx FME Brice Tsague(650214096=
) from Huawei is informed.","gerard.tchangoue@matech-cameroun.com","306","0=
7-06-2025 17:20:57","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005200591","O=
dza-PK10","","07-06-2025 17:15:16","07-06-2025 17:05:08","07-06-2025 18:02:=
44","Grid outage, site went down due to PWC ZTE dysfunctionment // He reset=
 it and reduced load, site on Gen ","Albran Byorel","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Grid outage, site went dow=
n due to PWC ZTE dysfunctionment // He reset it and reduced load, site on G=
en ","vanel.mbiada@matech-cameroun.com","609","07-06-2025 17:15:16","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0005200570","N=
gousso-II","","07-06-2025 17:11:34","07-06-2025 16:52:14","07-06-2025 19:38=
:02","Grid outage, Site went down due to Gen Overload // Grid return","MFOU=
AGUEGUE MATHIEU","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage, Site went down due to Gen Overload // Grid return","vanel.mbi=
ada@matech-cameroun.com","1161","07-06-2025 17:11:34","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005200445","M=
vog-Ebanda","","07-06-2025 16:50:08","07-06-2025 16:44:05","07-06-2025 17:4=
0:01","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, site went down because Gen failed to start due t=
o underfrequency alarm // He reset it anf Gen manually started","vanel.mbia=
da@matech-cameroun.com","343337","07-06-2025 16:50:08","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005200441","A=
bom","IHS_YND_269","07-06-2025 16:49:20","07-06-2025 16:44:05","07-06-2025 =
17:40:01","Grid outage, site went down because Gen failed to start due to u=
nderfrequency alarm // He reset it anf Gen manually started","Siligap Boris=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge, site went down because Gen failed to start due to underfrequency alarm =
// He reset it anf Gen manually started","vanel.mbiada@matech-cameroun.com"=
,"316","07-06-2025 16:49:20","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005200428","Ron=
d Point Express1114","","07-06-2025 16:42:18","07-06-2025 16:37:09","07-06-=
2025 17:43:57","Grid outage.gen failed to start due to alarm ""high temp"" =
//We add water and gen manually started ","Hyemafo Gildas","Equipment Repai=
r","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gr=
id outage, Site went down before Gen start due to poor backup // Gen starte=
d automatically","gerard.tchangoue@matech-cameroun.com","310","07-06-2025 1=
6:42:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005200365","MEHANDAN=
","","07-06-2025 16:31:50","07-06-2025 16:27:38","07-06-2025 18:42:06","Cas=
caded Incident from TTO5351504","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Gri stabilized","system","3=
44304","07-06-2025 16:31:50","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005200361","O=
dza II OCM","IHS_YND_528","07-06-2025 16:31:12","07-06-2025 16:27:38","07-0=
6-2025 18:42:06","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Gri stabilized","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down because gen failed to start due to PWC ZTE malfunction // Gri st=
abilized","vanel.mbiada@matech-cameroun.com","216","07-06-2025 16:31:12","M=
ATECH CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0005200355","Nko=
lbisson","IHS_YND_763","07-06-2025 16:30:03","07-06-2025 14:40:43","07-06-2=
025 19:30:54","Backtracking Grid outage, ACCESS ISSUE due to Landlord // Gr=
id returned","TIENTCHEU NZETCHIEU GAEL","Access Denial","Lease Or Legal","L=
andlord Related Issues","Access Issue - Land Lord","Backtracking Grid outag=
e, ACCESS ISSUE due to Landlord // Grid returned","gerard.tchangoue@matech-=
cameroun.com","6561","07-06-2025 16:30:03","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005200235","Eto=
ug ebe Meweulo","","07-06-2025 16:08:11","07-06-2025 16:05:00","07-06-2025 =
19:16:51","Grid fluctuation site went down because Gen started and stopped =
due to Grid bad voltage // Grid stabilized","Hyemafo Gildas","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
n site went down because Gen started and stopped due to Grid bad voltage //=
 Grid stabilized","gerard.tchangoue@matech-cameroun.com","192","07-06-2025 =
16:08:11","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005200232","Ngo=
usso Vallee","","07-06-2025 16:06:53","07-06-2025 15:57:42","07-06-2025 16:=
17:42","No power issue UBaie =3D54,2V site on Grid. The FME TX SYMPHORIEN (=
675295205) From Huawei is informed","Siligap Boris","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue UBaie =3D54,2V site on Grid. The FME TX SYMPHORIEN (675295205) From Hua=
wei is informed","gerard.tchangoue@matech-cameroun.com","551","07-06-2025 1=
6:06:53","MATECH CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0005200139","S=
OA UNIVERSITY STADIUM","","07-06-2025 15:49:13","07-06-2025 15:47:04","07-0=
6-2025 16:03:04","Grid outage, site went down due to fuel shortage // Refue=
lling done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid outage, site went down due to fuel shortage // Refuelling done","va=
nel.mbiada@matech-cameroun.com","130","07-06-2025 15:49:13","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005200137","N=
kolso","","07-06-2025 15:48:38","07-06-2025 15:45:27","07-06-2025 15:55:27"=
,"Active// No power issue, site is on Grid with Ubaie=3D54,9V, Mohamadou(69=
1144435) from Huawei is informed	","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive// No power issue, site is on Grid with Ubaie=3D54,9V, Mohamadou(69114=
4435) from Huawei is informed	","vanel.mbiada@matech-cameroun.com","192","0=
7-06-2025 15:48:38","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005200126","S=
tade-Abega","","07-06-2025 15:47:12","07-06-2025 15:40:00","07-06-2025 18:1=
2:02","Grid outage,site went down because Gen failed to start due to pwc ZT=
E dysfunction// he reset it and site on Grid","Mba Lazare Herve","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage,s=
ite went down because Gen failed to start due to pwc ZTE dysfunction// he r=
eset it and site on Grid","vanel.mbiada@matech-cameroun.com","433","07-06-2=
025 15:47:12","MATECH CMR"
"Closed Complete","Site Down","T1739","IHS_YND_691","NOCINC0005200108","Mba=
lla 2 REGIE","","07-06-2025 15:43:11","07-06-2025 15:37:52","07-06-2025 20:=
16:29","Site went down due to PSC3 Controller dysfunctionning// He reset it=
","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Site went down due to PSC3 Controller dysfunctionning// He reset it=
","gerard.tchangoue@matech-cameroun.com","319","07-06-2025 15:43:11","MATEC=
H CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005200081","Nko=
lbisson IITA LP","","07-06-2025 15:38:56","07-06-2025 15:32:44","07-06-2025=
 19:27:49","Grid Only, No space to deploy MDGE // Grid restored","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No =
space to deploy MDGE // Grid restored","gerard.tchangoue@matech-cameroun.co=
m","372","07-06-2025 15:38:56","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005200072","T=
alla Monatele","","07-06-2025 15:37:44","07-06-2025 15:35:34","07-06-2025 1=
5:45:34","No power issue, site is on grid with Ubaie=3D54.9V, TX FME Gregoi=
r (654547479) from Huawei is informed","Parker Tchoup","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue, site is on grid with Ubaie=3D54.9V, Gregoir (654547479) from Huawei=
 is informed","vanel.mbiada@matech-cameroun.com","130","07-06-2025 15:37:44=
","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005200056","B=
astos-Nylon","","07-06-2025 15:33:02","07-06-2025 15:26:37","07-06-2025 17:=
54:50","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage, site went down due to gen over load 240A pour 1=
7,5kVA //  He reduce the load and manually start the Gen","vanel.mbiada@mat=
ech-cameroun.com","347895","07-06-2025 15:33:02","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005200049","T=
singa","","07-06-2025 15:31:23","07-06-2025 15:26:37","07-06-2025 17:54:50"=
,"","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down due to gen over load 240A pour 17,5kVA=
 //  He reduce the load and manually start the Gen","vanel.mbiada@matech-ca=
meroun.com","347894","07-06-2025 15:31:23","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0005200045","N=
komkana 2","IHS_YND_126, IHS_YND_127","07-06-2025 15:30:51","07-06-2025 15:=
26:37","07-06-2025 17:54:50","Grid outage, site went down due to gen over l=
oad 240A pour 17,5kVA //  He reduce the load and manually start the Gen","M=
boua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to gen over load 240A pour 17,5kVA //  He red=
uce the load and manually start the Gen","vanel.mbiada@matech-cameroun.com"=
,"255","07-06-2025 15:30:51","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005200044","Mok=
olo Yaounde","","07-06-2025 15:30:35","07-06-2025 15:24:28","07-06-2025 16:=
35:47","Site went down due to insufficient of rectifier on site SS IHS Bern=
ard is informed // Site stabilised","","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to insufficient of rectifier on=
 site SS IHS Bernard is informed // Site stabilised","gerard.tchangoue@mate=
ch-cameroun.com","369","07-06-2025 15:30:35","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005200026","E=
mana lycee 2","","07-06-2025 15:25:26","07-06-2025 15:24:15","07-06-2025 17=
:29:56","Grid outage, site went  down due to Gen overload (20 KVA, 260A) //=
 He reduced 02 batteries racks","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage, site went  down due to Gen o=
verload (20 KVA, 260A) // He reduced 02 batteries racks","vanel.mbiada@mate=
ch-cameroun.com","73","07-06-2025 15:25:26","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005200017","A=
wae Escalier","","07-06-2025 15:22:48","07-06-2025 14:26:39","07-06-2025 18=
:18:39","Grid fluctuation,site went dowwn because Gen failed to start due t=
o Grid bad voltage//He bypassed the Grid and started gen manually","Albran =
Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation,site went dowwn because Gen failed to start due to =
Grid bad voltage//He bypassed the Grid and started gen manually","vanel.mbi=
ada@matech-cameroun.com","3370","07-06-2025 15:22:48","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005200016","Nsi=
meyong","","07-06-2025 15:22:30","07-06-2025 14:44:55","07-06-2025 17:54:55=
","Grid fluctuation,Site went down because Gen failed to start due to grid =
bad voltage//he bypassed the Grid and site on Gen","MINKA NICOLAS","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation,Site went down because Gen failed to start due to grid bad voltage/=
/he bypassed the Grid and site on Gen","gerard.tchangoue@matech-cameroun.co=
m","2256","07-06-2025 15:22:30","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005200015","C=
hapelle-Nsimeyong","","07-06-2025 15:22:13","07-06-2025 14:25:04","07-06-20=
25 17:16:51","Grid outage, site went down because gen failed to start due t=
o gen card faulty //Gen manually started","MINKA NICOLAS","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down =
because gen failed to start due to gen card faulty //Gen manually started",=
"vanel.mbiada@matech-cameroun.com","3429","07-06-2025 15:22:13","MATECH CMR=
"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0005199992","San=
ta Barbara Yde","IHS_YND_277, IHS_YND_242","07-06-2025 15:17:15","07-06-202=
5 15:08:04","07-06-2025 17:28:11","Grid outage, site went down because gen =
ran untill fuel shortage // refuelling done","Delor Telezing","Fuel Outage"=
,"Passive","Diesel","Diesel Outage","Grid outage, site went down because ge=
n ran untill fuel shortage // refuelling done","gerard.tchangoue@matech-cam=
eroun.com","552","07-06-2025 15:17:15","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005199984","O=
kola OCM","","07-06-2025 15:16:01","07-06-2025 15:09:52","07-06-2025 17:38:=
09","Site went down because 02/03 rectifiers dysfunctionned// He reset rect=
ifiers","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down because 02/03 rectifiers dysfunctionned=
// He reset rectifiers","vanel.mbiada@matech-cameroun.com","370","07-06-202=
5 15:16:01","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005199969","A=
ccacia New","","07-06-2025 15:13:53","07-06-2025 15:08:33","07-06-2025 18:0=
8:18","Grid outage ,no space to deploy a mobil gen//Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,n=
o space to deploy a mobil gen//Grid return","vanel.mbiada@matech-cameroun.c=
om","322","07-06-2025 15:13:53","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005199951","M=
ANGUIERS CHAPELLE","","07-06-2025 15:07:14","07-06-2025 15:04:06","07-06-20=
25 15:05:05","No power issue site on gen with U=3D56.2v Armand Nguetsa from=
 Huawei is informed ","Fabrice Pouakam","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
gen with U=3D56.2v Armand Nguetsa from Huawei is informed ","vanel.mbiada@m=
atech-cameroun.com","190","07-06-2025 15:07:14","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0005199946","M=
anguier","","07-06-2025 15:06:44","07-06-2025 15:04:27","07-06-2025 17:16:3=
8","Grid outage,gen Stopped due to Alarm High temp // Water Add in radiator=
 and Gen start manually.","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","Gen Temp High","Grid outage,gen Stopped due to Alarm High temp //=
 Water Add in radiator and Gen start manually.","vanel.mbiada@matech-camero=
un.com","137","07-06-2025 15:06:44","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005199894","Bit=
eng-Maetur","","07-06-2025 14:56:57","07-06-2025 14:48:39","07-06-2025 19:0=
5:59","Grid outage site went down because Gen failed to start due PWC ZTE d=
ysfonction // He reset the PWC and Gen manually started","Mba Lazare Herve"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage site went down because Gen failed to start due PWC ZTE dysfonctio=
n // He reset the PWC and Gen manually started","cedric.tiani@matech-camero=
un.com","500","07-06-2025 14:56:57","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005199815","A=
wae Ewonkan","","07-06-2025 14:52:05","07-06-2025 14:04:53","07-06-2025 14:=
52:40","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed //  Grid returned","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed //  Grid=
 returned","edwige.kapawo@matech-cameroun.com","2833","07-06-2025 14:52:05"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005199790","C=
arrefourt Nkomo","IHS_YND_175","07-06-2025 14:49:45","07-06-2025 14:40:26",=
"07-06-2025 15:27:27","No power issue site on grid with U=3D48v Lionnel Ste=
eve from Huawei site up at 05:59 PM","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on grid with U=3D48v Lionnel Steeve from Huawei site up at 05:=
59 PM","edwige.kapawo@matech-cameroun.com","560","07-06-2025 14:49:45","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005199753","B=
arriere IHS","","07-06-2025 14:44:36","07-06-2025 14:35:19","07-06-2025 15:=
13:21","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed //Grid return","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to=
 Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed //Grid return","e=
dwige.kapawo@matech-cameroun.com","558","07-06-2025 14:44:36","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005199737","B=
arriere","","07-06-2025 14:42:33","07-06-2025 14:38:24","07-06-2025 14:45:2=
4","No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266068/=
Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
bay: 54.6V site on Gen TX Fme SAMBA (654266068/Huawei) is informed.","edwig=
e.kapawo@matech-cameroun.com","250","07-06-2025 14:42:33","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005199733","M=
essassi 2","","07-06-2025 14:41:50","07-06-2025 14:33:39","07-06-2025 15:14=
:19","SYLVAIN kamdem / BTR / 682398693 working on site (swapp of PWC) // En=
d of work","Fabrice Pouakam","Installation Activity","Passive","Planned Act=
ivity","Installation Activity","SYLVAIN kamdem / BTR / 682398693 working on=
 site (swapp of PWC) // End of work","edwige.kapawo@matech-cameroun.com","4=
93","07-06-2025 14:41:50","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005199611","A=
WAE OCM","","07-06-2025 14:35:17","07-06-2025 14:32:09","07-06-2025 17:48:5=
9","Grid outage site went down because Gen failed to start due PWC ZTE dysf=
onctionned // He reset the PWC and sitd on Grid","Mba Lazare Herve","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outag=
e site went down because Gen failed to start due PWC ZTE dysfonctionned // =
He reset the PWC and sitd on Grid","edwige.kapawo@matech-cameroun.com","190=
","07-06-2025 14:35:17","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005199606","N=
YOM 2 IHS","","07-06-2025 14:33:53","07-06-2025 13:52:41","07-06-2025 19:29=
:27","Bactracking Site went down because the PWC OF ZTE dysfonction // He r=
eset the PWC","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","R=
ectifier Module Overloaded","Bactracking Site went down because the PWC OF =
ZTE dysfonction // He reset the PWC","edwige.kapawo@matech-cameroun.com","2=
474","07-06-2025 14:33:53","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005199578","N=
komo","","07-06-2025 14:32:16","07-06-2025 14:40:26","07-06-2025 15:27:27",=
"Site impacted by Carrefourt Nkomo","Mba Lazare Herve","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D48v Lionnel Steeve from Huawei site up at 05:59 PM","cedric.tiani@matech=
-cameroun.com","408183","07-06-2025 14:32:16","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005199469","N=
kolbong","","07-06-2025 14:10:41","07-06-2025 13:46:25","07-06-2025 13:49:5=
0","Site went Down because Gen started and stopped due to Gen overload(22kv=
a//350A)//We reduce load and gen manually started ","Delor Telezing","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Site went Down because=
 Gen started and stopped due to Gen overload(22kva//350A)//We reduce load a=
nd gen manually started ","edwige.kapawo@matech-cameroun.com","1457","07-06=
-2025 14:10:41","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0005199445","A=
battoir","","07-06-2025 14:01:45","07-06-2025 13:53:27","07-06-2025 15:11:3=
2","Grid outage gen failed to start due to battery GE faulty//Gen manually =
started with external battery","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Generator Battery","Grid outage gen failed to start d=
ue to battery GE faulty//Gen manually started with external battery","edwig=
e.kapawo@matech-cameroun.com","499","07-06-2025 14:01:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0005199436","Mamch Bu=
ilding","","07-06-2025 14:00:09","07-06-2025 13:50:44","07-06-2025 14:11:10=
","Cascaded Incident from TTO5350447","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage no space to deploy m=
obile gen // Grid return","system","1216495","07-06-2025 14:00:09","MATECH =
CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005199431","C=
harles-Atangana","IHS_YND_051","07-06-2025 13:58:53","07-06-2025 13:50:44",=
"07-06-2025 14:11:10","Grid outage no space to deploy mobile gen // Grid re=
turn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Grid outage no space to deploy mobile gen // Grid return","edwige.kapawo@=
matech-cameroun.com","490","07-06-2025 13:58:53","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005199410","E=
MANA BILICK CITY","","07-06-2025 13:53:23","07-06-2025 13:48:15","07-06-202=
5 17:40:15","Grid outage, site down because site behaves as Grid only site =
(Gen Noise) // Grid return","Fabrice Pouakam","Access Denial","Lease Or Leg=
al","Landlord Related Issues","Access Issue - Land Lord","Grid outage, site=
 down because site behaves as Grid only site (Gen Noise) // Grid return","e=
dwige.kapawo@matech-cameroun.com","310","07-06-2025 13:53:23","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005199360","S=
atcom","","07-06-2025 13:41:42","07-06-2025 13:22:29","07-06-2025 13:50:49"=
,"Active // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand =
Ngestsa (691144412) of huawei is informed","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue site on Grid with Ubaie=3D53,02 V Tx Fme Armand Ngest=
sa (691144412) of huawei is informed","edwige.kapawo@matech-cameroun.com","=
1154","07-06-2025 13:41:42","MATECH CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0005199164","Bon=
djock","","07-06-2025 13:07:39","07-06-2025 10:57:27","07-06-2025 14:12:34"=
,"Grid outage gen ran until fuel shortage//Refueling done","Fanda Brice","F=
uel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran until f=
uel shortage//Refueling done","cedric.tiani@matech-cameroun.com","7813","07=
-06-2025 13:07:39","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005199161","Beh=
ind P T school Yde","","07-06-2025 13:06:42","07-06-2025 11:31:27","07-06-2=
025 13:59:47","Grid Outage, Site went down because The rectifiers are not p=
owered due to diysfonctioning of MPR on site // He reset the MPR","Paul BIB=
OUM","Equipment Repair","Passive","Rectifier","Rectifier Module","Grid Outa=
ge, Site went down because The rectifiers are not powered due to diysfoncti=
oning of MPR on site // He reset the MPR","cedric.tiani@matech-cameroun.com=
","5715","07-06-2025 13:06:42","MATECH CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0005199159","BEA=
TITUDE ENTR=C9E PAVE","","07-06-2025 13:06:02","07-06-2025 11:40:47","07-06=
-2025 16:36:59","Site went down because 02/03 rectifiers went faulty // He =
reset it","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down because 02/03 rectifiers went faulty =
// He reset it","cedric.tiani@matech-cameroun.com","5116","07-06-2025 13:06=
:02","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005199153","ODZ=
A MINKAN EDIBI ASSI","","07-06-2025 13:05:20","07-06-2025 11:58:03","07-06-=
2025 14:25:29","Grid Outage, site went down because gen failed to start due=
 to PWC ZTE malfunction // He reset it and started the Gen manually","Albra=
n Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overlo=
aded","Grid Outage, site went down because gen failed to start due to PWC Z=
TE malfunction // He reset it and started the Gen manually","cedric.tiani@m=
atech-cameroun.com","4038","07-06-2025 13:05:20","MATECH CMR"
"Closed Complete","Site Down","T2104","IHS_YND_711","NOCINC0005199147","H-F=
ranco New","","07-06-2025 13:04:15","07-06-2025 12:42:54","07-06-2025 13:30=
:07","Grid outage, Site went down because GEN OVERLOAD (20KVA, 320A) RM IHS=
 BATE is informed// Grid return","Delor Telezing","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage, Site went down because GEN O=
VERLOAD (20KVA, 320A) RM IHS BATE is informed// Grid return","cedric.tiani@=
matech-cameroun.com","1282","07-06-2025 13:04:15","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0005199141","UPA=
C LP","","07-06-2025 13:03:29","07-06-2025 12:53:03","07-06-2025 13:30:28",=
"Grid outage .no space to deploy mobile gen // Grid returned","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage .no s=
pace to deploy mobile gen // Grid returned","cedric.tiani@matech-cameroun.c=
om","628","07-06-2025 13:03:29","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005199136","O=
lembe-Terminus","","07-06-2025 13:01:52","07-06-2025 13:00:33","07-06-2025 =
17:18:40","Grid outage, site went down because gen failed to start due to P=
WC ZTE malfunction // Gri stabilized","Fabrice Pouakam","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site went=
 down because gen failed to start due to PWC ZTE malfunction // Gri stabili=
zed","edwige.kapawo@matech-cameroun.com","81","07-06-2025 13:01:52","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005199090","O=
lembe-Terminus","","07-06-2025 12:54:17","07-06-2025 08:22:04","07-06-2025 =
12:51:37","Site went done due to work done by Valentin(698529863)swapp PWC/=
/End of works","Fabrice Pouakam","Installation Activity","Passive","Planned=
 Activity","Installation Activity","Site went done due to work done by Vale=
ntin(698529863)swapp PWC//End of works","edwige.kapawo@matech-cameroun.com"=
,"16334","07-06-2025 12:54:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0005199081","Crf Corn=
ier","","07-06-2025 12:52:36","07-06-2025 12:46:23","07-06-2025 13:12:48","=
Cascaded Incident from TTO5350016","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to disjunction i=
n the energy bay of a 125A circuit breaker already bridged with another 125=
A. (Need a second depart ) //Circuit breaker rearm","system","351212","07-0=
6-2025 12:52:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0005199080","Mobil-Es=
sos","","07-06-2025 12:52:36","07-06-2025 12:46:23","07-06-2025 13:12:48","=
Cascaded Incident from TTO5350016","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to disjunction i=
n the energy bay of a 125A circuit breaker already bridged with another 125=
A. (Need a second depart ) //Circuit breaker rearm","system","351211","07-0=
6-2025 12:52:36","MATECH CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0005199075","M=
adison","IHS_YND_109, IHS_YND_566","07-06-2025 12:51:32","07-06-2025 12:46:=
23","07-06-2025 16:52:28","Site went down due to disjunction in the energy =
bay of a 125A circuit breaker already bridged with another 125A. (Need a se=
cond depart ) //Circuit breaker rearm","MFOUAGUEGUE MATHIEU","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Site went down du=
e to disjunction in the energy bay of a 125A circuit breaker already bridge=
d with another 125A. (Need a second depart ) //Circuit breaker rearm","edwi=
ge.kapawo@matech-cameroun.com","309","07-06-2025 12:51:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0005199048","Scalom-I=
HS","","07-06-2025 12:47:01","07-06-2025 12:40:14","07-06-2025 14:04:19","C=
ascaded Incident from TTO5349979","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because Gen failed to=
 start due to PWC ZTE malfunction // Grid restoration","system","351575","0=
7-06-2025 12:47:01","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0005199046","S=
calom","IHS_YND_505","07-06-2025 12:46:22","07-06-2025 12:40:14","07-06-202=
5 14:08:59","Grid outage, site went down because Gen failed to start due to=
 PWC ZTE malfunction // Grid restoration","Paul BIBOUM","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","Grid outage, site went down becau=
se Gen failed to start due to PWC ZTE malfunction // Grid restoration","edw=
ige.kapawo@matech-cameroun.com","369","07-06-2025 12:46:22","MATECH CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0005198949","H=
-Franco New","","07-06-2025 12:18:22","07-06-2025 12:16:15","07-06-2025 12:=
33:40","Grid outtage site went down due to gen overload//We reduce load and=
 gen manually started","Delor Telezing","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","Grid outtage site went down due to gen overload//We=
 reduce load and gen manually started","cedric.tiani@matech-cameroun.com","=
128","07-06-2025 12:18:22","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005198939","M=
vog-Ada_OCM","","07-06-2025 12:15:52","07-06-2025 12:09:40","07-06-2025 14:=
23:29","Grid Only site, No space to deploy MGE // Grid returned","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only site=
, No space to deploy MGE // Grid returned","edwige.kapawo@matech-cameroun.c=
om","373","07-06-2025 12:15:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005198781","Ahala","=
","07-06-2025 11:48:23","07-06-2025 09:41:16","07-06-2025 12:25:51","Cascad=
ed Incident from TTO5348991","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Gen o=
verload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Grid =
return","system","362094","07-06-2025 11:48:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0005198715","Nkolo II=
 New","","07-06-2025 11:41:50","07-06-2025 10:06:45","07-06-2025 12:18:37",=
"Cascaded Incident from TTO5349613","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause gen failed to start due to PWC ZTE malfunction, Cyril IHS is informed =
// He reset controller and gen manually started","system","360701","07-06-2=
025 11:41:50","MATECH CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0005198712","M=
imboman-Village","IHS_YND_709","07-06-2025 11:41:16","07-06-2025 10:06:45",=
"07-06-2025 12:18:37","Grid outage, site went down because gen failed to st=
art due to PWC ZTE malfunction, Cyril IHS is informed // He reset controlle=
r and gen manually started","Mba Lazare Herve","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage, site went down bec=
ause gen failed to start due to PWC ZTE malfunction, Cyril IHS is informed =
// He reset controller and gen manually started","edwige.kapawo@matech-came=
roun.com","5672","07-06-2025 11:41:16","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005198633","C=
rf-Nsam","","07-06-2025 11:25:39","07-06-2025 11:20:32","07-06-2025 11:47:1=
1","Active//No power issue on site Ubaie =3D50.9V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D50.9V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","edwige.kapawo@matech-cameroun.com","308",=
"07-06-2025 11:25:39","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005198624","E=
toudi","","07-06-2025 11:22:39","07-06-2025 11:20:30","07-06-2025 11:23:43"=
,"Grid outage, Site went down dute to PWC dysfunction //He reset it and sit=
e on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rect=
ifier Module Overloaded","Grid outage, Site went down dute to PWC dysfuncti=
on //He reset it and site on Grid","edwige.kapawo@matech-cameroun.com","130=
","07-06-2025 11:22:39","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005198620","B=
arriere IHS","","07-06-2025 11:21:33","07-06-2025 11:14:02","07-06-2025 11:=
24:48","	Grid outage; Site went Down due to PWC dysfunctionned  SS IHS FELI=
X ZAMBE is informed//Site stabilized","Hyemafo Gildas","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","	Grid outage; Site went=
 Down due to PWC dysfunctionned  SS IHS FELIX ZAMBE is informed//Site stabi=
lized","edwige.kapawo@matech-cameroun.com","453","07-06-2025 11:21:33","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005198546","N=
omayos montee Meche","","07-06-2025 11:05:22","07-06-2025 11:04:59","07-06-=
2025 11:07:38","Grid outage, site went down before gen start due to poor ba=
ttery backup // Gen start automatically","Fanda Brice","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Grid outa=
ge, site went down before gen start due to poor battery backup // Gen start=
 automatically","edwige.kapawo@matech-cameroun.com","24","07-06-2025 11:05:=
22","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005198529","Odz=
a petit marche new","","07-06-2025 11:02:50","07-06-2025 09:41:14","07-06-2=
025 11:02:30","Backtracking 	Grid fluctuation,Site went down because GEN fa=
iled to start due to grid bad voltage  // He bypass grid and manually start=
 the gen	","Albran Byorel","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","Grid fluctuation,Site went down because GEN faile=
d to start due to grid bad voltage  // He bypass grid and manually start th=
e gen	","cedric.tiani@matech-cameroun.com","4897","07-06-2025 11:02:50","MA=
TECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005198515","NYO=
M 2 IHS","","07-06-2025 10:59:37","07-06-2025 09:59:07","07-06-2025 11:42:4=
8","	Bactracking Site went down because the PWC OF ZTE dysfonction // He re=
set the PWC","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","	Bactracking Site went down because the PWC OF =
ZTE dysfonction // He reset the PWC","cedric.tiani@matech-cameroun.com","36=
31","07-06-2025 10:59:37","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005198512","M=
endong vallee","","07-06-2025 10:58:52","07-06-2025 10:50:41","07-06-2025 1=
1:24:56","Grid outage site went down due to Gen overload (20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed and confirmed //Grid return","Fanda Brice","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site wen=
t down due to Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed an=
d confirmed //Grid return","edwige.kapawo@matech-cameroun.com","492","07-06=
-2025 10:58:52","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005198507","Men=
dong NB","","07-06-2025 10:57:44","07-06-2025 09:51:53","07-06-2025 11:07:2=
5","Bactracking Grid outage no space to deployed a mobile Gen awaiting // G=
rid return","","Grid Supply","Passive","Grid","National Grid - Grid Outage =
Issue","Grid outage no space to deployed a mobile Gen awaiting // Grid retu=
rn","cedric.tiani@matech-cameroun.com","3952","07-06-2025 10:57:44","MATECH=
 CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005198500","Jou=
vence Mbenda","","07-06-2025 10:55:31","07-06-2025 09:57:13","07-06-2025 11=
:13:54","Backtracking Grid outage, site went down because gen start and sto=
pped with high temp alarm // He added water and manually start the gen","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine T=
emp - Coolant Level Issue","Backtracking Grid outage, site went down becaus=
e gen start and stopped with high temp alarm // He added water and manually=
 start the gen","cedric.tiani@matech-cameroun.com","3499","07-06-2025 10:55=
:31","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0005198494","Nko=
lbisson usines des eaux 2","","07-06-2025 10:54:39","07-06-2025 09:50:19","=
07-06-2025 11:31:06","Grid outage, Site went down because Gen failed to sta=
rt due to battery Gen faulty// He started Gen with external battery","TIENT=
CHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Battery","Grid outage, Site went down because Gen failed to start due t=
o battery Gen faulty// He started Gen with external battery","cedric.tiani@=
matech-cameroun.com","3861","07-06-2025 10:54:39","MATECH CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0005198479","K=
ondengui","","07-06-2025 10:52:15","07-06-2025 10:50:05","07-06-2025 12:09:=
47","Site went down due to rectifiers dysfunctionned//We reset rectifiers",=
"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to rectifiers dysfunctionned//We reset rectifiers","ed=
wige.kapawo@matech-cameroun.com","131","07-06-2025 10:52:15","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005198477","EKI=
E","","07-06-2025 10:51:47","07-06-2025 10:38:57","07-06-2025 11:08:10","BA=
CKTRACKING Grid outage, site went down due to Grid bad voltage // Grid stab=
ilised","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","BACKTRACKING Grid outage, site went down due to Grid=
 bad voltage // Grid stabilised","cedric.tiani@matech-cameroun.com","770","=
07-06-2025 10:51:47","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005198435","S=
apeur Mimboman","","07-06-2025 10:42:18","07-06-2025 10:36:08","07-06-2025 =
11:59:54","Grid outage site went down due to gen overload(22 kva,318 A)// H=
e reduce load and gen manually started","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o gen overload(22 kva,318 A)// He reduce load and gen manually started","ed=
wige.kapawo@matech-cameroun.com","371","07-06-2025 10:42:18","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005198409","C=
harles-Atangana","","07-06-2025 10:35:42","07-06-2025 10:15:36","07-06-2025=
 11:01:34","Grid outage no space to deploy mobile gen //Grid return","","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gr=
id outage no space to deploy mobile gen //Grid return","edwige.kapawo@matec=
h-cameroun.com","1208","07-06-2025 10:35:42","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005198367","E=
toug ebe Meweulo","","07-06-2025 10:27:29","07-06-2025 10:23:17","07-06-202=
5 12:08:22","Site went down due to GEN CB disjuncted//We rearmed CB and sit=
e on gen ","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","F=
aulty Circuit Breaker","Site went down due to GEN CB disjuncted//We rearmed=
 CB and site on gen ","edwige.kapawo@matech-cameroun.com","253","07-06-2025=
 10:27:29","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005198363","E=
MANA BILICK CITY","","07-06-2025 10:25:50","07-06-2025 10:15:59","07-06-202=
5 11:30:40","Grid outage, site down because site behaves as Grid only site =
(Gen Noise) // Grid return","Fabrice Pouakam","Access Denial","Lease Or Leg=
al","Landlord Related Issues","Access Issue - Land Lord","Grid outage, site=
 down because site behaves as Grid only site (Gen Noise) // Grid return","e=
dwige.kapawo@matech-cameroun.com","593","07-06-2025 10:25:50","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005198215","Efo=
ulan MTN","","07-06-2025 09:55:01","07-06-2025 09:01:41","07-06-2025 09:15:=
51","Bactracking Grid outage, Site went down before Gen start due to poor b=
ackup // Gen started automaticaly","MINKA NICOLAS","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup // Gen started automaticaly","cedr=
ic.tiani@matech-cameroun.com","3201","07-06-2025 09:55:01","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005198208","ODZ=
A MINKAN EDIBI ASSI","","07-06-2025 09:54:01","07-06-2025 09:38:22","07-06-=
2025 11:00:25","Site went down due to rectifier dysfunctionning//We reset r=
ectifiers ","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to rectifier dysfunctionning//We reset rec=
tifiers ","cedric.tiani@matech-cameroun.com","940","07-06-2025 09:54:01","M=
ATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005198200","MBA=
LNGONG LYCEE","","07-06-2025 09:51:07","07-06-2025 08:53:59","07-06-2025 10=
:50:59","BACKTRACKING  Site went down because Gen stopped due to overload(9=
kva, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fand=
a Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site we=
nt down because Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe =
is informed and confirmed//Grid return","cedric.tiani@matech-cameroun.com",=
"3430","07-06-2025 09:51:07","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005198195","Mon=
tee Jouvence","","07-06-2025 09:50:19","07-06-2025 08:49:56","07-06-2025 11=
:37:55","bactracking Grid outage.gen failed to start due to ""high temp"" a=
larm//We add water and gen manually started","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue",=
"Grid outage.gen failed to start due to ""high temp"" alarm//We add water a=
nd gen manually started","cedric.tiani@matech-cameroun.com","3624","07-06-2=
025 09:50:19","MATECH CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0005198193","E=
SSOS OASIS 1111","","07-06-2025 09:50:08","07-06-2025 09:48:01","07-06-2025=
 11:27:34","Grid outage, Site went down because Gen overload (17kva, 250A)/=
/Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, Site went down because Gen overload (17kva, 250A=
)//Grid return","edwige.kapawo@matech-cameroun.com","128","07-06-2025 09:50=
:08","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005198189","Ron=
d Point Express1114","","07-06-2025 09:49:17","07-06-2025 09:13:53","07-06-=
2025 09:28:02","backtracking Grid outage, Site went down before Gen start d=
ue to poor backup // Gen started automatically","Hyemafo Gildas","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge, Site went down before Gen start due to poor backup // Gen started autom=
atically","cedric.tiani@matech-cameroun.com","2125","07-06-2025 09:49:17","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0005198179","Afanoya"=
,"","07-06-2025 09:46:30","07-06-2025 09:41:16","07-06-2025 12:25:51","Casc=
aded Incident from TTO5348991","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to Gen=
 overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Gri=
d return","system","362094","07-06-2025 09:46:30","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005198178","Eto=
ug ebe biscuiterie","","07-06-2025 09:46:28","07-06-2025 09:18:25","07-06-2=
025 10:22:13","BACK TRACKING Grid outage.gen failed to start due to poor ba=
ckup//Gen maually started ","Hyemafo Gildas","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","BACK TRACKING Grid outage.gen=
 failed to start due to poor backup//Gen maually started ","cedric.tiani@ma=
tech-cameroun.com","1684","07-06-2025 09:46:28","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005198173","M=
eyo","IHS_YND_257, IHS_YND_313, IHS_YND_762","07-06-2025 09:45:22","07-06-2=
025 09:41:16","07-06-2025 12:25:51","Grid outage, site went down due to Gen=
 overload (17KVA, 260A) SS HIS Felix Zambe is informed and confirmed // Gri=
d return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, site went down due to Gen overload (17KVA, 260A) SS=
 HIS Felix Zambe is informed and confirmed // Grid return","edwige.kapawo@m=
atech-cameroun.com","246","07-06-2025 09:45:22","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005198163","E=
toudi","","07-06-2025 09:43:20","07-06-2025 09:37:40","07-06-2025 10:17:45"=
,"Grid outage .site went down due to gen overload(20kva,300 A) //we reduce =
load and gen manually started ","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage .site went down due to gen ov=
erload(20kva,300 A) //we reduce load and gen manually started ","edwige.kap=
awo@matech-cameroun.com","341","07-06-2025 09:43:20","MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0005198006","B=
astos Bir","","07-06-2025 09:21:47","07-06-2025 09:00:12","07-06-2025 10:21=
:24","Grid outage.gen failed to start due to air intake//We purged and gen =
manually started ","Mboua Thierry","Fuel Outage (Probable)","Passive","ACDG=
 Gen","ACDG - Air Intake","Grid outage.gen failed to start due to air intak=
e//We purged and gen manually started ","edwige.kapawo@matech-cameroun.com"=
,"3246","07-06-2025 09:21:47","MATECH CMR"
"Closed Complete","Site Down","T3206","IHS_YND_759","NOCINC0005198005","Nko=
lfoulou Tsinga Village","","07-06-2025 09:21:47","07-06-2025 08:40:20","07-=
06-2025 09:22:35","Grid outage, site went down because Gen failed to start =
due to undervoltage alarm // He reset it and started Gen manually","Siligap=
 Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage, site went down because Gen failed to start due to undervoltage al=
arm // He reset it and started Gen manually","cedric.tiani@matech-cameroun.=
com","2488","07-06-2025 09:21:47","MATECH CMR"
"Closed Complete","Site Down","T1085","IHS_YND_130","NOCINC0005197998","Bas=
tos usine","","07-06-2025 09:19:54","07-06-2025 08:34:41","07-06-2025 09:30=
:07","BACKTRACKING//Site went down because Gen failed to start due to no au=
tomatism // He started Gen manually and put Gen in mode auto","Mboua Thierr=
y","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","BACKTRACKI=
NG//Site went down because Gen failed to start due to no automatism // He s=
tarted Gen manually and put Gen in mode auto","cedric.tiani@matech-cameroun=
.com","2713","07-06-2025 09:19:54","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005197957","Nko=
lbong","","07-06-2025 09:12:34","07-06-2025 08:28:04","07-06-2025 09:32:31"=
,"Site went Down because Gen started and stopped due to Gen overload(22kva/=
/350A) //  Grid return","Delor Telezing","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Site went Down because Gen started and stopped due=
 to Gen overload(22kva//350A) //  Grid return","cedric.tiani@matech-camerou=
n.com","2672","07-06-2025 09:12:34","MATECH CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0005197948","Ele=
veurs","","07-06-2025 09:09:26","07-06-2025 08:30:16","07-06-2025 09:35:06"=
,"Grid outage,site went down because Gen start and stopped with alarm*Short=
 circuit*//He reset the Gen card and start the Gen manually","Siligap Boris=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge,site went down because Gen start and stopped with alarm*Short circuit*//=
He reset the Gen card and start the Gen manually","cedric.tiani@matech-came=
roun.com","2351","07-06-2025 09:09:26","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005197926","Cit=
e des nations","","07-06-2025 09:04:35","07-06-2025 08:27:22","07-06-2025 0=
8:50:25","Active //No power issue ,site on Grid on site with Ubaie:53.7 V X=
 Fme Hosiah / 674007438 from huawei is informed","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active //No power issue ,site on Grid on site with Ubaie:53.7 V X Fme Hosia=
h / 674007438 from huawei is informed","cedric.tiani@matech-cameroun.com","=
2234","07-06-2025 09:04:35","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005197907","NKO=
MKANA ELIZA HOTEL","","07-06-2025 09:02:38","07-06-2025 08:28:19","07-06-20=
25 10:31:59","BACKTRACKING  Grid outage,no space to deploy MDG //Grid bretu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
BACKTRACKING  Grid outage,no space to deploy MDG //Grid breturn","cedric.ti=
ani@matech-cameroun.com","2060","07-06-2025 09:02:38","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005197880","N=
kolbi-Boss","","07-06-2025 08:55:01","07-06-2025 08:52:53","07-06-2025 09:2=
1:32","Grid outage, site went down before gen start due to poor battery bac=
kup // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before gen start due to poor battery backup // gen start autom=
atically","edwige.kapawo@matech-cameroun.com","129","07-06-2025 08:55:01","=
MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005197855","N=
yom OCM","","07-06-2025 08:50:35","07-06-2025 08:45:21","07-06-2025 09:30:4=
6","Site went down due to PWC ZTE  dysfunctionned // site stabilized ","Fab=
rice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Ov=
erloaded","Site went down due to PWC ZTE  dysfunctionned // site stabilized=
 ","edwige.kapawo@matech-cameroun.com","316","07-06-2025 08:50:35","MATECH =
CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0005197847","I=
mm-Olympique","","07-06-2025 08:49:44","07-06-2025 08:44:36","07-06-2025 10=
:04:44","Grid outage, site went down because gen stopped with under voltage=
 alarm // Reset done and gen started","Paul BIBOUM","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down becaus=
e gen stopped with under voltage alarm // Reset done and gen started","edwi=
ge.kapawo@matech-cameroun.com","308","07-06-2025 08:49:44","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005197816","N=
omayos montee Meche","","07-06-2025 08:43:01","07-06-2025 08:40:45","07-06-=
2025 08:43:55","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen Manually started","Fanda Brice","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup // Gen Manually started","edwige.kapawo@m=
atech-cameroun.com","137","07-06-2025 08:43:01","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005197813","M=
ontee-Des-Soeurs","","07-06-2025 08:41:42","07-06-2025 08:39:24","07-06-202=
5 09:26:35","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) //=
 Grid returned","edwige.kapawo@matech-cameroun.com","139","07-06-2025 08:41=
:42","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005197796","N=
koabang2","","07-06-2025 08:39:18","07-06-2025 08:33:07","07-06-2025 10:22:=
28","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ed=
wige.kapawo@matech-cameroun.com","373","07-06-2025 08:39:18","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005197789","S=
imbock OCM","","07-06-2025 08:38:35","07-06-2025 08:32:25","07-06-2025 11:1=
9:27","Active // No power issue Ubaie:51.5V site on battery The Tx Fme Hosi=
ah Mbah (674007438) of Huawei is informed","Hyemafo Gildas","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue Ubaie:51.5V site on battery The Tx Fme Hosiah Mbah (6=
74007438) of Huawei is informed","edwige.kapawo@matech-cameroun.com","371",=
"07-06-2025 08:38:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005197784","Golf Qua=
ter","","07-06-2025 08:36:54","07-06-2025 08:32:42","07-06-2025 09:28:21","=
Cascaded Incident from TTO5348505","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due=
 to automation failure//Gen manually started ","system","366122","07-06-202=
5 08:36:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005197785","Bastos B=
ethesda","","07-06-2025 08:36:54","07-06-2025 08:32:42","07-06-2025 09:28:2=
1","Cascaded Incident from TTO5348505","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage.gen failed to start=
 due to automation failure//Gen manually started ","system","366122","07-06=
-2025 08:36:54","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005197742","B=
astos-Nylon","IHS_YND_220, IHS_YND_563","07-06-2025 08:35:51","07-06-2025 0=
8:32:42","07-06-2025 09:28:21","Grid outage.gen failed to start due to auto=
mation failure//Gen manually started ","Mboua Thierry","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid outage.gen failed to start d=
ue to automation failure//Gen manually started ","edwige.kapawo@matech-came=
roun.com","190","07-06-2025 08:35:51","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005197731","M=
vog-Ada_OCM","","07-06-2025 08:35:05","07-06-2025 08:32:43","07-06-2025 10:=
59:33","Grid Only site, No space to deploy MDGE // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only site,=
 No space to deploy MDGE // Grid return","edwige.kapawo@matech-cameroun.com=
","143","07-06-2025 08:35:05","MATECH CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0005197724","Nsi=
meyong Terre Rouge","","07-06-2025 08:33:46","07-06-2025 08:24:39","07-06-2=
025 08:27:52","Grid outage, Site went down before Gen start due to poor bac=
kup // Gen started automatically","MINKA NICOLAS","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen started automatically","cedr=
ic.tiani@matech-cameroun.com","548","07-06-2025 08:33:46","MATECH CMR"
"Closed Complete","Site Down","CTR_419","IHS_YND_227","NOCINC0005197722","M=
vog Betsi","","07-06-2025 08:33:03","07-06-2025 08:28:44","07-06-2025 10:17=
:04","Grid-Gen, eneo fluctuation, site down due to poor backup // Grid retu=
rn","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Battery Low","Grid-Gen, eneo fluctuation, site down due to poor bac=
kup // Grid return","edwige.kapawo@matech-cameroun.com","260","07-06-2025 0=
8:33:03","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005197717","E=
MANA BILICK CITY","IHS_YND_279","07-06-2025 08:31:23","07-06-2025 08:28:15"=
,"07-06-2025 09:53:49","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid return","Fabrice Pouakam","Access Denial","L=
ease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid o=
utage, site down because site behaves as Grid only site (Gen Noise) // Grid=
 return","edwige.kapawo@matech-cameroun.com","190","07-06-2025 08:31:23","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005197706","E=
toudi","","07-06-2025 08:29:32","07-06-2025 08:27:05","07-06-2025 08:29:30"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen st=
arted automatically","Fabrice Pouakam","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup // Gen started automatically","edwige.kapawo@m=
atech-cameroun.com","148","07-06-2025 08:29:32","MATECH CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0005197642","Nko=
lfon Cimencam","","07-06-2025 08:10:48","07-06-2025 08:04:37","07-06-2025 1=
2:25:51","No power issue on site U=3D54,5v site on Gen FME Fulbert (6542660=
68) of huawei is informed.","Hyemafo Gildas","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site U=3D54,5v site on Gen FME Fulbert (654266068) of huawei is informed.",=
"cedric.tiani@matech-cameroun.com","372","07-06-2025 08:10:48","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005197483","E=
ssomba","","07-06-2025 07:41:58","07-06-2025 07:38:48","07-06-2025 22:36:21=
","(Unstable site) Site went down because PWC overload // Site stabilized",=
"Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down because PWC overload // Site=
 stabilized","edwige.kapawo@matech-cameroun.com","192","07-06-2025 07:41:58=
","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005197425","Ebo=
go","","07-06-2025 07:27:02","07-06-2025 07:20:53","07-06-2025 08:20:13","A=
ctive// No Power issue on site Ubaie 53V site on Grid, TX FME Julien /69309=
5849 from Huawei is informed","Siligap Boris","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power=
 issue on site Ubaie 53V site on Grid, TX FME Julien /693095849 from Huawei=
 is informed","cedric.tiani@matech-cameroun.com","370","07-06-2025 07:27:02=
","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0005197401","Ole=
mbe MTN","","07-06-2025 07:23:06","07-06-2025 07:17:53","07-06-2025 08:15:5=
4","Grid outage, Site went down because Gen ran until fuel shortage// Refue=
ling Done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage, Site went down because Gen ran until fuel shortage// Refue=
ling Done","cedric.tiani@matech-cameroun.com","2639","07-06-2025 07:23:06",=
"MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005197137","ODZ=
A BORNE 10","","07-06-2025 06:16:54","07-06-2025 06:10:47","07-06-2025 06:4=
9:31","Site went down due to PWC dysfunction //He reset it and site on Gen"=
,"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","Site went down due to PWC dysfunction //He reset it and site =
on Gen","loic.noumsi@matech-cameroun.com","368","07-06-2025 06:16:54","MATE=
CH CMR"
"Closed Complete","Site Down","T0920","IHS_YND_416","NOCINC0005197020","Ngw=
opi Boga","","07-06-2025 05:48:50","07-06-2025 05:40:42","07-06-2025 05:50:=
04","No power issue, site is on grid with Ubaie=3D54.5V; TX FME Etienne Fop=
a (693961474) from HUAWEI is informed","Kemeni Franklin","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue, site is on grid with Ubaie=3D54.5V; TX FME Etienne Fopa (69396147=
4) from HUAWEI is informed","loic.noumsi@matech-cameroun.com","488","07-06-=
2025 05:48:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0005196980","Dong",""=
,"07-06-2025 05:26:13","07-06-2025 01:10:59","07-06-2025 01:24:37","Cascade=
d Incident from TTO5346882","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Site impacted by Mbandjock","system","392261"=
,"07-06-2025 05:26:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0005196979","Donga","=
","07-06-2025 05:26:13","07-06-2025 01:10:59","07-06-2025 01:24:37","Cascad=
ed Incident from TTO5346882","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Mbandjock","system","392263=
","07-06-2025 05:26:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0005196977","Nguila",=
"","07-06-2025 05:26:12","07-06-2025 01:10:59","07-06-2025 01:24:37","Casca=
ded Incident from TTO5346882","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Site impacted by Mbandjock","system","39226=
2","07-06-2025 05:26:12","MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0005196887","Dag=
obert","","07-06-2025 04:50:57","07-06-2025 04:40:48","07-06-2025 04:50:25"=
,"Active: No power issue, site is on Grid with Ubaie=3D54,9V, FME TX Mohama=
dou//691144435 from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: No power issue, site is on Grid with Ubaie=3D54,9V, FME TX Moh=
amadou//691144435 from Huawei is informed.","loic.noumsi@matech-cameroun.co=
m","610","07-06-2025 04:50:57","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0005196870","Ema=
na Lycee","","07-06-2025 04:41:32","07-06-2025 04:32:22","07-06-2025 04:35:=
36"," No power issue site on grid with U=3D57v TX FME Symphorien(691316854)=
 from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm"," No power issue sit=
e on grid with U=3D57v TX FME Symphorien(691316854) from Huawei is informed=
","loic.noumsi@matech-cameroun.com","551","07-06-2025 04:41:32","MATECH CMR=
"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005196862","Mba=
nkolo petit paris","","07-06-2025 04:37:42","07-06-2025 04:30:31","07-06-20=
25 04:33:21","No power issue, site is on gen with Ubaie=3D54.4V, Brice Tsag=
ue (650 21 40 96) from Huawei is informed.","Mboua Thierry","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue, site is on gen with Ubaie=3D54.4V, Brice Tsague (650 21 40 96)=
 from Huawei is informed.","loic.noumsi@matech-cameroun.com","431","07-06-2=
025 04:37:42","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005196843","S=
tade-Abega","","07-06-2025 04:32:08","07-06-2025 03:21:59","07-06-2025 04:5=
6:29","No power issue on site and site impacted by Ekounou II that is not m=
anaged by us","Mba Lazare Herve","Customer Equipment Failure","Active","Act=
ive Equipment Failure","Affected by 3rd Party Site","No power issue on site=
 and site impacted by Ekounou II that is not managed by us","gaelle.njiofac=
k@matech-cameroun.com","4210","07-06-2025 04:32:08","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005196827","Ebo=
go","","07-06-2025 04:27:31","07-06-2025 04:20:21","07-06-2025 04:22:54","G=
rid outage,site went down before gen starts due to poor battery backup // G=
rid return","Siligap Boris","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage,site went down before gen starts d=
ue to poor battery backup // Grid return","loic.noumsi@matech-cameroun.com"=
,"431","07-06-2025 04:27:31","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005196557","E=
ssomba","","07-06-2025 03:03:33","07-06-2025 03:00:23","07-06-2025 04:49:28=
","(Unstable site) Site went down because PWC overload // Site stabilised",=
"Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down because PWC overload // Site=
 stabilised","gaelle.njiofack@matech-cameroun.com","191","07-06-2025 03:03:=
33","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005196352","Ebo=
go","","07-06-2025 01:29:18","07-06-2025 01:20:08","07-06-2025 01:40:41","G=
rid outage,site went down before gen starts due to poor battery backup // G=
rid returned","Siligap Boris","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage,site went down before gen starts=
 due to poor battery backup // Grid returned","loic.noumsi@matech-cameroun.=
com","552","07-06-2025 01:29:18","MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0005196330","Mes=
sassi okolo","","07-06-2025 01:22:17","07-06-2025 01:17:06","07-06-2025 09:=
53:49","Site up awaiting feedback","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site down because si=
te behaves as Grid only site (Gen Noise) // Grid return","loic.noumsi@matec=
h-cameroun.com","312","07-06-2025 01:22:17","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0005195868","Sac=
re Coeur Catholic Church","","06-06-2025 23:02:08","06-06-2025 22:45:59","0=
6-06-2025 23:13:30","Grid outage, site went down due to insufficiency of re=
ctifiers // He reseted rectifiers","Mboua Thierry","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","Grid outage, site went down due to ins=
ufficiency of rectifiers // He reseted rectifiers","loic.noumsi@matech-came=
roun.com","970","06-06-2025 23:02:08","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005195685","C=
omplexe-BEAC","","06-06-2025 22:16:38","06-06-2025 22:14:30","06-06-2025 23=
:16:58","No power issue on site ,site on Grid with U=3D54.6 v T Tx FME Lion=
nel// 655184876 from Huawei is informed (disjunction in the OCM bay / rearm=
ed circuit breaker)","Albran Byorel","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site ,si=
te on Grid with U=3D54.6 v T Tx FME Lionnel// 655184876 from Huawei is info=
rmed (disjunction in the OCM bay / rearmed circuit breaker)","vanel.mbiada@=
matech-cameroun.com","129","06-06-2025 22:16:38","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005195286","E=
koumdoum OCM","","06-06-2025 21:14:19","06-06-2025 20:30:07","07-06-2025 00=
:25:14","site went down due to PWC ZTE dysfunction // PWC ZTE put on baypas=
s mode.","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","site went down due to PWC ZTE dysfunction // PWC ZTE =
put on baypass mode.","vanel.mbiada@matech-cameroun.com","2653","06-06-2025=
 21:14:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_743","NOCINC0005194996","Ngousso =
Vallee","","06-06-2025 20:16:02","06-06-2025 20:08:13","06-06-2025 21:18:15=
","Cascaded Incident from TTO5345346","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,Site went down due t=
o rectifiers dysfunctionning //He reset and start the Gen manually","system=
","404076","06-06-2025 20:16:02","MATECH CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0005194981","M=
bedoumou - Ekali","IHS_YND_743, IHS_YND_723, IHS_YND_385, IHS_YND_553, IHS_=
YND_410, IHS_YND_344","06-06-2025 20:13:33","06-06-2025 20:08:13","06-06-20=
25 21:23:49","Grid outage,Site went down due to rectifiers dysfunctionning =
//He reset and start the Gen manually","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Grid outage,Site went down due to =
rectifiers dysfunctionning //He reset and start the Gen manually","vanel.mb=
iada@matech-cameroun.com","321","06-06-2025 20:13:33","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005194899","Eli=
g Edzoa","","06-06-2025 19:52:53","06-06-2025 19:05:39","06-06-2025 19:38:3=
9","Backtracking Grid outage.gen ran until fuel shortage//Refueling done","=
Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge.gen ran until fuel shortage//Refueling done","cedric.tiani@matech-camero=
un.com","2835","06-06-2025 19:52:53","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0005194870","Sac=
re Coeur Catholic Church","","06-06-2025 19:46:21","06-06-2025 19:23:12","0=
6-06-2025 19:30:44","Backtracking Active//No power issue on site. Site on G=
rid with Ubaie 1=3D48 V and Ubaie 2=3D50.7 The TX  FME Brice Tsague (650214=
096) from Huawei is informed.","Mboua Thierry","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power=
 issue on site. Site on Grid with Ubaie 1=3D48 V and Ubaie 2=3D50.7 The TX =
 FME Brice Tsague (650214096) from Huawei is informed.","cedric.tiani@matec=
h-cameroun.com","1390","06-06-2025 19:46:21","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005194760","N=
gouetou","","06-06-2025 19:21:05","06-06-2025 19:20:42","06-06-2025 19:31:1=
1","Active // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gre=
goire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gregoire (6=
54547479) from Huawei is informed","vanel.mbiada@matech-cameroun.com","25",=
"06-06-2025 19:21:05","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005194756","E=
ssomba","","06-06-2025 19:19:48","06-06-2025 19:19:31","07-06-2025 02:25:30=
","(Unstable site) Site went down because PWC overload // Site stabilised",=
"Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","(Unstable site) Site went down because PWC overload // Site=
 stabilised","vanel.mbiada@matech-cameroun.com","18","06-06-2025 19:19:48",=
"MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005194731","Ebo=
go","","06-06-2025 19:12:21","06-06-2025 18:58:04","06-06-2025 19:28:02","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed automatically","Siligap Boris","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Gen started automatically","cedric.tiani@matech-=
cameroun.com","858","06-06-2025 19:12:21","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005194701","Nko=
ulou Carriere carrefourt","","06-06-2025 19:06:58","06-06-2025 18:04:22","0=
6-06-2025 21:28:14","Backtracking","Mba Lazare Herve","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site went down because gen start=
 and stopped with high temp alarm // He added water and manually","cedric.t=
iani@matech-cameroun.com","411402","06-06-2025 19:06:58","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0005194583","Aba=
ng","IHS_YND_794","06-06-2025 18:47:44","06-06-2025 18:04:22","06-06-2025 2=
1:28:14","Backtracking Site went down because gen start and stopped with hi=
gh temp alarm // He added water and manually","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issu=
e","Site went down because gen start and stopped with high temp alarm // He=
 added water and manually","cedric.tiani@matech-cameroun.com","2603","06-06=
-2025 18:47:44","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0005194565","C=
RF Nkoabang","","06-06-2025 18:44:00","06-06-2025 18:16:54","06-06-2025 18:=
46:37","Active// No power issue on site Ubaie=3D53.6V site on Grid, FME TX =
LIONEL STYVE //655184876// from Huawei is informed","Mba Lazare Herve","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active// No power issue on site Ubaie=3D53.6V site on Grid, FME TX =
LIONEL STYVE //655184876// from Huawei is informed","vanel.mbiada@matech-ca=
meroun.com","1628","06-06-2025 18:44:00","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005194518","N=
YOM 2 IHS","","06-06-2025 18:32:44","06-06-2025 18:30:31","06-06-2025 19:37=
:15","Site went down due to controller ZTE faulty//He bypassed it and start=
ed Gen manually","Fabrice Pouakam","Equipment Repair","Passive","Control Pa=
nel","ATS-AMF Issue","Site went down due to controller ZTE faulty//He bypas=
sed it and started Gen manually","vanel.mbiada@matech-cameroun.com","134","=
06-06-2025 18:32:44","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005194506","A=
wae Ewonkan","","06-06-2025 18:30:02","06-06-2025 18:22:54","06-06-2025 18:=
56:24","Grid outage site went down due to Gen Overload (20Kva, Iload 310 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 310 A)IHS SS Alphonse is informed // Grid ret=
urn","vanel.mbiada@matech-cameroun.com","431","06-06-2025 18:30:02","MATECH=
 CMR"
"Closed Complete","Warning","T1071","IHS_YND_343","NOCINC0005194505","Mbedo=
umou - Ekali","","06-06-2025 18:29:56","","","Grid outage,Site went down du=
e to rectifiers dysfunctionning //He reset and start the Gen manually","Alb=
ran Byorel","Warning","Warning","POWER","Warning - Rectifier Module","Grid =
outage,Site went down due to rectifiers dysfunctionning //He reset and star=
t the Gen manually","cedric.tiani@matech-cameroun.com","3","06-06-2025 18:2=
9:56","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005194420","Mok=
olo Yaounde","","06-06-2025 18:11:13","06-06-2025 18:07:05","06-06-2025 18:=
34:12","Site went down due to insufficient of rectifier on site SS IHS Bern=
ard is informed //Site stabilised","","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down due to insufficient of rectifier on =
site SS IHS Bernard is informed //Site stabilised","cedric.tiani@matech-cam=
eroun.com","250","06-06-2025 18:11:13","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005194407","NKO=
MKANA ELIZA HOTEL","","06-06-2025 18:07:02","06-06-2025 18:00:54","06-06-20=
25 19:53:37","Site went down due to insufficient rectifiers on site//Site s=
tabilised","","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down due to insufficient rectifiers on site//Site stabilised","ce=
dric.tiani@matech-cameroun.com","369","06-06-2025 18:07:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0005194399","Nkoabang=
2","","06-06-2025 18:04:49","06-06-2025 17:59:40","06-06-2025 18:30:36","Ca=
scaded Incident from TTO5344663","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because the phase t=
hat feeds Air condition is gone//He made a bridge and started the AC ","sys=
tem","411633","06-06-2025 18:04:49","MATECH CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0005194396","N=
koabang","IHS_YND_526","06-06-2025 18:04:02","06-06-2025 17:59:40","06-06-2=
025 18:30:36","Site went down because the phase that feeds Air condition is=
 gone//He made a bridge and started the AC ","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","Site went down because the phase that feeds Air condition is gone//He ma=
de a bridge and started the AC ","vanel.mbiada@matech-cameroun.com","263","=
06-06-2025 18:04:02","MATECH CMR"
"Closed Complete","Site Down","T0107","IHS_YND_271","NOCINC0005194383","Yon=
a Hotel","","06-06-2025 17:59:51","06-06-2025 17:52:33","06-06-2025 18:05:5=
5","Active: no power issue, site is on grid with Ubaie=3D54.5V, Mohamadou(6=
91144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active: no power issue, site is on grid with Ubaie=3D54.4V, Mohamadou(69114=
4435) from Huawei is informed.","cedric.tiani@matech-cameroun.com","438","0=
6-06-2025 17:59:51","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0005194330","Tsi=
nga village","","06-06-2025 17:45:07","06-06-2025 17:36:52","06-06-2025 18:=
10:31","Active // No power issue UBaie =3D55V site on Grid. The FME TX SYMP=
HORIEN (675295205) From Huawei is informed ans said he is on site","Delor T=
elezing","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active // No power issue UBaie =3D55V site on Grid. Th=
e FME TX SYMPHORIEN (675295205) From Huawei is informed ans said he is on s=
ite","cedric.tiani@matech-cameroun.com","495","06-06-2025 17:45:07","MATECH=
 CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005194288","Eko=
umdoum OCM","","06-06-2025 17:33:19","06-06-2025 17:28:10","06-06-2025 18:5=
3:56","Grid outage,site went down because Gen failed to start due to PWC ZT=
E not configured//He started the Gen manually","Albran Byorel","Equipment R=
epair","Passive","Control Panel","ATS-AMF Issue","Grid outage,site went dow=
n because Gen failed to start due to PWC ZTE not configured//He started the=
 Gen manually","cedric.tiani@matech-cameroun.com","310","06-06-2025 17:33:1=
9","MATECH CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0005194284","Sap=
eur Mimboman","","06-06-2025 17:32:31","06-06-2025 17:26:16","06-06-2025 20=
:43:33","Site went down due c=E2ble which powered MTN equiments has burned =
//we replaced c=E2ble and site on grid","Mba Lazare Herve","Equipment Repai=
r","Passive","Infrastructure","Armoured Cable","Site went down due c=E2ble =
which powered MTN equiments has burned //we replaced c=E2ble and site on gr=
id","cedric.tiani@matech-cameroun.com","375","06-06-2025 17:32:31","MATECH =
CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005194217","A=
ccacia New","","06-06-2025 17:21:18","06-06-2025 17:18:00","06-06-2025 18:2=
1:18","Grid outage ,no space to deploy a mobil gen // grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
,no space to deploy a mobil gen // grid return","vanel.mbiada@matech-camero=
un.com","200","06-06-2025 17:21:18","MATECH CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0005194011","BIY=
EM ASSI LYCEE","","06-06-2025 16:45:04","06-06-2025 16:36:57","06-06-2025 1=
7:13:31","No power issue on site U=3D54.8V site on grid Tx Fme MBAH osiah (=
674007438) of huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site U=3D54.8V site on grid Tx Fme MBAH osiah (674007438) of huawei i=
s informed","cedric.tiani@matech-cameroun.com","488","06-06-2025 16:45:04",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005193979","N=
YOM 2 IHS","","06-06-2025 16:40:09","06-06-2025 16:39:54","06-06-2025 17:35=
:19","Grid outage, Site went down because Gen failed to start due to PWC dy=
sfunctionning// He reset PWC and manually started Gen","Fabrice Pouakam","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage, Site went down because Gen failed to start due to PWC dysfunctionni=
ng// He reset PWC and manually started Gen","vanel.mbiada@matech-cameroun.c=
om","16","06-06-2025 16:40:09","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005193963","M=
imboman-Ecole","","06-06-2025 16:37:35","06-06-2025 16:34:23","06-06-2025 1=
7:11:14","Site went down due to insufficient rectifiers on site//Site stabi=
lised","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to insufficient rectifiers on site//Site sta=
bilised","vanel.mbiada@matech-cameroun.com","193","06-06-2025 16:37:35","MA=
TECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005193891","Ako=
k Ndoe Yde","","06-06-2025 16:25:22","06-06-2025 16:16:59","06-06-2025 16:4=
0:47","Active//No power issue site,site on GEN with Ubaie U=3D53,5v.","Hyem=
afo Gildas","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue site,site on GEN with Ubaie =
U=3D53,5v.","cedric.tiani@matech-cameroun.com","504","06-06-2025 16:25:22",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005193865","M=
essassi 2","","06-06-2025 16:22:39","06-06-2025 16:19:25","06-06-2025 18:58=
:23","SYLVAIN kamdem / BTR / 682398693 working on site (swapp of PWC)","Fab=
rice Pouakam","Installation Activity","Passive","Planned Activity","Install=
ation Activity","SYLVAIN kamdem / BTR / 682398693 working on site (swapp of=
 PWC) // End of work","vanel.mbiada@matech-cameroun.com","196","06-06-2025 =
16:22:39","MATECH CMR"
"Closed Complete","Site Down","T0531","IHS_YND_309","NOCINC0005193795","Leb=
oudi","","06-06-2025 16:09:54","06-06-2025 16:00:36","06-06-2025 16:15:40",=
"Active // no power issue, site is on Grid with Ubaie=3D54.3V, Mohamadou(69=
1144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive // no power issue, site is on Grid with Ubaie=3D54.3V, Mohamadou(6911=
44435) from Huawei is informed.","cedric.tiani@matech-cameroun.com","559","=
06-06-2025 16:09:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0005193785","SAA 2","=
","06-06-2025 16:07:46","06-06-2025 15:52:59","06-06-2025 19:31:12","Cascad=
ed Incident from TTO5343963","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Base connector in MPR Burnt // Base conne=
ctor replaced","system","419073","06-06-2025 16:07:46","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005193781","Feb=
e Village","","06-06-2025 16:07:28","06-06-2025 15:58:59","06-06-2025 16:10=
:32","ACTIVE//no power issue, site is on GEN 54.3V  THE fme tx Mohamadou (6=
91144135) from Huawei is informed","Mboua Thierry","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no p=
ower issue, site is on GEN 54.3V  THE fme tx Mohamadou (691144135) from Hua=
wei is informed","cedric.tiani@matech-cameroun.com","510","06-06-2025 16:07=
:28","MATECH CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0005193766","BEA=
TITUDE ENTR=C9E PAVE","","06-06-2025 16:03:36","06-06-2025 15:36:20","06-06=
-2025 15:50:47","no power issue on site U=3D54.6 V site on Grid. The fme Tx=
 Mohamadou of Huawei/691144435 from Huawei is informed","TIENTCHEU NZETCHIE=
U GAEL","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","no power issue on site U=3D54.6 V site on Grid. The fme=
 Tx Mohamadou of Huawei/691144435 from Huawei is informed","cedric.tiani@ma=
tech-cameroun.com","1637","06-06-2025 16:03:36","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005193754","Saa=
","IHS_YND_726, IHS_YND_401, IHS_YND_404","06-06-2025 16:02:05","06-06-2025=
 15:52:59","06-06-2025 19:41:50","","Parker Tchoup","Fire on Site","Passive=
","Infrastructure","Fire - Burned","Base connector in MPR Burnt // Base con=
nector replaced","cedric.tiani@matech-cameroun.com","547","06-06-2025 16:02=
:05","MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0005193746","Dag=
obert","","06-06-2025 15:59:06","06-06-2025 15:41:52","06-06-2025 15:59:25"=
,"Active: No power issue, site is on Grid with Ubaie=3D54,9V, mohamadou//69=
1144435 from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue, site is on Grid with Ubaie=3D54,9V, mohamadou//691144=
435 from Huawei is informed.","cedric.tiani@matech-cameroun.com","1035","06=
-06-2025 15:59:06","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0005193706","Mfo=
u EPC","","06-06-2025 15:50:09","06-06-2025 13:29:40","06-06-2025 18:04:50"=
,"Backtracking The RM Martial (650252214) from Huawei is informed. ludovic =
kotap (694569589/ TELIS) is on site for mw installation // End of work","Mb=
a Lazare Herve","Installation Activity","Passive","Planned Activity","Insta=
llation Activity","Backtracking The RM Martial (650252214) from Huawei is i=
nformed. ludovic kotap (694569589/ TELIS) is on site for mw installation //=
 End of work","cedric.tiani@matech-cameroun.com","8430","06-06-2025 15:50:0=
9","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005193653","E=
toug ebe Meweulo","","06-06-2025 15:38:55","06-06-2025 15:37:38","06-06-202=
5 15:57:24","Active: No power issue, site on grid with Ubaie=3D53V, Hosiah(=
674007438) from Huawei is informed","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No=
 power issue, site on grid with Ubaie=3D53V, Hosiah(674007438) from Huawei =
is informed","vanel.mbiada@matech-cameroun.com","77","06-06-2025 15:38:55",=
"MATECH CMR"
"Closed Complete","Site Down","T2292","IHS_YND_453","NOCINC0005193425","Son=
g-bong","","06-06-2025 15:17:25","06-06-2025 14:48:55","06-06-2025 16:19:37=
","Backtracking Site went down because Gen failed to start due to FUSE GEN =
CARD  faulty//He made a bridge and manuallty started the  GEN","Kemeni Fran=
klin","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Site =
went down because Gen failed to start due to FUSE GEN CARD  faulty//He made=
 a bridge and manuallty started the  GEN","cedric.tiani@matech-cameroun.com=
","1711","06-06-2025 15:17:25","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005193298","Nsa=
m Sofavinc","","06-06-2025 14:48:58","06-06-2025 13:32:34","06-06-2025 13:5=
0:31","Bactracking  No power issue on site Ubaie =3D53.8V site on Grid The =
TX FME LIONEL TCHATCHOU /694 692 436 from huawei is informed","MINKA NICOLA=
S","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue on site Ubaie =3D53.8V site on Grid The TX FM=
E LIONEL TCHATCHOU /694 692 436 from huawei is informed","cedric.tiani@mate=
ch-cameroun.com","4585","06-06-2025 14:48:58","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005193274","Nko=
ulou Carriere carrefourt","","06-06-2025 14:43:32","06-06-2025 14:34:59","0=
6-06-2025 15:05:30","Grid outage, site went down because gen fails to start=
 due to PWC dysfunctionning, //site stabilised","Mba Lazare Herve","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage=
, site went down because gen fails to start due to PWC dysfunctionning, //s=
ite stabilised","cedric.tiani@matech-cameroun.com","514","06-06-2025 14:43:=
32","MATECH CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0005193245","Ngo=
uetou","","06-06-2025 14:39:33","06-06-2025 14:30:24","06-06-2025 14:55:20"=
,"Active // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Grego=
ire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gregoire (654=
547479) from Huawei is informed","cedric.tiani@matech-cameroun.com","550","=
06-06-2025 14:39:33","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005193223","Nko=
ulou Carriere carrefourt","","06-06-2025 14:34:51","06-06-2025 11:31:39","0=
6-06-2025 14:28:15","Bactracking 	Grid outage, site went down because gen f=
ails to start due to PWC dysfunctionning,  //He reset it and site on Grid",=
"Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","Grid outage, site went down because gen fails to start due =
to PWC dysfunctionning,  //He reset it and site on Grid","cedric.tiani@mate=
ch-cameroun.com","10993","06-06-2025 14:34:51","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005193218","A=
wae Ewonkan","","06-06-2025 14:32:08","06-06-2025 14:28:55","06-06-2025 14:=
32:34","Grid outage site went down due to Gen Overload (20Kva, Iload 310 A)=
IHS SS Alphonse is informed // Grid returned","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 310 A)IHS SS Alphonse is informed // Grid r=
eturned","vanel.mbiada@matech-cameroun.com","195","06-06-2025 14:32:08","MA=
TECH CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0005193205","MBI=
MBIM","","06-06-2025 14:29:50","06-06-2025 14:20:37","06-06-2025 14:21:14",=
"Wrongly created ticket","Parker Tchoup","Incorrectly Logged Tickets","Erro=
r","Error","Error","Wrongly created ticket","cedric.tiani@matech-cameroun.c=
om","554","06-06-2025 14:29:50","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005193171","A=
kak-Nkozoa-MTN-IHS","","06-06-2025 14:26:18","06-06-2025 14:18:53","06-06-2=
025 16:47:24","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // He added water and manually start the gen","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - =
Coolant Level Issue","Grid outage, site went down because gen start and sto=
pped with high temp alarm // He added water and manually start the gen","ge=
rard.tchangoue@matech-cameroun.com","447","06-06-2025 14:26:18","MATECH CMR=
"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005193116","Ebo=
go","","06-06-2025 14:13:16","06-06-2025 14:05:08","06-06-2025 15:49:37","G=
rid outage.gen ran until fuel shortage//Refueling done","Siligap Boris","Fu=
el Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until fu=
el shortage//Refueling done","gerard.tchangoue@matech-cameroun.com","489","=
06-06-2025 14:13:16","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005193023","Man=
guiers Dispensaire","","06-06-2025 14:01:39","06-06-2025 13:52:25","06-06-2=
025 14:55:02","Grid outage, Site went down before Gen start due to poor bac=
kup// Gen  manually  Started","Fabrice Pouakam","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup// Gen  manually  Started","gerard.tch=
angoue@matech-cameroun.com","555","06-06-2025 14:01:39","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005193021","M=
essassi 2","","06-06-2025 14:01:30","06-06-2025 13:56:19","06-06-2025 15:05=
:57","Site went Down due to insufficient rectifiers // Site Stabilized","Fa=
brice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went Down due to insufficient rectifiers // Site Stabilized","edwige.=
kapawo@matech-cameroun.com","313","06-06-2025 14:01:30","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005193010","Eki=
e sud","","06-06-2025 13:59:45","06-06-2025 13:58:36","06-06-2025 14:37:01"=
,"site went down due to PWC ZTE dysfunction // site on Gen (site stabilized=
 and he is in observation)","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","site went down due to PWC ZTE dysf=
unction // site on Gen (site stabilized and he is in observation)","gerard.=
tchangoue@matech-cameroun.com","69","06-06-2025 13:59:45","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005192935","E=
ssomba","","06-06-2025 13:51:37","06-06-2025 13:47:30","06-06-2025 17:20:52=
","(Unstable site)fme report that Site went down because PWC overload","Mba=
 Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Site went down because PWC overload // Site stabilised","edwige=
.kapawo@matech-cameroun.com","249","06-06-2025 13:51:37","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005192927","HOP=
ITAL DE LA CAISSE","","06-06-2025 13:49:26","06-06-2025 13:42:18","06-06-20=
25 14:16:59","Grid outage, Site went down before Gen start due to poor back=
up // Gen started automatically","Delor Telezing","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen started automatically","gera=
rd.tchangoue@matech-cameroun.com","429","06-06-2025 13:49:26","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005192755","Nsa=
m Sofavinc","IHS_YND_732","06-06-2025 13:08:01","06-06-2025 12:58:43","06-0=
6-2025 13:28:46","Site went Down due to disjunction of rectifier circuit br=
eaker  // He rearmed CB, Site on Grid","MINKA NICOLAS","Equipment Repair","=
Passive","Rectifier","Rectifier - Circuit Breaker","Site went Down due to d=
isjunction of rectifier circuit breaker  // He rearmed CB, Site on Grid","g=
erard.tchangoue@matech-cameroun.com","559","06-06-2025 13:08:01","MATECH CM=
R"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0005192727","Nsa=
m escale LP","","06-06-2025 13:02:24","06-06-2025 12:58:43","06-06-2025 13:=
28:46","Site impacted by Nsam Sofavinc","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went Down due to disjunction of rectif=
ier circuit breaker  // He rearmed CB, Site on Grid","gerard.tchangoue@mate=
ch-cameroun.com","429301","06-06-2025 13:02:24","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005192647","Eko=
umdoum OCM","","06-06-2025 12:44:31","06-06-2025 12:35:21","06-06-2025 13:5=
9:19","Grid outage,site went down because Gen failed to start due to PWC ZT=
E not configured//Grid return","Albran Byorel","Equipment Repair","Passive"=
,"Control Panel","ATS-AMF Issue","Grid outage,site went down because Gen fa=
iled to start due to PWC not configured//Grid return","gerard.tchangoue@mat=
ech-cameroun.com","551","06-06-2025 12:44:31","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005192618","Beh=
ind P T school Yde","","06-06-2025 12:37:13","06-06-2025 12:28:59","06-06-2=
025 13:16:14","Site went down due to MPR DYSFONNCTION on site  // He reset =
the MPR","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier =
Cabinet","Site went down due to MPR DYSFONNCTION on site  // He reset the M=
PR","gerard.tchangoue@matech-cameroun.com","495","06-06-2025 12:37:13","MAT=
ECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005192509","Awa=
e Ewonkan","","06-06-2025 12:15:44","06-06-2025 12:08:36","06-06-2025 12:55=
:48","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IH=
S SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid retur=
n","gerard.tchangoue@matech-cameroun.com","429","06-06-2025 12:15:44","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005192502","E=
lig Edzoa","","06-06-2025 12:14:51","06-06-2025 12:07:42","06-06-2025 13:20=
:56","Grid outage, site down because generator did not start due to flood a=
fter the rain. // he started the generator with a can of fuel.","Delor Tele=
zing","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Wat=
er In The Fuel","Grid outage, site down because generator did not start due=
 to flood after the rain. // he started the generator with a can of fuel.",=
"edwige.kapawo@matech-cameroun.com","430","06-06-2025 12:14:51","MATECH CMR=
"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005192469","Par=
adis Hotel","","06-06-2025 12:06:41","06-06-2025 11:58:31","06-06-2025 12:1=
3:39","Site went down due to Insufficient rectifiers on site // He added 01=
 rectifier and site stabilised","Siligap Boris","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down due to Insufficient rectif=
iers on site // He added 01 rectifier and site stabilised","gerard.tchangou=
e@matech-cameroun.com","490","06-06-2025 12:06:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005192421","MEHANDAN=
","","06-06-2025 12:01:06","06-06-2025 11:59:06","06-06-2025 12:07:28","Cas=
caded Incident from TTO5342415","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Gri stabilized","system","4=
32793","06-06-2025 12:01:06","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005192415","O=
dza II OCM","IHS_YND_528","06-06-2025 12:00:22","06-06-2025 11:59:06","06-0=
6-2025 12:07:28","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Gri stabilized","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down because gen failed to start due to PWC ZTE malfunction // Gri st=
abilized","edwige.kapawo@matech-cameroun.com","79","06-06-2025 12:00:22","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0005192355","H=
-General-Yde","","06-06-2025 11:48:02","06-06-2025 11:46:59","06-06-2025 12=
:04:38","Site went down due to plan work (swap of PWC) done by Epitech (692=
288751) // End of work","Siligap Boris","Installation Activity","Passive","=
Planned Activity","Installation Activity","Site went down due to plan work =
(swap of PWC) done by Epitech (692288751) // End of work","edwige.kapawo@ma=
tech-cameroun.com","64","06-06-2025 11:48:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_023","NOCINC0005192346","Montesqu=
ieux","","06-06-2025 11:46:00","06-06-2025 11:40:59","06-06-2025 11:57:24",=
"Cascaded Incident from TTO5342314","Paul BIBOUM","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active // No power issue, Ubaie:53. 4V =
Site on Grid The TX FME Armand (691144412) from Huawei is informed","system=
","433857","06-06-2025 11:46:00","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005192323","M=
vog-Ada_OCM","IHS_YND_023","06-06-2025 11:41:58","06-06-2025 11:40:59","06-=
06-2025 11:57:24","Active // No power issue, Ubaie:53. 4V Site on Grid The =
TX FME Armand (691144412) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue, Ubaie:53. 4V Site on Grid The TX FME Armand (691144412) fr=
om Huawei is informed","edwige.kapawo@matech-cameroun.com","59","06-06-2025=
 11:41:58","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005192243","O=
lembe-Terminus","","06-06-2025 11:25:08","06-06-2025 11:22:58","06-06-2025 =
15:16:25","Site went down due to Swap of PWC and GE done by M YOVO (SFM/ 69=
8529863) // End of work","Fabrice Pouakam","Installation Activity","Passive=
","Planned Activity","Installation Activity","Site went down due to Swap of=
 PWC and GE done by M YOVO (SFM/ 698529863) // End of work","edwige.kapawo@=
matech-cameroun.com","131","06-06-2025 11:25:08","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005192115","HOP=
ITAL DE LA CAISSE","","06-06-2025 11:01:17","06-06-2025 10:52:06","06-06-20=
25 11:23:09","Grid outage, Site went down before Gen start due to poor back=
up // Gen started automatically","Delor Telezing","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen started automatically","gera=
rd.tchangoue@matech-cameroun.com","552","06-06-2025 11:01:17","MATECH CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0005192023","Car=
refour Ayissi Ele","","06-06-2025 10:41:22","06-06-2025 10:32:11","06-06-20=
25 11:28:11","Solar site only // Solar returned","Parker Tchoup","Equipment=
 Repair","Passive","Solar","Solar Panel Issue","Solar site only // Solar re=
turned","gerard.tchangoue@matech-cameroun.com","552","06-06-2025 10:41:22",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005191999","S=
aa","","06-06-2025 10:38:01","06-06-2025 10:32:54","06-06-2025 11:04:45","S=
ite went Down because fme Parker is on site for work he replaces the charge=
 alternator and static battery charger // End of works","Parker Tchoup","Eq=
uipment Replacement","Passive","Planned Activity","Planned Activity - Passi=
ve","Site went Down because fme Parker is on site for work he replaces the =
charge alternator and static battery charger // End of works","edwige.kapaw=
o@matech-cameroun.com","309","06-06-2025 10:38:01","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005191973","Nko=
ulou Carriere carrefourt","","06-06-2025 10:32:02","06-06-2025 10:27:52","0=
6-06-2025 10:50:27","Grid outage, site went down because gen fails to start=
 due to PWC dysfunctionning, //site stabilised","Mba Lazare Herve","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage=
, site went down because gen fails to start due to PWC dysfunctionning, //s=
ite stabilised","gerard.tchangoue@matech-cameroun.com","251","06-06-2025 10=
:32:02","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0005191900","M=
fou EPC","","06-06-2025 10:21:13","06-06-2025 10:16:02","06-06-2025 13:28:2=
5","Active//No power issue on site, Site on Grid UBAIE=3D54.5V The RM Marti=
al (650252214) from Huawei is informed. ludovic kotap (694569589/ TELIS) is=
 on site for  mw installation","Mba Lazare Herve","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No po=
wer issue on site, Site on Grid UBAIE=3D54.5V The RM Martial (650252214) fr=
om Huawei is informed. ludovic kotap (694569589/ TELIS) is on site for  mw =
installation","edwige.kapawo@matech-cameroun.com","312","06-06-2025 10:21:1=
3","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005191894","Mok=
olo Yaounde","","06-06-2025 10:19:52","06-06-2025 10:10:40","06-06-2025 12:=
22:41","Site went down due to insufficient of rectifier on site SS IHS Bern=
ard is informed // Site stabilised","","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to insufficient of rectifier on=
 site SS IHS Bernard is informed // Site stabilised","gerard.tchangoue@mate=
ch-cameroun.com","553","06-06-2025 10:19:52","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005191808","C=
rf-Nsam","","06-06-2025 10:02:43","06-06-2025 10:01:59","06-06-2025 10:13:2=
1","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","edwige.kapawo@matech-cameroun.com","45","=
06-06-2025 10:02:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0005191667","Nkoa Ayo=
s","","06-06-2025 09:36:40","06-06-2025 09:30:23","06-06-2025 10:44:59","Ca=
scaded Incident from TTO5341553","MINKA NICOLAS","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage,gen ran till fuel shortag=
e//Refueling done","system","441529","06-06-2025 09:36:40","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0005191657","G=
SO","IHS_YND_067","06-06-2025 09:35:36","06-06-2025 09:29:59","06-06-2025 1=
0:44:59","Grid outage,gen ran till fuel shortage//Refueling done","MINKA NI=
COLAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ra=
n till fuel shortage//Refueling done","edwige.kapawo@matech-cameroun.com","=
552","06-06-2025 09:35:36","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005191363","E=
lig Edzoa","","06-06-2025 08:24:57","06-06-2025 08:14:59","06-06-2025 09:49=
:10","Grid outage, site down because generator did not start due to flood a=
fter the rain. // he started the generator with a can of fuel.","Delor Tele=
zing","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Wat=
er In The Fuel","Grid outage, site down because generator did not start due=
 to flood after the rain. // he started the generator with a can of fuel.",=
"edwige.kapawo@matech-cameroun.com","599","06-06-2025 08:24:57","MATECH CMR=
"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005191290","M=
essassi 2","","06-06-2025 08:06:29","06-06-2025 08:01:18","06-06-2025 10:40=
:03","Site went Down due to  insufficient rectifiers // Site Stabilized","F=
abrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went Down due to  insufficient rectifiers // Site Stabilized","edwig=
e.kapawo@matech-cameroun.com","314","06-06-2025 08:06:29","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005191283","Odz=
a petit marche new","","06-06-2025 08:06:03","06-06-2025 08:01:51","06-06-2=
025 08:33:54","Grid outage, site went down due Grid bad voltage (lack of 01=
 phase) // He did bridge on the good phases, site on Grid","Albran Byorel",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid outage, site went down due Grid bad voltage (lack of 01 phase) // He di=
d bridge on the good phases, site on Grid","gerard.tchangoue@matech-camerou=
n.com","252","06-06-2025 08:06:03","MATECH CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0005191064","BIY=
EM ASSI LYCEE","","06-06-2025 07:03:26","06-06-2025 06:54:16","06-06-2025 0=
9:16:04","No power issue on site U=3D54.9V site on grid Tx Fme MBAH osiah (=
674007438) of huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site U=3D54.9V site on grid Tx Fme MBAH osiah (674007438) of huawei i=
s informed","loic.noumsi@matech-cameroun.com","550","06-06-2025 07:03:26","=
MATECH CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0005190870","A=
FEME NORD","","06-06-2025 06:09:25","06-06-2025 06:06:13","06-06-2025 08:29=
:14","Grid outage, site went down because gen start and stopped with high t=
emp alarm // He added water and manual start of gen","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, site went down because gen start and stoppe=
d with high temp alarm // He added water and manual start of gen","franck.n=
komot@matech-cameroun.com","193","06-06-2025 06:09:25","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005190823","Mes=
sassi 2","","06-06-2025 06:02:07","06-06-2025 05:45:59","06-06-2025 05:46:4=
2","Grid fluctuations, site went down because Gen failed to start due to po=
or Battery backup// Grid Stabilized","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid fluctuations, =
site went down because Gen failed to start due to poor Battery backup// Gri=
d Stabilized","ludivine.ngamaleu@ihstowers.com","969","06-06-2025 06:02:07"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005190804","E=
bogo","","06-06-2025 05:56:50","06-06-2025 05:52:00","06-06-2025 05:55:49",=
"Grid outage, site went down before Gen start due poor backup battery // Ge=
n automatically started","Siligap Boris","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e Gen start due poor backup battery // Gen automatically started","gaelle.n=
jiofack@matech-cameroun.com","292","06-06-2025 05:56:50","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005190732","E=
ssomba","","06-06-2025 05:34:21","06-06-2025 05:32:13","06-06-2025 07:08:34=
","Site went down because PWC overload // Site stabilised","Mba Lazare Herv=
e","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Site went down because PWC overload // Site stabilised","gaelle.njiofack@ma=
tech-cameroun.com","130","06-06-2025 05:34:21","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005190517","N=
gousso-Savana","IHS_YND_561","06-06-2025 03:15:48","06-06-2025 03:14:41","0=
6-06-2025 05:17:35","No power issue, site is on grid with Ubaie=3D53.4V, Sy=
mphorien(650257151) from Huawei is informed","Siligap Boris","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue, site is on grid with Ubaie=3D53.4V, Symphorien(650257151) fro=
m Huawei is informed","gaelle.njiofack@matech-cameroun.com","68","06-06-202=
5 03:15:48","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005190516","F=
OUGEROLE","","06-06-2025 03:15:00","06-06-2025 03:14:41","06-06-2025 05:17:=
35","","Siligap Boris","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue, site is on grid with Ubaie=3D53.4V, Symphorien(650=
257151) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","463=
751","06-06-2025 03:15:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0005190472","Messassi=
 2","","06-06-2025 02:47:48","06-06-2025 02:39:40","06-06-2025 03:08:04","s=
ite  down due to 4/6 rectifiers had planted // Rectifiers reset. site is on=
 Grid.","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","site  down due to 4/6 rectifiers had planted // Rectifiers rese=
t. site is on Grid.","gaelle.njiofack@matech-cameroun.com","490","06-06-202=
5 02:47:48","MATECH CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0005190450","O=
yomabang OCM","","06-06-2025 02:38:23","06-06-2025 02:35:13","06-06-2025 03=
:34:29","Grid low voltage, site down because gen fails to start due to unde=
rvoltage alarm // Grid bypass, site is on gen ","TIENTCHEU NZETCHIEU GAEL",=
"Grid Supply","Passive","Grid","National Grid - Low Current Supply","Grid l=
ow voltage, site down because gen fails to start due to undervoltage alarm =
// Grid bypass, site is on gen ","vanel.mbiada@matech-cameroun.com","191","=
06-06-2025 02:38:23","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005190365","Mes=
sassi 2","","06-06-2025 01:57:17","06-06-2025 01:36:00","06-06-2025 01:38:0=
0","No power issue Ubaie:54.26V site on Grid, TX fme symphorien /650257151 =
from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ubai=
e:54.26V site on Grid, TX fme symphorien /650257151 from huawei is informed=
.","ludivine.ngamaleu@ihstowers.com","1278","06-06-2025 01:57:17","MATECH C=
MR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005190363","Ebo=
go","","06-06-2025 01:56:11","06-06-2025 01:32:53","06-06-2025 01:37:53","B=
ACKTRACKING: Grid outage, site went down before Gen start due poor backup b=
attery // Gen automatically started","Siligap Boris","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","BACKTRACKING: Grid ou=
tage, site went down before Gen start due poor backup battery // Gen automa=
tically started","franck.nkomot@matech-cameroun.com","1399","06-06-2025 01:=
56:11","MATECH CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0005190005","BIY=
EM ASSI LYCEE","","06-06-2025 00:53:47","06-06-2025 00:22:35","06-06-2025 0=
0:25:35","BACKTRACKING: No power issue on site U=3D54.9V site on grid Tx Fm=
e MBAH osiah (674007438) of huawei is informed","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"BACKTRACKING: No power issue on site U=3D54.9V site on grid Tx Fme MBAH o=
siah (674007438) of huawei is informed","franck.nkomot@matech-cameroun.com"=
,"1873","06-06-2025 00:53:47","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005189999","Eki=
e sud","","06-06-2025 00:51:49","06-06-2025 00:08:42","06-06-2025 02:26:30"=
,"BACKTRACKING. Site down due to bad grid voltage // site put on gen","Albr=
an Byorel","Grid Supply","Passive","Grid","National Grid - Low Current Supp=
ly","BACKTRACKING. Site down due to bad grid voltage // site put on gen","f=
ranck.nkomot@matech-cameroun.com","2588","06-06-2025 00:51:49","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005189697","E=
lig Edzoa","","05-06-2025 23:22:27","05-06-2025 23:21:11","06-06-2025 00:51=
:50","Grid outage, site down because generator did not start due to flood a=
fter the rain. // he started the generator with a can of fuel.","Delor Tele=
zing","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Wat=
er In The Fuel","Grid outage, site down because generator did not start due=
 to flood after the rain. // he started the generator with a can of fuel.",=
"gaelle.njiofack@matech-cameroun.com","77","05-06-2025 23:22:27","MATECH CM=
R"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0005189612","HOP=
ITAL GENERAL RAIL YDE","","05-06-2025 23:08:32","05-06-2025 22:21:13","06-0=
6-2025 10:56:39","Grid outage, site went down because gen stopped with unde=
r voltage alarm // Reset done and gen started","Delor Telezing","Equipment =
Repair","Passive","ACDG Gen","ACDG - Under Voltage","Grid outage, site went=
 down because gen stopped with under voltage alarm // Reset done and gen st=
arted","ludivine.ngamaleu@ihstowers.com","2839","05-06-2025 23:08:32","MATE=
CH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005189553","Man=
guiers Dispensaire","","05-06-2025 22:52:02","05-06-2025 22:45:49","05-06-2=
025 23:19:49","Grid outage, site went down due to insufficiency of rectifie=
rs // he reset 01 rectifier an put site on GEN","Fabrice Pouakam","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module","Grid outage, site went =
down due to insufficiency of rectifiers // he reset 01 rectifier an put sit=
e on GEN","franck.nkomot@matech-cameroun.com","374","05-06-2025 22:52:02","=
MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005189511","A=
kak-Nkozoa-MTN-IHS","","05-06-2025 22:42:34","05-06-2025 22:25:56","05-06-2=
025 23:26:44","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage,Site down because gen ran till fuel sho=
rtage // site refueled ","gaelle.njiofack@matech-cameroun.com","474724","05=
-06-2025 22:42:34","MATECH CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0005189503","S=
oa-II","IHS_YND_316","05-06-2025 22:41:05","05-06-2025 22:25:56","05-06-202=
5 23:26:44","Grid outage,Site down because gen ran till fuel shortage // si=
te refueled ","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage,Site down because gen ran till fuel shortage // site refue=
led ","gaelle.njiofack@matech-cameroun.com","909","05-06-2025 22:41:05","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_190","NOCINC0005189493","Ngousso-=
II","","05-06-2025 22:38:25","05-06-2025 22:26:31","05-06-2025 23:31:47","C=
ascaded Incident from TTO5339093","MFOUAGUEGUE MATHIEU","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause gen start and stopped due to high temp alarm // water added  and gen =
 manually started","system","474686","05-06-2025 22:38:25","MATECH CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0005189489","N=
kolmesseng","IHS_YND_190","05-06-2025 22:37:38","05-06-2025 22:26:31","05-0=
6-2025 23:31:47","Grid outage, site went down because gen start and stopped=
 due to high temp alarm // water added  and gen  manually started","Siligap=
 Boris","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - =
Coolant Level Issue","Grid outage, site went down because gen start and sto=
pped due to high temp alarm // water added  and gen  manually started","gae=
lle.njiofack@matech-cameroun.com","668","05-06-2025 22:37:38","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005189486","A=
wae Ewonkan","","05-06-2025 22:37:00","05-06-2025 22:35:53","05-06-2025 23:=
43:53","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed// Grid returned","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due=
 to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed// Grid ret=
urned","gaelle.njiofack@matech-cameroun.com","68","05-06-2025 22:37:00","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005189368","M=
essassi 2","","05-06-2025 22:14:59","05-06-2025 22:13:53","05-06-2025 23:01=
:38","No power issue Ubaie:53.28V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:53.28V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","gaelle.njiofack@matech-cameroun.com","69","05-06-2025 22:14:59","MATE=
CH CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0005189367","BIY=
EM ASSI LYCEE","","05-06-2025 22:14:53","05-06-2025 21:18:33","05-06-2025 2=
1:26:26","No power issue on site U=3D54.9V site on grid Tx Fme MBAH osiah (=
674007438) of huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site U=3D54.9V site on grid Tx Fme MBAH osiah (674007438) of huawei i=
s informed","loic.noumsi@matech-cameroun.com","3381","05-06-2025 22:14:53",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0005189260","M=
asque","IHS_YND_192","05-06-2025 21:57:45","05-06-2025 17:59:31","05-06-202=
5 18:03:25","Backtracking// No power issue on site. Site on Grid with Ubaie=
=3D54.3V The TX FME Eloundou // 693212405// From Huawei is informed.","Fabr=
ice Pouakam","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Backtracking// No power issue on site. Site on Gri=
d with Ubaie=3D54.3V The TX FME Eloundou // 693212405// From Huawei is info=
rmed.","gaelle.njiofack@matech-cameroun.com","14296","05-06-2025 21:57:45",=
"MATECH CMR"
"Closed Complete","Site Down","T2564","IHS_YND_739","NOCINC0005189037","NKO=
LMESSING rue Manguier","","05-06-2025 21:20:39","05-06-2025 19:50:09","05-0=
6-2025 22:10:09","Grid outage, Site went down because Gen failed to start d=
ue to battery Gen Faulty// He started Gen with external battery","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","G=
rid outage, Site went down because Gen failed to start due to battery Gen F=
aulty// He started Gen with external battery","loic.noumsi@matech-cameroun.=
com","5430","05-06-2025 21:20:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005188848","Mvog-Eba=
nda","","05-06-2025 20:55:05","05-06-2025 20:39:54","05-06-2025 20:54:58","=
Cascaded Incident from TTO5338314","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
Alarm Overload (16KVA /300A) // Grid return","system","480916","05-06-2025 =
20:55:05","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005188800","A=
bom","IHS_YND_269","05-06-2025 20:48:03","05-06-2025 20:39:54","05-06-2025 =
21:44:58","Grid outage, Site went down due to Alarm Overload (16KVA /300A) =
// Grid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down due to Alarm Overload (16KVA /3=
00A) // Grid return","gaelle.njiofack@matech-cameroun.com","491","05-06-202=
5 20:48:03","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0005188650","G=
SO","","05-06-2025 20:16:19","05-06-2025 20:10:08","05-06-2025 21:31:08","G=
rid outage,site went down because Gen started and stopped with alarm ""Over=
voltage""//Grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid outage,site went down because Gen started=
 and stopped with alarm ""Overvoltage""//Grid return","gaelle.njiofack@mate=
ch-cameroun.com","372","05-06-2025 20:16:19","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0005188624","Tsi=
nga village","","05-06-2025 20:11:48","05-06-2025 19:00:31","05-06-2025 20:=
20:50","Site went down due to poor backup battery // Site stabilised","Delo=
r Telezing","Equipment Repair","Passive","Control Panel","Power Cabinet - B=
attery Low","Site went down due to poor backup battery // Site stabilised",=
"loic.noumsi@matech-cameroun.com","4277","05-06-2025 20:11:48","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005188601","Ngo=
usso Vallee","","05-06-2025 20:09:39","05-06-2025 19:02:20","05-06-2025 19:=
16:03","Backtracking//Active // No power issue UBaie =3D54,2V site on Grid.=
 The FME TX SYMPHORIEN (675295205) From Huawei is informed","Siligap Boris"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Backtracking//Active // No power issue UBaie =3D54,2V site on =
Grid. The FME TX SYMPHORIEN (675295205) From Huawei is informed","loic.noum=
si@matech-cameroun.com","4040","05-06-2025 20:09:39","MATECH CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0005188545","N=
kolmesseng","IHS_YND_190","05-06-2025 20:03:55","05-06-2025 19:54:59","05-0=
6-2025 21:21:14","Grid outage, Site went down due Disfunctionement of Hybri=
d systhem // Gen start manually (and put on Grid-Gen)","Siligap Boris","Equ=
ipment Repair","Passive","Hybrid","Hybrid Module","Grid outage, Site went d=
own due Disfunctionement of Hybrid systhem // Gen start manually (and put o=
n Grid-Gen)","gaelle.njiofack@matech-cameroun.com","537","05-06-2025 20:03:=
55","MATECH CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0005188540","N=
gousso-II","","05-06-2025 20:03:18","05-06-2025 19:54:59","05-06-2025 21:21=
:14","","MFOUAGUEGUE MATHIEU","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, Site went down due Disfunctionement of Hybr=
id systhem // Gen start manually (and put on Grid-Gen)","gaelle.njiofack@ma=
tech-cameroun.com","483549","05-06-2025 20:03:18","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0005188538","Sim=
e Building","","05-06-2025 20:02:57","05-06-2025 17:51:09","06-06-2025 08:3=
4:42","Grid outage, site went down because gen failed to start due to grid =
contactor faulty // He bypassed ATS and Gen manually started","Mboua Thierr=
y","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid ou=
tage, site went down because gen failed to start due to grid contactor faul=
ty // He bypassed ATS and Gen manually started","loic.noumsi@matech-camerou=
n.com","7908","05-06-2025 20:02:57","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0005188281","K=
oweit City","","05-06-2025 19:15:15","05-06-2025 19:05:59","05-06-2025 20:2=
1:50","Site went down due to disjunction of Rectifiers CB because on refcti=
fier passed faulty // CB rearm ","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Cabinet","Site went down due to disjunction of Re=
ctifiers CB because on refctifier passed faulty // CB rearm ","gaelle.njiof=
ack@matech-cameroun.com","557","05-06-2025 19:15:15","MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0005188263","K=
amajou Building","","05-06-2025 19:10:14","05-06-2025 15:48:59","05-06-2025=
 16:01:00","Site went down due to a lack of rectifier // Site stabilized","=
Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier Module","S=
ite went down due to a lack of rectifier // Site stabilized","gaelle.njiofa=
ck@matech-cameroun.com","12076","05-06-2025 19:10:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005188153","Mvog-Eba=
nda","","05-06-2025 18:52:39","05-06-2025 17:59:13","05-06-2025 19:13:26","=
Cascaded Incident from TTO5337409","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","	Grid outage, site went down due to=
 alarm Overcurent // Gen card reset and gen start manually","system","49036=
1","05-06-2025 18:52:39","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005188103","S=
tade-Abega","","05-06-2025 18:44:27","05-06-2025 18:42:59","05-06-2025 19:0=
3:57","	No power issue on site and site impacted by Ekounou II that is not =
managed by us","Mba Lazare Herve","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","Affected by 3rd Party Site","	No power issue on si=
te and site impacted by Ekounou II that is not managed by us","gaelle.njiof=
ack@matech-cameroun.com","190","05-06-2025 18:44:27","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005188096","N=
yom OCM","","05-06-2025 18:41:06","05-06-2025 18:19:46","05-06-2025 19:02:5=
8","Grid fluctuation, site down because gen fails to start due to grid fluc=
tuation // Gen manually started","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site do=
wn because gen fails to start due to grid fluctuation // Gen manually start=
ed","gaelle.njiofack@matech-cameroun.com","1282","05-06-2025 18:41:06","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0005188066","E=
lig-Essono","","05-06-2025 18:34:19","05-06-2025 18:16:47","06-06-2025 01:2=
5:50","Active: No power issue, site is on grid with Ubaie=3D54V, The TX FME=
 Brice / 654419973 From hawei is informed.","Paul BIBOUM","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue, site is on grid with Ubaie=3D54V, The TX FME Brice / 654=
419973 From hawei is informed.","gaelle.njiofack@matech-cameroun.com","1053=
","05-06-2025 18:34:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005188053","Nkolfoul=
ou 2","","05-06-2025 18:32:05","05-06-2025 18:24:29","05-06-2025 19:06:07",=
"Cascaded Incident from TTO5337416","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to gen =
overload 300 A /20 KVA // Gen charge reduced and manual start of gen.","sys=
tem","488847","05-06-2025 18:32:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005188054","Melen Ba=
'aba","","05-06-2025 18:32:05","05-06-2025 18:24:29","05-06-2025 19:06:07",=
"Cascaded Incident from TTO5337416","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to gen =
overload 300 A /20 KVA // Gen charge reduced and manual start of gen.","sys=
tem","488846","05-06-2025 18:32:05","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0005188052","Ema=
na Lycee","","05-06-2025 18:31:47","05-06-2025 18:13:36","05-06-2025 20:20:=
45","Backtracking// No power issue site on grid with U=3D54v TX FME Symphor=
ien(691316854) from Huawei is informed","Fabrice Pouakam","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Backt=
racking// No power issue site on grid with U=3D54v Symphorien(691316854) fr=
om Huawei is informed","loic.noumsi@matech-cameroun.com","1092","05-06-2025=
 18:31:47","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005188030","N=
kolfoulou","IHS_YND_278, IHS_YND_308","05-06-2025 18:26:36","05-06-2025 18:=
24:29","05-06-2025 19:06:07","Grid outage, site down due to gen overload 30=
0 A /20 KVA // Gen charge reduced and manual start of gen.","Siligap Boris"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, si=
te down due to gen overload 300 A /20 KVA // Gen charge reduced and manual =
start of gen.","gaelle.njiofack@matech-cameroun.com","129","05-06-2025 18:2=
6:36","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005188025","A=
bom","IHS_YND_269","05-06-2025 18:24:21","05-06-2025 17:59:13","05-06-2025 =
19:13:48","Grid outage, site went down due to alarm Overcurent // Gen card =
reset and gen start manually","Siligap Boris","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Over Voltage","	Grid outage, site went down due to alarm=
 Overcurent // Gen card reset and gen start manually","gaelle.njiofack@mate=
ch-cameroun.com","1509","05-06-2025 18:24:21","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005188015","M=
vog-Ada_OCM","","05-06-2025 18:23:03","05-06-2025 18:06:46","05-06-2025 19:=
24:17","Grid Only site, No space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only sit=
e, No space to deploy MDGE // Grid returned","gaelle.njiofack@matech-camero=
un.com","978","05-06-2025 18:23:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0005187844","Nkoa Ayo=
s","","05-06-2025 17:54:07","05-06-2025 17:32:02","05-06-2025 19:17:33","Ca=
scaded Incident from TTO5337202","MINKA NICOLAS","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down due to al=
arm ''fail to start'' on Gen // He reseted card and started Gen manually","=
system","491939","05-06-2025 17:54:07","MATECH CMR"
"Cancelled","Warning","","IHS_YND_704","NOCINC0005187834","Bastos Bir","","=
05-06-2025 17:52:26","","","Cascaded Incident from TTO5337195","Mboua Thier=
ry","","","","","","system","268","05-06-2025 17:52:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0005187835","ARMP",""=
,"05-06-2025 17:52:26","05-06-2025 17:47:58","05-06-2025 18:03:25","Cascade=
d Incident from TTO5337195 ","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Backtracking// No power issue o=
n site. Site on Grid with Ubaie=3D54.3V The TX FME Eloundou // 693212405// =
From Huawei is informed","system","268","05-06-2025 17:52:26","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0005187830","D=
ragage","","05-06-2025 17:51:12","05-06-2025 17:59:31","05-06-2025 18:03:25=
","Delor is managing ETA : ASAP","Mboua Thierry","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Backtracking// No power issue on site. S=
ite on Grid with Ubaie=3D54.3V The TX FME Eloundou // 693212405// From Huaw=
ei is informed.","gaelle.njiofack@matech-cameroun.com","490648","05-06-2025=
 17:51:12","MATECH CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0005187792","B=
ondjock","","05-06-2025 17:43:04","05-06-2025 17:15:47","06-06-2025 01:25:2=
5","No power issue on site U=3D54.9V site on grid Tx Fme Etienne FOPA (6513=
20188) of huawei is informed","Fanda Brice","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D54.9V site on grid Tx Fme Etienne FOPA (651320188) of huawei is inf=
ormed","loic.noumsi@matech-cameroun.com","1638","05-06-2025 17:43:04","MATE=
CH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005187782","GSO=
","IHS_YND_067","05-06-2025 17:41:11","05-06-2025 17:32:02","05-06-2025 19:=
50:17","Grid outage, site went down due to alarm ''fail to start'' on Gen /=
/ He reseted card and started Gen manually","MINKA NICOLAS","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went dow=
n due to alarm ''fail to start'' on Gen // He reseted card and started Gen =
manually","loic.noumsi@matech-cameroun.com","549","05-06-2025 17:41:11","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005187761","T=
SINGA VILLAGE 2","","05-06-2025 17:38:26","05-06-2025 17:32:14","05-06-2025=
 19:12:21","site went down due to disjunction of Gen CB // CB rearm ","Delo=
r Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Main Breaker Tr=
ipped","site went down due to disjunction of Gen CB // CB rearm ","gaelle.n=
jiofack@matech-cameroun.com","373","05-06-2025 17:38:26","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005187640","E=
lig-Edzoa","","05-06-2025 17:22:53","05-06-2025 17:19:40","07-06-2025 20:01=
:30","Grid only site,No mobile gen  available // grid restored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site,=
No mobile gen  available // grid restored","gaelle.njiofack@matech-cameroun=
.com","194","05-06-2025 17:22:53","MATECH CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0005187636","E=
leveur","","05-06-2025 17:22:10","05-06-2025 17:19:58","05-06-2025 18:03:45=
","Grid outage, site went down due to Gen Overload (20KVA ; 300A) // Site S=
tabilized.","Siligap Boris","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site Ubay: 53V si=
te on Grid THE TX FME SYMPHORIEN (650257151) from HUAWEI is informed","gael=
le.njiofack@matech-cameroun.com","133","05-06-2025 17:22:10","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0005187320","Bar=
riere IHS","","05-06-2025 16:33:21","05-06-2025 16:25:15","05-06-2025 16:53=
:39","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS F=
ELIX ZAMBE is informed//Grid returned","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to =
Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed//Grid returned","l=
oic.noumsi@matech-cameroun.com","488","05-06-2025 16:33:21","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0005187243","AFE=
ME NORD","","05-06-2025 16:23:25","05-06-2025 16:16:16","05-06-2025 18:35:5=
9","Active; no power issue site on Grid with U=3D54,1 V;The fme TX Mohammad=
ou 691144435 of huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active; no power issue site on Grid with U=3D54,1 V;The fme TX Mohammadou 6=
91144435 of huawei is informed","loic.noumsi@matech-cameroun.com","430","05=
-06-2025 16:23:25","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005187236","Nko=
lbong","","05-06-2025 16:21:52","05-06-2025 16:13:37","05-06-2025 19:17:23"=
,"Site went Down because Gen started and stopped due to Gen overload(22kva/=
/350A) // Grid returned","Delor Telezing","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Site went Down because Gen started and stopped du=
e to Gen overload(22kva//350A) // Grid returned","loic.noumsi@matech-camero=
un.com","496","05-06-2025 16:21:52","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005187213","MEF=
OU ASSI","","05-06-2025 16:18:08","05-06-2025 16:05:48","05-06-2025 16:40:3=
3","Grid outage, Site went down before Gen start due to poor backup // Grid=
 returned","Fanda Brice","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, Site went down before Gen start due =
to poor backup // Grid returned","loic.noumsi@matech-cameroun.com","742","0=
5-06-2025 16:18:08","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005187154","Mok=
olo Yaounde","","05-06-2025 16:07:14","05-06-2025 15:58:49","05-06-2025 18:=
35:38","Site went down due to insufficient of rectifier on site SS IHS Bern=
ard is informed // Site stabilised","","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to insufficient of rectifier on=
 site SS IHS Bernard is informed // Site stabilised","loic.noumsi@matech-ca=
meroun.com","506","05-06-2025 16:07:14","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005187049","C=
rf-Nsam","","05-06-2025 15:50:14","05-06-2025 15:42:49","05-06-2025 16:42:0=
0","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","446=
","05-06-2025 15:50:14","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005186869","M=
vog-Ebanda","","05-06-2025 15:25:47","05-06-2025 14:37:15","05-06-2025 15:4=
5:34","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, site went down due to alarm Overcurent // Gen ca=
rd reset and gen start manually","gaelle.njiofack@matech-cameroun.com","122=
1060","05-06-2025 15:25:47","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005186803","Awa=
e Ewonkan","","05-06-2025 15:11:58","05-06-2025 15:05:49","05-06-2025 17:25=
:59","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IH=
S SS Alphonse is informed// Grid returned","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed// Grid retur=
ned","loic.noumsi@matech-cameroun.com","371","05-06-2025 15:11:58","MATECH =
CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005186713","M=
essassi 2","","05-06-2025 14:56:29","05-06-2025 14:47:23","05-06-2025 17:02=
:50","site went down due to two rectifiers had planted // Rectifiers reset.=
","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Cab=
inet","site went down due to two rectifiers had planted // Rectifiers reset=
.","franck.nkomot@matech-cameroun.com","549","05-06-2025 14:56:29","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005186669","Messassi=
 okolo","","05-06-2025 14:46:28","05-06-2025 14:28:23","05-06-2025 16:20:11=
","Cascaded Incident from TTO5335874","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (Gen Noise) // Grid returned","system","502=
688","05-06-2025 14:46:28","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005186662","E=
MANA BILICK CITY","IHS_YND_279","05-06-2025 14:45:30","05-06-2025 14:28:23"=
,"05-06-2025 16:20:23","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid returned","Fabrice Pouakam","Access Denial",=
"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid=
 outage, site down because site behaves as Grid only site (Gen Noise) // Gr=
id returned","franck.nkomot@matech-cameroun.com","1029","05-06-2025 14:45:3=
0","MATECH CMR"
"Closed Complete","Site Down","T1107-1","IHS_YND_217","NOCINC0005186634","A=
bom","IHS_YND_269","05-06-2025 14:41:22","05-06-2025 14:37:15","05-06-2025 =
15:45:34","Grid outage, site went down due to alarm Overcurent // Gen card =
reset and gen start manually","Siligap Boris","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Over Voltage","Grid outage, site went down due to alarm =
Overcurent // Gen card reset and gen start manually","franck.nkomot@matech-=
cameroun.com","248","05-06-2025 14:41:22","MATECH CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0005186477","S=
apeur","","05-06-2025 14:20:28","05-06-2025 14:16:19","05-06-2025 14:17:19"=
,"No power issue on site U=3D53.5V site on grid Tx Fme BRICE (650214096) of=
 huawei is informed","Mboua Thierry","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53.5V site on grid Tx Fme BRICE (650214096) of huawei is informed","vane=
l.mbiada@matech-cameroun.com","251","05-06-2025 14:20:28","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0005186333","N=
kolo II New","","05-06-2025 14:05:50","05-06-2025 14:04:26","05-06-2025 14:=
12:10","Active/ No power issue site on Gen with U=3D54.4V The FME Tx Lionel=
 Steve /655184876/ From huawei is informed.","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active/ No power issue site on Gen with U=3D54.4V The FME Tx Lionel Steve =
/655184876/ From huawei is informed.","vanel.mbiada@matech-cameroun.com","8=
5","05-06-2025 14:05:50","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005186111","O=
dza II OCM","IHS_YND_528","05-06-2025 13:31:34","05-06-2025 13:28:57","05-0=
6-2025 13:36:43","Grid Outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid Outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","vanel.mbiada@matech-cameroun.com","159","05-06-2025 13:31:34",=
"MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005186109","Aha=
la Echangeur","","05-06-2025 13:30:11","05-06-2025 13:04:57","05-06-2025 13=
:34:42","Backtracking Site went down due to insufficient rectifiers on site=
	//Site stabilised","MINKA NICOLAS","Equipment Repair","Passive","Rectifier=
","Rectifier Module"," Site went down due to insufficient rectifiers on sit=
e	//Site stabilised","cedric.tiani@matech-cameroun.com","1515","05-06-2025 =
13:30:11","MATECH CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0005185969","O=
dza II","","05-06-2025 13:01:32","05-06-2025 12:59:42","05-06-2025 15:36:30=
","Grid outage, site went down due to Grid fluctuations and no rcp on site =
// He bypassed Grid and started Gen manually","Albran Byorel","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid outage, s=
ite went down due to Grid fluctuations and no rcp on site // He bypassed Gr=
id and started Gen manually","vanel.mbiada@matech-cameroun.com","112","05-0=
6-2025 13:01:32","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0005185827","K=
oweit City","","05-06-2025 12:37:51","05-06-2025 12:36:38","05-06-2025 14:1=
2:51","Grid outage, Site went down because Gen started and stopped with ""l=
ow oil pressure"" alarm// He reset card GE and gen manually started","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, Site went down because Gen started and stopped with ""low oil p=
ressure"" alarm// He reset card GE and gen manually started","vanel.mbiada@=
matech-cameroun.com","74","05-06-2025 12:37:51","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005185823","B=
arriere IHS","","05-06-2025 12:37:07","05-06-2025 12:36:54","05-06-2025 13:=
09:50","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed//Grid returned","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due t=
o Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed//Grid returned",=
"vanel.mbiada@matech-cameroun.com","15","05-06-2025 12:37:07","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005185721","Mes=
sassi 2","","05-06-2025 12:12:06","05-06-2025 12:07:54","05-06-2025 12:11:1=
0","Grid outage site went down because Gen failed to start due to poor Batt=
ery backup// Grid return","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage site went down bec=
ause Gen failed to start due to poor Battery backup// Grid return","cedric.=
tiani@matech-cameroun.com","254","05-06-2025 12:12:06","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0005185510","ETO=
UDI Entree du palais","","05-06-2025 11:39:00","05-06-2025 11:25:47","05-06=
-2025 12:28:21","Grid outage.gen ran until fuel shortage//Refueling done","=
Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age.gen ran until fuel shortage//Refueling done","cedric.tiani@matech-camer=
oun.com","794","05-06-2025 11:39:00","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005185435","A=
wae Ewonkan","","05-06-2025 11:27:00","05-06-2025 11:26:22","05-06-2025 12:=
49:01","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed// Grid returned","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due=
 to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed// Grid ret=
urned","vanel.mbiada@matech-cameroun.com","40","05-06-2025 11:27:00","MATEC=
H CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005185425","Nko=
ulou Carriere carrefourt","","05-06-2025 11:24:09","05-06-2025 11:17:10","0=
5-06-2025 18:52:10","Eneo meter burning, Gen failed to start due to Alarm O=
vercurent // battery level reduced and site on Gen","Mba Lazare Herve","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Eneo meter burn=
ing, Gen failed to start due to Alarm Overcurent // battery level reduced a=
nd site on Gen","cedric.tiani@matech-cameroun.com","420","05-06-2025 11:24:=
09","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005185353","Aha=
la Echangeur","","05-06-2025 11:13:32","05-06-2025 11:08:09","05-06-2025 11=
:20:19","site down due to insufficiency of rectifiers //site stabilised","M=
INKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module","=
site down due to insufficiency of rectifiers //site stabilised","cedric.tia=
ni@matech-cameroun.com","324","05-06-2025 11:13:32","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005185239","N=
koabang Ebolmedjock","","05-06-2025 10:51:33","05-06-2025 10:50:10","05-06-=
2025 13:26:11","Grid outage,Site went down because Gen failed to start due =
to Gen batterry discharged//He started with an external battery","Mba Lazar=
e Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery"=
,"Grid outage,Site went down because Gen failed to start due to Gen batterr=
y discharged//He started with an external battery","vanel.mbiada@matech-cam=
eroun.com","84","05-06-2025 10:51:33","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005185208","Nko=
abang Alembe","","05-06-2025 10:43:34","05-06-2025 10:36:23","05-06-2025 11=
:10:11","Site down due to insufficiency of rectifiers IHS SS Alphonse is in=
formed//Site stabilised","Mba Lazare Herve","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site down due to insufficiency of rectifiers =
IHS SS Alphonse is informed//Site stabilised","cedric.tiani@matech-cameroun=
.com","432","05-06-2025 10:43:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0005185116","Nkoa Ayo=
s","","05-06-2025 10:27:27","05-06-2025 10:22:05","05-06-2025 12:23:43","Ca=
scaded Incident from TTO5334074","MINKA NICOLAS","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage..gen failed to start due =
to water infiltration un the tank//We purged and gen manually started ","sy=
stem","511155","05-06-2025 10:27:27","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0005185096","G=
SO","IHS_YND_067","05-06-2025 10:24:13","05-06-2025 10:22:05","05-06-2025 1=
2:46:18","Grid outage..gen failed to start due to water infiltration un the=
 tank//We purged and gen manually started ","MINKA NICOLAS","Fuel Outage (P=
robable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","Grid=
 outage..gen failed to start due to water infiltration un the tank//We purg=
ed and gen manually started ","vanel.mbiada@matech-cameroun.com","129","05-=
06-2025 10:24:13","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005184998","Mok=
olo Yaounde","","05-06-2025 10:13:07","05-06-2025 10:04:59","05-06-2025 10:=
31:33","Site went down due to insufficient of rectifier on site SS IHS Bern=
ard is informed//He reset it and site on Grid","","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to insufficient of r=
ectifier on site SS IHS Bernard is informed//He reset it and site on Grid",=
"cedric.tiani@matech-cameroun.com","489","05-06-2025 10:13:07","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005184751","C=
rf-Nsam","","05-06-2025 09:46:15","05-06-2025 09:44:58","05-06-2025 09:49:5=
2","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","vanel.mbiada@matech-cameroun.com","79","0=
5-06-2025 09:46:15","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005184493","Nko=
ulou Carriere carrefourt","","05-06-2025 09:08:52","05-06-2025 09:01:43","0=
5-06-2025 09:57:05","Grid outage,Site went down because Gen started and sto=
pped with alarm *Low oil pressure*//He added oil and manually started Gen",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil =
Pressure","Grid outage,Site went down because Gen started and stopped with =
alarm *Low oil pressure*//He added oil and manually started Gen","cedric.ti=
ani@matech-cameroun.com","430","05-06-2025 09:08:52","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005184339","Aha=
la Echangeur","","05-06-2025 08:42:36","05-06-2025 08:33:59","05-06-2025 08=
:59:07"," Site went down due to insufficient rectifiers on site//Site stabi=
lised","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down due to insufficient rectifiers on site//Site stabil=
ised","cedric.tiani@matech-cameroun.com","518","05-06-2025 08:42:36","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005184319","A=
wae Ewonkan","","05-06-2025 08:38:18","05-06-2025 08:36:38","05-06-2025 10:=
51:14","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed// Grid return","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due t=
o Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed// Grid retur=
n","vanel.mbiada@matech-cameroun.com","102","05-06-2025 08:38:18","MATECH C=
MR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005184286","M=
essassi 2","","05-06-2025 08:30:19","05-06-2025 08:27:44","05-06-2025 09:22=
:04","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automatically","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup // Gen started automatically","vanel.mbiad=
a@matech-cameroun.com","157","05-06-2025 08:30:19","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005184023","O=
dza II OCM","","05-06-2025 07:46:45","05-06-2025 07:44:25","05-06-2025 07:5=
3:19","Grid Outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Site stabilised","Albran Byorel","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Grid Outage, site went down=
 because gen failed to start due to PWC ZTE malfunction // Site stabilised"=
,"vanel.mbiada@matech-cameroun.com","143","05-06-2025 07:46:45","MATECH CMR=
"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005183990","A=
wae Ewonkan","","05-06-2025 07:40:05","05-06-2025 07:38:48","05-06-2025 07:=
49:26","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed","Albran Byorel","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage site went down due to Gen Overload=
 (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid return","vanel.mbi=
ada@matech-cameroun.com","78","05-06-2025 07:40:05","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005183988","B=
arriere","","05-06-2025 07:39:17","05-06-2025 07:37:58","05-06-2025 09:04:2=
4","site went down because gen start an stopped due to water infiltration i=
n tank // He purged The tank and Gen manually started","Hyemafo Gildas","Fu=
el Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The=
 Fuel","site went down because gen start an stopped due to water infiltrati=
on in tank // He purged The tank and Gen manually started","vanel.mbiada@ma=
tech-cameroun.com","80","05-06-2025 07:39:17","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005183829","Nko=
ulou Carriere carrefourt","","05-06-2025 07:00:44","05-06-2025 06:34:28","0=
5-06-2025 08:45:24","Bactracking  Grid fluctuation Site went down because G=
en failed to start due to Grid bad voltage,no rcp on site // He bypass the =
Grid Site on Gen","Mba Lazare Herve","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","Grid fluctuation Site went down because=
 Gen failed to start due to Grid bad voltage,no rcp on site // He bypass th=
e Grid Site on Gen","cedric.tiani@matech-cameroun.com","1577","05-06-2025 0=
7:00:44","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005183591","Mba=
nkolo petit paris","","05-06-2025 06:00:07","03-06-2025 14:29:35","03-06-20=
25 14:58:35","BACKTRACKING: No power issue, site is on gen with Ubaie=3D54.=
4V, Brice Tsague (650 21 40 96) from Huawei is informed.","Mboua Thierry","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","BACKTRACKING: No power issue, site is on gen with Ubaie=3D54.4V,=
 Brice Tsague (650 21 40 96) from Huawei is informed.","franck.nkomot@matec=
h-cameroun.com","142233","05-06-2025 06:00:07","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005183584","Lad=
a I Yde","","05-06-2025 05:58:45","03-06-2025 16:27:09","03-06-2025 16:43:4=
2","BACKTRACKING: Grid fluctuation site went down because Gen and started a=
nd stopped due to Grid bad voltage // He bypass the Grid and Gen manually s=
tarted","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","BACKTRACKING: Grid fluctuation site went down bec=
ause Gen and started and stopped due to Grid bad voltage // He bypass the G=
rid and Gen manually started","franck.nkomot@matech-cameroun.com","135096",=
"05-06-2025 05:58:45","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0005183570","Aba=
ng","","05-06-2025 05:55:34","03-06-2025 15:13:50","03-06-2025 15:46:50","B=
ACKTRACKING: Grid fluctuation Site went down because Gen failed to start du=
e to Grid bad voltage // He bypass the Grid Site on Gen","Mba Lazare Herve"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
BACKTRACKING: Grid fluctuation Site went down because Gen failed to start d=
ue to Grid bad voltage // He bypass the Grid Site on Gen","franck.nkomot@ma=
tech-cameroun.com","139305","05-06-2025 05:55:34","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005183565","Eto=
udi","","05-06-2025 05:53:47","03-06-2025 14:42:06","03-06-2025 15:14:42","=
BACKTRACKING: Grid fluctuation ,site went down because Gen fails to start d=
ue to grid bad voltage //Grid stabilisation","Fabrice Pouakam","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","BACKTRACKIMG: Grid =
fluctuation ,site went down because Gen fails to start due to grid bad volt=
age //Grid stabilisation","franck.nkomot@matech-cameroun.com","141101","05-=
06-2025 05:53:47","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005183534","Car=
refour Simbock","","05-06-2025 05:45:51","03-06-2025 21:08:23","03-06-2025 =
21:50:23","BACKTRACKING: Grid fluctuations, site went down because Gen fail=
 to start due to Grid bad voltage and no rcp on site // He bypassed the Gri=
d and started manually a Gen","Hyemafo Gildas","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","BACKTRACKING: Grid fluctuatio=
ns, site went down because Gen fail to start due to Grid bad voltage and no=
 rcp on site // He bypassed the Grid and started manually a Gen","franck.nk=
omot@matech-cameroun.com","117449","05-06-2025 05:45:51","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005183518","Nsa=
m Sofavinc","","05-06-2025 05:39:08","03-06-2025 16:57:03","03-06-2025 17:3=
5:03","Site went down due to insufficiency of rectifiers on site // He redu=
ced load","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to insufficiency of rectifiers on site // He=
 reduced load","franck.nkomot@matech-cameroun.com","132126","05-06-2025 05:=
39:08","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005183507","Mok=
olo Yaounde","","05-06-2025 05:35:35","03-06-2025 16:52:20","03-06-2025 17:=
23:20","BACKTRACKING: Active // No power issue Ubay: 54.4 V site on grid. T=
he Tx FME Eloundou Bertrand (693212405) from Huawei is informed","","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","BACKTRACKING: Active // No power issue Ubay: 54.4 V site on grid. The =
Tx FME Eloundou Bertrand (693212405) from Huawei is informed","franck.nkomo=
t@matech-cameroun.com","132196","05-06-2025 05:35:35","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0005183346","Nko=
lbisson usines des eaux 2","","05-06-2025 04:35:59","05-06-2025 03:31:30","=
05-06-2025 07:27:52","BACKTRACKING: Access issues during the night due to l=
andlord.Grid outage,site went down because Gen started and stopped with ala=
rm*Overurrent*//He reduiced the load and site on Grid","TIENTCHEU NZETCHIEU=
 GAEL","Access Denial","Lease Or Legal","Landlord Related Issues","Access I=
ssue - Land Lord","Grid outage,site went down because Gen started and stopp=
ed with alarm*Overurrent*//He reduiced the load and site on Grid","franck.n=
komot@matech-cameroun.com","3871","05-06-2025 04:35:59","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005183223","Aha=
la Echangeur","","05-06-2025 03:48:25","02-06-2025 08:20:02","04-06-2025 08=
:52:00","BACKTRACKING: Site went down due to insufficient rectifiers on sit=
e//Site stabilised","MINKA NICOLAS","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down due to insufficient rectifiers on site=
//Site stabilised","franck.nkomot@matech-cameroun.com","242903","05-06-2025=
 03:48:25","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005183211","ODZ=
A BORNE 10","","05-06-2025 03:41:58","02-06-2025 10:02:07","02-06-2025 11:3=
5:00","BACKTRACKING: Site went down due to PWC dysfunction //He reset it an=
d site on Gen","Albran Byorel","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","BACKTRACKING: Site went down due to PWC dysfunction //He r=
eset it and site on Gen","franck.nkomot@matech-cameroun.com","236392","05-0=
6-2025 03:41:58","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005183196","Ebo=
go","","05-06-2025 03:35:49","02-06-2025 13:09:00","02-06-2025 13:19:00","B=
ACKTRACKING: Grid outage, site went down before Gen start due poor backup b=
attery // Gen automatically started","Siligap Boris","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Fans Faulty","BACKTRACKING: Grid ou=
tage, site went down before Gen start due poor backup battery // Gen automa=
tically started","franck.nkomot@matech-cameroun.com","224809","05-06-2025 0=
3:35:49","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005183172","Mok=
olo Yaounde","","05-06-2025 03:29:02","02-06-2025 09:52:08","02-06-2025 10:=
24:44","BACKTRACKING: Active // No power issue Ubay: 54.4 V site on grid. T=
he Tx FME Eloundou Bertrand (693212405) from Huawei is informed","","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active // No power issue Ubay: 54.4 V site on grid. The Tx FME Eloundo=
u Bertrand (693212405) from Huawei is informed","franck.nkomot@matech-camer=
oun.com","236214","05-06-2025 03:29:02","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005183125","M=
essassi okolo","","05-06-2025 03:11:30","05-06-2025 03:05:17","05-06-2025 0=
3:20:05","BACKTRACKING. Grid outage , site went down before Gen started due=
 to poor battery backup // Grid return","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","BACKTRACKING. Gr=
id outage , site went down before Gen started due to poor battery backup //=
 Grid return","franck.nkomot@matech-cameroun.com","375","05-06-2025 03:11:3=
0","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0005183059","Mballa 4=
","","05-06-2025 02:48:47","05-06-2025 02:14:00","05-06-2025 03:11:00","Cas=
caded Incident from TTO5331722","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","BACKTRACKING. Grid outage, Site went =
down because the ENEO circuit breaker burned out// He bypassed the grid","s=
ystem","539941","05-06-2025 02:48:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0005183058","Ekombiti=
e","","05-06-2025 02:48:47","05-06-2025 02:14:00","05-06-2025 03:11:00","Ca=
scaded Incident from TTO5331722","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","BACKTRACKING. Grid outage, Site wen=
t down because the ENEO circuit breaker burned out// He bypassed the grid",=
"system","539942","05-06-2025 02:48:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_275","NOCINC0005183057","Nkolbong=
","","05-06-2025 02:48:46","05-06-2025 02:14:00","05-06-2025 03:11:00","Cas=
caded Incident from TTO5331722","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","BACKTRACKING. Grid outage, Site went =
down because the ENEO circuit breaker burned out// He bypassed the grid","s=
ystem","539940","05-06-2025 02:48:46","MATECH CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0005183044","San=
ta Barbara Yde","IHS_YND_275, IHS_YND_276, IHS_YND_242","05-06-2025 02:42:1=
1","05-06-2025 02:14:00","05-06-2025 03:11:00","BACKTRACKING. Grid outage, =
Site went down because the ENEO circuit breaker burned out// He bypassed th=
e grid","Delor Telezing","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Circuit Breaker Issue","BACKTRACKING. Grid outage, Site went do=
wn because the ENEO circuit breaker burned out// He bypassed the grid","fra=
nck.nkomot@matech-cameroun.com","1692","05-06-2025 02:42:11","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005182972","M=
ontee-Des-Soeurs","","05-06-2025 02:13:05","05-06-2025 02:03:00","05-06-202=
5 03:29:00","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) //=
 Grid returned","franck.nkomot@matech-cameroun.com","607","05-06-2025 02:13=
:05","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005182773","S=
imbock OCM","","05-06-2025 01:00:46","04-06-2025 20:22:38","05-06-2025 03:2=
5:05","Backtracking: Access issue during the night and grid fluctuations //=
 Site stabilised","Hyemafo Gildas","Access Denial","Lease Or Legal","Landlo=
rd Related Issues","Access Issue - Land Lord","Backtracking: Access issue d=
uring the night and grid fluctuations // Site stabilised","franck.nkomot@ma=
tech-cameroun.com","16689","05-06-2025 01:00:46","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005182694","Mes=
sassi 2","","05-06-2025 00:38:00","05-06-2025 00:28:54","05-06-2025 00:29:5=
4","No power issue Ubaie:54.3V site on Grid, TX fme symphorien /650257151 f=
rom huawei is informed.","Fabrice Pouakam","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ubaie=
:54.3V site on Grid, TX fme symphorien /650257151 from huawei is informed."=
,"franck.nkomot@matech-cameroun.com","548","05-06-2025 00:38:00","MATECH CM=
R"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005182654","Nko=
g-Edzen","","05-06-2025 00:24:00","04-06-2025 23:43:33","04-06-2025 23:45:3=
3","BACKTRACKING: Active//No power issue on site, Site on Grid Ubay =3D 56.=
4V The Tx Fme Gregoire (654547479) from Huawei is informed","Parker Tchoup"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","BACKTRACKING: Active//No power issue on site, Site on Grid Uba=
y =3D 56.4V The Tx Fme Gregoire (654547479) from Huawei is informed","franc=
k.nkomot@matech-cameroun.com","2428","05-06-2025 00:24:00","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005182653","M=
essassi 2","","05-06-2025 00:23:45","05-06-2025 00:20:38","05-06-2025 00:25=
:57","No power issue Ubaie:54.3V site on Grid, TX fme symphorien /650257151=
 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Uba=
ie:54.3V site on Grid, TX fme symphorien /650257151 from huawei is informed=
.","franck.nkomot@matech-cameroun.com","189","05-06-2025 00:23:45","MATECH =
CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005182649","Nko=
abang Alembe","","05-06-2025 00:22:50","04-06-2025 23:56:33","05-06-2025 07=
:31:12","BACKTRACKING//site down due to insufficiency of rectifiers IHS SS =
Alphonse is informed//Site stabilised","Mba Lazare Herve","Equipment Repair=
","Passive","Rectifier","Rectifier Module","site down due to insufficiency =
of rectifiers IHS SS Alphonse is informed//Site stabilised","franck.nkomot@=
matech-cameroun.com","1578","05-06-2025 00:22:50","MATECH CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0005182636","Y=
ona Hotel","","05-06-2025 00:18:48","05-06-2025 00:12:40","05-06-2025 02:14=
:40","Bactraking : Access issue during the Night,Grid low voltage ,gen sfai=
ls to start due to grid low voltage // Grid restoration","TIENTCHEU NZETCHI=
EU GAEL","Grid Supply","Passive","Grid","National Grid - Low Current Supply=
","Bactraking : Access issue during the Night,Grid low voltage ,gen sfails =
to start due to grid low voltage // Grid restoration","franck.nkomot@matech=
-cameroun.com","368","05-06-2025 00:18:48","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005182530","TSI=
NGA VILLAGE 2","","04-06-2025 23:50:23","04-06-2025 22:17:07","04-06-2025 2=
2:18:58","Backrating : Power issue has been resolved since 04-06-2025 22:15=
:52 No power issue on site, Site on Battery UBAIE=3D55.7V synphorien (67529=
5205) From huawei is informed","Delor Telezing","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Backrating : Po=
wer issue has been resolved since 04-06-2025 22:15:52 No power issue on sit=
e, Site on Battery UBAIE=3D55.7V synphorien (675295205) From huawei is info=
rmed","franck.nkomot@matech-cameroun.com","5597","04-06-2025 23:50:23","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005182316","C=
omplexe-BEAC","","04-06-2025 23:01:19","04-06-2025 22:25:08","05-06-2025 00=
:10:16","No power issue on site ,site on Grid with U=3D54.6 v T Tx FME Lion=
nel// 655184876 from Huawei is informed","Albran Byorel","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site ,site on Grid with U=3D54.6 v T Tx FME Lionnel// 655184876=
 from Huawei is informed","franck.nkomot@matech-cameroun.com","2172","04-06=
-2025 23:01:19","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005182128","TSI=
NGA VILLAGE 2","","04-06-2025 22:19:12","04-06-2025 21:35:15","04-06-2025 2=
2:15:52","Backtracking//Grid Outage Site went down because Gen FAILED To st=
art due to Alarms ""Underfrequency//He Manually Started the Gen (EU)","Delo=
r Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Under Frequency=
","Backtracking//Grid Outage Site went down because Gen FAILED To start due=
 to Alarms ""Underfrequency//He Manually Started the Gen(EU)","loic.noumsi@=
matech-cameroun.com","2638","04-06-2025 22:19:12","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005182072","E=
toug ebe Meweulo","","04-06-2025 22:09:35","04-06-2025 22:09:27","04-06-202=
5 23:52:35","Site went down due to Disjonction in the power bay (PWC  )  //=
 He made a bridge with 2 CB","Hyemafo Gildas","Equipment Repair","Passive",=
"Rectifier","Rectifier - Circuit Breaker","Site went down due to Disjonctio=
n in the power bay (PWC  )  // He made a bridge with 2 CB","gaelle.njiofack=
@matech-cameroun.com","9","04-06-2025 22:09:35","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0005181869","Meh=
anda 1","","04-06-2025 21:32:02","04-06-2025 20:18:35","04-06-2025 21:22:35=
","BACKTRACKING//Grid outage gen failed to start due to ATS dysfunctionning=
 //Grid return","Albran Byorel","Access Denial","Security","Security Concer=
ns In Site Environs","Access Issue - Security","BACKTRACKING//Grid outage g=
en failed to start due to ATS dysfunctionning //Grid return","loic.noumsi@m=
atech-cameroun.com","4408","04-06-2025 21:32:02","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005181862","Djo=
nassi-Yde","","04-06-2025 21:30:35","04-06-2025 19:58:13","04-06-2025 22:46=
:13","BACKTRACKING. Site went down due to 03/04 rectifier faulty on site SS=
 IIHS bernard Atangana is confirm // He reset rectifiers","Fabrice Pouakam"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module","BACKTRACKING.=
 Site went down due to 03/04 rectifier faulty on site SS IIHS bernard Atang=
ana is confirm // He reset rectifiers","ludivine.ngamaleu@ihstowers.com","5=
542","04-06-2025 21:30:35","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005181844","Eko=
umdoum OCM","","04-06-2025 21:28:40","04-06-2025 21:00:24","04-06-2025 23:1=
8:24","Backtracking//Grid outage, site went down due to Gen overload(20kva,=
280 A) // Grid restoration","Albran Byorel","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, site went down due to Gen overload=
(20kva,280 A) // Grid restoration","loic.noumsi@matech-cameroun.com","1697"=
,"04-06-2025 21:28:40","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005181736","B=
arriere IHS","","04-06-2025 21:11:47","04-06-2025 21:02:36","05-06-2025 08:=
52:54","Grid outage; Site went Down due to Gen overload(15Kva, 200A) SS IHS=
 FELIX ZAMBE is informed//Grid return","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage; Site went Down due to =
Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed//Grid return","gae=
lle.njiofack@matech-cameroun.com","553","04-06-2025 21:11:47","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005181683","S=
aa","","04-06-2025 20:59:50","04-06-2025 20:57:43","04-06-2025 21:00:16","G=
rid outage, site went down before Gen start due poor backup battery // Gen =
automatically started	","Parker Tchoup","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site went down before=
 Gen start due poor backup battery // Gen automatically started","gaelle.nj=
iofack@matech-cameroun.com","128","04-06-2025 20:59:50","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005181666","N=
kolfon Cimencam","","04-06-2025 20:56:23","04-06-2025 20:55:15","04-06-2025=
 20:58:54","Site is impacted by Afanoya II(Not manage by HIS)","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","	Site is impacted by Afanoya II(Not manage by HIS)=
","gaelle.njiofack@matech-cameroun.com","69","04-06-2025 20:56:23","MATECH =
CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005181662","N=
gouetou","","04-06-2025 20:55:28","04-06-2025 20:48:11","04-06-2025 21:00:0=
8","No power issue site on Gen, with Ubay=3D51.2V. The Tx Fme Gregoire (654=
547479) from Huawei is informed","Parker Tchoup","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 site on Gen, with Ubay=3D51.2V. The Tx Fme Gregoire (654547479) from Huawe=
i is informed","loic.noumsi@matech-cameroun.com","439","04-06-2025 20:55:28=
","MATECH CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0005181487","Car=
refour Ayissi Ele","","04-06-2025 20:27:11","04-06-2025 20:18:02","04-06-20=
25 21:34:02","BACKTRACKING// Active//No power issue on site ,site on Solar =
with Ubaie=3D 49.9V The Tx FME Gregroire /652070658/From HUAWEI is informed=
","Parker Tchoup","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","No power issue on site ,site on Solar with Ub=
aie=3D 49.9V The Tx FME Gregroire /652070658/From HUAWEI is informed","loic=
.noumsi@matech-cameroun.com","549","04-06-2025 20:27:11","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005181481","M=
ontee-Des-Soeurs","","04-06-2025 20:26:13","04-06-2025 20:24:04","05-06-202=
5 01:55:04","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) //=
 Grid returned","gaelle.njiofack@matech-cameroun.com","130","04-06-2025 20:=
26:13","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005181462","A=
wae Ewonkan","","04-06-2025 20:24:57","04-06-2025 20:24:51","04-06-2025 22:=
37:05","	Grid outage site went down due to Gen Overload (20Kva, Iload 225 A=
)IHS SS Alphonse is informed// Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","	Grid outage site went down due=
 to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed// Grid ret=
urn","gaelle.njiofack@matech-cameroun.com","7","04-06-2025 20:24:57","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005181360","B=
arriere","","04-06-2025 20:07:26","04-06-2025 20:05:15","04-06-2025 20:33:0=
8","No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266068/=
Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
bay: 54.6V site on Gen TX Fme SAMBA (654266068/Huawei) is informed.","gaell=
e.njiofack@matech-cameroun.com","133","04-06-2025 20:07:26","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005181202","Eto=
ug ebe biscuiterie","","04-06-2025 19:39:18","04-06-2025 19:30:10","04-06-2=
025 23:03:10","BACKTRACKING//Grid fluctuations, site went down due to Grid =
bad voltage and no rcp on site // He bypassed Grid and started Gen manually=
","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","BACKTRACKING//Grid fluctuations, site went down due to Gr=
id bad voltage and no rcp on site // He bypassed Grid and started Gen manua=
lly","loic.noumsi@matech-cameroun.com","548","04-06-2025 19:39:18","MATECH =
CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005181196","MBA=
LNGONG LYCEE","","04-06-2025 19:38:42","04-06-2025 18:58:32","04-06-2025 20=
:53:32","Backtracking//	Grid outage, Site went down because Gen stopped due=
 to overload(9kva, 130A) SS IHS Felix Zambe is informed and confirmed ","Fa=
nda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Backt=
racking//	Grid outage, Site went down because Gen stopped due to overload(9=
kva, 130A) SS IHS Felix Zambe is informed and confirmed ","gaelle.njiofack@=
matech-cameroun.com","2412","04-06-2025 19:38:42","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0005181068","O=
KOA Peage","","04-06-2025 19:05:57","04-06-2025 18:56:59","04-06-2025 19:28=
:36","Grid outage; Site went down due to Gen battery discharge // Gen start=
ed with battery Backup","Fanda Brice","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Generator Battery","Grid outage; Site went down due to Gen batte=
ry discharge // Gen started with battery Backup","gaelle.njiofack@matech-ca=
meroun.com","1162","04-06-2025 19:05:57","MATECH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0005181058","O=
ssombe","","04-06-2025 19:04:05","04-06-2025 18:59:57","04-06-2025 19:19:34=
","Site went down due to work (replacement of Gen Card by SS Parker) // End=
 of work.","Parker Tchoup","Equipment Replacement","Passive","Planned Activ=
ity","Planned Activity - ACDG Inspection","Site went down due to work (repl=
acement of Gen Card by SS Parker) // End of work.","gaelle.njiofack@matech-=
cameroun.com","249","04-06-2025 19:04:05","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005181038","M=
essassi 2","","04-06-2025 19:02:54","04-06-2025 19:01:46","04-06-2025 20:20=
:14","No power issue Ubaie:54.06V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:54.06V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","gaelle.njiofack@matech-cameroun.com","70","04-06-2025 19:02:54","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0005180868","Y=
ona Hotel","","04-06-2025 18:39:18","04-06-2025 12:24:26","04-06-2025 13:10=
:14","Active: no power issue, site is on grid with Ubaie=3D54.4V, Mohamadou=
(691144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"	Active: no power issue, site is on grid with Ubaie=3D54.4V, Mohamadou(69=
1144435) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","22=
492","04-06-2025 18:39:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005180611","Bastos-N=
ylon","","04-06-2025 17:54:41","04-06-2025 17:20:32","04-06-2025 21:29:50",=
"Cascaded Incident from TTO5328695","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Backtracking//Site went down due t=
o PWC overload // Site stabilised","system","565106","04-06-2025 17:54:41",=
"MATECH CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0005180365","Tsi=
nga","IHS_YND_126","04-06-2025 17:07:47","04-06-2025 17:20:32","04-06-2025 =
21:01:50","Backtracking//Site went down due to PWC overload // Site stabili=
sed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","Backtracking//Site went down due to PWC overload // Site =
stabilised","loic.noumsi@matech-cameroun.com","16508","04-06-2025 17:07:47"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0005180104","M=
imboman-Village","IHS_YND_709","04-06-2025 16:21:02","04-06-2025 16:16:55",=
"04-06-2025 17:09:42","	Grid outage, site went down because gen failed to s=
tart due to Pwc ZTE dysfunction// he reset it and started Gen manualy","Mba=
 Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","	Grid outage, site went down because gen failed to start due to=
 Pwc ZTE dysfunction// he reset it and started Gen manualy","gaelle.njiofac=
k@matech-cameroun.com","248","04-06-2025 16:21:02","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0005180100","N=
kolo II New","","04-06-2025 16:20:19","04-06-2025 16:16:55","04-06-2025 17:=
09:42","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","	Grid outage, site went down because gen failed to start =
due to Pwc ZTE dysfunction// he reset it and started Gen manualy","gaelle.n=
jiofack@matech-cameroun.com","568876","04-06-2025 16:20:19","MATECH CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0005180067","M=
volye-New","","04-06-2025 16:14:50","04-06-2025 16:10:44","04-06-2025 16:20=
:16","Active// No power Issue Site on Grid Ubaie =3D51.8V, The TX FME Mbah =
Hosiah (674007438) is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site=
 on Grid Ubaie =3D51.8V, The TX FME Mbah Hosiah (674007438) is informed","g=
aelle.njiofack@matech-cameroun.com","247","04-06-2025 16:14:50","MATECH CMR=
"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005179801","Odz=
a petit marche new","","04-06-2025 15:42:53","04-06-2025 15:37:48","04-06-2=
025 15:41:48","Grid outage, site went down due Grid bad voltage and no rcp =
on site // He bypassed Grid and started Gen manually","Albran Byorel","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid o=
utage, site went down due Grid bad voltage and no rcp on site // He bypasse=
d Grid and started Gen manually","loic.noumsi@matech-cameroun.com","306","0=
4-06-2025 15:42:53","MATECH CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0005179659","O=
yomabang OCM","","04-06-2025 15:21:27","04-06-2025 15:14:19","04-06-2025 15=
:49:29","Site went down due to Plan work done by RM Willy Kamga (699003823)=
 // End of work","TIENTCHEU NZETCHIEU GAEL","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to Plan w=
ork done by RM Willy Kamga (699003823) // End of work","gaelle.njiofack@mat=
ech-cameroun.com","429","04-06-2025 15:21:27","MATECH CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0005179607","A=
KONGO","","04-06-2025 15:12:55","04-06-2025 00:20:36","04-06-2025 00:21:23"=
,"BactrackingNo power issue on site Ubaie=3D52,5V site on Gen. The Tx FME R=
odrigue (655102999)from Huawei is informed. Repetitive issue ","Fanda Brice=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","BactrackingNo power issue on site Ubaie=3D52,5V site on Gen. =
The Tx FME Rodrigue (655102999)from Huawei is informed. Repetitive issue ",=
"mouliom.anselme@matech-cameroun.com","53540","04-06-2025 15:12:55","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005179550","B=
astos-Nylon","","04-06-2025 15:03:37","03-06-2025 12:54:57","03-06-2025 13:=
00:09","Bactracking  No power issue site on grid with U=3D53.6V site up at =
01:00 pm","Mboua Thierry","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Bactracking  No power issue site on g=
rid with U=3D53.6V site up at 01:00 pm","mouliom.anselme@matech-cameroun.co=
m","94121","04-06-2025 15:03:37","MATECH CMR"
"Closed Complete","Site Down","CTR_419","IHS_YND_227","NOCINC0005179516","M=
vog Betsi","","04-06-2025 14:57:09","04-06-2025 14:49:00","04-06-2025 14:59=
:02","Grid-Gen, eneo fluctuation, site down due to poor backup // eneo satb=
ilized","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid-Gen, eneo fluctuation, site down due to poor=
 backup // eneo satbilized","gaelle.njiofack@matech-cameroun.com","489","04=
-06-2025 14:57:09","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005179492","M=
ontee-Des-Soeurs","","04-06-2025 14:52:31","04-06-2025 14:51:15","04-06-202=
5 14:56:22","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) //=
 Grid returned","gaelle.njiofack@matech-cameroun.com","78","04-06-2025 14:5=
2:31","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005179477","S=
imbock OCM","","04-06-2025 14:50:24","04-06-2025 14:46:16","04-06-2025 14:5=
1:28","No power issue U=3D52.5V site on Grid The Tx Fme Hosiah Mbah (674007=
438) of Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=
=3D52.5V site on Grid The Tx Fme Hosiah Mbah (674007438) of Huawei is infor=
med","gaelle.njiofack@matech-cameroun.com","1418","04-06-2025 14:50:24","MA=
TECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005179467","OBA=
M NGOLA OCM","","04-06-2025 14:48:49","04-06-2025 14:43:41","04-06-2025 14:=
49:47","Grid outage, site went down because Gen failed to start due to card=
 Ge faulty // Gen manually started","MINKA NICOLAS","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down becaus=
e Gen failed to start due to card Ge faulty // Gen manually started","cedri=
c.tiani@matech-cameroun.com","309","04-06-2025 14:48:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0005179404","Leboudi"=
,"","04-06-2025 14:39:13","04-06-2025 14:31:26","04-06-2025 15:09:29","Casc=
aded Incident from TTO5327488","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue on site Ubaie 52=
V Site on Gen, The TX Mouhamadou (6144435) from Huawei is informed. (Site w=
ent down due to double disjunction CB(100*100A) in PWC that feeds OCM//H e =
rearmed it)","system","575021","04-06-2025 14:39:13","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0005179388","N=
kolafeme","IHS_YND_309","04-06-2025 14:37:35","04-06-2025 14:31:26","04-06-=
2025 16:29:29","No power issue on site Ubaie 52V Site on Gen, The TX Mouham=
adou (691144435) from Huawei is informed. (Site went down due to double dis=
junction CB(100*100A) in PWC that feeds OCM//H e rearmed it)","TIENTCHEU NZ=
ETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","No power issue on site Ubaie 52V Site on Gen, The=
 TX Mouhamadou (691144435) from Huawei is informed. (Site went down due to =
double disjunction CB(100*100A) in PWC that feeds OCM//H e rearmed it)","ga=
elle.njiofack@matech-cameroun.com","370","04-06-2025 14:37:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005179327","Eto koss=
 Yde","","04-06-2025 14:24:25","04-06-2025 14:20:47","04-06-2025 14:26:28",=
"Cascaded Incident from TTO5327416","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","	Grid outage, Site went down before =
Gen start due to poor backup // Gen Manually started","system","575642","04=
-06-2025 14:24:25","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005179311","M=
EFOU ASSI","IHS_YND_737","04-06-2025 14:21:14","04-06-2025 14:20:47","04-06=
-2025 14:26:28","	Grid outage, Site went down before Gen start due to poor =
backup // Gen Manually started","Fanda Brice","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","	Grid outage, Site went down=
 before Gen start due to poor backup // Gen Manually started","vanel.mbiada=
@matech-cameroun.com","29","04-06-2025 14:21:14","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005179307","Nom=
ayos montee Meche","","04-06-2025 14:20:30","04-06-2025 14:19:24","04-06-20=
25 14:21:26","	Grid outage, Site went down before Gen start due to poor bac=
kup // Gen Manually started","Fanda Brice","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","	Grid outage, Site went down be=
fore Gen start due to poor backup // Gen Manually started","cedric.tiani@ma=
tech-cameroun.com","67","04-06-2025 14:20:30","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005179276","M=
vog-Manga","","04-06-2025 14:13:20","04-06-2025 14:10:10","04-06-2025 15:15=
:32","Grid outage site went down due to PWC dysunction//He reset it and sit=
e on Gen","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Grid outage site went down due to PWC dysunction//He=
 reset it and site on Gen","vanel.mbiada@matech-cameroun.com","192","04-06-=
2025 14:13:20","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0005179225","Ema=
na Lycee","","04-06-2025 14:02:37","04-06-2025 13:56:11","04-06-2025 20:56:=
59","No power issue site on grid with U=3D54v Symphorien(691316854) from Hu=
awei is informed, site up without intervention.","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue site on grid with U=3D54v Symphorien(691316854) from Hua=
wei is informed, site up without intervention.","cedric.tiani@matech-camero=
un.com","388","04-06-2025 14:02:37","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005179178","Nko=
lbong","","04-06-2025 13:52:25","04-06-2025 13:43:14","04-06-2025 14:00:14"=
,"Site went Down because Gen started and stopped due to Gen overload(22kva/=
/350A) // Grid returned","Delor Telezing","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Site went Down because Gen started and stopped du=
e to Gen overload(22kva//350A) // Grid returned","cedric.tiani@matech-camer=
oun.com","552","04-06-2025 13:52:25","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0005179082","M=
elen Ba'aba","","04-06-2025 13:37:35","04-06-2025 13:31:38","04-06-2025 13:=
36:18","","Siligap Boris","Cascade Outage","Active","Cascade Active","Casca=
de Active","No power issue on site, Site on Grid UBAIE=3D54V. site up witho=
ut intervention.","vanel.mbiada@matech-cameroun.com","578534","04-06-2025 1=
3:37:35","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005179072","N=
kolfoulou","IHS_YND_308","04-06-2025 13:36:46","04-06-2025 13:31:38","04-06=
-2025 13:36:18","No power issue on site, Site on Grid UBAIE=3D54V. site up =
without intervention.","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, =
Site on Grid UBAIE=3D54V. site up without intervention.","vanel.mbiada@mate=
ch-cameroun.com","309","04-06-2025 13:36:46","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005179069","T=
SINGA VILLAGE 2","","04-06-2025 13:36:11","04-06-2025 13:30:55","04-06-2025=
 18:38:14","Active//No power issue on site, Site on Battery UBAIE=3D54.5V s=
ynphorien (675295205) From huawei is informed","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site, Site on Battery UBAIE=3D54.5V synphorien (=
675295205) From huawei is informed","vanel.mbiada@matech-cameroun.com","317=
","04-06-2025 13:36:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0005178933","Yona Hot=
el","","04-06-2025 13:12:16","04-06-2025 13:10:15","04-06-2025 13:14:49","C=
ascaded Incident from TTO5326966","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down due to wor=
k of our RM Willy Kamga (656072630) on site (securing transmission) // End =
of work","system","579784","04-06-2025 13:12:16","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005178931","N=
kolbi-Boss","IHS_YND_271","04-06-2025 13:11:35","04-06-2025 13:10:15","04-0=
6-2025 13:14:49","Site went down due to work of our RM Willy Kamga (6560726=
30) on site (securing transmission) // End of work","TIENTCHEU NZETCHIEU GA=
EL","Equipment Replacement","Passive","Planned Activity","Planned Activity =
- Passive","Site went down due to work of our RM Willy Kamga (656072630) on=
 site (securing transmission) // End of work","vanel.mbiada@matech-cameroun=
.com","81","04-06-2025 13:11:35","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005178895","ODZ=
A MINKAN EDIBI ASSI","","04-06-2025 13:08:28","04-06-2025 13:02:21","04-06-=
2025 14:08:21","Grid Outage, site went down because gen failed to start due=
 to PWC ZTE malfunction // He reset it and started the Gen manually","Albra=
n Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overlo=
aded","Grid Outage, site went down because gen failed to start due to PWC Z=
TE malfunction // He reset it and started the Gen manually","cedric.tiani@m=
atech-cameroun.com","369","04-06-2025 13:08:28","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0005178842","Tsi=
nga village","","04-06-2025 13:03:50","04-06-2025 12:56:52","04-06-2025 15:=
14:16","Grid outage, site went down due to Grid bad voltage and no rcp on s=
ite // He bypassed Grid and started Gen manually","Delor Telezing","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid outa=
ge, site went down due to Grid bad voltage and no rcp on site // He bypasse=
d Grid and started Gen manually","cedric.tiani@matech-cameroun.com","419","=
04-06-2025 13:03:50","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005178718","Aha=
la Echangeur","","04-06-2025 12:39:12","04-06-2025 12:37:01","04-06-2025 12=
:40:26","Site went down due to insufficient rectifiers on site//Site stabil=
ised","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Site went down due to insufficient rectifiers on site//Site stabili=
sed","cedric.tiani@matech-cameroun.com","132","04-06-2025 12:39:12","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0005178708","L=
eboudi","","04-06-2025 12:36:53","04-06-2025 12:32:18","04-06-2025 13:27:39=
","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Site went down due to double disjunction CB(100*100A) =
in PWC that feeds OCM//H e rearmed it ","vanel.mbiada@matech-cameroun.com",=
"582005","04-06-2025 12:36:53","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0005178689","N=
kolafeme","IHS_YND_309","04-06-2025 12:34:53","04-06-2025 12:32:18","04-06-=
2025 13:27:39","Site went down due to double disjunction CB(100*100A) in PW=
C that feeds OCM//H e rearmed it ","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","Rectifier","Rectifier - Circuit Breaker","Site went down d=
ue to double disjunction CB(100*100A) in PWC that feeds OCM//H e rearmed it=
 ","vanel.mbiada@matech-cameroun.com","156","04-06-2025 12:34:53","MATECH C=
MR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005178667","E=
toudi","","04-06-2025 12:30:55","04-06-2025 12:28:43","04-06-2025 12:30:36"=
,"Grid fluctuation ,site went down because Gen fails to start due to grid b=
ad voltage //Grid stabilisation","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Grid fluctuation ,site we=
nt down because Gen fails to start due to grid bad voltage //Grid stabilisa=
tion","vanel.mbiada@matech-cameroun.com","133","04-06-2025 12:30:55","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_255","IHS_YND_286","NOCINC0005178656","D=
agobert","","04-06-2025 12:29:18","04-06-2025 12:24:59","04-06-2025 12:37:3=
7","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Site went down due to work of our RM Willy Kamga (656=
072630) on site (securing transmission)//End of WORK","vanel.mbiada@matech-=
cameroun.com","582432","04-06-2025 12:29:18","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0005178650","MEH=
ANDAN","","04-06-2025 12:29:03","04-06-2025 12:28:54","05-06-2025 13:36:43"=
,"site went down because gen start an stopped due to water infiltration in =
tank // He purged The tank and Gen manually started","Albran Byorel","Fuel =
Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fu=
el","site went down because gen start an stopped due to water infiltration =
in tank // He purged The tank and Gen manually started","cedric.tiani@matec=
h-cameroun.com","11","04-06-2025 12:29:03","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005178644","N=
kolbi-Boss","IHS_YND_286","04-06-2025 12:27:28","04-06-2025 12:24:59","04-0=
6-2025 12:37:37","Site went down due to work of our RM Willy Kamga (6560726=
30) on site (securing transmission)//End of WORK","TIENTCHEU NZETCHIEU GAEL=
","Installation Activity","Passive","Planned Activity","Installation Activi=
ty","Site went down due to work of our RM Willy Kamga (656072630) on site (=
securing transmission)//End of WORK","vanel.mbiada@matech-cameroun.com","15=
0","04-06-2025 12:27:28","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005178607","N=
gouetou","","04-06-2025 12:20:50","04-06-2025 12:18:18","04-06-2025 12:25:1=
3","No power issue site on Gen, with Ubay=3D57V. The Tx Fme Gregoire (65454=
7479) from Huawei is informed","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on Gen, with Ubay=3D57V. The Tx Fme Gregoire (654547479) from Huawei is=
 informed","vanel.mbiada@matech-cameroun.com","154","04-06-2025 12:20:50","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005178558","MEHANDAN=
","","04-06-2025 12:08:44","04-06-2025 12:06:54","04-06-2025 12:08:14","Cas=
caded Incident from TTO5326544","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se Gen failed to start due to grid bad voltage // Grid returned","system","=
583505","04-06-2025 12:08:44","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005178550","O=
dza II OCM","IHS_YND_528","04-06-2025 12:07:11","04-06-2025 12:06:54","04-0=
6-2025 12:08:14","Grid fluctuation, site went down because Gen failed to st=
art due to grid bad voltage // Grid returned","Albran Byorel","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on, site went down because Gen failed to start due to grid bad voltage // G=
rid returned","vanel.mbiada@matech-cameroun.com","19","04-06-2025 12:07:11"=
,"MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005178487","Ebo=
go","","04-06-2025 11:54:50","04-06-2025 11:53:35","04-06-2025 11:57:53","A=
ctive// No Power issue on site Ubaie 53V site on Grid, Julien /693095849 fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issue =
on site Ubaie 53V site on Grid, Julien /693095849 from Huawei is informed",=
"cedric.tiani@matech-cameroun.com","76","04-06-2025 11:54:50","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005178450","M=
essassi 2","","04-06-2025 11:45:34","04-06-2025 11:44:28","04-06-2025 11:45=
:19","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automatically","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Grid outage, Site went down before =
Gen start due to poor backup // Gen started automatically","vanel.mbiada@ma=
tech-cameroun.com","69","04-06-2025 11:45:34","MATECH CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0005178444","F=
ebe Village","","04-06-2025 11:45:02","04-06-2025 11:44:53","04-06-2025 11:=
50:28","Site went down due to insufficient rectifier on site(01/4 rectifier=
s faulty)//Site stabilised","Mboua Thierry","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down due to insufficient rectifier =
on site(01/4 rectifiers faulty)//Site stabilised","vanel.mbiada@matech-came=
roun.com","10","04-06-2025 11:45:02","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005178270","M=
ontee-Jouvence-II","","04-06-2025 11:22:21","02-06-2025 15:40:58","02-06-20=
25 17:40:49","Bactracking No power issue site on grid with U=3D53v site up =
at 05:40 PM","Hyemafo Gildas","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Bactracking No power issue site o=
n grid with U=3D53v site up at 05:40 PM","mouliom.anselme@matech-cameroun.c=
om","157285","04-06-2025 11:22:21","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005178262","C=
NR","","04-06-2025 11:19:58","04-06-2025 11:17:04","04-06-2025 11:21:32","	=
Grid outage, Site went down before Gen start due to poor backup // Grid ret=
urn","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Battery Low","Grid outage, Site went down before Gen start due to p=
oor backup // Grid return","vanel.mbiada@matech-cameroun.com","175","04-06-=
2025 11:19:58","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005178140","Feb=
e Village","","04-06-2025 11:01:37","04-06-2025 10:56:22","04-06-2025 10:59=
:08","Site went down due to insufficient rectifier on site(01/4 rectifiers =
faulty)//Site stabilised","Mboua Thierry","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down due to insufficient rectifier on=
 site(01/4 rectifiers faulty)//Site stabilised","cedric.tiani@matech-camero=
un.com","316","04-06-2025 11:01:37","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0005178138","B=
iteng-Maetur","","04-06-2025 11:00:43","02-06-2025 22:50:51","02-06-2025 23=
:06:03","Batracking No power issue site on grid with U=3D52.1v site up at 1=
1:06 PM","Mba Lazare Herve","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Batracking No power issue site on g=
rid with U=3D52.1v site up at 11:06 PM","mouliom.anselme@matech-cameroun.co=
m","130194","04-06-2025 11:00:43","MATECH CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0005178020","C=
hapelle-Essos","","04-06-2025 10:42:53","02-06-2025 23:05:07","02-06-2025 2=
3:11:17","Bactracking Nopower issue siton grid with U=3D53.6v site up at 11=
:11 PM","Delor Telezing","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Bactracking Nopower issue siton grid w=
ith U=3D53.6v site up at 11:11 PM","mouliom.anselme@matech-cameroun.com","1=
28267","04-06-2025 10:42:53","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005177968","Mes=
sassi 2","","04-06-2025 10:32:26","04-06-2025 10:31:17","04-06-2025 10:43:0=
9","	Grid outage, Site went down before Gen start due to poor backup // Gen=
 start automatically","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","	Grid outage, Site went down befor=
e Gen start due to poor backup // Gen start automatically","cedric.tiani@ma=
tech-cameroun.com","71","04-06-2025 10:32:26","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005177936","M=
vog-Ebanda","","04-06-2025 10:25:55","04-06-2025 10:24:33","04-06-2025 10:3=
8:23","Site Down due to plan work, Tiencheu ( 692105769 / Epitech ) and his=
 team was on site to swap PWC // End of work","Siligap Boris","Installation=
 Activity","Passive","Planned Activity","Installation Activity","Site Down =
due to plan work, Tiencheu ( 692105769 / Epitech ) and his team was on site=
 to swap PWC // End of work","vanel.mbiada@matech-cameroun.com","84","04-06=
-2025 10:25:55","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005177716","Awa=
e Ewonkan","","04-06-2025 09:36:59","04-06-2025 09:30:49","04-06-2025 13:20=
:18","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IH=
S SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid retur=
n","cedric.tiani@matech-cameroun.com","372","04-06-2025 09:36:59","MATECH C=
MR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005177713","OBA=
M NGOLA OCM","","04-06-2025 09:36:30","04-06-2025 09:29:23","04-06-2025 09:=
39:19","Grid outage, site went down becausecGen failed to start due to card=
 Ge faulty // He started Gen manually ","MINKA NICOLAS","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down be=
causecGen failed to start due to card Ge faulty // He started Gen manually =
","cedric.tiani@matech-cameroun.com","428","04-06-2025 09:36:30","MATECH CM=
R"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005177668","S=
imbock OCM","","04-06-2025 09:28:45","04-06-2025 09:23:19","04-06-2025 09:3=
8:22","No power issue U=3D52V site on Grid The Tx Fme Hosiah Mbah (67400743=
8) of Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=3D5=
2V site on Grid The Tx Fme Hosiah Mbah (674007438) of Huawei is informed","=
vanel.mbiada@matech-cameroun.com","327","04-06-2025 09:28:45","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005177661","M=
ontee-Des-Soeurs","","04-06-2025 09:27:43","04-06-2025 09:24:51","04-06-202=
5 09:32:43","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) //=
 Grid returned","vanel.mbiada@matech-cameroun.com","173","04-06-2025 09:27:=
43","MATECH CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0005177570","Nko=
lafeme","","04-06-2025 09:14:19","04-06-2025 09:11:12","04-06-2025 09:49:50=
","Grid outage,site went down due to PWC dysfunctionning and Gen card fault=
y//He bypassed it and started the Gen manually","TIENTCHEU NZETCHIEU GAEL",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
,site went down due to PWC dysfunctionning and Gen card faulty//He bypassed=
 it and started the Gen manually","cedric.tiani@matech-cameroun.com","188",=
"04-06-2025 09:14:19","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005177457","Lad=
a I Yde","","04-06-2025 09:02:12","04-06-2025 09:00:03","04-06-2025 14:20:5=
9","Site went down due to 01/03 rectifiers is faulty on site //He added one=
 rectifier","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down due to 01/03 rectifiers is faulty on site /=
/He added one rectifier","cedric.tiani@matech-cameroun.com","130","04-06-20=
25 09:02:12","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005177383","N=
koabang Ebolmedjock","","04-06-2025 08:41:52","04-06-2025 08:36:08","04-06-=
2025 09:01:44","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Gen. Notice that it is impacted b=
y Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matech-camero=
un.com","345","04-06-2025 08:41:52","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005177196","M=
essassi 2","","04-06-2025 08:06:26","04-06-2025 08:01:08","04-06-2025 08:07=
:56","No power issue Ubaie:54.06V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:54.06V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed","vanel.mbiada@matech-cameroun.com","321","04-06-2025 08:06:26","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0005176940","Leboudi"=
,"","04-06-2025 07:05:01","04-06-2025 06:39:07","04-06-2025 08:54:19","Casc=
aded Incident from TTO5324601","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage,site went down d=
ue to PWC dysfunctionning and Gen card faulty//He bypassed it and started t=
he Gen manually","system","1242406","04-06-2025 07:05:01","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005176874","Lad=
a I Yde","","04-06-2025 06:54:09","04-06-2025 06:53:02","04-06-2025 08:41:3=
4","Site went down due to 01/03 rectifiers is faulty on site//Site stabilis=
ed","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down due to 01/03 rectifiers is faulty on site//Site sta=
bilised","cedric.tiani@matech-cameroun.com","68","04-06-2025 06:54:09","MAT=
ECH CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0005176823","Nko=
lafeme","IHS_YND_309","04-06-2025 06:40:16","04-06-2025 06:39:07","04-06-20=
25 09:03:05","Grid outage,site went down due to PWC dysfunctionning and Gen=
 card faulty//He bypassed it and started the Gen manually","TIENTCHEU NZETC=
HIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage,site went down due to PWC dysfunctionning and Gen card faulty//=
He bypassed it and started the Gen manually","cedric.tiani@matech-cameroun.=
com","70","04-06-2025 06:40:16","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005176778","O=
dza II OCM","","04-06-2025 06:29:11","04-06-2025 06:26:03","04-06-2025 06:3=
5:28","Grid fluctuation, site went down because Gen failed to start due to =
grid bad voltage  // Grid return","Albran Byorel","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site wen=
t down because Gen failed to start due to grid bad voltage  // Grid return"=
,"vanel.mbiada@matech-cameroun.com","190","04-06-2025 06:29:11","MATECH CMR=
"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005176760","A=
wae Ewonkan","","04-06-2025 06:25:17","04-06-2025 06:22:00","04-06-2025 07:=
42:31","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","gerard.tchangoue@matech-cameroun.com","199","04-06-2025 06:25:17","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005176322","N=
kozoa","","04-06-2025 04:15:09","04-06-2025 04:10:56","04-06-2025 06:07:48"=
," Site went down because gen started and stopped due to air intake causing=
 by pierced fuel pipe // He normalized fuel pipe and gen manually started",=
"Fabrice Pouakam","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Air=
 Intake"," Site went down because gen started and stopped due to air intake=
 causing by pierced fuel pipe // He normalized fuel pipe and gen manually s=
tarted","edwige.kapawo@matech-cameroun.com","255","04-06-2025 04:15:09","MA=
TECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0005175830","Mes=
sassi okolo","","04-06-2025 01:03:31","04-06-2025 00:59:21","04-06-2025 01:=
27:43","Grid outage , site went down before Gen started due to poor battery=
 backup // Grid return","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage , site went down bef=
ore Gen started due to poor battery backup // Grid return","edwige.kapawo@m=
atech-cameroun.com","251","04-06-2025 01:03:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005175816","MBIMBIM"=
,"","04-06-2025 00:56:29","04-06-2025 00:37:29","04-06-2025 00:37:35","Casc=
aded Incident from TTO5323404","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 52.1V. TX FME Willy Ngouni 699759164 of Huawei is informed.","system","=
617945","04-06-2025 00:56:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005175814","Yoko OCM=
","","04-06-2025 00:56:29","04-06-2025 00:37:29","04-06-2025 00:37:35","Cas=
caded Incident from TTO5323404","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 52.1V. TX FME Willy Ngouni 699759164 of Huawei is informed.","system",=
"617944","04-06-2025 00:56:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005175815","Ngouetou=
","","04-06-2025 00:56:29","04-06-2025 00:37:29","04-06-2025 00:37:35","Cas=
caded Incident from TTO5323404","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 52.1V. TX FME Willy Ngouni 699759164 of Huawei is informed.","system",=
"617944","04-06-2025 00:56:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005175812","Ngoum","=
","04-06-2025 00:56:28","04-06-2025 00:37:29","04-06-2025 00:37:35","Cascad=
ed Incident from TTO5323404","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 52.1V. TX FME Willy Ngouni 699759164 of Huawei is informed.","system","=
617946","04-06-2025 00:56:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005175813","Matsari"=
,"","04-06-2025 00:56:28","04-06-2025 00:37:29","04-06-2025 00:37:35","Casc=
aded Incident from TTO5323404","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 52.1V. TX FME Willy Ngouni 699759164 of Huawei is informed.","system","=
617943","04-06-2025 00:56:28","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005175541","Feb=
e Village","","03-06-2025 23:54:00","03-06-2025 23:51:51","03-06-2025 23:56=
:51","Site went down due to insufficiency of rectifiers, Francois IHS // Si=
te stabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down due to insufficiency of rectifiers, Francoi=
s IHS // Site stabilised","gerard.tchangoue@matech-cameroun.com","130","03-=
06-2025 23:54:00","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0005175239","Bar=
riere IHS","","03-06-2025 22:49:23","03-06-2025 20:35:09","03-06-2025 23:18=
:19","Grid Fluctuations; Site went Down due to Gen overload(15Kva, 200A) SS=
 IHS FELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid Fluctuations; Site went =
Down due to Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Gri=
d return","edwige.kapawo@matech-cameroun.com","8056","03-06-2025 22:49:23",=
"MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005175205","Lad=
a I Yde","","03-06-2025 22:40:52","03-06-2025 22:33:43","04-06-2025 01:43:4=
3","Active//No power issue on site ,site on Grid with Ubaie=3D54,3V The Tx =
FME Leonel Steve (655184876) from Huawei is informed.","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site ,site on Grid with Ubaie=3D54,3V =
The Tx FME Leonel Steve (655184876) from Huawei is informed.","gerard.tchan=
goue@matech-cameroun.com","447","03-06-2025 22:40:52","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005175053","S=
apeur Mimboman","","03-06-2025 22:11:25","03-06-2025 22:07:15","04-06-2025 =
09:18:42"," Acces issue during the nigth due to landlord (site went down be=
cause  PWC burnt partialy due to Lightning(surge protector,rcp burnt on sit=
e)//He connected it partially","Mba Lazare Herve","Access Denial","Lease Or=
 Legal","Landlord Related Issues","Access Issue - Land Lord"," Acces issue =
during the nigth due to landlord (site went down because  PWC burnt partial=
y due to Lightning(surge protector,rcp burnt on site)//He connected it part=
ially","christelle.ngonga@matech-cameroun.com","251","03-06-2025 22:11:25",=
"MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005174944","Djo=
nassi-Yde","","03-06-2025 21:51:54","03-06-2025 19:33:50","03-06-2025 22:19=
:43","site went down due to insufficient of rectifiers//He reset rectifier"=
,"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","site went down due to insufficient of rectifiers//He reset rectifier",=
"franck.nkomot@matech-cameroun.com","8768","03-06-2025 21:51:54","MATECH CM=
R"
"Closed Complete","Site Down","T3150","IHS_YND_214","NOCINC0005174873","Nko=
lmesseng-II","","03-06-2025 21:41:03","03-06-2025 21:36:42","03-06-2025 21:=
44:42","Grid outage, Gen failed to start due to  unknown alarm // he has se=
rved and manual start of Gen","Siligap Boris","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, Gen failed to start due to =
 unknown alarm // he has served and manual start of Gen","franck.nkomot@mat=
ech-cameroun.com","322","03-06-2025 21:41:03","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005174806","N=
kolfon Cimencam","","03-06-2025 21:31:20","03-06-2025 21:29:10","03-06-2025=
 21:31:35","Site is impacted by Afanoya II(Not manage by HIS)","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","Site is impacted by Afanoya II(Not manage by HIS)"=
,"christelle.ngonga@matech-cameroun.com","131","03-06-2025 21:31:20","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005174706","A=
wae Ewonkan","","03-06-2025 21:16:18","03-06-2025 21:12:01","03-06-2025 22:=
13:01","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","christelle.ngonga@matech-cameroun.com","258","03-06-2025 21:16:18","M=
ATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005174679","Ron=
d Point Express1114","","03-06-2025 21:12:55","03-06-2025 21:09:44","03-06-=
2025 21:20:44","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","fr=
anck.nkomot@matech-cameroun.com","192","03-06-2025 21:12:55","MATECH CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0005174461","N=
kongtock","","03-06-2025 20:41:02","03-06-2025 19:54:46","03-06-2025 22:02:=
46","Site Wen Down because fuse burning behind the GE card // he replaced t=
he fuse","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - =
Kick Starter","Site Wen Down because fuse burning behind the GE card // he =
replaced the fuse","christelle.ngonga@matech-cameroun.com","2777","03-06-20=
25 20:41:02","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0005174343","S=
calom","","03-06-2025 20:25:45","03-06-2025 20:24:37","03-06-2025 20:57:37"=
,"Grid outage, site went down Gen failed to start due to ATS Dysfunctioning=
 on Site // He reset ATS and started Gen manually","Paul BIBOUM","Equipment=
 Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went =
down Gen failed to start due to ATS Dysfunctioning on Site // He reset ATS =
and started Gen manually","christelle.ngonga@matech-cameroun.com","69","03-=
06-2025 20:25:45","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005174302","E=
ssomba","","03-06-2025 20:16:42","03-06-2025 20:12:36","03-06-2025 20:16:55=
","Site went down because PWC overload // Site stabilised","Mba Lazare Herv=
e","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Site went down because PWC overload // Site stabilised","christelle.ngonga@=
matech-cameroun.com","248","03-06-2025 20:16:42","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005174146","Nko=
abang Alembe","","03-06-2025 19:50:52","03-06-2025 19:47:23","03-06-2025 19=
:51:23","site went down due to insufficiency of rectifiers IHS SS Alphonse =
is informed//site stabilized","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","site went down due to insufficiency of r=
ectifiers IHS SS Alphonse is informed//site stabilized","franck.nkomot@mate=
ch-cameroun.com","210","03-06-2025 19:50:52","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005174145","B=
arriere IHS","","03-06-2025 19:50:18","03-06-2025 19:48:10","03-06-2025 20:=
32:32","Grid Fluctuations; Site went Down due to Gen overload(15Kva, 200A) =
SS IHS FELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid Fluctuations; Site wen=
t Down due to Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // G=
rid return","christelle.ngonga@matech-cameroun.com","129","03-06-2025 19:50=
:18","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005174099","M=
vog-Ada_OCM","","03-06-2025 19:44:42","03-06-2025 19:28:32","03-06-2025 19:=
51:32","Grid Only site, No space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only sit=
e, No space to deploy MDGE // Grid returned","christelle.ngonga@matech-came=
roun.com","6644","03-06-2025 19:44:42","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005174068","NYO=
M 2 IHS","","03-06-2025 19:40:50","03-06-2025 19:35:43","03-06-2025 21:37:4=
3","Site went down due to disjunction of CB (125A) in pwc ZTE // He rearmed=
 it, site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Control =
Panel","Circuit Breaker Tripped","Site went down due to disjunction of CB (=
125A) in pwc ZTE // He rearmed it, site on Grid","franck.nkomot@matech-came=
roun.com","308","03-06-2025 19:40:50","MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005173973","Mvo=
g Betsi Hospital","","03-06-2025 19:22:43","03-06-2025 19:20:35","03-06-202=
5 19:26:35","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid returnGrid outage, Site went down before G=
en start due to poor backup // Grid returnGrid outage, Site went down befor=
e Gen start due to poor backup // Grid return","franck.nkomot@matech-camero=
un.com","129","03-06-2025 19:22:43","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005173946","NTU=
I TOWN","","03-06-2025 19:14:44","03-06-2025 19:09:12","03-06-2025 22:02:12=
","Grid outage gen ran until fuel shortage//Refueling done","Parker Tchoup"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran unti=
l fuel shortage//Refueling done","franck.nkomot@matech-cameroun.com","333",=
"03-06-2025 19:14:44","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005173886","MBA=
LNGONG LYCEE","","03-06-2025 19:04:45","03-06-2025 18:16:06","03-06-2025 22=
:21:14","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down be=
cause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informe=
d and confirmed // Grid returned","franck.nkomot@matech-cameroun.com","2920=
","03-06-2025 19:04:45","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005173850","M=
vog-Manga","","03-06-2025 18:57:46","03-06-2025 18:50:36","03-06-2025 19:28=
:36","Grid outage, site went down because Gen failed to start due to Grid c=
ontactor faulty // Grid return","Albran Byorel","Equipment Repair","Passive=
","Control Panel","ATS-AMF Issue","Grid outage, site went down because Gen =
failed to start due to Grid contactor faulty // Grid return","franck.nkomot=
@matech-cameroun.com","431","03-06-2025 18:57:46","MATECH CMR"
"Closed Complete","Site Down","T0629","IHS_YND_058","NOCINC0005173766","Mvo=
lye","","03-06-2025 18:45:04","03-06-2025 18:11:40","03-06-2025 21:23:41","=
Grid outage,Site went down due to insufficiency of rectifiers // Site stabi=
lized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Grid outage,Site went down due to insufficiency of rectifiers // S=
ite stabilized","franck.nkomot@matech-cameroun.com","2005","03-06-2025 18:4=
5:04","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0005173746","Eto=
ug-Ebe 2","","03-06-2025 18:44:04","03-06-2025 17:56:50","03-06-2025 22:55:=
50","BACKTRACKING. Grid outage, no space to deploy a mobil gen // Grid rest=
oration","","Grid Supply","Passive","Grid","National Grid - Grid Outage Iss=
ue","BACKTRACKING. Grid outage, no space to deploy a mobil gen // Grid rest=
oration","franck.nkomot@matech-cameroun.com","2835","03-06-2025 18:44:04","=
MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005173644","O=
dza II OCM","","03-06-2025 18:30:47","03-06-2025 18:29:37","03-06-2025 18:3=
5:20","Grid Outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Site stabilised","Albran Byorel","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Grid Outage, site went down=
 because gen failed to start due to PWC ZTE malfunction // Site stabilised"=
,"christelle.ngonga@matech-cameroun.com","73","03-06-2025 18:30:47","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005173344","A=
wae Ewonkan","","03-06-2025 17:51:58","03-06-2025 17:50:52","03-06-2025 18:=
22:52","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","christelle.ngonga@matech-cameroun.com","67","03-06-2025 17:51:58","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005173342","O=
dza-PK10","","03-06-2025 17:51:18","03-06-2025 17:49:10","03-06-2025 18:02:=
27","Grid outage, Site went down because generator battery stolen // He sta=
rted Gen with external battery","Albran Byorel","Site Asset Theft","Theft",=
"Theft","Generator Battery Theft","Grid outage, Site went down because gene=
rator battery stolen // He started Gen with external battery","christelle.n=
gonga@matech-cameroun.com","129","03-06-2025 17:51:18","MATECH CMR"
"Closed Complete","Site Down","T0958","IHS_YND_269","NOCINC0005173186","Mvo=
g-Ebanda","","03-06-2025 17:21:55","03-06-2025 17:15:47","03-06-2025 21:11:=
42","Site Down due to works, Tiencheu ( 692105769 / Epitech ) and his team =
was on site to swap PWC // End of work","Siligap Boris","Installation Activ=
ity","Passive","Planned Activity","Installation Activity","Site Down due to=
 works, Tiencheu ( 692105769 / Epitech ) and his team was on site to swap P=
WC // End of work","franck.nkomot@matech-cameroun.com","368","03-06-2025 17=
:21:55","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005173176","N=
koabang2","","03-06-2025 17:18:51","03-06-2025 17:18:47","04-06-2025 01:18:=
55","Grid outage, site went down due to gen overload (22KVA, 330A) // Grid =
return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, site went down due to gen overload (22KVA, 330A) //=
 Grid return","christelle.ngonga@matech-cameroun.com","5","03-06-2025 17:18=
:51","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005173113","N=
koabang2","","03-06-2025 17:06:37","03-06-2025 17:03:30","03-06-2025 17:06:=
58","Grid outage, site went down due to gen overload (22KVA, 330A)// Site s=
tabilisation","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","	Grid outage, site went down due to gen overload (22KVA, 3=
30A)// Site stabilisation","christelle.ngonga@matech-cameroun.com","188","0=
3-06-2025 17:06:37","MATECH CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0005172999","L=
eboudi","","03-06-2025 16:48:59","03-06-2025 16:47:07","03-06-2025 16:53:50=
","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Grid outage, Site went down because Gen failed to star=
t due to PWC ZTE disfunction// He reset it, Site on Gen","christelle.ngonga=
@matech-cameroun.com","645634","03-06-2025 16:48:59","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0005172992","N=
kolafeme","IHS_YND_309","03-06-2025 16:48:13","03-06-2025 16:47:07","03-06-=
2025 16:57:30","Grid outage, Site went down because Gen failed to start due=
 to PWC ZTE disfunction// He reset it, Site on Gen","TIENTCHEU NZETCHIEU GA=
EL","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid outage, Site went down because Gen failed to start due to PWC ZTE dis=
function// He reset it, Site on Gen","christelle.ngonga@matech-cameroun.com=
","67","03-06-2025 16:48:13","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005172909","M=
essassi 2","","03-06-2025 16:40:01","03-06-2025 16:37:55","03-06-2025 16:42=
:26","No power issue Ubaie:54.03  V site on Grid, TX fme symphorien /650257=
151 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
Ubaie:54.03  V site on Grid, TX fme symphorien /650257151 from huawei is in=
formed.","christelle.ngonga@matech-cameroun.com","128","03-06-2025 16:40:01=
","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005172868","F=
OUGEROLE","","03-06-2025 16:35:29","03-06-2025 16:32:23","03-06-2025 18:00:=
32","No power issue, site is on grid with Ubaie=3D52.8V, Symphorien (650257=
151) fom Huawei is informed","Siligap Boris","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, si=
te is on grid with Ubaie=3D52.8V, Symphorien (650257151) fom Huawei is info=
rmed","christelle.ngonga@matech-cameroun.com","187","03-06-2025 16:35:29","=
MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0005172833","MEH=
ANDAN","","03-06-2025 16:31:18","03-06-2025 16:21:10","03-06-2025 16:56:10"=
,"","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down because gen failed to start with alarm=
 undervoltage // He reset gen card and gen manually started","franck.nkomot=
@matech-cameroun.com","647161","03-06-2025 16:31:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0005172809","Ekombiti=
e","","03-06-2025 16:28:40","03-06-2025 14:53:43","03-06-2025 16:52:43","Ca=
scaded Incident from TTO5319884","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went Down because the  rectifi=
er circuit breakers have tripped // He rearmed ","system","774327","03-06-2=
025 16:28:40","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005172797","Nko=
lnda","IHS_YND_528","03-06-2025 16:27:18","03-06-2025 16:21:10","03-06-2025=
 16:56:10","Grid outage, site went down because gen failed to start with al=
arm undervoltage // He reset gen card and gen manually started","Albran Byo=
rel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage, site went down because gen failed to start with alarm undervoltage /=
/ He reset gen card and gen manually started","franck.nkomot@matech-camerou=
n.com","369","03-06-2025 16:27:18","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005172627","T=
alla Monatele","","03-06-2025 16:07:17","03-06-2025 16:05:11","03-06-2025 1=
6:07:31","No power issue, site is on grid with Ubaie=3D52.3V, Gregoir (6545=
47479) from Huawei is informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue,=
 site is on grid with Ubaie=3D52.3V, Gregoir (654547479) from Huawei is inf=
ormed","christelle.ngonga@matech-cameroun.com","127","03-06-2025 16:07:17",=
"MATECH CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0005172562","San=
ta Barbara Yde","IHS_YND_743, IHS_YND_245, IHS_YND_745, IHS_YND_276, IHS_YN=
D_242, IHS_YND_740","03-06-2025 15:59:01","03-06-2025 14:53:43","03-06-2025=
 16:52:43","Site went Down because the  rectifier circuit breakers have tri=
pped // He rearmed ","Delor Telezing","Equipment Repair","Passive","Rectifi=
er","Rectifier - Circuit Breaker","Site went Down because the  rectifier ci=
rcuit breakers have tripped // He rearmed ","franck.nkomot@matech-cameroun.=
com","3919","03-06-2025 15:59:01","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0005172536","M=
bankomo IHS","","03-06-2025 15:56:05","03-06-2025 15:45:58","03-06-2025 16:=
00:49","No power issue on site, site on Gen with U=3D55.6V   Tx FME FULBERT=
 /654266068/ from huawei is informed, Site up without intervention","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site, site on Gen with U=3D55.6V   Tx =
FME FULBERT /654266068/ from huawei is informed, Site up without interventi=
on","christelle.ngonga@matech-cameroun.com","608","03-06-2025 15:56:05","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005172521","S=
imbock OCM","","03-06-2025 15:53:31","03-06-2025 15:51:16","03-06-2025 16:4=
3:15","No power issue U=3D52.5V site on Grid The Tx Fme Hosiah Mbah (674007=
438) of Huawei is informed ","Hyemafo Gildas","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=
=3D52.5V site on Grid The Tx Fme Hosiah Mbah (674007438) of Huawei is infor=
med ","christelle.ngonga@matech-cameroun.com","136","03-06-2025 15:53:31","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005172422","Eto koss=
 Yde","","03-06-2025 15:38:50","03-06-2025 15:36:44","03-06-2025 15:48:44",=
"Cascaded Incident from TTO5319722","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Grid returned","system","649757","03-06-2025=
 15:38:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005172423","ELOUMDEM=
 CARRIERE 2","","03-06-2025 15:38:50","03-06-2025 15:36:44","03-06-2025 15:=
48:44","Cascaded Incident from TTO5319722","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid returned","system","649757","03-=
06-2025 15:38:50","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005172413","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","03-06-2025 15:38:08","03-06-2025 15:36=
:44","03-06-2025 15:48:44","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","Fanda Brice","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Grid returned","franck.nkomot@mat=
ech-cameroun.com","86","03-06-2025 15:38:08","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005172358","Odz=
a II OCM","","03-06-2025 15:31:34","03-06-2025 15:23:22","03-06-2025 17:21:=
22","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction // Site stabilised","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, site went down b=
ecause gen failed to start due to PWC ZTE malfunction // Site stabilised","=
franck.nkomot@matech-cameroun.com","493","03-06-2025 15:31:34","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005172354","Ebo=
go","","03-06-2025 15:31:05","03-06-2025 15:23:00","03-06-2025 18:53:00","A=
ctive// No Power issue on site Ubaie 53V site on Grid, Julien /693095849 fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issue =
on site Ubaie 53V site on Grid, Julien /693095849 from Huawei is informed",=
"franck.nkomot@matech-cameroun.com","486","03-06-2025 15:31:05","MATECH CMR=
"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0005172350","Bas=
tos Bir","","03-06-2025 15:29:57","03-06-2025 15:22:53","03-06-2025 16:30:5=
3","Site went down due to insufficiency of rectifiers on site  // He added =
01 Rectifier","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rec=
tifier Distribution","Site went down due to insufficiency of rectifiers on =
site  // He added 01 Rectifier","franck.nkomot@matech-cameroun.com","425","=
03-06-2025 15:29:57","MATECH CMR"
"Closed Complete","Site Down","T1557","IHS_YND_313","NOCINC0005172304","Afa=
noya","","03-06-2025 15:26:09","03-06-2025 15:16:00","03-06-2025 16:36:00",=
"Site went down because 1/3 rectifier dysfunctioning // He reset rectifiers=
","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","Site went down because 1/3 rectifier dysfunctioning // He r=
eset rectifiers","franck.nkomot@matech-cameroun.com","2534","03-06-2025 15:=
26:09","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005172300","Nko=
langaa","","03-06-2025 15:25:06","03-06-2025 15:19:46","03-06-2025 18:59:46=
","Active // No power issue on site Ubay =3D 53.2V Site on Grid. TX FME Hen=
ri (699949693/Huawei) is on site for works","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue on site Ubay =3D 53.2V Site on Grid. TX FME Henri =
(699949693/Huawei) is on site for works","franck.nkomot@matech-cameroun.com=
","321","03-06-2025 15:25:06","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005172293","Nko=
ulou Carriere carrefourt","","03-06-2025 15:24:01","03-06-2025 15:18:47","0=
3-06-2025 15:26:47","Grid outage, Site went down due to insufficiency of re=
ctifiers//Site stablilsed","Mba Lazare Herve","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","Grid outage, Site went down due to insuffic=
iency of rectifiers//Site stablilsed","franck.nkomot@matech-cameroun.com","=
315","03-06-2025 15:24:01","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005172285","Nko=
lbong","","03-06-2025 15:22:41","03-06-2025 15:16:33","03-06-2025 17:06:33"=
,"Grid fluctuations, site went down due to Gen overload (22kva//350A) // Gr=
id restoration","Delor Telezing","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid fluctuations, site went down due to Gen overload (22k=
va//350A) // Grid restoration","franck.nkomot@matech-cameroun.com","369","0=
3-06-2025 15:22:41","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005172266","O=
LAMA","","03-06-2025 15:19:44","03-06-2025 15:16:38","03-06-2025 15:37:54",=
"No power issue on site Ubaie =3D50V site on Gen The TX FME Henri (69994969=
3) from Huawei is informed.Noticed that it is a repetitve issue","Fanda Bri=
ce","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site Ubaie =3D50V site on Gen The TX FME =
Henri (699949693) from Huawei is informed.Noticed that it is a repetitve is=
sue","christelle.ngonga@matech-cameroun.com","187","03-06-2025 15:19:44","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_122","IHS_YND_230","NOCINC0005172146","M=
eyong-Meyeme","","03-06-2025 14:59:04","03-06-2025 14:55:56","03-06-2025 15=
:01:03","Site wen Down due to works, RM Willy KAMGA (699003823/Matech) was =
on site to work // End of work","TIENTCHEU NZETCHIEU GAEL","Installation Ac=
tivity","Passive","Planned Activity","Installation Activity","Site wen Down=
 due to works, RM Willy KAMGA (699003823/Matech) was on site to work // End=
 of work","gerard.tchangoue@matech-cameroun.com","189","03-06-2025 14:59:04=
","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005172103","S=
tade-Abega","","03-06-2025 14:53:16","03-06-2025 14:48:10","03-06-2025 15:2=
5:49","No power issue, site is on grid with Ubaie=3D53.4V, Lionel adjep (65=
5184876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53.4V, Lionel adjep (655184876) from Hua=
wei is informed","gerard.tchangoue@matech-cameroun.com","307","03-06-2025 1=
4:53:16","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005172094","E=
lig Edzoa","","03-06-2025 14:52:34","03-06-2025 14:47:27","03-06-2025 16:16=
:27","Grid fluctuation,Site went down because gen fails to start due to gri=
d bad voltage //Grid return","Delor Telezing","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid fluctuation,Site went dow=
n because gen fails to start due to grid bad voltage //Grid return","gerard=
.tchangoue@matech-cameroun.com","308","03-06-2025 14:52:34","MATECH CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0005172087","E=
leveur","IHS_YND_277","03-06-2025 14:50:52","03-06-2025 14:39:40","03-06-20=
25 17:51:27","No power issue on site Ubay: 53V site on Grid THE TX FME SYMP=
HORIEN (650257151) from HUAWEI is informed","Siligap Boris","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site Ubay: 53V site on Grid THE TX FME SYMPHORIEN (650257151=
) from HUAWEI is informed","gerard.tchangoue@matech-cameroun.com","673","03=
-06-2025 14:50:52","MATECH CMR"
"Closed Complete","Site Down","T0629","IHS_YND_058","NOCINC0005172063","Mvo=
lye","","03-06-2025 14:46:03","03-06-2025 14:39:53","03-06-2025 14:48:03","=
Grid outage,Site went down due to insufficiency of rectifiers // Site stabi=
lized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Grid outage,Site went down due to insufficiency of rectifiers // S=
ite stabilized","loic.noumsi@matech-cameroun.com","371","03-06-2025 14:46:0=
3","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0005172059","Ngo=
usso-Savana","","03-06-2025 14:45:35","03-06-2025 14:53:43","03-06-2025 16:=
52:43","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Site went Down because the  rectifier circuit breakers have =
tripped // He rearmed ","loic.noumsi@matech-cameroun.com","774328","03-06-2=
025 14:45:35","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005172052","Ngo=
usso Vallee","","03-06-2025 14:44:55","03-06-2025 14:53:43","03-06-2025 16:=
52:43","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Site went Down because the  rectifier circuit breakers have =
tripped // He rearmed ","loic.noumsi@matech-cameroun.com","774326","03-06-2=
025 14:44:55","MATECH CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0005172033","Mba=
lla 4","","03-06-2025 14:43:36","03-06-2025 14:53:43","03-06-2025 16:52:43"=
,"","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Site went Down because the  rectifier circuit breakers have tripp=
ed // He rearmed ","loic.noumsi@matech-cameroun.com","774328","03-06-2025 1=
4:43:36","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0005172022","Tsi=
nga village","","03-06-2025 14:42:26","03-06-2025 14:39:18","03-06-2025 14:=
59:18","Site went down due to insufficiency of rectifier caused by increase=
 in load // He reduced the load, site on grid","Delor Telezing","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down due to ins=
ufficiency of rectifier caused by increase in load // He reduced the load, =
site on grid","loic.noumsi@matech-cameroun.com","189","03-06-2025 14:42:26"=
,"MATECH CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0005172019","Ngo=
ulmekong-Nord","","03-06-2025 14:41:43","03-06-2025 14:37:46","03-06-2025 1=
7:51:27","","Siligap Boris","Cascade Outage","Active","Cascade Active","Cas=
cade Active","TTO5319357","loic.noumsi@matech-cameroun.com","9423","03-06-2=
025 14:41:43","MATECH CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0005172010","San=
ta Barbara Gottam","","03-06-2025 14:40:54","03-06-2025 14:53:43","03-06-20=
25 16:52:43","","Delor Telezing","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Site went Down because the  rectifier circuit breaker=
s have tripped // He rearmed ","loic.noumsi@matech-cameroun.com","774327","=
03-06-2025 14:40:54","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0005172008","Oko=
lo Kilombo","","03-06-2025 14:40:21","03-06-2025 14:53:43","03-06-2025 16:5=
2:43","Site went Down because the  rectifier circuit breakers have tripped =
// He rearmed ","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Site went Down because the  rectifier circuit breake=
rs have tripped // He rearmed ","loic.noumsi@matech-cameroun.com","774325",=
"03-06-2025 14:40:21","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005171618","M=
vog-Manga","","03-06-2025 13:48:28","03-06-2025 13:44:16","03-06-2025 14:55=
:16","Grid outage site went down due to PWC dysunction//He reset it and sit=
e on Gen","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Grid outage site went down due to PWC dysunction//He=
 reset it and site on Gen","loic.noumsi@matech-cameroun.com","255","03-06-2=
025 13:48:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0005171552","Obobogo"=
,"","03-06-2025 13:38:25","03-06-2025 13:00:19","03-06-2025 13:05:48","Casc=
aded Incident from TTO5318759","MINKA NICOLAS","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by Efoulan Pont which is not=
 managed by us","system","652806","03-06-2025 13:38:25","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005171549","E=
foulan","IHS_YND_155","03-06-2025 13:37:30","03-06-2025 13:00:19","03-06-20=
25 13:05:48","Site impacted by Efoulan Pont which is not managed by us","MI=
NKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failur=
e","Affected by 3rd Party Site","Site impacted by Efoulan Pont which is not=
 managed by us","loic.noumsi@matech-cameroun.com","2232","03-06-2025 13:37:=
30","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005171499","S=
ous Prefecture","","03-06-2025 13:29:17","03-06-2025 13:16:07","03-06-2025 =
13:49:00","No power issue site on Grid Ubaie =3D55.2 V, The tx Huawei Fulbe=
rt (654266068) is informed","Fanda Brice","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site o=
n Grid Ubaie =3D55.2 V, The tx Huawei Fulbert (654266068) is informed","gae=
lle.njiofack@matech-cameroun.com","791","03-06-2025 13:29:17","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005171377","T=
alla Monatele","","03-06-2025 13:05:49","03-06-2025 12:57:34","03-06-2025 1=
3:13:57","Backtracking// No power issue, site is on Grid with Ubaie=3D53V, =
Gregoir (654547479) from Huawei is informed.","Parker Tchoup","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","B=
acktracking// No power issue, site is on Grid with Ubaie=3D53V, Gregoir (65=
4547479) from Huawei is informed.","gaelle.njiofack@matech-cameroun.com","4=
96","03-06-2025 13:05:49","MATECH CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0005171037","Dra=
gage","","03-06-2025 12:11:09","03-06-2025 12:02:03","03-06-2025 12:16:03",=
"Site went down due to insufficiency of rectifiers on site // Site Stabiliz=
ead","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficiency of rectifiers on site // Site St=
abilizead","loic.noumsi@matech-cameroun.com","547","03-06-2025 12:11:09","M=
ATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0005170880","Bas=
tos-BAT","","03-06-2025 11:48:15","03-06-2025 11:44:07","03-06-2025 11:50:1=
9","Active// No power issue, site is on gen with Ubaie=3D55,2 V The Tx Fme,=
 Eloundou(652586578) from Huawei is informed","Mboua Thierry","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive// No power issue, site is on gen with Ubaie=3D55,2 V The Tx Fme, Elou=
ndou(652586578) from Huawei is informed","loic.noumsi@matech-cameroun.com",=
"249","03-06-2025 11:48:15","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005170746","Mim=
boman4","","03-06-2025 11:32:25","03-06-2025 11:27:17","03-06-2025 12:28:23=
","Grid fluctuations, site went down because Gen failed to start due to gri=
d bad voltage //He bypassed Grid and started Gen manually","Mba Lazare Herv=
e","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuations, site went down because Gen failed to start due to grid=
 bad voltage //He bypassed Grid and started Gen manually","loic.noumsi@mate=
ch-cameroun.com","310","03-06-2025 11:32:25","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005170415","Men=
dong Plateau","","03-06-2025 10:42:08","03-06-2025 10:40:59","03-06-2025 11=
:50:57","Site went down because the fuel was not reaching the GE injectors =
// he removed and purged them, Grid returned","Hyemafo Gildas","Fuel Outage=
 (Probable)","Passive","ACDG Gen","ACDG - Injector Pump","Site went down be=
cause the fuel was not reaching the GE injectors // he removed and purged t=
hem, Grid returned","loic.noumsi@matech-cameroun.com","70","03-06-2025 10:4=
2:08","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005170403","M=
ontee-Des-Soeurs","","03-06-2025 10:39:48","03-06-2025 10:36:36","03-06-202=
5 11:31:44","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) //=
 Grid returned","gaelle.njiofack@matech-cameroun.com","194","03-06-2025 10:=
39:48","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005170325","M=
vog-Ebanda","","03-06-2025 10:26:31","03-06-2025 10:20:13","03-06-2025 10:4=
1:07","Boris says that Tiencheu ( 692105769 / Epitech ) is on site for Swap=
 of Bay // End of work","Siligap Boris","Installation Activity","Passive","=
Planned Activity","Installation Activity","Boris says that Tiencheu ( 69210=
5769 / Epitech ) is on site for Swap of Bay // End of work","loic.noumsi@ma=
tech-cameroun.com","379","03-06-2025 10:26:31","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005170188","M=
vog-Ada_OCM","","03-06-2025 10:08:31","03-06-2025 10:04:23","03-06-2025 13:=
11:21","Grid Only site, No space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only sit=
e, No space to deploy MDGE // Grid returned","loic.noumsi@matech-cameroun.c=
om","250","03-06-2025 10:08:31","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005170065","A=
wae Ewonkan","","03-06-2025 09:49:17","03-06-2025 09:46:11","03-06-2025 17:=
42:37","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","gaelle.njiofack@matech-cameroun.com","187","03-06-2025 09:49:17","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0005169832","N=
GONA","","03-06-2025 09:11:39","03-06-2025 09:10:13","03-06-2025 09:14:44",=
"site went down due to Bad Grid voltage // He bypassed Grid and he started =
Gen manually","Mba Lazare Herve","Grid Supply","Passive","Grid","National G=
rid - Unstable Grid Supply Issue","site went down due to Bad Grid voltage /=
/ Grid stop manually and site on Gen","gaelle.njiofack@matech-cameroun.com"=
,"87","03-06-2025 09:11:39","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005169626","C=
rf-Nsam","","03-06-2025 08:55:05","03-06-2025 08:45:58","03-06-2025 09:25:0=
5","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","loic.noumsi@matech-cameroun.com","548","0=
3-06-2025 08:55:05","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005169533","N=
kolfon Cimencam","","03-06-2025 08:33:46","03-06-2025 08:27:37","03-06-2025=
 08:35:17","	Site is impacted by Afanoya II(Not manage by HIS)","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","Aff=
ected by 3rd Party Site","	Site is impacted by Afanoya II(Not manage by HIS=
)","gaelle.njiofack@matech-cameroun.com","370","03-06-2025 08:33:46","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005169511","Nkol-Meb=
anga","","03-06-2025 08:29:31","03-06-2025 07:41:22","03-06-2025 07:45:55",=
"Cascaded Incident from TTO5316254","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 Gen start due poor backup battery // Gen automatically started","system","=
671393","03-06-2025 08:29:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005169510","Carrefou=
r Ayissi Ele","","03-06-2025 08:29:30","03-06-2025 07:41:22","03-06-2025 07=
:45:55","Cascaded Incident from TTO5316254","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n before Gen start due poor backup battery // Gen automatically started","s=
ystem","671393","03-06-2025 08:29:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005169367","MEHANDAN=
","","03-06-2025 07:56:28","03-06-2025 02:10:59","03-06-2025 02:50:10","Cas=
caded Incident from TTO5316315","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active: No power issue on site Ubaie =3D5=
4.4V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei is info=
rme","system","691227","03-06-2025 07:56:28","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005169364","O=
dza II OCM","IHS_YND_528","03-06-2025 07:55:32","03-06-2025 02:10:59","03-0=
6-2025 02:50:10","Active: No power issue on site Ubaie =3D54.4V site on Gri=
d. The TX FME Lionnel Adhex (655184876) from Huawei is informe","Albran Byo=
rel","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active: No power issue on site Ubaie =3D54.4V site on Grid=
. The TX FME Lionnel Adhex (655184876) from Huawei is informe","gaelle.njio=
fack@matech-cameroun.com","21865","03-06-2025 07:55:32","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005169304","Saa=
","IHS_YND_810, IHS_YND_809","03-06-2025 07:44:57","03-06-2025 07:41:22","0=
3-06-2025 07:45:55","Grid outage, site went down before Gen start due poor =
backup battery // Gen automatically started","Parker Tchoup","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down before Gen start due poor backup battery // Gen automatically st=
arted","loic.noumsi@matech-cameroun.com","216","03-06-2025 07:44:57","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005169250","O=
LAMA","","03-06-2025 07:34:24","03-06-2025 07:25:15","03-06-2025 08:36:19",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue","Fanda B=
rice","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX =
FME Henri (699949693) from Huawei is informed.Noticed that it is a repetitv=
e issue","gaelle.njiofack@matech-cameroun.com","550","03-06-2025 07:34:24",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005169236","T=
alla Monatele","","03-06-2025 07:31:06","03-06-2025 00:43:31","03-06-2025 0=
1:57:02","Backtracking// No power issue, site is on Grid with Ubaie=3D53V, =
Gregoir (654547479) from Huawei is informed.","Parker Tchoup","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","B=
acktracking// No power issue, site is on Grid with Ubaie=3D53V, Gregoir (65=
4547479) from Huawei is informed.","gaelle.njiofack@matech-cameroun.com","2=
4456","03-06-2025 07:31:06","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005169225","M=
essassi 2","","03-06-2025 07:28:58","03-06-2025 07:24:34","03-06-2025 07:37=
:47","Active//No power issue Ubaie:50,51 V site on Grid, TX fme symphorien =
/650257151 from huawei is informed.","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue Ubaie:53.96 V site on Grid, TX fme symphorien /650257151 fro=
m huawei is informed.","gaelle.njiofack@matech-cameroun.com","266","03-06-2=
025 07:28:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005169153","Carrefou=
r Ayissi Ele","","03-06-2025 07:23:10","03-06-2025 03:03:34","03-06-2025 05=
:19:06","Cascaded Incident from TTO5315323","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n before Gen start due poor backup battery // Gen automatically started","s=
ystem","812011","03-06-2025 07:23:10","MATECH CMR"
"Closed Complete","Site Down","T0629","IHS_YND_058","NOCINC0005169142","Mvo=
lye","","03-06-2025 07:21:08","03-06-2025 07:15:01","03-06-2025 08:03:26","=
site went down due to rectifier dysfunctioning caused by lightning//we Remo=
ved rectifier faulty and site on grid","MINKA NICOLAS","Force Majeure","Nat=
ural Disaster","Thunderstrike","Equipment Damaged","site went down due to r=
ectifier dysfonctioning causing by lightning//we Removed rectifier faulty a=
nd site on grid","ludivine.ngamaleu@ihstowers.com","368","03-06-2025 07:21:=
08","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005169080","S=
tade-Abega","","03-06-2025 07:07:53","03-06-2025 06:58:43","03-06-2025 08:2=
8:21","No power issue on site and site impacted by Ekounou II that is not m=
anaged by us ","Mba Lazare Herve","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","Affected by 3rd Party Site","No power issue on sit=
e and site impacted by Ekounou II that is not managed by us ","loic.noumsi@=
matech-cameroun.com","551","03-06-2025 07:07:53","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005169055","Djo=
nassi-Yde","","03-06-2025 06:58:33","03-06-2025 06:52:25","03-06-2025 11:52=
:43","Grid outage, site went down due 01 rectifier faulty // He replaced it=
, site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Grid outage, site went down due 01 rectifier faulty // =
He replaced it, site on Grid","loic.noumsi@matech-cameroun.com","368","03-0=
6-2025 06:58:33","MATECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0005169037","N=
koa Ayos","","03-06-2025 06:54:51","03-06-2025 05:12:01","03-06-2025 07:49:=
36","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid fluctuation , Site went down due to grid bad voltage and n=
o rcp on site //He bypassed the Grid, site on GEN","loic.noumsi@matech-came=
roun.com","680220","03-06-2025 06:54:51","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005168977","N=
koabang2","","03-06-2025 06:41:00","03-06-2025 06:37:54","03-06-2025 06:40:=
39","Grid outage, site went down due to gen overload (22KVA, 330A)// Site s=
tabilisation","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, site went down due to gen overload (22KVA, 33=
0A)// Site stabilisation","loic.noumsi@matech-cameroun.com","188","03-06-20=
25 06:41:00","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005168763","Odz=
a II OCM","","03-06-2025 05:25:16","03-06-2025 05:21:09","03-06-2025 05:29:=
09","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction // Site stabilised","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, site went down b=
ecause gen failed to start due to PWC ZTE malfunction // Site stabilised","=
gerard.tchangoue@matech-cameroun.com","248","03-06-2025 05:25:16","MATECH C=
MR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005168758","GSO=
","IHS_YND_067","03-06-2025 05:21:23","03-06-2025 05:12:01","03-06-2025 07:=
49:36","Grid fluctuation , Site went down due to grid bad voltage and no rc=
p on site //He bypassed the Grid, site on GEN","MINKA NICOLAS","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion , Site went down due to grid bad voltage and no rcp on site //He bypass=
ed the Grid, site on GEN","gerard.tchangoue@matech-cameroun.com","563","03-=
06-2025 05:21:23","MATECH CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0005168684","MES=
SAME NDONGO 1162","","03-06-2025 04:53:51","03-06-2025 04:08:45","03-06-202=
5 05:57:34","Grid outage,site went down because gen failed to start due to =
Gen card Faulty// He started Gen manually","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down =
because gen failed to start due to Gen card Faulty// He started Gen manuall=
y","gerard.tchangoue@matech-cameroun.com","2706","03-06-2025 04:53:51","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005168523","N=
koabang Ebolmedjock","","03-06-2025 03:46:33","03-06-2025 03:37:15","03-06-=
2025 03:51:30","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","gerard.tchangoue@m=
atech-cameroun.com","559","03-06-2025 03:46:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0005168501","Mbankolo=
 petit paris","","03-06-2025 03:33:03","03-06-2025 03:23:50","03-06-2025 05=
:16:58","Cascaded Incident from TTO5315380","Mboua Thierry","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage Site wwent dow=
n because Gen overload (18kva and 215(A)// He reduce the load of site","sys=
tem","1218281","03-06-2025 03:33:03","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0005168498","AFE=
ME NORD","IHS_YND_808","03-06-2025 03:32:18","03-06-2025 03:23:50","03-06-2=
025 05:16:58","Grid outage Site wwent down because Gen overload (18kva and =
215(A)// He reduce the load of site","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage Site wwent down=
 because Gen overload (18kva and 215(A)// He reduce the load of site","gera=
rd.tchangoue@matech-cameroun.com","509","03-06-2025 03:32:18","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005168444","Saa=
","IHS_YND_810, IHS_YND_809","03-06-2025 03:17:43","03-06-2025 02:58:34","0=
3-06-2025 05:19:06","Grid outage, site went down before Gen start due poor =
backup battery // Gen automatically started","Parker Tchoup","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down before Gen start due poor backup battery // Gen automatically st=
arted","gerard.tchangoue@matech-cameroun.com","2797","03-06-2025 03:17:43",=
"MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005168440","Nko=
l-Mebanga","","03-06-2025 03:14:55","03-06-2025 03:03:34","03-06-2025 05:19=
:06","cascade outage","Parker Tchoup","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","cascade outage","gerard.tchangoue@matech-camerou=
n.com","812011","03-06-2025 03:14:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0005168389","Leboudi"=
,"","03-06-2025 02:51:26","03-06-2025 02:24:50","03-06-2025 04:05:52","Casc=
aded Incident from TTO5315252","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down =
because Gen failed to start due to PWC ZTE disfunction// He reset it, Site =
on Gen","system","690146","03-06-2025 02:51:26","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005168315","Djo=
nassi-Yde","","03-06-2025 02:22:26","03-06-2025 02:16:19","03-06-2025 06:25=
:30","Access issue due to landlord and Site went down due to rectidfier dys=
functionning//He removed rectifier faulty","Fabrice Pouakam","Access Denial=
","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Ac=
cess issue due to landlord and Site went down due to rectidfier dysfunction=
ning//He removed rectifier faulty","gerard.tchangoue@matech-cameroun.com","=
368","03-06-2025 02:22:26","MATECH CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0005168286","Nko=
lafeme","IHS_YND_309","03-06-2025 02:06:21","03-06-2025 01:59:05","03-06-20=
25 04:13:36","Grid outage, Site went down because Gen failed to start due t=
o PWC ZTE disfunction// He reset it, Site on Gen","TIENTCHEU NZETCHIEU GAEL=
","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","G=
rid outage, Site went down because Gen failed to start due to PWC ZTE disfu=
nction// He reset it, Site on Gen","gerard.tchangoue@matech-cameroun.com","=
437","03-06-2025 02:06:21","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005168107","Ebo=
go","","03-06-2025 01:08:49","03-06-2025 00:59:33","03-06-2025 02:57:47","A=
ctive// No Power issue on site Ubaie 56V site on Grid, Julien /693095849 fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issue =
on site Ubaie 56V site on Grid, Julien /693095849 from Huawei is informed",=
"gerard.tchangoue@matech-cameroun.com","557","03-06-2025 01:08:49","MATECH =
CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005168030","Nko=
g-Edzen","","03-06-2025 00:47:32","03-06-2025 00:40:27","03-06-2025 00:50:2=
7","Active//No power issue on site, Site on Grid Ubay =3D 56.4V The Tx Fme =
Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Grid Ubay =3D 56.4V The Tx Fme Greg=
oire (654547479) from Huawei is informed.","gerard.tchangoue@matech-camerou=
n.com","426","03-06-2025 00:47:32","MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0005167982","Mes=
sassi okolo","","03-06-2025 00:27:05","03-06-2025 00:17:40","03-06-2025 00:=
30:46","Grid outage , site went down before Gen started due to poor battery=
 backup // Gen Manually started","Fabrice Pouakam","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage , site went=
 down before Gen started due to poor battery backup // Gen Manually started=
","gerard.tchangoue@matech-cameroun.com","566","03-06-2025 00:27:05","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005167969","Carrefou=
rt Nkomo","","03-06-2025 00:24:26","03-06-2025 00:14:30","03-06-2025 05:07:=
23","Cascaded Incident from TTO5314788","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went=
 down because Gen failed to start due to grid bad voltage // Grid power sta=
bilized","system","697897","03-06-2025 00:24:26","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005167960","N=
komo","IHS_YND_174","03-06-2025 00:22:37","03-06-2025 00:14:30","03-06-2025=
 05:10:49","Grid fluctuation, site went down because Gen failed to start du=
e to grid bad voltage // Grid power stabilized","Mba Lazare Herve","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation, site went down because Gen failed to start due to grid bad voltage=
 // Grid power stabilized","gerard.tchangoue@matech-cameroun.com","488","03=
-06-2025 00:22:37","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005167843","Ebo=
go","","02-06-2025 23:54:18","02-06-2025 23:45:11","03-06-2025 00:20:55","G=
rid outage, site went down before Gen start due poor backup battery // Gen =
automatically started","Siligap Boris","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
Gen start due poor backup battery // Gen automatically started","gerard.tch=
angoue@matech-cameroun.com","548","02-06-2025 23:54:18","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005167836","M=
ontee-Des-Soeurs","","02-06-2025 23:53:24","02-06-2025 23:42:04","02-06-202=
5 23:49:04","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A) // G=
rid return","kouoh.jean@ihstowers.com","682","02-06-2025 23:53:24","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0005167830","Crf-Mban=
kolo-IHS","","02-06-2025 23:52:23","02-06-2025 23:28:32","02-06-2025 23:53:=
32","Cascaded Incident from TTO5314583","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluuctuation, Site went D=
own due to poor backup (waiting Grid return) // Grid return","system","7006=
12","02-06-2025 23:52:23","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0005167808","Eto=
 koss Yde","","02-06-2025 23:44:17","02-06-2025 23:28:05","02-06-2025 23:48=
:05","FME Brice","Fanda Brice","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, Site went down before Gen start due to poo=
r backup // Grid returned","gerard.tchangoue@matech-cameroun.com","700639",=
"02-06-2025 23:44:17","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005167802","ELO=
UMDEM CARRIERE 2","","02-06-2025 23:43:09","02-06-2025 23:33:56","03-06-202=
5 03:10:52","ACTIVE//no power issue Ubaie:54.2V site on Gen, TX fme symphor=
ien /650257151 from huawei is informed","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//n=
o power issue Ubaie:54.2V site on Gen, TX fme symphorien /650257151 from hu=
awei is informed","gerard.tchangoue@matech-cameroun.com","555","02-06-2025 =
23:43:09","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005167796","N=
koabang2","","02-06-2025 23:41:18","02-06-2025 23:32:08","03-06-2025 04:18:=
36","Site went down due to Grid bad voltage and Gen overload (22KVA, 330A),=
 SS Blaise IHS is informed // He bypassed Grid and started Gen manually aft=
er reducing load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Site went down due to Grid bad voltage and Gen overloa=
d (22KVA, 330A), SS Blaise IHS is informed // He bypassed Grid and started =
Gen manually after reducing load","gerard.tchangoue@matech-cameroun.com","5=
51","02-06-2025 23:41:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0005167786","Jean Ves=
pa 2","","02-06-2025 23:36:26","02-06-2025 23:28:32","02-06-2025 23:53:32",=
"Cascaded Incident from TTO5314583","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluuctuation, Site went Down =
due to poor backup (waiting Grid return) // Grid return","system","700613",=
"02-06-2025 23:36:26","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0005167779","J=
-Vespa","IHS_YND_574, IHS_YND_544","02-06-2025 23:34:40","02-06-2025 23:28:=
32","02-06-2025 23:53:32","Grid fluuctuation, Site went Down due to poor ba=
ckup (waiting Grid return) // Grid return","Mboua Thierry","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid fluuctuati=
on, Site went Down due to poor backup (waiting Grid return) // Grid return"=
,"gerard.tchangoue@matech-cameroun.com","369","02-06-2025 23:34:40","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005167775","M=
EFOU ASSI","IHS_YND_737","02-06-2025 23:33:13","02-06-2025 23:28:05","02-06=
-2025 23:48:05","Grid outage, Site went down before Gen start due to poor b=
ackup // Grid returned","Fanda Brice","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Grid returned","gerard.tchangoue@matech-came=
roun.com","310","02-06-2025 23:33:13","MATECH CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0005167770","E=
mombo 2","","02-06-2025 23:31:55","02-06-2025 23:25:49","02-06-2025 23:45:4=
9","Active// No power issue on site ;site on Grid with Ubaie=3D54.4 V The T=
x Technician from Huawei Lionnel//694693436 is informed","MINKA NICOLAS","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active// No power issue on site ;site on Grid with Ubaie=3D54.4 V=
 The Tx Technician from Huawei Lionnel//694693436 is informed","gerard.tcha=
ngoue@matech-cameroun.com","367","02-06-2025 23:31:55","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005167753","S=
tade-Abega","","02-06-2025 23:28:24","02-06-2025 23:19:15","03-06-2025 02:2=
2:05","No pwer issus, site is on grid with Ubaie=3D53.4V, Lionel adjep(6551=
84876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pwer issu=
s, site is on grid with Ubaie=3D53.4V, Lionel adjep(655184876) from Huawei =
is informed","gerard.tchangoue@matech-cameroun.com","550","02-06-2025 23:28=
:24","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005167746","Men=
dong Plateau","","02-06-2025 23:26:52","02-06-2025 23:19:45","02-06-2025 23=
:54:14","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and Eneo return","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, site went down =
because gen start and stopped with high temp alarm // He added water and En=
eo return","gerard.tchangoue@matech-cameroun.com","427","02-06-2025 23:26:5=
2","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005167743","Mba=
nkolo petit paris","","02-06-2025 23:25:19","02-06-2025 23:16:10","02-06-20=
25 23:29:10","Active: no power issue, site is on grid with Ubaie=3D54.1V, M=
ohamadou((691144435) from Huawei is informed,","Mboua Thierry","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active: no power issue, site is on grid with Ubaie=3D54.1V, Mohamadou((6911=
44435) from Huawei is informed,","gerard.tchangoue@matech-cameroun.com","55=
0","02-06-2025 23:25:19","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0005167726","AFE=
ME NORD","","02-06-2025 23:22:42","02-06-2025 23:15:37","02-06-2025 23:29:3=
7","Site went down because gen fails to start due to grid bad voltage // Si=
te stabilized","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Site went down because gen fails t=
o start due to grid bad voltage // Site stabilized","gerard.tchangoue@matec=
h-cameroun.com","426","02-06-2025 23:22:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0005167723","HOPITAL =
DE LA CAISSE","IHS_YND_024","02-06-2025 23:22:04","02-06-2025 23:09:03","02=
-06-2025 23:29:03","No power issue site on Grid with U=3D56V. The FME TX Ar=
mand NGUETSA (699949553) from huawei is informed","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue site on Grid with U=3D56V. The FME TX Armand NGUETSA (69=
9949553) from huawei is informed","system","781","02-06-2025 23:22:04","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0005167724","Garbati =
building","","02-06-2025 23:22:04","02-06-2025 23:09:03","02-06-2025 23:29:=
03","Cascaded Incident from TTO5314500","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue site on Grid with=
 U=3D56V. The FME TX Armand NGUETSA (699949553) from huawei is informed","s=
ystem","701770","02-06-2025 23:22:04","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005167719","Man=
guiers Dispensaire","","02-06-2025 23:19:58","02-06-2025 23:10:46","03-06-2=
025 09:52:28","Grid outage, site went down due to insufficiency of rectifie=
rs // he added 02 rectifers, site on GEN","Fabrice Pouakam","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module","Grid outage, site went down d=
ue to insufficiency of rectifiers // he added 02 rectifers, site on GEN","g=
erard.tchangoue@matech-cameroun.com","553","02-06-2025 23:19:58","MATECH CM=
R"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005167703","Mam=
ch Building","","02-06-2025 23:17:11","02-06-2025 23:09:03","03-06-2025 00:=
31:08","Grid outage .gen failed to start due to air take//We purged and gen=
 manually started","Mboua Thierry","Fuel Outage (Probable)","Passive","ACDG=
 Gen","ACDG - Air Intake","Grid outage .gen failed to start due to air take=
//We purged and gen manually started","gerard.tchangoue@matech-cameroun.com=
","489","02-06-2025 23:17:11","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005167683","Mok=
olo Yaounde","","02-06-2025 23:16:02","02-06-2025 23:06:45","02-06-2025 23:=
29:45","Active // No power issue Ubay: 54.4 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.4 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","5=
58","02-06-2025 23:16:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0005167675","H-Franco=
 New","","02-06-2025 23:14:44","02-06-2025 23:06:50","02-06-2025 23:14:50",=
"Cascaded Incident from TTO5314466","Delor Telezing","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue, site is on Grid with=
 Ubaie =3D52.5V. The TX Armand Nguetsa (699949553) from Huawei is informed"=
,"system","701894","02-06-2025 23:14:44","MATECH CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0005167671","D=
joungolo","IHS_YND_711","02-06-2025 23:13:02","02-06-2025 23:06:50","02-06-=
2025 23:14:50","No power issue, site is on Grid with Ubaie =3D52.5V. The TX=
 Armand Nguetsa (699949553) from Huawei is informed","Mboua Thierry","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue, site is on Grid with Ubaie =3D52.5V. The TX Armand Ng=
uetsa (699949553) from Huawei is informed","gerard.tchangoue@matech-camerou=
n.com","373","02-06-2025 23:13:02","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005167664","S=
atcom","","02-06-2025 23:11:20","02-06-2025 23:05:09","03-06-2025 02:45:09"=
,"No power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144=
412) of huawei is informe","Delor Telezing","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144412) of huawei is inf=
orme","gerard.tchangoue@matech-cameroun.com","372","02-06-2025 23:11:20","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0005167654","A=
v-Germaine","","02-06-2025 23:09:56","02-06-2025 22:59:59","02-06-2025 23:1=
1:59","Grid only site, no space on site to deploy MGE // Grid returned","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid on=
ly site, no space on site to deploy MGE // Grid returned","gerard.tchangoue=
@matech-cameroun.com","598","02-06-2025 23:09:56","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0005167635","Aba=
ng","IHS_YND_289","02-06-2025 23:04:26","02-06-2025 22:55:13","02-06-2025 2=
3:05:13","Active//No power issue site on Grid with U=3D55.5V ,The FME TX He=
nri (691145055) from Huawei is informed","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue site on Grid with U=3D55.5V ,The FME TX Henri (69114505=
5) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","554","0=
2-06-2025 23:04:26","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005167601","Nko=
langaa","","02-06-2025 22:54:54","02-06-2025 22:55:13","02-06-2025 23:05:13=
","Site impacted by Abang","Mba Lazare Herve","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active//No power issue site on Grid with U=
=3D55.5V ,The FME TX Henri (691145055) from Huawei is informed","gerard.tch=
angoue@matech-cameroun.com","702580","02-06-2025 22:54:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005167592","MEHANDAN=
","","02-06-2025 22:54:06","02-06-2025 22:46:47","03-06-2025 02:09:29","Cas=
caded Incident from TTO5314342","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to CB(gen, grid and=
 cb rectifier) disjuncted causing by lithgning // CBs put back on, But the =
site site remained down at OCM; TX FME Lionel/655184876 from Huawei is info=
rmed","system","703077","02-06-2025 22:54:06","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005167564","O=
dza II OCM","IHS_YND_528","02-06-2025 22:51:55","02-06-2025 22:46:47","03-0=
6-2025 02:09:29","Site went down due to CB(gen, grid and cb rectifier) disj=
uncted causing by lithgning // CBs put back on, But the site site remained =
down at OCM; TX FME Lionel/655184876 from Huawei is informed","Albran Byore=
l","Force Majeure","Natural Disaster","Thunderstrike","Equipment Damaged","=
Site went down due to CB(gen, grid and cb rectifier) disjuncted causing by =
lithgning // CBs put back on, But the site site remained down at OCM; TX FM=
E Lionel/655184876 from Huawei is informed","gerard.tchangoue@matech-camero=
un.com","310","02-06-2025 22:51:55","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005167523","O=
LAMA","","02-06-2025 22:39:42","02-06-2025 22:31:43","02-06-2025 22:43:11",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue","Fanda B=
rice","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX =
FME Henri (699949693) from Huawei is informed.Noticed that it is a repetitv=
e issue","gerard.tchangoue@matech-cameroun.com","480","02-06-2025 22:39:42"=
,"MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005167417","Mvo=
g Betsi Hospital","","02-06-2025 22:17:53","02-06-2025 22:12:46","02-06-202=
5 22:18:54","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","loic.noumsi@matech-cameroun.com",=
"307","02-06-2025 22:17:53","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005166867","S=
ous Prefecture","","02-06-2025 20:48:02","02-06-2025 20:41:49","02-06-2025 =
20:52:27","No power issue site on Grid Ubaie =3D55.4 V, The tx Huawei Fulbe=
rt (654266068) is informed","Fanda Brice","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site o=
n Grid Ubaie =3D55.4 V, The tx Huawei Fulbert (654266068) is informed","chr=
istelle.ngonga@matech-cameroun.com","374","02-06-2025 20:48:02","MATECH CMR=
"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005166858","M=
eyo","","02-06-2025 20:47:01","02-06-2025 20:44:54","02-06-2025 20:54:17","=
Grid outage site went down due to Gen overload (17KVA, 260A) SS HIS Felix Z=
ambe is informed and confirmed// He reduced load","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went do=
wn due to Gen overload (17KVA, 260A) SS HIS Felix Zambe is informed and con=
firmed// He reduced load","christelle.ngonga@matech-cameroun.com","128","02=
-06-2025 20:47:01","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005166735","ELO=
UMDEM CARRIERE","","02-06-2025 20:29:18","02-06-2025 20:20:54","02-06-2025 =
21:42:16","Grid outage, Site went down due to Grid fluctuations and Poor ba=
ckup battery // Grid stabilised","Fanda Brice","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage, Site went down due=
 to Grid fluctuations and Poor backup battery // Grid stabilised","loic.nou=
msi@matech-cameroun.com","506","02-06-2025 20:29:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005166727","ELOUMDEM=
 CARRIERE 2","","02-06-2025 20:27:36","02-06-2025 20:21:52","02-06-2025 20:=
27:26","Cascaded Incident from TTO5313404","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid returned","system","705501","02-=
06-2025 20:27:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005166726","Eto koss=
 Yde","","02-06-2025 20:27:36","02-06-2025 20:21:52","02-06-2025 20:27:26",=
"Cascaded Incident from TTO5313404","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Grid returned","system","705500","02-06-2025=
 20:27:36","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005166715","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","02-06-2025 20:26:00","02-06-2025 20:21=
:52","02-06-2025 20:27:26","Grid outage, Site went down before Gen start du=
e to poor backup // Grid returned","Fanda Brice","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid returned","loic.noumsi@matech-ca=
meroun.com","250","02-06-2025 20:26:00","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005166705","B=
arriere","","02-06-2025 20:24:19","02-06-2025 20:19:09","02-06-2025 20:24:4=
8","No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/=
Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
bay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is informed.","chris=
telle.ngonga@matech-cameroun.com","311","02-06-2025 20:24:19","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005166559","MBA=
LNGONG LYCEE","","02-06-2025 20:01:55","02-06-2025 19:56:43","02-06-2025 21=
:20:59","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid returned","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","loic.noumsi@ma=
tech-cameroun.com","313","02-06-2025 20:01:55","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005166549","E=
ssomba","","02-06-2025 20:00:03","02-06-2025 19:58:55","02-06-2025 21:40:44=
","Site went down because PWC overload // Site stabilised,","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Site went down because PWC overload // Site stabilised,","christelle.ngong=
a@matech-cameroun.com","70","02-06-2025 20:00:03","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005166548","E=
lig-Edzoa","","02-06-2025 19:59:09","02-06-2025 19:55:54","02-06-2025 20:06=
:43","Grid only site , No space to deploy MDGE // Grid returned","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site=
 , No space to deploy MDGE // Grid returned","christelle.ngonga@matech-came=
roun.com","197","02-06-2025 19:59:09","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005166363","E=
lig Edzoa","","02-06-2025 19:31:07","02-06-2025 19:28:59","02-06-2025 20:24=
:01","Grid outage, Site went down due to grid fluctuations on site // Grid =
stabilised","Delor Telezing","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Grid outage, Site went down due to grid fluctua=
tions on site // Grid stabilised","christelle.ngonga@matech-cameroun.com","=
130","02-06-2025 19:31:07","MATECH CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0005166034","N=
gousso OCM","","02-06-2025 18:46:37","02-06-2025 18:44:29","02-06-2025 19:2=
0:47","Grid outage, site went down because Gen failed to start due to Grid =
bad voltage (lack of 2 phases) // He did bridge on the good phase, site on =
Grid","Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid outage, site went down because Gen failed to star=
t due to Grid bad voltage (lack of 2 phases) // He did bridge on the good p=
hase, site on Grid","christelle.ngonga@matech-cameroun.com","129","02-06-20=
25 18:46:37","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005165825","A=
wae Ewonkan","","02-06-2025 18:07:09","02-06-2025 18:06:00","02-06-2025 21:=
48:24","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","christelle.ngonga@matech-cameroun.com","71","02-06-2025 18:07:09","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005165817","N=
yom OCM","","02-06-2025 18:06:27","02-06-2025 18:04:20","02-06-2025 18:41:3=
7","Grid fluctuation, site down because gen fails to start due to grid fluc=
tuation // Gen manually started","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuation, site=
 down because gen fails to start due to grid fluctuation // Gen manually st=
arted","christelle.ngonga@matech-cameroun.com","129","02-06-2025 18:06:27",=
"MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0005165758","Nlo=
ngkak","","02-06-2025 18:01:42","02-06-2025 17:54:33","02-06-2025 18:47:13"=
,"Grid outage,site went down due to Grid fluctuations // Grid stabilised","=
Delor Telezing","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid outage,site went down due to Grid fluctuations // Grid =
stabilised","loic.noumsi@matech-cameroun.com","430","02-06-2025 18:01:42","=
MATECH CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0005165744","M=
atomb","","02-06-2025 18:00:12","02-06-2025 17:54:49","02-06-2025 18:14:14"=
," Poor battery backup ,Site down due to PM work ((draining)  ) // End of w=
ork.","Kemeni Franklin","Equipment Replacement","Passive","ACDG Gen","ACDG =
- Top Gasket"," Poor battery backup ,Site down due to PM work ((draining)  =
) // End of work.","christelle.ngonga@matech-cameroun.com","324","02-06-202=
5 18:00:12","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005165703","N=
koabang2","","02-06-2025 17:54:12","02-06-2025 17:50:05","02-06-2025 18:55:=
50","Grid outage, site went down due to gen overload (22KVA, 330A)// Site s=
tabilisation","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage, site went down due to gen overload (22KVA, 33=
0A)// Site stabilisation","christelle.ngonga@matech-cameroun.com","249","02=
-06-2025 17:54:12","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005165673","C=
rf-Nsam","","02-06-2025 17:48:58","02-06-2025 17:48:54","02-06-2025 17:57:0=
5","No power issue on site Ubaie =3D56.4V site on Grid The TX FME Henri (69=
9949693) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site Ubaie =3D56.4V site on Grid The TX FME Henri (699949693) from Hua=
wei is informed","christelle.ngonga@matech-cameroun.com","5","02-06-2025 17=
:48:58","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005165672","M=
vog-Ada_OCM","","02-06-2025 17:48:07","02-06-2025 17:46:00","02-06-2025 18:=
12:42","Grid Only site, No space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only sit=
e, No space to deploy MDGE // Grid returned","christelle.ngonga@matech-came=
roun.com","128","02-06-2025 17:48:07","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005165654","S=
atcom","","02-06-2025 17:45:19","02-06-2025 17:42:12","02-06-2025 17:52:40"=
,"No power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144=
412) of huawei is informe","Delor Telezing","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144412) of huawei is inf=
orme","christelle.ngonga@matech-cameroun.com","188","02-06-2025 17:45:19","=
MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005165617","Lad=
a I Yde","","02-06-2025 17:42:07","02-06-2025 17:39:02","02-06-2025 19:23:0=
9","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypassed the Grid and Gen manually started","Mba=
 Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation site went down because Gen and started and s=
topped due to Grid bad voltage // He bypassed the Grid and Gen manually sta=
rted","loic.noumsi@matech-cameroun.com","186","02-06-2025 17:42:07","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005165476","N=
kolfon Cimencam","","02-06-2025 17:20:08","02-06-2025 17:17:55","02-06-2025=
 17:20:25","Site is impacted by Afanoya II(Not manage by HIS)","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","Site is impacted by Afanoya II(Not manage by HIS)"=
,"christelle.ngonga@matech-cameroun.com","134","02-06-2025 17:20:08","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005165290","N=
koabang Ebolmedjock","","02-06-2025 16:57:29","02-06-2025 16:54:27","02-06-=
2025 17:23:32","Site impacted by Nkolmesseng-Abom wich is not manage by IHS=
","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipmen=
t Failure","Affected by 3rd Party Site","Site impacted by Nkolmesseng-Abom =
wich is not manage by IHS","christelle.ngonga@matech-cameroun.com","183","0=
2-06-2025 16:57:29","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005165094","O=
LAMA","","02-06-2025 16:28:22","02-06-2025 16:23:16","02-06-2025 16:29:06",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue","Fanda B=
rice","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX =
FME Henri (699949693) from Huawei is informed.Noticed that it is a repetitv=
e issue","christelle.ngonga@matech-cameroun.com","308","02-06-2025 16:28:22=
","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005165057","N=
YOM 2 IHS","","02-06-2025 16:22:21","02-06-2025 16:20:13","02-06-2025 19:03=
:48","No power issue Ubaie:50.2 V site on Grid, site up without interventio=
n. TX fme symphorien /650257151 from huawei is informed.","Fabrice Pouakam"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue Ubaie:50.2 V site on Grid, site up without inte=
rvention. TX fme symphorien /650257151 from huawei is informed.","christell=
e.ngonga@matech-cameroun.com","130","02-06-2025 16:22:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005165050","MEHANDAN=
","","02-06-2025 16:21:23","02-06-2025 16:18:09","02-06-2025 16:26:11","Cas=
caded Incident from TTO5311565","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
719728","02-06-2025 16:21:23","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005165044","O=
dza II OCM","IHS_YND_528","02-06-2025 16:20:19","02-06-2025 16:18:09","02-0=
6-2025 16:26:28","Grid Outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid Outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","christelle.ngonga@matech-cameroun.com","133","02-06-2025 16:20=
:19","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005165003","T=
alla Monatele","","02-06-2025 16:11:40","02-06-2025 16:10:31","02-06-2025 1=
6:14:44","No power issue, site is on grid with Ubaie=3D54.7V, Gregoir (6545=
47479) from Huawei is informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue,=
 site is on grid with Ubaie=3D54.7V, Gregoir (654547479) from Huawei is inf=
ormed","christelle.ngonga@matech-cameroun.com","70","02-06-2025 16:11:40","=
MATECH CMR"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0005164926","Ngo=
g Mapubi","","02-06-2025 15:57:27","02-06-2025 15:50:18","02-06-2025 16:11:=
09","Grid outage, site went down due to poor battery backup // Grid returne=
d","Kemeni Franklin","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","Grid outage, site went down due to poor battery backup //=
 Grid returned","loic.noumsi@matech-cameroun.com","429","02-06-2025 15:57:2=
7","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005164889","GSO=
","","02-06-2025 15:54:00","02-06-2025 15:51:50","02-06-2025 16:03:02","Gri=
d fluctuation , Site went down due to grid bad voltage and no rcp on site /=
/He bypassed the Grid, site on GEN","MINKA NICOLAS","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation , Site =
went down due to grid bad voltage and no rcp on site //He bypassed the Grid=
, site on GEN","loic.noumsi@matech-cameroun.com","131","02-06-2025 15:54:00=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005164590","MEHANDAN=
","","02-06-2025 15:19:44","02-06-2025 15:16:24","02-06-2025 15:32:41","Cas=
caded Incident from TTO5310982","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
723319","02-06-2025 15:19:44","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005164503","O=
dza II OCM","IHS_YND_528","02-06-2025 15:18:32","02-06-2025 15:16:24","02-0=
6-2025 15:32:41","Grid Outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid Outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","christelle.ngonga@matech-cameroun.com","130","02-06-2025 15:18=
:32","MATECH CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0005164394","Ema=
na","","02-06-2025 15:01:45","02-06-2025 14:54:36","02-06-2025 15:04:27","A=
ctive//No power issue on site, Ubaie =3D 54.5V. TX Fme Eloundou (693212405)=
 from HUAWEI is informed","Fabrice Pouakam","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site, Ubaie =3D 54.5V. TX Fme Eloundou (693212405) from HUAWEI is in=
formed","loic.noumsi@matech-cameroun.com","430","02-06-2025 15:01:45","MATE=
CH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005164356","Eto=
ug ebe biscuiterie","","02-06-2025 14:58:49","02-06-2025 14:53:39","02-06-2=
025 15:27:44","Grid fluctuation, site went down because Gen failed to start=
 due to Grid bad voltage and no RCP on site//He did bridge on the 02 good p=
hases","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid fluctuation, site went down because Gen failed =
to start due to Grid bad voltage and no RCP on site//He did bridge on the 0=
2 good phases","loic.noumsi@matech-cameroun.com","311","02-06-2025 14:58:49=
","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005164313","M=
essassi 2","","02-06-2025 14:56:38","02-06-2025 14:56:33","02-06-2025 14:57=
:55","No power issue Ubaie:53.96 V site on Grid, TX fme symphorien /6502571=
51 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=
baie:53.96 V site on Grid, TX fme symphorien /650257151 from huawei is info=
rmed.","christelle.ngonga@matech-cameroun.com","7","02-06-2025 14:56:38","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0005164259","B=
otmakak","","02-06-2025 14:45:57","02-06-2025 14:41:49","02-06-2025 14:48:2=
7","No power issue, Site on Grid Ubai=3D 53.8 V, The Tx Etienne (695033981/=
Huawei) is informed","Kemeni Franklin","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, Site on =
Grid Ubai=3D 53.8 V, The Tx Etienne (695033981/Huawei) is informed","christ=
elle.ngonga@matech-cameroun.com","248","02-06-2025 14:45:57","MATECH CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0005164221","Bye=
massi Carrefour","","02-06-2025 14:40:54","02-06-2025 14:36:21","02-06-2025=
 14:54:35","Grid outage, site went down due to Grid fluctuactions and Poor =
backup battery on site // Grid stabilised","Paul BIBOUM","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site wen=
t down due to Grid fluctuactions and Poor backup battery on site // Grid st=
abilised","loic.noumsi@matech-cameroun.com","274","02-06-2025 14:40:54","MA=
TECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005164201","Nsa=
m Sofavinc","IHS_YND_732","02-06-2025 14:35:57","02-06-2025 14:32:50","02-0=
6-2025 15:29:09","Site went down due to insufficiency of rectifiers on site=
 // He reduced load","MINKA NICOLAS","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to insufficiency of rectifiers on=
 site // He reduced load","christelle.ngonga@matech-cameroun.com","187","02=
-06-2025 14:35:57","MATECH CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0005164197","Nsa=
m escale LP","","02-06-2025 14:35:04","02-06-2025 14:32:50","02-06-2025 15:=
29:09","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"Site went down due to insufficiency of rectifiers on site // He reduced l=
oad","christelle.ngonga@matech-cameroun.com","725859","02-06-2025 14:35:04"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_546","IHS_YND_419","NOCINC0005163992","N=
gog Mapubi","","02-06-2025 13:58:09","02-06-2025 13:50:21","02-06-2025 15:4=
2:59","Grid outage.site went down due to grid conctactor dysfunctionned//We=
 manually activated grid contactor and site on grid","Kemeni Franklin","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage.si=
te went down due to grid conctactor dysfunctionned//We manually activated g=
rid contactor and site on grid","edwige.kapawo@matech-cameroun.com","469","=
02-06-2025 13:58:09","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0005163976","Oko=
lo Kilombo","","02-06-2025 13:55:34","02-06-2025 13:51:46","02-06-2025 14:0=
5:09","Grid outage,site went down because Gen failed to start due to Grid f=
luctuations// Grid stabilised","Fabrice Pouakam","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Grid outage,site went down =
because Gen failed to start due to Grid fluctuations// Grid stabilised","fr=
anck.nkomot@matech-cameroun.com","228","02-06-2025 13:55:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005163927","Messassi=
 okolo","","02-06-2025 13:47:11","02-06-2025 13:38:29","02-06-2025 14:06:48=
","Cascaded Incident from TTO5310350","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (Gen Noise) // Grid returned","system","729=
047","02-06-2025 13:47:11","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005163924","E=
MANA BILICK CITY","IHS_YND_279","02-06-2025 13:46:36","02-06-2025 13:38:29"=
,"02-06-2025 14:12:10","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid returned","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage, site down b=
ecause site behaves as Grid only site (Gen Noise) // Grid returned","edwige=
.kapawo@matech-cameroun.com","489","02-06-2025 13:46:36","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005163921","Mes=
sassi 2","","02-06-2025 13:46:09","02-06-2025 13:36:04","02-06-2025 13:47:0=
4","Grid outage site went down because Gen failed to start due to poor Batt=
ery backup// GEN automatically started","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site=
 went down because Gen failed to start due to poor Battery backup// GEN aut=
omatically started","franck.nkomot@matech-cameroun.com","607","02-06-2025 1=
3:46:09","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005163909","N=
kolbong","","02-06-2025 13:45:11","02-06-2025 13:35:59","02-06-2025 14:06:2=
8","Grid fluctuations, site went down due to Gen overload (22kva//350A) // =
Grid restoration","Delor Telezing","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid fluctuations, site went down due to Gen overload (2=
2kva//350A) // Grid restoration","edwige.kapawo@matech-cameroun.com","553",=
"02-06-2025 13:45:11","MATECH CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0005163907","N=
R-Omnisport","","02-06-2025 13:44:21","02-06-2025 13:38:09","02-06-2025 13:=
49:12","Wrong ticket","Delor Telezing","Incorrectly Logged Tickets","Error"=
,"Error","Error","Wrong ticket","edwige.kapawo@matech-cameroun.com","373","=
02-06-2025 13:44:21","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005163880","Eto=
udi","","02-06-2025 13:39:01","02-06-2025 13:35:50","02-06-2025 13:37:50","=
Grid fluctuation ,site went down because Gen fails to start due to grid bad=
 voltage //Grid stabilisation","Fabrice Pouakam","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Grid fluctuation ,site went=
 down because Gen fails to start due to grid bad voltage //Grid stabilisati=
on","mouliom.anselme@matech-cameroun.com","192","02-06-2025 13:39:01","MATE=
CH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005163537","Mfa=
ndena","","02-06-2025 12:50:08","30-05-2025 12:56:42","30-05-2025 16:10:50"=
,"BACKTRACKING. Site went down because 01/02 rectifiers dysfunctioning // H=
e reset rectifiers","Delor Telezing","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","BACKTRACKING. Site went down because 01/02 rectifier=
s dysfunctioning // He reset rectifiers","franck.nkomot@matech-cameroun.com=
","258806","02-06-2025 12:50:08","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005163507","ESS=
OS OASIS 1111","","02-06-2025 12:47:32","30-05-2025 10:16:42","30-05-2025 1=
0:18:04","BACKTRACKING. Grid outage, Site went down because Gen overload (1=
7kva, 250A) // GRid power return","Siligap Boris","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","BACKTRACKING. Grid outage, Site went down=
 because Gen overload (17kva, 250A) // GRid power return","franck.nkomot@ma=
tech-cameroun.com","268250","02-06-2025 12:47:32","MATECH CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0005163496","Ngo=
usso MTN","","02-06-2025 12:44:25","30-05-2025 12:52:18","30-05-2025 12:55:=
58","BACKTRACKING. Grid only site, no space to deploy MGE // Grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","BACKT=
RACKING. Grid only site, no space to deploy MGE // Grid return","franck.nko=
mot@matech-cameroun.com","258727","02-06-2025 12:44:25","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0005163475","NTE=
MASSI","","02-06-2025 12:39:29","30-05-2025 12:52:14","30-05-2025 12:55:58"=
,"BACKTRACKING. Grid outage, Site down due to Rectifiers issue // site stab=
ilised","Delor Telezing","Grid Supply","Passive","Grid","National Grid - Gr=
id Outage Issue","Grid outage, Site down due to Rectifiers issue // site st=
abilised","franck.nkomot@matech-cameroun.com","258435","02-06-2025 12:39:29=
","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005163436","OTE=
LE MTN","","02-06-2025 12:32:30","30-05-2025 11:13:08","30-05-2025 11:18:01=
","BACKTRACKING. Grid outage,site went because Gen  started and stopped  du=
e to alarm low oil pressure //He added oil and manually started with an ext=
ernal battery","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG =
- Load Breaker","BACKTRACKING. Grid outage,site went because Gen  started a=
nd stopped  due to alarm low oil pressure //He added oil and manually start=
ed with an external battery","franck.nkomot@matech-cameroun.com","263962","=
02-06-2025 12:32:30","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005163269","Odz=
a Minkan IHS","","02-06-2025 12:27:19","30-05-2025 12:48:57","30-05-2025 13=
:06:15","BACKTRACKING. Grid outage, site went down due to gen overload(20KV=
A, 240A),SS Felix IHS //He reduced the load an site on Gen","Albran Byorel"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, si=
te went down due to gen overload(20KVA, 240A),SS Felix IHS //He reduiced th=
e load an site on Gen","franck.nkomot@matech-cameroun.com","257902","02-06-=
2025 12:27:19","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005163238","Djo=
nassi-Yde","","02-06-2025 12:16:36","30-05-2025 10:57:27","30-05-2025 11:06=
:36","BACKTRACKING. site went down due to insufficient of rectifiers//He re=
set rectifier","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","=
Rectifier Module","BACKTRACKING. site went down due to insufficient of rect=
ifiers//He reset rectifier","franck.nkomot@matech-cameroun.com","263949","0=
2-06-2025 12:16:36","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005163117","Mok=
olo Yaounde","","02-06-2025 11:52:26","30-05-2025 10:13:12","30-05-2025 10:=
25:11","Bactracking  Active // No power issue Ubay: 54.4 V site on grid. Th=
e Tx FME Eloundou Bertrand (693212405) from Huawei is informed","","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Bactracking  Active // No power issue Ubay: 54.4 V site on grid. The Tx=
 FME Eloundou Bertrand (693212405) from Huawei is informed","mouliom.anselm=
e@matech-cameroun.com","265154","02-06-2025 11:52:26","MATECH CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0005162859","Nsa=
m escale LP","","02-06-2025 11:23:10","02-06-2025 11:17:06","02-06-2025 12:=
07:06","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"Grid fluctuation, site went down because Gen started and stopped to start=
 due to grid bad voltage// He bypassed the grid and started Gen manually	",=
"franck.nkomot@matech-cameroun.com","737276","02-06-2025 11:23:10","MATECH =
CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005162849","O=
LAMA","","02-06-2025 11:21:02","02-06-2025 11:18:02","02-06-2025 11:37:31",=
"Active // No power issue on site Ubaie =3D54.9V site on Gen The TX FME Hen=
ri (699949693) from Huawei is informed.Noticed that it is a repetitve issue=
","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active // No power issue on site Ubaie =3D54.9V=
 site on Gen The TX FME Henri (699949693) from Huawei is informed.Noticed t=
hat it is a repetitve issue","edwige.kapawo@matech-cameroun.com","181","02-=
06-2025 11:21:02","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005162845","Nsa=
m Sofavinc","IHS_YND_732","02-06-2025 11:20:11","02-06-2025 11:17:06","02-0=
6-2025 12:07:06","Grid fluctuation, site went down because Gen started and =
stopped to start due to grid bad voltage// He bypassed the grid and started=
 Gen manually	","MINKA NICOLAS","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Grid fluctuation, site went down because Gen=
 started and stopped to start due to grid bad voltage// He bypassed the gri=
d and started Gen manually	","franck.nkomot@matech-cameroun.com","186","02-=
06-2025 11:20:11","MATECH CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0005162740","N=
R-Omnisport","","02-06-2025 10:55:37","02-06-2025 10:51:30","02-06-2025 11:=
36:30","Grid outage, site went down because gen ran until fuel shortage // =
Refuelling done","Delor Telezing","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage, site went down because gen ran until fuel shortage //=
 Refuelling done","edwige.kapawo@matech-cameroun.com","248","02-06-2025 10:=
55:37","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0005162444","Ngo=
um","","02-06-2025 10:22:09","02-06-2025 10:07:00","02-06-2025 11:39:00","S=
ite went down because our FME was on site for plan work (emptying)// Plan w=
ork done","Parker Tchoup","Installation Activity","Passive","Planned Activi=
ty","Installation Activity","Site went down because our FME was on site for=
 plan work (emptying)","franck.nkomot@matech-cameroun.com","911","02-06-202=
5 10:22:09","MATECH CMR"
"Closed Complete","Warning","T3220","IHS_YND_765","NOCINC0005162260","MBALN=
GONG LYCEE","","02-06-2025 10:12:08","","","Site went down because Gen stop=
ped due to overload(9kva, 130A) SS IHS Felix Zambe is informed and confirme=
d //He reduced the loaad and manually started the Gen","Fanda Brice","Warni=
ng","Warning","POWER","Warning - ACDG - Overload","Site went down because G=
en stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informed and c=
onfirmed //He reduced the loaad and manually started the Gen","franck.nkomo=
t@matech-cameroun.com","1427","02-06-2025 10:12:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005162045","MEHANDAN=
","","02-06-2025 09:57:30","02-06-2025 09:50:48","02-06-2025 10:04:23","Cas=
caded Incident from TTO5308310","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // He reset controller and gen=
 manually started","system","736208","02-06-2025 09:57:30","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005162039","O=
dza II OCM","IHS_YND_528","02-06-2025 09:55:09","02-06-2025 09:50:48","02-0=
6-2025 10:04:23","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // He reset controller and gen manually started",=
"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","Grid outage, site went down because gen failed to start due to=
 PWC ZTE malfunction // He reset controller and gen manually started","edwi=
ge.kapawo@matech-cameroun.com","263","02-06-2025 09:55:09","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005161988","C=
rf-Nsam","","02-06-2025 09:43:59","02-06-2025 09:42:53","02-06-2025 09:43:5=
3","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","franck.nkomot@matech-cameroun.com","67","=
02-06-2025 09:43:59","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005161968","Acc=
acia New","","02-06-2025 09:39:41","02-06-2025 09:37:31","02-06-2025 14:04:=
23","Site went down due to dysfunctionment of CB (100 A) in DC BOX MTN // H=
e replaced it with CB (125A), site on Grid ","","Equipment Repair","Passive=
","Control Panel","Faulty Circuit Breaker","Site went down due to disjuncti=
on of CB (100 A) in DC BOX MTN // He replaced it with CB (125A), site on Gr=
id ","franck.nkomot@matech-cameroun.com","131","02-06-2025 09:39:41","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005161881","O=
LAMA","","02-06-2025 09:24:04","31-05-2025 01:03:37","31-05-2025 16:25:42",=
"BACKTRACKING. No power issue, Site on Gen with U=3D54.7V.The TX FME Henri =
(699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","BACKTRACKING=
. No power issue, Site on Gen with U=3D54.7V.The TX FME Henri (699949693) f=
rom Huawei is informed","franck.nkomot@matech-cameroun.com","202827","02-06=
-2025 09:24:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005161872","MEHANDAN=
","","02-06-2025 09:21:39","02-06-2025 09:12:45","02-06-2025 09:15:58","Cas=
caded Incident from TTO5308097","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use gen failed to start due to PWC ZTE malfunction // Site stabilised","sys=
tem","738432","02-06-2025 09:21:39","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005161837","O=
dza II OCM","IHS_YND_528","02-06-2025 09:15:59","02-06-2025 09:12:45","02-0=
6-2025 09:15:58","Grid fluctuations, site went down because gen failed to s=
tart due to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uations, site went down because gen failed to start due to PWC ZTE malfunct=
ion // Site stabilised","edwige.kapawo@matech-cameroun.com","196","02-06-20=
25 09:15:59","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005161811","Nta=
ba","","02-06-2025 09:09:43","02-06-2025 09:01:32","02-06-2025 09:09:32","G=
rid outage, site went down because gen failed to start due to Pwc ZTE dysfu=
nction // Grid return","Delor Telezing","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Grid outage, site went down because ge=
n failed to start due to Pwc ZTE dysfunction // Grid return","franck.nkomot=
@matech-cameroun.com","493","02-06-2025 09:09:43","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005161637","C=
rf-Nsam","","02-06-2025 08:37:15","02-06-2025 08:35:07","02-06-2025 08:42:1=
3","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","edwige.kapawo@matech-cameroun.com","130",=
"02-06-2025 08:37:15","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005161476","E=
toug ebe Meweulo","","02-06-2025 08:04:25","02-06-2025 07:59:16","02-06-202=
5 10:03:16","Grid fluctuation site went down because Gen started and stoppe=
d due to Grid bad voltage // He bypass Grid and put Site on Gen","Hyemafo G=
ildas","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation site went down because Gen started and stopped due t=
o Grid bad voltage // He bypass Grid and put Site on Gen","edwige.kapawo@ma=
tech-cameroun.com","311","02-06-2025 08:04:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005161429","Nsam esc=
ale LP","","02-06-2025 07:52:01","02-06-2025 07:49:28","02-06-2025 08:41:04=
","Cascaded Incident from TTO5307641","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage.site went down due to gen stopped=
 by neighbour //Gen manuanualy started by our FME","system","743339","02-06=
-2025 07:52:01","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005161428","Nsa=
m Sofavinc","IHS_YND_732","02-06-2025 07:51:37","02-06-2025 07:49:28","02-0=
6-2025 08:41:04","Grid outage.site went down due to gen stopped by neighbou=
r //Gen manuanualy started by our FME","MINKA NICOLAS","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage.site went down due =
to gen stopped by neighbour //Gen manuanualy started by our FME","edwige.ka=
pawo@matech-cameroun.com","130","02-06-2025 07:51:37","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005161426","Efo=
ulan MTN","","02-06-2025 07:50:46","02-06-2025 07:47:37","02-06-2025 09:09:=
09","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction // He reset controller and gen manually started","MINKA NICOLA=
S","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Grid outage, site went down because gen failed to start due to PWC ZTE malf=
unction // He reset controller and gen manually started","edwige.kapawo@mat=
ech-cameroun.com","189","02-06-2025 07:50:46","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005161421","E=
toug ebe Meweulo","","02-06-2025 07:49:32","02-06-2025 07:47:59","02-06-202=
5 07:48:46","Grid fluctuations // Grid return","Hyemafo Gildas","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid fluctuations =
// Grid return","edwige.kapawo@matech-cameroun.com","94","02-06-2025 07:49:=
32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005161370","ELOUMDEM=
 CARRIERE 2","","02-06-2025 07:36:10","02-06-2025 07:26:59","02-06-2025 07:=
32:42","Cascaded Incident from TTO5307559","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid return","system","744667","02-06=
-2025 07:36:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005161369","Eto koss=
 Yde","","02-06-2025 07:36:10","02-06-2025 07:26:59","02-06-2025 07:32:42",=
"Cascaded Incident from TTO5307559","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Grid return","system","744667","02-06-2025 0=
7:36:10","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005161367","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","02-06-2025 07:35:15","02-06-2025 07:26=
:59","02-06-2025 07:32:42","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","Fanda Brice","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor backup // Grid return","franck.nkomot@matech-=
cameroun.com","498","02-06-2025 07:35:15","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005161271","M=
essassi 2","","02-06-2025 07:10:49","02-06-2025 07:06:37","02-06-2025 07:07=
:37","No power issue Ubaie:53.82 V site on Grid, TX fme symphorien /6502571=
51 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=
baie:53.82 V site on Grid, TX fme symphorien /650257151 from huawei is info=
rmed.","franck.nkomot@matech-cameroun.com","254","02-06-2025 07:10:49","MAT=
ECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005161115","Mfa=
ndena","","02-06-2025 06:31:39","02-06-2025 06:30:33","02-06-2025 08:28:03"=
,"Site went down because 01/02 rectifiers disfunctionning // He reset recti=
fiers","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down because 01/02 rectifiers disfunctionning // He res=
et rectifiers","franck.nkomot@matech-cameroun.com","67","02-06-2025 06:31:3=
9","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005161071","N=
kolbong","","02-06-2025 06:15:35","02-06-2025 06:12:12","02-06-2025 06:14:5=
7","Grid fluctuations, site went down due to Gen overload (22kva//350A) // =
Grid restoration","Delor Telezing","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid fluctuations, site went down due to Gen overload (2=
2kva//350A) // Grid restoration","franck.nkomot@matech-cameroun.com","204",=
"02-06-2025 06:15:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005161001","Carrefou=
r Ayissi Ele","","02-06-2025 05:50:11","02-06-2025 01:14:31","02-06-2025 05=
:37:03","Cascaded Incident from TTO5306398","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n because gen stopped with alarm ""high temp"" // He cleaned the radiator ,=
 added water and manually start the Gen","system","766762","02-06-2025 05:5=
0:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005161002","Nkol-Meb=
anga","","02-06-2025 05:50:11","02-06-2025 01:14:31","02-06-2025 05:37:03",=
"Cascaded Incident from TTO5306398","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen stopped with alarm ""high temp"" // He cleaned the radiator , added w=
ater and manually start the Gen","system","766762","02-06-2025 05:50:11","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005160732","T=
alla Monatele","","02-06-2025 03:44:44","01-06-2025 21:35:27","02-06-2025 0=
5:00:41","BACK TRACKING","Parker Tchoup","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site i=
s on grid with Ubaie=3D54.9V, Gregoir (654547479) from Huawei is informed",=
"vanel.mbiada@matech-cameroun.com","22157","02-06-2025 03:44:44","MATECH CM=
R"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005160334","S=
aa","IHS_YND_810, IHS_YND_809","02-06-2025 01:20:40","02-06-2025 01:14:31",=
"02-06-2025 05:37:03","Grid outage, site went down because gen stopped with=
 alarm ""high temp"" // He cleaned the radiator , added water and manually =
start the Gen","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACD=
G - High Engine Temp - Coolant Level Issue","Grid outage, site went down be=
cause gen stopped with alarm ""high temp"" // He cleaned the radiator , add=
ed water and manually start the Gen","vanel.mbiada@matech-cameroun.com","37=
0","02-06-2025 01:20:40","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0005160164","E=
lig Edzoa","","02-06-2025 00:29:06","02-06-2025 00:26:34","02-06-2025 00:30=
:43","Grid fluctuation,Site went down because gen fails to start due to gri=
d bad voltage //Grid return","Delor Telezing","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid fluctuation,Site went dow=
n because gen fails to start due to grid bad voltage //Grid return","vanel.=
mbiada@matech-cameroun.com","153","02-06-2025 00:29:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005160031","Carrefou=
r Ayissi Ele","","01-06-2025 23:42:11","01-06-2025 23:24:42","02-06-2025 00=
:12:11","Cascaded Incident from TTO5305999","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","	Grid outage, site went do=
wn because gen stopped with alarm ""high temp"" // He added water and manua=
lly start the Gen	","system","773265","01-06-2025 23:42:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005160029","Nkol-Meb=
anga","","01-06-2025 23:41:40","01-06-2025 23:24:42","02-06-2025 00:12:11",=
"Cascaded Incident from TTO5305999","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","	Grid outage, site went down becau=
se gen stopped with alarm ""high temp"" // He added water and manually star=
t the Gen	","system","773265","01-06-2025 23:41:40","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005159985","S=
aa","IHS_YND_810, IHS_YND_809","01-06-2025 23:29:29","01-06-2025 23:24:42",=
"02-06-2025 00:19:12","	Grid outage, site went down because gen stopped wit=
h alarm ""high temp"" // He added water and manually start the Gen	","Parke=
r Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","	Grid outage, site went down because gen stopped wi=
th alarm ""high temp"" // He added water and manually start the Gen	","vane=
l.mbiada@matech-cameroun.com","288","01-06-2025 23:29:29","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005159903","N=
kolfon Cimencam","","01-06-2025 23:03:58","01-06-2025 22:59:46","02-06-2025=
 05:15:54","No power issue on site U=3D54,5v site on Gen The TX fme George(=
697461814) from huawei is informed. Noticed that site is impacted by Afanoy=
a II(Not manage by HIS)","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","Affected by 3rd Party Site","No power issu=
e on site U=3D54,5v site on Gen The TX fme George(697461814) from huawei is=
 informed. Noticed that site is impacted by Afanoya II(Not manage by HIS)",=
"vanel.mbiada@matech-cameroun.com","253","01-06-2025 23:03:58","MATECH CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0005159667","Omn=
isport-Rail","","01-06-2025 22:12:02","01-06-2025 22:09:24","01-06-2025 22:=
55:23","Grid outage,Site went down due to PSC3 Controller Faulty// He start=
ed the Gen manually","Delor Telezing","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage,Site went down due to PSC3 Controlle=
r Faulty// He started the Gen manually","franck.nkomot@matech-cameroun.com"=
,"159","01-06-2025 22:12:02","MATECH CMR"
"Closed Complete","Site Down","T0638","IHS_YND_318","NOCINC0005159604","SOA=
 University","","01-06-2025 22:01:22","01-06-2025 21:54:51","01-06-2025 22:=
55:54","Grid outage, site went down because gen start and stopped with high=
 temp alarm // he added water and manually start the gen","Siligap Boris","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, site went down because gen start and stopped with=
 high temp alarm // he added water and manually start the gen","franck.nkom=
ot@matech-cameroun.com","392","01-06-2025 22:01:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005159603","Elig-Edz=
oa","","01-06-2025 22:01:09","01-06-2025 21:40:06","02-06-2025 07:20:56","C=
ascaded Incident from TTO5305465","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen failed to=
 start due to Pwc ZTE dysfunction // Grid return","system","1263","01-06-20=
25 22:01:09","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005159513","Nta=
ba","","01-06-2025 21:45:29","01-06-2025 21:40:06","02-06-2025 07:26:06","(=
Access  Issue during the night  due to landlord )  Grid outage, site went d=
own because gen failed to start due to Pwc ZTE dysfunction // Grid return",=
"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","(Access  Issue during the night  due to landlord )  Grid outa=
ge, site went down because gen failed to start due to Pwc ZTE dysfunction /=
/ Grid returnGrid return","franck.nkomot@matech-cameroun.com","325","01-06-=
2025 21:45:29","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005159423","OBA=
M NGOLA OCM","","01-06-2025 21:27:41","01-06-2025 21:25:21","01-06-2025 21:=
40:21","Grid outage, Site went down due to Grid bad voltage and Gen failed =
to start due to c // Gen manually started","MINKA NICOLAS","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid outage, Site=
 went down due to Grid bad voltage and Gen failed to start due to c // Gen =
manually started","franck.nkomot@matech-cameroun.com","141","01-06-2025 21:=
27:41","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005159256","Acc=
acia New","","01-06-2025 20:57:37","01-06-2025 20:33:26","01-06-2025 22:09:=
26","Grid outage, no space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy MGE // Grid return","franck.nkomot@matech-cameroun.com","1453","0=
1-06-2025 20:57:37","MATECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0005159188","ODZ=
A CITE MBIA","","01-06-2025 20:47:22","01-06-2025 20:44:14","01-06-2025 21:=
27:14","Grid outage,DG started and stopped due with alarm ""oil pressure""(=
 unprouven Alarm ) // He reset DG card and started DG manually","Albran Byo=
rel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage,DG started and stopped due with alarm ""oil pressure""( unprouven Ala=
rm ) // He reset DG card and started DG manually","franck.nkomot@matech-cam=
eroun.com","189","01-06-2025 20:47:22","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005159034","Lad=
a I Yde","","01-06-2025 20:18:38","01-06-2025 20:17:31","01-06-2025 20:18:3=
1","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // Site stabilized","Mba Lazare Herve","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation=
 site went down because Gen and started and stopped due to Grid bad voltage=
 // Site stabilized","franck.nkomot@matech-cameroun.com","68","01-06-2025 2=
0:18:38","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005158995","M=
EHANDAN","","01-06-2025 20:11:22","01-06-2025 20:09:03","01-06-2025 20:57:0=
3","Grid fluctuation,Site went down because GEN failed to start due to grid=
 bad voltage(lack of 01 phase)// He did a bridge on the good phase, site on=
 Grid","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation,Site went down because GEN failed to=
 start due to grid bad voltage(lack of 01 phase)// He did a bridge on the g=
ood phase, site on Grid","gerard.tchangoue@matech-cameroun.com","141","01-0=
6-2025 20:11:22","MATECH CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0005158908","HOP=
ITAL DE LA CAISSE","","01-06-2025 19:53:06","01-06-2025 19:49:52","01-06-20=
25 19:53:52","No power issue site on Grid with U=3D56V. The FME TX Armand N=
GUETSA (699949553) from huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue site on Grid with U=3D56V. The FME TX Armand NGUETSA (69994955=
3) from huawei is informed","franck.nkomot@matech-cameroun.com","194","01-0=
6-2025 19:53:06","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0005158882","Nlo=
ngkak","","01-06-2025 19:49:25","01-06-2025 19:48:19","01-06-2025 20:00:19"=
,"Grid outage, Site down due to poor battery backup // Gen start automatica=
lly","Delor Telezing","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, Site down due to poor battery backup //=
 Gen start automatically","franck.nkomot@matech-cameroun.com","67","01-06-2=
025 19:49:25","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005158865","Nko=
abang2","","01-06-2025 19:46:52","01-06-2025 19:42:43","01-06-2025 20:07:43=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed //He reduced load","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to g=
en overload (22KVA, 330A), SS Blaise IHS is informed //He reduced load","fr=
anck.nkomot@matech-cameroun.com","271","01-06-2025 19:46:52","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005158828","S=
atcom","","01-06-2025 19:39:47","01-06-2025 19:36:36","01-06-2025 19:43:54"=
,"No power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144=
412) of huawei is informe	","Delor Telezing","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144412) of huawei is in=
forme	","gerard.tchangoue@matech-cameroun.com","192","01-06-2025 19:39:47",=
"MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005158753","Ebo=
go","","01-06-2025 19:29:50","01-06-2025 19:28:44","01-06-2025 19:33:44","G=
rid outage, site went down before Gen start due poor backup battery // Gen =
automatically started","Siligap Boris","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
Gen start due poor backup battery // Gen automatically started","franck.nko=
mot@matech-cameroun.com","67","01-06-2025 19:29:50","MATECH CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0005158727","Nya=
hoo","","01-06-2025 19:26:14","01-06-2025 19:24:08","01-06-2025 19:40:08","=
Active//No power issue on site U=3D53,3V site on Gen and The FME TX Gregoir=
e From huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue on site U=3D53,3V site on Gen and The FME TX Gregoire From hu=
awei is informed","franck.nkomot@matech-cameroun.com","127","01-06-2025 19:=
26:14","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005158659","Nko=
lbong","","01-06-2025 19:13:01","01-06-2025 19:07:44","01-06-2025 19:31:44"=
,"Grid outage, site went down due to Gen overload (22kva//350A) // Grid res=
toration","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, site went down due to Gen overload (22kva//350A) //=
 Grid restoration","franck.nkomot@matech-cameroun.com","318","01-06-2025 19=
:13:01","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005158164","M=
essassi 2","","01-06-2025 17:50:01","01-06-2025 17:44:35","01-06-2025 17:53=
:06","No power issue Ubaie:53.9 V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:53.9 V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","gerard.tchangoue@matech-cameroun.com","328","01-06-2025 17:50:01","MA=
TECH CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0005158145","Nya=
hoo","","01-06-2025 17:45:40","01-06-2025 17:41:30","01-06-2025 18:01:30","=
Grid fluctuation, Site went down because gen fails to start due to grid bad=
 voltage,no rcp// He bypassed the Grid and site on Gen","TIENTCHEU NZETCHIE=
U GAEL","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, Site went down because gen fails to start due to g=
rid bad voltage,no rcp// He bypassed the Grid and site on Gen","gerard.tcha=
ngoue@matech-cameroun.com","251","01-06-2025 17:45:40","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005158047","T=
alla Monatele","","01-06-2025 17:29:08","01-06-2025 17:27:56","01-06-2025 1=
7:35:51","No power issue, site is on grid with Ubaie=3D54.9V, Gregoir (6545=
47479) from Huawei is informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue,=
 site is on grid with Ubaie=3D54.9V, Gregoir (654547479) from Huawei is inf=
ormed","gerard.tchangoue@matech-cameroun.com","73","01-06-2025 17:29:08","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005157988","E=
ssomba","","01-06-2025 17:14:21","01-06-2025 17:11:43","01-06-2025 17:32:38=
","Site went down because PWC overload // Site stabilised,","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Site went down because PWC overload // Site stabilised,","gerard.tchangoue=
@matech-cameroun.com","159","01-06-2025 17:14:21","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005157606","M=
essassi 2","","01-06-2025 16:01:20","01-06-2025 15:57:09","01-06-2025 16:52=
:09","Grid outage site went down because Gen failed to start due to poor Ba=
ttery backup// GEN automatically started","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down beca=
use Gen failed to start due to poor Battery backup// GEN automatically star=
ted","gerard.tchangoue@matech-cameroun.com","253","01-06-2025 16:01:20","MA=
TECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005157251","Nko=
lbong","","01-06-2025 15:10:12","01-06-2025 15:02:06","01-06-2025 15:10:06"=
,"Grid outage, site went down due to Gen overload (22kva//350A) // Grid res=
toration","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, site went down due to Gen overload (22kva//350A) //=
 Grid restoration","franck.nkomot@matech-cameroun.com","487","01-06-2025 15=
:10:12","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005157191","M=
essassi 2","","01-06-2025 15:03:37","01-06-2025 15:02:22","01-06-2025 15:10=
:28","Grid outage site went down because Gen failed to start due to poor Ba=
ttery backup// GEN automatically started	","Fabrice Pouakam","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage s=
ite went down because Gen failed to start due to poor Battery backup// GEN =
automatically started	","gerard.tchangoue@matech-cameroun.com","77","01-06-=
2025 15:03:37","MATECH CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0005157156","Sim=
bock Maetur","","01-06-2025 14:57:14","01-06-2025 14:55:34","01-06-2025 16:=
12:34","Site went down do to insufficiency of rectifiers // Our FME Gildas =
was on site to add one rectifier. Site stabilized","Hyemafo Gildas","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site went down do to =
insufficiency of rectifiers // Our FME Gildas was on site to add one rectif=
ier. Site stabilized","franck.nkomot@matech-cameroun.com","101","01-06-2025=
 14:57:14","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005157143","O=
LAMA","","01-06-2025 14:54:02","01-06-2025 14:47:56","01-06-2025 17:28:26",=
"No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (6999=
49693) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubaie =3D54.9V site on Grid. The TX FME Henri (699949693) from Huawei=
 is informed","franck.nkomot@matech-cameroun.com","368","01-06-2025 14:54:0=
2","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005156996","M=
essassi 2","","01-06-2025 14:33:38","01-06-2025 14:27:30","01-06-2025 14:30=
:30","No power issue Ubaie:54.1 V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:54.1 V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","franck.nkomot@matech-cameroun.com","370","01-06-2025 14:33:38","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005156671","C=
rf-Nsam","","01-06-2025 13:48:40","01-06-2025 13:46:26","01-06-2025 16:56:3=
2","Active//No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","christelle.ngonga@matech-cameroun.com","1=
36","01-06-2025 13:48:40","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005156649","Nko=
abang Alembe","","01-06-2025 13:46:46","01-06-2025 13:44:39","01-06-2025 14=
:36:39","site went down due to insufficiency of rectifiers IHS SS Alphonse =
is informed//site stabilized","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","site went down due to insufficiency of r=
ectifiers IHS SS Alphonse is informed//site stabilized","edwige.kapawo@mate=
ch-cameroun.com","127","01-06-2025 13:46:46","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0005156634","ETO=
UDI Entree du palais","","01-06-2025 13:43:29","01-06-2025 13:41:21","01-06=
-2025 17:01:21","Site went down due to plan work (Brice (673923777/ Boiteco=
m) was on site for swap PWC) // End of work","Fabrice Pouakam","Installatio=
n Activity","Passive","Planned Activity","Installation Activity","Site went=
 down due to plan work (Brice (673923777/ Boitecom) was on site for swap PW=
C) // End of work","edwige.kapawo@matech-cameroun.com","129","01-06-2025 13=
:43:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005156583","SOA VILL=
AGE","","01-06-2025 13:35:11","01-06-2025 13:30:26","01-06-2025 13:34:57","=
Cascaded Incident from TTO5302197","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // He added water and manually =
start the gen","system","1239448","01-06-2025 13:35:11","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005156540","Djo=
nassi-Yde","","01-06-2025 13:31:24","01-06-2025 13:28:15","01-06-2025 14:30=
:15","site went down due to insufficient of rectifiers//He reset rectifier"=
,"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","site went down due to insufficient of rectifiers//He reset =
rectifier","edwige.kapawo@matech-cameroun.com","189","01-06-2025 13:31:24",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005156533","S=
OA TOWN","IHS_YND_323","01-06-2025 13:29:32","01-06-2025 13:27:26","01-06-2=
025 13:34:57","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // He added water and manually start the gen","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Co=
olant Level Issue","Grid outage, site went down because gen start and stopp=
ed with high temp alarm // He added water and manually start the gen","chri=
stelle.ngonga@matech-cameroun.com","127","01-06-2025 13:29:32","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005156326","Jou=
vence Mbenda","","01-06-2025 12:55:11","01-06-2025 12:50:00","01-06-2025 13=
:02:42","Grid Outage, Site went Down before gen started due to high temp al=
arm on Gen // Grid return","Hyemafo Gildas","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid Outage, Site went Down before gen sta=
rted due to high temp alarm on Gen // Grid return","edwige.kapawo@matech-ca=
meroun.com","312","01-06-2025 12:55:11","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005156305","ELO=
UMDEM CARRIERE 2","","01-06-2025 12:50:38","01-06-2025 12:36:52","01-06-202=
5 12:53:52","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, Site went down before Gen start due to poor =
backup // Grid return","edwige.kapawo@matech-cameroun.com","805145","01-06-=
2025 12:50:38","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005156210","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","01-06-2025 12:39:08","01-06-2025 12:36=
:52","01-06-2025 12:53:52","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","Fanda Brice","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor backup // Grid return","edwige.kapawo@matech-=
cameroun.com","138","01-06-2025 12:39:08","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0005156197","Eto=
 koss Yde","","01-06-2025 12:38:05","01-06-2025 12:36:52","01-06-2025 12:53=
:52","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, Site went down before Gen start due to poor backup =
// Grid return","edwige.kapawo@matech-cameroun.com","805144","01-06-2025 12=
:38:05","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005156187","Nom=
ayos montee Meche","","01-06-2025 12:37:03","01-06-2025 12:30:51","01-06-20=
25 12:56:25","Grid outage, site went down before Gen started due to poor ba=
ckup battery // Grid returned","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen started due to poor backup battery // Grid returned","edwige.kapa=
wo@matech-cameroun.com","451","01-06-2025 12:37:03","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005156169","Nsa=
m Sofavinc","IHS_YND_732","01-06-2025 12:36:04","01-06-2025 12:31:55","01-0=
6-2025 12:37:38","Grid Outage, Site went down before Gen start due to poor =
backup // Gen Started Automatically","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site wen=
t down before Gen start due to poor backup // Gen Started Automatically","e=
dwige.kapawo@matech-cameroun.com","250","01-06-2025 12:36:04","MATECH CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0005156140","Nsa=
m escale LP","","01-06-2025 12:34:45","01-06-2025 12:31:55","01-06-2025 12:=
37:38","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"Grid Outage, Site went down before Gen start due to poor backup // Gen St=
arted Automatically","edwige.kapawo@matech-cameroun.com","805435","01-06-20=
25 12:34:45","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005156133","SIM=
BOCK BONAMBAPE","","01-06-2025 12:33:41","01-06-2025 12:31:29","01-06-2025 =
12:35:48","Grid Outage, Site went down before Gen start due to poor backup =
// Gen Started Automatically","Hyemafo Gildas","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid Outage, Site went down=
 before Gen start due to poor backup // Gen Started Automatically","edwige.=
kapawo@matech-cameroun.com","133","01-06-2025 12:33:41","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0005155858","N=
kolangaa","","01-06-2025 11:53:50","01-06-2025 11:50:42","01-06-2025 16:03:=
41","Active // No power issue on site Ubay =3D 53.4V Site on Grid. TX FME H=
enri (699949693/Huawei) is on site for works","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue on site Ubay =3D 53.4V Site on Grid. TX FME Henr=
i (699949693/Huawei) is on site for works","christelle.ngonga@matech-camero=
un.com","189","01-06-2025 11:53:50","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005155853","Nko=
mo stade","","01-06-2025 11:52:37","01-06-2025 11:46:17","01-06-2025 11:54:=
30","Grid outage, Site went down before Gen start due to poor backup/ // Ge=
n automatically started","Mba Lazare Herve","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup/ // Gen automatically started","edwige.ka=
pawo@matech-cameroun.com","381","01-06-2025 11:52:37","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005155636","N=
gousso-Savana","IHS_YND_561","01-06-2025 11:04:37","01-06-2025 11:00:28","0=
1-06-2025 11:50:15","No power issue, site is on grid with Ubaie=3D52.7V, Sy=
mphorien(650257151) from Huawei is informed ","Siligap Boris","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue, site is on grid with Ubaie=3D52.7V, Symphorien(650257151) fr=
om Huawei is informed ","christelle.ngonga@matech-cameroun.com","250","01-0=
6-2025 11:04:37","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005155633","F=
OUGEROLE","","01-06-2025 11:03:51","01-06-2025 11:00:28","01-06-2025 11:50:=
15","","Siligap Boris","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue, site is on grid with Ubaie=3D52.7V, Symphorien(650=
257151) from Huawei is informed ","christelle.ngonga@matech-cameroun.com","=
810768","01-06-2025 11:03:51","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005155588","M=
essassi 2","","01-06-2025 10:58:41","01-06-2025 10:57:34","01-06-2025 11:59=
:05","No power issue Ubaie:54.1 V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:54.1 V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","christelle.ngonga@matech-cameroun.com","69","01-06-2025 10:58:41","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005155586","E=
ssomba","","01-06-2025 10:57:48","01-06-2025 10:56:41","01-06-2025 11:00:58=
","Site went down because 03/06 rectifiers dysfunctionned //Site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down because 03/06 rectifiers dysfunctionned //Site stabil=
ised","christelle.ngonga@matech-cameroun.com","69","01-06-2025 10:57:48","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005155543","M=
essassi 2","","01-06-2025 10:53:18","01-06-2025 10:49:10","01-06-2025 10:53=
:35","Grid outage site went down because Gen failed to start due to poor Ba=
ttery backup// GEN automatically started","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage si=
te went down because Gen failed to start due to poor Battery backup// GEN a=
utomatically started","christelle.ngonga@matech-cameroun.com","250","01-06-=
2025 10:53:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005155433","Eseka To=
wn","","01-06-2025 10:30:18","01-06-2025 10:26:39","01-06-2025 10:44:28","C=
ascaded Incident from TTO5300911","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid bad voltage, Site went down b=
efore Gen start due to poor backup // He put site on gen","system","812752"=
,"01-06-2025 10:30:18","MATECH CMR"
"Closed Complete","Site Down","T0139","IHS_YND_381","NOCINC0005155413","Bou=
mnyebel","IHS_YND_379, IHS_YND_378","01-06-2025 10:28:47","01-06-2025 10:26=
:39","01-06-2025 10:55:28","Grid bad voltage, Site went down before Gen sta=
rt due to poor backup // He put site on gen","Kemeni Franklin","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid bad vo=
ltage, Site went down before Gen start due to poor backup // He put site on=
 gen","edwige.kapawo@matech-cameroun.com","129","01-06-2025 10:28:47","MATE=
CH CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0005155404","Ese=
ka MTN","","01-06-2025 10:27:28","01-06-2025 10:26:39","01-06-2025 10:44:28=
","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid bad voltage, Site went down before Gen start due to poor b=
ackup // He put site on gen","edwige.kapawo@matech-cameroun.com","812753","=
01-06-2025 10:27:28","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005155315","N=
kolfon Cimencam","","01-06-2025 10:06:52","01-06-2025 10:05:35","01-06-2025=
 10:07:50","Site is impacted by Afanoya II(Not manage by HIS)","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","Site is impacted by Afanoya II(Not manage by HIS)"=
,"christelle.ngonga@matech-cameroun.com","78","01-06-2025 10:06:52","MATECH=
 CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005155193","Mes=
sassi 2","","01-06-2025 09:38:34","01-06-2025 09:31:27","01-06-2025 09:41:5=
6","Grid outage site went down because Gen failed to start due to poor Batt=
ery backup// GEN automatically started","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site=
 went down because Gen failed to start due to poor Battery backup// GEN aut=
omatically started","edwige.kapawo@matech-cameroun.com","429","01-06-2025 0=
9:38:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005155123","Messassi=
 okolo","","01-06-2025 09:34:04","01-06-2025 09:32:11","01-06-2025 10:30:36=
","Cascaded Incident from TTO5300578","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (Gen Noise) // Grid return","system","81597=
2","01-06-2025 09:34:04","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005155115","E=
MANA BILICK CITY","IHS_YND_279","01-06-2025 09:33:24","01-06-2025 09:32:11"=
,"01-06-2025 10:36:43","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid return","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage, site down bec=
ause site behaves as Grid only site (Gen Noise) // Grid return","christelle=
.ngonga@matech-cameroun.com","75","01-06-2025 09:33:24","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005155112","N=
kolbong","","01-06-2025 09:32:32","01-06-2025 09:29:17","01-06-2025 10:30:3=
4","Grid outage, site went down due to Gen overload (22kva//350A) // Grid r=
estoration","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, site went down due to Gen overload (22kva//350A) =
// Grid restoration","christelle.ngonga@matech-cameroun.com","196","01-06-2=
025 09:32:32","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005155009","T=
SINGA VILLAGE 2","","01-06-2025 09:10:24","01-06-2025 09:06:15","01-06-2025=
 09:18:31","Site down due to water leaking into tank // tank drained and ge=
n manually started","Delor Telezing","Fuel Outage","Passive","Diesel","Dies=
el Quality","Site down due to water leaking into tank // tank drained and g=
en manually started","christelle.ngonga@matech-cameroun.com","251","01-06-2=
025 09:10:24","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0005155006","Nko=
lfoulou","","01-06-2025 09:09:57","01-06-2025 08:46:38","01-06-2025 09:16:5=
5","Grid outage, site down due to gen overload 300 A /20 KVA // Gen charge =
reduced and manual start of gen.","Siligap Boris","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage, site down due to gen overloa=
d 300 A /20 KVA // Gen charge reduced and manual start of gen.","edwige.kap=
awo@matech-cameroun.com","1399","01-06-2025 09:09:57","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005154987","O=
LAMA","","01-06-2025 09:06:37","01-06-2025 09:01:31","01-06-2025 09:07:55",=
"No power issue on site Ubaie =3D55.1V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue.","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site Ubaie =3D55.1V site on Gen The TX=
 FME Henri (699949693) from Huawei is informed.Noticed that it is a repetit=
ve issue.","christelle.ngonga@matech-cameroun.com","308","01-06-2025 09:06:=
37","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005154887","E=
koumdoum OCM","","01-06-2025 08:44:18","01-06-2025 08:37:04","01-06-2025 09=
:06:25","Grid outage, site went down due to Gen overload(20kva,280 A) // Gr=
id restoration","Albran Byorel","Equipment Repair","Passive","DCDG Gen","DC=
DG - Overload","Grid outage, site went down due to Gen overload(20kva,280 A=
) // Grid restoration","christelle.ngonga@matech-cameroun.com","436","01-06=
-2025 08:44:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0005154713","Melen Ba=
'aba","","01-06-2025 08:02:38","01-06-2025 07:56:24","01-06-2025 08:33:12",=
"Cascaded Incident from TTO5300110","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to gen =
overload 300 A /20 KVA  //  Gen charge reduced and manual start of gen.","s=
ystem","821602","01-06-2025 08:02:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005154712","Nkolfoul=
ou 2","","01-06-2025 08:02:38","01-06-2025 07:56:24","01-06-2025 08:33:12",=
"Cascaded Incident from TTO5300110","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down due to gen =
overload 300 A /20 KVA  //  Gen charge reduced and manual start of gen.","s=
ystem","821602","01-06-2025 08:02:38","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005154692","N=
kolfoulou","IHS_YND_278, IHS_YND_308","01-06-2025 07:59:32","01-06-2025 07:=
56:24","01-06-2025 08:35:34","Grid outage, site down due to gen overload 30=
0 A /20 KVA  //  Gen charge reduced and manual start of gen.","Siligap Bori=
s","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, =
site down due to gen overload 300 A /20 KVA  //  Gen charge reduced and man=
ual start of gen.","christelle.ngonga@matech-cameroun.com","189","01-06-202=
5 07:59:32","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005154612","Men=
dong3","","01-06-2025 07:43:40","01-06-2025 07:41:24","01-06-2025 09:17:37"=
,"Grid Outage No space to deploy MGE. // Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Outage No space to d=
eploy MGE. // Grid return","edwige.kapawo@matech-cameroun.com","137","01-06=
-2025 07:43:40","MATECH CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0005154562","Jea=
n Vespa","","01-06-2025 07:35:56","01-06-2025 07:27:48","01-06-2025 07:49:4=
3","Grid fluctuation site went down because Gen failed to start due to Grid=
 bad voltage and No RCP on site // He bypass the Grid and Gen manually star=
ted","Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid fluctuation site went down because Gen failed to s=
tart due to Grid bad voltage and No RCP on site // He bypass the Grid and G=
en manually started","edwige.kapawo@matech-cameroun.com","488","01-06-2025 =
07:35:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0005154541","BATA Mok=
olo OCM","","01-06-2025 07:31:18","01-06-2025 07:16:30","01-06-2025 08:28:5=
4","Cascaded Incident from TTO5299944","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","TTO5299945","system","823964","01-06-2025 07=
:31:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0005154540","Nkomkana=
","","01-06-2025 07:31:18","01-06-2025 07:16:30","01-06-2025 08:28:54","TTO=
5299944","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Grid outage, Grid only  site // Diployment of mobile gen 20KVA","system","=
823965","01-06-2025 07:31:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0005154542","Tsinga",=
"","01-06-2025 07:31:18","01-06-2025 07:16:30","01-06-2025 08:28:54","Casca=
ded Incident from TTO5299944","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","TTO5299945","system","823961","01-06-202=
5 07:31:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0005154543","Entree C=
ite Verte","","01-06-2025 07:31:18","01-06-2025 07:16:30","01-06-2025 08:28=
:54","Cascaded Incident from TTO5299944","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","TTO5299945","system","823963","=
01-06-2025 07:31:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0005154538","Nkomkana=
 2","","01-06-2025 07:31:17","01-06-2025 07:16:30","01-06-2025 08:28:54","C=
ascaded Incident from TTO5299944","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","TTO5299945","system","823964","01-06=
-2025 07:31:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005154537","Golf Qua=
ter","","01-06-2025 07:31:17","01-06-2025 07:16:30","01-06-2025 08:28:54","=
Cascaded Incident from TTO5299944","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","TTO5299945","system","823962","01-0=
6-2025 07:31:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0005154539","Cite-Ver=
te","IHS_YND_220, IHS_YND_138, IHS_YND_200, IHS_YND_126, IHS_YND_559, IHS_Y=
ND_563, IHS_YND_127, IHS_YND_543","01-06-2025 07:31:17","01-06-2025 07:16:3=
0","01-06-2025 08:28:54","Grid outage, Grid only  site // Diployment of mob=
ile gen 20KVA","","Grid Supply","Passive","Grid","National Grid - Grid Outa=
ge Issue","Grid outage, Grid only  site // Diployment of mobile gen 20KVA",=
"system","887","01-06-2025 07:31:17","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005154523","B=
astos-Nylon","","01-06-2025 07:25:38","01-06-2025 07:16:30","01-06-2025 08:=
28:54","TTO5299944","Mboua Thierry","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","TTO5299944","christelle.ngonga@matech-cameroun.com=
","823963","01-06-2025 07:25:38","MATECH CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0005154519","B=
astos Bethesda","","01-06-2025 07:24:49","01-06-2025 07:16:30","01-06-2025 =
08:28:54","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, Grid only  site // Diployment of mobile gen =
20KVA","christelle.ngonga@matech-cameroun.com","823962","01-06-2025 07:24:4=
9","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005154497","TSI=
NGA VILLAGE 2","","01-06-2025 07:16:07","01-06-2025 07:14:52","01-06-2025 0=
8:37:15","Solar Hybrid Gen site ,Site went down because Gen started and sto=
pped due to water infiltration in the tank // He cleaned the tank , purged =
the Gen and site u","Delor Telezing","Fuel Outage (Probable)","Passive","Di=
esel","Tank Sealing Issue - Water In The Fuel","Solar Hybrid Gen site ,Site=
 went down because Gen started and stopped due to water infiltration in the=
 tank // He cleaned the tank , purged the Gen and site u","edwige.kapawo@ma=
tech-cameroun.com","76","01-06-2025 07:16:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0005154445","Jean Ves=
pa 2","","01-06-2025 07:08:40","01-06-2025 07:06:44","01-06-2025 07:40:50",=
"Cascaded Incident from TTO5299840","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluuctuation, Site went Down =
due to poor backup (waiting Grid return) // Grid return","system","824528",=
"01-06-2025 07:08:40","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0005154437","J=
-Vespa","IHS_YND_544","01-06-2025 07:06:48","01-06-2025 07:06:44","01-06-20=
25 07:40:50","Grid fluuctuation, Site went Down due to poor backup (waiting=
 Grid return) // Grid return","Mboua Thierry","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid fluuctuation, Site went=
 Down due to poor backup (waiting Grid return) // Grid return","christelle.=
ngonga@matech-cameroun.com","5","01-06-2025 07:06:48","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005154430","A=
wae Ewonkan","","01-06-2025 07:04:18","01-06-2025 07:02:23","01-06-2025 13:=
53:56","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","christelle.ngonga@matech-cameroun.com","117","01-06-2025 07:04:18","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005154388","O=
dza II OCM","","01-06-2025 06:53:25","01-06-2025 06:50:18","01-06-2025 06:5=
3:00","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Site stabilised","Albran Byorel","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Grid outage, site went down=
 because gen failed to start due to PWC ZTE malfunction // Site stabilised"=
,"christelle.ngonga@matech-cameroun.com","189","01-06-2025 06:53:25","MATEC=
H CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0005154368","Nom=
ayos","","01-06-2025 06:48:42","01-06-2025 06:46:37","01-06-2025 07:23:40",=
"Site went down because gen fails to start due to grid bad voltage // He by=
pass grid and manually start the gen","Fanda Brice","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Site went down because g=
en fails to start due to grid bad voltage // He bypass grid and manually st=
art the gen","edwige.kapawo@matech-cameroun.com","378","01-06-2025 06:48:42=
","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005154292","Eki=
e sud","","01-06-2025 06:25:56","01-06-2025 06:15:59","01-06-2025 07:23:14"=
,"Grid outage,DG started and stopped due with alarm ""oil pressure""( unpro=
uven Alarm ) // He reset DG card and started DG manually","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
DG started and stopped due with alarm ""oil pressure""( unprouven Alarm ) /=
/ He reset DG card and started DG manually","gerard.tchangoue@matech-camero=
un.com","598","01-06-2025 06:25:56","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005154289","Nko=
g-Edzen","","01-06-2025 06:24:42","01-06-2025 06:13:59","01-06-2025 08:17:3=
3","Active//No power issue on site, Site on Grid Ubay =3D 56.4V The Tx Fme =
Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Grid Ubay =3D 56.4V The Tx Fme Greg=
oire (654547479) from Huawei is informed.","gerard.tchangoue@matech-camerou=
n.com","644","01-06-2025 06:24:42","MATECH CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0005154225","D=
ong","","01-06-2025 06:08:07","01-06-2025 06:04:53","01-06-2025 11:19:45","=
Site down because gen overhit //Gen  radiator colded  and  water added ,Gen=
 manually started","Parker Tchoup","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Radiator","Site down because gen overhit //Gen  radiator colded  an=
d  water added ,Gen manually started","vanel.mbiada@matech-cameroun.com","1=
95","01-06-2025 06:08:07","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005154138","Feb=
e Village","","01-06-2025 05:36:30","01-06-2025 05:27:18","01-06-2025 07:16=
:30","Site went down because gen stopped with alarm high temp//he added wat=
er in radiator","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","AC=
DG - Radiator","Site went down because gen stopped with alarm high temp//he=
 added water in radiator","gerard.tchangoue@matech-cameroun.com","554","01-=
06-2025 05:36:30","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0005154076","S=
ous Prefecture","","01-06-2025 05:07:03","01-06-2025 01:06:12","01-06-2025 =
04:22:49","ACTIVE//No power issue site on Grid Ubaie =3D52.7 V, The tx Huaw=
ei Fulbert (654266068) is informed","Fanda Brice","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No po=
wer issue site on Grid Ubaie =3D52.7 V, The tx Huawei Fulbert (654266068) i=
s informed","vanel.mbiada@matech-cameroun.com","14452","01-06-2025 05:07:03=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0005153981","AWAE OCM=
","","01-06-2025 04:14:20","01-06-2025 04:04:58","01-06-2025 06:22:05","Cas=
caded Incident from TTO5299308","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because Gen CB tripp=
ed // CB reamed","system","835319","01-06-2025 04:14:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0005153980","Tradex-N=
komo","","01-06-2025 04:14:20","01-06-2025 04:04:58","01-06-2025 06:22:05",=
"Cascaded Incident from TTO5299308","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because Gen CB trip=
ped // CB reamed","system","835320","01-06-2025 04:14:20","MATECH CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0005153970","Nko=
mo II","IHS_YND_172, IHS_YND_173","01-06-2025 04:12:16","01-06-2025 04:04:5=
8","01-06-2025 06:22:05","site went down because Gen CB issue// CB reamed",=
"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Main Breake=
r Tripped","site went down because Gen CB tripped // CB reamed","gerard.tch=
angoue@matech-cameroun.com","438","01-06-2025 04:12:16","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005153957","N=
YOM 2 IHS","","01-06-2025 04:06:39","01-06-2025 03:59:16","01-06-2025 04:28=
:33","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup // Grid return","vanel.mbiada@matech-cameroun.com","444"=
,"01-06-2025 04:06:39","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005153927","Bit=
eng-Maetur","","01-06-2025 03:49:41","01-06-2025 03:40:33","01-06-2025 04:1=
0:04","Grid outage site went down because Gen failed to start due PWC ZTE  =
dysfonction // He reset the PWC and Gen manually started","Mba Lazare Herve=
","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","G=
rid outage site went down because Gen failed to start due PWC ZTE  dysfonct=
ion // He reset the PWC and Gen manually started","gerard.tchangoue@matech-=
cameroun.com","549","01-06-2025 03:49:41","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005153882","S=
tade-Abega","","01-06-2025 03:33:08","01-06-2025 03:28:48","01-06-2025 03:3=
5:11","Active // No pwer issue, site is on grid with Ubaie=3D53.4V, Lionel =
adjep(655184876) from Huawei is informed","Mba Lazare Herve","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive // No pwer issue, site is on grid with Ubaie=3D53.4V, Lionel adjep(655=
184876) from Huawei is informed","vanel.mbiada@matech-cameroun.com","261","=
01-06-2025 03:33:08","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005153870","O=
LAMA","","01-06-2025 03:27:55","01-06-2025 03:22:38","01-06-2025 03:28:16",=
"No power issue on site Ubaie =3D55.1V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue.","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site Ubaie =3D55.1V site on Gen The TX=
 FME Henri (699949693) from Huawei is informed.Noticed that it is a repetit=
ve issue.","vanel.mbiada@matech-cameroun.com","319","01-06-2025 03:27:55","=
MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0005153862","Beh=
ind P T school Yde","","01-06-2025 03:25:10","01-06-2025 03:16:57","01-06-2=
025 06:36:42","Grid outage site went down due to 01/04 rectifiers alarming =
on site //he reset it","Paul BIBOUM","Equipment Repair","Passive","Rectifie=
r","Rectifier Distribution","Grid outage site went down due to 01/04 rectif=
iers alarming on site //he reset it","gerard.tchangoue@matech-cameroun.com"=
,"494","01-06-2025 03:25:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005153854","Minka","=
","01-06-2025 03:24:06","01-06-2025 03:11:11","01-06-2025 03:21:13","Cascad=
ed Incident from TTO5299159","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability.Henri (699949693) from=
 Huawei is informed.","system","838520","01-06-2025 03:24:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005153855","Mom","",=
"01-06-2025 03:24:06","01-06-2025 03:11:11","01-06-2025 03:21:13","Cascaded=
 Incident from TTO5299159","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on grid with U=3D54v Site is=
 impacted by Ngoumou who is not our responsability.Henri (699949693) from H=
uawei is informed.","system","838519","01-06-2025 03:24:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005153853","OTELE MT=
N","","01-06-2025 03:24:05","01-06-2025 03:11:11","01-06-2025 03:21:13","Ca=
scaded Incident from TTO5299159","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on grid with U=3D54v S=
ite is impacted by Ngoumou who is not our responsability.Henri (699949693) =
from Huawei is informed.","system","838519","01-06-2025 03:24:05","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005153852","OLAMA","=
","01-06-2025 03:24:05","01-06-2025 03:11:11","01-06-2025 03:21:13","Cascad=
ed Incident from TTO5299159","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability.Henri (699949693) from=
 Huawei is informed.","system","838520","01-06-2025 03:24:05","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005153838","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","01-06-2025 03:20:=
25","01-06-2025 03:11:11","01-06-2025 03:21:13","No power issue site on gri=
d with U=3D54v Site is impacted by Ngoumou who is not our responsability.He=
nri (699949693) from Huawei is informed.","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","Affected by 3rd Party Site",=
"No power issue site on grid with U=3D54v Site is impacted by Ngoumou who i=
s not our responsability.Henri (699949693) from Huawei is informed.","gerar=
d.tchangoue@matech-cameroun.com","555","01-06-2025 03:20:25","MATECH CMR"
"Closed Complete","Site Down","T0401","IHS_YND_205","NOCINC0005153738","Ton=
golo MTN","","01-06-2025 02:53:44","01-06-2025 02:17:36","01-06-2025 03:59:=
36","Grid fluctuation, Site went down because gen fails to start due to gri=
d bad voltage// He bypasse the Grid and site on Gen","Fabrice Pouakam","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation, Site went down because gen fails to start due to grid bad volt=
age// He bypasse the Grid and site on Gen","olivier.kwedi@ihstowers.com","2=
169","01-06-2025 02:53:44","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005153699","S=
tade-Abega","","01-06-2025 02:46:08","01-06-2025 02:41:59","01-06-2025 02:4=
8:53","Active // No pwer issue, site is on grid with Ubaie=3D53.4V, Lionel =
adjep(655184876) from Huawei is informed","Mba Lazare Herve","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive // No pwer issue, site is on grid with Ubaie=3D53.4V, Lionel adjep(655=
184876) from Huawei is informed","vanel.mbiada@matech-cameroun.com","250","=
01-06-2025 02:46:08","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005153657","B=
arriere IHS","","01-06-2025 02:34:45","01-06-2025 02:25:35","01-06-2025 08:=
45:26","Grid Fluctuations; Site went Down due to Gen overload(15Kva, 200A) =
SS IHS FELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid Fluctuations; Site wen=
t Down due to Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // G=
rid return","vanel.mbiada@matech-cameroun.com","551","01-06-2025 02:34:45",=
"MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005153604","MBA=
LNGONG LYCEE","","01-06-2025 02:20:59","01-06-2025 02:11:52","01-06-2025 08=
:38:06","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid return","Fan=
da Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, Site went down because Gen stopped due to overload(9kva, 130A) SS IH=
S Felix Zambe is informed and confirmed // Grid return","gerard.tchangoue@m=
atech-cameroun.com","548","01-06-2025 02:20:59","MATECH CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0005153584","Nya=
hoo","IHS_EDA_102, IHS_EDA_049","01-06-2025 02:13:39","01-06-2025 02:06:31"=
,"01-06-2025 02:52:14","Active//No power issue on site U=3D53,3V site on Ge=
n and The FME TX Gregoire From huawei is informed","TIENTCHEU NZETCHIEU GAE=
L","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issue on site U=3D53,3V site on Gen and The=
 FME TX Gregoire From huawei is informed","gerard.tchangoue@matech-cameroun=
.com","429","01-06-2025 02:13:39","MATECH CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0005153557","NYA=
NON/DEMBO","","01-06-2025 02:04:28","01-06-2025 02:06:31","01-06-2025 02:52=
:14","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","Active//No power issue on site U=3D53,3V site on Gen a=
nd The FME TX Gregoire From huawei is informed","gerard.tchangoue@matech-ca=
meroun.com","842366","01-06-2025 02:04:28","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005153376","ODZ=
A MINKAN EDIBI ASSI","","01-06-2025 01:35:33","01-06-2025 01:26:19","01-06-=
2025 07:04:57","FME Jovi will manage after Nkomo 2","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outag=
e, site went down because gen failed to start due to PWC ZTE malfunction //=
 He reset the controller","gerard.tchangoue@matech-cameroun.com","555","01-=
06-2025 01:35:33","MATECH CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0005153338","E=
mombo-Tchad","IHS_YND_114","01-06-2025 01:23:45","01-06-2025 01:19:35","01-=
06-2025 12:25:04","No power issue on site Ubaie=3D54,1V site on Grid , The =
Tx FME Leonel/ 694693436/ from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site Ubaie=3D54,1V site on Grid , The Tx FME Leonel/ 694693436/ fr=
om Huawei is informed","vanel.mbiada@matech-cameroun.com","251","01-06-2025=
 01:23:45","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005153337","Nko=
langaa","","01-06-2025 01:23:24","01-06-2025 01:15:13","01-06-2025 01:23:01=
","Active // No power issue on site Ubay =3D 53.1V Site on Grid. TX FME Hen=
ri (699949693/Huawei) is on site for works","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue on site Ubay =3D 53.1V Site on Grid. TX FME Henri =
(699949693/Huawei) is on site for works","gerard.tchangoue@matech-cameroun.=
com","492","01-06-2025 01:23:24","MATECH CMR"
"Cancelled","Warning","CTR_040","IHS_YND_114","NOCINC0005153336","Kondengui=
","","01-06-2025 01:22:47","","","Active // No power issue site on Gen Ubai=
e:54.24 Lionnel Steve (655184876/Huawei) is informed","Albran Byorel","",""=
,"","","","vanel.mbiada@matech-cameroun.com","191","01-06-2025 01:22:47","M=
ATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005153334","Nom=
ayos montee Meche","","01-06-2025 01:22:26","01-06-2025 01:13:48","01-06-20=
25 01:59:48","Grid outage, site went down before Gen started due to poor ba=
ckup battery // Grid returned","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen started due to poor backup battery // Grid returned","gerard.tcha=
ngoue@matech-cameroun.com","519","01-06-2025 01:22:26","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005153311","N=
kolso","","01-06-2025 01:15:12","01-06-2025 01:12:59","01-06-2025 01:53:22"=
,"Grid outage, Site went down before Gen start due to poor backup/ // Gen a=
utomatically started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup/ // Gen automatically started","edwi=
ge.kapawo@matech-cameroun.com","133","01-06-2025 01:15:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005153306","MEHANDAN=
","","01-06-2025 01:14:21","01-06-2025 01:06:19","01-06-2025 01:39:23","Cas=
caded Incident from TTO5298584","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","	Active: No power issue on site Ubaie =3D=
54.4V site on Grid. The TX FME Lionnel Adhex (655184876) from Huawei is inf=
orme","system","845939","01-06-2025 01:14:21","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005153300","O=
dza II OCM","IHS_YND_528","01-06-2025 01:13:26","01-06-2025 01:06:19","01-0=
6-2025 01:39:23","	Active: No power issue on site Ubaie =3D54.4V site on Gr=
id. The TX FME Lionnel Adhex (655184876) from Huawei is informe","Albran By=
orel","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","	Active: No power issue on site Ubaie =3D54.4V site on Gr=
id. The TX FME Lionnel Adhex (655184876) from Huawei is informe","edwige.ka=
pawo@matech-cameroun.com","429","01-06-2025 01:13:26","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005153292","ELO=
UMDEM CARRIERE","","01-06-2025 01:11:12","01-06-2025 01:03:57","01-06-2025 =
01:32:19","Grid outage site went down before Gen started due to poor batter=
y back up // Gen automatically started","Fanda Brice","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage site wen=
t down before Gen started due to poor battery back up // Gen automatically =
started","gerard.tchangoue@matech-cameroun.com","437","01-06-2025 01:11:12"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005153276","E=
ssomba","","01-06-2025 01:07:43","01-06-2025 00:41:30","01-06-2025 06:03:38=
","Site went down because 03/06 rectifiers dysfunctionned //Site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","Site went down because 03/06 rectifiers dysfunctionned //=
Site stabilised","edwige.kapawo@matech-cameroun.com","1574","01-06-2025 01:=
07:43","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0005153267","AFE=
ME NORD","","01-06-2025 01:03:55","01-06-2025 00:54:46","01-06-2025 09:48:3=
5","Site went Down due to Gen Overload (20Kva, Iload 300 A) // Site stabili=
zed","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Site went Down due to Gen Overload (20Kva, Iload 300 A) // =
Site stabilized","gerard.tchangoue@matech-cameroun.com","550","01-06-2025 0=
1:03:55","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005153257","Mba=
nkolo petit paris","","01-06-2025 01:01:24","01-06-2025 00:53:14","01-06-20=
25 01:18:36","Active: no power issue, site is on grid with Ubaie=3D54.1V, M=
ohamadou((691144435) from Huawei is informed,","Mboua Thierry","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active: no power issue, site is on grid with Ubaie=3D54.1V, Mohamadou((6911=
44435) from Huawei is informed,","gerard.tchangoue@matech-cameroun.com","49=
1","01-06-2025 01:01:24","MATECH CMR"
"Closed Complete","Site Down","CTR_869","IHS_YND_407","NOCINC0005153248","M=
onatele MTN","","01-06-2025 00:59:09","01-06-2025 00:46:56","01-06-2025 01:=
59:14","","Parker Tchoup","Cascade Outage","Active","Cascade Active","Casca=
de Active","ACTIVE// No power issue site on Grid and UBaie=3D 53,6 V; The F=
me TX Gregoire (654547479) from Huawei is informed","edwige.kapawo@matech-c=
ameroun.com","1088","01-06-2025 00:59:09","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005153245","E=
vodoula OCM","","01-06-2025 00:57:47","01-06-2025 00:46:56","01-06-2025 06:=
09:40","Grid outage, site went down because gen failed to start due to grid=
 contactor faulty // He bypassed grid contactor and gen manually started","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","ATS=
-AMF Issue","Grid outage, site went down because gen failed to start due to=
 grid contactor faulty // He bypassed grid contactor and gen manually start=
ed","edwige.kapawo@matech-cameroun.com","1028","01-06-2025 00:57:47","MATEC=
H CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005153237","Mok=
olo Yaounde","","01-06-2025 00:55:34","01-06-2025 00:48:21","01-06-2025 01:=
14:15","Active // No power issue Ubay: 54.4 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.4 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","4=
34","01-06-2025 00:55:34","MATECH CMR"
"Closed Complete","Site Down","T2564","IHS_YND_739","NOCINC0005153233","NKO=
LMESSING rue Manguier","","01-06-2025 00:54:21","01-06-2025 00:46:55","01-0=
6-2025 01:46:55","Grid outage,gen failed to start due to ""low oil pressure=
// alarm//we reset the card and gen manually started","Siligap Boris","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,gen =
failed to start due to ""low oil pressure// alarm//we reset the card and ge=
n manually started","gerard.tchangoue@matech-cameroun.com","447","01-06-202=
5 00:54:21","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0005153205","N=
kolafeme","","01-06-2025 00:52:49","01-06-2025 00:49:35","01-06-2025 01:29:=
23","Grid outage, site went down due to grid fluctuations and no automatism=
 on Gen // Grid returned","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid outage, site went =
down due to grid fluctuations and no automatism on Gen // Grid returned","e=
dwige.kapawo@matech-cameroun.com","194","01-06-2025 00:52:49","MATECH CMR"
"Closed Complete","Site Down","CTR_073","IHS_YND_406","NOCINC0005153204","M=
onatele","IHS_YND_387, IHS_YND_407","01-06-2025 00:52:10","01-06-2025 00:46=
:56","01-06-2025 01:59:14","ACTIVE// No power issue site on Grid and UBaie=
=3D 53,6 V; The Fme TX Gregoire (654547479) from Huawei is informed","Parke=
r Tchoup","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","ACTIVE// No power issue site on Grid and UBaie=3D 53,=
6 V; The Fme TX Gregoire (654547479) from Huawei is informed","edwige.kapaw=
o@matech-cameroun.com","315","01-06-2025 00:52:10","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005153201","T=
alla Monatele","","01-06-2025 00:50:19","01-06-2025 00:46:56","01-06-2025 0=
1:59:14","tx","Parker Tchoup","Cascade Outage","Active","Cascade Active","C=
ascade Active","ACTIVE// No power issue site on Grid and UBaie=3D 53,6 V; T=
he Fme TX Gregoire (654547479) from Huawei is informed","vanel.mbiada@matec=
h-cameroun.com","902","01-06-2025 00:50:19","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0005153197","Ema=
na Lycee","","01-06-2025 00:48:17","01-06-2025 00:40:12","01-06-2025 01:17:=
19","No power issue site on grid with U=3D54v Symphorien(691316854) from Hu=
awei is informed, site up without intervention.","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue site on grid with U=3D54v Symphorien(691316854) from Hua=
wei is informed, site up without intervention.","gerard.tchangoue@matech-ca=
meroun.com","486","01-06-2025 00:48:17","MATECH CMR"
"Closed Complete","Site Down","CTR_273","IHS_YND_214","NOCINC0005153184","N=
kolmesseng-II","","01-06-2025 00:41:33","01-06-2025 00:40:26","01-06-2025 0=
0:45:35","Eneo outage, site down due to poor backup // Eneo return","Siliga=
p Boris","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","Eneo outage, site down due to poor backup // Eneo return","vanel.=
mbiada@matech-cameroun.com","68","01-06-2025 00:41:33","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005153182","Djo=
nassi-Yde","","01-06-2025 00:40:31","01-06-2025 00:37:24","01-06-2025 01:45=
:09","site went down due to insufficient of rectifiers//He reset rectifier"=
,"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","site went down due to insufficient of rectifiers//He reset rectifier",=
"cedric.tiani@matech-cameroun.com","188","01-06-2025 00:40:31","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005153178","Nko=
g-Edzen","","01-06-2025 00:39:38","01-06-2025 00:35:27","01-06-2025 01:42:1=
0","Active//No power issue on site, Site on Grid Ubay =3D 56.4V The Tx Fme =
Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Grid Ubay =3D 56.4V The Tx Fme Greg=
oire (654547479) from Huawei is informed.","cedric.tiani@matech-cameroun.co=
m","252","01-06-2025 00:39:38","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005153165","E=
bogo","","01-06-2025 00:32:52","01-06-2025 00:28:19","01-06-2025 18:49:52",=
"Active// No Power issue on site Ubaie 53.2V site on Grid, Julien /69309584=
9 from Huawei is informed","Siligap Boris","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power is=
sue on site Ubaie 53.2V site on Grid, Julien /693095849 from Huawei is info=
rmed","edwige.kapawo@matech-cameroun.com","275","01-06-2025 00:32:52","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005153136","S=
IMBOCK BONAMBAPE","","01-06-2025 00:26:11","01-06-2025 00:24:58","01-06-202=
5 02:28:58","Active // No power issue site on grid with Ubaie: 53.6V TX FME=
 Flubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue site on grid with Ubaie: 53.6V TX FME Flubert (654=
266068) from Huawei is informed","edwige.kapawo@matech-cameroun.com","75","=
01-06-2025 00:26:11","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005152811","Lad=
a I Yde","","31-05-2025 23:44:31","31-05-2025 23:40:22","01-06-2025 00:09:0=
8","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","edwige.kapawo@matech-cameroun.com","250","31-05-2025 23:44:31","MATECH C=
MR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0005152674","ODZ=
A CITE MBIA","","31-05-2025 23:24:09","31-05-2025 22:26:58","01-06-2025 00:=
15:16","Site down because the neighbors turned off the GEN // GEN turned ba=
ck on by FME","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Emergency Stop Switch","Site down because the neighbors turned off the G=
EN // GEN turned back on by FME","olivier.kwedi@ihstowers.com","3432","31-0=
5-2025 23:24:09","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005152514","N=
kolbong","","31-05-2025 23:03:09","31-05-2025 23:00:01","31-05-2025 23:03:1=
8","Grid outage, site went down due to Gen overload (22kva//350A) // Grid r=
estoration","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, site went down due to Gen overload (22kva//350A) =
// Grid restoration","edwige.kapawo@matech-cameroun.com","189","31-05-2025 =
23:03:09","MATECH CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0005152130","A=
FEME NORD","","31-05-2025 22:30:23","31-05-2025 22:23:57","31-05-2025 23:47=
:09","Site went Down due to Gen Overload (20Kva, Iload 300 A) // Site stabi=
lized","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Site went Down due to Gen Overload (20Kva, Iload 300 A) /=
/ Site stabilized","edwige.kapawo@matech-cameroun.com","387","31-05-2025 22=
:30:23","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005151657","Mon=
tee Jouvence","","31-05-2025 21:30:41","31-05-2025 21:23:23","31-05-2025 21=
:33:26","Grid outage, Site went down before Gen start due to poor backup //=
 Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, Site went down before Gen star=
t due to poor backup // Grid return","cedric.tiani@matech-cameroun.com","43=
9","31-05-2025 21:30:41","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005151611","B=
arriere","","31-05-2025 21:27:04","31-05-2025 21:25:45","31-05-2025 21:28:4=
0","No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/=
Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
bay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is informed.","chris=
telle.ngonga@matech-cameroun.com","81","31-05-2025 21:27:04","MATECH CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0005151594","A=
FEME NORD","","31-05-2025 21:25:10","31-05-2025 21:18:03","31-05-2025 22:06=
:29","Site went Down due to Gen Overload (20Kva, Iload 300 A) // Site stabi=
lized","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Site went Down due to Gen Overload (20Kva, Iload 300 A) /=
/ Site stabilized","christelle.ngonga@matech-cameroun.com","428","31-05-202=
5 21:25:10","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005151125","Aha=
la Echangeur","","31-05-2025 20:44:56","31-05-2025 20:38:46","01-06-2025 07=
:23:08","Grid outage gen failedto start due to overheating causing by headg=
asket issue //He added water and oil and gen manually started","MINKA NICOL=
AS","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage ge=
n failedto start due to overheating causing by headgasket issue //He added =
water and oil and gen manually started","cedric.tiani@matech-cameroun.com",=
"371","31-05-2025 20:44:56","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005150431","M=
imboman-Ecole","","31-05-2025 19:34:51","31-05-2025 19:27:34","31-05-2025 1=
9:39:24","No power issue on site U:53.9 V,site on grid The FME TX Eloundou =
Bertrant (693212405) From Huawei is Informed.","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site U:53.9 V,site on grid The FME TX Eloundou Bertran=
t (693212405) From Huawei is Informed.","ludivine.ngamaleu@ihstowers.com","=
438","31-05-2025 19:34:51","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005150378","N=
omayos montee Meche","","31-05-2025 19:32:15","31-05-2025 19:29:03","31-05-=
2025 19:32:22","Grid outage, site went down before Gen started due to poor =
backup battery // Grid returned","Fanda Brice","Equipment Repair","Passive"=
,"ACDG Gen","DG Low Battery","Grid outage, site went down before Gen starte=
d due to poor backup battery // Grid returned","christelle.ngonga@matech-ca=
meroun.com","192","31-05-2025 19:32:15","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0005150276","H=
-Paradis","","31-05-2025 19:14:44","31-05-2025 19:10:37","31-05-2025 20:59:=
54","No power issue, site is on grid with Ubaie: 54.4V, Symphorien(65025715=
1) from Huawei is informed","","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on grid =
with Ubaie: 54.4V, Symphorien(650257151) from Huawei is informed","christel=
le.ngonga@matech-cameroun.com","248","31-05-2025 19:14:44","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005150226","N=
kolfon Cimencam","","31-05-2025 19:04:49","31-05-2025 19:00:42","31-05-2025=
 19:07:44","Site is impacted by Afanoya II(Not manage by HIS)","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","Site is impacted by Afanoya II(Not manage by HIS)"=
,"christelle.ngonga@matech-cameroun.com","248","31-05-2025 19:04:49","MATEC=
H CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005150197","Mba=
nkolo petit paris","","31-05-2025 18:57:58","31-05-2025 18:28:26","31-05-20=
25 21:10:59","tx","Mboua Thierry","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Site went down because gen fails to start due to gri=
d bad voltage // He bypass grid and manually start the gen","cedric.tiani@m=
atech-cameroun.com","863015","31-05-2025 18:57:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005150182","ELOUMDEM=
 CARRIERE 2","","31-05-2025 18:54:04","31-05-2025 18:46:46","31-05-2025 18:=
52:25","Cascaded Incident from TTO5295202","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Grid return","system","861947","31-05=
-2025 18:54:04","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005150172","MEF=
OU ASSI","IHS_YND_768","31-05-2025 18:52:01","31-05-2025 18:46:46","31-05-2=
025 18:52:25","Grid outage, Site went down before Gen start due to poor bac=
kup // Grid return","Fanda Brice","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Grid return","cedric.tiani@matech-cameroun.com",=
"317","31-05-2025 18:52:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005150101","MEHANDAN=
","","31-05-2025 18:42:56","31-05-2025 18:36:07","31-05-2025 18:42:57","Cas=
caded Incident from TTO5295110","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
862567","31-05-2025 18:42:56","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005150093","Odz=
a II OCM","IHS_YND_528","31-05-2025 18:41:19","31-05-2025 18:36:07","31-05-=
2025 18:42:57","Grid outage, site went down because gen failed to start due=
 to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site =
went down because gen failed to start due to PWC ZTE malfunction // Site st=
abilised","cedric.tiani@matech-cameroun.com","314","31-05-2025 18:41:19","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005150043","N=
gousso-Savana","IHS_YND_561","31-05-2025 18:32:33","31-05-2025 18:26:07","3=
1-05-2025 19:52:17","Grid fluctuation, site went down before gen  start due=
 to grid fluctuation // Grid stabilisation","Siligap Boris","Grid Supply","=
Passive","Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuat=
ion, site went down before gen  start due to grid fluctuation // Grid stabi=
lisation","christelle.ngonga@matech-cameroun.com","387","31-05-2025 18:32:3=
3","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0005150042","AFE=
ME NORD","IHS_YND_808","31-05-2025 18:32:32","31-05-2025 18:28:26","31-05-2=
025 21:10:59","Site went down because gen fails to start due to grid bad vo=
ltage // He bypass grid and manually start the gen","TIENTCHEU NZETCHIEU GA=
EL","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Site went down because gen fails to start due to grid bad voltage // He =
bypass grid and manually start the gen","cedric.tiani@matech-cameroun.com",=
"247","31-05-2025 18:32:32","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005150035","F=
OUGEROLE","","31-05-2025 18:30:44","31-05-2025 18:26:07","31-05-2025 19:52:=
17","TTO5295052	","Siligap Boris","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Grid fluctuation, site went down before gen  start d=
ue to grid fluctuation // Grid stabilisation","christelle.ngonga@matech-cam=
eroun.com","863154","31-05-2025 18:30:44","MATECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0005149894","N=
koa Ayos","","31-05-2025 18:05:49","31-05-2025 17:55:03","31-05-2025 18:32:=
13","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid fluctuation , Site went down due to grid bad voltage //He =
bypassed the Grid, site on GEN","christelle.ngonga@matech-cameroun.com","12=
16399","31-05-2025 18:05:49","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005149863","GSO=
","IHS_YND_067","31-05-2025 17:59:11","31-05-2025 17:55:03","31-05-2025 18:=
39:35","Grid fluctuation , Site went down due to grid bad voltage //He bypa=
ssed the Grid, site on GEN","MINKA NICOLAS","Grid Supply","Passive","Grid",=
"National Grid - Low Current Supply","Grid fluctuation , Site went down due=
 to grid bad voltage //He bypassed the Grid, site on GEN","cedric.tiani@mat=
ech-cameroun.com","248","31-05-2025 17:59:11","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005149806","E=
koumdoum OCM","","31-05-2025 17:52:15","31-05-2025 17:50:07","31-05-2025 18=
:07:18","Grid outage, site went down due to Gen overload(20kva,280 A) IHS S=
S Pascaline is informed and confirmed // Grid restoration","Albran Byorel",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, sit=
e went down due to Gen overload(20kva,280 A) IHS SS Pascaline is informed a=
nd confirmed // Grid restoration","christelle.ngonga@matech-cameroun.com","=
130","31-05-2025 17:52:15","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005149640","Aha=
la Echangeur","","31-05-2025 17:28:47","31-05-2025 15:51:12","31-05-2025 18=
:04:09","Grid outage gen failedto start due to overheating causing by headg=
asket issue //He added water and oil  and gen manually started","MINKA NICO=
LAS","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Rad=
iator Leakage","Grid outage gen failedto start due to overheating causing b=
y headgasket issue //He added water and oil  and gen manually started","ced=
ric.tiani@matech-cameroun.com","5856","31-05-2025 17:28:47","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005149624","M=
essassi 2","","31-05-2025 17:24:59","31-05-2025 17:21:48","31-05-2025 17:29=
:52"," No power issue Ubaie:53.9 V site on Grid, TX fme symphorien /6502571=
51 from huawei is informed.	","Fabrice Pouakam","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No power issue=
 Ubaie:53.9 V site on Grid, TX fme symphorien /650257151 from huawei is inf=
ormed.","christelle.ngonga@matech-cameroun.com","193","31-05-2025 17:24:59"=
,"MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0005149526","Eko=
umdoum OCM","","31-05-2025 17:10:56","31-05-2025 17:07:45","31-05-2025 17:3=
7:02","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS =
Pascaline is informed and confirmed//Grid return","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went do=
wn due to Gen overload(20kva,280 A) IHS SS Pascaline is informed and confir=
med//Grid return","cedric.tiani@matech-cameroun.com","192","31-05-2025 17:1=
0:56","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005149510","SAA=
 Entrance","","31-05-2025 17:06:57","31-05-2025 17:05:48","31-05-2025 17:07=
:45","Grid fluctuation, Site went down because gen fails to start due to gr=
id bad voltage // Grid return","Parker Tchoup","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Grid fluctuation, Site went d=
own because gen fails to start due to grid bad voltage // Grid return","ced=
ric.tiani@matech-cameroun.com","70","31-05-2025 17:06:57","MATECH CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0005149410","N=
guila","","31-05-2025 16:42:48","31-05-2025 16:41:41","31-05-2025 16:59:10"=
,"No Power issue, site on battery Ubay =3D 48.2V Hybrid Site, Tx Fme Gregoi=
re (654547479) from Huawei is informed and confirmed","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No Power issue, site on battery Ubay =3D 48.2V Hybrid Site, Tx Fme G=
regoire (654547479) from Huawei is informed and confirmed","christelle.ngon=
ga@matech-cameroun.com","68","31-05-2025 16:42:48","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0005149370","Sac=
re Coeur Catholic Church","","31-05-2025 16:36:19","31-05-2025 16:32:08","3=
1-05-2025 16:48:02","Grid outage,site went down because Gen started and sta=
rted and stopped with *High temp * alarm//He opened the doors of the Gen","=
Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine =
Temp - Coolant Level Issue","Grid outage,site went down because Gen started=
 and started and stopped with *High temp * alarm//He opened the doors of th=
e Gen","cedric.tiani@matech-cameroun.com","251","31-05-2025 16:36:19","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005149342","M=
ambine","","31-05-2025 16:31:41","31-05-2025 16:23:30","31-05-2025 18:11:02=
","Grid outage,gen ran till fuel shortage//Refueling done","Fanda Brice","F=
uel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran till fu=
el shortage//Refueling done","christelle.ngonga@matech-cameroun.com","492",=
"31-05-2025 16:31:41","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005149306","O=
LAMA","","31-05-2025 16:25:47","31-05-2025 16:25:43","31-05-2025 16:26:02",=
" No power issue on site Ubaie =3D54.7V site on Gen The TX FME Henri (69994=
9693) from Huawei is informed.Noticed that it is a repetitve issue.","Fanda=
 Brice","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm"," No power issue on site Ubaie =3D54.7V site on Gen The =
TX FME Henri (699949693) from Huawei is informed.Noticed that it is a repet=
itve issue.","christelle.ngonga@matech-cameroun.com","5","31-05-2025 16:25:=
47","MATECH CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0005149138","Ngo=
uetou","","31-05-2025 16:00:28","31-05-2025 15:59:14","31-05-2025 16:55:11"=
,"No power issue site on Gen, with Ubay=3D52.4V. The Tx Fme Gregoire (65454=
7479) from Huawei is informed","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on Gen, with Ubay=3D52.4V. The Tx Fme Gregoire (654547479) from Huawei =
is informed","christelle.ngonga@matech-cameroun.com","76","31-05-2025 16:00=
:28","MATECH CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0005149127","Eli=
g Edzoa","","31-05-2025 15:59:00","31-05-2025 15:54:53","31-05-2025 17:14:2=
9","Site went down because gen fails to start due to grid bad voltage // He=
 bypass grid and manually start the gen","Delor Telezing","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Site went down bec=
ause gen fails to start due to grid bad voltage // He bypass grid and manua=
lly start the gen","christelle.ngonga@matech-cameroun.com","485","31-05-202=
5 15:59:00","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005149100","Acc=
acia New","","31-05-2025 15:53:26","31-05-2025 15:44:05","01-06-2025 08:34:=
57","Grid outage, no space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy MGE // Grid return","christelle.ngonga@matech-cameroun.com","563"=
,"31-05-2025 15:53:26","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0005149060","M=
bankomo IHS","","31-05-2025 15:44:24","31-05-2025 14:58:27","31-05-2025 16:=
24:36","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Site went down due to work of SS HIS Felix Zambe on site (Secu=
ring transmission )//End of work","christelle.ngonga@matech-cameroun.com","=
1226936","31-05-2025 15:44:24","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005148977","A=
wae Ewonkan","","31-05-2025 15:33:07","31-05-2025 15:28:55","31-05-2025 20:=
38:55","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","christelle.ngonga@matech-cameroun.com","253","31-05-2025 15:33:07","M=
ATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005148901","Nko=
l-Mebanga","","31-05-2025 15:14:13","31-05-2025 15:12:06","31-05-2025 16:18=
:57","Active//No power issue on site Ubaie=3D50V site on Solar site  Tx FME=
 Gregoire /654547479/Huawei is informed ","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie=3D50V site on Solar site  Tx FME Gregoire /=
654547479/Huawei is informed ","cedric.tiani@matech-cameroun.com","128","31=
-05-2025 15:14:13","MATECH CMR"
"Closed Complete","Site Down","CTR_066","IHS_YND_367","NOCINC0005148894","M=
andoumba OCM","","31-05-2025 15:13:39","31-05-2025 14:58:27","31-05-2025 16=
:24:36","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Site went down due to work of SS HIS Felix Zambe on site =
(Securing transmission )//End of work","christelle.ngonga@matech-cameroun.c=
om","1226935","31-05-2025 15:13:39","MATECH CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0005148891","N=
kenglikok","","31-05-2025 15:13:03","31-05-2025 14:58:27","31-05-2025 16:24=
:36","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Site went down due to work of SS HIS Felix Zambe on site (Se=
curing transmission )//End of work","christelle.ngonga@matech-cameroun.com"=
,"1226937","31-05-2025 15:13:03","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005148887","M=
ambine","","31-05-2025 15:12:21","31-05-2025 14:58:27","31-05-2025 15:59:40=
","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Site went down due to work of SS HIS Felix Zambe on site (Securing =
transmission )//End of work","christelle.ngonga@matech-cameroun.com","12269=
35","31-05-2025 15:12:21","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005148884","N=
kolfon Cimencam","","31-05-2025 15:11:15","31-05-2025 14:58:27","31-05-2025=
 15:34:55","No power issue on site U=3D54,5v site on Gen The TX fme George(=
697461814) from huawei is informed. Noticed that site is impacted by Afanoy=
a II(Not manage by HIS)","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","Affected by 3rd Party Site","Active//No po=
wer issue on site U=3D54,5v site on Gen The TX fme George(697461814) from h=
uawei is informed. Noticed that site is impacted by Afanoya II(Not manage b=
y HIS)","christelle.ngonga@matech-cameroun.com","1599","31-05-2025 15:11:15=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005148882","Angongo"=
,"","31-05-2025 15:10:48","31-05-2025 14:58:27","31-05-2025 16:24:36","Casc=
aded Incident from TTO5293727","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to work of SS HIS Feli=
x Zambe on site (Securing transmission )//End of work","system","1226936","=
31-05-2025 15:10:48","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0005148872","E=
beba","","31-05-2025 15:10:10","31-05-2025 14:58:27","31-05-2025 16:24:36",=
"","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Site went down due to work of SS HIS Felix Zambe on site (Securing tr=
ansmission )//End of work","ludivine.ngamaleu@ihstowers.com","1226937","31-=
05-2025 15:10:10","MATECH CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0005148843","Don=
ga","","31-05-2025 15:04:08","31-05-2025 15:02:35","31-05-2025 17:22:25","A=
ctive//No power issue with U=3D48V //site on Gen THe fme tx Gregoire 652070=
658 from Huawei is informed","Parker Tchoup","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue with U=3D48V //site on Gen THe fme tx Gregoire 652070658 from Huawei i=
s informed","christelle.ngonga@matech-cameroun.com","94","31-05-2025 15:04:=
08","MATECH CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0005148793","Mat=
sari","","31-05-2025 14:59:19","31-05-2025 14:57:13","31-05-2025 14:58:08",=
"No power issue on site with Ubaie=3D53.8V site on Gen ,The Tx Fme Gregoire=
( 652070658)from Huawei is informed","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site with Ubaie=3D53.8V site on Gen ,The Tx Fme Gregoire( 652070658=
)from Huawei is informed","christelle.ngonga@matech-cameroun.com","127","31=
-05-2025 14:59:19","MATECH CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0005148713","OKO=
A Peage","IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_350, =
IHS_YND_335","31-05-2025 14:43:33","31-05-2025 14:42:27","31-05-2025 16:24:=
42","Site went down due to work of SS HIS Felix Zambe on site (Securing tra=
nsmission )//End of work","Fanda Brice","Installation Activity","Passive","=
Planned Activity","Installation Activity","Site went down due to work of SS=
 HIS Felix Zambe on site (Securing transmission )//End of work","christelle=
.ngonga@matech-cameroun.com","2446","31-05-2025 14:43:33","MATECH CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0005148678","B=
ATA-Mokolo","","31-05-2025 14:38:57","31-05-2025 14:09:48","31-05-2025 16:5=
1:34","Grid Only, No space to deploy // Grid return","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to dep=
loy // Grid return","christelle.ngonga@matech-cameroun.com","1750","31-05-2=
025 14:38:57","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005148549","Aha=
la Echangeur","","31-05-2025 14:17:51","31-05-2025 11:57:38","31-05-2025 15=
:24:30","Grid outage, site went down because Gen failed to start due to GE =
contactor faulty // He blocked GE contactor, Site on Grid","MINKA NICOLAS",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outag=
e, site went down because Gen failed to start due to GE contactor faulty //=
 He blocked GE contactor, Site on Grid","franck.nkomot@matech-cameroun.com"=
,"8414","31-05-2025 14:17:51","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005148467","C=
omplexe-BEAC","","31-05-2025 13:59:20","31-05-2025 13:58:44","31-05-2025 14=
:07:37","fme jovi is on the way after Mvog-manga","Albran Byorel","Cascade =
Outage","Passive","Cascade Passive","Cascade Passive","Grid Outage //Grid R=
eturn","edwige.kapawo@matech-cameroun.com","878820","31-05-2025 13:59:20","=
MATECH CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0005148463","E=
kie-Elegance","IHS_YND_159","31-05-2025 13:58:49","31-05-2025 13:58:44","31=
-05-2025 14:07:37","Grid Outage //Grid Return","Albran Byorel","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage //Grid =
Return","edwige.kapawo@matech-cameroun.com","6","31-05-2025 13:58:49","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0005148450","M=
ini-Ferme","","31-05-2025 13:56:11","31-05-2025 13:54:04","31-05-2025 16:37=
:38","Grid Only, No space to deploy MGE //Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to d=
eploy MGE //Grid return","edwige.kapawo@matech-cameroun.com","128","31-05-2=
025 13:56:11","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0005148248","H=
-Progres","","31-05-2025 13:20:40","31-05-2025 13:18:32","31-05-2025 16:49:=
32","Grid Only, No space to deploy MGE //Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to de=
ploy MGE //Grid return","edwige.kapawo@matech-cameroun.com","129","31-05-20=
25 13:20:40","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005148218","Mvo=
g-Manga","","31-05-2025 13:14:00","31-05-2025 13:08:20","31-05-2025 15:26:1=
3","Grid outage site went down due to PWC dysunction//He reset it and site =
on Gen","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier=
 Module Overloaded","Grid outage site went down due to PWC dysunction//He r=
eset it and site on Gen","franck.nkomot@matech-cameroun.com","342","31-05-2=
025 13:14:00","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0005148157","B=
ATA Mokolo OCM","","31-05-2025 13:02:19","31-05-2025 12:59:05","31-05-2025 =
16:56:49","Grid Only, No space to deploy MGE //Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space=
 to deploy MGE //Grid return","edwige.kapawo@matech-cameroun.com","195","31=
-05-2025 13:02:19","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005148135","OBA=
M NGOLA OCM","","31-05-2025 12:56:01","31-05-2025 12:53:23","31-05-2025 12:=
59:52","Grid outage, site went down due to Grid bad voltage //  Gen automat=
ically started","MINKA NICOLAS","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Grid outage, site went down due to Grid bad =
voltage //  Gen automatically started","franck.nkomot@matech-cameroun.com",=
"159","31-05-2025 12:56:01","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005147990","EKI=
E","","31-05-2025 12:34:47","31-05-2025 12:32:39","31-05-2025 14:00:44","Si=
te went down because gen start and stopped due to grid bad voltage // Gen s=
tarted manually","Albran Byorel","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Site went down because gen start and stoppe=
d due to grid bad voltage // Gen started manually","franck.nkomot@matech-ca=
meroun.com","129","31-05-2025 12:34:47","MATECH CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0005147743","L=
eboudi","","31-05-2025 12:06:02","31-05-2025 11:56:06","31-05-2025 13:35:21=
","Active // no power issue, site is on Grid with Ubaie=3D54.33V, Mohamadou=
(691144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // no power issue, site is on Grid with Ubaie=3D54.33V, Mohamadou(=
691144435) from Huawei is informed.","edwige.kapawo@matech-cameroun.com","4=
323","31-05-2025 12:06:02","MATECH CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0005147742","MES=
SAME NDONGO 1162","","31-05-2025 12:05:43","31-05-2025 12:02:32","31-05-202=
5 13:18:42","Grid outage,site went down because gen failed to start due to =
Gen card Faulty// He started Gen manually","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down =
because gen failed to start due to Gen card Faulty// He started Gen manuall=
y","franck.nkomot@matech-cameroun.com","192","31-05-2025 12:05:43","MATECH =
CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0005147727","N=
koa Ayos","","31-05-2025 12:01:18","31-05-2025 11:56:06","31-05-2025 13:35:=
54","Grid outage, site went down due to Grid bad voltage // Gen automatical=
ly started","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Grid outage, site went down due to Grid bad volt=
age // Gen automatically started","edwige.kapawo@matech-cameroun.com","313"=
,"31-05-2025 12:01:18","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005147353","N=
koabang Ebolmedjock","","31-05-2025 10:51:28","31-05-2025 10:42:59","31-05-=
2025 11:24:00","Grid outage, site went down because gen start and stopped d=
ue to gen Overload (15Kva, 200A) // Grid Return","Mba Lazare Herve","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went =
down because gen start and stopped due to gen Overload (15Kva, 200A) // Gri=
d Return","edwige.kapawo@matech-cameroun.com","510","31-05-2025 10:51:28","=
MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005147265","Mok=
olo Yaounde","","31-05-2025 10:38:29","31-05-2025 10:37:25","31-05-2025 10:=
38:25","Active // No power issue Ubay: 54V site on grid. The Tx FME Eloundo=
u Bertrand (693212405) from Huawei is informed","","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue Ubay: 54V site on grid. The Tx FME Eloundou Bertrand (69321240=
5) from Huawei is informed","franck.nkomot@matech-cameroun.com","66","31-05=
-2025 10:38:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005147260","MEHANDAN=
","","31-05-2025 10:36:12","31-05-2025 10:32:48","31-05-2025 10:34:16","Cas=
caded Incident from TTO5291920","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
884864","31-05-2025 10:36:13","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005147253","O=
dza II OCM","IHS_YND_528","31-05-2025 10:34:54","31-05-2025 10:32:48","31-0=
5-2025 10:34:16","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","edwige.kapawo@matech-cameroun.com","128","31-05-2025 10:34:54"=
,"MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005147222","SIM=
BOCK BONAMBAPE","","31-05-2025 10:28:15","31-05-2025 10:26:47","31-05-2025 =
10:30:58","Grid Outage, Site went down before Gen start due to poor backup =
// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid Outage, Site went down before Gen st=
art due to poor backup // Grid return","franck.nkomot@matech-cameroun.com",=
"89","31-05-2025 10:28:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0005147202","Nomayos-=
IHS","","31-05-2025 10:24:11","31-05-2025 10:17:19","31-05-2025 11:09:35","=
Cascaded Incident from TTO5291798","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site Went Down due to Work ( PM) SS F=
elix ZAMBE IHS was on site for Work // End of work","system","1222162","31-=
05-2025 10:24:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005147203","Mambine"=
,"","31-05-2025 10:24:11","31-05-2025 10:17:19","31-05-2025 11:09:35","Casc=
aded Incident from TTO5291798","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site Went Down due to Work ( PM) SS Felix=
 ZAMBE IHS was on site for Work // End of work","system","1222165","31-05-2=
025 10:24:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005147204","Angongo"=
,"","31-05-2025 10:24:11","31-05-2025 10:17:19","31-05-2025 11:09:35","Casc=
aded Incident from TTO5291798","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site Went Down due to Work ( PM) SS Felix=
 ZAMBE IHS was on site for Work // End of work","system","1222163","31-05-2=
025 10:24:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005147205","Nkongtoc=
k","","31-05-2025 10:24:11","31-05-2025 10:17:19","31-05-2025 11:09:35","Ca=
scaded Incident from TTO5291798","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site Went Down due to Work ( PM) SS=
 Felix ZAMBE IHS was on site for Work // End of work","system","1222161","3=
1-05-2025 10:24:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005147201","Ebeba","=
","31-05-2025 10:24:10","31-05-2025 10:17:19","31-05-2025 11:09:35","Cascad=
ed Incident from TTO5291798","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site Went Down due to Work ( PM) SS Felix Z=
AMBE IHS was on site for Work // End of work","system","1222163","31-05-202=
5 10:24:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0005147200","Nkenglik=
ok","","31-05-2025 10:24:10","31-05-2025 10:17:19","31-05-2025 11:09:35","C=
ascaded Incident from TTO5291798","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site Went Down due to Work ( PM) S=
S Felix ZAMBE IHS was on site for Work // End of work","system","1222161","=
31-05-2025 10:24:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0005147199","Mbankomo=
 IHS","","31-05-2025 10:24:10","31-05-2025 10:17:19","31-05-2025 11:09:35",=
"Cascaded Incident from TTO5291798","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site Went Down due to Work ( PM) SS =
Felix ZAMBE IHS was on site for Work // End of work","system","1222164","31=
-05-2025 10:24:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0005147198","Mandoumb=
a OCM","","31-05-2025 10:24:10","31-05-2025 10:17:19","31-05-2025 11:09:35"=
,"Cascaded Incident from TTO5291798","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site Went Down due to Work ( PM=
) SS Felix ZAMBE IHS was on site for Work // End of work","system","1222164=
","31-05-2025 10:24:10","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0005147138","O=
KOA Peage","IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_697=
, IHS_YND_350, IHS_YND_335, IHS_YND_349","31-05-2025 10:21:30","31-05-2025 =
10:17:19","31-05-2025 12:18:49","Site Went Down due to Work ( PM) SS Felix =
ZAMBE IHS was on site for Work // End of work","Fanda Brice","Installation =
Activity","Passive","Planned Activity","Installation Activity","Site Went D=
own due to Work ( PM) SS Felix ZAMBE IHS was on site for Work // End of wor=
k","edwige.kapawo@matech-cameroun.com","252","31-05-2025 10:21:30","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005147127","Ahala","=
","31-05-2025 10:19:34","31-05-2025 10:16:19","31-05-2025 10:43:45","Cascad=
ed Incident from TTO5291774","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage site went down due to Gen ov=
erload (17KVA, 240A) SS HIS Felix Zambe is informed and confirmed// He redu=
ce load","system","885804","31-05-2025 10:19:34","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005147117","M=
eyo","IHS_YND_257","31-05-2025 10:18:27","31-05-2025 10:16:19","31-05-2025 =
10:43:45","Grid outage site went down due to Gen overload (17KVA, 240A) SS =
HIS Felix Zambe is informed and confirmed// He reduce load","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage si=
te went down due to Gen overload (17KVA, 240A) SS HIS Felix Zambe is inform=
ed and confirmed// He reduce load","edwige.kapawo@matech-cameroun.com","129=
","31-05-2025 10:18:27","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005147102","Mon=
tee Jouvence","","31-05-2025 10:14:51","31-05-2025 10:00:34","31-05-2025 13=
:22:34","Grid outage gen failed to start due to alarm high temp//We add wat=
er and gen manually started","Hyemafo Gildas","Equipment Repair","Passive",=
"ACDG Gen","Gen Temp High","Grid outage gen failed to start due to alarm hi=
gh temp//We add water and gen manually started","franck.nkomot@matech-camer=
oun.com","858","31-05-2025 10:14:51","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005147096","Acc=
acia New","","31-05-2025 10:13:24","31-05-2025 10:08:58","31-05-2025 14:50:=
56","Grid outage, no space to deploy a mobil gen // Grid restortion","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e, no space to deploy a mobil gen // Grid restortion","franck.nkomot@matech=
-cameroun.com","268","31-05-2025 10:13:24","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005147093","SAA=
 Entrance","","31-05-2025 10:12:37","31-05-2025 10:03:29","31-05-2025 10:15=
:29","Grid outage, site went down due to Grid bad voltage // GRID RETURN","=
Parker Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid outage, site went down due to Grid bad voltage // GRID R=
ETURN","franck.nkomot@matech-cameroun.com","550","31-05-2025 10:12:37","MAT=
ECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005146866","Aha=
la Echangeur","","31-05-2025 09:27:45","31-05-2025 09:22:37","31-05-2025 11=
:12:37","Site went down because gen stopped with low oil pressure//he added=
 oil and started the gen","MINKA NICOLAS","Equipment Repair","Passive","ACD=
G Gen","ACDG - Low Oil Pressure","Site went down because gen stopped with l=
ow oil pressure//he added oil and started the gen","franck.nkomot@matech-ca=
meroun.com","309","31-05-2025 09:27:45","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005146862","C=
rf-Nsam","","31-05-2025 09:25:53","31-05-2025 09:24:59","31-05-2025 09:51:2=
1","Active//No power issue on site Ubaie =3D53.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","edwige.kapawo@matech-cameroun.com","55","=
31-05-2025 09:25:53","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005146728","M=
vog-Manga","","31-05-2025 08:59:14","31-05-2025 08:56:59","31-05-2025 09:48=
:17","Grid outage site went down due to PWC dysunction//He reset it and sit=
e on Gen","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Grid outage site went down due to PWC dysunction//He=
 reset it and site on Gen","edwige.kapawo@matech-cameroun.com","137","31-05=
-2025 08:59:14","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005146718","Nko=
abang Alembe","","31-05-2025 08:56:50","31-05-2025 08:46:29","31-05-2025 12=
:12:29","site went down due to insufficiency of rectifiers IHS SS Alphonse =
is informed//site stabilized","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","site went down due to insufficiency of r=
ectifiers IHS SS Alphonse is informed//site stabilized","edwige.kapawo@mate=
ch-cameroun.com","621","31-05-2025 08:56:50","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005146595","C=
omplexe-BEAC","","31-05-2025 08:28:47","31-05-2025 08:25:40","31-05-2025 08=
:29:40","Grid outage, Site went down before Gen start due to Poor battery b=
ackup // Grid return","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to Poor battery backup // Grid return","franck.nkomot@matech-c=
ameroun.com","188","31-05-2025 08:28:47","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005146583","Men=
dong3","","31-05-2025 08:24:07","31-05-2025 08:19:58","31-05-2025 12:52:12"=
,"Grid Outage No space to deploy  MGE. // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid Outage No space to =
deploy  MGE. // Grid return","franck.nkomot@matech-cameroun.com","250","31-=
05-2025 08:24:07","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005146434","B=
arriere IHS","","31-05-2025 07:58:57","31-05-2025 07:56:44","31-05-2025 08:=
01:22","Grid Fluctuations; Site went Down due to Gen overload(15Kva, 200A) =
SS IHS FELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid Fluctuations; Site wen=
t Down due to Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // G=
rid return","edwige.kapawo@matech-cameroun.com","135","31-05-2025 07:58:57"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005146349","M=
essassi 2","","31-05-2025 07:55:02","31-05-2025 07:53:59","31-05-2025 08:02=
:58","Active // No power issue Ubaie:54.1 V site on Grid, TX fme symphorien=
 /650257151 from huawei is informed.","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue Ubaie:54.1 V site on Grid, TX fme symphorien /650257151 f=
rom huawei is informed.","edwige.kapawo@matech-cameroun.com","65","31-05-20=
25 07:55:02","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005146340","E=
vodoula OCM","","31-05-2025 07:50:54","31-05-2025 07:49:59","31-05-2025 08:=
24:56","Grid outage, site went down because gen failed to start due to grid=
 contactor faulty // He bypassed grid contactor and gen manually started","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","ATS=
-AMF Issue","Grid outage, site went down because gen failed to start due to=
 grid contactor faulty // He bypassed grid contactor and gen manually start=
ed","edwige.kapawo@matech-cameroun.com","56","31-05-2025 07:50:54","MATECH =
CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005146219","A=
wae Ewonkan","","31-05-2025 07:30:35","31-05-2025 07:29:59","31-05-2025 12:=
41:38","Site went Dowwn due to  Gen Overload (20Kva, Iload 225 A)IHS SS Alp=
honse is informed // Grid return","Albran Byorel","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Site went Dowwn due to  Gen Overload (20K=
va, Iload 225 A)IHS SS Alphonse is informed // Grid return","edwige.kapawo@=
matech-cameroun.com","38","31-05-2025 07:30:35","MATECH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0005146217","Lob=
o 2","","31-05-2025 07:29:25","31-05-2025 07:23:13","31-05-2025 12:33:59","=
Site went down due to 02/03 rectifier dysfonction // He replaced 02 rectifi=
ers","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to 02/03 rectifier dysfonction // He r=
eplaced 02 rectifiers","edwige.kapawo@matech-cameroun.com","373","31-05-202=
5 07:29:25","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005146102","Jou=
vence Mbenda","","31-05-2025 07:12:37","31-05-2025 07:10:28","31-05-2025 08=
:04:03","Grid outage.gen start and stopped due to alarm""high temp""//We ad=
ded water and gen manually started","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age.gen start and stopped due to alarm""high temp""//We added water and gen=
 manually started","franck.nkomot@matech-cameroun.com","130","31-05-2025 07=
:12:37","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005145976","SIM=
BOCK BONAMBAPE","","31-05-2025 06:53:42","31-05-2025 06:49:33","31-05-2025 =
06:53:04","Grid outage, Site went down before Gen start due to poor backup =
// Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Grid return","edwige.kapawo@matech-cameroun.com",=
"250","31-05-2025 06:53:42","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005145969","E=
mana Lycee","","31-05-2025 06:51:21","31-05-2025 06:48:13","31-05-2025 07:0=
2:32","Wrong ticket","Fabrice Pouakam","Incorrectly Logged Tickets","Error"=
,"Error","Error","Wrong ticket","edwige.kapawo@matech-cameroun.com","189","=
31-05-2025 06:51:21","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005145822","N=
kolfon Cimencam","","31-05-2025 06:30:03","31-05-2025 06:25:57","31-05-2025=
 06:32:02","No power issue, Site impacted by Afanoya-II","Hyemafo Gildas","=
Customer Equipment Failure","Active","Active Equipment Failure","Affected b=
y 3rd Party Site","No power issue, Site impacted by Afanoya-II","edwige.kap=
awo@matech-cameroun.com","247","31-05-2025 06:30:03","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005145808","T=
alla Monatele","","31-05-2025 06:24:54","31-05-2025 06:20:48","31-05-2025 0=
6:49:54","Active // No power issue, site is on grid with Ubaie:55.2V, Grego=
ire (654547479 /Huawei) is informed","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // =
No power issue, site is on grid with Ubaie:55.2V, Gregoire (654547479 /Huaw=
ei) is informed","edwige.kapawo@matech-cameroun.com","247","31-05-2025 06:2=
4:54","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005145459","N=
gouetou","","31-05-2025 05:25:56","31-05-2025 05:15:59","31-05-2025 05:30:0=
9","No power issue site on Gen, with Ubay=3D52.4V. The Tx Fme Gregoire (654=
547479) from Huawei is informed","Parker Tchoup","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 site on Gen, with Ubay=3D52.4V. The Tx Fme Gregoire (654547479) from Huawe=
i is informed","loic.noumsi@matech-cameroun.com","599","31-05-2025 05:25:56=
","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005145391","Jou=
vence Mbenda","","31-05-2025 04:45:37","31-05-2025 04:38:29","31-05-2025 05=
:30:56","Grid outage site went down because Gen stopped with alarm HIGH tem=
p // He added water and Gen manually started","Hyemafo Gildas","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"Grid outage site went down because Gen stopped with alarm HIGH temp // He=
 added water and Gen manually started","loic.noumsi@matech-cameroun.com","4=
28","31-05-2025 04:45:37","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005145199","M=
ambine","","31-05-2025 04:31:30","31-05-2025 04:25:24","31-05-2025 04:46:48=
","Grid outage, site went down because gen ran untill fuel shortage // Refu=
elling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage, site went down because gen ran untill fuel shortage // Refue=
lling done","loic.noumsi@matech-cameroun.com","367","31-05-2025 04:31:30","=
MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0005145187","Evo=
doula MTN","","31-05-2025 04:27:08","31-05-2025 04:20:58","31-05-2025 04:40=
:06","Grid outage, site went down because Gen failed to start due to automa=
tism dysfunctionning // He reseted it and manually started Gen","TIENTCHEU =
NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Grid outage, site went down because Gen failed to start due to automat=
ism dysunctionning // He reseted it and manually started Gen","loic.noumsi@=
matech-cameroun.com","371","31-05-2025 04:27:08","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005145143","B=
arriere IHS","","31-05-2025 04:07:45","31-05-2025 04:02:45","31-05-2025 07:=
40:24","Grid Fluctuations; fme Gildas report that Gen overload(15Kva, 200A)=
 SS IHS FELIX ZAMBE is informed // Grid return","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid Fluctuations; fme Gil=
das report that Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed //=
 Grid return","loic.noumsi@matech-cameroun.com","302","31-05-2025 04:07:45"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005145023","O=
dza-PK10","","31-05-2025 03:52:47","31-05-2025 03:48:40","31-05-2025 05:45:=
56","Site went down because Gen failed to start due to ATS not configured /=
/ He configured it and reseted ATS","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","Site went down because Gen failed to=
 start due to ATS not configured // He configured it and reseted ATS","loic=
.noumsi@matech-cameroun.com","247","31-05-2025 03:52:47","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005144616","Mon=
tee Jouvence","","31-05-2025 02:29:21","31-05-2025 02:26:59","31-05-2025 03=
:44:16","Grid outage, site went down because Gen started and stopped due to=
 charger batt Gen faulty // He started Gen with an external batttery ","Hye=
mafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batt=
ery","Grid outage, site went down because Gen started and stopped due to ch=
arger batt Gen faulty // He started Gen with an external batttery ","loic.n=
oumsi@matech-cameroun.com","143","31-05-2025 02:29:21","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005144605","T=
alla Monatele","","31-05-2025 02:25:42","31-05-2025 02:22:30","31-05-2025 0=
4:33:16","No power issue, site is on grid with Ubaie:51.3V, Gregoire (65454=
7479 /Huawei) is informed","Parker Tchoup","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site=
 is on grid with Ubaie:51.3V, Gregoire (654547479 /Huawei) is informed","lo=
ic.noumsi@matech-cameroun.com","193","31-05-2025 02:25:42","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005144571","Nko=
g-Edzen","","31-05-2025 02:15:11","31-05-2025 02:10:03","31-05-2025 04:15:4=
4","No power issue on site, Site on Gen Ubay =3D 54.9V The Tx Fme Gregoire =
(654547479) from Huawei is informed.","Parker Tchoup","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site, Site on Gen Ubay =3D 54.9V The Tx Fme Gregoire (654547479) f=
rom Huawei is informed.","loic.noumsi@matech-cameroun.com","309","31-05-202=
5 02:15:11","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005144480","SIM=
BOCK BONAMBAPE","","31-05-2025 01:55:48","31-05-2025 01:52:38","31-05-2025 =
01:56:53","Grid outage, Site went down before Gen start due to poor backup =
// Gen automatically started","Hyemafo Gildas","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor backup // Gen automatically started","loic.no=
umsi@matech-cameroun.com","191","31-05-2025 01:55:48","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005144474","Ebo=
go","","31-05-2025 01:51:59","31-05-2025 01:47:36","31-05-2025 04:43:14","A=
ctive// No Power issue on site Ubaie 53.2V site on Grid, Julien /693095849 =
from Huawei is informed; Site up without intervention.","Siligap Boris","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active// No Power issue on site Ubaie 53.2V site on Grid, Julien /=
693095849 from Huawei is informed; Site up without intervention.","loic.nou=
msi@matech-cameroun.com","264","31-05-2025 01:51:59","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005144468","MBA=
LNGONG LYCEE","","31-05-2025 01:47:56","31-05-2025 01:45:50","31-05-2025 07=
:50:49","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid return","Fan=
da Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, Site went down because Gen stopped due to overload(9kva, 130A) SS IH=
S Felix Zambe is informed and confirmed // Grid return","loic.noumsi@matech=
-cameroun.com","127","31-05-2025 01:47:56","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005144410","S=
tade-Abega","","31-05-2025 01:36:02","31-05-2025 01:30:50","31-05-2025 02:3=
9:12","Active // No pwer issue, site is on grid with Ubaie=3D53.4V, Lionel =
adjep(655184876) from Huawei is informed","Mba Lazare Herve","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive // No pwer issue, site is on grid with Ubaie=3D53.4V, Lionel adjep(655=
184876) from Huawei is informed","loic.noumsi@matech-cameroun.com","313","3=
1-05-2025 01:36:02","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005144395","Nko=
abang Alembe","","31-05-2025 01:34:57","31-05-2025 01:28:49","31-05-2025 05=
:06:38","Grid outage,site went down due to rectifiers dysfunctionning on si=
te //He reseted it","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Grid outage,site went down due to rectifiers dysfu=
nctionning on site //He reseted it","loic.noumsi@matech-cameroun.com","368"=
,"31-05-2025 01:34:57","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005144365","SAA=
 Entrance","","31-05-2025 01:24:10","31-05-2025 01:18:46","31-05-2025 01:35=
:46","Grid outage, site went down due to Grid bad voltage // He bypassed Gr=
id and put site on Gen","Parker Tchoup","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","Grid outage, site went down due to G=
rid bad voltage // He bypassed Grid and put site on Gen","loic.noumsi@matec=
h-cameroun.com","325","31-05-2025 01:24:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005144348","SOA VILL=
AGE","","31-05-2025 01:17:10","31-05-2025 01:13:23","31-05-2025 01:56:25","=
Cascaded Incident from TTO5288827","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // He added water and manually =
start the gen","system","917661","31-05-2025 01:17:10","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005144332","S=
OA TOWN","IHS_YND_323","31-05-2025 01:16:29","31-05-2025 01:13:23","31-05-2=
025 01:56:25","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // He added water and manually start the gen","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Co=
olant Level Issue","Grid outage, site went down because gen start and stopp=
ed with high temp alarm // He added water and manually start the gen","loic=
.noumsi@matech-cameroun.com","188","31-05-2025 01:16:29","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005144293","N=
omayos montee Meche","","31-05-2025 00:58:44","31-05-2025 00:56:21","31-05-=
2025 01:00:44","Grid outage, site went down before Gen started due to poor =
backup battery // Grid returned","Fanda Brice","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before Gen started due to poor backup battery // Grid returned","loic.noum=
si@matech-cameroun.com","144","31-05-2025 00:58:44","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005144137","O=
dza II OCM","","31-05-2025 00:33:19","31-05-2025 00:29:38","31-05-2025 00:3=
1:37","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Site stabilised","Albran Byorel","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down because gen failed to start due to PWC ZTE malfunction // Site stabili=
sed","loic.noumsi@matech-cameroun.com","223","31-05-2025 00:33:19","MATECH =
CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005144042","O=
LAMA","","31-05-2025 00:14:51","29-05-2025 17:34:15","29-05-2025 18:13:13",=
"Backtracking//Active // No power issue on site Ubaie =3D54.9V site on Gen =
The TX FME Henri (699949693) from Huawei is informed.Noticed that it is a r=
epetitve issue.","Fanda Brice","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Backtracking","loic.noumsi@matec=
h-cameroun.com","110436","31-05-2025 00:14:51","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005144015","OBA=
M NGOLA OCM","","31-05-2025 00:01:31","30-05-2025 23:55:17","31-05-2025 00:=
15:08","Grid outage, site went down due to Grid bad voltage (lack of 02 pha=
ses) and card Ge faulty //He bypassed Grid and started Gen manually","MINKA=
 NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid outage, site went down due to Grid bad voltage (lack of 02 ph=
ases) and card Ge faulty //He bypassed Grid and started Gen manually","loic=
.noumsi@matech-cameroun.com","375","31-05-2025 00:01:31","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005143798","B=
arriere","","30-05-2025 23:05:47","30-05-2025 23:01:29","30-05-2025 23:10:0=
4","No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/=
Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
bay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is informed.","loic.=
noumsi@matech-cameroun.com","259","30-05-2025 23:05:47","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0005143780","NKO=
NGKARAK","","30-05-2025 22:56:44","30-05-2025 22:54:37","30-05-2025 23:25:5=
4","Grid outage, Site went down because Gen started and stopped due to fuel=
 shortage // Refuelling done","TIENTCHEU NZETCHIEU GAEL","Fuel Outage","Pas=
sive","Diesel","Diesel Outage","Grid outage, Site went down because Gen sta=
rted and stopped due to fuel shortage // Refuelling done","loic.noumsi@mate=
ch-cameroun.com","128","30-05-2025 22:56:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0005143596","AFEME NO=
RD","","30-05-2025 22:21:24","30-05-2025 22:15:38","30-05-2025 22:23:42","C=
ascaded Incident from TTO5287998","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active: no power issue, site=
 is on grid with Ubaie=3D54.1V, Mohamadou((691144435) from Huawei is inform=
ed,","system","928136","30-05-2025 22:21:24","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005143593","Mba=
nkolo petit paris","IHS_YND_519","30-05-2025 22:20:48","30-05-2025 22:15:38=
","31-05-2025 02:23:42","Active: no power issue, site is on grid with Ubaie=
=3D54.1V, Mohamadou((691144435) from Huawei is informed,","Mboua Thierry","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active: no power issue, site is on grid with Ubaie=3D54.1V, Moha=
madou((691144435) from Huawei is informed,","cedric.tiani@matech-cameroun.c=
om","311","30-05-2025 22:20:48","MATECH CMR"
"Closed Complete","Site Down","T1323","IHS_YND_288","NOCINC0005143533","Mey=
ong Plateau","","30-05-2025 22:10:51","30-05-2025 21:59:42","30-05-2025 23:=
58:06","BACKTRACKING// Site went down because Gen started and stopped due t=
o high temp alarm // He added water and started GEN manually","TIENTCHEU NZ=
ETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine T=
emp - Coolant Level Issue","BACKTRACKING// Site went down because Gen start=
ed and stopped due to high temp alarm // He added water and started GEN man=
ually","cedric.tiani@matech-cameroun.com","669","30-05-2025 22:10:51","MATE=
CH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005143526","NYO=
M 2 IHS","","30-05-2025 22:10:03","30-05-2025 21:48:50","30-05-2025 23:44:4=
1","Site went down due to disjunction of CB (125A) in pwc ZTE // He rearmed=
 it, site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Control =
Panel","Circuit Breaker Tripped","Site went down due to disjunction of CB (=
125A) in pwc ZTE // He rearmed it, site on Grid","cedric.tiani@matech-camer=
oun.com","1274","30-05-2025 22:10:03","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005143522","OBA=
M NGOLA OCM","","30-05-2025 22:09:27","30-05-2025 21:34:06","30-05-2025 23:=
48:25","Backtracking// Grid outage, site went down due to Grid bad voltage =
(lack of 02 phases) and card Ge faulty // He did bridge on the good phase",=
"MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Backtracking// Grid outage, site went down due to Grid bad v=
oltage (lack of 02 phases) and card Ge faulty // He did bridge on the good =
phase","cedric.tiani@matech-cameroun.com","2122","30-05-2025 22:09:27","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005143377","E=
ssomba","","30-05-2025 21:47:28","30-05-2025 21:46:10","30-05-2025 21:47:29=
","Site went down because 03/06 rectifiers dysfunctionned //Site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down because 03/06 rectifiers dysfunctionned //Site stabil=
ised","vanel.mbiada@matech-cameroun.com","80","30-05-2025 21:47:28","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0005143216","AFEME NO=
RD","","30-05-2025 21:27:05","30-05-2025 21:23:03","30-05-2025 21:28:53","C=
ascaded Incident from TTO5287579","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active: no power issue, site=
 is on grid with Ubaie=3D54.1V, Mohamadou((691144435) from Huawie is inform=
ed,","system","925350","30-05-2025 21:27:05","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005143211","Mba=
nkolo petit paris","IHS_YND_519","30-05-2025 21:26:13","30-05-2025 21:23:03=
","30-05-2025 21:28:53","Active: no power issue, site is on grid with Ubaie=
=3D54.1V, Mohamadou((691144435) from Huawie is informed,","Mboua Thierry","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active: no power issue, site is on grid with Ubaie=3D54.1V, Moha=
madou((691144435) from Huawie is informed,","cedric.tiani@matech-cameroun.c=
om","190","30-05-2025 21:26:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0005143056","AFEME NO=
RD","","30-05-2025 21:01:00","30-05-2025 20:53:06","30-05-2025 20:59:04","C=
ascaded Incident from TTO5287393","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active: no power issue, site=
 is on grid with Ubaie=3D54.1V, Mohamadou((691144435) from Huawie is inform=
ed,","system","1212924","30-05-2025 21:01:00","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005143044","Mba=
nkolo petit paris","IHS_YND_519","30-05-2025 20:58:23","30-05-2025 20:53:06=
","30-05-2025 20:59:04","Active: no power issue, site is on grid with Ubaie=
=3D54.1V, Mohamadou((691144435) from Huawie is informed,","Mboua Thierry","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active: no power issue, site is on grid with Ubaie=3D54.1V, Moha=
madou((691144435) from Huawie is informed,","cedric.tiani@matech-cameroun.c=
om","318","30-05-2025 20:58:23","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005142745","A=
wae Ewonkan","","30-05-2025 20:16:09","30-05-2025 20:11:49","30-05-2025 23:=
24:38","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid returned","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid r=
eturned","vanel.mbiada@matech-cameroun.com","262","30-05-2025 20:16:09","MA=
TECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0005142451","Eke=
kam","","30-05-2025 19:54:18","30-05-2025 19:52:06","30-05-2025 20:27:31","=
Active//No power issue site and with Ubaie=3D53.9 V site on Gen The FME TX =
Mouamadou/658791013 //From is informed","TIENTCHEU NZETCHIEU GAEL","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active//No power issue site and with Ubaie=3D53.9 V site on Gen The FME=
 TX Mouamadou/658791013 //From is informed","cedric.tiani@matech-cameroun.c=
om","133","30-05-2025 19:54:18","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005142262","Ron=
d Point Express1114","","30-05-2025 19:31:37","30-05-2025 19:30:23","30-05-=
2025 20:28:32","Active: No power issue, site is on grid with Ubaie=3D54,5V,=
 Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active: No power issue, site is on grid with Ubaie=3D54,5V, Mbah hosiah(=
699699694) from Huawei is informed","cedric.tiani@matech-cameroun.com","75"=
,"30-05-2025 19:31:37","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005142248","Nko=
abang Ebolmedjock","","30-05-2025 19:30:25","30-05-2025 19:26:18","31-05-20=
25 10:21:18","Grid outage, site went down because gen start and stopped due=
 to gen Overload (15Kva, 200A)//Grid return","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down=
 because gen start and stopped due to gen Overload (15Kva, 200A)//Grid retu=
rn","cedric.tiani@matech-cameroun.com","249","30-05-2025 19:30:25","MATECH =
CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005142014","O=
LAMA","","30-05-2025 18:56:03","30-05-2025 18:42:25","30-05-2025 18:57:33",=
"Active // No power issue on site Ubaie =3D54.9V site on Gen The TX FME Hen=
ri (699949693) from Huawei is informed.Noticed that it is a repetitve issue=
.","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active // No power issue on site Ubaie =3D54.9=
V site on Gen The TX FME Henri (699949693) from Huawei is informed.Noticed =
that it is a repetitve issue.","vanel.mbiada@matech-cameroun.com","819","30=
-05-2025 18:56:03","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005141662","M=
vog-Manga","","30-05-2025 17:56:08","30-05-2025 17:50:00","30-05-2025 19:36=
:09","Grid outage,site went down because Gen started and stopped due to ala=
rm *Overvoltage* //He reset the Gen card and manually stared the Gen","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage,site went down because Gen started and stopped due to alarm *Ov=
ervoltage* //He reset the Gen card and manually stared the Gen","vanel.mbia=
da@matech-cameroun.com","370","30-05-2025 17:56:08","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005141469","Nko=
abang Ebolmedjock","","30-05-2025 17:29:46","30-05-2025 17:29:37","30-05-20=
25 19:13:35","Grid outage, site went down because gen start and stopped due=
 to gen Overload (15Kva, 200A)//Grid return","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down=
 because gen start and stopped due to gen Overload (15Kva, 200A)//Grid retu=
rn","cedric.tiani@matech-cameroun.com","10","30-05-2025 17:29:46","MATECH C=
MR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0005141255","A=
FEME NORD","","30-05-2025 17:10:24","30-05-2025 17:06:13","30-05-2025 18:26=
:58","Site went down due to double dysjuction(80*80A)in PWC that feeds OCM =
and MTN due to charge increase //He rearmed it","TIENTCHEU NZETCHIEU GAEL",=
"Equipment Repair","Passive","Rectifier","Rectifier - Circuit Breaker","Sit=
e went down due to double dysjuction(80*80A)in PWC that feeds OCM and MTN d=
ue to charge increase //He rearmed it","vanel.mbiada@matech-cameroun.com","=
252","30-05-2025 17:10:24","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005141066","Mok=
olo Yaounde","","30-05-2025 16:42:18","30-05-2025 16:40:12","30-05-2025 16:=
42:50","Active // No power issue Ubay: 54.4 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.4 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","cedric.tiani@matech-cameroun.com","127",=
"30-05-2025 16:42:18","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005140982","C=
rf-Nsam","","30-05-2025 16:32:11","30-05-2025 16:22:56","30-05-2025 18:40:4=
8","Active//No power issue on site Ubaie =3D53.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","556","3=
0-05-2025 16:32:11","MATECH CMR"
"Closed Complete","Site Down","T1113","IHS_YND_105","NOCINC0005140854","Omn=
isport 3","","30-05-2025 16:15:28","30-05-2025 16:10:51","30-05-2025 16:18:=
58","Feme is on the way ETA=3D05:00PM","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active: no power issue, site is o=
n grid with Ubaie=3D54.6V, Armand Nguetsa  (650257151) from Huawei is infor=
med","cedric.tiani@matech-cameroun.com","943309","30-05-2025 16:15:28","MAT=
ECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005140852","Mfa=
ndena","IHS_YND_105","30-05-2025 16:14:58","30-05-2025 16:10:51","30-05-202=
5 16:18:58","Active: no power issue, site is on grid with Ubaie=3D54.6V, Ar=
mand Nguetsa  (650257151) from Huawei is informed","Delor Telezing","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: no power issue, site is on grid with Ubaie=3D54.6V, Armand Ngu=
etsa  (650257151) from Huawei is informed","cedric.tiani@matech-cameroun.co=
m","248","30-05-2025 16:14:58","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005140824","C=
rf-Nsam","","30-05-2025 16:10:06","30-05-2025 16:02:47","30-05-2025 16:12:4=
3","Active//No power issue on site Ubaie =3D53.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","vanel.mbiada@matech-cameroun.com","440","=
30-05-2025 16:10:06","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0005140760","K=
oweit City","","30-05-2025 15:56:02","30-05-2025 15:54:36","30-05-2025 16:5=
9:53","Site went down because landlord has forbidden to start the Gen SS HI=
S Francois Deffo is informed //Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Emergency Stop","Site went down because la=
ndlord has forbidden to start the Gen SS HIS Francois Deffo is informed //G=
rid return","vanel.mbiada@matech-cameroun.com","87","30-05-2025 15:56:02","=
MATECH CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0005140719","B=
ONAS YDE","","30-05-2025 15:49:12","30-05-2025 15:45:33","30-05-2025 16:08:=
10","down because Gen failed to start due to ATS dysfunctionning//He reset =
it and manually started the Gen","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","ATS-AMF Issue","down because Gen failed to start due to A=
TS dysfunctionning//He reset it and manually started the Gen","vanel.mbiada=
@matech-cameroun.com","220","30-05-2025 15:49:12","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005140684","Nko=
abang Ebolmedjock","","30-05-2025 15:42:50","30-05-2025 15:39:42","30-05-20=
25 16:40:37","Grid outage, site went down because gen start and stopped due=
 to gen Overload (15Kva, 200A)// Grid return","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went dow=
n because gen start and stopped due to gen Overload (15Kva, 200A)// Grid re=
turn","cedric.tiani@matech-cameroun.com","189","30-05-2025 15:42:50","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0005140574","C=
arington","","30-05-2025 15:36:23","30-05-2025 15:34:07","31-05-2025 12:17:=
15","Grid only, lessor refuses to deploy Gen // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid only, lessor =
refuses to deploy Gen // Grid return","vanel.mbiada@matech-cameroun.com","1=
38","30-05-2025 15:36:23","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005140528","Nko=
abang Ebolmedjock","","30-05-2025 15:32:36","30-05-2025 15:30:20","30-05-20=
25 15:33:51","Grid outage, site went down because gen start and stopped due=
 to gen Overload (15Kva, 200A) // Grid return","Mba Lazare Herve","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went do=
wn because gen start and stopped due to gen Overload (15Kva, 200A) // Grid =
return","cedric.tiani@matech-cameroun.com","137","30-05-2025 15:32:36","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0005140334","B=
ONAS YDE","","30-05-2025 15:11:07","30-05-2025 15:06:44","30-05-2025 15:35:=
31","Grid outage,site went down because Gen failed to start due to ATS dysf=
unctionning//He reset it and manually started the Gen","Paul BIBOUM","Equip=
ment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,site we=
nt down because Gen failed to start due to ATS dysfunctionning//He reset it=
 and manually started the Gen","vanel.mbiada@matech-cameroun.com","264","30=
-05-2025 15:11:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005140331","FOUGEROL=
E","","30-05-2025 15:10:10","30-05-2025 15:06:37","30-05-2025 18:13:05","Ca=
scaded Incident from TTO5284387","Siligap Boris","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active // no power issue, site is on gri=
d with Ubaie=3D53V, Symphorien(650257151) from Huawei is informed // Notice=
 dsijonction are the BTS OCM","system","947037","30-05-2025 15:10:10","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005140317","N=
gousso-Savana","IHS_YND_561","30-05-2025 15:09:27","30-05-2025 15:06:37","3=
0-05-2025 18:13:05","Active // no power issue, site is on grid with Ubaie=
=3D53V, Symphorien(650257151) from Huawei is informed // Notice dsijonction=
 are the BTS OCM","Siligap Boris","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active // no power issue, sit=
e is on grid with Ubaie=3D53V, Symphorien(650257151) from Huawei is informe=
d // Notice dsijonction are the BTS OCM","vanel.mbiada@matech-cameroun.com"=
,"170","30-05-2025 15:09:27","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0005140267","Awa=
e Ewonkan","","30-05-2025 15:01:19","30-05-2025 15:00:57","30-05-2025 15:22=
:25","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IH=
S SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid retur=
n","cedric.tiani@matech-cameroun.com","23","30-05-2025 15:01:19","MATECH CM=
R"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005140217","M=
essassi 2","","30-05-2025 14:52:21","30-05-2025 14:48:59","30-05-2025 14:52=
:31","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup // Grid return","cedric.tiani@matech-cameroun.com","204"=
,"30-05-2025 14:52:21","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005140205","Acc=
acia New","","30-05-2025 14:50:38","30-05-2025 14:45:29","30-05-2025 15:15:=
09","Site went down due to disjunction CB(80A) in PWC that feeds MTN due to=
 charges increase//He rearmed it","","Equipment Repair","Passive","Rectifie=
r","Rectifier - Circuit Breaker","Site went down due to disjunction CB(80A)=
 in PWC that feeds MTN due to charges increase//He rearmed it","cedric.tian=
i@matech-cameroun.com","311","30-05-2025 14:50:38","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005140125","OBA=
M NGOLA OCM","","30-05-2025 14:35:47","30-05-2025 14:33:35","30-05-2025 14:=
39:37","Grid fluctuation, site went down because Gen failed to start  due t=
o Grid bad voltage and card Ge faulty // Grid return","MINKA NICOLAS","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid f=
luctuation, site went down because Gen failed to start  due to Grid bad vol=
tage and card Ge faulty // Grid return","cedric.tiani@matech-cameroun.com",=
"133","30-05-2025 14:35:47","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005139943","Mes=
sassi 2","","30-05-2025 14:09:20","30-05-2025 14:02:14","30-05-2025 14:14:1=
1","Grid outage, Site went down before Gen start due to poor backup // Gen =
started automatically","Fabrice Pouakam","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen started automatically","gerard.tchang=
oue@matech-cameroun.com","427","30-05-2025 14:09:20","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005139864","Ron=
d Point Express1114","","30-05-2025 13:59:43","30-05-2025 13:54:35","30-05-=
2025 14:00:35","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","ge=
rard.tchangoue@matech-cameroun.com","309","30-05-2025 13:59:43","MATECH CMR=
"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005139580","MBA=
LNGONG LYCEE","","30-05-2025 13:16:39","30-05-2025 13:07:29","30-05-2025 13=
:37:29","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid returned","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","gerard.tchango=
ue@matech-cameroun.com","551","30-05-2025 13:16:39","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005139550","Odz=
a Minkan IHS","","30-05-2025 13:10:23","30-05-2025 13:06:16","30-05-2025 13=
:49:39","Grid fluctuation, Site went down because Gen failed to start due t=
o Grid bad voltage// Grid return, site stabilised","Albran Byorel","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation, Site went down because Gen failed to start due to Grid bad voltage=
// Grid return, site stabilised","gerard.tchangoue@matech-cameroun.com","24=
8","30-05-2025 13:10:23","MATECH CMR"
"Closed Complete","Site Down","T1113","IHS_YND_105","NOCINC0005139490","Omn=
isport 3","","30-05-2025 13:03:07","30-05-2025 12:58:56","30-05-2025 14:28:=
50","Grid outage, Site went down because Gen start and stopped with ""High =
temps ""alarm // he added water and manually start the Gen","Delor Telezing=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid outage, Site went down because Gen start and stopped w=
ith ""High temps ""alarm // he added water and manually start the Gen","edw=
ige.kapawo@matech-cameroun.com","252","30-05-2025 13:03:07","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0005139473","NTE=
MASSI","","30-05-2025 12:58:55","30-05-2025 12:55:59","30-05-2025 17:31:31"=
,"","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Grid Outage//Grid return","gerard.tchangoue@matech-cameroun.com",=
"954647","30-05-2025 12:58:55","MATECH CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0005139461","Ngo=
usso MTN","IHS_YND_187","30-05-2025 12:56:27","30-05-2025 12:55:59","30-05-=
2025 17:31:31","Grid Outage//Grid return","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid Outage//Grid return","edwige.kap=
awo@matech-cameroun.com","28","30-05-2025 12:56:27","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005139239","N=
koabang Ebolmedjock","","30-05-2025 12:20:36","30-05-2025 12:11:59","30-05-=
2025 12:22:15","No power issue , Site impacted by Nkolmesseng-Abom","Mba La=
zare Herve","Customer Equipment Failure","Active","Active Equipment Failure=
","Affected by 3rd Party Site","No power issue , Site impacted by Nkolmesse=
ng-Abom","edwige.kapawo@matech-cameroun.com","518","30-05-2025 12:20:36","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005139148","O=
LAMA","","30-05-2025 12:02:34","30-05-2025 12:01:24","30-05-2025 12:08:22",=
"Active // No power issue on site Ubaie =3D54.9V site on Gen The TX FME Hen=
ri (699949693) from Huawei is informed.Noticed that it is a repetitve issue=
.","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active // No power issue on site Ubaie =3D54.9=
V site on Gen The TX FME Henri (699949693) from Huawei is informed.Noticed =
that it is a repetitve issue.","edwige.kapawo@matech-cameroun.com","72","30=
-05-2025 12:02:34","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005139114","M=
essassi 2","","30-05-2025 11:58:55","30-05-2025 11:55:41","30-05-2025 12:04=
:22","Active // No power issue Ubaie:54.05 V site on Grid, TX fme symphorie=
n /650257151 from huawei is informed.","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue Ubaie:54.05 V site on Grid, TX fme symphorien /650257151=
 from huawei is informed.","edwige.kapawo@matech-cameroun.com","196","30-05=
-2025 11:58:55","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005139053","C=
rf-Nsam","","30-05-2025 11:49:23","30-05-2025 11:47:59","30-05-2025 11:50:2=
2","Active//No power issue on site Ubaie =3D53.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","edwige.kapawo@matech-cameroun.com","85","=
30-05-2025 11:49:23","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005139028","NYO=
M 2 IHS","","30-05-2025 11:44:14","30-05-2025 11:41:09","30-05-2025 12:11:1=
0","Grid outage, Site went down before Gen start due to poor backup // Grid=
 return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","gerard.tchangoue@matech-cameroun.com","18=
6","30-05-2025 11:44:14","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005139024","A=
wae Ewonkan","","30-05-2025 11:43:45","30-05-2025 11:42:59","30-05-2025 13:=
30:50","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid return","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid ret=
urn","edwige.kapawo@matech-cameroun.com","48","30-05-2025 11:43:45","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005139018","N=
kolfon Cimencam","","30-05-2025 11:41:36","30-05-2025 11:38:21","30-05-2025=
 11:42:46","No power issue, Site impacted by Afanoya-II","Hyemafo Gildas","=
Customer Equipment Failure","Active","Active Equipment Failure","Affected b=
y 3rd Party Site","No power issue, Site impacted by Afanoya-II","edwige.kap=
awo@matech-cameroun.com","196","30-05-2025 11:41:36","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005138911","OTE=
LE MTN","","30-05-2025 11:26:26","30-05-2025 11:18:02","30-05-2025 12:04:34=
","Grid outage,site went because Gen  started and stopped  due to alarm *lo=
w oil pressure* //He added oil and maually started with an external battery=
","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pre=
ssure","Grid outage,site went because Gen  started and stopped  due to alar=
m *low oil pressure* //He added oil and maually started with an external ba=
ttery","gerard.tchangoue@matech-cameroun.com","504","30-05-2025 11:26:26","=
MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0005138791","Djo=
nassi-Yde","","30-05-2025 11:15:49","30-05-2025 11:06:37","30-05-2025 11:38=
:56","Site went down due to 02/04 rectifier faulty on site SS IIHS bernard =
Atangana is confirm // he replaced 02 rectifiers","Fabrice Pouakam","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site went down due to=
 02/04 rectifier faulty on site SS IIHS bernard Atangana is confirm // he r=
eplaced 02 rectifiers","gerard.tchangoue@matech-cameroun.com","553","30-05-=
2025 11:15:49","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005138705","NYO=
M 2 IHS","","30-05-2025 10:58:51","30-05-2025 10:54:43","30-05-2025 11:03:3=
7","Grid outage, Site went down before Gen start due to poor backup // Grid=
 return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","gerard.tchangoue@matech-cameroun.com","24=
9","30-05-2025 10:58:51","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005138679","SAA=
 Entrance","","30-05-2025 10:55:21","30-05-2025 10:52:08","30-05-2025 11:00=
:53","Grid outage, site went down due to Grid bad voltage // GRID RETURN","=
Parker Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid outage, site went down due to Grid bad voltage // GRID R=
ETURN","gerard.tchangoue@matech-cameroun.com","194","30-05-2025 10:55:21","=
MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005138667","N=
YOM 2 IHS","","30-05-2025 10:52:57","30-05-2025 10:52:50","30-05-2025 10:54=
:22","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup // Grid return","edwige.kapawo@matech-cameroun.com","9",=
"30-05-2025 10:52:57","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005138609","M=
vog-Manga","","30-05-2025 10:39:37","30-05-2025 10:38:59","30-05-2025 11:19=
:39","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectif=
ier Cabinet","Grid outage, Site went down before Gen start due to poor back=
up // Grid return","edwige.kapawo@matech-cameroun.com","40","30-05-2025 10:=
39:37","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005138542","M=
ontee-Des-Soeurs","","30-05-2025 10:27:08","30-05-2025 10:24:01","30-05-202=
5 15:39:32","Grid outage ,site down due to Gen overload (15 KVA/210 A)  // =
  Grid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A)  =
//   Grid return","edwige.kapawo@matech-cameroun.com","188","30-05-2025 10:=
27:08","MATECH CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0005138524","ESS=
OS OASIS 1111","","30-05-2025 10:23:16","30-05-2025 10:18:05","30-05-2025 1=
0:33:13","Grid outage, Site went down because Gen overload (17kva, 250A) //=
 GRid power return","Siligap Boris","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage, Site went down because Gen overload (17kva=
, 250A) // GRid power return","gerard.tchangoue@matech-cameroun.com","312",=
"30-05-2025 10:23:16","MATECH CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0005137977","N=
gousso OCM","","30-05-2025 08:30:36","30-05-2025 08:10:58","30-05-2025 09:1=
6:57","Grid outage gen failed to start due to card ge dysfunctionning//We r=
eset card GE and gen manually started ","Siligap Boris","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to star=
t due to card ge dysfunctionning//We reset card GE and gen manually started=
 ","edwige.kapawo@matech-cameroun.com","1178","30-05-2025 08:30:36","MATECH=
 CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005137659","Mvo=
g-Manga","","30-05-2025 07:15:57","30-05-2025 07:10:52","30-05-2025 07:35:1=
1","Site went down due to MPR DYSFONNCTION on site // Site stabilised","Alb=
ran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","S=
ite went down due to MPR DYSFONNCTION on site // Site stabilised","gerard.t=
changoue@matech-cameroun.com","307","30-05-2025 07:15:57","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005137454","N=
koabang Ebolmedjock","","30-05-2025 06:32:28","30-05-2025 06:30:59","30-05-=
2025 08:47:52","SITE went Down due to gen Overload (15Kva, 200A)  SS IHS Al=
phonse is informed // Grid STABILIZED","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","SITE went Down due to gen Overloa=
d (15Kva, 200A)  SS IHS Alphonse is informed // Grid STABILIZED","edwige.ka=
pawo@matech-cameroun.com","90","30-05-2025 06:32:28","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0005136981","O=
KOA Peage","","30-05-2025 03:32:58","30-05-2025 03:28:47","30-05-2025 03:43=
:44","site went down because gen start an stopped due to water infiltration=
 in tank // He purged The tank and Gen manually started","Fanda Brice","Fue=
l Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The =
Fuel","site went down because gen start an stopped due to water infiltratio=
n in tank // He purged The tank and Gen manually started","gaelle.njiofack@=
matech-cameroun.com","252","30-05-2025 03:32:58","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005136837","O=
LAMA","","30-05-2025 01:58:26","30-05-2025 01:55:12","30-05-2025 02:40:32",=
"Active // No power issue on site Ubaie =3D54.9V site on Gen The TX FME Hen=
ri (699949693) from Huawei is informed.Noticed that it is a repetitve issue=
.","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active // No power issue on site Ubaie =3D54.9=
V site on Gen The TX FME Henri (699949693) from Huawei is informed.Noticed =
that it is a repetitve issue.","loic.noumsi@matech-cameroun.com","195","30-=
05-2025 01:58:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0005136821","Mambine"=
,"","30-05-2025 01:48:33","30-05-2025 01:40:53","30-05-2025 02:28:20","Casc=
aded Incident from TTO5280447","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because gen start an stopp=
ed due to water infiltration in tank // He purged The tank and Gen manually=
 started","system","988401","30-05-2025 01:48:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005136811","Nkongtoc=
k","","30-05-2025 01:47:46","30-05-2025 01:40:53","30-05-2025 02:28:20","si=
te went down because gen start an stopped due to water infiltration in tank=
 // He purged The tank and Gen manually started","Kemeni Franklin","Cascade=
 Outage","Passive","Cascade Passive","Cascade Passive","site went down beca=
use gen start an stopped due to water infiltration in tank // He purged The=
 tank and Gen manually started","system","988399","30-05-2025 01:47:46","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0005136806","Mandoumb=
a OCM","","30-05-2025 01:47:45","30-05-2025 01:40:53","30-05-2025 02:28:20"=
,"Cascaded Incident from TTO5280447","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down because gen star=
t an stopped due to water infiltration in tank // He purged The tank and Ge=
n manually started","system","988400","30-05-2025 01:47:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005136809","Ebeba","=
","30-05-2025 01:47:45","30-05-2025 01:40:53","30-05-2025 02:28:20","Cascad=
ed Incident from TTO5280447","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down because gen start an stopped=
 due to water infiltration in tank // He purged The tank and Gen manually s=
tarted","system","988402","30-05-2025 01:47:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0005136807","Mbankomo=
 IHS","","30-05-2025 01:47:45","30-05-2025 01:40:53","30-05-2025 02:28:20",=
"site went down because gen start an stopped due to water infiltration in t=
ank // He purged The tank and Gen manually started","Fanda Brice","Cascade =
Outage","Passive","Cascade Passive","Cascade Passive","site went down becau=
se gen start an stopped due to water infiltration in tank // He purged The =
tank and Gen manually started","system","988402","30-05-2025 01:47:45","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0005136810","Mamb",""=
,"30-05-2025 01:47:45","30-05-2025 01:40:53","30-05-2025 02:28:20","site we=
nt down because gen start an stopped due to water infiltration in tank // H=
e purged The tank and Gen manually started","Kemeni Franklin","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","site went down because g=
en start an stopped due to water infiltration in tank // He purged The tank=
 and Gen manually started","system","988398","30-05-2025 01:47:45","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0005136808","Nkenglik=
ok","","30-05-2025 01:47:45","30-05-2025 01:40:53","30-05-2025 02:28:20","C=
ascaded Incident from TTO5280447","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because gen start a=
n stopped due to water infiltration in tank // He purged The tank and Gen m=
anually started","system","988400","30-05-2025 01:47:45","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0005136798","O=
KOA Peage","IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_350=
, IHS_YND_376, IHS_YND_349","30-05-2025 01:44:09","30-05-2025 01:40:53","30=
-05-2025 02:28:20","site went down because gen start an stopped due to wate=
r infiltration in tank // He purged The tank and Gen manually started","Fan=
da Brice","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue -=
 Water In The Fuel","site went down because gen start an stopped due to wat=
er infiltration in tank // He purged The tank and Gen manually started","ga=
elle.njiofack@matech-cameroun.com","197","30-05-2025 01:44:09","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005136654","Crf=
-Mbankolo-IHS","","30-05-2025 00:45:13","30-05-2025 00:37:51","30-05-2025 0=
0:49:38","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid fluctuations, Site went Down due to poor backup //Sit=
e stabilised","loic.noumsi@matech-cameroun.com","992144","30-05-2025 00:45:=
13","MATECH CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0005136647","Jea=
n Vespa","IHS_YND_574","30-05-2025 00:42:57","30-05-2025 00:37:51","30-05-2=
025 00:49:38","Grid fluctuations, Site went Down due to poor backup //Site =
stabilised","Mboua Thierry","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid fluctuations, Site went Down due to poor =
backup //Site stabilised","loic.noumsi@matech-cameroun.com","307","30-05-20=
25 00:42:57","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0005136578","O=
KOA Peage","IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_350=
, IHS_YND_335, IHS_YND_349","30-05-2025 00:28:33","30-05-2025 00:20:26","30=
-05-2025 00:47:38","Grid outage, site went down due to Grid bad voltage and=
 no rcp // He bypassed Grid and started Gen manually","Fanda Brice","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid out=
age, site went down due to Grid bad voltage and no rcp // He bypassed Grid =
and started Gen manually","gaelle.njiofack@matech-cameroun.com","488","30-0=
5-2025 00:28:33","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005136431","M=
vog-Manga","","29-05-2025 23:53:53","29-05-2025 23:50:43","30-05-2025 00:27=
:11","site went down due to Rectifier disfunctioning // site stabilized","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","=
site went down due to Rectifier disfunctioning // site stabilized","gaelle.=
njiofack@matech-cameroun.com","192","29-05-2025 23:53:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0005136389","Mandoumb=
a OCM","","29-05-2025 23:45:45","30-05-2025 00:20:26","30-05-2025 00:47:38"=
,"Cascaded Incident from TTO5279902","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to Grid bad voltage and no rcp // He bypassed Grid and started Gen manuall=
y","system","993176","29-05-2025 23:45:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005136390","Nkongtoc=
k","","29-05-2025 23:45:45","30-05-2025 00:20:26","30-05-2025 00:47:38","Ca=
scaded Incident from TTO5279902","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
Grid bad voltage and no rcp // He bypassed Grid and started Gen manually","=
system","993176","29-05-2025 23:45:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005136352","Messassi=
 okolo","","29-05-2025 23:30:52","29-05-2025 23:22:32","30-05-2025 08:10:47=
","Cascaded Incident from TTO5279948","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (Gen Noise)  // Grid return","system","9966=
01","29-05-2025 23:30:52","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005136348","E=
MANA BILICK CITY","IHS_YND_279","29-05-2025 23:28:37","29-05-2025 23:22:32"=
,"30-05-2025 08:14:24","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise)  // Grid return","Fabrice Pouakam","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage, site down b=
ecause site behaves as Grid only site (Gen Noise)  // Grid return","gaelle.=
njiofack@matech-cameroun.com","367","29-05-2025 23:28:37","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005136344","N=
kolbong","","29-05-2025 23:27:26","29-05-2025 23:19:15","30-05-2025 08:07:2=
6","Grid outage, site went down due to Gen overload (22kva//350A) // Grid r=
estoration","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, site went down due to Gen overload (22kva//350A) =
// Grid restoration","gaelle.njiofack@matech-cameroun.com","492","29-05-202=
5 23:27:26","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0005136338","M=
bankomo IHS","","29-05-2025 23:26:30","30-05-2025 00:20:26","30-05-2025 00:=
47:38","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, site went down due to Grid bad voltage and no rcp=
 // He bypassed Grid and started Gen manually","loic.noumsi@matech-cameroun=
.com","993176","29-05-2025 23:26:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005136331","Matsari"=
,"","29-05-2025 23:25:49","29-05-2025 23:19:07","30-05-2025 00:09:53","","P=
arker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active","=
	Active//No power issue, site is on Gen with Ubaie=3D48.8V. The Fme TX Greg=
oire (654547479) from Huawei is informed; Site up without intervention","sy=
stem","2986","29-05-2025 23:25:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005136333","Ngouetou=
","","29-05-2025 23:25:49","29-05-2025 23:19:07","30-05-2025 00:09:53","","=
Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active",=
"	Active//No power issue, site is on Gen with Ubaie=3D48.8V. The Fme TX Gre=
goire (654547479) from Huawei is informed; Site up without intervention","s=
ystem","402","29-05-2025 23:25:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005136334","MBIMBIM"=
,"IHS_YND_475, IHS_YND_460, IHS_YND_474, IHS_YND_454","29-05-2025 23:25:49"=
,"29-05-2025 23:19:07","30-05-2025 00:09:53","	Active//No power issue, site=
 is on Gen with Ubaie=3D48.8V. The Fme TX Gregoire (654547479) from Huawei =
is informed; Site up without intervention","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Act=
ive//No power issue, site is on Gen with Ubaie=3D48.8V. The Fme TX Gregoire=
 (654547479) from Huawei is informed; Site up without intervention","system=
","402","29-05-2025 23:25:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005136332","Yoko OCM=
","","29-05-2025 23:25:49","29-05-2025 23:19:07","30-05-2025 00:09:53","","=
Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active",=
"	Active//No power issue, site is on Gen with Ubaie=3D48.8V. The Fme TX Gre=
goire (654547479) from Huawei is informed; Site up without intervention","s=
ystem","402","29-05-2025 23:25:49","MATECH CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0005136321","N=
goum","","29-05-2025 23:24:23","29-05-2025 23:19:07","30-05-2025 00:09:53",=
"","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","	Active//No power issue, site is on Gen with Ubaie=3D48.8V. The Fme TX=
 Gregoire (654547479) from Huawei is informed; Site up without intervention=
","loic.noumsi@matech-cameroun.com","3283","29-05-2025 23:24:23","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0005136308","Nkenglik=
ok","","29-05-2025 23:21:50","30-05-2025 00:20:26","30-05-2025 00:47:38",""=
,"Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage, site went down due to Grid bad voltage and no rcp // H=
e bypassed Grid and started Gen manually","system","993175","29-05-2025 23:=
21:50","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005136303","M=
ambine","","29-05-2025 23:20:38","30-05-2025 00:20:26","30-05-2025 00:47:38=
","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage, site went down due to Grid bad voltage and no rcp // H=
e bypassed Grid and started Gen manually","loic.noumsi@matech-cameroun.com"=
,"993178","29-05-2025 23:20:38","MATECH CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0005136302","A=
ngongo","","29-05-2025 23:19:35","30-05-2025 00:20:26","30-05-2025 00:47:38=
","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","CASCADE SITE","loic.noumsi@matech-cameroun.com","993177","29-05-202=
5 23:19:35","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0005136288","E=
beba","","29-05-2025 23:16:58","30-05-2025 00:20:26","30-05-2025 00:47:38",=
"","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage, site went down due to Grid bad voltage and no rcp // He =
bypassed Grid and started Gen manually","loic.noumsi@matech-cameroun.com","=
993177","29-05-2025 23:16:58","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0005136243","J=
-Vespa","","29-05-2025 23:01:55","29-05-2025 23:00:40","30-05-2025 00:40:19=
","Grid fluuctuation, Site went Down due to poor backup (waiting Grid retur=
n) // Grid return","Mboua Thierry","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","Grid fluuctuation, Site went Down due to poor b=
ackup (waiting Grid return) // Grid return","gaelle.njiofack@matech-camerou=
n.com","76","29-05-2025 23:01:55","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005136241","MBA=
LNGONG LYCEE","","29-05-2025 23:01:05","29-05-2025 22:54:57","29-05-2025 23=
:08:31","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid returned","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","loic.noumsi@ma=
tech-cameroun.com","370","29-05-2025 23:01:05","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005136216","Ron=
d Point Express1114","","29-05-2025 22:55:38","29-05-2025 22:49:31","29-05-=
2025 23:07:34","Grid outage, Site went down before Gen start due to poor ba=
ckup // Site stabilised","Hyemafo Gildas","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Site stabilised","loic.noumsi@matech-cam=
eroun.com","368","29-05-2025 22:55:38","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005136215","M=
essassi 2","","29-05-2025 22:55:10","29-05-2025 22:53:03","30-05-2025 01:13=
:28","Grid outage, site went down because gen failed to start due to alarm =
high temp//We added water and gen manually started","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because gen failed to start due to ala=
rm high temp//We added water and gen manually started","gaelle.njiofack@mat=
ech-cameroun.com","129","29-05-2025 22:55:10","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0005136208","Cit=
e des nations","","29-05-2025 22:53:14","29-05-2025 22:49:05","29-05-2025 2=
2:55:02","Grid outage,site went down before Gen started due to Poor battery=
 backup // Grid returned","Paul BIBOUM","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage,site went down before =
Gen started due to Poor battery backup // Grid returned","loic.noumsi@matec=
h-cameroun.com","250","29-05-2025 22:53:14","MATECH CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0005136207","B=
ONAS YDE","","29-05-2025 22:53:01","29-05-2025 22:49:51","30-05-2025 01:25:=
57","	Active// No power Issue Site on Grid Ubai =3D53.7 V, The SS Eloundou =
Bertrand (693212405) from Huawei is informed","Paul BIBOUM","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive// No power Issue Site on Grid Ubai =3D53.7 V, The SS Eloundou Bertrand =
(693212405) from Huawei is informed","gaelle.njiofack@matech-cameroun.com",=
"191","29-05-2025 22:53:01","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005136152","A=
wae Ewonkan","","29-05-2025 22:33:43","29-05-2025 22:27:35","29-05-2025 22:=
52:57","	Grid outage site went down due to Gen overload (20kva,300A) // Sit=
e stabilized","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","	Grid outage site went down due to Gen overload (20kva,300A) =
// Site stabilized","gaelle.njiofack@matech-cameroun.com","370","29-05-2025=
 22:33:43","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005136109","B=
arriere IHS","","29-05-2025 22:20:33","29-05-2025 22:13:25","29-05-2025 23:=
14:43","Grid Fluctuation; fme Gildas report that Gen overload(15Kva, 200A) =
SS IHS FELIX ZAMBE is informed  // Grid returned","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid Fluctuation; fme Gi=
ldas report that Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed  =
// Grid returned","gaelle.njiofack@matech-cameroun.com","430","29-05-2025 2=
2:20:33","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0005136089","Eko=
mbitie","","29-05-2025 22:17:22","29-05-2025 22:12:14","29-05-2025 23:01:22=
","	Grid fluctuation , site went down because Gen started and stopped due t=
o Grid bad voltage// he bypassed, site is on GEN	","Fabrice Pouakam","Grid =
Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue","	Gri=
d fluctuation , site went down because Gen started and stopped due to Grid =
bad voltage// he bypassed, site is on GEN	","gerard.tchangoue@matech-camero=
un.com","309","29-05-2025 22:17:22","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005136039","Ebo=
go","","29-05-2025 22:08:14","29-05-2025 22:00:59","30-05-2025 01:10:21","A=
ctive// No Power issue on site Ubaie 53.2V site on Grid, Julien /693095849 =
from Huawei is informed;  Site up without intervention.","Siligap Boris","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active// No Power issue on site Ubaie 53.2V site on Grid, Julien =
/693095849 from Huawei is informed;  Site up without intervention.","cedric=
.tiani@matech-cameroun.com","436","29-05-2025 22:08:14","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005136034","TSI=
NGA VILLAGE 2","","29-05-2025 22:06:44","29-05-2025 21:38:30","29-05-2025 2=
2:28:22","Site went down due to disjunction CB(125A)in PWC that tripped MTN=
 // He rearmed CB","Delor Telezing","Equipment Repair","Passive","Rectifier=
","Rectifier Cabinet","Site went down due to disjunction CB(125A)in PWC tha=
t tripped MTN // He rearmed CB","vanel.mbiada@matech-cameroun.com","1695","=
29-05-2025 22:06:44","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005135798","A=
wae Ewonkan","","29-05-2025 21:10:44","29-05-2025 21:07:16","29-05-2025 22:=
07:22","Grid outage site went down due to Gen overload (20kva,300A) // Site=
 stabilized","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage site went down due to Gen overload (20kva,300A) //=
 Site stabilized","vanel.mbiada@matech-cameroun.com","209","29-05-2025 21:1=
0:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005135643","Mbeng","=
","29-05-2025 20:40:04","29-05-2025 20:31:26","29-05-2025 21:45:55","Cascad=
ed Incident from TTO5279113","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage; site went down because the con=
trolar did not send the start order // controlar reset and Gen start manual=
ly","system","1006716","29-05-2025 20:40:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005135644","Bondjock=
","","29-05-2025 20:40:04","29-05-2025 20:31:26","29-05-2025 21:45:55","Cas=
caded Incident from TTO5279113","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage; site went down because the =
controlar did not send the start order // controlar reset and Gen start man=
ually","system","1006715","29-05-2025 20:40:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005135627","Mom","",=
"29-05-2025 20:37:24","29-05-2025 20:31:26","29-05-2025 21:41:29","Cascaded=
 Incident from TTO5279112","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage; site went down because the contr=
olar did not send the start order // controlar reset and Gen start manually=
","system","1006717","29-05-2025 20:37:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0005135626","OTELE MT=
N","","29-05-2025 20:37:24","29-05-2025 20:31:26","29-05-2025 21:41:29","Ca=
scaded Incident from TTO5279112","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage; site went down because the=
 controlar did not send the start order // controlar reset and Gen start ma=
nually","system","1006717","29-05-2025 20:37:24","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0005135621","Min=
ka","IHS_YND_369, IHS_YND_531, IHS_YND_554, IHS_YND_553, IHS_YND_370, IHS_Y=
ND_372","29-05-2025 20:36:52","29-05-2025 20:31:26","29-05-2025 21:45:55","=
Grid outage; site went down because the controler did not send the start or=
der // controler reset and Gen start manually","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","ATS-AMF Issue","Grid outage; site went down=
 because the controlar did not send the start order // controlar reset and =
Gen start manually","cedric.tiani@matech-cameroun.com","327","29-05-2025 20=
:36:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005135292","Bastos-N=
ylon","","29-05-2025 20:15:05","29-05-2025 20:12:29","29-05-2025 20:52:24",=
"Cascaded Incident from TTO5278748","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen failed to start due to  GEN card faulty // Grid return","system","100=
7769","29-05-2025 20:15:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005135293","Bastos B=
ethesda","","29-05-2025 20:15:05","29-05-2025 20:12:29","29-05-2025 20:52:2=
4","Cascaded Incident from TTO5278748","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause gen failed to start due to  GEN card faulty // Grid return","system","=
1007770","29-05-2025 20:15:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005135291","Golf Qua=
ter","","29-05-2025 20:15:04","29-05-2025 20:12:29","29-05-2025 20:52:24","=
Cascaded Incident from TTO5278748","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen failed to start due to  GEN card faulty // Grid return","system","1007=
770","29-05-2025 20:15:04","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005135288","T=
singa","IHS_YND_220, IHS_YND_126, IHS_YND_563","29-05-2025 20:13:43","29-05=
-2025 20:12:29","29-05-2025 20:58:44","Grid outage, site went down because =
gen failed to start due to  GEN card faulty // Grid return","Mboua Thierry"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e, site went down because gen failed to start due to  GEN card faulty // Gr=
id return","vanel.mbiada@matech-cameroun.com","75","29-05-2025 20:13:43","M=
ATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005135256","NKO=
MKANA ELIZA HOTEL","","29-05-2025 20:07:01","29-05-2025 20:03:53","29-05-20=
25 20:53:45","Active//No power issue, Site on Grid Ubaie: 53.2V. The Tx FME=
 Brice Tsague(650214096) from Huawei is informed.","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue, Site on Grid Ubaie: 53.2V. The Tx FME Brice Tsague(650214096=
) from Huawei is informed.","vanel.mbiada@matech-cameroun.com","189","29-05=
-2025 20:07:01","MATECH CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0005135253","Aha=
la","","29-05-2025 20:06:14","29-05-2025 20:02:59","29-05-2025 20:37:43","G=
rid Outage site went down because Gen started and stopped due to ""high tem=
p"" alarm //He added water and Gen manually started","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid Outage site went down because Gen started and stopped due to =
""high temp"" alarm //He added water and Gen manually started","vanel.mbiad=
a@matech-cameroun.com","196","29-05-2025 20:06:14","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005135223","N=
koabang Ebolmedjock","","29-05-2025 19:59:25","29-05-2025 19:50:20","29-05-=
2025 20:15:14","Grid outage, site went down because gen start and stopped d=
ue to gen Overload (15Kva, 200A) // Site stabilised","Mba Lazare Herve","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site w=
ent down because gen start and stopped due to gen Overload (15Kva, 200A) //=
 Site stabilised","vanel.mbiada@matech-cameroun.com","546","29-05-2025 19:5=
9:25","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0005135206","S=
calom","IHS_YND_505","29-05-2025 19:55:08","29-05-2025 19:50:56","29-05-202=
5 21:23:08","Grid fluctuation, site went down because Gen failed to start d=
ue to ATS Dysfunctioning on Site // He reset ATS and site on Grid","Paul BI=
BOUM","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid fl=
uctuation, site went down because Gen failed to start due to ATS Dysfunctio=
ning on Site // He reset ATS and site on Grid","vanel.mbiada@matech-camerou=
n.com","253","29-05-2025 19:55:08","MATECH CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0005135189","S=
calom-IHS","","29-05-2025 19:53:30","29-05-2025 19:50:56","29-05-2025 20:46=
:32","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid fluctuation, site went down because Gen failed to start due to ATS Dys=
functioning on Site // He reset ATS and site on Grid","vanel.mbiada@matech-=
cameroun.com","1216616","29-05-2025 19:53:30","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005135171","E=
ssomba","","29-05-2025 19:49:40","29-05-2025 19:47:11","29-05-2025 19:52:36=
","Site went down because 03/06 rectifiers dysfunctionned //Site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down because 03/06 rectifiers dysfunctionned //Site stabil=
ised","vanel.mbiada@matech-cameroun.com","151","29-05-2025 19:49:40","MATEC=
H CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005135138","TSI=
NGA VILLAGE 2","","29-05-2025 19:44:13","29-05-2025 19:43:01","29-05-2025 2=
0:22:49","Site went down due to disjunction CB(125A)in  PWC that tripped MT=
N // He rearmed CB ","Delor Telezing","Equipment Repair","Passive","Rectifi=
er","Rectifier - Circuit Breaker","Site went down due to disjunction CB(125=
A)in  PWC that tripped MTN // He rearmed CB ","cedric.tiani@matech-cameroun=
.com","73","29-05-2025 19:44:13","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005135117","A=
ccacia New","","29-05-2025 19:38:12","29-05-2025 19:18:06","29-05-2025 19:5=
9:48","Grid outage, no space to deploy a mobil gen // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 no space to deploy a mobil gen // Grid return","vanel.mbiada@matech-camero=
un.com","1208","29-05-2025 19:38:12","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005135016","MBA=
LNGONG LYCEE","","29-05-2025 19:23:35","29-05-2025 19:22:13","29-05-2025 22=
:04:23","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid returned","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","cedric.tiani@m=
atech-cameroun.com","84","29-05-2025 19:23:35","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005135015","T=
amtam Weekend","","29-05-2025 19:23:21","29-05-2025 19:15:06","29-05-2025 2=
0:18:55","Site went due to work of francois IHS supervisor is on site //End=
 of work","Hyemafo Gildas","Installation Activity","Passive","Planned Activ=
ity","Installation Activity","Site went due to work of francois IHS supervi=
sor is on site //End of work","vanel.mbiada@matech-cameroun.com","496","29-=
05-2025 19:23:21","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005134954","Nko=
ulou Carriere carrefourt","","29-05-2025 19:12:01","25-05-2025 22:32:46","2=
5-05-2025 23:10:39","Backtracking Grid outage, Site went down due to insuff=
iciency of rectifiers//Site stablilsed","Mba Lazare Herve","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Grid outage, Site went down du=
e to insufficiency of rectifiers//Site stablilsed","cedric.tiani@matech-cam=
eroun.com","333556","29-05-2025 19:12:01","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005134930","Nom=
ayos montee Meche","","29-05-2025 19:08:46","26-05-2025 01:11:41","26-05-20=
25 01:46:13","ACTIVE//No power issue on site Grid , Ubaie=3D54.5V site On G=
rid The Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE//No power issue on site Grid , Ubaie=3D54.5V site On Grid =
The Tx FME Fulbert(654266068) from Huawei is informed","cedric.tiani@matech=
-cameroun.com","323825","29-05-2025 19:08:46","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005134877","SAA=
 Entrance","","29-05-2025 18:56:44","25-05-2025 22:58:08","26-05-2025 08:40=
:53","Active // No power issue on site , site on Gen , The TX FME Gr=E9goir=
e //654547479 from Huawei is informed","Parker Tchoup","Equipment Repair","=
Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid o=
utage, Site went down because Gen start and stopped with ""High temps"" ala=
rm // he added water and manually start the Gen","cedric.tiani@matech-camer=
oun.com","331116","29-05-2025 18:56:44","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005134843","A=
ccacia New","","29-05-2025 18:46:26","29-05-2025 18:40:17","29-05-2025 18:4=
9:22","Grid outage, no space to deploy a mobil gen // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 no space to deploy a mobil gen // Grid return","vanel.mbiada@matech-camero=
un.com","371","29-05-2025 18:46:26","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005134842","D=
amas","","29-05-2025 18:45:49","29-05-2025 18:40:39","29-05-2025 18:50:29",=
"Active// No power Issue Site on Grid Ubai =3D53,8 V, The FME The TX FME Mb=
ah Hosiah (674007438) is informed.","MINKA NICOLAS","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No=
 power Issue Site on Grid Ubai =3D53,8 V, The FME The TX FME Mbah Hosiah (6=
74007438) is informed.","vanel.mbiada@matech-cameroun.com","311","29-05-202=
5 18:45:49","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005134838","M=
ontee-Jouvence-II","","29-05-2025 18:45:14","29-05-2025 18:40:55","29-05-20=
25 19:23:38","No power issue on site, site on Grid with Ubaie=3D51.1V The T=
x Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site, site on Grid with Ubaie=3D51.1V The Tx Fm=
e Mbah Hosiah //674007438/ from HUAWEI is informed","vanel.mbiada@matech-ca=
meroun.com","260","29-05-2025 18:45:14","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0005134745","Man=
guiers Dispensaire","","29-05-2025 18:25:30","29-05-2025 18:24:20","29-05-2=
025 18:56:20","Active // No power issue site on grid with U=3D54,6 V Tx Fme=
 Armand Ngestsa (691144412) of huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active // No power issue site on grid with U=3D54,6 V Tx Fme Armand N=
gestsa (691144412) of huawei is informed","cedric.tiani@matech-cameroun.com=
","71","29-05-2025 18:25:30","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005134724","O=
dza II OCM","","29-05-2025 18:21:14","29-05-2025 18:14:57","29-05-2025 18:2=
3:05","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Site stabilised","Albran Byorel","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Grid outage, site went down=
 because gen failed to start due to PWC ZTE malfunction // Site stabilised"=
,"vanel.mbiada@matech-cameroun.com","379","29-05-2025 18:21:14","MATECH CMR=
"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005134566","NKO=
MKANA ELIZA HOTEL","","29-05-2025 17:57:16","29-05-2025 17:54:05","29-05-20=
25 19:34:46","Active: No power issue, site is on grid with Ubaie=3D53.2V,  =
 The FME TX Synphorien(691316854) from Huawei is informed","","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive: No power issue, site is on grid with Ubaie=3D53.2V,=20

The FME TX Synphorien(691316854) from Huawei is informed

","vanel.mbiada@matech-cameroun.com","191","29-05-2025 17:57:16","MATECH CM=
R"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005134063","M=
vog-Ebanda","","29-05-2025 16:41:28","29-05-2025 16:33:21","29-05-2025 17:0=
0:07","","Siligap Boris","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Active//No power issue, site is on Grid with Ubaie=3D53,2V The T=
X Synphorien / 675295205/ Huawei is informed","vanel.mbiada@matech-cameroun=
.com","1020640","29-05-2025 16:41:28","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0005134054","A=
bom","IHS_YND_269","29-05-2025 16:40:11","29-05-2025 16:33:21","29-05-2025 =
18:12:37","Active//No power issue, site is on Grid with Ubaie=3D53,2V The T=
X Synphorien / 675295205/ Huawei is informed","Siligap Boris","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue, site is on Grid with Ubaie=3D53,2V The TX Synphorien=
 / 675295205/ Huawei is informed","vanel.mbiada@matech-cameroun.com","807",=
"29-05-2025 16:40:11","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005133963","M=
ontee-Des-Soeurs","","29-05-2025 16:32:20","29-05-2025 16:29:29","30-05-202=
5 10:14:19","Grid outage ,site down due to Gen overload (15 KVA/210 A)  // =
Grid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 A)  //=
 Grid return","vanel.mbiada@matech-cameroun.com","173","29-05-2025 16:32:20=
","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005133865","NYO=
M 2 IHS","","29-05-2025 16:18:18","29-05-2025 16:09:10","29-05-2025 16:20:2=
9","Grid outage, Site went down before Gen start due to poor backup // Grid=
 return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","cedric.tiani@matech-cameroun.com","549","=
29-05-2025 16:18:18","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005133795","B=
arriere IHS","","29-05-2025 16:02:22","28-05-2025 09:19:07","28-05-2025 10:=
55:17","BACTRACKINGGrid outage, site went down due to gen overload(20KVA, 2=
40A),SS Felix IHS //He reduiced the load an site on Gen","Hyemafo Gildas","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site=
 went down due to gen overload(20KVA, 240A),SS Felix IHS //He reduiced the =
load an site on Gen","cedric.tiani@matech-cameroun.com","110597","29-05-202=
5 16:02:22","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005133787","M=
EFOU ASSI","","29-05-2025 16:00:01","28-05-2025 09:19:32","28-05-2025 09:30=
:20","BACTRACKING No power issue site on grid with Ubaie: 48V TX FME Fluber=
t (654266068) from Huawei is informed.Noticed impacted by Mendong 2","Fanda=
 Brice","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue site on grid with Ubaie: 48V TX FME Flub=
ert (654266068) from Huawei is informed.Noticed impacted by Mendong 2","ced=
ric.tiani@matech-cameroun.com","110432","29-05-2025 16:00:01","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005133774","ODZ=
A MINKAN EDIBI ASSI","","29-05-2025 15:57:34","29-05-2025 15:53:26","29-05-=
2025 15:57:20","Fme Albran is informed and said SWAPP of Batteries ongoing =
// End of work","Albran Byorel","Equipment Replacement","Passive","Planned =
Activity","Planned Activity - Passive","Fme Albran is informed and said SWA=
PP of Batteries ongoing // End of work","cedric.tiani@matech-cameroun.com",=
"249","29-05-2025 15:57:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005133730","MEHANDAN=
","","29-05-2025 15:50:02","29-05-2025 15:40:42","29-05-2025 15:49:58","Cas=
caded Incident from TTO5277021","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
1017761","29-05-2025 15:50:02","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005133723","O=
dza II OCM","IHS_YND_528","29-05-2025 15:48:55","29-05-2025 15:40:42","29-0=
5-2025 15:49:58","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","vanel.mbiada@matech-cameroun.com","495","29-05-2025 15:48:55",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005133611","C=
rf-Nsam","","29-05-2025 15:36:03","29-05-2025 14:06:37","29-05-2025 15:42:1=
1","Active//No power issue on site Ubaie =3D53.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","vanel.mbiada@matech-cameroun.com","5367",=
"29-05-2025 15:36:03","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005133505","Mvo=
g-Manga","","29-05-2025 15:16:14","29-05-2025 15:12:06","29-05-2025 15:50:5=
7","Grid outage,site went down because Gen started and stopped due to High =
temp alarm//He reset the Gen card and manually stared the Gen","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage,site went down because Gen started and stopped due to High temp alarm/=
/He reset the Gen card and manually stared the Gen","cedric.tiani@matech-ca=
meroun.com","250","29-05-2025 15:16:14","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005133493","ODZ=
A MINKAN EDIBI ASSI","","29-05-2025 15:15:09","29-05-2025 15:11:02","29-05-=
2025 15:15:13","Fme Albran is informed and said SWAPP of PWC ongoing // end=
 of work","Albran Byorel","Equipment Replacement","Passive","Planned Activi=
ty","Planned Activity - Passive","Fme Albran is informed and said SWAPP of =
PWC ongoing // end of work","cedric.tiani@matech-cameroun.com","248","29-05=
-2025 15:15:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005133374","Carrefou=
rt Nkomo","","29-05-2025 15:00:05","29-05-2025 14:56:01","29-05-2025 16:33:=
59","Cascaded Incident from TTO5276611","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage,site went down =
because Gen failed to start due to PWC Overload(12k//280A)SS HIS Bateu is i=
nformed//He reduiced the load and manually started the Gen","system","10203=
44","29-05-2025 15:00:05","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005133353","N=
komo","IHS_YND_174","29-05-2025 14:58:15","29-05-2025 14:56:01","29-05-2025=
 16:34:43","Grid outage,site went down because Gen failed to start due to P=
WC Overload(12k//280A)SS HIS Bateu is informed//He reduiced the load and ma=
nually started the Gen","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Grid outage,site went down because =
Gen failed to start due to PWC Overload(12k//280A)SS HIS Bateu is informed/=
/He reduiced the load and manually started the Gen","vanel.mbiada@matech-ca=
meroun.com","136","29-05-2025 14:58:15","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005133196","Mim=
boman4","","29-05-2025 14:32:16","29-05-2025 14:27:05","29-05-2025 15:30:31=
","No power issue U=3D54V site on Grid. TX FME Leonel Steve// 655184876// /=
 from huawei is informed.","Mba Lazare Herve","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=
=3D54V site on Grid. TX FME Leonel Steve// 655184876// / from huawei is inf=
ormed.","gerard.tchangoue@matech-cameroun.com","312","29-05-2025 14:32:16",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005132887","N=
koabang Ebolmedjock","","29-05-2025 13:56:23","29-05-2025 13:50:16","29-05-=
2025 14:42:02","Grid outage, site went down because gen start and stopped d=
ue to gen Overload (15Kva, 200A) // He reduice the load on site and manuall=
y start the gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage, site went down because gen start and stopp=
ed due to gen Overload (15Kva, 200A) // He reduice the load on site and man=
ually start the gen","edwige.kapawo@matech-cameroun.com","368","29-05-2025 =
13:56:23","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005132757","C=
rf-Nsam","","29-05-2025 13:38:57","29-05-2025 13:36:59","29-05-2025 13:42:4=
4","Active//No power issue on site Ubaie =3D53.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","edwige.kapawo@matech-cameroun.com","119",=
"29-05-2025 13:38:57","MATECH CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0005132693","Don=
g","","29-05-2025 13:28:44","29-05-2025 13:00:28","29-05-2025 16:18:02","Hy=
brid Gen,site went down because Gen failed to start(Level 0 of Ngouetou sta=
rted the Gen manually according to Felix Bateu)//(Investigation on going)",=
"Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Hybrid Gen,site went down because Gen failed to start(Level 0 of Ngoue=
tou started the Gen manually according to Felix Bateu)//(Investigation on g=
oing)","gerard.tchangoue@matech-cameroun.com","1698","29-05-2025 13:28:44",=
"MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005132594","Odz=
a Minkan IHS","","29-05-2025 13:12:33","29-05-2025 13:07:22","29-05-2025 16=
:33:42","Grid outage, site went down due to gen overload(20KVA, 240A),SS Fe=
lix IHS //He reduiced the load an site on Gen","Albran Byorel","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid outage, =
site went down due to gen overload(20KVA, 240A),SS Felix IHS //He reduiced =
the load an site on Gen","gerard.tchangoue@matech-cameroun.com","313","29-0=
5-2025 13:12:33","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005132559","Men=
dong Plateau","","29-05-2025 13:07:40","29-05-2025 12:59:27","29-05-2025 13=
:34:43","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and manually start the gen	","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, sit=
e went down because gen start and stopped with high temp alarm // He added =
water and manually start the gen	","gerard.tchangoue@matech-cameroun.com","=
493","29-05-2025 13:07:40","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0005132487","K=
oweit City","","29-05-2025 12:58:20","29-05-2025 12:56:08","29-05-2025 13:4=
3:45","Grid fluctuation, site went down because Gen failed to start due to =
grid bad voltage // He bypassed grid and started Gen manually","Albran Byor=
el","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because Gen failed to start due to grid=
 bad voltage // He bypassed grid and started Gen manually","edwige.kapawo@m=
atech-cameroun.com","133","29-05-2025 12:58:20","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005132332","Ako=
k Ndoe Yde","","29-05-2025 12:39:09","29-05-2025 12:34:57","29-05-2025 14:3=
3:12","Grid fluctuation,site went down because Gen started and stopped due =
to Grid bad voltage//He bypassed the Grid and started the Gen manually","Hy=
emafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation,site went down because Gen started and stoppe=
d due to Grid bad voltage//He bypassed the Grid and started the Gen manuall=
y","gerard.tchangoue@matech-cameroun.com","254","29-05-2025 12:39:09","MATE=
CH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005132298","Mvo=
g-Manga","","29-05-2025 12:32:09","29-05-2025 12:25:54","29-05-2025 12:48:5=
4","Grid outage,site went down because Gen started and stopped due to High =
temp alarm//He reset the Gen card and manually stared the Gen","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage,site went down because Gen started and stopped due to High temp alarm/=
/He reset the Gen card and manually stared the Gen","gerard.tchangoue@matec=
h-cameroun.com","377","29-05-2025 12:32:09","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0005132105","E=
koumdoum","","29-05-2025 12:02:04","29-05-2025 11:54:51","29-05-2025 15:02:=
49","Grid outage, site went down because gen start and stopped with high te=
mp alarm // he reset card and manual start of Gen","Albran Byorel","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site w=
ent down because gen start and stopped with high temp alarm // he reset car=
d and manual start of Gen","edwige.kapawo@matech-cameroun.com","434","29-05=
-2025 12:02:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005132097","MEHANDAN=
","","29-05-2025 12:00:16","29-05-2025 11:54:03","29-05-2025 12:01:12","Cas=
caded Incident from TTO5275193","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
1030918","29-05-2025 12:00:16","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005132093","O=
dza II OCM","IHS_YND_528","29-05-2025 11:59:13","29-05-2025 11:54:03","29-0=
5-2025 12:01:12","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","edwige.kapawo@matech-cameroun.com","312","29-05-2025 11:59:13"=
,"MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0005131837","Nko=
lmvack","","29-05-2025 11:24:51","29-05-2025 11:15:35","29-05-2025 11:45:35=
","Grid outage, Site went down because Gen start and stopped with ""High te=
mps ""alarm // he added water and manually start the Gen","Parker Tchoup","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, Site went down because Gen start and stopped with=
 ""High temps ""alarm // he added water and manually start the Gen","gerard=
.tchangoue@matech-cameroun.com","557","29-05-2025 11:24:51","MATECH CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0005131828","N=
R-Omnisport","","29-05-2025 11:23:59","29-05-2025 11:15:37","29-05-2025 11:=
31:23","Active // No power issue ,site on Gen with Ubaie=3D54 v The Tx FME =
Armand Nguetsa (691144412 /Huawei) is informed","Delor Telezing","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue ,site on Gen with Ubaie=3D54 v The Tx FME Armand=
 Nguetsa (691144412 /Huawei) is informed","edwige.kapawo@matech-cameroun.co=
m","502","29-05-2025 11:23:59","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005131727","NYO=
M 2 IHS","","29-05-2025 11:09:38","29-05-2025 11:07:31","29-05-2025 11:17:3=
1","Grid outage, Site went down before Gen start due to poor backup // Gen =
started automaticaly","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","Grid outage, Site went down before Gen start due to=
 poor backup // Gen started automaticaly","gerard.tchangoue@matech-cameroun=
.com","128","29-05-2025 11:09:38","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005131236","Nko=
abang Alembe","","29-05-2025 09:54:47","29-05-2025 09:51:36","29-05-2025 09=
:56:36","site went down due to imsufficiency of rectifiers IHS SS Alphonse =
is informed//site sitabilized","Mba Lazare Herve","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","site went down due to imsufficiency of =
rectifiers IHS SS Alphonse is informed//site sitabilized","gerard.tchangoue=
@matech-cameroun.com","192","29-05-2025 09:54:47","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005131215","A=
kak-Nkozoa-MTN-IHS","","29-05-2025 09:49:50","29-05-2025 09:48:59","29-05-2=
025 12:39:23","Active // No power issue Ubaie:53.55V site on Grid, TX fme s=
ymphorien /650257151 from huawei is informed.","Fabrice Pouakam","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue Ubaie:53.55V site on Grid, TX fme symphorien /65=
0257151 from huawei is informed.","edwige.kapawo@matech-cameroun.com","53",=
"29-05-2025 09:49:50","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005131205","Mim=
boman","","29-05-2025 09:48:58","29-05-2025 09:44:49","29-05-2025 11:04:49"=
,"Grid outage,Site went down because Gen failed to start due to charger sta=
tic faulty //He reconnected it and He started Gen manualy with external bat=
tery","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ge=
nerator Battery","Grid outage,Site went down because Gen failed to start du=
e to charger static faulty //He reconnected it and He started Gen manualy w=
ith external battery","gerard.tchangoue@matech-cameroun.com","250","29-05-2=
025 09:48:58","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005131097","N=
koabang Ebolmedjock","","29-05-2025 09:37:41","29-05-2025 09:31:32","29-05-=
2025 12:52:45","Grid outage, site went down because gen start and stopped d=
ue to gen Overload (15Kva, 200A) // He reduice the load on site and manuall=
y start the gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage, site went down because gen start and stopp=
ed due to gen Overload (15Kva, 200A) // He reduice the load on site and man=
ually start the gen","edwige.kapawo@matech-cameroun.com","370","29-05-2025 =
09:37:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0005131082","Mfou EPC=
","","29-05-2025 09:34:53","29-05-2025 09:25:44","29-05-2025 09:40:44","Cas=
caded Incident from TTO5274092","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issues iste on Grid w=
ith Ubay=3D54.9V ,The FME TX Fulbert (654266068) from Huawei is informed.",=
"system","1039562","29-05-2025 09:34:53","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0005131074","M=
fou OCM","IHS_YND_674","29-05-2025 09:33:51","29-05-2025 09:25:44","29-05-2=
025 09:40:44","Active//No power issues iste on Grid with Ubay=3D54.9V ,The =
FME TX Fulbert (654266068) from Huawei is informed.","Mba Lazare Herve","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issues iste on Grid with Ubay=3D54.9V ,The FME TX=
 Fulbert (654266068) from Huawei is informed.","edwige.kapawo@matech-camero=
un.com","488","29-05-2025 09:33:51","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0005131053","E=
koumdoum","","29-05-2025 09:29:18","29-05-2025 09:19:59","29-05-2025 09:39:=
30","Grid outage, site went down because gen start and stopped with high te=
mp alarm // he reset card and manual start of Gen","Albran Byorel","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site w=
ent down because gen start and stopped with high temp alarm // he reset car=
d and manual start of Gen","edwige.kapawo@matech-cameroun.com","560","29-05=
-2025 09:29:18","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005130984","O=
LAMA","","29-05-2025 09:18:47","29-05-2025 09:14:37","29-05-2025 09:57:42",=
"Active // No power issue on site Ubaie =3D54.9V site on Gen The TX FME Hen=
ri (699949693) from Huawei is informed.Noticed that it is a repetitve issue=
.","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active // No power issue on site Ubaie =3D54.9=
V site on Gen The TX FME Henri (699949693) from Huawei is informed.Noticed =
that it is a repetitve issue.","edwige.kapawo@matech-cameroun.com","251","2=
9-05-2025 09:18:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005130884","MEHANDAN=
","","29-05-2025 09:00:50","29-05-2025 08:58:59","29-05-2025 09:01:16","Cas=
caded Incident from TTO5273873","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
1041113","29-05-2025 09:00:50","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005130881","O=
dza II OCM","IHS_YND_528","29-05-2025 08:59:53","29-05-2025 08:58:59","29-0=
5-2025 09:01:58","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","edwige.kapawo@matech-cameroun.com","56","29-05-2025 08:59:53",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005130834","M=
essassi 2","","29-05-2025 08:50:40","29-05-2025 08:50:33","29-05-2025 10:06=
:20","Active // No power issue Ubaie:53.9 V site on Grid, TX fme symphorien=
 /650257151 from huawei is informed.","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue Ubaie:53.9 V site on Grid, TX fme symphorien /650257151 f=
rom huawei is informed.","edwige.kapawo@matech-cameroun.com","9","29-05-202=
5 08:50:40","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005130743","S=
tade-Abega","","29-05-2025 08:30:51","29-05-2025 08:26:59","29-05-2025 12:2=
5:00","No pwer issus, site is on grid with Ubaie=3D53.4V, Site impacted by =
EKounou-II ","Mba Lazare Herve","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","Affected by 3rd Party Site","No pwer issus, site is =
on grid with Ubaie=3D53.4V, Site impacted by EKounou-II ","edwige.kapawo@ma=
tech-cameroun.com","233","29-05-2025 08:30:51","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005130603","N=
YOM 2 IHS","","29-05-2025 08:21:53","29-05-2025 08:20:59","29-05-2025 09:27=
:13","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automaticaly","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen started automaticaly","edwige.kapawo=
@matech-cameroun.com","56","29-05-2025 08:21:53","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005130586","Ebo=
go","","29-05-2025 08:17:41","29-05-2025 08:14:33","29-05-2025 08:54:10","A=
ctive// No Power issue on site Ubaie 53.2V site on Grid, Julien /693095849 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issu=
e on site Ubaie 53.2V site on Grid, Julien /693095849 from Huawei is inform=
ed","gerard.tchangoue@matech-cameroun.com","189","29-05-2025 08:17:41","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005130543","Emana Ly=
cee","","29-05-2025 08:09:56","29-05-2025 08:06:09","29-05-2025 10:36:30","=
Cascaded Incident from TTO5273503","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,Site went down due to=
 PWC Huawei dysfunction//He reset and started the Gen Manuaually","system",=
"1044198","29-05-2025 08:09:56","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005130540","E=
mana lycee 2","IHS_YND_274","29-05-2025 08:09:17","29-05-2025 08:06:09","29=
-05-2025 10:36:30","Grid outage,Site went down due to PWC Huawei dysfunctio=
n//He reset and started the Gen Manuaually","Fabrice Pouakam","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage,Site=
 went down due to PWC Huawei dysfunction//He reset and started the Gen Manu=
aually","edwige.kapawo@matech-cameroun.com","190","29-05-2025 08:09:17","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0005130524","C=
lge-Advantiste","","29-05-2025 08:06:55","29-05-2025 07:58:45","29-05-2025 =
09:02:37","Grid outage, site went down because gen failed to start with ala=
rm Over voltaged // He reset gen card and gen manually started","MINKA NICO=
LAS","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Grid ou=
tage, site went down because gen failed to start with alarm Over voltaged /=
/ He reset gen card and gen manually started","edwige.kapawo@matech-camerou=
n.com","490","29-05-2025 08:06:55","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005130516","T=
alla Monatele","","29-05-2025 08:05:11","29-05-2025 07:56:46","29-05-2025 0=
8:16:45","Active  // No power issue, site is on grid with Ubaie:51.3V, Greg=
oir (654547479 /Huawei) is informed","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active  //=
 No power issue, site is on grid with Ubaie:51.3V, Gregoir (654547479 /Huaw=
ei) is informed","edwige.kapawo@matech-cameroun.com","506","29-05-2025 08:0=
5:11","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005130514","Mes=
sassi 2","","29-05-2025 08:04:58","29-05-2025 07:55:45","29-05-2025 08:16:3=
5","Site Went Down due to poor backup // Grid return","Fabrice Pouakam","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Si=
te Went Down due to poor backup // Grid return","gerard.tchangoue@matech-ca=
meroun.com","555","29-05-2025 08:04:58","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005130440","Nko=
g-Edzen","","29-05-2025 07:52:22","29-05-2025 07:44:15","29-05-2025 08:10:2=
6","Active//No power issue on site, Site on Gen Ubay =3D 53.6V The Tx Fme G=
regoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site, Site on Gen Ubay =3D 53.6V The Tx Fme Gregoi=
re (654547479) from Huawei is informed.","gerard.tchangoue@matech-cameroun.=
com","488","29-05-2025 07:52:22","MATECH CMR"
"Cancelled","Warning","CTR_337","IHS_YND_280","NOCINC0005130224","Messassi =
2","","29-05-2025 07:09:00","","","Active // No power issue Ubaie:53.9 V si=
te on Grid, TX fme symphorien /650257151 from huawei is informed.","Fabrice=
 Pouakam","","","","","","edwige.kapawo@matech-cameroun.com","5","29-05-202=
5 07:09:00","MATECH CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0005130070","M=
volye-New","","29-05-2025 06:51:46","29-05-2025 06:49:35","29-05-2025 06:59=
:43","Active// No power Issue Site on Grid Ubai =3D52 V, The TX FME Mbah Ho=
siah (674007438) is informed","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site o=
n Grid Ubai =3D52 V, The TX FME Mbah Hosiah (674007438) is informed","edwig=
e.kapawo@matech-cameroun.com","132","29-05-2025 06:51:46","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005130046","S=
atcom","","29-05-2025 06:44:08","29-05-2025 06:40:01","29-05-2025 06:59:16"=
,"Active//No power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa=
 (691144412) of huawei is informed","Delor Telezing","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144412)=
 of huawei is informed","edwige.kapawo@matech-cameroun.com","248","29-05-20=
25 06:44:08","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0005130041","E=
koumdoum","","29-05-2025 06:42:32","29-05-2025 06:28:18","29-05-2025 08:39:=
42","Grid outage, site went down because gen start and stopped with high te=
mp alarm // he reset card and manual start of Gen","Albran Byorel","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site w=
ent down because gen start and stopped with high temp alarm // he reset car=
d and manual start of Gen","ludivine.ngamaleu@ihstowers.com","855","29-05-2=
025 06:42:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0005129945","ODZA MIN=
KAN EDIBI ASSI","","29-05-2025 06:19:15","29-05-2025 06:07:03","29-05-2025 =
06:45:38","Cascaded Incident from TTO5272788","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site w=
ent down because Gen failed to start due to grid bad voltage No Rcp// He by=
passed grid and started Gen manually","system","1051198","29-05-2025 06:19:=
15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0005129944","Odza Min=
kan IHS","","29-05-2025 06:19:15","29-05-2025 06:07:03","29-05-2025 06:45:3=
8","Cascaded Incident from TTO5272788","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation, site went dow=
n because Gen failed to start due to grid bad voltage No Rcp// He bypassed =
grid and started Gen manually","system","1051197","29-05-2025 06:19:15","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005129941","MEHANDAN=
","","29-05-2025 06:19:14","29-05-2025 06:07:03","29-05-2025 06:45:38","Cas=
caded Incident from TTO5272788","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se Gen failed to start due to grid bad voltage No Rcp// He bypassed grid an=
d started Gen manually","system","1051199","29-05-2025 06:19:14","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0005129942","Mehanda =
1","","29-05-2025 06:19:14","29-05-2025 06:07:03","29-05-2025 06:45:38","Ca=
scaded Incident from TTO5272788","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuation, site went down beca=
use Gen failed to start due to grid bad voltage No Rcp// He bypassed grid a=
nd started Gen manually","system","1051199","29-05-2025 06:19:14","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0005129943","Nomayos =
montee Meche","","29-05-2025 06:19:14","29-05-2025 06:07:03","29-05-2025 06=
:45:38","Cascaded Incident from TTO5272788","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went =
down because Gen failed to start due to grid bad voltage No Rcp// He bypass=
ed grid and started Gen manually","system","1051200","29-05-2025 06:19:14",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0005129940","Mbedoumo=
u - Ekali","","29-05-2025 06:19:14","29-05-2025 06:07:03","29-05-2025 06:45=
:38","Cascaded Incident from TTO5272788","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Gen failed to start due to grid bad voltage No Rcp// He bypasse=
d grid and started Gen manually","system","1051196","29-05-2025 06:19:14","=
MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005129871","Nko=
lnda","IHS_YND_343, IHS_SGM_125, IHS_YND_723, IHS_YND_528, IHS_YND_746, IHS=
_YND_791, IHS_YND_715, IHS_YND_749","29-05-2025 06:15:09","29-05-2025 06:07=
:03","29-05-2025 06:45:38","Grid fluctuation, site went down because Gen fa=
iled to start due to grid bad voltage No Rcp// He bypassed grid and started=
 Gen manually","Albran Byorel","Grid Supply","Passive","Grid","National Gri=
d - Phase Controller Faulty","Grid fluctuation, site went down because Gen =
failed to start due to grid bad voltage No Rcp// He bypassed grid and start=
ed Gen manually","franck.nkomot@matech-cameroun.com","487","29-05-2025 06:1=
5:09","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005129248","O=
LAMA","","29-05-2025 03:56:45","29-05-2025 03:55:38","29-05-2025 03:59:15",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue.","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX=
 FME Henri (699949693) from Huawei is informed.Noticed that it is a repetit=
ve issue.","christelle.ngonga@matech-cameroun.com","68","29-05-2025 03:56:4=
5","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005128941","M=
essassi okolo","","29-05-2025 02:08:20","29-05-2025 02:06:16","29-05-2025 0=
8:10:32","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site down because site behaves as Grid only=
 site (Gen Noise) // Grid return","christelle.ngonga@matech-cameroun.com","=
1059401","29-05-2025 02:08:20","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005128938","E=
MANA BILICK CITY","IHS_YND_279","29-05-2025 02:07:23","29-05-2025 02:06:16"=
,"29-05-2025 08:15:42","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid return","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, site down be=
cause site behaves as Grid only site (Gen Noise) // Grid return","christell=
e.ngonga@matech-cameroun.com","68","29-05-2025 02:07:23","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005128933","N=
kolbong","","29-05-2025 02:05:28","29-05-2025 02:02:21","29-05-2025 08:07:5=
5","Site went Down because Gen started and stopped due to Gen overload(22kv=
a//350A),Radiator hose cut . // Grid returned","Delor Telezing","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Site went Down because Gen =
started and stopped due to Gen overload(22kva//350A),Radiator hose cut . //=
 Grid returned","christelle.ngonga@matech-cameroun.com","189","29-05-2025 0=
2:05:28","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0005128878","E=
koumdoum","","29-05-2025 01:35:50","29-05-2025 01:11:31","29-05-2025 02:44:=
30","Grid outage, site went down because gen start and stopped with high te=
mp alarm // he reset card and manual start of Gen","Albran Byorel","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site w=
ent down because gen start and stopped with high temp alarm // he reset car=
d and manual start of Gen","christelle.ngonga@matech-cameroun.com","1460","=
29-05-2025 01:35:50","MATECH CMR"
"Closed Complete","Site Down","T0370","IHS_YND_227","NOCINC0005128848","Mvo=
g Betsi","","29-05-2025 01:24:46","29-05-2025 01:19:31","29-05-2025 01:27:3=
1","Grid-Gen, eneo fluctuation, site down due to poor backup // eneo satbil=
ized","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid-Gen, eneo fluctuation, site down due to poor b=
ackup // eneo satbilized","franck.nkomot@matech-cameroun.com","315","29-05-=
2025 01:24:46","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005128613","S=
tade-Abega","","29-05-2025 00:36:30","29-05-2025 00:32:08","29-05-2025 00:4=
6:58","No pwer issus, site is on grid with Ubaie=3D53.4V, Lionel adjep(6551=
84876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pwer issu=
s, site is on grid with Ubaie=3D53.4V, Lionel adjep(655184876) from Huawei =
is informed","christelle.ngonga@matech-cameroun.com","263","29-05-2025 00:3=
6:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005128447","Yoko OCM=
","","29-05-2025 00:09:33","29-05-2025 00:02:16","29-05-2025 00:09:50","Cas=
caded Incident from TTO5271220","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site with Ubaie=3D53.8V=
 site on Gen ,The Tx Fme Gregoire( 652070658)from Huawei is informed","syst=
em","437","29-05-2025 00:09:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005128448","Ngouetou=
","","29-05-2025 00:09:33","29-05-2025 00:02:16","29-05-2025 00:09:50","Cas=
caded Incident from TTO5271220","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site with Ubaie=3D53.8V=
 site on Gen ,The Tx Fme Gregoire( 652070658)from Huawei is informed","syst=
em","437","29-05-2025 00:09:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005128449","MBIMBIM"=
,"","29-05-2025 00:09:33","29-05-2025 00:02:16","29-05-2025 00:09:50","Casc=
aded Incident from TTO5271220","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site with Ubaie=3D53.8V =
site on Gen ,The Tx Fme Gregoire( 652070658)from Huawei is informed","syste=
m","437","29-05-2025 00:09:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005128446","Ngoum","=
","29-05-2025 00:09:32","29-05-2025 00:02:16","29-05-2025 00:09:50","Cascad=
ed Incident from TTO5271220","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site with Ubaie=3D53.8V si=
te on Gen ,The Tx Fme Gregoire( 652070658)from Huawei is informed","system"=
,"436","29-05-2025 00:09:32","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005128434","M=
atsari","IHS_YND_475, IHS_YND_474, IHS_YND_454, IHS_YND_456","29-05-2025 00=
:07:22","29-05-2025 00:02:16","29-05-2025 00:09:50","No power issue on site=
 with Ubaie=3D53.8V site on Gen ,The Tx Fme Gregoire( 652070658)from Huawei=
 is informed","Parker Tchoup","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site with Ubaie=
=3D53.8V site on Gen ,The Tx Fme Gregoire( 652070658)from Huawei is informe=
d","christelle.ngonga@matech-cameroun.com","308","29-05-2025 00:07:22","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005128236","Emana Ly=
cee","","28-05-2025 23:18:49","28-05-2025 21:29:15","28-05-2025 23:14:15","=
Cascaded Incident from TTO5270756","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site down due to bad grid phase, =
// a bridge has been done on the good phase","system","1075811","28-05-2025=
 23:18:49","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0005128138","Sac=
re Coeur Catholic Church","","28-05-2025 22:56:58","28-05-2025 22:55:47","2=
8-05-2025 22:56:25","Incorrectly Logged Tickets","Mboua Thierry","Incorrect=
ly Logged Tickets","Error","Error","Error","TICKET CREATION ERROR","franck.=
nkomot@matech-cameroun.com","71","28-05-2025 22:56:58","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005128017","M=
vog-Manga","IHS_YND_274","28-05-2025 22:36:24","28-05-2025 21:29:15","28-05=
-2025 23:17:15","Site down due to on e bad grid phase, // A bridge has been=
 done on the good phase","Albran Byorel","Grid Supply","Passive","Grid","Na=
tional Grid - Grid Incomplete Phase","Site down due to bad grid phase, // a=
 bridge has been done on the good phase","christelle.ngonga@matech-cameroun=
.com","6431","28-05-2025 22:36:24","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005128012","M=
essassi 2","","28-05-2025 22:35:00","28-05-2025 22:30:47","28-05-2025 22:35=
:25","No power issue Ubaie:53.9 V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:53.9 V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","christelle.ngonga@matech-cameroun.com","255","28-05-2025 22:35:00","M=
ATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005127639","Acc=
acia New","","28-05-2025 21:41:36","28-05-2025 18:47:33","28-05-2025 21:53:=
56","Site went down due to disjunction dans le DC Box MTN 80A // He rearmed=
 CB (80A)","","Equipment Repair","Passive","Rectifier","Rectifier Module Ov=
erloaded","Site went down due to disjunction dans le DC Box MTN 80A // He r=
earmed CB (80A)","loic.noumsi@matech-cameroun.com","10445","28-05-2025 21:4=
1:36","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005127632","E=
mana lycee 2","","28-05-2025 21:40:53","28-05-2025 21:39:35","28-05-2025 23=
:53:35","Grid outage, site went down because gen failed to start due to PWC=
 ZTE malfunction // He reset the controller, grid return","Fabrice Pouakam"=
,"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,=
 site went down because gen failed to start due to PWC ZTE malfunction // H=
e reset the controller, grid return","gaelle.njiofack@matech-cameroun.com",=
"79","28-05-2025 21:40:53","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005127626","N=
kolfoulou","IHS_YND_719","28-05-2025 21:39:55","28-05-2025 21:35:44","28-05=
-2025 22:41:44","Grid outage, site went down before DG start due to Poor Ba=
tteries backup // Grid return","Siligap Boris","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before DG start due to Poor Batteries backup // Grid return","gaelle.njiof=
ack@matech-cameroun.com","252","28-05-2025 21:39:55","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005127609","T=
SINGA VILLAGE 2","","28-05-2025 21:38:49","28-05-2025 21:35:44","28-05-2025=
 22:41:44","","Delor Telezing","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down before DG start due to Poor=
 Batteries backup // Grid return","gaelle.njiofack@matech-cameroun.com","10=
75323","28-05-2025 21:38:49","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005127460","N=
YOM 2 IHS","","28-05-2025 21:10:19","28-05-2025 21:08:10","28-05-2025 21:25=
:54","No power issue Ubaie:54.31V site on Grid, site up without interventio=
n. TX fme symphorien /650257151 from huawei is informed.","Fabrice Pouakam"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue Ubaie:54.31V site on Grid, site up without inte=
rvention. TX fme symphorien /650257151 from huawei is informed.","gaelle.nj=
iofack@matech-cameroun.com","131","28-05-2025 21:10:19","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0005127436","Eko=
mbitie","","28-05-2025 21:08:29","28-05-2025 21:00:23","28-05-2025 21:42:36=
","Grid fluctuation , site went down because Gen started and stopped due to=
 Grid bad voltage// he bypassed, site is on GEN","Fabrice Pouakam","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation , site went down because Gen started and stopped due to Grid bad vo=
ltage// he bypassed, site is on GEN","loic.noumsi@matech-cameroun.com","487=
","28-05-2025 21:08:29","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005126816","B=
arriere","","28-05-2025 19:44:19","28-05-2025 19:22:10","28-05-2025 20:22:1=
0","No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/=
Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
bay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is informed.","gaell=
e.njiofack@matech-cameroun.com","1331","28-05-2025 19:44:19","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005126690","S=
aa","IHS_YND_810, IHS_YND_809","28-05-2025 19:25:00","28-05-2025 19:17:55",=
"28-05-2025 20:46:00","Grid outage. Site when down because Gen failed to st=
art due to fuel pump faulty//Grid return","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue on site ,site on Gen with Ubaie =3D53.8V The Tx Technici=
an from Huawei Gr=E9goire//654547479 is informed","loic.noumsi@matech-camer=
oun.com","426","28-05-2025 19:25:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005126678","Messassi=
 okolo","","28-05-2025 19:22:50","28-05-2025 19:18:26","28-05-2025 21:38:38=
","Cascaded Incident from TTO5269272","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (Gen Noise) // Grid return","system","10833=
12","28-05-2025 19:22:50","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005126672","E=
MANA BILICK CITY","IHS_YND_279","28-05-2025 19:21:34","28-05-2025 19:18:26"=
,"28-05-2025 21:42:38","Grid outage, site down because site behaves as Grid=
 only site (Gen Noise) // Grid return","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, site down be=
cause site behaves as Grid only site (Gen Noise) // Grid return","gaelle.nj=
iofack@matech-cameroun.com","190","28-05-2025 19:21:34","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005126671","Nko=
l-Mebanga","","28-05-2025 19:21:16","28-05-2025 19:21:55","28-05-2025 20:46=
:00","","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade=
 Active","Active// No power issue on site ,site on Gen with Ubaie =3D53.8V =
The Tx Technician from Huawei Gr=E9goire//654547479 is informed","loic.noum=
si@matech-cameroun.com","1080","28-05-2025 19:21:16","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005126668","N=
kolbong","","28-05-2025 19:20:45","28-05-2025 19:16:38","28-05-2025 21:34:3=
8","Site went Down because Gen started and stopped due to Gen overload(22kv=
a//350A) // Grid returned","Delor Telezing","Equipment Repair","Passive","D=
CDG Gen","DCDG - Overload","Site went Down because Gen started and stopped =
due to Gen overload(22kva//350A) // Grid returned","gaelle.njiofack@matech-=
cameroun.com","248","28-05-2025 19:20:45","MATECH CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0005126644","Car=
refour Ayissi Ele","","28-05-2025 19:16:24","28-05-2025 19:21:55","28-05-20=
25 20:46:00","","Parker Tchoup","Cascade Outage","Active","Cascade Active",=
"Cascade Active","Active// No power issue on site ,site on Gen with Ubaie =
=3D53.8V The Tx Technician from Huawei Gr=E9goire//654547479 is informed","=
loic.noumsi@matech-cameroun.com","1046","28-05-2025 19:16:24","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005126604","M=
essassi 2","","28-05-2025 19:08:00","28-05-2025 19:05:52","28-05-2025 20:36=
:42","No power issue Ubaie:54.04V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:54.04V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","gaelle.njiofack@matech-cameroun.com","131","28-05-2025 19:08:00","MAT=
ECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0005126585","ODZ=
A CITE MBIA","","28-05-2025 19:02:10","28-05-2025 13:18:57","28-05-2025 19:=
47:03","Site down because the neighbors turned off the GEN // GEN turned ba=
ck on by FME","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Emergency Stop","Site down because the neighbors turned off the GEN // G=
EN turned back on by FME","loic.noumsi@matech-cameroun.com","20594","28-05-=
2025 19:02:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005126284","Bastos-N=
ylon","","28-05-2025 18:23:00","28-05-2025 15:35:00","28-05-2025 17:47:57",=
"Cascaded Incident from TTO5267516","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Only, No space to deploy MDGE=
 // Grid returned","system","1096330","28-05-2025 18:23:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0005126285","Tsinga",=
"","28-05-2025 18:23:00","28-05-2025 15:35:00","28-05-2025 17:47:57","Casca=
ded Incident from TTO5267516","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid Only, No space to deploy MDGE // Gr=
id returned","system","1096329","28-05-2025 18:23:00","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0005126282","Nlo=
ngkak","","28-05-2025 18:22:20","28-05-2025 18:12:59","28-05-2025 19:13:48"=
,"Grid outage, Site down due to poor battery backup // Gen start automatica=
lly","Delor Telezing","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, Site down due to poor battery backup //=
 Gen start automatically","loic.noumsi@matech-cameroun.com","561","28-05-20=
25 18:22:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_175","NOCINC0005126135","Nkomo","=
","28-05-2025 18:02:22","28-05-2025 17:59:45","28-05-2025 18:38:04","Cascad=
ed Incident from TTO5268653","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage.gen failed to start due to=
 Alarm Overcurent // Grid return.","system","1087896","28-05-2025 18:02:22"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0005126120","A=
wae Escalier","IHS_YND_175","28-05-2025 18:00:56","28-05-2025 17:59:45","28=
-05-2025 18:38:04","Grid outage.gen failed to start due to Alarm Overcurent=
 // Grid return.","Albran Byorel","Equipment Repair","Passive","ACDG Gen","=
ACDG - Over Voltage","Grid outage.gen failed to start due to Alarm Overcure=
nt // Grid return.","gaelle.njiofack@matech-cameroun.com","72","28-05-2025 =
18:00:56","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005126111","Par=
adis Hotel","","28-05-2025 17:59:59","28-05-2025 17:50:53","28-05-2025 20:3=
9:05","Active //No power issue on site Ubaie =3D 53.2V. Fme TX Symphorien (=
650257151, HUAWEI) is informed","Siligap Boris","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //No pow=
er issue on site Ubaie =3D 53.2V. Fme TX Symphorien (650257151, HUAWEI) is =
informed","loic.noumsi@matech-cameroun.com","547","28-05-2025 17:59:59","MA=
TECH CMR"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0005126102","COR=
NIERS","","28-05-2025 17:59:21","28-05-2025 17:50:14","28-05-2025 19:34:08"=
,"Grid outage,no space to deploy mobile gen // Grid returned","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no sp=
ace to deploy mobile gen // Grid returned","loic.noumsi@matech-cameroun.com=
","548","28-05-2025 17:59:21","MATECH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0005126035","Mvo=
g-Ada_OCM","","28-05-2025 17:51:49","28-05-2025 17:48:36","28-05-2025 19:34=
:30","Grid Only site, No space to deploy MDGE // Grid returned","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only site,=
 No space to deploy MDGE // Grid returned","loic.noumsi@matech-cameroun.com=
","194","28-05-2025 17:51:49","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005126007","A=
wae Ewonkan","","28-05-2025 17:46:48","28-05-2025 17:40:43","28-05-2025 18:=
12:37","Grid outage site went down due to Gen overload (20kva,300A)//We red=
uced load and gen manually started","Albran Byorel","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage site went down due to Gen o=
verload (20kva,300A)//We reduced load and gen manually started","gaelle.nji=
ofack@matech-cameroun.com","366","28-05-2025 17:46:48","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005125830","A=
kak-Nkozoa-MTN-IHS","","28-05-2025 17:16:17","28-05-2025 16:58:07","28-05-2=
025 19:51:22","No power issue Ubaie:53.4V site on Grid, TX fme symphorien /=
650257151 from huawei is informed.","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue Ubaie:53.4V site on Grid, TX fme symphorien /650257151 from huawei is=
 informed.","gaelle.njiofack@matech-cameroun.com","1092","28-05-2025 17:16:=
17","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0005125793","Nko=
mo stade","","28-05-2025 17:09:44","28-05-2025 17:02:38","28-05-2025 18:48:=
09","Grid outage.gen failed to start due to Alarm low oil Pressure // Grid =
return and Gen card reset.","Mba Lazare Herve","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Low Oil Pressure","Grid outage.gen failed to start due =
to Alarm low oil Pressure // Grid return and Gen card reset.","loic.noumsi@=
matech-cameroun.com","427","28-05-2025 17:09:44","MATECH CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0005125773","S=
oa-II","IHS_YND_324","28-05-2025 17:06:18","28-05-2025 16:58:04","29-05-202=
5 10:54:18","Active // No power issue on site Ubay:56.2V , site on grid , J=
ulien ( 693095849 /Huawei) is informed","Siligap Boris","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue on site Ubay:56.2V , site on grid , Julien ( 693095849 /H=
uawei) is informed","loic.noumsi@matech-cameroun.com","495","28-05-2025 17:=
06:18","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005125728","M=
ontee-Jouvence-II","","28-05-2025 16:56:42","28-05-2025 16:42:13","28-05-20=
25 18:47:11","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid Outage Site went down because Gen Overload (20KV=
A, 300A) // Grid returned","loic.noumsi@matech-cameroun.com","1092429","28-=
05-2025 16:56:42","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005125722","D=
amas","","28-05-2025 16:54:00","28-05-2025 16:42:13","28-05-2025 18:47:11",=
"","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid Outage Site went down because Gen Overload (20KVA, 300A) // Gr=
id returned","loic.noumsi@matech-cameroun.com","1092431","28-05-2025 16:54:=
00","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005125709","T=
amtam Weekend","IHS_YND_153, IHS_YND_166, IHS_YND_562, IHS_YND_518","28-05-=
2025 16:51:18","28-05-2025 16:42:13","28-05-2025 18:47:32","Grid Outage Sit=
e went down because Gen Overload (20KVA, 300A) // Grid returned","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outa=
ge Site went down because Gen Overload (20KVA, 300A) // Grid returned","loi=
c.noumsi@matech-cameroun.com","546","28-05-2025 16:51:18","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005125695","A=
ccacia New","","28-05-2025 16:47:53","28-05-2025 16:42:13","28-05-2025 18:4=
7:32","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Grid Outage Site went down because Gen Overload (20KVA, 300A) // Grid retu=
rned","loic.noumsi@matech-cameroun.com","1092431","28-05-2025 16:47:53","MA=
TECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005125656","Ron=
d Point Express1114","","28-05-2025 16:45:41","28-05-2025 16:42:13","28-05-=
2025 18:44:06","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid Outage Site went down because Gen Overload (20=
KVA, 300A) // Grid returned","loic.noumsi@matech-cameroun.com","1092431","2=
8-05-2025 16:45:41","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005125633","Mai=
son komkana New","","28-05-2025 16:41:49","28-05-2025 16:34:43","28-05-2025=
 17:50:43","Grid outage,gen failed to start due to no battery GE //Gen manu=
ally started with external battery","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Generator Battery","Grid outage,gen failed to star=
t due to no battery GE //Gen manually started with external battery","loic.=
noumsi@matech-cameroun.com","427","28-05-2025 16:41:49","MATECH CMR"
"Closed Complete","Site Down","T1669","IHS_YND_195","NOCINC0005125374","chi=
na embassy yde","","28-05-2025 16:07:11","28-05-2025 16:03:02","28-05-2025 =
17:06:35","Grid outage, No space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
No space to deploy MDGE // Grid returned","loic.noumsi@matech-cameroun.com"=
,"250","28-05-2025 16:07:11","MATECH CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0005125309","Ako=
no","","28-05-2025 15:59:39","","","Alarm cleaned","Fanda Brice","Warning",=
"Warning","ENVIRONMENT","Warning - High Temperature","Alarm cleaned","loic.=
noumsi@matech-cameroun.com","795","28-05-2025 15:59:39","MATECH CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0005125138","Nko=
mkana","IHS_YND_138, IHS_YND_126, IHS_YND_127","28-05-2025 15:43:08","28-05=
-2025 15:35:00","28-05-2025 17:47:57","Grid Only, No space to deploy MDGE /=
/ Grid returned","","Grid Supply","Passive","Grid","National Grid - Grid Ou=
tage Issue","Grid Only, No space to deploy MDGE // Grid returned","loic.nou=
msi@matech-cameroun.com","490","28-05-2025 15:43:08","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0005125131","N=
komkana 2","","28-05-2025 15:42:18","28-05-2025 15:34:08","28-05-2025 17:47=
:57","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid Only, No space to deploy MDGE // Grid returned","gaelle.n=
jiofack@matech-cameroun.com","492","28-05-2025 15:42:18","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005124863","O=
dza-PK10","","28-05-2025 15:20:48","28-05-2025 15:10:59","28-05-2025 16:00:=
54"," brice kalong (botcom/690981199) is on site for swap of bay // End of =
work","Albran Byorel","Equipment Replacement","Passive","Planned Activity",=
"Planned Activity - Passive"," brice kalong (botcom/690981199) is on site f=
or swap of bay // End of work","gaelle.njiofack@matech-cameroun.com","589",=
"28-05-2025 15:20:48","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0005124836","Mai=
son komkana New","","28-05-2025 15:17:03","28-05-2025 15:07:51","28-05-2025=
 15:52:02","Grid outage,gen failed to start due to no battery GE //Gen manu=
ally started with external battery","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Generator Battery","Grid outage,gen failed to star=
t due to no battery GE //Gen manually started with external battery","loic.=
noumsi@matech-cameroun.com","553","28-05-2025 15:17:03","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005124733","Men=
dong3","","28-05-2025 15:05:19","28-05-2025 14:59:52","28-05-2025 17:47:14"=
,"Grid Outage No space to deploy a MDG // Grid returned","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No space t=
o deploy a MDG // Grid returned","gaelle.njiofack@matech-cameroun.com","328=
","28-05-2025 15:05:19","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005124559","C=
rf-Nsam","","28-05-2025 14:52:57","28-05-2025 14:52:52","28-05-2025 17:05:1=
0","Active//No power issue on site Ubaie =3D53.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D53.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","6",=
"28-05-2025 14:52:57","MATECH CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0005124531","P=
olytechnique","","28-05-2025 14:50:16","28-05-2025 14:42:07","28-05-2025 15=
:35:59","Grid only site , No space to deploy MDGE // Grid power returned","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
only site , No space to deploy MDGE // Grid power returned","gaelle.njiofac=
k@matech-cameroun.com","490","28-05-2025 14:50:16","MATECH CMR"
"Closed Complete","Warning","T0103","IHS_YND_110","NOCINC0005124469","Camp-=
Sonel","","28-05-2025 14:43:36","","","Grid bad voltage // He bypassed Grid=
 and started Gen manually","Siligap Boris","Warning","Warning","POWER","War=
ning - National Grid - Grid Incomplete Phase","Grid bad voltage // He bypas=
sed Grid and started Gen manually","loic.noumsi@matech-cameroun.com","493",=
"28-05-2025 14:43:36","MATECH CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0005124087","MES=
SAME NDONGO 1162","","28-05-2025 13:53:33","28-05-2025 13:51:16","28-05-202=
5 14:10:00","Grid outage,gen failed to start due to Gen card malfunctioning=
//he reseted the card and he started Gen manually","MINKA NICOLAS","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,gen fai=
led to start due to Gen card malfunctioning//he reseted the card and he sta=
rted Gen manually","vanel.mbiada@matech-cameroun.com","138","28-05-2025 13:=
53:33","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005124083","Fla=
menco","","28-05-2025 13:52:39","28-05-2025 13:47:19","28-05-2025 14:19:57"=
,"Grid outage,gen failed to start due to card GE dysfunctionned//We reset c=
ard GE and gen manually started","Mboua Thierry","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due t=
o card GE dysfunctionned//We reset card GE and gen manually started","vanel=
.mbiada@matech-cameroun.com","321","28-05-2025 13:52:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005124073","Bastos B=
ethesda","","28-05-2025 13:50:49","28-05-2025 13:40:44","28-05-2025 14:43:4=
5","Cascaded Incident from TTO5266303","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage gen failed to start=
 due to card GE dysfunctioned // He reseted it and started Gen manually","s=
ystem","1224595","28-05-2025 13:50:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005124071","Golf Qua=
ter","","28-05-2025 13:50:49","28-05-2025 13:40:44","28-05-2025 14:43:45","=
Cascaded Incident from TTO5266303","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage gen failed to start due=
 to card GE dysfunctioned // He reseted it and started Gen manually","syste=
m","1224596","28-05-2025 13:50:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005124072","Bastos-N=
ylon","","28-05-2025 13:50:49","28-05-2025 13:40:44","28-05-2025 14:43:45",=
"Cascaded Incident from TTO5266303","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage gen failed to start du=
e to card GE dysfunctioned // He reseted it and started Gen manually","syst=
em","1224595","28-05-2025 13:50:49","MATECH CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0005124049","Bas=
tos Ekoudou","","28-05-2025 13:45:36","28-05-2025 13:41:14","28-05-2025 13:=
51:06","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automaticaly","Mboua Thierry","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen start automaticaly","v=
anel.mbiada@matech-cameroun.com","263","28-05-2025 13:45:36","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005124008","T=
singa","IHS_YND_220, IHS_YND_126, IHS_YND_563","28-05-2025 13:41:54","28-05=
-2025 13:40:44","28-05-2025 14:42:08","Grid outage gen failed to start due =
to card GE dysfunctioned // He reseted it and started Gen manually","Mboua =
Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage gen failed to start due to card GE dysfunctioned // He reseted it=
 and started Gen manually","vanel.mbiada@matech-cameroun.com","71","28-05-2=
025 13:41:54","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005123947","Ako=
k Ndoe Yde","","28-05-2025 13:36:39","28-05-2025 13:32:28","28-05-2025 14:5=
6:24","Grid fluctuation, site went down because gen failed to start due to =
grid bad voltage No Rcp on site // He bypassed Grid and started Gen manuall=
y","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation, site went down because gen failed to s=
tart due to grid bad voltage No Rcp on site // He bypassed Grid and started=
 Gen manualy","vanel.mbiada@matech-cameroun.com","252","28-05-2025 13:36:39=
","MATECH CMR"
"Closed Complete","Site Down","CTR_447","IHS_YND_061","NOCINC0005123835","Y=
de University","","28-05-2025 13:29:12","28-05-2025 13:24:39","28-05-2025 1=
7:43:39","Active// No power Issue Site on gen Ubaie =3D52.1V, The FME Tx Th=
e TX FME Mbah Hosiah (674007438) is informed, Notice that we have disjuncti=
on at BTS OCM","Paul BIBOUM","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site on ge=
n Ubaie =3D52.1V, The FME Tx The TX FME Mbah Hosiah (674007438) is informed=
, Notice that we have disjunction at BTS OCM","vanel.mbiada@matech-cameroun=
.com","274","28-05-2025 13:29:12","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005123725","NKO=
MKANA ELIZA HOTEL","","28-05-2025 13:23:07","28-05-2025 13:18:13","28-05-20=
25 17:48:23","Grid outage, no space to deploy MDGE on site // Grid returned=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage, no space to deploy MDGE on site // Grid returned","vanel.mbiada@=
matech-cameroun.com","295","28-05-2025 13:23:07","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005123662","Nom=
ayos montee Meche","","28-05-2025 13:14:29","28-05-2025 13:12:17","28-05-20=
25 13:14:21","Grid outage, site went down before Gen started due to poor ba=
ckup battery // Grid returned","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen started due to poor backup battery // Grid returned","vanel.mbiad=
a@matech-cameroun.com","133","28-05-2025 13:14:29","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005123425","S=
oa-Sofamac","IHS_YND_720","28-05-2025 12:34:34","28-05-2025 12:28:33","28-0=
5-2025 13:11:09","Grid outage, site went down because gen failed to start w=
ith alarm overvoltage // He reset gen card and gen manually started","Silig=
ap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, site went down because gen failed to start with alarm overvolta=
ge // He reset gen card and gen manually started","vanel.mbiada@matech-came=
roun.com","362","28-05-2025 12:34:34","MATECH CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0005123394","S=
OA UNIVERSITY STADIUM","","28-05-2025 12:33:07","28-05-2025 12:28:33","28-0=
5-2025 13:11:09","","Siligap Boris","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, site went down because gen failed to =
start with alarm overvoltage // He reset gen card and gen manually started"=
,"vanel.mbiada@matech-cameroun.com","1100916","28-05-2025 12:33:07","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005123329","C=
hapelle-Nsimeyong","","28-05-2025 12:21:02","28-05-2025 12:19:47","28-05-20=
25 12:54:44","Site went down Gen failed to start due to Grid bad voltage(la=
ck of 02 phases on site)// He did a bridge on the Good phase","MINKA NICOLA=
S","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Site went down Gen failed to start due to Grid bad voltage(lack of 02 pha=
ses on site)// He did a bridge on the Good phase","vanel.mbiada@matech-came=
roun.com","75","28-05-2025 12:21:02","MATECH CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0005123286","Nko=
lo II New","","28-05-2025 12:13:47","28-05-2025 12:07:33","29-05-2025 10:51=
:30","No power issue, Site impacted by Mimboman-Don-Bosco","Mba Lazare Herv=
e","Customer Equipment Failure","Active","Active Equipment Failure","Affect=
ed by 3rd Party Site","No power issue, Site impacted by Mimboman-Don-Bosco"=
,"vanel.mbiada@matech-cameroun.com","376","28-05-2025 12:13:47","MATECH CMR=
"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005123280","Mim=
boman4","","28-05-2025 12:12:45","28-05-2025 12:07:32","28-05-2025 12:13:03=
","Grid fluctuations, site went down because Gen failed to start due to gri=
d bad voltage // Grid stabilised","Mba Lazare Herve","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuations, site=
 went down because Gen failed to start due to grid bad voltage // Grid stab=
ilised","vanel.mbiada@matech-cameroun.com","314","28-05-2025 12:12:45","MAT=
ECH CMR"
"Closed Complete","Warning","T0462","IHS_YND_123","NOCINC0005123217","Nkomo=
 II","","28-05-2025 12:05:47","","","Site alarming due to Grid outage // Gr=
id return","Albran Byorel","Warning","Warning","POWER","Warning - National =
Grid - Grid Outage Issue","Site alarming due to Grid outage // Grid return"=
,"landry.etame@ihstowers.com","319","28-05-2025 12:05:47","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005123216","E=
bogo","","28-05-2025 12:05:39","28-05-2025 12:03:29","28-05-2025 12:06:35",=
"Grid outage, site went down before Gen start due poor backup battery // Ge=
n automatically started","Siligap Boris","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e Gen start due poor backup battery // Gen automatically started","vanel.mb=
iada@matech-cameroun.com","131","28-05-2025 12:05:39","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005123171","Eto=
ug ebe Carrefour","","28-05-2025 11:58:21","28-05-2025 11:38:13","28-05-202=
5 13:18:25","Grid outage, site went down because Gen failed to start due to=
 battery Gen faulty // Grid returned","Hyemafo Gildas","Equipment Repair","=
Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, site went down=
 because Gen failed to start due to battery Gen faulty // Grid returned","v=
anel.mbiada@matech-cameroun.com","1209","28-05-2025 11:58:21","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0005123045","Oko=
lo Kilombo","","28-05-2025 11:42:45","28-05-2025 11:38:59","28-05-2025 12:2=
2:29","Site went down because Gen failed to start due to Relay (180V) ATS f=
aulty // He replaced it and Site on Grid","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","ATS Relay Faulty","Site went down because Ge=
n failed to start due to Relay (180V) ATS faulty // He replaced it and Site=
 on Grid","vanel.mbiada@matech-cameroun.com","227","28-05-2025 11:42:45","M=
ATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005123015","Mes=
sassi 2","","28-05-2025 11:34:32","28-05-2025 11:31:50","28-05-2025 11:40:5=
8","Grid outage site went down because Gen failed to start due to poor Batt=
ery backup// GEN automatically started","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site=
 went down because Gen failed to start due to poor Battery backup// GEN aut=
omatically started","vanel.mbiada@matech-cameroun.com","164","28-05-2025 11=
:34:32","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005122825","ODZ=
A MINKAN EDIBI ASSI","","28-05-2025 11:08:09","28-05-2025 11:05:54","28-05-=
2025 11:17:51","Site went down due to work done by ALBRAN(657108452) for PM=
 works//End of work","Albran Byorel","Installation Activity","Passive","Pla=
nned Activity","Installation Activity","Site went down due to work done by =
ALBRAN(657108452) for PM works//End of work","vanel.mbiada@matech-cameroun.=
com","136","28-05-2025 11:08:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005122787","MEHANDAN=
","","28-05-2025 11:04:06","28-05-2025 11:00:18","28-05-2025 11:04:27","Cas=
caded Incident from TTO5264938","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
1106077","28-05-2025 11:04:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005122788","Nkongtoc=
k","","28-05-2025 11:04:06","28-05-2025 11:00:18","28-05-2025 11:04:27","Ca=
scaded Incident from TTO5264938","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen failed to start due to PWC ZTE malfunction // Site stabilised","system=
","1106077","28-05-2025 11:04:06","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005122776","O=
dza II OCM","IHS_YND_528, IHS_YND_349","28-05-2025 11:02:31","28-05-2025 11=
:00:18","28-05-2025 11:04:27","Grid outage, site went down because gen fail=
ed to start due to PWC ZTE malfunction // Site stabilised","Albran Byorel",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gri=
d outage, site went down because gen failed to start due to PWC ZTE malfunc=
tion // Site stabilised","vanel.mbiada@matech-cameroun.com","135","28-05-20=
25 11:02:31","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005122712","OBA=
M NGOLA OCM","","28-05-2025 10:51:55","28-05-2025 10:48:32","28-05-2025 13:=
53:30","Grid outage, site went down due to Grid bad voltage and Gen failed =
to start due to card Ge faulty // He reseted it and started Gen manually af=
ter bypassing Grid","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage, site went down due to Grid bad voltag=
e and Gen failed to start due to card Ge faulty // He reseted it and starte=
d Gen manually after bypassing Grid","vanel.mbiada@matech-cameroun.com","20=
3","28-05-2025 10:51:55","MATECH CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0005122700","Mba=
nkomo CAF","","28-05-2025 10:48:07","28-05-2025 10:37:00","28-05-2025 11:53=
:06","Site went down due to disjunction of Gen Cb // He rearmed Cb, site on=
 Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Load Br=
eaker","Site went down due to disjunction of Gen Cb // He rearmed Cb, site =
on Gen","vanel.mbiada@matech-cameroun.com","668","28-05-2025 10:48:07","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005122288","N=
kolfon Cimencam","","28-05-2025 09:39:10","28-05-2025 09:34:56","28-05-2025=
 10:48:07","No power issue, Site impacted by Afanoya-II wich is not IHS sit=
e.","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipmen=
t Failure","Affected by 3rd Party Site","No power issue, Site impacted by A=
fanoya-II wich is not IHS site.","vanel.mbiada@matech-cameroun.com","256","=
28-05-2025 09:39:10","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005122230","O=
LAMA","","28-05-2025 09:30:10","28-05-2025 09:26:57","28-05-2025 11:35:26",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue.","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX=
 FME Henri (699949693) from Huawei is informed.Noticed that it is a repetit=
ve issue.","vanel.mbiada@matech-cameroun.com","194","28-05-2025 09:30:10","=
MATECH CMR"
"Cancelled","Warning","CTR_526","IHS_YND_696","NOCINC0005122090","Barriere =
IHS","","28-05-2025 09:10:25","","","fme Gildas report that Gen overload(15=
Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return","Hyemafo Gildas",=
"","","","","","vanel.mbiada@matech-cameroun.com","373","28-05-2025 09:10:2=
5","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005122085","S=
IMBOCK BONAMBAPE","IHS_YND_258","28-05-2025 09:09:03","28-05-2025 09:04:53"=
,"28-05-2025 11:20:00","Active // No power issue site on grid with Ubaie: 5=
2.9V TX FME Flubert (654266068) from Huawei is informed","Hyemafo Gildas","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active // No power issue site on grid with Ubaie: 52.9V TX FME F=
lubert (654266068) from Huawei is informed","vanel.mbiada@matech-cameroun.c=
om","251","28-05-2025 09:09:03","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005122077","M=
efou-Assi","","28-05-2025 09:07:50","28-05-2025 09:04:53","28-05-2025 09:20=
:00","gen Overload","Fanda Brice","Cascade Outage","Active","Cascade Active=
","Cascade Active","Active // No power issue site on grid with Ubaie: 52.9V=
 TX FME Flubert (654266068) from Huawei is informed","vanel.mbiada@matech-c=
ameroun.com","1112850","28-05-2025 09:07:50","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005122040","MBA=
LNGONG LYCEE","","28-05-2025 09:01:53","28-05-2025 08:57:29","28-05-2025 10=
:46:54","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down be=
cause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informe=
d and confirmed // Grid returned","vanel.mbiada@matech-cameroun.com","265",=
"28-05-2025 09:01:53","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005122009","N=
kolbong","","28-05-2025 08:56:48","28-05-2025 08:46:59","28-05-2025 11:33:3=
7","Site went Down because Gen started and stopped due to Gen overload(22kv=
a//350A) // Grid returned","Delor Telezing","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Site went Down because Gen started and stopped =
due to Gen overload(22kva//350A) // Grid returned","vanel.mbiada@matech-cam=
eroun.com","590","28-05-2025 08:56:48","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0005121958","Oko=
lo Kilombo","","28-05-2025 08:44:11","28-05-2025 08:41:56","28-05-2025 09:3=
9:11","Grid outage,site went down because Gen failed to start due to Grid b=
ad voltage,no rp on site//He bypassed the Grid and site on Gen","Fabrice Po=
uakam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid outage,site went down because Gen failed to start due to Grid ba=
d voltage,no rp on site//He bypassed the Grid and site on Gen","vanel.mbiad=
a@matech-cameroun.com","136","28-05-2025 08:44:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005121865","Messassi=
 okolo","","28-05-2025 08:30:58","28-05-2025 08:26:00","28-05-2025 11:38:21=
","Cascaded Incident from TTO5263921","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaved as Grid only site ( Gen Noise) //Grid returned","system","111=
5127","28-05-2025 08:30:58","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005121863","E=
MANA BILICK CITY","IHS_YND_279","28-05-2025 08:30:23","28-05-2025 08:26:00"=
,"28-05-2025 11:39:29","Grid outage, site down because generator faulty//Gr=
id return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG =
- Generator Faulty","Grid outage, site down because generator faulty//Grid =
return","vanel.mbiada@matech-cameroun.com","265","28-05-2025 08:30:23","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0005121861","Emana ly=
cee 2","IHS_YND_274","28-05-2025 08:29:46","28-05-2025 08:25:36","28-05-202=
5 08:43:16","Grid outage , site went down before Gen started due to poor ba=
ttery backup //gen automaticaly started","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage , s=
ite went down before Gen started due to poor battery backup //gen automatic=
aly started","system","250","28-05-2025 08:29:46","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005121857","E=
mana Lycee","","28-05-2025 08:28:50","28-05-2025 08:25:36","28-05-2025 08:4=
3:16","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage , site went down before Gen started due to poor=
 battery backup //gen automaticaly started","vanel.mbiada@matech-cameroun.c=
om","1115151","28-05-2025 08:28:50","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005121848","M=
essassi 2","","28-05-2025 08:26:39","28-05-2025 08:24:25","28-05-2025 08:37=
:31","Grid outage site went down because Gen failed to start due to poor Ba=
ttery backup// GEN automatically started","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage si=
te went down because Gen failed to start due to poor Battery backup// GEN a=
utomatically started","vanel.mbiada@matech-cameroun.com","136","28-05-2025 =
08:26:39","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005121532","Mon=
tee Jouvence","","28-05-2025 07:29:47","28-05-2025 07:28:34","28-05-2025 08=
:29:50","Grid outage gen failed to start due to alarm high temp//We add wat=
er and gen manually started","Hyemafo Gildas","Equipment Repair","Passive",=
"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage gen=
 failed to start due to alarm high temp//We add water and gen manually star=
ted","vanel.mbiada@matech-cameroun.com","74","28-05-2025 07:29:47","MATECH =
CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005121433","Men=
dong3","","28-05-2025 07:02:31","28-05-2025 06:59:18","28-05-2025 10:41:00"=
,"Grid Outage No space to deploy a MDG //Grid Return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Outage No space to d=
eploy a MDG //Grid Return","vanel.mbiada@matech-cameroun.com","194","28-05-=
2025 07:02:31","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005121426","S=
IMBOCK BONAMBAPE","","28-05-2025 06:59:11","28-05-2025 06:57:40","28-05-202=
5 07:01:12","Grid outage, Site went down before Gen start due to poor backu=
p // Gen automatically started","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Gen automatically started","vanel=
.mbiada@matech-cameroun.com","92","28-05-2025 06:59:11","MATECH CMR"
"Closed Complete","Site Down","T0460","IHS_YND_201","NOCINC0005121416","Cit=
e Verte","","28-05-2025 06:58:10","28-05-2025 06:56:48","28-05-2025 07:30:1=
1","Active//No power issue, site is on Grid with Ubaie=3D53V The Tx brice T=
chague / 650214096/ from Huawei is informed ","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue, site is on Grid with Ubaie=3D53V The Tx brice Tchague / 650214096=
/ from Huawei is informed ","vanel.mbiada@matech-cameroun.com","83","28-05-=
2025 06:58:10","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005121287","S=
aa","","28-05-2025 06:34:10","28-05-2025 06:31:48","28-05-2025 08:00:03","A=
ctive// No power issue on site ,site on Gen with Ubaie =3D53.8V The Tx Tech=
nician from Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue on site ,site on Gen with Ubaie =3D53.8V The=
 Tx Technician from Huawei Gr=E9goire//654547479 is informed","vanel.mbiada=
@matech-cameroun.com","144","28-05-2025 06:34:10","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0005120848","Eke=
kam","","28-05-2025 04:10:30","28-05-2025 04:06:18","28-05-2025 08:52:38","=
Hybrid gen site.site went down due to hybrid system failure//Gen manually s=
tarted","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Hybrid","H=
ybrid Module","Hybrid gen site.site went down due to hybrid system failure/=
/Gen manually started","franck.nkomot@matech-cameroun.com","253","28-05-202=
5 04:10:30","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005120773","Nko=
abang Alembe","","28-05-2025 03:28:33","28-05-2025 03:24:23","28-05-2025 12=
:23:47","site went down due to imsufficiency of rectifiers IHS SS Alphonse =
is informed//site sitabilized ","Mba Lazare Herve","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","site went down due to imsufficiency of=
 rectifiers IHS SS Alphonse is informed//site sitabilized ","franck.nkomot@=
matech-cameroun.com","251","28-05-2025 03:28:33","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005120772","O=
LAMA","","28-05-2025 03:27:57","28-05-2025 03:25:46","28-05-2025 04:24:04",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue.","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX=
 FME Henri (699949693) from Huawei is informed.Noticed that it is a repetit=
ve issue.","christelle.ngonga@matech-cameroun.com","132","28-05-2025 03:27:=
57","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005120710","N=
gouetou","","28-05-2025 03:13:21","28-05-2025 03:08:36","28-05-2025 03:17:4=
7","TTO5262670","Parker Tchoup","Cascade Outage","Active","Cascade Active",=
"Cascade Active","TTO5262670","christelle.ngonga@matech-cameroun.com","1133=
916","28-05-2025 03:13:21","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0005120709","M=
atsari","IHS_YND_475, IHS_YND_474, IHS_YND_454, IHS_YND_456","28-05-2025 03=
:12:45","28-05-2025 03:08:36","28-05-2025 03:17:47","No power issue on site=
 with Ubaie=3D56V site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gre=
goire( 652070658)from Huawei is informed","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site with Ubaie=3D56V site on Gen (start threshold ubai=3D48.4=
V) The Tx Fme Gregoire( 652070658)from Huawei is informed","christelle.ngon=
ga@matech-cameroun.com","250","28-05-2025 03:12:45","MATECH CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0005120708","M=
BIMBIM","","28-05-2025 03:11:53","28-05-2025 03:08:36","28-05-2025 03:17:47=
","","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Ac=
tive","No power issue on site with Ubaie=3D56V site on Gen (start threshold=
 ubai=3D48.4V) The Tx Fme Gregoire( 652070658)from Huawei is informed","chr=
istelle.ngonga@matech-cameroun.com","1133917","28-05-2025 03:11:53","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0005120707","N=
goum","","28-05-2025 03:11:23","28-05-2025 03:08:36","28-05-2025 03:17:47",=
"","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","No power issue on site with Ubaie=3D56V site on Gen (start threshold u=
bai=3D48.4V) The Tx Fme Gregoire( 652070658)from Huawei is informed","chris=
telle.ngonga@matech-cameroun.com","1133916","28-05-2025 03:11:23","MATECH C=
MR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0005120705","Y=
oko OCM","","28-05-2025 03:10:11","28-05-2025 03:08:36","28-05-2025 03:17:4=
7","","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","No power issue on site with Ubaie=3D56V site on Gen (start threshol=
d ubai=3D48.4V) The Tx Fme Gregoire( 652070658)from Huawei is informed","ch=
ristelle.ngonga@matech-cameroun.com","1133917","28-05-2025 03:10:11","MATEC=
H CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0005120187","Lab=
oratoire  Meka","","28-05-2025 00:38:08","28-05-2025 00:21:34","28-05-2025 =
17:23:47","Grid Only, No space to deploy MDG // Grid returned","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No sp=
ace to deploy MDG // Grid returned","franck.nkomot@matech-cameroun.com","99=
5","28-05-2025 00:38:08","MATECH CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0005119996","N=
KOMEKUI OCM","IHS_YND_341, IHS_YND_713","27-05-2025 23:32:14","27-05-2025 2=
3:28:06","28-05-2025 03:29:55","Grid fluctuation, Site went down because Ge=
n failed to start due to Grid bad voltage //He bypass Grid and put site on =
Gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Grid fluctuation, Site went down because Gen=
 failed to start due to Grid bad voltage //He bypass Grid and put site on G=
en","christelle.ngonga@matech-cameroun.com","249","27-05-2025 23:32:14","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0005119909","N=
KONGKARAK","","27-05-2025 23:10:32","27-05-2025 23:28:06","28-05-2025 03:29=
:55","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid fluctuation, Site went down because Gen failed=
 to start due to Grid bad voltage //He bypass Grid and put site on Gen","ch=
ristelle.ngonga@matech-cameroun.com","1146990","27-05-2025 23:10:32","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0005119905","L=
obo OCM","","27-05-2025 23:09:42","27-05-2025 23:28:06","28-05-2025 03:29:5=
5","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid fluctuation, Site went down because Gen failed t=
o start due to Grid bad voltage //He bypass Grid and put site on Gen","chri=
stelle.ngonga@matech-cameroun.com","1146990","27-05-2025 23:09:42","MATECH =
CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005119858","M=
essassi 2","","27-05-2025 22:59:10","27-05-2025 22:53:00","27-05-2025 23:01=
:14","No power issue Ubaie:54.04V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:54.31V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","christelle.ngonga@matech-cameroun.com","372","27-05-2025 22:59:10","M=
ATECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0005119658","ODZ=
A CITE MBIA","","27-05-2025 22:25:48","27-05-2025 22:20:41","28-05-2025 00:=
55:41","Site down because the neighbors turned off the GEN // GEN turns bac=
k on by FME","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- Emergency Stop","Site down because the neighbors turned off the GEN // GE=
N turns back on by FME","loic.noumsi@matech-cameroun.com","308","27-05-2025=
 22:25:48","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0005119553","Eke=
kam","","27-05-2025 22:07:07","27-05-2025 21:59:13","27-05-2025 23:22:13","=
Hybrid Gen, site went down because Gen failed to start due to automation ma=
lfunctioning // He started Gen manually","TIENTCHEU NZETCHIEU GAEL","Equipm=
ent Repair","Passive","Control Panel","ATS-AMF Issue","Hybrid Gen, site wen=
t down because Gen failed to start due to automation malfunctioning // He s=
tarted Gen manually","loic.noumsi@matech-cameroun.com","475","27-05-2025 22=
:07:07","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005119547","N=
kolfon Cimencam","","27-05-2025 22:05:46","27-05-2025 22:00:54","27-05-2025=
 23:42:13","	No power issue, Site impacted by Afanoya-II wich is not IHS si=
te.","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipme=
nt Failure","Affected by 3rd Party Site","	No power issue, Site impacted by=
 Afanoya-II wich is not IHS site.","gaelle.njiofack@matech-cameroun.com","2=
93","27-05-2025 22:05:46","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005119406","E=
ssomba","","27-05-2025 21:40:28","27-05-2025 21:36:19","27-05-2025 23:04:55=
","Site went down because 03/06 rectifiers dysfunctionned //Site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down because 03/06 rectifiers dysfunctionned //Site stabil=
ised","loic.noumsi@matech-cameroun.com","250","27-05-2025 21:40:28","MATECH=
 CMR"
"Closed Complete","Warning","CTR_016","IHS_YND_226","NOCINC0005119397","Mvo=
g-Betsi","","27-05-2025 21:38:33","","","the air conditioning was off // th=
e fme turned on the air conditioning","Hyemafo Gildas","Warning","Warning",=
"ENVIRONMENT","Warning - High Temperature","the air conditioning was off //=
 the fme turned on the air conditioning","loic.noumsi@matech-cameroun.com",=
"15750","27-05-2025 21:38:33","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005119352","S=
tade-Abega","","27-05-2025 21:31:18","27-05-2025 20:52:00","27-05-2025 23:2=
8:00","No pwer issus, site is on grid with Ubaie=3D53.4V, Lionel adjep(6551=
84876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pwer issu=
s, site is on grid with Ubaie=3D53.4V, Lionel adjep(655184876) from Huawei =
is informed","gaelle.njiofack@matech-cameroun.com","2359","27-05-2025 21:31=
:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0005119091","Nkolo II=
 New","","27-05-2025 21:01:45","27-05-2025 20:57:43","27-05-2025 21:03:16",=
"Cascaded Incident from TTO5260869","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuations, site went do=
wn because Gen failed to start due to grid bad voltage // Grid stabilised",=
"system","1149753","27-05-2025 21:01:45","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005119087","Mim=
boman4","IHS_YND_709","27-05-2025 21:01:04","27-05-2025 20:57:43","27-05-20=
25 21:03:16","Grid fluctuations, site went down because Gen failed to start=
 due to grid bad voltage // Grid stabilised","Mba Lazare Herve","Grid Suppl=
y","Passive","Grid","National Grid - Unstable Grid Supply Issue","Grid fluc=
tuations, site went down because Gen failed to start due to grid bad voltag=
e // Grid stabilised","gaelle.njiofack@matech-cameroun.com","202","27-05-20=
25 21:01:04","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005118804","NYO=
M FACE MAETUR","","27-05-2025 20:19:29","27-05-2025 20:17:13","27-05-2025 2=
0:28:51","Grid outage; Gen failed to start due to Low level of Oil // Grid =
return and Oil add","Fabrice Pouakam","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Oil Leakage","Grid outage; Gen failed to start due to Low level =
of Oil // Grid return and Oil add","loic.noumsi@matech-cameroun.com","137",=
"27-05-2025 20:19:29","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005118747","N=
YOM 2 IHS","","27-05-2025 20:13:18","27-05-2025 20:06:10","27-05-2025 20:35=
:25","Grid outage, generator failed to start due to discharged GE battery /=
/ Grid restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Generator Battery","Grid outage, generator failed to start due to d=
ischarged GE battery // Grid restored","loic.noumsi@matech-cameroun.com","4=
29","27-05-2025 20:13:18","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005118495","OBA=
M NGOLA OCM","","27-05-2025 19:38:38","27-05-2025 19:32:31","27-05-2025 20:=
51:14","Grid outage, site went down due to Grid bad voltage and Gen failed =
to start due to card Ge faulty // He reseted it and started Gen manually af=
ter bypassing Grid","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage, site went down due to Grid bad voltag=
e and Gen failed to start due to card Ge faulty // He reseted it and starte=
d Gen manually after bypassing Grid","loic.noumsi@matech-cameroun.com","368=
","27-05-2025 19:38:38","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005118386","N=
YOM 2 IHS","","27-05-2025 19:15:26","27-05-2025 19:10:18","27-05-2025 19:22=
:41","No power issue Ubaie:54.31V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:54.31V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","gaelle.njiofack@matech-cameroun.com","309","27-05-2025 19:15:26","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0005118164","N=
omayos-IHS","","27-05-2025 18:44:35","27-05-2025 18:42:28","27-05-2025 18:5=
0:57","No power issue on site Ubaie  51.7V site on Grid; Site up without in=
tervention","Fanda Brice","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie  51.7V s=
ite on Grid; Site up without intervention","gaelle.njiofack@matech-cameroun=
.com","128","27-05-2025 18:44:35","MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0005118067","M=
beng","IHS_YND_554, IHS_YND_553","27-05-2025 18:33:04","27-05-2025 18:29:00=
","27-05-2025 19:44:23","No power issue, site is on gen with Ubaie =3D 54.6=
V, The Tx FME Etienne 695033981 of huawei is informed.","Fanda Brice","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue, site is on gen with Ubaie =3D 54.6V, The Tx FME Etie=
nne 695033981 of huawei is informed.","loic.noumsi@matech-cameroun.com","24=
6","27-05-2025 18:33:04","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005117883","M=
essassi 2","","27-05-2025 18:04:34","27-05-2025 17:58:26","27-05-2025 18:05=
:35","No power issue Ubaie:54.31V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:54.31V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","gaelle.njiofack@matech-cameroun.com","370","27-05-2025 18:04:34","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0005117743","K=
amajou Building","","27-05-2025 17:44:04","27-05-2025 16:40:13","27-05-2025=
 16:42:05","Backtracking/  site went down due to Malfunction of rectifier /=
/ Site stabilized","Paul BIBOUM","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Backtracking/  site went down due to Malfunction of rect=
ifier // Site stabilized","gaelle.njiofack@matech-cameroun.com","3832","27-=
05-2025 17:44:04","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005117525","MBA=
LNGONG LYCEE","","27-05-2025 16:59:10","27-05-2025 16:50:55","27-05-2025 18=
:27:42","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down be=
cause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informe=
d and confirmed // Grid returned","loic.noumsi@matech-cameroun.com","496","=
27-05-2025 16:59:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0005117492","Ebeba","=
","27-05-2025 16:54:07","27-05-2025 16:43:59","27-05-2025 17:24:57","Cascad=
ed Incident from TTO5259107","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to disjunction of Cb(50A=
) in PWC // He rearmed Cb(50A), site on gen","system","1192980","27-05-2025=
 16:54:07","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005117491","N=
taba","","27-05-2025 16:53:50","27-05-2025 16:46:42","27-05-2025 16:50:15",=
"site went down due to work of  SS IHS Blaise Raoul // End of work.","Delor=
 Telezing","Equipment Replacement","Passive","Planned Activity","Planned Ac=
tivity - Site Inspection","site went down due to work of  SS IHS Blaise Rao=
ul // End of work.","gaelle.njiofack@matech-cameroun.com","429","27-05-2025=
 16:53:50","MATECH CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0005117489","Nke=
ng likok","IHS_YND_339","27-05-2025 16:53:28","27-05-2025 16:43:59","27-05-=
2025 17:24:57","Site went down due to disjunction of Cb(50A) in PWC // He r=
earmed Cb(50A), site on gen","Kemeni Franklin","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Site went down due to disjuncti=
on of Cb(50A) in PWC // He rearmed Cb(50A), site on gen","loic.noumsi@matec=
h-cameroun.com","569","27-05-2025 16:53:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0005117465","Messassi=
 Ngonlonk","","27-05-2025 16:47:55","27-05-2025 16:30:11","27-05-2025 17:40=
:06","Cascaded Incident from TTO5259070 - Cascade Removed From TTO5259070",=
"Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Cascaded Incident from TTO5259070","system","1165427","27-05-2025 16=
:47:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0005117464","Akak-Nko=
zoa-MTN-IHS","","27-05-2025 16:47:54","27-05-2025 16:30:11","27-05-2025 17:=
40:45","Cascaded Incident from TTO5259070 - Cascade Removed From TTO5259070=
","Fabrice Pouakam","Equipment Repair","Passive","Infrastructure","Armoured=
 Cable","Grid outage, site went down because Gen failed to start due to sho=
rt circuit in the generator // cable cut and reconnected to eliminate short=
 circuit and Gen start manually","system","1063","27-05-2025 16:47:54","MAT=
ECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005117436","Aha=
la Echangeur","","27-05-2025 16:41:20","27-05-2025 16:33:49","27-05-2025 18=
:41:26","Grid outage, site went down because Gen failed to start due to GE =
contactor faulty // He blocked GE contactor, Site on Grid","MINKA NICOLAS",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outag=
e, site went down because Gen failed to start due to GE contactor faulty //=
 He blocked GE contactor, Site on Grid","loic.noumsi@matech-cameroun.com","=
452","27-05-2025 16:41:20","MATECH CMR"
"Cancelled","Warning","","IHS_YND_133","NOCINC0005117431","Elig-Edzoa","","=
27-05-2025 16:40:48","","","Cascaded Incident from TTO5259032","","","","",=
"","","system","245","27-05-2025 16:40:48","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005117418","C=
hapelle-Nsimeyong","","27-05-2025 16:40:02","27-05-2025 16:36:43","27-05-20=
25 16:40:36","ticket error","MINKA NICOLAS","Incorrectly Logged Tickets","E=
rror","Error","Error","ticket error","gaelle.njiofack@matech-cameroun.com",=
"200","27-05-2025 16:40:02","MATECH CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0005117414","M=
essassi","IHS_YND_681, IHS_YND_799, IHS_YND_304","27-05-2025 16:39:16","27-=
05-2025 16:30:11","27-05-2025 17:40:06","grid outage, site went down becaus=
e Gen failed to start due to short circuit in the generator // cable cut an=
d reconnected to eliminate short circuit and Gen start manually","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","gri=
d outage, site went down because Gen failed to start due to short circuit i=
n the generator // cable cut and reconnected to eliminate short circuit and=
 Gen start manually","gaelle.njiofack@matech-cameroun.com","546","27-05-202=
5 16:39:16","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005117408","N=
kolondom","","27-05-2025 16:38:35","27-05-2025 16:30:11","27-05-2025 17:34:=
25","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","grid outage, site went down because Gen failed to start due t=
o short circuit in the generator // cable cut and reconnected to eliminate =
short circuit and Gen start manually","gaelle.njiofack@matech-cameroun.com"=
,"1165428","27-05-2025 16:38:35","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005117399","N=
KOLMEKONG YDE","","27-05-2025 16:38:05","27-05-2025 16:30:11","27-05-2025 1=
7:34:25","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","grid outage, site went down because Gen failed to start =
due to short circuit in the generator // cable cut and reconnected to elimi=
nate short circuit and Gen start manually","gaelle.njiofack@matech-cameroun=
.com","1165428","27-05-2025 16:38:05","MATECH CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0005117328","Ako=
no","","27-05-2025 16:30:46","","","Poire faulty // Site stabilised","Fanda=
 Brice","Warning","Warning","DIESEL","Warning - Fuel Line Issue","Poire fau=
lty // site stabilised","loic.noumsi@matech-cameroun.com","2118","27-05-202=
5 16:30:46","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0005117284","N=
kolangaa","","27-05-2025 16:19:48","27-05-2025 16:13:38","27-05-2025 16:42:=
21","site went down due to instalation of DC Box by Njoha mama (690811271/L=
OUMADE ING) Nkolanga // Eend of work","Mba Lazare Herve","Installation Acti=
vity","Passive","Planned Activity","Installation Activity","site went down =
due to instalation of DC Box by Njoha mama (690811271/LOUMADE ING) Nkolanga=
 // Eend of work","gaelle.njiofack@matech-cameroun.com","371","27-05-2025 1=
6:19:48","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005117102","O=
LAMA","","27-05-2025 15:53:44","27-05-2025 15:46:37","27-05-2025 15:58:39",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue.","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX=
 FME Henri (699949693) from Huawei is informed.Noticed that it is a repetit=
ve issue.","gaelle.njiofack@matech-cameroun.com","428","27-05-2025 15:53:44=
","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005116844","B=
arriere","","27-05-2025 15:25:53","27-05-2025 15:23:45","27-05-2025 15:41:4=
6","Grid outage, site went down because the generator has not started due t=
o a malfunction on the generator board. // Reset the generator board and si=
te on generator.","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Grid outage, site went down because the generator h=
as not started due to a malfunction on the generator board. // Reset the ge=
nerator board and site on generator.","gaelle.njiofack@matech-cameroun.com"=
,"129","27-05-2025 15:25:53","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005116716","N=
taba","","27-05-2025 15:06:23","27-05-2025 15:04:14","27-05-2025 15:09:05",=
"	Grid outage, site went down because gen failed to start due to Pwc ZTE dy=
sfunction // Grid return","Delor Telezing","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","	Grid outage, site went down becaus=
e gen failed to start due to Pwc ZTE dysfunction // Grid return","gaelle.nj=
iofack@matech-cameroun.com","131","27-05-2025 15:06:23","MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0005116611","Abo=
me","","27-05-2025 14:53:43","27-05-2025 14:40:31","27-05-2025 17:32:02","S=
ite went down due to disjunction of CB (80A) in PWC // He rearmed CB (80A),=
 site on GRID","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Site went down due to disjunction of CB (80A) i=
n PWC // He rearmed CB (80A), site on GRID","loic.noumsi@matech-cameroun.co=
m","794","27-05-2025 14:53:43","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005116597","Mes=
sassi 2","","27-05-2025 14:51:09","27-05-2025 14:42:02","27-05-2025 14:52:1=
0","No power issue Ubaie:54.31V site on Grid, TX fme symphorien /650257151 =
from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ubai=
e:54.31V site on Grid, TX fme symphorien /650257151 from huawei is informed=
.","loic.noumsi@matech-cameroun.com","549","27-05-2025 14:51:09","MATECH CM=
R"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005116564","Nko=
lnda","","27-05-2025 14:45:23","27-05-2025 14:41:17","27-05-2025 14:53:33",=
"Site went down due to plan of work (Telemetry connection) done by LELE (FM=
E telemetry / 655242229) // End of work","Albran Byorel","Installation Acti=
vity","Passive","Planned Activity","Installation Activity","Site went down =
due to plan of work (Telemetry connection) done by LELE (FME telemetry / 65=
5242229) // End of work","loic.noumsi@matech-cameroun.com","247","27-05-202=
5 14:45:23","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005116521","ODZ=
A MINKAN EDIBI ASSI","","27-05-2025 14:39:48","27-05-2025 14:30:35","27-05-=
2025 15:57:54","Grid outage, site went down due to GE battery faulty // Gri=
d returned","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Generator Faulty","Grid outage, site went down due to GE battery faulty //=
 Grid returned","loic.noumsi@matech-cameroun.com","554","27-05-2025 14:39:4=
8","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005115978","T=
amtam Weekend","","27-05-2025 14:10:25","27-05-2025 14:08:12","27-05-2025 1=
4:10:28","Grid Outage Site went down because Gen Overload (20KVA, 300A) // =
Grid returned","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid Outage Site went down because Gen Overload (20KVA, 300=
A) // Grid returned","vanel.mbiada@matech-cameroun.com","134","27-05-2025 1=
4:10:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005115870","MEHANDAN=
","","27-05-2025 13:58:31","27-05-2025 13:55:00","27-05-2025 14:04:53","Cas=
caded Incident from TTO5257282","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
1174453","27-05-2025 13:58:31","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005115818","O=
dza II OCM","IHS_YND_528","27-05-2025 13:57:12","27-05-2025 13:55:00","27-0=
5-2025 15:20:35","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","vanel.mbiada@matech-cameroun.com","134","27-05-2025 13:57:12",=
"MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005115205","Bar=
riere","","27-05-2025 12:58:32","27-05-2025 12:54:19","27-05-2025 13:54:05"=
,"Grid outage.site went down due to bad grid voltage//We bypass grid and ge=
n manually started ","Hyemafo Gildas","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","Grid outage.site went down due to bad =
grid voltage//We bypass grid and gen manually started ","vanel.mbiada@matec=
h-cameroun.com","254","27-05-2025 12:58:32","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005115016","N=
yom OCM","","27-05-2025 12:31:41","27-05-2025 12:29:31","27-05-2025 13:14:5=
4","Grid outage, Gen failed to start because ATS did not send the start  od=
er // ATS reset and Gen start manually","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","ATS-AMF Issue","Grid outage, Gen failed to sta=
rt because ATS did not send the start  oder // ATS reset and Gen start manu=
ally","vanel.mbiada@matech-cameroun.com","131","27-05-2025 12:31:41","MATEC=
H CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005114900","Mes=
sassi 2","","27-05-2025 12:15:05","27-05-2025 12:09:51","27-05-2025 12:19:0=
1","Grid outage site went down because Gen failed to start due to poor Batt=
ery backup// GEN automatically started","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site=
 went down because Gen failed to start due to poor Battery backup// GEN aut=
omatically started","vanel.mbiada@matech-cameroun.com","315","27-05-2025 12=
:15:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005114896","Messassi=
 okolo","","27-05-2025 12:14:27","27-05-2025 12:10:09","27-05-2025 14:43:50=
","Cascaded Incident from TTO5256271","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, with gen genrator=
 faulty.grid power awaited // Grid return","system","1180494","27-05-2025 1=
2:14:27","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005114892","E=
MANA BILICK CITY","IHS_YND_279","27-05-2025 12:13:24","27-05-2025 12:10:09"=
,"27-05-2025 14:48:39","Grid outage, site went down due to gen faulty // gr=
id power returned","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen=
","ACDG - Generator Faulty","Grid outage, site went down due to gen faulty =
// grid power returned","vanel.mbiada@matech-cameroun.com","197","27-05-202=
5 12:13:24","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005114829","M=
endong vallee","","27-05-2025 11:57:52","27-05-2025 11:54:29","27-05-2025 1=
4:26:52","Grid outage site went down due to Gen overload (20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed and confirmed // he reduced load and put site o=
n Gen (investigation on going)","Fanda Brice","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage site went down due to Gen overloa=
d (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed and confirmed // he reduced=
 load and put site on Gen (investigation on going)","vanel.mbiada@matech-ca=
meroun.com","204","27-05-2025 11:57:52","MATECH CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0005114563","E=
BOM","","27-05-2025 11:17:32","27-05-2025 11:14:20","27-05-2025 11:25:58","=
site went down because Samba huawei technician on site for work // Ent of w=
ork","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","site went down because Samba huawei techn=
ician on site for work // Ent of work","vanel.mbiada@matech-cameroun.com","=
193","27-05-2025 11:17:32","MATECH CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0005114530","Ese=
ka MTN","","27-05-2025 11:11:07","27-05-2025 11:02:49","27-05-2025 11:30:27=
","cascacaded behind TTO5256248","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage .gen started but dit no=
t feeds the site due to gen contactor dysfunctionned//Grid return","vanel.m=
biada@matech-cameroun.com","1178240","27-05-2025 11:11:07","MATECH CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0005114528","Ese=
ka Town","","27-05-2025 11:10:16","27-05-2025 11:02:49","27-05-2025 11:30:2=
7","cascaded behind TTO5256248","Kemeni Franklin","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen started but did not =
feedst the site due to  gen contactor dysfunctionning //Grid return","vanel=
.mbiada@matech-cameroun.com","1178240","27-05-2025 11:10:16","MATECH CMR"
"Closed Complete","Site Down","CTR_286","IHS_YND_381","NOCINC0005114492","B=
oumnyebel","IHS_YND_379, IHS_YND_378","27-05-2025 11:05:01","27-05-2025 11:=
02:49","27-05-2025 11:30:27","Grid outage, Site alarming on battery bacause=
 Gen started but did not feeds the site due to Gen contactor dysfunction// =
Grid return","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","ACD=
G - Load Contactor","Grid outage, Site alarming on battery bacause Gen star=
ted but did not feeds the site due to Gen contactor dysfunction// Grid retu=
rn","vanel.mbiada@matech-cameroun.com","133","27-05-2025 11:05:01","MATECH =
CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0005114140","Don=
g","","27-05-2025 10:02:28","27-05-2025 09:51:59","27-05-2025 14:03:43","Hy=
brid gen site.gen ran until fuel shortage//Refueling done","Parker Tchoup",=
"Fuel Outage","Passive","Diesel","Diesel Outage","Hybrid gen site.gen ran u=
ntil fuel shortage//Refueling done","vanel.mbiada@matech-cameroun.com","630=
","27-05-2025 10:02:28","MATECH CMR"
"Closed Complete","Site Down","T0539","IHS_YND_034","NOCINC0005114129","EMI=
A MTN","","27-05-2025 10:00:04","27-05-2025 09:58:46","28-05-2025 15:42:26"=
,"Grid outage, Site went Down due to No space to deploy // Grid power retur=
ned","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid outage, Site went Down due to No space to deploy // Grid power return=
ed","vanel.mbiada@matech-cameroun.com","79","27-05-2025 10:00:04","MATECH C=
MR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005114032","O=
LAMA","","27-05-2025 09:42:55","27-05-2025 09:38:29","27-05-2025 09:45:24",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue.","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX=
 FME Henri (699949693) from Huawei is informed.Noticed that it is a repetit=
ve issue.","vanel.mbiada@matech-cameroun.com","267","27-05-2025 09:42:55","=
MATECH CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0005113899","P=
olytechnique","","27-05-2025 09:17:38","27-05-2025 09:16:29","28-05-2025 14=
:30:57","Grid outage, Site went Down because No space to deploy//Grid retur=
n","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid outage, Site went Down because No space to deploy//Grid return","vanel.=
mbiada@matech-cameroun.com","70","27-05-2025 09:17:38","MATECH CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0005113632","E=
seka Town","","27-05-2025 08:28:06","27-05-2025 08:23:52","27-05-2025 09:25=
:56","Site went down due to disjunction on PWC//We rearmed the CB and site =
on gen ","Kemeni Franklin","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Circuit Breaker Issue","Site went down due to disjunction on =
PWC//We rearmed the CB and site on gen ","vanel.mbiada@matech-cameroun.com"=
,"256","27-05-2025 08:28:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005113605","MBIMBIM"=
,"","27-05-2025 08:20:24","27-05-2025 08:06:02","27-05-2025 09:29:15","Casc=
aded Incident from TTO5254759","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybride Module faulty. // Manual start =
of Gen.","system","1188641","27-05-2025 08:20:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005113604","Ngouetou=
","","27-05-2025 08:20:24","27-05-2025 08:06:02","27-05-2025 09:29:15","Cas=
caded Incident from TTO5254759","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybride Module faulty. // Manual start=
 of Gen.","system","1188640","27-05-2025 08:20:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005113602","Matsari"=
,"","27-05-2025 08:20:24","27-05-2025 08:06:02","27-05-2025 09:29:15","Casc=
aded Incident from TTO5254759","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybride Module faulty. // Manual start =
of Gen.","system","1188641","27-05-2025 08:20:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005113603","Yoko OCM=
","","27-05-2025 08:20:24","27-05-2025 08:06:02","27-05-2025 09:29:15","Cas=
caded Incident from TTO5254759","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybride Module faulty. // Manual start=
 of Gen.","system","1188642","27-05-2025 08:20:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005113601","Ngoum","=
","27-05-2025 08:20:23","27-05-2025 08:06:02","27-05-2025 09:29:15","Cascad=
ed Incident from TTO5254759","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Hybride Module faulty. // Manual start of=
 Gen.","system","1188640","27-05-2025 08:20:23","MATECH CMR"
"Assigned","Site Down","","IHS_YND_670","NOCINC0005113421","BOBOCK","","27-=
05-2025 07:42:33","27-05-2025 05:05:03","27-05-2025 10:24:15","Cascaded Inc=
ident from TTO5253999","Kemeni Franklin","Cascade Outage","","","","","syst=
em","9450","27-05-2025 07:42:33","MATECH CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0005113410","Bas=
tos Amb Coree","","27-05-2025 07:39:11","27-05-2025 07:38:02","27-05-2025 0=
7:54:38","	Grid outage No space to deploy a mobil Gen//Grid returned","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid out=
age No space to deploy a mobil Gen//Grid returned","vanel.mbiada@matech-cam=
eroun.com","71","27-05-2025 07:39:11","MATECH CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0005113351","Nya=
hoo","IHS_EDA_102","27-05-2025 07:20:59","27-05-2025 05:05:03","27-05-2025 =
10:24:15","Hybrid gen site .gen start and stopped due to low oil pressure /=
/We add oil and gen manually started ","TIENTCHEU NZETCHIEU GAEL","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Hybrid gen site .=
gen start and stopped due to low oil pressure //We add oil and gen manually=
 started ","vanel.mbiada@matech-cameroun.com","14530","27-05-2025 07:20:59"=
,"MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0005113183","Aha=
la Echangeur","","27-05-2025 06:56:15","27-05-2025 06:54:06","27-05-2025 06=
:58:05","Grid outage site went down and gen en failed to start due to poor =
backup//Grid return","MINKA NICOLAS","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage site went down and gen en=
 failed to start due to poor backup//Grid return","vanel.mbiada@matech-came=
roun.com","130","27-05-2025 06:56:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_190","NOCINC0005113167","Ngousso-=
II","","27-05-2025 06:50:41","27-05-2025 06:48:49","27-05-2025 06:51:49","C=
ascaded Incident from TTO5254345","MFOUAGUEGUE MATHIEU","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went Down due to Works, c=
hristian (650631358/Dowen) was on site for swap PWC IPT // end of work","sy=
stem","1193170","27-05-2025 06:50:41","MATECH CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0005113164","N=
kolmesseng","IHS_YND_190","27-05-2025 06:50:03","27-05-2025 06:48:49","27-0=
5-2025 06:51:49","Site went Down due to Work, christian (650631358/Dowen) w=
as on site for swap PWC IPT // end of work","Siligap Boris","Installation A=
ctivity","Passive","Planned Activity","Installation Activity","Site went Do=
wn due to Works, christian (650631358/Dowen) was on site for swap PWC IPT /=
/ end of work","vanel.mbiada@matech-cameroun.com","74","27-05-2025 06:50:03=
","MATECH CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0005113045","E=
lobi Mokolo","","27-05-2025 06:18:55","27-05-2025 06:06:59","27-05-2025 06:=
43:25","Active//No power issue on site, site on Grid with U=3D53,2 V The TX=
 FME Brice (650214096) from huawei is informed.","Mboua Thierry","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site, site on Grid with U=3D53,2 V The TX FME B=
rice (650214096) from huawei is informed.","edwige.kapawo@matech-cameroun.c=
om","717","27-05-2025 06:18:55","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0005113019","B=
riqueterie","","27-05-2025 06:08:28","27-05-2025 06:06:14","27-05-2025 07:3=
6:04","Grid Only, No space to deploy MGE //  Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid only site, no sp=
ace to deploy MDGE (awaiting Grid) // Grid return","edwige.kapawo@matech-ca=
meroun.com","135","27-05-2025 06:08:28","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005113018","Mok=
olo Yaounde","","27-05-2025 06:08:18","27-05-2025 06:02:05","27-05-2025 07:=
24:05","Active // No power issue Ubay: 54.4 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.4 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","3=
74","27-05-2025 06:08:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0005113012","Mamch Bu=
ilding","","27-05-2025 06:04:41","27-05-2025 06:02:47","27-05-2025 07:51:50=
","Cascaded Incident from TTO5254167","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid Only, No space to Deploy MD=
G//Grid return","system","1195897","27-05-2025 06:04:41","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0005113009","C=
harles-Atangana","IHS_YND_051","27-05-2025 06:03:55","27-05-2025 06:02:47",=
"27-05-2025 07:59:40","Grid Only, No space to Deploy MDG//Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Onl=
y, No space to Deploy MDG//Grid return","edwige.kapawo@matech-cameroun.com"=
,"69","27-05-2025 06:03:55","MATECH CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0005113006","Bri=
quetterie","","27-05-2025 06:00:58","27-05-2025 05:51:47","27-05-2025 07:38=
:16","Grid outage, no space to deploy a mobile gen//Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, n=
o space to deploy a mobile gen//Grid return","gerard.tchangoue@matech-camer=
oun.com","552","27-05-2025 06:00:58","MATECH CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0005112959","N=
gousso-II","","27-05-2025 05:44:11","26-05-2025 20:04:10","27-05-2025 06:40=
:10","(Bactracking) No power issue site on grid with U=3D53,1v, Armand ngue=
tsa/691144412 from Huawei is informed","MFOUAGUEGUE MATHIEU","Customer Equi=
pment Failure","Active","Active Equipment Failure","Affected by 3rd Party S=
ite","(Bactracking) No power issue site on grid with U=3D53,1v, Armand ngue=
tsa/691144412 from Huawei is informed","gerard.tchangoue@matech-cameroun.co=
m","34802","27-05-2025 05:44:11","MATECH CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0005112859","NYA=
NON/DEMBO","","27-05-2025 05:08:20","27-05-2025 05:05:03","27-05-2025 10:24=
:15","FME Gael is on site","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Hybrid gen site .gen start and s=
topped due to low oil pressure //We add oil and gen manually started","gera=
rd.tchangoue@matech-cameroun.com","1199455","27-05-2025 05:08:20","MATECH C=
MR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005112788","Ron=
d Point Express1114","","27-05-2025 04:28:54","27-05-2025 04:19:45","27-05-=
2025 04:33:10","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","ge=
rard.tchangoue@matech-cameroun.com","550","27-05-2025 04:28:54","MATECH CMR=
"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005112573","Ron=
d Point Express1114","","27-05-2025 03:13:27","27-05-2025 03:06:07","27-05-=
2025 03:12:09","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","ge=
rard.tchangoue@matech-cameroun.com","441","27-05-2025 03:13:27","MATECH CMR=
"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0005112342","N=
kolmesseng","","27-05-2025 02:26:30","27-05-2025 02:16:57","27-05-2025 02:4=
5:41","Site went Down due to Works, christian  (650631358/Dowen) was on sit=
e for swap PWC IPT // end of works","Siligap Boris","Equipment Replacement"=
,"Passive","Planned Activity","Planned Activity - Passive","Site went Down =
due to Works, christian  (650631358/Dowen) was on site for swap PWC IPT // =
end of works","edwige.kapawo@matech-cameroun.com","574","27-05-2025 02:26:3=
0","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005112266","SAA=
 Entrance","","27-05-2025 01:55:37","27-05-2025 01:54:27","27-05-2025 01:56=
:53","Grid outage, site went down due to Grid bad voltage // GRID RETURN","=
Parker Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid outage, site went down due to Grid bad voltage // GRID R=
ETURN","gerard.tchangoue@matech-cameroun.com","71","27-05-2025 01:55:37","M=
ATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005112240","Nko=
l-Mebanga","","27-05-2025 01:44:03","27-05-2025 01:34:45","28-05-2025 10:32=
:39","Solar only, Site went Down due to low Solar // Solar returned","Parke=
r Tchoup","Equipment Repair","Passive","Solar","Solar Panel Issue","Solar o=
nly, Site went Down due to low Solar // Solar returned","gerard.tchangoue@m=
atech-cameroun.com","559","27-05-2025 01:44:03","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005112128","Mok=
olo Yaounde","","27-05-2025 00:56:15","27-05-2025 00:48:01","27-05-2025 00:=
57:26","Active // No power issue Ubay: 54.4 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.4 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","4=
95","27-05-2025 00:56:15","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005111693","M=
essassi 2","","26-05-2025 23:00:48","26-05-2025 22:57:34","26-05-2025 23:00=
:38","	Grid outage site went down because Gen failed to start due to poor B=
attery backup// GEN automatically started","Fabrice Pouakam","Equipment Rep=
air","Passive","ACDG Gen","DG Low Battery","	Grid outage site went down bec=
ause Gen failed to start due to poor Battery backup// GEN automatically sta=
rted","edwige.kapawo@matech-cameroun.com","196","26-05-2025 23:00:48","MATE=
CH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0005111657","Sca=
lom","","26-05-2025 22:50:31","26-05-2025 22:48:20","26-05-2025 23:16:42","=
Grid Outage, site went down before gen start due to poor battery backup // =
Grid return","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid Outage, site went down before gen start du=
e to poor battery backup // Grid return","franck.nkomot@matech-cameroun.com=
","132","26-05-2025 22:50:31","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005111644","B=
arriere","","26-05-2025 22:48:50","26-05-2025 22:46:35","26-05-2025 23:39:3=
0","No power issue on site Ubay: 54.6V site on Gen TX Fme SAMBA (654266058/=
Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
bay: 54.6V site on Gen TX Fme SAMBA (654266058/Huawei) is informed.","chris=
telle.ngonga@matech-cameroun.com","137","26-05-2025 22:48:50","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005111639","Ako=
k Ndoe Yde","","26-05-2025 22:47:20","26-05-2025 22:43:09","26-05-2025 23:4=
5:22","Site went down due to Cb(80A) in PWC malfunction // He reamed Cb(80A=
) , site on grid","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Circuit Breaker Issue","Site went down due to Cb(80A)=
 in PWC malfunction // He reamed Cb(80A) , site on grid","franck.nkomot@mat=
ech-cameroun.com","252","26-05-2025 22:47:20","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005111633","M=
essassi okolo","","26-05-2025 22:45:51","26-05-2025 22:40:56","26-05-2025 2=
3:03:31","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site down because site behaves as Grid only=
 site ( Gen Noise) //Grid return","christelle.ngonga@matech-cameroun.com","=
1228270","26-05-2025 22:45:51","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005111630","E=
MANA BILICK CITY","IHS_YND_279","26-05-2025 22:45:04","26-05-2025 22:40:56"=
,"26-05-2025 23:03:31","Grid outage, site down because site behaves as Grid=
 only site ( Gen Noise) //Grid return","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, site down be=
cause site behaves as Grid only site ( Gen Noise) //Grid return","christell=
e.ngonga@matech-cameroun.com","250","26-05-2025 22:45:04","MATECH CMR"
"Closed Complete","Site Down","CTR_356","IHS_YND_376","NOCINC0005111349","M=
amb","","26-05-2025 21:53:42","26-05-2025 21:47:30","26-05-2025 23:32:52","=
Grid outage, site went down because gen failed to start due to grid contact=
or faulty // He bypassed ATS and Gen manually started","Kemeni Franklin","E=
quipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, si=
te went down because gen failed to start due to grid contactor faulty // He=
 bypassed ATS and Gen manually started","christelle.ngonga@matech-cameroun.=
com","764","26-05-2025 21:53:42","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005111326","Eto=
ug ebe Carrefour","","26-05-2025 21:50:29","26-05-2025 21:47:22","27-05-202=
5 00:21:10","Site went down because gen fails to start due to grid bad volt=
age // Grid return","Hyemafo Gildas","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","Site went down because gen fails to sta=
rt due to grid bad voltage // Grid return","franck.nkomot@matech-cameroun.c=
om","188","26-05-2025 21:50:29","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005111296","TSI=
NGA VILLAGE 2","","26-05-2025 21:44:11","26-05-2025 21:31:01","27-05-2025 0=
0:30:41","Active//No power issue on site, Site on Battery UBAIE=3D54.5V syn=
phorien (675295205) From huawei is informed","Delor Telezing","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site, Site on Battery UBAIE=3D54.5V synphorien (67=
5295205) From huawei is informed","franck.nkomot@matech-cameroun.com","791"=
,"26-05-2025 21:44:11","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0005111270","S=
calom","IHS_YND_505","26-05-2025 21:40:59","26-05-2025 21:37:47","26-05-202=
5 22:15:47","Grid Outage, site down before gen start due to poor battery ba=
ckup","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Battery Low","Grid Outage, site went down before gen start due to po=
or battery backup // Grid return","christelle.ngonga@matech-cameroun.com","=
193","26-05-2025 21:40:59","MATECH CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0005111267","S=
calom-IHS","","26-05-2025 21:40:13","26-05-2025 21:37:47","26-05-2025 22:07=
:47","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid Outage, site went down before gen start due to poor battery backup // =
Grid return","christelle.ngonga@matech-cameroun.com","1225797","26-05-2025 =
21:40:13","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005110744","Eto=
ug ebe Carrefour","","26-05-2025 20:19:19","26-05-2025 20:09:12","26-05-202=
5 20:26:12","Grid outage, site went down before gen start due to poor batte=
ry backup // gen start automatically","Hyemafo Gildas","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup // gen start automatic=
ally","franck.nkomot@matech-cameroun.com","608","26-05-2025 20:19:19","MATE=
CH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0005110739","Com=
plex Beac II","","26-05-2025 20:18:36","26-05-2025 20:10:26","26-05-2025 21=
:12:26","Grid outage .gen failed to start due to automation malfunctionning=
//Gen manually started (investigation ongoing)","Albran Byorel","Equipment =
Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage .gen failed =
to start due to automation malfunctionning//Gen manually started (investiga=
tion ongoing)","franck.nkomot@matech-cameroun.com","491","26-05-2025 20:18:=
36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005110138","Elig-Edz=
oa","","26-05-2025 19:05:48","26-05-2025 19:00:11","26-05-2025 22:02:07","C=
ascaded Incident from TTO5251013","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen failed to=
 start due to Pwc ZTE dysfunction // He bypassed ATS and started Gen manual=
ly","system","1241207","26-05-2025 19:05:48","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005110134","N=
taba","IHS_YND_133","26-05-2025 19:04:41","26-05-2025 19:00:11","26-05-2025=
 22:06:33","Grid outage, site went down because gen failed to start due to =
Pwc ZTE dysfunction // He bypassed ATS and started Gen manually","Delor Tel=
ezing","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid o=
utage, site went down because gen failed to start due to Pwc ZTE dysfunctio=
n // He bypassed ATS and started Gen manually","christelle.ngonga@matech-ca=
meroun.com","271","26-05-2025 19:04:41","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005110061","E=
ssomba","","26-05-2025 18:49:11","26-05-2025 18:46:04","26-05-2025 21:36:04=
","Site went down because 03/06 rectifiers dysfunctionned //Site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down because 03/06 rectifiers dysfunctionned //Site stabil=
ised","christelle.ngonga@matech-cameroun.com","189","26-05-2025 18:49:11","=
MATECH CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0005110048","N=
kolmesseng","","26-05-2025 18:45:43","26-05-2025 18:44:23","26-05-2025 18:4=
7:06"," No Power issue on site ,site on Grid with Ubaie=3D52,3 VThe Tx FME =
RM TX Martial 650252214// From Huawei is informed","Siligap Boris","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m"," No Power issue on site ,site on Grid with Ubaie=3D52,3 VThe Tx FME RM =
TX Martial 650252214// From Huawei is informed","christelle.ngonga@matech-c=
ameroun.com","81","26-05-2025 18:45:43","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005109718","M=
essassi 2","","26-05-2025 17:44:47","26-05-2025 17:42:36","26-05-2025 18:02=
:42","No power issue Ubaie:54.18V site on Grid, TX fme symphorien /65025715=
1 from huawei is informed.","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ub=
aie:54.18V site on Grid, TX fme symphorien /650257151 from huawei is inform=
ed.","christelle.ngonga@matech-cameroun.com","133","26-05-2025 17:44:47","M=
ATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005109577","Ron=
d Point Express1114","","26-05-2025 17:16:27","26-05-2025 17:08:16","26-05-=
2025 17:26:16","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","fr=
anck.nkomot@matech-cameroun.com","493","26-05-2025 17:16:27","MATECH CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0005109537","N=
sam Sofavinc T0","","26-05-2025 17:08:23","26-05-2025 17:06:17","26-05-2025=
 17:22:27","Site went down due to malfunction of PWC ZTE // PWC reset ,Grid=
 restoration","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Site went down due to malfunction of PWC ZTE // =
PWC reset ,Grid restoration","christelle.ngonga@matech-cameroun.com","127",=
"26-05-2025 17:08:23","MATECH CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0005109406","E=
lig-Essono","","26-05-2025 16:49:40","26-05-2025 16:46:28","26-05-2025 16:5=
3:06","Site down due to work  (Swap of bay ) done by Loumade Fme  Djoya Mam=
a 693451477 // End of work","Paul BIBOUM","Customer Equipment Failure","Act=
ive","Planned Activity","Planned Activity - Active","Site down due to work =
 (Swap of bay ) done by Loumade Fme  Djoya Mama 693451477 // End of work","=
christelle.ngonga@matech-cameroun.com","193","26-05-2025 16:49:40","MATECH =
CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0005109335","M=
bedoumou - Ekali","","26-05-2025 16:35:01","26-05-2025 16:32:45","26-05-202=
5 19:43:45","Grid outage, Site went down because gen start and stoppen with=
 alarm low oil pressure // He added oil pressure and gen manually started",=
"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pre=
ssure","Grid outage, Site went down because gen start and stoppen with alar=
m low oil pressure // He added oil pressure and gen manually started","chri=
stelle.ngonga@matech-cameroun.com","330","26-05-2025 16:35:01","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005109205","SAA=
 Entrance","","26-05-2025 16:08:10","26-05-2025 08:40:54","26-05-2025 09:13=
:09","Grid outage, site went down due to Grid bad voltage // GRID RETURN(ba=
ctracking)","Parker Tchoup","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Grid outage, site went down due to Grid bad volt=
age // GRID RETURN(bactracking)","mouliom.anselme@matech-cameroun.com","268=
38","26-05-2025 16:08:10","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0005109050","Men=
dong vallee","","26-05-2025 15:55:19","26-05-2025 15:49:58","26-05-2025 20:=
17:58","Grid outage site went down due to Gen overload (20KVA; 300A) IHS F=
=E9lix Zamb=E9 is informed and confirmed //  he reduced load and put site o=
n Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overlo=
ad","Grid outage site went down due to Gen overload (20KVA; 300A) IHS F=E9l=
ix Zamb=E9 is informed and confirmed //  he reduced load and put site on Ge=
n","franck.nkomot@matech-cameroun.com","322","26-05-2025 15:55:19","MATECH =
CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005109034","Sof=
avinc","","26-05-2025 15:53:35","26-05-2025 15:50:22","26-05-2025 16:31:22"=
,"Site went down because rectifiers disfunctionning// Site stabilized","MIN=
KA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down because rectifiers disfunctionning// Site stabilized","franck.=
nkomot@matech-cameroun.com","213","26-05-2025 15:53:35","MATECH CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0005109018","N=
sam Sofavinc T0","","26-05-2025 15:50:57","26-05-2025 15:49:49","26-05-2025=
 16:12:46","Site went down due to malfunction of PWC ZTE // PWC reset ,Grid=
 restoration","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Site went down due to malfunction of PWC ZTE // =
PWC reset ,Grid restoration","christelle.ngonga@matech-cameroun.com","69","=
26-05-2025 15:50:57","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0005109013","K=
oweit City","","26-05-2025 15:50:23","26-05-2025 15:47:16","26-05-2025 15:5=
2:12","Grid outage, site went down because gen failed to start with alarm u=
ndervoltage // He reseted gen card and gen manually started","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge, site went down because gen failed to start with alarm undervoltage // H=
e reseted gen card and gen manually started","christelle.ngonga@matech-came=
roun.com","188","26-05-2025 15:50:23","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005108894","OBA=
M NGOLA OCM","","26-05-2025 15:32:50","26-05-2025 15:31:43","26-05-2025 23:=
13:58","(Unstable) Grid outage, Site down because Gen failed to start due t=
o PWC dysfunctioning. FME Nicolas is informed an manages","MINKA NICOLAS","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage, Site went down because Gen failed to start due to PWC dysfunctioni=
ng// He reset PWC, Site on Grid","franck.nkomot@matech-cameroun.com","68","=
26-05-2025 15:32:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005108890","Carrefou=
r Ayissi Ele","","26-05-2025 15:32:08","26-05-2025 14:56:57","26-05-2025 15=
:32:57","Cascaded Incident from TTO5249458","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage gen failed to =
start due to sol=E9no=EFd valve rails y//Gen manually started","system","12=
43163","26-05-2025 15:32:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005108891","Nkol-Meb=
anga","","26-05-2025 15:32:08","26-05-2025 14:56:57","26-05-2025 15:32:57",=
"Cascaded Incident from TTO5249458","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage gen failed to start du=
e to sol=E9no=EFd valve rails y//Gen manually started","system","1243163","=
26-05-2025 15:32:08","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005108872","Men=
dong3","","26-05-2025 15:28:44","26-05-2025 15:24:21","26-05-2025 15:52:21"=
,"Grid Outage No space to deploy a MDG //Grid Restored","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid Outage No space to=
 deploy a MDG //Grid Restored","franck.nkomot@matech-cameroun.com","264","2=
6-05-2025 15:28:44","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005108852","N=
omayos montee Meche","","26-05-2025 15:25:34","26-05-2025 15:22:14","26-05-=
2025 15:52:34","Grid outage site went down before Gen started due to poor b=
attery back up // Eneo return","Fanda Brice","Equipment Repair","Passive","=
ACDG Gen","DG Low Battery","Grid outage site went down before Gen started d=
ue to poor battery back up // Eneo return","christelle.ngonga@matech-camero=
un.com","201","26-05-2025 15:25:34","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005108843","S=
IMBOCK BONAMBAPE","","26-05-2025 15:24:42","26-05-2025 15:22:32","26-05-202=
5 15:52:32","Grid outage, site went down due to Gen Overload (20kva, 350A) =
SS IHS Felix ZAMBE confirmed // Site stabilisation","Hyemafo Gildas","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went=
 down due to Gen Overload (20kva, 350A) SS IHS Felix ZAMBE confirmed // Sit=
e stabilisation","christelle.ngonga@matech-cameroun.com","131","26-05-2025 =
15:24:42","MATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0005108838","S=
ofavinc","","26-05-2025 15:23:48","26-05-2025 15:22:39","26-05-2025 15:28:3=
9","Site went down because rectifiers disfunctionning// Site stabilized","M=
INKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down because rectifiers disfunctionning// Site stabilized","chris=
telle.ngonga@matech-cameroun.com","70","26-05-2025 15:23:48","MATECH CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0005108726","B=
otmakak","","26-05-2025 14:59:50","26-05-2025 14:51:43","26-05-2025 15:05:3=
8","No power issue site on grid with U=3D53.8vv Notice that site is mpacted=
 by Sombo who is not our responsability","Kemeni Franklin","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue site on grid with U=3D53.8vv Notice that site is mpacted by Somb=
o who is not our responsability","christelle.ngonga@matech-cameroun.com","4=
87","26-05-2025 14:59:50","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005108717","S=
aa","IHS_YND_810, IHS_YND_809","26-05-2025 14:59:09","26-05-2025 14:52:57",=
"26-05-2025 17:15:57","Grid outage gen failed to start due to sol=E9no=EFd =
valve rails y//Gen manually started","Parker Tchoup","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Solenoid Coil","Grid outage gen failed to start d=
ue to sol=E9no=EFd valve rails y//Gen manually started","christelle.ngonga@=
matech-cameroun.com","373","26-05-2025 14:59:09","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005108714","T=
alla Monatele","","26-05-2025 14:58:13","26-05-2025 14:28:43","26-05-2025 1=
5:34:52","No power issue, site is on grid with Ubaie=3D54.9V, Gregoir (6545=
47479) from Huawei is informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue,=
 site is on grid with Ubaie=3D54.9V, Gregoir (654547479) from Huawei is inf=
ormed","christelle.ngonga@matech-cameroun.com","1771","26-05-2025 14:58:13"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0005108707","M=
beng","","26-05-2025 14:56:33","26-05-2025 14:15:24","26-05-2025 15:21:27",=
"No power issue, site is on gen with Ubaie =3D 54.6V, The Tx FME Etienne 69=
5033981 of huawei is informed.","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, s=
ite is on gen with Ubaie =3D 54.6V, The Tx FME Etienne 695033981 of huawei =
is informed.","christelle.ngonga@matech-cameroun.com","2470","26-05-2025 14=
:56:33","MATECH CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0005108705","Nko=
ngtock","","26-05-2025 14:56:17","26-05-2025 14:39:44","26-05-2025 15:57:44=
","Active: No power issue on site Ubaie=3D48,7V site on Gen The Tx FME Etie=
nne//695033981 from Huawei is informed","Kemeni Franklin","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue on site Ubaie=3D48,7V site on Gen The Tx FME Etienne//695=
033981 from Huawei is informed","franck.nkomot@matech-cameroun.com","994","=
26-05-2025 14:56:17","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005108676","Nko=
g-Edzen","","26-05-2025 14:53:25","26-05-2025 14:48:04","26-05-2025 14:59:0=
4","Active//No power issue on site, Site on Grid Ubay =3D 52.1V The Tx Fme =
Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Grid Ubay =3D 52.1V The Tx Fme Greg=
oire (654547479) from Huawei is informed.","franck.nkomot@matech-cameroun.c=
om","322","26-05-2025 14:53:25","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005108612","Bar=
riere","","26-05-2025 14:46:18","26-05-2025 14:20:09","26-05-2025 18:12:54"=
,"Grid outage, Site went down because Gen ran until fuel shortage// Refueli=
ng Done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, Site went down because Gen ran until fuel shortage// Refuelin=
g Done","franck.nkomot@matech-cameroun.com","1570","26-05-2025 14:46:18","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0005108453","L=
obo OCM","","26-05-2025 14:18:27","26-05-2025 14:12:20","26-05-2025 14:28:4=
4","	Grid outage,site went down due to Gen  Poor Batteries Backup // DG sta=
rted automatically.","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","ACDG Gen","DG Low Battery","	Grid outage,site went down due to Gen  Poor=
 Batteries Backup // DG started automatically.","loic.noumsi@matech-camerou=
n.com","367","26-05-2025 14:18:27","MATECH CMR"
"Closed Complete","Warning","T0211","IHS_YND_393","NOCINC0005108394","Ezeza=
ng","","26-05-2025 14:05:32","","","grid bad voltage,no rcp on site// He by=
passe the Grid and site on Gen","Parker Tchoup","Warning","Warning","POWER"=
,"Warning - Site on Battery","grid bad voltage,no rcp on site// He bypasse =
the Grid and site on Gen","loic.noumsi@matech-cameroun.com","729","26-05-20=
25 14:05:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005108375","Eto koss=
 Yde","","26-05-2025 14:03:10","26-05-2025 13:54:06","26-05-2025 14:02:14",=
"Cascaded Incident from TTO5249054","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","system","1246857=
","26-05-2025 14:03:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005108376","ELOUMDEM=
 CARRIERE 2","","26-05-2025 14:03:10","26-05-2025 13:54:06","26-05-2025 14:=
02:14","Cascaded Incident from TTO5249054","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","system","=
1246858","26-05-2025 14:03:10","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005108373","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","26-05-2025 14:01:54","26-05-2025 13:54=
:06","26-05-2025 14:02:14","Grid outage, Site went down before Gen start du=
e to poor backup // Gen started automatically","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","loic.noumsi@matech-cameroun.com","470","26-05-2025 14:01:54","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0005108297","B=
ISCUITERIE","","26-05-2025 13:47:28","26-05-2025 13:42:21","26-05-2025 13:4=
8:48","No power issue, site is on Grid with Ubaie=3D51.8 V The TX FME Mbah =
Hosiah (674007438) from Huawei is informed and up at 01:48 PM.","Paul BIBOU=
M","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue, site is on Grid with Ubaie=3D51.8 V The TX F=
ME Mbah Hosiah (674007438) from Huawei is informed and up at 01:48 PM.","ga=
elle.njiofack@matech-cameroun.com","308","26-05-2025 13:47:28","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0005108294","O=
bili Carrefour","","26-05-2025 13:46:50","26-05-2025 13:42:44","26-05-2025 =
13:48:35","	Grid fluctuation, site went down because Gen started and stoppe=
d due to Grid bad voltage// Grid stabilized","Paul BIBOUM","Grid Supply","P=
assive","Grid","National Grid - Unstable Grid Supply Issue","	Grid fluctuat=
ion, site went down because Gen started and stopped due to Grid bad voltage=
// Grid stabilized","gaelle.njiofack@matech-cameroun.com","247","26-05-2025=
 13:46:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0005108292","Scalom-I=
HS","","26-05-2025 13:46:41","26-05-2025 13:43:11","26-05-2025 13:51:55","C=
ascaded Incident from TTO5248958","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid Outage, site went down before gen start due =
to poor battery backup // Grid return","system","1247491","26-05-2025 13:46=
:41","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0005108283","Sca=
lom","IHS_YND_505","26-05-2025 13:45:23","26-05-2025 13:43:11","26-05-2025 =
13:53:37","Grid Outage, site went down before gen start due to poor battery=
 backup // Grid return","Paul BIBOUM","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid Outage, site went down before g=
en start due to poor battery backup // Grid return","loic.noumsi@matech-cam=
eroun.com","133","26-05-2025 13:45:23","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005108025","B=
arriere","","26-05-2025 13:00:48","26-05-2025 12:59:18","26-05-2025 13:24:4=
1","Site went down due to Plan work (test connection) done by MATECH (Fme G=
ildas 656040578) // End of work","Hyemafo Gildas","Installation Activity","=
Passive","Planned Activity","Installation Activity","Site went down due to =
Plan work (test connection) done by MATECH (Fme Gildas 656040578) // End of=
 work","gaelle.njiofack@matech-cameroun.com","92","26-05-2025 13:00:48","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0005107876","N=
kolondom","","26-05-2025 12:34:42","26-05-2025 12:32:35","26-05-2025 12:59:=
18","Grid outage, Site went down because Gen failed to start due to battery=
 Gen Faulty// He started Gen with external battery","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage,=
 Site went down because Gen failed to start due to battery Gen Faulty// He =
started Gen with external battery","gaelle.njiofack@matech-cameroun.com","1=
28","26-05-2025 12:34:42","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005107834","N=
gouetou","","26-05-2025 12:23:12","26-05-2025 12:20:33","26-05-2025 12:25:0=
4","	No power issue site on Gen, with Ubay=3D52.4V. The Tx Fme Gregoire (65=
4547479) from Huawei is informed","Parker Tchoup","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e site on Gen, with Ubay=3D51.9V. The Tx Fme Gregoire (654547479) from Huaw=
ei is informed","loic.noumsi@matech-cameroun.com","160","26-05-2025 12:23:1=
2","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005107820","Carrefou=
r Ayissi Ele","","26-05-2025 12:21:48","26-05-2025 12:15:41","26-05-2025 12=
:54:42","Cascaded Incident from TTO5248419","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n because Gen start and stopped with ""High temp"" alarm // He added water =
in the radiator, site on Gen","system","1258481","26-05-2025 12:21:48","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005107821","Nkol-Meb=
anga","","26-05-2025 12:21:48","26-05-2025 12:15:41","26-05-2025 12:54:42",=
"Cascaded Incident from TTO5248419","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen start and stopped with ""High temp"" alarm // He added water in the r=
adiator, site on Gen","system","1258480","26-05-2025 12:21:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0005107805","Ngoung",=
"","26-05-2025 12:20:30","26-05-2025 11:13:41","26-05-2025 12:00:51","Casca=
ded Incident from TTO5247984","Kemeni Franklin","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// No power issue, Site on grid Uba=
=3D No com","system","1256265","26-05-2025 12:20:30","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005107800","S=
aa","IHS_YND_810, IHS_YND_809","26-05-2025 12:19:59","26-05-2025 12:15:41",=
"26-05-2025 12:54:42","Grid outage, Site went down because Gen start and st=
opped with ""High temp"" alarm // He added water in the radiator, site on G=
en","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High En=
gine Temp - Coolant Level Issue","Grid outage, Site went down because Gen s=
tart and stopped with ""High temp"" alarm // He added water in the radiator=
, site on Gen","gaelle.njiofack@matech-cameroun.com","260","26-05-2025 12:1=
9:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0005107793","Boumnyeb=
el","","26-05-2025 12:18:30","26-05-2025 11:13:41","26-05-2025 12:00:51","C=
ascaded Incident from TTO5247984","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active// No power issue, Site on grid=
 Uba=3D No com","system","1256265","26-05-2025 12:18:30","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005107697","E=
vodoula OCM","","26-05-2025 12:04:43","26-05-2025 12:02:34","26-05-2025 12:=
17:54","Grid outage, site went down because gen failed to start due to batt=
ery gen faulty // Gen manually started with external battery","TIENTCHEU NZ=
ETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Bat=
tery","Grid outage, site went down because gen failed to start due to batte=
ry gen faulty // Gen manually with external battery","gaelle.njiofack@matec=
h-cameroun.com","130","26-05-2025 12:04:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0005107691","Mamb",""=
,"26-05-2025 12:03:37","26-05-2025 11:13:41","26-05-2025 12:00:41","Active/=
/ No power issue, Site on Grid Ubaie: 53.7 V, The FME Tx Etienne/695033981 =
From Huawei is informed.","Kemeni Franklin","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power i=
ssue, Site on Grid Ubaie: 53.7 V, The FME Tx Etienne/695033981 From Huawei =
is informed.","system","2996","26-05-2025 12:03:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005107489","MEHANDAN=
","","26-05-2025 11:41:10","26-05-2025 11:37:21","26-05-2025 11:47:13","Cas=
caded Incident from TTO5248060","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to PWC ZTE malfunction // Site stabilised","system",=
"1254873","26-05-2025 11:41:11","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005107484","O=
dza II OCM","IHS_YND_528","26-05-2025 11:40:31","26-05-2025 11:37:21","26-0=
5-2025 11:47:13","	Grid outage, site went down because gen failed to start =
due to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","	Grid outage, s=
ite went down because gen failed to start due to PWC ZTE malfunction // Sit=
e stabilised","gaelle.njiofack@matech-cameroun.com","192","26-05-2025 11:40=
:31","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005106439","O=
LAMA","","26-05-2025 08:45:45","26-05-2025 08:36:37","26-05-2025 09:56:20",=
"Grid outage, site went down due to grid bad voltage on site // He bypassed=
 Grid and started Gen manually","Fanda Brice","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid outage, site went down du=
e to grid bad voltage on site // He bypassed Grid and started Gen manually"=
,"loic.noumsi@matech-cameroun.com","550","26-05-2025 08:45:45","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005106099","O=
LAMA","","26-05-2025 07:17:07","26-05-2025 07:15:00","26-05-2025 08:36:00",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue.","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX=
 FME Henri (699949693) from Huawei is informed.Noticed that it is a repetit=
ve issue.","gaelle.njiofack@matech-cameroun.com","128","26-05-2025 07:17:07=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005106094","Elig-Edz=
oa","","26-05-2025 07:16:35","26-05-2025 07:10:53","26-05-2025 10:10:58","C=
ascaded Incident from TTO5246526","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen failed to=
 start due to Pwc ZTE dysfunction // He bypassed ATS and started Gen manual=
ly","system","1270527","26-05-2025 07:16:35","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005106084","N=
taba","IHS_YND_133","26-05-2025 07:14:59","26-05-2025 07:10:53","26-05-2025=
 10:15:35","Grid outage, site went down because gen failed to start due to =
Pwc ZTE dysfunction // He bypassed ATS and started Gen manually","Delor Tel=
ezing","Equipment Repair","Passive","Rectifier","Rectifier Module Overloade=
d","Grid outage, site went down because gen failed to start due to Pwc ZTE =
dysfunction // He bypassed ATS and started Gen manually","loic.noumsi@matec=
h-cameroun.com","248","26-05-2025 07:14:59","MATECH CMR"
"Closed Complete","Warning","T0105","IHS_YND_321","NOCINC0005105971","Soa",=
"","26-05-2025 06:35:24","","","No power issue on site, Ubay =3D 54V (Telem=
etry issue)","Siligap Boris","Warning","Warning","SYSTEM","Warning - Commun=
ication Failure","No power issue on site, Ubay =3D 54V (Telemetry issue)","=
loic.noumsi@matech-cameroun.com","1936","26-05-2025 06:35:24","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005105939","Nko=
l-Mebanga","","26-05-2025 06:28:45","26-05-2025 06:20:36","26-05-2025 09:49=
:49","Solar only site, Site went Down due to low Solar// Solar returned","P=
arker Tchoup","Equipment Repair","Passive","Solar","Solar Panel Issue","Sol=
ar only site, Site went Down due to low Solar// Solar returned","loic.noums=
i@matech-cameroun.com","489","26-05-2025 06:28:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0005105807","Yona Hot=
el","","26-05-2025 05:58:17","26-05-2025 05:50:37","26-05-2025 06:43:29","C=
ascaded Incident from TTO5246172","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went do=
wn because gen failed to start due to low oil pressure // He added oil, res=
eted and started Gen manually","system","1275266","26-05-2025 05:58:17","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0005105808","Dagobert=
","","26-05-2025 05:58:17","26-05-2025 05:50:37","26-05-2025 06:43:29","Cas=
caded Incident from TTO5246172","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down=
 because gen failed to start due to low oil pressure // He added oil, reset=
ed and started Gen manually","system","1275266","26-05-2025 05:58:17","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005105771","N=
kolbi-Boss","IHS_YND_271, IHS_YND_286","26-05-2025 05:54:45","26-05-2025 05=
:50:37","26-05-2025 06:50:40","Grid outage, Site went down because gen fail=
ed to start due to low oil pressure // He added oil, reseted and started Ge=
n manually","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG G=
en","ACDG - Low Oil Pressure","Grid outage, Site went down because gen fail=
ed to start due to low oil pressure // He added oil, reseted and started Ge=
n manually","edwige.kapawo@matech-cameroun.com","249","26-05-2025 05:54:45"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0005105731","O=
ssombe","","26-05-2025 05:38:24","26-05-2025 05:31:16","26-05-2025 09:14:32=
","site went down because gen ran until fuel shortage // refuelling done","=
Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","site went =
down because gen ran until fuel shortage // refuelling done","edwige.kapawo=
@matech-cameroun.com","429","26-05-2025 05:38:24","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0005105558","N=
kozoa","","26-05-2025 04:10:53","26-05-2025 04:04:36","26-05-2025 04:17:52"=
,"Active // No power issue UBaie =3D53,3V site on Grid The FME TX SYMPHORIE=
N (675295205) From Huawei is informed","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue UBaie =3D53,3V site on Grid The FME TX SYMPHORIEN (67529=
5205) From Huawei is informed","gerard.tchangoue@matech-cameroun.com","379"=
,"26-05-2025 04:10:53","MATECH CMR"
"Closed Complete","Site Down","T1071","IHS_YND_343","NOCINC0005105489","Mbe=
doumou - Ekali","IHS_YND_723, IHS_YND_385, IHS_YND_553, IHS_YND_410, IHS_YN=
D_595, IHS_EBO_015, IHS_YND_344, IHS_YND_411","26-05-2025 03:40:40","26-05-=
2025 03:37:23","26-05-2025 04:38:33","Grid fluctuation, site went down beca=
use Gen failed to start due to Grid bad voltage// he bypass the Grid and Ge=
n manually started","Albran Byorel","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Grid fluctuation, site went down because=
 Gen failed to start due to Grid bad voltage// he bypass the Grid and Gen m=
anually started","gerard.tchangoue@matech-cameroun.com","197","26-05-2025 0=
3:40:40","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005105311","Mok=
olo Yaounde","","26-05-2025 02:23:10","26-05-2025 02:19:58","26-05-2025 02:=
25:38","Active // No power issue Ubay: 54.4 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.4 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","gerard.tchangoue@matech-cameroun.com","1=
93","26-05-2025 02:23:10","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005105308","EMA=
NA BILICK CITY","","26-05-2025 02:21:29","26-05-2025 02:17:15","26-05-2025 =
02:36:42","Grid outage, site down because site behaves as Grid only site (n=
o Gen) awaiting Grid return","Fabrice Pouakam","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue","Grid outage, site down because site=
 behaves as Grid only site (no Gen) //Grid return","gerard.tchangoue@matech=
-cameroun.com","256","26-05-2025 02:21:29","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005105300","Mes=
sassi 2","","26-05-2025 02:15:10","26-05-2025 02:11:58","26-05-2025 02:27:1=
0","Grid outage site went down because Gen failed to start due to poor Batt=
ery backup// GEN automatically started","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site=
 went down because Gen failed to start due to poor Battery backup// GEN aut=
omatically started","gerard.tchangoue@matech-cameroun.com","194","26-05-202=
5 02:15:10","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005105208","Odz=
a Minkan IHS","","26-05-2025 01:52:44","26-05-2025 01:44:36","26-05-2025 02=
:32:58","Grid fluctuation, Site went down because Gen failed to start due t=
o Grid bad voltage// He bypassed Grid and started Gen manually","Albran Byo=
rel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, Site went down because Gen failed to start due to Gri=
d bad voltage// He bypassed Grid and started Gen manually","gerard.tchangou=
e@matech-cameroun.com","489","26-05-2025 01:52:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005105030","Nkol-Meb=
anga","","26-05-2025 00:32:21","26-05-2025 00:25:44","26-05-2025 01:00:26",=
"Cascaded Incident from TTO5245309","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen start and stopped with ""High temps"" alarm // He reset it: Site on g=
rid","system","1294194","26-05-2025 00:32:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005105029","Carrefou=
r Ayissi Ele","","26-05-2025 00:32:20","26-05-2025 00:25:44","26-05-2025 01=
:00:26","Cascaded Incident from TTO5245309","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n because Gen start and stopped with ""High temps"" alarm // He reset it: S=
ite on grid","system","1294195","26-05-2025 00:32:20","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005105019","Saa=
","IHS_YND_810, IHS_YND_809","26-05-2025 00:28:50","26-05-2025 00:25:44","2=
6-05-2025 01:07:10","Grid outage, Site went down because Gen start and stop=
ped with ""High temps"" alarm // He reset it: Site on grid","Parker Tchoup"=
,"Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, Site=
 went down because Gen start and stopped with ""High temps"" alarm // He re=
set it: Site on grid","gerard.tchangoue@matech-cameroun.com","188","26-05-2=
025 00:28:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0005104863","Dong",""=
,"25-05-2025 23:32:40","25-05-2025 23:22:59","25-05-2025 23:31:44","Cascade=
d Incident from TTO5245113","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active // No Power issue, site on battery Uba=
y =3D 48.2V  Hybrid Site, Tx Fme Gregoire (654547479) from Huawei is inform=
ed and confirmed","system","1292136","25-05-2025 23:32:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0005104862","Donga","=
","25-05-2025 23:32:40","25-05-2025 23:22:59","25-05-2025 23:31:44","Cascad=
ed Incident from TTO5245113","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active // No Power issue, site on battery Ub=
ay =3D 48.2V  Hybrid Site, Tx Fme Gregoire (654547479) from Huawei is infor=
med and confirmed","system","1292137","25-05-2025 23:32:40","MATECH CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0005104860","N=
guila","IHS_YND_434, IHS_YND_444","25-05-2025 23:31:51","25-05-2025 23:22:5=
9","25-05-2025 23:31:44","Active // No Power issue, site on battery Ubay =
=3D 48.2V  Hybrid Site, Tx Fme Gregoire (654547479) from Huawei is informed=
 and confirmed","Parker Tchoup","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active // No Power issue, site =
on battery Ubay =3D 48.2V  Hybrid Site, Tx Fme Gregoire (654547479) from Hu=
awei is informed and confirmed","edwige.kapawo@matech-cameroun.com","533","=
25-05-2025 23:31:51","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005104772","B=
arriere IHS","","25-05-2025 23:08:21","25-05-2025 22:57:59","25-05-2025 23:=
30:59","fme Gildas report that Gen overload(15Kva, 200A) SS IHS FELIX ZAMBE=
 is informed // Grid return	","Hyemafo Gildas","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","fme Gildas report that Gen overload(15Kva, 2=
00A) SS IHS FELIX ZAMBE is informed // Grid return	","edwige.kapawo@matech-=
cameroun.com","624","25-05-2025 23:08:21","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005104762","O=
kola OCM","","25-05-2025 23:06:36","25-05-2025 22:14:27","26-05-2025 01:31:=
37","Grid outage, Gen failed to start due to ""high temp"" alarm // We adde=
d water and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Rep=
air","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","=
Grid outage, Gen failed to start due to ""high temp"" alarm // We added wat=
er and gen manually started","edwige.kapawo@matech-cameroun.com","3130","25=
-05-2025 23:06:36","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005104237","O=
lembe-Terminus","","25-05-2025 21:22:06","25-05-2025 21:18:54","25-05-2025 =
21:54:54","Grid fluctuations, Site went down because Gen started and stoppe=
d due to Grid bad voltage// Grid stabilized","Fabrice Pouakam","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ions, Site went down because Gen started and stopped due to Grid bad voltag=
e// Grid stabilized","christelle.ngonga@matech-cameroun.com","193","25-05-2=
025 21:22:06","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005104182","MBA=
LNGONG LYCEE","","25-05-2025 21:10:20","25-05-2025 20:53:04","25-05-2025 23=
:11:04","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down be=
cause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informe=
d and confirmed // Grid returned","franck.nkomot@matech-cameroun.com","1038=
","25-05-2025 21:10:20","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005104155","E=
ssomba","","25-05-2025 21:06:12","25-05-2025 21:02:02","25-05-2025 21:25:02=
","Site went down because 03/06 rectifiers dysfunctionned //Site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down because 03/06 rectifiers dysfunctionned //Site stabil=
ised","christelle.ngonga@matech-cameroun.com","251","25-05-2025 21:06:12","=
MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005104148","Bar=
riere","","25-05-2025 21:04:27","25-05-2025 20:58:40","25-05-2025 21:05:40"=
,"Active: No power issue on site Ubay: 54.6V site on Grid TX Fme SAMBA (654=
266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power =
issue on site Ubay: 54.6V site on Grid TX Fme SAMBA (654266058/Huawei) is i=
nformed.","franck.nkomot@matech-cameroun.com","385","25-05-2025 21:04:27","=
MATECH CMR"
"Cancelled","Warning","CTR_322","IHS_YND_029","NOCINC0005104100","Sapeur","=
","25-05-2025 20:58:33","","","","Mboua Thierry","","","","","","ludivine.n=
gamaleu@ihstowers.com","10","25-05-2025 20:58:33","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005104041","M=
essassi 2","","25-05-2025 20:49:57","25-05-2025 20:44:38","25-05-2025 20:45=
:38","ACTIVE//no power issue Ubaie:53.9V site on Grid, TX fme symphorien /6=
50257151 from huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no =
power issue Ubaie:53.9V site on Grid, TX fme symphorien /650257151 from hua=
wei is informed","franck.nkomot@matech-cameroun.com","321","25-05-2025 20:4=
9:57","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0005104023","NKO=
ABANG NKOLO 3","","25-05-2025 20:45:50","25-05-2025 20:39:06","25-05-2025 2=
1:15:06","Grid outage,Site went down due to gen overload(10KVA, 130A) // he=
 reduced the load and started Gen manually","Mba Lazare Herve","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue to gen overload(10KVA, 130A) // he reduced the load and started Gen manu=
ally","franck.nkomot@matech-cameroun.com","405","25-05-2025 20:45:50","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005103876","SOA VILL=
AGE","","25-05-2025 20:13:30","25-05-2025 20:05:45","25-05-2025 20:40:32","=
Cascaded Incident from TTO5244022","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with overvoltage alarm // Gen reseted and manually s=
tart .","system","1310139","25-05-2025 20:13:30","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005103875","SOA=
 TOWN","IHS_YND_323","25-05-2025 20:13:01","25-05-2025 20:05:45","25-05-202=
5 20:40:32","Grid outage, site went down because gen start and stopped with=
 overvoltage alarm // Gen reseted and manually start .","Siligap Boris","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, s=
ite went down because gen start and stopped with overvoltage alarm // Gen r=
eseted and manually start .","franck.nkomot@matech-cameroun.com","437","25-=
05-2025 20:13:01","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005103857","OBA=
M NGOLA OCM","","25-05-2025 20:10:24","25-05-2025 20:04:05","25-05-2025 20:=
44:05","Grid Outage, Gen Failed to start due to Gen Card Faulty// Gen start=
 manually","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid Outage, Gen Failed to start due to Gen Card Faulty// G=
en start manually","franck.nkomot@matech-cameroun.com","380","25-05-2025 20=
:10:24","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005103806","O=
lembe-Terminus","","25-05-2025 20:01:51","25-05-2025 19:56:30","25-05-2025 =
20:20:30","Grid outage, Site went down because Gen failed to start due to R=
elay R2 48V Faulty // Relay R2 replaced","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","ATS Relay Faulty","Grid outage, Site went dow=
n because Gen failed to start due to Relay R2 48V Faulty // Relay R2 replac=
ed","christelle.ngonga@matech-cameroun.com","323","25-05-2025 20:01:51","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0005103715","T=
SINGA VILLAGE 2","","25-05-2025 19:43:11","25-05-2025 19:14:59","25-05-2025=
 20:23:59","Gen Only, Site went Down due to fuel shortage // Refueling Done=
","Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Outage","Gen On=
ly, Site went Down due to fuel shortage // Refueling Done","christelle.ngon=
ga@matech-cameroun.com","1694","25-05-2025 19:43:11","MATECH CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0005103594","MES=
SAME NDONGO 1162","","25-05-2025 19:16:48","25-05-2025 19:08:30","25-05-202=
5 19:28:30","Grid outage,gen failed to start due to Gen card malfunctioning=
//he reseted the card and he started Gen manually","MINKA NICOLAS","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,gen fai=
led to start due to Gen card malfunctioning//he reseted the card and he sta=
rted Gen manually","franck.nkomot@matech-cameroun.com","499","25-05-2025 19=
:16:48","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005103508","M=
essassi 2","","25-05-2025 18:56:56","25-05-2025 18:52:28","25-05-2025 20:09=
:28","Grid outage site went down because Gen failed to start due to poor Ba=
ttery backup// GEN automatically started","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage si=
te went down because Gen failed to start due to poor Battery backup// GEN a=
utomatically started","ludivine.ngamaleu@ihstowers.com","270","25-05-2025 1=
8:56:56","MATECH CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0005103477","SOA=
 VILLAGE","","25-05-2025 18:50:03","25-05-2025 18:40:48","25-05-2025 19:10:=
48","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid outage, Site went down before Gen start due to fuel shorta=
ge // Refueling done","franck.nkomot@matech-cameroun.com","1308751","25-05-=
2025 18:50:03","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005103414","S=
OA TOWN","IHS_YND_323","25-05-2025 18:39:55","25-05-2025 18:38:48","25-05-2=
025 19:10:48","Grid outage, Site went down before Gen start due to fuel sho=
rtage // Refueling done","Siligap Boris","Fuel Outage","Passive","Diesel","=
Diesel Outage","Grid outage, Site went down before Gen start due to fuel sh=
ortage // Refueling done","christelle.ngonga@matech-cameroun.com","69","25-=
05-2025 18:39:55","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005103356","Bar=
riere","","25-05-2025 18:31:54","25-05-2025 18:26:48","25-05-2025 20:05:48"=
,"Active: No power issue on site Ubay: 54.6V site on Grid TX Fme SAMBA (654=
266058/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power =
issue on site Ubay: 54.6V site on Grid TX Fme SAMBA (654266058/Huawei) is i=
nformed.","franck.nkomot@matech-cameroun.com","328","25-05-2025 18:31:54","=
MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0005103245","O=
lembe-Terminus","","25-05-2025 18:17:31","25-05-2025 18:10:23","25-05-2025 =
19:35:00","Grid outage site went down due to disfunctionning of PSC3 ( plan=
ed ) // PSC3 has been reset ,Grid returned","Fabrice Pouakam","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went do=
wn due to disfunctionning of PSC3 ( planed ) // PSC3 has been reset ,Grid r=
eturned","christelle.ngonga@matech-cameroun.com","429","25-05-2025 18:17:31=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005103195","Emana Ly=
cee","","25-05-2025 18:04:34","25-05-2025 17:59:22","25-05-2025 18:18:02","=
Cascaded Incident from TTO5243249","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down beca=
use Gen failed to started due to poor battery backup , // Grid returned.","=
system","1311173","25-05-2025 18:04:34","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005103186","E=
mana lycee 2","IHS_YND_274","25-05-2025 18:02:32","25-05-2025 17:59:22","25=
-05-2025 18:18:02","Grid outage , site went down because Gen failed to star=
ted due to poor battery backup , // Grid returned.","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","DG Low Battery","Grid outage , site wen=
t down because Gen failed to started due to poor battery backup , // Grid r=
eturned.","christelle.ngonga@matech-cameroun.com","191","25-05-2025 18:02:3=
2","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0005102971","Meh=
anda 1","","25-05-2025 17:23:21","25-05-2025 17:16:51","25-05-2025 17:32:51=
","Grid fluctuation,site went dowwn  due to Grid bad voltage// Grid return"=
,"Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid fluctuation,site went dowwn  due to Grid bad voltage//=
 Grid return","franck.nkomot@matech-cameroun.com","390","25-05-2025 17:23:2=
1","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005102901","M=
essassi 2","","25-05-2025 17:10:59","25-05-2025 17:05:48","25-05-2025 18:04=
:48","Grid outage site went down because Gen failed to start due to poor Ba=
ttery backup// GEN automatically started","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage si=
te went down because Gen failed to start due to poor Battery backup// GEN a=
utomatically started","franck.nkomot@matech-cameroun.com","312","25-05-2025=
 17:10:59","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005102795","M=
essassi okolo","","25-05-2025 16:49:41","25-05-2025 16:40:48","25-05-2025 1=
6:57:48","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site down because site behaves as Grid only=
 site (no Gen) // Grid returned","franck.nkomot@matech-cameroun.com","13157=
97","25-05-2025 16:49:41","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005102788","E=
MANA BILICK CITY","IHS_YND_279","25-05-2025 16:48:52","25-05-2025 16:40:48"=
,"25-05-2025 17:03:48","Grid outage, site down because site behaves as Grid=
 only site (no Gen) // Grid returned","Fabrice Pouakam","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage, site down bec=
ause site behaves as Grid only site (no Gen) // Grid returned","ludivine.ng=
amaleu@ihstowers.com","486","25-05-2025 16:48:52","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005102751","Mes=
sassi 2","","25-05-2025 16:42:58","25-05-2025 16:35:48","25-05-2025 16:59:4=
8","Grid outage site went down because Gen failed to start due to poor Batt=
ery backup// GEN automatically started","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site=
 went down because Gen failed to start due to poor Battery backup// GEN aut=
omatically started","franck.nkomot@matech-cameroun.com","505","25-05-2025 1=
6:42:58","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0005102652","N=
kolda","IHS_YND_327","25-05-2025 16:35:20","25-05-2025 16:26:09","25-05-202=
5 17:33:08","Site down due to grid low voltage, Gen did not receive other t=
o start // Grid stabilisation","Albran Byorel","Grid Supply","Passive","Gri=
d","National Grid - Low Current Supply","Site down due to grid low voltage,=
 Gen did not receive other to start // Grid stabilisation","christelle.ngon=
ga@matech-cameroun.com","751","25-05-2025 16:35:20","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0005102643","N=
simalen OCM","","25-05-2025 16:34:34","25-05-2025 16:26:09","25-05-2025 17:=
33:08","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Site down due to grid low voltage, Gen did not receive other=
 to start // Grid stabilisation","christelle.ngonga@matech-cameroun.com","1=
316657","25-05-2025 16:34:34","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005102623","O=
LAMA","","25-05-2025 16:29:58","25-05-2025 16:26:51","25-05-2025 17:34:26",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue.","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX=
 FME Henri (699949693) from Huawei is informed.Noticed that it is a repetit=
ve issue.","christelle.ngonga@matech-cameroun.com","188","25-05-2025 16:29:=
58","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005102453","ODZ=
A MINKAN EDIBI ASSI","","25-05-2025 15:51:13","25-05-2025 15:47:15","25-05-=
2025 19:31:15","Grid outage, site went down because gen failed to start due=
 to AVR faulty // Grid return","Albran Byorel","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - AVR","Grid outage, site went down because gen failed to=
 start due to AVR faulty // Grid return","franck.nkomot@matech-cameroun.com=
","239","25-05-2025 15:51:13","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005102193","M=
ontee-Des-Soeurs","","25-05-2025 14:56:32","24-05-2025 14:09:18","25-05-202=
5 16:40:40","Grid outage ,site down due to Gen overload (15 KVA/210 AM ) //=
 Grid restoration","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage ,site down due to Gen overload (15 KVA/210 =
AM ) // Grid restoration","christelle.ngonga@matech-cameroun.com","90588","=
25-05-2025 14:56:32","MATECH CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0005101874","Bri=
quetterie","","25-05-2025 14:01:12","25-05-2025 13:56:19","25-05-2025 14:30=
:19","Grid only site, no space to deploy MDGE // Grid returned","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site,=
 no space to deploy MDGE // Grid returned","loic.noumsi@matech-cameroun.com=
","294","25-05-2025 14:01:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005101860","Nsam esc=
ale LP","","25-05-2025 13:56:44","25-05-2025 13:50:13","25-05-2025 13:58:08=
","Cascaded Incident from TTO5241715","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, site went down before Gen starte=
d due to poor backup // Gen started automatically","system","1325830","25-0=
5-2025 13:56:44","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005101859","Nsa=
m Sofavinc","IHS_YND_732","25-05-2025 13:56:19","25-05-2025 13:50:13","25-0=
5-2025 13:58:08","Grid outage, site went down before Gen started due to poo=
r backup // Gen started automatically","MINKA NICOLAS","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before Gen started due to poor backup // Gen started automatically=
","loic.noumsi@matech-cameroun.com","368","25-05-2025 13:56:19","MATECH CMR=
"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005101810","Odz=
a Minkan IHS","","25-05-2025 13:49:22","25-05-2025 13:42:13","25-05-2025 16=
:08:13","Grid fluctuation, Site went down because Gen failed to start due t=
o Grid bad voltage// He bypassed Grid and started Gen manually","Albran Byo=
rel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, Site went down because Gen failed to start due to Gri=
d bad voltage// He bypassed Grid and started Gen manually","loic.noumsi@mat=
ech-cameroun.com","430","25-05-2025 13:49:22","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005101790","S=
imbock OCM","","25-05-2025 13:42:44","25-05-2025 13:38:24","25-05-2025 15:0=
9:24","Site went down because Felix IHS SS was on site for plan work (bay c=
onfiguration) // End of work","Hyemafo Gildas","Installation Activity","Pas=
sive","Planned Activity","Installation Activity","Site went down because Fe=
lix IHS SS was on site for plan work (bay configuration) // End of work","g=
aelle.njiofack@matech-cameroun.com","261","25-05-2025 13:42:44","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005101756","Messassi=
 okolo","","25-05-2025 13:36:34","25-05-2025 13:31:36","25-05-2025 14:03:19=
","Cascaded Incident from TTO5241579","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (no Gen)","system","1326919","25-05-2025 13=
:36:34","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005101739","E=
MANA BILICK CITY","IHS_YND_279","25-05-2025 13:33:44","25-05-2025 13:31:36"=
,"25-05-2025 14:03:19","Grid outage, site down because site behaves as Grid=
 only site (no Gen) // Grid returned","Fabrice Pouakam","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage, site down bec=
ause site behaves as Grid only site (no Gen) // Grid returned","gaelle.njio=
fack@matech-cameroun.com","130","25-05-2025 13:33:44","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005101718","B=
arriere","","25-05-2025 13:29:21","25-05-2025 13:22:11","25-05-2025 16:07:1=
1","Grid outage, Site went down before Gen start due to fuel shortage // Re=
fueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, Site went down before Gen start due to fuel shortage // =
Refueling done","loic.noumsi@matech-cameroun.com","432","25-05-2025 13:29:2=
1","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005101631","E=
vodoula OCM","","25-05-2025 13:12:19","25-05-2025 10:48:54","25-05-2025 11:=
39:39","Back traking/ Grid outage,gen failed to start due to grid bad volta=
ge,no rcp// Grid stabilized","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","Back traking/ Grid o=
utage,gen failed to start due to grid bad voltage,no rcp// Grid stabilized"=
,"gaelle.njiofack@matech-cameroun.com","8606","25-05-2025 13:12:19","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005101576","Song-bon=
g","","25-05-2025 13:00:29","25-05-2025 12:42:49","25-05-2025 12:59:15","Ca=
scaded Incident from TTO5241366","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site ,site on Gen wi=
ith Ubaie=3D52.4 V The TX FME Etienne/ 695033981 FROM Huawei is informed","=
system","1329802","25-05-2025 13:00:29","MATECH CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0005101546","Ese=
ka MTN","IHS_YND_453, IHS_YND_378","25-05-2025 12:52:45","25-05-2025 12:42:=
49","25-05-2025 17:01:30","No power issue on site ,site on Gen wiith Ubaie=
=3D52.4 V The TX FME Etienne/ 695033981 FROM Huawei is informed","Kemeni Fr=
anklin","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site ,site on Gen wiith Ubaie=3D52.4 =
V The TX FME Etienne/ 695033981 FROM Huawei is informed","loic.noumsi@matec=
h-cameroun.com","597","25-05-2025 12:52:45","MATECH CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0005101544","Ese=
ka Town","","25-05-2025 12:51:46","25-05-2025 12:42:49","25-05-2025 12:59:1=
5","","Kemeni Franklin","Cascade Outage","Active","Cascade Active","Cascade=
 Active","CASCADE OUTAGE","loic.noumsi@matech-cameroun.com","1329802","25-0=
5-2025 12:51:46","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005101515","E=
koumdoum OCM","","25-05-2025 12:47:21","25-05-2025 12:08:10","25-05-2025 13=
:31:33","Site went down due to disjunction of Cb(100A&80A) in DC BOX // He =
rearmed CBs, site on grid","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","ATS-AMF Issue","Site went down due to disjunction of Cb(100A&=
80A) in DC BOX // He rearmed CBs, site on grid","gaelle.njiofack@matech-cam=
eroun.com","2352","25-05-2025 12:47:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005101362","MEHANDAN=
","","25-05-2025 12:23:03","25-05-2025 12:18:27","25-05-2025 12:25:21","Cas=
caded Incident from TTO5241154","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to PWC ZTE malfunction // Site stabilised","system",=
"1331225","25-05-2025 12:23:03","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005101358","O=
dza II OCM","IHS_YND_528","25-05-2025 12:22:34","25-05-2025 12:18:27","25-0=
5-2025 12:25:54","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","	Grid outage, si=
te went down because gen failed to start due to PWC ZTE malfunction // Site=
 stabilised","gaelle.njiofack@matech-cameroun.com","249","25-05-2025 12:22:=
34","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005101330","O=
LAMA","","25-05-2025 12:18:53","25-05-2025 12:10:47","25-05-2025 12:45:45",=
"Active//No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed.Noticed that it is a repetitve issue",=
"Fanda Brice","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active//No power issue on site Ubaie =3D54.9V sit=
e on Gen The TX FME Henri (699949693) from Huawei is informed.Noticed that =
it is a repetitve issue","gaelle.njiofack@matech-cameroun.com","487","25-05=
-2025 12:18:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005101294","Carrefou=
r Ayissi Ele","","25-05-2025 12:10:14","25-05-2025 11:59:53","25-05-2025 12=
:30:04","Cascaded Incident from TTO5241064","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n because Gen start and stopped with ""High temps"" alarm // he added water=
 and manually start the Gen","system","1332326","25-05-2025 12:10:14","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005101272","S=
aa","IHS_YND_810","25-05-2025 12:08:08","25-05-2025 11:59:53","25-05-2025 1=
2:30:04","Grid outage, Site went down because Gen start and stopped with ""=
High temps"" alarm // he added water and manually start the Gen","Parker Tc=
houp","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage,=
 Site went down because Gen start and stopped with ""High temps"" alarm // =
he added water and manually start the Gen","loic.noumsi@matech-cameroun.com=
","497","25-05-2025 12:08:08","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0005101264","N=
kolo II New","","25-05-2025 12:04:12","25-05-2025 11:54:59","25-05-2025 12:=
17:26","No power issue, Site impacted by Mimboman-Don-Bosco","Mba Lazare He=
rve","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","No power issue, Site impacted by Mimboman-Don-Bosc=
o","loic.noumsi@matech-cameroun.com","554","25-05-2025 12:04:12","MATECH CM=
R"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005101061","OBA=
M NGOLA OCM","","25-05-2025 11:40:18","25-05-2025 11:32:10","25-05-2025 11:=
48:54","Grid Outage, Gen Failed to start due to Gen Card Faulty// Gen start=
 manually","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid Outage, Gen Failed to start due to Gen Card Faulty// G=
en start manually","loic.noumsi@matech-cameroun.com","489","25-05-2025 11:4=
0:18","MATECH CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0005101051","N=
sam Sofavinc T0","","25-05-2025 11:38:12","25-05-2025 11:33:04","25-05-2025=
 12:04:14","Site went down due to malfunction of PWC ZTE //  PWC reset and =
site on Gen","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rect=
ifier Module Overloaded","Site went down due to malfunction of PWC ZTE //  =
PWC reset and site on Gen","gaelle.njiofack@matech-cameroun.com","309","25-=
05-2025 11:38:12","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005101020","N=
YOM 2 IHS","","25-05-2025 11:29:55","25-05-2025 11:26:48","25-05-2025 11:30=
:09","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automaticaly","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen started automaticaly","gaelle.njiofa=
ck@matech-cameroun.com","189","25-05-2025 11:29:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0005101017","Nsam esc=
ale LP","","25-05-2025 11:29:03","25-05-2025 11:23:06","25-05-2025 11:29:57=
","Cascaded Incident from TTO5240783","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, site went down before Gen starte=
d due to poor backup // Gen started automatically","system","1334470","25-0=
5-2025 11:29:03","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005101014","Nsa=
m Sofavinc","IHS_YND_732","25-05-2025 11:28:14","25-05-2025 11:23:06","25-0=
5-2025 11:29:57","Grid outage, site went down before Gen started due to poo=
r backup // Gen started automatically","MINKA NICOLAS","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before Gen started due to poor backup // Gen started automatically=
","loic.noumsi@matech-cameroun.com","308","25-05-2025 11:28:14","MATECH CMR=
"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005100954","S=
imbock OCM","","25-05-2025 11:14:41","25-05-2025 11:08:32","25-05-2025 11:3=
4:49","Site went down due to work plan done by SS IHS Felix (bay configurat=
ion) // End of work","Hyemafo Gildas","Installation Activity","Passive","Pl=
anned Activity","Installation Activity","Site went down due to work plan do=
ne by SS IHS Felix (bay configuration) // End of work","gaelle.njiofack@mat=
ech-cameroun.com","370","25-05-2025 11:14:41","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005100707","E=
ssomba","","25-05-2025 10:28:55","25-05-2025 10:26:32","25-05-2025 19:03:31=
","Site went down because 03/06 rectifiers dysfunctionned //Site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down because 03/06 rectifiers dysfunctionned //Site stabil=
ised","loic.noumsi@matech-cameroun.com","145","25-05-2025 10:28:55","MATECH=
 CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0005100606","NKO=
ABANG NKOLO 3","","25-05-2025 10:06:04","25-05-2025 09:59:55","25-05-2025 1=
2:34:35","Grid outage,Site went down due to gen overload(10KVA, 130A) // he=
 reduced the load and started Gen manually","Mba Lazare Herve","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue to gen overload(10KVA, 130A) // he reduced the load and started Gen manu=
ally","loic.noumsi@matech-cameroun.com","370","25-05-2025 10:06:04","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005100545","M=
vog-Ada_OCM","","25-05-2025 09:53:53","25-05-2025 09:46:45","25-05-2025 14:=
24:41","Grid Only site, No space to deploy MGE // Grid restoration","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only s=
ite, No space to deploy MGE // Grid restoration","gaelle.njiofack@matech-ca=
meroun.com","430","25-05-2025 09:53:53","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005100543","E=
koumdoum OCM","","25-05-2025 09:52:58","25-05-2025 09:46:50","25-05-2025 11=
:38:51","Site went down due to disjunction of Cb(100A&80A) in DC BOX // He =
rearmed CBs, site on grid","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","ATS-AMF Issue","Site went down due to disjunction of Cb(100A&=
80A) in DC BOX // He rearmed CBs, site on grid","gaelle.njiofack@matech-cam=
eroun.com","369","25-05-2025 09:52:58","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0005100470","Nko=
londom","","25-05-2025 09:36:06","25-05-2025 09:31:56","25-05-2025 10:19:15=
","Grid outage, Site went down because Gen failed to start due to battery G=
en Faulty// He started Gen with external battery","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, S=
ite went down because Gen failed to start due to battery Gen Faulty// He st=
arted Gen with external battery","loic.noumsi@matech-cameroun.com","251","2=
5-05-2025 09:36:06","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0005100309","NKO=
ABANG NKOLO 3","","25-05-2025 09:03:38","25-05-2025 08:59:18","25-05-2025 0=
9:06:10","Grid fluctuations site went down because Gen started and stopped =
due to Grid bad voltage and RCP on site // He bypassed the Grid and started=
 Gen manually","Mba Lazare Herve","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","Grid fluctuations site went down because G=
en started and stopped due to Grid bad voltage and RCP on site // He bypass=
ed the Grid and started Gen manually","loic.noumsi@matech-cameroun.com","26=
1","25-05-2025 09:03:38","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005100305","N=
kolbong","","25-05-2025 09:02:43","25-05-2025 08:57:29","25-05-2025 10:45:2=
6","Site went Down because Gen started and stopped due to Gen overload(22kv=
a//350A) // Grid returned","Delor Telezing","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Site went Down because Gen started and stopped =
due to Gen overload(22kva//350A) // Grid returned","gaelle.njiofack@matech-=
cameroun.com","315","25-05-2025 09:02:43","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005100250","N=
yom OCM","","25-05-2025 08:47:01","25-05-2025 08:38:56","25-05-2025 17:02:5=
9","ACTIVE//no power issue Ubaie:54.2V site on Gen, TX fme symphorien /6502=
57151 from huawei is informed","Fabrice Pouakam","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no pow=
er issue Ubaie:54.2V site on Gen, TX fme symphorien /650257151 from huawei =
is informed","loic.noumsi@matech-cameroun.com","487","25-05-2025 08:47:01",=
"MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005100088","Mes=
sassi 2","","25-05-2025 08:06:34","25-05-2025 07:57:26","25-05-2025 16:18:5=
8","no power issue Ubaie:53.9V site on Grid, TX fme symphorien /650257151 f=
rom huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","no power issue Ubaie:=
53.9V site on Grid, TX fme symphorien /650257151 from huawei is informed","=
loic.noumsi@matech-cameroun.com","550","25-05-2025 08:06:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0005100053","Nkolo II=
 New","","25-05-2025 07:58:39","25-05-2025 07:53:41","25-05-2025 11:01:21",=
"Cascaded Incident from TTO5239714","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to 2/5 recti=
fiers that dysfunctionned // He added rectifiers after managing to have rec=
tifers ","system","1340871","25-05-2025 07:58:39","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005100047","Mim=
boman4","IHS_YND_709","25-05-2025 07:57:46","25-05-2025 07:53:41","25-05-20=
25 11:01:21","Site went down due to 2/5 rectifiers that dysfunctionned // H=
e added rectifiers after managing to have rectifers ","Mba Lazare Herve","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went down d=
ue to 2/5 rectifiers that dysfunctionned // He added rectifiers after manag=
ing to have rectifers ","loic.noumsi@matech-cameroun.com","247","25-05-2025=
 07:57:46","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005100009","N=
koabang2","","25-05-2025 07:44:25","25-05-2025 07:42:57","25-05-2025 11:55:=
38","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed //He reduced load","Mba Lazare Herve","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to=
 gen overload (22KVA, 330A), SS Blaise IHS is informed //He reduced load","=
gaelle.njiofack@matech-cameroun.com","90","25-05-2025 07:44:25","MATECH CMR=
"
"Closed Complete","Site Down","CTR_621","IHS_YND_278","NOCINC0005099988","N=
kolfoulou 2","","25-05-2025 07:39:24","25-05-2025 07:26:13","25-05-2025 07:=
42:42","ticket error","Siligap Boris","Incorrectly Logged Tickets","Error",=
"Error","Error","ticket error","gaelle.njiofack@matech-cameroun.com","792",=
"25-05-2025 07:39:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005099892","Messassi=
 okolo","","25-05-2025 07:12:53","25-05-2025 07:06:23","25-05-2025 07:58:47=
","Cascaded Incident from TTO5239516","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (no Gen) // Grid returned","system","134363=
8","25-05-2025 07:12:53","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005099880","Mes=
sassi 2","","25-05-2025 07:10:39","25-05-2025 07:03:04","25-05-2025 07:13:3=
2","Grid outage site went down because Gen failed to start due to poor Batt=
ery backup// GEN automatically started","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site=
 went down because Gen failed to start due to poor Battery backup// GEN aut=
omatically started","loic.noumsi@matech-cameroun.com","457","25-05-2025 07:=
10:39","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005099879","E=
MANA BILICK CITY","IHS_YND_279","25-05-2025 07:10:32","25-05-2025 07:06:23"=
,"25-05-2025 07:58:47","Grid outage, site down because site behaves as Grid=
 only site (no Gen) // Grid returned","Fabrice Pouakam","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage, site down bec=
ause site behaves as Grid only site (no Gen) // Grid returned","gaelle.njio=
fack@matech-cameroun.com","251","25-05-2025 07:10:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005099868","Emana Ly=
cee","","25-05-2025 07:06:43","25-05-2025 07:04:31","25-05-2025 07:21:46","=
Cascaded Incident from TTO5239500","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down beca=
use Gen failed to started due to poor battery backup , // Grid returned.","=
system","1349652","25-05-2025 07:06:43","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005099864","E=
mana lycee 2","IHS_YND_274","25-05-2025 07:05:44","25-05-2025 07:04:31","25=
-05-2025 07:21:46","Grid outage , site went down because Gen failed to star=
ted due to poor battery backup , // Grid returned.","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 outage , site went down because Gen failed to started due to poor battery =
backup , // Grid returned.","gaelle.njiofack@matech-cameroun.com","74","25-=
05-2025 07:05:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0005099852","Dagobert=
","","25-05-2025 07:00:05","25-05-2025 06:54:17","25-05-2025 08:33:27","Cas=
caded Incident from TTO5239477","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down=
 because gen failed to start due to low oil pressure // He added oil, reset=
ed and started Gen manually","system","1344357","25-05-2025 07:00:05","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0005099851","Yona Hot=
el","","25-05-2025 07:00:05","25-05-2025 06:54:17","25-05-2025 08:33:27","C=
ascaded Incident from TTO5239477","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went do=
wn because gen failed to start due to low oil pressure // He added oil, res=
eted and started Gen manually","system","1344357","25-05-2025 07:00:05","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005099846","N=
kolbi-Boss","IHS_YND_271, IHS_YND_286","25-05-2025 06:58:09","25-05-2025 06=
:54:17","25-05-2025 08:41:06","Grid outage, Site went down because gen fail=
ed to start due to low oil pressure // He added oil, reseted and started Ge=
n manually","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG G=
en","ACDG - Low Oil Pressure","Grid outage, Site went down because gen fail=
ed to start due to low oil pressure // He added oil, reseted and started Ge=
n manually","loic.noumsi@matech-cameroun.com","233","25-05-2025 06:58:09","=
MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005099480","Nko=
l-Mebanga","","25-05-2025 04:51:04","25-05-2025 04:45:50","25-05-2025 11:55=
:38","Solar only site, Site went Down due to low Solar// Solar returned","P=
arker Tchoup","Equipment Repair","Passive","Solar","Solar Panel Issue","Sol=
ar only site, Site went Down due to low Solar// Solar returned","cedric.tia=
ni@matech-cameroun.com","315","25-05-2025 04:51:04","MATECH CMR"
"Closed Complete","Warning","T0772","IHS_YND_207","NOCINC0005099344","ARMP =
Building","","25-05-2025 03:31:05","","","Grid outage// He deploy 20KVA","M=
boua Thierry","Warning","Warning","POWER","Warning - National Grid - Grid O=
utage Issue","Grid outage// He deploy 20KVA","cedric.tiani@matech-cameroun.=
com","3312","25-05-2025 03:31:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005099255","Ngoum","=
","25-05-2025 02:54:45","25-05-2025 02:50:17","25-05-2025 03:09:58","Cascad=
ed Incident from TTO5238803","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because Gen failed to star=
t due to Gen not in automatic mode//He started the Gen manually","system","=
1358732","25-05-2025 02:54:45","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0005099250","Yok=
o MTN","IHS_YND_475","25-05-2025 02:51:30","25-05-2025 02:50:17","25-05-202=
5 03:09:58","Site went down because Gen failed to start due to Gen not in a=
utomatic mode//He started the Gen manually","Parker Tchoup","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Site went down because Gen=
 failed to start due to Gen not in automatic mode//He started the Gen manua=
lly","cedric.tiani@matech-cameroun.com","74","25-05-2025 02:51:30","MATECH =
CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005099109","E=
ssomba","","25-05-2025 01:30:50","25-05-2025 01:29:19","25-05-2025 02:57:22=
","Site went down because 03/06 rectifiers dysfunctionned //Site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down because 03/06 rectifiers dysfunctionned //Site stabil=
ised","cedric.tiani@matech-cameroun.com","93","25-05-2025 01:30:50","MATECH=
 CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005099107","Mok=
olo Yaounde","","25-05-2025 01:29:26","25-05-2025 01:26:17","25-05-2025 01:=
32:07","Active // No power issue Ubay: 54.7V site on grid. The Tx FME Eloun=
dou Bertrand (693212405) from Huawei is informed","","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // =
No power issue Ubay: 54.7V site on grid. The Tx FME Eloundou Bertrand (6932=
12405) from Huawei is informed","cedric.tiani@matech-cameroun.com","190","2=
5-05-2025 01:29:26","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005099001","O=
LAMA","","25-05-2025 00:39:10","25-05-2025 00:30:00","25-05-2025 03:20:04",=
"Active//No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed.Noticed that it is a repetitve issue",=
"Fanda Brice","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active//No power issue on site Ubaie =3D54.9V sit=
e on Gen The TX FME Henri (699949693) from Huawei is informed.Noticed that =
it is a repetitve issue","cedric.tiani@matech-cameroun.com","551","25-05-20=
25 00:39:10","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005098983","S=
imbock OCM","","25-05-2025 00:33:17","25-05-2025 00:29:54","25-05-2025 07:0=
2:57","Grid outage, Site went down due to Gen (20 kva, 160A) overload // He=
 reduced Load","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, Site went down due to Gen (20 kva, 160A) overl=
oad // He reduced Load","cedric.tiani@matech-cameroun.com","204","25-05-202=
5 00:33:17","MATECH CMR"
"Closed Complete","Warning","T0211","IHS_YND_393","NOCINC0005098893","Ezeza=
ng","","25-05-2025 00:15:06","","","Site alarming because Gen started and s=
topped with alarm *High temp* due to generator fan belt faulty //He replace=
d and manually started the Gen","Parker Tchoup","Warning","Warning","POWER"=
,"Warning - ACDG - Fan Belt","Site alarming because Gen started and stopped=
 with alarm *High temp* due to generator fan belt faulty //He replaced and =
manually started the Gen","cedric.tiani@matech-cameroun.com","1635","25-05-=
2025 00:15:06","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005098791","M=
ambine","","24-05-2025 23:37:11","24-05-2025 23:31:03","24-05-2025 23:54:10=
","Grid outage, site went down because gen ran untill fuel shortage // Refu=
elling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage, site went down because gen ran untill fuel shortage // Refue=
lling done","cedric.tiani@matech-cameroun.com","369","24-05-2025 23:37:11",=
"MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005098588","Men=
dong3","","24-05-2025 22:36:43","24-05-2025 22:29:09","24-05-2025 22:31:36"=
,"","","Cascade Outage","Active","Cascade Active","Cascade Active","No powe=
r issue site on grid with U=3D55.2v Mbah Osiah(674007438) from Huaweio is i=
nformed","cedric.tiani@matech-cameroun.com","1374233","24-05-2025 22:36:43"=
,"MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005098585","Men=
dong NB","","24-05-2025 22:36:08","24-05-2025 22:29:09","24-05-2025 22:31:3=
6","","","Cascade Outage","Active","Cascade Active","Cascade Active","No po=
wer issue site on grid with U=3D55.2v Mbah Osiah(674007438) from Huaweio is=
 informed","cedric.tiani@matech-cameroun.com","1374232","24-05-2025 22:36:0=
8","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005098582","Nko=
abang Ebolmedjock","","24-05-2025 22:35:39","24-05-2025 22:33:28","24-05-20=
25 22:53:49","Grid outage, site went down because Gen stopped with alarm ""=
overcurrent""// He reset Gen card and Gen manually started","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage, site went down because Gen stopped with alarm ""overcurrent""// He re=
set Gen card and Gen manually started","cedric.tiani@matech-cameroun.com","=
132","24-05-2025 22:35:39","MATECH CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0005098571","Men=
dong Maeture","","24-05-2025 22:33:15","24-05-2025 22:29:09","24-05-2025 22=
:31:36","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","Cas=
cade Active","No power issue site on grid with U=3D55.2v Mbah Osiah(6740074=
38) from Huaweio is informed","cedric.tiani@matech-cameroun.com","1374233",=
"24-05-2025 22:33:15","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005098562","Men=
dong Plateau","IHS_YND_742, IHS_YND_569, IHS_YND_262","24-05-2025 22:32:20"=
,"24-05-2025 22:29:09","24-05-2025 23:31:36","No power issue site on grid w=
ith U=3D55.2v Mbah Osiah(674007438) from Huaweio is informed","Hyemafo Gild=
as","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue site on grid with U=3D55.2v Mbah Osiah(67400=
7438) from Huaweio is informed","cedric.tiani@matech-cameroun.com","191","2=
4-05-2025 22:32:20","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005098550","Eto=
ug ebe Carrefour","","24-05-2025 22:29:03","24-05-2025 22:20:56","24-05-202=
5 22:35:04","Grid outage, site went down before gen start due to poor batte=
ry backup // gen start automatically","Hyemafo Gildas","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup // gen start automatic=
ally","cedric.tiani@matech-cameroun.com","488","24-05-2025 22:29:03","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005098526","M=
essassi 2","","24-05-2025 22:26:03","24-05-2025 22:23:48","25-05-2025 01:10=
:17","ACTIVE//no power issue Ubaie:53.9V site on Grid, TX fme symphorien /6=
50257151 from huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no =
power issue Ubaie:53.9V site on Grid, TX fme symphorien /650257151 from hua=
wei is informed","cedric.tiani@matech-cameroun.com","137","24-05-2025 22:26=
:03","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005098400","N=
yom OCM","","24-05-2025 21:58:51","24-05-2025 21:49:59","24-05-2025 22:55:3=
7","ACTIVE//no power issue Ubaie:54.2V site on Gen, TX fme symphorien /6502=
57151 from huawei is informed","Fabrice Pouakam","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no pow=
er issue Ubaie:54.2V site on Gen, TX fme symphorien /650257151 from huawei =
is informed","vanel.mbiada@matech-cameroun.com","533","24-05-2025 21:58:51"=
,"MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005098257","SAA=
 Entrance","","24-05-2025 21:24:09","24-05-2025 21:15:56","24-05-2025 21:24=
:41","Grid outage, site went down due to Grid bad voltage // GRID RETURN","=
Parker Tchoup","Grid Supply","Passive","Grid","National Grid - Grid Outage =
Issue","Grid outage, site went down due to Grid bad voltage // GRID RETURN"=
,"gerard.tchangoue@matech-cameroun.com","494","24-05-2025 21:24:09","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_141","NOCINC0005098097","New-Marc=
he-Melen","","24-05-2025 20:58:58","24-05-2025 20:47:59","24-05-2025 20:55:=
54","Cascaded Incident from TTO5237486","Paul BIBOUM","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,no space to deploy m=
obile gen //grid power return","system","1386133","24-05-2025 20:58:58","MA=
TECH CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0005098038","An-=
Marche-Melen","IHS_YND_141","24-05-2025 20:50:05","24-05-2025 20:47:59","24=
-05-2025 22:04:52","Grid outage,no space to deploy mobile gen //grid power =
return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid outage,no space to deploy mobile gen //grid power return","gerard.=
tchangoue@matech-cameroun.com","127","24-05-2025 20:50:05","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005098006","Eto=
ug ebe Carrefour","","24-05-2025 20:43:13","24-05-2025 20:37:04","24-05-202=
5 20:43:41","Grid outage, Site went down before Gen start due to poor backu=
p // Gen started automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Gen started automatically","gerar=
d.tchangoue@matech-cameroun.com","370","24-05-2025 20:43:13","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005097725","M=
essassi 2","","24-05-2025 19:52:39","24-05-2025 19:52:31","24-05-2025 20:30=
:07","No power issue iste on grid with U=3D54.09v FME Synphorien (691316854=
) from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue ist=
e on grid with U=3D54.09v FME Synphorien (691316854) from Huawei is informe=
d","vanel.mbiada@matech-cameroun.com","10","24-05-2025 19:52:39","MATECH CM=
R"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005097515","N=
yom OCM","","24-05-2025 19:14:30","24-05-2025 19:11:18","24-05-2025 19:29:2=
3","ACTIVE//no power issue Ubaie:54.2V site on Gen, TX fme symphorien /6502=
57151 from huawei is informed","Fabrice Pouakam","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no pow=
er issue Ubaie:54.2V site on Gen, TX fme symphorien /650257151 from huawei =
is informed","vanel.mbiada@matech-cameroun.com","194","24-05-2025 19:14:30"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005097481","C=
omplexe-BEAC","","24-05-2025 19:04:29","24-05-2025 19:01:41","24-05-2025 19=
:12:58","Grid outage, Site went down before Gen start due to Poor battery b=
ackup // Grid return","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to Poor battery backup // Grid return","vanel.mbiada@matech-ca=
meroun.com","170","24-05-2025 19:04:29","MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0005097390","Nko=
abang MTN","","24-05-2025 18:36:06","24-05-2025 18:34:59","24-05-2025 18:36=
:59","Grid fluctuation, site went down because Gen started and Stopped due =
to Grid bad voltage//Grid stabilized","Mba Lazare Herve","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, s=
ite went down because Gen started and Stopped due to Grid bad voltage//Grid=
 stabilized","gerard.tchangoue@matech-cameroun.com","68","24-05-2025 18:36:=
06","MATECH CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0005097337","Omn=
isport-Rail","","24-05-2025 18:24:40","24-05-2025 18:22:04","24-05-2025 18:=
24:04","Site went down due to insufficiency of rectifiers  // Grid stabilis=
ed","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficiency of rectifiers  // Grid stabilise=
d","gerard.tchangoue@matech-cameroun.com","158","24-05-2025 18:24:40","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005097269","D=
amas","","24-05-2025 18:13:38","24-05-2025 18:04:31","24-05-2025 18:34:34",=
"Active// No power Issue Site on Grid Ubai =3D53,8 V, The FME The TX FME Mb=
ah Hosiah (674007438) is informed.","MINKA NICOLAS","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No=
 power Issue Site on Grid Ubai =3D53,8 V, The FME The TX FME Mbah Hosiah (6=
74007438) is informed.","vanel.mbiada@matech-cameroun.com","548","24-05-202=
5 18:13:38","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0005097247","Tam=
tam Weekend","","24-05-2025 18:10:51","24-05-2025 18:07:35","24-05-2025 18:=
25:35","Site went down due to Grid fluctuation and Gen overload // Grid ret=
urn","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Site went down due to Grid fluctuation and Gen overload // Grid retur=
n","gerard.tchangoue@matech-cameroun.com","197","24-05-2025 18:10:51","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005097241","A=
ccacia New","","24-05-2025 18:09:47","24-05-2025 18:04:37","24-05-2025 18:2=
0:14","Grid outage ,no space to deploy a mobil gen // grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
,no space to deploy a mobil gen // grid return","vanel.mbiada@matech-camero=
un.com","312","24-05-2025 18:09:47","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005097225","SAA=
 Entrance","","24-05-2025 18:07:52","24-05-2025 18:05:31","24-05-2025 18:07=
:31","Grid outage, site went down due to Grid bad voltage // GRID RETURN","=
Parker Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid outage, site went down due to Grid bad voltage // GRID R=
ETURN","gerard.tchangoue@matech-cameroun.com","142","24-05-2025 18:07:52","=
MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005097217","Ron=
d Point Express1114","","24-05-2025 18:06:10","24-05-2025 18:04:02","24-05-=
2025 18:39:02","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","ge=
rard.tchangoue@matech-cameroun.com","129","24-05-2025 18:06:10","MATECH CMR=
"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005097168","N=
koabang2","","24-05-2025 17:55:40","24-05-2025 17:54:20","24-05-2025 19:46:=
20","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","va=
nel.mbiada@matech-cameroun.com","81","24-05-2025 17:55:40","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005097165","Nko=
l-Mbanda","","24-05-2025 17:54:50","24-05-2025 17:47:44","24-05-2025 18:03:=
43","Grid outage,site went down due to Main generator faulty//grid power re=
turn","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Gener=
ator Faulty","Grid outage,site went down due to Main generator faulty//grid=
 power return","gerard.tchangoue@matech-cameroun.com","427","24-05-2025 17:=
54:50","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005097156","OBA=
M NGOLA OCM","","24-05-2025 17:53:15","24-05-2025 17:48:08","24-05-2025 19:=
27:08","Site went down due to insufficient rectifier on site//site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifier on site//site stabilised=
","gerard.tchangoue@matech-cameroun.com","308","24-05-2025 17:53:15","MATEC=
H CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005097082","OBA=
M NGOLA OCM","","24-05-2025 17:41:04","24-05-2025 17:36:58","24-05-2025 17:=
42:25","Site went down due to insufficient rectifier on site//site stabilis=
ed	","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficient rectifier on site//site stabilise=
d	","gerard.tchangoue@matech-cameroun.com","247","24-05-2025 17:41:04","MAT=
ECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0005096962","Clu=
b France","","24-05-2025 17:16:21","24-05-2025 17:15:08","24-05-2025 18:25:=
33","Grid only site, No space to deploy a MDG // Grid restored	","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site=
, No space to deploy a MDG // Grid restored	","gerard.tchangoue@matech-came=
roun.com","74","24-05-2025 17:16:21","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005096763","S=
apeur Mimboman","","24-05-2025 16:47:23","24-05-2025 15:06:06","24-05-2025 =
17:15:44","Site went down due to 02 rectifiers dysfunctionning // He resete=
d these rectifiers","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to 02 rectifiers dysfunctionnin=
g // He reseted these rectifiers","vanel.mbiada@matech-cameroun.com","6078"=
,"24-05-2025 16:47:23","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005096758","Sof=
avinc","","24-05-2025 16:46:31","24-05-2025 16:45:25","24-05-2025 17:03:25"=
,"Site went down because rectifiers disfunctionning// Site stabilized","MIN=
KA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down because rectifiers disfunctionning// Site stabilized","gerard.=
tchangoue@matech-cameroun.com","67","24-05-2025 16:46:31","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005096709","Nsi=
meyong","","24-05-2025 16:35:09","24-05-2025 16:26:55","24-05-2025 16:39:55=
","Grid outage, site went down because gen start and stopped with emergency=
 stop alarm // He manually start the gen(Investigation ongoing)","MINKA NIC=
OLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid=
 outage, site went down because gen start and stopped with emergency stop a=
larm // He manually start the gen(Investigation ongoing)","gerard.tchangoue=
@matech-cameroun.com","494","24-05-2025 16:35:09","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005096696","Mes=
sassi 2","","24-05-2025 16:31:23","24-05-2025 16:30:09","24-05-2025 16:33:5=
7","No power issue iste on grid with U=3D54.09v FME Synphorien (691316854) =
from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue iste =
on grid with U=3D54.09v FME Synphorien (691316854) from Huawei is informed"=
,"gerard.tchangoue@matech-cameroun.com","75","24-05-2025 16:31:23","MATECH =
CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005096650","Crf=
-Mbankolo-IHS","","24-05-2025 16:23:14","24-05-2025 16:16:58","24-05-2025 1=
6:24:49","(Very unstable) Site down due to insufficient rectifiers on site =
// site stabilised","Mboua Thierry","Equipment Repair","Passive","Rectifier=
","Rectifier Module","(Very unstable) Site down due to insufficient rectifi=
ers on site // site stabilised","gerard.tchangoue@matech-cameroun.com","377=
","24-05-2025 16:23:14","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005096567","N=
yom OCM","","24-05-2025 16:04:04","24-05-2025 15:09:53","24-05-2025 15:22:5=
0","ACTIVE//no power issue Ubaie:54.2V site on Gen, TX fme symphorien /6502=
57151 from huawei is informed","Fabrice Pouakam","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no pow=
er issue Ubaie:54.2V site on Gen, TX fme symphorien /650257151 from huawei =
is informed","vanel.mbiada@matech-cameroun.com","3252","24-05-2025 16:04:04=
","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005096519","Ron=
d Point Express1114","","24-05-2025 15:56:54","24-05-2025 15:47:49","24-05-=
2025 16:01:29","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","ge=
rard.tchangoue@matech-cameroun.com","546","24-05-2025 15:56:54","MATECH CMR=
"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0005096436","C=
lge-Advantiste","","24-05-2025 15:46:20","24-05-2025 15:38:12","24-05-2025 =
15:49:12","Site went down due to PWC dysfunction//Site stabilised","MINKA N=
ICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module Overload=
ed","Site went down due to PWC dysfunction//Site stabilised","vanel.mbiada@=
matech-cameroun.com","488","24-05-2025 15:46:20","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005096315","D=
amas","","24-05-2025 15:29:00","24-05-2025 15:20:41","24-05-2025 15:34:33",=
"Active// No power Issue Site on Grid Ubai =3D53,8 V, The FME The TX FME Mb=
ah Hosiah (674007438) is informed.","MINKA NICOLAS","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No=
 power Issue Site on Grid Ubai =3D53,8 V, The FME The TX FME Mbah Hosiah (6=
74007438) is informed.","vanel.mbiada@matech-cameroun.com","500","24-05-202=
5 15:29:00","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0005096313","Tam=
tam Weekend","","24-05-2025 15:28:43","24-05-2025 15:22:33","24-05-2025 15:=
46:03","Site went down due to Grid fluctuation and Gen overload // Grid ret=
urn","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Site went down due to Grid fluctuation and Gen overload // Grid retur=
n","gerard.tchangoue@matech-cameroun.com","1620","24-05-2025 15:28:43","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005096295","M=
ontee-Jouvence-II","","24-05-2025 15:26:54","24-05-2025 15:20:41","24-05-20=
25 15:36:23","No power issue on site, site on Grid with Ubaie=3D51.1V The T=
x Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site, site on Grid with Ubaie=3D51.1V The Tx Fm=
e Mbah Hosiah //674007438/ from HUAWEI is informed","vanel.mbiada@matech-ca=
meroun.com","375","24-05-2025 15:26:54","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0005096205","Odz=
a Minkan IHS","","24-05-2025 15:14:38","24-05-2025 15:07:19","24-05-2025 16=
:21:54","Grid fluctuation, Site went down because Gen failed to start due t=
o Grid bad voltage//  He bypassed Grid and started Gen manually","Albran By=
orel","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, Site went down because Gen failed to start due to Gr=
id bad voltage//  He bypassed Grid and started Gen manually","gerard.tchang=
oue@matech-cameroun.com","440","24-05-2025 15:14:38","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0005096192","Eto=
ug-Ebe 2","","24-05-2025 15:12:15","24-05-2025 15:05:06","24-05-2025 18:58:=
06","Grid outage, no space to deploy a mobil gen // Grid restoration","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, no space to deploy a mobil gen // Grid restoration","gerard.tchangoue@m=
atech-cameroun.com","430","24-05-2025 15:12:15","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005096189","M=
essassi 2","","24-05-2025 15:11:39","24-05-2025 15:10:01","24-05-2025 15:14=
:02","Grid outage site went down because Gen failed to start due to poor Ba=
ttery backup// GEN automatically started","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage si=
te went down because Gen failed to start due to poor Battery backup// GEN a=
utomatically started","vanel.mbiada@matech-cameroun.com","100","24-05-2025 =
15:11:39","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005096079","S=
imbock OCM","","24-05-2025 14:49:58","24-05-2025 14:46:49","24-05-2025 19:1=
2:39","Site went down due to work: Technician Njoya/690811271/LOUMANDE work=
ing on site (Swapp pwc)// End of work","Hyemafo Gildas","Equipment Replacem=
ent","Passive","Planned Activity","Planned Activity - Passive","Site went d=
own due to work: Technician Njoya/690811271/LOUMANDE working on site (Swapp=
 pwc)// End of work","vanel.mbiada@matech-cameroun.com","190","24-05-2025 1=
4:49:58","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0005096025","A=
bome","","24-05-2025 14:39:18","24-05-2025 14:37:01","24-05-2025 16:12:03",=
"Grid outage site went down because Gen failed to start due to Gen card fau=
lty // Gen Manually Started","MINKA NICOLAS","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen fa=
iled to start due to Gen card faulty // Gen Manually Started","vanel.mbiada=
@matech-cameroun.com","138","24-05-2025 14:39:18","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005095618","Eto=
ug ebe Carrefour","","24-05-2025 13:36:06","24-05-2025 13:28:00","24-05-202=
5 14:50:00","Grid outage site went down before gen started due to poor batt=
ery backup // Grid returned","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage site went down b=
efore gen started due to poor battery backup // Grid returned","christelle.=
ngonga@matech-cameroun.com","487","24-05-2025 13:36:06","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005095481","Nko=
abang Ebolmedjock","","24-05-2025 13:21:23","24-05-2025 13:17:12","24-05-20=
25 14:20:12","Grid outage, site went down because Gen stopped with alarm ""=
overcurrent""// He reset Gen card and Gen manually started","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage, site went down because Gen stopped with alarm ""overcurrent""// He re=
set Gen card and Gen manually started","franck.nkomot@matech-cameroun.com",=
"273","24-05-2025 13:21:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005095479","MEHANDAN=
","","24-05-2025 13:19:29","24-05-2025 13:15:41","24-05-2025 13:50:41","Cas=
caded Incident from TTO5234598","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
1400644","24-05-2025 13:19:29","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005095458","O=
dza II OCM","IHS_YND_528","24-05-2025 13:16:47","24-05-2025 13:15:41","24-0=
5-2025 13:50:41","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","christelle.ngonga@matech-cameroun.com","68","24-05-2025 13:16:=
47","MATECH CMR"
"Closed Complete","Site Down","T3180","IHS_YND_253","NOCINC0005095350","Clg=
e-Advantiste","","24-05-2025 13:01:41","24-05-2025 12:53:21","24-05-2025 13=
:00:42","Grid fluctuation,site went down because Gen failed to start due to=
 Grid bad voltage//Grid stabilised","MINKA NICOLAS","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation,site we=
nt down because Gen failed to start due to Grid bad voltage//Grid stabilise=
d","franck.nkomot@matech-cameroun.com","501","24-05-2025 13:01:41","MATECH =
CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0005095262","M=
aison-Blanche-IHS","","24-05-2025 12:43:59","24-05-2025 12:42:52","24-05-20=
25 19:08:27","Grid outage.no space to deploy mobile // Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.no space to deploy mobile // Grid return","christelle.ngonga@matech-camero=
un.com","68","24-05-2025 12:43:59","MATECH CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0005095255","O=
bobogo","","24-05-2025 12:43:14","24-05-2025 12:39:06","24-05-2025 12:57:29=
","","MINKA NICOLAS","Cascade Outage","Active","Cascade Active","Cascade Ac=
tive","Site impacted by CTR_773_Z_Efoulan-Pont(CTR-773) Not manage by IHS",=
"christelle.ngonga@matech-cameroun.com","1402788","24-05-2025 12:43:14","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005095253","E=
foulan","IHS_YND_155","24-05-2025 12:42:25","24-05-2025 12:39:06","24-05-20=
25 12:57:29","Site impacted by CTR_773_Z_Efoulan-Pont(CTR-773) Not manage b=
y IHS","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","Site impacted by CTR_773_Z_Efoul=
an-Pont(CTR-773) Not manage by IHS","christelle.ngonga@matech-cameroun.com"=
,"200","24-05-2025 12:42:25","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005095122","M=
ontee-Des-Soeurs","","24-05-2025 12:20:33","24-05-2025 12:16:26","24-05-202=
5 13:39:31","Grid outage site went down due to Gen overload (15kva,180A)//W=
e reduce load and gen manually started","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to =
Gen overload (15kva,180A)//We reduce load and gen manually started","christ=
elle.ngonga@matech-cameroun.com","249","24-05-2025 12:20:33","MATECH CMR"
"Closed Complete","Site Down","T0401","IHS_YND_205","NOCINC0005095063","Ton=
golo MTN","","24-05-2025 12:07:36","24-05-2025 12:01:28","24-05-2025 13:29:=
28","Site went down due to work done by Njoya(658849259) from OMNIUM (swapp=
er power cabinet)//End of works","Fabrice Pouakam","Equipment Replacement",=
"Passive","Planned Activity","Planned Activity - Passive","Site went down d=
ue to work done by Njoya(658849259) from OMNIUM (swapper power cabinet)//En=
d of works","franck.nkomot@matech-cameroun.com","368","24-05-2025 12:07:36"=
,"MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005095058","Nsi=
meyong","","24-05-2025 12:06:55","24-05-2025 12:03:41","24-05-2025 14:59:41=
","Grid outage, site went down because gen start and stopped with emergency=
 stop alarm // He manually start the gen(Investigation ongoing)","MINKA NIC=
OLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid=
 outage, site went down because gen start and stopped with emergency stop a=
larm // He manually start the gen(Investigation ongoing)","franck.nkomot@ma=
tech-cameroun.com","194","24-05-2025 12:06:55","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005095026","Crf=
-Mbankolo-IHS","","24-05-2025 12:01:05","24-05-2025 11:54:57","24-05-2025 1=
5:45:57","Site down due to insufficient rectifiers on site // site stabilis=
ed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site down due to insufficient rectifiers on site // site stabilised",=
"franck.nkomot@matech-cameroun.com","370","24-05-2025 12:01:05","MATECH CMR=
"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005094903","Nko=
lnda","","24-05-2025 11:33:20","24-05-2025 11:25:14","24-05-2025 12:26:42",=
"Grid outage ,site down because gen ran till fuel shortage // Site refueled=
","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid ou=
tage ,site down because gen ran till fuel shortage // Site refueled","franc=
k.nkomot@matech-cameroun.com","488","24-05-2025 11:33:20","MATECH CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0005094672","S=
cience","","24-05-2025 11:02:56","24-05-2025 10:57:49","24-05-2025 11:46:49=
","Grid outage, site went down because gen failed to start due to PWC ZTE m=
alfunction // Grid restoration","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site w=
ent down because gen failed to start due to PWC ZTE malfunction // Grid res=
toration","ludivine.ngamaleu@ihstowers.com","308","24-05-2025 11:02:56","MA=
TECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0005094469","ELO=
UMDEM CARRIERE 2","","24-05-2025 10:36:23","24-05-2025 10:28:17","24-05-202=
5 10:34:44","Grid outage, Site down due to poor battery backup // Gen start=
 automatically","Fanda Brice","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site down due to poor battery b=
ackup // Gen start automatically","christelle.ngonga@matech-cameroun.com","=
488","24-05-2025 10:36:23","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005094457","Eto=
ug ebe biscuiterie","","24-05-2025 10:35:10","24-05-2025 10:14:02","24-05-2=
025 10:34:23","Grid fluctuation, site went down because Gen failed to start=
 due to Grid bad voltage and no RCP on site// he bypass the Grid and Gen ma=
nually started","Hyemafo Gildas","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation, site went down because Ge=
n failed to start due to Grid bad voltage and no RCP on site// he bypass th=
e Grid and Gen manually started","christelle.ngonga@matech-cameroun.com","1=
268","24-05-2025 10:35:10","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005094391","M=
essassi 2","","24-05-2025 10:23:04","24-05-2025 10:19:48","24-05-2025 11:02=
:12","No power issue iste on grid with U=3D54.09v FME Synphorien (691316854=
) from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue ist=
e on grid with U=3D54.09v FME Synphorien (691316854) from Huawei is informe=
d","ludivine.ngamaleu@ihstowers.com","198","24-05-2025 10:23:04","MATECH CM=
R"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005094367","M=
vog-Manga","","24-05-2025 10:19:42","24-05-2025 10:04:35","24-05-2025 11:18=
:14","Grid outage , Gen fails to start due to unknow alarme // Gen card res=
eted and manual started","Albran Byorel","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid outage , Gen fails to start due to unkno=
w alarme // Gen card reseted and manual started","christelle.ngonga@matech-=
cameroun.com","908","24-05-2025 10:19:42","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005094363","E=
bogo","","24-05-2025 10:18:59","24-05-2025 10:04:50","24-05-2025 10:21:24",=
"Grid outage, site went down before Gen start due poor backup battery // Ge=
n automaticaly started","Siligap Boris","Equipment Repair","Passive","ACDG =
Gen","DG Low Battery","Grid outage, site went down before Gen start due poo=
r backup battery // Gen automaticaly started","christelle.ngonga@matech-cam=
eroun.com","851","24-05-2025 10:18:59","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005094298","A=
fanoya","","24-05-2025 10:09:12","24-05-2025 09:46:38","24-05-2025 11:22:38=
","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage site went down due to Gen overload (17KVA, 240A) SS =
HIS Felix Zambe is informed and confirmed// Grid return","ludivine.ngamaleu=
@ihstowers.com","1412909","24-05-2025 10:09:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005094225","Nkolfon =
Cimencam","","24-05-2025 09:59:44","24-05-2025 09:46:38","24-05-2025 11:22:=
38","Cascaded Incident from TTO5233264","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down du=
e to Gen overload (17KVA, 240A) SS HIS Felix Zambe is informed and confirme=
d// Grid return","system","1412908","24-05-2025 09:59:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005094224","Ahala","=
","24-05-2025 09:59:44","24-05-2025 09:46:38","24-05-2025 11:22:38","Cascad=
ed Incident from TTO5233264","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage site went down due to Gen ov=
erload (17KVA, 240A) SS HIS Felix Zambe is informed and confirmed// Grid re=
turn","system","1412909","24-05-2025 09:59:44","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005094215","M=
eyo","IHS_YND_257, IHS_YND_313, IHS_YND_762","24-05-2025 09:58:43","24-05-2=
025 09:46:38","24-05-2025 11:22:38","Grid outage site went down due to Gen =
overload (17KVA, 240A) SS HIS Felix Zambe is informed and confirmed// Grid =
return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage site went down due to Gen overload (17KVA, 240A) SS HI=
S Felix Zambe is informed and confirmed// Grid return","ludivine.ngamaleu@i=
hstowers.com","726","24-05-2025 09:58:43","MATECH CMR"
"Closed Complete","Site Down","T0629","IHS_YND_058","NOCINC0005094210","Mvo=
lye","","24-05-2025 09:56:51","24-05-2025 09:15:40","24-05-2025 10:11:08","=
No power issue U=3D52,7 v site on grid .  TX FME Lionel steve/655184876 fro=
m Huawei is informed .","MINKA NICOLAS","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=3D52,7=
 v site on grid .  TX FME Lionel steve/655184876 from Huawei is informed ."=
,"christelle.ngonga@matech-cameroun.com","2472","24-05-2025 09:56:51","MATE=
CH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005094206","Ebo=
go","","24-05-2025 09:56:03","24-05-2025 09:08:55","24-05-2025 09:59:42","A=
ctive// No Power issue on site Ubaie 53.2V site on Grid, TX FME Julien /693=
095849 from Huawei is informed","Siligap Boris","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Pow=
er issue on site Ubaie 53.2V site on Grid, TX FME Julien /693095849 from Hu=
awei is informed","christelle.ngonga@matech-cameroun.com","2829","24-05-202=
5 09:56:03","MATECH CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0005094017","MES=
SAME NDONGO 1162","","24-05-2025 09:24:49","24-05-2025 08:53:39","24-05-202=
5 10:41:39","Grid outage,gen failed to start due to Gen card malfunctioning=
//he reseted the card and he started Gen manually","MINKA NICOLAS","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,gen fai=
led to start due to Gen card malfunctioning//he reseted the card and he sta=
rted Gen manually","olivier.kwedi@ihstowers.com","1871","24-05-2025 09:24:4=
9","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_213","NOCINC0005093803","Nkolmess=
eng","","24-05-2025 09:05:40","24-05-2025 08:58:13","24-05-2025 10:08:07","=
Cascaded Incident from TTO5232816","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Cascaded Incident from TTO5232816",=
"system","1415714","24-05-2025 09:05:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_217","NOCINC0005093806","Abom",""=
,"24-05-2025 09:05:40","24-05-2025 08:58:13","24-05-2025 10:08:07","Cascade=
d Incident from TTO5232544","Siligap Boris","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage,DG stopped due with alarm ""oi=
l pressure""// gen card reset  and Gen manuallyHe put son ","system","14157=
15","24-05-2025 09:05:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_184","NOCINC0005093804","Nkolmess=
eng","IHS_YND_215, IHS_YND_213, IHS_YND_214, IHS_YND_217","24-05-2025 09:05=
:40","24-05-2025 08:58:13","24-05-2025 10:08:07","Grid outage,DG stopped du=
e with alarm ""oil pressure""// gen card reset  and Gen manuallyHe put son =
","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid outage,DG stopped due with alarm ""oil pressure""// gen card re=
set  and Gen manuallyHe put son ","system","6302","24-05-2025 09:05:40","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_214","NOCINC0005093805","Nkolmess=
eng-II","","24-05-2025 09:05:40","24-05-2025 08:58:13","24-05-2025 10:08:07=
","Cascaded Incident from TTO5232544","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,DG stopped due with =
alarm ""oil pressure""// gen card reset  and Gen manuallyHe put son ","syst=
em","1415714","24-05-2025 09:05:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_215","NOCINC0005093802","Eleveurs=
","","24-05-2025 09:05:39","24-05-2025 08:58:13","24-05-2025 10:08:07","Cas=
caded Incident from TTO5232544","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Cascaded Incident from TTO5232544","sy=
stem","1415715","24-05-2025 09:05:39","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005093711","MBA=
LNGONG LYCEE","","24-05-2025 09:00:25","24-05-2025 08:46:11","24-05-2025 09=
:02:11","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down be=
cause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informe=
d and confirmed // Grid returned","olivier.kwedi@ihstowers.com","856","24-0=
5-2025 09:00:25","MATECH CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0005093652","N=
kongtock","","24-05-2025 08:52:36","24-05-2025 08:44:32","24-05-2025 10:37:=
06"," No power issue on site Ubaie=3D48,7V site on Gen The Tx FME Etienne//=
695033981 from Huawei is informed","Kemeni Franklin","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No power =
issue on site Ubaie=3D48,7V site on Gen The Tx FME Etienne//695033981 from =
Huawei is informed","ludivine.ngamaleu@ihstowers.com","485","24-05-2025 08:=
52:36","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0005093567","B=
iteng-Maetur","","24-05-2025 08:37:43","24-05-2025 08:06:32","24-05-2025 12=
:40:44","Active//No power issue on site Ubaie =3D52.1V site on Grid The TX =
FME Henri (699949693) from Huawei is informed","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site Ubaie =3D52.1V site on Grid The TX FME He=
nri (699949693) from Huawei is informed","ludivine.ngamaleu@ihstowers.com",=
"1872","24-05-2025 08:37:43","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005093548","Nsi=
meyong","","24-05-2025 08:32:20","24-05-2025 08:18:13","24-05-2025 09:32:43=
","Grid outage , site down because ge was on stop mode. // gen manually sta=
rted","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","outage , site down because ge was on stop mode. // gen manually =
started","christelle.ngonga@matech-cameroun.com","847","24-05-2025 08:32:20=
","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005093414","Men=
dong3","","24-05-2025 08:08:55","24-05-2025 08:07:34","24-05-2025 09:00:34"=
,"Grid Outage No space to deploy a MDG //Grid Restored","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid Outage No space to=
 deploy a MDG //Grid Restored","christelle.ngonga@matech-cameroun.com","82"=
,"24-05-2025 08:08:55","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005093405","SIM=
BOCK BONAMBAPE","","24-05-2025 08:06:59","24-05-2025 08:05:52","24-05-2025 =
08:09:52","Grid outage, site went down due to Gen Overload (20kva, 350A) SS=
 IHS Felix ZAMBE confirmed // Site stabilisation","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went d=
own due to Gen Overload (20kva, 350A) SS IHS Felix ZAMBE confirmed // Site =
stabilisation","christelle.ngonga@matech-cameroun.com","68","24-05-2025 08:=
06:59","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0005093403","Aba=
ng","IHS_YND_794, IHS_YND_289","24-05-2025 08:06:32","24-05-2025 07:57:20",=
"24-05-2025 12:37:17","Active//No power issue site on Grid with U=3D55.5V ,=
The FME TX Henri (691145055) from Huawei is informed","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue site on Grid with U=3D55.5V ,The FME TX He=
nri (691145055) from Huawei is informed","olivier.kwedi@ihstowers.com","553=
","24-05-2025 08:06:32","MATECH CMR"
"Closed Complete","Site Down","T2564","IHS_YND_739","NOCINC0005093399","NKO=
LMESSING rue Manguier","","24-05-2025 08:05:31","24-05-2025 08:04:25","24-0=
5-2025 10:27:25","Grid outage, site went down due to grid bad voltage// he =
started gen manually","Siligap Boris","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","Grid outage, site went down due to gri=
d bad voltage// he started gen manually","christelle.ngonga@matech-cameroun=
.com","67","24-05-2025 08:05:31","MATECH CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0005093379","Nko=
abang entree carriere","","24-05-2025 08:04:52","24-05-2025 08:03:44","24-0=
5-2025 08:07:44","Grid outage, Site went down before Gen start due to poor =
backup // Gen started Automatically","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site =
went down before Gen start due to poor backup // Gen started Automatically"=
,"christelle.ngonga@matech-cameroun.com","69","24-05-2025 08:04:52","MATECH=
 CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005093374","Nko=
ulou Carriere carrefourt","","24-05-2025 08:03:34","24-05-2025 07:57:20","2=
4-05-2025 07:59:20","","Mba Lazare Herve","Cascade Outage","Active","Cascad=
e Active","Cascade Active","Active//No power issue site on Grid with U=3D55=
.5V ,The FME TX Henri (691145055) from Huawei is informed","christelle.ngon=
ga@matech-cameroun.com","1419260","24-05-2025 08:03:34","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005093370","Nko=
langaa","","24-05-2025 08:02:46","24-05-2025 07:57:20","24-05-2025 08:24:20=
","Site down due to disjonction in the DC Box // DC box CB reamed, site on =
grid.","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Casca=
de Active","Site down due to disjonction in the DC Box // DC box CB reamed,=
 site on grid.","christelle.ngonga@matech-cameroun.com","1419260","24-05-20=
25 08:02:46","MATECH CMR"
"Closed Complete","Site Down","CTR_369","IHS_YND_019","NOCINC0005093356","H=
otel de Ville Yde","","24-05-2025 08:00:52","24-05-2025 07:35:36","24-05-20=
25 10:31:36","Grid outage, site went down due to grid fluctuations // SITE =
stabilised","Paul BIBOUM","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","Grid outage, site went down due to grid fluctuatio=
ns // SITE stabilised","ludivine.ngamaleu@ihstowers.com","1518","24-05-2025=
 08:00:52","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005093285","Nko=
l-Mebanga","","24-05-2025 07:45:56","24-05-2025 07:26:48","24-05-2025 12:11=
:48","Solar only, Site went Down due to low Solar // Solar return","Parker =
Tchoup","Equipment Repair","Passive","Solar","Solar Panel Issue","Solar onl=
y, Site went Down due to low Solar // Solar return","olivier.kwedi@ihstower=
s.com","1148","24-05-2025 07:45:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_141","NOCINC0005093247","New-Marc=
he-Melen","","24-05-2025 07:44:01","24-05-2025 05:58:27","24-05-2025 06:30:=
27","Cascaded Incident from TTO5231629","Paul BIBOUM","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,no space to deploy m=
obile gen// grid power return","system","1426235","24-05-2025 07:44:01","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005093027","Nkongtoc=
k","","24-05-2025 06:55:30","24-05-2025 04:22:33","24-05-2025 06:01:28","Ca=
scaded Incident from TTO5231198","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen start and sto=
pped due to Gen card Faulty  //   Gen started by force mode","system","1431=
897","24-05-2025 06:55:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005093013","Bastos-N=
ylon","","24-05-2025 06:54:08","24-05-2025 04:22:33","24-05-2025 06:01:28",=
"Cascaded Incident from TTO5231198","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen start and st=
opped due to Gen card Faulty  //   Gen started by force mode","system","143=
1903","24-05-2025 06:54:08","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005093004","O=
LAMA","","24-05-2025 06:51:05","24-05-2025 06:45:50","24-05-2025 11:50:50",=
"Active: No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Hen=
ri (699949693) from Huawei is informed","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: N=
o power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (699949=
693) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","316","24-0=
5-2025 06:51:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0005092744","Mendong =
Maeture","","24-05-2025 06:08:37","24-05-2025 06:01:39","24-05-2025 06:44:3=
9","Cascaded Incident from TTO5231643","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Gen overload, Sit=
e went down due to low level of water in the radiator // Water add and Gen =
start manually","system","1426046","24-05-2025 06:08:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0005092745","Montee-J=
ouvence","","24-05-2025 06:08:37","24-05-2025 06:01:39","24-05-2025 06:44:3=
9","Cascaded Incident from TTO5231643","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Gen overload, Sit=
e went down due to low level of water in the radiator // Water add and Gen =
start manually","system","1426046","24-05-2025 06:08:37","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0005092738","M=
endong","IHS_YND_569, IHS_YND_236","24-05-2025 06:05:58","24-05-2025 06:01:=
39","24-05-2025 06:44:39","Grid outage, Gen overload, Site went down due to=
 low level of water in the radiator // Water add and Gen start manually","H=
yemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","G=
rid outage, Gen overload, Site went down due to low level of water in the r=
adiator // Water add and Gen start manually","vanel.mbiada@matech-cameroun.=
com","260","24-05-2025 06:05:58","MATECH CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0005092726","A=
n-Marche-Melen","IHS_YND_141","24-05-2025 06:02:43","24-05-2025 05:58:27","=
24-05-2025 06:30:27","Grid outage,no space to deploy mobile gen// grid powe=
r return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Is=
sue","Grid outage,no space to deploy mobile gen// grid power return","vanel=
.mbiada@matech-cameroun.com","257","24-05-2025 06:02:43","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005092706","ODZ=
A MINKAN EDIBI ASSI","","24-05-2025 05:56:17","24-05-2025 05:53:54","24-05-=
2025 07:58:54","Grid fluctuation, Site went down because Gen started and st=
opped due to Grid bad voltage and No RCP on site // He bypassed Grid and st=
arted Gen manually","Albran Byorel","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Grid fluctuation, Site went down because=
 Gen started and stopped due to Grid bad voltage and No RCP on site // He b=
ypassed Grid and started Gen manually","cedric.tiani@matech-cameroun.com","=
144","24-05-2025 05:56:17","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005092656","O=
dza II OCM","","24-05-2025 05:38:05","24-05-2025 05:32:54","24-05-2025 07:3=
1:54","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Site stabilised","Albran Byorel","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Grid outage, site went down=
 because gen failed to start due to PWC ZTE malfunction // Site stabilised"=
,"vanel.mbiada@matech-cameroun.com","313","24-05-2025 05:38:05","MATECH CMR=
"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005092633","Sof=
avinc","","24-05-2025 05:29:58","24-05-2025 05:29:53","24-05-2025 13:33:38"=
,"Site went down due to insufficiency of rectifiers on site // He reduced t=
he load","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficiency of rectifiers on site // He =
reduced the load","cedric.tiani@matech-cameroun.com","6","24-05-2025 05:29:=
58","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005092605","O=
LAMA","","24-05-2025 05:21:12","24-05-2025 05:16:48","24-05-2025 05:20:13",=
"No power issue on site Ubaie =3D54.7V site on Grid. The TX FME Henri (6999=
49693) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubaie =3D54.7V site on Grid. The TX FME Henri (699949693) from Huawei=
 is informed","vanel.mbiada@matech-cameroun.com","265","24-05-2025 05:21:12=
","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005092380","Eto=
ug ebe Meweulo","","24-05-2025 04:35:35","24-05-2025 04:34:09","24-05-2025 =
05:59:46","Grid fluctuation site went down because Gen started and stopped =
due to Grid bad voltage // Grid stabilised","Hyemafo Gildas","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
n site went down because Gen started and stopped due to Grid bad voltage //=
 Grid stabilised","cedric.tiani@matech-cameroun.com","87","24-05-2025 04:35=
:35","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005092369","Bar=
riere","","24-05-2025 04:31:06","24-05-2025 04:29:48","24-05-2025 05:01:44"=
,"Grid outage . site went down because Gen failed to start due to fuel filt=
er damaged//We replace fuel filter and gen manually started","Hyemafo Gilda=
s","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Filter","Grid outag=
e . site went down because Gen failed to start due to fuel filter damaged//=
We replace fuel filter and gen manually started","cedric.tiani@matech-camer=
oun.com","79","24-05-2025 04:31:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0005092362","Entree C=
ite Verte","","24-05-2025 04:29:53","24-05-2025 04:22:33","24-05-2025 06:01=
:28","Cascaded Incident from TTO5231198","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen start and=
 stopped due to Gen card Faulty  //   Gen started by force mode","system","=
1431903","24-05-2025 04:29:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0005092360","Tsinga",=
"","24-05-2025 04:29:53","24-05-2025 04:22:33","24-05-2025 06:01:28","Casca=
ded Incident from TTO5231198","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Bad Grid Voltage ,Gen start and stopped =
due to Gen card Faulty  //   Gen started by force mode","system","1431902",=
"24-05-2025 04:29:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0005092361","Dagobert=
","","24-05-2025 04:29:53","24-05-2025 04:22:33","24-05-2025 06:01:28","Cas=
caded Incident from TTO5231198","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen start=
 and stopped due to Gen card Faulty  //   Gen started by force mode","syste=
m","1431897","24-05-2025 04:29:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0005092358","Yona Hot=
el","","24-05-2025 04:29:52","24-05-2025 04:22:33","24-05-2025 06:01:28","C=
ascaded Incident from TTO5231198","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen sta=
rt and stopped due to Gen card Faulty  //   Gen started by force mode","sys=
tem","1431905","24-05-2025 04:29:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0005092359","Crf-Nkol=
bisson","","24-05-2025 04:29:52","24-05-2025 04:22:33","24-05-2025 06:01:28=
","Cascaded Incident from TTO5231198","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen=
 start and stopped due to Gen card Faulty  //   Gen started by force mode",=
"system","1431899","24-05-2025 04:29:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005092357","Bastos B=
ethesda","","24-05-2025 04:29:52","24-05-2025 04:22:33","24-05-2025 06:01:2=
8","Cascaded Incident from TTO5231198","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen start and=
 stopped due to Gen card Faulty  //   Gen started by force mode","system","=
1431900","24-05-2025 04:29:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0005092355","BATA Mok=
olo OCM","","24-05-2025 04:29:52","24-05-2025 04:22:33","24-05-2025 06:01:2=
8","Cascaded Incident from TTO5231198","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Bad Grid Voltage ,Gen start and stopped due =
to Gen card Faulty  //   Gen started by force mode","system","1431899","24-=
05-2025 04:29:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0005092356","Meyong-M=
eyeme","","24-05-2025 04:29:52","24-05-2025 04:22:33","24-05-2025 06:01:28"=
,"Cascaded Incident from TTO5231198","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen =
start and stopped due to Gen card Faulty  //   Gen started by force mode","=
system","1431904","24-05-2025 04:29:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0005092350","AFEME NO=
RD","","24-05-2025 04:29:51","24-05-2025 04:22:33","24-05-2025 06:01:28","C=
ascaded Incident from TTO5231198","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen sta=
rt and stopped due to Gen card Faulty  //   Gen started by force mode","sys=
tem","1431896","24-05-2025 04:29:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0005092351","Nkomkana=
 2","","24-05-2025 04:29:51","24-05-2025 04:22:33","24-05-2025 06:01:28","C=
ascaded Incident from TTO5231198","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen start and stop=
ped due to Gen card Faulty  //   Gen started by force mode","system","14319=
01","24-05-2025 04:29:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0005092354","Oyomaban=
g Ecole","","24-05-2025 04:29:51","24-05-2025 04:22:33","24-05-2025 06:01:2=
8","Cascaded Incident from TTO5231198","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Passive","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Ge=
n start and stopped due to Gen card Faulty  //   Gen started by force mode"=
,"system","1431904","24-05-2025 04:29:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0005092353","Nkomkana=
","","24-05-2025 04:29:51","24-05-2025 04:22:33","24-05-2025 06:01:28","Cas=
caded Incident from TTO5231198","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Bad Grid Voltage ,Gen start and stopped due to Gen =
card Faulty  //   Gen started by force mode","system","1431902","24-05-2025=
 04:29:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0005092352","Cite-Ver=
te","","24-05-2025 04:29:51","24-05-2025 04:22:33","24-05-2025 06:01:28","C=
ascaded Incident from TTO5231198","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Bad Grid Voltage ,Gen start and stopped due to Ge=
n card Faulty  //   Gen started by force mode","system","1431896","24-05-20=
25 04:29:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0005092348","Nkolbi-B=
oss","","24-05-2025 04:29:50","24-05-2025 04:22:33","24-05-2025 06:01:28","=
Cascaded Incident from TTO5231198","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen st=
art and stopped due to Gen card Faulty  //   Gen started by force mode","sy=
stem","1431898","24-05-2025 04:29:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005092349","Golf Qua=
ter","","24-05-2025 04:29:50","24-05-2025 04:22:33","24-05-2025 06:01:28","=
Cascaded Incident from TTO5231198","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Bad Grid Voltage ,Gen start and sto=
pped due to Gen card Faulty  //   Gen started by force mode","system","1431=
900","24-05-2025 04:29:50","MATECH CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0005092339","O=
yomabang OCM","IHS_YND_273, IHS_YND_220, IHS_YND_519, IHS_YND_138, IHS_YND_=
202, IHS_YND_200, IHS_YND_686, IHS_YND_126, IHS_YND_559, IHS_YND_230, IHS_Y=
ND_563, IHS_YND_271, IHS_YND_232, IHS_YND_127, IHS_YND_349, IHS_YND_286, IH=
S_YND_543","24-05-2025 04:25:48","24-05-2025 04:22:33","24-05-2025 06:01:28=
","fme GAEL is on site","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Bad Grid Voltage ,Gen start and sto=
pped due to Gen card Faulty  //   Gen started by force mode","vanel.mbiada@=
matech-cameroun.com","196","24-05-2025 04:25:48","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0005092312","Nlo=
ngkak","","24-05-2025 04:17:59","24-05-2025 04:12:49","24-05-2025 04:24:43"=
,"Grid outage, Site down due to poor battery backup // Gen start automatica=
lly","Delor Telezing","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, Site down due to poor battery backup //=
 Gen start automatically","cedric.tiani@matech-cameroun.com","311","24-05-2=
025 04:17:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005092300","Messassi=
 okolo","","24-05-2025 04:16:39","24-05-2025 04:05:55","24-05-2025 04:21:45=
","Cascaded Incident from TTO5231120","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage Site went down bec=
ause Landlord forbidden to start the Gen due to Noise//Grid return","system=
","1432876","24-05-2025 04:16:39","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005092279","S=
atcom","","24-05-2025 04:10:14","24-05-2025 03:55:58","24-05-2025 04:15:55"=
,"Grid fluctuation, Site went down because Gen failed to start due to Grid =
bad voltage //Grid stabilised","Delor Telezing","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","Grid fluctuation, Site went =
down because Gen failed to start due to Grid bad voltage //Grid stabilised"=
,"vanel.mbiada@matech-cameroun.com","857","24-05-2025 04:10:14","MATECH CMR=
"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005092268","E=
MANA BILICK CITY","IHS_YND_279","24-05-2025 04:07:09","24-05-2025 04:05:55"=
,"24-05-2025 04:27:13","Grid outage Site went down because Landlord forbidd=
en to start the Gen due to Noise//Grid return","Fabrice Pouakam","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid outage Site wen=
t down because Landlord forbidden to start the Gen due to Noise//Grid retur=
n","vanel.mbiada@matech-cameroun.com","75","24-05-2025 04:07:09","MATECH CM=
R"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005092265","M=
EHANDAN","","24-05-2025 04:05:34","24-05-2025 03:57:30","24-05-2025 04:05:3=
8","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, site went down because gen failed to start due to P=
WC ZTE malfunction // Site stabilised","vanel.mbiada@matech-cameroun.com","=
1433375","24-05-2025 04:05:34","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005092258","SIM=
BOCK BONAMBAPE","","24-05-2025 04:03:16","24-05-2025 03:56:58","24-05-2025 =
04:00:09","Grid outage, site went down due to Gen Overload (20kva, 350A) SS=
 IHS Felix ZAMBE confirmed // Site stabilisation","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went d=
own due to Gen Overload (20kva, 350A) SS IHS Felix ZAMBE confirmed // Site =
stabilisation","cedric.tiani@matech-cameroun.com","379","24-05-2025 04:03:1=
6","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005092255","NTU=
I TOWN","","24-05-2025 04:02:29","24-05-2025 03:57:13","24-05-2025 05:19:56=
","Grid outage,site went down due to disjunction  CB(63A) rectifier in PWC/=
/He rearmed it","Parker Tchoup","Equipment Repair","Passive","Rectifier","R=
ectifier - Circuit Breaker","Grid outage,site went down due to disjunction =
 CB(63A) rectifier in PWC//He rearmed it","cedric.tiani@matech-cameroun.com=
","317","24-05-2025 04:02:29","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005092248","Mes=
sassi 2","","24-05-2025 04:01:31","24-05-2025 03:57:17","24-05-2025 04:08:3=
9","Grid outage, Site down due to poor battery backup // Gen start automati=
cally","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, Site down due to poor battery backup=
 // Gen start automatically","cedric.tiani@matech-cameroun.com","255","24-0=
5-2025 04:01:31","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005092246","Odz=
a II OCM","IHS_YND_528","24-05-2025 04:00:43","24-05-2025 03:57:30","24-05-=
2025 04:05:38","Grid outage, site went down because gen failed to start due=
 to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site =
went down because gen failed to start due to PWC ZTE malfunction // Site st=
abilised","cedric.tiani@matech-cameroun.com","194","24-05-2025 04:00:43","M=
ATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005092243","Ron=
d Point Express1114","","24-05-2025 03:59:51","24-05-2025 03:55:39","24-05-=
2025 04:01:44","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","ce=
dric.tiani@matech-cameroun.com","253","24-05-2025 03:59:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0005092166","Donga","=
","24-05-2025 03:32:55","24-05-2025 03:09:02","24-05-2025 04:45:04","Cascad=
ed Incident from TTO5230936","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by  Mbanjock Camrail","system"=
,"1436250","24-05-2025 03:32:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0005092104","Dong",""=
,"24-05-2025 03:15:28","24-05-2025 03:09:02","24-05-2025 04:45:04","","Park=
er Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active","Sit=
e impacted by  Mbanjock Camrail","system","1436250","24-05-2025 03:15:28","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0005092103","Nguila",=
"IHS_YND_434, IHS_YND_444","24-05-2025 03:15:28","24-05-2025 03:09:02","24-=
05-2025 04:45:04","","Parker Tchoup","Customer Equipment Failure","Active",=
"Active Equipment Failure","Affected by 3rd Party Site","Site impacted by  =
Mbanjock Camrail","system","9118","24-05-2025 03:15:28","MATECH CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0005091833","M=
BIMBIM","","24-05-2025 01:21:17","24-05-2025 01:14:02","24-05-2025 11:16:02=
","Active//No power issue, site is on Gen with Ubaie=3D48V. The Fme TX Greg=
oire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue, site is on Gen with Ubaie=3D48V. The Fme TX Gregoire (65=
4547479) from Huawei is informed","vanel.mbiada@matech-cameroun.com","437",=
"24-05-2025 01:21:17","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005091729","B=
arriere","","24-05-2025 00:47:35","24-05-2025 00:45:26","24-05-2025 02:22:5=
4","Grid outage, Site went down because gen started and stopped  with alarm=
 *OVERCURRENT*//He reset the Gen card and manually started the Gen","Hyemaf=
o Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, Site went down because gen started and stopped  with alarm *OVE=
RCURRENT*//He reset the Gen card and manually started the Gen","vanel.mbiad=
a@matech-cameroun.com","131","24-05-2025 00:47:35","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005091714","S=
apeur Mimboman","","24-05-2025 00:43:17","24-05-2025 00:42:05","24-05-2025 =
00:44:49","Grid fluctuation ,site went down because Gen fails to start due =
to grid bad voltage //Grid stabilisation","Mba Lazare Herve","Grid Supply",=
"Passive","Grid","National Grid - Power Cable Faulty","Grid fluctuation ,si=
te went down because Gen fails to start due to grid bad voltage //Grid stab=
ilisation","vanel.mbiada@matech-cameroun.com","73","24-05-2025 00:43:17","M=
ATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005091648","Par=
adis Hotel","","24-05-2025 00:27:11","24-05-2025 00:25:58","24-05-2025 01:2=
3:01","Site went down due to MPR DYSFONNCTION on site / He reset the MPR","=
Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Cabinet"=
,"Site went down due to MPR DYSFONNCTION on site / He reset the MPR","cedri=
c.tiani@matech-cameroun.com","74","24-05-2025 00:27:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0005091633","Entree C=
ite Verte","","24-05-2025 00:23:44","24-05-2025 00:10:22","24-05-2025 01:13=
:07","Cascaded Incident from TTO5230368","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because gen fail=
ed to start due to grid bad voltage // He bypassed grid and manually start =
the gen","system","1446847","24-05-2025 00:23:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0005091632","Dagobert=
","","24-05-2025 00:23:44","24-05-2025 00:10:22","24-05-2025 01:13:07","Cas=
caded Incident from TTO5230368","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down because gen =
failed to start due to grid bad voltage // He bypassed grid and manually st=
art the gen","system","1446851","24-05-2025 00:23:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005091631","Nkongtoc=
k","","24-05-2025 00:23:44","24-05-2025 00:10:22","24-05-2025 01:13:07","Ca=
scaded Incident from TTO5230368","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because gen failed t=
o start due to grid bad voltage // He bypassed grid and manually start the =
gen","system","1446846","24-05-2025 00:23:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0005091628","Yona Hot=
el","","24-05-2025 00:23:43","24-05-2025 00:10:22","24-05-2025 01:13:07","C=
ascaded Incident from TTO5230368","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because ge=
n failed to start due to grid bad voltage // He bypassed grid and manually =
start the gen","system","1446845","24-05-2025 00:23:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005091627","Bastos B=
ethesda","","24-05-2025 00:23:43","24-05-2025 00:10:22","24-05-2025 01:13:0=
7","Cascaded Incident from TTO5230368","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because gen fail=
ed to start due to grid bad voltage // He bypassed grid and manually start =
the gen","system","1446848","24-05-2025 00:23:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0005091629","Crf-Nkol=
bisson","","24-05-2025 00:23:43","24-05-2025 00:10:22","24-05-2025 01:13:07=
","Cascaded Incident from TTO5230368","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Site went down becaus=
e gen failed to start due to grid bad voltage // He bypassed grid and manua=
lly start the gen","system","1446849","24-05-2025 00:23:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0005091630","Tsinga",=
"","24-05-2025 00:23:43","24-05-2025 00:10:22","24-05-2025 01:13:07","Casca=
ded Incident from TTO5230368","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down because gen failed to sta=
rt due to grid bad voltage // He bypassed grid and manually start the gen",=
"system","1446850","24-05-2025 00:23:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005091624","Bastos-N=
ylon","","24-05-2025 00:23:42","24-05-2025 00:10:22","24-05-2025 01:13:07",=
"Cascaded Incident from TTO5230368","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because gen failed =
to start due to grid bad voltage // He bypassed grid and manually start the=
 gen","system","1446846","24-05-2025 00:23:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0005091623","Oyomaban=
g Ecole","","24-05-2025 00:23:42","24-05-2025 00:10:22","24-05-2025 01:13:0=
7","Cascaded Incident from TTO5230368","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Passive","Cascade Passive","Cascade Passive","Site went down becau=
se gen failed to start due to grid bad voltage // He bypassed grid and manu=
ally start the gen","system","1446851","24-05-2025 00:23:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0005091625","BATA Mok=
olo OCM","","24-05-2025 00:23:42","24-05-2025 00:10:22","24-05-2025 01:13:0=
7","Cascaded Incident from TTO5230368","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Site went down because gen failed to start d=
ue to grid bad voltage // He bypassed grid and manually start the gen","sys=
tem","1446848","24-05-2025 00:23:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0005091626","Meyong-M=
eyeme","","24-05-2025 00:23:42","24-05-2025 00:10:22","24-05-2025 01:13:07"=
,"Cascaded Incident from TTO5230368","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Site went down because=
 gen failed to start due to grid bad voltage // He bypassed grid and manual=
ly start the gen","system","1446844","24-05-2025 00:23:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0005091619","AFEME NO=
RD","","24-05-2025 00:23:41","24-05-2025 00:10:22","24-05-2025 01:13:07","C=
ascaded Incident from TTO5230368","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because ge=
n failed to start due to grid bad voltage // He bypassed grid and manually =
start the gen","system","1446849","24-05-2025 00:23:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0005091621","Cite-Ver=
te","","24-05-2025 00:23:41","24-05-2025 00:10:22","24-05-2025 01:13:07","C=
ascaded Incident from TTO5230368","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Site went down because gen failed to start due to=
 grid bad voltage // He bypassed grid and manually start the gen","system",=
"1446850","24-05-2025 00:23:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005091618","Golf Qua=
ter","","24-05-2025 00:23:41","24-05-2025 00:10:22","24-05-2025 01:13:07","=
Cascaded Incident from TTO5230368","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because gen failed t=
o start due to grid bad voltage // He bypassed grid and manually start the =
gen","system","1446849","24-05-2025 00:23:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0005091622","Nkomkana=
","","24-05-2025 00:23:41","24-05-2025 00:10:22","24-05-2025 01:13:07","Cas=
caded Incident from TTO5230368","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Site went down because gen failed to start due to g=
rid bad voltage // He bypassed grid and manually start the gen","system","1=
446845","24-05-2025 00:23:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0005091620","Nkomkana=
 2","","24-05-2025 00:23:41","24-05-2025 00:10:22","24-05-2025 01:13:07","C=
ascaded Incident from TTO5230368","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because gen failed to=
 start due to grid bad voltage // He bypassed grid and manually start the g=
en","system","1446845","24-05-2025 00:23:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0005091617","Nkolbi-B=
oss","","24-05-2025 00:23:40","24-05-2025 00:10:22","24-05-2025 01:13:07","=
Cascaded Incident from TTO5230368","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down because g=
en failed to start due to grid bad voltage // He bypassed grid and manually=
 start the gen","system","1446847","24-05-2025 00:23:40","MATECH CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0005091591","O=
yomabang OCM","IHS_YND_273, IHS_YND_220, IHS_YND_519, IHS_YND_138, IHS_YND_=
202, IHS_YND_200, IHS_YND_686, IHS_YND_126, IHS_YND_559, IHS_YND_230, IHS_Y=
ND_563, IHS_YND_271, IHS_YND_232, IHS_YND_127, IHS_YND_349, IHS_YND_286, IH=
S_YND_543","24-05-2025 00:16:32","24-05-2025 00:10:22","24-05-2025 01:13:07=
","Site went down because gen failed to start due to grid bad voltage // He=
 bypassed grid and manually start the gen","TIENTCHEU NZETCHIEU GAEL","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site w=
ent down because gen failed to start due to grid bad voltage // He bypassed=
 grid and manually start the gen","cedric.tiani@matech-cameroun.com","371",=
"24-05-2025 00:16:32","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0005091098","Eto=
udi","","23-05-2025 22:54:40","23-05-2025 22:53:22","23-05-2025 22:54:17","=
Grid fluctuation ,site went down because Gen fails to start due to grid bad=
 voltage //Grid stabilisation","Fabrice Pouakam","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Grid fluctuation ,site went=
 down because Gen fails to start due to grid bad voltage //Grid stabilisati=
on","cedric.tiani@matech-cameroun.com","79","23-05-2025 22:54:40","MATECH C=
MR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005090915","E=
ssomba","","23-05-2025 22:30:03","23-05-2025 22:26:01","23-05-2025 22:30:52=
","Site went down because 03/06 rectifiers dysfunctionned // Grid stablised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down because 03/06 rectifiers dysfunctionned // Grid stabl=
ised","vanel.mbiada@matech-cameroun.com","243","23-05-2025 22:30:03","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005090526","M=
essassi 2","","23-05-2025 21:38:49","23-05-2025 21:32:41","23-05-2025 21:40=
:27","No power issue iste on grid with U=3D53.9v FME Synphorien (691316854)=
 from Huawei is informed	","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue ist=
e on grid with U=3D53.9v FME Synphorien (691316854) from Huawei is informed=
	","gerard.tchangoue@matech-cameroun.com","369","23-05-2025 21:38:49","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0005090502","A=
battoir","","23-05-2025 21:35:10","23-05-2025 21:20:03","23-05-2025 21:54:3=
0","Grid outage, Main Generator faulty // Grid return","Fabrice Pouakam","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, Main Generator faulty // Grid return","gerard.tchangoue@matech-cameroun=
.com","973","23-05-2025 21:35:10","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005090379","Par=
adis Hotel","","23-05-2025 21:18:25","23-05-2025 21:12:19","23-05-2025 21:4=
9:52","Site went down due to MPR DYSFONNCTION on site / He reset the MPR","=
Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Cabinet"=
,"Site went down due to MPR DYSFONNCTION on site / He reset the MPR","gerar=
d.tchangoue@matech-cameroun.com","367","23-05-2025 21:18:25","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005090321","Nko=
langaa","","23-05-2025 21:09:16","23-05-2025 21:01:06","24-05-2025 00:39:51=
","Site down due to disjonction in the DC Box // DC box CB reamed, site on =
grid.","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Cir=
cuit Breaker Tripped","Site down due to disjonction in the DC Box // DC box=
 CB reamed, site on grid.","gaelle.njiofack@matech-cameroun.com","491","23-=
05-2025 21:09:16","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005090104","NYO=
M 2 IHS","","23-05-2025 20:40:14","23-05-2025 20:34:03","23-05-2025 21:12:3=
1","Grid outage, Site went down before Gen start due to poor backup // Gen =
started automaticaly","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Gen started automaticaly","gaelle.njiofack=
@matech-cameroun.com","372","23-05-2025 20:40:14","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005089974","B=
arriere","","23-05-2025 20:14:25","23-05-2025 20:06:17","23-05-2025 23:01:5=
8","Grid outage . site went downbecause Gen failed to start due to fuel and=
 oil  filter damaged//We replace fuel and oil filter and gen manually start=
ed","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel F=
ilter","Grid outage . site went downbecause Gen failed to start due to fuel=
 and oil  filter damaged//We replace fuel and oil filter and gen manually s=
tarted","gerard.tchangoue@matech-cameroun.com","490","23-05-2025 20:14:25",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0005089707","Oyomaban=
g Ecole","","23-05-2025 19:39:52","23-05-2025 19:23:47","23-05-2025 19:36:4=
7","Cascaded Incident from TTO5228176","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Active","Cascade Active","Cascade Active","Active//No power issue =
site is on Gen with Ubaie=3D53,89V. TX FME Mohamadou // 699949072 from Huaw=
ei is informed","system","1457501","23-05-2025 19:39:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005089708","Bastos B=
ethesda","","23-05-2025 19:39:52","23-05-2025 19:23:47","23-05-2025 19:36:4=
7","Cascaded Incident from TTO5228176","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue site is on =
Gen with Ubaie=3D53,89V. TX FME Mohamadou // 699949072 from Huawei is infor=
med","system","1457500","23-05-2025 19:39:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0005089705","Nkomkana=
 2","","23-05-2025 19:39:51","23-05-2025 19:23:47","23-05-2025 19:36:47","C=
ascaded Incident from TTO5228176","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue site is on Gen w=
ith Ubaie=3D53,89V. TX FME Mohamadou // 699949072 from Huawei is informed",=
"system","1457501","23-05-2025 19:39:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0005089706","Cite-Ver=
te","","23-05-2025 19:39:51","23-05-2025 19:23:47","23-05-2025 19:36:47","C=
ascaded Incident from TTO5228176","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Active//No power issue site is on Gen with Ubaie=3D5=
3,89V. TX FME Mohamadou // 699949072 from Huawei is informed","system","145=
7500","23-05-2025 19:39:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_233","NOCINC0005089704","Oyomaban=
g OCM","","23-05-2025 19:39:51","23-05-2025 19:23:47","23-05-2025 19:36:47"=
,"Cascaded Incident from TTO5228176","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","Active//No power issue si=
te is on Gen with Ubaie=3D53,89V. TX FME Mohamadou // 699949072 from Huawei=
 is informed","system","1457500","23-05-2025 19:39:51","MATECH CMR"
"Closed Complete","Site Down","CTR_122","IHS_YND_230","NOCINC0005089593","M=
eyong-Meyeme","IHS_YND_233, IHS_YND_138, IHS_YND_202, IHS_YND_686, IHS_YND_=
563","23-05-2025 19:32:18","23-05-2025 19:23:47","23-05-2025 19:36:47","Act=
ive//No power issue site is on Gen with Ubaie=3D53,89V. TX FME Mohamadou //=
 699949072 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue site is on Gen with Ubaie=3D53,89V. TX FME Mohamadou=
 // 699949072 from Huawei is informed","gerard.tchangoue@matech-cameroun.co=
m","512","23-05-2025 19:32:18","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0005089355","Eto=
ug ebe Carrefour","","23-05-2025 19:09:30","23-05-2025 19:03:22","23-05-202=
5 19:09:09","	Grid outage site went down before gen started due to poor bat=
tery backup // Grid returned","Hyemafo Gildas","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","	Grid outage site went down=
 before gen started due to poor battery backup // Grid returned","gaelle.nj=
iofack@matech-cameroun.com","369","23-05-2025 19:09:30","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005089230","O=
dza II OCM","","23-05-2025 18:47:58","23-05-2025 18:44:45","23-05-2025 19:5=
0:43","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Site stabilisation","Albran Byorel","Equipment Repair","P=
assive","Rectifier","Rectifier Module Overloaded","Grid outage, site went d=
own because gen failed to start due to PWC ZTE malfunction // Site stabilis=
ation","gerard.tchangoue@matech-cameroun.com","195","23-05-2025 18:47:58","=
MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005089196","M=
essassi 2","","23-05-2025 18:42:32","23-05-2025 18:35:24","23-05-2025 18:50=
:43","No power issue iste on grid with U=3D53.9v FME Synphorien (691316854)=
 from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue iste=
 on grid with U=3D53.9v FME Synphorien (691316854) from Huawei is informed"=
,"gerard.tchangoue@matech-cameroun.com","430","23-05-2025 18:42:32","MATECH=
 CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0005088754","Nko=
abang entree carriere","","23-05-2025 17:58:33","23-05-2025 17:51:28","23-0=
5-2025 18:06:28","Grid outage, Site went down before Gen start due to poor =
backup // Gen started Automatically","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site =
went down before Gen start due to poor backup // Gen started Automatically"=
,"gerard.tchangoue@matech-cameroun.com","426","23-05-2025 17:58:33","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005088732","B=
arriere","","23-05-2025 17:54:53","23-05-2025 17:47:44","23-05-2025 18:02:4=
4","Grid outage, Site went down before Gen start due to fuel shortage // Re=
fueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, Site went down before Gen start due to fuel shortage // =
Refueling done","gerard.tchangoue@matech-cameroun.com","431","23-05-2025 17=
:54:53","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005088649","Nta=
ba","","23-05-2025 17:34:18","23-05-2025 17:29:09","23-05-2025 18:39:09","s=
ite went down due to replacement of PWC (12Kw 250A) with another A new 36KW=
 PWC // End of work","Delor Telezing","Equipment Replacement","Passive","Pl=
anned Activity","Planned Activity - Passive","site went down due to replace=
ment of PWC (12Kw 250A) with another A new 36KW PWC // End of work","gaelle=
.njiofack@matech-cameroun.com","310","23-05-2025 17:34:18","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005088575","Nko=
lnda","","23-05-2025 17:21:39","23-05-2025 17:19:04","23-05-2025 17:32:01",=
"site down due to work of SS Blaise Raoul /IHS (secures the transmission)//=
 End of work","Albran Byorel","Equipment Replacement","Passive","Planned Ac=
tivity","Planned Activity - Site Inspection","site down due to work of SS B=
laise Raoul /IHS (secures the transmission)// End of work","gaelle.njiofack=
@matech-cameroun.com","156","23-05-2025 17:21:39","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0005088406","M=
bankomo IHS","","23-05-2025 16:51:45","23-05-2025 16:43:32","23-05-2025 17:=
38:32","Grid outage, Site went down before Gen start due to poor backup // =
Gen started Manually","Fanda Brice","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen started Manually","gerard.tchangoue@matech=
-cameroun.com","494","23-05-2025 16:51:45","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005088320","Bar=
riere","","23-05-2025 16:37:10","23-05-2025 16:34:04","23-05-2025 17:05:28"=
,"Grid outage, Site went down before Gen start due to fuel shortage // Refu=
eling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage, Site went down before Gen start due to fuel shortage // Re=
fueling done","gaelle.njiofack@matech-cameroun.com","187","23-05-2025 16:37=
:10","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005088317","MBA=
LNGONG LYCEE","","23-05-2025 16:36:18","23-05-2025 16:16:07","23-05-2025 18=
:04:52","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down be=
cause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informe=
d and confirmed // Grid returned","gaelle.njiofack@matech-cameroun.com","12=
13","23-05-2025 16:36:18","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005088115","AKA=
K Nkozoa","","23-05-2025 16:13:21","23-05-2025 16:11:13","23-05-2025 17:29:=
11"," site went down because Gen started and stopped to start due to grid b=
ad voltage // He bypassed Grid and started Gen manually","Fabrice Pouakam",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"," site w=
ent down because Gen started and stopped to start due to grid bad voltage /=
/ He bypassed Grid and started Gen manually","gaelle.njiofack@matech-camero=
un.com","129","23-05-2025 16:13:21","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005088098","E=
toudi","","23-05-2025 16:08:21","23-05-2025 16:05:13","23-05-2025 17:19:25"=
," site went down because Gen started and stopped to start due to grid fluc=
tuation// He bypassed Grid and started Gen manually","Fabrice Pouakam","Gri=
d Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue"," s=
ite went down because Gen started and stopped to start due to grid fluctuat=
ion// He bypassed Grid and started Gen manually","gerard.tchangoue@matech-c=
ameroun.com","189","23-05-2025 16:08:21","MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0005088080","Nko=
abang MTN","","23-05-2025 16:01:52","23-05-2025 10:26:26","23-05-2025 10:33=
:40","Backtracking.  Grid fluctuation, site went down because Gen started a=
nd Stopped due to Grid bad voltage//Grid stabilized","Mba Lazare Herve","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Back=
tracking.  Grid fluctuation, site went down because Gen started and Stopped=
 due to Grid bad voltage//Grid stabilized","gerard.tchangoue@matech-camerou=
n.com","20127","23-05-2025 16:01:52","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0005088073","H=
-General-Yde","","23-05-2025 15:59:03","23-05-2025 15:56:57","23-05-2025 16=
:22:01","Grid outage,gen failed to start due to ""high temp"" alarm//we add=
 water and gen manually started (investigation ongoing)	","Siligap Boris","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage,gen failed to start due to ""high temp"" alarm//we=
 add water and gen manually started (investigation ongoing)	","gaelle.njiof=
ack@matech-cameroun.com","126","23-05-2025 15:59:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005087996","Carrefou=
rt Nkomo","","23-05-2025 15:46:55","23-05-2025 15:42:54","23-05-2025 15:49:=
54","Cascaded Incident from TTO5226426","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site went down due to insuf=
ficient rectifiers  // site stabilised","system","1470359","23-05-2025 15:4=
6:55","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005087987","N=
komo","IHS_YND_174","23-05-2025 15:44:59","23-05-2025 15:42:54","23-05-2025=
 15:49:54","site went down due to insufficient rectifiers  // site stabilis=
ed","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier =
Module","site went down due to insufficient rectifiers  // site stabilised"=
,"gaelle.njiofack@matech-cameroun.com","126","23-05-2025 15:44:59","MATECH =
CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005087984","C=
rf-Nsam","","23-05-2025 15:44:16","23-05-2025 15:39:51","23-05-2025 16:48:5=
1","Active//No power issue on site Ubaie =3D52.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D52.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","266=
","23-05-2025 15:44:16","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005087972","N=
YOM 2 IHS","","23-05-2025 15:41:42","23-05-2025 15:37:20","23-05-2025 16:32=
:13","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automaticaly","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen started automaticaly","gaelle.njiofa=
ck@matech-cameroun.com","263","23-05-2025 15:41:42","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005087915","E=
ssomba","","23-05-2025 15:32:56","23-05-2025 15:27:48","23-05-2025 16:17:48=
","Site went down because 03/06 rectifiers dysfunctionned // Grid restorati=
on","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down because 03/06 rectifiers dysfunctionned // Grid res=
toration","gaelle.njiofack@matech-cameroun.com","309","23-05-2025 15:32:56"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0005087767","O=
lezoa OCM","","23-05-2025 15:12:54","23-05-2025 15:06:47","23-05-2025 16:39=
:23","Grid outage, no space to deploy mobile gen // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no=
 space to deploy mobile gen//grid return","gerard.tchangoue@matech-cameroun=
.com","368","23-05-2025 15:12:54","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005087560","Ngo=
usso Vallee","","23-05-2025 14:50:58","23-05-2025 14:40:59","23-05-2025 16:=
06:50","	Grid outage, Gen failed to start due to alarm ""Undervoltage"" // =
He reset DG card and started DG manually","Siligap Boris","Equipment Repair=
","Passive","ACDG Gen","ACDG - Under Voltage","	Grid outage, Gen failed to =
start due to alarm ""Undervoltage"" // He reset DG card and started DG manu=
ally","loic.noumsi@matech-cameroun.com","600","23-05-2025 14:50:58","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0005087479","N=
kolbi-Boss","IHS_YND_271, IHS_YND_286","23-05-2025 14:36:48","23-05-2025 14=
:27:59","23-05-2025 15:13:43","Grid fluctuations, site went down due to Gri=
d bad voltage // He bypassed Grid and started Gen manually","TIENTCHEU NZET=
CHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuations, site went down due to Grid bad voltage // He =
bypassed Grid and started Gen manually","gerard.tchangoue@matech-cameroun.c=
om","530","23-05-2025 14:36:48","MATECH CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0005087466","Y=
ona Hotel","","23-05-2025 14:34:37","23-05-2025 14:27:59","23-05-2025 15:13=
:43","Site impacted by Nkolbi-Boss (CTR_333)","TIENTCHEU NZETCHIEU GAEL","C=
ascade Outage","Passive","Cascade Passive","Cascade Passive","Grid fluctuat=
ions, site went down due to Grid bad voltage // He bypassed Grid and starte=
d Gen manually","gerard.tchangoue@matech-cameroun.com","1474735","23-05-202=
5 14:34:37","MATECH CMR"
"Closed Complete","Site Down","CTR_255","IHS_YND_286","NOCINC0005087387","D=
agobert","","23-05-2025 14:20:25","23-05-2025 14:27:59","23-05-2025 15:13:4=
3","Site impacted by Nkolbi-Boss (CTR_333)","TIENTCHEU NZETCHIEU GAEL","Cas=
cade Outage","Passive","Cascade Passive","Cascade Passive","Grid fluctuatio=
ns, site went down due to Grid bad voltage // He bypassed Grid and started =
Gen manually","nadjia.njaya@ihstowers.com","1474734","23-05-2025 14:20:25",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005086964","E=
lig-Edzoa","","23-05-2025 13:05:48","23-05-2025 13:00:20","23-05-2025 13:34=
:30","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
site went down due to replacement of PWC (12Kw 250A) with another A new 36K=
W PWC // End of work	","christelle.ngonga@matech-cameroun.com","1479873","2=
3-05-2025 13:05:48","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005086954","N=
taba","IHS_YND_133","23-05-2025 13:04:33","23-05-2025 13:00:20","23-05-2025=
 13:39:54","site went down due to replacement of PWC (12Kw 250A) with anoth=
er A new 36KW PWC // End of work	","Delor Telezing","Equipment Replacement"=
,"Passive","Planned Activity","Planned Activity - Passive","site went down =
due to replacement of PWC (12Kw 250A) with another A new 36KW PWC // End of=
 work	","christelle.ngonga@matech-cameroun.com","254","23-05-2025 13:04:33"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005086892","E=
mana lycee 2","IHS_YND_274","23-05-2025 12:50:34","23-05-2025 12:46:25","23=
-05-2025 13:04:13","Grid outage , site went down because Gen failed to star=
ted due to poor battery backup , // Grid returned.","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","DG Low Battery","Grid outage , site wen=
t down because Gen failed to started due to poor battery backup , // Grid r=
eturned.","christelle.ngonga@matech-cameroun.com","250","23-05-2025 12:50:3=
4","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005086887","E=
mana Lycee","","23-05-2025 12:49:39","23-05-2025 12:46:25","23-05-2025 13:0=
4:13","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage , site went down because Gen failed to started =
due to poor battery backup , // Grid returned.","christelle.ngonga@matech-c=
ameroun.com","1480690","23-05-2025 12:49:39","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005086883","C=
hapelle-Nsimeyong","","23-05-2025 12:48:53","23-05-2025 12:18:25","24-05-20=
25 16:27:57","TTO5231778","MINKA NICOLAS","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","TTO5231778","christelle.ngonga@matech-camero=
un.com","1482336","23-05-2025 12:48:53","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005086878","A=
ccacia New","","23-05-2025 12:48:09","23-05-2025 12:18:25","24-05-2025 16:3=
7:47","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"DO Matech Andre EKO is on site working // End of work","christelle.ngonga@=
matech-cameroun.com","1482335","23-05-2025 12:48:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005086765","MEHANDAN=
","","23-05-2025 12:24:06","23-05-2025 12:18:46","23-05-2025 13:04:46","","=
Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Site whent down due to plan work. SS IHS was on site for securing trans=
mission//End of work","system","1482317","23-05-2025 12:24:06","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005086763","Odz=
a II OCM","","23-05-2025 12:23:33","23-05-2025 12:18:46","23-05-2025 13:04:=
46","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Site whent down due to plan work. SS IHS was on site for securi=
ng transmission//End of work","franck.nkomot@matech-cameroun.com","1482319"=
,"23-05-2025 12:23:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0005086757","Odza Min=
kan IHS","","23-05-2025 12:22:59","23-05-2025 12:18:46","23-05-2025 13:04:4=
6","Cascaded Incident from TTO5225065","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site whent down due to plan wor=
k. SS IHS was on site for securing transmission//End of work","system","148=
2317","23-05-2025 12:22:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0005086758","ODZA MIN=
KAN EDIBI ASSI","","23-05-2025 12:22:59","23-05-2025 12:18:46","23-05-2025 =
13:04:46","Cascaded Incident from TTO5225065","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site whent down due to p=
lan work. SS IHS was on site for securing transmission//End of work","syste=
m","1482318","23-05-2025 12:22:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0005086756","Mehanda =
1","","23-05-2025 12:22:58","23-05-2025 12:18:46","23-05-2025 13:04:46","Ca=
scaded Incident from TTO5225065","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site whent down due to plan work. SS =
IHS was on site for securing transmission//End of work","system","1482318",=
"23-05-2025 12:22:58","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005086754","Nko=
lnda","IHS_YND_528, IHS_YND_746, IHS_YND_527, IHS_YND_715, IHS_YND_749","23=
-05-2025 12:22:01","23-05-2025 12:18:46","23-05-2025 13:04:46","Site whent =
down due to plan work. SS IHS was on site for securing transmission//End of=
 work","Albran Byorel","Installation Activity","Passive","Planned Activity"=
,"Installation Activity","Site whent down due to plan work. SS IHS was on s=
ite for securing transmission//End of work","franck.nkomot@matech-cameroun.=
com","196","23-05-2025 12:22:01","MATECH CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0005086751","N=
kol-Mbanda","IHS_YND_148, IHS_YND_562","23-05-2025 12:21:34","23-05-2025 12=
:18:25","24-05-2025 16:37:47","DO Matech Andre EKO is on site working // En=
d of work","MINKA NICOLAS","Equipment Replacement","Passive","Planned Activ=
ity","Planned Activity - Passive","DO Matech Andre EKO is on site working /=
/ End of work","christelle.ngonga@matech-cameroun.com","190","23-05-2025 12=
:21:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0005086467","Messassi=
 2","","23-05-2025 11:24:05","23-05-2025 06:01:41","23-05-2025 06:38:52","B=
actraking No power issue iste on grid with U=3D53.9v FME Synphorien (691316=
854) from Huawei is informed ","Fabrice Pouakam","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Bactraking No =
power issue iste on grid with U=3D53.9v FME Synphorien (691316854) from Hua=
wei is informed ","christelle.ngonga@matech-cameroun.com","19346","23-05-20=
25 11:24:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0005086457","Nkoulou =
Carriere carrefourt","","23-05-2025 11:22:43","23-05-2025 06:29:19","23-05-=
2025 07:28:30","Backtraking. Grid outage, Site went down due to insufficien=
cy of rectifiers//Site stablilsed","Mba Lazare Herve","Equipment Repair","P=
assive","Rectifier","Rectifier Module","Backtraking. Grid outage, Site went=
 down due to insufficiency of rectifiers//Site stablilsed","christelle.ngon=
ga@matech-cameroun.com","17605","23-05-2025 11:22:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0005086454","Mvog-Man=
ga","","23-05-2025 11:21:31","23-05-2025 06:47:06","23-05-2025 07:28:18","B=
actraking : site down because ,(1/6) rectififiers was faulty //  Another re=
ctifier has been connected  and volttage will be stable in few hours","Albr=
an Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","Bac=
traking : site down because ,(1/6) rectififiers was faulty //  Another rect=
ifier has been connected  and volttage will be stable in few hours","christ=
elle.ngonga@matech-cameroun.com","16467","23-05-2025 11:21:31","MATECH CMR"
"Closed Complete","Site Down","T0920","IHS_YND_416","NOCINC0005086419","Ngw=
opi Boga","","23-05-2025 11:17:51","23-05-2025 08:59:23","23-05-2025 09:31:=
56","Grid outage , site went down before Gen started due to poor battery ba=
ckup // Grid return Power","Kemeni Franklin","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage , site went down =
before Gen started due to poor battery backup // Grid return Power","christ=
elle.ngonga@matech-cameroun.com","8309","23-05-2025 11:17:51","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005086223","O=
kola OCM","","23-05-2025 10:47:46","23-05-2025 10:39:38","23-05-2025 10:51:=
38","Grid  fluctuation , site went down due to Grid fluctuations  // Gen ma=
nually put on ","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","=
National Grid - Unstable Grid Supply Issue","Grid  fluctuation , site went =
down due to Grid fluctuations  // Gen manually put on ","christelle.ngonga@=
matech-cameroun.com","489","23-05-2025 10:47:46","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0005086199","MEH=
ANDAN","","23-05-2025 10:43:41","23-05-2025 10:34:37","23-05-2025 10:48:37"=
,"","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascade Act=
ive","Active: No power issue on site Ubaie =3D54.4V site on Grid. The TX FM=
E Lionnel Adhex (655184876) from Huawei is informed","franck.nkomot@matech-=
cameroun.com","1482248","23-05-2025 10:43:41","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005086195","Odz=
a II OCM","IHS_YND_528","23-05-2025 10:42:45","23-05-2025 10:34:37","23-05-=
2025 10:48:37","Active: No power issue on site Ubaie =3D54.4V site on Grid.=
 The TX FME Lionnel Adhex (655184876) from Huawei is informed","Albran Byor=
el","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active: No power issue on site Ubaie =3D54.4V site on Grid.=
 The TX FME Lionnel Adhex (655184876) from Huawei is informed","franck.nkom=
ot@matech-cameroun.com","489","23-05-2025 10:42:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0005086159","Odza Min=
kan IHS","","23-05-2025 10:39:25","23-05-2025 10:32:14","23-05-2025 10:40:1=
4","Cascaded Incident from TTO5224416","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site whent down due to plan wor=
k. SS IHS was on site for securing transmission//End of work","system","148=
2387","23-05-2025 10:39:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0005086160","ODZA MIN=
KAN EDIBI ASSI","","23-05-2025 10:39:25","23-05-2025 10:32:14","23-05-2025 =
10:40:14","Cascaded Incident from TTO5224416","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site whent down due to p=
lan work. SS IHS was on site for securing transmission//End of work","syste=
m","1482388","23-05-2025 10:39:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0005086158","Mehanda =
1","","23-05-2025 10:39:25","23-05-2025 10:32:14","23-05-2025 10:40:14","Ca=
scaded Incident from TTO5224416","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site whent down due to plan work. SS =
IHS was on site for securing transmission//End of work","system","1482388",=
"23-05-2025 10:39:25","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005086153","Nko=
lnda","IHS_YND_746, IHS_YND_715, IHS_YND_749","23-05-2025 10:38:32","23-05-=
2025 10:32:14","23-05-2025 10:40:14","Site whent down due to plan work. SS =
IHS was on site for securing transmission//End of work","Albran Byorel","In=
stallation Activity","Passive","Planned Activity","Installation Activity","=
Site whent down due to plan work. SS IHS was on site for securing transmiss=
ion//End of work","franck.nkomot@matech-cameroun.com","379","23-05-2025 10:=
38:32","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0005086131","C=
amp-Sic-Tsinga","","23-05-2025 10:34:27","23-05-2025 10:26:39","23-05-2025 =
10:26:40","","","Cascade Outage","Active","Cascade Active","Cascade Active"=
,"Site impacted by CNDH CTR_046 wich is not under IHS","christelle.ngonga@m=
atech-cameroun.com","1482715","23-05-2025 10:34:27","MATECH CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0005086125","C=
NDH","","23-05-2025 10:33:32","23-05-2025 10:26:18","23-05-2025 10:26:20","=
Wrongly logged ticket","Paul BIBOUM","Incorrectly Logged Tickets","Error","=
Error","Error","Wrongly logged ticket","christelle.ngonga@matech-cameroun.c=
om","435","23-05-2025 10:33:32","MATECH CMR"
"Closed Complete","Site Down","CTR_110","IHS_YND_028","NOCINC0005086116","H=
-Central","IHS_YND_010, IHS_YND_083, IHS_YND_087","23-05-2025 10:32:47","23=
-05-2025 10:26:39","23-05-2025 11:20:40","Site impacted by CNDH CTR_046 wic=
h is not under IHS","Paul BIBOUM","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","Affected by 3rd Party Site","Site impacted by CNDH=
 CTR_046 wich is not under IHS","christelle.ngonga@matech-cameroun.com","36=
9","23-05-2025 10:32:47","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0005086113","H=
-Progres","","23-05-2025 10:32:19","23-05-2025 10:26:39","23-05-2025 10:26:=
40","","","Cascade Outage","Active","Cascade Active","Cascade Active","Site=
 impacted by CNDH CTR_046 wich is not under IHS","christelle.ngonga@matech-=
cameroun.com","1482714","23-05-2025 10:32:19","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005086104","C=
NR","","23-05-2025 10:31:39","23-05-2025 10:26:39","23-05-2025 10:26:40",""=
,"Mboua Thierry","Cascade Outage","Active","Cascade Active","Cascade Active=
","Site impacted by CNDH CTR_046 wich is not under IHS","christelle.ngonga@=
matech-cameroun.com","1482715","23-05-2025 10:31:39","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005086024","Sof=
avinc","","23-05-2025 10:18:41","23-05-2025 10:14:26","23-05-2025 10:20:26"=
,"Active: No power issue, site is on Gen with Ubaie=3D56.4V, TX Henri (6999=
49693) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No powe=
r issue, site is on Gen with Ubaie=3D56.4V, TX Henri (699949693) from Huawe=
i is informed","franck.nkomot@matech-cameroun.com","256","23-05-2025 10:18:=
41","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005085956","N=
koabang2","","23-05-2025 10:01:33","23-05-2025 09:59:08","23-05-2025 12:55:=
56","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","ch=
ristelle.ngonga@matech-cameroun.com","147","23-05-2025 10:01:33","MATECH CM=
R"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0005085929","E=
zezang","","23-05-2025 09:58:25","23-05-2025 09:56:13","23-05-2025 09:56:25=
","Wrongly logged ticket","Parker Tchoup","Incorrectly Logged Tickets","Err=
or","Error","Error","Wrongly logged ticket","christelle.ngonga@matech-camer=
oun.com","133","23-05-2025 09:58:25","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005085674","Nko=
lbisson IITA LP","","23-05-2025 09:15:45","23-05-2025 09:13:28","23-05-2025=
 09:34:28","Grid Only, No space to deploy // Grid restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space=
 to deploy // Grid restored","franck.nkomot@matech-cameroun.com","138","23-=
05-2025 09:15:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005085413","Eseka To=
wn","","23-05-2025 08:33:55","23-05-2025 07:46:37","23-05-2025 09:08:57","C=
ascaded Incident from TTO5223385","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,Site went down because=
 Gen start and stopped due to Gen card dysfunction  //  He reset the Gen ca=
rd and manually started the Gen","system","1492121","23-05-2025 08:33:55","=
MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005085407","Nko=
lbisson IITA LP","","23-05-2025 08:29:50","23-05-2025 08:24:37","23-05-2025=
 08:35:37","Grid Only, No space to deploy // Grid restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space=
 to deploy // Grid restored","franck.nkomot@matech-cameroun.com","314","23-=
05-2025 08:29:50","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0005085369","C=
rf-Nkolbisson","","23-05-2025 08:20:06","23-05-2025 08:18:43","23-05-2025 0=
9:13:42","Grid fluctuation, site went down because gen fails to start due t=
o grid bad voltage // Gen permanently put on.","TIENTCHEU NZETCHIEU GAEL","=
Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue",=
"Grid fluctuation, site went down because gen fails to start due to grid ba=
d voltage // Gen permanently put on.","christelle.ngonga@matech-cameroun.co=
m","84","23-05-2025 08:20:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005085230","Song-bon=
g","","23-05-2025 07:51:02","23-05-2025 07:46:37","23-05-2025 09:08:57","Ca=
scaded Incident from TTO5223385","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,Site went down because =
Gen start and stopped due to Gen card dysfunction  //  He reset the Gen car=
d and manually started the Gen","system","1492121","23-05-2025 07:51:02","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005085223","E=
seka OCM","IHS_YND_378, IHS_YND_453","23-05-2025 07:49:44","23-05-2025 07:4=
6:37","23-05-2025 09:08:57","Grid outage,Site went down because Gen start a=
nd stopped due to Gen card dysfunction  //  He reset the Gen card and manua=
lly started the Gen","Kemeni Franklin","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage,Site went down because Gen start an=
d stopped due to Gen card dysfunction  //  He reset the Gen card and manual=
ly started the Gen","christelle.ngonga@matech-cameroun.com","188","23-05-20=
25 07:49:44","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0005084963","Nko=
lbisson IITA LP","","23-05-2025 07:42:23","23-05-2025 07:32:15","23-05-2025=
 07:42:15","Grid Only, No space to deploy // Grid restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space=
 to deploy // Grid restored","franck.nkomot@matech-cameroun.com","609","23-=
05-2025 07:42:23","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005084795","B=
arriere","","23-05-2025 06:56:02","23-05-2025 06:54:49","23-05-2025 07:58:4=
6","No power issue on site Ubay: 54.05V site on Grid TX Fme SAMBA (65426605=
8/Huawei) is informed.","Hyemafo Gildas","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 Ubay: 54.05V site on Grid TX Fme SAMBA (654266058/Huawei) is informed.","c=
hristelle.ngonga@matech-cameroun.com","74","23-05-2025 06:56:02","MATECH CM=
R"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005084558","O=
dza II OCM","","23-05-2025 05:54:28","23-05-2025 05:48:15","23-05-2025 05:5=
6:28","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Site stabilisation","Albran Byorel","Equipment Repair","P=
assive","Rectifier","Rectifier Module Overloaded","Grid outage, site went d=
own because gen failed to start due to PWC ZTE malfunction // Site stabilis=
ation","gaelle.njiofack@matech-cameroun.com","375","23-05-2025 05:54:28","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005084293","MEHANDAN=
","","23-05-2025 04:15:15","23-05-2025 04:09:29","23-05-2025 04:18:06","Cas=
caded Incident from TTO5222620","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
1505013","23-05-2025 04:15:15","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005084283","O=
dza II OCM","IHS_YND_528","23-05-2025 04:12:47","23-05-2025 04:09:29","23-0=
5-2025 04:18:42","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","loic.noumsi@matech-cameroun.com","200","23-05-2025 04:12:47","=
MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005084072","N=
koabang2","","23-05-2025 03:05:30","23-05-2025 02:54:17","23-05-2025 04:46:=
31","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","lo=
ic.noumsi@matech-cameroun.com","674","23-05-2025 03:05:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005083599","Ngouetou=
","","23-05-2025 00:29:53","23-05-2025 00:11:04","23-05-2025 02:02:31","Cas=
caded Incident from TTO5221863","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down because Ge=
n ran till fuel shortage // Refuelling done by EDONDE","system","1519172","=
23-05-2025 00:29:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005083598","Matsari"=
,"","23-05-2025 00:29:53","23-05-2025 00:11:04","23-05-2025 02:02:31","Casc=
aded Incident from TTO5221863","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, Site went down because Gen=
 ran till fuel shortage // Refuelling done by EDONDE","system","1519172","2=
3-05-2025 00:29:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005083600","MBIMBIM"=
,"","23-05-2025 00:29:53","23-05-2025 00:11:04","23-05-2025 02:02:31","Casc=
aded Incident from TTO5221863","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, Site went down because Gen=
 ran till fuel shortage // Refuelling done by EDONDE","system","1519172","2=
3-05-2025 00:29:53","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0005083590","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","23-05-2025 00:28:11","23-=
05-2025 00:11:04","23-05-2025 02:02:31","Grid outage, Site went down becaus=
e Gen ran till fuel shortage // Refuelling done by EDONDE","Parker Tchoup",=
"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, Site went do=
wn because Gen ran till fuel shortage // Refuelling done by EDONDE","loic.n=
oumsi@matech-cameroun.com","1028","23-05-2025 00:28:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005083492","MEHANDAN=
","","23-05-2025 00:05:35","23-05-2025 00:02:20","23-05-2025 00:27:45","Cas=
caded Incident from TTO5221756","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to PWC ZTE malfunction // Site stabilised","system",=
"1519680","23-05-2025 00:05:35","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005083488","O=
dza II OCM","IHS_YND_528","23-05-2025 00:04:33","23-05-2025 00:02:20","23-0=
5-2025 00:27:45","	Grid outage, site went down because gen failed to start =
due to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","	Grid outage, s=
ite went down because gen failed to start due to PWC ZTE malfunction // Sit=
e stabilised","gaelle.njiofack@matech-cameroun.com","8761","23-05-2025 00:0=
4:33","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005083346","C=
hapelle-Nsimeyong","","22-05-2025 23:32:06","22-05-2025 23:16:11","23-05-20=
25 10:56:24","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Grid outage . site went down due to fuel filter damged=
//We replace fuel filter and gen manually starter","gaelle.njiofack@matech-=
cameroun.com","1085","22-05-2025 23:32:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005083107","Messassi=
 okolo","","22-05-2025 22:33:34","22-05-2025 22:23:32","22-05-2025 22:37:32=
","Cascaded Incident from TTO5221344","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","	Grid outage, site down becaus=
e site behaves as Grid only site (no Gen)//Grid return","system","1531397",=
"22-05-2025 22:33:34","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005083067","EMA=
NA BILICK CITY","IHS_YND_279","22-05-2025 22:27:38","22-05-2025 22:23:32","=
22-05-2025 22:42:22","	Grid outage, site down because site behaves as Grid =
only site (no Gen)//Grid return","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","	Grid outage, site down because=
 site behaves as Grid only site (no Gen)//Grid return","cedric.tiani@matech=
-cameroun.com","247","22-05-2025 22:27:38","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005083026","Nko=
l-Mbanda","IHS_YND_148","22-05-2025 22:18:18","22-05-2025 21:37:11","23-05-=
2025 11:18:11","Grid outage . site went down due to fuel filter damged//We =
replace fuel filter and gen manually starter","MINKA NICOLAS","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Fuel Filter","Grid outage . site went do=
wn due to fuel filter damged//We replace fuel filter and gen manually start=
er","landry.etame@ihstowers.com","2468","22-05-2025 22:18:18","MATECH CMR"
"Closed Complete","Site Down","T1652","IHS_YND_273","NOCINC0005082768","Nko=
lbi-Boss","","22-05-2025 21:33:14","22-05-2025 21:29:06","22-05-2025 23:09:=
42","Grid fluctuations, site went down due to Grid bad voltage // He bypass=
ed Grid and started Gen manually","TIENTCHEU NZETCHIEU GAEL","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
ns, site went down due to Grid bad voltage // He bypassed Grid and started =
Gen manually","cedric.tiani@matech-cameroun.com","249","22-05-2025 21:33:14=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005082764","SOA VILL=
AGE","","22-05-2025 21:32:45","22-05-2025 21:28:54","22-05-2025 21:30:36","=
Cascaded Incident from TTO5220940","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // He added water and manually =
start the gen","system","1528730","22-05-2025 21:32:45","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005082759","OBA=
M NGOLA OCM","","22-05-2025 21:31:27","22-05-2025 21:26:19","22-05-2025 22:=
54:49","Grid Outage, Gen stopped due to Alarm emergency stop // Gen card re=
set and Gen start manually","MINKA NICOLAS","Equipment Repair","Passive","A=
CDG Gen","ACDG - Emergency Stop","Grid Outage, Gen stopped due to Alarm eme=
rgency stop // Gen card reset and Gen start manually","cedric.tiani@matech-=
cameroun.com","309","22-05-2025 21:31:27","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0005082756","C=
arrefourt Nkomo","","22-05-2025 21:30:57","22-05-2025 21:05:49","22-05-2025=
 21:50:59","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","site went down because (03/05) rectifiers took and al=
arm// Rectifiers reseted , site on grid","vanel.mbiada@matech-cameroun.com"=
,"1530084","22-05-2025 21:30:57","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005082748","SOA=
 TOWN","IHS_YND_323","22-05-2025 21:30:15","22-05-2025 21:28:54","22-05-202=
5 21:30:36","Grid outage, site went down because gen start and stopped with=
 high temp alarm // He added water and manually start the gen","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid outage, site went down because gen start and stopped=
 with high temp alarm // He added water and manually start the gen","cedric=
.tiani@matech-cameroun.com","82","22-05-2025 21:30:15","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005082619","N=
komo","IHS_YND_174","22-05-2025 21:09:00","22-05-2025 21:05:49","22-05-2025=
 21:50:59","site went down because (03/05) rectifiers took and alarm// Rect=
ifiers reseted , site on grid","Mba Lazare Herve","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","site went down because (03/05) rectifie=
rs took and alarm// Rectifiers reseted , site on grid","vanel.mbiada@matech=
-cameroun.com","192","22-05-2025 21:09:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0005082423","Accacia =
New","","22-05-2025 20:36:21","22-05-2025 19:06:30","22-05-2025 20:36:40","=
Cascaded Incident from TTO5220239","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage gen failed to start due to headgaske=
t  faulty//Grid return","system","1537121","22-05-2025 20:36:21","MATECH CM=
R"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0005082341","N=
koa Ayos","","22-05-2025 20:16:52","22-05-2025 20:12:48","22-05-2025 21:21:=
06","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","site Went down due to absence of 01 Eneo phase // bridge made b=
etween the two remaining phases","vanel.mbiada@matech-cameroun.com","153320=
1","22-05-2025 20:16:52","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0005082327","G=
SO","IHS_YND_067","22-05-2025 20:14:16","22-05-2025 20:12:30","22-05-2025 2=
1:21:06","site Went down due to absence of 01 Eneo phase // bridge made bet=
ween the two remaining phases","MINKA NICOLAS","Grid Supply","Passive","Gri=
d","National Grid - Grid Incomplete Phase","site Went down due to absence o=
f 01 Eneo phase // bridge made between the two remaining phases","vanel.mbi=
ada@matech-cameroun.com","107","22-05-2025 20:14:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_148","NOCINC0005082125","Chapelle=
-Nsimeyong","","22-05-2025 19:42:33","22-05-2025 19:06:30","22-05-2025 20:3=
6:40","Cascaded Incident from TTO5220239","MINKA NICOLAS","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage gen failed to st=
art due to headgasket  faulty//Grid return","system","1537121","22-05-2025 =
19:42:33","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005082124","E=
ssomba","","22-05-2025 19:42:28","22-05-2025 19:38:17","22-05-2025 21:58:33=
","Site went down because PWC overload (12Kw, 250A) SS IHS Alphonse DEFFO c=
onfirmed // Site stabilised","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Site went down because PWC=
 overload (12Kw, 250A) SS IHS Alphonse DEFFO confirmed // Site stabilised",=
"vanel.mbiada@matech-cameroun.com","253","22-05-2025 19:42:28","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005082058","NKO=
MKANA ELIZA HOTEL","","22-05-2025 19:35:28","22-05-2025 19:32:17","22-05-20=
25 20:36:33","Active//No power issue, Site on Grid Ubaie: 53.2V. The Tx FME=
 Brice Tsague(650214096) from Huawei is informed.","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue, Site on Grid Ubaie: 53.2V. The Tx FME Brice Tsague(650214096=
) from Huawei is informed.","cedric.tiani@matech-cameroun.com","192","22-05=
-2025 19:35:28","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005082053","Sof=
avinc","","22-05-2025 19:34:46","22-05-2025 19:33:40","22-05-2025 20:49:42"=
,"Site went down because Gen failed to start due to card Ge faulty // He re=
seted it and started Gen manually","MINKA NICOLAS","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Site went down because Gen failed t=
o start due to card Ge faulty // He reseted it and started Gen manually","c=
edric.tiani@matech-cameroun.com","67","22-05-2025 19:34:46","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005082038","Nko=
l-Mbanda","IHS_YND_562, IHS_YND_148","22-05-2025 19:31:41","22-05-2025 19:0=
6:30","22-05-2025 21:12:41","Grid outage gen failed to start due to headgas=
ket  faulty//Grid return","MINKA NICOLAS","Equipment Replacement","Passive"=
,"ACDG Gen","ACDG - Top Gasket","Grid outage gen failed to start due to hea=
dgasket  faulty//Grid return","cedric.tiani@matech-cameroun.com","1512","22=
-05-2025 19:31:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005081997","SOA VILL=
AGE","","22-05-2025 19:22:12","22-05-2025 18:52:51","22-05-2025 19:37:54","=
Cascaded Incident from TTO5220094","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // he added water and manual st=
art of Gen","system","1537902","22-05-2025 19:22:12","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005081971","Nko=
langaa","","22-05-2025 19:13:34","22-05-2025 19:10:28","22-05-2025 20:49:38=
","Site down due to disjonction in the DC Box // DC box CB reamed, site on =
grid.","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Cir=
cuit Breaker Tripped","Site down due to disjonction in the DC Box // DC box=
 CB reamed, site on grid.","cedric.tiani@matech-cameroun.com","187","22-05-=
2025 19:13:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0005081966","Mehanda =
1","","22-05-2025 19:12:31","22-05-2025 18:54:32","22-05-2025 19:02:15","Ca=
scaded Incident from TTO5220037","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuation, site went down beca=
use Gen failed to start due to Grid bad voltage// Grid stabilised","system"=
,"1537818","22-05-2025 19:12:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005081953","Carrefou=
rt Nkomo","","22-05-2025 19:10:21","22-05-2025 19:04:11","22-05-2025 20:40:=
49","Cascaded Incident from TTO5220035","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site went down because (02/=
05) rectifiers  alarming // Rectifiers reseted , site on grid","system","15=
37238","22-05-2025 19:10:21","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005081947","Nko=
lnda","IHS_YND_528, IHS_YND_746","22-05-2025 19:09:45","22-05-2025 18:54:32=
","22-05-2025 19:02:15","Grid fluctuation, site went down because Gen faile=
d to start due to Grid bad voltage// Grid stabilised","Albran Byorel","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid fluctua=
tion, site went down because Gen failed to start due to Grid bad voltage// =
Grid stabilised","cedric.tiani@matech-cameroun.com","914","22-05-2025 19:09=
:45","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005081946","N=
komo","IHS_YND_174","22-05-2025 19:09:24","22-05-2025 19:04:11","22-05-2025=
 20:50:12","site went down because (02/05) rectifiers  alarming // Rectifie=
rs reseted , site on grid","Mba Lazare Herve","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","site went down because (02/05) rectifiers  =
alarming // Rectifiers reseted , site on grid","vanel.mbiada@matech-camerou=
n.com","314","22-05-2025 19:09:24","MATECH CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0005081880","P=
olytechnique","","22-05-2025 18:58:36","22-05-2025 18:56:26","22-05-2025 19=
:23:12","Active//No power issue on site ,site on Grid ,Ubaie=3D54,3 V TX FM=
E Mbah Oshia (674007438) from hauwei is informed","","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site ,site on Grid ,Ubaie=3D54,3 V TX FME Mbah Oshia (67400=
7438) from hauwei is informed","vanel.mbiada@matech-cameroun.com","131","22=
-05-2025 18:58:36","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005081878","S=
OA TOWN","IHS_YND_323","22-05-2025 18:58:01","22-05-2025 18:52:51","22-05-2=
025 19:37:54","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // he added water and manual start of Gen","Siligap Bori=
s","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coola=
nt Level Issue","Grid outage, site went down because gen start and stopped =
with high temp alarm // he added water and manual start of Gen","vanel.mbia=
da@matech-cameroun.com","311","22-05-2025 18:58:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005081770","Song-bon=
g","","22-05-2025 18:43:11","22-05-2025 18:00:13","22-05-2025 19:36:43","Ca=
scaded Incident from TTO5219646","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,Soite went down because=
 Gen start and stopped due to Gen card dysfunction//He reset the Gen card a=
nd manually started the Gen","system","1541005","22-05-2025 18:43:11","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005081758","E=
lig-Edzoa","","22-05-2025 18:41:31","22-05-2025 18:32:22","22-05-2025 22:00=
:37","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
site went down due to replacement of PWC (12Kw 250A) with another A new 36K=
W PWC // End of work","vanel.mbiada@matech-cameroun.com","1539104","22-05-2=
025 18:41:31","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005081743","N=
taba","IHS_YND_133","22-05-2025 18:39:33","22-05-2025 18:32:22","22-05-2025=
 22:00:37","site went down due to replacement of PWC (12Kw 250A) with anoth=
er A new 36KW PWC // End of work","Delor Telezing","Equipment Replacement",=
"Passive","Planned Activity","Rectifier Servicing","site went down due to r=
eplacement of PWC (12Kw 250A) with another A new 36KW PWC // End of work","=
vanel.mbiada@matech-cameroun.com","433","22-05-2025 18:39:33","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005081588","E=
seka OCM","IHS_YND_378, IHS_YND_453","22-05-2025 18:13:23","22-05-2025 18:0=
0:13","22-05-2025 19:36:43","Grid outage,Soite went down because Gen start =
and stopped due to Gen card dysfunction//He reset the Gen card and manually=
 started the Gen","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage,Soite went down because Gen start and =
stopped due to Gen card dysfunction//He reset the Gen card and manually sta=
rted the Gen","vanel.mbiada@matech-cameroun.com","791","22-05-2025 18:13:23=
","MATECH CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0005081563","E=
seka Town","","22-05-2025 18:09:06","22-05-2025 18:00:13","22-05-2025 19:36=
:43","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage,Soite went down because Gen start and stopped du=
e to Gen card dysfunction//He reset the Gen card and manually started the G=
en","vanel.mbiada@matech-cameroun.com","1541005","22-05-2025 18:09:06","MAT=
ECH CMR"
"Closed Complete","Site Down","T1071","IHS_YND_343","NOCINC0005081510","Mbe=
doumou - Ekali","IHS_YND_160, IHS_YND_715, IHS_YND_312, IHS_YND_749","22-05=
-2025 17:57:05","22-05-2025 17:42:23","22-05-2025 17:46:51","Grid fluctuati=
on, site went down because Gen failed to start due to Grid bad voltage// he=
 bypass the Grid and Gen manually started","Albran Byorel","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,=
 site went down because Gen failed to start due to Grid bad voltage// he by=
pass the Grid and Gen manually started","cedric.tiani@matech-cameroun.com",=
"883","22-05-2025 17:57:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_160","NOCINC0005081492","Complex =
Beac II","","22-05-2025 17:55:34","22-05-2025 17:42:23","22-05-2025 17:46:5=
1","Cascaded Incident from TTO5219511","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation, site went dow=
n because Gen failed to start due to Grid bad voltage// he bypass the Grid =
and Gen manually started","system","1542058","22-05-2025 17:55:34","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0005081494","ODZA MIN=
KAN EDIBI ASSI","","22-05-2025 17:55:34","22-05-2025 17:42:23","22-05-2025 =
17:46:51","Cascaded Incident from TTO5219511","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site w=
ent down because Gen failed to start due to Grid bad voltage// he bypass th=
e Grid and Gen manually started","system","1542056","22-05-2025 17:55:34","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0005081493","Odza Min=
kan IHS","","22-05-2025 17:55:34","22-05-2025 17:42:23","22-05-2025 17:46:5=
1","Cascaded Incident from TTO5219511","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation, site went dow=
n because Gen failed to start due to Grid bad voltage// he bypass the Grid =
and Gen manually started","system","1542057","22-05-2025 17:55:34","MATECH =
CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005081460","Nko=
lnda","","22-05-2025 17:51:01","22-05-2025 17:42:23","22-05-2025 17:46:51",=
"","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid fluctuation, site went down because Gen failed to start due to=
 Grid bad voltage// he bypass the Grid and Gen manually started","cedric.ti=
ani@matech-cameroun.com","1542057","22-05-2025 17:51:01","MATECH CMR"
"Closed Complete","Warning","T1071","IHS_YND_343","NOCINC0005081307","Mbedo=
umou - Ekali","","22-05-2025 17:29:09","","","Grid fluctuation, site went d=
own because Gen failed to start due to Grid bad voltage// he bypass the Gri=
d and Gen manually started","Albran Byorel","Warning","Warning","POWER","Wa=
rning - National Grid - Grid Incomplete Phase","Grid fluctuation, site went=
 down because Gen failed to start due to Grid bad voltage// he bypass the G=
rid and Gen manually started","cedric.tiani@matech-cameroun.com","39","22-0=
5-2025 17:29:09","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0005081199","Val=
lee Bastos MTN","","22-05-2025 17:19:34","22-05-2025 17:17:50","22-05-2025 =
17:19:54","Site went down due to insufficient  rectifiers on site //Site st=
abilised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to insufficient  rectifiers on site //Site s=
tabilised","cedric.tiani@matech-cameroun.com","105","22-05-2025 17:19:34","=
MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0005081088","C=
hapelle-Nsimeyong","","22-05-2025 17:06:57","22-05-2025 16:59:26","22-05-20=
25 18:50:29","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","SS HIS Francois is on site working//End of work","vane=
l.mbiada@matech-cameroun.com","1538522","22-05-2025 17:06:57","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005081065","A=
ccacia New","","22-05-2025 17:04:22","22-05-2025 16:59:44","22-05-2025 18:4=
6:29","Grid outage ,no space to deploy a mobil gen //  grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
 ,no space to deploy a mobil gen //  grid return","vanel.mbiada@matech-came=
roun.com","280","22-05-2025 17:04:22","MATECH CMR"
"Closed Complete","Site Down","CTR_234","IHS_YND_415","NOCINC0005081044","B=
oga-Mahole","","22-05-2025 16:59:02","22-05-2025 16:58:57","22-05-2025 17:0=
1:01","Active//No power issue site on Grid with U=3D54.7V The Tx Fme freddy=
/690419006 from Huawei is informed","Kemeni Franklin","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue site on Grid with U=3D54.7V The Tx Fme freddy/690419006 from =
Huawei is informed","vanel.mbiada@matech-cameroun.com","6","22-05-2025 16:5=
9:02","MATECH CMR"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0005080938","Ngo=
g Mapubi","","22-05-2025 16:42:18","22-05-2025 16:30:16","22-05-2025 17:31:=
00","Grid fluctuation,site went down because Gen failed to start   due to g=
rid bad voltages and poor battery backup//He manually started the Gen","Kem=
eni Franklin","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation,site went down because Gen failed to start   =
due to grid bad voltages and poor battery backup//He manually started the G=
en","cedric.tiani@matech-cameroun.com","2950","22-05-2025 16:42:18","MATECH=
 CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005080937","Nko=
l-Mbanda","IHS_YND_148","22-05-2025 16:41:37","22-05-2025 16:36:26","22-05-=
2025 19:03:09","SS HIS Francois is on site working//End of work","MINKA NIC=
OLAS","Installation Activity","Passive","Planned Activity","Installation Ac=
tivity","SS HIS Francois is on site working//End of work","cedric.tiani@mat=
ech-cameroun.com","312","22-05-2025 16:41:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005080908","Elig-Edz=
oa","","22-05-2025 16:36:35","22-05-2025 15:22:34","22-05-2025 16:33:30","C=
ascaded Incident from TTO5218330","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","site went down due to PWC Overload(12Kw 250A) Bla=
ise Raoul SS IHS is iformed //Site stabilised","system","1544187","22-05-20=
25 16:36:35","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005080821","NYO=
M 2 IHS","","22-05-2025 16:26:49","22-05-2025 16:22:37","22-05-2025 16:31:0=
5","Grid outage, Site went down before Gen start due to poor backup// Gen s=
tarted automatically","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automatically","cedric.tiani@ma=
tech-cameroun.com","254","22-05-2025 16:26:49","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005080765","M=
ANGUIERS CHAPELLE","","22-05-2025 16:23:14","22-05-2025 16:19:40","22-05-20=
25 16:44:41","Active//No power issue on site ,site on Grid with Ubaie=3D53.=
6 V The Tx FME Symphorien (650257151) from Huawei is informed","Fabrice Pou=
akam","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active//No power issue on site ,site on Grid with Ubaie=
=3D53.6 V The Tx FME Symphorien (650257151) from Huawei is informed","vanel=
.mbiada@matech-cameroun.com","215","22-05-2025 16:23:14","MATECH CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0005080694","C=
lge-Advantiste","","22-05-2025 16:10:01","22-05-2025 16:09:49","22-05-2025 =
16:19:27","Active/ No power issue site on grid with U=3D50.8V Lionnel Steev=
e(655184876) from Huawei is informed","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/ N=
o power issue site on grid with U=3D50.8V Lionnel Steeve(655184876) from Hu=
awei is informed","vanel.mbiada@matech-cameroun.com","12","22-05-2025 16:10=
:01","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005080347","MBA=
LNGONG LYCEE","","22-05-2025 15:27:14","22-05-2025 15:25:03","22-05-2025 16=
:55:01","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, Site went down because Gen stopped due to overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed//Grid return","cedric.tiani@matech-ca=
meroun.com","132","22-05-2025 15:27:14","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005080326","Nta=
ba","IHS_YND_133","22-05-2025 15:25:44","22-05-2025 15:22:34","22-05-2025 1=
6:33:30","site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS=
 is iformed //Site stabilised","Delor Telezing","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","site went down due to PWC Over=
load(12Kw 250A) Blaise Raoul SS IHS is iformed //Site stabilised","cedric.t=
iani@matech-cameroun.com","191","22-05-2025 15:25:44","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005080323","Eto=
ug ebe biscuiterie","","22-05-2025 15:24:02","22-05-2025 15:20:48","22-05-2=
025 16:23:26","Grid fluctuation, site went down because Gen failed to start=
 due to Grid bad voltage and no RCP on site// he bypass the Grid and Gen ma=
nually started","Hyemafo Gildas","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation, site went down because Ge=
n failed to start due to Grid bad voltage and no RCP on site// he bypass th=
e Grid and Gen manually started","cedric.tiani@matech-cameroun.com","195","=
22-05-2025 15:24:02","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005080269","ODZ=
A MINKAN EDIBI ASSI","","22-05-2025 15:17:53","22-05-2025 15:14:45","22-05-=
2025 15:22:13","Grid fluctuation, Site went down because Gen started and st=
opped due to Grid bad voltag and No RCP on site // He bypassed Grid and sta=
rted Gen manually","Albran Byorel","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Grid fluctuation, Site went down because =
Gen started and stopped due to Grid bad voltag and No RCP on site // He byp=
assed Grid and started Gen manually","cedric.tiani@matech-cameroun.com","18=
9","22-05-2025 15:17:53","MATECH CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0005080255","N=
omayos","","22-05-2025 15:15:51","22-05-2025 15:14:36","22-05-2025 15:50:56=
","Grid outage,site went down due to  CB that tripped rectifier and  01 rec=
tifiers faulty on site //He rearemed the CB","Fanda Brice","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Grid outage,site went down due=
 to  CB that tripped rectifier and  01 rectifiers faulty on site //He reare=
med the CB","vanel.mbiada@matech-cameroun.com","76","22-05-2025 15:15:51","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0005080214","Damas","=
","22-05-2025 15:07:27","22-05-2025 14:24:33","22-05-2025 14:59:19","Cascad=
ed Incident from TTO5218231","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage ,no space to deploy a mobil g=
en // grid return","system","1547646","22-05-2025 15:07:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0005080215","Montee-J=
ouvence-II","","22-05-2025 15:07:27","22-05-2025 14:24:33","22-05-2025 14:5=
9:19","Cascaded Incident from TTO5218231","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage ,no space to de=
ploy a mobil gen // grid return","system","1547646","22-05-2025 15:07:27","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005080210","MEHANDAN=
","","22-05-2025 15:06:18","22-05-2025 14:56:01","22-05-2025 19:02:15","Cas=
caded Incident from TTO5218230","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to PWC ZTE malfunction // Site stabilised","system",=
"1552128","22-05-2025 15:06:18","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005080205","A=
ccacia New","IHS_YND_166, IHS_YND_518","22-05-2025 15:05:42","22-05-2025 14=
:24:33","22-05-2025 14:59:19","Grid outage ,no space to deploy a mobil gen =
// grid return","","Grid Supply","Passive","Grid","National Grid - Grid Out=
age Issue","Grid outage ,no space to deploy a mobil gen // grid return","ko=
uoh.jean@ihstowers.com","2471","22-05-2025 15:05:42","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005080204","O=
dza II OCM","IHS_YND_528","22-05-2025 15:05:24","22-05-2025 14:56:01","22-0=
5-2025 15:24:44","	Grid outage, site went down because gen failed to start =
due to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","	Grid outage, s=
ite went down because gen failed to start due to PWC ZTE malfunction // Sit=
e stabilised","vanel.mbiada@matech-cameroun.com","566","22-05-2025 15:05:24=
","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005080198","Ron=
d Point Express1114","","22-05-2025 15:02:07","22-05-2025 14:54:38","22-05-=
2025 16:18:22","Active: No power issue, site is on grid with Ubaie=3D54,5V,=
 Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active: No power issue, site is on grid with Ubaie=3D54,5V, Mbah hosiah(=
699699694) from Huawei is informed","cedric.tiani@matech-cameroun.com","131=
6","22-05-2025 15:02:07","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005080181","M=
efou-Assi","IHS_YND_537, IHS_YND_696","22-05-2025 14:58:33","22-05-2025 14:=
26:13","22-05-2025 16:23:44","Grid outage, site went down because gen faile=
d to start due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed =
// Grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, site went down because gen failed to start due t=
o gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return",=
"kouoh.jean@ihstowers.com","1942","22-05-2025 14:58:33","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005080166","Mon=
tee Jouvence","","22-05-2025 14:55:45","22-05-2025 14:54:38","22-05-2025 16=
:00:46","Grid outage, Site went down before Gen start due to poor backup// =
Gen started manually","Hyemafo Gildas","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started manually","cedric.tiani@matech-c=
ameroun.com","68","22-05-2025 14:55:45","MATECH CMR"
"Closed Complete","Site Down","T1333","IHS_YND_174","NOCINC0005080140","Car=
refourt Nkomo","","22-05-2025 14:51:21","22-05-2025 14:29:09","22-05-2025 1=
5:00:35","No power issue site on grid with U=3D53.3V Lionnel Steeve from Hu=
awei site up at 03:00 PM","Mba Lazare Herve","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on grid with U=3D53.3V Lionnel Steeve from Huawei site up at 03:00 PM","c=
edric.tiani@matech-cameroun.com","1333","22-05-2025 14:51:21","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005080128","E=
toug ebe Meweulo","","22-05-2025 14:48:33","22-05-2025 14:46:10","22-05-202=
5 15:03:38","Grid outage, Site went down before Gen start due to poor backu=
p// Gen started automatically","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup// Gen started automatically","vanel.m=
biada@matech-cameroun.com","144","22-05-2025 14:48:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0005080065","AFEME NO=
RD","","22-05-2025 14:40:32","22-05-2025 14:24:02","22-05-2025 14:36:40","C=
ascaded Incident from TTO5218078","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active: no power issue, site=
 is on grid with Ubaie=3D54V, Mohamadou((691144435) from Huawie is informed=
,","system","1547639","22-05-2025 14:40:32","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0005080062","Mba=
nkolo petit paris","IHS_YND_519","22-05-2025 14:40:11","22-05-2025 14:24:02=
","22-05-2025 16:52:21","Active: no power issue, site is on grid with Ubaie=
=3D54V, Mohamadou((691144435) from Huawie is informed,","Mboua Thierry","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active: no power issue, site is on grid with Ubaie=3D54V, Mohamado=
u((691144435) from Huawie is informed,","cedric.tiani@matech-cameroun.com",=
"969","22-05-2025 14:40:11","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005080050","Men=
dong3","","22-05-2025 14:38:51","22-05-2025 14:29:59","22-05-2025 14:53:00"=
,"	Grid Outage No space to deploy a MDG //Grid Restored","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","	Grid Outage No space =
to deploy a MDG //Grid Restored","cedric.tiani@matech-cameroun.com","533","=
22-05-2025 14:38:51","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0005080049","Tam=
tam Weekend","","22-05-2025 14:38:20","22-05-2025 14:22:10","22-05-2025 15:=
03:38","Grid Outage Site went down because Gen Overload (20KVA, 300A) // He=
 reduiced The load and Manually Started the Gen","Hyemafo Gildas","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went dow=
n because Gen Overload (20KVA, 300A) // He reduiced The load and Manually S=
tarted the Gen","cedric.tiani@matech-cameroun.com","970","22-05-2025 14:38:=
20","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005080041","B=
arriere IHS","","22-05-2025 14:37:33","22-05-2025 14:26:13","22-05-2025 16:=
23:44","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, site went down because gen failed to start due=
 to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return=
","vanel.mbiada@matech-cameroun.com","1552771","22-05-2025 14:37:33","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005080027","S=
IMBOCK BONAMBAPE","","22-05-2025 14:34:59","22-05-2025 14:26:45","22-05-202=
5 16:58:56","Active // No power issue site on grid with Ubaie: 54.5V TX FME=
 Flubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue site on grid with Ubaie: 52.9V TX FME Flubert (654=
266068) from Huawei is informed","vanel.mbiada@matech-cameroun.com","496","=
22-05-2025 14:34:59","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005080013","M=
EFOU ASSI","","22-05-2025 14:32:32","22-05-2025 14:26:13","22-05-2025 16:23=
:44","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, site went down because gen failed to start due to g=
en overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return","va=
nel.mbiada@matech-cameroun.com","1552770","22-05-2025 14:32:32","MATECH CMR=
"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0005079939","Ngo=
usso MTN","IHS_YND_187","22-05-2025 14:26:49","22-05-2025 14:08:39","22-05-=
2025 19:46:25","Grid outage//grid return","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid outage//grid return","cedric.tia=
ni@matech-cameroun.com","1091","22-05-2025 14:26:49","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005079867","Ako=
k Ndoe Yde","","22-05-2025 14:14:28","22-05-2025 14:11:17","22-05-2025 14:2=
4:58","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started automatically","Hyemafo Gildas","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup// Gen started automatically","cedric.tiani@=
matech-cameroun.com","192","22-05-2025 14:14:28","MATECH CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0005079866","ENA=
M","","22-05-2025 14:13:50","22-05-2025 14:08:38","22-05-2025 14:09:29","Wr=
ongly created ticket","","Incorrectly Logged Tickets","Error","Error","Erro=
r","Wrongly created ticket","cedric.tiani@matech-cameroun.com","313","22-05=
-2025 14:13:50","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0005079865","NTE=
MASSI","","22-05-2025 14:13:21","22-05-2025 14:08:39","22-05-2025 19:46:25"=
,"","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Grid outage//grid return","cedric.tiani@matech-cameroun.com","154=
8546","22-05-2025 14:13:21","MATECH CMR"
"Closed Complete","Warning","CTR_441","IHS_YND_687","NOCINC0005079856","OLA=
MA","","22-05-2025 14:11:35","","","Eneo outage // Gen started","Fanda Bric=
e","Warning","Warning","POWER","Warning - Site on Battery","Eneo outage // =
Gen started","gerard.tchangoue@matech-cameroun.com","432","22-05-2025 14:11=
:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005079768","MEHANDAN=
","","22-05-2025 13:54:30","22-05-2025 13:51:45","22-05-2025 14:00:11","Cas=
caded Incident from TTO5217743","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
1549504","22-05-2025 13:54:30","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005079756","O=
dza II OCM","IHS_YND_528","22-05-2025 13:52:54","22-05-2025 13:51:45","22-0=
5-2025 14:00:45","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","gerard.tchangoue@matech-cameroun.com","72","22-05-2025 13:52:5=
4","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0005078842","Sca=
lom","","22-05-2025 11:47:44","22-05-2025 11:45:33","22-05-2025 11:51:40","=
Site went Down du to work,  the telemetrie guys (Duclair 680685526) was on =
site for work  // End of works","Paul BIBOUM","Equipment Replacement","Pass=
ive","Planned Activity","Planned Activity - Passive","Site went Down du to =
work,  the telemetrie guys (Duclair 680685526) was on site for work  // End=
 of works","edwige.kapawo@matech-cameroun.com","131","22-05-2025 11:47:44",=
"MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005078726","AKA=
K Nkozoa","","22-05-2025 11:35:01","22-05-2025 11:28:54","22-05-2025 13:53:=
00","Grid outage, site down due to insufficient rectifier issue // He added=
 rectifiers and reseted it","Fabrice Pouakam","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","Grid outage, site down due to insufficient =
rectifier issue // He added rectifiers and reseted it","edwige.kapawo@matec=
h-cameroun.com","368","22-05-2025 11:35:01","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005078562","Nsi=
malen MTN","","22-05-2025 11:10:57","22-05-2025 11:10:34","22-05-2025 12:18=
:13","Grid outage, Site went because Gen ran until shortage// Refueling Don=
e","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid o=
utage, Site went because Gen ran until shortage// Refueling Done","edwige.k=
apawo@matech-cameroun.com","24","22-05-2025 11:10:57","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005078545","SAA=
 Entrance","","22-05-2025 11:07:34","22-05-2025 11:06:59","22-05-2025 11:08=
:59","Grid outage, site went down due to Grid bad voltage // He bypassed Gr=
id and put site on Gen","Parker Tchoup","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","Grid outage, site went down due to G=
rid bad voltage // He bypassed Grid and put site on Gen","edwige.kapawo@mat=
ech-cameroun.com","37","22-05-2025 11:07:34","MATECH CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0005078504","Aha=
la","","22-05-2025 11:00:15","22-05-2025 10:59:01","22-05-2025 11:41:01","s=
ite went down because gen failed to start due to grid bad voltage// He bypa=
ssed Grid and Gen manually started","Hyemafo Gildas","Grid Supply","Passive=
","Grid","National Grid - Unstable Grid Supply Issue","site went down becau=
se gen failed to start due to grid bad voltage// He bypassed Grid and Gen m=
anually started","edwige.kapawo@matech-cameroun.com","78","22-05-2025 11:00=
:15","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005078370","Mok=
olo Yaounde","","22-05-2025 10:39:52","22-05-2025 10:38:59","22-05-2025 13:=
13:59","Grid outage no space to deploy the MDG, // power returned","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
no space to deploy the MDG, // power returned","edwige.kapawo@matech-camero=
un.com","54","22-05-2025 10:39:52","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005078271","Acc=
acia New","","22-05-2025 10:35:18","22-05-2025 10:34:12","22-05-2025 11:59:=
40","Site went down because Dowen is on site for work (Swap of PWC) // End =
of work","","Installation Activity","Passive","Planned Activity","Installat=
ion Activity","Site went down because Dowen is on site for work (Swap of PW=
C) // End of work","edwige.kapawo@matech-cameroun.com","68","22-05-2025 10:=
35:18","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005078078","Acc=
acia New","","22-05-2025 10:14:58","22-05-2025 10:12:59","22-05-2025 10:24:=
47","Grid fluctuation, site went down because Gen started and stopped due t=
o grid bad voltage // Grid stabilized","","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Grid fluctuation, site went down b=
ecause Gen started and stopped due to grid bad voltage // Grid stabilized",=
"edwige.kapawo@matech-cameroun.com","121","22-05-2025 10:14:58","MATECH CMR=
"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005078052","M=
efou-Assi","IHS_YND_537, IHS_YND_520","22-05-2025 10:09:49","22-05-2025 09:=
59:59","22-05-2025 10:41:29","Grid outage, site went down because gen fails=
 to start due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed /=
/Grid returned","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, site went down because gen fails to start due to=
 gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed //Grid returned",=
"gerard.tchangoue@matech-cameroun.com","591","22-05-2025 10:09:49","MATECH =
CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005077996","S=
IMBOCK BONAMBAPE","","22-05-2025 10:06:33","22-05-2025 09:06:59","22-05-202=
5 10:45:59","Site impacted by Mefou-Assi (CTR_253)","Hyemafo Gildas","Casca=
de Outage","Passive","Cascade Passive","Cascade Passive","Grid outage, site=
 went down because gen fails to start due to gen overload(15Kva, 200A) SS I=
HS FELIX ZAMBE is informed //Grid returned","gerard.tchangoue@matech-camero=
un.com","3575","22-05-2025 10:06:33","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005077985","M=
EFOU ASSI","","22-05-2025 10:04:24","22-05-2025 09:59:59","22-05-2025 10:41=
:29","Site impacted by Mefou-Assi (CTR_253)","Fanda Brice","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 because gen fails to start due to gen overload(15Kva, 200A) SS IHS FELIX Z=
AMBE is informed //Grid returned","gerard.tchangoue@matech-cameroun.com","1=
563044","22-05-2025 10:04:24","MATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0005077932","S=
ofavinc","","22-05-2025 09:57:29","22-05-2025 09:52:16","22-05-2025 09:59:1=
6","Site went down because gen fails to start due to grid bad voltage // He=
 bypassed grid and manually started the gen","MINKA NICOLAS","Grid Supply",=
"Passive","Grid","National Grid - Unstable Grid Supply Issue","Site went do=
wn because gen fails to start due to grid bad voltage // He bypassed grid a=
nd manually started the gen","gerard.tchangoue@matech-cameroun.com","314","=
22-05-2025 09:57:29","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005077867","A=
hala","","22-05-2025 09:47:01","22-05-2025 09:45:50","22-05-2025 10:23:23",=
"Site went down due to 01/03 Rectifiers Dysfunctionning // He reset it: Sit=
e on grid","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to 01/03 Rectifiers Dysfunctionning // He =
reset it: Site on grid","gerard.tchangoue@matech-cameroun.com","72","22-05-=
2025 09:47:01","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0005077826","E=
lig-Edzoa","","22-05-2025 09:43:40","22-05-2025 09:40:53","22-05-2025 12:18=
:53","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
  site Went down due to works Njoya (658849259/matech ) was on site for swa=
p PWC // End of works","gerard.tchangoue@matech-cameroun.com","1564137","22=
-05-2025 09:43:40","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005077810","Nta=
ba","IHS_YND_133","22-05-2025 09:40:58","22-05-2025 09:40:53","22-05-2025 1=
2:48:14","  site Went down due to works Njoya (658849259/matech ) was on si=
te for swap PWC // End of works","Delor Telezing","Equipment Replacement","=
Passive","Planned Activity","Planned Activity - Passive","  site Went down =
due to works Njoya (658849259/matech ) was on site for swap PWC // End of w=
orks","edwige.kapawo@matech-cameroun.com","6","22-05-2025 09:40:58","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0005077806","M=
BIMBIM","","22-05-2025 09:40:00","22-05-2025 09:37:36","22-05-2025 09:43:36=
","Solar-Gen, Site went Down because Gen ran until fuel shortage // Solar r=
eturn (refueling Ongoing)","Parker Tchoup","Fuel Outage","Passive","Diesel"=
,"Diesel Outage","Solar-Gen, Site went Down because Gen ran until fuel shor=
tage // Solar return (refueling Ongoing)","gerard.tchangoue@matech-cameroun=
.com","146","22-05-2025 09:40:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0005077764","MVAN SAC=
EL","","22-05-2025 09:33:04","22-05-2025 09:21:38","22-05-2025 10:35:38","C=
ascaded Incident from TTO5215782","MINKA NICOLAS","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","no power issue on site U=3D53.3V site o=
n Grid.the fme TX TX LIONEL //655184876 from Huawei is informed","system","=
1565277","22-05-2025 09:33:04","MATECH CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0005077744","M=
VAN","IHS_YND_510","22-05-2025 09:30:49","22-05-2025 09:21:38","22-05-2025 =
10:35:38","no power issue on site U=3D53.3V site on Grid.the fme TX TX LION=
EL //655184876 from Huawei is informed","MINKA NICOLAS","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no powe=
r issue on site U=3D53.3V site on Grid.the fme TX TX LIONEL //655184876 fro=
m Huawei is informed","gerard.tchangoue@matech-cameroun.com","552","22-05-2=
025 09:30:49","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005077631","AKA=
K Nkozoa","","22-05-2025 09:17:21","22-05-2025 09:11:11","22-05-2025 10:08:=
57","Site went down due to 01/03 Rectifiers Dysfunctionning // He reset it:=
 Site on grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to 01/03 Rectifiers Dysfunctionning /=
/ He reset it: Site on grid","edwige.kapawo@matech-cameroun.com","371","22-=
05-2025 09:17:21","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005077425","F=
ouda-New","","22-05-2025 08:52:16","22-05-2025 08:48:59","22-05-2025 09:50:=
59","Grid outage,site went down due to relay 12 v faulty//We Bypassed relay=
 and gen manually started","Delor Telezing","Equipment Repair","Passive","A=
CDG Gen","ACDG - Relay Faulty","Grid outage,site went down due to relay 12 =
v faulty//We Bypassed relay and gen manually started","gerard.tchangoue@mat=
ech-cameroun.com","198","22-05-2025 08:52:16","MATECH CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0005076856","M=
BIMBIM","","22-05-2025 06:38:57","22-05-2025 06:32:50","22-05-2025 07:29:12=
","Solar-Gen, Site went Down because Gen ran until fuel shortage // Solar r=
eturn (refueling Ongoing)","Parker Tchoup","Fuel Outage","Passive","Diesel"=
,"Diesel Outage","Solar-Gen, Site went Down because Gen ran until fuel shor=
tage // Solar return (refueling Ongoing)","gerard.tchangoue@matech-cameroun=
.com","368","22-05-2025 06:38:57","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005076679","Nko=
l-Mebanga","","22-05-2025 05:44:13","22-05-2025 05:39:06","22-05-2025 10:26=
:31","Solar only, Site went Down due to low Solar // Solar return","Parker =
Tchoup","Equipment Repair","Passive","Solar","Solar Panel Issue","Solar onl=
y, Site went Down due to low Solar // Solar return","loic.noumsi@matech-cam=
eroun.com","308","22-05-2025 05:44:13","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005076645","AKA=
K Nkozoa","","22-05-2025 05:30:05","22-05-2025 05:29:50","22-05-2025 06:51:=
58","Grid outage, site down due to insufficient rectifier issue // Site sta=
bilised","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectif=
ier Distribution","Grid outage, site down due to insufficient rectifier iss=
ue // Site stabilised","loic.noumsi@matech-cameroun.com","16","22-05-2025 0=
5:30:05","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005076332","AKA=
K Nkozoa","","22-05-2025 03:10:04","22-05-2025 03:07:49","22-05-2025 05:15:=
07","Grid outage, site down due to insufficient rectifier issue // Site sta=
bilised","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Grid outage, site down due to insufficient rectifier issue // =
Site stabilised","gaelle.njiofack@matech-cameroun.com","136","22-05-2025 03=
:10:04","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005076255","N=
kolfon Cimencam","","22-05-2025 02:31:44","22-05-2025 02:23:16","22-05-2025=
 02:49:12","	No power issue, Site impacted by Afanoya-II wich is not IHS si=
te.","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipme=
nt Failure","Affected by 3rd Party Site","	No power issue, Site impacted by=
 Afanoya-II wich is not IHS site.","gaelle.njiofack@matech-cameroun.com","5=
09","22-05-2025 02:31:44","MATECH CMR"
"Closed Complete","Site Down","CTR_234","IHS_YND_415","NOCINC0005076134","B=
oga-Mahole","","22-05-2025 01:43:18","22-05-2025 01:18:08","22-05-2025 01:5=
5:54","Active//No power issue site on Grid with U=3D54.7V The Tx Fme freddy=
/690419006 from Huawei is informed","Kemeni Franklin","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue site on Grid with U=3D54.7V The Tx Fme freddy/690419006 from =
Huawei is informed","ludivine.ngamaleu@ihstowers.com","1511","22-05-2025 01=
:43:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005076121","Golf Qua=
ter","","22-05-2025 01:35:01","22-05-2025 01:29:42","22-05-2025 01:44:35","=
Cascaded Incident from TTO5214000","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage gen failed to start due=
 to card GE dysfunctioned (Access issue) // Grid returned ","system","15926=
41","22-05-2025 01:35:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005076122","Bastos-N=
ylon","","22-05-2025 01:35:01","22-05-2025 01:29:42","22-05-2025 01:44:35",=
"Cascaded Incident from TTO5214000","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage gen failed to start du=
e to card GE dysfunctioned (Access issue) // Grid returned ","system","1592=
641","22-05-2025 01:35:01","MATECH CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0005076113","Tsi=
nga","IHS_YND_220, IHS_YND_126","22-05-2025 01:32:53","22-05-2025 01:29:42"=
,"22-05-2025 01:51:04","Grid outage gen failed to start due to card GE dysf=
unctioned (Access issue) // Grid returned ","Mboua Thierry","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to =
start due to card GE dysfunctioned (Access issue) // Grid returned ","loic.=
noumsi@matech-cameroun.com","192","22-05-2025 01:32:53","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005076049","AKA=
K Nkozoa","","22-05-2025 01:11:33","22-05-2025 01:09:26","22-05-2025 01:38:=
35","Grid outage, site down due to insufficient rectifier issue // Site sta=
bilised","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Grid outage, site down due to insufficient rectifier issue // =
Site stabilised","loic.noumsi@matech-cameroun.com","128","22-05-2025 01:11:=
33","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005076045","Fla=
menco","","22-05-2025 01:10:16","22-05-2025 01:07:00","22-05-2025 01:47:42"=
,"Grid outage gen failed to start due to card GE dysfunctioned (Access issu=
e) // Grid returned ","Mboua Thierry","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage gen failed to start due to card GE d=
ysfunctioned (Access issue) // Grid returned ","loic.noumsi@matech-cameroun=
.com","196","22-05-2025 01:10:16","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005075983","N=
YOM 2 IHS","","22-05-2025 00:46:14","22-05-2025 00:42:01","22-05-2025 01:23=
:10","Grid fluctuations, Site went down due to grid bad voltage // He bypas=
sed Grid and started Gen manually","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuations, Site=
 went down due to grid bad voltage // He bypassed Grid and started Gen manu=
ally","gaelle.njiofack@matech-cameroun.com","255","22-05-2025 00:46:14","MA=
TECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005075952","NKO=
MKANA ELIZA HOTEL","","22-05-2025 00:38:24","22-05-2025 00:28:59","22-05-20=
25 01:44:13","Grid outage, no space to deploy MDGE on site // Grid returned=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage, no space to deploy MDGE on site // Grid returned","loic.noumsi@m=
atech-cameroun.com","566","22-05-2025 00:38:24","MATECH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0005075914","O=
ssombe","","22-05-2025 00:28:09","22-05-2025 00:24:01","22-05-2025 00:29:14=
","Active //No power issue, site on Gen, Ubaie 51V; Site up without interve=
ntion","Parker Tchoup","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Active //No power issue, site on Gen, Ub=
aie 51V; Site up without intervention","gaelle.njiofack@matech-cameroun.com=
","249","22-05-2025 00:28:09","MATECH CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0005075847","BIY=
EM ASSI LYCEE","","22-05-2025 00:12:13","22-05-2025 00:10:01","22-05-2025 1=
0:34:59","Site went down due to rectifiers damaged caused by lightning//We =
replaced  2 rectifiers and site on grid","Hyemafo Gildas","Force Majeure","=
Natural Disaster","Thunderstrike","Equipment Damaged","Site went down due t=
o rectifiers damaged caused by lightning//We replaced  2 rectifiers and sit=
e on grid","loic.noumsi@matech-cameroun.com","132","22-05-2025 00:12:13","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005075778","Emana Ly=
cee","","21-05-2025 23:53:48","21-05-2025 22:06:31","22-05-2025 01:44:05","=
Cascaded Incident from TTO5213078","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down due to pwc not wel=
l configured//We configure well and site on gen","system","1599112","21-05-=
2025 23:53:48","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005075588","AKA=
K Nkozoa","","21-05-2025 23:16:23","21-05-2025 23:08:13","21-05-2025 23:33:=
03","Grid fluctuation, site went down because Gen started and stopped to st=
art due to grid bad voltage // He bypassed Grid and started Gen manually","=
Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid fluctuation, site went down because Gen started and st=
opped to start due to grid bad voltage // He bypassed Grid and started Gen =
manually","loic.noumsi@matech-cameroun.com","491","21-05-2025 23:16:23","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005075568","N=
gouetou","","21-05-2025 23:09:24","21-05-2025 23:04:17","22-05-2025 00:33:3=
8","No power issue site on Gen, with Ubay=3D52.4V. The Tx Fme Gregoire (654=
547479) from Huawei is informed","Parker Tchoup","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 site on Gen, with Ubay=3D52.4V. The Tx Fme Gregoire (654547479) from Huawe=
i is informed","loic.noumsi@matech-cameroun.com","309","21-05-2025 23:09:24=
","MATECH CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0005075454","O=
bobogo","IHS_YND_070","21-05-2025 22:48:55","21-05-2025 22:44:45","21-05-20=
25 23:03:18","Site impacted by Efoulan-pont not managed by IHS","MINKA NICO=
LAS","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","Site impacted by Efoulan-pont","gaelle.njiofack@ma=
tech-cameroun.com","251","21-05-2025 22:48:55","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005075451","E=
foulan","","21-05-2025 22:48:23","21-05-2025 22:44:45","21-05-2025 23:03:18=
","","MINKA NICOLAS","Cascade Outage","Active","Cascade Active","Cascade Ac=
tive","Site impacted by Efoulan-pont","gaelle.njiofack@matech-cameroun.com"=
,"1596865","21-05-2025 22:48:23","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005075338","Nta=
ba","","21-05-2025 22:24:00","21-05-2025 22:16:43","21-05-2025 23:06:27","S=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Site went down due to PWC Overload(12=
Kw 250A) Blaise Raoul SS IHS is iformed //Site stabilised","loic.noumsi@mat=
ech-cameroun.com","438","21-05-2025 22:24:00","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005075292","Sof=
avinc","","21-05-2025 22:16:10","21-05-2025 22:10:04","22-05-2025 08:53:51"=
,"Site went down because gen fails to start due to grid bad voltage // He b=
ypass grid and manually start the gen","MINKA NICOLAS","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Site went down becaus=
e gen fails to start due to grid bad voltage// He bypass grid and manually =
start the gen","cedric.tiani@matech-cameroun.com","367","21-05-2025 22:16:1=
0","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005075280","E=
mana lycee 2","IHS_YND_274","21-05-2025 22:14:38","21-05-2025 22:06:31","22=
-05-2025 01:44:09","site went down due to pwc not well configured//We confi=
gure well and site on gen","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","site went down due to pwc not well config=
ured//We configure well and site on gen","vanel.mbiada@matech-cameroun.com"=
,"489","21-05-2025 22:14:38","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005075022","M=
vog-Ebanda","","21-05-2025 21:42:07","21-05-2025 21:37:16","21-05-2025 22:5=
5:42","Grid outage, Site went down before Gen start due to Poor battery bac=
kup; Grid return bu site still down due to disjunction in the BTS OCM // Re=
ctifier rearm and site on Grid.","Siligap Boris","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to Poor battery backup; Grid return bu site still d=
own due to disjunction in the BTS OCM // Rectifier rearm and site on Grid."=
,"vanel.mbiada@matech-cameroun.com","292","21-05-2025 21:42:07","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005074809","Emana Ly=
cee","","21-05-2025 21:11:21","21-05-2025 21:00:13","21-05-2025 21:10:22","=
Cascaded Incident from TTO5212559","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down beca=
use Gen failed to started due to poor battery backup// Gen automatically st=
arted","system","1602992","21-05-2025 21:11:21","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005074793","Ema=
na lycee 2","IHS_YND_274","21-05-2025 21:09:44","21-05-2025 21:00:13","21-0=
5-2025 21:10:22","Grid outage , site went down because Gen failed to starte=
d due to poor battery backup// Gen automatically started","Fabrice Pouakam"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"Grid outage , site went down because Gen failed to started due to poor ba=
ttery backup// Gen automatically started","cedric.tiani@matech-cameroun.com=
","572","21-05-2025 21:09:44","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005074775","O=
dza II OCM","","21-05-2025 21:06:03","21-05-2025 20:54:26","21-05-2025 22:2=
1:37","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // Site stabilised","Albran Byorel","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Grid outage, site went down=
 because gen failed to start due to PWC ZTE malfunction // Site stabilised"=
,"vanel.mbiada@matech-cameroun.com","699","21-05-2025 21:06:03","MATECH CMR=
"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005074523","N=
koabang2","","21-05-2025 20:41:45","21-05-2025 20:36:29","21-05-2025 21:06:=
24","	Grid outage, site went down due to gen overload (22KVA, 330A), SS Bla=
ise IHS is informed  //  after reducing load, Gen started manually","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, site went down due to gen overload (22KVA, 330A), SS Blaise IHS is=
 informed  //  after reducing load, Gen started manually","vanel.mbiada@mat=
ech-cameroun.com","318","21-05-2025 20:41:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005073960","EBOM",""=
,"21-05-2025 19:20:57","21-05-2025 15:11:09","21-05-2025 15:19:52","Cascade=
d Incident from TTO5211657","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue on site, Site on Grid=
 UBAIE=3D53V The FME TX Georges/697461814 From huawei is informed.site up a=
t 00:55 AM","system","1623731","21-05-2025 19:20:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_583","NOCINC0005073959","Nsam Sof=
avinc T0","","21-05-2025 19:20:57","21-05-2025 15:11:09","21-05-2025 15:19:=
52","Cascaded Incident from TTO5211657","MINKA NICOLAS","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active//No power issue on site, S=
ite on Grid UBAIE=3D53V The FME TX Georges/697461814 From huawei is informe=
d.site up at 00:55 AM","system","1623731","21-05-2025 19:20:57","MATECH CMR=
"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005073946","A=
hala","IHS_YND_583, IHS_YND_698","21-05-2025 19:18:42","21-05-2025 15:11:09=
","21-05-2025 19:19:52","Active//No power issue on site, Site on Grid UBAIE=
=3D53V The FME TX Georges/697461814 From huawei is informed","MINKA NICOLAS=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","Active//No power issue on site, Site on Grid UBAIE=3D53V The =
FME TX Georges/697461814 From huawei is informed.site up at 00:55 AM","vane=
l.mbiada@matech-cameroun.com","14854","21-05-2025 19:18:42","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005073853","E=
koumdoum OCM","","21-05-2025 19:01:29","21-05-2025 18:58:42","21-05-2025 22=
:41:24","Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline i=
s informed and confirmed//Grid returned","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen overload=
(20kva,280 A) IHS SS Pascaline is informed and confirmed//Grid returned","v=
anel.mbiada@matech-cameroun.com","168","21-05-2025 19:01:29","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005073777","C=
omplexe-BEAC","","21-05-2025 18:48:45","21-05-2025 18:45:33","21-05-2025 18=
:49:27","Grid outage, Site went down before Gen start due to Poor battery b=
ackup // Grid return","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to Poor battery backup // Grid return","vanel.mbiada@matech-ca=
meroun.com","193","21-05-2025 18:48:45","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005073734","Mok=
olo Yaounde","","21-05-2025 18:36:44","21-05-2025 18:32:37","21-05-2025 18:=
38:22","Active // No power issue Ubay: 54.4 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.4 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","cedric.tiani@matech-cameroun.com","248",=
"21-05-2025 18:36:44","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005073701","Nta=
ba","","21-05-2025 18:29:10","21-05-2025 18:24:47","21-05-2025 19:39:00","S=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overload(12Kw 2=
50A) Blaise Raoul SS IHS is iformed //Site stabilised","cedric.tiani@matech=
-cameroun.com","264","21-05-2025 18:29:10","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005073680","M=
endong vallee","","21-05-2025 18:24:50","21-05-2025 18:20:29","21-05-2025 2=
1:22:44","ACTIVE No power issue on site Ubaie=3D54.3V site on GRID, The Tx =
FME Hosiah//699699694 is informed","Fanda Brice","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No powe=
r issue on site Ubaie=3D54.3V site on GRID, The Tx FME Hosiah//699699694 is=
 informed","vanel.mbiada@matech-cameroun.com","262","21-05-2025 18:24:50","=
MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005073603","AKA=
K Nkozoa","","21-05-2025 18:12:07","21-05-2025 18:08:01","21-05-2025 19:10:=
18","Active// No power issue, site is on Grid with Ubaie=3D54,4 V TX FME Sy=
mphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power issue, site is on Grid with Ubaie=3D54,4 V TX FME Sympho=
rien (650257151) from Huawei is informed","cedric.tiani@matech-cameroun.com=
","247","21-05-2025 18:12:07","MATECH CMR"
"Closed Complete","Site Down","T1486","IHS_YND_683","NOCINC0005073596","BON=
AS YDE","","21-05-2025 18:11:05","21-05-2025 18:05:58","21-05-2025 19:10:18=
","Active// No power Issue Site on Grid Ubai =3D53.7 V, The SS Eloundou Ber=
trand (693212405) from Huawei is informed","Paul BIBOUM","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power Issue Site on Grid Ubai =3D53.7 V, The SS Eloundou Bertrand (69=
3212405) from Huawei is informed","cedric.tiani@matech-cameroun.com","308",=
"21-05-2025 18:11:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0005073586","Marche O=
dza","","21-05-2025 18:09:43","21-05-2025 16:02:03","21-05-2025 18:50:43","=
Cascaded Incident from TTO5211265","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue on site Ubaie: =
52.97 V site on Grid The TX Lionel steve (655184876 /Huawei)) is informed."=
,"system","1620602","21-05-2025 18:09:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0005073585","Mvog-Man=
ga","","21-05-2025 18:09:43","21-05-2025 16:02:03","21-05-2025 18:50:43","C=
ascaded Incident from TTO5211265","Albran Byorel","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue on site Ubaie: 5=
2.97 V site on Grid The TX Lionel steve (655184876 /Huawei)) is informed.",=
"system","1620601","21-05-2025 18:09:43","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005073578","O=
dza","IHS_YND_254, IHS_YND_580","21-05-2025 18:07:57","21-05-2025 16:02:03"=
,"21-05-2025 19:50:43","Active//No power issue on site Ubaie: 52.97 V site =
on Grid The TX Lionel steve (655184876 /Huawei)) is informed.Noticed dysjun=
ction at BTS OCM","Albran Byorel","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on sit=
e Ubaie: 52.97 V site on Grid The TX Lionel steve (655184876 /Huawei)) is i=
nformed.Noticed dysjunction at BTS OCM","vanel.mbiada@matech-cameroun.com",=
"7555","21-05-2025 18:07:57","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0005073531","Tam=
tam Weekend","","21-05-2025 17:57:36","21-05-2025 17:52:18","21-05-2025 17:=
58:01","Active: No power issue site on Grid with U=3D5,9V The TX FME Mbah H=
osiah (674007438) FROM Huawei is informed","Hyemafo Gildas","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue site on Grid with U=3D5,9V The TX FME Mbah Hosiah (6740=
07438) FROM Huawei is informed","cedric.tiani@matech-cameroun.com","319","2=
1-05-2025 17:57:36","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005073451","O=
LAMA","","21-05-2025 17:51:52","21-05-2025 17:47:34","21-05-2025 17:56:17",=
"No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (6999=
49693) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubaie =3D54.9V site on Grid. The TX FME Henri (699949693) from Huawei=
 is informed","vanel.mbiada@matech-cameroun.com","259","21-05-2025 17:51:52=
","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005073318","NTU=
I TOWN","","21-05-2025 17:21:20","21-05-2025 17:18:12","21-05-2025 20:10:34=
","Grid outage,site went down because CB(63A) in PWC that tripped MTN //He =
replaced it by a 125A","Parker Tchoup","Equipment Repair","Passive","Rectif=
ier","Rectifier - Circuit Breaker","Grid outage,site went down because CB(6=
3A) in PWC that tripped MTN //He replaced it by a 125A","cedric.tiani@matec=
h-cameroun.com","189","21-05-2025 17:21:20","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005073302","S=
IMBOCK BONAMBAPE","","21-05-2025 17:18:33","21-05-2025 17:16:27","21-05-202=
5 17:19:35","Active // No power issue site on grid with Ubaie: 52.9V TX FME=
 Flubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue site on grid with Ubaie: 52.9V TX FME Flubert (654=
266068) from Huawei is informed","vanel.mbiada@matech-cameroun.com","127","=
21-05-2025 17:18:33","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005073249","Ema=
na lycee 2","","21-05-2025 17:10:46","21-05-2025 17:01:59","21-05-2025 17:1=
6:41","Grid outage , site went down because Gen failed to started due to po=
or battery backup// Gen automatically started","Fabrice Pouakam","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge , site went down because Gen failed to started due to poor battery backu=
p// Gen automatically started","cedric.tiani@matech-cameroun.com","529","21=
-05-2025 17:10:46","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0005073126","Sac=
re Coeur Catholic Church","","21-05-2025 16:56:22","21-05-2025 16:54:16","2=
1-05-2025 16:56:01","Active//No power issue, site is on Grid with Ubaie 1=
=3D49V and Ubaie 2=3D51.3V.. The Tx FME Brice Tsague (650214096) from Huawe=
i is informed.Repetitive issues","Mboua Thierry","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue, site is on Grid with Ubaie 1=3D49V and Ubaie 2=3D51.3V.. The Tx F=
ME Brice Tsague (650214096) from Huawei is informed.Repetitive issues","ced=
ric.tiani@matech-cameroun.com","127","21-05-2025 16:56:22","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005073078","E=
vodoula OCM","","21-05-2025 16:48:36","21-05-2025 16:46:30","21-05-2025 16:=
59:38","No power issue site and with Ubaie=3D54.4 V site on Gen The FME TX =
Mouamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue site and with Ubaie=3D54.4 V site on Gen The FME =
TX Mouamadou/658791013 //From Huawei is informed","vanel.mbiada@matech-came=
roun.com","127","21-05-2025 16:48:36","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005073000","Nta=
ba","","21-05-2025 16:45:46","21-05-2025 16:38:33","21-05-2025 16:56:26","	=
Site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iforme=
d //Site stabilised","Delor Telezing","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","	Site went down due to PWC Overload(12Kw=
 250A) Blaise Raoul SS IHS is iformed //Site stabilised","cedric.tiani@mate=
ch-cameroun.com","434","21-05-2025 16:45:46","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005072982","Ema=
na lycee 2","","21-05-2025 16:44:28","21-05-2025 16:37:20","21-05-2025 16:5=
2:46","Grid outage , site went down because Gen failed to started due to po=
or battery backup// Gen automatically started","Fabrice Pouakam","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge , site went down because Gen failed to started due to poor battery backu=
p// Gen automatically started","cedric.tiani@matech-cameroun.com","429","21=
-05-2025 16:44:28","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005072774","Nko=
ulou Carriere carrefourt","","21-05-2025 16:20:14","21-05-2025 16:20:06","2=
1-05-2025 17:30:36","Grid outage, Site went down due to insufficiency of re=
ctifiers//Site stablilsed","Mba Lazare Herve","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","Grid outage, Site went down due to insuffic=
iency of rectifiers//Site stablilsed","cedric.tiani@matech-cameroun.com","9=
","21-05-2025 16:20:14","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005072733","M=
eyo","","21-05-2025 16:14:06","21-05-2025 16:08:58","21-05-2025 17:01:24","=
Grid outage site went down due to Gen overload (17KVA, 240A) SS HIS Felix Z=
ambe is informed and confirmed// Grid return","Hyemafo Gildas","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down d=
ue to Gen overload (17KVA, 240A) SS HIS Felix Zambe is informed and confirm=
ed// Grid return","vanel.mbiada@matech-cameroun.com","309","21-05-2025 16:1=
4:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005072647","Nkongtoc=
k","","21-05-2025 16:01:33","21-05-2025 14:56:38","21-05-2025 15:10:32","Ca=
scaded Incident from TTO5209562","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issues iste on Grid w=
ith U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Notic=
ed that it is impacted by Messamen ndongo not manage by IHS","system","1624=
128","21-05-2025 16:01:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005072646","Nkolfon =
Cimencam","","21-05-2025 16:01:33","21-05-2025 14:56:38","21-05-2025 15:10:=
32","Cascaded Incident from TTO5209562","Hyemafo Gildas","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active//No power issues iste on =
Grid with U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed=
.Noticed that it is impacted by Messamen ndongo not manage by IHS","system"=
,"1624135","21-05-2025 16:01:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0005072645","Ekoumdou=
m OCM","","21-05-2025 16:01:32","21-05-2025 14:56:38","21-05-2025 15:10:32"=
,"Cascaded Incident from TTO5209562","Albran Byorel","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active//No power issues iste on Grid=
 with U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Not=
iced that it is impacted by Messamen ndongo not manage by IHS","system","16=
24128","21-05-2025 16:01:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_261","NOCINC0005072644","Barriere=
","","21-05-2025 16:01:32","21-05-2025 14:56:38","21-05-2025 15:10:32","Cas=
caded Incident from TTO5209562","Hyemafo Gildas","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active//No power issues iste on Grid wit=
h U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Noticed=
 that it is impacted by Messamen ndongo not manage by IHS","system","162413=
5","21-05-2025 16:01:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0005072643","Nomayos-=
IHS","","21-05-2025 16:01:32","21-05-2025 14:56:38","21-05-2025 15:10:32","=
Cascaded Incident from TTO5209562","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active//No power issues iste on Grid wit=
h U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Noticed=
 that it is impacted by Messamen ndongo not manage by IHS","system","162413=
1","21-05-2025 16:01:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_255","NOCINC0005072642","Odza-PK1=
0","","21-05-2025 16:01:31","21-05-2025 14:56:38","21-05-2025 15:10:32","Ca=
scaded Incident from TTO5209562","Albran Byorel","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active//No power issues iste on Grid wit=
h U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Noticed=
 that it is impacted by Messamen ndongo not manage by IHS","system","162412=
4","21-05-2025 16:01:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0005072641","MVAN SAC=
EL","","21-05-2025 16:01:31","21-05-2025 14:56:38","21-05-2025 15:10:32","C=
ascaded Incident from TTO5209562","MINKA NICOLAS","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issues iste on Grid wi=
th U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Notice=
d that it is impacted by Messamen ndongo not manage by IHS","system","16241=
30","21-05-2025 16:01:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_157","NOCINC0005072639","MVAN",""=
,"21-05-2025 16:01:31","21-05-2025 14:56:38","21-05-2025 15:10:32","Cascade=
d Incident from TTO5209562","MINKA NICOLAS","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issues iste on Grid with U=
=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Noticed th=
at it is impacted by Messamen ndongo not manage by IHS","system","1624132",=
"21-05-2025 16:01:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0005072640","Nkenglik=
ok","","21-05-2025 16:01:31","21-05-2025 14:56:38","21-05-2025 15:10:32","C=
ascaded Incident from TTO5209562","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issues iste on Grid =
with U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Noti=
ced that it is impacted by Messamen ndongo not manage by IHS","system","162=
4123","21-05-2025 16:01:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_334","NOCINC0005072634","Mfou OCM=
","","21-05-2025 16:01:30","21-05-2025 14:56:38","21-05-2025 15:10:32","Cas=
caded Incident from TTO5209562","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issues iste on Grid w=
ith U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Notic=
ed that it is impacted by Messamen ndongo not manage by IHS","system","1624=
126","21-05-2025 16:01:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0005072635","Mandoumb=
a OCM","","21-05-2025 16:01:30","21-05-2025 14:56:38","21-05-2025 15:10:32"=
,"Cascaded Incident from TTO5209562","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issues iste on Gr=
id with U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.N=
oticed that it is impacted by Messamen ndongo not manage by IHS","system","=
1624130","21-05-2025 16:01:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_282","NOCINC0005072637","Meyo",""=
,"21-05-2025 16:01:30","21-05-2025 14:56:38","21-05-2025 15:10:32","Cascade=
d Incident from TTO5209562","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issues iste on Grid with U=
=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Noticed th=
at it is impacted by Messamen ndongo not manage by IHS","system","1624137",=
"21-05-2025 16:01:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_283","NOCINC0005072638","Abome","=
","21-05-2025 16:01:30","21-05-2025 14:56:38","21-05-2025 15:10:32","Cascad=
ed Incident from TTO5209562","MINKA NICOLAS","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issues iste on Grid with U=
=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Noticed th=
at it is impacted by Messamen ndongo not manage by IHS","system","1624124",=
"21-05-2025 16:01:30","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005072622","Nta=
ba","","21-05-2025 16:00:50","21-05-2025 15:52:38","21-05-2025 15:53:53","s=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","site went down due to PWC Overload(12Kw 2=
50A) Blaise Raoul SS IHS is iformed //Site stabilised","cedric.tiani@matech=
-cameroun.com","493","21-05-2025 16:00:50","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0005072540","O=
mnisport 3","","21-05-2025 15:46:40","21-05-2025 15:42:23","21-05-2025 16:5=
5:12","No power issue on site U=3D54.6V. TX HUAWEI Armand (699949553) is in=
formed","Delor Telezing","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54.6V. TX H=
UAWEI Armand (699949553) is informed","vanel.mbiada@matech-cameroun.com","2=
58","21-05-2025 15:46:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0005072437","EBOM",""=
,"21-05-2025 15:42:37","21-05-2025 14:56:38","21-05-2025 15:10:32","Cascade=
d Incident from TTO5209562","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issues iste on Grid with U=
=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.Noticed th=
at it is impacted by Messamen ndongo not manage by IHS","system","1624129",=
"21-05-2025 15:42:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_583","NOCINC0005072436","Nsam Sof=
avinc T0","","21-05-2025 15:42:36","21-05-2025 14:56:38","21-05-2025 15:10:=
32","Cascaded Incident from TTO5209562","MINKA NICOLAS","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active//No power issues iste on G=
rid with U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is informed.=
Noticed that it is impacted by Messamen ndongo not manage by IHS","system",=
"1624126","21-05-2025 15:42:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005072416","Emana Ly=
cee","","21-05-2025 15:41:39","21-05-2025 15:26:47","21-05-2025 15:40:13","=
Cascaded Incident from TTO5209926","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage.gen failed to start d=
ue to poor backup//GRID return","system","1622415","21-05-2025 15:41:39","M=
ATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005072316","Ema=
na lycee 2","IHS_YND_274","21-05-2025 15:29:59","21-05-2025 15:26:47","21-0=
5-2025 15:41:42","Grid outage.gen failed to start due to poor backup//GRID =
return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage.gen failed to start due to poor back=
up//GRID return","cedric.tiani@matech-cameroun.com","193","21-05-2025 15:29=
:59","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0005072315","A=
hala","","21-05-2025 15:29:36","21-05-2025 14:56:38","21-05-2025 15:10:32",=
"","MINKA NICOLAS","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","Active//No power issues iste on Grid with U=3D52.1V ,The FME TX Fulber=
t (654266068) from Huawei is informed.Noticed that it is impacted by Messam=
en ndongo not manage by IHS","vanel.mbiada@matech-cameroun.com","1624127","=
21-05-2025 15:29:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0005072006","OKOA Pea=
ge","","21-05-2025 15:06:49","21-05-2025 14:53:59","21-05-2025 16:06:16","A=
ctive//No power issue on site Ubaie =3D54,6 V site on Grid The TX FME Marti=
al//690087047 from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54,6 V site on Grid The TX FME Martial//69008=
7047 from Huawei is informed","system","770","21-05-2025 15:06:49","MATECH =
CMR"
"Cancelled","Warning","","IHS_YND_314","NOCINC0005072004","Sous Prefecture"=
,"","21-05-2025 15:06:49","","","Cascaded Incident from TTO5209597 - Cascad=
e Removed From TTO5209597","Fanda Brice","","","","","","system","770","21-=
05-2025 15:06:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0005072005","Mbankomo=
 IHS","","21-05-2025 15:06:49","21-05-2025 14:53:59","21-05-2025 16:06:30",=
"Cascaded Incident from TTO5209597 - Cascade Removed From TTO5209597","Fand=
a Brice","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Cascaded Incident from TTO5209597","system","770","21-=
05-2025 15:06:49","MATECH CMR"
"Closed Complete","Site Down","CTR_525","IHS_YND_544","NOCINC0005071993","J=
ean Vespa 2","","21-05-2025 15:05:29","21-05-2025 14:53:59","21-05-2025 16:=
06:27","Active//No power issue on site Ubaie =3D54,6 V site on Grid The TX =
FME Martial//690087047 from Huawei is informed","Mboua Thierry","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site Ubaie =3D54,6 V site on Grid The TX FME Mar=
tial//690087047 from Huawei is informed","vanel.mbiada@matech-cameroun.com"=
,"691","21-05-2025 15:05:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005071988","Angongo"=
,"","21-05-2025 15:04:32","21-05-2025 14:56:38","21-05-2025 15:10:32","Casc=
aded Incident from TTO5209550","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Cascaded Incident from TTO5209550","system",=
"1624133","21-05-2025 15:04:32","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005071976","NTU=
I TOWN","","21-05-2025 15:03:36","21-05-2025 14:54:25","21-05-2025 16:07:09=
","Grid outage,site went down because CB(63A) in PWC that tripped MTN //He =
rearmed it","Parker Tchoup","Equipment Repair","Passive","Rectifier","Recti=
fier - Circuit Breaker","Grid outage,site went down because CB(63A) in PWC =
that tripped MTN //He rearmed it","cedric.tiani@matech-cameroun.com","552",=
"21-05-2025 15:03:36","MATECH CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0005071970","C=
lge-Advantiste","","21-05-2025 15:02:39","21-05-2025 14:56:38","21-05-2025 =
15:10:32","tx","MINKA NICOLAS","Cascade Outage","Active","Cascade Active","=
Cascade Active","Active//No power issues iste on Grid with U=3D52.1V ,The F=
ME TX Fulbert (654266068) from Huawei is informed.Noticed that it is impact=
ed by Messamen ndongo not manage by IHS","vanel.mbiada@matech-cameroun.com"=
,"1624125","21-05-2025 15:02:39","MATECH CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0005071962","N=
omayos","IHS_YND_334, IHS_YND_367, IHS_YND_282, IHS_YND_283, IHS_YND_313, I=
HS_YND_674, IHS_YND_157, IHS_YND_348, IHS_YND_510, IHS_YND_339, IHS_YND_255=
, IHS_YND_697, IHS_YND_261, IHS_YND_583, IHS_YND_698, IHS_YND_291, IHS_YND_=
762, IHS_YND_350, IHS_YND_335, IHS_YND_165, IHS_YND_349, IHS_YND_253","21-0=
5-2025 15:01:21","21-05-2025 14:56:38","21-05-2025 15:10:32","Active//No po=
wer issues iste on Grid with U=3D52.1V ,The FME TX Fulbert (654266068) from=
 Huawei is informed.Noticed that it is impacted by Messamen ndongo not mana=
ge by IHS","Fanda Brice","Customer Equipment Failure","Active","Active Equi=
pment Failure","Affected by 3rd Party Site","Active//No power issues iste o=
n Grid with U=3D52.1V ,The FME TX Fulbert (654266068) from Huawei is inform=
ed.Noticed that it is impacted by Messamen ndongo not manage by IHS","vanel=
.mbiada@matech-cameroun.com","284","21-05-2025 15:01:21","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0005071951","E=
beba","","21-05-2025 14:59:34","21-05-2025 14:56:38","21-05-2025 15:10:32",=
"","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active=
","Active//No power issues iste on Grid with U=3D52.1V ,The FME TX Fulbert =
(654266068) from Huawei is informed.Noticed that it is impacted by Messamen=
 ndongo not manage by IHS","vanel.mbiada@matech-cameroun.com","1624134","21=
-05-2025 14:59:34","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0005071947","M=
ambine","","21-05-2025 14:58:37","21-05-2025 14:56:38","21-05-2025 15:10:32=
","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","Active//No power issues iste on Grid with U=3D52.1V ,The FME TX Fulber=
t (654266068) from Huawei is informed.Noticed that it is impacted by Messam=
en ndongo not manage by IHS","vanel.mbiada@matech-cameroun.com","1624133","=
21-05-2025 14:58:37","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005071931","A=
fanoya","","21-05-2025 14:57:37","21-05-2025 14:56:38","21-05-2025 15:10:32=
","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","Active//No power issues iste on Grid with U=3D52.1V ,The FME TX Ful=
bert (654266068) from Huawei is informed.Noticed that it is impacted by Mes=
samen ndongo not manage by IHS","vanel.mbiada@matech-cameroun.com","1624136=
","21-05-2025 14:57:37","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0005071929","M=
fou EPC","","21-05-2025 14:57:04","21-05-2025 14:56:38","21-05-2025 15:10:3=
2","","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Active//No power issues iste on Grid with U=3D52.1V ,The FME TX =
Fulbert (654266068) from Huawei is informed.Noticed that it is impacted by =
Messamen ndongo not manage by IHS","vanel.mbiada@matech-cameroun.com","1624=
125","21-05-2025 14:57:04","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005071857","Nta=
ba","","21-05-2025 14:44:39","21-05-2025 14:40:26","21-05-2025 14:58:24","s=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //site stabilised ","Delor Telezing","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","site went down due to PWC Overload(12Kw =
250A) Blaise Raoul SS IHS is iformed //site stabilised ","cedric.tiani@mate=
ch-cameroun.com","254","21-05-2025 14:44:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0005071789","MONTEE N=
KONDENGUI","","21-05-2025 14:36:47","21-05-2025 14:33:34","21-05-2025 21:27=
:19","Cascaded Incident from TTO5209384","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid only site, no space to d=
eploy MDG // grid returned","system","1625458","21-05-2025 14:36:47","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0005071784","M=
obil-Kondengui","IHS_YND_682","21-05-2025 14:36:05","21-05-2025 14:33:34","=
21-05-2025 21:27:19","Grid only site, no space to deploy MDG // grid return=
ed","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid only site, no space to deploy MDG // grid returned","gerard.tchangoue@=
matech-cameroun.com","152","21-05-2025 14:36:05","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005071780","Odz=
a II OCM","","21-05-2025 14:35:13","21-05-2025 14:29:59","21-05-2025 16:38:=
23","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction // Site stabilised","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, site went down b=
ecause gen failed to start due to PWC ZTE malfunction // Site stabilised","=
cedric.tiani@matech-cameroun.com","315","21-05-2025 14:35:13","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005071702","Ema=
na lycee 2","","21-05-2025 14:19:10","21-05-2025 14:13:00","21-05-2025 14:3=
6:17","Grid outage.gen failed to start due to poor backup//Gen start automa=
tically","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage.gen failed to start due to poor bac=
kup//Gen start automatically","edwige.kapawo@matech-cameroun.com","371","21=
-05-2025 14:19:10","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005071604","EMA=
NA BILICK CITY","","21-05-2025 14:06:21","21-05-2025 14:02:11","21-05-2025 =
14:10:17","Grid outage, site down because site behaves as Grid only site (G=
en Noise)//Grid return","Fabrice Pouakam","Access Denial","Lease Or Legal",=
"Landlord Related Issues","Access Issue - Land Lord","Grid outage, site dow=
n because site behaves as Grid only site (Gen Noise)//Grid return","edwige.=
kapawo@matech-cameroun.com","251","21-05-2025 14:06:21","MATECH CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0005071438","N=
R-Omnisport","","21-05-2025 13:46:04","21-05-2025 13:41:59","21-05-2025 13:=
54:01","Site went down due to plan work activity (SWAP of PWC) by Njoya (LO=
UMAD/ 690811271) // End of work","Delor Telezing","Installation Activity","=
Passive","Planned Activity","Installation Activity","Site went down due to =
plan work activity (SWAP of PWC) by Njoya (LOUMAD/ 690811271) // End of wor=
k","gerard.tchangoue@matech-cameroun.com","245","21-05-2025 13:46:04","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005071430","S=
imbock OCM","","21-05-2025 13:44:45","21-05-2025 13:42:38","21-05-2025 13:4=
5:56","Grid outage, site went down due 2/3 rectifiers faulty // Grid stabil=
ised","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Grid outage, site went down due 2/3 rectifiers faulty // Grid stab=
ilised","gerard.tchangoue@matech-cameroun.com","128","21-05-2025 13:44:45",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0005071336","M=
vog-Ada_OCM","","21-05-2025 13:29:50","21-05-2025 13:24:43","21-05-2025 13:=
46:46","Grid Only, No space to deploy MGE  // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space =
to deploy MGE  // Grid return","gerard.tchangoue@matech-cameroun.com","308"=
,"21-05-2025 13:29:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005071329","MEHANDAN=
","","21-05-2025 13:28:22","21-05-2025 13:22:01","21-05-2025 13:42:23","Cas=
caded Incident from TTO5208889","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction //Grid return","system","16236=
04","21-05-2025 13:28:22","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005071313","O=
dza II OCM","IHS_YND_528","21-05-2025 13:27:14","21-05-2025 13:22:01","21-0=
5-2025 13:42:46","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction //Grid return","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site wen=
t down because gen failed to start due to PWC ZTE malfunction //Grid return=
","gerard.tchangoue@matech-cameroun.com","314","21-05-2025 13:27:14","MATEC=
H CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0005071256","Nlo=
ng Mvolye New","","21-05-2025 13:20:16","21-05-2025 13:17:06","21-05-2025 1=
3:18:36","Grid outage, Site went down because Gen failed to start due to ba=
ttery Gen faulty// He started Gen with external battery","Paul BIBOUM","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage=
, Site went down because Gen failed to start due to battery Gen faulty// He=
 started Gen with external battery","edwige.kapawo@matech-cameroun.com","24=
2","21-05-2025 13:20:16","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005071242","Mim=
boman4","","21-05-2025 13:18:33","21-05-2025 13:13:24","21-05-2025 13:31:30=
","Grid outage, site went down because gen failed to start due to solenoid =
valve // He bypassed solenoid valve and Gen manually started","Mba Lazare H=
erve","Equipment Repair","Passive","ACDG Gen","ACDG - Solenoid Coil","Grid =
outage, site went down because gen failed to start due to solenoid valve //=
 He bypassed solenoid valve and Gen manually started","edwige.kapawo@matech=
-cameroun.com","310","21-05-2025 13:18:33","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005071128","S=
imbock OCM","","21-05-2025 13:01:41","21-05-2025 10:59:18","21-05-2025 11:0=
1:18","Grid outage, site went down due 2/3 rectifiers faulty // Grid stabil=
ised","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Grid outage, site went down due 2/3 rectifiers faulty // Grid stab=
ilised","gerard.tchangoue@matech-cameroun.com","7344","21-05-2025 13:01:41"=
,"MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005070920","NTU=
I TOWN","","21-05-2025 12:31:03","21-05-2025 12:28:49","21-05-2025 13:02:09=
","Grid fluctuations // Grid Stabilized","Parker Tchoup","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid fluctuations // Grid=
 Stabilized","edwige.kapawo@matech-cameroun.com","136","21-05-2025 12:31:03=
","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005070824","A=
kak-Nkozoa-MTN-IHS","","21-05-2025 12:19:43","21-05-2025 12:14:17","21-05-2=
025 14:37:10","Site went down due to plan work (PM) on site done by Giresse=
 (MATECH) // End of Work","Fabrice Pouakam","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to plan w=
ork (PM) on site done by Giresse (MATECH) // End of Work","gerard.tchangoue=
@matech-cameroun.com","328","21-05-2025 12:19:43","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005070792","Mim=
boman4","IHS_YND_709","21-05-2025 12:13:40","21-05-2025 12:09:31","21-05-20=
25 12:15:05","Grid fluctuations, site went down because Gen failed to start=
 due to grid bad voltage // Grid stabilised","Mba Lazare Herve","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tions, site went down because Gen failed to start due to grid bad voltage /=
/ Grid stabilised","edwige.kapawo@matech-cameroun.com","250","21-05-2025 12=
:13:40","MATECH CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0005070782","Nko=
lo II New","","21-05-2025 12:11:44","21-05-2025 12:09:31","21-05-2025 12:15=
:05","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid fluctuations, site went down because Gen failed to sta=
rt due to grid bad voltage // Grid stabilised","edwige.kapawo@matech-camero=
un.com","1627844","21-05-2025 12:11:44","MATECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0005070440","N=
koa Ayos","","21-05-2025 11:34:12","21-05-2025 11:26:04","21-05-2025 15:06:=
20","Site impacted by GSO (CTR_389)","MINKA NICOLAS","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","FME Lionel (698642145)fom Huawei was=
 on site working","gerard.tchangoue@matech-cameroun.com","1630341","21-05-2=
025 11:34:12","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005070396","T=
amtam Weekend","","21-05-2025 11:30:44","21-05-2025 11:21:59","21-05-2025 1=
2:21:59","No power issue site on Grid with U=3D52.7V The TX FME Mbah Hosiah=
 (674007438) FROM Huawei is informed .","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue site on Grid with U=3D52.7V The TX FME Mbah Hosiah (674007438) FRO=
M Huawei is informed .","gerard.tchangoue@matech-cameroun.com","526","21-05=
-2025 11:30:44","MATECH CMR"
"Closed Complete","Site Down","CTR_419","IHS_YND_227","NOCINC0005070327","M=
vog Betsi","","21-05-2025 11:21:51","21-05-2025 11:14:44","21-05-2025 11:27=
:44","Grid-Gen, eneo fluctuation, site down due to poor backup // eneo satb=
ilized","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid-Gen, eneo fluctuation, site down due to poor=
 backup // eneo satbilized","gerard.tchangoue@matech-cameroun.com","427","2=
1-05-2025 11:21:51","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005070305","Nko=
lbong","","21-05-2025 11:18:27","21-05-2025 11:11:19","21-05-2025 13:45:31"=
,"Site went Down because Gen started and stopped due to Gen overload(22kva/=
/350A) // Grid return","Delor Telezing","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","Site went Down because Gen started and stopped due =
to Gen overload(22kva//350A) // Grid return","edwige.kapawo@matech-cameroun=
.com","458","21-05-2025 11:18:27","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0005070236","G=
SO","IHS_YND_067","21-05-2025 11:08:48","21-05-2025 11:07:39","21-05-2025 1=
5:06:20","FME Lionel (698642145)fom Huawei was on site working//End of work=
","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","FME Lionel (698642145)fom Huawei was on site =
working//End of work","gerard.tchangoue@matech-cameroun.com","70","21-05-20=
25 11:08:48","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0005070007","UPA=
C LP","","21-05-2025 10:42:16","21-05-2025 10:40:06","21-05-2025 11:13:48",=
"Grid outage .no space to deploy mobile gen // Grid returned","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage .no s=
pace to deploy mobile gen // Grid returned","edwige.kapawo@matech-cameroun.=
com","132","21-05-2025 10:42:16","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005069999","Sof=
avinc","","21-05-2025 10:39:36","21-05-2025 10:36:30","21-05-2025 10:54:30"=
,"Site went down due to insufficiency of rectifiers on site // He reduced t=
he load","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficiency of rectifiers on site // He =
reduced the load","edwige.kapawo@matech-cameroun.com","187","21-05-2025 10:=
39:36","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005069756","NTU=
I TOWN","","21-05-2025 10:05:29","21-05-2025 10:04:59","21-05-2025 10:58:44=
","Grid fluctuations // Grid Stabilized","Parker Tchoup","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid fluctuations // Grid=
 Stabilized","edwige.kapawo@matech-cameroun.com","31","21-05-2025 10:05:29"=
,"MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005069706","Nko=
langaa","","21-05-2025 10:00:12","21-05-2025 09:57:43","21-05-2025 12:42:06=
","Site went down due to cable burned in PWC // Burned cable replaced: site=
 on grid","Mba Lazare Herve","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active // No power issue on site U=
bay =3D 53.1V Site on Grid.  TX FME Henri (699949693/Huawei) is on site for=
 works","edwige.kapawo@matech-cameroun.com","150","21-05-2025 10:00:12","MA=
TECH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0005069569","Mvo=
g-Ada_OCM","","21-05-2025 09:48:21","21-05-2025 09:41:11","21-05-2025 10:00=
:50","Grid Only, No space to deploy MGE // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to =
deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","431","21-05=
-2025 09:48:21","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005069443","SAA=
 Entrance","","21-05-2025 09:26:23","21-05-2025 09:22:13","21-05-2025 09:32=
:49","Grid fluctuation, Site went down because gen fails to start due to gr=
id bad voltage // He bypassed the Grid and site on Gen","Parker Tchoup","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuation, Site went down because gen fails to start due to grid bad vol=
tage // He bypassed the Grid and site on Gen","edwige.kapawo@matech-camerou=
n.com","251","21-05-2025 09:26:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005069366","MEHANDAN=
","","21-05-2025 09:10:49","21-05-2025 09:08:47","21-05-2025 09:16:47","Cas=
caded Incident from TTO5206942","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Grid return","system","1638=
418","21-05-2025 09:10:49","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005069361","O=
dza II OCM","IHS_YND_528","21-05-2025 09:09:54","21-05-2025 09:08:47","21-0=
5-2025 09:16:47","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid return","Albran Byorel","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site we=
nt down because gen failed to start due to PWC ZTE malfunction // Grid retu=
rn","gerard.tchangoue@matech-cameroun.com","69","21-05-2025 09:09:54","MATE=
CH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005069282","SAA=
 Entrance","","21-05-2025 08:59:54","21-05-2025 08:55:03","21-05-2025 09:07=
:58","Grid fluctuation, Site went down because gen fails to start due to gr=
id bad voltage // He bypassed the Grid and site on Gen","Parker Tchoup","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuation, Site went down because gen fails to start due to grid bad vol=
tage // He bypassed the Grid and site on Gen","edwige.kapawo@matech-camerou=
n.com","293","21-05-2025 08:59:54","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005069238","N=
koabang Ebolmedjock","","21-05-2025 08:53:31","21-05-2025 08:48:23","21-05-=
2025 09:50:35","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","gerard.tchangoue@m=
atech-cameroun.com","309","21-05-2025 08:53:31","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005069009","Mim=
boman4","","21-05-2025 08:15:31","20-05-2025 22:06:18","20-05-2025 23:31:43=
","Backtracking , Grid fluctuations, site went down because Gen failed to s=
tart due to grid bad voltage // Grid stabilised","Mba Lazare Herve","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid flu=
ctuations, site went down because Gen failed to start due to grid bad volta=
ge // Grid stabilised","edwige.kapawo@matech-cameroun.com","36555","21-05-2=
025 08:15:31","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005068625","N=
kolbong","","21-05-2025 06:51:59","21-05-2025 06:16:49","21-05-2025 09:44:0=
8","Site went Down because Gen started and stopped due to Gen overload(22kv=
a//350A) // Grid return","Delor Telezing","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Site went Down because Gen started and stopped du=
e to Gen overload(22kva//350A) // Grid return","gerard.tchangoue@matech-cam=
eroun.com","2167","21-05-2025 06:51:59","MATECH CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0005068291","Ako=
no","","21-05-2025 05:20:17","","","Grid fluctuation,site alarming because =
Gen failed to start due to Grid bad voltage//site on Gen","Fanda Brice","Wa=
rning","Warning","POWER","Warning - National Grid - Grid Incomplete Phase",=
"Grid fluctuation,site alarming because Gen failed to start due to Grid bad=
 voltage//site on Gen","christelle.ngonga@matech-cameroun.com","1947","21-0=
5-2025 05:20:17","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005068113","Nko=
l-Mebanga","","21-05-2025 04:16:36","21-05-2025 04:12:28","21-05-2025 11:18=
:28","Solar only site, // solar returned","Parker Tchoup","Equipment Repair=
","Passive","Solar","Solar Panel Issue","Solar only site, // solar returned=
","christelle.ngonga@matech-cameroun.com","248","21-05-2025 04:16:36","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0005068037","O=
ssombe","","21-05-2025 03:45:21","21-05-2025 03:43:03","21-05-2025 07:04:44=
","site went down because gen ran until fuel shortage // refueling done","P=
arker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","site went d=
own because gen ran until fuel shortage // refueling done","christelle.ngon=
ga@matech-cameroun.com","139","21-05-2025 03:45:21","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005067689","M=
ontee-Jouvence-II","","21-05-2025 01:29:17","19-05-2025 16:09:47","20-05-20=
25 07:54:22","No power issue on site, site on Grid with Ubaie=3D51.1V The T=
x Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site, site on Grid with Ubaie=3D51.1V The Tx Fm=
e Mbah Hosiah //674007438/ from HUAWEI is informed","christelle.ngonga@mate=
ch-cameroun.com","119971","21-05-2025 01:29:17","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005067659","E=
mana Lycee","","21-05-2025 01:21:19","21-05-2025 01:19:39","21-05-2025 06:1=
8:09","Grid Outage Site went down due to Gen overload // he reduced load an=
d restarted gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid Outage Site went down due to Gen overload // he red=
uced load and restarted gen","christelle.ngonga@matech-cameroun.com","102",=
"21-05-2025 01:21:19","MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0005067634","B=
astos Bir","","21-05-2025 01:07:02","19-05-2025 18:50:44","19-05-2025 20:01=
:30","Active//No power issue, site is on Gen with Ubaie=3D54.5 V, Eloundou =
bertrant(652586578) from Huawei is informed","Mboua Thierry","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue, site is on Gen with Ubaie=3D54.5 V, Eloundou bertrant=
(652586578) from Huawei is informed","christelle.ngonga@matech-cameroun.com=
","108979","21-05-2025 01:07:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005067633","Messassi=
 okolo","","21-05-2025 01:06:25","19-05-2025 18:52:35","19-05-2025 20:54:38=
","Cascaded Incident from TTO5193765","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (no Gen)//Grid return","system","1667460","=
21-05-2025 01:06:25","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005067593","ODZ=
A BORNE 10","","21-05-2025 00:53:56","21-05-2025 00:49:44","21-05-2025 02:1=
1:48","Site down because 1 rectifier planted the others // Rectifiers reset=
ed , site on grid","Albran Byorel","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site down because 1 rectifier planted the others // Re=
ctifiers reseted , site on grid","christelle.ngonga@matech-cameroun.com","2=
53","21-05-2025 00:53:56","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005067475","Mok=
olo Yaounde","","21-05-2025 00:08:03","21-05-2025 00:05:57","21-05-2025 01:=
50:42","Grid outage no space to deploy the MDG, // power returned","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
no space to deploy the MDG, // power returned","vanel.mbiada@matech-camerou=
n.com","128","21-05-2025 00:08:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005067341","MEHANDAN=
","","20-05-2025 23:26:35","20-05-2025 23:22:32","21-05-2025 00:35:53","Cas=
caded Incident from TTO5204708","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction //Grid return","system","16731=
39","20-05-2025 23:26:35","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005067338","O=
dza II OCM","IHS_YND_528","20-05-2025 23:25:39","20-05-2025 23:22:32","21-0=
5-2025 00:35:53","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction //Grid return","Albran Byorel","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down because gen failed to start due to PWC ZTE malfunction //Grid re=
turn","gaelle.njiofack@matech-cameroun.com","189","20-05-2025 23:25:39","MA=
TECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005066945","Nko=
langaa","","20-05-2025 21:41:56","20-05-2025 21:34:41","20-05-2025 23:32:00=
","Site down due to disjonction in the DC Box // DC box CB reamed, site on =
grid.","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Cir=
cuit Breaker Tripped","Site down due to disjonction in the DC Box // DC box=
 CB reamed, site on grid.","loic.noumsi@matech-cameroun.com","436","20-05-2=
025 21:41:56","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005066826","N=
kolbong","","20-05-2025 21:17:49","20-05-2025 21:12:39","21-05-2025 05:47:5=
0","Grid contactor Burn,Site went down because Gen started and stopped due =
to Gen overload(22kva//350A) // Grid return","Delor Telezing","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid contactor Burn,Site went=
 down because Gen started and stopped due to Gen overload(22kva//350A) // G=
rid return","gaelle.njiofack@matech-cameroun.com","311","20-05-2025 21:17:4=
9","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0005066727","NYO=
M FACE MAETUR","","20-05-2025 20:58:19","20-05-2025 20:53:04","20-05-2025 2=
1:16:25","Grid fluctuation,Site went down because Gen failed to start due t=
o Grid bad voltage // Grid stabilized","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,Si=
te went down because Gen failed to start due to Grid bad voltage // Grid st=
abilized","loic.noumsi@matech-cameroun.com","317","20-05-2025 20:58:19","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0005066649","Carrefou=
rt Nkomo","","20-05-2025 20:40:50","20-05-2025 20:34:20","20-05-2025 23:57:=
11","No power issue site on grid with U=3D52.8 v Lionnel Steeve from Huawei=
 is informed","Mba Lazare Herve","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wi=
th U=3D52.8 v Lionnel Steeve from Huawei is informed","system","390","20-05=
-2025 20:40:50","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005066639","N=
komo","","20-05-2025 20:39:33","20-05-2025 20:11:20","20-05-2025 20:13:40",=
"Ticket error (Doublon)","Mba Lazare Herve","Incorrectly Logged Tickets","E=
rror","Error","Error","Ticket error (Doublon)","ludivine.ngamaleu@ihstowers=
.com","2909","20-05-2025 20:39:33","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005066636","NYO=
M 2 IHS","","20-05-2025 20:39:15","20-05-2025 20:30:10","20-05-2025 20:40:0=
4","Grid outage,site went down because Gen started and stopped with alarm '=
'oil pressure''// He reseted the Gen Card and site on Grid ","Fabrice Pouak=
am","Equipment Repair","Passive","ACDG Gen","ACDG - Oil Pressure Sensor Fau=
lty","Grid outage,site went down because Gen started and stopped with alarm=
 ''oil pressure''// He reseted the Gen Card and site on Grid ","loic.noumsi=
@matech-cameroun.com","546","20-05-2025 20:39:15","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0005066572","N=
komo","","20-05-2025 20:26:16","20-05-2025 22:04:04","20-05-2025 22:18:23",=
"site went down because   (03/05) rectifiers took and alarm// Rectifiers re=
seted , site on grid","Mba Lazare Herve","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","site went down due to (03/05) rectifiers took an=
d alarm// Rectifiers reseted , site on grid","gaelle.njiofack@matech-camero=
un.com","5791","20-05-2025 20:26:16","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005066565","N=
taba","","20-05-2025 20:25:04","20-05-2025 20:20:57","21-05-2025 09:03:08",=
"Site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is infor=
med //Site stabilised (Site up after Power reset done )","Delor Telezing","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site=
 went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is informed /=
/Site stabilised (Site up after Power reset done )","gaelle.njiofack@matech=
-cameroun.com","248","20-05-2025 20:25:04","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005066558","A=
kak-Nkozoa-MTN-IHS","","20-05-2025 20:22:55","20-05-2025 20:19:46","20-05-2=
025 21:13:35","Grid Bad voltage, Site went down because Gen stopped with ""=
high temp"" alarm // He added water and started Gen manualy","Fabrice Pouak=
am","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid Bad volta=
ge, Site went down because Gen stopped with ""high temp"" alarm // He added=
 water and started Gen manualy","gaelle.njiofack@matech-cameroun.com","191"=
,"20-05-2025 20:22:55","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005066492","SOA=
 TOWN","","20-05-2025 20:03:27","20-05-2025 19:54:15","20-05-2025 21:59:57"=
,"Grid outage, site went down due to Rectifier issue // Site stabilised","S=
iligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Grid outage, site went down due to Rectifier issue // Site stabilised","loi=
c.noumsi@matech-cameroun.com","553","20-05-2025 20:03:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005066470","Bastos B=
ethesda","","20-05-2025 19:57:50","17-05-2025 13:06:27","19-05-2025 09:31:3=
9","Cascaded Incident from TTO5175786","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Only, No space to deploy//=
 Grid return ","system","1666694","20-05-2025 19:57:50","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005066326","M=
endong vallee","","20-05-2025 19:30:34","20-05-2025 19:26:16","21-05-2025 0=
6:37:05","Grid outage site went down due to Gen overload (20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed and confirmed  // Grid returned","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site=
 went down due to Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informe=
d and confirmed  // Grid returned","gaelle.njiofack@matech-cameroun.com","2=
59","20-05-2025 19:30:34","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005066296","A=
WAE OCM","","20-05-2025 19:24:32","20-05-2025 19:20:25","20-05-2025 21:28:4=
6","Grid outage site went down because Gen failed to start due PWC ZTE dysf=
onctionned // He reset the PWC and Gen manually started","Mba Lazare Herve"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"Grid outage site went down because Gen failed to start due PWC ZTE dysfon=
ctionned // He reset the PWC and Gen manually started","gaelle.njiofack@mat=
ech-cameroun.com","249","20-05-2025 19:24:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005066292","Nkongtoc=
k","","20-05-2025 19:23:54","20-05-2025 19:20:17","20-05-2025 19:23:08","Ca=
scaded Incident from TTO5203519","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due 2/3=
 rectifiers faulty // Grid stabilised","system","1687406","20-05-2025 19:23=
:54","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005066281","S=
imbock OCM","IHS_YND_349","20-05-2025 19:22:24","20-05-2025 19:20:17","20-0=
5-2025 19:23:08","Grid outage, site went down due 2/3 rectifiers faulty // =
Grid stabilised","Hyemafo Gildas","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Grid outage, site went down due 2/3 rectifiers faulty /=
/ Grid stabilised","gaelle.njiofack@matech-cameroun.com","128","20-05-2025 =
19:22:24","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005066145","Eto=
ug ebe Meweulo","","20-05-2025 18:57:36","20-05-2025 18:56:24","20-05-2025 =
20:24:17","Grid fluctuation site went down because Gen started and stopped =
due to Grid bad voltage // Grid stopped manually and Gen start","Hyemafo Gi=
ldas","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply =
Issue","Grid fluctuation site went down because Gen started and stopped due=
 to Grid bad voltage // Grid stopped manually and Gen start","loic.noumsi@m=
atech-cameroun.com","73","20-05-2025 18:57:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005066125","MEHANDAN=
","","20-05-2025 18:53:47","20-05-2025 18:52:07","20-05-2025 19:01:40","Cas=
caded Incident from TTO5203348","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to PWC ZTE malfunction // Grid return","system","168=
2336","20-05-2025 18:53:47","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005066121","O=
dza II OCM","IHS_YND_528","20-05-2025 18:53:13","20-05-2025 18:52:07","20-0=
5-2025 19:02:05","	Grid outage, site went down because gen failed to start =
due to PWC ZTE malfunction // Grid return","Albran Byorel","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","	Grid outage, site =
went down because gen failed to start due to PWC ZTE malfunction // Grid re=
turn","gaelle.njiofack@matech-cameroun.com","68","20-05-2025 18:53:13","MAT=
ECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005066102","NYO=
M 2 IHS","","20-05-2025 18:50:17","20-05-2025 18:42:07","20-05-2025 19:58:5=
1","Grid fluctuations, Site went down due to grid bad voltage // He bypasse=
d Grid and started Gen manually","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Grid fluctuations, Site w=
ent down due to grid bad voltage // He bypassed Grid and started Gen manual=
ly","loic.noumsi@matech-cameroun.com","491","20-05-2025 18:50:17","MATECH C=
MR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0005066058","Ngo=
usso Vallee","","20-05-2025 18:42:43","20-05-2025 18:38:16","20-05-2025 18:=
40:05","Site went down due to insufficiency of rectifiers // Grid stabilise=
d","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site went down due to insufficiency of rectifiers // Grid stabilised",=
"loic.noumsi@matech-cameroun.com","268","20-05-2025 18:42:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005066039","Emana Ly=
cee","","20-05-2025 18:40:10","20-05-2025 18:12:48","20-05-2025 18:29:39","=
Cascaded Incident from TTO5203147","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down befo=
re Gen started due to poor battery backup // Gen start automatically","syst=
em","1684635","20-05-2025 18:40:10","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0005066020","O=
mnisport 3","","20-05-2025 18:32:38","20-05-2025 18:28:27","20-05-2025 20:5=
4:04","Site went down because FME Njoya Mohamed (658849259) from I-ENG was =
on site for planned activitiy( swapp of PWC) // End of work","Delor Telezin=
g","Installation Activity","Passive","Planned Activity","Installation Activ=
ity","Site went down because FME Njoya Mohamed (658849259) from I-ENG was o=
n site for planned activitiy( swapp of PWC) // End of work","gaelle.njiofac=
k@matech-cameroun.com","252","20-05-2025 18:32:38","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005065944","E=
mana lycee 2","IHS_YND_274","20-05-2025 18:19:55","20-05-2025 18:12:48","20=
-05-2025 18:29:39","Grid outage , site went down before Gen started due to =
poor battery backup // Gen start automatically","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age , site went down before Gen started due to poor battery backup // Gen s=
tart automatically","gaelle.njiofack@matech-cameroun.com","429","20-05-2025=
 18:19:55","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005065895","Nta=
ba","","20-05-2025 18:12:14","20-05-2025 18:04:06","20-05-2025 18:22:10","S=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is informe=
d //Site stabilised","Delor Telezing","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Site went down due to PWC Overload(1=
2Kw 250A) Blaise Raoul SS IHS is informed //Site stabilised","loic.noumsi@m=
atech-cameroun.com","489","20-05-2025 18:12:14","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005065643","NTU=
I TOWN","","20-05-2025 17:31:21","20-05-2025 17:25:12","20-05-2025 19:10:40=
","Site went down due to dysfunctionned rectifiers, SS IHS Felix Bateu is i=
nformed // He reseted it","Parker Tchoup","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down due to dysfunctionned rectifiers=
, SS IHS Felix Bateu is informed // He reseted it","loic.noumsi@matech-came=
roun.com","370","20-05-2025 17:31:21","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005065578","Sof=
avinc","","20-05-2025 17:27:56","20-05-2025 17:23:47","20-05-2025 17:41:35"=
,"Site went down because Gen failed to start due to card Ge DYSFUNCTION // =
He reseted it and started Gen manually","MINKA NICOLAS","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Site went down because Gen fai=
led to start due to card Ge DYSFUNCTION // He reseted it and started Gen ma=
nually","loic.noumsi@matech-cameroun.com","250","20-05-2025 17:27:56","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005065444","E=
mana lycee 2","IHS_YND_274","20-05-2025 17:15:40","20-05-2025 17:10:31","20=
-05-2025 17:27:38","Grid outage , site went down before Gen started due to =
poor battery backup // Gen start automatically","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age , site went down before Gen started due to poor battery backup // Gen s=
tart automatically","gaelle.njiofack@matech-cameroun.com","310","20-05-2025=
 17:15:40","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005065442","E=
mana Lycee","","20-05-2025 17:14:09","20-05-2025 17:10:31","20-05-2025 17:2=
7:38","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage , site went down before Gen started due to poor=
 battery backup // Gen start automatically","gaelle.njiofack@matech-camerou=
n.com","1681017","20-05-2025 17:14:09","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005065406","Sof=
avinc","","20-05-2025 17:10:12","20-05-2025 17:07:01","20-05-2025 17:13:15"=
,"Site went down because Gen failed to start due to card Ge DYSFUNCTION // =
He reseted it and started Gen manually","MINKA NICOLAS","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Site went down because Gen fai=
led to start due to card Ge DYSFUNCTION // He reseted it and started Gen ma=
nually","loic.noumsi@matech-cameroun.com","192","20-05-2025 17:10:12","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005065312","Song-bon=
g","","20-05-2025 16:57:35","20-05-2025 15:37:06","20-05-2025 16:58:43","Ca=
scaded Incident from TTO5201497","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site Went down due to PWC OVERLOAD(=
12K//135A) // reduced load (reduction of 2 racks of battery) ","system","16=
79269","20-05-2025 16:57:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005065013","Emana Ly=
cee","","20-05-2025 16:40:35","20-05-2025 16:38:43","20-05-2025 16:54:24","=
Cascaded Incident from TTO5202136","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down befo=
re Gen started due to poor battery backup // Gen start automatically","syst=
em","1682710","20-05-2025 16:40:35","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005064997","E=
mana lycee 2","IHS_YND_274","20-05-2025 16:39:56","20-05-2025 16:38:43","20=
-05-2025 16:54:24","Grid outage , site went down before Gen started due to =
poor battery backup // Gen start automatically","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age , site went down before Gen started due to poor battery backup // Gen s=
tart automatically","gaelle.njiofack@matech-cameroun.com","74","20-05-2025 =
16:39:56","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005064591","Ebo=
go","","20-05-2025 16:18:01","20-05-2025 16:14:42","20-05-2025 16:50:10","A=
ctive// No Power issue on site Ubaie 53V site on Grid, TX FME Julien /69309=
5849 from Huawei is informed","Siligap Boris","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power=
 issue on site Ubaie 53V site on Grid, TX FME Julien /693095849 from Huawei=
 is informed","loic.noumsi@matech-cameroun.com","200","20-05-2025 16:18:01"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005064529","N=
YOM 2 IHS","","20-05-2025 16:10:18","20-05-2025 16:07:08","20-05-2025 18:09=
:34","Grid outage , site went down before Gen started due to poor battery b=
ackup but Now Gen did not start because Relay 48V is faulty // Gen started =
manually (replacement of Relay on going)","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Relay Faulty","Grid outage , site went dow=
n before Gen started due to poor battery backup but Now Gen did not start b=
ecause Relay 48V is faulty // Gen started manually (replacement of Relay on=
 going)","gaelle.njiofack@matech-cameroun.com","264","20-05-2025 16:10:18",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005064443","Eseka To=
wn","","20-05-2025 15:54:57","20-05-2025 15:37:06","20-05-2025 16:58:43","C=
ascaded Incident from TTO5201497","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site Went down due to PWC OVERLOAD=
(12K//135A) // reduced load (reduction of 2 racks of battery) ","system","1=
679268","20-05-2025 15:54:57","MATECH CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0005064393","Ese=
ka MTN","IHS_YND_453, IHS_YND_378","20-05-2025 15:48:15","20-05-2025 15:37:=
06","20-05-2025 16:58:43","site Went down due to PWC OVERLOAD(12K//135A) //=
 reduced load (reduction of 2 racks of battery) ","Kemeni Franklin","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","site Went =
down due to PWC OVERLOAD(12K//135A) // reduced load (reduction of 2 racks o=
f battery) ","loic.noumsi@matech-cameroun.com","670","20-05-2025 15:48:15",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005064327","N=
koabang2","","20-05-2025 15:37:37","20-05-2025 15:34:19","20-05-2025 17:38:=
17","Site went down due to Grid bad voltage and Gen overload (22KVA, 330A),=
 SS Blaise IHS is informed // He bypassed Grid and started Gen manually aft=
er reducing load","Mba Lazare Herve","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","Site went down due to Grid bad voltage =
and Gen overload (22KVA, 330A), SS Blaise IHS is informed // He bypassed Gr=
id and started Gen manually after reducing load","loic.noumsi@matech-camero=
un.com","200","20-05-2025 15:37:37","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005064272","N=
kolbong","","20-05-2025 15:29:47","20-05-2025 15:25:41","20-05-2025 20:34:5=
1","Grid contactor Burn,Site went down because Gen started and stopped due =
to Gen overload(22kva//350A)//Site stabilized","Delor Telezing","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid contactor Burn,Site we=
nt down because Gen started and stopped due to Gen overload(22kva//350A)// =
He reduiced load and Gen manually started","loic.noumsi@matech-cameroun.com=
","248","20-05-2025 15:29:47","MATECH CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0005064241","Ese=
ka Town","","20-05-2025 15:27:10","20-05-2025 12:47:02","20-05-2025 15:36:2=
7","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Site went down due to PWC OVERLOAD(12K//135A) // Site stabilis=
ed","loic.noumsi@matech-cameroun.com","1674996","20-05-2025 15:27:10","MATE=
CH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005064198","Mim=
boman4","","20-05-2025 15:23:15","20-05-2025 15:17:03","20-05-2025 15:23:22=
","	Grid fluctuations, site went down because Gen failed to start due to gr=
id bad voltage // Grid stabilised","Mba Lazare Herve","Grid Supply","Passiv=
e","Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuations, =
site went down because Gen failed to start due to grid bad voltage // Grid =
stabilised","loic.noumsi@matech-cameroun.com","373","20-05-2025 15:23:15","=
MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005063940","SOA=
 TOWN","","20-05-2025 15:04:04","20-05-2025 14:55:27","20-05-2025 16:40:22"=
,"Grid outage, site went down due to Rectifier issue // Site stabilised","S=
iligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Grid outage, site went down due to Rectifier issue // Site stabilised","loi=
c.noumsi@matech-cameroun.com","518","20-05-2025 15:04:04","MATECH CMR"
"Closed Complete","Warning","T0129","IHS_YND_379","NOCINC0005063873","Eseka=
 MTN","","20-05-2025 15:01:15","","","GRID OUTAGE SITE WENT ALARM BEFORE GE=
N START // GEN START AUTOMATICALLY","Kemeni Franklin","Warning","Warning","=
POWER","Warning - Site on Battery","GRID OUTAGE SITE WENT ALARM BEFORE GEN =
START // GEN START AUTOMATICALLY","loic.noumsi@matech-cameroun.com","10862"=
,"20-05-2025 15:01:15","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005063680","N=
kolbong","","20-05-2025 14:42:19","20-05-2025 14:40:14","20-05-2025 14:47:3=
8","Grid contactor Burn,Site went down because Gen started and stopped due =
to Gen overload(22kva//350A)//Site stabilised","Delor Telezing","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid contactor Burn,Site we=
nt down because Gen started and stopped due to Gen overload(22kva//350A)//S=
ite stabilised","ludivine.ngamaleu@ihstowers.com","126","20-05-2025 14:42:1=
9","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005063650","Mvo=
g-Manga","","20-05-2025 14:37:59","20-05-2025 14:30:05","20-05-2025 22:16:5=
7","Site went down due to MPR DYSFONNCTION on site // Site stabilised","Alb=
ran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","S=
ite went down due to MPR DYSFONNCTION on site // Site stabilised","loic.nou=
msi@matech-cameroun.com","476","20-05-2025 14:37:59","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005063636","M=
endong vallee","","20-05-2025 14:36:20","20-05-2025 14:14:04","20-05-2025 1=
6:32:56","Grid outage site went down due to Grid fluctuations and Gen overl=
oad (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed and confirmed // Grid ret=
urned","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid outage site went down due to Grid fluctuations and=
 Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed and confirmed /=
/ Grid returned","ludivine.ngamaleu@ihstowers.com","1337","20-05-2025 14:36=
:20","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005063347","T=
amtam Weekend","","20-05-2025 14:00:39","20-05-2025 13:06:23","20-05-2025 1=
6:26:14","No power issue site on Grid with U=3D52.7V The TX FME Mbah Hosiah=
 (674007438) FROM Huawei is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue site on Grid with U=3D52.7V The TX FME Mbah Hosiah (674007438) FROM =
Huawei is informed","vanel.mbiada@matech-cameroun.com","3257","20-05-2025 1=
4:00:39","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005063256","Men=
dong3","","20-05-2025 13:47:54","20-05-2025 13:43:45","20-05-2025 14:54:00"=
,"Grid Only site No Space to Deploy a MDG // Grid Restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only site No S=
pace to Deploy a MDG // Grid Restored","cedric.tiani@matech-cameroun.com","=
249","20-05-2025 13:47:54","MATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0005063238","S=
ofavinc","","20-05-2025 13:43:08","20-05-2025 13:42:56","20-05-2025 14:23:4=
7","Site went down because Gen failed to start due to card Ge DYSFUNCTION /=
/ He reseted it and started Gen manually","MINKA NICOLAS","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Site went down because Gen f=
ailed to start due to card Ge DYSFUNCTION // He reseted it and started Gen =
manually","vanel.mbiada@matech-cameroun.com","13","20-05-2025 13:43:08","MA=
TECH CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0005063157","Ese=
ka MTN","IHS_YND_378","20-05-2025 13:28:12","20-05-2025 12:47:02","20-05-20=
25 15:36:27","Site went down due to PWC OVERLOAD(12K//135A) // Site stabili=
sed","Kemeni Franklin","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Site went down due to PWC OVERLOAD(12K//135A) // Si=
te stabilised","cedric.tiani@matech-cameroun.com","2471","20-05-2025 13:28:=
12","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005063147","Nko=
ulou Carriere carrefourt","","20-05-2025 13:26:43","20-05-2025 13:17:29","2=
0-05-2025 18:48:45","Grid outage, Site went down due to insufficiency of re=
ctifiers // Grid stabilised","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Grid outage, Site went down due to insuff=
iciency of rectifiers // Grid stabilised","cedric.tiani@matech-cameroun.com=
","555","20-05-2025 13:26:43","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005063139","Nko=
langaa","","20-05-2025 13:25:39","20-05-2025 13:16:03","20-05-2025 15:16:03=
","	No power issue on site Ubay =3D 53.1V Site on Grid (TX FME Henri (69994=
9693) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","	No power iss=
ue on site Ubay =3D 53.1V Site on Grid (TX FME Henri (699949693) from Huawe=
i is informed","cedric.tiani@matech-cameroun.com","578","20-05-2025 13:25:3=
9","MATECH CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0005063115","N=
R-Omnisport","","20-05-2025 13:23:34","20-05-2025 13:21:24","20-05-2025 16:=
45:31","Site went down due to plan work activity (SWAP of PWC) by Njoya (LO=
UMAD/ 690811271) // End of work","Delor Telezing","Installation Activity","=
Passive","Planned Activity","Installation Activity","Site went down due to =
plan work activity (SWAP of PWC) by Njoya (LOUMAD/ 690811271) // End of wor=
k","vanel.mbiada@matech-cameroun.com","130","20-05-2025 13:23:34","MATECH C=
MR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005062978","N=
koabang2","","20-05-2025 13:02:14","20-05-2025 13:00:04","20-05-2025 14:42:=
01","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid returned","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed // Grid returned","va=
nel.mbiada@matech-cameroun.com","132","20-05-2025 13:02:14","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005062466","M=
vog-Manga","","20-05-2025 12:12:03","20-05-2025 12:10:49","20-05-2025 12:26=
:57","Site went down due to MPR DYSFONNCTION on site // Site stabilised","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site // Site stabilised","vanel.=
mbiada@matech-cameroun.com","76","20-05-2025 12:12:03","MATECH CMR"
"Closed Complete","Site Down","CTR_419","IHS_YND_227","NOCINC0005061955","M=
vog Betsi","","20-05-2025 11:15:13","20-05-2025 11:12:17","20-05-2025 11:23=
:42","Gridfluctuation, site down before Gen started due to poor batteries b=
ackup // Grid satbilized","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Gridfluctuation, site down befo=
re Gen started due to poor batteries backup // Grid satbilized","vanel.mbia=
da@matech-cameroun.com","176","20-05-2025 11:15:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005061850","Song-bon=
g","","20-05-2025 11:02:43","20-05-2025 10:55:19","20-05-2025 11:02:22","Ca=
scaded Incident from TTO5198785","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Ubaie =3D54.8V site on Gen TX Fme Etie=
nne Fopa / 695033981 from huawei is informed.","system","1667270","20-05-20=
25 11:02:43","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005061833","E=
seka OCM","IHS_YND_453","20-05-2025 11:00:01","20-05-2025 10:55:19","20-05-=
2025 11:02:22","Ubaie =3D54.8V site on Gen TX Fme Etienne Fopa / 695033981 =
from huawei is informed.","Kemeni Franklin","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Ubaie =3D54.8V site=
 on Gen TX Fme Etienne Fopa / 695033981 from huawei is informed.","vanel.mb=
iada@matech-cameroun.com","284","20-05-2025 11:00:01","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005061671","Odz=
a II OCM","","20-05-2025 10:31:47","20-05-2025 10:28:35","20-05-2025 10:40:=
38","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction // Grid return","Albran Byorel","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Grid outage, site went down becau=
se gen failed to start due to PWC ZTE malfunction // Grid return","cedric.t=
iani@matech-cameroun.com","194","20-05-2025 10:31:47","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005061587","Nko=
l-Mebanga","","20-05-2025 10:18:47","20-05-2025 04:59:34","20-05-2025 12:02=
:35","BACKTRACKING  Solar only // solar energy returned","Parker Tchoup","E=
quipment Repair","Passive","Solar","Solar Panel Issue","BACKTRACKING  Solar=
 only // solar energy returned","cedric.tiani@matech-cameroun.com","19154",=
"20-05-2025 10:18:47","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005061474","M=
vog-Manga","","20-05-2025 10:02:36","20-05-2025 10:01:27","20-05-2025 10:48=
:23","	Site went down due to MPR DYSFONNCTION on site // Site stabilised","=
Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet"=
,"	Site went down due to MPR DYSFONNCTION on site // Site stabilised","vane=
l.mbiada@matech-cameroun.com","71","20-05-2025 10:02:36","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0005061418","O=
mnisport 3","","20-05-2025 09:53:57","20-05-2025 09:30:49","20-05-2025 17:4=
6:48","Site went down because FME Njoya Mohamed (658849259) from I-ENG was =
on site for planned activitiy( swapp of PWC) // End of work","Delor Telezin=
g","Installation Activity","Passive","Planned Activity","Installation Activ=
ity","Site went down because FME Njoya Mohamed (658849259) from I-ENG was o=
n site for planned activitiy( swapp of PWC) // End of work","vanel.mbiada@m=
atech-cameroun.com","1388","20-05-2025 09:53:57","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005061237","B=
arriere","","20-05-2025 09:31:14","20-05-2025 09:30:04","20-05-2025 09:31:3=
8","Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS F=
elix ZAMBE confirmed// Site stabilized","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (20kva, 400A) SS IHS Felix ZAMBE confirmed// Site stabilized=
","vanel.mbiada@matech-cameroun.com","71","20-05-2025 09:31:14","MATECH CMR=
"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0005061232","TON=
GOLO SNEC","","20-05-2025 09:30:44","20-05-2025 09:25:36","20-05-2025 09:31=
:44","No power Issue Site on Grid Ubai =3D55.3 V. The TX FME Armand Nguetsa=
  (699949553) is informed","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power Issue Sit=
e on Grid Ubai =3D55.3 V. The TX FME Armand Nguetsa  (699949553) is informe=
d","cedric.tiani@matech-cameroun.com","309","20-05-2025 09:30:44","MATECH C=
MR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0005061193","SOA=
 TOWN","IHS_YND_323","20-05-2025 09:25:23","20-05-2025 09:23:13","20-05-202=
5 09:30:16","Grid outage, site went down because gen start and stopped with=
 high temp alarm // He added water and manually start the gen","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid outage, site went down because gen start and stopped=
 with high temp alarm // He added water and manually start the gen","cedric=
.tiani@matech-cameroun.com","132","20-05-2025 09:25:23","MATECH CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0005061037","SOA=
 VILLAGE","","20-05-2025 09:08:16","20-05-2025 09:23:13","20-05-2025 09:24:=
16","TX","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, site went down because gen start and stopped wit=
h high temp alarm // He added water and manually start the gen","cedric.tia=
ni@matech-cameroun.com","1665953","20-05-2025 09:08:16","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0005060982","NTU=
I TOWN","","20-05-2025 08:59:37","20-05-2025 08:57:15","20-05-2025 09:00:49=
","No power issue on site ,site on GRID with Ubaie=3D54.3V, Tx Fme Gregoire=
( 652070658)From Huawei is informed","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site ,site on GRID with Ubaie=3D54.3V, Tx Fme Gregoire( 652070658)F=
rom Huawei is informed","cedric.tiani@matech-cameroun.com","143","20-05-202=
5 08:59:37","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005060675","Mvo=
g-Manga","","20-05-2025 08:17:17","20-05-2025 08:16:07","20-05-2025 08:18:4=
7","Site went down due to MPR DYSFONNCTION on site   // Site stabilised","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR DYSFONNCTION on site   // Site stabilised","cedr=
ic.tiani@matech-cameroun.com","72","20-05-2025 08:17:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005060582","MEHANDAN=
","","20-05-2025 08:01:42","20-05-2025 07:42:40","20-05-2025 07:55:39","Cas=
caded Incident from TTO5197296","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
1657384","20-05-2025 08:01:42","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005060472","O=
dza II OCM","IHS_YND_528","20-05-2025 07:48:53","20-05-2025 07:42:40","20-0=
5-2025 07:55:39","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","vanel.mbiada@matech-cameroun.com","375","20-05-2025 07:48:53",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005060319","T=
alla Monatele","","20-05-2025 07:18:59","20-05-2025 04:32:27","20-05-2025 0=
8:10:33","No power issue, site is on grid with Ubaie=3D54.9V, Gregoir (6545=
47479) from Huawei is informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue,=
 site is on grid with Ubaie=3D54.9V, Gregoir (654547479) from Huawei is inf=
ormed","vanel.mbiada@matech-cameroun.com","9993","20-05-2025 07:18:59","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005060290","O=
LAMA","","20-05-2025 07:14:31","20-05-2025 07:09:11","20-05-2025 07:16:22",=
"No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (6999=
49693) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubaie =3D54.9V site on Grid. The TX FME Henri (699949693) from Huawei=
 is informed","vanel.mbiada@matech-cameroun.com","321","20-05-2025 07:14:31=
","MATECH CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0005060212","Mim=
boman3","","20-05-2025 07:03:12","20-05-2025 06:58:50","20-05-2025 07:50:35=
","Grid outage site went down because PWC of ZTE DYSFONCTION // He reset an=
d Gen manually started","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Grid outage site went down because =
PWC of ZTE DYSFONCTION // He reset and Gen manually started","cedric.tiani@=
matech-cameroun.com","263","20-05-2025 07:03:12","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005059801","O=
dza","IHS_YND_254, IHS_YND_580","20-05-2025 05:32:00","20-05-2025 05:10:51"=
,"20-05-2025 07:44:03","Active//No power issue on site Ubaie: 52.97 V site =
on Grid The TX Lionel steve (655184876 /Huawei)) is informed.Noticed cable =
burnt at the BTS OCM","Albran Byorel","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on=
 site Ubaie: 52.97 V site on Grid The TX Lionel steve (655184876 /Huawei)) =
is informed.Noticed cable burnt at the BTS OCM","christelle.ngonga@matech-c=
ameroun.com","1270","20-05-2025 05:32:00","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005059800","Ebo=
go","","20-05-2025 05:31:52","20-05-2025 05:25:35","20-05-2025 05:32:35","A=
ctive// No Power issue on site Ubaie 56V site on Grid, Julien /693095849 fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issue =
on site Ubaie 56V site on Grid, Julien /693095849 from Huawei is informed",=
"franck.nkomot@matech-cameroun.com","379","20-05-2025 05:31:52","MATECH CMR=
"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005059768","M=
vog-Manga","","20-05-2025 05:20:02","20-05-2025 05:10:51","20-05-2025 07:44=
:03","","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascade=
 Active","Active//No power issue on site Ubaie: 52.97 V site on Grid The TX=
 Lionel steve (655184876 /Huawei)) is informed.Noticed cable burnt at the B=
TS OCM","christelle.ngonga@matech-cameroun.com","1659232","20-05-2025 05:20=
:02","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0005059766","M=
arche Odza","","20-05-2025 05:19:19","20-05-2025 05:10:51","20-05-2025 07:4=
4:03","","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Active//No power issue on site Ubaie: 52.97 V site on Grid The T=
X Lionel steve (655184876 /Huawei)) is informed.Noticed cable burnt at the =
BTS OCM","christelle.ngonga@matech-cameroun.com","1659233","20-05-2025 05:1=
9:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005059759","Song-bon=
g","","20-05-2025 05:17:22","20-05-2025 05:14:18","20-05-2025 07:03:20","Ca=
scaded Incident from TTO5196533","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,site went down because =
Gen started and stopped with Alarm *low oil pressure* (Unproven alarm)//He =
reset the Gen card and manually started the GEN","system","1659016","20-05-=
2025 05:17:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005059758","Eseka To=
wn","","20-05-2025 05:17:22","20-05-2025 05:14:18","20-05-2025 07:03:20","C=
ascaded Incident from TTO5196533","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,site went down because=
 Gen started and stopped with Alarm *low oil pressure* (Unproven alarm)//He=
 reset the Gen card and manually started the GEN","system","1659016","20-05=
-2025 05:17:22","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0005059756","E=
seka OCM","IHS_YND_378, IHS_YND_453","20-05-2025 05:16:24","20-05-2025 05:1=
4:18","20-05-2025 07:03:20","Grid outage,site went down because Gen started=
 and stopped with Alarm *low oil pressure* (Unproven alarm)//He reset the G=
en card and manually started the GEN","Kemeni Franklin","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down bec=
ause Gen started and stopped with Alarm *low oil pressure* (Unproven alarm)=
//He reset the Gen card and manually started the GEN","christelle.ngonga@ma=
tech-cameroun.com","127","20-05-2025 05:16:24","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005059272","Mim=
boman","","20-05-2025 02:40:57","20-05-2025 02:32:39","20-05-2025 06:06:39"=
,"Site went down because gen start and stopped due to alarm*High temp*//he =
added water  and started the gen","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Site wen=
t down because gen start and stopped due to alarm*High temp*//he added wate=
r  and started the gen","franck.nkomot@matech-cameroun.com","499","20-05-20=
25 02:40:57","MATECH CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0005059157","O=
lezoa OCM","","20-05-2025 01:50:26","20-05-2025 01:41:18","21-05-2025 09:08=
:24","Grid outage.no space to deploy mobile gen//grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no sp=
ace to deploy mobile gen//grid return","christelle.ngonga@matech-cameroun.c=
om","549","20-05-2025 01:50:26","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005059120","E=
ssomba","","20-05-2025 01:39:47","20-05-2025 01:20:35","20-05-2025 05:23:35=
","Site went down because PWC overload // Site stabilised	","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Site went down because PWC overload // Site stabilised	","christelle.ngong=
a@matech-cameroun.com","1153","20-05-2025 01:39:47","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005059117","E=
mana lycee 2","","20-05-2025 01:38:16","20-05-2025 01:28:05","20-05-2025 01=
:46:07","Grid outage , site went down before Gen started due to poor batter=
y backup //Grid returned","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","DG Low Battery","Grid outage , site went down before Gen started =
due to poor battery backup //Grid returned","christelle.ngonga@matech-camer=
oun.com","612","20-05-2025 01:38:16","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005058946","EMA=
NA BILICK CITY","IHS_YND_279","20-05-2025 00:40:20","20-05-2025 00:29:10","=
20-05-2025 01:35:43","Grid outage, site down because site behaves as Grid o=
nly site (no Gen) // Grid restoration","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, site down be=
cause site behaves as Grid only site (no Gen) // Grid restoration","franck.=
nkomot@matech-cameroun.com","770","20-05-2025 00:40:20","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005058930","M=
essassi okolo","","20-05-2025 00:35:13","20-05-2025 00:29:10","20-05-2025 0=
1:31:23","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site down because site behaves as Grid only=
 site (no Gen) // Grid restoration","franck.nkomot@matech-cameroun.com","16=
68915","20-05-2025 00:35:13","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005058882","M=
essassi 2","","20-05-2025 00:24:24","20-05-2025 00:22:18","20-05-2025 01:38=
:57","Grid outage, Site went down due to rectifiers issue // Grid returned"=
,"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Grid outage, Site went down due to rectifiers issue // Grid returned",=
"christelle.ngonga@matech-cameroun.com","128","20-05-2025 00:24:24","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005058832","E=
mana Lycee","","20-05-2025 00:15:24","20-05-2025 00:09:59","20-05-2025 03:5=
5:59","Grid fluctuation,Site went down because Gen failed to start due to g=
rid bad voltage // He bypassed the Grid and started the Gen manually","Fabr=
ice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation,Site went down because Gen failed to start due=
 to grid bad voltage // He bypassed the Grid and started the Gen manually",=
"christelle.ngonga@matech-cameroun.com","327","20-05-2025 00:15:24","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0005058817","Eseka To=
wn","","20-05-2025 00:10:27","19-05-2025 22:04:41","19-05-2025 23:50:27","C=
ascaded Incident from TTO5195392","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue U=3D57.2V site on Gen =
The Tx FME Etienne FOPA /695033981/ From HUAWEI is informed","system","1670=
437","20-05-2025 00:10:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0005058818","Song-bon=
g","","20-05-2025 00:10:27","19-05-2025 22:04:41","19-05-2025 23:50:27","Ca=
scaded Incident from TTO5195392","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue U=3D57.2V site on Gen T=
he Tx FME Etienne FOPA /695033981/ From HUAWEI is informed","system","16704=
37","20-05-2025 00:10:27","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005058808","NYO=
M 2 IHS","","20-05-2025 00:07:55","19-05-2025 23:59:41","20-05-2025 02:47:3=
2","Grid outage, Site went down before Gen start due to poor backup // Gen =
started automaticaly","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","DG Low Battery","Grid outage, Site went down before Gen start due to =
poor backup // Gen started automaticaly","christelle.ngonga@matech-cameroun=
.com","495","20-05-2025 00:07:55","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005058792","Ebo=
go","","20-05-2025 00:03:24","19-05-2025 23:56:07","20-05-2025 01:24:58","A=
ctive// No Power issue on site Ubaie 56V site on Grid, Julien /693095849 fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Grid outage, site went d=
own before Gen start due to poor backup battery // Gen automaticaly started=
","christelle.ngonga@matech-cameroun.com","439","20-05-2025 00:03:24","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0005058735","Eseka OC=
M","IHS_YND_378, IHS_YND_453","19-05-2025 23:48:20","19-05-2025 22:04:41","=
19-05-2025 23:50:27","No power issue U=3D57.2V site on Gen The Tx FME Etien=
ne FOPA /695033981/ From HUAWEI is informed","Kemeni Franklin","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue U=3D57.2V site on Gen The Tx FME Etienne FOPA /695033981/ Fr=
om HUAWEI is informed","christelle.ngonga@matech-cameroun.com","6220","19-0=
5-2025 23:48:20","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0005058656","E=
koumdoum","","19-05-2025 23:34:01","19-05-2025 23:30:55","20-05-2025 01:32:=
55","Grid bad voltage, site went down because Gen failed to start due to la=
ck of 01 phase // He did a bridge on the good phase","Albran Byorel","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid ba=
d voltage, site went down because Gen failed to start due to lack of 01 pha=
se // He did a bridge on the good phase","christelle.ngonga@matech-cameroun=
.com","187","19-05-2025 23:34:01","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0005058595","NTE=
MASSI","","19-05-2025 23:18:06","19-05-2025 22:22:51","20-05-2025 07:42:10"=
,"Access issue  Grid outage, site went down because Gen failed to start due=
 to Gen contacteur faulty // He started the Gen manually","Delor Telezing",=
"Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue - =
Land Lord"," Grid outage, site went down because Gen failed to start due to=
 Gen contacteur faulty // He started the Gen manually","franck.nkomot@matec=
h-cameroun.com","3316","19-05-2025 23:18:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0005058466","Dong",""=
,"19-05-2025 22:52:00","19-05-2025 22:41:34","19-05-2025 23:19:03","Cascade=
d Incident from TTO5195087","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No Power issue on site Ubay =3D 50.5V, Tx Fme=
 Gregoire (654547479) from Huawei is informed and confirmed","system","1668=
157","19-05-2025 22:52:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0005058465","Donga","=
","19-05-2025 22:52:00","19-05-2025 22:41:34","19-05-2025 23:19:03","Cascad=
ed Incident from TTO5195087","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site Ubay =3D 50.5V, Tx Fm=
e Gregoire (654547479) from Huawei is informed and confirmed","system","166=
8157","19-05-2025 22:52:00","MATECH CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0005058463","N=
guila","IHS_YND_434, IHS_YND_444","19-05-2025 22:50:39","19-05-2025 22:41:3=
4","19-05-2025 23:19:03","No Power issue on site Ubay =3D 50.5V, Tx Fme Gre=
goire (654547479) from Huawei is informed and confirmed","Parker Tchoup","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No Power issue on site Ubay =3D 50.5V, Tx Fme Gregoire (654547479=
) from Huawei is informed and confirmed","landry.etame@ihstowers.com","546"=
,"19-05-2025 22:50:39","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005058460","N=
koabang2","","19-05-2025 22:49:32","19-05-2025 22:47:49","20-05-2025 01:30:=
49","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","landry=
.etame@ihstowers.com","105","19-05-2025 22:49:32","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005058404","O=
LAMA","","19-05-2025 22:37:21","19-05-2025 22:18:16","19-05-2025 23:20:38",=
"No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (6999=
49693) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubaie =3D54.9V site on Grid. The TX FME Henri (699949693) from Huawei=
 is informed","landry.etame@ihstowers.com","1146","19-05-2025 22:37:21","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0005058319","M=
obil-Kondengui","","19-05-2025 22:19:55","19-05-2025 22:12:37","19-05-2025 =
22:25:37","site went down due to plan work on site (SWAP of Energie Ubaie b=
y bigans / 650631358 )","","Installation Activity","Passive","Planned Activ=
ity","Installation Activity","site went down due to plan work on site (SWAP=
 of Energie Ubaie by bigans / 650631358 )","loic.noumsi@matech-cameroun.com=
","439","19-05-2025 22:19:55","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0005058087","Tsi=
nga village","","19-05-2025 21:36:31","19-05-2025 21:30:20","19-05-2025 23:=
28:20","Site went down due to insufficiency of rectifier caused by increase=
 in load // He reduced the load, site on grid","Delor Telezing","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down due to ins=
ufficiency of rectifier caused by increase in load // He reduced the load, =
site on grid","loic.noumsi@matech-cameroun.com","371","19-05-2025 21:36:31"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005057998","M=
endong vallee","","19-05-2025 21:21:00","19-05-2025 21:11:51","19-05-2025 2=
2:46:51","Grid outage site went down because Gen overload (20KVA; 300A) IHS=
 F=E9lix Zamb=E9 is informed and confirmed // Grid returned","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site=
 went down because Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is inform=
ed and confirmed // Grid returned","gaelle.njiofack@matech-cameroun.com","5=
51","19-05-2025 21:21:00","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0005057992","M=
bankomo IHS","","19-05-2025 21:19:14","19-05-2025 21:17:54","19-05-2025 22:=
00:54","Grid outage, Site went down before Gen start due to poor backup // =
Gen started Manually","Fanda Brice","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen started Manually","gaelle.njiofack@matech-=
cameroun.com","80","19-05-2025 21:19:14","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005057854","N=
kolbong","","19-05-2025 20:53:50","19-05-2025 20:50:27","19-05-2025 22:42:2=
7","Grid contactor Burn,Site went down because Gen started and stopped due =
to Gen overload(22kva//350A)//He reduiced the load and maually started the =
Gen","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Grid contactor Burn,Site went down because Gen started and stopped du=
e to Gen overload(22kva//350A)//He reduiced the load and maually started th=
e Gen","loic.noumsi@matech-cameroun.com","204","19-05-2025 20:53:50","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005057815","N=
YOM 2 IHS","","19-05-2025 20:45:02","19-05-2025 20:36:55","19-05-2025 21:16=
:17","Grid fluctuation,site went down because Gen failed to start due to Gr=
id bad voltage// Grid stabilisation","Fabrice Pouakam","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,site=
 went down because Gen failed to start due to Grid bad voltage// Grid stabi=
lisation","gaelle.njiofack@matech-cameroun.com","488","19-05-2025 20:45:02"=
,"MATECH CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0005057712","San=
ta Barbara Gottam","","19-05-2025 20:23:16","19-05-2025 20:13:07","19-05-20=
25 21:55:07","Grid outage, Gen failed to start due to Batterry Gen Faulty /=
/ Gen started with Battery backup.","Delor Telezing","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Generator Battery","Grid outage, Gen failed to st=
art due to Batterry Gen Faulty // Gen started with Battery backup.","loic.n=
oumsi@matech-cameroun.com","610","19-05-2025 20:23:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0005057701","Eseka OC=
M","IHS_YND_378, IHS_YND_453","19-05-2025 20:22:30","19-05-2025 20:12:26","=
19-05-2025 22:02:44","Grid outage Gen failed to start due gen card alarm //=
 Gen card reset and Gen start manually","Kemeni Franklin","Equipment Repair=
","Passive","Control Panel","DG Distribution Board","Grid outage Gen failed=
 to start due gen card alarm // Gen card reset and Gen start manually","sys=
tem","604","19-05-2025 20:22:30","MATECH CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0005057695","E=
seka Town","","19-05-2025 20:21:36","19-05-2025 20:12:26","19-05-2025 22:02=
:44","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage Gen failed to start due gen card alarm // Gen ca=
rd reset and Gen start manually","loic.noumsi@matech-cameroun.com","1669889=
","19-05-2025 20:21:36","MATECH CMR"
"Closed Complete","Site Down","CTR_311","IHS_YND_453","NOCINC0005057676","S=
ong-bong","","19-05-2025 20:19:34","19-05-2025 20:12:26","19-05-2025 22:02:=
44","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage Gen failed to start due gen card alarm // Gen car=
d reset and Gen start manually","loic.noumsi@matech-cameroun.com","1669889"=
,"19-05-2025 20:19:34","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005057652","N=
gouetou","","19-05-2025 20:13:39","19-05-2025 20:08:33","19-05-2025 21:10:0=
5","Active // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gre=
goire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gregoire (6=
54547479) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","3=
07","19-05-2025 20:13:39","MATECH CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0005057644","MES=
SAME NDONGO 1162","","19-05-2025 20:11:14","19-05-2025 20:02:09","19-05-202=
5 20:36:21","Grid outage,gen failed to start due to Gen card malfunctioning=
//he reseted the card and he started Gen manually","MINKA NICOLAS","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,gen fai=
led to start due to Gen card malfunctioning//he reseted the card and he sta=
rted Gen manually","loic.noumsi@matech-cameroun.com","545","19-05-2025 20:1=
1:14","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0005057628","K=
oweit City","","19-05-2025 20:07:23","19-05-2025 19:55:11","19-05-2025 20:0=
6:27","Grid outage, site went down because gen failed to start with alarm u=
ndervoltage // He reseted gen card and gen manually started","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, sit=
e went down because gen failed to start with alarm undervoltage // He reset=
ed gen card and gen manually started","loic.noumsi@matech-cameroun.com","73=
3","19-05-2025 20:07:23","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0005057549","M=
imboman-Ecole","","19-05-2025 19:54:38","19-05-2025 19:39:22","19-05-2025 1=
9:50:22","Active//No power issue on site U:54.2 V,site on grid The FME TX E=
loundou Bertrant (693212405) From Huawei is Informed.","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site U:54.2 V,site on grid The FME TX =
Eloundou Bertrant (693212405) From Huawei is Informed.","gaelle.njiofack@ma=
tech-cameroun.com","917","19-05-2025 19:54:38","MATECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0005057466","ODZ=
A CITE MBIA","","19-05-2025 19:38:47","19-05-2025 19:28:38","19-05-2025 19:=
30:38","Active//No power issue U=3D53,3V site on Grid.TX FME Leonel Steve (=
655184876) from Huawei is informed","Albran Byorel","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue U=3D53,3V site on Grid.TX FME Leonel Steve (655184876) from Hua=
wei is informed","loic.noumsi@matech-cameroun.com","610","19-05-2025 19:38:=
47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0005057406","Awae Esc=
alier","","19-05-2025 19:29:13","19-05-2025 19:22:16","19-05-2025 19:28:26"=
,"Cascaded Incident from TTO5193907","Albran Byorel","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","	No power issue on site ,site on Gri=
d with Ubaie=3D54.9 V The TX Henry/699949693// From Huawei is Informed","sy=
stem","1665706","19-05-2025 19:29:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_042","NOCINC0005057405","Mvog-Ada=
_OCM","","19-05-2025 19:29:12","19-05-2025 19:22:16","19-05-2025 19:28:26",=
"Cascaded Incident from TTO5193907","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","	No power issue on site ,site on Grid with Ubaie=
=3D54.9 V The TX Henry/699949693// From Huawei is Informed","system","16657=
06","19-05-2025 19:29:13","MATECH CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0005057393","A=
wae-Yde","IHS_YND_042, IHS_YND_171","19-05-2025 19:27:25","19-05-2025 19:22=
:16","19-05-2025 20:58:26","No power issue on site ,site on Grid with Ubaie=
=3D54.9 V The TX Henry/699949693// From Huawei is Informed","Albran Byorel"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","	No power issue on site ,site on Grid with Ubaie=3D54.9 V The =
TX Henry/699949693// From Huawei is Informed","gaelle.njiofack@matech-camer=
oun.com","310","19-05-2025 19:27:25","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0005057371","C=
omplexe-BEAC","","19-05-2025 19:21:23","19-05-2025 19:19:16","19-05-2025 19=
:23:51","Grid outage, Site went down before Gen start due to Poor battery b=
ackup // Gen start automatically","Albran Byorel","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to Poor battery backup // Gen start automatically"=
,"gaelle.njiofack@matech-cameroun.com","128","19-05-2025 19:21:23","MATECH =
CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005057369","T=
amtam Weekend","","19-05-2025 19:20:28","19-05-2025 19:19:19","19-05-2025 1=
9:20:47","Site went down due to Grid fluctuation and Gen overload // Grid s=
tabilized","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Site went down due to Grid fluctuation and Gen overload // Grid=
 stabilized","gaelle.njiofack@matech-cameroun.com","70","19-05-2025 19:20:2=
8","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005057367","E=
ssomba","","19-05-2025 19:19:55","19-05-2025 19:16:46","20-05-2025 00:37:46=
","Site went down because PWC overload // Site stabilised","Mba Lazare Herv=
e","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Site went down because PWC overload // Site stabilised","gaelle.njiofack@ma=
tech-cameroun.com","191","19-05-2025 19:19:55","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0005057363","B=
iteng-Maetur","","19-05-2025 19:19:10","19-05-2025 19:14:04","20-05-2025 02=
:20:59","Active//No power issue on site Ubaie =3D50.3V site on Grid The TX =
FME Henri (699949693) from Huawei is informed","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site Ubaie =3D50.3V site on Grid The TX FME He=
nri (699949693) from Huawei is informed","gaelle.njiofack@matech-cameroun.c=
om","307","19-05-2025 19:19:10","MATECH CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0005057362","Av-=
Germaine","","19-05-2025 19:19:09","19-05-2025 19:11:16","19-05-2025 19:13:=
52","Grid only site, no space on site to deploy MGE // Grid returned","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only=
 site, no space on site to deploy MGE // Grid returned","loic.noumsi@matech=
-cameroun.com","473","19-05-2025 19:19:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0005057321","Nkolo II=
 New","","19-05-2025 19:09:14","19-05-2025 19:02:24","19-05-2025 19:28:03",=
"Cascaded Incident from TTO5193822","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuations, site went do=
wn because Gen failed to start due to grid bad voltage // Grid stabilised",=
"system","1666881","19-05-2025 19:09:14","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005057316","Mim=
boman4","IHS_YND_709","19-05-2025 19:08:29","19-05-2025 19:02:24","19-05-20=
25 19:28:03","Grid fluctuations, site went down because Gen failed to start=
 due to grid bad voltage // Grid stabilised","Mba Lazare Herve","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tions, site went down because Gen failed to start due to grid bad voltage /=
/ Grid stabilised","loic.noumsi@matech-cameroun.com","367","19-05-2025 19:0=
8:29","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005057266","E=
MANA BILICK CITY","IHS_YND_279","19-05-2025 18:58:43","19-05-2025 18:52:35"=
,"19-05-2025 20:54:38","Grid outage, site down because site behaves as Grid=
 only site (no Gen)//Grid return","Fabrice Pouakam","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage, site down because=
 site behaves as Grid only site (no Gen)//Grid return","gaelle.njiofack@mat=
ech-cameroun.com","370","19-05-2025 18:58:43","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0005057261","D=
ragage","","19-05-2025 18:57:56","19-05-2025 18:50:49","19-05-2025 21:21:33=
","	Active//No power issue, site is on Gen with Ubaie=3D53.2V, Eloundou ber=
trant(652586578) from Huawei is informed","Mboua Thierry","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Acti=
ve//No power issue, site is on Gen with Ubaie=3D53.2V, Eloundou bertrant(65=
2586578) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","42=
8","19-05-2025 18:57:56","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005057235","E=
mana lycee 2","","19-05-2025 18:53:34","19-05-2025 18:49:19","19-05-2025 19=
:07:48","Grid outage , site went down before Gen started due to poor batter=
y backup //Grid returned","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","DG Low Battery","Grid outage , site went down before Gen started =
due to poor battery backup //Grid returned","gaelle.njiofack@matech-camerou=
n.com","257","19-05-2025 18:53:34","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0005057231","O=
mnisport 3","","19-05-2025 18:52:03","19-05-2025 18:46:55","19-05-2025 21:3=
0:56","Grid outage,site went down due to ATS RELAY faulty//He bypassed it a=
nd site on Grid","Delor Telezing","Equipment Repair","Passive","Control Pan=
el","ATS Relay Faulty","Grid outage,site went down due to ATS RELAY faulty/=
/He bypassed it and site on Grid","gaelle.njiofack@matech-cameroun.com","30=
9","19-05-2025 18:52:03","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005057219","S=
atcom","","19-05-2025 18:50:13","19-05-2025 18:46:01","20-05-2025 02:40:37"=
,"Active//No power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa=
 (691144412) of huawei is informed","Delor Telezing","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144412)=
 of huawei is informed","gaelle.njiofack@matech-cameroun.com","253","19-05-=
2025 18:50:13","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0005057215","Mvo=
g-Manga","","19-05-2025 18:48:54","19-05-2025 18:41:47","19-05-2025 22:26:4=
7","Site went down due to absence of one phase // bridge made between the o=
ther two	","Albran Byorel","Grid Supply","Passive","Grid","National Grid - =
Grid Incomplete Phase","Site went down due to absence of one phase // bridg=
e made between the other two	","gaelle.njiofack@matech-cameroun.com","462",=
"19-05-2025 18:48:54","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005057160","Ebo=
go","","19-05-2025 18:36:03","19-05-2025 18:31:05","19-05-2025 20:18:03","G=
rid outage, site went down before Gen start due poor backup battery // Gen =
automaticaly started","Siligap Boris","Equipment Repair","Passive","ACDG Ge=
n","DG Low Battery","Grid outage, site went down before Gen start due poor =
backup battery // Gen automaticaly started","loic.noumsi@matech-cameroun.co=
m","299","19-05-2025 18:36:03","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005057145","OBA=
M NGOLA OCM","","19-05-2025 18:33:39","19-05-2025 18:28:32","19-05-2025 20:=
52:32","Site went down due to insufficient rectifier on site//site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifier on site//site stabilised=
","loic.noumsi@matech-cameroun.com","308","19-05-2025 18:33:39","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0005057096","MONTEE N=
KONDENGUI","","19-05-2025 18:19:39","19-05-2025 15:59:27","19-05-2025 17:36=
:44","Cascaded Incident from TTO5192671","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down due to plan wo=
rk on site (SWAP of Energie Ubaie by bigans / 650631358 ) // End of work","=
system","1663493","19-05-2025 18:19:39","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005057020","E=
koumdoum OCM","","19-05-2025 18:10:42","19-05-2025 18:01:16","19-05-2025 20=
:09:02","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, Gen turn until fuel shortage // Refueling done=
","gaelle.njiofack@matech-cameroun.com","1663425","19-05-2025 18:10:42","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0005057011","Nsimalen=
 OCM","","19-05-2025 18:07:52","19-05-2025 18:00:03","19-05-2025 19:28:34",=
"Cascaded Incident from TTO5193452","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen start and stopped with high temp alarm // He added water and manually=
 start the gen","system","1663491","19-05-2025 18:07:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0005057010","Odza II =
OCM","","19-05-2025 18:07:21","19-05-2025 18:01:16","19-05-2025 20:09:02","=
Cascaded Incident from TTO5193469","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Gen turn until fuel sh=
ortage // Refueling done","system","1663425","19-05-2025 18:07:21","MATECH =
CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005057005","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","19-05-2025 18:05:23","19=
-05-2025 18:01:16","19-05-2025 20:09:02","Grid outage, Gen turn until fuel =
shortage // Refueling done","Albran Byorel","Fuel Outage","Passive","Diesel=
","Diesel Outage","Grid outage, Gen turn until fuel shortage // Refueling d=
one","gaelle.njiofack@matech-cameroun.com","248","19-05-2025 18:05:23","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0005056994","N=
kolda","IHS_YND_327","19-05-2025 18:03:07","19-05-2025 18:00:03","19-05-202=
5 19:28:34","Grid outage, site went down because gen start and stopped with=
 high temp alarm // He added water and manually start the gen","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid outage, site went down because gen start and stopped=
 with high temp alarm // He added water and manually start the gen","loic.n=
oumsi@matech-cameroun.com","185","19-05-2025 18:03:07","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005056977","N=
kolbong","","19-05-2025 17:59:16","19-05-2025 17:54:06","19-05-2025 18:04:4=
4","Grid contactor Burn,Site went down because Gen started and stopped due =
to Gen overload(22kva//350A)//He reduiced the load and maually started the =
Gen","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Grid contactor Burn,Site went down because Gen started and stopped du=
e to Gen overload(22kva//350A)//He reduiced the load and maually started th=
e Gen","gaelle.njiofack@matech-cameroun.com","311","19-05-2025 17:59:16","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005056921","O=
LAMA","","19-05-2025 17:47:00","19-05-2025 17:38:53","19-05-2025 18:23:37",=
"No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (6999=
49693) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubaie =3D54.9V site on Grid. The TX FME Henri (699949693) from Huawei=
 is informed","gaelle.njiofack@matech-cameroun.com","488","19-05-2025 17:47=
:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0005056891","ODZA MIN=
KAN EDIBI ASSI","","19-05-2025 17:44:26","19-05-2025 17:36:40","19-05-2025 =
17:42:52","Cascaded Incident from TTO5193291","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down due to pl=
an work activitiy on site (SS IHS Felix & Blaise were on site for a SWAP of=
 Ubaie) // End of work","system","1664866","19-05-2025 17:44:26","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0005056890","Mehanda =
1","","19-05-2025 17:44:26","19-05-2025 17:36:40","19-05-2025 17:42:52","Ca=
scaded Incident from TTO5193291","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to plan work activ=
itiy on site (SS IHS Felix & Blaise were on site for a SWAP of Ubaie) // En=
d of work","system","1664867","19-05-2025 17:44:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005056889","MEHANDAN=
","","19-05-2025 17:44:25","19-05-2025 17:36:40","19-05-2025 20:09:02","Cas=
caded Incident from TTO5193291","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to plan work activi=
tiy on site (SS IHS Felix & Blaise were on site for a SWAP of Ubaie) // End=
 of work","system","1664900","19-05-2025 17:44:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0005056888","H-Franco=
 New","","19-05-2025 17:44:25","19-05-2025 17:36:40","19-05-2025 17:42:52",=
"Cascaded Incident from TTO5193291","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to plan work a=
ctivitiy on site (SS IHS Felix & Blaise were on site for a SWAP of Ubaie) /=
/ End of work","system","1664864","19-05-2025 17:44:25","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005056866","Nko=
lnda","IHS_YND_711, IHS_YND_385, IHS_YND_528, IHS_YND_746, IHS_YND_749","19=
-05-2025 17:39:24","19-05-2025 17:36:40","19-05-2025 17:42:52","Site went d=
own due to plan work activitiy on site (SS IHS Felix & Blaise were on site =
for a SWAP of Ubaie) // End of work","Albran Byorel","Installation Activity=
","Passive","Planned Activity","Installation Activity","Site went down due =
to plan work activitiy on site (SS IHS Felix & Blaise were on site for a SW=
AP of Ubaie) // End of work","loic.noumsi@matech-cameroun.com","164","19-05=
-2025 17:39:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005056853","MEHANDAN=
","","19-05-2025 17:36:49","19-05-2025 17:32:29","19-05-2025 17:36:06","Cas=
caded Incident from TTO5193267","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Site stabilised","system","=
1665111","19-05-2025 17:36:49","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005056847","O=
dza II OCM","IHS_YND_528","19-05-2025 17:35:49","19-05-2025 17:32:29","19-0=
5-2025 17:36:06","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Site stabilised","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // Site =
stabilised","gaelle.njiofack@matech-cameroun.com","202","19-05-2025 17:35:4=
9","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005056840","Mes=
sassi 2","","19-05-2025 17:34:12","19-05-2025 17:28:48","19-05-2025 21:02:5=
5","Grid outage, site went down because Gen failed to start due to Gen over=
load (15 Kva, 290A) // Grid returned","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down because=
 Gen failed to start due to Gen overload (15 Kva, 290A) // Grid returned","=
gaelle.njiofack@matech-cameroun.com","326","19-05-2025 17:34:12","MATECH CM=
R"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0005056615","T=
radex-Nkomo","","19-05-2025 16:48:16","19-05-2025 16:44:58","19-05-2025 17:=
04:53","Grid outage, site went down due to Grid fluctuations // Grid stabil=
ised","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid outage, site went down due to Grid fluctuations /=
/ Grid stabilised","gaelle.njiofack@matech-cameroun.com","199","19-05-2025 =
16:48:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005056539","Ngouetou=
","","19-05-2025 16:34:41","19-05-2025 15:44:35","19-05-2025 17:48:57","Cas=
caded Incident from TTO5192903","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen site, site went down becaus=
e Gen started and stopped due to iBattery coast not well fixed// He fixed i=
t well","system","1664375","19-05-2025 16:34:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005056457","Emana Ly=
cee","","19-05-2025 16:21:39","19-05-2025 16:15:21","19-05-2025 16:32:28","=
Cascaded Incident from TTO5192799","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down befo=
re Gen started due to poor battery backup //Grid returned","system","166256=
6","19-05-2025 16:21:39","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005056450","E=
mana lycee 2","IHS_YND_274","19-05-2025 16:20:29","19-05-2025 16:15:21","19=
-05-2025 16:32:28","Grid outage , site went down before Gen started due to =
poor battery backup //Grid returned","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage , site =
went down before Gen started due to poor battery backup //Grid returned","g=
aelle.njiofack@matech-cameroun.com","309","19-05-2025 16:20:29","MATECH CMR=
"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0005056339","M=
obil-Kondengui","","19-05-2025 16:02:01","19-05-2025 15:59:13","19-05-2025 =
15:59:20","Ticket error","","Incorrectly Logged Tickets","Error","Error","E=
rror","Fme Justin is informed and reported plan work on site (SWAP of Ubaie=
)","loic.noumsi@matech-cameroun.com","703","19-05-2025 16:02:01","MATECH CM=
R"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0005056336","M=
obil-Kondengui","IHS_YND_682","19-05-2025 16:01:44","19-05-2025 15:59:27","=
19-05-2025 21:58:13","site went down due to plan work on site (SWAP of Ener=
gie Ubaie by bigans / 650631358 ) // End of work","","Installation Activity=
","Passive","Planned Activity","Installation Activity","site went down due =
to plan work on site (SWAP of Energie Ubaie by bigans / 650631358 ) // End =
of work","gaelle.njiofack@matech-cameroun.com","138","19-05-2025 16:01:44",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005056293","Ngoum","=
","19-05-2025 15:55:54","19-05-2025 15:44:35","19-05-2025 17:55:00","Cascad=
ed Incident from TTO5192608","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Hybrid Gen site, site went down because G=
en started and stopped due to iBattery coast not well fixed// He fixed it w=
ell","system","1664375","19-05-2025 15:55:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005056294","Yoko MTN=
","","19-05-2025 15:55:54","19-05-2025 15:44:35","19-05-2025 17:55:00","Cas=
caded Incident from TTO5192608","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen site, site went down becaus=
e Gen started and stopped due to iBattery coast not well fixed// He fixed i=
t well","system","1664376","19-05-2025 15:55:54","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005056288","ELO=
UMDEM CARRIERE","","19-05-2025 15:54:37","19-05-2025 15:49:29","19-05-2025 =
15:54:58","site went down due to work (Our FME FANDA BRICE XAVIER replace a=
 contactor) //  End of work","Fanda Brice","Equipment Replacement","Passive=
","Planned Activity","Planned Activity - Passive","site went down due to wo=
rk (Our FME FANDA BRICE XAVIER replace a contactor) //  End of work","gaell=
e.njiofack@matech-cameroun.com","309","19-05-2025 15:54:37","MATECH CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0005056274","Mat=
sari","IHS_YND_475, IHS_YND_454, IHS_YND_473, IHS_YND_456","19-05-2025 15:5=
3:03","19-05-2025 15:44:35","19-05-2025 17:55:00","Hybrid Gen site, site we=
nt down because Gen started and stopped due to iBattery coast not well fixe=
d// He fixed it well","Parker Tchoup","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Generator Battery","Hybrid Gen site, site went down because Gen =
started and stopped due to iBattery coast not well fixed// He fixed it well=
","loic.noumsi@matech-cameroun.com","509","19-05-2025 15:53:03","MATECH CMR=
"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0005056221","San=
ta Barbara Gottam","","19-05-2025 15:44:40","19-05-2025 15:40:33","19-05-20=
25 16:11:59","Grid outage, Gen failed to start due to Batterry Gen Faulty /=
/ Gen started with Battery backup.","Delor Telezing","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Generator Battery","Grid outage, Gen failed to st=
art due to Batterry Gen Faulty // Gen started with Battery backup.","loic.n=
oumsi@matech-cameroun.com","248","19-05-2025 15:44:40","MATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0005056162","S=
ofavinc","","19-05-2025 15:34:54","19-05-2025 15:31:45","19-05-2025 16:23:2=
4","Site went down because Gen failed to start due to card Ge DYSFUNCTION /=
/ He reseted it and started Gen manually","MINKA NICOLAS","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Site went down because Gen f=
ailed to start due to card Ge DYSFUNCTION // He reseted it and started Gen =
manually","gaelle.njiofack@matech-cameroun.com","189","19-05-2025 15:34:54"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005056161","M=
essassi 2","","19-05-2025 15:34:34","19-05-2025 15:30:20","19-05-2025 16:04=
:23","Grid outage, site went down because Gen failed to start due to Gen ov=
erload // He reduced load","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage, site went down because Gen failed=
 to start due to Gen overload // He reduced load","loic.noumsi@matech-camer=
oun.com","256","19-05-2025 15:34:34","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005056064","Nta=
ba","","19-05-2025 15:15:39","19-05-2025 15:09:31","19-05-2025 23:01:20","S=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Site went down due to PWC Overload(12=
Kw 250A) Blaise Raoul SS IHS is iformed //Site stabilised","loic.noumsi@mat=
ech-cameroun.com","369","19-05-2025 15:15:39","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0005055957","Nsi=
malen MTN","","19-05-2025 15:01:06","19-05-2025 14:56:54","19-05-2025 15:15=
:36","Grid Outage, site went down due to PM (Poor battery backup) // End of=
 work site on Gen","Albran Byorel","Equipment Replacement","Passive","Plann=
ed Activity","Planned Activity - Passive","Grid Outage, site went down due =
to PM (Poor battery backup) // End of work site on Gen","loic.noumsi@matech=
-cameroun.com","253","19-05-2025 15:01:06","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005055904","M=
vog-Manga","","19-05-2025 14:51:05","19-05-2025 14:38:24","19-05-2025 16:04=
:08","Site went down due to absence of one phase // bridge made between the=
 other two","Albran Byorel","Grid Supply","Passive","Grid","National Grid -=
 Grid Incomplete Phase","Site went down due to absence of one phase // brid=
ge made between the other two","loic.noumsi@matech-cameroun.com","763","19-=
05-2025 14:51:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0005055734","ODZA MIN=
KAN EDIBI ASSI","","19-05-2025 14:27:57","19-05-2025 14:22:46","19-05-2025 =
14:30:51","Cascaded Incident from TTO5191988","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down due to pl=
an work activitiy on site (SS IHS Felix & Blaise were on site for a SWAP of=
 Ubaie // End of work","system","1662110","19-05-2025 14:27:57","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0005055732","Mehanda =
1","","19-05-2025 14:27:56","19-05-2025 14:22:46","19-05-2025 14:30:51","Ca=
scaded Incident from TTO5191988","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to plan work activ=
itiy on site (SS IHS Felix & Blaise were on site for a SWAP of Ubaie // End=
 of work","system","1662109","19-05-2025 14:27:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0005055733","Odza Min=
kan IHS","","19-05-2025 14:27:56","19-05-2025 14:22:46","19-05-2025 14:30:5=
1","Cascaded Incident from TTO5191988","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to plan work=
 activitiy on site (SS IHS Felix & Blaise were on site for a SWAP of Ubaie =
// End of work","system","1662110","19-05-2025 14:27:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005055731","MEHANDAN=
","","19-05-2025 14:27:56","19-05-2025 14:22:46","19-05-2025 14:30:51","Cas=
caded Incident from TTO5191988","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to plan work activi=
tiy on site (SS IHS Felix & Blaise were on site for a SWAP of Ubaie // End =
of work","system","1662109","19-05-2025 14:27:56","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005055714","Nko=
lnda","IHS_YND_385, IHS_YND_528, IHS_YND_746, IHS_YND_715, IHS_YND_749","19=
-05-2025 14:25:53","19-05-2025 14:22:46","19-05-2025 14:30:51","Site went d=
own due to plan work activitiy on site (SS IHS Felix & Blaise were on site =
for a SWAP of Ubaie // End of work","Albran Byorel","Installation Activity"=
,"Passive","Planned Activity","Installation Activity","Site went down due t=
o plan work activitiy on site (SS IHS Felix & Blaise were on site for a SWA=
P of Ubaie // End of work","loic.noumsi@matech-cameroun.com","188","19-05-2=
025 14:25:53","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005055629","T=
amtam Weekend","","19-05-2025 14:15:34","19-05-2025 06:42:18","19-05-2025 0=
7:00:35","No power issue site on Grid with U=3D52.7V The TX FME Mbah Hosiah=
 (674007438) FROM Huawei is informed .","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue site on Grid with U=3D52.7V The TX FME Mbah Hosiah (674007438) FRO=
M Huawei is informed .","vanel.mbiada@matech-cameroun.com","27197","19-05-2=
025 14:15:34","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005055564","B=
arriere IHS","","19-05-2025 14:05:00","19-05-2025 14:02:55","20-05-2025 10:=
49:47","Site down due to GEN OVERLOAD (280A; 20KVA)//Grid return","Hyemafo =
Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site dow=
n due to GEN OVERLOAD (280A; 20KVA)//Grid return","vanel.mbiada@matech-came=
roun.com","127","19-05-2025 14:05:00","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005055510","N=
taba","","19-05-2025 13:54:50","19-05-2025 13:52:14","19-05-2025 14:11:46",=
"Site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iform=
ed //Site stabilised","Delor Telezing","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Site went down due to PWC Overload(12Kw=
 250A) Blaise Raoul SS IHS is iformed //Site stabilised","vanel.mbiada@mate=
ch-cameroun.com","157","19-05-2025 13:54:50","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0005055395","Nko=
langaa","","19-05-2025 13:40:42","19-05-2025 13:35:35","19-05-2025 13:48:23=
","No power issue on site Ubay =3D 53.1V Site on Grid (TX FME Henri (699949=
693) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site Ubay =3D 53.1V Site on Grid (TX FME Henri (699949693) from Huawei =
is informed","cedric.tiani@matech-cameroun.com","308","19-05-2025 13:40:42"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0005055049","ARMP",""=
,"19-05-2025 12:52:11","19-05-2025 12:46:05","19-05-2025 13:45:20","Cascade=
d Incident from TTO5191233","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down to start due to RCP faulty//He replace i=
t with a 200V of Relay","system","1660708","19-05-2025 12:52:11","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0005055048","Bastos B=
ir","","19-05-2025 12:52:10","19-05-2025 12:46:05","19-05-2025 13:45:20","C=
ascaded Incident from TTO5191233","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down to start due to RCP f=
aulty//He replace it with a 200V of Relay","system","1660707","19-05-2025 1=
2:52:10","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0005055034","D=
ragage","IHS_YND_704, IHS_YND_208","19-05-2025 12:50:01","19-05-2025 12:46:=
05","19-05-2025 13:45:20","Site went down to start due to RCP faulty//He re=
place it with a 200V of Relay","Mboua Thierry","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Site went down to start due t=
o RCP faulty//He replace it with a 200V of Relay","vanel.mbiada@matech-came=
roun.com","238","19-05-2025 12:50:01","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0005054779","Eki=
e sud","","19-05-2025 12:14:25","19-05-2025 12:13:18","19-05-2025 13:15:21"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage// He bypasse the Grid and site on Gen	","Albran Byorel","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation, Site went down because gen fails to start due to grid bad voltage/=
/ He bypasse the Grid and site on Gen	","cedric.tiani@matech-cameroun.com",=
"69","19-05-2025 12:14:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005054730","Messassi=
 okolo","","19-05-2025 12:08:54","19-05-2025 12:06:41","19-05-2025 16:24:33=
","Cascaded Incident from TTO5190893","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","	Grid outage, site down becaus=
e site behaves as Grid only site (no Gen)//Grid return","system","1662997",=
"19-05-2025 12:08:54","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005054727","E=
MANA BILICK CITY","IHS_YND_279","19-05-2025 12:08:06","19-05-2025 12:06:41"=
,"19-05-2025 16:28:21","Grid outage, site down because site behaves as Grid=
 only site (no Gen)//Grid return","Fabrice Pouakam","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","	Grid outage, site down becaus=
e site behaves as Grid only site (no Gen)//Grid return","vanel.mbiada@matec=
h-cameroun.com","87","19-05-2025 12:08:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005054716","Emana Ly=
cee","","19-05-2025 12:05:49","19-05-2025 12:00:23","19-05-2025 12:16:11","=
Cascaded Incident from TTO5190865","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down befo=
re Gen started due to poor battery backup //gen automaticaly started","syst=
em","1663371","19-05-2025 12:05:49","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005054712","E=
mana lycee 2","IHS_YND_274","19-05-2025 12:04:33","19-05-2025 12:00:23","19=
-05-2025 12:17:16","Grid outage , site went down before Gen started due to =
poor battery backup //gen automaticaly started","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age , site went down before Gen started due to poor battery backup //gen au=
tomaticaly started","vanel.mbiada@matech-cameroun.com","252","19-05-2025 12=
:04:33","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005054692","Mes=
sassi 2","","19-05-2025 12:01:03","19-05-2025 12:00:55","19-05-2025 12:10:4=
7","Grid outage site went down because Gen failed to start due to poor Batt=
ery backup// GEN automatically started","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site=
 went down because Gen failed to start due to poor Battery backup// GEN aut=
omatically started","cedric.tiani@matech-cameroun.com","10","19-05-2025 12:=
01:03","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005054528","C=
rf-Nsam","","19-05-2025 11:32:47","19-05-2025 11:29:26","19-05-2025 11:33:3=
8","Active // No power issue on site Ubaie =3D53.6V site on Grid The TX FME=
 Henri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri =
(699949693) from Huawei is informed","vanel.mbiada@matech-cameroun.com","20=
3","19-05-2025 11:32:47","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005054003","N=
kolbong","","19-05-2025 10:05:29","19-05-2025 10:03:11","19-05-2025 11:58:4=
1","	Grid outage,Site went down because Gen started and stopped due to Gen =
overload(22kva//350A)//He reduiced the load and maually started the Gen","D=
elor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","	=
Grid outage,Site went down because Gen started and stopped due to Gen overl=
oad(22kva//350A)//He reduiced the load and maually started the Gen","vanel.=
mbiada@matech-cameroun.com","139","19-05-2025 10:05:29","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005053976","Par=
adis Hotel","","19-05-2025 09:58:17","19-05-2025 09:57:09","19-05-2025 09:5=
9:36","Site went down due to Insufficient rectifiers on site(02)//He neeed =
to add 01 or 02 rectifiers and site stabilised","Siligap Boris","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down due to Ins=
ufficient rectifiers on site(02)//He neeed to add 01 or 02 rectifiers and s=
ite stabilised","cedric.tiani@matech-cameroun.com","69","19-05-2025 09:58:1=
7","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0005053955","ARMP",""=
,"19-05-2025 09:55:21","19-05-2025 09:52:50","19-05-2025 11:11:26","Cascade=
d Incident from TTO5189976","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage,Site went down because Gen failed to start =
due to RCP faulty//He manuallly started the Gen","system","1656741","19-05-=
2025 09:55:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0005053954","Bastos B=
ir","","19-05-2025 09:55:21","19-05-2025 09:52:50","19-05-2025 11:11:26","C=
ascaded Incident from TTO5189976","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,Site went down because G=
en failed to start due to RCP faulty//He manuallly started the Gen","system=
","1656742","19-05-2025 09:55:21","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0005053917","D=
ragage","IHS_YND_704, IHS_YND_208","19-05-2025 09:54:01","19-05-2025 09:52:=
50","19-05-2025 11:14:25","Grid outage,Site went down because Gen failed to=
 start due to RCP faulty//He manuallly started the Gen","Mboua Thierry","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 outage,Site went down because Gen failed to start due to RCP faulty//He ma=
nuallly started the Gen","vanel.mbiada@matech-cameroun.com","73","19-05-202=
5 09:54:01","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005053914","SIM=
BOCK BONAMBAPE","","19-05-2025 09:53:03","19-05-2025 09:50:51","19-05-2025 =
09:52:48","grid outage, site went down due to Gen Overload (20kva, 350A) SS=
 IHS Felix ZAMBE confirmed // Site stabilisation","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","grid outage, site went d=
own due to Gen Overload (20kva, 350A) SS IHS Felix ZAMBE confirmed // Site =
stabilisation","cedric.tiani@matech-cameroun.com","133","19-05-2025 09:53:0=
3","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005053857","B=
arriere IHS","","19-05-2025 09:49:50","19-05-2025 09:46:37","19-05-2025 12:=
38:53","Grid outage, site went down due to gen overload(20KVA, 240A),SS Fel=
ix IHS //He reduiced the load an site on Gen","Hyemafo Gildas","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down =
due to gen overload(20KVA, 240A),SS Felix IHS //He reduiced the load an sit=
e on Gen","vanel.mbiada@matech-cameroun.com","195","19-05-2025 09:49:50","M=
ATECH CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0005053773","Men=
dong Maeture","","19-05-2025 09:38:20","19-05-2025 09:36:11","19-05-2025 09=
:38:57","Grid fluctuation,site went down because gen failed to start due to=
 grid bad voltage // He bypassed the Grid and site on Grid","Hyemafo Gildas=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation,site went down because gen failed to start due to grid ba=
d voltage // He bypassed the Grid and site on Grid","cedric.tiani@matech-ca=
meroun.com","130","19-05-2025 09:38:20","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005053728","M=
endong vallee","","19-05-2025 09:31:41","19-05-2025 09:30:27","19-05-2025 0=
9:34:21","Grid outage site went down because Gen overload (20KVA; 300A) IHS=
 F=E9lix Zamb=E9 is informed and confirmed // Grid returned","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site=
 went down because Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is inform=
ed and confirmed // Grid returned","vanel.mbiada@matech-cameroun.com","76",=
"19-05-2025 09:31:41","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0005053654","Nko=
abang Ebolmedjock","","19-05-2025 09:20:18","19-05-2025 09:16:12","19-05-20=
25 12:22:58","Site went down because gen started and stopped with Alarm low=
 oil pressure//He added oil and manually Started the Gen","Mba Lazare Herve=
","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Site w=
ent down because gen started and stopped with Alarm low oil pressure//He ad=
ded oil and manually Started the Gen","cedric.tiani@matech-cameroun.com","2=
47","19-05-2025 09:20:18","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005053535","M=
ANGUIERS CHAPELLE","","19-05-2025 08:50:28","19-05-2025 08:45:34","19-05-20=
25 08:50:52","Active//No power issue on site ,site on Grid with Ubaie=3D53.=
6 V The Tx FME Symphorien (650257151) from Huawei is informed","Fabrice Pou=
akam","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active//No power issue on site ,site on Grid with Ubaie=
=3D53.6 V The Tx FME Symphorien (650257151) from Huawei is informed","vanel=
.mbiada@matech-cameroun.com","296","19-05-2025 08:50:28","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0005053422","Clu=
b France","","19-05-2025 08:20:27","19-05-2025 08:12:18","19-05-2025 19:35:=
15","Grid only site, No space to deploy a MDG // Grid restored","","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid only=
 site, No space to deploy a MDG // Grid restored","cedric.tiani@matech-came=
roun.com","490","19-05-2025 08:20:27","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005053344","Odz=
a II OCM","","19-05-2025 08:02:23","19-05-2025 07:53:59","19-05-2025 08:06:=
12","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction // Site stabilised","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, site went down b=
ecause gen failed to start due to PWC ZTE malfunction // Site stabilised","=
cedric.tiani@matech-cameroun.com","506","19-05-2025 08:02:23","MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0005053138","Nko=
abang MTN","","19-05-2025 07:09:45","19-05-2025 07:02:36","19-05-2025 08:05=
:53","Grid fluctuations, Site went down because gen failed to start due to =
grid bad voltage // He bypassed Grid and he manually started Gen","Mba Laza=
re Herve","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuations, Site went down because gen failed to start due =
to grid bad voltage // He bypassed Grid and he manually started Gen","cedri=
c.tiani@matech-cameroun.com","430","19-05-2025 07:09:45","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005053112","O=
LAMA","","19-05-2025 07:06:05","19-05-2025 07:05:56","19-05-2025 07:30:48",=
"No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (6999=
49693) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubaie =3D54.9V site on Grid. The TX FME Henri (699949693) from Huawei=
 is informed","ludivine.ngamaleu@ihstowers.com","10","19-05-2025 07:06:05",=
"MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0005052919","Eko=
mbitie","","19-05-2025 06:18:26","19-05-2025 06:12:19","19-05-2025 07:43:23=
","Grid fluctuation , site went down because Gen started and stopped due to=
 Grid bad voltage// he bypassed, site is on GEN","Fabrice Pouakam","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation , site went down because Gen started and stopped due to Grid bad vo=
ltage// he bypassed, site is on GEN","gerard.tchangoue@matech-cameroun.com"=
,"368","19-05-2025 06:18:26","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005052537","Sof=
avinc","","19-05-2025 03:31:18","19-05-2025 03:24:08","19-05-2025 07:12:41"=
,"Access issues during the night due to landlord Site went down because Gen=
 failed to start due to card Ge DYSFUNCTION // He reseted it and started Ge=
n manually","MINKA NICOLAS","Access Denial","Lease Or Legal","Landlord Rela=
ted Issues","Access Issue - Land Lord","Site went down because Gen failed t=
o start due to card Ge DYSFUNCTION // He reseted it and started Gen manuall=
y","gerard.tchangoue@matech-cameroun.com","431","19-05-2025 03:31:18","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005052514","T=
alla Monatele","","19-05-2025 03:16:15","19-05-2025 03:15:06","19-05-2025 0=
3:36:15","No power issue, site is on grid with Ubaie=3D54.9V, Gregoir (6545=
47479) from Huawei is informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue,=
 site is on grid with Ubaie=3D54.9V, Gregoir (654547479) from Huawei is inf=
ormed","christelle.ngonga@matech-cameroun.com","70","19-05-2025 03:16:15","=
MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005052512","O=
LAMA","","19-05-2025 03:14:57","19-05-2025 03:14:49","19-05-2025 03:24:49",=
"No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (6999=
49693) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubaie =3D54.9V site on Grid. The TX FME Henri (699949693) from Huawei=
 is informed","christelle.ngonga@matech-cameroun.com","9","19-05-2025 03:14=
:57","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005052511","N=
kolbong","","19-05-2025 03:14:09","19-05-2025 03:10:01","19-05-2025 05:56:1=
7","Grid outage,Site went down because Gen started and stopped due to Gen o=
verload(22kva//350A)//He reduiced the load and maually started the Gen","De=
lor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage,Site went down because Gen started and stopped due to Gen overloa=
d(22kva//350A)//He reduiced the load and maually started the Gen","christel=
le.ngonga@matech-cameroun.com","249","19-05-2025 03:14:09","MATECH CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0005052510","O=
bobogo","","19-05-2025 03:13:12","19-05-2025 03:04:53","19-05-2025 03:33:48=
","","MINKA NICOLAS","Cascade Outage","Active","Cascade Active","Cascade Ac=
tive","No power issue site on grid with Ubai1=3D55.3V, Site on GRID The TX =
Fme Hosiah / 674007438// from huawei is informed","christelle.ngonga@matech=
-cameroun.com","1666793","19-05-2025 03:13:12","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0005052509","E=
foulan","IHS_YND_155","19-05-2025 03:12:04","19-05-2025 03:04:53","19-05-20=
25 03:33:48","Site impacted by CTR_773_Z_Efoulan-Pont(CTR-773) Not manage b=
y IHS","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","No power issue site on grid with=
 Ubai1=3D55.3V, Site on GRID The TX Fme Hosiah / 674007438// from huawei is=
 informed","christelle.ngonga@matech-cameroun.com","432","19-05-2025 03:12:=
04","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0005052350","UPA=
C LP","","19-05-2025 01:37:30","19-05-2025 01:28:15","19-05-2025 01:38:15",=
"Active, no power issue, site on grid with U=3D54.4V Tx FME mand Ngetsa (??=
699949553??) From Huawei is informed.","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issu=
e, site on grid with U=3D54.4V Tx FME mand Ngetsa (??699949553??) From Huaw=
ei is informed.","gerard.tchangoue@matech-cameroun.com","556","19-05-2025 0=
1:37:30","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005052154","AKA=
K Nkozoa","","19-05-2025 00:01:45","18-05-2025 23:04:34","19-05-2025 01:34:=
37","Site went down due to insufficient rectifier issue // he reseted it","=
Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient rectifier issue // he reseted it","ge=
rard.tchangoue@matech-cameroun.com","3432","19-05-2025 00:01:45","MATECH CM=
R"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005051949","S=
IMBOCK BONAMBAPE","","18-05-2025 23:03:44","18-05-2025 22:19:30","19-05-202=
5 08:16:39","Grid outage, site went down due to Gen Overload (20kva, 350A) =
SS IHS Felix ZAMBE confirmed//Grid return","Hyemafo Gildas","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due=
 to Gen Overload (20kva, 350A) SS IHS Felix ZAMBE confirmed//Grid return","=
christelle.ngonga@matech-cameroun.com","2655","18-05-2025 23:03:44","MATECH=
 CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0005051937","Eko=
mbitie","","18-05-2025 22:57:20","18-05-2025 22:52:08","18-05-2025 22:58:08=
","Grid fluctuation, Site went down because gen fails to start due to grid =
bad voltage // He bypassed the Grid and site on Gen","Fabrice Pouakam","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation, Site went down because gen fails to start due to grid bad volt=
age // He bypassed the Grid and site on Gen","gerard.tchangoue@matech-camer=
oun.com","313","18-05-2025 22:57:20","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005051847","S=
aa","","18-05-2025 22:39:47","18-05-2025 20:50:47","18-05-2025 23:17:47","G=
rid outage, Site went down because Gen start and stopped with ""High temps"=
" alarm // he added water and manually start the Gen	","Parker Tchoup","Equ=
ipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, Site went=
 down because Gen start and stopped with ""High temps"" alarm // he added w=
ater and manually start the Gen	","kouoh.jean@ihstowers.com","6541","18-05-=
2025 22:39:47","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005051815","O=
LAMA","","18-05-2025 22:33:40","18-05-2025 19:20:57","18-05-2025 22:34:41",=
"Backtraking. Active // No power issue on site Ubaie =3D54.9V site on Grid.=
 The TX FME Henri (699949693) from Huawei is informed","Fanda Brice","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active // No power issue on site Ubaie =3D54.9V site on Grid. The TX =
FME Henri (699949693) from Huawei is informed","christelle.ngonga@matech-ca=
meroun.com","11564","18-05-2025 22:33:40","MATECH CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0005051805","M=
endong Maeture","","18-05-2025 22:30:29","18-05-2025 22:24:21","18-05-2025 =
23:35:36","Grid fluctuations, site went down due to bad Eneo voltage // Gri=
d restoration","Hyemafo Gildas","Grid Supply","Passive","Grid","National Gr=
id - Low Current Supply","Grid fluctuations, site went down due to bad Eneo=
 voltage // Grid restoration","christelle.ngonga@matech-cameroun.com","368"=
,"18-05-2025 22:30:29","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0005051561","T=
alla Monatele","","18-05-2025 21:52:46","18-05-2025 21:35:29","19-05-2025 0=
0:15:16"," no power issue, site is on grid with Ubaie=3D54.9V, Gregoir (654=
547479) from Huawei working on site","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," no power =
issue, site is on grid with Ubaie=3D54.9V, Gregoir (654547479) from Huawei =
working on site","christelle.ngonga@matech-cameroun.com","1038","18-05-2025=
 21:52:46","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005051554","E=
vodoula OCM","","18-05-2025 21:51:28","18-05-2025 21:45:19","18-05-2025 22:=
44:19","Grid outage,gen failed to start due to grid bad voltage,no rcp//he =
bypassed the Grid and site on Gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid outage,ge=
n failed to start due to grid bad voltage,no rcp//he bypassed the Grid and =
site on Gen","christelle.ngonga@matech-cameroun.com","370","18-05-2025 21:5=
1:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005051478","Emana Ly=
cee","","18-05-2025 21:45:39","18-05-2025 21:14:18","18-05-2025 21:30:33","=
Cascaded Incident from TTO5186963","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down befo=
re Gen started due to poor battery backup //gen automaticaly started.","sys=
tem","1673389","18-05-2025 21:45:39","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005051437","Nko=
l-Mebanga","","18-05-2025 21:40:09","18-05-2025 20:55:58","18-05-2025 20:56=
:13","WRONGLY TICKET","Parker Tchoup","Incorrectly Logged Tickets","Error",=
"Error","Error","WRONGLY TICKET","franck.nkomot@matech-cameroun.com","2652"=
,"18-05-2025 21:40:09","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005051417","OBA=
M NGOLA OCM","","18-05-2025 21:37:38","18-05-2025 21:32:31","18-05-2025 21:=
38:31","Site went down due to insufficient rectifier on site//site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifier on site//site stabilised=
","franck.nkomot@matech-cameroun.com","308","18-05-2025 21:37:38","MATECH C=
MR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005051397","N=
kolfon Cimencam","","18-05-2025 21:33:43","18-05-2025 21:20:36","18-05-2025=
 21:43:25","No power issue, Site impacted by Afanoya-II wich is not IHS sit=
e.","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipmen=
t Failure","Affected by 3rd Party Site","No power issue, Site impacted by A=
fanoya-II wich is not IHS site.","christelle.ngonga@matech-cameroun.com","7=
88","18-05-2025 21:33:43","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005051316","Ema=
na lycee 2","IHS_YND_274","18-05-2025 21:20:27","18-05-2025 21:14:18","18-0=
5-2025 21:32:36","Grid outage , site went down before Gen started due to po=
or battery backup //gen automaticaly started.","Fabrice Pouakam","Equipment=
 Repair","Passive","ACDG Gen","DG Low Battery","Grid outage , site went dow=
n before Gen started due to poor battery backup //gen automaticaly started.=
","franck.nkomot@matech-cameroun.com","463","18-05-2025 21:20:27","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005051177","Messassi=
 okolo","","18-05-2025 20:53:55","18-05-2025 20:41:10","18-05-2025 21:26:32=
","Cascaded Incident from TTO5186794","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (no Gen)//Grid return","system","1675333","=
18-05-2025 20:53:55","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0005051140","Nko=
lbong","","18-05-2025 20:44:21","18-05-2025 20:32:56","18-05-2025 22:03:56"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload // He reduiced load and Gen manually started","Delor Telezing","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen started and stopped due to Gen overload // He reduiced l=
oad and Gen manually started","franck.nkomot@matech-cameroun.com","686","18=
-05-2025 20:44:21","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0005051135","E=
mana Lycee","","18-05-2025 20:43:48","18-05-2025 20:29:15","18-05-2025 20:4=
8:12","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage , site went down before Gen to started due to p=
oor battery backup //gen automaticaly started.","christelle.ngonga@matech-c=
ameroun.com","1676048","18-05-2025 20:43:48","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005051131","E=
mana lycee 2","IHS_YND_274","18-05-2025 20:43:23","18-05-2025 20:29:15","18=
-05-2025 20:48:12","Grid outage , site went down before Gen to started due =
to poor battery backup //gen automaticaly started.","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","DG Low Battery","Grid outage , site wen=
t down before Gen to started due to poor battery backup //gen automaticaly =
started.","christelle.ngonga@matech-cameroun.com","849","18-05-2025 20:43:2=
3","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005051130","EMA=
NA BILICK CITY","IHS_YND_279","18-05-2025 20:43:17","18-05-2025 20:41:10","=
18-05-2025 21:31:50","Grid outage, site down because site behaves as Grid o=
nly site (no Gen)//Grid return","Fabrice Pouakam","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","Grid outage, site down because s=
ite behaves as Grid only site (no Gen)//Grid return","franck.nkomot@matech-=
cameroun.com","128","18-05-2025 20:43:17","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005051086","B=
arriere IHS","","18-05-2025 20:36:09","18-05-2025 20:29:56","19-05-2025 01:=
08:06","Grid outage, site went down because gen ran untill fuel shortage //=
 Refueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage, site went down because gen ran untill fuel shortage /=
/ Refueling done","christelle.ngonga@matech-cameroun.com","375","18-05-2025=
 20:36:09","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0005051077","NYO=
M 2 IHS","","18-05-2025 20:35:24","18-05-2025 20:30:14","18-05-2025 20:53:1=
4","Grid fluctuation,site went down because Gen failed to start due to Grid=
 bad voltage// Grid stabilisation","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,site w=
ent down because Gen failed to start due to Grid bad voltage// Grid stabili=
sation","franck.nkomot@matech-cameroun.com","1743","18-05-2025 20:35:24","M=
ATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005051070","Mes=
sassi 2","","18-05-2025 20:34:16","18-05-2025 20:30:07","18-05-2025 22:22:0=
7","(very unstable) Grid outage, Site went down due to 02/08 rectifiers iss=
ue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","(very unstable) Grid outage, Site went down due =
to 02/08 rectifiers issue // Grid stabilised","franck.nkomot@matech-camerou=
n.com","250","18-05-2025 20:34:16","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005050859","B=
arriere","","18-05-2025 20:04:05","18-05-2025 20:02:58","19-05-2025 00:05:0=
2","No power issue on site Ubay: 54.05V site on Grid TX Fme SAMBA (65426605=
8/Huawei) is informed","Hyemafo Gildas","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
Ubay: 54.05V site on Grid TX Fme SAMBA (654266058/Huawei) is informed","chr=
istelle.ngonga@matech-cameroun.com","69","18-05-2025 20:04:05","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005050788","M=
endong vallee","","18-05-2025 19:46:03","18-05-2025 18:55:58","18-05-2025 1=
9:51:58","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage.gen start and stopped due to alarm ""high temp""=
 // We added water and gen manually started","christelle.ngonga@matech-came=
roun.com","1674461","18-05-2025 19:46:03","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005050615","OBA=
M NGOLA OCM","","18-05-2025 19:17:18","18-05-2025 19:14:09","18-05-2025 20:=
45:09","Site went down due to insufficient rectifier on site//site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifier on site//site stabilised=
","franck.nkomot@matech-cameroun.com","190","18-05-2025 19:17:18","MATECH C=
MR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0005050497","Men=
dong Maeture","IHS_YND_692","18-05-2025 18:58:06","18-05-2025 18:55:58","18=
-05-2025 19:53:58","Grid outage.gen start and stopped due to alarm ""high t=
emp"" // We added water and gen manually started","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","Gen Temp High","Grid outage.gen start and =
stopped due to alarm ""high temp"" // We added water and gen manually start=
ed","franck.nkomot@matech-cameroun.com","129","18-05-2025 18:58:06","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0005050494","C=
amp-Sic-Tsinga","","18-05-2025 18:56:55","18-05-2025 18:40:48","18-05-2025 =
19:08:38","No power issue Ubaie:53.8V, Site on Grid. The Tx FME Brice Tsagu=
e(650214096/ Huawei) is informed.","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ubaie:53.8=
V, Site on Grid. The Tx FME Brice Tsague(650214096/ Huawei) is informed.","=
christelle.ngonga@matech-cameroun.com","968","18-05-2025 18:56:55","MATECH =
CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005050474","C=
NR","","18-05-2025 18:55:35","18-05-2025 18:40:17","18-05-2025 19:39:06","N=
o power issue site on grid with U=3D53.8V Brice (650214096)  from Huaie is =
informed","Mboua Thierry","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D=
53.8V Brice (650214096)  from Huaie is informed","christelle.ngonga@matech-=
cameroun.com","918","18-05-2025 18:55:35","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0005050471","H=
-Progres","","18-05-2025 18:54:45","18-05-2025 18:40:56","18-05-2025 20:31:=
56","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage. Gen ran until fuel shortage //Refueling done","christelle.ngong=
a@matech-cameroun.com","1668268","18-05-2025 18:54:45","MATECH CMR"
"Closed Complete","Site Down","CTR_110","IHS_YND_028","NOCINC0005050466","H=
-Central","IHS_YND_083","18-05-2025 18:54:08","18-05-2025 18:40:56","18-05-=
2025 20:31:56","Grid outage. Gen ran until fuel shortage //Refueling done",=
"Paul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage=
. Gen ran until fuel shortage //Refueling done","christelle.ngonga@matech-c=
ameroun.com","793","18-05-2025 18:54:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005050297","MEHANDAN=
","","18-05-2025 18:23:07","18-05-2025 18:16:39","18-05-2025 18:23:38","Cas=
caded Incident from TTO5185769","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to PWC=
 ZTE malfunction ,//  site stabilization","system","1675844","18-05-2025 18=
:23:07","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005050289","O=
dza II OCM","IHS_YND_528","18-05-2025 18:21:46","18-05-2025 18:16:39","18-0=
5-2025 18:23:38","Grid outage, site went down due to PWC ZTE malfunction ,/=
/  site stabilization","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","ATS-AMF Issue","Grid outage, site went down due to PWC ZTE malfun=
ction ,//  site stabilization","christelle.ngonga@matech-cameroun.com","309=
","18-05-2025 18:21:46","MATECH CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0005050279","T=
radex-Nkomo","","18-05-2025 18:20:36","18-05-2025 18:14:56","18-05-2025 20:=
26:56","Site went down due to insufficient rectifier on site//site stabilis=
ed","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifier on site//site stabilised=
","christelle.ngonga@matech-cameroun.com","341","18-05-2025 18:20:36","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005050231","E=
toug ebe Meweulo","","18-05-2025 18:13:21","18-05-2025 18:12:06","18-05-202=
5 18:13:56","Grid fluctuation site went down because Gen started and stoppe=
d due to Grid bad voltage // Grid stabilised","Hyemafo Gildas","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion site went down because Gen started and stopped due to Grid bad voltage =
// Grid stabilised","christelle.ngonga@matech-cameroun.com","76","18-05-202=
5 18:13:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005050095","MEHANDAN=
","","18-05-2025 17:39:36","18-05-2025 17:34:59","18-05-2025 17:42:59","Cas=
caded Incident from TTO5185547","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to PWC=
 ZTE malfunction // site stabilized Without intervention","system","1672129=
","18-05-2025 17:39:36","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005050094","O=
dza II OCM","IHS_YND_528","18-05-2025 17:39:08","18-05-2025 17:34:59","18-0=
5-2025 17:42:59","Grid outage, site went down due to PWC ZTE malfunction //=
 site stabilized Without intervention","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site went =
down due to PWC ZTE malfunction // site stabilized Without intervention","c=
hristelle.ngonga@matech-cameroun.com","251","18-05-2025 17:39:08","MATECH C=
MR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0005050037","R=
d-Pt-Express","","18-05-2025 17:27:05","18-05-2025 17:25:59","18-05-2025 17=
:34:59","SS IHS was on site for plan work (securing transmission)//End of w=
ork","","Installation Activity","Passive","Planned Activity","Installation =
Activity","SS IHS was on site for plan work (securing transmission)//End of=
 work","christelle.ngonga@matech-cameroun.com","67","18-05-2025 17:27:05","=
MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005049998","SAA=
 Entrance","","18-05-2025 17:21:12","18-05-2025 17:13:06","18-05-2025 17:21=
:06","Site went down due to plan work activity (SS MATECH PARKER WAS ON SIT=
E to swap of RCP) // End of work","Parker Tchoup","Installation Activity","=
Passive","Planned Activity","Installation Activity","Site went down due to =
plan work activity (SS MATECH PARKER WAS ON SITE to swap of RCP) // End of =
work","franck.nkomot@matech-cameroun.com","487","18-05-2025 17:21:12","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005049675","E=
toug ebe Meweulo","","18-05-2025 16:25:38","18-05-2025 16:24:33","18-05-202=
5 16:26:02","Grid fluctuation site went down because Gen started and stoppe=
d due to Grid bad voltage // Grid stabilised","Hyemafo Gildas","Grid Supply=
","Passive","Grid","National Grid - Low Current Supply","Grid fluctuation s=
ite went down because Gen started and stopped due to Grid bad voltage // Gr=
id stabilised","christelle.ngonga@matech-cameroun.com","66","18-05-2025 16:=
25:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_008","NOCINC0005049549","CNDH",""=
,"18-05-2025 15:56:55","18-05-2025 15:52:39","18-05-2025 16:50:08","ERROR t=
icket logged","Paul BIBOUM","Incorrectly Logged Tickets","Error","Error","E=
rror","ERROR ticket logged","system","256","18-05-2025 15:56:55","MATECH CM=
R"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0005049538","C=
NR","","18-05-2025 15:55:04","18-05-2025 15:52:39","18-05-2025 15:55:02","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
 automatically","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","DG=
 Low Battery","Grid outage, Site went down before Gen start due to poor bac=
kup // Gen start automatically","christelle.ngonga@matech-cameroun.com","14=
6","18-05-2025 15:55:04","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005049525","E=
ssomba","","18-05-2025 15:52:25","18-05-2025 12:34:13","18-05-2025 13:17:55=
","Site went down because PWC overload // Site stabilised,","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Site went down because PWC overload // Site stabilised,","landry.etame@ihs=
towers.com","11893","18-05-2025 15:52:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005049483","ELOUMDEM=
 CARRIERE 2","","18-05-2025 15:46:14","18-05-2025 15:41:23","18-05-2025 15:=
48:23","Cascaded Incident from TTO5184835","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","system","=
1671732","18-05-2025 15:46:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005049482","Eto koss=
 Yde","","18-05-2025 15:46:14","18-05-2025 15:41:23","18-05-2025 15:48:23",=
"Cascaded Incident from TTO5184835","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","system","1671732=
","18-05-2025 15:46:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0005049481","ELOUMDEM=
 CARRIERE","","18-05-2025 15:46:13","18-05-2025 15:41:23","18-05-2025 17:23=
:23","Grid outage, site went down because gen failed to start due to gen co=
ntactor dysfonction // Grid power return","Fanda Brice","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, site went down b=
ecause gen failed to start due to gen contactor dysfonction // Grid power r=
eturn","system","290","18-05-2025 15:46:13","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005049470","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","18-05-2025 15:43:05","18-05-2025 15:41=
:23","18-05-2025 15:48:23","Grid outage, Site went down before Gen start du=
e to poor backup // Gen started automatically","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","franck.nkomot@matech-cameroun.com","104","18-05-2025 15:43:05","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005049449","MEHANDAN=
","","18-05-2025 15:37:37","18-05-2025 15:34:47","18-05-2025 16:40:47","Cas=
caded Incident from TTO5184794","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to PWC=
 ZTE malfunction // site stabilized Without intervention","system","1678275=
","18-05-2025 15:37:37","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005049436","O=
dza II OCM","IHS_YND_528","18-05-2025 15:36:53","18-05-2025 15:34:47","18-0=
5-2025 16:50:47","Grid outage, site went down due to PWC ZTE malfunction //=
 site stabilized Without intervention","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site went =
down due to PWC ZTE malfunction // site stabilized Without intervention","c=
hristelle.ngonga@matech-cameroun.com","128","18-05-2025 15:36:53","MATECH C=
MR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0005049403","R=
d-Pt-Express","","18-05-2025 15:29:16","18-05-2025 15:24:06","18-05-2025 15=
:44:06","SS IHS was on site for plan work (securing transmission)//End of w=
ork","","Installation Activity","Passive","Planned Activity","Installation =
Activity","SS IHS was on site for plan work (securing transmission)//End of=
 work","christelle.ngonga@matech-cameroun.com","311","18-05-2025 15:29:16",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005049258","N=
taba","","18-05-2025 15:11:28","18-05-2025 15:10:21","18-05-2025 20:44:57",=
"Site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iform=
ed //Site stabilised","Delor Telezing","Equipment Repair","Passive","DCDG G=
en","DCDG - Overload","Site went down due to PWC Overload(12Kw 250A) Blaise=
 Raoul SS IHS is iformed //Site stabilised","christelle.ngonga@matech-camer=
oun.com","68","18-05-2025 15:11:28","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005049123","N=
kolfon Cimencam","","18-05-2025 14:47:23","18-05-2025 14:46:16","18-05-2025=
 14:54:11","No power issue, Site impacted by Afanoya-II wich is not manage =
by IHS","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equi=
pment Failure","Affected by 3rd Party Site","No power issue, Site impacted =
by Afanoya-II wich is not manage by IHS","christelle.ngonga@matech-cameroun=
.com","68","18-05-2025 14:47:23","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005049068","OBA=
M NGOLA OCM","","18-05-2025 14:39:12","18-05-2025 14:32:47","18-05-2025 14:=
38:47","Site went down due to insufficient rectifier on site//site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifier on site//site stabilised=
","franck.nkomot@matech-cameroun.com","386","18-05-2025 14:39:12","MATECH C=
MR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005049063","SIM=
BOCK BONAMBAPE","","18-05-2025 14:38:17","18-05-2025 14:29:11","18-05-2025 =
22:03:34","grid outage, site went down due to Gen Overload (20kva, 350A) SS=
 IHS Felix ZAMBE confirmed // Site stabilisation","Hyemafo Gildas","Equipme=
nt Repair","Passive","DCDG Gen","DCDG - Overload","grid outage, site went d=
own due to Gen Overload (20kva, 350A) SS IHS Felix ZAMBE confirmed // Site =
stabilisation","franck.nkomot@matech-cameroun.com","547","18-05-2025 14:38:=
17","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005049021","T=
amtam Weekend","","18-05-2025 14:30:40","18-05-2025 14:29:32","18-05-2025 1=
7:30:01","No power issue site on Grid with U=3D52.7V The TX FME Mbah Hosiah=
 (674007438) FROM Huawei is informed .","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue site on Grid with U=3D52.7V The TX FME Mbah Hosiah (674007438) FRO=
M Huawei is informed .","gaelle.njiofack@matech-cameroun.com","69","18-05-2=
025 14:30:40","MATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0005049018","S=
ofavinc","","18-05-2025 14:30:01","18-05-2025 14:29:57","18-05-2025 15:30:5=
7","Site went down due to insufficiency of rectifiers on site // He reduced=
 the load","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers on site // H=
e reduced the load","gaelle.njiofack@matech-cameroun.com","5","18-05-2025 1=
4:30:01","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0005048919","A=
kak-Nkozoa-MTN-IHS","","18-05-2025 14:16:10","18-05-2025 14:08:56","18-05-2=
025 16:02:56","Grid outage, Site went down because Gen stopped with ""high =
temp"" alarm // He added water and started Gen manualy","Fabrice Pouakam","=
Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, Site w=
ent down because Gen stopped with ""high temp"" alarm // He added water and=
 started Gen manualy","gaelle.njiofack@matech-cameroun.com","437","18-05-20=
25 14:16:10","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005048886","L=
abogenie","","18-05-2025 14:11:10","18-05-2025 12:15:47","18-05-2025 12:30:=
32","Grid outage.no space to deploy mobile gen // Grid restoration","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid outag=
e.no space to deploy mobile gen // Grid restoration","gaelle.njiofack@matec=
h-cameroun.com","6925","18-05-2025 14:11:10","MATECH CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0005048767","T=
radex-Nkomo","","18-05-2025 13:44:42","18-05-2025 13:40:35","18-05-2025 15:=
31:35","Grid outage. Gen ran until fuel shortage //Refueling done","Albran =
Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage. Gen =
ran until fuel shortage //Refueling done","gaelle.njiofack@matech-cameroun.=
com","248","18-05-2025 13:44:42","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005048722","A=
wae Ewonkan","","18-05-2025 13:31:20","18-05-2025 13:29:10","18-05-2025 13:=
53:10","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid Restored","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid R=
estored","gaelle.njiofack@matech-cameroun.com","131","18-05-2025 13:31:20",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0005048541","A=
fanoya","","18-05-2025 12:55:31","18-05-2025 12:47:57","18-05-2025 13:31:12=
","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, site went down due to Gen overload (17KVA, 240A) FM=
E IHS Felix Zambe is informed // Grid returned","gaelle.njiofack@matech-cam=
eroun.com","1667786","18-05-2025 12:55:31","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0005048533","A=
hala","","18-05-2025 12:53:52","18-05-2025 12:47:57","18-05-2025 13:31:12",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down due to Gen overload (17KVA, 240A) FME =
IHS Felix Zambe is informed // Grid returned","gaelle.njiofack@matech-camer=
oun.com","1667786","18-05-2025 12:53:52","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005048527","M=
eyo","IHS_YND_257, IHS_YND_313","18-05-2025 12:51:05","18-05-2025 12:47:57"=
,"18-05-2025 13:39:40","Grid outage, site went down due to Gen overload (17=
KVA, 240A) FME IHS Felix Zambe is informed // Grid returned","Hyemafo Gilda=
s","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, =
site went down due to Gen overload (17KVA, 240A) FME IHS Felix Zambe is inf=
ormed // Grid returned","gaelle.njiofack@matech-cameroun.com","189","18-05-=
2025 12:51:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005048524","MEHANDAN=
","","18-05-2025 12:49:44","18-05-2025 12:46:02","18-05-2025 13:10:10","Cas=
caded Incident from TTO5183762","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to PWC=
 ZTE malfunction // site stabilized Without intervention","system","1667894=
","18-05-2025 12:49:44","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005048515","O=
dza II OCM","IHS_YND_528","18-05-2025 12:47:23","18-05-2025 12:46:02","18-0=
5-2025 13:10:10","Grid outage, site went down due to PWC ZTE malfunction //=
 site stabilized Without intervention","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site went =
down due to PWC ZTE malfunction // site stabilized Without intervention","g=
aelle.njiofack@matech-cameroun.com","83","18-05-2025 12:47:23","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005048290","Sof=
avinc","","18-05-2025 12:21:35","18-05-2025 12:11:25","18-05-2025 12:29:02"=
,"Site went down due to insufficiency of rectifiers on site  // He reduced =
the load","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Site went down due to insufficiency of rectifiers on=
 site  // He reduced the load","loic.noumsi@matech-cameroun.com","611","18-=
05-2025 12:21:35","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005048220","N=
kolfon Cimencam","","18-05-2025 12:09:00","18-05-2025 12:02:53","18-05-2025=
 12:28:39","No power issue, Site impacted by Afanoya-II","Hyemafo Gildas","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue, Site impacted by Afanoya-II","gaelle.njiofack@ma=
tech-cameroun.com","368","18-05-2025 12:09:00","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005048140","C=
rf-Nsam","","18-05-2025 11:57:50","18-05-2025 11:51:43","18-05-2025 12:18:1=
8","Active // No power issue on site Ubaie =3D53.4V site on Grid The TX FME=
 Henri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue on site Ubaie =3D53.4V site on Grid The TX FME Henri =
(699949693) from Huawei is informed","gaelle.njiofack@matech-cameroun.com",=
"369","18-05-2025 11:57:50","MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0005048119","Nko=
abang MTN","","18-05-2025 11:53:35","18-05-2025 11:48:17","18-05-2025 12:37=
:26","Grid fluctuations, Site went down because gen failed to start due to =
grid bad voltage // He bypassed Grid and he manually started Gen","Mba Laza=
re Herve","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuations, Site went down because gen failed to start due =
to grid bad voltage // He bypassed Grid and he manually started Gen","loic.=
noumsi@matech-cameroun.com","318","18-05-2025 11:53:35","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005048082","B=
arriere","","18-05-2025 11:46:55","18-05-2025 11:39:47","18-05-2025 13:00:3=
9","Grid outage, Site went down due fuel shortage // Refuelling done","Hyem=
afo Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, =
Site went down due fuel shortage // Refuelling done","gaelle.njiofack@matec=
h-cameroun.com","429","18-05-2025 11:46:55","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0005048081","E=
kombitie","","18-05-2025 11:46:26","18-05-2025 11:40:20","18-05-2025 12:34:=
20","Grid fluctuation, Site went down because gen failed to start due to gr=
id bad voltage // He bypassed the Grid and site on Gen","Fabrice Pouakam","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, Site went down because gen fails to start due to grid bad v=
oltage // He bypassed the Grid and site on Gen","gaelle.njiofack@matech-cam=
eroun.com","368","18-05-2025 11:46:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005048046","MEHANDAN=
","","18-05-2025 11:41:35","18-05-2025 11:25:16","18-05-2025 12:04:48","Cas=
caded Incident from TTO5183155","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n start and stopped with high temp alarm // He added water and manually sta=
rted the gen","system","1665557","18-05-2025 11:41:35","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0005048030","M=
fou EPC","","18-05-2025 11:39:22","18-05-2025 11:31:13","18-05-2025 11:38:3=
1","Site went down due to plan work activity (Onion 694204295 was on site t=
o swap FH) // End of Work","Mba Lazare Herve","Installation Activity","Pass=
ive","Planned Activity","Installation Activity","Site went down due to plan=
 work activity (Onion 694204295 was on site to swap FH) // End of Work","ga=
elle.njiofack@matech-cameroun.com","490","18-05-2025 11:39:22","MATECH CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0005047986","C=
arington","","18-05-2025 11:33:34","18-05-2025 10:01:35","18-05-2025 11:38:=
30","No power issue site on grid with U=3D54v Notice that we have disjuncti=
on at OCM Equipements Armand Nguetsa from Huawei is informed","","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue site on grid with U=3D54v Notice that we have disjunction =
at OCM Equipements Armand Nguetsa from Huawei is informed","gaelle.njiofack=
@matech-cameroun.com","5520","18-05-2025 11:33:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0005047980","Mbedoumo=
u - Ekali","","18-05-2025 11:32:59","18-05-2025 11:25:16","18-05-2025 12:04=
:48","Cascaded Incident from TTO5183155","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen start and stopped with high temp alarm // He added water and man=
ually started the gen","system","1665560","18-05-2025 11:32:59","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0005047981","Odza II =
OCM","","18-05-2025 11:32:59","18-05-2025 11:25:16","18-05-2025 12:04:48","=
Cascaded Incident from TTO5183155","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // He added water and manually =
started the gen","system","1665562","18-05-2025 11:32:59","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005047959","Nko=
lnda","IHS_YND_343, IHS_YND_536, IHS_YND_723, IHS_YND_385, IHS_YND_528, IHS=
_YND_553, IHS_YND_527, IHS_YND_410, IHS_YND_595, IHS_EBO_015, IHS_YND_344, =
IHS_YND_411","18-05-2025 11:28:19","18-05-2025 11:25:16","18-05-2025 12:04:=
48","Grid outage, site went down because gen start and stopped with high te=
mp alarm // He added water and manually started the gen","Albran Byorel","E=
quipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Le=
vel Issue","Grid outage, site went down because gen start and stopped with =
high temp alarm // He added water and manually started the gen","loic.noums=
i@matech-cameroun.com","184","18-05-2025 11:28:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005047928","Nkol-Meb=
anga","","18-05-2025 11:23:33","18-05-2025 10:05:38","18-05-2025 15:31:10",=
"Cascaded Incident from TTO5182757","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active"," No power issue on site ,site on Gen =
with Ubaie =3D52.2V The Tx Technician from Huawei Gr=E9goire//654547479 is =
informed","system","1670248","18-05-2025 11:23:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005047927","Carrefou=
r Ayissi Ele","","18-05-2025 11:23:33","18-05-2025 10:05:38","18-05-2025 15=
:31:10","Cascaded Incident from TTO5182757","Parker Tchoup","Cascade Outage=
","Active","Cascade Active","Cascade Active"," No power issue on site ,site=
 on Gen with Ubaie =3D52.2V The Tx Technician from Huawei Gr=E9goire//65454=
7479 is informed","system","1670248","18-05-2025 11:23:33","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005047884","N=
koabang Ebolmedjock","","18-05-2025 11:10:31","18-05-2025 10:32:15","18-05-=
2025 11:46:25","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","gaelle.njiofack@ma=
tech-cameroun.com","2297","18-05-2025 11:10:31","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005047612","Saa=
","IHS_YND_810, IHS_YND_809","18-05-2025 10:07:13","18-05-2025 10:04:38","1=
8-05-2025 17:55:00"," No power issue on site ,site on Gen with Ubaie =3D52.=
2V The Tx Technician from Huawei Gr=E9goire//654547479 is informed","Parker=
 Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm"," No power issue on site ,site on Gen with Ubaie =3D52.=
2V The Tx Technician from Huawei Gr=E9goire//654547479 is informed","stepha=
ne.nkamwa@ihstowers.com","526","18-05-2025 10:07:13","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005047543","O=
LAMA","","18-05-2025 09:54:29","18-05-2025 09:46:59","18-05-2025 10:20:47",=
"Active // No power issue on site Ubaie =3D54.9V site on Grid. The TX FME H=
enri (699949693) from Huawei is informed","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (69=
9949693) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","20=
40","18-05-2025 09:54:29","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005047471","SAA=
 Entrance","","18-05-2025 09:39:45","18-05-2025 09:32:33","18-05-2025 10:03=
:28","Site went down due to plan work activity (SS MATECH PARKER WAS ON SIT=
E to swap of RCP) // End of work","Parker Tchoup","Installation Activity","=
Passive","Planned Activity","Installation Activity","Site went down due to =
plan work activity (SS MATECH PARKER WAS ON SITE to swap of RCP) // End of =
work","loic.noumsi@matech-cameroun.com","433","18-05-2025 09:39:45","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005047447","E=
ssomba","","18-05-2025 09:35:27","18-05-2025 09:32:20","18-05-2025 10:46:39=
","Site went down because PWC overload // Site stabilised,","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Site went down because PWC overload // Site stabilised,","gaelle.njiofack@=
matech-cameroun.com","189","18-05-2025 09:35:27","MATECH CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0005047362","A=
bang","","18-05-2025 09:16:26","18-05-2025 03:40:16","18-05-2025 04:19:16",=
"Active//No power issue site on Grid with U=3D55.5V ,The FME TX Henri (6911=
45055) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue site on Grid with U=3D55.5V ,The FME TX Henri (691145055) from H=
uawei is informed","gaelle.njiofack@matech-cameroun.com","20171","18-05-202=
5 09:16:26","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005047286","Sof=
avinc","","18-05-2025 09:04:27","18-05-2025 09:00:23","18-05-2025 09:51:44"=
,"	Site went down because Gen failed to start due to card Ge faulty // He r=
eseted it and started Gen manually","MINKA NICOLAS","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","	Site went down because Gen failed=
 to start due to card Ge faulty // He reseted it and started Gen manually",=
"loic.noumsi@matech-cameroun.com","245","18-05-2025 09:04:27","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005047225","Odz=
a petit marche new","","18-05-2025 08:55:18","18-05-2025 08:50:09","18-05-2=
025 09:51:54","Site went down Gen failed to start due to Grid bad voltage(l=
ack of 01 phase on site)// He did a bridge on the Good phase","Albran Byore=
l","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Site went down Gen failed to start due to Grid bad voltage(lack of 02 pha=
ses on site)// He did a bridge on the Good phase","loic.noumsi@matech-camer=
oun.com","310","18-05-2025 08:55:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0005047196","Mendong =
vallee","","18-05-2025 08:48:38","18-05-2025 08:36:47","18-05-2025 10:19:31=
","Cascaded Incident from TTO5182276","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuations, site went down =
due to bad Eneo voltage // He bypassed Grid and put site on Gen","system","=
1668418","18-05-2025 08:48:38","MATECH CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0005047167","Men=
dong Maeture","IHS_YND_692","18-05-2025 08:41:04","18-05-2025 08:36:47","18=
-05-2025 10:21:42","Grid fluctuations, site went down due to bad Eneo volta=
ge // He bypassed Grid and put site on Gen","Hyemafo Gildas","Grid Supply",=
"Passive","Grid","National Grid - Poles Failed","Grid fluctuations, site we=
nt down due to bad Eneo voltage // He bypassed Grid and put site on Gen","l=
oic.noumsi@matech-cameroun.com","257","18-05-2025 08:41:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0005047077","ARMP",""=
,"18-05-2025 08:16:23","18-05-2025 08:10:17","18-05-2025 08:51:39","Cascade=
d Incident from TTO5182158","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","site went down due to 02/04 rectifiers faulty // replac=
ement of 02 rectifiers ","system","1669984","18-05-2025 08:16:23","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0005047076","Bastos B=
ir","","18-05-2025 08:16:22","18-05-2025 08:10:17","18-05-2025 08:51:39","C=
ascaded Incident from TTO5182158","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to 02/04 rectifie=
rs faulty // replacement of 02 rectifiers ","system","1669984","18-05-2025 =
08:16:23","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0005047066","D=
ragage","IHS_YND_704, IHS_YND_208","18-05-2025 08:13:41","18-05-2025 08:10:=
17","18-05-2025 08:51:39","site went down due to 02/04 rectifiers faulty //=
 replacement of 02 rectifiers ","Mboua Thierry","Equipment Repair","Passive=
","Rectifier","Rectifier Module","site went down due to 02/04 rectifiers fa=
ulty // replacement of 02 rectifiers ","gaelle.njiofack@matech-cameroun.com=
","205","18-05-2025 08:13:41","MATECH CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0005046912","A=
ngongo","","18-05-2025 07:43:40","18-05-2025 06:20:26","18-05-2025 08:52:45=
","Site went down because Gen started and stopped due to the dirt in the ta=
nk // He purged it and restarted Gen manually","Fanda Brice","Fuel Outage (=
Probable)","Passive","Diesel","Fuel Line Issue","Site went down because Gen=
 started and stopped due to the dirt in the tank // He purged it and restar=
ted Gen manually","gaelle.njiofack@matech-cameroun.com","4995","18-05-2025 =
07:43:40","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005046904","Nko=
l-Mebanga","","18-05-2025 07:42:00","18-05-2025 07:32:53","18-05-2025 07:42=
:19","Solar only site, // solar returned","Parker Tchoup","Equipment Repair=
","Passive","Solar","Solar Panel Issue","Solar only site, // solar returned=
","loic.noumsi@matech-cameroun.com","547","18-05-2025 07:42:00","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0005046800","Odza II =
OCM","","18-05-2025 07:25:27","18-05-2025 06:48:27","18-05-2025 07:50:55","=
Cascaded Incident from TTO5181677","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","	Grid fluctuation, site went down b=
ecause Gen failed to start due to grid bad voltage No Rcp// He bypassed gri=
d and started Gen manually","system","1667735","18-05-2025 07:25:27","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005046646","MEHANDAN=
","","18-05-2025 06:54:56","18-05-2025 06:48:27","18-05-2025 07:50:55","Cas=
caded Incident from TTO5181677","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid fluctuation, site went down beca=
use Gen failed to start due to grid bad voltage No Rcp// He bypassed grid a=
nd started Gen manually","system","1667732","18-05-2025 06:54:56","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0005046645","Mbedoumo=
u - Ekali","","18-05-2025 06:54:56","18-05-2025 06:48:27","18-05-2025 07:50=
:55","Cascaded Incident from TTO5181677","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","	Grid fluctuation, site went =
down because Gen failed to start due to grid bad voltage No Rcp// He bypass=
ed grid and started Gen manually","system","1667732","18-05-2025 06:54:56",=
"MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005046635","Nko=
lnda","IHS_YND_343, IHS_YND_536, IHS_YND_723, IHS_YND_385, IHS_YND_528, IHS=
_YND_527, IHS_YND_410, IHS_YND_595, IHS_EBO_015, IHS_YND_344, IHS_YND_411",=
"18-05-2025 06:51:35","18-05-2025 06:48:27","18-05-2025 07:50:55","Grid flu=
ctuation, site went down because Gen failed to start due to grid bad voltag=
e No Rcp// He bypassed grid and started Gen manually","Albran Byorel","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","	Grid =
fluctuation, site went down because Gen failed to start due to grid bad vol=
tage No Rcp// He bypassed grid and started Gen manually","loic.noumsi@matec=
h-cameroun.com","189","18-05-2025 06:51:35","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005046441","Sof=
avinc","","18-05-2025 05:58:28","18-05-2025 05:56:17","18-05-2025 07:02:40"=
,"Site went down because Gen failed to start due to card Ge faulty // He re=
seted it and started Gen manually","MINKA NICOLAS","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Site went down because Gen failed t=
o start due to card Ge faulty // He reseted it and started Gen manually","g=
erard.tchangoue@matech-cameroun.com","132","18-05-2025 05:58:28","MATECH CM=
R"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005046111","O=
LAMA","","18-05-2025 03:55:44","18-05-2025 03:48:38","18-05-2025 05:46:33",=
"Active // No power issue on site Ubaie =3D54.9V site on Grid. The TX FME H=
enri (699949693) from Huawei is informed","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (69=
9949693) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","427","=
18-05-2025 03:55:44","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005045697","Jou=
vence Mbenda","","18-05-2025 01:08:13","18-05-2025 01:05:08","18-05-2025 05=
:20:32","Grid fluctuation,site went down because Gen failed to start due to=
 grid bad voltage(lack of 1 phase)//He made a bridge with the Good phases",=
"Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid fluctuation,site went down because Gen failed to start=
 due to grid bad voltage(lack of 1 phase)//He made a bridge with the Good p=
hases","gerard.tchangoue@matech-cameroun.com","186","18-05-2025 01:08:13","=
MATECH CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0005045566","Men=
dong Maeture","","18-05-2025 00:40:21","18-05-2025 00:34:09","18-05-2025 06=
:24:16","Grid fluctuations, site went down due to bad Eneo voltage // He by=
passed Grid and put site on Gen","Hyemafo Gildas","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Grid fluctuations, site we=
nt down due to bad Eneo voltage // He bypassed Grid and put site on Gen","g=
erard.tchangoue@matech-cameroun.com","372","18-05-2025 00:40:21","MATECH CM=
R"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005045526","Nko=
g-Edzen","","18-05-2025 00:33:03","18-05-2025 00:28:55","18-05-2025 05:00:3=
9","Site went Down due  to  faulty priming pump // priming pump temporarily=
 replace","Parker Tchoup","Fuel Outage (Probable)","Passive","ACDG Gen","AC=
DG - Injector Pump","Site went Down due  to  faulty priming pump // priming=
 pump temporarily replace","gerard.tchangoue@matech-cameroun.com","249","18=
-05-2025 00:33:03","MATECH CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0005045464","C=
arington","","18-05-2025 00:20:08","18-05-2025 00:14:59","18-05-2025 10:00:=
19","Grid only, lessor refuses to deploy Gen // Grid return and power reset=
 done but site remain down","","Grid Supply","Passive","Grid","National Gri=
d - Grid Outage Issue","	Grid only, lessor refuses to deploy Gen // Grid re=
turn and power reset done but site remain down ","edwige.kapawo@matech-came=
roun.com","310","18-05-2025 00:20:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0005045456","Nkolanga=
a","","18-05-2025 00:15:46","18-05-2025 00:07:40","18-05-2025 03:39:26","Ca=
scaded Incident from TTO5180370","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","FME Herve report that site vandali=
zed // it restored power","system","1677717","18-05-2025 00:15:46","MATECH =
CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005045455","Nko=
ulou Carriere carrefourt","","18-05-2025 00:15:29","18-05-2025 00:07:40","1=
8-05-2025 03:39:26","Site impacted by Abang","Mba Lazare Herve","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","FME Herve report that =
site vandalized // it restored power","gerard.tchangoue@matech-cameroun.com=
","1677717","18-05-2025 00:15:29","MATECH CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0005045452","A=
bang","IHS_YND_794, IHS_YND_289","18-05-2025 00:14:51","18-05-2025 00:07:40=
","18-05-2025 03:39:26","FME Herve report that site vandalized // it restor=
ed power","Mba Lazare Herve","Site Intrusion","Intrusion On Site","Intrusio=
n On Site","Intrusion - Vandalism/Sabotage","FME Herve report that site van=
dalized // it restored power","edwige.kapawo@matech-cameroun.com","432","18=
-05-2025 00:14:51","MATECH CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0005045402","M=
obil-Kondengui","","18-05-2025 00:02:05","17-05-2025 23:09:35","18-05-2025 =
06:54:59","fme report that Grid outage, No space to deploy a MGE // Grid re=
turn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"fme report that Grid outage, No space to deploy a MGE // Grid return","lu=
divine.ngamaleu@ihstowers.com","3150","18-05-2025 00:02:05","MATECH CMR"
"Closed Complete","Site Down","T1591","IHS_YND_172","NOCINC0005045151","Tra=
dex-Nkomo","","17-05-2025 23:11:00","17-05-2025 23:08:48","17-05-2025 23:24=
:14","Site went down due to disjunction of Cb(63A) in GE // He rearmed Cb(6=
3A), site on Gen)","Albran Byorel","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Load Breaker","Site went down due to disjunction of Cb(63A) in GE /=
/ He rearmed Cb(63A), site on Gen)","gerard.tchangoue@matech-cameroun.com",=
"132","17-05-2025 23:11:00","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005045147","Mam=
ch Building","","17-05-2025 23:09:56","17-05-2025 23:06:49","18-05-2025 00:=
32:51","Grid fluctuation, Site went down because Gen failed to start due to=
 Grid bad voltage No rcp//  He bypassed Grid and started Gen manually","Mbo=
ua Thierry","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation, Site went down because Gen failed to start due=
 to Grid bad voltage No rcp//  He bypassed Grid and started Gen manually","=
gerard.tchangoue@matech-cameroun.com","188","17-05-2025 23:09:56","MATECH C=
MR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005045117","Men=
dong NB","","17-05-2025 23:01:40","17-05-2025 22:58:28","17-05-2025 23:07:0=
2","Grid Only, No space to deploy // Grid return	","","Grid Supply","Passiv=
e","Grid","National Grid - Grid Outage Issue","Grid Only, No space to deplo=
y // Grid return	","edwige.kapawo@matech-cameroun.com","193","17-05-2025 23=
:01:40","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005045114","TSI=
NGA VILLAGE 2","","17-05-2025 23:00:48","17-05-2025 22:56:34","18-05-2025 0=
0:24:04","Site went due to disfunction of PWC controller's causing by  high=
 temp in PWC because CB of extractor tripped// He rearmed CB of extractor",=
"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","Site went due to disfunction of PWC controller's causing by  =
high temp in PWC because CB of extractor tripped// He rearmed CB of extract=
or","edwige.kapawo@matech-cameroun.com","255","17-05-2025 23:00:48","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005045072","A=
WAE OCM","","17-05-2025 22:51:54","17-05-2025 22:48:44","17-05-2025 23:45:4=
4","Grid outage site went down because Gen failed to start due PWC ZTE dysf=
onctionned // He reset the PWC and Gen manually started","Mba Lazare Herve"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage site went down because Gen failed to start due PWC ZTE dysfonctio=
nned // He reset the PWC and Gen manually started","edwige.kapawo@matech-ca=
meroun.com","191","17-05-2025 22:51:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0005044973","Afanoya"=
,"","17-05-2025 22:38:01","17-05-2025 20:53:21","18-05-2025 09:01:35","Casc=
aded Incident from TTO5179228","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to disjunction of c=
ircuit breaker (100A) in the ocm BTS / CB rearmed","system","1674713","17-0=
5-2025 22:38:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005044972","Ahala","=
","17-05-2025 22:38:01","17-05-2025 20:53:21","18-05-2025 09:01:35","Cascad=
ed Incident from TTO5179228","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to disjunction of cir=
cuit breaker (100A) in the ocm BTS / CB rearmed","system","1674713","17-05-=
2025 22:38:01","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005044955","S=
atcom","","17-05-2025 22:34:29","17-05-2025 22:19:12","17-05-2025 22:42:15"=
,"No power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144=
412) of huawei is informed","Delor Telezing","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144412) of huawei is in=
formed","ludivine.ngamaleu@ihstowers.com","918","17-05-2025 22:34:29","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005044627","A=
wae Ewonkan","","17-05-2025 21:47:14","17-05-2025 21:45:04","17-05-2025 21:=
50:04","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid Restored","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid R=
estored","edwige.kapawo@matech-cameroun.com","131","17-05-2025 21:47:14","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0005044585","Ngoung",=
"","17-05-2025 21:46:14","17-05-2025 18:26:11","17-05-2025 18:30:20","Activ=
e//No power issue, site is on Grid with Ubaie=3D50 V The tx FME Yannick Mba=
h (670610135) from Huawei is informed","Kemeni Franklin","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue, site is on Grid with Ubaie=3D50 V The tx FME Yannick Mbah=
 (670610135) from Huawei is informed","system","12003","17-05-2025 21:46:14=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0005044580","Mamb",""=
,"17-05-2025 21:46:13","17-05-2025 18:26:11","17-05-2025 18:30:20","Active/=
/No power issue, site is on Grid with Ubaie=3D50 V The tx FME Yannick Mbah =
(670610135) from Huawei is inform","Kemeni Franklin","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue, site is on Grid with Ubaie=3D50 V The tx FME Yannick Mbah (67=
0610135) from Huawei is inform","system","12002","17-05-2025 21:46:13","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_416","NOCINC0005044579","Ngwopi B=
oga","","17-05-2025 21:46:12","17-05-2025 18:26:11","17-05-2025 18:30:20","=
Cascaded Incident from TTO5178098 - Cascade Removed From TTO5178098","Kemen=
i Franklin","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue, site is on Grid with Ubaie=
=3D50 V The tx FME Yannick Mbah (670610135) from Huawei is inform","system"=
,"12001","17-05-2025 21:46:12","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005044463","M=
eyo","IHS_YND_257, IHS_YND_313","17-05-2025 21:30:34","17-05-2025 20:53:21"=
,"18-05-2025 09:01:35","Site went down due to disjunction of circuit breake=
r (100A) in the ocm BTS / CB rearmed","Hyemafo Gildas","Equipment Repair","=
Passive","Control Panel","Circuit Breaker Tripped","Site went down due to d=
isjunction of circuit breaker (100A) in the ocm BTS / CB rearmed","edwige.k=
apawo@matech-cameroun.com","2234","17-05-2025 21:30:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0005044459","Afanoya"=
,"","17-05-2025 21:29:59","17-05-2025 19:28:53","17-05-2025 20:21:10","Casc=
aded Incident from TTO5179209","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down due to Gen =
overload (17KVA, 240A) // Grid return","system","1672614","17-05-2025 21:29=
:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005044458","Ahala","=
","17-05-2025 21:29:59","17-05-2025 19:28:53","17-05-2025 20:21:10","Cascad=
ed Incident from TTO5179209","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage site went down due to Gen ov=
erload (17KVA, 240A) // Grid return","system","1672613","17-05-2025 21:29:5=
9","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0005044434","Bar=
riere IHS","","17-05-2025 21:25:21","17-05-2025 21:19:59","17-05-2025 23:59=
:51","Grid outage, Site went down because Gen started and stopped due to Ge=
n overload(20kva, 265A) // He reduced load and Start Gen manually","Hyemafo=
 Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage, Site went down because Gen started and stopped due to Gen overload(20=
kva, 265A) // He reduced load and Start Gen manually","franck.nkomot@matech=
-cameroun.com","572","17-05-2025 21:25:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0005044299","Nkoa Ayo=
s","","17-05-2025 21:06:33","17-05-2025 20:56:59","17-05-2025 23:32:52","Ca=
scaded Incident from TTO5179035","MINKA NICOLAS","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuation , Site went down due=
 to grid bad voltage //He bypassed the Grid, site on GEN","system","1674445=
","17-05-2025 21:06:33","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0005044293","G=
SO","IHS_YND_067","17-05-2025 21:05:47","17-05-2025 20:56:59","17-05-2025 2=
3:42:58","Grid fluctuation , Site went down due to grid bad voltage //He by=
passed the Grid, site on GEN","MINKA NICOLAS","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid fluctuation , Site went d=
own due to grid bad voltage //He bypassed the Grid, site on GEN","edwige.ka=
pawo@matech-cameroun.com","529","17-05-2025 21:05:47","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005044118","M=
essassi 2","","17-05-2025 20:36:33","17-05-2025 20:27:44","17-05-2025 23:00=
:14","(very unstable) Grid outage, Site went down due to 02/08 rectifiers i=
ssue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","(very unstable) Grid outage, Site went down du=
e to 02/08 rectifiers issue // Grid stabilised","kouoh.jean@ihstowers.com",=
"531","17-05-2025 20:36:33","MATECH CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0005044110","Awa=
e Escalier","","17-05-2025 20:35:53","17-05-2025 20:32:46","17-05-2025 21:5=
6:46","Grid outage, Site went down because Gen failed to start due to alarm=
""low oil pressure""//He added oil and Gen started","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Oil Pressure Sensor Faulty","Grid =
outage, Site went down because Gen failed to start due to alarm""low oil pr=
essure""//He added oil and Gen started","franck.nkomot@matech-cameroun.com"=
,"231","17-05-2025 20:35:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0005044102","Bastos B=
ir","","17-05-2025 20:34:42","17-05-2025 20:25:07","17-05-2025 22:43:07","C=
ascaded Incident from TTO5178791","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to insufficiency =
of rectifiers(Bernard IHS confirm) // site stabilized","system","1676309","=
17-05-2025 20:34:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0005044103","ARMP",""=
,"17-05-2025 20:34:42","17-05-2025 20:25:07","17-05-2025 22:43:07","Cascade=
d Incident from TTO5178791","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","site went down due to insufficiency of rectifiers(Berna=
rd IHS confirm) // site stabilized","system","1676310","17-05-2025 20:34:42=
","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0005044084","D=
ragage","IHS_YND_704, IHS_YND_208","17-05-2025 20:33:14","17-05-2025 20:23:=
07","18-05-2025 00:08:21","site went down due to insufficiency of rectifier=
s(Bernard IHS confirm) // site stabilized","Mboua Thierry","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","site went down due to insuffic=
iency of rectifiers(Bernard IHS confirm) // site stabilized","edwige.kapawo=
@matech-cameroun.com","7321","17-05-2025 20:33:14","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0005044071","N=
kolo II New","","17-05-2025 20:30:18","17-05-2025 20:18:52","17-05-2025 20:=
31:51","No power issue, Site impacted by Mimboman-Don-Bosco","Mba Lazare He=
rve","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","No power issue, Site impacted by Mimboman-Don-Bosc=
o","edwige.kapawo@matech-cameroun.com","687","17-05-2025 20:30:18","MATECH =
CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0005043901","Mey=
o","IHS_YND_257, IHS_YND_313","17-05-2025 20:00:31","17-05-2025 19:28:53","=
17-05-2025 20:28:25","Grid outage site went down due to Gen overload (17KVA=
, 240A) // Grid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Grid outage site went down due to Gen overload (17=
KVA, 240A) // Grid return","landry.etame@ihstowers.com","7165","17-05-2025 =
20:00:31","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0005043513","N=
kolbong","","17-05-2025 18:50:21","17-05-2025 18:00:17","17-05-2025 20:46:4=
0","Site went down because rectifier disfunctionning // He reset it: Site o=
n grid","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down because rectifier disfunctionning // He reset it:=
 Site on grid","edwige.kapawo@matech-cameroun.com","3005","17-05-2025 18:50=
:21","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005043492","E=
mana lycee 2","IHS_YND_274","17-05-2025 18:45:45","17-05-2025 18:34:25","17=
-05-2025 18:50:03","Grid outage , site went down before Gen failed to start=
ed due to poor battery backup //gen automaticaly started.","Fabrice Pouakam=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low=
","Grid outage , site went down before Gen failed to started due to poor ba=
ttery backup //gen automaticaly started.","edwige.kapawo@matech-cameroun.co=
m","682","17-05-2025 18:45:45","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0005043466","Men=
dong vallee","","17-05-2025 18:40:59","17-05-2025 18:20:51","18-05-2025 01:=
22:31","Grid outage site went down because Gen overload (20KVA; 300A) IHS F=
=E9lix Zamb=E9 is informed and confirmed // Grid returned","Fanda Brice","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site w=
ent down because Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed=
 and confirmed // Grid returned","franck.nkomot@matech-cameroun.com","1209"=
,"17-05-2025 18:40:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0005043178","Manguier=
","","17-05-2025 17:59:52","17-05-2025 15:29:19","17-05-2025 16:35:19","Cas=
caded Incident from TTO5176771","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue on site ,site on=
 Grid with Ubaie=3D53.6 V The Tx FME Symphorien (650257151) from Huawei is =
informed","system","1672448","17-05-2025 17:59:52","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0005043126","Car=
refour Simbock","","17-05-2025 17:50:41","17-05-2025 17:47:19","17-05-2025 =
18:09:55","Grid outage, Site went down before Gen start due to poor backup =
// Gen start automatically","Hyemafo Gildas","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen start automatically","franck.nkom=
ot@matech-cameroun.com","202","17-05-2025 17:50:41","MATECH CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0005042990","T=
radex-Nkomo","","17-05-2025 17:27:22","17-05-2025 17:19:13","17-05-2025 19:=
32:48","Site went down due to disjunction of Cb(63A) in GE // He rearmed Cb=
(63A), site on Gen","Albran Byorel","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Load Breaker","Site went down due to disjunction of Cb(63A) in GE =
// He rearmed Cb(63A), site on Gen","edwige.kapawo@matech-cameroun.com","49=
0","17-05-2025 17:27:22","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005042784","MBA=
LNGONG LYCEE","","17-05-2025 16:51:41","17-05-2025 16:26:21","17-05-2025 17=
:02:49","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down be=
cause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informe=
d and confirmed // Grid returned","franck.nkomot@matech-cameroun.com","1521=
","17-05-2025 16:51:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0005042770","Ahala","=
","17-05-2025 16:50:15","17-05-2025 16:44:54","17-05-2025 18:43:58","Cascad=
ed Incident from TTO5177268","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down because Gen overload // G=
rid return","system","1674111","17-05-2025 16:50:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0005042743","Nkolfon =
Cimencam","","17-05-2025 16:47:02","17-05-2025 16:44:54","17-05-2025 18:43:=
58","Cascaded Incident from TTO5177268","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because Gen ov=
erload // Grid return","system","1674111","17-05-2025 16:47:02","MATECH CMR=
"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0005042737","M=
eyo","IHS_YND_257, IHS_YND_762","17-05-2025 16:46:00","17-05-2025 16:44:54"=
,"17-05-2025 18:43:58","Site went down because Gen overload // Grid return"=
,"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Site went down because Gen overload // Grid return","edwige.kapawo@matech=
-cameroun.com","67","17-05-2025 16:46:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005042736","Nkol-Meb=
anga","","17-05-2025 16:45:44","17-05-2025 16:37:01","17-05-2025 22:25:31",=
"Cascaded Incident from TTO5177258","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because 01/03 recti=
fier disfunctionning SS BATEU Felix IHS is informed // He reset it: Site on=
 grid","system","1661269","17-05-2025 16:45:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005042735","Carrefou=
r Ayissi Ele","","17-05-2025 16:45:44","17-05-2025 16:37:01","17-05-2025 22=
:25:31","Cascaded Incident from TTO5177258","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down because 01/=
03 rectifier disfunctionning SS BATEU Felix IHS is informed // He reset it:=
 Site on grid","system","1661268","17-05-2025 16:45:44","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005042703","Men=
dong NB","","17-05-2025 16:37:58","17-05-2025 16:24:46","17-05-2025 17:34:2=
5","Grid Only, No space to deploy // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid Only, No space to deploy=
 // Grid return","franck.nkomot@matech-cameroun.com","792","17-05-2025 16:3=
7:58","MATECH CMR"
"Closed Complete","Site Down","T0289","IHS_YND_106","NOCINC0005042697","Mfa=
ndena","","17-05-2025 16:36:24","17-05-2025 16:31:18","17-05-2025 19:13:08"=
,"Active: no power issue, site is on grid with Ubaie=3D54.6V, Symphorien (6=
50257151) from Huawei working on site","Delor Telezing","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active:=
 no power issue, site is on grid with Ubaie=3D54.6V, Symphorien (650257151)=
 from Huawei working on site","franck.nkomot@matech-cameroun.com","307","17=
-05-2025 16:36:24","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0005042685","O=
mnisport 3","","17-05-2025 16:33:26","17-05-2025 16:30:18","18-05-2025 15:5=
7:18","Site went down due to PWC Overloaded (12K, 250A) //site stabilised",=
"Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Site went down due to PWC Overloaded (12K, 250A) //site stabilised","edwig=
e.kapawo@matech-cameroun.com","188","17-05-2025 16:33:26","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005042607","E=
vodoula OCM","","17-05-2025 16:18:22","17-05-2025 16:10:13","17-05-2025 16:=
54:01","Grid outage, site went down because gen failed to start with alarm =
undervoltage // He reset gen card and gen manually started","TIENTCHEU NZET=
CHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Under Voltage",=
"Grid outage, site went down because gen failed to start with alarm undervo=
ltage // He reset gen card and gen manually started","edwige.kapawo@matech-=
cameroun.com","490","17-05-2025 16:18:22","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005042516","N=
yom OCM","","17-05-2025 16:03:05","17-05-2025 15:57:53","17-05-2025 16:19:1=
2"," Grid outage gen failed to start due to battery GE discharged causing b=
y static charger faulty//Grid return","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Generator Battery"," Grid outage gen failed to=
 start due to battery GE discharged causing by static charger faulty//Grid =
return","edwige.kapawo@matech-cameroun.com","314","17-05-2025 16:03:05","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0005042500","S=
apeur Mimboman","","17-05-2025 16:00:39","17-05-2025 15:56:26","17-05-2025 =
17:23:26","Grid outage site went down due to gen overload(22 kva,318 A)//We=
 reduce load and gen manually started","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 gen overload(22 kva,318 A)//We reduce load and gen manually started","edwi=
ge.kapawo@matech-cameroun.com","255","17-05-2025 16:00:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0005042482","Montee-J=
ouvence-II","","17-05-2025 15:56:06","17-05-2025 15:34:49","17-05-2025 15:5=
2:09","Cascaded Incident from TTO5176795","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid Outage // Grid restore=
d","system","1672123","17-05-2025 15:56:06","MATECH CMR"
"Closed Complete","Site Down","T0573","IHS_YND_387","NOCINC0005042407","Tal=
la Monatele","IHS_EDA_049, IHS_YND_532","17-05-2025 15:48:36","17-05-2025 1=
5:45:29","17-05-2025 19:07:17","Active: no power issue, site is on grid wit=
h Ubaie=3D54.9V, Gregoir (654547479) from Huawei working on site","Parker T=
choup","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active: no power issue, site is on grid with Ubaie=3D54.=
9V, Gregoir (654547479) from Huawei working on site","franck.nkomot@matech-=
cameroun.com","188","17-05-2025 15:48:36","MATECH CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0005042397","NKO=
LOSSAN OKOK","","17-05-2025 15:47:45","17-05-2025 15:45:29","17-05-2025 19:=
05:53","Active: no power issue, site is on grid with Ubaie=3D54.9V, Gregoir=
 (654547479) from Huawei working on site","Parker Tchoup","Cascade Outage",=
"Active","Cascade Active","Cascade Active","Active: no power issue, site is=
 on grid with Ubaie=3D54.9V, Gregoir (654547479) from Huawei working on sit=
e","franck.nkomot@matech-cameroun.com","1671499","17-05-2025 15:47:45","MAT=
ECH CMR"
"Cancelled","Warning","CTR_251","IHS_YND_136","NOCINC0005042393","Vallee-Ba=
stos OCM","","17-05-2025 15:47:15","","","","","","","","","","kouoh.jean@i=
hstowers.com","428","17-05-2025 15:47:15","MATECH CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0005042394","V=
allee-Bastos OCM","","17-05-2025 15:47:15","17-05-2025 15:40:08","18-05-202=
5 09:02:31","Grid only, No space to deploy, // Grid return and Power reset =
done","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Grid only, No space to deploy, // Grid return and Power reset done","edwi=
ge.kapawo@matech-cameroun.com","429","17-05-2025 15:47:15","MATECH CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0005042391","Nko=
lo II New","","17-05-2025 15:46:36","17-05-2025 15:37:38","17-05-2025 16:37=
:38","Site impacted  by MIMBOMAN4","Mba Lazare Herve","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid fluctuations, site went dow=
n because Gen failed to start due to grid bad voltage // He bypassed Grid a=
nd started Gen manually","franck.nkomot@matech-cameroun.com","1671959","17-=
05-2025 15:46:36","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005042385","Men=
dong Plateau","","17-05-2025 15:46:02","17-05-2025 15:42:56","17-05-2025 16=
:00:51","Grid Outage // Grid return (investigation Ongoing)","Hyemafo Gilda=
s","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 Outage // Grid return (investigation Ongoing)","franck.nkomot@matech-camer=
oun.com","187","17-05-2025 15:46:02","MATECH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0005042380","Mvo=
g-Ada_OCM","","17-05-2025 15:44:59","17-05-2025 15:34:43","17-05-2025 16:21=
:33","Grid only on site, No space on site to deploy MGE // Grid return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid on=
ly on site, No space on site to deploy MGE // Grid return","franck.nkomot@m=
atech-cameroun.com","617","17-05-2025 15:44:59","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0005042379","M=
vog-Ebanda","","17-05-2025 15:44:54","17-05-2025 15:41:34","17-05-2025 17:1=
0:31","Grid outage, Site went down because Gen started and stopped due to G=
en overload// Grid return","Siligap Boris","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Grid outage, Site went down because Gen started =
and stopped due to Gen overload// Grid return","kouoh.jean@ihstowers.com","=
201","17-05-2025 15:44:54","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005042372","Men=
dong3","","17-05-2025 15:44:01","17-05-2025 15:40:49","17-05-2025 22:33:10"=
,"Grid only site no space to deploy MDE // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid only site no space=
 to deploy MDE // Grid return","franck.nkomot@matech-cameroun.com","193","1=
7-05-2025 15:44:01","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005042370","Nko=
abang2","","17-05-2025 15:43:14","17-05-2025 15:35:04","17-05-2025 16:23:04=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","franck.n=
komot@matech-cameroun.com","492","17-05-2025 15:43:14","MATECH CMR"
"Closed Complete","Site Down","T3150","IHS_YND_214","NOCINC0005042367","Nko=
lmesseng-II","","17-05-2025 15:42:32","17-05-2025 15:35:24","17-05-2025 16:=
36:24","Grid outage, Gen stopped with alarm Under voltage // Gen card reset=
 and site on Gen","Siligap Boris","Equipment Repair","Passive","ACDG Gen","=
ACDG - Under Voltage","Grid outage, Gen stopped with alarm Under voltage //=
 Gen card reset and site on Gen","franck.nkomot@matech-cameroun.com","428",=
"17-05-2025 15:42:32","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005042364","Mim=
boman4","IHS_YND_709","17-05-2025 15:41:47","17-05-2025 15:37:38","17-05-20=
25 16:37:38","Grid fluctuations, site went down because Gen failed to start=
 due to grid bad voltage // He bypassed Grid and started Gen manually","Mba=
 Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuations, site went down because Gen failed to start=
 due to grid bad voltage // He bypassed Grid and started Gen manually","fra=
nck.nkomot@matech-cameroun.com","250","17-05-2025 15:41:47","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005042360","Ako=
k Ndoe Yde","","17-05-2025 15:41:13","17-05-2025 15:35:05","17-05-2025 16:0=
1:29","Grid outage site went down due to poor Battery backup// Grid return"=
,"Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Battery Low","Grid outage site went down due to poor Battery backup// =
Grid return","franck.nkomot@matech-cameroun.com","369","17-05-2025 15:41:13=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0005042355","Accacia =
New","","17-05-2025 15:40:36","17-05-2025 15:34:49","17-05-2025 15:52:09","=
Cascaded Incident from TTO5176795","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid Outage // Grid restored","system","1672124"=
,"17-05-2025 15:40:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0005042356","Damas","=
","17-05-2025 15:40:36","17-05-2025 15:34:49","17-05-2025 15:52:09","Cascad=
ed Incident from TTO5176795","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid Outage // Grid restored","system","1=
672123","17-05-2025 15:40:36","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005042347","T=
amtam Weekend","IHS_YND_562, IHS_YND_166, IHS_YND_518","17-05-2025 15:38:59=
","17-05-2025 15:33:49","17-05-2025 16:08:32","Grid Outage // Grid restored=
","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Grid Out=
age Issue","Grid Outage // Grid restored","edwige.kapawo@matech-cameroun.co=
m","311","17-05-2025 15:38:59","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005042337","E=
MANA BILICK CITY","IHS_YND_279","17-05-2025 15:37:46","17-05-2025 15:32:32"=
,"17-05-2025 18:41:32","Grid outage, site down because site behaves as Grid=
 only site (no Gen) //Grid return","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage, site down becaus=
e site behaves as Grid only site (no Gen) //Grid return","edwige.kapawo@mat=
ech-cameroun.com","316","17-05-2025 15:37:46","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005042332","M=
essassi okolo","","17-05-2025 15:36:23","17-05-2025 15:32:32","18-05-2025 0=
0:26:20","ACTIVE//No power issue on site Ubaie=3D54.5V, site on Gen The TX =
Fme Synphorien 691316854 of Huawei is informed","Fabrice Pouakam","Cascade =
Outage","Passive","Cascade Passive","Cascade Passive","ACTIVE//No power iss=
ue on site Ubaie=3D54.5V, site on Gen The TX Fme Synphorien 691316854 of Hu=
awei is informed","edwige.kapawo@matech-cameroun.com","17913","17-05-2025 1=
5:36:23","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0005042331","Sof=
avinc","","17-05-2025 15:36:18","17-05-2025 15:32:57","17-05-2025 15:36:57"=
,"Site went down because rectifiers disfunctionning// Site stabilized","MIN=
KA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down because rectifiers disfunctionning// Site stabilized","franck.=
nkomot@matech-cameroun.com","202","17-05-2025 15:36:18","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005042327","Ron=
d Point Express1114","","17-05-2025 15:35:23","17-05-2025 15:28:17","17-05-=
2025 16:10:08","Grid outage, Site down due to poor battery backup // Grid r=
eturn","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, Site down due to poor battery backup =
// Grid return","franck.nkomot@matech-cameroun.com","427","17-05-2025 15:35=
:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0005042325","Omnispor=
t-Rail","","17-05-2025 15:35:02","17-05-2025 15:29:19","17-05-2025 16:35:19=
","Cascaded Incident from TTO5176771","Delor Telezing","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue on site ,si=
te on Grid with Ubaie=3D53.6 V The Tx FME Symphorien (650257151) from Huawe=
i is informed","system","1672449","17-05-2025 15:35:02","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005042323","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","17-05-2025 15:34:31","17-05-=
2025 15:29:19","17-05-2025 16:35:19","Active//No power issue on site ,site =
on Grid with Ubaie=3D53.6 V The Tx FME Symphorien (650257151) from Huawei i=
s informed","Fabrice Pouakam","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site ,s=
ite on Grid with Ubaie=3D53.6 V The Tx FME Symphorien (650257151) from Huaw=
ei is informed","edwige.kapawo@matech-cameroun.com","314","17-05-2025 15:34=
:31","MATECH CMR"
"Closed Complete","Site Down","T2564","IHS_YND_739","NOCINC0005042322","NKO=
LMESSING rue Manguier","","17-05-2025 15:34:18","17-05-2025 15:23:12","17-0=
5-2025 16:35:24","Grid outage, site went down due to grid bad voltage// he =
started gen manually","Siligap Boris","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","Grid outage, site went down due to gri=
d bad voltage// he started gen manually","franck.nkomot@matech-cameroun.com=
","666","17-05-2025 15:34:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005042287","MEHANDAN=
","","17-05-2025 15:30:45","17-05-2025 15:26:58","17-05-2025 16:50:58","Cas=
caded Incident from TTO5176725","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // He reseted the controller, =
grid returned","system","1672579","17-05-2025 15:30:45","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005042283","O=
dza II OCM","IHS_YND_528","17-05-2025 15:30:11","17-05-2025 15:26:58","17-0=
5-2025 16:50:58","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // He reseted the controller, grid returned","Alb=
ran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Over=
loaded","Grid outage, site went down because gen failed to start due to PWC=
 ZTE malfunction // He reseted the controller, grid returned","edwige.kapaw=
o@matech-cameroun.com","194","17-05-2025 15:30:11","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0005042259","Ema=
na Lycee","","17-05-2025 15:29:27","17-05-2025 15:26:22","17-05-2025 18:50:=
03","Grid outage, site went down due to poor backup battery // Grid returne=
d","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Battery Low","Grid outage, site went down due to poor backup batter=
y // Grid returned","franck.nkomot@matech-cameroun.com","186","17-05-2025 1=
5:29:27","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005042258","S=
atcom","","17-05-2025 15:29:13","17-05-2025 15:24:52","17-05-2025 18:38:27"=
,"No power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144=
412) of huawei is informed","Delor Telezing","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144412) of huawei is in=
formed","edwige.kapawo@matech-cameroun.com","262","17-05-2025 15:29:13","MA=
TECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005042240","Mok=
olo Yaounde","","17-05-2025 15:28:31","17-05-2025 15:24:26","17-05-2025 19:=
25:59","Active // No power issue Ubay: 54.7V site on grid. The Tx FME Eloun=
dou Bertrand (693212405) from Huawei is informed","","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // =
No power issue Ubay: 54.7V site on grid. The Tx FME Eloundou Bertrand (6932=
12405) from Huawei is informed","franck.nkomot@matech-cameroun.com","246","=
17-05-2025 15:28:31","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005042193","M=
essassi 2","","17-05-2025 15:22:08","17-05-2025 15:19:53","17-05-2025 16:31=
:27","(very unstable) Grid outage, Site went down due to 02/08 rectifiers i=
ssue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","(very unstable) Grid outage, Site went down du=
e to 02/08 rectifiers issue // Grid stabilised","edwige.kapawo@matech-camer=
oun.com","137","17-05-2025 15:22:08","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005042165","S=
aa","IHS_YND_810, IHS_YND_809","17-05-2025 15:18:09","17-05-2025 15:13:01",=
"17-05-2025 22:25:31","Site went down because 01/03 rectifier disfunctionni=
ng SS BATEU Felix IHS is informed // He reset it: Site on grid","Parker Tch=
oup","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went=
 down because 01/03 rectifier disfunctionning SS BATEU Felix IHS is informe=
d // He reset it: Site on grid","edwige.kapawo@matech-cameroun.com","309","=
17-05-2025 15:18:09","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0005042154","Ebo=
go","","17-05-2025 15:17:37","17-05-2025 15:14:22","17-05-2025 15:30:47","G=
rid outage, site went down before Gen start due poor backup battery // Gen =
automatically started","Siligap Boris","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
Gen start due poor backup battery // Gen automatically started","franck.nko=
mot@matech-cameroun.com","197","17-05-2025 15:17:37","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005042080","SAA=
 Entrance","","17-05-2025 15:07:05","17-05-2025 15:00:00","17-05-2025 15:11=
:47","Grid outage, site went down due to Grid bad voltage // GRID RETURN","=
Parker Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid outage, site went down due to Grid bad voltage // GRID R=
ETURN","franck.nkomot@matech-cameroun.com","427","17-05-2025 15:07:05","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0005042065","Crf-Mban=
kolo-IHS","","17-05-2025 15:03:55","17-05-2025 14:56:26","17-05-2025 15:07:=
16","Cascaded Incident from TTO5176477","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage, Site went Down du=
e to  poor backup // Grid return","system","1667283","17-05-2025 15:03:55",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0005042058","J=
-Vespa","IHS_YND_574, IHS_YND_544","17-05-2025 15:01:39","17-05-2025 14:56:=
26","17-05-2025 15:07:16","Grid Outage, Site went Down due to  poor backup =
// Grid return","Mboua Thierry","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid Outage, Site went Down due to  poor b=
ackup // Grid return","edwige.kapawo@matech-cameroun.com","314","17-05-2025=
 15:01:39","MATECH CMR"
"Closed Complete","Site Down","CTR_525","IHS_YND_544","NOCINC0005042054","J=
ean Vespa 2","","17-05-2025 15:01:09","17-05-2025 14:56:26","17-05-2025 15:=
07:16","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Outage, Site went Down due to  poor backup // Grid retu=
rn","franck.nkomot@matech-cameroun.com","1667283","17-05-2025 15:01:09","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0005042023","H=
-Paradis","","17-05-2025 14:55:09","17-05-2025 14:48:58","17-05-2025 19:43:=
50","Active// no power issue, site is on grid with Ubaie: 49.9V, Symphorien=
(650257151) from Huawei is informed","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active// no power issue=
, site is on grid with Ubaie: 49.9V, Symphorien(650257151) from Huawei is i=
nformed","vanel.mbiada@matech-cameroun.com","372","17-05-2025 14:55:09","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005042021","FOUGEROL=
E","","17-05-2025 14:54:37","17-05-2025 14:48:52","17-05-2025 18:13:18","Ca=
scaded Incident from TTO5176433","Siligap Boris","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active // no power issue, site is on gri=
d with Ubaie=3D53V, Symphorien(650257151) from Huawei is informed,","system=
","1667726","17-05-2025 14:54:37","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005042018","N=
gousso-Savana","IHS_YND_561","17-05-2025 14:54:00","17-05-2025 14:48:52","1=
7-05-2025 18:13:18","Active // no power issue, site is on grid with Ubaie=
=3D53V, Symphorien(650257151) from Huawei is informed,","Siligap Boris","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active // no power issue, site is on grid with Ubaie=3D53V, Sympho=
rien(650257151) from Huawei is informed,","vanel.mbiada@matech-cameroun.com=
","309","17-05-2025 14:54:00","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005041929","M=
efou-Assi","","17-05-2025 14:44:09","17-05-2025 14:22:00","17-05-2025 15:12=
:40","Grid outage, site went down because gen fails to start due to gen ove=
rload(15Kva, 200A) SS IHS FELIX ZAMBE is informed //Grid returned","Fanda B=
rice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outag=
e, site went down because gen fails to start due to gen overload(15Kva, 200=
A) SS IHS FELIX ZAMBE is informed //Grid returned","vanel.mbiada@matech-cam=
eroun.com","1331","17-05-2025 14:44:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0005041920","Nkol-Meb=
anga","","17-05-2025 14:41:34","17-05-2025 14:37:58","17-05-2025 14:38:58",=
"Cascaded Incident from TTO5176313","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active// No power issue on site ,site=
 on Gen with Ubaie =3D53.8V The Tx Technician from Huawei Gr=E9goire//65454=
7479 is informed","system","1674454","17-05-2025 14:41:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0005041919","Carrefou=
r Ayissi Ele","","17-05-2025 14:41:33","17-05-2025 14:37:58","17-05-2025 14=
:38:58","Cascaded Incident from TTO5176313","Parker Tchoup","Cascade Outage=
","Active","Cascade Active","Cascade Active","Active// No power issue on si=
te ,site on Gen with Ubaie =3D53.8V The Tx Technician from Huawei Gr=E9goir=
e//654547479 is informed","system","1674454","17-05-2025 14:41:33","MATECH =
CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005041910","Saa=
","IHS_YND_810, IHS_YND_809","17-05-2025 14:40:07","17-05-2025 14:34:58","1=
7-05-2025 14:38:58","Active// No power issue on site ,site on Gen with Ubai=
e =3D53.8V The Tx Technician from Huawei Gr=E9goire//654547479 is informed"=
,"Parker Tchoup","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active// No power issue on site ,site on Gen w=
ith Ubaie =3D53.8V The Tx Technician from Huawei Gr=E9goire//654547479 is i=
nformed","franck.nkomot@matech-cameroun.com","335","17-05-2025 14:40:07","M=
ATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0005041740","Mvo=
g Betsi Hospital","","17-05-2025 14:03:41","17-05-2025 13:58:32","17-05-202=
5 14:04:32","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","loic.noumsi@matech-cameroun.com",=
"309","17-05-2025 14:03:41","MATECH CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0005041603","Ngo=
usso MTN","IHS_YND_187","17-05-2025 13:35:23","17-05-2025 13:25:59","17-05-=
2025 16:39:18","Grid only site, no space to deploy MGE // Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid onl=
y site, no space to deploy MGE // Grid return","loic.noumsi@matech-cameroun=
.com","564","17-05-2025 13:35:23","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0005041595","NTE=
MASSI","","17-05-2025 13:34:06","17-05-2025 13:25:59","17-05-2025 16:39:49"=
,"Grid outage, Site down due to Rectifiers issue // site stabilised","Delor=
 Telezing","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid outage, Site down due to Rectifiers issue // site stabilised","loic.no=
umsi@matech-cameroun.com","1665543","17-05-2025 13:34:06","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0005041571","E=
vodoula OCM","","17-05-2025 13:30:53","17-05-2025 13:23:48","17-05-2025 15:=
51:40","Grid outage,gen failed to start due to grid bad voltage,no rcp//he =
bypassed the Grid and site on Gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid outage,ge=
n failed to start due to grid bad voltage,no rcp//he bypassed the Grid and =
site on Gen","loic.noumsi@matech-cameroun.com","426","17-05-2025 13:30:53",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005041535","Golf Qua=
ter","","17-05-2025 13:27:40","17-05-2025 13:06:27","19-05-2025 09:31:39","=
Cascaded Incident from TTO5175796 - Cascade Removed From TTO5175796","Mboua=
 Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid Only, No space to deploy// Grid return ","system","1666694","17-05-2025=
 13:27:40","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005041470","B=
astos-Nylon","","17-05-2025 13:14:48","17-05-2025 13:06:27","19-05-2025 09:=
31:39","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Only, No space to deploy// Grid return ","gaelle.njiofa=
ck@matech-cameroun.com","1666693","17-05-2025 13:14:48","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0005041461","N=
komkana","IHS_YND_220, IHS_YND_138, IHS_YND_126, IHS_YND_563, IHS_YND_127",=
"17-05-2025 13:13:39","17-05-2025 13:06:27","19-05-2025 09:33:14","Grid Onl=
y, No space to deploy// Grid return ","","Grid Supply","Passive","Grid","Na=
tional Grid - Grid Outage Issue","Grid Only, No space to deploy// Grid retu=
rn ","gaelle.njiofack@matech-cameroun.com","433","17-05-2025 13:13:39","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0005041457","N=
komkana 2","","17-05-2025 13:13:03","17-05-2025 13:06:27","19-05-2025 09:31=
:39","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid Only, No space to deploy// Grid return ","gaelle.njiofack=
@matech-cameroun.com","1666694","17-05-2025 13:13:03","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005041443","T=
singa","","17-05-2025 13:10:42","17-05-2025 13:06:27","19-05-2025 09:31:39"=
,"","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid Only, No space to deploy// Grid return ","gaelle.njiofack@mat=
ech-cameroun.com","1666693","17-05-2025 13:10:42","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005041013","Men=
dong NB","","17-05-2025 12:36:13","17-05-2025 12:32:40","17-05-2025 14:07:4=
0","Grid Only, No space to deploy // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid Only, No space to deploy=
 // Grid return","loic.noumsi@matech-cameroun.com","214","17-05-2025 12:36:=
13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005040960","Emana Ly=
cee","","17-05-2025 12:26:50","17-05-2025 12:23:36","17-05-2025 12:34:01","=
Cascaded Incident from TTO5175181","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down befo=
re Gen failed to started due to poor battery backup //gen automaticaly star=
ted.","system","1662091","17-05-2025 12:26:50","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005040955","E=
mana lycee 2","IHS_YND_274","17-05-2025 12:25:45","17-05-2025 12:23:36","17=
-05-2025 12:34:25","Grid outage , site went down before Gen failed to start=
ed due to poor battery backup //gen automaticaly started.","Fabrice Pouakam=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low=
","Grid outage , site went down before Gen failed to started due to poor ba=
ttery backup //gen automaticaly started.","gaelle.njiofack@matech-cameroun.=
com","130","17-05-2025 12:25:45","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005040934","SIM=
BOCK BONAMBAPE","","17-05-2025 12:22:43","17-05-2025 12:18:47","17-05-2025 =
13:43:47","grid outage, site went down due to Gen Overload (20kva, 350A) SS=
 IHS Felix ZAMBE confirmed // He reduced the load, site on gen","Hyemafo Gi=
ldas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","grid outag=
e, site went down due to Gen Overload (20kva, 350A) SS IHS Felix ZAMBE conf=
irmed // He reduced the load, site on gen","loic.noumsi@matech-cameroun.com=
","236","17-05-2025 12:22:43","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005040666","B=
arriere IHS","","17-05-2025 11:58:42","17-05-2025 11:52:29","17-05-2025 12:=
52:48","Grid outage, site went down because gen started and stopped with hi=
gh temp alarm // he added water and manually start the gen","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid outage, site went down because gen started and stopped=
 with high temp alarm // he added water and manually start the gen","loic.n=
oumsi@matech-cameroun.com","374","17-05-2025 11:58:42","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005040365","Nko=
g-Edzen","","17-05-2025 11:05:25","17-05-2025 10:58:15","17-05-2025 12:00:1=
4","Active//No power issue on site, Site on Grid Ubay =3D 53.6V The Tx Fme =
Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Grid Ubay =3D 53.6V The Tx Fme Greg=
oire (654547479) from Huawei is informed.","loic.noumsi@matech-cameroun.com=
","431","17-05-2025 11:05:25","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005040324","Men=
dong3","","17-05-2025 10:58:19","17-05-2025 10:55:48","17-05-2025 11:27:50"=
,"Grid only site no space to deploy MDGE // grid returned","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid only site no sp=
ace to deploy MDGE // grid returned","loic.noumsi@matech-cameroun.com","152=
","17-05-2025 10:58:19","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005040283","Par=
adis Hotel","","17-05-2025 10:51:35","17-05-2025 10:45:28","17-05-2025 17:3=
9:12","Site down due insufficient of rectifiers  // Site Stabilized","Silig=
ap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module","Site=
 down due insufficient of rectifiers  // Site Stabilized","loic.noumsi@mate=
ch-cameroun.com","368","17-05-2025 10:51:35","MATECH CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0005040070","M=
obil-Kondengui","IHS_YND_682","17-05-2025 10:26:27","17-05-2025 10:19:20","=
17-05-2025 22:27:46","Grid outage, No space to deploy a MGE // Grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d outage, No space to deploy a MGE // Grid return","gaelle.njiofack@matech-=
cameroun.com","428","17-05-2025 10:26:27","MATECH CMR"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0005040057","M=
ONTEE NKONDENGUI","","17-05-2025 10:25:46","17-05-2025 10:19:20","17-05-202=
5 22:27:46","","Albran Byorel","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, No space to deploy a MGE // Grid return","=
gaelle.njiofack@matech-cameroun.com","1662281","17-05-2025 10:25:46","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005039967","Minka","=
","17-05-2025 10:07:41","17-05-2025 10:00:15","17-05-2025 10:34:27","Cascad=
ed Incident from TTO5174053","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid unstable, Grid stabilized but Eneo con=
tactor did not stick due to battery backup discharge // Generator started m=
anually to charge the batteries; Generator off, contactor Stick and site on=
 Grid","system","1663393","17-05-2025 10:07:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005039968","Bondjock=
","","17-05-2025 10:07:41","17-05-2025 10:00:15","17-05-2025 10:34:27","Cas=
caded Incident from TTO5174053","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid unstable, Grid stabilized but Eneo =
contactor did not stick due to battery backup discharge // Generator starte=
d manually to charge the batteries; Generator off, contactor Stick and site=
 on Grid","system","1663393","17-05-2025 10:07:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005039966","Mbeng","=
","17-05-2025 10:07:40","17-05-2025 10:00:15","17-05-2025 10:34:27","Cascad=
ed Incident from TTO5174053","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid unstable, Grid stabilized but Eneo con=
tactor did not stick due to battery backup discharge // Generator started m=
anually to charge the batteries; Generator off, contactor Stick and site on=
 Grid","system","1663394","17-05-2025 10:07:40","MATECH CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0005039954","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_554, IHS_YND_553, IHS_YND_372","17-0=
5-2025 10:05:34","17-05-2025 10:00:15","17-05-2025 10:34:27","Grid unstable=
, Grid stabilized but Eneo contactor did not stick due to battery backup di=
scharge // Generator started manually to charge the batteries; Generator of=
f, contactor Stick and site on Grid","Fanda Brice","Grid Supply","Passive",=
"Grid","National Grid - Unstable Grid Supply Issue","Grid unstable, Grid st=
abilized but Eneo contactor did not stick due to battery backup discharge /=
/ Generator started manually to charge the batteries; Generator off, contac=
tor Stick and site on Grid","loic.noumsi@matech-cameroun.com","320","17-05-=
2025 10:05:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005039411","Emana Ly=
cee","","17-05-2025 09:01:51","17-05-2025 08:50:31","17-05-2025 09:06:08","=
Cascaded Incident from TTO5173390","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down befo=
re Gen failed to started due to poor battery backup // gen automaticaly sta=
rted.","system","1660372","17-05-2025 09:01:51","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005039375","Elo=
umdem stade","","17-05-2025 08:57:43","17-05-2025 08:53:35","17-05-2025 09:=
01:00","Grid outage, site went down due to insufficience of rectifiers // h=
e added 01 rectifier, site on Grid","Fanda Brice","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Grid outage, site went down due to insu=
fficience of rectifiers // he added 01 rectifier, site on Grid","loic.noums=
i@matech-cameroun.com","249","17-05-2025 08:57:43","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005039367","Ema=
na lycee 2","IHS_YND_274","17-05-2025 08:55:40","17-05-2025 08:50:31","17-0=
5-2025 09:06:16","Grid outage , site went down before Gen failed to started=
 due to poor battery backup // gen automaticaly started.","Fabrice Pouakam"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"Grid outage , site went down before Gen failed to started due to poor bat=
tery backup // gen automaticaly started.","loic.noumsi@matech-cameroun.com"=
,"311","17-05-2025 08:55:40","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005039331","E=
ssomba","","17-05-2025 08:50:34","17-05-2025 08:49:00","17-05-2025 19:01:16=
","Site went down because PWC overload // Site stabilised, Without interven=
tion","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Site went down because PWC overload // Site stabilise=
d, Without intervention","gaelle.njiofack@matech-cameroun.com","95","17-05-=
2025 08:50:34","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0005038927","Mam=
ch Building","","17-05-2025 06:53:58","17-05-2025 06:48:49","17-05-2025 07:=
09:36","Grid outage,Site went down because Gen failed to start due to no au=
tomatism on site//He started the Gen manually","Mboua Thierry","Equipment R=
epair","Passive","Control Panel","ATS-AMF Issue","Grid outage,Site went dow=
n because Gen failed to start due to no automatism on site//He started the =
Gen manually","gerard.tchangoue@matech-cameroun.com","310","17-05-2025 06:5=
3:58","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005038827","S=
atcom","","17-05-2025 06:22:03","17-05-2025 06:15:51","17-05-2025 06:26:58"=
,"No power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144=
412) of huawei is informed","Delor Telezing","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144412) of huawei is in=
formed","vanel.mbiada@matech-cameroun.com","373","17-05-2025 06:22:03","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0005038756","H=
-Franco New","","17-05-2025 06:01:58","17-05-2025 06:00:41","17-05-2025 06:=
22:11","Grid outage, Site went down because GEN OVERLOAD (20KVA, 320A) RM I=
HS BATE is informed// Grid return	","Delor Telezing","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because GE=
N OVERLOAD (20KVA, 320A) RM IHS BATE is informed// Grid return	","vanel.mbi=
ada@matech-cameroun.com","78","17-05-2025 06:01:58","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0005038704","Nko=
ulou Carriere carrefourt","","17-05-2025 05:48:47","17-05-2025 05:37:19","1=
7-05-2025 07:11:44","FME Antoine will managed after ABANG","Mba Lazare Herv=
e","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Unstable=
 Grid, site went down because Gen stopped due to Alarm undervoltage, // Gen=
 card reset and Grid stabilized","gerard.tchangoue@matech-cameroun.com","16=
57710","17-05-2025 05:48:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0005038689","Nkolanga=
a","","17-05-2025 05:47:57","17-05-2025 05:37:19","17-05-2025 07:11:44","Ca=
scaded Incident from TTO5172593","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Unstable Grid, site went down beca=
use Gen stopped due to Alarm undervoltage, // Gen card reset and Grid stabi=
lized","system","1657709","17-05-2025 05:47:57","MATECH CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0005038682","A=
bang","IHS_YND_794, IHS_YND_289","17-05-2025 05:45:38","17-05-2025 05:37:19=
","17-05-2025 07:11:55","Unstable Grid, site went down because Gen stopped =
due to Alarm under voltage, // Gen card reset and Grid stabilized","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Under Voltage","=
Unstable Grid, site went down because Gen stopped due to Alarm undervoltage=
, // Gen card reset and Grid stabilized","ludivine.ngamaleu@ihstowers.com",=
"500","17-05-2025 05:45:38","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0005038667","UPA=
C LP","","17-05-2025 05:37:54","17-05-2025 05:10:47","17-05-2025 06:23:19",=
"Grid outage .no space to deploy mobile gen // Grid returned","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage .no s=
pace to deploy mobile gen // Grid returned","gerard.tchangoue@matech-camero=
un.com","1628","17-05-2025 05:37:54","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005038662","Nko=
l-Mebanga","","17-05-2025 05:37:00","17-05-2025 05:28:59","17-05-2025 11:01=
:03","Solar only site, // solar returned","Parker Tchoup","Equipment Repair=
","Passive","Solar","Solar Panel Issue","Solar only site, // solar returned=
","gerard.tchangoue@matech-cameroun.com","482","17-05-2025 05:37:00","MATEC=
H CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0005038657","Jea=
n Vespa","IHS_YND_574","17-05-2025 05:36:09","17-05-2025 05:27:57","17-05-2=
025 06:41:48","Site went down because Gen failed to start due to Eneo fuse =
dysfunctionning // He fixed it","Mboua Thierry","Grid Supply","Passive","Gr=
id","National Grid - Fuse Burnt","Site went down because Gen failed to star=
t due to Eneo fuse dysfunctionning // He fixed it","gerard.tchangoue@matech=
-cameroun.com","492","17-05-2025 05:36:09","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005038626","Crf=
-Mbankolo-IHS","","17-05-2025 05:32:54","17-05-2025 05:27:57","17-05-2025 0=
6:41:48","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Site went down because Gen failed to start due to Eneo fus=
e dysfunctionning // He fixed it","gerard.tchangoue@matech-cameroun.com","1=
658267","17-05-2025 05:32:54","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005038570","N=
koabang2","","17-05-2025 05:17:20","17-05-2025 05:11:10","17-05-2025 08:50:=
01","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","vanel.=
mbiada@matech-cameroun.com","371","17-05-2025 05:17:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0005038565","Jean Ves=
pa 2","","17-05-2025 05:14:34","17-05-2025 05:10:26","17-05-2025 06:40:34",=
"Cascaded Incident from TTO5172455","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down due to Eneo fuse wa=
s cut, // fuse connected and site on Grid","system","1659292","17-05-2025 0=
5:14:34","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0005038560","J=
-Vespa","IHS_YND_544","17-05-2025 05:12:59","17-05-2025 05:10:26","17-05-20=
25 06:40:34","site went down due to Eneo fuse was cut, // fuse connected an=
d site on Grid","Mboua Thierry","Grid Supply","Passive","Grid","National Gr=
id - Fuse Burnt","site went down due to Eneo fuse was cut, // fuse connecte=
d and site on Grid","vanel.mbiada@matech-cameroun.com","153","17-05-2025 05=
:12:59","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005038532","SAA=
 Entrance","","17-05-2025 05:00:42","17-05-2025 04:28:28","17-05-2025 07:26=
:09","Grid outage, site went down due to Grid bad voltage // He bypassed Gr=
id and put site on Gen","Parker Tchoup","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","Grid outage, site went down due to G=
rid bad voltage // He bypassed Grid and put site on Gen","gerard.tchangoue@=
matech-cameroun.com","3631","17-05-2025 05:00:42","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0005038273","N=
koabang2","","17-05-2025 02:59:55","17-05-2025 02:56:45","17-05-2025 05:04:=
11","site down due to bad grid voltage // Grid restored ","Mba Lazare Herve=
","Grid Supply","Passive","Grid","National Grid - Grid Incomplete Phase","s=
ite down due to bad grid voltage // Grid restored ","vanel.mbiada@matech-ca=
meroun.com","192","17-05-2025 02:59:55","MATECH CMR"
"Closed Complete","Site Down","T1739","IHS_YND_691","NOCINC0005038151","Mba=
lla 2 REGIE","","17-05-2025 02:19:09","17-05-2025 02:10:51","17-05-2025 03:=
36:02","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage // Site stabilized","Delor Telezing","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, sit=
e went down because Gen failed to start due to grid bad voltage // Site sta=
bilized","gerard.tchangoue@matech-cameroun.com","498","17-05-2025 02:19:09"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0005037984","Yoko MTN=
","","17-05-2025 01:16:14","16-05-2025 22:43:45","17-05-2025 05:22:46","Cas=
caded Incident from TTO5171460","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down because Ge=
n failed to start due to battery charger HS // He reconnected it","system",=
"1675248","17-05-2025 01:16:14","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005037920","Par=
adis Hotel","","17-05-2025 00:46:54","17-05-2025 00:41:45","17-05-2025 09:2=
9:31","Site went down due to rectifier Issue (02/06 rectifiers dysfunctioni=
ng on site) SS IHS Blaise is informed // He reseted them","Siligap Boris","=
Equipment Repair","Passive","Rectifier","Rectifier Module","Site went down =
due to rectifier Issue (02/06 rectifiers dysfunctioning on site) SS IHS Bla=
ise is informed // He reseted them","gerard.tchangoue@matech-cameroun.com",=
"309","17-05-2025 00:46:54","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005037901","E=
ssomba","","17-05-2025 00:42:03","17-05-2025 00:32:53","17-05-2025 07:26:54=
","Site went down because PWC overload // Site stabilised,","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Site went down because PWC overload // Site stabilised,","ludivine.ngamale=
u@ihstowers.com","551","17-05-2025 00:42:03","MATECH CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0005037894","Sap=
eur Mimboman","","17-05-2025 00:37:20","17-05-2025 00:36:12","17-05-2025 07=
:21:59","Site went down due to 02 rectifiers dysfunctionning // He reseted =
these rectifiers","Mba Lazare Herve","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to 02 rectifiers dysfunctionning =
// He reseted these rectifiers","gerard.tchangoue@matech-cameroun.com","69"=
,"17-05-2025 00:37:20","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005037878","AKA=
K Nkozoa","","17-05-2025 00:29:04","17-05-2025 00:24:52","17-05-2025 01:26:=
12","Site went down due to insufficient rectifier issue // he reseted it","=
Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient rectifier issue // he reseted it","ge=
rard.tchangoue@matech-cameroun.com","253","17-05-2025 00:29:04","MATECH CMR=
"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0005037727","M=
BIMBIM","IHS_YND_460, IHS_YND_475, IHS_YND_473","16-05-2025 23:51:01","16-0=
5-2025 22:43:45","17-05-2025 05:22:46","Grid outage, Site went down because=
 Gen failed to start due to battery charger HS // He reconnected it","Parke=
r Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternat=
or","Grid outage, Site went down because Gen failed to start due to battery=
 charger HS // He reconnected it","vanel.mbiada@matech-cameroun.com","4037"=
,"16-05-2025 23:51:01","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005037679","O=
LAMA","","16-05-2025 23:31:17","16-05-2025 23:23:01","17-05-2025 00:12:04",=
"No power issue on site Ubaie =3D54.9V site on Grid. The TX FME Henri (6999=
49693) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubaie =3D54.9V site on Grid. The TX FME Henri (699949693) from Huawei=
 is informed","ludivine.ngamaleu@ihstowers.com","497","16-05-2025 23:31:17"=
,"MATECH CMR"
"Cancelled","Warning","","IHS_YND_537","NOCINC0005037584","MEFOU ASSI","","=
16-05-2025 23:08:54","","","site impacted by Mefou  Assi/ IHS_YND_258","Fan=
da Brice","","","","","","system","2040","16-05-2025 23:08:54","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005037560","M=
ontee-Jouvence-II","","16-05-2025 23:03:49","16-05-2025 22:11:36","16-05-20=
25 23:30:27","ACTIVE// No power issue on site, site on Grid with Ubaie=3D54=
.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo G=
ildas","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE// No power issue on site, site on Grid with Ubaie=
=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed","ludi=
vine.ngamaleu@ihstowers.com","3135","16-05-2025 23:03:49","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005037547","A=
ccacia New","","16-05-2025 23:00:29","16-05-2025 22:11:06","17-05-2025 00:1=
3:29","No power issue on site Ubaie=3D52.88V site on Grid , The Tx FME Mbah=
 Hosiah (699699694) from Huawei is informed","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site Ubaie=3D52.88V site on Grid , The Tx FME Mbah Hosiah (699699694) fr=
om Huawei is informed","ludivine.ngamaleu@ihstowers.com","2965","16-05-2025=
 23:00:29","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005037460","M=
efou-Assi","IHS_YND_520","16-05-2025 22:41:01","16-05-2025 22:34:54","17-05=
-2025 07:24:36","Grid outage, site went down because gen fails to start due=
 to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed //Grid returne=
d","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage, site went down because gen fails to start due to gen overload=
(15Kva, 200A) SS IHS FELIX ZAMBE is informed //Grid returned","vanel.mbiada=
@matech-cameroun.com","368","16-05-2025 22:41:01","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005037454","S=
IMBOCK BONAMBAPE","","16-05-2025 22:38:25","16-05-2025 22:34:54","17-05-202=
5 08:14:36","Active // No power issue site on grid with Ubaie: 52.9V TX FME=
 Flubert (654266068) from Huawei is informed","Hyemafo Gildas","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Active // No power issu=
e site on grid with Ubaie: 52.9V TX FME Flubert (654266068) from Huawei is =
informed","vanel.mbiada@matech-cameroun.com","1668612","16-05-2025 22:38:25=
","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005037401","A=
WAE OCM","","16-05-2025 22:30:36","16-05-2025 22:20:59","16-05-2025 23:29:0=
2","Grid outage site went down because Gen failed to start due PWC ZTE dysf=
onctionned // He reset the PWC and Gen manually started","Mba Lazare Herve"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage site went down because Gen failed to start due PWC ZTE dysfonctio=
nned // He reset the PWC and Gen manually started","vanel.mbiada@matech-cam=
eroun.com","579","16-05-2025 22:30:36","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0005037364","Nlo=
ngkak","","16-05-2025 22:22:25","16-05-2025 22:22:15","16-05-2025 22:51:15"=
,"grid outage, site went down because Gen started and stopped due to alarm =
over Voltage//he reset Gen card and Started Gen","Delor Telezing","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage, site we=
nt down because Gen started and stopped due to alarm over Voltage//he reset=
 Gen card and Started Gen","loic.noumsi@matech-cameroun.com","11","16-05-20=
25 22:22:25","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005037343","D=
amas","","16-05-2025 22:19:35","16-05-2025 22:11:28","17-05-2025 07:06:55",=
"Grid outage, site went down due to PSC3 Controller dysfunctionning // He r=
eseted it","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid outage, site went down due to PSC3 Controller dysfunct=
ionning // He reseted it","loic.noumsi@matech-cameroun.com","488","16-05-20=
25 22:19:35","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0005037324","NKO=
MEKUI OCM","","16-05-2025 22:16:37","16-05-2025 22:08:27","17-05-2025 00:12=
:34","No power issue site on Gen with U=3D54.5 V The Tx Fme Mohamadou mouam=
 // 691144435 from Huawei is informed site impacted by Mbankolo camtel","TI=
ENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equip=
ment Failure","Affected by 3rd Party Site","No power issue site on Gen with=
 U=3D54.5 V The Tx Fme Mohamadou mouam // 691144435 from Huawei is informed=
 site impacted by Mbankolo camtel","loic.noumsi@matech-cameroun.com","491",=
"16-05-2025 22:16:37","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005037270","S=
atcom","","16-05-2025 22:05:25","16-05-2025 22:00:13","17-05-2025 00:13:01"=
,"No power issue site on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144=
412) of huawei is informe","Delor Telezing","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on Grid with Ubay:53.2V Tx Fme Armand Ngestsa (691144412) of huawei is inf=
orme","edwige.kapawo@matech-cameroun.com","313","16-05-2025 22:05:25","MATE=
CH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005037199","Nko=
g-Edzen","","16-05-2025 21:53:39","16-05-2025 21:47:31","17-05-2025 00:18:3=
4","Active//No power issue on site, Site on Grid Ubay =3D 56.4V The Tx Fme =
Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Grid Ubay =3D 56.4V The Tx Fme Greg=
oire (654547479) from Huawei is informed.","loic.noumsi@matech-cameroun.com=
","369","16-05-2025 21:53:39","MATECH CMR"
"Closed Complete","Site Down","T1112","IHS_YND_074","NOCINC0005037176","Obi=
li Chapelle","","16-05-2025 21:49:34","16-05-2025 21:41:26","16-05-2025 22:=
51:26","Grid outage, site went down because Gen failed to start due to Card=
 Ge faulty, SS IHS Francois Ndoungou is informed // Grid restored","Paul BI=
BOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
outage, site went down because Gen failed to start due to Card Ge faulty, S=
S IHS Francois Ndoungou is informed // Grid restored","loic.noumsi@matech-c=
ameroun.com","489","16-05-2025 21:49:34","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005036998","O=
LAMA","","16-05-2025 21:20:57","16-05-2025 21:12:50","16-05-2025 21:21:26",=
"Active // No power issue on site Ubaie =3D55.1V site on Grid The TX FME He=
nri (699949693) from Huawei is informed.Noticed that it is a repetitve issu=
e","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active // No power issue on site Ubaie =3D55.1=
V site on Grid The TX FME Henri (699949693) from Huawei is informed.Noticed=
 that it is a repetitve issue","edwige.kapawo@matech-cameroun.com","488","1=
6-05-2025 21:20:57","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005036940","B=
arriere IHS","","16-05-2025 21:09:35","16-05-2025 21:03:23","16-05-2025 22:=
28:11","Grid outage, site went down due to Gen overload // He reduced the l=
oad and site on Gen","Hyemafo Gildas","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","Grid outage, site went down due to Gen overload // He=
 reduced the load and site on Gen","edwige.kapawo@matech-cameroun.com","373=
","16-05-2025 21:09:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0005036890","Tamtam W=
eekend","","16-05-2025 21:01:54","16-05-2025 20:56:02","16-05-2025 21:54:29=
","Cascaded Incident from TTO5170446","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, No space to deploy=
 MGE // Grid restored","system","1667392","16-05-2025 21:01:54","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0005036889","Damas","=
","16-05-2025 21:01:54","16-05-2025 20:56:02","16-05-2025 21:54:29","Cascad=
ed Incident from TTO5170446","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid Outage, No space to deploy MGE // Gr=
id restored","system","1667392","16-05-2025 21:01:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0005036891","Montee-J=
ouvence-II","","16-05-2025 21:01:54","16-05-2025 20:56:02","16-05-2025 21:5=
4:29","Cascaded Incident from TTO5170446","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid Outage, No space to de=
ploy MGE // Grid restored","system","1667391","16-05-2025 21:01:54","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0005036882","R=
d-Pt-Express","IHS_YND_166, IHS_YND_151, IHS_YND_518","16-05-2025 21:00:20"=
,"16-05-2025 20:56:02","16-05-2025 21:54:29","Grid Outage, No space to depl=
oy MGE // Grid restored","","Grid Supply","Passive","Grid","National Grid -=
 Grid Outage Issue","Grid Outage, No space to deploy MGE // Grid restored",=
"edwige.kapawo@matech-cameroun.com","258","16-05-2025 21:00:20","MATECH CMR=
"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005036697","N=
gousso-Savana","IHS_YND_561","16-05-2025 20:42:36","16-05-2025 20:15:27","1=
6-05-2025 21:33:36","Grid Outage, site went down before gen start due to po=
or battery backup // Gen start automatically","Siligap Boris","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage,=
 site went down before gen start due to poor battery backup // Gen start au=
tomatically","edwige.kapawo@matech-cameroun.com","1630","16-05-2025 20:42:3=
6","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005036664","F=
OUGEROLE","","16-05-2025 20:38:29","16-05-2025 20:15:27","16-05-2025 21:33:=
36","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid Outage, site went down before gen start due to poor batter=
y backup // Gen start automatically","edwige.kapawo@matech-cameroun.com","1=
669773","16-05-2025 20:38:29","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005036572","OBA=
M NGOLA OCM","","16-05-2025 20:22:24","16-05-2025 20:17:13","16-05-2025 21:=
40:00","Site went down due to insufficient rectifier on site//site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifier on site//site stabilised=
","loic.noumsi@matech-cameroun.com","312","16-05-2025 20:22:24","MATECH CMR=
"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005036506","AKA=
K Nkozoa","","16-05-2025 20:11:01","16-05-2025 20:06:24","16-05-2025 23:41:=
24","Site went down due to insufficient rectifier issue // he reseted it","=
Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient rectifier issue // he reseted it","lo=
ic.noumsi@matech-cameroun.com","278","16-05-2025 20:11:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0005036332","Biteng",=
"","16-05-2025 19:50:13","16-05-2025 19:27:39","16-05-2025 19:57:06","Casca=
ded Incident from TTO5169783 - Cascade Removed From TTO5169783","Mba Lazare=
 Herve","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Gri=
d outage,Gen stopped with alarm high temp(alarm unproven)//he reset the gen=
 card and started it","system","1665395","16-05-2025 19:50:13","MATECH CMR"
"Closed Complete","Site Down","T1549","IHS_YND_295","NOCINC0005036291","NGO=
NA","","16-05-2025 19:44:52","16-05-2025 19:27:39","16-05-2025 19:57:06",""=
,"Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage,Gen stopped with alarm high temp(alarm unproven)//he r=
eset the gen card and started it","loic.noumsi@matech-cameroun.com","166539=
4","16-05-2025 19:44:52","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005036279","Lad=
a I Yde","","16-05-2025 19:41:37","16-05-2025 19:27:39","16-05-2025 19:57:0=
6","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage,Gen stopped with alarm high temp(alarm unproven)/=
/he reset the gen card and started it","loic.noumsi@matech-cameroun.com","1=
665396","16-05-2025 19:41:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0005036254","Nkolo II=
 New","","16-05-2025 19:38:40","16-05-2025 19:15:24","16-05-2025 19:52:17",=
"Cascaded Incident from TTO5169679","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuations, site went do=
wn because Gen failed to start due to grid bad voltage // Grid stabilised",=
"system","1666119","16-05-2025 19:38:40","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0005036249","NKO=
ABANG NKOLO 3","IHS_YND_295, IHS_YND_249, IHS_YND_526, IHS_YND_750, IHS_YND=
_795, IHS_YND_248","16-05-2025 19:37:45","16-05-2025 19:27:39","16-05-2025 =
23:30:39","Grid outage,Gen stopped with alarm high temp(alarm unproven)//he=
 reset the gen card and started it Site impacted by (NKOABANG T0058)","Mba =
Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","Grid outage,Gen stopped with alarm high temp(alarm unproven)//he reset t=
he gen card and started it Site impacted by (NKOABANG T0058)","loic.noumsi@=
matech-cameroun.com","606","16-05-2025 19:37:45","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0005036204","Mim=
boman4","IHS_YND_709","16-05-2025 19:28:39","16-05-2025 19:15:24","16-05-20=
25 19:52:17","Grid fluctuations, site went down because Gen failed to start=
 due to grid bad voltage // Grid stabilised","Mba Lazare Herve","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tions, site went down because Gen failed to start due to grid bad voltage /=
/ Grid stabilised","loic.noumsi@matech-cameroun.com","796","16-05-2025 19:2=
8:39","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0005036116","Bit=
eng-Maetur","","16-05-2025 19:14:04","16-05-2025 19:27:39","16-05-2025 19:5=
7:06","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","cascade outage","loic.noumsi@matech-cameroun.com","1665394=
","16-05-2025 19:14:04","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005036111","Nko=
abang2","","16-05-2025 19:12:04","16-05-2025 19:27:39","16-05-2025 19:57:06=
","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","cascade outage","loic.noumsi@matech-cameroun.com","1665394","1=
6-05-2025 19:12:04","MATECH CMR"
"Closed Complete","Site Down","T1850","IHS_YND_376","NOCINC0005036078","Mam=
b","","16-05-2025 19:07:38","16-05-2025 18:42:31","16-05-2025 19:42:57","Gr=
id outage, site went down because gen failed to start due to grid contactor=
 faulty // He bypassed ATS and Gen manually started","Kemeni Franklin","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, s=
ite went down because gen failed to start due to grid contactor faulty // H=
e bypassed ATS and Gen manually started","loic.noumsi@matech-cameroun.com",=
"1508","16-05-2025 19:07:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005036063","SOA VILL=
AGE","","16-05-2025 19:03:35","16-05-2025 18:53:59","16-05-2025 20:05:18","=
Cascaded Incident from TTO5169510","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // he added water and manual st=
art of Gen","system","1667374","16-05-2025 19:03:35","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005036054","S=
OA TOWN","IHS_YND_323","16-05-2025 19:02:27","16-05-2025 18:53:59","16-05-2=
025 20:05:47","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // he added water and manual start of Gen","Siligap Bori=
s","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coola=
nt Level Issue","Grid outage, site went down because gen start and stopped =
with high temp alarm // he added water and manual start of Gen","edwige.kap=
awo@matech-cameroun.com","509","16-05-2025 19:02:27","MATECH CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0005036002","Nko=
abang entree carriere","","16-05-2025 18:54:49","16-05-2025 19:27:39","16-0=
5-2025 19:57:06","","Mba Lazare Herve","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","Grid outage,Gen stopped with alarm high temp(al=
arm unproven)//he reset the gen card and started it","loic.noumsi@matech-ca=
meroun.com","1665393","16-05-2025 18:54:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_152","NOCINC0005035961","Rd-Pt-Ex=
press","IHS_YND_166, IHS_YND_151, IHS_YND_518","16-05-2025 18:48:29","16-05=
-2025 18:40:37","16-05-2025 19:17:22","Grid Only, Grid Outage No space to D=
eploy MGE // Grid return","","Grid Supply","Passive","Grid","National Grid =
- Grid Outage Issue","Grid Only, Grid Outage No space to Deploy MGE // Grid=
 return","system","472","16-05-2025 18:48:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0005035960","Damas","=
","16-05-2025 18:48:29","16-05-2025 18:40:37","16-05-2025 19:17:22","Cascad=
ed Incident from TTO5169387 - Cascade Removed From TTO5169387","MINKA NICOL=
AS","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid On=
ly, Grid Outage No space to Deploy MGE // Grid return","system","1668155","=
16-05-2025 18:48:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0005035962","Montee-J=
ouvence-II","","16-05-2025 18:48:29","16-05-2025 18:40:37","16-05-2025 19:1=
7:22","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Only, Grid Outage No space to Deploy MGE // Grid return=
","system","1668156","16-05-2025 18:48:29","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005035944","T=
amtam Weekend","","16-05-2025 18:45:46","16-05-2025 18:40:37","16-05-2025 1=
9:17:22","fme is on the way ETA 07:30 PM","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid Only, Grid Outage No s=
pace to Deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","166=
8155","16-05-2025 18:45:46","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005035932","Ron=
d Point Express1114","","16-05-2025 18:43:36","16-05-2025 18:37:24","16-05-=
2025 18:55:04","Grid outage, Site down due to poor battery backup // Grid r=
eturn","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, Site down due to poor battery backup =
// Grid return","loic.noumsi@matech-cameroun.com","373","16-05-2025 18:43:3=
6","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005035865","Bondjock=
","","16-05-2025 18:30:21","16-05-2025 18:05:26","16-05-2025 19:00:47","Cas=
caded Incident from TTO5169163","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid fluctuations, Site went down before=
 Gen start due to poor backup // Grid Stabilized","system","1669271","16-05=
-2025 18:30:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005035864","Mbeng","=
","16-05-2025 18:30:20","16-05-2025 18:05:26","16-05-2025 19:00:47","Cascad=
ed Incident from TTO5169163","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuations, Site went down before Ge=
n start due to poor backup // Grid Stabilized","system","1669271","16-05-20=
25 18:30:20","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005035855","B=
arriere","","16-05-2025 18:27:28","16-05-2025 18:24:11","16-05-2025 18:36:3=
1","Site went down due to plan work, SS IHS Felix was on site for battery t=
est // End of work","Hyemafo Gildas","Installation Activity","Passive","Pla=
nned Activity","Installation Activity","Site went down due to plan work, SS=
 IHS Felix was on site for battery test // End of work","edwige.kapawo@mate=
ch-cameroun.com","199","16-05-2025 18:27:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005035824","Minka","=
","16-05-2025 18:21:02","16-05-2025 18:05:26","16-05-2025 19:00:47","Cascad=
ed Incident from TTO5169163","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuations, Site went down before Ge=
n start due to poor backup // Grid Stabilized","system","1669270","16-05-20=
25 18:21:02","MATECH CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0005035739","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_372","16-05-2025 18:14:34","16-05-20=
25 18:05:26","16-05-2025 19:00:47","Grid fluctuations, Site went down befor=
e Gen start due to poor backup // Gen started manually","Fanda Brice","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 fluctuations, Site went down before Gen start due to poor backup // Gen st=
arted manually","loic.noumsi@matech-cameroun.com","550","16-05-2025 18:14:3=
4","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005035727","SAA=
 Entrance","","16-05-2025 18:13:52","16-05-2025 18:07:46","16-05-2025 18:16=
:13","Grid outage, site went down due to Grid bad voltage // He bypassed Gr=
id and put site on Gen","Parker Tchoup","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","Grid outage, site went down due to G=
rid bad voltage // He bypassed Grid and put site on Gen","loic.noumsi@matec=
h-cameroun.com","368","16-05-2025 18:13:52","MATECH CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0005035709","B=
yemassi Carrefour","","16-05-2025 18:10:45","16-05-2025 17:40:27","16-05-20=
25 18:49:15","Grid outage site went down because Gen fails to start due to =
battery ge discharged causing  //He started Gen manualy with external batte=
ry","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Generator=
 Battery","Grid outage site went down because Gen fails to start due to bat=
tery ge discharged causing  //He started Gen manualy with external battery"=
,"edwige.kapawo@matech-cameroun.com","1819","16-05-2025 18:10:45","MATECH C=
MR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0005035554","S=
calom-IHS","","16-05-2025 17:40:35","16-05-2025 17:24:45","16-05-2025 18:54=
:13","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid outage, site went down Gen failed to start due to ATS Dysfunctioning o=
n Site // He reset ATS and started Gen manually","loic.noumsi@matech-camero=
un.com","1665538","16-05-2025 17:40:35","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0005035493","S=
calom","IHS_YND_505","16-05-2025 17:27:59","16-05-2025 17:24:45","16-05-202=
5 18:56:02","Grid outage, site went down Gen failed to start due to ATS Dys=
functioning on Site // He reset ATS and started Gen manually","Paul BIBOUM"=
,"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,=
 site went down Gen failed to start due to ATS Dysfunctioning on Site // He=
 reset ATS and started Gen manually","edwige.kapawo@matech-cameroun.com","1=
95","16-05-2025 17:27:59","MATECH CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0005035446","Nko=
abang entree carriere","","16-05-2025 17:23:18","16-05-2025 17:15:11","16-0=
5-2025 17:25:33","No power issue, Site impacted by Nkoabang_T058","Mba Laza=
re Herve","3RD Party Power Failure","Passive","Power Provided By 3RD Party"=
,"Power Provided By 3RD Party","No power issue, Site impacted by Nkoabang_T=
058","loic.noumsi@matech-cameroun.com","487","16-05-2025 17:23:18","MATECH =
CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0005035372","Feb=
e Village","","16-05-2025 17:08:24","16-05-2025 17:03:17","16-05-2025 18:04=
:56","Grid fluctuation, site went down because Gen failed to start due to l=
ack of 01 phase on site // he did a bridge with a good phase","Mboua Thierr=
y","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, site went down because Gen failed to start due to lack =
of 01 phase on site // he did a bridge with a good phase","loic.noumsi@mate=
ch-cameroun.com","308","16-05-2025 17:08:24","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0005035256","Clu=
b France","","16-05-2025 16:50:14","16-05-2025 16:43:05","16-05-2025 18:41:=
02","Grid only site, no space to deploy MDGE // Grid returned","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site, =
no space to deploy MDGE // Grid returned","loic.noumsi@matech-cameroun.com"=
,"430","16-05-2025 16:50:14","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0005035203","B=
iyemassi LAC","","16-05-2025 16:42:10","16-05-2025 16:28:50","16-05-2025 18=
:42:44","Grid outage.no space to deploy MDGE // Grid returned","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no s=
pace to deploy MDGE // Grid returned","edwige.kapawo@matech-cameroun.com","=
801","16-05-2025 16:42:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0005035202","ELOUMDEM=
 CARRIERE 2","","16-05-2025 16:42:08","16-05-2025 16:38:12","16-05-2025 16:=
44:40","Cascaded Incident from TTO5168524","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","system","=
1667317","16-05-2025 16:42:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0005035201","Eto koss=
 Yde","","16-05-2025 16:42:08","16-05-2025 16:38:12","16-05-2025 16:44:40",=
"Cascaded Incident from TTO5168524","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","system","1667317=
","16-05-2025 16:42:08","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0005035191","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","16-05-2025 16:41:21","16-05-2025 16:38=
:12","16-05-2025 16:44:40","Grid outage, Site went down before Gen start du=
e to poor backup // Gen started automatically","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","loic.noumsi@matech-cameroun.com","191","16-05-2025 16:41:21","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005035152","S=
aa","","16-05-2025 16:36:40","16-05-2025 16:35:31","16-05-2025 17:00:14","S=
ite went down due to Planned work // End of work","Parker Tchoup","Installa=
tion Activity","Passive","Planned Activity","Installation Activity","Site w=
ent down due to Planned work // End of work","edwige.kapawo@matech-cameroun=
.com","70","16-05-2025 16:36:40","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005035149","Acc=
acia New","","16-05-2025 16:36:21","16-05-2025 16:25:15","16-05-2025 18:47:=
54","Grid outage .no space to deploy mobile gen// grid power returned","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age .no space to deploy mobile gen// grid power returned","loic.noumsi@mate=
ch-cameroun.com","668","16-05-2025 16:36:21","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0005035018","Mam=
bine","","16-05-2025 16:16:20","16-05-2025 16:11:09","16-05-2025 18:16:45",=
"Grid outage, site went down because gen ran untill fuel shortage // Refuel=
ling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, site went down because gen ran untill fuel shortage // Refuell=
ing done","loic.noumsi@matech-cameroun.com","312","16-05-2025 16:16:20","MA=
TECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0005034949","Eko=
mbitie","","16-05-2025 16:07:07","16-05-2025 16:02:59","16-05-2025 16:54:53=
","Grid fluctuation, Site went down because gen fails to start due to grid =
bad voltage // He bypassed the Grid and site on Gen","Fabrice Pouakam","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation, Site went down because gen fails to start due to grid bad volt=
age // He bypassed the Grid and site on Gen","loic.noumsi@matech-cameroun.c=
om","249","16-05-2025 16:07:07","MATECH CMR"
"Closed Complete","Site Down","CTR_356","IHS_YND_376","NOCINC0005034669","M=
amb","","16-05-2025 15:29:32","16-05-2025 15:19:11","16-05-2025 16:45:32","=
Grid outage gen failed t o start due battery GE faulty//Gen manually starte=
d with external battery","Kemeni Franklin","Equipment Repair","Passive","AC=
DG Gen","ACDG - Generator Battery","Grid outage gen failed t o start due ba=
ttery GE faulty//Gen manually started with external battery","loic.noumsi@m=
atech-cameroun.com","622","16-05-2025 15:29:32","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005034656","C=
rf-Nsam","","16-05-2025 15:26:21","16-05-2025 15:20:45","16-05-2025 15:42:5=
8","Active // No power issue on site Ubaie =3D53.4V site on Grid The TX FME=
 Henri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue on site Ubaie =3D53.4V site on Grid The TX FME Henri =
(699949693) from Huawei is informed","edwige.kapawo@matech-cameroun.com","3=
37","16-05-2025 15:26:21","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0005034637","Ebe=
ba","","16-05-2025 15:23:11","16-05-2025 15:15:32","16-05-2025 15:21:01","S=
ite went down due to plan work activity (Daniel Foumekong was on site to un=
block radiator) // End of Work","Fanda Brice","Installation Activity","Pass=
ive","Planned Activity","Installation Activity","Site went down due to plan=
 work activity (Daniel Foumekong was on site to unblock radiator) // End of=
 Work","loic.noumsi@matech-cameroun.com","460","16-05-2025 15:23:11","MATEC=
H CMR"
"Closed Complete","Site Down","T1112","IHS_YND_074","NOCINC0005034623","Obi=
li Chapelle","","16-05-2025 15:20:23","16-05-2025 15:05:07","16-05-2025 16:=
13:31","Grid outage, site went down because Gen failed to start due to Card=
 Ge faulty, SS IHS Francois Ndoungou is informed // He started Gen manually=
","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Grid outage, site went down because Gen failed to start due to Card Ge=
 faulty, SS IHS Francois Ndoungou is informed // He started Gen manually","=
loic.noumsi@matech-cameroun.com","916","16-05-2025 15:20:23","MATECH CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0005034589","Bye=
massi Carrefour","","16-05-2025 15:15:49","16-05-2025 15:11:09","16-05-2025=
 17:26:04","Grid outage.gen started and stopped due to low oil pressure//We=
 add oil and gen manually started","Paul BIBOUM","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Low Oil Pressure","Grid outage.gen started and stoppe=
d due to low oil pressure//We add oil and gen manually started","loic.noums=
i@matech-cameroun.com","280","16-05-2025 15:15:49","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0005034557","Efo=
ulan MTN","","16-05-2025 15:12:16","16-05-2025 15:05:59","16-05-2025 15:51:=
21","Grid outage, Site went down because Gen started and stopped with ""low=
 oil pressure"" alarm// He reset card GE and gen manually started","MINKA N=
ICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage, Site went down because Gen started and stopped with ""low oil pre=
ssure"" alarm// He reset card GE and gen manually started","edwige.kapawo@m=
atech-cameroun.com","378","16-05-2025 15:12:16","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005034443","Nta=
ba","","16-05-2025 14:48:21","16-05-2025 14:41:11","16-05-2025 17:19:11","S=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Site went down due to PWC Overload(12Kw 2=
50A) Blaise Raoul SS IHS is iformed //Site stabilised","franck.nkomot@matec=
h-cameroun.com","432","16-05-2025 14:48:21","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005034400","N=
koabang Ebolmedjock","","16-05-2025 14:41:56","16-05-2025 14:31:59","16-05-=
2025 15:20:32","No power issue Site impacted by Nkolmesseng-Abom","Mba Laza=
re Herve","Customer Equipment Failure","Active","Active Equipment Failure",=
"Affected by 3rd Party Site","No power issue Site impacted by Nkolmesseng-A=
bom","edwige.kapawo@matech-cameroun.com","598","16-05-2025 14:41:56","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0005034294","S=
calom-IHS","","16-05-2025 14:29:23","16-05-2025 14:16:21","16-05-2025 15:57=
:34","Grid outage.gen failed to tart due to ATS dysfunctionning//Gen manual=
ly started ","","Cascade Outage","Passive","Cascade Passive","Cascade Passi=
ve","Grid outage.gen failed to tart due to ATS dysfunctionning//Gen manuall=
y started ","christelle.ngonga@matech-cameroun.com","1661","16-05-2025 14:2=
9:23","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005034284","M=
ontee-Jouvence-II","","16-05-2025 14:28:40","16-05-2025 14:18:14","16-05-20=
25 15:38:42","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid Outage Site went down because Gen Overload (20KV=
A, 300A) // He reduiced The load and Manually Started the Gen","christelle.=
ngonga@matech-cameroun.com","1668461","16-05-2025 14:28:40","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005034281","D=
amas","","16-05-2025 14:28:04","16-05-2025 14:18:14","16-05-2025 15:38:42",=
"","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid Outage Site went down because Gen Overload (20KVA, 300A) // He=
 reduiced The load and Manually Started the Gen","christelle.ngonga@matech-=
cameroun.com","1668460","16-05-2025 14:28:04","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005034266","A=
ccacia New","","16-05-2025 14:25:48","16-05-2025 14:18:14","16-05-2025 15:3=
8:42","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Grid Outage Site went down because Gen Overload (20KVA, 300A) // He reduic=
ed The load and Manually Started the Gen","christelle.ngonga@matech-camerou=
n.com","1668460","16-05-2025 14:25:48","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005034255","O=
dza II OCM","","16-05-2025 14:23:53","16-05-2025 14:20:29","16-05-2025 14:2=
8:54","Grid fluctuation, Site went down because gen fails to start due to g=
rid bad voltage// Grid Stabilized","Albran Byorel","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site we=
nt down because gen fails to start due to grid bad voltage// Grid Stabilize=
d","christelle.ngonga@matech-cameroun.com","206","16-05-2025 14:23:53","MAT=
ECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0005034236","Tam=
tam Weekend","IHS_YND_562, IHS_YND_166, IHS_YND_518","16-05-2025 14:21:20",=
"16-05-2025 14:18:14","16-05-2025 15:40:29","Grid Outage Site went down bec=
ause Gen Overload (20KVA, 300A) // He reduiced The load and Manually Starte=
d the Gen","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid Outage Site went down because Gen Overload (20KVA, 300A) /=
/ He reduiced The load and Manually Started the Gen","franck.nkomot@matech-=
cameroun.com","187","16-05-2025 14:21:20","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0005034227","Sca=
lom","IHS_YND_505","16-05-2025 14:19:31","16-05-2025 14:16:21","16-05-2025 =
15:58:20","Grid outage, site went down Gen failed to start due to ATS Dysfu=
nctioning on Site // He reset ATS and started Gen manually","Paul BIBOUM","=
Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, s=
ite went down Gen failed to start due to ATS Dysfunctioning on Site // He r=
eset ATS and started Gen manually","franck.nkomot@matech-cameroun.com","191=
","16-05-2025 14:19:31","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0005034225","Ron=
d Point Express1114","","16-05-2025 14:18:53","16-05-2025 14:16:37","16-05-=
2025 14:24:23","Grid outage, Site down due to poor battery backup // Grid r=
eturn","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, Site down due to poor battery backup =
// Grid return","franck.nkomot@matech-cameroun.com","137","16-05-2025 14:18=
:53","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005034149","MBA=
LNGONG LYCEE","","16-05-2025 13:57:23","16-05-2025 13:52:13","16-05-2025 15=
:24:06","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down be=
cause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informe=
d and confirmed // Grid returned","franck.nkomot@matech-cameroun.com","312"=
,"16-05-2025 13:57:23","MATECH CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0005034130","Mba=
nkomo CAF","","16-05-2025 13:52:31","16-05-2025 13:34:22","16-05-2025 14:46=
:13","site went down because gen start an stopped due to water infiltration=
 in tank // He purged and change fuel filter ","Fanda Brice","Fuel Outage (=
Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","sit=
e went down because gen start an stopped due to water infiltration in tank =
// He purged and change fuel filter ","franck.nkomot@matech-cameroun.com","=
1090","16-05-2025 13:52:31","MATECH CMR"
"Closed Complete","Warning","T1550","IHS_YND_537","NOCINC0005034045","MEFOU=
 ASSI","","16-05-2025 13:40:18","","","Site alarming with grid outage//gen =
manually started","Fanda Brice","Warning","Warning","POWER","Warning - Batt=
ery Failure","Site alarming with grid outage//gen manually started","ange.k=
ongo@ihstowers.com","10","16-05-2025 13:40:18","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005034020","N=
koabang Ebolmedjock","","16-05-2025 13:35:07","16-05-2025 13:29:59","16-05-=
2025 13:34:59","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Gen. Notice that it is impacted b=
y Nkolmesseng-Abom(CTR-711) Not Manager By IHS","christelle.ngonga@matech-c=
ameroun.com","309","16-05-2025 13:35:07","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005034001","Eto=
ug ebe biscuiterie","","16-05-2025 13:32:14","16-05-2025 13:22:08","16-05-2=
025 13:32:08","FME Gildas and SS IHS was on site for plan work (swap of MPR=
) // End on work","Hyemafo Gildas","Installation Activity","Passive","Plann=
ed Activity","Installation Activity","FME Gildas and SS IHS was on site for=
 plan work (swap of MPR) // End on work","franck.nkomot@matech-cameroun.com=
","607","16-05-2025 13:32:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005033986","Acropole=
","","16-05-2025 13:29:58","16-05-2025 13:26:16","16-05-2025 13:30:19","Cas=
caded Incident from TTO5167115","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to insufficient of =
rectifier on site // Site stabilized","system","1658298","16-05-2025 13:29:=
58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005033987","C-Suprem=
e","","16-05-2025 13:29:58","16-05-2025 13:26:16","16-05-2025 13:30:19","Ca=
scaded Incident from TTO5167115","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site went down due to insufficient of rectifier on=
 site // Site stabilized","system","1658299","16-05-2025 13:29:58","MATECH =
CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005033976","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","16-05-2025 13:28:26","16-05-2025 1=
3:26:16","16-05-2025 13:30:19","Site went down due to insufficient of recti=
fier on site // Site stabilized","MINKA NICOLAS","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to insufficient of re=
ctifier on site // Site stabilized","kouoh.jean@ihstowers.com","130","16-05=
-2025 13:28:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005033783","C-Suprem=
e","","16-05-2025 12:56:24","16-05-2025 12:44:59","16-05-2025 12:48:59","Ca=
scaded Incident from TTO5166873","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage , site went down before Gen failed to =
started due to poor battery backup // Grid restoration","system","1660724",=
"16-05-2025 12:56:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005033782","Acropole=
","","16-05-2025 12:56:24","16-05-2025 12:44:59","16-05-2025 12:48:59","Cas=
caded Incident from TTO5166873","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage , site went down before Ge=
n failed to started due to poor battery backup // Grid restoration","system=
","1660724","16-05-2025 12:56:24","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005033780","O=
LAMA","","16-05-2025 12:56:04","16-05-2025 12:46:41","16-05-2025 12:58:11",=
"No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949=
693) from Huawei is informed.Noticed that it is a repetitve issue","Fanda B=
rice","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site Ubaie =3D54.9V site on Gen The TX =
FME Henri (699949693) from Huawei is informed.Noticed that it is a repetitv=
e issue","christelle.ngonga@matech-cameroun.com","564","16-05-2025 12:56:04=
","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005033769","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","16-05-2025 12:54:25","16-05-2025 1=
2:44:59","16-05-2025 12:48:59","","MINKA NICOLAS","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage , site went =
down before Gen failed to started due to poor battery backup // Grid restor=
ation","kouoh.jean@ihstowers.com","566","16-05-2025 12:54:25","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005033748","M=
essassi 2","","16-05-2025 12:49:50","16-05-2025 12:48:38","16-05-2025 12:49=
:23","(very unstable) Grid outage, Site went down due to 02/08 rectifiers i=
ssue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","(very unstable) Grid outage, Site w=
ent down due to 02/08 rectifiers issue // Grid stabilised","kouoh.jean@ihst=
owers.com","74","16-05-2025 12:49:50","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0005033492","M=
ANGUIERS CHAPELLE","","16-05-2025 12:10:41","16-05-2025 12:08:22","16-05-20=
25 12:32:22","Grid outage, site went down due to gen overload (22kva, 340A)=
","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Grid outage, site went down due to gen overload (22kva, 340A)","christe=
lle.ngonga@matech-cameroun.com","140","16-05-2025 12:10:41","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005033461","B=
arriere","","16-05-2025 12:08:29","16-05-2025 12:06:58","16-05-2025 12:47:5=
8","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed//Grid return","Hyemafo Gildas","Equipme=
nt Repair","Passive","DCDG Gen","DCDG - Overload","Grid outage, Site went d=
own because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and co=
nfirmed//Grid return","christelle.ngonga@matech-cameroun.com","92","16-05-2=
025 12:08:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005033453","Acropole=
","","16-05-2025 12:07:18","16-05-2025 12:02:00","16-05-2025 12:06:06","Cas=
caded Incident from TTO5166485","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage , site went down before Ge=
n failed to started due to poor battery backup // Grid restoration","system=
","1656164","16-05-2025 12:07:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005033454","C-Suprem=
e","","16-05-2025 12:07:18","16-05-2025 12:02:00","16-05-2025 12:06:06","Ca=
scaded Incident from TTO5166485","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage , site went down before Gen failed to =
started due to poor battery backup // Grid restoration","system","1656164",=
"16-05-2025 12:07:18","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005033445","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","16-05-2025 12:06:16","16-05-2025 1=
2:02:00","16-05-2025 12:06:11","Grid outage , site went down before Gen fai=
led to started due to poor battery backup // Grid restoration","MINKA NICOL=
AS","Equipment Repair","Passive","ACDG Gen","DG Low Battery","Grid outage ,=
 site went down before Gen failed to started due to poor battery backup // =
Grid restoration","christelle.ngonga@matech-cameroun.com","257","16-05-2025=
 12:06:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005033382","TSINGA V=
ILLAGE 2","","16-05-2025 11:54:21","16-05-2025 11:49:03","16-05-2025 11:52:=
04","Cascaded Incident from TTO5166388","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site, Site on =
Grid UBAIE=3D54V synphorien (675295205) From huawei is informed.","system",=
"1656933","16-05-2025 11:54:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005033381","Nkolfoul=
ou 2","","16-05-2025 11:54:21","16-05-2025 11:49:03","16-05-2025 11:52:04",=
"Cascaded Incident from TTO5166388","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site, Site on Grid =
UBAIE=3D54V synphorien (675295205) From huawei is informed.","system","1656=
934","16-05-2025 11:54:21","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005033367","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","16-05-2025 11:51:10","1=
6-05-2025 11:49:03","16-05-2025 11:52:04","No power issue on site, Site on =
Grid UBAIE=3D54V synphorien (675295205) From huawei is informed.","Siligap =
Boris","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site, Site on Grid UBAIE=3D54V synphor=
ien (675295205) From huawei is informed.","christelle.ngonga@matech-camerou=
n.com","128","16-05-2025 11:51:10","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0005033150","Nko=
abang Alembe","","16-05-2025 11:18:45","16-05-2025 11:10:24","16-05-2025 11=
:30:24","ACTIVE// No power issue on site Ubaie=3D53.5V site on Gen Lionel A=
djep /655-18-48-76 from Huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE// No power issue on site Ubaie=3D53.5V site on Gen Lionel Adjep /655=
-18-48-76 from Huawei is informed","franck.nkomot@matech-cameroun.com","501=
","16-05-2025 11:18:45","MATECH CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0005033084","T=
radex-Nkomo","","16-05-2025 11:09:36","16-05-2025 11:02:27","16-05-2025 12:=
30:27","site went down because gen start an stopped due to water infiltrati=
on in tank // He purged The tank and Gen manually started","Albran Byorel",=
"Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In =
The Fuel","site went down because gen start an stopped due to water infiltr=
ation in tank // He purged The tank and Gen manually started","christelle.n=
gonga@matech-cameroun.com","430","16-05-2025 11:09:36","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0005032951","L=
abogenie","","16-05-2025 10:43:01","16-05-2025 10:40:54","16-05-2025 10:43:=
51","Grid outage.no space to deploy mobile gen // Grid restoration","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.no space to deploy mobile gen // Grid restoration","christelle.ngonga@mate=
ch-cameroun.com","129","16-05-2025 10:43:01","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005032941","Crf=
-Mbankolo-IHS","","16-05-2025 10:41:14","16-05-2025 10:37:00","16-05-2025 1=
3:24:00","Site down due to insufficient rectifiers on site // site stabilis=
ed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site down due to insufficient rectifiers on site // site stabilised",=
"franck.nkomot@matech-cameroun.com","255","16-05-2025 10:41:14","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0005032866","C-Suprem=
e","","16-05-2025 10:29:11","16-05-2025 10:26:43","16-05-2025 10:30:06","Ca=
scaded Incident from TTO5165735","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage , site went down before Gen failed to =
started due to poor battery backup // Grid restoration","system","264918","=
16-05-2025 10:29:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0005032865","Acropole=
","","16-05-2025 10:29:11","16-05-2025 10:26:43","16-05-2025 10:30:06","Cas=
caded Incident from TTO5165735","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage , site went down before Ge=
n failed to started due to poor battery backup // Grid restoration","system=
","264919","16-05-2025 10:29:11","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005032852","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","16-05-2025 10:27:51","16-05-2025 1=
0:26:43","16-05-2025 10:30:06","Fme Nicolas is on the way eta 01:50 PM","MI=
NKA NICOLAS","Equipment Repair","Passive","ACDG Gen","DG Low Battery","Grid=
 outage , site went down before Gen failed to started due to poor battery b=
ackup // Grid restoration","christelle.ngonga@matech-cameroun.com","69","16=
-05-2025 10:27:51","MATECH CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0005032772","Bas=
tos Amb Coree","","16-05-2025 10:17:07","16-05-2025 10:13:01","17-05-2025 1=
1:26:48","Grid outage No space to deploy a mobil Gen//Grid returned","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e No space to deploy a mobil Gen//Grid returned","franck.nkomot@matech-came=
roun.com","247","16-05-2025 10:17:07","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005032743","C=
rf-Nsam","","16-05-2025 10:12:50","16-05-2025 10:07:31","16-05-2025 10:26:1=
8","Active: No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","christelle.ngonga@matech-cameroun.com","3=
20","16-05-2025 10:12:50","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005032707","ELO=
UMDEM CARRIERE","","16-05-2025 10:05:38","16-05-2025 10:02:28","16-05-2025 =
11:25:12","Site went down due to planned work on site // End of work","Fand=
a Brice","Installation Activity","Passive","Planned Activity","Installation=
 Activity","Site went down due to planned work on site // End of work","fra=
nck.nkomot@matech-cameroun.com","191","16-05-2025 10:05:38","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0005032667","Eto=
ug ebe biscuiterie","","16-05-2025 09:56:49","16-05-2025 09:55:42","16-05-2=
025 13:03:42","FME Gildas and SS IHS was on site for plan work (swap of MPR=
) // End on work","Hyemafo Gildas","Installation Activity","Passive","Plann=
ed Activity","Installation Activity","FME Gildas and SS IHS was on site for=
 plan work (swap of MPR) // End on work","franck.nkomot@matech-cameroun.com=
","68","16-05-2025 09:56:49","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0005032600","C=
rf-Nsam","","16-05-2025 09:45:01","16-05-2025 09:40:50","16-05-2025 09:45:5=
0","Active: No power issue on site Ubaie =3D53.6V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","franck.nkomot@matech-cameroun.com","253",=
"16-05-2025 09:45:01","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0005032433","Nko=
g-Edzen","","16-05-2025 09:19:38","16-05-2025 09:07:09","16-05-2025 09:25:0=
9","Active//No power issue on site, Site on Grid Ubay =3D 52.8V The Tx Fme =
Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Grid Ubay =3D 52.8V The Tx Fme Greg=
oire (654547479) from Huawei is informed.","franck.nkomot@matech-cameroun.c=
om","750","16-05-2025 09:19:38","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005032117","AKA=
K Nkozoa","","16-05-2025 08:21:40","16-05-2025 08:15:14","16-05-2025 10:05:=
14","Site went down due to insufficient rectifier // he reseted it","Fabric=
e Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","Sit=
e went down due to insufficient rectifier // he reseted it","franck.nkomot@=
matech-cameroun.com","387","16-05-2025 08:21:40","MATECH CMR"
"Closed Complete","Site Down","T0210","IHS_YND_206","NOCINC0005031900","ARM=
P","","16-05-2025 07:23:35","16-05-2025 07:16:27","16-05-2025 12:18:25","Gr=
id outage ,gen failed to start due to fuel pump faulty//Grid return","Mboua=
 Thierry","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Fuel Pump",=
"Grid outage ,gen failed to start due to fuel pump faulty//Grid return","fr=
anck.nkomot@matech-cameroun.com","428","16-05-2025 07:23:35","MATECH CMR"
"Closed Complete","Site Down","T1591","IHS_YND_172","NOCINC0005031833","Tra=
dex-Nkomo","","16-05-2025 07:02:41","16-05-2025 07:01:29","16-05-2025 07:48=
:36","site went down because gen start an stopped due to water infiltration=
 in tank // He purged The tank and Gen manually started","Albran Byorel","F=
uel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In Th=
e Fuel","site went down because gen start an stopped due to water infiltrat=
ion in tank // He purged The tank and Gen manually started","cedric.tiani@m=
atech-cameroun.com","73","16-05-2025 07:02:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0005031827","Dragage"=
,"","16-05-2025 07:00:46","16-05-2025 06:56:43","16-05-2025 08:42:50","Casc=
aded Incident from TTO5164384","Mboua Thierry","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site went down because gen failed to st=
art due to unbalanced phase causing by rectifier dysfunctionned //We balanc=
ed phases and site on gen","system","243","16-05-2025 07:00:46","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0005031828","Bastos-B=
AT","","16-05-2025 07:00:46","16-05-2025 06:56:43","16-05-2025 08:42:50","C=
ascaded Incident from TTO5164384","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because gen failed to=
 start due to unbalanced phase causing by rectifier dysfunctionned //We bal=
anced phases and site on gen","system","243","16-05-2025 07:00:46","MATECH =
CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0005031819","ARM=
P Building","IHS_YND_192, IHS_YND_129","16-05-2025 06:57:59","16-05-2025 06=
:56:43","16-05-2025 10:21:43","site went down because gen failed to start d=
ue to unbalanced phase causing by rectifier dysfunctionned //We balanced ph=
ases and site on gen","Mboua Thierry","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","site went down because gen failed to start due t=
o unbalanced phase causing by rectifier dysfunctionned //We balanced phases=
 and site on gen","cedric.tiani@matech-cameroun.com","76","16-05-2025 06:57=
:59","MATECH CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0005031806","E=
lobi Mokolo","","16-05-2025 06:52:25","16-05-2025 06:46:12","16-05-2025 07:=
20:07","Site went down because gen fails to start due to grid bad voltage /=
/ He bypass grid and manually start the gen","Mboua Thierry","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Site went down =
because gen fails to start due to grid bad voltage // He bypass grid and ma=
nually start the gen","vanel.mbiada@matech-cameroun.com","374","16-05-2025 =
06:52:25","MATECH CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0005031800","A=
RMP","","16-05-2025 06:50:59","16-05-2025 06:46:42","16-05-2025 10:18:15","=
Grid outage ,gen failed to start due to fuel pump faulty//Grid return","","=
Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Lifting Pump Faulty","G=
rid outage ,gen failed to start due to fuel pump faulty//Grid return","vane=
l.mbiada@matech-cameroun.com","258","16-05-2025 06:50:59","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005031620","SAA=
 Entrance","","16-05-2025 05:47:04","16-05-2025 01:13:54","16-05-2025 01:49=
:16","Active // No power issue on site , site on Gen , The TX FME Gr=E9goir=
e //654547479 from Huawei is informed","Parker Tchoup","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/ No power issue on site , site on Gen , The TX FME Gr=E9goire //654547479 =
from Huawei is informed","cedric.tiani@matech-cameroun.com","16392","16-05-=
2025 05:47:04","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005031618","E=
ssomba","","16-05-2025 05:45:49","16-05-2025 05:44:40","16-05-2025 08:43:54=
","Grid outage site went down because Gen failed to start due PWC overload =
// Grid return","Mba Lazare Herve","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module Overloaded","Grid outage site went down because Gen fail=
ed to start due PWC overload // Grid return","vanel.mbiada@matech-cameroun.=
com","70","16-05-2025 05:45:49","MATECH CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0005031508","S=
OA UNIVERSITY STADIUM","","16-05-2025 05:08:49","16-05-2025 04:58:50","16-0=
5-2025 05:39:34","","Siligap Boris","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, site went down because gen failed to =
start with alarm *overvoltage* // He reset gen card and gen manually starte=
d","vanel.mbiada@matech-cameroun.com","270333","16-05-2025 05:08:49","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0005031500","S=
oa-Sofamac","IHS_YND_720","16-05-2025 05:04:22","16-05-2025 04:58:50","16-0=
5-2025 05:39:34","Grid outage, site went down because gen failed to start w=
ith alarm *overvoltage* // He reset gen card and gen manually started","Sil=
igap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, site went down because gen failed to start with alarm *overvo=
ltage* // He reset gen card and gen manually started","vanel.mbiada@matech-=
cameroun.com","332","16-05-2025 05:04:22","MATECH CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0005031406","T=
radex-Nkomo","","16-05-2025 04:16:10","16-05-2025 04:12:59","16-05-2025 05:=
22:30","Grid outage, site went down because gen failed  to start due to wat=
er in the tank // He purged it and manually start the gen","Albran Byorel",=
"Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In =
The Fuel","Grid outage, site went down because gen failed  to start due to =
water in the tank // He purged it and manually start the gen","vanel.mbiada=
@matech-cameroun.com","193","16-05-2025 04:16:10","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0005031327","Mam=
bine","","16-05-2025 03:30:25","16-05-2025 03:28:05","16-05-2025 03:46:12",=
"Grid outage, site went down because gen ran untill fuel shortage // Refuel=
ling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, site went down because gen ran untill fuel shortage // Refuell=
ing done","cedric.tiani@matech-cameroun.com","141","16-05-2025 03:30:25","M=
ATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0005031250","Odz=
a petit marche new","","16-05-2025 02:57:37","16-05-2025 02:47:59","16-05-2=
025 03:41:13","Grid fluctuation,gen failed to start due to grid bad voltage=
,no rcp//He bypassed the Grid and site on Gen","Albran Byorel","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion,gen failed to start due to grid bad voltage,no rcp//He bypassed the Gri=
d and site on Gen","cedric.tiani@matech-cameroun.com","578","16-05-2025 02:=
57:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005031177","Bastos-N=
ylon","","16-05-2025 02:48:18","16-05-2025 01:45:00","16-05-2025 02:38:21",=
"Cascaded Incident from TTO5163524","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen failed to start (investigation ongoing)","system","267596","16-05-2025=
 02:48:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_311","NOCINC0005031179","Nkolda",=
"","16-05-2025 02:48:18","16-05-2025 01:45:00","16-05-2025 02:38:21","Casca=
ded Incident from TTO5163524","Albran Byorel","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage site went down because Gen f=
ailed to start (investigation ongoing)","system","267596","16-05-2025 02:48=
:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005031178","Bastos B=
ethesda","","16-05-2025 02:48:18","16-05-2025 01:45:00","16-05-2025 02:38:2=
1","Cascaded Incident from TTO5163524","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen failed to start (investigation ongoing)","system","267595","16-05-2=
025 02:48:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005031176","Golf Qua=
ter","","16-05-2025 02:48:17","16-05-2025 01:45:00","16-05-2025 02:38:21","=
Cascaded Incident from TTO5163524","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start (investigation ongoing)","system","267596","16-05-2025 =
02:48:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_298","NOCINC0005031175","Olembe",=
"","16-05-2025 02:48:17","16-05-2025 01:45:00","16-05-2025 02:38:21","Casca=
ded Incident from TTO5163524","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 failed to start (investigation ongoing)","system","267595","16-05-2025 02:=
48:17","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005031144","N=
gouetou","","16-05-2025 02:36:09","16-05-2025 02:32:02","16-05-2025 02:45:3=
0","Active // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gre=
goire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gregoire (6=
54547479) from Huawei is informed","vanel.mbiada@matech-cameroun.com","249"=
,"16-05-2025 02:36:09","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005031118","Mok=
olo Yaounde","","16-05-2025 02:24:07","16-05-2025 02:20:54","16-05-2025 02:=
30:08","Active // No power issue Ubay: 54.7V site on grid. The Tx FME Eloun=
dou Bertrand (693212405) from Huawei is informed","","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // =
No power issue Ubay: 54.7V site on grid. The Tx FME Eloundou Bertrand (6932=
12405) from Huawei is informed","cedric.tiani@matech-cameroun.com","194","1=
6-05-2025 02:24:07","MATECH CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0005031041","Tsi=
nga","IHS_YND_298, IHS_YND_220, IHS_YND_126, IHS_YND_563, IHS_YND_311","16-=
05-2025 01:48:10","16-05-2025 01:45:00","16-05-2025 02:47:25","ACCESS issue=
s during the night due to lanlord Grid outage site went down because Gen fa=
iled to start (investigation ongoing)","Mboua Thierry","Access Denial","Lea=
se Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid out=
age site went down because Gen failed to start (investigation ongoing)","ce=
dric.tiani@matech-cameroun.com","191","16-05-2025 01:48:10","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0005030996","Sac=
re Coeur Catholic Church","","16-05-2025 01:30:58","15-05-2025 14:01:15","1=
5-05-2025 14:16:09","BACTRACKING Active//No power issue, site is on Grid wi=
th Ubaie 1=3D49V and Ubaie 2=3D51.3V.. The Tx FME Brice Tsague (650214096) =
from Huawei is informed.","Mboua Thierry","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm"," Active//No power iss=
ue, site is on Grid with Ubaie 1=3D49V and Ubaie 2=3D51.3V.. The Tx FME Bri=
ce Tsague (650214096) from Huawei is informed.","vanel.mbiada@matech-camero=
un.com","41384","16-05-2025 01:30:58","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0005030927","M=
vog-Manga","","16-05-2025 01:04:33","16-05-2025 00:56:39","16-05-2025 01:16=
:50","Active// No power issue on site. Site on Grid Ubai=3D54.3 V, The FME =
TX Lionel Adjep/655184876/ From Huawei is informed","Albran Byorel","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power issue on site. Site on Grid Ubai=3D54.3 V, The FME T=
X Lionel Adjep/655184876/ From Huawei is informed","vanel.mbiada@matech-cam=
eroun.com","476","16-05-2025 01:04:33","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005030921","NKO=
MKANA ELIZA HOTEL","","16-05-2025 01:03:53","16-05-2025 00:56:41","16-05-20=
25 02:41:14","Active//No power issue, Site on Grid Ubaie: 53.6V. The Tx FME=
 Brice Tsague(650214096) from Huawei is informed.","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue, Site on Grid Ubaie: 53.6V. The Tx FME Brice Tsague(650214096=
) from Huawei is informed.","cedric.tiani@matech-cameroun.com","433","16-05=
-2025 01:03:53","MATECH CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0005030831","T=
radex-Nkomo","","16-05-2025 00:34:10","16-05-2025 00:31:09","16-05-2025 03:=
19:34","	Grid outage, site went down because gen failed to start with alarm=
 undervoltage // He reset gen card and gen manually started","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","	Grid out=
age, site went down because gen failed to start with alarm undervoltage // =
He reset gen card and gen manually started","vanel.mbiada@matech-cameroun.c=
om","182","16-05-2025 00:34:10","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005030784","Bar=
riere","","16-05-2025 00:18:57","16-05-2025 00:13:38","16-05-2025 03:28:50"=
,"Grid outage,site went down because Gen failed to start due to ATS dysfunc=
tionning//He reset it and site on Gen","Hyemafo Gildas","Equipment Repair",=
"Passive","Control Panel","ATS-AMF Issue","Grid outage,site went down becau=
se Gen failed to start due to ATS dysfunctionning//He reset it and site on =
Gen","cedric.tiani@matech-cameroun.com","435","16-05-2025 00:18:57","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005030607","O=
kola OCM","","15-05-2025 23:32:27","15-05-2025 23:26:19","15-05-2025 23:32:=
46","Active//No power issue on site site on Gen with Ubaie=3D54,5 V  FME TX=
 Mohamadou /691144435/ from Huawei (Affected by ngomo)","TIENTCHEU NZETCHIE=
U GAEL","Customer Equipment Failure","Active","Active Equipment Failure","A=
ffected by 3rd Party Site","Active//No power issue on site site on Gen with=
 Ubaie=3D54,5 V  FME TX Mohamadou /691144435/ from Huawei (Affected by ngom=
o)","vanel.mbiada@matech-cameroun.com","370","15-05-2025 23:32:27","MATECH =
CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005030596","Nko=
l-Mebanga","","15-05-2025 23:29:08","15-05-2025 23:20:57","16-05-2025 11:52=
:46","Solar only site // Solar restored","Parker Tchoup","Equipment Repair"=
,"Passive","Solar","Solar Panel Issue","Solar only site // Solar restored",=
"cedric.tiani@matech-cameroun.com","492","15-05-2025 23:29:08","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0005030502","Par=
adis Hotel","","15-05-2025 23:08:09","15-05-2025 23:06:57","15-05-2025 23:5=
1:30","Site went down due to 02/03 rectifiers dysfunction on site//He reset=
 it and site on Grid ","Siligap Boris","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to 02/03 rectifiers dysfunction=
 on site//He reset it and site on Grid ","cedric.tiani@matech-cameroun.com"=
,"73","15-05-2025 23:08:09","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005030223","F=
ouda-New","","15-05-2025 22:03:44","15-05-2025 21:27:22","15-05-2025 21:37:=
26","Active: no power issue, site is on battery with Ubaie=3D54V, Armand Ng=
uetsa(691144412) from Huawei is informed	","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: no power issue, site is on battery with Ubaie=3D54V, Armand Nguetsa(69=
1144412) from Huawei is informed	","ludivine.ngamaleu@ihstowers.com","2183"=
,"15-05-2025 22:03:44","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0005030170","F=
ouda-New","","15-05-2025 21:53:46","15-05-2025 21:45:26","15-05-2025 21:56:=
48","Active // no power issue, site is on battery with Ubaie: 54.3V, Armand=
 Nguetsa(691144412) from Huawei is informed","Delor Telezing","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive // no power issue, site is on battery with Ubaie: 54.3V, Armand Nguet=
sa(691144412) from Huawei is informed","edwige.kapawo@matech-cameroun.com",=
"501","15-05-2025 21:53:46","MATECH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0005029968","Lob=
o 2","","15-05-2025 21:09:48","15-05-2025 20:54:40","15-05-2025 23:50:04","=
Grid outage site went down because Gen failed to start due to Hybrid system=
 dysfonction // He reset the hybrid system and Gen manually started","TIENT=
CHEU NZETCHIEU GAEL","Equipment Repair","Passive","Hybrid","Hybrid Module",=
"Grid outage site went down because Gen failed to start due to Hybrid syste=
m dysfonction // He reset the hybrid system and Gen manually started","oliv=
ier.kwedi@ihstowers.com","909","15-05-2025 21:09:48","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005029898","B=
arriere","","15-05-2025 20:58:40","15-05-2025 20:55:28","15-05-2025 21:18:0=
8"," Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS F=
elix Zambe is informed and confirmed//Grid return","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload"," Grid outage, Site went=
 down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and =
confirmed//Grid return","edwige.kapawo@matech-cameroun.com","194","15-05-20=
25 20:58:40","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005029848","T=
amtam Weekend","","15-05-2025 20:50:53","15-05-2025 20:49:44","15-05-2025 2=
1:04:47","Grid fluctuation,site went down because Gen failed to start due t=
o grid bad voltage//He bypassed the grid and site on Gen","Hyemafo Gildas",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid fluctuation,site went down because Gen failed to start due to grid bad =
voltage//He bypassed the grid and site on Gen","edwige.kapawo@matech-camero=
un.com","70","15-05-2025 20:50:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0005029786","Nkolfoul=
ou 2","","15-05-2025 20:41:41","15-05-2025 20:36:11","15-05-2025 21:02:04",=
"Cascaded Incident from TTO5161981","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 DG start due to Poor Batteries backup // Grid return","system","271717","1=
5-05-2025 20:41:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005029788","TSINGA V=
ILLAGE 2","","15-05-2025 20:41:41","15-05-2025 20:36:11","15-05-2025 21:02:=
04","Cascaded Incident from TTO5161981","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
efore DG start due to Poor Batteries backup // Grid return","system","27171=
8","15-05-2025 20:41:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0005029787","Ngoulmek=
ong-Nord","","15-05-2025 20:41:41","15-05-2025 20:36:11","15-05-2025 21:02:=
04","Cascaded Incident from TTO5161981","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
fore DG start due to Poor Batteries backup // Grid return","system","271717=
","15-05-2025 20:41:41","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0005029772","N=
kolfoulou","IHS_YND_278, IHS_YND_277, IHS_YND_719","15-05-2025 20:39:20","1=
5-05-2025 20:36:11","15-05-2025 21:04:03","Grid outage, site went down befo=
re DG start due to Poor Batteries backup // Grid return","Siligap Boris","E=
quipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","G=
rid outage, site went down before DG start due to Poor Batteries backup // =
Grid return","edwige.kapawo@matech-cameroun.com","190","15-05-2025 20:39:20=
","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0005029660","ETO=
UDI Entree du palais","","15-05-2025 20:12:24","15-05-2025 20:06:18","15-05=
-2025 20:36:18","Grid outage, site went down because Gen fails to start due=
 to Gen card dysfunction // He Reset The Gen card done and Gen started","Fa=
brice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, site went down because Gen fails to start due to Gen card =
dysfunction // He Reset The Gen card done and Gen started","gerard.tchangou=
e@matech-cameroun.com","367","15-05-2025 20:12:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005029576","MEHANDAN=
","","15-05-2025 19:52:34","15-05-2025 19:43:13","15-05-2025 21:41:05","Cas=
caded Incident from TTO5161741","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n start and stopped with alarm ""Over voltage""(unprouven Alarm)// He reset=
 Gen card and Gen manually started","system","274692","15-05-2025 19:52:34"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005029573","O=
dza II OCM","IHS_YND_528","15-05-2025 19:51:22","15-05-2025 19:43:13","15-0=
5-2025 21:41:05","Grid outage, site went down because gen start and stopped=
 with alarm ""Over voltage""(unprouven Alarm)// He reset Gen card and Gen m=
anually started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","A=
CDG - Control Panel","Grid outage, site went down because gen start and sto=
pped with alarm ""Over voltage""(unprouven Alarm)// He reset Gen card and G=
en manually started","edwige.kapawo@matech-cameroun.com","491","15-05-2025 =
19:51:22","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005029495","Mes=
sassi 2","","15-05-2025 19:32:34","15-05-2025 19:27:22","15-05-2025 22:15:1=
6","(very unstable) Grid outage, Site went down due to 02/08 rectifiers iss=
ue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Grid outage, Site went down due to 02/08 rectifi=
ers issue // Grid stabilised","gerard.tchangoue@matech-cameroun.com","314",=
"15-05-2025 19:32:34","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005029274","Crf=
-Mbankolo-IHS","","15-05-2025 18:59:04","15-05-2025 18:52:56","15-05-2025 2=
1:02:57","Site down due to insufficient rectifiers on site // site stabilis=
ed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site down due to insufficient rectifiers on site // site stabilised",=
"gerard.tchangoue@matech-cameroun.com","369","15-05-2025 18:59:04","MATECH =
CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005029157","Acc=
acia New","","15-05-2025 18:43:10","15-05-2025 18:39:00","15-05-2025 18:47:=
34","Grid outage, no space to deploy a mobil gen // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, n=
o space to deploy a mobil gen // Grid return","gerard.tchangoue@matech-came=
roun.com","252","15-05-2025 18:43:10","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005029118","Bar=
riere","","15-05-2025 18:37:12","15-05-2025 18:28:43","15-05-2025 19:50:36"=
,"Site went Down due to Work Gildas (656040578/Matech ) was on site for wor=
k (Swap Gen) // End of works Gen swap (30KVA)","Hyemafo Gildas","Equipment =
Replacement","Passive","Planned Activity","Planned Activity - Passive","Sit=
e went Down due to Work Gildas (656040578/Matech ) was on site for work (Sw=
ap Gen) // End of works Gen swap (30KVA)","gerard.tchangoue@matech-cameroun=
.com","509","15-05-2025 18:37:12","MATECH CMR"
"Closed Complete","Site Down","CTR_234","IHS_YND_415","NOCINC0005028519","B=
oga-Mahole","","15-05-2025 17:33:27","15-05-2025 16:37:05","15-05-2025 20:2=
0:35","Active//No power issue site on Grid with U=3D50,6V The Tx Fme Etienn=
e fopa // 695033981// of huawei is informed","Kemeni Franklin","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue site on Grid with U=3D50,6V The Tx Fme Etienne fopa =
// 695033981// of huawei is informed","ludivine.ngamaleu@ihstowers.com","33=
83","15-05-2025 17:33:27","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0005028480","O=
mnisport-Rail","","15-05-2025 17:25:13","15-05-2025 17:24:06","15-05-2025 1=
9:12:35","Grid outage, site went down because gen failed to start due to PW=
C malfunction // He reset controller and gen manually started","Delor Telez=
ing","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded"=
,"Grid outage, site went down because gen failed to start due to PWC malfun=
ction // He reset controller and gen manually started","edwige.kapawo@matec=
h-cameroun.com","69","15-05-2025 17:25:13","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0005028382","S=
calom","","15-05-2025 17:12:34","15-05-2025 17:11:27","15-05-2025 17:16:16"=
,"Site went down  due to grid bad voltage // Grid stabilized","Paul BIBOUM"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Site went down  due to grid bad voltage // Grid stabilized","edwige.kapawo@=
matech-cameroun.com","68","15-05-2025 17:12:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_750","NOCINC0005028318","Nkoabang=
 entree carriere","","15-05-2025 17:04:34","15-05-2025 16:41:57","15-05-202=
5 20:56:07","Cascaded Incident from TTO5160354","Mba Lazare Herve","Cascade=
 Outage","Passive","Cascade Passive","Cascade Passive","Site went down beca=
use cable of the DC BOX is damaged // We took the source from the other DC =
box to power it","system","285819","15-05-2025 17:04:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0005028317","Nkoabang=
2","","15-05-2025 17:04:34","15-05-2025 16:41:57","15-05-2025 20:56:07","Ca=
scaded Incident from TTO5160354","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because cable of th=
e DC BOX is damaged // We took the source from the other DC box to power it=
","system","285818","15-05-2025 17:04:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0005028319","Biteng",=
"","15-05-2025 17:04:34","15-05-2025 16:41:57","15-05-2025 20:56:07","Casca=
ded Incident from TTO5160354","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down because cable of the D=
C BOX is damaged // We took the source from the other DC box to power it","=
system","285820","15-05-2025 17:04:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0005028315","NGONA","=
","15-05-2025 17:04:33","15-05-2025 16:41:57","15-05-2025 20:56:07","Cascad=
ed Incident from TTO5160354","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because cable of the DC=
 BOX is damaged // We took the source from the other DC box to power it","s=
ystem","285818","15-05-2025 17:04:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0005028316","Biteng-M=
aetur","","15-05-2025 17:04:33","15-05-2025 16:41:57","15-05-2025 20:56:07"=
,"Cascaded Incident from TTO5160354","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down because cable o=
f the DC BOX is damaged // We took the source from the other DC box to powe=
r it","system","285818","15-05-2025 17:04:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005028278","Emana Ly=
cee","","15-05-2025 17:00:40","15-05-2025 16:55:56","15-05-2025 17:11:05","=
Cascaded Incident from TTO5160465","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down befo=
re Gen failed to started due to poor battery backup // gen automaticaly sta=
rt.","system","270417","15-05-2025 17:00:40","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005028276","E=
mana lycee 2","IHS_YND_274","15-05-2025 17:00:01","15-05-2025 16:55:56","15=
-05-2025 17:12:47","Grid outage , site went down before Gen failed to start=
ed due to poor battery backup // gen automaticaly start.","Fabrice Pouakam"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"Grid outage , site went down before Gen failed to started due to poor bat=
tery backup // gen automaticaly start.","edwige.kapawo@matech-cameroun.com"=
,"246","15-05-2025 17:00:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0005028221","Boumnyeb=
el","","15-05-2025 16:54:12","15-05-2025 16:31:35","15-05-2025 16:32:33","C=
ascaded Incident from TTO5160313","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Cascaded Incident from TTO5160313","s=
ystem","1357","15-05-2025 16:54:12","MATECH CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0005028210","S=
cience","","15-05-2025 16:53:35","15-05-2025 16:43:59","15-05-2025 17:35:59=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage and no rcp on site // he bypassed grid and manually start th=
e gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","Grid fluctuation, site went down because g=
en start and stopped due to grid bad voltage and no rcp on site // he bypas=
sed grid and manually start the gen","edwige.kapawo@matech-cameroun.com","5=
77","15-05-2025 16:53:35","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0005028164","NKO=
ABANG NKOLO 3","IHS_YND_295, IHS_YND_249, IHS_YND_526, IHS_YND_750, IHS_YND=
_795, IHS_YND_248","15-05-2025 16:50:13","15-05-2025 16:41:57","15-05-2025 =
20:56:07","Site went down because cable of the DC BOX is damaged // We took=
 the source from the other DC box to power it (Site impacted by NKOABANG T0=
058)","Mba Lazare Herve","Equipment Repair","Passive","Infrastructure","Arm=
oured Cable","Site went down because cable of the DC BOX is damaged // We t=
ook the source from the other DC box to power it (Site impacted by NKOABANG=
 T0058)","gerard.tchangoue@matech-cameroun.com","497","15-05-2025 16:50:13"=
,"MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005028147","Lad=
a I Yde","","15-05-2025 16:47:45","15-05-2025 16:41:57","15-05-2025 20:56:0=
7","tx Awaiting evidences","Mba Lazare Herve","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down because cable of the DC B=
OX is damaged // We took the source from the other DC box to power it","ger=
ard.tchangoue@matech-cameroun.com","285819","15-05-2025 16:47:45","MATECH C=
MR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005028133","S=
IMBOCK BONAMBAPE","","15-05-2025 16:45:45","15-05-2025 16:42:31","15-05-202=
5 20:22:09","Active // No power issue site on grid with Ubaie: 54.5V TX FME=
 Flubert (654266068) from Huawei is informed","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue site on grid with Ubaie: 54.5V TX FME Flubert (654=
266068) from Huawei is informed","edwige.kapawo@matech-cameroun.com","195",=
"15-05-2025 16:45:45","MATECH CMR"
"Closed Complete","Site Down","T0139","IHS_YND_381","NOCINC0005028120","Bou=
mnyebel","","15-05-2025 16:44:33","15-05-2025 16:35:59","15-05-2025 16:46:5=
6","No power issue site on Battery with U=3D54.5v Etienne(695033981) from H=
uawei is informed","Kemeni Franklin","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on Bat=
tery with U=3D54.5v Etienne(695033981) from Huawei is informed","gerard.tch=
angoue@matech-cameroun.com","515","15-05-2025 16:44:33","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0005028025","Men=
dong Plateau","","15-05-2025 16:30:01","15-05-2025 15:53:51","15-05-2025 17=
:07:33","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and manually start the gen","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, site=
 went down because gen start and stopped with high temp alarm // He added w=
ater and manually start the gen","gerard.tchangoue@matech-cameroun.com","21=
71","15-05-2025 16:30:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0005027806","Mbedoumo=
u - Ekali","","15-05-2025 15:54:55","15-05-2025 15:16:35","15-05-2025 16:00=
:32","Cascaded Incident from TTO5159715","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Gen failed to start due to grid bad voltage No Rcp// He bypasse=
d grid and started Gen manually","system","269141","15-05-2025 15:54:55","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0005027713","N=
omayos montee Meche","","15-05-2025 15:39:23","15-05-2025 15:33:59","15-05-=
2025 16:50:59","Grid outage, Site went down due to fuell shortage // Grid r=
eturn ( refulling ongoing)","Fanda Brice","Fuel Outage","Passive","Diesel",=
"Diesel Outage","Grid outage, Site went down due to fuell shortage // Grid =
return ( refulling ongoing)","edwige.kapawo@matech-cameroun.com","325","15-=
05-2025 15:39:23","MATECH CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0005027700","A=
cropole","","15-05-2025 15:36:07","15-05-2025 15:34:59","15-05-2025 17:10:1=
9","Active // No power issue, Ubay=3D53. 8V Site on Grid The TX FME Armand =
(691144412) from Huawei is informed","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // =
No power issue, Ubay=3D53. 8V Site on Grid The TX FME Armand (691144412) fr=
om Huawei is informed","edwige.kapawo@matech-cameroun.com","69","15-05-2025=
 15:36:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0005027613","MBIMBIM"=
,"","15-05-2025 15:25:21","19-05-2025 15:44:35","19-05-2025 17:48:57","Hybr=
id Gen site, site went down because Gen started and stopped due to iBattery=
 coast not well fixed// He fixed it well","Parker Tchoup","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Hybrid Gen site, site went d=
own because Gen started and stopped due to iBattery coast not well fixed// =
He fixed it well","system","1664374","15-05-2025 15:25:21","MATECH CMR"
"Cancelled","Site Down","","IHS_YND_454","NOCINC0005027607","Ngouetou","","=
15-05-2025 15:25:20","","","Cascaded Incident from TTO5159572","Parker Tcho=
up","Cascade Outage","","","","","system","0","15-05-2025 15:25:20","MATECH=
 CMR"
"Cancelled","Site Down","","IHS_YND_474","NOCINC0005027602","Yoko OCM","","=
15-05-2025 15:25:18","","","Cascaded Incident from TTO5159572","Parker Tcho=
up","Cascade Outage","","","","","system","0","15-05-2025 15:25:18","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005027601","Matsari"=
,"","15-05-2025 15:25:18","16-05-2025 22:43:45","17-05-2025 05:22:46","Casc=
aded Incident from TTO5159572","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, Site went down because Gen=
 failed to start due to battery charger HS // He reconnected it","system","=
1675247","15-05-2025 15:25:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005027595","Ngoum","=
","15-05-2025 15:25:17","16-05-2025 22:43:45","17-05-2025 05:22:46","Cascad=
ed Incident from TTO5159572","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because Gen f=
ailed to start due to battery charger HS // He reconnected it","system","16=
75248","15-05-2025 15:25:17","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005027558","N=
kolfon Cimencam","","15-05-2025 15:21:35","15-05-2025 15:14:27","15-05-2025=
 15:24:07","No power issue, Site impacted by Afanoya-II","Hyemafo Gildas","=
Customer Equipment Failure","Active","Active Equipment Failure","Affected b=
y 3rd Party Site","No power issue, Site impacted by Afanoya-II","edwige.kap=
awo@matech-cameroun.com","430","15-05-2025 15:21:35","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0005027544","Nko=
lnda","IHS_YND_343, IHS_YND_536, IHS_YND_723, IHS_YND_385, IHS_YND_528, IHS=
_YND_553, IHS_YND_410, IHS_EBO_015, IHS_YND_344","15-05-2025 15:20:14","15-=
05-2025 15:16:35","15-05-2025 16:00:32","Grid fluctuation, site went down b=
ecause Gen failed to start due to grid bad voltage No Rcp// He bypassed gri=
d and started Gen manually","Albran Byorel","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid fluctuation, site went down=
 because Gen failed to start due to grid bad voltage No Rcp// He bypassed g=
rid and started Gen manually","gerard.tchangoue@matech-cameroun.com","220",=
"15-05-2025 15:20:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005027543","MEHANDAN=
","","15-05-2025 15:20:08","15-05-2025 15:15:25","15-05-2025 16:00:32","Cas=
caded Incident from TTO5159694","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se Gen failed to start due to grid bad voltage No Rcp// He bypassed grid an=
d started Gen manually","system","269214","15-05-2025 15:20:08","MATECH CMR=
"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005027525","O=
dza II OCM","IHS_YND_528","15-05-2025 15:18:36","15-05-2025 15:15:25","15-0=
5-2025 16:07:12","Grid fluctuation, Site went down because gen fails to sta=
rt due to grid bad voltage// Grid Stabilized","Albran Byorel","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on, Site went down because gen fails to start due to grid bad voltage// Gri=
d Stabilized","edwige.kapawo@matech-cameroun.com","194","15-05-2025 15:18:3=
6","MATECH CMR"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0005027461","Ngo=
g Mapubi","","15-05-2025 15:09:34","15-05-2025 15:02:13","15-05-2025 20:23:=
12","Active// No power issue on site ,site on Grid with Ubaie=3D 54V The fm=
e tx Etienne fopa // 695033981// of huawei is informed","Kemeni Franklin","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active// No power issue on site ,site on Grid with Ubaie=3D 54V =
The fme tx Etienne fopa // 695033981// of huawei is informed","gerard.tchan=
goue@matech-cameroun.com","441","15-05-2025 15:09:34","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005027222","B=
arriere IHS","","15-05-2025 14:25:46","15-05-2025 14:18:38","15-05-2025 17:=
30:36","Active // No power issue on site Ubaie =3D 53.6V Site on Grid ,FME =
TX Flubert (654266068) from HUAWEI is informed","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue on site Ubaie =3D 53.6V Site on Grid ,FME TX Flu=
bert (654266068) from HUAWEI is informed","christelle.ngonga@matech-camerou=
n.com","429","15-05-2025 14:25:46","MATECH CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0005027071","B=
otmakak","","15-05-2025 13:59:08","15-05-2025 13:30:01","15-05-2025 14:57:4=
8","Active// No power issue, Site on Grid Ubai=3D 54V, The Tx Etienne (6950=
33981/Huawei) is informed	","Kemeni Franklin","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power=
 issue, Site on Grid Ubai=3D 54V, The Tx Etienne (695033981/Huawei) is info=
rmed	","christelle.ngonga@matech-cameroun.com","1748","15-05-2025 13:59:08"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0005026933","N=
kolso","","15-05-2025 13:37:57","15-05-2025 13:37:51","15-05-2025 14:41:38"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage// He bypasse the Grid and site on Gen","TIENTCHEU NZETCHIEU GAEL=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation, Site went down because gen fails to start due to grid ba=
d voltage// He bypasse the Grid and site on Gen","christelle.ngonga@matech-=
cameroun.com","6","15-05-2025 13:37:57","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005026818","M=
EFOU ASSI","","15-05-2025 13:20:12","15-05-2025 11:40:48","15-05-2025 16:43=
:55","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","No power issue site on Gen with Ubaie: 53.6V TX FME Flubert (654266=
068) from Huawei is informed","christelle.ngonga@matech-cameroun.com","2822=
96","15-05-2025 13:20:12","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0005026792","ODZ=
A MINKAN EDIBI ASSI","","15-05-2025 13:14:46","15-05-2025 12:45:34","15-05-=
2025 14:41:35","Eneo Outage, site went down due to  ``under voltage`` Alarm=
 // he reset it and Start Gen manually","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Eneo Outage, site went down du=
e to  ``under voltage`` Alarm // he reset it and Start Gen manually","franc=
k.nkomot@matech-cameroun.com","1753","15-05-2025 13:14:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0005026776","AWAE OCM=
","","15-05-2025 13:11:10","15-05-2025 12:52:34","15-05-2025 13:06:34","Cas=
caded Incident from TTO5158886","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen started and stopped with ""low oil pressure"" alarm// He reset card GE=
 and gen manually started","system","277780","15-05-2025 13:11:10","MATECH =
CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0005026771","Nko=
mo II","IHS_YND_173","15-05-2025 13:09:31","15-05-2025 12:52:34","15-05-202=
5 13:06:34","Grid outage, Site went down because Gen started and stopped wi=
th ""low oil pressure"" alarm// He reset card GE and gen manually started",=
"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pre=
ssure","Grid outage, Site went down because Gen started and stopped with ""=
low oil pressure"" alarm// He reset card GE and gen manually started","fran=
ck.nkomot@matech-cameroun.com","1017","15-05-2025 13:09:31","MATECH CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0005026655","Nko=
lbisson usine des eaux","","15-05-2025 12:49:30","15-05-2025 12:44:18","15-=
05-2025 12:49:18","Active: No power issue site on gen with U=3D53V Mohamado=
u (691144135) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active: No power issue site on gen with U=3D53V Mohamadou (691144135) fr=
om Huawei is informed","franck.nkomot@matech-cameroun.com","313","15-05-202=
5 12:49:30","MATECH CMR"
"Closed Complete","Site Down","T3446","IHS_YND_712","NOCINC0005026639","Nko=
lkoumou OCM","","15-05-2025 12:47:14","15-05-2025 12:44:06","15-05-2025 12:=
50:06","No power issue site on gen with U=3D50v Mohamadou(691144435) from H=
uawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on gen with U=3D50v Mohamadou(691144435) from Huawei is informed.","fra=
nck.nkomot@matech-cameroun.com","188","15-05-2025 12:47:14","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0005026628","EMA=
NA BILICK CITY","IHS_YND_279","15-05-2025 12:45:27","15-05-2025 12:37:04","=
15-05-2025 14:17:04","Grid outage, site down because site behaves as Grid o=
nly site (no Gen) //Grid return","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid outage, site down because =
site behaves as Grid only site (no Gen) //Grid return","franck.nkomot@matec=
h-cameroun.com","588","15-05-2025 12:45:27","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005026626","M=
essassi okolo","","15-05-2025 12:45:08","15-05-2025 12:37:04","15-05-2025 1=
4:13:04","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site down because site behaves as Grid only=
 site (no Gen) //Grid return","christelle.ngonga@matech-cameroun.com","2787=
24","15-05-2025 12:45:08","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005026610","M=
EHANDAN","","15-05-2025 12:42:16","15-05-2025 12:26:08","15-05-2025 12:56:1=
7","No power issue on site ,site on Grid with Ubaie=3D54 V the TX fme Lione=
l /655184876 from huawei is Informed site Impacted by Odza 2","Albran Byore=
l","Customer Equipment Failure","Active","Active Equipment Failure","Affect=
ed by 3rd Party Site","No power issue on site ,site on Grid with Ubaie=3D54=
 V the TX fme Lionel /655184876 from huawei is Informed site Impacted by Od=
za 2","christelle.ngonga@matech-cameroun.com","970","15-05-2025 12:42:16","=
MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0005026601","Dag=
obert","","15-05-2025 12:41:23","15-05-2025 12:35:17","15-05-2025 12:53:17"=
,"Active: No power issue, site is on Grid with Ubaie=3D54,7V, mohamadou//69=
1144435 from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue, site is on Grid with Ubaie=3D54,7V, mohamadou//691144=
435 from Huawei is informed.","franck.nkomot@matech-cameroun.com","367","15=
-05-2025 12:41:23","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005026595","Men=
dong3","","15-05-2025 12:40:19","15-05-2025 12:37:11","15-05-2025 12:47:11"=
,"Grid outage no space to deploy a MDG// Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage no space to d=
eploy a MDG// Grid return","franck.nkomot@matech-cameroun.com","189","15-05=
-2025 12:40:19","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0005026566","SIM=
BOCK BONAMBAPE","","15-05-2025 12:38:45","15-05-2025 12:35:36","15-05-2025 =
12:39:36","Grid outage, Site went down before Gen start due to poor backup =
// Gen automatically started","Hyemafo Gildas","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor backup // Gen automatically started","franck.=
nkomot@matech-cameroun.com","190","15-05-2025 12:38:45","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005026536","M=
efou-Assi","IHS_YND_537","15-05-2025 12:35:04","15-05-2025 11:40:48","15-05=
-2025 16:43:55","No power issue site on Gen with Ubaie: 53.6V TX FME Fluber=
t (654266068) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue site on Gen with Ubaie: 53.6V TX FME Flubert (654266068) from Huawei i=
s informed","christelle.ngonga@matech-cameroun.com","3257","15-05-2025 12:3=
5:04","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005026534","Ako=
k Ndoe Yde","","15-05-2025 12:34:55","15-05-2025 12:31:45","15-05-2025 15:0=
1:13","Grid fluctuation, site went down because gen failed to start due to =
grid bad voltage No Rcp on site // He bypassed Grid and started Gen manualy=
","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation, site went down because gen failed to st=
art due to grid bad voltage No Rcp on site // He bypassed Grid and started =
Gen manualy","franck.nkomot@matech-cameroun.com","191","15-05-2025 12:34:55=
","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0005026531","AFE=
ME NORD","","15-05-2025 12:34:04","15-05-2025 12:28:46","15-05-2025 12:54:4=
6","Site Went down due to Grid fluctuation // Grid Stabilized","TIENTCHEU N=
ZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Site Went down due to Grid fluctuation // Grid Stabilized","f=
ranck.nkomot@matech-cameroun.com","319","15-05-2025 12:34:04","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005026528","Odz=
a II OCM","","15-05-2025 12:33:14","15-05-2025 12:29:03","15-05-2025 12:56:=
03","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction // Grid return","Albran Byorel","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Grid outage, site went down becau=
se gen failed to start due to PWC ZTE malfunction // Grid return","franck.n=
komot@matech-cameroun.com","252","15-05-2025 12:33:14","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0005026522","N=
kolafeme","","15-05-2025 12:32:53","15-05-2025 12:26:44","15-05-2025 12:45:=
25","Grid outage, site went down due to grid fluctuations and no automatism=
 on Gen // Grid returned","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid outage, site went =
down due to grid fluctuations and no automatism on Gen // Grid returned","c=
hristelle.ngonga@matech-cameroun.com","370","15-05-2025 12:32:53","MATECH C=
MR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005026490","Mes=
sassi 2","","15-05-2025 12:27:24","15-05-2025 12:18:09","15-05-2025 12:28:0=
9","Grid outage site went down because Gen failed to start due to poor Batt=
ery backup// Grid power return","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage site went do=
wn because Gen failed to start due to poor Battery backup// Grid power retu=
rn","franck.nkomot@matech-cameroun.com","557","15-05-2025 12:27:24","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0005026417","E=
toudi","","15-05-2025 12:21:13","15-05-2025 12:17:33","15-05-2025 12:21:06"=
,"Grid Low voltage ,site went down because Gen fails to start due to grid l=
ow voltage //Gen manually started","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Low Current Supply","Grid Low voltage ,site went =
down because Gen fails to start due to grid low voltage //Gen manually star=
ted","christelle.ngonga@matech-cameroun.com","220","15-05-2025 12:21:13","M=
ATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005026371","ELO=
UMDEM CARRIERE","","15-05-2025 12:12:55","15-05-2025 12:11:27","15-05-2025 =
12:43:27","Grid outage site went down before Gen started due to poor batter=
y back up // Gen automatically started","Fanda Brice","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage site wen=
t down before Gen started due to poor battery back up // Gen automatically =
started","franck.nkomot@matech-cameroun.com","90","15-05-2025 12:12:55","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0005026277","S=
calom","","15-05-2025 11:59:36","15-05-2025 11:55:28","15-05-2025 12:00:34"=
,"Grid outage, site went down because Gen failed to start due to PWC ZTE ma=
lfunction // Grid restoration","Paul BIBOUM","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Grid outage, site went down because Gen fail=
ed to start due to PWC ZTE malfunction // Grid restoration","christelle.ngo=
nga@matech-cameroun.com","249","15-05-2025 11:59:36","MATECH CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0005026260","A=
cropole","","15-05-2025 11:56:23","15-05-2025 11:51:53","15-05-2025 12:16:2=
4","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage , site went down before Gen failed to started due to=
 poor battery backup , Gen automaticaly start","christelle.ngonga@matech-ca=
meroun.com","328","15-05-2025 11:56:23","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005026258","C=
-Supreme","","15-05-2025 11:55:20","15-05-2025 11:51:53","15-05-2025 12:16:=
24","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage , site went down before Gen failed to started due to poor batter=
y backup , Gen automaticaly start","christelle.ngonga@matech-cameroun.com",=
"361","15-05-2025 11:55:20","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005026250","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","15-05-2025 11:54:01","15-05-2025 1=
1:51:53","15-05-2025 12:16:24","Grid outage , site went down before Gen fai=
led to started due to poor battery backup , Gen automaticaly start","MINKA =
NICOLAS","Equipment Repair","Passive","ACDG Gen","DG Low Battery","Grid out=
age , site went down before Gen failed to started due to poor battery backu=
p , Gen automaticaly start","christelle.ngonga@matech-cameroun.com","129","=
15-05-2025 11:54:01","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0005026009","Ole=
mbe MTN","","15-05-2025 11:20:02","15-05-2025 11:11:52","15-05-2025 12:42:5=
2","Grid fluctuation.site went down due to CB Gen disjuncted//We rearmed th=
e CB","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Circuit Breaker Issue","Grid fluctuation.site went down due to C=
B Gen disjuncted//We rearmed the CB","franck.nkomot@matech-cameroun.com","4=
91","15-05-2025 11:20:02","MATECH CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0005025860","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","15-05-2025 10:56:50","15-05-2025 1=
0:54:43","15-05-2025 10:59:00","Grid outage , site went down before Gen fai=
led to started due to poor battery backup // Gen automaticaly started","MIN=
KA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batte=
ry","Grid outage , site went down before Gen failed to started due to poor =
battery backup // Gen automaticaly started","christelle.ngonga@matech-camer=
oun.com","128","15-05-2025 10:56:50","MATECH CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0005025858","A=
cropole","","15-05-2025 10:56:16","15-05-2025 10:54:43","15-05-2025 10:59:0=
0","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage , site went down before Gen failed to started due to=
 poor battery backup // Gen automaticaly started","christelle.ngonga@matech=
-cameroun.com","263535","15-05-2025 10:56:16","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005025792","C=
-Supreme","","15-05-2025 10:45:35","15-05-2025 10:54:43","15-05-2025 10:59:=
00","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage , site went down before Gen failed to started due to poor batter=
y backup // Gen automaticaly started","christelle.ngonga@matech-cameroun.co=
m","263535","15-05-2025 10:45:35","MATECH CMR"
"Closed Complete","Site Down","T1112","IHS_YND_074","NOCINC0005025639","Obi=
li Chapelle","","15-05-2025 10:20:37","15-05-2025 09:03:36","15-05-2025 10:=
42:36","Grid Outage Site went down because Gen stopped with alarm "" emerge=
ncy stop"" //He Reset the Gen Card and Gen manually started","Paul BIBOUM",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid Outag=
e Site went down because Gen stopped with alarm "" emergency stop"" //He Re=
set the Gen Card and Gen manually started","franck.nkomot@matech-cameroun.c=
om","4622","15-05-2025 10:20:37","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005025608","A=
ccacia New","","15-05-2025 10:16:10","15-05-2025 10:15:03","15-05-2025 14:3=
0:18","Grid outage, no space to deploy a mobil gen // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 no space to deploy a mobil gen // Grid return","christelle.ngonga@matech-c=
ameroun.com","68","15-05-2025 10:16:10","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005025603","E=
ssomba","","15-05-2025 10:15:06","15-05-2025 10:13:59","15-05-2025 10:18:07=
","Site went down because 03/06 rectifiers dysfunctionned // Grid  restorat=
ion","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down because 03/06 rectifiers dysfunctionned // Grid  r=
estoration","christelle.ngonga@matech-cameroun.com","69","15-05-2025 10:15:=
06","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005025585","Nom=
ayos montee Meche","","15-05-2025 10:10:44","15-05-2025 08:53:11","15-05-20=
25 10:41:11","Grid outage, Site went down because Gen started and stopped w=
ith ""over voltage"" alarm// He reset Gen card and started manually","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage, Site went down because Gen started and stopped with ""over voltag=
e"" alarm// He reset Gen card and started manually","franck.nkomot@matech-c=
ameroun.com","4654","15-05-2025 10:10:44","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005025555","E=
mana lycee 2","","15-05-2025 10:04:56","15-05-2025 10:04:47","15-05-2025 14=
:27:26","Grid outage , site went down before Gen failed to started due to p=
oor battery backup // gen automaticaly start.","Fabrice Pouakam","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge , site went down before Gen failed to started due to poor battery backup=
 // gen automaticaly start.","christelle.ngonga@matech-cameroun.com","10","=
15-05-2025 10:04:56","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0005025429","S=
imbock OCM","","15-05-2025 09:41:54","15-05-2025 09:11:50","15-05-2025 09:4=
0:16","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","Casca=
de Active","Site impacted by Nkozie wich is not manage by IHS","christelle.=
ngonga@matech-cameroun.com","262214","15-05-2025 09:41:54","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0005025341","C=
RH-Etoug-Ebe","","15-05-2025 09:27:21","15-05-2025 09:11:50","15-05-2025 09=
:40:16","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","Cas=
cade Active","Site impacted by Nkozie wich is not manage by IHS","christell=
e.ngonga@matech-cameroun.com","262211","15-05-2025 09:27:21","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005025278","M=
endong vallee","","15-05-2025 09:14:33","15-05-2025 09:11:50","15-05-2025 0=
9:40:16","","Fanda Brice","Cascade Outage","Active","Cascade Active","Casca=
de Active","Site impacted by Nkozie wich is not manage by IHS","christelle.=
ngonga@matech-cameroun.com","262212","15-05-2025 09:14:33","MATECH CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0005025268","M=
aison-Blanche-IHS","IHS_YND_692, IHS_YND_229, IHS_YND_537, IHS_YND_264, IHS=
_YND_520, IHS_YND_143, IHS_YND_258","15-05-2025 09:13:56","15-05-2025 09:11=
:50","15-05-2025 09:40:16","Site impacted by Nkozie wich is not manage by I=
HS","","Customer Equipment Failure","Active","Active Equipment Failure","Af=
fected by 3rd Party Site","Site impacted by Nkozie wich is not manage by IH=
S","christelle.ngonga@matech-cameroun.com","126","15-05-2025 09:13:56","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0005025248","B=
yemassi Carrefour","","15-05-2025 09:11:42","15-05-2025 09:11:50","15-05-20=
25 09:40:16","","Paul BIBOUM","Cascade Outage","Active","Cascade Active","C=
ascade Active","Site impacted by Nkozie wich is not manage by IHS","christe=
lle.ngonga@matech-cameroun.com","262215","15-05-2025 09:11:42","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005025238","M=
efou-Assi","","15-05-2025 09:10:39","15-05-2025 09:11:50","15-05-2025 09:40=
:16","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","Site impacted by Nkozie wich is not manage by IHS","christelle.ngon=
ga@matech-cameroun.com","262213","15-05-2025 09:10:39","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005025234","S=
IMBOCK BONAMBAPE","","15-05-2025 09:10:00","15-05-2025 09:11:50","15-05-202=
5 09:40:16","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active",=
"Cascade Active","Site impacted by Nkozie wich is not manage by IHS","chris=
telle.ngonga@matech-cameroun.com","262214","15-05-2025 09:10:00","MATECH CM=
R"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005025229","M=
EFOU ASSI","","15-05-2025 09:09:01","15-05-2025 09:11:50","15-05-2025 09:40=
:16","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","Site impacted by Nkozie wich is not manage by IHS","christelle.ngon=
ga@matech-cameroun.com","262211","15-05-2025 09:09:01","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0005025055","C=
RH-Etoug-Ebe","","15-05-2025 08:37:49","15-05-2025 08:37:45","15-05-2025 08=
:38:50","No power issue, site is on grid with Ubaie=3D52.1V, mohamadou(6911=
44435) from Huawei is informed","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
, site is on grid with Ubaie=3D52.1V, mohamadou(691144435) from Huawei is i=
nformed","christelle.ngonga@matech-cameroun.com","5","15-05-2025 08:37:49",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0005025052","M=
aison-Blanche-IHS","","15-05-2025 08:37:21","15-05-2025 08:35:14","15-05-20=
25 08:35:57","No power issue , Ubaie: 54 V  site on Grid. The FME TX Mbah H=
osiah (674007438) from Huawei is informed","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue , =
Ubaie: 54 V  site on Grid. The FME TX Mbah Hosiah (674007438) from Huawei i=
s informed","christelle.ngonga@matech-cameroun.com","128","15-05-2025 08:37=
:21","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0005025047","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","15-05-2025 08:35:57","15=
-05-2025 08:32:51","15-05-2025 08:37:08","Site down due to rectifier issue =
 // Site stabilisation ","Albran Byorel","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Site down due to rectifier issue  // Site stabil=
isation ","christelle.ngonga@matech-cameroun.com","187","15-05-2025 08:35:5=
7","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005025046","O=
dza II OCM","","15-05-2025 08:35:27","15-05-2025 08:32:51","15-05-2025 08:3=
7:08","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Site down due to rectifier issue  // Site stabilisation ","ch=
ristelle.ngonga@matech-cameroun.com","264714","15-05-2025 08:35:27","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0005025042","M=
EHANDAN","","15-05-2025 08:34:53","15-05-2025 08:32:51","15-05-2025 08:37:0=
8","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Site down due to rectifier issue  // Site stabilisation ","chris=
telle.ngonga@matech-cameroun.com","264714","15-05-2025 08:34:53","MATECH CM=
R"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0005025037","E=
koumdoum OCM","","15-05-2025 08:33:51","15-05-2025 08:32:51","15-05-2025 08=
:37:08","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Site down due to rectifier issue  // Site stabilisation ","=
christelle.ngonga@matech-cameroun.com","264715","15-05-2025 08:33:51","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0005024850","N=
yom OCM","","15-05-2025 07:48:44","15-05-2025 07:44:35","15-05-2025 08:11:0=
6","Grid outage ,gen started and stopped due to overheating//We add water a=
nd gen manually started","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage ,gen s=
tarted and stopped due to overheating//We add water and gen manually starte=
d","christelle.ngonga@matech-cameroun.com","250","15-05-2025 07:48:44","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005024781","M=
ontee-Des-Soeurs","","15-05-2025 07:36:22","15-05-2025 07:35:15","15-05-202=
5 07:50:06","Active // No power issue, site is on grid with Ubaie: 50.04V, =
Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue, site is on grid with Ubaie: 50.04V, Mbah hosiah=
(699699694) from Huawei is informed","christelle.ngonga@matech-cameroun.com=
","68","15-05-2025 07:36:22","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005024756","B=
arriere IHS","","15-05-2025 07:33:21","15-05-2025 07:32:14","15-05-2025 07:=
47:09","No power issue on site Ubaie =3D 53.4V Site on Grid ,FME TX Flubert=
 (654266068) from HUAWEI is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site Ubaie =3D 53.4V Site on Grid ,FME TX Flubert (654266068) fro=
m HUAWEI is informed","christelle.ngonga@matech-cameroun.com","69","15-05-2=
025 07:33:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0005024478","Yoko OCM=
","","15-05-2025 06:37:24","15-05-2025 06:10:16","15-05-2025 07:12:16","Cas=
caded Incident from TTO5156313","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue, site is on Gen wi=
th Ubaie=3D49,4V. The Fme TX Gregoire (654547479) from Huawei is informed",=
"system","273226","15-05-2025 06:37:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0005024479","Ngouetou=
","","15-05-2025 06:37:24","15-05-2025 06:10:16","15-05-2025 07:12:16","Cas=
caded Incident from TTO5156313","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue, site is on Gen wi=
th Ubaie=3D49,4V. The Fme TX Gregoire (654547479) from Huawei is informed",=
"system","273226","15-05-2025 06:37:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0005024476","Ngoum","=
","15-05-2025 06:37:24","15-05-2025 06:10:16","15-05-2025 07:12:16","Cascad=
ed Incident from TTO5156313","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue, site is on Gen with =
Ubaie=3D49,4V. The Fme TX Gregoire (654547479) from Huawei is informed","sy=
stem","273225","15-05-2025 06:37:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0005024477","Matsari"=
,"","15-05-2025 06:37:24","15-05-2025 06:10:16","15-05-2025 07:12:16","Casc=
aded Incident from TTO5156313","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue, site is on Gen wit=
h Ubaie=3D49,4V. The Fme TX Gregoire (654547479) from Huawei is informed","=
system","273225","15-05-2025 06:37:24","MATECH CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0005024436","M=
BIMBIM","IHS_YND_475, IHS_YND_460, IHS_YND_474, IHS_YND_454","15-05-2025 06=
:29:28","15-05-2025 06:10:16","15-05-2025 08:52:16","Active//No power issue=
, site is on Gen with Ubaie=3D49,4V. The Fme TX Gregoire (654547479) from H=
uawei is informed","Parker Tchoup","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, site=
 is on Gen with Ubaie=3D49,4V. The Fme TX Gregoire (654547479) from Huawei =
is informed","loic.noumsi@matech-cameroun.com","1154","15-05-2025 06:29:28"=
,"MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0005024256","Aka=
k-Nkozoa-MTN-IHS","","15-05-2025 05:57:32","15-05-2025 05:43:06","15-05-202=
5 07:34:06","Grid outage, Gen stopped due to Alarm Oil pressure // Gen card=
 reset and Gen start manually","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Low Oil Pressure","Grid outage, Gen stopped due to Al=
arm Oil pressure // Gen card reset and Gen start manually","loic.noumsi@mat=
ech-cameroun.com","1072","15-05-2025 05:57:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005024101","MEHANDAN=
","","15-05-2025 05:15:58","15-05-2025 05:11:56","15-05-2025 05:14:22","Cas=
caded Incident from TTO5155962","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to PWC ZTE malfunction // Grid return","system","262=
197","15-05-2025 05:15:58","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005024084","O=
dza II OCM","IHS_YND_528","15-05-2025 05:14:11","15-05-2025 05:11:56","15-0=
5-2025 05:14:22","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid return","Albran Byorel","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","	Grid outage, site w=
ent down because gen failed to start due to PWC ZTE malfunction // Grid ret=
urn","gaelle.njiofack@matech-cameroun.com","137","15-05-2025 05:14:11","MAT=
ECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0005023447","ODZ=
A CITE MBIA","","15-05-2025 02:46:54","15-05-2025 02:40:37","15-05-2025 03:=
32:46","Grid outage,DG started and stopped due with alarm ""oil pressure""(=
 unprouven Alarm ) // He reset DG card and started DG manually","Albran Byo=
rel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage,DG started and stopped due with alarm ""oil pressure""( unprouven Ala=
rm ) // He reset DG card and started DG manually","loic.noumsi@matech-camer=
oun.com","378","15-05-2025 02:46:54","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0005023341","K=
oweit City","","15-05-2025 02:10:50","15-05-2025 02:00:36","15-05-2025 03:1=
3:38","Grid outage, site went down because gen failed to start with alarm u=
ndervoltage // He reseted gen card and gen manually started","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge, site went down because gen failed to start with alarm undervoltage // H=
e reseted gen card and gen manually started","loic.noumsi@matech-cameroun.c=
om","614","15-05-2025 02:10:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_258","NOCINC0005022861","Mefou-As=
si","","15-05-2025 00:07:53","14-05-2025 23:55:59","15-05-2025 00:00:05","C=
ascaded Incident from TTO5154808","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on grid with Ubaie: 5=
2.8V TX FME Flubert (654266068) from Huawei is informed","system","266861",=
"15-05-2025 00:07:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_520","NOCINC0005022844","SIMBOCK =
BONAMBAPE","","15-05-2025 00:04:09","14-05-2025 23:55:59","15-05-2025 00:00=
:05","Cascaded Incident from TTO5154808","Hyemafo Gildas","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue site on grid wit=
h Ubaie: 52.8V TX FME Flubert (654266068) from Huawei is informed","system"=
,"266861","15-05-2025 00:04:09","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0005022836","M=
EFOU ASSI","IHS_YND_520, IHS_YND_258","15-05-2025 00:02:20","14-05-2025 23:=
55:59","15-05-2025 00:00:05","No power issue site on grid with Ubaie: 52.8V=
 TX FME Flubert (654266068) from Huawei is informed","Fanda Brice","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue site on grid with Ubaie: 52.8V TX FME Flubert (654266068=
) from Huawei is informed","loic.noumsi@matech-cameroun.com","382","15-05-2=
025 00:02:20","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0005022420","B=
arriere IHS","","14-05-2025 22:39:38","14-05-2025 22:25:26","14-05-2025 23:=
57:24","No power issue on site Ubaie =3D 53.6V Site on Grid ,FME TX Flubert=
 (654266068) from HUAWEI is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site Ubaie =3D 53.6V Site on Grid ,FME TX Flubert (654266068) fro=
m HUAWEI is informed","cedric.tiani@matech-cameroun.com","853","14-05-2025 =
22:39:38","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005022407","Bar=
riere","","14-05-2025 22:37:50","14-05-2025 22:31:43","15-05-2025 08:00:43"=
,"Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Feli=
x Zambe is informed and confirmed","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen=
 overload(20kva,400 A) IHS SS Felix Zambe is informed and confirmed","cedri=
c.tiani@matech-cameroun.com","369","14-05-2025 22:37:50","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0005022127","N=
goulmekong-Nord","","14-05-2025 21:54:22","14-05-2025 20:05:08","14-05-2025=
 22:41:18","Site went down due to disjunction of Cb(125A) in PWC // He rear=
med Cb(125A), site on grid","Siligap Boris","Equipment Repair","Passive","C=
ontrol Panel","Circuit Breaker Tripped","Site went down due to disjunction =
of Cb(125A) in PWC // He rearmed Cb(125A), site on grid","vanel.mbiada@mate=
ch-cameroun.com","6555","14-05-2025 21:54:22","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005022124","Mok=
olo Yaounde","","14-05-2025 21:53:41","14-05-2025 11:29:24","14-05-2025 21:=
41:56","BACTRACKING Grid outage no space to deploy the MDG//Grid power retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage no space to deploy the MDG//Grid power return","cedric.tiani@ma=
tech-cameroun.com","37458","14-05-2025 21:53:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0005021499","Messassi=
 2","","14-05-2025 20:30:16","14-05-2025 20:04:05","14-05-2025 20:14:38","C=
ascaded Incident from TTO5153277","Fabrice Pouakam","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
54v Symphorien from Huawei is informed site up at 08:14 PM","system","31669=
9","14-05-2025 20:30:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005021500","Nkolondo=
m","","14-05-2025 20:30:16","14-05-2025 20:04:05","14-05-2025 20:14:38","Ca=
scaded Incident from TTO5153277","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue site on grid with U=3D5=
4v Symphorien from Huawei is informed site up at 08:14 PM","system","316700=
","14-05-2025 20:30:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0005021498","Nyom OCM=
","","14-05-2025 20:30:15","14-05-2025 20:04:05","14-05-2025 20:14:38","Cas=
caded Incident from TTO5153277","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D54=
v Symphorien from Huawei is informed site up at 08:14 PM","system","316699"=
,"14-05-2025 20:30:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0005021497","Nkozoa",=
"","14-05-2025 20:30:15","14-05-2025 20:04:05","14-05-2025 20:14:38","Casca=
ded Incident from TTO5153277","Fabrice Pouakam","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on grid with U=3D54v =
Symphorien from Huawei is informed site up at 08:14 PM","system","316698","=
14-05-2025 20:30:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0005021496","Messassi=
","","14-05-2025 20:30:15","14-05-2025 20:04:05","14-05-2025 20:14:38","Cas=
caded Incident from TTO5153277","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D54=
v Symphorien from Huawei is informed site up at 08:14 PM","system","316703"=
,"14-05-2025 20:30:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0005021495","Olembe-T=
erminus","","14-05-2025 20:30:15","14-05-2025 20:04:05","14-05-2025 20:14:3=
8","Cascaded Incident from TTO5153277","Fabrice Pouakam","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue site on grid with=
 U=3D54v Symphorien from Huawei is informed site up at 08:14 PM","system","=
316700","14-05-2025 20:30:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0005021494","NKOLMEKO=
NG YDE","","14-05-2025 20:30:14","14-05-2025 20:04:05","14-05-2025 20:14:38=
","Cascaded Incident from TTO5153277","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on grid with =
U=3D54v Symphorien from Huawei is informed site up at 08:14 PM","system","3=
16701","14-05-2025 20:30:14","MATECH CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0005021408","Awa=
e Escalier","","14-05-2025 20:17:31","13-05-2025 13:35:07","13-05-2025 14:0=
3:31"," BACKTRACKING Site went down due to rectifiers dysfuntion on site //=
site stabilised","Albran Byorel","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to rectifiers dysfuntion on site //si=
te stabilised","cedric.tiani@matech-cameroun.com","110545","14-05-2025 20:1=
7:31","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005021363","O=
lembe","IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IHS_YND_303, IH=
S_YND_280, IHS_YND_304","14-05-2025 20:09:12","14-05-2025 20:04:05","14-05-=
2025 20:14:38","No power issue site on grid with U=3D54v Symphorien from Hu=
awei is informed site up at 08:14 PM","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on grid with U=3D54v Symphorien from Huawei is informed site u=
p at 08:14 PM","vanel.mbiada@matech-cameroun.com","309","14-05-2025 20:09:1=
2","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0005021334","H-Franco=
 New","","14-05-2025 20:03:39","14-05-2025 19:55:53","14-05-2025 20:02:55",=
"Cascaded Incident from TTO5153206","Delor Telezing","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","	No power issue, site is on Grid wit=
h Ubaie =3D52.5V. The TX Armand Nguetsa (699949553) from Huawei is informed=
","system","266821","14-05-2025 20:03:39","MATECH CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0005021300","D=
joungolo","IHS_YND_711","14-05-2025 20:00:01","14-05-2025 19:55:53","14-05-=
2025 20:02:18","No power issue, site is on Grid with Ubaie =3D52.5V. The TX=
 Armand Nguetsa (699949553) from Huawei is informed","Mboua Thierry","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","	No power issue, site is on Grid with Ubaie =3D52.5V. The TX Armand N=
guetsa (699949553) from Huawei is informed","vanel.mbiada@matech-cameroun.c=
om","249","14-05-2025 20:00:01","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0005021272","ODZ=
A BORNE 10","","14-05-2025 19:55:53","13-05-2025 09:30:27","13-05-2025 10:1=
0:24","Bactracking site went down due to rectifiers dysfunctionning //He  r=
eset it and site on Grid","Albran Byorel","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","site went down due to rectifiers dysfunctionnin=
g //He  reset it and site on Grid","cedric.tiani@matech-cameroun.com","1239=
27","14-05-2025 19:55:53","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0005021220","Nsa=
m Sofavinc","","14-05-2025 19:48:52","14-05-2025 19:40:38","14-05-2025 20:3=
3:19","Site went down because  CB(40A)in PWC that tripped MTN due to cable =
burnt //He rearmed it ","MINKA NICOLAS","Equipment Repair","Passive","Recti=
fier","Rectifier - Circuit Breaker","Site went down because  CB(40A)in PWC =
that tripped MTN due to cable burnt //He rearmed it ","cedric.tiani@matech-=
cameroun.com","495","14-05-2025 19:48:52","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005021212","Elo=
umdem stade","","14-05-2025 19:47:16","14-05-2025 19:37:59","14-05-2025 20:=
04:02","Grid outage ,site went down because Gen failed to start due to Gen =
overload(13kva//140A) SS HIS felix zambe is informed//He reduiced the load =
and manually started the Gen","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage ,site went down because Gen failed =
to start due to Gen overload(13kva//140A) SS HIS felix zambe is informed//H=
e reduiced the load and manually started the Gen","cedric.tiani@matech-came=
roun.com","559","14-05-2025 19:47:16","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005021201","Acc=
acia New","","14-05-2025 19:45:28","14-05-2025 19:36:17","15-05-2025 08:45:=
26","Grid outage ,no space to deploy a mobil gen awaiting grid return	","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage ,no space to deploy a mobil gen awaiting grid return	","cedric.tiani@m=
atech-cameroun.com","553","14-05-2025 19:45:28","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005021199","Men=
dong NB","","14-05-2025 19:44:54","14-05-2025 18:53:44","14-05-2025 20:15:5=
9","Grid Only, No space to deploy // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid Only, No space to deploy=
 // Grid return","cedric.tiani@matech-cameroun.com","3071","14-05-2025 19:4=
4:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0005021146","Nkozoa",=
"","14-05-2025 19:35:59","13-05-2025 08:56:15","13-05-2025 09:43:20","Casca=
ded Incident from TTO5140789","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation.site went due to lack=
 of phases //Grid power stabilized","system","284838","14-05-2025 19:35:59"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0005021145","Ekombiti=
e","","14-05-2025 19:35:58","13-05-2025 08:56:15","13-05-2025 09:43:20","Ca=
scaded Incident from TTO5140789","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation.site went due to l=
ack of phases //Grid power stabilized","system","284837","14-05-2025 19:35:=
58","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005021083","Saa=
","","14-05-2025 19:23:53","14-05-2025 19:21:45","14-05-2025 19:27:30","Act=
ive// No power issue on site ,site on Gen with Ubaie =3D50.6V The Tx Techni=
cian from Huawei Gr=E9goire//654547479 is informed","Parker Tchoup","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power issue on site ,site on Gen with Ubaie =3D50.6V The T=
x Technician from Huawei Gr=E9goire//654547479 is informed","cedric.tiani@m=
atech-cameroun.com","129","14-05-2025 19:23:53","MATECH CMR"
"Cancelled","Warning","","IHS_YND_010","NOCINC0005021062","CNR","","14-05-2=
025 19:18:40","","","Cascaded Incident from TTO5152950","Mboua Thierry","",=
"","","","","system","1086","14-05-2025 19:18:40","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005021010","A=
ccacia New","","14-05-2025 19:04:13","14-05-2025 18:14:11","14-05-2025 19:1=
1:37","Grid outage, no space to deploy a mobil gen // Grid return","","Casc=
ade Outage","Active","Cascade Active","Cascade Active","Active // No power =
issue, site is on grid with Ubaie: 53.96V, Mbah hosiah(699699694) from Huaw=
ei is informed","vanel.mbiada@matech-cameroun.com","1222278","14-05-2025 19=
:04:13","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0005020979","Eto=
ug-Ebe 2","","14-05-2025 19:00:41","14-05-2025 18:57:29","14-05-2025 19:32:=
25","Grid outage, no space to deploy a mobil gen // Grid restoration","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, no space to deploy a mobil gen // Grid restoration","cedric.tiani@matec=
h-cameroun.com","193","14-05-2025 19:00:41","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0005020937","C=
RH-Etoug-Ebe","","14-05-2025 18:52:36","14-05-2025 18:29:28","14-05-2025 18=
:56:48","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen start automatically=
","vanel.mbiada@matech-cameroun.com","1389","14-05-2025 18:52:36","MATECH C=
MR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0005020866","M=
aison-Blanche-IHS","","14-05-2025 18:34:49","14-05-2025 18:27:39","14-05-20=
25 18:55:43","Grid outage.no space to deploy mobile // Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.no space to deploy mobile ","vanel.mbiada@matech-cameroun.com","431","14-0=
5-2025 18:34:49","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005020774","M=
ontee-Des-Soeurs","IHS_YND_562","14-05-2025 18:22:27","14-05-2025 18:14:11"=
,"14-05-2025 21:26:34","Active // No power issue, site is on grid with Ubai=
e: 53.96V, Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active // No power issue, site is on grid with Ubaie: 53.96V, =
Mbah hosiah(699699694) from Huawei is informed","vanel.mbiada@matech-camero=
un.com","497","14-05-2025 18:22:27","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005020496","O=
LAMA","","14-05-2025 17:38:59","13-05-2025 21:19:47","13-05-2025 21:24:25",=
"BACTRACKING Active//No power issue on site Ubaie =3D54.9V site on Gen The =
TX FME Henri (699949693) from Huawei is informed.Noticed that it is a repet=
itve issue","Fanda Brice","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie =
=3D54.9V site on Gen The TX FME Henri (699949693) from Huawei is informed.N=
oticed that it is a repetitve issue","cedric.tiani@matech-cameroun.com","73=
153","14-05-2025 17:38:59","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005020405","Elo=
umdem stade","","14-05-2025 17:23:55","14-05-2025 17:17:47","14-05-2025 17:=
51:45","Grid outage ,site went down because Gen failed to start due to Gen =
overload(13kva//140A) SS HIS felix zambe is informed//He reduiced the load =
and manually started the Gen","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage ,site went down because Gen failed =
to start due to Gen overload(13kva//140A) SS HIS felix zambe is informed//H=
e reduiced the load and manually started the Gen","cedric.tiani@matech-came=
roun.com","369","14-05-2025 17:23:55","MATECH CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0005020348","A=
ngongo","","14-05-2025 17:14:03","14-05-2025 16:56:59","14-05-2025 18:34:49=
","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Site was on Gen due to Grid outage, Site went down because Gen stop=
ped with ""High temp ""alarm // He added water and manually start the Gen",=
"vanel.mbiada@matech-cameroun.com","270475","14-05-2025 17:14:03","MATECH C=
MR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0005020286","Ebe=
ba","IHS_YND_335","14-05-2025 16:59:13","14-05-2025 16:56:59","14-05-2025 1=
8:34:49","Site was on Gen due to Grid outage, Site went down because Gen st=
opped with ""High temp ""alarm // He added water and manually start the Gen=
","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine=
 Temp - Coolant Level Issue","Site was on Gen due to Grid outage, Site went=
 down because Gen stopped with ""High temp ""alarm // He added water and ma=
nually start the Gen","cedric.tiani@matech-cameroun.com","135","14-05-2025 =
16:59:13","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005020263","Eto=
ug ebe Meweulo","","14-05-2025 16:56:48","14-05-2025 16:53:38","14-05-2025 =
18:18:40","Site went down due to fuel shortage // Refuelling done","Hyemafo=
 Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Site went down d=
ue to fuel shortage // Refuelling done","cedric.tiani@matech-cameroun.com",=
"191","14-05-2025 16:56:48","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0005020251","M=
essassi okolo","","14-05-2025 16:54:23","13-05-2025 17:30:54","13-05-2025 1=
9:05:31","Bactracking ACTIVE//No power issue on site Ubaie=3D54.5V, site on=
 Grid The TX Fme Synphorien 691316854 of Huawei is informed.Noticed impacte=
d by pont emmana","Fabrice Pouakam","Customer Equipment Failure","Active","=
Active Equipment Failure","Affected by 3rd Party Site","ACTIVE//No power is=
sue on site Ubaie=3D54.4V, site on Grid The TX Fme Synphorien 691316854 of =
Huawei is informed.Noticed impacted by pont emmana","cedric.tiani@matech-ca=
meroun.com","84210","14-05-2025 16:54:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0005020233","Barriere=
 IHS","","14-05-2025 16:50:29","14-05-2025 16:47:20","14-05-2025 17:45:18",=
"Cascaded Incident from TTO5152041","Hyemafo Gildas","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen fails to start due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE i=
s informed // He reduice the load and site on GEN","system","271171","14-05=
-2025 16:50:29","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005020223","M=
efou-Assi","IHS_YND_696","14-05-2025 16:48:32","14-05-2025 16:47:20","14-05=
-2025 17:45:18","Grid outage, site went down because gen fails to start due=
 to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // He reduice =
the load and site on GEN","Fanda Brice","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","Grid outage, site went down because gen fails to st=
art due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // He r=
eduice the load and site on GEN","vanel.mbiada@matech-cameroun.com","73","1=
4-05-2025 16:48:32","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0005020179","Bar=
riere","","14-05-2025 16:41:15","14-05-2025 16:33:04","14-05-2025 18:19:12"=
,"Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Feli=
x Zambe is informed and confirmed//He reduiced the load an site on Gen","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, Site went down because Gen overload(20kva,400 A) IHS SS Felix Za=
mbe is informed and confirmed//He reduiced the load an site on Gen","cedric=
.tiani@matech-cameroun.com","492","14-05-2025 16:41:15","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005020157","E=
bogo","","14-05-2025 16:39:00","14-05-2025 16:36:13","14-05-2025 16:40:16",=
"Grid outage, site went down before Gen start due poor backup battery // Ge=
n automatically started","Siligap Boris","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e Gen start due poor backup battery // Gen automatically started","vanel.mb=
iada@matech-cameroun.com","168","14-05-2025 16:39:00","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005020155","ELO=
UMDEM CARRIERE","","14-05-2025 16:38:17","14-05-2025 16:33:06","14-05-2025 =
17:07:10","Grid fluctuation,Site went down because Gen failed to start due =
to grid bad voltage//he bypassed the Grid and site on Gen","Fanda Brice","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d fluctuation,Site went down because Gen failed to start due to grid bad vo=
ltage//he bypassed the Grid and site on Gen","cedric.tiani@matech-cameroun.=
com","313","14-05-2025 16:38:17","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005020146","Odz=
a II OCM","","14-05-2025 16:36:43","14-05-2025 16:30:37","14-05-2025 16:38:=
34","Grid outage, site went down because gen failed to start due to PWC ZTE=
 malfunction // Grid return","Albran Byorel","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
ecause gen failed to start due to PWC ZTE malfunction // Grid return","cedr=
ic.tiani@matech-cameroun.com","367","14-05-2025 16:36:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0005020143","Nyom OCM=
","","14-05-2025 16:36:19","14-05-2025 16:04:56","14-05-2025 18:07:43","Cas=
caded Incident from TTO5151916","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work of SS HIS=
 Felix Bateu  is on site working(Installation of  PLD) //End of work","syst=
em","273663","14-05-2025 16:36:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0005020141","Messassi=
","","14-05-2025 16:36:19","14-05-2025 16:04:56","14-05-2025 18:07:43","Cas=
caded Incident from TTO5151916","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work of SS HIS=
 Felix Bateu  is on site working(Installation of  PLD) //End of work","syst=
em","273666","14-05-2025 16:36:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0005020142","Nkozoa",=
"","14-05-2025 16:36:19","14-05-2025 16:04:56","14-05-2025 18:07:43","Casca=
ded Incident from TTO5151916","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work of SS HIS F=
elix Bateu  is on site working(Installation of  PLD) //End of work","system=
","273664","14-05-2025 16:36:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005020144","Nkongtoc=
k","","14-05-2025 16:36:19","14-05-2025 16:04:56","14-05-2025 18:07:43","Ca=
scaded Incident from TTO5151916","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work of SS HI=
S Felix Bateu  is on site working(Installation of  PLD) //End of work","sys=
tem","273665","14-05-2025 16:36:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0005020140","Olembe-T=
erminus","","14-05-2025 16:36:18","14-05-2025 16:04:56","14-05-2025 18:07:4=
3","Cascaded Incident from TTO5151916","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work of=
 SS HIS Felix Bateu  is on site working(Installation of  PLD) //End of work=
","system","273664","14-05-2025 16:36:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0005020138","Ekombiti=
e","","14-05-2025 16:36:18","14-05-2025 16:04:56","14-05-2025 18:07:43","Ca=
scaded Incident from TTO5151916","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work of SS HI=
S Felix Bateu  is on site working(Installation of  PLD) //End of work","sys=
tem","273665","14-05-2025 16:36:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0005020139","NKOLMEKO=
NG YDE","","14-05-2025 16:36:18","14-05-2025 16:04:56","14-05-2025 18:07:43=
","Cascaded Incident from TTO5151916","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work of =
SS HIS Felix Bateu  is on site working(Installation of  PLD) //End of work"=
,"system","273663","14-05-2025 16:36:18","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005020095","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_349","14-05-2025 16:31:07","14-05-2025 16:04:56","14-05-=
2025 18:07:43","Site went down due to work of SS HIS Felix Bateu  is on sit=
e working(Installation of  PLD) //End of work","Fabrice Pouakam","Installat=
ion Activity","Passive","Planned Activity","Installation Activity","Site we=
nt down due to work of SS HIS Felix Bateu  is on site working(Installation =
of  PLD) //End of work","cedric.tiani@matech-cameroun.com","1572","14-05-20=
25 16:31:07","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005020093","M=
ontee-Des-Soeurs","","14-05-2025 16:30:29","14-05-2025 16:25:19","14-05-202=
5 17:19:43","Grid outage,Site went down because Gen failed to start due to =
ATS dysfunction on site//He reset it and started the Gen manually","Hyemafo=
 Gildas","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid=
 outage,Site went down because Gen failed to start due to ATS dysfunction o=
n site//He reset it and started the Gen manually","vanel.mbiada@matech-came=
roun.com","311","14-05-2025 16:30:29","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005019891","Nko=
l-Mebanga","","14-05-2025 16:06:09","14-05-2025 15:40:09","14-05-2025 15:52=
:52","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, site went down before Gen start due poor backup b=
attery // Gen automatically started","cedric.tiani@matech-cameroun.com","12=
17206","14-05-2025 16:06:09","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0005019846","Lad=
a I Yde","","14-05-2025 15:57:14","14-05-2025 15:54:05","14-05-2025 16:17:4=
3","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // He bypass the Grid and Gen manually started","Mba L=
azare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen and started and sto=
pped due to Grid bad voltage // He bypass the Grid and Gen manually started=
","cedric.tiani@matech-cameroun.com","190","14-05-2025 15:57:14","MATECH CM=
R"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005019743","Saa=
","IHS_YND_810, IHS_YND_809","14-05-2025 15:42:14","14-05-2025 15:40:09","1=
4-05-2025 15:52:52","Grid outage, site went down before Gen start due poor =
backup battery // Gen automatically started","Parker Tchoup","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
site went down before Gen start due poor backup battery // Gen automaticall=
y started","cedric.tiani@matech-cameroun.com","126","14-05-2025 15:42:14","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_141","NOCINC0005019713","New-Marc=
he-Melen","","14-05-2025 15:38:39","13-05-2025 18:24:42","14-05-2025 22:06:=
38","Cascaded Incident from TTO5144466","Paul BIBOUM","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,no space to deploy m=
obile gen// grid power return","system","365981","14-05-2025 15:38:39","MAT=
ECH CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0005019705","Car=
refour Ayissi Ele","","14-05-2025 15:37:50","14-05-2025 15:40:09","14-05-20=
25 15:52:52","FME is on the way ETA=3D04:15 PM","Parker Tchoup","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid outage, site went=
 down before Gen start due poor backup battery // Gen automatically started=
","cedric.tiani@matech-cameroun.com","1217207","14-05-2025 15:37:50","MATEC=
H CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0005019691","Mon=
tee Jouvence","","14-05-2025 15:35:06","14-05-2025 15:28:54","14-05-2025 15=
:58:42","Grid outage site went down because Gen stopped with alarm high tem=
p //He added water and Gen manually started","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue",=
"Grid outage site went down because Gen stopped with alarm high temp //He a=
dded water and Gen manually started","cedric.tiani@matech-cameroun.com","37=
3","14-05-2025 15:35:06","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005019528","C=
rf Cornier","","14-05-2025 15:13:57","14-05-2025 15:13:43","14-05-2025 15:2=
1:04","ACTIVE //No power issue Ubaie=3D 49.7V site on Grid Armand NGUETSA /=
/ 699949553// from huawei is informed,","MINKA NICOLAS","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE =
//No power issue Ubaie=3D 49.7V site on Grid Armand NGUETSA // 699949553// =
from huawei is informed,","vanel.mbiada@matech-cameroun.com","16","14-05-20=
25 15:13:57","MATECH CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0005019388","Tsi=
nga","","14-05-2025 14:51:31","14-05-2025 14:47:07","14-05-2025 14:56:48","=
Active// No power issue on site Ubaie=3D50.1V site on Grid The Tx Eloundou =
Bertrand /693212405/Huawei is informed","Mboua Thierry","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power issue on site Ubaie=3D50.1V site on Grid The Tx Eloundou Bertran=
d /693212405/Huawei is informed","cedric.tiani@matech-cameroun.com","265","=
14-05-2025 14:51:31","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0005019370","Men=
dong3","","14-05-2025 14:48:57","14-05-2025 14:47:49","14-05-2025 18:29:19"=
,"Grid outage no space to deploy a MDG// Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage no space to d=
eploy a MDG// Grid return","cedric.tiani@matech-cameroun.com","68","14-05-2=
025 14:48:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0005019074","Barriere=
 IHS","","14-05-2025 13:57:43","14-05-2025 13:51:59","14-05-2025 14:35:58",=
"Cascaded Incident from TTO5150829","Hyemafo Gildas","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because Gen overlo=
ad(15kva,200 A) IHS SS Felix Zambe is informed and confirmed // He reduced =
the load and manually started the Gen","system","266990","14-05-2025 13:57:=
43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0005019073","MEFOU AS=
SI","","14-05-2025 13:57:43","14-05-2025 13:51:59","14-05-2025 14:35:58","C=
ascaded Incident from TTO5150829","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because Gen overload(15=
kva,200 A) IHS SS Felix Zambe is informed and confirmed // He reduced the l=
oad and manually started the Gen","system","266990","14-05-2025 13:57:43","=
MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005019058","M=
efou-Assi","IHS_YND_537, IHS_YND_696","14-05-2025 13:55:32","14-05-2025 13:=
51:59","14-05-2025 14:35:58","Site went down because Gen overload(15kva,200=
 A) IHS SS Felix Zambe is informed and confirmed // He reduced the load and=
 manually started the Gen","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Site went down because Gen overload(15kva,200 A) I=
HS SS Felix Zambe is informed and confirmed // He reduced the load and manu=
ally started the Gen","edwige.kapawo@matech-cameroun.com","214","14-05-2025=
 13:55:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005018961","Elig-Edz=
oa","","14-05-2025 13:42:11","14-05-2025 13:39:59","14-05-2025 14:23:47","C=
ascaded Incident from TTO5150724","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Site went down due to PWC Overload(12Kw 250A) Bla=
ise Raoul SS IHS is iformed //Site stabilised","system","275107","14-05-202=
5 13:42:11","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0005018944","N=
taba","IHS_YND_133","14-05-2025 13:40:58","14-05-2025 13:39:59","14-05-2025=
 14:30:47","Site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS I=
HS is iformed //Site stabilised","Delor Telezing","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due to PWC Ov=
erload(12Kw 250A) Blaise Raoul SS IHS is iformed //Site stabilised","edwige=
.kapawo@matech-cameroun.com","61","14-05-2025 13:40:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0005018898","Messassi=
 2","","14-05-2025 13:35:02","14-05-2025 12:54:59","14-05-2025 13:36:00","C=
ascaded Incident from TTO5150434","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work of FME =
and Felix bateu on site working//End of work","system","277730","14-05-2025=
 13:35:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0005018896","Nyom OCM=
","","14-05-2025 13:35:02","14-05-2025 12:54:59","14-05-2025 13:36:00","Cas=
caded Incident from TTO5150434","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work of FME an=
d Felix bateu on site working//End of work","system","277729","14-05-2025 1=
3:35:02","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005018693","C=
-Supreme","","14-05-2025 13:11:58","14-05-2025 13:09:47","14-05-2025 13:17:=
56","Active // No power issue, site on Grid with Ubaie: 50.2V, Brice Tsague=
 (650 21 40 96) from Huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power =
issue, site on Grid with Ubaie: 50.2V, Brice Tsague (650 21 40 96) from Hua=
wei is informed","edwige.kapawo@matech-cameroun.com","132","14-05-2025 13:1=
1:58","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0005018676","NKO=
MEKUI OCM","","14-05-2025 13:10:17","14-05-2025 13:01:59","14-05-2025 13:14=
:09","No power issue site on Gen with U=3D54.5 V The Tx Fme Mohamadou mouam=
 // 691144435 from Huawei is informed site impacted by Mbankolo camtel","TI=
ENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equip=
ment Failure","Affected by 3rd Party Site","No power issue site on Gen with=
 U=3D54.5 V The Tx Fme Mohamadou mouam // 691144435 from Huawei is informed=
 site impacted by Mbankolo camtel","loic.noumsi@matech-cameroun.com","500",=
"14-05-2025 13:10:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0005018640","Olembe-T=
erminus","","14-05-2025 13:10:06","14-05-2025 12:54:59","14-05-2025 13:36:0=
0","Cascaded Incident from TTO5150434","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work of=
 FME and Felix bateu on site working//End of work","system","277728","14-05=
-2025 13:10:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005018643","Nkolondo=
m","","14-05-2025 13:10:06","14-05-2025 12:54:59","14-05-2025 13:36:00","Ca=
scaded Incident from TTO5150434","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work of FME a=
nd Felix bateu on site working//End of work","system","277731","14-05-2025 =
13:10:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0005018641","Messassi=
","","14-05-2025 13:10:06","14-05-2025 12:54:59","14-05-2025 13:36:00","Cas=
caded Incident from TTO5150434","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work of FME an=
d Felix bateu on site working//End of work","system","277727","14-05-2025 1=
3:10:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0005018642","Nkozoa",=
"","14-05-2025 13:10:06","14-05-2025 12:54:59","14-05-2025 13:36:00","Casca=
ded Incident from TTO5150434","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work of FME and =
Felix bateu on site working//End of work","system","277728","14-05-2025 13:=
10:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0005018638","Ekombiti=
e","","14-05-2025 13:10:05","14-05-2025 12:54:59","14-05-2025 13:36:00","Ca=
scaded Incident from TTO5150434","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work of FME a=
nd Felix bateu on site working//End of work","system","277730","14-05-2025 =
13:10:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0005018639","NKOLMEKO=
NG YDE","","14-05-2025 13:10:05","14-05-2025 12:54:59","14-05-2025 13:36:00=
","Cascaded Incident from TTO5150434","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work of =
FME and Felix bateu on site working//End of work","system","277729","14-05-=
2025 13:10:05","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005018585","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_280, IHS_YND_304","14-05-2025 13:04:59","14-05-2025 12:5=
4:59","14-05-2025 13:36:35","Site went down due to work of FME and Felix ba=
teu on site working//End of work","Fabrice Pouakam","Installation Activity"=
,"Passive","Planned Activity","Installation Activity","Site went down due t=
o work of FME and Felix bateu on site working//End of work","vanel.mbiada@m=
atech-cameroun.com","601","14-05-2025 13:04:59","MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0005018534","Nko=
abang MTN","","14-05-2025 12:59:55","14-05-2025 12:57:07","14-05-2025 13:00=
:20","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup // Grid return","olivier.kwedi@ihstowers.com","169","14=
-05-2025 12:59:55","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005018434","T=
amtam Weekend","","14-05-2025 12:50:25","14-05-2025 12:49:11","14-05-2025 1=
3:19:11","site went down due to  Gen overload (20KVA / 300A) // Grid stabil=
ized","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","site went down due to  Gen overload (20KVA / 300A) // Grid stabilize=
d","vanel.mbiada@matech-cameroun.com","74","14-05-2025 12:50:25","MATECH CM=
R"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005018050","S=
OA TOWN","","14-05-2025 12:20:25","14-05-2025 12:19:59","14-05-2025 12:22:4=
8","Site went down due to our fme on site doing  (PM)//End of work","Siliga=
p Boris","Installation Activity","Passive","Planned Activity","Installation=
 Activity","Site went down due to our fme on site doing  (PM)//End of work"=
,"edwige.kapawo@matech-cameroun.com","27","14-05-2025 12:20:25","MATECH CMR=
"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0005018029","E=
kounou","","14-05-2025 12:16:58","14-05-2025 12:09:26","14-05-2025 13:48:12=
","Site went down due to CB(100A*100A) in PWC that tripped ocm //He rearmed=
 it","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier - =
Circuit Breaker","Site went down due to CB(100A*100A) in PWC that tripped o=
cm //He rearmed it","edwige.kapawo@matech-cameroun.com","453","14-05-2025 1=
2:16:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005018013","MEHANDAN=
","","14-05-2025 12:14:36","14-05-2025 12:00:55","14-05-2025 12:13:18","Cas=
caded Incident from TTO5149925","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,site went down because GE=
N failed to start due to ATS and Gen card faulty // grid returned	","system=
","1215947","14-05-2025 12:14:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0005017980","Nyom OCM=
","","14-05-2025 12:09:36","14-05-2025 11:35:37","14-05-2025 12:26:28","Cas=
caded Incident from TTO5149724","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Grid outage.site went down due to g=
en failed to start because poor backup //Grid return(investigation ongoinng=
)","system","268113","14-05-2025 12:09:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0005017981","Nkongtoc=
k","","14-05-2025 12:09:36","14-05-2025 11:35:37","14-05-2025 12:26:28","Ca=
scaded Incident from TTO5149724","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive"," Grid outage.site went down due to =
gen failed to start because poor backup //Grid return(investigation ongoinn=
g)","system","268115","14-05-2025 12:09:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005017982","Nkolondo=
m","","14-05-2025 12:09:36","14-05-2025 11:35:37","14-05-2025 12:26:28","Ca=
scaded Incident from TTO5149724","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive"," Grid outage.site went down due to =
gen failed to start because poor backup //Grid return(investigation ongoinn=
g)","system","268112","14-05-2025 12:09:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0005017976","Olembe-T=
erminus","","14-05-2025 12:09:35","14-05-2025 11:35:37","14-05-2025 12:26:2=
8","Cascaded Incident from TTO5149724","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive"," Grid outage.site went down d=
ue to gen failed to start because poor backup //Grid return(investigation o=
ngoinng)","system","268114","14-05-2025 12:09:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0005017975","NKOLMEKO=
NG YDE","","14-05-2025 12:09:35","14-05-2025 11:35:37","14-05-2025 12:26:28=
","Cascaded Incident from TTO5149724","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive"," Grid outage.site went down du=
e to gen failed to start because poor backup //Grid return(investigation on=
goinng)","system","268114","14-05-2025 12:09:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0005017978","Messassi=
","","14-05-2025 12:09:35","14-05-2025 11:35:37","14-05-2025 12:26:28","Cas=
caded Incident from TTO5149724","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Grid outage.site went down due to g=
en failed to start because poor backup //Grid return(investigation ongoinng=
)","system","268115","14-05-2025 12:09:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0005017974","Ekombiti=
e","","14-05-2025 12:09:35","14-05-2025 11:35:37","14-05-2025 12:26:28","Ca=
scaded Incident from TTO5149724","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive"," Grid outage.site went down due to =
gen failed to start because poor backup //Grid return(investigation ongoinn=
g)","system","268116","14-05-2025 12:09:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0005017979","Nkozoa",=
"","14-05-2025 12:09:35","14-05-2025 11:35:37","14-05-2025 12:26:28","Casca=
ded Incident from TTO5149724","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive"," Grid outage.site went down due to gen=
 failed to start because poor backup //Grid return(investigation ongoinng)"=
,"system","268112","14-05-2025 12:09:35","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0005017962","Odz=
a II OCM","IHS_YND_528","14-05-2025 12:08:23","14-05-2025 12:00:55","14-05-=
2025 12:13:18","Grid outage ,site went down because GEN failed to start due=
 to ATS and Gen card faulty // grid returned	","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went =
down because GEN failed to start due to ATS and Gen card faulty // grid ret=
urned	","loic.noumsi@matech-cameroun.com","449","14-05-2025 12:08:23","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005017793","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_349, IHS_YND_304","14-05-2025 11:44:02","14-05-2025 11:3=
5:37","14-05-2025 12:26:56"," Grid outage.site went down due to gen failed =
to start because poor backup //Grid return(investigation ongoinng)","Fabric=
e Pouakam","Equipment Repair","Passive","Control Panel","Power Cabinet - Ba=
ttery Low"," Grid outage.site went down due to gen failed to start because =
poor backup //Grid return(investigation ongoinng)","ludivine.ngamaleu@ihsto=
wers.com","507","14-05-2025 11:44:02","MATECH CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0005017755","E=
seka Town","","14-05-2025 11:38:58","14-05-2025 11:28:59","14-05-2025 11:41=
:08","Site went down because gen start and stopped due to grid bad voltage,=
 no rcp on site // Grid stabilized","Kemeni Franklin","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Site went down because=
 gen start and stopped due to grid bad voltage, no rcp on site // Grid stab=
ilized","edwige.kapawo@matech-cameroun.com","601","14-05-2025 11:38:58","MA=
TECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005017346","Mok=
olo Yaounde","","14-05-2025 10:30:31","14-05-2025 10:24:23","14-05-2025 10:=
38:07","Active // No power issue Ubay: 54.7V site on grid. The Tx FME Eloun=
dou Bertrand (693212405) from Huawei is informed","","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // =
No power issue Ubay: 54.7V site on grid. The Tx FME Eloundou Bertrand (6932=
12405) from Huawei is informed","edwige.kapawo@matech-cameroun.com","369","=
14-05-2025 10:30:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005017200","Emana Ly=
cee","","14-05-2025 10:07:37","14-05-2025 10:04:19","14-05-2025 10:21:26","=
Cascaded Incident from TTO5149068","Fabrice Pouakam","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Grid outage , site went down before =
Gen failed to started due to poor battery backup// Site on Grid","system","=
1215899","14-05-2025 10:07:37","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005017194","E=
mana lycee 2","IHS_YND_274","14-05-2025 10:06:31","14-05-2025 10:04:19","14=
-05-2025 10:21:26","Grid outage , site went down before Gen failed to start=
ed due to poor battery backup// Site on Grid","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Grid outage , site went down before Gen failed to started due to poor batt=
ery backup// Site on Grid","edwige.kapawo@matech-cameroun.com","133","14-05=
-2025 10:06:31","MATECH CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0005017091","Nsa=
m escale LP","","14-05-2025 09:52:42","14-05-2025 09:45:34","17-05-2025 17:=
04:24","Grid  Only, Site went down due to bad voltage on site , Eneo has be=
en contacted // Grid stabilised","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Incomplete Phase","Grid  Only, Site went down due to bad volt=
age on site , Eneo has been contacted // Grid stabilised","loic.noumsi@mate=
ch-cameroun.com","429","14-05-2025 09:52:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0005017087","Marche O=
dza","","14-05-2025 09:50:53","14-05-2025 09:47:39","14-05-2025 09:57:39","=
Cascaded Incident from TTO5148937","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue on site Ubaie: =
52.97 V site on Grid The TX Lionel steve (655184876 /Huawei)) is informed."=
,"system","267364","14-05-2025 09:50:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0005017086","Mvog-Man=
ga","","14-05-2025 09:50:53","14-05-2025 09:47:39","14-05-2025 09:57:39","C=
ascaded Incident from TTO5148937","Albran Byorel","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue on site Ubaie: 5=
2.97 V site on Grid The TX Lionel steve (655184876 /Huawei)) is informed.",=
"system","267364","14-05-2025 09:50:53","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0005017064","O=
dza","IHS_YND_254, IHS_YND_580","14-05-2025 09:49:49","14-05-2025 09:47:39"=
,"14-05-2025 09:57:39","Active//No power issue on site Ubaie: 52.97 V site =
on Grid The TX Lionel steve (655184876 /Huawei)) is informed.","Albran Byor=
el","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue on site Ubaie: 52.97 V site on Grid =
The TX Lionel steve (655184876 /Huawei)) is informed.","vanel.mbiada@matech=
-cameroun.com","131","14-05-2025 09:49:49","MATECH CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0005017018","Jea=
n Vespa","IHS_YND_574","14-05-2025 09:40:56","14-05-2025 09:31:59","14-05-2=
025 09:44:59","Grid fluctuation, site went down because Gen failed to start=
 due to grid bad voltage No crcp // He bypassed the grid and started Gen ma=
nually","Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid fluctuation, site went down because Gen failed =
to start due to grid bad voltage No crcp // He bypassed the grid and starte=
d Gen manually","loic.noumsi@matech-cameroun.com","538","14-05-2025 09:40:5=
6","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0005016994","Crf=
-Mbankolo-IHS","","14-05-2025 09:38:10","14-05-2025 09:31:59","14-05-2025 0=
9:44:59","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid fluctuation, site went down because Gen failed to sta=
rt due to grid bad voltage No crcp // He bypassed the grid and started Gen =
manually","loic.noumsi@matech-cameroun.com","268408","14-05-2025 09:38:10",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0005016957","J=
-Vespa","IHS_YND_544","14-05-2025 09:27:49","14-05-2025 09:18:28","14-05-20=
25 09:36:28","Grid fluctuation, site went down because Gen failed to start =
due to grid bad voltage No crcp // He bypassed the grid and started Gen man=
ually","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid fluctuation, site went down because Gen failed to start due to =
grid bad voltage No crcp // He bypassed the grid and started Gen manually",=
"ludivine.ngamaleu@ihstowers.com","815","14-05-2025 09:27:49","MATECH CMR"
"Closed Complete","Site Down","CTR_525","IHS_YND_544","NOCINC0005016929","J=
ean Vespa 2","","14-05-2025 09:23:41","14-05-2025 09:18:28","14-05-2025 09:=
36:28","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid fluctuation, site went down because Gen failed to start=
 due to grid bad voltage No crcp // He bypassed the grid and started Gen ma=
nually","loic.noumsi@matech-cameroun.com","269209","14-05-2025 09:23:41","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0005016618","N=
YOM 2 IHS","","14-05-2025 08:35:52","14-05-2025 08:31:37","14-05-2025 08:46=
:37","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automaticaly","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen started automaticaly","vanel.mbiada@=
matech-cameroun.com","256","14-05-2025 08:35:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005016613","Emana Ly=
cee","","14-05-2025 08:34:47","14-05-2025 08:24:57","14-05-2025 08:40:22","=
Cascaded Incident from TTO5148428","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down befo=
re Gen failed to started due to poor battery backup// Site on Grid","system=
","264994","14-05-2025 08:34:47","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005016603","E=
mana lycee 2","IHS_YND_274","14-05-2025 08:32:56","14-05-2025 08:24:57","14=
-05-2025 08:41:20","Grid outage , site went down before Gen failed to start=
ed due to poor battery backup// Site on Grid","Fabrice Pouakam","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outag=
e , site went down before Gen failed to started due to poor battery backup/=
/ Site on Grid","vanel.mbiada@matech-cameroun.com","480","14-05-2025 08:32:=
56","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0005016259","N=
kolfon Cimencam","","14-05-2025 07:13:42","14-05-2025 07:04:33","14-05-2025=
 07:15:36","No power issue, Site impacted by Afanoya-II","Hyemafo Gildas","=
Customer Equipment Failure","Active","Active Equipment Failure","Affected b=
y 3rd Party Site","No power issue, Site impacted by Afanoya-II","vanel.mbia=
da@matech-cameroun.com","550","14-05-2025 07:13:42","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005016165","S=
aa","IHS_YND_810, IHS_YND_809","14-05-2025 06:56:09","14-05-2025 06:49:56",=
"14-05-2025 08:22:54","Site went down because 01/03 rectifier disfunctionni=
ng SS BATEU Felix IHS is informed // He reset it: Site on grid","Parker Tch=
oup","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went=
 down because 01/03 rectifier disfunctionning SS BATEU Felix IHS is informe=
d // He reset it: Site on grid","vanel.mbiada@matech-cameroun.com","374","1=
4-05-2025 06:56:09","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005016082","Nko=
l-Mebanga","","14-05-2025 06:41:44","14-05-2025 06:49:56","14-05-2025 08:10=
:09","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Site went down because 01/03 rectifier disfunctionning SS BATE=
U Felix IHS is informed // He reset it: Site on grid","loic.noumsi@matech-c=
ameroun.com","270705","14-05-2025 06:41:44","MATECH CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0005016071","Car=
refour Ayissi Ele","","14-05-2025 06:40:28","14-05-2025 06:49:56","14-05-20=
25 08:10:09","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Site went down because 01/03 rectifier disfunctionning=
 SS BATEU Felix IHS is informed // He reset it: Site on grid","loic.noumsi@=
matech-cameroun.com","270705","14-05-2025 06:40:28","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0005016010","TSI=
NGA VILLAGE 2","","14-05-2025 06:26:14","14-05-2025 06:17:09","14-05-2025 0=
7:36:13","Site went down due to Gen under voltage alarm //control reset of =
all parameters and generator restart ","Delor Telezing","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Under Voltage","Site went down due to Gen unde=
r voltage alarm //control reset of all parameters and generator restart ","=
loic.noumsi@matech-cameroun.com","546","14-05-2025 06:26:14","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005015857","AKA=
K Nkozoa","","14-05-2025 05:48:02","14-05-2025 05:43:48","14-05-2025 06:39:=
48","Site went down due to insufficient rectifier issue // he reseted it","=
Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient rectifier issue // he reseted it","lo=
ic.noumsi@matech-cameroun.com","255","14-05-2025 05:48:02","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0005015845","Tam=
tam Weekend","","14-05-2025 05:44:45","13-05-2025 22:41:31","13-05-2025 22:=
43:12","Grid outage, site went down before Gen start due poor backup batter=
y //Grid returned","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before Gen=
 start due poor backup battery //Grid returned","loic.noumsi@matech-camerou=
n.com","25395","14-05-2025 05:44:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0005015783","Messassi=
 2","","14-05-2025 05:26:35","14-05-2025 05:05:06","14-05-2025 05:27:51","C=
ascaded Incident from TTO5147487","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive"," Grid outage.site went down due to=
 gen failed to start //Grid return(investigation ongoinng)","system","29146=
8","14-05-2025 05:26:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005015784","Nkolondo=
m","","14-05-2025 05:26:35","14-05-2025 05:05:06","14-05-2025 05:27:51","Ca=
scaded Incident from TTO5147487","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive"," Grid outage.site went down due to =
gen failed to start //Grid return(investigation ongoinng)","system","291467=
","14-05-2025 05:26:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0005015781","Nkozoa",=
"","14-05-2025 05:26:34","14-05-2025 05:05:06","14-05-2025 05:27:51","Casca=
ded Incident from TTO5147487","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive"," Grid outage.site went down due to gen=
 failed to start //Grid return(investigation ongoinng)","system","291467","=
14-05-2025 05:26:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0005015779","Olembe-T=
erminus","","14-05-2025 05:26:34","14-05-2025 05:05:06","14-05-2025 05:27:5=
1","Cascaded Incident from TTO5147487","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive"," Grid outage.site went down d=
ue to gen failed to start //Grid return(investigation ongoinng)","system","=
291466","14-05-2025 05:26:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0005015782","Nyom OCM=
","","14-05-2025 05:26:34","14-05-2025 05:05:06","14-05-2025 05:27:51","Cas=
caded Incident from TTO5147487","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Grid outage.site went down due to g=
en failed to start //Grid return(investigation ongoinng)","system","291470"=
,"14-05-2025 05:26:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0005015780","Messassi=
","","14-05-2025 05:26:34","14-05-2025 05:05:06","14-05-2025 05:27:51","Cas=
caded Incident from TTO5147487","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Grid outage.site went down due to g=
en failed to start //Grid return(investigation ongoinng)","system","291469"=
,"14-05-2025 05:26:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0005015777","Ekombiti=
e","","14-05-2025 05:26:33","14-05-2025 05:05:06","14-05-2025 05:27:51","Ca=
scaded Incident from TTO5147487","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive"," Grid outage.site went down due to =
gen failed to start //Grid return(investigation ongoinng)","system","291468=
","14-05-2025 05:26:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0005015778","NKOLMEKO=
NG YDE","","14-05-2025 05:26:33","14-05-2025 05:05:06","14-05-2025 05:27:51=
","Cascaded Incident from TTO5147487","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive"," Grid outage.site went down du=
e to gen failed to start //Grid return(investigation ongoinng)","system","2=
91470","14-05-2025 05:26:33","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005015769","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_280, IHS_YND_304","14-05-2025 05:19:12","14-05-2025 05:0=
5:06","14-05-2025 05:27:51"," Grid outage.site went down due to gen failed =
to start //Grid return(investigation ongoinng)","Fabrice Pouakam","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel"," Grid outage.site we=
nt down due to gen failed to start //Grid return(investigation ongoinng)","=
gaelle.njiofack@matech-cameroun.com","847","14-05-2025 05:19:12","MATECH CM=
R"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005015590","MBA=
LNGONG LYCEE","","14-05-2025 04:23:39","14-05-2025 04:08:13","14-05-2025 10=
:31:36","(Very unstable) Site went down because Gen stopped due to overload=
(9kva, 130A) SS IHS Felix Zambe is informed and confirmed ","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","(Very unstable) S=
ite went down because Gen stopped due to overload(9kva, 130A) SS IHS Felix =
Zambe is informed and confirmed ","loic.noumsi@matech-cameroun.com","927","=
14-05-2025 04:23:39","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005014814","B=
arriere","","14-05-2025 00:28:17","13-05-2025 23:15:58","14-05-2025 00:37:1=
6","Active//No power issue on site Ubay: 54.42V site on Grid TX Fme SAMBA (=
654266058/Huawei) is informed","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue on site Ubay: 54.42V site on Grid TX Fme SAMBA (654266058/Huawei) i=
s informed","loic.noumsi@matech-cameroun.com","4340","14-05-2025 00:28:17",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005014694","E=
ssomba","","14-05-2025 00:00:07","13-05-2025 23:52:54","14-05-2025 01:55:46=
","Site went down because 03/06 rectifiers dysfunctionned // He reset it an=
d site on grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down because 03/06 rectifiers dysfunctionned=
 // He reset it and site on grid","kouoh.jean@ihstowers.com","434","14-05-2=
025 00:00:07","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005014564","O=
kola OCM","","13-05-2025 23:26:26","13-05-2025 23:21:11","14-05-2025 01:04:=
13","Grid outage, site went down due to Grid fluctuations and no RCP // He =
bypassed Grid and put site on Gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid outage, s=
ite went down due to Grid fluctuations and no RCP // He bypassed Grid and p=
ut site on Gen","cedric.tiani@matech-cameroun.com","317","13-05-2025 23:26:=
26","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0005014438","SAA=
 Entrance","","13-05-2025 22:49:25","13-05-2025 22:44:14","13-05-2025 23:07=
:20","Grid outage, site went down due to Grid bad voltage // He bypassed Gr=
id and put site on Gen","Parker Tchoup","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","Grid outage, site went down due to G=
rid bad voltage // He bypassed Grid and put site on Gen","cedric.tiani@mate=
ch-cameroun.com","312","13-05-2025 22:49:25","MATECH CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0005014387","E=
kounou","","13-05-2025 22:39:38","13-05-2025 21:40:27","13-05-2025 23:22:20=
","Site went down due to disjunction in the ocm BTS // He rearmed CB","Albr=
an Byorel","Equipment Repair","Passive","Control Panel","BTS Breaker Trippe=
d","Site went down due to disjunction in the ocm BTS // He rearmed CB","gae=
lle.njiofack@matech-cameroun.com","3552","13-05-2025 22:39:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005014367","MEHANDAN=
","","13-05-2025 22:32:12","13-05-2025 22:27:53","13-05-2025 22:38:55","Cas=
caded Incident from TTO5145903","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,site went down because GE=
N failed to start due to ATS and Gen card faulty // grid returned	","system=
","1214302","13-05-2025 22:32:12","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005014359","O=
dza II OCM","IHS_YND_528","13-05-2025 22:31:00","13-05-2025 22:27:53","13-0=
5-2025 22:48:55","Grid outage ,site went down because GEN failed to start d=
ue to ATS and Gen card faulty // grid returned	","Albran Byorel","Equipment=
 Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage ,site went =
down because GEN failed to start due to ATS and Gen card faulty // grid ret=
urned	","gaelle.njiofack@matech-cameroun.com","189","13-05-2025 22:31:00","=
MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005014088","M=
endong vallee","","13-05-2025 21:34:30","13-05-2025 21:27:18","14-05-2025 0=
9:42:40","Grid outage site went down because Gen overload (20KVA; 300A) IHS=
 F=E9lix Zamb=E9 is informed and confirmed // Grid return","Fanda Brice","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site w=
ent down because Gen overload (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed=
 and confirmed // Grid return","vanel.mbiada@matech-cameroun.com","433","13=
-05-2025 21:34:30","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005014021","MBA=
LNGONG LYCEE","","13-05-2025 21:22:00","13-05-2025 20:58:51","13-05-2025 22=
:36:34","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down be=
cause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informe=
d and confirmed // Grid returned","cedric.tiani@matech-cameroun.com","1391"=
,"13-05-2025 21:22:00","MATECH CMR"
"Closed Complete","Site Down","T0638","IHS_YND_318","NOCINC0005013718","SOA=
 University","","13-05-2025 20:27:46","13-05-2025 20:21:38","13-05-2025 20:=
29:54","Grid outage,site went down because gen failed to start due to grid =
bad voltage(01 phases off)//he did a bridge with the good phase","Siligap B=
oris","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid outage,site went down because gen failed to start due to grid bad=
 voltage(01 phases off)//he did a bridge with the good phase","cedric.tiani=
@matech-cameroun.com","369","13-05-2025 20:27:46","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005013648","M=
ontee-Des-Soeurs","","13-05-2025 20:14:29","13-05-2025 20:02:21","13-05-202=
5 20:22:53","ACTIVE //No power issue, site on Grid with Ubaie =3D49.7 V The=
 Tx FME Hosiah //674007438 is informed.","Hyemafo Gildas","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIV=
E //No power issue, site on Grid with Ubaie =3D49.7 V The Tx FME Hosiah //6=
74007438 is informed.","vanel.mbiada@matech-cameroun.com","729","13-05-2025=
 20:14:29","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005013589","O=
kola OCM","","13-05-2025 20:08:30","13-05-2025 20:02:13","13-05-2025 20:11:=
06","	Active No power issue on site ; U=3D54,6 V site on Gen the TX FME Moh=
amadou(691144435) of Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","	Active No power issue on site ; U=3D54,6 V site on Gen the TX FME Moh=
amadou(691144435) of Huawei is informed","vanel.mbiada@matech-cameroun.com"=
,"378","13-05-2025 20:08:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005013456","Angongo"=
,"","13-05-2025 19:43:06","13-05-2025 18:13:47","13-05-2025 19:13:15","Casc=
aded Incident from TTO5144392","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen s=
tart and stopped due to high temp // He added water and manually start the =
gen","system","265807","13-05-2025 19:43:06","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005013444","Nko=
abang2","","13-05-2025 19:39:01","13-05-2025 19:36:55","13-05-2025 21:36:45=
","Grid outage gen failed to start due to gen overload(22kva,310A)//Grid re=
turn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage gen failed to start due to gen overload(22kva,310A)//G=
rid return","cedric.tiani@matech-cameroun.com","127","13-05-2025 19:39:01",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0005013327","O=
kola OCM","","13-05-2025 19:12:17","13-05-2025 19:04:11","13-05-2025 19:31:=
34","Active No power issue on site ; U=3D54,6 V site on Gen the TX FME Moha=
madou(691144435) of Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active No power issue on site ; U=3D54,6 V site on Gen the TX FME Moham=
adou(691144435) of Huawei is informed","vanel.mbiada@matech-cameroun.com","=
487","13-05-2025 19:12:17","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005013318","E=
mana lycee 2","","13-05-2025 19:09:16","13-05-2025 19:03:43","13-05-2025 19=
:20:43","Grid outage , site went down before Gen failed to started due to p=
oor battery backup// Site on Grid","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage , site we=
nt down before Gen failed to started due to poor battery backup// Site on G=
rid","vanel.mbiada@matech-cameroun.com","334","13-05-2025 19:09:16","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0005013201","M=
efou-Assi","","13-05-2025 18:46:13","13-05-2025 18:38:59","13-05-2025 21:34=
:07","Site went down because Gen overload(15kva,200 A) IHS SS Felix Zambe i=
s informed and confirmed // He reduced the load and manually started the Ge=
n","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Site went down because Gen overload(15kva,200 A) IHS SS Felix Zambe is inf=
ormed and confirmed // He reduced the load and manually started the Gen","v=
anel.mbiada@matech-cameroun.com","435","13-05-2025 18:46:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0005013198","MEFOU AS=
SI","","13-05-2025 18:45:33","13-05-2025 18:38:38","13-05-2025 18:51:59","C=
ascaded Incident from TTO5144556","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on grid with U=3D53.1=
V Mbah Osiah from Huawei is informed","system","271438","13-05-2025 18:45:3=
3","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0005013190","S=
IMBOCK BONAMBAPE","IHS_YND_537","13-05-2025 18:44:23","13-05-2025 18:38:38"=
,"13-05-2025 18:51:59","No power issue site on grid with U=3D53.1V Mbah Osi=
ah from Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on grid with U=3D53.1V Mbah Osiah from Huawei is informed","vanel.mbiada@=
matech-cameroun.com","346","13-05-2025 18:44:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_141","NOCINC0005013136","New-Marc=
he-Melen","","13-05-2025 18:30:53","13-05-2025 16:16:54","13-05-2025 16:57:=
25","Cascaded Incident from TTO5143611","Paul BIBOUM","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, site went down beca=
use gen start and stopped due to high temp // He added water and manually s=
tart the gen","system","279848","13-05-2025 18:30:53","MATECH CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0005013121","A=
n-Marche-Melen","IHS_YND_141","13-05-2025 18:27:58","13-05-2025 18:24:42","=
14-05-2025 22:08:34","Grid outage,no space to deploy mobile gen// grid powe=
r return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Is=
sue","Grid outage,no space to deploy mobile gen// grid power return","vanel=
.mbiada@matech-cameroun.com","197","13-05-2025 18:27:58","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0005013112","Nom=
ayos montee Meche","","13-05-2025 18:25:08","13-05-2025 18:23:56","13-05-20=
25 18:25:16","Active//No power issues iste on Grid with U=3D54.1V ,The FME =
TX Fulbert (654266068) from Huawei is informed	","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issues iste on Grid with U=3D54.1V ,The FME TX Fulbert (65=
4266068) from Huawei is informed	","cedric.tiani@matech-cameroun.com","73",=
"13-05-2025 18:25:08","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005013108","Jou=
vence Mbenda","","13-05-2025 18:24:16","13-05-2025 18:15:06","13-05-2025 18=
:44:58","Grid fluctuation,site went down because Gen failed to start due to=
 grid bad voltage(lack of 1 phase)//He made a bridge with the Good phases",=
"Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid fluctuation,site went down because Gen failed to start=
 due to grid bad voltage(lack of 1 phase)//He made a bridge with the Good p=
hases","cedric.tiani@matech-cameroun.com","551","13-05-2025 18:24:16","MATE=
CH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0005013058","Ebe=
ba","IHS_YND_335","13-05-2025 18:16:05","13-05-2025 18:13:47","13-05-2025 1=
9:13:15","Grid outage, site went down because gen start and stopped due to =
high temp // He added water and manually start the gen","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because gen start and stopped due to h=
igh temp // He added water and manually start the gen","cedric.tiani@matech=
-cameroun.com","139","13-05-2025 18:16:05","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0005013026","Jou=
vence Mbenda","","13-05-2025 18:08:25","13-05-2025 18:00:16","13-05-2025 18=
:08:16","Grid outage site went down because Gen failed to start due to poor=
 Battery backup// Gen automatically  started","Hyemafo Gildas","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
 site went down because Gen failed to start due to poor Battery backup// Ge=
n automatically  started","cedric.tiani@matech-cameroun.com","490","13-05-2=
025 18:08:25","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0005012997","M=
endong vallee","","13-05-2025 18:02:17","13-05-2025 17:59:11","13-05-2025 2=
1:13:34","Grid outage site went down because Gen over load (20KVA; 300A)  I=
HS F=E9lix Zamb=E9 is informed and confirmed //Grid return","Fanda Brice","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","=
Grid outage site went down because Gen over load (20KVA; 300A)  IHS F=E9lix=
 Zamb=E9 is informed and confirmed //Grid return","vanel.mbiada@matech-came=
roun.com","187","13-05-2025 18:02:17","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005012859","E=
MANA BILICK CITY","","13-05-2025 17:38:43","13-05-2025 17:34:29","13-05-202=
5 19:11:58","Grid outage, Site went down because Landlord forbidden to star=
t the Gen due to Noise //Grid return","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Emergency Stop","Grid outage, Site went down b=
ecause Landlord forbidden to start the Gen due to Noise //Grid return","van=
el.mbiada@matech-cameroun.com","256","13-05-2025 17:38:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005012761","Emana Ly=
cee","","13-05-2025 17:30:42","13-05-2025 17:27:29","13-05-2025 17:43:09","=
Cascaded Incident from TTO5144052","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down beca=
use Gen failed to started due to poor battery backup// Gen automatically st=
arted","system","261247","13-05-2025 17:30:42","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005012758","E=
mana lycee 2","IHS_YND_274","13-05-2025 17:29:45","13-05-2025 17:27:29","13=
-05-2025 17:43:31","Grid outage , site went down because Gen failed to star=
ted due to poor battery backup// Gen automatically started","Fabrice Pouaka=
m","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid outage , site went down because Gen failed to started due to poor =
battery backup// Gen automatically started","vanel.mbiada@matech-cameroun.c=
om","137","13-05-2025 17:29:45","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005012734","M=
essassi 2","","13-05-2025 17:26:30","13-05-2025 17:24:03","13-05-2025 17:37=
:14","Grid outage site went down because Gen failed to start due to poor Ba=
ttery backup// Grid power return","Fabrice Pouakam","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage site went =
down because Gen failed to start due to poor Battery backup// Grid power re=
turn","vanel.mbiada@matech-cameroun.com","149","13-05-2025 17:26:30","MATEC=
H CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0005012722","Ako=
k Ndoe Yde","","13-05-2025 17:20:21","13-05-2025 17:10:59","13-05-2025 17:5=
6:56","Grid outage site went down because Gen failed to start due to poor B=
attery backup// Gen manually started","Hyemafo Gildas","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site we=
nt down because Gen failed to start due to poor Battery backup// Gen manual=
ly started","cedric.tiani@matech-cameroun.com","563","13-05-2025 17:20:21",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005012668","C=
rf Cornier","","13-05-2025 17:09:56","13-05-2025 17:04:48","13-05-2025 17:1=
3:01","ACTIVE //No power issue Ubaie=3D 49.7V site on Grid Armand NGUETSA /=
/ 699949553// from huawei is informed,","MINKA NICOLAS","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE =
//No power issue Ubaie=3D 49.7V site on Grid Armand NGUETSA // 699949553// =
from huawei is informed,","vanel.mbiada@matech-cameroun.com","310","13-05-2=
025 17:09:56","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0005012661","Men=
dong NB","","13-05-2025 17:08:13","13-05-2025 17:04:06","13-05-2025 17:05:1=
0","Wrongly created ticket","","Incorrectly Logged Tickets","Error","Error"=
,"Error","Wrongly created ticket","cedric.tiani@matech-cameroun.com","248",=
"13-05-2025 17:08:13","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0005012585","E=
bogo","","13-05-2025 17:01:20","13-05-2025 16:54:03","13-05-2025 17:10:18",=
"Grid fluctuation, Site went down before Gen start due to poor backup// Gri=
d return","Siligap Boris","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid fluctuation, Site went down before Gen star=
t due to poor backup// Grid return","vanel.mbiada@matech-cameroun.com","439=
","13-05-2025 17:01:20","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0005012495","B=
arriere","","13-05-2025 16:44:31","13-05-2025 16:36:59","13-05-2025 21:40:1=
4","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed //Grid returned","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and=
 confirmed //Grid returned","vanel.mbiada@matech-cameroun.com","454","13-05=
-2025 16:44:31","MATECH CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0005012373","N=
guila","IHS_YND_141","13-05-2025 16:24:33","13-05-2025 16:16:54","13-05-202=
5 17:01:10","Grid outage, site went down because gen start and stopped due =
to high temp // He added water and manually start the gen","Parker Tchoup",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, site went down because gen start and stopped due=
 to high temp // He added water and manually start the gen","vanel.mbiada@m=
atech-cameroun.com","460","13-05-2025 16:24:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0005012118","H-Franco=
 New","","13-05-2025 15:33:32","13-05-2025 15:27:12","13-05-2025 16:36:55",=
"Cascaded Incident from TTO5143314","Delor Telezing","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue, site is on Grid with=
 Ubaie =3D52.9V. The TX Armand Nguetsa (699949553) from Huawei is informed"=
,"system","275889","13-05-2025 15:33:32","MATECH CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0005012109","D=
joungolo","IHS_YND_711","13-05-2025 15:32:23","13-05-2025 15:27:12","13-05-=
2025 17:36:55","No power issue, site is on Grid with Ubaie =3D52.9V. The TX=
 Armand Nguetsa (699949553) from Huawei is informed.","Mboua Thierry","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue, site is on Grid with Ubaie =3D52.9V. The TX Armand N=
guetsa (699949553) from Huawei is informed","vanel.mbiada@matech-cameroun.c=
om","312","13-05-2025 15:32:23","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005012104","Elo=
umdem stade","","13-05-2025 15:30:37","13-05-2025 15:28:21","13-05-2025 18:=
12:53","Grid outage ,site went down because Gen failed to start due to Gen =
overload(13kva//140A) SS HIS felix zambe is informed//He reduiced the load =
and manually started the Gen","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage ,site went down because Gen failed =
to start due to Gen overload(13kva//140A) SS HIS felix zambe is informed//H=
e reduiced the load and manually started the Gen","cedric.tiani@matech-came=
roun.com","137","13-05-2025 15:30:37","MATECH CMR"
"Closed Complete","Site Down","CTR_431","IHS_YND_321","NOCINC0005012093","S=
oa","","13-05-2025 15:28:44","13-05-2025 15:25:49","13-05-2025 15:45:10","G=
rid outage, Site went down because Gen failed to start with ""overcurrent""=
 alarm// He balanced the load,reset the Gen card  and started Gen manually"=
,"Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, Site went down because Gen failed to start with ""overcu=
rrent"" alarm// He balanced the load and started Gen manually","vanel.mbiad=
a@matech-cameroun.com","176","13-05-2025 15:28:44","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005011967","Nta=
ba","","13-05-2025 15:05:40","13-05-2025 15:00:29","13-05-2025 15:18:44","s=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","site went down due to PWC Overload(12Kw 2=
50A) Blaise Raoul SS IHS is iformed //Site stabilised","cedric.tiani@matech=
-cameroun.com","312","13-05-2025 15:05:40","MATECH CMR"
"Closed Complete","Site Down","T0288","IHS_YND_001","NOCINC0005011930","Roy=
al Hotel Yde","","13-05-2025 14:57:36","13-05-2025 14:53:28","13-05-2025 15=
:03:10","Active //No power issue on site ,site on Grid with Ubaie=3D53.9 V =
The  Brice Tsague(650214096) from Huawei is working on site.","Paul BIBOUM"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active //No power issue on site ,site on Grid with Ubaie=3D53.=
9 V The  Brice Tsague(650214096) from Huawei is working on site.","cedric.t=
iani@matech-cameroun.com","248","13-05-2025 14:57:36","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005011898","AKA=
K Nkozoa","","13-05-2025 14:54:05","13-05-2025 14:51:50","13-05-2025 15:41:=
17","Site went due to 03/04 rectifiers dysfunctionning//He reset it ","Fabr=
ice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","S=
ite went due to 03/04 rectifiers dysfunctionning//He reset it ","cedric.tia=
ni@matech-cameroun.com","136","13-05-2025 14:54:05","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005011895","M=
ontee-Des-Soeurs","","13-05-2025 14:53:58","13-05-2025 14:49:50","13-05-202=
5 14:54:18","Active // No power issue, site is on grid with Ubaie: 53.96V, =
Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue, site is on grid with Ubaie: 53.96V, Mbah hosiah=
(699699694) from Huawei is informed","vanel.mbiada@matech-cameroun.com","24=
9","13-05-2025 14:53:58","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005011883","N=
koabang Ebolmedjock","","13-05-2025 14:49:07","13-05-2025 14:45:40","13-05-=
2025 14:59:26","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matec=
h-cameroun.com","208","13-05-2025 14:49:07","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0005011783","Mok=
olo Yaounde","","13-05-2025 14:34:09","13-05-2025 14:30:56","13-05-2025 14:=
37:27","Active // No power issue Ubay: 53V site on grid. The Tx FME Eloundo=
u Bertrand (693212405) from Huawei is informed","","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue Ubay: 53V site on grid. The Tx FME Eloundou Bertrand (69321240=
5) from Huawei is informed","cedric.tiani@matech-cameroun.com","194","13-05=
-2025 14:34:09","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0005011776","Saa=
","","13-05-2025 14:33:21","13-05-2025 14:32:07","13-05-2025 14:34:57","Gri=
d outage , site went down because Gen failed to started due to poor battery=
 backup// Gen automatically started","Parker Tchoup","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage , site we=
nt down because Gen failed to started due to poor battery backup// Gen auto=
matically started","cedric.tiani@matech-cameroun.com","75","13-05-2025 14:3=
3:21","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005011751","Ema=
na lycee 2","","13-05-2025 14:27:10","13-05-2025 14:25:00","13-05-2025 14:4=
0:59","Grid outage , site went down because Gen failed to started due to po=
or battery backup// Gen automatically started","Fabrice Pouakam","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge , site went down because Gen failed to started due to poor battery backu=
p// Gen automatically started","franck.nkomot@matech-cameroun.com","131","1=
3-05-2025 14:27:10","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0005011703","EKI=
E","","13-05-2025 14:17:57","13-05-2025 14:09:47","13-05-2025 14:41:11","Si=
te went down due to CB(63A)PWC that tripped MTN //He rearmed ","Albran Byor=
el","Equipment Repair","Passive","Rectifier","Rectifier - Circuit Breaker",=
"Site went down due to CB(63A)PWC that tripped MTN //He rearmed ","franck.n=
komot@matech-cameroun.com","491","13-05-2025 14:17:57","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0005011460","S=
tade-Abega","","13-05-2025 13:47:37","13-05-2025 13:45:26","13-05-2025 14:1=
3:46","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // He reset controller and gen manually start","Mba Lazare H=
erve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, site went down because gen failed to start due to PWC ZTE m=
alfunction // He reset controller and gen manually start","edwige.kapawo@ma=
tech-cameroun.com","132","13-05-2025 13:47:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_148","NOCINC0005011275","Chapelle=
-Nsimeyong","","13-05-2025 13:14:13","13-05-2025 12:41:59","13-05-2025 14:3=
6:37","Cascaded Incident from TTO5142374","MINKA NICOLAS","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive",":Grid outage,site went down =
due to Main generator faulty//grid power return","system","271193","13-05-2=
025 13:14:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0005011274","Accacia =
New","","13-05-2025 13:14:12","13-05-2025 12:41:59","13-05-2025 14:36:37","=
Cascaded Incident from TTO5142374","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive",":Grid outage,site went down due to Main generato=
r faulty//grid power return","system","271194","13-05-2025 13:14:12","MATEC=
H CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0005011215","ELO=
UMDEM CARRIERE","","13-05-2025 13:05:32","13-05-2025 12:24:59","13-05-2025 =
13:48:37","Grid outage, site went down because gen start and stopped due to=
 low oil pressure* // He reset the gen card and manually start the gen","Fa=
nda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, site went down because gen start and stopped due to low oil pr=
essure* // He reset the gen card and manually start the gen","franck.nkomot=
@matech-cameroun.com","2434","13-05-2025 13:05:32","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0005011134","Nko=
l-Mbanda","IHS_YND_562, IHS_YND_148","13-05-2025 12:50:17","13-05-2025 12:4=
1:59","13-05-2025 14:46:00",":Grid outage,site went down due to Main genera=
tor faulty//grid power return","MINKA NICOLAS","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Generator Faulty",":Grid outage,site went down due to M=
ain generator faulty//grid power return","franck.nkomot@matech-cameroun.com=
","499","13-05-2025 12:50:17","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005010983","F=
OUGEROLE","","13-05-2025 12:22:23","13-05-2025 12:14:10","13-05-2025 12:50:=
07","Grid outage, site went down because gen start and stopped with high te=
mp alarm // He added water and manually start the gen","Siligap Boris","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Leve=
l Issue","Grid outage, site went down because gen start and stopped with hi=
gh temp alarm // He added water and manually start the gen","edwige.kapawo@=
matech-cameroun.com","494","13-05-2025 12:22:23","MATECH CMR"
"Closed Complete","Site Down","T1328","IHS_YND_247","NOCINC0005010922","Oko=
lo","","13-05-2025 12:15:07","13-05-2025 12:06:58","13-05-2025 14:01:40","S=
ite went down due to PSC3 Controller dysfunctionning// He reset it","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Site went down due to PSC3 Controller dysfunctionning// He reset it","franc=
k.nkomot@matech-cameroun.com","490","13-05-2025 12:15:07","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0005010859","A=
wae Ewonkan","","13-05-2025 12:00:28","13-05-2025 11:57:15","13-05-2025 12:=
58:15","Grid outage site went down due to Gen overload (20kva,300A)//We red=
uce load and gen manually started","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid outage site went down due to Gen ov=
erload (20kva,300A)//We reduce load and gen manually started","edwige.kapaw=
o@matech-cameroun.com","195","13-05-2025 12:00:28","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0005010835","Nsi=
meyong","","13-05-2025 11:51:10","13-05-2025 11:42:59","13-05-2025 12:20:50=
","Grid outage gen failed to start due to alarm high temp//We added water a=
nd gen manually started","MINKA NICOLAS","Equipment Repair","Passive","ACDG=
 Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage gen fail=
ed to start due to alarm high temp//We added water and gen manually started=
","franck.nkomot@matech-cameroun.com","491","13-05-2025 11:51:10","MATECH C=
MR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005010819","M=
ontee-Des-Soeurs","","13-05-2025 11:46:08","13-05-2025 11:41:44","13-05-202=
5 12:18:39",":Grid outage site went down due to Gen overload (15kva,130A)//=
We reduce load and gen manually started","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload",":Grid outage site went down due t=
o Gen overload (15kva,130A)//We reduce load and gen manually started","fran=
ck.nkomot@matech-cameroun.com","266","13-05-2025 11:46:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0005010591","Ngoulmek=
ong-Nord","","13-05-2025 11:02:03","13-05-2025 10:16:20","13-05-2025 10:48:=
39","Cascaded Incident from TTO5141521","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
fore DG start due to Poor Batteries backup//manual start of Gen","system","=
272839","13-05-2025 11:02:03","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0005010365","M=
ontee-Des-Soeurs","","13-05-2025 10:27:28","13-05-2025 10:21:18","13-05-202=
5 10:58:58","Grid outage site went down due to Gen overload (15kva,130A)//W=
e reduce load and gen manually started","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to =
Gen overload (15kva,130A)//We reduce load and gen manually started","edwige=
.kapawo@matech-cameroun.com","372","13-05-2025 10:27:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0005010324","Nkolfoul=
ou Tsinga Village","","13-05-2025 10:23:37","13-05-2025 10:16:20","13-05-20=
25 11:43:20","Cascaded Incident from TTO5141256 - Cascade Removed From TTO5=
141256","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, site went down before DG start due to Poor Batter=
ies backup//manual start of Gen","system","272841","13-05-2025 10:23:37","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005010321","SOA VILL=
AGE","","13-05-2025 10:23:36","13-05-2025 10:16:20","13-05-2025 11:43:20","=
Cascaded Incident from TTO5141256 - Cascade Removed From TTO5141256","Silig=
ap Boris","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage, site went down before DG start due to Poor Batteries backup//ma=
nual start of Gen","system","272842","13-05-2025 10:23:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_758","NOCINC0005010322","Nkolfoul=
ou CSD MTN","","13-05-2025 10:23:36","13-05-2025 10:16:20","13-05-2025 11:4=
3:20","Cascaded Incident from TTO5141256 - Cascade Removed From TTO5141256"=
,"Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage, site went down before DG start due to Poor Batteries bac=
kup//manual start of Gen","system","272843","13-05-2025 10:23:36","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_296","NOCINC0005010323","Nkolfoul=
ou","IHS_YND_561, IHS_YND_269, IHS_YND_277, IHS_YND_719, IHS_YND_323, IHS_Y=
ND_758, IHS_YND_759","13-05-2025 10:23:36","13-05-2025 10:16:20","13-05-202=
5 11:43:20","Grid outage, site went down before DG start due to Poor Batter=
ies backup//manual start of Gen","Siligap Boris","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage, site went down before DG=
 start due to Poor Batteries backup//manual start of Gen","system","436","1=
3-05-2025 10:23:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0005010320","TSINGA V=
ILLAGE 2","","13-05-2025 10:23:35","13-05-2025 10:16:20","13-05-2025 11:43:=
20","Cascaded Incident from TTO5141256 - Cascade Removed From TTO5141256","=
Delor Telezing","Cascade Outage","Passive","Cascade Passive","Cascade Passi=
ve","Grid outage, site went down before DG start due to Poor Batteries back=
up//manual start of Gen","system","272843","13-05-2025 10:23:35","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0005010318","FOUGEROL=
E","","13-05-2025 10:23:35","13-05-2025 10:16:20","13-05-2025 11:43:20","Ca=
scaded Incident from TTO5141256 - Cascade Removed From TTO5141256","Siligap=
 Boris","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Gri=
d outage, site went down before DG start due to Poor Batteries backup//manu=
al start of Gen","system","272842","13-05-2025 10:23:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0005010319","Mvog-Eba=
nda","","13-05-2025 10:23:35","13-05-2025 10:16:20","13-05-2025 11:43:20","=
Cascaded Incident from TTO5141256 - Cascade Removed From TTO5141256","Silig=
ap Boris","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage, site went down before DG start due to Poor Batteries backup//ma=
nual start of Gen","system","272842","13-05-2025 10:23:35","MATECH CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0005010283","Nko=
lfoulou 2","","13-05-2025 10:20:18","13-05-2025 10:16:20","13-05-2025 11:25=
:23","Grid outage, gen ran until fuel shortage//Refueling done","Siligap Bo=
ris","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, gen ran=
 until fuel shortage//Refueling done","franck.nkomot@matech-cameroun.com","=
239","13-05-2025 10:20:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0005010261","MEHANDAN=
","","13-05-2025 10:16:04","13-05-2025 10:10:34","13-05-2025 10:34:14","Cas=
caded Incident from TTO5141218","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,site went down because GE=
N failed to start due to ATS and Gen card faulty // grid returned	","system=
","1215299","13-05-2025 10:16:04","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0005010252","O=
dza II OCM","IHS_YND_528","13-05-2025 10:14:47","13-05-2025 10:10:34","13-0=
5-2025 10:34:43","Grid outage ,site went down because GEN failed to start d=
ue to ATS and Gen card faulty // grid returned	","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site wen=
t down because GEN failed to start due to ATS and Gen card faulty // grid r=
eturned	","edwige.kapawo@matech-cameroun.com","254","13-05-2025 10:14:47","=
MATECH CMR"
"Closed Complete","Site Down","CTR_011","IHS_YND_196","NOCINC0005010046","P=
DC","","13-05-2025 09:43:50","13-05-2025 09:38:36","13-05-2025 10:29:58","S=
ite went down due to work of SS HIS Francois was on site for work(Swapped o=
f PWC ZTE)//End of work","Mboua Thierry","Installation Activity","Passive",=
"Planned Activity","Installation Activity","Site went down due to work of S=
S HIS Francois was on site for work(Swapped of PWC ZTE)//End of work","edwi=
ge.kapawo@matech-cameroun.com","315","13-05-2025 09:43:50","MATECH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0005010035","Lob=
o 2","","13-05-2025 09:40:38","13-05-2025 09:31:59","13-05-2025 12:53:48","=
Grid outage site went down because Gen failed to start due to Hybrid system=
 dysfonction // He reset the hybrid system and Gen manually started","TIENT=
CHEU NZETCHIEU GAEL","Equipment Repair","Passive","Hybrid","Hybrid Module",=
"Grid outage site went down because Gen failed to start due to Hybrid syste=
m dysfonction // He reset the hybrid system and Gen manually started","fran=
ck.nkomot@matech-cameroun.com","520","13-05-2025 09:40:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0005009899","Messassi=
","","13-05-2025 09:09:53","13-05-2025 08:56:15","13-05-2025 09:43:20","Cas=
caded Incident from TTO5140789","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation.site went due to la=
ck of phases //Grid power stabilized","system","284839","13-05-2025 09:09:5=
3","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0005009900","Nyom OCM=
","","13-05-2025 09:09:53","13-05-2025 08:56:15","13-05-2025 09:43:20","Cas=
caded Incident from TTO5140789","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation.site went due to la=
ck of phases //Grid power stabilized","system","284839","13-05-2025 09:09:5=
3","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0005009902","Nkolondo=
m","","13-05-2025 09:09:53","13-05-2025 08:56:15","13-05-2025 09:43:20","Ca=
scaded Incident from TTO5140789","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation.site went due to l=
ack of phases //Grid power stabilized","system","284840","13-05-2025 09:09:=
53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0005009897","NKOLMEKO=
NG YDE","","13-05-2025 09:09:52","13-05-2025 08:56:15","13-05-2025 09:43:20=
","Cascaded Incident from TTO5140789","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation.site went due=
 to lack of phases //Grid power stabilized","system","284838","13-05-2025 0=
9:09:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0005009898","Olembe-T=
erminus","","13-05-2025 09:09:52","13-05-2025 08:56:15","13-05-2025 09:43:2=
0","Cascaded Incident from TTO5140789","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation.site went du=
e to lack of phases //Grid power stabilized","system","284840","13-05-2025 =
09:09:52","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0005009885","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_304","13-05-2025 09:05:32","13-05-2025 08:56:15","13-05-=
2025 09:43:20","Grid fluctuation.site went due to lack of phases //Grid pow=
er stabilized","Fabrice Pouakam","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation.site went due to lack of p=
hases //Grid power stabilized","rouselle.schoune@ihstowers.com","558","13-0=
5-2025 09:05:32","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0005009695","C=
RF Nkoabang","","13-05-2025 08:39:20","13-05-2025 08:34:08","13-05-2025 09:=
39:12","Solar Only, site down due to sunset  // Sun shine return ","Mba Laz=
are Herve","Equipment Repair","Passive","Solar","Solar Panel Issue","Solar =
Only, site down due to sunset  // Sun shine return ","edwige.kapawo@matech-=
cameroun.com","313","13-05-2025 08:39:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0005009661","SOA VILL=
AGE","","13-05-2025 08:32:20","13-05-2025 08:09:29","13-05-2025 08:53:13","=
Cascaded Incident from TTO5140438","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen start and stopped with ""High temps ""alarm // he added water and manu=
ally start the Gen","system","266162","13-05-2025 08:32:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005009632","Messassi=
 okolo","","13-05-2025 08:30:02","13-05-2025 08:24:14","13-05-2025 14:13:35=
","Cascaded Incident from TTO5140487","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage Site went down bec=
ause Landlord forbidden to start the Gen due to Noise //Grid return","syste=
m","286880","13-05-2025 08:30:02","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005009621","E=
MANA BILICK CITY","IHS_YND_279","13-05-2025 08:28:42","13-05-2025 08:24:14"=
,"13-05-2025 14:17:21","Grid outage Site went down because Landlord forbidd=
en to start the Gen due to Noise //Grid return","Fabrice Pouakam","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid outage Site we=
nt down because Landlord forbidden to start the Gen due to Noise //Grid ret=
urn","edwige.kapawo@matech-cameroun.com","270","13-05-2025 08:28:42","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0005009577","M=
essassi 2","","13-05-2025 08:18:25","13-05-2025 08:09:59","13-05-2025 10:33=
:23","Site went down due to 04/06 rectifiers dysfunctionning //He reset it =
and site on Grid ","Fabrice Pouakam","Equipment Repair","Passive","Rectifie=
r","Rectifier Distribution","Site went down due to 04/06 rectifiers dysfunc=
tionning //He reset it and site on Grid ","edwige.kapawo@matech-cameroun.co=
m","508","13-05-2025 08:18:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005009572","Emana Ly=
cee","","13-05-2025 08:15:20","13-05-2025 08:12:59","13-05-2025 08:28:34","=
Cascaded Incident from TTO5140431","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down beca=
use Gen failed to started due to poor battery backup//  Gen automatically s=
tarted","system","265982","13-05-2025 08:15:20","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005009569","E=
mana lycee 2","IHS_YND_274","13-05-2025 08:14:44","13-05-2025 08:12:59","13=
-05-2025 08:29:11","Grid outage , site went down because Gen failed to star=
ted due to poor battery backup//  Gen automatically started","Fabrice Pouak=
am","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery L=
ow","Grid outage , site went down because Gen failed to started due to poor=
 battery backup//  Gen automatically started","edwige.kapawo@matech-camerou=
n.com","106","13-05-2025 08:14:44","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0005009564","S=
OA TOWN","IHS_YND_323","13-05-2025 08:13:40","13-05-2025 08:09:29","13-05-2=
025 08:53:13","Grid outage, Site went down because Gen start and stopped wi=
th ""High temps ""alarm // he added water and manually start the Gen","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp=
 - Coolant Level Issue","Grid outage, Site went down because Gen start and =
stopped with ""High temps ""alarm // he added water and manually start the =
Gen","edwige.kapawo@matech-cameroun.com","252","13-05-2025 08:13:40","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005009551","A=
WAE OCM","","13-05-2025 08:09:40","13-05-2025 08:05:59","13-05-2025 09:55:0=
5","grid outage, Site went down to due to PWC ""ZTE' dysfunction// he reset=
 it and started Gen","Mba Lazare Herve","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","grid outage, Site went down to due to =
PWC ""ZTE' dysfunction// he reset it and started Gen","edwige.kapawo@matech=
-cameroun.com","223","13-05-2025 08:09:40","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0005009544","C=
RF Nkoabang","","13-05-2025 08:06:35","13-05-2025 08:01:59","13-05-2025 08:=
16:36","Solar Only, site down due to sunset  // Sun shine return ","Mba Laz=
are Herve","Equipment Repair","Passive","Solar","Solar Panel Issue","Solar =
Only, site down due to sunset  // Sun shine return ","edwige.kapawo@matech-=
cameroun.com","277","13-05-2025 08:06:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005009509","Golf Qua=
ter","","13-05-2025 07:55:36","13-05-2025 07:50:16","13-05-2025 08:05:06","=
Cascaded Incident from TTO5140355","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage gen failed to start due=
 to card GE dysfunctioned // Grid returned","system","281655","13-05-2025 0=
7:55:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005009511","Bastos B=
ethesda","","13-05-2025 07:55:36","13-05-2025 07:50:16","13-05-2025 08:05:0=
6","Cascaded Incident from TTO5140355","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage gen failed to start=
 due to card GE dysfunctioned // Grid returned","system","281655","13-05-20=
25 07:55:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0005009510","Bastos-N=
ylon","","13-05-2025 07:55:36","13-05-2025 07:50:16","13-05-2025 08:05:06",=
"Cascaded Incident from TTO5140355","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage gen failed to start du=
e to card GE dysfunctioned // Grid returned","system","281654","13-05-2025 =
07:55:36","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0005009501","T=
singa","IHS_YND_220, IHS_YND_126, IHS_YND_563","13-05-2025 07:53:49","13-05=
-2025 07:50:16","13-05-2025 08:12:53","Grid outage gen failed to start due =
to card GE dysfunctioned // Grid returned","Mboua Thierry","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to s=
tart due to card GE dysfunctioned // Grid returned","edwige.kapawo@matech-c=
ameroun.com","214","13-05-2025 07:53:49","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005009402","Fla=
menco","","13-05-2025 07:35:29","13-05-2025 07:29:20","13-05-2025 08:01:42"=
,"Grid outage gen failed to start due to card GE dysfunctioned // Grid retu=
rned","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Grid outage gen failed to start due to card GE dysfunctioned // =
Grid returned","franck.nkomot@matech-cameroun.com","369","13-05-2025 07:35:=
29","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005009253","O=
LAMA","","13-05-2025 07:09:16","13-05-2025 07:01:59","13-05-2025 07:39:05",=
"Active // No power issue, Site on Gen, Ubaie: 54.9V The FME Tx Etienne/695=
033981 From Huawei is informed.","Fanda Brice","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No pow=
er issue, Site on Gen, Ubaie: 54.9V The FME Tx Etienne/695033981 From Huawe=
i is informed.","edwige.kapawo@matech-cameroun.com","438","13-05-2025 07:09=
:16","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005009245","NKO=
MKANA ELIZA HOTEL","","13-05-2025 07:08:54","13-05-2025 06:59:59","13-05-20=
25 07:59:27","Active//No power issue, Site on Grid Ubaie: 53.2V. The Tx FME=
 Brice Tsague(650214096) from Huawei is informed.","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue, Site on Grid Ubaie: 53.2V. The Tx FME Brice Tsague(650214096=
) from Huawei is informed.","franck.nkomot@matech-cameroun.com","535","13-0=
5-2025 07:08:54","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0005009109","Nko=
l-Mebanga","","13-05-2025 06:48:31","13-05-2025 06:44:11","13-05-2025 09:57=
:52","Active//No power issue on site Ubaie=3D49.8V site on Solar Tx FME Gre=
goire /654547479/Huawei is informed","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie=3D49.8V site on Solar Tx FME Gregoire /654547479=
/Huawei is informed","franck.nkomot@matech-cameroun.com","260","13-05-2025 =
06:48:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0005008454","Tsinga",=
"IHS_YND_220, IHS_YND_126, IHS_YND_563","13-05-2025 04:23:43","13-05-2025 0=
4:19:57","13-05-2025 04:33:27","Grid outage site went down before Gen start=
 due to poor battery backup // Grid restoration","Mboua Thierry","Equipment=
 Repair","Passive","ACDG Gen","DG Low Battery","Grid outage site went down =
before Gen start due to poor battery backup // Grid restoration","system","=
226","13-05-2025 04:23:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0005008453","Bastos B=
ethesda","","13-05-2025 04:23:42","13-05-2025 04:19:57","13-05-2025 04:33:2=
7","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage site went down before Gen start due to poor battery =
backup // Grid restoration","system","272598","13-05-2025 04:23:42","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0005008452","Golf Qua=
ter","","13-05-2025 04:23:42","13-05-2025 04:19:57","13-05-2025 04:33:27","=
","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Grid outage site went down before Gen start due to poor battery back=
up // Grid restoration","system","272599","13-05-2025 04:23:42","MATECH CMR=
"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0005008424","B=
astos-Nylon","","13-05-2025 04:22:06","13-05-2025 04:19:57","13-05-2025 04:=
33:27","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage site went down before Gen start due to poor batt=
ery backup // Grid restoration","christelle.ngonga@matech-cameroun.com","27=
2598","13-05-2025 04:22:06","MATECH CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0005008411","Mes=
sa Carriere","","13-05-2025 04:17:28","13-05-2025 04:10:12","13-05-2025 07:=
47:12","Grid outage,site went down because  CB(62A) of Gen disjuncted due t=
o grid distributor burning//He rearmed the and grid distributor replacement=
 ongoing","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - L=
oad Breaker","Grid outage,site went down because  CB(62A) of Gen disjuncted=
 due to grid distributor burning//He rearmed the and grid distributor repla=
cement ongoing","franck.nkomot@matech-cameroun.com","437","13-05-2025 04:17=
:28","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0005008331","Fla=
menco","","13-05-2025 03:57:02","13-05-2025 03:50:57","13-05-2025 04:38:08"=
,"Grid outage gen failed to start due to card GE dysfunctioned // Grid retu=
rned","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Grid outage gen failed to start due to card GE dysfunctioned // =
Grid returned","franck.nkomot@matech-cameroun.com","365","13-05-2025 03:57:=
02","MATECH CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0005008312","Mes=
sa Carriere","","13-05-2025 03:51:50","13-05-2025 03:44:34","13-05-2025 04:=
03:34","Grid outage site went down before Gen start due to poor battery bac=
kup // Gen automatically started","Mboua Thierry","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage site went do=
wn before Gen start due to poor battery backup // Gen automatically started=
","franck.nkomot@matech-cameroun.com","437","13-05-2025 03:51:50","MATECH C=
MR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0005008220","UPA=
C LP","","13-05-2025 03:07:31","13-05-2025 02:59:29","13-05-2025 03:05:29",=
"Active, no power issue, site on grid with U=3D54.4V Tx FME mand Ngetsa (??=
699949553??) From Huawei is informed.","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issu=
e, site on grid with U=3D54.4V Tx FME mand Ngetsa (??699949553??) From Huaw=
ei is informed.","franck.nkomot@matech-cameroun.com","484","13-05-2025 03:0=
7:31","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0005008188","C=
RF Nkoabang","","13-05-2025 02:49:33","13-05-2025 02:49:20","13-05-2025 07:=
57:19","Grid-solar site, Grid outage, site down due to sunset  // Sun shine=
 return ","Mba Lazare Herve","Equipment Repair","Passive","Solar","Solar Pa=
nel Issue","Grid-solar site, Grid outage, site down due to sunset  // Sun s=
hine return ","christelle.ngonga@matech-cameroun.com","103","13-05-2025 02:=
49:33","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005007940","O=
LAMA","","13-05-2025 01:10:34","13-05-2025 01:07:24","13-05-2025 01:11:18",=
"No power issue on site Ubaie =3D54.9V site on GEN. The TX FME Henri (69994=
9693) from Huawei is informed","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.9V site on GEN. The TX FME Henri (699949693) from Huawei i=
s informed","christelle.ngonga@matech-cameroun.com","191","13-05-2025 01:10=
:34","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005007724","AKA=
K Nkozoa","","13-05-2025 00:04:06","12-05-2025 23:56:30","13-05-2025 01:33:=
30","Grid fluctuation, site went down because Gen started and stopped to st=
art due to grid bad voltage // Grid return","Fabrice Pouakam","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on, site went down because Gen started and stopped to start due to grid bad=
 voltage // Grid return","franck.nkomot@matech-cameroun.com","457","13-05-2=
025 00:04:06","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005007526","MBA=
LNGONG LYCEE","","12-05-2025 23:14:43","12-05-2025 22:48:56","12-05-2025 23=
:42:56","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed//Grid return","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down becaus=
e Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informed an=
d confirmed//Grid return","franck.nkomot@matech-cameroun.com","1549","12-05=
-2025 23:14:43","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005007388","OBA=
M NGOLA OCM","","12-05-2025 22:41:16","12-05-2025 22:39:56","12-05-2025 22:=
45:56","Site went down due to insufficient rectifier on site//site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifier on site//site stabilised=
","franck.nkomot@matech-cameroun.com","81","12-05-2025 22:41:16","MATECH CM=
R"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0005007304","Mes=
sa Carriere","","12-05-2025 22:24:09","12-05-2025 22:22:58","12-05-2025 22:=
23:58","Grid outage site went down before Gen start due to poor battery bac=
kup // Gen automatically started","Mboua Thierry","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage site went do=
wn before Gen start due to poor battery backup // Gen automatically started=
","cedric.tiani@matech-cameroun.com","72","12-05-2025 22:24:09","MATECH CMR=
"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0005007213","Nko=
lbisson usines des eaux 2","","12-05-2025 22:05:10","12-05-2025 21:59:45","=
12-05-2025 23:08:15","Active: No power issue, site is on GEN with Ubaie=3D5=
1.7V. The Tx FME Mohamadou moaum ( 691144435 )of huawei is informed.","TIEN=
TCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","Active: No power issue, site is on GEN wi=
th Ubaie=3D51.7V. The Tx FME Mohamadou moaum ( 691144435 )of huawei is info=
rmed.","cedric.tiani@matech-cameroun.com","326","12-05-2025 22:05:10","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005007089","C=
rf Cornier","","12-05-2025 21:43:35","12-05-2025 21:34:25","12-05-2025 21:4=
7:51","Active, No power issue site on Grid with U=3D50.2VTX FME Armand Nges=
tsa (691144412)From huawei is informed","MINKA NICOLAS","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active,=
 No power issue site on Grid with U=3D50.2VTX FME Armand Ngestsa (691144412=
)From huawei is informed","gaelle.njiofack@matech-cameroun.com","551","12-0=
5-2025 21:43:35","MATECH CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0005007055","San=
ta Barbara Gottam","","12-05-2025 21:38:56","12-05-2025 21:29:59","12-05-20=
25 23:32:59","site down because Grid contactor did not glue // Grid contact=
or reseted and site left on grid.","Delor Telezing","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","site down because Grid contactor did=
 not glue // Grid contactor reseted and site left on grid.","cedric.tiani@m=
atech-cameroun.com","538","12-05-2025 21:38:56","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0005006920","N=
KOLMEKONG YDE","","12-05-2025 21:15:34","12-05-2025 21:11:23","12-05-2025 2=
2:47:23","Grid fluctuation, site went down because Gen failed to start due =
to PWC dysfonction // Grid Stabilized","Fabrice Pouakam","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuation, sit=
e went down because Gen failed to start due to PWC dysfonction // Grid Stab=
ilized","gaelle.njiofack@matech-cameroun.com","252","12-05-2025 21:15:34","=
MATECH CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0005006842","Mes=
sa Carriere","","12-05-2025 21:04:19","12-05-2025 21:02:10","12-05-2025 21:=
12:36","Grid outage site went down before Gen start due to poor battery bac=
kup // Gen automatically started","Mboua Thierry","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage site went do=
wn before Gen start due to poor battery backup // Gen automatically started=
","cedric.tiani@matech-cameroun.com","130","12-05-2025 21:04:19","MATECH CM=
R"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0005006678","D=
amas","","12-05-2025 20:40:46","12-05-2025 20:36:39","13-05-2025 07:54:14",=
"Acces issue due to landloard,Site went down due to CB(125A) in PWC that tr=
ipped ocm//He rearmed it","MINKA NICOLAS","Access Denial","Lease Or Legal",=
"Landlord Related Issues","Access Issue - Land Lord","Acces issue due to la=
ndloard,Site went down due to CB(125A) in PWC that tripped ocm//He rearmed =
it","gaelle.njiofack@matech-cameroun.com","248","12-05-2025 20:40:46","MATE=
CH CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0005006650","Mel=
en Ba'aba","","12-05-2025 20:34:58","12-05-2025 20:34:21","12-05-2025 22:07=
:55","Site down because one circuit breaker of 80 A  is HS  in the DC box, =
// CB remplacement done, site is on grid.","Siligap Boris","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site =
down because one circuit breaker of 80 A  is HS  in the DC box, // CB rempl=
acement done, site is on grid.","cedric.tiani@matech-cameroun.com","38","12=
-05-2025 20:34:58","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0005006634","N=
gousso-Savana","IHS_YND_561","12-05-2025 20:31:00","12-05-2025 20:14:47","1=
2-05-2025 22:37:47","Grid Outage, site went down before gen start due to po=
or battery backup // Gen start automatically","Siligap Boris","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage,=
 site went down before gen start due to poor battery backup // Gen start au=
tomatically","gaelle.njiofack@matech-cameroun.com","974","12-05-2025 20:31:=
00","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0005006605","OBA=
M NGOLA OCM","","12-05-2025 20:28:24","12-05-2025 20:27:13","12-05-2025 20:=
49:35","Site went down due to insufficient rectifier on site//site stabilis=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifier on site//site stabilised=
","cedric.tiani@matech-cameroun.com","72","12-05-2025 20:28:24","MATECH CMR=
"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0005006558","F=
OUGEROLE","","12-05-2025 20:20:07","12-05-2025 20:14:47","12-05-2025 21:30:=
53","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid Outage, site went down before gen start due to poor batter=
y backup // Gen start automatically","gaelle.njiofack@matech-cameroun.com",=
"272947","12-05-2025 20:20:07","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0005006525","AKA=
K Nkozoa","","12-05-2025 20:16:55","12-05-2025 20:16:47","12-05-2025 20:17:=
48","Grid fluctuation, site went down because Gen started and stopped to st=
art due to grid bad voltage // Grid return","Fabrice Pouakam","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on, site went down because Gen started and stopped to start due to grid bad=
 voltage // Grid return","cedric.tiani@matech-cameroun.com","9","12-05-2025=
 20:16:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0005006520","Nkoabang=
2","","12-05-2025 20:15:51","12-05-2025 20:06:11","12-05-2025 22:08:07","Ca=
scaded Incident from TTO5137005","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because 02/04 recti=
fiers dysfunctionned // He resetd rectifiers,site on Grid","system","302154=
","12-05-2025 20:15:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0005006519","NGONA","=
","12-05-2025 20:15:51","12-05-2025 20:06:11","12-05-2025 22:08:07","Cascad=
ed Incident from TTO5137005","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because 02/04 rectifier=
s dysfunctionned // He resetd rectifiers,site on Grid","system","302154","1=
2-05-2025 20:15:51","MATECH CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0005006488","N=
koabang","IHS_YND_295, IHS_YND_526","12-05-2025 20:12:18","12-05-2025 20:06=
:11","12-05-2025 22:08:07","Site went down because 02/04 rectifiers dysfunc=
tionned // He resetd rectifiers,site on Grid","Mba Lazare Herve","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","Site went down because 0=
2/04 rectifiers dysfunctionned // He resetd rectifiers,site on Grid","gaell=
e.njiofack@matech-cameroun.com","368","12-05-2025 20:12:18","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0005006439","Sac=
re Coeur Catholic Church","","12-05-2025 20:02:55","12-05-2025 19:57:41","1=
2-05-2025 20:01:02","Active//No power issue, site is on Grid with Ubaie 1=
=3D48.5V and Ubaie 2=3D51.4V.. The Tx FME Brice Tsague (650214096) from Hua=
wei is informed.","Mboua Thierry","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, site =
is on Grid with Ubaie 1=3D48.5V and Ubaie 2=3D51.4V.. The Tx FME Brice Tsag=
ue (650214096) from Huawei is informed.","cedric.tiani@matech-cameroun.com"=
,"315","12-05-2025 20:02:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0005006159","Elig-Edz=
oa","","12-05-2025 19:09:11","12-05-2025 19:04:43","12-05-2025 19:06:14","C=
ascaded Incident from TTO5136590","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","site went down due to PWC Overload(12Kw 250A) Bla=
ise Raoul SS IHS is iformed //Site stabilised","system","262831","12-05-202=
5 19:09:11","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0005006146","Ebe=
ba","","12-05-2025 19:06:58","12-05-2025 19:05:45","12-05-2025 20:06:30","G=
rid outage, site went down because gen start and stopped due to high temp /=
/ He added water and manually start the gen","Fanda Brice","Equipment Repai=
r","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gr=
id outage, site went down because gen start and stopped due to high temp //=
 He added water and manually start the gen","cedric.tiani@matech-cameroun.c=
om","74","12-05-2025 19:06:58","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0005006041","E=
toug ebe Meweulo","","12-05-2025 18:50:37","12-05-2025 18:48:31","12-05-202=
5 19:43:08","Site went down due to CB(125A) PWC that tripped ocm disjuncted=
 due to charge increase//He made a bridge with another CB(125A*63A)","Hyema=
fo Gildas","Equipment Repair","Passive","Rectifier","Rectifier - Circuit Br=
eaker","Site went down due to CB(125A) PWC that tripped ocm disjuncted due =
to charge increase//He made a bridge with another CB(125A*63A)","gaelle.nji=
ofack@matech-cameroun.com","127","12-05-2025 18:50:37","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0005005997","Nta=
ba","IHS_YND_133","12-05-2025 18:42:52","12-05-2025 18:39:43","12-05-2025 1=
9:06:14","site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS=
 is iformed //Site stabilised","Delor Telezing","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","site went down due to PWC Over=
load(12Kw 250A) Blaise Raoul SS IHS is iformed //Site stabilised","cedric.t=
iani@matech-cameroun.com","190","12-05-2025 18:42:52","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0005005889","C=
RF Nkoabang","","12-05-2025 18:25:27","12-05-2025 18:20:11","12-05-2025 18:=
53:14","Grid-solar site, site went down due to Grid unstable // Grid stabil=
ized","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Un=
stable Grid Supply Issue","Grid-solar site, site went down due to Grid unst=
able // Grid stabilized","gaelle.njiofack@matech-cameroun.com","317","12-05=
-2025 18:25:27","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0005005833","Mom=
","","12-05-2025 18:15:48","12-05-2025 18:13:39","12-05-2025 18:16:38","Gri=
d outage, site went down before Gen start due poor backup battery //Grid re=
turn","Fanda Brice","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Battery Low","Grid outage, site went down before Gen start due poor =
backup battery //Grid return","cedric.tiani@matech-cameroun.com","131","12-=
05-2025 18:15:48","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0005005796","Tam=
tam Weekend","","12-05-2025 18:08:30","12-05-2025 18:06:53","12-05-2025 18:=
14:17","Grid outage, site went down before Gen start due poor backup batter=
y //Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","ATS-AMF Issue","Grid outage, site went down before Gen start due poor =
backup battery //Grid return","cedric.tiani@matech-cameroun.com","98","12-0=
5-2025 18:08:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005005693","Bondjock=
","","12-05-2025 17:56:08","12-05-2025 17:37:36","12-05-2025 17:43:01","Cas=
caded Incident from TTO5135891","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid fluctuations, Site went down before=
 Gen start due to poor battery backup // Gen	automatically started","system=
","260724","12-05-2025 17:56:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005005687","Mbeng","=
","12-05-2025 17:56:07","12-05-2025 17:37:36","12-05-2025 17:43:01","Cascad=
ed Incident from TTO5135891","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuations, Site went down before Ge=
n start due to poor battery backup // Gen	automatically started","system","=
260723","12-05-2025 17:56:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005005689","Minka","=
","12-05-2025 17:56:07","12-05-2025 17:37:36","12-05-2025 17:43:01","Cascad=
ed Incident from TTO5135891","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuations, Site went down before Ge=
n start due to poor battery backup // Gen	automatically started","system","=
260725","12-05-2025 17:56:07","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0005005480","Mom=
","IHS_YND_369, IHS_YND_371, IHS_YND_554, IHS_YND_553, IHS_YND_372","12-05-=
2025 17:45:00","12-05-2025 17:37:36","12-05-2025 17:43:16","Grid fluctuatio=
ns, Site went down before Gen start due to poor battery backup // Gen	autom=
atically started","Fanda Brice","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid fluctuations, Site went down before G=
en start due to poor battery backup // Gen	automatically started","cedric.t=
iani@matech-cameroun.com","445","12-05-2025 17:45:00","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0005005446","NKO=
MKANA ELIZA HOTEL","","12-05-2025 17:35:37","12-05-2025 17:34:24","12-05-20=
25 17:51:26","Active//No power issue, Site on Grid Ubaie: 49.4V. The Tx FME=
 Brice Tsague(650214096) from Huawei is informed.","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue, Site on Grid Ubaie: 49.4V. The Tx FME Brice Tsague(650214096=
) from Huawei is informed.","cedric.tiani@matech-cameroun.com","74","12-05-=
2025 17:35:37","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005005263","S=
aa","","12-05-2025 16:58:10","12-05-2025 16:49:59","12-05-2025 16:53:12","G=
rid outage, site went down before Gen start due poor backup battery //Grid =
return","Parker Tchoup","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, site went down before Gen start due p=
oor backup battery //Grid return","gaelle.njiofack@matech-cameroun.com","49=
2","12-05-2025 16:58:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005005081","Mbeng","=
","12-05-2025 16:28:24","12-05-2025 16:19:50","12-05-2025 16:29:15","Cascad=
ed Incident from TTO5135286","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down due to Fuel sho=
rtage // Refueling done","system","265552","12-05-2025 16:28:24","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005005082","Bondjock=
","","12-05-2025 16:28:24","12-05-2025 16:19:50","12-05-2025 16:29:15","Cas=
caded Incident from TTO5135286","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Fuel =
shortage // Refueling done","system","265553","12-05-2025 16:28:24","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005005054","Emana Ly=
cee","","12-05-2025 16:25:48","12-05-2025 16:13:20","12-05-2025 16:31:21","=
Cascaded Incident from TTO5135283","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down beca=
use Gen failed to started due to poor battery backup//  Gen automatically s=
tarted","system","265757","12-05-2025 16:25:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005005000","Minka","=
","12-05-2025 16:25:32","12-05-2025 16:15:59","12-05-2025 16:30:26","Cascad=
ed Incident from TTO5135301","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down due to Fuel sho=
rtage // Refueling done","system","265785","12-05-2025 16:25:32","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0005005001","Mom","",=
"12-05-2025 16:25:32","12-05-2025 16:15:59","12-05-2025 16:30:26","Cascaded=
 Incident from TTO5135301","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Grid outage, site went down due to Fuel shortage=
 // Refueling done","system","265782","12-05-2025 16:25:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0005004999","OLAMA","=
","12-05-2025 16:25:31","12-05-2025 16:15:59","12-05-2025 16:30:26","Cascad=
ed Incident from TTO5135301","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No powwer issue on site Ubaie=3D56.4 V=
 site on Gen. site impacted by Ngoumou which is not managing by IHS","syste=
m","265787","12-05-2025 16:25:31","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0005004991","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","12-05-2025 16:24:=
34","12-05-2025 16:15:59","12-05-2025 16:30:26","Active//No powwer issue on=
 site Ubaie=3D53.7 V site on Gen. site impacted by Ngoumou which is not man=
aging by IHS","Fanda Brice","Customer Equipment Failure","Active","Active E=
quipment Failure","Affected by 3rd Party Site","Active//No powwer issue on =
site Ubaie=3D53.7 V site on Gen. site impacted by Ngoumou which is not mana=
ging by IHS","cedric.tiani@matech-cameroun.com","516","12-05-2025 16:24:34"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_201","IHS_YND_368","NOCINC0005004979","O=
tele","IHS_YND_370, IHS_YND_369, IHS_YND_371, IHS_YND_554, IHS_YND_372","12=
-05-2025 16:22:57","12-05-2025 16:19:50","12-05-2025 16:29:15","Grid outage=
, site went down due to Fuel shortage // Refueling done","Fanda Brice","Fue=
l Outage","Passive","Diesel","Diesel Outage","Grid outage, site went down d=
ue to Fuel shortage // Refueling done","gaelle.njiofack@matech-cameroun.com=
","188","12-05-2025 16:22:57","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005004976","E=
mana lycee 2","IHS_YND_274","12-05-2025 16:22:26","12-05-2025 16:13:20","12=
-05-2025 16:31:21","Grid outage , site went down because Gen failed to star=
ted due to poor battery backup//  Gen automatically started","Fabrice Pouak=
am","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery L=
ow","Grid outage , site went down because Gen failed to started due to poor=
 battery backup//  Gen automatically started","gaelle.njiofack@matech-camer=
oun.com","547","12-05-2025 16:22:26","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0005004966","OTE=
LE MTN","","12-05-2025 16:20:43","12-05-2025 16:15:59","12-05-2025 16:30:26=
","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","Active//No powwer issue on site Ubaie=3D56.4 V site on Gen. site impac=
ted by Ngoumou which is not managing by IHS","cedric.tiani@matech-cameroun.=
com","265788","12-05-2025 16:20:43","MATECH CMR"
"Closed Complete","Warning","CTR_201","IHS_YND_368","NOCINC0005004887","Ote=
le","","12-05-2025 16:09:04","","","	Grid outage, site went down due to Fue=
l shortage // Refueling done","Fanda Brice","Warning","Warning","POWER","Wa=
rning - ACDG - Fuel Leakage","Grid outage, site went down due to Fuel short=
age // Refueling done","cedric.tiani@matech-cameroun.com","2836","12-05-202=
5 16:09:04","MATECH CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0005004825","L=
eboudi","","12-05-2025 15:58:47","12-05-2025 15:52:34","12-05-2025 18:11:57=
","Active: no power issue, site is on Grid with Ubaie=3D54.33V, Mohamadou(6=
91144435) from Huawei is informed; site up without intervention.","TIENTCHE=
U NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active: no power issue, site is on Grid with =
Ubaie=3D54.33V, Mohamadou(691144435) from Huawei is informed; site up witho=
ut intervention.","gaelle.njiofack@matech-cameroun.com","374","12-05-2025 1=
5:58:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0005004640","Angongo"=
,"","12-05-2025 15:43:17","12-05-2025 15:32:58","12-05-2025 16:07:36","Casc=
aded Incident from TTO5134904","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen s=
tart and stopped due to high temp // He added water and manually start the =
gen","system","275348","12-05-2025 15:43:17","MATECH CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0005004628","Bas=
tos Amb Coree","","12-05-2025 15:41:13","12-05-2025 15:39:00","12-05-2025 1=
7:31:08","Grid outage No space to deploy a mobil Gen  // Grid restored","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage No space to deploy a mobil Gen  // Grid restored","cedric.tiani@matech=
-cameroun.com","134","12-05-2025 15:41:13","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005004610","S=
aa","","12-05-2025 15:38:26","12-05-2025 15:34:11","12-05-2025 15:41:52","	=
Grid outage, site went down before Gen start due poor backup battery // Gri=
d return	E","Parker Tchoup","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","	Grid outage, site went down before Gen start =
due poor backup battery // Grid return	E","gaelle.njiofack@matech-cameroun.=
com","256","12-05-2025 15:38:26","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0005004564","Ebe=
ba","IHS_YND_335","12-05-2025 15:29:29","12-05-2025 15:27:52","12-05-2025 1=
6:07:36","Grid outage, site went down because gen start and stopped due to =
high temp // He added water and manually start the gen","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because gen start and stopped due to h=
igh temp // He added water and manually start the gen","cedric.tiani@matech=
-cameroun.com","98","12-05-2025 15:29:29","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0005004285","Acc=
acia New","","12-05-2025 14:41:26","12-05-2025 14:37:17","12-05-2025 16:13:=
00","Site went down due to CB(63A) in PWC that tripped MTN is faulty//He re=
placed by CB(80A)","","Equipment Repair","Passive","Rectifier","Rectifier -=
 Circuit Breaker","Site went down due to CB(63A) in PWC that tripped MTN is=
 faulty//He replaced by CB(80A)","cedric.tiani@matech-cameroun.com","251","=
12-05-2025 14:41:26","MATECH CMR"
"Closed Complete","Site Down","T1113","IHS_YND_105","NOCINC0005004096","Omn=
isport 3","","12-05-2025 14:12:35","12-05-2025 14:05:29","12-05-2025 16:15:=
29","Site went down due to PWC Overloaded (12K, 250A) //site stabilised","D=
elor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Site went down due to PWC Overloaded (12K, 250A) //site stabili=
sed","cedric.tiani@matech-cameroun.com","426","12-05-2025 14:12:35","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0005004095","E=
ssomba","","12-05-2025 14:12:28","12-05-2025 14:11:16","12-05-2025 14:13:07=
","Site went down because rectifiers dysfunctionned// Site stabilised,site =
on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down because rectifiers dysfunctionned// Site stabi=
lised,site on Grid","vanel.mbiada@matech-cameroun.com","73","12-05-2025 14:=
12:28","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0005004073","MBA=
LNGONG LYCEE","","12-05-2025 14:06:34","12-05-2025 14:03:23","12-05-2025 14=
:44:16","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed//Grid return","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down becaus=
e Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informed an=
d confirmed//Grid return","cedric.tiani@matech-cameroun.com","193","12-05-2=
025 14:06:34","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0005004070","GSO=
","","12-05-2025 14:06:04","12-05-2025 13:58:52","12-05-2025 14:12:41","Gri=
d outage,site went down because Gen started and stopped with alarm *Overvol=
tage*//Grid return(investigation ongoing)","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went down =
because Gen started and stopped with alarm *Overvoltage*//Grid return(inves=
tigation ongoing)","cedric.tiani@matech-cameroun.com","433","12-05-2025 14:=
06:04","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0005004010","Eto=
ug ebe Meweulo","","12-05-2025 13:58:56","12-05-2025 13:57:48","12-05-2025 =
13:59:46","Grid fluctuation site went down because Gen started and stopped =
due to Grid bad voltage and RCP on site // Grid stabilised","Hyemafo Gildas=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation site went down because Gen started and stopped due to Gri=
d bad voltage and RCP on site // Grid stabilised","cedric.tiani@matech-came=
roun.com","69","12-05-2025 13:58:56","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0005004000","S=
aa","","12-05-2025 13:56:42","12-05-2025 13:50:33","12-05-2025 14:01:50","G=
rid outage, site went down before Gen start due poor backup battery // Grid=
 return","Parker Tchoup","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, site went down before Gen start due =
poor backup battery // Grid return","vanel.mbiada@matech-cameroun.com","370=
","12-05-2025 13:56:42","MATECH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0005003895","Lob=
o 2","","12-05-2025 13:45:10","12-05-2025 13:21:03","12-05-2025 14:48:13","=
Hybrid gen site. Site went down due to hybrid system failure//He reset it a=
nd Gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","Hybrid","Hybrid Module","Hybrid gen site. Site went down due to hybr=
id system failure//He reset it and Gen manually started","cedric.tiani@mate=
ch-cameroun.com","1448","12-05-2025 13:45:10","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0005003562","N=
koabang Ebolmedjock","","12-05-2025 12:49:15","12-05-2025 12:43:02","12-05-=
2025 19:23:39","Active//No power issue, Site on Gen. The Tx FME Brice Tsagu=
e(650214096) from Huawei is informed. Notice that it is impacted by Nkolmes=
seng-Abom Not Manager By IHS","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","Active=
//No power issue, Site on Gen. The Tx FME Brice Tsague(650214096) from Huaw=
ei is informed. Notice that it is impacted by Nkolmesseng-Abom Not Manager =
By IHS","vanel.mbiada@matech-cameroun.com","374","12-05-2025 12:49:15","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005003348","A=
WAE OCM","","12-05-2025 12:15:11","12-05-2025 12:13:22","12-05-2025 13:58:1=
9","Grid ouatge,Site went down because the PWC OF ZTE dysfonction // He res=
et the PWC and start the GEN manually","Mba Lazare Herve","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","Grid ouatge,Site wen=
t down because the PWC OF ZTE dysfonction // He reset the PWC and start the=
 GEN manually","vanel.mbiada@matech-cameroun.com","111","12-05-2025 12:15:1=
1","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0005003186","Nko=
abang2","","12-05-2025 11:45:11","12-05-2025 11:36:00","12-05-2025 12:57:10=
","SS MATECH (Siewe) was on site working(Replacement of  the Grid contactor=
)//End of work","Mba Lazare Herve","Installation Activity","Passive","Plann=
ed Activity","Installation Activity","SS MATECH (Siewe) was on site working=
(Replacement of  the Grid contactor)//End of work","cedric.tiani@matech-cam=
eroun.com","552","12-05-2025 11:45:11","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005003039","C=
rf Cornier","","12-05-2025 11:20:28","12-05-2025 11:17:16","12-05-2025 11:2=
0:34","Active, No power issue site on Grid  with U=3D50.2VTX FME Armand Nge=
stsa (691144412)From huawei is informed","MINKA NICOLAS","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
, No power issue site on Grid  with U=3D50.2VTX FME Armand Ngestsa (6911444=
12)From huawei is informed","vanel.mbiada@matech-cameroun.com","193","12-05=
-2025 11:20:28","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005002898","Mes=
sassi 2","","12-05-2025 10:58:04","12-05-2025 10:48:59","12-05-2025 11:04:0=
1"," Site went down due to 02/06 rectifiers malfunctioning // He reset it a=
nd site on grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier"=
,"Rectifier Distribution"," Site went down due to 02/06 rectifiers malfunct=
ioning // He reset it and site on grid","cedric.tiani@matech-cameroun.com",=
"546","12-05-2025 10:58:04","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0005002774","C=
-Supreme","","12-05-2025 10:38:45","12-05-2025 10:33:31","12-05-2025 11:59:=
30","Active: No power issue, site on Grid with Ubaie=3D50.2V, Brice Tsague =
(650 21 40 96) from Huawei is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power iss=
ue, site on Grid with Ubaie=3D50.2V, Brice Tsague (650 21 40 96) from Huawe=
i is informed","vanel.mbiada@matech-cameroun.com","315","12-05-2025 10:38:4=
5","MATECH CMR"
"Closed Complete","Site Down","T0292","IHS_YND_231","NOCINC0005002602","Nko=
lso","","12-05-2025 10:07:49","12-05-2025 10:05:27","12-05-2025 10:10:55","=
Grid fluctuation,site went down because Gen started and stopped due to Grid=
 bad voltage//Grid return","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,site =
went down because Gen started and stopped due to Grid bad voltage//Grid ret=
urn","cedric.tiani@matech-cameroun.com","143","12-05-2025 10:07:49","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005002576","Emana Ly=
cee","","12-05-2025 10:00:11","12-05-2025 09:55:00","12-05-2025 10:12:47","=
Cascaded Incident from TTO5132571","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage , site went down befo=
re Gen started due to poor battery backup//Gen automatically started,  Site=
 on Gen","system","1216281","12-05-2025 10:00:11","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005002572","E=
mana lycee 2","IHS_YND_274","12-05-2025 09:59:28","12-05-2025 09:55:00","12=
-05-2025 10:12:47","Grid outage , site went down before Gen started due to =
poor battery backup//Gen automatically started,  Site on Gen","Fabrice Poua=
kam","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Grid outage , site went down before Gen started due to poor battery b=
ackup//Gen automatically started,  Site on Gen","vanel.mbiada@matech-camero=
un.com","269","12-05-2025 09:59:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0005002195","Minka","=
","12-05-2025 08:59:16","12-05-2025 08:54:26","12-05-2025 09:39:11","Cascad=
ed Incident from TTO5132154","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage,site went down because Gen fail=
ed to start(investigation ongoing)//Grid return","system","277873","12-05-2=
025 08:59:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0005002196","Bondjock=
","","12-05-2025 08:59:16","12-05-2025 08:54:26","12-05-2025 09:39:11","Cas=
caded Incident from TTO5132154","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage,site went down because Gen f=
ailed to start(investigation ongoing)//Grid return","system","277873","12-0=
5-2025 08:59:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0005002194","Mbeng","=
","12-05-2025 08:59:15","12-05-2025 08:54:26","12-05-2025 09:39:11","Cascad=
ed Incident from TTO5132154","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage,site went down because Gen fail=
ed to start(investigation ongoing)//Grid return","system","277872","12-05-2=
025 08:59:15","MATECH CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0005002188","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_372","12-05-2025 08:57:37","12-05-20=
25 08:54:26","12-05-2025 09:39:49","Grid outage,site went down because Gen =
failed to start(investigation ongoing)//Grid return","Fanda Brice","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site we=
nt down because Gen failed to start(investigation ongoing)//Grid return","v=
anel.mbiada@matech-cameroun.com","193","12-05-2025 08:57:37","MATECH CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0005001705","Ese=
ka MTN","IHS_YND_378","12-05-2025 07:06:49","12-05-2025 07:03:39","12-05-20=
25 07:22:16","Grid fluctuation,Site went down because Gen started and stopp=
ed due to grid bad voltage//He bypassed the Grid and site on Gen","Kemeni F=
ranklin","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation,Site went down because Gen started and stopped due=
 to grid bad voltage//He bypassed the Grid and site on Gen","cedric.tiani@m=
atech-cameroun.com","191","12-05-2025 07:06:49","MATECH CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0005001685","NKO=
LMEKONG YDE","","12-05-2025 07:02:39","12-05-2025 06:53:59","12-05-2025 08:=
00:36","Grid outage,site went down because GEN failed to start due to charg=
ing alternator fuse cut causing battery discharge//He replaced the it and m=
aually started the Gen","Fabrice Pouakam","Equipment Repair","Passive","ACD=
G Gen","ACDG - Charging Alternator","Grid outage,site went down because GEN=
 failed to start due to charging alternator fuse cut causing battery discha=
rge//He replaced the it and maually started the Gen","cedric.tiani@matech-c=
ameroun.com","521","12-05-2025 07:02:39","MATECH CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0005001674","E=
kie sud","","12-05-2025 07:00:42","12-05-2025 06:59:30","12-05-2025 07:50:2=
8","Grid bad voltage, Site went down Because gen fails to start due to lack=
 of 01 phase on site // He bypassed Grid and started Gen manually","Albran =
Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid bad voltage, Site went down Because gen fails to start due to l=
ack of 01 phase on site // He bypassed Grid and started Gen manually","chri=
stelle.ngonga@matech-cameroun.com","73","12-05-2025 07:00:42","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005001659","O=
LAMA","","12-05-2025 06:57:20","12-05-2025 06:54:10","12-05-2025 07:58:30",=
"No power issue on site Ubaie =3D54.9V site on GEN. The TX FME Henri (69994=
9693) from Huawei is informed","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.9V site on GEN. The TX FME Henri (699949693) from Huawei i=
s informed","christelle.ngonga@matech-cameroun.com","191","12-05-2025 06:57=
:20","MATECH CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0005001655","Ese=
ka Town","","12-05-2025 06:56:55","12-05-2025 07:03:39","12-05-2025 07:22:1=
6","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid fluctuation,Site went down because Gen started and stoppe=
d due to grid bad voltage//He byapassed the Grid and site on Gen","franck.n=
komot@matech-cameroun.com","262761","12-05-2025 06:56:55","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0005001642","O=
mnisport 3","","12-05-2025 06:52:55","12-05-2025 06:51:36","12-05-2025 07:0=
9:19","Site went down due to PWC Overloaded (12K, 250A) //site stabilised",=
"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","Site went down due to PWC Overloaded (12K, 250A) //site stabi=
lised","christelle.ngonga@matech-cameroun.com","80","12-05-2025 06:52:55","=
MATECH CMR"
"Closed Complete","Site Down","T1746","IHS_YND_178","NOCINC0005001639","Emo=
mbo","","12-05-2025 06:51:56","12-05-2025 06:47:48","12-05-2025 07:11:37","=
Site went down because gen start and stopped due to alarm*high temp*//he ad=
ded water and started the gen","Mba Lazare Herve","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Site went d=
own because gen start and stopped due to alarm*high temp*//he added water a=
nd started the gen","franck.nkomot@matech-cameroun.com","429","12-05-2025 0=
6:51:56","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0005001555","Mim=
boman","","12-05-2025 06:29:34","12-05-2025 06:00:20","12-05-2025 07:28:00"=
,"Site went down because gen start and stopped due to alarm*low oil pressur=
e*//he added oil and started the gen","Mba Lazare Herve","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down because gen=
 start and stopped due to alarm*low oil pressure*//he added oil and started=
 the gen","franck.nkomot@matech-cameroun.com","1754","12-05-2025 06:29:34",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0005001149","E=
kie sud","","12-05-2025 04:31:06","12-05-2025 04:29:41","12-05-2025 05:13:0=
0","Grid bad voltage, Site went down Because gen fails to start due to lack=
 of 01 phase on site // He bypassed Grid and started Gen manually","Albran =
Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid bad voltage, Site went down Because gen fails to start due to l=
ack of 01 phase on site // He bypassed Grid and started Gen manualy","chris=
telle.ngonga@matech-cameroun.com","86","12-05-2025 04:31:06","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0005000929","A=
WAE OCM","","12-05-2025 03:09:42","12-05-2025 03:08:36","12-05-2025 06:19:3=
6","Grid outage, site went down because gen failed to start due to PWC ZTE =
malfunction // He reset controller and gen manually started. (Notice that F=
ME was on site waiting for the concierge.)","Mba Lazare Herve","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, si=
te went down because gen failed to start due to PWC ZTE malfunction // He r=
eset controller and gen manually started. (Notice that FME was on site wait=
ing for the concierge.)","christelle.ngonga@matech-cameroun.com","68","12-0=
5-2025 03:09:42","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0005000871","C=
RF Nkoabang","","12-05-2025 02:26:35","12-05-2025 02:25:28","12-05-2025 09:=
30:47","Grid-solar site, Grid outage, site down due to sunset,// Sun shine =
return ","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid -=
 Grid Outage Issue","Grid-solar site, Grid outage, site down due to sunset,=
// Sun shine return ","christelle.ngonga@matech-cameroun.com","68","12-05-2=
025 02:26:35","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0005000847","S=
atcom","","12-05-2025 02:17:40","12-05-2025 02:08:27","12-05-2025 03:55:19"=
,"No power issue site on Grid with Ubay:31.9V Tx Fme Armand Ngestsa (691144=
412) of huawei is informed","Delor Telezing","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on Grid with Ubay:31.9V Tx Fme Armand Ngestsa (691144412) of huawei is in=
formed","christelle.ngonga@matech-cameroun.com","554","12-05-2025 02:17:40"=
,"MATECH CMR"
"Closed Complete","Site Down","T1113","IHS_YND_105","NOCINC0005000733","Omn=
isport 3","","12-05-2025 00:59:55","12-05-2025 00:54:58","12-05-2025 01:50:=
27","Site went down due to PWC Overloaded (12K, 250A) // site stabilized SS=
 IHS Alphonse confirmed","Delor Telezing","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Site went down due to PWC Overlo=
aded (12K, 250A) // site stabilized SS IHS Alphonse confirmed","franck.nkom=
ot@matech-cameroun.com","297","12-05-2025 00:59:55","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0005000728","O=
LAMA","","12-05-2025 00:51:36","12-05-2025 00:50:27","12-05-2025 00:52:38",=
"No power issue on site Ubaie =3D54.9V site on GEN. The TX FME Henri (69994=
9693) from Huawei is informed","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie =3D54.9V site on GEN. The TX FME Henri (699949693) from Huawei i=
s informed","christelle.ngonga@matech-cameroun.com","70","12-05-2025 00:51:=
36","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0005000680","N=
gouetou","","12-05-2025 00:32:24","12-05-2025 00:30:51","12-05-2025 00:40:5=
8","Active // No power issue site on Gen, with Ubay=3D53.1 V. The Tx Fme Gr=
egoire (654547479) from Huawei is informed","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive // No power issue site on Gen, with Ubay=3D53.1 V. The Tx Fme Gregoire =
(654547479) from Huawei is informed","christelle.ngonga@matech-cameroun.com=
","95","12-05-2025 00:32:24","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0005000621","C=
rf Cornier","","12-05-2025 00:13:35","12-05-2025 00:13:00","12-05-2025 00:2=
0:00","Active, No power issue site on battery with U=3D51.6VTX FME Armand N=
gestsa (691144412) From huawei is informed","MINKA NICOLAS","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive, No power issue site on battery with U=3D51.6VTX FME Armand Ngestsa (69=
1144412) From huawei is informed","christelle.ngonga@matech-cameroun.com","=
36","12-05-2025 00:13:35","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0005000533","Elo=
umdem stade","","11-05-2025 23:35:05","11-05-2025 23:28:53","11-05-2025 23:=
46:53","Site went down due to Grid bad voltage,and gen failed to start,no r=
cp // bypassed grid and started the gen","Fanda Brice","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Site went down due to=
 Grid bad voltage,and gen failed to start,no rcp // bypassed grid and start=
ed the gen","franck.nkomot@matech-cameroun.com","374","11-05-2025 23:35:05"=
,"MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0005000339","Nko=
abang MTN","","11-05-2025 22:46:27","11-05-2025 22:38:15","12-05-2025 00:08=
:15","Grid outage, site went down because gen start and stopped with over c=
urrent alarm(Unprouven alarm) // Reset of gen card done and gen started","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, site went down because gen start and stopped with over c=
urrent alarm(Unprouven alarm) // Reset of gen card done and gen started","l=
oic.noumsi@matech-cameroun.com","493","11-05-2025 22:46:27","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0005000208","E=
mana lycee 2","","11-05-2025 22:17:05","11-05-2025 22:11:57","11-05-2025 22=
:27:57","Grid outage,site went down before Gen started due to poor Battery =
Backup // Gen automatically started","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,site we=
nt down before Gen started due to poor Battery Backup // Gen automatically =
started","gaelle.njiofack@matech-cameroun.com","309","11-05-2025 22:17:05",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0005000183","T=
amtam Weekend","IHS_YND_562, IHS_YND_518","11-05-2025 22:11:31","11-05-2025=
 22:06:01","12-05-2025 00:08:15","site went down due to Grid outage and gen=
 failed to start due to ATS malfunctioning  //  he bypassed and put site on=
 Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Panel"=
,"ATS Timer Faulty","site went down due to Grid outage and gen failed to st=
art due to ATS malfunctioning  //  he bypassed and put site on Grid return"=
,"gaelle.njiofack@matech-cameroun.com","331","11-05-2025 22:11:31","MATECH =
CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0005000168","M=
ontee-Jouvence-II","","11-05-2025 22:09:55","11-05-2025 22:06:01","12-05-20=
25 00:06:01","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","site went down due to Grid outage and gen failed to s=
tart due to ATS dysfonctionning  //  he bypass and put site on Grid return"=
,"gaelle.njiofack@matech-cameroun.com","302134","11-05-2025 22:09:55","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0005000160","A=
ccacia New","","11-05-2025 22:08:40","11-05-2025 22:06:01","12-05-2025 00:0=
6:01","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"site went down due to Grid outage and gen failed to start due to ATS dysfo=
nctionning  //  he bypass and put site on Grid return","gaelle.njiofack@mat=
ech-cameroun.com","302134","11-05-2025 22:08:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0005000143","Messassi=
 okolo","","11-05-2025 22:07:22","11-05-2025 22:02:34","11-05-2025 22:19:46=
","Cascaded Incident from TTO5129828","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down because=
 site behaves as Grid only site (no Gen) //Grid return","system","273470","=
11-05-2025 22:07:22","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0005000134","E=
MANA BILICK CITY","IHS_YND_279","11-05-2025 22:05:42","11-05-2025 22:02:34"=
,"11-05-2025 22:24:43","Grid outage, site down because site behaves as Grid=
 only site (no Gen) //Grid return","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage, site down becaus=
e site behaves as Grid only site (no Gen) //Grid return","gaelle.njiofack@m=
atech-cameroun.com","189","11-05-2025 22:05:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0005000045","Emana Ly=
cee","","11-05-2025 21:58:16","11-05-2025 21:47:02","11-05-2025 22:04:46","=
Cascaded Incident from TTO5129717","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down before=
 Gen started due to poor Battery Backup // Gen automatically started","syst=
em","267342","11-05-2025 21:58:16","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0005000025","Ema=
na lycee 2","IHS_YND_274","11-05-2025 21:55:17","11-05-2025 21:47:02","11-0=
5-2025 22:04:46","Grid outage,site went down before Gen started due to poor=
 Battery Backup // Gen automatically started","Fabrice Pouakam","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outag=
e,site went down before Gen started due to poor Battery Backup // Gen autom=
atically started","gaelle.njiofack@matech-cameroun.com","566","11-05-2025 2=
1:55:17","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0005000003","Mes=
sassi 2","","11-05-2025 21:53:22","11-05-2025 21:47:02","11-05-2025 22:21:3=
3","Site went down because 04/06 rectifiers dysfuncionned// He reset rectif=
iers, site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down because 04/06 rectifiers dysfuncionne=
d// He reset rectifiers, site on Gen","loic.noumsi@matech-cameroun.com","38=
2","11-05-2025 21:53:22","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004999663","O=
LAMA","","11-05-2025 20:54:57","11-05-2025 20:47:51","11-05-2025 21:06:40",=
"Active//No power issue on site Ubaie =3D54.9V site on GEN. The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.9V site on GEN. The TX FME Henri (69994969=
3) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","427","11=
-05-2025 20:54:57","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004999659","N=
gouetou","","11-05-2025 20:54:15","11-05-2025 20:49:04","11-05-2025 20:58:5=
8","Active // No power issue site on Gen, with Ubay=3D54.4V. site up withou=
t intervention.","Parker Tchoup","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active // No power issue site =
on Gen, with Ubay=3D54.4V. site up without intervention.","gaelle.njiofack@=
matech-cameroun.com","312","11-05-2025 20:54:15","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004999602","D=
amas","","11-05-2025 20:42:04","11-05-2025 20:37:56","12-05-2025 07:24:11",=
" Acces issue due to landloard,Site went down due to CB(125A) in PWC that t=
ripped ocm//He rearmed it ","MINKA NICOLAS","Access Denial","Lease Or Legal=
","Landlord Related Issues","Access Issue - Land Lord","Site went down due =
to CB(125A) in PWC that tripped ocm//He rearmed it ","gaelle.njiofack@matec=
h-cameroun.com","249","11-05-2025 20:42:04","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004999585","MEH=
ANDAN","","11-05-2025 20:38:45","11-05-2025 20:33:16","11-05-2025 21:04:31"=
,"Grid fluctuation,Site went down because GEN failed to start due to grid b=
ad voltage(lack of 01 phase)// He did a bridge on the good phase, site on G=
rid ","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid fluctuation,Site went down because GEN failed to =
start due to grid bad voltage(lack of 01 phase)// He did a bridge on the go=
od phase, site on Grid ","loic.noumsi@matech-cameroun.com","465","11-05-202=
5 20:38:45","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004999548","Nta=
ba","","11-05-2025 20:28:26","11-05-2025 20:25:19","11-05-2025 21:16:13","G=
rid outage, site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS I=
HS is informed // Grid restored","Delor Telezing","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is informed // Grid =
restored","gaelle.njiofack@matech-cameroun.com","188","11-05-2025 20:28:26"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004999526","S=
aa","","11-05-2025 20:23:01","11-05-2025 20:18:51","11-05-2025 20:24:26","	=
Grid outage, site went down before Gen start due poor backup battery // Gri=
d return","Parker Tchoup","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","	Grid outage, site went down before Gen start du=
e poor backup battery // Grid return","gaelle.njiofack@matech-cameroun.com"=
,"251","11-05-2025 20:23:01","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004999483","SAA=
 Entrance","","11-05-2025 20:13:41","11-05-2025 20:06:34","11-05-2025 20:41=
:20","Grid fluctuations, Site went down due to grid bad voltage on site // =
He bypassed Grid and put site on Gen","Parker Tchoup","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid fluctuations, Sit=
e went down due to grid bad voltage on site // He bypassed Grid and put sit=
e on Gen","gaelle.njiofack@matech-cameroun.com","428","11-05-2025 20:13:41"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004999045","O=
mnisport 3","","11-05-2025 18:52:37","11-05-2025 18:47:27","11-05-2025 23:4=
4:36"," Site went down due to PWC Overloaded (12K, 250A) // site stabilized=
 SS IHS Alphonse confirmed","Delor Telezing","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low"," Site went down due to PWC Ov=
erloaded (12K, 250A) // site stabilized SS IHS Alphonse confirmed","vanel.m=
biada@matech-cameroun.com","311","11-05-2025 18:52:37","MATECH CMR"
"Closed Complete","Site Down","T1113","IHS_YND_105","NOCINC0004998987","Omn=
isport 3","","11-05-2025 18:39:59","11-05-2025 18:33:50","11-05-2025 18:39:=
16","Site went down due to PWC Overloaded (12K, 250A) // site stabilized SS=
 IHS Alphonse confirmed","Delor Telezing","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re Gen started due to poor backup battery // Grid returned","loic.noumsi@ma=
tech-cameroun.com","370","11-05-2025 18:39:59","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004998821","Nom=
ayos montee Meche","","11-05-2025 18:19:35","11-05-2025 18:12:28","11-05-20=
25 18:22:16","Grid outage, site went down before Gen started due to poor ba=
ckup battery // Grid returned","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen started due to poor backup battery // Grid returned","loic.noumsi=
@matech-cameroun.com","428","11-05-2025 18:19:35","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004998791","S=
aa","","11-05-2025 18:13:24","11-05-2025 18:09:08","11-05-2025 18:11:58","G=
rid outage, site went down before Gen start due poor backup battery // Grid=
 returned","Parker Tchoup","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, site went down before Gen start du=
e poor backup battery // Grid returned","gaelle.njiofack@matech-cameroun.co=
m","257","11-05-2025 18:13:24","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004998624","S=
OA TOWN","","11-05-2025 17:38:56","11-05-2025 17:36:48","11-05-2025 17:39:1=
8","site went down due to rectifier issue // 01 rectifier add and site on G=
en.","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down due to rectifier issue // 01 rectifier add and site o=
n Gen.","gaelle.njiofack@matech-cameroun.com","271","11-05-2025 17:38:56","=
MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004998619","Eke=
kam","","11-05-2025 17:38:09","11-05-2025 17:35:55","11-05-2025 18:25:19","=
Hybrid Gen, site went down because Gen failed to start due to automation ma=
lfunctioning // He started Gen manually","TIENTCHEU NZETCHIEU GAEL","Equipm=
ent Repair","Passive","Control Panel","ATS-AMF Issue","Hybrid Gen, site wen=
t down because Gen failed to start due to automation malfunctioning // He s=
tarted Gen manually","gaelle.njiofack@matech-cameroun.com","135","11-05-202=
5 17:38:09","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004998536","Nta=
ba","","11-05-2025 17:21:13","11-05-2025 17:16:46","11-05-2025 17:34:45","s=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is informe=
d //Site stabilised","Delor Telezing","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","site went down due to PWC Overload(12Kw =
250A) Blaise Raoul SS IHS is informed //Site stabilised","loic.noumsi@matec=
h-cameroun.com","268","11-05-2025 17:21:13","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004998188","Oko=
lo Kilombo","","11-05-2025 16:54:30","11-05-2025 16:38:23","11-05-2025 18:0=
0:58","Active //no power issue Ubaie:54.8V site on Grid The TX FME Symphori=
en (675295205) from Huawei is informed.","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve //no power issue Ubaie:54.8V site on Grid The TX FME Symphorien (6752952=
05) from Huawei is informed.","landry.etame@ihstowers.com","968","11-05-202=
5 16:54:30","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004998030","Oko=
lo Kilombo","","11-05-2025 16:21:28","11-05-2025 16:14:17","11-05-2025 16:2=
9:24","Grid outage, site went down due to insufficiency of rectifiers // Gr=
id returned","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Grid outage, site went down due to insufficiency of rectif=
iers // Grid returned","loic.noumsi@matech-cameroun.com","431","11-05-2025 =
16:21:28","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0004998016","ODZ=
A BORNE 10","","11-05-2025 16:19:04","11-05-2025 16:11:14","11-05-2025 17:2=
9:00","Site went down due to 2/3 rectifiers faulty on site // He reseted th=
ese rectifiers","Albran Byorel","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to 2/3 rectifiers faulty on site // He=
 reseted these rectifiers","loic.noumsi@matech-cameroun.com","471","11-05-2=
025 16:19:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004997824","MEHANDAN=
","","11-05-2025 15:53:33","11-05-2025 15:44:09","11-05-2025 15:51:47","Cas=
caded Incident from TTO5127117","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid outage, site went down because g=
en failed to start due to PWC ZTE malfunction // Grid return","system","260=
547","11-05-2025 15:53:33","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004997798","O=
dza II OCM","IHS_YND_528","11-05-2025 15:51:19","11-05-2025 15:44:09","11-0=
5-2025 15:51:47","	Grid outage, site went down because gen failed to start =
due to PWC ZTE malfunction // Grid return","Albran Byorel","Equipment Repai=
r","Passive","Rectifier","Rectifier Cabinet","	Grid outage, site went down =
because gen failed to start due to PWC ZTE malfunction // Grid return","gae=
lle.njiofack@matech-cameroun.com","432","11-05-2025 15:51:19","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004997742","S=
aa","","11-05-2025 15:45:30","11-05-2025 15:37:19","11-05-2025 15:46:22","G=
rid outage, site went down due poor backup battery // Grid returned","Parke=
r Tchoup","Equipment Repair","Passive","Control Panel","Power Cabinet - Bat=
tery Low","Grid outage, site went down due poor backup battery // Grid retu=
rned","loic.noumsi@matech-cameroun.com","492","11-05-2025 15:45:30","MATECH=
 CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0004997363","Men=
dong Maeture","","11-05-2025 14:47:39","11-05-2025 14:23:33","11-05-2025 15=
:06:00","Active//No power issue, site is on grid with Ubaie=3D53V, TX FME M=
bah hosiah(699699694) from Huawei is informed.","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue, site is on grid with Ubaie=3D53V, TX FME Mbah hos=
iah(699699694) from Huawei is informed.","loic.noumsi@matech-cameroun.com",=
"1447","11-05-2025 14:47:39","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004996983","UPA=
C LP","","11-05-2025 14:11:51","11-05-2025 14:09:26","11-05-2025 14:45:06",=
"Grid outage,no space to deploy a mobil Gen // Grid returned","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no sp=
ace to deploy a mobil Gen // Grid returned","vanel.mbiada@matech-cameroun.c=
om","146","11-05-2025 14:11:51","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004996954","MBA=
LNGONG LYCEE","","11-05-2025 14:05:31","11-05-2025 13:57:02","12-05-2025 01=
:24:08","Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed //Grid return","Fanda Brice","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down becau=
se Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informed a=
nd confirmed //Grid return","vanel.mbiada@matech-cameroun.com","510","11-05=
-2025 14:05:31","MATECH CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0004996837","Ako=
no","","11-05-2025 13:45:34","","","Grid fluctuation,site alarming because =
Gen failed to start due to Grid bad voltage//site on Gen ","Fanda Brice","W=
arning","Warning","POWER","Warning - National Grid - Grid Incomplete Phase"=
,"Grid fluctuation,site alarming because Gen failed to start due to Grid ba=
d voltage//site on Gen ","cedric.tiani@matech-cameroun.com","9734","11-05-2=
025 13:45:34","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004996675","B=
arriere","","11-05-2025 13:20:27","09-05-2025 23:18:29","13-05-2025 16:29:2=
7","backtracking Eneo meter burnt , Site went down because Gen overload(20k=
va,400 A) IHS SS Felix Zambe is informed and confirmed","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","backtracking Eneo =
meter burnt , Site went down because Gen overload(20kva,400 A) IHS SS Felix=
 Zambe is informed and confirmed","cedric.tiani@matech-cameroun.com","13691=
9","11-05-2025 13:20:27","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004996361","M=
bankomo IHS","","11-05-2025 12:16:42","11-05-2025 11:57:59","11-05-2025 12:=
20:52","Grid outage, Site went down before Gen start due to poor backup // =
Gen started Manually","Fanda Brice","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen started Manually","vanel.mbiada@matech-cam=
eroun.com","3630","11-05-2025 12:16:42","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004996146","Mfo=
u EPC","","11-05-2025 11:18:41","11-05-2025 11:14:58","11-05-2025 11:45:13"=
,"Gri fluctuation, site went down because gen start and stopped due to grid=
 bad voltage // He bypass grid and manually start the gen","Mba Lazare Herv=
e","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Gri fluctuation, site went down because gen start and stopped due to grid=
 bad voltage // He bypass grid and manually start the gen","vanel.mbiada@ma=
tech-cameroun.com","224","11-05-2025 11:18:41","MATECH CMR"
"Closed Complete","Warning","T0462","IHS_YND_123","NOCINC0004995611","Nkomo=
 II","","11-05-2025 09:46:02","","","	Grid fluctuation, site went down beca=
use gen start and stopped due to grid bad voltage // He bypass grid and man=
ually start the gen	","Albran Byorel","Warning","Warning","POWER","Warning =
- National Grid - Grid Incomplete Phase","	Grid fluctuation, site went down=
 because gen start and stopped due to grid bad voltage // He bypass grid an=
d manually start the gen	","vanel.mbiada@matech-cameroun.com","388","11-05-=
2025 09:46:02","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004994958","A=
WAE OCM","","11-05-2025 07:31:35","11-05-2025 07:29:02","11-05-2025 09:39:1=
8","site went down due to PWC disfonction ,Gen manuel started","Mba Lazare =
Herve","Equipment Repair","Passive","Rectifier","Rectifier Module","site we=
nt down due to PWC disfonction ,Gen manuel started","vanel.mbiada@matech-ca=
meroun.com","155","11-05-2025 07:31:35","MATECH CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004994182","SOA=
 VILLAGE","","11-05-2025 02:53:26","09-05-2025 21:06:00","09-05-2025 21:40:=
00","Backtracking, Active //No power issue on site ,site on Grid with Ubaie=
=3D54.6 V The Tx FME Synphorien//691316854 from Huawei is informed","Siliga=
p Boris","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Backtracking, Active //No power issue on site ,site on=
 Grid with Ubaie=3D54.6 V The Tx FME Synphorien//691316854 from Huawei is i=
nformed","loic.noumsi@matech-cameroun.com","107247","11-05-2025 02:53:26","=
MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004994177","Tam=
tam Weekend","","11-05-2025 02:51:47","09-05-2025 16:12:22","09-05-2025 16:=
43:22","Backtracking, NO power issue on site ,mba hosiah was on site workin=
g","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","NO power issue on site ,mba hosiah was on s=
ite working","loic.noumsi@matech-cameroun.com","124766","11-05-2025 02:51:4=
7","MATECH CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0004994174","Cam=
p-Sonel","","11-05-2025 02:50:18","09-05-2025 14:31:48","09-05-2025 15:04:4=
8","Backtracking,Grid outage, site went down because gen start and stopped =
with high temp alarm (unproved) // He reset it and manually start the gen	"=
,"Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, site went down because gen start and stopped with high t=
emp alarm (unproved) // He reset it and manually start the gen	","loic.noum=
si@matech-cameroun.com","130711","11-05-2025 02:50:18","MATECH CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0004994170","Yok=
o MTN","","11-05-2025 02:49:32","09-05-2025 19:41:07","09-05-2025 20:10:59"=
,"Backtracking .  No power issue, Site on grid Ubaie: 54.8V , Site impacted=
 by Ntui camtel","Parker Tchoup","Customer Equipment Failure","Active","Act=
ive Equipment Failure","Affected by 3rd Party Site","Backtracking .  No pow=
er issue, Site on grid Ubaie: 54.8V , Site impacted by Ntui camtel","edwige=
.kapawo@matech-cameroun.com","112106","11-05-2025 02:49:32","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0004994165","ODZ=
A BORNE 10","","11-05-2025 02:46:58","09-05-2025 17:07:01","09-05-2025 18:4=
9:54","backtraking ,Site went down due to PWC dysfunction //He reset it and=
 site on Gen","Albran Byorel","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Site went down due to PWC dysfunction //He reset=
 it and site on Gen","edwige.kapawo@matech-cameroun.com","121198","11-05-20=
25 02:46:58","MATECH CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0004994076","N=
KONGKARAK","","11-05-2025 01:57:25","09-05-2025 14:11:05","09-05-2025 15:31=
:12","Backtracking,Site went down because Gen started and stopped due to wo=
rk of Daniel fomekong on site ( pierced pelletZ) // End of work","TIENTCHEU=
 NZETCHIEU GAEL","Installation Activity","Passive","Planned Activity","Inst=
allation Activity","Site went down because Gen started and stopped due to w=
ork of Daniel fomekong on site ( pierced pelletZ) // End of work","edwige.k=
apawo@matech-cameroun.com","129140","11-05-2025 01:57:25","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004993564","O=
LAMA","","10-05-2025 22:57:44","10-05-2025 22:56:59","11-05-2025 00:59:50",=
"Active//No power issue on site Ubaie =3D54.9V site on GEN. The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.9V site on GEN. The TX FME Henri (69994969=
3) from Huawei is informed","edwige.kapawo@matech-cameroun.com","46","10-05=
-2025 22:57:44","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004992978","AWA=
E OCM","","10-05-2025 21:20:47","10-05-2025 21:15:27","11-05-2025 02:09:44"=
,"Grid outage, site went down because gen failed to start due to PWC ZTE ma=
lfunction // He reset controller and gen manually started. (Notice that  FM=
E was on site waiting for the concierge.)","Mba Lazare Herve","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down because gen failed to start due to PWC ZTE malfunction // He re=
set controller and gen manually started. (Notice that  FME was on site wait=
ing for the concierge.","franck.nkomot@matech-cameroun.com","368","10-05-20=
25 21:20:47","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004992949","N=
YOM 2 IHS","","10-05-2025 21:14:17","10-05-2025 21:12:04","10-05-2025 21:13=
:46","Wrongly logged ticket","Fabrice Pouakam","Incorrectly Logged Tickets"=
,"Error","Error","Error","Wrongly logged ticket","christelle.ngonga@matech-=
cameroun.com","49795","10-05-2025 21:14:17","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004992768","Eto=
ug ebe biscuiterie","","10-05-2025 20:50:21","10-05-2025 20:31:06","10-05-2=
025 21:38:25","Site down due to Grid fluctuation,  Gen did not  start  // G=
en manually  started","Hyemafo Gildas","Grid Supply","Passive","Grid","Nati=
onal Grid - Unstable Grid Supply Issue","Site down due to Grid fluctuation,=
  Gen did not  start  // Gen manually  started","christelle.ngonga@matech-c=
ameroun.com","1156","10-05-2025 20:50:21","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004992611","E=
ssomba","","10-05-2025 20:19:04","10-05-2025 20:15:57","10-05-2025 20:48:11=
","Site went down due to 04/05 rectifiers alarming//He reset it and site on=
 Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Distribution","Site went down due to 04/05 rectifiers alarming//He reset=
 it and site on Grid","christelle.ngonga@matech-cameroun.com","189","10-05-=
2025 20:19:04","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004992563","Men=
dong NB","","10-05-2025 20:09:43","10-05-2025 19:58:22","10-05-2025 21:24:5=
9","Grid outage no space to deploy a mobile Gen,// Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no =
space to deploy a mobile Gen,// Grid return","franck.nkomot@matech-cameroun=
.com","682","10-05-2025 20:09:43","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004992225","Nta=
ba","","10-05-2025 19:06:08","10-05-2025 19:00:58","10-05-2025 19:18:58","s=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","site went down due to PWC Overload(12Kw 250A) Blaise R=
aoul SS IHS is iformed //Site stabilised","franck.nkomot@matech-cameroun.co=
m","311","10-05-2025 19:06:08","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004992169","N=
gouetou","","10-05-2025 18:57:12","10-05-2025 18:47:35","10-05-2025 19:22:2=
9","Wrongly logged ticket","Parker Tchoup","Incorrectly Logged Tickets","Er=
ror","Error","Error","Wrongly logged ticket","christelle.ngonga@matech-came=
roun.com","579","10-05-2025 18:57:12","MATECH CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0004992065","B=
ISCUITERIE","","10-05-2025 18:27:22","10-05-2025 18:24:23","10-05-2025 23:2=
3:32","Site Went down due to Gen over load ( Gen can not  longer handle the=
 load (320A) even after reducing 4/6 batteries) // He reduced load","Paul B=
IBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site Went=
 down due to Gen over load ( Gen can not  longer handle the load (320A) eve=
n after reducing 4/6 batteries) // He reduced load","christelle.ngonga@mate=
ch-cameroun.com","180","10-05-2025 18:27:22","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004991986","Men=
dong NB","","10-05-2025 18:11:06","10-05-2025 18:08:50","10-05-2025 19:46:5=
0","Grid outage no space to deploy a mobile Gen awaiting // Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage no space to deploy a mobile Gen awaiting // Grid return","christelle.=
ngonga@matech-cameroun.com","137","10-05-2025 18:11:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004991967","Scalom-I=
HS","","10-05-2025 18:06:03","10-05-2025 18:04:21","10-05-2025 18:12:21","C=
ascaded Incident from TTO5120354","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because Gen failed to=
 start due to PWC ZTE malfunction // Gen manually started","system","266417=
","10-05-2025 18:06:03","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004991963","S=
calom","IHS_YND_505","10-05-2025 18:05:27","10-05-2025 18:04:21","10-05-202=
5 18:14:21","Grid outage, site went down because Gen failed to start due to=
 PWC ZTE malfunction // Gen manually started","Paul BIBOUM","Equipment Repa=
ir","Passive","Control Panel","Panel Distribution Board","Grid outage, site=
 went down because Gen failed to start due to PWC ZTE malfunction // Gen ma=
nually started","christelle.ngonga@matech-cameroun.com","67","10-05-2025 18=
:05:27","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004991895","B=
itoto","","10-05-2025 17:48:41","10-05-2025 17:46:32","10-05-2025 18:03:32"=
,"Grid outage, site went down because Gen failed to start due to PWC ZTE ma=
lfunction // Gen manually started","Mba Lazare Herve","Equipment Repair","P=
assive","Control Panel","Panel Distribution Board","Grid outage, site went =
down because Gen failed to start due to PWC ZTE malfunction // Gen manually=
 started","christelle.ngonga@matech-cameroun.com","130","10-05-2025 17:48:4=
1","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004991855","Sca=
lom","","10-05-2025 17:42:02","10-05-2025 17:38:53","10-05-2025 17:42:53","=
Grid outage, site went down because Gen failed to start due to PWC ZTE malf=
unction // Gen manually started","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Panel Distribution Board","Grid outage, site went down be=
cause Gen failed to start due to PWC ZTE malfunction // Gen manually starte=
d","franck.nkomot@matech-cameroun.com","190","10-05-2025 17:42:02","MATECH =
CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0004991562","Bit=
eng","","10-05-2025 16:34:55","10-05-2025 16:29:44","10-05-2025 17:05:44","=
Grid outage site went down because Gen failed to start due PWC dysfonction =
// He reset the PWC, site on Gen","Mba Lazare Herve","Equipment Repair","Pa=
ssive","Control Panel","Panel Distribution Board","Grid outage site went do=
wn because Gen failed to start due PWC dysfonction // He reset the PWC, sit=
e on Gen","franck.nkomot@matech-cameroun.com","312","10-05-2025 16:34:55","=
MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004991533","Nta=
ba","","10-05-2025 16:30:51","10-05-2025 16:25:38","10-05-2025 16:43:38","s=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","site went down due to PWC Overload(12Kw 2=
50A) Blaise Raoul SS IHS is iformed //Site stabilised","franck.nkomot@matec=
h-cameroun.com","315","10-05-2025 16:30:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004991336","Scalom-I=
HS","","10-05-2025 15:54:25","10-05-2025 15:47:24","10-05-2025 16:36:03","C=
ascaded Incident from TTO5119601","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because   Gen failed =
to start due to PWC ZTE malfunction // Gen manually started","system","2673=
69","10-05-2025 15:54:25","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004991324","Sca=
lom","IHS_YND_505","10-05-2025 15:52:40","10-05-2025 15:47:24","10-05-2025 =
16:37:36","Grid outage, site went down because   Gen failed to start due to=
 PWC ZTE malfunction // Gen manually started","Paul BIBOUM","Equipment Repa=
ir","Passive","Control Panel","Panel Distribution Board","Grid outage, site=
 went down because   Gen failed to start due to PWC ZTE malfunction // Gen =
manually started","franck.nkomot@matech-cameroun.com","317","10-05-2025 15:=
52:40","MATECH CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0004991311","B=
ONAS YDE","","10-05-2025 15:50:38","10-05-2025 14:12:27","10-05-2025 16:20:=
28","Active// No power Issue Site on Grid Ubai =3D54,6 V, The SS Eloundou B=
ertrand (693212405) from Huawei is informed","Paul BIBOUM","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power Issue Site on Grid Ubai =3D54,6 V, The SS Eloundou Bertrand (=
693212405) from Huawei is informed","christelle.ngonga@matech-cameroun.com"=
,"5892","10-05-2025 15:50:38","MATECH CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0004991297","B=
ondjock","","10-05-2025 15:47:25","10-05-2025 15:38:46","10-05-2025 16:31:4=
6","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, Site went down before Gen start due to poor battery b=
ackup // Grid return","christelle.ngonga@matech-cameroun.com","267799","10-=
05-2025 15:47:25","MATECH CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004991288","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_372","10-05-2025 15:45:26","10-05-20=
25 15:38:46","10-05-2025 16:31:46","Grid outage, Site went down before Gen =
start due to poor battery backup // Grid return","Fanda Brice","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
, Site went down before Gen start due to poor battery backup // Grid return=
","christelle.ngonga@matech-cameroun.com","401","10-05-2025 15:45:26","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0004991279","M=
inka","","10-05-2025 15:43:26","10-05-2025 15:38:46","10-05-2025 16:31:46",=
"","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage, Site went down before Gen start due to poor battery back=
up // Grid return","christelle.ngonga@matech-cameroun.com","267799","10-05-=
2025 15:43:26","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004991223","Ebo=
go","","10-05-2025 15:31:06","10-05-2025 15:24:29","10-05-2025 15:28:29","A=
ctive// No Power issue on site Ubaie 56V site on Grid, Julien /693095849 fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issue =
on site Ubaie 56V site on Grid, Julien /693095849 from Huawei is informed",=
"franck.nkomot@matech-cameroun.com","399","10-05-2025 15:31:06","MATECH CMR=
"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0004991164","M=
beng","","10-05-2025 15:26:01","10-05-2025 15:38:46","10-05-2025 16:31:46",=
"","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage, Site went down before Gen start due to poor battery back=
up // Grid return","christelle.ngonga@matech-cameroun.com","267799","10-05-=
2025 15:26:01","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004991107","O=
LAMA","","10-05-2025 15:17:40","10-05-2025 15:10:29","10-05-2025 15:25:29",=
"Active//No power issue on site Ubaie =3D54.9V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.9V site on Grid The TX FME Henri (69994969=
3) from Huawei is informed","christelle.ngonga@matech-cameroun.com","432","=
10-05-2025 15:17:40","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0004991041","T=
alla Monatele","","10-05-2025 15:02:25","10-05-2025 14:15:07","10-05-2025 1=
6:25:07","Active: no power issue, site is on grid with Ubaie=3D54.9V, Grego=
ir (654547479) from Huawei working on site","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: no power issue, site is on grid with Ubaie=3D54.9V, Gregoir (654547479=
) from Huawei working on site","ludivine.ngamaleu@ihstowers.com","2838","10=
-05-2025 15:02:25","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004991014","B=
itoto","","10-05-2025 14:53:31","10-05-2025 14:15:23","10-05-2025 16:00:23"=
,"Grid outage, site went down because Gen failed to start due to PWC ZTE ma=
lfunction // Gen manually started","Mba Lazare Herve","Equipment Repair","P=
assive","Control Panel","Panel Distribution Board","Grid outage, site went =
down because Gen failed to start due to PWC ZTE malfunction // Gen manually=
 started","christelle.ngonga@matech-cameroun.com","2289","10-05-2025 14:53:=
31","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004990804","M=
arche Odza","","10-05-2025 14:29:30","10-05-2025 11:45:22","10-05-2025 14:0=
5:14","Site went down due to 2/3 rectifiers faulty // he reseted it","Albra=
n Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","Site=
 went down due to 2/3 rectifiers faulty // he reseted it","loic.noumsi@mate=
ch-cameroun.com","9872","10-05-2025 14:29:30","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004990710","Oko=
lo Kilombo","","10-05-2025 14:20:05","10-05-2025 14:12:54","10-05-2025 16:1=
2:54","Active //no power issue Ubaie:54.8 V site on GEN The TX FME Synphori=
en (675295205) from Huawei is informed.","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve //no power issue Ubaie:54.8 V site on GEN The TX FME Synphorien (6752952=
05) from Huawei is informed.","loic.noumsi@matech-cameroun.com","431","10-0=
5-2025 14:20:05","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004990507","Eke=
kam","","10-05-2025 13:54:53","10-05-2025 13:52:56","10-05-2025 15:07:56","=
Grid outage site went down because Gen stopped with alarm HIGH temp due to =
Radiator pierced // He added water manually start of Gen","TIENTCHEU NZETCH=
IEU GAEL","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid out=
age site went down because Gen stopped with alarm HIGH temp due to Radiator=
 pierced // He added water manually start of Gen","loic.noumsi@matech-camer=
oun.com","118","10-05-2025 13:54:53","MATECH CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0004990461","B=
ISCUITERIE","","10-05-2025 13:52:25","10-05-2025 13:47:11","10-05-2025 15:3=
7:11"," Grid bad voltage, site down because,  gen ran still fuel shortage /=
/ site refuelled","Paul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Ou=
tage"," Grid bad voltage, site down because,  gen ran still fuel shortage /=
/ site refuelled","gaelle.njiofack@matech-cameroun.com","316","10-05-2025 1=
3:52:25","MATECH CMR"
"Closed Complete","Site Down","CTR_242","IHS_YND_059","NOCINC0004990031","E=
-Poste 2","","10-05-2025 12:38:57","10-05-2025 12:36:51","10-05-2025 12:38:=
06","ACTIVE/ No power issue site on Grid with Ubaie=3D53.1V , Site up witho=
ut intervention  MBAH OSIAH (699699694) from Huawei is informed","Paul BIBO=
UM","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","ACTIVE/ No power issue site on Grid with Ubaie=3D53.1V tx M=
ohamadou(691144435)from Huawei is informed","gaelle.njiofack@matech-camerou=
n.com","126","10-05-2025 12:38:57","MATECH CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0004989949","B=
ONAS YDE","","10-05-2025 12:22:08","10-05-2025 12:05:55","10-05-2025 14:02:=
43","Grid outage, site went down Gen failed to start due to PWC ZTE malfunc=
tion // Gen manually started","Paul BIBOUM","Equipment Repair","Passive","C=
ontrol Panel","Panel Distribution Board","Grid outage, site went down Gen f=
ailed to start due to PWC ZTE malfunction // Gen manually started","gaelle.=
njiofack@matech-cameroun.com","973","10-05-2025 12:22:08","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004989940","A=
wae Ewonkan","","10-05-2025 12:21:16","10-05-2025 12:14:09","10-05-2025 14:=
05:56","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // He reduced load","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down =
due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // He r=
educed load","gaelle.njiofack@matech-cameroun.com","428","10-05-2025 12:21:=
16","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004989725","C=
amp-Sic-Tsinga","","10-05-2025 11:45:12","10-05-2025 10:19:02","10-05-2025 =
10:27:11","Grid outage no space to deploy MGE // Grid return, Power issue r=
esolved but site remains down  Brice Tsague(650214096/ Huawei) is informed.=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage no space to deploy MGE // Grid return, Power issue resolved but s=
ite remains down  Brice Tsague(650214096/ Huawei) is informed.","gaelle.nji=
ofack@matech-cameroun.com","5171","10-05-2025 11:45:12","MATECH CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004989567","Bas=
tos Amb Coree","","10-05-2025 11:19:40","10-05-2025 10:47:30","10-05-2025 1=
1:59:41","Grid only site, no space to deploy MDGE // Grid returned","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only s=
ite, no space to deploy MDGE // Grid returned","loic.noumsi@matech-cameroun=
.com","1932","10-05-2025 11:19:40","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004989544","Sim=
e Building","","10-05-2025 11:13:32","10-05-2025 11:09:22","10-05-2025 11:1=
1:56","No power issue on site ,site on Gen wiith Ubaie=3D48.4 V The TX FME =
Brice Tsague/ 650214096/ Huawei is informed.","Mboua Thierry","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site ,site on Gen wiith Ubaie=3D48.4 V The TX FME Brice Ts=
ague/ 650214096/ Huawei is informed.","loic.noumsi@matech-cameroun.com","25=
0","10-05-2025 11:13:32","MATECH CMR"
"Closed Complete","Site Down","CTR_419","IHS_YND_227","NOCINC0004989164","M=
vog Betsi","","10-05-2025 10:17:11","10-05-2025 09:32:55","10-05-2025 10:29=
:03","Grid outage, Gen failed to start due to diesel filter blocked // clea=
ning the diesel filter and Gen start manually","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Fuel Filter","Grid outage, Gen failed =
to start due to diesel filter blocked // cleaning the diesel filter and Gen=
 start manually","gaelle.njiofack@matech-cameroun.com","2657","10-05-2025 1=
0:17:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004989137","Nkongtoc=
k","","10-05-2025 10:13:44","10-05-2025 10:06:53","10-05-2025 10:10:33","Ca=
scaded Incident from TTO5117114","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down before =
DG start due to Poor Batteries backup// Grid return","system","273511","10-=
05-2025 10:13:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004989136","TSINGA V=
ILLAGE 2","","10-05-2025 10:13:43","10-05-2025 10:06:53","10-05-2025 10:10:=
33","Cascaded Incident from TTO5117114","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
efore DG start due to Poor Batteries backup// Grid return","system","273510=
","10-05-2025 10:13:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004989135","Nkolfoul=
ou 2","","10-05-2025 10:13:43","10-05-2025 10:06:53","10-05-2025 10:10:33",=
"Cascaded Incident from TTO5117114","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 DG start due to Poor Batteries backup// Grid return","system","273511","10=
-05-2025 10:13:43","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004989120","N=
kolfoulou","IHS_YND_278, IHS_YND_719, IHS_YND_349","10-05-2025 10:10:48","1=
0-05-2025 10:06:53","10-05-2025 10:10:33","Grid outage, site went down befo=
re DG start due to Poor Batteries backup// Grid return","Siligap Boris","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e, site went down before DG start due to Poor Batteries backup// Grid retur=
n","gaelle.njiofack@matech-cameroun.com","236","10-05-2025 10:10:48","MATEC=
H CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004989025","Efo=
ulan MTN","","10-05-2025 09:49:10","10-05-2025 09:34:04","10-05-2025 10:25:=
03","Grid outage, Site went down because Gen started and stopped with ""low=
 oil pressure"" alarm// He reset card GE and gen manually started","MINKA N=
ICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","=
Grid outage, Site went down because Gen started and stopped with ""low oil =
pressure"" alarm// He reset card GE and gen manually started","loic.noumsi@=
matech-cameroun.com","907","10-05-2025 09:49:10","MATECH CMR"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0004989013","Nko=
lndom","","10-05-2025 09:48:13","10-05-2025 09:18:02","10-05-2025 09:54:03"=
,"Grid outage, site went down because Gen failed to start due to no automat=
ion // He started Gen manually","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","ATS-AMF Issue","Grid outage, site went down because Ge=
n failed to start due to no automation // He started Gen manually","loic.no=
umsi@matech-cameroun.com","1812","10-05-2025 09:48:13","MATECH CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0004988991","A=
n-Marche-Melen","IHS_YND_141","10-05-2025 09:45:22","10-05-2025 09:27:14","=
10-05-2025 11:10:23","Grid outage, No space to deploy MDG // Grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage, No space to deploy MDG // Grid return","gaelle.njiofack@matech-came=
roun.com","1089","10-05-2025 09:45:22","MATECH CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0004988929","N=
ew-Marche-Melen","","10-05-2025 09:30:52","10-05-2025 09:27:14","10-05-2025=
 11:10:23","","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid outage, No space to deploy MDG // Grid return","gaell=
e.njiofack@matech-cameroun.com","268499","10-05-2025 09:30:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004988921","Scalom-I=
HS","","10-05-2025 09:27:53","10-05-2025 09:07:43","10-05-2025 11:18:55","C=
ascaded Incident from TTO5116872","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because Gen failed to=
 start due to no automation // He started Gen manually","system","276953","=
10-05-2025 09:27:53","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004988906","S=
calom","IHS_YND_505","10-05-2025 09:25:53","10-05-2025 09:07:43","10-05-202=
5 11:20:56","Grid outage, site went down because Gen failed to start due to=
 no automation // He started Gen manually","Paul BIBOUM","Equipment Repair"=
,"Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down bec=
ause Gen failed to start due to no automation // He started Gen manually","=
gaelle.njiofack@matech-cameroun.com","1091","10-05-2025 09:25:53","MATECH C=
MR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004988799","Saa=
","","10-05-2025 09:09:26","10-05-2025 09:00:21","10-05-2025 10:04:49","Gri=
d outage, site went down because Gen failed to start due to battery Ge faul=
ty // he started it with an external battery, site on Gen","Parker Tchoup",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid ou=
tage, site went down because Gen failed to start due to battery Ge faulty /=
/ he started it with an external battery, site on Gen","loic.noumsi@matech-=
cameroun.com","546","10-05-2025 09:09:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0004988783","Yona Hot=
el","","10-05-2025 09:05:56","10-05-2025 09:01:03","10-05-2025 09:34:08","C=
ascaded Incident from TTO5116695","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site went do=
wn because gen failed to start with alarm undervoltage // He reset gen card=
 and gen manually started","system","270222","10-05-2025 09:05:56","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0004988784","Dagobert=
","","10-05-2025 09:05:56","10-05-2025 09:01:03","10-05-2025 09:34:08","Cas=
caded Incident from TTO5116695","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 because gen failed to start with alarm undervoltage // He reset gen card a=
nd gen manually started","system","270222","10-05-2025 09:05:56","MATECH CM=
R"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0004988749","N=
kolbi-Boss","IHS_YND_271, IHS_YND_286","10-05-2025 09:04:14","10-05-2025 09=
:01:03","10-05-2025 09:41:12","Grid outage, site went down because gen fail=
ed to start with alarm undervoltage // He reset gen card and gen manually s=
tarted","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Grid outage, site went down because gen failed to s=
tart with alarm undervoltage // He reset gen card and gen manually started"=
,"loic.noumsi@matech-cameroun.com","192","10-05-2025 09:04:14","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004988607","M=
elen Ba'aba","","10-05-2025 08:42:12","10-05-2025 08:41:05","10-05-2025 11:=
03:46","Grid outage, Gen failed to start due to alternator belt cut // alte=
rnator belt replace and Gen start manually","Siligap Boris","Equipment Repa=
ir","Passive","Infrastructure","Armoured Cable","Grid outage, Gen failed to=
 start due to alternator belt cut // alternator belt replace and Gen start =
manually","gaelle.njiofack@matech-cameroun.com","68","10-05-2025 08:42:12",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004988587","B=
arriere IHS","","10-05-2025 08:40:43","10-05-2025 08:33:37","10-05-2025 10:=
08:19","Active//No power issue U=3D 53.7V Site on Grid , Site up without in=
tervention","Hyemafo Gildas","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active//No power issue U=3D 53.7V =
Site on Grid , Site up without intervention","gaelle.njiofack@matech-camero=
un.com","427","10-05-2025 08:40:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0004988580","Bastos-B=
AT","","10-05-2025 08:39:02","10-05-2025 08:33:59","10-05-2025 10:05:51","C=
ascaded Incident from TTO5116492","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active/No power issue on site, site on =
Gen Ubay =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ HUAWEI) is inform=
ed","system","271862","10-05-2025 08:39:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_207","NOCINC0004988576","ARMP Bui=
lding","","10-05-2025 08:39:02","10-05-2025 08:33:59","10-05-2025 10:05:51"=
,"Cascaded Incident from TTO5116492","Mboua Thierry","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active/No power issue on site, site =
on Gen Ubay =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ HUAWEI) is inf=
ormed","system","271861","10-05-2025 08:39:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_514","NOCINC0004988579","Etoudi2"=
,"","10-05-2025 08:39:02","10-05-2025 08:33:59","10-05-2025 10:05:51","Casc=
aded Incident from TTO5116492","Delor Telezing","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active/No power issue on site, site on Ge=
n Ubay =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ HUAWEI) is informed=
","system","271861","10-05-2025 08:39:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_035","NOCINC0004988578","Bastos A=
mb Coree","","10-05-2025 08:39:02","10-05-2025 08:33:59","10-05-2025 10:05:=
51","Cascaded Incident from TTO5116492","","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active/No power issue on site, site on Gen Uba=
y =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ HUAWEI) is informed","sy=
stem","271860","10-05-2025 08:39:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004988577","Bastos B=
ir","","10-05-2025 08:39:02","10-05-2025 08:33:59","10-05-2025 10:05:51","C=
ascaded Incident from TTO5116492","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active/No power issue on site, site on =
Gen Ubay =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ HUAWEI) is inform=
ed","system","271863","10-05-2025 08:39:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0004988572","Dragage"=
,"","10-05-2025 08:39:01","10-05-2025 08:33:59","10-05-2025 10:05:51","Casc=
aded Incident from TTO5116492","Mboua Thierry","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active/No power issue on site, site on Gen=
 Ubay =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ HUAWEI) is informed"=
,"system","271860","10-05-2025 08:39:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_516","NOCINC0004988574","ETOUDI E=
ntree du palais","","10-05-2025 08:39:01","10-05-2025 08:33:59","10-05-2025=
 10:05:51","Cascaded Incident from TTO5116492","Fabrice Pouakam","Cascade O=
utage","Active","Cascade Active","Cascade Active","Active/No power issue on=
 site, site on Gen Ubay =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ HU=
AWEI) is informed","system","271862","10-05-2025 08:39:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_206","NOCINC0004988573","ARMP",""=
,"10-05-2025 08:39:01","10-05-2025 08:33:59","10-05-2025 10:05:51","Cascade=
d Incident from TTO5116492","Mboua Thierry","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active/No power issue on site, site on Gen Ub=
ay =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ HUAWEI) is informed","s=
ystem","271861","10-05-2025 08:39:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004988575","Omnispor=
t-Rail","","10-05-2025 08:39:01","10-05-2025 08:33:59","10-05-2025 10:05:51=
","Cascaded Incident from TTO5116492","Delor Telezing","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active/No power issue on site, sit=
e on Gen Ubay =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ HUAWEI) is i=
nformed","system","271864","10-05-2025 08:39:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_195","NOCINC0004988571","china em=
bassy yde","","10-05-2025 08:39:00","10-05-2025 08:33:59","10-05-2025 10:05=
:51","Cascaded Incident from TTO5116492","","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active/No power issue on site, site on Gen Ub=
ay =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ HUAWEI) is informed","s=
ystem","271863","10-05-2025 08:39:00","MATECH CMR"
"Closed Complete","Site Down","T0046","IHS_YND_191","NOCINC0004988561","Mba=
lla II","IHS_YND_195, IHS_YND_192, IHS_YND_206, IHS_YND_516, IHS_YND_506, I=
HS_YND_207, IHS_YND_704, IHS_YND_035, IHS_YND_514, IHS_YND_129","10-05-2025=
 08:37:05","10-05-2025 08:33:59","10-05-2025 10:05:51","Active/No power iss=
ue on site, site on Gen Ubay =3D 49.9 V, Fme Tx Eloundou Bertrand (65258657=
8/ HUAWEI) is informed","Delor Telezing","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active/No power issue =
on site, site on Gen Ubay =3D 49.9 V, Fme Tx Eloundou Bertrand (652586578/ =
HUAWEI) is informed","loic.noumsi@matech-cameroun.com","186","10-05-2025 08=
:37:05","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004988495","B=
riqueterie","","10-05-2025 08:16:21","10-05-2025 08:12:32","10-05-2025 09:2=
7:01","Grid only site, no space to deploy MDGE (awaiting Grid) // Grid retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid only site, no space to deploy MDGE (awaiting Grid) // Grid return","ga=
elle.njiofack@matech-cameroun.com","231","10-05-2025 08:16:21","MATECH CMR"
"Closed Complete","Site Down","CTR_419","IHS_YND_227","NOCINC0004988459","M=
vog Betsi","","10-05-2025 08:06:47","10-05-2025 08:01:39","10-05-2025 08:43=
:38","Grid outage, site went down due to fuse of card GE faulty // he did b=
ridge on the good fuses","Hyemafo Gildas","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage, site went down due to fuse of c=
ard GE faulty // he did bridge on the good fuses","gaelle.njiofack@matech-c=
ameroun.com","309","10-05-2025 08:06:47","MATECH CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004988454","M=
amch Building","","10-05-2025 08:04:58","10-05-2025 07:54:56","10-05-2025 1=
1:48:00","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid only site, no space to deploy MDGE // Grid returned",=
"gaelle.njiofack@matech-cameroun.com","281443","10-05-2025 08:04:58","MATEC=
H CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004988446","Cha=
rles-Atangana","IHS_YND_051","10-05-2025 08:03:08","10-05-2025 07:54:56","1=
0-05-2025 11:56:00","Grid only site, no space to deploy MDGE // Grid return=
ed","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid only site, no space to deploy MDGE // Grid returned","loic.noumsi@mate=
ch-cameroun.com","696","10-05-2025 08:03:08","MATECH CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004988405","Bri=
quetterie","","10-05-2025 07:56:41","10-05-2025 07:38:30","10-05-2025 09:36=
:33","Grid only site, no space to deploy MDGE // Grid returned","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site,=
 no space to deploy MDGE // Grid returned","loic.noumsi@matech-cameroun.com=
","1092","10-05-2025 07:56:41","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004988305","N=
kolfon Cimencam","","10-05-2025 07:47:11","10-05-2025 07:41:55","10-05-2025=
 08:25:48","No power issue, Site impacted by Afanoya_II","Hyemafo Gildas","=
Customer Equipment Failure","Active","Active Equipment Failure","Affected b=
y 3rd Party Site","No power issue, Site impacted by Afanoya_II","gaelle.nji=
ofack@matech-cameroun.com","318","10-05-2025 07:47:11","MATECH CMR"
"Closed Complete","Site Down","T0526","IHS_YND_088","NOCINC0004988258","Elo=
bi Mokolo","","10-05-2025 07:37:25","10-05-2025 07:30:17","10-05-2025 09:25=
:53","Site went down due to Grid bad voltage and no RCP on site // He bypas=
sed Grid and started Gen manually","Mboua Thierry","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Site went down due to Gri=
d bad voltage and no RCP on site // He bypassed Grid and started Gen manual=
ly","loic.noumsi@matech-cameroun.com","429","10-05-2025 07:37:25","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_258","NOCINC0004988253","Mefou-As=
si","IHS_YND_537, IHS_YND_520","10-05-2025 07:36:05","10-05-2025 07:15:09",=
"10-05-2025 09:48:22","Active// No power issue on site Ubaie=3D53.1 V site =
On Gen The Tx FME Fulbert(654266068) of huawei is informed. Repetitive issu=
e","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active// No power issue on site Ubaie=3D54.5V =
site On Grid The Tx FME Fulbert(654266068) of huawei is informed. Repetitiv=
e issue","system","1256","10-05-2025 07:36:05","MATECH CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0004988238","Mae=
tur","","10-05-2025 07:32:14","10-05-2025 07:16:31","10-05-2025 08:10:59","=
Grid outage, site down due to GE circuit breaker (32 A) disjunction  // CB =
rearmed","Mboua Thierry","Equipment Repair","Passive","Control Panel","Circ=
uit Breaker Tripped","Grid outage, site down due to GE circuit breaker (32 =
A) disjunction  // CB rearmed","loic.noumsi@matech-cameroun.com","944","10-=
05-2025 07:32:14","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004988217","S=
IMBOCK BONAMBAPE","","10-05-2025 07:26:04","10-05-2025 07:15:09","10-05-202=
5 08:48:22","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active",=
"Cascade Active","Active// No power issue on site Ubaie=3D54.5V site On Gri=
d The Tx FME Fulbert(654266068) of huawei is informed. Repetitive issue","g=
aelle.njiofack@matech-cameroun.com","276384","10-05-2025 07:26:04","MATECH =
CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004988197","M=
EFOU ASSI","","10-05-2025 07:21:23","10-05-2025 07:15:09","10-05-2025 08:48=
:22","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","Active// No power issue on site Ubaie=3D54.5V site On Grid The Tx F=
ME Fulbert(654266068) of huawei is informed. Repetitive issue","gaelle.njio=
fack@matech-cameroun.com","276384","10-05-2025 07:21:23","MATECH CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004988025","MAN=
GUIERS CHAPELLE","","10-05-2025 06:33:29","10-05-2025 06:24:14","10-05-2025=
 10:13:42","Grid outage, site went down due to gen overload (22kva, 340A) S=
S IHS Bernard ATANGANA is informed and confirmed // Grid returned","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, site went down due to gen overload (22kva, 340A) SS IHS Bernard ATAN=
GANA is informed and confirmed // Grid returned","gerard.tchangoue@matech-c=
ameroun.com","556","10-05-2025 06:33:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_207","NOCINC0004988020","ARMP Bui=
lding","","10-05-2025 06:32:23","10-05-2025 06:21:41","10-05-2025 06:47:30"=
,"Cascaded Incident from TTO5115809","Mboua Thierry","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down due t=
o Ge Card malfunctionning // He reconfigured Ge Card","system","272642","10=
-05-2025 06:32:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0004988015","Bastos-B=
AT","","10-05-2025 06:30:53","10-05-2025 06:21:41","10-05-2025 06:47:30","C=
ascaded Incident from TTO5115809","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to G=
e Card malfunctionning // He reconfigured Ge Card","system","272643","10-05=
-2025 06:30:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_514","NOCINC0004988014","Etoudi2"=
,"","10-05-2025 06:30:53","10-05-2025 06:21:41","10-05-2025 06:47:30","Casc=
aded Incident from TTO5115809","Delor Telezing","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to Ge =
Card malfunctionning // He reconfigured Ge Card","system","272641","10-05-2=
025 06:30:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004988011","Omnispor=
t-Rail","","10-05-2025 06:30:52","10-05-2025 06:21:41","10-05-2025 06:47:30=
","Cascaded Incident from TTO5115809","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to Ge Card malfunctionning // He reconfigured Ge Card","system","272644","=
10-05-2025 06:30:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_035","NOCINC0004988013","Bastos A=
mb Coree","","10-05-2025 06:30:52","10-05-2025 06:21:41","10-05-2025 06:47:=
30","Cascaded Incident from TTO5115809","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down due to Ge Card =
malfunctionning // He reconfigured Ge Card","system","272640","10-05-2025 0=
6:30:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_206","NOCINC0004988010","ARMP",""=
,"10-05-2025 06:30:52","10-05-2025 06:21:41","10-05-2025 06:47:30","Cascade=
d Incident from TTO5115809","Mboua Thierry","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, site went down due to Ge Card=
 malfunctionning // He reconfigured Ge Card","system","272641","10-05-2025 =
06:30:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004988012","Bastos B=
ir","","10-05-2025 06:30:52","10-05-2025 06:21:41","10-05-2025 06:47:30","C=
ascaded Incident from TTO5115809","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to G=
e Card malfunctionning // He reconfigured Ge Card","system","272642","10-05=
-2025 06:30:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_195","NOCINC0004988008","china em=
bassy yde","","10-05-2025 06:30:51","10-05-2025 06:21:41","10-05-2025 06:47=
:30","Cascaded Incident from TTO5115809","","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, site went down due to Ge Card=
 malfunctionning // He reconfigured Ge Card","system","272643","10-05-2025 =
06:30:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0004988009","Dragage"=
,"","10-05-2025 06:30:51","10-05-2025 06:21:41","10-05-2025 06:47:30","Casc=
aded Incident from TTO5115809","Mboua Thierry","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down due to Ge C=
ard malfunctionning // He reconfigured Ge Card","system","272640","10-05-20=
25 06:30:51","MATECH CMR"
"Closed Complete","Site Down","T0046","IHS_YND_191","NOCINC0004987977","Mba=
lla II","IHS_YND_195, IHS_YND_192, IHS_YND_206, IHS_YND_506, IHS_YND_207, I=
HS_YND_704, IHS_YND_035, IHS_YND_514, IHS_YND_129","10-05-2025 06:23:48","1=
0-05-2025 06:21:41","10-05-2025 06:47:30","Grid outage, site went down due =
to Ge Card malfunctionning // He reconfigured Ge Card","Delor Telezing","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, s=
ite went down due to Ge Card malfunctionning // He reconfigured Ge Card","e=
dwige.kapawo@matech-cameroun.com","128","10-05-2025 06:23:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004987870","TSINGA V=
ILLAGE 2","","10-05-2025 06:01:34","10-05-2025 05:55:39","10-05-2025 06:00:=
09","Cascaded Incident from TTO5115668","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
efore DG start due to Poor Batteries backup// Grid return ","system","26709=
2","10-05-2025 06:01:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004987869","Melen Ba=
'aba","","10-05-2025 06:01:34","10-05-2025 05:55:39","10-05-2025 06:00:09",=
"Cascaded Incident from TTO5115668","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 DG start due to Poor Batteries backup// Grid return ","system","267092","1=
0-05-2025 06:01:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004987868","Nkolfoul=
ou 2","","10-05-2025 06:01:34","10-05-2025 05:55:39","10-05-2025 06:00:09",=
"Cascaded Incident from TTO5115668","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 DG start due to Poor Batteries backup// Grid return ","system","267093","1=
0-05-2025 06:01:34","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004987854","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","10-05-2025 05:59:50","1=
0-05-2025 05:55:39","10-05-2025 06:00:09","Grid outage, site went down befo=
re DG start due to Poor Batteries backup// Grid return ","Siligap Boris","E=
quipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","G=
rid outage, site went down before DG start due to Poor Batteries backup// G=
rid return ","edwige.kapawo@matech-cameroun.com","251","10-05-2025 05:59:50=
","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004987804","MBA=
LNGONG LYCEE","","10-05-2025 05:43:35","10-05-2025 05:33:59","10-05-2025 05=
:49:03","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, Site went down because Gen stopped due to overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed//Grid return","gerard.tchangoue@matec=
h-cameroun.com","578","10-05-2025 05:43:35","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004987790","Nko=
l-Mebanga","","10-05-2025 05:37:56","10-05-2025 05:35:33","10-05-2025 11:22=
:09","Solar only site, // solar returned","Parker Tchoup","Equipment Repair=
","Passive","Solar","Solar Control Panel Board","Solar only site, // solar =
return","gerard.tchangoue@matech-cameroun.com","144","10-05-2025 05:37:56",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004987789","N=
kolfon Cimencam","","10-05-2025 05:36:51","10-05-2025 05:27:43","10-05-2025=
 06:38:06","No power issue, Site impacted  by Afanoya_II","Hyemafo Gildas",=
"Customer Equipment Failure","Active","Active Equipment Failure","Affected =
by 3rd Party Site","No power issue, Site impacted  by Afanoya_II","edwige.k=
apawo@matech-cameroun.com","549","10-05-2025 05:36:51","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004987649","Elo=
umdem stade","","10-05-2025 04:43:20","10-05-2025 04:34:59","10-05-2025 06:=
01:54","Site went down due to Grid bad voltage,and gen failed to start,no r=
cp // bypassed grid and started the gen","Fanda Brice","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Site went down due to=
 Grid bad voltage,and gen failed to start,no rcp // bypassed grid and start=
ed the gen","gerard.tchangoue@matech-cameroun.com","502","10-05-2025 04:43:=
20","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004987541","B=
arriere IHS","","10-05-2025 04:08:35","10-05-2025 03:58:43","10-05-2025 05:=
20:44","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, site went down due to Gen OVERLOAD (15 KVA, 17=
0 A) // He reduced load","edwige.kapawo@matech-cameroun.com","266626","10-0=
5-2025 04:08:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0004987536","MEFOU AS=
SI","","10-05-2025 04:06:16","10-05-2025 03:58:43","10-05-2025 05:20:44",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid outage, site went down due to Gen OVERLOAD (15 KVA, 170 A) // He r=
educed load","system","266626","10-05-2025 04:06:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_520","NOCINC0004987537","SIMBOCK =
BONAMBAPE","","10-05-2025 04:06:16","10-05-2025 03:58:43","10-05-2025 05:20=
:44","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, site went down due to Gen OVERLOAD (15 KVA, 170 =
A) // He reduced load","system","266627","10-05-2025 04:06:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_054","NOCINC0004987535","Olezoa M=
TN","","10-05-2025 04:04:44","10-05-2025 03:44:34","10-05-2025 04:04:28","C=
ascaded Incident from TTO5115244","MINKA NICOLAS","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","ACTIVE No power issue on site U =3D 54,=
1 V site on Grid,  Brice Tsague of huawei is informed. Site impacted by Yao=
unde MSC","system","267540","10-05-2025 04:04:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0004987534","Nkoa Ayo=
s","","10-05-2025 04:04:44","10-05-2025 03:44:34","10-05-2025 04:04:28","Ca=
scaded Incident from TTO5115244","MINKA NICOLAS","Cascade Outage","Active",=
"Cascade Active","Cascade Active","ACTIVE No power issue on site U =3D 54,1=
 V site on Grid,  Brice Tsague of huawei is informed. Site impacted by Yaou=
nde MSC","system","267540","10-05-2025 04:04:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_066","NOCINC0004987533","GSO","",=
"10-05-2025 04:04:44","10-05-2025 03:44:34","10-05-2025 04:04:28","Cascaded=
 Incident from TTO5115244","MINKA NICOLAS","Cascade Outage","Active","Casca=
de Active","Cascade Active","ACTIVE No power issue on site U =3D 54,1 V sit=
e on Grid,  Brice Tsague of huawei is informed. Site impacted by Yaounde MS=
C","system","267541","10-05-2025 04:04:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_039","NOCINC0004987532","Siantou =
Radio TV","","10-05-2025 04:04:43","10-05-2025 03:44:34","10-05-2025 04:04:=
28","Cascaded Incident from TTO5115244","","Cascade Outage","Active","Casca=
de Active","Cascade Active","ACTIVE No power issue on site U =3D 54,1 V sit=
e on Grid,  Brice Tsague of huawei is informed. Site impacted by Yaounde MS=
C","system","267539","10-05-2025 04:04:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_038","NOCINC0004987529","Siantou =
Inferieur","","10-05-2025 04:04:43","10-05-2025 03:44:34","10-05-2025 04:04=
:28","Cascaded Incident from TTO5115244","","Cascade Outage","Active","Casc=
ade Active","Cascade Active","ACTIVE No power issue on site U =3D 54,1 V si=
te on Grid,  Brice Tsague of huawei is informed. Site impacted by Yaounde M=
SC","system","267541","10-05-2025 04:04:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_070","NOCINC0004987531","Efoulan"=
,"","10-05-2025 04:04:43","10-05-2025 03:44:34","10-05-2025 04:04:28","Casc=
aded Incident from TTO5115244","MINKA NICOLAS","Cascade Outage","Active","C=
ascade Active","Cascade Active","ACTIVE No power issue on site U =3D 54,1 V=
 site on Grid,  Brice Tsague of huawei is informed. Site impacted by Yaound=
e MSC","system","267539","10-05-2025 04:04:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_508","NOCINC0004987530","Crf-Nsam=
","","10-05-2025 04:04:43","10-05-2025 03:44:34","10-05-2025 04:04:28","Cas=
caded Incident from TTO5115244","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE No power issue on site U =3D 54,1 =
V site on Grid,  Brice Tsague of huawei is informed. Site impacted by Yaoun=
de MSC","system","267540","10-05-2025 04:04:43","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004987528","M=
efou-Assi","IHS_YND_537, IHS_YND_520, IHS_YND_696","10-05-2025 04:03:56","1=
0-05-2025 03:58:43","10-05-2025 05:20:44","Grid outage, site went down due =
to Gen OVERLOAD (15 KVA, 170 A) // He reduced load","Fanda Brice","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went do=
wn due to Gen OVERLOAD (15 KVA, 170 A) // He reduced load","edwige.kapawo@m=
atech-cameroun.com","314","10-05-2025 04:03:56","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004987493","Efo=
ulan MTN","IHS_YND_038, IHS_YND_508, IHS_YND_070, IHS_YND_039, IHS_YND_066,=
 IHS_YND_067, IHS_YND_054","10-05-2025 03:51:43","10-05-2025 03:44:34","10-=
05-2025 04:04:28","ACTIVE No power issue on site U =3D 54,1 V site on Grid,=
  Brice Tsague of huawei is informed. Site impacted by Yaounde MSC","MINKA =
NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure","=
Affected by 3rd Party Site","ACTIVE No power issue on site U =3D 54,1 V sit=
e on Grid,  Brice Tsague of huawei is informed. Site impacted by Yaounde MS=
C","gerard.tchangoue@matech-cameroun.com","430","10-05-2025 03:51:43","MATE=
CH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004987402","Mok=
olo Yaounde","","10-05-2025 03:12:25","10-05-2025 03:04:14","10-05-2025 08:=
46:10","Grid only site, no space to deploy MDGE // Grid returned","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e, no space to deploy MDGE // Grid returned","gerard.tchangoue@matech-camer=
oun.com","493","10-05-2025 03:12:25","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004987320","Ebo=
go","","10-05-2025 02:36:01","10-05-2025 02:26:59","10-05-2025 05:41:58","G=
rid outage,site went down before gen starts due to poor battery backup // G=
rid returned","Siligap Boris","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage,site went down before gen starts=
 due to poor battery backup // Grid returned","gerard.tchangoue@matech-came=
roun.com","543","10-05-2025 02:36:01","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004987152","Lad=
a I Yde","","10-05-2025 01:11:46","10-05-2025 01:05:35","10-05-2025 01:12:1=
7","Active//No power issue site on Grid with U=3D54.8V Lionel Adjep(6551848=
76) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue site on Grid with U=3D54.9V Lionel Adjep(655184876) from Huawei is =
informed","gerard.tchangoue@matech-cameroun.com","372","10-05-2025 01:11:46=
","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004986618","S=
aa","","09-05-2025 22:39:41","09-05-2025 22:36:30","09-05-2025 23:32:14","A=
ctive // No power issue site on Grid, with Ubaie: 54.3V. The Tx Fme Gregoir=
e (654547479) from Huawei informed","Parker Tchoup","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue site on Grid, with Ubaie: 54.3V. The Tx Fme Gregoire (6545474=
79) from Huawei informed","edwige.kapawo@matech-cameroun.com","192","09-05-=
2025 22:39:41","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004986113","Jou=
vence Mbenda","","09-05-2025 21:02:33","09-05-2025 20:54:09","09-05-2025 21=
:46:09","Grid outage site went down because Gen stopped with alarm HIGH tem=
p // He added water Gen manually started","Hyemafo Gildas","Equipment Repai=
r","Passive","ACDG Gen","Gen Temp High","Grid outage site went down because=
 Gen stopped with alarm HIGH temp // He added water Gen manually started","=
franck.nkomot@matech-cameroun.com","505","09-05-2025 21:02:33","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004985983","BAT=
A Mokolo OCM","","09-05-2025 20:40:34","29-04-2025 13:39:12","30-04-2025 07=
:52:43","Grid outage.no space to deploy mobile gen//Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no=
 space to deploy mobile gen//Grid return","christelle.ngonga@matech-camerou=
n.com","889282","09-05-2025 20:40:34","MATECH CMR"
"Closed Complete","Site Down","T3175","IHS_YND_566","NOCINC0004985941","Crf=
 Cornier","","09-05-2025 20:29:57","09-05-2025 20:22:47","09-05-2025 22:02:=
47","Site went down due to Dysjunction of CB in PWC due to increse load // =
CB put back on","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","R=
ectifier Module Overloaded","Site went down due to Dysjunction of CB in PWC=
 due to increse load // CB put back on","franck.nkomot@matech-cameroun.com"=
,"431","09-05-2025 20:29:57","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004985848","D=
amas","","09-05-2025 20:05:12","09-05-2025 20:00:06","09-05-2025 20:05:06",=
"Active// No power Issue Site on Grid Ubai =3D53,8 V, The FME The TX FME Mb=
ah Hosiah (674007438) is informed.","MINKA NICOLAS","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No=
 power Issue Site on Grid Ubai =3D53,8 V, The FME The TX FME Mbah Hosiah (6=
74007438) is informed.","christelle.ngonga@matech-cameroun.com","307","09-0=
5-2025 20:05:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004985834","Barriere=
 IHS","","09-05-2025 20:00:10","09-05-2025 19:19:58","09-05-2025 21:46:58",=
"Cascaded Incident from TTO5113011","Hyemafo Gildas","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down due t=
o Gen OVERLOAD (15 KVA, 170 A) // Grid returned","system","268949","09-05-2=
025 20:00:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_520","NOCINC0004985833","SIMBOCK =
BONAMBAPE","","09-05-2025 20:00:10","09-05-2025 19:19:58","09-05-2025 21:46=
:58","Cascaded Incident from TTO5113011","Hyemafo Gildas","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
due to Gen OVERLOAD (15 KVA, 170 A) // Grid returned","system","268949","09=
-05-2025 20:00:10","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004985611","B=
arriere","","09-05-2025 19:28:09","09-05-2025 19:19:55","09-05-2025 23:17:4=
6","Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS F=
elix ZAMBE confirmed//grid return","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen=
 overload (20kva, 400A) SS IHS Felix ZAMBE confirmed//grid return","franck.=
nkomot@matech-cameroun.com","496","09-05-2025 19:28:09","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004985594","M=
EFOU ASSI","","09-05-2025 19:24:52","09-05-2025 19:19:58","09-05-2025 21:46=
:58","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, site went down due to Gen OVERLOAD (15 KVA, 170 A) =
// Grid returned","christelle.ngonga@matech-cameroun.com","268949","09-05-2=
025 19:24:52","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004985590","M=
efou-Assi","IHS_YND_537, IHS_YND_520, IHS_YND_696","09-05-2025 19:24:09","0=
9-05-2025 19:19:58","09-05-2025 21:46:58","Grid outage, site went down due =
to Gen OVERLOAD (15 KVA, 170 A) // Grid returned","Fanda Brice","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down=
 due to Gen OVERLOAD (15 KVA, 170 A) // Grid returned","christelle.ngonga@m=
atech-cameroun.com","252","09-05-2025 19:24:09","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004985587","E=
koumdoum","","09-05-2025 19:23:10","09-05-2025 19:15:03","09-05-2025 21:35:=
05","Grid bad voltage, site went down because Gen failed to start due to la=
ck of 01 phase // He did a bridge on the good phase","Albran Byorel","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid ba=
d voltage, site went down because Gen failed to start due to lack of 01 pha=
se // He did a bridge on the good phase","christelle.ngonga@matech-cameroun=
.com","488","09-05-2025 19:23:10","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004985582","C=
RF Nkoabang","","09-05-2025 19:22:06","09-05-2025 19:20:58","10-05-2025 09:=
37:35","Grid-solar site, Grid outage, site down due to sunset, // Grid retu=
rn ","Mba Lazare Herve","Equipment Repair","Passive","Solar","Solar Synchro=
nization","Grid-solar site, Grid outage, site down due to sunset, // Grid r=
eturn ","christelle.ngonga@matech-cameroun.com","69","09-05-2025 19:22:06",=
"MATECH CMR"
"Closed Complete","Site Down","T0395","IHS_YND_065","NOCINC0004985546","Ess=
os DCS","","09-05-2025 19:18:53","09-05-2025 19:10:35","09-05-2025 20:43:35=
","Grid outage site went down because Gen failed to start due to grid conta=
ctor faulty// Gen manually started","Delor Telezing","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","Grid outage site went down because =
Gen failed to start due to grid contactor faulty// Gen manually started","f=
ranck.nkomot@matech-cameroun.com","499","09-05-2025 19:18:53","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004985502","Men=
dong NB","","09-05-2025 19:07:48","09-05-2025 19:01:37","09-05-2025 20:24:3=
7","Grid Only, No space to deploy // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid Only, No space to deploy=
 // Grid return","franck.nkomot@matech-cameroun.com","372","09-05-2025 19:0=
7:48","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004985488","O=
dza","","09-05-2025 19:04:25","09-05-2025 18:58:15","09-05-2025 19:07:15","=
Active/ No power issue on site, site on Grid, Ubay 53V Lienel Adhex / 65518=
4876 from Huawei is informed","Albran Byorel","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/ No power =
issue on site, site on Grid, Ubay 53V Lienel Adhex / 655184876 from Huawei =
is informed","christelle.ngonga@matech-cameroun.com","371","09-05-2025 19:0=
4:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004985430","Angongo"=
,"","09-05-2025 18:53:42","09-05-2025 18:49:42","09-05-2025 19:06:42","Casc=
aded Incident from TTO5112816","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down because Gen st=
opped with alarm HIGH temp // He added water Gen manually started","system"=
,"278116","09-05-2025 18:53:42","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004985419","E=
beba","IHS_YND_335","09-05-2025 18:51:50","09-05-2025 18:39:42","09-05-2025=
 19:06:42","Grid outage site went down because Gen stopped with alarm HIGH =
temp // He added water Gen manually started","Fanda Brice","Equipment Repai=
r","Passive","ACDG Gen","Gen Temp High","Grid outage site went down because=
 Gen stopped with alarm HIGH temp // He added water Gen manually started","=
christelle.ngonga@matech-cameroun.com","921","09-05-2025 18:51:50","MATECH =
CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004985407","A=
wae Ewonkan","","09-05-2025 18:50:41","09-05-2025 18:47:31","09-05-2025 20:=
50:31","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid Restored","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid R=
estored","christelle.ngonga@matech-cameroun.com","191","09-05-2025 18:50:41=
","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004985324","NTU=
I TOWN","","09-05-2025 18:31:13","09-05-2025 18:29:05","09-05-2025 20:05:05=
","Site went down Because gen fails to start due to lack of 01 phase on sit=
e // He make the bridge with a good phase: Site on grid","Parker Tchoup","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went down B=
ecause gen fails to start due to lack of 01 phase on site // He make the br=
idge with a good phase: Site on grid","franck.nkomot@matech-cameroun.com","=
129","09-05-2025 18:31:13","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004985295","Nko=
g-Edzen","","09-05-2025 18:29:08","09-05-2025 18:08:39","09-05-2025 18:20:3=
9","Active//No power issue on site, Site on Grid Ubay =3D 54.6V The Tx Fme =
Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Grid Ubay =3D 54.6V The Tx Fme Greg=
oire (654547479) from Huawei is informed.","franck.nkomot@matech-cameroun.c=
om","1230","09-05-2025 18:29:08","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004985067","E=
lig-Edzoa","","09-05-2025 17:55:58","09-05-2025 17:55:54","09-05-2025 18:16=
:10","No power issue on site Ubay 54.6V site on Gird, Site up without inter=
vention","","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","No power issue on site Ubay 54.6V site on Gird, Sit=
e up without intervention","christelle.ngonga@matech-cameroun.com","5","09-=
05-2025 17:55:58","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004985061","M=
EHANDAN","","09-05-2025 17:54:47","09-05-2025 17:48:52","09-05-2025 17:58:3=
9","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, site went down because gen failed to start due to P=
WC ZTE malfunction // Grid return","christelle.ngonga@matech-cameroun.com",=
"267101","09-05-2025 17:54:47","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004985053","O=
dza II OCM","IHS_YND_528","09-05-2025 17:54:00","09-05-2025 17:48:52","09-0=
5-2025 17:58:39","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid return","Albran Byorel","Equipment Repair=
","Passive","Control Panel","Panel Distribution Board","Grid outage, site w=
ent down because gen failed to start due to PWC ZTE malfunction // Grid ret=
urn","christelle.ngonga@matech-cameroun.com","310","09-05-2025 17:54:00","M=
ATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004985000","Jou=
vence Mbenda","","09-05-2025 17:41:26","09-05-2025 17:38:19","09-05-2025 18=
:42:19","Grid outage gen failed to start due to automation malfuncttionning=
//Gen manually started","Hyemafo Gildas","Equipment Repair","Passive","Cont=
rol Panel","ATS-AMF Issue","Grid outage gen failed to start due to automati=
on malfuncttionning//Gen manually started","franck.nkomot@matech-cameroun.c=
om","188","09-05-2025 17:41:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004984984","Akono","=
","09-05-2025 17:39:06","29-04-2025 14:34:12","03-05-2025 04:33:58","wrongl=
y logge tickets","Fanda Brice","Incorrectly Logged Tickets","Error","Error"=
,"Error","wrongly logge tickets","christelle.ngonga@matech-cameroun.com","8=
75094","09-05-2025 17:39:06","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004984962","S=
IMBOCK BONAMBAPE","","09-05-2025 17:32:47","09-05-2025 17:25:40","09-05-202=
5 18:34:40","Grid outage , gen started but topped due to disjonction   //  =
 Gen CB rearmed ","Hyemafo Gildas","Equipment Repair","Passive","DCDG Gen",=
"DCDG - Circuit Breaker","Grid outage , gen started but topped due to disjo=
nction   //   Gen CB rearmed ","christelle.ngonga@matech-cameroun.com","428=
","09-05-2025 17:32:47","MATECH CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004984861","EMA=
NA BILICK CITY","","09-05-2025 17:17:16","29-04-2025 16:37:49","29-04-2025 =
16:40:33","Grid outage, Gen stopped by landload for noise disturbance, // G=
rid restoration","Fabrice Pouakam","Access Denial","Access","Access","Acces=
s - Key Lock","Grid outage, Gen stopped by landload for noise disturbance, =
// Grid restoration","christelle.ngonga@matech-cameroun.com","866582","09-0=
5-2025 17:17:16","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004984729","Man=
guiers Dispensaire","","09-05-2025 16:58:31","29-04-2025 03:34:26","29-04-2=
025 03:42:08"," No power issue site on grid with U=3D54,8 V Tx Fme Armand N=
geutsa (691144412) of huawei is informed","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No=
 power issue site on grid with U=3D54,8 V Tx Fme Armand Ngeutsa (691144412)=
 of huawei is informed","alwine.fambou@ihstowers.com","912311","09-05-2025 =
16:58:31","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004984518","Mok=
olo Yaounde","","09-05-2025 16:25:48","09-05-2025 16:24:40","09-05-2025 18:=
16:40","site went down due to insufficient of rectifier on site// site stab=
ilized","","Equipment Repair","Passive","Rectifier","Rectifier Module","sit=
e went down due to insufficient of rectifier on site// site stabilized","fr=
anck.nkomot@matech-cameroun.com","70","09-05-2025 16:25:48","MATECH CMR"
"Closed Complete","Site Down","T3175","IHS_YND_566","NOCINC0004984365","Crf=
 Cornier","","09-05-2025 16:09:04","09-05-2025 16:03:55","09-05-2025 16:39:=
55","Site went down due to Dysjunction of CB in PWC due to increse load // =
CB put back on","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","R=
ectifier Module Overloaded","Site went down due to Dysjunction of CB in PWC=
 due to increse load // CB put back on","franck.nkomot@matech-cameroun.com"=
,"463","09-05-2025 16:09:04","MATECH CMR"
"Closed Complete","Site Down","CTR_431","IHS_YND_321","NOCINC0004984283","S=
oa","","09-05-2025 15:57:27","09-05-2025 15:56:21","09-05-2025 15:57:21","G=
rid outage site went down because Gen failed to start due PWC dysfonction /=
/ Site stabilized","Siligap Boris","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module Overloaded","Grid outage site went down because Gen fail=
ed to start due PWC dysfonction // Site stabilized","christelle.ngonga@mate=
ch-cameroun.com","67","09-05-2025 15:57:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004984239","Saa","",=
"09-05-2025 15:52:00","09-05-2025 15:45:05","09-05-2025 17:36:05","Cascaded=
 Incident from TTO5111478","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because FME Parker was on si=
te with SS IHS FELIX for plan work (Swap of MPR) // End of work","system","=
1224091","09-05-2025 15:52:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004984238","SAA Entr=
ance","","09-05-2025 15:52:00","09-05-2025 15:50:05","09-05-2025 17:07:05",=
"Cascaded Incident from TTO5111478","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because FME Parker =
was on site with SS IHS FELIX for plan work (Swap of MPR) // End of work","=
system","274339","09-05-2025 15:52:00","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004984236","SAA=
 2","IHS_YND_542, IHS_YND_405","09-05-2025 15:51:19","09-05-2025 15:45:05",=
"09-05-2025 17:09:05","Site went down because FME Parker was on site with S=
S IHS FELIX for plan work (Swap of MPR) // End of work","Parker Tchoup","In=
stallation Activity","Passive","Planned Activity","Installation Activity","=
Site went down because FME Parker was on site with SS IHS FELIX for plan wo=
rk (Swap of MPR) // End of work","franck.nkomot@matech-cameroun.com","1651"=
,"09-05-2025 15:51:19","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004984204","B=
arriere","","09-05-2025 15:48:39","09-05-2025 15:39:30","09-05-2025 19:13:3=
0","Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS F=
elix ZAMBE confirmed // Grid stabilised","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen overload (20kva, 400A) SS IHS Felix ZAMBE confirmed // Grid stabilis=
ed","franck.nkomot@matech-cameroun.com","550","09-05-2025 15:48:39","MATECH=
 CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004984097","SOA=
 VILLAGE","","09-05-2025 15:32:41","09-05-2025 15:30:34","09-05-2025 15:40:=
34","Active //No power issue on site ,site on Grid with Ubaie=3D54.6 V The =
Tx FME Synphorien//691316854 from Huawei is informed","Siligap Boris","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active //No power issue on site ,site on Grid with Ubaie=3D54.6 V Th=
e Tx FME Synphorien//691316854 from Huawei is informed","christelle.ngonga@=
matech-cameroun.com","128","09-05-2025 15:32:41","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004984030","Odz=
a petit marche new","","09-05-2025 15:21:15","09-05-2025 15:18:46","09-05-2=
025 17:52:15","Site went down due to insufficient rectifiers on site // Sit=
e stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down due to insufficient rectifiers on site // Si=
te stabilized","franck.nkomot@matech-cameroun.com","150","09-05-2025 15:21:=
15","MATECH CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0004984027","M=
volye-New","","09-05-2025 15:20:07","09-05-2025 15:13:57","09-05-2025 15:27=
:16","Active// No power Issue Site on Grid Ubai =3D52 V, The TX FME Mbah Ho=
siah (674007438) is informed","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site o=
n Grid Ubai =3D52 V, The TX FME Mbah Hosiah (674007438) is informed","chris=
telle.ngonga@matech-cameroun.com","371","09-05-2025 15:20:07","MATECH CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0004983952","A=
v-Germaine","","09-05-2025 15:03:55","09-05-2025 14:27:31","10-05-2025 08:3=
9:24","Grid only site, no space on site to deploy MGE // Grid returned","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid on=
ly site, no space on site to deploy MGE // Grid returned","gaelle.njiofack@=
matech-cameroun.com","2185","09-05-2025 15:03:55","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004983744","M=
arche Odza","","09-05-2025 14:27:16","09-05-2025 14:01:38","09-05-2025 15:0=
2:38","Grid fluctuation,site went down due to poor batterie backup// Grid s=
tabilisation","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid fluctuation,site went down due to poor =
batterie backup// Grid stabilisation","gaelle.njiofack@matech-cameroun.com"=
,"1539","09-05-2025 14:27:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0004983723","Kondengu=
i","","09-05-2025 14:20:41","09-05-2025 13:24:29","09-05-2025 16:54:29","Ca=
scaded Incident from TTO5110854","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, no space to deploy MGE /=
/ grid power return","system","275857","09-05-2025 14:20:41","MATECH CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0004983717","E=
mombo-Tchad","IHS_YND_114","09-05-2025 14:19:48","09-05-2025 13:24:29","09-=
05-2025 16:54:29","Grid outage, no space to deploy MGE // grid power return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage, no space to deploy MGE // grid power return","gaelle.njiofack@ma=
tech-cameroun.com","3320","09-05-2025 14:19:48","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004983671","Tam=
tam Weekend","","09-05-2025 14:07:51","09-05-2025 13:55:36","09-05-2025 14:=
00:41","No power issue site on Grid with U=3D51.5V The TX FME Mbah Hosiah (=
674007438) FROM Huawei is informed and manage","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue site on Grid with U=3D51.5V The TX FME Mbah Hosiah (6740074=
38) FROM Huawei is informed and manage","loic.noumsi@matech-cameroun.com","=
736","09-05-2025 14:07:51","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004983670","Odz=
a petit marche new","","09-05-2025 14:07:27","09-05-2025 13:50:14","09-05-2=
025 15:10:14","Site went down due to insufficient rectifiers on site // Sit=
e stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down due to insufficient rectifiers on site // Si=
te stabilized","olivier.kwedi@ihstowers.com","1034","09-05-2025 14:07:27","=
MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004983512","Imm=
-Olympique","","09-05-2025 13:41:54","09-05-2025 13:34:46","09-05-2025 14:1=
8:29","Site went down due to insufficient rectifiers on site//He reset it(N=
eeded to add 01 or 02 rectifiers )","Paul BIBOUM","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to insufficient rect=
ifiers on site//He reset it(Needed to add 01 or 02 rectifiers )","loic.noum=
si@matech-cameroun.com","429","09-05-2025 13:41:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004983488","MEHANDAN=
","","09-05-2025 13:37:52","09-05-2025 13:31:24","09-05-2025 13:44:26","Cas=
caded Incident from TTO5110559","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // Grid return","system","1217=
656","09-05-2025 13:37:52","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004983480","O=
dza II OCM","IHS_YND_528","09-05-2025 13:36:31","09-05-2025 13:31:24","09-0=
5-2025 13:44:26","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // Grid return","Albran Byorel","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site we=
nt down because gen failed to start due to PWC ZTE malfunction // Grid retu=
rn","gaelle.njiofack@matech-cameroun.com","308","09-05-2025 13:36:31","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004983470","M=
vog-Manga","","09-05-2025 13:35:18","09-05-2025 13:31:04","09-05-2025 13:53=
:52","Grid outage, site went down because gen failed to start due to no aut=
omation // He started gen manually","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","Grid outage, site went down because =
gen failed to start due to no automation // He started gen manually","gaell=
e.njiofack@matech-cameroun.com","256","09-05-2025 13:35:18","MATECH CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0004983453","Av-=
Germaine","","09-05-2025 13:31:26","09-05-2025 13:23:19","09-05-2025 14:16:=
43","Grid only site, no space on site to deploy MDGE // Grid returned","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid onl=
y site, no space on site to deploy MDGE // Grid returned","loic.noumsi@mate=
ch-cameroun.com","488","09-05-2025 13:31:26","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004983379","B=
arriere","","09-05-2025 13:18:51","09-05-2025 13:15:41","09-05-2025 13:17:3=
2","Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS F=
elix ZAMBE confirmed // Grid stabilised","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen overload (20kva, 400A) SS IHS Felix ZAMBE confirmed // Grid stabilis=
ed","gaelle.njiofack@matech-cameroun.com","191","09-05-2025 13:18:51","MATE=
CH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0004983364","Mvo=
g-Ada_OCM","","09-05-2025 13:16:23","09-05-2025 13:10:16","09-05-2025 14:16=
:59","Grid only on site, No space on site to deploy MDGE // Grid returned",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 only on site, No space on site to deploy MDGE // Grid returned","loic.noum=
si@matech-cameroun.com","368","09-05-2025 13:16:23","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004983348","N=
kolfon Cimencam","","09-05-2025 13:11:06","09-05-2025 13:09:01","09-05-2025=
 13:34:48","Grid Outage, site went down due to Poor battery backup // Grid =
return","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid Outage, site went down due to Poor battery b=
ackup // Grid return","gaelle.njiofack@matech-cameroun.com","126","09-05-20=
25 13:11:06","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004983088","Aha=
la Echangeur","","09-05-2025 12:29:49","09-05-2025 12:24:25","09-05-2025 13=
:46:36","Grid outage, site went down due to grid bad voltage (lack of 02 ph=
ases) // he did a bridge on the good phases, site on Gen","MINKA NICOLAS","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id outage, site went down due to grid bad voltage (lack of 02 phases) // he=
 did a bridge on the good phases, site on Gen","loic.noumsi@matech-cameroun=
.com","325","09-05-2025 12:29:49","MATECH CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0004983052","Cam=
p-Sonel","","09-05-2025 12:26:25","09-05-2025 12:06:15","09-05-2025 12:24:1=
7","Grid outage, site went down because gen start and stopped with high tem=
p alarm (unproved) // He reset it and manually start the gen","Siligap Bori=
s","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coola=
nt Level Issue","Grid outage, site went down because gen start and stopped =
with high temp alarm (unproved) // He reset it and manually start the gen",=
"loic.noumsi@matech-cameroun.com","1211","09-05-2025 12:26:25","MATECH CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004982729","Ngu=
ila","","09-05-2025 11:34:05","09-05-2025 11:25:57","09-05-2025 11:30:03","=
No Power issue on site Ubay =3D 49.1V, Tx Fme Gregoire (654547479) from Hua=
wei is informed and confirmed","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No Power issue o=
n site Ubay =3D 49.1V, Tx Fme Gregoire (654547479) from Huawei is informed =
and confirmed","loic.noumsi@matech-cameroun.com","489","09-05-2025 11:34:05=
","MATECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004982703","Emo=
mbo Esssomba","","09-05-2025 11:29:51","09-05-2025 11:24:07","09-05-2025 12=
:39:27","	Grid fluctuation, Site went down because gen fails to start due t=
o grid bad voltage,no RCP// He bypassed the Grid and site on Gen","Mba Laza=
re Herve","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","	Grid fluctuation, Site went down because gen fails to start due t=
o grid bad voltage,no RCP// He bypassed the Grid and site on Gen","loic.nou=
msi@matech-cameroun.com","344","09-05-2025 11:29:51","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004982672","A=
kak-Nkozoa-MTN-IHS","","09-05-2025 11:23:32","09-05-2025 11:16:24","09-05-2=
025 11:44:06","Grid outage, Gen stopped due to Alarm Oil pressure // Gen ca=
rd reset and Gen start manually","Fabrice Pouakam","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage, Gen stopped due to =
Alarm Oil pressure // Gen card reset and Gen start manually","gaelle.njiofa=
ck@matech-cameroun.com","430","09-05-2025 11:23:32","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004982602","N=
koabang Ebolmedjock","","09-05-2025 11:11:47","09-05-2025 11:07:24","09-05-=
2025 11:13:16","Site impacted by Nkolmesseng Abom","Mba Lazare Herve","Cust=
omer Equipment Failure","Active","Active Equipment Failure","Affected by 3r=
d Party Site","Site impacted by Nkolmesseng Abom","gaelle.njiofack@matech-c=
ameroun.com","264","09-05-2025 11:11:47","MATECH CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0004982601","Cam=
p-Sonel","","09-05-2025 11:11:38","09-05-2025 10:37:28","09-05-2025 11:31:4=
9","Grid outage gen failed to start due to automation malfunctionning//Gen =
manually started","Siligap Boris","Equipment Repair","Passive","Control Pan=
el","ATS-AMF Issue","Grid outage gen failed to start due to automation malf=
unctionning//Gen manually started","loic.noumsi@matech-cameroun.com","2051"=
,"09-05-2025 11:11:38","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004982408","L=
abogenie","","09-05-2025 10:35:54","09-05-2025 10:30:47","09-05-2025 10:47:=
35","No power issue U =3D54,5V site on Grid. The Tx FME Eloundou (693212405=
 )from Huawei is informed. Notice that it is the repetitive issue","","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue U =3D54,5V site on Grid. The Tx FME Eloundou (6932124=
05 )from Huawei is informed. Notice that it is the repetitive issue","gaell=
e.njiofack@matech-cameroun.com","308","09-05-2025 10:35:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0004982343","Lobo OCM=
","","09-05-2025 10:21:45","09-05-2025 10:08:51","09-05-2025 11:53:09","Cas=
caded Incident from TTO5109172","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, gen stopped du=
e to alarm ""high temp"" // We added water and gen manually started","syste=
m","273130","09-05-2025 10:21:45","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004982337","NKO=
MEKUI OCM","IHS_YND_341","09-05-2025 10:19:19","09-05-2025 10:08:51","09-05=
-2025 11:53:09","Grid outage, gen stopped due to alarm ""high temp"" // We =
added water and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment=
 Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issu=
e","Grid outage, gen stopped due to alarm ""high temp"" // We added water a=
nd gen manually started","loic.noumsi@matech-cameroun.com","734","09-05-202=
5 10:19:19","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004982286","Nko=
g-Edzen","","09-05-2025 10:10:57","09-05-2025 10:03:49","09-05-2025 10:05:5=
8","Active//No power issue on site, Site on Grid Ubay =3D 52.3V The Tx Fme =
Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site, Site on Grid Ubay =3D 52.3V The Tx Fme Greg=
oire (654547479) from Huawei is informed.","loic.noumsi@matech-cameroun.com=
","429","09-05-2025 10:10:57","MATECH CMR"
"Closed Complete","Site Down","T0470","IHS_YND_022","NOCINC0004982213","Mvo=
g Ada","IHS_YND_004","09-05-2025 10:01:36","09-05-2025 09:54:27","10-05-202=
5 08:34:25","Grid only site, no space to deploy MGE // Grid returned","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only=
 site, no space to deploy MGE // Grid returned","loic.noumsi@matech-camerou=
n.com","429","09-05-2025 10:01:36","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004982210","M=
ambine","","09-05-2025 10:01:02","09-05-2025 09:54:45","09-05-2025 11:46:55=
","Hybrid gen, site gen failed to start due to fuel pipe burst // We replac=
ed fuel pipe and gen manually started","Fanda Brice","Fuel Outage (Probable=
)","Passive","Diesel","Fuel Line Issue","Hybrid gen, site gen failed to sta=
rt due to fuel pipe burst // We replaced fuel pipe and gen manually started=
","gaelle.njiofack@matech-cameroun.com","378","09-05-2025 10:01:02","MATECH=
 CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004982185","Av =
Kennedy","","09-05-2025 09:57:56","09-05-2025 09:54:27","10-05-2025 08:34:2=
5","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Gr=
id only site, no space to deploy MGE // Grid returned","loic.noumsi@matech-=
cameroun.com","353207","09-05-2025 09:57:56","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004982053","Nko=
lbisson usines des eaux 2","","09-05-2025 09:31:23","09-05-2025 09:23:15","=
09-05-2025 11:22:32","Grid outage, Site went down because Gen failed to sta=
rt with ""overcurrent"" alarm // He reseted Gen card and started Gen manual=
ly","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Grid outage, Site went down because Gen failed to start=
 with ""overcurrent"" alarm // He reseted Gen card and started Gen manually=
","loic.noumsi@matech-cameroun.com","489","09-05-2025 09:31:23","MATECH CMR=
"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004982032","Odz=
a petit marche new","","09-05-2025 09:25:49","09-05-2025 09:19:43","09-05-2=
025 12:02:59","Site went down due to insufficient rectifiers on site // he =
reseted it","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to insufficient rectifiers on site // he r=
eseted it","loic.noumsi@matech-cameroun.com","367","09-05-2025 09:25:49","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004981983","S=
AA 2","","09-05-2025 09:16:42","09-05-2025 09:09:30","09-05-2025 09:35:23",=
"No power issue on site Ubay 54.2 V site on Gen, Gregoire / from huawei is =
informed. Site UP wethout intervention","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Nopower=
 issue on site Ubay 54.2 V site on Gen, Gregoire / from huawei is informed"=
,"gaelle.njiofack@matech-cameroun.com","433","09-05-2025 09:16:42","MATECH =
CMR"
"Closed Complete","Site Down","T0539","IHS_YND_034","NOCINC0004981952","EMI=
A MTN","","09-05-2025 09:12:51","09-05-2025 09:09:44","09-05-2025 13:09:13"=
,"Grid only site, no space to deploy MGE // Grid returned","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid only site, no s=
pace to deploy MGE // Grid returned","loic.noumsi@matech-cameroun.com","188=
","09-05-2025 09:12:51","MATECH CMR"
"Cancelled","Warning","CTR_237","IHS_YND_261","NOCINC0004981943","Barriere"=
,"","09-05-2025 09:07:55","","","Grid outage, Site went down because Gen ov=
erload (20kva, 400A) SS IHS Felix ZAMBE confirmed// Site stabilized","Hyema=
fo Gildas","","","","","","gaelle.njiofack@matech-cameroun.com","69","09-05=
-2025 09:07:55","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004981778","C=
RF Nkoabang","","09-05-2025 08:31:16","09-05-2025 08:26:02","09-05-2025 09:=
42:51","Grid-solar site, Grid outage, site down due to sunset  // Grid retu=
rn","Mba Lazare Herve","Equipment Repair","Passive","Solar","Solar Synchron=
ization","Grid-solar site, Grid outage, site down due to sunset  // Grid re=
turn","gaelle.njiofack@matech-cameroun.com","315","09-05-2025 08:31:16","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004981733","M=
arche Odza","","09-05-2025 08:20:16","09-05-2025 08:14:25","09-05-2025 09:0=
9:09","","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Active/ No power issue on site, site on Grid, Ubay 52.9V Lienel =
Adhex / 655184876 from Huawei is informed","gaelle.njiofack@matech-cameroun=
.com","279944","09-05-2025 08:20:16","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004981732","O=
dza","IHS_YND_580","09-05-2025 08:19:38","09-05-2025 08:14:25","09-05-2025 =
11:09:09","Active/ No power issue on site, site on Grid, Ubay 52.9V Lienel =
Adhex / 655184876 from Huawei is informed","Albran Byorel","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve/ No power issue on site, site on Grid, Ubay 52.9V Lienel Adhex / 6551848=
76 from Huawei is informed","gaelle.njiofack@matech-cameroun.com","314","09=
-05-2025 08:19:38","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004981683","S=
calom","","09-05-2025 08:11:33","09-05-2025 08:07:26","09-05-2025 08:14:31"=
,"Grid outage, Gen failed to start due to ATS not functioning // Grid retur=
n","Paul BIBOUM","Equipment Repair","Passive","Control Panel","ATS-AMF Issu=
e","Grid outage, Gen failed to start due to ATS not functioning // Grid ret=
urn","gaelle.njiofack@matech-cameroun.com","248","09-05-2025 08:11:33","MAT=
ECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004981214","Nko=
lbisson usines des eaux 2","","09-05-2025 06:50:28","09-05-2025 06:45:19","=
09-05-2025 08:19:42","Grid outage, Site went down because Gen failed to sta=
rt with ""overcurrent"" alarm // He reseted Gen card and started Gen manual=
ly","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Grid outage, Site went down because Gen failed to start=
 with ""overcurrent"" alarm // He reseted Gen card and started Gen manually=
","cedric.tiani@matech-cameroun.com","310","09-05-2025 06:50:28","MATECH CM=
R"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004981180","N=
kolo II New","","09-05-2025 06:39:54","09-05-2025 06:35:07","09-05-2025 08:=
06:37","Grid fluctuation, site went down because Gen failed to start due to=
 bad voltage// Gen started Mannually","Mba Lazare Herve","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, s=
ite went down because Gen failed to start due to bad voltage// Gen started =
Mannually","vanel.mbiada@matech-cameroun.com","288","09-05-2025 06:39:54","=
MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004981139","S=
IMBOCK BONAMBAPE","","09-05-2025 06:30:13","09-05-2025 06:24:32","09-05-202=
5 07:05:11","Grid outage, site went down due to Grid bad voltage // he did =
a bridge on the good phase","Hyemafo Gildas","Grid Supply","Passive","Grid"=
,"National Grid - Phase Controller Faulty","Grid outage, site went down due=
 to Grid bad voltage // he did a bridge on the good phase","vanel.mbiada@ma=
tech-cameroun.com","342","09-05-2025 06:30:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004981125","Nsimalen=
 OCM","","09-05-2025 06:25:08","09-05-2025 06:17:00","09-05-2025 11:06:55",=
"Cascaded Incident from TTO5107762","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid gen site gen gailedt to start=
 due to gen contactor faulty//We replace gen gen contactor and gen manually=
 started .Power issue resolved but site rains down and power reset has done=
 Lionnel Steeve(655184876) from Huawei is informed","system","287273","09-0=
5-2025 06:25:08","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004981114","N=
kolda","IHS_YND_327","09-05-2025 06:23:41","09-05-2025 06:17:00","09-05-202=
5 11:06:55","Grid gen site gen gailedt to start due to gen contactor faulty=
//We replace gen gen contactor and gen manually started .Power issue resolv=
ed but site rains down and power reset has done Lionnel Steeve(","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid=
 gen site gen gailedt to start due to gen contactor faulty//We replace gen =
gen contactor and gen manually started .Power issue resolved but site rains=
 down and power reset has done Lionnel Steeve(655184876) from Huawei is inf=
ormed","vanel.mbiada@matech-cameroun.com","401","09-05-2025 06:23:41","MATE=
CH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004981093","Mam=
bine","","09-05-2025 06:18:40","09-05-2025 06:10:31","09-05-2025 06:36:19",=
"Grid outage site went down because Gen failed to start due to Hybride syst=
em dysfonction // He reset the hybrid system and Gen manually started","Fan=
da Brice","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid outag=
e site went down because Gen failed to start due to Hybride system dysfonct=
ion // He reset the hybrid system and Gen manually started","cedric.tiani@m=
atech-cameroun.com","490","09-05-2025 06:18:40","MATECH CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0004981028","H=
-Deputes","","09-05-2025 05:58:27","09-05-2025 05:53:17","09-05-2025 12:10:=
22","Grid outage, no space to deploy a mobil Gen //  Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
no space to deploy a mobil Gen //  Grid return","vanel.mbiada@matech-camero=
un.com","311","09-05-2025 05:58:27","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004980952","AKA=
K Nkozoa","","09-05-2025 05:29:12","09-05-2025 04:28:01","09-05-2025 08:46:=
03","Site went down due to insufficient rectifier issue // he reseted it","=
Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient rectifier issue // he reseted it","ce=
dric.tiani@matech-cameroun.com","3672","09-05-2025 05:29:12","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004980885","Sof=
avinc","","09-05-2025 05:03:35","09-05-2025 05:00:13","09-05-2025 06:06:49"=
,"Grid Outage Site went down because Gen Failed due to battery  Gen  faulty=
  //He Manually Started the Gen","MINKA NICOLAS","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Generator Battery","Grid Outage Site went down becaus=
e Gen Failed due to battery  Gen  faulty  //He Manually Started the Gen","c=
edric.tiani@matech-cameroun.com","203","09-05-2025 05:03:35","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004980708","MBA=
LNGONG LYCEE","","09-05-2025 03:41:43","09-05-2025 03:32:59","09-05-2025 06=
:43:38","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, Site went down because Gen stopped due to overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed//Grid return","cedric.tiani@matech-ca=
meroun.com","526","09-05-2025 03:41:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_422","NOCINC0004980489","Botmakak=
","IHS_EDA_101","09-05-2025 02:16:15","09-05-2025 02:04:59","09-05-2025 02:=
10:59","","Kemeni Franklin","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Active// No power issue, Site on Ge=
n Ubai=3D 54V, The Tx Etienne (695033981/Huawei) is informed	","kouoh.jean@=
ihstowers.com","677","09-05-2025 02:16:15","MATECH CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0004980488","Nko=
ngtock","","09-05-2025 02:14:50","09-05-2025 02:11:43","09-05-2025 02:27:16=
","ACTIVE// No power issue on site Ubaie=3D48,9V site on Gen The Tx FME Eti=
enne//695033981 from Huawei is informed","Kemeni Franklin","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTI=
VE// No power issue on site Ubaie=3D48,9V site on Gen The Tx FME Etienne//6=
95033981 from Huawei is informed","cedric.tiani@matech-cameroun.com","188",=
"09-05-2025 02:14:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004980460","Angongo"=
,"","09-05-2025 01:59:18","09-05-2025 01:48:26","09-05-2025 01:50:32","Casc=
aded Incident from TTO5106959","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE / No power issue site on battery with=
 U=3D53 V The Tx FME Etienne (695033981) from Hauawei is informed,","system=
","303201","09-05-2025 01:59:18","MATECH CMR"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0004980457","Ngo=
g Mapubi","","09-05-2025 01:58:19","09-05-2025 01:49:59","09-05-2025 02:03:=
16","Grid outage,site went down because Gen failed to start due to Grid bad=
 voltage,no rcp on site//Grid return","Kemeni Franklin","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","Grid outage,site wen=
t down because Gen failed to start due to Grid bad voltage,no rcp on site//=
Grid return","cedric.tiani@matech-cameroun.com","501","09-05-2025 01:58:19"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004980451","E=
beba","IHS_YND_335","09-05-2025 01:56:45","09-05-2025 01:48:26","09-05-2025=
 01:50:32","ACTIVE / No power issue site on battery with U=3D53 V The Tx FM=
E Etienne (695033981) from Hauawei is informed,","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE / No power issue site on battery with U=3D53 V The Tx FME Etienne (6=
95033981) from Hauawei is informed,","vanel.mbiada@matech-cameroun.com","50=
0","09-05-2025 01:56:45","MATECH CMR"
"Closed Complete","Warning","T0462","IHS_YND_123","NOCINC0004980424","Nkomo=
 II","","09-05-2025 01:48:26","","","Grid outage,Gen failed to start invest=
igation ongoing//Grid return","Albran Byorel","Warning","Warning","POWER","=
Warning - Grid Off","Grid outage,Gen failed to start investigation ongoing/=
/Grid return","cedric.tiani@matech-cameroun.com","2070","09-05-2025 01:48:2=
6","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_332","NOCINC0004980417","NKOMEKUI=
 OCM","","09-05-2025 01:46:00","09-05-2025 01:24:01","09-05-2025 01:57:45",=
"Cascaded Incident from TTO5106902","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue Ubaie=3D 49=
.3 V site on Grid The TX FME Mohamadou 691144435// from huawei is informed.=
","system","268701","09-05-2025 01:46:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004980416","NKONGKAR=
AK","","09-05-2025 01:45:59","09-05-2025 01:24:01","09-05-2025 01:57:45","C=
ascaded Incident from TTO5106902","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue Ubaie=3D 49.3=
 V site on Grid The TX FME Mohamadou 691144435// from huawei is informed.",=
"system","268701","09-05-2025 01:45:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004980406","Sous Pre=
fecture","","09-05-2025 01:42:00","09-05-2025 01:24:01","09-05-2025 01:29:1=
7","ACTIVE//No power issue site on Grid Ubaie =3D52.7 V, The tx Huawei Fulb=
ert (654266068) is informed","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power iss=
ue site on Grid Ubaie =3D52.7 V, The tx Huawei Fulbert (654266068) is infor=
med","system","1079","09-05-2025 01:42:00","MATECH CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0004980401","Mba=
nkomo CAF","","09-05-2025 01:40:24","09-05-2025 01:36:12","09-05-2025 02:44=
:24","No power issue site on Gen with U=3D53v Flubert(654266068) from Huawe=
i is informed","Fanda Brice","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on Gen with U=
=3D53v Flubert(654266068) from Huawei is informed","cedric.tiani@matech-cam=
eroun.com","253","09-05-2025 01:40:24","MATECH CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0004980400","L=
obo OCM","IHS_YND_713, IHS_YND_332","09-05-2025 01:40:21","09-05-2025 01:24=
:01","09-05-2025 01:57:45","No power issue Ubaie=3D 49.3 V site on Grid The=
 TX FME Mohamadou 691144435// from huawei is informed.","TIENTCHEU NZETCHIE=
U GAEL","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue Ubaie=3D 49.3 V site on Grid The TX FME =
Mohamadou 691144435// from huawei is informed.","vanel.mbiada@matech-camero=
un.com","980","09-05-2025 01:40:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004980394","MEHANDAN=
","","09-05-2025 01:36:38","09-05-2025 01:04:29","09-05-2025 02:33:33","Cas=
caded Incident from TTO5106821","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // He reseted controller and g=
en manually started","system","284445","09-05-2025 01:36:38","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004980393","Nko=
lbisson IITA LP","","09-05-2025 01:36:23","09-05-2025 01:29:12","12-05-2025=
 08:44:58","Access issue during the weekend, and Grid outage, no space to d=
eploy a mobil Gen //Grid return","","Access Denial","Lease Or Legal","Landl=
ord Related Issues","Access Issue - Land Lord","Grid outage, no space to de=
ploy a mobil Gen //Grid return","cedric.tiani@matech-cameroun.com","432","0=
9-05-2025 01:36:23","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004980389","Ebo=
go","","09-05-2025 01:34:00","09-05-2025 01:20:53","09-05-2025 02:31:15","N=
o power issue on site Ubaie: 53.2 V site On GRID   The Tx FME JULIEN (69309=
5849) of Huawei is informed","Siligap Boris","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie: 53.2 V site On GRID=20

The Tx FME JULIEN (693095849) of Huawei is informed
","cedric.tiani@matech-cameroun.com","788","09-05-2025 01:34:00","MATECH CM=
R"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004980387","Tam=
tam Weekend","","09-05-2025 01:32:35","09-05-2025 01:14:25","09-05-2025 01:=
54:55","Active: No power issue site on Grid with U=3D52.5V The TX FME Mbah =
Hosiah (674007438) FROM Huawei is informed","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue site on Grid with U=3D52.5V The TX FME Mbah Hosiah (67=
4007438) FROM Huawei is informed","cedric.tiani@matech-cameroun.com","1091"=
,"09-05-2025 01:32:35","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004980383","MEF=
OU ASSI","","09-05-2025 01:31:15","09-05-2025 01:30:20","09-05-2025 02:50:1=
7","Active // No power issue site on grid with Ubaie: 53.4V Flubert(6542660=
68) from Huawei is informed","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power i=
ssue site on grid with Ubaie: 53.4V Flubert(654266068) from Huawei is infor=
med","cedric.tiani@matech-cameroun.com","57","09-05-2025 01:31:15","MATECH =
CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0004980379","AFE=
ME NORD","IHS_YND_808","09-05-2025 01:29:38","09-05-2025 01:06:28","09-05-2=
025 01:59:28","Site Went down due to Grid fluctuation // Grid Stabilized","=
TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","Site Went down due to Grid fluctuation // Grid Sta=
bilized","cedric.tiani@matech-cameroun.com","1391","09-05-2025 01:29:38","M=
ATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0004980377","Mba=
nkolo petit paris","","09-05-2025 01:28:46","09-05-2025 01:06:28","09-05-20=
25 01:59:28","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Site Went down due to Grid fluctuation // Grid Stabili=
zed","cedric.tiani@matech-cameroun.com","298566","09-05-2025 01:28:46","MAT=
ECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0004980371","Clu=
b France","","09-05-2025 01:27:16","09-05-2025 01:23:55","09-05-2025 02:29:=
49","No power issue on site Ubaie: 50.8 V site On GRID   The Tx FME JULIEN =
(693095849) of Huawei is informed","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ub=
aie: 50.8 V site On GRID=20

The Tx FME JULIEN (693095849) of Huawei is informed
","cedric.tiani@matech-cameroun.com","202","09-05-2025 01:27:16","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004980370","Leboudi"=
,"","09-05-2025 01:26:36","09-05-2025 01:08:09","09-05-2025 01:42:21","Casc=
aded Incident from TTO5106828","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
due to grid fluctuations and no automatism on Gen // Grid returned","system=
","291437","09-05-2025 01:26:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0004980360","H-Franco=
 New","","09-05-2025 01:23:48","09-05-2025 01:04:44","09-05-2025 01:24:31",=
"Cascaded Incident from TTO5106801","Delor Telezing","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue, site is on Grid with=
 Ubaie =3D52.6V. The TX brice (650214096) from Huawei is informed.","system=
","269990","09-05-2025 01:23:48","MATECH CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0004980352","M=
adagascar-Yde-New","","09-05-2025 01:22:48","09-05-2025 01:19:36","09-05-20=
25 04:56:39","Active//No power issue on site Ubaie:53.9V; site on Grid. The=
 Tx fme Brice Tsague /650214096) from Huawei is informed","","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue on site Ubaie:53.9V; site on Grid. The Tx fme Brice Ts=
ague /650214096) from Huawei is informed","vanel.mbiada@matech-cameroun.com=
","193","09-05-2025 01:22:48","MATECH CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0004980348","N=
kolbisson usine des eaux","","09-05-2025 01:17:47","09-05-2025 01:12:31","0=
9-05-2025 03:00:07","No power issue site on gen with U=3D54v Mohamadou from=
 Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
site on gen with U=3D54v Mohamadou from Huawei is informed","vanel.mbiada@m=
atech-cameroun.com","317","09-05-2025 01:17:47","MATECH CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0004980343","A=
wae-Yde","","09-05-2025 01:14:47","09-05-2025 01:09:36","09-05-2025 03:03:0=
9","No power issue on site , Ubaie=3D54.4V site On GridThe Tx FME Georges 6=
97461814 from Huawei is informed","Albran Byorel","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site , Ubaie=3D54.4V site On GridThe Tx FME Georges 697461814 from Hua=
wei is informed","vanel.mbiada@matech-cameroun.com","312","09-05-2025 01:14=
:47","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004980339","N=
kolafeme","IHS_YND_309","09-05-2025 01:13:26","09-05-2025 01:08:09","09-05-=
2025 01:42:21","Grid outage, site went down due to grid fluctuations and no=
 automatism on Gen // Grid returned","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went=
 down due to grid fluctuations and no automatism on Gen // Grid returned","=
vanel.mbiada@matech-cameroun.com","317","09-05-2025 01:13:26","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004980336","Sim=
e Building","","09-05-2025 01:12:54","09-05-2025 01:04:38","09-05-2025 03:3=
7:01","ACTIVE// No power issue U=3D54V site on Grid tx fme BRICE Tsague/ 65=
0214096 from huawie is informed.","Mboua Thierry","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No p=
ower issue U=3D54V site on Grid tx fme BRICE Tsague/ 650214096 from huawie =
is informed.","cedric.tiani@matech-cameroun.com","497","09-05-2025 01:12:54=
","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004980333","O=
dza II OCM","IHS_YND_528","09-05-2025 01:11:44","09-05-2025 01:04:29","09-0=
5-2025 02:33:33","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // He reseted controller and gen manually started=
","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e Overloaded","Grid outage, site went down because gen failed to start due =
to PWC ZTE malfunction // He reseted controller and gen manually started","=
vanel.mbiada@matech-cameroun.com","436","09-05-2025 01:11:44","MATECH CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0004980313","D=
joungolo","IHS_YND_711","09-05-2025 01:08:59","09-05-2025 01:04:44","09-05-=
2025 03:34:20","No power issue, site is on Grid with Ubaie =3D52.6V. The TX=
 brice (650214096) from Huawei is informed.","Mboua Thierry","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue, site is on Grid with Ubaie =3D52.6V. The TX brice (650214096)=
 from Huawei is informed.","vanel.mbiada@matech-cameroun.com","256","09-05-=
2025 01:08:59","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004980300","Tsi=
nga village","","09-05-2025 01:02:41","09-05-2025 00:53:59","09-05-2025 03:=
03:13","Active // No power issue UBaie =3D55V site on Grid. The FME TX SYMP=
HORIEN (675295205) From Huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive // No power issue UBaie =3D55V site on Grid. The FME TX SYMPHORIEN (67=
5295205) From Huawei is informed","cedric.tiani@matech-cameroun.com","523",=
"09-05-2025 01:02:41","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0004980296","Ema=
na Lycee","","09-05-2025 01:02:00","09-05-2025 00:52:59","09-05-2025 02:52:=
40","No power issue site on grid with Ubay: 54.4V Symphorien(691316854) fro=
m Huawei is informed.","Fabrice Pouakam","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with Ubay: 54.4V Symphorien(691316854) from Huawei is informed.","ced=
ric.tiani@matech-cameroun.com","542","09-05-2025 01:02:00","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004980294","Nko=
abang Alembe","","09-05-2025 01:00:25","09-05-2025 00:58:14","09-05-2025 03=
:02:41","ACTIVE// No power issue on site Ubaie=3D54.2V site on Gen Lionel A=
djep /655-18-48-76 from Huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE// No power issue on site Ubaie=3D54.2V site on Gen Lionel Adjep /655=
-18-48-76 from Huawei is informed","cedric.tiani@matech-cameroun.com","131"=
,"09-05-2025 01:00:25","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0004980226","O=
kola OCM","","09-05-2025 00:43:59","09-05-2025 00:31:49","09-05-2025 00:49:=
24","Active//No power issue on site site on Gen with Ubaie=3D54,5 V ,,The c=
onf call has been made between The FME TX Mohamadou /691144435/ from Huawei=
 with our FME","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issu=
e on site site on Gen with Ubaie=3D54,5 V ,,The conf call has been made bet=
ween The FME TX Mohamadou /691144435/ from Huawei with our FME","vanel.mbia=
da@matech-cameroun.com","731","09-05-2025 00:43:59","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004980134","O=
LAMA","","09-05-2025 00:09:58","09-05-2025 00:04:45","09-05-2025 00:25:03",=
"Active//No power issue on site Ubaie =3D54.7V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.7V site on Grid The TX FME Henri (69994969=
3) from Huawei is informed","cedric.tiani@matech-cameroun.com","314","09-05=
-2025 00:09:58","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004980052","S=
aa","","08-05-2025 23:45:20","08-05-2025 23:41:52","09-05-2025 00:33:42","G=
rid outage,site went down because Gen started and stopped with Alarm *low o=
il pressure*//He added oil and manually started the Gen","Parker Tchoup","E=
quipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outag=
e,site went down because Gen started and stopped with Alarm *low oil pressu=
re*//He added oil and manually started the Gen","vanel.mbiada@matech-camero=
un.com","209","08-05-2025 23:45:20","MATECH CMR"
"Closed Complete","Site Down","CTR_066","IHS_YND_367","NOCINC0004980028","M=
andoumba OCM","IHS_YND_350, IHS_YND_349","08-05-2025 23:37:32","08-05-2025 =
23:30:59","09-05-2025 00:34:29","Grid fluctuation,site went down because Ge=
n started and stopped due to Grid bad voltage //He bypassed the Grid and si=
te on GEN","Kemeni Franklin","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Grid fluctuation,site went down because Gen sta=
rted and stopped due to Grid bad voltage //He bypassed the Grid and site on=
 GEN","vanel.mbiada@matech-cameroun.com","549","08-05-2025 23:37:32","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0004980025","N=
kongtock","","08-05-2025 23:35:57","08-05-2025 23:30:59","09-05-2025 00:34:=
29","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid fluctuation,site went down because Gen started and stopp=
ed due to Grid bad voltage //He bypassed the Grid and site on GEN","vanel.m=
biada@matech-cameroun.com","268392","08-05-2025 23:35:57","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004980021","M=
ambine","","08-05-2025 23:35:03","08-05-2025 23:30:59","09-05-2025 00:34:29=
","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid fluctuation,site went down because Gen started and stopped due=
 to Grid bad voltage //He bypassed the Grid and site on GEN","vanel.mbiada@=
matech-cameroun.com","268392","08-05-2025 23:35:03","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004979762","D=
amas","","08-05-2025 22:24:54","08-05-2025 22:20:44","09-05-2025 05:55:26",=
"Active// No power Issue Site on Grid Ubai =3D54,1V, The FME The TX FME Mba=
h Hosiah (674007438) is informed.","MINKA NICOLAS","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No =
power Issue Site on Grid Ubai =3D54,1V, The FME The TX FME Mbah Hosiah (674=
007438) is informed.","edwige.kapawo@matech-cameroun.com","251","08-05-2025=
 22:24:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004979728","Angongo"=
,"","08-05-2025 22:18:36","08-05-2025 22:01:19","08-05-2025 23:21:11","Casc=
aded Incident from TTO5106046","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen s=
tart and stopped due to high temp // He added water and manually start the =
gen","system","273607","08-05-2025 22:18:36","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0004979650","Ebe=
ba","IHS_YND_335","08-05-2025 22:03:41","08-05-2025 22:01:19","08-05-2025 2=
3:21:11","Grid outage, site went down because gen start and stopped due to =
high temp // He added water and manually start the gen","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because gen start and stopped due to h=
igh temp // He added water and manually start the gen","gerard.tchangoue@ma=
tech-cameroun.com","143","08-05-2025 22:03:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004979599","Melen Ba=
'aba","","08-05-2025 21:57:36","08-05-2025 19:32:23","08-05-2025 21:34:52",=
"Cascaded Incident from TTO5105918","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went Down due to insufficient=
 rectifiers  // He replaced 01 rectifers, Site on Grid","system","268286","=
08-05-2025 21:57:36","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004979571","N=
kolfoulou","IHS_YND_308","08-05-2025 21:52:44","08-05-2025 19:32:23","08-05=
-2025 21:34:52","Site went Down due to insufficient rectifiers  // He repla=
ced 01 rectifers, Site on Grid","Siligap Boris","Equipment Repair","Passive=
","Rectifier","Rectifier Distribution","Site went Down due to insufficient =
rectifiers  // He replaced 01 rectifers, Site on Grid","edwige.kapawo@matec=
h-cameroun.com","8421","08-05-2025 21:52:44","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004979161","E=
ssomba","","08-05-2025 20:44:37","08-05-2025 20:41:29","08-05-2025 22:34:19=
","Site went down due to 04/05 rectifiers alarming//He reset it and site on=
 Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to 04/05 rectifiers alarming//He reset it an=
d site on Grid","edwige.kapawo@matech-cameroun.com","189","08-05-2025 20:44=
:37","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004979147","N=
goulmekong-Nord","","08-05-2025 20:42:01","08-05-2025 20:37:48","08-05-2025=
 21:06:26","Grid outage, Site went down before Gen started due to poor back=
up // Grid return","Siligap Boris","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
started due to poor backup // Grid return","edwige.kapawo@matech-cameroun.c=
om","254","08-05-2025 20:42:01","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004979083","SAA=
 Entrance","","08-05-2025 20:33:55","08-05-2025 20:25:34","08-05-2025 20:59=
:34","Grid fluctuation, site went down because Gen failed to start due to b=
ad voltage // he bypass the Grid and site on Gen","Parker Tchoup","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, site went down because Gen failed to start due to bad voltage // he=
 bypass the Grid and site on Gen","gerard.tchangoue@matech-cameroun.com","5=
03","08-05-2025 20:33:55","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004978853","N=
kolo II New","","08-05-2025 19:46:07","08-05-2025 19:36:49","08-05-2025 20:=
15:11","No power issue, Site impacted by Mimboman-Don-Bosco","Mba Lazare He=
rve","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","No power issue, Site impacted by Mimboman-Don-Bosc=
o","edwige.kapawo@matech-cameroun.com","559","08-05-2025 19:46:07","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004978810","SOA UNIV=
ERSITY STADIUM","","08-05-2025 19:35:12","08-05-2025 19:27:07","08-05-2025 =
20:18:25","Cascaded Incident from TTO5105060","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage,gen failed t=
o start due to grid bad voltage,no rcp on site//he bypassed grid and starte=
d the gen","system","304885","08-05-2025 19:35:12","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0004978808","S=
oa-Sofamac","IHS_YND_720","08-05-2025 19:34:15","08-05-2025 19:27:07","08-0=
5-2025 20:18:25","Grid outage,gen failed to start due to grid bad voltage,n=
o rcp on site//he bypassed grid and started the gen","Siligap Boris","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid ou=
tage,gen failed to start due to grid bad voltage,no rcp on site//he bypasse=
d grid and started the gen","edwige.kapawo@matech-cameroun.com","428","08-0=
5-2025 19:34:15","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004978390","C=
rf-Nsam","","08-05-2025 18:12:29","08-05-2025 18:10:59","08-05-2025 18:21:5=
0","No power issue on site Ubaie =3D53.6V site on Grid The TX FME Henri (69=
9949693) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site Ubaie =3D53.6V site on Grid The TX FME Henri (699949693) from Hua=
wei is informed","edwige.kapawo@matech-cameroun.com","91","08-05-2025 18:12=
:29","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004978363","S=
atcom","","08-05-2025 18:07:44","08-05-2025 17:58:59","08-05-2025 20:17:01"=
,"No power issue site on Grid with Ubay:31.9V Tx Fme Armand Ngestsa (691144=
412) of huawei is informed","Delor Telezing","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on Grid with Ubay:31.9V Tx Fme Armand Ngestsa (691144412) of huawei is in=
formed","edwige.kapawo@matech-cameroun.com","559","08-05-2025 18:07:44","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0004978360","S=
apeur Mimboman","","08-05-2025 18:06:46","08-05-2025 18:05:59","08-05-2025 =
18:23:21","Grid outage site went down due to gen overload(22 kva,318 A)//We=
 reduce load and gen manually started","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to=
 gen overload(22 kva,318 A)//We reduce load and gen manually started","edwi=
ge.kapawo@matech-cameroun.com","47","08-05-2025 18:06:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004978356","TSINGA V=
ILLAGE 2","","08-05-2025 18:05:57","08-05-2025 15:38:58","08-05-2025 21:34:=
14","Cascaded Incident from TTO5103456","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went Down due to insuffi=
cient rectifiers  // He replaced 01 rectifers, Site on Grid","system","2822=
01","08-05-2025 18:05:57","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004978230","Mom=
","","08-05-2025 17:45:07","08-05-2025 17:40:02","08-05-2025 18:45:36","Gri=
d fluctuations, Site went down before Gen start due to poor battery backup =
// He put site on Gen ","Fanda Brice","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid fluctuations, Site went down be=
fore Gen start due to poor battery backup // He put site on Gen ","gerard.t=
changoue@matech-cameroun.com","307","08-05-2025 17:45:07","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004978116","Nko=
abang2","","08-05-2025 17:31:43","08-05-2025 17:22:33","08-05-2025 19:15:23=
","Grid outage, site went down due to gen overload (22KVA, 330A),// Grid re=
turn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage, site went down due to gen overload (22KVA, 330A),// G=
rid return","gerard.tchangoue@matech-cameroun.com","551","08-05-2025 17:31:=
43","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0004978108","Sac=
re Coeur Catholic Church","","08-05-2025 17:29:18","08-05-2025 17:27:10","0=
8-05-2025 18:35:19","Active//No power issue, site is on Grid with Ubaie 1=
=3D48.2V and Ubaie 2=3D50.9V.. The Tx FME Brice Tsague (650214096) from Hua=
wei is informed.","Mboua Thierry","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, site =
is on Grid with Ubaie 1=3D48.2V and Ubaie 2=3D50.9V.. The Tx FME Brice Tsag=
ue (650214096) from Huawei is informed.","gerard.tchangoue@matech-cameroun.=
com","129","08-05-2025 17:29:18","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004978069","ELO=
UMDEM CARRIERE","","08-05-2025 17:21:49","08-05-2025 17:16:39","08-05-2025 =
17:25:49","No power issue , Site on Grid and Ubaie=3D55V The Tx Fme Fulbert=
 //654266068 from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue , Site on Grid and Ubaie=3D55V The Tx Fme Fulbert //654266068 from Huaw=
ei is informed","gerard.tchangoue@matech-cameroun.com","312","08-05-2025 17=
:21:49","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004977913","Par=
adis Hotel","","08-05-2025 16:54:27","08-05-2025 16:45:15","08-05-2025 18:2=
9:15","Site went down because 02/03 rectifiers dysfuncionned// He reset rec=
tifiers","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down because 02/03 rectifiers dysfuncionned// He reset=
 rectifiers","gerard.tchangoue@matech-cameroun.com","553","08-05-2025 16:54=
:27","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004977907","Elo=
umdem stade","","08-05-2025 16:53:21","08-05-2025 16:44:07","08-05-2025 22:=
23:30","Grid fluctuation, Site went down due to Grid bad voltage and No RCP=
 on site // He bypassed the Grid and Gen manually started","Fanda Brice","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d fluctuation, Site went down due to Grid bad voltage and No RCP on site //=
 He bypassed the Grid and Gen manually started","gerard.tchangoue@matech-ca=
meroun.com","555","08-05-2025 16:53:21","MATECH CMR"
"Closed Complete","Site Down","T1431","IHS_YND_561","NOCINC0004977855","FOU=
GEROLE","","08-05-2025 16:47:06","08-05-2025 16:41:55","08-05-2025 17:08:13=
","site alarming due to grid outage DG stopped due to alarm ""coolant High =
temperature""// He added the water and started GE manually","Siligap Boris"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","site alarming due to grid outage DG stopped due to alarm ""c=
oolant High temperature""// He added the water and started GE manually","ge=
rard.tchangoue@matech-cameroun.com","312","08-05-2025 16:47:06","MATECH CMR=
"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0004977781","S=
oa-II","","08-05-2025 16:31:09","08-05-2025 16:25:02","08-05-2025 17:02:51"=
,"Site went down because the PWC OF ZTE dysfonction // He reset the PWC","S=
iligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module Ov=
erloaded","	Site went down because the PWC OF ZTE dysfonction // He reset t=
he PWC","edwige.kapawo@matech-cameroun.com","367","08-05-2025 16:31:09","MA=
TECH CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0004977715","Tsi=
nga","","08-05-2025 16:21:42","08-05-2025 16:12:59","08-05-2025 16:30:54","=
Active// No power issue on site Ubaie=3D51,5V site on Grid The Tx Eloundou =
Bertrand /693212405/Huawei is informed","Mboua Thierry","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power issue on site Ubaie=3D51,5V site on Grid The Tx Eloundou Bertran=
d /693212405/Huawei is informed","gerard.tchangoue@matech-cameroun.com","52=
4","08-05-2025 16:21:42","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004977641","O=
LAMA","","08-05-2025 16:07:08","08-05-2025 16:01:02","08-05-2025 18:10:50",=
"No power issue on site on Grid Ubaie =3D54.9V, The TX FME Henri (699949693=
) from Huawei is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 on Grid Ubaie =3D54.9V, The TX FME Henri (699949693) from Huawei is inform=
ed","edwige.kapawo@matech-cameroun.com","367","08-05-2025 16:07:08","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0004977568","Nkol-Meb=
anga","","08-05-2025 16:03:15","08-05-2025 15:58:54","08-05-2025 16:00:30",=
"Cascaded Incident from TTO5103575","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active //No power issue on site U=3D5=
3,6V, site on Gen, Gregoire /654547479/ from Huawei is informed","system","=
266508","08-05-2025 16:03:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004977567","Carrefou=
r Ayissi Ele","","08-05-2025 16:03:15","08-05-2025 15:58:54","08-05-2025 16=
:00:30","Cascaded Incident from TTO5103575","Parker Tchoup","Cascade Outage=
","Active","Cascade Active","Cascade Active","Active //No power issue on si=
te U=3D53,6V, site on Gen, Gregoire /654547479/ from Huawei is informed","s=
ystem","266508","08-05-2025 16:03:15","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004977557","Saa=
","IHS_YND_810, IHS_YND_809","08-05-2025 16:02:03","08-05-2025 15:58:54","0=
8-05-2025 16:00:30","Active //No power issue on site U=3D53,6V, site on Gen=
, Gregoire /654547479/ from Huawei is informed","Parker Tchoup","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active //No power issue on site U=3D53,6V, site on Gen, Gregoire /65454747=
9/ from Huawei is informed","gerard.tchangoue@matech-cameroun.com","190","0=
8-05-2025 16:02:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004977525","Akak-Nko=
zoa-MTN-IHS","","08-05-2025 15:57:37","08-05-2025 15:19:44","08-05-2025 15:=
22:27","Cascaded Incident from TTO5103215","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
: 53,4V site on Gen (Hybrid site). Symphorien  (675295205 / Huawei) is info=
rmed. ","system","283351","08-05-2025 15:57:37","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004977511","E=
ssomba","","08-05-2025 15:54:59","08-05-2025 15:47:17","08-05-2025 18:19:49=
","Site went down due to 04/05 rectifiers Alarming on site//He reset it and=
 site on Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","=
Rectifier Distribution","Site went down due to 04/05 rectifiers Alarming on=
 site//He reset it and site on Gen","edwige.kapawo@matech-cameroun.com","46=
4","08-05-2025 15:54:59","MATECH CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004977508","Nko=
lafeme","","08-05-2025 15:54:29","08-05-2025 15:48:17","08-05-2025 17:22:45=
","Grid outage,site went due to PWC ZTE dysfunction and no automatism on si=
te//He bypassed it and site on Gen","TIENTCHEU NZETCHIEU GAEL","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage,sit=
e went due to PWC ZTE dysfunction and no automatism on site//He bypassed it=
 and site on Gen","gerard.tchangoue@matech-cameroun.com","373","08-05-2025 =
15:54:29","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004977483","Elo=
umdem stade","","08-05-2025 15:48:39","08-05-2025 15:39:59","08-05-2025 15:=
48:19","Grid outage, Site went down before Gen start due to poor backup// G=
en Automatically Started","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen Automatically Started","gerard.tchangou=
e@matech-cameroun.com","521","08-05-2025 15:48:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004977471","Nkolfoul=
ou 2","","08-05-2025 15:46:19","08-05-2025 15:38:58","08-05-2025 21:34:14",=
"Cascaded Incident from TTO5103456","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went Down due to insufficient=
 rectifiers  // He replaced 01 rectifers, Site on Grid","system","282202","=
08-05-2025 15:46:19","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004977455","N=
kolfoulou","IHS_YND_278, IHS_YND_719","08-05-2025 15:42:25","08-05-2025 15:=
38:58","08-05-2025 17:20:14","Site went Down due to insufficient rectifiers=
  // site Stabilized","Siligap Boris","Equipment Repair","Passive","Rectifi=
er","Rectifier Distribution","Site went Down due to insufficient rectifiers=
  // site Stabilized","edwige.kapawo@matech-cameroun.com","208","08-05-2025=
 15:42:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004977453","Melen Ba=
'aba","","08-05-2025 15:42:09","08-05-2025 14:23:23","08-05-2025 14:27:42",=
"Cascaded Incident from TTO5102830","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 DG start : Poor Batteries backup// Grid return","system","265015","08-05-2=
025 15:42:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004977454","TSINGA V=
ILLAGE 2","","08-05-2025 15:42:09","08-05-2025 14:23:23","08-05-2025 14:27:=
42","Cascaded Incident from TTO5102830","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
efore DG start : Poor Batteries backup// Grid return","system","265014","08=
-05-2025 15:42:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004977452","Nkolfoul=
ou 2","","08-05-2025 15:42:08","08-05-2025 14:23:23","08-05-2025 14:27:42",=
"Cascaded Incident from TTO5102830","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 DG start : Poor Batteries backup// Grid return","system","265015","08-05-2=
025 15:42:08","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004977398","N=
kolfon Cimencam","","08-05-2025 15:34:50","08-05-2025 15:24:59","08-05-2025=
 15:48:38","Site impacted by Afanoya_II","Hyemafo Gildas","Customer Equipme=
nt Failure","Active","Active Equipment Failure","Affected by 3rd Party Site=
","Site impacted by Afanoya_II","edwige.kapawo@matech-cameroun.com","592","=
08-05-2025 15:34:50","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004977328","H=
-Paradis","","08-05-2025 15:33:31","08-05-2025 15:25:25","08-05-2025 15:45:=
49","Grid Outage, No space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No space =
to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","487","08=
-05-2025 15:33:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_317","NOCINC0004977127","Soa-Sofa=
mac","","08-05-2025 15:01:33","08-05-2025 14:57:20","08-05-2025 15:43:55","=
Grid outage, site went down because gen start and stopped with over voltage=
 alarm // He reset it and manually start the gen","Siligap Boris","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site we=
nt down because gen start and stopped with over voltage alarm // He reset i=
t and manually start the gen","system","253","08-05-2025 15:01:33","MATECH =
CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004977123","S=
OA UNIVERSITY STADIUM","","08-05-2025 15:00:47","08-05-2025 14:57:20","08-0=
5-2025 15:45:46","Site went down because the PWC OF ZTE dysfonction // He r=
eset the PWC","Siligap Boris","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Site went down because the PWC OF ZTE dysfonctio=
n // He reset the PWC","edwige.kapawo@matech-cameroun.com","208","08-05-202=
5 15:00:47","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004977118","Mom=
","","08-05-2025 15:00:15","08-05-2025 14:54:59","08-05-2025 15:26:49","Gri=
d outage, Site went down before Gen start due to poor battery backup // Gen=
 manually started","Fanda Brice","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor battery backup // Gen manually started","gerard.tchangoue@m=
atech-cameroun.com","317","08-05-2025 15:00:15","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004976986","Tam=
tam Weekend","","08-05-2025 14:35:21","08-05-2025 14:27:11","08-05-2025 14:=
43:52","No power Issue Site on Grid Ubai =3D50.8 V. The TX FME Mbah Hosiah =
(674007438) is informed","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power Issue Site o=
n Grid Ubai =3D50.8 V. The TX FME Mbah Hosiah (674007438) is informed","edw=
ige.kapawo@matech-cameroun.com","490","08-05-2025 14:35:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0004976975","Elig-Edz=
oa","","08-05-2025 14:34:01","08-05-2025 14:31:07","08-05-2025 17:00:28","C=
ascaded Incident from TTO5102856","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","site went down due to PWC Overload(12Kw 250A) Bla=
ise Raoul SS IHS is iformed //Site stabilised","system","293385","08-05-202=
5 14:34:01","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0004976950","N=
taba","IHS_YND_133","08-05-2025 14:33:14","08-05-2025 14:31:07","08-05-2025=
 17:05:56","site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS I=
HS is iformed //Site stabilised","Delor Telezing","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","site went down due to PWC Ov=
erload(12Kw 250A) Blaise Raoul SS IHS is iformed //Site stabilised","edwige=
.kapawo@matech-cameroun.com","128","08-05-2025 14:33:14","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004976947","Nko=
abang Alembe","","08-05-2025 14:32:22","08-05-2025 14:29:12","08-05-2025 14=
:43:18","No power issue, Site impacted by Ayongoum","Mba Lazare Herve","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","Affected by 3=
rd Party Site","No power issue, Site impacted by Ayongoum","franck.nkomot@m=
atech-cameroun.com","191","08-05-2025 14:32:22","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004976927","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","08-05-2025 14:28:30","0=
8-05-2025 14:23:23","08-05-2025 14:29:08","Grid outage, site went down befo=
re DG start : Poor Batteries backup// Grid return","Siligap Boris","Equipme=
nt Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid ou=
tage, site went down before DG start : Poor Batteries backup// Grid return"=
,"franck.nkomot@matech-cameroun.com","308","08-05-2025 14:28:30","MATECH CM=
R"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004976885","Nko=
lbisson IITA LP","","08-05-2025 14:22:12","08-05-2025 14:20:59","08-05-2025=
 14:22:59","Grid Only, No space to deploy // Grid restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Over Voltage","Grid Only, No space=
 to deploy // Grid restored","franck.nkomot@matech-cameroun.com","74","08-0=
5-2025 14:22:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004976878","Nsimalen=
 OCM","","08-05-2025 14:21:06","08-05-2025 14:17:59","08-05-2025 18:12:26",=
"Cascaded Incident from TTO5102766","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen started=
 and stopped due AVR faulty // He replaced AVR ","system","280070","08-05-2=
025 14:21:06","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004976869","N=
kolda","IHS_YND_327","08-05-2025 14:19:50","08-05-2025 14:17:59","08-05-202=
5 18:47:26","Site went down because Gen started and stopped due AVR faulty =
// He replaced AVR ","Albran Byorel","Equipment Repair","Passive","ACDG Gen=
","ACDG - AVR","Site went down because Gen started and stopped due AVR faul=
ty // He replaced AVR ","franck.nkomot@matech-cameroun.com","112","08-05-20=
25 14:19:50","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004976730","B=
arriere","","08-05-2025 13:57:48","08-05-2025 13:49:36","08-05-2025 14:43:4=
7","Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS F=
elix ZAMBE confirmed// site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (20kva, 400A) SS IHS Felix ZAMBE confirmed// site stabilised=
","franck.nkomot@matech-cameroun.com","493","08-05-2025 13:57:48","MATECH C=
MR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004976682","Nta=
ba","","08-05-2025 13:51:54","08-05-2025 13:44:47","08-05-2025 14:02:47","S=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Site went down due to PWC Overload(12Kw 250A) Blaise R=
aoul SS IHS is iformed //Site stabilised","franck.nkomot@matech-cameroun.co=
m","428","08-05-2025 13:51:54","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004976628","Nko=
lbisson IITA LP","","08-05-2025 13:42:40","08-05-2025 13:37:46","08-05-2025=
 14:01:46","Grid Only, No space to deploy // Grid restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space=
 to deploy // Grid restored","franck.nkomot@matech-cameroun.com","295","08-=
05-2025 13:42:40","MATECH CMR"
"Closed Complete","Warning","T0322","IHS_YND_312","NOCINC0004976626","Nkoln=
da","","08-05-2025 13:42:29","","","Site went down due to CB(125A) which po=
wered MTN equiments disjuncted//We rearmed CB","Albran Byorel","Warning","W=
arning","POWER","Warning - Rectifier - Circuit Breaker","Site went down due=
 to CB(125A) which powered MTN equiments disjuncted//We rearmed CB","moulio=
m.anselme@matech-cameroun.com","33","08-05-2025 13:42:29","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004976611","M=
vog-Manga","","08-05-2025 13:39:23","08-05-2025 13:21:41","08-05-2025 14:41=
:21","Grid outage,Site went down because Gen failed to start due to Grid co=
ntactor not excited // He excited the Grid contactor and site on Grid Power=
 issue resolved  but remains down at OCM LIONEL ","Albran Byorel","Equipmen=
t Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,Site went =
down because Gen failed to start due to Grid contactor not excited // He ex=
cited the Grid contactor and site on Grid Power issue resolved  but remains=
 down at OCM LIONEL","franck.nkomot@matech-cameroun.com","1064","08-05-2025=
 13:39:23","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0004976511","C=
rf Cornier","","08-05-2025 13:21:09","08-05-2025 01:10:14","08-05-2025 02:0=
1:14","Active, No power issue site on battery with U=3D54.6VTX FME Armand N=
gestsa (691144412) From huawei is informed","MINKA NICOLAS","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive, No power issue site on battery with U=3D54.6VTX FME Armand Ngestsa (69=
1144412) From huawei is informed","franck.nkomot@matech-cameroun.com","4385=
6","08-05-2025 13:21:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004976416","Omnispor=
t-Rail","","08-05-2025 13:08:54","08-05-2025 13:05:06","08-05-2025 15:04:49=
","Cascaded Incident from TTO5102238","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) SS IHS Bernard ATANGANA is informed and conf=
irmed// grid restoration","system","298735","08-05-2025 13:08:54","MATECH C=
MR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004976415","M=
ANGUIERS CHAPELLE","IHS_YND_506","08-05-2025 13:08:16","08-05-2025 13:05:06=
","08-05-2025 15:04:49","Grid outage, site went down due to gen overload (2=
2kva, 340A) SS IHS Bernard ATANGANA is informed and confirmed// grid restor=
ation","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage, site went down due to gen overload (22kva, 340A) SS I=
HS Bernard ATANGANA is informed and confirmed// grid restoration","franck.n=
komot@matech-cameroun.com","191","08-05-2025 13:08:16","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004976253","M=
ANGUIERS CHAPELLE","IHS_YND_506","08-05-2025 12:53:32","08-05-2025 12:50:27=
","08-05-2025 13:01:27","Grid outage, site went down due to gen overload (2=
2kva, 340A) SS IHS Bernard ATANGANA is informed and confirmed// grid restor=
ation","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage, site went down due to gen overload (22kva, 340A) SS I=
HS Bernard ATANGANA is informed and confirmed// grid restoration","franck.n=
komot@matech-cameroun.com","187","08-05-2025 12:53:32","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004976211","H=
-Paradis","","08-05-2025 12:49:24","08-05-2025 12:48:15","08-05-2025 13:02:=
15","Grid outage//Grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage//Grid return","franck.nkomot@matech-=
cameroun.com","70","08-05-2025 12:49:24","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004976165","O=
mnisport-Rail","","08-05-2025 12:41:46","08-05-2025 12:50:27","08-05-2025 1=
3:01:27","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, site went down due to gen overload (22kva, 3=
40A) SS IHS Bernard ATANGANA is informed and confirmed// grid restoration",=
"franck.nkomot@matech-cameroun.com","263617","08-05-2025 12:41:46","MATECH =
CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004976141","An-=
Marche-Melen","","08-05-2025 12:38:31","08-05-2025 12:33:49","08-05-2025 12=
:51:49","Grid outage, No space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No sp=
ace to deploy MDG // Grid return","franck.nkomot@matech-cameroun.com","3328=
","08-05-2025 12:38:31","MATECH CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0004976097","N=
R-Omnisport","","08-05-2025 12:28:53","08-05-2025 12:21:28","08-05-2025 13:=
04:28","Site went down due to disjunction of Cb(80A*80A) in PWC that trippe=
d OCM// He reamed Cb(80A*80A), site on grid","Delor Telezing","Equipment Re=
pair","Passive","Rectifier","Rectifier - Circuit Breaker","Site went down d=
ue to disjunction of Cb(80A*80A) in PWC that tripped OCM// He reamed Cb(80A=
*80A), site on grid","franck.nkomot@matech-cameroun.com","446","08-05-2025 =
12:28:53","MATECH CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0004976054","Sap=
eur Mimboman","","08-05-2025 12:19:05","08-05-2025 12:09:54","08-05-2025 13=
:34:54","Grid outage site went down due to gen overload(22 kva,318 A)//We r=
educe load and gen manually started","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to g=
en overload(22 kva,318 A)//We reduce load and gen manually started","franck=
.nkomot@matech-cameroun.com","1042","08-05-2025 12:19:05","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004975804","Mok=
olo Yaounde","","08-05-2025 11:50:07","08-05-2025 11:49:52","08-05-2025 12:=
54:52","site went down due to insufficient of rectifier on site// site stab=
ilized","","Equipment Repair","Passive","Rectifier","Rectifier Module","sit=
e went down due to insufficient of rectifier on site// site stabilized","fr=
anck.nkomot@matech-cameroun.com","16","08-05-2025 11:50:07","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004975640","N=
koabang Ebolmedjock","","08-05-2025 11:25:12","08-05-2025 11:19:04","08-05-=
2025 11:25:04","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","franck.nkomot@mate=
ch-cameroun.com","369","08-05-2025 11:25:12","MATECH CMR"
"Closed Complete","Site Down","CTR_447","IHS_YND_061","NOCINC0004975521","Y=
de University","","08-05-2025 11:09:34","08-05-2025 11:01:24","08-05-2025 1=
3:51:24","No power issue site on grid wity U=3D54v Notice that we have disj=
unction at OCM equipements Mbah Osiah from Huawei is informed","Paul BIBOUM=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue site on grid wity U=3D54v Notice that we have =
disjunction at OCM equipements Mbah Osiah from Huawei is informed","franck.=
nkomot@matech-cameroun.com","491","08-05-2025 11:09:34","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004975517","Fla=
menco","","08-05-2025 11:08:14","08-05-2025 11:01:07","08-05-2025 11:19:07"=
,"Grid outage gen failed to start due to card GE dysfunctioned // Grid retu=
rned","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Grid outage gen failed to start due to card GE dysfunctioned // =
Grid returned","franck.nkomot@matech-cameroun.com","428","08-05-2025 11:08:=
14","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004975473","Nta=
ba","","08-05-2025 11:01:46","08-05-2025 10:59:37","08-05-2025 11:17:37","S=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Site went down due to PWC Overload(12Kw 250A) Blaise R=
aoul SS IHS is iformed //Site stabilised","franck.nkomot@matech-cameroun.co=
m","130","08-05-2025 11:01:46","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004975471","Efo=
ulan MTN","","08-05-2025 11:01:13","08-05-2025 10:59:04","08-05-2025 11:29:=
00","Grid outage .gen failed to start due to alarm ""high temp""//We add wa=
ter and gen manually started ","MINKA NICOLAS","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage .g=
en failed to start due to alarm ""high temp""//We add water and gen manuall=
y started ","franck.nkomot@matech-cameroun.com","129","08-05-2025 11:01:13"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004975364","Bondjock=
","","08-05-2025 10:47:34","08-05-2025 10:27:28","08-05-2025 11:28:55","Cas=
caded Incident from TTO5100931","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage.gen failed to start due to p=
oor backup//Gen manually started ","system","1206","08-05-2025 10:47:34","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004975362","Mbeng","=
","08-05-2025 10:47:33","08-05-2025 10:27:28","08-05-2025 11:28:55","Cascad=
ed Incident from TTO5100931","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen failed to start due to poor=
 backup//Gen manually started ","system","1205","08-05-2025 10:47:33","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004975363","Minka","=
","08-05-2025 10:47:33","08-05-2025 10:27:28","08-05-2025 11:28:55","Cascad=
ed Incident from TTO5100931","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen failed to start due to poor=
 backup//Gen manually started ","system","1205","08-05-2025 10:47:33","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004975356","Scalom-I=
HS","","08-05-2025 10:46:36","08-05-2025 10:31:26","08-05-2025 10:59:23","C=
ascaded Incident from TTO5100902","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage gen failed to start due to automation=
 malfunctionning//Gen manually started ","system","1214314","08-05-2025 10:=
46:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0004975342","Montee-J=
ouvence-II","","08-05-2025 10:44:29","08-05-2025 10:39:25","08-05-2025 11:2=
3:25","Cascaded Incident from TTO5100974","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to work =
done by FME Matech FONGANG Gildas and IHS SS Felix Zambe(checking ATS)//End=
 of work","system","1213584","08-05-2025 10:44:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004975340","Accacia =
New","","08-05-2025 10:44:29","08-05-2025 10:39:25","08-05-2025 11:23:25","=
Cascaded Incident from TTO5100974","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Site went down due to work done by FME Matech FO=
NGANG Gildas and IHS SS Felix Zambe(checking ATS)//End of work","system","1=
213586","08-05-2025 10:44:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0004975341","Damas","=
","08-05-2025 10:44:29","08-05-2025 10:39:25","08-05-2025 11:23:25","Cascad=
ed Incident from TTO5100974","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to work done by FME Ma=
tech FONGANG Gildas and IHS SS Felix Zambe(checking ATS)//End of work","sys=
tem","1213585","08-05-2025 10:44:29","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004975321","T=
amtam Weekend","IHS_YND_562, IHS_YND_166, IHS_YND_518","08-05-2025 10:42:29=
","08-05-2025 10:39:25","08-05-2025 11:29:25","Site went down due to work d=
one by FME Matech FONGANG Gildas and IHS SS Felix Zambe(checking ATS)//End =
of work","Hyemafo Gildas","Installation Activity","Passive","Planned Activi=
ty","Installation Activity","Site went down due to work done by FME Matech =
FONGANG Gildas and IHS SS Felix Zambe(checking ATS)//End of work","franck.n=
komot@matech-cameroun.com","185","08-05-2025 10:42:29","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0004975303","GSO=
","","08-05-2025 10:39:59","08-05-2025 10:23:49","08-05-2025 10:25:06","No =
power issue site on grid wit U=3D54.36v Lionnel Steeve from Huawei is infor=
med","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue site on grid wit U=3D54.36v=
 Lionnel Steeve from Huawei is informed","franck.nkomot@matech-cameroun.com=
","971","08-05-2025 10:39:59","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004975282","B=
ATA Mokolo OCM","","08-05-2025 10:35:31","08-05-2025 10:31:24","08-05-2025 =
12:31:24","Grid outage.no space to deploy mobile gen//Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.=
no space to deploy mobile gen//Grid return","franck.nkomot@matech-cameroun.=
com","248","08-05-2025 10:35:31","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004975274","Mom=
","IHS_YND_369, IHS_YND_371, IHS_YND_553, IHS_YND_372","08-05-2025 10:34:33=
","08-05-2025 10:27:28","08-05-2025 11:28:55","Grid outage.gen failed to st=
art due to poor backup//Gen manually started ","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage.g=
en failed to start due to poor backup//Gen manually started ","franck.nkomo=
t@matech-cameroun.com","622","08-05-2025 10:34:33","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004975270","S=
calom","IHS_YND_505","08-05-2025 10:32:32","08-05-2025 10:30:26","08-05-202=
5 11:00:56","Grid outage gen failed to start due to automation malfunctionn=
ing//Gen manually started ","Paul BIBOUM","Equipment Repair","Passive","Con=
trol Panel","ATS-AMF Issue","Grid outage gen failed to start due to automat=
ion malfunctionning//Gen manually started ","franck.nkomot@matech-cameroun.=
com","155","08-05-2025 10:32:32","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004975244","M=
essassi 2","","08-05-2025 10:26:07","08-05-2025 10:19:00","08-05-2025 12:44=
:00","Site went down because 04/06 rectifiers dysfuncionned// He reset rect=
ifiers, site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down because 04/06 rectifiers dysfuncion=
ned// He reset rectifiers, site on Gen","franck.nkomot@matech-cameroun.com"=
,"428","08-05-2025 10:26:07","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004975080","Nta=
ba","","08-05-2025 09:56:00","08-05-2025 09:39:07","08-05-2025 09:57:07","s=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","site went down due to PWC Overload(12Kw 250A) Blaise R=
aoul SS IHS is iformed //Site stabilised","stephane.nkamwa@ihstowers.com","=
1014","08-05-2025 09:56:00","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004974833","K=
oweit City","","08-05-2025 09:16:37","08-05-2025 08:48:27","08-05-2025 10:1=
9:04","No power issue site on grid with U=3D56.2V Lionnel Steeve from Huawe=
i is informed","Albran Byorel","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with=
 U=3D56.2V Lionnel Steeve from Huawei is informed","franck.nkomot@matech-ca=
meroun.com","1691","08-05-2025 09:16:37","MATECH CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0004974657","E=
ntree Cite Verte","","08-05-2025 08:55:02","08-05-2025 08:47:55","08-05-202=
5 10:18:55","No power issue site on grid with U=3D52.2v Mohamadou from Huaw=
ei is informed site up at 08:48 AM","Paul BIBOUM","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e site on grid with U=3D52.2v Mohamadou from Huawei is informed site up at =
08:48 AM","franck.nkomot@matech-cameroun.com","428","08-05-2025 08:55:02","=
MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004974643","M=
arche Odza","","08-05-2025 08:50:51","08-05-2025 08:48:37","08-05-2025 08:5=
1:37","Grid fluctuation,site went down due to rectifiers dysfunction// Grid=
 stabilisation","Albran Byorel","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Grid fluctuation,site went down due to rectifiers dysfunc=
tion// Grid stabilisation","franck.nkomot@matech-cameroun.com","135","08-05=
-2025 08:50:51","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004974634","B=
arriere","","08-05-2025 08:49:38","08-05-2025 08:46:27","08-05-2025 13:01:2=
7","Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS F=
elix ZAMBE confirmed// site stabilised","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload (20kva, 400A) SS IHS Felix ZAMBE confirmed// site stabilised=
","franck.nkomot@matech-cameroun.com","192","08-05-2025 08:49:38","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0004974454","Montee-J=
ouvence-II","","08-05-2025 08:18:02","08-05-2025 08:06:17","08-05-2025 09:3=
0:54","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Site went down due to work done by FME Matech FONGANG Gildas=
 and IHS SS Felix Zambe(checking ATS)//End of work","system","273344","08-0=
5-2025 08:18:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0004974452","Damas","=
","08-05-2025 08:18:01","08-05-2025 08:06:17","08-05-2025 09:30:54","","MIN=
KA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Site went down due to work done by FME Matech FONGANG Gildas and IHS SS Fe=
lix Zambe(checking ATS)//End of work","system","273343","08-05-2025 08:18:0=
1","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0004974453","Tamtam W=
eekend","IHS_YND_562, IHS_YND_166, IHS_YND_518","08-05-2025 08:18:01","08-0=
5-2025 08:06:17","08-05-2025 09:30:54","Site went down due to work done by =
FME Matech FONGANG Gildas and IHS SS Felix Zambe(checking ATS)//End of work=
","Hyemafo Gildas","Installation Activity","Passive","Planned Activity","In=
stallation Activity","Site went down due to work done by FME Matech FONGANG=
 Gildas and IHS SS Felix Zambe(checking ATS)//End of work","system","704","=
08-05-2025 08:18:01","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004974446","A=
ccacia New","","08-05-2025 08:16:26","08-05-2025 08:06:17","08-05-2025 09:3=
0:54","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Site went down due to work done by FME Matech FONGANG Gildas and IHS SS Fe=
lix Zambe(checking ATS)//End of work","franck.nkomot@matech-cameroun.com","=
273344","08-05-2025 08:16:26","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004974026","H=
-Paradis","","08-05-2025 06:48:42","08-05-2025 06:46:28","08-05-2025 06:49:=
39","Grid outage//Grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage//Grid return","vanel.mbiada@matech-c=
ameroun.com","135","08-05-2025 06:48:42","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004972885","N=
koabang Ebolmedjock","","08-05-2025 01:22:09","08-05-2025 01:17:57","08-05-=
2025 01:36:09","	Active//No power issue, Site on Gen. Notice that it is imp=
acted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","Affected b=
y 3rd Party Site","	Active//No power issue, Site on Gen. Notice that it is =
impacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@mat=
ech-cameroun.com","253","08-05-2025 01:22:09","MATECH CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0004972745","B=
ATA-Mokolo","","08-05-2025 00:40:24","08-05-2025 00:37:11","08-05-2025 00:4=
9:02","Active, no power issue, site on grid with U=3D55,9V; Tx FME Brice/65=
0214096/ From huawei is informed","","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issue, si=
te on grid with U=3D55,9V; Tx FME Brice/650214096/ From huawei is informed"=
,"vanel.mbiada@matech-cameroun.com","195","08-05-2025 00:40:24","MATECH CMR=
"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004972705","E=
ssomba","","08-05-2025 00:31:34","08-05-2025 00:27:19","08-05-2025 01:51:20=
","Site went down due to 03/05 rectifiers Alarming  on site//He reset it an=
d site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to 03/05 rectifiers Alarming  on si=
te//He reset it and site on Grid","vanel.mbiada@matech-cameroun.com","257",=
"08-05-2025 00:31:34","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004972686","N=
kolfon Cimencam","","08-05-2025 00:24:16","08-05-2025 00:17:03","08-05-2025=
 00:30:59","Active//No power issue on site U=3D54,5v site on Gen The TX fme=
 George(697461814) from huawei is informed. Noticed that site is impacted b=
y Afanoya II(Not manage by HIS)","Hyemafo Gildas","Customer Equipment Failu=
re","Active","Active Equipment Failure","Affected by 3rd Party Site","Activ=
e//No power issue on site U=3D54,5v site on Gen The TX fme George(697461814=
) from huawei is informed. Noticed that site is impacted by Afanoya II(Not =
manage by HIS)","vanel.mbiada@matech-cameroun.com","434","08-05-2025 00:24:=
16","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0004972594","C=
rf Cornier","","07-05-2025 23:45:56","07-05-2025 23:43:20","08-05-2025 01:0=
4:05","Active, No power issue site on battery with U=3D54.6VTX FME Armand N=
gestsa (691144412)From huawei is informed","MINKA NICOLAS","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve, No power issue site on battery with U=3D54.6VTX FME Armand Ngestsa (691=
144412)From huawei is informed","vanel.mbiada@matech-cameroun.com","157","0=
7-05-2025 23:45:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004972583","Nsimalen=
 OCM","","07-05-2025 23:43:03","07-05-2025 23:10:59","07-05-2025 23:39:44",=
"Cascaded Incident from TTO5097657","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site on gen due to grid outage, si=
te went down due to Gen contacteur faulty // He bypassed the gen contactor =
site on gen","system","269518","07-05-2025 23:43:03","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004972577","B=
arriere","","07-05-2025 23:40:49","07-05-2025 22:06:29","08-05-2025 08:08:2=
9","Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS F=
elix ZAMBE confirmed// site stabilised ","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen overload (20kva, 400A) SS IHS Felix ZAMBE confirmed// site stabilise=
d ","vanel.mbiada@matech-cameroun.com","5661","07-05-2025 23:40:49","MATECH=
 CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004972476","Mes=
sassi 2","","07-05-2025 23:21:49","07-05-2025 23:16:38","08-05-2025 01:04:3=
3","Site went down because 04/06 rectifiers dysfuncionned// He reset rectif=
iers, site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down because 04/06 rectifiers dysfuncionne=
d// He reset rectifiers, site on Gen","cedric.tiani@matech-cameroun.com","3=
13","07-05-2025 23:21:49","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004972459","N=
kolda","IHS_YND_327","07-05-2025 23:20:06","07-05-2025 23:10:59","07-05-202=
5 23:39:44","Site on gen due to grid outage, site went down due to Gen cont=
acteur faulty // He bypassed the gen contactor site on gen","Albran Byorel"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Site on g=
en due to grid outage, site went down due to Gen contacteur faulty // He by=
passed the gen contactor site on gen","cedric.tiani@matech-cameroun.com","5=
48","07-05-2025 23:20:06","MATECH CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0004972361","E=
ntree Cite Verte","","07-05-2025 23:01:24","07-05-2025 22:28:09","07-05-202=
5 23:58:31","Active//No power issue, site is on Grid with Ubaie=3D53,4V,Bri=
se Tsague(650214096) from Huawei is informed","Paul BIBOUM","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue, site is on Grid with Ubaie=3D53,4V,Brise Tsague(650214=
096) from Huawei is informed","vanel.mbiada@matech-cameroun.com","1996","07=
-05-2025 23:01:24","MATECH CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0004972358","T=
SINGA VILLAGE 2","","07-05-2025 22:59:22","07-05-2025 22:40:02","07-05-2025=
 23:09:52","Active//No power issue on site, Site on Battery UBAIE=3D54.5V (=
start threshold=3D 47.5V) synphorien (675295205) From huawei is informed","=
Delor Telezing","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active//No power issue on site, Site on Battery=
 UBAIE=3D54.5V (start threshold=3D 47.5V) synphorien (675295205) From huawe=
i is informed","vanel.mbiada@matech-cameroun.com","1161","07-05-2025 22:59:=
22","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004972087","Ole=
mbe MTN","","07-05-2025 21:55:57","07-05-2025 21:32:44","07-05-2025 22:11:4=
4","Site went down because rectifiers crashed // rectifier reset ","Fabrice=
 Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site=
 went down because rectifiers crashed // rectifier reset ","edwige.kapawo@m=
atech-cameroun.com","1394","07-05-2025 21:55:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004972055","Nsimalen=
 OCM","","07-05-2025 21:49:22","07-05-2025 21:45:05","07-05-2025 22:35:53",=
"Cascaded Incident from TTO5097166","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site on gen due to grid outage, si=
te went down due to Gen contacteur no excited // He excited gen contactor s=
ite on gen","system","267629","07-05-2025 21:49:22","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004972052","N=
kolda","IHS_YND_327","07-05-2025 21:48:17","07-05-2025 21:45:05","07-05-202=
5 22:35:53","Site on gen due to grid outage, site went down due to Gen cont=
acteur no excited // He excited gen contactor site on gen","Albran Byorel",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Site on ge=
n due to grid outage, site went down due to Gen contacteur no excited // He=
 excited gen contactor site on gen","gerard.tchangoue@matech-cameroun.com",=
"193","07-05-2025 21:48:17","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004972041","Nta=
ba","","07-05-2025 21:44:13","07-05-2025 19:58:01","07-05-2025 21:56:30","s=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed=
 //Site stabilised","Delor Telezing","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","site went down due to PWC Overload(12Kw 250A) Blaise R=
aoul SS IHS is iformed //Site stabilised","landry.etame@ihstowers.com","637=
3","07-05-2025 21:44:13","MATECH CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0004971866","N=
yanon","","07-05-2025 21:24:53","07-05-2025 17:56:59","07-05-2025 18:00:03"=
,"	ACTIVE //No power issue , site on Gen Ubaie=3D49.8 The TX FMEGr=E9goire =
//654547479// from huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","	ACTIVE //No power issue , site on Gen Ubaie=3D49.8 The TX FMEGr=E9goire=
 //654547479// from huawei is informed","gerard.tchangoue@matech-cameroun.c=
om","12475","07-05-2025 21:24:53","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004971822","SAA=
 2","","07-05-2025 21:17:10","07-05-2025 21:14:56","07-05-2025 21:17:08","G=
rid outage, site went down because gen start and stopped with high temp ala=
rm due to generator pellet pierced // He added water and Gen manually start=
ed(replacement ongoing)","Parker Tchoup","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Radiator Leakage","Grid outage, site went down because gen st=
art and stopped with high temp alarm due to generator pellet pierced // He =
added water and Gen manually started(replacement ongoing)","edwige.kapawo@m=
atech-cameroun.com","135","07-05-2025 21:17:10","MATECH CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0004971784","N=
R-Omnisport","","07-05-2025 21:09:09","07-05-2025 19:52:59","07-05-2025 22:=
04:27","Site went down due to disjunction of Cb(80A*80A) in PWC that trippe=
d OCM// He reamed Cb(80A*80A), site on grid","Delor Telezing","Equipment Re=
pair","Passive","Rectifier","Rectifier - Circuit Breaker","Site went down d=
ue to disjunction of Cb(80A*80A) in PWC that tripped OCM// He reamed Cb(80A=
*80A), site on grid","gerard.tchangoue@matech-cameroun.com","4636","07-05-2=
025 21:09:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0004971744","Montee-J=
ouvence-II","","07-05-2025 21:02:00","07-05-2025 19:56:51","07-05-2025 20:5=
1:55","Cascaded Incident from TTO5096696","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site went down due to Grid =
outage and gen failed to start due to ATS dysfonctionning//Grid return","sy=
stem","266688","07-05-2025 21:02:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0004971743","Damas","=
","07-05-2025 21:02:00","07-05-2025 19:56:51","07-05-2025 20:51:55","Cascad=
ed Incident from TTO5096696","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down due to Grid outage and gen=
 failed to start due to ATS dysfonctionning//Grid return","system","266688"=
,"07-05-2025 21:02:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004971742","Accacia =
New","","07-05-2025 21:01:59","07-05-2025 19:56:51","07-05-2025 20:51:55","=
Cascaded Incident from TTO5096696","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","site went down due to Grid outage and gen failed=
 to start due to ATS dysfonctionning//Grid return","system","266688","07-05=
-2025 21:01:59","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004971700","AWA=
E OCM","","07-05-2025 20:51:09","07-05-2025 20:49:00","07-05-2025 21:22:42"=
,"Grid outage, site went down because gen failed to start due to PWC ZTE ma=
lfunction, // He reset and gen manually started","Mba Lazare Herve","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outag=
e, site went down because gen failed to start due to PWC ZTE malfunction, /=
/ He reset and gen manually started","edwige.kapawo@matech-cameroun.com","1=
31","07-05-2025 20:51:09","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004971661","B=
ATA Mokolo OCM","","07-05-2025 20:47:10","07-05-2025 20:38:00","07-05-2025 =
20:57:00","Grid outage.no space to deploy mobile gen//Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.=
no space to deploy mobile gen//Grid return","gerard.tchangoue@matech-camero=
un.com","551","07-05-2025 20:47:10","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004971653","Tam=
tam Weekend","IHS_YND_562, IHS_YND_166, IHS_YND_518","07-05-2025 20:45:58",=
"07-05-2025 19:56:51","07-05-2025 20:52:24","site went down due to Grid out=
age and gen failed to start due to ATS dysfonctionning//Grid return","Hyema=
fo Gildas","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","si=
te went down due to Grid outage and gen failed to start due to ATS dysfonct=
ionning//Grid return","edwige.kapawo@matech-cameroun.com","2948","07-05-202=
5 20:45:58","MATECH CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0004971652","E=
ntree Cite Verte","","07-05-2025 20:45:56","07-05-2025 20:36:59","07-05-202=
5 20:57:59","No power issue, site is on grid with Ubaie=3D52.9V, TX Fme Bri=
ce Tsague/654419973 of huawei is informed.","Paul BIBOUM","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue, site is on grid with Ubaie=3D52.9V, TX Fme Brice Tsague/65441997=
3 of huawei is informed.","gerard.tchangoue@matech-cameroun.com","538","07-=
05-2025 20:45:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004971620","Jean Ves=
pa 2","","07-05-2025 20:40:25","07-05-2025 20:14:20","07-05-2025 21:10:44",=
"Cascaded Incident from TTO5096502","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because gen start a=
nd stopped due to grid bad voltage(lack of 2 phases), no RCP on site // He =
made a bridge with a good phase ","system","301889","07-05-2025 20:40:25","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004971554","Crf-Mban=
kolo-IHS","","07-05-2025 20:30:45","07-05-2025 20:14:20","07-05-2025 21:19:=
49","Cascaded Incident from TTO5096552","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation site went dow=
n because Gen failed to start due to Grid bad voltage on site //  Grid stab=
ilized","system","301889","07-05-2025 20:30:45","MATECH CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004971528","Jea=
n Vespa","IHS_YND_574","07-05-2025 20:26:38","07-05-2025 20:23:30","07-05-2=
025 21:19:49","Grid fluctuation site went down because Gen failed to start =
due to Grid bad voltage on site //  Grid stabilized","Mboua Thierry","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation site went down because Gen failed to start due to Grid bad voltag=
e on site //  Grid stabilized","edwige.kapawo@matech-cameroun.com","189","0=
7-05-2025 20:26:38","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004971495","Nko=
lbisson IITA LP","","07-05-2025 20:21:46","07-05-2025 20:13:31","07-05-2025=
 21:06:33","Grid Only, No space to deploy // Grid restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space=
 to deploy // Grid restored","edwige.kapawo@matech-cameroun.com","496","07-=
05-2025 20:21:46","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004971482","J=
-Vespa","IHS_YND_574, IHS_YND_544","07-05-2025 20:19:34","07-05-2025 20:14:=
20","07-05-2025 21:10:44","Site went down because gen start and stopped due=
 to grid bad voltage(lack of 2 phases), no RCP on site // He made a bridge =
with a good phase ","Mboua Thierry","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Site went down because gen start and sto=
pped due to grid bad voltage(lack of 2 phases), no RCP on site // He made a=
 bridge with a good phase ","gerard.tchangoue@matech-cameroun.com","315","0=
7-05-2025 20:19:34","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004971474","A=
wae Ewonkan","","07-05-2025 20:17:33","07-05-2025 20:16:25","07-05-2025 21:=
08:26","(Very unstable) Grid outage site went down due to Gen Overload (20K=
va, Iload 225 A)IHS SS Alphonse is informed","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","(Very unstable) Grid outage si=
te went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is inf=
ormed","gerard.tchangoue@matech-cameroun.com","69","07-05-2025 20:17:33","M=
ATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004971333","Nko=
lnda","IHS_YND_528","07-05-2025 19:59:16","07-05-2025 19:56:32","07-05-2025=
 20:51:51","Site went down due to disjunction of Cb(125A) in PWC that tripp=
ed MTN// He reamed Cb(125A), site on grid","Albran Byorel","Equipment Repai=
r","Passive","Rectifier","Rectifier - Circuit Breaker","Site went down due =
to disjunction of Cb(125A) in PWC that tripped MTN// He reamed Cb(125A), si=
te on grid","edwige.kapawo@matech-cameroun.com","165","07-05-2025 19:59:16"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0004971267","S=
cience","","07-05-2025 19:52:43","07-05-2025 19:43:26","07-05-2025 20:29:12=
","Grid outage, Site went down because Gen started and stopped with alarm "=
"undervoltage""// He balanced the load and started gen manually","TIENTCHEU=
 NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Under Volt=
age","Grid outage, Site went down because Gen started and stopped with alar=
m ""undervoltage""// He balanced the load and started gen manually","gerard=
.tchangoue@matech-cameroun.com","558","07-05-2025 19:52:43","MATECH CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0004971253","N=
R-Omnisport","","07-05-2025 19:50:56","07-05-2025 19:41:44","07-05-2025 19:=
51:44","Active//No power issue ,site on Gen with Ubaie=3D54 v The Tx FME Ar=
mand Nguetsa//691144412 from Huawei is informed","Delor Telezing","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue ,site on Gen with Ubaie=3D54 v The Tx FME Armand =
Nguetsa//691144412 from Huawei is informed","gerard.tchangoue@matech-camero=
un.com","553","07-05-2025 19:50:56","MATECH CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004971152","S=
calom-IHS","","07-05-2025 19:37:38","07-05-2025 19:31:23","08-05-2025 09:01=
:18","Grid outage;no space to deploy mobil Gen //Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage;no sp=
ace to deploy mobil Gen //Grid return","gerard.tchangoue@matech-cameroun.co=
m","377","07-05-2025 19:37:38","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004971131","M=
essassi 2","","07-05-2025 19:33:10","07-05-2025 19:31:58","07-05-2025 22:07=
:06","(Very unstable) Grid outage, Site went down due to 02/06 rectifiers i=
ssue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","(Very unstable) Grid outage, Site went down du=
e to 02/06 rectifiers issue // Grid stabilised","gerard.tchangoue@matech-ca=
meroun.com","74","07-05-2025 19:33:10","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004971111","A=
ccacia New","","07-05-2025 19:29:50","07-05-2025 16:22:06","07-05-2025 19:4=
9:23","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Grid Outage, No space to deploy MGE // Grid restored.Disjonction de CB 125=
A","kouoh.jean@ihstowers.com","279636","07-05-2025 19:29:50","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004971109","B=
iyemassi LAC","","07-05-2025 19:28:31","07-05-2025 16:22:06","07-05-2025 19=
:49:20","Grid outage.no space to deploy mobile gen//Grid return","","Cascad=
e Outage","Passive","Cascade Passive","Cascade Passive","Grid outage.no spa=
ce to deploy mobile gen//Grid return","kouoh.jean@ihstowers.com","279635","=
07-05-2025 19:28:31","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004970954","O=
LAMA","","07-05-2025 19:03:44","07-05-2025 18:56:33","07-05-2025 19:46:33",=
"grid outage,gen ran till fuel shortage//Refueling done","Fanda Brice","Fue=
l Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran till fuel=
 shortage//Refueling done","gerard.tchangoue@matech-cameroun.com","432","07=
-05-2025 19:03:44","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004970812","Nom=
ayos montee Meche","","07-05-2025 18:42:42","07-05-2025 18:41:34","07-05-20=
25 18:43:47","Grid outage site went down before Gen started due to poor bat=
tery back up // Eneo return","Fanda Brice","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage site went down befo=
re Gen started due to poor battery back up // Eneo return","edwige.kapawo@m=
atech-cameroun.com","69","07-05-2025 18:42:42","MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004970365","Nko=
abang MTN","","07-05-2025 17:41:39","07-05-2025 17:37:31","07-05-2025 18:16=
:19","Grid outage, site went down because gen start and stopped with over c=
urrent alarm(Unprouven alarm) // Reset of gen card done and gen started","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, site went down because gen start and stopped with over c=
urrent alarm(Unprouven alarm) // Reset of gen card done and gen started","e=
dwige.kapawo@matech-cameroun.com","248","07-05-2025 17:41:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004970244","Angongo"=
,"","07-05-2025 17:20:04","07-05-2025 17:13:54","07-05-2025 18:11:23","Casc=
aded Incident from TTO5095082","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen s=
tart and stopped due to high temp // He added water and manually start the =
gen","system","1225955","07-05-2025 17:20:04","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004970241","E=
beba","IHS_YND_335","07-05-2025 17:19:26","07-05-2025 17:13:54","07-05-2025=
 18:11:23","Grid outage, site went down because gen start and stopped due t=
o high temp // He added water and manually start the gen","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, site wen=
t down because gen start and stopped due to high temp // He added water and=
 manually start the gen","gerard.tchangoue@matech-cameroun.com","333","07-0=
5-2025 17:19:26","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004969858","Nko=
lbisson IITA LP","","07-05-2025 16:26:25","07-05-2025 15:04:34","07-05-2025=
 18:33:48","Grid Only, No space to deploy MGE // Grid restoration","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, N=
o space to deploy MGE // Grid restoration","edwige.kapawo@matech-cameroun.c=
om","4911","07-05-2025 16:26:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004969815","MEHANDAN=
","","07-05-2025 16:19:33","07-05-2025 16:13:08","07-05-2025 20:51:51","Cas=
caded Incident from TTO5094576","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to PWC ZTE malfunction // He reseted controller and g=
en manually started","system","1243952","07-05-2025 16:19:33","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004969809","O=
dza II OCM","IHS_YND_528","07-05-2025 16:18:49","07-05-2025 16:13:08","07-0=
5-2025 20:51:51","Grid outage, site went down because gen failed to start d=
ue to PWC ZTE malfunction // He reseted controller and gen manually started=
","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Grid outage, site went down because gen failed to start due to PWC ZTE =
malfunction // He reseted controller and gen manually started","gerard.tcha=
ngoue@matech-cameroun.com","342","07-05-2025 16:18:49","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004969796","Ron=
d Point Express1114","","07-05-2025 16:16:22","07-05-2025 16:11:07","07-05-=
2025 16:29:10","Grid outage, Site down due to poor battery backup // Grid r=
eturn","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, Site down due to poor battery backup =
// Grid return","edwige.kapawo@matech-cameroun.com","315","07-05-2025 16:16=
:22","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004969766","C=
RF Nkoabang","","07-05-2025 16:11:54","07-05-2025 16:10:42","07-05-2025 18:=
13:10","Solar -Grid, No space to deploy MGE // grid restoration","Mba Lazar=
e Herve","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Solar -Grid, No space to deploy MGE // grid restoration","gerard.tchangou=
e@matech-cameroun.com","73","07-05-2025 16:11:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0004969750","Elig-Edz=
oa","","07-05-2025 16:10:15","07-05-2025 16:03:30","07-05-2025 19:29:15","C=
ascaded Incident from TTO5094474","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","fme report  that PWC Overload(12Kw 250A) Blaise R=
aoul SS IHS is iformed","system","280645","07-05-2025 16:10:15","MATECH CMR=
"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004969739","ODZ=
A MINKAN EDIBI ASSI","","07-05-2025 16:08:04","07-05-2025 15:58:59","07-05-=
2025 17:49:59","Eneo Outage, site went down because Gen under voltage AVR f=
aulty  // Separate Excitation","Albran Byorel","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - AVR","Eneo Outage, site went down because Gen under vol=
tage AVR faulty  // Separate Excitation","edwige.kapawo@matech-cameroun.com=
","592","07-05-2025 16:08:04","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004969714","Nta=
ba","IHS_YND_133","07-05-2025 16:05:44","07-05-2025 16:03:30","07-05-2025 1=
9:29:15","fme report  that PWC Overload(12Kw 250A) Blaise Raoul SS IHS is i=
formed","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","fme report  that PWC Overload(12Kw 250A) Blaise Raoul=
 SS IHS is iformed","edwige.kapawo@matech-cameroun.com","135","07-05-2025 1=
6:05:44","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004969625","T=
amtam Weekend","","07-05-2025 15:51:39","07-05-2025 16:22:06","07-05-2025 1=
9:26:07","fme is on site","Hyemafo Gildas","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","TTO5093264","kouoh.jean@ihstowers.com","112=
89","07-05-2025 15:51:39","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004969582","D=
amas","","07-05-2025 15:42:59","07-05-2025 16:22:06","07-05-2025 19:49:06",=
"","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid Outage, No space to deploy MGE // Grid restored.Disjonction de=
 CB 125A","kouoh.jean@ihstowers.com","279635","07-05-2025 15:42:59","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0004969576","Nkolondo=
m","","07-05-2025 15:41:32","07-05-2025 14:38:07","07-05-2025 15:03:14","Ca=
scaded Incident from TTO5093914","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site Went Down because Giresse (677=
735657/Matech) was on site for work (PM) // End of work","system","271646",=
"07-05-2025 15:41:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0004969575","Ekombiti=
e","","07-05-2025 15:41:31","07-05-2025 14:38:07","07-05-2025 15:03:14","Ca=
scaded Incident from TTO5093914","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site Went Down because Giresse (677=
735657/Matech) was on site for work (PM) // End of work","system","271645",=
"07-05-2025 15:41:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004969539","MEHANDAN=
","","07-05-2025 15:36:07","07-05-2025 15:31:19","07-05-2025 16:00:26","Cas=
caded Incident from TTO5094266","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,Site went Down due to cont=
roller ZTE faulty // He manually started the Gen","system","268467","07-05-=
2025 15:36:07","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004969533","O=
dza II OCM","IHS_YND_528","07-05-2025 15:34:28","07-05-2025 15:31:19","07-0=
5-2025 16:00:26","Grid outage,Site went Down due to controller ZTE faulty /=
/ He manually started the Gen","Albran Byorel","Equipment Repair","Passive"=
,"Control Panel","ATS-AMF Issue","Grid outage,Site went Down due to control=
ler ZTE faulty // He manually started the Gen","gerard.tchangoue@matech-cam=
eroun.com","191","07-05-2025 15:34:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0004969384","Nkol-Meb=
anga","","07-05-2025 15:11:11","07-05-2025 15:06:02","07-05-2025 15:07:21",=
"Cascaded Incident from TTO5094077","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen start and stopped with ""High temps"" alarm // he added water and man=
ually start the Gen","system","269936","07-05-2025 15:11:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004969383","Carrefou=
r Ayissi Ele","","07-05-2025 15:11:11","07-05-2025 15:06:02","07-05-2025 15=
:07:21","Cascaded Incident from TTO5094077","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went dow=
n because Gen start and stopped with ""High temps"" alarm // he added water=
 and manually start the Gen","system","269936","07-05-2025 15:11:11","MATEC=
H CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004969378","Saa=
","IHS_YND_810, IHS_YND_809","07-05-2025 15:10:11","07-05-2025 15:50:02","0=
7-05-2025 17:12:33","Grid outage, Site went down because Gen start and stop=
ped with ""High temps"" alarm // he added water and manually start the Gen"=
,"Parker Tchoup","Equipment Repair","Passive","ACDG Gen","Gen Temp High","G=
rid outage, Site went down because Gen start and stopped with ""High temps"=
" alarm // he added water and manually start the Gen","edwige.kapawo@matech=
-cameroun.com","4037","07-05-2025 15:10:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0004969375","Montee-J=
ouvence-II","","07-05-2025 15:09:52","07-05-2025 13:34:06","07-05-2025 19:4=
9:23","Cascaded Incident from TTO5093264","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid Outage, No space to de=
ploy MGE // Grid restored","system","289715","07-05-2025 15:09:52","MATECH =
CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004969364","Bri=
quetterie","","07-05-2025 15:07:21","07-05-2025 15:02:59","07-05-2025 19:28=
:42","Grid Only, No space to deploy //Grid restored","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to dep=
loy //Grid restored","edwige.kapawo@matech-cameroun.com","263","07-05-2025 =
15:07:21","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0004969345","Bar=
riere IHS","","07-05-2025 15:04:01","07-05-2025 15:02:59","07-05-2025 16:16=
:07","Grid outage, Gen start and stop due to Gen battery discharged // Grid=
 return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - G=
enerator Battery","Grid outage, Gen start and stop due to Gen battery disch=
arged // Grid return","edwige.kapawo@matech-cameroun.com","63","07-05-2025 =
15:04:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0004969252","Messassi=
","","07-05-2025 14:51:52","07-05-2025 14:38:07","07-05-2025 15:03:14","Cas=
caded Incident from TTO5093914","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site Went Down because Giresse (6777=
35657/Matech) was on site for work (PM) // End of work","system","271647","=
07-05-2025 14:51:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0004969254","Nyom OCM=
","","07-05-2025 14:51:52","07-05-2025 14:38:07","07-05-2025 15:03:14","Cas=
caded Incident from TTO5093914","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site Went Down because Giresse (6777=
35657/Matech) was on site for work (PM) // End of work","system","271646","=
07-05-2025 14:51:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0004969253","Nkozoa",=
"","07-05-2025 14:51:52","07-05-2025 14:38:07","07-05-2025 15:03:14","Casca=
ded Incident from TTO5093914","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site Went Down because Giresse (677735=
657/Matech) was on site for work (PM) // End of work","system","271647","07=
-05-2025 14:51:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0004969251","Olembe-T=
erminus","","07-05-2025 14:51:51","07-05-2025 14:38:07","07-05-2025 15:03:1=
4","Cascaded Incident from TTO5093914","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site Went Down because Giress=
e (677735657/Matech) was on site for work (PM) // End of work","system","27=
1647","07-05-2025 14:51:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0004969250","NKOLMEKO=
NG YDE","","07-05-2025 14:51:51","07-05-2025 14:38:07","07-05-2025 15:03:14=
","Cascaded Incident from TTO5093914","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site Went Down because Giresse=
 (677735657/Matech) was on site for work (PM) // End of work","system","271=
646","07-05-2025 14:51:51","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004969234","MBA=
LNGONG LYCEE","","07-05-2025 14:48:44","07-05-2025 11:21:30","07-05-2025 16=
:13:18","Site went Down due to Gen overload(9kva, 130A) SS IHS Felix Zambe =
is informed and confirmed // Grid return","Fanda Brice","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Site went Down due to Gen overload(=
9kva, 130A) SS IHS Felix Zambe is informed and confirmed // Grid return","e=
dwige.kapawo@matech-cameroun.com","12435","07-05-2025 14:48:44","MATECH CMR=
"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0004969217","Bye=
massi Carrefour","","07-05-2025 14:46:15","07-05-2025 13:51:00","07-05-2025=
 16:17:00","Grid outage,site went down because Gen start and stopped with a=
larm *low oil pressure*// He added oil and manually started the Gen","Paul =
BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","=
Grid outage,site went down because Gen start and stopped with alarm *low oi=
l pressure*// He added oil and manually started the Gen","edwige.kapawo@mat=
ech-cameroun.com","10309","07-05-2025 14:46:15","MATECH CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0004969197","Ole=
mbe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IHS_=
YND_303, IHS_YND_304","07-05-2025 14:43:26","07-05-2025 14:38:07","07-05-20=
25 15:03:14","site Went Down because Giresse (677735657/Matech) was on site=
 for work (PM) // End of work","Fabrice Pouakam","Equipment Replacement","P=
assive","Planned Activity","Planned Activity - Passive","site Went Down bec=
ause Giresse (677735657/Matech) was on site for work (PM) // End of work","=
edwige.kapawo@matech-cameroun.com","320","07-05-2025 14:43:26","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004968731","B=
ATA Mokolo OCM","","07-05-2025 13:44:14","07-05-2025 13:42:07","07-05-2025 =
13:50:07","Grid outage, no space to deploy mobile gen // Grid returned	",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy mobile gen // Grid returned	","christelle.ngonga@=
matech-cameroun.com","128","07-05-2025 13:44:14","MATECH CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0004968662","R=
d-Pt-Express","IHS_YND_562, IHS_YND_166, IHS_YND_151, IHS_YND_546, IHS_YND_=
518","07-05-2025 13:37:24","07-05-2025 13:34:06","07-05-2025 19:49:23","Gri=
d Outage, No space to deploy MGE // Grid restored","","Grid Supply","Passiv=
e","Grid","National Grid - Grid Outage Issue","Grid Outage, No space to dep=
loy MGE // Grid restored","christelle.ngonga@matech-cameroun.com","21458","=
07-05-2025 13:37:24","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004968641","B=
iyemassi LAC","","07-05-2025 13:33:17","07-05-2025 13:31:10","07-05-2025 16=
:15:44","Grid outage No space to deploy MGE // Grid power return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage N=
o space to deploy MGE // Grid power return","christelle.ngonga@matech-camer=
oun.com","128","07-05-2025 13:33:17","MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004968614","c=
hina embassy yde","","07-05-2025 13:27:41","07-05-2025 13:23:33","07-05-202=
5 14:59:27","Grid outage, No space to deploy MGE // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MGE // Grid return","christelle.ngonga@matech-cameroun.co=
m","249","07-05-2025 13:27:41","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004968613","M=
ontee-Jouvence-II","","07-05-2025 13:27:08","07-05-2025 13:24:00","07-05-20=
25 13:31:23","ACTIVE// No power issue on site, site on Grid with Ubaie=3D54=
.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo G=
ildas","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE// No power issue on site, site on Grid with Ubaie=
=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed","chri=
stelle.ngonga@matech-cameroun.com","189","07-05-2025 13:27:08","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004968606","D=
amas","","07-05-2025 13:26:11","07-05-2025 13:24:02","07-05-2025 13:41:30",=
"Active//No power issue on site ,site on Grid with Ubaie=3D53.6V, TX FME Mb=
ah Hosiah (674007438) is informed","MINKA NICOLAS","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue on site ,site on Grid with Ubaie=3D53.6V, TX FME Mbah Hosiah (67=
4007438) is informed","christelle.ngonga@matech-cameroun.com","130","07-05-=
2025 13:26:11","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0004968531","C=
rf Cornier","","07-05-2025 13:08:39","07-05-2025 13:06:21","07-05-2025 13:2=
9:24","Active, No power issue site on battery with U=3D54.3VTX FME Armand N=
gestsa (691144412)From huawei is informed","MINKA NICOLAS","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve, No power issue site on battery with U=3D54.3VTX FME Armand Ngestsa (691=
144412)From huawei is informed","christelle.ngonga@matech-cameroun.com","13=
9","07-05-2025 13:08:39","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004968514","N=
koabang Ebolmedjock","","07-05-2025 13:06:51","07-05-2025 13:01:34","07-05-=
2025 13:21:14","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","christelle.ngonga@=
matech-cameroun.com","318","07-05-2025 13:06:51","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004968488","Tam=
tam Weekend","","07-05-2025 13:03:18","07-05-2025 12:59:53","07-05-2025 13:=
56:08","Grid outage.gen failed to start due to gen overload//We reduce load=
 and gen manually started ","Hyemafo Gildas","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage.gen failed to start due to gen ove=
rload//We reduce load and gen manually started ","franck.nkomot@matech-came=
roun.com","206","07-05-2025 13:03:18","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0004968403","Clu=
b France","","07-05-2025 12:48:04","07-05-2025 12:42:53","07-05-2025 16:14:=
47","Grid outage, No space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space =
to deploy MGE // Grid return","franck.nkomot@matech-cameroun.com","312","07=
-05-2025 12:48:04","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004968170","Men=
dong NB","","07-05-2025 12:06:37","07-05-2025 11:55:18","07-05-2025 12:03:1=
8","Active:No power issue on site, Ubaie: 53.5V Site on Grid with The Tx Fm=
e Mbah hosiah (?+237 6 99 69 96 94) from Huawei is informed","","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active:No power issue on site, Ubaie: 53.5V Site on Grid with The Tx Fme M=
bah hosiah (?+237 6 99 69 96 94) from Huawei is informed","franck.nkomot@ma=
tech-cameroun.com","680","07-05-2025 12:06:37","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0004967884","E=
toudi","","07-05-2025 11:31:44","07-05-2025 11:29:37","07-05-2025 11:32:03"=
,"Grid Low voltage ,site went down because Gen fails to start due to grid l=
ow voltage //Grid stabilisation","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Low Current Supply","Grid Low voltage ,site went do=
wn because Gen fails to start due to grid low voltage //Grid stabilisation"=
,"christelle.ngonga@matech-cameroun.com","128","07-05-2025 11:31:44","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0004967802","Mamch Bu=
ilding","","07-05-2025 11:17:40","07-05-2025 11:15:38","07-05-2025 11:18:46=
","Cascaded Incident from TTO5092226","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid only site ,no space to depl=
oy MGE // Grid restoration","system","262147","07-05-2025 11:17:40","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0004967781","C=
harles-Atangana","IHS_YND_051","07-05-2025 11:16:47","07-05-2025 11:15:38",=
"07-05-2025 11:28:38","Grid only site ,no space to deploy MGE // Grid resto=
ration","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid only site ,no space to deploy MGE // Grid restoration","christelle=
.ngonga@matech-cameroun.com","455","07-05-2025 11:16:47","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004967765","C=
RF Nkoabang","","07-05-2025 11:14:31","07-05-2025 11:12:24","07-05-2025 11:=
28:06","	Solar ,Grid Only site, No space for mobile gen // grid restoration=
","Mba Lazare Herve","Equipment Repair","Passive","Solar","Solar Control Pa=
nel Board","	Solar ,Grid Only site, No space for mobile gen // grid restora=
tion","christelle.ngonga@matech-cameroun.com","128","07-05-2025 11:14:31","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0004967621","Nkolbiss=
on usines des eaux 2","","07-05-2025 10:49:40","07-05-2025 10:34:14","07-05=
-2025 11:57:14","Cascaded Incident from TTO5091972","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage.gen failed to start due to alarm undervoltage//We reset card GE and ge=
n manually started","system","271634","07-05-2025 10:49:40","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004967599","SAA=
 Entrance","","07-05-2025 10:45:02","07-05-2025 10:40:30","07-05-2025 11:12=
:30","Grid fluctuation, site went down because Gen failed to start due to b=
ad voltage // he bypass the Grid and site on Gen","Parker Tchoup","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, site went down because Gen failed to start due to bad voltage // he=
 bypass the Grid and site on Gen","franck.nkomot@matech-cameroun.com","273"=
,"07-05-2025 10:45:02","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0004967579","Eto=
ug-Ebe 2","","07-05-2025 10:39:16","07-05-2025 10:31:08","07-05-2025 16:46:=
16","Grid outage, No space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space =
to deploy MGE // Grid return","franck.nkomot@matech-cameroun.com","489","07=
-05-2025 10:39:16","MATECH CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0004967568","Nko=
lbisson","IHS_YND_763","07-05-2025 10:37:21","07-05-2025 10:34:14","07-05-2=
025 11:57:14","Grid outage.gen failed to start due to alarm undervoltage //=
 We reset card GE and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Under Voltage","Grid outage.gen=
 failed to start due to alarm undervoltage//We reset card GE and gen manual=
ly started","franck.nkomot@matech-cameroun.com","188","07-05-2025 10:37:21"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004967474","M=
arche Odza","","07-05-2025 10:24:53","07-05-2025 10:23:46","07-05-2025 10:2=
5:15","Grid fluctuation,site went down due to rectifiers dysfunction// Grid=
 stabilisation","Albran Byorel","Grid Supply","Passive","Grid","National Gr=
id - Unstable Grid Supply Issue","Grid fluctuation,site went down due to re=
ctifiers dysfunction// Grid stabilisation","christelle.ngonga@matech-camero=
un.com","68","07-05-2025 10:24:53","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004967434","E=
mana lycee 2","IHS_YND_274","07-05-2025 10:17:36","07-05-2025 10:14:30","07=
-05-2025 10:31:30","Grid outage.gen failed to start due to poor backup//Gen=
 start automatically","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage.gen failed to start du=
e to poor backup//Gen start automatically","christelle.ngonga@matech-camero=
un.com","187","07-05-2025 10:17:36","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004967424","E=
mana Lycee","","07-05-2025 10:16:22","07-05-2025 10:14:30","07-05-2025 10:3=
1:30","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage.gen failed to start due to poor backup//Gen sta=
rt automatically","christelle.ngonga@matech-cameroun.com","273025","07-05-2=
025 10:16:22","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004967400","Acc=
acia New","","07-05-2025 10:12:55","07-05-2025 10:11:49","07-05-2025 16:22:=
05","Grid outage, no space to deploy MGE // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy MGE // Grid return","franck.nkomot@matech-cameroun.com","68","07-=
05-2025 10:12:55","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004967297","B=
arriere","","07-05-2025 09:56:08","07-05-2025 08:25:56","07-05-2025 08:35:5=
6","Active//No power issue on site Ubay: 54.51V site on Grid Henry (6999496=
93/Huawei) is informed","Hyemafo Gildas","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue=
 on site Ubay: 54.51V site on Grid Henry (699949693/Huawei) is informed","c=
hristelle.ngonga@matech-cameroun.com","5413","07-05-2025 09:56:08","MATECH =
CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004967288","M=
ANGUIERS CHAPELLE","","07-05-2025 09:54:03","07-05-2025 08:37:50","07-05-20=
25 11:55:50","Grid outage, site went down due to gen overload (22kva, 340A)=
 SS IHS Bernard ATANGANA is informed and confirmed//  grid restoration","Fa=
brice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid outage, site went down due to gen overload (22kva, 340A) SS IHS Bernard=
 ATANGANA is informed and confirmed//  grid restoration","christelle.ngonga=
@matech-cameroun.com","4574","07-05-2025 09:54:03","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004967254","C=
RF Nkoabang","","07-05-2025 09:48:14","07-05-2025 09:48:10","07-05-2025 09:=
58:29","Solar ,Grid Only site, No space for mobile gen // grid restoration"=
,"Mba Lazare Herve","Equipment Repair","Passive","Solar","Solar Control Pan=
el Board","Solar ,Grid Only site, No space for mobile gen // grid restorati=
on","christelle.ngonga@matech-cameroun.com","5","07-05-2025 09:48:14","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004966699","N=
kolo II New","","07-05-2025 08:28:16","07-05-2025 08:19:06","07-05-2025 09:=
19:06","Active/ No power issue site on Gen with U=3D50.8V The FME Tx Lionel=
 Steve /655184876/ From huawei is informed.","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active/ No power issue site on Gen with U=3D50.8V The FME Tx Lionel Steve =
/655184876/ From huawei is informed.","franck.nkomot@matech-cameroun.com","=
551","07-05-2025 08:28:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_748","NOCINC0004966685","Nkoabang=
 Alembe","","07-05-2025 08:25:52","07-05-2025 08:18:06","07-05-2025 14:33:0=
5","Cascaded Incident from TTO5090964","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, no space to dep=
loy MGE // Grid return","system","294144","07-05-2025 08:25:52","MATECH CMR=
"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004966668","Nko=
lbisson IITA LP","IHS_YND_748","07-05-2025 08:23:12","07-05-2025 08:18:06",=
"07-05-2025 14:33:05","Grid outage, no space to deploy MGE // Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage, no space to deploy MGE // Grid return","franck.nkomot@matech-camer=
oun.com","307","07-05-2025 08:23:12","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004966587","Mfo=
u EPC","","07-05-2025 08:05:47","07-05-2025 07:55:41","07-05-2025 08:44:41"=
,"Site went down due to 02 rectifiers faulty on site // He reset Rectifiers=
: Site on grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to 02 rectifier faulty on site // H=
e reset Rectifiers: Site on grid","franck.nkomot@matech-cameroun.com","940"=
,"07-05-2025 08:05:47","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004966548","Mes=
sassi 2","","07-05-2025 07:53:00","07-05-2025 07:49:52","07-05-2025 13:42:5=
2","(Very unstable) Grid outage, Site went down due to 02/06 rectifiers iss=
ue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","(Very unstable) Grid outage, Site went down due =
to 02/06 rectifiers issue // Grid stabilised","franck.nkomot@matech-camerou=
n.com","190","07-05-2025 07:53:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004966540","Emana Ly=
cee","","07-05-2025 07:51:25","07-05-2025 07:50:36","07-05-2025 08:05:36","=
Cascaded Incident from TTO5090808","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage.gen failed to start d=
ue to poor backup//Gen start automatically","system","267095","07-05-2025 0=
7:51:25","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004966530","E=
mana lycee 2","IHS_YND_274","07-05-2025 07:50:51","07-05-2025 07:48:36","07=
-05-2025 08:06:36","Grid outage.gen failed to start due to poor backup//Gen=
 start automatically","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage.gen failed to start du=
e to poor backup//Gen start automatically","franck.nkomot@matech-cameroun.c=
om","136","07-05-2025 07:50:51","MATECH CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0004966369","E=
lobi Mokolo","","07-05-2025 07:25:49","07-05-2025 07:22:40","07-05-2025 08:=
21:40","Active//No power issue on site, site on Grid with U=3D53,2 V The TX=
 FME Brice (650214096) from huawei is informed.","Mboua Thierry","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site, site on Grid with U=3D53,2 V The TX FME B=
rice (650214096) from huawei is informed.","franck.nkomot@matech-cameroun.c=
om","190","07-05-2025 07:25:49","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004966143","B=
riqueterie","","07-05-2025 06:38:59","07-05-2025 06:34:52","07-05-2025 08:2=
9:52","Grid outage, no space to deploy MGE on site // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 no space to deploy MGE on site // Grid return","loic.noumsi@matech-camerou=
n.com","248","07-05-2025 06:38:59","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004965771","M=
ambine","","07-05-2025 05:01:37","07-05-2025 04:57:29","07-05-2025 07:16:29=
","Hybrid gen site.gen failed to start due to oil sensor disconnected//We f=
ixed oil sensor and gen manually started","Fanda Brice","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Oil Sensor Switch","Hybrid gen site.gen failed=
 to start due to oil sensor disconnected//We fixed oil sensor and gen manua=
lly started","loic.noumsi@matech-cameroun.com","249","07-05-2025 05:01:37",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0004965683","Messassi=
 okolo","","07-05-2025 04:30:00","07-05-2025 04:25:07","07-05-2025 07:50:05=
","Cascaded Incident from TTO5089832","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, we can't deploy t=
he mobile generator to this site because of the noise pollution// Grid retu=
rn","system","293","07-05-2025 04:30:00","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004965680","E=
MANA BILICK CITY","IHS_YND_279","07-05-2025 04:29:13","07-05-2025 04:25:07"=
,"07-05-2025 07:56:07","Grid outage, we can't deploy the mobile generator t=
o this site because of the noise pollution// Grid return","Fabrice Pouakam"=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, we can't deploy the mobile generator to this site because of the noi=
se pollution// Grid return","loic.noumsi@matech-cameroun.com","248","07-05-=
2025 04:29:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004965410","Ebogo","=
","07-05-2025 02:26:23","07-05-2025 02:16:11","07-05-2025 02:23:11","Cascad=
ed Incident from TTO5089486","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage,site went down before DG star=
t : Poor Batteries backup// Grid return","system","265654","07-05-2025 02:2=
6:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004965407","Melen Ba=
'aba","","07-05-2025 02:26:22","07-05-2025 02:16:11","07-05-2025 02:21:38",=
"Cascaded Incident from TTO5089486","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,site went down before =
DG start : Poor Batteries backup// Grid return","system","265654","07-05-20=
25 02:26:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004965409","TSINGA V=
ILLAGE 2","","07-05-2025 02:26:22","07-05-2025 02:16:11","07-05-2025 02:21:=
38","Cascaded Incident from TTO5089486","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage,site went down be=
fore DG start : Poor Batteries backup// Grid return","system","265655","07-=
05-2025 02:26:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004965408","Ngoulmek=
ong-Nord","","07-05-2025 02:26:22","07-05-2025 02:16:11","07-05-2025 02:21:=
38","Cascaded Incident from TTO5089486","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,site went down bef=
ore DG start : Poor Batteries backup// Grid return","system","265655","07-0=
5-2025 02:26:22","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004965393","N=
kolfoulou","IHS_YND_308, IHS_YND_277, IHS_YND_719, IHS_YND_307","07-05-2025=
 02:22:40","07-05-2025 02:16:11","07-05-2025 02:23:11","Grid outage, site w=
ent down before DG start : Poor Batteries backup// Grid return","Siligap Bo=
ris","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Grid outage,site went down before DG start : Poor Batteries backup// =
Grid return","loic.noumsi@matech-cameroun.com","390","07-05-2025 02:22:40",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004965246","Elig Edz=
oa","","07-05-2025 01:16:43","07-05-2025 01:06:11","07-05-2025 01:32:41","C=
ascaded Incident from TTO5089289","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
Grid fluctuations and poor backup battery // Grid stabilised","system","631=
","07-05-2025 01:16:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0004965245","Charles-=
Atangana","","07-05-2025 01:16:42","07-05-2025 01:06:11","07-05-2025 01:32:=
41","Cascaded Incident from TTO5089289","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down due to Grid flu=
ctuations and poor backup battery // Grid stabilised","system","631","07-05=
-2025 01:16:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_134","NOCINC0004965243","Vallee B=
astos MTN","","07-05-2025 01:16:42","07-05-2025 01:06:11","07-05-2025 01:32=
:41","Cascaded Incident from TTO5089289","Mboua Thierry","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to Grid fluctuations and poor backup battery // Grid stabilised","system=
","631","07-05-2025 01:16:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_016","NOCINC0004965242","Maetur",=
"","07-05-2025 01:16:42","07-05-2025 01:06:11","07-05-2025 01:32:41","Casca=
ded Incident from TTO5089289","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Grid =
fluctuations and poor backup battery // Grid stabilised","system","631","07=
-05-2025 01:16:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0004965244","Hopital =
Central","","07-05-2025 01:16:42","07-05-2025 01:06:11","07-05-2025 01:32:4=
1","Cascaded Incident from TTO5089289","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid outage, site went down due to Grid fluc=
tuations and poor backup battery // Grid stabilised","system","631","07-05-=
2025 01:16:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0004965241","ELIg-Ess=
ono","","07-05-2025 01:16:41","07-05-2025 01:06:11","07-05-2025 01:32:41","=
Cascaded Incident from TTO5089289","Delor Telezing","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 Grid fluctuations and poor backup battery // Grid stabilised","system","63=
0","07-05-2025 01:16:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_731","NOCINC0004965238","UPAC LP"=
,"","07-05-2025 01:16:41","07-05-2025 01:06:11","07-05-2025 01:32:41","Casc=
aded Incident from TTO5089289","","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Grid outage, site went down due to Grid fluctuations=
 and poor backup battery // Grid stabilised","system","630","07-05-2025 01:=
16:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0004965240","Garbati =
building","","07-05-2025 01:16:41","07-05-2025 01:06:11","07-05-2025 01:32:=
41","Cascaded Incident from TTO5089289","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to Grid fluctuations and poor backup battery // Grid stabilised","system=
","630","07-05-2025 01:16:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0004965239","Sapeur",=
"","07-05-2025 01:16:41","07-05-2025 01:06:11","07-05-2025 01:32:41","Casca=
ded Incident from TTO5089289","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to Grid =
fluctuations and poor backup battery // Grid stabilised","system","630","07=
-05-2025 01:16:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0004965237","HOPITAL =
DE LA CAISSE","","07-05-2025 01:16:41","07-05-2025 01:06:11","07-05-2025 01=
:32:41","Cascaded Incident from TTO5089289","Delor Telezing","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site went do=
wn due to Grid fluctuations and poor backup battery // Grid stabilised","sy=
stem","630","07-05-2025 01:16:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_049","NOCINC0004965235","Etoa-Mek=
i","","07-05-2025 01:16:40","07-05-2025 01:06:11","07-05-2025 01:32:41","Ca=
scaded Incident from TTO5089289","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to G=
rid fluctuations and poor backup battery // Grid stabilised","system","629"=
,"07-05-2025 01:16:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0004965236","POLYCLIN=
IQUE TSINGA","","07-05-2025 01:16:40","07-05-2025 01:06:11","07-05-2025 01:=
32:41","Cascaded Incident from TTO5089289","Mboua Thierry","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 due to Grid fluctuations and poor backup battery // Grid stabilised","syst=
em","629","07-05-2025 01:16:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0004965232","H-Franco=
 New","","07-05-2025 01:16:40","07-05-2025 01:06:11","07-05-2025 01:32:41",=
"Cascaded Incident from TTO5089289","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down due t=
o Grid fluctuations and poor backup battery // Grid stabilised","system","6=
29","07-05-2025 01:16:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_091","NOCINC0004965234","Jouvence=
 2000","","07-05-2025 01:16:40","07-05-2025 01:06:11","07-05-2025 01:32:41"=
,"Cascaded Incident from TTO5089289","Delor Telezing","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, site went down due =
to Grid fluctuations and poor backup battery // Grid stabilised","system","=
629","07-05-2025 01:16:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0004965233","Mamch Bu=
ilding","","07-05-2025 01:16:40","07-05-2025 01:06:11","07-05-2025 01:32:41=
","Cascaded Incident from TTO5089289","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, site went down due =
to Grid fluctuations and poor backup battery // Grid stabilised","system","=
629","07-05-2025 01:16:40","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004965223","O=
LAMA","","07-05-2025 01:11:22","07-05-2025 01:11:11","07-05-2025 01:50:32",=
"No power issue on site Ubaie =3D54.9V, The TX FME Henri (699949693) from H=
uawei is informed","Fanda Brice","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie =
=3D54.9V, The TX FME Henri (699949693) from Huawei is informed","ludivine.n=
gamaleu@ihstowers.com","12","07-05-2025 01:11:22","MATECH CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0004965222","Hot=
el de Ville Yde","IHS_YND_711, IHS_YND_563, IHS_YND_051, IHS_YND_091, IHS_Y=
ND_049, IHS_YND_086, IHS_YND_064, IHS_YND_731, IHS_YND_029, IHS_YND_024, IH=
S_YND_014, IHS_YND_016, IHS_YND_134, IHS_YND_027, IHS_YND_125, IHS_YND_504"=
,"07-05-2025 01:11:22","07-05-2025 01:06:11","07-05-2025 01:32:41","Grid ou=
tage, site went down due to Grid fluctuations and poor backup battery // Gr=
id stabilised","Paul BIBOUM","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Grid outage, site went down due to Grid fluctua=
tions and poor backup battery // Grid stabilised","loic.noumsi@matech-camer=
oun.com","312","07-05-2025 01:11:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004965041","Omnispor=
t-Rail","","07-05-2025 00:16:48","07-05-2025 00:13:48","07-05-2025 07:59:14=
","Cascaded Incident from TTO5089074","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) SS IHS Bernard ATANGANA is informed and conf=
irmed//Grid return","system","294578","07-05-2025 00:16:48","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004965040","M=
ANGUIERS CHAPELLE","IHS_YND_506","07-05-2025 00:16:02","07-05-2025 00:13:48=
","07-05-2025 07:59:14","Grid outage, site went down due to gen overload (2=
2kva, 340A) SS IHS Bernard ATANGANA is informed and confirmed//Grid return"=
,"Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","Grid outage, site went down due to gen overload (22kva, 340A) SS IHS Ber=
nard ATANGANA is informed and confirmed//Grid return","ludivine.ngamaleu@ih=
stowers.com","135","07-05-2025 00:16:02","MATECH CMR"
"Cancelled","Warning","CTR_161","IHS_YND_506","NOCINC0004965034","Omnisport=
-Rail","","07-05-2025 00:15:02","","","","Delor Telezing","","","","","","l=
udivine.ngamaleu@ihstowers.com","10","07-05-2025 00:15:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0004965029","Charles-=
Atangana","","07-05-2025 00:12:58","07-05-2025 00:00:42","07-05-2025 00:18:=
22","Cascaded Incident from TTO5089041","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down due to grid flu=
ctuations // SITE stabilised","system","266649","07-05-2025 00:12:58","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004965030","Elig Edz=
oa","","07-05-2025 00:12:58","07-05-2025 00:00:42","07-05-2025 00:18:22","C=
ascaded Incident from TTO5089041","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down due to =
grid fluctuations // SITE stabilised","system","266650","07-05-2025 00:12:5=
8","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_134","NOCINC0004965027","Vallee B=
astos MTN","","07-05-2025 00:12:57","07-05-2025 00:00:42","07-05-2025 00:18=
:22","Cascaded Incident from TTO5089041","Mboua Thierry","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to grid fluctuations // SITE stabilised","system","266647","07-05-2025 0=
0:12:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0004965025","ELIg-Ess=
ono","","07-05-2025 00:12:57","07-05-2025 00:00:42","07-05-2025 00:18:22","=
Cascaded Incident from TTO5089041","Delor Telezing","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 grid fluctuations // SITE stabilised","system","266651","07-05-2025 00:12:=
57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_016","NOCINC0004965026","Maetur",=
"","07-05-2025 00:12:57","07-05-2025 00:00:42","07-05-2025 00:18:22","Casca=
ded Incident from TTO5089041","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to grid =
fluctuations // SITE stabilised","system","266649","07-05-2025 00:12:57","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0004965028","Hopital =
Central","","07-05-2025 00:12:57","07-05-2025 00:00:42","07-05-2025 00:18:2=
2","Cascaded Incident from TTO5089041","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid outage, site went down due to grid fluc=
tuations // SITE stabilised","system","266646","07-05-2025 00:12:57","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_731","NOCINC0004965022","UPAC LP"=
,"","07-05-2025 00:12:56","07-05-2025 00:00:42","07-05-2025 00:18:22","Casc=
aded Incident from TTO5089041","","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Grid outage, site went down due to grid fluctuations=
 // SITE stabilised","system","266650","07-05-2025 00:12:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0004965023","Sapeur",=
"","07-05-2025 00:12:56","07-05-2025 00:00:42","07-05-2025 00:18:22","Casca=
ded Incident from TTO5089041","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down due to grid =
fluctuations // SITE stabilised","system","266648","07-05-2025 00:12:56","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0004965021","HOPITAL =
DE LA CAISSE","","07-05-2025 00:12:56","07-05-2025 00:00:42","07-05-2025 00=
:18:22","Cascaded Incident from TTO5089041","Delor Telezing","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site went do=
wn due to grid fluctuations // SITE stabilised","system","266650","07-05-20=
25 00:12:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0004965020","POLYCLIN=
IQUE TSINGA","","07-05-2025 00:12:56","07-05-2025 00:00:42","07-05-2025 00:=
18:22","Cascaded Incident from TTO5089041","Mboua Thierry","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 due to grid fluctuations // SITE stabilised","system","266645","07-05-2025=
 00:12:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0004965024","Garbati =
building","","07-05-2025 00:12:56","07-05-2025 00:00:42","07-05-2025 00:18:=
22","Cascaded Incident from TTO5089041","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to grid fluctuations // SITE stabilised","system","266646","07-05-2025 0=
0:12:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_049","NOCINC0004965019","Etoa-Mek=
i","","07-05-2025 00:12:55","07-05-2025 00:00:42","07-05-2025 00:18:22","Ca=
scaded Incident from TTO5089041","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to g=
rid fluctuations // SITE stabilised","system","266647","07-05-2025 00:12:55=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0004965017","Mamch Bu=
ilding","","07-05-2025 00:12:55","07-05-2025 00:00:42","07-05-2025 00:18:22=
","Cascaded Incident from TTO5089041","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, site went down due =
to grid fluctuations // SITE stabilised","system","266647","07-05-2025 00:1=
2:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_091","NOCINC0004965018","Jouvence=
 2000","","07-05-2025 00:12:55","07-05-2025 00:00:42","07-05-2025 00:18:22"=
,"Cascaded Incident from TTO5089041","Delor Telezing","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, site went down due =
to grid fluctuations // SITE stabilised","system","266648","07-05-2025 00:1=
2:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0004965016","H-Franco=
 New","","07-05-2025 00:12:55","07-05-2025 00:00:42","07-05-2025 00:18:22",=
"Cascaded Incident from TTO5089041","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down due t=
o grid fluctuations // SITE stabilised","system","266648","07-05-2025 00:12=
:55","MATECH CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0004965014","Hot=
el de Ville Yde","IHS_YND_711, IHS_YND_563, IHS_YND_051, IHS_YND_091, IHS_Y=
ND_049, IHS_YND_086, IHS_YND_064, IHS_YND_731, IHS_YND_029, IHS_YND_024, IH=
S_YND_014, IHS_YND_016, IHS_YND_134, IHS_YND_027, IHS_YND_125, IHS_YND_504"=
,"07-05-2025 00:07:41","07-05-2025 00:00:42","07-05-2025 00:18:22","Grid ou=
tage, site went down due to grid fluctuations // SITE stabilised","Paul BIB=
OUM","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid outage, site went down due to grid fluctuations // SITE stabilised=
","loic.noumsi@matech-cameroun.com","420","07-05-2025 00:07:41","MATECH CMR=
"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004964919","Eto=
ug ebe Carrefour","","06-05-2025 23:44:24","06-05-2025 23:41:19","06-05-202=
5 23:48:24","Grid outage site went down before gen started due to poor batt=
ery backup // Grid returned","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage site went down b=
efore gen started due to poor battery backup // Grid returned","loic.noumsi=
@matech-cameroun.com","185","06-05-2025 23:44:24","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004964842","Eto=
ug ebe biscuiterie","","06-05-2025 23:28:14","06-05-2025 23:20:56","07-05-2=
025 00:11:05","Grid outage, site went down due to Site went down because 01=
 rectifier slot faulty, // He removed rectifier of this slot, site on Gen",=
"Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Grid outage, site went down due to Site went down because 01 rectifier s=
lot faulty, // He removed rectifier of this slot, site on Gen","loic.noumsi=
@matech-cameroun.com","439","06-05-2025 23:28:14","MATECH CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0004964754","N=
kenglikok","","06-05-2025 23:02:03","06-05-2025 22:51:52","07-05-2025 00:23=
:15","Active // no power issue, site is on grid with No com, transmission c=
ard burnt ,The Tx FME Etienne 695033981 of huawei is informed","Kemeni Fran=
klin","Cascade Outage","Active","Cascade Active","Cascade Active","Active n=
o power issue on site, site on Gen with U=3D55V Tx FME FULBERT /654266068/ =
from huawei is informed, Site up without intervention","gaelle.njiofack@mat=
ech-cameroun.com","270689","06-05-2025 23:02:03","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004964750","M=
bankomo IHS","IHS_YND_348, IHS_YND_339","06-05-2025 23:01:07","06-05-2025 2=
2:51:52","07-05-2025 00:23:52","Active no power issue on site, site on Gen =
with U=3D55V Tx FME FULBERT /654266068/ from huawei is informed, Site up wi=
thout intervention","Fanda Brice","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active no power issue on site=
, site on Gen with U=3D55V Tx FME FULBERT /654266068/ from huawei is inform=
ed, Site up without intervention","gaelle.njiofack@matech-cameroun.com","55=
6","06-05-2025 23:01:07","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004964722","E=
beba","","06-05-2025 22:58:44","06-05-2025 22:51:52","06-05-2025 23:11:46",=
"","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active=
","Active no power issue on site, site on Gen with U=3D55V Tx FME FULBERT /=
654266068/ from huawei is informed, Site up without intervention","gaelle.n=
jiofack@matech-cameroun.com","270689","06-05-2025 22:58:44","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004964719","Men=
dong NB","","06-05-2025 22:56:53","06-05-2025 20:51:32","06-05-2025 23:08:5=
4","Grid outage, site went down due to disjunction of CB 125 A in the Huawe=
i bay // CB rearmed","","Equipment Repair","Passive","Control Panel","Circu=
it Breaker Tripped","Grid outage, site went down due to disjunction of CB 1=
25 A in the Huawei bay // CB rearmed","gaelle.njiofack@matech-cameroun.com"=
,"7521","06-05-2025 22:56:53","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004964612","NKO=
MKANA ELIZA HOTEL","","06-05-2025 22:30:48","06-05-2025 22:28:40","06-05-20=
25 22:34:18","Grid outage, no space to deploy MGE on site // Grid returned"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d outage, no space to deploy MGE on site // Grid returned","cedric.tiani@ma=
tech-cameroun.com","128","06-05-2025 22:30:48","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004964607","BAT=
A Mokolo OCM","","06-05-2025 22:29:43","06-05-2025 22:28:29","06-05-2025 22=
:32:30","Grid outage, no space to deploy mobile gen // Grid returned","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, no space to deploy mobile gen // Grid returned","cedric.tiani@matech-ca=
meroun.com","75","06-05-2025 22:29:43","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004964521","E=
ssomba","","06-05-2025 22:08:58","06-05-2025 22:04:56","06-05-2025 22:10:12=
","Site went down due to 03/06 rectifiers faulty on site// He reset it and =
site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to 03/06 rectifiers faulty on site// =
He reset it and site on Grid","vanel.mbiada@matech-cameroun.com","244","06-=
05-2025 22:08:58","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004964409","N=
omayos montee Meche","","06-05-2025 21:53:33","06-05-2025 21:49:05","06-05-=
2025 22:02:16","Grid outage site went down before Gen started due to poor b=
attery back up // Eneo return","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage site went down be=
fore Gen started due to poor battery back up // Eneo return","vanel.mbiada@=
matech-cameroun.com","269","06-05-2025 21:53:33","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004964287","Nta=
ba","","06-05-2025 21:33:00","06-05-2025 21:24:52","06-05-2025 21:42:11","	=
site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iforme=
d //Site stabilised","Delor Telezing","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","	site went down due to PWC Overload(12Kw=
 250A) Blaise Raoul SS IHS is iformed //Site stabilised","cedric.tiani@mate=
ch-cameroun.com","489","06-05-2025 21:33:00","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0004964281","E=
toug ebe Meweulo","","06-05-2025 21:29:30","06-05-2025 21:27:03","06-05-202=
5 21:53:12","site went down because CB125A who feed equipment ocm disjuncte=
d in PWC//he rearmed","Hyemafo Gildas","Equipment Repair","Passive","Rectif=
ier","Rectifier - Circuit Breaker","site went down because CB125A who feed =
equipment ocm disjuncted in PWC//he rearmed","vanel.mbiada@matech-cameroun.=
com","148","06-05-2025 21:29:30","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004964013","Eto=
ug ebe Carrefour","","06-05-2025 20:43:26","06-05-2025 20:41:11","06-05-202=
5 20:49:53","Grid outage site went down before gen started due to poor batt=
ery backup // Grid retun","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage site went down befo=
re gen started due to poor battery backup // Grid retun","cedric.tiani@mate=
ch-cameroun.com","135","06-05-2025 20:43:26","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004964009","Mes=
sassi 2","","06-05-2025 20:42:48","06-05-2025 20:38:37","06-05-2025 20:48:1=
0","Site went down because 04/06 rectifiers dysfuncionned// He reset rectif=
iers, site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down because 04/06 rectifiers dysfuncionn=
ed// He reset rectifiers, site on Grid","cedric.tiani@matech-cameroun.com",=
"252","06-05-2025 20:42:48","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004963888","Nta=
ba","","06-05-2025 20:25:52","06-05-2025 20:23:47","06-05-2025 20:41:39","s=
ite went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is informe=
d //Site stabilised","Delor Telezing","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","site went down due to PWC Overload(12Kw =
250A) Blaise Raoul SS IHS is informed //Site stabilised","cedric.tiani@mate=
ch-cameroun.com","126","06-05-2025 20:25:52","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004963765","Odz=
a petit marche new","","06-05-2025 20:03:02","06-05-2025 20:01:46","06-05-2=
025 20:51:32","Site went down due to insufficient rectifiers on site // He =
reset it and site on Grid","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficient rectifiers =
on site // He reset it and site on Grid","cedric.tiani@matech-cameroun.com"=
,"77","06-05-2025 20:03:02","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004963697","Eto=
ug ebe biscuiterie","","06-05-2025 19:50:00","06-05-2025 19:46:04","06-05-2=
025 21:01:10","Site went down due to 01 rectifier faulty on site //He repla=
ced it  and site on Grid","Hyemafo Gildas","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to 01 rectifier faulty on s=
ite //He replaced it  and site on Grid","vanel.mbiada@matech-cameroun.com",=
"237","06-05-2025 19:50:00","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004963572","N=
gouetou","","06-05-2025 19:29:42","06-05-2025 09:43:23","07-05-2025 04:55:0=
9","Active // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gre=
goire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gregoire (6=
54547479) from Huawei is informed","cedric.tiani@matech-cameroun.com","3518=
1","06-05-2025 19:29:42","MATECH CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004963552","M=
ini-Ferme","","06-05-2025 19:23:49","06-05-2025 19:19:36","07-05-2025 10:57=
:36","Grid outage, no space to deploy a mobile gen// grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
no space to deploy a mobile gen// grid return","vanel.mbiada@matech-camerou=
n.com","253","06-05-2025 19:23:49","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004963477","N=
kolo II New","","06-05-2025 19:08:54","06-05-2025 19:01:37","06-05-2025 20:=
26:19","Active/ No power issue site on Gen with U=3D53.5V The FME Tx Lionel=
 Steve /655184876/ From huawei is informed.","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active/ No power issue site on Gen with U=3D53.5V The FME Tx Lionel Steve =
/655184876/ From huawei is informed.","vanel.mbiada@matech-cameroun.com","4=
38","06-05-2025 19:08:54","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004963414","Men=
dong NB","","06-05-2025 18:55:42","06-05-2025 18:48:24","06-05-2025 19:20:2=
9","No power issue on site, Ubaie: 53.3V Site on Grid with The Tx Fme Mbah =
hosiah(?+237 6 99 69 96 94) from Huawei is informed","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site, Ubaie: 53.3V Site on Grid with The Tx Fme Mbah hosiah(?+23=
7 6 99 69 96 94) from Huawei is informed","cedric.tiani@matech-cameroun.com=
","439","06-05-2025 18:55:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004963167","Omnispor=
t-Rail","","06-05-2025 18:05:20","06-05-2025 10:46:02","06-05-2025 22:08:51=
","Cascaded Incident from TTO5083847","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","	Grid outage, site went down du=
e to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and conf=
irmed// Site stablised","system","314094","06-05-2025 18:05:20","MATECH CMR=
"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004963132","Bri=
quetterie","","06-05-2025 17:55:58","06-05-2025 17:50:45","07-05-2025 00:25=
:02","Grid outage, no space to deploy mobile gen on site // grid power retu=
rned","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Grid outage, no space to deploy mobile gen on site // grid power returned=
","cedric.tiani@matech-cameroun.com","314","06-05-2025 17:55:58","MATECH CM=
R"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0004963128","Mba=
nkomo CAF","","06-05-2025 17:54:44","06-05-2025 17:52:35","06-05-2025 18:36=
:08","Grid outage,gen ran till fuel shortage//refueling done","Fanda Brice"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran till=
 fuel shortage//refueling done","cedric.tiani@matech-cameroun.com","130","0=
6-05-2025 17:54:44","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004963097","B=
arriere","","06-05-2025 17:47:43","06-05-2025 17:41:31","06-05-2025 18:08:2=
5","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed//Grid return","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went d=
own because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and co=
nfirmed//Grid return","vanel.mbiada@matech-cameroun.com","373","06-05-2025 =
17:47:43","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004963032","Man=
guiers Dispensaire","","06-05-2025 17:36:19","06-05-2025 17:30:07","06-05-2=
025 17:50:00","Active // No power issue site on grid with U=3D54,8 V Tx Fme=
 Armand Ngestsa (691144412) of huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active // No power issue site on grid with U=3D54,8 V Tx Fme Armand N=
gestsa (691144412) of huawei is informed","cedric.tiani@matech-cameroun.com=
","373","06-05-2025 17:36:19","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004962946","C=
RF Nkoabang","","06-05-2025 17:19:39","06-05-2025 17:01:09","07-05-2025 09:=
31:55","Solar only site: site down due to sunset // Grid restoration","Mba =
Lazare Herve","Equipment Repair","Passive","Solar","Solar Control Panel Boa=
rd","Solar only site: site down due to sunset // Solar Return or Grid","van=
el.mbiada@matech-cameroun.com","1111","06-05-2025 17:19:39","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0004962861","Eto=
ug-Ebe 2","","06-05-2025 17:00:43","06-05-2025 16:54:30","07-05-2025 09:13:=
27","Grid outage;No space to deploy mobil Gen awaiting Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
;No space to deploy mobil Gen awaiting Grid return","cedric.tiani@matech-ca=
meroun.com","374","06-05-2025 17:00:43","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004962825","Nko=
abang Alembe","","06-05-2025 16:54:25","06-05-2025 16:49:14","06-05-2025 17=
:00:00","ACTIVE// No power issue on site Ubaie=3D53.3V site on Gen Lionel A=
djep/655-18-48-76 from Huawei is informed.Noticed impacted by Ayongoum","Mb=
a Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fai=
lure","Affected by 3rd Party Site","ACTIVE// No power issue on site Ubaie=
=3D53.3V site on Gen Lionel Adjep/655-18-48-76 from Huawei is informed.Noti=
ced impacted by Ayongoum","cedric.tiani@matech-cameroun.com","312","06-05-2=
025 16:54:25","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004962745","Men=
dong NB","","06-05-2025 16:36:02","06-05-2025 16:32:48","06-05-2025 16:55:3=
9","No power issue on site, Ubaie: 53.3V Site on Grid with The Tx Fme Mbah =
hosiah(?+237 6 99 69 96 94) from Huawei is informed","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site, Ubaie: 53.3V Site on Grid with The Tx Fme Mbah hosiah(?+23=
7 6 99 69 96 94) from Huawei is informed","cedric.tiani@matech-cameroun.com=
","195","06-05-2025 16:36:02","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004962711","Meh=
anda 1","","06-05-2025 16:32:43","06-05-2025 16:28:30","06-05-2025 18:08:52=
"," Grid outage gen failed to start due to ATS faulty//He manually started =
the  Gen	","Albran Byorel","Equipment Repair","Passive","Control Panel","AT=
S-AMF Issue"," Grid outage gen failed to start due to ATS faulty//He manual=
ly started the  Gen	","cedric.tiani@matech-cameroun.com","254","06-05-2025 =
16:32:43","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0004962635","C=
rf Cornier","","06-05-2025 16:22:06","06-05-2025 16:17:58","06-05-2025 16:2=
6:41","Active, No power issue site on battery with U=3D54.3VTX FME Armand N=
gestsa (691144412)From huawei is informed","MINKA NICOLAS","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve, No power issue site on battery with U=3D54VTX FME Armand Ngestsa (69114=
4412)From huawei is informed","vanel.mbiada@matech-cameroun.com","249","06-=
05-2025 16:22:06","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004962177","N=
kolo II New","","06-05-2025 15:07:03","06-05-2025 15:02:55","06-05-2025 16:=
08:48","Active/ No power issue site on Gen with U=3D53.5V The FME Tx Lionel=
 Steve /655184876/ From huawei is informed.","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active/ No power issue site on Gen with U=3D53.5V The FME Tx Lionel Steve =
/655184876/ From huawei is informed.","vanel.mbiada@matech-cameroun.com","2=
50","06-05-2025 15:07:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004962145","MEHANDAN=
","","06-05-2025 15:00:11","06-05-2025 14:51:06","06-05-2025 15:44:14","Cas=
caded Incident from TTO5085713","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site went down because Gen=
 failed to start due to controller ZTE faulty //He manually started the Gen=
","system","270633","06-05-2025 15:00:11","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004962144","O=
dza II OCM","IHS_YND_528","06-05-2025 14:59:24","06-05-2025 14:51:06","06-0=
5-2025 15:44:14","Grid outage,site went down because Gen failed to start du=
e to controller ZTE faulty //He manually started the Gen","Albran Byorel","=
Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,si=
te went down because Gen failed to start due to controller ZTE faulty //He =
manually started the Gen","vanel.mbiada@matech-cameroun.com","500","06-05-2=
025 14:59:24","MATECH CMR"
"Closed Complete","Site Down","CTR_201","IHS_YND_368","NOCINC0004961671","O=
tele","IHS_YND_370, IHS_YND_369, IHS_YND_371, IHS_YND_372","06-05-2025 14:0=
6:32","06-05-2025 14:02:17","06-05-2025 14:07:46","Grid outage,site went do=
wn because Gen failed to start due to Grid contactor not excited //He bypas=
sed it and maually started the Gen","Fanda Brice","Equipment Repair","Passi=
ve","Control Panel","ATS-AMF Issue","Grid outage,site went down because Gen=
 failed to start due to Grid contactor not excited //He bypassed it and mau=
ally started the Ge","gerard.tchangoue@matech-cameroun.com","255","06-05-20=
25 14:06:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004961649","Bondjock=
","","06-05-2025 14:04:29","06-05-2025 14:02:17","06-05-2025 14:07:46","Cas=
caded Incident from TTO5085122 - Cascade Removed From TTO5085122","Fanda Br=
ice","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid o=
utage,site went down because Gen failed to start due to Grid contactor not =
excited //He bypassed it and maually started the Ge","system","266377","06-=
05-2025 14:04:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004961648","Minka","=
","06-05-2025 14:04:28","06-05-2025 14:02:17","06-05-2025 14:07:46","Cascad=
ed Incident from TTO5085122 - Cascade Removed From TTO5085122","Fanda Brice=
","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid outa=
ge,site went down because Gen failed to start due to Grid contactor not exc=
ited //He bypassed it and maually started the Ge","system","266376","06-05-=
2025 14:04:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004961647","Mbeng","=
","06-05-2025 14:04:28","06-05-2025 14:02:17","06-05-2025 14:07:46","Cascad=
ed Incident from TTO5085122 - Cascade Removed From TTO5085122","Fanda Brice=
","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid outa=
ge,site went down because Gen failed to start due to Grid contactor not exc=
ited //He bypassed it and maually started the Ge","system","266376","06-05-=
2025 14:04:28","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004961613","N=
yom OCM","","06-05-2025 14:00:05","06-05-2025 13:50:59","06-05-2025 14:40:1=
7","Grid outage, Site went down because gen started and stopped due to air =
intake causing by pierced fuel pipe // He normalized fuel pipe and gen manu=
ally started","Fabrice Pouakam","Fuel Outage (Probable)","Passive","ACDG Ge=
n","ACDG - Air Intake","Grid outage, Site went down because gen started and=
 stopped due to air intake causing by pierced fuel pipe // He normalized fu=
el pipe and gen manually started","gerard.tchangoue@matech-cameroun.com","5=
47","06-05-2025 14:00:05","MATECH CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004961595","M=
om","","06-05-2025 13:58:21","06-05-2025 14:02:17","06-05-2025 14:07:46","S=
ite impacted by OTELE","Fanda Brice","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage,site went down because Gen failed to =
start due to Grid contactor not excited //He bypassed it and maually starte=
d the Ge","gerard.tchangoue@matech-cameroun.com","266377","06-05-2025 13:58=
:21","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004961474","ODZ=
A MINKAN EDIBI ASSI","","06-05-2025 13:35:44","06-05-2025 13:34:32","06-05-=
2025 14:33:40","Grid outage,site went down because Gen started and stopped =
with alarm *overvoltage*//He manually started the Gen","Albran Byorel","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,sit=
e went down because Gen started and stopped with alarm *overvoltage*//He ma=
nually started the Gen","edwige.kapawo@matech-cameroun.com","73","06-05-202=
5 13:35:44","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0004961467","M=
fou EPC","","06-05-2025 13:34:24","06-05-2025 13:29:17","06-05-2025 15:07:3=
6","Grid outage,site went down because Gen failed to start due to Grid  con=
tactor faulty //He bypassed it and manually started the Gen","Mba Lazare He=
rve","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid out=
age,site went down because Gen failed to start due to Grid  contactor fault=
y //He bypassed it and manually started the Gen","gerard.tchangoue@matech-c=
ameroun.com","309","06-05-2025 13:34:24","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004961352","B=
arriere","","06-05-2025 13:11:48","06-05-2025 11:58:31","06-05-2025 13:12:0=
6","Active//No power issue on site Ubay: 54.51V site on Grid Henry (6999496=
93/Huawei) is informed","Hyemafo Gildas","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue=
 on site Ubay: 54.51V site on Grid Henry (699949693/Huawei) is informed","g=
erard.tchangoue@matech-cameroun.com","4398","06-05-2025 13:11:48","MATECH C=
MR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004960607","Bri=
quetterie","","06-05-2025 11:19:48","06-05-2025 11:14:59","06-05-2025 15:02=
:48","Grid Only, No space to deploy // Grid power restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space=
 to deploy // Grid power restore","edwige.kapawo@matech-cameroun.com","290"=
,"06-05-2025 11:19:48","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004960477","M=
ANGUIERS CHAPELLE","IHS_YND_506","06-05-2025 10:52:36","06-05-2025 10:46:02=
","06-05-2025 22:08:51","	Grid outage, site went down due to gen overload (=
22kva, 340A) SS HISBernard ATANGANA is informed and confirmed// Site stabli=
sed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","	Grid outage, site went down due to gen overload (22kva, 340A) SS HI=
SBernard ATANGANA is informed and confirmed// Site stablised","gerard.tchan=
goue@matech-cameroun.com","395","06-05-2025 10:52:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004960254","MBIMBIM"=
,"","06-05-2025 10:28:41","06-05-2025 08:42:46","06-05-2025 09:42:50","Casc=
aded Incident from TTO5082826","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Our Engineer Felix ATANGANA -- 691145560/I=
ENG is informed and reverts No power issue, site on GEN, U=3D49.2V. TX FME =
Abdouraman 657959647 / Huawei is informed","system","271352","06-05-2025 10=
:28:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0004960249","Yoko OCM=
","","06-05-2025 10:28:40","06-05-2025 08:42:46","06-05-2025 09:42:50","Cas=
caded Incident from TTO5082826","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Our Engineer Felix ATANGANA -- 691145560/=
IENG is informed and reverts No power issue, site on GEN, U=3D49.2V. TX FME=
 Abdouraman 657959647 / Huawei is informed","system","271356","06-05-2025 1=
0:28:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004960250","Ngouetou=
","","06-05-2025 10:28:40","06-05-2025 08:42:46","06-05-2025 09:42:50","Cas=
caded Incident from TTO5082826","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Our Engineer Felix ATANGANA -- 691145560/=
IENG is informed and reverts No power issue, site on GEN, U=3D49.2V. TX FME=
 Abdouraman 657959647 / Huawei is informed","system","271361","06-05-2025 1=
0:28:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004960248","Matsari"=
,"","06-05-2025 10:28:39","06-05-2025 08:42:46","06-05-2025 09:42:50","Casc=
aded Incident from TTO5082826","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Our Engineer Felix ATANGANA -- 691145560/I=
ENG is informed and reverts No power issue, site on GEN, U=3D49.2V. TX FME =
Abdouraman 657959647 / Huawei is informed","system","271355","06-05-2025 10=
:28:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004960240","Ngoum","=
","06-05-2025 10:28:38","06-05-2025 08:42:46","06-05-2025 09:42:50","Cascad=
ed Incident from TTO5082826","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Our Engineer Felix ATANGANA -- 691145560/IEN=
G is informed and reverts No power issue, site on GEN, U=3D49.2V. TX FME Ab=
douraman 657959647 / Huawei is informed","system","271349","06-05-2025 10:2=
8:38","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004960202","NKO=
MKANA ELIZA HOTEL","","06-05-2025 10:23:31","06-05-2025 10:18:19","06-05-20=
25 10:32:02","Active//No power issue, Site on Grid Ubaie: 53.3V. The Tx FME=
 Brice Tsague(650214096) from Huawei is informed.","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue, Site on Grid Ubaie: 53.3V. The Tx FME Brice Tsague(650214096=
) from Huawei is informed.","edwige.kapawo@matech-cameroun.com","313","06-0=
5-2025 10:23:31","MATECH CMR"
"Closed Complete","Site Down","T0535","IHS_YND_234","NOCINC0004960178","Oyo=
mabang MTN","","06-05-2025 10:19:32","06-05-2025 10:15:03","06-05-2025 10:2=
5:49","Site went down due to 3 rectifiers burnt causing by Grid fluctuation=
//we replace these rectifiers site on grid","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module","Site went down due=
 to 3 rectifiers burnt causing by Grid fluctuation//we replace these rectif=
iers site on grid","edwige.kapawo@matech-cameroun.com","269","06-05-2025 10=
:19:32","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004960125","C=
RF Nkoabang","","06-05-2025 10:14:45","06-05-2025 10:08:59","06-05-2025 10:=
24:59","Solar Grid Only site down due to grid outage No space for mobile ge=
n // Grid return","Mba Lazare Herve","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Solar Grid Only site down due to grid outage =
No space for mobile gen // Grid return","gerard.tchangoue@matech-cameroun.c=
om","347","06-05-2025 10:14:45","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004960022","B=
arriere","","06-05-2025 10:02:45","06-05-2025 09:53:59","06-05-2025 11:49:1=
8","Site went Down because Gildas (656040578/Matech) was on site for work (=
 PM) // End of works","Hyemafo Gildas","Equipment Replacement","Passive","P=
lanned Activity","Planned Activity - Passive","Site went Down because Gilda=
s (656040578/Matech) was on site for work ( PM) // End of works","gerard.tc=
hangoue@matech-cameroun.com","527","06-05-2025 10:02:45","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004959899","Cit=
e des nations","","06-05-2025 09:44:17","06-05-2025 09:42:10","06-05-2025 0=
9:48:10","Grid outage,site went down before Gen started due to Poor battery=
 backup//Gen automatically started","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage,site went do=
wn before Gen started due to Poor battery backup//Gen automatically started=
","edwige.kapawo@matech-cameroun.com","128","06-05-2025 09:44:17","MATECH C=
MR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004959751","SIM=
BOCK BONAMBAPE","","06-05-2025 09:25:06","06-05-2025 09:19:55","06-05-2025 =
09:27:59","Active//No power issue Ubaie: 54.15V site on Grid.The FME TX Mba=
h Hosiah (674007438/699699694) from Huawei is informed. ","Hyemafo Gildas",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active//No power issue Ubaie: 54.15V site on Grid.The FME TX Mb=
ah Hosiah (674007438/699699694) from Huawei is informed. ","edwige.kapawo@m=
atech-cameroun.com","312","06-05-2025 09:25:06","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004959495","M=
ANGUIERS CHAPELLE","","06-05-2025 08:35:15","06-05-2025 08:25:59","06-05-20=
25 09:57:59","site went down due to gen overload (22kva, 340A) SS HISBernar=
d ATANGANA is informed and confirmed // Site stabilised","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","site went down d=
ue to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and con=
firmed // Site stabilised","edwige.kapawo@matech-cameroun.com","558","06-05=
-2025 08:35:15","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004959402","SAA=
 Entrance","","06-05-2025 08:15:28","06-05-2025 08:11:17","06-05-2025 08:16=
:27","Site Went Down because AHANDA (697487490/Matech) was on site to works=
 (Re-establishment of the Eneo phases) // End of work","Parker Tchoup","Equ=
ipment Replacement","Passive","Planned Activity","Planned Activity - Passiv=
e","Site Went Down because AHANDA (697487490/Matech) was on site to works (=
Re-establishment of the Eneo phases) // End of work","edwige.kapawo@matech-=
cameroun.com","253","06-05-2025 08:15:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004959336","Bastos B=
ir","","06-05-2025 08:00:03","06-05-2025 07:56:33","06-05-2025 11:00:56","C=
ascaded Incident from TTO5082605","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because rectifiers cr=
ashed // rectifier reset ","system","273989","06-05-2025 08:00:03","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004959337","ARMP",""=
,"06-05-2025 08:00:03","06-05-2025 07:56:33","06-05-2025 11:00:56","Cascade=
d Incident from TTO5082605","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down because rectifiers crashed // rectifier =
reset ","system","273989","06-05-2025 08:00:03","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004959331","D=
ragage","IHS_YND_704, IHS_YND_208","06-05-2025 07:58:41","06-05-2025 07:56:=
33","06-05-2025 11:00:56","Site went down because rectifiers crashed // rec=
tifier reset ","Mboua Thierry","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down because rectifiers crashed // rectifier res=
et ","edwige.kapawo@matech-cameroun.com","129","06-05-2025 07:58:41","MATEC=
H CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004959187","Bri=
quetterie","","06-05-2025 07:20:33","06-05-2025 07:02:25","06-05-2025 10:24=
:44","Grid outage, no space to deploy MGE // Grid returned","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spa=
ce to deploy MGE // Grid returned","edwige.kapawo@matech-cameroun.com","108=
9","06-05-2025 07:20:33","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004959133","B=
arriere","","06-05-2025 07:01:24","06-05-2025 06:26:15","06-05-2025 09:41:2=
0","(Very Unstable) Grid outage, Site went down because Gen overload(20kva,=
400 A) IHS SS Felix Zambe is informed and confirmed // Grid return","Hyemaf=
o Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","(Very =
Unstable) Grid outage, Site went down because Gen overload(20kva,400 A) IHS=
 SS Felix Zambe is informed and confirmed // Grid return","kouoh.jean@ihsto=
wers.com","2110","06-05-2025 07:01:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004958963","Nkongtoc=
k","","06-05-2025 06:06:41","06-05-2025 05:54:33","06-05-2025 06:54:33","Ca=
scaded Incident from TTO5082144","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issues iste on Grid w=
ith U=3D54.1V ,The FME TX Fulbert (654266068) from Huawei is informed","sys=
tem","274205","06-05-2025 06:06:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004958962","Angongo"=
,"","06-05-2025 06:06:41","06-05-2025 05:54:33","06-05-2025 06:54:33","Casc=
aded Incident from TTO5082144","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issues iste on Grid with U=
=3D54.1V ,The FME TX Fulbert (654266068) from Huawei is informed","system",=
"274209","06-05-2025 06:06:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004958958","Ebeba","=
","06-05-2025 06:06:40","06-05-2025 05:54:33","06-05-2025 06:54:33","Cascad=
ed Incident from TTO5082144","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issues iste on Grid with U=3D=
54.1V ,The FME TX Fulbert (654266068) from Huawei is informed","system","27=
4205","06-05-2025 06:06:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004958956","Nkenglik=
ok","","06-05-2025 06:06:40","06-05-2025 05:54:33","06-05-2025 06:54:33","C=
ascaded Incident from TTO5082144","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issues iste on Grid =
with U=3D54.1V ,The FME TX Fulbert (654266068) from Huawei is informed","sy=
stem","274205","06-05-2025 06:06:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004958961","Mambine"=
,"","06-05-2025 06:06:40","06-05-2025 05:54:33","06-05-2025 06:54:33","Casc=
aded Incident from TTO5082144","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issues iste on Grid with U=
=3D54.1V ,The FME TX Fulbert (654266068) from Huawei is informed","system",=
"274206","06-05-2025 06:06:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004958960","OKOA Pea=
ge","","06-05-2025 06:06:40","06-05-2025 05:54:33","06-05-2025 06:54:33","C=
ascaded Incident from TTO5082144","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issues iste on Grid with=
 U=3D54.1V ,The FME TX Fulbert (654266068) from Huawei is informed","system=
","274208","06-05-2025 06:06:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004958959","Nomayos-=
IHS","","06-05-2025 06:06:40","06-05-2025 05:54:33","06-05-2025 06:54:33","=
Cascaded Incident from TTO5082144","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active//No power issues iste on Grid wit=
h U=3D54.1V ,The FME TX Fulbert (654266068) from Huawei is informed","syste=
m","274207","06-05-2025 06:06:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004958955","Mbankomo=
 IHS","","06-05-2025 06:06:39","06-05-2025 05:54:33","06-05-2025 06:54:33",=
"Cascaded Incident from TTO5082144","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issues iste on Grid wi=
th U=3D54.1V ,The FME TX Fulbert (654266068) from Huawei is informed","syst=
em","274208","06-05-2025 06:06:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004958954","Mandoumb=
a OCM","","06-05-2025 06:06:39","06-05-2025 05:54:33","06-05-2025 06:54:33"=
,"Cascaded Incident from TTO5082144","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issues iste on Gr=
id with U=3D54.1V ,The FME TX Fulbert (654266068) from Huawei is informed",=
"system","274207","06-05-2025 06:06:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004958953","Sous Pre=
fecture","","06-05-2025 06:06:39","06-05-2025 05:54:33","06-05-2025 06:54:3=
3","Cascaded Incident from TTO5082144","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active//No power issues iste on Grid=
 with U=3D54.1V ,The FME TX Fulbert (654266068) from Huawei is informed","s=
ystem","274206","06-05-2025 06:06:39","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004958937","N=
omayos montee Meche","","06-05-2025 06:02:34","06-05-2025 05:54:33","06-05-=
2025 08:28:39","Active//No power issues iste on Grid with U=3D54.1V ,The FM=
E TX Fulbert (654266068) from Huawei is informed","Fanda Brice","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","Active//No power issues i=
ste on Grid with U=3D54.1V ,The FME TX Fulbert (654266068) from Huawei is i=
nformed","gaelle.njiofack@matech-cameroun.com","274208","06-05-2025 06:02:3=
4","MATECH CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004958926","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_791, I=
HS_YND_339, IHS_YND_697, IHS_YND_330, IHS_YND_350, IHS_YND_335, IHS_YND_349=
","06-05-2025 05:58:40","06-05-2025 05:54:33","06-05-2025 08:34:16","Active=
//No power issues iste on Grid with U=3D54.1V ,The FME TX Fulbert (65426606=
8) from Huawei is informed","Fanda Brice","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issu=
es iste on Grid with U=3D54.1V ,The FME TX Fulbert (654266068) from Huawei =
is informed","gaelle.njiofack@matech-cameroun.com","248","06-05-2025 05:58:=
40","MATECH CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004958324","Bri=
quetterie","","06-05-2025 01:06:13","06-05-2025 00:57:53","06-05-2025 02:21=
:42","Grid outage, no space to deploy MGE // Grid returned","","Grid Supply=
","Passive","Grid","National Grid - Grid Over Voltage","Grid outage, no spa=
ce to deploy MGE // Grid returned","loic.noumsi@matech-cameroun.com","501",=
"06-05-2025 01:06:13","MATECH CMR"
"Closed Complete","Site Down","CTR_115","IHS_YND_375","NOCINC0004958255","N=
goung","","06-05-2025 00:46:32","06-05-2025 00:38:16","06-05-2025 03:02:15"=
,"Grid outage, Site went down because gen stopped with alarm high temp // H=
e added water in radiator","Kemeni Franklin","Equipment Repair","Passive","=
ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Sit=
e went down because gen stopped with alarm high temp // He added water in r=
adiator","loic.noumsi@matech-cameroun.com","497","06-05-2025 00:46:32","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004958038","C=
rf-Nsam","","05-05-2025 23:29:11","05-05-2025 23:14:58","06-05-2025 00:19:4=
4","No power issue on site Ubaie =3D52.4V site on Grid The TX FME Henri (69=
9949693) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site Ubaie =3D52.4V site on Grid The TX FME Henri (699949693) from Hua=
wei is informed","gaelle.njiofack@matech-cameroun.com","855","05-05-2025 23=
:29:11","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004957979","Oko=
lo Kilombo","","05-05-2025 23:16:22","05-05-2025 21:39:14","06-05-2025 00:0=
3:06","No power issue Ubaie:54.7 V site on Grid The TX FME Synphorien (6752=
95205) from Huawei is informed.","Fabrice Pouakam","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue Ubaie:54.7 V site on Grid The TX FME Synphorien (675295205) from Huawei =
is informed.","loic.noumsi@matech-cameroun.com","5829","05-05-2025 23:16:22=
","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0004957883","Eto=
ug-Ebe 2","","05-05-2025 22:49:41","05-05-2025 22:40:36","06-05-2025 16:26:=
19","Grid only no space to deploy MDG//Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid only no space to deplo=
y MDG//Grid return","cedric.tiani@matech-cameroun.com","546","05-05-2025 22=
:49:41","MATECH CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0004957865","Nko=
mkana","","05-05-2025 22:45:09","05-05-2025 22:37:02","05-05-2025 22:46:20"=
,"Grid Only, No space to deploy // Grid return","","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid Only, No space to deploy /=
/ Grid return","cedric.tiani@matech-cameroun.com","488","05-05-2025 22:45:0=
9","MATECH CMR"
"Closed Complete","Site Down","T2292","IHS_YND_453","NOCINC0004957741","Son=
g-bong","","05-05-2025 22:15:14","05-05-2025 21:13:46","05-05-2025 23:34:57=
","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid outage, site went down due to generator board fuse popped =
// he made the fuse bridge, site on Gen","olivier.kwedi@ihstowers.com","276=
635","05-05-2025 22:15:14","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0004957670","Mai=
son komkana New","","05-05-2025 21:59:21","05-05-2025 21:19:07","05-05-2025=
 22:48:00","Access issues during the night // Site stabilised","Mboua Thier=
ry","Access Denial","Access","Access","Access - Key Lock","Access issues du=
ring the night // Site stabilised","cedric.tiani@matech-cameroun.com","2414=
","05-05-2025 21:59:21","MATECH CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0004957663","C=
NDH","","05-05-2025 21:56:56","05-05-2025 21:24:40","05-05-2025 22:02:34","=
Ticket error","Paul BIBOUM","Incorrectly Logged Tickets","Error","Error","E=
rror","Ticket error","ludivine.ngamaleu@ihstowers.com","1937","05-05-2025 2=
1:56:56","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004957659","Fla=
menco","","05-05-2025 21:55:54","05-05-2025 21:48:26","05-05-2025 22:32:40"=
,"Access issues during the night // Grid returned","Mboua Thierry","Access =
Denial","Access","Access","Access - Key Lock","Access issues during the nig=
ht // Grid returned","cedric.tiani@matech-cameroun.com","448","05-05-2025 2=
1:55:54","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004957589","ODZ=
A MINKAN EDIBI ASSI","","05-05-2025 21:40:30","05-05-2025 21:33:21","05-05-=
2025 21:43:43","Grid fluctuation, Site went down because Gen failed to star=
t  due to Grid bad voltag and No RCP on site // Grid return","Albran Byorel=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation, Site went down because Gen failed to start  due to Grid =
bad voltag and No RCP on site // Grid return","cedric.tiani@matech-cameroun=
.com","430","05-05-2025 21:40:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004957498","Eseka To=
wn","","05-05-2025 21:22:07","05-05-2025 21:13:46","05-05-2025 23:34:57","C=
ascaded Incident from TTO5080448","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 generator board fuse popped // he made the fuse bridge, site on Gen","syst=
em","276635","05-05-2025 21:22:07","MATECH CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0004957486","Ese=
ka MTN","IHS_YND_453, IHS_YND_378","05-05-2025 21:20:02","05-05-2025 21:13:=
46","05-05-2025 23:34:57","Grid outage, site went down due to generator boa=
rd fuse popped // he made the fuse bridge, site on Gen","Kemeni Franklin","=
Equipment Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid outage, =
site went down due to generator board fuse popped // he made the fuse bridg=
e, site on Gen","cedric.tiani@matech-cameroun.com","377","05-05-2025 21:20:=
02","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004957339","O=
dza II OCM","","05-05-2025 20:54:51","05-05-2025 20:51:58","05-05-2025 21:0=
0:10","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // He reseted controller and gen manually started","Albran B=
yorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overloade=
d","Grid outage, site went down because gen failed to start due to PWC ZTE =
malfunction // He reseted controller and gen manually started","vanel.mbiad=
a@matech-cameroun.com","175","05-05-2025 20:54:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0004957243","Mvog-Man=
ga","","05-05-2025 20:39:48","05-05-2025 20:31:50","05-05-2025 21:19:05","C=
ascaded Incident from TTO5080157","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to CB ((125A) dis=
juncted at OCM =E9quipements//CB rearmed","system","314933","05-05-2025 20:=
39:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0004957244","Marche O=
dza","","05-05-2025 20:39:48","05-05-2025 20:31:50","05-05-2025 21:19:05","=
Cascaded Incident from TTO5080157","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to CB ((125A) di=
sjuncted at OCM =E9quipements//CB rearmed","system","314933","05-05-2025 20=
:39:48","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004957235","O=
dza","IHS_YND_254, IHS_YND_580","05-05-2025 20:39:00","05-05-2025 20:31:50"=
,"05-05-2025 21:19:05","Site went down due to CB ((125A) disjuncted at OCM =
=E9quipements//CB rearmed","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to=
 CB ((125A) disjuncted at OCM =E9quipements//CB rearmed","vanel.mbiada@mate=
ch-cameroun.com","431","05-05-2025 20:39:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004956997","Bastos B=
ethesda","","05-05-2025 20:14:08","05-05-2025 20:07:24","07-05-2025 01:32:4=
1","Cascaded Incident from TTO5079873 - Cascade Removed From TTO5079873","M=
boua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","Grid outage, site went down due to grid fluctuations // SITE stabilised"=
,"system","404","05-05-2025 20:14:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0004956995","Bastos-N=
ylon","","05-05-2025 20:14:07","05-05-2025 20:07:04","05-05-2025 21:16:30",=
"Cascaded Incident from TTO5079873 - Cascade Removed From TTO5079873","Mbou=
a Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid outage, gen failed to start due to Gen overload(17kva,200A) SS IHS BER=
NARD IS INFORMED // He reduce the load and manually start the Gen","system"=
,"273284","05-05-2025 20:14:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004956994","Golf Qua=
ter","","05-05-2025 20:14:07","05-05-2025 20:07:04","05-05-2025 21:16:30","=
Cascaded Incident from TTO5079873 - Cascade Removed From TTO5079873","Mboua=
 Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage, gen failed to start due to Gen overload(17kva,200A) SS IHS BERN=
ARD IS INFORMED // He reduce the load and manually start the Gen","system",=
"273283","05-05-2025 20:14:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_282","NOCINC0004956993","Meyo",""=
,"05-05-2025 20:14:07","05-05-2025 20:07:24","05-05-2025 20:56:21","Grid fl=
uctuation  site went down because  gen failed to start due to Grid bad volt=
age , no rcp//He bypassed grid and started the gen","Hyemafo Gildas","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation  site went down because  gen failed to start due to Grid bad volt=
age , no rcp//He bypassed grid and started the gen","system","403","05-05-2=
025 20:14:07","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004956972","T=
singa","","05-05-2025 20:12:40","05-05-2025 20:07:04","05-05-2025 21:16:30"=
,"","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, gen failed to start due to Gen overload(17kva,200A) S=
S IHS BERNARD IS INFORMED // He reduce the load and manually start the Gen"=
,"vanel.mbiada@matech-cameroun.com","273283","05-05-2025 20:12:40","MATECH =
CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004956961","N=
komkana 2","IHS_YND_220, IHS_YND_126, IHS_YND_127","05-05-2025 20:11:19","0=
5-05-2025 20:07:04","05-05-2025 21:16:30","Grid outage, gen failed to start=
 due to Gen overload(17kva,200A) SS IHS BERNARD IS INFORMED // He reduce th=
e load and manually start the Gen","Mboua Thierry","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid outage, gen failed to start due to =
Gen overload(17kva,200A) SS IHS BERNARD IS INFORMED // He reduce the load a=
nd manually start the Gen","vanel.mbiada@matech-cameroun.com","256","05-05-=
2025 20:11:19","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004956771","NKO=
MKANA ELIZA HOTEL","","05-05-2025 19:49:13","05-05-2025 19:40:00","05-05-20=
25 22:46:57","Grid outage no space to deploy MGE on site // Grid power retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage no space to deploy MGE on site // Grid power return","cedric.ti=
ani@matech-cameroun.com","554","05-05-2025 19:49:13","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004956697","B=
ATA Mokolo OCM","","05-05-2025 19:39:57","05-05-2025 19:34:33","05-05-2025 =
22:44:40","Grid only site and no space to deploy // Grid returned","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only si=
te and no space to deploy // Grid returned","vanel.mbiada@matech-cameroun.c=
om","325","05-05-2025 19:39:57","MATECH CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004956518","V=
allee-Bastos OCM","","05-05-2025 19:04:32","05-05-2025 04:48:59","05-05-202=
5 04:49:14","BACKTRACKING Active: no power issue, site is on grid with Ubai=
e=3D52.3V, Armand Nguetsa(691144412) from Huawei is informed","","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active: no power issue, site is on grid with Ubaie=3D52.3V, Armand Nguets=
a(691144412) from Huawei is informed","cedric.tiani@matech-cameroun.com","5=
1334","05-05-2025 19:04:32","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004956507","M=
ontee-Jouvence-II","","05-05-2025 19:02:48","05-05-2025 10:25:26","05-05-20=
25 10:30:23","BACKTRACKING  ACTIVE// No power issue on site, site on Grid w=
ith Ubaie=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is inform=
ed","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","ACTIVE// No power issue on site, site on G=
rid with Ubaie=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is i=
nformed","cedric.tiani@matech-cameroun.com","31043","05-05-2025 19:02:48","=
MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004956475","MBA=
LNGONG LYCEE","","05-05-2025 18:58:31","05-05-2025 18:55:23","05-05-2025 19=
:25:56"," Site went down because Gen stopped due to overload(9kva, 130A) SS=
 IHS Felix Zambe is informed and confirmed //Grid return","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload"," Site went down bec=
ause Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe is informed=
 and confirmed //Grid return","cedric.tiani@matech-cameroun.com","189","05-=
05-2025 18:58:31","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004956268","Imm=
-Olympique","","05-05-2025 18:27:40","05-05-2025 15:38:31","05-05-2025 17:5=
0:39","ACTIVE// No power issue site on gen with U=3D52.7v The FME TX Brice =
stague(65072631) from HUAWEI is informed.","Paul BIBOUM","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE=
// No power issue site on gen with U=3D52.7v The FME TX Brice stague(650726=
31) from HUAWEI is informed.","cedric.tiani@matech-cameroun.com","10150","0=
5-05-2025 18:27:40","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004956224","M=
essassi okolo","","05-05-2025 18:21:15","05-05-2025 17:13:05","05-05-2025 1=
7:50:27","No power issue site on grid with U=3D54.4V Symphorien from huawei=
 is informed.Noticed site impacted by emana pont 	","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","Affected by 3r=
d Party Site","No power issue site on grid with U=3D54.4V Symphorien from h=
uawei is informed.Noticed site impacted by emana pont 	","cedric.tiani@mate=
ch-cameroun.com","4308","05-05-2025 18:21:15","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004956143","E=
kombitie","","05-05-2025 18:00:16","05-05-2025 17:41:03","05-05-2025 18:09:=
24"," no power issue, site is on Gen with Ubaie=3D54.6V, Symphorien(6502571=
51/ huawei) is informed","Fabrice Pouakam","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm"," no power issue, sit=
e is on Gen with Ubaie=3D54.6V, Symphorien(650257151/ huawei) is informed",=
"vanel.mbiada@matech-cameroun.com","1155","05-05-2025 18:00:16","MATECH CMR=
"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004955804","E=
MANA BILICK CITY","","05-05-2025 17:24:57","05-05-2025 17:13:55","05-05-202=
5 17:44:11","Grid outage,Site went down because Gen failed to start due to =
Main Gen faulty// Grid return","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Generator Faulty","Grid outage,Site went down because=
 Gen failed to start due to Main Gen faulty// Grid return","vanel.mbiada@ma=
tech-cameroun.com","664","05-05-2025 17:24:57","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004955779","Mes=
sassi 2","","05-05-2025 17:23:51","05-05-2025 17:14:59","05-05-2025 17:53:0=
2","Site went down because 04/06 rectifiers dysfuncionned// He reset rectif=
iers, site on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down because 04/06 rectifiers dysfuncionn=
ed// He reset rectifiers, site on Grid","cedric.tiani@matech-cameroun.com",=
"534","05-05-2025 17:23:51","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004955703","Nko=
abang Alembe","","05-05-2025 17:11:25","05-05-2025 17:02:59","05-05-2025 17=
:11:56","ACTIVE// No power issue on site Ubaie=3D54.2V site on Gen Lionel A=
djep/655-18-48-76 from Huawei  is informed.","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE// No power issue on site Ubaie=3D54.2V site on Gen Lionel Adjep/655=
-18-48-76 from Huawei  is informed.","cedric.tiani@matech-cameroun.com","50=
7","05-05-2025 17:11:25","MATECH CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0004955670","M=
BIMBIM","","05-05-2025 17:07:10","05-05-2025 16:53:24","05-05-2025 18:26:06=
","Active//No power issue on site Ubaie=3D49V, Site on battery, The Tx Fme =
Gregoire( 652070658)from Huawei is informe","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue on site Ubaie=3D49V, Site on battery, The Tx Fme Gregoi=
re( 652070658)from Huawei is informe","vanel.mbiada@matech-cameroun.com","8=
27","05-05-2025 17:07:10","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004955669","C=
RF Nkoabang","","05-05-2025 17:07:02","05-05-2025 16:49:35","06-05-2025 08:=
43:44","Solar Grid Only site down due to grid outage No space for mobile ge=
n // Grid return","Mba Lazare Herve","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Solar Grid Only site down due to grid outage =
No space for mobile gen // Grid return","ludivine.ngamaleu@ihstowers.com","=
1048","05-05-2025 17:07:02","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004955644","E=
mana Lycee","","05-05-2025 17:00:47","05-05-2025 16:54:30","05-05-2025 16:5=
5:57","WRONGLY CREATED TICKET","Fabrice Pouakam","Incorrectly Logged Ticket=
s","Error","Error","Error","WRONGLY CREATED TICKET","vanel.mbiada@matech-ca=
meroun.com","379","05-05-2025 17:00:47","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004955638","E=
mana lycee 2","","05-05-2025 16:59:55","05-05-2025 16:54:42","05-05-2025 17=
:12:06","Grid outage,site went down before Gen started due to poor Battery =
Backup//Gen automatically started","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage,site went=
 down before Gen started due to poor Battery Backup//Gen automatically star=
ted","vanel.mbiada@matech-cameroun.com","314","05-05-2025 16:59:55","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004955630","A=
wae Ewonkan","","05-05-2025 16:57:21","05-05-2025 16:52:08","05-05-2025 17:=
11:43","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid Restored","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid R=
estored","vanel.mbiada@matech-cameroun.com","314","05-05-2025 16:57:21","MA=
TECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004955615","Oko=
lo Kilombo","","05-05-2025 16:55:21","05-05-2025 14:10:09","05-05-2025 17:4=
7:51","Active //no power issue Ubaie:50.9 V site on GEN The TX FME Synphori=
en (675295205) from Huawei is informed.","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve //no power issue Ubaie:50.9 V site on GEN The TX FME Synphorien (6752952=
05) from Huawei is informed.","edwige.kapawo@matech-cameroun.com","9913","0=
5-05-2025 16:55:21","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004955591","E=
ssomba","","05-05-2025 16:51:56","05-05-2025 16:47:25","05-05-2025 17:21:38=
","Site went down due to 03/06 rectifiers on site// He reset it and site on=
 Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to 03/06 rectifiers on site// He reset it an=
d site on Grid","vanel.mbiada@matech-cameroun.com","272","05-05-2025 16:51:=
56","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004955530","Nko=
lfoulou","","05-05-2025 16:46:01","05-05-2025 16:43:47","05-05-2025 16:46:3=
2","Grid outage,site went down before DG start : Poor Batteries backup// Gr=
id return","Siligap Boris","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage,site went down before DG start : Po=
or Batteries backup// Grid return","cedric.tiani@matech-cameroun.com","134"=
,"05-05-2025 16:46:01","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004955525","Ebo=
go","","05-05-2025 16:45:19","05-05-2025 16:42:09","05-05-2025 16:49:43","G=
rid fluctuation site went down because Gen failed to start due to Grid bad =
voltage and poor battery backup // Grid return","Siligap Boris","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid fluct=
uation site went down because Gen failed to start due to Grid bad voltage a=
nd poor battery backup // Grid return","cedric.tiani@matech-cameroun.com","=
191","05-05-2025 16:45:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004955481","Yoko MTN=
","","05-05-2025 16:36:18","05-05-2025 16:31:54","05-05-2025 17:21:41","","=
Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid outage, site went down due to Huawei bay malfunction // he reseted=
 Huawei controller and put site on GEn","system","293514","05-05-2025 16:36=
:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004955480","Matsari"=
,"IHS_YND_475, IHS_YND_473","05-05-2025 16:36:18","05-05-2025 16:31:54","05=
-05-2025 17:21:41","Grid outage, site went down due to Huawei bay malfuncti=
on // he reseted Huawei controller and put site on GEn","Parker Tchoup","Eq=
uipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, sit=
e went down due to Huawei bay malfunction // he reseted Huawei controller a=
nd put site on GEn","system","264","05-05-2025 16:36:18","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0004955467","Ngo=
um","","05-05-2025 16:35:03","05-05-2025 16:31:54","05-05-2025 17:21:41",""=
,"Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage, site went down due to Huawei bay malfunction // he reset=
ed Huawei controller and put site on GEn","cedric.tiani@matech-cameroun.com=
","293513","05-05-2025 16:35:03","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004955126","ODZ=
A MINKAN EDIBI ASSI","","05-05-2025 15:59:58","05-05-2025 15:58:17","05-05-=
2025 18:17:33","Grid outage,site went down because Gen started and stopped =
with alarm *overvoltage*//He manually started the Gen","Albran Byorel","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,sit=
e went down because Gen started and stopped with alarm *overvoltage*//He ma=
nually started the Gen","cedric.tiani@matech-cameroun.com","102","05-05-202=
5 15:59:58","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004955121","S=
imbock OCM","","05-05-2025 15:58:46","05-05-2025 15:54:09","05-05-2025 16:1=
9:43","Grid Outage, site went down because Gen started and  stopped with ""=
high temp"" alarm//He added water and manually started the Gen","Hyemafo Gi=
ldas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Co=
olant Level Issue","Grid Outage, site went down because Gen started and  st=
opped with ""high temp"" alarm//He added water and manually started the Gen=
","vanel.mbiada@matech-cameroun.com","278","05-05-2025 15:58:46","MATECH CM=
R"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004955059","Eko=
umdoum OCM","","05-05-2025 15:46:14","05-05-2025 15:38:03","05-05-2025 17:3=
5:08"," site went down due to Gen overload(20kva,280 A) IHS SS Pascaline is=
 informed and confirmed//Grid return","Albran Byorel","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload"," site went down due to Gen overload(2=
0kva,280 A) IHS SS Pascaline is informed and confirmed//Grid return","cedri=
c.tiani@matech-cameroun.com","492","05-05-2025 15:46:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004954964","MEHANDAN=
","","05-05-2025 15:41:36","05-05-2025 15:36:24","05-05-2025 16:46:21","sit=
e went down due to water infiltration in th=E9 tank//We purged and gen manu=
ally started","Albran Byorel","Fuel Outage (Probable)","Passive","Diesel","=
Tank Sealing Issue - Water In The Fuel","site went down due to water infilt=
ration in th=E9 tank//We purged and gen manually started","system","312","0=
5-05-2025 15:41:36","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004954959","O=
dza II OCM","","05-05-2025 15:40:48","05-05-2025 15:36:24","05-05-2025 15:4=
4:34","Grid outage,Site went Down due to controller ZTE faulty  // He manua=
lly started the Gen","Albran Byorel","Equipment Repair","Passive","Control =
Panel","ATS-AMF Issue","Grid outage,Site went Down due to controller ZTE fa=
ulty  // He manually started the Gen","vanel.mbiada@matech-cameroun.com","2=
65","05-05-2025 15:40:48","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004954839","Mvo=
g-Manga","","05-05-2025 15:32:38","05-05-2025 15:27:29","05-05-2025 15:58:4=
3","Grid outage, Gen  started  and stopped due to alarm *overvoltage* //he =
reduced the load, reset the Gen card and maually started the Gen","Albran B=
yorel","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","grid =
outage,ge start and stopped due to water mixed with fuel in tank//he purged=
 it and started the ge","cedric.tiani@matech-cameroun.com","311","05-05-202=
5 15:32:38","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004954835","M=
elen Ba'aba","","05-05-2025 15:31:46","05-05-2025 15:23:21","05-05-2025 16:=
25:53","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","vanel.mbiada@matech-cameroun.com","506","05-05-2025 15:31=
:46","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004954726","Imm=
-Olympique","","05-05-2025 15:17:16","05-05-2025 15:15:03","05-05-2025 15:3=
7:19","Site went down due to insufficient rectifiers on site//He need to ad=
d 02 rectifiers and site stabilised","Paul BIBOUM","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","Site went down due to insufficient rec=
tifiers on site//He need to add 02 rectifiers and site stabilised","cedric.=
tiani@matech-cameroun.com","134","05-05-2025 15:17:16","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004954699","N=
koabang Ebolmedjock","","05-05-2025 15:13:23","05-05-2025 15:09:40","05-05-=
2025 15:16:20","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matec=
h-cameroun.com","224","05-05-2025 15:13:23","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004954595","Elo=
umdem stade","","05-05-2025 14:48:32","05-05-2025 14:47:57","05-05-2025 15:=
00:32","Active//No power issue site on Grid with U=3D56.3V Georges(69746181=
4)from Huawei is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue=
 site on Grid with U=3D56.3V Georges(697461814)from Huawei is informed","ce=
dric.tiani@matech-cameroun.com","36","05-05-2025 14:48:32","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004954582","M=
ANGUIERS CHAPELLE","","05-05-2025 14:46:08","05-05-2025 14:16:52","05-05-20=
25 17:58:35","site went down due to gen overload (22kva, 340A) SS HISBernar=
d ATANGANA is informed and confirmed  // Site stabilised","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","site went down =
due to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and co=
nfirmed  // Site stabilised","ludivine.ngamaleu@ihstowers.com","1757","05-0=
5-2025 14:46:08","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0004954532","C=
-Supreme","","05-05-2025 14:37:08","05-05-2025 14:30:59","05-05-2025 14:51:=
15","Active: No power issue, site on Grid with Ubaie=3D54.5V, Brice Tsague =
(650 21 40 96) from Huawei is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power iss=
ue, site on Grid with Ubaie=3D54.5V, Brice Tsague (650 21 40 96) from Huawe=
i is informed","vanel.mbiada@matech-cameroun.com","370","05-05-2025 14:37:0=
8","MATECH CMR"
"Closed Complete","Site Down","CTR_369","IHS_YND_019","NOCINC0004954461","H=
otel de Ville Yde","","05-05-2025 14:22:29","05-05-2025 13:44:13","05-05-20=
25 16:14:46","site went down because CB (125A*125A) tripped in Dcbox who fe=
eds equipments OCM / //He rearmed and  site on grid","Paul BIBOUM","Equipme=
nt Repair","Passive","Rectifier","Rectifier - Circuit Breaker","site went d=
own because CB (125A*125A) tripped in Dcbox who feeds equipments OCM / //He=
 rearmed and  site on grid","gerard.tchangoue@matech-cameroun.com","2297","=
05-05-2025 14:22:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_748","NOCINC0004954341","Nkoabang=
 Alembe","","05-05-2025 14:01:35","05-05-2025 13:24:55","05-05-2025 14:08:5=
9","Cascaded Incident from TTO5076747","Mba Lazare Herve","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power Issue on site , Mr Tsa=
gue (Tele-infra / Tel: 655676762) is on site for Swapped ","system","268796=
","05-05-2025 14:01:35","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004954273","Aha=
la Echangeur","","05-05-2025 13:43:13","05-05-2025 13:36:52","05-05-2025 14=
:15:17","Grid fluctuation, Site went down because gen faild to start due to=
 grid bad voltage and no RCP // He bypassed Grid and  Gen manually started"=
,"MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid fluctuation, Site went down because gen faild to start=
 due to grid bad voltage and no RCP // He bypassed Grid and  Gen manually s=
tarted","edwige.kapawo@matech-cameroun.com","382","05-05-2025 13:43:13","MA=
TECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004954197","Elo=
umdem stade","","05-05-2025 13:29:56","05-05-2025 13:29:52","05-05-2025 13:=
42:10","Grid fluctuation, Site went down due to Grid bad voltage and No RCP=
 on site // He bypassed the Grid and Gen manually started","Fanda Brice","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d fluctuation, Site went down due to Grid bad voltage and No RCP on site //=
 He bypassed the Grid and Gen manually started","edwige.kapawo@matech-camer=
oun.com","5","05-05-2025 13:29:56","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004953959","Mok=
olo Yaounde","","05-05-2025 12:46:30","05-05-2025 12:45:59","05-05-2025 13:=
50:59","site went down due to insufficient of rectifier on site// site stab=
ilized	","","Equipment Repair","Passive","Rectifier","Rectifier Module","si=
te went down due to insufficient of rectifier on site// site stabilized	","=
edwige.kapawo@matech-cameroun.com","32","05-05-2025 12:46:30","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004953841","M=
ANGUIERS CHAPELLE","","05-05-2025 12:24:22","05-05-2025 12:18:06","05-05-20=
25 13:58:26","(Very unstable) site went down due to gen overload // Site st=
abilised","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","(Very unstable) site went down due to gen overload // Site stab=
ilised","gerard.tchangoue@matech-cameroun.com","378","05-05-2025 12:24:22",=
"MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004953731","Eto=
udi","","05-05-2025 12:08:11","05-05-2025 12:01:59","05-05-2025 12:26:10","=
Grid outage, Site went down because Gen failed to start due to Gen card dis=
function// He reset Gen card and started Gen manually","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, =
Site went down because Gen failed to start due to Gen card disfunction// He=
 reset Gen card and started Gen manually","edwige.kapawo@matech-cameroun.co=
m","372","05-05-2025 12:08:11","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004953668","M=
ANGUIERS CHAPELLE","","05-05-2025 11:52:30","05-05-2025 11:47:35","05-05-20=
25 11:52:28","site went down due to gen overload (22kva, 340A) Sp HIS Berna=
rd ATANGANA is informed and confirmed // Site stabilised","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","site went down =
due to gen overload (22kva, 340A) Sp HIS Bernard ATANGANA is informed and c=
onfirmed // Site stabilised","gerard.tchangoue@matech-cameroun.com","297","=
05-05-2025 11:52:30","MATECH CMR"
"Closed Complete","Site Down","T1597","IHS_YND_670","NOCINC0004953117","BOB=
OCK","","05-05-2025 10:37:46","05-05-2025 06:17:45","05-05-2025 10:39:00","=
","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Site went down because Gen started and stopped with ""low oil pres=
sure"" alarm// He added oil and started Gen manualy","edwige.kapawo@matech-=
cameroun.com","294428","05-05-2025 10:37:46","MATECH CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0004952931","N=
dogbessol","","05-05-2025 10:00:24","05-05-2025 09:58:59","05-05-2025 10:03=
:26","Active//No power issue on site ,site on GEN wiith Ubaie=3D51.9 V The =
TX FME Etienne/ 695033981/ Huawei is informed","Kemeni Franklin","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site ,site on GEN wiith Ubaie=3D51.9 V The TX F=
ME Etienne/ 695033981/ Huawei is informed","gerard.tchangoue@matech-camerou=
n.com","271","05-05-2025 10:00:24","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004952910","M=
essassi 2","","05-05-2025 09:56:34","05-05-2025 09:55:21","05-05-2025 09:56=
:21","(Very unstable) Grid outage, Site went down due to 02/06 rectifiers i=
ssue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","(Very unstable) Grid outage, Site went down du=
e to 02/06 rectifiers issue // Grid stabilised","gerard.tchangoue@matech-ca=
meroun.com","75","05-05-2025 09:56:34","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004952846","M=
ANGUIERS CHAPELLE","","05-05-2025 09:42:15","05-05-2025 09:37:06","05-05-20=
25 10:14:05","(Very unstable) site went down due to gen overload // Site st=
abilised","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","(Very unstable) site went down due to gen overload // Site stab=
ilised","gerard.tchangoue@matech-cameroun.com","310","05-05-2025 09:42:15",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004952816","B=
arriere","","05-05-2025 09:36:44","05-05-2025 08:20:24","06-05-2025 05:40:2=
1","(Very Unstable) Grid outage, Site went down because Gen overload(20kva,=
400 A) IHS SS Felix Zambe is informed and confirmed","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","(Very Unstable) Grid =
outage, Site went down because Gen overload(20kva,400 A) IHS SS Felix Zambe=
 is informed and confirmed//Grid return","gerard.tchangoue@matech-cameroun.=
com","4581","05-05-2025 09:36:44","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004952562","M=
essassi 2","","05-05-2025 09:00:06","05-05-2025 08:58:55","05-05-2025 09:09=
:57","(Very unstable) Grid outage, Site went down due to 02/06 rectifiers i=
ssue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","(Very unstable) Grid outage, Site went down du=
e to 02/06 rectifiers issue // Grid stabilised","gerard.tchangoue@matech-ca=
meroun.com","74","05-05-2025 09:00:06","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004952472","N=
gouetou","","05-05-2025 08:38:06","05-05-2025 08:32:57","05-05-2025 10:21:5=
5","Active // No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gre=
goire (654547479) from Huawei informed","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue site on Gen, with Ubay=3D54.4V. The Tx Fme Gregoire (6545=
47479) from Huawei informed","edwige.kapawo@matech-cameroun.com","310","05-=
05-2025 08:38:06","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004952396","M=
ANGUIERS CHAPELLE","","05-05-2025 08:17:30","05-05-2025 08:07:59","05-05-20=
25 08:25:59","site went down due to gen overload (22kva, 340A) Sp HIS Berna=
rd ATANGANA is informed and confirmed","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","site went down due to gen overload=
 (22kva, 340A) Sp HIS Bernard ATANGANA is informed and confirmed","gerard.t=
changoue@matech-cameroun.com","572","05-05-2025 08:17:30","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004952349","O=
LAMA","","05-05-2025 08:03:52","05-05-2025 07:56:07","05-05-2025 08:05:55",=
"Active: No power issue on site Ubaie =3D54.9V, The TX FME Henri (699949693=
) from Huawei is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issue=
 on site Ubaie =3D54.9V, The TX FME Henri (699949693) from Huawei is inform=
ed","gerard.tchangoue@matech-cameroun.com","466","05-05-2025 08:03:52","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004952321","M=
essassi 2","","05-05-2025 07:55:09","05-05-2025 07:52:02","05-05-2025 07:56=
:02","(Very unstable) Grid outage, Site went down due to 02/06 rectifiers i=
ssue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","(Very unstable) Grid outage, Site went down du=
e to 02/06 rectifiers issue // Grid stabilised","gerard.tchangoue@matech-ca=
meroun.com","189","05-05-2025 07:55:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0004952256","NYANON/D=
EMBO","","05-05-2025 07:52:58","05-05-2025 06:17:45","05-05-2025 10:39:00",=
"Cascaded Incident from TTO5074353","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Site went down because =
Gen started and stopped with ""low oil pressure"" alarm// He added oil and =
started Gen manualy","system","294428","05-05-2025 07:52:58","MATECH CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0004952029","Nya=
hoo","IHS_EDA_102, IHS_YND_670","05-05-2025 07:36:54","05-05-2025 06:17:45"=
,"05-05-2025 10:39:00","Site went down because Gen started and stopped with=
 ""low oil pressure"" alarm// He added oil and started Gen manualy","TIENTC=
HEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil=
 Pressure","Site went down because Gen started and stopped with ""low oil p=
ressure"" alarm// He added oil and started Gen manualy","edwige.kapawo@mate=
ch-cameroun.com","4750","05-05-2025 07:36:54","MATECH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004951997","Com=
plex Beac II","","05-05-2025 07:23:10","05-05-2025 07:19:01","05-05-2025 08=
:49:43","Grid Outage Site went down because Gen failled To start due to Ala=
rms ""overcurrent'' //He reset gen Card.gen mannually started","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Ou=
tage Site went down because Gen failled To start due to Alarms ""overcurren=
t'' //He reset gen Card.gen mannually started","edwige.kapawo@matech-camero=
un.com","250","05-05-2025 07:23:10","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004951987","B=
arriere","","05-05-2025 07:19:25","05-05-2025 07:15:40","05-05-2025 07:19:4=
0","(Very Unstable) Grid outage, Site went down because Gen overload(20kva,=
400 A) IHS SS Felix Zambe is informed and confirmed//Grid return","Hyemafo =
Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, Site went down because Gen overload(20kva,400 A) IHS SS Felix Zambe is=
 informed and confirmed//Grid return","gerard.tchangoue@matech-cameroun.com=
","226","05-05-2025 07:19:25","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004951961","M=
essassi 2","","05-05-2025 07:15:24","05-05-2025 07:13:12","05-05-2025 07:15=
:12","(Very unstable) Grid outage, Site went down due to 02/06 rectifiers i=
ssue // Grid stabilised","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","(Very unstable) Grid outage, Site went down du=
e to 02/06 rectifiers issue // Grid stabilised","gerard.tchangoue@matech-ca=
meroun.com","133","05-05-2025 07:15:24","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004951915","Oko=
lo Kilombo","","05-05-2025 07:06:52","05-05-2025 07:00:42","05-05-2025 07:0=
9:25","Active //no power issue Ubaie:54.8 V site on Grid The TX FME Synphor=
ien (675295205) from Huawei is informed.","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive //no power issue Ubaie:54.8 V site on Grid The TX FME Synphorien (67529=
5205) from Huawei is informed.","edwige.kapawo@matech-cameroun.com","371","=
05-05-2025 07:06:52","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004951876","Nko=
g-Edzen","","05-05-2025 07:03:11","05-05-2025 06:17:54","05-05-2025 07:57:5=
4","Grid outage. Gen started and stopped due to ""high temp"" alarm // He a=
dded water and Gen manually started","Parker Tchoup","Equipment Repair","Pa=
ssive","ACDG Gen","Gen Temp High","Grid outage. Gen started and stopped due=
 to ""high temp"" alarm // He added water and Gen manually started","edwige=
.kapawo@matech-cameroun.com","2718","05-05-2025 07:03:11","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004951746","C=
RF Nkoabang","","05-05-2025 06:37:58","05-05-2025 06:21:46","05-05-2025 07:=
02:22","Grid outage No space to deploy // Grid power return","Mba Lazare He=
rve","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage No space to deploy // Grid power return","christelle.ngonga@matec=
h-cameroun.com","973","05-05-2025 06:37:58","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0004951721","Ngo=
um","","05-05-2025 06:31:53","05-05-2025 06:18:13","05-05-2025 07:24:54","S=
ite went Down due to Fuel shortage // Tank inclined (refueling proccess ong=
oing)","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Si=
te went Down due to Fuel shortage // Tank inclined (refueling proccess ongo=
ing)","franck.nkomot@matech-cameroun.com","864","05-05-2025 06:31:53","MATE=
CH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004951432","ODZ=
A MINKAN EDIBI ASSI","","05-05-2025 04:35:30","05-05-2025 04:30:24","05-05-=
2025 06:08:57","Grid outage,site went down due to Rectifier dysfunctionning=
 on site //He reset it and site on Grid","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Grid outage,site went down due t=
o Rectifier dysfunctionning on site //He reset it and site on Grid","franck=
.nkomot@matech-cameroun.com","307","05-05-2025 04:35:30","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004951300","SAA=
 Entrance","","05-05-2025 03:31:17","05-05-2025 03:23:42","05-05-2025 03:51=
:42","Site went down because 2/3 rectifier disfunctionning // He reset rect=
ifiers and site on grid","Parker Tchoup","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Site went down because 2/3 rectifier disfunction=
ning // He reset rectifiers and site on grid","franck.nkomot@matech-camerou=
n.com","456","05-05-2025 03:31:17","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004951264","O=
LAMA","","05-05-2025 03:07:50","05-05-2025 02:55:34","05-05-2025 03:15:09",=
"No power issue on site U=3D54,9 V site on Gen , The Tx FME Etienne/6513201=
88/ from Huawei is informed","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on si=
te U=3D54,9 V site on Gen , The Tx FME Etienne/651320188/ from Huawei is in=
formed","christelle.ngonga@matech-cameroun.com","737","05-05-2025 03:07:50"=
,"MATECH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004951222","Com=
plex Beac II","","05-05-2025 02:50:06","05-05-2025 02:42:45","05-05-2025 05=
:48:23","Site went down because Gen failed to start due to Grid bad voltage=
 // he bypass the Grid and Gen manually started","Albran Byorel","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","Site went d=
own because Gen failed to start due to Grid bad voltage // he bypass the Gr=
id and Gen manually started","franck.nkomot@matech-cameroun.com","442","05-=
05-2025 02:50:06","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0004951176","NKO=
NGKARAK","","05-05-2025 02:23:39","05-05-2025 02:17:23","05-05-2025 06:40:3=
3","Site went down because Gen started and stopped due to pierced pellet //=
 he added Water and Manually Started The Gen","TIENTCHEU NZETCHIEU GAEL","E=
quipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Le=
vel Issue","Site went down because Gen started and stopped due to pierced p=
ellet // he added Water and Manually Started The Gen","franck.nkomot@matech=
-cameroun.com","377","05-05-2025 02:23:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0004951010","Nkol-Meb=
anga","","05-05-2025 01:51:10","05-05-2025 01:47:32","05-05-2025 02:33:32",=
"Cascaded Incident from TTO5073164","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site down because gen ran till fue=
l shortage // Tilt tank (refueling proccess is on going )","system","281671=
","05-05-2025 01:51:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004951009","Carrefou=
r Ayissi Ele","","05-05-2025 01:51:10","05-05-2025 01:47:32","05-05-2025 02=
:33:32","Cascaded Incident from TTO5073164","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site down because gen ran =
till fuel shortage // Tilt tank (refueling proccess is on going )","system"=
,"281671","05-05-2025 01:51:10","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004950962","S=
aa","IHS_YND_810, IHS_YND_809","05-05-2025 01:44:52","05-05-2025 01:42:32",=
"05-05-2025 02:33:32","Site down because gen ran till fuel shortage // Tilt=
 tank (refueling proccess is on going )","Parker Tchoup","Fuel Outage","Pas=
sive","Diesel","Diesel Outage","Site down because gen ran till fuel shortag=
e // Tilt tank (refueling proccess is on going )","christelle.ngonga@matech=
-cameroun.com","141","05-05-2025 01:44:52","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0004950789","Ngo=
um","","05-05-2025 00:53:00","05-05-2025 00:45:38","05-05-2025 06:11:36","S=
ite down because gen ran till fuel shortage // Tilt tank (refueling procces=
s is on going )","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel O=
utage","Site down because gen ran till fuel shortage // Tilt tank (refuelin=
g proccess is on going )","franck.nkomot@matech-cameroun.com","443","05-05-=
2025 00:53:00","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004950643","N=
gouetou","","04-05-2025 23:38:47","04-05-2025 23:36:40","05-05-2025 03:23:4=
0","Site went down because gen stopped due to unknow alarm in the  card // =
He reset Gen card and manually start the gen","Parker Tchoup","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Site went down because g=
en stopped due to unknow alarm in the  card // He reset Gen card and manual=
ly start the gen","christelle.ngonga@matech-cameroun.com","129","04-05-2025=
 23:38:47","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004950561","Eto=
ug ebe biscuiterie","","04-05-2025 23:08:35","04-05-2025 23:02:58","04-05-2=
025 23:49:58","Grid fluctuation site went down because Gen failed to start =
due to Grid bad voltage// He bypass the Grid and Gen manually started","Hye=
mafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen failed to start due=
 to Grid bad voltage// He bypass the Grid and Gen manually started","franck=
.nkomot@matech-cameroun.com","338","04-05-2025 23:08:35","MATECH CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004950203","Cha=
rles-Atangana","IHS_YND_051","04-05-2025 21:41:37","04-05-2025 21:31:28","0=
4-05-2025 22:58:38","Grid only site ,no space to deploy MGE // Grid restora=
tion","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Grid only site ,no space to deploy MGE // Grid restoration","loic.noumsi@=
matech-cameroun.com","611","04-05-2025 21:41:37","MATECH CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004950201","M=
amch Building","","04-05-2025 21:41:03","04-05-2025 21:31:28","04-05-2025 2=
2:50:26","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid only site ,no space to deploy MGE // Grid restoration=
","gaelle.njiofack@matech-cameroun.com","268199","04-05-2025 21:41:03","MAT=
ECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004950198","Nko=
zoa","","04-05-2025 21:40:03","04-05-2025 21:31:22","04-05-2025 22:22:22","=
Grid bad voltage, site went down because gen ran untill fuel shortage (due =
to small fuel tank capacity Gen 30kva // 60L Tank on site ) // Refueling do=
ne","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Gri=
d bad voltage, site went down because gen ran untill fuel shortage (due to =
small fuel tank capacity Gen 30kva // 60L Tank on site ) // Refueling done"=
,"loic.noumsi@matech-cameroun.com","546","04-05-2025 21:40:03","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004950185","A=
ccacia New","","04-05-2025 21:36:41","04-05-2025 21:31:34","04-05-2025 21:4=
8:17","	Grid outage ,no space to deploy a mobil gen // grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid outag=
e ,no space to deploy a mobil gen // grid return","gaelle.njiofack@matech-c=
ameroun.com","308","04-05-2025 21:36:41","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004949996","M=
endong vallee","","04-05-2025 21:00:22","04-05-2025 18:56:45","05-05-2025 0=
0:15:31","Gen over load (20KVA; 300A) HS F=E9lix Zamb=E9 is informed and co=
nfirmed ","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Gen over load (20KVA; 300A) HS F=E9lix Zamb=E9 is informed and conf=
irmed ","gaelle.njiofack@matech-cameroun.com","7418","04-05-2025 21:00:22",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004949948","Eseka To=
wn","","04-05-2025 20:51:23","04-05-2025 20:13:34","04-05-2025 20:20:47","C=
ascaded Incident from TTO5071835","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue, site is on Gr=
id with Ubaie=3D 53,6 V The FME Yannick Mbah (698270715) from Huawei is inf=
ormed","system","272932","04-05-2025 20:51:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0004949944","Eseka MT=
N","","04-05-2025 20:51:22","04-05-2025 20:13:34","04-05-2025 20:20:47","Ca=
scaded Incident from TTO5071835","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue, site is on Gri=
d with Ubaie=3D 53,6 V The FME Yannick Mbah (698270715) from Huawei is info=
rmed","system","272931","04-05-2025 20:51:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0004949939","Ndogbess=
ol","","04-05-2025 20:51:21","04-05-2025 20:13:34","04-05-2025 20:20:47","C=
ascaded Incident from TTO5071835","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue, site is on Gr=
id with Ubaie=3D 53,6 V The FME Yannick Mbah (698270715) from Huawei is inf=
ormed","system","272918","04-05-2025 20:51:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0004949935","Boumnyeb=
el","","04-05-2025 20:51:20","04-05-2025 20:13:34","04-05-2025 20:20:47","C=
ascaded Incident from TTO5071835","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue, site is on Gr=
id with Ubaie=3D 53,6 V The FME Yannick Mbah (698270715) from Huawei is inf=
ormed","system","272928","04-05-2025 20:51:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004949933","Song-bon=
g","","04-05-2025 20:51:20","04-05-2025 20:13:34","04-05-2025 20:20:47","Ca=
scaded Incident from TTO5071835","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue, site is on Gri=
d with Ubaie=3D 53,6 V The FME Yannick Mbah (698270715) from Huawei is info=
rmed","system","272924","04-05-2025 20:51:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0004949928","Mamb",""=
,"04-05-2025 20:51:19","04-05-2025 20:13:34","04-05-2025 20:20:47","Cascade=
d Incident from TTO5071835","Kemeni Franklin","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active//No power issue, site is on Grid wit=
h Ubaie=3D 53,6 V The FME Yannick Mbah (698270715) from Huawei is informed"=
,"system","272922","04-05-2025 20:51:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0004949929","Ngoung",=
"","04-05-2025 20:51:19","04-05-2025 20:13:34","04-05-2025 20:20:47","Casca=
ded Incident from TTO5071835","Kemeni Franklin","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue, site is on Grid w=
ith Ubaie=3D 53,6 V The FME Yannick Mbah (698270715) from Huawei is informe=
d","system","272915","04-05-2025 20:51:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_416","NOCINC0004949927","Ngwopi B=
oga","","04-05-2025 20:51:18","04-05-2025 20:13:34","04-05-2025 20:20:47","=
Cascaded Incident from TTO5071835","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active//No power issue, site is on G=
rid with Ubaie=3D 53,6 V The FME Yannick Mbah (698270715) from Huawei is in=
formed","system","272927","04-05-2025 20:51:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_781","NOCINC0004949926","BIBOMDJI=
DJIEL","","04-05-2025 20:51:18","04-05-2025 20:13:34","04-05-2025 20:20:47"=
,"Cascaded Incident from TTO5071835","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue, site is on=
 Grid with Ubaie=3D 53,6 V The FME Yannick Mbah (698270715) from Huawei is =
informed","system","272919","04-05-2025 20:51:18","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004949895","O=
dza II OCM","IHS_YND_528","04-05-2025 20:41:41","04-05-2025 20:28:32","04-0=
5-2025 20:45:35","Site went down due to Disjunction of Grid CB // Grid CB r=
earm","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Circu=
it Breaker","Site went down due to Disjunction of Grid CB // Grid CB rearm"=
,"gaelle.njiofack@matech-cameroun.com","791","04-05-2025 20:41:41","MATECH =
CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004949843","M=
EHANDAN","","04-05-2025 20:33:21","04-05-2025 20:28:32","04-05-2025 20:45:3=
5","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Site went down due to Disjunction of Grid CB // Grid CB rearm","=
gaelle.njiofack@matech-cameroun.com","1451","04-05-2025 20:33:21","MATECH C=
MR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004949588","Mes=
sassi 2","","04-05-2025 19:43:32","04-05-2025 19:35:56","04-05-2025 19:43:0=
4","Grid outage, Site went down due to 02/06 rectifiers issue // Grid stabi=
lised","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Grid outage, Site went down due to 02/06 rectifiers issue // Gri=
d stabilised","loic.noumsi@matech-cameroun.com","457","04-05-2025 19:43:32"=
,"MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004949559","Ron=
d Point Express1114","","04-05-2025 19:37:14","04-05-2025 19:31:07","04-05-=
2025 19:41:45","Grid outage, Site down due to poor battery backup // Gen st=
art automatically","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site down due to poor bat=
tery backup // Gen start automatically","loic.noumsi@matech-cameroun.com","=
368","04-05-2025 19:37:14","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004949465","E=
koumdoum OCM","","04-05-2025 19:16:21","04-05-2025 19:06:58","05-05-2025 10=
:18:08","Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline i=
s informed and confirmed// Grid return","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen overload(=
20kva,280 A) IHS SS Pascaline is informed and confirmed// Grid return","gae=
lle.njiofack@matech-cameroun.com","564","04-05-2025 19:16:21","MATECH CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0004949293","Nko=
ngtock","","04-05-2025 18:36:11","04-05-2025 18:29:02","04-05-2025 18:44:32=
","Site went down due to HUAwei bay malfunction // Site stabilised","Kemeni=
 Franklin","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Si=
te went down due to HUAwei bay malfunction // Site stabilised","loic.noumsi=
@matech-cameroun.com","430","04-05-2025 18:36:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0004949247","Acropole=
","","04-05-2025 18:27:37","04-05-2025 18:19:02","04-05-2025 18:35:29","Cas=
caded Incident from TTO5071171","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","SS IHS Francois reported No power issue o=
n site Ubay =3D 52V, Oshia (674007438//Huawei) is informed","system","515",=
"04-05-2025 18:27:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_058","NOCINC0004949246","Mvolye",=
"","04-05-2025 18:27:37","04-05-2025 18:19:02","04-05-2025 18:35:29","Casca=
ded Incident from TTO5071171","MINKA NICOLAS","Cascade Outage","Active","Ca=
scade Active","Cascade Active","SS IHS Francois reported No power issue on =
site Ubay =3D 52V, Oshia (674007438//Huawei) is informed","system","515","0=
4-05-2025 18:27:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_560","NOCINC0004949248","Cite des=
 nations","","04-05-2025 18:27:37","04-05-2025 18:19:02","04-05-2025 18:35:=
29","Cascaded Incident from TTO5071171","Paul BIBOUM","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","SS IHS Francois reported No power i=
ssue on site Ubay =3D 52V, Oshia (674007438//Huawei) is informed","system",=
"515","04-05-2025 18:27:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_721","NOCINC0004949243","VOIRIE M=
UNICIPALE YAOUNDE","","04-05-2025 18:27:36","04-05-2025 18:19:02","04-05-20=
25 18:35:29","Cascaded Incident from TTO5071171","Paul BIBOUM","Cascade Out=
age","Active","Cascade Active","Cascade Active","SS IHS Francois reported N=
o power issue on site Ubay =3D 52V, Oshia (674007438//Huawei) is informed",=
"system","514","04-05-2025 18:27:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_026","NOCINC0004949242","ENAM",""=
,"04-05-2025 18:27:36","04-05-2025 18:19:02","04-05-2025 18:35:29","Cascade=
d Incident from TTO5071171","","Cascade Outage","Active","Cascade Active","=
Cascade Active","SS IHS Francois reported No power issue on site Ubay =3D 5=
2V, Oshia (674007438//Huawei) is informed","system","514","04-05-2025 18:27=
:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_018","NOCINC0004949244","P&T Buil=
ding","","04-05-2025 18:27:36","04-05-2025 18:19:02","04-05-2025 18:35:29",=
"Cascaded Incident from TTO5071171","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","SS IHS Francois reported No power issue on site Ub=
ay =3D 52V, Oshia (674007438//Huawei) is informed","system","514","04-05-20=
25 18:27:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_235","NOCINC0004949245","Etoug-Eb=
e 2","","04-05-2025 18:27:36","04-05-2025 18:19:02","04-05-2025 18:35:29","=
Cascaded Incident from TTO5071171","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","SS IHS Francois reported No power issue on site Uba=
y =3D 52V, Oshia (674007438//Huawei) is informed","system","514","04-05-202=
5 18:27:36","MATECH CMR"
"Closed Complete","Site Down","CTR_401","IHS_YND_041","NOCINC0004949222","L=
ycee Leclerc School","IHS_YND_026, IHS_YND_721, IHS_YND_018, IHS_YND_235, I=
HS_YND_058, IHS_YND_036, IHS_YND_560","04-05-2025 18:22:11","04-05-2025 18:=
17:02","04-05-2025 18:35:29","SS IHS Francois reported No power issue on si=
te Ubay =3D 52V, Oshia (674007438//Huawei) is informed","Paul BIBOUM","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","SS IHS Francois reported No power issue on site Ubay =3D 52V, Oshia =
(674007438//Huawei) is informed","gaelle.njiofack@matech-cameroun.com","310=
","04-05-2025 18:22:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004949218","ELOUMDEM=
 CARRIERE 2","","04-05-2025 18:21:19","04-05-2025 18:10:22","04-05-2025 18:=
22:51","Cascaded Incident from TTO5071142","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","system","=
1215290","04-05-2025 18:21:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004949217","Eto koss=
 Yde","","04-05-2025 18:21:18","04-05-2025 18:10:22","04-05-2025 18:22:51",=
"Cascaded Incident from TTO5071142","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","system","1215289=
","04-05-2025 18:21:18","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004949209","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","04-05-2025 18:17:44","04-05-2025 18:=
10:22","04-05-2025 18:22:51","Grid outage, Site went down before Gen start =
due to poor backup // Gen started automatically","Fanda Brice","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
, Site went down before Gen start due to poor backup // Gen started automat=
ically","gaelle.njiofack@matech-cameroun.com","444","04-05-2025 18:17:44","=
MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004949208","B=
arriere","","04-05-2025 18:17:14","04-05-2025 17:58:30","05-05-2025 01:24:2=
5","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed//Grid return","Hyemafo Gildas","Equipme=
nt Repair","Passive","DCDG Gen","DCDG - Overload","Grid outage, Site went d=
own because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and co=
nfirmed//Grid return","loic.noumsi@matech-cameroun.com","1125","04-05-2025 =
18:17:14","MATECH CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0004949079","M=
endong Maeture","","04-05-2025 17:51:18","04-05-2025 17:46:06","04-05-2025 =
18:32:53","Grid outage.gen start and stopped due to alarm ""high temp"" // =
We added water and gen manually started","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gri=
d outage.gen start and stopped due to alarm ""high temp"" // We added water=
 and gen manually started","gaelle.njiofack@matech-cameroun.com","313","04-=
05-2025 17:51:18","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004949052","M=
EHANDAN","","04-05-2025 17:43:36","04-05-2025 17:39:28","04-05-2025 17:52:2=
4","Site went down due to Bad Grid voltage, // Grid stabilized","Albran Byo=
rel","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply I=
ssue","Site went down due to Bad Grid voltage, // Grid stabilized","gaelle.=
njiofack@matech-cameroun.com","250","04-05-2025 17:43:36","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004948965","E=
koumdoum OCM","","04-05-2025 17:17:02","04-05-2025 17:09:52","04-05-2025 18=
:29:44","Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline i=
s informed and confirmed// Grid return","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen overload(=
20kva,280 A) IHS SS Pascaline is informed and confirmed// Grid return","gae=
lle.njiofack@matech-cameroun.com","431","04-05-2025 17:17:02","MATECH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004948919","Com=
plex Beac II","","04-05-2025 17:03:28","04-05-2025 16:57:16","04-05-2025 17=
:57:34","Grid Outage Site went down because Gen FAILED To start due to Alar=
ms ""overvoltage'' //He reseted ACDG Card","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage Site went down =
because Gen FAILED To start due to Alarms ""overvoltage'' //He reseted ACDG=
 Card","franck.nkomot@matech-cameroun.com","373","04-05-2025 17:03:28","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_058","NOCINC0004948802","Mvolye",=
"","04-05-2025 16:45:22","04-05-2025 16:27:59","04-05-2025 16:51:04","Casca=
ded Incident from TTO5070609","MINKA NICOLAS","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
failed to start due to automation malfunctionning // he started Gen manuall=
y","system","1214445","04-05-2025 16:45:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_018","NOCINC0004948794","P&T Buil=
ding","","04-05-2025 16:43:21","04-05-2025 16:27:59","04-05-2025 16:51:04",=
"Cascaded Incident from TTO5070609","","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","Grid outage, site went down because gen failed =
to start due to automation malfunctionning // he started Gen manually","sys=
tem","1214444","04-05-2025 16:43:21","MATECH CMR"
"Closed Complete","Site Down","T2743","IHS_YND_721","NOCINC0004948764","VOI=
RIE MUNICIPALE YAOUNDE","","04-05-2025 16:36:51","04-05-2025 16:27:59","04-=
05-2025 16:51:04","","Paul BIBOUM","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage, site went down because gen failed to s=
tart due to automation malfunctionning // he started Gen manually","franck.=
nkomot@matech-cameroun.com","1214444","04-05-2025 16:36:51","MATECH CMR"
"Closed Complete","Site Down","T0538","IHS_YND_036","NOCINC0004948762","Acr=
opole","","04-05-2025 16:36:10","04-05-2025 16:27:59","04-05-2025 16:51:04"=
,"","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","cascaded outage","franck.nkomot@matech-cameroun.com","1214443","04=
-05-2025 16:36:10","MATECH CMR"
"Closed Complete","Site Down","CTR_401","IHS_YND_041","NOCINC0004948754","L=
ycee Leclerc School","IHS_YND_721, IHS_YND_018, IHS_YND_235, IHS_YND_058, I=
HS_YND_036","04-05-2025 16:35:34","04-05-2025 16:25:59","04-05-2025 16:51:0=
4","Grid outage, site went down because gen failed to start due to automati=
on malfunctionning (SS IHS Francois Ndoungou is informed) // he started Gen=
 manually","Paul BIBOUM","Equipment Repair","Passive","Control Panel","ATS-=
AMF Issue","Grid outage, site went down because gen failed to start due to =
automation malfunctionning (SS IHS Francois Ndoungou is informed) // he sta=
rted Gen manually","gaelle.njiofack@matech-cameroun.com","575","04-05-2025 =
16:35:34","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0004948741","Eto=
ug-Ebe 2","","04-05-2025 16:34:19","04-05-2025 16:27:59","04-05-2025 16:51:=
04","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","C=
ascade outage","loic.noumsi@matech-cameroun.com","1214442","04-05-2025 16:3=
4:19","MATECH CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0004948733","ENA=
M","","04-05-2025 16:32:14","04-05-2025 16:25:06","04-05-2025 16:51:17","Gr=
id outage, no space to deploy MGE // Grid returned","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage, no space to de=
ploy MGE // Grid returned","loic.noumsi@matech-cameroun.com","429","04-05-2=
025 16:32:14","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004948731","Cit=
e des nations","","04-05-2025 16:31:10","04-05-2025 16:24:03","04-05-2025 1=
6:52:58","Site went down due to insufficient rectifiers on site//Site stabi=
lised","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficient rectifiers on site//Site stabilis=
ed","loic.noumsi@matech-cameroun.com","427","04-05-2025 16:31:10","MATECH C=
MR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004948639","M=
ANGUIERS CHAPELLE","","04-05-2025 16:12:39","04-05-2025 16:03:59","04-05-20=
25 19:45:59","site went down due to gen overload (22kva, 340A) Sp HIS Berna=
rd ATANGANA is informed and confirmed","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","site went down due to gen overload=
 (22kva, 340A) Sp HIS Bernard ATANGANA is informed and confirmed","gaelle.n=
jiofack@matech-cameroun.com","521","04-05-2025 16:12:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004948574","Yoko MTN=
","","04-05-2025 16:01:23","04-05-2025 15:51:11","04-05-2025 15:54:02","Cas=
caded Incident from TTO5070359 - Cascade Removed From TTO5070359","Parker T=
choup","Cascade Outage","Active","Cascade Active","Cascade Active","Solar H=
ybrid GEN site, No power issue site on Solar, with U=3D52.1V. The Tx Fme Gr=
egoire (654547479) from Huawei informed","system","1223771","04-05-2025 16:=
01:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004948573","Matsari"=
,"IHS_YND_475, IHS_YND_473","04-05-2025 16:01:22","04-05-2025 15:51:11","04=
-05-2025 17:50:49","Cascaded Incident from TTO5070359 - Cascade Removed Fro=
m TTO5070359","Parker Tchoup","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Solar Hybrid GEN site, No power i=
ssue site on Solar, with U=3D52.1V. The Tx Fme Gregoire (654547479) from Hu=
awei informed","system","611","04-05-2025 16:01:22","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0004948560","Ngo=
um","","04-05-2025 15:59:16","04-05-2025 15:51:11","04-05-2025 15:54:02",""=
,"Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active=
","Solar Hybrid GEN site, No power issue site on Solar, with U=3D52.1V. The=
 Tx Fme Gregoire (654547479) from Huawei informed","loic.noumsi@matech-came=
roun.com","2515","04-05-2025 15:59:16","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004948426","N=
koabang Ebolmedjock","","04-05-2025 15:38:37","04-05-2025 15:16:29","04-05-=
2025 17:16:08","	Active//No power issue, Site on Gen. Notice that it is imp=
acted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","Affected b=
y 3rd Party Site","	Active//No power issue, Site on Gen. Notice that it is =
impacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","gaelle.njiofack@=
matech-cameroun.com","1329","04-05-2025 15:38:37","MATECH CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0004948296","Bye=
massi Carrefour","","04-05-2025 15:13:58","04-05-2025 15:05:52","04-05-2025=
 17:59:43","Grid outage .gen failed to start due to diesel pipe issue // Gr=
id returned","Paul BIBOUM","Fuel Outage (Probable)","Passive","Diesel","Fue=
l Line Issue","Grid outage .gen failed to start due to diesel pipe issue //=
Grid return","loic.noumsi@matech-cameroun.com","487","04-05-2025 15:13:58",=
"MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004948075","SAA=
 Entrance","","04-05-2025 14:41:13","04-05-2025 14:35:09","04-05-2025 15:35=
:57","Active: No power issue, site is on Gen with Ubaie=3D54.5V, The FME Gr=
egoire /654547479 Huawei is informed","Parker Tchoup","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Active: =
No power issue, site is on Gen with Ubaie=3D54.5V, The FME Gregoire /654547=
479 Huawei is informed","loic.noumsi@matech-cameroun.com","366","04-05-2025=
 14:41:13","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004948053","ODZ=
A MINKAN EDIBI ASSI","","04-05-2025 14:38:37","04-05-2025 14:36:28","04-05-=
2025 14:57:34","Grid outage, Site went down because Gen failed to start due=
 to  faulty Gen battery  // Grid returned","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, Site went =
down because Gen failed to start due to  faulty Gen battery  // Grid return=
ed","loic.noumsi@matech-cameroun.com","130","04-05-2025 14:38:37","MATECH C=
MR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004947819","M=
essassi 2","","04-05-2025 13:56:56","04-05-2025 13:51:24","04-05-2025 15:01=
:51","Grid outage, site went down due to trip of CB (100 A) in the bay ZTE =
// he rearmed it","Fabrice Pouakam","Equipment Repair","Passive","Control P=
anel","BTS Breaker Tripped","Grid outage, site went down due to trip of CB =
(100 A) in the bay ZTE // he rearmed it","vanel.mbiada@matech-cameroun.com"=
,"334","04-05-2025 13:56:56","MATECH CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004947658","MAN=
GUIERS CHAPELLE","","04-05-2025 13:24:37","04-05-2025 13:17:29","04-05-2025=
 14:41:33","site went down due to gen overload (22kva, 340A) SS HISBernard =
ATANGANA is informed and confirmed // Site stabilised","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","site went down due=
 to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and confi=
rmed // Site stabilised","cedric.tiani@matech-cameroun.com","2901","04-05-2=
025 13:24:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_520","NOCINC0004947605","SIMBOCK =
BONAMBAPE","","04-05-2025 13:13:31","04-05-2025 13:09:59","04-05-2025 14:11=
:59","Cascaded Incident from TTO5069230","Hyemafo Gildas","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
due to Gen OVERLOAD (15 KVA, 170 A) that caused double disjunction (2*125A)=
 in OCM bay // he reduced load, site on GEN","system","276824","04-05-2025 =
13:13:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0004947604","MEFOU AS=
SI","","04-05-2025 13:13:31","04-05-2025 13:09:59","04-05-2025 14:11:59","C=
ascaded Incident from TTO5069230","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to Gen=
 OVERLOAD (15 KVA, 170 A) that caused double disjunction (2*125A) in OCM ba=
y // he reduced load, site on GEN","system","276824","04-05-2025 13:13:31",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004947584","M=
efou-Assi","IHS_YND_537, IHS_YND_520","04-05-2025 13:12:16","04-05-2025 13:=
09:59","04-05-2025 14:11:59","Grid outage, site went down due to Gen OVERLO=
AD (15 KVA, 170 A) that caused double disjunction (2*125A) in OCM bay // he=
 reduced load, site on GEN","Fanda Brice","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Grid outage, site went down due to Gen OVERLOAD (=
15 KVA, 170 A) that caused double disjunction (2*125A) in OCM bay // he red=
uced load, site on GEN","vanel.mbiada@matech-cameroun.com","138","04-05-202=
5 13:12:16","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004947456","Aka=
k-Nkozoa-MTN-IHS","","04-05-2025 12:44:20","04-05-2025 12:39:07","04-05-202=
5 13:07:23","Grid fluctuation, site went down because Gen start and stopped=
 due to Grid bad voltage // he bypass Grid and manually start the Gen","Fab=
rice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because Gen start and stopped=
 due to Grid bad voltage // he bypass Grid and manually start the Gen","ced=
ric.tiani@matech-cameroun.com","315","04-05-2025 12:44:20","MATECH CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0004947338","K=
ondengui","","04-05-2025 12:21:20","04-05-2025 12:11:45","04-05-2025 12:22:=
46","","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascade =
Active","ACTIVE// No power issue on site Ubaie=3D54,3V site on Grid , The T=
x FME Leonel/ 694693436/ from Huawei is informed","vanel.mbiada@matech-came=
roun.com","1215428","04-05-2025 12:21:20","MATECH CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0004947332","E=
mombo-Tchad","IHS_YND_114","04-05-2025 12:20:00","04-05-2025 12:11:45","04-=
05-2025 13:31:32","ACTIVE// No power issue on site Ubaie=3D54,3V site on Gr=
id , The Tx FME Leonel/ 694693436/ from Huawei is informed","","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE// No power issue on site Ubaie=3D54,3V site on Grid , The Tx FME Leo=
nel/ 694693436/ from Huawei is informed","vanel.mbiada@matech-cameroun.com"=
,"496","04-05-2025 12:20:00","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004947236","Men=
dong3","","04-05-2025 12:01:04","04-05-2025 12:00:58","04-05-2025 18:38:12"=
,"Grid Outage No space to deploy a MDG // Grid Restored","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No space t=
o deploy a MDG // Grid Restored","cedric.tiani@matech-cameroun.com","7","04=
-05-2025 12:01:04","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004947231","Lad=
a I Yde","","04-05-2025 12:00:16","04-05-2025 11:59:59","04-05-2025 13:30:0=
3","Active//No power issue site on Grid with U=3D54.0V Lionel Adjep(6551848=
76) from Huawei is informed.Noticed cable vandalised at the BTS MTN","Mba L=
azare Herve","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active//No power issue site on Grid with U=3D54.0V=
 Lionel Adjep(655184876) from Huawei is informed.Noticed cable vandalised a=
t the BTS MTN","cedric.tiani@matech-cameroun.com","18","04-05-2025 12:00:16=
","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0004947180","Eto=
ug ebe Meweulo","","04-05-2025 11:48:03","04-05-2025 11:45:43","04-05-2025 =
11:49:32","Grid outage, Site went down before Gen start due to poor backup/=
/ Gen started automatically","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup// Gen started automatically","cedric.ti=
ani@matech-cameroun.com","141","04-05-2025 11:48:03","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004947122","SAA=
 Entrance","","04-05-2025 11:29:57","04-05-2025 11:27:16","04-05-2025 12:45=
:26","Active: No power issue, site is on Gen with Ubaie=3D54.5V,   The FME =
Gregoire /654547479 Huawei is informed","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active:=
 No power issue, site is on Gen with Ubaie=3D54.5V,=20

The FME Gregoire /654547479 Huawei is informed
","cedric.tiani@matech-cameroun.com","162","04-05-2025 11:29:57","MATECH CM=
R"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004946976","NKO=
MKANA ELIZA HOTEL","","04-05-2025 11:10:10","04-05-2025 11:08:53","04-05-20=
25 11:10:12","No power issue on site U=3D53V, site on Grid, UP at 11:10 AM"=
,"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site U=3D53V, site on Grid, UP at 11:10 A=
M","cedric.tiani@matech-cameroun.com","78","04-05-2025 11:10:10","MATECH CM=
R"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004946924","N=
kozoa","","04-05-2025 10:59:07","04-05-2025 10:54:02","04-05-2025 11:47:51"=
,"Grid bad voltage, site went down because gen ran untill fuel shortage // =
Refueling done.(due to little fuel tank Gen 30kva // 60L Tank on site )","F=
abrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid bad =
voltage, site went down because gen ran untill fuel shortage // Refueling d=
one.(due to little fuel tank Gen 30kva // 60L Tank on site )","vanel.mbiada=
@matech-cameroun.com","306","04-05-2025 10:59:07","MATECH CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0004946790","N=
kolso","","04-05-2025 10:38:13","04-05-2025 10:10:06","04-05-2025 10:20:35"=
,"Active//No power issue on site ,site on Grid with Ubaie=3D54.9 V The Tx F=
ME Mouahamadou (691144435) of Huawei is informed.","TIENTCHEU NZETCHIEU GAE=
L","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issue on site ,site on Grid with Ubaie=3D54=
.9 V The Tx FME Mouahamadou (691144435) of Huawei is informed.","vanel.mbia=
da@matech-cameroun.com","1688","04-05-2025 10:38:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0004946768","MEFOU AS=
SI","","04-05-2025 10:36:03","04-05-2025 10:10:15","04-05-2025 11:30:39","C=
ascaded Incident from TTO5068273 - Cascade Removed From TTO5068273","Fanda =
Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid=
 outage, site went down because gen fails to start due to gen overload(15Kv=
a, 200A) SS IHS FELIX ZAMBE is informed // He reduice the load and manually=
 start the gen","system","273234","04-05-2025 10:36:03","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004946757","S=
IMBOCK BONAMBAPE","","04-05-2025 10:33:59","04-05-2025 10:10:15","04-05-202=
5 11:30:39","fme is informed ETA 11:20","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen fails to start due to gen overload(15Kva, 200A) SS IHS FELIX ZAM=
BE is informed // He reduice the load and manually start the gen","vanel.mb=
iada@matech-cameroun.com","273234","04-05-2025 10:33:59","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004946747","M=
efou-Assi","IHS_YND_537, IHS_YND_520","04-05-2025 10:32:37","04-05-2025 10:=
10:15","04-05-2025 11:30:39","Grid outage, site went down because gen fails=
 to start due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed /=
/ He reduice the load and manually start the gen","Fanda Brice","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down=
 because gen fails to start due to gen overload(15Kva, 200A) SS IHS FELIX Z=
AMBE is informed // He reduice the load and manually start the gen","vanel.=
mbiada@matech-cameroun.com","1343","04-05-2025 10:32:37","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004946670","Men=
dong vallee","","04-05-2025 10:18:25","04-05-2025 10:16:12","04-05-2025 18:=
55:45","Gen over load (20KVA; 300A) HS F=E9lix Zamb=E9 is informed and conf=
irmed // Grid returned","Fanda Brice","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","Gen over load (20KVA; 300A) HS F=E9lix Zamb=E9 is inf=
ormed and confirmed // Grid returned","cedric.tiani@matech-cameroun.com","1=
34","04-05-2025 10:18:25","MATECH CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004946439","SOA=
 VILLAGE","","04-05-2025 09:37:12","04-05-2025 09:35:55","04-05-2025 09:40:=
29","Active //No power issue on site ,site on Grid with Ubaie=3D54.6 V The =
Tx FME Synphorien//691316854 from Huawei is informed","Siligap Boris","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active //No power issue on site ,site on Grid with Ubaie=3D54.6 V Th=
e Tx FME Synphorien//691316854 from Huawei is informed","cedric.tiani@matec=
h-cameroun.com","78","04-05-2025 09:37:12","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004946362","Nom=
ayos montee Meche","","04-05-2025 09:25:46","04-05-2025 09:24:34","04-05-20=
25 09:40:34","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On G=
rid The Tx FME Fulbert(654266068) from Huawei is informed.","Fanda Brice","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On Grid=
 The Tx FME Fulbert(654266068) from Huawei is informed.","cedric.tiani@mate=
ch-cameroun.com","73","04-05-2025 09:25:46","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004946133","B=
arriere","","04-05-2025 08:31:32","04-05-2025 08:24:25","04-05-2025 13:46:3=
5","Site went down because Gen overload (20kva, 400A) SS IHS Felix ZAMBE co=
nfirmed//Grid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Site went down because Gen overload (20kva, 400A) SS=
 IHS Felix ZAMBE confirmed//Grid return","cedric.tiani@matech-cameroun.com"=
,"428","04-05-2025 08:31:32","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004946087","N=
koabang Ebolmedjock","","04-05-2025 08:22:18","04-05-2025 08:01:06","04-05-=
2025 08:11:13","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matec=
h-cameroun.com","1273","04-05-2025 08:22:18","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004945980","Sim=
e Building","","04-05-2025 07:51:18","04-05-2025 07:47:05","04-05-2025 07:5=
5:25","Grid outage, Site went down before Gen start due to poor backup // G=
en automatically started","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen automatically started","cedric.tiani=
@matech-cameroun.com","254","04-05-2025 07:51:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004945973","Yoko MTN=
","","04-05-2025 07:49:12","04-05-2025 07:43:37","04-05-2025 07:51:52","Cas=
caded Incident from TTO5067392","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE no power issue U:52.7V site on Gen=
. TX FME APPIAH Gregoire/654547479/ from Huawei is informed.","system","260=
419","04-05-2025 07:49:12","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0004945968","Ngo=
um","IHS_YND_473","04-05-2025 07:48:46","04-05-2025 07:43:37","04-05-2025 0=
7:51:52","ACTIVE no power issue U:52.7V site on Gen. TX FME APPIAH Gregoire=
/654547479/ from Huawei is informed.","Parker Tchoup","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE no=
 power issue U:52.7V site on Gen. TX FME APPIAH Gregoire/654547479/ from Hu=
awei is informed.","cedric.tiani@matech-cameroun.com","310","04-05-2025 07:=
48:46","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004945903","SIM=
BOCK BONAMBAPE","","04-05-2025 07:25:07","04-05-2025 07:22:50","04-05-2025 =
07:29:05","Grid outage, Site went down before Gen start due to poor backup =
// Gen automatically started ","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup // Gen automatically started ","cedri=
c.tiani@matech-cameroun.com","138","04-05-2025 07:25:07","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004945849","O=
LAMA","","04-05-2025 07:11:14","04-05-2025 07:06:54","04-05-2025 07:10:21",=
"No power issue on site U=3D54,9 V site on Gen , The Tx FME Etienne/6513201=
88/ from Huawei is informed","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on si=
te U=3D54,9 V site on Gen , The Tx FME Etienne/651320188/ from Huawei is in=
formed","cedric.tiani@matech-cameroun.com","261","04-05-2025 07:11:14","MAT=
ECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004945829","Ona=
ngondi (melen bikop)","","04-05-2025 07:07:20","04-05-2025 07:00:11","04-05=
-2025 07:27:21","Grid outage Site went down because Gen failed to start due=
 to hybrid system malfunction // he manually started the Gen	","Fanda Brice=
","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid outage Site w=
ent down because Gen failed to start due to hybrid system malfunction // he=
 manually started the Gen	","cedric.tiani@matech-cameroun.com","430","04-05=
-2025 07:07:20","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004945498","B=
arriere","","04-05-2025 05:12:38","04-05-2025 05:04:08","04-05-2025 08:20:0=
0","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed//Grid return","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went d=
own because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and co=
nfirmed//Grid return","christelle.ngonga@matech-cameroun.com","511","04-05-=
2025 05:12:38","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004945454","UPA=
C LP","","04-05-2025 04:55:07","04-05-2025 03:27:40","04-05-2025 05:56:53",=
"Active, no power issue, site on grid with U=3D55V Tx FME mand Ngetsa (??69=
9949553??) From Huawei is informed.","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issue,=
 site on grid with U=3D55V Tx FME mand Ngetsa (??699949553??) From Huawei i=
s informed.","franck.nkomot@matech-cameroun.com","5248","04-05-2025 04:55:0=
7","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_105","NOCINC0004945384","Omnispor=
t 3","","04-05-2025 04:24:40","03-05-2025 22:29:24","03-05-2025 22:29:29","=
	No power issue on site U=3D54.6V. TX HUAWEI Armand (699949553) is informed=
","Delor Telezing","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","	No power issue on site U=3D54V. TX HUAWEI A=
rmand (699949553) is informed","christelle.ngonga@matech-cameroun.com","213=
16","04-05-2025 04:24:40","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004945261","Man=
guiers Dispensaire","","04-05-2025 03:21:56","04-05-2025 02:53:39","04-05-2=
025 05:47:39","Grid outage,Site went down due to 02/04 rectifiers malfuncti=
oning on site//He reset it and manually started the Gen","Fabrice Pouakam",=
"Equipment Repair","Passive","Rectifier","Rectifier Module","Grid outage,Si=
te went down due to 02/04 rectifiers malfunctioning on site//He reset it an=
d manually started the Gen","franck.nkomot@matech-cameroun.com","1698","04-=
05-2025 03:21:56","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004945226","UPA=
C LP","","04-05-2025 02:57:05","04-05-2025 02:48:01","04-05-2025 03:21:01",=
"Grid outage. Site went down due to no space to deploy mobile Gen //Grid re=
turn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Grid outage. Site went down due to no space to deploy mobile Gen //Grid r=
eturn","franck.nkomot@matech-cameroun.com","545","04-05-2025 02:57:05","MAT=
ECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004945212","Lad=
a I Yde","","04-05-2025 02:46:29","04-05-2025 02:37:08","04-05-2025 05:42:0=
5","Active//No power issue site on Grid with U=3D54.9V Lionel Adjep(6551848=
76) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue site on Grid with U=3D53.4V Lionel Adjep(655184876) from Huawei is =
informed","franck.nkomot@matech-cameroun.com","562","04-05-2025 02:46:29","=
MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004945180","S=
atcom","","04-05-2025 02:19:44","04-05-2025 02:13:18","04-05-2025 02:34:18"=
,"No power issue site on Grid with Ubay:31.9V Tx Fme Armand Ngestsa (691144=
412) of huawei is inform","Delor Telezing","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on Grid with Ubay:31.9V Tx Fme Armand Ngestsa (691144412) of huawei is info=
rm","christelle.ngonga@matech-cameroun.com","387","04-05-2025 02:19:44","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004944943","SOA VILL=
AGE","","04-05-2025 00:47:22","04-05-2025 00:37:02","04-05-2025 01:45:02","=
Cascaded Incident from TTO5066196","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // He added water and manually =
start the gen","system","271546","04-05-2025 00:47:22","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004944920","S=
OA TOWN","IHS_YND_323","04-05-2025 00:37:12","04-05-2025 00:35:02","04-05-2=
025 01:46:02","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // He added water and manually start the gen","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage,=
 site went down because gen start and stopped with high temp alarm // He ad=
ded water and manually start the gen","christelle.ngonga@matech-cameroun.co=
m","131","04-05-2025 00:37:12","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004944834","M=
ANGUIERS CHAPELLE","","04-05-2025 00:12:55","04-05-2025 00:09:26","04-05-20=
25 02:45:25","site went down due to gen overload (22kva, 340A)  Sp HIS Bern=
ard ATANGANA is informed and confirmed//Grid return","Fabrice Pouakam","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","site went down due t=
o gen overload (22kva, 340A)  Sp HIS Bernard ATANGANA is informed and confi=
rmed//Grid return","kouoh.jean@ihstowers.com","210","04-05-2025 00:12:55","=
MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004944768","O=
mnisport 3","","03-05-2025 23:53:01","03-05-2025 19:45:33","03-05-2025 22:2=
9:16","Site went down due to PWC Overloaded (12K, 250A) // site stabilized =
SS IHS Alphonse confirmed","Delor Telezing","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Site went down due to PWC Over=
loaded (12K, 250A) // site stabilized SS IHS Alphonse confirmed","kouoh.jea=
n@ihstowers.com","14849","03-05-2025 23:53:01","MATECH CMR"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0004944715","M=
ONTEE NKONDENGUI","","03-05-2025 23:28:36","03-05-2025 23:18:44","05-05-202=
5 19:48:51","","Albran Byorel","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid only, no space to deploy MDG.//grid return","franc=
k.nkomot@matech-cameroun.com","427590","03-05-2025 23:28:36","MATECH CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004944708","M=
obil-Kondengui","IHS_YND_682","03-05-2025 23:26:57","03-05-2025 23:18:44","=
05-05-2025 19:48:51","Grid only, no space to deploy MDG.//grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid onl=
y, no space to deploy MDG.//grid return","franck.nkomot@matech-cameroun.com=
","494","03-05-2025 23:26:57","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004944497","Crf=
-Mbankolo-IHS","","03-05-2025 22:32:21","03-05-2025 22:27:13","03-05-2025 2=
3:08:13","Site down due to insufficient rectifiers on site // site stabilis=
ed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site down due to insufficient rectifiers on site // site stabilised",=
"franck.nkomot@matech-cameroun.com","334","03-05-2025 22:32:21","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004944441","Yoko MTN=
","","03-05-2025 22:18:50","03-05-2025 21:40:16","04-05-2025 03:43:16","","=
Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid outage, site went down because gen fails to start du to battery ge=
 faulty (SS IHS Felix is informed) // gen start with battery backup","syste=
m","289317","03-05-2025 22:18:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004944440","Matsari"=
,"","03-05-2025 22:18:49","03-05-2025 21:40:16","04-05-2025 03:43:16","Casc=
aded Incident from TTO5065599 - Cascade Removed From TTO5065599","Parker Tc=
houp","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid =
outage, site went down because gen fails to start du to battery ge faulty (=
SS IHS Felix is informed) // gen start with battery backup","system","28931=
7","03-05-2025 22:18:49","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0004944430","Ngo=
um","","03-05-2025 22:16:28","03-05-2025 21:40:16","04-05-2025 03:43:16","F=
me Ahanda is unreachable. Supervisor Parker and RM are informed","Parker Tc=
houp","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid =
outage, site went down because gen fails to start du to battery ge faulty (=
SS IHS Felix is informed) // gen start with battery backup","franck.nkomot@=
matech-cameroun.com","289317","03-05-2025 22:16:28","MATECH CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004944370","MBI=
MBIM","IHS_YND_460, IHS_YND_475, IHS_YND_473","03-05-2025 21:56:27","03-05-=
2025 21:40:16","04-05-2025 03:43:16"," Gen failed to start due to battery d=
ischarged  // gen start with external  battery ","Parker Tchoup","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Generator Battery"," Gen failed to st=
art due to battery discharged  // gen start with external  battery ","loic.=
noumsi@matech-cameroun.com","973","03-05-2025 21:56:27","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004944298","N=
omayos montee Meche","","03-05-2025 21:46:16","03-05-2025 21:44:10","03-05-=
2025 21:46:02","Active: No power issue, site is on grid with Ubaie=3D53.1V,=
 Flubert (654266068) from Huawei is informed","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue, site is on grid with Ubaie=3D53.1V, Flubert (654266068=
) from Huawei is informed","gaelle.njiofack@matech-cameroun.com","127","03-=
05-2025 21:46:16","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0004944211","E=
toug ebe Meweulo","","03-05-2025 21:29:57","03-05-2025 21:10:31","03-05-202=
5 22:03:42","Grid outage, site went down due to Grid bad voltage // He bypa=
ssed Grid and put site on Gen","Hyemafo Gildas","Grid Supply","Passive","Gr=
id","National Grid - Low Current Supply","Grid outage, site went down due t=
o Grid bad voltage // He bypassed Grid and put site on Gen","gaelle.njiofac=
k@matech-cameroun.com","1166","03-05-2025 21:29:57","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004943904","B=
arriere","","03-05-2025 20:34:52","03-05-2025 19:00:42","04-05-2025 04:31:4=
2","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // Grid stabilised","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site =
went down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed =
and confirmed // Grid stabilised","loic.noumsi@matech-cameroun.com","5651",=
"03-05-2025 20:34:52","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0004943817","Eto=
ug ebe Meweulo","","03-05-2025 20:18:04","03-05-2025 20:14:59","03-05-2025 =
20:18:24","Grid outage, site went down due to Grid bad voltage // He bypass=
ed Grid and put site on Gen","Hyemafo Gildas","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid outage, site went down du=
e to Grid bad voltage // He bypassed Grid and put site on Gen","loic.noumsi=
@matech-cameroun.com","420","03-05-2025 20:18:04","MATECH CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0004943386","OKO=
A Peage","","03-05-2025 19:04:42","03-05-2025 18:58:54","03-05-2025 19:00:4=
1","No power issue site on Gen U=3D55,5V TX FME HENRI /699949693 from huawe=
i is informed","Fanda Brice","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on Gen U=3D55,=
5V TX FME HENRI /699949693 from huawei is informed","loic.noumsi@matech-cam=
eroun.com","349","03-05-2025 19:04:42","MATECH CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0004943153","Bas=
tos Bir","","03-05-2025 18:09:27","03-05-2025 18:05:18","03-05-2025 18:30:0=
1","Grid outage, site went down due to Grid fluctuations // He bypassed Gri=
d and put Site on Gen","Mboua Thierry","Grid Supply","Passive","Grid","Nati=
onal Grid - Unstable Grid Supply Issue","Grid outage, site went down due to=
 Grid fluctuations // He bypassed Grid and put Site on Gen","loic.noumsi@ma=
tech-cameroun.com","355","03-05-2025 18:09:27","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004943037","E=
lig-Edzoa","","03-05-2025 17:51:13","03-05-2025 16:51:05","03-05-2025 20:34=
:10","Grid only site , Grid outage // Grid return","","Grid Supply","Passiv=
e","Grid","National Grid - Grid Outage Issue","Grid only site , Grid outage=
 // Grid return","gaelle.njiofack@matech-cameroun.com","3610","03-05-2025 1=
7:51:13","MATECH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004943016","Com=
plex Beac II","","03-05-2025 17:45:18","03-05-2025 17:40:58","03-05-2025 18=
:15:02","Grid outage, Site went down because disjuncction of Cb(32A) in DC =
BOX MTN // He rearmed CB(32A), site on gen","Albran Byorel","Equipment Repa=
ir","Passive","Control Panel","Circuit Breaker Tripped","Grid outage, Site =
went down because disjuncction of Cb(32A) in DC BOX MTN // He rearmed CB(32=
A), site on gen","loic.noumsi@matech-cameroun.com","261","03-05-2025 17:45:=
18","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004942747","O=
LAMA","","03-05-2025 16:41:02","03-05-2025 16:32:54","03-05-2025 16:50:00",=
"Active: No power issue on site Ubaie =3D54.3V,   The TX FME Henri (6999496=
93) from Huawei is informed","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power iss=
ue on site Ubaie =3D54.3V, The TX FME Henri (699949693) from Huawei is info=
rmed
","gaelle.njiofack@matech-cameroun.com","489","03-05-2025 16:41:02","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004942554","O=
mnisport 3","","03-05-2025 16:16:32","03-05-2025 16:09:25","03-05-2025 16:2=
8:25","	Site went down due to PWC Overloaded (12K, 250A) ","Delor Telezing"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Si=
te went down due to PWC Overloaded (12K, 250A) // site stabilized","gaelle.=
njiofack@matech-cameroun.com","428","03-05-2025 16:16:32","MATECH CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004942437","Av =
Kennedy","","03-05-2025 15:52:03","03-05-2025 15:43:38","03-05-2025 18:40:5=
4","Grid outage, access issue during the Weekend due to landlord & no space=
 to deploy MGE on site // Grid stabilised","","Grid Supply","Passive","Grid=
","National Grid - Grid Outage Issue","Grid outage, access issue during the=
 Weekend due to landlord & no space to deploy MGE on site // Grid stabilise=
d","cedric.tiani@matech-cameroun.com","506","03-05-2025 15:52:03","MATECH C=
MR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004942363","M=
ANGUIERS CHAPELLE","","03-05-2025 15:36:30","03-05-2025 13:58:09","04-05-20=
25 00:01:20","	site went down due to gen overload (22kva, 340A) SS HISBerna=
rd ATANGANA is informed and confirmed","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","site went down due to gen overload=
 (22kva, 340A) SS HISBernard ATANGANA is informed and confirmed//site stabi=
lised","gaelle.njiofack@matech-cameroun.com","36439","03-05-2025 15:36:30",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004942340","B=
arriere","","03-05-2025 15:32:10","03-05-2025 14:34:56","03-05-2025 18:36:1=
2","Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS F=
elix ZAMBE confirmed // Grid return","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because G=
en overload (20kva, 400A) SS IHS Felix ZAMBE confirmed// Grid return","gael=
le.njiofack@matech-cameroun.com","3435","03-05-2025 15:32:10","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004941762","Man=
guiers Dispensaire","","03-05-2025 13:53:57","03-05-2025 13:44:48","03-05-2=
025 14:00:56","Active // No power issue site on grid with U=3D54,8 V Tx Fme=
 Armand Ngestsa (691144412) of huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active // No power issue site on grid with U=3D54,8 V Tx Fme Armand N=
gestsa (691144412) of huawei is informed","cedric.tiani@matech-cameroun.com=
","550","03-05-2025 13:53:57","MATECH CMR"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0004941581","E=
zezang","","03-05-2025 13:20:31","03-05-2025 13:10:59","03-05-2025 15:00:12=
","Grid outage, site went down due to fuel shortage // Refuelling done","Pa=
rker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,=
 site went down due to fuel shortage // Refuelling done","loic.noumsi@matec=
h-cameroun.com","573","03-05-2025 13:20:31","MATECH CMR"
"Closed Complete","Warning","T0211","IHS_YND_393","NOCINC0004941414","Ezeza=
ng","","03-05-2025 12:53:28","","","Grid outage, site went down due to fuel=
 shortage // Refuelling done","Parker Tchoup","Warning","Warning","DIESEL",=
"Warning - Low Fuel Level","Grid outage, site went down due to fuel shortag=
e // Refuelling done","cedric.tiani@matech-cameroun.com","2168","03-05-2025=
 12:53:28","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004941399","E=
lig-Edzoa","","03-05-2025 12:50:16","03-05-2025 12:43:06","03-05-2025 14:08=
:24","	Site went down due to PWC Overloaded (12K,) // Site stabilized","","=
Cascade Outage","Passive","Cascade Passive","Cascade Passive","	Site went d=
own due to PWC Overloaded (12K,) // Site stabilized","vanel.mbiada@matech-c=
ameroun.com","278444","03-05-2025 12:50:16","MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004941392","Nko=
lmvack","","03-05-2025 12:49:00","03-05-2025 12:39:59","03-05-2025 13:49:39=
","ACTIVE// No power issue: Ubaie=3D51,6V site on Battery The Tx Fme Tsague=
( 690488850)from Huawei is informed ","Parker Tchoup","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// =
No power issue: Ubaie=3D51,6V site on Battery The Tx Fme Tsague( 690488850)=
from Huawei is informed ","cedric.tiani@matech-cameroun.com","542","03-05-2=
025 12:49:00","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0004941389","N=
taba","IHS_YND_133","03-05-2025 12:47:33","03-05-2025 12:43:06","03-05-2025=
 14:08:24","	Site went down due to PWC Overloaded (12K,) // Site stabilized=
","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","	Site went down due to PWC Overloaded (12K,) // Site stabil=
ized","vanel.mbiada@matech-cameroun.com","268","03-05-2025 12:47:33","MATEC=
H CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004941369","Cha=
rles-Atangana","","03-05-2025 12:40:13","03-05-2025 12:36:02","03-05-2025 1=
2:46:12","Active//No power issue on site ,site on Grid with Ubaie=3D48 V Th=
e TX FME Bertran(652586578) from Huawei is informed,","","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue on site ,site on Grid with Ubaie=3D48V The TX FME Bertran(=
652586578) from Huawei is informed,","cedric.tiani@matech-cameroun.com","25=
2","03-05-2025 12:40:13","MATECH CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0004941366","Jou=
vence 2000","","03-05-2025 12:39:39","03-05-2025 12:36:53","03-05-2025 12:4=
6:26","No power issue on site U=3D54,4 V site on grid The TX FME Armand Ngu=
etsa /691144412 from huawei is informed","Delor Telezing","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site U=3D54,4 V site on grid The TX FME Armand Nguetsa /691144=
412 from huawei is informed","cedric.tiani@matech-cameroun.com","167","03-0=
5-2025 12:39:39","MATECH CMR"
"Closed Complete","Site Down","T0211","IHS_YND_393","NOCINC0004941352","Eze=
zang","","03-05-2025 12:37:38","03-05-2025 12:18:22","03-05-2025 12:19:29",=
"wrongly created ticket","Parker Tchoup","Incorrectly Logged Tickets","Erro=
r","Error","Error","wrongly created ticket","cedric.tiani@matech-cameroun.c=
om","1157","03-05-2025 12:37:38","MATECH CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0004941347","A=
ngongo","","03-05-2025 12:36:19","03-05-2025 12:28:10","03-05-2025 13:28:19=
"," Hybrid gen site .site went down due to water infiltration in the tank//=
We purged water and gen manually started","Fanda Brice","Fuel Outage (Proba=
ble)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel"," Hybrid =
gen site .site went down due to water infiltration in the tank//We purged w=
ater and gen manually started","vanel.mbiada@matech-cameroun.com","490","03=
-05-2025 12:36:19","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004941264","Mim=
boman4","","03-05-2025 12:23:03","03-05-2025 12:19:43","03-05-2025 12:29:23=
","Grid outage,site went down because Gen failed to start (investigation on=
going)","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid outage,site went down because Gen failed to start (inv=
estigation ongoing)","cedric.tiani@matech-cameroun.com","201","03-05-2025 1=
2:23:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0004941204","Bastos-B=
AT","","03-05-2025 12:15:20","03-05-2025 12:03:00","03-05-2025 18:43:48","C=
ascaded Incident from TTO5061914","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Access Issue during the=
 Weekend due to landlord // Grid returned","system","288127","03-05-2025 12=
:15:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_206","NOCINC0004941203","ARMP",""=
,"03-05-2025 12:15:20","03-05-2025 12:03:00","03-05-2025 18:43:48","Cascade=
d Incident from TTO5061914","Mboua Thierry","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, Access Issue during the Weeke=
nd due to landlord // Grid returned","system","288127","03-05-2025 12:15:20=
","MATECH CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0004941178","Dra=
gage","","03-05-2025 12:11:41","03-05-2025 12:03:00","03-05-2025 18:43:48",=
"","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage, Access Issue during the Weekend due to landlord // Gri=
d returned","cedric.tiani@matech-cameroun.com","288127","03-05-2025 12:11:4=
1","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0004941169","ARM=
P Building","IHS_YND_192, IHS_YND_206, IHS_YND_129","03-05-2025 12:09:14","=
03-05-2025 12:03:00","03-05-2025 18:43:48","Grid outage, Access Issue durin=
g the Weekend due to landlord // Grid returned","Mboua Thierry","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, Acces=
s Issue during the Weekend due to landlord // Grid returned","cedric.tiani@=
matech-cameroun.com","374","03-05-2025 12:09:14","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004941148","M=
vog-Ada_OCM","","03-05-2025 12:06:42","03-05-2025 12:04:27","03-05-2025 12:=
25:54","Grid only no space // grid return","","Grid Supply","Passive","Grid=
","National Grid - Grid Outage Issue","Grid only no space // grid return","=
vanel.mbiada@matech-cameroun.com","136","03-05-2025 12:06:42","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004941125","S=
atcom","","03-05-2025 12:01:17","03-05-2025 11:59:56","03-05-2025 12:21:46"=
," No power issue site on Grid with Ubay:31.9V Tx Fme Armand Ngestsa (69114=
4412) of huawei is inform","Delor Telezing","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm"," No power issue sit=
e on Grid with Ubay:31.9V Tx Fme Armand Ngestsa (691144412) of huawei is in=
form","vanel.mbiada@matech-cameroun.com","82","03-05-2025 12:01:17","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0004941103","A=
RMP","","03-05-2025 11:57:00","03-05-2025 11:54:51","03-05-2025 18:40:36","=
Grid outage, access issue during the Weekend due to landlord // Grid return=
ed","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage, access issue during the Weekend due to landlord // Grid return=
ed","vanel.mbiada@matech-cameroun.com","130","03-05-2025 11:57:00","MATECH =
CMR"
"Closed Complete","Warning","T0772","IHS_YND_207","NOCINC0004940955","ARMP =
Building","","03-05-2025 11:27:32","","","Grid outage, Access Issue during =
the Weekend due to landlord // Grid returned","Mboua Thierry","Warning","Wa=
rning","POWER","Warning - Low Voltage","Grid outage, Access Issue during th=
e Weekend due to landlord // Grid returned","cedric.tiani@matech-cameroun.c=
om","1882","03-05-2025 11:27:32","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004940532","E=
kombitie","","03-05-2025 10:22:00","03-05-2025 10:12:59","03-05-2025 10:25:=
16","Active: no power issue, site is on Grid  with Ubaie=3D54.6V, Symphorie=
n(650257151) from huawei is informed","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active:=
 no power issue, site is on Grid  with Ubaie=3D54.6V, Symphorien(650257151)=
 from huawei is informed","cedric.tiani@matech-cameroun.com","542","03-05-2=
025 10:22:00","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004940230","M=
ANGUIERS CHAPELLE","","03-05-2025 09:20:57","03-05-2025 09:15:44","03-05-20=
25 13:45:25","site went down due to gen overload (22kva, 340A) SS HISBernar=
d ATANGANA is informed and confirmed//site stabilised","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","site went down due=
 to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and confi=
rmed//site stabilised","vanel.mbiada@matech-cameroun.com","314","03-05-2025=
 09:20:57","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004940016","O=
LAMA","","03-05-2025 08:25:57","03-05-2025 08:17:49","03-05-2025 08:20:19",=
"Active//No power issue on site Ubaie =3D55.1V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie =3D55.1V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","loic.noumsi@matech-cameroun.com","488","03-05-20=
25 08:25:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_721","NOCINC0004939965","VOIRIE M=
UNICIPALE YAOUNDE","","03-05-2025 08:01:59","03-05-2025 07:57:39","03-05-20=
25 09:15:56","Cascaded Incident from TTO5060547","Paul BIBOUM","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Grid outage.no space to=
 deploy mobile gen//grid power retun","system","260","03-05-2025 08:01:59",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_017","NOCINC0004939964","H-Depute=
s","","03-05-2025 08:01:59","03-05-2025 07:57:39","03-05-2025 09:15:56","Ca=
scaded Incident from TTO5060547","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage.no space to deploy mobile gen//grid po=
wer retun","system","260","03-05-2025 08:01:59","MATECH CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0004939957","E=
NAM","IHS_YND_017, IHS_YND_721","03-05-2025 07:59:50","03-05-2025 07:57:39"=
,"03-05-2025 09:17:51","Grid outage.no space to deploy mobile gen//grid pow=
er retun","","Grid Supply","Passive","Grid","National Grid - Grid Outage Is=
sue","Grid outage.no space to deploy mobile gen//grid power retun","vanel.m=
biada@matech-cameroun.com","132","03-05-2025 07:59:50","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004939907","M=
ANGUIERS CHAPELLE","","03-05-2025 07:46:13","02-05-2025 22:04:28","03-05-20=
25 08:46:57","Backtracking  site went down due to gen overload (22kva, 340A=
) SS HISBernard ATANGANA is informed and confirmed.//He reduced the load an=
d maually started the Gen","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","site went down due to gen overload (22kva, 340=
A) SS HISBernard ATANGANA is informed and confirmed.//He reduced the load a=
nd maually started the Gen","cedric.tiani@matech-cameroun.com","34906","03-=
05-2025 07:46:13","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004939841","Mom=
","","03-05-2025 07:21:03","03-05-2025 07:11:42","03-05-2025 09:33:58","Gri=
d outage, DG ran till fuel shortage // refueling done	","Fanda Brice","Fuel=
 Outage","Passive","Diesel","Diesel Outage","Grid outage, DG ran till fuel =
shortage // refueling done	","vanel.mbiada@matech-cameroun.com","562","03-0=
5-2025 07:21:03","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004939788","M=
essassi 2","","03-05-2025 07:01:33","03-05-2025 06:54:19","03-05-2025 08:13=
:07","Site went down because 04/06 rectifiers dysfuncionned// He reset rect=
ifiers, site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down because 04/06 rectifiers dysfuncion=
ned// He reset rectifiers, site on Gen","vanel.mbiada@matech-cameroun.com",=
"436","03-05-2025 07:01:33","MATECH CMR"
"Closed Complete","Site Down","CTR_063","IHS_YND_365","NOCINC0004939466","A=
kono","","03-05-2025 04:41:05","03-05-2025 04:33:59","03-05-2025 06:06:47",=
"Grid outage, Gen stopped because engine is already very old // Gen Start m=
anually (this site need a new Gen)","Fanda Brice","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Generator Faulty","Grid outage, Gen stopped because =
engine is already very old // Gen Start manually (this site need a new Gen)=
","edwige.kapawo@matech-cameroun.com","427","03-05-2025 04:41:05","MATECH C=
MR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004939451","Av =
Kennedy","","03-05-2025 04:30:39","03-05-2025 04:28:28","03-05-2025 07:19:4=
8","Grid , only site ,No psace for mobile gen //  grid restoration","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid , only=
 site ,No psace for mobile gen //  grid restoration","edwige.kapawo@matech-=
cameroun.com","132","03-05-2025 04:30:39","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004939345","O=
LAMA","","03-05-2025 03:44:31","03-05-2025 03:41:23","03-05-2025 04:27:20",=
"Active//No power issue on site Ubaie =3D54.1V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed.Noticed repetitive issues","Fanda Bri=
ce","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue on site Ubaie =3D54.1V site on Grid =
The TX FME Henri (699949693) from Huawei is informed.Noticed repetitive iss=
ues","edwige.kapawo@matech-cameroun.com","189","03-05-2025 03:44:31","MATEC=
H CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004939116","Mok=
olo Yaounde","","03-05-2025 02:27:12","03-05-2025 02:22:01","03-05-2025 02:=
34:03","Active // No power issue Ubay: 54.4 V site on grid. The Tx FME Elou=
ndou Bertrand (693212405) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //=
 No power issue Ubay: 54.4 V site on grid. The Tx FME Eloundou Bertrand (69=
3212405) from Huawei is informed","edwige.kapawo@matech-cameroun.com","312"=
,"03-05-2025 02:27:12","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004939112","Ron=
d Point Express1114","","03-05-2025 02:24:39","03-05-2025 02:20:28","03-05-=
2025 02:36:21","Grid outage, Site down due to poor battery backup // Gen st=
art automatically","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site down due to poor bat=
tery backup // Gen start automatically","edwige.kapawo@matech-cameroun.com"=
,"252","03-05-2025 02:24:39","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004939028","Oko=
lo Kilombo","","03-05-2025 02:02:09","03-05-2025 01:57:48","03-05-2025 02:2=
9:34","Active //no power issue Ubaie:54.7 V site on Grid The TX FME Synphor=
ien (675295205) from Huawei is informed.","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive //no power issue Ubaie:54.7 V site on Grid The TX FME Synphorien (67529=
5205) from Huawei is informed.","edwige.kapawo@matech-cameroun.com","262","=
03-05-2025 02:02:09","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004938648","B=
arriere","","03-05-2025 00:21:37","03-05-2025 00:19:25","03-05-2025 07:50:1=
5","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed//Grid return","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went d=
own because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and co=
nfirmed//Grid return","edwige.kapawo@matech-cameroun.com","133","03-05-2025=
 00:21:37","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004938506","E=
vodoula OCM","","02-05-2025 23:55:01","02-05-2025 23:45:59","03-05-2025 07:=
03:18","Site went down  due to 02/03 rectifiers faulty //He replaced it ","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down  due to 02/03 rectifiers faulty //He replaced it=
 ","edwige.kapawo@matech-cameroun.com","543","02-05-2025 23:55:01","MATECH =
CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004938485","M=
ambine","","02-05-2025 23:46:28","02-05-2025 23:36:59","03-05-2025 00:16:11=
","Grid outage, site went down because gen ran untill fuel shortage // Tank=
 inclined (Refueling ongoing)","Fanda Brice","Fuel Outage","Passive","Diese=
l","Diesel Outage","Grid outage, site went down because gen ran untill fuel=
 shortage // Tank inclined (Refueling ongoing)","edwige.kapawo@matech-camer=
oun.com","570","02-05-2025 23:46:28","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004938241","E=
kombitie","","02-05-2025 22:37:14","02-05-2025 22:34:05","02-05-2025 23:01:=
20","Active // No power issue, site is on Grid with Ubaie=3D54.5V, Symphori=
en(650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on Grid with Ubaie=3D54.5V, Symphorien(650257151/ huawei) is =
informed","edwige.kapawo@matech-cameroun.com","191","02-05-2025 22:37:14","=
MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0004938239","E=
lig Edzoa","","02-05-2025 22:36:46","02-05-2025 21:01:38","02-05-2025 23:16=
:31","Active // No power issue site on Grid with Ubay: 52.1V Tx Fme Armand =
Ngestsa (691144412 / huawei) is informed","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve // No power issue site on Grid with Ubay: 52.1V Tx Fme Armand Ngestsa (6=
91144412 / huawei) is informed","franck.nkomot@matech-cameroun.com","5709",=
"02-05-2025 22:36:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004938217","Saa","",=
"02-05-2025 22:32:37","02-05-2025 21:43:42","02-05-2025 21:43:43","Cascaded=
 Incident from TTO5058283","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","No Power Issue on Site, U=3D54.4V site on GEN =
-- TX FME Gregoire 654547479 of Huawei is informed","system","267701","02-0=
5-2025 22:32:37","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004937950","Mes=
sassi 2","","02-05-2025 21:47:22","02-05-2025 21:41:13","02-05-2025 21:49:1=
3","Grid outage, Site went down due to 02/06 rectifiers issue // Grid stabi=
lised","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Grid outage, Site went down due to 02/06 rectifiers issue // Gri=
d stabilised","franck.nkomot@matech-cameroun.com","370","02-05-2025 21:47:2=
2","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004937939","Emana Ly=
cee","","02-05-2025 21:45:59","02-05-2025 21:39:38","02-05-2025 21:59:10","=
Cascaded Incident from TTO5058170","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Fme Fabrice is infor=
med and reported poor backup battery // Grid returned","system","267886","0=
2-05-2025 21:45:59","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004937916","E=
mana lycee 2","IHS_YND_274","02-05-2025 21:44:51","02-05-2025 21:39:38","02=
-05-2025 21:59:10","Grid outage, Fme Fabrice is informed and reported poor =
backup battery // Grid returned","Fabrice Pouakam","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Fme Fabric=
e is informed and reported poor backup battery // Grid returned","franck.nk=
omot@matech-cameroun.com","314","02-05-2025 21:44:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0004937910","Messassi=
 okolo","","02-05-2025 21:44:17","02-05-2025 21:11:19","02-05-2025 21:42:56=
","Cascaded Incident from TTO5058155","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down due=
 to generator faulty // Grid returned","system","269557","02-05-2025 21:44:=
17","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004937903","E=
MANA BILICK CITY","IHS_YND_279","02-05-2025 21:43:33","02-05-2025 21:11:19"=
,"02-05-2025 21:42:56","Grid outage site went down due to generator faulty =
// Grid returned","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Faulty","Grid outage site went down due to generator fau=
lty // Grid returned","kouoh.jean@ihstowers.com","1935","02-05-2025 21:43:3=
3","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0004937712","O=
KOA Peage","IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_350, IHS_YND_349=
","02-05-2025 21:11:49","02-05-2025 20:55:39","02-05-2025 21:58:41","Site w=
ent down because 02/03 rectifier dysfunctionned // We reset rectifiers and =
site on grid","Fanda Brice","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down because 02/03 rectifier dysfunctionned // We r=
eset rectifiers and site on grid","franck.nkomot@matech-cameroun.com","970"=
,"02-05-2025 21:11:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004937660","Mandoumb=
a OCM","","02-05-2025 21:01:40","02-05-2025 20:55:39","02-05-2025 21:58:41"=
,"","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Site went down because 02/03 rectifier dysfunctionned // We rese=
t rectifiers and site on grid","system","1219929","02-05-2025 21:01:40","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004937661","Nkongtoc=
k","","02-05-2025 21:01:40","02-05-2025 20:55:39","02-05-2025 21:58:41","",=
"Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Site went down because 02/03 rectifier dysfunctionned // We reset re=
ctifiers and site on grid","system","1219930","02-05-2025 21:01:40","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004937651","M=
bankomo IHS","","02-05-2025 20:59:49","02-05-2025 20:55:39","02-05-2025 21:=
58:41","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Site went down because 02/03 rectifier dysfunctionned // We re=
set rectifiers and site on grid","franck.nkomot@matech-cameroun.com","12199=
31","02-05-2025 20:59:49","MATECH CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0004937626","N=
kenglikok","","02-05-2025 20:53:24","02-05-2025 20:55:39","02-05-2025 21:58=
:41","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Site went down because 02/03 rectifier dysfunctionned // We =
reset rectifiers and site on grid","franck.nkomot@matech-cameroun.com","121=
9931","02-05-2025 20:53:24","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004937620","M=
ambine","","02-05-2025 20:52:46","02-05-2025 20:55:39","02-05-2025 21:58:41=
","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Site went down because 02/03 rectifier dysfunctionned // We reset r=
ectifiers and site on grid","franck.nkomot@matech-cameroun.com","1219929","=
02-05-2025 20:52:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0004937582","Elig-Edz=
oa","","02-05-2025 20:44:37","30-04-2025 21:16:58","02-05-2025 18:14:57","C=
ascaded Incident from TTO5039193","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","site went down due to PWC Overload(12Kw 250A) Bla=
ise Raoul SS IHS is informed // Grid returned","system","434800","02-05-202=
5 20:44:37","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004937501","Mes=
sassi 2","","02-05-2025 20:19:23","02-05-2025 20:10:17","02-05-2025 20:29:1=
7","Grid outage, Site went down due to 02/06 rectifiers issue // Grid stabi=
lised","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Grid outage, Site went down due to 02/06 rectifiers issue // Gri=
d stabilised","franck.nkomot@matech-cameroun.com","548","02-05-2025 20:19:2=
3","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004937499","E=
mana lycee 2","IHS_YND_274","02-05-2025 20:18:32","02-05-2025 20:11:36","02=
-05-2025 20:35:36","Grid outage, Fme Fabrice is informed and reported poor =
backup battery // Grid returned","Fabrice Pouakam","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Fme Fabric=
e is informed and reported poor backup battery // Grid returned","franck.nk=
omot@matech-cameroun.com","417","02-05-2025 20:18:32","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004937496","E=
mana Lycee","","02-05-2025 20:17:00","02-05-2025 20:11:36","02-05-2025 20:3=
4:36","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, Fme Fabrice is informed and reported poor back=
up battery // Grid returned","franck.nkomot@matech-cameroun.com","265902","=
02-05-2025 20:17:00","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004937491","SAA=
 Entrance","","02-05-2025 20:15:04","02-05-2025 20:11:58","02-05-2025 21:27=
:58","Site went down because insufficient of rectifier on site SS IHS felix=
 Bate is informed//he excited the controller","Parker Tchoup","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down because insu=
fficient of rectifier on site SS IHS felix Bate is informed//he excited the=
 controller","franck.nkomot@matech-cameroun.com","187","02-05-2025 20:15:04=
","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004937411","Nko=
zoa","","02-05-2025 19:52:02","02-05-2025 19:45:39","02-05-2025 21:18:39","=
Site went down because gen failed to start due to grid bad voltage // He by=
passed the grid and gen manually started","Fabrice Pouakam","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Site went down b=
ecause gen failed to start due to grid bad voltage // He bypassed the grid =
and gen manually started","franck.nkomot@matech-cameroun.com","422","02-05-=
2025 19:52:02","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004937356","Oko=
lo Kilombo","","02-05-2025 19:37:19","02-05-2025 19:29:40","02-05-2025 19:4=
8:40","Active //no power issue Ubaie:54.7 V site on Grid The TX FME Synphor=
ien (675295205) from Huawei is informed.","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive //no power issue Ubaie:54.7 V site on Grid The TX FME Synphorien (67529=
5205) from Huawei is informed.","franck.nkomot@matech-cameroun.com","460","=
02-05-2025 19:37:19","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004937260","Mfo=
u EPC","","02-05-2025 19:21:11","02-05-2025 18:51:02","02-05-2025 19:36:02"=
,"Grid outage.gen failed to start due to batter GE discharged//Gen manually=
 started with external battery","Mba Lazare Herve","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Generator Battery","Grid outage.gen failed to start=
 due to batter GE discharged//Gen manually started with external battery","=
franck.nkomot@matech-cameroun.com","1810","02-05-2025 19:21:11","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004937104","ODZA MIN=
KAN EDIBI ASSI","","02-05-2025 18:58:58","02-05-2025 18:14:01","02-05-2025 =
19:31:01","Cascaded Incident from TTO5056869","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down due to CB=
(125A) which powered MTN equiments disjuncted//We rearmed CB","system","280=
273","02-05-2025 18:58:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004937103","Odza Min=
kan IHS","","02-05-2025 18:58:58","02-05-2025 18:14:01","02-05-2025 19:31:0=
1","Cascaded Incident from TTO5056869","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to CB(125A) =
which powered MTN equiments disjuncted//We rearmed CB","system","280272","0=
2-05-2025 18:58:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004937102","Mehanda =
1","","02-05-2025 18:58:58","02-05-2025 18:14:01","02-05-2025 19:31:01","Ca=
scaded Incident from TTO5056869","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to CB(125A) which =
powered MTN equiments disjuncted//We rearmed CB","system","280274","02-05-2=
025 18:58:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0004937101","Mbedoumo=
u - Ekali","","02-05-2025 18:58:57","02-05-2025 18:14:01","02-05-2025 19:31=
:01","Cascaded Incident from TTO5056869","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to CB(125A=
) which powered MTN equiments disjuncted//We rearmed CB","system","280272",=
"02-05-2025 18:58:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004936934","Odza II =
OCM","","02-05-2025 18:38:21","02-05-2025 18:14:01","02-05-2025 19:31:01","=
Cascaded Incident from TTO5056869","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to CB(125A) whic=
h powered MTN equiments disjuncted//We rearmed CB","system","280273","02-05=
-2025 18:38:21","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004936855","MEH=
ANDAN","","02-05-2025 18:24:30","02-05-2025 18:14:01","02-05-2025 19:31:01"=
,"","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Site went down due to CB(125A) which powered MTN equiments disjunc=
ted//We rearmed CB","franck.nkomot@matech-cameroun.com","280274","02-05-202=
5 18:24:30","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004936809","Nko=
lnda","IHS_YND_343, IHS_YND_528, IHS_YND_746, IHS_YND_527, IHS_YND_715, IHS=
_YND_749","02-05-2025 18:18:20","02-05-2025 18:14:01","02-05-2025 19:31:01"=
,"Site went down due to CB(125A) which powered MTN equiments disjuncted//We=
 rearmed CB","Albran Byorel","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Circuit Breaker Issue","Site went down due to CB(125A) whic=
h powered MTN equiments disjuncted//We rearmed CB","franck.nkomot@matech-ca=
meroun.com","260","02-05-2025 18:18:20","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004936754","E=
kombitie","","02-05-2025 18:09:23","02-05-2025 18:02:15","02-05-2025 18:10:=
40","No power issue, site is on Grid with Ubaie=3D54.5V, Symphorien(6502571=
51/ huawei) is informed","Fabrice Pouakam","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site=
 is on Grid with Ubaie=3D54.5V, Symphorien(650257151/ huawei) is informed",=
"loic.noumsi@matech-cameroun.com","429","02-05-2025 18:09:23","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004936679","Men=
dong NB","","02-05-2025 17:57:36","02-05-2025 17:51:29","02-05-2025 18:10:0=
9","Grid outage, Site went down because CB 100A faulty in Pwc//He rearmed t=
he CB","","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gri=
d outage, Site went down because CB 100A faulty in Pwc//He rearmed the CB",=
"loic.noumsi@matech-cameroun.com","368","02-05-2025 17:57:36","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004936481","B=
arriere","","02-05-2025 17:30:15","02-05-2025 17:16:13","03-05-2025 00:15:2=
3","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // Grid stabilised","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site =
went down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed =
and confirmed // Grid stabilised","loic.noumsi@matech-cameroun.com","843","=
02-05-2025 17:30:15","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004936315","Nko=
l-Mbanda","","02-05-2025 17:18:04","02-05-2025 17:12:36","02-05-2025 17:28:=
38","Site went down due to Work make by IHS SS and FME(Configuration of ZTE=
 bay) //End of work","MINKA NICOLAS","Equipment Replacement","Passive","Pla=
nned Activity","Planned Activity - Passive","Site went down due to Work mak=
e by IHS SS and FME(Configuration of ZTE bay) //End of work","loic.noumsi@m=
atech-cameroun.com","329","02-05-2025 17:18:04","MATECH CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0004935993","Omn=
isport-Rail","","02-05-2025 16:43:42","02-05-2025 16:40:34","02-05-2025 17:=
12:43","Site went down due to cable which powered DC BOX is burnt//We repla=
ced the cable and site on gen","Delor Telezing","Equipment Repair","Passive=
","Infrastructure","Armoured Cable","Site went down due to cable which powe=
red DC BOX is burnt//We replaced the cable and site on gen","franck.nkomot@=
matech-cameroun.com","189","02-05-2025 16:43:42","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0004935860","S=
ous Prefecture","","02-05-2025 16:31:52","02-05-2025 16:22:46","02-05-2025 =
16:39:24","No power issue site on Gen Ubaie =3D55.2V, The tx Huawei Fulbert=
 (654266068) is informed","Fanda Brice","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
Gen Ubaie =3D55.2V, The tx Huawei Fulbert (654266068) is informed","franck.=
nkomot@matech-cameroun.com","547","02-05-2025 16:31:52","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004935842","Mon=
tee Jouvence","","02-05-2025 16:29:23","02-05-2025 16:23:14","02-05-2025 17=
:40:59","Grid outage gen failed to start due to battery GE discharged causi=
ng by static charger faulty// Grid restored","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage gen fail=
ed to start due to battery GE discharged causing by static charger faulty//=
 Grid restored","loic.noumsi@matech-cameroun.com","370","02-05-2025 16:29:2=
3","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004935469","Emana Ly=
cee","","02-05-2025 16:02:50","02-05-2025 15:45:02","02-05-2025 16:02:18","=
Cascaded Incident from TTO5055236","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Fme Fabrice is infor=
med and reported poor backup battery // Grid returned","system","267531","0=
2-05-2025 16:02:50","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004935436","Ebo=
go","","02-05-2025 15:56:31","02-05-2025 15:41:25","02-05-2025 16:01:25","A=
ctive// No Power issue on site Ubaie 53V site on Grid, Julien /693095849 fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issue =
on site Ubaie 53V site on Grid, Julien /693095849 from Huawei is informed",=
"loic.noumsi@matech-cameroun.com","908","02-05-2025 15:56:31","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004935426","Mes=
sassi 2","","02-05-2025 15:54:57","02-05-2025 15:40:40","02-05-2025 16:05:2=
2","Grid outage, Site went down due to 02/06 rectifiers issue // Grid stabi=
lised","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Grid outage, Site went down due to 02/06 rectifiers issue // Gri=
d stabilised","franck.nkomot@matech-cameroun.com","858","02-05-2025 15:54:5=
7","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004935347","E=
mana lycee 2","IHS_YND_274","02-05-2025 15:48:17","02-05-2025 15:45:02","02=
-05-2025 16:02:18","Grid outage, Fme Fabrice is informed and reported poor =
backup battery // Grid returned","Fabrice Pouakam","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Fme Fabric=
e is informed and reported poor backup battery // Grid returned","franck.nk=
omot@matech-cameroun.com","196","02-05-2025 15:48:17","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004935028","B=
arriere","","02-05-2025 15:09:34","02-05-2025 14:57:25","02-05-2025 17:01:5=
7","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // Grid stabilised","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site =
went down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed =
and confirmed // Grid stabilised","loic.noumsi@matech-cameroun.com","730","=
02-05-2025 15:09:34","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004934913","M=
ANGUIERS CHAPELLE","","02-05-2025 14:52:59","02-05-2025 14:13:51","02-05-20=
25 15:03:32","Grid outage, site went down due to gen overload (22kva, 340A)=
 SS HISBernard ATANGANA is informed and confirmed//Grid return","Fabrice Po=
uakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge, site went down due to gen overload (22kva, 340A) SS HISBernard ATANGANA=
 is informed and confirmed//Grid return","loic.noumsi@matech-cameroun.com",=
"2350","02-05-2025 14:52:59","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004934756","N=
koabang Ebolmedjock","","02-05-2025 14:30:40","02-05-2025 14:25:32","02-05-=
2025 14:26:04","Active//No power issue, Site on Gen. The Tx FME Brice Tsagu=
e(650214096) from Huawei is informed. Notice that it is impacted by Nkolmes=
seng-Abom Not Manager By IHS","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","Active=
//No power issue, Site on Gen. The Tx FME Brice Tsague(650214096) from Huaw=
ei is informed. Notice that it is impacted by Nkolmesseng-Abom Not Manager =
By IHS","franck.nkomot@matech-cameroun.com","309","02-05-2025 14:30:40","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004934685","N=
koabang2","","02-05-2025 14:18:03","02-05-2025 14:02:50","02-05-2025 15:13:=
34","Grid outage.gen failed to start due to alarm '' high temp''//We add wa=
ter and gen manually started ","Mba Lazare Herve","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage=
.gen failed to start due to alarm '' high temp''//We add water and gen manu=
ally started ","loic.noumsi@matech-cameroun.com","914","02-05-2025 14:18:03=
","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004934680","A=
kak-Nkozoa-MTN-IHS","","02-05-2025 14:16:57","02-05-2025 14:07:48","02-05-2=
025 15:55:11","Grid outage, site went down due to fuel shortage // Refuelli=
ng done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage, site went down due to fuel shortage // Refuelling done","loi=
c.noumsi@matech-cameroun.com","550","02-05-2025 14:16:57","MATECH CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004934311","M=
imboman-Village","","02-05-2025 13:17:02","02-05-2025 13:12:52","02-05-2025=
 13:15:41","No power issue on site ,site on Grid with U=3D54.14V The TX FME=
 Eloundou Bertrand/ 693212405 of huawei is informed.","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site ,site on Grid with U=3D54.14V The TX FME E=
loundou Bertrand/ 693212405 of huawei is informed.","loic.noumsi@matech-cam=
eroun.com","251","02-05-2025 13:17:02","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004934254","Ngo=
usso Vallee","","02-05-2025 13:07:39","02-05-2025 12:58:28","02-05-2025 13:=
15:51","Grid outage,site went down because Gen started and stopped with ala=
rm ''low oil pressure'' // he reset the Gen Card and site on Grid ","Siliga=
p Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Oil Pressure Senso=
r Faulty","Grid outage,site went down because Gen started and stopped with =
alarm ''low oil pressure'' // he reset the Gen Card and site on Grid ","loi=
c.noumsi@matech-cameroun.com","551","02-05-2025 13:07:39","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004934242","M=
essassi okolo","","02-05-2025 13:05:09","02-05-2025 12:56:35","02-05-2025 1=
3:00:55","ACTIVE//No power issue on site Ubaie=3D54.4V, site on Grid The TX=
 Fme Synphorien 691316854 of Huawei is informed.Noticed impacted by pont em=
mana","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue on site Ubaie=3D=
54.4V, site on Grid The TX Fme Synphorien 691316854 of Huawei is informed.N=
oticed impacted by pont emmana","loic.noumsi@matech-cameroun.com","516","02=
-05-2025 13:05:09","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004934237","E=
MANA BILICK CITY","","02-05-2025 13:03:37","02-05-2025 12:55:21","02-05-202=
5 13:16:34","Grid outage site went down due to generator faulty // Grid ret=
urned","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ge=
nerator Faulty","Grid outage site went down due to generator faulty // Grid=
 returned","loic.noumsi@matech-cameroun.com","497","02-05-2025 13:03:37","M=
ATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004934078","Mes=
sassi 2","","02-05-2025 12:42:49","02-05-2025 12:36:43","02-05-2025 13:24:5=
8","Grid outage, Site went down due to 02/06 rectifiers issue // Grid stabi=
lised","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Grid outage, Site went down due to 02/06 rectifiers issue // Gri=
d stabilised","loic.noumsi@matech-cameroun.com","368","02-05-2025 12:42:49"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004934075","Emana Ly=
cee","","02-05-2025 12:42:16","02-05-2025 12:37:39","02-05-2025 13:14:52","=
Cascaded Incident from TTO5053779","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Fme Fabrice is infor=
med and reported poor backup battery // Grid returned","system","264207","0=
2-05-2025 12:42:16","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004934065","E=
mana lycee 2","IHS_YND_274","02-05-2025 12:40:47","02-05-2025 12:37:39","02=
-05-2025 13:14:52","Grid outage, Fme Fabrice is informed and reported poor =
backup battery // Grid returned","Fabrice Pouakam","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Fme Fabric=
e is informed and reported poor backup battery // Grid returned","loic.noum=
si@matech-cameroun.com","189","02-05-2025 12:40:47","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004933945","Nko=
l-Mbanda","","02-05-2025 12:18:11","02-05-2025 12:11:05","02-05-2025 12:27:=
29","Site went down due to Work make by IHS SS and FME(Configuration of ZTE=
 bay) //End of work","MINKA NICOLAS","Installation Activity","Passive","Pla=
nned Activity","Installation Activity","Site went down due to Work make by =
IHS SS and FME(Configuration of ZTE bay) //End of work","loic.noumsi@matech=
-cameroun.com","427","02-05-2025 12:18:11","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004933591","B=
arriere","","02-05-2025 11:19:44","02-05-2025 11:09:27","02-05-2025 14:23:0=
4","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // Grid returned","Hyemafo Gildas","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site we=
nt down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed an=
d confirmed // Grid returned","loic.noumsi@matech-cameroun.com","619","02-0=
5-2025 11:19:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_148","NOCINC0004933491","Chapelle=
-Nsimeyong","","02-05-2025 11:07:07","02-05-2025 10:18:13","02-05-2025 10:5=
4:38","Cascaded Incident from TTO5053040","MINKA NICOLAS","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down due to IHS wo=
rk by Francois Ndoungou(Checking of PWC ZTE) //End of work","system","2934"=
,"02-05-2025 11:07:07","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004933424","Nko=
l-Mbanda","IHS_YND_562, IHS_YND_148","02-05-2025 10:54:38","02-05-2025 10:1=
8:13","02-05-2025 10:54:38","Site went down due to IHS work by Francois Ndo=
ungou(Checking of PWC ZTE) //End of work","MINKA NICOLAS","Installation Act=
ivity","Passive","Planned Activity","Installation Activity","Site went down=
 due to IHS work by Francois Ndoungou(Checking of PWC ZTE) //End of work","=
loic.noumsi@matech-cameroun.com","2426","02-05-2025 10:54:38","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004933332","A=
ccacia New","","02-05-2025 10:36:25","02-05-2025 10:18:13","02-05-2025 10:5=
4:38","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Site went down due to IHS work by Francois Ndoungou(Checking of PWC ZTE) /=
/End of work","loic.noumsi@matech-cameroun.com","1093","02-05-2025 10:36:25=
","MATECH CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0004933193","Omn=
isport-Rail","","02-05-2025 10:13:55","02-05-2025 10:08:50","02-05-2025 10:=
20:50","site went down due to cable which powered DC BOX is burnt//We fixed=
 the cable and site on gen","Delor Telezing","Equipment Repair","Passive","=
Infrastructure","Armoured Cable","site went down due to cable which powered=
 DC BOX is burnt//We fixed the cable and site on gen","loic.noumsi@matech-c=
ameroun.com","306","02-05-2025 10:13:55","MATECH CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0004932576","OKO=
A Peage","","02-05-2025 08:54:11","02-05-2025 08:48:03","02-05-2025 08:50:0=
5","ACTIVE No power issue site on Gen U=3D54,9V TX FME HENRI /699949693 fro=
m huawei is informed","Fanda Brice","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power issue site =
on Gen U=3D54,9V TX FME HENRI /699949693 from huawei is informed","loic.nou=
msi@matech-cameroun.com","368","02-05-2025 08:54:11","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004932558","SAA=
 Entrance","","02-05-2025 08:49:23","02-05-2025 08:42:11","02-05-2025 09:32=
:29","Grid outage gen failed to start due to battery GE discharged causing =
by static charger faulty//Gen manually started with external battery","Park=
er Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batter=
y","Grid outage gen failed to start due to battery GE discharged causing by=
 static charger faulty//Gen manually started with external battery","loic.n=
oumsi@matech-cameroun.com","433","02-05-2025 08:49:23","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004932535","A=
WAE OCM","","02-05-2025 08:45:09","02-05-2025 08:39:58","02-05-2025 09:36:5=
6","site went down due to work by Sephane from CLEANIT(working on ZTE BAY )=
//End of work","Mba Lazare Herve","Installation Activity","Passive","Planne=
d Activity","Installation Activity","site went down due to work by Sephane =
from CLEANIT(working on ZTE BAY )//End of work","loic.noumsi@matech-camerou=
n.com","313","02-05-2025 08:45:09","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004932512","B=
arriere","","02-05-2025 08:40:50","01-05-2025 20:51:34","02-05-2025 10:15:4=
6","grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed//Grid return","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","grid outage, Site went d=
own because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and co=
nfirmed//Grid return","loic.noumsi@matech-cameroun.com","42557","02-05-2025=
 08:40:50","MATECH CMR"
"Closed Complete","Site Down","T0287","IHS_YND_038","NOCINC0004932460","Sia=
ntou Inferieur","","02-05-2025 08:28:21","02-05-2025 08:23:12","02-05-2025 =
08:43:13","Grid outage, no space to deploy //Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space=
 to deploy //Grid return","loic.noumsi@matech-cameroun.com","310","02-05-20=
25 08:28:21","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0004931884","O=
KOA Peage","IHS_YND_367, IHS_YND_348, IHS_YND_339, IHS_YND_350, IHS_YND_335=
, IHS_YND_349","02-05-2025 06:08:00","02-05-2025 05:59:59","02-05-2025 06:0=
3:13","Grid outage site went down because Gen stopped with alarm HIGH temp =
due to Radiator pierced // Headded water and Gen manually started","Fanda B=
rice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Ra=
diator Leakage","Grid outage site went down because Gen stopped with alarm =
HIGH temp due to Radiator pierced // Headded water and Gen manually started=
","gerard.tchangoue@matech-cameroun.com","482","02-05-2025 06:08:00","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004931857","Mambine"=
,"","02-05-2025 06:00:05","02-05-2025 05:59:59","02-05-2025 06:03:13","Casc=
aded Incident from TTO5051231 - Cascade Removed From TTO5051231","Fanda Bri=
ce","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage site went down because Gen stopped with alarm HIGH temp due to Radiato=
r pierced // Headded water and Gen manually started","system","266699","02-=
05-2025 06:00:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004931858","Nkongtoc=
k","","02-05-2025 06:00:05","02-05-2025 05:59:59","02-05-2025 06:03:13","Ca=
scaded Incident from TTO5051231 - Cascade Removed From TTO5051231","Kemeni =
Franklin","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage site went down because Gen stopped with alarm HIGH temp due to R=
adiator pierced // Headded water and Gen manually started","system","266698=
","02-05-2025 06:00:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004931856","Mandoumb=
a OCM","","02-05-2025 06:00:05","02-05-2025 05:59:59","02-05-2025 06:03:13"=
,"Cascaded Incident from TTO5051231 - Cascade Removed From TTO5051231","Kem=
eni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","Grid outage site went down because Gen stopped with alarm HIGH temp due =
to Radiator pierced // Headded water and Gen manually started","system","26=
6699","02-05-2025 06:00:05","MATECH CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0004931832","N=
kenglikok","","02-05-2025 05:51:53","02-05-2025 05:59:59","02-05-2025 06:03=
:13","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage site went down because Gen stopped with alarm HI=
GH temp due to Radiator pierced // Headded water and Gen manually started",=
"gerard.tchangoue@matech-cameroun.com","266698","02-05-2025 05:51:53","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004931818","Angongo"=
,"","02-05-2025 05:46:19","02-05-2025 05:59:59","02-05-2025 06:03:13","Casc=
aded Incident from TTO5051199 - Cascade Removed From TTO5051199","Fanda Bri=
ce","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage site went down because Gen stopped with alarm HIGH temp due to Radiato=
r pierced // Headded water and Gen manually started","system","266700","02-=
05-2025 05:46:19","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004931808","E=
beba","","02-05-2025 05:42:19","02-05-2025 05:59:59","02-05-2025 06:03:13",=
"","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage site went down because Gen stopped with alarm HIGH temp d=
ue to Radiator pierced // Headded water and Gen manually started","gerard.t=
changoue@matech-cameroun.com","266700","02-05-2025 05:42:19","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004931799","Nom=
ayos montee Meche","","02-05-2025 05:39:17","02-05-2025 05:38:09","02-05-20=
25 05:42:05","Active: No power issue, site is on grid with Ubaie=3D51.2V, F=
lubert (654266068) from Huawei is informed","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue, site is on grid with Ubaie=3D51.2V, Flubert (654266068) =
from Huawei is informed","edwige.kapawo@matech-cameroun.com","69","02-05-20=
25 05:39:17","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004931737","Nko=
l-Mbanda","","02-05-2025 05:14:42","02-05-2025 05:09:59","02-05-2025 08:23:=
15","Site went down due to IHS work by Francois Ndoungou(Checking of PWC ZT=
E) //End of work ","MINKA NICOLAS","Installation Activity","Passive","Plann=
ed Activity","Installation Activity","Site went down due to IHS work by Fra=
ncois Ndoungou(Checking of PWC ZTE) //End of work ","edwige.kapawo@matech-c=
ameroun.com","284","02-05-2025 05:14:42","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004931716","MBA=
LNGONG LYCEE","","02-05-2025 05:06:10","02-05-2025 04:44:43","02-05-2025 07=
:05:15","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid returned","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","edwige.kapawo@=
matech-cameroun.com","1289","02-05-2025 05:06:10","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004931546","M=
bankomo IHS","","02-05-2025 04:18:01","02-05-2025 04:10:52","02-05-2025 05:=
07:02","Grid outage, Site went down due to Oil pressure alarm// Oil added a=
nd Gen started","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Low Oil Pressure","Grid outage, Site went down due to Oil pressure alarm=
// Oil added and Gen started","gerard.tchangoue@matech-cameroun.com","430",=
"02-05-2025 04:18:01","MATECH CMR"
"Closed Complete","Site Down","CTR_401","IHS_YND_041","NOCINC0004931495","L=
ycee Leclerc School","","02-05-2025 04:09:36","02-05-2025 03:59:59","02-05-=
2025 04:11:19","Active// No power issue on site ,UBAIE=3D54.9V site is on G=
RID and the FME TX MBAH OSIAH (699699694) from huawei is informed","Paul BI=
BOUM","Customer Equipment Failure","Active","Active Equipment Failure","Aff=
ected by 3rd Party Site","Active// No power issue on site ,UBAIE=3D54.9V si=
te is on GRID and the FME TX MBAH OSIAH (699699694) from huawei is informed=
","gerard.tchangoue@matech-cameroun.com","578","02-05-2025 04:09:36","MATEC=
H CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0004931356","Mae=
tur","","02-05-2025 03:07:39","02-05-2025 03:05:29","02-05-2025 03:59:29","=
Grid Outage, site went down because Gen stopped due to ""Digital Input b"" =
alarm //He reset Card Gen and gen manually started","Mboua Thierry","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage, site =
went down because Gen stopped due to ""Digital Input b"" alarm //He reset C=
ard Gen and gen manually started","edwige.kapawo@matech-cameroun.com","131"=
,"02-05-2025 03:07:39","MATECH CMR"
"Cancelled","Warning","T1851","IHS_YND_330","NOCINC0004931188","OKOA Peage"=
,"","02-05-2025 02:27:55","","","Active// No power issue on site Ubaie: 55.=
3 V site On Gen The Tx FME Fulbert(654266068) of huawei is informed","Fanda=
 Brice","","","","","","edwige.kapawo@matech-cameroun.com","188","02-05-202=
5 02:27:55","MATECH CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0004931159","Omn=
isport-Rail","","02-05-2025 02:19:46","01-05-2025 16:35:29","02-05-2025 02:=
34:34","Active // No power issue on site Ubaie: 50.2V site on Grid The TX F=
ME Armand Nguetsa (699949553) from huawei is informed. (Back traking)","Del=
or Telezing","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active // No power issue on site Ubaie: 50.2V site=
 on Grid The TX FME Armand Nguetsa (699949553) from huawei is informed. (Ba=
ck traking)","ludivine.ngamaleu@ihstowers.com","35058","02-05-2025 02:19:46=
","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004931059","SAA=
 Entrance","","02-05-2025 01:39:20","02-05-2025 01:37:59","02-05-2025 02:01=
:33","Site went down because insufficient of rectifier on site SS IHS felix=
 Bate is informed//he excited the controller","Parker Tchoup","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down because insu=
fficient of rectifier on site SS IHS felix Bate is informed//he excited the=
 controller","edwige.kapawo@matech-cameroun.com","82","02-05-2025 01:39:20"=
,"MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004930769","Nko=
l-Mbanda","","02-05-2025 00:41:18","02-05-2025 00:32:59","02-05-2025 02:36:=
51","Grid outage, site went down because Gen started and stopped with"" ala=
rm overvoltage"" //He reset the Gen card site on gen","MINKA NICOLAS","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, sit=
e went down because Gen started and stopped with"" alarm overvoltage"" //He=
 reset the Gen card site on gen","edwige.kapawo@matech-cameroun.com","500",=
"02-05-2025 00:41:18","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004930571","C=
rf-Nkolbisson","","01-05-2025 23:53:58","01-05-2025 23:51:20","01-05-2025 2=
3:59:20","Eneo outage, site went down due to the controller has not given t=
he start command  // controller reseted and manual start of DG","TIENTCHEU =
NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Eneo outage, site went down due to the controller has not given the st=
art command  // controller reseted and manual start of DG","gerard.tchangou=
e@matech-cameroun.com","160","01-05-2025 23:53:58","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004930560","M=
ANGUIERS CHAPELLE","","01-05-2025 23:51:24","01-05-2025 23:46:14","02-05-20=
25 00:54:23","Grid outage, site went down due to gen overload (22kva, 340A)=
 SS HISBernard ATANGANA is informed and confirmed","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went=
 down due to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed =
and confirmed","gerard.tchangoue@matech-cameroun.com","311","01-05-2025 23:=
51:24","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004930539","Nko=
l-Mbanda","","01-05-2025 23:39:34","01-05-2025 23:32:14","01-05-2025 23:44:=
59","Grid outage, site went down because Gen started and stopped with"" ala=
rm overvoltage"" //He reset the Gen card site on gen","MINKA NICOLAS","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, sit=
e went down because Gen started and stopped with"" alarm overvoltage"" //He=
 reset the Gen card site on gen","ludivine.ngamaleu@ihstowers.com","441","0=
1-05-2025 23:39:34","MATECH CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004930309","Cha=
rles-Atangana","IHS_YND_051","01-05-2025 22:44:07","01-05-2025 22:39:58","0=
2-05-2025 00:05:08"," Grid only site ,no space to deploy MGE // Grid restor=
ation","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
"," Grid only site ,no space to deploy MGE // Grid restoration ","edwige.ka=
pawo@matech-cameroun.com","250","01-05-2025 22:44:07","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004930304","Mok=
olo Yaounde","","01-05-2025 22:43:31","01-05-2025 22:38:23","01-05-2025 23:=
59:18","Active // No power issue Ubay: 53V site on grid. The Tx FME Eloundo=
u Bertrand (693212405) from Huawei is informed","","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue Ubay: 53V site on grid. The Tx FME Eloundou Bertrand (69321240=
5) from Huawei is informed","edwige.kapawo@matech-cameroun.com","309","01-0=
5-2025 22:43:31","MATECH CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004930290","M=
amch Building","","01-05-2025 22:40:28","01-05-2025 22:39:58","01-05-2025 2=
3:56:43","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive"," Grid only site ,no space to deploy MGE // Grid restoratio=
n ","olivier.kwedi@ihstowers.com","1220885","01-05-2025 22:40:28","MATECH C=
MR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004930144","M=
ontee-Des-Soeurs","","01-05-2025 22:02:27","01-05-2025 21:53:07","01-05-202=
5 22:10:43","No power issue, site is on grid with Ubaie: 54.6V, Mbah hosiah=
(699699694) from Huawei is informed","Hyemafo Gildas","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue, site is on grid with Ubaie: 54.6V, Mbah hosiah(699699694) from Huawe=
i is informed","christelle.ngonga@matech-cameroun.com","561","01-05-2025 22=
:02:27","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004929746","ELO=
UMDEM CARRIERE","","01-05-2025 20:55:51","01-05-2025 20:52:07","02-05-2025 =
06:37:44","Grid outage site went down due to bad grid voltage//We bypass gr=
id and gen manualy started ","Fanda Brice","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","Grid outage site went down due to=
 bad grid voltage//We bypass grid and gen manualy started ","franck.nkomot@=
matech-cameroun.com","225","01-05-2025 20:55:51","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004929566","Oko=
lo Kilombo","","01-05-2025 20:32:52","01-05-2025 20:26:36","02-05-2025 05:3=
6:37","Site went down due to insufficiency of rectifiers // Grid returned",=
"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficiency of rectifiers // Grid returned","fr=
anck.nkomot@matech-cameroun.com","377","01-05-2025 20:32:52","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004929087","C=
rf-Nkolbisson","","01-05-2025 19:17:47","01-05-2025 19:14:38","01-05-2025 1=
9:58:38","Grid fluctuation, site went down because gen fails to start due t=
o grid bad voltage // Grid stabilized","TIENTCHEU NZETCHIEU GAEL","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, site went down because gen fails to start due to grid bad voltage /=
/ Grid stabilized","christelle.ngonga@matech-cameroun.com","190","01-05-202=
5 19:17:47","MATECH CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0004929080","N=
kol-Mbanda","","01-05-2025 19:15:18","01-05-2025 19:13:12","01-05-2025 21:3=
4:12","Grid outage, site went down because Gen started and stopped with"" a=
larm overvoltage"" //He reset the Gen card site on gen","MINKA NICOLAS","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, s=
ite went down because Gen started and stopped with"" alarm overvoltage"" //=
He reset the Gen card site on gen","franck.nkomot@matech-cameroun.com","127=
","01-05-2025 19:15:18","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004928916","N=
omayos montee Meche","","01-05-2025 18:39:02","01-05-2025 18:38:58","01-05-=
2025 19:23:41","Active: No power issue, site is on grid with Ubaie=3D53.1V,=
 Flubert (654266068) from Huawei is informed","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue, site is on grid with Ubaie=3D53.1V, Flubert (654266068=
) from Huawei is informed","christelle.ngonga@matech-cameroun.com","5","01-=
05-2025 18:39:02","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004928570","N=
YOM 2 IHS","","01-05-2025 17:38:21","01-05-2025 17:32:13","01-05-2025 19:01=
:37","Grid fluctuation,site went down because Gen failed to start due to Gr=
id bad voltage// Grid stabilisation","Fabrice Pouakam","Grid Supply","Passi=
ve","Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuation,s=
ite went down because Gen failed to start due to Grid bad voltage// Grid st=
abilisation","christelle.ngonga@matech-cameroun.com","369","01-05-2025 17:3=
8:21","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004928373","H=
-General-Yde","","01-05-2025 17:07:00","01-05-2025 16:59:49","01-05-2025 17=
:26:40","No power issue site on grid with Ubay:54.4V Symphorien /691316854 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with Ubay:54.4V Symphorien /691316854 from Huawei is informed","chris=
telle.ngonga@matech-cameroun.com","432","01-05-2025 17:07:00","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004928329","Bar=
riere","","01-05-2025 16:57:51","01-05-2025 16:47:41","01-05-2025 20:46:28"=
,"Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS Fel=
ix ZAMBE confirmed // Grid return","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen=
 overload (20kva, 400A) SS IHS Felix ZAMBE confirmed // Grid returned","fra=
nck.nkomot@matech-cameroun.com","1109","01-05-2025 16:57:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004928320","Eto koss=
 Yde","","01-05-2025 16:56:44","01-05-2025 16:50:20","01-05-2025 16:56:20",=
"Cascaded Incident from TTO5047133","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","system","1212900=
","01-05-2025 16:56:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004928321","ELOUMDEM=
 CARRIERE 2","","01-05-2025 16:56:44","01-05-2025 16:50:20","01-05-2025 16:=
56:20","Cascaded Incident from TTO5047133","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","system","=
1212899","01-05-2025 16:56:44","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004928287","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","01-05-2025 16:53:31","01-05-2025 16:50=
:20","01-05-2025 16:56:20","Grid outage, Site went down before Gen start du=
e to poor backup // Gen started automatically","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","franck.nkomot@matech-cameroun.com","193","01-05-2025 16:53:31","MATE=
CH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004928169","NYO=
M FACE MAETUR","","01-05-2025 16:28:56","01-05-2025 16:27:48","01-05-2025 1=
7:44:48","Grid fluctuation,Site went down because Gen failed to start due t=
o Grid bad voltage // Site put on Gen","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,Si=
te went down because Gen failed to start due to Grid bad voltage // Site pu=
t on Gen","franck.nkomot@matech-cameroun.com","69","01-05-2025 16:28:56","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004928122","E=
koumdoum OCM","","01-05-2025 16:15:51","01-05-2025 16:11:46","02-05-2025 12=
:02:01","Grid outage site went down due to Gen overload(20kva,280 A) IHS SS=
 Pascaline is informed//Grid return .Power issue resolved at ocm but site r=
emains down and power reset has done Lionnel STEEVE (655184","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"," Grid outage s=
ite went down due to Gen overload(20kva,280 A) IHS SS Pascaline is informed=
//Grid return .Power issue resolved at ocm but site remains down and power =
reset has done Lionnel STEEVE (655184876) From Huawei is informed site up a=
t 12:02 PM","christelle.ngonga@matech-cameroun.com","246","01-05-2025 16:15=
:51","MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004928034","M=
vog-Ada_OCM","","01-05-2025 15:57:23","01-05-2025 15:51:17","01-05-2025 16:=
00:57","Grid Only, No space to deploy // Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to de=
ploy // Grid return","christelle.ngonga@matech-cameroun.com","367","01-05-2=
025 15:57:23","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004928030","N=
kolo II New","","01-05-2025 15:56:26","01-05-2025 15:48:18","01-05-2025 16:=
59:41","Site impacted by CTR_654 Mimboman Don Bosco wich is not manage by I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","Site impacted by CTR_654 Mimboma=
n Don Bosco wich is not manage by IHS","christelle.ngonga@matech-cameroun.c=
om","489","01-05-2025 15:56:26","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004928027","S=
atcom","","01-05-2025 15:55:24","01-05-2025 15:47:17","01-05-2025 23:52:48"=
,"Active // No power issue site on Grid with Ubay:50.8V Tx Fme Armand Ngest=
sa (691144412) of huawei is inform","Delor Telezing","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","Affected by 3rd Party Site","Ac=
tive // No power issue site on Grid with Ubay:50.8V Tx Fme Armand Ngestsa (=
691144412) of huawei is inform","christelle.ngonga@matech-cameroun.com","48=
8","01-05-2025 15:55:24","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004927860","E=
kombitie","","01-05-2025 15:30:27","01-05-2025 15:22:18","01-05-2025 17:30:=
03","Active: no power issue, site is on Gen with Ubaie=3D55V, Symphorien(65=
0257151) from huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no =
power issue, site is on Gen with Ubaie=3D55V, Symphorien(650257151) from hu=
awei is informed","franck.nkomot@matech-cameroun.com","490","01-05-2025 15:=
30:27","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004927737","N=
omayos montee Meche","","01-05-2025 15:17:30","01-05-2025 15:14:19","01-05-=
2025 17:36:11","Active: No power issue, site is on grid with Ubaie=3D53.1V,=
 Flubert (654266068) from Huawei is informed","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue, site is on grid with Ubaie=3D53.1V, Flubert (654266068=
) from Huawei is informed","franck.nkomot@matech-cameroun.com","192","01-05=
-2025 15:17:30","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004927718","F=
ouda-New","","01-05-2025 15:15:06","01-05-2025 15:05:00","02-05-2025 00:37:=
09","Active: no power issue, site is on battery with Ubaie=3D54V, Armand Ng=
uetsa(691144412) from Huawei is informed","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: no power issue, site is on battery with Ubaie=3D54V, Armand Nguetsa (69=
1144412) from Huawei is informed","franck.nkomot@matech-cameroun.com","607"=
,"01-05-2025 15:15:06","MATECH CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0004927649","K=
ondengui","","01-05-2025 15:09:57","01-05-2025 15:05:48","02-05-2025 00:29:=
12","Active // No power issue site on Gen Ubaie:54.2V Lionnel Steve (655184=
876/Huawei) is informed","Albran Byorel","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power iss=
ue site on Gen Ubaie:54.2V Lionnel Steve (655184876/Huawei) is informed","f=
ranck.nkomot@matech-cameroun.com","250","01-05-2025 15:09:57","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004927535","Mok=
olo Yaounde","","01-05-2025 14:55:43","01-05-2025 14:54:37","01-05-2025 14:=
59:37","No power issue U =3D53V site on grid. The Tx FME Eloundou Bertrand =
(693212405) from Huawei is informed","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D53V=
 site on grid. The Tx FME Eloundou Bertrand (693212405) from Huawei is info=
rmed","franck.nkomot@matech-cameroun.com","67","01-05-2025 14:55:43","MATEC=
H CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0004927516","OKO=
A Peage","","01-05-2025 14:52:29","01-05-2025 14:46:21","01-05-2025 14:56:2=
1","Active// No power issue on site Ubaie: 55.3 Vsite On Gen The Tx FME Ful=
bert(654266068) of huawei is informe","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No=
 power issue on site Ubaie: 55.3 Vsite On Gen The Tx FME Fulbert(654266068)=
 of huawei is informe","franck.nkomot@matech-cameroun.com","369","01-05-202=
5 14:52:29","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0004927142","Nsa=
m Sofavinc","","01-05-2025 13:54:56","01-05-2025 13:48:44","01-05-2025 13:5=
4:55","Grid outage, site went down before Gen started due to poor backup //=
 Grid returned","MINKA NICOLAS","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, site went down before Gen sta=
rted due to poor backup // Grid returned","loic.noumsi@matech-cameroun.com"=
,"372","01-05-2025 13:54:56","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004926433","Bar=
riere","","01-05-2025 12:06:07","01-05-2025 11:58:51","01-05-2025 12:44:46"=
,"Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS Fel=
ix ZAMBE confirmed // Grid returned","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because G=
en overload (20kva, 400A) SS IHS Felix ZAMBE confirmed // Grid returned","l=
oic.noumsi@matech-cameroun.com","437","01-05-2025 12:06:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004926424","Eto koss=
 Yde","","01-05-2025 12:04:35","01-05-2025 11:58:49","01-05-2025 12:05:41",=
"Cascaded Incident from TTO5044974","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","system","1216045=
","01-05-2025 12:04:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004926425","ELOUMDEM=
 CARRIERE 2","","01-05-2025 12:04:35","01-05-2025 11:58:49","01-05-2025 12:=
05:41","Cascaded Incident from TTO5044974","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup // Gen started automatically","system","=
1216046","01-05-2025 12:04:35","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004926418","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","01-05-2025 12:03:36","01-05-2025 11:58=
:49","01-05-2025 12:05:41","Grid outage, Site went down before Gen start du=
e to poor backup // Gen started automatically","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor backup // Gen started automatic=
ally","loic.noumsi@matech-cameroun.com","289","01-05-2025 12:03:36","MATECH=
 CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004926208","Oko=
lo Kilombo","","01-05-2025 11:27:41","01-05-2025 11:25:26","01-05-2025 11:2=
7:52","Grid outage, site went down due to insufficiency of rectifiers, // s=
ite stabilized","Fabrice Pouakam","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Grid outage, site went down due to insufficiency of rec=
tifiers, // site stabilized","gaelle.njiofack@matech-cameroun.com","136","0=
1-05-2025 11:27:41","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004926122","Fla=
menco","","01-05-2025 11:12:44","01-05-2025 11:02:36","01-05-2025 12:17:52"=
,"Grid outage gen failed to start due to card GE dysfunctioned // Grid retu=
rned","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Grid outage gen failed to start due to card GE dysfunctioned // =
Grid returned","loic.noumsi@matech-cameroun.com","609","01-05-2025 11:12:44=
","MATECH CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0004926087","M=
IMBOMAN LIBERTE","","01-05-2025 11:07:59","01-05-2025 10:57:59","01-05-2025=
 11:25:29","No power issue on site Ubaie 53.3V site on Grid , Armand Nguets=
a /699949563 from Huawei is informed.","Mba Lazare Herve","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site Ubaie 53.3V site on Grid , Armand Nguetsa /699949563 from=
 Huawei is informed.","gaelle.njiofack@matech-cameroun.com","601","01-05-20=
25 11:07:59","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004925991","M=
ANGUIERS CHAPELLE","","01-05-2025 10:41:13","01-05-2025 04:27:00","01-05-20=
25 11:58:00","Grid outage, site went down due to gen overload (22kva, 340A)=
 SS HISBernard ATANGANA is informed and confirmed","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went=
 down due to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed =
and confirmed","gaelle.njiofack@matech-cameroun.com","22454","01-05-2025 10=
:41:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_556","NOCINC0004925988","NKOMKANA=
 ELIZA HOTEL","","01-05-2025 10:40:29","01-05-2025 10:30:19","01-05-2025 12=
:12:01","Cascaded Incident from TTO5044433","","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, No space de deploy a MG.//=
 Grid returned","system","272109","01-05-2025 10:40:29","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004925933","B=
ATA Mokolo OCM","IHS_YND_556","01-05-2025 10:34:32","01-05-2025 10:30:19","=
01-05-2025 12:12:01","Grid outage, No space de deploy a MG.// Grid returned=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage, No space de deploy a MG.// Grid returned","gaelle.njiofack@matec=
h-cameroun.com","254","01-05-2025 10:34:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0004925474","Nkoabang=
2","","01-05-2025 09:11:46","01-05-2025 08:34:20","01-05-2025 09:28:53","Ca=
scaded Incident from TTO5043869","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","	Active// No power issue, site is on =
GRID with U=3D54.3 V. The TX FME Lionel Adjep (655184876) from Huawei is wo=
rking on site.","system","271768","01-05-2025 09:11:46","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004925465","Nom=
ayos montee Meche","","01-05-2025 09:07:15","01-05-2025 09:06:40","01-05-20=
25 09:49:58","Active: No power issue, site is on grid with Ubaie=3D50V, Flu=
bert (654266068) from Huawei is informed","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active:=
 No power issue, site is on grid with Ubaie=3D50V, Flubert (654266068) from=
 Huawei is informed","loic.noumsi@matech-cameroun.com","36","01-05-2025 09:=
07:15","MATECH CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0004925438","N=
koabang","IHS_YND_526, IHS_YND_736","01-05-2025 08:59:40","01-05-2025 08:34=
:20","01-05-2025 09:28:53","	Active// No power issue, site is on GRID with =
U=3D54.3 V. The TX FME Lionel Adjep (655184876) from Huawei is informed","M=
ba Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","	Active// No power issue, site is on GRID with=
 U=3D54.3 V. The TX FME Lionel Adjep (655184876) from Huawei is working on =
site.","gaelle.njiofack@matech-cameroun.com","1520","01-05-2025 08:59:40","=
MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004925344","C=
RF Nkoabang","","01-05-2025 08:41:45","01-05-2025 08:34:20","01-05-2025 09:=
28:53","Fme Herve is informed ETA 9:25 AM","Mba Lazare Herve","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","	Active// No power issue, s=
ite is on GRID with U=3D54.3 V. The TX FME Lionel Adjep (655184876) from Hu=
awei is working on site.","loic.noumsi@matech-cameroun.com","271768","01-05=
-2025 08:41:45","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004924879","M=
essassi 2","","01-05-2025 07:10:23","01-05-2025 07:07:14","01-05-2025 18:02=
:59","Site went down due to rectifier issues // Grid stabilised","Fabrice P=
ouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site w=
ent down due to rectifier issues // Grid stabilised","gaelle.njiofack@matec=
h-cameroun.com","191","01-05-2025 07:10:23","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004924245","Man=
guiers Dispensaire","","01-05-2025 04:07:48","01-05-2025 03:59:27","01-05-2=
025 11:22:37","Fme Fabrice has been informed and reported rectifier issue (=
2/4 faulty rectifiers), ss IHS Bernard is informed // He replaced rectifier=
s, site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Fme Fabrice has been informed and reported rectifier is=
sue (2/4 faulty rectifiers), ss IHS Bernard is informed // He replaced rect=
ifiers, site on Gen","vanel.mbiada@matech-cameroun.com","501","01-05-2025 0=
4:07:48","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004924139","OTE=
LE MTN","","01-05-2025 03:09:00","01-05-2025 03:06:40","01-05-2025 03:45:41=
","Grid outage,site went because Gen failed to start due to disjunction of =
Generator CB   //He rearmed and manually started the Gen","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Grid outage,sit=
e went because Gen failed to start due to disjunction of Generator CB   //H=
e rearmed and manually started the Gen","cedric.tiani@matech-cameroun.com",=
"141","01-05-2025 03:09:00","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004923874","M=
ANGUIERS CHAPELLE","","01-05-2025 01:18:05","01-05-2025 01:12:53","01-05-20=
25 03:47:54","	Grid outage, site went down due to gen overload (22kva, 340A=
) SS HISBernard ATANGANA is informed and confirmed//Site stabilised","Fabri=
ce Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","	Gri=
d outage, site went down due to gen overload (22kva, 340A) SS HISBernard AT=
ANGANA is informed and confirmed//Site stabilised","vanel.mbiada@matech-cam=
eroun.com","313","01-05-2025 01:18:05","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004923829","SAA=
 Entrance","","01-05-2025 01:00:26","01-05-2025 00:54:01","01-05-2025 01:20=
:09","Grid outage,site went down because Gen failed to start due to Grid co=
ntactor faulty//He bypassed it and manually start the Gen","Parker Tchoup",=
"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,s=
ite went down because Gen failed to start due to Grid contactor faulty//He =
bypassed it and manually start the Gen","cedric.tiani@matech-cameroun.com",=
"387","01-05-2025 01:00:26","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004923285","O=
LAMA","","30-04-2025 22:25:03","30-04-2025 21:45:49","01-05-2025 00:30:38",=
"Active//No power issue on site Ubaie =3D54.1V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed.Noticed repetitive issues","Fanda Bri=
ce","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue on site Ubaie =3D54.1V site on Grid =
The TX FME Henri (699949693) from Huawei is informed.Noticed repetitive iss=
ues","loic.noumsi@matech-cameroun.com","2355","30-04-2025 22:25:03","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004923204","N=
kolafeme","","30-04-2025 22:08:18","30-04-2025 21:59:59","01-05-2025 00:50:=
15","Active//No power issue, Site on Grid Ubai=3D 55,9V The TX Mouhamadou (=
6144435) from Huawei is informed. ","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue, Site on Grid Ubai=3D 55,9V The TX Mouhamadou (61444=
35) from Huawei is informed. ","edwige.kapawo@matech-cameroun.com","499","3=
0-04-2025 22:08:18","MATECH CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004923002","E=
kie-Elegance","IHS_YND_159","30-04-2025 21:35:52","30-04-2025 21:05:44","30=
-04-2025 23:58:00","Grid outage site went down because Gen started and stoo=
pped due to alarm low oil pressure // He added oil and Gen manually started=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil P=
ressure","Grid outage site went down because Gen started and stoopped due t=
o alarm low oil pressure // He added oil and Gen manually started","edwige.=
kapawo@matech-cameroun.com","1808","30-04-2025 21:35:52","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004922985","C=
omplexe-BEAC","","30-04-2025 21:33:52","30-04-2025 21:05:44","30-04-2025 23=
:58:00","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage site went down because Gen started and stoopped=
 due to alarm low oil pressure // He added oil and Gen manually started","e=
dwige.kapawo@matech-cameroun.com","277009","30-04-2025 21:33:52","MATECH CM=
R"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004922727","O=
LAMA","","30-04-2025 20:57:26","30-04-2025 20:49:18","30-04-2025 21:21:22",=
"Grid outage, Site went down before Gen start due to poor backup // Gen sta=
rted Manually","Fanda Brice","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup // Gen started Manually","loic.noumsi@matech-cameroun.co=
m","489","30-04-2025 20:57:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004922629","Leboudi"=
,"","30-04-2025 20:46:28","30-04-2025 20:41:09","30-04-2025 21:11:05","Casc=
aded Incident from TTO5040591","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
due to grid fluctuations and no automatism on Gen // He bypassed Grid and s=
tarted manually Gen","system","264187","30-04-2025 20:46:28","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004922614","N=
kolafeme","IHS_YND_309","30-04-2025 20:44:17","30-04-2025 20:41:09","30-04-=
2025 21:13:48","Grid outage, site went down due to grid fluctuations and no=
 automatism on Gen // He bypassed Grid and started manually Gen","TIENTCHEU=
 NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, site went down due to grid fluctuations and no automatis=
m on Gen // He bypassed Grid and started manually Gen","edwige.kapawo@matec=
h-cameroun.com","189","30-04-2025 20:44:17","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004922401","Odz=
a Minkan IHS","","30-04-2025 20:20:13","30-04-2025 20:03:19","30-04-2025 21=
:08:53","Grid outage, site went down due to rectifiers faulty // He replace=
d 1/2 rectifiers ","Albran Byorel","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Grid outage, site went down due to rectifiers faulty /=
/ He replaced 1/2 rectifiers ","loic.noumsi@matech-cameroun.com","1015","30=
-04-2025 20:20:13","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004922107","H=
-General-Yde","","30-04-2025 19:33:56","30-04-2025 19:27:48","30-04-2025 19=
:43:19","No power issue site on grid with Ubay:49.3V Symphorien /691316854 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with Ubay:49.3V Symphorien /691316854 from Huawei is informed","edwig=
e.kapawo@matech-cameroun.com","369","30-04-2025 19:33:56","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004922080","M=
essassi 2","","30-04-2025 19:30:12","30-04-2025 19:25:30","30-04-2025 21:13=
:29","Site went down because 02/06 rectifiers dysfuncionned// He reset rect=
ifiers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down because 02/06 rectifiers dysfuncionned// He rese=
t rectifiers","loic.noumsi@matech-cameroun.com","284","30-04-2025 19:30:12"=
,"MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004921831","Odz=
a Minkan IHS","","30-04-2025 18:54:57","30-04-2025 18:50:48","30-04-2025 19=
:18:59","Grid outage, Site went down due to grid bad voltage, // Grid stabi=
lised","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid outage, Site went down due to grid bad voltage, =
// Grid stabilised","loic.noumsi@matech-cameroun.com","250","30-04-2025 18:=
54:57","MATECH CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0004921721","Nsa=
m escale LP","","30-04-2025 18:36:32","30-04-2025 18:30:26","01-05-2025 02:=
40:25","Grid outage, no space to deploy a mobil gen // Grid restoration",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy a mobil gen // Grid restoration","loic.noumsi@mat=
ech-cameroun.com","367","30-04-2025 18:36:32","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004921590","SAA=
 Entrance","","30-04-2025 18:14:43","30-04-2025 18:10:38","30-04-2025 18:23=
:30","Grid outage, Site went down because gen fails to start due to automat=
ism system dysfunctionning // He reset it and manually start the gen","Park=
er Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, Site went down because gen fails to start due to automatism sy=
stem dysfunctionning // He reset it and manually start the gen","loic.noums=
i@matech-cameroun.com","246","30-04-2025 18:14:43","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004921522","N=
goulmekong-Nord","","30-04-2025 18:00:51","30-04-2025 17:57:19","30-04-2025=
 18:57:26","Site went down due to PSC3 Controller dysfunctionning// He rese=
t it","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Site went down due to PSC3 Controller dysfunctionning// He reset=
 it","edwige.kapawo@matech-cameroun.com","213","30-04-2025 18:00:51","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004921424","Elig Edz=
oa","","30-04-2025 17:44:39","30-04-2025 21:16:58","02-05-2025 18:14:57","c=
ascade","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid Only, No MDG to deploy // Grid returned","system","43479=
9","30-04-2025 17:44:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0004921423","Elig-Edz=
oa","","30-04-2025 17:44:39","30-04-2025 17:15:58","30-04-2025 21:15:57","G=
rid Only, No MDG to deploy // Grid returned","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid Only, No MDG to deploy // Gri=
d returned","system","1721","30-04-2025 17:44:39","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004921311","Nta=
ba","IHS_YND_133, IHS_YND_504","30-04-2025 17:20:04","30-04-2025 17:15:58",=
"02-05-2025 18:14:57","site went down due to PWC Overload(12Kw 250A) Blaise=
 Raoul SS IHS is informed // Grid stabilised","Delor Telezing","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","site went down =
due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is informed // Grid retu=
rned","loic.noumsi@matech-cameroun.com","247","30-04-2025 17:20:04","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004921110","A=
ccacia New","","30-04-2025 16:50:06","30-04-2025 16:47:57","30-04-2025 17:0=
0:59","Active//No power issue Ubay =3D54.6V site on Grid.The FME TX Mbah Ho=
siah (674007438/699699694) from Huawei is informed.","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue Ubay =3D54.6V site on Grid.The FME TX Mbah Hosiah (67400743=
8/699699694) from Huawei is informed.","edwige.kapawo@matech-cameroun.com",=
"130","30-04-2025 16:50:06","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004921012","Nko=
lfoulou","","30-04-2025 16:39:27","30-04-2025 16:35:19","30-04-2025 16:40:3=
9","Site went down due to PWC IPT dysfunctionning// site on Grid","Siligap =
Boris","Equipment Repair","Passive","Rectifier","Rectifier Module Overloade=
d","Site went down due to PWC IPT dysfunctionning// site on Grid","loic.nou=
msi@matech-cameroun.com","249","30-04-2025 16:39:27","MATECH CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004921009","M=
amch Building","","30-04-2025 16:38:55","30-04-2025 16:33:46","30-04-2025 1=
8:59:46","No power issue site on gen with Ubay=3D54V Notice that site is im=
pacted by Charles Atangana","Mboua Thierry","Customer Equipment Failure","A=
ctive","Active Equipment Failure","Affected by 3rd Party Site","No power is=
sue site on gen with Ubay=3D54V Notice that site is impacted by Charles Ata=
ngana","edwige.kapawo@matech-cameroun.com","310","30-04-2025 16:38:55","MAT=
ECH CMR"
"Closed Complete","Site Down","T0401","IHS_YND_205","NOCINC0004920907","Ton=
golo MTN","","30-04-2025 16:19:50","30-04-2025 13:33:39","30-04-2025 17:09:=
48","Grid otage site went down because Gen failed to start due to  Gen card=
 faulty // he started Gen manually ","Fabrice Pouakam","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid otage site went down becau=
se Gen failed to start due to  Gen card faulty // he started Gen manually "=
,"edwige.kapawo@matech-cameroun.com","9972","30-04-2025 16:19:50","MATECH C=
MR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004920838","MBA=
LNGONG LYCEE","","30-04-2025 16:06:56","30-04-2025 15:55:36","30-04-2025 18=
:50:15","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid returned","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid returned","ludivine.ngama=
leu@ihstowers.com","681","30-04-2025 16:06:56","MATECH CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004920834","Lab=
oratoire  Meka","","30-04-2025 16:05:41","30-04-2025 15:53:21","30-04-2025 =
17:33:53","Grid Only, No space to deploy MG // Grid returned","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No spa=
ce to deploy MG // Grid returned","ludivine.ngamaleu@ihstowers.com","741","=
30-04-2025 16:05:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0004920640","Crf-Nkol=
bisson","","30-04-2025 15:45:20","30-04-2025 15:37:33","30-04-2025 15:47:59=
","Cascaded Incident from TTO5038256","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue on site U=
bay=3D53.8 V site on gen. Tx FME Mohammadou (691144435/ HUAWEi) is informed=
","system","260813","30-04-2025 15:45:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0004920639","Oyomaban=
g Ecole","","30-04-2025 15:45:19","30-04-2025 15:37:33","30-04-2025 15:47:5=
9","Cascaded Incident from TTO5038256","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Active","Cascade Active","Cascade Active","No power issue on site =
Ubay=3D53.8 V site on gen. Tx FME Mohammadou (691144435/ HUAWEi) is informe=
d","system","260813","30-04-2025 15:45:19","MATECH CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0004920628","O=
yomabang OCM","IHS_YND_686, IHS_YND_232","30-04-2025 15:43:40","30-04-2025 =
15:37:33","30-04-2025 15:47:59","No power issue on site Ubay=3D53.8 V site =
on gen. Tx FME Mohammadou (691144435/ HUAWEi) is informed","TIENTCHEU NZETC=
HIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","No power issue on site Ubay=3D53.8 V site on gen. Tx=
 FME Mohammadou (691144435/ HUAWEi) is informed","edwige.kapawo@matech-came=
roun.com","368","30-04-2025 15:43:40","MATECH CMR"
"Closed Complete","Site Down","T3149","IHS_YND_044","NOCINC0004920520","Pol=
ytechnique","","30-04-2025 15:27:19","30-04-2025 15:21:41","30-04-2025 17:0=
5:35","","","Cascade Outage","Active","Cascade Active","Cascade Active","Ac=
tive// No power Issue Site on Grid Ubay =3D53,7 V, The TX FME Mbah Hosiah (=
674007438) is on site for work","edwige.kapawo@matech-cameroun.com","276519=
","30-04-2025 15:27:19","MATECH CMR"
"Closed Complete","Site Down","T0036","IHS_YND_076","NOCINC0004920515","Le =
Flamboyant","","30-04-2025 15:26:45","30-04-2025 15:21:41","30-04-2025 17:0=
5:35","","Paul BIBOUM","Cascade Outage","Active","Cascade Active","Cascade =
Active","Active// No power Issue Site on Grid Ubay =3D53,7 V, The TX FME Mb=
ah Hosiah (674007438) is on site for work","edwige.kapawo@matech-cameroun.c=
om","276518","30-04-2025 15:26:45","MATECH CMR"
"Closed Complete","Site Down","T0817","IHS_YND_061","NOCINC0004920514","Yde=
 University","IHS_YND_076, IHS_YND_043, IHS_YND_078, IHS_YND_044","30-04-20=
25 15:25:51","30-04-2025 15:21:41","30-04-2025 19:02:42","Active// No power=
 Issue Site on Grid Ubay =3D53,7 V, The TX FME Mbah Hosiah (674007438) is o=
n site for work","Paul BIBOUM","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site on =
Grid Ubay =3D53,7 V, The TX FME Mbah Hosiah (674007438) is on site for work=
","edwige.kapawo@matech-cameroun.com","250","30-04-2025 15:25:51","MATECH C=
MR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004920511","An-=
Marche-Melen","","30-04-2025 15:25:10","30-04-2025 15:21:41","30-04-2025 17=
:05:35","","","Cascade Outage","Active","Cascade Active","Cascade Active","=
Active// No power Issue Site on Grid Ubay =3D53,7 V, The TX FME Mbah Hosiah=
 (674007438) is on site for work","edwige.kapawo@matech-cameroun.com","2765=
18","30-04-2025 15:25:10","MATECH CMR"
"Closed Complete","Site Down","T3172","IHS_YND_043","NOCINC0004920505","Emi=
a","","30-04-2025 15:23:56","30-04-2025 15:21:41","30-04-2025 17:05:35","",=
"","Cascade Outage","Active","Cascade Active","Cascade Active","Active// No=
 power Issue Site on Grid Ubay =3D53,7 V, The TX FME Mbah Hosiah (674007438=
) is on site for work","edwige.kapawo@matech-cameroun.com","276518","30-04-=
2025 15:23:56","MATECH CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0004920463","B=
ATA-Mokolo","","30-04-2025 15:17:37","30-04-2025 15:09:29","30-04-2025 16:2=
2:06","Grid Only, No space to deploy //  Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to de=
ploy //  Grid return","edwige.kapawo@matech-cameroun.com","489","30-04-2025=
 15:17:37","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004920450","E=
kombitie","","30-04-2025 15:15:37","30-04-2025 15:09:27","30-04-2025 15:10:=
34","Active: no power issue, site is on Gen with Ubaie=3D55V, Symphorien(65=
0257151) from huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no =
power issue, site is on Gen with Ubaie=3D55V, Symphorien(650257151) from hu=
awei is informed","edwige.kapawo@matech-cameroun.com","372","30-04-2025 15:=
15:37","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004920411","Nko=
lbong","","30-04-2025 15:09:24","30-04-2025 15:06:14","30-04-2025 16:12:03"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload // He reduiced load and Gen manually started","Delor Telezing","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen started and stopped due to Gen overload // He reduiced l=
oad and Gen manually started","edwige.kapawo@matech-cameroun.com","191","30=
-04-2025 15:09:24","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0004920390","H=
-Progres","","30-04-2025 15:05:36","30-04-2025 14:37:12","30-04-2025 16:19:=
45","Grid outage.no space to deploy MGE //grid power arestored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deploy MGE //grid power arestored","olivier.kwedi@ihstowers.com","=
1705","30-04-2025 15:05:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004920385","Bastos B=
ethesda","","30-04-2025 15:04:24","30-04-2025 14:53:49","30-04-2025 14:55:2=
6","Cascaded Incident from TTO5037933","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active// No power issue on site Ub=
aie:53.1V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is inform=
ed ","system","263326","30-04-2025 15:04:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004920382","Tsinga",=
"","30-04-2025 15:03:46","30-04-2025 14:53:49","30-04-2025 14:55:26","Casca=
ded Incident from TTO5037933","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active// No power issue on site Ubaie:53.1V=
 site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informed ","sys=
tem","263325","30-04-2025 15:03:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004920380","Golf Qua=
ter","","30-04-2025 15:03:46","30-04-2025 14:53:49","30-04-2025 14:55:26","=
Cascaded Incident from TTO5037933","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active// No power issue on site Ubaie:=
53.1V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informed "=
,"system","263325","30-04-2025 15:03:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004920381","Nkomkana=
 2","","30-04-2025 15:03:46","30-04-2025 14:53:49","30-04-2025 16:17:39","G=
rid outage, Site went down due to Gen overload  SS IHS Bernard Atangana is =
informed// Grid return","Mboua Thierry","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","Grid outage, Site went down due to Gen overload  SS=
 IHS Bernard Atangana is informed// Grid return","system","597","30-04-2025=
 15:03:46","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004920364","B=
astos-Nylon","IHS_YND_220, IHS_YND_563, IHS_YND_127","30-04-2025 15:01:01",=
"30-04-2025 14:53:49","30-04-2025 14:55:26","Active// No power issue on sit=
e Ubaie:53.1V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is in=
formed ","Mboua Thierry","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active// No power issue on site Ubaie:=
53.1V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informed "=
,"edwige.kapawo@matech-cameroun.com","433","30-04-2025 15:01:01","MATECH CM=
R"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0004920358","Nko=
mkana","","30-04-2025 15:00:02","30-04-2025 14:55:54","30-04-2025 16:21:35"=
,"Grid Only, No space to deploy // Grid return","","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid Only, No space to deploy /=
/ Grid return","edwige.kapawo@matech-cameroun.com","249","30-04-2025 15:00:=
02","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004919934","O=
LAMA","","30-04-2025 13:40:36","30-04-2025 13:35:17","30-04-2025 13:46:09",=
"No power issue on site U:54.9 V( hybrid site). The Tx FME Henri (699949693=
)from Huawei is informed.","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 U:54.9 V( hybrid site). The Tx FME Henri (699949693)from Huawei is informe=
d.","christelle.ngonga@matech-cameroun.com","320","30-04-2025 13:40:36","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004919920","E=
kombitie","","30-04-2025 13:38:47","30-04-2025 13:35:41","30-04-2025 13:48:=
25","Active: no power issue, site is on Gen with Ubaie=3D54.5V, Symphorien(=
650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue, site is on Gen with Ubaie=3D54.5V, Symphorien(650257151/ huawei)=
 is informed","christelle.ngonga@matech-cameroun.com","188","30-04-2025 13:=
38:47","MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004919910","c=
hina embassy yde","","30-04-2025 13:36:48","30-04-2025 13:33:41","30-04-202=
5 18:00:45"," Grid outage, No space to deploy MG // Grid returned","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue"," Grid outage=
, No space to deploy MG // Grid returned","christelle.ngonga@matech-camerou=
n.com","187","30-04-2025 13:36:48","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0004919845","NKO=
NGKARAK","","30-04-2025 13:23:41","30-04-2025 12:52:25","30-04-2025 14:04:0=
5","Site went down because Gen started and stopped due to pierced pellet //=
 he added Water and Manually Started The Gen","TIENTCHEU NZETCHIEU GAEL","E=
quipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Le=
vel Issue","Site went down because Gen started and stopped due to pierced p=
ellet // he added Water and Manually Started The Gen","franck.nkomot@matech=
-cameroun.com","1877","30-04-2025 13:23:41","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004919725","Ebo=
go","","30-04-2025 13:01:45","30-04-2025 12:52:25","30-04-2025 15:13:42","N=
o power issue site on grid with U=3D53.8v Symphorien from Huawei is informe=
d","Siligap Boris","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.8v S=
ymphorien from Huawei is informed","franck.nkomot@matech-cameroun.com","561=
","30-04-2025 13:01:45","MATECH CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0004919722","B=
astos Ekoudou","","30-04-2025 13:00:15","30-04-2025 12:57:46","30-04-2025 1=
3:19:46","Grid outage gen failed to start due to battery GE faulty//Gen man=
ually started with external battery","Mboua Thierry","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Generator Battery","Grid outage gen failed to sta=
rt due to battery GE faulty//Gen manually started with external battery","c=
hristelle.ngonga@matech-cameroun.com","150","30-04-2025 13:00:15","MATECH C=
MR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004919679","S=
OA UNIVERSITY STADIUM","","30-04-2025 12:50:32","30-04-2025 12:43:25","30-0=
4-2025 14:18:37","Grid outage, Site went down because Gen failed to start d=
ue to Gen card disfunction// He reset Gen card and started Gen manually","S=
iligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Coolant Pipe"=
,"Grid outage, Site went down because Gen failed to start due to Gen card d=
isfunction// He reset Gen card and started Gen manually","christelle.ngonga=
@matech-cameroun.com","428","30-04-2025 12:50:32","MATECH CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004919633","MBI=
MBIM","","30-04-2025 12:40:32","30-04-2025 12:31:24","30-04-2025 12:32:59",=
"Wronly ticket","Parker Tchoup","Incorrectly Logged Tickets","Error","Error=
","Error","Wronly ticket","franck.nkomot@matech-cameroun.com","549","30-04-=
2025 12:40:32","MATECH CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004919478","M=
vog-Manga","","30-04-2025 12:14:02","30-04-2025 12:07:52","30-04-2025 12:57=
:11","Grid fluctuation, site went down because Gen failed to start due to G=
rid fluctuations // Grid returned","Albran Byorel","Grid Supply","Passive",=
"Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuation, site=
 went down because Gen failed to start due to Grid fluctuations // Grid ret=
urned","christelle.ngonga@matech-cameroun.com","372","30-04-2025 12:14:02",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004919472","S=
atcom","","30-04-2025 12:12:38","30-04-2025 12:06:23","30-04-2025 12:26:52"=
,"Active // No power issue site on Grid with Ubay:50.8V Tx Fme Armand Ngest=
sa (691144412) of huawei is informed","Delor Telezing","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/ No power issue site on Grid with Ubay:50.8V Tx Fme Armand Ngestsa (691144=
412) of huawei is informed","christelle.ngonga@matech-cameroun.com","376","=
30-04-2025 12:12:38","MATECH CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0004919463","C=
hapelle-Essos","","30-04-2025 12:11:30","30-04-2025 12:04:21","30-04-2025 1=
2:12:22","No power issue on site ,site on Grid with Ubaie=3D54,1 V The Tx F=
ME Armand Nguetsa /699949553// from huawei is informed","Delor Telezing","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site ,site on Grid with Ubaie=3D54,1 V The Tx F=
ME Armand Nguetsa /699949553// from huawei is informed","christelle.ngonga@=
matech-cameroun.com","430","30-04-2025 12:11:30","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004919380","O=
mnisport-Rail","","30-04-2025 11:55:26","30-04-2025 11:50:19","30-04-2025 1=
1:55:05","Site down due to work done by SS IHS Bernard and Blaise: Oreon co=
ntroller configuration//End of work","Delor Telezing","Equipment Replacemen=
t","Passive","Planned Activity","Planned Activity - Passive","Site down due=
 to work done by SS IHS Bernard and Blaise: Oreon controller configuration/=
/End of work","christelle.ngonga@matech-cameroun.com","308","30-04-2025 11:=
55:26","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004919185","Fla=
menco","","30-04-2025 11:24:26","30-04-2025 11:18:10","30-04-2025 11:28:10"=
,"Active//No power issue on site Ubaie =3D54,5V site on Grid TX Fme Tsague =
Brice (650214096) from Huawei is informed","Mboua Thierry","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site Ubaie =3D54,5V site on Grid TX Fme Tsague Brice =
(650214096) from Huawei is informed","franck.nkomot@matech-cameroun.com","3=
77","30-04-2025 11:24:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004919113","Bondjock=
","","30-04-2025 11:19:49","30-04-2025 09:18:20","30-04-2025 10:30:20","Cas=
caded Incident from TTO5036067","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, Site went down before Gen s=
tart due to poor battery backup // Grid return","system","269005","30-04-20=
25 11:19:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004919112","Minka","=
","30-04-2025 11:19:48","30-04-2025 09:18:20","30-04-2025 10:30:20","Cascad=
ed Incident from TTO5036067","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Site went down before Gen star=
t due to poor battery backup // Grid return","system","269005","30-04-2025 =
11:19:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004919111","Mbeng","=
","30-04-2025 11:19:48","30-04-2025 09:18:20","30-04-2025 10:30:20","Cascad=
ed Incident from TTO5036067","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Site went down before Gen star=
t due to poor battery backup // Grid return","system","269004","30-04-2025 =
11:19:48","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004919052","M=
ANGUIERS CHAPELLE","","30-04-2025 11:11:33","30-04-2025 11:11:29","30-04-20=
25 14:14:33","Grid outage, site went down due to gen overload (22kva, 340A)=
 SS HISBernard ATANGANA is informed and confirmed//Site stabilised","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage, site went down due to gen overload (22kva, 340A) SS HISBernard ATAN=
GANA is informed and confirmed//Site stabilised","christelle.ngonga@matech-=
cameroun.com","5","30-04-2025 11:11:33","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004918920","NKO=
MKANA ELIZA HOTEL","","30-04-2025 10:54:53","30-04-2025 10:48:44","30-04-20=
25 16:22:04","Grid outage,no space to deploy a mobile Gen //  Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage,no space to deploy a mobile Gen //Grid return","franck.nkomot@matec=
h-cameroun.com","370","30-04-2025 10:54:53","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004918894","B=
ATA Mokolo OCM","","30-04-2025 10:52:53","30-04-2025 10:45:45","30-04-2025 =
16:20:59","Grid outage,no space to deploy MGE // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no sp=
ace to deploy MGE // Grid return","christelle.ngonga@matech-cameroun.com","=
429","30-04-2025 10:52:53","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004918887","C=
RF Nkoabang","","30-04-2025 10:51:25","30-04-2025 10:40:16","30-04-2025 10:=
56:16","Solar Grid Only site down due to grid outage No space for mobile ge=
n // Grid return","Mba Lazare Herve","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Solar Grid Only site down due to grid outage =
No space for mobile gen // Grid return","christelle.ngonga@matech-cameroun.=
com","670","30-04-2025 10:51:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0004918567","Oyomaban=
g Ecole","","30-04-2025 09:55:48","30-04-2025 09:51:17","30-04-2025 10:02:3=
4","Cascaded Incident from TTO5035778","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Active","Cascade Active","Cascade Active","No power issue on site =
Ubai=3D53.8 V site on gen. Tx FME Mohammadou/691144435/ From HUAWEI","syste=
m","267023","30-04-2025 09:55:48","MATECH CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0004918537","O=
yomabang OCM","IHS_YND_686","30-04-2025 09:53:24","30-04-2025 09:51:17","30=
-04-2025 10:02:34","No power issue on site Ubai=3D53.8 V site on gen. Tx FM=
E Mohammadou/691144435/ From HUAWEI","TIENTCHEU NZETCHIEU GAEL","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site Ubai=3D53.8 V site on gen. Tx FME Mohammadou/691144=
435/ From HUAWEI","christelle.ngonga@matech-cameroun.com","128","30-04-2025=
 09:53:24","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004918298","Mom=
","IHS_YND_369, IHS_YND_371, IHS_YND_372","30-04-2025 09:26:01","30-04-2025=
 09:18:20","30-04-2025 10:30:20","Grid outage, Site went down before Gen st=
art due to poor battery backup // Grid return","Fanda Brice","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
Site went down before Gen start due to poor battery backup // Grid return",=
"franck.nkomot@matech-cameroun.com","462","30-04-2025 09:26:01","MATECH CMR=
"
"Closed Complete","Site Down","T0579","IHS_YND_366","NOCINC0004918236","Man=
doumba MTN","","30-04-2025 09:17:32","30-04-2025 09:12:25","30-04-2025 10:4=
9:25","Grid outage gen failed to start due to battery GE faulty//Gen manual=
ly started with external battery","Kemeni Franklin","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Generator Battery","Grid outage gen failed to star=
t due to battery GE faulty//Gen manually started with external battery","fr=
anck.nkomot@matech-cameroun.com","307","30-04-2025 09:17:32","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004918211","C=
rf-Nkolbisson","","30-04-2025 09:15:32","30-04-2025 09:01:20","30-04-2025 1=
0:39:33","No power issue on site Ubaie=3D56.4 V site on grid Mohamadou(6911=
44435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site Ubaie=3D56.4 V site on grid Mohamadou(691144435) from Hu=
awei is informed","christelle.ngonga@matech-cameroun.com","853","30-04-2025=
 09:15:32","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004918186","Lad=
a I Yde","","30-04-2025 09:09:50","30-04-2025 09:01:54","30-04-2025 09:55:5=
4","Site went down due to Grid fluctuation // Site put on Gen","Mba Lazare =
Herve","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply=
 Issue","Site went down due to Grid fluctuation // Site put on Gen","franck=
.nkomot@matech-cameroun.com","477","30-04-2025 09:09:50","MATECH CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0004918038","OKO=
A Peage","","30-04-2025 08:39:42","30-04-2025 08:35:30","30-04-2025 10:48:0=
9","Active// No power issue on site Ubaie: 55.3 Vsite On Gen The Tx FME Ful=
bert(654266068) of huawei is informe","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No=
 power issue on site Ubaie: 55.3 Vsite On Gen The Tx FME Fulbert(654266068)=
 of huawei is informe","franck.nkomot@matech-cameroun.com","253","30-04-202=
5 08:39:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004918010","MEHANDAN=
","","30-04-2025 08:30:16","30-04-2025 08:27:42","30-04-2025 10:05:21","Cas=
caded Incident from TTO5035160","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage gen failed to start due to=
 card GE dysfunctionning//We rest card GE and gen manually started ","syste=
m","279289","30-04-2025 08:30:16","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004917992","O=
dza II OCM","IHS_YND_528","30-04-2025 08:28:48","30-04-2025 08:27:42","30-0=
4-2025 10:05:21","Grid outage gen failed to start due to card GE dysfunctio=
nning//We rest card GE and gen manually started ","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen fail=
ed to start due to card GE dysfunctionning//We rest card GE and gen manuall=
y started ","christelle.ngonga@matech-cameroun.com","68","30-04-2025 08:28:=
48","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004917984","M=
essassi 2","","30-04-2025 08:27:44","30-04-2025 08:26:38","30-04-2025 08:28=
:40","Site went down down due to insufficciency of rectifiers//Rectifier re=
set","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down down due to insufficciency of rectifiers//Rectifier=
 reset","christelle.ngonga@matech-cameroun.com","68","30-04-2025 08:27:44",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0004917918","Dagobert=
","","30-04-2025 08:11:48","30-04-2025 07:52:44","30-04-2025 08:16:19","Cas=
caded Incident from TTO5035012","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Site impacted  CTR_576 Nkobiss=
on Nodal wich is manage by IHS","system","1216447","30-04-2025 08:11:48","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004917919","Entree C=
ite Verte","","30-04-2025 08:11:48","30-04-2025 07:52:44","30-04-2025 08:16=
:19","Cascaded Incident from TTO5035012","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Site impacted  CTR_576 Nkobisson N=
odal wich is manage by IHS","system","1216451","30-04-2025 08:11:48","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0004917916","Yona Hot=
el","","30-04-2025 08:11:47","30-04-2025 07:52:44","30-04-2025 08:16:19","C=
ascaded Incident from TTO5035012","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Site impacted  CTR_576 Nkobi=
sson Nodal wich is manage by IHS","system","1216446","30-04-2025 08:11:47",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004917917","Tsinga",=
"","30-04-2025 08:11:47","30-04-2025 07:52:44","30-04-2025 08:16:19","Casca=
ded Incident from TTO5035012","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Site impacted  CTR_576 Nkobisson Nodal wich=
 is manage by IHS","system","1216451","30-04-2025 08:11:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004917915","Bastos B=
ethesda","","30-04-2025 08:11:47","30-04-2025 07:52:44","30-04-2025 08:16:1=
9","Cascaded Incident from TTO5035012","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Site impacted  CTR_576 Nkobisson N=
odal wich is manage by IHS","system","1216453","30-04-2025 08:11:47","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0004917914","Meyong-M=
eyeme","","30-04-2025 08:11:47","30-04-2025 07:52:44","30-04-2025 08:16:19"=
,"Cascaded Incident from TTO5035012","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","Site impacted  CTR_576 Nk=
obisson Nodal wich is manage by IHS","system","1216449","30-04-2025 08:11:4=
7","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0004917913","BATA Mok=
olo OCM","","30-04-2025 08:11:46","30-04-2025 07:52:44","30-04-2025 08:16:1=
9","Cascaded Incident from TTO5035012","","Cascade Outage","Active","Cascad=
e Active","Cascade Active","Site impacted  CTR_576 Nkobisson Nodal wich is =
manage by IHS","system","1216445","30-04-2025 08:11:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0004917911","Cite-Ver=
te","","30-04-2025 08:11:46","30-04-2025 07:52:44","30-04-2025 08:16:19","C=
ascaded Incident from TTO5035012","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Site impacted  CTR_576 Nkobisson Nodal wich is manag=
e by IHS","system","1216452","30-04-2025 08:11:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0004917912","Bastos-N=
ylon","","30-04-2025 08:11:46","30-04-2025 07:52:44","30-04-2025 08:16:19",=
"Cascaded Incident from TTO5035012","Mboua Thierry","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Site impacted  CTR_576 Nkobisson Noda=
l wich is manage by IHS","system","1216450","30-04-2025 08:11:46","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004917908","Golf Qua=
ter","","30-04-2025 08:11:45","30-04-2025 07:52:44","30-04-2025 08:16:19","=
Cascaded Incident from TTO5035012","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","Site impacted  CTR_576 Nkobisson Nodal=
 wich is manage by IHS","system","1216454","30-04-2025 08:11:45","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004917910","Nkomkana=
 2","","30-04-2025 08:11:45","30-04-2025 07:52:44","30-04-2025 08:16:19","C=
ascaded Incident from TTO5035012","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Site impacted  CTR_576 Nkobisson Nodal =
wich is manage by IHS","system","1216448","30-04-2025 08:11:45","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0004917907","Nkolbi-B=
oss","","30-04-2025 08:11:45","30-04-2025 07:52:44","30-04-2025 08:16:19","=
Cascaded Incident from TTO5035012","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","Site impacted  CTR_576 Nkob=
isson Nodal wich is manage by IHS","system","1216453","30-04-2025 08:11:45"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004917909","AFEME NO=
RD","","30-04-2025 08:11:45","30-04-2025 07:52:44","30-04-2025 08:16:19","C=
ascaded Incident from TTO5035012","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Site impacted  CTR_576 Nkobi=
sson Nodal wich is manage by IHS","system","1216447","30-04-2025 08:11:45",=
"MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004917898","Meh=
anda 1","","30-04-2025 08:09:53","30-04-2025 07:19:40","30-04-2025 10:26:46=
","Grid outage gen failed to start due to ATS dysfunctionning //Grid return=
","Albran Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Iss=
ue","Grid outage gen failed to start due to ATS dysfunctionning //Grid retu=
rn","franck.nkomot@matech-cameroun.com","3014","30-04-2025 08:09:53","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0004917860","N=
komkana","IHS_YND_273, IHS_YND_220, IHS_YND_519, IHS_YND_138, IHS_YND_202, =
IHS_YND_126, IHS_YND_559, IHS_YND_230, IHS_YND_563, IHS_YND_271, IHS_YND_12=
7, IHS_YND_286, IHS_YND_543","30-04-2025 07:59:50","30-04-2025 07:52:44","3=
0-04-2025 08:16:19","Site impacted  CTR_576 Nkobisson Nodal wich is manage =
by IHS","","Customer Equipment Failure","Active","Active Equipment Failure"=
,"Affected by 3rd Party Site","Site impacted  CTR_576 Nkobisson Nodal wich =
is manage by IHS","christelle.ngonga@matech-cameroun.com","428","30-04-2025=
 07:59:50","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004917798","A=
kak-Nkozoa-MTN-IHS","","30-04-2025 07:42:19","30-04-2025 07:43:12","30-04-2=
025 10:11:38","Grid bad voltage , gen frequency very low 48 HZ // increase =
gen frequency to 50.5 HZ","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","ACDG - Under Frequency","Grid bad voltage , gen frequency very lo=
w 48 HZ // increase gen frequency to 50.5 HZ","christelle.ngonga@matech-cam=
eroun.com","5421","30-04-2025 07:42:19","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004917712","M=
EHANDAN","","30-04-2025 07:16:48","30-04-2025 07:09:39","30-04-2025 07:51:3=
9","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage ,site went down because Gen failed to start due to A=
TS and Gen card faulty // grid returned","franck.nkomot@matech-cameroun.com=
","269554","30-04-2025 07:16:48","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004917632","O=
dza II OCM","IHS_YND_528","30-04-2025 07:12:31","30-04-2025 07:09:39","30-0=
4-2025 07:51:39","Grid outage ,site went down because Gen failed to start d=
ue to ATS and Gen card faulty // grid returned","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went=
 down because Gen failed to start due to ATS and Gen card faulty // grid re=
turned","franck.nkomot@matech-cameroun.com","173","30-04-2025 07:12:31","MA=
TECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004916425","Car=
refour Simbock","","30-04-2025 01:24:08","30-04-2025 01:13:59","30-04-2025 =
01:59:34","Site went down because gen start and stopped due to grid bad vol=
tage // Gen started manually","Hyemafo Gildas","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Site went down because gen st=
art and stopped due to grid bad voltage // Gen started manually","cedric.ti=
ani@matech-cameroun.com","610","30-04-2025 01:24:08","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004916410","Men=
dong vallee","","30-04-2025 01:20:24","30-04-2025 01:12:02","30-04-2025 11:=
48:40","Grid outage site went down because Gen over load (20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed // Grid return","Fanda Brice","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down becaus=
e Gen over load (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed // Grid retur=
n","cedric.tiani@matech-cameroun.com","503","30-04-2025 01:20:24","MATECH C=
MR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004916187","C=
RF Nkoabang","","30-04-2025 00:31:06","30-04-2025 00:28:35","30-04-2025 09:=
34:39","Solar Grid Only site down due to grid outage // Grid restoration","=
Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Grid Outa=
ge Issue","Solar Grid Only site down due to grid outage // Grid restoration=
","vanel.mbiada@matech-cameroun.com","152","30-04-2025 00:31:06","MATECH CM=
R"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0004916133","N=
simalen OCM","","30-04-2025 00:06:38","29-04-2025 23:57:59","30-04-2025 01:=
08:20","Grid outage, Site cnnected on the DG MTN , Gen failed to start beca=
use  generator fan belt got cut // he replaced and manually start the Gen",=
"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Fan Belt","=
Grid outage, Site went down because Gen failed to start because  generator =
fan belt got cut // he replaced and manually start the Gen","cedric.tiani@m=
atech-cameroun.com","520","30-04-2025 00:06:38","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004916132","Nsi=
malen MTN","","30-04-2025 00:05:53","29-04-2025 23:56:59","30-04-2025 01:15=
:24","Grid outage, Site went down because Gen failed to start because  gene=
rator fan belt got cut // he replaced and manually start the Gen","Albran B=
yorel","Equipment Repair","Passive","ACDG Gen","ACDG - Fan Belt","Grid outa=
ge, Site went down because Gen failed to start because  generator fan belt =
got cut // he replaced and manually start the Gen","cedric.tiani@matech-cam=
eroun.com","535","30-04-2025 00:05:53","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004916123","Sim=
e Building","","30-04-2025 00:03:53","29-04-2025 23:58:41","30-04-2025 00:0=
8:18","	Grid outage, Site went down before Gen start due to poor backup // =
Gen automatically started","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","	Grid outage, Site went down be=
fore Gen start due to poor backup // Gen automatically started","cedric.tia=
ni@matech-cameroun.com","313","30-04-2025 00:03:53","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004916121","Odz=
a petit marche new","","30-04-2025 00:03:06","29-04-2025 23:59:45","30-04-2=
025 01:27:09","Site went down due to insufficient rectifiers on site//He re=
set it and site on Grid","Albran Byorel","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Site went down due to insufficient rectifiers on=
 site//He reset it and site on Grid","cedric.tiani@matech-cameroun.com","20=
2","30-04-2025 00:03:06","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004915933","Nko=
l-Mbanda","","29-04-2025 23:00:59","29-04-2025 22:17:45","30-04-2025 00:21:=
58","Grid outage, site went down because Gen started and stopped with"" ala=
rm overvoltage"" //He reset the Gen card site on gen","MINKA NICOLAS","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, sit=
e went down because Gen started and stopped with"" alarm overvoltage"" //He=
 reset the Gen card site on gen","edwige.kapawo@matech-cameroun.com","2595"=
,"29-04-2025 23:00:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004915741","Elig Edz=
oa","","29-04-2025 22:12:32","29-04-2025 21:58:11","29-04-2025 22:12:15","C=
ascaded Incident from TTO5032625","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down due to PWC Overload(=
12Kw 250A) Blaise Raoul SS IHS is informed // Grid return","system","266757=
","29-04-2025 22:12:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0004915740","Elig-Edz=
oa","","29-04-2025 22:12:32","29-04-2025 21:58:11","29-04-2025 22:12:15","C=
ascaded Incident from TTO5032625","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","site went down due to PWC Overload(12Kw 250A) Bla=
ise Raoul SS IHS is informed // Grid return","system","266757","29-04-2025 =
22:12:32","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004915708","Nta=
ba","IHS_YND_133, IHS_YND_504","29-04-2025 22:05:25","29-04-2025 21:58:11",=
"29-04-2025 22:12:28","site went down due to PWC Overload(12Kw 250A) Blaise=
 Raoul SS IHS is informed // Grid return","Delor Telezing","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","site went down due =
to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is informed // Grid return",=
"edwige.kapawo@matech-cameroun.com","435","29-04-2025 22:05:25","MATECH CMR=
"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0004915641","EKI=
E","","29-04-2025 21:51:25","29-04-2025 21:48:19","29-04-2025 22:32:01","Si=
te went down because gen start and stopped due to grid bad voltage // Gen s=
tarted manually","Albran Byorel","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Site went down because gen start and stoppe=
d due to grid bad voltage // Gen started manually","edwige.kapawo@matech-ca=
meroun.com","186","29-04-2025 21:51:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004915150","SOA VILL=
AGE","","29-04-2025 20:46:16","29-04-2025 20:41:57","29-04-2025 21:18:51","=
Cascaded Incident from TTO5031893","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC dysfonction // He reset the PWC and Gen manuall=
y started","system","263895","29-04-2025 20:46:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004915149","Melen Ba=
'aba","","29-04-2025 20:46:16","29-04-2025 20:41:57","29-04-2025 21:18:51",=
"Cascaded Incident from TTO5031893","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen failed to start due PWC dysfonction // He reset the PWC and Gen manual=
ly started","system","263895","29-04-2025 20:46:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004915151","Ebogo","=
","29-04-2025 20:46:16","29-04-2025 20:41:57","29-04-2025 21:18:51","Cascad=
ed Incident from TTO5031893","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down because Gen fa=
iled to start due PWC dysfonction // He reset the PWC and Gen manually star=
ted","system","263896","29-04-2025 20:46:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_318","NOCINC0004915145","SOA Univ=
ersity","","29-04-2025 20:46:15","29-04-2025 20:41:57","29-04-2025 21:18:51=
","Cascaded Incident from TTO5031893","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage site went down becau=
se Gen failed to start due PWC dysfonction // He reset the PWC and Gen manu=
ally started","system","263896","29-04-2025 20:46:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004915147","SOA UNIV=
ERSITY STADIUM","","29-04-2025 20:46:15","29-04-2025 20:41:57","29-04-2025 =
21:18:51","Cascaded Incident from TTO5031893","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage site went do=
wn because Gen failed to start due PWC dysfonction // He reset the PWC and =
Gen manually started","system","263897","29-04-2025 20:46:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_319","NOCINC0004915148","SOA 2","=
","29-04-2025 20:46:15","29-04-2025 20:41:57","29-04-2025 21:18:51","Cascad=
ed Incident from TTO5031893","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down because Gen fa=
iled to start due PWC dysfonction // He reset the PWC and Gen manually star=
ted","system","263894","29-04-2025 20:46:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004915146","SOA TOWN=
","","29-04-2025 20:46:15","29-04-2025 20:41:57","29-04-2025 21:18:51","Cas=
caded Incident from TTO5031893","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 failed to start due PWC dysfonction // He reset the PWC and Gen manually s=
tarted","system","263897","29-04-2025 20:46:15","MATECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0004915111","Soa=
","IHS_YND_318, IHS_YND_320, IHS_YND_720, IHS_YND_319, IHS_YND_308, IHS_YND=
_323, IHS_YND_307","29-04-2025 20:43:18","29-04-2025 20:41:57","29-04-2025 =
21:18:51","Grid outage site went down because Gen failed to start due PWC d=
ysfonction // He reset the PWC and Gen manually started","Siligap Boris","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage site went down because Gen failed to start due PWC dysfonction // He=
 reset the PWC and Gen manually started","edwige.kapawo@matech-cameroun.com=
","81","29-04-2025 20:43:18","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004915090","Men=
dong NB","","29-04-2025 20:41:01","29-04-2025 20:33:59","30-04-2025 11:29:0=
2","Grid outage.site went down because landlord did not start his gen//Grid=
 return","","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage.site went down because landlord did not start his gen//Grid re=
turn","edwige.kapawo@matech-cameroun.com","423","29-04-2025 20:41:01","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004915034","A=
ccacia New","","29-04-2025 20:34:55","29-04-2025 20:05:44","29-04-2025 21:3=
5:21","Fme gildas is on the way eta 09:30 PM","","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site site went because Ge=
n failed to started due to PWC dysfunction // He reset it and manually star=
ted the GEN	","christelle.ngonga@matech-cameroun.com","273404","29-04-2025 =
20:34:55","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004914998","Nsi=
malen MTN","","29-04-2025 20:30:53","29-04-2025 20:21:59","29-04-2025 23:35=
:52","Grid transformer of the Quarter explodes , site down because, Gen CB =
tripped // Gen CB reamed, investigation on going)","Albran Byorel","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Load Breaker","Grid transformer of =
the Quarter explodes , site down because, Gen CB tripped // Gen CB reamed, =
investigation on going","edwige.kapawo@matech-cameroun.com","535","29-04-20=
25 20:30:53","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004914936","Odz=
a Minkan IHS","","29-04-2025 20:19:27","29-04-2025 20:13:56","30-04-2025 02=
:18:40","Site went down because gen start and stopped due to grid bad volta=
ge, no rcp  // Gen started manually(Noticed that there is dysfunction at th=
e BTS MTN)","Albran Byorel","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Site went down because gen start and stopped due=
 to grid bad voltage, no rcp  // Gen started manually(Noticed that there is=
 dysfunction at the BTS MTN)","edwige.kapawo@matech-cameroun.com","332","29=
-04-2025 20:19:27","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004914914","B=
iteng-Maetur","","29-04-2025 20:16:59","29-04-2025 20:03:52","29-04-2025 21=
:17:34","Grid outage, site went down because gen failed to start due to PWC=
 ZTE malfunction // He reset controller ","Mba Lazare Herve","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down because gen failed to start due to PWC ZTE malfunction // He res=
et controller ","christelle.ngonga@matech-cameroun.com","789","29-04-2025 2=
0:16:59","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0004914901","C=
hapelle-Nsimeyong","","29-04-2025 20:13:30","29-04-2025 20:05:44","29-04-20=
25 22:17:02","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","	TTO5031621","christelle.ngonga@matech-cameroun.com","=
273404","29-04-2025 20:13:30","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0004914863","N=
simalen OCM","","29-04-2025 20:07:09","29-04-2025 19:59:54","29-04-2025 23:=
28:56","Grid transformer of the Quarter explodes , Equipement connected on =
the MTN DG, Gen CB tripped  // Gen CB reamed, investigation on going","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","G=
rid transformer of the Quarter explodes , site down because, Gen CB tripped=
 // Gen CB reamed, investigation on going)","christelle.ngonga@matech-camer=
oun.com","436","29-04-2025 20:07:09","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004914835","Nko=
l-Mbanda","IHS_YND_562, IHS_YND_148","29-04-2025 20:02:02","29-04-2025 19:5=
7:44","29-04-2025 21:35:02","Grid outage site site went because Gen failed =
to started due to PWC dysfunction // He reset it and manually started the G=
EN	","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","Grid outage site site went because Gen failed to started =
due to PWC dysfunction // He reset it and manually started the GEN	","edwig=
e.kapawo@matech-cameroun.com","259","29-04-2025 20:02:02","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004914830","Sca=
lom","","29-04-2025 20:01:03","29-04-2025 19:56:39","29-04-2025 20:10:15","=
Grid outage.gen failed to start due to automation malfunctionning//Grid ret=
urn","Paul BIBOUM","Equipment Repair","Passive","Control Panel","ATS-AMF Is=
sue","Grid outage.gen failed to start due to automation malfunctionning//Gr=
id return","edwige.kapawo@matech-cameroun.com","265","29-04-2025 20:01:03",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_212","NOCINC0004914743","H-Genera=
l-Yde","","29-04-2025 19:43:39","29-04-2025 17:25:13","29-04-2025 20:28:46"=
,"Site went down Because gen fails to start due to lack of 2 phases on site=
 // He make the bridge with a good phase (power reset done)","Siligap Boris=
","Grid Supply","Passive","Grid","National Grid - Grid Incomplete Phase","S=
ite went down Because gen fails to start due to lack of 2 phases on site //=
 He make the bridge with a good phase (power reset done)","christelle.ngong=
a@matech-cameroun.com","8306","29-04-2025 19:43:39","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004914736","NYO=
M FACE MAETUR","","29-04-2025 19:42:09","29-04-2025 19:38:56","29-04-2025 2=
0:38:31","Grid fluctuation,Site went down because Gen failed to start due t=
o Grid bad voltage // Grid stabilized","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,Si=
te went down because Gen failed to start due to Grid bad voltage // Grid st=
abilized","edwige.kapawo@matech-cameroun.com","195","29-04-2025 19:42:09","=
MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004914732","Eto=
ug ebe Carrefour","","29-04-2025 19:41:28","29-04-2025 19:37:12","29-04-202=
5 20:28:45","Grid fluctuation, Site went down because Gen failed to start d=
ue to Grid bad voltage //Grid power stabilized","Hyemafo Gildas","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctu=
ation, Site went down because Gen failed to start due to Grid bad voltage /=
/Grid power stabilized","edwige.kapawo@matech-cameroun.com","256","29-04-20=
25 19:41:28","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004914572","Ako=
k Ndoe Yde","","29-04-2025 19:24:30","29-04-2025 19:22:20","29-04-2025 20:1=
9:17","Grid outage, Site went down before  Gen start due to poor backup// G=
en manually Started","Hyemafo Gildas","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before  =
Gen start due to poor backup// Gen manually Started","edwige.kapawo@matech-=
cameroun.com","131","29-04-2025 19:24:30","MATECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0004914518","Nsa=
m Sofavinc","","29-04-2025 19:16:25","29-04-2025 18:48:09","29-04-2025 19:5=
8:25","Site went Down due to rectifier circuit breaker falls // He rearmed =
CB","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier - C=
ircuit Breaker","Site went Down due to rectifier circuit breaker falls // H=
e rearmed CB","edwige.kapawo@matech-cameroun.com","1696","29-04-2025 19:16:=
25","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004914512","Odz=
a petit marche new","","29-04-2025 19:14:17","29-04-2025 18:50:59","29-04-2=
025 22:08:20","Site went down due to 01/03 rectifiers dysfunctionning on si=
te//he reset it and site on Grid","Albran Byorel","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to 01/03 rectifiers =
dysfunctionning on site//he reset it and site on Grid","edwige.kapawo@matec=
h-cameroun.com","1399","29-04-2025 19:14:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004914273","ELOUMDEM=
 CARRIERE 2","","29-04-2025 18:26:42","29-04-2025 18:23:32","29-04-2025 18:=
29:13","Cascaded Incident from TTO5030906","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup// Gen Automatically","system","272297","=
29-04-2025 18:26:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004914272","Eto koss=
 Yde","","29-04-2025 18:26:42","29-04-2025 18:23:32","29-04-2025 18:29:13",=
"Cascaded Incident from TTO5030906","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup// Gen Automatically","system","272297","29-04-2=
025 18:26:42","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004914264","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","29-04-2025 18:25:57","29-04-2025 18:23=
:32","29-04-2025 18:29:13","Grid outage, Site went down before Gen start du=
e to poor backup// Gen Automatically","Fanda Brice","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup// Gen Automatically","franck.nkom=
ot@matech-cameroun.com","147","29-04-2025 18:25:57","MATECH CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004914261","B=
iteng","","29-04-2025 18:25:21","29-04-2025 18:17:55","29-04-2025 19:17:52"=
,"Site down due to ZTE Dysfonction de la bay // Gen manually started","Mba =
Lazare Herve","Equipment Repair","Passive","Control Panel","Panel Distribut=
ion Board","Site down due to ZTE Dysfonction de la bay // Gen manually star=
ted","christelle.ngonga@matech-cameroun.com","447","29-04-2025 18:25:21","M=
ATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004914250","Men=
dong NB","","29-04-2025 18:24:08","29-04-2025 18:21:56","29-04-2025 19:43:0=
9","Grid Only, No space to deploy  // Grid return","","Grid Supply","Passiv=
e","Grid","National Grid - Grid Outage Issue","Grid Only, No space to deplo=
y  // Grid return","edwige.kapawo@matech-cameroun.com","133","29-04-2025 18=
:24:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0004914246","Dagobert=
","","29-04-2025 18:22:52","29-04-2025 18:14:22","29-04-2025 18:45:50","Cas=
caded Incident from TTO5030862","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site Ubaie:5=
2.7 V The FME TX Mohamadou (691144435)from Huawei is informed","system","26=
5841","29-04-2025 18:22:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0004914244","Yona Hot=
el","","29-04-2025 18:22:51","29-04-2025 18:14:22","29-04-2025 18:45:50","C=
ascaded Incident from TTO5030862","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
:52.7 V The FME TX Mohamadou (691144435)from Huawei is informed","system","=
265841","29-04-2025 18:22:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0004914245","Crf-Nkol=
bisson","","29-04-2025 18:22:51","29-04-2025 18:14:22","29-04-2025 18:45:50=
","Cascaded Incident from TTO5030862","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue on site U=
baie:52.7 V The FME TX Mohamadou (691144435)from Huawei is informed","syste=
m","265841","29-04-2025 18:22:51","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0004914226","N=
kolbi-Boss","IHS_YND_271, IHS_YND_232, IHS_YND_286","29-04-2025 18:20:39","=
29-04-2025 18:14:22","29-04-2025 18:45:50","No power issue on site Ubaie:52=
.7 V The FME TX Mohamadou (691144435)from Huawei is informed","TIENTCHEU NZ=
ETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","No power issue on site Ubaie:52.7 V The FME TX Mo=
hamadou (691144435)from Huawei is informed","christelle.ngonga@matech-camer=
oun.com","378","29-04-2025 18:20:39","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0004913999","E=
lig Edzoa","","29-04-2025 17:42:28","29-04-2025 17:07:16","29-04-2025 19:33=
:43","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS=
 IHS is informed // Grid return","christelle.ngonga@matech-cameroun.com","2=
77057","29-04-2025 17:42:28","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004913996","E=
lig-Edzoa","","29-04-2025 17:41:44","29-04-2025 17:07:16","29-04-2025 19:33=
:43","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is inform=
ed // Grid return","christelle.ngonga@matech-cameroun.com","277056","29-04-=
2025 17:41:44","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004913989","A=
WAE OCM","","29-04-2025 17:38:52","29-04-2025 17:35:44","29-04-2025 18:44:1=
5","Grid outage, site went down because gen failed to start due to PWC ZTE =
malfunction, // He resetrand gen manually started","Mba Lazare Herve","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Is=
sue","Site went down because the PWC OF ZTE dysfonction // He reset the PWC=
","christelle.ngonga@matech-cameroun.com","189","29-04-2025 17:38:52","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004913975","N=
kolo II New","","29-04-2025 17:37:17","29-04-2025 17:32:59","29-04-2025 17:=
53:20","Site impacted by CTR_654 Mimboman Don Bosco wich is not manage by I=
HS","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","Site impacted by CTR_654 Mimboma=
n Don Bosco wich is not manage by IHS","christelle.ngonga@matech-cameroun.c=
om","259","29-04-2025 17:37:17","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004913911","Bit=
eng-Maetur","","29-04-2025 17:21:25","29-04-2025 17:16:16","29-04-2025 18:5=
6:49","Site down due to ZTE Dysfonction de la bay // Reset and  Gen manuall=
y started","Mba Lazare Herve","Equipment Repair","Passive","Control Panel",=
"Panel Distribution Board","Site down due to ZTE Dysfonction de la bay // R=
eset and  Gen manually started","christelle.ngonga@matech-cameroun.com","31=
0","29-04-2025 17:21:25","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004913841","N=
omayos montee Meche","","29-04-2025 17:11:09","29-04-2025 17:06:00","29-04-=
2025 18:27:14","Active: No power issue, site is on grid with Ubaie=3D53V, F=
lubert(654266068) from Huawei is informed","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
: No power issue, site is on grid with Ubaie=3D53V, Flubert(654266068) from=
 Huawei is informed","christelle.ngonga@matech-cameroun.com","309","29-04-2=
025 17:11:09","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0004913838","N=
taba","IHS_YND_133, IHS_YND_504","29-04-2025 17:10:23","29-04-2025 17:07:16=
","29-04-2025 19:33:43","site went down due to PWC Overload(12Kw 250A) Blai=
se Raoul SS IHS is informed // Grid return","Delor Telezing","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","site went down due to PWC Over=
load(12Kw 250A) Blaise Raoul SS IHS is informed // Grid return","christelle=
.ngonga@matech-cameroun.com","188","29-04-2025 17:10:23","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004913802","NTU=
I TOWN","","29-04-2025 17:06:21","29-04-2025 17:04:59","29-04-2025 21:14:04=
","Site went down Because gen fails to start due to lack of 01 phase on sit=
e // He make the bridge with a good phase: Site on grid","Parker Tchoup","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Sit=
e went down Because gen fails to start due to lack of 01 phase on site // H=
e make the bridge with a good phase: Site on grid","franck.nkomot@matech-ca=
meroun.com","83","29-04-2025 17:06:21","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004913687","E=
mana Lycee","","29-04-2025 16:43:21","29-04-2025 16:35:24","29-04-2025 16:5=
0:33","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage,site went down before Gen started due to poor B=
attery Backup//Gen automatically started","christelle.ngonga@matech-camerou=
n.com","1214021","29-04-2025 16:43:21","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004913685","E=
mana lycee 2","IHS_YND_274","29-04-2025 16:42:33","29-04-2025 16:35:24","29=
-04-2025 16:50:33","Grid outage,site went down before Gen started due to po=
or Battery Backup//Grid Retun","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage,site went dow=
n before Gen started due to poor Battery Backup//Grid Retun","christelle.ng=
onga@matech-cameroun.com","430","29-04-2025 16:42:33","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004913675","H=
-General-Yde","","29-04-2025 16:41:54","29-04-2025 16:27:43","29-04-2025 17=
:24:41","No power issue site on grid with Ubay:54.4V Symphorien /691316854 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with Ubay:54.4V Symphorien /691316854 from Huawei is informed","chris=
telle.ngonga@matech-cameroun.com","851","29-04-2025 16:41:54","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004913664","Nom=
ayos montee Meche","","29-04-2025 16:40:09","29-04-2025 16:36:00","29-04-20=
25 16:40:15","Active: No power issue, site is on grid with Ubaie=3D53V, Flu=
bert(654266068) from Huawei is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No power issue, site is on grid with Ubaie=3D53V, Flubert(654266068) from H=
uawei is informed","christelle.ngonga@matech-cameroun.com","250","29-04-202=
5 16:40:09","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004913649","Mes=
sassi 2","","29-04-2025 16:39:32","29-04-2025 16:35:26","29-04-2025 16:45:4=
0","Site down due to planted rectifiers // Rectifiers reset , site on grid"=
,"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site down due to planted rectifiers // Rectifiers reset , site on grid=
","christelle.ngonga@matech-cameroun.com","247","29-04-2025 16:39:32","MATE=
CH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0004913631","Lob=
o 2","","29-04-2025 16:38:42","29-04-2025 16:33:28","29-04-2025 19:01:48","=
Grid outage site went down because Gen failed to start due to Hybrid system=
 dysfonction // He reset the hybrid system and Gen manually started","TIENT=
CHEU NZETCHIEU GAEL","Equipment Repair","Passive","Hybrid","Hybrid Module",=
"Grid outage site went down because Gen failed to start due to Hybrid syste=
m dysfonction // He reset the hybrid system and Gen manually started","chri=
stelle.ngonga@matech-cameroun.com","315","29-04-2025 16:38:42","MATECH CMR"
"Closed Complete","Site Down","T1328","IHS_YND_247","NOCINC0004913624","Oko=
lo","","29-04-2025 16:38:01","29-04-2025 16:31:54","29-04-2025 16:41:03","A=
CTIVE// No power issue site Ubaie=3D52.5V site on Gen, The tx Fme Symphorie=
n(650257151)from Huawei is informed.","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE/=
/ No power issue site Ubaie=3D52.5V site on Gen, The tx Fme Symphorien(6502=
57151)from Huawei is informed.","christelle.ngonga@matech-cameroun.com","36=
7","29-04-2025 16:38:01","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004913305","Nsi=
malen MTN","","29-04-2025 15:46:06","29-04-2025 15:28:53","29-04-2025 16:18=
:22","Grid transformer of the Quarter explodes , site down because, Gen CB =
tripped  // Gen CB reamed, investigation on going","Albran Byorel","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Load Breaker","Grid transformer of =
the Quarter explodes , site down because, Gen CB tripped  // Gen CB reamed,=
 investigation on going","christelle.ngonga@matech-cameroun.com","1034","29=
-04-2025 15:46:06","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0004913288","N=
simalen OCM","","29-04-2025 15:43:01","29-04-2025 15:38:47","29-04-2025 16:=
12:03","Grid transformer of the Quarter explodes , Equipement connected on =
the MTN DG, Gen CB tripped  // Gen CB reamed, investigation on going","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","G=
rid transformer of the Quarter explodes , site down because, Gen CB tripped=
  // Gen CB reamed, investigation on going","christelle.ngonga@matech-camer=
oun.com","255","29-04-2025 15:43:01","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004913181","E=
lig-Edzoa","","29-04-2025 15:20:07","29-04-2025 15:03:00","29-04-2025 15:25=
:27","Wrongly logged ticket","","Incorrectly Logged Tickets","Error","Error=
","Error","Wrongly logged ticket","christelle.ngonga@matech-cameroun.com","=
1028","29-04-2025 15:20:07","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004913165","E=
MANA BILICK CITY","","29-04-2025 15:16:56","29-04-2025 15:02:39","29-04-202=
5 16:36:32","Grid outage, Gen stopped by landload for noise disturbance, //=
 Grid restoration","Fabrice Pouakam","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid outage, Gen stopped by landload for nois=
e disturbance, // Grid restoration","christelle.ngonga@matech-cameroun.com"=
,"858","29-04-2025 15:16:56","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004913162","M=
essassi okolo","","29-04-2025 15:16:14","29-04-2025 15:15:02","29-04-2025 1=
6:37:47","Site impacted by CTR_799  pont emana wish is not manage by IHS","=
Fabrice Pouakam","3RD Party Power Failure","Passive","Power Provided By 3RD=
 Party","Power Provided By 3RD Party","Site impacted by CTR_799  pont emana=
 wish is not manage by IHS","christelle.ngonga@matech-cameroun.com","73","2=
9-04-2025 15:16:14","MATECH CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0004912566","H=
-Deputes","","29-04-2025 14:02:13","29-04-2025 13:49:03","29-04-2025 16:14:=
24","No power issue on site Ubaie=3D54.5 V, Brice stague 650214096 of huawe=
i is informed","","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","No power issue on site Ubaie=3D54.5 V, Brice =
stague 650214096 of huawei is informed","christelle.ngonga@matech-cameroun.=
com","791","29-04-2025 14:02:13","MATECH CMR"
"Closed Complete","Site Down","T0958","IHS_YND_269","NOCINC0004912564","Mvo=
g-Ebanda","","29-04-2025 14:01:58","29-04-2025 13:58:45","29-04-2025 15:26:=
50","Grid outage site went down due to Gen failed to start //Grid return(in=
vestigation ongoing)","Siligap Boris","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","Grid outage site went down due to Gen =
failed to start //Grid return(investigation ongoing)","ludivine.ngamaleu@ih=
stowers.com","194","29-04-2025 14:01:58","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004912560","N=
koabang Ebolmedjock","","29-04-2025 14:01:05","29-04-2025 13:11:54","29-04-=
2025 14:12:10","Site impated by Nkomessing Abom CTR_711  wich is not manage=
 by IHS","Mba Lazare Herve","Customer Equipment Failure","Active","Active E=
quipment Failure","Affected by 3rd Party Site","Site impated by Nkomessing =
Abom CTR_711  wich is not manage by IHS","christelle.ngonga@matech-cameroun=
.com","2952","29-04-2025 14:01:05","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004912505","Bar=
riere","","29-04-2025 13:53:25","29-04-2025 13:38:12","29-04-2025 14:46:48"=
,"Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Feli=
x Zambe is informed and confirmed //Grid return","Hyemafo Gildas","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went do=
wn because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and con=
firmed //Grid return","ludivine.ngamaleu@ihstowers.com","914","29-04-2025 1=
3:53:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004912335","Ebogo","=
","29-04-2025 13:34:07","29-04-2025 13:17:33","29-04-2025 13:27:33","Cascad=
ed Incident from TTO5028642","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down because Gen fa=
iled to start due PWC dysfonction // He reset the PWC and Gen manually star=
ted","system","269258","29-04-2025 13:34:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004912333","Melen Ba=
'aba","","29-04-2025 13:34:06","29-04-2025 13:17:33","29-04-2025 13:27:33",=
"Cascaded Incident from TTO5028642","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen failed to start due PWC dysfonction // He reset the PWC and Gen manual=
ly started","system","269257","29-04-2025 13:34:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_319","NOCINC0004912332","SOA 2","=
","29-04-2025 13:34:06","29-04-2025 13:17:33","29-04-2025 13:27:33","Cascad=
ed Incident from TTO5028642","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down because Gen fa=
iled to start due PWC dysfonction // He reset the PWC and Gen manually star=
ted","system","269259","29-04-2025 13:34:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004912331","SOA UNIV=
ERSITY STADIUM","","29-04-2025 13:34:06","29-04-2025 13:17:33","29-04-2025 =
13:27:33","Cascaded Incident from TTO5028642","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage site went do=
wn because Gen failed to start due PWC dysfonction // He reset the PWC and =
Gen manually started","system","269258","29-04-2025 13:34:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004912334","SOA VILL=
AGE","","29-04-2025 13:34:06","29-04-2025 13:17:33","29-04-2025 13:27:33","=
Cascaded Incident from TTO5028642","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC dysfonction // He reset the PWC and Gen manuall=
y started","system","269259","29-04-2025 13:34:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_318","NOCINC0004912329","SOA Univ=
ersity","","29-04-2025 13:34:05","29-04-2025 13:17:33","29-04-2025 13:27:33=
","Cascaded Incident from TTO5028642","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage site went down becau=
se Gen failed to start due PWC dysfonction // He reset the PWC and Gen manu=
ally started","system","269260","29-04-2025 13:34:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004912330","SOA TOWN=
","","29-04-2025 13:34:05","29-04-2025 13:17:33","29-04-2025 13:27:33","Cas=
caded Incident from TTO5028642","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 failed to start due PWC dysfonction // He reset the PWC and Gen manually s=
tarted","system","269257","29-04-2025 13:34:05","MATECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0004912313","Soa=
","IHS_YND_318, IHS_YND_320, IHS_YND_720, IHS_YND_319, IHS_YND_308, IHS_YND=
_323, IHS_YND_307","29-04-2025 13:32:12","29-04-2025 13:17:33","29-04-2025 =
13:27:33","Grid outage site went down because Gen failed to start due PWC d=
ysfonction // He reset the PWC and Gen manually started","Siligap Boris","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage site went down because Gen failed to start due PWC dysfonction // He=
 reset the PWC and Gen manually started","franck.nkomot@matech-cameroun.com=
","880","29-04-2025 13:32:12","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004911680","H=
-General-Yde","","29-04-2025 12:40:42","29-04-2025 12:36:33","29-04-2025 12=
:49:31"," No power issue site on grid with Ubay:54.4V Symphorien /691316854=
 from Huawei is informed","Siligap Boris","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm"," No power issue site =
on grid with Ubay:54.4V Symphorien /691316854 from Huawei is informed","chr=
istelle.ngonga@matech-cameroun.com","250","29-04-2025 12:40:42","MATECH CMR=
"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004911469","Saa=
","IHS_YND_810, IHS_YND_809","29-04-2025 12:26:23","29-04-2025 12:22:11","2=
9-04-2025 13:00:11","Grid outage, Site went down because Gen start and stop=
ped with ""High temps"" alarm // he added water and manually start the Gen"=
,"Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High Engin=
e Temp - Coolant Level Issue","Grid outage, Site went down because Gen star=
t and stopped with ""High temps"" alarm // he added water and manually star=
t the Gen","ludivine.ngamaleu@ihstowers.com","253","29-04-2025 12:26:23","M=
ATECH CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0004911436","Car=
refour Ayissi Ele","","29-04-2025 12:23:16","29-04-2025 12:22:11","29-04-20=
25 13:00:11","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Grid outage, Site went down because Gen start and stop=
ped with ""High temps"" alarm // he added water and manually start the Gen"=
,"ludivine.ngamaleu@ihstowers.com","265357","29-04-2025 12:23:16","MATECH C=
MR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004911432","Nko=
l-Mebanga","","29-04-2025 12:22:21","29-04-2025 12:22:11","29-04-2025 13:00=
:11","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, Site went down because Gen start and stopped with=
 ""High temps"" alarm // he added water and manually start the Gen","ludivi=
ne.ngamaleu@ihstowers.com","265358","29-04-2025 12:22:21","MATECH CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0004911429","Ess=
os Marche","","29-04-2025 12:21:43","29-04-2025 11:59:23","29-04-2025 12:16=
:23","Active// No power issue, Ubaie: 52.5 V Site on Grid The TX FME Armand=
 (691144412) from Huawei is informed","Delor Telezing","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
 No power issue, Ubaie: 52.5 V Site on Grid The TX FME Armand (691144412) f=
rom Huawei is informed","ludivine.ngamaleu@ihstowers.com","1341","29-04-202=
5 12:21:43","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004911198","M=
ANGUIERS CHAPELLE","","29-04-2025 12:01:46","29-04-2025 11:53:37","30-04-20=
25 10:41:42","Grid outage, site went down due to gen overload (22kva, 340A)=
 SS HISBernard ATANGANA is informed and confirmed","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went=
 down due to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed =
and confirmed","christelle.ngonga@matech-cameroun.com","490","29-04-2025 12=
:01:46","MATECH CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004910932","Cha=
rles-Atangana","","29-04-2025 11:24:08","29-04-2025 10:15:39","29-04-2025 1=
1:22:54"," Grid only site ,no space to deploy MGE // Grid restoration","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"," Grid on=
ly site ,no space to deploy MGE // Grid restoration","ludivine.ngamaleu@ihs=
towers.com","4287","29-04-2025 11:24:08","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004910665","Bas=
tos-BAT","","29-04-2025 10:51:48","29-04-2025 10:21:22","29-04-2025 11:53:0=
3","Grid outage site went down because Gen failed to start due to poor batt=
ery backup//Gen automatically started","Mboua Thierry","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site we=
nt down because Gen failed to start due to poor battery backup//Gen automat=
ically started","ludivine.ngamaleu@ihstowers.com","2651","29-04-2025 10:51:=
48","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004910634","Mok=
olo Yaounde","","29-04-2025 10:48:36","29-04-2025 10:16:06","29-04-2025 13:=
14:06","Grid outage.no space to deploy mobile gen// Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no=
 space to deploy mobile gen// Grid return","ludivine.ngamaleu@ihstowers.com=
","1951","29-04-2025 10:48:36","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004910594","N=
omayos montee Meche","","29-04-2025 10:44:54","29-04-2025 10:09:47","29-04-=
2025 12:55:47","Active: No power issue, site is on grid with Ubaie=3D53V, F=
lubert(654266068) from Huawei is informed","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
: No power issue, site is on grid with Ubaie=3D53V, Flubert(654266068) from=
 Huawei is informed","christelle.ngonga@matech-cameroun.com","2108","29-04-=
2025 10:44:54","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004910586","M=
essassi 2","","29-04-2025 10:43:10","29-04-2025 10:08:57","29-04-2025 11:13=
:06","Site down due to  planted rectifiers  // Rectifiers reset , site on g=
rid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site down due to  planted rectifiers  // Rectifiers reset , site o=
n grid","christelle.ngonga@matech-cameroun.com","2055","29-04-2025 10:43:10=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004910390","SOA VILL=
AGE","","29-04-2025 10:13:55","29-04-2025 10:08:35","29-04-2025 11:14:35","=
Cascaded Incident from TTO5026441","Siligap Boris","Cascade Outage","Active=
","Cascade Active","Cascade Active"," Site went down due to plan work by FM=
E Blaise Raoul is currently in site (PWC configuration) // End of work","sy=
stem","273305","29-04-2025 10:13:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004910391","Ebogo","=
","29-04-2025 10:13:55","29-04-2025 10:08:35","29-04-2025 11:14:35","Cascad=
ed Incident from TTO5026441","Siligap Boris","Cascade Outage","Active","Cas=
cade Active","Cascade Active"," Site went down due to plan work by FME Blai=
se Raoul is currently in site (PWC configuration) // End of work","system",=
"273305","29-04-2025 10:13:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004910387","SOA UNIV=
ERSITY STADIUM","","29-04-2025 10:13:54","29-04-2025 10:08:35","29-04-2025 =
11:14:35","Cascaded Incident from TTO5026441","Siligap Boris","Cascade Outa=
ge","Active","Cascade Active","Cascade Active"," Site went down due to plan=
 work by FME Blaise Raoul is currently in site (PWC configuration) // End o=
f work","system","273307","29-04-2025 10:13:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_319","NOCINC0004910388","SOA 2","=
","29-04-2025 10:13:54","29-04-2025 10:08:35","29-04-2025 11:14:35","Cascad=
ed Incident from TTO5026441","Siligap Boris","Cascade Outage","Active","Cas=
cade Active","Cascade Active"," Site went down due to plan work by FME Blai=
se Raoul is currently in site (PWC configuration) // End of work","system",=
"273305","29-04-2025 10:13:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004910386","SOA TOWN=
","","29-04-2025 10:13:54","29-04-2025 10:08:35","29-04-2025 11:14:35","Cas=
caded Incident from TTO5026441","Siligap Boris","Cascade Outage","Active","=
Cascade Active","Cascade Active"," Site went down due to plan work by FME B=
laise Raoul is currently in site (PWC configuration) // End of work","syste=
m","273306","29-04-2025 10:13:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004910389","Melen Ba=
'aba","","29-04-2025 10:13:54","29-04-2025 10:08:35","29-04-2025 11:14:35",=
"Cascaded Incident from TTO5026441","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active"," Site went down due to plan work by F=
ME Blaise Raoul is currently in site (PWC configuration) // End of work","s=
ystem","273306","29-04-2025 10:13:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_318","NOCINC0004910385","SOA Univ=
ersity","","29-04-2025 10:13:53","29-04-2025 10:08:35","29-04-2025 11:14:35=
","Cascaded Incident from TTO5026441","Siligap Boris","Cascade Outage","Act=
ive","Cascade Active","Cascade Active"," Site went down due to plan work by=
 FME Blaise Raoul is currently in site (PWC configuration) // End of work",=
"system","273307","29-04-2025 10:13:53","MATECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0004910359","Soa=
","IHS_YND_318, IHS_YND_320, IHS_YND_720, IHS_YND_319, IHS_YND_308, IHS_YND=
_323, IHS_YND_307","29-04-2025 10:09:48","29-04-2025 10:08:35","29-04-2025 =
11:14:35"," Site went down due to plan work by FME Blaise Raoul (PWC config=
uration) // End of work","Siligap Boris","Customer Equipment Failure","Acti=
ve","Planned Activity","Planned Activity - Active"," Site went down due to =
plan work by FME Blaise Raoul (PWC configuration) // End of work","franck.n=
komot@matech-cameroun.com","73","29-04-2025 10:09:48","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004910311","Nsi=
malen MTN","","29-04-2025 10:00:43","29-04-2025 09:56:53","29-04-2025 11:08=
:28","Grid  transformer of the Quarter explodes , site down because, gen tu=
rned till fuel shortage // site refueled 200L","Albran Byorel","Fuel Outage=
","Passive","Diesel","Diesel Outage","Grid  transformer of the Quarter expl=
odes , site down because, gen turned till fuel shortage // site refueled 20=
0L","franck.nkomot@matech-cameroun.com","231","29-04-2025 10:00:43","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004910243","E=
kombitie","","29-04-2025 09:46:31","29-04-2025 09:28:21","29-04-2025 09:40:=
21","Active: no power issue, site is on Gen with Ubaie=3D54.6V, Symphorien(=
650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue, site is on Gen with Ubaie=3D54.6V, Symphorien(650257151/ huawei)=
 is informed","franck.nkomot@matech-cameroun.com","1091","29-04-2025 09:46:=
31","MATECH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0004910113","Lob=
o 2","","29-04-2025 09:24:59","29-04-2025 09:19:45","29-04-2025 12:02:45","=
Hybrid gen site. Site went down due to hybrid system failure//Gen manually =
started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Hybrid","=
Hybrid Module","Hybrid gen sitesite went down due to hybrid system failure/=
/Gen manually started","ludivine.ngamaleu@ihstowers.com","315","29-04-2025 =
09:24:59","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004910078","Ako=
k Ndoe Yde","","29-04-2025 09:21:29","29-04-2025 09:11:59","29-04-2025 09:3=
6:23","Grid outage, Site went down before Gen start due to poor backup// Ge=
n manually Started","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// Gen manually Started","ludivine.ngamaleu@ihsto=
wers.com","571","29-04-2025 09:21:29","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0004910067","Mba=
nkolo petit paris","","29-04-2025 09:19:40","29-04-2025 09:09:59","29-04-20=
25 18:23:33","Active: no power issue, site is on Gen with Ubaie=3D54.3V, Mo=
hamadou((691144435) from Huawie is informed,","Mboua Thierry","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive: no power issue, site is on Gen with Ubaie=3D54.3V, Mohamadou((691144=
435) from Huawie is informed,","ludivine.ngamaleu@ihstowers.com","582","29-=
04-2025 09:19:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0004910038","Mvog-Man=
ga","","29-04-2025 09:13:04","29-04-2025 08:54:29","29-04-2025 09:43:29","C=
ascaded Incident from TTO5025999","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to CB ((125A) dis=
juncted at OCM =E9quipements//CB rearmed","system","299174","29-04-2025 09:=
13:04","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004909988","Odz=
a Minkan IHS","","29-04-2025 09:00:44","29-04-2025 08:44:54","29-04-2025 12=
:45:54","Active//No Power issue on site U=3D51.4V site on Grid. The Tx Fme =
Lionel Adjep (655184876) From HUAWEI is informed","Albran Byorel","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No Power issue on site U=3D51.4V site on Grid. The Tx Fme Lionel=
 Adjep (655184876) From HUAWEI is informed","ludivine.ngamaleu@ihstowers.co=
m","951","29-04-2025 09:00:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0004909985","Marche O=
dza","","29-04-2025 09:00:14","29-04-2025 08:54:29","29-04-2025 09:43:29","=
Cascaded Incident from TTO5025999","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to CB ((125A) di=
sjuncted at OCM =E9quipements//CB rearmed","system","299174","29-04-2025 09=
:00:14","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004909979","O=
dza","IHS_YND_254, IHS_YND_580","29-04-2025 08:59:07","29-04-2025 08:54:29"=
,"29-04-2025 09:43:29","Site went down due to CB ((125A) disjuncted at OCM =
=E9quipements//CB rearmed","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to=
 CB ((125A) disjuncted at OCM =E9quipements//CB rearmed","franck.nkomot@mat=
ech-cameroun.com","279","29-04-2025 08:59:07","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004909789","O=
LAMA","","29-04-2025 08:12:35","29-04-2025 07:25:17","29-04-2025 08:25:17",=
"No power issue on site U:54.9 V( hybrid site). The Tx FME Henri (699949693=
)from Huawei is informed.","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 U:54.9 V( hybrid site). The Tx FME Henri (699949693)from Huawei is informe=
d.","loic.noumsi@matech-cameroun.com","2840","29-04-2025 08:12:35","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0004909750","Mamch Bu=
ilding","","29-04-2025 08:06:01","29-04-2025 07:31:54","29-04-2025 09:32:17=
","Cascaded Incident from TTO5025571","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage ,no space to deploy =
MGE","system","275593","29-04-2025 08:06:01","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004909712","Nko=
l-Mbanda","","29-04-2025 08:00:24","29-04-2025 07:51:12","29-04-2025 08:48:=
12","Grid fluctuation,Site went down due to Grid bad voltage//site stabilis=
ed","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation,Site went down due to Grid bad voltage/=
/site stabilised","loic.noumsi@matech-cameroun.com","555","29-04-2025 08:00=
:24","MATECH CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004909600","Cha=
rles-Atangana","IHS_YND_051","29-04-2025 07:38:01","29-04-2025 07:31:54","2=
9-04-2025 09:32:17","Grid outage ,no space to deploy MGE","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,no space=
 to deploy MGE","loic.noumsi@matech-cameroun.com","369","29-04-2025 07:38:0=
1","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004909228","Mok=
olo Yaounde","","29-04-2025 06:39:40","29-04-2025 06:27:28","29-04-2025 09:=
02:57","Grid outage.no space to deploy mobile gen//Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deploy mobile gen//Grid return","loic.noumsi@matech-cameroun.com",=
"733","29-04-2025 06:39:40","MATECH CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004909185","S=
tade-Abega","","29-04-2025 06:26:16","29-04-2025 04:11:40","29-04-2025 06:4=
2:06","Grid outage,site went down because Gen failed to start due to pwc ZT=
E dysfunction// he reset it and started Gen manualy","Mba Lazare Herve","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid o=
utage,site went down because Gen failed to start due to pwc ZTE dysfunction=
// he reset it and started Gen manualy","loic.noumsi@matech-cameroun.com","=
8077","29-04-2025 06:26:16","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004909069","B=
arriere","","29-04-2025 05:33:21","29-04-2025 05:30:16","29-04-2025 11:34:1=
6","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because G=
en overload(20kva,400 A) IHS SS Felix Zambe is informed and confirmed","loi=
c.noumsi@matech-cameroun.com","187","29-04-2025 05:33:21","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004909018","Eto=
ug ebe Carrefour","","29-04-2025 05:07:37","29-04-2025 04:29:26","29-04-202=
5 07:09:15","Grid outage, site went down because gen ran untill fuel shorta=
ge // He bypassed Gen and put Grid on site","Hyemafo Gildas","Fuel Outage",=
"Passive","Diesel","Diesel Outage","Grid outage, site went down because gen=
 ran untill fuel shortage // He bypassed Gen and put Grid on site","gaelle.=
njiofack@matech-cameroun.com","2291","29-04-2025 05:07:37","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004909013","Lad=
a I Yde","","29-04-2025 05:02:50","29-04-2025 04:54:37","29-04-2025 05:22:3=
7","Site went down due to rectifier dysfunctioned//We reset rectifier and s=
ite on grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to rectifier dysfunctioned//We reset r=
ectifier and site on grid","loic.noumsi@matech-cameroun.com","494","29-04-2=
025 05:02:50","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004908994","M=
ANGUIERS CHAPELLE","","29-04-2025 04:51:21","28-04-2025 20:48:00","29-04-20=
25 07:46:49","Grid  meter burn, gen overload (22kva, 340A)  //Gen manually =
started","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid  meter burn, gen overload (22kva, 340A)  //Gen manually sta=
rted","kouoh.jean@ihstowers.com","29002","29-04-2025 04:51:21","MATECH CMR"
"Closed Complete","Site Down","T2743","IHS_YND_721","NOCINC0004908921","VOI=
RIE MUNICIPALE YAOUNDE","","29-04-2025 04:24:20","29-04-2025 04:11:02","29-=
04-2025 04:26:42","error ticket","Paul BIBOUM","Incorrectly Logged Tickets"=
,"Error","Error","Error","error ticket","gaelle.njiofack@matech-cameroun.co=
m","799","29-04-2025 04:24:20","MATECH CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0004908846","A=
FEME NORD","","29-04-2025 03:54:14","29-04-2025 03:18:05","29-04-2025 06:03=
:05","Site went die to CB (125A) disjuncted at MTN equiments //CB rearmed",=
"TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Circuit Breaker Issue","Site went die to CB (125A) disjuncted=
 at MTN equiments //CB rearmed","loic.noumsi@matech-cameroun.com","2170","2=
9-04-2025 03:54:14","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004908636","N=
kolo II New","","29-04-2025 02:42:44","29-04-2025 02:13:36","29-04-2025 03:=
36:32","Active/	No power issue site on Gen with U=3D53.5V The FME Tx Lionel=
 Steve /655184876/ From huawei is informed.","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active/	No power issue site on Gen with U=3D53.5V The FME Tx Lionel Steve =
/655184876/ From huawei is informed.","loic.noumsi@matech-cameroun.com","17=
49","29-04-2025 02:42:44","MATECH CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004908519","S=
calom-IHS","","29-04-2025 01:52:07","28-04-2025 21:33:53","29-04-2025 01:09=
:52","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid outage, Gen failed to start due unknow raison (Access issues during th=
e night) // Grid return","kouoh.jean@ihstowers.com","275367","29-04-2025 01=
:52:07","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004908502","S=
calom","","29-04-2025 01:48:01","28-04-2025 21:33:53","29-04-2025 01:09:52"=
,"","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Grid outage, Gen failed to start due unknow raison (Access issues du=
ring the night) // Grid return","kouoh.jean@ihstowers.com","275367","29-04-=
2025 01:48:01","MATECH CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0004908491","Ese=
ka Town","","29-04-2025 01:47:16","29-04-2025 01:33:08","29-04-2025 04:32:3=
1","Grid outage, site went down due to Card Ge faulty // he reseted it and =
started Gen manually","Kemeni Franklin","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid outage, site went down due to Card Ge fau=
lty // he reseted it and started Gen manually","vanel.mbiada@matech-camerou=
n.com","1015","29-04-2025 01:47:16","MATECH CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0004908454","ODZ=
A BORNE 10","","29-04-2025 01:29:45","29-04-2025 01:18:20","29-04-2025 04:4=
9:56","Site went down because 3 rectifiers damaged due to lightning // He r=
eplaced 2 rectifiers and site on grid","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down because 3 rectifier=
s damaged due to lightning // He replaced 2 rectifiers and site on grid","v=
anel.mbiada@matech-cameroun.com","686","29-04-2025 01:29:45","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0004908368","Mba=
nkolo petit paris","","29-04-2025 01:04:51","29-04-2025 00:57:55","29-04-20=
25 02:45:56","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Grid outage, SIte went down due to Grid fluctuations /=
/ he bypassed Grid and put site on Gen","gaelle.njiofack@matech-cameroun.co=
m","270184","29-04-2025 01:04:51","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0004908354","AFE=
ME NORD","IHS_YND_808","29-04-2025 01:00:05","29-04-2025 00:55:55","29-04-2=
025 02:45:56","Grid outage, SIte went down due to Grid fluctuations // he b=
ypassed Grid and put site on Gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid outage, SI=
te went down due to Grid fluctuations // he bypassed Grid and put site on G=
en","gaelle.njiofack@matech-cameroun.com","337","29-04-2025 01:00:05","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004908066","B=
arriere","","28-04-2025 23:47:35","28-04-2025 23:46:19","29-04-2025 04:50:1=
0","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // Grid returned","Hyemafo Gildas","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site we=
nt down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed an=
d confirmed // Grid returned","kouoh.jean@ihstowers.com","77","28-04-2025 2=
3:47:35","MATECH CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004908038","S=
aa","","28-04-2025 23:45:02","28-04-2025 21:50:44","29-04-2025 02:19:03","G=
rid outage, site went down baecause gen failed to start due to battery Gen =
faulty // Gen manually start with external battery","Parker Tchoup","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, s=
ite went down baecause gen failed to start due to battery Gen faulty // Gen=
 manually start with external battery","kouoh.jean@ihstowers.com","6859","2=
8-04-2025 23:45:02","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004908030","Jou=
vence Mbenda","","28-04-2025 23:42:03","28-04-2025 23:21:54","29-04-2025 06=
:13:54","Grid outage site went down because Gen stopped with alarm HIGH tem=
p // He added water Gen manually started","Hyemafo Gildas","Equipment Repai=
r","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gr=
id outage site went down because Gen stopped with alarm HIGH temp // He add=
ed water Gen manually started","gaelle.njiofack@matech-cameroun.com","1210"=
,"28-04-2025 23:42:03","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004908026","Oko=
lo Kilombo","","28-04-2025 23:40:50","28-04-2025 23:36:43","29-04-2025 00:2=
8:41","Grid fluctuation,Site went down because Gen failed to start due to G=
rid bad voltage // Grid stabilized ","Fabrice Pouakam","Grid Supply","Passi=
ve","Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuation,S=
ite went down because Gen failed to start due to Grid bad voltage // Grid s=
tabilized ","gaelle.njiofack@matech-cameroun.com","248","28-04-2025 23:40:5=
0","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004908020","Men=
dong vallee","","28-04-2025 23:39:56","28-04-2025 23:23:48","29-04-2025 07:=
01:15","Grid outage, Site went down due to Gen overload (20 KVA, 330A) // G=
rid restored ","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down due to Gen overload (20 KVA, 330A)=
 // Grid restored ","gaelle.njiofack@matech-cameroun.com","969","28-04-2025=
 23:39:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004907955","Scalom-I=
HS","","28-04-2025 23:16:54","28-04-2025 20:59:47","28-04-2025 21:33:46","C=
ascaded Incident from TTO5023065","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage,site went down because gen failed to =
start due to no automatism on site//He started the Gen manually","system","=
270334","28-04-2025 23:16:54","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004907916","Ebo=
go","","28-04-2025 23:06:58","28-04-2025 22:41:44","28-04-2025 23:02:10","G=
rid outage,site went down before gen starts due to poor battery backup//Gri=
d return","Siligap Boris","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage,site went down before gen starts due=
 to poor battery backup//Grid return","vanel.mbiada@matech-cameroun.com","1=
515","28-04-2025 23:06:58","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004907893","A=
wae Ewonkan","","28-04-2025 22:56:00","28-04-2025 22:17:07","28-04-2025 22:=
30:08","Grid outage site went down due to Gen Overload (20Kva, load 310 A) =
// he reduced load","Albran Byorel","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","	Grid outage site went down due to Gen Overload (20Kva,=
 load 310 A) // he reduced load","kouoh.jean@ihstowers.com","2334","28-04-2=
025 22:56:00","MATECH CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0004907871","B=
ONAS YDE","","28-04-2025 22:53:26","28-04-2025 22:19:13","29-04-2025 01:33:=
22","Grid outage, site went down Gen failed to start due to PWC ZTE malfunc=
tion // He reseted it and started Gen manually","Paul BIBOUM","Equipment Re=
pair","Passive","Control Panel","Panel Distribution Board","Grid outage, si=
te went down Gen failed to start due to PWC ZTE malfunction // He reseted i=
t and started Gen manually","vanel.mbiada@matech-cameroun.com","2054","28-0=
4-2025 22:53:26","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004907832","NYO=
M FACE MAETUR","","28-04-2025 22:43:45","28-04-2025 22:36:34","28-04-2025 2=
3:22:40","Grid fluctuation,Site went down because Gen failed to start due t=
o Grid bad voltage // Grid stabilized ","Fabrice Pouakam","Grid Supply","Pa=
ssive","Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuatio=
n,Site went down because Gen failed to start due to Grid bad voltage // Gri=
d stabilized ","cedric.tiani@matech-cameroun.com","432","28-04-2025 22:43:4=
5","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004907675","Meh=
anda 1","","28-04-2025 22:10:55","28-04-2025 22:08:40","28-04-2025 22:47:29=
","Grid outage, Gen failed to start due unknow raison (Access issues during=
 the night) // Grid return","Albran Byorel","Access Denial","Security","Sec=
urity Concerns In Site Environs","Access Issue - Security","Grid outage, Ge=
n failed to start due unknow raison (Access issues during the night) // Gri=
d return","cedric.tiani@matech-cameroun.com","136","28-04-2025 22:10:55","M=
ATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004907631","Odz=
a II OCM","","28-04-2025 22:07:57","28-04-2025 21:58:59","28-04-2025 23:00:=
50","Grid fluctuations, site went down because Gen failed to start due to g=
rid bad voltage // Grid stabilized","Albran Byorel","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuations, site =
went down because Gen failed to start due to grid bad voltage // Grid stabi=
lized","cedric.tiani@matech-cameroun.com","540","28-04-2025 22:07:57","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0004907612","A=
bom","","28-04-2025 22:03:54","28-04-2025 21:27:43","28-04-2025 23:20:37","=
Grid Outage Site went down because Gen FAILED To start due to Alarm ""Under=
frequency'' (Gen overload)  // He reseted it","Siligap Boris","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage Site went do=
wn because Gen FAILED To start due to Alarm ""Underfrequency'' (Gen overloa=
d)  // He reseted it","vanel.mbiada@matech-cameroun.com","2172","28-04-2025=
 22:03:54","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004907577","Mok=
olo Yaounde","","28-04-2025 21:57:38","28-04-2025 21:02:27","28-04-2025 22:=
11:00","site went down due to insufficient of rectifier on site SS IHS Bern=
ard is informed// site stabilized","","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","	site went down due to insufficient of rectifier on=
 site SS IHS Bernard is informed// site stabilized","cedric.tiani@matech-ca=
meroun.com","3312","28-04-2025 21:57:38","MATECH CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0004907553","A=
v-Germaine","","28-04-2025 21:53:47","28-04-2025 21:31:38","29-04-2025 05:0=
2:33","ACTIVE No power issue on site, site on Grid with Ubaie=3D53.4 V THE =
Tx fme Armand Nguetsa /699949553/ from Huawei is informed","","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
CTIVE No power issue on site, site on Grid with Ubaie=3D53.4 V THE Tx fme A=
rmand Nguetsa /699949553/ from Huawei is informe","vanel.mbiada@matech-came=
roun.com","1330","28-04-2025 21:53:47","MATECH CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004907546","Abo=
me","","28-04-2025 21:52:14","28-04-2025 21:25:01","29-04-2025 05:01:04","N=
o power issue on site Ubay 53.7V site on Grid and The TX FME Leonel Steve (=
655184876) from huawei is informed , site up without intervention","MINKA N=
ICOLAS","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site Ubay 53.7V site on Grid and The =
TX FME Leonel Steve (655184876) from huawei is informed , site up without i=
ntervention","cedric.tiani@matech-cameroun.com","1634","28-04-2025 21:52:14=
","MATECH CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004907522","S=
hell-Nsimeyong","IHS_YND_070, IHS_YND_505, IHS_YND_071, IHS_YND_155","28-04=
-2025 21:48:02","28-04-2025 21:07:53","29-04-2025 01:09:52","Grid outage, A=
ccess issue during the Night due to landord // Grid returned","MINKA NICOLA=
S","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage, Access issue during the Night due to landord // Grid returned","va=
nel.mbiada@matech-cameroun.com","17089","28-04-2025 21:48:02","MATECH CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0004907512","Sim=
bock Maetur","","28-04-2025 21:46:40","28-04-2025 21:28:24","28-04-2025 22:=
40:10","Grid outage, Gen failed to star due to his alimentation card faulty=
 // bride make with fuse and Gen started manually","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Coolant Pipe","Grid outage, Gen fa=
iled to star due to his alimentation card faulty // bride make with fuse an=
d Gen started manually","cedric.tiani@matech-cameroun.com","1097","28-04-20=
25 21:46:40","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004907499","Mvo=
g-Manga","","28-04-2025 21:44:27","28-04-2025 21:36:17","28-04-2025 21:56:2=
2","Grid fluctuation, site went down because Gen failed to start due to Gri=
d fluctuations // Grid returned","Albran Byorel","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Grid fluctuation, site went=
 down because Gen failed to start due to Grid fluctuations // Grid returned=
","cedric.tiani@matech-cameroun.com","491","28-04-2025 21:44:27","MATECH CM=
R"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004907439","E=
foulan","","28-04-2025 21:36:33","28-04-2025 21:07:53","29-04-2025 01:09:52=
","Active// No power issue site on grid with Ubai1=3D55.1V, Site on GRID Th=
e TX Fme Hosiah / 674007438// from huawei is informed","MINKA NICOLAS","Cas=
cade Outage","Passive","Cascade Passive","Cascade Passive","Active// No pow=
er issue site on grid with Ubai1=3D55.1V, Site on GRID The TX Fme Hosiah / =
674007438// from huawei is informed","vanel.mbiada@matech-cameroun.com","17=
471","28-04-2025 21:36:33","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004907363","Sca=
lom","IHS_YND_505","28-04-2025 21:21:59","28-04-2025 20:59:47","28-04-2025 =
21:33:46","Grid outage,site went down because gen failed to start due to no=
 automatism on site//He started the Gen manually","Paul BIBOUM","Equipment =
Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,site went do=
wn because gen failed to start due to no automatism on site//He started the=
 Gen manually","cedric.tiani@matech-cameroun.com","1333","28-04-2025 21:21:=
59","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004907305","Tam=
tam Weekend","","28-04-2025 21:15:50","28-04-2025 21:11:43","28-04-2025 22:=
11:37","Active: No power issue site on Grid with U=3D51,9V The TX FME Mbah =
Hosiah (674007438) FROM Huawei is informed","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue site on Grid with U=3D51,9V The TX FME Mbah Hosiah (67=
4007438) FROM Huawei is informed","cedric.tiani@matech-cameroun.com","247",=
"28-04-2025 21:15:50","MATECH CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004907303","O=
bobogo","","28-04-2025 21:15:21","28-04-2025 21:07:53","29-04-2025 01:09:52=
","Active//No power issue on site ,site on Gen with Ubaie=3D51V The Tx FME =
Lionnel // 694693436 from Huawei is informed","MINKA NICOLAS","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Active//No power issue o=
n site ,site on Gen with Ubaie=3D51V The Tx FME Lionnel // 694693436 from H=
uawei is informed","vanel.mbiada@matech-cameroun.com","17460","28-04-2025 2=
1:15:21","MATECH CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004907301","Nsi=
meyong Shell","","28-04-2025 21:15:17","28-04-2025 21:07:06","29-04-2025 01=
:13:22","Grid outage, access issue during the night // Grid returned","MINK=
A NICOLAS","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid outage, access issue during the night // Grid returned","cedric.ti=
ani@matech-cameroun.com","492","28-04-2025 21:15:17","MATECH CMR"
"Closed Complete","Site Down","T3180","IHS_YND_253","NOCINC0004907277","Clg=
e-Advantiste","","28-04-2025 21:13:39","28-04-2025 21:06:25","29-04-2025 04=
:56:26","	Active/ No power issue site on grid with U=3D50.8V Lionnel Steeve=
(655184876) from Huawei is informed","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Active/ N=
o power issue site on grid with U=3D50.8V Lionnel Steeve(655184876) from Hu=
awei is informed","cedric.tiani@matech-cameroun.com","435","28-04-2025 21:1=
3:39","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0004907256","Aba=
ng","","28-04-2025 21:10:48","28-04-2025 20:57:04","28-04-2025 21:15:52","c=
ascade","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, Site went downdue to poor backup// Grid restor=
ed","cedric.tiani@matech-cameroun.com","335210","28-04-2025 21:10:48","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004907255","D=
amas","","28-04-2025 21:10:39","28-04-2025 21:03:30","29-04-2025 08:04:38",=
"Active//No power issue on site ,site on Grid with Ubaie=3D52.2 V he FME Th=
e TX FME Mbah Hosiah (674007438) is informed","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site ,site on Grid with Ubaie=3D54.3 V he FME The =
TX FME Mbah Hosiah (674007438) is informed","vanel.mbiada@matech-cameroun.c=
om","430","28-04-2025 21:10:39","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0004907214","Nko=
langaa","IHS_YND_290","28-04-2025 21:05:19","28-04-2025 20:57:04","28-04-20=
25 21:15:52","Grid outage, Site went downdue to poor backup// Grid restored=
","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Battery Low","Grid outage, Site went downdue to poor backup// Grid =
restored","cedric.tiani@matech-cameroun.com","496","28-04-2025 21:05:19","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0004907212","C=
harles-Atangana","","28-04-2025 21:04:29","28-04-2025 21:00:20","28-04-2025=
 22:15:30","Grid outage //Grid restored.","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid outage //Grid restored.","vanel.=
mbiada@matech-cameroun.com","251","28-04-2025 21:04:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004907206","Emana Ly=
cee","","28-04-2025 21:03:37","28-04-2025 20:57:48","28-04-2025 21:13:04","=
Cascaded Incident from TTO5022860","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down before=
 Gen started due to poor Battery Backup//Gen automatically started","system=
","277365","28-04-2025 21:03:37","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004907198","E=
mana lycee 2","IHS_YND_274","28-04-2025 21:03:04","28-04-2025 20:57:48","28=
-04-2025 21:13:04","Grid outage,site went down before Gen started due to po=
or Battery Backup//Gen automatically started","Fabrice Pouakam","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outag=
e,site went down before Gen started due to poor Battery Backup//Gen automat=
ically started","vanel.mbiada@matech-cameroun.com","317","28-04-2025 21:03:=
04","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004907196","Nko=
ulou Carriere carrefourt","","28-04-2025 21:02:42","28-04-2025 20:56:31","2=
8-04-2025 22:30:44","Grid outage gen failed to start due to alarm '' low oi=
l pressure''//We add oil and gen manually started ","Mba Lazare Herve","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage =
gen failed to start due to alarm '' low oil pressure''//We add oil and gen =
manually started ","cedric.tiani@matech-cameroun.com","372","28-04-2025 21:=
02:42","MATECH CMR"
"Closed Complete","Site Down","CTR_273","IHS_YND_214","NOCINC0004907188","N=
kolmesseng-II","","28-04-2025 21:00:45","28-04-2025 20:54:31","28-04-2025 2=
2:49:18","Grid outage, Gen stopped with alarm Under voltage // Gen card res=
et and site on Gen","Siligap Boris","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Under Voltage","Grid outage, Gen stopped with alarm Under voltage =
// Gen card reset and site on Gen","vanel.mbiada@matech-cameroun.com","375"=
,"28-04-2025 21:00:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004907158","Ebogo","=
","28-04-2025 20:57:12","28-04-2025 20:47:14","28-04-2025 20:58:53","Cascad=
ed Incident from TTO5022800","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down because Gen fa=
iled to start due PWC dysfonction // He reset the PWC and Gen manually star=
ted","system","598","28-04-2025 20:57:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_319","NOCINC0004907156","SOA 2","=
","28-04-2025 20:57:12","28-04-2025 20:47:14","28-04-2025 20:58:53","Cascad=
ed Incident from TTO5022800","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down because Gen fa=
iled to start due PWC dysfonction // He reset the PWC and Gen manually star=
ted","system","598","28-04-2025 20:57:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004907157","SOA VILL=
AGE","","28-04-2025 20:57:12","28-04-2025 20:47:14","28-04-2025 20:58:53","=
Cascaded Incident from TTO5022800","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC dysfonction // He reset the PWC and Gen manuall=
y started","system","598","28-04-2025 20:57:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_318","NOCINC0004907153","SOA Univ=
ersity","","28-04-2025 20:57:11","28-04-2025 20:47:14","28-04-2025 20:58:53=
","Cascaded Incident from TTO5022800","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage site went down becau=
se Gen failed to start due PWC dysfonction // He reset the PWC and Gen manu=
ally started","system","597","28-04-2025 20:57:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004907155","SOA UNIV=
ERSITY STADIUM","","28-04-2025 20:57:11","28-04-2025 20:47:14","28-04-2025 =
20:58:53","Cascaded Incident from TTO5022800","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage site went do=
wn because Gen failed to start due PWC dysfonction // He reset the PWC and =
Gen manually started","system","597","28-04-2025 20:57:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004907154","SOA TOWN=
","","28-04-2025 20:57:11","28-04-2025 20:47:14","28-04-2025 20:58:53","Cas=
caded Incident from TTO5022800","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 failed to start due PWC dysfonction // He reset the PWC and Gen manually s=
tarted","system","597","28-04-2025 20:57:11","MATECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0004907144","Soa=
","IHS_YND_318, IHS_YND_320, IHS_YND_720, IHS_YND_319, IHS_YND_323, IHS_YND=
_307","28-04-2025 20:55:26","28-04-2025 20:47:14","28-04-2025 20:58:53","Gr=
id outage site went down because Gen failed to start due PWC dysfonction //=
 He reset the PWC and Gen manually started","Siligap Boris","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage site w=
ent down because Gen failed to start due PWC dysfonction // He reset the PW=
C and Gen manually started","cedric.tiani@matech-cameroun.com","492","28-04=
-2025 20:55:26","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004907140","N=
kolo II New","","28-04-2025 20:54:35","28-04-2025 20:48:26","28-04-2025 21:=
00:59","No power issue, site is on Grid with Ubaie=3D53,4V, Lionel adjep(65=
5184876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on Grid with Ubaie=3D53,4V, Lionel adjep(655184876) from Huaw=
ei is informed","vanel.mbiada@matech-cameroun.com","370","28-04-2025 20:54:=
35","MATECH CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0004907134","Nke=
ng likok","","28-04-2025 20:53:08","28-04-2025 20:46:56","28-04-2025 20:47:=
08","wrongly created ticket","Kemeni Franklin","Incorrectly Logged Tickets"=
,"Error","Error","Error","wrongly created ticket","cedric.tiani@matech-came=
roun.com","373","28-04-2025 20:53:08","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0004907065","Y=
oko OCM","IHS_YND_405, IHS_YND_456","28-04-2025 20:41:47","28-04-2025 20:36=
:28","28-04-2025 20:40:35","ACTIVE No power issue on site U =3D 56,6 V site=
 on Grid TX FME Gregoire / 654547479 is informed.Noticed heavy rain ","Park=
er Tchoup","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","ACTIVE No power issue on site U =3D 56,6 V site on G=
rid TX FME Gregoire / 654547479 is informed.Noticed heavy rain ","vanel.mbi=
ada@matech-cameroun.com","320","28-04-2025 20:41:47","MATECH CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0004907051","M=
BIMBIM","","28-04-2025 20:38:57","28-04-2025 20:36:28","28-04-2025 20:40:35=
","","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Ac=
tive","ACTIVE No power issue on site U =3D 56,6 V site on Grid TX FME Grego=
ire / 654547479 is informed.Noticed heavy rain ","vanel.mbiada@matech-camer=
oun.com","264416","28-04-2025 20:38:57","MATECH CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0004907016","N=
goum","","28-04-2025 20:32:00","28-04-2025 19:40:43","28-04-2025 21:17:37",=
"ACTIVE no power issue U:53.6V site on grid. TX FME APPIAH Gregoire/6545474=
79/ from Huawei is informed.	","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE no power =
issue U:53.6V site on grid. TX FME APPIAH Gregoire/654547479/ from Huawei i=
s informed.	","vanel.mbiada@matech-cameroun.com","3079","28-04-2025 20:32:0=
0","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004906945","OBA=
M NGOLA OCM","","28-04-2025 20:22:44","28-04-2025 20:07:31","28-04-2025 22:=
23:59","Site went down due to (03/04) Rectifiers dysfonction // He Reset it=
 and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down due to (03/04) Rectifiers dysfonctio=
n // He Reset it and Site is on Grid","cedric.tiani@matech-cameroun.com","9=
14","28-04-2025 20:22:44","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004906800","Nko=
g-Edzen","","28-04-2025 20:00:05","28-04-2025 19:51:57","29-04-2025 01:00:4=
9","Active: No power issue site on Battery with U=3D52.4 V ( start threshol=
d =3D50 V)The Tx Fme Gregoire(654547479) from Huawei is informed","Parker T=
choup","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active: No power issue site on Battery with U=3D52.4 V (=
 start threshold =3D50 V)The Tx Fme Gregoire(654547479) from Huawei is info=
rmed","vanel.mbiada@matech-cameroun.com","489","28-04-2025 20:00:05","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004906615","SAA Entr=
ance","","28-04-2025 19:33:40","28-04-2025 19:18:56","28-04-2025 21:38:05",=
"Cascaded Incident from TTO5022130","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to insufficient=
 rectifier on site //He reset it ","system","276316","28-04-2025 19:33:40",=
"MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004906579","SAA=
 2","IHS_YND_542, IHS_YND_405","28-04-2025 19:27:18","28-04-2025 19:18:56",=
"28-04-2025 21:38:05","Site went down due to insufficient rectifier on site=
 //He reset it ","Parker Tchoup","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to insufficient rectifier on site //H=
e reset it ","cedric.tiani@matech-cameroun.com","503","28-04-2025 19:27:18"=
,"MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004906554","Saa=
","","28-04-2025 19:21:37","28-04-2025 19:18:56","28-04-2025 21:38:17","Fme=
 is informed ETA 08:05 PM","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","ACTIVE No power issue on site U =3D 56,6 V =
site on Grid TX FME Gregoire / 654547479 is informed.Noticed heavy rain ","=
cedric.tiani@matech-cameroun.com","276315","28-04-2025 19:21:37","MATECH CM=
R"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0004906408","Ebe=
ba","","28-04-2025 18:51:27","28-04-2025 18:43:19","28-04-2025 19:47:46","G=
rid hybrid gen site gen failed to start due to alarm high temp//We add wate=
r and gen manually started ","Fanda Brice","Equipment Repair","Passive","AC=
DG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid hybrid gen si=
te gen failed to start due to alarm high temp//We add water and gen manuall=
y started ","cedric.tiani@matech-cameroun.com","489","28-04-2025 18:51:27",=
"MATECH CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004906403","Nsi=
meyong Shell","","28-04-2025 18:50:58","28-04-2025 18:42:47","28-04-2025 19=
:00:51","Grid outage//He deploy 33KVA","MINKA NICOLAS","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage//He deploy 33KV=
A","cedric.tiani@matech-cameroun.com","492","28-04-2025 18:50:58","MATECH C=
MR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004906389","O=
bobogo","","28-04-2025 18:50:29","28-04-2025 18:42:13","28-04-2025 18:55:48=
","Grid outage,site went down before Gen start due to poor battery backup//=
 Gen started automatically","MINKA NICOLAS","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage,site went down bef=
ore Gen start due to poor battery backup// Gen started automatically","vane=
l.mbiada@matech-cameroun.com","497","28-04-2025 18:50:29","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004906386","E=
foulan","","28-04-2025 18:49:54","28-04-2025 18:42:48","28-04-2025 20:04:22=
","Active// No power issue site on grid with Ubai1=3D54.6V, Site on GRID Th=
e TX Fme Hosiah / 674007438// from huawei is informed","MINKA NICOLAS","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active// No power issue site on grid with Ubai1=3D54.6V, Site on GR=
ID The TX Fme Hosiah / 674007438// from huawei is informed","vanel.mbiada@m=
atech-cameroun.com","426","28-04-2025 18:49:54","MATECH CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004906383","S=
hell-Nsimeyong","","28-04-2025 18:49:15","28-04-2025 18:41:10","28-04-2025 =
18:54:16","cable connecting equipment to stolen generator // disabling eneo=
 and starting GE","MINKA NICOLAS","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage//He deploy 33KVA","vanel.mbiada@mate=
ch-cameroun.com","487","28-04-2025 18:49:15","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004906360","S=
calom","","28-04-2025 18:46:52","28-04-2025 18:41:31","28-04-2025 18:54:32"=
,"Active//No power issue on site ,site on Grid with Ubaie=3D52.5V The TX FM=
E Mbah Hosiah (674007438) from Huawei is informed ","Paul BIBOUM","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site ,site on Grid with Ubaie=3D52.5V The TX F=
ME Mbah Hosiah (674007438) from Huawei is informed ","vanel.mbiada@matech-c=
ameroun.com","322","28-04-2025 18:46:52","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004906260","Men=
dong NB","","28-04-2025 18:31:06","28-04-2025 18:28:55","29-04-2025 17:11:5=
7","Grid outage no space to deployed a mobile Gen awaiting   //  Grid retur=
n","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid outage no space to deployed a mobile Gen awaiting   //  Grid return","c=
edric.tiani@matech-cameroun.com","131","28-04-2025 18:31:06","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004906197","M=
essassi 2","","28-04-2025 18:22:53","28-04-2025 18:16:25","28-04-2025 20:57=
:29","Site went down due to rectifier issues // Grid stabilised","Fabrice P=
ouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site w=
ent down due to rectifier issues // Grid stabilised","vanel.mbiada@matech-c=
ameroun.com","390","28-04-2025 18:22:53","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004905869","O=
dza II OCM","","28-04-2025 17:58:43","28-04-2025 17:55:24","28-04-2025 18:3=
9:28","Site went down due to work of our FME Albran(657108542) on site (ins=
tallation of ATS)//End of work","Albran Byorel","Installation Activity","Pa=
ssive","Planned Activity","Installation Activity","Site went down due to wo=
rk of our FME Albran(657108542) on site (installation of ATS)//End of work"=
,"vanel.mbiada@matech-cameroun.com","200","28-04-2025 17:58:43","MATECH CMR=
"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004905505","Imm=
-Olympique","","28-04-2025 17:12:25","28-04-2025 17:03:59","28-04-2025 17:1=
3:33","Site went down due to insufficient rectifiers on site//He reset it(N=
eeded to add 01 or 02 rectifiers )","Paul BIBOUM","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to insufficient rect=
ifiers on site//He reset it(Needed to add 01 or 02 rectifiers )","cedric.ti=
ani@matech-cameroun.com","507","28-04-2025 17:12:25","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004905499","NTU=
I TOWN","","28-04-2025 17:11:32","28-04-2025 17:02:59","28-04-2025 19:57:45=
","Grid outage,site went down because Gen failed to start due to Grid conta=
ctor not excited//He excited and site on Gen","Parker Tchoup","Equipment Re=
pair","Passive","Control Panel","ATS-AMF Issue","Grid outage,site went down=
 because Gen failed to start due to Grid contactor not excited//He excited =
and site on Gen","cedric.tiani@matech-cameroun.com","514","28-04-2025 17:11=
:32","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004905447","H=
-General-Yde","","28-04-2025 17:04:13","28-04-2025 17:01:46","28-04-2025 18=
:09:46","Active // No power issue site on grid with Ubay:54.4V Symphorien /=
691316854 from Huawei is informed","Siligap Boris","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue site on grid with Ubay:54.4V Symphorien /691316854 from Huawei=
 is informed","vanel.mbiada@matech-cameroun.com","148","28-04-2025 17:04:13=
","MATECH CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0004905384","Ole=
mbe","","28-04-2025 16:55:52","28-04-2025 16:54:27","28-04-2025 17:23:42","=
Grid fluctuation,site went down because Gen failed to start due to Grid bad=
 voltage,RCP on site(not well configured)//He bypassed the Grid and site on=
 GEN","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid fluctuation,site went down because Gen failed t=
o start due to Grid bad voltage,RCP on site(not well configured)//He bypass=
ed the Grid and site on GEN","cedric.tiani@matech-cameroun.com","87","28-04=
-2025 16:55:52","MATECH CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0004905353","B=
oumnyebel OCM","","28-04-2025 16:54:12","28-04-2025 16:50:24","28-04-2025 1=
6:51:28","Wrongly created ticket","Kemeni Franklin","Incorrectly Logged Tic=
kets","Error","Error","Error","Wrongly created ticket","vanel.mbiada@matech=
-cameroun.com","228","28-04-2025 16:54:12","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004905305","OTE=
LE MTN","","28-04-2025 16:47:28","28-04-2025 16:39:59","28-04-2025 18:38:43=
","Grid outage,site went because Gen failed to start due to Battery Gen fau=
lty and low oil pressure //He added oil and  maually started with an extern=
al battery ","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - =
Generator Battery","Grid outage,site went because Gen failed to start due t=
o Battery Gen faulty and low oil pressure //He added oil and  maually start=
ed with an external battery ","cedric.tiani@matech-cameroun.com","450","28-=
04-2025 16:47:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0004905228","Elig-Edz=
oa","","28-04-2025 16:43:03","28-04-2025 16:40:22","28-04-2025 16:41:14","C=
ascaded Incident from TTO5020587","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","site went down due to PWC Overload(12Kw 250A) Bla=
ise Raoul SS IHS is iformed // Site stablised and site is on Grid","system"=
,"161","28-04-2025 16:43:03","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004905214","Nta=
ba","IHS_YND_133","28-04-2025 16:41:30","28-04-2025 16:40:22","28-04-2025 1=
6:47:37","site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS=
 is iformed // Site stablised and site is on Grid","Delor Telezing","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","site went =
down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is iformed // Site =
stablised and site is on Grid","cedric.tiani@matech-cameroun.com","70","28-=
04-2025 16:41:30","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004905206","B=
arriere","","28-04-2025 16:40:46","28-04-2025 16:37:34","28-04-2025 23:26:2=
4","GEN OVERLOAD","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage, Site went down because Gen overload(20kva,4=
00 A) IHS SS Felix Zambe is informed and confirmed//He reduced the load and=
 site on GEN","vanel.mbiada@matech-cameroun.com","193","28-04-2025 16:40:46=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004904590","Mom","",=
"28-04-2025 16:05:47","28-04-2025 15:58:40","28-04-2025 16:04:53","Cascaded=
 Incident from TTO5019903","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on grid with U=3D54v Site is=
 impacted by Ngoumou who is not our responsability.Henri (699949693) from H=
uawei is informed.","system","266783","28-04-2025 16:05:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004904588","OTELE MT=
N","","28-04-2025 16:05:46","28-04-2025 15:58:40","28-04-2025 16:04:53","Ca=
scaded Incident from TTO5019903","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on grid with U=3D54v S=
ite is impacted by Ngoumou who is not our responsability.Henri (699949693) =
from Huawei is informed.","system","266782","28-04-2025 16:05:46","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004904589","Minka","=
","28-04-2025 16:05:46","28-04-2025 15:58:40","28-04-2025 16:04:53","Cascad=
ed Incident from TTO5019903","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability.Henri (699949693) from=
 Huawei is informed.","system","266782","28-04-2025 16:05:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004904587","OLAMA","=
","28-04-2025 16:05:46","28-04-2025 15:58:40","28-04-2025 16:04:53","Cascad=
ed Incident from TTO5019903","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability.Henri (699949693) from=
 Huawei is informed.","system","266783","28-04-2025 16:05:46","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004904579","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","28-04-2025 16:04:=
49","28-04-2025 15:58:40","28-04-2025 17:04:00","No power issue site on gri=
d with U=3D54v Site is impacted by Ngoumou who is not our responsability.He=
nri (699949693) from Huawei is informed.","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","Affected by 3rd Party Site",=
"No power issue site on grid with U=3D54v Site is impacted by Ngoumou who i=
s not our responsability.Henri (699949693) from Huawei is informed.","cedri=
c.tiani@matech-cameroun.com","370","28-04-2025 16:04:49","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004904373","Nom=
ayos montee Meche","","28-04-2025 15:42:53","28-04-2025 15:40:45","28-04-20=
25 16:50:44","Active: No power issue, site is on grid with Ubaie=3D53V, Flu=
bert(654266068) from Huawei is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No power issue, site is on grid with Ubaie=3D53V, Flubert(654266068) from H=
uawei is informed","cedric.tiani@matech-cameroun.com","129","28-04-2025 15:=
42:53","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004904349","Imm=
-Olympique","","28-04-2025 15:39:40","28-04-2025 15:34:33","28-04-2025 15:5=
2:03","Site went down due to insufficient rectifiers on site//He reset it(N=
eeded to add 01 or 02 rectifiers )","Paul BIBOUM","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to insufficient rect=
ifiers on site//He reset it(Needed to add 01 or 02 rectifiers )","cedric.ti=
ani@matech-cameroun.com","308","28-04-2025 15:39:40","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004904334","N=
koabang2","","28-04-2025 15:37:36","28-04-2025 15:34:14","28-04-2025 15:45:=
55","Site went down due to work of Herve mbah(657108482) on site  ( doing P=
M)//End of work","Mba Lazare Herve","Installation Activity","Passive","Plan=
ned Activity","Installation Activity","Site went down due to work of Herve =
mbah(657108482) on site  ( doing PM)//End of work","vanel.mbiada@matech-cam=
eroun.com","203","28-04-2025 15:37:36","MATECH CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0004904201","B=
yemassi Carrefour","","28-04-2025 15:16:09","28-04-2025 15:13:52","28-04-20=
25 16:20:25","Active//No power issue on site ,site on Gen with Ubaie=3D53.3=
V The FME TX Bah Hosiah //674007438// From Huawei is Informed,","Paul BIBOU=
M","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issue on site ,site on Gen with Ubaie=3D53.=
3V The FME TX Bah Hosiah //674007438// From Huawei is Informed,","vanel.mbi=
ada@matech-cameroun.com","137","28-04-2025 15:16:09","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004904195","E=
ssomba","","28-04-2025 15:15:11","28-04-2025 15:13:58","28-04-2025 15:18:55=
","Site went down due to Rectifier issue // He reseted the rectifier","Mba =
Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down due to Rectifier issue // He reseted the rectifier","vanel.m=
biada@matech-cameroun.com","75","28-04-2025 15:15:11","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004904169","E=
kombitie","","28-04-2025 15:10:19","28-04-2025 15:04:01","28-04-2025 17:10:=
49"," no power issue, site is on Gen with Ubaie=3D 54.6V, Symphorien(650257=
151) from huawei is informed.Repetitive Issue","Fabrice Pouakam","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
," no power issue, site is on Gen with Ubaie=3D 54.6V, Symphorien(650257151=
) from huawei is informed.Repetitive Issue","vanel.mbiada@matech-cameroun.c=
om","380","28-04-2025 15:10:19","MATECH CMR"
"Closed Complete","Site Down","CTR_447","IHS_YND_061","NOCINC0004904038","Y=
de University","","28-04-2025 14:55:06","28-04-2025 14:52:59","28-04-2025 1=
5:06:28","Active//No power issue on site ,site on Grid with Ubaie=3D53.6 V =
The Tx FME Hosiah//674 007438 Notice that we have dijunction at OCM Equipem=
ents","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active//No power issue on site ,site on Gri=
d with Ubaie=3D53.6 V The Tx FME Hosiah//674 007438 Notice that we have dij=
unction at OCM Equipements","vanel.mbiada@matech-cameroun.com","128","28-04=
-2025 14:55:06","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004903922","N=
koabang Ebolmedjock","","28-04-2025 14:40:53","28-04-2025 14:09:21","28-04-=
2025 14:15:33","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matec=
h-cameroun.com","1893","28-04-2025 14:40:53","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004903693","Beh=
ind P T school Yde","","28-04-2025 14:05:23","28-04-2025 12:44:10","28-04-2=
025 15:12:58","Site went down because Gen failed to start due to Charger al=
ternator  faulty//He connected to the static  charger and manually started =
the Gen ","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Cha=
rging Alternator","Site went down because Gen failed to start due to Charge=
r alternator  faulty//He connected to the static  charger and manually star=
ted the Gen ","edwige.kapawo@matech-cameroun.com","4874","28-04-2025 14:05:=
23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004903669","Akono","=
","28-04-2025 14:02:39","28-04-2025 13:56:59","28-04-2025 14:03:30","Cascad=
ed Incident from TTO5018844","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue, Site impacted by Ngoumou","sys=
tem","266818","28-04-2025 14:02:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004903668","Minka","=
","28-04-2025 14:02:39","28-04-2025 13:56:59","28-04-2025 14:03:30","Cascad=
ed Incident from TTO5018844","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue, Site impacted by Ngoumou","sys=
tem","266818","28-04-2025 14:02:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004903667","OTELE MT=
N","","28-04-2025 14:02:39","28-04-2025 13:56:59","28-04-2025 14:03:30","Ca=
scaded Incident from TTO5018844","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue, Site impacted by Ngoumou",=
"system","266817","28-04-2025 14:02:39","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004903650","Mom=
","IHS_YND_531, IHS_YND_371, IHS_YND_365","28-04-2025 14:00:54","28-04-2025=
 13:56:59","28-04-2025 14:03:30","No power issue, Site impacted by Ngoumou"=
,"Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fail=
ure","Affected by 3rd Party Site","No power issue, Site impacted by Ngoumou=
","edwige.kapawo@matech-cameroun.com","237","28-04-2025 14:00:54","MATECH C=
MR"
"Closed Complete","Site Down","CTR_447","IHS_YND_061","NOCINC0004903574","Y=
de University","","28-04-2025 13:44:48","28-04-2025 13:35:35","28-04-2025 1=
3:48:29","Active// No power Issue Site on Grid Ubai =3D53,6 V, The TX FME M=
bah Hosiah (674007438) is informed, Notice that we have disjunction at BTS =
OCM","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active// No power Issue Site on Grid Ubai =
=3D53,6 V, The TX FME Mbah Hosiah (674007438) is informed, Notice that we h=
ave disjunction at BTS OCM","edwige.kapawo@matech-cameroun.com","553","28-0=
4-2025 13:44:48","MATECH CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0004903416","E=
mombo-Tchad","","28-04-2025 13:19:22","28-04-2025 13:17:18","28-04-2025 13:=
20:16","Grid outage//Grid return","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid outage//Grid return","edwige.kapawo@mate=
ch-cameroun.com","125","28-04-2025 13:19:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004903154","MEHANDAN=
","","28-04-2025 12:35:39","28-04-2025 12:33:59","28-04-2025 12:37:58","Cas=
caded Incident from TTO5018270","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,site went down because Ge=
n failed to start due to ATS and Gen card faulty // grid returned","system"=
,"264659","28-04-2025 12:35:39","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004903152","Odz=
a II OCM","IHS_YND_528","28-04-2025 12:34:57","28-04-2025 12:33:59","28-04-=
2025 12:37:58","Grid outage ,site went down because Gen failed to start due=
 to ATS and Gen card faulty // grid returned","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went d=
own because Gen failed to start due to ATS and Gen card faulty // grid retu=
rned","edwige.kapawo@matech-cameroun.com","60","28-04-2025 12:34:57","MATEC=
H CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004902945","Men=
dong NB","","28-04-2025 12:17:38","28-04-2025 12:08:59","28-04-2025 17:41:0=
5","Grid outage, no space to deploy MDG //Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage, no space to=
 deploy MDG //Grid return","edwige.kapawo@matech-cameroun.com","520","28-04=
-2025 12:17:38","MATECH CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0004902655","Ess=
os Marche","","28-04-2025 12:06:41","28-04-2025 11:59:59","28-04-2025 12:33=
:47","Active// No power issue, Ubaie: 52.5 V Site on Grid The TX FME Armand=
 (691144412) from Huawei is informed","Delor Telezing","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
 No power issue, Ubaie: 52.5 V Site on Grid The TX FME Armand (691144412) f=
rom Huawei is informed","edwige.kapawo@matech-cameroun.com","403","28-04-20=
25 12:06:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004902645","Emana Ly=
cee","","28-04-2025 12:06:14","28-04-2025 12:00:18","28-04-2025 12:21:33","=
Cascaded Incident from TTO5017689","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down due t=
o poor backup// Grid return","system","266656","28-04-2025 12:06:14","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004902592","E=
mana lycee 2","IHS_YND_274","28-04-2025 12:03:25","28-04-2025 12:00:18","28=
-04-2025 12:21:33","Grid outage, Site went down due to poor backup// Grid r=
eturn","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, Site went down due to poor backup// =
Grid return","edwige.kapawo@matech-cameroun.com","188","28-04-2025 12:03:25=
","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004902577","M=
essassi 2","","28-04-2025 12:01:27","28-04-2025 11:57:06","28-04-2025 12:25=
:04","Grid fluctuations, Site went down due to poor backup// Grid return","=
Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Battery Low","Grid fluctuations, Site went down due to poor backup// Gr=
id return","edwige.kapawo@matech-cameroun.com","264","28-04-2025 12:01:27",=
"MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004902542","Nko=
londom","","28-04-2025 11:57:19","28-04-2025 11:51:13","28-04-2025 12:48:51=
","Site went Down due to Grid bad voltage // Bypassed grid and started the =
gen","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Site went Down due to Grid bad voltage // Bypassed gr=
id and started the gen","edwige.kapawo@matech-cameroun.com","393","28-04-20=
25 11:57:19","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004902437","Efo=
ulan MTN","","28-04-2025 11:41:01","28-04-2025 11:38:51","28-04-2025 12:18:=
50","Gid outage gen failed to start due to kick starter issue//Gen manually=
 started","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - K=
ick Starter","Gid outage gen failed to start due to kick starter issue//Gen=
 manually started","edwige.kapawo@matech-cameroun.com","131","28-04-2025 11=
:41:01","MATECH CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004902238","Obo=
bogo","","28-04-2025 11:11:17","28-04-2025 11:01:59","28-04-2025 12:23:51",=
"Grid outage, Site went down before Gen start due to poor backup// Gen Auto=
matically Startedgen failed","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down b=
efore Gen start due to poor backup// Gen Automatically Startedgen failed","=
edwige.kapawo@matech-cameroun.com","560","28-04-2025 11:11:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004902157","Scalom-I=
HS","","28-04-2025 11:05:06","28-04-2025 10:59:59","28-04-2025 12:28:06","C=
ascaded Incident from TTO5017133","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage gen failed to start due to automation=
 malfunctionning//Gen manually started","system","270093","28-04-2025 11:05=
:06","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004902052","S=
calom","IHS_YND_505","28-04-2025 11:03:20","28-04-2025 10:59:59","28-04-202=
5 12:29:28","Grid outage gen failed to start due to automation malfunctionn=
ing//Gen manually started","Paul BIBOUM","Equipment Repair","Passive","Cont=
rol Panel","ATS-AMF Issue","Grid outage gen failed to start due to automati=
on malfunctionning//Gen manually started","edwige.kapawo@matech-cameroun.co=
m","202","28-04-2025 11:03:20","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004901901","B=
arriere","","28-04-2025 10:55:32","28-04-2025 10:46:59","28-04-2025 15:54:0=
7","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed //Grid return","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and c=
onfirmed //Grid return","edwige.kapawo@matech-cameroun.com","514","28-04-20=
25 10:55:32","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004901833","E=
ssomba","","28-04-2025 10:44:49","28-04-2025 10:42:29","28-04-2025 11:04:52=
","Site went down Because 02/05 rectifier dysfonction // He reset the recti=
fier ","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down Because 02/05 rectifier dysfonction // He reset =
the rectifier ","edwige.kapawo@matech-cameroun.com","142","28-04-2025 10:44=
:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0004901778","Hotel de=
 Ville Yde","","28-04-2025 10:39:05","28-04-2025 10:27:59","28-04-2025 11:0=
3:13","Cascaded Incident from TTO5016804","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Only, No space to deploy =
MGE //  Grid return","system","264771","28-04-2025 10:39:05","MATECH CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0004901752","N=
R-Bastos","IHS_YND_019","28-04-2025 10:36:50","28-04-2025 10:27:59","28-04-=
2025 11:03:13","Grid Only, No space to deploy MGE //  Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, N=
o space to deploy MGE //  Grid return","edwige.kapawo@matech-cameroun.com",=
"532","28-04-2025 10:36:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004901735","Song-bon=
g","","28-04-2025 10:34:33","28-04-2025 10:27:56","28-04-2025 11:19:33","Ca=
scaded Incident from TTO5016752","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage Gen failed to start due=
 gen card alarm // Gen card reset and Gen start manually","system","265014"=
,"28-04-2025 10:34:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004901734","Eseka To=
wn","","28-04-2025 10:34:33","28-04-2025 10:27:56","28-04-2025 11:19:33","C=
ascaded Incident from TTO5016752","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage Gen failed to start du=
e gen card alarm // Gen card reset and Gen start manually","system","265014=
","28-04-2025 10:34:33","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0004901706","E=
seka OCM","IHS_YND_378, IHS_YND_453","28-04-2025 10:30:09","28-04-2025 10:2=
7:56","28-04-2025 11:19:33","Grid outage Gen failed to start due gen card a=
larm // Gen card reset and Gen start manually","Kemeni Franklin","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage Gen faile=
d to start due gen card alarm // Gen card reset and Gen start manually","ed=
wige.kapawo@matech-cameroun.com","134","28-04-2025 10:30:09","MATECH CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0004901656","OKO=
A Peage","","28-04-2025 10:19:10","28-04-2025 10:13:04","28-04-2025 10:25:3=
2","Active// No power issue on site Ubaie: 55 Vsite On Gen The Tx FME Fulbe=
rt(654266068) of huawei is informed","Fanda Brice","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No =
power issue on site Ubaie: 55 Vsite On Gen The Tx FME Fulbert(654266068) of=
 huawei is informed","edwige.kapawo@matech-cameroun.com","367","28-04-2025 =
10:19:10","MATECH CMR"
"Closed Complete","Site Down","T1328","IHS_YND_247","NOCINC0004901652","Oko=
lo","","28-04-2025 10:18:22","28-04-2025 10:16:59","28-04-2025 11:35:59","G=
rid outage, Site went down because Gen failed to start due to battery Gen f=
aulty// He started Gen with external battery","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, Site =
went down because Gen failed to start due to battery Gen faulty// He starte=
d Gen with external battery","edwige.kapawo@matech-cameroun.com","84","28-0=
4-2025 10:18:22","MATECH CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0004901647","M=
aison-Blanche-IHS","","28-04-2025 10:17:32","28-04-2025 10:14:25","28-04-20=
25 11:37:58","No power issue , Ubaie: 53.8 V site on Grid. The FME TX Mbah =
Hosiah (674007438) from Huawei is informed","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue ,=
 Ubaie: 53.8 V site on Grid. The FME TX Mbah Hosiah (674007438) from Huawei=
 is informed","edwige.kapawo@matech-cameroun.com","188","28-04-2025 10:17:3=
2","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004901480","Mok=
olo Yaounde","","28-04-2025 09:44:41","28-04-2025 09:41:49","28-04-2025 13:=
02:13","site went down due to insufficient of rectifier on site  SS  IHS Be=
rnard is informed// site stabilized","","Equipment Repair","Passive","Recti=
fier","Rectifier Module","site went down due to insufficient of rectifier o=
n site  SS  IHS Bernard is informed// site stabilized","edwige.kapawo@matec=
h-cameroun.com","173","28-04-2025 09:44:41","MATECH CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004901310","Awa=
e Escalier","","28-04-2025 09:14:50","28-04-2025 09:10:59","28-04-2025 09:4=
6:37","Grid outage, Site went down because Gen failed to start due to alarm=
""low oil pressure""//He added oil and Gen started","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage, Si=
te went down because Gen failed to start due to alarm""low oil pressure""//=
He added oil and Gen started","edwige.kapawo@matech-cameroun.com","232","28=
-04-2025 09:14:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004900958","Omnispor=
t-Rail","","28-04-2025 08:01:50","28-04-2025 07:37:59","28-04-2025 17:09:40=
","Cascaded Incident from TTO5015788","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and confi=
rmed// He reduced the load","system","339781","28-04-2025 08:01:50","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004900849","M=
ANGUIERS CHAPELLE","IHS_YND_506","28-04-2025 07:46:31","28-04-2025 07:37:59=
","28-04-2025 20:37:59"," eneo meter burn, gen overload (22kva, 340A) SS HI=
S Bernard ATANGANA is informed and confirmed","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down=
 due to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and c=
onfirmed// He reduced the load","edwige.kapawo@matech-cameroun.com","514","=
28-04-2025 07:46:31","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004900797","Nom=
ayos montee Meche","","28-04-2025 07:29:00","28-04-2025 07:27:47","28-04-20=
25 07:32:10","ACTIVE//No power issue on site GRID , Ubaie: 53V site On Grid=
 The Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","ACTIVE//No power issue on site GRID , Ubaie: 53V site On Grid The Tx=
 FME Fulbert(654266068) from Huawei is informed","edwige.kapawo@matech-came=
roun.com","74","28-04-2025 07:29:00","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004900741","B=
arriere","","28-04-2025 07:11:29","28-04-2025 06:15:16","28-04-2025 09:25:3=
6","Grid outage, Site down due to Gen overload(20kva,400 A) IHS SS Felix Za=
mbe is informed and confirmed // Grid returned","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site down due=
 to Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and confirmed =
// Grid returned","loic.noumsi@matech-cameroun.com","3374","28-04-2025 07:1=
1:29","MATECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004900665","Emo=
mbo Esssomba","","28-04-2025 06:58:43","28-04-2025 06:49:36","28-04-2025 08=
:22:09","Grid fluctuation, site went down because  due to grid bad voltage =
No crcp // He bypassed the grid and started Gen manually","Mba Lazare Herve=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation, site went down because  due to grid bad voltage No crcp =
// He bypassed the grid and started Gen manually","loic.noumsi@matech-camer=
oun.com","547","28-04-2025 06:58:43","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004900506","M=
bankomo IHS","","28-04-2025 06:13:22","28-04-2025 06:08:14","28-04-2025 06:=
41:30","Grid outage.gen failed to start due to card Ge faulty // He reseted=
 card GE and gen manually started","Fanda Brice","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to start due t=
o card Ge faulty // He reseted card GE and gen manually started","loic.noum=
si@matech-cameroun.com","308","28-04-2025 06:13:22","MATECH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0004900464","Lob=
o 2","","28-04-2025 05:53:41","28-04-2025 05:50:03","28-04-2025 08:12:01","=
Site went down due to 02/05 rectifier dysfonction // He replaced 02 rectifi=
ers ","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to 02/05 rectifier dysfonction // He =
replaced 02 rectifiers ","loic.noumsi@matech-cameroun.com","219","28-04-202=
5 05:53:41","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004899613","Elo=
umdem stade","","28-04-2025 00:50:01","28-04-2025 00:46:41","28-04-2025 02:=
17:22","Site went down because gen failed to start due to grid bad voltage =
// He bypassed grid and manually started the gen","Fanda Brice","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Site went do=
wn because gen failed to start due to grid bad voltage // He bypassed grid =
and manually started the gen","gaelle.njiofack@matech-cameroun.com","201","=
28-04-2025 00:50:01","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004899593","OBA=
M NGOLA OCM","","28-04-2025 00:45:11","28-04-2025 00:20:59","28-04-2025 01:=
17:59","Site went down due to disjuntion of Rectifier Circuit Breaker // Re=
ctifier Circuit breaker rearm","MINKA NICOLAS","Equipment Repair","Passive"=
,"Rectifier","Rectifier - Circuit Breaker","Site went down due to disjuntio=
n of Rectifier Circuit Breaker // Rectifier Circuit breaker rearm","loic.no=
umsi@matech-cameroun.com","1453","28-04-2025 00:45:11","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004899525","Jou=
vence Mbenda","","28-04-2025 00:16:40","28-04-2025 00:07:26","28-04-2025 00=
:17:49","No power issue on site Ubay 54V site on Gen, site up without inter=
vention","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site Ubay 54V site =
on Gen, site up without intervention","gaelle.njiofack@matech-cameroun.com"=
,"555","28-04-2025 00:16:40","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004899498","Nom=
ayos montee Meche","","28-04-2025 00:01:24","27-04-2025 23:58:02","28-04-20=
25 00:32:35","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On G=
rid The Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On Grid =
The Tx FME Fulbert(654266068) from Huawei is informed","gaelle.njiofack@mat=
ech-cameroun.com","203","28-04-2025 00:01:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004899459","Omnispor=
t-Rail","","27-04-2025 23:47:20","27-04-2025 22:34:27","28-04-2025 07:08:34=
","Cascaded Incident from TTO5014195","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and confi=
rmed// He reduced the load","system","293175","27-04-2025 23:47:20","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004899455","M=
ANGUIERS CHAPELLE","IHS_YND_506","27-04-2025 23:46:39","27-04-2025 22:34:27=
","28-04-2025 07:08:34","Grid outage, site went down due to gen overload (2=
2kva, 340A) SS HISBernard ATANGANA is informed and confirmed// He reduced t=
he load","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, site went down due to gen overload (22kva, 340A) SS=
 HISBernard ATANGANA is informed and confirmed// He reduced the load","loic=
.noumsi@matech-cameroun.com","4333","27-04-2025 23:46:39","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004899359","B=
arriere","","27-04-2025 23:16:35","27-04-2025 23:00:19","28-04-2025 06:07:5=
3","Grid outage, Site down due to Gen overload(20kva,400 A) IHS SS Felix Za=
mbe is informed and confirmed // Grid returned","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site down due=
 to Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and confirmed =
// Grid returned","franck.nkomot@matech-cameroun.com","977","27-04-2025 23:=
16:35","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004899319","M=
efou-Assi","IHS_YND_537, IHS_YND_520","27-04-2025 23:07:46","27-04-2025 22:=
35:33","27-04-2025 23:33:02","Grid outage, site went down because gen fails=
 to start due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed /=
/ He reduice the load","Fanda Brice","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid outage, site went down because gen fails to start=
 due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // He redu=
ice the load","franck.nkomot@matech-cameroun.com","1934","27-04-2025 23:07:=
46","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004899309","S=
IMBOCK BONAMBAPE","","27-04-2025 23:04:24","27-04-2025 22:35:33","27-04-202=
5 23:33:02","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Grid outage, site went down because gen fails to start=
 due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // He redu=
ice the load","franck.nkomot@matech-cameroun.com","272167","27-04-2025 23:0=
4:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0004899298","BIYEMASS=
I NIKI","","27-04-2025 23:01:16","27-04-2025 20:28:43","28-04-2025 09:59:52=
","Cascaded Incident from TTO5013371","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid only site.no space to depl=
oy mobile gen // grid power restored","system","315424","27-04-2025 23:01:1=
6","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004899263","M=
EFOU ASSI","","27-04-2025 22:57:04","27-04-2025 22:35:33","27-04-2025 23:33=
:02","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, site went down because gen fails to start due to ge=
n overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // He reduice the lo=
ad","franck.nkomot@matech-cameroun.com","272167","27-04-2025 22:57:04","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004899242","OLAMA","=
","27-04-2025 22:52:46","27-04-2025 22:41:20","28-04-2025 01:14:06","Cascad=
ed Incident from TTO5013905","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by NGOUMOU that IHS does not man=
age","system","271840","27-04-2025 22:52:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004899244","Minka","=
","27-04-2025 22:52:46","27-04-2025 22:41:20","28-04-2025 01:14:06","Cascad=
ed Incident from TTO5013905","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by NGOUMOU that IHS does not man=
age","system","271840","27-04-2025 22:52:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004899243","OTELE MT=
N","","27-04-2025 22:52:46","27-04-2025 22:41:20","28-04-2025 01:14:06","Ca=
scaded Incident from TTO5013905","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by NGOUMOU that IHS does not=
 manage","system","271841","27-04-2025 22:52:46","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004899225","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371","27-04-2025 22:48:37","27-04-20=
25 22:41:20","28-04-2025 01:14:06","Site impacted by NGOUMOU that IHS does =
not manage","Fanda Brice","Customer Equipment Failure","Active","Active Equ=
ipment Failure","Affected by 3rd Party Site","Site impacted by NGOUMOU that=
 IHS does not manage","franck.nkomot@matech-cameroun.com","437","27-04-2025=
 22:48:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0004899139","Tamtam W=
eekend","","27-04-2025 22:20:54","27-04-2025 20:28:43","28-04-2025 09:59:52=
","Cascaded Incident from TTO5013371","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid only site.no space to depl=
oy mobile gen // grid power restored","system","315426","27-04-2025 22:20:5=
4","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0004899141","Montee-J=
ouvence-II","","27-04-2025 22:20:54","27-04-2025 20:28:43","28-04-2025 09:5=
9:52","Cascaded Incident from TTO5013371","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid only site.no space to =
deploy mobile gen // grid power restored","system","315425","27-04-2025 22:=
20:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004899140","Biyemass=
i LAC","","27-04-2025 22:20:54","27-04-2025 20:28:43","28-04-2025 09:59:52"=
,"Cascaded Incident from TTO5013371","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid only site.no space to deploy mobile gen /=
/ grid power restored","system","315426","27-04-2025 22:20:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0004899138","Damas","=
","27-04-2025 22:20:54","27-04-2025 20:28:43","28-04-2025 09:59:52","Cascad=
ed Incident from TTO5013371","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid only site.no space to deploy mobile =
gen // grid power restored","system","315427","27-04-2025 22:20:54","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004899137","Accacia =
New","","27-04-2025 22:20:53","27-04-2025 20:28:43","28-04-2025 09:59:52","=
Cascaded Incident from TTO5013371","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid only site.no space to deploy mobile gen // =
grid power restored","system","315425","27-04-2025 22:20:53","MATECH CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004899109","Cha=
rles-Atangana","","27-04-2025 22:12:32","27-04-2025 22:05:00","27-04-2025 2=
2:19:00","Grid outage // Grid return","","Grid Supply","Passive","Grid","Na=
tional Grid - Grid Outage Issue","Grid outage // Grid return","franck.nkomo=
t@matech-cameroun.com","454","27-04-2025 22:12:32","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004899026","OBA=
M NGOLA OCM","","27-04-2025 21:49:15","27-04-2025 21:36:53","27-04-2025 22:=
40:41","Grid outage, Site went down Gen failed to start due to Grid bad vol=
tage(lack of 01 phase on site)// He did a bridge on the Good phase","MINKA =
NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid outage, Site went down Gen failed to start due to Grid bad vol=
tage(lack of 01 phase on site)// He did a bridge on the Good phase","franck=
.nkomot@matech-cameroun.com","743","27-04-2025 21:49:15","MATECH CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0004898781","R=
d-Pt-Express","IHS_YND_562, IHS_YND_724, IHS_YND_166, IHS_YND_151, IHS_YND_=
546, IHS_YND_518","27-04-2025 20:58:52","27-04-2025 20:28:43","28-04-2025 0=
9:59:52","Grid only site.no space to deploy mobile gen // grid power restor=
ed","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid only site.no space to deploy mobile gen // grid power restored","franc=
k.nkomot@matech-cameroun.com","1809","27-04-2025 20:58:52","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004898701","M=
essassi 2","","27-04-2025 20:49:18","27-04-2025 20:39:46","27-04-2025 21:24=
:17","Site went down due to rectifier issues // Grid stabilised","Fabrice P=
ouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site w=
ent down due to rectifier issues // Grid stabilised","cedric.tiani@matech-c=
ameroun.com","574","27-04-2025 20:49:18","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004898692","Nko=
ulou Carriere carrefourt","","27-04-2025 20:48:49","27-04-2025 20:46:53","2=
7-04-2025 21:54:53","Grid outage,site went down because Gen failed due to G=
rid bad voltage//He bypassed the Grid and site on GEN","Mba Lazare Herve","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id outage,site went down because Gen failed due to Grid bad voltage//He byp=
assed the Grid and site on GEN","franck.nkomot@matech-cameroun.com","117","=
27-04-2025 20:48:49","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004898669","S=
IMBOCK BONAMBAPE","","27-04-2025 20:43:57","27-04-2025 20:37:42","27-04-202=
5 21:25:42","Grid outage, Site went down because Gen Overload (20kva, 350A)=
 SS IHS Felix ZAMBE confirmed// He reduiced load and started Gen manualy","=
Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage, Site went down because Gen Overload (20kva, 350A) SS IHS Felix=
 ZAMBE confirmed// He reduiced load and started Gen manualy","cedric.tiani@=
matech-cameroun.com","376","27-04-2025 20:43:57","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004898649","Jou=
vence Mbenda","","27-04-2025 20:40:18","27-04-2025 20:05:11","27-04-2025 21=
:00:11","Grid outage site went down because Gen stopped with alarm HIGH tem=
p // He added water Gen manually started","Hyemafo Gildas","Equipment Repai=
r","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gr=
id outage site went down because Gen stopped with alarm HIGH temp // He add=
ed water Gen manually started","franck.nkomot@matech-cameroun.com","2108","=
27-04-2025 20:40:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004898617","Akono","=
","27-04-2025 20:33:45","27-04-2025 20:29:05","27-04-2025 20:34:05","Cascad=
ed Incident from TTO5013170","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by Ngoumou (not managing by IHS)=
","system","264701","27-04-2025 20:33:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004898615","OLAMA","=
","27-04-2025 20:33:44","27-04-2025 20:29:05","27-04-2025 20:34:05","Cascad=
ed Incident from TTO5013170","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by Ngoumou (not managing by IHS)=
","system","264701","27-04-2025 20:33:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0004898616","Obobogo"=
,"","27-04-2025 20:33:44","27-04-2025 20:29:05","27-04-2025 20:34:05","Casc=
aded Incident from TTO5013170","MINKA NICOLAS","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by Ngoumou (not managing by =
IHS)","system","264701","27-04-2025 20:33:44","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004898608","OTE=
LE MTN","IHS_YND_687, IHS_YND_155, IHS_YND_371, IHS_YND_370, IHS_YND_365","=
27-04-2025 20:32:14","27-04-2025 20:29:05","27-04-2025 20:34:05","Site impa=
cted by Ngoumou (not managing by IHS)","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","Affected by 3rd Party Site","Si=
te impacted by Ngoumou (not managing by IHS)","franck.nkomot@matech-camerou=
n.com","190","27-04-2025 20:32:14","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004898585","Mom=
","","27-04-2025 20:30:39","27-04-2025 20:29:05","27-04-2025 20:34:05","","=
Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active","S=
ite impacted by Ngoumou (not managing by IHS)","franck.nkomot@matech-camero=
un.com","264702","27-04-2025 20:30:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004898378","Omnispor=
t-Rail","","27-04-2025 19:59:52","27-04-2025 19:49:59","27-04-2025 20:50:40=
","Cascaded Incident from TTO5012905","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and confi=
rmed// He reduced the load","system","267089","27-04-2025 19:59:52","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004898376","M=
ANGUIERS CHAPELLE","IHS_YND_506","27-04-2025 19:59:20","27-04-2025 19:49:59=
","27-04-2025 20:50:40","Grid outage, site went down due to gen overload (2=
2kva, 340A) SS HISBernard ATANGANA is informed and confirmed// He reduced t=
he load","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, site went down due to gen overload (22kva, 340A) SS=
 HISBernard ATANGANA is informed and confirmed// He reduced the load","kouo=
h.jean@ihstowers.com","562","27-04-2025 19:59:20","MATECH CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0004898265","E=
mombo-Tchad","","27-04-2025 19:41:20","27-04-2025 19:32:59","28-04-2025 12:=
34:59","Grid outage, no space to deploy MGE // grid power return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
no space to deploy MGE // grid power return","cedric.tiani@matech-cameroun.=
com","502","27-04-2025 19:41:20","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004898258","E=
kombitie","","27-04-2025 19:40:45","27-04-2025 19:38:38","27-04-2025 19:50:=
25","Active: no power issue, site is on Gen with Ubaie=3D54.5V, Symphorien(=
650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue, site is on Gen with Ubaie=3D54.5V, Symphorien(650257151/ huawei)=
 is informed","cedric.tiani@matech-cameroun.com","129","27-04-2025 19:40:45=
","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004898129","E=
vodoula OCM","","27-04-2025 19:11:55","27-04-2025 19:01:45","27-04-2025 23:=
22:46",",gen failed to start due to grid bad voltage,no RCP//he bypassed th=
e Grid and site on Gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive",=
"Grid","National Grid - Unstable Grid Supply Issue",",gen failed to start d=
ue to grid bad voltage,no RCP//he bypassed the Grid and site on Gen","franc=
k.nkomot@matech-cameroun.com","610","27-04-2025 19:11:55","MATECH CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004898002","SOA=
 UNIVERSITY STADIUM","","27-04-2025 18:41:08","27-04-2025 18:41:03","27-04-=
2025 19:28:39"," Grid outage, site went down because Gen failed to start du=
e to gen card faulty // Grid return","Siligap Boris","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel"," Grid outage, site went down beca=
use Gen failed to start due to gen card faulty // Grid return","franck.nkom=
ot@matech-cameroun.com","6","27-04-2025 18:41:08","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004897782","B=
arriere","","27-04-2025 18:06:23","27-04-2025 17:37:15","27-04-2025 19:55:3=
5","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // Grid return","Hyemafo Gildas","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went=
 down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and =
confirmed // Grid return","kouoh.jean@ihstowers.com","1749","27-04-2025 18:=
06:23","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004897764","B=
arriere","","27-04-2025 18:04:49","26-04-2025 20:58:49","27-04-2025 17:22:3=
6","","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS=
 Felix Zambe is informed and confirmed //Grid return","kouoh.jean@ihstowers=
.com","75961","27-04-2025 18:04:49","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004897727","S=
IMBOCK BONAMBAPE","","27-04-2025 17:56:57","27-04-2025 14:05:52","27-04-202=
5 17:17:32","Grid outage gen failed to start due to alarm ''high temp''//We=
 remove thermosthat  and gen manually started","Hyemafo Gildas","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid outage gen failed=
 to start due to alarm ''high temp''//We remove thermosthat  and gen manual=
ly started","kouoh.jean@ihstowers.com","287818","27-04-2025 17:56:57","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004897676","S=
OA TOWN","","27-04-2025 17:45:10","27-04-2025 17:38:02","27-04-2025 18:10:5=
1","Grid outage site went down due to Generator phase terminal block that a=
liment rectifiers   is faulty //He replaced and manually started the Gen","=
Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage site went down due to Generator phase terminal block that a=
liment rectifiers   is faulty //He replaced and manually started the Gen","=
kouoh.jean@ihstowers.com","429","27-04-2025 17:45:10","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004897612","Eke=
kam","","27-04-2025 17:31:01","27-04-2025 17:29:39","27-04-2025 17:33:42","=
Grid outage site went down because Gen stopped with alarm HIGH temp due to =
Radiator pierced // He added water manually start of Gen","TIENTCHEU NZETCH=
IEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Grid outage site went down because Gen stopped with=
 alarm HIGH temp due to Radiator pierced // He added water manually start o=
f Gen","franck.nkomot@matech-cameroun.com","83","27-04-2025 17:31:01","MATE=
CH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0004897583","EKI=
E","","27-04-2025 17:24:24","27-04-2025 17:15:17","27-04-2025 18:15:17","Si=
te went down because CB of rectifier tripped causing by Grid Overvoltage// =
CB of rectifier put back on","Albran Byorel","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Site went down because CB of rectifier tr=
ipped causing by Grid Overvoltage// CB of rectifier put back on","franck.nk=
omot@matech-cameroun.com","547","27-04-2025 17:24:24","MATECH CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0004897549","NYA=
NON/DEMBO","","27-04-2025 17:21:16","27-04-2025 16:49:09","27-04-2025 17:53=
:46","Site went down because Gen stopped with alarm high temperature// He a=
dded water in radiator and manually started the Gen","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Site went down because Gen stopped with alarm high tempe=
rature// He added water in radiator and manually started the Gen","olivier.=
kwedi@ihstowers.com","1928","27-04-2025 17:21:16","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004897437","E=
vodoula OCM","","27-04-2025 17:11:55","27-04-2025 16:48:33","27-04-2025 18:=
01:03","Grid Outage, site went down because Gen stopped with ""low oil pres=
sure"" alarm // He added oil and started Gen manualy","TIENTCHEU NZETCHIEU =
GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Gr=
id Outage, site went down because Gen stopped with ""low oil pressure"" ala=
rm // He added oil and started Gen manualy","cedric.tiani@matech-cameroun.c=
om","1403","27-04-2025 17:11:55","MATECH CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0004897326","O=
lezoa OCM","","27-04-2025 16:48:49","27-04-2025 16:15:41","30-04-2025 16:26=
:38","Grid outage.no space to deploy mobile gen //Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no s=
pace to deploy mobile gen //Grid return","kouoh.jean@ihstowers.com","1989",=
"27-04-2025 16:48:49","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0004897280","Ngo=
usso-Savana","","27-04-2025 16:37:13","27-04-2025 16:28:00","27-04-2025 17:=
00:15","Grid fluctuation,site went down because Gen failed to start due gri=
d bad voltage//He bypassed the Grid and site on Gen","Siligap Boris","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation,site went down because Gen failed to start due grid bad voltage//=
He bypassed the Grid and site on Gen","cedric.tiani@matech-cameroun.com","5=
54","27-04-2025 16:37:13","MATECH CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004897272","Bon=
djock","","27-04-2025 16:34:58","27-04-2025 16:27:40","27-04-2025 18:15:40"=
,"Grid outage; site went down because Gen started and stopped with alarm ""=
high temperature"" // He added water and Gen manually started","Fanda Brice=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid outage; site went down because Gen started and stopped=
 with alarm ""high temperature"" // He added water and Gen manually started=
","cedric.tiani@matech-cameroun.com","439","27-04-2025 16:34:58","MATECH CM=
R"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004897256","D=
amas","","27-04-2025 16:32:34","27-04-2025 15:19:55","27-04-2025 16:55:40",=
"","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid only site.no space to deploy mobile gen // grid power restored=
","cedric.tiani@matech-cameroun.com","283274","27-04-2025 16:32:34","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0004897131","R=
d-Pt-Express","IHS_YND_166, IHS_YND_518","27-04-2025 16:10:04","27-04-2025 =
15:19:55","27-04-2025 16:55:40","Grid only site.no space to deploy mobile g=
en // grid power restored","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","Grid only site.no space to deploy mobile gen // grid=
 power restored","kouoh.jean@ihstowers.com","3010","27-04-2025 16:10:04","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004897129","T=
amtam Weekend","","27-04-2025 16:09:29","27-04-2025 15:17:18","27-04-2025 1=
5:30:58","Active: No power issue site on Grid with U=3D51,9V The TX FME Mba=
h Hosiah (674007438) FROM Huawei is informed","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active: No power issue site on Grid with U=3D51,9V The TX FME Mbah Hosiah (=
674007438) FROM Huawei is informed","kouoh.jean@ihstowers.com","3132","27-0=
4-2025 16:09:29","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004897088","M=
ontee-Jouvence-II","","27-04-2025 16:02:01","27-04-2025 15:19:55","27-04-20=
25 16:55:40","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid only site.no space to deploy mobile gen // grid =
power restored","kouoh.jean@ihstowers.com","283274","27-04-2025 16:02:01","=
MATECH CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0004897029","E=
mombo-Tchad","","27-04-2025 15:51:52","27-04-2025 15:44:32","27-04-2025 18:=
17:40","Grid outage,No space to deploy a mobil gen //grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,N=
o space to deploy a mobil gen //grid return","cedric.tiani@matech-cameroun.=
com","441","27-04-2025 15:51:52","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004896929","Ron=
d Point Express1114","","27-04-2025 15:35:29","27-04-2025 15:29:45","27-04-=
2025 16:01:11","Grid outage, Site down due to poor battery backup // Gen st=
art automatically","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site down due to poor bat=
tery backup // Gen start automatically","cedric.tiani@matech-cameroun.com",=
"345","27-04-2025 15:35:29","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004896787","Men=
dong3","","27-04-2025 15:06:28","27-04-2025 15:01:10","28-04-2025 00:15:33"=
,"Grid outage.nospace to deploy mobile gen // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage.nospace =
to deploy mobile gen // Grid return","vanel.mbiada@matech-cameroun.com","31=
9","27-04-2025 15:06:28","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004896689","H=
-Paradis","","27-04-2025 14:41:04","27-04-2025 14:19:57","27-04-2025 14:53:=
17",":Grid outage//Grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue",":Grid outage//Grid return","edwige.kapawo@matec=
h-cameroun.com","1268","27-04-2025 14:41:04","MATECH CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004896602","Crf=
-Nsam","","27-04-2025 14:31:43","27-04-2025 14:29:52","27-04-2025 15:39:35"=
,"Grid outage gen failed to start due to alarm ''overcurrent'//We reset car=
d GE and gen manually started","MINKA NICOLAS","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage gen failed to start due to =
alarm ''overcurrent'//We reset card GE and gen manually started","vanel.mbi=
ada@matech-cameroun.com","112","27-04-2025 14:31:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004896355","Afanoya"=
,"","27-04-2025 14:04:40","27-04-2025 13:44:59","27-04-2025 17:00:45","","H=
yemafo Gildas","Cascade Outage","Active","Cascade Active","Cascade Active",=
"ACTIVE //No power issue U=3D 54,6v Site on Grid The Tx Fme Georges /697466=
1814 from huawei is informed.Noticed dijunction at  ocm ","joelle.ekessi@ih=
stowers.com","274856","27-04-2025 14:04:40","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004896235","M=
eyo","IHS_YND_257, IHS_YND_313","27-04-2025 13:54:20","27-04-2025 13:44:59"=
,"27-04-2025 17:00:45","ACTIVE //No power issue U=3D 54,6v Site on Grid The=
 Tx Fme Georges /6974661814 from huawei is informed.Noticed dijunction at  =
ocm ","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","ACTIVE //No power issue U=3D 54,6v Site =
on Grid The Tx Fme Georges /6974661814 from huawei is informed.Noticed diju=
nction at  ocm ","edwige.kapawo@matech-cameroun.com","561","27-04-2025 13:5=
4:20","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0004896215","A=
hala","","27-04-2025 13:49:59","27-04-2025 13:44:59","27-04-2025 17:00:45",=
"","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","Cascade Act=
ive","ACTIVE //No power issue U=3D 54,6v Site on Grid The Tx Fme Georges /6=
974661814 from huawei is informed.Noticed dijunction at  ocm ","edwige.kapa=
wo@matech-cameroun.com","274856","27-04-2025 13:49:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004896160","Song-bon=
g","","27-04-2025 13:40:56","27-04-2025 13:18:59","27-04-2025 13:39:58","Ca=
scaded Incident from TTO5010291","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage Gen failed to start due=
 gen card alarm // Gen card reset and Gen start manually","system","290675"=
,"27-04-2025 13:40:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004896159","Eseka To=
wn","","27-04-2025 13:40:56","27-04-2025 13:18:59","27-04-2025 13:39:58","C=
ascaded Incident from TTO5010291","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage Gen failed to start du=
e gen card alarm // Gen card reset and Gen start manually","system","290674=
","27-04-2025 13:40:56","MATECH CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0004896153","Men=
dong Maeture","","27-04-2025 13:39:22","27-04-2025 13:34:14","27-04-2025 14=
:36:30","Grid outage.gen failed to start due to gen overload(20Kva,250A)//W=
e reduce load and gen manually started","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage.gen failed to start du=
e to gen overload(20Kva,250A)//We reduce load and gen manually started","va=
nel.mbiada@matech-cameroun.com","309","27-04-2025 13:39:22","MATECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004896147","Emo=
mbo Esssomba","","27-04-2025 13:38:37","27-04-2025 13:34:26","27-04-2025 16=
:08:35","Grid fluctuation, Site went down because gen fails to start due to=
 grid bad voltage,no rcp// He bypassed the Grid and site on Gen","Mba Lazar=
e Herve","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation, Site went down because gen fails to start due to =
grid bad voltage,no rcp// He bypassed the Grid and site on Gen","vanel.mbia=
da@matech-cameroun.com","251","27-04-2025 13:38:37","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004896144","M=
efou-Assi","IHS_YND_520","27-04-2025 13:37:58","27-04-2025 13:05:52","27-04=
-2025 17:17:25",":Grid outage gen failed to start due to alarm ''overcurren=
t'//We reset card GE and gen manually started","Fanda Brice","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel",":Grid outage gen failed t=
o start due to alarm ''overcurrent'//We reset card GE and gen manually star=
ted","edwige.kapawo@matech-cameroun.com","1927","27-04-2025 13:37:58","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0004896111","E=
seka OCM","IHS_YND_378, IHS_YND_453","27-04-2025 13:28:57","27-04-2025 13:1=
8:59","27-04-2025 14:17:58","Grid outage Gen failed to start due gen card a=
larm // Gen card reset and Gen start manually","Kemeni Franklin","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage Gen faile=
d to start due gen card alarm // Gen card reset and Gen start manually","ed=
wige.kapawo@matech-cameroun.com","599","27-04-2025 13:28:57","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004896011","Men=
dong vallee","","27-04-2025 13:13:28","27-04-2025 12:50:09","28-04-2025 00:=
44:24","Grid outage site went down because Gen over load (20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed // Grid returned","Fanda Brice","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down beca=
use Gen over load (20KVA; 300A) IHS F=E9lix Zamb=E9 is informed // Grid ret=
urned","vanel.mbiada@matech-cameroun.com","1400","27-04-2025 13:13:28","MAT=
ECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004896002","Mfo=
u EPC","","27-04-2025 13:10:48","27-04-2025 13:08:25","27-04-2025 13:28:07"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen Aut=
omatically Started","Mba Lazare Herve","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage, Site went down before Gen start du=
e to poor backup// Gen Automatically Started","vanel.mbiada@matech-cameroun=
.com","144","27-04-2025 13:10:48","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004895936","O=
dza II OCM","","27-04-2025 12:55:26","27-04-2025 12:46:59","27-04-2025 12:5=
5:12","Grid outage ,site went down because Gen failed to start due to ATS a=
nd Gen card faulty // grid returned","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went down becau=
se Gen failed to start due to ATS and Gen card faulty // grid returned","ed=
wige.kapawo@matech-cameroun.com","509","27-04-2025 12:55:26","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0004895900","Clu=
b France","","27-04-2025 12:47:07","27-04-2025 12:42:55","27-04-2025 16:54:=
27","Grid Only, No space to deploy MDG//Grid return","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to dep=
loy MDG//Grid return","vanel.mbiada@matech-cameroun.com","253","27-04-2025 =
12:47:07","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0004895861","A=
battoir","","27-04-2025 12:37:09","27-04-2025 12:32:00","27-04-2025 14:54:3=
9","Grid outage, Main Generator faulty // Grid return","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outag=
e, Main Generator faulty // Grid return","edwige.kapawo@matech-cameroun.com=
","310","27-04-2025 12:37:09","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004895834","Mvo=
g-Manga","","27-04-2025 12:30:12","27-04-2025 12:25:05","27-04-2025 12:32:4=
6","Active// No power issue on site. Site on Grid Ubai=3D54.3 V, The FME TX=
 Lionel Adjep/655184876/ From Huawei is informed","Albran Byorel","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power issue on site. Site on Grid Ubai=3D54.3 V, The FME TX =
Lionel Adjep/655184876/ From Huawei is informed","vanel.mbiada@matech-camer=
oun.com","309","27-04-2025 12:30:12","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004895794","Ngo=
usso Vallee","","27-04-2025 12:23:42","27-04-2025 10:32:27","27-04-2025 13:=
09:50","Grid outage, Site went down because Gen started and stopped with ""=
low oil pressure"" alarm// He reset card GE and gen manually started","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, Site went down because Gen started and stopped with ""low oil =
pressure"" alarm// He reset card GE and gen manually started","vanel.mbiada=
@matech-cameroun.com","6676","27-04-2025 12:23:42","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0004895739","S=
ous Prefecture","","27-04-2025 12:15:57","27-04-2025 12:10:45","27-04-2025 =
13:45:50","ACTIVE//No power issue site on Gen Ubaie =3D55.2V, The tx Huawei=
 Fulbert (654266068) is informed ","Fanda Brice","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No pow=
er issue site on Gen Ubaie =3D55.2V, The tx Huawei Fulbert (654266068) is i=
nformed ","edwige.kapawo@matech-cameroun.com","313","27-04-2025 12:15:57","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004895686","Mvog-Eba=
nda","","27-04-2025 12:03:19","27-04-2025 10:29:18","27-04-2025 11:44:13","=
","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive",":Grid outage gen failed to start due to alarm '' underfrequency''//W=
e reset card GE and gen manually started","joelle.ekessi@ihstowers.com","30=
7943","27-04-2025 12:03:19","MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0004895673","M=
beng","","27-04-2025 12:00:34","27-04-2025 11:49:59","27-04-2025 12:21:32",=
"Active// no power issue, site is on gen with Ubaie =3D 54.9V, The Tx FME E=
tienne 695033981 of huawei is informed","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// =
no power issue, site is on gen with Ubaie =3D 54.9V, The Tx FME Etienne 695=
033981 of huawei is informed","edwige.kapawo@matech-cameroun.com","636","27=
-04-2025 12:00:34","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004895652","SIM=
BOCK BONAMBAPE","","27-04-2025 11:55:21","27-04-2025 11:47:08","27-04-2025 =
14:00:01","Grid outage,site went down because Gen started and stop with ala=
rm High temp due to gen thermostar faulty//He replaced and site on Gen","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine T=
emp - Coolant Level Issue","Grid outage,site went down because Gen started =
and stop with alarm High temp due to gen thermostar faulty//He replaced and=
 site on Gen","vanel.mbiada@matech-cameroun.com","494","27-04-2025 11:55:21=
","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004895651","MBA=
LNGONG LYCEE","","27-04-2025 11:55:13","27-04-2025 11:48:00","27-04-2025 19=
:20:25","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, Site went down because Gen stopped due to overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed//Grid return","edwige.kapawo@matech-c=
ameroun.com","435","27-04-2025 11:55:13","MATECH CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0004895642","San=
ta Barbara Gottam","","27-04-2025 11:54:07","27-04-2025 11:49:48","27-04-20=
25 12:41:33","Grid outage gen failed to start due to alarm undervoltage//We=
 reset card GE and gen manually started","Delor Telezing","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to st=
art due to alarm undervoltage//We reset card GE and gen manually started","=
vanel.mbiada@matech-cameroun.com","260","27-04-2025 11:54:07","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004895640","Men=
dong NB","","27-04-2025 11:53:05","27-04-2025 11:37:49","27-04-2025 14:18:5=
9","Grid ooutage.no space to deploy mobile gen//Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Over Voltage","Grid ooutage.no sp=
ace to deploy mobile gen//Grid return","vanel.mbiada@matech-cameroun.com","=
916","27-04-2025 11:53:05","MATECH CMR"
"Closed Complete","Site Down","CTR_632","IHS_YND_721","NOCINC0004895618","V=
OIRIE MUNICIPALE YAOUNDE","","27-04-2025 11:47:31","27-04-2025 11:38:20","2=
7-04-2025 12:41:59","Active// No power issue on site Ubaie: 54,3 V site on =
grid, Brice Tsague (650214096) from huawei is informed","Paul BIBOUM","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue on site Ubaie: 54,3 V site on grid, Brice Ts=
ague (650214096) from huawei is informed","edwige.kapawo@matech-cameroun.co=
m","552","27-04-2025 11:47:31","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004895578","Jou=
vence Mbenda","","27-04-2025 11:37:48","27-04-2025 11:36:42","27-04-2025 12=
:01:26","Grid outage site went down because Gen stopped with alarm HIGH tem=
p  // He  added water Gen manually started","Hyemafo Gildas","Equipment Rep=
air","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","=
Grid outage site went down because Gen stopped with alarm HIGH temp  // He =
 added water Gen manually started","vanel.mbiada@matech-cameroun.com","67",=
"27-04-2025 11:37:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_121","NOCINC0004895543","Emombo-T=
chad","","27-04-2025 11:27:51","27-04-2025 11:08:13","27-04-2025 12:45:05",=
"","","Cascade Outage","Active","Cascade Active","Cascade Active","Active /=
/ No power issue site on Gen Ubaie:54.2V  Lionnel Steve (655184876/Huawei) =
is informed","joelle.ekessi@ihstowers.com","277072","27-04-2025 11:27:51","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0004895541","Kondengu=
i","IHS_YND_121","27-04-2025 11:27:17","27-04-2025 11:08:13","27-04-2025 13=
:45:05","Active // No power issue site on Gen Ubaie:54.2V  Lionnel Steve (6=
55184876/Huawei) is informed","Albran Byorel","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No powe=
r issue site on Gen Ubaie:54.2V  Lionnel Steve (655184876/Huawei) is inform=
ed","joelle.ekessi@ihstowers.com","1146","27-04-2025 11:27:17","MATECH CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0004895530","B=
otmakak","","27-04-2025 11:24:03","27-04-2025 11:21:55","27-04-2025 11:26:4=
4","Active// No power issue, Site on Gen Ubai=3D 54V, The Tx Etienne (69503=
3981/Huawei) is informed	","Kemeni Franklin","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power =
issue, Site on Gen Ubai=3D 54V, The Tx Etienne (695033981/Huawei) is inform=
ed	","edwige.kapawo@matech-cameroun.com","129","27-04-2025 11:24:03","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004895522","Scalom-I=
HS","","27-04-2025 11:22:33","27-04-2025 10:41:12","27-04-2025 16:55:22","C=
ascaded Incident from TTO5009324","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid Only, No space to deploy // Grid return","sy=
stem","292832","27-04-2025 11:22:33","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004895507","Elo=
umdem stade","","27-04-2025 11:18:56","27-04-2025 11:14:46","27-04-2025 12:=
11:11","Grid outage, Site went down before Gen start due to poor backup// G=
en Automatically Started","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen Automatically Started","vanel.mbiada@ma=
tech-cameroun.com","251","27-04-2025 11:18:56","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004895445","Tam=
tam Weekend","","27-04-2025 11:05:46","27-04-2025 10:51:35","27-04-2025 11:=
08:31","","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, site went down before Gen start du=
e to poor backup // Gen automatically started","vanel.mbiada@matech-camerou=
n.com","851","27-04-2025 11:05:46","MATECH CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0004895414","T=
ongolo OCM","","27-04-2025 11:01:30","27-04-2025 10:59:20","27-04-2025 11:2=
4:38","Site went down because Gen failed to start due to Grid bad voltage a=
nd no RCP on site // he bypass the Grid and Gen manually started","Delor Te=
lezing","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Site went down because Gen failed to start due to Grid bad voltage a=
nd no RCP on site // he bypass the Grid and Gen manually started","edwige.k=
apawo@matech-cameroun.com","132","27-04-2025 11:01:30","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004895413","Car=
refour Simbock","","27-04-2025 11:01:11","27-04-2025 10:56:01","27-04-2025 =
12:25:06","Grid outage gen failed to start due to alarm '' high temp temp''=
//We add water and gen manually started","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gri=
d outage gen failed to start due to alarm '' high temp temp''//We add water=
 and gen manually started","vanel.mbiada@matech-cameroun.com","310","27-04-=
2025 11:01:11","MATECH CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0004895406","Eto=
ug ebe Meweulo","","27-04-2025 11:00:07","27-04-2025 10:57:56","27-04-2025 =
11:17:40","Grid fluctuation site went down because Gen failed to start due =
to Grid bad voltage and RCP on site // Grid return","Hyemafo Gildas","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation site went down because Gen failed to start due to Grid bad voltag=
e and RCP on site // Grid return","vanel.mbiada@matech-cameroun.com","132",=
"27-04-2025 11:00:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004895402","ELOUMDEM=
 CARRIERE 2","","27-04-2025 10:59:16","27-04-2025 10:46:31","27-04-2025 14:=
34:56","Cascaded Incident from TTO5009363","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive",":Grid outage gen failed to st=
art due to alarm ''overcurrent'//We reset card GE and gen manually started"=
,"system","285466","27-04-2025 10:59:16","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004895400","Mon=
tee Jouvence","","27-04-2025 10:58:35","27-04-2025 10:56:49","27-04-2025 12=
:10:16","Grid outage, site went down because Gen failed to start due to Gen=
 battery faulty// He started Gen with external battery","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outa=
ge, site went down because Gen failed to start due to Gen battery faulty// =
He started Gen with external battery","vanel.mbiada@matech-cameroun.com","1=
07","27-04-2025 10:58:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0004895372","Scalom",=
"","27-04-2025 10:55:24","27-04-2025 10:46:31","27-04-2025 10:50:43","Activ=
e//No power issue on site ,site on Grid with Ubaie=3D54,5V The TX FME Mbah =
Hosiah (674007438) from Huawei is informed","Paul BIBOUM","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site ,site on Grid with Ubaie=3D54,5V The TX FME Mbah =
Hosiah (674007438) from Huawei is informed","system","533","27-04-2025 10:5=
5:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004895355","MEHANDAN=
","","27-04-2025 10:52:13","27-04-2025 10:47:45","27-04-2025 11:03:02","Cas=
caded Incident from TTO5009385","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,site went down because GE=
N failed to start due to ATS and Gen card faulty // grid returned","system"=
,"271066","27-04-2025 10:52:13","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004895350","O=
dza II OCM","IHS_YND_528","27-04-2025 10:50:53","27-04-2025 10:47:45","27-0=
4-2025 11:30:44","Grid outage ,site went down because Gen failed to start d=
ue to ATS and Gen card faulty // grid returned","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went=
 down because GEN failed to start due to ATS and Gen card faulty // grid re=
turned","edwige.kapawo@matech-cameroun.com","190","27-04-2025 10:50:53","MA=
TECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004895343","Saa=
","","27-04-2025 10:49:42","27-04-2025 10:48:30","27-04-2025 11:44:08","Gri=
d outage site went down because Gen failed to start due to Gen card faulty =
// Gen Manually Started","Parker Tchoup","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid outage site went down because Gen failed=
 to start due to Gen card faulty // Gen Manually Started","vanel.mbiada@mat=
ech-cameroun.com","73","27-04-2025 10:49:42","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004895330","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","27-04-2025 10:47:49","27-04-2025 10:46=
:31","27-04-2025 14:34:56",":Grid outage gen failed to start due to alarm '=
'overcurrent'//We reset card GE and gen manually started","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel",":Grid outage g=
en failed to start due to alarm ''overcurrent'//We reset card GE and gen ma=
nually started","vanel.mbiada@matech-cameroun.com","80","27-04-2025 10:47:4=
9","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004895322","Eto=
 koss Yde","","27-04-2025 10:46:45","27-04-2025 10:46:31","27-04-2025 14:34=
:56","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive",":Grid outage gen failed to start due to alarm ''overcurrent'//We=
 reset card GE and gen manually started","vanel.mbiada@matech-cameroun.com"=
,"285466","27-04-2025 10:46:45","MATECH CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0004895314","Biy=
emassi LAC","","27-04-2025 10:45:25","27-04-2025 10:41:10","27-04-2025 17:0=
2:06","Grid Only, No space to deploy //  Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to de=
ploy //  Grid return","vanel.mbiada@matech-cameroun.com","257","27-04-2025 =
10:45:25","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004895307","Ako=
k Ndoe Yde","","27-04-2025 10:44:39","27-04-2025 10:39:55","27-04-2025 12:4=
3:22","Grid outage, Site went down before Gen start due to poor backup// Ge=
n manually Started","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// Gen manually Started","vanel.mbiada@matech-cam=
eroun.com","285","27-04-2025 10:44:39","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004895298","A=
ccacia New","IHS_YND_505","27-04-2025 10:43:19","27-04-2025 10:41:12","27-0=
4-2025 17:00:22","Grid Only, No space to deploy // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No s=
pace to deploy // Grid return","edwige.kapawo@matech-cameroun.com","129","2=
7-04-2025 10:43:19","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004895284","E=
MANA BILICK CITY","","27-04-2025 10:40:57","27-04-2025 10:37:47","27-04-202=
5 11:19:55","Grid outage dite went down due to generator faulty//Grid retur=
m","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid outage dite went down due to generator faulty//Grid retur=
m","edwige.kapawo@matech-cameroun.com","192","27-04-2025 10:40:57","MATECH =
CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004895265","Ron=
d Point Express1114","","27-04-2025 10:39:13","27-04-2025 10:37:16","27-04-=
2025 10:45:24","Grid outage Site went down before Gen started due to poor b=
attery backup // Grid returned","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage Site went dow=
n before Gen started due to poor battery backup // Grid returned","vanel.mb=
iada@matech-cameroun.com","117","27-04-2025 10:39:13","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0004895239","A=
bom","IHS_YND_269","27-04-2025 10:37:25","27-04-2025 10:29:18","27-04-2025 =
11:44:13",":Grid outage gen failed to start due to alarm '' underfrequency'=
'//We reset card GE and gen manually started","Siligap Boris","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel",":Grid outage gen failed =
to start due to alarm '' underfrequency''//We reset card GE and gen manuall=
y started","edwige.kapawo@matech-cameroun.com","488","27-04-2025 10:37:25",=
"MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004895238","Nko=
lmvack","","27-04-2025 10:37:20","27-04-2025 10:34:02","27-04-2025 18:01:02=
","ACTIVE// No power issue: Ubaie=3D52V site on Battery The Tx Fme Tsague( =
690488850)from Huawei is informed ","Parker Tchoup","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No=
 power issue: Ubaie=3D52V site on Battery The Tx Fme Tsague( 690488850)from=
 Huawei is informed ","vanel.mbiada@matech-cameroun.com","199","27-04-2025 =
10:37:20","MATECH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0004895209","Mvo=
g-Ada_OCM","","27-04-2025 10:31:39","27-04-2025 10:30:18","27-04-2025 11:09=
:15","Grid Only, No space to deploy // Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid Only, No space to depl=
oy // Grid return","vanel.mbiada@matech-cameroun.com","82","27-04-2025 10:3=
1:39","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0004895196","Min=
ka","","27-04-2025 10:29:26","27-04-2025 10:26:58","27-04-2025 20:34:05","A=
ctive//No power issue on Site, Ubaie=3D50,7V site on Gen , Etienne(69503398=
1)) from Huawei is informed","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power iss=
ue on Site, Ubaie=3D50,7V site on Gen , Etienne(695033981)) from Huawei is =
informed","vanel.mbiada@matech-cameroun.com","149","27-04-2025 10:29:26","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004895192","M=
bankomo IHS","","27-04-2025 10:28:20","27-04-2025 10:18:59","27-04-2025 10:=
51:43","Grid outage site went down because Gen failed to start due to Gen c=
ard faulty // Gen Manually Started","Fanda Brice","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage site went down because G=
en failed to start due to Gen card faulty // Gen Manually Started","edwige.=
kapawo@matech-cameroun.com","562","27-04-2025 10:28:20","MATECH CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004895187","Cha=
rles-Atangana","","27-04-2025 10:27:05","27-04-2025 10:25:44","27-04-2025 1=
0:33:47","Grid outage // Grid return","","Grid Supply","Passive","Grid","Na=
tional Grid - Grid Outage Issue","Grid outage // Grid return","vanel.mbiada=
@matech-cameroun.com","82","27-04-2025 10:27:05","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004895094","Oko=
lo Kilombo","","27-04-2025 10:16:39","27-04-2025 10:14:30","27-04-2025 11:4=
0:50",":Site went down due to insufficiency of rectifiers//We reset it and =
site on grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","R=
ectifier Module",":Site went down due to insufficiency of rectifiers//We re=
set it and site on grid","vanel.mbiada@matech-cameroun.com","129","27-04-20=
25 10:16:39","MATECH CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004895092","SOA=
 VILLAGE","","27-04-2025 10:16:01","27-04-2025 10:11:45","27-04-2025 11:08:=
45","Active// No power issue, site is on Grid with Ubaie=3D54,3 V TX FME Ju=
lien (693095849) from Huawei is informed","Siligap Boris","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue, site is on Grid with Ubaie=3D54,3 V TX FME Julien (6930=
95849) from Huawei is informed","vanel.mbiada@matech-cameroun.com","258","2=
7-04-2025 10:16:01","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004895086","Nko=
lfoulou","","27-04-2025 10:15:03","27-04-2025 10:11:52","27-04-2025 10:15:2=
4","Site went down due to PWC IPT dysfunctionning// site on Grid","Siligap =
Boris","Equipment Repair","Passive","Rectifier","Rectifier Module Overloade=
d","Site went down due to PWC IPT dysfunctionning// site on Grid","vanel.mb=
iada@matech-cameroun.com","192","27-04-2025 10:15:03","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004895082","Ebo=
go","","27-04-2025 10:13:48","27-04-2025 10:08:33","27-04-2025 10:23:07","G=
rid outage,site went down before gen starts due to poor battery backup//Gri=
d return","Siligap Boris","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage,site went down before gen starts due=
 to poor battery backup//Grid return","vanel.mbiada@matech-cameroun.com","3=
16","27-04-2025 10:13:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004895078","Melen Ba=
'aba","","27-04-2025 10:13:17","27-04-2025 10:09:16","27-04-2025 11:30:24",=
"Cascaded Incident from TTO5009071","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to PWC IPT dysf=
unctionning//He reset it and site on Grid","system","287688","27-04-2025 10=
:13:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_319","NOCINC0004895077","SOA 2","=
","27-04-2025 10:13:17","27-04-2025 10:09:16","27-04-2025 11:30:24","Cascad=
ed Incident from TTO5009071","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to PWC IPT dysfunction=
ning//He reset it and site on Grid","system","287688","27-04-2025 10:13:17"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004895076","SOA TOWN=
","","27-04-2025 10:13:16","27-04-2025 10:09:16","27-04-2025 11:30:24","Cas=
caded Incident from TTO5009071","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to PWC IPT dysfunct=
ionning//He reset it and site on Grid","system","287687","27-04-2025 10:13:=
16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_318","NOCINC0004895075","SOA Univ=
ersity","","27-04-2025 10:13:16","27-04-2025 10:09:16","27-04-2025 11:30:24=
","Cascaded Incident from TTO5009071","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site went down due to PWC IPT dy=
sfunctionning//He reset it and site on Grid","system","287687","27-04-2025 =
10:13:16","MATECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0004895066","Soa=
","IHS_YND_318, IHS_YND_320, IHS_YND_319, IHS_YND_308","27-04-2025 10:11:29=
","27-04-2025 10:09:16","27-04-2025 11:30:24","Site went down due to PWC IP=
T dysfunctionning//He reset it and site on Grid","Siligap Boris","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went dow=
n due to PWC IPT dysfunctionning//He reset it and site on Grid","vanel.mbia=
da@matech-cameroun.com","133","27-04-2025 10:11:29","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004895014","M=
ANGUIERS CHAPELLE","IHS_YND_506","27-04-2025 09:56:46","27-04-2025 08:09:31=
","27-04-2025 19:44:25","Meter burnt, site went down due to gen Overload(20=
KVA,270A)","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Meter burnt, site went down due to gen Overload(20KVA,270A) //=
 Load Reduced","edwige.kapawo@matech-cameroun.com","7746","27-04-2025 09:56=
:46","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004894998","SAA=
 Entrance","","27-04-2025 09:53:49","27-04-2025 09:51:25","27-04-2025 10:01=
:27","Active//No power issue on site Ubaie=3D54.1V site on Gen Tx FME Grego=
ire /654547479/Huawei is informed.","Parker Tchoup","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie=3D54.1V site on Gen Tx FME Gregoire /654547479/Hu=
awei is informed.","vanel.mbiada@matech-cameroun.com","145","27-04-2025 09:=
53:49","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004894996","O=
mnisport-Rail","","27-04-2025 09:53:13","27-04-2025 09:49:31","27-04-2025 1=
0:05:17","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Active//No power issue on site ,site on Gen with Ubaie=3D=
53.4 V The Tx FME Armand Nguetsa//699949553 from Huawei is informed ","edwi=
ge.kapawo@matech-cameroun.com","296007","27-04-2025 09:53:13","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004894983","M=
essassi 2","","27-04-2025 09:49:49","27-04-2025 09:48:40","27-04-2025 12:58=
:56","Site went down due to 04/06 rectifiers dysfuncionned//Site stabilised=
","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to 04/06 rectifiers dysfuncionned//Site stabilised=
","edwige.kapawo@matech-cameroun.com","70","27-04-2025 09:49:49","MATECH CM=
R"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004894976","E=
kombitie","","27-04-2025 09:49:08","27-04-2025 09:41:03","27-04-2025 10:07:=
11","Active: no power issue, site is on Gen with Ubaie=3D54.5V, Symphorien(=
650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue, site is on Gen with Ubaie=3D54.5V, Symphorien(650257151/ huawei)=
 is informed","edwige.kapawo@matech-cameroun.com","487","27-04-2025 09:49:0=
8","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004894701","Nko=
g-Edzen","","27-04-2025 08:51:00","27-04-2025 08:42:51","27-04-2025 10:30:4=
8","Grid Outage, site went down because gen stopped with unknown alarm (inv=
estigation ongoing) // Reset done and gen started","Parker Tchoup","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage, site w=
ent down because gen stopped with unknown alarm (investigation ongoing) // =
Reset done and gen started","vanel.mbiada@matech-cameroun.com","490","27-04=
-2025 08:51:00","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004894508","N=
kolo II New","","27-04-2025 08:16:48","27-04-2025 08:07:39","27-04-2025 08:=
50:55","No power issue site on Grid Ubaie: 54.7V, Site impacted by Mimboman=
_Don_bosco","Mba Lazare Herve","Customer Equipment Failure","Active","Activ=
e Equipment Failure","Affected by 3rd Party Site","No power issue site on G=
rid Ubaie: 54.7V, Site impacted by Mimboman_Don_bosco","edwige.kapawo@matec=
h-cameroun.com","550","27-04-2025 08:16:48","MATECH CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004894490","SOA=
 UNIVERSITY STADIUM","","27-04-2025 08:11:18","27-04-2025 08:07:07","27-04-=
2025 09:44:02","Grid outage.site went down due to gen failed to start //Gri=
d return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - C=
ontrol Panel","Grid outage.site went down due to gen failed to start //Grid=
 return","vanel.mbiada@matech-cameroun.com","252","27-04-2025 08:11:18","MA=
TECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004894295","Nom=
ayos montee Meche","","27-04-2025 07:36:02","27-04-2025 07:33:24","27-04-20=
25 07:35:36","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On G=
rid The Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On Grid =
The Tx FME Fulbert(654266068) from Huawei is informed","vanel.mbiada@matech=
-cameroun.com","159","27-04-2025 07:36:02","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004894168","NTE=
MASSI","","27-04-2025 07:11:06","27-04-2025 07:05:59","27-04-2025 07:40:46"=
,"Grid outage, Site down due to Rectifiers issue // site stabilised","Delor=
 Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Gri=
d outage, Site down due to Rectifiers issue // site stabilised","vanel.mbia=
da@matech-cameroun.com","308","27-04-2025 07:11:06","MATECH CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004894024","Bas=
tos Amb Coree","","27-04-2025 06:37:41","27-04-2025 06:26:34","27-04-2025 0=
6:56:04","Grid Only, No space to deploy MGE // Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No space=
 to deploy MGE // Grid return","franck.nkomot@matech-cameroun.com","668","2=
7-04-2025 06:37:41","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004893919","S=
atcom","","27-04-2025 05:50:11","27-04-2025 05:37:03","27-04-2025 08:44:12"=
,"Active // No power issue site on Grid with Ubay:50.8V Tx Fme Armand Ngest=
sa (691144412) of huawei is informed","Delor Telezing","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/ No power issue site on Grid with Ubay:50.8V Tx Fme Armand Ngestsa (691144=
412) of huawei is informed","christelle.ngonga@matech-cameroun.com","789","=
27-04-2025 05:50:11","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004893839","B=
riqueterie","","27-04-2025 05:20:41","27-04-2025 05:07:01","27-04-2025 06:5=
3:04","Grid outage ,no space to deploy MGE // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,no spac=
e to deploy MGE // Grid return","christelle.ngonga@matech-cameroun.com","82=
1","27-04-2025 05:20:41","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004893786","Eke=
kam","","27-04-2025 04:58:04","27-04-2025 04:55:51","27-04-2025 07:22:39","=
Grid outage site went down because Gen stopped with alarm HIGH temp due to =
Radiator pierced // He added water manually start of Gen","TIENTCHEU NZETCH=
IEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator Leakage"=
,"Grid outage site went down because Gen stopped with alarm HIGH temp due t=
o Radiator pierced // He added water manually start of Gen","ludivine.ngama=
leu@ihstowers.com","134","27-04-2025 04:58:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004893784","Minka","=
","27-04-2025 04:57:21","27-04-2025 04:52:28","27-04-2025 04:58:28","Cascad=
ed Incident from TTO5007603","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Impacted by Ngoumou (not managing by IHS)","sy=
stem","263403","27-04-2025 04:57:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004893783","OTELE MT=
N","","27-04-2025 04:57:21","27-04-2025 04:52:28","27-04-2025 04:58:28","Ca=
scaded Incident from TTO5007603","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Impacted by Ngoumou (not managing by IHS)"=
,"system","263403","27-04-2025 04:57:21","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004893782","Mom=
","IHS_YND_531, IHS_YND_371","27-04-2025 04:55:32","27-04-2025 04:52:28","2=
7-04-2025 04:58:28","Impacted by Ngoumou (not managing by IHS)","Fanda Bric=
e","Customer Equipment Failure","Active","Active Equipment Failure","Affect=
ed by 3rd Party Site","Impacted by Ngoumou (not managing by IHS)","ludivine=
.ngamaleu@ihstowers.com","186","27-04-2025 04:55:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004893780","AFEME NO=
RD","","27-04-2025 04:54:53","27-04-2025 04:07:32","27-04-2025 05:48:02","C=
ascaded Incident from TTO5007572","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because ge=
n failed to start due to grid bad voltage // He bypassed grid and manually =
start the gen","system","273668","27-04-2025 04:54:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0004893781","Dagobert=
","","27-04-2025 04:54:53","27-04-2025 04:07:32","27-04-2025 05:48:02","Cas=
caded Incident from TTO5007572","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down because gen =
failed to start due to grid bad voltage // He bypassed grid and manually st=
art the gen","system","273665","27-04-2025 04:54:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004893779","Golf Qua=
ter","","27-04-2025 04:54:52","27-04-2025 04:07:32","27-04-2025 05:48:02","=
Cascaded Incident from TTO5007572","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because gen failed t=
o start due to grid bad voltage // He bypassed grid and manually start the =
gen","system","273665","27-04-2025 04:54:52","MATECH CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004893775","Bri=
quetterie","","27-04-2025 04:52:46","27-04-2025 04:46:33","27-04-2025 07:03=
:45","Grid outage ,no space to deploy MGE // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,no space=
 to deploy MGE // Grid return","ludivine.ngamaleu@ihstowers.com","373","27-=
04-2025 04:52:46","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004893773","N=
komkana 2","","27-04-2025 04:51:11","27-04-2025 04:07:32","27-04-2025 05:48=
:02","Cascaded Incident from TTO5007572","Mboua Thierry","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because gen fa=
iled to start due to grid bad voltage // He bypassed grid and manually star=
t the gen","christelle.ngonga@matech-cameroun.com","273670","27-04-2025 04:=
51:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_233","NOCINC0004893757","Oyomaban=
g OCM","IHS_YND_273, IHS_YND_220, IHS_YND_519, IHS_YND_138, IHS_YND_202, IH=
S_YND_200, IHS_YND_686, IHS_YND_126, IHS_YND_559, IHS_YND_230, IHS_YND_232,=
 IHS_YND_127, IHS_YND_286, IHS_YND_543","27-04-2025 04:40:40","27-04-2025 0=
4:07:32","27-04-2025 05:48:02","Site went down because gen failed to start =
due to grid bad voltage // He bypassed grid and manually start the gen","TI=
ENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Low=
 Current Supply","Site went down because gen failed to start due to grid ba=
d voltage // He bypassed grid and manually start the gen","christelle.ngong=
a@matech-cameroun.com","1989","27-04-2025 04:40:40","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004893736","B=
astos-Nylon","","27-04-2025 04:31:02","27-04-2025 04:07:32","27-04-2025 05:=
48:02","Cascaded Incident from TTO5007572","Mboua Thierry","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down because gen =
failed to start due to grid bad voltage // He bypassed grid and manually st=
art the gen","christelle.ngonga@matech-cameroun.com","273671","27-04-2025 0=
4:31:02","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0004893734","N=
komkana","","27-04-2025 04:30:13","27-04-2025 04:07:32","27-04-2025 05:48:0=
2","Cascaded Incident from TTO5007572","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Site went down because gen failed to start d=
ue to grid bad voltage // He bypassed grid and manually start the gen","chr=
istelle.ngonga@matech-cameroun.com","273666","27-04-2025 04:30:13","MATECH =
CMR"
"Closed Complete","Site Down","CTR_553","IHS_YND_686","NOCINC0004893722","O=
yomabang Ecole","","27-04-2025 04:29:28","27-04-2025 04:07:32","27-04-2025 =
05:48:02","Cascaded Incident from TTO5007572","TIENTCHEU NZETCHIEU GAEL","C=
ascade Outage","Passive","Cascade Passive","Cascade Passive","Site went dow=
n because gen failed to start due to grid bad voltage // He bypassed grid a=
nd manually start the gen","christelle.ngonga@matech-cameroun.com","273668"=
,"27-04-2025 04:29:28","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004893721","B=
ATA Mokolo OCM","","27-04-2025 04:28:32","27-04-2025 04:07:32","27-04-2025 =
05:48:02","Cascaded Incident from TTO5007572","","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down because gen failed to =
start due to grid bad voltage // He bypassed grid and manually start the ge=
n","christelle.ngonga@matech-cameroun.com","273667","27-04-2025 04:28:32","=
MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004893717","C=
ite-Verte","","27-04-2025 04:27:20","27-04-2025 04:07:32","27-04-2025 05:48=
:02","Cascaded Incident from TTO5007572","","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Site went down because gen failed to start=
 due to grid bad voltage // He bypassed grid and manually start the gen","c=
hristelle.ngonga@matech-cameroun.com","273666","27-04-2025 04:27:20","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_122","IHS_YND_230","NOCINC0004893710","M=
eyong-Meyeme","","27-04-2025 04:25:31","27-04-2025 04:07:32","27-04-2025 05=
:48:02","Cascaded Incident from TTO5007572","TIENTCHEU NZETCHIEU GAEL","Cas=
cade Outage","Passive","Cascade Passive","Cascade Passive","Site went down =
because gen failed to start due to grid bad voltage // He bypassed grid and=
 manually start the gen","christelle.ngonga@matech-cameroun.com","273669","=
27-04-2025 04:25:31","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004893709","C=
rf-Nkolbisson","","27-04-2025 04:24:39","27-04-2025 04:07:32","27-04-2025 0=
5:48:02","Cascaded Incident from TTO5007572","TIENTCHEU NZETCHIEU GAEL","Ca=
scade Outage","Passive","Cascade Passive","Cascade Passive","Site went down=
 because gen failed to start due to grid bad voltage // He bypassed grid an=
d manually start the gen","christelle.ngonga@matech-cameroun.com","273669",=
"27-04-2025 04:24:39","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004893705","T=
singa","","27-04-2025 04:23:50","27-04-2025 04:07:32","27-04-2025 05:48:02"=
,"Cascaded Incident from TTO5007572","Mboua Thierry","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because gen failed=
 to start due to grid bad voltage // He bypassed grid and manually start th=
e gen","christelle.ngonga@matech-cameroun.com","273670","27-04-2025 04:23:5=
0","MATECH CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0004893702","E=
ntree Cite Verte","","27-04-2025 04:23:03","27-04-2025 04:07:32","27-04-202=
5 05:48:02","Cascaded Incident from TTO5007572","Paul BIBOUM","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down because g=
en failed to start due to grid bad voltage // He bypassed grid and manually=
 start the gen","christelle.ngonga@matech-cameroun.com","273666","27-04-202=
5 04:23:03","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0004893699","N=
kolbi-Boss","","27-04-2025 04:22:12","27-04-2025 04:07:32","27-04-2025 05:4=
8:02","Cascaded Incident from TTO5007572","TIENTCHEU NZETCHIEU GAEL","Casca=
de Outage","Passive","Cascade Passive","Cascade Passive","Site went down be=
cause gen failed to start due to grid bad voltage // He bypassed grid and m=
anually start the gen","christelle.ngonga@matech-cameroun.com","273667","27=
-04-2025 04:22:12","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004893674","M=
bankomo IHS","","27-04-2025 04:07:16","27-04-2025 03:45:01","27-04-2025 04:=
35:01","Site went down due to (02/02) rectifiers dysfunction // He reset it=
 and site on Grid","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to (02/02) rectifiers dysfunction // =
He reset it and site on Grid","christelle.ngonga@matech-cameroun.com","1336=
","27-04-2025 04:07:16","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004893551","UPA=
C LP","","27-04-2025 03:15:50","27-04-2025 03:08:34","27-04-2025 11:01:33",=
"Grid outage.no space to deploy mobile gen //Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no space =
to deploy mobile gen //Grid return","ludivine.ngamaleu@ihstowers.com","437"=
,"27-04-2025 03:15:50","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004893502","H=
-General-Yde","","27-04-2025 02:54:26","27-04-2025 02:50:06","27-04-2025 03=
:08:11","No power issue site on grid with Ubay:54.4V Symphorien /691316854 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with Ubay:54.4V Symphorien /691316854 from Huawei is informed","chris=
telle.ngonga@matech-cameroun.com","261","27-04-2025 02:54:26","MATECH CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004893303","V=
allee-Bastos OCM","","27-04-2025 01:34:26","27-04-2025 01:30:18","27-04-202=
5 20:39:35"," Grid only no free mobile gen to deploy ,// grid restoration",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"," Gri=
d only no free mobile gen to deploy ,// grid restoration","christelle.ngong=
a@matech-cameroun.com","249","27-04-2025 01:34:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004893201","Dong",""=
,"27-04-2025 00:53:20","27-04-2025 00:13:31","27-04-2025 02:35:31","Cascade=
d Incident from TTO5006785","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Site went down because Gen ran until Fuel =
shortage // refueling done","system","1222338","27-04-2025 00:53:20","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004893199","Ngouetou=
","","27-04-2025 00:53:20","27-04-2025 00:13:31","27-04-2025 02:35:31","Cas=
caded Incident from TTO5006785","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because Gen ran until F=
uel shortage // refueling done","system","1222339","27-04-2025 00:53:20","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004893200","Donga","=
","27-04-2025 00:53:20","27-04-2025 00:13:31","27-04-2025 02:35:31","Cascad=
ed Incident from TTO5006785","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because Gen ran until Fuel=
 shortage // refueling done","system","1222339","27-04-2025 00:53:20","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004893202","Yoko MTN=
","","27-04-2025 00:53:20","27-04-2025 00:13:31","27-04-2025 02:35:31","Cas=
caded Incident from TTO5006785","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because Gen ran until F=
uel shortage // refueling done","system","1222337","27-04-2025 00:53:20","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004893198","Ngoum","=
","27-04-2025 00:53:19","27-04-2025 00:13:31","27-04-2025 02:35:31","Cascad=
ed Incident from TTO5006785","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because Gen ran until Fuel=
 shortage // refueling done","system","1222337","27-04-2025 00:53:19","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004893197","Matsari"=
,"","27-04-2025 00:53:19","27-04-2025 00:13:31","27-04-2025 02:35:31","Casc=
aded Incident from TTO5006785","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because Gen ran until Fu=
el shortage // refueling done","system","1222340","27-04-2025 00:53:19","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0004893195","Nguila",=
"","27-04-2025 00:53:19","27-04-2025 00:13:31","27-04-2025 02:35:31","Casca=
ded Incident from TTO5006785","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down because Gen ran until Fue=
l shortage // refueling done","system","1222338","27-04-2025 00:53:19","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004893196","MBIMBIM"=
,"","27-04-2025 00:53:19","27-04-2025 00:13:31","27-04-2025 02:35:31","Casc=
aded Incident from TTO5006785","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because Gen ran until Fu=
el shortage // refueling done","system","1222340","27-04-2025 00:53:19","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0004893147","C=
harles-Atangana","IHS_YND_051","27-04-2025 00:43:40","27-04-2025 00:12:32",=
"27-04-2025 07:00:00","Grid outage ,no space to deploy MGE // Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage ,no space to deploy MGE // Grid return","christelle.ngonga@matech-c=
ameroun.com","1869","27-04-2025 00:43:40","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004893145","Mok=
olo Yaounde","","27-04-2025 00:43:26","27-04-2025 00:14:00","27-04-2025 06:=
55:00","Active // No power issue Ubay:54.6V site on grid. The Tx FME Elound=
ou Bertrand (693212405) from Huawei is informed","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue Ubay:54.6V site on grid. The Tx FME Eloundou Bertrand (693212=
405) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","1768","27-=
04-2025 00:43:26","MATECH CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004893142","M=
amch Building","","27-04-2025 00:42:43","27-04-2025 00:12:32","27-04-2025 0=
6:53:19","Cascaded Incident from TTO5006856","Mboua Thierry","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Cascaded Incident from TT=
O5006856","christelle.ngonga@matech-cameroun.com","287547","27-04-2025 00:4=
2:43","MATECH CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0004893139","Y=
ona Hotel","","27-04-2025 00:42:00","26-04-2025 23:57:47","27-04-2025 01:13=
:49","Active: no power issue, site is on grid with Ubaie=3D54.5V, Mohamadou=
(691144435) from Huawei is informe","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active: no power issue, site is on grid with Ubaie=3D54.5V, Mohamadou(69114=
4435) from Huawei is informe","christelle.ngonga@matech-cameroun.com","2654=
","27-04-2025 00:42:00","MATECH CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0004893081","Oss=
ombe","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS=
_YND_434, IHS_YND_444, IHS_YND_473","27-04-2025 00:17:37","27-04-2025 00:13=
:31","27-04-2025 02:35:31","Site went down because Gen ran until Fuel short=
age // refueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Di=
esel Outage","Site went down because Gen ran until Fuel shortage // refueli=
ng done","franck.nkomot@matech-cameroun.com","247","27-04-2025 00:17:37","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004893001","E=
koumdoum OCM","","26-04-2025 23:53:33","26-04-2025 23:49:25","27-04-2025 15=
:13:43","Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline i=
s informed and confirmed// Grid return","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen overload(=
20kva,280 A) IHS SS Pascaline is informed and confirmed// Grid return","chr=
istelle.ngonga@matech-cameroun.com","249","26-04-2025 23:53:33","MATECH CMR=
"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004892959","N=
omayos montee Meche","","26-04-2025 23:38:26","26-04-2025 23:37:20","27-04-=
2025 01:16:34","Active: No power issue, site is on grid with Ubaie=3D51V, F=
lubert(654266068) from Huawei is informed","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
: No power issue, site is on grid with Ubaie=3D51V, Flubert(654266068) from=
 Huawei is informed","christelle.ngonga@matech-cameroun.com","67","26-04-20=
25 23:38:26","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004892956","M=
essassi okolo","","26-04-2025 23:37:43","26-04-2025 23:36:36","27-04-2025 0=
0:56:22","Site impacted  by pont emana wish is not manage by IHS","Fabrice =
Pouakam","Customer Equipment Failure","Active","Active Equipment Failure","=
Affected by 3rd Party Site","Site impacted  by pont emana wish is not manag=
e by IHS","christelle.ngonga@matech-cameroun.com","69","26-04-2025 23:37:43=
","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004892947","NTE=
MASSI","","26-04-2025 23:35:47","26-04-2025 23:26:36","27-04-2025 03:42:36"=
,"Grid outage, Site down due to Rectifiers issue // Site on Gen","Delor Tel=
ezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Grid ou=
tage, Site down due to Rectifiers issue // Site on Gen","ludivine.ngamaleu@=
ihstowers.com","552","26-04-2025 23:35:47","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004892881","NTE=
MASSI","","26-04-2025 23:14:24","26-04-2025 23:06:20","26-04-2025 23:22:20"=
,"Grid outage, Site down due to Rectifiers issue // Site on Gen","Delor Tel=
ezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Grid ou=
tage, Site down due to Rectifiers issue // Site on Gen","ludivine.ngamaleu@=
ihstowers.com","485","26-04-2025 23:14:24","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004892878","M=
endong vallee","","26-04-2025 23:12:50","26-04-2025 23:04:43","27-04-2025 0=
1:25:31","Active //No power issue on site U=3D50.9 V The Tx FME Hosiah//699=
699694 is informed","Fanda Brice","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active //No power issue on si=
te U=3D50.9 V The Tx FME Hosiah//699699694 is informed","christelle.ngonga@=
matech-cameroun.com","488","26-04-2025 23:12:50","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004892683","NTE=
MASSI","","26-04-2025 22:27:32","26-04-2025 22:10:25","26-04-2025 23:00:25"=
,"Grid outage, Site down due to Rectifiers issue // Site on Gen","Delor Tel=
ezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Grid ou=
tage, Site down due to Rectifiers issue // Site on Gen","loic.noumsi@matech=
-cameroun.com","1028","26-04-2025 22:27:32","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004892656","F=
ouda-New","","26-04-2025 22:19:58","26-04-2025 21:54:43","27-04-2025 07:58:=
16","Site went down due to Dysjunction of CB(125A) in PWC  (Access issue du=
ring the night due to Landlord) // CB Rearmed","Delor Telezing","Equipment =
Repair","Passive","Control Panel","BTS Breaker Tripped","Site went down due=
 to Dysjunction of CB(125A) in PWC  (Access issue during the night due to L=
andlord) // CB Rearmed","gaelle.njiofack@matech-cameroun.com","1516","26-04=
-2025 22:19:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004892490","Melen Ba=
'aba","","26-04-2025 21:44:33","26-04-2025 21:17:10","26-04-2025 22:21:10",=
"Cascaded Incident from TTO5005948","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down due to(2/7) rectifi=
er faulty//We reset rectifiers and site on grid","system","276257","26-04-2=
025 21:44:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_318","NOCINC0004892443","SOA Univ=
ersity","","26-04-2025 21:36:34","26-04-2025 21:17:10","26-04-2025 22:21:10=
","Cascaded Incident from TTO5005948","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","site went down due to(2/7) recti=
fier faulty//We reset rectifiers and site on grid","system","276254","26-04=
-2025 21:36:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004892427","SOA UNIV=
ERSITY STADIUM","","26-04-2025 21:34:49","26-04-2025 21:17:10","26-04-2025 =
22:21:10","Cascaded Incident from TTO5005948","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","site went down due to(2/=
7) rectifier faulty//We reset rectifiers and site on grid","system","276256=
","26-04-2025 21:34:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004892429","SOA VILL=
AGE","","26-04-2025 21:34:49","26-04-2025 21:17:10","26-04-2025 22:21:10","=
Cascaded Incident from TTO5005948","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down due to(2/7) rectifie=
r faulty//We reset rectifiers and site on grid","system","276255","26-04-20=
25 21:34:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004892430","Ebogo","=
","26-04-2025 21:34:49","26-04-2025 21:17:10","26-04-2025 22:21:10","Cascad=
ed Incident from TTO5005948","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down due to(2/7) rectifier faul=
ty//We reset rectifiers and site on grid","system","276256","26-04-2025 21:=
34:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_319","NOCINC0004892428","SOA 2","=
","26-04-2025 21:34:49","26-04-2025 21:17:10","26-04-2025 22:21:10","Cascad=
ed Incident from TTO5005948","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down due to(2/7) rectifier faul=
ty//We reset rectifiers and site on grid","system","276255","26-04-2025 21:=
34:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004892426","SOA TOWN=
","","26-04-2025 21:34:48","26-04-2025 21:17:10","26-04-2025 22:21:10","Cas=
caded Incident from TTO5005948","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down due to(2/7) rectifier f=
aulty//We reset rectifiers and site on grid","system","276254","26-04-2025 =
21:34:48","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004892411","T=
amtam Weekend","","26-04-2025 21:33:00","26-04-2025 21:24:41","26-04-2025 2=
2:16:24","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","site went down due to disjunction of CB (125A) in the PWC=
 // CB rearm","gaelle.njiofack@matech-cameroun.com","268767","26-04-2025 21=
:33:00","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004892404","D=
amas","","26-04-2025 21:32:23","26-04-2025 21:24:41","26-04-2025 22:16:24",=
"","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","site went down due to disjunction of CB (125A) in the PWC // CB rea=
rm","gaelle.njiofack@matech-cameroun.com","268766","26-04-2025 21:32:23","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0004892401","R=
d-Pt-Express","IHS_YND_166, IHS_YND_151, IHS_YND_546, IHS_YND_518","26-04-2=
025 21:31:49","26-04-2025 21:24:41","26-04-2025 22:16:24","site went down d=
ue to disjunction of CB (125A) in the PWC // CB rearm","","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site w=
ent down due to disjunction of CB (125A) in the PWC // CB rearm","gaelle.nj=
iofack@matech-cameroun.com","428","26-04-2025 21:31:49","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004892399","M=
ontee-Jouvence-II","","26-04-2025 21:31:16","26-04-2025 21:24:41","26-04-20=
25 22:16:24","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","site went down due to disjunction of CB (125A) in the=
 PWC // CB rearm","gaelle.njiofack@matech-cameroun.com","268767","26-04-202=
5 21:31:16","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004892390","B=
iyemassi LAC","","26-04-2025 21:30:08","26-04-2025 21:24:41","26-04-2025 22=
:16:24","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","site went down due to disjunction of CB (125A) in the PWC // CB rearm","=
gaelle.njiofack@matech-cameroun.com","268766","26-04-2025 21:30:08","MATECH=
 CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004892386","Nlo=
ngkak","","26-04-2025 21:29:11","26-04-2025 21:22:03","26-04-2025 21:56:03"=
,"site went down due to insufficient of rectifiers on site // Site Stabiliz=
ed","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down due to insufficient of rectifiers on site // Site Sta=
bilized","loic.noumsi@matech-cameroun.com","429","26-04-2025 21:29:11","MAT=
ECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0004892367","Soa=
","IHS_YND_318, IHS_YND_320, IHS_YND_720, IHS_YND_319, IHS_YND_308, IHS_YND=
_323, IHS_YND_307","26-04-2025 21:27:19","26-04-2025 21:17:10","26-04-2025 =
22:21:10","site went down due to(2/7) rectifier faulty//We reset rectifiers=
 and site on grid","Siligap Boris","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","site went down due to(2/7) rectifier faulty//We reset =
rectifiers and site on grid","loic.noumsi@matech-cameroun.com","610","26-04=
-2025 21:27:19","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004892329","M=
essassi okolo","","26-04-2025 21:20:50","26-04-2025 21:11:38","26-04-2025 2=
1:24:35","ACTIVE//No power issue on site Ubaie=3D54.4V, site on Grid The TX=
 Fme Synphorien 691316854 of Huawei is informed.Noticed impacted by pont em=
mana","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equip=
ment Failure","Affected by 3rd Party Site","ACTIVE//No power issue on site =
Ubaie=3D54.4V, site on Grid The TX Fme Synphorien 691316854 of Huawei is in=
formed.Noticed impacted by pont emmana","gaelle.njiofack@matech-cameroun.co=
m","554","26-04-2025 21:20:50","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004892256","Par=
adis Hotel","","26-04-2025 21:12:43","26-04-2025 21:03:37","26-04-2025 22:5=
7:37","Site went down because 01/03 malfunctioning rectifier // He reset re=
ctifiers","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down because 01/03 malfunctioning rectifier // He res=
et rectifiers","loic.noumsi@matech-cameroun.com","547","26-04-2025 21:12:43=
","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004891944","M=
essassi 2","","26-04-2025 20:29:40","26-04-2025 20:26:25","26-04-2025 21:47=
:24","Site went down because 04/06 rectifiers dysfuncionned// He reset rect=
ifiers, site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down because 04/06 rectifiers dysfuncion=
ned// He reset rectifiers, site on Gen","gaelle.njiofack@matech-cameroun.co=
m","196","26-04-2025 20:29:40","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004891715","Eke=
kam","","26-04-2025 19:52:06","26-04-2025 19:42:41","26-04-2025 20:21:36","=
Site went downt due to work of Our FME Gael (soldering the unloading pot)//=
 End of work","TIENTCHEU NZETCHIEU GAEL","Equipment Replacement","Passive",=
"Planned Activity","Planned Activity - ACDG Inspection","Site went downt du=
e to work of Our FME Gael (soldering the unloading pot)// End of work","loi=
c.noumsi@matech-cameroun.com","566","26-04-2025 19:52:06","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004891689","N=
koabang2","","26-04-2025 19:47:14","26-04-2025 19:44:06","26-04-2025 21:08:=
48",":Grid outage gen failed to start due to gen overload(22kva,310A)//We r=
educe load and gen manually started","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload",":Grid outage gen failed to start du=
e to gen overload(22kva,310A)//We reduce load and gen manually started","ga=
elle.njiofack@matech-cameroun.com","189","26-04-2025 19:47:14","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004891650","Par=
adis Hotel","","26-04-2025 19:39:27","26-04-2025 19:27:18","26-04-2025 19:5=
6:51","Site went down because 01/03 rectifiers dysfuncionned// He reset rec=
tifiers","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down because 01/03 rectifiers dysfuncionned// He reset=
 rectifiers","loic.noumsi@matech-cameroun.com","729","26-04-2025 19:39:27",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004891593","B=
itoto","","26-04-2025 19:29:54","26-04-2025 19:19:59","26-04-2025 23:26:32"=
,"	Active//No power issue on site , Tx Issue : site on Grid ,Ubai: 53.1V; T=
he fme Tx Henri (699949693) From huawei is informed","Mba Lazare Herve","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","	Active//No power issue on site , Tx Issue : site on Grid ,Ubai: 5=
3.1V; The fme Tx Henri (699949693) From huawei is informed","gaelle.njiofac=
k@matech-cameroun.com","596","26-04-2025 19:29:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004891473","Melen Ba=
'aba","","26-04-2025 19:08:56","26-04-2025 18:54:49","26-04-2025 19:12:12",=
"Cascaded Incident from TTO5004868","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site Ubay 54V site =
on Grid Julien /693095849 from Huawei is informed, site up without interven=
tion","system","270638","26-04-2025 19:08:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004891474","Ebogo","=
","26-04-2025 19:08:56","26-04-2025 18:54:49","26-04-2025 19:12:12","Cascad=
ed Incident from TTO5004868","Siligap Boris","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubay 54V site on Grid=
 Julien /693095849 from Huawei is informed, site up without intervention","=
system","270637","26-04-2025 19:08:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_319","NOCINC0004891472","SOA 2","=
","26-04-2025 19:08:55","26-04-2025 18:54:49","26-04-2025 19:12:12","Cascad=
ed Incident from TTO5004868","Siligap Boris","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubay 54V site on Grid=
 Julien /693095849 from Huawei is informed, site up without intervention","=
system","270636","26-04-2025 19:08:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004891471","SOA UNIV=
ERSITY STADIUM","","26-04-2025 19:08:55","26-04-2025 18:54:49","26-04-2025 =
19:12:12","Cascaded Incident from TTO5004868","Siligap Boris","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","No power issue on site Ubay=
 54V site on Grid Julien /693095849 from Huawei is informed, site up withou=
t intervention","system","270636","26-04-2025 19:08:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_318","NOCINC0004891469","SOA Univ=
ersity","","26-04-2025 19:08:55","26-04-2025 18:54:49","26-04-2025 19:12:12=
","Cascaded Incident from TTO5004868","Siligap Boris","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue on site Ubay 54V sit=
e on Grid Julien /693095849 from Huawei is informed, site up without interv=
ention","system","270637","26-04-2025 19:08:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004891470","SOA TOWN=
","","26-04-2025 19:08:55","26-04-2025 18:54:49","26-04-2025 19:12:12","Cas=
caded Incident from TTO5004868","Siligap Boris","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubay 54V site on G=
rid Julien /693095849 from Huawei is informed, site up without intervention=
","system","270637","26-04-2025 19:08:55","MATECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0004891453","Soa=
","IHS_YND_318, IHS_YND_320, IHS_YND_720, IHS_YND_319, IHS_YND_308, IHS_YND=
_323, IHS_YND_307","26-04-2025 19:05:58","26-04-2025 18:54:49","26-04-2025 =
19:12:12","No power issue on site Ubay 54V site on Grid Julien /693095849 f=
rom Huawei is informed, site up without intervention","Siligap Boris","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site Ubay 54V site on Grid Julien /693095849 from =
Huawei is informed, site up without intervention","loic.noumsi@matech-camer=
oun.com","670","26-04-2025 19:05:58","MATECH CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004891432","SOA=
 VILLAGE","","26-04-2025 19:02:16","26-04-2025 18:54:49","26-04-2025 19:12:=
12","","Siligap Boris","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue on site Ubay 54V site on Grid Julien /693095849 fro=
m Huawei is informed, site up without intervention","gaelle.njiofack@matech=
-cameroun.com","270639","26-04-2025 19:02:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0004890845","Monatele=
","","26-04-2025 17:31:49","26-04-2025 17:23:06","26-04-2025 18:14:12","Cas=
caded Incident from TTO5004179","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down due to Fue=
l shortage  // Refueling done (100L)","system","276073","26-04-2025 17:31:4=
9","MATECH CMR"
"Closed Complete","Site Down","T0053","IHS_YND_407","NOCINC0004890836","Mon=
atele MTN","IHS_YND_406","26-04-2025 17:31:15","26-04-2025 17:23:06","26-04=
-2025 18:14:12","Grid outage, Site went down due to Fuel shortage  // Refue=
ling done (100L)","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage, Site went down due to Fuel shortage  // Refueling don=
e (100L)","loic.noumsi@matech-cameroun.com","490","26-04-2025 17:31:15","MA=
TECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004890738","Mes=
sassi 2","","26-04-2025 17:20:53","26-04-2025 17:08:49","26-04-2025 18:00:2=
7","	Site went down because 04/06 rectifiers dysfuncionned// He reset recti=
fiers, site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","	Site went down because 04/06 rectifiers dysfuncion=
ned// He reset rectifiers, site on Gen","loic.noumsi@matech-cameroun.com","=
7641","26-04-2025 17:20:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004890649","NKONGKAR=
AK","","26-04-2025 17:01:53","26-04-2025 16:50:37","26-04-2025 18:16:05","C=
ascaded Incident from TTO5003926","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage,site went dow=
n hybrid system malfunction //  DG start manually and  hybrid system reset.=
","system","277806","26-04-2025 17:01:53","MATECH CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0004890610","L=
obo OCM","IHS_YND_713","26-04-2025 16:57:43","26-04-2025 16:50:37","26-04-2=
025 18:16:05","Grid outage,site went down hybrid system malfunction //  DG =
start manually and  hybrid system reset.","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","Hybrid","Hybrid Module","Grid outage,site went down=
 hybrid system malfunction //  DG start manually and  hybrid system reset."=
,"gaelle.njiofack@matech-cameroun.com","426","26-04-2025 16:57:43","MATECH =
CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0004890588","C=
arington","","26-04-2025 16:53:47","26-04-2025 16:49:38","26-04-2025 18:55:=
23","Grid only, lessor refuses to deploy Gen // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid only, lessor =
refuses to deploy Gen // Grid return","gaelle.njiofack@matech-cameroun.com"=
,"250","26-04-2025 16:53:47","MATECH CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004890373","V=
allee-Bastos OCM","","26-04-2025 16:26:02","26-04-2025 16:16:56","26-04-202=
5 21:08:10","GRID ONLY, Grid outage, No MG to deploy on site // Grid return=
ed","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
GRID ONLY, Grid outage, No MG to deploy on site // Grid returned","gaelle.n=
jiofack@matech-cameroun.com","547","26-04-2025 16:26:02","MATECH CMR"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0004890358","COR=
NIERS","","26-04-2025 16:24:04","26-04-2025 16:15:55","26-04-2025 19:00:55"=
,"Grid outage,no space to deploy mobile gen // Grid returned","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no sp=
ace to deploy mobile gen // Grid returned","loic.noumsi@matech-cameroun.com=
","490","26-04-2025 16:24:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004890259","Entree C=
ite Verte","","26-04-2025 16:04:20","26-04-2025 15:54:51","26-04-2025 16:33=
:59","Cascaded Incident from TTO5003459","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to=
 alarm High temp // Water add and Gen start manually","system","274208","26=
-04-2025 16:04:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004890258","Tsinga",=
"","26-04-2025 16:04:20","26-04-2025 15:54:51","26-04-2025 16:33:59","Casca=
ded Incident from TTO5003459","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, Gen stopped due to alarm Hi=
gh temp // Water add and Gen start manually","system","274209","26-04-2025 =
16:04:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0004890256","Bastos-N=
ylon","","26-04-2025 16:04:19","26-04-2025 15:54:51","26-04-2025 16:33:59",=
"Cascaded Incident from TTO5003459","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to al=
arm High temp // Water add and Gen start manually","system","274209","26-04=
-2025 16:04:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004890254","Nkomkana=
 2","","26-04-2025 16:04:19","26-04-2025 15:54:51","26-04-2025 16:33:59","C=
ascaded Incident from TTO5003459","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to alar=
m High temp // Water add and Gen start manually","system","274210","26-04-2=
025 16:04:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004890257","Bastos B=
ethesda","","26-04-2025 16:04:19","26-04-2025 15:54:51","26-04-2025 16:33:5=
9","Cascaded Incident from TTO5003459","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to=
 alarm High temp // Water add and Gen start manually","system","274207","26=
-04-2025 16:04:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004890255","Nkomkana=
","","26-04-2025 16:04:19","26-04-2025 15:54:51","26-04-2025 16:33:59","Cas=
caded Incident from TTO5003459","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage, Gen stopped due to alarm High temp // =
Water add and Gen start manually","system","274208","26-04-2025 16:04:19","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004890253","Golf Qua=
ter","","26-04-2025 16:04:18","26-04-2025 15:54:51","26-04-2025 16:33:59","=
Cascaded Incident from TTO5003459","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to ala=
rm High temp // Water add and Gen start manually","system","274209","26-04-=
2025 16:04:18","MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004890205","C=
ite-Verte","IHS_YND_220, IHS_YND_138, IHS_YND_200, IHS_YND_126, IHS_YND_563=
, IHS_YND_127, IHS_YND_543","26-04-2025 15:56:33","26-04-2025 15:54:51","26=
-04-2025 16:33:59","Grid outage, Gen stopped due to alarm High temp // Wate=
r add and Gen start manually","","Equipment Repair","Passive","ACDG Gen","G=
en Temp High","Grid outage, Gen stopped due to alarm High temp // Water add=
 and Gen start manually","gaelle.njiofack@matech-cameroun.com","103","26-04=
-2025 15:56:33","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004890193","O=
mnisport 3","","26-04-2025 15:54:10","26-04-2025 15:52:03","26-04-2025 21:0=
0:33","Site went down due to PWC Overloaded (12K, 250A) // site stabilized =
SS IHS Alphonse confirmed","Delor Telezing","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","Site went down due to PWC Overload=
ed (12K, 250A) // site stabilized SS IHS Alphonse confirmed","gaelle.njiofa=
ck@matech-cameroun.com","128","26-04-2025 15:54:10","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004889839","Ron=
d Point Express1114","","26-04-2025 15:25:36","26-04-2025 15:16:29","26-04-=
2025 15:34:23","Grid outage Site went down before Gen started due to poor b=
attery backup // Grid returned","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage Site went dow=
n before Gen started due to poor battery backup // Grid returned","loic.nou=
msi@matech-cameroun.com","547","26-04-2025 15:25:36","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0004889780","C=
harles-Atangana","IHS_YND_051","26-04-2025 15:16:34","26-04-2025 15:08:26",=
"26-04-2025 15:19:53","Grid Outage, No free MDG to deploy on site // Grid r=
eturn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Grid Outage, No free MDG to deploy on site // Grid return","gaelle.njiof=
ack@matech-cameroun.com","489","26-04-2025 15:16:34","MATECH CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004889762","M=
amch Building","","26-04-2025 15:15:59","26-04-2025 15:08:26","26-04-2025 1=
5:18:53","No power issue site on grid with U=3D54v Notice that site is impa=
cted by Charles Atangana","Mboua Thierry","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid Outage, No free MDG to deploy on site /=
/ Grid return","gaelle.njiofack@matech-cameroun.com","284105","26-04-2025 1=
5:15:59","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004889750","M=
essassi okolo","","26-04-2025 15:13:58","26-04-2025 15:02:50","26-04-2025 1=
5:34:14","ACTIVE//No power issue on site Ubaie=3D54.4V, site on Grid The TX=
 Fme Synphorien 691316854 of Huawei is informed.Noticed impacted by pont em=
mana","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equip=
ment Failure","Affected by 3rd Party Site","ACTIVE//No power issue on site =
Ubaie=3D54.4V, site on Grid The TX Fme Synphorien 691316854 of Huawei is in=
formed.Noticed impacted by pont emmana","gaelle.njiofack@matech-cameroun.co=
m","670","26-04-2025 15:13:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004889736","OLAMA","=
","26-04-2025 15:12:25","26-04-2025 14:34:00","26-04-2025 14:40:00","Cascad=
ed Incident from TTO5002646","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Impacted by NGOUMOU wich is not manage by IHS"=
,"system","365299","26-04-2025 15:12:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_004","NOCINC0004889721","Av Kenne=
dy","","26-04-2025 15:09:55","26-04-2025 14:34:00","26-04-2025 14:40:00","C=
ascaded Incident from TTO5002646","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Cascaded Incident from TTO5002646","system","365299"=
,"26-04-2025 15:09:55","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004889704","B=
arriere","","26-04-2025 15:08:56","26-04-2025 15:05:49","26-04-2025 16:58:4=
3","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed //Grid return","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and c=
onfirmed //Grid return","kouoh.jean@ihstowers.com","188","26-04-2025 15:08:=
56","MATECH CMR"
"Closed Complete","Site Down","T0470","IHS_YND_022","NOCINC0004889629","Mvo=
g Ada","","26-04-2025 15:01:44","26-04-2025 14:43:34","26-04-2025 21:25:50"=
,"Grid outage, No space to deploy a MG // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","
Grid outage, No space to deploy a MG // Grid return
","loic.noumsi@matech-cameroun.com","1090","26-04-2025 15:01:44","MATECH CM=
R"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004889466","Ako=
no","IHS_YND_687, IHS_YND_004","26-04-2025 14:40:08","26-04-2025 14:34:00",=
"26-04-2025 18:01:00","Impacted by NGOUMOU wich is not manage by IHS","Fand=
a Brice","Customer Equipment Failure","Active","Active Equipment Failure","=
Affected by 3rd Party Site","Impacted by NGOUMOU wich is not manage by IHS"=
,"gaelle.njiofack@matech-cameroun.com","369","26-04-2025 14:40:08","MATECH =
CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0004889434","Av-=
Germaine","","26-04-2025 14:38:33","26-04-2025 14:34:17","26-04-2025 18:58:=
03","Grid-only; No space to deploy a MG // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid-only; No space to =
deploy a MG // Grid return","gaelle.njiofack@matech-cameroun.com","257","26=
-04-2025 14:38:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004889363","Omnispor=
t-Rail","","26-04-2025 14:28:56","26-04-2025 13:37:50","27-04-2025 02:30:33=
","Cascaded Incident from TTO5002459","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Meter burnt, site went down due=
 to gen Overload(20KVA,270A) // Load Reduced","system","333160","26-04-2025=
 14:28:56","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004889325","M=
essassi 2","","26-04-2025 14:18:39","26-04-2025 14:13:24","26-04-2025 16:49=
:56","Site went down because 04/06 rectifiers dysfuncionned// He reset rect=
ifiers, site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down because 04/06 rectifiers dysfuncion=
ned// He reset rectifiers, site on Gen","vanel.mbiada@matech-cameroun.com",=
"317","26-04-2025 14:18:39","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0004889248","A=
battoir","","26-04-2025 14:06:48","26-04-2025 14:03:57","26-04-2025 18:04:2=
3","Grid outage, Main Generator faulty // Grid return","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outag=
e, Main Generator faulty // Grid return","vanel.mbiada@matech-cameroun.com"=
,"172","26-04-2025 14:06:48","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004889229","E=
lig-Edzoa","","26-04-2025 14:01:37","26-04-2025 13:10:14","26-04-2025 18:56=
:42","GRID ONLY, Grid outage, No MG to deploy on site // Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","GRID ONLY=
, Grid outage, No MG to deploy on site // Grid return","vanel.mbiada@matech=
-cameroun.com","3085","26-04-2025 14:01:37","MATECH CMR"
"Closed Complete","Site Down","T0460","IHS_YND_201","NOCINC0004889219","Cit=
e Verte","","26-04-2025 13:59:50","26-04-2025 13:50:45","26-04-2025 15:34:4=
1","Fme Yamen is informed and reported No space to deploy a MG // Grid retu=
rned","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Fme Yamen is informed and reported No space to deploy a MG // Grid return=
ed","cedric.tiani@matech-cameroun.com","546","26-04-2025 13:59:50","MATECH =
CMR"
"Closed Complete","Site Down","T1556","IHS_YND_182","NOCINC0004889206","Tit=
i Garage","","26-04-2025 13:57:03","26-04-2025 13:31:49","26-04-2025 23:28:=
46","Active//No power issue on site U=3D51.5 V site on Grid The TX FME Arma=
nd // 691144412 from Huawei is informed.","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site U=3D51.5 V site on Grid The TX FME Armand // 691=
144412 from Huawei is informed.","cedric.tiani@matech-cameroun.com","1515",=
"26-04-2025 13:57:03","MATECH CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0004889117","Ngo=
usso MTN","IHS_YND_187","26-04-2025 13:45:07","26-04-2025 13:32:57","26-04-=
2025 19:02:55","Grid outage, not access to deploy mobile gen//Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage, not access to deploy mobile gen//Grid return","cedric.tiani@matech=
-cameroun.com","731","26-04-2025 13:45:07","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004889114","Eke=
kam","","26-04-2025 13:44:07","26-04-2025 13:39:16","26-04-2025 14:11:35","=
Grid outage, site went down due to high temperature impacted to the muffler=
 being pierced, // Water added in the radiator and Gen started manually","T=
IENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Hi=
gh Engine Temp - Coolant Level Issue","Grid outage, site went down due to h=
igh temperature impacted to the muffler being pierced, // Water added in th=
e radiator and Gen started manually","cedric.tiani@matech-cameroun.com","29=
2","26-04-2025 13:44:07","MATECH CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004889109","MAN=
GUIERS CHAPELLE","IHS_YND_506","26-04-2025 13:42:43","26-04-2025 13:37:50",=
"27-04-2025 02:33:13","Meter burnt, site went down due to gen Overload(20KV=
A,270A) // Load Reduced","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Meter burnt, site went down due to gen Overload(=
20KVA,270A) // Load Reduced","cedric.tiani@matech-cameroun.com","294","26-0=
4-2025 13:42:43","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004889103","NTE=
MASSI","","26-04-2025 13:41:19","26-04-2025 13:32:57","26-04-2025 19:02:55"=
,"","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Grid outage, not access to deploy mobile gen//Grid return","cedri=
c.tiani@matech-cameroun.com","289844","26-04-2025 13:41:19","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004889005","Nlo=
ngkak","","26-04-2025 13:35:33","26-04-2025 13:32:13","26-04-2025 13:38:20"=
,"Grid outage, Site down due to poor battery backup // Gen start automatica=
lly","Delor Telezing","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, Site down due to poor battery backup //=
 Gen start automatically","cedric.tiani@matech-cameroun.com","201","26-04-2=
025 13:35:33","MATECH CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0004888997","Mba=
lla 4","","26-04-2025 13:33:36","26-04-2025 13:31:26","26-04-2025 13:40:40"=
,"Running ticket","Delor Telezing","Incorrectly Logged Tickets","Error","Er=
ror","Error","Running ticket","cedric.tiani@matech-cameroun.com","130","26-=
04-2025 13:33:36","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004888987","M=
essa-Carriere OCM","","26-04-2025 13:32:16","26-04-2025 13:16:03","26-04-20=
25 15:31:19","GRID ONLY, LL refuses to deploy Gen  due to noise  SS IHS Pas=
caline is confirm // Grid return","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","GRID ONLY, LL refuses to deploy Gen  due to n=
oise  SS IHS Pascaline is confirm // Grid return","vanel.mbiada@matech-came=
roun.com","974","26-04-2025 13:32:16","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004888985","Nsi=
malen MTN","","26-04-2025 13:31:46","26-04-2025 13:00:22","26-04-2025 14:08=
:12","Site went down because generator circuit-breaker tripped due to a sho=
rt-circuit // CB rearmed","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Circuit Breaker Tripped","Site went down because generator cir=
cuit-breaker tripped due to a short-circuit // CB rearmed","cedric.tiani@ma=
tech-cameroun.com","1884","26-04-2025 13:31:46","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004888890","H=
-General-Yde","","26-04-2025 13:18:39","26-04-2025 13:05:23","26-04-2025 23=
:29:27","No power issue site on grid with Ubay:54.4V Symphorien /691316854 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with Ubay:54.4V Symphorien /691316854 from Huawei is informed","vanel=
.mbiada@matech-cameroun.com","797","26-04-2025 13:18:39","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004888711","N=
koabang Ebolmedjock","","26-04-2025 13:02:51","26-04-2025 12:59:40","26-04-=
2025 13:10:50","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matec=
h-cameroun.com","192","26-04-2025 13:02:51","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0004888677","N=
simalen OCM","","26-04-2025 12:56:38","26-04-2025 12:54:12","26-04-2025 14:=
55:28","site impacted by NSIMALEN MTN (Site went down because generator cir=
cuit-breaker tripped due to a short-circuit // CB rearmed)","Albran Byorel"=
,"Equipment Repair","Passive","Control Panel","Circuit Breaker Tripped","si=
te impacted by NSIMALEN MTN (Site went down because generator circuit-break=
er tripped due to a short-circuit // CB rearmed)","vanel.mbiada@matech-came=
roun.com","147","26-04-2025 12:56:38","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004888655","Cit=
e des nations","","26-04-2025 12:52:16","26-04-2025 12:50:06","26-04-2025 1=
2:56:09","Grid outage,site went down before Gen started due to Poor battery=
 backup//Gen automatically started","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage,site went do=
wn before Gen started due to Poor battery backup//Gen automatically started=
","cedric.tiani@matech-cameroun.com","131","26-04-2025 12:52:16","MATECH CM=
R"
"Closed Complete","Site Down","T1739","IHS_YND_691","NOCINC0004888642","Mba=
lla 2 REGIE","","26-04-2025 12:49:44","26-04-2025 12:19:35","26-04-2025 13:=
39:32","Grid outage,Site went down because Gen failed to start due to charg=
er static hs // He started Gen manualy with external battery","Delor Telezi=
ng","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator","G=
rid outage,Site went down because Gen failed to start due to charger static=
 hs // He started Gen manualy with external battery","cedric.tiani@matech-c=
ameroun.com","1809","26-04-2025 12:49:44","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004888567","Mam=
bine","","26-04-2025 12:36:22","26-04-2025 12:33:07","26-04-2025 13:02:51",=
"Grid outage site went down because Gen failed to start due to Hybride syst=
em dysfonction // He reset the hybrid system and Gen manually started","Fan=
da Brice","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid outag=
e site went down because Gen failed to start due to Hybride system dysfonct=
ion // He reset the hybrid system and Gen manually started","cedric.tiani@m=
atech-cameroun.com","196","26-04-2025 12:36:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004888504","MEHANDAN=
","","26-04-2025 12:25:04","26-04-2025 12:19:31","26-04-2025 12:24:15","Cas=
caded Incident from TTO5001517","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,site went down because GE=
N failed to start due to ATS and Gen card faulty // grid returned","system"=
,"333","26-04-2025 12:25:04","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004888489","Odz=
a II OCM","IHS_YND_528","26-04-2025 12:22:41","26-04-2025 12:19:31","26-04-=
2025 12:24:54","Grid outage ,site went down because GEN failed to start due=
 to ATS and Gen card faulty // grid returned","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went d=
own because GEN failed to start due to ATS and Gen card faulty // grid retu=
rned","cedric.tiani@matech-cameroun.com","192","26-04-2025 12:22:41","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004888355","Carrefou=
r Ayissi Ele","","26-04-2025 11:59:39","26-04-2025 11:55:40","26-04-2025 12=
:14:13","Cascaded Incident from TTO5001356","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage,site went down=
 because Gen failed to start due to fuse that supplies the AV Generator Boa=
rd was untightend//He tightened tthe fuse and started the gen manually","sy=
stem","266731","26-04-2025 11:59:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0004888356","Nkol-Meb=
anga","","26-04-2025 11:59:39","26-04-2025 11:55:40","26-04-2025 12:14:13",=
"Cascaded Incident from TTO5001356","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,site went down because=
 Gen failed to start due to fuse that supplies the AV Generator Board was u=
ntightend//He tightened tthe fuse and started the gen manually","system","2=
66731","26-04-2025 11:59:39","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004888345","Saa=
","IHS_YND_810, IHS_YND_809","26-04-2025 11:57:54","26-04-2025 11:55:40","2=
6-04-2025 12:14:13","Grid outage,site went down because Gen failed to start=
 due to fuse that supplies the AV Generator Board was untightend//He tighte=
ned tthe fuse and started the gen manually","Parker Tchoup","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Kick Starter","Grid outage,site went down =
because Gen failed to start due to fuse that supplies the AV Generator Boar=
d was untightend//He tightened tthe fuse and started the gen manually","ced=
ric.tiani@matech-cameroun.com","135","26-04-2025 11:57:54","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0004888312","M=
anguier","","26-04-2025 11:50:21","26-04-2025 11:44:49","26-04-2025 12:11:0=
6","Grid outage,gen failed to start due to alarm undervoltage // he reseted=
 it and started the gen","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage,gen failed to start due to alar=
m undervoltage // he reseted it and started the gen","vanel.mbiada@matech-c=
ameroun.com","333","26-04-2025 11:50:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_111","NOCINC0004888289","Essos Ma=
rche","","26-04-2025 11:45:35","26-04-2025 11:25:59","26-04-2025 15:14:39",=
"Cascaded Incident from TTO5001241","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down becaus=
e faulty circuit breaker AC due to high temp on site  // he replaced the AC=
 and started the Gen manually","system","290365","26-04-2025 11:45:35","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004888246","Entree C=
ite Verte","","26-04-2025 11:36:28","26-04-2025 11:17:05","26-04-2025 15:02=
:27","Cascaded Incident from TTO5001174","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid only, Grid outage // MG de=
ployed","system","276546","26-04-2025 11:36:28","MATECH CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0004888242","Cam=
p-Sonel","IHS_YND_111, IHS_YND_108, IHS_YND_109","26-04-2025 11:35:09","26-=
04-2025 11:25:59","26-04-2025 15:14:39","Grid outage,site went down because=
 faulty circuit breaker AC due to high temp on site  // he replaced the AC =
and started the Gen manually","Siligap Boris","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Circuit Breaker Issue","Grid outage,site w=
ent down because faulty circuit breaker AC due to high temp on site  // he =
replaced the AC and started the Gen manually","cedric.tiani@matech-cameroun=
.com","551","26-04-2025 11:35:09","MATECH CMR"
"Closed Complete","Site Down","T0836","IHS_YND_109","NOCINC0004888229","Mob=
il-Essos","","26-04-2025 11:34:03","26-04-2025 11:25:59","26-04-2025 15:14:=
39","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid outage,site went down because faulty circuit breaker AC du=
e to high temp on site  // he replaced the AC and started the Gen manually"=
,"cedric.tiani@matech-cameroun.com","290364","26-04-2025 11:34:03","MATECH =
CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0004888222","RUE=
 FOE","","26-04-2025 11:31:29","26-04-2025 11:25:59","26-04-2025 15:15:32",=
"Site impacted by CAMP Sonel","Delor Telezing","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site impacted by CAMP Sonel","cedric.ti=
ani@matech-cameroun.com","290364","26-04-2025 11:31:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0004888189","Bastos-N=
ylon","","26-04-2025 11:25:16","26-04-2025 11:17:05","26-04-2025 15:02:27",=
"Cascaded Incident from TTO5001146","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid only, Grid outage // MG deplo=
yed","system","276544","26-04-2025 11:25:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004888188","Nkomkana=
","","26-04-2025 11:25:16","26-04-2025 11:17:05","26-04-2025 15:02:27","Cas=
caded Incident from TTO5001146","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid only, Grid outage // MG deployed","system","27=
6544","26-04-2025 11:25:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004888190","Bastos B=
ethesda","","26-04-2025 11:25:16","26-04-2025 11:17:05","26-04-2025 15:02:2=
7","Cascaded Incident from TTO5001146 - Cascade Removed From TTO5001146","M=
boua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","Grid only, Grid outage // MG deployed","system","276546","26-04-2025 11:=
25:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0004888187","Cite-Ver=
te","IHS_YND_220, IHS_YND_138, IHS_YND_200, IHS_YND_126, IHS_YND_563, IHS_Y=
ND_127, IHS_YND_543","26-04-2025 11:25:15","26-04-2025 11:17:05","26-04-202=
5 15:02:27","Grid only, Grid outage // MG deployed","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid only, Grid outage // M=
G deployed","system","490","26-04-2025 11:25:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004888186","Golf Qua=
ter","","26-04-2025 11:25:15","26-04-2025 11:17:05","26-04-2025 15:02:27","=
Cascaded Incident from TTO5001146","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid only, Grid outage // MG deploy=
ed","system","276545","26-04-2025 11:25:15","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004888161","N=
komkana 2","","26-04-2025 11:22:16","26-04-2025 11:17:05","26-04-2025 15:02=
:27","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid only, Grid outage // MG deployed","vanel.mbiada@matech-ca=
meroun.com","276545","26-04-2025 11:22:16","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004888152","T=
singa","","26-04-2025 11:20:31","26-04-2025 11:17:05","26-04-2025 15:02:27"=
,"fme is informed ETA : 13:00 PM","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid only, Grid outage // MG deploye=
d","vanel.mbiada@matech-cameroun.com","276544","26-04-2025 11:20:31","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0004888117","Mbankolo=
 petit paris","","26-04-2025 11:13:16","26-04-2025 11:05:58","26-04-2025 13=
:24:19","Cascaded Incident from TTO5001092","Mboua Thierry","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid ou","system","438","2=
6-04-2025 11:13:16","MATECH CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0004888090","A=
FEME NORD","IHS_YND_808","26-04-2025 11:10:10","26-04-2025 11:05:58","26-04=
-2025 16:06:35","Site went down due to configuring and checking the automat=
ion // End of work","TIENTCHEU NZETCHIEU GAEL","Equipment Replacement","Pas=
sive","Planned Activity","Planned Activity - Passive","Site went down due t=
o configuring and checking the automation // End of work","vanel.mbiada@mat=
ech-cameroun.com","252","26-04-2025 11:10:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004888020","Omnispor=
t-Rail","","26-04-2025 10:55:14","26-04-2025 10:39:02","26-04-2025 11:00:15=
","Cascaded Incident from TTO5000926","Delor Telezing","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue on site ,si=
te on Grid with Ubaie=3D53.6 V The Tx FME Armand Nguetsa//699949553 from Hu=
awei is informed","system","264274","26-04-2025 10:55:14","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004887979","M=
ANGUIERS CHAPELLE","IHS_YND_506","26-04-2025 10:48:10","26-04-2025 10:39:02=
","26-04-2025 11:00:15","Active//No power issue on site ,site on Grid with =
Ubaie=3D53.6 V The Tx FME Armand Nguetsa//699949553 from Huawei is informed=
","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active//No power issue on site ,site on Gri=
d with Ubaie=3D53.6 V The Tx FME Armand Nguetsa//699949553 from Huawei is i=
nformed","cedric.tiani@matech-cameroun.com","549","26-04-2025 10:48:10","MA=
TECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004887837","NTE=
MASSI","","26-04-2025 10:34:16","26-04-2025 09:45:04","26-04-2025 11:21:02"=
,"Grid fluctuation,site went down because Gen failed to start due to Grid b=
ad voltage due to lack of 02 phasee//He made a bridge with the Goood phase"=
,"Delor Telezing","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation,site went down because Gen failed to star=
t due to Grid bad voltage due to lack of 02 phasee//He made a bridge with t=
he Goood phase","cedric.tiani@matech-cameroun.com","2953","26-04-2025 10:34=
:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0004887740","Mamch Bu=
ilding","","26-04-2025 10:21:02","26-04-2025 10:17:41","26-04-2025 11:54:47=
","Cascaded Incident from TTO5000646","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","	Grid outage //Grid restored.","=
system","1222222","26-04-2025 10:21:02","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0004887739","C=
harles-Atangana","IHS_YND_051","26-04-2025 10:20:18","26-04-2025 10:17:41",=
"26-04-2025 13:18:03","	Grid outage //Grid restored.","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","	Grid outage //Grid resto=
red.","vanel.mbiada@matech-cameroun.com","158","26-04-2025 10:20:18","MATEC=
H CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004887485","Eko=
umdoum OCM","","26-04-2025 10:05:54","26-04-2025 10:03:47","26-04-2025 11:5=
9:11","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS =
Pascaline is informed and confirmed//Grid return","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, sit=
e went down due to Gen overload(20kva,280 A) IHS SS Pascaline is informed a=
nd confirmed//Grid return","cedric.tiani@matech-cameroun.com","128","26-04-=
2025 10:05:54","MATECH CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0004887308","Fou=
da rue des g=E9n=E9raux","","26-04-2025 09:38:20","26-04-2025 09:36:59","26=
-04-2025 11:33:21","Grid outage, Site went down because Gen failed to start=
 due to battery Gen faulty// He started Gen with external battery","Delor T=
elezing","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery"=
,"Grid outage, Site went down because Gen failed to start due to battery Ge=
n faulty// He started Gen with external battery","cedric.tiani@matech-camer=
oun.com","82","26-04-2025 09:38:20","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004887259","E=
MANA BILICK CITY","","26-04-2025 09:27:03","26-04-2025 09:21:23","26-04-202=
5 19:13:52","Grid outage site went down due to main gen faulty  // Grid ret=
urn","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Faulty","Grid outage site went down due to main gen faulty  // Grid r=
eturn","vanel.mbiada@matech-cameroun.com","342","26-04-2025 09:27:03","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004887247","Elig Edz=
oa","","26-04-2025 09:25:27","26-04-2025 09:19:59","26-04-2025 09:56:42","C=
ascaded Incident from TTO5000074 - Cascade Removed From TTO5000074","Delor =
Telezing","Cascade Outage","Passive","Cascade Passive","Cascade Passive","S=
ite went down due to PWC Overload (12k//250A) SS HIS Blaise is informed //H=
e reduced the load and site on Gen","system","276351","26-04-2025 09:25:27"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004887237","E=
lig-Edzoa","","26-04-2025 09:24:06","26-04-2025 09:19:59","26-04-2025 09:56=
:42","Grid only, No space to deploy MDG awaiting Grid restoration","","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","Site went down d=
ue to PWC Overload (12k//250A) SS HIS Blaise is informed //He reduced the l=
oad and site on Gen","vanel.mbiada@matech-cameroun.com","276351","26-04-202=
5 09:24:06","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004887223","Nta=
ba","IHS_YND_133, IHS_YND_504","26-04-2025 09:21:13","26-04-2025 09:19:59",=
"26-04-2025 10:01:26","Site went down due to PWC Overload (12k//250A) SS HI=
S Blaise is informed //He reduced the load and site on Gen","Delor Telezing=
","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","S=
ite went down due to PWC Overload (12k//250A) SS HIS Blaise is informed //H=
e reduced the load and site on Gen","cedric.tiani@matech-cameroun.com","75"=
,"26-04-2025 09:21:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004887188","Omnispor=
t-Rail","","26-04-2025 09:16:13","26-04-2025 08:36:27","26-04-2025 10:17:09=
","Cascaded Incident from TTO4999768","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because ENEO MET=
ER burnt on site //site on Gen","system","271524","26-04-2025 09:16:13","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004887173","M=
vog-Ada_OCM","","26-04-2025 09:14:30","26-04-2025 09:07:01","26-04-2025 19:=
03:29"," Grid outage, No space to deploy a MG // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","
Grid outage, No space to deploy a MG // Grid return
","vanel.mbiada@matech-cameroun.com","450","26-04-2025 09:14:30","MATECH CM=
R"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004887050","E=
kombitie","","26-04-2025 08:59:21","26-04-2025 08:57:12","26-04-2025 09:00:=
20","Active: no power issue, site is on Gen with Ubaie=3D54.5V, Symphorien(=
650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue, site is on Gen with Ubaie=3D54.5V, Symphorien(650257151/ huawei)=
 is informed","vanel.mbiada@matech-cameroun.com","131","26-04-2025 08:59:21=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004887042","Emana Ly=
cee","","26-04-2025 08:58:12","26-04-2025 08:56:16","26-04-2025 09:12:07","=
Cascaded Incident from TTO4999854","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation,site went down b=
ecause Gen failed to start due to Grid bad voltage//Grid return","system","=
371248","26-04-2025 08:58:13","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004887035","E=
mana lycee 2","IHS_YND_274","26-04-2025 08:57:31","26-04-2025 08:56:16","26=
-04-2025 09:12:07","Grid fluctuation,site went down because Gen failed to s=
tart due to Grid bad voltage//Grid return","Fabrice Pouakam","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid fluctuation,site=
 went down because Gen failed to start due to Grid bad voltage//Grid return=
","vanel.mbiada@matech-cameroun.com","77","26-04-2025 08:57:31","MATECH CMR=
"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004887033","Mes=
sassi 2","","26-04-2025 08:56:48","26-04-2025 08:55:40","26-04-2025 09:06:5=
5","Site went down because 02/06 rectifiers dysfuncionned// He reset rectif=
iers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down because 02/06 rectifiers dysfuncionned// He reset =
rectifiers","cedric.tiani@matech-cameroun.com","69","26-04-2025 08:56:48","=
MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004887016","Odz=
a petit marche new","","26-04-2025 08:52:15","26-04-2025 08:46:03","26-04-2=
025 09:27:03","Site went down due to 01/03 rectifiers dysfunctionning on si=
te//he reset it and site on Grid","Albran Byorel","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to 01/03 rectifiers =
dysfunctionning on site//he reset it and site on Grid","cedric.tiani@matech=
-cameroun.com","373","26-04-2025 08:52:15","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004886963","M=
ANGUIERS CHAPELLE","IHS_YND_506","26-04-2025 08:39:45","26-04-2025 08:36:27=
","26-04-2025 10:23:09","Site went down because ENEO METER burnt on site //=
site on Gen","Fabrice Pouakam","Fire on Site","Passive","Infrastructure","F=
ire - Burned","Site went down because ENEO METER burnt on site //site on Ge=
n","vanel.mbiada@matech-cameroun.com","200","26-04-2025 08:39:45","MATECH C=
MR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004886945","C=
omplexe-BEAC","","26-04-2025 08:36:39","26-04-2025 08:33:29","26-04-2025 08=
:37:47","Grid outage,Site went down because main gen faulty//Grid return","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fa=
ulty","Grid outage,Site went down because main gen faulty//Grid return","va=
nel.mbiada@matech-cameroun.com","191","26-04-2025 08:36:39","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004886944","Eko=
umdoum OCM","","26-04-2025 08:36:33","26-04-2025 08:34:25","26-04-2025 09:3=
9:38","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS =
Pascaline is informed and confirmed//Grid return","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went do=
wn due to Gen overload(20kva,280 A) IHS SS Pascaline is informed and confir=
med//Grid return","cedric.tiani@matech-cameroun.com","129","26-04-2025 08:3=
6:33","MATECH CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004886862","L=
eboudi","","26-04-2025 08:23:37","26-04-2025 08:19:10","26-04-2025 09:01:46=
","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Grid outage,site went down because Gen failed to start=
 due to automatism dysfunction(configuration to be normalised)//Gen manuall=
y started","vanel.mbiada@matech-cameroun.com","1222137","26-04-2025 08:23:3=
7","MATECH CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004886861","Nko=
lafeme","IHS_YND_309","26-04-2025 08:23:36","26-04-2025 08:19:10","26-04-20=
25 09:05:30","Grid outage,site went down because Gen failed to start due to=
 automatism dysfunction(configuration to be normalised)//Gen manually start=
ed","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel"=
,"ATS-AMF Issue","Grid outage,site went down because Gen failed to start du=
e to automatism dysfunction(configuration to be normalised)//Gen manually s=
tarted","cedric.tiani@matech-cameroun.com","267","26-04-2025 08:23:36","MAT=
ECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004886840","Nom=
ayos montee Meche","","26-04-2025 08:18:15","26-04-2025 08:14:00","26-04-20=
25 10:00:07","Grid fluctuation, site went down because gen fails to start d=
ue to grid bad voltage //GEN started manually","Fanda Brice","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
n, site went down because gen fails to start due to grid bad voltage //GEN =
started manually","cedric.tiani@matech-cameroun.com","256","26-04-2025 08:1=
8:15","MATECH CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004886795","Mes=
sa Carriere","","26-04-2025 08:07:57","26-04-2025 08:03:49","26-04-2025 09:=
33:26","Grid outage,site went down because Gen failed to start because Gen =
CARD was not on automatic mode//He started manually(investigation ongoing) =
","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid outage,site went down because Gen failed to start because Gen C=
ARD was not on automatic mode//He started manually(investigation ongoing) "=
,"cedric.tiani@matech-cameroun.com","249","26-04-2025 08:07:57","MATECH CMR=
"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004886779","c=
hina embassy yde","","26-04-2025 08:04:30","26-04-2025 08:00:36","26-04-202=
5 09:51:15","Active//No power issue site on grid with U=3D52.4V The Tx FME =
Eloundou Bertrand from Huawei is informed","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power =
issue site on grid with U=3D52.4V The Tx FME Eloundou Bertrand from Huawei =
is informed","vanel.mbiada@matech-cameroun.com","235","26-04-2025 08:04:30"=
,"MATECH CMR"
"Closed Complete","Warning","T1071","IHS_YND_343","NOCINC0004886753","Mbedo=
umou - Ekali","","26-04-2025 07:56:56","","","Site alarm due to grid bad vo=
ltage//He manually started the Gen","Albran Byorel","Warning","Warning","PO=
WER","Warning - National Grid - Grid Incomplete Phase","Site alarm due to g=
rid bad voltage//He manually started the Gen","cedric.tiani@matech-cameroun=
.com","610","26-04-2025 07:56:56","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004886751","N=
koabang Ebolmedjock","","26-04-2025 07:56:02","26-04-2025 07:51:43","26-04-=
2025 08:10:47","Grid outage, gen start and stopped with alarm 'High temp' /=
/ He added water  site on gen","Mba Lazare Herve","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage=
, gen start and stopped with alarm 'High temp' // He added water  site on g=
en","vanel.mbiada@matech-cameroun.com","260","26-04-2025 07:56:02","MATECH =
CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004886743","S=
atcom","","26-04-2025 07:54:23","26-04-2025 07:49:18","26-04-2025 08:00:20"=
,"	Active // No power issue site on Grid with U=3D53,02 V Tx Fme Armand Nge=
stsa (691144412) of huawei is informed","Delor Telezing","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Activ=
e // No power issue site on Grid with U=3D53,02 V Tx Fme Armand Ngestsa (69=
1144412) of huawei is informed","vanel.mbiada@matech-cameroun.com","305","2=
6-04-2025 07:54:23","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004886698","B=
arriere","","26-04-2025 07:42:13","26-04-2025 07:36:07","26-04-2025 14:58:0=
1","GEN OVERLOAD","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage, Site went down because Gen overload(20kva,4=
00 A) IHS SS Felix Zambe is informed and confirmed //Grid return","vanel.mb=
iada@matech-cameroun.com","367","26-04-2025 07:42:13","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004886623","E=
koumdoum","","26-04-2025 07:23:31","26-04-2025 07:20:17","26-04-2025 08:26:=
18","Grid outage, site went down due to rectifier issue // He reseted it","=
Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Grid outage, site went down due to rectifier issue // He reseted it","vane=
l.mbiada@matech-cameroun.com","195","26-04-2025 07:23:31","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004886621","H=
-General-Yde","","26-04-2025 07:22:17","26-04-2025 07:18:32","26-04-2025 10=
:35:23","No power issue site on grid with Ubay:54.4V Symphorien /691316854 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with Ubay:54.4V Symphorien /691316854 from Huawei is informed","vanel=
.mbiada@matech-cameroun.com","226","26-04-2025 07:22:17","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004886384","Nsi=
malen MTN","","26-04-2025 06:25:55","26-04-2025 06:19:40","26-04-2025 07:41=
:17","Site went down because electrical transformer of the Quarter explodes=
 and created an overvoltage that disjunted all the CB in PWC//He rearmed an=
d site on Gen","Albran Byorel","Equipment Repair","Passive","Rectifier","Re=
ctifier - Circuit Breaker","Site went down because electrical transformer o=
f the Quarter explodes and created an overvoltage that disjunted all the CB=
 in PWC//He rearmed and site on Gen","franck.nkomot@matech-cameroun.com","3=
76","26-04-2025 06:25:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0004886362","NGONA","=
","26-04-2025 06:18:22","26-04-2025 06:07:41","26-04-2025 06:13:41","Cascad=
ed Incident from TTO4999062","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubaie=3D54.4 V sit=
e on grid , TTx FME Eloudou//693212405 from Huawei is informed","system","2=
66196","26-04-2025 06:18:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_792","NOCINC0004886364","NKOABANG=
 NKOLO 3","","26-04-2025 06:18:22","26-04-2025 06:07:41","26-04-2025 06:13:=
41","Cascaded Incident from TTO4999062","Mba Lazare Herve","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
=3D54.4 V site on grid , TTx FME Eloudou//693212405 from Huawei is informed=
","system","266196","26-04-2025 06:18:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0004886363","Nkoabang=
2","","26-04-2025 06:18:22","26-04-2025 06:07:41","26-04-2025 06:13:41","Ca=
scaded Incident from TTO4999062","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site Ubaie=3D54.4 V=
 site on grid , TTx FME Eloudou//693212405 from Huawei is informed","system=
","266197","26-04-2025 06:18:22","MATECH CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004886340","Nko=
abang entree carriere","IHS_YND_295, IHS_YND_526, IHS_YND_792","26-04-2025 =
06:10:46","26-04-2025 06:07:41","26-04-2025 06:13:41","No power issue on si=
te Ubaie=3D54.4 V site on grid , TTx FME Eloudou//693212405 from Huawei is =
informed","Mba Lazare Herve","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie=3D54.=
4 V site on grid , TTx FME Eloudou//693212405 from Huawei is informed","fra=
nck.nkomot@matech-cameroun.com","186","26-04-2025 06:10:46","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0004886071","O=
lembe","","26-04-2025 05:15:37","26-04-2025 05:10:30","26-04-2025 05:51:30"=
,"Grid outage, gen failed to start due to card Ge Dysfunctionning // We res=
eted card GE and gen manually started","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, gen failed to st=
art due to card Ge Dysfunctionning // We reseted card GE and gen manually s=
tarted","christelle.ngonga@matech-cameroun.com","309","26-04-2025 05:15:37"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004885637","H=
-General-Yde","","26-04-2025 03:38:36","26-04-2025 03:32:27","26-04-2025 03=
:40:14","No power issue site on grid with Ubay:54.4V Symphorien /691316854 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with Ubay:54.6V Symphorien /691316854 from Huawei is informed","chris=
telle.ngonga@matech-cameroun.com","370","26-04-2025 03:38:36","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004885526","E=
kombitie","","26-04-2025 03:13:32","26-04-2025 03:10:24","26-04-2025 03:21:=
04","Active: no power issue, site is on Gen with Ubaie=3D 49.8V, Symphorien=
(650257151) from huawei is informed","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
no power issue, site is on Gen with Ubaie=3D 49.8V, Symphorien(650257151) f=
rom huawei is informed","christelle.ngonga@matech-cameroun.com","189","26-0=
4-2025 03:13:32","MATECH CMR"
"Closed Complete","Warning","","IHS_YND_365","NOCINC0004885367","Akono","",=
"26-04-2025 02:36:37","","","Gen  automaticaly started","Fanda Brice","Warn=
ing","Warning","POWER","Warning - Site on Battery","Gen  automaticaly start=
ed","christelle.ngonga@matech-cameroun.com","7931","26-04-2025 02:36:37","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004885361","M=
bankomo IHS","","26-04-2025 02:34:39","26-04-2025 02:24:33","26-04-2025 02:=
49:44","Site went down due to (02/02) rectifiers dysfunction // He reset it=
 and site on Grid","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to (02/02) rectifiers dysfunction // =
He reset it and site on Grid","franck.nkomot@matech-cameroun.com","3646","2=
6-04-2025 02:34:39","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004885319","Mok=
olo Yaounde","","26-04-2025 02:16:07","26-04-2025 02:10:45","26-04-2025 02:=
16:45","No power issue U =3D53V site on grid. The Tx FME Eloundou Bertrand =
(693212405) from Huawei is informed","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D53V=
 site on grid. The Tx FME Eloundou Bertrand (693212405) from Huawei is info=
rmed","franck.nkomot@matech-cameroun.com","323","26-04-2025 02:16:07","MATE=
CH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004885256","Eke=
kam","","26-04-2025 02:00:09","26-04-2025 01:21:50","26-04-2025 05:37:50","=
Grid outage gen failed to start due to alarm high temp // We added water an=
d gen manually started. (Note that FME informs us that the generator exhaus=
t pipe is also damaged and needs to be welded))","TIENTCHEU NZETCHIEU GAEL"=
,"Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage gen f=
ailed to start due to alarm high temp // We added water and gen manually st=
arted","franck.nkomot@matech-cameroun.com","9406","26-04-2025 02:00:09","MA=
TECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004885199","NTE=
MASSI","","26-04-2025 01:30:35","26-04-2025 01:01:17","26-04-2025 09:40:05"=
,"access issue at night due to landlord  Site down due to Rectifiers issue =
// he rest it and site on Grid ","Delor Telezing","Access Denial","Lease Or=
 Legal","Landlord Related Issues","Access Issue - Land Lord","access issue =
at night due to landlord  Site down due to Rectifiers issue // he rest it a=
nd site on Grid ","franck.nkomot@matech-cameroun.com","1759","26-04-2025 01=
:30:35","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004885149","Eto=
 koss Yde","","26-04-2025 01:16:15","26-04-2025 01:15:07","26-04-2025 02:13=
:38","Avtive// No power issue, site is on grid with Ubaie=3D51.8V, Fulbert =
(654266068) from Huawei is informed","Fanda Brice","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Avtive// No =
power issue, site is on grid with Ubaie=3D51.8V, Fulbert (654266068) from H=
uawei is informed","franck.nkomot@matech-cameroun.com","70","26-04-2025 01:=
16:15","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004884942","SAA=
 Entrance","","26-04-2025 00:14:12","25-04-2025 23:35:59","26-04-2025 00:18=
:59","Grid outage and site was on Gen. Grid return but site went down becau=
se contactor didn't stick // he pushed the contactor","Parker Tchoup","Grid=
 Supply","Passive","Grid","National Grid - Circuit Breaker","Grid outage an=
d site was on Gen. Grid return but site went down because contactor didn't =
stick // he pushed the contactor","franck.nkomot@matech-cameroun.com","2294=
","26-04-2025 00:14:12","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004884824","MEF=
OU ASSI","","25-04-2025 23:38:35","25-04-2025 23:33:26","26-04-2025 01:19:2=
6","Grid fluctuation,Site went down because Gen failed to start due to Grid=
 bad voltage, on site//He bypassed the Grid and gen manually started","Fand=
a Brice","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation,Site went down because Gen failed to start due to =
Grid bad voltage, on site//He bypassed the Grid and gen manually started","=
franck.nkomot@matech-cameroun.com","311","25-04-2025 23:38:35","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0004884789","ELO=
UMDEM CARRIERE 2","","25-04-2025 23:22:29","25-04-2025 23:16:34","25-04-202=
5 23:36:34","ACTIVE//no power issue Ubaie:54.8V site on Gen, TX fme symphor=
ien (650257151) from huawei is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//=
no power issue Ubaie:54.8V site on Gen, TX fme symphorien (650257151) from =
huawei is informed","franck.nkomot@matech-cameroun.com","357","25-04-2025 2=
3:22:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0004884770","Nkoabang=
2","","25-04-2025 23:15:54","25-04-2025 22:46:51","25-04-2025 23:09:51","Ca=
scaded Incident from TTO4997211","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site Ubaie=3D54.3 V=
 site on grid , TTx FME Eloudou//693212405 from Huawei is informed","system=
","270913","25-04-2025 23:15:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0004884769","Biteng-M=
aetur","","25-04-2025 23:15:54","25-04-2025 22:46:51","25-04-2025 23:09:51"=
,"Cascaded Incident from TTO4997211","Mba Lazare Herve","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue on site Ubaie=3D54=
.3 V site on grid , TTx FME Eloudou//693212405 from Huawei is informed","sy=
stem","270914","25-04-2025 23:15:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0004884771","Biteng",=
"","25-04-2025 23:15:54","25-04-2025 22:46:51","25-04-2025 23:09:51","Casca=
ded Incident from TTO4997211","Mba Lazare Herve","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site Ubaie=3D54.3 V si=
te on grid , TTx FME Eloudou//693212405 from Huawei is informed","system","=
270914","25-04-2025 23:15:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0004884768","NGONA","=
","25-04-2025 23:15:53","25-04-2025 22:46:51","25-04-2025 23:09:51","Cascad=
ed Incident from TTO4997211","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubaie=3D54.3 V sit=
e on grid , TTx FME Eloudou//693212405 from Huawei is informed","system","2=
70915","25-04-2025 23:15:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_792","NOCINC0004884686","NKOABANG=
 NKOLO 3","","25-04-2025 22:56:30","25-04-2025 22:46:51","25-04-2025 23:09:=
51","Cascaded Incident from TTO4997211","Mba Lazare Herve","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
=3D54.3 V site on grid , TTx FME Eloudou//693212405 from Huawei is informed=
","system","270913","25-04-2025 22:56:30","MATECH CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004884683","Nko=
abang entree carriere","IHS_YND_295, IHS_YND_249, IHS_YND_526, IHS_YND_792,=
 IHS_YND_248","25-04-2025 22:55:59","25-04-2025 22:46:51","26-04-2025 00:49=
:51","No power issue on site Ubaie=3D54.3 V site on grid , TTx FME Eloudou/=
/693212405 from Huawei is informed","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site Ubaie=3D54.3 V site on grid , TTx FME Eloudou//693212405 fro=
m Huawei is informed","loic.noumsi@matech-cameroun.com","549","25-04-2025 2=
2:55:59","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004884585","MEF=
OU ASSI","","25-04-2025 22:32:43","25-04-2025 22:26:34","25-04-2025 22:32:3=
9","Grid outage site went down due to Gen failed to start // Grid return","=
Fanda Brice","Grid Supply","Passive","Grid","National Grid - Grid Outage Is=
sue","Grid outage site went down due to Gen failed to start // Grid return"=
,"loic.noumsi@matech-cameroun.com","371","25-04-2025 22:32:43","MATECH CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004884444","MAN=
GUIERS CHAPELLE","","25-04-2025 22:07:49","25-04-2025 21:58:32","25-04-2025=
 22:26:32","Grid outage, site went down due to Gen Overload(20KVA,270) // G=
rid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, site went down due to Gen Overload(20KVA,270) //=
 Grid return","ludivine.ngamaleu@ihstowers.com","559","25-04-2025 22:07:49"=
,"MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004884397","Eto=
 koss Yde","","25-04-2025 22:01:18","25-04-2025 21:45:08","25-04-2025 23:49=
:08","Grid outage, Gen run still fuel shortage // The film tilted the tank.=
 Site on Gen","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid outage, Gen run still fuel shortage // The film tilted the tank. Si=
te on Gen","loic.noumsi@matech-cameroun.com","972","25-04-2025 22:01:18","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004884344","O=
mnisport-Rail","","25-04-2025 21:48:04","25-04-2025 21:22:51","25-04-2025 2=
2:27:18","	Grid outage, site went downdue to Gen overload // reduces the lo=
ad and site on Gen","Delor Telezing","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","	Grid outage, site went downdue to Gen overload // red=
uces the load and site on Gen","gaelle.njiofack@matech-cameroun.com","1514"=
,"25-04-2025 21:48:04","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004884313","SAA=
 Entrance","","25-04-2025 21:38:42","25-04-2025 21:31:32","25-04-2025 22:18=
:26","Grid Gen site and site was on Gen; Grid return but site went down bec=
ause contactor didn't stick // he pushed the contactor","Parker Tchoup","Gr=
id Supply","Passive","Grid","National Grid - Circuit Breaker","Grid Gen sit=
e and site was on Gen; Grid return but site went down because contactor did=
 not stick // he pushed the contactor","loic.noumsi@matech-cameroun.com","4=
32","25-04-2025 21:38:42","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004884297","E=
lig-Edzoa","","25-04-2025 21:35:47","25-04-2025 21:30:26","25-04-2025 22:11=
:20"," Grid only, site went down due to Grid outage // Grid restoration",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"," Grid =
only, site went down due to Grid outage // Grid restoration","gaelle.njiofa=
ck@matech-cameroun.com","322","25-04-2025 21:35:47","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0004884276","EKI=
E","","25-04-2025 21:28:58","25-04-2025 21:20:52","25-04-2025 22:00:19","Si=
te went down because CB of rectifier tripped causing by Grid Overvoltage// =
CB of rectifier put back on ","Albran Byorel","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Site went down because CB of rectifier t=
ripped causing by Grid Overvoltage// CB of rectifier put back on ","loic.no=
umsi@matech-cameroun.com","487","25-04-2025 21:28:58","MATECH CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0004884218","Ngo=
uetou","","25-04-2025 21:18:52","25-04-2025 21:05:46","25-04-2025 22:48:46"=
,"Hybrid Gen, Site was down due to fuel shortage. This site is refueling by=
 Edonde // Site refueled","Parker Tchoup","Fuel Outage","Passive","Diesel",=
"Diesel Outage","Hybrid Gen, Site was down due to fuel shortage. This site =
is refueling by Edonde // Site refueled","loic.noumsi@matech-cameroun.com",=
"1035","25-04-2025 21:18:52","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004884061","Eke=
kam","","25-04-2025 20:54:26","25-04-2025 20:49:12","25-04-2025 22:20:12","=
Grid outage gen failed to start due to alarm high temp // We added water an=
d gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","ACDG Gen","Gen Temp High","Grid outage gen failed to start due to ala=
rm high temp // We added water and gen manually started","loic.noumsi@matec=
h-cameroun.com","315","25-04-2025 20:54:26","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004884021","M=
ontee-Des-Soeurs","","25-04-2025 20:49:34","25-04-2025 20:23:18","26-04-202=
5 02:41:30","No power issue, site is on grid with Ubaie: 54.6V, Mbah hosiah=
(699699694) from Huawei is informed","Hyemafo Gildas","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue, site is on grid with Ubaie: 54.6V, Mbah hosiah(699699694) from Huawe=
i is informed","olivier.kwedi@ihstowers.com","1578","25-04-2025 20:49:34","=
MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0004883874","N=
gousso-Savana","","25-04-2025 20:19:52","25-04-2025 20:06:40","25-04-2025 2=
1:17:26","Site went down because CB(2*125A) disjuncted in the OCM bay due t=
o Gen overload (20KVA,300A) // We rearmed the CB and site on gen ","Siligap=
 Boris","Equipment Repair","Passive","Control Panel","Power Cabinet - Circu=
it Breaker Issue","Site went down because CB(2*125A) disjuncted in the OCM =
bay due to Gen overload (20KVA,300A) // We rearmed the CB and site on gen "=
,"gaelle.njiofack@matech-cameroun.com","793","25-04-2025 20:19:52","MATECH =
CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0004883872","F=
OUGEROLE","","25-04-2025 20:19:12","25-04-2025 20:06:40","25-04-2025 21:17:=
26","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Site went down because CB(2*125A) disjuncted in the OCM bay due=
 to Gen overload (20KVA,300A) // We rearmed the CB and site on gen ","gaell=
e.njiofack@matech-cameroun.com","1964","25-04-2025 20:19:12","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004883868","E=
koumdoum OCM","","25-04-2025 20:18:12","25-04-2025 20:02:04","26-04-2025 08=
:27:46","Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline i=
s informed and confirmed// He reduced the load an manually started GEN","Al=
bran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Sit=
e went down due to Gen overload(20kva,280 A) IHS SS Pascaline is informed a=
nd confirmed// He reduced the load an manually started GEN","gaelle.njiofac=
k@matech-cameroun.com","969","25-04-2025 20:18:12","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004883678","Eto=
ug ebe Carrefour","","25-04-2025 19:55:35","25-04-2025 19:46:06","25-04-202=
5 21:30:43","Grid outage, site went down because gen start and stopped with=
 alarm ""high temp"" // he added water and manually start the Gen	","Hyemaf=
o Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Grid outage, site went down because gen start and s=
topped with alarm ""high temp"" // he added water and manually start the Ge=
n	","ludivine.ngamaleu@ihstowers.com","569","25-04-2025 19:55:35","MATECH C=
MR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0004883626","A=
battoir","","25-04-2025 19:46:37","25-04-2025 19:44:30","25-04-2025 21:30:4=
0","Grid outage, Site down due to STATIC GE HS on site // Fme deployed a mo=
bil GE (20 KVA) on site","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Generator Faulty","Grid outage, Site down due to STATIC GE =
HS on site // Fme deployed a mobil GE on site","gaelle.njiofack@matech-came=
roun.com","128","25-04-2025 19:46:37","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004883591","Nko=
abang2","","25-04-2025 19:41:10","25-04-2025 19:16:54","25-04-2025 20:52:50=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // He reduced the load and gen manually started	","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage, site went down due to gen overload (22KVA, 330A), SS Blaise IHS is =
informed // He reduced the load and gen manually started	","ludivine.ngamal=
eu@ihstowers.com","10886","25-04-2025 19:41:10","MATECH CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0004883414","Omn=
isport-Rail","","25-04-2025 19:10:48","25-04-2025 18:59:41","25-04-2025 20:=
08:57","Grid outage, site went downdue to Gen overload // reduces the load =
and site on Gen","Delor Telezing","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Grid outage, site went downdue to Gen overload // reduces=
 the load and site on Gen","loic.noumsi@matech-cameroun.com","1080","25-04-=
2025 19:10:48","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004883398","M=
bankomo IHS","","25-04-2025 19:07:05","25-04-2025 18:36:41","25-04-2025 19:=
21:47","Grid outage, Gen failed to start due to Card of Gen faulty, // Gene=
rator started manually and generator rectifiers were reset","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
 Gen failed to start due to Card of Gen faulty, // Generator started manual=
ly and generator rectifiers were reset","gaelle.njiofack@matech-cameroun.co=
m","1825","25-04-2025 19:07:05","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004883391","MBA=
LNGONG LYCEE","","25-04-2025 19:05:29","25-04-2025 18:55:20","25-04-2025 21=
:08:20","Grid Outage Site went down due to Gen overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went d=
own due to Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and conf=
irmed // Grid return","loic.noumsi@matech-cameroun.com","611","25-04-2025 1=
9:05:29","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004883387","H=
-General-Yde","","25-04-2025 19:04:37","25-04-2025 18:50:25","25-04-2025 19=
:19:34","Active // No power issue site on grid with Ubay:54.6V Symphorien /=
691316854 from Huawei is informed","Siligap Boris","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No=
 power issue site on grid with Ubay:54.6V Symphorien /691316854 from Huawei=
 is informed","gaelle.njiofack@matech-cameroun.com","853","25-04-2025 19:04=
:37","MATECH CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0004883333","Nke=
ng likok","","25-04-2025 18:53:17","25-04-2025 18:45:08","25-04-2025 19:47:=
36","No power issue on site Ubaie 49.1V site on Gen, (Etienne/+237 6 93 96 =
14 74) from Huawei is informed and managed","Kemeni Franklin","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site Ubaie 49.1V site on Gen, (Etienne/+237 6 93 96 14 74)=
 from Huawei is informed and managed","loic.noumsi@matech-cameroun.com","49=
0","25-04-2025 18:53:17","MATECH CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004883273","Mel=
en Ba'aba","","25-04-2025 18:37:39","25-04-2025 18:13:31","25-04-2025 19:46=
:28","Grid outage, site went down because gen start and stopped with Alarm =
Under frequency // He reset gen card and gen manually started","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,=
 site went down because gen start and stopped with Alarm Under frequency //=
 He reset gen card and gen manually started","loic.noumsi@matech-cameroun.c=
om","1449","25-04-2025 18:37:39","MATECH CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004883183","Mes=
sa Carriere","","25-04-2025 18:16:20","25-04-2025 17:49:06","25-04-2025 18:=
23:01","	Grid outage site went down before Gen start due to poor battery ba=
ckup // Grid reurn","Mboua Thierry","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","	Grid outage site went down before Gen=
 start due to poor battery backup // Grid reurn","loic.noumsi@matech-camero=
un.com","1635","25-04-2025 18:16:20","MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004883150","c=
hina embassy yde","","25-04-2025 18:09:45","25-04-2025 17:44:36","25-04-202=
5 18:21:36","Active//No power issues on Site and Ubaie=3D52.3V The FME TX E=
loundou Bertrand (693 21 24 05) is informed and the site up at =3D03:23PM",=
"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issues on Site and Ubaie=3D52.3V The FME TX=
 Eloundou Bertrand (693 21 24 05) is informed and the site up at =3D03:23PM=
","gaelle.njiofack@matech-cameroun.com","1510","25-04-2025 18:09:45","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004883126","N=
kolfon Cimencam","","25-04-2025 18:07:33","25-04-2025 17:36:46","26-04-2025=
 01:19:56","Active//No power issue on site U=3D54,5v site on Gen The TX fme=
 George(697461814) from huawei is informed. ","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site U=3D54,5v site on Gen The TX fme George(6974=
61814) from huawei is informed. ","gaelle.njiofack@matech-cameroun.com","18=
48","25-04-2025 18:07:33","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004883125","Man=
guiers Dispensaire","","25-04-2025 18:07:27","25-04-2025 18:00:19","25-04-2=
025 18:08:32","Grid fluctuations site went down due to bad grid voltage and=
 no RCP //grid power stabilized","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuations site=
 went down due to bad grid voltage and no RCP //grid power stabilized","loi=
c.noumsi@matech-cameroun.com","429","25-04-2025 18:07:27","MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004883110","Nko=
lmvack","","25-04-2025 18:05:10","25-04-2025 17:55:57","25-04-2025 20:25:31=
","Grid outage, site down due to fuel shortage // Refuelling done","Parker =
Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, site=
 down due to fuel shortage // Refuelling done","loic.noumsi@matech-cameroun=
.com","554","25-04-2025 18:05:10","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004883087","Tam=
tam Weekend","","25-04-2025 18:01:38","25-04-2025 17:38:25","25-04-2025 17:=
40:44","Grid outage, site went down before Gen start due to poor backup // =
Gen automatically started","Hyemafo Gildas","Grid Supply","Passive","Grid",=
"National Grid - Grid Outage Issue","Grid outage, site went down before Gen=
 start due to poor backup // Gen automatically started","loic.noumsi@matech=
-cameroun.com","5429","25-04-2025 18:01:38","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004883067","J=
-Vespa","IHS_YND_544","25-04-2025 17:57:39","25-04-2025 17:34:33","25-04-20=
25 18:13:41","site went down due to Bad eneo voltage (no RCP on site) // Ge=
n started manually	","Mboua Thierry","Grid Supply","Passive","Grid","Nation=
al Grid - Unstable Grid Supply Issue","site went down due to Bad eneo volta=
ge (no RCP on site) // Gen started manually	","gaelle.njiofack@matech-camer=
oun.com","1387","25-04-2025 17:57:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004883026","ELOUMDEM=
 CARRIERE 2","","25-04-2025 17:51:15","25-04-2025 17:35:19","25-04-2025 20:=
22:33","Cascaded Incident from TTO4995210","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
ecause Gen failed to start due to battery Gen faulty// He started Gen with =
external battery","system","275222","25-04-2025 17:51:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004883025","Eto koss=
 Yde","","25-04-2025 17:51:15","25-04-2025 17:35:19","25-04-2025 20:22:33",=
"Cascaded Incident from TTO4995210","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
Gen failed to start due to battery Gen faulty// He started Gen with externa=
l battery","system","275222","25-04-2025 17:51:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004883023","Crf-Mban=
kolo-IHS","","25-04-2025 17:50:32","25-04-2025 17:38:40","25-04-2025 18:22:=
06","Cascaded Incident from TTO4995220","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down due to Bad eneo=
 voltage (no RCP on site) // Gen started manually	","system","267766","25-0=
4-2025 17:50:32","MATECH CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004883006","Jea=
n Vespa","IHS_YND_574","25-04-2025 17:47:46","25-04-2025 17:38:40","25-04-2=
025 18:22:06","site went down due to Bad eneo voltage (no RCP on site) // G=
en started manually	","Mboua Thierry","Grid Supply","Passive","Grid","Natio=
nal Grid - Unstable Grid Supply Issue","site went down due to Bad eneo volt=
age (no RCP on site) // Gen started manually	","gaelle.njiofack@matech-came=
roun.com","547","25-04-2025 17:47:46","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004882981","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","25-04-2025 17:45:27","25-04-2025 17:=
35:19","25-04-2025 20:22:33","Grid outage, Site went down because Gen faile=
d to start due to battery Gen faulty// He started Gen with external battery=
","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator B=
attery","Grid outage, Site went down because Gen failed to start due to bat=
tery Gen faulty// He started Gen with external battery","gaelle.njiofack@ma=
tech-cameroun.com","610","25-04-2025 17:45:27","MATECH CMR"
"Closed Complete","Site Down","CTR_525","IHS_YND_544","NOCINC0004882978","J=
ean Vespa 2","","25-04-2025 17:44:50","25-04-2025 17:34:33","25-04-2025 18:=
13:41","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","site went down due to Bad eneo voltage (no RCP on site) // G=
en started manually	","gaelle.njiofack@matech-cameroun.com","268264","25-04=
-2025 17:44:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_731","NOCINC0004882976","UPAC LP"=
,"","25-04-2025 17:44:37","25-04-2025 17:32:06","25-04-2025 17:46:07","Grid=
 outage.no space to deploy mobile gen //Grid return","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage.no space to de=
ploy mobile gen //Grid return","system","751","25-04-2025 17:44:37","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004882977","AFEME NO=
RD","IHS_YND_808","25-04-2025 17:44:37","25-04-2025 17:32:06","25-04-2025 1=
7:46:07","Site Went down due to Grid fluctuation // Grid Stabilized","TIENT=
CHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Unstab=
le Grid Supply Issue","Site Went down due to Grid fluctuation // Grid Stabi=
lized","system","751","25-04-2025 17:44:37","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0004882916","Mba=
nkolo petit paris","","25-04-2025 17:39:17","25-04-2025 17:32:06","25-04-20=
25 17:46:07","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Site Went down due to Grid fluctuation // Grid Stabili=
zed","loic.noumsi@matech-cameroun.com","275598","25-04-2025 17:39:17","MATE=
CH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004882892","Ngo=
usso Vallee","","25-04-2025 17:36:39","25-04-2025 17:29:32","25-04-2025 21:=
05:55","Grid outage,DG started and stopped due with alarm ""oil pressure""(=
 unprouven Alarm ) // He reset DG card and started DG manually","Siligap Bo=
ris","Equipment Repair","Passive","ACDG Gen","ACDG - Oil Pressure Sensor Fa=
ulty","Grid outage,DG started and stopped due with alarm ""oil pressure""( =
unprouven Alarm ) // He reset DG card and started DG manually","loic.noumsi=
@matech-cameroun.com","428","25-04-2025 17:36:39","MATECH CMR"
"Closed Complete","Site Down","T3180","IHS_YND_253","NOCINC0004882887","Clg=
e-Advantiste","","25-04-2025 17:35:49","25-04-2025 17:31:42","25-04-2025 19=
:08:57","Grid outage,site went down because gen overload(20kva,280A)// Grid=
 restoration","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage,site went down because gen overload(20kva,280A)//=
 Grid restoration","loic.noumsi@matech-cameroun.com","248","25-04-2025 17:3=
5:49","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004882844","E=
lig-Edzoa","","25-04-2025 17:30:53","25-04-2025 16:20:12","25-04-2025 19:06=
:01","No poaer issue on site Ubay 54.6V site on Gird, Site up without inter=
vention ","","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","No poaer issue on site Ubay 54.6V site on Gird, Si=
te up without intervention ","gaelle.njiofack@matech-cameroun.com","4242","=
25-04-2025 17:30:53","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004882788","D=
ragage","IHS_YND_704, IHS_YND_208","25-04-2025 17:25:03","25-04-2025 17:15:=
57","25-04-2025 18:30:26","Site iimpacted by Mballa-II","Mboua Thierry","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","Affected by =
3rd Party Site","Site iimpacted by Mballa-II","gaelle.njiofack@matech-camer=
oun.com","548","25-04-2025 17:25:03","MATECH CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0004882779","A=
RMP","","25-04-2025 17:24:09","25-04-2025 17:15:57","25-04-2025 18:30:26","=
","","Cascade Outage","Active","Cascade Active","Cascade Active","Site iimp=
acted by Mballa-II","gaelle.njiofack@matech-cameroun.com","269276","25-04-2=
025 17:24:09","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004882772","M=
EHANDAN","","25-04-2025 17:22:54","25-04-2025 17:14:07","25-04-2025 17:54:1=
2","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","	TTO4994940","gaelle.njiofack@matech-cameroun.com","298168","25-=
04-2025 17:22:54","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004882768","O=
dza II OCM","IHS_YND_528","25-04-2025 17:22:14","25-04-2025 17:14:07","25-0=
4-2025 17:54:12","Grid outage ,site went down because GEN failed to start d=
ue to ATS and Gen card faulty // grid returned","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","	Grid outage ,site wen=
t down because GEN failed to start due to ATS and Gen card faulty // grid r=
eturned","gaelle.njiofack@matech-cameroun.com","489","25-04-2025 17:22:14",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004882762","B=
astos Bir","","25-04-2025 17:21:31","25-04-2025 17:15:57","25-04-2025 18:30=
:26","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Cascade=
 Active","Site iimpacted by Mballa-II","gaelle.njiofack@matech-cameroun.com=
","269275","25-04-2025 17:21:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004882757","Minka","=
","25-04-2025 17:20:40","25-04-2025 17:13:50","25-04-2025 18:23:50","Cascad=
ed Incident from TTO4994914","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Impacted by NGOUMOU wich is not manage by IHS"=
,"system","297983","25-04-2025 17:20:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004882758","Mom","",=
"25-04-2025 17:20:40","25-04-2025 17:13:50","25-04-2025 18:23:50","Cascaded=
 Incident from TTO4994914","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Impacted by NGOUMOU wich is not manage by IHS","=
system","297984","25-04-2025 17:20:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004882756","OTELE MT=
N","","25-04-2025 17:20:39","25-04-2025 17:13:50","25-04-2025 18:23:50","Ca=
scaded Incident from TTO4994914","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Impacted by NGOUMOU wich is not manage by =
IHS","system","297984","25-04-2025 17:20:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004882755","OLAMA","=
","25-04-2025 17:20:39","25-04-2025 17:13:50","25-04-2025 18:23:50","Cascad=
ed Incident from TTO4994914","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Impacted by NGOUMOU wich is not manage by IHS"=
,"system","297983","25-04-2025 17:20:39","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004882747","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","25-04-2025 17:18:=
57","25-04-2025 17:13:50","25-04-2025 18:23:50","Impacted by NGOUMOU wich i=
s not manage by IHS","Fanda Brice","Customer Equipment Failure","Active","A=
ctive Equipment Failure","Affected by 3rd Party Site","Impacted by NGOUMOU =
wich is not manage by IHS","loic.noumsi@matech-cameroun.com","308","25-04-2=
025 17:18:57","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004882664","NTE=
MASSI","","25-04-2025 17:03:32","25-04-2025 16:57:20","25-04-2025 17:06:20"=
,"Grid outage, Site down due to Rectifiers issue // Grid returned","Delor T=
elezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Grid =
outage, Site down due to Rectifiers issue // Grid returned","ludivine.ngama=
leu@ihstowers.com","373","25-04-2025 17:03:32","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0004882631","M=
vog-Ebanda","","25-04-2025 16:55:59","25-04-2025 16:45:59","25-04-2025 17:0=
0:45","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","site impacted by work of Francis LeLe GAIO /655242229Telemetr=
y text.","gaelle.njiofack@matech-cameroun.com","271073","25-04-2025 16:55:5=
9","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0004882628","A=
bom","IHS_YND_269","25-04-2025 16:55:18","25-04-2025 16:45:59","25-04-2025 =
17:00:45","site impacted by work of Francis LeLe GAIO /655242229Telemetry t=
ext.","Siligap Boris","Equipment Replacement","Passive","Planned Activity",=
"Planned Activity - Passive","site impacted by work of Francis LeLe GAIO /6=
55242229Telemetry text.","gaelle.njiofack@matech-cameroun.com","560","25-04=
-2025 16:55:18","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004882337","M=
bankomo IHS","","25-04-2025 16:11:37","25-04-2025 15:26:23","25-04-2025 16:=
51:20","Site went down due to (02/02) rectifiers dysfunction // He reset it=
 and site on Grid","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to (02/02) rectifiers dysfunction // =
He reset it and site on Grid","gaelle.njiofack@matech-cameroun.com","2715",=
"25-04-2025 16:11:37","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004882285","Mes=
sassi 2","","25-04-2025 16:04:50","25-04-2025 15:59:21","25-04-2025 16:08:0=
6","Site went down because rectifiers dysfunctionned// He reset rectifiers"=
,"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site went down because rectifiers dysfunctionned// He reset rectifiers=
","loic.noumsi@matech-cameroun.com","330","25-04-2025 16:04:50","MATECH CMR=
"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004882205","L=
eboudi","","25-04-2025 15:53:01","25-04-2025 15:47:49","25-04-2025 18:24:12=
","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive"," Grid outage, site went down due to Gen swap // End of=
 work","gaelle.njiofack@matech-cameroun.com","281733","25-04-2025 15:53:01"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004882196","N=
kolafeme","IHS_YND_309","25-04-2025 15:52:00","25-04-2025 15:47:49","25-04-=
2025 18:28:27"," Grid outage, site went down due to Gen swap // End of work=
","TIENTCHEU NZETCHIEU GAEL","Equipment Replacement","Passive","Planned Act=
ivity","Planned Activity - ACDG Replacement"," Grid outage, site went down =
due to Gen swap // End of work","gaelle.njiofack@matech-cameroun.com","251"=
,"25-04-2025 15:52:00","MATECH CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0004882087","O=
lezoa OCM","","25-04-2025 15:37:12","25-04-2025 15:35:51","25-04-2025 16:09=
:09","Grid outage, No space to deploy a MDG//Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space=
 to deploy a MDG//Grid return","gaelle.njiofack@matech-cameroun.com","82","=
25-04-2025 15:37:12","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004881999","E=
beba","","25-04-2025 15:24:11","25-04-2025 15:22:04","25-04-2025 15:49:51",=
"Hybrid gen site .gen failed to start due to automation malfunctionning//Ge=
n manually started ","Fanda Brice","Equipment Repair","Passive","Hybrid","H=
ybrid Module","Hybrid gen site .gen failed to start due to automation malfu=
nctionning//Gen manually started ","gaelle.njiofack@matech-cameroun.com","1=
28","25-04-2025 15:24:11","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004881984","M=
ANGUIERS CHAPELLE","","25-04-2025 15:20:15","25-04-2025 15:17:01","25-04-20=
25 15:54:52","Grid outage, site went down due to gen Overload(20KVA,270A) /=
/ he reduced load, site on gen","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen Ov=
erload(20KVA,270A) // he reduced load, site on gen","gaelle.njiofack@matech=
-cameroun.com","195","25-04-2025 15:20:15","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004881977","S=
calom","","25-04-2025 15:19:25","25-04-2025 15:15:23","25-04-2025 17:51:22"=
,"","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Site down due to work of francois was on site for Work//End of work"=
,"gaelle.njiofack@matech-cameroun.com","1276384","25-04-2025 15:19:25","MAT=
ECH CMR"
"Closed Complete","Warning","CTR_479","IHS_YND_580","NOCINC0004881972","Mar=
che Odza","","25-04-2025 15:18:54","","","Grid fluctuation,site went down d=
ue to rectifiers dysfunction//He reset and site on Grid","Albran Byorel","W=
arning","Warning","POWER","Warning - Rectifier Module","Grid fluctuation,si=
te went down due to rectifiers dysfunction//He reset and site on Grid","loi=
c.noumsi@matech-cameroun.com","1388","25-04-2025 15:18:54","MATECH CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004881960","S=
calom-IHS","IHS_YND_071","25-04-2025 15:18:29","25-04-2025 15:15:23","25-04=
-2025 17:51:22","Site down due to work of francois was on site for Work//En=
d of work","","Installation Activity","Passive","Planned Activity","Install=
ation Activity","Site down due to work of francois was on site for Work//En=
d of work","gaelle.njiofack@matech-cameroun.com","188","25-04-2025 15:18:29=
","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004881902","M=
arche Odza","","25-04-2025 15:13:32","25-04-2025 15:09:17","25-04-2025 16:2=
4:35","Grid fluctuation,site went down due to rectifiers dysfunction//He re=
set and site on Grid","Albran Byorel","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Grid fluctuation,site went down due to rectifiers d=
ysfunction//He reset and site on Grid","gaelle.njiofack@matech-cameroun.com=
","256","25-04-2025 15:13:32","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004881869","BAT=
A Mokolo OCM","","25-04-2025 15:09:09","25-04-2025 15:04:04","26-04-2025 17=
:34:29","Fme Yamen is informed and reported no space to deploy MG. // grid =
return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Fme Yamen is informed and reported no space to deploy MG. // grid retur=
n","loic.noumsi@matech-cameroun.com","306","25-04-2025 15:09:09","MATECH CM=
R"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004881790","Nko=
abang2","","25-04-2025 14:54:18","25-04-2025 14:42:59","25-04-2025 15:32:23=
","Grid outage, site went down due to gen overload (22KVA, 330A),// Grid re=
turn	","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, site went down due to gen overload (22KVA, 330A),// =
Grid return	","ludivine.ngamaleu@ihstowers.com","1036","25-04-2025 14:54:18=
","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004881591","N=
kolangaa","","25-04-2025 14:12:15","25-04-2025 14:04:50","25-04-2025 14:19:=
46","TX issue : Joint visit between power and TX for load normalization // =
End of Work","Mba Lazare Herve","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","TX issue : Joint visit between =
power and TX for load normalization // End of Work","vanel.mbiada@matech-ca=
meroun.com","446","25-04-2025 14:12:15","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004881423","Aha=
la Echangeur","","25-04-2025 13:42:41","25-04-2025 13:35:32","25-04-2025 14=
:22:15","Site went down due to insufficient rectifiers on site // he rejack=
ed it","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down due to insufficient rectifiers on site // he rejack=
ed it","cedric.tiani@matech-cameroun.com","430","25-04-2025 13:42:41","MATE=
CH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004881411","Com=
plex Beac II","","25-04-2025 13:39:18","25-04-2025 13:29:59","25-04-2025 14=
:03:46","Grid outage,site went down because main gen faulty//Grid return","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fa=
ulty","Grid outage,site went down because main gen faulty//Grid return","ce=
dric.tiani@matech-cameroun.com","560","25-04-2025 13:39:18","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0004881356","C=
hapelle-Nsimeyong","","25-04-2025 13:28:02","25-04-2025 13:24:44","25-04-20=
25 13:30:55","AcTIVE: no power issue, site is on grid with Ubaie=3D54.5V, H=
osiah(699699694) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","AcTIV=
E: no power issue, site is on grid with Ubaie=3D54.5V, Hosiah(699699694) fr=
om Huawei is informed","vanel.mbiada@matech-cameroun.com","199","25-04-2025=
 13:28:02","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004881354","A=
ccacia New","","25-04-2025 13:27:07","25-04-2025 13:24:52","25-04-2025 17:3=
0:53","No power issue site on grid with U=3D54v Mbah osiah(674007438) from =
Huawei is informed","","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D54v=
 Mbah osiah(674007438) from Huawei is informed","vanel.mbiada@matech-camero=
un.com","136","25-04-2025 13:27:07","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004881319","Ole=
mbe MTN","","25-04-2025 13:17:17","25-04-2025 13:16:06","25-04-2025 18:36:0=
6","Site went down due to SS HIS fELIX  Bate was on site working(changing t=
he MPR. //End of wotk","Fabrice Pouakam","Installation Activity","Passive",=
"Planned Activity","Installation Activity","Site went down due to SS HIS fE=
LIX  Bate was on site working(changing the MPR. //End of wotk","cedric.tian=
i@matech-cameroun.com","72","25-04-2025 13:17:17","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004881304","Nko=
l-Mbanda","","25-04-2025 13:10:16","25-04-2025 13:03:47","25-04-2025 15:34:=
35","Active// No power Issue Site on Grid Ubai =3D54,3V, The FME The TX FME=
 Mbah Hosiah (674007438) is informed.","MINKA NICOLAS","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
 No power Issue Site on Grid Ubai =3D54,3V, The FME The TX FME Mbah Hosiah =
(674007438) is informed.","cedric.tiani@matech-cameroun.com","390","25-04-2=
025 13:10:16","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004881298","B=
iteng-Maetur","","25-04-2025 13:08:30","25-04-2025 13:04:11","25-04-2025 13=
:46:44","Active//No power issue on site Ubaie =3D50.3V site on Grid The TX =
FME Henri (699949693) from Huawei is informed.Noticed disjunction at the BT=
S OCM","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie =
=3D50.3V site on Grid The TX FME Henri (699949693) from Huawei is informed.=
Noticed disjunction at the BTS OCM","vanel.mbiada@matech-cameroun.com","261=
","25-04-2025 13:08:30","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004881270","N=
kolfon Cimencam","","25-04-2025 13:01:32","25-04-2025 12:54:13","25-04-2025=
 13:00:45","Active//No power issue on site U=3D54,5v site on Gen The TX fme=
 George(697461814) from huawei is informed. Noticed that site is impacted b=
y Afanoya II(Not manage by HIS)","Hyemafo Gildas","Customer Equipment Failu=
re","Active","Active Equipment Failure","Affected by 3rd Party Site","Activ=
e//No power issue on site U=3D54,5v site on Gen The TX fme George(697461814=
) from huawei is informed. Noticed that site is impacted by Afanoya II(Not =
manage by HIS)","vanel.mbiada@matech-cameroun.com","440","25-04-2025 13:01:=
32","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004881181","Sca=
lom","","25-04-2025 12:39:54","25-04-2025 12:37:16","25-04-2025 12:43:39","=
Site went down because SS HIS Francois was on site working(Normalisation of=
 the Automatism)//End of work","Paul BIBOUM","Installation Activity","Passi=
ve","Planned Activity","Installation Activity","Site went down because SS H=
IS Francois was on site working(Normalisation of the Automatism)//End of wo=
rk","cedric.tiani@matech-cameroun.com","159","25-04-2025 12:39:54","MATECH =
CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004881154","Eto=
ug ebe Carrefour","","25-04-2025 12:37:17","25-04-2025 12:31:59","25-04-202=
5 12:37:44","Grid outage, site went down due to high temp alarm on gen // h=
e added water and started manually Gen","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid=
 outage, site went down due to high temp alarm on gen // he added water and=
 started manually Gen","cedric.tiani@matech-cameroun.com","318","25-04-2025=
 12:37:17","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004881150","Eko=
umdoum OCM","","25-04-2025 12:36:35","25-04-2025 12:28:24","25-04-2025 14:5=
6:47"," site went down due to Gen overload(20kva,280 A) IHS SS Pascaline is=
 informed // We reduce load and gen manually started","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload"," site went down due t=
o Gen overload(20kva,280 A) IHS SS Pascaline is informed // We reduce load =
and gen manually started","cedric.tiani@matech-cameroun.com","492","25-04-2=
025 12:36:35","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004881144","Efo=
ulan MTN","","25-04-2025 12:35:43","25-04-2025 12:30:37","25-04-2025 13:40:=
05","Site went down because gen stopped with low oil pressure//he added oil=
 and started the gen","MINKA NICOLAS","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Low Oil Pressure","Site went down because gen stopped with low o=
il pressure//he added oil and started the gen","cedric.tiani@matech-camerou=
n.com","307","25-04-2025 12:35:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004881042","Leboudi"=
,"","25-04-2025 12:15:11","25-04-2025 12:13:31","25-04-2025 12:34:40","Casc=
aded Incident from TTO4992941","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid fluctuation,site went d=
own because Gen failed to start due to Grid bad voltage//He bypassed and ma=
nually started the Gen","system","265728","25-04-2025 12:15:11","MATECH CMR=
"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004881039","Nko=
lafeme","IHS_YND_309","25-04-2025 12:14:42","25-04-2025 12:13:31","25-04-20=
25 12:35:52","Grid fluctuation,site went down because Gen failed to start d=
ue to Grid bad voltage//He bypassed and manually started the Gen","TIENTCHE=
U NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation,site went down because Gen failed to star=
t due to Grid bad voltage//He bypassed and manually started the Gen","cedri=
c.tiani@matech-cameroun.com","72","25-04-2025 12:14:42","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004881009","Aha=
la Echangeur","","25-04-2025 12:07:35","25-04-2025 12:06:28","25-04-2025 13=
:01:46","Site went down due to insufficiency of rectifier // He reduced the=
 load , site on Gen","MINKA NICOLAS","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to insufficiency of rectifier // =
He reduced the load , site on Gen","cedric.tiani@matech-cameroun.com","68",=
"25-04-2025 12:07:35","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004880831","E=
MANA BILICK CITY","","25-04-2025 11:41:18","25-04-2025 11:19:58","25-04-202=
5 16:05:43","Grid outage site went down due to generator faulty // Grid ret=
urn","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Grid=
 Outage Issue","Grid outage site went down due to generator faulty // Grid =
return","vanel.mbiada@matech-cameroun.com","1281","25-04-2025 11:41:18","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004880723","ODZA MIN=
KAN EDIBI ASSI","","25-04-2025 11:26:49","25-04-2025 11:06:26","25-04-2025 =
11:20:20","Cascaded Incident from TTO4992509","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Fme, RM are informed and=
 reported that new batteries behave as Poor battery backup // Grid restored=
","system","291475","25-04-2025 11:26:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004880722","Odza Min=
kan IHS","","25-04-2025 11:26:48","25-04-2025 11:06:26","25-04-2025 11:20:2=
0","Cascaded Incident from TTO4992509","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Fme, RM are informed and report=
ed that new batteries behave as Poor battery backup // Grid restored","syst=
em","291475","25-04-2025 11:26:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004880721","Mehanda =
1","","25-04-2025 11:26:48","25-04-2025 11:06:26","25-04-2025 11:20:20","Ca=
scaded Incident from TTO4992509","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Fme, RM are informed and reported tha=
t new batteries behave as Poor battery backup // Grid restored","system","2=
91475","25-04-2025 11:26:48","MATECH CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0004880667","BEA=
TITUDE ENTR=C9E PAVE","","25-04-2025 11:18:06","25-04-2025 11:08:55","25-04=
-2025 11:38:09","Site went down due to work of DO MATECH  Herve (697335400)=
 is on site (swapp of Gen)//End of work","TIENTCHEU NZETCHIEU GAEL","Instal=
lation Activity","Passive","Planned Activity","Installation Activity","Site=
 went down due to work of DO MATECH  Herve (697335400) is on site (swapp of=
 Gen)//End of work","cedric.tiani@matech-cameroun.com","552","25-04-2025 11=
:18:06","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004880662","Efo=
ulan MTN","","25-04-2025 11:17:31","25-04-2025 11:08:24","25-04-2025 12:11:=
18"," Grid Outage, site went down because Gen stopped due to ""LOW OIL PRES=
SURE"" alarm //He added oil  and gen manually started","MINKA NICOLAS","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure"," Grid Outage=
, site went down because Gen stopped due to ""LOW OIL PRESSURE"" alarm //He=
 added oil  and gen manually started","cedric.tiani@matech-cameroun.com","5=
48","25-04-2025 11:17:31","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004880655","Nko=
lnda","IHS_YND_746, IHS_YND_715, IHS_YND_749","25-04-2025 11:15:36","25-04-=
2025 11:06:26","25-04-2025 11:20:20","Fme, RM are informed and reported tha=
t new batteries behave as Poor battery backup // Grid restored","Albran Byo=
rel","Equipment Repair","Passive","Rectifier","Rectifier Battery","Fme, RM =
are informed and reported that new batteries behave as Poor battery backup =
// Grid restored","cedric.tiani@matech-cameroun.com","551","25-04-2025 11:1=
5:36","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004880647","Nom=
ayos montee Meche","","25-04-2025 11:14:02","25-04-2025 10:58:46","25-04-20=
25 11:35:49","Active: No power issue, site is on grid with Ubaie=3D53V, Flu=
bert(654266068) from Huawei is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No power issue, site is on grid with Ubaie=3D53V, Flubert(654266068) from H=
uawei is informed","cedric.tiani@matech-cameroun.com","917","25-04-2025 11:=
14:02","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004880606","Eto=
ug ebe Carrefour","","25-04-2025 11:09:05","25-04-2025 10:59:59","25-04-202=
5 11:47:34","Grid outage,site went down because Gen started and stoppped wi=
th alarm high temp//He added water","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age,site went down because Gen started and stoppped with alarm high temp//H=
e added water","cedric.tiani@matech-cameroun.com","547","25-04-2025 11:09:0=
5","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004880445","Mes=
sassi 2","","25-04-2025 10:50:53","25-04-2025 10:48:35","25-04-2025 10:58:3=
7","Grid outage Site went down before Gen started due to poor battery backu=
p // Gen started automatically","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage Site went do=
wn before Gen started due to poor battery backup // Gen started automatical=
ly","cedric.tiani@matech-cameroun.com","139","25-04-2025 10:50:53","MATECH =
CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004880323","Mok=
olo Yaounde","","25-04-2025 10:31:41","25-04-2025 10:31:31","25-04-2025 11:=
38:29","site went down due to insufficient of rectifier on site// site stab=
ilized","","Equipment Repair","Passive","Rectifier","Rectifier Module","sit=
e went down due to insufficient of rectifier on site// site stabilized","ce=
dric.tiani@matech-cameroun.com","11","25-04-2025 10:31:41","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004880133","Eko=
umdoum OCM","","25-04-2025 09:56:33","25-04-2025 09:52:23","25-04-2025 12:2=
6:37","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS =
Pascaline is informed and confirmed//site stabilised","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site wen=
t down due to Gen overload(20kva,280 A) IHS SS Pascaline is informed and co=
nfirmed//site stabilised","cedric.tiani@matech-cameroun.com","251","25-04-2=
025 09:56:33","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004880032","Eto=
ug ebe Carrefour","","25-04-2025 09:39:23","25-04-2025 09:34:14","25-04-202=
5 09:51:39","Grid outage,site went down because Gen started and stoppped wi=
th alarm high temp//He added  water","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid ou=
tage,site went down because Gen started and stoppped with alarm high temp//=
He added  water","cedric.tiani@matech-cameroun.com","310","25-04-2025 09:39=
:23","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004879771","Sca=
lom","IHS_YND_505","25-04-2025 08:57:47","25-04-2025 08:48:59","25-04-2025 =
09:50:11","Grid outage,site went down because gen failed to start due to no=
 automatism on site//He started the Gen manually ","Paul BIBOUM","Equipment=
 Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,site went d=
own because gen failed to start due to no automatism on site//He started th=
e Gen manually ","cedric.tiani@matech-cameroun.com","528","25-04-2025 08:57=
:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004879744","Leboudi"=
,"","25-04-2025 08:52:54","25-04-2025 07:59:39","25-04-2025 08:54:46","Casc=
aded Incident from TTO4991287","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
due to gen gen overload(20Kva, 375A), SS IHS Pascaline is informed// Grid p=
ower return","system","273781","25-04-2025 08:52:54","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0004879740","Mba=
nkolo petit paris","","25-04-2025 08:52:25","25-04-2025 08:51:16","25-04-20=
25 10:54:57","Grid outage,site went down because gen ran till fuel shortage=
//Refueling done","Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage,site went down because gen ran till fuel shortage//Ref=
ueling done","cedric.tiani@matech-cameroun.com","70","25-04-2025 08:52:25",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004879712","M=
bankomo IHS","","25-04-2025 08:46:29","25-04-2025 08:44:16","25-04-2025 09:=
06:52","Site went down due to (02/02) rectifiers dysfunction // He reset it=
 and site on Grid","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to (02/02) rectifiers dysfunction // =
He reset it and site on Grid","vanel.mbiada@matech-cameroun.com","134","25-=
04-2025 08:46:29","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004879709","NTE=
MASSI","","25-04-2025 08:45:49","25-04-2025 08:45:35","25-04-2025 11:15:57"=
,"Grid outage, Site down due to Rectifiers issue // Grid returned","Delor T=
elezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Grid =
outage, Site down due to Rectifiers issue // Grid returned","cedric.tiani@m=
atech-cameroun.com","14","25-04-2025 08:45:49","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004879695","NTU=
I TOWN","","25-04-2025 08:44:50","25-04-2025 08:43:42","25-04-2025 08:45:40=
","Grid fluctuation,site went down because Gen failed to start due to Grid =
bad voltage//Grid return ","Parker Tchoup","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","Grid fluctuation,site went down b=
ecause Gen failed to start due to Grid bad voltage//Grid return ","cedric.t=
iani@matech-cameroun.com","69","25-04-2025 08:44:50","MATECH CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004879685","S=
calom-IHS","","25-04-2025 08:41:45","25-04-2025 08:48:59","25-04-2025 09:48=
:38","fme is on the way 09:50 AM","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage,site went down because gen failed to =
start due to no automatism on site//He started the Gen manually ","vanel.mb=
iada@matech-cameroun.com","271027","25-04-2025 08:41:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0004879604","Nguila",=
"","25-04-2025 08:19:59","25-04-2025 07:52:16","25-04-2025 08:00:05","Casca=
ded Incident from TTO4991240","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active//No power issue with U=3D54V //site =
on Battery THe fme tx Gregoire 652070658 from Huawei is informed.Noticed im=
pacted by Mbandjock","system","1216604","25-04-2025 08:19:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004879593","Song-bon=
g","","25-04-2025 08:17:18","24-04-2025 19:00:27","24-04-2025 19:10:06","Ca=
scaded Incident from TTO4991212","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","ACTIVE //No power issue U=3D51V site o=
n Gen The Tx FME Etienne FOPA /695033981/ From HUAWEI is informed ","system=
","47811","25-04-2025 08:17:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004879592","Eseka To=
wn","","25-04-2025 08:17:17","24-04-2025 19:00:27","24-04-2025 19:10:06","C=
ascaded Incident from TTO4991212","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","ACTIVE //No power issue U=3D51V site =
on Gen The Tx FME Etienne FOPA /695033981/ From HUAWEI is informed ","syste=
m","47810","25-04-2025 08:17:17","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004879545","N=
kolafeme","IHS_YND_309","25-04-2025 08:03:21","25-04-2025 07:59:39","25-04-=
2025 08:54:46","Grid outage, site went down due to gen gen overload(20Kva, =
375A), SS IHS Pascaline is informed// Grid power return","TIENTCHEU NZETCHI=
EU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage, site went down due to gen gen overload(20Kva, 375A), SS IHS Pascaline=
 is informed// Grid power return","vanel.mbiada@matech-cameroun.com","222",=
"25-04-2025 08:03:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004879507","Dong",""=
,"25-04-2025 07:55:09","25-04-2025 07:52:16","25-04-2025 08:00:05","Cascade=
d Incident from TTO4991240","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue with U=3D54V //site on=
 Battery THe fme tx Gregoire 652070658 from Huawei is informed.Noticed impa=
cted by Mbandjock","system","1216604","25-04-2025 07:55:09","MATECH CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004879501","D=
onga","IHS_YND_433, IHS_YND_444","25-04-2025 07:53:50","25-04-2025 07:52:16=
","25-04-2025 08:00:05","Active//No power issue with U=3D54V //site on Batt=
ery THe fme tx Gregoire 652070658 from Huawei is informed.Noticed impacted =
by Mbandjock","Parker Tchoup","Customer Equipment Failure","Active","Active=
 Equipment Failure","Affected by 3rd Party Site","Active//No power issue wi=
th U=3D54V //site on Battery THe fme tx Gregoire 652070658 from Huawei is i=
nformed.Noticed impacted by Mbandjock","vanel.mbiada@matech-cameroun.com","=
95","25-04-2025 07:53:50","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0004879479","E=
seka OCM","IHS_YND_378, IHS_YND_453","25-04-2025 07:48:52","24-04-2025 19:0=
0:27","24-04-2025 19:10:06","Bactracking ACTIVE //No power issue U=3D51V si=
te on Gen The Tx FME Etienne FOPA /695033981/ From HUAWEI is informed ","Ke=
meni Franklin","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","ACTIVE //No power issue U=3D51V site on Gen The =
Tx FME Etienne FOPA /695033981/ From HUAWEI is informed ","cedric.tiani@mat=
ech-cameroun.com","46106","25-04-2025 07:48:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004879455","Emana Ly=
cee","","25-04-2025 07:42:59","25-04-2025 07:37:13","25-04-2025 07:55:36","=
Cascaded Incident from TTO4991169","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation,site went down b=
ecause Gen failed to start due to Grid bad voltage//Grid return","system","=
267963","25-04-2025 07:42:59","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004879435","E=
mana lycee 2","IHS_YND_274","25-04-2025 07:39:45","25-04-2025 07:37:13","25=
-04-2025 07:55:36","Grid fluctuation,site went down because Gen failed to s=
tart due to Grid bad voltage//Grid return","Fabrice Pouakam","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
n,site went down because Gen failed to start due to Grid bad voltage//Grid =
return","vanel.mbiada@matech-cameroun.com","153","25-04-2025 07:39:45","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004879053","E=
MANA BILICK CITY","","25-04-2025 06:33:34","25-04-2025 06:26:20","25-04-202=
5 07:41:16","Grid outage site  went down due to generator faulty // Grid re=
turn","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Gri=
d Outage Issue","Grid outage//Grid return","vanel.mbiada@matech-cameroun.co=
m","436","25-04-2025 06:33:34","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004878967","Eko=
umdoum OCM","","25-04-2025 06:07:28","25-04-2025 06:02:20","25-04-2025 08:5=
6:46","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS =
Pascaline is informed and confirmed//Grid return","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went do=
wn due to Gen overload(20kva,280 A) IHS SS Pascaline is informed and confir=
med//Grid return","edwige.kapawo@matech-cameroun.com","328","25-04-2025 06:=
07:28","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004878948","N=
kolfon Cimencam","","25-04-2025 06:01:43","25-04-2025 05:54:23","25-04-2025=
 06:03:16","site impacted by Afanoya_II","Hyemafo Gildas","Customer Equipme=
nt Failure","Active","Active Equipment Failure","Affected by 3rd Party Site=
","site impacted by Afanoya_II","edwige.kapawo@matech-cameroun.com","441","=
25-04-2025 06:01:43","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004878926","Mes=
sassi 2","","25-04-2025 05:55:12","25-04-2025 05:52:03","25-04-2025 07:50:4=
4","Site went down because 02/06 rectifiers dysfuncionned// He reset rectif=
iers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down because 02/06 rectifiers dysfuncionned// He reset =
rectifiers","edwige.kapawo@matech-cameroun.com","191","25-04-2025 05:55:12"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004878831","Leboudi"=
,"","25-04-2025 05:20:21","25-04-2025 05:09:59","25-04-2025 06:56:09","Casc=
aded Incident from TTO4990504","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage,site went due to=
 PWC ZTE dysfunction and no automatism on site//He bypassed it and site on =
Gen","system","269739","25-04-2025 05:20:21","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004878829","N=
kolafeme","IHS_YND_309","25-04-2025 05:19:16","25-04-2025 05:09:59","25-04-=
2025 07:18:00","Grid outage,site went due to PWC ZTE dysfunction and no aut=
omatism on site//He bypassed it and site on Gen","TIENTCHEU NZETCHIEU GAEL"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage,site went due to PWC ZTE dysfunction and no automatism on site//H=
e bypassed it and site on Gen","edwige.kapawo@matech-cameroun.com","557","2=
5-04-2025 05:19:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004878730","Akono","=
","25-04-2025 05:00:08","25-04-2025 04:51:59","25-04-2025 05:02:35","Cascad=
ed Incident from TTO4990384","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue  site on Grid Ubay: 53.5V, Site=
 impacted by Ngoumou_T0169","system","263483","25-04-2025 05:00:08","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004878729","Minka","=
","25-04-2025 05:00:08","25-04-2025 04:51:59","25-04-2025 05:02:35","Cascad=
ed Incident from TTO4990384","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue  site on Grid Ubay: 53.5V, Site=
 impacted by Ngoumou_T0169","system","263482","25-04-2025 05:00:08","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004878728","OTELE MT=
N","","25-04-2025 05:00:07","25-04-2025 04:51:59","25-04-2025 05:02:35","Ca=
scaded Incident from TTO4990384","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue  site on Grid Ubay: 53.5V, =
Site impacted by Ngoumou_T0169","system","263482","25-04-2025 05:00:07","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004878727","OLAMA","=
","25-04-2025 05:00:07","25-04-2025 04:51:59","25-04-2025 05:02:35","Cascad=
ed Incident from TTO4990384","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue  site on Grid Ubay: 53.5V, Site=
 impacted by Ngoumou_T0169","system","263482","25-04-2025 05:00:07","MATECH=
 CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004878723","Mom=
","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_365","25-04-2025 04:58:49=
","25-04-2025 04:51:59","25-04-2025 05:02:35","No power issue  site on Grid=
 Ubay: 53.5V, Site impacted by Ngoumou_T0169","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","Affected by 3rd Party Si=
te","No power issue  site on Grid Ubay: 53.5V, Site impacted by Ngoumou_T01=
69","edwige.kapawo@matech-cameroun.com","411","25-04-2025 04:58:49","MATECH=
 CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0004878692","BEA=
TITUDE ENTR=C9E PAVE","","25-04-2025 04:46:57","25-04-2025 04:40:47","25-04=
-2025 07:13:37","Site went down because Gen failed to start due to Gen card=
 faulty// He manually started the Gen","TIENTCHEU NZETCHIEU GAEL","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Site went down becau=
se Gen failed to start due to Gen card faulty// He manually started the Gen=
","edwige.kapawo@matech-cameroun.com","371","25-04-2025 04:46:57","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004878670","MEHANDAN=
","","25-04-2025 04:35:39","25-04-2025 04:29:15","25-04-2025 04:48:15","Cas=
caded Incident from TTO4990315","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,site went down because GE=
N failed to start due to ATS and Gen card faulty // grid returned	","system=
","384","25-04-2025 04:35:39","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004878661","Odz=
a II OCM","IHS_YND_528","25-04-2025 04:33:24","25-04-2025 04:29:15","25-04-=
2025 05:46:23","Grid outage ,site went down because GEN failed to start due=
 to ATS and Gen card faulty // grid returned	","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went =
down because GEN failed to start due to ATS and Gen card faulty // grid ret=
urned	","edwige.kapawo@matech-cameroun.com","280","25-04-2025 04:33:24","MA=
TECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004878605","Nko=
g-Edzen","","25-04-2025 04:08:50","25-04-2025 04:05:36","25-04-2025 05:57:5=
7","No power issue on site, site on Grid with Ubay: 51.9V The Tx Fme Gregoi=
re (654547479) from Huawei is informed.","Parker Tchoup","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site, site on Grid with Ubay: 51.9V The Tx Fme Gregoire (654547=
479) from Huawei is informed.","edwige.kapawo@matech-cameroun.com","195","2=
5-04-2025 04:08:50","MATECH CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004878582","Nom=
ayos","","25-04-2025 03:57:55","25-04-2025 03:55:48","25-04-2025 05:43:56",=
"Site went down because 05/08 rectifiers disfunctionning// He reset rectifi=
ers","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site went down because 05/08 rectifiers disfunctionning// He reset rec=
tifiers","edwige.kapawo@matech-cameroun.com","128","25-04-2025 03:57:55","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0004878458","E=
zezang","IHS_YND_401","25-04-2025 03:20:18","25-04-2025 03:15:10","25-04-20=
25 04:45:38","Grid outage, site went down because gen failed to start due t=
o gen battery  faulty // Gen manually started with external battery","Parke=
r Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery=
","Grid outage, site went down because gen failed to start due to gen batte=
ry  faulty // Gen manually started with external battery","edwige.kapawo@ma=
tech-cameroun.com","309","25-04-2025 03:20:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004877953","Nkomkana=
","","25-04-2025 00:56:46","24-04-2025 23:02:12","25-04-2025 01:29:10","Cas=
caded Incident from TTO4989535","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Site went down because gen fails to start due to gr=
id bad voltage // He bypass grid and manually start the gen","system","2773=
38","25-04-2025 00:56:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_233","NOCINC0004877941","Oyomaban=
g OCM","IHS_YND_200","25-04-2025 00:55:19","24-04-2025 23:02:12","25-04-202=
5 01:29:10","Site went down because gen failed to start due to grid bad vol=
tage // He bypassed grid and manually start the gen","TIENTCHEU NZETCHIEU G=
AEL","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Site went down because gen failed to start due to grid bad voltage // H=
e bypassed grid and manually start the gen","joelle.ekessi@ihstowers.com","=
6787","25-04-2025 00:55:19","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004877495","H=
-General-Yde","","24-04-2025 23:28:40","24-04-2025 23:20:31","24-04-2025 23=
:41:03","Active // No power issue site on grid with Ubay:54.6V Symphorien f=
rom Huawei is informed","Siligap Boris","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power issu=
e site on grid with Ubay:54.6V Symphorien from Huawei is informed","edwige.=
kapawo@matech-cameroun.com","489","24-04-2025 23:28:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0004877428","Nkolanga=
a","","24-04-2025 23:11:34","24-04-2025 22:55:49","25-04-2025 01:41:47","Ca=
scaded Incident from TTO4988910","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen start and stopped with high temp alarm // He added water and manually=
 start the gen","system","277755","24-04-2025 23:11:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0004877427","Nkoulou =
Carriere carrefourt","","24-04-2025 23:11:34","24-04-2025 22:55:49","25-04-=
2025 01:41:47","Cascaded Incident from TTO4988910","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage, sit=
e went down because gen start and stopped with high temp alarm // He added =
water and manually start the gen","system","277755","24-04-2025 23:11:34","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0004877421","Dagobert=
","","24-04-2025 23:10:40","24-04-2025 23:01:58","24-04-2025 23:13:07","Cas=
caded Incident from TTO4988923","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active // No power issue on si=
te ,site on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is on=
 site to work (Upgrade 10G_COREVO)","system","262960","24-04-2025 23:10:40"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004877422","Entree C=
ite Verte","","24-04-2025 23:10:40","24-04-2025 23:01:58","24-04-2025 23:13=
:07","Cascaded Incident from TTO4988923","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active // No power issue on site ,=
site on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is on sit=
e to work (Upgrade 10G_COREVO)","system","262965","24-04-2025 23:10:40","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0004877416","BATA Mok=
olo OCM","","24-04-2025 23:10:39","24-04-2025 23:01:58","24-04-2025 23:13:0=
7","Cascaded Incident from TTO4988923","","Cascade Outage","Active","Cascad=
e Active","Cascade Active","Active // No power issue on site ,site on Grid =
with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is on site to work (Up=
grade 10G_COREVO)","system","262964","24-04-2025 23:10:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0004877419","Yona Hot=
el","","24-04-2025 23:10:39","24-04-2025 23:01:58","24-04-2025 23:13:07","C=
ascaded Incident from TTO4988923","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active // No power issue on =
site ,site on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is =
on site to work (Upgrade 10G_COREVO)","system","262962","24-04-2025 23:10:3=
9","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0004877417","Meyong-M=
eyeme","","24-04-2025 23:10:39","24-04-2025 23:01:58","24-04-2025 23:13:07"=
,"Cascaded Incident from TTO4988923","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","Active // No power issue =
on site ,site on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) =
Is on site to work (Upgrade 10G_COREVO)","system","262962","24-04-2025 23:1=
0:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0004877420","Crf-Nkol=
bisson","","24-04-2025 23:10:39","24-04-2025 23:01:58","24-04-2025 23:13:07=
","Cascaded Incident from TTO4988923","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","Active // No power issue=
 on site ,site on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF)=
 Is on site to work (Upgrade 10G_COREVO)","system","262961","24-04-2025 23:=
10:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004877418","Bastos B=
ethesda","","24-04-2025 23:10:39","24-04-2025 23:01:58","24-04-2025 23:13:0=
7","Cascaded Incident from TTO4988923","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active // No power issue on site ,=
site on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is on sit=
e to work (Upgrade 10G_COREVO)","system","262963","24-04-2025 23:10:39","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0004877414","Cite-Ver=
te","","24-04-2025 23:10:38","24-04-2025 23:01:58","24-04-2025 23:13:07","C=
ascaded Incident from TTO4988923","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Active // No power issue on site ,site on Grid with =
Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is on site to work (Upgrade=
 10G_COREVO)","system","262960","24-04-2025 23:10:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004877411","Golf Qua=
ter","","24-04-2025 23:10:38","24-04-2025 23:01:58","24-04-2025 23:13:07","=
Cascaded Incident from TTO4988923","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active // No power issue on site ,site=
 on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is on site to=
 work (Upgrade 10G_COREVO)","system","262964","24-04-2025 23:10:38","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004877413","Nkomkana=
 2","","24-04-2025 23:10:38","24-04-2025 23:01:58","24-04-2025 23:13:07","C=
ascaded Incident from TTO4988923","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active // No power issue on site ,site =
on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is on site to =
work (Upgrade 10G_COREVO)","system","262960","24-04-2025 23:10:38","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004877412","AFEME NO=
RD","","24-04-2025 23:10:38","24-04-2025 23:01:58","24-04-2025 23:13:07","C=
ascaded Incident from TTO4988923","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active // No power issue on =
site ,site on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is =
on site to work (Upgrade 10G_COREVO)","system","262961","24-04-2025 23:10:3=
8","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0004877415","Bastos-N=
ylon","","24-04-2025 23:10:38","24-04-2025 23:01:58","24-04-2025 23:13:07",=
"Cascaded Incident from TTO4988923","Mboua Thierry","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active // No power issue on site ,sit=
e on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is on site t=
o work (Upgrade 10G_COREVO)","system","262963","24-04-2025 23:10:38","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0004877410","Nkolbi-B=
oss","","24-04-2025 23:10:37","24-04-2025 23:01:58","24-04-2025 23:13:07","=
Cascaded Incident from TTO4988923","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","Active // No power issue on=
 site ,site on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is=
 on site to work (Upgrade 10G_COREVO)","system","262963","24-04-2025 23:10:=
37","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004877393","T=
singa","IHS_YND_273, IHS_YND_220, IHS_YND_519, IHS_YND_138, IHS_YND_202, IH=
S_YND_126, IHS_YND_559, IHS_YND_230, IHS_YND_563, IHS_YND_271, IHS_YND_232,=
 IHS_YND_286, IHS_YND_543","24-04-2025 23:03:05","24-04-2025 23:01:58","24-=
04-2025 23:13:07","Active // No power issue on site ,site on Grid with Ubai=
e: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is on site to work (Upgrade 10G=
_COREVO)","Mboua Thierry","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Active // No power issue on site ,sit=
e on Grid with Ubaie: 51.3V. SONKOUE Emmanuel (694567096/SNEF) Is on site t=
o work (Upgrade 10G_COREVO)","edwige.kapawo@matech-cameroun.com","68","24-0=
4-2025 23:03:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004877374","Abang","=
IHS_YND_794, IHS_YND_289","24-04-2025 22:57:54","24-04-2025 22:55:49","25-0=
4-2025 01:41:47","Grid outage, site went down because gen start and stopped=
 with high temp alarm // He added water and manually start the gen","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Tem=
p - Coolant Level Issue","Grid outage, site went down because gen started a=
nd stopped with high temp alarm // He added water and manually start the ge=
n","joelle.ekessi@ihstowers.com","126","24-04-2025 22:57:54","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004877362","NTE=
MASSI","","24-04-2025 22:54:46","24-04-2025 22:49:33","25-04-2025 00:56:43"=
,"Site went down because of insufficient rectifiers  //site stabilised","De=
lor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down because of insufficient rectifiers  //site stabilised","edwi=
ge.kapawo@matech-cameroun.com","314","24-04-2025 22:54:46","MATECH CMR"
"Closed Complete","Site Down","CTR_553","IHS_YND_686","NOCINC0004877040","O=
yomabang Ecole","","24-04-2025 21:45:58","24-04-2025 21:35:53","24-04-2025 =
21:37:53","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mo=
uhamadou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue, Site on Gen and Ubaie=3D 55,3V The TX Mouh=
amadou (6144435) from Huawei is informed.","franck.nkomot@matech-cameroun.c=
om","606","24-04-2025 21:45:58","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004877001","M=
bankomo IHS","","24-04-2025 21:36:40","24-04-2025 21:33:34","24-04-2025 21:=
50:04","Site down due to Rectifier dysfuntionning // He reset it: site on g=
rid","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site down due to Rectifier dysfuntionning // He reset it: site on grid=
","christelle.ngonga@matech-cameroun.com","186","24-04-2025 21:36:40","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004876861","B=
arriere","","24-04-2025 21:11:17","24-04-2025 21:10:09","26-04-2025 05:58:5=
1","Gen overload","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage, Site went down because Gen overload(20kva,4=
00 A) IHS SS Felix Zambe is informed and confirmed //Grid return","christel=
le.ngonga@matech-cameroun.com","69","24-04-2025 21:11:17","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004876836","Eto=
ug ebe Carrefour","","24-04-2025 21:08:28","24-04-2025 21:03:18","24-04-202=
5 21:21:18","Grid outage, site went down due to Gen over current  alarm  //=
 he reset and start Gen","Hyemafo Gildas","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage, site went down due to Gen over =
current  alarm  // he reset and start Gen","franck.nkomot@matech-cameroun.c=
om","311","24-04-2025 21:08:28","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004876799","Meh=
anda 1","","24-04-2025 21:03:39","24-04-2025 19:40:01","25-04-2025 06:42:31=
","ACCESS ISSUES during the night due to lanlord Grid fluctuation,site went=
 because Gen failed to start due to Grid bad voltage//SITE on gen","Albran =
Byorel","Access Denial","Lease Or Legal","Landlord Related Issues","Access =
Issue - Land Lord","Grid fluctuation,site went because Gen failed to start =
due to Grid bad voltage//SITE on gen","franck.nkomot@matech-cameroun.com","=
5019","24-04-2025 21:03:39","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004876416","B=
iteng-Maetur","","24-04-2025 19:53:52","24-04-2025 19:52:46","24-04-2025 20=
:01:29","No power issue, Ubay:52.1V on grid, Tx FME Henry//699949693 From h=
uawei is informed","Mba Lazare Herve","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue, Ubay:52.1=
V on grid, Tx FME Henry//699949693 From huawei is informed","christelle.ngo=
nga@matech-cameroun.com","68","24-04-2025 19:53:52","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004876317","B=
itoto","","24-04-2025 19:43:24","24-04-2025 19:37:08","24-04-2025 21:20:50"=
,"No power issue on site , Tx Issue : site on Grid ,Ubai: 52,9V; The fme Tx=
 Henri (699949693) From huawei is informed and notice that disjunction at O=
CM Equipment ","Mba Lazare Herve","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site , Tx I=
ssue : site on Grid ,Ubai: 52,9V; The fme Tx Henri (699949693) From huawei =
is informed and notice that disjunction at OCM Equipment ","christelle.ngon=
ga@matech-cameroun.com","377","24-04-2025 19:43:24","MATECH CMR"
"Resolved","Site Down","","IHS_YND_415","NOCINC0004876140","Boga-Mahole",""=
,"24-04-2025 19:11:06","24-04-2025 18:58:59","24-04-2025 18:59:59","Cascade=
d Incident from TTO4987458 - Cascade Removed From TTO4987458","Kemeni Frank=
lin","","","","","No power issue on site U=3D56,3v site on gen Tx fme Fredd=
y 690419006 of huawei is informed","system","727","24-04-2025 19:11:06","MA=
TECH CMR"
"Resolved","Site Down","","IHS_YND_376","NOCINC0004876138","Mamb","","24-04=
-2025 19:10:20","24-04-2025 18:58:59","24-04-2025 18:59:59","Cascaded Incid=
ent from TTO4987458 - Cascade Removed From TTO4987458","Kemeni Franklin",""=
,"","","","No power issue on site U=3D56,3v site on gen Tx fme Freddy 69041=
9006 of huawei is informed","system","681","24-04-2025 19:10:20","MATECH CM=
R"
"Resolved","Site Down","","IHS_YND_419","NOCINC0004876133","Ngog Mapubi",""=
,"24-04-2025 19:10:19","24-04-2025 18:58:59","24-04-2025 18:59:59","Cascade=
d Incident from TTO4987458 - Cascade Removed From TTO4987458","Kemeni Frank=
lin","","","","","No power issue on site U=3D56,3v site on gen Tx fme Fredd=
y 690419006 of huawei is informed","system","680","24-04-2025 19:10:19","MA=
TECH CMR"
"Resolved","Site Down","","IHS_YND_453","NOCINC0004876136","Song-bong","","=
24-04-2025 19:10:19","24-04-2025 18:58:59","24-04-2025 18:59:59","Cascaded =
Incident from TTO4987458 - Cascade Removed From TTO4987458","Kemeni Frankli=
n","","","","","No power issue on site U=3D56,3v site on gen Tx fme Freddy =
690419006 of huawei is informed","system","680","24-04-2025 19:10:19","MATE=
CH CMR"
"Resolved","Site Down","","IHS_YND_377","NOCINC0004876135","Eseka OCM","","=
24-04-2025 19:10:19","24-04-2025 18:58:59","24-04-2025 18:59:59","Cascaded =
Incident from TTO4987458 - Cascade Removed From TTO4987458","Kemeni Frankli=
n","","","","","No power issue on site U=3D56,3v site on gen Tx fme Freddy =
690419006 of huawei is informed","system","680","24-04-2025 19:10:19","MATE=
CH CMR"
"Resolved","Site Down","","IHS_YND_378","NOCINC0004876132","Eseka Town","",=
"24-04-2025 19:10:19","24-04-2025 18:58:59","24-04-2025 18:59:59","Cascaded=
 Incident from TTO4987458 - Cascade Removed From TTO4987458","Kemeni Frankl=
in","","","","","No power issue on site U=3D56,3v site on gen Tx fme Freddy=
 690419006 of huawei is informed","system","680","24-04-2025 19:10:19","MAT=
ECH CMR"
"Resolved","Site Down","","IHS_YND_381","NOCINC0004876134","Boumnyebel","",=
"24-04-2025 19:10:19","24-04-2025 18:58:59","24-04-2025 18:59:59","Cascaded=
 Incident from TTO4987458 - Cascade Removed From TTO4987458","Kemeni Frankl=
in","","","","","No power issue on site U=3D56,3v site on gen Tx fme Freddy=
 690419006 of huawei is informed","system","680","24-04-2025 19:10:19","MAT=
ECH CMR"
"Resolved","Site Down","","IHS_YND_380","NOCINC0004876131","Boumnyebel OCM"=
,"","24-04-2025 19:10:18","24-04-2025 18:58:59","24-04-2025 18:59:59","Casc=
aded Incident from TTO4987458 - Cascade Removed From TTO4987458","Kemeni Fr=
anklin","","","","","No power issue on site U=3D56,3v site on gen Tx fme Fr=
eddy 690419006 of huawei is informed","system","679","24-04-2025 19:10:18",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0004876040","M=
volye-New","","24-04-2025 18:53:10","24-04-2025 18:51:03","24-04-2025 19:05=
:45","Active// No power Issue Site on Grid Ubai =3D51,6 V, The TX FME Mbah =
Hosiah (674007438) is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site=
 on Grid Ubai =3D51,6 V, The TX FME Mbah Hosiah (674007438) is informed","c=
hristelle.ngonga@matech-cameroun.com","128","24-04-2025 18:53:10","MATECH C=
MR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004876011","Nko=
abang2","","24-04-2025 18:48:20","24-04-2025 18:42:50","24-04-2025 19:35:50=
","Grid outage .site went down due to bad grid voltage//We bypass grid and =
gen manually started","Mba Lazare Herve","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","Grid outage .site went down due to =
bad grid voltage//We bypass grid and gen manually started","franck.nkomot@m=
atech-cameroun.com","331","24-04-2025 18:48:20","MATECH CMR"
"Closed Complete","Site Down","CTR_431","IHS_YND_321","NOCINC0004875982","S=
oa","","24-04-2025 18:44:53","24-04-2025 18:43:46","24-04-2025 18:53:46","S=
ite down because  of short circuit in the PSC3 controler  //   REPLACING TH=
E PHASE CONTROLLER RELAY","Siligap Boris","Equipment Repair","Passive","Con=
trol Panel","Relay","Site down because  of short circuit in the PSC3 contro=
ler  //   REPLACING THE PHASE CONTROLLER RELAY","christelle.ngonga@matech-c=
ameroun.com","67","24-04-2025 18:44:53","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004875969","E=
ssomba","","24-04-2025 18:40:54","24-04-2025 18:39:45","24-04-2025 21:05:34=
","Site went down because 02/05 rectifier dysfonction on sitE // He reset 0=
1/05 rectifier and replaced 01/05 rectifier","Mba Lazare Herve","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down because 02=
/05 rectifier dysfonction on sitE // He reset 01/05 rectifier and replaced =
01/05 rectifier","christelle.ngonga@matech-cameroun.com","70","24-04-2025 1=
8:40:54","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004875887","E=
koumdoum OCM","","24-04-2025 18:26:33","24-04-2025 18:10:26","24-04-2025 20=
:30:26","Grid fluctuations, site down due to Gen Overload // Grid return","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid fluctuations, site down due to Gen Overload // Grid return","christelle=
.ngonga@matech-cameroun.com","968","24-04-2025 18:26:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0004875849","Mendong =
vallee","","24-04-2025 18:14:11","24-04-2025 17:48:56","24-04-2025 19:39:40=
","Grid outage site went down due to Gen Overload (20Kva) // Grid return","=
Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gri=
d outage site went down due to Gen Overload (20Kva) // Grid return","christ=
elle.ngonga@matech-cameroun.com","1516","24-04-2025 18:14:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004875816","Odza II =
OCM","","24-04-2025 18:07:47","24-04-2025 17:33:43","24-04-2025 18:01:43","=
Cascaded Incident from TTO4987028","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site down because  new batteries be=
have as Poor battery backup ( it does not carry the site during the change =
over ) // Grid restored","system","275498","24-04-2025 18:07:47","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0004875812","Mbedoumo=
u - Ekali","","24-04-2025 18:07:46","24-04-2025 17:33:43","24-04-2025 18:01=
:43","Cascaded Incident from TTO4987028","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site down because  new batter=
ies behave as Poor battery backup ( it does not carry the site during the c=
hange over ) // Grid restored","system","275499","24-04-2025 18:07:46","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004875751","Mehanda =
1","","24-04-2025 17:49:38","24-04-2025 17:33:43","24-04-2025 19:17:43","",=
"Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade Passi=
ve","Site down because  new batteries behave as Poor battery backup ( it do=
es not carry the site during the change over ) // Grid restored","system","=
275498","24-04-2025 17:49:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004875753","ODZA MIN=
KAN EDIBI ASSI","","24-04-2025 17:49:38","24-04-2025 17:33:43","24-04-2025 =
18:01:43","Cascaded Incident from TTO4987028","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site down because  new b=
atteries behave as Poor battery backup ( it does not carry the site during =
the change over ) // Grid restored","system","275498","24-04-2025 17:49:38"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004875752","Odza Min=
kan IHS","","24-04-2025 17:49:38","24-04-2025 17:33:43","24-04-2025 18:01:4=
3","Cascaded Incident from TTO4987028","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site down because  new batterie=
s behave as Poor battery backup ( it does not carry the site during the cha=
nge over ) // Grid restored","system","275499","24-04-2025 17:49:38","MATEC=
H CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004875732","Nko=
lnda","IHS_YND_343, IHS_YND_746, IHS_YND_527, IHS_YND_715, IHS_YND_749","24=
-04-2025 17:47:50","24-04-2025 17:33:43","24-04-2025 19:17:43","Grid outage=
 Site went down before Gen start due to poor backup // Grid return","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery"=
,"Site down because  new batteries behave as Poor battery backup ( it does =
not carry the site during the change over ) // Grid restored","franck.nkomo=
t@matech-cameroun.com","848","24-04-2025 17:47:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004875719","Mom","",=
"24-04-2025 17:45:51","24-04-2025 17:37:42","24-04-2025 17:43:42","Cascaded=
 Incident from TTO4986995","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Impacted by NGOUMOU impacts that ihs does not ma=
nage","system","268110","24-04-2025 17:45:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004875717","OTELE MT=
N","","24-04-2025 17:45:51","24-04-2025 17:37:42","24-04-2025 17:43:42","Ca=
scaded Incident from TTO4986995","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Impacted by NGOUMOU impacts that ihs does =
not manage","system","268111","24-04-2025 17:45:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004875716","OLAMA","=
","24-04-2025 17:45:51","24-04-2025 17:37:42","24-04-2025 17:43:42","Cascad=
ed Incident from TTO4986995","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Impacted by NGOUMOU impacts that ihs does not =
manage","system","268110","24-04-2025 17:45:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004875718","Minka","=
","24-04-2025 17:45:51","24-04-2025 17:37:42","24-04-2025 17:43:42","Cascad=
ed Incident from TTO4986995","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Impacted by NGOUMOU impacts that ihs does not =
manage","system","268110","24-04-2025 17:45:51","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004875702","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","24-04-2025 17:42:=
52","24-04-2025 17:37:42","24-04-2025 19:27:07","Impacted by NGOUMOU that i=
hs does not manage","Fanda Brice","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","Affected by 3rd Party Site","Impacted by NGOUMOU t=
hat ihs does not manage","franck.nkomot@matech-cameroun.com","311","24-04-2=
025 17:42:52","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004875669","Eto=
ug ebe Carrefour","","24-04-2025 17:36:09","24-04-2025 17:30:47","24-04-202=
5 17:48:47","Grid outage, site went down due to high temp alarm on gen // h=
e added water and started manually Gen","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid=
 outage, site went down due to high temp alarm on gen // he added water and=
 started manually Gen","franck.nkomot@matech-cameroun.com","322","24-04-202=
5 17:36:09","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0004875412","E=
toudi","","24-04-2025 17:03:37","24-04-2025 16:59:26","24-04-2025 17:03:30"=
,"Grid Low voltage  ,site went down because Gen fails to start due to grid =
 low voltage //Grid stabilisation","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Low Current Supply","Grid Low voltage  ,site went=
 down because Gen fails to start due to grid  low voltage //Grid stabilisat=
ion","christelle.ngonga@matech-cameroun.com","252","24-04-2025 17:03:37","M=
ATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0004875409","Sac=
re Coeur Catholic Church","","24-04-2025 17:03:04","24-04-2025 16:53:42","2=
4-04-2025 19:27:52","Active//No power issue, site is on Grid with Ubaie 1=
=3D48.2V and Ubaie 2=3D50.9V.. The Tx FME Brice Tsague (650214096) from Hua=
wei is informed.","Mboua Thierry","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, site =
is on Grid with Ubaie 1=3D48.2V and Ubaie 2=3D50.9V.. The Tx FME Brice Tsag=
ue (650214096) from Huawei is informed.","franck.nkomot@matech-cameroun.com=
","563","24-04-2025 17:03:04","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004875407","O=
mnisport-Rail","","24-04-2025 17:02:54","24-04-2025 17:00:48","24-04-2025 1=
7:03:32","No power issue on site Ubaie =3D49,3V site on Grid The TX FME Arm=
and Nguetsa (699949553) from huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Ubaie =3D49,3V site on Grid The TX FME Armand Ng=
uetsa (699949553) from huawei is informed.","christelle.ngonga@matech-camer=
oun.com","127","24-04-2025 17:02:54","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0004875291","Men=
dong Plateau","","24-04-2025 16:44:50","24-04-2025 16:39:20","24-04-2025 17=
:18:20","Site went down because gen stopped with low oil pressure//he added=
 oil and started the gen","Hyemafo Gildas","Equipment Repair","Passive","AC=
DG Gen","ACDG - Low Oil Pressure","Site went down because gen stopped with =
low oil pressure//he added oil and started the gen","franck.nkomot@matech-c=
ameroun.com","331","24-04-2025 16:44:50","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004875201","A=
wae Ewonkan","","24-04-2025 16:23:56","24-04-2025 16:20:49","24-04-2025 16:=
25:38","Grid outage site went down due to Gen Overload (20Kva, load 310 A) =
// Grid restoration","Albran Byorel","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid outage site went down due to Gen Overload (20Kva,=
 load 310 A) // Grid restoration","christelle.ngonga@matech-cameroun.com","=
188","24-04-2025 16:23:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004875121","Angongo"=
,"","24-04-2025 16:13:58","24-04-2025 15:15:26","24-04-2025 16:19:22","Casc=
aded Incident from TTO4986301","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down due to high t=
emp Alarm  caused by accordion cut // He welded accordion and added water, =
Gen started manually","system","312323","24-04-2025 16:13:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004875105","Ebeba","=
IHS_YND_335","24-04-2025 16:10:37","24-04-2025 15:15:26","24-04-2025 16:19:=
22","Grid outage, site went down due to high temp Alarm  caused by accordio=
n cut // He welded accordion and added water, Gen started manually","Fanda =
Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Grid outage, site went down due to high temp Alarm  ca=
used by accordion cut // He welded accordion and added water, Gen started m=
anually","christelle.ngonga@matech-cameroun.com","3312","24-04-2025 16:10:3=
7","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004875056","H=
-General-Yde","","24-04-2025 16:04:55","24-04-2025 16:00:27","24-04-2025 19=
:01:29","No power issue site on grid with U=3D54v Symphorien from Huawei is=
 informed","Siligap Boris","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54v Symphorien from Huawei is informed","christelle.ngonga@matech-camero=
un.com","269","24-04-2025 16:04:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004874922","Angongo"=
,"","24-04-2025 15:45:58","24-04-2025 13:43:29","24-04-2025 14:04:29","Casc=
aded Incident from TTO4985144","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen s=
tart and stopped due to high temp // He added water and manually start the =
gen","system","274747","24-04-2025 15:45:58","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004874803","E=
koumdoum","","24-04-2025 15:29:40","24-04-2025 15:28:34","24-04-2025 15:30:=
02","Site down due to Grid Low voltage, Gen Did not receive oder to start /=
/ Grid stabilisation","Albran Byorel","Grid Supply","Passive","Grid","Natio=
nal Grid - Low Current Supply","Site down due to Grid Low voltage, Gen Did =
not receive oder to start // Grid stabilisation","christelle.ngonga@matech-=
cameroun.com","67","24-04-2025 15:29:40","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0004874764","E=
toug ebe Meweulo","","24-04-2025 15:24:19","24-04-2025 15:19:10","24-04-202=
5 15:24:43","Grid outage gen failed to start due to alarm ''unbalance'//We =
rest card GE and gen Manually started","Hyemafo Gildas","Grid Supply","Pass=
ive","Grid","National Grid - Low Current Supply","Site down due to Grid Low=
 voltage,  Gen Did not receive oder to start // Grid stabilisation","christ=
elle.ngonga@matech-cameroun.com","309","24-04-2025 15:24:19","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004874722","Nko=
lbong","","24-04-2025 15:20:28","24-04-2025 15:12:05","24-04-2025 17:34:41"=
,"No power issue on site, site on Grid with Ubaie=3D51.8 V The TX FME SYNPH=
ORIEN /615295205 of Huawei is informed.","Delor Telezing","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site, site on Grid with Ubaie=3D51.8 V The TX FME SYNPHORIEN /=
615295205 of Huawei is informed.","franck.nkomot@matech-cameroun.com","504"=
,"24-04-2025 15:20:28","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004874530","M=
elen Ba'aba","","24-04-2025 14:50:30","24-04-2025 11:25:19","24-04-2025 12:=
36:40","Grid outage.gen gailed to start due to belt cut//We change belt and=
 site on gen","Siligap Boris","Equipment Repair","Passive","Infrastructure"=
,"Armoured Cable","Site went down due to released and chafed belt // he rep=
laced it by a new belt","franck.nkomot@matech-cameroun.com","12313","24-04-=
2025 14:50:30","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004874231","Men=
dong vallee","","24-04-2025 14:16:41","24-04-2025 14:07:35","24-04-2025 16:=
06:53","Grid outage ,Site down due to malfonction of pwc // he reset and pu=
t the site on gen","Fanda Brice","Equipment Repair","Passive","Control Pane=
l","Panel Distribution Board","Grid outage ,Site down due to malfonction of=
 pwc // he reset and put the site on gen","loic.noumsi@matech-cameroun.com"=
,"3962","24-04-2025 14:16:41","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004874100","E=
beba","IHS_YND_335","24-04-2025 13:53:37","24-04-2025 13:43:29","24-04-2025=
 14:04:29","Grid outage, site went down because gen start and stopped due t=
o high temp // He added water and manually start the gen","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Clogged Rad=
iator","Grid outage, site went down because gen start and stopped due to hi=
gh temp // He added water and manually start the gen","loic.noumsi@matech-c=
ameroun.com","609","24-04-2025 13:53:37","MATECH CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0004873959","NYA=
NON/DEMBO","","24-04-2025 13:26:44","24-04-2025 13:19:18","24-04-2025 13:41=
:45","Active// no power issue on site ,site on Gen with Ubaie=3D54.3V The T=
x FME Gregroire (654547479) from Hauawei is informed,","TIENTCHEU NZETCHIEU=
 GAEL","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active// no power issue on site ,site on Gen with Ubaie=
=3D54.3V The Tx FME Gregroire (654547479) from Hauawei is informed,","ludiv=
ine.ngamaleu@ihstowers.com","447","24-04-2025 13:26:44","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004873712","B=
iteng-Maetur","","24-04-2025 13:02:30","24-04-2025 12:54:20","24-04-2025 13=
:17:00","Active//No power issue, Ubay:54V on grid, Tx FME Henry//699949693 =
From huawei is  on site and Notice that we have disjunction at BTS OCM // H=
e rearm it","Mba Lazare Herve","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, Ubay:54V=
 on grid, Tx FME Henry//699949693 From huawei is  on site and Notice that w=
e have disjunction at BTS OCM // He rearm it","gaelle.njiofack@matech-camer=
oun.com","492","24-04-2025 13:02:30","MATECH CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004873700","Aha=
la","","24-04-2025 13:00:57","24-04-2025 12:49:39","24-04-2025 13:13:28","G=
rid outage, site went down due to fuel shortage // Refuelling done","Hyemaf=
o Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, si=
te went down due to fuel shortage // Refuelling done","loic.noumsi@matech-c=
ameroun.com","767","24-04-2025 13:00:57","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004873690","Eto=
ug ebe Carrefour","","24-04-2025 12:57:43","24-04-2025 12:51:36","24-04-202=
5 14:05:39","Grid outage, site went down due to high temp alarm on gen // h=
e added water and started manually Gen","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid=
 outage, site went down due to high temp alarm on gen // he added water and=
 started manually Gen","loic.noumsi@matech-cameroun.com","367","24-04-2025 =
12:57:43","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004873626","N=
KOLMEKONG YDE","","24-04-2025 12:42:27","24-04-2025 12:33:05","24-04-2025 1=
6:31:29"," Grid outage , gen fail to start due to AVR faulty //  Grid resto=
ration ,  AVR to be replaced","Fabrice Pouakam","Equipment Repair","Passive=
","ACDG Gen","ACDG - AVR"," Grid outage , gen fail to start due to AVR faul=
ty //  Grid restoration ,  AVR to be replaced","gaelle.njiofack@matech-came=
roun.com","564","24-04-2025 12:42:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004873606","Angongo"=
,"","24-04-2025 12:40:03","24-04-2025 12:13:50","24-04-2025 12:41:35","Casc=
aded Incident from TTO4984454","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen s=
tart and stopped due to high temp // He added water and manually start the =
gen","system","265879","24-04-2025 12:40:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004873563","MEHANDAN=
","","24-04-2025 12:32:43","24-04-2025 12:25:13","24-04-2025 12:43:54","Cas=
caded Incident from TTO4984519","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Fme, RM are informed and reported that=
 new batteries behave as Poor battery backup // Grid restored","system","26=
5083","24-04-2025 12:32:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0004873562","Mbedoumo=
u - Ekali","","24-04-2025 12:32:43","24-04-2025 12:25:13","24-04-2025 12:43=
:54","Cascaded Incident from TTO4984519","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Fme, RM are informed and repo=
rted that new batteries behave as Poor battery backup // Grid restored","sy=
stem","265084","24-04-2025 12:32:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004873564","Odza II =
OCM","","24-04-2025 12:32:43","24-04-2025 12:25:13","24-04-2025 12:43:54","=
Cascaded Incident from TTO4984519","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Fme, RM are informed and reported t=
hat new batteries behave as Poor battery backup // Grid restored","system",=
"265084","24-04-2025 12:32:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004873555","ODZA MIN=
KAN EDIBI ASSI","","24-04-2025 12:30:25","24-04-2025 12:25:13","24-04-2025 =
12:43:54","Cascaded Incident from TTO4984519","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Fme, RM are informed and=
 reported that new batteries behave as Poor battery backup // Grid restored=
","system","265084","24-04-2025 12:30:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004873553","Mehanda =
1","","24-04-2025 12:30:24","24-04-2025 12:25:13","24-04-2025 12:43:54","Ca=
scaded Incident from TTO4984519","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Fme, RM are informed and reported tha=
t new batteries behave as Poor battery backup // Grid restored","system","2=
65083","24-04-2025 12:30:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004873554","Odza Min=
kan IHS","","24-04-2025 12:30:24","24-04-2025 12:25:13","24-04-2025 12:43:5=
4","Cascaded Incident from TTO4984519","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Fme, RM are informed and report=
ed that new batteries behave as Poor battery backup // Grid restored","syst=
em","265083","24-04-2025 12:30:24","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004873540","Nko=
lnda","IHS_YND_343, IHS_YND_528, IHS_YND_746, IHS_YND_527, IHS_YND_715, IHS=
_YND_749","24-04-2025 12:28:26","24-04-2025 12:25:13","24-04-2025 12:43:54"=
,"Fme, RM are informed and reported that new batteries behave as Poor batte=
ry backup // Grid restored","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Battery","Fme, RM are informed and reported that new b=
atteries behave as Poor battery backup // Grid restored","loic.noumsi@matec=
h-cameroun.com","194","24-04-2025 12:28:26","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004873492","E=
beba","IHS_YND_335","24-04-2025 12:19:08","24-04-2025 12:13:50","24-04-2025=
 12:41:35","Grid outage, site went down because gen start and stopped due t=
o high temp // He added water and manually start the gen","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Grid outage, site went down because gen start and stopped due to=
 high temp // He added water and manually start the gen","loic.noumsi@matec=
h-cameroun.com","319","24-04-2025 12:19:08","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004873406","N=
yom OCM","","24-04-2025 12:00:42","24-04-2025 11:57:30","24-04-2025 13:39:5=
8","Grid outage, Gen failed to start due to Malfunction of Gen card // Gen =
card reset and Gen start manually","Fabrice Pouakam","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen failed to start =
due to Malfunction of Gen card // Gen card reset and Gen start manually","g=
aelle.njiofack@matech-cameroun.com","194","24-04-2025 12:00:42","MATECH CMR=
"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004873348","Nom=
ayos montee Meche","","24-04-2025 11:50:01","24-04-2025 11:43:51","24-04-20=
25 11:52:14","Site went down due to poor backup battery // grid returned","=
Fanda Brice","Equipment Repair","Passive","Control Panel","Power Cabinet - =
Battery Low","Site went down due to poor backup battery // grid returned","=
loic.noumsi@matech-cameroun.com","371","24-04-2025 11:50:01","MATECH CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0004873286","OLA=
MA","","24-04-2025 11:33:30","24-04-2025 10:59:20","24-04-2025 13:26:07","G=
rid outage site went down because Gen failed to start due to Gen card fault=
y // Gen Manually Started","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid outage site went down because Gen failed=
 to start due to Gen card faulty // Gen Manually Started","gaelle.njiofack@=
matech-cameroun.com","2502","24-04-2025 11:33:30","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004873262","NTU=
I TOWN","","24-04-2025 11:29:44","24-04-2025 11:22:36","24-04-2025 13:31:47=
","Site went down because gen fails to start due to grid bad voltage // He =
bypassed grid and manually started the gen","Parker Tchoup","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Site went down b=
ecause gen fails to start due to grid bad voltage // He bypassed grid and m=
anually started the gen","ludivine.ngamaleu@ihstowers.com","429","24-04-202=
5 11:29:44","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004873250","C=
omplexe-BEAC","","24-04-2025 11:28:42","24-04-2025 11:17:27","24-04-2025 12=
:36:39","Grid fluctuation Site down because gen fail to start due to Grid b=
ad voltage // Gen started manually.","Albran Byorel","Grid Supply","Passive=
","Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuation Sit=
e down because gen fail to start due to Grid bad voltage // Gen started man=
ually.","gaelle.njiofack@matech-cameroun.com","676","24-04-2025 11:28:42","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004873155","Song-bon=
g","","24-04-2025 11:14:26","24-04-2025 10:56:59","24-04-2025 12:49:16","Ca=
scaded Incident from TTO4984042","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to Gen=
 card faulty // Gen start Mnually and Gen card will be replaced","system","=
270266","24-04-2025 11:14:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004873154","Eseka To=
wn","","24-04-2025 11:14:26","24-04-2025 10:56:59","24-04-2025 12:49:16","C=
ascaded Incident from TTO4984042","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Gen stopped due to Ge=
n card faulty // Gen start Mnually and Gen card will be replaced","system",=
"270266","24-04-2025 11:14:26","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0004873146","E=
seka OCM","IHS_YND_378, IHS_YND_453","24-04-2025 11:12:15","24-04-2025 10:5=
6:59","24-04-2025 12:49:16","Grid outage, Gen stopped due to Gen card fault=
y // Gen start Mnually and Gen card will be replaced","Kemeni Franklin","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, G=
en stopped due to Gen card faulty // Gen start Mnually and Gen card will be=
 replaced","gaelle.njiofack@matech-cameroun.com","917","24-04-2025 11:12:15=
","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004873051","M=
ontee-Des-Soeurs","","24-04-2025 10:53:49","24-04-2025 10:48:37","24-04-202=
5 13:35:28","Grid fluctuation,Site went down because GEN failed to start du=
e to grid bad voltage(lack of 01 phase)// He did a bridge on the good phase=
","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation,Site went down because GEN failed to sta=
rt due to grid bad voltage(lack of 01 phase)// He did a bridge on the good =
phase","loic.noumsi@matech-cameroun.com","314","24-04-2025 10:53:49","MATEC=
H CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0004873033","Ngo=
ulmekong-Nord","","24-04-2025 10:51:15","24-04-2025 10:48:06","24-04-2025 1=
0:52:34","site impacted by Mballa 4","Siligap Boris","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","Affected by 3rd Party Site","si=
te impacted by Mballa 4","gaelle.njiofack@matech-cameroun.com","190","24-04=
-2025 10:51:15","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004872934","Odz=
a petit marche new","","24-04-2025 10:33:43","24-04-2025 10:25:31","24-04-2=
025 10:41:31","Site went down due to insufficient rectifiers on site//Site =
stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to insufficient rectifiers on site//Site s=
tabilized","ludivine.ngamaleu@ihstowers.com","493","24-04-2025 10:33:43","M=
ATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004872909","SAA=
 Entrance","","24-04-2025 10:29:33","24-04-2025 10:09:52","24-04-2025 11:18=
:45","Grid outage, Site went down because Gen failed to start due to batter=
y Gen faulty // He replaced it  with a NEW battery, site on Gen","Parker Tc=
houp","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","G=
rid outage, Site went down because Gen failed to start due to battery Gen f=
aulty // He replaced it  with a NEW battery, site on Gen","loic.noumsi@mate=
ch-cameroun.com","1183","24-04-2025 10:29:33","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004872637","Eki=
e sud","","24-04-2025 09:58:42","24-04-2025 09:52:22","24-04-2025 12:13:25"=
,"Grid outage, site went down due to fuel shortage // Refuelling done","Alb=
ran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, =
site went down due to fuel shortage // Refuelling done","loic.noumsi@matech=
-cameroun.com","381","24-04-2025 09:58:42","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004872393","M=
elen Ba'aba","","24-04-2025 09:18:10","24-04-2025 09:00:58","24-04-2025 10:=
09:42","Grid outage.gen gailed to start due to belt cut//We change belt and=
 site on gen","Siligap Boris","Equipment Repair","Passive","Infrastructure"=
,"Armoured Cable","site went down due to released belt // fme fixed it","lo=
ic.noumsi@matech-cameroun.com","1033","24-04-2025 09:18:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004872295","OLAMA","=
","24-04-2025 08:53:23","24-04-2025 08:46:31","24-04-2025 10:22:37","Cascad=
ed Incident from TTO4983088","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Gen stopped because engine is =
already very old // Gen Start manually (this site need a new Gen)","system"=
,"271170","24-04-2025 08:53:23","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004872292","Ako=
no","IHS_YND_687","24-04-2025 08:52:45","24-04-2025 08:46:31","24-04-2025 1=
0:22:37","Grid outage, Gen stopped because engine is already very old // Ge=
n Start manually (this site need a new Gen)","Fanda Brice","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage, Gen stopped=
 because engine is already very old // Gen Start manually (this site need a=
 new Gen)","gaelle.njiofack@matech-cameroun.com","375","24-04-2025 08:52:45=
","MATECH CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004872191","MAN=
GUIERS CHAPELLE","","24-04-2025 08:35:11","24-04-2025 08:33:01","24-04-2025=
 10:36:11","grid outage, site went down due to gen Overload(20KVA,270) // g=
rid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","grid outage, site went down due to gen Overload(20KVA,270) //=
 grid return","edwige.kapawo@matech-cameroun.com","132","24-04-2025 08:35:1=
1","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004872185","N=
kolfon Cimencam","","24-04-2025 08:32:59","24-04-2025 08:28:51","24-04-2025=
 09:17:45","Active//No power issue on site U=3D54,5v site on Gen The TX fme=
 George(697461814) from huawei is informed. Noticed that site is impacted b=
y Afanoya (Not manage by HIS)","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue on site U=3D54,5v site on Gen The TX fme George(697461814) from hua=
wei is informed. Noticed that site is impacted by Afanoya (Not manage by HI=
S)","edwige.kapawo@matech-cameroun.com","249","24-04-2025 08:32:59","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004872183","Mimboman=
4","","24-04-2025 08:32:32","24-04-2025 08:24:41","24-04-2025 09:32:21","Ca=
scaded Incident from TTO4982973","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on Gen with U=3D5=
3.5V The FME Tx Lionel Steve /655184876/ From huawei is informed.","system"=
,"272429","24-04-2025 08:32:32","MATECH CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004872182","Nko=
lo II New","IHS_YND_266","24-04-2025 08:32:01","24-04-2025 08:24:41","24-04=
-2025 09:32:21","No power issue site on Gen with U=3D53.5V The FME Tx Lione=
l Steve /655184876/ From huawei is informed.","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue site on Gen with U=3D53.5V The FME Tx Lionel Steve /655184=
876/ From huawei is informed.","ludivine.ngamaleu@ihstowers.com","441","24-=
04-2025 08:32:01","MATECH CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004872180","Mvo=
g-Betsi","","24-04-2025 08:31:23","24-04-2025 08:28:13","24-04-2025 09:20:3=
3","Ticket error","Hyemafo Gildas","Incorrectly Logged Tickets","Error","Er=
ror","Error","Ticket error","edwige.kapawo@matech-cameroun.com","190","24-0=
4-2025 08:31:23","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004872177","Tsi=
nga village","","24-04-2025 08:30:45","24-04-2025 08:28:38","24-04-2025 12:=
03:29","Active // No power issue UBaie =3D54,7V site on Grid The FME TX Jul=
ien (693095849) From Huawei is informed","Delor Telezing","Customer Equipme=
nt Failure","Active","Active Equipment Failure","Fibre Failure","Active // =
No power issue UBaie =3D54,7V site on Grid The FME TX Julien (693095849) Fr=
om Huawei is informed","edwige.kapawo@matech-cameroun.com","128","24-04-202=
5 08:30:45","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004872151","Nko=
lbisson usines des eaux 2","","24-04-2025 08:22:17","24-04-2025 08:18:25","=
24-04-2025 08:26:07","Site went down due to planned work consisting to repl=
ace CB 125 A by another CB 125A // work done","TIENTCHEU NZETCHIEU GAEL","E=
quipment Replacement","Passive","Planned Activity","Planned Activity - Pass=
ive","Site went down due to planned work consisting to replace CB 125 A by =
another CB 125A // work done","loic.noumsi@matech-cameroun.com","233","24-0=
4-2025 08:22:17","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004872135","E=
lig-Edzoa","","24-04-2025 08:16:22","24-04-2025 08:07:14","24-04-2025 08:34=
:31","Grid only site went down due to Grid outage // Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e went down due to Grid outage // Grid return","loic.noumsi@matech-cameroun=
.com","550","24-04-2025 08:16:22","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004872124","M=
essa-Carriere OCM","","24-04-2025 08:14:24","24-04-2025 08:07:18","24-04-20=
25 08:21:37","No power issue site on grid with U=3D52V, FME TX Mohamadou/69=
1144435/ from Huawei is informed.","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gr=
id with U=3D52V, FME TX Mohamadou/691144435/ from Huawei is informed.","edw=
ige.kapawo@matech-cameroun.com","428","24-04-2025 08:14:24","MATECH CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0004872057","Mba=
lla 4","","24-04-2025 08:02:02","24-04-2025 07:58:50","24-04-2025 08:56:13"=
,"Active: No power issue, site is on grid with Ubaie=3D54.3V, Armand nguets=
a 691144412) from Huawei is informed","Delor Telezing","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No power issue, site is on grid with Ubaie=3D54.3V, Armand nguetsa (6911444=
12) from Huawei is informed","loic.noumsi@matech-cameroun.com","193","24-04=
-2025 08:02:02","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0004871989","Ngo=
usso-Savana","","24-04-2025 07:49:44","24-04-2025 07:42:37","24-04-2025 07:=
50:41","site impacted by Mballa 4","Siligap Boris","Customer Equipment Fail=
ure","Active","Active Equipment Failure","Affected by 3rd Party Site","site=
 impacted by Mballa 4","loic.noumsi@matech-cameroun.com","427","24-04-2025 =
07:49:44","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004871933","Odz=
a petit marche new","","24-04-2025 07:38:21","24-04-2025 06:28:13","24-04-2=
025 08:40:46","Grid outage,site went down due to Rectifier dysfunctionning =
on site //He reset it and site on Grid","Albran Byorel","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","	Grid outage,site went=
 down due to Rectifier dysfunctionning on site //He reset it and site on Gr=
id","ludivine.ngamaleu@ihstowers.com","4209","24-04-2025 07:38:21","MATECH =
CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004871780","Nko=
g-Edzen","","24-04-2025 07:08:15","24-04-2025 06:59:06","24-04-2025 07:09:4=
9","No power issue on site, site on Battery with U=3D54V The Tx Fme Gregoir=
e (654547479) from Huawei is informed.","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site, site on Battery with U=3D54V The Tx Fme Gregoire (65454747=
9) from Huawei is informed.","ludivine.ngamaleu@ihstowers.com","549","24-04=
-2025 07:08:15","MATECH CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0004871736","N=
goum","","24-04-2025 06:58:21","24-04-2025 06:54:12","24-04-2025 07:40:30",=
"Solar Hybrid GEN site, No power issue site on Gen, with U=3D52.7V. The Tx =
Fme Gregoire (654547479) from Huawei informed","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Solar Hybrid GEN site, No power issue site on Gen, with U=3D52.7V. The Tx F=
me Gregoire (654547479) from Huawei informed","edwige.kapawo@matech-camerou=
n.com","251","24-04-2025 06:58:21","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004871708","NTE=
MASSI","","24-04-2025 06:53:12","24-04-2025 06:30:34","24-04-2025 06:52:03"=
,"Grid outage // Grid return","Delor Telezing","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue","Grid outage // Grid return","ludivi=
ne.ngamaleu@ihstowers.com","1359","24-04-2025 06:53:12","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004871660","M=
ontee-Des-Soeurs","","24-04-2025 06:37:46","24-04-2025 06:31:40","24-04-202=
5 06:37:12","Site was on Gen and not charge the New Battery Backup, site we=
nt down due to baterry backup completely discharged//Grid Restored	","Hyema=
fo Gildas","Equipment Repair","Passive","Control Panel","Power Cabinet - Ba=
ttery Low","Site was on Gen and not charge the New Battery Backup, site wen=
t down due to baterry backup completely discharged//Grid Restored	","edwige=
.kapawo@matech-cameroun.com","367","24-04-2025 06:37:46","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004871653","Odz=
a II OCM","","24-04-2025 06:36:34","24-04-2025 06:31:18","24-04-2025 06:49:=
05","Grid outage ,site went down because GEN failed to start due to ATS and=
 Gen card faulty // grid returned	","Albran Byorel","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went down becaus=
e GEN failed to start due to ATS and Gen card faulty // grid returned	","ge=
rard.tchangoue@matech-cameroun.com","1333","24-04-2025 06:36:34","MATECH CM=
R"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004871569","O=
mnisport-Rail","","24-04-2025 06:09:17","24-04-2025 05:36:04","24-04-2025 0=
7:41:01","Grid outage, Gen failed to start due to Alarm Low oil pressure //=
 Gen cart reset and site on Gen (Our fme will be on site for draining)","De=
lor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Press=
ure","Grid outage, Gen failed to start due to Alarm Low oil pressure // Gen=
 cart reset and site on Gen (Our fme will be on site for draining)","kouoh.=
jean@ihstowers.com","1994","24-04-2025 06:09:17","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004871505","O=
LAMA","","24-04-2025 05:49:36","24-04-2025 05:39:59","24-04-2025 06:01:41",=
"Active//No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","edwige.kapawo@matech-cameroun.com","578","24-04-=
2025 05:49:36","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004871396","Nko=
g-Edzen","","24-04-2025 05:08:59","24-04-2025 05:02:53","24-04-2025 05:16:5=
3","No power issue on site, site on Battery with U=3D54V The Tx Fme Gregoir=
e (654547479) from Huawei is informed.","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site, site on Battery with U=3D54V The Tx Fme Gregoire (65454747=
9) from Huawei is informed.","gerard.tchangoue@matech-cameroun.com","367","=
24-04-2025 05:08:59","MATECH CMR"
"Closed Complete","Site Down","CTR_694","IHS_YND_714","NOCINC0004871359","E=
kekam","","24-04-2025 04:57:17","24-04-2025 04:52:10","24-04-2025 07:37:31"=
,"Grid outage gen failed to start due to alarm high temp // We added water =
and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pa=
ssive","ACDG Gen","Gen Temp High","Grid outage gen failed to start due to a=
larm high temp because silent drilled // We added water and gen manually st=
arted","gerard.tchangoue@matech-cameroun.com","308","24-04-2025 04:57:17","=
MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0004871347","Evo=
doula MTN","","24-04-2025 04:53:52","24-04-2025 04:09:23","24-04-2025 04:59=
:23","Grid outage, site went down because gen start and stopped with Under =
voltage alarm // he Reset the Gen card and gen started Manually","TIENTCHEU=
 NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, site went down because gen start and stopped with Under =
voltage alarm // he Reset the Gen card and gen started Manually","gerard.tc=
hangoue@matech-cameroun.com","5041","24-04-2025 04:53:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_408","NOCINC0004871152","Evodoula=
 MTN","","24-04-2025 03:45:32","24-04-2025 02:14:59","24-04-2025 04:06:49",=
"fme is on the way ETA 04:55 AM","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage gen ran until =
fuel shortage//Refueling done","system","272800","24-04-2025 03:45:32","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004871133","Ngouetou=
","","24-04-2025 03:38:51","24-04-2025 02:12:54","24-04-2025 02:13:55","Cas=
caded Incident from TTO4981665","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","	No power issue. Site is on battery with =
U =3D 52.1V. TX FME Willy Ngouni 699759164 of Huawei is informed.","system"=
,"273064","24-04-2025 03:38:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004871134","MBIMBIM"=
,"","24-04-2025 03:38:51","24-04-2025 02:12:54","24-04-2025 02:13:55","Casc=
aded Incident from TTO4981665","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","	No power issue. Site is on battery with U=
 =3D 52.1V. TX FME Willy Ngouni 699759164 of Huawei is informed.","system",=
"273063","24-04-2025 03:38:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0004871132","Yoko OCM=
","","24-04-2025 03:38:50","24-04-2025 02:12:54","24-04-2025 02:13:55","Cas=
caded Incident from TTO4981665","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","	No power issue. Site is on battery with =
U =3D 52.1V. TX FME Willy Ngouni 699759164 of Huawei is informed.","system"=
,"273065","24-04-2025 03:38:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004871131","Matsari"=
,"","24-04-2025 03:38:50","24-04-2025 02:12:54","24-04-2025 02:13:55","Casc=
aded Incident from TTO4981665","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","	No power issue. Site is on battery with U=
 =3D 52.1V. TX FME Willy Ngouni 699759164 of Huawei is informed.","system",=
"273066","24-04-2025 03:38:50","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004871125","Meh=
anda 1","","24-04-2025 03:32:38","24-04-2025 03:22:59","24-04-2025 03:35:59=
","ACTIVE No power issue on site U=3D 53,2V site on grid the TX fme Lionnel=
 Steve / 655184876 from huawei is informed","Albran Byorel","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACT=
IVE No power issue on site U=3D 53,2V site on grid the TX fme Lionnel Steve=
 / 655184876 from huawei is informed","gerard.tchangoue@matech-cameroun.com=
","1414","24-04-2025 03:32:38","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004871118","Ebo=
go","","24-04-2025 03:28:43","24-04-2025 03:26:25","24-04-2025 03:50:25","A=
ctive// No Power issue on site Ubaie 53.2V site on Grid, Julien /693095849 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issu=
e on site Ubaie 53.2V site on Grid, Julien /693095849 from Huawei is inform=
ed","gerard.tchangoue@matech-cameroun.com","139","24-04-2025 03:28:43","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0004871077","B=
otmakak","IHS_EDA_101","24-04-2025 02:53:09","24-04-2025 02:45:00","24-04-2=
025 02:55:00","Active// No power issue, Site on Gen Ubai=3D 53.8V, The Tx E=
tienne/695033981/From Huawei is informed	","Kemeni Franklin","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue, Site on Gen Ubai=3D 53.8V, The Tx Etienne/695033981/=
From Huawei is informed	","edwige.kapawo@matech-cameroun.com","490","24-04-=
2025 02:53:09","MATECH CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004871075","S=
OA UNIVERSITY STADIUM","","24-04-2025 02:52:32","24-04-2025 02:47:16","24-0=
4-2025 02:54:08","Grid outage.site went down due to gen failed to start //G=
rid return","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","Grid outage.site went down due to gen failed to start //Gr=
id return","edwige.kapawo@matech-cameroun.com","317","24-04-2025 02:52:32",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004871071","M=
elen Ba'aba","","24-04-2025 02:50:40","24-04-2025 02:45:32","24-04-2025 02:=
58:41","Grid fluctuations, site went down because Gen failed to start due t=
o grid bad voltage and poor backup // Grid stabilised","Siligap Boris","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuations, site went down because Gen failed to start due to grid bad vo=
ltage and poor backup // Grid stabilised","edwige.kapawo@matech-cameroun.co=
m","309","24-04-2025 02:50:40","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004871063","Nko=
lnda","IHS_YND_528, IHS_YND_527, IHS_YND_715, IHS_YND_749","24-04-2025 02:4=
6:37","24-04-2025 02:22:33","24-04-2025 03:29:33"," Grid outage Site went d=
own before Gen start due to poor backup // Grid return","Albran Byorel","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site w=
as on Gen and not charge the New Battery Backup, site went down due to bate=
rry backup completely discharged//Grid Restored","gerard.tchangoue@matech-c=
ameroun.com","1470","24-04-2025 02:46:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004871055","OTELE MT=
N","","24-04-2025 02:44:22","24-04-2025 02:37:59","24-04-2025 02:47:59","Ca=
scaded Incident from TTO4981700","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on gen with U=3D55V No=
tice that site is impacted by Ngoumou who is not our responsability","syste=
m","264379","24-04-2025 02:44:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004871054","OLAMA","=
","24-04-2025 02:44:22","24-04-2025 02:37:59","24-04-2025 02:47:59","Cascad=
ed Incident from TTO4981700","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on gen with U=3D55V Notice=
 that site is impacted by Ngoumou who is not our responsability","system","=
264378","24-04-2025 02:44:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004871057","Akono","=
","24-04-2025 02:44:22","24-04-2025 02:37:59","24-04-2025 02:47:59","Cascad=
ed Incident from TTO4981700","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on gen with U=3D55V Notice=
 that site is impacted by Ngoumou who is not our responsability","system","=
264377","24-04-2025 02:44:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004871056","Mom","",=
"24-04-2025 02:44:22","24-04-2025 02:37:59","24-04-2025 02:47:59","Cascaded=
 Incident from TTO4981700","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on gen with U=3D55V Notice t=
hat site is impacted by Ngoumou who is not our responsability","system","26=
4377","24-04-2025 02:44:22","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0004871049","Min=
ka","IHS_YND_687, IHS_YND_531, IHS_YND_370, IHS_YND_365","24-04-2025 02:42:=
58","24-04-2025 02:37:59","24-04-2025 02:47:59","No power issue site on gen=
 with U=3D55V Notice that site is impacted by Ngoumou who is not our respon=
sability","Fanda Brice","Customer Equipment Failure","Active","Active Equip=
ment Failure","Affected by 3rd Party Site","No power issue site on gen with=
 U=3D55V Notice that site is impacted by Ngoumou who is not our responsabil=
ity","gerard.tchangoue@matech-cameroun.com","300","24-04-2025 02:42:58","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004871035","c=
hina embassy yde","","24-04-2025 02:38:02","24-04-2025 02:28:53","24-04-202=
5 02:40:55","No power issue site on Grid Ubay: 52.3V , site impacted by CBC=
_radio","","Customer Equipment Failure","Active","Active Equipment Failure"=
,"Affected by 3rd Party Site","No power issue site on Grid Ubay: 52.3V , si=
te impacted by CBC_radio","edwige.kapawo@matech-cameroun.com","550","24-04-=
2025 02:38:02","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004871027","ODZ=
A MINKAN EDIBI ASSI","","24-04-2025 02:35:11","24-04-2025 02:22:33","24-04-=
2025 02:54:59","","Albran Byorel","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Site was on Gen and not charge the New Battery Backu=
p, site went down due to baterry backup completely discharged//Grid Restore=
d","gerard.tchangoue@matech-cameroun.com","279731","24-04-2025 02:35:11","M=
ATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004871024","Odz=
a Minkan IHS","","24-04-2025 02:34:25","24-04-2025 02:22:33","24-04-2025 02=
:54:59","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Site was on Gen and not charge the New Battery Backup, site=
 went down due to baterry backup completely discharged//Grid Restored","ger=
ard.tchangoue@matech-cameroun.com","279730","24-04-2025 02:34:25","MATECH C=
MR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004871013","Ngo=
usso Vallee","","24-04-2025 02:28:18","24-04-2025 02:20:03","24-04-2025 05:=
22:26","Grid outage, DG stopped due with alarm ""oil pressure"" // He bypas=
sed grid and put site on Gen manually","Siligap Boris","Equipment Repair","=
Passive","ACDG Gen","ACDG - Oil Pressure Sensor Faulty","Grid outage, DG st=
opped due with alarm ""oil pressure"" // He bypassed grid and put site on G=
en manually","gerard.tchangoue@matech-cameroun.com","496","24-04-2025 02:28=
:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004871006","MEHANDAN=
","","24-04-2025 02:25:13","24-04-2025 02:22:02","24-04-2025 03:00:02","Cas=
caded Incident from TTO4981644","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,site went down because GE=
N failed to start due to ATS and Gen card faulty // grid returned	","system=
","279761","24-04-2025 02:25:13","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004871002","O=
dza II OCM","IHS_YND_528","24-04-2025 02:24:14","24-04-2025 02:22:02","24-0=
4-2025 03:38:33","Grid outage ,site went down because GEN failed to start d=
ue to ATS and Gen card faulty // grid returned	","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site wen=
t down because GEN failed to start due to ATS and Gen card faulty // grid r=
eturned	","edwige.kapawo@matech-cameroun.com","133","24-04-2025 02:24:14","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004870997","Leboudi"=
,"","24-04-2025 02:21:35","24-04-2025 02:19:59","24-04-2025 02:27:29","Casc=
aded Incident from TTO4981634","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue site on grid zit=
h U=3D54v Mohamadou from Huawei is informed site up at 02;27 AM","system","=
315976","24-04-2025 02:21:35","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004870995","N=
kolafeme","IHS_YND_309","24-04-2025 02:20:56","24-04-2025 02:19:59","24-04-=
2025 02:27:29","No power issue site on grid zith U=3D54v Mohamadou from Hua=
wei is informed site up at 02;27 AM","TIENTCHEU NZETCHIEU GAEL","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue site on grid zith U=3D54v Mohamadou from Huawei is informed=
 site up at 02;27 AM","edwige.kapawo@matech-cameroun.com","58","24-04-2025 =
02:20:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004870992","Ngoulmek=
ong-Nord","","24-04-2025 02:20:05","24-04-2025 02:13:02","24-04-2025 03:14:=
36","Cascaded Incident from TTO4981626","Siligap Boris","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","no power issue on site Ubay: 53V =
site on Grid THE TX FME SYMPHORIEN (650257151) from HUAWEI is informed	","s=
ystem","265879","24-04-2025 02:20:05","MATECH CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004870987","E=
leveur","IHS_YND_277","24-04-2025 02:19:17","24-04-2025 02:13:02","24-04-20=
25 03:14:36","no power issue on site Ubay: 53V site on Grid THE TX FME SYMP=
HORIEN (650257151) from HUAWEI is informed	","Siligap Boris","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no=
 power issue on site Ubay: 53V site on Grid THE TX FME SYMPHORIEN (65025715=
1) from HUAWEI is informed	","edwige.kapawo@matech-cameroun.com","376","24-=
04-2025 02:19:17","MATECH CMR"
"Closed Complete","Site Down","T0211","IHS_YND_393","NOCINC0004870984","Eze=
zang","IHS_YND_408","24-04-2025 02:18:00","24-04-2025 02:14:59","24-04-2025=
 04:06:49","Grid outage gen ran until fuel shortage//Refueling done","Parke=
r Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen=
 ran until fuel shortage//Refueling done","gerard.tchangoue@matech-cameroun=
.com","182","24-04-2025 02:18:00","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004870974","E=
koumdoum","","24-04-2025 02:15:01","24-04-2025 02:09:48","24-04-2025 02:15:=
33","Site down due to Grid low voltage , gen did not start // Grid stabiliz=
ation","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Unst=
able Grid Supply Issue","Site down due to Grid low voltage , gen did not st=
art // Grid stabilization","edwige.kapawo@matech-cameroun.com","314","24-04=
-2025 02:15:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004870961","Omnispor=
t-Rail","","24-04-2025 02:09:55","24-04-2025 02:04:55","24-04-2025 03:08:36=
","Cascaded Incident from TTO4981588","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down due=
 to gen Overload(20KVA,270) // grid return","system","280845","24-04-2025 0=
2:09:55","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004870959","M=
ANGUIERS CHAPELLE","IHS_YND_506","24-04-2025 02:09:06","24-04-2025 02:04:55=
","24-04-2025 03:09:57","site up awaiting feedback","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","grid outage, site wen=
t down due to gen Overload(20KVA,270) // grid return","edwige.kapawo@matech=
-cameroun.com","252","24-04-2025 02:09:06","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004870942","Ebo=
go","","24-04-2025 02:02:03","24-04-2025 01:53:59","24-04-2025 02:09:10","G=
rid outage,site went down before gen starts due to poor battery backup//Gri=
d return","Siligap Boris","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage,site went down before gen starts due=
 to poor battery backup//Grid return","gerard.tchangoue@matech-cameroun.com=
","485","24-04-2025 02:02:03","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004870899","SAA=
 Entrance","","24-04-2025 01:35:22","24-04-2025 01:27:59","24-04-2025 01:41=
:59","Grid outage site went down due to Gen failed to start//Grid return","=
Parker Tchoup","Grid Supply","Passive","Grid","National Grid - Grid Outage =
Issue","Grid outage site went down due to Gen failed to start//Grid return"=
,"gerard.tchangoue@matech-cameroun.com","444","24-04-2025 01:35:22","MATECH=
 CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004870739","Nko=
lbong","","24-04-2025 00:25:25","24-04-2025 00:21:19","24-04-2025 00:28:49"=
,"No power issue on site, site on Grid with Ubaie=3D52.7V The TX FME SYNPHO=
RIEN /615295205 of Huawei is informed.","Delor Telezing","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site, site on Grid with Ubaie=3D52.7V The TX FME SYNPHORIEN /61=
5295205 of Huawei is informed.","gerard.tchangoue@matech-cameroun.com","248=
","24-04-2025 00:25:25","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004870668","B=
arriere","","24-04-2025 00:13:04","24-04-2025 00:07:54","24-04-2025 00:31:5=
4","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed //Grid return","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and c=
onfirmed //Grid return","edwige.kapawo@matech-cameroun.com","311","24-04-20=
25 00:13:04","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004870662","Odz=
a petit marche new","","24-04-2025 00:11:26","23-04-2025 23:45:59","24-04-2=
025 02:28:12","Grid outage,site went down due to Rectifier dysfunctionning =
on site //He reset it and site on Grid","Albran Byorel","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","Grid outage,site went down due to=
 Rectifier dysfunctionning on site //He reset it and site on Grid","gerard.=
tchangoue@matech-cameroun.com","1575","24-04-2025 00:11:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0004870577","Nkoa Ayo=
s","","23-04-2025 23:48:40","23-04-2025 23:37:03","24-04-2025 01:14:32","Ca=
scaded Incident from TTO4981125","MINKA NICOLAS","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active//No power issue Ubay: 54.43V site=
 on Grid.The FME TX eloundou (652586578) from Huawei is informed.","system"=
,"275035","23-04-2025 23:48:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_098","NOCINC0004870573","Ekounou"=
,"","23-04-2025 23:47:16","23-04-2025 23:37:03","24-04-2025 01:14:32","Casc=
aded Incident from TTO4981125","Albran Byorel","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue Ubay: 54.43V site o=
n Grid.The FME TX eloundou (652586578) from Huawei is informed.","system","=
275035","23-04-2025 23:47:16","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0004870553","G=
SO","IHS_YND_098, IHS_YND_067","23-04-2025 23:45:13","23-04-2025 23:37:03",=
"24-04-2025 01:14:32","Active//No power issue Ubay: 54.43V site on Grid.The=
 FME TX eloundou (652586578) from Huawei is informed.","MINKA NICOLAS","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active//No power issue Ubay: 54.43V site on Grid.The FME TX eloundo=
u (652586578) from Huawei is informed.","edwige.kapawo@matech-cameroun.com"=
,"490","23-04-2025 23:45:13","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004870539","Odz=
a petit marche new","","23-04-2025 23:38:29","23-04-2025 23:34:19","23-04-2=
025 23:40:13","Site went down due to insufficient rectifiers on site//Site =
stabilized	","Albran Byorel","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to insufficient rectifiers on site//Site =
stabilized	","gerard.tchangoue@matech-cameroun.com","250","23-04-2025 23:38=
:29","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004870515","Eko=
mbitie","","23-04-2025 23:31:49","23-04-2025 23:28:41","23-04-2025 23:32:25=
","Active: no power issue, site is on Gen with Ubaie=3D54.6V, Symphorien(65=
0257151) from huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no =
power issue, site is on Gen with Ubaie=3D54.6V, Symphorien(650257151) from =
huawei is informed","gerard.tchangoue@matech-cameroun.com","189","23-04-202=
5 23:31:49","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004870493","N=
komkana 2","IHS_YND_220, IHS_YND_126, IHS_YND_563, IHS_YND_127","23-04-2025=
 23:22:56","23-04-2025 23:12:59","24-04-2025 01:10:32","Active // No power =
issue on site ,site on Grid with Ubaie: 51.7V.  SONKOUE Emmanuel (694567096=
/SNEF) Is on site to work (Upgrade 10G_COREVO)","Mboua Thierry","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active // No power issue on site ,site on Grid with Ubaie: 51.7V.  SONKOUE=
 Emmanuel (694567096/SNEF) Is on site to work (Upgrade 10G_COREVO)","edwige=
.kapawo@matech-cameroun.com","598","23-04-2025 23:22:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004870490","Tsinga",=
"","23-04-2025 23:21:23","23-04-2025 23:12:59","24-04-2025 01:10:32","Casca=
ded Incident from TTO4981031 - Cascade Removed From TTO4981031","Mboua Thie=
rry","Cascade Outage","Active","Cascade Active","Cascade Active","Active //=
 No power issue on site ,site on Grid with Ubaie: 51.7V.  SONKOUE Emmanuel =
(694567096/SNEF) Is on site to work (Upgrade 10G_COREVO)","system","269436"=
,"23-04-2025 23:21:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004870488","Golf Qua=
ter","","23-04-2025 23:21:22","23-04-2025 23:12:59","24-04-2025 01:10:32","=
Cascaded Incident from TTO4981031 - Cascade Removed From TTO4981031","Mboua=
 Thierry","Cascade Outage","Active","Cascade Active","Cascade Active","Acti=
ve // No power issue on site ,site on Grid with Ubaie: 51.7V.  SONKOUE Emma=
nuel (694567096/SNEF) Is on site to work (Upgrade 10G_COREVO)","system","26=
9436","23-04-2025 23:21:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004870489","Bastos B=
ethesda","","23-04-2025 23:21:22","23-04-2025 23:12:59","24-04-2025 01:10:3=
2","Cascaded Incident from TTO4981031 - Cascade Removed From TTO4981031","M=
boua Thierry","Cascade Outage","Active","Cascade Active","Cascade Active","=
Active // No power issue on site ,site on Grid with Ubaie: 51.7V.  SONKOUE =
Emmanuel (694567096/SNEF) Is on site to work (Upgrade 10G_COREVO)","system"=
,"269436","23-04-2025 23:21:22","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004870479","B=
astos-Nylon","","23-04-2025 23:19:42","23-04-2025 23:12:59","24-04-2025 01:=
10:32","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Casca=
de Active","Active // No power issue on site ,site on Grid with Ubaie: 51.7=
V.  SONKOUE Emmanuel (694567096/SNEF) Is on site to work (Upgrade 10G_COREV=
O)","edwige.kapawo@matech-cameroun.com","269437","23-04-2025 23:19:42","MAT=
ECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004870421","Oko=
lo Kilombo","","23-04-2025 22:59:56","23-04-2025 22:49:59","23-04-2025 23:0=
0:44","Grid outage, site went down due to insufficiency of rectifiers, // s=
ite stabilized","Fabrice Pouakam","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Grid outage, site went down due to insufficiency of rec=
tifiers, // site stabilized","gerard.tchangoue@matech-cameroun.com","598","=
23-04-2025 22:59:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_177","NOCINC0004870340","Awae-Yde=
","","23-04-2025 22:42:42","23-04-2025 22:25:25","23-04-2025 22:51:05","Cas=
caded Incident from TTO4980772","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubaie: 53,2V site =
on GRID. Rodrigue (655102999/Huawei)is informed and reports Radio issue.","=
system","279295","23-04-2025 22:42:42","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004870033","B=
ATA Mokolo OCM","","23-04-2025 21:48:41","23-04-2025 21:41:27","23-04-2025 =
22:56:55","No power issue on site Ubay 52.5V site on Grid TX Brice (6544199=
73) From Huawei is informed","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubay 52.=
5V site on Grid TX Brice (654419973) From Huawei is informed","christelle.n=
gonga@matech-cameroun.com","435","23-04-2025 21:48:41","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004869983","Eto=
ug ebe Carrefour","","23-04-2025 21:40:41","23-04-2025 21:33:32","23-04-202=
5 23:09:03","Site went down because gen fails to start due to grid bad volt=
age // He bypass grid and manually start the gen","Hyemafo Gildas","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Site went=
 down because gen fails to start due to grid bad voltage // He bypass grid =
and manually start the gen","cedric.tiani@matech-cameroun.com","429","23-04=
-2025 21:40:41","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004869928","Meh=
anda 1","","23-04-2025 21:31:23","23-04-2025 21:21:59","24-04-2025 00:49:45=
","Access issue due to landlord Grid outage,gen failed to start due to auto=
mation failure//Grid power return","Albran Byorel","Access Denial","Lease O=
r Legal","Landlord Related Issues","Access Issue - Land Lord","Access issue=
 due to landlord Grid outage,gen failed to start due to automation failure/=
/Grid power return","cedric.tiani@matech-cameroun.com","565","23-04-2025 21=
:31:23","MATECH CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004869886","Nko=
abang entree carriere","","23-04-2025 21:19:32","23-04-2025 21:18:05","23-0=
4-2025 21:44:56","grid outage, gen start and stopped with alarm 'Low oil pr=
essure' // He added oil and Gen manually started","Mba Lazare Herve","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","grid outage, g=
en start and stopped with alarm 'Low oil pressure' // He added oil and Gen =
manually started","cedric.tiani@matech-cameroun.com","88","23-04-2025 21:19=
:32","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004869857","A=
wae Ewonkan","","23-04-2025 21:14:11","23-04-2025 21:12:06","23-04-2025 23:=
45:44","Grid outage site went down due to Gen Overload (20Kva, load 310 A) =
// he reduced load","Albran Byorel","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage site went down due to Gen Overload (20Kva, =
load 310 A) // he reduced load","christelle.ngonga@matech-cameroun.com","12=
7","23-04-2025 21:14:11","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004869844","B=
itoto","","23-04-2025 21:12:02","23-04-2025 21:11:51","23-04-2025 22:10:27"=
,"Site went down due to PWC ""ZTE' dysfunction// he reset it and started Ge=
n","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","Site went down to due to PWC ""ZTE' dysfunction// he res=
et it and started Gen","christelle.ngonga@matech-cameroun.com","13","23-04-=
2025 21:12:02","MATECH CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0004869800","E=
toug ebe Meweulo","","23-04-2025 21:05:13","23-04-2025 20:59:02","23-04-202=
5 22:17:11","Site went down Gen failed to start due to Grid bad voltage// H=
e did a bridge on the Good phase","Hyemafo Gildas","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Site went down Gen failed=
 to start due to Grid bad voltage// He did a bridge on the Good phase","chr=
istelle.ngonga@matech-cameroun.com","372","23-04-2025 21:05:13","MATECH CMR=
"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004869730","Mok=
olo Yaounde","","23-04-2025 20:56:02","23-04-2025 20:45:56","23-04-2025 22:=
00:27","No power issue U =3D5.6V site on grid. The Tx FME Eloundou Bertrand=
 (693212405)from Huawei is informed","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D5.6=
V site on grid. The Tx FME Eloundou Bertrand (693212405)from Huawei is info=
rmed","cedric.tiani@matech-cameroun.com","607","23-04-2025 20:56:02","MATEC=
H CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004869684","NKO=
MEKUI OCM","","23-04-2025 20:51:02","23-04-2025 20:48:48","23-04-2025 20:50=
:50","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted b=
y Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","Affected by 3r=
d Party Site","Active//No power issue on site U=3D54.5 V site on Gen.Site i=
mpacted by Mbankolo Camtel and not managing by IHS","cedric.tiani@matech-ca=
meroun.com","135","23-04-2025 20:51:02","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004869510","C=
omplexe-BEAC","","23-04-2025 20:22:50","23-04-2025 20:21:44","23-04-2025 20=
:51:55","Grid fluctuation Site down because  gen fail to start due to Grid =
bad voltage // Gen started manually","Albran Byorel","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuation Site d=
own because  gen fail to start due to Grid bad voltage // Gen started manua=
lly","christelle.ngonga@matech-cameroun.com","67","23-04-2025 20:22:50","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004869395","E=
koumdoum","","23-04-2025 20:00:20","23-04-2025 19:59:09","23-04-2025 20:54:=
58","Site down due to Grid low voltage , gen did not start // Grid stabiliz=
ation ","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Uns=
table Grid Supply Issue","Site down due to Grid low voltage , gen did not s=
tart // Grid stabilization ","christelle.ngonga@matech-cameroun.com","72","=
23-04-2025 20:00:20","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004869323","N=
koabang Ebolmedjock","","23-04-2025 19:52:54","23-04-2025 19:51:48","23-04-=
2025 20:33:57","Grid outage,site went because Gen started and stopped with =
alarm Overcurrent//he reset it and manually started Gen ","Mba Lazare Herve=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge,site went because Gen started and stopped with alarm Overcurrent//he res=
et it and manually started Gen ","christelle.ngonga@matech-cameroun.com","6=
7","23-04-2025 19:52:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004869297","Eto koss=
 Yde","","23-04-2025 19:48:37","23-04-2025 18:31:30","23-04-2025 20:07:28",=
"Cascaded Incident from TTO4979625","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
Gen failed to start due to battery Gen faulty// He started Gen with externa=
l battery","system","308023","23-04-2025 19:48:37","MATECH CMR"
"Closed Complete","Site Down","CTR_694","IHS_YND_714","NOCINC0004869249","E=
kekam","","23-04-2025 19:38:54","23-04-2025 19:36:42","23-04-2025 21:07:21"=
,"Grid outage, site went down due to high temperature impacted to the muffl=
er being pierced, // Water added in the radiator and Gen started manually",=
"TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - =
High Engine Temp - Coolant Level Issue","Grid outage, site went down due to=
 high temperature impacted to the muffler being pierced, // Water added in =
the radiator and Gen started manually","christelle.ngonga@matech-cameroun.c=
om","133","23-04-2025 19:38:54","MATECH CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0004869136","Men=
dong Maeture","","23-04-2025 19:23:07","23-04-2025 19:14:50","23-04-2025 20=
:10:35","Site went down due to CB (100A) in PWC that tripped MTN // He adde=
d CB(63A) and rearmed","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","BTS Breaker Tripped","Site went down due to CB (100A) in PWC tha=
t tripped MTN // He added CB(63A) and rearmed","cedric.tiani@matech-camerou=
n.com","497","23-04-2025 19:23:07","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004869039","M=
endong vallee","","23-04-2025 19:14:27","23-04-2025 19:09:08","24-04-2025 0=
0:24:11","Grid outage site went down due to Gen Overload (20Kva) // he redu=
ced load","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage site went down due to Gen Overload (20Kva) // he reduce=
d load","christelle.ngonga@matech-cameroun.com","320","23-04-2025 19:14:27"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004869005","S=
IMBOCK BONAMBAPE","","23-04-2025 19:07:48","23-04-2025 19:05:42","23-04-202=
5 19:12:04","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup // Grid return","christelle.ngonga@matech-cameroun=
.com","127","23-04-2025 19:07:48","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004868920","Nom=
ayos montee Meche","","23-04-2025 18:48:34","23-04-2025 18:47:24","23-04-20=
25 20:32:57","Grid outage,site went because Gen started and stopped with al=
arm undervoltage and unbalanced KW//He reset it and site on GEN","Fanda Bri=
ce","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage,site went because Gen started and stopped with alarm undervoltage and =
unbalanced KW//He reset it and site on GEN","cedric.tiani@matech-cameroun.c=
om","71","23-04-2025 18:48:34","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004868867","N=
KOLMEKONG YDE","","23-04-2025 18:38:22","23-04-2025 18:33:15","23-04-2025 1=
8:39:48","Grid fluctuation Site down because  gen fail to start due to Grid=
 bad voltage // Grid return","Fabrice Pouakam","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Grid fluctuation Site down be=
cause  gen fail to start due to Grid bad voltage // Grid return","christell=
e.ngonga@matech-cameroun.com","3353","23-04-2025 18:38:22","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004868857","M=
EFOU ASSI","IHS_YND_737","23-04-2025 18:36:37","23-04-2025 18:31:30","23-04=
-2025 20:07:28","Grid outage, Site went down because Gen failed to start du=
e to battery Gen faulty// He started Gen with external battery","Fanda Bric=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid=
 outage, Site went down because Gen failed to start due to battery Gen faul=
ty// He started Gen with external battery","christelle.ngonga@matech-camero=
un.com","308","23-04-2025 18:36:37","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0004868660","Ngo=
usso-Savana","","23-04-2025 18:01:35","23-04-2025 17:59:25","23-04-2025 18:=
05:35","site went down due to PWC Huawei malfunction, // He reset and site =
on Grid","Siligap Boris","Equipment Repair","Passive","Control Panel","ATS-=
AMF Issue","site went down due to PWC Huawei malfunction, // He reset and s=
ite on Grid","christelle.ngonga@matech-cameroun.com","130","23-04-2025 18:0=
1:35","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0004868624","NKO=
ABANG NKOLO 3","","23-04-2025 17:53:38","23-04-2025 17:49:22","23-04-2025 1=
8:31:22","Site went down because of insufficient rectifiers // He added 1 r=
ectifier and site stabilized","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down because of insufficient r=
ectifiers // He added 1 rectifier and site stabilized","cedric.tiani@matech=
-cameroun.com","256","23-04-2025 17:53:38","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004868590","B=
ATA Mokolo OCM","","23-04-2025 17:47:03","23-04-2025 17:44:54","23-04-2025 =
20:08:00","Grid outage No space to deploy //grid restoration","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No sp=
ace to deploy //grid restoration","christelle.ngonga@matech-cameroun.com","=
130","23-04-2025 17:47:03","MATECH CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0004868554","E=
ntree Cite Verte","","23-04-2025 17:43:45","23-04-2025 17:34:34","23-04-202=
5 19:40:33","No power issue, site is on grid with Ubaie=3D52.9V, TX Fme Bri=
ce Tsague/654419973 of huawei is informed.","Paul BIBOUM","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue, site is on grid with Ubaie=3D52.9V, TX Fme Brice Tsague/65441997=
3 of huawei is informed.","christelle.ngonga@matech-cameroun.com","552","23=
-04-2025 17:43:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0004868514","Bastos E=
koudou","","23-04-2025 17:37:43","23-04-2025 17:29:27","23-04-2025 19:10:05=
","ACTIVE// No power issue site on Grid U=3D 54,3 V The TX Eloudou//6932124=
05 is informed ","Mboua Thierry","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No power issue site o=
n Grid U=3D 54,3 V The TX Eloudou//693212405 is informed ","joelle.ekessi@i=
hstowers.com","497","23-04-2025 17:37:43","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004868513","B=
arriere","","23-04-2025 17:37:20","23-04-2025 17:31:07","23-04-2025 23:48:3=
0","grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed //Grid return","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","grid outage, Site went =
down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and c=
onfirmed //Grid return","cedric.tiani@matech-cameroun.com","374","23-04-202=
5 17:37:20","MATECH CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0004868467","Mba=
lla 4","","23-04-2025 17:31:51","23-04-2025 17:24:41","23-04-2025 19:15:53"=
,"Active: No power issue, site is on grid with Ubaie=3D54.3V, Armand nguets=
a(691144412) from Huawei is informed","Delor Telezing","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No power issue, site is on grid with Ubaie=3D54.3V, Armand nguetsa(69114441=
2) from Huawei is informed","cedric.tiani@matech-cameroun.com","431","23-04=
-2025 17:31:51","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004868274","Eko=
mbitie","","23-04-2025 17:09:46","23-04-2025 17:08:27","23-04-2025 19:20:20=
","Active: no power issue, site is on Gen with Ubaie=3D54.6V, Symphorien(65=
0257151) from huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no =
power issue, site is on Gen with Ubaie=3D54.6V, Symphorien(650257151) from =
huawei is informed","cedric.tiani@matech-cameroun.com","80","23-04-2025 17:=
09:46","MATECH CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0004868161","San=
ta Barbara Yde","","23-04-2025 16:50:14","23-04-2025 16:45:04","23-04-2025 =
16:50:51","Active//No power issue on site; Ubaie: 54.8 V site on Grid The F=
ME Synphorien//691316854// from Huawei is on site","Delor Telezing","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site; Ubaie: 54.8 V site on Grid The FME Syn=
phorien//691316854// from Huawei is on site","cedric.tiani@matech-cameroun.=
com","311","23-04-2025 16:50:14","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0004868146","C=
rf Cornier","","23-04-2025 16:47:35","23-04-2025 16:37:25","23-04-2025 16:5=
3:04","No power issue on site T:49.9V site on grid TX FME Armand Ngestsa (6=
91144412)From huawei is informed","MINKA NICOLAS","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site T:49.9V site on grid TX FME Armand Ngestsa (691144412)From huawei=
 is informed","christelle.ngonga@matech-cameroun.com","611","23-04-2025 16:=
47:35","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004868109","Ngo=
usso Vallee","","23-04-2025 16:37:16","23-04-2025 16:35:02","23-04-2025 17:=
56:29","Grid outage, site went down because gen start and stopped with alar=
m oil pressure // He reset gen card and gen manually started	","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage, site went down because gen start and stopped with alarm oil pressure =
// He reset gen card and gen manually started	","cedric.tiani@matech-camero=
un.com","135","23-04-2025 16:37:16","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004868099","Nsi=
malen MTN","","23-04-2025 16:34:59","23-04-2025 16:33:50","23-04-2025 16:43=
:43","Grid outage, Site went down before Gen start due to poor backup // Gr=
id restoration","Albran Byorel","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup // Grid restoration","cedric.tiani@matech-cameroun.co=
m","70","23-04-2025 16:34:59","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004868055","B=
ATA Mokolo OCM","","23-04-2025 16:22:58","23-04-2025 16:19:50","23-04-2025 =
16:24:24","Grid outage No space to deploy // Grid power return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No =
space to deploy // Grid power return","christelle.ngonga@matech-cameroun.co=
m","189","23-04-2025 16:22:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004868046","ELOUMDEM=
 CARRIERE 2","","23-04-2025 16:20:35","23-04-2025 16:18:52","23-04-2025 16:=
35:42","Cascaded Incident from TTO4978201","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage,site went down be=
fore gen start due to poor battery backup// Gen manually started","system",=
"265760","23-04-2025 16:20:35","MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004868042","Eto=
 koss Yde","","23-04-2025 16:19:49","23-04-2025 16:18:52","23-04-2025 16:35=
:42","Cascaded Incident from TTO4978201","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Cascaded Incident from TTO49782=
01","christelle.ngonga@matech-cameroun.com","265760","23-04-2025 16:19:49",=
"MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004868039","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","23-04-2025 16:19:16","23-04-2025 16:18=
:52","23-04-2025 16:35:42","Grid outage,site went down before gen start due=
 to poor battery backup// Gen manually started","Fanda Brice","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,=
site went down before gen start due to poor battery backup// Gen manually s=
tarted","cedric.tiani@matech-cameroun.com","26","23-04-2025 16:19:16","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004868003","N=
omayos montee Meche","","23-04-2025 16:10:00","23-04-2025 16:09:56","23-04-=
2025 18:02:45","Grid outage,site went because Gen started and stopped with =
alarm overvoltage and unbalanced KW//He reset it and site on GEN","Fanda Br=
ice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage,site went because Gen started and stopped with alarm overvoltage and =
unbalanced KW//He reset it and site on GEN","christelle.ngonga@matech-camer=
oun.com","5","23-04-2025 16:10:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0004867938","Marche O=
dza","","23-04-2025 15:54:25","23-04-2025 15:29:25","23-04-2025 16:39:24","=
Cascaded Incident from TTO4977875","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because the CB of th=
e Grid is faulty//He replaced by a C63","system","290142","23-04-2025 15:54=
:25","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004867810","AWA=
E OCM","","23-04-2025 15:49:27","23-04-2025 15:43:17","23-04-2025 16:53:34"=
,"Grid outage site went down because the PWC malfunctions //he reset the PW=
C and manually started","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Grid outage site went down because =
the PWC malfunctions //he reset the PWC and manually started","cedric.tiani=
@matech-cameroun.com","371","23-04-2025 15:49:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0004867751","Mvog-Man=
ga","","23-04-2025 15:41:02","23-04-2025 15:29:25","23-04-2025 16:39:24","C=
ascaded Incident from TTO4977875","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because the CB of the=
 Grid is faulty//He replaced by a C63","system","290141","23-04-2025 15:41:=
02","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004867739","O=
dza","IHS_YND_254, IHS_YND_580","23-04-2025 15:39:32","23-04-2025 15:29:25"=
,"23-04-2025 16:39:24","Site went down because the CB of the Grid is faulty=
//He replaced by a C63","Albran Byorel","Grid Supply","Passive","Grid","Nat=
ional Grid - Circuit Breaker","Site went down because the CB of the Grid is=
 faulty//He replaced by a C63","christelle.ngonga@matech-cameroun.com","608=
","23-04-2025 15:39:32","MATECH CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0004867724","Men=
dong Maeture","","23-04-2025 15:35:05","23-04-2025 15:25:40","23-04-2025 17=
:34:12","Site went down due to trip of MTN CB (180A)  in the power cabinet =
// CB rearm ","Hyemafo Gildas","Equipment Repair","Passive","Control Panel"=
,"BTS Breaker Tripped","Site went down due to trip of MTN CB (180A)  in the=
 power cabinet // CB rearm ","cedric.tiani@matech-cameroun.com","565","23-0=
4-2025 15:35:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004867506","Mom","",=
"23-04-2025 14:59:11","23-04-2025 14:57:33","23-04-2025 14:59:40","Cascaded=
 Incident from TTO4977566","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on gen with U=3D57v Notice t=
hat site is impacted by Ngoumou who is not our responsability","system","12=
19733","23-04-2025 14:59:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004867505","OTELE MT=
N","","23-04-2025 14:59:11","23-04-2025 14:57:33","23-04-2025 14:59:40","Ca=
scaded Incident from TTO4977566","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on gen with U=3D57v No=
tice that site is impacted by Ngoumou who is not our responsability","syste=
m","1219732","23-04-2025 14:59:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004867507","Akono","=
","23-04-2025 14:59:11","23-04-2025 14:57:33","23-04-2025 14:59:40","Cascad=
ed Incident from TTO4977566","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on gen with U=3D57v Notice=
 that site is impacted by Ngoumou who is not our responsability","system","=
1219732","23-04-2025 14:59:11","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0004867475","Min=
ka","IHS_YND_531, IHS_YND_370, IHS_YND_365","23-04-2025 14:57:53","23-04-20=
25 14:57:33","23-04-2025 15:30:40","No power issue site on gen with U=3D57v=
 Notice that site is impacted by Ngoumou who is not our responsability","Fa=
nda Brice","Customer Equipment Failure","Active","Active Equipment Failure"=
,"Affected by 3rd Party Site","No power issue site on gen with U=3D57v Noti=
ce that site is impacted by Ngoumou who is not our responsability","cedric.=
tiani@matech-cameroun.com","21","23-04-2025 14:57:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004867466","Abang","=
","23-04-2025 14:57:22","23-04-2025 14:42:10","23-04-2025 15:30:44","Cascad=
ed Incident from TTO4977529","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site went down because Gen=
 failed to start due to grid bad voltage//He bypassed the Grid and site on =
Gen","system","1220715","23-04-2025 14:57:22","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004867460","Nsi=
malen MTN","","23-04-2025 14:56:59","23-04-2025 14:52:50","23-04-2025 15:02=
:32","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automatically","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen started automatically","cedric.tiani@=
matech-cameroun.com","250","23-04-2025 14:56:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_057","NOCINC0004867431","Mvolye-N=
ew","","23-04-2025 14:55:40","23-04-2025 14:39:36","23-04-2025 15:50:15","A=
ctive// No power Issue Site on Grid Ubai =3D51,6 V, The TX FME Mbah Hosiah =
(674007438) is informed","","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site on Gri=
d Ubai =3D51,6 V, The TX FME Mbah Hosiah (674007438) is informed","joelle.e=
kessi@ihstowers.com","965","23-04-2025 14:55:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004867425","Nkolfon =
Cimencam","","23-04-2025 14:54:52","23-04-2025 14:34:49","23-04-2025 15:50:=
13","Active//No power issue on site U=3D54,5v site on Gen The TX fme George=
(697461814) from huawei is informed. Noticed that site is impacted by Afano=
ya (Not manage by HIS)impacted by afanoya II not manage b","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","Affected=
 by 3rd Party Site","Active//No power issue on site U=3D54,5v site on Gen T=
he TX fme George(697461814) from huawei is informed. Noticed that site is i=
mpacted by Afanoya (Not manage by HIS)impacted by afanoya II not manage by =
IHS","joelle.ekessi@ihstowers.com","1204","23-04-2025 14:54:52","MATECH CMR=
"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0004867401","Nko=
langaa","IHS_YND_290","23-04-2025 14:50:23","23-04-2025 14:42:10","23-04-20=
25 15:31:49","Grid outage,site went down because Gen failed to start due to=
 grid bad voltage//He bypassed the Grid and site on Gen","Mba Lazare Herve"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid outage,site went down because Gen failed to start due to grid bad volt=
age//He bypassed the Grid and site on Gen","cedric.tiani@matech-cameroun.co=
m","862","23-04-2025 14:50:23","MATECH CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0004867352","AFE=
ME NORD","IHS_YND_808","23-04-2025 14:40:08","23-04-2025 14:36:24","23-04-2=
025 15:40:33","Active: no power issue, site is on grid with Ubaie=3D50.1V, =
Njoya((691144435) from Huawie is working on site","TIENTCHEU NZETCHIEU GAEL=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","Active: no power issue, site is on grid with Ubaie=3D50.1V, N=
joya((691144435) from Huawie is working on site","cedric.tiani@matech-camer=
oun.com","777","23-04-2025 14:40:08","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0004867350","Mba=
nkolo petit paris","","23-04-2025 14:39:39","23-04-2025 14:36:24","23-04-20=
25 14:40:31","","Mboua Thierry","Cascade Outage","Active","Cascade Active",=
"Cascade Active","Active: no power issue, site is on grid with Ubaie=3D50.1=
V, Njoya((691144435) from Huawie is working on site","cedric.tiani@matech-c=
ameroun.com","196","23-04-2025 14:39:39","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004867332","Nom=
ayos montee Meche","","23-04-2025 14:37:09","23-04-2025 14:35:45","23-04-20=
25 15:50:09","Active: No power issue, site is on grid with Ubaie=3D53V, Flu=
bert(654266068) from Huawei is informe","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: N=
o power issue, site is on grid with Ubaie=3D53V, Flubert(654266068) from Hu=
awei is informe","loic.noumsi@matech-cameroun.com","85","23-04-2025 14:37:0=
9","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004867321","Mon=
tee Jouvence","","23-04-2025 14:35:39","23-04-2025 14:34:27","23-04-2025 17=
:08:43","grid outage ,site down due because gen turned till fuel shortage /=
/ site refueled","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel =
Outage","grid outage ,site down due because gen turned till fuel shortage /=
/ site refueled","vanel.mbiada@matech-cameroun.com","73","23-04-2025 14:35:=
39","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004867250","E=
ssomba","","23-04-2025 14:26:22","23-04-2025 14:15:09","23-04-2025 15:50:06=
","Active // No power issue site on Gen with U=3D53.1 V Tx Fme Henri(691145=
055) of Huawei is informed. ","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No p=
ower issue site on Gen with U=3D53.1 V Tx Fme Henri(691145055) of Huawei is=
 informed. ","vanel.mbiada@matech-cameroun.com","674","23-04-2025 14:26:22"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004867148","Ebeba","=
","23-04-2025 14:03:18","23-04-2025 09:27:40","23-04-2025 10:34:33","Cascad=
ed Incident from TTO4976310","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site Ubaie 49.1V site on Gen=
, Etienne/+237 6 93 96 14 74from Huawei is informed and manage","system","2=
82885","23-04-2025 14:03:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004867090","ODZA MIN=
KAN EDIBI ASSI","","23-04-2025 13:52:04","23-04-2025 13:40:21","23-04-2025 =
17:42:30","Grid outage,site went down due to Rectifier dysfunctionning on s=
ite //He reset it and site on Grid","Albran Byorel","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Grid outage,site went down due to Rec=
tifier dysfunctionning on site //He reset it and site on Grid","system","70=
3","23-04-2025 13:52:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_312","NOCINC0004867089","Nkolnda"=
,"IHS_YND_343, IHS_YND_528, IHS_YND_746, IHS_YND_715","23-04-2025 13:52:04"=
,"23-04-2025 13:40:21","23-04-2025 13:52:47","No power issue, site is on gr=
id with Ubaie=3D55,1V, site up at 01:52 PM, Lionel Steeve(655184876) from H=
uawei is informed","Albran Byorel","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on g=
rid with Ubaie=3D55,1V, site up at 01:52 PM, Lionel Steeve(655184876) from =
Huawei is informed","system","703","23-04-2025 13:52:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004867088","Odza Min=
kan IHS","","23-04-2025 13:52:03","23-04-2025 13:40:21","23-04-2025 13:52:4=
7","Cascaded Incident from TTO4977136 - Cascade Removed From TTO4977136","A=
lbran Byorel","Cascade Outage","Active","Cascade Active","Cascade Active","=
No power issue, site is on grid with Ubaie=3D55,1V, site up at 01:52 PM, Li=
onel Steeve(655184876) from Huawei is informed","system","275206","23-04-20=
25 13:52:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004867085","MEHANDAN=
","","23-04-2025 13:50:40","23-04-2025 13:40:21","23-04-2025 13:52:47","Cas=
caded Incident from TTO4977048","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue, site is on grid with Ubai=
e=3D55,1V, site up at 01:52 PM, Lionel Steeve(655184876) from Huawei is inf=
ormed","system","275207","23-04-2025 13:50:40","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004867080","Meh=
anda 1","","23-04-2025 13:49:34","23-04-2025 13:40:21","23-04-2025 13:52:47=
","","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascade Ac=
tive","No power issue, site is on grid with Ubaie=3D55,1V, site up at 01:52=
 PM, Lionel Steeve(655184876) from Huawei is informed","cedric.tiani@matech=
-cameroun.com","275206","23-04-2025 13:49:34","MATECH CMR"
"Closed Complete","Site Down","T1071","IHS_YND_343","NOCINC0004866991","Mbe=
doumou - Ekali","","23-04-2025 13:45:37","23-04-2025 13:40:21","23-04-2025 =
17:26:47","Active: No pwer issue, site is on Grid U=3D53.4V.Noticed impacte=
d by  Ebanga Ngoulou","Albran Byorel","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","Active: No pwer issue, site is on Grid U=3D53.4V.No=
ticed impacted by  Ebanga Ngoulou","cedric.tiani@matech-cameroun.com","2752=
06","23-04-2025 13:45:37","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004866905","Eto=
ug ebe Carrefour","","23-04-2025 13:35:09","23-04-2025 13:24:02","23-04-202=
5 14:31:39","Grid outage,site went down because GEN does not support the lo=
ad(investigation ongoing)//He reduced the load and started the Gen manually=
","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","Grid outage,site went down because GEN does not support the load(investi=
gation ongoing)//He reduced the load and started the Gen manually","cedric.=
tiani@matech-cameroun.com","667","23-04-2025 13:35:09","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004866875","Men=
dong3","","23-04-2025 13:28:54","23-04-2025 10:10:45","24-04-2025 12:44:20"=
,"Site went down due to disjunction of Cb(63A) in PWC // He rearmed Cb(63A)=
, site on grid","","Equipment Repair","Passive","Control Panel","ATS-AMF Is=
sue","Site went down due to disjunction of Cb(63A) in PWC // He rearmed Cb(=
63A), site on grid","cedric.tiani@matech-cameroun.com","11890","23-04-2025 =
13:28:54","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004866855","Jou=
vence Mbenda","","23-04-2025 13:25:01","23-04-2025 08:59:43","23-04-2025 13=
:38:31","Grid outage ,site went down because gen started  and stopped due t=
o alarm high temp //We add water and gen manually started","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","Grid outage ,site went down because gen started  and stopped=
 due to alarm high temp //We add water and gen manually started","cedric.ti=
ani@matech-cameroun.com","15919","23-04-2025 13:25:01","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004866760","A=
WAE OCM","","23-04-2025 13:07:04","23-04-2025 12:57:55","23-04-2025 15:06:2=
6","Grid ouatge,Site went down because the PWC OF ZTE dysfonction // He res=
et the PWC and start the  GEN manually","Mba Lazare Herve","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","Grid ouatge,Site we=
nt down because the PWC OF ZTE dysfonction // He reset the PWC and start th=
e  GEN manually","vanel.mbiada@matech-cameroun.com","885","23-04-2025 13:07=
:04","MATECH CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0004866309","Nke=
ng likok","IHS_YND_339","23-04-2025 12:26:50","23-04-2025 09:27:40","23-04-=
2025 10:34:33","No power issue on site Ubaie 49.1V site on Gen, Etienne/+23=
7 6 93 96 14 74from Huawei is informed and manage","Kemeni Franklin","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site Ubaie 49.1V site on Gen, Etienne/+237 6 93 96 =
14 74from Huawei is informed and manage","vanel.mbiada@matech-cameroun.com"=
,"10750","23-04-2025 12:26:50","MATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004866237","BIY=
EMASSI NIKI","","23-04-2025 12:19:10","23-04-2025 12:15:03","23-04-2025 17:=
34:21","site down due to work the  ( swapping of power cabinet ) //End of w=
ork","Hyemafo Gildas","Installation Activity","Passive","Planned Activity",=
"Installation Activity","site down due to work the  ( swapping of power cab=
inet ) //End of work","cedric.tiani@matech-cameroun.com","1720","23-04-2025=
 12:19:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004865963","Saa","",=
"23-04-2025 11:25:03","23-04-2025 11:10:58","23-04-2025 12:08:20","Cascaded=
 Incident from TTO4975924","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because rectifier disfunctio=
nning // He reset it: Site on grid","system","276755","23-04-2025 11:25:03"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004865962","SAA Entr=
ance","","23-04-2025 11:25:03","23-04-2025 11:10:58","23-04-2025 12:08:20",=
"Cascaded Incident from TTO4975924","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because rectifier d=
isfunctionning // He reset it: Site on grid","system","276755","23-04-2025 =
11:25:03","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004865960","SAA=
 2","IHS_YND_542, IHS_YND_405","23-04-2025 11:24:18","23-04-2025 11:10:58",=
"23-04-2025 12:09:07","Site went down because rectifier disfunctionning // =
He reset it: Site on grid","Parker Tchoup","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down because rectifier disfunctionni=
ng // He reset it: Site on grid","cedric.tiani@matech-cameroun.com","3000",=
"23-04-2025 11:24:18","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0004865766","Nko=
abang Ebolmedjock","","23-04-2025 10:49:16","23-04-2025 09:55:03","23-04-20=
25 13:19:41","Grid outage, Gen stopped due to low iol pressure // Oil add a=
nd Gen start manually","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - Low Oil Pressure","Grid outage, Gen stopped due to low iol p=
ressure // Oil add and Gen start manually","cedric.tiani@matech-cameroun.co=
m","3254","23-04-2025 10:49:16","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004865754","M=
essa-Carriere OCM","","23-04-2025 10:46:43","23-04-2025 10:41:10","23-04-20=
25 11:58:14","No power issue site on grid with U=3D52V, FME TX Mohamadou/69=
1144435/ from Huawei is informed.	","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D52V, FME TX Mohamadou/691144435/ from Huawei is informed.	","v=
anel.mbiada@matech-cameroun.com","335","23-04-2025 10:46:43","MATECH CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004865749","Eke=
kam","","23-04-2025 10:44:52","23-04-2025 10:31:37","23-04-2025 11:29:30","=
Grid outage, site went down due to high temperature impacted to the muffler=
 being pierced, // Water added in the radiator and Gen started manually","T=
IENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","Gen Temp =
High","Grid outage, site went down due to high temperature impacted to the =
muffler being pierced, // Water added in the radiator and Gen started manua=
lly","cedric.tiani@matech-cameroun.com","796","23-04-2025 10:44:52","MATECH=
 CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004865739","Eki=
e sud","","23-04-2025 10:42:22","23-04-2025 10:24:13","23-04-2025 12:54:45"=
,"Grid outage, Gen failed to start due to Gen card alarm // Gen card reset =
and en start manually","Albran Byorel","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage, Gen failed to start due to Gen car=
d alarm // Gen card reset and en start manually","cedric.tiani@matech-camer=
oun.com","1090","23-04-2025 10:42:22","MATECH CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0004865724","N=
kol-Mbanda","","23-04-2025 10:39:01","23-04-2025 09:31:53","23-04-2025 14:4=
7:12","Grid outage, Site went down due to fuel shortage // Refueling done",=
"MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge, Site went down due to fuel shortage // Refueling done","vanel.mbiada@ma=
tech-cameroun.com","21240","23-04-2025 10:39:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004865679","SOA VILL=
AGE","","23-04-2025 10:29:52","23-04-2025 10:16:44","23-04-2025 11:16:22","=
Cascaded Incident from TTO4975589","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down due to R=
CP faulty causing by lightninng // We bypassed grid and gen manually starte=
d","system","279970","23-04-2025 10:29:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004865678","Melen Ba=
'aba","","23-04-2025 10:29:51","23-04-2025 10:16:44","23-04-2025 11:16:22",=
"Cascaded Incident from TTO4975589","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down due to =
RCP faulty causing by lightninng // We bypassed grid and gen manually start=
ed","system","279970","23-04-2025 10:29:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_319","NOCINC0004865677","SOA 2","=
","23-04-2025 10:29:51","23-04-2025 10:16:44","23-04-2025 11:16:22","Cascad=
ed Incident from TTO4975589","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down due to RCP fau=
lty causing by lightninng // We bypassed grid and gen manually started","sy=
stem","279969","23-04-2025 10:29:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_318","NOCINC0004865674","SOA Univ=
ersity","","23-04-2025 10:29:50","23-04-2025 10:16:44","23-04-2025 11:16:22=
","Cascaded Incident from TTO4975589","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage site went down due t=
o RCP faulty causing by lightninng // We bypassed grid and gen manually sta=
rted","system","279971","23-04-2025 10:29:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004865675","SOA TOWN=
","","23-04-2025 10:29:50","23-04-2025 10:16:44","23-04-2025 11:16:22","Cas=
caded Incident from TTO4975589","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down due to RCP =
faulty causing by lightninng // We bypassed grid and gen manually started",=
"system","279971","23-04-2025 10:29:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004865676","SOA UNIV=
ERSITY STADIUM","","23-04-2025 10:29:50","23-04-2025 10:16:44","23-04-2025 =
11:16:22","Cascaded Incident from TTO4975589","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage site went do=
wn due to RCP faulty causing by lightninng // We bypassed grid and gen manu=
ally started","system","279969","23-04-2025 10:29:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0004865673","NGONA","=
","23-04-2025 10:29:49","23-04-2025 10:16:44","23-04-2025 11:16:22","Cascad=
ed Incident from TTO4975589","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down due to RCP =
faulty causing by lightninng // We bypassed grid and gen manually started",=
"system","279969","23-04-2025 10:29:49","MATECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0004865640","Soa=
","IHS_YND_295, IHS_YND_318, IHS_YND_320, IHS_YND_720, IHS_YND_319, IHS_YND=
_308, IHS_YND_323","23-04-2025 10:25:51","23-04-2025 10:09:44","23-04-2025 =
11:16:22","Grid outage site went down due to RCP faulty causing by lightnin=
ng // We bypassed grid and gen manually started","Siligap Boris","Force Maj=
eure","Natural Disaster","Thunderstrike","Equipment Damaged","Grid outage s=
ite went down due to RCP faulty causing by lightninng // We bypassed grid a=
nd gen manually started","cedric.tiani@matech-cameroun.com","1240","23-04-2=
025 10:25:51","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0004865332","E=
lig Edzoa","","23-04-2025 09:50:19","23-04-2025 09:33:53","23-04-2025 09:40=
:12","","Delor Telezing","Cascade Outage","Active","Cascade Active","Cascad=
e Active","ACTIVE No power issue U=3D57V site on grid TX FME Armand Nguetsa=
 /691144412 from huawei is informed ","vanel.mbiada@matech-cameroun.com","2=
82441","23-04-2025 09:50:19","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0004865265","N=
taba","IHS_YND_504","23-04-2025 09:38:02","23-04-2025 09:33:53","23-04-2025=
 09:40:12","ACTIVE No power issue U=3D57V site on grid TX FME Armand Nguets=
a /691144412 from huawei is informed ","Delor Telezing","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE =
No power issue U=3D57V site on grid TX FME Armand Nguetsa /691144412 from h=
uawei is informed ","vanel.mbiada@matech-cameroun.com","250","23-04-2025 09=
:38:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004865222","Abang","=
","23-04-2025 09:28:19","23-04-2025 08:39:58","23-04-2025 10:21:12","Cascad=
ed Incident from TTO4974890","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage gen failed to start due to=
 alarm high temp//We add water and gen manually started","system","1235349"=
,"23-04-2025 09:28:19","MATECH CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0004865195","N=
gousso OCM","","23-04-2025 09:23:05","23-04-2025 09:18:56","23-04-2025 13:3=
9:38","Grid outage, Site went down due to Fuel shortage // Refueling done",=
"Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge, Site went down due to Fuel shortage // Refueling done","vanel.mbiada@ma=
tech-cameroun.com","250","23-04-2025 09:23:05","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004865188","A=
wae Ewonkan","","23-04-2025 09:22:30","23-04-2025 09:19:21","23-04-2025 10:=
35:24","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
 // he reduced load","Albran Byorel","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid outage site went down due to Gen Overload (20Kva,=
 Iload 225 A) // he reduced load","vanel.mbiada@matech-cameroun.com","190",=
"23-04-2025 09:22:30","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004865172","F=
ouda-New","","23-04-2025 09:18:10","23-04-2025 08:59:47","23-04-2025 11:08:=
09","Grid outage, Gen failed to start due to Alarm Fail to start // Gen car=
d reset and Gen start  Manually ","Delor Telezing","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen failed to start du=
e to Alarm Fail to start // Gen card reset and Gen start  Manually ","vanel=
.mbiada@matech-cameroun.com","1104","23-04-2025 09:18:10","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004865094","B=
arriere","","23-04-2025 09:05:54","23-04-2025 09:04:43","23-04-2025 17:16:5=
7","grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed //Grid return","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","grid outage, Site went =
down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and c=
onfirmed //Grid return","vanel.mbiada@matech-cameroun.com","72","23-04-2025=
 09:05:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004865040","Song-bon=
g","","23-04-2025 08:54:49","23-04-2025 08:12:15","23-04-2025 10:19:01","Ca=
scaded Incident from TTO4974894","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage Gen failed to start due=
 gen card alarm // Gen card reset and Gen start manually","system","287390"=
,"23-04-2025 08:54:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004865039","Eseka To=
wn","","23-04-2025 08:54:49","23-04-2025 08:12:15","23-04-2025 10:19:01","C=
ascaded Incident from TTO4974894","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage Gen failed to start du=
e gen card alarm // Gen card reset and Gen start manually","system","287390=
","23-04-2025 08:54:49","MATECH CMR"
"Closed Complete","Site Down","T3206","IHS_YND_759","NOCINC0004865018","Nko=
lfoulou Tsinga Village","","23-04-2025 08:49:53","23-04-2025 08:43:38","23-=
04-2025 10:22:53","Grid outage, gen failed to start because the battery ter=
minals were not well tightened//We fixed well battery terminals and gen man=
ually started","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACD=
G - Generator Battery","Grid outage, gen failed to start because the batter=
y terminals were not well tightened//We fixed well battery terminals and ge=
n manually started","cedric.tiani@matech-cameroun.com","375","23-04-2025 08=
:49:53","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0004865001","E=
seka OCM","IHS_YND_378, IHS_YND_453","23-04-2025 08:45:27","23-04-2025 08:1=
2:15","23-04-2025 10:19:01","Grid outage Gen failed to start due gen card a=
larm // Gen card reset and Gen start manually","Kemeni Franklin","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage Gen faile=
d to start due gen card alarm // Gen card reset and Gen start manually","va=
nel.mbiada@matech-cameroun.com","1993","23-04-2025 08:45:27","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004864997","N=
kolangaa","IHS_YND_290","23-04-2025 08:43:27","23-04-2025 08:39:58","23-04-=
2025 10:22:45","Grid outage gen failed to start due to alarm high temp//We =
add water and gen manually started","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","Gen Temp High","Grid outage gen failed to start due to=
 alarm high temp//We add water and gen manually started","vanel.mbiada@mate=
ch-cameroun.com","210","23-04-2025 08:43:27","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004864884","N=
KOLMEKONG YDE","","23-04-2025 08:31:43","23-04-2025 08:19:24","23-04-2025 1=
0:51:20","Grid outage, Site went down due to fuel shortage // Refuelling do=
ne","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Gri=
d outage, Site went down due to fuel shortage // Refuelling done","vanel.mb=
iada@matech-cameroun.com","740","23-04-2025 08:31:43","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004864870","Nko=
abang2","","23-04-2025 08:28:28","23-04-2025 08:15:21","23-04-2025 09:10:46=
","Fme Brice is informed and reported Gen overload (22KVA, 330A), the super=
visor IHS ALPHONSE is informed // grid restored","Mba Lazare Herve","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Fme Brice is informed a=
nd reported Gen overload (22KVA, 330A), the supervisor IHS ALPHONSE is info=
rmed // grid restored","cedric.tiani@matech-cameroun.com","1435","23-04-202=
5 08:28:28","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004864866","M=
arche Odza","","23-04-2025 08:26:32","23-04-2025 07:32:15","23-04-2025 10:4=
1:04","Grid fluctuation,site went down due to insufficient rectifiers //sit=
e stabilised","Albran Byorel","Grid Supply","Passive","Grid","National Grid=
 - Unstable Grid Supply Issue","Grid fluctuation,site went down due to insu=
fficient rectifiers //site stabilised","vanel.mbiada@matech-cameroun.com","=
3258","23-04-2025 08:26:32","MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004864815","E=
lig-Edzoa","","23-04-2025 08:13:55","23-04-2025 07:41:21","23-04-2025 13:35=
:24","Grid only site went down due to Grid outage // Grid reurn","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid only site=
 went down due to Grid outage // Grid reurn","vanel.mbiada@matech-cameroun.=
com","1955","23-04-2025 08:13:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004864723","Nkongtoc=
k","","23-04-2025 07:52:05","23-04-2025 07:33:00","23-04-2025 08:05:07","Ca=
scaded Incident from TTO4974532","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Gen overload, Site wen=
t down due to low level of water in the radiator // Water add and Gen start=
 manually","system","1145","23-04-2025 07:52:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0004864720","Mendong =
vallee","","23-04-2025 07:52:05","23-04-2025 07:33:00","23-04-2025 08:05:07=
","Cascaded Incident from TTO4974532","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Gen overload, Site we=
nt down due to low level of water in the radiator // Water add and Gen star=
t manually","system","1145","23-04-2025 07:52:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0004864721","Mendong =
Maeture","","23-04-2025 07:52:05","23-04-2025 07:33:00","23-04-2025 08:05:0=
7","Cascaded Incident from TTO4974532","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Gen overload, Sit=
e went down due to low level of water in the radiator // Water add and Gen =
start manually","system","1145","23-04-2025 07:52:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0004864722","Montee-J=
ouvence","","23-04-2025 07:52:05","23-04-2025 07:33:00","23-04-2025 08:05:0=
7","Cascaded Incident from TTO4974532","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Gen overload, Sit=
e went down due to low level of water in the radiator // Water add and Gen =
start manually","system","1145","23-04-2025 07:52:05","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004864716","MBA=
LNGONG LYCEE","","23-04-2025 07:50:45","23-04-2025 07:41:01","24-04-2025 10=
:26:20","Fme Fanda Brice is informed and reported Gen overload, SS IHS Feli=
x is informed // grid restored","Fanda Brice","Grid Supply","Passive","Grid=
","National Grid - Equipment Burnt","Fme Fanda Brice is informed and report=
ed Gen overload, SS IHS Felix is informed // grid restored","cedric.tiani@m=
atech-cameroun.com","585","23-04-2025 07:50:45","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004864692","E=
koumdoum OCM","","23-04-2025 07:46:09","23-04-2025 07:35:59","23-04-2025 07=
:56:33","Grid outage, Site went dowm due to Gen overload // Grid return","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, Site went dowm due to Gen overload // Grid return","vanel.mbiada=
@matech-cameroun.com","610","23-04-2025 07:46:09","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004864669","M=
endong","IHS_YND_692, IHS_YND_569, IHS_YND_236, IHS_YND_349","23-04-2025 07=
:40:13","23-04-2025 07:33:00","23-04-2025 08:05:07","Grid outage, Gen overl=
oad, Site went down due to low level of water in the radiator // Water add =
and Gen start manually","Hyemafo Gildas","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Radiator","Grid outage, Gen overload, Site went down due to l=
ow level of water in the radiator // Water add and Gen start manually","van=
el.mbiada@matech-cameroun.com","434","23-04-2025 07:40:13","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004864634","Odz=
a II OCM","","23-04-2025 07:28:50","23-04-2025 07:17:38","23-04-2025 07:44:=
36","	Grid outage ,site went down because GEN failed to start due to ATS an=
d Gen card faulty // grid returned	","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","	Grid outage ,site went down beca=
use GEN failed to start due to ATS and Gen card faulty // grid returned	","=
cedric.tiani@matech-cameroun.com","25201","23-04-2025 07:28:50","MATECH CMR=
"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004864564","O=
LAMA","","23-04-2025 07:14:07","23-04-2025 07:09:54","23-04-2025 08:22:18",=
"Active//No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","vanel.mbiada@matech-cameroun.com","254","23-04-2=
025 07:14:07","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004864554","Nko=
g-Edzen","","23-04-2025 07:12:06","23-04-2025 07:05:52","23-04-2025 11:55:2=
8","Grid outage,Site went down because GEN ran until fuel shortage//Refueli=
ng done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage,Site went down because GEN ran until fuel shortage//Refueling d=
one","cedric.tiani@matech-cameroun.com","374","23-04-2025 07:12:06","MATECH=
 CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004864550","Ebo=
go","","23-04-2025 07:11:18","23-04-2025 07:03:07","23-04-2025 07:15:19","G=
rid outage,site went down before gen starts due to poor battery backup//Gri=
d return","Siligap Boris","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage,site went down before gen starts due=
 to poor battery backup//Grid return","cedric.tiani@matech-cameroun.com","4=
92","23-04-2025 07:11:18","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004864539","M=
ANGUIERS CHAPELLE","","23-04-2025 07:10:11","23-04-2025 07:05:55","23-04-20=
25 10:09:52","Grid outage, site went down due to fuel shortage // Refuellli=
ng done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage, site went down due to fuel shortage // Refuellling done","va=
nel.mbiada@matech-cameroun.com","258","23-04-2025 07:10:11","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004864502","M=
bankomo IHS","","23-04-2025 07:00:38","23-04-2025 06:54:27","23-04-2025 10:=
21:01","Grid outage, Gen failed to start due to Card of Gen faulty, // Gene=
rator started manually and generator rectifiers were reset","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
 Gen failed to start due to Card of Gen faulty, // Generator started manual=
ly and generator rectifiers were reset","vanel.mbiada@matech-cameroun.com",=
"372","23-04-2025 07:00:38","MATECH CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004864497","Ngu=
ila","","23-04-2025 06:59:36","23-04-2025 06:31:15","23-04-2025 12:46:18","=
Grrid outage, Gen failed to start due to Battery Discharge // Gen started w=
ith battery backup","Parker Tchoup","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Battery","Grrid outage, Gen failed to start due to Batte=
ry Discharge // Gen started with battery backup","cedric.tiani@matech-camer=
oun.com","1857","23-04-2025 06:59:36","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004864491","A=
kak-Nkozoa-MTN-IHS","","23-04-2025 06:57:27","23-04-2025 06:21:17","23-04-2=
025 11:03:50","Site went down due to fuel shortage // Refuelling done","Fab=
rice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Site went d=
own due to fuel shortage // Refuelling done","vanel.mbiada@matech-cameroun.=
com","2172","23-04-2025 06:57:27","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004864461","Men=
dong NB","","23-04-2025 06:50:09","23-04-2025 06:45:00","23-04-2025 20:58:0=
0","Grid ooutage.no space to deploy mobile gen//Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid ooutage.no sp=
ace to deploy mobile gen//Grid return","cedric.tiani@matech-cameroun.com","=
310","23-04-2025 06:50:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004864441","Ebeba","=
","23-04-2025 06:44:29","23-04-2025 06:32:34","23-04-2025 09:26:35","Cascad=
ed Incident from TTO4974281","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site was struck by lightning ; GE card, sta=
tic charger, eneo meter, faulty surge protector, eneo transformer fuse open=
, 02 card faulty in TX equipment // Gen starts manually","system","279034",=
"23-04-2025 06:44:29","MATECH CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0004864425","Nke=
ng likok","IHS_YND_339","23-04-2025 06:39:52","23-04-2025 06:32:34","23-04-=
2025 09:26:35","site was struck by lightning ; GE card, static charger, ene=
o meter, faulty surge protector, eneo transformer fuse open, 02 card faulty=
 in TX equipment // Gen starts manually","Kemeni Franklin","Force Majeure",=
"Natural Disaster","Thunderstrike","Equipment Damaged","site was struck by =
lightning ; GE card, static charger, eneo meter, faulty surge protector, en=
eo transformer fuse open, 02 card faulty in TX equipment // Gen starts manu=
ally","cedric.tiani@matech-cameroun.com","439","23-04-2025 06:39:52","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004864327","TSINGA V=
ILLAGE 2","","23-04-2025 06:18:09","23-04-2025 06:10:24","23-04-2025 06:14:=
55","Cascaded Incident from TTO4974173","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation,site went do=
wn because Gen failed to start due to Grid bad voltage//site on GEN","syste=
m","266027","23-04-2025 06:18:09","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004864322","N=
kolfoulou","IHS_YND_719","23-04-2025 06:16:31","23-04-2025 06:10:24","23-04=
-2025 06:14:55","Grid fluctuation,site went down because Gen failed to star=
t due to Grid bad voltage//site on GEN","Siligap Boris","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,sit=
e went down because Gen failed to start due to Grid bad voltage//site on GE=
N","vanel.mbiada@matech-cameroun.com","368","23-04-2025 06:16:31","MATECH C=
MR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0004864319","E=
bogo","","23-04-2025 06:15:23","23-04-2025 06:10:02","23-04-2025 06:16:54",=
"Grid outage, Site went down before Gen start due to poor backup/ // Gen au=
tomatically started","Siligap Boris","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup/ // Gen automatically started","vanel.mbiada@mat=
ech-cameroun.com","323","23-04-2025 06:15:23","MATECH CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0004864290","S=
oa-II","","23-04-2025 06:07:56","23-04-2025 06:04:17","23-04-2025 07:05:53"=
,"Site went down because of the malfunctioning of the ZTE PWC // He reset t=
he PWC","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier=
 Module Overloaded","Site went down because of the malfunctioning of the ZT=
E PWC // He reset the PWC","vanel.mbiada@matech-cameroun.com","220","23-04-=
2025 06:07:56","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004864272","Nom=
ayos montee Meche","","23-04-2025 06:03:46","23-04-2025 05:57:24","23-04-20=
25 06:11:38","Grid outage, Site went down before Gen start due to poor back=
up/ // Gen automatically started","Fanda Brice","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup/ // Gen automatically started","cedri=
c.tiani@matech-cameroun.com","383","23-04-2025 06:03:46","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004864263","M=
EFOU ASSI","","23-04-2025 06:02:38","23-04-2025 05:47:41","23-04-2025 06:13=
:22","Grid outage, Site went down before Gen start due to poor backup/ // G=
en automatically started","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup/ // Gen automatically started","vanel.mbiada@=
matech-cameroun.com","898","23-04-2025 06:02:38","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004864252","Mon=
tee Jouvence","","23-04-2025 05:59:24","23-04-2025 05:56:22","23-04-2025 06=
:35:41","Site was on Gen due to Grid outage, site went down because gen sto=
pped with high temp alarm // he added water and manually start the gen","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine T=
emp - Coolant Level Issue","Site was on Gen due to Grid outage, site went d=
own because gen stopped with high temp alarm // he added water and manually=
 start the gen","cedric.tiani@matech-cameroun.com","183","23-04-2025 05:59:=
24","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004864212","O=
LAMA","","23-04-2025 05:46:25","23-04-2025 05:43:00","23-04-2025 05:50:46",=
"Active//No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","vanel.mbiada@matech-cameroun.com","206","23-04-2=
025 05:46:25","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004864168","N=
kolfoulou","","23-04-2025 05:35:56","23-04-2025 05:33:42","23-04-2025 05:40=
:51","Grid fluctuation,site went iwn because Gen failed to start due to Gri=
d bad voltage//Grid return","Siligap Boris","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid fluctuation,site went iwn b=
ecause Gen failed to start due to Grid bad voltage//Grid return","vanel.mbi=
ada@matech-cameroun.com","135","23-04-2025 05:35:56","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0004864147","Nko=
langaa","","23-04-2025 05:28:11","23-04-2025 05:24:58","23-04-2025 05:28:50=
","Grid fluctuation,site went iwn because Gen failed to start due to Grid b=
ad voltage//Grid return","Mba Lazare Herve","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid fluctuation,site went iwn b=
ecause Gen failed to start due to Grid bad voltage//Grid return","vanel.mbi=
ada@matech-cameroun.com","194","23-04-2025 05:28:11","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0004864145","Aba=
ng","","23-04-2025 05:27:15","23-04-2025 05:23:58","23-04-2025 05:28:17","A=
ctive//No power issue site on Grid with U=3D55.5V ,The FME TX Henri (691145=
055) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue site on Grid with U=3D55.5V ,The FME TX Henri (691145055) from Hua=
wei is informed","vanel.mbiada@matech-cameroun.com","198","23-04-2025 05:27=
:15","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004864140","OTE=
LE MTN","","23-04-2025 05:26:30","23-04-2025 05:24:07","23-04-2025 05:28:05=
","Active//No power issue site on Grid with U=3D55.5V ,The FME TX Henri (69=
1145055) from Huawei is informed","Fanda Brice","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue site on Grid with U=3D55.5V ,The FME TX Henri (691145055) from Huaw=
ei is informed","vanel.mbiada@matech-cameroun.com","144","23-04-2025 05:26:=
30","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004864105","O=
dza II OCM","","23-04-2025 05:12:41","23-04-2025 05:09:50","23-04-2025 06:2=
9:13","Grid outage,Site went Down due to ATS and Gen card Faulty // Grid re=
stored","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","Grid outage,Site went Down due to ATS and Gen card Faulty // G=
rid restored","vanel.mbiada@matech-cameroun.com","173","23-04-2025 05:12:41=
","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004864041","Jou=
vence Mbenda","","23-04-2025 05:00:27","23-04-2025 04:57:06","23-04-2025 05=
:28:21","Grid outage.gen failed to start due to alarm high temp //We add wa=
ter and gen manually started ","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.g=
en failed to start due to alarm high temp //We add water and gen manually s=
tarted ","vanel.mbiada@matech-cameroun.com","202","23-04-2025 05:00:27","MA=
TECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004863934","Nsi=
malen MTN","","23-04-2025 04:40:47","23-04-2025 04:38:33","23-04-2025 05:02=
:55","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automatically","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen started automatically","cedric.tiani@=
matech-cameroun.com","135","23-04-2025 04:40:47","MATECH CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004863711","M=
ambine","","23-04-2025 02:57:31","23-04-2025 02:53:06","23-04-2025 03:13:56=
","Hybrid gen site .gen failed to start due to airintake//We purged and gen=
 manually started ","Fanda Brice","Fuel Outage (Probable)","Passive","ACDG =
Gen","ACDG - Air Intake","Hybrid gen site .gen failed to start due to airin=
take//We purged and gen manually started ","vanel.mbiada@matech-cameroun.co=
m","266","23-04-2025 02:57:31","MATECH CMR"
"Closed Complete","Site Down","T0401","IHS_YND_205","NOCINC0004863703","Ton=
golo MTN","","23-04-2025 02:53:02","23-04-2025 02:43:55","23-04-2025 03:17:=
53","Grid otage site went down because Gen failed to start due to  Gen card=
 faulty // he started Gen manually ","Fabrice Pouakam","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid otage site went down becau=
se Gen failed to start due to  Gen card faulty // he started Gen manually "=
,"cedric.tiani@matech-cameroun.com","548","23-04-2025 02:53:02","MATECH CMR=
"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004863615","Ako=
no","IHS_YND_687","23-04-2025 02:25:48","23-04-2025 02:22:38","23-04-2025 0=
2:44:36"," Grid outage, Site went down due to Dysfunctioning of Gen (Old Ge=
n) // Gen start manually.","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","
Grid outage, Site went down due to Dysfunctioning of Gen (Old Gen) // Gen s=
tart manually.","cedric.tiani@matech-cameroun.com","191","23-04-2025 02:25:=
48","MATECH CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0004863584","OLA=
MA","","23-04-2025 02:24:10","23-04-2025 02:22:38","23-04-2025 02:44:36",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","
Grid outage, Site went down due to Dysfunctioning of Gen (Old Gen) // Gen s=
tart manually.","cedric.tiani@matech-cameroun.com","265208","23-04-2025 02:=
24:10","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004863579","NKO=
MEKUI OCM","","23-04-2025 02:22:11","23-04-2025 02:17:58","23-04-2025 02:20=
:17","No power issue site on gen with U=3D54.5v Notice that site is impacte=
d by Mbankolo Camtel","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","No pow=
er issue site on gen with U=3D54.5v Notice that site is impacted by Mbankol=
o Camtel","cedric.tiani@matech-cameroun.com","254","23-04-2025 02:22:11","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004863457","F=
ouda-New","","23-04-2025 01:50:59","23-04-2025 01:47:08","23-04-2025 02:47:=
08","Active: no power issue, site is on battery with Ubaie=3D54.6V, Armand =
Nguetsa(691144412) from Huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: no power issue, site is on battery with Ubaie=3D54.6V, Armand Nguetsa=
(691144412) from Huawei is informed","vanel.mbiada@matech-cameroun.com","23=
1","23-04-2025 01:50:59","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004863444","Mim=
boman4","","23-04-2025 01:44:01","23-04-2025 01:35:49","23-04-2025 01:51:53=
","Grid outage,site went down because gen failed to start due to battery Ge=
 faulty //grid return","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - Generator Battery","Grid outage,site went down because gen f=
ailed to start due to battery Ge faulty //grid return","cedric.tiani@matech=
-cameroun.com","493","23-04-2025 01:44:01","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004863421","N=
yom OCM","","23-04-2025 01:34:46","23-04-2025 01:33:29","23-04-2025 01:47:0=
7","Grid fluctuation,site went down because Gen failed to start due to ALAR=
M failed to start//Grid return","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid fluctuation,site went down beca=
use Gen failed to start due to ALARM failed to start//Grid return","vanel.m=
biada@matech-cameroun.com","78","23-04-2025 01:34:46","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004863418","O=
dza","","23-04-2025 01:33:40","23-04-2025 01:30:17","23-04-2025 03:17:40","=
Grid fluctuation,site went down because Gen failed to start due to grid bad=
 voltage//he bypassed the Grid and site on Gen","Albran Byorel","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tion,site went down because Gen failed to start due to grid bad voltage//he=
 bypassed the Grid and site on Gen","vanel.mbiada@matech-cameroun.com","204=
","23-04-2025 01:33:40","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004863415","Nsi=
malen MTN","","23-04-2025 01:32:59","23-04-2025 01:30:50","23-04-2025 01:40=
:08","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","cedric.tiani@matech-cameroun.com","129","=
23-04-2025 01:32:59","MATECH CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0004863396","Evo=
doula MTN","","23-04-2025 01:18:12","23-04-2025 01:16:59","23-04-2025 02:55=
:00","Grid outage, site went down because gen start and stopped with Under =
voltage alarm // he Reset the Gen card and gen started Manually","TIENTCHEU=
 NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, site went down because gen start and stopped with Under =
voltage alarm // he Reset the Gen card and gen started Manually","cedric.ti=
ani@matech-cameroun.com","74","23-04-2025 01:18:12","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004863380","M=
EHANDAN","","23-04-2025 01:12:04","23-04-2025 01:09:02","23-04-2025 01:50:1=
7","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage,Site went Down due to ATS and Gen card Faulty // Gri=
d restored","vanel.mbiada@matech-cameroun.com","262535","23-04-2025 01:12:0=
4","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004863377","O=
dza II OCM","IHS_YND_528","23-04-2025 01:10:56","23-04-2025 01:09:02","23-0=
4-2025 01:50:56","Grid outage,Site went Down due to ATS and Gen card Faulty=
 // Grid restored","Albran Byorel","Equipment Repair","Passive","Control Pa=
nel","ATS-AMF Issue","Grid outage,Site went Down due to ATS and Gen card Fa=
ulty // Grid restored","vanel.mbiada@matech-cameroun.com","115","23-04-2025=
 01:10:56","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004863362","S=
atcom","","23-04-2025 01:08:46","23-04-2025 01:04:33","23-04-2025 01:20:33"=
,"ACTIVE//No power issue on site, site on gen Ubaie=3D31.9V .The Tx Fme Arm=
and nguetsa(691144412) From huawei is informed.","Delor Telezing","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE//No power issue on site, site on gen Ubaie=3D31.9V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","vanel.mbiada@matech-came=
roun.com","254","23-04-2025 01:08:46","MATECH CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0004863053","Nke=
ng likok","IHS_YND_339","22-04-2025 23:28:50","22-04-2025 23:23:36","22-04-=
2025 23:27:03","Grid fluctuation,site went down because Gen failed to start=
 due to Grid bad voltage//Gen manually started","Kemeni Franklin","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation,site went down because Gen failed to start due to Grid bad voltage//=
Gen manually started","cedric.tiani@matech-cameroun.com","315","22-04-2025 =
23:28:50","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0004863043","Ebe=
ba","","22-04-2025 23:26:14","22-04-2025 23:23:36","22-04-2025 23:27:03",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid fluctuation,site went down because Gen failed to start due to Grid=
 bad voltage//Gen manually started","cedric.tiani@matech-cameroun.com","261=
559","22-04-2025 23:26:14","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004862918","Elo=
umdem stade","","22-04-2025 23:05:27","22-04-2025 23:00:16","22-04-2025 23:=
10:03","site went down due to insufficiency of rectifiers// site stabilised=
","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"site went down due to insufficiency of rectifiers// site stabilised","ced=
ric.tiani@matech-cameroun.com","312","22-04-2025 23:05:27","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004862859","Nom=
ayos montee Meche","","22-04-2025 22:57:58","22-04-2025 22:56:44","22-04-20=
25 23:10:19","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On G=
rid The Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On Grid =
The Tx FME Fulbert(654266068) from Huawei is informed","cedric.tiani@matech=
-cameroun.com","75","22-04-2025 22:57:58","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004862146","Eki=
e sud","","22-04-2025 21:50:59","22-04-2025 21:48:49","22-04-2025 22:40:01"=
,"Grid outage,site went down due to PWC ZTE dysfunctionning//He reset it an=
d started the GEN manually","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","Grid outage,site went down due to =
PWC ZTE dysfunctionning//He reset it and started the GEN manually","gerard.=
tchangoue@matech-cameroun.com","131","22-04-2025 21:50:59","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004862104","M=
ontee-Des-Soeurs","","22-04-2025 21:40:13","22-04-2025 21:36:02","22-04-202=
5 22:39:37"," access issue during the night due to landlord(Site went down =
because Gen failed to start investigation ongoing)","Hyemafo Gildas","Acces=
s Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land L=
ord"," access issue during the night due to landlord(Site went down because=
 Gen failed to start investigation ongoing)","edwige.kapawo@matech-cameroun=
.com","252","22-04-2025 21:40:13","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004862052","M=
essassi 2","","22-04-2025 21:30:28","22-04-2025 21:25:20","22-04-2025 21:30=
:08","Site went down due to Deficiency rectifiers on site//site stabilised"=
,"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site went down due to Deficiency rectifiers on site//site stabilised",=
"edwige.kapawo@matech-cameroun.com","310","22-04-2025 21:30:28","MATECH CMR=
"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004861917","A=
wae Ewonkan","","22-04-2025 21:09:57","22-04-2025 21:07:59","23-04-2025 01:=
30:27","no power issue on site Tx issue U=3D54.1V site on Grid , the fme tx=
 Henri//699949693 from Huawei is informed","Albran Byorel","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no p=
ower issue on site Tx issue U=3D54.1V site on Grid , the fme tx Leonel Stev=
e//655184876 from Huawei is informed","edwige.kapawo@matech-cameroun.com","=
119","22-04-2025 21:09:57","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004861813","B=
iteng-Maetur","","22-04-2025 20:52:51","22-04-2025 20:43:35","22-04-2025 21=
:06:14","Active//No power issue, Ubay:52.1V on grid, Tx FME lionel steve ad=
jep/655124876/ From huawei is informed. Notice that we have disjunction at =
BTS OCM","Mba Lazare Herve","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Active//No power issue, Ubay:52.1V =
on grid, Tx FME lionel steve adjep/655124876/ From huawei is informed. Noti=
ce that we have disjunction at BTS OCM","edwige.kapawo@matech-cameroun.com"=
,"558","22-04-2025 20:52:51","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004861711","B=
arriere","","22-04-2025 20:32:53","22-04-2025 20:23:59","23-04-2025 07:20:5=
1","Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS F=
elix ZAMBE confirmed// Grid return","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Ge=
n overload (20kva, 400A) SS IHS Felix ZAMBE confirmed// Grid return","edwig=
e.kapawo@matech-cameroun.com","535","22-04-2025 20:32:53","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004861633","Eto=
ug ebe Carrefour","","22-04-2025 20:13:22","22-04-2025 20:07:59","22-04-202=
5 21:59:03","Grid outage,site went down because GEN started and stoppped wi=
th alarm undervoltage//he reduced the frequency and started the GEN manuall=
y","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Under V=
oltage","Grid outage,site went down because GEN started and stoppped with a=
larm undervoltage//he reduced the frequency and started the GEN manually","=
gerard.tchangoue@matech-cameroun.com","324","22-04-2025 20:13:22","MATECH C=
MR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004861623","N=
omayos montee Meche","","22-04-2025 20:10:42","22-04-2025 20:07:35","22-04-=
2025 20:36:51","Grid outage, Site went down before Gen start due to poor ba=
ckup/ // Gen automatically started","Fanda Brice","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup/ // Gen automatically started","ger=
ard.tchangoue@matech-cameroun.com","421","22-04-2025 20:10:42","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004861513","N=
KOLMEKONG YDE","","22-04-2025 19:45:17","22-04-2025 19:34:59","22-04-2025 1=
9:50:01","Active//No power issue on site Ubaie =3D53,2 V site on Grid The T=
X FME Synphorien (650257151) from Huawei is informed","Fabrice Pouakam","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site Ubaie =3D53,2 V site on Grid The TX=
 FME Synphorien (650257151) from Huawei is informed","edwige.kapawo@matech-=
cameroun.com","619","22-04-2025 19:45:17","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004861419","N=
YOM 2 IHS","","22-04-2025 19:26:33","22-04-2025 19:21:24","22-04-2025 19:42=
:55","Grid fluctuation,site went down because Gen failed to start due to Gr=
id bad voltage//site on GEN","Fabrice Pouakam","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Grid fluctuation,site went do=
wn because Gen failed to start due to Grid bad voltage//site on GEN","edwig=
e.kapawo@matech-cameroun.com","311","22-04-2025 19:26:33","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004861234","A=
WAE OCM","","22-04-2025 19:00:00","22-04-2025 18:55:49","22-04-2025 20:29:0=
0","Site went down due to disjunction of CB in the energy bay ZTE // He rea=
rmed CB, site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to =
disjunction of CB in the energy bay ZTE // He rearmed CB, site on Grid","ed=
wige.kapawo@matech-cameroun.com","254","22-04-2025 19:00:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004861092","SOA VILL=
AGE","","22-04-2025 18:41:25","22-04-2025 18:38:27","22-04-2025 19:03:27","=
Cascaded Incident from TTO4970503","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work on site =
// End of work","system","278507","22-04-2025 18:41:25","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004861085","SOA=
 TOWN","IHS_YND_323","22-04-2025 18:40:37","22-04-2025 18:38:27","22-04-202=
5 19:03:27","Site went down due to work on site // End of work","Siligap Bo=
ris","Installation Activity","Passive","Planned Activity","Installation Act=
ivity","Site went down due to work on site // End of work","gerard.tchangou=
e@matech-cameroun.com","131","22-04-2025 18:40:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0004861012","Elig-Edz=
oa","","22-04-2025 18:30:48","22-04-2025 18:25:37","22-04-2025 19:12:59","C=
ascaded Incident from TTO4970397","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","site went down due to PWC Overload(12Kw 250A) Bla=
ise Raoul SS IHS is iformed // load reduiced and site is on Grid","system",=
"311","22-04-2025 18:30:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004861013","Elig Edz=
oa","","22-04-2025 18:30:48","22-04-2025 18:25:37","22-04-2025 19:12:59","C=
ascaded Incident from TTO4970397","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down due to PWC Overload(=
12Kw 250A) Blaise Raoul SS IHS is iformed // load reduiced and site is on G=
rid","system","311","22-04-2025 18:30:48","MATECH CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0004860997","N=
taba","IHS_YND_133, IHS_YND_504","22-04-2025 18:29:55","22-04-2025 18:25:37=
","22-04-2025 19:16:01","site went down due to PWC Overload(12Kw 250A) Blai=
se Raoul SS IHS is iformed // load reduiced and site is on Grid","Delor Tel=
ezing","Equipment Repair","Passive","Rectifier","Rectifier Module Overloade=
d","site went down due to PWC Overload(12Kw 250A) Blaise Raoul SS IHS is if=
ormed // load reduiced and site is on Grid","edwige.kapawo@matech-cameroun.=
com","259","22-04-2025 18:29:55","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004860876","AWA=
E OCM","","22-04-2025 18:08:40","22-04-2025 17:59:29","22-04-2025 18:35:29"=
,"Site went down due to disjunction of CB in the energy bay ZTE // He rearm=
ed CB, site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to di=
sjunction of CB in the energy bay ZTE // He rearmed CB, site on Grid","edwi=
ge.kapawo@matech-cameroun.com","553","22-04-2025 18:08:40","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004860818","Nsi=
malen MTN","","22-04-2025 17:58:25","22-04-2025 17:53:59","22-04-2025 18:03=
:59","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","gerard.tchangoue@matech-cameroun.com","26=
6","22-04-2025 17:58:25","MATECH CMR"
"Closed Complete","Warning","CTR_005","IHS_YND_374","NOCINC0004860543","Mat=
omb","","22-04-2025 17:15:57","","","FME report no High temp Issue on site"=
,"Kemeni Franklin","Warning","Warning","POWER","Warning - ACDG - High Engin=
e Temp - Radiator Leakage","CTR_005","gerard.tchangoue@matech-cameroun.com"=
,"478","22-04-2025 17:15:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004860510","Leboudi"=
,"","22-04-2025 17:11:45","22-04-2025 17:09:02","22-04-2025 17:12:00","Casc=
aded Incident from TTO4969838","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site Went Down because  aben=
a (699999625/Mactech) was on site for work ( swap in the  baie IPT ) // End=
 of work","system","284047","22-04-2025 17:11:45","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004860508","N=
kolafeme","IHS_YND_309","22-04-2025 17:11:12","22-04-2025 17:09:02","22-04-=
2025 17:13:02","Site Went Down because  abena (699999625/Mactech) was on si=
te for work ( swap in the  baie IPT ) // End of work","TIENTCHEU NZETCHIEU =
GAEL","Equipment Replacement","Passive","Planned Activity","Planned Activit=
y - Passive","Site Went Down because  abena (699999625/Mactech) was on site=
 for work ( swap in the  baie IPT ) // End of work","edwige.kapawo@matech-c=
ameroun.com","130","22-04-2025 17:11:12","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004860429","Elo=
umdem stade","","22-04-2025 16:58:07","22-04-2025 16:52:54","22-04-2025 20:=
00:22","Grid fluctuation, Site went down because gen fails to start due to =
grid bad voltage// Grid stabilized","Fanda Brice","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site wen=
t down because gen fails to start due to grid bad voltage// Grid stabilized=
","gerard.tchangoue@matech-cameroun.com","314","22-04-2025 16:58:07","MATEC=
H CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004860344","Eke=
kam","","22-04-2025 16:47:20","22-04-2025 16:44:59","22-04-2025 18:22:30","=
Gen stopped due to alarm High Temperature // add water and Start Gen manual=
ly   ","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","=
Gen Temp High","Gen stopped due to alarm High Temperature // add water and =
Start Gen manually   ","gerard.tchangoue@matech-cameroun.com","142","22-04-=
2025 16:47:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0004860291","BONAS YD=
E","","22-04-2025 16:36:36","22-04-2025 16:31:39","22-04-2025 18:06:33","Ca=
scaded Incident from TTO4969585","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage gen ran until fuel shortage=
 // Refueling done","system","271715","22-04-2025 16:36:36","MATECH CMR"
"Closed Complete","Site Down","CTR_242","IHS_YND_059","NOCINC0004860286","E=
-Poste 2","IHS_YND_683","22-04-2025 16:35:47","22-04-2025 16:31:39","22-04-=
2025 18:06:33","Grid outage gen ran until fuel shortage // Refueling done",=
"Paul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage=
 gen ran until fuel shortage // Refueling done","edwige.kapawo@matech-camer=
oun.com","249","22-04-2025 16:35:47","MATECH CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004860262","Mel=
en Ba'aba","","22-04-2025 16:31:35","22-04-2025 16:27:25","22-04-2025 16:55=
:25","Site went Down because fme was on site to work (PM) // End of work","=
Siligap Boris","Equipment Replacement","Passive","Planned Activity","Planne=
d Activity - Passive","Site went Down because fme was on site to work (PM) =
// End of work","gerard.tchangoue@matech-cameroun.com","434","22-04-2025 16=
:31:35","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004860230","AWA=
E OCM","","22-04-2025 16:26:55","22-04-2025 16:23:44","22-04-2025 17:01:56"=
,"Site went down due to disjunction of CB in the energy bay ZTE // He rearm=
ed CB, site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to di=
sjunction of CB in the energy bay ZTE // He rearmed CB, site on Grid","gera=
rd.tchangoue@matech-cameroun.com","221","22-04-2025 16:26:55","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004860004","Nom=
ayos montee Meche","","22-04-2025 15:58:49","22-04-2025 15:55:29","22-04-20=
25 15:57:04","Grid outage, Site went down before Gen start due to poor back=
up/ // Gen automatically started","Fanda Brice","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup/ // Gen automatically started","gerar=
d.tchangoue@matech-cameroun.com","201","22-04-2025 15:58:49","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004859943","NYO=
M FACE MAETUR","","22-04-2025 15:46:27","22-04-2025 15:44:15","22-04-2025 1=
7:38:15","Grid outage .site went down due to relay 220v faulty//We replace =
relay and gen manually started","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage .site went down due to r=
elay 220v faulty//We replace relay and gen manually started","gerard.tchang=
oue@matech-cameroun.com","134","22-04-2025 15:46:27","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004859886","Nko=
l-Mbanda","","22-04-2025 15:38:39","22-04-2025 15:37:30","22-04-2025 15:51:=
30","FME Matech MINKA SOL Nicolas (656587607 /674885070) is on site for wor=
k (swap of battery bay) // End of work","MINKA NICOLAS","Installation Activ=
ity","Passive","Planned Activity","Installation Activity","FME Matech MINKA=
 SOL Nicolas (656587607 /674885070) is on site for work (swap of battery ba=
y) // End of work","gerard.tchangoue@matech-cameroun.com","70","22-04-2025 =
15:38:39","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004859836","Mok=
olo Yaounde","","22-04-2025 15:32:54","22-04-2025 15:24:23","22-04-2025 15:=
26:23","Site went down due to insufficient rectifiers Faulty on site//Site =
stabilised","","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to insufficient rectifiers Faulty on site//Site stabili=
sed","gerard.tchangoue@matech-cameroun.com","512","22-04-2025 15:32:54","MA=
TECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004859776","NTU=
I TOWN","","22-04-2025 15:23:26","22-04-2025 15:14:59","22-04-2025 15:28:59=
","Site went down because Gen failed to start due to Grid bad voltage(lack =
of 01 phase on site)// He did a bridge on the Good phase","Parker Tchoup","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Si=
te went down because Gen failed to start due to Grid bad voltage(lack of 01=
 phase on site)// He did a bridge on the Good phase","gerard.tchangoue@mate=
ch-cameroun.com","509","22-04-2025 15:23:26","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0004859618","Sac=
re Coeur Catholic Church","","22-04-2025 15:04:34","22-04-2025 15:03:17","2=
2-04-2025 15:10:32","Active//No power issue, site is on Grid  with Ubaie 1=
=3D48.3V and Ubaie 2=3D51.4V.. The Tx FME Brice Tsague(650214096) from Huaw=
ei is informed.","Mboua Thierry","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, site i=
s on Grid  with Ubaie 1=3D48.3V and Ubaie 2=3D51.4V.. The Tx FME Brice Tsag=
ue(650214096) from Huawei is informed.","gerard.tchangoue@matech-cameroun.c=
om","78","22-04-2025 15:04:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_190","NOCINC0004859441","Ngousso-=
II","","22-04-2025 14:41:24","22-04-2025 14:31:59","22-04-2025 15:39:33","C=
ascaded Incident from TTO4968611","MFOUAGUEGUE MATHIEU","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down due to 03/04 sl=
ot off rectifier malfuction //he reset it and site is on Grid ","system","2=
79181","22-04-2025 14:41:24","MATECH CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0004859438","N=
kolmesseng","IHS_YND_190","22-04-2025 14:40:33","22-04-2025 14:31:59","22-0=
4-2025 15:54:36","site went down due to 03/04 slot off rectifier malfuction=
 //he reset it and site is on Grid ","Siligap Boris","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","site went down due to 03/04 slot off=
 rectifier malfuction //he reset it and site is on Grid ","edwige.kapawo@ma=
tech-cameroun.com","514","22-04-2025 14:40:33","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004859290","M=
essassi 2","","22-04-2025 14:30:00","22-04-2025 14:26:54","22-04-2025 15:20=
:20","Site went down because rectifiers disfunctionning // He reset it ","F=
abrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down because rectifiers disfunctionning // He reset it ","chris=
telle.ngonga@matech-cameroun.com","188","22-04-2025 14:30:00","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004858801","M=
essa-Carriere OCM","","22-04-2025 13:29:11","22-04-2025 13:21:05","22-04-20=
25 13:31:05","No power issue site on grid with U=3D52,1V, FME TX Mohamadou/=
691144435/ from Huawei is informed.","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D52,1V, FME TX Mohamadou/691144435/ from Huawei is informed.",=
"franck.nkomot@matech-cameroun.com","487","22-04-2025 13:29:11","MATECH CMR=
"
"Closed Complete","Warning","","IHS_YND_240","NOCINC0004858369","Montee Jou=
vence","","22-04-2025 12:29:07","","","site Alarming due to work in the sit=
e // end work","Hyemafo Gildas","Warning","Warning","POWER","Warning - Plan=
ned Activity - Passive","site Alarming due to work in the site // end work"=
,"christelle.ngonga@matech-cameroun.com","1052","22-04-2025 12:29:07","MATE=
CH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004858318","NTU=
I TOWN","","22-04-2025 12:19:01","22-04-2025 12:14:54","22-04-2025 14:20:05=
","Grid outage gen ran until fuel shortage//Refueling done","Parker Tchoup"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran unti=
l fuel shortage//Refueling done","christelle.ngonga@matech-cameroun.com","2=
48","22-04-2025 12:19:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004858313","Leboudi"=
,"","22-04-2025 12:17:49","22-04-2025 12:11:03","22-04-2025 16:32:13","Casc=
aded Incident from TTO4967332","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site Went Down because  aben=
a (699999625/Mactech) was on site for work ( swap in the  baie IPT ) // End=
 of work","system","280241","22-04-2025 12:17:49","MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004858289","N=
kolafeme","IHS_YND_309","22-04-2025 12:13:20","22-04-2025 12:10:03","22-04-=
2025 16:33:52","Site Went Down because  abena (699999625/Mactech) was on si=
te for work ( swap in the  baie IPT ) // End of work","TIENTCHEU NZETCHIEU =
GAEL","Equipment Replacement","Passive","Planned Activity","Planned Activit=
y - Passive","Site Went Down because  abena (699999625/Mactech) was on site=
 for work ( swap in the  baie IPT ) // End of work","christelle.ngonga@mate=
ch-cameroun.com","414","22-04-2025 12:13:20","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004858125","Aka=
k-Nkozoa-MTN-IHS","","22-04-2025 11:38:15","22-04-2025 11:34:06","22-04-202=
5 17:13:06","FME Matech Fabrice (657108613) is on site for work (swap of ba=
ttery bay) //  End of work","Fabrice Pouakam","Equipment Replacement","Pass=
ive","Planned Activity","Planned Activity - Passive","FME Matech Fabrice (6=
57108613) is on site for work (swap of battery bay) //  End of work","franc=
k.nkomot@matech-cameroun.com","250","22-04-2025 11:38:15","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004858040","Eto=
ug ebe Carrefour","","22-04-2025 11:23:27","22-04-2025 11:16:18","22-04-202=
5 13:37:08","Site down because ,Grid faulty since tree days ( meter burned =
), gen ran still fuel shortage // site refueled .","Hyemafo Gildas","Fuel O=
utage","Passive","Diesel","Diesel Outage","Grid faulty since tree days ( me=
ter burned ), gen ran still fuel shortage // site refueled .","christelle.n=
gonga@matech-cameroun.com","430","22-04-2025 11:23:27","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004857959","B=
iteng-Maetur","","22-04-2025 11:08:51","22-04-2025 11:02:36","22-04-2025 13=
:30:12"," No power issue on site U:52.51 V, Load: 142 A, FME TX Lionnel (65=
5184876 / HUAWEI) is informed","Mba Lazare Herve","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No power iss=
ue on site U:52.51 V, Load: 142 A, FME TX Lionnel (655184876 / HUAWEI) is i=
nformed","christelle.ngonga@matech-cameroun.com","377","22-04-2025 11:08:51=
","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004857818","N=
kolangaa","IHS_YND_290","22-04-2025 11:00:45","22-04-2025 10:56:31","22-04-=
2025 13:51:03"," No power issue site On gen with U=3D53.1v Notice that we h=
ave disjunction at OCM Equipements. Kenfack (691145055) from Huawei is info=
rmed ","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm"," No power issue site On gen with U=3D=
53.1v Notice that we have disjunction at OCM Equipements. Kenfack (69114505=
5) from Huawei is informed ","christelle.ngonga@matech-cameroun.com","255",=
"22-04-2025 11:00:45","MATECH CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0004857812","A=
bang","","22-04-2025 11:00:00","22-04-2025 10:56:31","22-04-2025 13:51:03",=
"Cascaded Incident from TTO4966797","Mba Lazare Herve","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Cascaded Incident from TTO4966797"=
,"christelle.ngonga@matech-cameroun.com","277663","22-04-2025 11:00:00","MA=
TECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004857459","Elo=
umdem stade","","22-04-2025 10:10:14","22-04-2025 10:03:06","22-04-2025 10:=
29:06","Grid fluctuation, Site went down because gen fails to start due to =
grid bad voltage// He put site on Gen","Fanda Brice","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site =
went down because gen fails to start due to grid bad voltage// He put site =
on Gen","franck.nkomot@matech-cameroun.com","429","22-04-2025 10:10:14","MA=
TECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004857388","Nom=
ayos montee Meche","","22-04-2025 09:55:03","22-04-2025 09:51:56","22-04-20=
25 09:59:51","Grid outage site went down before Gen started due to poor bat=
tery back up // Eneo return","Fanda Brice","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage site went down befo=
re Gen started due to poor battery back up // Eneo return","christelle.ngon=
ga@matech-cameroun.com","502","22-04-2025 09:55:03","MATECH CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0004857093","Nko=
lfoulou CSD MTN","","22-04-2025 09:01:58","22-04-2025 08:57:45","22-04-2025=
 09:45:37","Grid outage,gen failed to start due to alarm""low oil pressure"=
"//we reset card GE and gen manually started","Siligap Boris","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,gen failed t=
o start due to alarm""low oil pressure""//we reset card GE and gen manually=
 started","franck.nkomot@matech-cameroun.com","254","22-04-2025 09:01:58","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004856968","Akono","=
","22-04-2025 08:37:49","22-04-2025 08:04:31","22-04-2025 08:11:28","Cascad=
ed Incident from TTO4965657","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue on site Ubaie =3D54.9V =
site on Grid The TX FME Rodrigue (655102999) from Huawei is informed","syst=
em","266266","22-04-2025 08:37:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004856965","OTELE MT=
N","","22-04-2025 08:37:48","22-04-2025 08:04:31","22-04-2025 08:11:28","Ca=
scaded Incident from TTO4965657","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue on site Ubaie =3D54=
.9V site on Grid The TX FME Rodrigue (655102999) from Huawei is informed","=
system","266266","22-04-2025 08:37:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004856966","Minka","=
","22-04-2025 08:37:48","22-04-2025 08:04:31","22-04-2025 08:11:28","Cascad=
ed Incident from TTO4965657","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue on site Ubaie =3D54.9V =
site on Grid The TX FME Rodrigue (655102999) from Huawei is informed","syst=
em","266267","22-04-2025 08:37:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004856967","Mom","",=
"22-04-2025 08:37:48","22-04-2025 08:04:31","22-04-2025 08:11:28","Cascaded=
 Incident from TTO4965657","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Active//No power issue on site Ubaie =3D54.9V si=
te on Grid The TX FME Rodrigue (655102999) from Huawei is informed","system=
","266266","22-04-2025 08:37:48","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004856914","Ako=
k Ndoe Yde","","22-04-2025 08:28:55","22-04-2025 08:22:42","22-04-2025 09:0=
0:43","Grid outage, site down due to poor battery backup // Gen start manua=
lly","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, site down due to poor battery backup //=
 Gen start manually","franck.nkomot@matech-cameroun.com","374","22-04-2025 =
08:28:55","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004856838","Saa=
","","22-04-2025 08:08:04","22-04-2025 08:04:55","22-04-2025 09:08:55","Gri=
d outage ,site down due to fuel issue // Fuel tank tilted , refueling is on=
 going","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage ,site down due to fuel issue // Fuel tank tilted , refueling is =
on going","franck.nkomot@matech-cameroun.com","190","22-04-2025 08:08:04","=
MATECH CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0004856805","OLA=
MA","IHS_YND_531, IHS_YND_371, IHS_YND_370, IHS_YND_365","22-04-2025 08:06:=
46","22-04-2025 08:04:31","22-04-2025 08:35:28","Active//No power issue on =
site Ubaie =3D54.9V site on Grid The TX FME Rodrigue (655102999) from Huawe=
i is informed","Fanda Brice","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site Uba=
ie =3D54.9V site on Grid The TX FME Rodrigue (655102999) from Huawei is inf=
ormed","franck.nkomot@matech-cameroun.com","137","22-04-2025 08:06:46","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004856518","B=
arriere","","22-04-2025 06:47:42","21-04-2025 22:53:05","22-04-2025 19:00:0=
1","grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // Grid return","Hyemafo Gildas","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","grid outage, Site went=
 down because Gen overload(20kva,400 A) IHS SS Felix Zambe is informed and =
confirmed // Grid return","vanel.mbiada@matech-cameroun.com","28478","22-04=
-2025 06:47:42","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004856417","M=
essa-Carriere OCM","","22-04-2025 06:19:43","22-04-2025 06:03:25","22-04-20=
25 09:09:47","Grid outage.no space to deploy mobile gen//Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge.no space to deploy mobile gen//Grid return","vanel.mbiada@matech-camerou=
n.com","980","22-04-2025 06:19:43","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004856369","Ako=
k Ndoe Yde","","22-04-2025 06:08:44","22-04-2025 06:04:20","22-04-2025 06:2=
8:15","Grid outage, site down due to poor battery backup // Gen start manua=
lly","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, site down due to poor battery backup //=
 Gen start manually","vanel.mbiada@matech-cameroun.com","265","22-04-2025 0=
6:08:44","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0004856360","Y=
oko OCM","","22-04-2025 06:06:31","22-04-2025 05:58:10","22-04-2025 06:30:5=
9","No power issue on site ,site on Gen with Ubaie=3D53V, Tx Fme Gregoire( =
652070658)From Huawei is informed.","Parker Tchoup","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site ,site on Gen with Ubaie=3D53V, Tx Fme Gregoire( 652070658)From =
Huawei is informed.","vanel.mbiada@matech-cameroun.com","503","22-04-2025 0=
6:06:31","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004855944","M=
arche Odza","","22-04-2025 04:42:50","22-04-2025 04:33:35","22-04-2025 04:4=
2:20","Grid fluctuation,site went down due to insufficient rectifiers //sit=
e stabilised","Albran Byorel","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Grid fluctuation,site went down due to insufficient rectifi=
ers //site stabilised","vanel.mbiada@matech-cameroun.com","556","22-04-2025=
 04:42:50","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004855844","SAA=
 Entrance","","22-04-2025 03:26:32","22-04-2025 03:17:56","22-04-2025 06:49=
:30","Grid outage,Site went down because Gen ailed to start due to Gen star=
ter faulty//He replaced and manually started the Gen","Parker Tchoup","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid outage,Site =
went down because Gen ailed to start due to Gen starter faulty//He replaced=
 and manually started the Gen","cedric.tiani@matech-cameroun.com","518","22=
-04-2025 03:26:32","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004855842","NKO=
MEKUI OCM","","22-04-2025 03:25:28","22-04-2025 03:18:08","22-04-2025 03:20=
:08","No power issue site on gen with U=3D54.5v Notice that site is impacte=
d by Mbankolo Camtel","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","No pow=
er issue site on gen with U=3D54.5v Notice that site is impacted by Mbankol=
o Camtel","cedric.tiani@matech-cameroun.com","442","22-04-2025 03:25:28","M=
ATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004855739","Nko=
abang Alembe","","22-04-2025 02:57:56","22-04-2025 01:06:03","22-04-2025 03=
:28:11","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Eneo outage, DG stopped due to fuel shortage // Refuelin=
g done, 20L","cedric.tiani@matech-cameroun.com","269838","22-04-2025 02:57:=
56","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004855576","Mok=
olo Yaounde","","22-04-2025 01:57:10","22-04-2025 01:52:58","22-04-2025 02:=
02:23","No power issue U =3D53,2V site on grid. The Tx FME Eloundou Bertran=
d (693212405)from Huawei is informed","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D53=
,2V site on grid. The Tx FME Eloundou Bertrand (693212405)from Huawei is in=
formed","cedric.tiani@matech-cameroun.com","254","22-04-2025 01:57:10","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0004855568","B=
astos-BAT","","22-04-2025 01:52:24","22-04-2025 01:50:10","22-04-2025 02:02=
:10","Grid outage site went down because Gen failed to start due to poor ba=
ttery backup//Gen automatically started","Mboua Thierry","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site =
went down because Gen failed to start due to poor battery backup//Gen autom=
atically started","vanel.mbiada@matech-cameroun.com","135","22-04-2025 01:5=
2:24","MATECH CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0004855535","M=
VAN SACEL","","22-04-2025 01:38:02","22-04-2025 01:35:35","22-04-2025 02:14=
:27","No power issue on site U=3D54,5v site on Grid Tx FME Lionel (65518487=
6) of huawei is informed","MINKA NICOLAS","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54,5v site on Grid Tx FME Lionel (655184876) of huawei is informed","=
vanel.mbiada@matech-cameroun.com","149","22-04-2025 01:38:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004855318","Bastos B=
ethesda","","22-04-2025 00:16:03","22-04-2025 00:03:53","22-04-2025 00:10:4=
4","Cascaded Incident from TTO4963991","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active// No power issue on site Ub=
aie=3D50.6V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is info=
rmed.Repetitive Issues","system","266446","22-04-2025 00:16:03","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0004855317","Bastos-N=
ylon","","22-04-2025 00:16:03","22-04-2025 00:03:53","22-04-2025 00:10:44",=
"Cascaded Incident from TTO4963991","Mboua Thierry","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active// No power issue on site Ubaie=
=3D50.6V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informe=
d.Repetitive Issues","system","266447","22-04-2025 00:16:03","MATECH CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0004855312","Mim=
boman","","22-04-2025 00:12:11","22-04-2025 00:06:59","22-04-2025 01:24:23"=
,"Grid fluctuation,site went down because Gen failed to start due to Grid b=
ad voltage and no RCP on site// He bypass the Grid and Site onGen	","Mba La=
zare Herve","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation,site went down because Gen failed to start due =
to Grid bad voltage and no RCP on site// He bypass the Grid and Site onGen	=
","cedric.tiani@matech-cameroun.com","313","22-04-2025 00:12:11","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004855308","Golf Qua=
ter","","22-04-2025 00:11:10","22-04-2025 00:03:53","22-04-2025 00:10:44","=
Cascaded Incident from TTO4963991","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active// No power issue on site Ubaie=
=3D50.6V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informe=
d.Repetitive Issues","system","266446","22-04-2025 00:11:10","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004855302","T=
singa","IHS_YND_220, IHS_YND_126, IHS_YND_563","22-04-2025 00:08:04","22-04=
-2025 00:03:53","22-04-2025 00:45:46","Active// No power issue on site Ubai=
e=3D50.6V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is inform=
ed.Repetitive Issues","Mboua Thierry","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue o=
n site Ubaie=3D50.6V site on Grid The Tx Eloundou Bertrand /693212405/Huawe=
i is informed.Repetitive Issues","vanel.mbiada@matech-cameroun.com","252","=
22-04-2025 00:08:04","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0004855301","N=
komkana","","22-04-2025 00:07:14","22-04-2025 00:03:54","22-04-2025 03:06:1=
0","FME Emmanuel SONKOUE(694 56 70 96) from  SNEF is on site working to Upg=
rade 10G_COREVO //End of work","","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","FME Emmanuel SONKOUE(694 56 7=
0 96) from  SNEF is on site working to Upgrade 10G_COREVO //End of work","v=
anel.mbiada@matech-cameroun.com","201","22-04-2025 00:07:14","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004855299","N=
komkana 2","","22-04-2025 00:06:13","22-04-2025 00:03:02","22-04-2025 01:38=
:49","No power issue on site ,site on Grid with Ubaie=3D50.2 V The TX fme B=
rice stague//650214096/690286359 from huawei is informed ","Mboua Thierry",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","No power issue on site ,site on Grid with Ubaie=3D50.2 V The TX=
 fme Brice stague//650214096/690286359 from huawei is informed ","vanel.mbi=
ada@matech-cameroun.com","192","22-04-2025 00:06:13","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004855228","Sof=
avinc","","21-04-2025 23:43:32","21-04-2025 23:38:19","21-04-2025 23:56:31"=
,"Site went down due to insufficient  rectifiers on site// Site stabilized"=
,"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient  rectifiers on site// Site stabilized=
","cedric.tiani@matech-cameroun.com","313","21-04-2025 23:43:32","MATECH CM=
R"
"Closed Complete","Site Down","CTR_694","IHS_YND_714","NOCINC0004855217","E=
kekam","","21-04-2025 23:41:31","21-04-2025 18:22:20","22-04-2025 01:07:40"=
,"Backtracking Hybrid Gen Site: Site went down due to hybrid system dysfunc=
tionning // Reset PSC 3 and Gen manually started .","TIENTCHEU NZETCHIEU GA=
EL","Equipment Repair","Passive","Hybrid","Hybrid Module"," Hybrid Gen Site=
: Site went down due to hybrid system dysfunctionning // Reset PSC 3 and Ge=
n manually started .","vanel.mbiada@matech-cameroun.com","19152","21-04-202=
5 23:41:31","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004855122","M=
ontee-Des-Soeurs","","21-04-2025 23:21:30","21-04-2025 23:17:14","22-04-202=
5 07:41:01","Site down because  Grid neutral phase got disconnected from th=
e pole// site put permanently on gen","Hyemafo Gildas","Grid Supply","Passi=
ve","Grid","National Grid - Poles Failed","Site down due to Grid neutral ph=
ase disconnected frome poles// site put permanenly on gen","vanel.mbiada@ma=
tech-cameroun.com","257","21-04-2025 23:21:30","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004855007","N=
kolondom","","21-04-2025 22:50:54","21-04-2025 22:49:47","21-04-2025 23:00:=
07","Grid fluctuation,site went down because Gen failed to start due to Gri=
d bad voltage//He bypassed the Grid and site on Gen","Fabrice Pouakam","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation,site went down because Gen failed to start due to Grid bad volt=
age//He bypassed the Grid and site on Gen","vanel.mbiada@matech-cameroun.co=
m","69","21-04-2025 22:50:54","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004855002","NYO=
M 2 IHS","","21-04-2025 22:49:28","21-04-2025 22:43:19","21-04-2025 22:53:2=
3","Grid fluctuation,site went down because Gen failed to start due to Grid=
 bad voltage//Grid return","Fabrice Pouakam","Grid Supply","Passive","Grid"=
,"National Grid - Phase Controller Faulty","Grid fluctuation,site went down=
 because Gen failed to start due to Grid bad voltage//Grid return","cedric.=
tiani@matech-cameroun.com","370","21-04-2025 22:49:28","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004855001","NYO=
M FACE MAETUR","","21-04-2025 22:48:57","21-04-2025 22:43:48","21-04-2025 2=
3:45:04","Grid fluctuation,Site went down because Gen failed to start due t=
o Grid bad voltage //He bypassed the Grid and site on GEN","Fabrice Pouakam=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation,Site went down because Gen failed to start due to Grid ba=
d voltage //He bypassed the Grid and site on GEN","cedric.tiani@matech-came=
roun.com","310","21-04-2025 22:48:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004854989","Nkolfon =
Cimencam","","21-04-2025 22:48:06","21-04-2025 22:23:25","21-04-2025 23:03:=
54","Cascaded Incident from TTO4963597","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation,site went do=
wn because Gen failed to start due to Grid bad voltage//Grid return","syste=
m","265234","21-04-2025 22:48:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0004854988","Ahala","=
","21-04-2025 22:48:05","21-04-2025 22:23:25","21-04-2025 23:03:54","Cascad=
ed Incident from TTO4963597","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid fluctuation,site went down because =
Gen failed to start due to Grid bad voltage//Grid return","system","265234"=
,"21-04-2025 22:48:05","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004854980","O=
LAMA","","21-04-2025 22:44:53","21-04-2025 22:41:42","21-04-2025 22:51:54",=
"Active//No power issue on site Ubaie =3D54.1V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.1V site on Grid The TX FME Henri (69994969=
3) from Huawei is informed","vanel.mbiada@matech-cameroun.com","193","21-04=
-2025 22:44:53","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004854962","M=
eyo","IHS_YND_257, IHS_YND_313, IHS_YND_762","21-04-2025 22:39:34","21-04-2=
025 22:23:25","21-04-2025 23:03:54","Grid fluctuation,site went down becaus=
e Gen failed to start due to Grid bad voltage//Grid return","Hyemafo Gildas=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation,site went down because Gen failed to start due to Grid ba=
d voltage//Grid return","vanel.mbiada@matech-cameroun.com","969","21-04-202=
5 22:39:34","MATECH CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0004854947","A=
fanoya","","21-04-2025 22:38:09","21-04-2025 22:23:25","21-04-2025 23:03:54=
","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid fluctuation,site went down because Gen failed to start due =
to Grid bad voltage//Grid return","vanel.mbiada@matech-cameroun.com","26523=
4","21-04-2025 22:38:09","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004854900","Nsi=
malen MTN","","21-04-2025 22:30:26","21-04-2025 22:28:11","21-04-2025 22:38=
:18","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automatically","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen started automatically","cedric.tiani@=
matech-cameroun.com","136","21-04-2025 22:30:26","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004854897","Bar=
riere","","21-04-2025 22:29:48","21-04-2025 21:04:35","21-04-2025 22:44:44"=
,"grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Feli=
x Zambe is informed and confirmed // He reduced the load and gen manually s=
tarted","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","grid outage, Site went down because Gen overload(20kva,400 A) IHS =
SS Felix Zambe is informed and confirmed // He reduced the load and gen man=
ually started","cedric.tiani@matech-cameroun.com","34704","21-04-2025 22:29=
:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004854616","MEHANDAN=
","","21-04-2025 21:15:51","21-04-2025 21:11:48","21-04-2025 22:00:17","Cas=
caded Incident from TTO4963158","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,site went down because GE=
N failed to start due to ATS and Gen card faulty // grid returned","system"=
,"269595","21-04-2025 21:15:51","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004854610","O=
dza II OCM","IHS_YND_528","21-04-2025 21:14:40","21-04-2025 21:11:48","21-0=
4-2025 22:00:17","Grid outage ,site went down because GEN failed to start d=
ue to ATS and Gen card faulty // grid returned","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went=
 down because GEN failed to start due to ATS and Gen card faulty // grid re=
turned","edwige.kapawo@matech-cameroun.com","173","21-04-2025 21:14:40","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004854586","Elig Edz=
oa","","21-04-2025 21:10:34","21-04-2025 21:03:59","21-04-2025 21:48:31","C=
ascaded Incident from TTO4963059","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","(Grid outage,Site went down because=
 Gen failed (investigation ongoing)","system","1240929","21-04-2025 21:10:3=
4","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0004854585","Elig-Edz=
oa","","21-04-2025 21:10:34","21-04-2025 21:03:59","21-04-2025 21:48:31","C=
ascaded Incident from TTO4963059","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","(Grid outage,Site went down because Gen failed (i=
nvestigation ongoing)","system","1240929","21-04-2025 21:10:34","MATECH CMR=
"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0004854516","N=
taba","IHS_YND_133, IHS_YND_504","21-04-2025 21:05:07","21-04-2025 21:03:59=
","21-04-2025 22:58:07","Access issue DUE TO LANDLORD Site went down due to=
 PWC Huawei malfunction SS IHS Blaise Raoul confirmed //He reset it and sit=
e on GEN","Delor Telezing","Access Denial","Lease Or Legal","Landlord Relat=
ed Issues","Access Issue - Land Lord","(Grid outage,Site went down because =
Gen failed (investigation ongoing)","edwige.kapawo@matech-cameroun.com","69=
","21-04-2025 21:05:07","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004854499","Sof=
avinc","","21-04-2025 21:02:51","21-04-2025 20:57:18","21-04-2025 21:03:33"=
,"Site went down because rectifiers disfunctionning// Site stabilized","MIN=
KA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down because rectifiers disfunctionning// Site stabilized","gerard.=
tchangoue@matech-cameroun.com","333","21-04-2025 21:02:51","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004854405","NYO=
M FACE MAETUR","","21-04-2025 20:49:58","21-04-2025 20:46:28","21-04-2025 2=
0:48:28","Eneo fluctuations, Site went down because gen fails to start due =
to Grid fluctuations //Grid stabilisation","Fabrice Pouakam","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Eneo fluctuations, Si=
te went down because gen fails to start due to Grid fluctuations //Grid sta=
bilisation","gerard.tchangoue@matech-cameroun.com","211","21-04-2025 20:49:=
58","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004854339","Aka=
k-Nkozoa-MTN-IHS","","21-04-2025 20:36:59","21-04-2025 20:26:59","21-04-202=
5 22:09:51","Site went down due to PWC Huawei malfunction SS IHS Felix Bate=
u confirmed //He reset it and site on GEN","Fabrice Pouakam","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Site went down du=
e to PWC Huawei malfunction SS IHS Felix Bateu confirmed //He reset it and =
site on GEN","gerard.tchangoue@matech-cameroun.com","602","21-04-2025 20:36=
:59","MATECH CMR"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004854258","N=
omayos montee Meche","","21-04-2025 20:15:00","21-04-2025 20:07:52","21-04-=
2025 22:10:52","Grid fluctuation, Site went down because gen fails to start=
 due to grid bad voltage// He bypasse the Grid and site on Gen","Fanda Bric=
e","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage// He bypasse the Grid and site on Gen","edwige.kapawo@matech-cam=
eroun.com","429","21-04-2025 20:15:00","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004854181","Bar=
riere","","21-04-2025 19:56:14","21-04-2025 19:54:05","21-04-2025 19:56:23"=
,"Grid outage, Site down due to gen overlord (20KVA/ load 350A) IHS SS Feli=
x Zambe is informed and confirmed // Grid restoration","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site d=
own due to gen overlord (20KVA/ load 350A) IHS SS Felix Zambe is informed a=
nd confirmed // Grid restoration","gerard.tchangoue@matech-cameroun.com","1=
30","21-04-2025 19:56:14","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004854145","B=
iteng-Maetur","","21-04-2025 19:47:26","21-04-2025 19:40:15","21-04-2025 20=
:48:05","Active//No power issue, Ubay:52.1V on grid, Tx FME lionel steve ad=
jep/655124876/ From huawei is informed. Notice that we have disjunction at =
BTS OCM","Mba Lazare Herve","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Active//No power issue, Ubay:52.1V =
on grid, Tx FME lionel steve adjep/655124876/ From huawei is informed. Noti=
ce that we have disjunction at BTS OCM","edwige.kapawo@matech-cameroun.com"=
,"432","21-04-2025 19:47:26","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0004853912","O=
lembe","","21-04-2025 19:16:03","21-04-2025 19:09:48","21-04-2025 20:02:51"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage,// He bypasse the Grid and site on Gen","Fabrice Pouakam","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation, Site went down because gen fails to start due to grid bad voltag=
e,// He bypasse the Grid and site on Gen","edwige.kapawo@matech-cameroun.co=
m","376","21-04-2025 19:16:03","MATECH CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0004853807","N=
koabang","","21-04-2025 18:47:08","21-04-2025 18:44:53","21-04-2025 19:27:0=
4","Site went down because 01/04 rectifiers dysfunctionned // He resetd rec=
tifiers,site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Site went down because 01/04 rectifiers dysfunct=
ionned // He resetd rectifiers,site on Grid","edwige.kapawo@matech-cameroun=
.com","136","21-04-2025 18:47:08","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004853792","Sof=
avinc","","21-04-2025 18:42:46","21-04-2025 18:37:12","21-04-2025 18:43:12"=
,"Site went down because rectifiers disfunctionning// Site stabilized","MIN=
KA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module","di=
sfunctionning","gerard.tchangoue@matech-cameroun.com","335","21-04-2025 18:=
42:46","MATECH CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004853479","Mvo=
g-Betsi","","21-04-2025 17:46:39","21-04-2025 17:45:30","21-04-2025 18:03:3=
0","Site went down due to rectifiers insufficiency // site stabilized","Hye=
mafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","S=
ite went down due to rectifiers insufficiency // site stabilized","gerard.t=
changoue@matech-cameroun.com","69","21-04-2025 17:46:39","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0004853341","Men=
dong Plateau","","21-04-2025 17:17:58","21-04-2025 17:11:59","21-04-2025 17=
:19:59","No power issue site on grid with U=3D51.2v Notice that we have dys=
junction at MTN Equipements site up at 05:19 PM Mbah Osiah from Huawei was =
informed","Hyemafo Gildas","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D51.2v Notice that we have dysjunction at MTN Equipements site up at 05:1=
9 PM Mbah Osiah from Huawei was informed","gerard.tchangoue@matech-cameroun=
.com","359","21-04-2025 17:17:58","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004853328","Men=
dong vallee","","21-04-2025 17:16:50","21-04-2025 17:07:59","21-04-2025 17:=
58:59","Site went down due to gen Overload(20KVA; 300A) IHS F=E9lix Zamb=E9=
 is informed and confirmed//he Reduice the Load and Manually Started the Ge=
n","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Site went down due to gen Overload(20KVA; 300A) IHS F=E9lix Zamb=E9 is inf=
ormed and confirmed//he Reduice the Load and Manually Started the Gen","ger=
ard.tchangoue@matech-cameroun.com","532","21-04-2025 17:16:50","MATECH CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0004853308","E=
kie sud","","21-04-2025 17:12:47","21-04-2025 15:04:12","21-04-2025 17:16:1=
0","Grid outage gen ran until fuel shortage//Refueling done","Albran Byorel=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran unt=
il fuel shortage//Refueling done","edwige.kapawo@matech-cameroun.com","7716=
","21-04-2025 17:12:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004853297","Angongo"=
,"","21-04-2025 17:10:44","21-04-2025 17:03:43","21-04-2025 17:54:43","Casc=
aded Incident from TTO4961656","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage,gen stopped with alarm high t=
emp//he added water in radiator","system","269871","21-04-2025 17:10:44","M=
ATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0004853291","Ebe=
ba","IHS_YND_335","21-04-2025 17:08:50","21-04-2025 17:03:43","21-04-2025 1=
7:54:43","Grid outage,gen stopped with alarm high temp//he added water in r=
adiator","Fanda Brice","Equipment Repair","Passive","ACDG Gen","Gen Temp Hi=
gh","Grid outage,gen stopped with alarm high temp//he added water in radiat=
or","gerard.tchangoue@matech-cameroun.com","308","21-04-2025 17:08:50","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0004853149","M=
endong Maeture","","21-04-2025 16:45:09","21-04-2025 16:41:56","21-04-2025 =
20:45:07","Site went down due to Disjunction of CB (100A) of MTN in the Ene=
rgie bay // CB rearm (Need to replace this CB wiht 125A of CB)","Hyemafo Gi=
ldas","Equipment Repair","Passive","Rectifier","Rectifier - Circuit Breaker=
","Site went down due to Disjunction of CB (100A) of MTN in the Energie bay=
 // CB rearm (Need to replace this CB wiht 125A of CB)","edwige.kapawo@mate=
ch-cameroun.com","194","21-04-2025 16:45:09","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004853131","Jou=
vence Mbenda","","21-04-2025 16:38:43","21-04-2025 16:37:34","21-04-2025 17=
:21:52","Grid outage, site went down because gen start and stopped due to a=
larm""high temp""//We added water and gen manually started","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, sit=
e went down because gen start and stopped due to alarm""high temp""//We add=
ed water and gen manually started","gerard.tchangoue@matech-cameroun.com","=
70","21-04-2025 16:38:43","MATECH CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004853120","Mvo=
g-Betsi","","21-04-2025 16:35:48","21-04-2025 16:33:36","21-04-2025 16:39:3=
4","Site went down due to rectifiers insufficiency  // site stabilized","Hy=
emafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down due to rectifiers insufficiency  // site stabilized","gerard=
.tchangoue@matech-cameroun.com","133","21-04-2025 16:35:48","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004853118","O=
mnisport-Rail","","21-04-2025 16:35:31","21-04-2025 16:28:24","21-04-2025 1=
6:46:36","No power issue on site Ubaie =3D49,6V site on Grid The TX FME Arm=
and Nguetsa (699949553) from huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Ubaie =3D49,6V site on Grid The TX FME Armand Ng=
uetsa (699949553) from huawei is informed.","edwige.kapawo@matech-cameroun.=
com","428","21-04-2025 16:35:31","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004853108","Nsi=
malen MTN","","21-04-2025 16:34:03","21-04-2025 16:26:59","21-04-2025 16:36=
:18","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","gerard.tchangoue@matech-cameroun.com","42=
4","21-04-2025 16:34:03","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004853027","M=
efou-Assi","","21-04-2025 16:24:23","21-04-2025 16:17:03","21-04-2025 19:11=
:14","Grid outage, Site went down due to Gen overload, // Grid return","Fan=
da Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, Site went down due to Gen overload, // Grid return","edwige.kapawo@m=
atech-cameroun.com","441","21-04-2025 16:24:23","MATECH CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004852860","Car=
refour Simbock","","21-04-2025 15:52:42","21-04-2025 14:25:33","21-04-2025 =
18:02:58","Grid outage site went down because Gen failed to start due to Ge=
n battery faulty // Eneo return.","Hyemafo Gildas","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Generator Battery","Grid outage site went down beca=
use Gen failed to start due to Gen battery faulty // Eneo return.","gerard.=
tchangoue@matech-cameroun.com","5230","21-04-2025 15:52:42","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004852857","Men=
dong NB","","21-04-2025 15:51:02","21-04-2025 15:20:54","21-04-2025 18:20:0=
0","Grid ooutage.no space to deploy mobile gen//Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid ooutage.no sp=
ace to deploy mobile gen//Grid return","gerard.tchangoue@matech-cameroun.co=
m","1809","21-04-2025 15:51:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004852698","Tsinga",=
"","21-04-2025 15:16:44","21-04-2025 15:06:35","21-04-2025 15:17:00","Casca=
ded Incident from TTO4960944","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active// No power issue on site Ubaie:53.1V=
 site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informed","syst=
em","262473","21-04-2025 15:16:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004852697","Bastos B=
ethesda","","21-04-2025 15:16:43","21-04-2025 15:06:35","21-04-2025 15:17:0=
0","Cascaded Incident from TTO4960944","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active// No power issue on site Ub=
aie:53.1V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is inform=
ed","system","262472","21-04-2025 15:16:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004852695","Golf Qua=
ter","","21-04-2025 15:16:43","21-04-2025 15:06:35","21-04-2025 15:17:00","=
Cascaded Incident from TTO4960944","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active// No power issue on site Ubaie:=
53.1V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informed",=
"system","262472","21-04-2025 15:16:43","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004852678","B=
astos-Nylon","IHS_YND_220, IHS_YND_563, IHS_YND_127","21-04-2025 15:14:49",=
"21-04-2025 15:06:35","21-04-2025 15:17:00","Active// No power issue on sit=
e Ubaie:53.1V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is in=
formed","Mboua Thierry","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active// No power issue on site Ubaie:5=
3.1V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informed","=
edwige.kapawo@matech-cameroun.com","495","21-04-2025 15:14:49","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004852556","Mes=
sassi 2","","21-04-2025 15:03:01","21-04-2025 14:58:50","21-04-2025 17:19:5=
0","Eneo outage, DG did not start due to alarm low oil pressure // Oil adde=
d, card reseted and Manual start of DG","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - Low Oil Pressure","Eneo outage, DG did not s=
tart due to alarm low oil pressure // Oil added, card reseted and Manual st=
art of DG","gerard.tchangoue@matech-cameroun.com","252","21-04-2025 15:03:0=
1","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004852505","Mon=
tee Jouvence","","21-04-2025 14:54:02","21-04-2025 14:13:54","21-04-2025 15=
:53:47","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started manually","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Gen started manually","gerard.tchangoue@ma=
tech-cameroun.com","2409","21-04-2025 14:54:02","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004852497","E=
MANA BILICK CITY","","21-04-2025 14:51:04","21-04-2025 14:31:55","21-04-202=
5 16:31:44","FME report that awaiting Eneo return because the generator was=
 disconnected due to noise pollution","Fabrice Pouakam","Access Denial","Le=
ase Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid Ou=
tage, Site went Down due to Gen Noise (access issue due to landlord) // Gri=
d restoration","edwige.kapawo@matech-cameroun.com","1150","21-04-2025 14:51=
:04","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004852278","Men=
dong vallee","","21-04-2025 14:02:48","21-04-2025 13:52:42","21-04-2025 16:=
45:46","Site went down due to gen Overload(20KVA; 300A) IHS F=E9lix Zamb=E9=
 is informed and confirmed//he Reduice the Load and Manually Started the Ge=
n","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Site went down due to gen Overload(20KVA; 300A) IHS F=E9lix Zamb=E9 is inf=
ormed and confirmed//he Reduice the Load and Manually Started the Gen","lan=
dry.etame@ihstowers.com","607","21-04-2025 14:02:48","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004852267","UPA=
C LP","","21-04-2025 14:00:44","21-04-2025 13:50:37","22-04-2025 10:59:37",=
"Grid outage, No space to deploy // Grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage, No space to deplo=
y // Grid return","landry.etame@ihstowers.com","608","21-04-2025 14:00:44",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004852240","N=
koabang Ebolmedjock","","21-04-2025 13:56:31","21-04-2025 13:55:25","21-04-=
2025 14:32:43","Site went down because rectifier disfunctionning // He rese=
t ","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down because rectifier disfunctionning // He reset ","ch=
ristelle.ngonga@matech-cameroun.com","67","21-04-2025 13:56:31","MATECH CMR=
"
"Closed Complete","Site Down","CTR_921","IHS_YND_791","NOCINC0004852228","N=
omayos montee Meche","","21-04-2025 13:54:38","21-04-2025 13:35:31","21-04-=
2025 14:03:31","Grid outage site went down before Gen started due to poor b=
attery back up // Eneo return","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage site went down be=
fore Gen started due to poor battery back up // Eneo return","christelle.ng=
onga@matech-cameroun.com","1202","21-04-2025 13:54:38","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004852225","Aka=
k-Nkozoa-MTN-IHS","","21-04-2025 13:53:29","21-04-2025 13:26:24","21-04-202=
5 14:02:14","site went down because the Cb(125A) of PWC Dysjoncted// he mad=
e the bridge of CB(63*63A)","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Circuit Breaker Issue","site went down bec=
ause the Cb(125A) of PWC Dysjoncted// he made the bridge of CB(63*63A)","la=
ndry.etame@ihstowers.com","1627","21-04-2025 13:53:29","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004852221","M=
arche Odza","","21-04-2025 13:52:57","21-04-2025 13:49:50","21-04-2025 13:5=
4:57","Site went down because rectifier disfunctionning // He reset ","Albr=
an Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","Sit=
e went down because rectifier disfunctionning // He reset ","christelle.ngo=
nga@matech-cameroun.com","189","21-04-2025 13:52:57","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004852217","M=
ontee-Jouvence-II","","21-04-2025 13:52:16","21-04-2025 13:49:58","21-04-20=
25 13:54:54","Grid outage site went down before Gen started due to poor bat=
tery back up // Eneo return","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage site went down b=
efore Gen started due to poor battery back up // Eneo return","christelle.n=
gonga@matech-cameroun.com","139","21-04-2025 13:52:16","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004852196","E=
mana lycee 2","","21-04-2025 13:47:29","21-04-2025 13:36:22","21-04-2025 13=
:59:16","Grid outage.gen failed to start due to exhaust pipe faulty causing=
 by high temp//We open the door and site on gen","Fabrice Pouakam","Equipme=
nt Repair","Passive","ACDG Gen","Gen Temp High","Site went Down because Exh=
aust hose cut // he opened the doors","christelle.ngonga@matech-cameroun.co=
m","668","21-04-2025 13:47:29","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004852193","Nko=
lbisson usines des eaux 2","","21-04-2025 13:47:15","21-04-2025 13:35:06","=
21-04-2025 13:51:06","Grdi fluctuation, Site went down because Gen failed t=
o start due to grid bad voltage No crcp // Eneo stabilized","TIENTCHEU NZET=
CHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grdi fluctuation, Site went down because Gen failed to start due=
 to grid bad voltage No crcp // Eneo stabilized","franck.nkomot@matech-came=
roun.com","730","21-04-2025 13:47:15","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004852190","M=
EFOU ASSI","","21-04-2025 13:46:46","21-04-2025 13:36:40","21-04-2025 14:06=
:13","Grid outage site went down before Gen started due to poor battery bac=
k up // Eneo return","Fanda Brice","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage site went down before Gen s=
tarted due to poor battery back up // Eneo return","christelle.ngonga@matec=
h-cameroun.com","608","21-04-2025 13:46:46","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004852189","Mes=
sassi 2","","21-04-2025 13:46:38","21-04-2025 13:35:32","21-04-2025 13:53:3=
2","Site went down due to Deficiency rectifiers on site//site stabilised","=
Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to Deficiency rectifiers on site//site stabilised","f=
ranck.nkomot@matech-cameroun.com","668","21-04-2025 13:46:38","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004852186","O=
dza II OCM","IHS_YND_528","21-04-2025 13:46:06","21-04-2025 13:33:59","21-0=
4-2025 15:41:02","Grid outage site went down because Gen failed to start du=
e to Gen card faulty // Gen Manually Started","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went do=
wn because Gen failed to start due to Gen card faulty // Gen Manually Start=
ed","christelle.ngonga@matech-cameroun.com","729","21-04-2025 13:46:06","MA=
TECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004852184","Ako=
k Ndoe Yde","","21-04-2025 13:45:59","21-04-2025 13:35:45","21-04-2025 13:4=
8:45","Grid outage site went down before Gen started due to poor battery ba=
ck up // Eneo return","Hyemafo Gildas","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage site went down before G=
en started due to poor battery back up // Eneo return","franck.nkomot@matec=
h-cameroun.com","615","21-04-2025 13:45:59","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004852172","M=
EHANDAN","","21-04-2025 13:44:27","21-04-2025 13:33:59","21-04-2025 15:41:0=
2","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage site went down because Gen failed to start due to Ge=
n card faulty // Gen Manually Started","christelle.ngonga@matech-cameroun.c=
om","275529","21-04-2025 13:44:27","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004852159","Nsi=
malen MTN","","21-04-2025 13:42:32","21-04-2025 13:33:23","21-04-2025 13:43=
:23","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","franck.nkomot@matech-cameroun.com","550",=
"21-04-2025 13:42:32","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004852150","M=
essassi okolo","","21-04-2025 13:42:19","21-04-2025 13:33:12","21-04-2025 1=
5:08:52","No power issue on site Ubaie: 54.59 V, Load 109,2 A, site on Grid=
 The TX Fme Synphorien 691316854 of Huwei is informed","Fabrice Pouakam","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site Ubaie: 54.59 V, Load 109,2 A, site on Grid=
 The TX Fme Synphorien 691316854 of Huwei is informed","christelle.ngonga@m=
atech-cameroun.com","549","21-04-2025 13:42:19","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004852142","E=
mana Lycee","","21-04-2025 13:39:47","21-04-2025 13:36:22","21-04-2025 13:5=
9:32","Site went Down because Exhaust hose cut // he opened the doors","Fab=
rice Pouakam","Cascade Outage","Active","Cascade Active","Cascade Active","=
Site went Down because Exhaust hose cut // he opened the doors","christelle=
.ngonga@matech-cameroun.com","1328","21-04-2025 13:39:47","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0004852101","Sac=
re Coeur Catholic Church","","21-04-2025 13:31:33","21-04-2025 13:29:25","2=
1-04-2025 15:47:57","Active//No power issue, Site on Grid Ubay:49.8 V. The =
Tx FME Brice Tsague(650214096) from Huawei is informed.","Mboua Thierry","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Grid Ubay:49.8 V. The Tx FME Bric=
e Tsague(650214096) from Huawei is informed.","christelle.ngonga@matech-cam=
eroun.com","129","21-04-2025 13:31:33","MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004852081","M=
elen Ba'aba","","21-04-2025 13:29:34","21-04-2025 13:14:28","21-04-2025 13:=
46:36","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // He bypass grid and manually start the gen","Siligap =
Boris","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage // He bypass grid and manually start the gen","christelle=
.ngonga@matech-cameroun.com","908","21-04-2025 13:29:34","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004851718","Eto=
udi2","","21-04-2025 12:08:52","21-04-2025 11:13:42","21-04-2025 11:23:42",=
"No power issue site on Grid with U=3D49,8V. The FME Tx Armand Nguetsa 6911=
44412/ from Huawei is informed. ","Delor Telezing","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on Grid with U=3D49,8V. The FME Tx Armand Nguetsa 691144412/ from H=
uawei is informed. ","franck.nkomot@matech-cameroun.com","3311","21-04-2025=
 12:08:52","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004851596","O=
LAMA","","21-04-2025 11:50:47","21-04-2025 11:21:39","21-04-2025 12:56:38",=
"No power issue on site U:54.9 V( hybrid site). The Tx FME Henri (699949693=
)from Huawei is informed.	","Fanda Brice","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U:54.9 V( hybrid site). The Tx FME Henri (699949693)from Huawei is inform=
ed.	","christelle.ngonga@matech-cameroun.com","1749","21-04-2025 11:50:47",=
"MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004851593","Eki=
e sud","","21-04-2025 11:50:32","21-04-2025 11:42:59","21-04-2025 12:48:59"=
,"Grid fluctuation, Site went down because gen fails to start due to grid b=
ad voltage// He bypasse the Grid and site on Gen","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, Site went down because gen fails to start due to grid bad voltage//=
 He bypasse the Grid and site on Gen","franck.nkomot@matech-cameroun.com","=
454","21-04-2025 11:50:32","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004851438","O=
mnisport-Rail","","21-04-2025 11:24:52","21-04-2025 11:16:46","21-04-2025 1=
1:26:46","Site impacted by MANGUIERS CHAPELLE","Delor Telezing","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","Active//No power issue on=
 site ,site on Grid with Ubaie=3D53.6 V The Tx FME Armand Nguetsa//69994955=
3 from Huawei is informed","christelle.ngonga@matech-cameroun.com","276297"=
,"21-04-2025 11:24:52","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004851433","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","21-04-2025 11:23:58","21-04-=
2025 11:16:46","21-04-2025 15:38:46","grid outage, site went down due to ge=
n Overload(20KVA,270) // grid return","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","grid outage, site went down due to =
gen Overload(20KVA,270) // grid return","christelle.ngonga@matech-cameroun.=
com","434","21-04-2025 11:23:58","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0004851428","M=
anguier","","21-04-2025 11:22:35","21-04-2025 11:16:46","21-04-2025 15:08:4=
6","Site impacted by MANGUIERS CHAPELLE","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active//No power issue on site=
 ,site on Grid with Ubaie=3D53.6 V The Tx FME Armand Nguetsa//699949553 fro=
m Huawei is informed","christelle.ngonga@matech-cameroun.com","276297","21-=
04-2025 11:22:35","MATECH CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0004851342","G=
olf Quater","","21-04-2025 11:20:41","21-04-2025 11:09:19","21-04-2025 12:4=
5:45","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Active// No power issue on site Ubaie=3D49.8V site on Grid The T=
x Eloundou Bertrand /693212405/Huawei is informed","christelle.ngonga@matec=
h-cameroun.com","269533","21-04-2025 11:20:41","MATECH CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0004851311","B=
astos Bethesda","","21-04-2025 11:20:02","21-04-2025 11:09:19","21-04-2025 =
12:45:45","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Ca=
scade Active","Active// No power issue on site Ubaie=3D49.8V site on Grid T=
he Tx Eloundou Bertrand /693212405/Huawei is informed","christelle.ngonga@m=
atech-cameroun.com","269534","21-04-2025 11:20:02","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004851307","T=
singa","IHS_YND_220, IHS_YND_126, IHS_YND_563","21-04-2025 11:19:27","21-04=
-2025 11:09:19","21-04-2025 12:45:45","Active// No power issue on site Ubai=
e=3D49.8V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is inform=
ed","Mboua Thierry","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active// No power issue on site Ubaie=3D49.=
8V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informed","ch=
ristelle.ngonga@matech-cameroun.com","609","21-04-2025 11:19:27","MATECH CM=
R"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004851302","B=
astos-Nylon","","21-04-2025 11:17:49","21-04-2025 11:09:19","21-04-2025 12:=
45:45","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Casca=
de Active","Active// No power issue on site Ubaie=3D49.8V site on Grid The =
Tx Eloundou Bertrand /693212405/Huawei is informed","franck.nkomot@matech-c=
ameroun.com","269533","21-04-2025 11:17:49","MATECH CMR"
"Closed Complete","Site Down","T1582","IHS_YND_138","NOCINC0004851283","Nko=
mkana 2","","21-04-2025 11:13:22","21-04-2025 11:10:48","21-04-2025 16:32:4=
8","site went down due to insufficient rectifiers on site//site stabilized =
(need to added two rectifiers)","Mboua Thierry","Equipment Repair","Passive=
","Rectifier","Rectifier Module","site went down due to insufficient rectif=
iers on site//site stabilized (need to added two rectifiers)","franck.nkomo=
t@matech-cameroun.com","155","21-04-2025 11:13:22","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004850775","M=
arche Odza","","21-04-2025 09:50:39","21-04-2025 09:49:32","21-04-2025 09:5=
0:47","Grid fluctuation,site went down due to rectifiers dysfunction//Grid =
stabilisation","Albran Byorel","Grid Supply","Passive","Grid","National Gri=
d - Unstable Grid Supply Issue","Grid fluctuation,site went down due to rec=
tifiers dysfunction//Grid stabilisation","christelle.ngonga@matech-cameroun=
.com","69","21-04-2025 09:50:39","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004850767","B=
iteng-Maetur","","21-04-2025 09:49:52","21-04-2025 09:45:45","21-04-2025 12=
:28:21","No power issue on site U:52.51 V, Load: 150 A, FME TX Lionnel (655=
184876 / HUAWEI) is informed","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site U:52.51 V, Load: 150 A, FME TX Lionnel (655184876 / HUAWEI) is inf=
ormed","christelle.ngonga@matech-cameroun.com","248","21-04-2025 09:49:52",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004850384","M=
elen Ba'aba","","21-04-2025 08:55:14","21-04-2025 08:48:05","21-04-2025 10:=
00:05","site down because gen took  undervoltge alarm // Gen card reseted",=
"Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","site down because gen took  undervoltge alarm // Gen card reseted","ch=
ristelle.ngonga@matech-cameroun.com","430","21-04-2025 08:55:14","MATECH CM=
R"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004850041","Eki=
e sud","","21-04-2025 07:36:08","21-04-2025 07:31:33","21-04-2025 08:53:59"=
," site down due to Grid bad phase , gen took an overvoltage alarm / reset =
and start gen manually","Albran Byorel","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel"," site down due to Grid bad phase , gen took an=
 overvoltage alarm / reset and start gen manually","franck.nkomot@matech-ca=
meroun.com","275","21-04-2025 07:36:08","MATECH CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004850029","M=
imboman-Ecole","","21-04-2025 07:32:10","21-04-2025 07:15:03","21-04-2025 0=
9:04:44","No power issue on site U:54.2 V,site on grid The FME TX Eloundou =
Bertrant / 693212405/ From Huawei is Informed.","Mba Lazare Herve","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site U:54.2 V,site on grid The FME TX Eloundou Bertra=
nt / 693212405/ From Huawei is Informed.","christelle.ngonga@matech-camerou=
n.com","1029","21-04-2025 07:32:10","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0004849997","Ema=
na Lycee","","21-04-2025 07:19:23","21-04-2025 07:08:11","21-04-2025 13:22:=
11","Site went down due to insufficient rectifiers on site(there is 04 rect=
ifiers on site)//He need to add 02 rectifiers","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","Site went down due to in=
sufficient rectifiers on site(there is 04 rectifiers on site)//He need to a=
dd 02 rectifiers","franck.nkomot@matech-cameroun.com","673","21-04-2025 07:=
19:23","MATECH CMR"
"Closed Complete","Site Down","T1582","IHS_YND_138","NOCINC0004849926","Nko=
mkana 2","","21-04-2025 06:55:05","21-04-2025 06:53:57","21-04-2025 10:50:5=
7","site went down due to insufficient rectifiers on site//site stabilized =
(need to added two rectifiers)","Mboua Thierry","Equipment Repair","Passive=
","Rectifier","Rectifier Module","site went down due to insufficient rectif=
iers on site//site stabilized (need to added two rectifiers)","christelle.n=
gonga@matech-cameroun.com","68","21-04-2025 06:55:05","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004849820","B=
arriere","","21-04-2025 06:25:18","21-04-2025 06:11:10","21-04-2025 14:45:1=
0","grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // He reduced the load and gen manually=
 started","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","grid outage, Site went down because Gen overload(20kva,400 A) IH=
S SS Felix Zambe is informed and confirmed // He reduced the load and gen m=
anually started","franck.nkomot@matech-cameroun.com","849","21-04-2025 06:2=
5:18","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004849743","E=
mana Lycee","","21-04-2025 05:56:13","21-04-2025 05:51:49","21-04-2025 06:5=
8:49","Site went down due to insufficient rectifiers on site(there is 04 re=
ctifiers on site)//He need to add 02 rectifiers","Fabrice Pouakam","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","Site went down due to =
insufficient rectifiers on site(there is 04 rectifiers on site)//He need to=
 add 02 rectifiers","loic.noumsi@matech-cameroun.com","265","21-04-2025 05:=
56:13","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004849732","Aka=
k-Nkozoa-MTN-IHS","","21-04-2025 05:53:53","21-04-2025 05:41:57","21-04-202=
5 08:40:41","Grid outage. Site went down due to PWC dysfunctionning//We res=
et PWC site on gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage. Site went down due to PWC dysfuncti=
onning//We reset PWC site on gen","loic.noumsi@matech-cameroun.com","15818"=
,"21-04-2025 05:53:53","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004849679","OTE=
LE MTN","","21-04-2025 05:38:45","21-04-2025 05:28:34","21-04-2025 14:00:25=
","Site went because Gen started and stopped with alarm low oil pressure //=
He added oil and started Gen manually","Fanda Brice","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Low Oil Pressure","Site went because Gen started =
and stopped with alarm low oil pressure //He added oil and started Gen manu=
ally","loic.noumsi@matech-cameroun.com","612","21-04-2025 05:38:45","MATECH=
 CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004849675","Nko=
ulou Carriere carrefourt","","21-04-2025 05:37:19","21-04-2025 05:28:10","2=
1-04-2025 05:41:49","Error ticket","Mba Lazare Herve","Incorrectly Logged T=
ickets","Error","Error","Error","Running ticket","loic.noumsi@matech-camero=
un.com","550","21-04-2025 05:37:19","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004849662","Eto=
udi2","","21-04-2025 05:30:03","21-04-2025 05:19:55","21-04-2025 06:54:55",=
"Site went down due to insufficiency of rectifier (Site on 02 Rectifiers ) =
SS IHS Bernard Atagana is informed and confimed // Site Stabilized","Delor =
Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Site=
 went down due to insufficiency of rectifier (Site on 02 Rectifiers ) SS IH=
S Bernard Atagana is informed and confimed // Site Stabilized","loic.noumsi=
@matech-cameroun.com","609","21-04-2025 05:30:03","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004849363","Aka=
k-Nkozoa-MTN-IHS","","21-04-2025 03:52:07","21-04-2025 03:43:49","21-04-202=
5 03:55:29","Grid outage, Site went down because Gen failed to start due to=
 PWC ZTE dysfunction// He reset it, Site on Gen","Fabrice Pouakam","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site w=
ent down because Gen failed to start due to PWC ZTE dysfunction// He reset =
it, Site on Gen","loic.noumsi@matech-cameroun.com","499","21-04-2025 03:52:=
07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004849351","Matsari"=
,"","21-04-2025 03:50:17","21-04-2025 03:40:51","21-04-2025 04:59:51","Casc=
aded Incident from TTO4957226","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Huawei controller responsible for the l=
oad order of the Gen faulty. // Manual start of Gen.","system","267595","21=
-04-2025 03:50:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004849353","MBIMBIM"=
,"","21-04-2025 03:50:17","21-04-2025 03:40:51","21-04-2025 04:59:51","Casc=
aded Incident from TTO4957226","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Huawei controller responsible for the l=
oad order of the Gen faulty. // Manual start of Gen.","system","267594","21=
-04-2025 03:50:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0004849352","Yoko OCM=
","","21-04-2025 03:50:17","21-04-2025 03:40:51","21-04-2025 04:59:51","Cas=
caded Incident from TTO4957226","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Huawei controller responsible for the =
load order of the Gen faulty. // Manual start of Gen.","system","267595","2=
1-04-2025 03:50:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004849350","Ngoum","=
","21-04-2025 03:50:16","21-04-2025 03:40:51","21-04-2025 04:59:51","Cascad=
ed Incident from TTO4957226","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Huawei controller responsible for the loa=
d order of the Gen faulty. // Manual start of Gen.","system","267594","21-0=
4-2025 03:50:16","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004849346","N=
gouetou","","21-04-2025 03:49:23","21-04-2025 03:38:09","21-04-2025 07:07:5=
5","Hybrid Gen:Site went down because Gen stopped due to water leak in the =
generator radiator collector //he added water and manually started GEN","Pa=
rker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator Leaka=
ge","Hybrid Gen:Site went down because Gen stopped due to water leak in the=
 generator radiator collector //he added water and manually started GEN","l=
oic.noumsi@matech-cameroun.com","676","21-04-2025 03:49:23","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004849283","B=
arriere","","21-04-2025 03:11:29","21-04-2025 03:09:20","21-04-2025 05:59:4=
0","Fme Gildas is informed and reported Gen overload (20kva,400 A) IHS SS F=
elix Zambe is informed and confirmed // Grid returned","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Fme Gildas is infor=
med and reported Gen overload (20kva,400 A) IHS SS Felix Zambe is informed =
and confirmed // Grid returned","loic.noumsi@matech-cameroun.com","130","21=
-04-2025 03:11:29","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004849265","NKO=
MEKUI OCM","","21-04-2025 03:05:02","21-04-2025 02:55:44","21-04-2025 04:57=
:51","Site impacted by Mbankolo Camtel","TIENTCHEU NZETCHIEU GAEL","Custome=
r Equipment Failure","Active","Active Equipment Failure","Affected by 3rd P=
arty Site","Site impacted by Mbankolo Camtel","loic.noumsi@matech-cameroun.=
com","559","21-04-2025 03:05:02","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004849162","O=
dza II OCM","","21-04-2025 02:09:48","21-04-2025 02:00:43","21-04-2025 02:1=
0:47","Grid outage ,site went down because GEN failed to start due to ATS a=
nd Gen card faulty // grid returned","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went down becau=
se GEN failed to start due to ATS and Gen card faulty // grid returned","lo=
ic.noumsi@matech-cameroun.com","547","21-04-2025 02:09:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004849108","MEHANDAN=
","","21-04-2025 02:03:12","21-04-2025 01:42:59","21-04-2025 01:50:38","Cas=
caded Incident from TTO4956944","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage ,site went down because GE=
N failed to start due to ATS and Gen card faulty// Grid returned","system",=
"1216943","21-04-2025 02:03:12","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004849086","O=
dza II OCM","IHS_YND_528","21-04-2025 02:00:09","21-04-2025 01:42:59","21-0=
4-2025 01:51:18","Grid outage ,site went down because GEN failed to start d=
ue to ATS and Gen card faulty// Grid returned","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went =
down because GEN failed to start due to ATS and Gen card faulty// Grid retu=
rned","loic.noumsi@matech-cameroun.com","1032","21-04-2025 02:00:09","MATEC=
H CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004849055","TSI=
NGA VILLAGE 2","","21-04-2025 01:43:37","21-04-2025 01:34:23","21-04-2025 0=
2:42:26","Grid outage Site down due to Fuel shortage // Refuelling done","D=
elor Telezing","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outag=
e Site down due to Fuel shortage // Refuelling done","loic.noumsi@matech-ca=
meroun.com","555","21-04-2025 01:43:37","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004849023","B=
arriere","","21-04-2025 01:29:19","21-04-2025 01:20:13","21-04-2025 02:02:1=
7","Fme Gildas is informed and reported Gen overload (20kva,400 A) IHS SS F=
elix Zambe is informed and confirmed // Grid returned","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Fme Gildas is infor=
med and reported Gen overload (20kva,400 A) IHS SS Felix Zambe is informed =
and confirmed // Grid returned","loic.noumsi@matech-cameroun.com","547","21=
-04-2025 01:29:19","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004848995","B=
iteng-Maetur","","21-04-2025 01:15:56","20-04-2025 22:18:46","20-04-2025 22=
:19:45","Active//No power issue, U=3D52.1V on grid, Tx FME lionel steve adj=
ep/655124876/ From huawei is informed","Mba Lazare Herve","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue, U=3D52.1V on grid, Tx FME lionel steve adjep/655124876/ =
From huawei is informed","loic.noumsi@matech-cameroun.com","10631","21-04-2=
025 01:15:56","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004848949","A=
kak-Nkozoa-MTN-IHS","","21-04-2025 00:48:05","21-04-2025 00:39:57","21-04-2=
025 03:04:05","Grid outage, Site went down because Gen stopped with ""high =
temp"" alarm // He added water and started Gen manualy","Fabrice Pouakam","=
Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, Site w=
ent down because Gen stopped with ""high temp"" alarm // He added water and=
 started Gen manualy","loic.noumsi@matech-cameroun.com","489","21-04-2025 0=
0:48:05","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004848886","MBA=
LNGONG LYCEE","","21-04-2025 00:22:08","21-04-2025 00:13:44","21-04-2025 00=
:21:31","Fme Fanda Brice is informed and reported Gen overload, SS IHS Feli=
x is informed // grid restored","Fanda Brice","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Fme Fanda Brice is informed and reported Gen =
overload, SS IHS Felix is informed // grid restored","loic.noumsi@matech-ca=
meroun.com","505","21-04-2025 00:22:08","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004848800","M=
bankomo IHS","","21-04-2025 00:12:40","21-04-2025 00:06:34","21-04-2025 00:=
21:13","Grid outage,gen failed to start due to card Ge faulty // Gen manual=
ly restarted ","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG =
- Control Panel","Grid outage,gen failed to start due to card Ge faulty // =
Gen manually restarted ","loic.noumsi@matech-cameroun.com","367","21-04-202=
5 00:12:40","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004848564","A=
WAE OCM","","20-04-2025 23:06:45","20-04-2025 22:57:30","20-04-2025 23:51:1=
3","Site went down due to disjunction of CB in the energy bay ZTE // He rea=
rmed CB, site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to =
disjunction of CB in the energy bay ZTE // He rearmed CB, site on Grid","va=
nel.mbiada@matech-cameroun.com","557","20-04-2025 23:06:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004848495","Mom","",=
"20-04-2025 22:41:10","20-04-2025 22:30:59","20-04-2025 22:41:14","Cascaded=
 Incident from TTO4956250","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","site impacted by Ngoumou","system","264605","20-=
04-2025 22:41:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004848493","OTELE MT=
N","","20-04-2025 22:41:10","20-04-2025 22:30:59","20-04-2025 22:41:14","Ca=
scaded Incident from TTO4956250","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","site impacted by Ngoumou","system","264605=
","20-04-2025 22:41:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004848494","Minka","=
","20-04-2025 22:41:10","20-04-2025 22:30:59","20-04-2025 22:41:14","Cascad=
ed Incident from TTO4956250","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","site impacted by Ngoumou","system","264604","2=
0-04-2025 22:41:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004848492","OLAMA","=
","20-04-2025 22:41:10","20-04-2025 22:30:59","20-04-2025 22:41:14","Cascad=
ed Incident from TTO4956250","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","site impacted by Ngoumou","system","264604","2=
0-04-2025 22:41:10","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004848471","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","20-04-2025 22:38:=
08","20-04-2025 22:30:59","20-04-2025 23:50:51","site impacted by Ngoumou",=
"Fanda Brice","Customer Equipment Failure","Active","Active Equipment Failu=
re","Affected by 3rd Party Site","site impacted by Ngoumou","cedric.tiani@m=
atech-cameroun.com","430","20-04-2025 22:38:08","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004847971","Men=
dong vallee","","20-04-2025 20:44:12","20-04-2025 20:22:57","20-04-2025 23:=
21:02","Site down due to disjunction of circuit breaker (125A) in the energ=
y bay ZTE // CB rearmed, site on GRID","Fanda Brice","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site down d=
ue to disjunction of circuit breaker (125A) in the energy bay ZTE // CB rea=
rmed, site on GRID","cedric.tiani@matech-cameroun.com","1276","20-04-2025 2=
0:44:12","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004847936","B=
arriere","","20-04-2025 20:38:06","20-04-2025 19:41:51","21-04-2025 00:42:2=
4","SITE DOWN SINCE 05:32 PM FME Rodrigue(95934760) is on site doing swappe=
d of PWC ZTE // swap ended","Hyemafo Gildas","Installation Activity","Passi=
ve","Planned Activity","Installation Activity","SITE DOWN SINCE 05:32 PM FM=
E Rodrigue(95934760) is on site doing swapped of PWC ZTE // swap ended","va=
nel.mbiada@matech-cameroun.com","3376","20-04-2025 20:38:06","MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004847837","C=
ite-Verte","","20-04-2025 20:24:22","20-04-2025 20:14:52","20-04-2025 22:09=
:13","Site went down due to disjunction of CBs (125A & 63A) in BTS OCM (FME=
 TX Brice TSAGUE (650214096 / HUAWEI Technician) is informed) // He rearmed=
 CBs, site on grid","","Equipment Repair","Passive","Control Panel","BTS Br=
eaker Faulty","Site went down due to disjunction of CBs (125A & 63A) in BTS=
 OCM (FME TX Brice TSAGUE (650214096 / HUAWEI Technician) is informed) // H=
e rearmed CBs, site on grid","vanel.mbiada@matech-cameroun.com","571","20-0=
4-2025 20:24:22","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004847822","C=
rf-Nsam","","20-04-2025 20:17:44","20-04-2025 20:14:50","20-04-2025 20:21:5=
7","Active//No power issue on site Ubaie =3D52.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D52.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","vanel.mbiada@matech-cameroun.com","175","=
20-04-2025 20:17:44","MATECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0004847773","N=
koa Ayos","","20-04-2025 19:57:10","20-04-2025 19:54:58","20-04-2025 19:55:=
32","Wrongly created ticket","MINKA NICOLAS","Incorrectly Logged Tickets","=
Error","Error","Error","Wrongly created ticket","vanel.mbiada@matech-camero=
un.com","132","20-04-2025 19:57:10","MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004847514","C=
ite-Verte","","20-04-2025 18:44:53","20-04-2025 17:36:37","20-04-2025 19:12=
:32","Active: no power issue, site is ongrid with Ubaie=3D53.6V, TX Fme Bri=
ce Tsague of huawei is informed. Notice that we have disjunction at BTS OCM=
","","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active: no power issue, site is ongrid with Ubaie=3D53.6V,=
 TX Fme Brice Tsague of huawei is informed. Notice that we have disjunction=
 at BTS OCM","vanel.mbiada@matech-cameroun.com","4097","20-04-2025 18:44:53=
","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0004847010","M=
fou EPC","","20-04-2025 16:59:03","20-04-2025 16:30:35","20-04-2025 20:21:2=
5","Grid outage,site went down because Gen failed to start due to unknow ra=
ison (more investigation on going) // Grid return","Mba Lazare Herve","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site=
 went down because Gen failed to start due to unknow raison (more investiga=
tion on going) // Grid return","vanel.mbiada@matech-cameroun.com","1709","2=
0-04-2025 16:59:03","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0004846968","Ema=
na Lycee","","20-04-2025 16:49:44","20-04-2025 16:44:12","20-04-2025 17:48:=
02","Site went down due to insufficient rectifiers on site(there is 04 rect=
ifiers on site)//He need to add 02 rectifiers","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","Site went down due to in=
sufficient rectifiers on site(there is 04 rectifiers on site)//He need to a=
dd 02 rectifiers","cedric.tiani@matech-cameroun.com","333","20-04-2025 16:4=
9:44","MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004846841","C=
ite-Verte","","20-04-2025 16:24:32","20-04-2025 16:23:19","20-04-2025 17:14=
:47","Grid outage//Grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","Grid outage//Grid return","vanel.mbiada@matech-=
cameroun.com","75","20-04-2025 16:24:32","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0004846763","Sac=
re Coeur Catholic Church","","20-04-2025 16:13:26","20-04-2025 16:11:15","2=
0-04-2025 16:20:15","Active//No power issue on site. Site on Grid with Ubai=
e=3D52,8 V The TX Fme Brice Tsague (656718906) from Huawei is informed","Mb=
oua Thierry","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active//No power issue on site. Site on Grid with =
Ubaie=3D52,8 V The TX Fme Brice Tsague (656718906) from Huawei is informed"=
,"cedric.tiani@matech-cameroun.com","131","20-04-2025 16:13:26","MATECH CMR=
"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0004846698","O=
KOA Peage","IHS_YND_695, IHS_YND_350","20-04-2025 15:56:33","20-04-2025 15:=
48:22","20-04-2025 16:00:54","Active// No power issue on site Ubaie=3D54.1 =
site On Grid The Tx FME Fulbert(654266068) of huawei is informed","Fanda Br=
ice","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active// No power issue on site Ubaie=3D54.1 site On Grid =
The Tx FME Fulbert(654266068) of huawei is informed","cedric.tiani@matech-c=
ameroun.com","492","20-04-2025 15:56:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004846686","Mambine"=
,"","20-04-2025 15:53:30","20-04-2025 15:48:22","20-04-2025 16:00:54","Acti=
ve// No power issue on site Ubaie=3D55Vsite On Grid The Tx FME Fulbert(6542=
66068) of huawei is informed ","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active// No power issue on site Ubaie=3D54.1=
 site On Grid The Tx FME Fulbert(654266068) of huawei is informed","system"=
,"795","20-04-2025 15:53:30","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004846677","M=
bankomo IHS","","20-04-2025 15:52:38","20-04-2025 15:48:22","20-04-2025 16:=
00:54","Active// No power issue on site Ubaie=3D55Vsite On Grid The Tx FME =
Fulbert(654266068) of huawei is informed ","Fanda Brice","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active// No power issue on site =
Ubaie=3D55Vsite On Grid The Tx FME Fulbert(654266068) of huawei is informed=
 ","vanel.mbiada@matech-cameroun.com","267191","20-04-2025 15:52:38","MATEC=
H CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004846647","Nsi=
malen MTN","","20-04-2025 15:50:27","20-04-2025 15:47:15","20-04-2025 15:57=
:22","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","cedric.tiani@matech-cameroun.com","193","=
20-04-2025 15:50:27","MATECH CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0004846560","G=
olf Quater","","20-04-2025 15:42:56","20-04-2025 15:37:46","20-04-2025 16:0=
4:12","ACTIVE//No Power issue on site Ubaie=3D53,4V site on Grid The Tx FME=
 Eloumdou betrrand//693212405 from Huawei is informed","Mboua Thierry","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","ACTIVE//No Power issue on site Ubaie=3D53,4V site on Grid The Tx FM=
E Eloumdou betrrand//693212405 from Huawei is informed","vanel.mbiada@matec=
h-cameroun.com","310","20-04-2025 15:42:56","MATECH CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0004846559","M=
vog-Betsi","","20-04-2025 15:42:15","20-04-2025 15:39:02","20-04-2025 15:42=
:22","Site went down due to rectifiers insufficiency  // site stabilized","=
Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to rectifiers insufficiency  // site stabilized","vane=
l.mbiada@matech-cameroun.com","193","20-04-2025 15:42:15","MATECH CMR"
"Closed Complete","Site Down","T0537","IHS_YND_225","NOCINC0004846522","Sci=
ence","","20-04-2025 15:36:00","20-04-2025 15:33:42","20-04-2025 16:41:36",=
"Site went down due to Swapped of PWC by SS HIS Deffo and Willy Kamga(MATEC=
H)//End of Work","TIENTCHEU NZETCHIEU GAEL","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to Swappe=
d of PWC by SS HIS Deffo and Willy Kamga(MATECH)//End of Work","cedric.tian=
i@matech-cameroun.com","139","20-04-2025 15:36:00","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004846510","NKO=
MKANA ELIZA HOTEL","","20-04-2025 15:33:47","20-04-2025 15:33:40","20-04-20=
25 18:16:43","site went down due to insufficiency of rectifiers //Site stab=
ilised","","Equipment Repair","Passive","Rectifier","Rectifier Module","sit=
e went down due to insufficiency of rectifiers //Site stabilised","cedric.t=
iani@matech-cameroun.com","8","20-04-2025 15:33:47","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004846466","N=
KOLMEKONG YDE","","20-04-2025 15:26:49","20-04-2025 15:25:06","20-04-2025 1=
5:30:55","Active//No power issue on site Ubaie =3D53,2 V site on Grid The T=
X FME Synphorien (650257151) from Huawei is informed","Fabrice Pouakam","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site Ubaie =3D53,2 V site on Grid The TX=
 FME Synphorien (650257151) from Huawei is informed","vanel.mbiada@matech-c=
ameroun.com","104","20-04-2025 15:26:49","MATECH CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0004846425","Ngo=
uetou","","20-04-2025 15:23:35","20-04-2025 15:17:25","20-04-2025 19:25:37"=
,"Hybrid Gen:Site went down because Gen stopped due to water leak in the ge=
nerator radiator collector //he added water and manually started GEN","Park=
er Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator Leakage=
","Hybrid Gen:Site went down because Gen stopped due to water leak in the g=
enerator radiator collector //he added water and manually started GEN","ced=
ric.tiani@matech-cameroun.com","371","20-04-2025 15:23:35","MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0004846238","K=
amajou Building","","20-04-2025 14:40:46","20-04-2025 14:37:09","20-04-2025=
 14:46:31","Grid outage, Site went down due to Poor battery backup // Grid =
return","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, Site went down due to Poor battery back=
up // Grid return","vanel.mbiada@matech-cameroun.com","217","20-04-2025 14:=
40:46","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004846224","A=
ccacia New","","20-04-2025 14:32:54","20-04-2025 14:27:36","20-04-2025 17:1=
1:10","ACTIVE No power issue U=3D 54,5 V site on Grid the TX fme mba hosia =
/ 650255744 from huawei is informed","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power issue U=
=3D 54,5 V site on Grid the TX fme mba hosia / 650255744 from huawei is inf=
ormed","vanel.mbiada@matech-cameroun.com","319","20-04-2025 14:32:54","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0004846208","C=
hapelle-Nsimeyong","","20-04-2025 14:30:02","20-04-2025 14:27:40","20-04-20=
25 17:08:47","AcTIVE: no power issue, site is on grid with Ubaie=3D54.5V, H=
osiah(699699694) from Huawei is informed	","MINKA NICOLAS","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","AcTI=
VE: no power issue, site is on grid with Ubaie=3D54.5V, Hosiah(699699694) f=
rom Huawei is informed	","vanel.mbiada@matech-cameroun.com","143","20-04-20=
25 14:30:02","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004845772","AWA=
E OCM","","20-04-2025 13:09:39","20-04-2025 13:08:25","20-04-2025 13:18:39"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automaticaly","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup// Gen started automaticaly","cedric.tiani@matec=
h-cameroun.com","76","20-04-2025 13:09:39","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004845631","Nko=
abang2","","20-04-2025 12:48:19","20-04-2025 12:42:39","20-04-2025 12:59:39=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed// Grid return","Mba Lazare Herve","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen o=
verload (22KVA, 330A), SS Blaise IHS is informed// Grid return","cedric.tia=
ni@matech-cameroun.com","341","20-04-2025 12:48:19","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004845562","Eto=
ug ebe Carrefour","","20-04-2025 12:35:20","20-04-2025 12:30:02","20-04-202=
5 13:14:01","Grid fluctuation,site went down because Gen failed to start du=
e to Grid bad voltage//He bypassed the Grid and site on Gen","Hyemafo Gilda=
s","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation,site went down because Gen failed to start due to Grid b=
ad voltage//He bypassed the Grid and site on Gen","cedric.tiani@matech-came=
roun.com","318","20-04-2025 12:35:20","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004845539","N=
koabang Ebolmedjock","","20-04-2025 12:28:50","20-04-2025 12:22:30","20-04-=
2025 12:30:16","Active//No power issue, Site on Gen. The Tx FME Brice Tsagu=
e(650214096) from Huawei is informed. Notice that it is impacted by Nkolmes=
seng-Abom Not Manager By IHS","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","Active=
//No power issue, Site on Gen. The Tx FME Brice Tsague(650214096) from Huaw=
ei is informed. Notice that it is impacted by Nkolmesseng-Abom Not Manager =
By IHS","gerard.tchangoue@matech-cameroun.com","381","20-04-2025 12:28:50",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004845504","A=
ccacia New","","20-04-2025 12:23:27","20-04-2025 12:17:10","20-04-2025 13:2=
1:10","No power issue site on gen with U=3D54.5V Notice that site is down b=
ehind Nkolzie who is not our responsability","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
site on gen with U=3D54.5V Notice that site is down behind Nkolzie who is n=
ot our responsability","gerard.tchangoue@matech-cameroun.com","378","20-04-=
2025 12:23:27","MATECH CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0004845499","N=
kol-Mbanda","","20-04-2025 12:21:30","20-04-2025 12:17:16","20-04-2025 15:0=
7:01","Grid outage site site went because Gen failed to started due to PWC =
dysfunction // He reset  it and manually started the GEN","MINKA NICOLAS","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage site site went because Gen failed to started due to PWC dysfunction=
 // He reset  it and manually started the GEN","gerard.tchangoue@matech-cam=
eroun.com","256","20-04-2025 12:21:30","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004845382","Par=
adis Hotel","","20-04-2025 11:59:52","20-04-2025 11:57:37","20-04-2025 17:1=
9:20","Site went down due to  insufficient rectifiers on site //He added 02=
 rectifiers","Siligap Boris","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to  insufficient rectifiers on site //He =
added 02 rectifiers","cedric.tiani@matech-cameroun.com","136","20-04-2025 1=
1:59:52","MATECH CMR"
"Closed Complete","Site Down","T1486","IHS_YND_683","NOCINC0004845265","BON=
AS YDE","","20-04-2025 11:45:18","20-04-2025 11:40:59","20-04-2025 16:25:56=
","Francois NDUEGOU is on site  doing swapp of PWC ZTE //END OF WORK","Paul=
 BIBOUM","Installation Activity","Passive","Planned Activity","Installation=
 Activity","Francois NDUEGOU is on site  doing swapp of PWC ZTE //END OF WO=
RK","cedric.tiani@matech-cameroun.com","260","20-04-2025 11:45:18","MATECH =
CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0004844977","M=
adagascar-Yde-New","","20-04-2025 10:47:36","19-04-2025 15:33:19","21-04-20=
25 09:46:30","Access issue at Night ,Grid ooutage,no space to deploy MDG //=
  Grid return,","","Grid Supply","Passive","Grid","National Grid - Grid Out=
age Issue","Access issue at Night ,Grid ooutage,no space to deploy MDG //  =
Grid return,","cedric.tiani@matech-cameroun.com","69257","20-04-2025 10:47:=
36","MATECH CMR"
"Closed Complete","Site Down","CTR_115","IHS_YND_375","NOCINC0004844962","N=
goung","","20-04-2025 10:42:50","20-04-2025 08:48:21","20-04-2025 12:00:21"=
,"Grid outage,site went down because GEN started and stopped due to alarm h=
igh temp//He added water","Kemeni Franklin","Equipment Repair","Passive","A=
CDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage,site =
went down because GEN started and stopped due to alarm high temp//He added =
water","gerard.tchangoue@matech-cameroun.com","6870","20-04-2025 10:42:50",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004844841","Manguier=
","","20-04-2025 10:11:27","20-04-2025 10:07:14","20-04-2025 10:12:14","Cas=
caded Incident from TTO4951980","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue U=3D53,3V on Gri=
d The fme Tx Armand ngeutsa From huawei is informed","system","266352","20-=
04-2025 10:11:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004844840","Omnispor=
t-Rail","","20-04-2025 10:11:27","20-04-2025 10:07:14","20-04-2025 10:12:14=
","Cascaded Incident from TTO4951980","Delor Telezing","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue U=3D53,3V o=
n Grid The fme Tx Armand ngeutsa From huawei is informed","system","266352"=
,"20-04-2025 10:11:27","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004844812","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","20-04-2025 10:10:33","20-04-=
2025 10:07:14","20-04-2025 10:12:14","Active//No power issue U=3D53,3V on G=
rid The fme Tx Armand ngeutsa From huawei is informed","Fabrice Pouakam","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue U=3D53,3V on Grid The fme Tx Armand ngeuts=
a From huawei is informed","gerard.tchangoue@matech-cameroun.com","200","20=
-04-2025 10:10:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004844745","Bastos B=
ethesda","","20-04-2025 10:01:02","20-04-2025 09:51:31","20-04-2025 10:00:5=
4","Cascaded Incident from TTO4951939","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active// No power issue on site Ub=
aie=3D50.6V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is info=
rmed","system","267277","20-04-2025 10:01:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004844743","Golf Qua=
ter","","20-04-2025 10:01:02","20-04-2025 09:51:31","20-04-2025 10:00:54","=
Cascaded Incident from TTO4951939","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active// No power issue on site Ubaie=
=3D50.6V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informe=
d","system","267277","20-04-2025 10:01:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0004844744","Bastos-N=
ylon","","20-04-2025 10:01:02","20-04-2025 09:51:31","20-04-2025 10:00:54",=
"Cascaded Incident from TTO4951939","Mboua Thierry","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active// No power issue on site Ubaie=
=3D50.6V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informe=
d","system","267277","20-04-2025 10:01:02","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004844740","T=
singa","IHS_YND_220, IHS_YND_126, IHS_YND_563","20-04-2025 09:59:55","20-04=
-2025 09:51:31","20-04-2025 10:00:54","Active// No power issue on site Ubai=
e=3D50.6V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is inform=
ed","Mboua Thierry","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active// No power issue on site Ubaie=3D50.=
6V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informed","ge=
rard.tchangoue@matech-cameroun.com","506","20-04-2025 09:59:55","MATECH CMR=
"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004844552","Odz=
a II OCM","","20-04-2025 09:13:41","20-04-2025 09:09:33","20-04-2025 09:12:=
19","Grid outage gen failed to start due to card GE dysfunctionned //Grid r=
eturn","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid outage gen failed to start due to card GE dysfunctionned /=
/Grid return","cedric.tiani@matech-cameroun.com","249","20-04-2025 09:13:41=
","MATECH CMR"
"Closed Complete","Site Down","T1582","IHS_YND_138","NOCINC0004844382","Nko=
mkana 2","","20-04-2025 08:53:03","20-04-2025 08:47:28","20-04-2025 09:14:5=
6","Site went down due to insufficient rectifiers//Site stabilised","Mboua =
Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module","Site =
went down due to insufficient rectifiers//Site stabilised","cedric.tiani@ma=
tech-cameroun.com","336","20-04-2025 08:53:03","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004844361","B=
iteng-Maetur","","20-04-2025 08:49:00","20-04-2025 08:31:59","20-04-2025 09=
:41:59","Active//No power issue, U=3D52V on grid, Tx FME lionel steve adjep=
/655124876/ From huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue, U=3D52V on grid, Tx FME lionel steve adjep/655124876/ From=
 huawei is informed","gerard.tchangoue@matech-cameroun.com","1023","20-04-2=
025 08:49:00","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004844355","Bas=
tos-BAT","","20-04-2025 08:47:20","20-04-2025 08:43:09","20-04-2025 08:49:1=
1","Active// No power issue, site is on grid with Ubaie=3D54,9 V The Tx Fme=
, Eloundou(652586578) from Huawei is informed","Mboua Thierry","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power issue, site is on grid with Ubaie=3D54,9 V The Tx Fme, El=
oundou(652586578) from Huawei is informed","cedric.tiani@matech-cameroun.co=
m","252","20-04-2025 08:47:20","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004844230","Awa=
e Ewonkan","","20-04-2025 08:07:18","20-04-2025 08:02:49","20-04-2025 08:08=
:25","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IH=
S SS Alphonse is informed // Grid Restored","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due =
to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid Res=
tored","cedric.tiani@matech-cameroun.com","270","20-04-2025 08:07:18","MATE=
CH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004843932","Sof=
avinc","","20-04-2025 06:40:18","20-04-2025 06:33:59","20-04-2025 08:06:10"=
,"Grid outage, site went down because gen failed to start due to gen contac=
tor faulty // He bypassed gen contactor and gen manually started","MINKA NI=
COLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Gri=
d outage, site went down because gen failed to start due to gen contactor f=
aulty // He bypassed gen contactor and gen manually started","cedric.tiani@=
matech-cameroun.com","380","20-04-2025 06:40:18","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004843797","Aka=
k-Nkozoa-MTN-IHS","","20-04-2025 06:01:31","20-04-2025 05:55:59","20-04-202=
5 06:17:43","site went down due to PWC dysfunctionning, // He Reset it and =
site is on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","site went down due to PWC dysfunctionning, // He Reset=
 it and site is on Grid","gaelle.njiofack@matech-cameroun.com","574","20-04=
-2025 06:01:31","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004843303","NKO=
MEKUI OCM","","20-04-2025 03:24:26","20-04-2025 02:46:46","20-04-2025 04:24=
:44","Site impacted by Mbankolo Camtel","TIENTCHEU NZETCHIEU GAEL","Custome=
r Equipment Failure","Active","Active Equipment Failure","Affected by 3rd P=
arty Site","Site impacted by Mbankolo Camtel","gaelle.njiofack@matech-camer=
oun.com","2262","20-04-2025 03:24:26","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004843256","Odz=
a petit marche new","","20-04-2025 02:50:57","20-04-2025 02:47:08","20-04-2=
025 07:55:39","Grid outage. Site went down due to rectifier dysfunctionning=
//We reset rectifier and site on GEN","Albran Byorel","Equipment Repair","P=
assive","Rectifier","Rectifier Module","Grid outage. Site went down due to =
rectifier dysfunctionning//We reset rectifier and site on GEN","gaelle.njio=
fack@matech-cameroun.com","230","20-04-2025 02:50:57","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004843126","Mok=
olo Yaounde","","20-04-2025 01:41:42","20-04-2025 01:32:22","20-04-2025 01:=
43:50","Grid outage, no space to deploy a mobile gen // grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e, no space to deploy a mobile gen // grid return","loic.noumsi@matech-came=
roun.com","561","20-04-2025 01:41:42","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004843125","Nko=
abang Alembe","","20-04-2025 01:41:37","20-04-2025 00:53:15","20-04-2025 02=
:03:00","Grid fluctuation,site went down due to 3 rectifiers dysfunction on=
 site //H reset it","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Grid fluctuation,site went down due to 3 rectifier=
s dysfunction on site //H reset it","gaelle.njiofack@matech-cameroun.com","=
2903","20-04-2025 01:41:37","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004843108","Bas=
tos-BAT","","20-04-2025 01:39:26","20-04-2025 01:30:11","20-04-2025 01:46:5=
9","	Grid outage , site went down before Gen started due to poor battery ba=
ckup// Grid Power return","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","	Grid outage , site went down be=
fore Gen started due to poor battery backup// Grid Power return","loic.noum=
si@matech-cameroun.com","555","20-04-2025 01:39:26","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004843099","Ako=
no","IHS_YND_687","20-04-2025 01:37:23","20-04-2025 01:28:12","20-04-2025 0=
1:46:09","	Grid outage, Site went down due to Dysfunctioning of Gen (Old Ge=
n) // Gen start manually. (need to replace Gen)","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - Generator Faulty","	Grid outage, Site w=
ent down due to Dysfunctioning of Gen (Old Gen) // Gen start manually. (nee=
d to replace Gen)","loic.noumsi@matech-cameroun.com","552","20-04-2025 01:3=
7:23","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004843095","Beh=
ind P T school Yde","","20-04-2025 01:34:53","20-04-2025 01:24:44","20-04-2=
025 06:23:39","SITE DOWN due to rectifier issue and MPR faulty (Supervisor =
IHS Francois is informed) // Paul reseted Rectifier","Paul BIBOUM","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","SITE DOWN due to recti=
fier issue and MPR faulty (Supervisor IHS Francois is informed) // Paul res=
eted Rectifier","loic.noumsi@matech-cameroun.com","610","20-04-2025 01:34:5=
3","MATECH CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0004843078","Men=
dong Maeture","","20-04-2025 01:26:32","20-04-2025 00:18:45","20-04-2025 03=
:59:14","Site went down due to Disjunction of CB (100A) of MTN in the Energ=
ie bay // CB rearm (Need to replace this CB wiht 125A of CB)","Hyemafo Gild=
as","Equipment Repair","Passive","Rectifier","Rectifier - Circuit Breaker",=
"Site went down due to Disjunction of CB (100A) of MTN in the Energie bay /=
/ CB rearm (Need to replace this CB wiht 125A of CB)","gaelle.njiofack@mate=
ch-cameroun.com","4068","20-04-2025 01:26:32","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004843019","M=
ontee-Des-Soeurs","","20-04-2025 00:55:08","19-04-2025 21:59:50","20-04-202=
5 09:32:23","ACCESS ISSUES during the night due to landlord Site went down =
due to CB(63A) in pwc that tripped OCM//He rearmed it (replacement needed)"=
,"Hyemafo Gildas","Access Denial","Lease Or Legal","Landlord Related Issues=
","Access Issue - Land Lord","ACCESS ISSUES during the night due to landlor=
d Site went down due to CB(63A) in pwc that tripped OCM//He rearmed it (rep=
lacement needed)","gaelle.njiofack@matech-cameroun.com","10519","20-04-2025=
 00:55:08","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004842900","M=
ontee-Des-Soeurs","","20-04-2025 00:30:00","19-04-2025 19:38:33","19-04-202=
5 21:57:54","Grid outage, site went down due to Gen overloard // Grid retur=
n","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Grid outage, site went down due to Gen overloard // Grid return","gaell=
e.njiofack@matech-cameroun.com","17489","20-04-2025 00:30:00","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004842872","M=
EHANDAN","","20-04-2025 00:15:27","20-04-2025 00:07:12","20-04-2025 00:15:5=
1","Site went down due to insufficient rectifiers on site//site stabilised"=
,"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient rectifiers on site//site stabilised",=
"vanel.mbiada@matech-cameroun.com","497","20-04-2025 00:15:27","MATECH CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0004842844","N=
koabang","","20-04-2025 00:03:06","19-04-2025 23:46:53","20-04-2025 01:21:1=
4","Site went down because 03/04 rectifiers dysfunctionned // He resetd rec=
tifiers,site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Site went down because 03/04 rectifiers dysfunct=
ionned // He resetd rectifiers,site on Grid","vanel.mbiada@matech-cameroun.=
com","974","20-04-2025 00:03:06","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004842832","SIM=
BOCK BONAMBAPE","","19-04-2025 23:56:29","19-04-2025 23:45:53","20-04-2025 =
00:07:03","	Grid outage, Site went down before Gen start due to poor backup=
 // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","	Grid outage, Site went down before Gen =
start due to poor backup // Grid return","gaelle.njiofack@matech-cameroun.c=
om","638","19-04-2025 23:56:29","MATECH CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0004842777","NYA=
NON/DEMBO","","19-04-2025 23:43:27","19-04-2025 21:32:49","20-04-2025 05:20=
:54","Grid outage, Gen stopped due to power supply fuse of the card cut bec=
ause of The Lightning // Fuse bridged and starting the Gen ","TIENTCHEU NZE=
TCHIEU GAEL","Force Majeure","Natural Disaster","Thunderstrike","Equipment =
Damaged","Grid outage, Gen stopped due to power supply fuse of the card cut=
 because of The Lightning // Fuse bridged and starting the Gen ","gaelle.nj=
iofack@matech-cameroun.com","7839","19-04-2025 23:43:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004842682","Bastos B=
ethesda","","19-04-2025 23:16:30","19-04-2025 23:08:03","20-04-2025 00:42:2=
9","Cascaded Incident from TTO4949645 - Cascade Removed From TTO4949645","M=
boua Thierry","Cascade Outage","Active","Cascade Active","Cascade Active","=
Active// No power issue on site Ubaie=3D54,5V site on Grid The Tx Eloundou =
Bertrand /693212405/Huawei is informed","system","298350","19-04-2025 23:16=
:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004842683","Tsinga",=
"IHS_YND_220, IHS_YND_126, IHS_YND_563","19-04-2025 23:16:30","19-04-2025 2=
3:08:03","20-04-2025 00:42:29","Active// No power issue on site Ubaie=3D54,=
5V site on Grid The Tx Eloundou Bertrand /693212405/Huawei is informed","Mb=
oua Thierry","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active// No power issue on site Ubaie=3D54,5V site=
 on Grid The Tx Eloundou Bertrand /693212405/Huawei is informed","system","=
507","19-04-2025 23:16:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004842681","Golf Qua=
ter","","19-04-2025 23:16:30","19-04-2025 23:08:03","20-04-2025 00:42:29","=
Cascaded Incident from TTO4949645 - Cascade Removed From TTO4949645","Mboua=
 Thierry","Cascade Outage","Active","Cascade Active","Cascade Active","Acti=
ve// No power issue on site Ubaie=3D54,5V site on Grid The Tx Eloundou Bert=
rand /693212405/Huawei is informed","system","298351","19-04-2025 23:16:30"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004842672","B=
astos-Nylon","","19-04-2025 23:15:29","19-04-2025 23:08:03","20-04-2025 00:=
42:29","site down because impacted by Camp SIC TSINGA","Mboua Thierry","Cas=
cade Outage","Active","Cascade Active","Cascade Active","Active// No power =
issue on site Ubaie=3D54,5V site on Grid The Tx Eloundou Bertrand /69321240=
5/Huawei is informed","vanel.mbiada@matech-cameroun.com","298350","19-04-20=
25 23:15:29","MATECH CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004842667","C=
RF Nkoabang","","19-04-2025 23:12:42","19-04-2025 23:10:31","20-04-2025 01:=
21:31","Grid outage No space to deploy // Grid power return","Mba Lazare He=
rve","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage No space to deploy // Grid power return","vanel.mbiada@matech-cam=
eroun.com","132","19-04-2025 23:12:42","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004842526","B=
arriere","","19-04-2025 22:46:26","19-04-2025 21:02:15","20-04-2025 19:40:4=
9","Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed//He reduced the load and site on GEN","=
Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Felix =
Zambe is informed and confirmed//He reduced the load and site on GEN","vane=
l.mbiada@matech-cameroun.com","6252","19-04-2025 22:46:26","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004842265","A=
WAE OCM","","19-04-2025 21:51:01","19-04-2025 21:50:50","19-04-2025 22:52:3=
1","Grid outage,Site went down due to ZTE PWC malfuntioning// He reset the =
PWC and  site on Grid .","Mba Lazare Herve","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup // Grid restoration","vanel.mbiada@matech=
-cameroun.com","13","19-04-2025 21:51:01","MATECH CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0004842260","M=
endong Maeture","","19-04-2025 21:49:57","19-04-2025 21:45:47","19-04-2025 =
23:06:49","site went down because gen failed to start due to grid bad volta=
ge // He bypassed the Grid and site on Gen","Hyemafo Gildas","Grid Supply",=
"Passive","Grid","National Grid - Unstable Grid Supply Issue","site went do=
wn because gen failed to start due to grid bad voltage // He bypassed the G=
rid and site on Gen","vanel.mbiada@matech-cameroun.com","250","19-04-2025 2=
1:49:57","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004842257","A=
wae Ewonkan","","19-04-2025 21:48:58","19-04-2025 21:45:44","20-04-2025 05:=
52:48","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // He reduced the load and site on Gen","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage site went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse=
 is informed // He reduced the load and site on Gen","vanel.mbiada@matech-c=
ameroun.com","195","19-04-2025 21:48:58","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004842226","Nko=
l-Mbanda","","19-04-2025 21:43:31","19-04-2025 21:37:16","19-04-2025 21:49:=
22","Site went down due to malfunction of Bay // Bay reset","MINKA NICOLAS"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Si=
te went down due to malfunction of Bay // Bay reset","vanel.mbiada@matech-c=
ameroun.com","376","19-04-2025 21:43:31","MATECH CMR"
"Closed Complete","Site Down","T0535","IHS_YND_234","NOCINC0004842224","Oyo=
mabang MTN","","19-04-2025 21:42:17","19-04-2025 21:20:50","20-04-2025 00:3=
0:38","Site went down due to Bad Grid voltage // Grid stopped manually and =
site on Gen (we need RCP in this site)","TIENTCHEU NZETCHIEU GAEL","Grid Su=
pply","Passive","Grid","National Grid - Grid Incomplete Phase","Site went d=
own due to Bad Grid voltage // Grid stopped manually and site on Gen (we ne=
ed RCP in this site)","vanel.mbiada@matech-cameroun.com","1287","19-04-2025=
 21:42:17","MATECH CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0004842107","B=
astos Bethesda","","19-04-2025 21:28:06","19-04-2025 19:01:13","19-04-2025 =
19:37:16","Site impacted by BASTOS NYLON","Mboua Thierry","Cascade Outage",=
"Active","Cascade Active","Cascade Active","Active: No power issue, site is=
 on Grid with Ubaie=3D53.3V.  The Tx FME   Eloundou(652586578) from huawei =
is informed.","vanel.mbiada@matech-cameroun.com","277328","19-04-2025 21:28=
:06","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004841946","O=
LAMA","","19-04-2025 20:59:43","19-04-2025 20:16:15","20-04-2025 01:46:09",=
"Active: No power issue, site is on grid with Ubaie=3D54.9V (hybrid site). =
 The Tx FME Henri (699949693)from Huawei is informed.","Fanda Brice","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active: No power issue, site is on grid with Ubaie=3D54.9V (hybrid si=
te).

The Tx FME Henri (699949693)from Huawei is informed.
","vanel.mbiada@matech-cameroun.com","2609","19-04-2025 20:59:43","MATECH C=
MR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004841917","N=
KOLMEKONG YDE","","19-04-2025 20:53:36","19-04-2025 20:49:23","20-04-2025 0=
1:00:10","No Power issue on site Ubaie 54V site on Grid, TX FME Synphorien =
(650257151) from Huawei is informed","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No Power=
 issue on site Ubaie 54V site on Grid, TX FME Synphorien (650257151) from H=
uawei is informed","vanel.mbiada@matech-cameroun.com","254","19-04-2025 20:=
53:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004841916","Saa","",=
"19-04-2025 20:53:23","19-04-2025 20:43:07","19-04-2025 21:23:34","Cascaded=
 Incident from TTO4948754","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down because gen failled to start=
 due to relay contactor faulty // He bypassed and manually stated gen","sys=
tem","263956","19-04-2025 20:53:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004841913","Carrefou=
r Ayissi Ele","","19-04-2025 20:53:22","19-04-2025 20:43:07","19-04-2025 21=
:23:34","Cascaded Incident from TTO4948754","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","site went down because gen=
 failled to start due to relay contactor faulty // He bypassed and manually=
 stated gen","system","263955","19-04-2025 20:53:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0004841915","Nkol-Meb=
anga","","19-04-2025 20:53:22","19-04-2025 20:43:07","19-04-2025 21:23:34",=
"Cascaded Incident from TTO4948754","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because gen failled=
 to start due to relay contactor faulty // He bypassed and manually stated =
gen","system","263955","19-04-2025 20:53:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004841914","SAA Entr=
ance","","19-04-2025 20:53:22","19-04-2025 20:43:07","19-04-2025 21:23:34",=
"Cascaded Incident from TTO4948754","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because gen failled=
 to start due to relay contactor faulty // He bypassed and manually stated =
gen","system","263956","19-04-2025 20:53:22","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004841907","SAA=
 2","IHS_YND_810, IHS_YND_542, IHS_YND_809, IHS_YND_405","19-04-2025 20:52:=
22","19-04-2025 20:43:07","19-04-2025 21:27:33","site went down because gen=
 failled to start due to relay contactor faulty // He bypassed and manually=
 stated gen","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG =
- Load Contactor","site went down because gen failled to start due to relay=
 contactor faulty // He bypassed and manually stated gen","gerard.tchangoue=
@matech-cameroun.com","556","19-04-2025 20:52:22","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004841723","Eto=
ug ebe Carrefour","","19-04-2025 20:19:29","19-04-2025 20:11:59","19-04-202=
5 22:04:10","	Grid fluctuation,site went down because Gen failed to start d=
ue to Grid bad voltage//He bypassed the Grid and site on Gen","Hyemafo Gild=
as","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply Is=
sue","	Grid fluctuation,site went down because Gen failed to start due to G=
rid bad voltage//He bypassed the Grid and site on Gen","gerard.tchangoue@ma=
tech-cameroun.com","451","19-04-2025 20:19:29","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004841695","Tam=
tam Weekend","","19-04-2025 20:05:55","19-04-2025 19:54:59","19-04-2025 22:=
33:20","	Site went down due to work of Nomade team ( 6 58 84 92 59 ) is on =
site for swap bay // END OF WORK	","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Site went d=
own due to work of Nomade team ( 6 58 84 92 59 ) is on site for swap bay //=
 END OF WORK	","gerard.tchangoue@matech-cameroun.com","657","19-04-2025 20:=
05:55","MATECH CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0004841672","N=
gousso-II","","19-04-2025 19:59:36","19-04-2025 19:03:12","19-04-2025 20:52=
:23","Site went down because Gen failed to start due to PWC malfunctioning =
// He reset PWC, Site on Grid","MFOUAGUEGUE MATHIEU","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Cabinet","Site went down because Gen failed t=
o start due to PWC malfunctioning // He reset PWC, Site on Grid","vanel.mbi=
ada@matech-cameroun.com","3385","19-04-2025 19:59:36","MATECH CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0004841579","A=
cropole","","19-04-2025 19:45:58","19-04-2025 19:41:47","19-04-2025 20:35:4=
7","site went down because gen failled to start due to leak of phases grid =
caused by CB grid faulty ( No RCP on site ) // He bypassed Grid and started=
 gen mannually ","MINKA NICOLAS","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","site went down because gen failled to start=
 due to leak of phases grid caused by CB grid faulty ( No RCP on site ) // =
He bypassed Grid and started gen mannually ","vanel.mbiada@matech-cameroun.=
com","252","19-04-2025 19:45:58","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004841556","Acc=
acia New","","19-04-2025 19:41:59","19-04-2025 18:49:59","20-04-2025 07:49:=
18","Grid outage.no space to deploy mobile gen //Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no sp=
ace to deploy mobile gen //Grid return","gerard.tchangoue@matech-cameroun.c=
om","3122","19-04-2025 19:41:59","MATECH CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0004841524","G=
olf Quater","","19-04-2025 19:36:05","19-04-2025 19:01:13","19-04-2025 19:3=
7:16","Site impacted by BASTOS NYLON","Mboua Thierry","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","Active: No power issue, site is on =
Grid with Ubaie=3D53.3V.  The Tx FME   Eloundou(652586578) from huawei is i=
nformed.","vanel.mbiada@matech-cameroun.com","277328","19-04-2025 19:36:05"=
,"MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004841368","MEH=
ANDAN","","19-04-2025 19:13:30","19-04-2025 19:08:22","19-04-2025 19:48:22"=
,"Grid fluctuation, site went down because Gen failed to start due to grid =
bad voltage No Rcp // Grid stabilized","Albran Byorel","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, sit=
e went down because Gen failed to start due to grid bad voltage No Rcp // G=
rid stabilized","gerard.tchangoue@matech-cameroun.com","309","19-04-2025 19=
:13:30","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0004841350","N=
komkana","","19-04-2025 19:09:01","19-04-2025 19:04:42","19-04-2025 19:26:4=
2","Grid outage,No space to deploy a mobile gen // Grid restored","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,N=
o space to deploy a mobile gen // Grid restored","vanel.mbiada@matech-camer=
oun.com","260","19-04-2025 19:09:01","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004841319","T=
singa","","19-04-2025 19:04:38","19-04-2025 19:01:13","19-04-2025 19:37:16"=
,"Site impacted by BASTOS NYLON","Mboua Thierry","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active: No power issue, site is on Grid =
with Ubaie=3D53.3V.  The Tx FME   Eloundou(652586578) from huawei is inform=
ed.","vanel.mbiada@matech-cameroun.com","277329","19-04-2025 19:04:38","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004841304","B=
astos-Nylon","IHS_YND_220, IHS_YND_563, IHS_YND_127","19-04-2025 19:03:42",=
"19-04-2025 19:01:13","19-04-2025 19:37:16","Active: No power issue, site i=
s on Grid with Ubaie=3D53.3V.  The Tx FME   Eloundou(652586578) from huawei=
 is informed.","Mboua Thierry","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active: No power issue, site is =
on Grid with Ubaie=3D53.3V.  The Tx FME   Eloundou(652586578) from huawei i=
s informed.","vanel.mbiada@matech-cameroun.com","150","19-04-2025 19:03:42"=
,"MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0004841298","Clu=
b France","","19-04-2025 19:03:02","19-04-2025 18:50:59","19-04-2025 19:26:=
10","Grid outage,no space to deploy a mobile DG // grid restored","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,n=
o space to deploy a mobile DG // grid restored","gerard.tchangoue@matech-ca=
meroun.com","724","19-04-2025 19:03:02","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004841296","Fla=
menco","","19-04-2025 19:02:22","19-04-2025 18:49:59","19-04-2025 19:30:59"=
,"Grid outage, site went down because gen failed to start due to gen card f=
aulty // started Gen manualy","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen =
failed to start due to gen card faulty // started Gen manualy","gerard.tcha=
ngoue@matech-cameroun.com","744","19-04-2025 19:02:22","MATECH CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0004841219","Biy=
emassi LAC","","19-04-2025 18:34:33","19-04-2025 18:24:59","19-04-2025 19:2=
8:59","Grid outage No space to deployed a mobile Gen // Grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage No space to deployed a mobile Gen // Grid power return","gerard.tch=
angoue@matech-cameroun.com","575","19-04-2025 18:34:33","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004841218","D=
amas","","19-04-2025 18:34:20","19-04-2025 18:19:08","19-04-2025 19:04:58",=
"Active//No power issue on site ,site on Grid with Ubaie=3D54.3 V he FME Th=
e TX FME Mbah Hosiah (674007438) is informed","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site ,site on Grid with Ubaie=3D54.3 V he FME The =
TX FME Mbah Hosiah (674007438) is informed","vanel.mbiada@matech-cameroun.c=
om","912","19-04-2025 18:34:20","MATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004841211","BIY=
EMASSI NIKI","","19-04-2025 18:33:16","19-04-2025 18:23:59","19-04-2025 19:=
26:59","Grid outage,Site went down because Gen failed to start due to Grid =
contactor malfunctionning  // He bypassed it site on Gen","Hyemafo Gildas",=
"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,S=
ite went down because Gen failed to start due to Grid contactor malfunction=
ning  // He bypassed it site on Gen","gerard.tchangoue@matech-cameroun.com"=
,"558","19-04-2025 18:33:16","MATECH CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0004841210","M=
endong Maeture","","19-04-2025 18:33:12","19-04-2025 18:20:56","19-04-2025 =
20:59:26","Grid outage, site went down because gen start and stopped due to=
 high temp caused by pierced radator // He added water and manually start t=
he gen(Radiator to be repaired)","Hyemafo Gildas","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Radiator","Grid outage, site went down because gen s=
tart and stopped due to high temp caused by by pierced radator // He added =
water and manually start the gen(Radiator to be repaired)","vanel.mbiada@ma=
tech-cameroun.com","737","19-04-2025 18:33:12","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004841205","Ako=
k Ndoe Yde","","19-04-2025 18:32:24","19-04-2025 18:22:59","19-04-2025 19:2=
7:59","Grid outage site went down before Gen stated due to poor battery bac=
kyup // Gen started mannuelly","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 before Gen stated due to poor battery backyup // Gen started mannuelly","g=
erard.tchangoue@matech-cameroun.com","566","19-04-2025 18:32:24","MATECH CM=
R"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004841204","S=
calom","","19-04-2025 18:32:19","19-04-2025 18:23:10","19-04-2025 20:19:04"=
,"Grid outage, Site went down due to disfonctinnement of Auto mode (bad con=
figuration on ATS) // Gen start manually and more investigation on going","=
Paul BIBOUM","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","=
Grid outage, Site went down due to disfonctinnement of Auto mode (bad confi=
guration on ATS) // Gen start manually and more investigation on going

","vanel.mbiada@matech-cameroun.com","550","19-04-2025 18:32:19","MATECH CM=
R"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004841198","BAT=
A Mokolo OCM","","19-04-2025 18:30:55","19-04-2025 18:21:59","19-04-2025 19=
:27:59","Grid outage No space to deploy // Grid power return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No sp=
ace to deploy // Grid power return","gerard.tchangoue@matech-cameroun.com",=
"537","19-04-2025 18:30:55","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004841190","NKO=
MKANA ELIZA HOTEL","","19-04-2025 18:30:01","19-04-2025 18:21:59","19-04-20=
25 19:27:51","Grid outage,no space to deploy a mobile DG,// grid restored",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage,no space to deploy a mobile DG,// grid restored","gerard.tchangoue@=
matech-cameroun.com","484","19-04-2025 18:30:01","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004841158","Bas=
tos-BAT","","19-04-2025 18:24:36","19-04-2025 18:19:22","19-04-2025 18:25:2=
2","Grid outage , site went down before Gen started due to poor battery bac=
kup// Grid Power return","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage , site went down befo=
re Gen started due to poor battery backup// Grid Power return","gerard.tcha=
ngoue@matech-cameroun.com","315","19-04-2025 18:24:36","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004841072","M=
ontee-Jouvence-II","","19-04-2025 18:07:38","19-04-2025 18:01:18","19-04-20=
25 18:07:18","Grid fluctuation, site went down because Gen failed to start =
due to Grid bad voltage and no RCP on site //Site stabilized","Hyemafo Gild=
as","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because Gen failed to start due to Grid=
 bad voltage and no RCP on site //Site stabilized","vanel.mbiada@matech-cam=
eroun.com","382","19-04-2025 18:07:38","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004841067","S=
IMBOCK BONAMBAPE","","19-04-2025 18:06:22","19-04-2025 18:02:07","19-04-202=
5 18:05:44","Grid outage, Site went down before Gen start due to poor backu=
p/ // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Grid return","vanel.mbiada@matech-cameroun.co=
m","256","19-04-2025 18:06:22","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0004841019","Ebe=
ba","","19-04-2025 17:57:05","19-04-2025 17:50:49","19-04-2025 19:47:52","G=
rid outage,gen stopped with alarm high temp//he added water in radiator","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid o=
utage,gen stopped with alarm high temp//he added water in radiator","gerard=
.tchangoue@matech-cameroun.com","377","19-04-2025 17:57:05","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004841018","M=
ontee-Des-Soeurs","","19-04-2025 17:57:03","19-04-2025 17:51:52","19-04-202=
5 17:57:52","Grid outage, site went down due to Gen overloard // Reduced lo=
ad and site on Gen","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid outage, site went down due to Gen overloard // Re=
duced load and site on Gen","vanel.mbiada@matech-cameroun.com","312","19-04=
-2025 17:57:03","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004840799","A=
kak-Nkozoa-MTN-IHS","","19-04-2025 17:14:58","19-04-2025 17:14:49","19-04-2=
025 17:40:49","Site went down because  ZTE PWC malfunction (it does not sen=
d the boot order) // eneo return, site on eneo","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","ATS-AMF Issue","Site went down because=
  ZTE PWC malfunction (it does not send the boot order) // eneo return, sit=
e on eneo","vanel.mbiada@matech-cameroun.com","11","19-04-2025 17:14:58","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0004840788","S=
ofavinc","","19-04-2025 17:12:37","19-04-2025 17:11:22","19-04-2025 18:05:2=
2","Grid outage, site went down because gen failed to start due to gen cont=
actor faulty // He bypassed gen contactor and gen manually started","MINKA =
NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","G=
rid outage, site went down because gen failed to start due to gen contactor=
 faulty // He bypassed gen contactor and gen manually started","vanel.mbiad=
a@matech-cameroun.com","76","19-04-2025 17:12:37","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004840769","E=
mana lycee 2","","19-04-2025 17:07:41","19-04-2025 16:45:15","19-04-2025 17=
:13:26","Grid outage,gen stopped with alarm high temp//he added water in ra=
diator","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","Gen Temp=
 High","Grid outage,gen stopped with alarm high temp//he added water in rad=
iator","vanel.mbiada@matech-cameroun.com","1347","19-04-2025 17:07:41","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004840762","B=
iteng-Maetur","","19-04-2025 17:06:23","19-04-2025 16:56:06","19-04-2025 22=
:52:35","Fme Herve is informed and reported TX issue, the FME TX Lionnel (6=
55184876 / HUAWEI) is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Fme Herve is=
 informed and reported TX issue, the FME TX Lionnel (655184876 / HUAWEI) is=
 informed","vanel.mbiada@matech-cameroun.com","619","19-04-2025 17:06:23","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004840425","OTELE MT=
N","","19-04-2025 15:58:23","19-04-2025 15:52:38","19-04-2025 15:58:31","Ca=
scaded Incident from TTO4946953","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue site on Grid with U=
=3D53,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impac=
ted by Ngoumou(T0169) not manage by IHS","system","267075","19-04-2025 15:5=
8:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004840424","OLAMA","=
","19-04-2025 15:58:23","19-04-2025 15:52:38","19-04-2025 15:58:31","Cascad=
ed Incident from TTO4946953","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) not manage by IHS","system","267075","19-04-2025 15:58:23=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004840426","Akono","=
","19-04-2025 15:58:23","19-04-2025 15:52:38","19-04-2025 15:58:31","Cascad=
ed Incident from TTO4946953","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) not manage by IHS","system","267075","19-04-2025 15:58:23=
","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004840406","Mom=
","IHS_YND_687, IHS_YND_531, IHS_YND_365","19-04-2025 15:55:47","19-04-2025=
 15:52:38","19-04-2025 15:58:31","Active//No power issue site on Grid with =
U=3D53,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impa=
cted by Ngoumou(T0169) not manage by IHS","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","Affected by 3rd Party Site",=
"Active//No power issue site on Grid with U=3D53,3 V The FME TX Etienne(695=
033981) From Huawei is informed. Site impacted by Ngoumou(T0169) not manage=
 by IHS","gerard.tchangoue@matech-cameroun.com","191","19-04-2025 15:55:47"=
,"MATECH CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0004840296","Ngo=
uetou","","19-04-2025 15:36:41","19-04-2025 15:12:59","19-04-2025 17:46:59"=
,"Site down because DG did not start due to his card has planted caused by =
Eneo fluctuation // Card reseted and manual start of DG","Parker Tchoup","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Site down bec=
ause DG did not start due to his card has planted caused by Eneo fluctuatio=
n // Card reseted and manual start of DG","gerard.tchangoue@matech-cameroun=
.com","1423","19-04-2025 15:36:41","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0004840291","Eto=
ug-Ebe 2","","19-04-2025 15:35:33","19-04-2025 15:26:59","19-04-2025 17:11:=
59","Grid outage no space to deploy a mobil gen// grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no s=
pace to deploy a mobil gen// grid return","gerard.tchangoue@matech-cameroun=
.com","515","19-04-2025 15:35:33","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004840249","Mes=
sassi 2","","19-04-2025 15:23:35","19-04-2025 15:19:26","19-04-2025 18:23:0=
5","fme report that rectifier Issue // RECTIFIER reseted","Fabrice Pouakam"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module","fme report th=
at rectifier Issue // RECTIFIER reseted","gerard.tchangoue@matech-cameroun.=
com","251","19-04-2025 15:23:35","MATECH CMR"
"Closed Complete","Warning","CTR_060","IHS_YND_348","NOCINC0004840246","Nke=
nglikok","","19-04-2025 15:22:56","","","site Alarming due to Grid Fluctuat=
ion // Grid Stabilized","Kemeni Franklin","Warning","Warning","POWER","Warn=
ing - National Grid - Grid Outage Issue","site Alarming due to Grid Fuctuet=
ion // Grid Stabilized","adonis.defokoua@ihstowers.com","431","19-04-2025 1=
5:22:56","MATECH CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0004840227","G=
olf Quater","","19-04-2025 15:20:39","19-04-2025 15:13:34","19-04-2025 15:3=
4:50","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Active// No power issue on site Ubaie: 53.3V site on gEn TX Fme =
Eloundou(652586578) from Huawei is informed","vanel.mbiada@matech-cameroun.=
com","269521","19-04-2025 15:20:39","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004840223","T=
singa","","19-04-2025 15:19:42","19-04-2025 15:13:34","19-04-2025 15:34:50"=
,"","Mboua Thierry","Cascade Outage","Active","Cascade Active","Cascade Act=
ive","Active// No power issue on site Ubaie: 53.3V site on gEn TX Fme Eloun=
dou(652586578) from Huawei is informed","vanel.mbiada@matech-cameroun.com",=
"269521","19-04-2025 15:19:42","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004840207","B=
astos-Nylon","IHS_YND_220, IHS_YND_127","19-04-2025 15:15:44","19-04-2025 1=
5:13:34","19-04-2025 15:34:50","Active// No power issue on site Ubaie: 53.3=
V site on gEn TX Fme Eloundou(652586578) from Huawei is informed","Mboua Th=
ierry","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active// No power issue on site Ubaie: 53.3V site on gEn=
 TX Fme Eloundou(652586578) from Huawei is informed","vanel.mbiada@matech-c=
ameroun.com","130","19-04-2025 15:15:44","MATECH CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0004840094","C=
NDH","","19-04-2025 14:58:14","19-04-2025 14:49:37","19-04-2025 15:08:26","=
Wrong ticket, Site not manage by IHS ","Paul BIBOUM","Incorrectly Logged Ti=
ckets","Error","Error","Error","Wrong ticket, Site not manage by IHS ","van=
el.mbiada@matech-cameroun.com","518","19-04-2025 14:58:14","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004840053","N=
kolda","","19-04-2025 14:50:44","19-04-2025 14:49:31","19-04-2025 20:43:37"=
,"Site very unstable FME report that Site went down due to (2/5)Rectifier d=
ysfunctionning because The Load Increase // he replaced Rectifiers","Albran=
 Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Site very unstable FME report that Site went down due to (2/5)Rectifi=
er dysfunctionning because The Load Increase // he replaced Rectifiers","va=
nel.mbiada@matech-cameroun.com","74","19-04-2025 14:50:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004839992","Eto koss=
 Yde","","19-04-2025 14:41:20","19-04-2025 14:36:28","19-04-2025 14:40:28",=
"Cascaded Incident from TTO4946455","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup// Grid power return","system","332","19-04-2025=
 14:41:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004839993","ELOUMDEM=
 CARRIERE 2","","19-04-2025 14:41:20","19-04-2025 14:36:28","19-04-2025 14:=
40:28","Cascaded Incident from TTO4946455","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup// Grid power return","system","333","19-=
04-2025 14:41:20","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004839975","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","19-04-2025 14:36:38","19-04-2025 14:=
34:28","19-04-2025 14:40:28","Grid outage, Site went down before Gen start =
due to poor backup// Grid power return","Fanda Brice","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site we=
nt down before Gen start due to poor backup// Grid power return","vanel.mbi=
ada@matech-cameroun.com","132","19-04-2025 14:36:38","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004839972","ELO=
UMDEM CARRIERE","","19-04-2025 14:35:14","19-04-2025 14:33:02","19-04-2025 =
14:35:02","Grid outage,site went down because gen failed to start //grid re=
turn(investigation ongoing)","Fanda Brice","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage,site went down because gen fail=
ed to start //grid return(investigation ongoing)","gerard.tchangoue@matech-=
cameroun.com","134","19-04-2025 14:35:14","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004839963","B=
arriere IHS","","19-04-2025 14:33:14","19-04-2025 14:27:59","19-04-2025 14:=
33:36","Active//No power issue U=3D 53.6V Site on Grid The TX FME Rm Alain =
/691144423 from huawei is informed","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue U=3D 53.6V Site on Grid The TX FME Rm Alain /691144423 from hu=
awei is informed","vanel.mbiada@matech-cameroun.com","316","19-04-2025 14:3=
3:14","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004839962","Mok=
olo Yaounde","","19-04-2025 14:33:07","19-04-2025 14:31:57","19-04-2025 17:=
06:57","Site went down due to insufficient rectifiers Faulty on site//Site =
stabilised","","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to insufficient rectifiers Faulty on site//Site stabili=
sed","gerard.tchangoue@matech-cameroun.com","71","19-04-2025 14:33:07","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004839961","E=
lig-Edzoa","","19-04-2025 14:32:24","19-04-2025 14:27:16","19-04-2025 17:15=
:16","Grid Outage, No space to deploy // Grid restored","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid Outage, No space t=
o deploy // Grid restored","vanel.mbiada@matech-cameroun.com","310","19-04-=
2025 14:32:24","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004839950","SIM=
BOCK BONAMBAPE","","19-04-2025 14:31:03","19-04-2025 14:07:59","19-04-2025 =
17:42:21","ACTIVE No power issue U=3D 54,4 V Site on Grid TXFme lionel /694=
693436 from huawei is informed","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No powe=
r issue U=3D 54,4 V Site on Grid TXFme lionel /694693436 from huawei is inf=
ormed","gerard.tchangoue@matech-cameroun.com","1385","19-04-2025 14:31:03",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0004839904","O=
kolo","","19-04-2025 14:20:23","19-04-2025 14:10:12","19-04-2025 15:49:58",=
"ACTIVE// No power issue site Ubaie=3D52.5V site on Grid, The tx Fme Sympho=
rien(650257151)from Huawei is informed.","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTI=
VE// No power issue site Ubaie=3D52.5V site on Grid, The tx Fme Symphorien(=
650257151)from Huawei is informed.","edwige.kapawo@matech-cameroun.com","61=
2","19-04-2025 14:20:23","MATECH CMR"
"Closed Complete","Site Down","T1622","IHS_YND_186","NOCINC0004839860","Ngo=
usso Carrefour","","19-04-2025 14:11:30","19-04-2025 14:09:22","19-04-2025 =
16:54:22","Eneo outage, site Down due to Gen Overload  //  Eneo return","Si=
ligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Ene=
o outage, site Down due to Gen Overload  //  Eneo return","cedric.tiani@mat=
ech-cameroun.com","129","19-04-2025 14:11:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004839821","Omnispor=
t-Rail","","19-04-2025 14:04:13","19-04-2025 13:59:59","19-04-2025 18:06:12=
","Cascaded Incident from TTO4946237","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down due=
 to gen Overload(20KVA,270) // grid return","system","288123","19-04-2025 1=
4:04:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004839822","Manguier=
","","19-04-2025 14:04:13","19-04-2025 13:59:59","19-04-2025 18:06:12","Cas=
caded Incident from TTO4946237","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, site went down due to g=
en Overload(20KVA,270) // grid return","system","288123","19-04-2025 14:04:=
13","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004839804","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","19-04-2025 14:00:44","19-04-=
2025 13:59:59","19-04-2025 18:06:12","grid outage, site went down due to ge=
n Overload(20KVA,270) // grid return","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","grid outage, site went down due to =
gen Overload(20KVA,270) // grid return","edwige.kapawo@matech-cameroun.com"=
,"46","19-04-2025 14:00:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0004839719","Montee-J=
ouvence-II","","19-04-2025 13:45:39","19-04-2025 12:33:45","19-04-2025 17:0=
0:27","Cascaded Incident from TTO4945829","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to work =
of Nomade team ( 6 58 84 92 59 ) is on site for swap bay // END OF WORK","s=
ystem","4314","19-04-2025 13:45:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004839671","Nsimalen=
 OCM","","19-04-2025 13:29:30","19-04-2025 12:19:59","19-04-2025 13:51:24",=
"Cascaded Incident from TTO4945683","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to (2/5)Rectifi=
er dysfunctionning because The Load Increase //he reset the Rectifier, site=
 on Grid","system","272483","19-04-2025 13:29:30","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004839663","Eto=
udi2","","19-04-2025 13:28:26","19-04-2025 13:26:11","19-04-2025 14:38:11",=
"Site went down due to insufficiency of rectifier (Site on 02 Rectifiers ) =
SS IHS Bernard Atagana is informed and confimed // Site Stabilized","Delor =
Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Site=
 went down due to insufficiency of rectifier (Site on 02 Rectifiers ) SS IH=
S Bernard Atagana is informed and confimed // Site Stabilized","cedric.tian=
i@matech-cameroun.com","136","19-04-2025 13:28:26","MATECH CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0004839594","M=
aison-Blanche-IHS","","19-04-2025 13:12:24","19-04-2025 13:11:59","19-04-20=
25 17:05:56","Grid outage.no space to deploy mobile gen.//Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age.no space to deploy mobile gen.//Grid return","edwige.kapawo@matech-came=
roun.com","26","19-04-2025 13:12:24","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004839544","N=
koabang Ebolmedjock","","19-04-2025 12:57:01","19-04-2025 12:51:41","19-04-=
2025 13:01:48","No power issue, site on Grid Ubaie:52.6V  Site impacted by =
Nkolmessing-Abom(ctr_711)","Mba Lazare Herve","Customer Equipment Failure",=
"Active","Active Equipment Failure","Affected by 3rd Party Site","No power =
issue, site on Grid Ubaie:52.6V  Site impacted by Nkolmessing-Abom(ctr_711)=
","edwige.kapawo@matech-cameroun.com","321","19-04-2025 12:57:01","MATECH C=
MR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004839477","B=
iteng-Maetur","","19-04-2025 12:42:51","19-04-2025 12:39:38","19-04-2025 13=
:35:38","Site went down due to work: Nicolas (657108614/ sc matech)is on si=
te for swap PWC// END OF WORK","Mba Lazare Herve","Installation Activity","=
Passive","Planned Activity","Installation Activity","Site went down due to =
work: Nicolas (657108614/ sc matech)is on site for swap PWC// END OF WORK",=
"edwige.kapawo@matech-cameroun.com","195","19-04-2025 12:42:51","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0004839469","Damas","=
","19-04-2025 12:42:18","19-04-2025 12:33:45","19-04-2025 17:00:27","Cascad=
ed Incident from TTO4945829","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to work of Nomade team=
 ( 6 58 84 92 59 ) is on site for swap bay // END OF WORK","system","513","=
19-04-2025 12:42:18","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004839327","N=
kolda","IHS_YND_327","19-04-2025 12:23:07","19-04-2025 12:19:59","19-04-202=
5 13:51:24","Site went down due to (2/5)Rectifier dysfunctionning because T=
he Load Increase //he reset the Rectifier, site on Grid","Albran Byorel","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went down d=
ue to (2/5)Rectifier dysfunctionning because The Load Increase //he reset t=
he Rectifier, site on Grid","edwige.kapawo@matech-cameroun.com","189","19-0=
4-2025 12:23:07","MATECH CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004839241","Tam=
tam Weekend","IHS_YND_166, IHS_YND_518","19-04-2025 12:11:10","19-04-2025 1=
2:04:45","19-04-2025 17:02:45","Site went down due to work of Nomade team (=
 6 58 84 92 59 ) is on site for swap bay // END OF WORK","Hyemafo Gildas","=
Installation Activity","Passive","Planned Activity","Installation Activity"=
,"Site went down due to work of Nomade team ( 6 58 84 92 59 ) is on site fo=
r swap bay // END OF WORK","cedric.tiani@matech-cameroun.com","386","19-04-=
2025 12:11:10","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004839193","O=
mnisport-Rail","","19-04-2025 11:59:55","19-04-2025 11:49:59","19-04-2025 1=
2:50:20","Grid outage, site went down because Gen started and stopped with =
alarm low oil pressure  // He reset  the Gen card and site on Gen","Delor T=
elezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage, site went down because Gen started and stopped with alarm low oi=
l pressure  // He reset  the Gen card and site on Gen","edwige.kapawo@matec=
h-cameroun.com","598","19-04-2025 11:59:55","MATECH CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0004839094","Nko=
lbisson usine des eaux","","19-04-2025 11:43:57","19-04-2025 11:42:43","19-=
04-2025 11:44:36","No power issue, site is on Grid with the fme tx Mohamado=
u (691144135) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue, site is on Grid with the fme tx Mohamadou (691144135) fr=
om Huawei is informed","cedric.tiani@matech-cameroun.com","75","19-04-2025 =
11:43:57","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004839079","C=
amp-Sic-Tsinga","","19-04-2025 11:38:52","19-04-2025 11:28:59","19-04-2025 =
12:11:38","Active//No power issue Ubaie:54.5V, Site on Grid. The Tx FME Bri=
ce Tsague(650214096/ Huawei) is informed.","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power =
issue Ubaie:54.5V, Site on Grid. The Tx FME Brice Tsague(650214096/ Huawei)=
 is informed.","edwige.kapawo@matech-cameroun.com","594","19-04-2025 11:38:=
52","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004838995","Eto=
ug ebe Carrefour","","19-04-2025 11:21:30","19-04-2025 11:18:16","19-04-202=
5 11:44:01","Grid ouatge,site went down because Gen started and stopped bec=
ause the   Neighbour   stopped the GEN due to noise //Gen manually started"=
,"Hyemafo Gildas","Access Denial","Lease Or Legal","Landlord Related Issues=
","Access Issue - Land Lord","Grid ouatge,site went down because Gen starte=
d and stopped because the   Neighbour   stopped the GEN due to noise //Gen =
manually started","cedric.tiani@matech-cameroun.com","194","19-04-2025 11:2=
1:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004838963","Accacia =
New","","19-04-2025 11:14:56","19-04-2025 11:03:57","19-04-2025 14:33:57","=
Cascaded Incident from TTO4945238","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage gen ran until fuel shortage//Refueli=
ng done","system","1248259","19-04-2025 11:14:56","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_148","NOCINC0004838964","Chapelle=
-Nsimeyong","","19-04-2025 11:14:56","19-04-2025 11:03:57","19-04-2025 14:3=
3:57","Cascaded Incident from TTO4945238","MINKA NICOLAS","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage gen ran until fu=
el shortage//Refueling done","system","1248259","19-04-2025 11:14:56","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004838916","E=
kombitie","","19-04-2025 11:07:51","19-04-2025 10:54:59","19-04-2025 13:17:=
11","Active: no power issue, site is on Gen with Ubaie=3D54.5V, Symphorien(=
650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue, site is on Gen with Ubaie=3D54.5V, Symphorien(650257151/ huawei)=
 is informed","edwige.kapawo@matech-cameroun.com","773","19-04-2025 11:07:5=
1","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004838905","Nko=
l-Mbanda","IHS_YND_562, IHS_YND_148","19-04-2025 11:06:07","19-04-2025 11:0=
3:57","19-04-2025 14:33:57","Grid outage gen ran until fuel shortage//Refue=
ling done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage gen ran until fuel shortage//Refueling done","cedric.tiani@ma=
tech-cameroun.com","131","19-04-2025 11:06:07","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004838865","Nlo=
ngkak","","19-04-2025 10:59:13","19-04-2025 10:58:03","19-04-2025 12:00:31"=
,"site went down due to insufficient of rectifiers on site // Site Stabiliz=
ed","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down due to insufficient of rectifiers on site // Site Sta=
bilized","cedric.tiani@matech-cameroun.com","71","19-04-2025 10:59:13","MAT=
ECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004838860","Eto=
udi2","","19-04-2025 10:58:27","19-04-2025 10:55:16","19-04-2025 11:52:04",=
"site went down due to insufficient of rectifiers on site // Site Stabilize=
d","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","site went down due to insufficient of rectifiers on site // Site Stab=
ilized","cedric.tiani@matech-cameroun.com","192","19-04-2025 10:58:27","MAT=
ECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004838846","Sca=
lom","IHS_YND_505","19-04-2025 10:56:10","19-04-2025 10:30:47","19-04-2025 =
13:32:41","Site went down due to work: Hermann (699999625/ sc matech)is on =
site for swap bay IPT// END OF WORK","Paul BIBOUM","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Site went down due to=
 work: Hermann (699999625/ sc matech)is on site for swap bay IPT// END OF W=
ORK","cedric.tiani@matech-cameroun.com","1524","19-04-2025 10:56:10","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004838831","A=
kak-Nkozoa-MTN-IHS","","19-04-2025 10:54:49","19-04-2025 10:46:41","19-04-2=
025 12:44:48","Hybrid Gen site , Site went down because Gen started and sto=
pped with alarm high temp // He added water and Gen manually started","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Te=
mp - Coolant Level Issue","Hybrid Gen site , Site went down because Gen sta=
rted and stopped with alarm high temp // He added water and Gen manually st=
arted","edwige.kapawo@matech-cameroun.com","490","19-04-2025 10:54:49","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004838812","O=
mnisport-Rail","","19-04-2025 10:51:39","19-04-2025 10:25:59","19-04-2025 1=
1:17:27","Grid outage, site went down because Gen started and stopped with =
alarm LOW OIL PRESSURE// He reset the Gen card  and site on Gen","Delor Tel=
ezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage, site went down because Gen started and stopped with alarm LOW OIL =
PRESSURE// He reset the Gen card  and site on Gen","edwige.kapawo@matech-ca=
meroun.com","1542","19-04-2025 10:51:39","MATECH CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004838766","S=
calom-IHS","","19-04-2025 10:38:52","19-04-2025 10:30:47","19-04-2025 13:30=
:18","Site went down due to work: Hermann (699999625/ sc matech)is on site =
for swap bay IPT","","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Site went down due to work: Hermann (699999625/ sc matech)is on s=
ite for swap bay IPT// END OF WORK","edwige.kapawo@matech-cameroun.com","27=
1825","19-04-2025 10:38:52","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004838762","M=
essassi 2","","19-04-2025 10:38:08","19-04-2025 10:37:03","19-04-2025 12:12=
:33","Site went down due to rectifiers dysfunctionning on site  //Site stab=
ilised","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to rectifiers dysfunctionning on site  //Sit=
e stabilised","edwige.kapawo@matech-cameroun.com","67","19-04-2025 10:38:08=
","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004838528","MBA=
LNGONG LYCEE","","19-04-2025 09:53:38","19-04-2025 09:52:23","19-04-2025 14=
:34:23","fme is informed and said Gen overload (9kva, 130A) SS IHS Felix Za=
mbe is informed and confirmed","Fanda Brice","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","fme is informed and said Gen overload (9kva, 1=
30A) SS IHS Felix Zambe is informed and confirmed","cedric.tiani@matech-cam=
eroun.com","76","19-04-2025 09:53:38","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004838397","M=
bankomo IHS","","19-04-2025 09:28:20","19-04-2025 09:21:14","19-04-2025 09:=
51:19","Grid outage gen failed to start due to card GE faulty// gen manuall=
y started","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid outage gen failed to start due to card GE faulty// gen m=
anually started","edwige.kapawo@matech-cameroun.com","427","19-04-2025 09:2=
8:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0004838390","Obobogo"=
,"","19-04-2025 09:26:56","19-04-2025 08:57:54","19-04-2025 12:31:11","Casc=
aded Incident from TTO4944480","MINKA NICOLAS","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage gen ran until fuel shortage=
//Refueling done","system","277507","19-04-2025 09:26:56","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004838386","Eto=
udi2","","19-04-2025 09:26:15","19-04-2025 09:22:53","19-04-2025 10:13:39",=
"Site went down due to insufficiency of rectifier on site  // site stabiliz=
ed","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficiency of rectifier on site  // site st=
abilized","cedric.tiani@matech-cameroun.com","203","19-04-2025 09:26:15","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_508","NOCINC0004838270","Crf-Nsam=
","","19-04-2025 09:06:03","19-04-2025 08:57:54","19-04-2025 12:31:11","Cas=
caded Incident from TTO4944480","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage gen ran until fuel shortag=
e//Refueling done","system","277507","19-04-2025 09:06:03","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004838253","E=
foulan","IHS_YND_155, IHS_YND_508","19-04-2025 09:04:08","19-04-2025 08:57:=
54","19-04-2025 12:33:11","Grid outage gen ran until fuel shortage//Refueli=
ng done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage gen ran until fuel shortage//Refueling done","edwige.kapawo@mat=
ech-cameroun.com","375","19-04-2025 09:04:08","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004838227","Aka=
k-Nkozoa-MTN-IHS","","19-04-2025 08:54:30","19-04-2025 07:57:13","19-04-202=
5 10:05:16","site went down due to PWC Huawei  dysfunctionning, // He Reset=
 it and site is on Grid","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","site went down due to PWC Huawei  d=
ysfunctionning, // He Reset it and site is on Grid","cedric.tiani@matech-ca=
meroun.com","3439","19-04-2025 08:54:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004838205","Manguier=
","","19-04-2025 08:53:02","19-04-2025 08:47:10","19-04-2025 09:00:13","Cas=
caded Incident from TTO4944415","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue on site ,site on=
 Grid with Ubaie=3D53.6 V The Tx FME Armand Nguetsa//699949553 from Huawei =
is informed","system","263611","19-04-2025 08:53:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004838204","Omnispor=
t-Rail","","19-04-2025 08:53:02","19-04-2025 08:47:10","19-04-2025 09:00:13=
","Cascaded Incident from TTO4944415","Delor Telezing","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue on site ,si=
te on Grid with Ubaie=3D53.6 V The Tx FME Armand Nguetsa//699949553 from Hu=
awei is informed","system","263611","19-04-2025 08:53:02","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004838197","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","19-04-2025 08:51:24","19-04-=
2025 08:47:10","19-04-2025 09:00:13","Active//No power issue on site ,site =
on Grid with Ubaie=3D53.6 V The Tx FME Armand Nguetsa//699949553 from Huawe=
i is informed","Fabrice Pouakam","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site=
 ,site on Grid with Ubaie=3D53.6 V The Tx FME Armand Nguetsa//699949553 fro=
m Huawei is informed","cedric.tiani@matech-cameroun.com","255","19-04-2025 =
08:51:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004838125","OTELE MT=
N","","19-04-2025 08:28:45","19-04-2025 08:22:15","19-04-2025 08:25:37","Ca=
scaded Incident from TTO4944309","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on gen with U=3D57v No=
tice that site is impacted by Ngoumou who is not our responsability","syste=
m","1214729","19-04-2025 08:28:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004838126","Mom","",=
"19-04-2025 08:28:45","19-04-2025 08:22:15","19-04-2025 08:25:37","Cascaded=
 Incident from TTO4944309","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on gen with U=3D57v Notice t=
hat site is impacted by Ngoumou who is not our responsability","system","12=
14728","19-04-2025 08:28:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004838127","Akono","=
","19-04-2025 08:28:45","19-04-2025 08:22:15","19-04-2025 08:25:37","Cascad=
ed Incident from TTO4944309","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on gen with U=3D57v Notice=
 that site is impacted by Ngoumou who is not our responsability","system","=
1214728","19-04-2025 08:28:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004838124","OLAMA","=
","19-04-2025 08:28:44","19-04-2025 08:22:15","19-04-2025 08:25:37","Cascad=
ed Incident from TTO4944309","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on gen with U=3D57v Notice=
 that site is impacted by Ngoumou who is not our responsability","system","=
1214729","19-04-2025 08:28:44","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0004838093","Min=
ka","IHS_YND_687, IHS_YND_531, IHS_YND_370, IHS_YND_365","19-04-2025 08:24:=
28","19-04-2025 08:22:15","19-04-2025 08:25:37","No power issue site on gen=
 with U=3D57v Notice that site is impacted by Ngoumou who is not our respon=
sability","Fanda Brice","Customer Equipment Failure","Active","Active Equip=
ment Failure","Affected by 3rd Party Site","No power issue site on gen with=
 U=3D57v Notice that site is impacted by Ngoumou who is not our responsabil=
ity","cedric.tiani@matech-cameroun.com","134","19-04-2025 08:24:28","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004838071","SOA VILL=
AGE","","19-04-2025 08:20:36","19-04-2025 08:13:48","19-04-2025 09:53:52","=
Cascaded Incident from TTO4944281","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","(9kva, 130A) SS IHS Felix Zambe is"=
,"system","272793","19-04-2025 08:20:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004838068","Ebogo","=
","19-04-2025 08:18:59","19-04-2025 08:11:14","19-04-2025 08:15:37","Cascad=
ed Incident from TTO4944226","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid fluctuation,site went down due to PW=
C IPT dysfunction//He reset it and site on GRID","system","280418","19-04-2=
025 08:18:59","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004838064","S=
OA TOWN","IHS_YND_323","19-04-2025 08:17:57","19-04-2025 08:11:48","19-04-2=
025 09:53:52","Grid fluctuation,site went down because Gen failed to start =
due to Grid bad voltage//He bypassed the Grid and site on GEN","Siligap Bor=
is","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation,site went down because Gen failed to start due to Grid =
bad voltage//He bypassed the Grid and site on GEN","edwige.kapawo@matech-ca=
meroun.com","370","19-04-2025 08:17:57","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004838018","N=
kolfoulou","IHS_YND_307","19-04-2025 08:15:22","19-04-2025 08:11:14","19-04=
-2025 08:17:01","Grid fluctuation,site went down due to PWC IPT dysfunction=
//He reset it and site on GRID","Siligap Boris","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Grid fluctuation,site went down due to PW=
C IPT dysfunction//He reset it and site on GRID","edwige.kapawo@matech-came=
roun.com","249","19-04-2025 08:15:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0004837926","Marche O=
dza","","19-04-2025 07:52:17","19-04-2025 07:47:58","19-04-2025 07:52:33","=
Cascaded Incident from TTO4944114","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue on site Ubaie: =
52.4 V site on Grid The TX Lionel steve (655184876 /Huawei)) is informed. (=
MPR power supply disconnected// reconnected with Huawei's agreement)","syst=
em","267402","19-04-2025 07:52:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0004837925","Mvog-Man=
ga","","19-04-2025 07:52:16","19-04-2025 07:47:58","19-04-2025 07:52:33","C=
ascaded Incident from TTO4944114","Albran Byorel","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue on site Ubaie: 5=
2.4 V site on Grid The TX Lionel steve (655184876 /Huawei)) is informed. (M=
PR power supply disconnected// reconnected with Huawei's agreement)","syste=
m","267402","19-04-2025 07:52:16","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004837922","O=
dza","IHS_YND_254, IHS_YND_580","19-04-2025 07:51:07","19-04-2025 07:47:58"=
,"19-04-2025 08:36:03","Active//No power issue on site Ubaie: 52.4 V site o=
n Grid The TX Lionel steve (655184876 /Huawei)) is informed. (MPR power sup=
ply disconnected// reconnected with Huawei's agreement)","Albran Byorel","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue on site Ubaie: 52.4 V site on Grid The TX =
Lionel steve (655184876 /Huawei)) is informed. (MPR power supply disconnect=
ed// reconnected with Huawei's agreement)","edwige.kapawo@matech-cameroun.c=
om","190","19-04-2025 07:51:07","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004837878","M=
ontee-Des-Soeurs","","19-04-2025 07:42:27","19-04-2025 07:37:17","19-04-202=
5 07:46:31","Active // No power issue, site is on grid with Ubaie: 54.6V, M=
bah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active // No power issue, site is on grid with Ubaie: 54.6V, Mbah hosiah(6=
99699694) from Huawei is informed","edwige.kapawo@matech-cameroun.com","311=
","19-04-2025 07:42:27","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004837871","Nlo=
ngkak","","19-04-2025 07:40:52","19-04-2025 07:39:33","19-04-2025 10:09:44"=
,"site went down due to insufficient of rectifiers on site // Site Stabiliz=
ed","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down due to insufficient of rectifiers on site // Site Sta=
bilized","cedric.tiani@matech-cameroun.com","80","19-04-2025 07:40:52","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004837857","O=
lembe-Terminus","","19-04-2025 07:36:24","19-04-2025 07:35:05","19-04-2025 =
08:16:24","site went down due to disfunctionning of PSC3 // He bypassed the=
 PSC 3, site on grid","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","site went down due to disfunctionning of PSC3 =
// He bypassed the PSC 3, site on grid","edwige.kapawo@matech-cameroun.com"=
,"80","19-04-2025 07:36:24","MATECH CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0004837819","M=
adagascar-Yde-New","","19-04-2025 07:29:15","19-04-2025 07:20:07","19-04-20=
25 15:32:57","Grid Only, No space to deploy // Grid restored","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Only, No spa=
ce to deploy // Grid restored","cedric.tiani@matech-cameroun.com","549","19=
-04-2025 07:29:15","MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004837734","NKO=
MEKUI OCM","","19-04-2025 07:10:59","19-04-2025 07:04:52","19-04-2025 07:10=
:35","No power issue site on Gen with U=3D54.3 V The Tx Fme Mohamadou mouam=
 // 691144435 from Huawei is informed site impacted by Mbankolo camtel","TI=
ENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equip=
ment Failure","Affected by 3rd Party Site","No power issue site on Gen with=
 U=3D54.3 V The Tx Fme Mohamadou mouam // 691144435 from Huawei is informed=
 site impacted by Mbankolo camtel","cedric.tiani@matech-cameroun.com","369"=
,"19-04-2025 07:10:59","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004837726","Aka=
k-Nkozoa-MTN-IHS","","19-04-2025 07:09:00","19-04-2025 06:55:49","19-04-202=
5 07:06:40","Grid outage,site went down before Gen started due to poor batt=
ery backup//Gen automatically started","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,site =
went down before Gen started due to poor battery backup//Gen automatically =
started","cedric.tiani@matech-cameroun.com","1364","19-04-2025 07:09:00","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004837717","B=
arriere","","19-04-2025 07:04:40","19-04-2025 06:29:26","19-04-2025 19:50:2=
6","grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // He reduced the load and gen manually=
 started	","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","grid outage, Site went down because Gen overload(20kva,400 A) I=
HS SS Felix Zambe is informed and confirmed // He reduced the load and gen =
manually started	","edwige.kapawo@matech-cameroun.com","2116","19-04-2025 0=
7:04:40","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004837496","Aka=
k-Nkozoa-MTN-IHS","","19-04-2025 06:17:14","19-04-2025 06:08:05","19-04-202=
5 06:16:05","Grid outage , site down due to poor battery backup // Grid res=
toration","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage , site down due to poor battery ba=
ckup // Grid restoration","franck.nkomot@matech-cameroun.com","550","19-04-=
2025 06:17:14","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004837424","Aka=
k-Nkozoa-MTN-IHS","","19-04-2025 05:58:02","19-04-2025 05:52:45","19-04-202=
5 06:01:45","Grid outage , site down due to poor battery backup // Grid res=
toration","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage , site down due to poor battery ba=
ckup // Grid restoration","franck.nkomot@matech-cameroun.com","319","19-04-=
2025 05:58:02","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004837010","Mon=
tee Jouvence","","19-04-2025 02:50:55","19-04-2025 02:44:27","19-04-2025 03=
:36:55","Grid outage, site down due to Poor battery backup // Grid retorati=
on","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Battery Low","Grid outage, site down due to Poor battery backup // =
Grid retoration","franck.nkomot@matech-cameroun.com","389","19-04-2025 02:5=
0:55","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004836949","Aka=
k-Nkozoa-MTN-IHS","","19-04-2025 02:25:42","19-04-2025 02:15:31","19-04-202=
5 02:29:50","Grid outage , site down due to poor battery backup // Grid res=
toration","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage , site down due to poor battery ba=
ckup // Grid restoration","christelle.ngonga@matech-cameroun.com","613","19=
-04-2025 02:25:42","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004836948","SIM=
BOCK BONAMBAPE","","19-04-2025 02:24:50","19-04-2025 02:20:27","19-04-2025 =
02:27:27","Grid outage, Site went down before Gen start due to poor backup/=
 // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup/ // Grid return","franck.nkomot@matech-cameroun.com=
","263","19-04-2025 02:24:50","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004836909","Eto=
udi2","","19-04-2025 02:05:55","19-04-2025 02:00:49","19-04-2025 02:50:36",=
"Site went down due to insufficiency of rectifier // site stabilized","Delo=
r Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to insufficiency of rectifier // site stabilized","christe=
lle.ngonga@matech-cameroun.com","307","19-04-2025 02:05:55","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004836881","A=
kak-Nkozoa-MTN-IHS","","19-04-2025 01:52:58","19-04-2025 01:49:47","19-04-2=
025 02:06:34","Grid outage , site down due to  poor battery backup // Grid =
restoration","Fabrice Pouakam","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage , site down due to  poor batter=
y backup // Grid restoration","christelle.ngonga@matech-cameroun.com","193"=
,"19-04-2025 01:52:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004836871","Manguier=
","","19-04-2025 01:47:47","18-04-2025 22:10:26","18-04-2025 22:25:26","Cas=
caded Incident from TTO4942954","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to g=
en overload (22kva, 340A) S// He reduced the load","system","273119","19-04=
-2025 01:47:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004836870","Omnispor=
t-Rail","","19-04-2025 01:47:46","18-04-2025 22:10:26","18-04-2025 22:25:26=
","Cascaded Incident from TTO4942954","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) S// He reduced the load","system","273119","=
19-04-2025 01:47:46","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004836866","Nlo=
ngkak","","19-04-2025 01:46:47","19-04-2025 01:31:40","19-04-2025 01:51:45"=
,"Site went down due to insufficient of rectifiers// Site Stabilized","Delo=
r Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to insufficient of rectifiers// Site Stabilized","christel=
le.ngonga@matech-cameroun.com","908","19-04-2025 01:46:47","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004836864","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","19-04-2025 01:45:44","18-04-=
2025 22:10:26","18-04-2025 22:26:26","","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due t=
o gen overload (22kva, 340A) S// He reduced the load","kouoh.jean@ihstowers=
.com","12920","19-04-2025 01:45:44","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004836854","SAA=
 Entrance","","19-04-2025 01:38:53","18-04-2025 23:20:57","18-04-2025 23:27=
:57","Cascaded Incident from TTO4942527","Parker Tchoup","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid gen site , Site went Dow=
n due to Grid fluctuations // grid restoration","franck.nkomot@matech-camer=
oun.com","275970","19-04-2025 01:38:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004836831","Omnispor=
t-Rail","","19-04-2025 01:30:26","18-04-2025 21:04:33","18-04-2025 21:19:33=
","Cascaded Incident from TTO4942905","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) S// He reduced the load","system","276940","=
19-04-2025 01:30:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004836832","Manguier=
","","19-04-2025 01:30:26","18-04-2025 21:04:33","18-04-2025 21:19:33","Cas=
caded Incident from TTO4942905","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to g=
en overload (22kva, 340A) S// He reduced the load","system","276940","19-04=
-2025 01:30:26","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004836825","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","19-04-2025 01:29:07","18-04-=
2025 21:04:33","18-04-2025 21:22:33","","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due t=
o gen overload (22kva, 340A) S// He reduced the load","kouoh.jean@ihstowers=
.com","15875","19-04-2025 01:29:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004836814","TSINGA V=
ILLAGE 2","","19-04-2025 01:24:02","18-04-2025 20:44:47","18-04-2025 20:50:=
47","No power issue on site U: 51.1 V ,site on gen The Tx FME Symphorien/65=
0257151 From Huawei is informed","Delor Telezing","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site U: 51.1 V ,site on gen The Tx FME Symphorien/650257151 From Huawe=
i is informed","christelle.ngonga@matech-cameroun.com","16756","19-04-2025 =
01:24:02","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004836671","Mes=
sassi 2","","19-04-2025 00:33:28","19-04-2025 00:29:18","19-04-2025 00:38:1=
8","Site went down due to rectifier dysfunction//Site stabilised","Fabrice =
Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site =
went down due to rectifier dysfunction//Site stabilised","franck.nkomot@mat=
ech-cameroun.com","252","19-04-2025 00:33:28","MATECH CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0004836611","N=
gousso-II","","19-04-2025 00:01:48","18-04-2025 21:40:35","19-04-2025 09:00=
:38","ACCESS ISSUES during the Night Grid fluctuation,Site went down becaus=
e Gen failed to start due to Grid bad voltage//He bypassed the Grid and sit=
e on GEN","MFOUAGUEGUE MATHIEU","Access Denial","Lease Or Legal","Landlord =
Related Issues","Access Issue - Land Lord","ACCESS ISSUES during the Night =
Grid fluctuation,Site went down because Gen failed to start due to Grid bad=
 voltage//He bypassed the Grid and site on GEN","christelle.ngonga@matech-c=
ameroun.com","8474","19-04-2025 00:01:48","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004836608","NYO=
M FACE MAETUR","","19-04-2025 00:00:24","18-04-2025 23:54:07","19-04-2025 0=
2:06:18","Grid fluctuation , site went  down because Gen failed to start du=
e to Grid bad voltage // He bypassed the Grid and site  on gen","Fabrice Po=
uakam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation , site went  down because Gen failed to start due to=
 Grid bad voltage // He bypassed the Grid and site  on gen","franck.nkomot@=
matech-cameroun.com","378","19-04-2025 00:00:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004836513","Emana Ly=
cee","","18-04-2025 23:37:48","18-04-2025 23:29:50","18-04-2025 23:57:50","=
Cascaded Incident from TTO4942559","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down before=
 Gen started due to poor Battery Backup//Grid restoration","system","275709=
","18-04-2025 23:37:48","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004836512","E=
mana lycee 2","IHS_YND_274","18-04-2025 23:36:57","18-04-2025 23:29:50","18=
-04-2025 23:57:50","Grid outage,site went down before Gen started due to po=
or Battery Backup//Grid restoration","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,site we=
nt down before Gen started due to poor Battery Backup//Grid restoration","c=
hristelle.ngonga@matech-cameroun.com","428","18-04-2025 23:36:57","MATECH C=
MR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004836488","SAA=
 2","IHS_YND_542, IHS_YND_405","18-04-2025 23:27:13","18-04-2025 23:15:57",=
"18-04-2025 23:30:57","Grid gen site , Site went Down due to Grid fluctuati=
ons // grid restoration","Parker Tchoup","Grid Supply","Passive","Grid","Na=
tional Grid - Unstable Grid Supply Issue","Grid gen site , Site went Down d=
ue to Grid fluctuations // grid restoration","franck.nkomot@matech-cameroun=
.com","716","18-04-2025 23:27:13","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004836479","Saa=
","","18-04-2025 23:24:55","18-04-2025 23:20:57","18-04-2025 23:27:57","Cas=
caded Incident from TTO4942527","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Cascaded Incident from TTO4942527","fr=
anck.nkomot@matech-cameroun.com","275970","18-04-2025 23:24:55","MATECH CMR=
"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004836405","B=
iteng-Maetur","","18-04-2025 23:03:29","18-04-2025 22:52:19","18-04-2025 23=
:53:07","Site went down due to insufficiency of rectifiers//site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficiency of rectifiers//site stabilised",=
"christelle.ngonga@matech-cameroun.com","672","18-04-2025 23:03:29","MATECH=
 CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004836396","Oko=
lo Kilombo","","18-04-2025 23:00:01","18-04-2025 22:27:52","19-04-2025 00:2=
1:52","Grid outage , gen failed  to start due to an unknown  alarm // He re=
set and start gen manually","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage , gen failed  to start due t=
o an unknown  alarm // He reset and start gen manually","franck.nkomot@mate=
ch-cameroun.com","1930","18-04-2025 23:00:01","MATECH CMR"
"Cancelled","Warning","T3220","IHS_YND_765","NOCINC0004836387","MBALNGONG L=
YCEE","","18-04-2025 22:57:31","","","","Fanda Brice","","","","","","franc=
k.nkomot@matech-cameroun.com","1807","18-04-2025 22:57:31","MATECH CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0004836315","F=
OUGEROLE","","18-04-2025 22:42:51","18-04-2025 22:32:52","19-04-2025 00:03:=
51","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid outage , Site went down due to gen overload (20Kva, 300A) =
// Grid restoration","franck.nkomot@matech-cameroun.com","278913","18-04-20=
25 22:42:51","MATECH CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0004836311","N=
gousso-Savana","IHS_YND_561","18-04-2025 22:42:01","18-04-2025 22:32:52","1=
9-04-2025 00:03:51","Grid outage , Site went down due to gen overload (20Kv=
a, 300A) // Grid restoration","Siligap Boris","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage , Site went down due to gen overl=
oad (20Kva, 300A) // Grid restoration","franck.nkomot@matech-cameroun.com",=
"550","18-04-2025 22:42:01","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004836265","M=
EHANDAN","","18-04-2025 22:33:03","18-04-2025 22:27:57","18-04-2025 23:45:5=
7","	Site went down due to insufficient rectifiers on site//site stabilised=
","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","	Site went down due to insufficient rectifiers on site//site stabilised=
","franck.nkomot@matech-cameroun.com","308","18-04-2025 22:33:03","MATECH C=
MR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004836026","SAA=
 Entrance","","18-04-2025 21:52:26","18-04-2025 21:43:16","18-04-2025 21:56=
:16","Grid outage .gen failed to start due to starter relay faulty // He by=
pass it and gen manually started","Parker Tchoup","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Relay Faulty","Grid outage .gen failed to start due =
to starter relay faulty // He bypass it and gen manually started","loic.nou=
msi@matech-cameroun.com","552","18-04-2025 21:52:26","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004835863","B=
iteng-Maetur","","18-04-2025 21:18:39","18-04-2025 21:13:31","18-04-2025 22=
:36:10","Grid outage site down due to Rectifier faulty // remplacement of 1=
 Rectifier and left site on grid","Mba Lazare Herve","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","Grid outage site down due to Rectifi=
er faulty // remplacement of 1 Rectifier and left site on grid","gaelle.nji=
ofack@matech-cameroun.com","310","18-04-2025 21:18:39","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004835862","E=
ssomba","","18-04-2025 21:17:10","18-04-2025 21:11:03","18-04-2025 22:23:40=
","Grid fluctuations, Site down due to the malfunction of 3/4 rectifiers //=
 reset of 3 rectifiers, site on Grid","Mba Lazare Herve","Grid Supply","Pas=
sive","Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuation=
s, Site down due to the malfunction of 3/4 rectifiers // reset of 3 rectifi=
ers, site on Grid","gaelle.njiofack@matech-cameroun.com","368","18-04-2025 =
21:17:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004835795","Ngoum","=
","18-04-2025 21:07:48","18-04-2025 20:58:00","18-04-2025 21:13:00","Cascad=
ed Incident from TTO4941730","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage.site went down due to gen fai=
led to start //Grid returned","system","299227","18-04-2025 21:07:48","MATE=
CH CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004835787","MBI=
MBIM","IHS_YND_475","18-04-2025 21:07:11","18-04-2025 20:58:00","18-04-2025=
 21:13:00","Grid outage.site went down due to gen failed to start //Grid re=
turned","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","Grid outage.site went down due to gen failed to start //Grid r=
eturned","loic.noumsi@matech-cameroun.com","552","18-04-2025 21:07:11","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0004835699","Mballa 4=
","","18-04-2025 20:59:48","18-04-2025 20:53:42","18-04-2025 21:46:01","Cas=
caded Incident from TTO4941626","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site down due to Gen ove=
r hit // He added water and started  gen manually","system","284789","18-04=
-2025 20:59:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_275","NOCINC0004835697","Nkolbong=
","","18-04-2025 20:59:48","18-04-2025 20:53:42","18-04-2025 21:46:01","Cas=
caded Incident from TTO4941626","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site down due to Gen ove=
r hit // He added water and started  gen manually","system","284789","18-04=
-2025 20:59:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0004835698","Ekombiti=
e","","18-04-2025 20:59:48","18-04-2025 20:53:42","18-04-2025 21:46:01","Ca=
scaded Incident from TTO4941626","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site down due to Gen o=
ver hit // He added water and started  gen manually","system","284790","18-=
04-2025 20:59:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004835696","Ngoulmek=
ong-Nord","","18-04-2025 20:59:48","18-04-2025 20:53:42","18-04-2025 21:46:=
01","Cascaded Incident from TTO4941626","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down due to =
Gen over hit // He added water and started  gen manually","system","284790"=
,"18-04-2025 20:59:48","MATECH CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0004835691","San=
ta Barbara Yde","IHS_YND_277, IHS_YND_275, IHS_YND_276, IHS_YND_242","18-04=
-2025 20:57:51","18-04-2025 20:53:42","18-04-2025 21:46:01","Grid outage, s=
ite down due to Gen over hit // He added water and started  gen manually","=
Delor Telezing","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Gr=
id outage, site down due to Gen over hit // He added water and started  gen=
 manually","gaelle.njiofack@matech-cameroun.com","250","18-04-2025 20:57:51=
","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0004835574","Ngo=
usso-Savana","","18-04-2025 20:35:34","18-04-2025 20:20:25","18-04-2025 20:=
38:16","Site went down and Fme Boris reported gen overload (20Kva, 300A) //=
 site on Gen","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Site went down and Fme Boris reported gen overload (20Kva, 30=
0A) // site on Gen","loic.noumsi@matech-cameroun.com","910","18-04-2025 20:=
35:34","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004835564","Eto=
udi2","","18-04-2025 20:34:28","18-04-2025 20:28:20","19-04-2025 00:44:35",=
"Site went down due to insufficiency of rectifier (Site on 01 Rectifiers ) =
SS IHS Bernard Atagana is informed and confimed // Site Stabilized","Delor =
Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Site=
 went down due to insufficiency of rectifier (Site on 01 Rectifiers ) SS IH=
S Bernard Atagana is informed and confimed // Site Stabilized","loic.noumsi=
@matech-cameroun.com","369","18-04-2025 20:34:28","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004835552","B=
arriere","","18-04-2025 20:29:43","18-04-2025 19:47:32","18-04-2025 20:47:1=
5","Site went down due to gen overload (20KVA/ load 350A) and Bay overload/=
/ Site stabilized due to traffic reduice .","Hyemafo Gildas","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Site went down due to gen over=
load (20KVA/ load 350A) and Bay overload// Site stabilized due to traffic r=
eduice .","gaelle.njiofack@matech-cameroun.com","2532","18-04-2025 20:29:43=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004835459","Manguier=
","","18-04-2025 20:09:59","18-04-2025 20:01:40","18-04-2025 20:16:40","Cas=
caded Incident from TTO4941361","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to g=
en overload (22kva, 340A) S// He reduced the load","system","280839","18-04=
-2025 20:09:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004835458","Omnispor=
t-Rail","","18-04-2025 20:09:59","18-04-2025 20:01:40","18-04-2025 20:16:40=
","Cascaded Incident from TTO4941361","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) S// He reduced the load","system","280839","=
18-04-2025 20:09:59","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004835452","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","18-04-2025 20:07:54","18-04-=
2025 20:01:40","18-04-2025 20:20:40","Our FME Fabrice is on the way ETA 10:=
30 PM","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage, site went down due to gen overload (22kva, 340A) S// =
He reduced the load","gaelle.njiofack@matech-cameroun.com","375","18-04-202=
5 20:07:54","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004835353","M=
essassi okolo","","18-04-2025 19:47:53","18-04-2025 19:41:56","18-04-2025 2=
0:00:04","	No power issue on site Ubaie=3D 54.59 V, Load 109,2 A, site on G=
rid The TX Fme Synphorien 691316854 of Huewai is informed","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","	No power issue on site Ubaie=3D 54.59 V, Load 109,2 A, site =
on Grid The TX Fme Synphorien 691316854 of Huewai is informed","gaelle.njio=
fack@matech-cameroun.com","358","18-04-2025 19:47:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004835144","Nsimalen=
 OCM","","18-04-2025 19:11:36","18-04-2025 17:18:58","18-04-2025 23:40:58",=
"Cascaded Incident from TTO4940359","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to (2/5)Rectifi=
er dysfunctionning because The Load Increase //he reset the Rectifier, site=
 on Grid","system","297886","18-04-2025 19:11:36","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004835113","TSI=
NGA VILLAGE 2","","18-04-2025 19:03:36","18-04-2025 18:56:23","18-04-2025 1=
9:27:56","Site down due to Gen batteries HS //  gen started with external b=
attery ","Delor Telezing","Equipment Repair","Passive","DCDG Gen","DCDG - G=
enerator Battery","Site down due to Gen batteries HS //  gen started with e=
xternal battery ","loic.noumsi@matech-cameroun.com","434","18-04-2025 19:03=
:36","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004835054","Eto=
udi2","","18-04-2025 18:48:28","18-04-2025 18:43:23","18-04-2025 18:54:32",=
"site down due to Rectifier issue // he reseted rectifier","Delor Telezing"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module","site down due=
 to Rectifier issue // he reseted rectifier","gaelle.njiofack@matech-camero=
un.com","306","18-04-2025 18:48:28","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004835044","NTE=
MASSI","","18-04-2025 18:44:01","18-04-2025 18:39:46","18-04-2025 23:22:36"=
,"Site down because gen has been moved to Nsimeyong // grid return","Delor =
Telezing","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Site down because gen has been moved to Nsimeyong // grid return","loic.=
noumsi@matech-cameroun.com","255","18-04-2025 18:44:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0004834865","Monatele=
","","18-04-2025 18:09:20","18-04-2025 18:00:32","18-04-2025 19:22:37","Cas=
caded Incident from TTO4940670","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,gen ran till fuel shortage=
 // Refueling done","system","528","18-04-2025 18:09:20","MATECH CMR"
"Closed Complete","Site Down","T0053","IHS_YND_407","NOCINC0004834857","Mon=
atele MTN","IHS_YND_406","18-04-2025 18:07:38","18-04-2025 18:00:32","18-04=
-2025 19:24:33","Grid outage,gen ran till fuel shortage // Refueling done",=
"Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge,gen ran till fuel shortage // Refueling done","gaelle.njiofack@matech-ca=
meroun.com","427","18-04-2025 18:07:38","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004834717","N=
kolondom","","18-04-2025 17:44:55","18-04-2025 17:39:45","18-04-2025 18:02:=
31","Grid outage//He deploy 20kva","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage//He deploy 20kva"=
,"gaelle.njiofack@matech-cameroun.com","311","18-04-2025 17:44:55","MATECH =
CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0004834705","A=
battoir","","18-04-2025 17:41:12","18-04-2025 17:34:59","18-04-2025 23:23:5=
6","Grid outage , Site down due to Gen faulty // Grid return","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Gri=
d outage , Site down due to Gen faulty // Grid return","loic.noumsi@matech-=
cameroun.com","374","18-04-2025 17:41:12","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004834600","N=
gouetou","","18-04-2025 17:20:39","18-04-2025 17:17:24","18-04-2025 18:47:5=
5","Grid outage,gen failed to start due to alarm undervoltage//he reset car=
d and started the gen","Parker Tchoup","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage,gen failed to start due to alarm un=
dervoltage//he reset CARD and started the gen","loic.noumsi@matech-cameroun=
.com","197","18-04-2025 17:20:39","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004834595","N=
kolda","IHS_YND_327","18-04-2025 17:19:02","18-04-2025 17:18:58","18-04-202=
5 23:40:58","Site went down due to (2/5)Rectifier dysfunctionning because T=
he Load Increase //he reset the Rectifier, site on Grid","Albran Byorel","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went down d=
ue to (2/5)Rectifier dysfunctionning because The Load Increase //he reset t=
he Rectifier, site on Grid","gaelle.njiofack@matech-cameroun.com","5","18-0=
4-2025 17:19:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004834576","Manguier=
","","18-04-2025 17:16:47","18-04-2025 17:09:31","18-04-2025 17:19:38","Cas=
caded Incident from TTO4940310","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to g=
en overload (22kva, 340A) SS HISBernard ATANGANA is informed and confirmed =
// Grid restored","system","269514","18-04-2025 17:16:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004834575","Omnispor=
t-Rail","","18-04-2025 17:16:47","18-04-2025 17:09:31","18-04-2025 17:19:38=
","Cascaded Incident from TTO4940310","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and confi=
rmed // Grid restored","system","269514","18-04-2025 17:16:47","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004834551","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","18-04-2025 17:12:43","18-04-=
2025 17:09:31","18-04-2025 17:20:56","Grid outage, site went down due to ge=
n overload (22kva, 340A) SS HISBernard ATANGANA is informed and confirmed /=
/ Grid restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage, site went down due to gen overload (22kva, =
340A) SS HISBernard ATANGANA is informed and confirmed // Grid restored","g=
aelle.njiofack@matech-cameroun.com","193","18-04-2025 17:12:43","MATECH CMR=
"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004834546","B=
arriere","","18-04-2025 17:11:47","18-04-2025 17:08:39","18-04-2025 17:55:4=
1","Site down due to gen overload (20KVA/ load 350A) and Bay overload// Sit=
e stabilized due to traffic reduice .","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue on site Ubay: 54.4V site on Grid Henry (699949693/Huawei) i=
s informed","gaelle.njiofack@matech-cameroun.com","189","18-04-2025 17:11:4=
7","MATECH CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0004834516","E=
TOUDI CHAPELLE","","18-04-2025 17:09:25","18-04-2025 17:08:18","18-04-2025 =
17:11:49","Site went down because of insufficient rectifiers //site stabili=
zed","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","Site went down because of insufficient rectifiers //site=
 stabilized","gaelle.njiofack@matech-cameroun.com","68","18-04-2025 17:09:2=
5","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004834478","Par=
adis Hotel","","18-04-2025 17:00:30","18-04-2025 16:55:11","18-04-2025 18:0=
4:36","Grid Outage Site went down because Gen FAILED To start due to Alarms=
 ""Overfrequency // He reseted card and manually started the Gen","Siligap =
Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 Outage Site went down because Gen FAILED To start due to Alarms ""Overfreq=
uency // He reseted card and manually started the Gen","loic.noumsi@matech-=
cameroun.com","320","18-04-2025 17:00:30","MATECH CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0004834406","Mba=
lla 4","","18-04-2025 16:48:56","18-04-2025 16:41:46","18-04-2025 17:45:56"=
,"Grid outage, Gen stopped due to level coolant temp alarm // he reseted ca=
rd, site on grid","Delor Telezing","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Grid outage, Gen stopped due to level coolant temp =
alarm // he reseted card, site on grid ","loic.noumsi@matech-cameroun.com",=
"1231","18-04-2025 16:48:56","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004834385","NTU=
I TOWN","","18-04-2025 16:43:17","18-04-2025 16:35:05","18-04-2025 16:50:38=
","Site went down because Gen failed to start due to Grid bad voltage(lack =
of 01 phase on site)// He did a bridge on the Good phase","Parker Tchoup","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Si=
te went down Gen failed to start due to Grid bad voltage(lack of 01 phase o=
n site)// He did a bridge on the Good phase","loic.noumsi@matech-cameroun.c=
om","493","18-04-2025 16:43:17","MATECH CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0004834329","San=
ta Barbara Gottam","","18-04-2025 16:38:22","18-04-2025 16:30:45","18-04-20=
25 17:21:42","Grid outage,gen failed to start due to alarm undervoltage // =
he reset it and started the gen","Delor Telezing","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due =
to alarm undervoltage // he reset it and started the gen","loic.noumsi@mate=
ch-cameroun.com","458","18-04-2025 16:38:22","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004834317","Beh=
ind P T school Yde","","18-04-2025 16:35:40","18-04-2025 16:29:30","18-04-2=
025 17:00:30","Grid outage, Gen failed to due to Battery=92s charger (48/12=
V DC) faulty // Battery=92s charger replace and Gen start manually","Paul B=
IBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator"=
,"Grid outage, Gen failed to due to Battery=92s charger (48/12V DC) faulty =
// Battery=92s charger replace and Gen start manually","loic.noumsi@matech-=
cameroun.com","371","18-04-2025 16:35:40","MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004834208","Nko=
lmvack","","18-04-2025 16:21:43","18-04-2025 16:14:31","18-04-2025 16:25:31=
","Site impacted by Ondondo","Parker Tchoup","Customer Equipment Failure","=
Active","Active Equipment Failure","Affected by 3rd Party Site","Site impac=
ted by Ondondo","loic.noumsi@matech-cameroun.com","433","18-04-2025 16:21:4=
3","MATECH CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004834176","M=
ini-Ferme","","18-04-2025 16:16:33","18-04-2025 16:11:30","18-04-2025 18:53=
:59","	grid outage, no space to deploy a mobile gen// grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","	grid outage=
, no space to deploy a mobile gen// grid return","loic.noumsi@matech-camero=
un.com","304","18-04-2025 16:16:33","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004834171","H=
-Paradis","","18-04-2025 16:15:22","18-04-2025 16:12:16","18-04-2025 19:12:=
41","Grid only, Grid Outage; // MG deployed 13KVA","","Grid Supply","Passiv=
e","Grid","National Grid - Grid Outage Issue","Grid only, Grid Outage; // M=
G deployed 13KVA","gaelle.njiofack@matech-cameroun.com","187","18-04-2025 1=
6:15:22","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004834140","Eto=
ug ebe Carrefour","","18-04-2025 16:06:50","18-04-2025 16:01:41","18-04-202=
5 16:19:32","Site down because the  ENEO meter got burnt // Fme put site on=
 gen","Hyemafo Gildas","Fire on Site","Passive","Infrastructure","Fire - Bu=
rned","Site down because the  ENEO meter got burnt // Fme put site on gen",=
"loic.noumsi@matech-cameroun.com","309","18-04-2025 16:06:50","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004834110","Nko=
l-Mbanda","","18-04-2025 16:00:02","18-04-2025 15:52:52","18-04-2025 20:12:=
00","Site went down due to Swap of PWC IPT 36K with PWC ZTE 36k // End of w=
ork","MINKA NICOLAS","Installation Activity","Passive","Planned Activity","=
Installation Activity","Site went down due to Swap of PWC IPT 36K with PWC =
ZTE 36k // End of work","loic.noumsi@matech-cameroun.com","431","18-04-2025=
 16:00:02","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004834104","Odz=
a petit marche new","","18-04-2025 15:58:35","18-04-2025 15:50:29","18-04-2=
025 16:08:31","Grid outage, Site went down due to refueling (Poor battery b=
ackup) // End of refueling","Albran Byorel","Equipment Replacement","Passiv=
e","Planned Activity","Planned Activity - Passive","Grid outage, Site went =
down due to refueling (Poor battery backup) // End of refueling","loic.noum=
si@matech-cameroun.com","487","18-04-2025 15:58:35","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004834094","Ngo=
usso Vallee","","18-04-2025 15:56:12","18-04-2025 15:49:28","18-04-2025 17:=
53:46","Grid outage, site went down because gen start and stopped with alar=
m oil pressure // He reset gen card and gen manually started","Siligap Bori=
s","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, site went down because gen start and stopped with alarm oil pressure /=
/ He reset gen card and gen manually started","loic.noumsi@matech-cameroun.=
com","405","18-04-2025 15:56:12","MATECH CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004834021","Awa=
e Escalier","","18-04-2025 15:43:02","18-04-2025 15:38:17","18-04-2025 19:0=
5:25","Grid fluctuation,site went down because Gen failed to start due to G=
rid bad voltage// Grid CB disjuncted and gen start","Albran Byorel","Grid S=
upply","Passive","Grid","National Grid - Unstable Grid Supply Issue","Grid =
fluctuation,site went down because Gen failed to start due to Grid bad volt=
age// Grid CB disjuncted and gen start","loic.noumsi@matech-cameroun.com","=
286","18-04-2025 15:43:02","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004833712","B=
iteng-Maetur","","18-04-2025 14:56:03","18-04-2025 13:47:45","18-04-2025 15=
:45:43","Site went down due to insufficient rectifiers on site//He reset an=
d site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module Overloaded","Site went down due to insufficient rectifie=
rs on site//He reset and site on Grid","loic.noumsi@matech-cameroun.com","4=
100","18-04-2025 14:56:03","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004833696","E=
kombitie","","18-04-2025 14:54:01","18-04-2025 14:47:49","18-04-2025 15:06:=
34","Active: no power issue, site is on Grid with Ubaie=3D54.5V, Symphorien=
(650257151) from huawei is informed","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
no power issue, site is on Grid with Ubaie=3D54.5V, Symphorien(650257151) f=
rom huawei is informed","gaelle.njiofack@matech-cameroun.com","374","18-04-=
2025 14:54:01","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004833670","N=
koabang Ebolmedjock","","18-04-2025 14:48:41","18-04-2025 14:41:18","18-04-=
2025 15:01:31","site impacted by Nkolmesseng Abom which is not managing by =
us","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","Affected by 3rd Party Site","site impacted by Nkolmesseng Abo=
m which is not managing by us","loic.noumsi@matech-cameroun.com","443","18-=
04-2025 14:48:41","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004833618","C=
amp-Sic-Tsinga","","18-04-2025 14:40:42","18-04-2025 14:16:17","18-04-2025 =
15:19:04","Active//No power issue U=3D50,6V, Site on Grid. The Tx FME Brice=
 Tsague(650214096) from Huawei is informed.","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue U=3D50,6V, Site on Grid. The Tx FME Brice Tsague(650214096) from Hu=
awei is informed.","vanel.mbiada@matech-cameroun.com","1466","18-04-2025 14=
:40:42","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004833568","A=
wae Ewonkan","","18-04-2025 14:32:13","18-04-2025 14:30:06","18-04-2025 17:=
54:43","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // He reduced the load and site on Gen","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage site went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse=
 is informed // He reduced the load and site on Gen","cedric.tiani@matech-c=
ameroun.com","128","18-04-2025 14:32:13","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004833459","Nlo=
ngkak","","18-04-2025 14:11:58","18-04-2025 13:49:12","18-04-2025 14:23:17"=
,"site went down due to insufficient of rectifiers// Site Stabilized","Delo=
r Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","si=
te went down due to insufficient of rectifiers// Site Stabilized","stephane=
.nkamwa@ihstowers.com","1367","18-04-2025 14:11:58","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004833435","N=
koabang Ebolmedjock","","18-04-2025 14:08:26","18-04-2025 13:57:11","18-04-=
2025 14:10:13","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","vanel.mbiada@matec=
h-cameroun.com","676","18-04-2025 14:08:26","MATECH CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004833363","M=
ini-Ferme","","18-04-2025 13:51:57","18-04-2025 13:49:15","18-04-2025 13:53=
:28","grid outage, no space to deploy a mobile gen// grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, =
no space to deploy a mobile gen// grid return","vanel.mbiada@matech-camerou=
n.com","163","18-04-2025 13:51:57","MATECH CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0004833290","Bas=
tos Bir","","18-04-2025 13:39:08","18-04-2025 13:35:48","18-04-2025 14:23:2=
4","site down due to Generator swapp ( 20 KVA) // end of work","Mboua Thier=
ry","Equipment Replacement","Passive","Planned Activity","Planned Activity =
- ACDG Replacement","site down due to Generator swapp ( 20 KVA) // end of w=
ork","cedric.tiani@matech-cameroun.com","201","18-04-2025 13:39:08","MATECH=
 CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004833142","Ntu=
i administration","","18-04-2025 13:11:30","18-04-2025 13:09:36","18-04-202=
5 14:51:44","site went down due to absence of the Eneo phase which supplies=
 the Eneo contactor  // Grid stopped  manually and Gen start","Parker Tchou=
p","Grid Supply","Passive","Grid","National Grid - Grid Incomplete Phase","=
site went down due to absence of the Eneo phase which supplies the Eneo con=
tactor  // Grid stopped  manually and Gen start","vanel.mbiada@matech-camer=
oun.com","115","18-04-2025 13:11:30","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004833067","Nsi=
malen MTN","","18-04-2025 12:59:53","18-04-2025 12:57:40","18-04-2025 13:07=
:35","Grid outage, Site went down before Gen start due to poor backup // Ge=
n automatically started","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen automatically started","vanel.mbiada@=
matech-cameroun.com","133","18-04-2025 12:59:53","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004833016","Beh=
ind P T school Yde","","18-04-2025 12:51:25","18-04-2025 12:50:13","18-04-2=
025 12:51:43","Wrongly logged ticket","Paul BIBOUM","Incorrectly Logged Tic=
kets","Error","Error","Error","Wrongly logged ticket","vanel.mbiada@matech-=
cameroun.com","73","18-04-2025 12:51:25","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004833013","Sca=
lom","","18-04-2025 12:50:18","18-04-2025 12:48:56","18-04-2025 12:56:31","=
Grid fluctuation,site went down because Gen failed to start due to Grid bad=
 voltage//Grid return","Paul BIBOUM","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","Grid fluctuation,site went down because=
 Gen failed to start due to Grid bad voltage//Grid return","vanel.mbiada@ma=
tech-cameroun.com","83","18-04-2025 12:50:18","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004832941","O=
lembe-Terminus","","18-04-2025 12:42:03","18-04-2025 12:39:54","18-04-2025 =
12:45:51","ACTIVE//no power issue Ubaie:54.59V site on Gen, TX fme symphori=
en /650257151 from huawei is informed","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE=
//no power issue Ubaie:54.59V site on Gen, TX fme symphorien /650257151 fro=
m huawei is informed","vanel.mbiada@matech-cameroun.com","131","18-04-2025 =
12:42:03","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004832809","M=
ontee-Des-Soeurs","","18-04-2025 12:21:55","18-04-2025 12:19:41","18-04-202=
5 12:30:48","Active // No power issue, site is on grid with Ubaie: 53.96V, =
Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active // No power issue, site is on grid with Ubaie: 53.96V, Mbah hosiah=
(699699694) from Huawei is informed","vanel.mbiada@matech-cameroun.com","13=
6","18-04-2025 12:21:55","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004832801","E=
kombitie","","18-04-2025 12:17:44","18-04-2025 12:15:23","18-04-2025 12:30:=
06","Active: no power issue, site is on Grid with Ubaie=3D54.5V, Symphorien=
(650257151) from huawei is informed","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
no power issue, site is on Grid with Ubaie=3D54.5V, Symphorien(650257151) f=
rom huawei is informed","vanel.mbiada@matech-cameroun.com","142","18-04-202=
5 12:17:44","MATECH CMR"
"Closed Complete","Site Down","T0216","IHS_YND_032","NOCINC0004832781","Kam=
ajou Building","","18-04-2025 12:12:58","18-04-2025 12:11:41","18-04-2025 1=
2:20:31","Active; no power issue site on grid with U=3D53,5V;The fme TX Hos=
iah 674007438 of huawei is informed","Paul BIBOUM","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active; no p=
ower issue site on grid with U=3D53,5V;The fme TX Hosiah 674007438 of huawe=
i is informed","cedric.tiani@matech-cameroun.com","78","18-04-2025 12:12:58=
","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004832240","M=
essassi okolo","","18-04-2025 10:46:49","18-04-2025 10:43:30","18-04-2025 1=
1:17:05","Grid outage,site went down because Gen start and stopped with ala=
rm high temp//He added water and site on Gen","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","Grid outage,site went down because Gen start and stopped with alarm high=
 temp//He added water and site on Gen","vanel.mbiada@matech-cameroun.com","=
201","18-04-2025 10:46:49","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004831897","A=
wae Ewonkan","","18-04-2025 09:49:12","18-04-2025 09:46:46","18-04-2025 12:=
34:00","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // He reduced the load and site on Gen","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage site went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse=
 is informed // He reduced the load and site on Gen","vanel.mbiada@matech-c=
ameroun.com","147","18-04-2025 09:49:12","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004831880","M=
arche Odza","","18-04-2025 09:46:01","18-04-2025 09:44:50","18-04-2025 10:5=
0:05","Grid fluctuation,site went down due to rectifiers dysfunction//He re=
set and site on Grid","Albran Byorel","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Grid fluctuation,site went down due to rectifiers d=
ysfunction//He reset and site on Grid","vanel.mbiada@matech-cameroun.com","=
72","18-04-2025 09:46:01","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0004831829","Val=
lee Bastos MTN","","18-04-2025 09:35:14","18-04-2025 09:33:00","18-04-2025 =
09:37:02","Site went down due to insufficient of rectifier on site //site s=
tabilized","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficient of rectifier on site //site=
 stabilized","cedric.tiani@matech-cameroun.com","135","18-04-2025 09:35:14"=
,"MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004831822","Odz=
a petit marche new","","18-04-2025 09:34:34","18-04-2025 09:31:23","18-04-2=
025 09:52:50","Site went down due to rectifier dysfunctionning//We reset re=
ctifier and site on grid","Albran Byorel","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down due to rectifier dysfunctionning=
//We reset rectifier and site on grid","cedric.tiani@matech-cameroun.com","=
192","18-04-2025 09:34:34","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004831814","Sof=
avinc","","18-04-2025 09:31:01","18-04-2025 09:21:53","18-04-2025 10:17:00"=
,"Grid outage, site went down because gen failed to start due to gen contac=
tor faulty // He bypassed gen contactor and gen manually started","MINKA NI=
COLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Gri=
d outage, site went down because gen failed to start due to gen contactor f=
aulty // He bypassed gen contactor and gen manually started","cedric.tiani@=
matech-cameroun.com","549","18-04-2025 09:31:01","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004831789","Man=
guiers Dispensaire","","18-04-2025 09:26:27","18-04-2025 09:18:10","18-04-2=
025 11:17:53","Grid fluctuation,site went down due to rectifiers dysfunctio=
n//He reset and site on Grid","Fabrice Pouakam","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Grid fluctuation,site went down due to re=
ctifiers dysfunction//He reset and site on Grid","cedric.tiani@matech-camer=
oun.com","498","18-04-2025 09:26:27","MATECH CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0004831777","C=
NDH","","18-04-2025 09:22:30","18-04-2025 09:17:04","18-04-2025 09:30:19","=
Site manage by CAMUSAT","Paul BIBOUM","Customer Equipment Failure","Active"=
,"Active Equipment Failure","Affected by 3rd Party Site","Site manage by CA=
MUSAT","vanel.mbiada@matech-cameroun.com","326","18-04-2025 09:22:30","MATE=
CH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004831765","Nko=
ulou Carriere carrefourt","","18-04-2025 09:20:03","18-04-2025 09:10:50","1=
8-04-2025 13:16:40","Site went down due to disjunction of Cb in PWC // He r=
eamed Cb, site on grid","Mba Lazare Herve","Equipment Repair","Passive","Co=
ntrol Panel","BTS Breaker Tripped","Site went down due to disjunction of Cb=
 in PWC // He reamed Cb, site on grid","cedric.tiani@matech-cameroun.com","=
554","18-04-2025 09:20:03","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004831626","Nlo=
ngkak","","18-04-2025 08:53:34","18-04-2025 08:50:23","18-04-2025 10:11:37"=
,"site went down due to insufficient of rectifiers// Site Stabilized","Delo=
r Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","si=
te went down due to insufficient of rectifiers// Site Stabilized","cedric.t=
iani@matech-cameroun.com","192","18-04-2025 08:53:34","MATECH CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004831623","Bas=
tos Amb Coree","","18-04-2025 08:52:25","18-04-2025 08:05:07","18-04-2025 0=
9:43:10","Grid outage .no space to deploy a mobile Gen // Grid power Restor=
ed","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage .no space to deploy a mobile Gen // Grid power Restored","cedri=
c.tiani@matech-cameroun.com","2839","18-04-2025 08:52:25","MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004831509","Nko=
lmvack","","18-04-2025 08:31:19","18-04-2025 08:05:57","18-04-2025 08:06:37=
","Wrongly logged ticket","Parker Tchoup","Incorrectly Logged Tickets","Err=
or","Error","Error","Wrongly logged ticket","cedric.tiani@matech-cameroun.c=
om","1523","18-04-2025 08:31:19","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004831473","A=
WAE OCM","","18-04-2025 08:18:59","18-04-2025 08:17:45","18-04-2025 09:23:3=
6","Grid outage,Site went down due to ZTE PWC dysfunctioning// He reset the=
 PWC and site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Grid outage,Site went down due to ZTE PWC dysfu=
nctioning// He reset the PWC and site on Grid","vanel.mbiada@matech-camerou=
n.com","76","18-04-2025 08:18:59","MATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0004831314","S=
ofavinc","","18-04-2025 07:44:21","18-04-2025 07:42:14","18-04-2025 08:51:2=
0","Grid outage, site went down because gen failed to start due to gen cont=
actor faulty // He bypassed gen contactor and gen manually started","MINKA =
NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","G=
rid outage, site went down because gen failed to start due to gen contactor=
 faulty // He bypassed gen contactor and gen manually started","vanel.mbiad=
a@matech-cameroun.com","128","18-04-2025 07:44:21","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004831078","B=
riqueterie","","18-04-2025 06:47:06","18-04-2025 06:45:52","18-04-2025 08:5=
6:11","Grid outage ,no space to deploy mobil Gen // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,n=
o space to deploy mobil Gen // Grid return","vanel.mbiada@matech-cameroun.c=
om","75","18-04-2025 06:47:06","MATECH CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004831051","Bri=
quetterie","","18-04-2025 06:39:31","18-04-2025 06:25:22","18-04-2025 09:07=
:21","Grid outage ,no space to deploy mobil Gen // Grid return,","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,n=
o space to deploy mobil Gen // Grid return,","franck.nkomot@matech-cameroun=
.com","850","18-04-2025 06:39:31","MATECH CMR"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0004831007","Ngo=
g Mapubi","","18-04-2025 06:28:54","18-04-2025 06:06:47","18-04-2025 07:40:=
25","Grid outage,site went down because Gen failed to start due to Grid bad=
 voltage,no rcp on site//He bypassed the Grid and site on Gen","Kemeni Fran=
klin","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid outage,site went down because Gen failed to start due to Grid bad=
 voltage,no rcp on site//He bypassed the Grid and site on Gen","franck.nkom=
ot@matech-cameroun.com","1328","18-04-2025 06:28:54","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004830934","N=
KOLMEKONG YDE","","18-04-2025 06:03:13","18-04-2025 05:26:03","18-04-2025 0=
9:30:51","Grid outage,Site went down because Gen failed to start due to Gen=
 battery discharged//He started the GEN with an external battery","Fabrice =
Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery"=
,"Grid outage,Site went down because Gen failed to start due to Gen battery=
 discharged//He started the GEN with an external battery","christelle.ngong=
a@matech-cameroun.com","2277","18-04-2025 06:03:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004830930","OLAMA","=
","18-04-2025 06:03:03","18-04-2025 05:55:55","18-04-2025 06:24:26","Cascad=
ed Incident from TTO4936179","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) not manage by IHS","system","266818","18-04-2025 06:03:03=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004830931","OTELE MT=
N","","18-04-2025 06:03:03","18-04-2025 05:55:55","18-04-2025 06:24:26","Ca=
scaded Incident from TTO4936179","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue site on Grid with U=
=3D53,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impac=
ted by Ngoumou(T0169) not manage by IHS","system","266818","18-04-2025 06:0=
3:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004830933","Akono","=
","18-04-2025 06:03:03","18-04-2025 05:55:55","18-04-2025 06:24:26","Cascad=
ed Incident from TTO4936179","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) not manage by IHS","system","266819","18-04-2025 06:03:03=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004830932","Minka","=
","18-04-2025 06:03:03","18-04-2025 05:55:55","18-04-2025 06:24:26","Cascad=
ed Incident from TTO4936179","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) not manage by IHS","system","266819","18-04-2025 06:03:03=
","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004830928","Mom=
","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_365","18-04-2025 06:02:05=
","18-04-2025 05:55:55","18-04-2025 06:24:26","Active//No power issue site =
on Grid with U=3D53,3 V The FME TX Etienne(695033981) From Huawei is inform=
ed. Site impacted by Ngoumou(T0169) not manage by IHS","Fanda Brice","Custo=
mer Equipment Failure","Active","Active Equipment Failure","Affected by 3rd=
 Party Site","Active//No power issue site on Grid with U=3D53,3 V The FME T=
X Etienne(695033981) From Huawei is informed. Site impacted by Ngoumou(T016=
9) not manage by IHS","ludivine.ngamaleu@ihstowers.com","371","18-04-2025 0=
6:02:05","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004830913","N=
yom OCM","","18-04-2025 05:49:56","18-04-2025 05:45:48","18-04-2025 09:47:0=
1","Grid outage,site went down because Gen start and stopped with alarm low=
 oil pressure//He added oil and site on Gen","Fabrice Pouakam","Equipment R=
epair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage,site wen=
t down because Gen start and stopped with alarm low oil pressure//He added =
oil and site on Gen","christelle.ngonga@matech-cameroun.com","249","18-04-2=
025 05:49:56","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004830906","Awa=
e Ewonkan","","18-04-2025 05:46:34","18-04-2025 05:35:03","18-04-2025 06:02=
:02","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IH=
S SS Alphonse is informed // He reduced the load and site on Gen","Albran B=
yorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge site went down due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse i=
s informed // He reduced the load and site on Gen","franck.nkomot@matech-ca=
meroun.com","1131","18-04-2025 05:46:34","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0004830883","Val=
lee Bastos MTN","","18-04-2025 05:36:01","18-04-2025 05:32:48","18-04-2025 =
09:07:20","Site went down due to  insufficient of rectifier on site//He res=
et it and site on grid","Mboua Thierry","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down due to  insufficient of rectifier =
on site//He reset it and site on grid","franck.nkomot@matech-cameroun.com",=
"194","18-04-2025 05:36:01","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004830882","O=
dza II OCM","","18-04-2025 05:35:33","18-04-2025 05:30:24","18-04-2025 06:3=
3:51","Grid outage ,site went down because GEN failed to start due to Gen c=
ard faulty// He started the Gen manually","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,site went down =
because GEN failed to start due to Gen card faulty// He started the Gen man=
ually","christelle.ngonga@matech-cameroun.com","311","18-04-2025 05:35:33",=
"MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004830870","Nsi=
malen MTN","","18-04-2025 05:30:57","18-04-2025 05:26:39","18-04-2025 05:36=
:39","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","franck.nkomot@matech-cameroun.com","259",=
"18-04-2025 05:30:57","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004830824","Ebo=
go","","18-04-2025 05:15:52","18-04-2025 05:09:57","18-04-2025 05:22:57","A=
ctive// No Power issue on site Ubaie 53.2V site on Grid, Julien /693095849 =
from Huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issu=
e on site Ubaie 53.2V site on Grid, Julien /693095849 from Huawei is inform=
ed","franck.nkomot@matech-cameroun.com","356","18-04-2025 05:15:52","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004830785","N=
kolondom","","18-04-2025 04:58:04","18-04-2025 04:51:55","18-04-2025 09:00:=
07","Grid outage//He deploy 20kva","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage//He deploy 20kva"=
,"christelle.ngonga@matech-cameroun.com","370","18-04-2025 04:58:04","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004830471","E=
kombitie","","18-04-2025 01:47:35","18-04-2025 01:45:29","18-04-2025 03:33:=
13","No power issue, site is on Gen with Ubaie=3D54.5V, Symphorien(65025715=
1/ huawei) is informed","Fabrice Pouakam","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power issu=
e, site is on Gen with Ubaie=3D54.5V, Symphorien(650257151/ huawei) is info=
rmed","christelle.ngonga@matech-cameroun.com","127","18-04-2025 01:47:35","=
MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004830426","Bas=
tos-BAT","","18-04-2025 01:31:01","18-04-2025 01:28:42","18-04-2025 01:36:4=
2","Grid outage , site went down before Gen started due to poor battery bac=
kup// gen automatically started","Mboua Thierry","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage , site went d=
own before Gen started due to poor battery backup// gen automatically start=
ed","ludivine.ngamaleu@ihstowers.com","139","18-04-2025 01:31:01","MATECH C=
MR"
"Closed Complete","Site Down","T3206","IHS_YND_759","NOCINC0004830415","Nko=
lfoulou Tsinga Village","","18-04-2025 01:20:47","18-04-2025 01:15:34","18-=
04-2025 01:25:34","Grid fluctuation, Site went down because Gen failed to s=
tart due to Grid bad voltage // Grid Stabilisation","Siligap Boris","Grid S=
upply","Passive","Grid","National Grid - Low Current Supply","Grid fluctuat=
ion, Site went down because Gen failed to start due to Grid bad voltage // =
Grid Stabilisatio","ludivine.ngamaleu@ihstowers.com","314","18-04-2025 01:2=
0:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0004830378","NKOLMEKO=
NG YDE","","18-04-2025 01:02:22","18-04-2025 00:35:57","18-04-2025 02:04:26=
","Cascaded Incident from TTO4935519","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site down because=
 Gen was no feeding the batteries  // He added the power limiation","system=
","278856","18-04-2025 01:02:22","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0004830366","Mes=
sassi Ngonlonk","","18-04-2025 01:00:58","18-04-2025 00:37:57","18-04-2025 =
02:09:17","Cascaded Incident from TTO4935520","Fabrice Pouakam","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Cascaded Incident from=
 TTO4935520","franck.nkomot@matech-cameroun.com","1235398","18-04-2025 01:0=
0:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004830363","Akak-Nko=
zoa-MTN-IHS","","18-04-2025 00:59:12","18-04-2025 00:37:57","18-04-2025 02:=
09:17","Cascaded Incident from TTO4935520","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, Site down be=
cause Gen was no feeding the batteries  // He added the power limiation","s=
ystem","1235398","18-04-2025 00:59:12","MATECH CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0004830358","M=
essassi","IHS_YND_316, IHS_YND_681, IHS_YND_799","18-04-2025 00:58:05","18-=
04-2025 00:35:57","18-04-2025 02:09:17","Grid outage, Site down because Gen=
 was not feeding the batteries  // He added the power limiation","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage, Site down because Gen was no feeding the batteries  // He added t=
he power limiation","christelle.ngonga@matech-cameroun.com","1329","18-04-2=
025 00:58:05","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004830351","Beh=
ind P T school Yde","","18-04-2025 00:55:01","18-04-2025 00:44:59","18-04-2=
025 07:08:28","Access issue at night Grid outage,site went down because Gen=
 failed to start due to Charger static faulty//He started the GEN with an e=
xternal battery","Paul BIBOUM","Access Denial","Lease Or Legal","Landlord R=
elated Issues","Access Issue - Land Lord","Access issue at night Grid outag=
e,site went down because Gen failed to start due to Charger static faulty//=
He started the GEN with an external battery","ludivine.ngamaleu@ihstowers.c=
om","603","18-04-2025 00:55:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0004830348","NKOLMEKO=
NG YDE","","18-04-2025 00:53:59","17-04-2025 23:17:37","17-04-2025 23:52:55=
","Cascaded Incident from TTO4935267","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Gen failed to sta=
rt due to alarm overcurrent // Gen cart reset and site on Gen","system","12=
18615","18-04-2025 00:53:59","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004830270","B=
arriere","","18-04-2025 00:27:46","17-04-2025 23:53:32","18-04-2025 00:10:1=
1","Active//No power issue on site Ubay: 54.4V site on Grid Henry (69994969=
3/Huawei) is informed","Hyemafo Gildas","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue =
on site Ubay: 54.4V site on Grid Henry (699949693/Huawei) is informed","chr=
istelle.ngonga@matech-cameroun.com","2055","18-04-2025 00:27:46","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004830234","Akak-Nko=
zoa-MTN-IHS","","18-04-2025 00:08:02","17-04-2025 23:20:37","18-04-2025 00:=
05:53","Cascaded Incident from TTO4935228","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, Gen failed t=
o start due to alarm overcurrent // Gen cart reset and site on Gen","system=
","1218434","18-04-2025 00:08:02","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004830167","Nlo=
ngkak","","17-04-2025 23:50:02","17-04-2025 23:37:43","17-04-2025 23:58:43"=
,"site went down due to insufficient of rectifiers// Site Stabilized","Delo=
r Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","si=
te went down due to insufficient of rectifiers// Site Stabilized","franck.n=
komot@matech-cameroun.com","740","17-04-2025 23:50:02","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0004830110","Mes=
sassi Ngonlonk","","17-04-2025 23:29:39","17-04-2025 23:20:37","18-04-2025 =
00:05:53","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, Gen failed to start due to alarm overcurre=
nt // Gen cart reset and site on Gen","franck.nkomot@matech-cameroun.com","=
1218434","17-04-2025 23:29:39","MATECH CMR"
"Closed Complete","Site Down","T0051","IHS_YND_297","NOCINC0004830106","Mes=
sassi","IHS_YND_316, IHS_YND_681, IHS_YND_799","17-04-2025 23:27:53","17-04=
-2025 23:17:37","18-04-2025 00:05:53","Grid outage, Gen failed to start due=
 to alarm overcurrent // Gen cart reset and site on Gen","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
, Gen failed to start due to alarm overcurrent // Gen cart reset and site o=
n Gen","franck.nkomot@matech-cameroun.com","1208","17-04-2025 23:27:53","MA=
TECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004829953","Eto=
ug ebe Carrefour","","17-04-2025 22:55:34","17-04-2025 22:52:17","17-04-202=
5 22:58:55","Grid outage, Site went down because Gen failed to start due to=
 Grid bad voltage and poor backup //grid stabilized","Hyemafo Gildas","Grid=
 Supply","Passive","Grid","National Grid - Low Current Supply","Grid outage=
, Site went down because Gen failed to start due to Grid bad voltage and po=
or backup //grid stabilized","ludivine.ngamaleu@ihstowers.com","198","17-04=
-2025 22:55:34","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004829863","AWA=
E OCM","","17-04-2025 22:31:40","17-04-2025 22:25:19","17-04-2025 22:49:08"=
,"Grid outage, Site went down before Gen start due to poor backup // Grid r=
estoration","Mba Lazare Herve","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, Site went down before Gen star=
t due to poor backup // Grid restoration","loic.noumsi@matech-cameroun.com"=
,"382","17-04-2025 22:31:40","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0004829568","Nko=
langaa","","17-04-2025 21:34:07","17-04-2025 21:25:59","17-04-2025 22:25:59=
","Site went down because the Cb(125A) of PWC dysfonction due to load incre=
ased // He reamed the Cb","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Circuit Breaker Tripped","Site went down because the Cb(125=
A) of PWC dysfonction due to load increased // He reamed the Cb","loic.noum=
si@matech-cameroun.com","489","17-04-2025 21:34:07","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004829466","B=
iteng-Maetur","","17-04-2025 21:21:19","17-04-2025 20:56:56","18-04-2025 10=
:32:17","Site went down due to insufficiency of rectifiers//site stabilised=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficiency of rectifiers//site stabilised",=
"loic.noumsi@matech-cameroun.com","1465","17-04-2025 21:21:19","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004829434","Men=
dong vallee","","17-04-2025 21:14:25","17-04-2025 21:09:16","17-04-2025 21:=
23:16","Site wen down due to work on site by FMS Judicael (instalation of B=
aie )//End of work, site stabilized","Fanda Brice","Equipment Replacement",=
"Passive","Planned Activity","Planned Activity - Passive","Site wen down du=
e to work on site by FMS Judicael (instalation of Baie )//End of work, site=
 stabilized","loic.noumsi@matech-cameroun.com","310","17-04-2025 21:14:25",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004829366","M=
essassi okolo","","17-04-2025 21:00:31","17-04-2025 20:53:10","17-04-2025 2=
2:24:43","No power issue on site Ubaie=3D 54.59 V, Load 109,2 A, site on Gr=
id The TX Fme Synphorien 691316854 of Huewai is informed","Fabrice Pouakam"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue on site Ubaie=3D 54.59 V, Load 109,2 A, site on=
 Grid The TX Fme Synphorien 691316854 of Huewai is informed","loic.noumsi@m=
atech-cameroun.com","443","17-04-2025 21:00:31","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004829307","Mes=
sassi 2","","17-04-2025 20:51:00","17-04-2025 20:41:48","17-04-2025 22:28:4=
8","Grid outage, site went down because gen start and stopped due to high t=
emp // He added water and manually start the gen","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, site went do=
wn because gen start and stopped due to high temp // He added water and man=
ually start the gen","loic.noumsi@matech-cameroun.com","553","17-04-2025 20=
:51:00","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004829252","Awa=
e Ewonkan","","17-04-2025 20:40:33","17-04-2025 20:30:25","17-04-2025 21:39=
:16","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IH=
S SS Alphonse is informed // He reduced the load and started Gen manually",=
"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IHS SS A=
lphonse is informed // He reduced the load and started Gen manually","loic.=
noumsi@matech-cameroun.com","610","17-04-2025 20:40:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_508","NOCINC0004829186","Crf-Nsam=
","","17-04-2025 20:31:02","17-04-2025 20:21:58","17-04-2025 20:36:34","Cas=
caded Incident from TTO4934149","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because Gen failed to s=
tart due to Lack of 2 Phase and No RCP on Site// He bypassed Grid and start=
ed Gen manually","system","308307","17-04-2025 20:31:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0004829185","Obobogo"=
,"","17-04-2025 20:31:01","17-04-2025 20:21:58","17-04-2025 20:36:34","Casc=
aded Incident from TTO4934149","MINKA NICOLAS","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because Gen failed to st=
art due to Lack of 2 Phase and No RCP on Site// He bypassed Grid and starte=
d Gen manually","system","308307","17-04-2025 20:31:01","MATECH CMR"
"Closed Complete","Site Down","T2795","IHS_YND_070","NOCINC0004829176","Efo=
ulan","IHS_YND_155, IHS_YND_508","17-04-2025 20:29:10","17-04-2025 20:21:58=
","17-04-2025 20:36:34","Site went down because Gen failed to start due to =
Lack of 2 Phase and No RCP on Site// He bypassed Grid and started Gen manua=
lly","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Site went down because Gen failed to start due to Lack =
of 2 Phase and No RCP on Site// He bypassed Grid and started Gen manually",=
"loic.noumsi@matech-cameroun.com","433","17-04-2025 20:29:10","MATECH CMR"
"Closed Complete","Warning","T0197","IHS_YND_263","NOCINC0004829145","Mendo=
ng Plateau","","17-04-2025 20:22:13","","","FME is informed, and manage it =
// grid CB rearmed","Hyemafo Gildas","Warning","Warning","POWER","Warning -=
 ATS-AMF Issue","FME is informed, and manage it // grid CB rearmed","loic.n=
oumsi@matech-cameroun.com","10951","17-04-2025 20:22:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004828936","Omnispor=
t-Rail","","17-04-2025 19:45:52","17-04-2025 18:42:05","18-04-2025 10:34:21=
","Cascaded Incident from TTO4933866","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed and confi=
rmed// He reduced the load and manually start the GEN","system","335940","1=
7-04-2025 19:45:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004828937","Manguier=
","","17-04-2025 19:45:52","17-04-2025 18:42:05","18-04-2025 10:34:21","Cas=
caded Incident from TTO4933866","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to g=
en overload (22kva, 340A) SS HISBernard ATANGANA is informed and confirmed/=
/ He reduced the load and manually start the GEN","system","335940","17-04-=
2025 19:45:52","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004828927","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","17-04-2025 19:42:17","17-04-=
2025 18:42:05","18-04-2025 10:34:21","Grid outage, site went down due to ge=
n overload (22kva, 340A) SS HISBernard ATANGANA is informed and confirmed//=
 He reduced the load and manually start the GEN","Fabrice Pouakam","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went d=
own due to gen overload (22kva, 340A) SS HISBernard ATANGANA is informed an=
d confirmed// He reduced the load and manually start the GEN","gaelle.njiof=
ack@matech-cameroun.com","3613","17-04-2025 19:42:17","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004828905","E=
ssomba","","17-04-2025 19:35:33","17-04-2025 19:30:23","17-04-2025 20:22:45=
","Grid fluctuations, Site down due to the malfunction of 3/4 rectifiers //=
 reset of 3 rectifiers, site on Grid","Mba Lazare Herve","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid fluctuations, Si=
te down due to the malfunction of 3/4 rectifiers // reset of 3 rectifiers, =
site on Grid","gaelle.njiofack@matech-cameroun.com","311","17-04-2025 19:35=
:33","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004828808","N=
kolda","","17-04-2025 19:15:46","17-04-2025 19:11:34","17-04-2025 22:55:34"=
,"Site went down due to (2/5)Rectifier dysfunctionning because The Load Inc=
rease //he reset the Rectifier, site on Grid","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down due to (2/5)=
Rectifier dysfunctionning because The Load Increase //he reset the Rectifie=
r, site on Grid","gaelle.njiofack@matech-cameroun.com","253","17-04-2025 19=
:15:46","MATECH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0004828658","Lob=
o 2","","17-04-2025 18:49:35","17-04-2025 18:43:27","17-04-2025 22:00:30","=
Site down due to gen overload // He reduced the load , site on grid","TIENT=
CHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overlo=
ad","Site down due to gen overload // He reduced the load , site on grid","=
loic.noumsi@matech-cameroun.com","369","17-04-2025 18:49:35","MATECH CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0004828584","E=
TOUDI CHAPELLE","","17-04-2025 18:40:02","17-04-2025 18:37:52","17-04-2025 =
18:40:52","Site went down because of insufficient rectifiers //site stabili=
zed","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Site went down because of insufficient rectifiers //site stabilized=
","gaelle.njiofack@matech-cameroun.com","131","17-04-2025 18:40:02","MATECH=
 CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0004828461","Ngo=
usso-Savana","","17-04-2025 18:20:44","17-04-2025 18:16:54","17-04-2025 18:=
31:10","Prensence of Grid Gen start due to PWC Huawei malfunction,  // He r=
eset and site on Grid","Siligap Boris","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Prensence of Grid Gen start due to PWC =
Huawei malfunction,  // He reset and site on Grid","loic.noumsi@matech-came=
roun.com","230","17-04-2025 18:20:44","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004828349","S=
calom","","17-04-2025 18:11:38","17-04-2025 18:07:31","17-04-2025 18:21:22"=
,"	Grid Outage, site went down before gen start due to poor battery backup =
// Grid return","Paul BIBOUM","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","	Grid Outage, site went down before gen star=
t due to poor battery backup // Grid return","gaelle.njiofack@matech-camero=
un.com","248","17-04-2025 18:11:38","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004828324","M=
essassi okolo","","17-04-2025 18:06:12","17-04-2025 17:57:53","17-04-2025 1=
9:39:31","Grid outage, Site went down due to malfunction of Gen card // Gen=
 card reset","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Grid outage, Site went down due to malfunction of Gen c=
ard // Gen card reset","gaelle.njiofack@matech-cameroun.com","501","17-04-2=
025 18:06:12","MATECH CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0004828200","Men=
dong Plateau","","17-04-2025 17:50:46","17-04-2025 17:47:25","17-04-2025 18=
:13:56","site went down due to disjunction of Grid circuit breaker in the A=
TS // Grid circuit breaker rearm","Hyemafo Gildas","Grid Supply","Passive",=
"Grid","National Grid - Circuit Breaker","site went down due to disjunction=
 of Grid circuit breaker in the ATS // Grid circuit breaker rearm","loic.no=
umsi@matech-cameroun.com","202","17-04-2025 17:50:46","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004828080","Eto=
ug ebe Carrefour","","17-04-2025 17:28:22","17-04-2025 13:40:54","17-04-202=
5 17:17:25","Grid outage, Site went down because Gen failed to start due to=
 Grid bad voltage and poor backup //grid stabilized","Hyemafo Gildas","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid o=
utage, Site went down because Gen failed to start due to Grid bad voltage a=
nd poor backup //grid stabilized","loic.noumsi@matech-cameroun.com","14138"=
,"17-04-2025 17:28:22","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0004828054","Mes=
sassi Ngonlonk","","17-04-2025 17:21:32","17-04-2025 16:24:32","17-04-2025 =
17:03:17","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, Gen failed to start due to alarm overcurre=
nt // Gen cart reset and site on Gen","loic.noumsi@matech-cameroun.com","28=
6703","17-04-2025 17:21:32","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004827886","BAT=
A Mokolo OCM","","17-04-2025 16:54:34","17-04-2025 16:46:44","17-04-2025 16=
:54:52","Grid outage, No space to deploy a MDG // Grid restored","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy a MDG // Grid restored","loic.noumsi@matech-cameroun.com"=
,"597","17-04-2025 16:54:34","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004827869","B=
arriere","","17-04-2025 16:51:16","17-04-2025 16:48:08","17-04-2025 22:27:3=
2","Grid outage, Site down due to gen overlord (20KVA/ load 350A) IHS SS Fe=
lix Zambe is informed and confirmed // Grid restoration","Hyemafo Gildas","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site=
 down due to gen overlord (20KVA/ load 350A) IHS SS Felix Zambe is informed=
 and confirmed // Grid restoration","gaelle.njiofack@matech-cameroun.com","=
189","17-04-2025 16:51:16","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004827813","Sim=
e Building","","17-04-2025 16:43:50","17-04-2025 16:42:42","17-04-2025 17:2=
5:41","Site went down because 02/05 rectifiers dysfuncionned //He reset rec=
tifiers ","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Site went down because 02/05 rectifiers dysfuncionne=
d //He reset rectifiers ","gaelle.njiofack@matech-cameroun.com","69","17-04=
-2025 16:43:50","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004827693","N=
KOLMEKONG YDE","","17-04-2025 16:32:09","17-04-2025 16:18:32","17-04-2025 1=
9:06:43","Fabrice is informed","Fabrice Pouakam","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Gen failed to start due =
to alarm overcurrent // Gen cart reset and site on Gen","gaelle.njiofack@ma=
tech-cameroun.com","287063","17-04-2025 16:32:09","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004827689","M=
EHANDAN","","17-04-2025 16:30:33","17-04-2025 16:27:26","18-04-2025 10:21:0=
9","Site went down due to insufficient rectifiers on site//site stabilised"=
,"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient rectifiers on site//site stabilised",=
"gaelle.njiofack@matech-cameroun.com","189","17-04-2025 16:30:33","MATECH C=
MR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004827685","E=
kombitie","","17-04-2025 16:29:48","17-04-2025 16:16:25","17-04-2025 16:38:=
57","Active: no power issue, site is on Gen with Ubaie=3D54.5V, Symphorien(=
650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue, site is on Gen with Ubaie=3D54.5V, Symphorien(650257151/ huawei)=
 is informed","loic.noumsi@matech-cameroun.com","804","17-04-2025 16:29:48"=
,"MATECH CMR"
"Closed Complete","Site Down","T0051","IHS_YND_297","NOCINC0004827665","Mes=
sassi","IHS_YND_681, IHS_YND_799","17-04-2025 16:26:39","17-04-2025 16:18:3=
2","17-04-2025 19:06:43","Grid outage, Gen failed to start due to alarm ove=
rcurrent // Gen cart reset and site on Gen","Fabrice Pouakam","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Gen failed to st=
art due to alarm overcurrent // Gen cart reset and site on Gen","gaelle.nji=
ofack@matech-cameroun.com","542","17-04-2025 16:26:39","MATECH CMR"
"Closed Complete","Site Down","T1431","IHS_YND_561","NOCINC0004827564","FOU=
GEROLE","","17-04-2025 16:05:17","17-04-2025 15:53:50","17-04-2025 16:49:10=
","Grid outage, Gen stopped due to Alarm high temp // Water add and Gen sta=
rt manually","Siligap Boris","Equipment Repair","Passive","ACDG Gen","Gen T=
emp High","Grid outage, Gen stopped due to Alarm high temp // Water add and=
 Gen start manually","loic.noumsi@matech-cameroun.com","688","17-04-2025 16=
:05:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004827542","Omnispor=
t-Rail","","17-04-2025 16:01:01","17-04-2025 15:48:12","17-04-2025 18:32:27=
","Cascaded Incident from TTO4932247","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","OUR FME is on site; site went d=
own due to burn Eneo fuse and Cable // Gen start manually","system","274494=
","17-04-2025 16:01:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004827544","Manguier=
","","17-04-2025 16:01:01","17-04-2025 15:48:12","17-04-2025 18:32:27","Cas=
caded Incident from TTO4932247","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","OUR FME is on site; site went down d=
ue to burn Eneo fuse and Cable // Gen start manually","system","274494","17=
-04-2025 16:01:01","MATECH CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004827533","MAN=
GUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","17-04-2025 15:58:23","17-04-20=
25 15:48:12","17-04-2025 18:34:10","OUR FME is on site; site went down due =
to burn Eneo fuse and Cable // Gen start manually","Fabrice Pouakam","Grid =
Supply","Passive","Grid","National Grid - Fuse Burnt","OUR FME is on site; =
site went down due to burn Eneo fuse and Cable // Gen start manually","loic=
.noumsi@matech-cameroun.com","760","17-04-2025 15:58:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004827508","Eseka To=
wn","","17-04-2025 15:51:22","17-04-2025 15:43:22","17-04-2025 16:43:18","C=
ascaded Incident from TTO4932207","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,DG started and stopped=
 due with alarm ""oil pressure""( unprouven Alarm ) // He bypassed grid and=
 put Gen on Manual Mode","system","274844","17-04-2025 15:51:22","MATECH CM=
R"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0004827496","E=
seka OCM","IHS_YND_378","17-04-2025 15:50:03","17-04-2025 15:43:22","17-04-=
2025 16:43:18","Grid outage,DG started and stopped due with alarm ""oil pre=
ssure""( unprouven Alarm ) // He bypassed grid and put Gen on Manual Mode",=
"Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil P=
ressure","Grid outage,DG started and stopped due with alarm ""oil pressure"=
"( unprouven Alarm ) // He bypassed grid and put Gen on Manual Mode","loic.=
noumsi@matech-cameroun.com","402","17-04-2025 15:50:03","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004827397","Nlo=
ngkak","","17-04-2025 15:32:00","17-04-2025 15:24:01","17-04-2025 16:09:01"=
,"site went down due to insufficient of rectifiers// Site Stabilized","Delo=
r Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","si=
te went down due to insufficient of rectifiers// Site Stabilized","loic.nou=
msi@matech-cameroun.com","480","17-04-2025 15:32:00","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004827354","OBA=
M NGOLA OCM","","17-04-2025 15:27:06","17-04-2025 15:20:35","17-04-2025 19:=
50:39"," Grid outage, Gen failed to start due to starter faulty, charging a=
lternator faulty, static charger faulty, // starter and static charger repl=
ace, site on Gen","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","=
ACDG - Charging Alternator"," Grid outage, Gen failed to start due to start=
er faulty, charging alternator faulty, static charger faulty, // starter an=
d static charger replace, site on Gen","loic.noumsi@matech-cameroun.com","3=
92","17-04-2025 15:27:06","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0004827204","E=
bogo","","17-04-2025 15:14:50","17-04-2025 14:34:28","17-04-2025 16:05:32",=
"Grid outage, IHS technicia Moise was on site and after his work , he left =
the site on Gen, but the bay had taken an alarm.//bay reset","Siligap Boris=
","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","Grid outage=
, site on Gen, but the bay had taken an alarm. // bay reset","gaelle.njiofa=
ck@matech-cameroun.com","2423","17-04-2025 15:14:50","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004827194","Aka=
k-Nkozoa-MTN-IHS","","17-04-2025 15:10:50","17-04-2025 15:05:55","17-04-202=
5 19:59:01","Grid outage , site down due to malfunction in the energy bay /=
/  Energy bay reset Gen manually started","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Panel Distribution Board","Grid outage , sit=
e down due to malfunction in the energy bay //  Energy bay reset Gen manual=
ly started","loic.noumsi@matech-cameroun.com","297","17-04-2025 15:10:50","=
MATECH CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004827168","Mvo=
g-Betsi","","17-04-2025 15:06:35","17-04-2025 14:56:19","17-04-2025 15:14:1=
4","Grid fluctuation, Site went down because Gen failed to start due to Gri=
d bad voltage // Grid stabilized","Hyemafo Gildas","Grid Supply","Passive",=
"Grid","National Grid - Unstable Grid Supply Issue","	Grid fluctuation, Sit=
e went down because Gen failed to start due to Grid bad voltage // Grid sta=
bilized","loic.noumsi@matech-cameroun.com","617","17-04-2025 15:06:35","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004826972","Tsinga",=
"","17-04-2025 14:40:52","17-04-2025 07:09:22","17-04-2025 12:34:11","Casca=
ded Incident from TTO4931107","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Bactracking Site went down due to cable =
burnt in the dc box that tripped OCM//he replaced ","system","291295","17-0=
4-2025 14:40:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004826971","Bastos B=
ethesda","","17-04-2025 14:40:52","17-04-2025 07:09:22","17-04-2025 12:34:1=
1","Cascaded Incident from TTO4931107","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Bactracking Site went down due =
to cable burnt in the dc box that tripped OCM//he replaced ","system","2912=
96","17-04-2025 14:40:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004826970","Golf Qua=
ter","","17-04-2025 14:40:52","17-04-2025 07:09:22","17-04-2025 12:34:11","=
Cascaded Incident from TTO4931107","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Bactracking Site went down due to c=
able burnt in the dc box that tripped OCM//he replaced ","system","291296",=
"17-04-2025 14:40:52","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0004826892","S=
oa-Sofamac","","17-04-2025 14:39:22","17-04-2025 14:35:55","17-04-2025 15:3=
0:04","Grid outage site went down due to fuel shortage // Refueling done","=
Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Quality","Grid outa=
ge site went down due to fuel shortage // Refueling done","vanel.mbiada@mat=
ech-cameroun.com","208","17-04-2025 14:39:22","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004826846","Mes=
sassi 2","","17-04-2025 14:34:15","17-04-2025 14:17:04","17-04-2025 16:17:2=
8","Site went down because 03/06 rectifiers dysfunctionned // He reset rect=
ifiers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down because 03/06 rectifiers dysfunctionned // He re=
set rectifiers","kouoh.jean@ihstowers.com","8469","17-04-2025 14:34:15","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004826773","C=
amp-Sic-Tsinga","","17-04-2025 14:23:31","17-04-2025 14:14:11","17-04-2025 =
18:36:38","Active//No power issue U=3D50,6V, Site on Grid. The Tx FME Brice=
 Tsague(650214096) from Huawei is informed.","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","NO SPACE to deploy MG // Grid retu=
rn","kouoh.jean@ihstowers.com","562","17-04-2025 14:23:31","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004826721","N=
kozoa","","17-04-2025 14:17:13","17-04-2025 14:14:46","17-04-2025 15:18:57"=
,"Grid outage, site went down due to swap of the GEN on site // End of work=
","Fabrice Pouakam","Equipment Replacement","Passive","Planned Activity","P=
lanned Activity - ACDG Replacement","Grid outage, site went down due to swa=
p of the GEN on site // End of work","edwige.kapawo@matech-cameroun.com","1=
49","17-04-2025 14:17:13","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004826607","Nko=
ulou Carriere carrefourt","","17-04-2025 13:59:16","17-04-2025 13:50:57","1=
7-04-2025 17:17:42","Site went down because 02/05 rectifiers dysfuncionned/=
/ He reset rectifiers ","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because 02/05 rectif=
iers dysfuncionned// He reset rectifiers ","cedric.tiani@matech-cameroun.co=
m","500","17-04-2025 13:59:16","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004826539","N=
kolfon Cimencam","","17-04-2025 13:47:42","17-04-2025 13:44:28","17-04-2025=
 13:50:04","Active//No power issue on site U=3D54,5v site on Gen The TX fme=
 George(697461814) from huawei is informed. Noticed that site is impacted b=
y Afanoya  II(Not manage by HIS)","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","Affected by 3rd Party Site","Acti=
ve//No power issue on site U=3D54,5v site on Gen The TX fme George(69746181=
4) from huawei is informed. Noticed that site is impacted by Afanoya  II(No=
t manage by HIS)","vanel.mbiada@matech-cameroun.com","195","17-04-2025 13:4=
7:42","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0004826516","S=
ous Prefecture","IHS_YND_220, IHS_YND_563, IHS_YND_127","17-04-2025 13:45:4=
7","17-04-2025 07:09:22","17-04-2025 12:34:11","Bactracking Site went down =
due to cable burnt in the dc box that tripped OCM//he replaced ","Fanda Bri=
ce","Equipment Repair","Passive","Infrastructure","Armoured Cable","Bactrac=
king Site went down due to cable burnt in the dc box that tripped OCM//he r=
eplaced ","cedric.tiani@matech-cameroun.com","23786","17-04-2025 13:45:47",=
"MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004826475","Aha=
la Echangeur","","17-04-2025 13:37:02","17-04-2025 13:28:30","17-04-2025 14=
:34:23","Site went down due to insufficient rectifiers on site//He reset it=
 and site on Gen","MINKA NICOLAS","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site went down due to insufficient rectifiers on site//=
He reset it and site on Gen","edwige.kapawo@matech-cameroun.com","513","17-=
04-2025 13:37:02","MATECH CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004826463","Mel=
en Ba'aba","","17-04-2025 13:34:04","17-04-2025 13:30:47","17-04-2025 15:18=
:12","Grid outage, site went down due to Fuel shortage // Refueling done","=
Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outage","
Grid outage, site went down due to Fuel shortage // Refueling done
","edwige.kapawo@matech-cameroun.com","198","17-04-2025 13:34:04","MATECH C=
MR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004826458","Nlo=
ngkak","","17-04-2025 13:32:50","17-04-2025 13:28:40","17-04-2025 14:14:37"=
,"Grid fluctuation,site went down because Gen failed to start due to Grid b=
ad voltage(lavk of one phase)//He bypasse the Grid an site on GEN","Delor T=
elezing","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation,site went down because Gen failed to start due to =
Grid bad voltage(lavk of one phase)//He bypasse the Grid an site on GEN","e=
dwige.kapawo@matech-cameroun.com","251","17-04-2025 13:32:50","MATECH CMR"
"Closed Complete","Site Down","T1739","IHS_YND_691","NOCINC0004826421","Mba=
lla 2 REGIE","","17-04-2025 13:25:29","17-04-2025 13:24:10","17-04-2025 19:=
04:50","Site went down because 01/03 rectifiers dysfuncionned //He reduced =
the load","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectif=
ier Module Overloaded","Site went down because 01/03 rectifiers dysfuncionn=
ed //He reduced the load","vanel.mbiada@matech-cameroun.com","79","17-04-20=
25 13:25:29","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0004826413","NKO=
ABANG NKOLO 3","","17-04-2025 13:24:29","17-04-2025 13:15:02","17-04-2025 1=
4:01:29","Grid outage,Site went down due to gen overload(10KVA, 110A) // he=
 reduced the load and started Gen manually","Mba Lazare Herve","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down d=
ue to gen overload(10KVA, 110A) // he reduced the load and started Gen manu=
ally","vanel.mbiada@matech-cameroun.com","568","17-04-2025 13:24:29","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004826381","S=
atcom","","17-04-2025 13:17:09","17-04-2025 13:15:57","17-04-2025 13:30:57"=
,"Active // No power issue site on Grid with U=3D53,02 V Tx Fme Armand Nges=
tsa (691144412) of huawei is informed","Delor Telezing","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue site on Grid with U=3D53,02 V Tx Fme Armand Ngestsa (6911=
44412) of huawei is informed","vanel.mbiada@matech-cameroun.com","73","17-0=
4-2025 13:17:09","MATECH CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0004826332","Sap=
eur Mimboman","","17-04-2025 13:06:05","17-04-2025 13:03:50","17-04-2025 14=
:53:55","Grid outage site went down due to gen overload(22 kva,318 A)//We r=
educe load and gen manually started","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to g=
en overload(22 kva,318 A)//We reduce load and gen manually started","cedric=
.tiani@matech-cameroun.com","136","17-04-2025 13:06:05","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004826329","N=
yom OCM","","17-04-2025 13:05:17","17-04-2025 13:02:05","17-04-2025 13:05:1=
8","Site went down because Gen failed to start due to Grid bad voltage //he=
 bypassed Grid and started the Gen","Fabrice Pouakam","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Site went down because=
 Gen failed to start due to Grid bad voltage //he bypassed Grid and started=
 the Gen","edwige.kapawo@matech-cameroun.com","194","17-04-2025 13:05:17","=
MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004826279","Sim=
e Building","","17-04-2025 13:00:26","17-04-2025 12:54:10","17-04-2025 14:0=
6:26","site went down due to insufficiency of rectifiers //Site stabilised"=
,"Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module=
","site went down due to insufficiency of rectifiers //Site stabilised","ce=
dric.tiani@matech-cameroun.com","377","17-04-2025 13:00:26","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004826275","NKO=
MKANA ELIZA HOTEL","","17-04-2025 12:59:43","17-04-2025 12:45:19","17-04-20=
25 13:55:43","site went down due to insufficiency of rectifiers //Site stab=
ilised","","Equipment Repair","Passive","Rectifier","Rectifier Module","sit=
e went down due to insufficiency of rectifiers //Site stabilised","cedric.t=
iani@matech-cameroun.com","865","17-04-2025 12:59:43","MATECH CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0004826236","C=
NDH","","17-04-2025 12:54:39","17-04-2025 12:50:45","17-04-2025 13:00:24","=
site manage by CAMUSAT","Paul BIBOUM","Customer Equipment Failure","Active"=
,"Active Equipment Failure","Affected by 3rd Party Site","site manage by CA=
MUSAT","edwige.kapawo@matech-cameroun.com","234","17-04-2025 12:54:39","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004826055","OTELE MT=
N","","17-04-2025 12:22:13","17-04-2025 12:01:32","17-04-2025 12:07:08","Ca=
scaded Incident from TTO4930415","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site ,site on Gen with U=
baie=3D50,3 V Etienne//695033981 is informed.Site impacted by Ngoummou","sy=
stem","1241","17-04-2025 12:22:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004825935","Akono","=
","17-04-2025 12:06:42","17-04-2025 12:01:32","17-04-2025 12:07:08","Cascad=
ed Incident from TTO4930415","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site ,site on Gen with Ubaie=
=3D50,3 V Etienne//695033981 is informed.Site impacted by Ngoummou","system=
","310","17-04-2025 12:06:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004825930","Mom","",=
"17-04-2025 12:05:21","17-04-2025 12:01:32","17-04-2025 12:07:08","Cascaded=
 Incident from TTO4930415","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue on site ,site on Gen with Ubaie=
=3D50,3 V Etienne//695033981 is informed.Site impacted by Ngoummou","system=
","229","17-04-2025 12:05:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004825929","OLAMA","=
","17-04-2025 12:05:21","17-04-2025 12:01:32","17-04-2025 12:07:08","Cascad=
ed Incident from TTO4930415","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site ,site on Gen with Ubaie=
=3D50,3 V Etienne//695033981 is informed.Site impacted by Ngoummou","system=
","229","17-04-2025 12:05:21","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0004825916","Min=
ka","IHS_YND_687, IHS_YND_531, IHS_YND_370, IHS_YND_365","17-04-2025 12:03:=
44","17-04-2025 12:01:32","17-04-2025 12:07:08","No power issue on site ,si=
te on Gen with Ubaie=3D50,3 V Etienne//695033981 is informed.Site impacted =
by Ngoummou","Fanda Brice","Customer Equipment Failure","Active","Active Eq=
uipment Failure","Affected by 3rd Party Site","No power issue on site ,site=
 on Gen with Ubaie=3D50,3 V Etienne//695033981 is informed.Site impacted by=
 Ngoummou","cedric.tiani@matech-cameroun.com","133","17-04-2025 12:03:44","=
MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004825831","SAA=
 2","","17-04-2025 11:46:40","17-04-2025 11:42:31","17-04-2025 11:43:51","r=
unning ticket","Parker Tchoup","Incorrectly Logged Tickets","Error","Error"=
,"Error","running ticket","cedric.tiani@matech-cameroun.com","250","17-04-2=
025 11:46:40","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004825748","O=
lembe-Terminus","","17-04-2025 11:35:47","17-04-2025 11:26:35","17-04-2025 =
11:38:51","Active//No power issue on site U=3D54.7V, site on Grid, Synphori=
en/691316854/ from Huawei is informed","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue on site U=3D54.7V, site on Grid, Synphorien/691316854/ fro=
m Huawei is informed","vanel.mbiada@matech-cameroun.com","554","17-04-2025 =
11:35:47","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004825410","Sim=
e Building","","17-04-2025 10:39:16","17-04-2025 10:35:04","17-04-2025 10:4=
1:26","site went down due to insufficiency of rectifiers //Site stabilised"=
,"Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module=
","site went down due to insufficiency of rectifiers //Site stabilised","ce=
dric.tiani@matech-cameroun.com","253","17-04-2025 10:39:16","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0004825402","Ngo=
um","","17-04-2025 10:38:36","17-04-2025 10:34:25","17-04-2025 11:09:07","S=
ite went down due to work ( PM ) // end of work .","Parker Tchoup","Install=
ation Activity","Passive","Planned Activity","Installation Activity","Site =
went down due to work ( PM ) // end of work .","cedric.tiani@matech-camerou=
n.com","252","17-04-2025 10:38:36","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004825188","N=
KOLMEKONG YDE","","17-04-2025 10:01:36","17-04-2025 09:51:18","17-04-2025 1=
3:40:07","Grid outage,Site went down because Gen failed to start due to Gen=
 battery discharged//He started the GEN with an external battery","Fabrice =
Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery"=
,"Grid outage,Site went down because Gen failed to start due to Gen battery=
 discharged//He started the GEN with an external battery","edwige.kapawo@ma=
tech-cameroun.com","619","17-04-2025 10:01:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004825170","Emana Ly=
cee","","17-04-2025 09:56:19","17-04-2025 09:43:09","17-04-2025 10:01:56","=
Cascaded Incident from TTO4929566","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down before=
 Gen started due to poor Battery Backup//Gen automatically started","system=
","274813","17-04-2025 09:56:19","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004825158","E=
mana lycee 2","IHS_YND_274","17-04-2025 09:55:25","17-04-2025 09:43:09","17=
-04-2025 10:01:56","Grid outage,site went down before Gen started due to po=
or Battery Backup//Gen automatically started","Fabrice Pouakam","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outag=
e,site went down before Gen started due to poor Battery Backup//Gen automat=
ically started","edwige.kapawo@matech-cameroun.com","737","17-04-2025 09:55=
:25","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004825008","MEH=
ANDAN","","17-04-2025 09:30:23","17-04-2025 09:23:16","17-04-2025 14:23:48"=
,"site went down due to insufficiency of rectifiers //Site stabilised","Alb=
ran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","si=
te went down due to insufficiency of rectifiers //Site stabilised","cedric.=
tiani@matech-cameroun.com","428","17-04-2025 09:30:23","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0004824936","Y=
oko OCM","","17-04-2025 09:09:52","17-04-2025 08:47:35","17-04-2025 10:37:0=
9","grid outage,gen ran till fuel shortage//refueling done","Parker Tchoup"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran till=
 fuel shortage//refueling done","cedric.tiani@matech-cameroun.com","1338","=
17-04-2025 09:09:52","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004824912","M=
essassi okolo","","17-04-2025 09:06:58","17-04-2025 09:05:47","17-04-2025 1=
1:40:14","ACTIVE//No power issue on site Ubaie=3D54.5V, site on Grid The TX=
 Fme Synphorien 691316854 of Huewai is informed","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site Ubaie=3D54.5V, site on Grid The TX Fme S=
ynphorien 691316854 of Huewai is informed","edwige.kapawo@matech-cameroun.c=
om","72","17-04-2025 09:06:58","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004824864","Mam=
bine","","17-04-2025 08:57:47","17-04-2025 08:39:32","17-04-2025 09:18:23",=
"Grid outage site went down due to fuel outage//Refueling done","Fanda Bric=
e","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage site went =
down due to fuel outage//Refueling done","cedric.tiani@matech-cameroun.com"=
,"1096","17-04-2025 08:57:47","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004824822","Nko=
ulou Carriere carrefourt","","17-04-2025 08:52:51","17-04-2025 08:43:44","1=
7-04-2025 10:46:49","Site went down because the CB(40A) in PWC tripped the =
rectifiers //He rearmed it","Mba Lazare Herve","Equipment Repair","Passive"=
,"Rectifier","Rectifier - Circuit Breaker","Site went down because the CB(4=
0A) in PWC tripped the rectifiers //He rearmed it","cedric.tiani@matech-cam=
eroun.com","548","17-04-2025 08:52:51","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004824713","N=
goulmekong-Nord","","17-04-2025 08:25:32","17-04-2025 08:13:15","17-04-2025=
 10:31:10","Grid outage,site went down due to PWC malfunctioning//He reset =
it and manually start the Gen","Siligap Boris","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage,site went down due =
to PWC malfunctioning//He reset it and manually start the Gen","edwige.kapa=
wo@matech-cameroun.com","738","17-04-2025 08:25:32","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004824656","A=
wae Ewonkan","","17-04-2025 08:10:42","17-04-2025 08:09:14","17-04-2025 09:=
59:30","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // He reduced the load and started Gen manually=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)IHS SS=
 Alphonse is informed // He reduced the load and started Gen manually","edw=
ige.kapawo@matech-cameroun.com","90","17-04-2025 08:10:42","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004824583","Nko=
zoa","","17-04-2025 07:54:44","17-04-2025 07:53:31","17-04-2025 08:02:57","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// site stabilised","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went=
 down due to gen overload (20kva, 340A) SS HIS Felix bateu is informed and =
confirmed// site stabilised","cedric.tiani@matech-cameroun.com","75","17-04=
-2025 07:54:44","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004824528","N=
goulmekong-Nord","","17-04-2025 07:43:31","17-04-2025 07:41:18","17-04-2025=
 07:46:34","Grid outage,site went down before Gen started due to poor batte=
ry backup","Siligap Boris","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage,site went down before Gen started d=
ue to poor battery backup","edwige.kapawo@matech-cameroun.com","134","17-04=
-2025 07:43:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004824216","MBIMBIM"=
,"","17-04-2025 06:17:12","17-04-2025 05:49:53","17-04-2025 07:00:22","Casc=
aded Incident from TTO4928438","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage ,Gen failed to start due to=
 fuel outage(Refuelin done by Edonde)//Grid return","system","274213","17-0=
4-2025 06:17:12","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004824184","O=
lembe-Terminus","","17-04-2025 06:08:51","17-04-2025 05:59:40","17-04-2025 =
09:45:26","ACTIVE//no power issue Ubaie:54.59V site on Gen, TX fme symphori=
en /650257151 from huawei is informed","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE=
//no power issue Ubaie:54.59V site on Gen, TX fme symphorien /650257151 fro=
m huawei is informed","edwige.kapawo@matech-cameroun.com","553","17-04-2025=
 06:08:51","MATECH CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004824164","N=
gouetou","","17-04-2025 06:00:51","17-04-2025 05:49:53","17-04-2025 07:00:2=
2","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage ,Gen failed to start due to fuel outage(Refuelin don=
e by Edonde)//Grid return","edwige.kapawo@matech-cameroun.com","274213","17=
-04-2025 06:00:51","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004824163","TSI=
NGA VILLAGE 2","","17-04-2025 06:00:35","17-04-2025 05:55:59","17-04-2025 0=
8:40:21","Grid outage,site went down because gen failed to start due to Gen=
 battery faulty//he started the gen manually ","Delor Telezing","Equipment =
Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage,site w=
ent down because gen failed to start due to Gen battery faulty//he started =
the gen manually","gerard.tchangoue@matech-cameroun.com","277","17-04-2025 =
06:00:35","MATECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0004824162","M=
atsari","","17-04-2025 05:59:57","17-04-2025 05:49:53","17-04-2025 07:00:22=
","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Grid outage ,Gen failed to start due to fuel outage(Refuelin done=
 by Edonde)//Grid return","edwige.kapawo@matech-cameroun.com","274214","17-=
04-2025 05:59:57","MATECH CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0004824159","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","17-04-2025 05:59:10","17-=
04-2025 05:49:53","17-04-2025 07:00:22","Grid outage ,Gen failed to start d=
ue to fuel outage(Refueling have to be done by Edonde)//Grid return .","Par=
ker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage ,Gen failed to start due to fuel outage(Refueling have to be d=
one by Edonde)//Grid return .","edwige.kapawo@matech-cameroun.com","558","1=
7-04-2025 05:59:10","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004824075","Nsi=
malen MTN","","17-04-2025 05:29:44","17-04-2025 05:22:28","17-04-2025 05:32=
:19","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","edwige.kapawo@matech-cameroun.com","437",=
"17-04-2025 05:29:44","MATECH CMR"
"Closed Complete","Site Down","T0139","IHS_YND_381","NOCINC0004823954","Bou=
mnyebel","","17-04-2025 04:31:51","17-04-2025 04:28:41","17-04-2025 05:00:5=
4","Grid outage,site went down because Grid contactor did not excited // He=
 excited and site on Grid ","Kemeni Franklin","Equipment Repair","Passive",=
"Control Panel","ATS-AMF Issue","Grid outage,site went down because Grid co=
ntactor did not excited // He excited and site on Grid ","edwige.kapawo@mat=
ech-cameroun.com","191","17-04-2025 04:31:51","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004823613","E=
MANA BILICK CITY","","17-04-2025 03:01:50","17-04-2025 02:54:17","19-04-202=
5 00:43:06","Grid Outage, Site went Down due to Gen Noise (access issue due=
 to landlord) // Grid restoration","Fabrice Pouakam","Access Denial","Lease=
 Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid Outag=
e, Site went Down due to Gen Noise (access issue due to landlord) // Grid r=
estoration","gerard.tchangoue@matech-cameroun.com","455","17-04-2025 03:01:=
50","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004823550","M=
essassi okolo","","17-04-2025 02:38:57","17-04-2025 02:34:49","17-04-2025 0=
2:47:36","ACTIVE//No power issue on site Ubaie=3D54.4V, site on Grid The TX=
 Fme Synphorien 691316854 of Huawei is informed.Noticed impacted by pont em=
mana","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue on site Ubaie=3D=
54.4V, site on Grid The TX Fme Synphorien 691316854 of Huawei is informed.N=
oticed impacted by pont emmana","olivier.kwedi@ihstowers.com","250","17-04-=
2025 02:38:57","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004823217","M=
EHANDAN","","17-04-2025 01:36:13","17-04-2025 01:34:00","17-04-2025 06:57:1=
4","Site went down due to insufficience of rectifiers on site SS IHS Pascal=
ine is informed // Site Stabilised","Albran Byorel","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Site went down due to insufficience o=
f rectifiers on site SS IHS Pascaline is informed // Site Stabilised","oliv=
ier.kwedi@ihstowers.com","135","17-04-2025 01:36:13","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004823203","E=
mana Lycee","","17-04-2025 01:31:54","17-04-2025 01:25:40","17-04-2025 01:4=
5:02","No power issue site on grid with Ubay: 54.4V Symphorien(691316854) f=
rom Huawei is informed.","Fabrice Pouakam","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on grid with Ubay: 54.4V Symphorien(691316854) from Huawei is informed.","e=
dwige.kapawo@matech-cameroun.com","376","17-04-2025 01:31:54","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004822918","E=
mana lycee 2","","17-04-2025 00:43:44","17-04-2025 00:23:36","17-04-2025 09=
:10:48","Active// No power issue, site is on Grid with Ubaie: 56,4 V (burni=
ng dominoes in the DC BOX) ,TX FME Symphorien (650257151) from Huawei is in=
formed","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Active// No power issue, site is on G=
rid with Ubaie: 56,4 V (burning dominoes in the DC BOX) ,TX FME Symphorien =
(650257151) from Huawei is informed","edwige.kapawo@matech-cameroun.com","1=
209","17-04-2025 00:43:44","MATECH CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0004822849","Nlo=
ng Mvolye New","","17-04-2025 00:29:01","17-04-2025 00:20:59","17-04-2025 0=
1:08:49","Grid outage gen ran until fuel shortage//Refueling done(60L)","Pa=
ul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage ge=
n ran until fuel shortage//Refueling done(60L)","gerard.tchangoue@matech-ca=
meroun.com","483","17-04-2025 00:29:01","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004822733","Mes=
sassi 2","","17-04-2025 00:04:57","17-04-2025 00:01:49","17-04-2025 00:10:4=
9","Site went down due to rectifier dysfunction//Site stabilised","Fabrice =
Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site =
went down due to rectifier dysfunction//Site stabilised","gerard.tchangoue@=
matech-cameroun.com","189","17-04-2025 00:04:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004822694","OLAMA","=
","16-04-2025 23:55:28","16-04-2025 23:51:23","16-04-2025 23:57:44","Cascad=
ed Incident from TTO4926846","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) no manager by IHS","system","259985","16-04-2025 23:55:28=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004822695","Minka","=
","16-04-2025 23:55:28","16-04-2025 23:51:23","16-04-2025 23:57:44","Cascad=
ed Incident from TTO4926846","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) no manager by IHS","system","259986","16-04-2025 23:55:28=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004822696","Akono","=
","16-04-2025 23:55:28","16-04-2025 23:51:23","16-04-2025 23:57:44","Cascad=
ed Incident from TTO4926846","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) no manager by IHS","system","259985","16-04-2025 23:55:28=
","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004822689","Mom=
","IHS_YND_687, IHS_YND_371, IHS_YND_365","16-04-2025 23:53:35","16-04-2025=
 23:51:23","16-04-2025 23:57:44","Active//No power issue site on Grid with =
U=3D53,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impa=
cted by Ngoumou(T0169) no manager by IHS","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","Affected by 3rd Party Site",=
"Active//No power issue site on Grid with U=3D53,3 V The FME TX Etienne(695=
033981) From Huawei is informed. Site impacted by Ngoumou(T0169) no manager=
 by IHS","gerard.tchangoue@matech-cameroun.com","133","16-04-2025 23:53:35"=
,"MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004822534","Nko=
lbisson IITA LP","","16-04-2025 23:16:00","16-04-2025 23:13:48","16-04-2025=
 23:19:26","No power issue site on grid Ubaie=3D53,8V Mohamadou 691144435 f=
rom HAUWEI is informed. Notice that site impacted by Nkolbisson 2 OCM (Not =
managing by IHS)","","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue site on grid Ubaie=3D53,8V =
Mohamadou 691144435 from HAUWEI is informed. Notice that site impacted by N=
kolbisson 2 OCM (Not managing by IHS)","gerard.tchangoue@matech-cameroun.co=
m","133","16-04-2025 23:16:00","MATECH CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0004822533","Mai=
son komkana New","","16-04-2025 23:15:54","16-04-2025 22:20:40","16-04-2025=
 22:52:54","Grid outage site went down before gen start due to poor battery=
 backup // Geen manually started","Mboua Thierry","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage site went do=
wn before gen start due to poor battery backup // Geen manually started","l=
udivine.ngamaleu@ihstowers.com","3315","16-04-2025 23:15:54","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004822442","Nko=
ulou Carriere carrefourt","","16-04-2025 22:59:01","16-04-2025 22:39:44","1=
7-04-2025 07:55:05"," access issue due to night, site went down due to CB(4=
0A) in PWC that tripped MTN//HE REARMED","Mba Lazare Herve","Access Denial"=
,"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord"," ac=
cess issue due to night, site went down due to CB(40A) in PWC that tripped =
MTN//HE REARMED","ludivine.ngamaleu@ihstowers.com","1158","16-04-2025 22:59=
:01","MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004822441","c=
hina embassy yde","","16-04-2025 22:58:45","16-04-2025 22:54:18","17-04-202=
5 00:21:28","Grid outage,no space to deploy MGE // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no =
space to deploy MGE // Grid return","edwige.kapawo@matech-cameroun.com","26=
8","16-04-2025 22:58:45","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004822426","A=
wae Escalier","","16-04-2025 22:56:58","16-04-2025 22:53:52","16-04-2025 23=
:33:58","Grid fluctuation,site went down because gen failed to start due to=
 grid bad voltage//Grid Stabilized","Albran Byorel","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation,site we=
nt down because gen failed to start due to grid bad voltage//Grid Stabilize=
d","edwige.kapawo@matech-cameroun.com","188","16-04-2025 22:56:58","MATECH =
CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004822409","Ona=
ngondi (melen bikop)","","16-04-2025 22:54:42","16-04-2025 22:26:27","16-04=
-2025 23:22:27","Hybrid gen site .site went down due to hybrid malfunctionn=
ing//Gen manually started","Fanda Brice","Equipment Repair","Passive","Hybr=
id","Hybrid Module","Hybrid gen site .site went down due to hybrid malfunct=
ionning//Gen manually started","gerard.tchangoue@matech-cameroun.com","1696=
","16-04-2025 22:54:42","MATECH CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0004822323","N=
komkana","","16-04-2025 22:32:42","16-04-2025 22:21:31","16-04-2025 22:48:2=
9","Grid outage,no space to deploy MGE // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage,no space to =
deploy MGE // Grid return","christelle.ngonga@matech-cameroun.com","672","1=
6-04-2025 22:32:42","MATECH CMR"
"Closed Complete","Site Down","T0029","IHS_YND_357","NOCINC0004822276","Sac=
re Coeur Catholic Church","","16-04-2025 22:20:37","16-04-2025 22:09:31","1=
6-04-2025 22:49:31","Grid outage,site went down because Gen ran until fuel =
shortage//Refueling done","Mboua Thierry","Fuel Outage","Passive","Diesel",=
"Diesel Outage","Grid outage,site went down because Gen ran until fuel shor=
tage//Refueling done","franck.nkomot@matech-cameroun.com","667","16-04-2025=
 22:20:37","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004822123","B=
arriere","","16-04-2025 22:01:39","16-04-2025 19:23:14","16-04-2025 20:18:1=
9","Grid fluctuation,Site went down because Gen failed to start due to Grid=
 bad voltage//He bypassed the Grid and site on Gen","Hyemafo Gildas","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation,Site went down because Gen failed to start due to Grid bad voltag=
e//He bypassed the Grid and site on Gen","christelle.ngonga@matech-cameroun=
.com","9506","16-04-2025 22:01:39","MATECH CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0004821794","G=
olf Quater","","16-04-2025 21:03:22","16-04-2025 20:52:16","16-04-2025 22:4=
7:39","Cascaded Incident from TTO4925772","Mboua Thierry","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Cascaded Incident from TTO49=
25772","christelle.ngonga@matech-cameroun.com","299590","16-04-2025 21:03:2=
2","MATECH CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004821788","T=
singa","","16-04-2025 21:02:38","16-04-2025 20:52:16","16-04-2025 22:47:39"=
,"Cascaded Incident from TTO4925772 - Cascade Removed From TTO4925772","Mbo=
ua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Site went down due to insufficient rectifiers//He reduced the load and res=
et it(02 rectifiers needed)","christelle.ngonga@matech-cameroun.com","29958=
9","16-04-2025 21:02:38","MATECH CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0004821783","B=
astos Bethesda","","16-04-2025 21:01:44","16-04-2025 20:52:16","16-04-2025 =
22:47:39","Cascaded Incident from TTO4925772 - Cascade Removed From TTO4925=
772","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Site went down due to insufficient rectifiers//He reduced the loa=
d and reset it(02 rectifiers needed)","christelle.ngonga@matech-cameroun.co=
m","299589","16-04-2025 21:01:44","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004821773","N=
komkana 2","IHS_YND_220, IHS_YND_563, IHS_YND_127","16-04-2025 21:00:35","1=
6-04-2025 20:52:16","16-04-2025 22:47:39","Site went down due to insufficie=
nt rectifiers//He reduced the load and reset it(02 rectifiers needed)","Mbo=
ua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to insufficient rectifiers//He reduced the load and reset =
it(02 rectifiers needed)","christelle.ngonga@matech-cameroun.com","500","16=
-04-2025 21:00:35","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004821767","B=
astos-Nylon","","16-04-2025 20:59:50","16-04-2025 20:52:16","17-04-2025 05:=
51:38","Active// No power issue on site Ubaie: 53.3V site on gEn   TX Fme E=
loundou(652586578) from Huawei is informed","Mboua Thierry","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive// No power issue on site Ubaie: 53.3V site on gEn   TX Fme Eloundou(652=
586578) from Huawei is informed","christelle.ngonga@matech-cameroun.com","3=
021","16-04-2025 20:59:50","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004821529","Fla=
menco","","16-04-2025 20:34:15","16-04-2025 20:02:38","16-04-2025 20:46:38"=
,"Grid outage, site went down because gen failed to start due to gen card f=
aulty// Gen manually started","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen =
failed to start due to gen card faulty// Gen manually started","franck.nkom=
ot@matech-cameroun.com","1898","16-04-2025 20:34:15","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004821365","A=
wae Ewonkan","","16-04-2025 20:09:06","16-04-2025 19:56:39","16-04-2025 21:=
06:25","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid Restored","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid R=
estored","franck.nkomot@matech-cameroun.com","748","16-04-2025 20:09:06","M=
ATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004821325","Bit=
eng-Maetur","","16-04-2025 20:02:20","16-04-2025 20:01:11","16-04-2025 20:4=
6:07","Site went down due to insufficient rectifiers on site//He reset and =
site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to insufficient rectifiers on site//H=
e reset and site on Grid","franck.nkomot@matech-cameroun.com","70","16-04-2=
025 20:02:20","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004821309","N=
kolda","","16-04-2025 19:59:04","16-04-2025 19:56:57","16-04-2025 19:59:13"=
,"Grid fluctuations, Site went down before Gen start due to poor backup // =
Grid return","Albran Byorel","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid fluctuations, Site went down before Gen =
start due to poor backup // Grid return","christelle.ngonga@matech-cameroun=
.com","128","16-04-2025 19:59:04","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004821263","C=
RH-Etoug-Ebe","","16-04-2025 19:57:09","16-04-2025 19:54:01","16-04-2025 20=
:09:44","Grid outage, Site went down due to poor battery backup // Gen star=
t automatically","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down due to poor =
battery backup // Gen start automatically","christelle.ngonga@matech-camero=
un.com","189","16-04-2025 19:57:09","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004821250","O=
lembe-Terminus","","16-04-2025 19:55:45","16-04-2025 19:51:35","16-04-2025 =
23:45:47","ACTIVE//no power issue Ubaie:54.59V site on Gen, TX fme symphori=
en /650257151 from huawei is informed","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE=
//no power issue Ubaie:54.2V site on Gen, TX fme symphorien /650257151 from=
 huawei is informed","christelle.ngonga@matech-cameroun.com","251","16-04-2=
025 19:55:45","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004821215","N=
kozoa","","16-04-2025 19:53:58","16-04-2025 19:51:49","17-04-2025 00:38:57"=
,"Active // No power issue UBaie =3D54,7V site on Grid The FME TX SYMPHORIE=
N (675295205) From Huawei is informed","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue UBaie =3D54,7V site on Grid The FME TX SYMPHORIEN (67529=
5205) From Huawei is informed","christelle.ngonga@matech-cameroun.com","130=
","16-04-2025 19:53:58","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004821142","NKO=
MKANA ELIZA HOTEL","","16-04-2025 19:41:54","16-04-2025 19:34:46","16-04-20=
25 20:46:46","Grid outage,no space to deploy MDG // Grid power return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age,no space to deploy MDG // Grid power return","christelle.ngonga@matech-=
cameroun.com","429","16-04-2025 19:41:54","MATECH CMR"
"Closed Complete","Site Down","T3206","IHS_YND_759","NOCINC0004821132","Nko=
lfoulou Tsinga Village","","16-04-2025 19:40:51","16-04-2025 19:24:33","16-=
04-2025 20:32:33","Grid outage,Site went due to PWC malfunction//He reset i=
t and manually started the Gen","Siligap Boris","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Grid outage,Site went due to P=
WC malfunction//He reset it and manually started the Gen","christelle.ngong=
a@matech-cameroun.com","979","16-04-2025 19:40:51","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004821106","A=
WAE OCM","","16-04-2025 19:37:35","16-04-2025 19:34:28","16-04-2025 23:37:5=
6","Site went down because the PWC OF ZTE dysfonction // He reset the PWC",=
"Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Circuit Breaker Issue","Site went down because the PWC OF ZTE dysfonc=
tion // He reset the PWC","christelle.ngonga@matech-cameroun.com","189","16=
-04-2025 19:37:35","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004821102","B=
ATA Mokolo OCM","","16-04-2025 19:36:57","16-04-2025 19:32:50","16-04-2025 =
22:51:21","Grid only ,  Site went Down due to Grid outge (No space for mobi=
le gen)// awaiting grid restoration","","Grid Supply","Passive","Grid","Nat=
ional Grid - Grid Outage Issue","Grid only ,  Site went Down due to Grid ou=
tge (No space for mobile gen)// awaiting grid restoration","christelle.ngon=
ga@matech-cameroun.com","248","16-04-2025 19:36:57","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004820743","A=
wae Ewonkan","","16-04-2025 18:31:32","16-04-2025 18:22:25","16-04-2025 18:=
46:25","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid Restored","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid R=
estored","christelle.ngonga@matech-cameroun.com","548","16-04-2025 18:31:32=
","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004820730","N=
kolondom","","16-04-2025 18:29:30","16-04-2025 18:25:22","16-04-2025 18:39:=
58","Grid outage,Site went down because Gen failed to start due to Main Gen=
 faulty//Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Generator Faulty","Grid outage,Site went down because Gen fail=
ed to start due to Main Gen faulty//Grid return","christelle.ngonga@matech-=
cameroun.com","249","16-04-2025 18:29:30","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004820721","B=
arriere","","16-04-2025 18:27:25","16-04-2025 18:21:17","16-04-2025 18:49:1=
2","Grid outage, Site down due to gen overlord (20KVA/ load 350A) IHS SS Fe=
lix Zambe is informed and confirmed // Grid restoration","Hyemafo Gildas","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site=
 down due to gen overlord (20KVA/ load 350A) IHS SS Felix Zambe is informed=
 and confirmed // Grid restoration","christelle.ngonga@matech-cameroun.com"=
,"370","16-04-2025 18:27:25","MATECH CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0004820623","OLA=
MA","","16-04-2025 18:14:23","16-04-2025 18:08:16","16-04-2025 20:56:57","N=
o power issue on site, Site on Battery, UBAIE=3D54.9V.( the starting thresh=
old ubaie=3D47.5 VThe TX FME Henri (699949693) from Huawei is informed","Fa=
nda Brice","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","No power issue on site, Site on Battery, UBAIE=3D54.=
9V.( the starting threshold ubaie=3D47.5 VThe TX FME Henri (699949693) from=
 Huawei is informed","franck.nkomot@matech-cameroun.com","368","16-04-2025 =
18:14:23","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004820621","OTE=
LE MTN","","16-04-2025 18:13:30","16-04-2025 18:08:24","16-04-2025 18:14:24=
","Active//No power issue, site is on Grid with Ubaie=3D52,3V,Etienne (6950=
33981) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power =
issue, site is on Grid with Ubaie=3D52,3V,Etienne (695033981) from Huawei i=
s informed","franck.nkomot@matech-cameroun.com","307","16-04-2025 18:13:30"=
,"MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004820616","NYO=
M FACE MAETUR","","16-04-2025 18:12:54","16-04-2025 18:09:44","16-04-2025 1=
8:23:44","Grid outage, Site went down due to installation of the contactors=
 on site//Site stabilized","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","ATS-AMF Issue","Grid outage, Site went down due to installa=
tion of the contactors on site//Site stabilized","franck.nkomot@matech-came=
roun.com","191","16-04-2025 18:12:54","MATECH CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004820531","S=
hell-Nsimeyong","","16-04-2025 17:55:18","16-04-2025 17:50:10","16-04-2025 =
17:50:55","","MINKA NICOLAS","Customer Equipment Failure","Active","Active =
Equipment Failure","Affected by 3rd Party Site","Traffic rerouted by OCM on=
 Mobile BTS not power managed by IHS.","alexandre.kamal@ihstowers.com","309=
","16-04-2025 17:55:18","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004820373","C=
rf-Nkolbisson","","16-04-2025 17:32:24","16-04-2025 17:30:16","16-04-2025 1=
8:07:31","Disjunction in the energie bay due to the site load which increas=
ed there from (we need second depart)// disjunctor rearm","TIENTCHEU NZETCH=
IEU GAEL","Equipment Repair","Passive","Control Panel","Circuit Breaker Tri=
pped","Disjunction in the energie bay due to the site load which increased =
there from (we need second depart)// disjunctor rearm","christelle.ngonga@m=
atech-cameroun.com","129","16-04-2025 17:32:24","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004820343","O=
dza II OCM","","16-04-2025 17:31:26","16-04-2025 17:29:19","16-04-2025 17:3=
7:42","Grid outage gen failed to start due to card GE dysfunctionning//Grid=
 return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid outage gen failed to start due to card GE dysfunctionnin=
g//Grid return","christelle.ngonga@matech-cameroun.com","128","16-04-2025 1=
7:31:26","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004820336","M=
ontee-Des-Soeurs","","16-04-2025 17:30:44","16-04-2025 17:28:33","17-04-202=
5 00:44:23"," Active // No power issue, site is on grid with Ubaie: 53.96V,=
 Mbah hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
"," Active // No power issue, site is on grid with Ubaie: 53.96V, Mbah hosi=
ah(699699694) from Huawei is informed","christelle.ngonga@matech-cameroun.c=
om","132","16-04-2025 17:30:44","MATECH CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004820139","SOA=
 VILLAGE","","16-04-2025 16:57:21","16-04-2025 16:56:16","16-04-2025 16:58:=
16","Active// No power issue, site is on GEN with Ubaie=3D54,8 V TX FME Jul=
ien(693095849) from Huawei is informed","Siligap Boris","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power issue, site is on GEN with Ubaie=3D54,8 V TX FME Julien(69309584=
9) from Huawei is informed","franck.nkomot@matech-cameroun.com","66","16-04=
-2025 16:57:21","MATECH CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0004820026","Odz=
a II","","16-04-2025 16:43:03","16-04-2025 16:25:55","16-04-2025 16:52:55",=
"Grid outage,Site went down because Gen failed to start due to Hybrid syste=
m malfunctioning//He reset it and manually started the gen ","Albran Byorel=
","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid outage,Site w=
ent down because Gen failed to start due to Hybrid system malfunctioning//H=
e reset it and manually started the gen ","christelle.ngonga@matech-camerou=
n.com","1110","16-04-2025 16:43:03","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004820019","Nsi=
malen MTN","","16-04-2025 16:41:53","16-04-2025 16:32:45","16-04-2025 16:41=
:45","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","christelle.ngonga@matech-cameroun.com","5=
49","16-04-2025 16:41:53","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004820013","Mfo=
u EPC","","16-04-2025 16:40:38","16-04-2025 15:51:22","16-04-2025 16:50:07"=
,"Grid outage.site went down because Gen started and stopped with alarm hig=
h temp//He added water and started the Gen manually","Mba Lazare Herve","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Grid outage.site went down because Gen started and stopped with =
alarm high temp//He added water and started the Gen manually","christelle.n=
gonga@matech-cameroun.com","2958","16-04-2025 16:40:38","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004819994","Bar=
riere","","16-04-2025 16:37:59","16-04-2025 16:10:46","16-04-2025 17:42:46"=
,"Grid outage, Site down due to gen overlord (20KVA/ load 350A) IHS SS Feli=
x Zambe is informed and confirmed // Grid restoration","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site d=
own due to gen overlord (20KVA/ load 350A) IHS SS Felix Zambe is informed a=
nd confirmed // Grid restoration","christelle.ngonga@matech-cameroun.com","=
1724","16-04-2025 16:37:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004819968","Mimboman=
4","","16-04-2025 16:33:06","16-04-2025 16:25:02","16-04-2025 17:27:02","Ca=
scaded Incident from TTO4923672","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause Gen failed to start due to bad voltage// Gen started Mannually","sys=
tem","337018","16-04-2025 16:33:06","MATECH CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004819939","Nko=
lo II New","IHS_YND_266","16-04-2025 16:29:09","16-04-2025 16:25:02","16-04=
-2025 17:27:02","Grid fluctuation, site went down because Gen failed to sta=
rt due to bad voltage// Gen started Mannually","Mba Lazare Herve","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, site went down because Gen failed to start due to bad voltage// Gen=
 started Mannually","loic.noumsi@matech-cameroun.com","248","16-04-2025 16:=
29:09","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004819787","N=
kolfon Cimencam","","16-04-2025 15:58:49","16-04-2025 15:51:38","16-04-2025=
 15:55:05","Active//No power issue, Site on Grid. Notice that it is impacte=
d by Afanoya II The Tx FME Fulbert from Huawei is informed","Hyemafo Gildas=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","Active//No power issue, Site on Grid. Notice that it is impac=
ted by Afanoya II The Tx FME Fulbert from Huawei is informed","christelle.n=
gonga@matech-cameroun.com","432","16-04-2025 15:58:49","MATECH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0004819751","S=
apeur Mimboman","","16-04-2025 15:53:10","16-04-2025 15:51:04","16-04-2025 =
16:20:41","Grid outage site went down due to gen overload(22 kva,318 A)//We=
 reduce ,  Grid restoration","Mba Lazare Herve","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage site went down due to gen overl=
oad(22 kva,318 A)//We reduce ,=20
Grid restoration","christelle.ngonga@matech-cameroun.com","127","16-04-2025=
 15:53:10","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004819720","M=
essassi 2","","16-04-2025 15:47:46","16-04-2025 15:46:39","16-04-2025 16:56=
:40","Site went down because 02/06 rectifiers dysfuncionned// He reset rect=
ifiers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down because 02/06 rectifiers dysfuncionned// He rese=
t rectifiers","christelle.ngonga@matech-cameroun.com","69","16-04-2025 15:4=
7:46","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004819698","M=
arche Odza","","16-04-2025 15:45:42","16-04-2025 14:37:31","16-04-2025 16:2=
9:31","Hybrid_GEN,  Site went down because Gen battery went faulty // Start=
ed the Gen with external battery to rescue site ","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Generator Battery","Hybrid_GEN,  Gen=
 battery went faulty // Started the Gen with external battery to rescue sit=
e ","alexandre.kamal@ihstowers.com","4093","16-04-2025 15:45:42","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004819677","OLAMA","=
","16-04-2025 15:42:15","16-04-2025 15:17:50","16-04-2025 16:38:03","Cascad=
ed Incident from TTO4923363","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site down due to work done by Brice Fanda(6=
57108549): PM Work//End of work","system","269006","16-04-2025 15:42:15","M=
ATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004819662","Ako=
no","IHS_YND_687","16-04-2025 15:40:57","16-04-2025 15:17:50","16-04-2025 1=
6:38:03","Site down due to work done by Brice Fanda(657108549): PM Work//En=
d of work","Fanda Brice","Installation Activity","Passive","Planned Activit=
y","Installation Activity","Site down due to work done by Brice Fanda(65710=
8549): PM Work//End of work","christelle.ngonga@matech-cameroun.com","1388"=
,"16-04-2025 15:40:57","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0004819586","M=
fou EPC","","16-04-2025 15:38:14","16-04-2025 14:55:01","16-04-2025 15:38:4=
4","Grid outage.site went down due to gen failed to start//Grid return","Mb=
a Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Grid outage.site went down due to gen failed to start//Grid return","c=
hristelle.ngonga@matech-cameroun.com","2594","16-04-2025 15:38:14","MATECH =
CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0004819142","O=
kolo","","16-04-2025 14:31:34","16-04-2025 14:25:23","16-04-2025 15:28:37",=
"Site went down Gen failed to start due to Grid bad voltage(lack of 02 phas=
es on site)// He did a bridge on the Good phase","Fabrice Pouakam","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Site went=
 down Gen failed to start due to Grid bad voltage(lack of 02 phases on site=
)// He did a bridge on the Good phase","gaelle.njiofack@matech-cameroun.com=
","372","16-04-2025 14:31:34","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004819123","Sim=
e Building","","16-04-2025 14:25:50","16-04-2025 14:19:46","16-04-2025 14:2=
5:46","Grid outage; site went down due to insufficiency of rectifiers // Gr=
id return","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Grid outage; site went down due to insufficiency of rectifiers=
 // Grid return","loic.noumsi@matech-cameroun.com","365","16-04-2025 14:25:=
50","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004819058","N=
koabang2","","16-04-2025 14:16:32","16-04-2025 14:04:23","16-04-2025 15:10:=
56","Grid outage .site went down due to bad grid voltage//We bypass grid an=
d gen manually started ","Mba Lazare Herve","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid outage .site went down due =
to bad grid voltage//We bypass grid and gen manually started ","gaelle.njio=
fack@matech-cameroun.com","730","16-04-2025 14:16:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004818948","Scalom-I=
HS","","16-04-2025 13:46:10","16-04-2025 13:35:08","16-04-2025 13:35:25","C=
ascaded Incident from TTO4922534","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage.gen ran until fuel shortage//Refuelin=
g done","system","662","16-04-2025 13:46:10","MATECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004818914","Sca=
lom","IHS_YND_505","16-04-2025 13:44:20","16-04-2025 13:35:08","16-04-2025 =
15:19:29","Grid outage.gen ran until fuel shortage//Refueling done","Paul B=
IBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ra=
n until fuel shortage//Refueling done","loic.noumsi@matech-cameroun.com","5=
53","16-04-2025 13:44:20","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0004818890","Val=
lee Bastos MTN","","16-04-2025 13:39:13","16-04-2025 12:48:42","16-04-2025 =
15:16:58","site down due to rectifer issue // he reseted it","Mboua Thierry=
","Equipment Repair","Passive","Rectifier","Rectifier Module","site down du=
e to rectifer issue // he reseted it","loic.noumsi@matech-cameroun.com","30=
32","16-04-2025 13:39:13","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0004818654","N=
simalen OCM","","16-04-2025 13:00:11","16-04-2025 12:48:40","16-04-2025 15:=
29:29","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","site down due to energy bay faullty // He made power reset",=
"gaelle.njiofack@matech-cameroun.com","278018","16-04-2025 13:00:11","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004818632","N=
kozoa","","16-04-2025 12:57:40","16-04-2025 12:53:28","16-04-2025 16:21:20"=
,"site down due to fuel shortage // refuelling made","Fabrice Pouakam","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Fuel Leakage","site down due to=
 fuel shortage // refuelling made","gaelle.njiofack@matech-cameroun.com","2=
54","16-04-2025 12:57:40","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004818604","N=
kolda","IHS_YND_327","16-04-2025 12:52:54","16-04-2025 12:48:40","16-04-202=
5 15:29:29","site down due to energy bay faullty // He made power reset","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Ov=
erloaded","site down due to energy bay faullty // He made power reset","gae=
lle.njiofack@matech-cameroun.com","255","16-04-2025 12:52:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004818460","Bastos B=
ethesda","","16-04-2025 12:39:39","16-04-2025 11:54:42","16-04-2025 14:03:3=
2","Cascaded Incident from TTO4921792","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid, outage , No MG to deploy =
on site // Grid return","system","274210","16-04-2025 12:39:39","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004818461","Tsinga",=
"","16-04-2025 12:39:39","16-04-2025 11:54:42","16-04-2025 14:03:32","Casca=
ded Incident from TTO4921792","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid, outage , No MG to deploy on site /=
/ Grid return","system","274211","16-04-2025 12:39:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004818462","Entree C=
ite Verte","","16-04-2025 12:39:39","16-04-2025 11:54:42","16-04-2025 14:03=
:32","Cascaded Incident from TTO4921792","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid, outage , No MG to deploy =
on site // Grid return","system","274211","16-04-2025 12:39:39","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0004818458","Bastos-N=
ylon","","16-04-2025 12:39:38","16-04-2025 11:54:42","16-04-2025 14:03:32",=
"Cascaded Incident from TTO4921792","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid, outage , No MG to deploy on =
site // Grid return","system","274209","16-04-2025 12:39:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004818456","Nkomkana=
 2","","16-04-2025 12:39:38","16-04-2025 11:54:42","16-04-2025 14:03:32","C=
ascaded Incident from TTO4921792","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid, outage , No MG to deploy on si=
te // Grid return","system","274209","16-04-2025 12:39:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0004818459","BATA Mok=
olo OCM","","16-04-2025 12:39:38","16-04-2025 11:54:42","16-04-2025 14:03:3=
2","Cascaded Incident from TTO4921792","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid, outage , No MG to deploy on site // Gr=
id return","system","274209","16-04-2025 12:39:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004818457","Nkomkana=
","","16-04-2025 12:39:38","16-04-2025 11:54:42","16-04-2025 14:03:32","Cas=
caded Incident from TTO4921792","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid, outage , No MG to deploy on site // Grid retu=
rn","system","274210","16-04-2025 12:39:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004818455","Golf Qua=
ter","","16-04-2025 12:39:37","16-04-2025 11:54:42","16-04-2025 14:03:32","=
Cascaded Incident from TTO4921792","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid, outage , No MG to deploy on s=
ite // Grid return","system","274208","16-04-2025 12:39:37","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004818353","Aka=
k-Nkozoa-MTN-IHS","","16-04-2025 12:17:44","16-04-2025 12:08:26","16-04-202=
5 13:40:04","Fme is informed and said malfunction in the energy bay // bay =
reset","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","fme is informed and said malfunction in the energy ba=
y // bay reset","loic.noumsi@matech-cameroun.com","559","16-04-2025 12:17:4=
4","MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004818269","C=
ite-Verte","IHS_YND_220, IHS_YND_138, IHS_YND_200, IHS_YND_126, IHS_YND_559=
, IHS_YND_563, IHS_YND_127, IHS_YND_543","16-04-2025 12:09:05","16-04-2025 =
11:54:42","16-04-2025 14:03:32","Grid, outage , No MG to deploy on site // =
Grid return","","Grid Supply","Passive","Grid","National Grid - Grid Outage=
 Issue","Grid, outage , No MG to deploy on site // Grid return","gaelle.nji=
ofack@matech-cameroun.com","864","16-04-2025 12:09:05","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004818072","Ebo=
go","","16-04-2025 11:29:06","16-04-2025 11:11:48","16-04-2025 11:44:01","	=
Active// No Power issue on site Ubaie 56V site on Grid, Julien /693095849 f=
rom Huawei is informed","Siligap Boris","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","	Active// No Power issu=
e on site Ubaie 56V site on Grid, Julien /693095849 from Huawei is informed=
","loic.noumsi@matech-cameroun.com","1039","16-04-2025 11:29:06","MATECH CM=
R"
"Closed Complete","Site Down","T1579","IHS_YND_480","NOCINC0004817975","Sic=
 Cite Verte Matgenie","","16-04-2025 11:13:18","16-04-2025 11:01:39","16-04=
-2025 15:44:49","Grid outage .no space to deploy to deploy mobile gen//Grid=
 return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Iss=
ue","Grid outage .no space to deploy to deploy mobile gen//Grid return","ge=
rard.tchangoue@matech-cameroun.com","700","16-04-2025 11:13:18","MATECH CMR=
"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004817964","AKA=
K Nkozoa","","16-04-2025 11:10:24","16-04-2025 11:00:36","08-05-2025 17:56:=
55","Access issue due to Landlord, the supervisor Alphonse , Our RM Willy a=
nd Our Do Andre Eko are informed//Grid install","Fabrice Pouakam","Access D=
enial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord=
","Access issue due to Landlord, the supervisor Alphonse , Our RM Willy and=
 Our Do Andre Eko are informed//Grid install","gerard.tchangoue@matech-came=
roun.com","589","16-04-2025 11:10:24","MATECH CMR"
"Closed Complete","Site Down","T0460","IHS_YND_201","NOCINC0004817872","Cit=
e Verte","","16-04-2025 10:58:29","16-04-2025 10:47:20","16-04-2025 11:42:0=
4","Grid outage, No MG to deploy site // Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, No MG to dep=
loy site // Grid return","edwige.kapawo@matech-cameroun.com","670","16-04-2=
025 10:58:29","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004817861","Ona=
ngondi (melen bikop)","","16-04-2025 10:56:24","16-04-2025 10:27:12","16-04=
-2025 11:17:02","Grid outage gen failed to start due to automation failure/=
/Gen manually started ","Fanda Brice","Equipment Repair","Passive","Control=
 Panel","ATS-AMF Issue","Grid outage gen failed to start due to automation =
failure//Gen manually started ","gerard.tchangoue@matech-cameroun.com","175=
3","16-04-2025 10:56:24","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004817832","Nko=
g-Edzen","","16-04-2025 10:49:14","16-04-2025 10:41:41","16-04-2025 10:42:3=
1","No power issue on site, site on Battery with U=3D52v The Tx Fme Gregoir=
e (654547479) from Huawei is informed. ","Parker Tchoup","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site, site on Battery with U=3D52v The Tx Fme Gregoire (6545474=
79) from Huawei is informed. ","gerard.tchangoue@matech-cameroun.com","454"=
,"16-04-2025 10:49:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004817825","SOA UNIV=
ERSITY STADIUM","","16-04-2025 10:48:27","16-04-2025 08:34:55","16-04-2025 =
14:01:15","Wrongly ticket","Siligap Boris","Incorrectly Logged Tickets","Er=
ror","Error","Error","Wrongly ticket","system","8012","16-04-2025 10:48:27"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004817823","Bastos B=
ethesda","","16-04-2025 10:48:27","16-04-2025 08:34:55","16-04-2025 10:34:0=
8","Cascaded Incident from TTO4920485","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, No MG to deploy si=
te // Grid return","system","271840","16-04-2025 10:48:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004817824","Nomayos-=
IHS","","16-04-2025 10:48:27","16-04-2025 08:34:55","16-04-2025 08:35:07","=
Wrongly ticket","Fanda Brice","Incorrectly Logged Tickets","Error","Error",=
"Error","Wrongly ticket","system","8012","16-04-2025 10:48:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0004817822","BATA Mok=
olo OCM","","16-04-2025 10:48:26","16-04-2025 08:34:55","16-04-2025 10:34:0=
8","Cascaded Incident from TTO4920485","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid outage, No MG to deploy site // Grid re=
turn","system","271839","16-04-2025 10:48:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_120","NOCINC0004817821","Sapeur M=
imboman","","16-04-2025 10:48:26","16-04-2025 08:34:55","16-04-2025 14:40:5=
9","Grid outage site went down due to gen overload(22 kva,318 A)//We reduce=
 load and gen manually started ","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage site went down due to gen o=
verload(22 kva,318 A)//We reduce load and gen manually started ","system","=
22943","16-04-2025 10:48:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004817788","Crf-Mban=
kolo-IHS","","16-04-2025 10:45:54","16-04-2025 09:31:27","16-04-2025 10:20:=
16","Cascaded Incident from TTO4921181","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down su=
e to fuel shortage // Refueling done","system","268194","16-04-2025 10:45:5=
4","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004817736","J=
-Vespa","IHS_YND_574, IHS_YND_544","16-04-2025 10:37:50","16-04-2025 09:31:=
27","16-04-2025 10:20:16","Grid outage, site went down sue to fuel shortage=
 // Refueling done","Mboua Thierry","Fuel Outage","Passive","Diesel","Diese=
l Outage","Grid outage, site went down sue to fuel shortage // Refueling do=
ne","edwige.kapawo@matech-cameroun.com","3984","16-04-2025 10:37:50","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0004817673","C=
arrefourt Nkomo","","16-04-2025 10:24:33","16-04-2025 09:46:22","16-04-2025=
 11:30:32","Grid outage gen ran until fuel shortage//Refueling done","Mba L=
azare Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage =
gen ran until fuel shortage//Refueling done","edwige.kapawo@matech-cameroun=
.com","2292","16-04-2025 10:24:33","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004817655","Beh=
ind P T school Yde","","16-04-2025 10:23:19","16-04-2025 10:18:07","16-04-2=
025 11:56:07","Grid outage.gen failed to start due to poor backup//Gen manu=
ally started ","Paul BIBOUM","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage.gen failed to start due to poor b=
ackup//Gen manually started ","gerard.tchangoue@matech-cameroun.com","313",=
"16-04-2025 10:23:19","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004817621","A=
wae Ewonkan","","16-04-2025 10:17:38","16-04-2025 10:14:27","16-04-2025 10:=
21:24","	Grid outage site went down due to Gen Overload (20Kva, Iload 225 A=
)IHS SS Alphonse is informed // Grid Restored","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","	Grid outage site went down =
due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid=
 Restored","edwige.kapawo@matech-cameroun.com","192","16-04-2025 10:17:38",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0004817611","M=
adagascar-Yde-New","","16-04-2025 10:16:27","16-04-2025 10:11:16","16-04-20=
25 15:32:16","Grid only site , site down due to Grid outage, No space to de=
ploy a MG // Grid restoration","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid only site , site down due to Grid outage, N=
o space to deploy a MG // Grid restoration","edwige.kapawo@matech-cameroun.=
com","312","16-04-2025 10:16:27","MATECH CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004817560","M=
ontesquieux","","16-04-2025 10:10:06","16-04-2025 10:07:42","16-04-2025 11:=
45:23","site went down due to disfunctionning of rectifiers // Rectifiers r=
eset","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","site went down due to disfunctionning of rectifiers // Rectifiers res=
et","edwige.kapawo@matech-cameroun.com","145","16-04-2025 10:10:06","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004817509","C=
omplexe-BEAC","","16-04-2025 10:01:45","16-04-2025 09:31:33","16-04-2025 09=
:58:33","Site went down due to CB(100A) of rectifier disjuncted //We rearme=
d CB and site on grid","Albran Byorel","Equipment Repair","Passive","Rectif=
ier","Rectifier - Circuit Breaker","Site went down due to CB(100A) of recti=
fier disjuncted //We rearmed CB and site on grid","kouoh.jean@ihstowers.com=
","1813","16-04-2025 10:01:45","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004817452","M=
EHANDAN","","16-04-2025 09:50:39","16-04-2025 09:47:57","16-04-2025 16:49:5=
7","Site went down due to insufficiency of rectifiers on site SS IHS Pascal=
ine is confirm // Site stabilised","Albran Byorel","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Site went do=
wn due to insufficiency of rectifiers on site SS IHS Pascaline is confirm /=
/ Site stabilised","kouoh.jean@ihstowers.com","164","16-04-2025 09:50:39","=
MATECH CMR"
"Closed Complete","Site Down","CTR_122","IHS_YND_230","NOCINC0004817421","M=
eyong-Meyeme","","16-04-2025 09:46:20","16-04-2025 09:44:48","16-04-2025 10=
:34:31","Grid outage.gen failed to start due to battery GE discharged//Gen =
manually started with external battery","TIENTCHEU NZETCHIEU GAEL","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage.gen=
 failed to start due to battery GE discharged//Gen manually started with ex=
ternal battery","edwige.kapawo@matech-cameroun.com","93","16-04-2025 09:46:=
20","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004817313","E=
kombitie","","16-04-2025 09:29:21","16-04-2025 09:03:39","16-04-2025 10:07:=
19","Active: no power issue, site is on Gen with Ubaie=3D55V, Symphorien(65=
0257151) from huawei is informed	","Fabrice Pouakam","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Active: n=
o power issue, site is on Gen with Ubaie=3D55V, Symphorien(650257151) from =
huawei is informed	","edwige.kapawo@matech-cameroun.com","1544","16-04-2025=
 09:29:21","MATECH CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0004817282","Odz=
a II","","16-04-2025 09:24:13","16-04-2025 09:12:04","16-04-2025 13:52:04",=
"Grid outage, Site went down due to Fuel shortage // Refueling done","Albra=
n Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, Si=
te went down due to Fuel shortage // Refueling done","franck.nkomot@matech-=
cameroun.com","2525","16-04-2025 09:24:13","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004817277","Nko=
ulou Carriere carrefourt","","16-04-2025 09:23:22","16-04-2025 09:03:13","1=
6-04-2025 11:58:48","Grid outage gen failed to start due to automation malf=
unctionning//Gen manually started ","Mba Lazare Herve","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid outage gen failed to start d=
ue to automation malfunctionning//Gen manually started ","franck.nkomot@mat=
ech-cameroun.com","1211","16-04-2025 09:23:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004817141","Nkomkana=
","","16-04-2025 08:59:31","16-04-2025 08:34:55","16-04-2025 10:34:08","Cas=
caded Incident from TTO4920485","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage, No MG to deploy site // Grid return","=
system","271838","16-04-2025 08:59:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004817140","Nkomkana=
 2","","16-04-2025 08:59:30","16-04-2025 08:34:55","16-04-2025 10:34:08","C=
ascaded Incident from TTO4920485","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, No MG to deploy site //=
 Grid return","system","271840","16-04-2025 08:59:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004817128","Entree C=
ite Verte","","16-04-2025 08:58:19","16-04-2025 08:34:55","16-04-2025 10:34=
:08","Cascaded Incident from TTO4920485","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, No MG to deploy si=
te // Grid return","system","271840","16-04-2025 08:58:19","MATECH CMR"
"Closed Complete","Warning","T0046","IHS_YND_191","NOCINC0004817116","Mball=
a II","","16-04-2025 08:56:30","","","site alarm due to eneo contactor faul=
ty // he will replace contactor, site on gen","Delor Telezing","Warning","W=
arning","POWER","Warning - Low Voltage","site alarm due to eneo contactor f=
aulty // he will replace contactor, site on gen","franck.nkomot@matech-came=
roun.com","2837","16-04-2025 08:56:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004817113","Tsinga",=
"","16-04-2025 08:56:04","16-04-2025 08:34:55","16-04-2025 10:34:08","Casca=
ded Incident from TTO4920483 - Cascade Removed From TTO4920483","Mboua Thie=
rry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid o=
utage, No MG to deploy site // Grid return","system","271837","16-04-2025 0=
8:56:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004817111","Golf Qua=
ter","","16-04-2025 08:56:04","16-04-2025 08:34:55","16-04-2025 10:34:08","=
Cascaded Incident from TTO4920483 - Cascade Removed From TTO4920483","Mboua=
 Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage, No MG to deploy site // Grid return","system","271837","16-04-2=
025 08:56:04","MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004817087","C=
ite-Verte","IHS_YND_220, IHS_YND_138, IHS_YND_200, IHS_YND_126, IHS_YND_559=
, IHS_YND_563, IHS_YND_127, IHS_YND_543","16-04-2025 08:51:55","16-04-2025 =
08:34:55","16-04-2025 11:39:08","Grid outage, No MG to deploy site // Grid =
return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid outage, No MG to deploy site // Grid return","franck.nkomot@matech=
-cameroun.com","1021","16-04-2025 08:51:55","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004817085","B=
astos-Nylon","","16-04-2025 08:51:14","16-04-2025 08:34:55","16-04-2025 10:=
34:08","our technician thierry is on the way ETA 09:45 AM","Mboua Thierry",=
"Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage=
, No MG to deploy site // Grid return","edwige.kapawo@matech-cameroun.com",=
"271838","16-04-2025 08:51:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004817070","Abang","=
","16-04-2025 08:47:40","16-04-2025 08:29:48","16-04-2025 11:14:22","Cascad=
ed Incident from TTO4920444","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site sent down due to CB(32 A)  gen di=
sjuncted //We rearmed CB site on gen ","system","279171","16-04-2025 08:47:=
40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0004817067","Carrefou=
rt Nkomo","","16-04-2025 08:46:26","16-04-2025 08:27:27","16-04-2025 09:04:=
04","Cascaded Incident from TTO4920378","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, Gen stopped du=
e to Alarm High temp // Water add and Gen start manually","system","1221651=
","16-04-2025 08:46:26","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004817059","N=
kolangaa","IHS_YND_290","16-04-2025 08:44:08","16-04-2025 08:29:48","16-04-=
2025 13:31:53","No power issue site On gen with U=3D54v Notice that we have=
 disjunction at OCM Equipements Lionnel Steeve from Huawei is informed site=
 up at 11:14 AM","Mba Lazare Herve","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site On gen =
with U=3D54v Notice that we have disjunction at OCM Equipements Lionnel Ste=
eve from Huawei is informed site up at 11:14 AM","franck.nkomot@matech-came=
roun.com","861","16-04-2025 08:44:08","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0004816987","Nko=
mo","IHS_YND_174","16-04-2025 08:31:38","16-04-2025 08:27:27","16-04-2025 0=
9:08:44","Grid outage, Gen stopped due to Alarm High temp // Water add and =
Gen start manually","Mba Lazare Herve","Equipment Repair","Passive","ACDG G=
en","Gen Temp High","Grid outage, Gen stopped due to Alarm High temp // Wat=
er add and Gen start manually","edwige.kapawo@matech-cameroun.com","777","1=
6-04-2025 08:31:38","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004816820","Ebo=
go","","16-04-2025 07:50:25","16-04-2025 07:46:16","16-04-2025 08:09:19","A=
ctive// No Power issue on site Ubaie 56V site on Grid, Julien /693095849 fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power issue =
on site Ubaie 56V site on Grid, Julien /693095849 from Huawei is informed",=
"franck.nkomot@matech-cameroun.com","250","16-04-2025 07:50:25","MATECH CMR=
"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0004816699","K=
amajou Building","","16-04-2025 07:28:53","16-04-2025 07:21:17","16-04-2025=
 07:30:55","Grid outage, Site went down due to Poor battery backup  // Grid=
 return","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage, Site went down due to Poor battery bac=
kup  // Grid return","edwige.kapawo@matech-cameroun.com","491","16-04-2025 =
07:28:53","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004816676","J=
-Vespa","IHS_YND_574, IHS_YND_544","16-04-2025 07:20:43","16-04-2025 06:33:=
24","16-04-2025 07:44:10","Grid outage, site went down sue to fuel shortage=
 // Grid return","Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down sue to fuel shortage // Grid return","g=
erard.tchangoue@matech-cameroun.com","2840","16-04-2025 07:20:43","MATECH C=
MR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004816643","Ako=
no","IHS_YND_687","16-04-2025 07:14:07","16-04-2025 06:56:51","16-04-2025 0=
7:31:04"," Grid outage, Site went down due to Dysfunctioning of Gen (Old Ge=
n) // Gen start manually.","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","
Grid outage, Site went down due to Dysfunctioning of Gen (Old Gen) // Gen s=
tart manually.
","edwige.kapawo@matech-cameroun.com","1037","16-04-2025 07:14:07","MATECH =
CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0004816633","OLA=
MA","","16-04-2025 07:12:10","16-04-2025 06:56:51","16-04-2025 07:31:04",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","
Grid outage, Site went down due to Dysfunctioning of Gen (Old Gen) // Gen s=
tart manually.
","edwige.kapawo@matech-cameroun.com","277624","16-04-2025 07:12:10","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004816597","Jean Ves=
pa 2","","16-04-2025 07:06:06","16-04-2025 06:33:24","16-04-2025 10:20:16",=
"Cascaded Incident from TTO4919890","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down sue to=
 fuel shortage // Grid return","system","279064","16-04-2025 07:06:06","MAT=
ECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004816561","Crf=
-Mbankolo-IHS","","16-04-2025 06:58:43","16-04-2025 06:33:24","16-04-2025 0=
7:54:38","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid outage, site went down sue to fuel shortage // Grid r=
eturn","gerard.tchangoue@matech-cameroun.com","279064","16-04-2025 06:58:43=
","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0004816551","O=
kola OCM","","16-04-2025 06:55:31","16-04-2025 06:13:18","16-04-2025 11:08:=
30","Grid outage, Site wen down due to fuel shortage // Refueling done","TI=
ENTCHEU NZETCHIEU GAEL","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage, Gen failed to start due to battery Gen faulty, // Gen started w=
ith Battery Backup","gerard.tchangoue@matech-cameroun.com","2535","16-04-20=
25 06:55:31","MATECH CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004816548","Jea=
n Vespa","IHS_YND_544, IHS_YND_574","16-04-2025 06:54:31","16-04-2025 06:50=
:05","16-04-2025 07:54:38","Grid outage, site went down sue to fuel shortag=
e // Grid return","Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage, site went down sue to fuel shortage // Grid return","=
gerard.tchangoue@matech-cameroun.com","267","16-04-2025 06:54:31","MATECH C=
MR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0004816521","Oko=
la","","16-04-2025 06:52:09","16-04-2025 06:48:59","16-04-2025 11:58:55","G=
rid outage, Gen failed to start due to battery Gen faulty, // Gen started w=
ith Battery Backup","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Generator Battery","Grid outage, Gen failed to start du=
e to battery Gen faulty, // Gen started with Battery Backup","gerard.tchang=
oue@matech-cameroun.com","191","16-04-2025 06:52:09","MATECH CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0004816408","M=
atomb","","16-04-2025 06:36:44","16-04-2025 06:30:27","16-04-2025 07:54:38"=
,"Grid outage, site went down because gen failed to start with false alarm =
Emergency stop  // He started gen manually, site on gen","Kemeni Franklin",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
, site went down because gen failed to start with false alarm Emergency sto=
p  // He started gen manually, site on gen","edwige.kapawo@matech-cameroun.=
com","377","16-04-2025 06:36:44","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004816399","E=
vodoula OCM","","16-04-2025 06:35:26","16-04-2025 05:42:10","16-04-2025 06:=
44:12","No power issue site and with Ubaie:54.2 V site on Gen The FME TX Mo=
hamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue site and with Ubaie:54.2 V site on Gen The FME TX M=
ohamadou/658791013 //From Huawei is informed","edwige.kapawo@matech-camerou=
n.com","3197","16-04-2025 06:35:26","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004816312","Nsi=
malen MTN","","16-04-2025 06:01:40","16-04-2025 05:59:25","16-04-2025 06:08=
:25","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","gerard.tchangoue@matech-cameroun.com","13=
6","16-04-2025 06:01:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004816221","Abang","=
","16-04-2025 05:34:58","16-04-2025 05:31:27","16-04-2025 07:41:01","Cascad=
ed Incident from TTO4919528","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","GRid outage site went down due to Gen =
GB tripped causing by lightning//Cb reamed","system","275706","16-04-2025 0=
5:34:58","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004816220","N=
kolangaa","IHS_YND_290","16-04-2025 05:33:42","16-04-2025 05:31:27","16-04-=
2025 07:41:08","GRid outage site went down due to Gen GB tripped causing by=
 lightning//Cb reamed","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - Load Breaker","GRid outage site went down due to Gen GB trip=
ped causing by lightning//Cb reamed","edwige.kapawo@matech-cameroun.com","1=
36","16-04-2025 05:33:42","MATECH CMR"
"Closed Complete","Site Down","T0139","IHS_YND_381","NOCINC0004816211","Bou=
mnyebel","","16-04-2025 05:28:35","16-04-2025 05:26:27","16-04-2025 06:00:1=
1","Grid outage,site went down because Grid contactor did not excited // He=
 excited and site on Grid ","Kemeni Franklin","Equipment Repair","Passive",=
"Control Panel","ATS-AMF Issue","Grid outage,site went down because Grid co=
ntactor did not excited // He excited and site on Grid ","edwige.kapawo@mat=
ech-cameroun.com","129","16-04-2025 05:28:35","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0004816123","Nko=
mo stade","","16-04-2025 05:12:18","16-04-2025 05:03:59","16-04-2025 06:41:=
29","Grid outage.gen failed to start due to card GE dysfunctionned//We rese=
t card GE and gen manually started ","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to star=
t due to card GE dysfunctionned//We reset card GE and gen manually started =
","gerard.tchangoue@matech-cameroun.com","500","16-04-2025 05:12:18","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004816100","E=
vodoula OCM","","16-04-2025 05:05:51","16-04-2025 04:56:38","16-04-2025 05:=
36:41","grid outage,gen failed to start due to grid bad voltage,no rcp//he =
bypassed the Grid and site on Gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","grid outage,ge=
n failed to start due to grid bad voltage,no rcp//he bypassed the Grid and =
site on Gen","edwige.kapawo@matech-cameroun.com","554","16-04-2025 05:05:51=
","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004816059","Nsi=
malen MTN","","16-04-2025 04:48:36","16-04-2025 04:42:24","16-04-2025 05:04=
:24","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","gerard.tchangoue@matech-cameroun.com","37=
2","16-04-2025 04:48:36","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004816039","A=
wae Ewonkan","","16-04-2025 04:41:37","16-04-2025 04:37:22","16-04-2025 08:=
27:35","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed//We reduce load and gen manually started","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage, Site went down because Gen overload(20KVA,310A) SS IHS Alphonse DEF=
FO is informed//We reduce load and gen manually started","edwige.kapawo@mat=
ech-cameroun.com","256","16-04-2025 04:41:37","MATECH CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0004815992","S=
ous Prefecture","","16-04-2025 04:24:20","16-04-2025 03:45:08","16-04-2025 =
04:34:05","ACTIVE//No power issue site on Gen Ubaie =3D55.5V, The tx Huawei=
 Fulbert (654266068) is informed ","Fanda Brice","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No pow=
er issue site on Gen Ubaie =3D55.5V, The tx Huawei Fulbert (654266068) is i=
nformed ","edwige.kapawo@matech-cameroun.com","2354","16-04-2025 04:24:20",=
"MATECH CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004815984","NKO=
MEKUI OCM","","16-04-2025 04:21:05","16-04-2025 04:15:50","16-04-2025 04:22=
:55","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted b=
y Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","Affected by 3r=
d Party Site","Active//No power issue on site U=3D54.5 V site on Gen.Site i=
mpacted by Mbankolo Camtel and not managing by IHS","gerard.tchangoue@matec=
h-cameroun.com","316","16-04-2025 04:21:05","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004815969","Nsi=
malen MTN","","16-04-2025 04:09:24","16-04-2025 03:59:59","16-04-2025 04:10=
:56","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","gerard.tchangoue@matech-cameroun.com","56=
6","16-04-2025 04:09:24","MATECH CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0004815933","Mba=
nkomo CAF","","16-04-2025 03:59:14","16-04-2025 03:52:04","16-04-2025 03:59=
:04","No power issue site on Gen with U=3D53v Flubert(654266068) from Huawe=
i is informed","Fanda Brice","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on Gen with U=
=3D53v Flubert(654266068) from Huawei is informed","gerard.tchangoue@matech=
-cameroun.com","431","16-04-2025 03:59:14","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004815914","Nko=
ulou Carriere carrefourt","","16-04-2025 03:50:07","16-04-2025 03:32:59","1=
6-04-2025 03:49:59","Site up awaiting feedback","Mba Lazare Herve","Cascade=
 Outage","Active","Cascade Active","Cascade Active","Active//No power issue=
 site on Grid with U=3D55.5V ,The FME TX Henri (691145055) from Huawei is i=
nformed","gerard.tchangoue@matech-cameroun.com","268233","16-04-2025 03:50:=
07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0004815907","Nkolanga=
a","","16-04-2025 03:48:57","16-04-2025 03:32:59","16-04-2025 03:49:59","Ca=
scaded Incident from TTO4919181","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue site on Grid w=
ith U=3D55.5V ,The FME TX Henri (691145055) from Huawei is informed","syste=
m","268233","16-04-2025 03:48:57","MATECH CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0004815904","Aba=
ng","IHS_YND_794, IHS_YND_289","16-04-2025 03:48:18","16-04-2025 03:32:59",=
"16-04-2025 03:49:59","Active//No power issue site on Grid with U=3D55.5V ,=
The FME TX Henri (691145055) from Huawei is informed","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue site on Grid with U=3D55.5V ,The FME TX He=
nri (691145055) from Huawei is informed","gerard.tchangoue@matech-cameroun.=
com","920","16-04-2025 03:48:18","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004815895","N=
kolondom","","16-04-2025 03:40:06","16-04-2025 03:31:59","16-04-2025 08:00:=
38","Grid outage, site went down sue to GE HS // Grid return","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Gri=
d outage, site went down sue to GE HS // Grid return","gerard.tchangoue@mat=
ech-cameroun.com","489","16-04-2025 03:40:06","MATECH CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0004815879","B=
astos-BAT","","16-04-2025 03:28:47","16-04-2025 03:22:33","16-04-2025 03:30=
:33","Grid outage , site went down before Gen started due to poor battery b=
ackup// gen automatically started","Mboua Thierry","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage , site went=
 down before Gen started due to poor battery backup// gen automatically sta=
rted","edwige.kapawo@matech-cameroun.com","375","16-04-2025 03:28:47","MATE=
CH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004815875","Mok=
olo Yaounde","","16-04-2025 03:26:35","16-04-2025 03:24:52","16-04-2025 04:=
12:54","No power issue U =3D54,6V site on grid. The Tx FME Eloundou Bertran=
d (693212405)from Huawei is informed","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D54=
,6V site on grid. The Tx FME Eloundou Bertrand (693212405)from Huawei is in=
formed","gerard.tchangoue@matech-cameroun.com","105","16-04-2025 03:26:35",=
"MATECH CMR"
"Closed Complete","Site Down","T0417-1","IHS_YND_220","NOCINC0004815857","G=
olf Quater","","16-04-2025 03:18:32","16-04-2025 03:16:12","16-04-2025 03:1=
8:12","ACTIVE//No Power issue on site Ubaie=3D53,5V site on Grid The Tx FME=
 Eloumdou betrrand//693212405 from Huawei is informed","Mboua Thierry","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","ACTIVE//No Power issue on site Ubaie=3D53,5V site on Grid The Tx FM=
E Eloumdou betrrand//693212405 from Huawei is informed","gerard.tchangoue@m=
atech-cameroun.com","141","16-04-2025 03:18:32","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0004815852","Ema=
na Lycee","","16-04-2025 03:16:19","16-04-2025 03:14:07","16-04-2025 03:21:=
42","No power issue site on grid with U=3D56v Symphorien(691316854) from Hu=
awei is informed.","Fabrice Pouakam","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gri=
d with U=3D56v Symphorien(691316854) from Huawei is informed.","gerard.tcha=
ngoue@matech-cameroun.com","134","16-04-2025 03:16:19","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004815797","O=
lembe-Terminus","","16-04-2025 02:55:02","16-04-2025 02:51:51","16-04-2025 =
06:54:24","Site down due to work done by IHS SS Felix Bateu(677549887)//End=
 of work","Fabrice Pouakam","Installation Activity","Passive","Planned Acti=
vity","Installation Activity","Site down due to work done by IHS SS Felix B=
ateu(677549887)//End of work","gerard.tchangoue@matech-cameroun.com","193",=
"16-04-2025 02:55:02","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004815773","Nko=
g-Edzen","","16-04-2025 02:32:39","16-04-2025 02:30:24","16-04-2025 05:19:4=
2","No power issue on site, site on Battery with U=3D52v The Tx Fme Gregoir=
e (654547479) from Huawei is informed.","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site, site on Battery with U=3D52v The Tx Fme Gregoire (65454747=
9) from Huawei is informed.","gerard.tchangoue@matech-cameroun.com","136","=
16-04-2025 02:32:39","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004815726","SAA=
 Entrance","","16-04-2025 02:09:48","16-04-2025 02:02:59","16-04-2025 02:52=
:59","Grid outage .gen failed to start due to starter relay faulty // He by=
pass it and gen manually started","Parker Tchoup","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Relay Faulty","Grid outage .gen failed to start due =
to starter relay faulty // He bypass it and gen manually started","gerard.t=
changoue@matech-cameroun.com","411","16-04-2025 02:09:48","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004815696","Lad=
a I Yde","","16-04-2025 01:57:39","16-04-2025 01:56:30","16-04-2025 01:57:3=
0","Site went down due to rectifier dysfunctionned//We reset rectifier and =
site on grid ","Mba Lazare Herve","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site went down due to rectifier dysfunctionned//We rese=
t rectifier and site on grid ","gerard.tchangoue@matech-cameroun.com","70",=
"16-04-2025 01:57:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_083","NOCINC0004815575","H-Progre=
s","","16-04-2025 01:05:03","16-04-2025 00:59:22","16-04-2025 01:08:39","Ca=
scaded Incident from TTO4918783","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","Active No power issue on site U=3D53,2V site on Grid =
Mohamadou/691144435 from Huawei is informed","system","263071","16-04-2025 =
01:05:03","MATECH CMR"
"Closed Complete","Site Down","CTR_110","IHS_YND_028","NOCINC0004815572","H=
-Central","IHS_YND_083","16-04-2025 01:04:29","16-04-2025 00:59:22","16-04-=
2025 01:08:39","Active No power issue on site U=3D53,2V site on Grid Mohama=
dou/691144435 from Huawei is informed","Paul BIBOUM","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active No =
power issue on site U=3D53,2V site on Grid Mohamadou/691144435 from Huawei =
is informed","gerard.tchangoue@matech-cameroun.com","308","16-04-2025 01:04=
:29","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004815554","C=
amp-Sic-Tsinga","","16-04-2025 00:58:18","16-04-2025 00:43:11","16-04-2025 =
01:20:47","Active//No power issue U=3D50,6V, Site on Grid. The Tx FME Brice=
 Tsague(650214096) from Huawei is informed.","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue U=3D50,6V, Site on Grid. The Tx FME Brice Tsague(650214096) from Hu=
awei is informed.","gerard.tchangoue@matech-cameroun.com","908","16-04-2025=
 00:58:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004815409","Akono","=
","16-04-2025 00:23:43","16-04-2025 00:15:59","16-04-2025 00:21:44","Cascad=
ed Incident from TTO4918588","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) no manager by IHS","system","265701","16-04-2025 00:23:43=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004815407","OTELE MT=
N","","16-04-2025 00:23:42","16-04-2025 00:15:59","16-04-2025 00:21:44","Ca=
scaded Incident from TTO4918588","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue site on Grid with U=
=3D53,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impac=
ted by Ngoumou(T0169) no manager by IHS","system","265700","16-04-2025 00:2=
3:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004815408","Minka","=
","16-04-2025 00:23:42","16-04-2025 00:15:59","16-04-2025 00:21:44","Cascad=
ed Incident from TTO4918588","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) no manager by IHS","system","265700","16-04-2025 00:23:42=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004815406","OLAMA","=
","16-04-2025 00:23:42","16-04-2025 00:15:59","16-04-2025 00:21:44","Cascad=
ed Incident from TTO4918588","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169) no manager by IHS","system","265701","16-04-2025 00:23:42=
","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004815403","Mom=
","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_365","16-04-2025 00:22:01=
","16-04-2025 00:15:59","16-04-2025 00:21:44","Active//No power issue site =
on Grid with U=3D53,3 V The FME TX Etienne(695033981) From Huawei is inform=
ed. Site impacted by Ngoumou(T0169) no manager by IHS","Fanda Brice","Custo=
mer Equipment Failure","Active","Active Equipment Failure","Affected by 3rd=
 Party Site","Active//No power issue site on Grid with U=3D53,3 V The FME T=
X Etienne(695033981) From Huawei is informed. Site impacted by Ngoumou(T016=
9) no manager by IHS","gerard.tchangoue@matech-cameroun.com","364","16-04-2=
025 00:22:01","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004815401","N=
goulmekong-Nord","","16-04-2025 00:21:08","16-04-2025 00:19:01","16-04-2025=
 00:22:35","Grid outage, Site went down before Gen started due to poor back=
up // Grid return","Siligap Boris","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
started due to poor backup // Grid return","edwige.kapawo@matech-cameroun.c=
om","128","16-04-2025 00:21:08","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004815316","Ebo=
go","","15-04-2025 23:57:47","15-04-2025 23:50:22","15-04-2025 23:52:22","G=
rid outage, Site went down before Gen started due to poor backup // Gen sta=
rted automatically","Siligap Boris","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 started due to poor backup // Gen started automatically","gerard.tchangoue=
@matech-cameroun.com","446","15-04-2025 23:57:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004815305","Melen Ba=
'aba","","15-04-2025 23:55:43","15-04-2025 23:45:03","16-04-2025 00:10:55",=
"Cascaded Incident from TTO4918456","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen fails to start due to PWC dysfunctionning, // gen manually started","=
system","267555","15-04-2025 23:55:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004815306","TSINGA V=
ILLAGE 2","","15-04-2025 23:55:43","15-04-2025 23:45:03","16-04-2025 00:10:=
55","Cascaded Incident from TTO4918456","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen fails to start due to PWC dysfunctionning, // gen manually start=
ed","system","267555","15-04-2025 23:55:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004815304","Nkolfoul=
ou 2","","15-04-2025 23:55:43","15-04-2025 23:45:03","16-04-2025 00:10:55",=
"Cascaded Incident from TTO4918456","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen fails to start due to PWC dysfunctionning, // gen manually started","=
system","267556","15-04-2025 23:55:43","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004815289","Nko=
lfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","15-04-2025 23:53:29","15-=
04-2025 23:45:03","16-04-2025 00:12:32","Grid outage, site went down becaus=
e gen fails to start due to PWC dysfunctionning, // gen manually started","=
Siligap Boris","Equipment Repair","Passive","Control Panel","ATS-AMF Issue"=
,"Grid outage, site went down because gen fails to start due to PWC dysfunc=
tionning, // gen manually started","gerard.tchangoue@matech-cameroun.com","=
538","15-04-2025 23:53:29","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004815158","MEH=
ANDAN","","15-04-2025 23:22:17","15-04-2025 23:21:05","16-04-2025 09:28:24"=
,"very unstable site and FME report that rectifiers issue","Albran Byorel",=
"Equipment Repair","Passive","Rectifier","Rectifier Module","Site went down=
 due to insufficiency of rectifiers on site SS IHS Pascaline is confirm // =
Site stabilised","gerard.tchangoue@matech-cameroun.com","73","15-04-2025 23=
:22:17","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004815065","M=
essassi 2","","15-04-2025 23:01:26","15-04-2025 22:59:12","15-04-2025 23:03=
:07","	Site went down because 02/06 rectifiers dysfuncionned// He reset rec=
tifiers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","	Site went down because 02/06 rectifiers dysfuncionned// He re=
set rectifiers","edwige.kapawo@matech-cameroun.com","136","15-04-2025 23:01=
:26","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0004815032","NKO=
ABANG NKOLO 3","","15-04-2025 22:52:40","15-04-2025 22:51:18","16-04-2025 0=
0:02:45","Grid fluctuation site went down because Gen started and stopped d=
ue to Grid bad voltage and RCP on site // He bypass the Grid site on Gen","=
Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation site went down because Gen started and st=
opped due to Grid bad voltage and RCP on site // He bypass the Grid site on=
 Gen","gerard.tchangoue@matech-cameroun.com","83","15-04-2025 22:52:40","MA=
TECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004814994","Cit=
e des nations","","15-04-2025 22:37:24","15-04-2025 22:30:59","16-04-2025 0=
0:14:24","Site went down due to insufficient rectifiers on site//Site stabi=
lised","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficient rectifiers on site//Site stabilis=
ed	","gerard.tchangoue@matech-cameroun.com","386","15-04-2025 22:37:24","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004814744","A=
wae Ewonkan","","15-04-2025 21:48:41","15-04-2025 21:45:52","15-04-2025 21:=
53:43","	Grid outage site went down due to Gen Overload (20Kva, Iload 225 A=
)IHS SS Alphonse is informed // Grid Restored","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","	Grid outage site went down =
due to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid=
 Restored","christelle.ngonga@matech-cameroun.com","198","15-04-2025 21:48:=
41","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004814724","Cit=
e des nations","","15-04-2025 21:44:27","15-04-2025 21:25:01","15-04-2025 2=
1:47:01","Site went down due to insufficient rectifiers on site//Site stabi=
lised","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficient rectifiers on site//Site stabilis=
ed","christelle.ngonga@matech-cameroun.com","1167","15-04-2025 21:44:27","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004814597","B=
iteng-Maetur","","15-04-2025 21:23:54","15-04-2025 21:16:48","15-04-2025 22=
:23:17","Site went down due to insufficient rectifiers on site//He reset an=
d site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to insufficient rectifiers on site/=
/He reset and site on Grid","christelle.ngonga@matech-cameroun.com","428","=
15-04-2025 21:23:54","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004814589","E=
kombitie","","15-04-2025 21:22:09","15-04-2025 21:15:02","15-04-2025 21:37:=
02","Grid fluctuation, Site went down because gen failed to start due to gr=
id bad voltage,/ He bypassed the Grid and site on Gen","Fabrice Pouakam","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d fluctuation, Site went down because gen failed to start due to grid bad v=
oltage,/ He bypassed the Grid and site on Gen","christelle.ngonga@matech-ca=
meroun.com","429","15-04-2025 21:22:09","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004814464","B=
itoto","","15-04-2025 21:06:22","15-04-2025 21:03:16","15-04-2025 22:20:30"=
,"Active//No power issue on site , Tx Issue : site on Grid ,Ubai: 54,4V; Th=
e fme Tx Henri (699949693) From huawei is informed and notice that disjunct=
ion at OCM Equipment","Mba Lazare Herve","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue=
 on site , Tx Issue : site on Grid ,Ubai: 54,4V; The fme Tx Henri (69994969=
3) From huawei is informed and notice that disjunction at OCM Equipment","c=
hristelle.ngonga@matech-cameroun.com","187","15-04-2025 21:06:22","MATECH C=
MR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004814449","C=
rf-Nkolbisson","","15-04-2025 21:04:55","15-04-2025 20:47:44","15-04-2025 2=
1:49:44","Site went down Because disjunction of Cb due to the site load whi=
ch increased there from (we need second depart)// CB rearmed","TIENTCHEU NZ=
ETCHIEU GAEL","Equipment Repair","Passive","Control Panel","Circuit Breaker=
 Tripped","Site went down Because disjunction of Cb due to the site load wh=
ich increased there from (we need second depart)// CB rearmed","christelle.=
ngonga@matech-cameroun.com","1032","15-04-2025 21:04:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_283","NOCINC0004814371","Abome","=
","15-04-2025 20:47:36","15-04-2025 15:56:45","15-04-2025 16:10:45","Cascad=
ed Incident from TTO4917286","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","The site wen down do to plan work // End =
of work, site on Grid","system","666880","15-04-2025 20:47:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0004814367","Mvog-Man=
ga","","15-04-2025 20:47:35","15-04-2025 15:56:45","15-04-2025 16:10:45","C=
ascaded Incident from TTO4917286","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","The site wen down do to plan work //=
 End of work, site on Grid","system","666879","15-04-2025 20:47:35","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_728","NOCINC0004814366","TROPICAN=
A NEW","","15-04-2025 20:47:35","15-04-2025 15:56:45","15-04-2025 16:10:45"=
,"Cascaded Incident from TTO4917286","MINKA NICOLAS","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","The site wen down do to plan work=
 // End of work, site on Grid","system","666878","15-04-2025 20:47:35","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_807","NOCINC0004814369","Ahala Ec=
hangeur","","15-04-2025 20:47:35","15-04-2025 15:56:45","15-04-2025 16:10:4=
5","Cascaded Incident from TTO4917286","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","The site wen down do to plan wo=
rk // End of work, site on Grid","system","666881","15-04-2025 20:47:35","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_253","NOCINC0004814370","Clge-Adv=
antiste","","15-04-2025 20:47:35","15-04-2025 15:56:45","15-04-2025 16:10:4=
5","Cascaded Incident from TTO4917286","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","The site wen down do to plan wo=
rk // End of work, site on Grid","system","666880","15-04-2025 20:47:35","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004814368","Odza II =
OCM","","15-04-2025 20:47:35","15-04-2025 15:56:45","15-04-2025 16:10:45","=
Cascaded Incident from TTO4917286","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","The site wen down do to plan work /=
/ End of work, site on Grid","system","666878","15-04-2025 20:47:35","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_256","NOCINC0004814365","MESSAME =
NDONGO 1162","","15-04-2025 20:47:34","15-04-2025 15:56:45","15-04-2025 16:=
10:45","Cascaded Incident from TTO4917286","MINKA NICOLAS","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","The site wen down do to pla=
n work // End of work, site on Grid","system","666879","15-04-2025 20:47:34=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_161","NOCINC0004814363","Sofavinc=
","","15-04-2025 20:47:34","15-04-2025 15:56:45","15-04-2025 16:10:45","Cas=
caded Incident from TTO4917286","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","The site wen down do to plan work // E=
nd of work, site on Grid","system","666882","15-04-2025 20:47:34","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0004814362","Carrefou=
rt Nkomo","","15-04-2025 20:47:34","15-04-2025 15:56:45","15-04-2025 16:10:=
45","Cascaded Incident from TTO4917286","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","The site wen down do to pla=
n work // End of work, site on Grid","system","666879","15-04-2025 20:47:34=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_160","NOCINC0004814364","Complex =
Beac II","","15-04-2025 20:47:34","15-04-2025 15:56:45","15-04-2025 16:10:4=
5","Cascaded Incident from TTO4917286","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","The site wen down do to plan wo=
rk // End of work, site on Grid","system","666881","15-04-2025 20:47:34","M=
ATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004814317","Tou=
ring Club International","IHS_YND_174, IHS_YND_161, IHS_YND_160, IHS_YND_25=
6, IHS_YND_728, IHS_YND_254, IHS_YND_527, IHS_YND_807, IHS_YND_253, IHS_YND=
_283","15-04-2025 20:42:00","15-04-2025 15:56:45","15-04-2025 16:10:45","Th=
e site wen down do to plan work // End of work, site on Grid","Albran Byore=
l","Equipment Repair","Passive","Planned Activity","Planned Activity - DCGG=
 Gen","The site wen down do to plan work // End of work, site on Grid","fra=
nck.nkomot@matech-cameroun.com","17116","15-04-2025 20:42:00","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004814225","Cit=
e des nations","","15-04-2025 20:30:44","15-04-2025 20:01:31","15-04-2025 2=
0:45:31","Site went down due to insufficient rectifiers on site//Site stabi=
lised","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficient rectifiers on site//Site stabilis=
ed","christelle.ngonga@matech-cameroun.com","1754","15-04-2025 20:30:44","M=
ATECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004814184","ODZ=
A CITE MBIA","","15-04-2025 20:25:00","15-04-2025 20:10:40","15-04-2025 21:=
12:40","Grid fluctuation, Site went down because Gen failed to start due to=
 Grid bad voltage // Grid stabilized","Albran Byorel","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site=
 went down because Gen failed to start due to Grid bad voltage // Grid stab=
ilized","ludivine.ngamaleu@ihstowers.com","861","15-04-2025 20:25:00","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004814151","M=
essassi 2","","15-04-2025 20:17:47","15-04-2025 20:10:41","15-04-2025 20:31=
:43","Grid fluctuation, Site went down because Gen fails to start due to Gr=
id bad voltage// Grid stabilized","Fabrice Pouakam","Grid Supply","Passive"=
,"Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuation, Sit=
e went down because Gen fails to start due to Grid bad voltage// Grid stabi=
lized","christelle.ngonga@matech-cameroun.com","427","15-04-2025 20:17:47",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004814079","O=
lembe-Terminus","","15-04-2025 20:01:47","15-04-2025 19:58:32","15-04-2025 =
21:06:32","Grid outage site went don due to grid contactor faulty // Grid r=
eturn","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-=
AMF Issue","Grid outage site went don due to grid contactor faulty // Grid =
return","christelle.ngonga@matech-cameroun.com","196","15-04-2025 20:01:47"=
,"MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004813929","Odz=
a petit marche new","","15-04-2025 19:37:44","15-04-2025 19:31:37","15-04-2=
025 20:57:37","Grid outage. Site went down due to rectifier dysfunctionning=
//We reset rectifier//Grid return","Albran Byorel","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","Grid outage. Site went down due to rec=
tifier dysfunctionning//We reset rectifier//Grid return","christelle.ngonga=
@matech-cameroun.com","367","15-04-2025 19:37:44","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004813842","N=
koabang Ebolmedjock","","15-04-2025 19:21:26","15-04-2025 19:08:06","15-04-=
2025 19:36:06","Grid fuctuation,Site went down due to Grid bad voltages //G=
rid return","Mba Lazare Herve","Grid Supply","Passive","Grid","National Gri=
d - Phase Controller Faulty","Grid fuctuation,Site went down due to Grid ba=
d voltages //Grid return","christelle.ngonga@matech-cameroun.com","801","15=
-04-2025 19:21:26","MATECH CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0004813579","A=
cropole","","15-04-2025 18:36:13","15-04-2025 18:34:06","15-04-2025 18:55:4=
9","Site down because  Njoya mohamed (658849259 ) of Loumade was  on site f=
or swap on battery and DC BOX // End of work","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","S=
ite down because  Njoya mohamed (658849259 ) of Loumade was  on site for sw=
ap on battery and DC BOX // End of work","christelle.ngonga@matech-cameroun=
.com","127","15-04-2025 18:36:13","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004813551","C=
rf-Nkolbisson","","15-04-2025 18:31:53","15-04-2025 18:15:46","15-04-2025 2=
0:18:39","Site went down Because disjunction of Cb due to the site load whi=
ch increased there from (we need second depart)// CB rearmed","TIENTCHEU NZ=
ETCHIEU GAEL","Equipment Repair","Passive","Control Panel","Circuit Breaker=
 Tripped","	Site went down Because disjunction of Cb due to the site load w=
hich increased there from (we need second depart)// CB rearmed","christelle=
.ngonga@matech-cameroun.com","968","15-04-2025 18:31:53","MATECH CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0004813435","ETO=
UDI CHAPELLE","","15-04-2025 18:12:20","15-04-2025 18:11:09","15-04-2025 18=
:13:09","Our FME Delor specifies that after the ART visit, he went to retur=
n the rectifiers to Etoudi 2. Currently, the Etoudi Chapelle site has a ins=
ufficient of rectifiers//site stabilized","Delor Telezing","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Our FME Delor specifies that a=
fter the ART visit, he went to return the rectifiers to Etoudi 2. Currently=
, the Etoudi Chapelle site has a insufficient of rectifiers//site stabilize=
d","franck.nkomot@matech-cameroun.com","73","15-04-2025 18:12:20","MATECH C=
MR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004813411","Beh=
ind P T school Yde","","15-04-2025 18:08:39","15-04-2025 17:47:18","15-04-2=
025 19:01:18","Site went down due to insufficience of rectifier causing by =
02/05 slots faulty, SS IHS FRANCOIS is informed // He disconnected the faul=
ty slots of rectifier","Paul BIBOUM","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to insufficience of rectifier cau=
sing by 02/05 slots faulty, SS IHS FRANCOIS is informed // He disconnected =
the faulty slots of rectifier","ludivine.ngamaleu@ihstowers.com","1282","15=
-04-2025 18:08:39","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004813350","O=
lembe-Terminus","","15-04-2025 18:02:53","15-04-2025 17:56:34","15-04-2025 =
18:30:34","Grid outage site went don due to grid contactor faulty // Grid r=
eturn","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-=
AMF Issue","Grid outage site went don due to grid contactor faulty // Grid =
return","christelle.ngonga@matech-cameroun.com","381","15-04-2025 18:02:53"=
,"MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004813057","NYO=
M FACE MAETUR","","15-04-2025 17:23:45","15-04-2025 17:22:39","15-04-2025 1=
7:27:39","Eneo fluctuations, Site went down because gen fails to start due =
to Grid fluctuations //Grid stabilisation","Fabrice Pouakam","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Eneo fluctuations, Si=
te went down because gen fails to start due to Grid fluctuations //Grid sta=
bilisation","christelle.ngonga@matech-cameroun.com","67","15-04-2025 17:23:=
45","MATECH CMR"
"Closed Complete","Site Down","T0538","IHS_YND_036","NOCINC0004813055","Acr=
opole","","15-04-2025 17:23:02","15-04-2025 17:18:56","15-04-2025 17:30:49"=
,"Site down due to work of  Njoya mohamed (658849259 ) Loumade was on site =
for  swap on battery and DC BOX // End of work","MINKA NICOLAS","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Site down due to work of  Njoya mohamed (658849259 ) Loumade was on site f=
or  swap on battery and DC BOX // End of work","christelle.ngonga@matech-ca=
meroun.com","247","15-04-2025 17:23:02","MATECH CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0004813038","Oss=
ombe","","15-04-2025 17:19:04","15-04-2025 17:15:58","15-04-2025 19:15:58",=
"Grid outage, Site went down because Gen failed to start due to Gen card di=
sfunction// He reset Gen card and started Gen manually","Parker Tchoup","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, S=
ite went down because Gen failed to start due to Gen card disfunction// He =
reset Gen card and started Gen manually","christelle.ngonga@matech-cameroun=
.com","187","15-04-2025 17:19:04","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004812934","Cit=
e des nations","","15-04-2025 16:59:43","15-04-2025 16:56:50","15-04-2025 1=
7:02:50","Active //No power issue ,site on Grid on site with Ubaie=3D55 V X=
 Fme Hosiah (674007438) from huawei is informed","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active //No power issue ,site on Grid on site with Ubaie=3D55 V X Fme Hosia=
h (674007438) from huawei is informed","franck.nkomot@matech-cameroun.com",=
"174","15-04-2025 16:59:43","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004812926","Nsi=
malen MTN","","15-04-2025 16:57:36","15-04-2025 16:48:19","15-04-2025 17:10=
:54","Grid outage, Site went down before Gen start due to poor backup // Gr=
id restoration","Albran Byorel","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup // Grid restoration","christelle.ngonga@matech-camero=
un.com","558","15-04-2025 16:57:36","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004812898","Imm=
-Olympique","","15-04-2025 16:55:06","15-04-2025 16:47:59","15-04-2025 17:0=
5:59","Site went down because 02/06 rectifiers hanging //He reset rectifier=
s ,site on Grid","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Site went down because 02/06 rectifiers hanging=
 //He reset rectifiers ,site on Grid","christelle.ngonga@matech-cameroun.co=
m","428","15-04-2025 16:55:06","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004812874","Ako=
k Ndoe Yde","","15-04-2025 16:52:14","15-04-2025 16:47:59","15-04-2025 17:2=
9:37","Grid outage, site went down due to poor battery backup , Gen fails t=
o start // Grid restoration","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
due to poor battery backup , Gen fails to start // Grid restoration","franc=
k.nkomot@matech-cameroun.com","256","15-04-2025 16:52:14","MATECH CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004812662","L=
eboudi","","15-04-2025 16:20:57","15-04-2025 16:12:24","15-04-2025 16:25:24=
","Cascaded Incident from TTO4915352","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","TTO4915352","christel=
le.ngonga@matech-cameroun.com","265697","15-04-2025 16:20:57","MATECH CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004812635","Nko=
lafeme","IHS_YND_309","15-04-2025 16:16:31","15-04-2025 16:12:24","15-04-20=
25 16:25:24","Grid outage, site went down due to gen gen overload(20Kva, 38=
0A), SS IHS Pascaline is informed// Grid power return","TIENTCHEU NZETCHIEU=
 GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge, site went down due to gen gen overload(20Kva, 380A), SS IHS Pascaline i=
s informed// Grid power return","christelle.ngonga@matech-cameroun.com","80=
0","15-04-2025 16:16:31","MATECH CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0004812631","Odz=
a II","","15-04-2025 16:15:46","15-04-2025 15:56:29","15-04-2025 16:27:49",=
"Site went down because gen failed to start due to grid bad voltage // Grid=
 restoration","Albran Byorel","Grid Supply","Passive","Grid","National Grid=
 - Low Current Supply","Site went down because gen failed to start due to g=
rid bad voltage // Grid restoration","christelle.ngonga@matech-cameroun.com=
","1159","15-04-2025 16:15:46","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004812503","Sim=
e Building","","15-04-2025 15:51:01","15-04-2025 15:37:42","15-04-2025 15:5=
1:42","site went down due to insufficiency of rectifiers // He reset it","M=
boua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module","=
site went down due to insufficiency of rectifiers // He reset it","ludivine=
.ngamaleu@ihstowers.com","800","15-04-2025 15:51:01","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004812491","Imm=
-Olympique","","15-04-2025 15:47:01","15-04-2025 15:29:39","15-04-2025 15:4=
3:16","Site went down because 02/06 rectifiers hanging //He reset rectifier=
s ,site on Grid","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Site went down because 02/06 rectifiers hanging=
 //He reset rectifiers ,site on Grid","ludivine.ngamaleu@ihstowers.com","10=
43","15-04-2025 15:47:01","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004812415","O=
dza II OCM","","15-04-2025 15:36:34","15-04-2025 15:23:27","15-04-2025 15:4=
2:27","Grid outage gen failed to start due to card GE dysfunctionning//Grid=
 return","Albran Byorel","Equipment Repair","Passive","DCDG Gen","DCDG - Pa=
nel Board","Grid outage gen failed to start due to card GE dysfunctionning/=
/Grid return","christelle.ngonga@matech-cameroun.com","789","15-04-2025 15:=
36:34","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004812297","Odz=
a II OCM","","15-04-2025 15:14:42","15-04-2025 15:08:35","15-04-2025 15:14:=
35","Grid outage gen failed to start due to card GE dysfunctionning//Grid r=
eturn","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid outage gen failed to start due to card GE dysfunctionning/=
/Grid return","franck.nkomot@matech-cameroun.com","368","15-04-2025 15:14:4=
2","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_283","NOCINC0004812209","Abome","=
","15-04-2025 15:05:40","15-04-2025 14:46:22","15-04-2025 15:00:38","Cascad=
ed Incident from TTO4914702","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227523","15-04-2025 15:05:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0004812205","Awae Ewo=
nkan","","15-04-2025 15:05:39","15-04-2025 14:46:22","15-04-2025 15:00:38",=
"Cascaded Incident from TTO4914702","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227522","15-04-2025 15:05:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004812206","ODZA MIN=
KAN EDIBI ASSI","","15-04-2025 15:05:39","15-04-2025 14:46:22","15-04-2025 =
15:00:38","Cascaded Incident from TTO4914702","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227519","15-04-2025 15:05:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_253","NOCINC0004812204","Clge-Adv=
antiste","","15-04-2025 15:05:39","15-04-2025 14:46:22","15-04-2025 15:00:3=
8","Cascaded Incident from TTO4914702","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227525","15-04-2025 15:05:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_524","NOCINC0004812200","ODZA BOR=
NE 10","","15-04-2025 15:05:38","15-04-2025 14:46:22","15-04-2025 15:00:38"=
,"Cascaded Incident from TTO4914702","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227522","15-04-2025 15:05:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004812203","Abang","=
","15-04-2025 15:05:38","15-04-2025 14:46:22","15-04-2025 15:00:38","Cascad=
ed Incident from TTO4914702","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227528","15-04-2025 15:05:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004812201","Odza Min=
kan IHS","","15-04-2025 15:05:38","15-04-2025 14:46:22","15-04-2025 15:00:3=
8","Cascaded Incident from TTO4914702","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227520","15-04-2025 15:05:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_336","NOCINC0004812199","EKIE",""=
,"15-04-2025 15:05:38","15-04-2025 14:46:22","15-04-2025 15:00:38","Cascade=
d Incident from TTO4914702","Albran Byorel","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227526","15-04-2025 15:05:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0004812198","Mvog-Man=
ga","","15-04-2025 15:05:37","15-04-2025 14:46:22","15-04-2025 15:00:38","C=
ascaded Incident from TTO4914702","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227529","15-04-2025 15:05:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0004812196","Nkolanga=
a","","15-04-2025 15:05:37","15-04-2025 14:46:22","15-04-2025 15:00:38","Ca=
scaded Incident from TTO4914702","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227527","15-04-2025 15:05:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_728","NOCINC0004812197","TROPICAN=
A NEW","","15-04-2025 15:05:37","15-04-2025 14:46:22","15-04-2025 15:00:38"=
,"Cascaded Incident from TTO4914702","MINKA NICOLAS","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227525","15-04-2025 15:05:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_256","NOCINC0004812195","MESSAME =
NDONGO 1162","","15-04-2025 15:05:37","15-04-2025 14:46:22","15-04-2025 15:=
00:38","Cascaded Incident from TTO4914702","MINKA NICOLAS","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227528","15-04-2025 15:05:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_160","NOCINC0004812191","Complex =
Beac II","","15-04-2025 15:05:36","15-04-2025 14:46:22","15-04-2025 15:00:3=
8","Cascaded Incident from TTO4914702","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227521","15-04-2025 15:05:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004812194","Nomayos =
montee Meche","","15-04-2025 15:05:36","15-04-2025 14:46:22","15-04-2025 15=
:00:38","Cascaded Incident from TTO4914702","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227524","15-04-2025 15:05:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004812193","Mehanda =
1","","15-04-2025 15:05:36","15-04-2025 14:46:22","15-04-2025 15:00:38","Ca=
scaded Incident from TTO4914702","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227527","15-04-2025 15:05:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_252","NOCINC0004812189","Koweit C=
ity","","15-04-2025 15:05:35","15-04-2025 14:46:22","15-04-2025 15:00:38","=
Cascaded Incident from TTO4914702","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227526","15-04-2025 15:05:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_161","NOCINC0004812187","Sofavinc=
","","15-04-2025 15:05:35","15-04-2025 14:46:22","15-04-2025 15:00:38","Cas=
caded Incident from TTO4914702","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227521","15-04-2025 15:05:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_730","NOCINC0004812188","Odza pet=
it marche new","","15-04-2025 15:05:35","15-04-2025 14:46:22","15-04-2025 1=
5:00:38","Cascaded Incident from TTO4914702","Albran Byorel","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227520","15-04-2025 15:05:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0004812185","Mbedoumo=
u - Ekali","","15-04-2025 15:05:34","15-04-2025 14:46:22","15-04-2025 15:00=
:38","Cascaded Incident from TTO4914702","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227524","15-04-2025 15:05:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0004812184","Carrefou=
rt Nkomo","","15-04-2025 15:05:34","15-04-2025 14:46:22","15-04-2025 15:00:=
38","Cascaded Incident from TTO4914702","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","system","1227519","15-04-2025 15:05:34","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004812134","Tou=
ring Club International","IHS_YND_174, IHS_YND_343, IHS_YND_161, IHS_YND_73=
0, IHS_YND_252, IHS_YND_160, IHS_YND_528, IHS_YND_746, IHS_YND_791, IHS_YND=
_256, IHS_YND_289, IHS_YND_728, IHS_YND_254, IHS_YND_336, IHS_YND_524, IHS_=
YND_715, IHS_YND_290, IHS_YND_312, IHS_YND_253, IHS_YND_535, IHS_YND_749, I=
HS_YND_283","15-04-2025 14:56:31","15-04-2025 14:46:22","15-04-2025 15:00:3=
8","  The site wen down do to plan work (swap of batteries) // End of work,=
 site on Grid","Albran Byorel","Equipment Repair","Passive","Planned Activi=
ty","Planned Activity - DCGG Gen","

The site wen down do to plan work (swap of batteries) // End of work, site =
on Grid","franck.nkomot@matech-cameroun.com","610","15-04-2025 14:56:31","M=
ATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004812113","Nko=
lnda","","15-04-2025 14:53:27","15-04-2025 14:46:22","15-04-2025 15:00:38",=
"Cascaded Incident from TTO4914702","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Cascaded Incident from TTO4914702"=
,"franck.nkomot@matech-cameroun.com","1227523","15-04-2025 14:53:27","MATEC=
H CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004811349","Ako=
k Ndoe Yde","","15-04-2025 13:23:12","15-04-2025 13:13:52","15-04-2025 14:0=
6:55","Grid outage, site went down due to poor battery backup // Gen start =
manually","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, site went down due to poor battery=
 backup // Gen start manually","loic.noumsi@matech-cameroun.com","561","15-=
04-2025 13:23:12","MATECH CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0004811279","E=
toudi","","15-04-2025 13:17:06","15-04-2025 13:00:46","15-04-2025 14:03:08"=
,"Grid outage, Gen Failed to start due to disfunctionnement of Gen card // =
Gen card Reset ","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Grid outage, Gen Failed to start due to disfunction=
nement of Gen card // Gen card Reset ","edwige.kapawo@matech-cameroun.com",=
"980","15-04-2025 13:17:06","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004811276","C=
RH-Etoug-Ebe","","15-04-2025 13:16:03","15-04-2025 13:12:56","15-04-2025 13=
:29:34","Grid outage, Site went down due to poor battery backup // Gen star=
t automatically","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down due to poor =
battery backup // Gen start automatically","edwige.kapawo@matech-cameroun.c=
om","189","15-04-2025 13:16:03","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004811271","N=
koabang Ebolmedjock","","15-04-2025 13:15:16","15-04-2025 13:11:09","15-04-=
2025 13:57:55","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","Affected by=
 3rd Party Site","Active//No power issue, Site on Gen. Notice that it is im=
pacted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","edwige.kapawo@mate=
ch-cameroun.com","248","15-04-2025 13:15:16","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004811251","N=
kolda","IHS_YND_327","15-04-2025 13:13:20","15-04-2025 13:08:09","15-04-202=
5 13:16:09","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Albran Byorel","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Grid return","edwige.kapawo@matech-cameroun.com"=
,"312","15-04-2025 13:13:20","MATECH CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0004811227","N=
simalen OCM","","15-04-2025 13:12:28","15-04-2025 13:08:09","15-04-2025 13:=
16:09","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage, Site went down before Gen start due to poor bac=
kup // Grid return","edwige.kapawo@matech-cameroun.com","269849","15-04-202=
5 13:12:28","MATECH CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0004811217","E=
lig-Essono","","15-04-2025 13:11:37","15-04-2025 13:04:30","15-04-2025 13:2=
8:34","Grid fluctuations site went down due to bad Grid voltage // Grid pow=
er stabilized","Paul BIBOUM","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Grid fluctuations site went down due to bad Gri=
d voltage // Grid power stabilized","edwige.kapawo@matech-cameroun.com","42=
7","15-04-2025 13:11:37","MATECH CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004811149","Lab=
oratoire  Meka","","15-04-2025 12:57:02","15-04-2025 12:42:54","16-04-2025 =
09:21:22","Site went down due to insufficient rectifiers on site // rectiie=
rs reset","","Equipment Repair","Passive","Rectifier","Rectifier Module","S=
ite went down due to insufficient rectifiers on site // rectiiers reset","l=
oic.noumsi@matech-cameroun.com","849","15-04-2025 12:57:02","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004811108","M=
bankomo IHS","","15-04-2025 12:50:04","15-04-2025 12:25:49","15-04-2025 12:=
26:03","No power issue on  site on Grid with Ubaie =3D55.37V The TX FME FUL=
BERT (654266068) from Huawei is informed","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on  site on Grid with Ubaie =3D55.37V The TX FME FULBERT (654266068=
) from Huawei is informed","loic.noumsi@matech-cameroun.com","1456","15-04-=
2025 12:50:04","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004810794","O=
mnisport 3","","15-04-2025 12:00:35","15-04-2025 11:53:24","15-04-2025 17:2=
0:24","No power issue on site U=3D54V. TX HUAWEI Armand (699949553) is info=
rmed","Delor Telezing","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue on site U=3D54V. TX HUAWE=
I Armand (699949553) is informed","loic.noumsi@matech-cameroun.com","432","=
15-04-2025 12:00:35","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004810100","Sim=
e Building","","15-04-2025 10:15:30","15-04-2025 10:09:14","15-04-2025 10:1=
5:54","Grid outage; site went down due to Poor battery backup // Grid retur=
n","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Battery Low","Grid outage; site went down due to Poor battery backup =
// Grid return","edwige.kapawo@matech-cameroun.com","376","15-04-2025 10:15=
:30","MATECH CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004810073","Lab=
oratoire  Meka","","15-04-2025 10:10:37","15-04-2025 10:04:14","15-04-2025 =
10:22:45","Site went down because 01/03 rectifiers dysfuncionned //We reset=
 rectifier(replacement rectifiers ongoing )","","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down because 01/03 rectifiers d=
ysfuncionned //We reset rectifier(replacement rectifiers ongoing )","edwige=
.kapawo@matech-cameroun.com","384","15-04-2025 10:10:37","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004809879","O=
mnisport 3","","15-04-2025 09:33:55","15-04-2025 09:27:32","15-04-2025 10:5=
7:10","Grid bad voltage Site down due to phase controller relay faulty // W=
e replaced it by a relay 220V, site on grid","Delor Telezing","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid bad volta=
ge Site down due to phase controller relay faulty // We replaced it by a re=
lay 220V, site on grid","edwige.kapawo@matech-cameroun.com","384","15-04-20=
25 09:33:55","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004809779","Ebo=
go","","15-04-2025 09:14:55","15-04-2025 09:02:40","15-04-2025 10:52:48","O=
ur FME was  on site,  Power issue has been resolved since 15-04-2025 10:52 =
AM but site remained down (Site went down due to CB (125A) faulty// we repl=
ace CB) Julien /393095849 from Huawei is on site.","Siligap Boris","Equipme=
nt Repair","Passive","Rectifier","Rectifier - Circuit Breaker","Our Technic=
ian Boris LIGAPE (657100525//681809743//LEC) was  on site,=20
Power issue has been resolved   since 15-04-2025 10:52 AM but site remained=
 down=20

Feedback : Site went down due to CB (125A) faulty// we replace CB

Julien /393095849 from Huawei is on site.","loic.noumsi@matech-cameroun.com=
","736","15-04-2025 09:14:55","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004809731","Eto=
udi2","","15-04-2025 09:03:46","15-04-2025 09:01:37","15-04-2025 18:28:10",=
"Site wen down due to Delor removed two rectifiers from Etoudi 2 to put in =
Etoudi chapel because of passage of the ART. The rectifiers have been repla=
ced//Site stabilizes","Delor Telezing","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site wen down due to Delor removed two rectifiers =
from Etoudi 2 to put in Etoudi chapel because of passage of the ART. The re=
ctifiers have been replaced//Site stabilizes","loic.noumsi@matech-cameroun.=
com","130","15-04-2025 09:03:46","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004809347","M=
EHANDAN","","15-04-2025 07:39:32","15-04-2025 07:38:18","15-04-2025 16:26:1=
8","Site went down due to insufficiency of rectifiers on site SS IHS Pascal=
ine is confirm // Site stabilised","Albran Byorel","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","Site went down due to insufficiency of=
 rectifiers on site SS IHS Pascaline is confirm // Site stabilised","edwige=
.kapawo@matech-cameroun.com","76","15-04-2025 07:39:32","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004809287","M=
essassi 2","","15-04-2025 07:27:39","15-04-2025 07:18:59","15-04-2025 08:49=
:34","Site went down because 02/06 rectifiers dysfuncionned// He reset rect=
ifiers ","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down because 02/06 rectifiers dysfuncionned// He res=
et rectifiers ","edwige.kapawo@matech-cameroun.com","521","15-04-2025 07:27=
:39","MATECH CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0004809017","Mba=
nkolo petit paris","","15-04-2025 06:25:58","15-04-2025 06:19:40","15-04-20=
25 08:25:20","site went down because Gen failed to start due to battery GE =
faulty //Gen manually started with external battery","Mboua Thierry","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Generator Battery","site went dow=
n because Gen failed to start due to battery GE faulty //Gen manually start=
ed with external battery","cedric.tiani@matech-cameroun.com","378","15-04-2=
025 06:25:58","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004808885","MEH=
ANDAN","","15-04-2025 05:25:21","15-04-2025 05:17:07","15-04-2025 05:54:07"=
,"Site went down due to insufficiency of rectifiers on site SS IHS Pascalin=
e is confirm // Site stabilised","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to insufficiency of r=
ectifiers on site SS IHS Pascaline is confirm // Site stabilised","cedric.t=
iani@matech-cameroun.com","495","15-04-2025 05:25:21","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004808832","A=
kak-Nkozoa-MTN-IHS","","15-04-2025 05:13:03","15-04-2025 05:09:52","15-04-2=
025 07:21:22","Grid outage,gen start and stopped due to low oil pressure //=
We add oil and gen manually started","Fabrice Pouakam","Equipment Repair","=
Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage,gen start and st=
opped due to low oil pressure //We add oil and gen manually started","edwig=
e.kapawo@matech-cameroun.com","193","15-04-2025 05:13:03","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004808734","Lad=
a I Yde","","15-04-2025 04:28:01","15-04-2025 04:25:38","15-04-2025 05:05:5=
5","site went down due to Grid fluctuation // Site put on Gen","Mba Lazare =
Herve","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply=
 Issue","site went down due to Grid fluctuation // Site put on Gen","edwige=
.kapawo@matech-cameroun.com","144","15-04-2025 04:28:01","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004808707","Beh=
ind P T school Yde","","15-04-2025 04:23:21","15-04-2025 04:15:57","15-04-2=
025 07:41:52","Site went down due to insufficience of rectifier causing by =
02/05 slots faulty, SS IHS FRANCOIS is informed  // He disconnected the fau=
lty slots of rectifier ","Paul BIBOUM","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to 02/05 Rectifiers faulty on s=
ite // He removed and replaced the faulty rectifier ","edwige.kapawo@matech=
-cameroun.com","445","15-04-2025 04:23:21","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004808593","E=
kombitie","","15-04-2025 03:28:50","15-04-2025 02:58:09","15-04-2025 04:10:=
53","Active: no power issue, site is on Gen with Ubaie=3D55V, Symphorien(65=
0257151) from huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no =
power issue, site is on Gen with Ubaie=3D55V, Symphorien(650257151) from hu=
awei is informed","edwige.kapawo@matech-cameroun.com","1842","15-04-2025 03=
:28:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004808331","MEHANDAN=
","","15-04-2025 01:32:01","15-04-2025 01:30:55","15-04-2025 01:57:01","Sit=
e went down due to insufficience of rectifiers on site SS IHS Pascaline is =
informed // He reset the rectifier	","Albran Byorel","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","Site went down due to insufficience =
of rectifiers on site SS IHS Pascaline is informed // He reset the rectifie=
r	","joelle.ekessi@ihstowers.com","68","15-04-2025 01:32:01","MATECH CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004808258","Nko=
abang entree carriere","IHS_YND_792, IHS_YND_795","15-04-2025 01:09:56","15=
-04-2025 01:06:42","15-04-2025 01:10:56","no power issue on site ,site on G=
rid with Ubaie=3D54.3 V The Tx FME Eloudou//693212405 from Huawei is inform=
ed","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","no power issue on site ,site on Grid wit=
h Ubaie=3D54.3 V The Tx FME Eloudou//693212405 from Huawei is informed","ed=
wige.kapawo@matech-cameroun.com","194","15-04-2025 01:09:56","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004808255","Lad=
a I Yde","","15-04-2025 01:08:39","15-04-2025 01:06:42","15-04-2025 01:10:5=
6","","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Cascad=
e Active","no power issue on site ,site on Grid with Ubaie=3D54.3 V The Tx =
FME Eloudou//693212405 from Huawei is informed","edwige.kapawo@matech-camer=
oun.com","262564","15-04-2025 01:08:39","MATECH CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0004808249","NKO=
ABANG NKOLO 3","","15-04-2025 01:07:45","15-04-2025 01:06:42","15-04-2025 0=
1:10:56","","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","=
Cascade Active","no power issue on site ,site on Grid with Ubaie=3D54.3 V T=
he Tx FME Eloudou//693212405 from Huawei is informed","edwige.kapawo@matech=
-cameroun.com","262564","15-04-2025 01:07:45","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004808205","E=
kombitie","","15-04-2025 00:54:58","15-04-2025 00:50:45","15-04-2025 00:56:=
10","Active: no power issue, site is on Gen with Ubaie=3D55V, Symphorien(65=
0257151) from huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no =
power issue, site is on Gen with Ubaie=3D55V, Symphorien(650257151) from hu=
awei is informed","edwige.kapawo@matech-cameroun.com","254","15-04-2025 00:=
54:58","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004808167","Beh=
ind P T school Yde","","15-04-2025 00:36:22","15-04-2025 00:34:00","15-04-2=
025 01:20:14","Access issues during the night   Grid outage,site went down =
because Gen failed to start (investigation ongoing) //Grid return","Paul BI=
BOUM","Access Denial","Lease Or Legal","Landlord Related Issues","Access Is=
sue - Land Lord","Access issues during the night   Grid outage,site went do=
wn because Gen failed to start (investigation ongoing) //Grid return","edwi=
ge.kapawo@matech-cameroun.com","143","15-04-2025 00:36:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004808111","Nsimalen=
 OCM","","15-04-2025 00:26:11","14-04-2025 23:02:48","14-04-2025 23:05:57",=
"Cascaded Incident from TTO4910232","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down before=
 Gen start due to poor backup // Grid return","system","270111","15-04-2025=
 00:26:11","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004808101","N=
kolda","IHS_YND_327","15-04-2025 00:24:40","14-04-2025 23:02:48","14-04-202=
5 23:05:57","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Albran Byorel","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Grid return","cedric.tiani@matech-cameroun.com",=
"4913","15-04-2025 00:24:40","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004808024","N=
KOLMEKONG YDE","","15-04-2025 00:00:30","14-04-2025 23:54:16","15-04-2025 0=
0:16:55","Grid fluctuation,site went down because Gen failed to start  due =
to Grid bad voltage//He bypassed the Grid and site on Gen","Fabrice Pouakam=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation,site went down because Gen failed to start  due to Grid b=
ad voltage//He bypassed the Grid and site on Gen","joelle.ekessi@ihstowers.=
com","375","15-04-2025 00:00:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004807902","Emana Ly=
cee","","14-04-2025 23:40:18","14-04-2025 23:25:26","15-04-2025 00:29:37","=
Cascaded Incident from TTO4910003","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,Site went down becaus=
e Gen start and stopped due to ""high temp"" alarm//We add water and Gen ma=
nually started","system","283117","14-04-2025 23:40:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0004807901","Emana ly=
cee 2","IHS_YND_274","14-04-2025 23:39:47","14-04-2025 23:25:26","15-04-202=
5 00:29:37","Grid outage,Site went down because Gen start and stopped due t=
o ""high temp"" alarm//We added water and Gen manually started","Fabrice Po=
uakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Grid outage,Site went down because Gen start and stopp=
ed due to ""high temp"" alarm//We added water and Gen manually started","jo=
elle.ekessi@ihstowers.com","862","14-04-2025 23:39:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0004807883","Messassi=
 okolo","","14-04-2025 23:34:29","14-04-2025 17:14:26","14-04-2025 17:53:57=
","Cascaded Incident from TTO4907834","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to rectifie=
rs dysfunctionning //We reset rectifiers and site on grid","system","290962=
","14-04-2025 23:34:29","MATECH CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004807863","Lab=
oratoire  Meka","","14-04-2025 23:27:32","14-04-2025 23:18:20","14-04-2025 =
23:37:51","Site went down due to insufficient rectifiers on site //Site sta=
bilised","","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to insufficient rectifiers on site //Site stabilised","edw=
ige.kapawo@matech-cameroun.com","553","14-04-2025 23:27:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004807758","OLAMA","=
","14-04-2025 23:01:03","14-04-2025 22:36:56","14-04-2025 22:40:03","Active=
//No power issue on site, Site on Battery, UBAIE=3D51.1V.( the starting thr=
eshold ubaie=3D47.5 VThe TX FME Henri (699949693) from Huawei is informed",=
"Fanda Brice","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active//No power issue on site, Site on Battery, =
UBAIE=3D51.1V.( the starting threshold ubaie=3D47.5 VThe TX FME Henri (6999=
49693) from Huawei is informed","joelle.ekessi@ihstowers.com","1448","14-04=
-2025 23:01:03","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004807721","SAA=
 Entrance","","14-04-2025 22:49:00","14-04-2025 22:44:41","14-04-2025 23:00=
:09","Grid fluctuation, site went down because Gen failed to start due to G=
rid contactor not excited//He excited and site on Grid","Parker Tchoup","Eq=
uipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid fluctuation=
, site went down because Gen failed to start due to Grid contactor not exci=
ted//He excited and site on Grid","edwige.kapawo@matech-cameroun.com","260"=
,"14-04-2025 22:49:00","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004807695","Cit=
e des nations","","14-04-2025 22:45:46","14-04-2025 22:39:03","14-04-2025 2=
2:45:03","Active //No power issue ,site on Grid on site with Ubaie=3D53 V X=
 Fme Hosiah / 674007438 from huawei is informed","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active //No power issue ,site on Grid on site with Ubaie=3D53 V X Fme Hosia=
h / 674007438 from huawei is informed","edwige.kapawo@matech-cameroun.com",=
"404","14-04-2025 22:45:46","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004807625","NYO=
M FACE MAETUR","","14-04-2025 22:21:33","14-04-2025 22:03:21","15-04-2025 0=
1:08:47","Grid outage,Site went down because Gen failed to start due to Gri=
d contactor not exciting//He excited and site on Grid","Fabrice Pouakam","E=
quipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,Sit=
e went down because Gen failed to start due to Grid contactor not exciting/=
/He excited and site on Grid","gerard.tchangoue@matech-cameroun.com","1093"=
,"14-04-2025 22:21:33","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004807616","C=
rf-Nkolbisson","","14-04-2025 22:19:45","14-04-2025 22:14:39","14-04-2025 2=
2:38:12","Site went down Because disjunction of Cb due to the site load whi=
ch increased there from (we need second depart)// CB rearmed","TIENTCHEU NZ=
ETCHIEU GAEL","Equipment Repair","Passive","Rectifier","Rectifier - Circuit=
 Breaker","Site went down Because disjunction of Cb due to the site load wh=
ich increased there from (we need second depart)// CB rearmed","edwige.kapa=
wo@matech-cameroun.com","307","14-04-2025 22:19:45","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004807206","N=
kolondom","","14-04-2025 21:08:58","14-04-2025 21:01:41","14-04-2025 22:36:=
22","Grid outage,Gen failed to start due to main Gen faulty//Grid reurn","F=
abrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator F=
aulty","Grid outage,Gen failed to start due to main Gen faulty//Grid reurn"=
,"edwige.kapawo@matech-cameroun.com","439","14-04-2025 21:08:58","MATECH CM=
R"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004807049","B=
iteng-Maetur","","14-04-2025 20:35:20","14-04-2025 20:27:11","15-04-2025 01=
:38:34","Site went down due to insufficient rectifiers on site//He reset an=
d site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to insufficient rectifiers on site/=
/He reset and site on Grid","edwige.kapawo@matech-cameroun.com","490","14-0=
4-2025 20:35:20","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004806957","C=
rf-Nkolbisson","","14-04-2025 20:14:16","14-04-2025 20:03:59","14-04-2025 2=
0:25:22","Site went down Because disjunction of Cb due to the site load whi=
ch increased there from (we need second depart)// CB rearmed","TIENTCHEU NZ=
ETCHIEU GAEL","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Circuit Breaker Issue","Site went down Because disjunction of Cb due to th=
e site load which increased there from (we need second depart)// CB rearmed=
","edwige.kapawo@matech-cameroun.com","618","14-04-2025 20:14:16","MATECH C=
MR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004806950","NYO=
M 2 IHS","","14-04-2025 20:12:13","14-04-2025 20:07:04","14-04-2025 21:03:0=
4","Grid outage, site went down because gen start and stopped with alarm hi=
gh temperature due to accordion of radiator cut // He welded the accordion =
and gen manually started","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","ACDG - Radiator","Grid outage, site went down because gen start a=
nd stopped with alarm high temperature due to accordion of radiator cut // =
He welded the accordion and gen manually started","gerard.tchangoue@matech-=
cameroun.com","310","14-04-2025 20:12:13","MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004806916","Mes=
sassi okolo","","14-04-2025 20:05:17","14-04-2025 19:56:01","14-04-2025 20:=
09:35","Grid outage, Site went down before Gen start due to poor backup // =
Grid return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, Site went down before Gen star=
t due to poor backup // Grid return","stephane.nkamwa@ihstowers.com","557",=
"14-04-2025 20:05:17","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004806873","M=
essassi okolo","","14-04-2025 19:51:31","14-04-2025 19:45:19","14-04-2025 1=
9:53:26","wrongly ticket","Fabrice Pouakam","Incorrectly Logged Tickets","E=
rror","Error","Error","wrongly ticket","edwige.kapawo@matech-cameroun.com",=
"374","14-04-2025 19:51:31","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004806840","N=
KOLMEKONG YDE","","14-04-2025 19:45:09","14-04-2025 19:36:56","14-04-2025 2=
0:25:56","Grid outage, gen ran until fuel shortage//Tank inclined","Fabrice=
 Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, ge=
n ran until fuel shortage//Tank inclined","edwige.kapawo@matech-cameroun.co=
m","494","14-04-2025 19:45:09","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004806700","Beh=
ind P T school Yde","","14-04-2025 19:09:30","14-04-2025 19:07:59","14-04-2=
025 19:11:59","Grid outage, site down due to poor backup // Grid restored",=
"Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Battery Low","Grid outage, site down due to poor backup // Grid restored",=
"gerard.tchangoue@matech-cameroun.com","92","14-04-2025 19:09:30","MATECH C=
MR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0004806489","ETO=
UDI CHAPELLE","","14-04-2025 18:40:21","14-04-2025 18:39:13","14-04-2025 18=
:40:13","Site went down because of insufficient rectifiers //site stabilize=
d","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down because of insufficient rectifiers //site stabilized",=
"gerard.tchangoue@matech-cameroun.com","69","14-04-2025 18:40:21","MATECH C=
MR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004806486","E=
MANA BILICK CITY","","14-04-2025 18:39:54","14-04-2025 18:32:46","14-04-202=
5 20:28:21","Site went down because the Gen Cb dysjuncted due to load on si=
te  // He reamed Gen Cb","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Load Breaker","Site went down because the Gen Cb dysjuncted=
 due to load on site  // He reamed Gen Cb","edwige.kapawo@matech-cameroun.c=
om","430","14-04-2025 18:39:54","MATECH CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004806460","Mvo=
g-Betsi","","14-04-2025 18:37:08","14-04-2025 18:33:03","14-04-2025 18:51:0=
3","Grid fluctuation, Site went down because Gen failed to start due to Gri=
d bad voltage // Grid stabilized","Hyemafo Gildas","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site we=
nt down because Gen failed to start due to Grid bad voltage // Grid stabili=
zed","gerard.tchangoue@matech-cameroun.com","247","14-04-2025 18:37:08","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004806445","C=
rf-Nkolbisson","","14-04-2025 18:33:43","14-04-2025 18:27:34","14-04-2025 1=
9:15:34","Disjunction in the energie bay due to the site load which increas=
ed there from (we need second depart)// disjunctor rearm","TIENTCHEU NZETCH=
IEU GAEL","Equipment Repair","Passive","Control Panel","Circuit Breaker Tri=
pped","Disjunction in the energie bay due to the site load which increased =
there from (we need second depart)// disjunctor rearm","edwige.kapawo@matec=
h-cameroun.com","370","14-04-2025 18:33:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004806437","Emana Ly=
cee","","14-04-2025 18:32:22","14-04-2025 18:28:07","14-04-2025 18:31:58","=
Cascaded Incident from TTO4908248","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen start automatically","system","272156=
","14-04-2025 18:32:22","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004806432","E=
mana lycee 2","IHS_YND_274","14-04-2025 18:31:44","14-04-2025 18:28:07","14=
-04-2025 18:45:00","Grid outage, Site went down before Gen start due to poo=
r backup // Gen start automatically","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site w=
ent down before Gen start due to poor backup // Gen start automatically","e=
dwige.kapawo@matech-cameroun.com","218","14-04-2025 18:31:44","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004806347","B=
iyemassi LAC","","14-04-2025 18:13:50","14-04-2025 18:04:41","14-04-2025 18=
:54:50","Site went down due to CB(125A)in PWC that tripped OCM//He rearmed =
the CB","","Equipment Repair","Passive","Control Panel","Power Cabinet - Ci=
rcuit Breaker Issue","Site went down due to CB(125A)in PWC that tripped OCM=
//He rearmed the CB","edwige.kapawo@matech-cameroun.com","550","14-04-2025 =
18:13:50","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004806175","Acc=
acia New","","14-04-2025 17:36:00","14-04-2025 17:35:54","14-04-2025 20:23:=
54","Site went down because malfunction of rectifiers due to high temp caus=
ing by fan stop  // he turned the fans back on","","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","Site went down because malfunction of =
rectifiers due to high temp causing by fan stop  // he turned the fans back=
 on
","gerard.tchangoue@matech-cameroun.com","8","14-04-2025 17:36:00","MATECH =
CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004806079","M=
essassi 2","IHS_YND_279","14-04-2025 17:17:35","14-04-2025 17:14:26","14-04=
-2025 20:22:29","Site went down due to rectifiers malfunctioning // reset o=
f rectifiers and site on grid","Fabrice Pouakam","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to rectifiers malfunc=
tioning // reset of rectifiers and site on grid","edwige.kapawo@matech-came=
roun.com","190","14-04-2025 17:17:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004806038","Angongo"=
,"","14-04-2025 17:10:40","14-04-2025 17:00:59","14-04-2025 18:34:29","Casc=
aded Incident from TTO4907765","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site Went Down due to high temp // added =
water","system","1226809","14-04-2025 17:10:40","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004806034","E=
beba","IHS_YND_335","14-04-2025 17:09:53","14-04-2025 17:00:59","14-04-2025=
 18:34:29","Site Went Down due to high temp // added water","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","Gen Temp High","Site Went Down due =
to high temp // added water","edwige.kapawo@matech-cameroun.com","535","14-=
04-2025 17:09:53","MATECH CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0004806028","Nke=
ng likok","","14-04-2025 17:08:45","14-04-2025 17:04:42","14-04-2025 17:07:=
42","No power issue on site ,site on Grid with Ubaie=3D52 V The TX FME Etie=
nne(695033981) from Huawei is informed.","Kemeni Franklin","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site ,site on Grid with Ubaie=3D52 V The TX FME Etienne(69503=
3981) from Huawei is informed.","gerard.tchangoue@matech-cameroun.com","243=
","14-04-2025 17:08:45","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004806026","B=
iyemassi LAC","","14-04-2025 17:07:16","14-04-2025 16:55:59","14-04-2025 17=
:07:37","Site went Down because Noya (658849259/From LOUMAD) as on site for=
 swap DC BOX // End of works","","Installation Activity","Passive","Planned=
 Activity","Installation Activity","Site went Down because Noya (658849259/=
From LOUMAD) as on site for swap DC BOX // End of works","edwige.kapawo@mat=
ech-cameroun.com","679","14-04-2025 17:07:16","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004806025","Odz=
a petit marche new","","14-04-2025 17:07:07","14-04-2025 16:35:47","14-04-2=
025 17:21:47","Site went down due to rectifier dysfunctionning//We reset re=
ctifier and site on grid","Albran Byorel","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down due to rectifier dysfunctionning=
//We reset rectifier and site on grid","gerard.tchangoue@matech-cameroun.co=
m","1881","14-04-2025 17:07:07","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004805895","Acc=
acia New","","14-04-2025 16:53:14","14-04-2025 16:51:01","14-04-2025 17:10:=
01","Grid only, site went Down due to Grid outage // grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,=
no space to deploy a mobil gen // grid return","gerard.tchangoue@matech-cam=
eroun.com","196","14-04-2025 16:53:14","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004805838","NYO=
M FACE MAETUR","","14-04-2025 16:47:10","14-04-2025 16:45:59","14-04-2025 1=
7:15:59","Grid outage, site went down because gen failed to start due to gr=
id contactor faulty // He bypassed ATS and Gen manually started","Fabrice P=
ouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid =
outage, site went down because gen failed to start due to grid contactor fa=
ulty // He bypassed ATS and Gen manually started","edwige.kapawo@matech-cam=
eroun.com","73","14-04-2025 16:47:10","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004805790","Cit=
e des nations","","14-04-2025 16:41:46","14-04-2025 16:36:36","14-04-2025 1=
6:43:22","Our technician Paul is informed and says that, Active/ No power i=
ssue on site Ubay 53V site on Grid mBAH Osiah (674007438/Huawei) is informe=
d.","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Our technician Paul is informed and says that=
, Active/ No power issue on site Ubay 53V site on Grid mBAH Osiah (67400743=
8/Huawei) is informed.","gerard.tchangoue@matech-cameroun.com","311","14-04=
-2025 16:41:46","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004805465","O=
dza II OCM","","14-04-2025 16:20:59","14-04-2025 16:16:50","14-04-2025 16:3=
4:46","Grid outage gen failed to start due to card GE dysfunctionning//Grid=
 return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid outage gen failed to start due to card GE dysfunctionnin=
g//Grid return","edwige.kapawo@matech-cameroun.com","251","14-04-2025 16:20=
:59","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004805408","Nsi=
malen MTN","","14-04-2025 16:10:57","14-04-2025 16:04:44","14-04-2025 16:27=
:44","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automatically","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen started automatically","gerard.tchang=
oue@matech-cameroun.com","374","14-04-2025 16:10:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004805367","Mvog-Eba=
nda","","14-04-2025 16:07:52","14-04-2025 15:11:46","14-04-2025 16:30:27","=
Cascaded Incident from TTO4906719","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due=
 to alarm underfrequency//We reset card GE and gen manually started ","syst=
em","269846","14-04-2025 16:07:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004805256","Nsimalen=
 OCM","","14-04-2025 15:54:43","14-04-2025 15:47:42","14-04-2025 15:51:37",=
"Cascaded Incident from TTO4906912","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down before=
 Gen start due to poor backup // Grid return","system","267695","14-04-2025=
 15:54:43","MATECH CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004805247","N=
kolda","IHS_YND_327","14-04-2025 15:52:49","14-04-2025 15:47:42","14-04-202=
5 15:51:37","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Albran Byorel","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Grid return","edwige.kapawo@matech-cameroun.com"=
,"308","14-04-2025 15:52:49","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0004805078","A=
bom","IHS_YND_269","14-04-2025 15:31:53","14-04-2025 15:11:46","14-04-2025 =
16:30:27","Grid outage.gen failed to start due to alarm underfrequency//We =
reset card GE and gen manually started ","Siligap Boris","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to sta=
rt due to alarm underfrequency//We reset card GE and gen manually started "=
,"edwige.kapawo@matech-cameroun.com","1208","14-04-2025 15:31:53","MATECH C=
MR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004804817","O=
lembe-Terminus","","14-04-2025 14:57:45","14-04-2025 14:55:36","14-04-2025 =
15:00:32","Site down due to work done by Fabrice (657108613)// End of work"=
,"Fabrice Pouakam","Equipment Replacement","Passive","Planned Activity","Pl=
anned Activity - Passive","Site down due to work done by Fabrice (657108613=
)// End of work","mouliom.anselme@matech-cameroun.com","131","14-04-2025 14=
:57:45","MATECH CMR"
"Closed Complete","Site Down","T3172","IHS_YND_043","NOCINC0004804807","Emi=
a","","14-04-2025 14:54:40","14-04-2025 14:38:32","14-04-2025 16:29:13","No=
 power issue site on grid with U=3D50.5V Mbah osiah(674007438) from Huawei =
is informed","","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","No power issue site on grid with U=3D50.5V Mbah=
 osiah(674007438) from Huawei is informed","gerard.tchangoue@matech-camerou=
n.com","969","14-04-2025 14:54:40","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004804799","NYO=
M FACE MAETUR","","14-04-2025 14:53:55","14-04-2025 14:36:33","14-04-2025 1=
6:08:15","Grid outage, site went down because gen failed to start due to gr=
id contactor faulty // He bypassed ATS and Gen manually started","Fabrice P=
ouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid =
outage, site went down because gen failed to start due to grid contactor fa=
ulty // He bypassed ATS and Gen manually started","gerard.tchangoue@matech-=
cameroun.com","1043","14-04-2025 14:53:55","MATECH CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004804795","M=
ontesquieux","","14-04-2025 14:53:29","14-04-2025 14:51:20","14-04-2025 15:=
06:20","Site went down due to Deficiency rectifiers on site//site stabilise=
d","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to Deficiency rectifiers on site//site stabilised","m=
ouliom.anselme@matech-cameroun.com","129","14-04-2025 14:53:29","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0004804611","Biteng-M=
aetur","","14-04-2025 14:22:25","14-04-2025 12:00:11","14-04-2025 15:10:38"=
,"Site went down due to insufficiency of rectifiers//We reset rectifiers si=
te on grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down due to insufficiency of rectifiers//We rese=
t rectifiers site on grid","christelle.ngonga@matech-cameroun.com","8536","=
14-04-2025 14:22:25","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004804536","Nko=
zoa","","14-04-2025 14:08:27","14-04-2025 13:58:09","14-04-2025 14:42:50","=
Grid outage, site went down due to gen overload (20kva, 340A) // He reduced=
 the load and site on GEN","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen overloa=
d (20kva, 340A) // He reduced the load and site on GEN","franck.nkomot@mate=
ch-cameroun.com","656","14-04-2025 14:08:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004804527","TSINGA V=
ILLAGE 2","","14-04-2025 14:06:54","14-04-2025 13:57:35","14-04-2025 15:12:=
45","Cascaded Incident from TTO4906026","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage.gen failed to sta=
rt due to alarm low oil pressure//Grid return","system","266641","14-04-202=
5 14:06:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004804528","Nkongtoc=
k","","14-04-2025 14:06:54","14-04-2025 13:57:35","14-04-2025 15:12:45","Ca=
scaded Incident from TTO4906026","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due=
 to alarm low oil pressure//Grid return","system","266640","14-04-2025 14:0=
6:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004804524","Nkolfoul=
ou 2","","14-04-2025 14:06:53","14-04-2025 13:57:35","14-04-2025 15:12:45",=
"Cascaded Incident from TTO4906026","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start du=
e to alarm low oil pressure//Grid return","system","266641","14-04-2025 14:=
06:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004804526","Odza II =
OCM","","14-04-2025 14:06:53","14-04-2025 13:57:35","14-04-2025 15:12:45","=
Cascaded Incident from TTO4906026","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due=
 to alarm low oil pressure//Grid return","system","266640","14-04-2025 14:0=
6:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004804525","Melen Ba=
'aba","","14-04-2025 14:06:53","14-04-2025 13:57:35","14-04-2025 15:12:45",=
"Cascaded Incident from TTO4906026","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start du=
e to alarm low oil pressure//Grid return","system","266640","14-04-2025 14:=
06:53","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004804476","Eto=
ug ebe Carrefour","","14-04-2025 14:01:23","14-04-2025 13:57:06","14-04-202=
5 14:03:06","Grid fluctuation,site went down because Gen failed to start du=
e to Grid bad voltage//He bypassed the Grid and site on Gen","Hyemafo Gilda=
s","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation,site went down because Gen failed to start due to Grid b=
ad voltage//He bypassed the Grid and site on Gen","ludivine.ngamaleu@ihstow=
ers.com","257","14-04-2025 14:01:23","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004804470","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_527, IHS_YND_719, IHS_YND_349=
","14-04-2025 14:00:46","14-04-2025 13:57:35","14-04-2025 15:14:27","Grid o=
utage.gen failed to start due to alarm low oil pressure//Grid return","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure=
","Grid outage.gen failed to start due to alarm low oil pressure//Grid retu=
rn","christelle.ngonga@matech-cameroun.com","191","14-04-2025 14:00:46","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_234","IHS_YND_415","NOCINC0004804450","B=
oga-Mahole","","14-04-2025 13:55:22","14-04-2025 13:39:15","14-04-2025 14:5=
6:08","Grid outage,Site went down because Gen failed to start due to Grid c=
ontactor dysfunctionning // He bypass it site on grid","Kemeni Franklin","E=
quipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,Sit=
e went down because Gen failed to start due to Grid contactor dysfunctionni=
ng // He bypass it site on grid","franck.nkomot@matech-cameroun.com","968",=
"14-04-2025 13:55:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004804439","Ebogo","=
","14-04-2025 13:53:18","14-04-2025 13:42:10","14-04-2025 15:48:30","Grid o=
utage gen ran until fuel shortage//Refueling done (200l)","Siligap Boris","=
Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran until =
fuel shortage//Refueling done (200l)","christelle.ngonga@matech-cameroun.co=
m","1652","14-04-2025 13:53:18","MATECH CMR"
"Closed Complete","Warning","T0046","IHS_YND_191","NOCINC0004804367","Mball=
a II","","14-04-2025 13:39:45","","","Site alarming due to Grid outage  // =
Gen start automatically","Delor Telezing","Warning","Warning","POWER","Warn=
ing - Low Voltage","Site alarming due to Grid outage  // Gen start automati=
cally","franck.nkomot@matech-cameroun.com","1099","14-04-2025 13:39:45","MA=
TECH CMR"
"Closed Complete","Warning","T0046","IHS_YND_191","NOCINC0004804359","Mball=
a II","","14-04-2025 13:37:41","","","Site alarming due to Grid outage  // =
Gen start automatically","Delor Telezing","Warning","Warning","POWER","Warn=
ing - Low Voltage","Site alarming due to Grid outage  // Gen start automati=
cally","franck.nkomot@matech-cameroun.com","972","14-04-2025 13:37:41","MAT=
ECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004804263","Nsi=
malen MTN","","14-04-2025 13:18:27","14-04-2025 13:12:19","14-04-2025 13:22=
:19","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","christelle.ngonga@matech-cameroun.com","3=
68","14-04-2025 13:18:27","MATECH CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0004804194","I=
mm-Olympique","","14-04-2025 13:01:01","14-04-2025 12:54:45","14-04-2025 13=
:35:23","Site went down due to disjunction of Cb(125*63)A in PWC // He ream=
ed Cb(125*63)A, site on grid","Paul BIBOUM","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due t=
o disjunction of Cb(125*63)A in PWC // He reamed Cb(125*63)A, site on grid"=
,"franck.nkomot@matech-cameroun.com","377","14-04-2025 13:01:01","MATECH CM=
R"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0004804048","A=
v-Germaine","","14-04-2025 12:39:55","14-04-2025 12:08:43","14-04-2025 14:1=
1:27","Site went Down because Hermane Abena (699999625 )  of DOWEN Service =
was working on site ( battery swapp , instalation of  DC Box ) // End of wo=
rk","","Installation Activity","Passive","Planned Activity","Installation A=
ctivity","Site went Down because Hermane Abena (699999625 )  of DOWEN Servi=
ce was working on site ( battery swapp , instalation of  DC Box ) // End of=
 work","franck.nkomot@matech-cameroun.com","1873","14-04-2025 12:39:55","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004803818","M=
EHANDAN","","14-04-2025 12:13:14","14-04-2025 12:05:06","14-04-2025 12:25:3=
3","Site went down due to insufficienciency of rectifiers//Grid return","Al=
bran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","S=
ite went down due to insufficienciency of rectifiers//Grid return","franck.=
nkomot@matech-cameroun.com","490","14-04-2025 12:13:14","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004803797","Odz=
a petit marche new","","14-04-2025 12:08:23","14-04-2025 11:52:12","14-04-2=
025 13:10:07","Site went down due to rectifier dysfunctionning//We reset re=
ctifier and site on grid","Albran Byorel","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down due to rectifier dysfunctionning=
//We reset rectifier and site on grid","franck.nkomot@matech-cameroun.com",=
"972","14-04-2025 12:08:23","MATECH CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0004803602","S=
OA 2","","14-04-2025 11:33:59","14-04-2025 11:06:53","14-04-2025 11:10:17",=
"No power issue site on grid with U=3D56.4 v Julien(693095849) from Huawei =
is informed site up at 11:47 AM","Siligap Boris","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 site on grid with U=3D56.4 v Julien(693095849) from Huawei is informed sit=
e up at 11:47 AM","olivier.kwedi@ihstowers.com","1627","14-04-2025 11:33:59=
","MATECH CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0004803585","S=
oa-II","","14-04-2025 11:28:57","14-04-2025 11:06:50","14-04-2025 13:19:24"=
," No power issue on site  U:53.3 V , site on grid ,  Julien ( 693095849 ) =
of Huawe is informed ,evicences awaited from feme","Siligap Boris","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m"," No power issue on site  U:53.3 V , site on grid ,  Julien ( 693095849 =
) of Huawe is informed","franck.nkomot@matech-cameroun.com","1328","14-04-2=
025 11:28:57","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004803238","E=
MANA BILICK CITY","","14-04-2025 10:40:31","14-04-2025 10:23:24","14-04-202=
5 10:25:55","No power issue site on grid with U=3D54v Notice that site is i=
mpacted by Emana Lycee2 ","Fabrice Pouakam","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on grid with U=3D54v Notice that site is impacted by Emana Lycee2 ","olivi=
er.kwedi@ihstowers.com","1028","14-04-2025 10:40:31","MATECH CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004803193","NKO=
LOSSAN OKOK","","14-04-2025 10:34:25","14-04-2025 10:23:08","14-04-2025 14:=
59:57","Grid outage gen failed to start due to automation malfunctiong//Gen=
 manually started","Parker Tchoup","Equipment Repair","Passive","Control Pa=
nel","ATS-AMF Issue","Grid outage gen failed to start due to automation mal=
functiong//Gen manually started","ludivine.ngamaleu@ihstowers.com","678","1=
4-04-2025 10:34:25","MATECH CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0004803177","S=
oa-Sofamac","","14-04-2025 10:31:35","14-04-2025 10:24:29","14-04-2025 11:3=
0:01","TX issue   U:56.4 V  site  on batteryb Julien ( 693095849 )  of Huaw=
ei is working on site ","Siligap Boris","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","TX issue   U:56.4 V  si=
te  on batteryb Julien ( 693095849 )  of Huawei is working on site ","franc=
k.nkomot@matech-cameroun.com","426","14-04-2025 10:31:35","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004803135","B=
iteng-Maetur","","14-04-2025 10:24:44","14-04-2025 10:08:37","14-04-2025 11=
:45:37","Site went down due to insufficiency of rectifiers//We reset rectif=
iers site on grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down due to insufficiency of rectifiers//=
We reset rectifiers site on grid","olivier.kwedi@ihstowers.com","969","14-0=
4-2025 10:24:44","MATECH CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0004803115","M=
adagascar-Yde-New","","14-04-2025 10:19:33","14-04-2025 10:00:22","14-04-20=
25 10:21:50","Site went down due to work by Herman Abena(699999625) / DOWEN=
, SWAP of battery) // End of work","","Installation Activity","Passive","Pl=
anned Activity","Installation Activity","Site went down due to work by Herm=
an Abena(699999625) / DOWEN, SWAP of battery) // End of work","olivier.kwed=
i@ihstowers.com","1152","14-04-2025 10:19:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0004802971","Messassi=
 okolo","","14-04-2025 09:56:18","14-04-2025 09:36:39","14-04-2025 09:37:21=
","No power issue site on grid with U=3D54v Notice that site is impacted by=
 Emana Lycee2","Fabrice Pouakam","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wi=
th U=3D54v Notice that site is impacted by Emana Lycee2","system","1179","1=
4-04-2025 09:56:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004802970","Emana Ly=
cee","","14-04-2025 09:56:17","14-04-2025 09:36:39","14-04-2025 10:44:27","=
Cascaded Incident from TTO4904336","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuations.site went down =
due to bad grid voltage//Grid power stabilized","system","275217","14-04-20=
25 09:56:17","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0004802943","Ema=
na lycee 2","IHS_YND_274","14-04-2025 09:52:48","14-04-2025 09:36:39","14-0=
4-2025 10:45:43","Grid fluctuations.site went down due to bad grid voltage/=
/Grid power stabilized","Fabrice Pouakam","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Grid fluctuations.site went down d=
ue to bad grid voltage//Grid power stabilized","christelle.ngonga@matech-ca=
meroun.com","1164","14-04-2025 09:52:48","MATECH CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0004802919","Oss=
ombe","","14-04-2025 09:49:30","14-04-2025 09:32:18","14-04-2025 11:37:46",=
"Hybrid gen site .gen ran until fuel shortage//Refueling done","Parker Tcho=
up","Fuel Outage","Passive","Diesel","Diesel Outage","Hybrid gen site .gen =
ran until fuel shortage//Refueling done","christelle.ngonga@matech-cameroun=
.com","1177","14-04-2025 09:49:30","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004802626","M=
essassi 2","","14-04-2025 08:58:11","14-04-2025 08:55:02","14-04-2025 09:45=
:22","Site went down due to insufficieny of rectifiers//We reset rectifiers=
","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficieny of rectifiers//We reset rectifiers=
","christelle.ngonga@matech-cameroun.com","191","14-04-2025 08:58:11","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0004802426","N=
guila","","14-04-2025 08:23:53","14-04-2025 08:15:34","14-04-2025 10:03:09"=
,"Grid outage.gen failed to start due to card GE dysfunctionned //We reset =
card GE and gen manually started","Parker Tchoup","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to start due =
to card GE dysfunctionned //We reset card GE and gen manually started","chr=
istelle.ngonga@matech-cameroun.com","501","14-04-2025 08:23:53","MATECH CMR=
"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004802284","E=
kombitie","","14-04-2025 07:50:26","14-04-2025 07:41:17","14-04-2025 08:05:=
17","No power issue site on gen with U=3D54.5 V site on Gen. THE TX Synphor=
ien 691316854 of Huawei is informed","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue site on gen with U=3D54.36V site on Gen THE TX Synphorien 691316854 =
of Huawei is informed","franck.nkomot@matech-cameroun.com","550","14-04-202=
5 07:50:26","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0004802156","Nko=
abang Ebolmedjock","","14-04-2025 07:28:20","14-04-2025 07:14:11","14-04-20=
25 11:31:52","Grid outage.gen ran until fuel shortage//Refueling done","Mba=
 Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outag=
e.gen ran until fuel shortage//Refueling done","christelle.ngonga@matech-ca=
meroun.com","1992","14-04-2025 07:28:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_393","NOCINC0004802127","Ezezang"=
,"","14-04-2025 07:20:33","14-04-2025 07:12:14","14-04-2025 07:29:14","Site=
 went down due to work (PM) // End of work","Parker Tchoup","Equipment Repa=
ir","Passive","Planned Activity","Planned Activity - DCGG Gen","Site went d=
own due to work (PM) // End of work","christelle.ngonga@matech-cameroun.com=
","500","14-04-2025 07:20:33","MATECH CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0004802034","Lob=
o 2","","14-04-2025 06:59:29","14-04-2025 06:43:22","14-04-2025 10:44:29","=
Hybrid gen sitesite went down due to hybrid system failure//Gen manually st=
arted","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Hybrid","Hy=
brid Module","Hybrid gen sitesite went down due to hybrid system failure//G=
en manually started","franck.nkomot@matech-cameroun.com","968","14-04-2025 =
06:59:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0004801689","Monatele=
","","14-04-2025 05:23:42","14-04-2025 05:04:24","14-04-2025 05:30:22","Cas=
caded Incident from TTO4902901","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site ,site on G=
RID with Ubaie=3D54.4V The TX FME Gregoire(654547479) from Huawei is inform=
ed ","system","270056","14-04-2025 05:23:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_733","NOCINC0004801688","Nkog-Edz=
en","","14-04-2025 05:23:41","14-04-2025 05:04:24","14-04-2025 05:30:22","C=
ascaded Incident from TTO4902901","Parker Tchoup","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue on site ,site on=
 GRID with Ubaie=3D54.4V The TX FME Gregoire(654547479) from Huawei is info=
rmed ","system","270054","14-04-2025 05:23:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_337","NOCINC0004801687","Okola","=
","14-04-2025 05:23:41","14-04-2025 05:04:24","14-04-2025 05:30:22","Cascad=
ed Incident from TTO4902901","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active//No power issue on site ,s=
ite on GRID with Ubaie=3D54.4V The TX FME Gregoire(654547479) from Huawei i=
s informed ","system","270055","14-04-2025 05:23:41","MATECH CMR"
"Closed Complete","Site Down","T0053","IHS_YND_407","NOCINC0004801674","Mon=
atele MTN","IHS_YND_337, IHS_BMD_320, IHS_YND_530, IHS_YND_733, IHS_YND_406=
, IHS_YND_390","14-04-2025 05:12:35","14-04-2025 05:04:24","14-04-2025 07:4=
3:43","Active//No power issue on site ,site on GRID with Ubaie=3D54.4V The =
TX FME Gregoire(654547479) from Huawei is informed ","Parker Tchoup","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue on site ,site on GRID with Ubaie=3D54.4V The T=
X FME Gregoire(654547479) from Huawei is informed ","cedric.tiani@matech-ca=
meroun.com","492","14-04-2025 05:12:35","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004801462","Odz=
a petit marche new","","14-04-2025 03:02:46","14-04-2025 02:59:49","14-04-2=
025 03:29:30","Site went down due to insufficiency of rectifiers on site SS=
 IHS Pascaline is confirm // He reduced the load","Albran Byorel","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module","Site went down due to i=
nsufficiency of rectifiers on site SS IHS Pascaline is confirm // He reduce=
d the load","cedric.tiani@matech-cameroun.com","178","14-04-2025 03:02:46",=
"MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004801322","MEH=
ANDAN","","14-04-2025 01:58:57","14-04-2025 01:52:51","14-04-2025 05:26:33"=
,"Site went down due to insufficience of rectifiers on site SS IHS Pascalin=
e is informed // He reset the rectifier","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Site went down due to=
 insufficience of rectifiers on site SS IHS Pascaline is informed // He res=
et the rectifier","cedric.tiani@matech-cameroun.com","368","14-04-2025 01:5=
8:57","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004801239","MEH=
ANDAN","","14-04-2025 01:28:45","14-04-2025 01:25:33","14-04-2025 01:30:33"=
,"RECTIFIERS ISSUES","Albran Byorel","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to insufficient  rectifiers on si=
te//site stabilised","cedric.tiani@matech-cameroun.com","193","14-04-2025 0=
1:28:45","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004800739","Acc=
acia New","","13-04-2025 23:30:58","13-04-2025 23:29:50","13-04-2025 23:47:=
41","Grid outage ,no space to deploy a mobil gen // grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,n=
o space to deploy a mobil gen // grid return","cedric.tiani@matech-cameroun=
.com","70","13-04-2025 23:30:58","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004800737","M=
EHANDAN","","13-04-2025 23:30:42","13-04-2025 20:17:32","14-04-2025 01:08:0=
6","Site went  down due to rectifiers dysfunction//He reset it and site on =
Grid","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Site went  down due to rectifiers dysfunction//He reset it and site=
 on Grid","kouoh.jean@ihstowers.com","11592","13-04-2025 23:30:42","MATECH =
CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0004800708","Nko=
abang Ebolmedjock","","13-04-2025 23:20:10","13-04-2025 23:08:00","14-04-20=
25 00:05:32","Site went down because gen started and stopped with Alarm low=
 oil pressure//He reset the Gen Card and manually Started the Gen","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Site went down because gen started and stopped with Alarm low oil pressure/=
/He reset the Gen Card and manually Started the Gen","cedric.tiani@matech-c=
ameroun.com","731","13-04-2025 23:20:10","MATECH CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004800613","Mvo=
g-Betsi","","13-04-2025 22:48:54","13-04-2025 22:43:43","13-04-2025 22:49:5=
8","Site went down due to one of the AVR=92s pins disconnected (probably du=
e to vibration of the GENERATOR). //we have repositioned and recalibrated t=
he AVR (SX460).","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","=
ACDG - AVR","Site went down due to one of the AVR=92s pins disconnected (pr=
obably due to vibration of the GENERATOR). //we have repositioned and recal=
ibrated the AVR (SX460).","cedric.tiani@matech-cameroun.com","312","13-04-2=
025 22:48:54","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004800402","F=
ouda-New","","13-04-2025 22:03:33","13-04-2025 21:57:27","13-04-2025 22:10:=
29","Active// No power issue, site is on Grid with U=3D54.3 V The Tx Fme Ar=
mand //691144412 from Huawei is informed","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power issue, site is on Grid with U=3D54.3 V The Tx Fme Armand //69=
1144412 from Huawei is informed","joelle.ekessi@ihstowers.com","367","13-04=
-2025 22:03:33","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004800301","E=
mana Lycee","","13-04-2025 21:41:42","13-04-2025 21:34:20","13-04-2025 22:0=
1:37","Site up, awaiting feedback","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen start and stopped with high temp alarm // He added water and manuall=
y start the gen","edwige.kapawo@matech-cameroun.com","29463","13-04-2025 21=
:41:42","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004800285","Mes=
sassi 2","","13-04-2025 21:37:50","13-04-2025 21:33:44","13-04-2025 21:55:3=
5","Site went down due to insufficience of rectifier// He reduiced load","F=
abrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to insufficience of rectifier// He reduiced load","edw=
ige.kapawo@matech-cameroun.com","247","13-04-2025 21:37:50","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004800277","E=
mana lycee 2","IHS_YND_274","13-04-2025 21:36:32","13-04-2025 21:34:20","13=
-04-2025 22:01:37","Grid outage, site went down because gen start and stopp=
ed with high temp alarm // He added water and manually start the gen","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Te=
mp - Coolant Level Issue","Grid outage, site went down because gen start an=
d stopped with high temp alarm // He added water and manually start the gen=
","edwige.kapawo@matech-cameroun.com","133","13-04-2025 21:36:32","MATECH C=
MR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0004800257","Val=
lee Bastos MTN","","13-04-2025 21:30:42","13-04-2025 21:27:27","13-04-2025 =
22:31:27","Site went down because insufficient of rectifier //site stabiliz=
ed(need to added 01 rectifier)","Mboua Thierry","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down because insufficient of re=
ctifier //site stabilized(need to added 01 rectifier)","franck.nkomot@matec=
h-cameroun.com","196","13-04-2025 21:30:42","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004800254","NYO=
M FACE MAETUR","","13-04-2025 21:30:11","13-04-2025 21:26:01","13-04-2025 2=
3:10:18","Grid fluctuation,Site went down before Gen started due to Grid ba=
d voltage//He bypassed the Grid and site on Gen","Fabrice Pouakam","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation,Site went down before Gen started due to Grid bad voltage//He bypas=
sed the Grid and site on Gen","edwige.kapawo@matech-cameroun.com","251","13=
-04-2025 21:30:11","MATECH CMR"
"Closed Complete","Site Down","T1582","IHS_YND_138","NOCINC0004800248","Nko=
mkana 2","","13-04-2025 21:29:25","13-04-2025 21:20:19","13-04-2025 21:49:1=
9","site went down due to insufficient rectifiers on site//site stabilized(=
need to added one rectifier)","Mboua Thierry","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","site went down due to insufficient rectifie=
rs on site//site stabilized(need to added one rectifier)","franck.nkomot@ma=
tech-cameroun.com","547","13-04-2025 21:29:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004800234","Afanoya"=
,"","13-04-2025 21:27:08","13-04-2025 21:17:10","13-04-2025 21:36:47","Casc=
aded Incident from TTO4901219","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to MTN CB trip in t=
he power cabinet//He rearmed the CB","system","268996","13-04-2025 21:27:08=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0004800230","Ahala","=
","13-04-2025 21:26:00","13-04-2025 21:17:10","13-04-2025 21:36:47","Cascad=
ed Incident from TTO4901219","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to MTN CB trip in the=
 power cabinet//He rearmed the CB","system","268996","13-04-2025 21:26:00",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004800212","M=
eyo","IHS_YND_257, IHS_YND_313","13-04-2025 21:22:26","13-04-2025 21:17:10"=
,"13-04-2025 21:36:47","Site went down due to MTN CB trip in the power cabi=
net//He rearmed the CB","Hyemafo Gildas","Equipment Repair","Passive","Cont=
rol Panel","BTS Breaker Tripped","Site went down due to MTN CB trip in the =
power cabinet//He rearmed the CB","edwige.kapawo@matech-cameroun.com","317"=
,"13-04-2025 21:22:26","MATECH CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004800204","Mvo=
g-Betsi","","13-04-2025 21:19:52","13-04-2025 21:01:53","13-04-2025 21:19:5=
3","Grid fluctuation site went down because Gen failed to start due to Grid=
 bad voltage // He bypassed the Grid and site on Gen","Hyemafo Gildas","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation site went down because Gen failed to start due to Grid bad volt=
age // He bypassed the Grid and site on Gen","franck.nkomot@matech-cameroun=
.com","1080","13-04-2025 21:19:52","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004800039","B=
iyemassi LAC","","13-04-2025 20:47:46","13-04-2025 20:22:39","13-04-2025 20=
:30:39","Active: no power issue, site is on grid with Ubaie=3D48V; Hosiah (=
674007438) from Huawei is informed","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, =
site is on grid with Ubaie=3D48V; Hosiah (674007438) from Huawei is informe=
d","franck.nkomot@matech-cameroun.com","1509","13-04-2025 20:47:46","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004800032","B=
arriere","","13-04-2025 20:47:02","13-04-2025 20:23:42","13-04-2025 20:25:4=
2","Active//No power issue on site Ubay: 54.4V site on Grid Henry (69994969=
3/Huawei) is informed","Hyemafo Gildas","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue =
on site Ubay: 54.4V site on Grid Henry (699949693/Huawei) is informed","fra=
nck.nkomot@matech-cameroun.com","1401","13-04-2025 20:47:02","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004800011","C=
rf-Nkolbisson","","13-04-2025 20:41:22","13-04-2025 19:31:36","13-04-2025 2=
0:38:56","Grid fluctuation, site went down because gen fails to start due t=
o grid bad voltage // Grid stabilized","TIENTCHEU NZETCHIEU GAEL","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, site went down because gen fails to start due to grid bad voltage /=
/ Grid stabilized","edwige.kapawo@matech-cameroun.com","4187","13-04-2025 2=
0:41:22","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004799928","B=
iteng-Maetur","","13-04-2025 20:25:28","13-04-2025 20:17:19","13-04-2025 22=
:46:51","Site went down due to installation of new Generator (30kva) on sit=
e","Mba Lazare Herve","Installation Activity","Passive","Planned Activity",=
"Installation Activity","Site went down due to installation of new Generato=
r (30kva) on site","edwige.kapawo@matech-cameroun.com","491","13-04-2025 20=
:25:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004799826","Nkolfon =
Cimencam","","13-04-2025 19:57:35","13-04-2025 19:37:59","13-04-2025 20:51:=
14","Cascaded Incident from TTO4900738","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to CB in P=
WC that tripped MTN//He rearmed the CB","system","267983","13-04-2025 19:57=
:35","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004799805","M=
eyo","IHS_YND_257, IHS_YND_762","13-04-2025 19:47:40","13-04-2025 19:37:59"=
,"13-04-2025 20:51:14","Site went down due to MTN CB trip in the power cabi=
net//He rearmed the CB","Hyemafo Gildas","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to M=
TN CB trip in the power cabinet//He rearmed the CB","edwige.kapawo@matech-c=
ameroun.com","581","13-04-2025 19:47:40","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0004799764","A=
hala","","13-04-2025 19:42:17","13-04-2025 19:37:59","13-04-2025 20:51:14",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Site went down due to CB in PWC that tripped MTN//He rearmed the C=
B","edwige.kapawo@matech-cameroun.com","267983","13-04-2025 19:42:17","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004799734","C=
rf-Nkolbisson","","13-04-2025 19:35:58","13-04-2025 19:31:34","13-04-2025 1=
9:31:35","wrongly ticket","TIENTCHEU NZETCHIEU GAEL","Incorrectly Logged Ti=
ckets","Error","Error","Error","wrongly ticket","edwige.kapawo@matech-camer=
oun.com","265","13-04-2025 19:35:58","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004799491","Nko=
zoa","","13-04-2025 18:48:30","13-04-2025 18:22:18","13-04-2025 19:08:18","=
Grid outage, site went down due to gen overload (20kva, 340A) // He reduced=
 the load and site on GEN","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen overloa=
d (20kva, 340A) // He reduced the load and site on GEN","franck.nkomot@mate=
ch-cameroun.com","1573","13-04-2025 18:48:30","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004799487","Acc=
acia New","","13-04-2025 18:47:15","13-04-2025 18:40:00","13-04-2025 18:50:=
00","Grid outage, No space to deploy a MDG//Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space =
to deploy a MDG//Grid return","franck.nkomot@matech-cameroun.com","437","13=
-04-2025 18:47:15","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004799352","Cit=
e des nations","","13-04-2025 18:16:53","13-04-2025 18:14:36","13-04-2025 1=
8:25:36","Our technician Paul is informed and says that, Active/ No power i=
ssue on site Ubay 53V site on Grid mBAH Osiah (674007438/Huawei) is informe=
d.","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Our technician Paul is informed and says that=
, Active/ No power issue on site Ubay 53V site on Grid mBAH Osiah (67400743=
8/Huawei) is informed.","franck.nkomot@matech-cameroun.com","137","13-04-20=
25 18:16:53","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004799350","Eto=
ug ebe Carrefour","","13-04-2025 18:16:03","13-04-2025 18:11:50","13-04-202=
5 18:17:50","Grid outage, Site went down because Gen failed to start due to=
 Grid bad voltage and poor backup //grid stabilized","Hyemafo Gildas","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid o=
utage, Site went down because Gen failed to start due to Grid bad voltage a=
nd poor backup //grid stabilized","franck.nkomot@matech-cameroun.com","254"=
,"13-04-2025 18:16:03","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004799273","O=
dza II OCM","","13-04-2025 18:03:01","13-04-2025 17:57:49","13-04-2025 18:1=
3:49","Grid fluctuation, site went down because gen fails to start due to g=
rid bad voltage // Grid Stabilized","Albran Byorel","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site w=
ent down because gen fails to start due to grid bad voltage // Grid Stabili=
zed","edwige.kapawo@matech-cameroun.com","315","13-04-2025 18:03:01","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004799114","MEHANDAN=
","","13-04-2025 17:34:19","13-04-2025 17:28:15","13-04-2025 19:57:55","Sit=
e went down due to insufficient  rectifiers on site//site stabilised","Albr=
an Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","Sit=
e went down due to insufficient  rectifiers on site//site stabilised","joel=
le.ekessi@ihstowers.com","366","13-04-2025 17:34:19","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004798948","Ebo=
go","","13-04-2025 17:03:40","13-04-2025 16:53:59","13-04-2025 17:06:59","G=
rid fluctuations, Site went down before Gen started due to poor backup // H=
e put site on Gen","Siligap Boris","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid fluctuations, Site went down befor=
e Gen started due to poor backup // He put site on Gen","edwige.kapawo@mate=
ch-cameroun.com","583","13-04-2025 17:03:40","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004798830","Man=
guiers Dispensaire","","13-04-2025 16:44:05","13-04-2025 16:40:45","13-04-2=
025 16:42:45","Site went down due to rectifiers deficiency  // rectifier re=
set done","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to rectifiers deficiency  // rectifier res=
et done","franck.nkomot@matech-cameroun.com","201","13-04-2025 16:44:05","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004798725","A=
wae Ewonkan","","13-04-2025 16:15:53","13-04-2025 16:07:38","13-04-2025 16:=
10:26","Grid outage site went down due to Gen Overload (20Kva, Iload 225 A)=
IHS SS Alphonse is informed // Grid Restored","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid R=
estored","edwige.kapawo@matech-cameroun.com","497","13-04-2025 16:15:53","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004798719","Abang","=
","13-04-2025 16:15:03","13-04-2025 16:06:39","13-04-2025 19:26:39","Cascad=
ed Incident from TTO4899419","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because the Cb(125A) of=
 PWC dysfonction due to load increased // He reamed the Cb","system","27353=
3","13-04-2025 16:15:03","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004798715","N=
kolangaa","IHS_YND_290","13-04-2025 16:13:46","13-04-2025 16:06:39","13-04-=
2025 19:26:39","Site went down because the Cb(125A) of PWC dysfonction due =
to load increased // He reamed the Cb","Mba Lazare Herve","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site w=
ent down because the Cb(125A) of PWC dysfonction due to load increased // H=
e reamed the Cb","edwige.kapawo@matech-cameroun.com","428","13-04-2025 16:1=
3:46","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004798684","Man=
guiers Dispensaire","","13-04-2025 16:05:03","13-04-2025 16:03:51","13-04-2=
025 16:15:51","Grid fluctuations site went down due to bad grid voltage and=
 no RCP //grid power stabilized","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid fluctuations site went dow=
n due to bad grid voltage and no RCP //grid power stabilized","franck.nkomo=
t@matech-cameroun.com","73","13-04-2025 16:05:03","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004798646","Nko=
zoa","","13-04-2025 15:57:50","13-04-2025 15:48:43","13-04-2025 16:07:02","=
Grid outage, site went down due to gen overload (20kva, 340A) // Grid resto=
red","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, site went down due to gen overload (20kva, 340A) // Gri=
d restored","edwige.kapawo@matech-cameroun.com","549","13-04-2025 15:57:50"=
,"MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004798644","Cit=
e des nations","","13-04-2025 15:57:16","13-04-2025 15:52:02","13-04-2025 1=
6:35:24","Our technician Paul is informed and says that, Active/ No power i=
ssue on site Ubay 53V site on Grid mBAH Osiah (674007438/Huawei) is informe=
d.","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Our technician Paul is informed and says that=
, Active/ No power issue on site Ubay 53V site on Grid mBAH Osiah (67400743=
8/Huawei) is informed.","edwige.kapawo@matech-cameroun.com","315","13-04-20=
25 15:57:16","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004798561","Ebo=
go","","13-04-2025 15:48:13","13-04-2025 15:46:03","13-04-2025 15:50:03","G=
rid outage, Site went down before Gen started due to poor backup // Gen sta=
rted automatically","Siligap Boris","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 started due to poor backup // Gen started automatically","franck.nkomot@ma=
tech-cameroun.com","131","13-04-2025 15:48:13","MATECH CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0004798551","E=
TOUDI CHAPELLE","","13-04-2025 15:46:40","13-04-2025 15:44:26","13-04-2025 =
15:47:41","Site went down because of insufficient rectifiers  //site stabil=
ized","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down because of insufficient rectifiers  //site stabiliz=
ed","edwige.kapawo@matech-cameroun.com","135","13-04-2025 15:46:40","MATECH=
 CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004798255","OBA=
M NGOLA OCM","","13-04-2025 15:04:32","13-04-2025 14:48:20","13-04-2025 15:=
38:20","Grid bad voltage, Site went down  due to absence of 02 Grid  phases=
 on site // He bypassed Grid and started Gen manually","MINKA NICOLAS","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
bad voltage, Site went down  due to absence of 02 Grid  phases on site // H=
e bypassed Grid and started Gen manually","edwige.kapawo@matech-cameroun.co=
m","973","13-04-2025 15:04:32","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004798115","N=
kozoa","","13-04-2025 14:56:13","13-04-2025 14:52:02","13-04-2025 15:06:05"=
,"Grid outage, site went down due to gen overload (20kva, 340A) // Grid res=
tored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage, site went down due to gen overload (20kva, 340A) // G=
rid restored","edwige.kapawo@matech-cameroun.com","252","13-04-2025 14:56:1=
3","MATECH CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004798043","Nko=
lfoulou","","13-04-2025 14:42:26","13-04-2025 14:33:16","13-04-2025 14:47:1=
6","Grid fluctuation, Site went down before Gen started due to poor backup/=
/ GEN started automatically","Siligap Boris","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid fluctuation, Site went down before G=
en started due to poor backup// GEN started automatically","edwige.kapawo@m=
atech-cameroun.com","551","13-04-2025 14:42:26","MATECH CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004797795","Nko=
lbisson IITA LP","","13-04-2025 14:02:38","13-04-2025 12:56:22","13-04-2025=
 13:10:50","Grid outage, No space to deploy a MDG grid // Power return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage, No space to deploy a MDG grid // Power return","christelle.ngonga@mat=
ech-cameroun.com","3977","13-04-2025 14:02:38","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004797498","A=
WAE OCM","","13-04-2025 13:07:44","13-04-2025 12:55:28","13-04-2025 15:08:1=
0","Grid outage, Site went down because Gen failed to start due to PWC malf=
unctioning// He reset it and manually start the Gen","Mba Lazare Herve","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid o=
utage, Site went down because Gen failed to start due to PWC malfunctioning=
// He reset it and manually start the Gen","gerard.tchangoue@matech-camerou=
n.com","738","13-04-2025 13:07:44","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004797485","C=
omplexe-BEAC","","13-04-2025 13:05:17","13-04-2025 13:01:04","13-04-2025 13=
:10:04","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started manually","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup // Gen started manually","gerard.tchangoue@mat=
ech-cameroun.com","254","13-04-2025 13:05:17","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004797467","C=
rf-Nkolbisson","","13-04-2025 13:00:23","13-04-2025 12:55:59","13-04-2025 1=
3:09:42","Grid fluctuation, site went down because gen fails to start due t=
o grid bad voltage // Grid stabilized","TIENTCHEU NZETCHIEU GAEL","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, site went down because gen fails to start due to grid bad voltage /=
/ Grid stabilized","gerard.tchangoue@matech-cameroun.com","266","13-04-2025=
 13:00:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_002","NOCINC0004797307","Yde-M-Ce=
ntral","","13-04-2025 12:42:27","13-04-2025 12:07:03","13-04-2025 12:45:00"=
,"Cascaded Incident from TTO4897685","","Cascade Outage","Active","Cascade =
Active","Cascade Active","No power issue,Site impacted by CBC-radio","syste=
m","266270","13-04-2025 12:42:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_005","NOCINC0004797306","Imm-Olym=
pique","","13-04-2025 12:42:26","13-04-2025 12:07:03","13-04-2025 12:45:00"=
,"Cascaded Incident from TTO4897685","Paul BIBOUM","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue,Site impacted by CBC-ra=
dio","system","266270","13-04-2025 12:42:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_003","NOCINC0004797305","Mercure"=
,"","13-04-2025 12:42:26","13-04-2025 12:07:03","13-04-2025 12:45:00","Casc=
aded Incident from TTO4897685","","Cascade Outage","Active","Cascade Active=
","Cascade Active","No power issue,Site impacted by CBC-radio","system","26=
6270","13-04-2025 12:42:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_007","NOCINC0004797304","Montee-A=
nne-Rouge","","13-04-2025 12:42:25","13-04-2025 12:07:03","13-04-2025 12:45=
:00","Cascaded Incident from TTO4897685","","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue,Site impacted by CBC-radio","s=
ystem","266271","13-04-2025 12:42:25","MATECH CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0004797260","E=
lig-Essono","IHS_YND_007, IHS_YND_003, IHS_YND_005, IHS_YND_002","13-04-202=
5 12:35:25","13-04-2025 12:07:03","13-04-2025 12:45:00","No power issue,Sit=
e impacted by CBC-radio","Paul BIBOUM","Customer Equipment Failure","Active=
","Active Equipment Failure","Affected by 3rd Party Site","No power issue,S=
ite impacted by CBC-radio","gerard.tchangoue@matech-cameroun.com","1703","1=
3-04-2025 12:35:25","MATECH CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004797254","L=
eboudi","","13-04-2025 12:32:44","13-04-2025 11:56:15","13-04-2025 14:12:51=
","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Grid outage site went down because Gen overload(20KVA,=
340A) SS IHS F=E9lix Bateu is informed and Is confirmed// He reduced the lo=
ad on site and started gen manualy","gerard.tchangoue@matech-cameroun.com",=
"295691","13-04-2025 12:32:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0004797151","Ekekam",=
"","13-04-2025 12:09:02","13-04-2025 11:59:52","13-04-2025 12:02:20","Casca=
ded Incident from TTO4897558","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, gen failled to s=
tart due to relay finder (48V) HS // blocked grid contactor","system","1297=
","13-04-2025 12:09:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004797149","Nkolfoul=
ou 2","","13-04-2025 12:09:01","13-04-2025 11:59:52","13-04-2025 12:02:20",=
"Cascaded Incident from TTO4897558","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, gen failled to start =
due to relay finder (48V) HS // blocked grid contactor","system","1298","13=
-04-2025 12:09:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004797150","TSINGA V=
ILLAGE 2","","13-04-2025 12:09:01","13-04-2025 11:59:52","13-04-2025 12:02:=
20","Cascaded Incident from TTO4897558","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, gen failled to s=
tart due to relay finder (48V) HS // blocked grid contactor","system","1299=
","13-04-2025 12:09:01","MATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004797139","BIY=
EMASSI NIKI","","13-04-2025 12:08:11","13-04-2025 12:04:06","13-04-2025 12:=
08:44","Grid Outage Site went down due to Gen overload(5kva, 200A) // GRID =
stabilized","Hyemafo Gildas","Equipment Repair","Passive","DCDG Gen","DCDG =
- Overload","GRid Outage Site went down due to Gen overload(5kva, 200A) // =
GRID stabilized","christelle.ngonga@matech-cameroun.com","247","13-04-2025 =
12:08:11","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004797137","N=
kolfoulou","IHS_YND_278, IHS_YND_719, IHS_YND_714","13-04-2025 12:07:31","1=
3-04-2025 11:59:52","13-04-2025 13:23:20","Grid outage, gen failled to star=
t due to relay finder (48V) HS // blocked grid contactor (Replaced ongoing)=
","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Relay Fau=
lty","Grid outage, gen failled to start due to relay finder (48V) HS // blo=
cked grid contactor","gerard.tchangoue@matech-cameroun.com","1296","13-04-2=
025 12:07:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_287","NOCINC0004797136","Nkolafem=
e","IHS_YND_309","13-04-2025 12:07:30","13-04-2025 11:56:15","13-04-2025 14=
:12:51","Grid outage, site went down because Gen is  overloaded(20KVA,375A)=
 SS IHS F=E9lix Bateu is informed and  confirmed// He reduced the load on s=
ite and started gen manually","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down becaus=
e Gen is  overloaded(20KVA,375A) SS IHS F=E9lix Bateu is informed and  conf=
irmed// He reduced the load on site and started gen manually","christelle.n=
gonga@matech-cameroun.com","675","13-04-2025 12:07:30","MATECH CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0004797082","E=
bogo","","13-04-2025 11:59:27","13-04-2025 11:32:15","13-04-2025 11:33:28",=
"Grid outage, Site went down before Gen started due to poor backup // Gen s=
tarted automatically","Siligap Boris","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en started due to poor backup // Gen started automatically","gerard.tchango=
ue@matech-cameroun.com","2411","13-04-2025 11:59:27","MATECH CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0004797049","N=
dogbessol","","13-04-2025 11:49:44","13-04-2025 11:36:26","13-04-2025 12:02=
:07","No power issue on site U=3D53,2V site on Gen , The Tx FME Etienne/651=
320188/ from Huawei is informed","Kemeni Franklin","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site U=3D53,2V site on Gen , The Tx FME Etienne/651320188/ from Huawe=
i is informed","gerard.tchangoue@matech-cameroun.com","799","13-04-2025 11:=
49:44","MATECH CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0004797012","E=
lig Edzoa","","13-04-2025 11:41:04","13-04-2025 11:24:47","13-04-2025 12:15=
:56","No power issue site on grid with U=3D51v, Armand (699949553 / Huawei)=
 is informed	","Delor Telezing","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wit=
h U=3D51v, Armand (699949553 / Huawei) is informed	","gerard.tchangoue@mate=
ch-cameroun.com","978","13-04-2025 11:41:04","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004797006","Bit=
eng-Maetur","","13-04-2025 11:40:07","13-04-2025 11:33:39","13-04-2025 12:5=
7:47","Active//No power issue on site Ubaie =3D52.3V site on Grid The TX FM=
E Henri (699949693) from Huawei is informed and works on site","Mba Lazare =
Herve","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No power issue on site Ubaie =3D52.3V site on Gr=
id The TX FME Henri (699949693) from Huawei is informed and works on site",=
"gerard.tchangoue@matech-cameroun.com","389","13-04-2025 11:40:07","MATECH =
CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004796840","Aka=
k-Nkozoa-MTN-IHS","","13-04-2025 11:03:10","13-04-2025 10:56:59","13-04-202=
5 13:16:03","Grid outage site went down because Gen failed to start due PWC=
 dysfonction // He reset the PWC,and start the Gen manually","Fabrice Pouak=
am","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage site went down because Gen failed to start due PWC dysfonction // He r=
eset the PWC,and start the Gen manually","christelle.ngonga@matech-cameroun=
.com","372","13-04-2025 11:03:10","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004796745","Ebo=
go","","13-04-2025 10:46:21","13-04-2025 10:37:13","13-04-2025 11:12:06","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed automatically","Siligap Boris","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Gen started automatically","christelle.ngonga@ma=
tech-cameroun.com","687","13-04-2025 10:46:21","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004796736","C=
RH-Etoug-Ebe","","13-04-2025 10:44:39","13-04-2025 10:34:59","13-04-2025 10=
:49:37","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen start automatically=
","gerard.tchangoue@matech-cameroun.com","581","13-04-2025 10:44:39","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_419","IHS_YND_227","NOCINC0004796716","M=
vog Betsi","","13-04-2025 10:40:33","13-04-2025 10:33:17","13-04-2025 10:37=
:17","Grid-Gen, eneo fluctuation, site down due to poor backup // eneo satb=
ilized","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid-Gen, eneo fluctuation, site down due to poor=
 backup // eneo satbilized","gerard.tchangoue@matech-cameroun.com","437","1=
3-04-2025 10:40:33","MATECH CMR"
"Closed Complete","Warning","","IHS_YND_227","NOCINC0004796698","Mvog Betsi=
","","13-04-2025 10:37:06","","","grid outage, Poor batteries backup // Gri=
d restoration","Hyemafo Gildas","Warning","Warning","POWER","Warning - Low =
Voltage","grid outage, Poor batteries backup // Grid restoration","christel=
le.ngonga@matech-cameroun.com","885","13-04-2025 10:37:06","MATECH CMR"
"Closed Complete","Warning","","IHS_YND_365","NOCINC0004796620","Akono","",=
"13-04-2025 10:29:31","","","Grid fluctuation, Site went down because Gen f=
ails to start due Gen card disfunction// He reset Gen and started Gen manua=
ly","Fanda Brice","Warning","Warning","POWER","Warning - Battery Low Voltag=
e","Grid fluctuation, Site went down because Gen fails to start due Gen car=
d disfunction// He reset Gen and started Gen manualy","christelle.ngonga@ma=
tech-cameroun.com","749","13-04-2025 10:29:31","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004796533","Cit=
e des nations","","13-04-2025 10:13:22","13-04-2025 10:08:41","13-04-2025 1=
0:18:52","Active //No power issue ,site on Grid on site with Ubaie=3D53 V X=
 Fme Hosiah / 674007438 from huawei is informed.","Paul BIBOUM","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active //No power issue ,site on Grid on site with Ubaie=3D53 V X Fme Hosi=
ah / 674007438 from huawei is informed.","christelle.ngonga@matech-cameroun=
.com","281","13-04-2025 10:13:22","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0004796463","C=
NR","","13-04-2025 10:05:37","13-04-2025 10:00:26","13-04-2025 10:13:12","A=
ctive//No power issue, Site on Grid with U=3D53.8V. The FME Fabrice NGANKEU=
(695524845) from OMNIUM works on site.","Mboua Thierry","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue, Site on Grid with U=3D53.8V. The Tx FME Brice Tsague(65021=
4096) from Huawei is informed.","gerard.tchangoue@matech-cameroun.com","312=
","13-04-2025 10:05:37","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004796461","Mok=
olo Yaounde","","13-04-2025 10:05:11","13-04-2025 09:06:57","13-04-2025 09:=
41:25","Grid outage, no space to deploy a mobile gen // grid return","","Gr=
id Supply","Passive","Planned Activity","National Grid Reconnect","Grid out=
age, no space to deploy a mobile gen // grid return","christelle.ngonga@mat=
ech-cameroun.com","3495","13-04-2025 10:05:11","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004796410","Bas=
tos-BAT","","13-04-2025 09:58:48","13-04-2025 09:39:35","13-04-2025 09:57:5=
9","Grid outage , site went down before Gen started due to poor battery bac=
kup// Grid Power return","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage , site went down befo=
re Gen started due to poor battery backup// Grid Power return","christelle.=
ngonga@matech-cameroun.com","1153","13-04-2025 09:58:48","MATECH CMR"
"Closed Complete","Warning","","IHS_YND_004","NOCINC0004796227","Av Kennedy=
","","13-04-2025 09:24:50","","","Grid , only site ,No psace for mobile gen=
 // grid restoration","","Warning","Warning","POWER","Warning - National Gr=
id - Grid Outage Issue","Grid , only site ,No psace for mobile gen // grid =
restoration","christelle.ngonga@matech-cameroun.com","826","13-04-2025 09:2=
4:50","MATECH CMR"
"Closed Complete","Warning","T1071","IHS_YND_343","NOCINC0004795858","Mbedo=
umou - Ekali","","13-04-2025 07:52:59","","","Grid outage .gen fails to sta=
rt due to grid fluctuation //Grid restored","Albran Byorel","Warning","Warn=
ing","POWER","Warning - AC Failure","Grid outage .gen fails to start due to=
 grid fluctuation //Grid restored","christelle.ngonga@matech-cameroun.com",=
"852","13-04-2025 07:52:59","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004795822","N=
yom OCM","","13-04-2025 07:42:07","13-04-2025 07:21:55","13-04-2025 09:14:1=
1","Grid low voltage, Site went down because gen fails to start due to grid=
 bad voltage // He bypass grid and manually start the gen","Fabrice Pouakam=
","Grid Supply","Passive","Grid","National Grid - Low Current Supply","Grid=
 low voltage, Site went down because gen fails to start due to grid bad vol=
tage // He bypass grid and manually start the gen","gerard.tchangoue@matech=
-cameroun.com","1214","13-04-2025 07:42:07","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004795529","NTU=
I TOWN","","13-04-2025 06:13:52","13-04-2025 06:08:40","13-04-2025 07:12:40=
","Grid outage gen ran until fuel shortage//Refueling done","Parker Tchoup"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran unti=
l fuel shortage//Refueling done","loic.noumsi@matech-cameroun.com","313","1=
3-04-2025 06:13:52","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0004795360","NKO=
NGKARAK","","13-04-2025 04:51:20","13-04-2025 04:40:59","13-04-2025 05:25:3=
2","Grid outage, Gen stopped due to High temp alarm cause by pellet pierced=
  // gluing the pellet, water added and Gen start manually","TIENTCHEU NZET=
CHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Gen stopped due to High temp alarm cause by pellet pierced  // glu=
ing the pellet, water added and Gen start manually","cedric.tiani@matech-ca=
meroun.com","1098","13-04-2025 04:51:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004795136","Biyemass=
i LAC","","13-04-2025 03:05:20","13-04-2025 01:50:28","13-04-2025 03:52:19"=
,"Cascaded Incident from TTO4895372","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid Outage Site went down due to Gen overload=
(5kva, 200A) // GRID stabilized","system","281499","13-04-2025 03:05:20","M=
ATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004795071","BIY=
EMASSI NIKI","IHS_YND_546","13-04-2025 02:45:00","13-04-2025 01:50:28","13-=
04-2025 03:52:19","Grid Outage Site went down due to Gen overload(5kva, 200=
A) // GRID stabilized","Hyemafo Gildas","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","Grid Outage Site went down due to Gen overload(5kva=
, 200A) // GRID stabilized","cedric.tiani@matech-cameroun.com","4440","13-0=
4-2025 02:45:00","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004795039","E=
vodoula OCM","","13-04-2025 02:29:22","13-04-2025 02:13:19","13-04-2025 03:=
13:19","No power issue site and with Ubaie=3D54.4 V site on Gen The FME TX =
Mohamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue site and with Ubaie=3D54.4 V site on Gen The FME =
TX Mouamadou/658791013 //From Huawei is informed","cedric.tiani@matech-came=
roun.com","964","13-04-2025 02:29:22","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004794848","NKO=
MKANA ELIZA HOTEL","","13-04-2025 01:03:20","13-04-2025 00:59:48","13-04-20=
25 01:09:59","The fme Thierry is informed and said no space to deploy MG, a=
waiting grid return // grid restored","","Grid Supply","Passive","Grid","Na=
tional Grid - Grid Outage Issue","The fme Thierry is informed and said no s=
pace to deploy MG, awaiting grid return // grid restored","cedric.tiani@mat=
ech-cameroun.com","212","13-04-2025 01:03:20","MATECH CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004794746","M=
ini-Ferme","","13-04-2025 00:26:11","13-04-2025 00:11:03","13-04-2025 14:08=
:03","Grid outage, no space to deploy a mobile gen// grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
no space to deploy a mobile gen// grid return","gaelle.njiofack@matech-came=
roun.com","909","13-04-2025 00:26:11","MATECH CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0004794691","Ole=
mbe","","13-04-2025 00:02:46","12-04-2025 23:56:53","13-04-2025 00:29:23","=
Grid outage, Gen ran until fuel shortage // Refueling done","Fabrice Pouaka=
m","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, Gen ran u=
ntil fuel shortage // Refueling done
","cedric.tiani@matech-cameroun.com","385","13-04-2025 00:02:46","MATECH CM=
R"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004794655","B=
iteng-Maetur","","12-04-2025 23:51:53","12-04-2025 22:15:46","13-04-2025 00=
:00:21","Incorrectly logged tickets","Mba Lazare Herve","Incorrectly Logged=
 Tickets","Error","Error","Error","Incorrectly logged tickets","gaelle.njio=
fack@matech-cameroun.com","5769","12-04-2025 23:51:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004794640","Nkolfon =
Cimencam","","12-04-2025 23:42:36","12-04-2025 23:22:15","13-04-2025 00:43:=
04","Cascaded Incident from TTO4894861","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down du=
e to Gen overload (17KVA, 250A) // Grid return","system","268929","12-04-20=
25 23:42:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004794639","Afanoya"=
,"","12-04-2025 23:42:36","12-04-2025 23:22:15","13-04-2025 00:43:04","Casc=
aded Incident from TTO4894861","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down due to Gen =
overload (17KVA, 250A) // Grid return","system","268929","12-04-2025 23:42:=
36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0004794638","Ahala","=
","12-04-2025 23:42:36","12-04-2025 23:22:15","13-04-2025 00:43:04","Cascad=
ed Incident from TTO4894861","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage site went down due to Gen ov=
erload (17KVA, 250A) // Grid return","system","268929","12-04-2025 23:42:36=
","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004794629","M=
eyo","IHS_YND_257, IHS_YND_313, IHS_YND_762","12-04-2025 23:38:45","12-04-2=
025 23:22:15","13-04-2025 00:43:04","Grid outage site went down due to Gen =
overload (17KVA, 240A) // Grid return","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage site went down due to G=
en overload (17KVA, 240A) // Grid return","cedric.tiani@matech-cameroun.com=
","990","12-04-2025 23:38:45","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0004794545","O=
bili Carrefour","","12-04-2025 23:15:07","12-04-2025 22:52:58","13-04-2025 =
00:19:01","Our technician Paul is informed and says that, Active/ No power =
issue on site Ubay 53.4V site on Grid mBAH Osiah (674007438/Huawei) is info=
rmed.","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Our technician Paul is informed and says t=
hat, Active/ No power issue on site Ubay 53.4V site on Grid mBAH Osiah (674=
007438/Huawei) is informed.","gaelle.njiofack@matech-cameroun.com","1330","=
12-04-2025 23:15:07","MATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004794421","BIY=
EMASSI NIKI","","12-04-2025 22:39:17","12-04-2025 22:18:25","12-04-2025 23:=
38:39","Grid Outage Site went down due to Gen overload(5kva, 200A) // fme r=
educed load and restarted gen","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid Outage Site went down due to Gen overl=
oad(5kva, 200A) // fme reduced load and restarted gen
","ludivine.ngamaleu@ihstowers.com","1253","12-04-2025 22:39:17","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_729","NOCINC0004794411","Nkolbiss=
on IITA LP","","12-04-2025 22:37:31","12-04-2025 22:27:23","12-04-2025 23:0=
0:51","Cascaded Incident from TTO4894588","","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because of CB(125A) in PWC=
 due to load increase//He reamed the CB and reduce the load","system","2792=
96","12-04-2025 22:37:31","MATECH CMR"
"Closed Complete","Site Down","T1937","IHS_YND_232","NOCINC0004794407","Crf=
-Nkolbisson","IHS_YND_729","12-04-2025 22:36:35","12-04-2025 22:27:23","12-=
04-2025 23:00:51","Site went down because of CB(125A) in PWC due to load in=
crease//He reamed the CB and reduce the load","TIENTCHEU NZETCHIEU GAEL","E=
quipment Repair","Passive","Rectifier","Rectifier Cabinet","Site went down =
because of CB(125A) in PWC due to load increase//He reamed the CB and reduc=
e the load","cedric.tiani@matech-cameroun.com","552","12-04-2025 22:36:35",=
"MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004794392","Bas=
tos-BAT","","12-04-2025 22:33:26","12-04-2025 22:28:11","12-04-2025 22:34:0=
1","grid outage,gen failed to start//grid return","Mboua Thierry","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Generator Faulty","grid outage,gen f=
ailed to start//grid return","cedric.tiani@matech-cameroun.com","316","12-0=
4-2025 22:33:26","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004794319","Ron=
d Point Express1114","","12-04-2025 22:16:10","12-04-2025 22:13:01","12-04-=
2025 23:09:18","Grid Gen site , site was on Gen, Grid return site went down=
 due to Poor battery backup // site on Grid","Hyemafo Gildas","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid Gen sit=
e , site was on Gen, Grid return site went down due to Poor battery backup =
// site on Grid
","cedric.tiani@matech-cameroun.com","190","12-04-2025 22:16:10","MATECH CM=
R"
"Cancelled","Warning","T2149","IHS_EDA_056","NOCINC0004794253","Ndogbessol"=
,"","12-04-2025 21:58:43","","","RUNNING TICKET","Kemeni Franklin","","",""=
,"","","cedric.tiani@matech-cameroun.com","550","12-04-2025 21:58:43","MATE=
CH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004794252","NYO=
M FACE MAETUR","","12-04-2025 21:58:00","12-04-2025 21:52:52","12-04-2025 2=
3:26:48","site down due to grid bad voltage // he started gen manually","Fa=
brice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","site down due to grid bad voltage // he started gen manually"=
,"cedric.tiani@matech-cameroun.com","310","12-04-2025 21:58:00","MATECH CMR=
"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004794248","CRH=
-Etoug-Ebe","","12-04-2025 21:56:18","12-04-2025 21:50:07","12-04-2025 22:0=
4:33","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"cedric.tiani@matech-cameroun.com","371","12-04-2025 21:56:18","MATECH CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0004794246","Biy=
emassi LAC","","12-04-2025 21:55:32","12-04-2025 21:38:18","12-04-2025 22:1=
2:13","Grid outage, no space to deploy MGE,// Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spac=
e to deploy MGE,// Grid return
","cedric.tiani@matech-cameroun.com","1035","12-04-2025 21:55:32","MATECH C=
MR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0004794090","K=
amajou Building","","12-04-2025 21:33:06","12-04-2025 21:31:48","12-04-2025=
 21:34:48","Grid outage Site went down before gen started due to poor batte=
ry backup // Grid return","Paul BIBOUM","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active; no power issue =
site on grid with U=3D54,3V;The fme TX Hosiah 674007438 of huawei is inform=
ed","gerard.tchangoue@matech-cameroun.com","78","12-04-2025 21:33:06","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004793878","E=
ssomba","","12-04-2025 20:58:09","12-04-2025 20:54:54","12-04-2025 21:23:54=
","Grid fluctuations, Site down due to the malfunction of 3/4 rectifiers //=
 reset of 3 rectifiers, site on Grid","Mba Lazare Herve","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Grid fluctuations, Site down due=
 to the malfunction of 3/4 rectifiers // reset of 3 rectifiers, site on Gri=
d","gerard.tchangoue@matech-cameroun.com","197","12-04-2025 20:58:09","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004793608","M=
EHANDAN","","12-04-2025 20:08:51","12-04-2025 20:04:40","12-04-2025 21:58:4=
0","Site went down due to Deficiency rectifiers on site//site stabilised","=
Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to Deficiency rectifiers on site//site stabilised","ger=
ard.tchangoue@matech-cameroun.com","252","12-04-2025 20:08:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004793555","Bastos B=
ir","","12-04-2025 19:58:54","12-04-2025 13:59:21","12-04-2025 19:03:48","C=
ascaded Incident from TTO4892768","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because of insufficie=
nt rectifiers on site //site stabilized","system","280844","12-04-2025 19:5=
8:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004793556","ARMP",""=
,"12-04-2025 19:58:54","12-04-2025 13:59:21","12-04-2025 19:03:48","Cascade=
d Incident from TTO4892768","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down because of insufficient rectifiers on si=
te //site stabilized","system","280844","12-04-2025 19:58:54","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004793520","B=
itoto","","12-04-2025 19:52:32","12-04-2025 19:46:12","12-04-2025 20:49:12"=
,"Active//No power issue on site , Tx Issue : site on Grid ,Ubai: 54,4V; Th=
e fme Tx George/697461814/ From huawei is informed and notice that disjunct=
ion at OCM Equipment","Mba Lazare Herve","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue=
 on site , Tx Issue : site on Grid ,Ubai: 54,4V; The fme Tx George/69746181=
4/ From huawei is informed and notice that disjunction at OCM Equipment","g=
erard.tchangoue@matech-cameroun.com","382","12-04-2025 19:52:32","MATECH CM=
R"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004793437","M=
ontee-Des-Soeurs","","12-04-2025 19:45:08","12-04-2025 19:31:22","12-04-202=
5 21:05:37","Site went down due to 02/04 rectifiers faulty //He reset Recti=
fiers","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier=
 Cabinet","Site went down due to 02/04 rectifiers faulty //He reset Rectifi=
ers","gerard.tchangoue@matech-cameroun.com","827","12-04-2025 19:45:08","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004793402","M=
ontee-Des-Soeurs","","12-04-2025 19:37:51","12-04-2025 12:44:43","12-04-202=
5 18:40:43","rectifiers faulty","Hyemafo Gildas","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to 02/04 rectifiers f=
aulty //one rectifier added","kouoh.jean@ihstowers.com","24789","12-04-2025=
 19:37:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_285","NOCINC0004793107","Nkolbiss=
on","IHS_YND_763","12-04-2025 18:49:26","12-04-2025 18:44:25","12-04-2025 2=
2:34:01","Grid outage, ACCESS ISSUES during the Night due to Landlord // Gi=
d return","TIENTCHEU NZETCHIEU GAEL","Access Denial","Lease Or Legal","Land=
lord Related Issues","Access Issue - Land Lord","Grid outage, ACCESS ISSUES=
 during the Night due to Landlord // Gid return","system","301","12-04-2025=
 18:49:26","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004793098","Nko=
lbisson usines des eaux 2","","12-04-2025 18:48:38","12-04-2025 18:44:25","=
12-04-2025 22:34:01","ACCESS ISSUES during the Night due to Landlord","TIEN=
TCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, ACCESS ISSUES during the Night due to Landlord // G=
id return","cedric.tiani@matech-cameroun.com","300038","12-04-2025 18:48:38=
","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004792857","D=
ragage","IHS_YND_704, IHS_YND_208","12-04-2025 17:58:05","12-04-2025 13:59:=
21","12-04-2025 19:03:48","Site went down because of insufficient rectifier=
s on site //added one rectifier","Mboua Thierry","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down because of insufficient r=
ectifiers on site //added one rectifier","gerard.tchangoue@matech-cameroun.=
com","21470","12-04-2025 17:58:05","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004792853","Ebo=
go","","12-04-2025 17:57:13","12-04-2025 17:55:58","12-04-2025 17:57:58","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed automatically","Siligap Boris","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Gen started automatically","cedric.tiani@matech-=
cameroun.com","76","12-04-2025 17:57:13","MATECH CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004792775","NKO=
LOSSAN OKOK","","12-04-2025 17:44:05","12-04-2025 17:40:57","12-04-2025 19:=
48:02","Grid outage, site down because gen ran till diesel outage//refuelin=
g done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage, site down because gen ran till diesel outage//refueling done","=
cedric.tiani@matech-cameroun.com","189","12-04-2025 17:44:05","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004792742","Nsi=
malen MTN","","12-04-2025 17:35:44","12-04-2025 17:30:30","12-04-2025 17:52=
:26","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","cedric.tiani@matech-cameroun.com","315","=
12-04-2025 17:35:44","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004792642","M=
EHANDAN","","12-04-2025 17:08:30","12-04-2025 17:03:10","12-04-2025 17:07:2=
0","Site went down due to Deficiency rectifiers on site//site stabilised","=
Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to Deficiency rectifiers on site//site stabilised","ger=
ard.tchangoue@matech-cameroun.com","322","12-04-2025 17:08:30","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004792638","NKO=
MKANA ELIZA HOTEL","","12-04-2025 17:08:15","12-04-2025 17:06:08","12-04-20=
25 17:08:16","grid outage,no space to deploy MDG // Grid power return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid out=
age,no space to deploy MDG // Grid power return","cedric.tiani@matech-camer=
oun.com","128","12-04-2025 17:08:15","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004792557","Lad=
a I Yde","","12-04-2025 16:56:13","12-04-2025 16:54:02","12-04-2025 18:57:0=
2","Grid fluctuation,site went down because Gen failed to start deu to Grid=
 bad voltage //He bypassed the Grid and site on Gen","Mba Lazare Herve","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuation,site went down because Gen failed to start deu to Grid bad vol=
tage //He bypassed the Grid and site on Gen","cedric.tiani@matech-cameroun.=
com","133","12-04-2025 16:56:13","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004792526","M=
EHANDAN","","12-04-2025 16:50:33","12-04-2025 13:54:41","12-04-2025 16:51:4=
1","Site went down due to Deficiency rectifiers on site//site stabilised","=
Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to Deficiency rectifiers on site//site stabilised","kou=
oh.jean@ihstowers.com","10902","12-04-2025 16:50:33","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004792522","Saa=
","","12-04-2025 16:50:01","12-04-2025 16:44:49","12-04-2025 16:49:02","Sit=
e went down because FME Parker  was on site doing PM","Parker Tchoup","Inst=
allation Activity","Passive","Planned Activity","Installation Activity","Si=
te went down because FME Parker  was on site doing PM","gerard.tchangoue@ma=
tech-cameroun.com","314","12-04-2025 16:50:01","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004792449","B=
iteng-Maetur","","12-04-2025 16:43:40","12-04-2025 11:32:59","12-04-2025 12=
:32:59","Active//No power issue on site Ubaie =3D50.3V site on Grid The TX =
FME Henri (699949693) from Huawei is informed","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site Ubaie =3D50.3V site on Grid The TX FME He=
nri (699949693) from Huawei is informed","gerard.tchangoue@matech-cameroun.=
com","18642","12-04-2025 16:43:40","MATECH CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004792420","M=
ontesquieux","","12-04-2025 16:37:30","12-04-2025 16:35:42","12-04-2025 20:=
28:42","site went down due to disfunctionning of rectifiers // He reset rec=
tifiers site is on grid","Paul BIBOUM","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","site went down due to disfunctionning of rectifier=
s // He reset rectifiers site is on grid","gerard.tchangoue@matech-cameroun=
.com","109","12-04-2025 16:37:30","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0004792250","H=
-Progres","","12-04-2025 16:06:41","12-04-2025 15:19:28","12-04-2025 22:38:=
41","Grid outage, no space to deploy MGE,// Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy MGE,// Grid return
","gerard.tchangoue@matech-cameroun.com","2835","12-04-2025 16:06:41","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0004792237","A=
bang","","12-04-2025 16:04:26","12-04-2025 15:24:01","12-04-2025 15:40:21",=
"","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","Active//No power issue on site Ubaie =3D53V site on Grid The TX FME=
 Henri (699949693) from Huawei is informed.Noticed disjonction at the BTS O=
CM","gerard.tchangoue@matech-cameroun.com","268716","12-04-2025 16:04:26","=
MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004792226","N=
kolangaa","IHS_YND_290","12-04-2025 16:02:22","12-04-2025 15:24:01","12-04-=
2025 17:57:53","Active//No power issue on site Ubaie =3D53V site on Grid Th=
e TX FME Henri (699949693) from Huawei is informed.Noticed disjonction at t=
he BTS OCM","Mba Lazare Herve","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site U=
baie =3D53V site on Grid The TX FME Henri (699949693) from Huawei is inform=
ed.Noticed disjonction at the BTS OCM","gerard.tchangoue@matech-cameroun.co=
m","2302","12-04-2025 16:02:22","MATECH CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0004792134","B=
ATA-Mokolo","","12-04-2025 15:45:49","12-04-2025 15:37:18","12-04-2025 22:4=
1:24","FME report that  no space to deploy MGE, awaiting Eneo return // GRI=
D RESTORED","","Grid Supply","Passive","Grid","National Grid - Grid Outage =
Issue","FME report that  no space to deploy MGE, awaiting Eneo return // GR=
ID RESTORED","gerard.tchangoue@matech-cameroun.com","512","12-04-2025 15:45=
:49","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004791823","Nsi=
malen MTN","","12-04-2025 14:53:02","12-04-2025 14:51:54","12-04-2025 15:05=
:15","Grid Outage, site went down before gen start due to poor battery back=
up // Gen started automatically","Albran Byorel","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, site went do=
wn before gen start due to poor battery backup // Gen started automatically=
","cedric.tiani@matech-cameroun.com","69","12-04-2025 14:53:02","MATECH CMR=
"
"Closed Complete","Site Down","CTR_115","IHS_YND_375","NOCINC0004791797","N=
goung","","12-04-2025 14:45:41","12-04-2025 13:43:19","12-04-2025 15:34:15"=
,"Grid fluctuation,site went down because Gen failed to start due to grid b=
advoltage//he bypassed the Grid and site on Gen","Kemeni Franklin","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation,site went down because Gen failed to start due to grid badvoltage//=
he bypassed the Grid and site on Gen","gerard.tchangoue@matech-cameroun.com=
","3743","12-04-2025 14:45:41","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004791760","Sof=
avinc","","12-04-2025 14:39:59","12-04-2025 14:30:51","12-04-2025 15:08:51"=
,"Grid fluctuation,site went down because Gen failed to start due to grid b=
advoltage(lack of phases)//he bypassed the Grid and site on Gen","MINKA NIC=
OLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation,site went down because Gen failed to start due to gri=
d badvoltage(lack of phases)//he bypassed the Grid and site on Gen","cedric=
.tiani@matech-cameroun.com","549","12-04-2025 14:39:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004791759","Bastos B=
ir","","12-04-2025 14:39:24","12-04-2025 13:52:21","12-04-2025 13:55:21","C=
ascaded Incident from TTO4891253","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because of insufficie=
nt rectifiers on site //site stabilized","system","274122","12-04-2025 14:3=
9:24","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004791690","Cit=
e des nations","","12-04-2025 14:30:15","12-04-2025 14:26:05","13-04-2025 0=
0:34:26","Active //No power issue ,site on Grid on site with Ubaie=3D53 V X=
 Fme Hosiah / 674007438 from huawei is informed.","Paul BIBOUM","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active //No power issue ,site on Grid on site with Ubaie=3D53 V X Fme Hosi=
ah / 674007438 from huawei is informed.","edwige.kapawo@matech-cameroun.com=
","251","12-04-2025 14:30:15","MATECH CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004791667","Mvo=
g-Betsi","","12-04-2025 14:25:03","12-04-2025 14:15:52","12-04-2025 15:03:3=
5","Grid fluctuation site went down because Gen failed to start due to Grid=
 bad voltage // He bypassed the Grid and site on Gen","Hyemafo Gildas","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation site went down because Gen failed to start due to Grid bad volt=
age // He bypassed the Grid and site on Gen","edwige.kapawo@matech-cameroun=
.com","552","12-04-2025 14:25:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004791581","ARMP",""=
,"12-04-2025 14:10:55","12-04-2025 13:52:21","12-04-2025 13:55:21","Cascade=
d Incident from TTO4891253","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down because of insufficient rectifiers on si=
te //site stabilized","system","274122","12-04-2025 14:10:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_192","NOCINC0004791563","Dragage"=
,"IHS_YND_704, IHS_YND_208","12-04-2025 14:08:26","12-04-2025 13:52:21","12=
-04-2025 13:55:21","Site went down because of insufficient rectifiers on si=
te //site stabilized","Mboua Thierry","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down because of insufficient rectifiers o=
n site //site stabilized","joelle.ekessi@ihstowers.com","966","12-04-2025 1=
4:08:26","MATECH CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0004791404","Ess=
os Marche","","12-04-2025 13:53:23","12-04-2025 13:30:08","12-04-2025 14:10=
:56","No power issue, Ubaie: 53. 2 V Site on Grid The TX FME Armand (691144=
412) from Huawei is informed","Delor Telezing","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, =
Ubaie: 53. 2 V Site on Grid The TX FME Armand (691144412) from Huawei is in=
formed","edwige.kapawo@matech-cameroun.com","1396","12-04-2025 13:53:23","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0004791399","Messassi=
 2","","12-04-2025 13:52:25","12-04-2025 12:17:19","12-04-2025 12:27:19","S=
ite went down because 01/03 rectifiers dysfunctionned// He reset rectifiers=
","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down because 01/03 rectifiers dysfunctionned// He reset rec=
tifiers","joelle.ekessi@ihstowers.com","5708","12-04-2025 13:52:25","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004791088","Abang","=
","12-04-2025 13:08:34","12-04-2025 09:55:29","12-04-2025 13:21:57","Cascad=
ed Incident from TTO4890705","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site Ubaie =3D5=
3V site on Grid The TX FME Henri (699949693) from Huawei is informed.Notice=
d disjonction at the BTS OCM","system","281150","12-04-2025 13:08:34","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004791070","N=
kolangaa","IHS_YND_290","12-04-2025 13:05:52","12-04-2025 09:55:29","12-04-=
2025 13:21:57","Active//No power issue on site Ubaie =3D53V site on Grid Th=
e TX FME Henri (699949693) from Huawei is informed.Noticed disjonction at t=
he BTS OCM","Mba Lazare Herve","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site U=
baie =3D53V site on Grid The TX FME Henri (699949693) from Huawei is inform=
ed.Noticed disjonction at the BTS OCM","edwige.kapawo@matech-cameroun.com",=
"11424","12-04-2025 13:05:52","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004791044","Nsi=
malen MTN","","12-04-2025 13:02:25","12-04-2025 12:58:08","12-04-2025 13:02=
:04","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Grid Supply","Passive","Grid","National Grid - =
Grid Outage Issue","Grid outage, Site went down before Gen start due to poo=
r backup // Grid return","edwige.kapawo@matech-cameroun.com","258","12-04-2=
025 13:02:25","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004790925","OTE=
LE MTN","","12-04-2025 12:48:13","12-04-2025 12:36:47","12-04-2025 14:27:16=
","grid outage,gen ran still fuel shortage//Refueling done","Fanda Brice","=
Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran still =
fuel shortage//Refueling done","vanel.mbiada@matech-cameroun.com","687","12=
-04-2025 12:48:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_517","NOCINC0004790894","Montee-D=
es-Soeurs","","12-04-2025 12:42:29","12-04-2025 12:18:25","12-04-2025 12:33=
:25","Site went down due to 02/04 rectifiers faulty //He reset it","Hyemafo=
 Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","Site =
went down due to 02/04 rectifiers faulty //He reset it","joelle.ekessi@ihst=
owers.com","1445","12-04-2025 12:42:29","MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0004790846","K=
amajou Building","","12-04-2025 12:31:24","12-04-2025 12:07:15","12-04-2025=
 15:17:23","Site went down because SS HIS Francois Ndoungou is on site (ins=
tallation oa an additional DC SOURCE to correct the CB(80A))","Paul BIBOUM"=
,"Installation Activity","Passive","Planned Activity","Installation Activit=
y","Site went down because SS HIS Francois Ndoungou is on site (installatio=
n oa an additional DC SOURCE to correct the CB(80A))","edwige.kapawo@matech=
-cameroun.com","1450","12-04-2025 12:31:24","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004790729","BAT=
A Mokolo OCM","","12-04-2025 12:12:01","12-04-2025 12:04:48","13-04-2025 01=
:06:17","grid outage, no space to deploy MG // Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","grid outage, no spa=
ce to deploy MG // Grid return","edwige.kapawo@matech-cameroun.com","435","=
12-04-2025 12:12:01","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004790718","NKO=
MKANA ELIZA HOTEL","","12-04-2025 12:10:03","12-04-2025 12:04:55","12-04-20=
25 12:14:06","Site went down due to  insufficient rectifiers//site stabiliz=
ed","","Equipment Repair","Passive","Rectifier","Rectifier Module","Site we=
nt down due to  insufficient rectifiers//site stabilized","edwige.kapawo@ma=
tech-cameroun.com","308","12-04-2025 12:10:03","MATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004790477","BIY=
EMASSI NIKI","","12-04-2025 11:32:36","12-04-2025 11:18:59","12-04-2025 14:=
27:59","Grid Outage Site went down due to Gen overload(5kva, 200A) // fme r=
educed load and restarted gen","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid Outage Site went down due to Gen overl=
oad(5kva, 200A) // fme reduced load and restarted gen","edwige.kapawo@matec=
h-cameroun.com","818","12-04-2025 11:32:36","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004790459","A=
kak-Nkozoa-MTN-IHS","","12-04-2025 11:29:34","12-04-2025 11:25:27","12-04-2=
025 12:07:12","Grid outage site went down because Gen failed to start due P=
WC dysfonction // He reset the PWC,and start the Gen manually","Fabrice Pou=
akam","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage site went down because Gen failed to start due PWC dysfoncti=
on // He reset the PWC,and start the Gen manually","edwige.kapawo@matech-ca=
meroun.com","249","12-04-2025 11:29:34","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004790391","Nsi=
malen MTN","","12-04-2025 11:16:01","12-04-2025 11:06:53","12-04-2025 11:16=
:02","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup // Grid return","edwige.kapawo@matech-cameroun.com","548",=
"12-04-2025 11:16:01","MATECH CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004790331","CRH=
-Etoug-Ebe","","12-04-2025 11:06:42","12-04-2025 11:01:32","12-04-2025 11:1=
7:38","Grid outage, Site went down before Gen start due to poor backup // G=
en start automatically","Hyemafo Gildas","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen start automatically","edwige.kapawo@m=
atech-cameroun.com","381","12-04-2025 11:06:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004790319","ETOUDI C=
HAPELLE","","12-04-2025 11:01:40","12-04-2025 10:57:34","12-04-2025 11:01:1=
8","Site went down because of insufficient rectifiers  //site stabilized","=
Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down because of insufficient rectifiers  //site stabilized","jo=
elle.ekessi@ihstowers.com","248","12-04-2025 11:01:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004790181","Nkolkoum=
ou OCM","","12-04-2025 10:38:41","12-04-2025 10:34:41","12-04-2025 11:21:35=
","Cascaded Incident from TTO4889715","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down gen start and stopped with alarm over current // He reset gen card a=
nd gen manually","system","271955","12-04-2025 10:38:41","MATECH CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0004790174","Nko=
lbisson usine des eaux","IHS_YND_712","12-04-2025 10:36:56","12-04-2025 10:=
32:41","12-04-2025 11:21:35","Grid outage, site went down because gen start=
ed and stopped with alarm over current // He reset gen card and gen manuall=
y","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Grid outage, site went down because gen started and stop=
ped with alarm over current // He reset gen card and gen manually","edwige.=
kapawo@matech-cameroun.com","541","12-04-2025 10:36:56","MATECH CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0004790072","Dra=
gage","","12-04-2025 10:25:08","12-04-2025 10:22:55","12-04-2025 10:26:46",=
"Site went down because of  insufficient rectifiers on site //site stabiliz=
ed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down because of  insufficient rectifiers on site //site sta=
bilized","edwige.kapawo@matech-cameroun.com","134","12-04-2025 10:25:08","M=
ATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004789923","Ako=
k Ndoe Yde","","12-04-2025 10:10:13","12-04-2025 10:00:07","12-04-2025 10:0=
4:39","Grid outage, Site went down before Gen start due to poor backup // G=
en start manually","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen start manually","edwige.kapawo@matech-came=
roun.com","638","12-04-2025 10:10:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004789907","Abang","=
","12-04-2025 10:07:46","11-04-2025 18:19:18","12-04-2025 05:20:50","Cascad=
ed Incident from TTO4887870","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site Ubaie: 53V=
 site on Grid The TX FME Henri (699949693) from Huawei is informed.","syste=
m","330223","12-04-2025 10:07:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_229","NOCINC0004789900","CRH-Etou=
g-Ebe","","12-04-2025 10:05:42","12-04-2025 09:59:36","12-04-2025 10:15:32"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen st=
art automatically","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen start automatically","joelle.ekessi@ihstow=
ers.com","367","12-04-2025 10:05:42","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004789857","Bas=
tos-BAT","","12-04-2025 09:57:40","12-04-2025 09:55:21","12-04-2025 13:35:0=
0","Grid outage gen  ran until fuel shortage//Refueling done","Mboua Thierr=
y","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen  ran u=
ntil fuel shortage//Refueling done","edwige.kapawo@matech-cameroun.com","14=
0","12-04-2025 09:57:40","MATECH CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0004789844","B=
astos Bethesda","","12-04-2025 09:55:06","12-04-2025 08:40:56","12-04-2025 =
14:16:56","Grid-Gen, eneo outage, site down due to fuel shortage // refueli=
ng done and site on GEN","Mboua Thierry","Fuel Outage","Passive","Diesel","=
Diesel Outage","Grid-Gen, eneo outage, site down due to fuel shortage // re=
fueling done and site on GEN","edwige.kapawo@matech-cameroun.com","17975","=
12-04-2025 09:55:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0004789843","Sapeur",=
"","12-04-2025 09:54:36","12-04-2025 09:05:09","12-04-2025 23:00:36","Casca=
ded Incident from TTO4889333","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, no space to deploy MGE,// G=
rid return
","system","320223","12-04-2025 09:54:36","MATECH CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0004789819","E=
-Police","IHS_YND_029","12-04-2025 09:48:36","12-04-2025 09:05:09","12-04-2=
025 23:00:36","Grid outage, no space to deploy MGE,// Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 no space to deploy MGE,// Grid return
","edwige.kapawo@matech-cameroun.com","2609","12-04-2025 09:48:36","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004789541","Emana Ly=
cee","","12-04-2025 09:09:45","12-04-2025 08:54:21","12-04-2025 09:10:53","=
Cascaded Incident from TTO4889029","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen start and stopped due to high temp // He added water and manually st=
art the gen","system","924","12-04-2025 09:09:45","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0004789538","Val=
lee Bastos MTN","","12-04-2025 09:09:14","12-04-2025 08:59:43","12-04-2025 =
13:39:08","Grid outage gen  ran until fuel shortage//Refueling done","Mboua=
 Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen=
  ran until fuel shortage//Refueling done","vanel.mbiada@matech-cameroun.co=
m","572","12-04-2025 09:09:14","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004789525","E=
mana lycee 2","IHS_YND_274","12-04-2025 09:05:29","12-04-2025 08:54:21","12=
-04-2025 09:10:53","Grid outage, site went down because gen start and stopp=
ed due to high temp // He added water and manually start the gen","Fabrice =
Pouakam","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outa=
ge, site went down because gen start and stopped due to high temp // He add=
ed water and manually start the gen","edwige.kapawo@matech-cameroun.com","6=
70","12-04-2025 09:05:29","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004789513","Nko=
lbong","","12-04-2025 09:02:12","12-04-2025 08:56:57","12-04-2025 09:02:48"=
,"Grid outage ,site went down because due to Gen overload// Grid return","D=
elor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid outage ,site went down because due to Gen overload// Grid return","edwi=
ge.kapawo@matech-cameroun.com","317","12-04-2025 09:02:12","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004789469","Cit=
e des nations","","12-04-2025 08:50:31","12-04-2025 08:45:18","12-04-2025 0=
9:40:04","Active //No power issue ,site on Grid on site with Ubaie:53.7 V X=
 Fme Hosiah / 674007438 from huawei is informed","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active //No power issue ,site on Grid on site with Ubaie:53.7 V X Fme Hosia=
h / 674007438 from huawei is informed","edwige.kapawo@matech-cameroun.com",=
"314","12-04-2025 08:50:31","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004789397","Nko=
lbisson usines des eaux 2","","12-04-2025 08:34:05","12-04-2025 08:30:57","=
12-04-2025 09:23:21","Grid outage, site went down  due to Gen overload(12.5=
kva) IHS SS Alphonse is informed// He reduce load","TIENTCHEU NZETCHIEU GAE=
L","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, =
site went down  due to Gen overload(12.5kva) IHS SS Alphonse is informed// =
He reduce load","edwige.kapawo@matech-cameroun.com","189","12-04-2025 08:34=
:05","MATECH CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0004789393","M=
vog-Betsi","","12-04-2025 08:33:11","12-04-2025 08:31:01","12-04-2025 09:27=
:46","Site went down due to one of the AVR=92s pins disconnected (probably =
due to vibration of the GENERATOR). //we have repositioned and recalibrated=
 the AVR (SX460).","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - AVR","Site went down due to one of the AVR=92s pins disconnected (=
probably due to vibration of the GENERATOR). //we have repositioned and rec=
alibrated the AVR (SX460).","edwige.kapawo@matech-cameroun.com","131","12-0=
4-2025 08:33:11","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004789349","Mfo=
u EPC","","12-04-2025 08:20:03","12-04-2025 08:07:40","12-04-2025 10:13:57"=
,"Grid outage, site went down because gen ran until fuel shortage // Refuel=
ing done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage, site went down because gen ran until fuel shortage // Refu=
eling done","edwige.kapawo@matech-cameroun.com","744","12-04-2025 08:20:03"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004789308","Ngouetou=
","","12-04-2025 08:06:08","12-04-2025 07:58:12","12-04-2025 08:14:52","Cas=
caded Incident from TTO4888794","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site with Ubaie=
=3D54V site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gregoire( 6520=
70658)from Huawei is informed","system","273843","12-04-2025 08:06:08","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_301","IHS_YND_460","NOCINC0004789302","M=
atsari","IHS_YND_454, IHS_YND_456","12-04-2025 08:05:25","12-04-2025 07:58:=
12","12-04-2025 09:40:52","Active//No power issue on site with Ubaie=3D54V =
site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gregoire( 652070658)f=
rom Huawei is informed","Parker Tchoup","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue =
on site with Ubaie=3D54V site on Gen (start threshold ubai=3D48.4V) The Tx =
Fme Gregoire( 652070658)from Huawei is informed","edwige.kapawo@matech-came=
roun.com","435","12-04-2025 08:05:25","MATECH CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0004789282","M=
BIMBIM","","12-04-2025 08:00:59","12-04-2025 07:58:12","12-04-2025 08:14:52=
","","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Ac=
tive","Active//No power issue on site with Ubaie=3D54V site on Gen (start t=
hreshold ubai=3D48.4V) The Tx Fme Gregoire( 652070658)from Huawei is inform=
ed","edwige.kapawo@matech-cameroun.com","273843","12-04-2025 08:00:59","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004789222","E=
MANA BILICK CITY","","12-04-2025 07:46:45","12-04-2025 07:34:38","12-04-202=
5 08:57:22","Grid Outage, Site went Down due to Gen Noise (access issue due=
 to landlord) // manual start of Gen","Fabrice Pouakam","Access Denial","Le=
ase Or Legal","Landlord Related Issues","Access Issue - Land Lord","Grid Ou=
tage, Site went Down due to Gen Noise (access issue due to landlord) // man=
ual start of Gen","edwige.kapawo@matech-cameroun.com","729","12-04-2025 07:=
46:45","MATECH CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0004789199","C=
-Supreme","","12-04-2025 07:40:23","12-04-2025 07:37:09","12-04-2025 21:35:=
57","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space =
to deploy a MDG//Grid Restored","edwige.kapawo@matech-cameroun.com","195","=
12-04-2025 07:40:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0004789126","Hotel de=
 Ville Yde","","12-04-2025 07:22:36","12-04-2025 07:14:37","12-04-2025 13:3=
3:50","Cascaded Incident from TTO4888602","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went Down due to Grid out=
age (No space to deploy) // grid power restored","system","283637","12-04-2=
025 07:22:36","MATECH CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0004789120","N=
R-Bastos","IHS_YND_019","12-04-2025 07:20:49","12-04-2025 07:14:37","12-04-=
2025 13:33:50","Site went Down due to Grid outage (No space to deploy) // g=
rid power restored","","Grid Supply","Passive","Grid","National Grid - Grid=
 Outage Issue","Site went Down due to Grid outage (No space to deploy) // g=
rid power restored","edwige.kapawo@matech-cameroun.com","373","12-04-2025 0=
7:20:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_057","NOCINC0004789055","Mvolye-N=
ew","","12-04-2025 07:00:59","12-04-2025 06:57:53","12-04-2025 08:50:30","S=
ite went Down due to Grid outage (No space to deploy) // grid power restore=
d","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","S=
ite went Down due to Grid outage (No space to deploy) // grid power restore=
d","joelle.ekessi@ihstowers.com","187","12-04-2025 07:00:59","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004788820","C=
amp-Sic-Tsinga","","12-04-2025 06:00:39","12-04-2025 05:55:31","12-04-2025 =
21:23:31","Grid outage no space to deploy mobile gen//Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
no space to deploy mobile gen//Grid return","olivier.kwedi@ihstowers.com","=
310","12-04-2025 06:00:39","MATECH CMR"
"Closed Complete","Site Down","T0526","IHS_YND_088","NOCINC0004788804","Elo=
bi Mokolo","","12-04-2025 05:52:07","12-04-2025 05:43:02","12-04-2025 06:37=
:33",":Grid outage gen  ran until fuel shortage//Refueling done","Mboua Thi=
erry","Fuel Outage","Passive","Diesel","Diesel Outage",":Grid outage gen  r=
an until fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.com","=
999","12-04-2025 05:52:07","MATECH CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0004788794","Bye=
massi Carrefour","","12-04-2025 05:47:13","12-04-2025 05:34:54","12-04-2025=
 07:36:30","Grid outage gen ran until fuel shortage//Refueling done","Paul =
BIBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen r=
an until fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.com","=
740","12-04-2025 05:47:13","MATECH CMR"
"Closed Complete","Site Down","T0539","IHS_YND_034","NOCINC0004788751","EMI=
A MTN","","12-04-2025 05:30:13","12-04-2025 05:27:09","12-04-2025 08:49:39"=
,"Grid outage, Site went Down due to No space to deploy // grid power resto=
red","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid outage, Site went Down due to No space to deploy // grid power restor=
ed","ludivine.ngamaleu@ihstowers.com","185","12-04-2025 05:30:13","MATECH C=
MR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004788721","Abo=
me","","12-04-2025 05:15:30","12-04-2025 05:04:26","12-04-2025 05:21:30","A=
ctive/ No power issue on site Ubay 53.7V site on Grid  and The TX FME Leone=
l Steve (655184876) from huawei is informed , site up without intervention"=
,"MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active/ No power issue on site Ubay 53.7V site=
 on Grid  and The TX FME Leonel Steve (655184876) from huawei is informed ,=
 site up without intervention","ludivine.ngamaleu@ihstowers.com","666","12-=
04-2025 05:15:30","MATECH CMR"
"Closed Complete","Site Down","T0217","IHS_YND_018","NOCINC0004788687","P&T=
 Building","","12-04-2025 05:01:15","12-04-2025 04:51:56","12-04-2025 21:38=
:31","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space=
 to deploy a MDG//Grid Restored","ludivine.ngamaleu@ihstowers.com","559","1=
2-04-2025 05:01:15","MATECH CMR"
"Closed Complete","Site Down","T3149","IHS_YND_044","NOCINC0004788669","Pol=
ytechnique","","12-04-2025 04:58:45","12-04-2025 04:49:40","12-04-2025 08:4=
5:04","Grid outage, Site went Down because No space todeploy // grid power =
restored","","Grid Supply","Passive","Grid","National Grid - Grid Outage Is=
sue","Grid outage, Site went Down because No space todeploy // grid power r=
estored","ludivine.ngamaleu@ihstowers.com","545","12-04-2025 04:58:45","MAT=
ECH CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0004788667","ENA=
M","","12-04-2025 04:58:11","12-04-2025 04:49:04","12-04-2025 05:00:07",": =
No power issue on site Ubaie=3D52 V site on Grid . The TX fme Hosiah //6996=
99694 of huawei is informed.","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm",": No power issue on site Ubaie=
=3D52 V site on Grid . The TX fme Hosiah //699699694 of huawei is informed.=
","ludivine.ngamaleu@ihstowers.com","549","12-04-2025 04:58:11","MATECH CMR=
"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004788662","Av =
Kennedy","","12-04-2025 04:57:19","12-04-2025 04:47:01","12-04-2025 09:36:0=
1","Grid only, Eneo outage, no space to deploy MGE // eneo return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only, E=
neo outage, no space to deploy MGE // eneo return","ludivine.ngamaleu@ihsto=
wers.com","619","12-04-2025 04:57:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0004788655","Montee-J=
ouvence-II","","12-04-2025 04:51:12","12-04-2025 04:11:00","12-04-2025 22:2=
5:56","Cascaded Incident from TTO4888030","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, no space to de=
ploy MGE,// Grid return
","system","337979","12-04-2025 04:51:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0004788653","Damas","=
","12-04-2025 04:51:12","12-04-2025 04:11:00","12-04-2025 22:25:56","Cascad=
ed Incident from TTO4888030","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, no space to deploy MGE,// Gr=
id return
","system","337979","12-04-2025 04:51:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0004788654","Tamtam W=
eekend","","12-04-2025 04:51:12","12-04-2025 04:11:00","12-04-2025 22:25:56=
","Cascaded Incident from TTO4888030","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, no space to deploy=
 MGE,// Grid return
","system","337979","12-04-2025 04:51:12","MATECH CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004788637","Bas=
tos Amb Coree","","12-04-2025 04:40:33","12-04-2025 04:34:17","12-04-2025 1=
3:02:55","Site went Down due to Grid outage (No space to deploy) // grid po=
wer restored","","Grid Supply","Passive","Grid","National Grid - Grid Outag=
e Issue","Site went Down due to Grid outage (No space to deploy) // grid po=
wer restored","loic.noumsi@matech-cameroun.com","377","12-04-2025 04:40:33"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0004788614","R=
d-Pt-Express","IHS_YND_166, IHS_YND_151, IHS_YND_518","12-04-2025 04:27:15"=
,"12-04-2025 04:11:00","12-04-2025 22:25:56","Grid outage, no space to depl=
oy MGE,// Grid return","","Grid Supply","Passive","Grid","National Grid - G=
rid Outage Issue","Grid outage, no space to deploy MGE,// Grid return
","gaelle.njiofack@matech-cameroun.com","976","12-04-2025 04:27:15","MATECH=
 CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004788579","Lad=
a I Yde","","12-04-2025 04:14:42","12-04-2025 04:13:11","12-04-2025 06:53:0=
4","Site went down because 02/3 rectifiers were malfunctioning  // He reset=
 them","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down because 02/3 rectifiers were malfunctioning  // =
He reset them","ludivine.ngamaleu@ihstowers.com","92","12-04-2025 04:14:42"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004788544","M=
essassi okolo","","12-04-2025 04:03:14","12-04-2025 03:39:37","12-04-2025 1=
2:45:36","ACTIVE//No power issue on site Ubaie=3D54.4V, site on Grid The TX=
 Fme Synphorien 691316854 of Huawei is informed.","Fabrice Pouakam","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","ACTIVE//No power issue on site Ubaie=3D54.4V, site on Grid The TX Fme =
Synphorien 691316854 of Huawei is informe","gaelle.njiofack@matech-cameroun=
.com","1418","12-04-2025 04:03:14","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004788510","Mes=
sassi 2","","12-04-2025 03:48:42","12-04-2025 03:41:31","12-04-2025 03:52:4=
2","Site went down because 01/03 rectifiers dysfunctionned// He reset recti=
fiers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down because 01/03 rectifiers dysfunctionned// He rese=
t rectifiers","gaelle.njiofack@matech-cameroun.com","432","12-04-2025 03:48=
:42","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004788480","N=
kolangaa","IHS_YND_290","12-04-2025 03:38:32","11-04-2025 18:19:18","12-04-=
2025 05:20:50","Active//No power issue on site Ubaie: 53V site on Grid The =
TX FME Henri (699949693) from Huawei is informed.","Mba Lazare Herve","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site Ubaie: 53V site on Grid The TX FME He=
nri (699949693) from Huawei is informed.","loic.noumsi@matech-cameroun.com"=
,"33993","12-04-2025 03:38:32","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004788440","Eko=
mbitie","","12-04-2025 03:19:12","12-04-2025 01:43:00","12-04-2025 03:15:10=
","Grid fluctuation, Site went down because gen failed to start due to grid=
 bad voltage,/ He bypassed the Grid and site on Gen","Fabrice Pouakam","Gri=
d Supply","Passive","Grid","National Grid - Unstable Grid Supply Issue","Gr=
id fluctuation, Site went down because gen failed to start due to grid bad =
voltage,/ He bypassed the Grid and site on Gen","ludivine.ngamaleu@ihstower=
s.com","5795","12-04-2025 03:19:12","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004788419","B=
riqueterie","","12-04-2025 03:08:58","12-04-2025 02:41:39","12-04-2025 21:2=
4:51","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spac=
e to deploy a MDG//Grid Restored","gaelle.njiofack@matech-cameroun.com","16=
40","12-04-2025 03:08:58","MATECH CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004788208","Bri=
quetterie","","12-04-2025 02:29:57","12-04-2025 02:18:43","12-04-2025 21:33=
:36","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space=
 to deploy a MDG//Grid Restored","ludivine.ngamaleu@ihstowers.com","675","1=
2-04-2025 02:29:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004788203","Golf Qua=
ter","","12-04-2025 02:27:43","12-04-2025 02:03:39","12-04-2025 04:01:48","=
Cascaded Incident from TTO4887558","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue site on gen  with Ubaie=
:54V Mohamadou Eloundou Bertrand from Huaei is informed from Huawei is info=
rmed","system","287826","12-04-2025 02:27:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004788204","Bastos B=
ethesda","","12-04-2025 02:27:43","12-04-2025 02:03:39","12-04-2025 04:01:4=
8","Cascaded Incident from TTO4887558","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue site on gen  with U=
baie:54V Mohamadou Eloundou Bertrand from Huaei is informed from Huawei is =
informed","system","287826","12-04-2025 02:27:43","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004788200","B=
astos-Nylon","IHS_YND_220, IHS_YND_563","12-04-2025 02:26:59","12-04-2025 0=
2:03:39","12-04-2025 08:20:48","No power issue site on gen  with Ubaie:54V =
Mohamadou Eloundou Bertrand from Huaei is informed from Huawei is informed"=
,"Mboua Thierry","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue site on gen  with Ubaie:54V Moh=
amadou Eloundou Bertrand from Huaei is informed from Huawei is informed","g=
aelle.njiofack@matech-cameroun.com","1401","12-04-2025 02:26:59","MATECH CM=
R"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0004788174","Bas=
tos Ekoudou","","12-04-2025 02:13:30","12-04-2025 02:12:25","12-04-2025 04:=
55:22","Grid outage, Gen ran until fuel shortage // Refueling done","Mboua =
Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, Gen=
 ran until fuel shortage // Refueling done","ludivine.ngamaleu@ihstowers.co=
m","66","12-04-2025 02:13:30","MATECH CMR"
"Closed Complete","Site Down","T1669","IHS_YND_195","NOCINC0004788172","chi=
na embassy yde","","12-04-2025 02:11:50","12-04-2025 02:10:36","12-04-2025 =
12:36:20","Site went Down due to Grid outage (No space to deploy) // grid p=
ower restored","","Grid Supply","Passive","Grid","National Grid - Grid Outa=
ge Issue","Site went Down due to Grid outage (No space to deploy) // grid p=
ower restored","ludivine.ngamaleu@ihstowers.com","74","12-04-2025 02:11:50"=
,"MATECH CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0004788159","Tsi=
nga","","12-04-2025 02:07:28","12-04-2025 02:02:13","12-04-2025 04:11:13","=
Grid outage, Gen ran until fuel shortage // Refueling done","Mboua Thierry"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, Gen ran unt=
il fuel shortage // Refueling done","gaelle.njiofack@matech-cameroun.com","=
316","12-04-2025 02:07:28","MATECH CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004788154","Lab=
oratoire  Meka","","12-04-2025 02:06:30","12-04-2025 02:01:15","12-04-2025 =
12:46:15","Grid Outage, No space to deploy // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No spac=
e to deploy // Grid return","ludivine.ngamaleu@ihstowers.com","315","12-04-=
2025 02:06:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004788141","Biyemass=
i LAC","","12-04-2025 02:02:54","12-04-2025 01:50:36","12-04-2025 13:56:36"=
,"Grid outage, No space to deploy a mobil Gen // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No s=
pace to deploy a mobil Gen // Grid return","system","738","12-04-2025 02:02=
:54","MATECH CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004788129","BIY=
EMASSI NIKI","","12-04-2025 01:59:53","12-04-2025 01:50:36","12-04-2025 02:=
56:14","Grid Outage Site went down due to Gen overload(5kva, 200A)  // fme =
reduced load and restarted gen","Hyemafo Gildas","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid Outage Site went down due to Gen over=
load(5kva, 200A)  // fme reduced load and restarted gen","gaelle.njiofack@m=
atech-cameroun.com","661","12-04-2025 01:59:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_030","NOCINC0004788116","E-Police=
","","12-04-2025 01:56:01","12-04-2025 01:47:15","12-04-2025 08:46:38","Cas=
caded Incident from TTO4887448","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage, Site went Down because No space todepl=
oy // grid power restored","system","288990","12-04-2025 01:56:01","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0004788117","Sapeur",=
"","12-04-2025 01:56:01","12-04-2025 01:47:15","12-04-2025 08:46:38","Casca=
ded Incident from TTO4887448","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, Site went Down because No s=
pace todeploy // grid power restored","system","288990","12-04-2025 01:56:0=
1","MATECH CMR"
"Closed Complete","Site Down","CTR_323","IHS_YND_043","NOCINC0004788105","E=
mia","IHS_YND_030, IHS_YND_029","12-04-2025 01:52:30","12-04-2025 01:47:15"=
,"12-04-2025 08:47:45","Grid outage, Site went Down because No space todepl=
oy // grid power restored","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","Grid outage, Site went Down because No space todeplo=
y // grid power restored","gaelle.njiofack@matech-cameroun.com","316","12-0=
4-2025 01:52:30","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0004788099","Hop=
ital Central","","12-04-2025 01:50:19","12-04-2025 01:45:07","12-04-2025 21=
:35:17","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Sp=
ace to deploy a MDG//Grid Restored","gaelle.njiofack@matech-cameroun.com","=
313","12-04-2025 01:50:19","MATECH CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0004787991","Y=
de-M-Central","","12-04-2025 01:08:24","12-04-2025 01:00:43","12-04-2025 01=
:22:02","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","Site impacted by CBC","gaelle.njiofack@matech-cameroun.com","263008","12=
-04-2025 01:08:24","MATECH CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0004787987","E=
lig-Essono","","12-04-2025 01:06:55","12-04-2025 01:00:43","12-04-2025 01:2=
2:02","","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Site impacted by CBC","gaelle.njiofack@matech-cameroun.com","26=
3008","12-04-2025 01:06:55","MATECH CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0004787984","I=
mm-Olympique","IHS_YND_007, IHS_YND_012, IHS_YND_002","12-04-2025 01:05:50"=
,"12-04-2025 01:00:43","12-04-2025 01:22:02","Site impacted by CBC","Paul B=
IBOUM","3RD Party Power Failure","Passive","Power Provided By 3RD Party","P=
ower Provided By 3RD Party","Site impacted by CBC","gaelle.njiofack@matech-=
cameroun.com","308","12-04-2025 01:05:50","MATECH CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004787982","M=
ontee-Anne-Rouge","","12-04-2025 01:05:08","12-04-2025 01:00:43","12-04-202=
5 01:22:02","","","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Site impacted by CBC","gaelle.njiofack@matech-cameroun.com","263008"=
,"12-04-2025 01:05:08","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004787971","Acc=
acia New","","12-04-2025 00:56:29","12-04-2025 00:51:12","12-04-2025 13:55:=
49","Grid outage, No space to deploy a MDG//Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space =
to deploy a MDG//Grid return","gaelle.njiofack@matech-cameroun.com","319","=
12-04-2025 00:56:29","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004787804","Nko=
zoa","","12-04-2025 00:03:26","12-04-2025 00:00:18","12-04-2025 11:24:18","=
Grid outage, site went down due to gen overload (20kva, 340A) // He reduced=
 the load and site on GEN","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen overloa=
d (20kva, 340A) // He reduced the load and site on GEN","gaelle.njiofack@ma=
tech-cameroun.com","190","12-04-2025 00:03:26","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004787733","Man=
guiers Dispensaire","","11-04-2025 23:48:36","11-04-2025 23:46:23","11-04-2=
025 23:48:30","Grid fluctuations site went down due to bad grid voltage and=
 no RCP //grid power stabilized","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Unstable Grid Supply Issue","Grid fluctuations site=
 went down due to bad grid voltage and no RCP //grid power stabilized","gae=
lle.njiofack@matech-cameroun.com","133","11-04-2025 23:48:36","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0004787648","Clu=
b France","","11-04-2025 23:27:34","11-04-2025 23:12:56","12-04-2025 13:49:=
05","Site went Down due to Grid outage (No space to deploy) // grid power r=
estored","","Grid Supply","Passive","Grid","National Grid - Grid Outage Iss=
ue","Site went Down due to Grid outage (No space to deploy) // grid power r=
estored","gaelle.njiofack@matech-cameroun.com","878","11-04-2025 23:27:34",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004787621","M=
EHANDAN","","11-04-2025 23:19:06","11-04-2025 18:59:52","11-04-2025 23:15:5=
2","Site is unstable due to rectifiers issue","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down due to Defic=
iency rectifiers on site//site stabilised","gaelle.njiofack@matech-cameroun=
.com","78447","11-04-2025 23:19:06","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004787459","M=
essassi 2","","11-04-2025 22:41:19","11-04-2025 22:36:03","11-04-2025 22:50=
:02","Site went down because 01/03 rectifiers dysfunctionned// He reset rec=
tifiers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down because 01/03 rectifiers dysfunctionned// He re=
set rectifiers","olivier.kwedi@ihstowers.com","318","11-04-2025 22:41:19","=
MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004787449","C=
rf-Nkolbisson","","11-04-2025 22:38:26","11-04-2025 22:26:19","11-04-2025 2=
2:51:38","Site went down because of CB(125A) in PWC due to load increase//H=
e reamed the CB and reduce the load (awaiting intervention of orange after =
two departs)","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","site down due to Disjun=
ction in the ocm bay // grid return (awaiting intervention of orange)","oli=
vier.kwedi@ihstowers.com","728","11-04-2025 22:38:26","MATECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004787447","Sim=
e Building","","11-04-2025 22:37:31","11-04-2025 22:30:10","12-04-2025 05:3=
4:36","Grid outage, Gen stopped due to High temp // Water add and gen start=
 manually","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","Gen Tem=
p High","Grid outage, Gen stopped due to High temp // Water add and gen sta=
rt manually","ludivine.ngamaleu@ihstowers.com","441","11-04-2025 22:37:31",=
"MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004787433","Mok=
olo Yaounde","","11-04-2025 22:35:36","11-04-2025 22:21:24","12-04-2025 21:=
26:28","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spa=
ce to deploy a MDG//Grid Restored","ludivine.ngamaleu@ihstowers.com","853",=
"11-04-2025 22:35:36","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004787209","E=
MANA BILICK CITY","","11-04-2025 21:41:31","11-04-2025 21:30:03","11-04-202=
5 21:47:22","Active: no power issue, site is on gen with Ubaie: 53V, Sympho=
rien(650257151) from Huawei is informed","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: no power issue, site is on gen with Ubaie: 53V, Symphorien(650257151) f=
rom Huawei is informed","vanel.mbiada@matech-cameroun.com","689","11-04-202=
5 21:41:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_129","NOCINC0004787121","Bastos-B=
AT","","11-04-2025 21:26:43","11-04-2025 20:56:24","11-04-2025 21:38:53","C=
ascaded Incident from TTO4886113","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage gen failed to start due =
to no automatism on site //gen manually started","system","270310","11-04-2=
025 21:26:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004787116","Ngoulmek=
ong-Nord","","11-04-2025 21:25:39","11-04-2025 21:02:11","11-04-2025 21:32:=
06","Cascaded Incident from TTO4886194","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,site went down due=
 to high temp alarm //He added water and manually start the gen","system","=
320466","11-04-2025 21:25:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0004787117","Mballa 4=
","","11-04-2025 21:25:39","11-04-2025 21:02:11","11-04-2025 21:32:06","Cas=
caded Incident from TTO4886194","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage,site went down due to hig=
h temp alarm //He added water and manually start the gen","system","320466"=
,"11-04-2025 21:25:39","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004787109","Lad=
a I Yde","","11-04-2025 21:22:55","11-04-2025 21:07:39","11-04-2025 22:13:3=
4","Grid fluctuation,Site went down because Gen failed to start due to Grid=
 bad voltage //He bypassed the Grid and site on GEN","Mba Lazare Herve","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuation,Site went down because Gen failed to start due to Grid bad vol=
tage //He bypassed the Grid and site on GEN","vanel.mbiada@matech-cameroun.=
com","917","11-04-2025 21:22:55","MATECH CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0004787057","San=
ta Barbara Yde","IHS_YND_277, IHS_YND_242","11-04-2025 21:13:43","11-04-202=
5 21:02:11","11-04-2025 21:32:06","Grid outage,site went down due to high t=
emp alarm //He added water and manually start the gen","Delor Telezing","Eq=
uipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage,site went=
 down due to high temp alarm //He added water and manually start the gen","=
vanel.mbiada@matech-cameroun.com","693","11-04-2025 21:13:43","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004787035","Eko=
mbitie","","11-04-2025 21:08:39","11-04-2025 21:02:11","11-04-2025 21:32:06=
","site impacted by Santa babara yde (Grid outage,site went down due to hig=
h temp alarm //He added water and manually start the gen)","Fabrice Pouakam=
","Equipment Repair","Passive","ACDG Gen","Gen Temp High","site impacted by=
 Santa babara yde (Grid outage,site went down due to high temp alarm //He a=
dded water and manually start the gen)","vanel.mbiada@matech-cameroun.com",=
"1875","11-04-2025 21:08:39","MATECH CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0004787034","Dra=
gage","","11-04-2025 21:08:37","11-04-2025 20:58:52","12-04-2025 00:25:32",=
"No power issue on site Ubay 50.8V site on Grid; Site up without interventi=
on","Mboua Thierry","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue on site Ubay 50.8V site on G=
rid; Site up without intervention","vanel.mbiada@matech-cameroun.com","586"=
,"11-04-2025 21:08:37","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004787011","Odz=
a Minkan IHS","","11-04-2025 21:03:57","11-04-2025 20:53:07","11-04-2025 21=
:15:42","Site went down due to Rectifier issue // we reset rectifier, site =
on Grid","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifie=
r Cabinet","Site went down due to Rectifier issue // we reset rectifier, si=
te on Grid","vanel.mbiada@matech-cameroun.com","651","11-04-2025 21:03:57",=
"MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0004786990","ARM=
P Building","IHS_YND_129","11-04-2025 21:01:33","11-04-2025 20:56:24","11-0=
4-2025 21:38:53","Grid outage gen failed to start due to no automatism on s=
ite //gen manually started","Mboua Thierry","Equipment Repair","Passive","C=
ontrol Panel","ATS-AMF Issue","Grid outage gen failed to start due to no au=
tomatism on site //gen manually started","vanel.mbiada@matech-cameroun.com"=
,"310","11-04-2025 21:01:33","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004786878","Nko=
zoa","","11-04-2025 20:45:40","11-04-2025 20:37:23","11-04-2025 20:45:43","=
Grid outage site went down because Gen overload(20KVA,340A) SS IHS F=E9lix =
Bateu is informed and Is confirmed// Grid return","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went d=
own because Gen overload(20KVA,340A) SS IHS F=E9lix Bateu is informed and I=
s confirmed// He reduced the load on site and started gen manualy","vanel.m=
biada@matech-cameroun.com","499","11-04-2025 20:45:40","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004786864","M=
essassi 2","","11-04-2025 20:43:15","11-04-2025 20:40:07","11-04-2025 20:44=
:53","Site went down due to rectifier dysfunction//Site stabilised","Fabric=
e Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","Sit=
e went down due to rectifier dysfunction//Site stabilised","vanel.mbiada@ma=
tech-cameroun.com","189","11-04-2025 20:43:15","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004786816","C=
rf-Nkolbisson","","11-04-2025 20:35:26","11-04-2025 19:27:16","11-04-2025 2=
0:00:28","Active// No power issue, site is on grid with Ubaie=3D55,4 V, Moh=
amadou(691144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue, site is on grid with Ubaie=3D55,4 V, Mohama=
dou(691144435) from Huawei is informed","vanel.mbiada@matech-cameroun.com",=
"4091","11-04-2025 20:35:26","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004786810","B=
iteng-Maetur","","11-04-2025 20:34:50","11-04-2025 19:43:35","12-04-2025 06=
:04:31","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","vanel.m=
biada@matech-cameroun.com","3076","11-04-2025 20:34:50","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004786800","O=
lembe-Terminus","","11-04-2025 20:32:44","11-04-2025 17:43:32","11-04-2025 =
18:35:01","Active//No power issue on site U=3D54.7V, site on Grid, Synphori=
en/691316854/ from Huawei is informed","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue on site U=3D54.7V, site on Grid, Synphorien/691316854/ fro=
m Huawei is informed","vanel.mbiada@matech-cameroun.com","10153","11-04-202=
5 20:32:44","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004786519","M=
essassi okolo","","11-04-2025 19:40:24","11-04-2025 19:01:14","11-04-2025 1=
9:10:44","ACTIVE//No power issue on site Ubaie=3D54.4V, site on Grid The TX=
 Fme Synphorien 691316854 of Huawei is informed.Noticed impacted by pont em=
mana ","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue on site Ubaie=
=3D54.4V, site on Grid The TX Fme Synphorien 691316854 of Huawei is informe=
d.Noticed impacted by pont emmana ","vanel.mbiada@matech-cameroun.com","235=
2","11-04-2025 19:40:24","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004786407","Nsi=
malen MTN","","11-04-2025 19:30:21","11-04-2025 19:27:14","11-04-2025 19:43=
:20","Grid Outage, site went down before gen start due to poor battery back=
up // Gen started automatically","Albran Byorel","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, site went do=
wn before gen start due to poor battery backup // Gen started automatically=
","vanel.mbiada@matech-cameroun.com","188","11-04-2025 19:30:21","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004786382","Mom","",=
"11-04-2025 19:25:11","11-04-2025 15:43:02","11-04-2025 15:49:15","Cascaded=
 Incident from TTO4883818","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue on site ,site on Gen with Ubaie=
=3D50,3 V Etienne//695033981 is informed.Site impacted by Ngoummou","system=
","274648","11-04-2025 19:25:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004786383","Akono","=
","11-04-2025 19:25:11","11-04-2025 15:43:02","11-04-2025 15:49:15","Cascad=
ed Incident from TTO4883818","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site ,site on Gen with Ubaie=
=3D50,3 V Etienne//695033981 is informed.Site impacted by Ngoummou","system=
","274649","11-04-2025 19:25:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004786381","OLAMA","=
","11-04-2025 19:25:10","11-04-2025 15:43:02","11-04-2025 15:49:15","Cascad=
ed Incident from TTO4883818","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site ,site on Gen with Ubaie=
=3D50,3 V Etienne//695033981 is informed.Site impacted by Ngoummou","system=
","274648","11-04-2025 19:25:10","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004786202","Crf=
-Mbankolo-IHS","","11-04-2025 18:57:20","11-04-2025 18:21:14","11-04-2025 2=
0:13:33","Grid outage, site went down due to Gen overload(15kva,240A), Bern=
ar IHS is informed//He reduced the load and site on Gen","Mboua Thierry","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site =
went down due to Gen overload(15kva,240A), Bernar IHS is informed//He reduc=
ed the load and site on Gen","vanel.mbiada@matech-cameroun.com","2167","11-=
04-2025 18:57:20","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004786170","Aka=
k-Nkozoa-MTN-IHS","","11-04-2025 18:50:01","11-04-2025 18:43:53","11-04-202=
5 19:38:51","Grid outage site went down because Gen failed to start due PWC=
 dysfonction // He reset the PWC,and start the Gen manually","Fabrice Pouak=
am","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid outage site went down because Gen failed to start due PWC dysfonction=
 // He reset the PWC,and start the Gen manually","vanel.mbiada@matech-camer=
oun.com","370","11-04-2025 18:50:01","MATECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004786099","Emo=
mbo Esssomba","","11-04-2025 18:36:40","11-04-2025 18:31:26","11-04-2025 19=
:43:33","Grid outage site went down because Gen failed to start due to Grid=
 bad voltage//He bypassed the Grid and site on Gen","Mba Lazare Herve","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
outage site went down because Gen failed to start due to Grid bad voltage//=
He bypassed the Grid and site on Gen","vanel.mbiada@matech-cameroun.com","3=
14","11-04-2025 18:36:40","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004786096","Cit=
e des nations","","11-04-2025 18:35:19","11-04-2025 18:27:51","11-04-2025 1=
8:30:17","Active //No power issue ,site on Grid on site with Ubaie=3D53 V X=
 Fme Hosiah / 674007438 from huawei is informed","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active //No power issue ,site on Grid on site with Ubaie=3D53 V X Fme Hosia=
h / 674007438 from huawei is informed","vanel.mbiada@matech-cameroun.com","=
449","11-04-2025 18:35:19","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004786084","Oko=
lo Kilombo","","11-04-2025 18:32:57","11-04-2025 18:23:20","11-04-2025 20:0=
5:32","Grid fluctuation,Site went because Gen Failed to start due to Grid b=
ad voltage(lack of  2 phases)  //He did a bridge with the Good phase","Fabr=
ice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation,Site went because Gen Failed to start due to G=
rid bad voltage(lack of  2 phases)  //He did a bridge with the Good phase",=
"vanel.mbiada@matech-cameroun.com","578","11-04-2025 18:32:57","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004786049","Nsi=
malen MTN","","11-04-2025 18:24:24","11-04-2025 18:16:10","11-04-2025 18:47=
:38","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automatically","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen started automatically","vanel.mbiada@=
matech-cameroun.com","495","11-04-2025 18:24:24","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004785958","Eto=
udi2","","11-04-2025 18:07:50","11-04-2025 17:46:45","11-04-2025 19:14:57",=
"Site went down due to CB(125A) in PWC that tripped MTN //He rearmed it","D=
elor Telezing","Equipment Repair","Passive","Rectifier","Rectifier - Circui=
t Breaker","Site went down due to CB(125A) in PWC that tripped MTN //He rea=
rmed it","vanel.mbiada@matech-cameroun.com","1266","11-04-2025 18:07:50","M=
ATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004785897","Fla=
menco","","11-04-2025 17:59:27","11-04-2025 17:41:35","11-04-2025 19:55:29"=
,"Grid outage,gen failed to start due to card GE dysfunctionned//We reset c=
ard GE and gen manually started","Mboua Thierry","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due t=
o card GE dysfunctionned//We reset card GE and gen manually started","vanel=
.mbiada@matech-cameroun.com","1072","11-04-2025 17:59:27","MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004785883","Nko=
abang MTN","","11-04-2025 17:56:50","11-04-2025 17:48:41","11-04-2025 18:06=
:25","Site went down due to work of Felix Bate on site","Mba Lazare Herve",=
"Installation Activity","Passive","Planned Activity","Installation Activity=
","Site went down due to work of Felix Bate on site","vanel.mbiada@matech-c=
ameroun.com","490","11-04-2025 17:56:50","MATECH CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0004785675","Nko=
mkana","","11-04-2025 17:21:32","11-04-2025 17:19:19","11-04-2025 21:51:08"=
,"Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space to =
deploy a MDG//Grid Restored","cedric.tiani@matech-cameroun.com","135","11-0=
4-2025 17:21:32","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004785672","BAT=
A Mokolo OCM","","11-04-2025 17:20:54","11-04-2025 17:16:40","11-04-2025 19=
:50:56","Grid outage, No space to deploy a MDG // Grid restored","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy a MDG // Grid restored","cedric.tiani@matech-cameroun.com=
","255","11-04-2025 17:20:54","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004785670","MBA=
LNGONG LYCEE","","11-04-2025 17:20:20","11-04-2025 17:16:11","11-04-2025 17=
:26:13","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Site stabilized",=
"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, Site went down because Gen stopped due to overload(9kva, 130A) S=
S IHS Felix Zambe is informed and confirmed // Site stabilized","cedric.tia=
ni@matech-cameroun.com","251","11-04-2025 17:20:20","MATECH CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004785667","NYO=
M 2 IHS","","11-04-2025 17:19:49","11-04-2025 17:11:36","11-04-2025 18:11:4=
3","Grid outage, Gen stopped due to Alarm High temp // Water add, Gen Card =
reset and Gen start manually","Fabrice Pouakam","Equipment Repair","Passive=
","ACDG Gen","Gen Temp High","Grid outage, Gen stopped due to Alarm High te=
mp // Water add, Gen Card reset and Gen start manually","cedric.tiani@matec=
h-cameroun.com","494","11-04-2025 17:19:49","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004785515","C=
RH-Etoug-Ebe","","11-04-2025 16:58:48","11-04-2025 16:46:42","11-04-2025 17=
:00:04","no power issue, site is on grid with Ubaie=3D53V, mohamadou(691144=
435) from Huawei is informed","Hyemafo Gildas","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue, =
site is on grid with Ubaie=3D53V, mohamadou(691144435) from Huawei is infor=
med","cedric.tiani@matech-cameroun.com","727","11-04-2025 16:58:48","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0004785388","E=
lig Edzoa","","11-04-2025 16:34:22","11-04-2025 16:21:03","11-04-2025 16:30=
:51","No power issue site on grid with U=3D51v, Armand (699949553 / Huawei)=
 is informed","Delor Telezing","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with=
 U=3D51v, Armand (699949553 / Huawei) is informed","cedric.tiani@matech-cam=
eroun.com","800","11-04-2025 16:34:22","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004785293","ODZ=
A MINKAN EDIBI ASSI","","11-04-2025 16:21:55","11-04-2025 16:18:21","11-04-=
2025 17:56:02","site Went down due to insufficient rectifiers //he reset it=
","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","site Went down due to insufficient rectifiers //he reset it","vanel.mbi=
ada@matech-cameroun.com","215","11-04-2025 16:21:55","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004785092","H=
-Paradis","","11-04-2025 15:47:11","11-04-2025 15:42:01","11-04-2025 15:50:=
10","Active // No power issue site on grid with U=3D50,5 V Tx Fme Armand Ng=
estsa (691144412) of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power =
issue site on grid with U=3D50,5 V Tx Fme Armand Ngestsa (691144412) of hua=
wei is informed","cedric.tiani@matech-cameroun.com","311","11-04-2025 15:47=
:11","MATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0004785084","Min=
ka","IHS_YND_687, IHS_YND_370, IHS_YND_365","11-04-2025 15:46:16","11-04-20=
25 15:43:02","11-04-2025 15:49:15","No power issue on site ,site on Gen wit=
h Ubaie=3D50,3 V Etienne//695033981 is informed.Site impacted by Ngoummou",=
"Fanda Brice","Customer Equipment Failure","Active","Active Equipment Failu=
re","Affected by 3rd Party Site","No power issue on site ,site on Gen with =
Ubaie=3D50,3 V Etienne//695033981 is informed.Site impacted by Ngoummou","v=
anel.mbiada@matech-cameroun.com","194","11-04-2025 15:46:16","MATECH CMR"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0004785075","M=
ONTEE NKONDENGUI","","11-04-2025 15:43:27","11-04-2025 15:34:15","11-04-202=
5 15:40:16","No power issue U =3D52.4V site on Grid. The Tx FME Eloundou (6=
93212405 )from Huawei is informed","Albran Byorel","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue U =3D52.4V site on Grid. The Tx FME Eloundou (693212405 )from Huawei is =
informed","cedric.tiani@matech-cameroun.com","553","11-04-2025 15:43:27","M=
ATECH CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004784981","Ntu=
i administration","","11-04-2025 15:33:05","11-04-2025 15:31:47","11-04-202=
5 18:21:26","Grid outage Site went down because Gen ran until fuel Shortage=
","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","No powe=
r issue U =3D53,2V site on grid. The Tx FME Eloundou Bertrand (693212405)fr=
om Huawei is informed","vanel.mbiada@matech-cameroun.com","78","11-04-2025 =
15:33:05","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004784973","Mok=
olo Yaounde","","11-04-2025 15:31:23","11-04-2025 15:28:38","11-04-2025 15:=
30:23","No power issue U =3D53,2V site on grid. The Tx FME Eloundou Bertran=
d (693212405)from Huawei is informed","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D53=
,2V site on grid. The Tx FME Eloundou Bertrand (693212405)from Huawei is in=
formed","vanel.mbiada@matech-cameroun.com","166","11-04-2025 15:31:23","MAT=
ECH CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004784779","Sca=
lom","","11-04-2025 14:59:42","11-04-2025 14:53:33","11-04-2025 15:03:07","=
No power issue on site U=3D54.5V site on Grid The tx fme Mohamadou/ 6911444=
35 from Huawei is informed","Paul BIBOUM","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54.5V site on Grid The tx fme Mohamadou/ 691144435 from Huawei is inf=
ormed","mouliom.anselme@matech-cameroun.com","370","11-04-2025 14:59:42","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004784777","N=
koabang Ebolmedjock","","11-04-2025 14:59:29","11-04-2025 14:51:20","11-04-=
2025 15:00:41","Active//No power issue, Site on Gen. The Tx FME Brice Tsagu=
e(650214096) from Huawei is informed. Notice that it is impacted by Nkolmes=
seng-Abom Not Manager By IHS","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","Active=
//No power issue, Site on Gen. The Tx FME Brice Tsague(650214096) from Huaw=
ei is informed. Notice that it is impacted by Nkolmesseng-Abom Not Manager =
By IHS","cedric.tiani@matech-cameroun.com","490","11-04-2025 14:59:29","MAT=
ECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004784761","Nko=
l-Mbanda","","11-04-2025 14:56:43","11-04-2025 14:46:25","11-04-2025 15:06:=
41","Grid fluctuation,Site went down due to Grid bad voltage//sits stabilis=
ed","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation,Site went down due to Grid bad voltage/=
/sits stabilised","vanel.mbiada@matech-cameroun.com","619","11-04-2025 14:5=
6:43","MATECH CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004784480","M=
ontee-Des-Soeurs","","11-04-2025 14:13:59","11-04-2025 14:06:47","11-04-202=
5 14:57:32","Site went down due to 02/04 rectifiers faulty //He reset it","=
Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to 02/04 rectifiers faulty //He reset it","gerard.tcha=
ngoue@matech-cameroun.com","433","11-04-2025 14:13:59","MATECH CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0004784393","Nko=
mkana","IHS_YND_220, IHS_YND_126, IHS_YND_563, IHS_YND_127","11-04-2025 13:=
57:19","11-04-2025 13:49:08","11-04-2025 14:21:44","Grid Only, No space to =
deploy MDG // Grid return","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","Grid Only, No space to deploy MDG // Grid return","e=
dwige.kapawo@matech-cameroun.com","616","11-04-2025 13:57:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004784349","Tsinga",=
"","11-04-2025 13:52:01","11-04-2025 13:49:08","11-04-2025 14:19:38","Casca=
ded Incident from TTO4882936 - Cascade Removed From TTO4882936","Mboua Thie=
rry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid O=
nly, No space to deploy MDG // Grid return","system","267246","11-04-2025 1=
3:52:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004784348","Golf Qua=
ter","","11-04-2025 13:52:01","11-04-2025 13:49:08","11-04-2025 14:19:38","=
Cascaded Incident from TTO4882936 - Cascade Removed From TTO4882936","Mboua=
 Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid Only, No space to deploy MDG // Grid return","system","267245","11-04-2=
025 13:52:01","MATECH CMR"
"Closed Complete","Site Down","T0958","IHS_YND_269","NOCINC0004784327","Mvo=
g-Ebanda","","11-04-2025 13:49:31","11-04-2025 13:39:19","11-04-2025 15:06:=
22","Grid outage,Site went down due to GEN contactor dysfunctionning//he st=
arted the GEN manually","Siligap Boris","Equipment Repair","Passive","ACDG =
Gen","ACDG - Load Contactor","Grid outage,Site went down due to GEN contact=
or dysfunctionning//he started the GEN manually","edwige.kapawo@matech-came=
roun.com","2735","11-04-2025 13:49:31","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004784320","B=
astos-Nylon","","11-04-2025 13:48:28","11-04-2025 13:49:08","11-04-2025 14:=
19:38","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Only, No space to deploy MDG // Grid return","gerard.tc=
hangoue@matech-cameroun.com","267245","11-04-2025 13:48:28","MATECH CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0004784314","B=
astos Bethesda","","11-04-2025 13:47:13","11-04-2025 13:49:08","11-04-2025 =
14:19:38","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid Only, No space to deploy MDG // Grid return","gerard=
.tchangoue@matech-cameroun.com","267246","11-04-2025 13:47:13","MATECH CMR"
"Closed Complete","Site Down","T1582","IHS_YND_138","NOCINC0004784303","Nko=
mkana 2","","11-04-2025 13:46:03","11-04-2025 13:26:33","11-04-2025 13:45:3=
3","site went down because insufficient of rectifier on site//site stabiliz=
ed(need to added one rectifier)","Mboua Thierry","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","site went down because insufficient of r=
ectifier on site//site stabilized(need to added one rectifier)","edwige.kap=
awo@matech-cameroun.com","1171","11-04-2025 13:46:03","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004784101","Fla=
menco","","11-04-2025 13:14:14","11-04-2025 13:08:04","11-04-2025 14:02:34"=
,"Grid outage, site went down because gen failed to start due to gen card f=
aulty// Gen manually started","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen =
failed to start due to gen card faulty// Gen manually started","edwige.kapa=
wo@matech-cameroun.com","371","11-04-2025 13:14:14","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004784015","Nsi=
malen MTN","","11-04-2025 12:55:30","11-04-2025 12:51:16","11-04-2025 13:01=
:52","Grid outage, site went down  due to poor battery backup // Grid retur=
n","Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Battery Low","Grid outage, site went down  due to poor battery backup=
 // Grid return","edwige.kapawo@matech-cameroun.com","254","11-04-2025 12:5=
5:30","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004783999","Crf=
-Mbankolo-IHS","","11-04-2025 12:50:33","11-04-2025 12:46:25","11-04-2025 1=
4:19:15","Grid outage, site went down due to Gen overload(15kva,240A), Bern=
ar IHS is informed//He reduced the load and site on Gen","Mboua Thierry","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site =
went down due to Gen overload(15kva,240A), Bernar IHS is informed//He reduc=
ed the load and site on Gen","edwige.kapawo@matech-cameroun.com","271","11-=
04-2025 12:50:33","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004783943","NKO=
MKANA ELIZA HOTEL","","11-04-2025 12:47:59","11-04-2025 12:38:48","11-04-20=
25 15:43:32","Grid outage no space to deploy // Grid power return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
no space to deploy // Grid power return","edwige.kapawo@matech-cameroun.com=
","551","11-04-2025 12:47:59","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004783931","B=
ATA Mokolo OCM","","11-04-2025 12:45:08","11-04-2025 12:35:59","11-04-2025 =
14:18:38","Grid outage, No space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No =
space to deploy MDG // Grid return","gerard.tchangoue@matech-cameroun.com",=
"550","11-04-2025 12:45:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_214","NOCINC0004783871","Nkolmess=
eng-II","","11-04-2025 12:38:27","11-04-2025 12:31:06","11-04-2025 12:46:41=
","Cascaded Incident from TTO4882393","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,DG stopped due with =
alarm ""oil pressure""( unprouven Alarm ) // He  put site on Gen manually",=
"system","1214240","11-04-2025 12:38:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_213","NOCINC0004783870","Nkolmess=
eng","","11-04-2025 12:38:27","11-04-2025 12:31:06","11-04-2025 12:46:41","=
Cascaded Incident from TTO4882393","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,DG stopped due with ala=
rm ""oil pressure""( unprouven Alarm ) // He  put site on Gen manually","sy=
stem","1214239","11-04-2025 12:38:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_217","NOCINC0004783872","Abom",""=
,"11-04-2025 12:38:27","11-04-2025 12:31:06","11-04-2025 12:46:41","Cascade=
d Incident from TTO4882393","Siligap Boris","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage,DG stopped due with alarm ""oi=
l pressure""( unprouven Alarm ) // He  put site on Gen manually","system","=
1214240","11-04-2025 12:38:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_215","NOCINC0004783869","Eleveurs=
","","11-04-2025 12:38:27","11-04-2025 12:31:06","11-04-2025 12:46:41","Cas=
caded Incident from TTO4882393","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,DG stopped due with alarm =
""oil pressure""( unprouven Alarm ) // He  put site on Gen manually","syste=
m","1214239","11-04-2025 12:38:27","MATECH CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0004783842","Nko=
lmesseng","IHS_YND_215, IHS_YND_213, IHS_YND_214, IHS_YND_217","11-04-2025 =
12:34:14","11-04-2025 12:31:06","11-04-2025 12:49:41","Grid outage,DG stopp=
ed due with alarm ""oil pressure""( unprouven Alarm ) // He  put site on Ge=
n manually","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","Grid outage,DG stopped due with alarm ""oil pressure""( un=
prouven Alarm ) // He  put site on Gen manually","edwige.kapawo@matech-came=
roun.com","188","11-04-2025 12:34:14","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004783755","N=
koabang Ebolmedjock","","11-04-2025 12:21:02","11-04-2025 12:18:36","11-04-=
2025 12:26:44","No power issue Ubay 53.8V on GEN,Site impacted by Nkolmessi=
ng-Abom-II","Mba Lazare Herve","Customer Equipment Failure","Active","Activ=
e Equipment Failure","Affected by 3rd Party Site","No power issue Ubay 53.8=
V on GEN,Site impacted by Nkolmessing-Abom-II","gerard.tchangoue@matech-cam=
eroun.com","147","11-04-2025 12:21:02","MATECH CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0004783500","N=
kolkoumou OCM","","11-04-2025 11:45:24","11-04-2025 11:31:59","11-04-2025 1=
1:52:07","No power issue on site ,site on Grid with Ubaie=3D53,9 V The Tx F=
ME Mouahamadou (691144435) of Huawei is informed.","TIENTCHEU NZETCHIEU GAE=
L","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue on site ,site on Grid with Ubaie=3D53,9 V The=
 Tx FME Mouahamadou (691144435) of Huawei is informed.","gerard.tchangoue@m=
atech-cameroun.com","806","11-04-2025 11:45:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004783481","OTELE MT=
N","","11-04-2025 11:41:31","11-04-2025 11:36:42","11-04-2025 11:42:23","Ca=
scaded Incident from TTO4881922","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on grid with Ubaie: 53=
.5V.  Site impacted by Ngoumou_T0169","system","282349","11-04-2025 11:41:3=
1","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004783482","Akono","=
","11-04-2025 11:41:31","11-04-2025 11:36:42","11-04-2025 11:42:23","Cascad=
ed Incident from TTO4881922","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with Ubaie: 53.5V.=
  Site impacted by Ngoumou_T0169","system","282349","11-04-2025 11:41:31","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004783480","OLAMA","=
","11-04-2025 11:41:30","11-04-2025 11:36:42","11-04-2025 11:42:23","Cascad=
ed Incident from TTO4881922","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with Ubaie: 53.5V.=
  Site impacted by Ngoumou_T0169","system","282349","11-04-2025 11:41:30","=
MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004783440","Mom=
","IHS_YND_687, IHS_YND_531, IHS_YND_365","11-04-2025 11:38:50","11-04-2025=
 11:36:42","11-04-2025 11:42:23","No power issue site on grid with Ubaie: 5=
3.5V.  Site impacted by Ngoumou_T0169","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","Affected by 3rd Party Site","No=
 power issue site on grid with Ubaie: 53.5V.  Site impacted by Ngoumou_T016=
9","edwige.kapawo@matech-cameroun.com","129","11-04-2025 11:38:50","MATECH =
CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004783393","Ona=
ngondi (melen bikop)","","11-04-2025 11:31:32","11-04-2025 11:23:12","11-04=
-2025 13:31:12","Hybrid gen site .site went down due to hybrid malfunctionn=
ing//Gen manually started ","Fanda Brice","Equipment Repair","Passive","Hyb=
rid","Hybrid Module","Hybrid gen site .site went down due to hybrid malfunc=
tionning//Gen manually started ","edwige.kapawo@matech-cameroun.com","501",=
"11-04-2025 11:31:32","MATECH CMR"
"Closed Complete","Warning","T0183","IHS_YND_184","NOCINC0004783162","Nkolm=
esseng","","11-04-2025 10:51:46","","","Grid outage,DG stopped due with ala=
rm ""oil pressure""( unprouven Alarm ) // He  put site on Gen manually","Si=
ligap Boris","Warning","Warning","POWER","Warning - Site on Battery","Grid =
outage,DG stopped due with alarm ""oil pressure""( unprouven Alarm ) // He =
 put site on Gen manually","edwige.kapawo@matech-cameroun.com","1705","11-0=
4-2025 10:51:46","MATECH CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0004783091","E=
TOUDI CHAPELLE","","11-04-2025 10:45:18","11-04-2025 10:44:59","11-04-2025 =
10:47:25","site went down due to rectifiers dysfunctionnning // he reset th=
e rectifiers module and site on Grid","Delor Telezing","Equipment Repair","=
Passive","Rectifier","Rectifier Module","site went down due to rectifiers d=
ysfunctionnning // he reset the rectifiers module and site on Grid","gerard=
.tchangoue@matech-cameroun.com","21","11-04-2025 10:45:18","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004783010","B=
iteng-Maetur","","11-04-2025 10:30:47","11-04-2025 10:28:03","11-04-2025 15=
:01:14","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","gerard.=
tchangoue@matech-cameroun.com","166","11-04-2025 10:30:47","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004782492","M=
bankomo IHS","","11-04-2025 09:32:07","11-04-2025 09:17:48","11-04-2025 10:=
14:39","Active no power issue on site, site on Gen with U=3D54V Tx FME FULB=
ERT /654266068/ from huawei is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active n=
o power issue on site, site on Gen with U=3D54V Tx FME FULBERT /654266068/ =
from huawei is informed","gerard.tchangoue@matech-cameroun.com","860","11-0=
4-2025 09:32:07","MATECH CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004782293","M=
ontesquieux","","11-04-2025 09:03:29","11-04-2025 09:01:59","11-04-2025 11:=
11:00","Site went down because rectifier disfunctionning // He reset it: Si=
te on grid","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down because rectifier disfunctionning // He reset it=
: Site on grid","gerard.tchangoue@matech-cameroun.com","90","11-04-2025 09:=
03:29","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004782256","Man=
guiers Dispensaire","","11-04-2025 08:53:12","11-04-2025 08:51:02","11-04-2=
025 08:53:02","Grid fluctuations site went down due to bad grid voltage and=
 no RCP //grid power stabilized","Fabrice Pouakam","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Grid fluctuations site we=
nt down due to bad grid voltage and no RCP //grid power stabilized","edwige=
.kapawo@matech-cameroun.com","131","11-04-2025 08:53:12","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004782253","N=
kolondom","","11-04-2025 08:52:39","11-04-2025 08:49:59","11-04-2025 17:59:=
12","Grid outage,Site went down because Gen failed to start due to Main Gen=
 faulty//Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Generator Faulty","Grid outage,Site went down because Gen fail=
ed to start due to Main Gen faulty//Grid return","gerard.tchangoue@matech-c=
ameroun.com","162","11-04-2025 08:52:39","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004782246","B=
iteng-Maetur","","11-04-2025 08:51:18","11-04-2025 08:45:59","11-04-2025 09=
:55:55","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) // He reduced the load and manually start the Ge=
n. Alphonce (658 027 928) confirmed ","Mba Lazare Herve","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen started and stopped due to Gen overload(20kva, 280A) // He reduced th=
e load and manually start the Gen. Alphonce (658 027 928) confirmed ","gera=
rd.tchangoue@matech-cameroun.com","320","11-04-2025 08:51:18","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004782182","Par=
adis Hotel","","11-04-2025 08:35:06","11-04-2025 08:31:35","11-04-2025 09:3=
1:18","Site went down because 1/2 rectifier dysfunction/ He reset rectifer"=
,"Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down because 1/2 rectifier dysfunction/ He reset rectifer","ed=
wige.kapawo@matech-cameroun.com","211","11-04-2025 08:35:06","MATECH CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0004782016","B=
otmakak","IHS_EDA_101","11-04-2025 08:02:08","11-04-2025 05:53:04","11-04-2=
025 07:15:27","Site went down because gen fails to start due to grid bad vo=
ltage // He bypass grid and manually start the gen","Kemeni Franklin","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site w=
ent down because gen fails to start due to grid bad voltage // He bypass gr=
id and manually start the gen","kouoh.jean@ihstowers.com","7745","11-04-202=
5 08:02:08","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004782014","M=
essassi 2","","11-04-2025 08:01:48","11-04-2025 07:57:35","11-04-2025 08:03=
:17","Grid fluctuation, Site went down because Gen started due to Grid bad =
voltage// Grid stabilized","Fabrice Pouakam","Grid Supply","Passive","Grid"=
,"National Grid - Phase Controller Faulty","Grid fluctuation, Site went dow=
n because Gen started due to Grid bad voltage// Grid stabilized","edwige.ka=
pawo@matech-cameroun.com","255","11-04-2025 08:01:48","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004781790","Nko=
lnda","","11-04-2025 07:02:26","11-04-2025 06:37:56","11-04-2025 08:15:56",=
"Site went down Gen failed to start due to Grid bad voltage // He bypass gr=
id on the Good phase","Albran Byorel","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","Site went down Gen failed to start due=
 to Grid bad voltage // He bypass grid on the Good phase","edwige.kapawo@ma=
tech-cameroun.com","1471","11-04-2025 07:02:26","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004781757","NTE=
MASSI","","11-04-2025 06:57:10","11-04-2025 06:55:03","11-04-2025 07:44:03"=
,"Site went down because 1/2 rectifier dysfunction // He reset rectifer","D=
elor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down because 1/2 rectifier dysfunction // He reset rectifer","ed=
wige.kapawo@matech-cameroun.com","127","11-04-2025 06:57:10","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004781578","Nko=
ulou Carriere carrefourt","","11-04-2025 06:15:07","11-04-2025 00:37:59","1=
1-04-2025 06:41:57","Site went down because CB tripped in DC BOX // CB rear=
med","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Circuit Breaker Issue","Site went down because CB tripped in DC =
BOX // CB rearmed","franck.nkomot@matech-cameroun.com","20229","11-04-2025 =
06:15:07","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004781537","Mam=
bine","","11-04-2025 06:02:04","11-04-2025 05:39:54","11-04-2025 09:51:40",=
"Grid Outage, Site went Down due to Fuel shortage // tank inclined","Fanda =
Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid Outage, Site =
went Down due to Fuel shortage // tank inclined","franck.nkomot@matech-came=
roun.com","1331","11-04-2025 06:02:04","MATECH CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0004781526","B=
otmakak","","11-04-2025 05:59:46","11-04-2025 05:48:11","11-04-2025 05:53:0=
3","","Kemeni Franklin","Cascade Outage","Active","Cascade Active","Cascade=
 Active","Active// No power site on Grid with U=3D55,2V FREDDY /690419006 f=
rom Huawe is informed","franck.nkomot@matech-cameroun.com","5940","11-04-20=
25 05:59:46","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004781317","Aka=
k-Nkozoa-MTN-IHS","","11-04-2025 04:53:02","11-04-2025 04:45:53","11-04-202=
5 05:12:53","Grid outage, Gen fails to start due to overcurent alarm/ Gen c=
ard reset and manually stared","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage, Gen fails to start due t=
o overcurent alarm/ Gen card reset and manually stared","franck.nkomot@mate=
ch-cameroun.com","466","11-04-2025 04:53:02","MATECH CMR"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0004781282","Nko=
lndom","","11-04-2025 04:39:42","11-04-2025 04:30:13","11-04-2025 05:19:13"=
,"Grid outage gen failed to start due to alarm overcurrent//We reset card G=
E and gen manually started","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage gen failed to start due to a=
larm overcurrent//We reset card GE and gen manually started","franck.nkomot=
@matech-cameroun.com","569","11-04-2025 04:39:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_148","NOCINC0004781162","Chapelle=
-Nsimeyong","","11-04-2025 03:51:20","11-04-2025 01:14:03","11-04-2025 02:2=
7:03","Cascaded Incident from TTO4878821","MINKA NICOLAS","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage gen ran until fu=
el shortage//Refueling done","system","269410","11-04-2025 03:51:20","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0004780744","N=
kol-Mbanda","IHS_YND_562, IHS_YND_148","11-04-2025 01:20:11","11-04-2025 01=
:14:03","11-04-2025 02:37:03","Grid outage gen ran until fuel shortage//Ref=
ueling done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage gen ran until fuel shortage//Refueling done","franck.nkomot=
@matech-cameroun.com","369","11-04-2025 01:20:11","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004780742","A=
ccacia New","","11-04-2025 01:19:31","11-04-2025 01:14:03","11-04-2025 02:2=
7:03","Grid outage gen ran until fuel shortage//Refueling done","","Cascade=
 Outage","Passive","Cascade Passive","Cascade Passive","Grid outage gen ran=
 until fuel shortage//Refueling done","franck.nkomot@matech-cameroun.com","=
269410","11-04-2025 01:19:31","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004780714","Fla=
menco","","11-04-2025 01:05:04","11-04-2025 00:37:25","11-04-2025 01:06:02"=
,"Grid outage, site went down because gen failed to start due to gen card f=
aulty // Grid restored","Mboua Thierry","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid outage, site went down because gen failed=
 to start due to gen card faulty // Grid restored","franck.nkomot@matech-ca=
meroun.com","1660","11-04-2025 01:05:04","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004780596","Nko=
londom","","11-04-2025 00:50:24","11-04-2025 00:19:13","11-04-2025 03:13:13=
","Malfunction of ATS in the ZTE BTS due to Eneo fluctuation // ATS Reset",=
"Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Iss=
ue","Malfunction of ATS in the ZTE BTS due to Eneo fluctuation // ATS Reset=
","franck.nkomot@matech-cameroun.com","3575","11-04-2025 00:50:24","MATECH =
CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004780567","B=
ATA Mokolo OCM","","11-04-2025 00:40:39","11-04-2025 00:01:28","11-04-2025 =
01:01:42","Grid outage, No space to deploy a MDG // Grid restored","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.=
no space to deploy mobile gen//Grid return","franck.nkomot@matech-cameroun.=
com","2352","11-04-2025 00:40:39","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004780493","NKO=
MKANA ELIZA HOTEL","","11-04-2025 00:22:58","11-04-2025 00:03:48","11-04-20=
25 01:03:51","Eneo outage and Grid only, no space to deployed MGE // Grid r=
eturned","","Grid Supply","Passive","Grid","National Grid - Grid Outage Iss=
ue","Eneo outage and Grid only, no space to deployed MGE // Grid returned",=
"franck.nkomot@matech-cameroun.com","1151","11-04-2025 00:22:58","MATECH CM=
R"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004780452","Ole=
mbe MTN","","11-04-2025 00:05:59","10-04-2025 23:43:49","11-04-2025 01:29:4=
9","Site went down because IPT controller dyfunction //He bypassed it and p=
ut site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Control Pan=
el","ATS-AMF Issue","Site went down because IPT controller dyfunction //He =
bypassed it and put site on Gen","franck.nkomot@matech-cameroun.com","1331"=
,"11-04-2025 00:05:59","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004780447","A=
WAE OCM","","11-04-2025 00:03:16","10-04-2025 23:51:05","11-04-2025 03:22:0=
5","Site went down because of the malfunctioning of the ZTE PWC // He reset=
 the PWC","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","=
ATS-AMF Issue","Site went down because of the malfunctioning of the ZTE PWC=
 // He reset the PWC","franck.nkomot@matech-cameroun.com","733","11-04-2025=
 00:03:16","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004780389","Odz=
a Minkan IHS","","10-04-2025 23:45:11","10-04-2025 23:05:05","11-04-2025 12=
:24:33"," Site went down due to Rectifier issue // He reduced the load","Al=
bran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module"," =
Site went down due to Rectifier issue // He reduced the load","franck.nkomo=
t@matech-cameroun.com","2407","10-04-2025 23:45:11","MATECH CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004780232","O=
bobogo","","10-04-2025 23:17:35","10-04-2025 22:09:23","11-04-2025 03:10:41=
","Site impacted by CTR_773 Efoulan ont with is not manage by IHS","MINKA N=
ICOLAS","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Site impacted by CTR_773 Efoulan ont with is not manage=
 by IHS","franck.nkomot@matech-cameroun.com","4093","10-04-2025 23:17:35","=
MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004780152","B=
iteng-Maetur","","10-04-2025 22:59:23","10-04-2025 22:26:17","10-04-2025 22=
:39:17","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) // He reduced the load and manually start the Ge=
n. Alphonce (658 027 928) confirmed ","Mba Lazare Herve","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen started and stopped due to Gen overload(20kva, 280A) // He reduced th=
e load and manually start the Gen. Alphonce (658 027 928) confirmed ","fran=
ck.nkomot@matech-cameroun.com","1988","10-04-2025 22:59:23","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004780098","Eki=
e sud","","10-04-2025 22:48:05","10-04-2025 22:29:59","11-04-2025 00:13:59"=
,"Grid bad voltage, Site went down Because gen fails to start due to lack o=
f 01 phase on site // He bypassed Grid and started Gen manualy","Albran Byo=
rel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid bad voltage, Site went down Because gen fails to start due to lack=
 of 01 phase on site // He bypassed Grid and started Gen manualy","franck.n=
komot@matech-cameroun.com","1087","10-04-2025 22:48:05","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004780070","E=
foulan","","10-04-2025 22:38:20","10-04-2025 22:09:08","10-04-2025 23:09:08=
","Site impacted by CTR_773 Efoulan ont with is not manage by IHS","MINKA N=
ICOLAS","Customer Equipment Failure","Active","Active Equipment Failure","A=
ffected by 3rd Party Site","Site impacted by CTR_773 Efoulan ont with is no=
t manage by IHS","franck.nkomot@matech-cameroun.com","1753","10-04-2025 22:=
38:20","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004779737","Nko=
zoa","","10-04-2025 22:00:33","10-04-2025 21:49:17","10-04-2025 21:57:12","=
Site went down Gen failed to start due to Grid bad voltage// Grid return","=
Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Site went down Gen failed to start due to Grid bad voltage/=
/ Grid return","gaelle.njiofack@matech-cameroun.com","677","10-04-2025 22:0=
0:33","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004779672","M=
EHANDAN","","10-04-2025 21:54:42","10-04-2025 21:49:12","10-04-2025 21:54:1=
2","Site went down due to Deficiency rectifiers on site//site stabilised","=
Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to Deficiency rectifiers on site//site stabilised","gae=
lle.njiofack@matech-cameroun.com","332","10-04-2025 21:54:42","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004779620","Tou=
ring Club International","","10-04-2025 21:46:45","10-04-2025 20:43:34","11=
-04-2025 00:25:34","Grid Outage Site went down because Gen overload (20KVA,=
 270A) SS IHS Pascaline confirmed // He reduced the load and start the Gen =
Manually","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid Outage Site went down because Gen overload (20KVA, 270A) SS =
IHS Pascaline confirmed // He reduced the load and start the Gen Manually",=
"gaelle.njiofack@matech-cameroun.com","3792","10-04-2025 21:46:45","MATECH =
CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004779517","C=
rf-Nkolbisson","","10-04-2025 21:38:02","10-04-2025 21:04:47","10-04-2025 2=
1:33:12","Site went down because of CB(125A) in PWC due to load increase//H=
e reamed the CB and reduce the load","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","=
Site went down because of CB(125A) in PWC due to load increase//He reamed t=
he CB and reduce the load","gaelle.njiofack@matech-cameroun.com","1996","10=
-04-2025 21:38:02","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004779174","Beh=
ind P T school Yde","","10-04-2025 21:08:06","10-04-2025 20:46:52","10-04-2=
025 21:45:52","Grid outage, site down due to poor backup // Grid restored",=
"Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Battery Low","Grid outage, site down due to poor backup // Grid restored",=
"ludivine.ngamaleu@ihstowers.com","1275","10-04-2025 21:08:06","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004779031","E=
koumdoum OCM","","10-04-2025 20:48:32","10-04-2025 20:42:26","10-04-2025 21=
:34:11","Grid fluctuations, site down due to Gen Overload // Grid return","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid fluctuations, site down due to Gen Overload // Grid return","gaelle.nji=
ofack@matech-cameroun.com","367","10-04-2025 20:48:32","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004778886","B=
iteng-Maetur","","10-04-2025 20:31:23","10-04-2025 20:03:01","10-04-2025 21=
:15:24","Grid outage, site went down due to Gen overload // reduced load an=
d site on Gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Grid outage, site went down due to Gen overload // reduce=
d load and site on Gen","gaelle.njiofack@matech-cameroun.com","1703","10-04=
-2025 20:31:23","MATECH CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004778858","H=
-Paradis","","10-04-2025 20:24:43","10-04-2025 13:57:32","10-04-2025 17:39:=
32","Grid outage, site went down due to Gen overload // he tripped the batt=
eries","","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, site went down due to Gen overload // he tripped the batteries","oli=
vier.kwedi@ihstowers.com","23232","10-04-2025 20:24:43","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004778853","NYO=
M FACE MAETUR","","10-04-2025 20:23:20","10-04-2025 19:20:09","10-04-2025 2=
0:22:45","Grid outage, site went down because gen failed to start due to gr=
id contactor faulty // He bypassed ATS and Gen manually started","Fabrice P=
ouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid =
outage, site went down because gen failed to start due to grid contactor fa=
ulty // He bypassed ATS and Gen manually started","ludivine.ngamaleu@ihstow=
ers.com","3793","10-04-2025 20:23:20","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004778792","BAT=
A Mokolo OCM","","10-04-2025 20:09:53","10-04-2025 19:59:38","10-04-2025 20=
:21:38","Grid outage, No space to deploy a MDG // Grid restored","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy a MDG // Grid restored","ludivine.ngamaleu@ihstowers.com"=
,"617","10-04-2025 20:09:53","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004778779","C=
rf-Nkolbisson","","10-04-2025 20:07:04","10-04-2025 19:34:06","10-04-2025 2=
0:25:46","Site went down because of CB(125A) in PWC due to load increase//H=
e reamed the CB and reduce the load","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","=
Site went down because of CB(125A) in PWC due to load increase//He reamed t=
he CB and reduce the load","gaelle.njiofack@matech-cameroun.com","1979","10=
-04-2025 20:07:04","MATECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0004778541","N=
koa Ayos","","10-04-2025 19:23:25","10-04-2025 19:09:00","10-04-2025 19:40:=
19","Cascade at TTO4876312","MINKA NICOLAS","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, Site went down because Gen fa=
iled to start due to ATS dysfunction // He reset ATS and started Gen manual=
ly","gaelle.njiofack@matech-cameroun.com","276846","10-04-2025 19:23:25","M=
ATECH CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004778434","E=
leveur","","10-04-2025 19:04:55","10-04-2025 18:45:39","10-04-2025 19:36:23=
","Grid outage, Gen overload, Grid return but Grid contactor disjunct // Gr=
id Contactor rearm","Siligap Boris","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage, Gen overload, Grid return but Grid contact=
or disjunct // Grid Contactor rearm","gaelle.njiofack@matech-cameroun.com",=
"1157","10-04-2025 19:04:55","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0004778414","GSO=
","IHS_YND_067","10-04-2025 19:01:12","10-04-2025 18:53:00","10-04-2025 19:=
40:19","Grid outage, Site went down because Gen failed to start due to ATS =
dysfunction // He reset ATS and started Gen manually","MINKA NICOLAS","Equi=
pment Repair","Passive","Control Panel","ATS Relay Faulty","Grid outage, Si=
te went down because Gen failed to start due to ATS dysfunction // He reset=
 ATS and started Gen manually","ludivine.ngamaleu@ihstowers.com","493","10-=
04-2025 19:01:12","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004778365","Aha=
la Echangeur","","10-04-2025 18:54:28","10-04-2025 17:53:00","10-04-2025 19=
:01:09","site went down due to 02/03 Rectifiers disfunctionning because Gri=
d Bad Voltage // he Reseted the Rectifiers and Site is on Grid","MINKA NICO=
LAS","Equipment Repair","Passive","Rectifier","Rectifier Module","site went=
 down due to 02/03 Rectifiers disfunctionning because Grid Bad Voltage // h=
e Reseted the Rectifiers and Site is on Grid","etienne.itondo@ihstowers.com=
","3689","10-04-2025 18:54:28","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004777913","S=
IMBOCK BONAMBAPE","","10-04-2025 17:52:56","10-04-2025 12:54:46","10-04-202=
5 17:48:08","site down due to gen overload // load reduced","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","site down due =
to gen overload // load reduced","mouliom.anselme@matech-cameroun.com","178=
91","10-04-2025 17:52:56","MATECH CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004777813","Bon=
djock","","10-04-2025 17:38:39","10-04-2025 16:59:22","10-04-2025 18:50:58"=
,"Grid outage, Site went down due to Fuel shortage // Refueling done","Fand=
a Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, Sit=
e went down due to Fuel shortage // Refueling done","ludivine.ngamaleu@ihst=
owers.com","4203","10-04-2025 17:38:39","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0004777800","Djo=
nassi-Yde","","10-04-2025 17:37:20","10-04-2025 15:30:57","10-04-2025 17:31=
:50","site went down due to insufficient of rectifiers//We reset rectifier =
","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Cab=
inet","site went down due to insufficient of rectifiers//We reset rectifier=
 ","gaelle.njiofack@matech-cameroun.com","7583","10-04-2025 17:37:20","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004777791","M=
bankomo IHS","","10-04-2025 17:35:51","10-04-2025 16:28:38","10-04-2025 18:=
46:23","Site went down due to insufficient rectifiers(02/03) on site//Site =
stabilized (he added 2 rectifiers)","Fanda Brice","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to insufficient rect=
ifiers(02/03) on site//Site stabilized (he added 2 rectifiers)","gaelle.nji=
ofack@matech-cameroun.com","4034","10-04-2025 17:35:51","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004777616","NYO=
M FACE MAETUR","","10-04-2025 17:11:33","10-04-2025 16:55:13","10-04-2025 1=
7:57:05","Site down due Absence of On Eneo phase // bridge made with the re=
maining 02 phase","Fabrice Pouakam","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Incomplete Phase","Site down due Absence of On Eneo phase // =
bridge made with the remaining 02 phase","ludivine.ngamaleu@ihstowers.com",=
"981","10-04-2025 17:11:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_758","NOCINC0004777444","Nkolfoul=
ou CSD MTN","","10-04-2025 16:50:08","10-04-2025 16:38:25","10-04-2025 17:2=
8:57","Cascaded Incident from TTO4874948","Siligap Boris","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage site went down d=
ue to  Gen overload (20Kva)//Grid restored","system","285962","10-04-2025 1=
6:50:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_296","NOCINC0004777445","Nkolfoul=
ou","","10-04-2025 16:50:08","10-04-2025 16:38:25","10-04-2025 17:28:57","C=
ascaded Incident from TTO4874948","Siligap Boris","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down due to  G=
en overload (20Kva)//Grid restored","system","285962","10-04-2025 16:50:08"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0004777446","Nkolfoul=
ou Tsinga Village","","10-04-2025 16:50:08","10-04-2025 16:38:25","10-04-20=
25 17:28:57","Cascaded Incident from TTO4874948","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage site went=
 down due to  Gen overload (20Kva)//Grid restored","system","285963","10-04=
-2025 16:50:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004777443","SOA VILL=
AGE","","10-04-2025 16:50:07","10-04-2025 16:38:25","10-04-2025 23:58:25","=
 Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Julien(=
693095849) from Huawei is informed","Siligap Boris","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," Active// N=
o power issue, site is on GEN with Ubaie=3D54,4 V TX FME Julien(693095849) =
from Huawei is informed","system","702","10-04-2025 16:50:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004777442","Mvog-Eba=
nda","","10-04-2025 16:50:07","10-04-2025 16:38:25","10-04-2025 17:28:57","=
Cascaded Incident from TTO4874948","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down due to  =
Gen overload (20Kva)//Grid restored","system","285961","10-04-2025 16:50:07=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0004777441","FOUGEROL=
E","","10-04-2025 16:50:07","10-04-2025 16:38:25","10-04-2025 17:28:57","Si=
te up, awaiting feedback","Siligap Boris","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid outage site went down due to  Gen overl=
oad (20Kva)//Grid restored","system","285961","10-04-2025 16:50:07","MATECH=
 CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0004777410","Aba=
ttoir","","10-04-2025 16:47:02","10-04-2025 16:33:49","10-04-2025 17:39:42"=
,"Grid outage, Gen failed to start due to Battery Gen faulty, // Gen start =
with external battery","Fabrice Pouakam","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Generator Battery","Grid outage, Gen failed to start due to B=
attery Gen faulty, // Gen start with external battery","ludivine.ngamaleu@i=
hstowers.com","2511","10-04-2025 16:47:02","MATECH CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0004777407","Nko=
lfoulou 2","IHS_YND_561, IHS_YND_269, IHS_YND_758, IHS_YND_296, IHS_YND_759=
","10-04-2025 16:46:34","10-04-2025 16:38:25","10-04-2025 17:28:57","Grid o=
utage site went down due to  Gen overload (20Kva)//Grid restored","Siligap =
Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge site went down due to  Gen overload (20Kva)//Grid restored","gaelle.njio=
fack@matech-cameroun.com","490","10-04-2025 16:46:34","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004777398","Nko=
londom","","10-04-2025 16:44:57","10-04-2025 16:29:43","10-04-2025 18:33:51=
","Grid outage, Site went down because Gen failed to start due to ATS malfu=
nctionning// Grid return","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","ATS-AMF Issue","Grid outage, Site went down because Gen fail=
ed to start due to ATS malfunctionning// Grid return","ludivine.ngamaleu@ih=
stowers.com","8892","10-04-2025 16:44:57","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004777377","Nlo=
ngkak","","10-04-2025 16:42:44","10-04-2025 16:22:38","10-04-2025 16:40:38"=
,"site went down due to insufficient of rectifiers// Site Stabilized","Delo=
r Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","si=
te went down due to insufficient of rectifiers// Site Stabilized","gaelle.n=
jiofack@matech-cameroun.com","1207","10-04-2025 16:42:44","MATECH CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0004777136","Mae=
tur","","10-04-2025 16:11:13","10-04-2025 15:48:00","10-04-2025 16:28:43","=
Grid outage, Gen failed to start due to alarm ''short circuit'', Disjuncteu=
r Eneo HS // Gen cart reset and Gen manually start","Mboua Thierry","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen f=
ailed to start due to alarm ''short circuit'', Disjuncteur Eneo HS // Gen c=
art reset and Gen manually start","ludivine.ngamaleu@ihstowers.com","1394",=
"10-04-2025 16:11:13","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004777129","Beh=
ind P T school Yde","","10-04-2025 16:09:59","10-04-2025 15:46:40","10-04-2=
025 16:46:17","Eneo outage, site down due to poor backup","Paul BIBOUM","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","En=
eo outage, site down due to poor backup","ludivine.ngamaleu@ihstowers.com",=
"1399","10-04-2025 16:09:59","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004777117","B=
arriere IHS","","10-04-2025 16:08:33","10-04-2025 14:45:15","10-04-2025 17:=
48:43","Grid outage, site went down due to Gen overload, // Reduced load si=
te on Gen","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid outage, site went down due to Gen overload, // Reduced loa=
d site on Gen","gaelle.njiofack@matech-cameroun.com","4999","10-04-2025 16:=
08:33","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004777073","M=
efou-Assi","","10-04-2025 16:04:44","10-04-2025 14:33:52","10-04-2025 17:47=
:55","Grid outage, Site went down due to Gen overload, // Reduction of load=
","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage, Site went down due to Gen overload, // Reduction of load","gae=
lle.njiofack@matech-cameroun.com","5454","10-04-2025 16:04:44","MATECH CMR"
"Closed Complete","Site Down","T2585","IHS_YND_744","NOCINC0004776942","Ele=
veur Meec Bon Berger","","10-04-2025 15:46:43","10-04-2025 15:21:25","10-04=
-2025 17:19:48","Grid outage gen failed to start due to alarm underfrequenc=
y//Grid power return","Siligap Boris","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","DG took alarm UNDERFREQUENCY // grid return and =
fme reseted card","ludivine.ngamaleu@ihstowers.com","1518","10-04-2025 15:4=
6:43","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004776809","UPA=
C LP","","10-04-2025 15:28:17","10-04-2025 15:12:11","10-04-2025 15:46:57",=
"Grid outage, No space to deploy // grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage, No space to deplo=
y // grid return","gaelle.njiofack@matech-cameroun.com","967","10-04-2025 1=
5:28:17","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004776238","M=
endong","","10-04-2025 14:09:14","10-04-2025 13:27:51","10-04-2025 14:07:36=
"," Grid outage, site down due to DG overload (15KVA//130A) // He reduce th=
e load and started DG","Hyemafo Gildas","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","Grid outage, site down due to DG overload (15KVA//1=
30A) // He reduce the load and started DG","vanel.mbiada@matech-cameroun.co=
m","2484","10-04-2025 14:09:14","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004776192","Men=
dong3","","10-04-2025 14:01:50","10-04-2025 13:53:34","10-04-2025 17:52:34"=
,"Grid outage, no space to deploy// grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage, no space to deplo=
y// grid return","vanel.mbiada@matech-cameroun.com","497","10-04-2025 14:01=
:50","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004775780","Eto=
udi","","10-04-2025 13:12:31","10-04-2025 12:17:17","10-04-2025 13:39:07","=
site went down due to PWC dysfunctionning, // He Reset, site on Grid","Fabr=
ice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Ove=
rloaded","site went down due to PWC dysfunctionning, // He Reset, site on G=
rid","vanel.mbiada@matech-cameroun.com","3315","10-04-2025 13:12:31","MATEC=
H CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0004775441","GSO=
","","10-04-2025 12:29:15","10-04-2025 12:22:59","10-04-2025 12:54:50","Sit=
e went down because Gen failed to start due to ATS malfunction// He reset A=
TS and started Gen manually","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","ATS-AMF Issue","Site went down because Gen failed to start =
due to ATS malfunction// He reset ATS and started Gen manually","vanel.mbia=
da@matech-cameroun.com","376","10-04-2025 12:29:15","MATECH CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0004775379","E=
BOM","","10-04-2025 12:23:02","10-04-2025 11:34:52","10-04-2025 14:28:52","=
Active No power issue on site U=3D54v site on Grid Lionel//694693436 of hua=
wei is informed.","Hyemafo Gildas","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active No power issue on sit=
e U=3D54v site on Grid Lionel//694693436 of huawei is informed.","vanel.mbi=
ada@matech-cameroun.com","2891","10-04-2025 12:23:02","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004775370","M=
EFOU ASSI","","10-04-2025 12:20:35","10-04-2025 11:54:55","10-04-2025 12:47=
:28","Active // No power issue site on grid with Ubaie: 53.3V Flubert(65426=
6068) from Huawei is informed","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power=
 issue site on grid with Ubaie: 53.3V Flubert(654266068) from Huawei is inf=
ormed","vanel.mbiada@matech-cameroun.com","1541","10-04-2025 12:20:35","MAT=
ECH CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004775263","Sim=
e Building","","10-04-2025 12:08:57","10-04-2025 12:04:47","10-04-2025 12:4=
5:30","site went down due to insufficiency of rectifiers // He reset it, Ad=
ded rectifiers ongoing","Mboua Thierry","Equipment Repair","Passive","Recti=
fier","Rectifier Module","site went down due to insufficiency of rectifiers=
 // He reset it, Added rectifiers ongoing","vanel.mbiada@matech-cameroun.co=
m","251","10-04-2025 12:08:57","MATECH CMR"
"Closed Complete","Site Down","T3180","IHS_YND_253","NOCINC0004775253","Clg=
e-Advantiste","","10-04-2025 12:07:35","10-04-2025 11:59:22","10-04-2025 15=
:25:22","Grid outage, Site went down because Gen started and stopped with "=
"over voltage"" alarm// He reset Gen card and started manually","MINKA NICO=
LAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage, Site went down because Gen started and stopped with ""over voltage""=
 alarm// He reset Gen card and started manually","vanel.mbiada@matech-camer=
oun.com","494","10-04-2025 12:07:35","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004775251","Man=
guiers Dispensaire","","10-04-2025 12:07:28","10-04-2025 12:05:03","10-04-2=
025 12:15:03","Site went down because Gen failed to start due to Grid bad v=
oltage //Grid power stabilized","Fabrice Pouakam","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Site went down because Gen=
 failed to start due to Grid bad voltage //Grid power stabilized","vanel.mb=
iada@matech-cameroun.com","146","10-04-2025 12:07:28","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004775183","Aha=
la Echangeur","","10-04-2025 11:56:19","10-04-2025 11:49:09","10-04-2025 13=
:23:25","Grid outage, Gen Failed to start due to Water infiltration in the =
Tank // Tank purge and Gen start manually.","MINKA NICOLAS","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Fuel Injection Pump Calibration","Grid out=
age, Gen Failed to start due to Water infiltration in the Tank // Tank purg=
e and Gen start manually.","vanel.mbiada@matech-cameroun.com","431","10-04-=
2025 11:56:19","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004775175","Men=
dong NB","","10-04-2025 11:54:45","10-04-2025 11:37:34","11-04-2025 08:14:5=
9"," No power issue on site, Ubaie: 51.81V  Site on Grid with  The Tx Fme M=
bah hosiah(?+237 6 99 69 96 94) from Huawei is informed","","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No=
 power issue on site, Ubaie=3D51.81V  Site on Grid with  The Tx Fme Mbah ho=
siah(?+237 6 99 69 96 94) from Huawei is informed","vanel.mbiada@matech-cam=
eroun.com","1032","10-04-2025 11:54:45","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004775151","NTE=
MASSI","","10-04-2025 11:52:43","10-04-2025 11:50:38","10-04-2025 18:06:38"=
,"Grid outage, site went down because gen failed start due to gen card faul=
ty // Gen manually started","Delor Telezing","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen f=
ailed start due to gen card faulty // Gen manually started","vanel.mbiada@m=
atech-cameroun.com","126","10-04-2025 11:52:43","MATECH CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0004775134","MVA=
N","","10-04-2025 11:49:51","10-04-2025 11:45:40","10-04-2025 12:57:47","Si=
te Went Down due to Eneo fluctuation // He put site on Gen","MINKA NICOLAS"=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Site W=
ent Down due to Eneo fluctuation // He put site on Gen","vanel.mbiada@matec=
h-cameroun.com","253","10-04-2025 11:49:51","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004774931","Ron=
d Point Express1114","","10-04-2025 11:46:24","10-04-2025 11:34:17","10-04-=
2025 11:55:17","Grid outage Site went down before Gen started due to poor b=
attery backup // Gen start automatically","Hyemafo Gildas","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage Sit=
e went down before Gen started due to poor battery backup // Gen start auto=
matically","vanel.mbiada@matech-cameroun.com","728","10-04-2025 11:46:24","=
MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0004774699","Nsi=
meyong","","10-04-2025 11:12:03","10-04-2025 10:52:55","10-04-2025 12:13:29=
","Grid outage site went because Gen failed to start due automatic start bo=
ttom was not on// he started the Gen manually","MINKA NICOLAS","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went becaus=
e Gen failed to start due automatic start bottom was not on// he started th=
e Gen manually","vanel.mbiada@matech-cameroun.com","1149","10-04-2025 11:12=
:03","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004774646","Tou=
ring Club International","","10-04-2025 11:02:22","10-04-2025 10:54:56","10=
-04-2025 17:44:29","Grid outage, Site went down due to Gen overload // Grid=
 return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage, Site went down due to Gen overload // Grid return","v=
anel.mbiada@matech-cameroun.com","447","10-04-2025 11:02:22","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0004774574","O=
KOA Peage","","10-04-2025 10:52:09","10-04-2025 10:45:01","10-04-2025 13:37=
:59","Site went down due to controller PSC3 damaged due to lightning//We di=
sconnected controller PSC3 and site on grid ","Fanda Brice","Force Majeure"=
,"Natural Disaster","Thunderstrike","Equipment Damaged","Site went down due=
 to controller PSC3 damaged due to lightning//We disconnected controller PS=
C3 and site on grid ","vanel.mbiada@matech-cameroun.com","429","10-04-2025 =
10:52:09","MATECH CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0004774536","Aba=
ttoir","","10-04-2025 10:46:11","10-04-2025 10:33:26","10-04-2025 11:53:57"=
,"Grid outage site went down because Gen failed to start due to Gen battery=
 faulty //He started the gen manaully","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Generator Battery","Grid outage site went dow=
n because Gen failed to start due to Gen battery faulty //He started the ge=
n manaully","vanel.mbiada@matech-cameroun.com","766","10-04-2025 10:46:11",=
"MATECH CMR"
"Closed Complete","Site Down","T1557","IHS_YND_313","NOCINC0004774412","Afa=
noya","","10-04-2025 10:39:23","10-04-2025 10:15:15","10-04-2025 11:23:50",=
"grid outage,gen failed to start due to grid bad voltage // he bypassed the=
 Grid and site on Gen","Hyemafo Gildas","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","grid outage,gen failed to start due =
to grid bad voltage // he bypassed the Grid and site on Gen","vanel.mbiada@=
matech-cameroun.com","1450","10-04-2025 10:39:23","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004774293","SIM=
BOCK BONAMBAPE","","10-04-2025 10:15:28","10-04-2025 10:07:12","10-04-2025 =
11:39:53","Grid outage site went down due to gen failed to start //Grid ret=
urn (investigation ongoing)","Hyemafo Gildas","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage site went down due to gen fa=
iled to start //Grid return (investigation ongoing)","vanel.mbiada@matech-c=
ameroun.com","497","10-04-2025 10:15:28","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004774221","ODZ=
A MINKAN EDIBI ASSI","","10-04-2025 10:04:51","10-04-2025 09:58:20","10-04-=
2025 16:43:20","site Went down due to insufficient rectifier issue on site =
//he reset it","Albran Byorel","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","site Went down due to insufficient rectifier issue on site=
 //he reset it","vanel.mbiada@matech-cameroun.com","392","10-04-2025 10:04:=
51","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004774154","Par=
adis Hotel","","10-04-2025 09:56:11","10-04-2025 09:49:46","10-04-2025 15:1=
3:46","Grid outage, site went down  due to Gen overload //  battery reducti=
on and site on Gen","Siligap Boris","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage, site went down  due to Gen overload //  ba=
ttery reduction and site on Gen","vanel.mbiada@matech-cameroun.com","385","=
10-04-2025 09:56:11","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004774139","Odz=
a petit marche new","","10-04-2025 09:54:10","10-04-2025 09:36:55","10-04-2=
025 15:31:55","Site went down due to insufficient rectifiers on site//Site =
stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to insufficient rectifiers on site//Site s=
tabilized","vanel.mbiada@matech-cameroun.com","1036","10-04-2025 09:54:10",=
"MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004774123","Nlo=
ngkak","","10-04-2025 09:51:48","10-04-2025 09:46:16","10-04-2025 10:14:44"=
,"site went down due to insufficient of rectifiers//We reset rectifier site=
 on grid","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","site went down due to insufficient of rectifiers//We reset rec=
tifier site on grid","vanel.mbiada@matech-cameroun.com","332","10-04-2025 0=
9:51:48","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004774111","S=
atcom","","10-04-2025 09:50:00","10-04-2025 09:31:35","10-04-2025 09:35:04"=
,"ACTIVE No power issue on site U=3D 52,7V site on grid the TX fme Lionnel =
Steve / 655184876 from huawei is informed","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACT=
IVE No power issue on site U=3D 52,7V site on grid the TX fme Lionnel Steve=
 / 655184876 from huawei is informed","vanel.mbiada@matech-cameroun.com","1=
106","10-04-2025 09:50:00","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004774086","B=
arriere","","10-04-2025 09:47:15","10-04-2025 09:24:03","10-04-2025 17:58:3=
2"," Gen failed to start due to Gen overload // Reduced load and Gen start =
manually","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload"," Gen failed to start due to Gen overload // Reduced load and Gen=
 start manually","vanel.mbiada@matech-cameroun.com","1393","10-04-2025 09:4=
7:15","MATECH CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004774085","Nom=
ayos montee Meche","","10-04-2025 09:47:10","10-04-2025 09:35:02","10-04-20=
25 10:01:02","Grid outage, Site went down before Gen start due to poor back=
up/ // Gen automatically started","Fanda Brice","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup/ // Gen automatically started","vanel=
.mbiada@matech-cameroun.com","729","10-04-2025 09:47:10","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004774055","B=
ATA Mokolo OCM","","10-04-2025 09:43:51","10-04-2025 09:35:40","10-04-2025 =
09:44:43","Grid outage, No space to deploy a MDG // Grid restored","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 No space to deploy a MDG // Grid restored","vanel.mbiada@matech-cameroun.c=
om","493","10-04-2025 09:43:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0004774035","Ahala","=
","10-04-2025 09:41:27","10-04-2025 08:50:25","10-04-2025 10:17:50","Cascad=
ed Incident from TTO4870903","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage site went down due to Gen ov=
erload (17KVA, 250A) // we reduce load and gen manually started. FME IHS Fe=
lix Zambe is inform","system","277893","10-04-2025 09:41:27","MATECH CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0004773924","M=
fou OCM","","10-04-2025 09:28:25","10-04-2025 09:25:15","10-04-2025 09:30:1=
3","Active: No power issue, site is on Gen with Ubaie=3D54,2 V, the Fme TX =
lionel tchatchoua(694693436) from Huawei is informed .","Mba Lazare Herve",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active: No power issue, site is on Gen with Ubaie=3D54,2 V, the=
 Fme TX lionel tchatchoua(694693436) from Huawei is informed (Swapped by ZT=
E)","vanel.mbiada@matech-cameroun.com","191","10-04-2025 09:28:25","MATECH =
CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004773738","N=
kolondom","","10-04-2025 09:09:11","10-04-2025 09:06:03","10-04-2025 09:09:=
19","Grid outage, Site went down because Gen failed to start due to ATS mal=
functionning// Grid return","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","ATS-AMF Issue","Grid outage, Site went down because Gen fa=
iled to start due to ATS malfunctionning// Grid return","cedric.tiani@matec=
h-cameroun.com","190","10-04-2025 09:09:11","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004773685","M=
eyo","IHS_YND_257","10-04-2025 08:58:30","10-04-2025 08:50:25","10-04-2025 =
10:17:50","Grid outage site went down due to Gen overload (17KVA, 250A) // =
we reduce load and gen manually started. FME IHS Felix Zambe is inform","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage site went down due to Gen overload (17KVA, 250A) // we reduce loa=
d and gen manually started. FME IHS Felix Zambe is inform","alexandre.kamal=
@ihstowers.com","485","10-04-2025 08:58:30","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004773670","M=
bankomo IHS","","10-04-2025 08:54:18","10-04-2025 08:13:41","10-04-2025 08:=
20:34","Active no power issue on site, site on Gen with U=3D54V Tx FME FULB=
ERT /654266068/ from huawei is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active n=
o power issue on site, site on Gen with U=3D54V Tx FME FULBERT /654266068/ =
from huawei is informed","cedric.tiani@matech-cameroun.com","2438","10-04-2=
025 08:54:18","MATECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004773662","HOP=
ITAL GENERAL RAIL YDE","","10-04-2025 08:51:52","10-04-2025 08:44:41","10-0=
4-2025 10:02:53","Grid outage, Site went down because Gen overload (9kva,16=
0A) SS IHS Bernard ATANGANA confirmed// Grid return","Delor Telezing","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen overload (9kva,160A) SS IHS Bernard ATANGANA confirmed//=
 Grid return","cedric.tiani@matech-cameroun.com","431","10-04-2025 08:51:52=
","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004773659","Pha=
rmacie Bleue","","10-04-2025 08:51:27","10-04-2025 08:44:19","10-04-2025 10=
:02:24","Grid outage, Site went down because Gen started and stopped with "=
"over voltage"" alarm// He reset Gen card and started manually","Siligap Bo=
ris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage, Site went down because Gen started and stopped with ""over voltage""=
 alarm// He reset Gen card and started manually","cedric.tiani@matech-camer=
oun.com","429","10-04-2025 08:51:27","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004773651","N=
goulmekong-Nord","","10-04-2025 08:50:48","10-04-2025 08:31:27","10-04-2025=
 17:18:12","Grid outage, site went down due to GEN OVER LOARD // Grid retur=
n","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","Grid outage, site went down due to GEN OVER LOARD // Grid return","cedri=
c.tiani@matech-cameroun.com","1163","10-04-2025 08:50:48","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004773564","Ngo=
usso Vallee","","10-04-2025 08:36:09","10-04-2025 08:21:53","10-04-2025 10:=
10:53","Grid outage, Site went down because Gen started and stopped with ""=
low oil pressure"" alarm// He reset card GE and gen manually started","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage, Site went down because Gen started and stopped with ""low oil press=
ure"" alarm// He reset card GE and gen manually started","cedric.tiani@mate=
ch-cameroun.com","857","10-04-2025 08:36:09","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004773362","Odz=
a II OCM","","10-04-2025 08:00:45","10-04-2025 07:59:23","10-04-2025 09:18:=
35","Grid outage .gen gailed to start due to card GE faulty //gen manually =
started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid outage .gen gailed to start due to card GE faulty //gen =
manually started","cedric.tiani@matech-cameroun.com","84","10-04-2025 08:00=
:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0004772910","Biteng-M=
aetur","","10-04-2025 06:22:14","10-04-2025 06:14:05","10-04-2025 06:20:17"=
,"No power issue site on Grid with U=3D53.1v site on Grid Flubert(654266068=
) from Huawei is informed,","Mba Lazare Herve","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on Grid with U=3D53.1v site on Grid Flubert(654266068) from Huawei is i=
nformed,","christelle.ngonga@matech-cameroun.com","490","10-04-2025 06:22:1=
4","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004772741","Odz=
a petit marche new","","10-04-2025 05:37:47","09-04-2025 21:44:37","10-04-2=
025 07:16:06","Site went down due to insufficient rectifiers on site//Site =
stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to insufficient rectifiers on site//Site s=
tabilized","christian.fonkou@ihstowers.com","28391","10-04-2025 05:37:47","=
MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0004772440","Eto=
ug-Ebe 2","","10-04-2025 04:12:24","10-04-2025 04:00:17","10-04-2025 20:59:=
44"," site went down due to Absence of Grid phase, // bridge made between 0=
2 phase","","Grid Supply","Passive","Grid","National Grid - Grid Incomplete=
 Phase"," site went down due to Absence of Grid phase, // bridge made betwe=
en 02 phase","franck.nkomot@matech-cameroun.com","728","10-04-2025 04:12:24=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_736","NOCINC0004772164","CRF Nkoa=
bang","","10-04-2025 02:50:16","10-04-2025 02:40:08","10-04-2025 08:00:30",=
"Grid outage No space to deploy // Grid power return","Mba Lazare Herve","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge No space to deploy // Grid power return","christelle.ngonga@matech-camer=
oun.com","609","10-04-2025 02:50:16","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004772121","Nko=
zoa","","10-04-2025 02:37:04","10-04-2025 01:45:48","10-04-2025 03:14:39","=
Grid outage,Site went down due to Gen overload // Gen charge reduced and ma=
nually started","Fabrice Pouakam","Equipment Repair","Passive","DCDG Gen","=
DCDG - Overload","Grid outage,Site went down due to Gen overload // Gen cha=
rge reduced and manually started","franck.nkomot@matech-cameroun.com","9195=
","10-04-2025 02:37:04","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004772045","Ole=
mbe MTN","","10-04-2025 02:12:11","10-04-2025 01:15:02","10-04-2025 03:08:0=
2","Site went down because IPT controller dyfunction //He bypassed it and p=
ut site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Control Pan=
el","Panel Distribution Board","Site went down because IPT controller dyfun=
ction //He bypassed it and put site on Gen","christian.fonkou@ihstowers.com=
","3430","10-04-2025 02:12:11","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004771614","Tsi=
nga village","","10-04-2025 00:02:47","09-04-2025 20:30:23","10-04-2025 00:=
07:23","Site went down due to insufficiency of rectifier caused by increase=
 in load // He reduced the load, site on grid","Delor Telezing","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down due to ins=
ufficiency of rectifier caused by increase in load // He reduced the load, =
site on grid","franck.nkomot@matech-cameroun.com","12744","10-04-2025 00:02=
:47","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004771504","Nko=
londom","","09-04-2025 23:38:29","09-04-2025 22:20:13","10-04-2025 01:14:53=
","Grid outage, Site went down because Gen failed to start due to ATS malfu=
nctionning// He reset ATS and Gen manually started","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Sit=
e went down because Gen failed to start due to ATS malfunctionning// He res=
et ATS and Gen manually started
","franck.nkomot@matech-cameroun.com","19712","09-04-2025 23:38:29","MATECH=
 CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004771495","Emo=
mbo Esssomba","","09-04-2025 23:37:02","09-04-2025 23:26:49","10-04-2025 01=
:52:02","Eneo outage, site Down due to malfunction of the RCP// Gen manuall=
y started.","Mba Lazare Herve","Grid Supply","Passive","Grid","National Gri=
d - Phase Controller Faulty","Eneo outage, site Down due to malfunction of =
the RCP// Gen manually started.","franck.nkomot@matech-cameroun.com","614",=
"09-04-2025 23:37:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_275","NOCINC0004771473","Nkolbong=
","","09-04-2025 23:31:58","09-04-2025 23:01:53","09-04-2025 23:02:53","Gri=
d outage.site went down due to gen failed to start //Grid return","Delor Te=
lezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage.site went down due to gen failed to start //Grid return","joelle.e=
kessi@ihstowers.com","1806","09-04-2025 23:31:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0004771472","Nkozoa",=
"","09-04-2025 23:31:37","09-04-2025 23:00:33","09-04-2025 23:05:37","Site =
went down Gen failed to start due to Grid bad voltage// Grid return","Fabri=
ce Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Site went down Gen failed to start due to Grid bad voltage// Gri=
d return","joelle.ekessi@ihstowers.com","1865","09-04-2025 23:31:37","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_374","NOCINC0004771374","Matomb",=
"","09-04-2025 23:06:39","09-04-2025 22:22:32","10-04-2025 00:38:32","Grid =
outage site went down due to Gen GB tripped causing by lightning//Cb reamed=
","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","Grid outage site went down due to Gen GB tripped causing by lightn=
ing//Cb reamed","joelle.ekessi@ihstowers.com","2647","09-04-2025 23:06:39",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004771361","F=
ouda-New","","09-04-2025 23:05:07","09-04-2025 20:35:01","10-04-2025 04:55:=
27","Active: no power issue, site is on battery with Ubaie=3D54.3V, Armand =
Nguetsa(691144412) from Huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: no power issue, site is on battery with Ubaie=3D54.3V, Armand Nguetsa=
(691144412) from Huawei is informed","joelle.ekessi@ihstowers.com","9007","=
09-04-2025 23:05:07","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0004771296","Nko=
langaa","","09-04-2025 22:50:36","09-04-2025 22:10:31","10-04-2025 02:18:37=
","Site went down because the Cb(125A) of PWC dysfonction due to load incre=
ased // He reamed the Cb","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Circuit Breaker Tripped","Site went down because the Cb(125=
A) of PWC dysfonction due to load increased // He reamed the Cb","christian=
.fonkou@ihstowers.com","2406","09-04-2025 22:50:36","MATECH CMR"
"Closed Complete","Site Down","T0287","IHS_YND_038","NOCINC0004771181","Sia=
ntou Inferieur","","09-04-2025 22:26:14","09-04-2025 21:40:53","09-04-2025 =
22:10:53","Grid outage no space to deploy mobile gen//Grid retuirn","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
 no space to deploy mobile gen//Grid retuirn","stephane.nkamwa@ihstowers.co=
m","2722","09-04-2025 22:26:14","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004771169","Ole=
mbe MTN","","09-04-2025 22:22:34","09-04-2025 21:26:37","09-04-2025 22:51:3=
7","Site went down because IPT controller dyfunction //He bypassed it and s=
ite on Gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Site went down because IPT controller dyfunction //He by=
passed it and site on Gen","stephane.nkamwa@ihstowers.com","3358","09-04-20=
25 22:22:34","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004771108","Tou=
ring Club International","","09-04-2025 22:14:51","09-04-2025 21:50:42","09=
-04-2025 22:55:42","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed // Grid return","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went down=
 because Gen overload (20Kw, 270A) SS IHS Pascaline confirmed // Grid retur=
n","stephane.nkamwa@ihstowers.com","1450","09-04-2025 22:14:51","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004771084","Essomba"=
,"","09-04-2025 22:10:07","09-04-2025 21:45:45","10-04-2025 00:30:45","Casc=
aded Incident from TTO4867802","Mba Lazare Herve","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","site down due to TX issue Lionnel Steve=
 (655184876/Huawei) is informed","system","274761","09-04-2025 22:10:07","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_121","NOCINC0004771085","Emombo-T=
chad","","09-04-2025 22:10:07","09-04-2025 21:45:45","10-04-2025 00:30:45",=
"Cascaded Incident from TTO4867802","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","site down due to TX issue Lionnel Steve (655184876=
/Huawei) is informed","system","274761","09-04-2025 22:10:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004771078","Bitoto",=
"","09-04-2025 22:10:06","09-04-2025 21:45:45","10-04-2025 00:30:45","Casca=
ded Incident from TTO4867802","Mba Lazare Herve","Cascade Outage","Active",=
"Cascade Active","Cascade Active","site down due to TX issue Lionnel Steve =
(655184876/Huawei) is informed","system","274761","09-04-2025 22:10:06","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_267","NOCINC0004771082","Mimboman=
-Village","","09-04-2025 22:10:06","09-04-2025 21:45:45","10-04-2025 00:30:=
45","Cascaded Incident from TTO4867802","Mba Lazare Herve","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","site down due to TX issue Lion=
nel Steve (655184876/Huawei) is informed","system","274760","09-04-2025 22:=
10:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_120","NOCINC0004771080","Sapeur M=
imboman","","09-04-2025 22:10:06","09-04-2025 21:45:45","10-04-2025 00:30:4=
5","Cascaded Incident from TTO4867802","Mba Lazare Herve","Cascade Outage",=
"Active","Cascade Active","Cascade Active","site down due to TX issue Lionn=
el Steve (655184876/Huawei) is informed","system","274762","09-04-2025 22:1=
0:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004771079","Tradex-N=
komo","","09-04-2025 22:10:06","09-04-2025 21:45:45","10-04-2025 00:30:45",=
"Cascaded Incident from TTO4867802","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","site down due to TX issue Lionnel Ste=
ve (655184876/Huawei) is informed","system","274763","09-04-2025 22:10:06",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004771083","AWAE OCM=
","","09-04-2025 22:10:06","09-04-2025 21:45:45","10-04-2025 00:30:45","Cas=
caded Incident from TTO4867802","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","site down due to TX issue Lionnel Stev=
e (655184876/Huawei) is informed","system","274763","09-04-2025 22:10:06","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_093","NOCINC0004771076","Chapelle=
-Essos","","09-04-2025 22:10:05","09-04-2025 21:45:45","10-04-2025 00:30:45=
","Cascaded Incident from TTO4867802","Delor Telezing","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","site down due to TX issue Lionnel =
Steve (655184876/Huawei) is informed","system","274762","09-04-2025 22:10:0=
5","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0004771077","Kondengu=
i","","09-04-2025 22:10:05","09-04-2025 21:45:45","10-04-2025 00:30:45","Ca=
scaded Incident from TTO4867802","Albran Byorel","Cascade Outage","Active",=
"Cascade Active","Cascade Active","site down due to TX issue Lionnel Steve =
(655184876/Huawei) is informed","system","274763","09-04-2025 22:10:05","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004771024","H=
-General-Yde","","09-04-2025 22:01:27","09-04-2025 20:49:14","09-04-2025 23=
:22:14","Grid outage, Site went down because gen failed to start due to gen=
 overload(13KVA, 160A), Blaise IHS is informed // Grid return","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,=
 Site went down because gen failed to start due to gen overload(13KVA, 160A=
), Blaise IHS is informed // Grid return","rouselle.schoune@ihstowers.com",=
"4333","09-04-2025 22:01:27","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004771013","Nko=
abang Alembe","","09-04-2025 21:59:13","09-04-2025 21:12:07","10-04-2025 01=
:02:07","Grid outage, Site went down because Gen ran until fuel shortage// =
Refueling Done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage, Site went down because Gen ran until fuel shortage//=
 Refueling Done","stephane.nkamwa@ihstowers.com","2827","09-04-2025 21:59:1=
3","MATECH CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004771006","B=
iteng","IHS_YND_093, IHS_YND_114, IHS_YND_292, IHS_YND_172, IHS_YND_120, IH=
S_YND_267, IHS_YND_173, IHS_YND_179, IHS_YND_121","09-04-2025 21:58:51","09=
-04-2025 21:45:45","10-04-2025 00:30:45","Active// No power issue, site on =
Grid with Ubaie=3D52V, Lionnel Steve (655184876/Huawei) is informed","Mba L=
azare Herve","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active// No power issue, site on Grid with Ubaie=
=3D52V, Lionnel Steve (655184876/Huawei) is informed","loic.noumsi@matech-c=
ameroun.com","788","09-04-2025 21:58:51","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004770954","MEH=
ANDAN","","09-04-2025 21:50:47","09-04-2025 20:38:20","10-04-2025 03:08:20"=
,"Site went down due to insufficient rectifiers on site//site stabilised","=
Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to insufficient rectifiers on site//site stabilised","s=
tephane.nkamwa@ihstowers.com","4349","09-04-2025 21:50:47","MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004770946","Mes=
sassi okolo","","09-04-2025 21:50:00","09-04-2025 20:33:07","09-04-2025 22:=
13:07","Grid outage, Site down because , Gen failed to start due to Faulty =
cable of start order and burn charger static // Gen start manually","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, Gen failed to start due to Faulty cable of start order and bur=
n charger static // Gen start manually","stephane.nkamwa@ihstowers.com","46=
15","09-04-2025 21:50:00","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004770923","Ngo=
usso Vallee","","09-04-2025 21:47:14","09-04-2025 20:29:09","09-04-2025 21:=
12:36","Eneo outage, GEN ran and stopped due to  false oil pressure alarm  =
Grid return, Card reseted ","Siligap Boris","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Eneo outage, GEN ran and stopped due to  f=
alse oil pressure alarm  Grid return, Card reseted ","stephane.nkamwa@ihsto=
wers.com","6456","09-04-2025 21:47:14","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004770866","C=
rf-Nkolbisson","","09-04-2025 21:41:45","09-04-2025 21:04:38","09-04-2025 2=
1:46:38","site went down because the CB(125A)which feeds OCM equipment trip=
ped// CB rearmed","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","=
Control Panel","Circuit Breaker Tripped","site went down because the CB(125=
A)which feeds OCM equipment tripped// CB rearmed","loic.noumsi@matech-camer=
oun.com","2228","09-04-2025 21:41:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_801","NOCINC0004770859","HOPITAL =
GENERAL RAIL YDE","","09-04-2025 21:40:18","09-04-2025 20:51:59","09-04-202=
5 21:15:02","Cascaded Incident from TTO4867260","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage site went=
 down because Gen failed to start due to no automanism on site // Gen manua=
lly started","system","292374","09-04-2025 21:40:18","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004770709","E=
koumdoum OCM","","09-04-2025 21:21:09","09-04-2025 20:31:31","09-04-2025 21=
:36:31","Grid outage, Site went down because Gen overload (20kva, 300A) SS =
IHS alphonse confirmed// Grid return","Albran Byorel","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because G=
en overload (20kva, 300A) SS IHS alphonse confirmed// Grid return","gaelle.=
njiofack@matech-cameroun.com","2980","09-04-2025 21:21:09","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004770678","M=
essassi 2","","09-04-2025 21:17:03","09-04-2025 21:01:43","09-04-2025 23:12=
:43","Grid outage, site went down because gen start and stopped due to high=
 temp // He added water and manually start the gen","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, site went =
down because gen start and stopped due to high temp // He added water and m=
anually start the gen","loic.noumsi@matech-cameroun.com","921","09-04-2025 =
21:17:03","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004770645","NYO=
M FACE MAETUR","","09-04-2025 21:12:30","09-04-2025 20:29:06","10-04-2025 0=
0:28:06","Grid outage, Site went down because Gen failed to start due Gen c=
ard Faulty// Grid Restored","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen faile=
d to start due Gen card Faulty// Grid Restored","loic.noumsi@matech-camerou=
n.com","2606","09-04-2025 21:12:30","MATECH CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004770629","M=
balla 4","","09-04-2025 21:10:25","09-04-2025 20:28:37","09-04-2025 21:14:3=
7","Grid outage gen failed to start due to high temp alarm//We add water an=
d gen manually started","Delor Telezing","Equipment Repair","Passive","ACDG=
 Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage gen fail=
ed to start due to high temp alarm//We add water and gen manually started
","loic.noumsi@matech-cameroun.com","2509","09-04-2025 21:10:25","MATECH CM=
R"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004770584","Pha=
rmacie Bleue","IHS_YND_801","09-04-2025 21:05:19","09-04-2025 20:51:59","09=
-04-2025 21:15:02","Grid outage site went down because Gen failed to start =
due to no automanism on site // Gen manually started","Siligap Boris","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site=
 went down because Gen failed to start due to no automanism on site // Gen =
manually started","loic.noumsi@matech-cameroun.com","801","09-04-2025 21:05=
:19","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004770552","Par=
adis Hotel","","09-04-2025 21:00:27","09-04-2025 20:22:32","09-04-2025 21:0=
9:56","gen took alarm UNDERFREQUENCY // FME reset card","Siligap Boris","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","gen took alarm=
 UNDERFREQUENCY // FME reset card","loic.noumsi@matech-cameroun.com","2276"=
,"09-04-2025 21:00:27","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004770502","N=
goulmekong-Nord","","09-04-2025 20:52:08","09-04-2025 20:19:56","09-04-2025=
 21:13:56","Grid outage, site went down due to Gen overload(12.5kva,210 A) =
IHS SS Blaise Raoul is informed and confirmed//Grid return","Siligap Boris"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, si=
te went down due to Gen overload(12.5kva,210 A) IHS SS Blaise Raoul is info=
rmed and confirmed//Grid return","loic.noumsi@matech-cameroun.com","1933","=
09-04-2025 20:52:08","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004770412","Tou=
ring Club International","","09-04-2025 20:37:53","09-04-2025 20:31:37","09=
-04-2025 20:59:32"," site down due to bad eneo voltage // Grid stopped manu=
ally and Gen Start","Albran Byorel","Grid Supply","Passive","Grid","Nationa=
l Grid - Unstable Grid Supply Issue"," site down due to bad eneo voltage //=
 Grid stopped manually and Gen Start","loic.noumsi@matech-cameroun.com","37=
7","09-04-2025 20:37:53","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004770396","E=
mana lycee 2","","09-04-2025 20:35:24","09-04-2025 20:23:42","09-04-2025 23=
:03:38","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and Gen started manually","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, site went down because gen start and stopped wit=
h high temp alarm // He added water and Gen started manually","loic.noumsi@=
matech-cameroun.com","704","09-04-2025 20:35:24","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004770379","E=
kombitie","","09-04-2025 20:32:44","09-04-2025 20:20:38","09-04-2025 21:14:=
38","No power issue site on gen with U=3D54.36V site on Gen THE TX Synphori=
en 691316854 of Huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue site on gen with U=3D54.36V site on Gen THE TX Synphorien 691316854 o=
f Huawei is informed","loic.noumsi@matech-cameroun.com","728","09-04-2025 2=
0:32:44","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004770353","B=
iteng-Maetur","","09-04-2025 20:28:39","09-04-2025 20:21:27","10-04-2025 02=
:54:27","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) // He reduced the load and manually start the Ge=
n","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Grid outage, Site went down because Gen started and stopped due to Ge=
n overload(20kva, 280A) // He reduced the load and manually start the Gen",=
"loic.noumsi@matech-cameroun.com","433","09-04-2025 20:28:39","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004770031","NTU=
I TOWN","","09-04-2025 19:56:08","09-04-2025 19:30:59","09-04-2025 21:45:59=
","Grid outage gen ran until fuel shortage//Refueling done","Parker Tchoup"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran unti=
l fuel shortage//Refueling done","gaelle.njiofack@matech-cameroun.com","151=
0","09-04-2025 19:56:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0004769665","Nkol-Meb=
anga","","09-04-2025 18:58:57","09-04-2025 18:42:29","09-04-2025 19:48:29",=
"Cascaded Incident from TTO4866313","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work made by=
 IHS SS Francois Ndoungou(654915716) is working on site(replacement battery=
 backup)   // End of work","system","314445","09-04-2025 18:58:57","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004769666","Saa","",=
"09-04-2025 18:58:57","09-04-2025 18:42:29","09-04-2025 19:48:29","Cascaded=
 Incident from TTO4866313","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to work made by IHS SS F=
rancois Ndoungou(654915716) is working on site(replacement battery backup) =
  // End of work","system","314446","09-04-2025 18:58:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004769664","SAA Entr=
ance","","09-04-2025 18:58:56","09-04-2025 18:42:29","09-04-2025 19:48:29",=
"Cascaded Incident from TTO4866313","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work made by=
 IHS SS Francois Ndoungou(654915716) is working on site(replacement battery=
 backup)   // End of work","system","314445","09-04-2025 18:58:56","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004769663","Carrefou=
r Ayissi Ele","","09-04-2025 18:58:56","09-04-2025 18:42:29","09-04-2025 19=
:48:29","Cascaded Incident from TTO4866313","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down due to work=
 made by IHS SS Francois Ndoungou(654915716) is working on site(replacement=
 battery backup)   // End of work","system","314446","09-04-2025 18:58:56",=
"MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004769658","SAA=
 2","IHS_YND_810, IHS_YND_542, IHS_YND_809, IHS_YND_405","09-04-2025 18:56:=
53","09-04-2025 18:42:29","09-04-2025 19:48:29","Site went down due to work=
 made by IHS SS Francois Ndoungou(654915716) is working on site(replacement=
 battery backup)   // End of work","Parker Tchoup","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Site went down due to=
 work made by IHS SS Francois Ndoungou(654915716) is working on site(replac=
ement battery backup)   // End of work","stephane.nkamwa@ihstowers.com","86=
5","09-04-2025 18:56:53","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004769356","S=
imbock OCM","","09-04-2025 18:25:45","09-04-2025 18:21:34","09-04-2025 19:1=
8:54","site down due to rectifier issue // rectifier added","Hyemafo Gildas=
","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","site down d=
ue to rectifier issue // rectifier added","gaelle.njiofack@matech-cameroun.=
com","252","09-04-2025 18:25:45","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004769261","M=
ANGUIERS CHAPELLE","","09-04-2025 18:11:40","09-04-2025 17:54:18","09-04-20=
25 18:05:51","Grid outage,site down due to over voltage // one battery fuse=
 removed to reduce load.","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","ACDG - Over Voltage","Grid outage,site down due to over voltage /=
/ one battery fuse removed to reduce load.","gaelle.njiofack@matech-camerou=
n.com","1043","09-04-2025 18:11:40","MATECH CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004769245","MBA=
LNGONG LYCEE","","09-04-2025 18:08:43","09-04-2025 17:24:11","09-04-2025 22=
:36:11","Grid Outage Site went down due to Gen overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went d=
own due to Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and conf=
irmed // Grid return","stephane.nkamwa@ihstowers.com","2673","09-04-2025 18=
:08:43","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004769178","N=
kozoa","","09-04-2025 18:00:23","09-04-2025 17:45:09","09-04-2025 21:15:22"=
,"Boris Was on site for Work // End of work","Fabrice Pouakam","Installatio=
n Activity","Passive","Planned Activity","Installation Activity","Boris Was=
 on site for Work // End of work","gaelle.njiofack@matech-cameroun.com","91=
6","09-04-2025 18:00:23","MATECH CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0004769146","M=
anguier","","09-04-2025 17:55:07","09-04-2025 17:39:52","09-04-2025 18:14:5=
2"," Grid fluctuation ,site went down due to grid bad voltage ,no rcp on si=
te//He bypassed the grid and site on Gen","Fabrice Pouakam","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty"," Grid fluctuatio=
n ,site went down due to grid bad voltage ,no rcp on site//He bypassed the =
grid and site on Gen","gaelle.njiofack@matech-cameroun.com","916","09-04-20=
25 17:55:07","MATECH CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004768855","Nsi=
meyong Shell","","09-04-2025 17:18:01","09-04-2025 15:47:15","10-04-2025 07=
:03:41","ACCESS ISSUES during the night Site went down due to cable which p=
owered PWC has burnt//Wre replace the cable and site on gen","MINKA NICOLAS=
","Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue =
- Land Lord","ACCESS ISSUES during the night Site went down due to cable wh=
ich powered PWC has burnt//Wre replace the cable and site on gen","stephane=
.nkamwa@ihstowers.com","5447","09-04-2025 17:18:01","MATECH CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0004768840","Ema=
na Lycee","","09-04-2025 17:16:11","09-04-2025 16:55:59","09-04-2025 17:49:=
51","No power issue site on grid with U=3D54v Symphorien(691316854) from Hu=
awei is informed, site up without intervention.","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue site on grid with U=3D54v Symphorien(691316854) from Hua=
wei is informed, site up at 03:56 PM,

","loic.noumsi@matech-cameroun.com","1213","09-04-2025 17:16:11","MATECH CM=
R"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004768809","Ako=
k Ndoe Yde","","09-04-2025 17:12:43","09-04-2025 16:58:26","09-04-2025 18:1=
3:15","Grid outage, site down before Gen start due to Poor battery Backp //=
 Gen start","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, site down before Gen start due t=
o Poor battery Backp // Gen start","gaelle.njiofack@matech-cameroun.com","8=
58","09-04-2025 17:12:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004768426","Mom","",=
"09-04-2025 16:53:09","09-04-2025 16:47:18","09-04-2025 16:54:14","Cascaded=
 Incident from TTO4865117","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Site impacted by Ngoumou","system","263836","=
09-04-2025 16:53:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004768423","OLAMA","=
","09-04-2025 16:53:08","09-04-2025 16:47:18","09-04-2025 16:54:14","Cascad=
ed Incident from TTO4865117","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site impacted by Ngoumou","system","263835"=
,"09-04-2025 16:53:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004768425","Minka","=
","09-04-2025 16:53:08","09-04-2025 16:47:18","09-04-2025 16:54:14","Cascad=
ed Incident from TTO4865117","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site impacted by Ngoumou","system","263836"=
,"09-04-2025 16:53:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004768424","OTELE MT=
N","","09-04-2025 16:53:08","09-04-2025 16:47:18","09-04-2025 16:54:14","Ca=
scaded Incident from TTO4865117","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site impacted by Ngoumou","system","263=
837","09-04-2025 16:53:08","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004768352","Ako=
no","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_370","09-04-2025 16:49:=
36","09-04-2025 16:47:18","09-04-2025 16:54:14","Site impacted by Ngoumou (=
 not under our responsability )","Fanda Brice","3RD Party Power Failure","P=
assive","Power Provided By 3RD Party","Power Provided By 3RD Party","Site i=
mpacted by Ngoumou","gaelle.njiofack@matech-cameroun.com","139","09-04-2025=
 16:49:36","MATECH CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0004768325","BIY=
EM ASSI LYCEE","","09-04-2025 16:40:03","09-04-2025 16:06:48","09-04-2025 1=
7:02:48","Grid outage,site went down because Gen failed to start (investiga=
tion )","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid outage,site went down because Gen failed to start (inves=
tigation )","gaelle.njiofack@matech-cameroun.com","1996","09-04-2025 16:40:=
03","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004768217","Par=
adis Hotel","","09-04-2025 16:33:00","09-04-2025 16:27:47","09-04-2025 17:3=
9:27","Site went down due to(1/2) rectifiers dysfunctionned//We reset recti=
fier and site on grid ","Siligap Boris","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down due to(1/2) rectifiers dysfunction=
ned//We reset rectifier and site on grid ","gaelle.njiofack@matech-cameroun=
.com","313","09-04-2025 16:33:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004768181","Scalom-I=
HS","","09-04-2025 16:25:49","09-04-2025 16:05:11","09-04-2025 16:40:11","C=
ascaded Incident from TTO4864906","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Site went down due to insufficiency of rectifiers=
, Francois IHS is informed // He reduced the load","system","323904","09-04=
-2025 16:25:49","MATECH CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004768174","S=
calom","IHS_YND_505","09-04-2025 16:25:00","09-04-2025 16:05:11","09-04-202=
5 16:40:11","Site went down due to insufficiency of rectifiers, Francois IH=
S is informed // He reduced the load","Paul BIBOUM","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Site went down due to insufficiency o=
f rectifiers, Francois IHS is informed // He reduced the load","loic.noumsi=
@matech-cameroun.com","1190","09-04-2025 16:25:00","MATECH CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004768121","S=
hell-Nsimeyong","","09-04-2025 16:14:36","09-04-2025 16:05:14","09-04-2025 =
16:40:14","Grid outage, site went down because the generator cable damaged =
//he connect another cable to rescue the site","MINKA NICOLAS","Equipment R=
epair","Passive","Infrastructure","Armoured Cable","Grid outage, site went =
down because the generator cable damaged //he connect another cable to resc=
ue the site","loic.noumsi@matech-cameroun.com","564","09-04-2025 16:14:36",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0004768077","K=
amajou Building","IHS_YND_085","09-04-2025 16:08:37","09-04-2025 15:47:07",=
"09-04-2025 16:47:40","site down due to disjunction of  a CB (80A) in the p=
wc // rearmed circuit breaker","Paul BIBOUM","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","site down due to di=
sjunction of  a CB (80A) in the pwc // rearmed circuit breaker","loic.noums=
i@matech-cameroun.com","1291","09-04-2025 16:08:37","MATECH CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004768048","Lab=
oratoire  Meka","","09-04-2025 16:05:33","09-04-2025 15:39:05","09-04-2025 =
16:53:49","Grid Outage, No space to deploy // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No spac=
e to deploy // Grid return","stephane.nkamwa@ihstowers.com","1589","09-04-2=
025 16:05:33","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004767963","B=
riqueterie","","09-04-2025 15:56:23","09-04-2025 15:47:07","09-04-2025 16:4=
7:40","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"site down due to disjunction of  a CB (80A) in the pwc (Supervisor IHS is =
already informed) // rearmed circuit breaker","loic.noumsi@matech-cameroun.=
com","267211","09-04-2025 15:56:23","MATECH CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0004767894","H=
-Progres","","09-04-2025 15:42:26","09-04-2025 15:24:18","09-04-2025 16:44:=
37","Grid outage no space to deploy mobile gen//Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spa=
ce to deploy mobile gen//Grid return","gaelle.njiofack@matech-cameroun.com"=
,"1089","09-04-2025 15:42:26","MATECH CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004767849","Efo=
ulan MTN","","09-04-2025 15:35:14","09-04-2025 14:22:57","09-04-2025 17:56:=
36","Gen stopped due to Alarm low oil pressure // Reset and start gen, grid=
 return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Gen stopped due to Alarm low oil pressure // Reset and start =
gen, grid return","stephane.nkamwa@ihstowers.com","4338","09-04-2025 15:35:=
14","MATECH CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0004767846","Nko=
mkana","","09-04-2025 15:34:39","09-04-2025 14:26:08","09-04-2025 22:12:08"=
,"Grid outage, No space to deploy MDG// Grid return","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage, No space to d=
eploy MDG// Grid return","stephane.nkamwa@ihstowers.com","4112","09-04-2025=
 15:34:39","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004767819","C=
amp-Sic-Tsinga","","09-04-2025 15:32:07","09-04-2025 15:29:56","09-04-2025 =
17:11:11","Grid outage no space to deploy mobile gen//Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
no space to deploy mobile gen//Grid return","gaelle.njiofack@matech-camerou=
n.com","132","09-04-2025 15:32:07","MATECH CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004767786","Tsi=
nga village","","09-04-2025 15:28:02","09-04-2025 14:48:44","09-04-2025 15:=
42:50","Site went down due to insufficiency of rectifier caused by increase=
 in load // He reduced the load, site on grid","Delor Telezing","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down due to ins=
ufficiency of rectifier caused by increase in load // He reduced the load, =
site on grid","stephane.nkamwa@ihstowers.com","2359","09-04-2025 15:28:02",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004767773","c=
hina embassy yde","","09-04-2025 15:24:27","09-04-2025 15:04:21","09-04-202=
5 16:49:18","Grid outage no space to deploy mobile gen//Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e no space to deploy mobile gen//Grid return","rouselle.schoune@ihstowers.c=
om","1207","09-04-2025 15:24:27","MATECH CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0004767757","I=
mm-Olympique","","09-04-2025 15:22:18","09-04-2025 15:03:14","09-04-2025 15=
:46:45","site went down due to tripped CB(125A) in the power cabinet  //we =
rearmed CB  ","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Recti=
fier Cabinet","site went down due to tripped CB(125A) in the power cabinet =
 //we rearmed CB ","rouselle.schoune@ihstowers.com","1145","09-04-2025 15:2=
2:18","MATECH CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004767753","N=
komkana 2","","09-04-2025 15:21:24","09-04-2025 14:24:14","09-04-2025 16:30=
:14","Site went down because it was impacted by madagascar which is a Grid =
only","Mboua Thierry","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","Site went down because it was impacted by=
 madagascar which is a Grid only","rouselle.schoune@ihstowers.com","3431","=
09-04-2025 15:21:24","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004767719","Bastos B=
ethesda","","09-04-2025 15:16:11","09-04-2025 14:24:41","09-04-2025 14:28:1=
2","Cascaded Incident from TTO4864319","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue site on gen  with U=
=3D54v Mohamadou Eloundou Bertrand from Huaei is informed from Huawei is in=
formed","system","272128","09-04-2025 15:16:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004767718","Golf Qua=
ter","","09-04-2025 15:16:11","09-04-2025 14:24:41","09-04-2025 14:28:12","=
Cascaded Incident from TTO4864319","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue site on gen  with U=3D5=
4v Mohamadou Eloundou Bertrand from Huaei is informed from Huawei is inform=
ed","system","272128","09-04-2025 15:16:11","MATECH CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004767697","B=
astos-Nylon","IHS_YND_220, IHS_YND_563, IHS_YND_127","09-04-2025 15:12:19",=
"09-04-2025 14:24:41","09-04-2025 17:30:41","No power issue site on gen  wi=
th U=3D54v Mohamadou Eloundou Bertrand from Huaei is informed from Huawei i=
s informed","Mboua Thierry","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on gen  with U=
=3D54v Mohamadou Eloundou Bertrand from Huaei is informed from Huawei is in=
formed","vanel.mbiada@matech-cameroun.com","2859","09-04-2025 15:12:19","MA=
TECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004767032","Jou=
vence Mbenda","","09-04-2025 14:18:27","09-04-2025 14:12:44","09-04-2025 14=
:28:26","site down due to Grid fluctuation // site put on gen","Hyemafo Gil=
das","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply I=
ssue","site down due to Grid fluctuation // site put on gen","vanel.mbiada@=
matech-cameroun.com","344","09-04-2025 14:18:27","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004767031","A=
ccacia New","","09-04-2025 14:18:07","09-04-2025 13:11:50","09-04-2025 21:4=
8:50","Grid Only, No space to deploy // Grid return","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid Only, No space to dep=
loy // Grid return","olivier.kwedi@ihstowers.com","3978","09-04-2025 14:18:=
07","MATECH CMR"
"Closed Complete","Site Down","T0287","IHS_YND_038","NOCINC0004767015","Sia=
ntou Inferieur","","09-04-2025 14:14:53","09-04-2025 14:11:14","09-04-2025 =
16:47:20","Grid outage no space to deploy mobile gen//Grid retuirn","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
 no space to deploy mobile gen//Grid retuirn","vanel.mbiada@matech-cameroun=
.com","220","09-04-2025 14:14:53","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004766851","A=
kak-Nkozoa-MTN-IHS","","09-04-2025 13:50:38","09-04-2025 13:21:07","09-04-2=
025 21:41:07","Site went went down because Fme was replacing the Generator =
housing Gasket","Fabrice Pouakam","Installation Activity","Passive","Planne=
d Activity","Installation Activity","Site went went down because Fme was re=
placing the Generator housing Gasket","cedric.tiani@matech-cameroun.com","1=
773","09-04-2025 13:50:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_152","NOCINC0004766845","Rd-Pt-Ex=
press","","09-04-2025 13:49:55","09-04-2025 13:14:15","09-04-2025 21:48:15"=
,"Grid only, Site wen Down due to Eneo Outage (no space to deployed MGE) //=
 Grid returned","","Grid Supply","Passive","Grid","National Grid - Grid Out=
age Issue","Grid only, Site wen Down due to Eneo Outage (no space to deploy=
ed MGE) // Grid returned","system","2140","09-04-2025 13:49:55","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0004766846","Tamtam W=
eekend","","09-04-2025 13:49:55","09-04-2025 13:14:15","09-04-2025 21:48:15=
","Active//No power issue site on Grid with U=3D54.8V The TX FME Mbah Hosia=
h (674007438) FROM Huawei is informed.","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue site on Grid with U=3D54.8V The TX FME Mbah Hosiah (674007=
438) FROM Huawei is informed.","system","2140","09-04-2025 13:49:55","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0004766847","Montee-J=
ouvence-II","","09-04-2025 13:49:55","09-04-2025 13:14:15","09-04-2025 21:4=
8:15","Grid outage, Site went down because Gen overload (15kva, 250A) SS IH=
S Felix Zambe is informed // GRid power return","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went dow=
n because Gen overload (15kva, 250A) SS IHS Felix Zambe is informed // GRid=
 power return","system","2140","09-04-2025 13:49:55","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004766831","D=
amas","","09-04-2025 13:48:22","09-04-2025 13:14:15","09-04-2025 21:49:15",=
"Active//No power issue on site ,site on Grid with Ubaie=3D54.6 V he FME Th=
e TX FME Mbah Hosiah (674007438) is informed","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site ,site on Grid with Ubaie=3D54.6 V he FME The =
TX FME Mbah Hosiah (674007438) is informed","cedric.tiani@matech-cameroun.c=
om","2048","09-04-2025 13:48:22","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004766800","B=
iyemassi LAC","","09-04-2025 13:46:07","09-04-2025 13:01:43","09-04-2025 21=
:49:43","Grid outage, no space to deploy a mobile Gen// Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e, no space to deploy a mobile Gen// Grid return","vanel.mbiada@matech-came=
roun.com","2666","09-04-2025 13:46:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004766791","MEHANDAN=
","","09-04-2025 13:45:18","09-04-2025 10:59:38","09-04-2025 11:55:32","Cas=
caded Incident from TTO4863510","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage gen failed to start due to=
 card GE dysfunctionned//We reset card GE and gen manually started","system=
","291999","09-04-2025 13:45:18","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004766707","ETO=
UDI Entree du palais","","09-04-2025 13:35:03","09-04-2025 13:32:44","09-04=
-2025 13:41:45","Grid outage, Site went down before Gen start due to poor b=
ackup // Gen started manually","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Gen started manually","cedric.tia=
ni@matech-cameroun.com","140","09-04-2025 13:35:03","MATECH CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0004766607","Men=
dong Maeture","","09-04-2025 13:28:41","09-04-2025 13:00:22","09-04-2025 14=
:51:37","site went down because gen failed to start due to grid bad voltage=
 // He bypassed the Grid and site on Grid","Hyemafo Gildas","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","site went down b=
ecause gen failed to start due to grid bad voltage // He bypassed the Grid =
and site on Grid","vanel.mbiada@matech-cameroun.com","1700","09-04-2025 13:=
28:41","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004766536","M=
efou-Assi","","09-04-2025 13:17:34","09-04-2025 12:39:25","09-04-2025 13:53=
:52","Grid outage, site went down because gen failed to start due to gen ov=
erload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // Grid return","Fanda B=
rice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outag=
e, site went down because gen fails to start due to gen overload(15Kva, 200=
A) SS IHS FELIX ZAMBE is informed // Grid return","olivier.kwedi@ihstowers.=
com","2290","09-04-2025 13:17:34","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004766463","O=
dza","","09-04-2025 13:06:23","09-04-2025 12:35:12","09-04-2025 15:27:26","=
Grid outage, site went down because gen failed to start due to hybrid syste=
m malfunction // Gen manually started","Albran Byorel","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down becau=
se gen failed to start due to hybrid system malfunction // Gen manually sta=
rted","olivier.kwedi@ihstowers.com","1872","09-04-2025 13:06:23","MATECH CM=
R"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0004766454","Tsi=
nga","","09-04-2025 13:05:45","09-04-2025 12:05:11","09-04-2025 14:28:12","=
Grid outage.gen ran until fuel shortage//Refueling done","Mboua Thierry","F=
uel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until f=
uel shortage//Refueling done","vanel.mbiada@matech-cameroun.com","3635","09=
-04-2025 13:05:45","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004766401","Fla=
menco","","09-04-2025 13:00:40","09-04-2025 12:52:20","09-04-2025 14:32:14"=
,"Grid outage site went down because Gen failed to start due to Gen card fa=
ulty // Gen manually started","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen f=
ailed to start due to Gen card faulty // Gen manually started","vanel.mbiad=
a@matech-cameroun.com","501","09-04-2025 13:00:40","MATECH CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004766390","NKO=
LMEKONG YDE","","09-04-2025 12:58:43","09-04-2025 12:51:35","10-04-2025 16:=
54:44","PWC damaged and need replacement (site still down) // PWC reset","F=
abrice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabinet=
 - Battery Low","PWC damaged and need replacement (site still down) // PWC =
reset","cedric.tiani@matech-cameroun.com","429","09-04-2025 12:58:43","MATE=
CH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0004766384","Clu=
b France","","09-04-2025 12:57:31","09-04-2025 12:52:37","09-04-2025 15:52:=
21","Grid only, no space to deployed MDG // Grid returned","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid only, no space =
to deployed MDG // Grid returned","cedric.tiani@matech-cameroun.com","295",=
"09-04-2025 12:57:31","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004766324","B=
ATA Mokolo OCM","","09-04-2025 12:53:33","09-04-2025 12:21:11","09-04-2025 =
16:32:27","Grid outage no space to deploy mobile gen//Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
no space to deploy mobile gen//Grid return","cedric.tiani@matech-cameroun.c=
om","1943","09-04-2025 12:53:33","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004766303","Nko=
l-Mbanda","","09-04-2025 12:48:06","09-04-2025 12:42:56","09-04-2025 15:26:=
56","No power issue site on grid with U=3D54v site up at 03:26 PM Mbah Osia=
h from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on grid with U=3D54v site up at 03:26 PM Mbah Osiah from Huawei is informed=
","cedric.tiani@matech-cameroun.com","311","09-04-2025 12:48:06","MATECH CM=
R"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004765937","Efo=
ulan MTN","","09-04-2025 12:16:19","09-04-2025 11:46:01","09-04-2025 12:56:=
46","Grid outage, Site went down because Gen failed to start due to Kick st=
arter faulty// He started Gen manualy with external Kick started","MINKA NI=
COLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid =
outage, Site went down because Gen failed to start due to Kick starter faul=
ty// He started Gen manualy with external Kick started","vanel.mbiada@matec=
h-cameroun.com","1819","09-04-2025 12:16:19","MATECH CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004765813","M=
imboman-Village","","09-04-2025 12:01:56","09-04-2025 10:25:52","09-04-2025=
 10:30:19","no power issue on site ,site on Grid with U=3D54.6V The TX FME =
Eloundou Bertrand/ 693212405 of huawei is informed. ","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","no power issue on site ,site on Grid with U=3D54.6V The TX FME El=
oundou Bertrand/ 693212405 of huawei is informed. ","cedric.tiani@matech-ca=
meroun.com","5766","09-04-2025 12:01:56","MATECH CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0004765789","Hot=
el de Ville Yde","","09-04-2025 11:57:45","09-04-2025 11:51:23","09-04-2025=
 12:53:04","Site went down due to CB(125A)in PWC that tripped affecting MTN=
//He rearmed the CB","Paul BIBOUM","Equipment Repair","Passive","Control Pa=
nel","Circuit Breaker Tripped","Site went down due to CB(125A)in PWC that t=
ripped affecting MTN//He rearmed the CB","vanel.mbiada@matech-cameroun.com"=
,"383","09-04-2025 11:57:45","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004765768","B=
iteng-Maetur","","09-04-2025 11:53:58","09-04-2025 09:31:09","09-04-2025 10=
:00:58","No power issue site on Grid with U=3D54v Flubert(654266068) from H=
uawei is informed,","Mba Lazare Herve","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on G=
rid with U=3D54v Flubert(654266068) from Huawei is informed,","cedric.tiani=
@matech-cameroun.com","8571","09-04-2025 11:53:58","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004765550","E=
koumdoum","","09-04-2025 11:21:33","09-04-2025 10:33:48","09-04-2025 12:35:=
19","Grid Outage, site went down because Gen start and stopped with ""high =
temp"" alarm due to accordion cut // He oppened the doors and manually star=
t the gen","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Exhaust","Grid Outage, site went down because Gen start and stopped with ""=
high temp"" alarm due to accordion cut // He oppened the doors and manually=
 start the gen","vanel.mbiada@matech-cameroun.com","2866","09-04-2025 11:21=
:33","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004765367","M=
bankomo IHS","","09-04-2025 11:16:09","09-04-2025 10:50:58","09-04-2025 11:=
15:22","Grid outage gen failed to start due to its  malfunctioning card// C=
ard reset done and gen manually started","Fanda Brice","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to start=
 due to its  malfunctioning card// Card reset done and gen manually started=
","cedric.tiani@matech-cameroun.com","1512","09-04-2025 11:16:09","MATECH C=
MR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004765308","Odz=
a petit marche new","","09-04-2025 11:07:09","09-04-2025 10:59:30","09-04-2=
025 12:29:25","Site went down due to insufficient rectifiers on site//Site =
stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to insufficient rectifiers on site//Site s=
tabilized","vanel.mbiada@matech-cameroun.com","460","09-04-2025 11:07:09","=
MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004765306","Odz=
a II OCM","IHS_YND_528","09-04-2025 11:06:49","09-04-2025 10:59:38","09-04-=
2025 12:02:55","Grid outage gen failed to start due to card GE dysfunctionn=
ed // We reset card GE and gen manually started","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen faile=
d to start due to card GE dysfunctionned//We reset card GE and gen manually=
 started","cedric.tiani@matech-cameroun.com","432","09-04-2025 11:06:49","M=
ATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004765278","Beh=
ind P T school Yde","","09-04-2025 11:04:28","09-04-2025 10:57:13","09-04-2=
025 12:41:47","Grid outage site went down due to no automatism on site caus=
ed by faulty Gen card  //Gen manually started","Paul BIBOUM","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went dow=
n due to no automatisme on site due to Gen card faulty //Gen manually start=
ed","cedric.tiani@matech-cameroun.com","436","09-04-2025 11:04:28","MATECH =
CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004765230","Nko=
abang MTN","","09-04-2025 10:54:42","09-04-2025 10:46:11","09-04-2025 12:09=
:12","Grid outage, Site went down because Gen is overloaded(20, 300A) SS IH=
S Alphonse DEFFO is informed// He reduced load and started Gen manually","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage, Site went down because Gen overload(20, 300A) SS IHS Alphonse=
 DEFFO is informed// He reduiced load and started Gen manualy","vanel.mbiad=
a@matech-cameroun.com","512","09-04-2025 10:54:42","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004765071","SIM=
BOCK BONAMBAPE","","09-04-2025 10:42:14","09-04-2025 10:37:51","09-04-2025 =
12:25:52","Grid outage, Site went down before Gen start due to poor backup/=
 // Gen manually started","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup/ // Gen manually started","vanel.mbiada@ma=
tech-cameroun.com","264","09-04-2025 10:42:14","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004765058","Nko=
lnda","","09-04-2025 10:40:38","09-04-2025 10:37:05","09-04-2025 11:09:10",=
"Grid fluctuation, Site went down because gen fails to start due Grid conta=
ctor not excited//  site on Gen","Albran Byorel","Equipment Repair","Passiv=
e","Control Panel","ATS-AMF Issue","Grid fluctuation, Site went down becaus=
e gen fails to start due Grid contactor not excited//  site on Gen","vanel.=
mbiada@matech-cameroun.com","214","09-04-2025 10:40:38","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004765038","Mim=
boman4","","09-04-2025 10:37:36","09-04-2025 10:20:09","09-04-2025 13:00:13=
","Grid outage,Site went down because Gen battery is faulty//He started the=
 Gen with the external battery","Mba Lazare Herve","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Generator Battery","Grid outage,Site went down beca=
use Gen battery is faulty//He started the Gen with the external battery","v=
anel.mbiada@matech-cameroun.com","1048","09-04-2025 10:37:36","MATECH CMR"
"Closed Complete","Site Down","T3180","IHS_YND_253","NOCINC0004764627","Clg=
e-Advantiste","","09-04-2025 10:07:10","09-04-2025 09:51:04","09-04-2025 11=
:56:05","Gen card alarm low oil pressure// reset done gen need servicing","=
MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pres=
sure","11. Gen card alarm low oil pressure// reset done gen need servicing
","cedric.tiani@matech-cameroun.com","967","09-04-2025 10:07:10","MATECH CM=
R"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004764126","Nko=
londom","","09-04-2025 09:00:30","09-04-2025 08:43:19","09-04-2025 09:37:24=
","Grid outage, Site went down because Gen failed to start due to ATS malfu=
nctioning// He reset ATS and Gen manually started","Fabrice Pouakam","Equip=
ment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site w=
ent down because Gen failed to start due to ATS malfunctioning// He reset A=
TS and Gen manually started","cedric.tiani@matech-cameroun.com","1034","09-=
04-2025 09:00:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004764088","Donga","=
","09-04-2025 08:55:28","09-04-2025 08:03:56","09-04-2025 08:10:57","Cascad=
ed Incident from TTO4860754","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Mbadjock camrail","system",=
"273676","09-04-2025 08:55:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004764089","Dong",""=
,"09-04-2025 08:55:28","09-04-2025 08:03:56","09-04-2025 08:10:57","Cascade=
d Incident from TTO4860754","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Site impacted by Mbadjock camrail","system","=
273676","09-04-2025 08:55:28","MATECH CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0004764079","N=
guila","IHS_YND_434, IHS_YND_444","09-04-2025 08:54:22","09-04-2025 08:03:5=
6","09-04-2025 10:45:57","Site impacted by Mbadjock camrail","Parker Tchoup=
","Customer Equipment Failure","Active","Active Equipment Failure","Affecte=
d by 3rd Party Site","Site impacted by Mbadjock camrail","vanel.mbiada@mate=
ch-cameroun.com","3027","09-04-2025 08:54:22","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004763906","Nko=
lnda","","09-04-2025 08:22:28","09-04-2025 08:18:00","09-04-2025 09:17:29",=
"Grid outage, Site went down because Gen started and stopped with ""low oil=
 pressure"" alarm// He reset card GE and gen manually started","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage, Site went down because Gen started and stopped with ""low oil pressur=
e"" alarm// He reset card GE and gen manually started","vanel.mbiada@matech=
-cameroun.com","269","09-04-2025 08:22:28","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004763815","E=
vodoula OCM","","09-04-2025 08:04:45","09-04-2025 07:56:30","09-04-2025 10:=
21:56","No power issue on site ubaie 54V site on Grid Ghislain (694434993/I=
NG) is on site for Swap.","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site ubaie 54V site on Grid Ghislain (694434993/ING) is on site for=
 Swap.","cedric.tiani@matech-cameroun.com","496","09-04-2025 08:04:45","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004763803","E=
kombitie","","09-04-2025 08:03:30","09-04-2025 07:58:09","09-04-2025 10:21:=
46","Active: no power issue, site is on Grid with Ubaie=3D51.4V, Symphorien=
(650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no p=
ower issue, site is on Grid with Ubaie=3D51.4V, Symphorien(650257151/ huawe=
i) is informed","cedric.tiani@matech-cameroun.com","323","09-04-2025 08:03:=
30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004763714","Song-bon=
g","","09-04-2025 07:50:16","09-04-2025 07:40:13","09-04-2025 08:29:23","Ca=
scaded Incident from TTO4860352","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,site went down because =
Gen failed to start due to Gen contactor faulty // he bypassed and start th=
e Gen manually","system","275043","09-04-2025 07:50:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004763713","Eseka To=
wn","","09-04-2025 07:50:15","09-04-2025 07:40:13","09-04-2025 08:29:23","C=
ascaded Incident from TTO4860352","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,site went down because=
 Gen failed to start due to Gen contactor faulty // he bypassed and start t=
he Gen manually","system","275043","09-04-2025 07:50:15","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0004763706","E=
seka OCM","IHS_YND_378, IHS_YND_453","09-04-2025 07:49:30","09-04-2025 07:4=
0:13","09-04-2025 08:29:23","Grid outage,site went down because Gen failed =
to start due to Gen contactor faulty // he bypassed and start the Gen manua=
lly","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - Load=
 Contactor","Grid outage,site went down because Gen failed to start due to =
Gen contactor faulty // he bypassed and start the Gen manually","cedric.tia=
ni@matech-cameroun.com","558","09-04-2025 07:49:30","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004763553","Nko=
lbong","","09-04-2025 07:19:57","09-04-2025 07:15:21","09-04-2025 08:19:56"=
,"Grid outage,site went don because Grid  cable has burnt out and ATS fault=
y // site on Gen","Delor Telezing","Equipment Repair","Passive","Control Pa=
nel","ATS-AMF Issue","Grid outage,site went don because Grid  cable has bur=
nt out and ATS faulty // site on Gen","vanel.mbiada@matech-cameroun.com","2=
78","09-04-2025 07:19:57","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004763495","Nko=
londom","","09-04-2025 07:12:06","09-04-2025 06:44:10","09-04-2025 08:26:38=
","Grid outage, Site went down because Gen failed to start due to ATS malfu=
nctionning// He reset ATS and Gen manually started","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site =
went down because Gen failed to start due to ATS malfunctionning// He reset=
 ATS and Gen manually started","vanel.mbiada@matech-cameroun.com","1678","0=
9-04-2025 07:12:06","MATECH CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0004763459","MES=
SAME NDONGO 1162","","09-04-2025 07:03:33","09-04-2025 06:40:17","09-04-202=
5 07:27:13","grid outage,gen failed to start due to Gen card  malfunctionin=
g//he reset the card and started it","MINKA NICOLAS","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start d=
ue to Gen card  malfunctioning//he reset the card and started it","cedric.t=
iani@matech-cameroun.com","1396","09-04-2025 07:03:33","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0004763213","C=
arrefourt Nkomo","","09-04-2025 06:15:02","09-04-2025 06:05:59","09-04-2025=
 07:23:15","Grid outage.gen failed to start due to alarm low oil pressure//=
We added oil and gen manually started ","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage.gen failed t=
o start due to alarm low oil pressure//We added oil and gen manually starte=
d ","gerard.tchangoue@matech-cameroun.com","544","09-04-2025 06:15:02","MAT=
ECH CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0004763183","Bit=
oto","","09-04-2025 06:03:04","09-04-2025 05:51:59","09-04-2025 07:32:24","=
Grid outage, site went down because gen failed to start due to PWC ZTE malf=
unction // He reset controller and gen manually started","Mba Lazare Herve"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage, site went down because gen failed to start due to PWC ZTE malfun=
ction // He reset controller and gen manually started","gerard.tchangoue@ma=
tech-cameroun.com","666","09-04-2025 06:03:04","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004763177","B=
iteng-Maetur","","09-04-2025 06:01:15","09-04-2025 05:44:02","09-04-2025 08=
:25:56","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) // He reduced the load  and manually start the G=
en","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) // He reduced the load  and manually start the Gen=
","edwige.kapawo@matech-cameroun.com","1034","09-04-2025 06:01:15","MATECH =
CMR"
"Closed Complete","Site Down","T3180","IHS_YND_253","NOCINC0004763173","Clg=
e-Advantiste","","09-04-2025 05:59:52","09-04-2025 05:31:31","09-04-2025 06=
:42:25","Grid outage, Site went down because Gen started and stopped with "=
"low oil pressure"" alarm// He reset card GE and gen manually started","MIN=
KA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, Site went down because Gen started and stopped with ""low oil=
 pressure"" alarm// He reset card GE and gen manually started","gerard.tcha=
ngoue@matech-cameroun.com","1702","09-04-2025 05:59:52","MATECH CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0004763168","Mae=
tur","","09-04-2025 05:58:16","09-04-2025 05:24:59","09-04-2025 07:14:20","=
Grid outage,Gen failed to start due to Gen CB 32A tripped//he reamed the CB=
","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Load Brea=
ker","Grid outage,Gen failed to start due to Gen CB 32A tripped//he reamed =
the CB","gerard.tchangoue@matech-cameroun.com","1998","09-04-2025 05:58:16"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004763026","O=
mnisport 3","","09-04-2025 05:08:10","09-04-2025 05:05:00","09-04-2025 06:0=
7:00","Grid outage,site went down due to ATS RELAY faulty//He bypassed it a=
nd site on Grid","Delor Telezing","Equipment Repair","Passive","Control Pan=
el","ATS Relay Faulty","Grid outage,site went down due to ATS RELAY faulty/=
/He bypassed it and site on Grid","gerard.tchangoue@matech-cameroun.com","1=
91","09-04-2025 05:08:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004762946","Afanoya"=
,"","09-04-2025 04:38:02","09-04-2025 04:29:29","09-04-2025 06:09:29","Casc=
aded Incident from TTO4859401","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site wen down because CB (=
125A) in PWC  that tripped MTN //He reamed the cb","system","286351","09-04=
-2025 04:38:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0004762945","ELOUMDEM=
 CARRIERE","","09-04-2025 04:38:01","09-04-2025 04:29:29","09-04-2025 06:09=
:29","Cascaded Incident from TTO4859401","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage,site wen down becau=
se CB (125A) in PWC  that tripped MTN //He reamed the cb","system","286351"=
,"09-04-2025 04:38:01","MATECH CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004762930","Aha=
la","IHS_YND_767, IHS_YND_313","09-04-2025 04:34:47","09-04-2025 04:29:29",=
"09-04-2025 06:09:29","Grid outage,site went down because of CB (125A) in P=
WC  that tripped MTN //He reamed the cb","Hyemafo Gildas","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Grid o=
utage,site went down because of CB (125A) in PWC  that tripped MTN //He rea=
med the cb","gerard.tchangoue@matech-cameroun.com","319","09-04-2025 04:34:=
47","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004762889","E=
kombitie","","09-04-2025 04:17:16","09-04-2025 04:10:41","09-04-2025 04:18:=
25","Active: no power issue, site is on Grid with Ubaie=3D54.5V, Symphorien=
(650257151/ huawei) is informed	","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no =
power issue, site is on Grid with Ubaie=3D54.5V, Symphorien(650257151/ huaw=
ei) is informed	","gerard.tchangoue@matech-cameroun.com","396","09-04-2025 =
04:17:16","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004762860","Ole=
mbe MTN","","09-04-2025 04:04:04","09-04-2025 03:37:50","09-04-2025 07:54:2=
5","Site went down because IPT controller dyfunction //He bypassed it and s=
ite on Gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Site went down because IPT controller dyfunction //He by=
passed it and site on Gen","gerard.tchangoue@matech-cameroun.com","1575","0=
9-04-2025 04:04:04","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004762846","O=
dza","","09-04-2025 04:00:34","09-04-2025 03:53:18","09-04-2025 04:34:18","=
Grid outage, site went down because gen failed to start due to hybrid syste=
m malfunction // Gen manually started","Albran Byorel","Equipment Repair","=
Passive","Hybrid","Hybrid Module","Grid outage, site went down because gen =
failed to start due to hybrid system malfunction // Gen manually started","=
gerard.tchangoue@matech-cameroun.com","437","09-04-2025 04:00:34","MATECH C=
MR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004762709","M=
bankomo IHS","","09-04-2025 03:04:31","09-04-2025 03:00:16","09-04-2025 03:=
33:16","Grid outage gen failed to start due to card GE dysfunctionned//We r=
eset card GE and gen manually started","Fanda Brice","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to start d=
ue to card GE dysfunctionned//We reset card GE and gen manually started","g=
erard.tchangoue@matech-cameroun.com","256","09-04-2025 03:04:31","MATECH CM=
R"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004762662","MBA=
LNGONG LYCEE","","09-04-2025 02:57:18","09-04-2025 02:46:13","09-04-2025 03=
:16:37","Grid Outage Site went down due to Gen overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went d=
own due to Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and conf=
irmed // Grid return","edwige.kapawo@matech-cameroun.com","666","09-04-2025=
 02:57:18","MATECH CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0004762435","Nko=
abang Ebolmedjock","","09-04-2025 02:16:36","09-04-2025 02:05:24","09-04-20=
25 02:27:26","Grid fuctuation,Site went down due to Grid bad voltages //Gri=
d return","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Grid fuctuation,Site went down due to Grid bad =
voltages //Grid return","edwige.kapawo@matech-cameroun.com","672","09-04-20=
25 02:16:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004762350","Dong",""=
,"09-04-2025 01:58:48","09-04-2025 01:48:46","09-04-2025 01:58:34","Cascade=
d Incident from TTO4858709","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Site impacted by Mbadjock camrail","system","=
1216667","09-04-2025 01:58:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004762349","Donga","=
","09-04-2025 01:58:48","09-04-2025 01:48:46","09-04-2025 01:58:34","Cascad=
ed Incident from TTO4858709","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Mbadjock camrail","system",=
"1216667","09-04-2025 01:58:48","MATECH CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0004762337","N=
guila","IHS_YND_434, IHS_YND_444","09-04-2025 01:55:04","09-04-2025 01:48:4=
6","09-04-2025 01:58:34","Site impacted by Mbadjock camrail","Parker Tchoup=
","Customer Equipment Failure","Active","Active Equipment Failure","Affecte=
d by 3rd Party Site","Site impacted by Mbadjock camrail","edwige.kapawo@mat=
ech-cameroun.com","379","09-04-2025 01:55:04","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004762290","Men=
dong vallee","","09-04-2025 01:35:40","09-04-2025 01:20:32","09-04-2025 01:=
50:11","Active //No power issue on site U=3D55,1 V The Tx FME Hosiah//69969=
9694 is informed","Fanda Brice","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active //No power issue on site=
 U=3D55,1 V The Tx FME Hosiah//699699694 is informed","edwige.kapawo@matech=
-cameroun.com","909","09-04-2025 01:35:40","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004762237","E=
koumdoum","","09-04-2025 01:18:18","09-04-2025 00:55:01","09-04-2025 02:32:=
01","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS Pa=
scaline is informed and confirmed//We reduced load and gen manually started=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS Pasca=
line is informed and confirmed//We reduced load and gen manually started","=
edwige.kapawo@matech-cameroun.com","1398","09-04-2025 01:18:18","MATECH CMR=
"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004762202","ODZ=
A MINKAN EDIBI ASSI","","09-04-2025 01:04:58","09-04-2025 01:01:49","09-04-=
2025 15:42:53","site Went down due to insufficient rectifier issue on site =
//he reset it","Albran Byorel","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","site Went down due to insufficient rectifier issue on site=
 //he reset it","edwige.kapawo@matech-cameroun.com","190","09-04-2025 01:04=
:58","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004762201","Mon=
tee Jouvence","","09-04-2025 01:04:12","09-04-2025 00:58:24","09-04-2025 01=
:16:24","Grid outage, site down due to Poor battery backup // Grid return",=
"Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Battery Low","Grid outage, site down due to Poor battery backup // Grid=
 return","edwige.kapawo@matech-cameroun.com","349","09-04-2025 01:04:12","M=
ATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004762193","Mom=
","","09-04-2025 01:00:31","09-04-2025 00:59:17","09-04-2025 01:38:17","Act=
ive//No power issue site on Grid with U=3D53,3 V The FME TX Etienne(6950339=
81) From Huawei is informed. Site impacted by Ngoumou(T0169) no manager by =
IHS","Fanda Brice","Customer Equipment Failure","Active","Active Equipment =
Failure","Affected by 3rd Party Site","Active//No power issue site on Grid =
with U=3D53,3 V The FME TX Etienne(695033981) From Huawei is informed. Site=
 impacted by Ngoumou(T0169) no manager by IHS","edwige.kapawo@matech-camero=
un.com","76","09-04-2025 01:00:31","MATECH CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004762191","Ebo=
go","","09-04-2025 00:59:41","09-04-2025 00:55:27","09-04-2025 01:22:27","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed automatically","Siligap Boris","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Gen started automatically","edwige.kapawo@matech=
-cameroun.com","255","09-04-2025 00:59:41","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004762188","UPA=
C LP","","09-04-2025 00:58:50","09-04-2025 00:42:35","09-04-2025 01:18:35",=
"Grid outage,no space to deploy MDG // Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage,no space to dep=
loy MDG // Grid return","edwige.kapawo@matech-cameroun.com","976","09-04-20=
25 00:58:50","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004762186","N=
kozoa","","09-04-2025 00:57:05","09-04-2025 00:23:41","09-04-2025 03:27:41"=
,"Grid outage site went down because Gen overload(20KVA,340A) SS IHS F=E9li=
x Bateu is informed and Is confirmed// He reduced the load on site and star=
ted gen manualy","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage site went down because Gen overload(20KVA,34=
0A) SS IHS F=E9lix Bateu is informed and Is confirmed// He reduced the load=
 on site and started gen manualy","edwige.kapawo@matech-cameroun.com","2006=
","09-04-2025 00:57:05","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004762184","Beh=
ind P T school Yde","","09-04-2025 00:56:34","09-04-2025 00:39:08","09-04-2=
025 01:09:08","Grid outage, site went down because gen failed to start due =
to gen card faulty //Grid restored","Paul BIBOUM","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
gen failed to start due to gen card faulty //Grid restored","landry.etame@i=
hstowers.com","1047","09-04-2025 00:56:34","MATECH CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004762179","E=
leveur","","09-04-2025 00:55:56","09-04-2025 00:35:46","09-04-2025 01:35:46=
","no power issue on site U=3D56V site on Grid THE TX FME SYMPHORIEN (65025=
7151) from HUAWEI is informed	","Siligap Boris","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue =
on site U=3D56V site on Grid THE TX FME SYMPHORIEN (650257151) from HUAWEI =
is informed	","edwige.kapawo@matech-cameroun.com","1211","09-04-2025 00:55:=
56","MATECH CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004762174","M=
ini-Ferme","","09-04-2025 00:55:00","09-04-2025 00:38:47","09-04-2025 01:05=
:47","grid outage, no space to deploy a mobile gen// grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, =
no space to deploy a mobile gen// grid return","edwige.kapawo@matech-camero=
un.com","974","09-04-2025 00:55:00","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004762151","C=
RH-Etoug-Ebe","","09-04-2025 00:47:49","09-04-2025 00:38:41","09-04-2025 01=
:09:13","Eneo outage,sitedown due to poor backup // Grid return","Hyemafo G=
ildas","Equipment Repair","Passive","Control Panel","Power Cabinet - Batter=
y Low","Eneo outage,sitedown due to poor backup // Grid return","edwige.kap=
awo@matech-cameroun.com","549","09-04-2025 00:47:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004762144","ARMP",""=
,"09-04-2025 00:46:26","09-04-2025 00:43:51","09-04-2025 02:27:51","Cascade=
d Incident from TTO4858469","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down due to psc3 dysfunction due to high temp=
//He reset it","system","321666","09-04-2025 00:46:26","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004762139","D=
ragage","IHS_YND_208","09-04-2025 00:44:59","09-04-2025 00:43:51","09-04-20=
25 02:27:51","Site went down due to psc3 dysfunction due to high temp//He r=
eset it","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Site went down due to psc3 dysfunction due to high temp//He r=
eset it","edwige.kapawo@matech-cameroun.com","69","09-04-2025 00:44:59","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004762082","O=
lembe-Terminus","","09-04-2025 00:34:31","09-04-2025 00:17:12","09-04-2025 =
06:53:00","Grid outage site went down due to MPR faulty//We reset rectiifie=
r","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Ca=
binet","Grid outage site went down due to MPR faulty//We reset rectiifier",=
"edwige.kapawo@matech-cameroun.com","1041","09-04-2025 00:34:31","MATECH CM=
R"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004762068","Nko=
londom","","09-04-2025 00:32:01","09-04-2025 00:26:53","09-04-2025 00:42:53=
","Grid outage, Site went down because Gen failed to start due to ATS malfu=
nctionning// He reset ATS and Gen manually started","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site =
went down because Gen failed to start due to ATS malfunctionning// He reset=
 ATS and Gen manually started","edwige.kapawo@matech-cameroun.com","331","0=
9-04-2025 00:32:01","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004762067","Awa=
e Ewonkan","","09-04-2025 00:31:13","09-04-2025 00:26:55","09-04-2025 03:33=
:32","Grid outage site went down due to Gen overload (20KVA, 300A) // He re=
duce load and Start Gen Manually","Albran Byorel","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage site went down due to Gen ove=
rload (20KVA, 300A) // He reduce load and Start Gen Manually","edwige.kapaw=
o@matech-cameroun.com","3330","09-04-2025 00:31:13","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004762034","Odz=
a II OCM","","09-04-2025 00:22:19","09-04-2025 00:15:03","09-04-2025 03:25:=
43","Site Went Down due to ATS Faulty // He put site on Gen","Albran Byorel=
","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Site Went D=
own due to ATS Faulty // He put site on Gen","edwige.kapawo@matech-cameroun=
.com","538","09-04-2025 00:22:19","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004762024","Nko=
lbong","","09-04-2025 00:20:49","09-04-2025 00:01:40","09-04-2025 05:04:40"=
,"The eneo cable has burnt out and ATS faulty //  site left on GEN","Delor =
Telezing","Equipment Repair","Passive","Control Panel","ATS Relay Faulty","=
The eneo cable has burnt out and ATS faulty //  site left on GEN","edwige.k=
apawo@matech-cameroun.com","1150","09-04-2025 00:20:49","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004761907","C=
amp-Sic-Tsinga","","08-04-2025 23:51:44","08-04-2025 23:48:34","09-04-2025 =
02:20:08","Grid outage.no space to deploy mobile gen // grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage.no space to deploy mobile gen // grid power return","edwige.kapawo@=
matech-cameroun.com","191","08-04-2025 23:51:44","MATECH CMR"
"Closed Complete","Site Down","T3446","IHS_YND_712","NOCINC0004761857","Nko=
lkoumou OCM","","08-04-2025 23:44:23","08-04-2025 23:37:11","09-04-2025 03:=
33:11","eneo outage, site down due to fuel shortage // refuelling done","TI=
ENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Gri=
d Outage Issue","eneo outage, site down due to fuel shortage // refuelling =
done","edwige.kapawo@matech-cameroun.com","433","08-04-2025 23:44:23","MATE=
CH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004761642","Ole=
mbe MTN","","08-04-2025 22:55:19","08-04-2025 22:48:17","08-04-2025 22:50:1=
7","Site went down because insufficient of rectifier on site SS IHS felix b=
ateu is informed//Grid return	","Fabrice Pouakam","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down because insufficient of =
rectifier on site SS IHS felix bateu is informed//Grid return	","christelle=
.ngonga@matech-cameroun.com","423","08-04-2025 22:55:19","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004761602","NYO=
M FACE MAETUR","","08-04-2025 22:40:09","08-04-2025 22:18:55","08-04-2025 2=
3:31:39","Eneo fluctuations, Site went down due to Grid bad voltage // He b=
ypassed Grid ","Fabrice Pouakam","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Eneo fluctuations, Site went down due to Gr=
id bad voltage // He bypassed Grid ","gerard.tchangoue@matech-cameroun.com"=
,"1275","08-04-2025 22:40:09","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004761394","Nko=
ulou Carriere carrefourt","","08-04-2025 21:59:59","08-04-2025 21:51:50","0=
8-04-2025 21:59:50","Grid outage, site went down because due to Gen overloa=
d(20kva,310 A) IHS SS Alphonse is informed// We reduce load and gen manuall=
y started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, site went down because due to Gen overload(20kva=
,310 A) IHS SS Alphonse is informed// We reduce load and gen manually start=
ed","gerard.tchangoue@matech-cameroun.com","186064","08-04-2025 21:59:59","=
MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004761393","Nko=
ulou Carriere carrefourt","","08-04-2025 21:59:58","08-04-2025 21:59:58","0=
8-04-2025 23:43:27","Site went down because gen overload (13Kw, 180A) SS IH=
S Alphonse DEFFO is informed// he Reduice the Load and Site is on Gen","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","S=
ite went down because gen overload (13Kw, 180A) SS IHS Alphonse DEFFO is in=
formed// he Reduice the Load and Site is on Gen","christian.fonkou@ihstower=
s.com","183919","08-04-2025 21:59:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_190","NOCINC0004761359","Ngousso-=
II","","08-04-2025 21:52:33","08-04-2025 21:30:38","08-04-2025 22:42:38","C=
ascaded Incident from TTO4857373","MFOUAGUEGUE MATHIEU","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down due to insuffic=
iency rectifiers// site up (retifiers to be replaced)","system","268323","0=
8-04-2025 21:52:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0004761275","Crf-Nkol=
bisson","","08-04-2025 21:42:49","08-04-2025 20:51:44","08-04-2025 22:03:44=
","site went down because the CB(125A)which feeds OCM equipment tripped// C=
B rearmed","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control=
 Panel","Circuit Breaker Tripped","site went down because the CB(125A)which=
 feeds OCM equipment tripped// CB rearmed","joelle.ekessi@ihstowers.com","3=
066","08-04-2025 21:42:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_796","NOCINC0004761272","Nkoabang=
 Ebolmedjock","","08-04-2025 21:41:46","08-04-2025 21:30:38","08-04-2025 22=
:42:38","Cascaded Incident from TTO4857373","Mba Lazare Herve","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","site went down due to i=
nsufficiency rectifiers// site up (retifiers to be replaced)","system","268=
323","08-04-2025 21:41:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_213","NOCINC0004761265","Nkolmess=
eng","IHS_YND_190, IHS_YND_796","08-04-2025 21:40:45","08-04-2025 21:30:38"=
,"08-04-2025 22:42:38","site went down due to insufficiency rectifiers// si=
te up (retifiers to be replaced)","Siligap Boris","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","site went down due to insufficiency rec=
tifiers// site up (retifiers to be replaced)","joelle.ekessi@ihstowers.com"=
,"608","08-04-2025 21:40:45","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004761194","ETO=
UDI Entree du palais","","08-04-2025 21:29:05","08-04-2025 21:19:46","08-04=
-2025 21:42:46","Grid outage, Site went down because Gen failled to start /=
/ Grid return (investigation ongoing)","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down b=
ecause Gen failled to start // Grid return (investigation ongoing)","gerard=
.tchangoue@matech-cameroun.com","560","08-04-2025 21:29:05","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004761124","UPA=
C LP","","08-04-2025 21:22:50","08-04-2025 21:09:43","08-04-2025 21:45:43",=
"Grid outage,no space to deploy MDG // Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage,no space to dep=
loy MDG // Grid return","christian.fonkou@ihstowers.com","788","08-04-2025 =
21:22:50","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004761120","SIM=
BOCK BONAMBAPE","","08-04-2025 21:22:06","08-04-2025 20:22:55","08-04-2025 =
21:31:55","site went down because the CB(125A)which feeds OCM equipment tri=
pped// CB rearmed (Site impacted by Mefou-Assi)","Hyemafo Gildas","Equipmen=
t Repair","Passive","Control Panel","Circuit Breaker Tripped","site went do=
wn because the CB(125A)which feeds OCM equipment tripped// CB rearmed (Site=
 impacted by Mefou-Assi)","gerard.tchangoue@matech-cameroun.com","3551","08=
-04-2025 21:22:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004761033","SOA VILL=
AGE","","08-04-2025 21:12:26","08-04-2025 20:33:36","08-04-2025 21:05:36","=
Cascaded Incident from TTO4857069","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage , Site went Down due to=
  Gen overload, // Grid restoration.","system","271747","08-04-2025 21:12:2=
6","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004761032","TSINGA V=
ILLAGE 2","","08-04-2025 21:12:26","08-04-2025 20:33:36","08-04-2025 21:05:=
36","Cascaded Incident from TTO4857069","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage , Site went Down =
due to  Gen overload, // Grid restoration.","system","271747","08-04-2025 2=
1:12:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0004761035","Nkolfoul=
ou Tsinga Village","","08-04-2025 21:12:26","08-04-2025 20:33:36","08-04-20=
25 21:05:36","Cascaded Incident from TTO4857069","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage , Site we=
nt Down due to  Gen overload, // Grid restoration.","system","271747","08-0=
4-2025 21:12:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_296","NOCINC0004761034","Nkolfoul=
ou","","08-04-2025 21:12:26","08-04-2025 20:33:36","08-04-2025 21:05:36","C=
ascaded Incident from TTO4857069","Siligap Boris","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage , Site went Down due to =
 Gen overload, // Grid restoration.","system","271746","08-04-2025 21:12:26=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004761031","Mvog-Eba=
nda","","08-04-2025 21:12:25","08-04-2025 20:33:36","08-04-2025 21:05:36","=
Cascaded Incident from TTO4857069","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage , Site went Down due to=
  Gen overload, // Grid restoration.","system","271746","08-04-2025 21:12:2=
5","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_258","NOCINC0004761004","Mefou-As=
si","IHS_YND_537","08-04-2025 21:07:37","08-04-2025 20:42:31","08-04-2025 2=
2:29:33","site went down because the CB(125A)which feeds OCM equipment trip=
ped// CB rearmed","Fanda Brice","Equipment Repair","Passive","Control Panel=
","Circuit Breaker Tripped","site went down because the CB(125A)which feeds=
 OCM equipment tripped// CB rearmed","joelle.ekessi@ihstowers.com","1507","=
08-04-2025 21:07:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004760996","Nkolfoul=
ou 2","IHS_YND_269, IHS_YND_719, IHS_YND_323, IHS_YND_296, IHS_YND_759","08=
-04-2025 21:06:42","08-04-2025 20:33:36","08-04-2025 21:05:36","Grid outage=
 , Site went Down due to  Gen overload, // Grid restoration.","Siligap Bori=
s","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,=
 Site went Down due to  Gen overload, // Grid restoration.","joelle.ekessi@=
ihstowers.com","1987","08-04-2025 21:06:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004760700","ETOUDI C=
HAPELLE","","08-04-2025 20:30:16","08-04-2025 20:26:13","08-04-2025 22:29:2=
1","Grid outage.site went down because gen failed to start//Grid return(inv=
estigation ongoing)","Delor Telezing","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage.site went down because gen failed to=
 start//Grid return(investigation ongoing)","joelle.ekessi@ihstowers.com","=
244","08-04-2025 20:30:16","MATECH CMR"
"Closed Complete","Site Down","T0535","IHS_YND_234","NOCINC0004760689","Oyo=
mabang MTN","","08-04-2025 20:28:21","08-04-2025 19:47:51","08-04-2025 20:5=
4:58","No power issue on site ,site on Gen with Ubaie =3D 53V The FME TX Mo=
uhamadou //699949072// From Huawei is informed.","TIENTCHEU NZETCHIEU GAEL"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue on site ,site on Gen with Ubaie =3D 53V The FME=
 TX Mouhamadou //699949072// From Huawei is informed.","gerard.tchangoue@ma=
tech-cameroun.com","2431","08-04-2025 20:28:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_287","NOCINC0004760490","Nkolafem=
e","IHS_YND_309","08-04-2025 20:03:12","08-04-2025 19:47:49","08-04-2025 20=
:54:49","Grid outage, Site went down due to Gen overload(20KVA, 375A) SS IH=
S Pascaline is informed // he Reduced the Load and Manually Started the Gen=
","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down due to Gen overload(20KVA, 375A) S=
S IHS Pascaline is informed // he Reduced the Load and Manually Started the=
 Gen","system","2982","08-04-2025 20:03:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004760488","Ngoulmek=
ong-Nord","","08-04-2025 20:03:12","08-04-2025 19:51:49","08-04-2025 20:54:=
49","Grid outage, site went down due to Gen overload(12.5kva,210 A) IHS SS =
Blaise Raoul is informed and confirmed//Grid return","Siligap Boris","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down due to =
insufficiency of rectifiers on site // He reduced the load","system","683",=
"08-04-2025 20:03:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004760491","TSINGA V=
ILLAGE 2","","08-04-2025 20:03:12","08-04-2025 19:51:49","08-04-2025 20:19:=
49","Cascaded Incident from TTO4856392","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down due to CB Gen =
disjuncted //We rearmed the CB and site on gen","system","266909","08-04-20=
25 20:03:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004760489","Leboudi"=
,"","08-04-2025 20:03:12","08-04-2025 19:51:49","08-04-2025 20:54:49","Casc=
aded Incident from TTO4856392 - Cascade Removed From TTO4856392","TIENTCHEU=
 NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage, Site went down due to Gen overload(20KVA, 375A) SS IHS P=
ascaline is informed // he Reduced the Load and Manually Started the Gen","=
system","266999","08-04-2025 20:03:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004760487","Melen Ba=
'aba","","08-04-2025 20:03:11","08-04-2025 19:51:49","08-04-2025 20:19:49",=
"Cascaded Incident from TTO4856392 - Cascade Removed From TTO4856392","Sili=
gap Boris","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
site went down due to CB Gen disjuncted //We rearmed the CB and site on gen=
","system","266908","08-04-2025 20:03:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004760486","Nkolfoul=
ou 2","","08-04-2025 20:03:11","08-04-2025 19:51:49","08-04-2025 20:19:49",=
"Cascaded Incident from TTO4856392 - Cascade Removed From TTO4856392","Sili=
gap Boris","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
site went down due to CB Gen disjuncted //We rearmed the CB and site on gen=
","system","266908","08-04-2025 20:03:11","MATECH CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004760435","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","08-04-2025 19:56:07","0=
8-04-2025 19:51:49","08-04-2025 20:19:49","site went down due to CB Gen dis=
juncted //We rearmed the CB and site on gen","Siligap Boris","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","sit=
e went down due to CB Gen disjuncted //We rearmed the CB and site on gen","=
gerard.tchangoue@matech-cameroun.com","259","08-04-2025 19:56:07","MATECH C=
MR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004760415","E=
kombitie","","08-04-2025 19:50:26","08-04-2025 19:39:19","08-04-2025 19:49:=
19","Active: no power issue, site is on Grid with Ubaie=3D54.5V, Symphorien=
(650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no p=
ower issue, site is on Grid with Ubaie=3D54.5V, Symphorien(650257151/ huawe=
i) is informed","gerard.tchangoue@matech-cameroun.com","668","08-04-2025 19=
:50:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_301","NOCINC0004760355","Tsinga v=
illage","","08-04-2025 19:44:45","08-04-2025 19:17:38","08-04-2025 19:19:38=
","Site went down due to insufficiency of rectifier caused by increase in l=
oad // He reduced the load, site on grid","Delor Telezing","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Site went down due to insuffic=
iency of rectifier caused by increase in load // He reduced the load, site =
on grid","christelle.ngonga@matech-cameroun.com","1628","08-04-2025 19:44:4=
5","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_087","NOCINC0004760111","Camp-Sic=
-Tsinga","","08-04-2025 19:05:45","08-04-2025 17:41:39","08-04-2025 17:44:4=
8","Grid outage.no space to deploy mobile gen // grid power return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.no space to deploy mobile gen // grid power return","joelle.ekessi@ihstowe=
rs.com","5047","08-04-2025 19:05:45","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0004760064","A=
hala","","08-04-2025 18:55:50","08-04-2025 18:43:43","08-04-2025 19:25:43",=
"Gid outage,Site went down because CB (125A)in PWC had tripped ocm //He rea=
rmed it","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Circuit Breaker Issue","Gid outage,Site went down because CB (1=
25A)in PWC had tripped ocm //He rearmed it","gerard.tchangoue@matech-camero=
un.com","728","08-04-2025 18:55:50","MATECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004759912","Emo=
mbo Esssomba","","08-04-2025 18:25:22","08-04-2025 18:11:00","08-04-2025 19=
:34:00","Grid outage.site went down due to gen failed to start //grid retur=
n(investigation ongoing)","Mba Lazare Herve","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage.site went down due to gen fai=
led to start //grid return(investigation ongoing)","gerard.tchangoue@matech=
-cameroun.com","863","08-04-2025 18:25:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0004759608","Biteng-M=
aetur","","08-04-2025 17:28:53","08-04-2025 14:27:42","08-04-2025 18:30:09"=
,"No power issue site on Grid with U=3D53.1v site on Grid Flubert(654266068=
) from Huawei is informed,","Mba Lazare Herve","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on Grid with U=3D53.1v site on Grid Flubert(654266068) from Huawei is i=
nformed,","christelle.ngonga@matech-cameroun.com","10872","08-04-2025 17:28=
:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0004759375","Olembe-T=
erminus","","08-04-2025 16:54:32","08-04-2025 16:50:29","08-04-2025 17:13:2=
9","Grid outage site went don due to grid contactor faulty//We replace grid=
 contactor and site on grid","Fabrice Pouakam","Equipment Repair","Passive"=
,"Control Panel","ATS-AMF Issue","Grid outage site went don due to grid con=
tactor faulty//We replace grid contactor and site on grid","joelle.ekessi@i=
hstowers.com","245","08-04-2025 16:54:32","MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004759349","B=
astos Bir","","08-04-2025 16:50:09","08-04-2025 16:39:46","08-04-2025 20:15=
:46","Active//No power issue, site is on Gen with Ubaie=3D54.5 V, Eloundou =
bertrant(652586578) from Huawei is informed","Mboua Thierry","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue, site is on Gen with Ubaie=3D54.5 V, Eloundou bertrant=
(652586578) from Huawei is informed","gerard.tchangoue@matech-cameroun.com"=
,"624","08-04-2025 16:50:09","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004758991","B=
arriere","","08-04-2025 16:06:37","08-04-2025 15:43:19","08-04-2025 16:48:1=
9","grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // He reduced the load and gen manually=
 started","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","grid outage, Site went down because Gen overload(20kva,400 A) IH=
S SS Felix Zambe is informed and confirmed // He reduced the load and gen m=
anually started","gerard.tchangoue@matech-cameroun.com","1399","08-04-2025 =
16:06:37","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004758909","C=
amp-Sic-Tsinga","","08-04-2025 15:54:06","08-04-2025 14:27:56","08-04-2025 =
15:13:56","Grid outage.no space to deploy mobile gen // grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage.no space to deploy mobile gen // grid power return","gerard.tchango=
ue@matech-cameroun.com","5171","08-04-2025 15:54:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_321","NOCINC0004758874","Soa","",=
"08-04-2025 15:45:36","08-04-2025 14:16:32","08-04-2025 15:23:19","site wen=
t down due to(1/7) rectifier faulty//We replaced rectifier faulty and site =
on grid","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","site went down due to(1/7) rectifier faulty//We replaced rectifi=
er faulty and site on grid","joelle.ekessi@ihstowers.com","9483","08-04-202=
5 15:45:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004758607","Bondjock=
","","08-04-2025 15:07:45","08-04-2025 14:18:27","08-04-2025 15:21:27","Cas=
caded Incident from TTO4854186","Fanda Brice","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue site on grid with U=3D54.6v =
Flubert from Huawei is informed","system","337519","08-04-2025 15:07:45","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_706","NOCINC0004758606","Mbankomo=
 CAF","","08-04-2025 15:07:45","08-04-2025 14:18:27","08-04-2025 15:21:27",=
"Cascaded Incident from TTO4854186","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D54=
.6v Flubert from Huawei is informed","system","337519","08-04-2025 15:07:45=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_281","NOCINC0004758592","Odza II"=
,"","08-04-2025 15:05:57","08-04-2025 14:31:50","08-04-2025 14:40:50","Site=
 Went Down due to ATS Faulty // He put site on Gen","Albran Byorel","Equipm=
ent Repair","Passive","Control Panel","ATS-AMF Issue","Site Went Down due t=
o ATS Faulty // He put site on Gen","joelle.ekessi@ihstowers.com","2049","0=
8-04-2025 15:05:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004758584","Nomayos =
montee Meche","","08-04-2025 15:04:08","08-04-2025 14:18:27","08-04-2025 15=
:21:27","Cascaded Incident from TTO4854186","Fanda Brice","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue site on grid wit=
h U=3D54.6v Flubert from Huawei is informed","system","337519","08-04-2025 =
15:04:08","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004758581","F=
ouda-New","","08-04-2025 15:03:36","08-04-2025 14:07:30","08-04-2025 15:31:=
30","Site went down due to MPR malfunctioning // Reset of rectifiers done",=
"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Cabine=
t","Site went down due to MPR malfunctioning // Reset of rectifiers done","=
joelle.ekessi@ihstowers.com","3367","08-04-2025 15:03:36","MATECH CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004758575","Nom=
ayos","IHS_YND_791, IHS_YND_706, IHS_YND_372, IHS_YND_762","08-04-2025 15:0=
2:39","08-04-2025 14:18:27","09-04-2025 10:21:27","No powe issue site on gr=
id with U=3D54.6v Flubert from Huawei is informed","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No powe issue site on grid with U=3D54.6v Flubert from Huawei is informed=
","gerard.tchangoue@matech-cameroun.com","2653","08-04-2025 15:02:39","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004758509","S=
OA TOWN","","08-04-2025 14:53:27","08-04-2025 14:24:11","08-04-2025 16:05:1=
1","Site went down due to trip of Cb(100A)  in PWC that feeds ocm // He cha=
nged with Cb(125A), site on grid","Siligap Boris","Equipment Repair","Passi=
ve","Control Panel","Circuit Breaker Tripped","Site went down due to trip o=
f Cb(100A)  in PWC that feeds ocm // He changed with Cb(125A), site on grid=
","gerard.tchangoue@matech-cameroun.com","1757","08-04-2025 14:53:27","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004758244","A=
kak-Nkozoa-MTN-IHS","","08-04-2025 14:18:46","08-04-2025 14:15:34","08-04-2=
025 16:05:34","Grid outage .gen failed to start due to low oil pressure//We=
 added oil and gen manually started ","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage .gen failed to =
start due to low oil pressure//We added oil and gen manually started ","ger=
ard.tchangoue@matech-cameroun.com","195","08-04-2025 14:18:46","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004758214","NTU=
I TOWN","","08-04-2025 14:10:53","08-04-2025 13:26:41","08-04-2025 15:21:41=
","Grid outage.gen failed to start due to air intake//We purged and gen man=
ually started","Parker Tchoup","Fuel Outage (Probable)","Passive","ACDG Gen=
","ACDG - Air Intake","Grid outage.gen failed to start due to air intake//W=
e purged and gen manually started","gerard.tchangoue@matech-cameroun.com","=
2653","08-04-2025 14:10:53","MATECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004758174","ODZ=
A CITE MBIA","","08-04-2025 14:08:42","08-04-2025 13:29:46","08-04-2025 14:=
39:46","Grid fluctuation site went down due to bad grid voltage and gen fai=
led to start //Grid power stabilized","Albran Byorel","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid fluctuation site =
went down due to bad grid voltage and gen failed to start //Grid power stab=
ilized","gerard.tchangoue@matech-cameroun.com","2337","08-04-2025 14:08:42"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004758150","ARMP",""=
,"08-04-2025 14:05:19","08-04-2025 13:26:28","08-04-2025 13:55:09","Cascade=
d Incident from TTO4853654","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down due to insufficiency of rectifiers on si=
te  // Site Stabilizead","system","304550","08-04-2025 14:05:19","MATECH CM=
R"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004758106","D=
ragage","IHS_YND_208","08-04-2025 13:59:33","08-04-2025 13:26:28","08-04-20=
25 13:55:09","Site went down due to insufficiency of rectifiers on site  //=
 Site Stabilizead","Mboua Thierry","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to insufficiency of rectifiers on s=
ite  // Site Stabilizead","gerard.tchangoue@matech-cameroun.com","1986","08=
-04-2025 13:59:33","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004758044","C=
rf-Nkolbisson","","08-04-2025 13:50:49","08-04-2025 13:37:36","08-04-2025 1=
8:38:36","site went down because the  CB(125A)which feeds OCM equipment tri=
pped// CB rearmed ","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive"=
,"Control Panel","Circuit Breaker Tripped","site went down due to CB(125A)w=
hich feeds OCM =E9quipements tripped//we rearmed CB","gerard.tchangoue@mate=
ch-cameroun.com","794","08-04-2025 13:50:49","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0004758028","N=
komo","","08-04-2025 13:47:56","08-04-2025 13:39:41","08-04-2025 13:57:41",=
"Grid outage gen failed to start due to alarm high temp//We added water and=
 gen manually started","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage gen fai=
led to start due to alarm high temp//We added water and gen manually starte=
d","gerard.tchangoue@matech-cameroun.com","496","08-04-2025 13:47:56","MATE=
CH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004757667","Mon=
tee Jouvence","","08-04-2025 13:00:19","08-04-2025 12:46:54","08-04-2025 13=
:02:47","Grid outage, site down due to Poor battery backup  // Grid return"=
,"Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Battery Low","site down due to poor backup // site up without interven=
tion","gerard.tchangoue@matech-cameroun.com","806","08-04-2025 13:00:19","M=
ATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004757613","Man=
guiers Dispensaire","","08-04-2025 12:54:23","08-04-2025 12:43:59","08-04-2=
025 14:57:59","Grid outage.site went due to grid contactor faulty//We bypas=
sed grid contactor and site on grid","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid outage.site went due to grid=
 contactor faulty//We bypassed grid contactor and site on grid","gerard.tch=
angoue@matech-cameroun.com","625","08-04-2025 12:54:23","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004757404","Bit=
eng-Maetur","","08-04-2025 12:38:32","08-04-2025 12:32:00","08-04-2025 14:1=
6:34","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) // He reduced the load","Mba Lazare Herve","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen started and stopped due to Gen overload(20kva, 280A) // He=
 reduced the load","gerard.tchangoue@matech-cameroun.com","452","08-04-2025=
 12:38:32","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004757399","Nlo=
ngkak","","08-04-2025 12:37:50","08-04-2025 12:05:49","08-04-2025 12:58:10"=
,"overvoltage on one Eneo phase //removal of this phase and bridge made wit=
h the remaining two phases","Delor Telezing","Grid Supply","Passive","Grid"=
,"National Grid - Grid Incomplete Phase","overvoltage on one Eneo phase //r=
emoval of this phase and bridge made with the remaining two phases","loic.n=
oumsi@matech-cameroun.com","1922","08-04-2025 12:37:50","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004757389","E=
kombitie","","08-04-2025 12:37:17","08-04-2025 12:31:04","08-04-2025 12:48:=
25","Active: no power issue, site is on Grid with Ubaie=3D54.5V, Symphorien=
(650257151/ huawei) is informed","Fabrice Pouakam","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no p=
ower issue, site is on Grid with Ubaie=3D54.5V, Symphorien(650257151/ huawe=
i) is informed","gerard.tchangoue@matech-cameroun.com","375","08-04-2025 12=
:37:17","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0004757358","M=
fou EPC","","08-04-2025 12:33:12","08-04-2025 12:27:59","08-04-2025 12:58:5=
1","Grid outage , Gen stopped due to belt cut // Gen belt replace","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Fan Belt","Grid =
outage , Gen stopped due to belt cut // Gen belt replace","gerard.tchangoue=
@matech-cameroun.com","314","08-04-2025 12:33:12","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004757295","E=
vodoula OCM","","08-04-2025 12:27:26","08-04-2025 12:22:12","08-04-2025 13:=
29:27","No power issue on site ubaie 54V site on Grid Ghislain  (694434993/=
ING) is on site for Swap.","TIENTCHEU NZETCHIEU GAEL","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site ubaie 54V site on Grid Ghislain  (694434993/ING) is on site f=
or Swap.","gaelle.njiofack@matech-cameroun.com","315","08-04-2025 12:27:26"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004757251","N=
kolfon Cimencam","","08-04-2025 12:23:35","08-04-2025 11:55:16","09-04-2025=
 08:45:27","Active//No power issue, Site on Grid Ubai=3D 52,8V. Notice that=
 it is impacted by Afanoya II The Tx FME Fulbert from Huawei is informed","=
Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 52=
,8V. Notice that it is impacted by Afanoya II The Tx FME Fulbert from Huawe=
i is informed","gaelle.njiofack@matech-cameroun.com","1700","08-04-2025 12:=
23:35","MATECH CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004757153","Nsi=
malen MTN","","08-04-2025 12:11:50","08-04-2025 12:01:26","08-04-2025 12:11=
:26","Grid Outage, site went down before gen start due to poor battery back=
up // Gen started automatically","Albran Byorel","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, site went do=
wn before gen start due to poor battery backup // Gen started automatically=
","loic.noumsi@matech-cameroun.com","625","08-04-2025 12:11:50","MATECH CMR=
"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0004756864","E=
lig Edzoa","","08-04-2025 11:25:53","08-04-2025 11:02:45","08-04-2025 12:22=
:03","No power issue site on grid with U=3D51v, Armand (699949553 / Huawei)=
 is informed","Delor Telezing","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with=
 U=3D51v, Armand (699949553 / Huawei) is informed","loic.noumsi@matech-came=
roun.com","1389","08-04-2025 11:25:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004756643","ELOUMDEM=
 CARRIERE 2","","08-04-2025 10:55:39","08-04-2025 10:45:39","08-04-2025 10:=
51:21","Cascaded Incident from TTO4852012","Fanda Brice","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue site on grid with=
 U=3D54v Flubert from Huawei is informed","system","350351","08-04-2025 10:=
55:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004756641","Eto koss=
 Yde","","08-04-2025 10:55:38","08-04-2025 10:45:39","08-04-2025 10:51:21",=
"Cascaded Incident from TTO4852012","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D54=
v Flubert from Huawei is informed","system","350351","08-04-2025 10:55:38",=
"MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004756628","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","08-04-2025 10:53:49","08-04-2025 10:45=
:39","09-04-2025 10:21:21","No power issue site on grid with U=3D54v Fluber=
t from Huawei is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with U=3D54v Flubert from Huawei is informed","loic.noumsi@matech-cam=
eroun.com","492","08-04-2025 10:53:49","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004756533","K=
oweit City","","08-04-2025 10:41:34","08-04-2025 10:32:27","08-04-2025 10:3=
2:28","Wrongly ticket ","Albran Byorel","Incorrectly Logged Tickets","Error=
","Error","Error","Wrongly ticket ","loic.noumsi@matech-cameroun.com","548"=
,"08-04-2025 10:41:34","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004756445","Nko=
zoa","","08-04-2025 10:29:13","08-04-2025 10:21:14","08-04-2025 10:30:29","=
Active // No power issue UBaie =3D54,7V site on Grid The FME TX SYMPHORIEN =
(675295205) From Huawei is informed","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/ No power issue UBaie =3D54,7V site on Grid The FME TX SYMPHORIEN (6752952=
05) From Huawei is informed","loic.noumsi@matech-cameroun.com","481","08-04=
-2025 10:29:13","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004755919","Odz=
a petit marche new","","08-04-2025 09:18:20","08-04-2025 09:05:08","08-04-2=
025 10:01:08","Site went down due to insufficiency of rectifiers on site SS=
 IHS Pascaline is confirm // He reduced the load","Albran Byorel","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module","Site went down due to i=
nsufficiency of rectifiers on site SS IHS Pascaline is confirm // He reduce=
d the load","loic.noumsi@matech-cameroun.com","793","08-04-2025 09:18:20","=
MATECH CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0004755685","N=
goum","","08-04-2025 08:41:17","08-04-2025 08:23:08","09-04-2025 15:54:45",=
"SITE DOWN DUE TO PWC burnt // PWC  replace","Parker Tchoup","Fire on Site"=
,"Passive","Infrastructure","Fire - Burned","FME indormed us that PWC burnt=
 and site still down","loic.noumsi@matech-cameroun.com","1091","08-04-2025 =
08:41:17","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004755642","J=
-Vespa","","08-04-2025 08:32:17","08-04-2025 08:25:59","08-04-2025 08:29:42=
","site went down due to cable of eneo meter burned and gen failed to start=
 //we replace the cable","Mboua Thierry","Equipment Repair","Passive","Infr=
astructure","Armoured Cable","site went down due to cable of eneo meter bur=
ned and gen failed to start //we replace the cable","loic.noumsi@matech-cam=
eroun.com","379","08-04-2025 08:32:17","MATECH CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004755466","Jea=
n Vespa","","08-04-2025 08:05:52","08-04-2025 07:56:52","08-04-2025 08:28:5=
3","site went down due to cable of eneo meter burned and gen failed to star=
t //we replace the cable","Mboua Thierry","Equipment Repair","Passive","Inf=
rastructure","Armoured Cable","site went down due to cable of eneo meter bu=
rned and gen failed to start //we replace the cable","loic.noumsi@matech-ca=
meroun.com","541","08-04-2025 08:05:52","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004755125","C=
amp-Sic-Tsinga","","08-04-2025 06:49:36","07-04-2025 16:49:03","07-04-2025 =
23:55:13","Grid outage.no space to deploy mobile gen // grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage.no space to deploy mobile gen // grid power return","kouoh.jean@ihs=
towers.com","50434","08-04-2025 06:49:36","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0004754878","Feb=
e Village","","08-04-2025 06:04:11","08-04-2025 05:56:57","08-04-2025 07:14=
:17","Site down due to gen overload // fme reduced load, gen restarted","Mb=
oua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Sit=
e down due to gen overload // fme reduced load, gen restarted","edwige.kapa=
wo@matech-cameroun.com","435","08-04-2025 06:04:11","MATECH CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0004754743","NYO=
M","","08-04-2025 05:13:01","08-04-2025 05:06:48","08-04-2025 06:22:30","si=
te down due to rectifier issue // need of 1 rectifier, site on grid ","Fabr=
ice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Battery","=
site down due to rectifier issue // need of 1 rectifier, site on grid ","ge=
rard.tchangoue@matech-cameroun.com","374","08-04-2025 05:13:01","MATECH CMR=
"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0004754729","M=
volye-New","","08-04-2025 05:05:59","08-04-2025 05:01:47","08-04-2025 05:09=
:06","No power Issue Site on Grid Ubai =3D51.8V, The FME The TX FME Mbah Ho=
siah (674007438) is informed","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power Issue Site on Grid Ub=
ai =3D51.8V, The FME The TX FME Mbah Hosiah (674007438) is informed","gerar=
d.tchangoue@matech-cameroun.com","253","08-04-2025 05:05:59","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004754490","N=
kolfon Cimencam","","08-04-2025 03:43:15","08-04-2025 03:33:59","08-04-2025=
 03:44:35","Active//No power issue, Site on Grid Ubai=3D 52,8V. Notice that=
 it is impacted by Afanoya II The Tx FME Fulbert from Huawei is informed","=
Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 52=
,8V. Notice that it is impacted by Afanoya II The Tx FME Fulbert from Huawe=
i is informed","gerard.tchangoue@matech-cameroun.com","557","08-04-2025 03:=
43:15","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004754099","Mfo=
u EPC","","08-04-2025 02:00:58","08-04-2025 01:26:32","08-04-2025 02:38:52"=
,"site down due to high temp on generator  // water added ","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","Gen Temp High","site down due =
to high temp on generator  // water added ","edwige.kapawo@matech-cameroun.=
com","2068","08-04-2025 02:00:58","MATECH CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0004753928","Don=
g","","08-04-2025 01:16:37","08-04-2025 01:07:29","08-04-2025 05:11:29","Si=
te Went Down due to fuel Shortage // Tank inclined (refueling Ongoing)","Pa=
rker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Site Went Do=
wn due to fuel Shortage // Tank inclined (refueling Ongoing)","edwige.kapaw=
o@matech-cameroun.com","583","08-04-2025 01:16:37","MATECH CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0004753611","NYO=
M","","08-04-2025 00:51:45","08-04-2025 00:25:36","08-04-2025 01:45:01","Si=
te went Dow due to grid bad voltage //he did a bridge on good phase","Fabri=
ce Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Site went Dow due to grid bad voltage //he did a bridge on good =
phase","edwige.kapawo@matech-cameroun.com","1570","08-04-2025 00:51:45","MA=
TECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004753592","Nko=
abang MTN","","08-04-2025 00:50:37","08-04-2025 00:25:18","08-04-2025 01:53=
:27","Site Went Down due to 02/03 rectifier dysfunction // rectifier reset"=
,"Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site Went Down due to 02/03 rectifier dysfunction // rectifier reset"=
,"edwige.kapawo@matech-cameroun.com","1520","08-04-2025 00:50:37","MATECH C=
MR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004752488","Nsi=
malen MTN","","07-04-2025 23:48:39","07-04-2025 23:34:00","07-04-2025 23:44=
:24","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automatically","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen started automatically","edwige.kapawo=
@matech-cameroun.com","879","07-04-2025 23:48:39","MATECH CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004751800","Jou=
vence Mbenda","","07-04-2025 23:14:43","07-04-2025 22:27:07","08-04-2025 00=
:07:31","Grid outage gen start and stopped due to alarm high temp //We add =
water and gen manually started","Hyemafo Gildas","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage =
gen start and stopped due to alarm high temp //We add water and gen manuall=
y started","edwige.kapawo@matech-cameroun.com","2857","07-04-2025 23:14:43"=
,"MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004751684","Nko=
abang MTN","","07-04-2025 22:49:10","07-04-2025 22:29:57","07-04-2025 23:17=
:57","Grid outage, Site went down because Gen overload(20, 300A) SS IHS Alp=
honse DEFFO is informed// He reduiced load and started Gen manualy","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen overload(20, 300A) SS IHS Alphonse DEFF=
O is informed// He reduiced load and started Gen manualy","gerard.tchangoue=
@matech-cameroun.com","1154","07-04-2025 22:49:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0004751542","Crf-Nkol=
bisson","","07-04-2025 22:24:20","07-04-2025 20:41:08","07-04-2025 21:18:18=
","Grid outage, site went down before gen start due to poor battery backup =
// Manual Start of Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Manual Start of Gen","c=
hristelle.ngonga@matech-cameroun.com","6193","07-04-2025 22:24:20","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0004751487","Awae Ewo=
nkan","","07-04-2025 22:12:38","07-04-2025 18:20:08","07-04-2025 19:04:31",=
"Cascaded Incident from TTO4844574","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 Gen Ovaloard(12KVa, 150A), SS IHS Alphonse DEFFO is informed // Grid retur=
n","system","286935","07-04-2025 22:12:38","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004751403","NYO=
M FACE MAETUR","","07-04-2025 22:00:33","07-04-2025 21:50:24","07-04-2025 2=
3:10:05","Site went down due to 01/03 Rectifier dysfunction// He reset it: =
site on grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to 01/03 Rectifier dysfunction// He re=
set it: site on grid","franck.nkomot@matech-cameroun.com","610","07-04-2025=
 22:00:33","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004751394","Odz=
a petit marche new","","07-04-2025 21:56:09","07-04-2025 21:01:58","07-04-2=
025 21:09:58","Rectifier issue //reduced load","Albran Byorel","Equipment R=
epair","Passive","Rectifier","Rectifier Cabinet","Rectifier issue //reduced=
 load","landry.etame@ihstowers.com","3252","07-04-2025 21:56:09","MATECH CM=
R"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004751205","N=
kozoa","","07-04-2025 21:23:20","07-04-2025 21:04:34","07-04-2025 21:27:34"=
,"Grid outage site went down because Gen overload(20KVA,340A) SS IHS F=E9li=
x Bateu is informed and Is confirmed// He reduced the load on site and star=
ted gen manualy","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage site went down because Gen overload(20KVA,34=
0A) SS IHS F=E9lix Bateu is informed and Is confirmed// He reduced the load=
 on site and started gen manualy","kouoh.jean@ihstowers.com","1127","07-04-=
2025 21:23:20","MATECH CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004751055","M=
balla 4","","07-04-2025 21:02:28","07-04-2025 20:58:21","07-04-2025 21:07:2=
1","Grid outage,Site went down before gen failed to start (investigation on=
going)","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid outage,Site went down before gen failed to start (invest=
igation ongoing)","franck.nkomot@matech-cameroun.com","248","07-04-2025 21:=
02:28","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004751025","B=
arriere IHS","","07-04-2025 20:59:05","07-04-2025 20:35:45","07-04-2025 23:=
06:15","Site went down because CB (125A) tripped in PWC who feeds equipment=
s OCM // He reduced the load","Hyemafo Gildas","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down be=
cause CB (125A) tripped in PWC who feeds equipments OCM // He reduced the l=
oad","kouoh.jean@ihstowers.com","1401","07-04-2025 20:59:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004751011","SOA TOWN=
","","07-04-2025 20:57:37","07-04-2025 20:09:08","07-04-2025 20:42:08","Cas=
caded Incident from TTO4845428","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid  fluctuation, Site went Down due =
to Poor battery backup // gen manually started and put on gen, Power issue =
resolved at 08:42 PM But Site remains Down after Power reset done ).  FME T=
XJulien (693095849) from Huawei is informed.","system","280873","07-04-2025=
 20:57:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_322","NOCINC0004751010","Soa-II",=
"","07-04-2025 20:57:37","07-04-2025 20:09:08","07-04-2025 20:42:08","Casca=
ded Incident from TTO4845428","Siligap Boris","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid  fluctuation, Site went Down due to=
 Poor battery backup // gen manually started and put on gen, Power issue re=
solved at 08:42 PM But Site remains Down after Power reset done ).  FME TXJ=
ulien (693095849) from Huawei is informed.","system","280875","07-04-2025 2=
0:57:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004751005","Ebogo","=
","07-04-2025 20:57:36","07-04-2025 20:09:08","07-04-2025 20:42:08","Cascad=
ed Incident from TTO4845428","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid  fluctuation, Site went Down due to =
Poor battery backup // gen manually started and put on gen, Power issue res=
olved at 08:42 PM But Site remains Down after Power reset done ).  FME TXJu=
lien (693095849) from Huawei is informed.","system","280873","07-04-2025 20=
:57:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_317","NOCINC0004751004","Soa-Sofa=
mac","","07-04-2025 20:57:36","07-04-2025 20:09:08","07-04-2025 20:42:08","=
Cascaded Incident from TTO4845428","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid  fluctuation, Site went Down d=
ue to Poor battery backup // gen manually started and put on gen, Power iss=
ue resolved at 08:42 PM But Site remains Down after Power reset done ).  FM=
E TXJulien (693095849) from Huawei is informed.","system","280872","07-04-2=
025 20:57:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004751006","Akak-Nko=
zoa-MTN-IHS","","07-04-2025 20:57:36","07-04-2025 20:09:08","07-04-2025 20:=
42:08","Cascaded Incident from TTO4845428","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid  fluctuation, Site w=
ent Down due to Poor battery backup // gen manually started and put on gen,=
 Power issue resolved at 08:42 PM But Site remains Down after Power reset d=
one ).  FME TXJulien (693095849) from Huawei is informed.","system","280873=
","07-04-2025 20:57:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004751007","SOA UNIV=
ERSITY STADIUM","","07-04-2025 20:57:36","07-04-2025 20:09:08","07-04-2025 =
20:42:08","Cascaded Incident from TTO4845428","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid  fluctuation, Site =
went Down due to Poor battery backup // gen manually started and put on gen=
, Power issue resolved at 08:42 PM But Site remains Down after Power reset =
done ).  FME TXJulien (693095849) from Huawei is informed.","system","28087=
4","07-04-2025 20:57:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_321","NOCINC0004751003","Soa","",=
"07-04-2025 20:57:35","07-04-2025 20:09:08","07-04-2025 20:42:08","Cascaded=
 Incident from TTO4845428","Siligap Boris","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid  fluctuation, Site went Down due to Po=
or battery backup // gen manually started and put on gen, Power issue resol=
ved at 08:42 PM But Site remains Down after Power reset done ).  FME TXJuli=
en (693095849) from Huawei is informed.","system","280876","07-04-2025 20:5=
7:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0004751002","NYOM 2 I=
HS","","07-04-2025 20:57:35","07-04-2025 20:09:08","07-04-2025 20:42:08","C=
ascaded Incident from TTO4845428","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid  fluctuation, Site went Down =
due to Poor battery backup // gen manually started and put on gen, Power is=
sue resolved at 08:42 PM But Site remains Down after Power reset done ).  F=
ME TXJulien (693095849) from Huawei is informed.","system","280876","07-04-=
2025 20:57:35","MATECH CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0004750759","S=
OA 2","IHS_YND_707, IHS_YND_321, IHS_YND_317, IHS_YND_390, IHS_YND_552, IHS=
_YND_307, IHS_YND_316, IHS_YND_351, IHS_YND_720, IHS_YND_326, IHS_YND_324, =
IHS_YND_322, IHS_YND_320","07-04-2025 20:29:17","07-04-2025 20:09:08","07-0=
4-2025 20:42:08","Grid  fluctuation, Site went Down due to Poor battery bac=
kup // gen manually started and put on gen, Power issue resolved at 08:42 P=
M But Site remains Down after Power reset done ).  FME TXJulien (693","Sili=
gap Boris","Equipment Repair","Passive","Control Panel","Power Cabinet - Ba=
ttery Low","Grid  fluctuation, Site went Down due to Poor battery backup //=
 gen manually started and put on gen, Power issue resolved at 08:42 PM But =
Site remains Down after Power reset done ).  FME TXJulien (693095849) from =
Huawei is informed.","franck.nkomot@matech-cameroun.com","1209","07-04-2025=
 20:29:17","MATECH CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004750528","B=
iteng","","07-04-2025 20:01:57","07-04-2025 19:31:49","07-04-2025 19:58:49"=
,"ZTE Dysfonction de la bay // Gen manually started","Mba Lazare Herve","Eq=
uipment Repair","Passive","Control Panel","Panel Distribution Board","ZTE D=
ysfonction de la bay // Gen manually started","kouoh.jean@ihstowers.com","1=
809","07-04-2025 20:01:57","MATECH CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0004750442","N=
koabang","","07-04-2025 19:46:02","07-04-2025 19:23:43","07-04-2025 21:45:4=
3","Active// No power issue, site is on GRID with U=3D54.3 V. The TX FME Li=
onel Adjep (655184876) from Huawei is working on site.","Mba Lazare Herve",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active// No power issue, site is on GRID with U=3D54.3 V. The T=
X FME Lionel Adjep (655184876) from Huawei is working on site.","kouoh.jean=
@ihstowers.com","1340","07-04-2025 19:46:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004750416","Afanoya"=
,"","07-04-2025 19:41:55","07-04-2025 19:03:26","07-04-2025 20:04:26","Casc=
aded Incident from TTO4844836","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down due to Gen =
overload (17KVA, 250A) // we reduce load and gen manually started. FME IHS =
Felix Zambe is inform","system","270033","07-04-2025 19:41:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004750417","Nkolfon =
Cimencam","","07-04-2025 19:41:55","07-04-2025 19:03:26","07-04-2025 20:04:=
26","Cascaded Incident from TTO4844836","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down du=
e to Gen overload (17KVA, 250A) // we reduce load and gen manually started.=
 FME IHS Felix Zambe is inform","system","270033","07-04-2025 19:41:55","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0004750415","Ahala","=
","07-04-2025 19:41:55","07-04-2025 19:03:26","07-04-2025 20:04:26","Cascad=
ed Incident from TTO4844836","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage site went down due to Gen ov=
erload (17KVA, 250A) // we reduce load and gen manually started. FME IHS Fe=
lix Zambe is inform","system","270033","07-04-2025 19:41:55","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004750261","M=
eyo","IHS_YND_257, IHS_YND_313, IHS_YND_762","07-04-2025 19:16:36","07-04-2=
025 19:03:26","07-04-2025 20:04:26","Grid outage site went down due to Gen =
overload (17KVA, 250A) // we reduce load and gen manually started. FME IHS =
Felix Zambe is inform","Hyemafo Gildas","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","Grid outage site went down due to Gen overload (17K=
VA, 250A) // we reduce load and gen manually started. FME IHS Felix Zambe i=
s inform","franck.nkomot@matech-cameroun.com","791","07-04-2025 19:16:36","=
MATECH CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004750211","Eto=
 koss Yde","","07-04-2025 19:10:04","07-04-2025 17:09:36","07-04-2025 19:15=
:36","Eneo outages Gen started but Gen contactor don't  working (Faulty) //=
 Gen contactor  replaced and gen started ","Fanda Brice","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Load Contactor","Eneo outages Gen started but=
 Gen contactor don't  working (Faulty) // Gen contactor  replaced and gen s=
tarted ","landry.etame@ihstowers.com","7230","07-04-2025 19:10:04","MATECH =
CMR"
"Closed Complete","Warning","T0029","IHS_YND_357","NOCINC0004750121","Sacre=
 Coeur Catholic Church","","07-04-2025 18:56:35","","","Site alarming due t=
o Grid outage // Grid return","Mboua Thierry","Warning","Warning","POWER","=
Warning - Grid Off","Site alarming due to Grid outage // Grid return
","franck.nkomot@matech-cameroun.com","3623","07-04-2025 18:56:35","MATECH =
CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004750085","E=
kombitie","","07-04-2025 18:50:07","07-04-2025 18:21:57","08-04-2025 00:40:=
21","Active: no power issue, site is on Grid with Ubaie:54.5V, Symphorien(6=
50257151) from Huawei is informed. ","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
no power issue, site is on Grid with Ubaie:54.5V, Symphorien(650257151) fro=
m Huawei is informed. ","kouoh.jean@ihstowers.com","1691","07-04-2025 18:50=
:07","MATECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004750062","Emo=
mbo Esssomba","","07-04-2025 18:45:49","07-04-2025 18:30:17","07-04-2025 18=
:56:17","Grid outage.site went down due to gen failed to start //grid retur=
n(investigation ongoing)","Mba Lazare Herve","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage.site went down due to gen fai=
led to start //grid return(investigation ongoing)","landry.etame@ihstowers.=
com","932","07-04-2025 18:45:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0004750044","Awae Esc=
alier","","07-04-2025 18:43:14","07-04-2025 18:20:08","07-04-2025 19:04:31"=
,"Cascaded Incident from TTO4844574","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down due t=
o Gen Ovaloard(12KVa, 150A), SS IHS Alphonse DEFFO is informed // Grid retu=
rn","system","286934","07-04-2025 18:43:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_177","NOCINC0004750040","Awae-Yde=
","IHS_YND_535, IHS_YND_171","07-04-2025 18:42:30","07-04-2025 18:20:08","0=
7-04-2025 19:04:31","Grid outage, site went down due to Gen Ovaloard(12KVa,=
 150A), SS IHS Alphonse DEFFO is informed // Grid return","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site=
 went down due to Gen Ovaloard(12KVa, 150A), SS IHS Alphonse DEFFO is infor=
med // Grid return","christelle.ngonga@matech-cameroun.com","1342","07-04-2=
025 18:42:30","MATECH CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004749937","B=
iteng","","07-04-2025 18:22:03","07-04-2025 17:11:55","07-04-2025 18:55:03"=
,"ZTE Dysfonction de la bay  // Gen manually started","Mba Lazare Herve","E=
quipment Repair","Passive","Control Panel","Panel Distribution Board","ZTE =
Dysfonction de la bay  // Gen manually started","kouoh.jean@ihstowers.com",=
"4210","07-04-2025 18:22:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004749751","SOA VILL=
AGE","","07-04-2025 17:53:12","07-04-2025 17:37:12","07-04-2025 18:23:12","=
Cascaded Incident from TTO4844223","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // He added water and manually =
start the gen","system","275126","07-04-2025 17:53:12","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004749735","S=
OA TOWN","IHS_YND_323","07-04-2025 17:51:22","07-04-2025 17:35:12","07-04-2=
025 18:23:12","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // He added water and manually start the gen","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cl=
ogged Radiator","Grid outage, site went down because gen start and stopped =
with high temp alarm // He added water and manually start the gen","franck.=
nkomot@matech-cameroun.com","972","07-04-2025 17:51:22","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004749720","C=
amp-Sic-Tsinga","","07-04-2025 17:48:43","07-04-2025 16:21:04","07-04-2025 =
16:27:04","Grid outage.no space to deploy mobile gen // grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage.no space to deploy mobile gen // grid power return","kouoh.jean@ihs=
towers.com","5260","07-04-2025 17:48:43","MATECH CMR"
"Cancelled","Warning","CTR_211","IHS_YND_248","NOCINC0004749549","Biteng","=
","07-04-2025 17:27:26","","","","Mba Lazare Herve","","","","","","franck.=
nkomot@matech-cameroun.com","22569","07-04-2025 17:27:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004749437","Angongo"=
,"","07-04-2025 17:10:22","07-04-2025 16:41:29","07-04-2025 18:42:29","Casc=
aded Incident from TTO4843846","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site Went Down due to high temp // added =
water","system","293323","07-04-2025 17:10:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004749433","Ebeba","=
IHS_YND_335","07-04-2025 17:09:40","07-04-2025 16:41:29","07-04-2025 18:42:=
29","Site Went Down due to high temp // added water","Fanda Brice","Equipme=
nt Repair","Passive","ACDG Gen","Gen Temp High","Site Went Down due to high=
 temp // added water","christelle.ngonga@matech-cameroun.com","1692","07-04=
-2025 17:09:40","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0004749382","Bar=
riere IHS","","07-04-2025 17:03:15","07-04-2025 16:48:00","07-04-2025 18:15=
:47","Gen overload /  load reduced and gen manualy started","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gen overload /=
  load reduced and gen manualy started","franck.nkomot@matech-cameroun.com"=
,"1067","07-04-2025 17:03:15","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004749352","N=
KOLMEKONG YDE","","07-04-2025 16:59:47","07-04-2025 14:24:38","07-04-2025 1=
8:32:50"," Site up, awaiting feedback","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Panel Distribution Board","Energy bay faulty //=
 power reset done on OCM bay","franck.nkomot@matech-cameroun.com","9311","0=
7-04-2025 16:59:47","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0004749274","Nko=
langaa","","07-04-2025 16:45:48","07-04-2025 15:57:29","07-04-2025 17:30:55=
","Active//No power issue on site Ubaie =3D53V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed.","Mba Lazare Herve","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site Ubaie =3D53V site on Grid The TX FME Henri (6999=
49693) from Huawei is informed.","landry.etame@ihstowers.com","2900","07-04=
-2025 16:45:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004749202","Emana Ly=
cee","","07-04-2025 16:29:53","07-04-2025 16:24:43","07-04-2025 17:38:04","=
Cascaded Incident from TTO4843556","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid low voltage, Gen did not sta=
rt // Grid restoration","system","279465","07-04-2025 16:29:53","MATECH CMR=
"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004749193","E=
mana lycee 2","IHS_YND_274","07-04-2025 16:28:49","07-04-2025 16:24:43","07=
-04-2025 17:38:04","Grid low voltage, Gen did not start // Grid restoration=
","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Low Cur=
rent Supply","Grid low voltage, Gen did not start // Grid restoration","fra=
nck.nkomot@matech-cameroun.com","247","07-04-2025 16:28:49","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004749114","ETO=
UDI Entree du palais","","07-04-2025 16:13:13","07-04-2025 16:05:03","07-04=
-2025 16:23:03","Site went down because 01/03 rectifiers dysfuncionned// He=
 reset rectifier","Fabrice Pouakam","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down because 01/03 rectifiers dysfuncionned=
// He reset rectifier","franck.nkomot@matech-cameroun.com","491","07-04-202=
5 16:13:13","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004748986","Imm=
-Olympique","","07-04-2025 15:48:25","07-04-2025 15:43:18","07-04-2025 15:5=
3:18","Active//No power issue on Site ,Site on Grid with Ubaie=3D52V The TX=
 FME Mohamadou mouam //691144435 from Huawei is informed","Paul BIBOUM","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on Site ,Site on Grid with Ubaie=3D52V The =
TX FME Mohamadou mouam //691144435 from Huawei is informed","franck.nkomot@=
matech-cameroun.com","308","07-04-2025 15:48:25","MATECH CMR"
"Closed Complete","Site Down","CTR_546","IHS_YND_419","NOCINC0004748981","N=
gog Mapubi","","07-04-2025 15:46:12","07-04-2025 15:05:04","07-04-2025 16:1=
1:30","Active// No power issue on site ,site on Gen with Ubaie=3D 54,6V The=
 fme tx Etienne fopa // 695033981 of huawei is informed	","Kemeni Franklin"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active// No power issue on site ,site on Gen with Ubaie=3D 54,=
6V The fme tx Etienne fopa // 695033981 of huawei is informed	","franck.nko=
mot@matech-cameroun.com","2469","07-04-2025 15:46:12","MATECH CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004748941","Men=
dong3","","07-04-2025 15:39:29","07-04-2025 15:38:24","07-04-2025 15:40:24"=
,"Grid outage, no space to deploy// grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage, no space to deplo=
y// grid return","franck.nkomot@matech-cameroun.com","66","07-04-2025 15:39=
:29","MATECH CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0004748913","N=
kol-Mbanda","","07-04-2025 15:33:56","07-04-2025 15:22:48","07-04-2025 17:2=
7:48","Grid outage gen ran until fuel shortage//Refueling done","MINKA NICO=
LAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran =
until fuel shortage//Refueling done","franck.nkomot@matech-cameroun.com","6=
69","07-04-2025 15:33:56","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004748900","M=
ontee-Jouvence-II","","07-04-2025 15:31:39","07-04-2025 15:20:31","07-04-20=
25 17:24:31","Grid outage, Site went down because Gen overload (15kva, 250A=
) SS IHS Felix Zambe is informed // GRid power return","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site w=
ent down because Gen overload (15kva, 250A) SS IHS Felix Zambe is informed =
// GRid power return","franck.nkomot@matech-cameroun.com","670","07-04-2025=
 15:31:39","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0004748894","C=
hapelle-Nsimeyong","","07-04-2025 15:30:25","07-04-2025 15:21:12","07-04-20=
25 17:28:12","AcTIVE: no power issue, site is on grid with Ubaie=3D54.5V, H=
osiah(699699694) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","AcTIV=
E: no power issue, site is on grid with Ubaie=3D54.5V, Hosiah(699699694) fr=
om Huawei is informed","franck.nkomot@matech-cameroun.com","553","07-04-202=
5 15:30:25","MATECH CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004748858","c=
hina embassy yde","","07-04-2025 15:22:26","07-04-2025 15:19:16","07-04-202=
5 21:22:16","Active//No power issues on Site and Ubaie=3D52.3V The FME TX E=
loundou Bertrand (693 21 24 05) is informed and the site up at =3D03:23PM",=
"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issues on Site and Ubaie=3D52.3V The FME TX=
 Eloundou Bertrand (693 21 24 05) is informed and the site up at =3D03:23PM=
","franck.nkomot@matech-cameroun.com","191","07-04-2025 15:22:26","MATECH C=
MR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004748855","A=
ccacia New","","07-04-2025 15:21:37","07-04-2025 15:19:28","07-04-2025 19:1=
9:28","Grid only site No space fo mobile gen // Grid restoration","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e No space fo mobile gen // Grid restoration","franck.nkomot@matech-camerou=
n.com","131","07-04-2025 15:21:37","MATECH CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0004748819","Jou=
vence 2000","","07-04-2025 15:14:47","07-04-2025 15:07:21","07-04-2025 15:1=
7:21","site down due to insufficient rectifiers //  reset of rectifiers, si=
te on Gen","Delor Telezing","Equipment Repair","Passive","Rectifier","Recti=
fier Module","site down due to insufficient rectifiers //  reset of rectifi=
ers, site on Gen","franck.nkomot@matech-cameroun.com","447","07-04-2025 15:=
14:47","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0004748754","ELOUMDEM=
 CARRIERE","","07-04-2025 15:06:46","07-04-2025 15:02:07","07-04-2025 15:36=
:48","Cascaded Incident from TTO4843002","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage ,gen fails to start=
 due to Alarm gen under frequency // Gen manually started
","system","284513","07-04-2025 15:06:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004748755","ELOUMDEM=
 CARRIERE 2","","07-04-2025 15:06:46","07-04-2025 15:02:07","07-04-2025 15:=
36:48","Cascaded Incident from TTO4843002","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage ,gen fails to sta=
rt due to Alarm gen under frequency // Gen manually started
","system","284512","07-04-2025 15:06:46","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004748753","ELO=
UMDEM CARRIERE","","07-04-2025 15:06:45","07-04-2025 14:50:36","07-04-2025 =
15:01:47","Grid outage .gen failed to start due to terminal battery not wel=
l tighted //We fixed very well battery terminal and gen maually started ","=
Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batt=
ery","Grid outage .gen failed to start due to terminal battery not well tig=
hted //We fixed very well battery terminal and gen maually started ","franc=
k.nkomot@matech-cameroun.com","970","07-04-2025 15:06:45","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004748743","MEF=
OU ASSI","IHS_YND_767, IHS_YND_261, IHS_YND_768","07-04-2025 15:05:14","07-=
04-2025 15:02:07","07-04-2025 17:28:37","Grid outage ,gen fails to start du=
e to Alarm gen under frequency // Gen manually started","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,gen=
 fails to start due to Alarm gen under frequency // Gen manually started
","landry.etame@ihstowers.com","189","07-04-2025 15:05:14","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004748714","B=
arriere","","07-04-2025 15:01:05","07-04-2025 14:48:52","07-04-2025 15:59:5=
2","grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // He reduced the load and gen manually=
 started","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","grid outage, Site went down because Gen overload(20kva,400 A) IH=
S SS Felix Zambe is informed and confirmed // He reduced the load and gen m=
anually started","kouoh.jean@ihstowers.com","734","07-04-2025 15:01:05","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004748707","A=
wae Ewonkan","","07-04-2025 14:58:45","07-04-2025 14:39:38","07-04-2025 16:=
51:38","Grid outage site went down due to Gen overload (20KVA, 300A) // we =
reduce load and gen manually started. FME IHS Felix Alphonse NDEFO","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage site went down due to Gen overload (20KVA, 300A) // we reduce load and=
 gen manually started. FME IHS Felix Alphonse NDEFO","kouoh.jean@ihstowers.=
com","1148","07-04-2025 14:58:45","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004748667","Men=
dong vallee","","07-04-2025 14:45:06","07-04-2025 14:25:54","07-04-2025 16:=
50:54","Grid outage site went down because Gen over load (20KVA; 300A) // G=
rid return IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site we=
nt down because Gen over load (20KVA; 300A) // Grid return IHS F=E9lix Zamb=
=E9 is informed and confirmed","gaelle.njiofack@matech-cameroun.com","1153"=
,"07-04-2025 14:45:06","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004748489","Eki=
e sud","","07-04-2025 14:12:57","07-04-2025 13:59:27","07-04-2025 15:16:03"=
,"Grid bad voltage, Dg failed to start and site went down // Grid bypassed,=
 site on DG	","Albran Byorel","Grid Supply","Passive","Grid","National Grid=
 - Phase Controller Faulty","Grid bad voltage, Dg failed to start and site =
went down // Grid bypassed, site on DG	","loic.noumsi@matech-cameroun.com",=
"811","07-04-2025 14:12:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0004748444","EBOM",""=
,"07-04-2025 14:01:34","07-04-2025 13:55:52","07-04-2025 15:12:32","Cascade=
d Incident from TTO4842646","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage.gen ran until fuel shortage//=
Refueling done","system","302944","07-04-2025 14:01:34","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0004748440","A=
hala","IHS_YND_698","07-04-2025 14:00:57","07-04-2025 13:55:52","07-04-2025=
 15:12:32","Grid outage.gen ran until fuel shortage//Refueling done","MINKA=
 NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen=
 ran until fuel shortage//Refueling done","joelle.ekessi@ihstowers.com","30=
6","07-04-2025 14:00:57","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004748364","A=
WAE OCM","","07-04-2025 13:46:52","07-04-2025 13:31:01","07-04-2025 14:20:0=
1","Site down due to poor battery backup // Site up without intervention ",=
"Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Battery Low","Site down due to poor battery backup // Site up without=
 intervention ","loic.noumsi@matech-cameroun.com","953","07-04-2025 13:46:5=
2","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004748288","A=
wae Ewonkan","","07-04-2025 13:32:19","07-04-2025 13:17:11","07-04-2025 13:=
22:05","No power issue on site Ubaie 54V site on Grid, site up without any =
intervention","Albran Byorel","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie 54V =
site on Grid, site up without any intervention","loic.noumsi@matech-camerou=
n.com","909","07-04-2025 13:32:19","MATECH CMR"
"Closed Complete","Warning","T0379","IHS_YND_473","NOCINC0004748247","Yoko =
MTN","","07-04-2025 13:25:40","","","site alarming due to Grid outage // Ge=
n start automatically","Parker Tchoup","Warning","Warning","POWER","Warning=
 - National Grid - Grid Outage Issue","site alarming due to Grid outage // =
Gen start automatically","loic.noumsi@matech-cameroun.com","1635","07-04-20=
25 13:25:40","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004748190","B=
iteng-Maetur","","07-04-2025 13:14:30","07-04-2025 13:05:13","07-04-2025 17=
:53:13","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) // He reduced the load	","Mba Lazare Herve","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site we=
nt down because Gen started and stopped due to Gen overload(20kva, 280A) //=
 He reduced the load	","loic.noumsi@matech-cameroun.com","559","07-04-2025 =
13:14:30","MATECH CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0004748161","Nsa=
m escale LP","","07-04-2025 13:10:36","07-04-2025 12:38:09","07-04-2025 14:=
08:50","Nicolas is managing to arrive on site","","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Fuel shortage // Refueling done
","gaelle.njiofack@matech-cameroun.com","278826","07-04-2025 13:10:36","MAT=
ECH CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0004748038","Nsa=
m Sofavinc","IHS_YND_732","07-04-2025 12:50:21","07-04-2025 12:38:09","07-0=
4-2025 14:08:50","Fuel shortage // Refueling done","MINKA NICOLAS","Fuel Ou=
tage","Passive","Diesel","Diesel Outage","Fuel shortage // Refueling done
","loic.noumsi@matech-cameroun.com","733","07-04-2025 12:50:21","MATECH CMR=
"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004747986","Tou=
ring Club International","","07-04-2025 12:44:15","07-04-2025 12:40:03","07=
-04-2025 13:28:00","Grid fluctuation, Site down due to Gen overload // Grid=
 Return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
er Voltage","Grid fluctuation, Site down due to Gen overload // Grid Return
","loic.noumsi@matech-cameroun.com","253","07-04-2025 12:44:15","MATECH CMR=
"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004747934","N=
KOLMEKONG YDE","","07-04-2025 12:32:32","07-04-2025 12:27:23","07-04-2025 1=
2:50:48","Site unstabe Because the PWC and rectifier dysfonction // site st=
abilized","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site unstabe Because the PWC and rectifier dysfonction // sit=
e stabilized","gaelle.njiofack@matech-cameroun.com","310","07-04-2025 12:32=
:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004747829","SOA VILL=
AGE","","07-04-2025 12:11:53","07-04-2025 12:05:16","07-04-2025 12:25:21","=
Cascaded Incident from TTO4841920","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","fme Boris (657100528/Matech) is on =
the site for work (Significant oil leakage from upper seals) // End of work=
","system","266187","07-04-2025 12:11:53","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004747826","S=
OA TOWN","IHS_YND_323","07-04-2025 12:11:13","07-04-2025 12:03:16","07-04-2=
025 12:25:56","fme Boris (657100528/Matech) is on the site for work (Signif=
icant oil leakage from upper seals) // End of work","Siligap Boris","Equipm=
ent Replacement","Passive","Planned Activity","Planned Activity - Passive",=
"fme Boris (657100528/Matech) is on the site for work (Significant oil leak=
age from upper seals) // End of work","loic.noumsi@matech-cameroun.com","47=
8","07-04-2025 12:11:13","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0004747715","A=
bome","","07-04-2025 12:02:07","07-04-2025 11:49:42","07-04-2025 14:42:42",=
"Grid outage.gen ran until fuel shortage//Refueling done","MINKA NICOLAS","=
Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until =
fuel shortage//Refueling done","loic.noumsi@matech-cameroun.com","747","07-=
04-2025 12:02:07","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004747543","Ako=
k Ndoe Yde","","07-04-2025 11:29:24","07-04-2025 11:21:17","07-04-2025 12:1=
9:33","Site down due to work done by Gildas Fongang (656040578): radiator c=
leaned // End of work","Hyemafo Gildas","Installation Activity","Passive","=
Planned Activity","Installation Activity","Site down due to work done by Gi=
ldas Fongang (656040578): radiator cleaned // End of work","loic.noumsi@mat=
ech-cameroun.com","488","07-04-2025 11:29:24","MATECH CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004747327","Nsi=
meyong Terre Rouge","","07-04-2025 10:52:15","07-04-2025 10:47:26","07-04-2=
025 13:58:27","Fuel shortage // Refueling done","MINKA NICOLAS","Fuel Outag=
e","Passive","Diesel","Diesel Outage","Fuel shortage // Refueling done
","loic.noumsi@matech-cameroun.com","290","07-04-2025 10:52:15","MATECH CMR=
"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004747173","Mon=
tee Jouvence","","07-04-2025 10:31:43","07-04-2025 10:18:25","07-04-2025 10=
:46:10","Site down due to work done by Gildas Fongang (656040578): test of =
automation // End of work","Hyemafo Gildas","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site down due to work done b=
y Gildas Fongang (656040578): test of automation // End of work","loic.noum=
si@matech-cameroun.com","799","07-04-2025 10:31:43","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004745969","B=
iteng-Maetur","","07-04-2025 06:50:23","07-04-2025 06:45:18","07-04-2025 11=
:35:51","No power issue on site Ubay 54V site on Gen Henry (699949693/Huawe=
i) is informed","Mba Lazare Herve","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubay =
54V site on Gen Henry (699949693/Huawei) is informed","joelle.ekessi@ihstow=
ers.com","306","07-04-2025 06:50:23","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004745854","Eki=
e sud","","07-04-2025 06:08:53","07-04-2025 06:05:35","07-04-2025 06:28:52"=
,"Site went Down due to Gen Overvoltage // He reduced battery charge","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","S=
ite went Down due to Gen Overvoltage // He reduces battery charge","edwige.=
kapawo@matech-cameroun.com","250","07-04-2025 06:08:53","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004745832","E=
kombitie","","07-04-2025 06:00:10","07-04-2025 05:56:55","07-04-2025 07:17:=
20","Site went down because GEN failed to start due to grid bad voltage // =
He did a bridge and the site is on grid","Fabrice Pouakam","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Site went down be=
cause GEN failed to start due to grid bad voltage // He did a bridge and th=
e site is on grid","edwige.kapawo@matech-cameroun.com","196","07-04-2025 06=
:00:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0004745710","Nkolondo=
m","","07-04-2025 05:22:42","07-04-2025 05:20:46","07-04-2025 06:49:22","Ca=
scaded Incident from TTO4839562","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause Gen failed to start due to PWC dysfonction // Grid Stabilized","syste=
m","276342","07-04-2025 05:22:42","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004745703","N=
KOLMEKONG YDE","IHS_YND_304","07-04-2025 05:21:58","07-04-2025 05:20:46","0=
7-04-2025 07:49:55","Grid fluctuation, site went down because Gen failed to=
 start due to PWC dysfonction // Grid Stabilized","Fabrice Pouakam","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Grid fluctuation, sit=
e went down because Gen failed to start due to PWC dysfonction // Grid Stab=
ilized","edwige.kapawo@matech-cameroun.com","73","07-04-2025 05:21:58","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0004745638","Nkolondo=
m","","07-04-2025 05:01:39","07-04-2025 04:58:18","07-04-2025 05:01:34","Ca=
scaded Incident from TTO4839482","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause Gen failed to start due to PWC dysfonction // Grid Stabilized","syste=
m","263073","07-04-2025 05:01:39","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004745635","N=
KOLMEKONG YDE","IHS_YND_304","07-04-2025 05:00:33","07-04-2025 04:58:18","0=
7-04-2025 05:01:34","Grid fluctuation, site went down because Gen failed to=
 start due to PWC dysfonction // Grid Stabilized","Fabrice Pouakam","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid fluct=
uation, site went down because Gen failed to start due to PWC dysfonction /=
/ Grid Stabilized","edwige.kapawo@matech-cameroun.com","136","07-04-2025 05=
:00:33","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004745585","Eki=
e sud","","07-04-2025 04:39:45","07-04-2025 04:27:22","07-04-2025 05:43:43"=
,"Grid bad voltage, Site went down Because gen fails to start due to lack o=
f 01 phase on site // He bypassed Grid and started Gen manualy","Albran Byo=
rel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid bad voltage, Site went down Because gen fails to start due to lack=
 of 01 phase on site // He bypassed Grid and started Gen manualy","edwige.k=
apawo@matech-cameroun.com","744","07-04-2025 04:39:45","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004744240","B=
iteng-Maetur","","07-04-2025 01:55:16","07-04-2025 00:57:52","07-04-2025 02=
:35:46","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) // He reduced the load","Mba Lazare Herve","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen started and stopped due to Gen overload(20kva, 280A) // =
He reduced the load ","edwige.kapawo@matech-cameroun.com","3445","07-04-202=
5 01:55:16","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004744140","N=
kolondom","","07-04-2025 01:13:10","07-04-2025 01:09:39","07-04-2025 01:16:=
02","No power issue site on grid with Ubaie: 57V Site up  Notice that site =
is mpacted by Nkolmekong yde ","Fabrice Pouakam","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","No pow=
er issue site on grid with Ubaie: 57V Site up  Notice that site is mpacted =
by Nkolmekong yde ","edwige.kapawo@matech-cameroun.com","213","07-04-2025 0=
1:13:10","MATECH CMR"
"Closed Complete","Site Down","CTR_360","IHS_YND_373","NOCINC0004744031","M=
aloun","","07-04-2025 00:19:52","07-04-2025 00:10:39","07-04-2025 00:40:36"=
,"No power issue on site U=3D54,6V site on Gen , The Tx FME Etienne/6513201=
88/ from Huawei is informed","Kemeni Franklin","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D54,6V site on Gen , The Tx FME Etienne/651320188/ from Huawei is=
 informed","edwige.kapawo@matech-cameroun.com","554","07-04-2025 00:19:52",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004743860","N=
KOLMEKONG YDE","","06-04-2025 23:35:00","06-04-2025 23:31:51","06-04-2025 2=
3:41:51","Grid fluctuation, site went down because Gen failed to start due =
to PWC dysfonction // He reset the PWC and Gen manually started","Fabrice P=
ouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Overload=
ed","Grid outage site went down because Gen failed to start due PWC dysfonc=
tion // He reset the PWC and Gen manually started","edwige.kapawo@matech-ca=
meroun.com","191","06-04-2025 23:35:00","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004743831","Odz=
a petit marche new","","06-04-2025 23:25:58","06-04-2025 15:03:35","06-04-2=
025 15:04:27","No power issue site on grid with U=3D54v Lionnel Steeve from=
 Huawei is informed we have telemetry issue in site ","Albran Byorel","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue site on grid with U=3D54v Lionnel Steeve from Huawei =
is informed we have telemetry issue in site ","ludivine.ngamaleu@ihstowers.=
com","30144","06-04-2025 23:25:58","MATECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0004743384","Soa=
","","06-04-2025 21:46:10","06-04-2025 21:40:33","06-04-2025 21:59:47","Gri=
d outage site went down because Gen failed to start due PWC dysfonction // =
He reset the PWC and Gen manually started","Siligap Boris","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","Grid outage site we=
nt down because Gen failed to start due PWC dysfonction // He reset the PWC=
 and Gen manually started","franck.nkomot@matech-cameroun.com","338","06-04=
-2025 21:46:10","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004742878","Aha=
la Echangeur","","06-04-2025 20:33:10","06-04-2025 20:07:00","06-04-2025 23=
:00:44","Site went down because GEN failed to start due to grid bad voltage=
(lack of 01 phase)and no RCP// He balanced the phase","MINKA NICOLAS","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Site went Do=
wn du to Grid  Outage // Grid returned","franck.nkomot@matech-cameroun.com"=
,"1571","06-04-2025 20:33:10","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004742842","Aka=
k-Nkozoa-MTN-IHS","","06-04-2025 20:18:28","06-04-2025 20:09:21","06-04-202=
5 22:35:52","Grid outage,gen start and stopped due to low oil pressure //We=
 add oil and gen manually started","Fabrice Pouakam","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Low Oil Pressure","Site went Down due to low oil =
pressure // Oil added","franck.nkomot@matech-cameroun.com","548","06-04-202=
5 20:18:28","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004742823","SAA Entr=
ance","","06-04-2025 20:12:11","06-04-2025 19:56:16","06-04-2025 20:22:53",=
"Cascaded Incident from TTO4836360","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause gen fails to start due to grid bad voltage // He bypassed the Grid a=
nd site on Gen","system","266663","06-04-2025 20:12:11","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004742820","Saa=
","IHS_YND_542","06-04-2025 20:11:27","06-04-2025 19:56:16","06-04-2025 20:=
22:53","Grid fluctuation, site went down because gen fails to start due to =
grid bad voltage // He bypassed the Grid and site on Gen","Parker Tchoup","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, site went down because gen fails to start due to grid bad v=
oltage // He bypassed the Grid and site on Gen","franck.nkomot@matech-camer=
oun.com","912","06-04-2025 20:11:27","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004742808","Awa=
e Ewonkan","","06-04-2025 20:07:41","06-04-2025 19:53:55","06-04-2025 22:02=
:24","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed//Grid return","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed//Grid return","=
franck.nkomot@matech-cameroun.com","850","06-04-2025 20:07:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004742759","SOA UNIV=
ERSITY STADIUM","","06-04-2025 19:57:00","06-04-2025 19:11:57","06-04-2025 =
20:11:19","Grid outage, site went down because gen failed to start due to P=
wc ZTE dysfunction// He reset it and started Gen manualy","Siligap Boris","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage, site went down because gen failed to start due to Pwc ZTE dysfunct=
ion// He reset it and started Gen manualy","system","3248","06-04-2025 19:5=
7:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0004742744","Biteng-M=
aetur","","06-04-2025 19:54:10","06-04-2025 18:44:57","06-04-2025 20:31:22"=
,"Cascaded Incident from TTO4835880 - Cascade Removed From TTO4835880  No p=
ower issue site on grid with U=3D54v Lionnel Steeve from Huaei is informed"=
,"Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Site went Down due to Eneo Outage (mayor re=
fused to start the GE) // Grid restored","system","4153","06-04-2025 19:54:=
10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0004742743","EBOM",""=
,"06-04-2025 19:54:10","06-04-2025 18:44:57","06-04-2025 20:31:22","Cascade=
d Incident from TTO4835880","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went Down due to Eneo Outage (mayor =
refused to start the GE) // Grid restored","system","285521","06-04-2025 19=
:54:10","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0004742399","Nsi=
meyong","IHS_YND_698","06-04-2025 18:52:07","06-04-2025 18:44:57","06-04-20=
25 20:31:22","ACCESS ISSUE DUE TO LANDLORD , Grid outage,gen failed to due =
to refusal by landlord to started gen//Grid return","MINKA NICOLAS","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Site went Down=
 due to Eneo Outage (mayor refused to start the GE) // Grid restored","fran=
ck.nkomot@matech-cameroun.com","430","06-04-2025 18:52:07","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004742192","Nko=
zoa","","06-04-2025 18:13:59","06-04-2025 18:08:49","06-04-2025 18:20:28","=
Grid outage site went down because Gen overload(20KVA,340A) SS IHS F=E9lix =
Bateu is informed and Is confirmed// He reduced the load on site and starte=
d gen manualy","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage site went down because Gen overload(20KVA,340A=
) SS IHS F=E9lix Bateu is informed and Is confirmed// He reduced the load o=
n site and started gen manualy","franck.nkomot@matech-cameroun.com","311","=
06-04-2025 18:13:59","MATECH CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0004742184","N=
gousso-II","","06-04-2025 18:11:33","06-04-2025 18:09:22","06-04-2025 18:11=
:39","Site went down because Gen failed to start due to PWC dysfunctionning=
// He reset PWC, Site on Grid","MFOUAGUEGUE MATHIEU","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Grid outage,site went dow=
n due to dysfunction of PWC  //up without intervention (investigation ongoi=
ng)","franck.nkomot@matech-cameroun.com","132","06-04-2025 18:11:33","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004742182","M=
ontee-Jouvence-II","","06-04-2025 18:09:52","06-04-2025 17:56:34","06-04-20=
25 18:00:58","ACTIVE// No power issue on site, site on Grid with Ubaie=3D 5=
4V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed.","Hyemafo G=
ildas","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE// No power issue on site, site on Grid with Ubaie=
=3D 54V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed.","fran=
ck.nkomot@matech-cameroun.com","799","06-04-2025 18:09:52","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004741964","C=
rf-Nkolbisson","","06-04-2025 17:35:47","06-04-2025 17:11:41","06-04-2025 1=
7:53:03","Site went down because of CB(125A) in PWC due to load increase//H=
e reamed the CB","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","R=
ectifier","Rectifier Cabinet","Site went down because of CB(125A) in PWC du=
e to load increase//He reamed the CB","franck.nkomot@matech-cameroun.com","=
1447","06-04-2025 17:35:47","MATECH CMR"
"Closed Complete","Site Down","T0211","IHS_YND_393","NOCINC0004741852","Eze=
zang","","06-04-2025 17:18:56","06-04-2025 17:09:42","06-04-2025 17:53:51",=
"Site went Down due to fuel filter was clogged due to dirt at the bottom of=
 the tank. // We cleaned and put the generator back into service.","Parker =
Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Filter","Site =
went Down due to fuel filter was clogged due to dirt at the bottom of the t=
ank. // We cleaned and put the generator back into service.","franck.nkomot=
@matech-cameroun.com","598","06-04-2025 17:18:56","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0004741557","C=
NR","","06-04-2025 16:35:39","06-04-2025 16:21:27","06-04-2025 16:30:17","N=
o power issue site on grid with U=3D53.4V Mohamadou from Huaie is informed"=
,"Mboua Thierry","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.4V Moh=
amadou from Huaie is informed","franck.nkomot@matech-cameroun.com","852","0=
6-04-2025 16:35:39","MATECH CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004741444","ODZ=
A CITE MBIA","","06-04-2025 16:22:59","06-04-2025 16:16:53","06-04-2025 16:=
42:24","Grid fluctuation, Site went down because Gen failed to start due to=
 Grid bad voltage // Grid stabilized","Albran Byorel","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site=
 went down because Gen failed to start due to Grid bad voltage // Grid stab=
ilized","franck.nkomot@matech-cameroun.com","367","06-04-2025 16:22:59","MA=
TECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0004741409","ELO=
UMDEM CARRIERE 2","","06-04-2025 16:15:48","06-04-2025 16:11:34","06-04-202=
5 16:20:54","ACTIVE//no power issue Ubaie:54.2V site on Gen, TX fme symphor=
ien /650257151 from huawei is informed","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//n=
o power issue Ubaie:54.2V site on Gen, TX fme symphorien /650257151 from hu=
awei is informed","franck.nkomot@matech-cameroun.com","255","06-04-2025 16:=
15:48","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004741402","M=
EFOU ASSI","","06-04-2025 16:13:56","06-04-2025 16:09:40","06-04-2025 16:55=
:38","Grid outage, Site went down because Gen failed to start due to PWC dy=
sfunctionning// He reset it and manually start the Gen","Fanda Brice","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid out=
age, Site went down because Gen failed to start due to PWC dysfunctionning/=
/ He reset it and manually start the Gen","franck.nkomot@matech-cameroun.co=
m","258","06-04-2025 16:13:56","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004741380","B=
arriere","","06-04-2025 16:11:55","06-04-2025 16:06:41","06-04-2025 23:00:2=
9","grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Fe=
lix Zambe is informed and confirmed // He reduced the load and gen manually=
 started","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","grid outage, Site went down because Gen overload(20kva,400 A) IH=
S SS Felix Zambe is informed and confirmed // He reduced the load and gen m=
anually started","franck.nkomot@matech-cameroun.com","315","06-04-2025 16:1=
1:55","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004741314","Mon=
tee Jouvence","","06-04-2025 15:57:11","06-04-2025 15:33:04","06-04-2025 16=
:26:44","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started manually","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Gen started manually","franck.nkomot@matec=
h-cameroun.com","1448","06-04-2025 15:57:11","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004741293","M=
arche Odza","","06-04-2025 15:54:16","06-04-2025 15:48:05","06-04-2025 17:2=
8:13","Site went down due to PSC3 Controller dysfunctionning// He reset it"=
,"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Site went down due to PSC3 Controller dysfunctionning// He reset it",=
"franck.nkomot@matech-cameroun.com","373","06-04-2025 15:54:16","MATECH CMR=
"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004741227","UPA=
C LP","","06-04-2025 15:46:38","06-04-2025 15:27:32","06-04-2025 16:07:27",=
"Grid outage,no space to deploy MDG // Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage,no space to dep=
loy MDG // Grid return","franck.nkomot@matech-cameroun.com","1147","06-04-2=
025 15:46:38","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004741224","Ako=
k Ndoe Yde","","06-04-2025 15:45:59","06-04-2025 15:23:37","06-04-2025 16:1=
3:04","Grid outage, Site down due to poor battery backup // Gen started man=
ually","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, Site down due to poor battery backup =
// Gen started manually","franck.nkomot@matech-cameroun.com","1343","06-04-=
2025 15:45:59","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004741087","Mom","",=
"06-04-2025 15:30:11","06-04-2025 15:14:31","06-04-2025 15:20:31","Cascaded=
 Incident from TTO4834258","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Active//No power issue, site is on Grid with Uba=
ie=3D52,3V,Etienne (695033981) from Huawei is informed.Noticed impacted by =
Ngoumou","system","269406","06-04-2025 15:30:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004741088","Akono","=
","06-04-2025 15:30:11","06-04-2025 15:14:31","06-04-2025 15:20:31","Cascad=
ed Incident from TTO4834258","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue, site is on Grid with U=
baie=3D52,3V,Etienne (695033981) from Huawei is informed.Noticed impacted b=
y Ngoumou","system","269405","06-04-2025 15:30:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004741086","Minka","=
","06-04-2025 15:30:10","06-04-2025 15:14:31","06-04-2025 15:20:31","Cascad=
ed Incident from TTO4834258","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue, site is on Grid with U=
baie=3D52,3V,Etienne (695033981) from Huawei is informed.Noticed impacted b=
y Ngoumou","system","269405","06-04-2025 15:30:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004741085","OKOA Pea=
ge","","06-04-2025 15:30:10","06-04-2025 15:14:31","06-04-2025 15:20:31","C=
ascaded Incident from TTO4834258","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue, site is on Grid w=
ith Ubaie=3D52,3V,Etienne (695033981) from Huawei is informed.Noticed impac=
ted by Ngoumou","system","269405","06-04-2025 15:30:10","MATECH CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004741011","OTE=
LE MTN","IHS_YND_330, IHS_YND_371, IHS_YND_370, IHS_YND_365","06-04-2025 15=
:25:26","06-04-2025 15:14:31","06-04-2025 15:20:31","Active//No power issue=
, site is on Grid with Ubaie=3D52,3V,Etienne (695033981) from Huawei is inf=
ormed.Noticed impacted by Ngoumou","Fanda Brice","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","Active=
//No power issue, site is on Grid with Ubaie=3D52,3V,Etienne (695033981) fr=
om Huawei is informed.Noticed impacted by Ngoumou","franck.nkomot@matech-ca=
meroun.com","656","06-04-2025 15:25:26","MATECH CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0004740954","OLA=
MA","","06-04-2025 15:15:48","06-04-2025 15:14:24","06-04-2025 15:20:45","A=
ctive//No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (=
699949693) from Huawei is informed","Fanda Brice","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No po=
wer issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949693) f=
rom Huawei is informed","franck.nkomot@matech-cameroun.com","85","06-04-202=
5 15:15:48","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004740949","Nko=
g-Edzen","","06-04-2025 15:13:55","06-04-2025 14:57:42","06-04-2025 16:01:4=
4","Grid outage site went down because Gen failed to start due PWC dysfonct=
ion // He reset the PWC and Gen manually started","Parker Tchoup","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage =
site went down because Gen failed to start due PWC dysfonction // He reset =
the PWC and Gen manually started","franck.nkomot@matech-cameroun.com","974"=
,"06-04-2025 15:13:55","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004740809","N=
yom OCM","","06-04-2025 14:49:03","06-04-2025 14:30:54","06-04-2025 14:40:1=
5","ACTIVE//no power issue Ubaie:54.2V site on Gen, TX fme symphorien /6502=
57151 from huawei is informed","Fabrice Pouakam","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no pow=
er issue Ubaie:54.2V site on Gen, TX fme symphorien /650257151 from huawei =
is informed","cedric.tiani@matech-cameroun.com","1090","06-04-2025 14:49:03=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004740504","SOA VILL=
AGE","","06-04-2025 14:03:31","06-04-2025 14:01:43","06-04-2025 14:03:43","=
Cascaded Incident from TTO4833668","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down before =
Gen start due to poor backup // Gen start automatically","system","266593",=
"06-04-2025 14:03:31","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004740499","SOA=
 TOWN","IHS_YND_323","06-04-2025 14:02:53","06-04-2025 14:01:43","06-04-202=
5 14:03:43","Grid outage, Site went down before Gen start due to poor backu=
p // Gen start automatically","Siligap Boris","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup // Gen start automatically","cedric.tia=
ni@matech-cameroun.com","71","06-04-2025 14:02:53","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004740458","Men=
dong vallee","","06-04-2025 13:56:30","06-04-2025 13:53:24","06-04-2025 13:=
56:24","Grid outage site went down because Gen over load (20KVA; 300A) // G=
rid return IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site we=
nt down because Gen over load (20KVA; 300A) // Grid return IHS F=E9lix Zamb=
=E9 is informed and confirmed","landry.etame@ihstowers.com","187","06-04-20=
25 13:56:30","MATECH CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004740451","ELO=
UMDEM CARRIERE","","06-04-2025 13:55:32","06-04-2025 13:48:23","06-04-2025 =
13:59:44","Grid outage,site went down because gen failed to start //grid re=
turn(investigation ongoing)","Fanda Brice","Grid Supply","Passive","Grid","=
National Grid - Grid Outage Issue","Grid outage,site went down because gen =
failed to start //grid return(investigation ongoing)","landry.etame@ihstowe=
rs.com","431","06-04-2025 13:55:32","MATECH CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0004740416","C=
rf Cornier","","06-04-2025 13:50:12","06-04-2025 13:47:50","06-04-2025 14:0=
0:47","No power issue ste on grid with U=3D54v Armand Nguetsa frm Huaei isi=
nformed","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue ste on grid with U=3D54=
v Armand Nguetsa frm Huaei isinformed","cedric.tiani@matech-cameroun.com","=
143","06-04-2025 13:50:12","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004740382","O=
lembe-Terminus","","06-04-2025 13:46:25","06-04-2025 12:17:12","06-04-2025 =
13:05:45","Grid fluctuation, site went down because gen fails to start due =
to grid bad voltage // He bypassed the Grid and site on Gen","Fabrice Pouak=
am","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because gen fails to start due to grid =
bad voltage // He bypassed the Grid and site on Gen","cedric.tiani@matech-c=
ameroun.com","5355","06-04-2025 13:46:25","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004740368","E=
ssomba","","06-04-2025 13:42:51","06-04-2025 13:39:38","06-04-2025 13:56:07=
","Site went down because 03/06 rectifiers dysfunctionned// He reset it and=
 site ogrid ","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down because 03/06 rectifiers dysfunctionned//=
 He reset it and site ogrid ","kouoh.jean@ihstowers.com","194","06-04-2025 =
13:42:51","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004740364","ETO=
UDI Entree du palais","","06-04-2025 13:41:24","06-04-2025 13:34:59","06-04=
-2025 13:42:53","Site went down because 01/03 rectifiers dysfuncionned// He=
 reset rectifier","Fabrice Pouakam","Equipment Repair","Passive","Rectifier=
","Rectifier Module","site down due to 1 out of 3 rectifiers crashed // rec=
tifier reset","gerard.tchangoue@matech-cameroun.com","386","06-04-2025 13:4=
1:24","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004740270","Bas=
tos-BAT","","06-04-2025 13:26:27","06-04-2025 13:19:22","07-04-2025 02:42:2=
8","Active// No power issue, site is on grid with Ubaie=3D54,9 V The Tx Fme=
, Eloundou(652586578) from Huawei is informed","Mboua Thierry","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power issue, site is on grid with Ubaie=3D54,9 V The Tx Fme, El=
oundou(652586578) from Huawei is informed","landry.etame@ihstowers.com","42=
5","06-04-2025 13:26:27","MATECH CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0004740265","Dra=
gage","","06-04-2025 13:26:03","06-04-2025 13:19:00","06-04-2025 13:22:00",=
"Active//No power issue, site is on Gen with Ubaie=3D55V, Eloundou bertrant=
(652586578) from Huawei is informed","Mboua Thierry","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue, site is on Gen with Ubaie=3D55V, Eloundou bertrant(652586578)=
 from Huawei is informed","landry.etame@ihstowers.com","424","06-04-2025 13=
:26:03","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0004740262","ARM=
P Building","","06-04-2025 13:25:43","06-04-2025 13:19:38","06-04-2025 13:2=
6:38","Grid outage gen failed to start due to autmation malfunctionning//ge=
n manually started ","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","ATS-AMF Issue","Grid outage gen failed to start due to autmation ma=
lfunctionning//gen manually started ","landry.etame@ihstowers.com","366","0=
6-04-2025 13:25:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0004740260","Nkolondo=
m","","06-04-2025 13:25:21","06-04-2025 13:23:32","06-04-2025 13:53:13","Ca=
scaded Incident from TTO4833380","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC dysfonction // He reset the PWC and Gen manuall=
y started","system","290403","06-04-2025 13:25:21","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004740253","N=
KOLMEKONG YDE","IHS_YND_304","06-04-2025 13:24:40","06-04-2025 13:23:32","0=
6-04-2025 13:53:13","Grid outage site went down because Gen failed to start=
 due PWC dysfonction // He reset the PWC and Gen manually started","Fabrice=
 Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Overlo=
aded","Grid outage site went down because Gen failed to start due PWC dysfo=
nction // He reset the PWC and Gen manually started","kouoh.jean@ihstowers.=
com","69","06-04-2025 13:24:40","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004740171","M=
essassi 2","","06-04-2025 13:13:17","06-04-2025 13:11:03","06-04-2025 13:32=
:03","Site went down because 01/05 rectifiers dysfuncionned// He reset rect=
ifier","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site down due to 01 out of 05 rectifiers crashed // We did a res=
et","cedric.tiani@matech-cameroun.com","136","06-04-2025 13:13:17","MATECH =
CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004740060","E=
MANA BILICK CITY","","06-04-2025 12:54:36","06-04-2025 12:39:27","06-04-202=
5 12:57:50","Grid outage.gen failed to start due to automation malfunctionn=
ing//Gen manually started ","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","ATS-AMF Issue","Grid outage.gen failed to start due to aut=
omation malfunctionning//Gen manually started ","kouoh.jean@ihstowers.com",=
"911","06-04-2025 12:54:36","MATECH CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004739953","M=
ini-Ferme","","06-04-2025 12:42:30","06-04-2025 12:17:19","06-04-2025 12:50=
:19","	grid outage, no space to deploy a mobile gen// grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","	grid outage=
, no space to deploy a mobile gen// grid return","cedric.tiani@matech-camer=
oun.com","1512","06-04-2025 12:42:30","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004739942","E=
mana lycee 2","IHS_YND_274","06-04-2025 12:41:14","06-04-2025 12:36:03","06=
-04-2025 13:15:10","Grid outage, Site went down before Gen start due to poo=
r backup // Gen start automatically","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site w=
ent down before Gen start due to poor backup // Gen start automatically","k=
ouoh.jean@ihstowers.com","312","06-04-2025 12:41:14","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004739925","E=
mana Lycee","","06-04-2025 12:39:40","06-04-2025 12:36:03","06-04-2025 13:1=
5:10","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen start automatically","kouoh.jean@ihstowers.com","1228245","06-0=
4-2025 12:39:40","MATECH CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004739910","B=
iyemassi LAC","","06-04-2025 12:37:18","06-04-2025 12:31:13","07-04-2025 06=
:48:28","grid outage, no space to deploy a mobile gen// grid return","","Eq=
uipment Repair","Passive","Control Panel","BTS Breaker Tripped","site down =
due to disjunction in the BTS Orange // CB rearmed","cedric.tiani@matech-ca=
meroun.com","366","06-04-2025 12:37:18","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004739775","B=
iteng-Maetur","","06-04-2025 12:23:20","06-04-2025 12:21:13","06-04-2025 12=
:31:13","No power issue site on Grid with U=3D54v Flubert(654266068) from H=
uawei is informed,","Mba Lazare Herve","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on G=
rid with U=3D54v Flubert(654266068) from Huawei is informed,","gerard.tchan=
goue@matech-cameroun.com","129","06-04-2025 12:23:20","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004739763","C=
RH-Etoug-Ebe","","06-04-2025 12:22:00","06-04-2025 12:18:36","06-04-2025 12=
:32:36","","Hyemafo Gildas","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Grid outage, site went down before =
gen start due to poor battery backup // Gen start automatically","gerard.tc=
hangoue@matech-cameroun.com","205","06-04-2025 12:22:00","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004739742","S=
atcom","","06-04-2025 12:20:00","06-04-2025 12:17:44","06-04-2025 13:19:26"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D51V .The Tx Fme Arma=
nd nguetsa(691144412) From huawei is informed.","Delor Telezing","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D51V .The Tx Fme Arma=
nd nguetsa(691144412) From huawei is informed.","gerard.tchangoue@matech-ca=
meroun.com","137","06-04-2025 12:20:00","MATECH CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004739721","D=
amas","","06-04-2025 12:16:38","06-04-2025 12:03:26","06-04-2025 12:07:26",=
"Active//No power issue on site ,site on Grid with Ubaie=3D54.3 V he FME Th=
e TX FME Mbah Hosiah (674007438) is informed","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site ,site on Grid with Ubaie=3D54.3 V he FME The =
TX FME Mbah Hosiah (674007438) is informed","cedric.tiani@matech-cameroun.c=
om","12904","06-04-2025 12:16:38","MATECH CMR"
"Cancelled","Warning","CTR_074","IHS_YND_166","NOCINC0004739720","Damas",""=
,"06-04-2025 12:16:36","","","Active//No power issue on site ,site on Grid =
with Ubaie=3D54.3 V he FME The TX FME Mbah Hosiah (674007438) is informed",=
"MINKA NICOLAS","","","","","","gerard.tchangoue@matech-cameroun.com","789"=
,"06-04-2025 12:16:36","MATECH CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0004739715","A=
RMP","","06-04-2025 12:15:19","06-04-2025 12:14:03","06-04-2025 13:20:25","=
Grid outage gen failed to start due to automation malfunctionning//Gen manu=
ally started","","Equipment Repair","Passive","Control Panel","ATS-AMF Issu=
e","Grid outage gen failed to start due to automation malfunctionning//Gen =
manually started","gerard.tchangoue@matech-cameroun.com","77","06-04-2025 1=
2:15:19","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004739704","M=
ontee-Jouvence-II","","06-04-2025 12:13:47","06-04-2025 12:04:23","06-04-20=
25 12:10:52","ACTIVE// No power issue on site, site on Grid with Ubaie=3D54=
.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informe","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","ACTIVE// No power issue on site, site on Grid with Ubaie=
=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informe","gerar=
d.tchangoue@matech-cameroun.com","565","06-04-2025 12:13:47","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004739697","Crf=
-Mbankolo-IHS","","06-04-2025 12:12:34","06-04-2025 12:08:15","06-04-2025 1=
2:54:15","Grid outage, site went down due to Gen overload(15kva,240A), Bern=
ar IHS is informed//He reduced the load and site on Gen","Mboua Thierry","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site =
went down due to Gen overload(15kva,240A), Bernar IHS is informed//He reduc=
ed the load and site on Gen","gerard.tchangoue@matech-cameroun.com","260","=
06-04-2025 12:12:34","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004739686","A=
ccacia New","","06-04-2025 12:10:34","06-04-2025 12:04:15","06-04-2025 17:4=
3:05","Grid outage.no space to deploy mobile gen //Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deploy mobile gen //Grid return","gerard.tchangoue@matech-cameroun=
.com","381","06-04-2025 12:10:34","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004739599","A=
WAE OCM","","06-04-2025 11:51:03","06-04-2025 11:45:32","06-04-2025 11:57:3=
2","Grid outage, Site went down before Gen start due to poor backup // Gen =
start automatically","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Gen start automatically","cedric.tiani@mat=
ech-cameroun.com","332","06-04-2025 11:51:03","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004739292","A=
wae Ewonkan","","06-04-2025 10:46:03","06-04-2025 10:43:51","06-04-2025 10:=
45:05","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed//Grid return","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed//Grid return"=
,"gerard.tchangoue@matech-cameroun.com","133","06-04-2025 10:46:03","MATECH=
 CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004739260","Ole=
mbe MTN","","06-04-2025 10:38:11","06-04-2025 10:36:02","06-04-2025 10:46:4=
8","Site went down because insufficient of rectifier on site SS IHS felix b=
ateu is informed//Grid return","Fabrice Pouakam","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down because insufficient of r=
ectifier on site SS IHS felix bateu is informed//Grid return","cedric.tiani=
@matech-cameroun.com","130","06-04-2025 10:38:11","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004739210","E=
vodoula OCM","","06-04-2025 10:24:25","06-04-2025 10:16:12","06-04-2025 10:=
17:20","No power issue site on grid with U=3D54v Takam Krislin(694434993) f=
rom SIMIDEBIS is working on site","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue site on grid with U=3D54v Takam Krislin(694434993) from SIMIDE=
BIS is working on site","cedric.tiani@matech-cameroun.com","494","06-04-202=
5 10:24:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004739105","Mom","",=
"06-04-2025 10:08:53","06-04-2025 10:02:54","06-04-2025 10:03:47","Cascaded=
 Incident from TTO4832042","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on grid with U=3D54v Site is=
 impacted by Ngoumou who is not our responsability","system","266269","06-0=
4-2025 10:08:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004739104","Minka","=
","06-04-2025 10:08:53","06-04-2025 10:02:54","06-04-2025 10:03:47","Cascad=
ed Incident from TTO4832042","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability","system","266268","06=
-04-2025 10:08:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004739103","Angongo"=
,"","06-04-2025 10:08:52","06-04-2025 10:02:54","06-04-2025 10:03:47","Casc=
aded Incident from TTO4832042","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on grid with U=3D54v Sit=
e is impacted by Ngoumou who is not our responsability","system","266268","=
06-04-2025 10:08:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004739100","OKOA Pea=
ge","","06-04-2025 10:08:52","06-04-2025 10:02:54","06-04-2025 10:03:47","C=
ascaded Incident from TTO4832042","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on grid with U=3D54v =
Site is impacted by Ngoumou who is not our responsability","system","266267=
","06-04-2025 10:08:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004739101","OLAMA","=
","06-04-2025 10:08:52","06-04-2025 10:02:54","06-04-2025 10:03:47","Cascad=
ed Incident from TTO4832042","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Site =
is impacted by Ngoumou who is not our responsability","system","266270","06=
-04-2025 10:08:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004739102","OTELE MT=
N","","06-04-2025 10:08:52","06-04-2025 10:02:54","06-04-2025 10:03:47","Ca=
scaded Incident from TTO4832042","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on grid with U=3D54v S=
ite is impacted by Ngoumou who is not our responsability","system","266269"=
,"06-04-2025 10:08:52","MATECH CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004739086","Ako=
no","IHS_YND_330, IHS_YND_687, IHS_YND_531, IHS_YND_335, IHS_YND_371, IHS_Y=
ND_370","06-04-2025 10:05:19","06-04-2025 10:02:54","06-04-2025 10:03:47","=
No power issue site on grid with U=3D54v Site is impacted by Ngoumou who is=
 not our responsability.Henri (699949693) from Huawei is informed.","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue site on grid with U=3D54v Site is impacte=
d by Ngoumou who is not our responsability","cedric.tiani@matech-cameroun.c=
om","146","06-04-2025 10:05:19","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004739015","N=
goulmekong-Nord","","06-04-2025 09:55:23","06-04-2025 09:51:59","06-04-2025=
 09:54:59","Site went down due to insufficiency of rectifiers on site // He=
 reduced the load","Siligap Boris","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to insufficiency of rectifiers on s=
ite // He reduced the load","gerard.tchangoue@matech-cameroun.com","205","0=
6-04-2025 09:55:23","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004738910","N=
goulmekong-Nord","","06-04-2025 09:41:28","06-04-2025 09:19:20","06-04-2025=
 09:25:57","Site went down due to insufficiency of rectifiers on site  // H=
e reduced the load","Siligap Boris","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down due to insufficiency of rectifiers on =
site  // He reduced the load","cedric.tiani@matech-cameroun.com","1329","06=
-04-2025 09:41:28","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0004738761","Nko=
mo stade","","06-04-2025 09:29:14","06-04-2025 09:23:59","06-04-2025 09:41:=
59","Site went down due to insufficiency of rectifiers on site  // He reduc=
ed the load","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to insufficiency of rectifiers on site=
  // He reduced the load","gerard.tchangoue@matech-cameroun.com","316","06-=
04-2025 09:29:14","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004738681","N=
KOLMEKONG YDE","","06-04-2025 09:18:49","06-04-2025 09:12:19","06-04-2025 0=
9:14:20","Grid outage site went down because Gen failed to start due PWC dy=
sfonction // He reset the PWC and Gen manually started","Fabrice Pouakam","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage site went down because Gen failed to start due PWC dysfonction // H=
e reset the PWC and Gen manually started","cedric.tiani@matech-cameroun.com=
","392","06-04-2025 09:18:49","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004738272","N=
kolbong","","06-04-2025 08:23:11","06-04-2025 08:18:35","06-04-2025 08:23:5=
7","Grid outage.site went down due to gen failed to start //Grid return(inv=
estigation ongoing)","Delor Telezing","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage.site went down due to gen failed to =
start //Grid return(investigation ongoing)","cedric.tiani@matech-cameroun.c=
om","315","06-04-2025 08:23:11","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004737673","O=
LAMA","","06-04-2025 06:08:14","06-04-2025 05:58:53","06-04-2025 06:00:48",=
"Active//No power issue on site Ubaie =3D54.9V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.9V site on Grid The TX FME Henri (69994969=
3) from Huawei is informed","rouselle.schoune@ihstowers.com","562","06-04-2=
025 06:08:14","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004737659","E=
kombitie","","06-04-2025 05:59:52","06-04-2025 05:37:39","06-04-2025 06:00:=
58","No power issue site on gen with U=3D54.5V site on Gen THE TX Synphorie=
n 691316854 of Huawei is informed","Fabrice Pouakam","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue site on gen with U=3D54.5V site on Gen THE TX Synphorien 691316854 of =
Huawei is informed","cedric.tiani@matech-cameroun.com","1335","06-04-2025 0=
5:59:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004737198","Abattoir=
","","06-04-2025 03:19:31","06-04-2025 02:23:39","06-04-2025 03:19:38","Cas=
caded Incident from TTO4829984","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to PWC dysfunctio=
nning, // He Reset it and site is on Grid","system","3352","06-04-2025 03:1=
9:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004737199","ETOUDI C=
HAPELLE","","06-04-2025 03:19:31","06-04-2025 02:23:39","06-04-2025 03:19:3=
8","Cascaded Incident from TTO4829984","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down due to PWC dysf=
unctionning, // He Reset it and site is on Grid","system","3352","06-04-202=
5 03:19:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0004737200","Etoudi 2=
","","06-04-2025 03:19:31","06-04-2025 02:23:39","06-04-2025 03:19:38","Cas=
caded Incident from TTO4829984","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to PWC dysfunctio=
nning, // He Reset it and site is on Grid","system","3352","06-04-2025 03:1=
9:31","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004737129","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","06-04-2025 02:46:45","06-04-2=
025 02:23:39","06-04-2025 03:19:38","site went down due to PWC dysfunctionn=
ing, // He Reset it and site is on Grid","Fabrice Pouakam","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","site went down due =
to PWC dysfunctionning, // He Reset it and site is on Grid","cedric.tiani@m=
atech-cameroun.com","1387","06-04-2025 02:46:45","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004736970","Ron=
d Point Express1114","","06-04-2025 01:57:40","06-04-2025 01:48:31","06-04-=
2025 02:40:54","Active: No power issue, site is on grid with Ubaie=3D54,5V,=
 Mbah hosiah(699699694) from Huawei is informed ","Hyemafo Gildas","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active: No power issue, site is on grid with Ubaie=3D54,5V, Mbah hosiah=
(699699694) from Huawei is informed ","cedric.tiani@matech-cameroun.com","5=
49","06-04-2025 01:57:40","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004736710","Odz=
a petit marche new","","06-04-2025 00:39:52","06-04-2025 00:13:44","06-04-2=
025 03:45:09","grid outage,gen failed to start due to grid bad voltage,no r=
cp//he did a bridge on good phase","Albran Byorel","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","grid outage,gen failed to=
 start due to grid bad voltage,no rcp//he did a bridge on good phase","cedr=
ic.tiani@matech-cameroun.com","1568","06-04-2025 00:39:52","MATECH CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004736695","C=
amp-Sic-Tsinga","","06-04-2025 00:33:32","06-04-2025 00:29:25","06-04-2025 =
02:56:21","Grid outage.no space to deploy mobile gen // grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage.no space to deploy mobile gen // grid power return","cedric.tiani@m=
atech-cameroun.com","249","06-04-2025 00:33:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004736630","Donga","=
","06-04-2025 00:19:25","05-04-2025 23:54:48","06-04-2025 00:10:55","Cascad=
ed Incident from TTO4829351","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active //No power issue, site on Battery wit=
h Ubaie=3D50,4V, The TX FME Gregoire (654547479) from Huawei is informed. N=
otice that Site is impacted by Mbanjock camrail","system","266868","06-04-2=
025 00:19:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004736631","Dong",""=
,"06-04-2025 00:19:25","05-04-2025 23:54:48","06-04-2025 00:10:55","Cascade=
d Incident from TTO4829351","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active //No power issue, site on Battery with=
 Ubaie=3D50,4V, The TX FME Gregoire (654547479) from Huawei is informed. No=
tice that Site is impacted by Mbanjock camrail","system","266867","06-04-20=
25 00:19:25","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004736577","Aka=
k-Nkozoa-MTN-IHS","","06-04-2025 00:03:26","05-04-2025 23:55:16","06-04-202=
5 00:05:16","site went down due to PWC dysfunctionning, // He Reset it and =
site is on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module Overloaded","site went down due to PWC dysfunctionning, =
// He Reset it and site is on Grid","cedric.tiani@matech-cameroun.com","491=
","06-04-2025 00:03:26","MATECH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0004736574","O=
ssombe","IHS_YND_431, IHS_YND_443, IHS_YND_432, IHS_YND_434, IHS_YND_444","=
06-04-2025 00:02:14","05-04-2025 23:54:48","06-04-2025 00:10:55","Active //=
No power issue, site on Battery with Ubaie=3D50,4V, The TX FME Gregoire (65=
4547479) from Huawei is informed. Notice that Site is impacted by Mbanjock =
camrail","Parker Tchoup","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active //No power issue, site on Batte=
ry with Ubaie=3D50,4V, The TX FME Gregoire (654547479) from Huawei is infor=
med. Notice that Site is impacted by Mbanjock camrail","cedric.tiani@matech=
-cameroun.com","447","06-04-2025 00:02:14","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004736150","B=
iteng-Maetur","","05-04-2025 22:07:02","05-04-2025 19:40:49","05-04-2025 22=
:22:01","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) // He reduced the load","Mba Lazare Herve","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen started and stopped due to Gen overload(20kva, 280A) // =
He reduced the load","olivier.kwedi@ihstowers.com","8775","05-04-2025 22:07=
:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004736136","Akono","=
","05-04-2025 22:00:00","05-04-2025 21:48:56","05-04-2025 22:10:26","Cascad=
ed Incident from TTO4828822","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169)  no manager by IHS","system","274455","05-04-2025 22:00:0=
0","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004736135","Minka","=
","05-04-2025 22:00:00","05-04-2025 21:48:56","05-04-2025 22:10:26","Cascad=
ed Incident from TTO4828822","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169)  no manager by IHS","system","274456","05-04-2025 22:00:0=
0","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004736133","OLAMA","=
","05-04-2025 21:59:59","05-04-2025 21:48:56","05-04-2025 22:10:26","Cascad=
ed Incident from TTO4828822","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by Ngoumou(T0169)  no manager by IHS","system","274455","05-04-2025 21:59:5=
9","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004736134","OTELE MT=
N","","05-04-2025 21:59:59","05-04-2025 21:48:56","05-04-2025 22:10:26","Ca=
scaded Incident from TTO4828822","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue site on Grid with U=
=3D53,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impac=
ted by Ngoumou(T0169)  no manager by IHS","system","274456","05-04-2025 21:=
59:59","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004736125","Mom=
","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_365","05-04-2025 21:59:01=
","05-04-2025 21:48:56","06-04-2025 00:20:07","Active//No power issue site =
on Grid with U=3D53,3 V The FME TX Etienne(695033981) From Huawei is inform=
ed. Site impacted by Ngoumou(T0169)  no manager by IHS","Fanda Brice","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue site on Grid with U=3D53,3 V The FME TX Etien=
ne(695033981) From Huawei is informed. Site impacted by Ngoumou(T0169)  no =
manager by IHS","ludivine.ngamaleu@ihstowers.com","607","05-04-2025 21:59:0=
1","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004736046","Eto=
udi","","05-04-2025 21:45:31","05-04-2025 21:39:20","05-04-2025 22:21:11","=
site went down due to PWC dysfunctionning, // He Reset it and site is on Gr=
id","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","site went down due to PWC dysfunctionning, // He Reset i=
t and site is on Grid","ludivine.ngamaleu@ihstowers.com","372","05-04-2025 =
21:45:31","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004736029","NYO=
M FACE MAETUR","","05-04-2025 21:41:19","05-04-2025 21:35:55","06-04-2025 0=
0:49:12","Grid outage,site went down because Grid contactor did not excited=
//He excited and site on Grid ","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","ATS-AMF Issue","Grid outage,site went down because Gri=
d contactor did not excited//He excited and site on Grid ","franck.nkomot@m=
atech-cameroun.com","325","05-04-2025 21:41:19","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004736028","N=
goulmekong-Nord","","05-04-2025 21:41:01","05-04-2025 21:37:40","05-04-2025=
 22:39:12","Site went down because insufficient of rectifier on site//site =
stabilized","Siligap Boris","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down because insufficient of rectifier on site//sit=
e stabilized","olivier.kwedi@ihstowers.com","202","05-04-2025 21:41:01","MA=
TECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004735418","Meh=
anda 1","","05-04-2025 20:00:53","05-04-2025 19:48:46","06-04-2025 08:05:29=
","Access problem at this time of day (prohibited by the landlord)   Grid o=
utage gen failed to start due to ATS dysfuctionning// We reset it and Site =
is on Gen","Albran Byorel","Access Denial","Lease Or Legal","Landlord Relat=
ed Issues","Access Issue - Land Lord","Access problem at this time of day (=
prohibited by the landlord)   Grid outage gen failed to start due to ATS dy=
sfuctionning// We reset it and Site is on Gen","ludivine.ngamaleu@ihstowers=
.com","728","05-04-2025 20:00:53","MATECH CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0004735335","N=
gousso-II","","05-04-2025 19:41:42","05-04-2025 19:12:32","05-04-2025 20:02=
:02","Grid outage,site went down due to dysfunction of PWC  //he reset it a=
nd site on GEN","MFOUAGUEGUE MATHIEU","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Grid outage,site went down due to dysfun=
ction of PWC //he reset it and site on GEN","olivier.kwedi@ihstowers.com","=
1751","05-04-2025 19:41:42","MATECH CMR"
"Closed Complete","Site Down","T1622","IHS_YND_186","NOCINC0004735189","Ngo=
usso Carrefour","","05-04-2025 19:26:18","05-04-2025 19:12:41","05-04-2025 =
20:04:58","Grid outage,site went down due to dysfunction of PWC //he reset =
it and site on GEN","Siligap Boris","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Grid outage,site went down due to dysfunct=
ion of PWC //he reset it and site on GEN","ludivine.ngamaleu@ihstowers.com"=
,"872","05-04-2025 19:26:18","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004735035","B=
riqueterie","","05-04-2025 19:07:21","05-04-2025 18:09:08","06-04-2025 07:5=
8:25","Grid only site  No space to deploy mobile gen//Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only si=
te  No space to deploy mobile gen//Grid return","edwige.kapawo@matech-camer=
oun.com","3494","05-04-2025 19:07:21","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004734999","E=
vodoula OCM","","05-04-2025 18:57:38","05-04-2025 13:33:22","05-04-2025 19:=
06:37","Site went down due to Eneo contactor HS // He bridged and put on Ge=
n","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel",=
"ATS-AMF Issue","Site went down due to Eneo contactor HS // He bridged and =
put on Gen","olivier.kwedi@ihstowers.com","19457","05-04-2025 18:57:38","MA=
TECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004734987","M=
essassi 2","","05-04-2025 18:55:19","05-04-2025 17:40:06","05-04-2025 22:27=
:38","Site went down due to insufficient rectifiers on site//He added one r=
ectifier ","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to insufficient rectifiers on site//He ad=
ded one rectifier ","olivier.kwedi@ihstowers.com","4515","05-04-2025 18:55:=
19","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004734777","Mon=
tee Jouvence","","05-04-2025 18:32:18","05-04-2025 18:07:04","05-04-2025 18=
:35:11","Site went Down due to eneo fluctuations // Grid stabilized","Hyema=
fo Gildas","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Site went Down due to eneo fluctuations // Grid stabilized","ludivine.n=
gamaleu@ihstowers.com","1515","05-04-2025 18:32:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004734749","Saa","",=
"05-04-2025 18:27:57","05-04-2025 15:50:19","05-04-2025 17:07:36","Cascaded=
 Incident from TTO4826109","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went Down due to Grid fluctuations // =
He put site on Gen","system","288639","05-04-2025 18:27:57","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004734748","SAA Entr=
ance","","05-04-2025 18:27:57","05-04-2025 15:50:19","05-04-2025 17:07:36",=
"Cascaded Incident from TTO4826109","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went Down due to Grid fluctua=
tions // He put site on Gen","system","288639","05-04-2025 18:27:57","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_085","NOCINC0004734612","Briquete=
rie","","05-04-2025 18:08:09","05-04-2025 17:48:51","05-04-2025 18:07:59","=
Grid only, Site went Down due (no space to deployed MGE) // Grid returned",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 only, Site went Down due (no space to deployed MGE) // Grid returned","sys=
tem","1158","05-04-2025 18:08:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_002","NOCINC0004734611","Yde-M-Ce=
ntral","","05-04-2025 18:08:08","05-04-2025 17:48:51","05-04-2025 18:07:59"=
,"Cascaded Incident from TTO4827064","","Cascade Outage","Active","Cascade =
Active","Cascade Active","Site impacted by CBC-radio","system","267604","05=
-04-2025 18:08:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_003","NOCINC0004734610","Mercure"=
,"","05-04-2025 18:08:08","05-04-2025 17:48:51","05-04-2025 18:07:59","Casc=
aded Incident from TTO4827064","","Cascade Outage","Active","Cascade Active=
","Cascade Active","Site impacted by CBC-radio","system","267604","05-04-20=
25 18:08:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_007","NOCINC0004734609","Montee-A=
nne-Rouge","","05-04-2025 18:08:08","05-04-2025 17:48:51","05-04-2025 18:07=
:59","Cascaded Incident from TTO4827064","","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Site impacted by CBC-radio","system","267604"=
,"05-04-2025 18:08:08","MATECH CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0004734575","E=
lig-Essono","IHS_YND_007, IHS_YND_003, IHS_YND_005, IHS_YND_002","05-04-202=
5 18:02:11","05-04-2025 17:48:51","05-04-2025 18:07:59","Site impacted by C=
BC-radio","Paul BIBOUM","Customer Equipment Failure","Active","Active Equip=
ment Failure","Affected by 3rd Party Site","Site impacted by CBC-radio","ed=
wige.kapawo@matech-cameroun.com","801","05-04-2025 18:02:11","MATECH CMR"
"Closed Complete","Site Down","T0105","IHS_YND_321","NOCINC0004734542","Soa=
","","05-04-2025 17:58:30","05-04-2025 17:27:20","05-04-2025 18:02:40","Gri=
d-Gen, site down due to 1 out of 6 rectifiers crashed // rectifier reset ",=
"Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Grid-Gen, site down due to 1 out of 6 rectifiers crashed // rectifier res=
et ","ludivine.ngamaleu@ihstowers.com","1871","05-04-2025 17:58:30","MATECH=
 CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004734084","BIY=
EMASSI NIKI","","05-04-2025 16:42:36","05-04-2025 16:19:21","05-04-2025 21:=
51:36","ACTIVE //No power issue U=3D 54.6V site on Grid the TX FME Mbah Hos=
iah /674007438// from huawei is informed","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTI=
VE //No power issue U=3D 54.6V site on Grid the TX FME Mbah Hosiah /6740074=
38// from huawei is informed","ludivine.ngamaleu@ihstowers.com","1396","05-=
04-2025 16:42:36","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004734063","Aka=
k-Nkozoa-MTN-IHS","","05-04-2025 16:37:56","05-04-2025 16:09:39","05-04-202=
5 16:31:39","Grid outage, site went down due to PWC malfunction // Gen manu=
ally started","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","R=
ectifier Module Overloaded","Grid outage, site went down due to PWC malfunc=
tion // Gen manually started","ludivine.ngamaleu@ihstowers.com","1699","05-=
04-2025 16:37:56","MATECH CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004733845","Nko=
l-Mebanga","","05-04-2025 16:03:37","05-04-2025 15:50:19","05-04-2025 17:07=
:36","Site up awaiting feedback","Parker Tchoup","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went Down due to Grid fluctuatio=
ns // He put site on Gen","ludivine.ngamaleu@ihstowers.com","288640","05-04=
-2025 16:03:37","MATECH CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0004733839","Car=
refour Ayissi Ele","","05-04-2025 16:02:12","05-04-2025 15:50:19","05-04-20=
25 21:07:36","No power issue site on solar with U=3D53v Gregroire(652070658=
) from Huawei is informed","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","No power issue site on solar with U=3D53v G=
regroire(652070658) from Huawei is informed","ludivine.ngamaleu@ihstowers.c=
om","288639","05-04-2025 16:02:12","MATECH CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0004733812","E=
-Police","","05-04-2025 15:59:17","05-04-2025 11:11:10","05-04-2025 16:25:5=
1","   Grid only, Site went Down due to Grid Outage (No space to deploy)//g=
rid restoration","","Grid Supply","Passive","Grid","National Grid - Grid Ou=
tage Issue","   Grid only, Site went Down due to Grid Outage (No space to d=
eploy)//grid restoration","olivier.kwedi@ihstowers.com","17289","05-04-2025=
 15:59:17","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004733766","SAA=
 2","IHS_YND_810, IHS_YND_542, IHS_YND_809, IHS_YND_405","05-04-2025 15:51:=
38","05-04-2025 15:50:19","05-04-2025 17:07:36","Site went Down due to Grid=
 fluctuations // He put site on Gen","Parker Tchoup","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Site went Down due to Grid fl=
uctuations // He put site on Gen","ludivine.ngamaleu@ihstowers.com","80","0=
5-04-2025 15:51:38","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004733748","Nko=
londom","","05-04-2025 15:44:07","05-04-2025 15:31:00","05-04-2025 16:38:53=
","Grid outage, Site went down because Gen failed to start due to ATS malfu=
nctionning// He reset ATS and Gen manually started","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site =
went down because Gen failed to start due to ATS malfunctionning// He reset=
 ATS and Gen manually started","ludivine.ngamaleu@ihstowers.com","788","05-=
04-2025 15:44:07","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004733737","Nko=
g-Edzen","","05-04-2025 15:42:56","05-04-2025 15:23:24","05-04-2025 20:53:0=
0","Site went down due to bay Huawei Controller malfunction// He reset it",=
"Parker Tchoup","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","Site went down due to bay Huawei Controller dysfunctionning //=
 He reset it","ludivine.ngamaleu@ihstowers.com","1173","05-04-2025 15:42:56=
","MATECH CMR"
"Closed Complete","Site Down","CTR_369","IHS_YND_019","NOCINC0004733514","H=
otel de Ville Yde","","05-04-2025 15:27:24","05-04-2025 14:52:14","05-04-20=
25 15:01:57","Active//No power issue on site ,site on Grid wiith Ubaie=3D53=
.3V The TX FME Brice Tsague/ 690286359/ Huawei is informed","Paul BIBOUM","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site ,site on Grid wiith Ubaie=3D54.1 =
V The TX FME Brice Tsague/ 690286359/ Huawei is informed","gerard.tchangoue=
@matech-cameroun.com","2111","05-04-2025 15:27:24","MATECH CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0004733505","N=
R-Bastos","","05-04-2025 15:26:31","05-04-2025 14:51:10","05-04-2025 17:24:=
49","Grid only, Site wen Down due to Eneo Outage (no space to deployed MGE)=
 // Grid returned","","Grid Supply","Passive","Grid","National Grid - Grid =
Outage Issue","Grid only, Site wen Down due to Eneo Outage (no space to dep=
loyed MGE) // Grid returned","gerard.tchangoue@matech-cameroun.com","2122",=
"05-04-2025 15:26:31","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004733392","ETO=
UDI Entree du palais","","05-04-2025 15:07:00","05-04-2025 14:54:46","05-04=
-2025 16:01:51","site down due to 1 out of 3 rectifiers crashed // rectifie=
r reset","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","site down due to 1 out of 3 rectifiers crashed // rectifier re=
set","ludivine.ngamaleu@ihstowers.com","735","05-04-2025 15:07:00","MATECH =
CMR"
"Closed Complete","Site Down","T0539","IHS_YND_034","NOCINC0004733337","EMI=
A MTN","","05-04-2025 14:56:00","05-04-2025 14:24:47","05-04-2025 16:26:02"=
,"Grid only, site went Down due to Grid outage (no space to deployed MGE) /=
/ Grid returned","","Grid Supply","Passive","Grid","National Grid - Grid Ou=
tage Issue","Grid only, site went Down due to Grid outage (no space to depl=
oyed MGE) // Grid returned","ludivine.ngamaleu@ihstowers.com","1873","05-04=
-2025 14:56:00","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0004733329","Clu=
b France","","05-04-2025 14:54:48","05-04-2025 14:23:37","05-04-2025 16:17:=
37","Grid only, no space to deployed MGE // Grid returned	","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid only, no space=
 to deployed MGE // Grid returned","ludivine.ngamaleu@ihstowers.com","1872"=
,"05-04-2025 14:54:48","MATECH CMR"
"Closed Complete","Site Down","T0217","IHS_YND_018","NOCINC0004733322","P&T=
 Building","","05-04-2025 14:53:29","05-04-2025 14:16:18","05-04-2025 17:03=
:18","Grid only, no space to deployed MGE // Grid returned","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid only, no space=
 to deployed MGE // Grid returned","ludivine.ngamaleu@ihstowers.com","2232"=
,"05-04-2025 14:53:29","MATECH CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0004733309","ENA=
M","","05-04-2025 14:50:53","05-04-2025 14:14:45","05-04-2025 17:06:45","Gr=
id only, Site wen Down due to Eneo Outage (Access issue ) // Grid returned"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d only, Site wen Down due to Eneo Outage (Access issue ) // Grid returned",=
"ludivine.ngamaleu@ihstowers.com","2169","05-04-2025 14:50:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0004733306","Bastos E=
koudou","","05-04-2025 14:49:48","05-04-2025 13:14:14","05-04-2025 14:38:29=
","Cascaded Incident from TTO4825573","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage , site went down bef=
ore Gen started due to poor battery backup// Grid Power return","system","3=
05382","05-04-2025 14:49:48","MATECH CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004733132","Bas=
tos Amb Coree","","05-04-2025 14:09:44","05-04-2025 13:55:35","05-04-2025 1=
7:25:35","Grid only, Site wen Down due to Eneo Outage (no space to deployed=
 MGE) // Grid returned","","Grid Supply","Passive","Grid","National Grid - =
Grid Outage Issue","Grid only, Site wen Down due to Eneo Outage (no space t=
o deployed MGE) // Grid returned","franck.nkomot@matech-cameroun.com","850"=
,"05-04-2025 14:09:44","MATECH CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004733013","E=
foulan","","05-04-2025 13:51:06","05-04-2025 13:46:44","05-04-2025 13:56:38=
","Site impacted by Efoulan Pont","MINKA NICOLAS","Customer Equipment Failu=
re","Active","Active Equipment Failure","Affected by 3rd Party Site","Site =
impacted by Efoulan Pont","franck.nkomot@matech-cameroun.com","262","05-04-=
2025 13:51:06","MATECH CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0004733000","R=
d-Pt-Express","","05-04-2025 13:47:55","05-04-2025 13:35:38","05-04-2025 16=
:31:44","Grid only, Site wen Down due to Eneo Outage (no space to deployed =
MGE) // Grid returned","","Grid Supply","Passive","Grid","National Grid - G=
rid Outage Issue","Grid only, Site wen Down due to Eneo Outage (no space to=
 deployed MGE) // Grid returned ","franck.nkomot@matech-cameroun.com","738"=
,"05-04-2025 13:47:55","MATECH CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004732991","M=
ontee-Jouvence-II","","05-04-2025 13:46:05","05-04-2025 13:34:43","05-04-20=
25 21:52:49","ACTIVE// No power issue on site, site on Grid with Ubaie=3D54=
.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo G=
ildas","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE// No power issue on site, site on Grid with Ubaie=
=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed","fran=
ck.nkomot@matech-cameroun.com","683","05-04-2025 13:46:05","MATECH CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004732984","T=
amtam Weekend","","05-04-2025 13:45:05","05-04-2025 13:35:49","05-04-2025 1=
4:21:48","Active//No power issue site on Grid with U=3D54.V The TX FME Mbah=
 Hosiah (674007438) FROM Huawei is informed.","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue site on Grid with U=3D54.V The TX FME Mbah Hosiah (6=
74007438) FROM Huawei is informed.","franck.nkomot@matech-cameroun.com","55=
7","05-04-2025 13:45:05","MATECH CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004732791","Mok=
olo Yaounde","","05-04-2025 13:23:31","05-04-2025 12:56:15","05-04-2025 16:=
48:15","Grid outage, No space to deploy MDG// Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spac=
e to deploy MDG// Grid return","franck.nkomot@matech-cameroun.com","1637","=
05-04-2025 13:23:31","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004732783","Bas=
tos-BAT","IHS_YND_193","05-04-2025 13:22:23","05-04-2025 13:14:14","05-04-2=
025 14:38:33","Grid outage , site went down before Gen started due to poor =
battery backup// Grid Power return","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage , site wen=
t down before Gen started due to poor battery backup// Grid Power return","=
franck.nkomot@matech-cameroun.com","490","05-04-2025 13:22:23","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0004732737","Mobil-Es=
sos","","05-04-2025 13:16:06","05-04-2025 12:39:54","05-04-2025 13:31:57","=
Cascaded Incident from TTO4824858","Siligap Boris","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D53.5v site =
on grid Tx fme Armand Nguetsa of huawei is informed","system","278454","05-=
04-2025 13:16:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0004732738","Crf Corn=
ier","","05-04-2025 13:16:06","05-04-2025 12:39:54","05-04-2025 13:31:57","=
Cascaded Incident from TTO4824858","MINKA NICOLAS","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D53.5v site =
on grid Tx fme Armand Nguetsa of huawei is informed","system","278454","05-=
04-2025 13:16:06","MATECH CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004732694","M=
adison","IHS_YND_109, IHS_YND_566","05-04-2025 13:08:11","05-04-2025 12:39:=
54","05-04-2025 17:42:26","No power issue on site U=3D53.5v site on grid Tx=
 fme Armand Nguetsa of huawei is informed","MFOUAGUEGUE MATHIEU","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site U=3D53.5v site on grid Tx fme Armand Nguetsa of hu=
awei is informed","franck.nkomot@matech-cameroun.com","1698","05-04-2025 13=
:08:11","MATECH CMR"
"Closed Complete","Site Down","T1071","IHS_YND_343","NOCINC0004732560","Mbe=
doumou - Ekali","","05-04-2025 12:44:16","05-04-2025 12:15:52","05-04-2025 =
21:44:52","No power Ubaie=3D53,4V site on GRID The Tx FME Rodrigue (6551029=
99)from Huawei is informed.","Albran Byorel","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power Ubaie=3D5=
3,4V site on GRID The Tx FME Rodrigue (655102999)from Huawei is informed.",=
"franck.nkomot@matech-cameroun.com","1705","05-04-2025 12:44:16","MATECH CM=
R"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0004732510","Biy=
emassi LAC","","05-04-2025 12:34:26","05-04-2025 12:29:13","05-04-2025 16:1=
7:13","Grid only, no space to deployed MGE // Grid returned","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid only, no spac=
e to deployed MGE // Grid returned","franck.nkomot@matech-cameroun.com","31=
4","05-04-2025 12:34:26","MATECH CMR"
"Closed Complete","Site Down","T0528","IHS_YND_027","NOCINC0004732499","Hop=
ital Central","","05-04-2025 12:32:59","05-04-2025 12:29:47","05-04-2025 17=
:01:47","Grid outage//grid power return","","Grid Supply","Passive","Grid",=
"National Grid - Grid Outage Issue","Grid outage//grid power return","franc=
k.nkomot@matech-cameroun.com","193","05-04-2025 12:32:59","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004732441","Odz=
a II OCM","","05-04-2025 12:27:00","05-04-2025 12:14:54","05-04-2025 12:59:=
54","Site went Down due to ATS and Gen card Faulty // Grid restaured","Albr=
an Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Si=
te went Down due to ATS and Gen card Faulty // Grid restaured","franck.nkom=
ot@matech-cameroun.com","727","05-04-2025 12:27:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_283","NOCINC0004732388","Abome","=
","05-04-2025 12:21:48","05-04-2025 11:51:13","06-04-2025 04:40:37","Cascad=
ed Incident from TTO4824396","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid Outage Site went down because Gen ov=
erload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the load and =
start the Gen Manually","system","324598","05-04-2025 12:21:48","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_253","NOCINC0004732385","Clge-Adv=
antiste","","05-04-2025 12:21:47","05-04-2025 11:51:13","06-04-2025 04:40:3=
7","Cascaded Incident from TTO4824396","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage Site went down beca=
use Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the=
 load and start the Gen Manually","system","324600","05-04-2025 12:21:47","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004732387","Elig Edz=
oa","","05-04-2025 12:21:47","05-04-2025 11:51:13","06-04-2025 04:40:37","C=
ascaded Incident from TTO4824396","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage Site went down because =
Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the loa=
d and start the Gen Manually","system","324597","05-04-2025 12:21:47","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_312","NOCINC0004732384","Nkolnda"=
,"","05-04-2025 12:21:47","05-04-2025 11:51:13","06-04-2025 04:40:37","Casc=
aded Incident from TTO4824396","Albran Byorel","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid Outage Site went down because Gen =
overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the load an=
d start the Gen Manually","system","324604","05-04-2025 12:21:47","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004732383","Abang","=
","05-04-2025 12:21:47","05-04-2025 11:51:13","06-04-2025 04:40:37","Cascad=
ed Incident from TTO4824396","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage Site went down because Gen=
 overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the load a=
nd start the Gen Manually","system","324603","05-04-2025 12:21:47","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0004732386","Awae Ewo=
nkan","","05-04-2025 12:21:47","05-04-2025 11:51:13","06-04-2025 04:40:37",=
"Cascaded Incident from TTO4824396","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage Site went down because=
 Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the lo=
ad and start the Gen Manually","system","324600","05-04-2025 12:21:47","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_281","NOCINC0004732380","Odza II"=
,"","05-04-2025 12:21:46","05-04-2025 11:51:13","06-04-2025 04:40:37","Casc=
aded Incident from TTO4824396","Albran Byorel","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid Outage Site went down because Gen =
overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the load an=
d start the Gen Manually","system","324597","05-04-2025 12:21:46","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_275","NOCINC0004732382","Nkolbong=
","","05-04-2025 12:21:46","05-04-2025 11:51:13","06-04-2025 04:40:37","Cas=
caded Incident from TTO4824396","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid Outage Site went down because Ge=
n overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the load =
and start the Gen Manually","system","324603","05-04-2025 12:21:46","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_807","NOCINC0004732381","Ahala Ec=
hangeur","","05-04-2025 12:21:46","05-04-2025 11:51:13","06-04-2025 04:40:3=
7","Cascaded Incident from TTO4824396","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage Site went down beca=
use Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the=
 load and start the Gen Manually","system","324596","05-04-2025 12:21:46","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_336","NOCINC0004732377","EKIE",""=
,"05-04-2025 12:21:45","05-04-2025 11:51:13","06-04-2025 04:40:37","Cascade=
d Incident from TTO4824396","Albran Byorel","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid Outage Site went down because Gen ove=
rload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the load and s=
tart the Gen Manually","system","324602","05-04-2025 12:21:45","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_524","NOCINC0004732378","ODZA BOR=
NE 10","","05-04-2025 12:21:45","05-04-2025 11:51:13","06-04-2025 04:40:37"=
,"Cascaded Incident from TTO4824396","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage Site went down becaus=
e Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the l=
oad and start the Gen Manually","system","324595","05-04-2025 12:21:45","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0004732376","Mvog-Man=
ga","","05-04-2025 12:21:45","05-04-2025 11:51:13","06-04-2025 04:40:37","C=
ascaded Incident from TTO4824396","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage Site went down because G=
en overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the load=
 and start the Gen Manually","system","324595","05-04-2025 12:21:45","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004732379","Odza Min=
kan IHS","","05-04-2025 12:21:45","05-04-2025 11:51:13","06-04-2025 04:40:3=
7","Cascaded Incident from TTO4824396","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage Site went down beca=
use Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the=
 load and start the Gen Manually","system","324602","05-04-2025 12:21:45","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0004732374","Ekoumdou=
m OCM","","05-04-2025 12:21:44","05-04-2025 11:51:13","06-04-2025 04:40:37"=
,"Cascaded Incident from TTO4824396","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage Site went down becaus=
e Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the l=
oad and start the Gen Manually","system","324594","05-04-2025 12:21:44","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_728","NOCINC0004732375","TROPICAN=
A NEW","","05-04-2025 12:21:44","05-04-2025 11:51:13","06-04-2025 04:40:37"=
,"Cascaded Incident from TTO4824396","MINKA NICOLAS","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage Site went down becaus=
e Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the l=
oad and start the Gen Manually","system","324601","05-04-2025 12:21:44","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_256","NOCINC0004732373","MESSAME =
NDONGO 1162","","05-04-2025 12:21:44","05-04-2025 11:51:13","06-04-2025 04:=
40:37","Cascaded Incident from TTO4824396","MINKA NICOLAS","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid Outage Site went down =
because Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced=
 the load and start the Gen Manually","system","324596","05-04-2025 12:21:4=
4","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0004732372","Nkoulou =
Carriere carrefourt","","05-04-2025 12:21:44","05-04-2025 11:51:13","06-04-=
2025 04:40:37","Cascaded Incident from TTO4824396","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","Grid Outage Site=
 went down because Gen overload (20KVA, 270A) SS IHS Pascaline confirmed //=
 He reduced the load and start the Gen Manually","system","324599","05-04-2=
025 12:21:44","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_161","NOCINC0004732369","Sofavinc=
","","05-04-2025 12:21:43","05-04-2025 11:51:13","06-04-2025 04:40:37","Cas=
caded Incident from TTO4824396","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage Site went down because Gen=
 overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the load a=
nd start the Gen Manually","system","324594","05-04-2025 12:21:43","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_252","NOCINC0004732370","Koweit C=
ity","","05-04-2025 12:21:43","05-04-2025 11:51:13","05-04-2025 12:59:06","=
Cascaded Incident from TTO4824396","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage Site went down because =
Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the loa=
d and start the Gen Manually","system","324601","05-04-2025 12:21:43","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_800","NOCINC0004732368","ODZA CIT=
E MBIA","","05-04-2025 12:21:43","05-04-2025 11:51:13","06-04-2025 04:40:37=
","Cascaded Incident from TTO4824396","Albran Byorel","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid Outage Site went down becau=
se Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the =
load and start the Gen Manually","system","324598","05-04-2025 12:21:43","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_328","NOCINC0004732371","Nsimalen=
 MTN","","05-04-2025 12:21:43","05-04-2025 11:51:13","06-04-2025 04:40:37",=
"Cascaded Incident from TTO4824396","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage Site went down because=
 Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // He reduced the lo=
ad and start the Gen Manually","system","324599","05-04-2025 12:21:43","MAT=
ECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004732303","Tou=
ring Club International","IHS_YND_800, IHS_YND_161, IHS_YND_252, IHS_YND_32=
8, IHS_YND_794, IHS_YND_528, IHS_YND_256, IHS_YND_291, IHS_YND_728, IHS_YND=
_254, IHS_YND_336, IHS_YND_524, IHS_YND_715, IHS_YND_281, IHS_YND_807, IHS_=
YND_275, IHS_YND_290, IHS_YND_312, IHS_YND_253, IHS_YND_535, IHS_YND_504, I=
HS_YND_283","05-04-2025 12:07:31","05-04-2025 11:51:13","06-04-2025 04:40:3=
7","Grid Outage Site went down because Gen overload (20KVA, 270A) SS IHS Pa=
scaline confirmed // He reduced the load and start the Gen Manually","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid O=
utage Site went down because Gen overload (20KVA, 270A) SS IHS Pascaline co=
nfirmed // He reduced the load and start the Gen Manually","franck.nkomot@m=
atech-cameroun.com","979","05-04-2025 12:07:31","MATECH CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0004732197","MVA=
N SACEL","","05-04-2025 11:43:03","05-04-2025 11:28:48","05-04-2025 11:48:4=
8","Grid fluctuation, Site went down because Gen started and stopped due to=
 Grid bad voltage// He bypassed Grid and started Gen manually","MINKA NICOL=
AS","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, Site went down because Gen started and stopped due to =
Grid bad voltage// He bypassed Grid and started Gen manually","franck.nkomo=
t@matech-cameroun.com","856","05-04-2025 11:43:03","MATECH CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004732162","Acc=
acia New","","05-04-2025 11:37:32","05-04-2025 11:12:18","05-04-2025 16:23:=
56","Grid only, site went Down due to Grid outage (no space to deployed MGE=
) // Grid returned","","Grid Supply","Passive","Grid","National Grid - Grid=
 Outage Issue","Grid only, site went Down due to Grid outage (no space to d=
eployed MGE) // Grid returned","franck.nkomot@matech-cameroun.com","1516","=
05-04-2025 11:37:32","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004732152","Mam=
bine","","05-04-2025 11:36:27","05-04-2025 11:27:13","05-04-2025 11:58:13",=
"Grid outage, site went down because gen ran until fuel shortage // Refueli=
ng done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage, site went down because gen ran until fuel shortage // Refueling =
done","franck.nkomot@matech-cameroun.com","555","05-04-2025 11:36:27","MATE=
CH CMR"
"Closed Complete","Site Down","T3172","IHS_YND_043","NOCINC0004732111","Emi=
a","","05-04-2025 11:30:20","05-04-2025 11:12:13","05-04-2025 16:26:21","Gr=
id only, site went Down due to Grid outage (no space to deployed MGE) // Gr=
id returned","","Grid Supply","Passive","Grid","National Grid - Grid Outage=
 Issue","Grid only, site went Down due to Grid outage (no space to deployed=
 MGE) // Grid returned","franck.nkomot@matech-cameroun.com","1088","05-04-2=
025 11:30:20","MATECH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004732105","Com=
plex Beac II","","05-04-2025 11:29:19","05-04-2025 11:21:47","05-04-2025 12=
:30:47","Grid outage, site went down because the generator card cable is fa=
ulty //grid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage, site went down because the generator =
card cable is faulty //grid return","franck.nkomot@matech-cameroun.com","45=
3","05-04-2025 11:29:19","MATECH CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004732094","Bri=
quetterie","","05-04-2025 11:27:38","05-04-2025 11:24:27","05-04-2025 17:32=
:27","Grid outage no space to deploy mobile gen//Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy mobile gen//Grid return","franck.nkomot@matech-cameroun.com",=
"192","05-04-2025 11:27:38","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004732092","Ako=
k Ndoe Yde","","05-04-2025 11:26:42","05-04-2025 11:15:28","05-04-2025 12:5=
0:28","Grid outage, Site down due to poor battery backup // Gen started man=
ually","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, Site down due to poor battery backup =
// Gen started manually","franck.nkomot@matech-cameroun.com","675","05-04-2=
025 11:26:42","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004732064","Saa=
","","05-04-2025 11:20:29","05-04-2025 11:13:15","05-04-2025 13:36:15","(Si=
te impactedby SAA_t0142) Site went down because 2/3 rectifier disfunctionni=
ng Felix BATEU is informed// He reset rectifiers and site on grid","Parker =
Tchoup","Equipment Repair","Passive","Rectifier","Rectifier Module","(Site =
impactedby SAA_t0142) Site went down because 2/3 rectifier disfunctionning =
Felix BATEU is informed// He reset rectifiers and site on grid","franck.nko=
mot@matech-cameroun.com","435","05-04-2025 11:20:29","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004732056","SAA=
 Entrance","","05-04-2025 11:18:25","05-04-2025 11:13:14","05-04-2025 13:36=
:15","Site went down because 2/3 rectifier disfunctionning Felix BATEU is i=
nformed// He reset rectifiers and site on grid","Parker Tchoup","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down because 2/=
3 rectifier disfunctionning Felix BATEU is informed// He reset rectifiers a=
nd site on gridite on grid","franck.nkomot@matech-cameroun.com","312","05-0=
4-2025 11:18:25","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004732024","N=
KOLMEKONG YDE","","05-04-2025 11:16:01","05-04-2025 11:11:44","05-04-2025 1=
5:58:35","Site went down because PWC dysfunctionning IHS SS BERNARD ATANGAN=
A is informed and confirmed// He reset the it and manually start the Gen","=
Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","Site went down because PWC dysfunctionning IHS SS BERNARD ATA=
NGANA is informed and confirmed// He reset the it and manually start the Ge=
n","franck.nkomot@matech-cameroun.com","259","05-04-2025 11:16:01","MATECH =
CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0004732017","M=
VAN","","05-04-2025 11:14:55","05-04-2025 11:09:44","05-04-2025 12:23:59","=
grid outage,gen failed to start due to grid bad voltage,no rcp//he bypassed=
 the Grid and site on Gen","MINKA NICOLAS","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","grid outage,gen failed to start d=
ue to grid bad voltage,no rcp//he bypassed the Grid and site on Gen","franc=
k.nkomot@matech-cameroun.com","312","05-04-2025 11:14:55","MATECH CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004731901","SOA=
 VILLAGE","","05-04-2025 11:05:51","05-04-2025 10:56:38","05-04-2025 17:43:=
38","Active//No power issue, site is on Grid with Ubaie=3D54,6V The TX Synp=
horien / 675295205/ Huawei is informed","Siligap Boris","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue, site is on Grid with Ubaie=3D54,6V The TX Synphorien / 675=
295205/ Huawei is informed","franck.nkomot@matech-cameroun.com","554","05-0=
4-2025 11:05:51","MATECH CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004731876","Mel=
en Ba'aba","","05-04-2025 11:01:36","05-04-2025 10:48:23","05-04-2025 11:20=
:23","Grid outage,site down due to fuel shortage// Refueling done","Siligap=
 Boris","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,site =
down due to fuel shortage// Refueling done","franck.nkomot@matech-cameroun.=
com","1427","05-04-2025 11:01:36","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004731782","ODZ=
A MINKAN EDIBI ASSI","","05-04-2025 10:48:46","05-04-2025 10:36:27","05-04-=
2025 14:08:27","site Went down due to insufficient rectifier issue on site =
//he reset it","Albran Byorel","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","site Went down due to insufficient rectifier issue on site=
 //he reset it","franck.nkomot@matech-cameroun.com","740","05-04-2025 10:48=
:46","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004731727","Oko=
lo Kilombo","","05-04-2025 10:38:00","05-04-2025 10:27:53","05-04-2025 14:1=
1:53","Grid outage,site went down because Gen failed to start due to Grid b=
ad voltage,no rp on site//He bypassed the Grid and site on Gen ","Fabrice P=
ouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid outage,site went down because Gen failed to start due to Grid b=
ad voltage,no rp on site//He bypassed the Grid and site on Gen ","franck.nk=
omot@matech-cameroun.com","608","05-04-2025 10:38:00","MATECH CMR"
"Closed Complete","Site Down","T0030","IHS_YND_041","NOCINC0004731338","Lyc=
ee Leclerc School","","05-04-2025 09:48:52","05-04-2025 07:17:42","05-04-20=
25 07:18:09","Active// No power issue on site ,UBAIE=3D53.5V site is on GRI=
D and the FME TX MBAH OSIAH (699699694) from huawei is informed","Paul BIBO=
UM","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// No power issue on site ,UBAIE=3D53.5V site is on G=
RID and the FME TX MBAH OSIAH (699699694) from huawei is informed","loic.no=
umsi@matech-cameroun.com","9071","05-04-2025 09:48:52","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004731288","Men=
dong vallee","","05-04-2025 09:36:38","05-04-2025 06:52:22","05-04-2025 08:=
44:33","No power issue on site T51.8 v siteon grid   Fubert, 654266068 Of h=
uawei is informed","Fanda Brice","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue on site T51.8 v=
 siteon grid   Fubert, 654266068 Of huawei is informed","loic.noumsi@matech=
-cameroun.com","9857","05-04-2025 09:36:38","MATECH CMR"
"Closed Complete","Site Down","T3206","IHS_YND_759","NOCINC0004731166","Nko=
lfoulou Tsinga Village","","05-04-2025 09:19:19","05-04-2025 08:54:14","05-=
04-2025 10:08:14","Grid fluctuation, Site went down because Gen failed to s=
tart due to Grid bad voltage // He bypassed the Grid and site on Gen","Sili=
gap Boris","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","Grid fluctuation, Site went down because Gen failed to start due =
to Grid bad voltage // He bypassed the Grid and site on Gen","alexandre.kam=
al@ihstowers.com","1506","05-04-2025 09:19:19","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004730985","Meh=
anda 1","","05-04-2025 08:48:39","05-04-2025 03:22:02","05-04-2025 03:22:50=
","Grid Phase faulty, Gen fails to start // Grid restoraton","Albran Byorel=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid Phase faulty, Gen fails to start // Grid restoraton
","loic.noumsi@matech-cameroun.com","19597","05-04-2025 08:48:39","MATECH C=
MR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004730940","Awa=
e Ewonkan","","05-04-2025 08:40:39","05-04-2025 07:21:51","05-04-2025 10:05=
:09","Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline is i=
nformed and confirmed//he reduced the load","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen overl=
oad(20kva,280 A) IHS SS Pascaline is informed and confirmed//he reduced the=
 load","loic.noumsi@matech-cameroun.com","4767","05-04-2025 08:40:39","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0004730476","K=
ondengui","","05-04-2025 06:43:05","05-04-2025 04:42:16","05-04-2025 11:55:=
49","Active//No power issue, site is on grid with Ubaie=3D54V, Eloundou ber=
trant(652586578) from Huawei is informed","Albran Byorel","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue, site is on grid with Ubaie=3D54V, Eloundou bertrant(6525=
86578) from Huawei is informed","loic.noumsi@matech-cameroun.com","7250","0=
5-04-2025 06:43:05","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004730358","B=
iteng-Maetur","","05-04-2025 06:01:12","05-04-2025 05:34:48","05-04-2025 06=
:10:48","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) // He reduced the load","Mba Lazare Herve","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen started and stopped due to Gen overload(20kva, 280A) // =
He reduced the load","gaelle.njiofack@matech-cameroun.com","1586","05-04-20=
25 06:01:12","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004730267","M=
essassi 2","","05-04-2025 05:24:26","05-04-2025 00:27:23","05-04-2025 01:11=
:39","Grid outage, Gen failed to start due High temp Alarm // Water add Gen=
 Start Manually","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Gen failed to=
 start due High temp Alarm // Water add Gen Start Mnually
","gaelle.njiofack@matech-cameroun.com","17824","05-04-2025 05:24:26","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004730230","M=
essassi okolo","","05-04-2025 05:12:15","05-04-2025 00:26:29","05-04-2025 0=
1:00:27","Grid outage, Gen failed to start due to Faulty cable of start ord=
er and burn charger static  // replacement of start-up command cable and st=
atic charger; Gen start manually","Fabrice Pouakam","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Kick Starter","Grid outage, Gen failed to start du=
e to Faulty cable of start order and burn charger static  // replacement of=
 start-up command cable and static charger; Gen start manually
","gaelle.njiofack@matech-cameroun.com","17148","05-04-2025 05:12:15","MATE=
CH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004730220","Oko=
lo Kilombo","","05-04-2025 05:07:36","05-04-2025 03:10:11","05-04-2025 03:2=
8:53","site down due to planned work activity ongoing, inverter MADE AND CO=
NNECTED by MATECH // work done","Fabrice Pouakam","Installation Activity","=
Passive","Planned Activity","Installation Activity","site down due to plann=
ed work activity ongoing, inverter MADE AND CONNECTED by MATECH // work don=
e","loic.noumsi@matech-cameroun.com","7046","05-04-2025 05:07:36","MATECH C=
MR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0004730121","E=
mombo-Tchad","","05-04-2025 04:33:15","05-04-2025 04:02:07","05-04-2025 11:=
55:49","Grid outage,no space to deploy MDG // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no space=
 to deploy MDG // Grid return","loic.noumsi@matech-cameroun.com","1869","05=
-04-2025 04:33:15","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004730080","Aka=
k-Nkozoa-MTN-IHS","","05-04-2025 04:26:44","05-04-2025 04:12:26","05-04-202=
5 04:22:07","site down due to refueling (impacted by poor battery backup) /=
/ End of refueling","Fabrice Pouakam","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","site down due to refueling (impacted=
 by poor battery backup) // End of refueling","gaelle.njiofack@matech-camer=
oun.com","860","05-04-2025 04:26:44","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004730051","Man=
guiers Dispensaire","","05-04-2025 04:15:36","05-04-2025 03:59:21","05-04-2=
025 04:21:07","site down due to replacement action of an equipment made by =
Assistant DO (Iroume) // contactor replaced","Fabrice Pouakam","Equipment R=
eplacement","Passive","Planned Activity","Planned Activity - Passive","site=
 down due to replacement action of an equipment made by Assistant DO (Iroum=
e) // contactor replaced","gaelle.njiofack@matech-cameroun.com","976","05-0=
4-2025 04:15:36","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004729929","M=
essassi 2","","05-04-2025 03:28:56","04-04-2025 17:21:14","04-04-2025 17:59=
:13","Grid outage, Gen failed to start due High temp Alarm // Water add Gen=
 Start Manually","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - High Engine Temp - Coolant Level Issue","Grid outage, Gen failed to=
 start due High temp Alarm // Water add Gen Start Manually","gaelle.njiofac=
k@matech-cameroun.com","36464","05-04-2025 03:28:56","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004729926","Meh=
anda 1","","05-04-2025 03:26:00","05-04-2025 03:22:51","05-04-2025 08:05:51=
","Grid fluctuation site went down due to bad Grid voltage//Grid power stab=
ilized","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid fluctuation site went down due to bad Grid volt=
age//Grid power stabilized","loic.noumsi@matech-cameroun.com","190","05-04-=
2025 03:26:00","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004729590","Nko=
lbong","","05-04-2025 01:10:34","05-04-2025 00:28:23","05-04-2025 01:39:29"=
,"Grid outage, Gen failed to start due to Gen Card dysfunctioning // Grid r=
eturn","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","Grid outage, Gen failed to start due to Gen Card dysfunctionin=
g // Grid return","gaelle.njiofack@matech-cameroun.com","2532","05-04-2025 =
01:10:34","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0004729565","Feb=
e Village","","05-04-2025 00:54:01","05-04-2025 00:41:29","05-04-2025 04:26=
:15","Gen overload // reduced the site load ","Mboua Thierry","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Gen overload // reduced the s=
ite load=20
","loic.noumsi@matech-cameroun.com","927","05-04-2025 00:54:01","MATECH CMR=
"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004729492","Tou=
ring Club International","","05-04-2025 00:29:23","05-04-2025 00:22:17","05=
-04-2025 00:42:08","Gen overload // reducing the site load ","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gen overload /=
/ reducing the site load ","loic.noumsi@matech-cameroun.com","427","05-04-2=
025 00:29:23","MATECH CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0004729218","K=
ondengui","","04-04-2025 23:18:03","05-04-2025 00:18:43","05-04-2025 00:43:=
53","site down due to TX issue / site up without intervention","Albran Byor=
el","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","site down due to TX issue / site up without intervention","=
loic.noumsi@matech-cameroun.com","21024","04-04-2025 23:18:03","MATECH CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0004728997","San=
ta Barbara Gottam","","04-04-2025 22:22:20","04-04-2025 21:45:53","04-04-20=
25 22:39:12","Grid outrage gen failes to start due to alarm ""undervoltage"=
"on card GE//We reset card GE and gen manually started","Delor Telezing","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outrage =
gen failes to start due to alarm ""undervoltage""on card GE//We reset card =
GE and gen manually started","stephane.nkamwa@ihstowers.com","2188","04-04-=
2025 22:22:20","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004728972","TSI=
NGA VILLAGE 2","","04-04-2025 22:14:09","04-04-2025 21:53:57","04-04-2025 2=
3:27:14","Site down due to Disjunction of circuit breaker 125A in the Huawe=
i Ubay //circuit breaker rearmed","Delor Telezing","Equipment Repair","Pass=
ive","Control Panel","Faulty Circuit Breaker","Site down due to Disjunction=
 of circuit breaker 125A in the Huawei Ubay //circuit breaker rearmed","edw=
ige.kapawo@matech-cameroun.com","1214","04-04-2025 22:14:09","MATECH CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004728915","E=
ssomba","","04-04-2025 22:05:01","04-04-2025 21:59:50","04-04-2025 22:44:03=
","Grid outage site went down because Gen failed to start due PWC dysfoncti=
on // He reset the PWC and Gen manually started","Mba Lazare Herve","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outag=
e site went down because Gen failed to start due PWC dysfonction // He rese=
t the PWC and Gen manually started","edwige.kapawo@matech-cameroun.com","31=
2","04-04-2025 22:05:01","MATECH CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004728911","Emo=
mbo Esssomba","","04-04-2025 22:03:33","04-04-2025 21:23:20","04-04-2025 23=
:55:01","site down due to battery gen faulty // gen restarted with an exter=
nal battery","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","AC=
DG - Generator Battery","site down due to battery gen faulty // gen restart=
ed with an external battery","edwige.kapawo@matech-cameroun.com","2414","04=
-04-2025 22:03:33","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004728898","E=
kombitie","","04-04-2025 22:01:25","04-04-2025 21:28:14","04-04-2025 23:07:=
08","site down due to Bad Eneo voltage,// site put on Gen","Fabrice Pouakam=
","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply Issu=
e","site down due to Bad Eneo voltage,// site put on Gen","edwige.kapawo@ma=
tech-cameroun.com","1993","04-04-2025 22:01:25","MATECH CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004728563","Mes=
sa Carriere","","04-04-2025 21:10:47","04-04-2025 18:44:32","04-04-2025 20:=
00:16","Grid outage site went down because Gen failed to start due to Gen c=
ard faulty // Gen Manually Started","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage site went down because=
 Gen failed to start due to Gen card faulty // Gen Manually Started","edwig=
e.kapawo@matech-cameroun.com","8776","04-04-2025 21:10:47","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004728528","M=
eyo","","04-04-2025 21:07:14","04-04-2025 20:04:59","04-04-2025 21:07:19","=
site down due to disjunction of circuit breaker (125A) in the energy ubay /=
 CB rearmed","Hyemafo Gildas","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Circuit Breaker Issue","site down due to disjunction of ci=
rcuit breaker (125A) in the energy ubay / CB rearmed","edwige.kapawo@matech=
-cameroun.com","3736","04-04-2025 21:07:14","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004728466","Odz=
a petit marche new","","04-04-2025 20:56:45","04-04-2025 19:20:34","05-04-2=
025 13:38:39","Site down due to low oil in the engin // oil added and manua=
l start of Gen","Albran Byorel","Equipment Repair","Passive","ACDG Gen","AC=
DG - Low Oil Pressure","Site down due to low oil in the engin // oil added =
and manual start of Gen","edwige.kapawo@matech-cameroun.com","5771","04-04-=
2025 20:56:45","MATECH CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0004728416","A=
hala","","04-04-2025 20:47:14","04-04-2025 20:28:05","04-04-2025 22:31:51",=
"CB trip  in the OCM BTS due to load increase// CB reaarmed","MINKA NICOLAS=
","Equipment Repair","Passive","Control Panel","Circuit Breaker Tripped","C=
B trip  in the OCM BTS due to load increase// CB reaarmed","edwige.kapawo@m=
atech-cameroun.com","1149","04-04-2025 20:47:14","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004728411","N=
yom OCM","","04-04-2025 20:45:56","04-04-2025 20:28:40","04-04-2025 21:34:1=
2","""Active: no power issue, site is on Gen with Ubaie:54.4V, Symphorien(6=
50257151) from Huawei is informed.  ""","Fabrice Pouakam","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","""Act=
ive: no power issue, site is on Gen with Ubaie:54.4V, Symphorien(650257151)=
 from Huawei is informed.=20
""
","edwige.kapawo@matech-cameroun.com","1037","04-04-2025 20:45:56","MATECH =
CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004728300","C=
ite-Verte","","04-04-2025 20:21:22","04-04-2025 19:41:12","05-04-2025 00:48=
:45","site down due to no grid eneo, gen mobile absent / grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Site down=
 due to no grid eneo, gen mobile absent / grid return","edwige.kapawo@matec=
h-cameroun.com","2411","04-04-2025 20:21:22","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004728267","C=
rf-Nsam","","04-04-2025 20:13:22","04-04-2025 20:05:09","05-04-2025 20:08:1=
5","Gird outage, site down due to poor baytery backup (battery not conficur=
ed) // Gen Start manually","MINKA NICOLAS","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Gird outage, site down due to p=
oor baytery backup (battery not conficured) // Gen Start manually","edwige.=
kapawo@matech-cameroun.com","494","04-04-2025 20:13:22","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004728254","C=
rf-Nkolbisson","","04-04-2025 20:11:23","04-04-2025 19:44:12","04-04-2025 2=
1:56:11","Site went down because of CB(125A) in PWC due to load increase//H=
e reamed the CB","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","R=
ectifier","Rectifier Cabinet","Site went down because of CB(125A) in PWC du=
e to load increase//He reamed the CB","edwige.kapawo@matech-cameroun.com","=
1632","04-04-2025 20:11:23","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004728228","S=
OA TOWN","","04-04-2025 20:07:27","04-04-2025 19:51:17","04-04-2025 20:55:4=
4","Grid outage, site went down because gen start and stopped with high tem=
p alarm // He added water and manually start the gen","Siligap Boris","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and manually start the gen","edwige.kapawo@m=
atech-cameroun.com","971","04-04-2025 20:07:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_283","NOCINC0004728203","Abome","=
","04-04-2025 20:05:22","04-04-2025 19:41:07","04-04-2025 23:21:43","Cascad=
ed Incident from TTO4819554","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site down due to Gen overload // charge r=
educed","system","281972","04-04-2025 20:05:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_312","NOCINC0004728200","Nkolnda"=
,"","04-04-2025 20:05:21","04-04-2025 19:41:07","04-04-2025 23:21:43","Casc=
aded Incident from TTO4819554","Albran Byorel","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site down due to Gen overload // charge=
 reduced","system","281971","04-04-2025 20:05:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004728199","Abang","=
","04-04-2025 20:05:21","04-04-2025 19:41:07","04-04-2025 23:21:43","Cascad=
ed Incident from TTO4819554","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site down due to Gen overload // charg=
e reduced","system","281974","04-04-2025 20:05:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_253","NOCINC0004728201","Clge-Adv=
antiste","","04-04-2025 20:05:21","04-04-2025 19:41:07","04-04-2025 23:21:4=
3","Cascaded Incident from TTO4819554","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site down due to Gen overload /=
/ charge reduced","system","281968","04-04-2025 20:05:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_281","NOCINC0004728196","Odza II"=
,"","04-04-2025 20:05:20","04-04-2025 19:41:07","04-04-2025 23:21:43","Casc=
aded Incident from TTO4819554","Albran Byorel","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site down due to Gen overload // charge=
 reduced","system","281971","04-04-2025 20:05:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004728195","Odza Min=
kan IHS","","04-04-2025 20:05:20","04-04-2025 19:41:07","04-04-2025 23:21:4=
3","Cascaded Incident from TTO4819554","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site down due to Gen overload /=
/ charge reduced","system","281964","04-04-2025 20:05:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_807","NOCINC0004728198","Ahala Ec=
hangeur","","04-04-2025 20:05:20","04-04-2025 19:41:07","04-04-2025 23:21:4=
3","Cascaded Incident from TTO4819554","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site down due to Gen overload /=
/ charge reduced","system","281974","04-04-2025 20:05:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0004728191","Ekoumdou=
m OCM","","04-04-2025 20:05:19","04-04-2025 19:41:07","04-04-2025 23:21:43"=
,"Cascaded Incident from TTO4819554","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site down due to Gen overload // =
charge reduced","system","281971","04-04-2025 20:05:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004728194","Odza II =
OCM","","04-04-2025 20:05:19","04-04-2025 19:41:07","04-04-2025 23:21:43","=
Cascaded Incident from TTO4819554","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site down due to Gen overload // ch=
arge reduced","system","281968","04-04-2025 20:05:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_336","NOCINC0004728193","EKIE",""=
,"04-04-2025 20:05:19","04-04-2025 19:41:07","04-04-2025 23:21:43","Cascade=
d Incident from TTO4819554","Albran Byorel","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","site down due to Gen overload // charge re=
duced","system","281965","04-04-2025 20:05:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_728","NOCINC0004728192","TROPICAN=
A NEW","","04-04-2025 20:05:19","04-04-2025 19:41:07","04-04-2025 23:21:43"=
,"Cascaded Incident from TTO4819554","MINKA NICOLAS","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site down due to Gen overload // =
charge reduced","system","281967","04-04-2025 20:05:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_256","NOCINC0004728190","MESSAME =
NDONGO 1162","","04-04-2025 20:05:18","04-04-2025 19:41:07","04-04-2025 23:=
21:43","Cascaded Incident from TTO4819554","MINKA NICOLAS","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site down due to Gen overlo=
ad // charge reduced","system","281973","04-04-2025 20:05:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0004728187","Nkoulou =
Carriere carrefourt","","04-04-2025 20:05:18","04-04-2025 19:41:07","04-04-=
2025 23:21:43","Cascaded Incident from TTO4819554","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","site down due to=
 Gen overload // charge reduced","system","281970","04-04-2025 20:05:18","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_160","NOCINC0004728188","Complex =
Beac II","","04-04-2025 20:05:18","04-04-2025 19:41:07","04-04-2025 23:21:4=
3","Cascaded Incident from TTO4819554","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site down due to Gen overload /=
/ charge reduced","system","281966","04-04-2025 20:05:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_328","NOCINC0004728186","Nsimalen=
 MTN","","04-04-2025 20:05:18","04-04-2025 19:41:07","04-04-2025 23:21:43",=
"Cascaded Incident from TTO4819554","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site down due to Gen overload // c=
harge reduced","system","281972","04-04-2025 20:05:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004728189","Mehanda =
1","","04-04-2025 20:05:18","04-04-2025 19:41:07","04-04-2025 23:21:43","Ca=
scaded Incident from TTO4819554","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site down due to Gen overload // char=
ge reduced","system","281964","04-04-2025 20:05:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_161","NOCINC0004728183","Sofavinc=
","","04-04-2025 20:05:17","04-04-2025 19:41:07","04-04-2025 23:21:43","Cas=
caded Incident from TTO4819554","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site down due to Gen overload // charg=
e reduced","system","281963","04-04-2025 20:05:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_252","NOCINC0004728184","Koweit C=
ity","","04-04-2025 20:05:17","04-04-2025 19:41:07","04-04-2025 23:21:43","=
Cascaded Incident from TTO4819554","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site down due to Gen overload // ch=
arge reduced","system","281973","04-04-2025 20:05:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_800","NOCINC0004728182","ODZA CIT=
E MBIA","","04-04-2025 20:05:17","04-04-2025 19:41:07","04-04-2025 23:21:43=
","Cascaded Incident from TTO4819554","Albran Byorel","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","site down due to Gen overload //=
 charge reduced","system","281967","04-04-2025 20:05:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0004728181","Mbedoumo=
u - Ekali","","04-04-2025 20:05:16","04-04-2025 19:41:07","04-04-2025 23:21=
:43","Cascaded Incident from TTO4819554","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site down due to Gen overload=
 // charge reduced","system","281970","04-04-2025 20:05:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0004728180","Carrefou=
rt Nkomo","","04-04-2025 20:05:16","04-04-2025 19:41:07","04-04-2025 23:21:=
43","Cascaded Incident from TTO4819554","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site down due to Gen overlo=
ad // charge reduced","system","281963","04-04-2025 20:05:16","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004728074","Tou=
ring Club International","IHS_YND_174, IHS_YND_343, IHS_YND_800, IHS_YND_16=
1, IHS_YND_252, IHS_YND_723, IHS_YND_328, IHS_YND_794, IHS_YND_160, IHS_YND=
_528, IHS_YND_746, IHS_YND_553, IHS_YND_256, IHS_YND_291, IHS_YND_728, IHS_=
YND_336, IHS_YND_527, IHS_YND_715, IHS_YND_281, IHS_YND_595, IHS_YND_807, I=
HS_YND_290, IHS_YND_312, IHS_YND_253, IHS_YND_535, IHS_YND_411, IHS_YND_283=
","04-04-2025 19:50:18","04-04-2025 19:41:07","04-04-2025 23:21:43","site d=
own due to Gen overload // charge reduced","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","site down due to Gen overload //=
 charge reduced","edwige.kapawo@matech-cameroun.com","552","04-04-2025 19:5=
0:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004727923","Bondjock=
","","04-04-2025 19:25:55","04-04-2025 18:03:38","04-04-2025 19:42:03","Cas=
caded Incident from TTO4818672","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
start and stopped with high temp alarm // he added water and manually start=
 the gen","system","1223042","04-04-2025 19:25:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004727921","Mbeng","=
","04-04-2025 19:25:54","04-04-2025 18:03:38","04-04-2025 19:42:03","Cascad=
ed Incident from TTO4818672","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen sta=
rt and stopped with high temp alarm // he added water and manually start th=
e gen","system","1223043","04-04-2025 19:25:54","MATECH CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004727796","Ngu=
ila","","04-04-2025 19:10:08","04-04-2025 18:23:49","04-04-2025 20:16:49","=
Site went down because gen failed to start with alarm undervoltage // He re=
set gen card and gen manually started","Parker Tchoup","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Site went down because gen fail=
ed to start with alarm undervoltage // He reset gen card and gen manually s=
tarted","edwige.kapawo@matech-cameroun.com","2781","04-04-2025 19:10:08","M=
ATECH CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0004727313","Min=
ka","IHS_YND_369, IHS_YND_553, IHS_YND_372","04-04-2025 18:05:49","04-04-20=
25 18:03:38","04-04-2025 19:42:43","Grid outage, site went down because gen=
 start and stopped with high temp alarm // he added water and manually star=
t the gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Hi=
gh Engine Temp - Coolant Level Issue","Grid outage, site went down because =
gen start and stopped with high temp alarm // he added water and manually s=
tart the gen","edwige.kapawo@matech-cameroun.com","132","04-04-2025 18:05:4=
9","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004726773","A=
wae Ewonkan","","04-04-2025 17:04:53","04-04-2025 16:52:36","04-04-2025 20:=
27:38","Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline is=
 informed and confirmed//he reduced the load","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen ove=
rload(20kva,280 A) IHS SS Pascaline is informed and confirmed//he reduced t=
he load","rouselle.schoune@ihstowers.com","738","04-04-2025 17:04:53","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004726620","A=
wae Escalier","","04-04-2025 16:48:52","04-04-2025 16:16:45","04-04-2025 20=
:31:50","Grid fluctuation,site went dowwn because Gen failed to start due t=
o Grid bad voltage//He bypassed the Grid and sarted gen manaully","Albran B=
yorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation,site went dowwn because Gen failed to start due to G=
rid bad voltage//He bypassed the Grid and sarted gen manaully","cedric.tian=
i@matech-cameroun.com","1928","04-04-2025 16:48:52","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004726581","Nko=
l-Mbanda","","04-04-2025 16:44:42","04-04-2025 16:35:31","04-04-2025 18:15:=
31","Active// No power Issue Site on Grid Ubai =3D54,3V, The FME The TX FME=
 Mbah Hosiah (674007438) is informed.","MINKA NICOLAS","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
 No power Issue Site on Grid Ubai =3D54,3V, The FME The TX FME Mbah Hosiah =
(674007438) is informed.","cedric.tiani@matech-cameroun.com","552","04-04-2=
025 16:44:42","MATECH CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0004726533","Clu=
b France","","04-04-2025 16:38:48","04-04-2025 16:37:30","04-04-2025 18:16:=
30","Grid outage,no space to deploy MDG // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage,no space to=
 deploy MDG // Grid return","cedric.tiani@matech-cameroun.com","79","04-04-=
2025 16:38:48","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004726493","O=
dza","","04-04-2025 16:34:38","04-04-2025 14:54:25","04-04-2025 19:05:14","=
Grid outage, site went down because gen failed to start due to hybrid syste=
m malfunction // Gen manually started","Albran Byorel","Equipment Repair","=
Passive","Hybrid","Hybrid Module","Grid outage, site went down because gen =
failed to start due to hybrid system malfunction // Gen manually started","=
cedric.tiani@matech-cameroun.com","6014","04-04-2025 16:34:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004726283","Nkolfon =
Cimencam","","04-04-2025 15:53:57","04-04-2025 12:39:37","04-04-2025 13:54:=
46","Cascaded Incident from TTO4817512","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen failed due to gen overload(17KVA, 190A) //He reduiced the load, =
site on gen","system","293138","04-04-2025 15:53:57","MATECH CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004726272","M=
eyo","IHS_YND_762","04-04-2025 15:52:18","04-04-2025 12:39:37","04-04-2025 =
13:54:46","BACTRACKING  Grid outage, site went down because gen failed to s=
tart due to gen overload(17KVA, 190A) //He reduiced the load, site on gen",=
"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage, site went down because gen failed due to gen overload(17KVA, =
190A) //He reduiced the load, site on gen","cedric.tiani@matech-cameroun.co=
m","11562","04-04-2025 15:52:18","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0004726261","GSO=
","","04-04-2025 15:49:58","04-04-2025 15:41:45","04-04-2025 17:01:45","Sit=
e went down because Gen failed to start due to ATS malfunction// He reset A=
TS and started Gen manually","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","ATS-AMF Issue","Site went down because Gen failed to start =
due to ATS malfunction// He reset ATS and started Gen manually","cedric.tia=
ni@matech-cameroun.com","494","04-04-2025 15:49:58","MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004726116","Nko=
abang MTN","","04-04-2025 15:35:32","04-04-2025 15:11:21","04-04-2025 16:11=
:57","Grid outage, Site went down because Gen overload(20, 300A) SS IHS Alp=
honse DEFFO is informed// He reduiced load and started Gen manualy","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen overload(20, 300A) SS IHS Alphonse DEFF=
O is informed// He reduiced load and started Gen manualy","cedric.tiani@mat=
ech-cameroun.com","1452","04-04-2025 15:35:32","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004726070","Eki=
e sud","","04-04-2025 15:29:13","04-04-2025 15:18:52","04-04-2025 16:58:38"=
,"Grid outage, site went down because gen failed to start due to (hybrid sy=
stem and automatism) dysfunctioning// Gen manually started","Albran Byorel"=
,"Equipment Repair","Passive","Hybrid","Hybrid Module","Grid outage, site w=
ent down because gen failed to start due to (hybrid system and automatism) =
dysfunctioning// Gen manually started","gerard.tchangoue@matech-cameroun.co=
m","622","04-04-2025 15:29:13","MATECH CMR"
"Closed Complete","Site Down","T1591","IHS_YND_172","NOCINC0004725898","Tra=
dex-Nkomo","","04-04-2025 15:02:32","04-04-2025 15:01:19","04-04-2025 18:28=
:19","Site down due to GEn over voltage // Reset and start gen ","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Site d=
own due to GEn over voltage // Reset and start gen ","gerard.tchangoue@mate=
ch-cameroun.com","74","04-04-2025 15:02:32","MATECH CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004725894","Mvo=
g-Manga","","04-04-2025 15:01:51","04-04-2025 15:00:04","04-04-2025 16:11:1=
1","Gen overload // reducing the site load ","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Gen overload // reducing the s=
ite load ","gerard.tchangoue@matech-cameroun.com","109","04-04-2025 15:01:5=
1","MATECH CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0004725889","San=
ta Barbara Yde","","04-04-2025 15:00:35","04-04-2025 14:59:23","05-04-2025 =
19:03:06","Active//No power issue on site; Ubaie: 54.8 V site on Grid The F=
ME Synphorien//691316854// from Huawei is informed. and Notice that there i=
s rain in the area","Delor Telezing","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on =
site; Ubaie: 54.8 V site on Grid The FME Synphorien//691316854// from Huawe=
i is informed. and Notice that there is rain in the area","gerard.tchangoue=
@matech-cameroun.com","72","04-04-2025 15:00:35","MATECH CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0004725887","Hot=
el de Ville Yde","","04-04-2025 15:00:03","04-04-2025 14:57:53","04-04-2025=
 15:00:35","Active//No power issue on site ,site on Grid wiith Ubaie=3D54.1=
 V The TX FME Brice Tsague/ 690286359/ Huawei is informed ","Paul BIBOUM","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Site went down because SS HIS Bate and Felix Zambe was working o=
n site","gerard.tchangoue@matech-cameroun.com","131","04-04-2025 15:00:03",=
"MATECH CMR"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0004725886","Nko=
lndom","","04-04-2025 14:59:31","04-04-2025 14:52:20","04-04-2025 21:24:34"=
,"Active//No power isue on site ,site on Grid with Ubaie=3D53 V The TX FME =
Synphorien //691316854 from huawei is informed.Noticed dysfunction at the M=
TN BTS","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Active//No power isue on site ,site o=
n Grid with Ubaie=3D53 V The TX FME Synphorien //691316854 from huawei is i=
nformed.Noticed dysfunction at the MTN BTS","gerard.tchangoue@matech-camero=
un.com","431","04-04-2025 14:59:31","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0004725742","O=
lembe","","04-04-2025 14:39:50","04-04-2025 14:19:33","04-04-2025 16:08:46"=
,"Active//No power issue on site Ubaie =3D53.4V site on Grid The TX FME Syn=
phorien (650257151) from Huawei is informed.Noticed disjonction at the ocm"=
,"Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie =3D53.4=
V site on Grid The TX FME Synphorien (650257151) from Huawei is informed.No=
ticed disjonction at the ocm","gerard.tchangoue@matech-cameroun.com","1218"=
,"04-04-2025 14:39:50","MATECH CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0004725675","A=
ngongo","","04-04-2025 14:31:36","04-04-2025 13:42:24","04-04-2025 14:00:15=
","No power issue on site U=3D54v site on gen Tx Etienne of huawei is infor=
med","Fanda Brice","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v site on gen T=
x Etienne of huawei is informed","olivier.kwedi@ihstowers.com","2953","04-0=
4-2025 14:31:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_141","NOCINC0004725628","New-Marc=
he-Melen","","04-04-2025 14:23:43","04-04-2025 13:51:09","04-04-2025 14:27:=
54","Cascaded Incident from TTO4816763","Paul BIBOUM","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, No space to deploy =
MDG // Grid return","system","389510","04-04-2025 14:23:43","MATECH CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004725595","L=
eboudi","","04-04-2025 14:18:44","04-04-2025 12:29:12","04-04-2025 14:39:07=
","Active: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(6911=
44435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435) =
from Huawei is informed","olivier.kwedi@ihstowers.com","6573","04-04-2025 1=
4:18:44","MATECH CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0004725585","Ebe=
ba","","04-04-2025 14:15:49","04-04-2025 14:13:23","04-04-2025 14:34:40","S=
ite Went Down due to high temp // added water","Fanda Brice","Equipment Rep=
air","Passive","ACDG Gen","Gen Temp High","Site Went Down due to high temp =
// added water","edwige.kapawo@matech-cameroun.com","147","04-04-2025 14:15=
:49","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004725572","Imm=
-Olympique","","04-04-2025 14:13:40","04-04-2025 13:57:03","05-04-2025 20:1=
7:37","Active//No power issue on Site ,Site on Grid with Ubaie=3D52V The TX=
 FME Mohamadou mouam //691144435 from Huawei is informed","Paul BIBOUM","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on Site ,Site on Grid with Ubaie=3D52V The =
TX FME Mohamadou mouam //691144435 from Huawei is informed","ludivine.ngama=
leu@ihstowers.com","998","04-04-2025 14:13:40","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004725564","C=
omplexe-BEAC","","04-04-2025 14:12:20","04-04-2025 14:01:30","04-04-2025 15=
:42:05","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started manually","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup // Gen started manually","edwige.kapawo@matech=
-cameroun.com","651","04-04-2025 14:12:20","MATECH CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0004725559","O=
bili Carrefour","","04-04-2025 14:10:29","04-04-2025 13:08:17","04-04-2025 =
15:33:28","Grid fluctuation, site went down because Gen started and stopped=
 due to Grid bad voltage// He bypassed Grid and Gen manualy started","Paul =
BIBOUM","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, site went down because Gen started and stopped due=
 to Grid bad voltage// He bypassed Grid and Gen manualy started","olivier.k=
wedi@ihstowers.com","3733","04-04-2025 14:10:29","MATECH CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004725558","An-=
Marche-Melen","IHS_YND_141","04-04-2025 14:10:25","04-04-2025 13:51:09","04=
-04-2025 14:27:54","Grid outage, No space to deploy MDG // Grid return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage, No space to deploy MDG // Grid return","ludivine.ngamaleu@ihstowers.c=
om","1157","04-04-2025 14:10:25","MATECH CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004725525","M=
efou-Assi","IHS_YND_537","04-04-2025 14:05:45","04-04-2025 13:17:26","04-04=
-2025 16:06:47","Grid outage, site went down because gen fails to start due=
 to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // He reduice =
the load and manually start the gen","Fanda Brice","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid outage, site went down because gen =
fails to start due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is infor=
med // He reduice the load and manually start the gen","olivier.kwedi@ihsto=
wers.com","2900","04-04-2025 14:05:45","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004725467","Nko=
lnda","","04-04-2025 13:56:28","04-04-2025 13:54:11","04-04-2025 14:08:51",=
"Site went Down due to Eneo bad voltage // He put site on Gen","Albran Byor=
el","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Site went Down due to Eneo bad voltage // He put site on Gen","edwige.ka=
pawo@matech-cameroun.com","138","04-04-2025 13:56:28","MATECH CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0004725454","A=
hala","","04-04-2025 13:53:36","04-04-2025 13:39:22","04-04-2025 20:56:20",=
"Disjunction in the BTS OCM due to load increase// CB reaarm","Hyemafo Gild=
as","Equipment Repair","Passive","Control Panel","Circuit Breaker Tripped",=
"Disjunction in the BTS OCM due to load increase// CB reaarm
","edwige.kapawo@matech-cameroun.com","855","04-04-2025 13:53:36","MATECH C=
MR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004725432","Mfo=
u EPC","","04-04-2025 13:52:18","04-04-2025 13:39:04","04-04-2025 13:55:16"=
,"Site Went Down due to high temp // added water","Mba Lazare Herve","Equip=
ment Repair","Passive","ACDG Gen","Gen Temp High","Site Went Down due to hi=
gh temp // added water","ludivine.ngamaleu@ihstowers.com","796","04-04-2025=
 13:52:18","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0004725418","Nko=
langaa","","04-04-2025 13:50:52","04-04-2025 13:38:37","05-04-2025 20:35:57=
","Active//No power issue on site Ubaie =3D53V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed.","Mba Lazare Herve","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site Ubaie =3D53V site on Grid The TX FME Henri (6999=
49693) from Huawei is informed.","ludivine.ngamaleu@ihstowers.com","736","0=
4-04-2025 13:50:52","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004725400","Men=
dong vallee","","04-04-2025 13:47:21","04-04-2025 13:32:07","04-04-2025 16:=
36:22","	Grid outage site went down because Gen over load (20KVA; 300A) // =
Grid return IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Brice","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","	Grid outage site =
went down because Gen over load (20KVA; 300A) // Grid return IHS F=E9lix Za=
mb=E9 is informed and confirmed","ludivine.ngamaleu@ihstowers.com","916","0=
4-04-2025 13:47:21","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004725309","B=
arriere IHS","","04-04-2025 13:33:18","04-04-2025 13:17:58","04-04-2025 14:=
05:25","No power issue on site Ubay 53,5V site on Grid, disjunction of CB 1=
25A in the OCM Bay / Disjunctor rearm by Mbah Osiah (674007438/huawei)","Hy=
emafo Gildas","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","No power issue on site Ubay 53,5V site on Grid, d=
isjunction of CB 125A in the OCM Bay / Disjunctor rearm by Mbah Osiah (6740=
07438/huawei)","gerard.tchangoue@matech-cameroun.com","921","04-04-2025 13:=
33:18","MATECH CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004725301","Eto=
ug ebe Carrefour","","04-04-2025 13:32:02","04-04-2025 13:17:31","04-04-202=
5 14:31:11","Grid outage, Site went down because Gen failed to start due to=
 Grid bad voltag and poor backup //He bypassed Grid and started Gen manualy=
","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid outage, Site went down because Gen failed to start d=
ue to Grid bad voltag and poor backup //He bypassed Grid and started Gen ma=
nualy","ludivine.ngamaleu@ihstowers.com","871","04-04-2025 13:32:02","MATEC=
H CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004725299","Emana Ly=
cee","","04-04-2025 13:31:17","04-04-2025 13:22:53","04-04-2025 16:05:53","=
Cascaded Incident from TTO4816204","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen start and stopped with high temp alarm // He added water and manuall=
y start the gen","system","1333342","04-04-2025 13:31:17","MATECH CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004725275","S=
IMBOCK BONAMBAPE","","04-04-2025 13:29:13","04-04-2025 13:17:38","04-04-202=
5 14:00:17","ACTIVE// No power issue on site, site on Grid with Ubaie=3D 54=
,4V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed.","Hyemafo =
Gildas","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","ACTIVE// No power issue on site, site on Grid with Ubai=
e=3D 54,4V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed.","e=
dwige.kapawo@matech-cameroun.com","696","04-04-2025 13:29:13","MATECH CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004725172","M=
EFOU ASSI","","04-04-2025 13:21:26","04-04-2025 13:17:26","04-04-2025 16:10=
:16","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Awaiting RCA","edwige.kapawo@matech-cameroun.com","391450","04-0=
4-2025 13:21:26","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004725160","O=
lembe-Terminus","","04-04-2025 13:20:41","04-04-2025 13:12:35","04-04-2025 =
18:55:35","Site on gen due to grid outage,site went down due to relay Q11 f=
aulty// relay Q11 replaced","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","Relay","Site on gen due to grid outage,site went down due =
to relay Q11 faulty// relay Q11 replaced","edwige.kapawo@matech-cameroun.co=
m","488","04-04-2025 13:20:41","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004725137","E=
mana lycee 2","IHS_YND_274","04-04-2025 13:17:03","04-04-2025 12:47:53","04=
-04-2025 16:05:53","Grid outage, site went down because gen start and stopp=
ed with high temp alarm // He added water and manually start the gen","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Te=
mp - Coolant Level Issue","Grid outage, site went down because gen start an=
d stopped with high temp alarm // He added water and manually start the gen=
","olivier.kwedi@ihstowers.com","1751","04-04-2025 13:17:03","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004725088","M=
EHANDAN","","04-04-2025 13:11:40","04-04-2025 12:36:27","06-04-2025 04:40:3=
7","Grid outage,Site went down because Gen failed to start (investigation o=
ngoing)","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid outage,Site went down because Gen failed to start (inves=
tigation ongoing)","olivier.kwedi@ihstowers.com","2115","04-04-2025 13:11:4=
0","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004725014","S=
atcom","","04-04-2025 12:58:46","04-04-2025 12:36:39","04-04-2025 13:40:46"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D51V .The Tx Fme Arma=
nd nguetsa(691144412) From huawei is informed.","Delor Telezing","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D51V .The Tx Fme Arma=
nd nguetsa(691144412) From huawei is informed.","olivier.kwedi@ihstowers.co=
m","1328","04-04-2025 12:58:46","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004725012","Ole=
mbe MTN","","04-04-2025 12:58:24","04-04-2025 12:34:17","05-04-2025 00:10:3=
3","site down due to replacement of Grid contactor // contactor replaced","=
Fabrice Pouakam","Installation Activity","Passive","Planned Activity","Inst=
allation Activity","site down due to replacement of Grid contactor // conta=
ctor replaced","ludivine.ngamaleu@ihstowers.com","1448","04-04-2025 12:58:2=
4","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004725011","Oko=
lo Kilombo","","04-04-2025 12:58:17","04-04-2025 12:38:02","04-04-2025 14:4=
0:17","Grid outage, site went down because gen fails to start due to Gen ca=
ble faulty // He bypassed gen cable and gen manually started","Fabrice Poua=
kam","Equipment Repair","Passive","Infrastructure","Armoured Cable","Grid o=
utage, site went down because gen fails to start due to Gen cable faulty //=
 He bypassed gen cable and gen manually started","edwige.kapawo@matech-came=
roun.com","1216","04-04-2025 12:58:17","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004725006","Odz=
a II OCM","","04-04-2025 12:57:20","04-04-2025 12:38:07","04-04-2025 14:11:=
22","Site went Down due to ATS and Gen card Faulty // Grid restaured","Albr=
an Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Si=
te went Down due to ATS and Gen card Faulty // Grid restaured","edwige.kapa=
wo@matech-cameroun.com","1154","04-04-2025 12:57:20","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004725001","E=
MANA BILICK CITY","","04-04-2025 12:56:02","04-04-2025 12:30:55","04-04-202=
5 13:40:39","Grid outage.gen failed to start due to automation malfunctionn=
ing//Gen manually started","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","ATS-AMF Issue","Grid outage.gen failed to start due to auto=
mation malfunctionning//Gen manually started","edwige.kapawo@matech-camerou=
n.com","1509","04-04-2025 12:56:02","MATECH CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004724992","Nko=
lafeme","","04-04-2025 12:54:27","04-04-2025 12:29:57","04-04-2025 14:42:55=
","Grid outage, Site went down due to Gen overload(20KVA, 375A) SS IHS Pasc=
aline confirmed// he Reduced the Load and Manually Started the Gen","TIENTC=
HEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Grid outage, Site went down due to Gen overload(20KVA, 375A) SS IHS Pas=
caline confirmed// he Reduced the Load and Manually Started the Gen","ludiv=
ine.ngamaleu@ihstowers.com","1471","04-04-2025 12:54:27","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004724977","AWA=
E OCM","","04-04-2025 12:53:43","04-04-2025 12:38:19","04-04-2025 13:28:39"=
,"Site went down because of the malfunctioning  of the  ZTE PWC  // He rese=
t the PWC","Mba Lazare Herve","Equipment Repair","Passive","Control Panel",=
"ATS-AMF Issue","Site went down because of the malfunctioning  of the  ZTE =
PWC  // He reset the PWC","edwige.kapawo@matech-cameroun.com","925","04-04-=
2025 12:53:43","MATECH CMR"
"Closed Complete","Site Down","T0535","IHS_YND_234","NOCINC0004724918","Oyo=
mabang MTN","","04-04-2025 12:43:23","04-04-2025 12:29:13","05-04-2025 21:4=
2:36","No power issue on site ,site on Gen with Ubaie =3D 53V The FME TX Mo=
uhamadou //699949072// From Huawei is informed.","TIENTCHEU NZETCHIEU GAEL"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue on site ,site on Gen with Ubaie =3D 53V The FME=
 TX Mouhamadou //699949072// From Huawei is informed.","gerard.tchangoue@ma=
tech-cameroun.com","851","04-04-2025 12:43:23","MATECH CMR"
"Closed Complete","Site Down","T2222","IHS_YND_697","NOCINC0004724866","Nom=
ayos-IHS","","04-04-2025 12:37:03","04-04-2025 12:17:46","04-04-2025 12:35:=
46","Grid outage, site went down due to gen Overload(15KVA, 170A), Felix Za=
mbe IHS is informed // Grid return","Fanda Brice","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen Ov=
erload(15KVA, 170A), Felix Zambe IHS is informed // Grid return","gerard.tc=
hangoue@matech-cameroun.com","1158","04-04-2025 12:37:03","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0004724800","Nsi=
meyong","IHS_YND_698","04-04-2025 12:26:43","04-04-2025 12:13:30","04-04-20=
25 13:08:08","Eneo outage, site down due to Gen Overload // Eneo return","M=
INKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","En=
eo outage, site down due to Gen Overload // Eneo return","edwige.kapawo@mat=
ech-cameroun.com","794","04-04-2025 12:26:43","MATECH CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0004724762","EBO=
M","","04-04-2025 12:21:28","04-04-2025 12:13:30","04-04-2025 13:08:08","Ac=
tive No power issue on site U=3D54v site on Grid Lionel//694693436 of huawe=
i is informed.","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Active No power issue on site U=3D54v site on Grid Li=
onel//694693436 of huawei is informed.","edwige.kapawo@matech-cameroun.com"=
,"1016","04-04-2025 12:21:28","MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004724753","Mes=
sassi okolo","","04-04-2025 12:20:17","04-04-2025 12:08:01","04-04-2025 14:=
40:22","Grid outage, Gen failed to start due to Faulty cable of start order=
 and burn charger static  // Gen start manually","Fabrice Pouakam","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Turbo Charger","Grid outage, Gen fa=
iled to start due to Faulty cable of start order and burn charger static  /=
/ Gen start manually
","edwige.kapawo@matech-cameroun.com","737","04-04-2025 12:20:17","MATECH C=
MR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004724749","Bar=
riere","","04-04-2025 12:19:08","04-04-2025 12:12:56","04-04-2025 12:56:46"=
,"site down due to gen overload // reducing the site load ","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","site down due =
to gen overload // reducing the site load ","edwige.kapawo@matech-cameroun.=
com","373","04-04-2025 12:19:08","MATECH CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004724741","Mes=
sassi 2","","04-04-2025 12:17:54","04-04-2025 12:10:44","04-04-2025 13:07:0=
4","Grid outage, Gen failed to start due High temp Alarm // Water add Gen S=
tart Mnually","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","Ge=
n Temp High","Grid outage, Gen failed to start due High temp Alarm // Water=
 add Gen Start Mnually
","edwige.kapawo@matech-cameroun.com","431","04-04-2025 12:17:54","MATECH C=
MR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004724594","E=
koumdoum","","04-04-2025 12:06:08","04-04-2025 11:48:52","04-04-2025 13:01:=
52","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS Pa=
scaline is informed and confirmed//We reduced load and gen manually started=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS Pasca=
line is informed and confirmed//We reduced load and gen manually started","=
edwige.kapawo@matech-cameroun.com","1037","04-04-2025 12:06:08","MATECH CMR=
"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0004724565","F=
OUGEROLE","","04-04-2025 12:02:35","04-04-2025 11:46:24","04-04-2025 12:09:=
15","Active: no power issue, site is on grid with Ubaie=3D53V, Symphorien (=
650257151) fom Huawei is informed","Siligap Boris","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no p=
ower issue, site is on grid with Ubaie=3D53V, Symphorien (650257151) fom Hu=
awei is informed","edwige.kapawo@matech-cameroun.com","972","04-04-2025 12:=
02:35","MATECH CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0004724509","Ngo=
usso-Savana","","04-04-2025 11:58:04","04-04-2025 11:44:50","04-04-2025 12:=
16:48","Grid outage ,site went down because Gen started and stopped due to =
Gen overload (20KVA,260A)//Grid return","Siligap Boris","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went down because=
 Gen started and stopped due to Gen overload (20KVA,260A)//Grid return","ed=
wige.kapawo@matech-cameroun.com","794","04-04-2025 11:58:04","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004724499","Ako=
k Ndoe Yde","","04-04-2025 11:56:16","04-04-2025 11:49:04","04-04-2025 13:3=
6:21","Grid outage, Site down due to poor battery backup // Gen started man=
ually","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, Site down due to poor battery backup =
// Gen started manually","edwige.kapawo@matech-cameroun.com","433","04-04-2=
025 11:56:16","MATECH CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004724496","CRH=
-Etoug-Ebe","","04-04-2025 11:55:33","04-04-2025 11:49:20","04-04-2025 12:2=
8:20","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"edwige.kapawo@matech-cameroun.com","374","04-04-2025 11:55:33","MATECH CMR=
"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004724408","Bit=
eng-Maetur","","04-04-2025 11:49:38","04-04-2025 11:28:26","04-04-2025 13:4=
4:18","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) // He reduced the load","Mba Lazare Herve","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen started and stopped due to Gen overload(20kva, 280A) // He=
 reduced the load","edwige.kapawo@matech-cameroun.com","1273","04-04-2025 1=
1:49:38","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004724328","Par=
adis Hotel","","04-04-2025 11:31:00","04-04-2025 11:18:29","04-04-2025 12:1=
6:32","Site went Down due to Alarm Over frequency // reset and start","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site =
went Down due to Alarm Over frequency // reset and start","edwige.kapawo@ma=
tech-cameroun.com","752","04-04-2025 11:31:00","MATECH CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004724289","M=
bankomo IHS","","04-04-2025 11:21:07","04-04-2025 11:02:30","04-04-2025 12:=
02:31","Grid outage gen failed to start due to card GE dysfunctionned//We r=
eset card GE and gen manually started ","Fanda Brice","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to start =
due to card GE dysfunctionned//We reset card GE and gen manually started ",=
"edwige.kapawo@matech-cameroun.com","1118","04-04-2025 11:21:07","MATECH CM=
R"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0004724276","Nko=
mo stade","","04-04-2025 11:19:43","04-04-2025 11:13:28","04-04-2025 11:19:=
47","Site went down due to Insufficient of rectifier on site // Site stabil=
ized","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to Insufficient of rectifier on site // Site =
stabilized","gerard.tchangoue@matech-cameroun.com","376","04-04-2025 11:19:=
43","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004724253","Awa=
e Ewonkan","","04-04-2025 11:16:24","04-04-2025 11:11:11","04-04-2025 12:42=
:22","Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline is i=
nformed and confirmed//site stabilised","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen overload(=
20kva,280 A) IHS SS Pascaline is informed and confirmed//site stabilised","=
edwige.kapawo@matech-cameroun.com","314","04-04-2025 11:16:24","MATECH CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0004724245","Mba=
lla 4","","04-04-2025 11:14:48","04-04-2025 11:13:32","04-04-2025 11:25:32"=
,"Grid outage,Site went down before gen failed to start  (investigation ong=
oing)","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","Grid outage,Site went down before gen failed to start  (invest=
igation ongoing)","edwige.kapawo@matech-cameroun.com","77","04-04-2025 11:1=
4:48","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004724219","Ngo=
usso Vallee","","04-04-2025 11:12:50","04-04-2025 11:05:21","04-04-2025 12:=
16:50","Grid outage, Site went down because Gen started and stopped with ""=
low oil pressure"" alarm// He reset card GE and gen manually started","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, Site went down because Gen started and stopped with ""low oil =
pressure"" alarm// He reset card GE and gen manually started","gerard.tchan=
goue@matech-cameroun.com","450","04-04-2025 11:12:50","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004724059","Minka","=
","04-04-2025 10:42:46","04-04-2025 10:32:54","04-04-2025 10:44:40","Cascad=
ed Incident from TTO4814980","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","site impacted by Ngoumou(T0169)","system","264=
477","04-04-2025 10:42:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004724060","Akono","=
","04-04-2025 10:42:46","04-04-2025 10:32:54","04-04-2025 10:44:40","Cascad=
ed Incident from TTO4814980","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","site impacted by Ngoumou(T0169)","system","264=
477","04-04-2025 10:42:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004724058","OTELE MT=
N","","04-04-2025 10:42:46","04-04-2025 10:32:54","04-04-2025 10:44:40","Ca=
scaded Incident from TTO4814980","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","site impacted by Ngoumou(T0169)","system",=
"264478","04-04-2025 10:42:46","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004724057","OLAMA","=
","04-04-2025 10:42:45","04-04-2025 10:32:54","04-04-2025 10:44:40","Cascad=
ed Incident from TTO4814980","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","site impacted by Ngoumou(T0169)","system","264=
477","04-04-2025 10:42:45","MATECH CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004724052","Mom=
","IHS_YND_687, IHS_YND_531, IHS_YND_371, IHS_YND_365","04-04-2025 10:41:05=
","04-04-2025 10:32:54","04-04-2025 10:44:40","site impacted by Ngoumou(T01=
69)","Fanda Brice","Customer Equipment Failure","Active","Active Equipment =
Failure","Affected by 3rd Party Site","site impacted by Ngoumou(T0169)","ge=
rard.tchangoue@matech-cameroun.com","492","04-04-2025 10:41:05","MATECH CMR=
"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004724017","MBA=
LNGONG LYCEE","","04-04-2025 10:31:52","04-04-2025 10:17:40","04-04-2025 18=
:32:04","Grid Outage Site went down due to Gen overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went d=
own due to Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and conf=
irmed // Grid return","edwige.kapawo@matech-cameroun.com","854","04-04-2025=
 10:31:52","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004723999","S=
imbock OCM","","04-04-2025 10:26:54","03-04-2025 08:00:37","03-04-2025 08:1=
1:06","site down due to alarm high temp on GEN // water added in the radiat=
or","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","site down due to alarm high temp on GEN =
// water added in the radiator","gerard.tchangoue@matech-cameroun.com","951=
78","04-04-2025 10:26:54","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004723934","Ole=
mbe MTN","","04-04-2025 10:18:22","04-04-2025 10:15:59","04-04-2025 10:18:5=
9","Site went down due to insufficiency of rectifiers,  // Added rectifier =
ongoing","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers,  // Added r=
ectifier ongoing","gerard.tchangoue@matech-cameroun.com","145","04-04-2025 =
10:18:22","MATECH CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0004723927","C=
NR","","04-04-2025 10:16:57","04-04-2025 10:11:39","04-04-2025 10:36:55","N=
o power issue site on grid with U=3D53.4V Mohamadou from Huaie is informed/=
/site up at 10:36 AM","Mboua Thierry","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gr=
id with U=3D53.4V Mohamadou from Huaie is informed//site up at 10:36 AM","e=
dwige.kapawo@matech-cameroun.com","319","04-04-2025 10:16:57","MATECH CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004723914","C=
rf-Nsam","","04-04-2025 10:15:17","04-04-2025 10:13:11","04-04-2025 10:16:5=
5","Grid outage, Site went down before Gen start due to poor backup // Gen =
started automatically (Awaitting Configuration of battery backup)","MINKA N=
ICOLAS","Equipment Repair","Passive","Control Panel","Power Cabinet - Batte=
ry Low","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started automatically (Awaitting Configuration of battery backup)","ed=
wige.kapawo@matech-cameroun.com","128","04-04-2025 10:15:17","MATECH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0004723840","Mvo=
g-Ada_OCM","","04-04-2025 10:11:17","04-04-2025 09:59:50","04-04-2025 10:41=
:42","Site down due to disjonction in the OCM bay.// CB rearmed.","","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Iss=
ue","Site down due to disjonction in the OCM bay.// CB rearmed.","edwige.ka=
pawo@matech-cameroun.com","1361","04-04-2025 10:11:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004723783","Abang","=
","04-04-2025 09:59:34","04-04-2025 09:47:59","04-04-2025 12:05:59","Cascad=
ed Incident from TTO4814665","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because the Cb(125A) of=
 PWC dysfonction due to load increased // He reamed the Cb","system","27451=
8","04-04-2025 09:59:34","MATECH CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004723776","N=
kolangaa","IHS_YND_290","04-04-2025 09:58:46","04-04-2025 09:47:59","04-04-=
2025 12:05:59","Site went down because the Cb(125A) of PWC dysfonction due =
to load increased // He reamed the Cb","Mba Lazare Herve","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site w=
ent down because the Cb(125A) of PWC dysfonction due to load increased // H=
e reamed the Cb","edwige.kapawo@matech-cameroun.com","648","04-04-2025 09:5=
8:46","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004723759","N=
goulmekong-Nord","","04-04-2025 09:55:22","04-04-2025 09:49:14","04-04-2025=
 10:14:21","Site went down because insufficient of rectifier on site//site =
stabilized","Siligap Boris","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down because insufficient of rectifier on site//sit=
e stabilized","edwige.kapawo@matech-cameroun.com","369","04-04-2025 09:55:2=
2","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004723741","Nko=
zoa","","04-04-2025 09:52:17","04-04-2025 09:47:57","04-04-2025 10:45:48","=
Site Went Down due to Fuel shortage // Grid restaured","Fabrice Pouakam","F=
uel Outage","Passive","Diesel","Diesel Outage","Site Went Down due to Fuel =
shortage // Grid restaured","gerard.tchangoue@matech-cameroun.com","289","0=
4-04-2025 09:52:17","MATECH CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004723689","H=
-General-Yde","","04-04-2025 09:41:41","04-04-2025 09:31:56","04-04-2025 10=
:17:57","No power issue on site ,site on Grid with Ubaie=3D54.4 V Synphorie=
n of huawei is informed","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 ,site on Grid with Ubaie=3D54.4 V Synphorien of huawei is informed","edwig=
e.kapawo@matech-cameroun.com","585","04-04-2025 09:41:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004723575","SOA VILL=
AGE","","04-04-2025 09:31:38","04-04-2025 09:28:37","04-04-2025 10:24:07","=
Cascaded Incident from TTO4814432","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // He added water and manually =
start the gen","system","289910","04-04-2025 09:31:38","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004723568","SOA=
 TOWN","IHS_YND_323","04-04-2025 09:30:14","04-04-2025 09:26:37","04-04-202=
5 10:24:53","Grid outage, site went down because gen start and stopped with=
 high temp alarm // He added water and manually start the gen","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, s=
ite went down because gen start and stopped with high temp alarm // He adde=
d water and manually start the gen","edwige.kapawo@matech-cameroun.com","25=
0","04-04-2025 09:30:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0004723555","Etoudi 2=
","","04-04-2025 09:27:27","04-04-2025 09:17:56","04-04-2025 09:24:59","Cas=
caded Incident from TTO4814406","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site down due to protection work of =
the transmission that created dysfunctionment in the energy bay // energy b=
ay has been reconfigured","system","1218460","04-04-2025 09:27:27","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004723554","ETOUDI C=
HAPELLE","","04-04-2025 09:27:27","04-04-2025 09:17:56","04-04-2025 09:24:5=
9","Cascaded Incident from TTO4814406","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site down due to protection wo=
rk of the transmission that created dysfunctionment in the energy bay // en=
ergy bay has been reconfigured","system","1218460","04-04-2025 09:27:27","M=
ATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004723544","Eto=
udi","IHS_YND_694, IHS_YND_211","04-04-2025 09:25:50","04-04-2025 09:17:56"=
,"04-04-2025 09:24:59","site down due to protection work of the transmissio=
n that created dysfunctionment in the energy bay // energy bay has been rec=
onfigured ","Fabrice Pouakam","Installation Activity","Passive","Planned Ac=
tivity","Installation Activity","site down due to protection work of the tr=
ansmission that created dysfunctionment in the energy bay // energy bay has=
 been reconfigured","edwige.kapawo@matech-cameroun.com","475","04-04-2025 0=
9:25:50","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004723469","ETO=
UDI Entree du palais","","04-04-2025 09:10:36","04-04-2025 09:08:25","04-04=
-2025 09:26:33","site down due to 2 out of 3 rectifiers crashed  // rectifi=
er reset ","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","site down due to 2 out of 3 rectifiers crashed  // rectifier=
 reset ","edwige.kapawo@matech-cameroun.com","132","04-04-2025 09:10:36","M=
ATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004723451","Mon=
tee Jouvence","","04-04-2025 09:07:57","04-04-2025 09:05:47","04-04-2025 09=
:41:00","Grid outage, site went down Gen failed to start due to ATS Dysfunc=
tioning on Site // He reset it and Site is on Gen","Hyemafo Gildas","Equipm=
ent Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, site we=
nt down Gen failed to start due to ATS Dysfunctioning on Site // He reset i=
t and Site is on Gen","edwige.kapawo@matech-cameroun.com","131","04-04-2025=
 09:07:57","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004723257","Ngo=
usso Vallee","","04-04-2025 08:24:47","04-04-2025 08:03:59","04-04-2025 09:=
01:47","Grid outage, Site went down because Gen started and stopped with ""=
low oil pressure"" alarm// He reset card GE and gen manually started","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, Site went down because Gen started and stopped with ""low oil =
pressure"" alarm// He reset card GE and gen manually started","gerard.tchan=
goue@matech-cameroun.com","1249","04-04-2025 08:24:47","MATECH CMR"
"Closed Complete","Site Down","T2795","IHS_YND_070","NOCINC0004723248","Efo=
ulan","","04-04-2025 08:21:09","04-04-2025 08:15:14","04-04-2025 08:19:49",=
"Grid fluctuation, Site went down because gen failed to start due to grid b=
ad voltage,// He bypassed the Grid and site on Gen","MINKA NICOLAS","Grid S=
upply","Passive","Grid","National Grid - Unstable Grid Supply Issue","Grid =
Fluctuation // Grid Stabilized","gerard.tchangoue@matech-cameroun.com","356=
","04-04-2025 08:21:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0004723221","Etoudi 2=
","","04-04-2025 08:13:03","04-04-2025 08:04:59","04-04-2025 08:33:27","Cas=
caded Incident from TTO4814022","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site down due to protection work of =
the transmission that created dysfunctionment in the energy bay // energy b=
ay has been reconfigured and grid return","system","266388","04-04-2025 08:=
13:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004723219","Abattoir=
","","04-04-2025 08:13:03","04-04-2025 08:04:59","04-04-2025 08:33:27","Cas=
caded Incident from TTO4814022","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site down due to protection work of =
the transmission that created dysfunctionment in the energy bay // energy b=
ay has been reconfigured and grid return","system","266387","04-04-2025 08:=
13:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004723220","ETOUDI C=
HAPELLE","","04-04-2025 08:13:03","04-04-2025 08:04:59","04-04-2025 08:33:2=
7","Cascaded Incident from TTO4814022","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site down due to protection wo=
rk of the transmission that created dysfunctionment in the energy bay // en=
ergy bay has been reconfigured and grid return","system","266387","04-04-20=
25 08:13:03","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004723205","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","04-04-2025 08:10:32","04-04-2=
025 08:04:59","04-04-2025 08:33:27","site down due to protection work of th=
e transmission that created dysfunctionment in the energy bay // energy bay=
 has been reconfigured and grid return","Fabrice Pouakam","Installation Act=
ivity","Passive","Planned Activity","Installation Activity","site down due =
to protection work of the transmission that created dysfunctionment in the =
energy bay // energy bay has been reconfigured and grid return","gerard.tch=
angoue@matech-cameroun.com","334","04-04-2025 08:10:32","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004723189","M=
essa-Carriere OCM","","04-04-2025 08:07:29","04-04-2025 07:57:59","04-04-20=
25 10:17:05","Active//No power issue on Site ,Site on Grid with Ubaie=3D52V=
 The TX FME Mohamadou mouam //691144435 from Huawei is informed","","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on Site ,Site on Grid with Ubaie=3D52V The TX F=
ME Mohamadou mouam //691144435 from Huawei is informed","gerard.tchangoue@m=
atech-cameroun.com","572","04-04-2025 08:07:29","MATECH CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0004722476","A=
v-Germaine","","04-04-2025 05:23:26","04-04-2025 05:17:58","04-04-2025 06:5=
6:58","Grid only, Eneo outage, no space to deploy MGE // eneo return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only=
, Eneo outage, no space to deploy MGE // eneo return","loic.noumsi@matech-c=
ameroun.com","329","04-04-2025 05:23:26","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0004722125","NKO=
NGKARAK","","04-04-2025 02:22:31","04-04-2025 02:07:46","04-04-2025 06:05:2=
0","Site went down because gen stopped with alarm high temp caused by pierc=
ed pellet // he added water in radiator, glued pellet with resin and starte=
d GE","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","A=
CDG - High Engine Temp - Coolant Level Issue","Site went down because gen s=
topped with alarm high temp caused by pierced pellet // he added water in r=
adiator, glued pellet with resin and started GE","gaelle.njiofack@matech-ca=
meroun.com","886","04-04-2025 02:22:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004720966","ETOUDI C=
HAPELLE","","04-04-2025 00:45:05","04-04-2025 00:04:58","04-04-2025 06:20:5=
1","Cascaded Incident from TTO4811342","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site down due to protection wo=
rk of the transmission that created dysfunctionment in the energy bay // en=
ergy bay has been reconfigured and grid return ","system","288135","04-04-2=
025 00:45:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0004720967","Etoudi 2=
","","04-04-2025 00:45:05","04-04-2025 00:04:58","04-04-2025 06:20:51","Cas=
caded Incident from TTO4811342","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site down due to protection work of =
the transmission that created dysfunctionment in the energy bay // energy b=
ay has been reconfigured and grid return ","system","288136","04-04-2025 00=
:45:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004720965","Abattoir=
","","04-04-2025 00:45:05","04-04-2025 00:04:58","04-04-2025 06:20:51","Cas=
caded Incident from TTO4811342","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site down due to protection work of =
the transmission that created dysfunctionment in the energy bay // energy b=
ay has been reconfigured and grid return ","system","288134","04-04-2025 00=
:45:05","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004720770","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","04-04-2025 00:25:13","04-04-2=
025 00:04:58","04-04-2025 06:20:51","site down due to protection work of th=
e transmission that created dysfunctionment in the energy bay // energy bay=
 has been reconfigured and grid return ","Fabrice Pouakam","Installation Ac=
tivity","Passive","Planned Activity","Installation Activity","site down due=
 to protection work of the transmission that created dysfunctionment in the=
 energy bay // energy bay has been reconfigured and grid return ","loic.nou=
msi@matech-cameroun.com","1216","04-04-2025 00:25:13","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004720759","Ako=
k Ndoe Yde","","04-04-2025 00:20:00","04-04-2025 00:08:48","04-04-2025 00:4=
0:11","Grid outage, site down due to poor battery backup // Gen start manua=
lly","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, site down due to poor battery backup //=
 Gen start manually","gaelle.njiofack@matech-cameroun.com","673","04-04-202=
5 00:20:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_801","NOCINC0004720540","HOPITAL =
GENERAL RAIL YDE","","03-04-2025 23:16:19","03-04-2025 22:54:02","04-04-202=
5 00:07:50","Cascaded Incident from TTO4810984","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Rectifiers issue // s=
ite stabilized","system","371265","03-04-2025 23:16:19","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004720455","Pha=
rmacie Bleue","IHS_YND_801","03-04-2025 23:02:07","03-04-2025 22:54:02","04=
-04-2025 00:07:50","Rectifiers issue // site stabilized","Siligap Boris","E=
quipment Repair","Passive","Rectifier","Rectifier Cabinet","Rectifiers issu=
e // site stabilized","franck.nkomot@matech-cameroun.com","486","03-04-2025=
 23:02:07","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004720432","Nko=
londom","","03-04-2025 22:51:54","03-04-2025 22:40:39","03-04-2025 23:09:07=
","","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS Re=
lay Faulty","Grid outage, Site went down because Gen failed to start due to=
 ATS disfunctioning // He reset ATS","franck.nkomot@matech-cameroun.com","6=
76","03-04-2025 22:51:54","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004720162","ETO=
UDI Entree du palais","","03-04-2025 21:53:28","03-04-2025 21:48:12","03-04=
-2025 21:50:28","Grid outage, Site went down before Gen start due to poor b=
ackup // Gen started manually","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Gen started manually","cedric.tia=
ni@matech-cameroun.com","318","03-04-2025 21:53:28","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004720150","C=
rf-Nkolbisson","","03-04-2025 21:52:09","03-04-2025 21:44:55","03-04-2025 2=
3:50:48","	Disjunction in the energie bay due to the site load which increa=
sed there from (we need second depart)// disjunctor rearm","TIENTCHEU NZETC=
HIEU GAEL","Equipment Repair","Passive","Control Panel","Circuit Breaker Tr=
ipped","	Disjunction in the energie bay due to the site load which increase=
d there from (we need second depart)// disjunctor rearm","cedric.tiani@mate=
ch-cameroun.com","435","03-04-2025 21:52:09","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004720083","E=
koumdoum OCM","","03-04-2025 21:40:47","03-04-2025 20:34:31","03-04-2025 22=
:07:37","Site went down because 2 CBs (63A & 100A) tripped in DC BOX // CB =
put back on","Albran Byorel","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Circuit Breaker Issue","Site went down because 2 CBs (63A &=
 100A) tripped in DC BOX // CB put back on","cedric.tiani@matech-cameroun.c=
om","3977","03-04-2025 21:40:47","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004719967","Eko=
mbitie","","03-04-2025 21:19:53","03-04-2025 21:11:21","03-04-2025 21:18:12=
","Grid fluctuation, Site went down because gen failed to start due to grid=
 bad voltage,no rcp// He bypassed the Grid and site on Gen","Fabrice Pouaka=
m","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, Site went down because gen failed to start due to grid =
bad voltage,no rcp// He bypassed the Grid and site on Gen","cedric.tiani@ma=
tech-cameroun.com","513","03-04-2025 21:19:53","MATECH CMR"
"Closed Complete","Site Down","T0401","IHS_YND_205","NOCINC0004719950","Ton=
golo MTN","","03-04-2025 21:17:12","03-04-2025 21:04:57","03-04-2025 21:32:=
52","Grid outage, Gen failed to start due to Alarm oil pressure // Oil add =
and Gen start manually","Fabrice Pouakam","Equipment Repair","Passive","ACD=
G Gen","ACDG - Low Oil Pressure","Grid outage, Gen failed to start due to A=
larm oil pressure // Oil add and Gen start manually","cedric.tiani@matech-c=
ameroun.com","736","03-04-2025 21:17:12","MATECH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004719921","MEF=
OU ASSI","","03-04-2025 21:11:44","03-04-2025 21:09:32","03-04-2025 21:14:0=
5","Grid fluctuation,Site went down because Gen failed to start due to Grid=
 bad voltage, on site//He bypassed the Grid and gen manually started","Fand=
a Brice","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation,Site went down because Gen failed to start due to =
Grid bad voltage, on site//He bypassed the Grid and gen manually started","=
cedric.tiani@matech-cameroun.com","134","03-04-2025 21:11:44","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004719689","B=
arriere","","03-04-2025 20:30:45","03-04-2025 20:22:30","03-04-2025 21:11:0=
7","Gen overload // reduced load","Hyemafo Gildas","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Gen overload // reduced load","cedric.ti=
ani@matech-cameroun.com","496","03-04-2025 20:30:45","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004719674","Man=
guiers Dispensaire","","03-04-2025 20:27:05","03-04-2025 20:11:54","03-04-2=
025 20:20:43","Active // No power issue site on grid with U=3D54,5 V Tx Fme=
 Armand Ngestsa (691144412) of huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active // No power issue site on grid with U=3D54,5 V Tx Fme Armand N=
gestsa (691144412) of huawei is informed","cedric.tiani@matech-cameroun.com=
","912","03-04-2025 20:27:05","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004719613","M=
ANGUIERS CHAPELLE","","03-04-2025 20:16:23","03-04-2025 20:09:07","03-04-20=
25 20:11:07","Gen overload // reduced load","Fabrice Pouakam","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Gen overload // reduced load"=
,"cedric.tiani@matech-cameroun.com","437","03-04-2025 20:16:23","MATECH CMR=
"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004719313","A=
wae Ewonkan","","03-04-2025 19:27:16","03-04-2025 19:18:39","03-04-2025 23:=
00:39","Grid outage, Site went down because Gen overload(20KVA,310A) IHS SS=
 Alphonse Deffo confirmed //Grid return","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload(20KVA,310A) IHS SS Alphonse Deffo confirmed //Grid return","=
cedric.tiani@matech-cameroun.com","518","03-04-2025 19:27:16","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004719171","Cit=
e des nations","","03-04-2025 18:56:35","03-04-2025 18:52:24","03-04-2025 1=
9:16:23","Site went down due to insufficient rectifiers(02/03) Faulty on si=
te//Site stabilised","Paul BIBOUM","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to insufficient rectifiers(02/03) F=
aulty on site//Site stabilised","cedric.tiani@matech-cameroun.com","251","0=
3-04-2025 18:56:35","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004718657","S=
atcom","","03-04-2025 17:34:27","03-04-2025 17:27:04","03-04-2025 19:40:59"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","cedric.tiani@matech-ca=
meroun.com","444","03-04-2025 17:34:27","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004718651","BAT=
A Mokolo OCM","","03-04-2025 17:33:22","03-04-2025 17:25:10","03-04-2025 17=
:48:46","Grid outage.no space to deploy mobile gen//Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no=
 space to deploy mobile gen//Grid return","cedric.tiani@matech-cameroun.com=
","493","03-04-2025 17:33:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_795","NOCINC0004718625","Lada I Y=
de","","03-04-2025 17:27:41","03-04-2025 17:16:50","03-04-2025 17:20:37","C=
ascaded Incident from TTO4808795","Mba Lazare Herve","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active// No power issue, site is on =
Grid with Ubaie=3D56,2V, Lionel Adjep(655184876) from Huawei was working  o=
n site","system","269031","03-04-2025 17:27:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_750","NOCINC0004718623","Nkoabang=
 entree carriere","","03-04-2025 17:27:40","03-04-2025 17:16:50","03-04-202=
5 17:20:37","Cascaded Incident from TTO4808795","Mba Lazare Herve","Cascade=
 Outage","Active","Cascade Active","Cascade Active","Active// No power issu=
e, site is on Grid with Ubaie=3D56,2V, Lionel Adjep(655184876) from Huawei =
was working  on site","system","269032","03-04-2025 17:27:40","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_792","NOCINC0004718624","NKOABANG=
 NKOLO 3","","03-04-2025 17:27:40","03-04-2025 17:16:50","03-04-2025 17:20:=
37","Cascaded Incident from TTO4808795","Mba Lazare Herve","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active// No power issue, site =
is on Grid with Ubaie=3D56,2V, Lionel Adjep(655184876) from Huawei was work=
ing  on site","system","269032","03-04-2025 17:27:40","MATECH CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0004718568","Bit=
eng","IHS_YND_750, IHS_YND_792, IHS_YND_795","03-04-2025 17:18:59","03-04-2=
025 17:16:50","03-04-2025 18:20:37","Active// No power issue, site is on Gr=
id with Ubaie=3D56,2V, Lionel Adjep(655184876) from Huawei was working  on =
site","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active// No power issue, site is on Gr=
id with Ubaie=3D56,2V, Lionel Adjep(655184876) from Huawei was working  on =
site","cedric.tiani@matech-cameroun.com","130","03-04-2025 17:18:59","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004718526","B=
arriere","","03-04-2025 17:14:18","03-04-2025 12:28:09","03-04-2025 18:15:4=
2","No power issue U=3D 51.9V Site on Grid The TX FME henri /6145055 from h=
uawei is informed.","Hyemafo Gildas","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=3D 51.9V =
Site on Grid The TX FME henri /6145055 from huawei is informed.","cedric.ti=
ani@matech-cameroun.com","17170","03-04-2025 17:14:18","MATECH CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0004718488","N=
goum","","03-04-2025 17:05:47","03-04-2025 16:58:33","03-04-2025 18:15:34",=
"Solar Hybrid GEN site, No power issue site on Solar, with U=3D52.7V. The T=
x Fme Gregoire (654547479) from Huawei informed","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Solar Hybrid GEN site, No power issue site on Solar, with U=3D52.7V. The =
Tx Fme Gregoire (654547479) from Huawei informed","cedric.tiani@matech-came=
roun.com","435","03-04-2025 17:05:47","MATECH CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0004718470","Y=
de-M-Central","","03-04-2025 17:01:54","03-04-2025 16:57:43","03-04-2025 18=
:25:55","No power issue site on grid with U=3D52,3v,Mohamadou(691144435) fr=
om Huawei is informed","","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D=
52,3v,Mohamadou(691144435) from Huawei is informed","cedric.tiani@matech-ca=
meroun.com","252","03-04-2025 17:01:54","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004718363","M=
EHANDAN","","03-04-2025 16:37:28","03-04-2025 16:31:54","03-04-2025 16:51:1=
9","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, site went down because gen failed to start due to n=
o automatism // grid return","cedric.tiani@matech-cameroun.com","272068","0=
3-04-2025 16:37:28","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004718360","O=
dza II OCM","IHS_YND_528","03-04-2025 16:36:58","03-04-2025 16:31:54","03-0=
4-2025 16:51:19","Grid outage, site went down because gen failed to start d=
ue to no automatism // grid return","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","Grid outage, site went down because =
gen failed to start due to no automatism // grid return","cedric.tiani@mate=
ch-cameroun.com","305","03-04-2025 16:36:58","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004718314","Nko=
londom","","03-04-2025 16:29:39","03-04-2025 16:26:29","03-04-2025 16:58:12=
","Grid outage, Site went down because Gen failed to start due to ATS malfu=
nctionning// He reset ATS and Gen manually started","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site =
went down because Gen failed to start due to ATS malfunctionning// He reset=
 ATS and Gen manually started","cedric.tiani@matech-cameroun.com","191","03=
-04-2025 16:29:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004718018","Akak-Nko=
zoa-MTN-IHS","","03-04-2025 15:47:09","03-04-2025 15:17:03","03-04-2025 16:=
45:57","Site went down due to work Fabrice /657108613/MATECH is working on =
site (PM work) // End of work","Fabrice Pouakam","Installation Activity","P=
assive","Planned Activity","Installation Activity","Site went down due to w=
ork Fabrice /657108613/MATECH is working on site (PM work) // End of work",=
"joelle.ekessi@ihstowers.com","1808","03-04-2025 15:47:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0004717949","NKOLMEKO=
NG YDE","","03-04-2025 15:42:00","03-04-2025 15:21:53","03-04-2025 16:03:42=
","Grid  outage, site down before Gen start due to poor Battery backup // G=
en start automatically","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid  outage, site down before G=
en start due to poor Battery backup // Gen start automatically","joelle.eke=
ssi@ihstowers.com","1209","03-04-2025 15:42:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_169","NOCINC0004717940","Ekoumdou=
m","","03-04-2025 15:40:31","03-04-2025 14:45:26","03-04-2025 15:01:52","Gr=
id outage,Site went down because Gen failed to start du to prefilterdiesel =
dirty//Grid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Fuel Filter","Grid outage,Site went down because Gen failed to sta=
rt du to prefilterdiesel dirty//Grid return","joelle.ekessi@ihstowers.com",=
"3306","03-04-2025 15:40:31","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004717937","M=
ANGUIERS CHAPELLE","","03-04-2025 15:40:21","03-04-2025 15:31:05","03-04-20=
25 16:16:39","Site went down because SS IHS Bernard was working on site ","=
Fabrice Pouakam","Installation Activity","Passive","Planned Activity","Inst=
allation Activity","Site went down because SS IHS Bernard was working on si=
te ","gerard.tchangoue@matech-cameroun.com","557","03-04-2025 15:40:21","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0004717931","Biteng-M=
aetur","","03-04-2025 15:39:24","03-04-2025 14:03:18","03-04-2025 20:30:21"=
,"No power issue site on Grid with U=3D54v Flubert(654266068) from Huawei i=
s informed,","Mba Lazare Herve","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on Grid wit=
h U=3D54v Flubert(654266068) from Huawei is informed,","joelle.ekessi@ihsto=
wers.com","5767","03-04-2025 15:39:24","MATECH CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004717926","M=
amch Building","","03-04-2025 15:38:40","03-04-2025 15:31:32","03-04-2025 1=
9:55:38","No, power issue site on grid with U=3D54v Mohamadou from Huawei i=
s informed","Mboua Thierry","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No, power issue site on grid with U=
=3D54v Mohamadou from Huawei is informed","gerard.tchangoue@matech-cameroun=
.com","429","03-04-2025 15:38:40","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004717707","C=
rf-Nkolbisson","","03-04-2025 15:06:58","03-04-2025 14:45:46","03-04-2025 1=
5:00:53","Active// No power issue, site is on grid with Ubaie=3D55,4 V, Moh=
amadou(691144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue, site is on grid with Ubaie=3D55,4 V, Mohama=
dou(691144435) from Huawei is informed","gerard.tchangoue@matech-cameroun.c=
om","1273","03-04-2025 15:06:58","MATECH CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0004717680","LOB=
O MTN","","03-04-2025 15:01:55","03-04-2025 14:14:44","03-04-2025 15:50:18"=
,"Hybrid gen site: Gen failed to start due to hybrid system dysfonctionning=
 // he reset the Gen card and manually start the gen","TIENTCHEU NZETCHIEU =
GAEL","Equipment Repair","Passive","Hybrid","Hybrid Module","Hybrid gen sit=
e: Gen failed to start due to hybrid system dysfonctionning // he reset the=
 Gen card and manually start the gen","gerard.tchangoue@matech-cameroun.com=
","2831","03-04-2025 15:01:55","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004717112","Meh=
anda 1","","03-04-2025 13:47:29","03-04-2025 13:06:18","03-04-2025 14:30:47=
","site went Down due to bad Eneo Voltage // He put site on GEN","Albran By=
orel","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","site went Down due to bad Eneo Voltage // He put site on GEN","edwige.=
kapawo@matech-cameroun.com","2472","03-04-2025 13:47:29","MATECH CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0004716611","E=
kie sud","","03-04-2025 12:51:21","03-04-2025 12:42:06","03-04-2025 18:43:4=
6","No power issue site on grid with U=3D53v Lionnel from Huawei is informe=
d ","Albran Byorel","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53v Li=
onnel from Huawei is informed ","edwige.kapawo@matech-cameroun.com","556","=
03-04-2025 12:51:21","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004716582","N=
koabang Ebolmedjock","","03-04-2025 12:45:28","03-04-2025 12:44:14","03-04-=
2025 20:45:21","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Gen. Notice that it is impacted b=
y Nkolmesseng-Abom(CTR-711) Not Manager By IHS","edwige.kapawo@matech-camer=
oun.com","75","03-04-2025 12:45:28","MATECH CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0004716351","Nko=
lbisson usine des eaux","","03-04-2025 12:09:43","03-04-2025 11:41:50","03-=
04-2025 18:37:16","No power issue site on gen with U=3D54v Mohamadou from H=
uawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on gen with U=3D54v Mohamadou from Huawei is informed","stephane.nkamwa@=
ihstowers.com","1674","03-04-2025 12:09:43","MATECH CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004716285","Nko=
lbisson usines des eaux 2","","03-04-2025 11:58:55","03-04-2025 11:41:48","=
03-04-2025 19:55:31","Active: No power issue, site is on GEN with Ubaie=3D4=
8.5V.  The Tx FME Mohamadou moaum ( 691144435 )of huawei is informed.","TIE=
NTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Active: No power issue, site is on GEN w=
ith Ubaie=3D48.5V.

The Tx FME Mohamadou moaum ( 691144435 )of huawei is informed.

","franck.nkomot@matech-cameroun.com","1028","03-04-2025 11:58:55","MATECH =
CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0004716269","Y=
ona Hotel","","03-04-2025 11:57:00","03-04-2025 11:30:52","03-04-2025 14:23=
:09","Grid outage Site went down because gen start and stopped with  alarm =
high temp//We added water and gen manually started","TIENTCHEU NZETCHIEU GA=
EL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid outage Site went down because gen start and stopped =
with  alarm high temp//We added water and gen manually started","edwige.kap=
awo@matech-cameroun.com","1569","03-04-2025 11:57:00","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004716239","Ako=
k Ndoe Yde","","03-04-2025 11:54:04","03-04-2025 11:21:46","03-04-2025 14:4=
9:22","Site went down because Gen failed to start due to grid bad voltages,=
  no RCp  // He bypassed the Grid and site on GEN","Hyemafo Gildas","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Site wen=
t down because Gen failed to start due to grid bad voltages,  no RCp  // He=
 bypassed the Grid and site on GEN","edwige.kapawo@matech-cameroun.com","19=
39","03-04-2025 11:54:04","MATECH CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0004716196","S=
ofavinc","","03-04-2025 11:46:32","03-04-2025 11:43:26","03-04-2025 12:59:2=
6","site went down due to insuffisance of rectifier // Site up (Added recti=
fier ongoing)","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","site went down due to insuffisance of rectifier // Site up=
 (Added rectifier ongoing)","edwige.kapawo@matech-cameroun.com","187","03-0=
4-2025 11:46:32","MATECH CMR"
"Closed Complete","Warning","T1550","IHS_YND_537","NOCINC0004716026","MEFOU=
 ASSI","","03-04-2025 11:16:03","","","Grid fluctuation,Site went down beca=
use Gen failed to start due to Grid bad voltage, on site//He bypassed the G=
rid and gen manually started","Fanda Brice","Warning","Warning","POWER","Wa=
rning - National Grid - Grid Incomplete Phase","Grid fluctuation,Site went =
down because Gen failed to start due to Grid bad voltage, on site//He bypas=
sed the Grid and gen manually started","franck.nkomot@matech-cameroun.com",=
"160","03-04-2025 11:16:03","MATECH CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004716000","Nko=
londom","","03-04-2025 11:10:27","03-04-2025 10:44:11","03-04-2025 11:13:16=
","Grid outage, Site went down because Gen failed to start due to ATS malfu=
nctionning// He reset ATS and Gen manually started","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site =
went down because Gen failed to start due to ATS malfunctionning// He reset=
 ATS and Gen manually started","franck.nkomot@matech-cameroun.com","1577","=
03-04-2025 11:10:27","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004715998","N=
goulmekong-Nord","","03-04-2025 11:10:09","03-04-2025 10:56:51","03-04-2025=
 13:46:40","Site went down because insufficient of rectifier on site//site =
stabilized","Siligap Boris","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down because insufficient of rectifier on site//sit=
e stabilized","edwige.kapawo@matech-cameroun.com","799","03-04-2025 11:10:0=
9","MATECH CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0004715961","Val=
lee Bastos MTN","","03-04-2025 11:04:36","03-04-2025 11:01:22","03-04-2025 =
12:19:32","Site went down because insufficient of rectifier //site stabiliz=
ed(need to added 01 rectifier)","Mboua Thierry","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down because insufficient of re=
ctifier //site stabilized(need to added 01 rectifier)","franck.nkomot@matec=
h-cameroun.com","195","03-04-2025 11:04:36","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004715938","E=
kombitie","","03-04-2025 11:01:46","03-04-2025 10:49:31","03-04-2025 13:15:=
00","Active: no power issue, site is on Gen with Ubaie:54.3V, Symphorien(65=
0257151) from Huawei is informed.","Fabrice Pouakam","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no=
 power issue, site is on Gen with Ubaie:54.3V, Symphorien(650257151) from H=
uawei is informed.","edwige.kapawo@matech-cameroun.com","736","03-04-2025 1=
1:01:46","MATECH CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004715933","Bar=
riere","","03-04-2025 10:59:54","03-04-2025 10:11:44","03-04-2025 11:56:42"=
,"Grrid outage site went down due to gen overload (20Kva,350A)//We reduce l=
oad and gen manually started ","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grrid outage site went down due to gen over=
load (20Kva,350A)//We reduce load and gen manually started ","franck.nkomot=
@matech-cameroun.com","2891","03-04-2025 10:59:54","MATECH CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0004715925","Mvo=
g-Ada_OCM","","03-04-2025 10:59:00","03-04-2025 10:24:45","03-04-2025 11:45=
:01","No power issue, U=3D53. 4V Site on Grid The TX FME Armand (691144412)=
 from Huawei is informed","","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue, U=3D53. 4V Site on=
 Grid The TX FME Armand (691144412) from Huawei is informed","franck.nkomot=
@matech-cameroun.com","2056","03-04-2025 10:59:00","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004715920","Elo=
umdem stade","","03-04-2025 10:57:26","03-04-2025 10:51:09","03-04-2025 12:=
13:10","site went down because insufficiency rectifiers on site (02 rectifi=
ers ) due to Load increase on site//load reduced","Fanda Brice","Equipment =
Repair","Passive","Rectifier","Rectifier Module","site went down because in=
sufficiency rectifiers on site (02 rectifiers ) due to Load increase on sit=
e//load reduced","franck.nkomot@matech-cameroun.com","379","03-04-2025 10:5=
7:26","MATECH CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004715918","SIM=
BOCK BONAMBAPE","","03-04-2025 10:57:14","03-04-2025 10:44:00","03-04-2025 =
11:36:22","Grid outage, Site down due to poor battery backup // Gen start m=
anualy","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, Site down due to poor battery backup=
 // Gen start manualy","edwige.kapawo@matech-cameroun.com","795","03-04-202=
5 10:57:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004715741","ELOUMDEM=
 CARRIERE 2","","03-04-2025 10:32:27","03-04-2025 10:23:35","03-04-2025 10:=
29:53","Cascaded Incident from TTO4805556","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation,Site went do=
wn because Gen failed to start due to Grid bad voltage, on site//He bypasse=
d the Grid and gen manually started","system","286636","03-04-2025 10:32:27=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004715740","Eto koss=
 Yde","","03-04-2025 10:32:26","03-04-2025 10:23:35","03-04-2025 10:29:53",=
"Cascaded Incident from TTO4805556","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation,Site went down beca=
use Gen failed to start due to Grid bad voltage, on site//He bypassed the G=
rid and gen manually started","system","286635","03-04-2025 10:32:26","MATE=
CH CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004715717","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","03-04-2025 10:30:02","03-04-2025 10:23=
:35","03-04-2025 10:29:53","Grid fluctuation,Site went down because Gen fai=
led to start due to Grid bad voltage, on site//He bypassed the Grid and gen=
 manually started","Fanda Brice","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation,Site went down because Gen=
 failed to start due to Grid bad voltage, on site//He bypassed the Grid and=
 gen manually started","franck.nkomot@matech-cameroun.com","389","03-04-202=
5 10:30:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0004715712","Mendong =
vallee","","03-04-2025 10:29:09","03-04-2025 10:20:30","03-04-2025 12:55:24=
","Cascaded Incident from TTO4805498","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went Down due to poor backup =
// Manual start of Gen","system","279594","03-04-2025 10:29:09","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0004715713","Montee-J=
ouvence","","03-04-2025 10:29:09","03-04-2025 10:20:30","03-04-2025 11:28:4=
5","Grid outage, Site down due to poor battery backup // Gen start manualy"=
,"Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Grid outage, Site down due to poor battery backup // Gen start manua=
ly","system","519","03-04-2025 10:29:09","MATECH CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004715663","M=
endong","IHS_YND_692, IHS_YND_236","03-04-2025 10:25:35","03-04-2025 10:20:=
30","03-04-2025 12:55:24","Site went Down due to poor backup // Manual star=
t of Gen","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Site went Down due to poor backup // Manual sta=
rt of Gen","edwige.kapawo@matech-cameroun.com","306","03-04-2025 10:25:35",=
"MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004715662","Awa=
e Ewonkan","","03-04-2025 10:25:34","03-04-2025 10:09:22","03-04-2025 13:15=
:17","Grid outage site went down due to  Gen Overload (20Kva, Iload 225 A)I=
HS SS Alphonse is informed // Grid Restored ","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down du=
e to  Gen Overload (20Kva, Iload 225 A)IHS SS Alphonse is informed // Grid =
Restored ","franck.nkomot@matech-cameroun.com","2946","03-04-2025 10:25:34"=
,"MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004715624","Bit=
eng-Maetur","","03-04-2025 10:18:49","03-04-2025 10:15:20","03-04-2025 11:5=
6:22","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the l=
oad","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, Site went down because Gen started and stopped due to =
Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the =
load","franck.nkomot@matech-cameroun.com","211","03-04-2025 10:18:49","MATE=
CH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004715579","Mon=
tee Jouvence","","03-04-2025 10:11:04","03-04-2025 10:08:25","03-04-2025 11=
:28:44","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started manually","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Gen started automatically","franck.nkomot@=
matech-cameroun.com","160","03-04-2025 10:11:04","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004715573","Ako=
k Ndoe Yde","","03-04-2025 10:08:44","03-04-2025 10:06:31","03-04-2025 10:3=
2:30","Grid outage, Site down due to poor battery backup // Gen started aut=
omatically","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site down due to poor battery ba=
ckup // Gen started automatically","edwige.kapawo@matech-cameroun.com","134=
","03-04-2025 10:08:44","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0004715570","EKI=
E","","03-04-2025 10:08:03","03-04-2025 09:52:43","03-04-2025 15:10:54","Gr=
id outage, site went down because gen failed to start due to grid contactor=
 faulty // He bypassed grid contactor  and Gen manually started","Albran By=
orel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid ou=
tage, site went down because gen failed to start due to grid contactor faul=
ty // He bypassed grid contactor  and Gen manually started","edwige.kapawo@=
matech-cameroun.com","920","03-04-2025 10:08:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0004715503","Etoudi 2=
","","03-04-2025 09:55:35","03-04-2025 09:48:00","03-04-2025 09:56:19","Cas=
caded Incident from TTO4805292","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work made by I=
HS SS Felix ZAMBE(657108641) is working on site  // End of work","system","=
296002","03-04-2025 09:55:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004715502","ETOUDI C=
HAPELLE","","03-04-2025 09:55:34","03-04-2025 09:48:00","03-04-2025 09:56:1=
9","Cascaded Incident from TTO4805292","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work mad=
e by IHS SS Felix ZAMBE(657108641) is working on site  // End of work","sys=
tem","296002","03-04-2025 09:55:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004715501","Abattoir=
","","03-04-2025 09:55:34","03-04-2025 09:48:00","03-04-2025 09:56:19","Cas=
caded Incident from TTO4805292","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work made by I=
HS SS Felix ZAMBE(657108641) is working on site  // End of work","system","=
296001","03-04-2025 09:55:34","MATECH CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004715488","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","03-04-2025 09:53:12","03-04-2=
025 09:48:00","03-04-2025 09:56:19","Site went down due to work done by IHS=
 SS Felix ZAMBE(657108641)  // End of work","Fabrice Pouakam","Installation=
 Activity","Passive","Planned Activity","Installation Activity","Site went =
down due to work done by IHS SS Felix ZAMBE(657108641)  // End of work","ed=
wige.kapawo@matech-cameroun.com","313","03-04-2025 09:53:12","MATECH CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0004715446","N=
kolbi-Boss","","03-04-2025 09:43:55","03-04-2025 09:39:46","03-04-2025 09:5=
0:24","wrong ticket","TIENTCHEU NZETCHIEU GAEL","Incorrectly Logged Tickets=
","Error","Error","Error","wrong ticket","edwige.kapawo@matech-cameroun.com=
","250","03-04-2025 09:43:55","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004715426","NYO=
M FACE MAETUR","","03-04-2025 09:40:30","03-04-2025 08:41:58","03-04-2025 1=
0:42:25","Site Went Down due to eneo bad voltage // He site put on Gen","Fa=
brice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Site Went Down due to eneo bad voltage // He site put on Gen"=
,"edwige.kapawo@matech-cameroun.com","3514","03-04-2025 09:40:30","MATECH C=
MR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004715106","Nko=
londom","","03-04-2025 08:53:48","03-04-2025 08:49:37","03-04-2025 09:07:34=
","Grid outage, Site went down because Gen failed to start due to ATS malfu=
nctionning// He reset ATS and Gen manually started","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site =
went down because Gen failed to start due to ATS malfunctionning// He reset=
 ATS and Gen manually started","edwige.kapawo@matech-cameroun.com","368","0=
3-04-2025 08:53:48","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004715088","Ole=
mbe MTN","","03-04-2025 08:48:07","03-04-2025 08:46:59","03-04-2025 09:07:0=
9","Site went down due to insufficiency of rectifiers,  // Added rectifier =
ongoing","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to insufficiency of rectifiers, Pascaline I=
HS is informed // Added rectifier ongoing","gerard.tchangoue@matech-camerou=
n.com","69","03-04-2025 08:48:07","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004715035","Eko=
umdoum OCM","","03-04-2025 08:31:08","03-04-2025 08:27:50","03-04-2025 10:2=
9:50","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS =
Pascaline is informed and confirmed//Grid return","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went do=
wn due to Gen overload(20kva,280 A) IHS SS Pascaline is informed and confir=
med//Grid return","gerard.tchangoue@matech-cameroun.com","199","03-04-2025 =
08:31:08","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004714553","ODZ=
A MINKAN EDIBI ASSI","","03-04-2025 07:31:28","03-04-2025 07:20:21","03-04-=
2025 11:23:43","site Went  down due to rectifier issue // site Stabilized",=
"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"site Went  down due to rectifier issue // site Stabilized","edwige.kapawo=
@matech-cameroun.com","668","03-04-2025 07:31:28","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004713669","Man=
guiers Dispensaire","","03-04-2025 02:54:27","02-04-2025 22:41:00","03-04-2=
025 00:05:32","Site went down due to 3/4 rectifier faulty on site // He res=
et rectifiers Rectifier: Site on grid","Fabrice Pouakam","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down due to 3/4 rectif=
ier faulty on site // He reset rectifiers Rectifier: Site on grid","kamga.v=
irgile@ihstowers.com","15208","03-04-2025 02:54:27","MATECH CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004713663","Mes=
sa Carriere","","03-04-2025 02:51:00","03-04-2025 00:32:45","03-04-2025 00:=
48:59","	Grid outage site went down because Gen failed to start due to Gen =
card faulty // Gen Manually Started","Mboua Thierry","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","	Grid outage site went down becau=
se Gen failed to start due to Gen card faulty // Gen Manually Started","kam=
ga.virgile@ihstowers.com","10587","03-04-2025 02:51:00","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004713660","Crf=
-Mbankolo-IHS","","03-04-2025 02:48:05","02-04-2025 22:03:08","03-04-2025 0=
2:47:19","site down due to insufficient rectifiers on site // site stabilis=
ed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","site down due to insufficient rectifiers on site // site stabilised",=
"christelle.ngonga@matech-cameroun.com","17098","03-04-2025 02:48:05","MATE=
CH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004713627","ODZ=
A MINKAN EDIBI ASSI","","03-04-2025 02:36:23","03-04-2025 00:14:52","03-04-=
2025 05:08:24","rectifier Tripped // Rectifier reset ","Albran Byorel","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module","rectifier Tripped =
// Rectifier reset ","christelle.ngonga@matech-cameroun.com","8492","03-04-=
2025 02:36:23","MATECH CMR"
"Closed Complete","Site Down","T1297","IHS_YND_734","NOCINC0004713617","Mim=
boman Chateau","","03-04-2025 02:32:05","03-04-2025 02:15:45","03-04-2025 0=
2:45:25","ACTIVE// No power issue on site site on Grid with Ubaie=3D53.3V T=
he FME TX Leonel Adjet /655184876// From Huawei is informed .","","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE// No power issue on site site on Grid with Ubaie=3D53V The FME TX=
 Leonel Adjet /655184876// From Huawei is informed .","kamga.virgile@ihstow=
ers.com","4614","03-04-2025 02:32:05","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004713614","Ole=
mbe MTN","","03-04-2025 02:31:21","03-04-2025 01:50:41","03-04-2025 07:50:5=
5","Site went down due to insufficiency of rectifiers on site // site stabi=
lized(need to add 01 rectifier)","Fabrice Pouakam","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","Site went down due to insufficiency of=
 rectifiers on site // site stabilized(need to add 01 rectifier)","loic.nou=
msi@matech-cameroun.com","2441","03-04-2025 02:31:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004713586","Song-bon=
g","","03-04-2025 02:24:38","03-04-2025 02:14:47","03-04-2025 06:11:42","Ca=
scaded Incident from TTO4803191","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage gen failed to start due=
 to fuse of card GE faulty//We bypass fuse and gen manually started ","syst=
em","323168","03-04-2025 02:24:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004713585","Eseka To=
wn","","03-04-2025 02:24:38","03-04-2025 02:14:47","03-04-2025 06:11:42","C=
ascaded Incident from TTO4803191","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage gen failed to start du=
e to fuse of card GE faulty//We bypass fuse and gen manually started ","sys=
tem","323167","03-04-2025 02:24:38","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0004713581","E=
seka OCM","IHS_YND_378, IHS_YND_453","03-04-2025 02:23:52","03-04-2025 02:1=
4:47","03-04-2025 06:11:42","Grid outage gen failed to start due to fuse of=
 card GE faulty//We bypass fuse and gen manually started ","Kemeni Franklin=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge gen failed to start due to fuse of card GE faulty//We bypass fuse and ge=
n manually started ","alexandre.kamal@ihstowers.com","546","03-04-2025 02:2=
3:52","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004712618","S=
imbock OCM","","02-04-2025 21:57:25","02-04-2025 21:10:54","02-04-2025 22:3=
0:05","Site went down due to 01/04 Rectifier faulty on site // He removed t=
he faulty rectifier site is actually on grid","Hyemafo Gildas","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down due to 01/0=
4 Rectifier faulty on site // He removed the faulty rectifier site is actua=
lly on grid","cedric.tiani@matech-cameroun.com","2792","02-04-2025 21:57:25=
","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0004712558","GSO=
","","02-04-2025 21:42:26","02-04-2025 20:48:42","02-04-2025 21:54:13","Gri=
d bad voltage // Site permanally put on Gen","MINKA NICOLAS","Grid Supply",=
"Passive","Grid","National Grid - Low Current Supply","Grid bad voltage // =
Site permanally put on Gen","cedric.tiani@matech-cameroun.com","3292","02-0=
4-2025 21:42:26","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004712500","OBA=
M NGOLA OCM","","02-04-2025 21:30:01","02-04-2025 21:07:50","02-04-2025 22:=
00:20","Grid Gen site , Grid bad voltage // Gen permanally put on ","MINKA =
NICOLAS","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supp=
ly Issue","Grid Gen site , Grid bad voltage // Gen permanally put on ","ced=
ric.tiani@matech-cameroun.com","1333","02-04-2025 21:30:01","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004712111","B=
arriere IHS","","02-04-2025 20:47:36","02-04-2025 19:59:59","02-04-2025 22:=
05:28","Disjonction in the Power Cabinet Bay // CB Rearmed","Hyemafo Gildas=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Bre=
aker Issue","Disjonction in the Power Cabinet Bay // CB Rearmed","cedric.ti=
ani@matech-cameroun.com","2858","02-04-2025 20:47:36","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004712106","B=
itoto","","02-04-2025 20:46:15","02-04-2025 20:20:01","02-04-2025 21:28:00"=
,"site down due to disjunction in the ocm BTS // Breaker circuit  rearmed s=
ite on grid","Mba Lazare Herve","Equipment Repair","Passive","Control Panel=
","BTS Breaker Tripped","site down due to disjunction in the ocm BTS // Bre=
aker circuit  rearmed site on grid","cedric.tiani@matech-cameroun.com","157=
5","02-04-2025 20:46:15","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004711962","S=
imbock OCM","","02-04-2025 20:25:42","02-04-2025 19:53:01","02-04-2025 20:4=
8:13","Site went down due to 01/04 Rectifier faulty on site // He removed t=
he faulty rectifier site is actually on grid","Hyemafo Gildas","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down due to 01/0=
4 Rectifier faulty on site // He removed the faulty rectifier site is actua=
lly on grid","cedric.tiani@matech-cameroun.com","1961","02-04-2025 20:25:42=
","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0004711937","M=
vog-Ebanda","","02-04-2025 20:23:43","02-04-2025 19:32:53","02-04-2025 22:0=
0:19","site down due to disjunction of circuit breakers in the energy bay c=
aused by overload // circuit breaker rearmed","Siligap Boris","Equipment Re=
pair","Passive","Rectifier","Rectifier - Circuit Breaker","site down due to=
 disjunction of circuit breakers in the energy bay caused by overload // ci=
rcuit breaker rearmed","loic.noumsi@matech-cameroun.com","3051","02-04-2025=
 20:23:43","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004711794","C=
rf-Nkolbisson","","02-04-2025 19:56:54","02-04-2025 19:34:22","02-04-2025 2=
0:21:35","disjunction 125A of circuit breakers in the pwc caused by overloa=
d // need a second starting","TIENTCHEU NZETCHIEU GAEL","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","disjunction 125A of ci=
rcuit breakers in the pwc caused by overload // need a second starting","ce=
dric.tiani@matech-cameroun.com","1353","02-04-2025 19:56:54","MATECH CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0004711765","Oss=
ombe","","02-04-2025 19:51:09","02-04-2025 19:26:00","02-04-2025 20:29:05",=
"site impacted by Ntui camtel","Parker Tchoup","3RD Party Power Failure","P=
assive","Power Provided By 3RD Party","Power Provided By 3RD Party","site i=
mpacted by Ntui camtel","cedric.tiani@matech-cameroun.com","1569","02-04-20=
25 19:51:09","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004711624","NYO=
M FACE MAETUR","","02-04-2025 19:29:55","02-04-2025 19:22:32","02-04-2025 2=
0:26:12","Grid outage, Site went down because Gen failed to start due Gen c=
ard Faulty// Grid Restored","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, Site went down because Gen =
failed to start due Gen card Faulty// Grid Restored","loic.noumsi@matech-ca=
meroun.com","471","02-04-2025 19:29:55","MATECH CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004711540","Awa=
e Ewonkan","","02-04-2025 19:12:04","02-04-2025 19:02:44","02-04-2025 19:55=
:55","Gen overloard // Grid return","Albran Byorel","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Gen overloard // Grid return","loic.nou=
msi@matech-cameroun.com","617","02-04-2025 19:12:04","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004711498","E=
kombitie","","02-04-2025 19:01:18","02-04-2025 18:27:45","02-04-2025 20:09:=
59","Bad eneo voltage // Site put on Gen","Fabrice Pouakam","Grid Supply","=
Passive","Grid","National Grid - Unstable Grid Supply Issue","Bad eneo volt=
age // Site put on Gen","loic.noumsi@matech-cameroun.com","2014","02-04-202=
5 19:01:18","MATECH CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0004711462","NYO=
M","","02-04-2025 18:54:00","02-04-2025 18:36:12","02-04-2025 18:44:18","Gr=
id gen site . Grid outage Rectifier Deficiency //Eneo Return","Fabrice Poua=
kam","Equipment Repair","Passive","Rectifier","Rectifier Module","Grid gen =
site . Grid outage Rectifier Deficiency //Eneo Return","cedric.tiani@matech=
-cameroun.com","1069","02-04-2025 18:54:00","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004711390","Yoko MTN=
","","02-04-2025 18:40:54","02-04-2025 17:42:53","02-04-2025 18:40:21","Cas=
caded Incident from TTO4800516","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","SITE IMPACTED BY Ntui Camtel","system"=
,"267609","02-04-2025 18:40:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0004711388","NTUI TOW=
N","","02-04-2025 18:40:54","02-04-2025 17:42:53","02-04-2025 18:40:21","Ca=
scaded Incident from TTO4800516","Parker Tchoup","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","SITE IMPACTED BY Ntui Camtel","system=
","267609","02-04-2025 18:40:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004711389","Saa","",=
"02-04-2025 18:40:54","02-04-2025 17:42:53","02-04-2025 18:40:21","Cascaded=
 Incident from TTO4800516","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","SITE IMPACTED BY Ntui Camtel","system","267=
610","02-04-2025 18:40:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004711387","Donga","=
","02-04-2025 18:40:54","02-04-2025 17:42:53","02-04-2025 18:40:21","Cascad=
ed Incident from TTO4800516","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","SITE IMPACTED BY Ntui Camtel","system","2=
67610","02-04-2025 18:40:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_690","NOCINC0004711385","Ntui adm=
inistration","","02-04-2025 18:40:53","02-04-2025 17:42:53","02-04-2025 18:=
40:21","Cascaded Incident from TTO4800516","Parker Tchoup","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","SITE IMPACTED BY Ntui Camte=
l","system","267612","02-04-2025 18:40:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004711384","Ngouetou=
","","02-04-2025 18:40:53","02-04-2025 17:42:53","02-04-2025 18:40:21","Cas=
caded Incident from TTO4800516","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","SITE IMPACTED BY Ntui Camtel","system"=
,"267608","02-04-2025 18:40:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004711383","Ngoum","=
","02-04-2025 18:40:53","02-04-2025 17:42:53","02-04-2025 18:40:21","Cascad=
ed Incident from TTO4800516","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","SITE IMPACTED BY Ntui Camtel","system","2=
67611","02-04-2025 18:40:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0004711386","Nkol-Meb=
anga","","02-04-2025 18:40:53","02-04-2025 17:42:53","02-04-2025 18:40:21",=
"Cascaded Incident from TTO4800516","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","SITE IMPACTED BY Ntui Camtel","sys=
tem","267611","02-04-2025 18:40:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0004711381","Nguila",=
"","02-04-2025 18:40:52","02-04-2025 17:42:53","02-04-2025 18:40:21","Casca=
ded Incident from TTO4800516","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","SITE IMPACTED BY Ntui Camtel","system","=
267608","02-04-2025 18:40:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_424","NOCINC0004711382","Ossombe"=
,"","02-04-2025 18:40:52","02-04-2025 17:42:53","02-04-2025 18:40:21","Casc=
aded Incident from TTO4800516","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","SITE IMPACTED BY Ntui Camtel","system",=
"267610","02-04-2025 18:40:52","MATECH CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004711216","SAA=
 2","IHS_YND_433, IHS_YND_424, IHS_YND_475, IHS_YND_454, IHS_YND_690, IHS_Y=
ND_809, IHS_YND_434, IHS_YND_403, IHS_YND_405, IHS_YND_473","02-04-2025 18:=
08:10","02-04-2025 17:42:53","02-04-2025 18:40:21","SITE IMPACTED BY Ntui C=
amtel","Parker Tchoup","3RD Party Power Failure","Passive","Power Provided =
By 3RD Party","Power Provided By 3RD Party","SITE IMPACTED BY Ntui Camtel",=
"cedric.tiani@matech-cameroun.com","1518","02-04-2025 18:08:10","MATECH CMR=
"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004711155","E=
mana lycee 2","","02-04-2025 18:01:33","02-04-2025 17:36:22","02-04-2025 17=
:57:43","Active: no power issue, site is on Gen with Ubaie=3D51,9V site on =
Grid, Symphorien(650257151) from huawei is informed","Fabrice Pouakam","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active: no power issue, site is on Gen with Ubaie=3D51,9V site on G=
rid, Symphorien(650257151) from huawei is informed","cedric.tiani@matech-ca=
meroun.com","1512","02-04-2025 18:01:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004711017","Song-bon=
g","","02-04-2025 17:37:20","02-04-2025 16:32:43","02-04-2025 18:28:42","Ca=
scaded Incident from TTO4800279","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,Site went down because =
Gen failed to start due to Grid contactor malfunctionning  // He bypassed i=
t site on Grid","system","278879","02-04-2025 17:37:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004711016","Eseka To=
wn","","02-04-2025 17:37:20","02-04-2025 16:32:43","02-04-2025 18:28:42","C=
ascaded Incident from TTO4800279","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,Site went down because=
 Gen failed to start due to Grid contactor malfunctionning  // He bypassed =
it site on Grid","system","278879","02-04-2025 17:37:20","MATECH CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0004711005","E=
seka OCM","IHS_YND_378, IHS_YND_453","02-04-2025 17:34:53","02-04-2025 16:3=
2:43","02-04-2025 18:28:42","Grid outage,Site went down because Gen failed =
to start due to Grid contactor malfunctionning  // He bypassed it site on G=
rid","Kemeni Franklin","Equipment Repair","Passive","Control Panel","ATS-AM=
F Issue","Grid outage,Site went down because Gen failed to start due to Gri=
d contactor malfunctionning  // He bypassed it site on Grid","cedric.tiani@=
matech-cameroun.com","3731","02-04-2025 17:34:53","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0004710974","G=
SO","","02-04-2025 17:29:42","02-04-2025 17:00:19","02-04-2025 18:47:25","A=
TS malfunction // manually switching the site to Grid","MINKA NICOLAS","Equ=
ipment Repair","Passive","Control Panel","ATS-AMF Issue","ATS malfunction /=
/ manually switching the site to Grid","cedric.tiani@matech-cameroun.com","=
1806","02-04-2025 17:29:42","MATECH CMR"
"Closed Complete","Site Down","CTR_063","IHS_YND_365","NOCINC0004710962","A=
kono","","02-04-2025 17:25:17","02-04-2025 16:32:03","02-04-2025 16:33:02",=
"wrongly ticket","Fanda Brice","Incorrectly Logged Tickets","Error","Error"=
,"Error","wrongly ticket","cedric.tiani@matech-cameroun.com","3195","02-04-=
2025 17:25:17","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004710928","M=
essa-Carriere OCM","","02-04-2025 17:18:58","02-04-2025 15:21:40","02-04-20=
25 19:58:00","Active//No power issue on Site ,Site on Grid with Ubaie=3D54,=
4 V The TX FME Mohamadou mouam //691144435 from Huawei is informed","","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active//No power issue on Site ,Site on Grid with Ubaie=3D54,4 V Th=
e TX FME Mohamadou mouam //691144435 from Huawei is informed","mouliom.anse=
lme@matech-cameroun.com","7039","02-04-2025 17:18:58","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004710898","A=
wae Ewonkan","","02-04-2025 17:14:33","02-04-2025 15:40:57","02-04-2025 18:=
40:20","Grid outage, Site went down because Gen overload(20KVA,310A) IHS SS=
 Alphonse Deffo confirmed //Grid return","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload(20KVA,310A) IHS SS Alphonse Deffo confirmed //Grid return","=
cedric.tiani@matech-cameroun.com","5618","02-04-2025 17:14:33","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004710748","O=
dza","","02-04-2025 16:44:22","02-04-2025 16:09:54","02-04-2025 20:01:51","=
Grid fluctuation, Site went down because gen failed to start due to 01 lack=
 phase No RCp on site // He did a bridge on a Good phase","Albran Byorel","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, Site went down because gen failed to start due to 01 lack p=
hase No RCp on site // He did a bridge on a Good phase","cedric.tiani@matec=
h-cameroun.com","2069","02-04-2025 16:44:22","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004710657","Nko=
zoa","","02-04-2025 16:29:08","02-04-2025 15:40:44","02-04-2025 17:18:25","=
Gen overloard // reduction of 03 battery rack and Gen start manually","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gen=
 overloard // reduction of 03 battery rack and Gen start manually","loic.no=
umsi@matech-cameroun.com","4019","02-04-2025 16:29:08","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004710584","E=
koumdoum","","02-04-2025 16:19:56","02-04-2025 15:44:56","02-04-2025 15:50:=
31","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS Pa=
scaline is informed and confirmed//We reduced load and gen manually started=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS Pasca=
line is informed and confirmed//We reduce load and gen manually started","c=
edric.tiani@matech-cameroun.com","2101","02-04-2025 16:19:56","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004710568","A=
kak-Nkozoa-MTN-IHS","","02-04-2025 16:17:06","02-04-2025 15:50:58","02-04-2=
025 15:51:58","No power issue on site T54.6 V, site on gen ","Fabrice Pouak=
am","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site T54.6 V, site on gen ","cedric.tiani=
@matech-cameroun.com","1569","02-04-2025 16:17:06","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004710551","M=
ANGUIERS CHAPELLE","","02-04-2025 16:14:14","02-04-2025 14:59:44","02-04-20=
25 15:08:30","Site down due to Bad eneo voltage // Eneo stabilizated","Fabr=
ice Pouakam","Grid Supply","Passive","Grid","National Grid - Unstable Grid =
Supply Issue","Site down due to Bad eneo voltage // Eneo stabilizated
","cedric.tiani@matech-cameroun.com","4472","02-04-2025 16:14:14","MATECH C=
MR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004710479","A=
WAE OCM","","02-04-2025 16:03:40","02-04-2025 15:27:11","02-04-2025 18:55:2=
1","Grid outage, site went down because gen failed to start due to PWC ZTE =
malfunction, // He reset controller and gen manually started","Mba Lazare H=
erve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, site went down because gen failed to start due to PWC ZTE m=
alfunction, // He reset controller and gen manually started","cedric.tiani@=
matech-cameroun.com","2190","02-04-2025 16:03:40","MATECH CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004710213","M=
ini-Ferme","","02-04-2025 15:29:16","02-04-2025 14:29:07","02-04-2025 15:49=
:09","	grid outage, no space to deploy a mobile gen// grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","	grid outage=
, no space to deploy a mobile gen// grid return","cedric.tiani@matech-camer=
oun.com","3610","02-04-2025 15:29:16","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004710160","M=
essassi okolo","","02-04-2025 15:21:33","02-04-2025 14:15:19","03-04-2025 0=
5:36:50","	ACTIVE//No power issue on site Ubaie=3D54.5V, site on Grid The T=
X Fme Synphorien 691316854 of Huewai is informed","Fabrice Pouakam","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","	ACTIVE//No power issue on site Ubaie=3D54.5V, site on Grid The TX Fme=
 Synphorien 691316854 of Huewai is informed","cedric.tiani@matech-cameroun.=
com","3976","02-04-2025 15:21:33","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004709844","Nko=
lbong","","02-04-2025 14:42:23","02-04-2025 14:05:18","02-04-2025 15:37:43"=
,"Grid outage,gen failed to start due to card Ge dysfunctionning//We rest c=
ard GE and Gen manually started","Delor Telezing","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due =
to card Ge dysfunctionning//We rest card GE and Gen manually started","cedr=
ic.tiani@matech-cameroun.com","2226","02-04-2025 14:42:23","MATECH CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004709494","An-=
Marche-Melen","","02-04-2025 13:57:12","02-04-2025 13:53:44","02-04-2025 15=
:52:44","Grid outage, No space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No sp=
ace to deploy MDG // Grid return","cedric.tiani@matech-cameroun.com","210",=
"02-04-2025 13:57:12","MATECH CMR"
"Closed Complete","Site Down","CTR_255","IHS_YND_286","NOCINC0004709457","D=
agobert","","02-04-2025 13:49:19","02-04-2025 13:37:06","02-04-2025 14:21:5=
4","Grid outage, site went down because gen start and stopped with over cou=
rent alarm (unpruven) // Reset done and gen started","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage, site went down because gen start and stopped with over courent alarm=
 (unpruven) // Reset done and gen started","cedric.tiani@matech-cameroun.co=
m","734","02-04-2025 13:49:19","MATECH CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004709374","SOA=
 TOWN","","02-04-2025 13:33:13","02-04-2025 13:14:59","02-04-2025 14:34:13"=
,"Site went down due to work Boris/657100525/MATECH is working on site (PM =
work) // End of work","Siligap Boris","Installation Activity","Passive","Pl=
anned Activity","Installation Activity","Site went down due to work Boris/6=
57100525/MATECH is working on site (PM work) // End of work","cedric.tiani@=
matech-cameroun.com","1096","02-04-2025 13:33:13","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004709290","Nko=
lnda","","02-04-2025 13:20:17","02-04-2025 12:39:01","02-04-2025 13:58:50",=
"Grid outage, site went down because gen started and stopped due to load in=
crease //We reduced the load and manually start the Gen","Albran Byorel","E=
quipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, site we=
nt down because gen started and stopped due to load increase //We reduced t=
he load and manually start the Gen","mouliom.anselme@matech-cameroun.com","=
2477","02-04-2025 13:20:17","MATECH CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004709092","O=
dza II OCM","","02-04-2025 12:56:25","02-04-2025 12:49:13","02-04-2025 15:4=
2:45","Grid outage, site went down because gen failed to start due to no au=
tomatism // grid return","Albran Byorel","Fuel Outage (Probable)","Passive"=
,"Diesel","Fuel Line Issue","Grid outage, site went down because gen failed=
 to start due to no automatism // grid return","cedric.tiani@matech-camerou=
n.com","434","02-04-2025 12:56:25","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004709000","Mam=
bine","","02-04-2025 12:39:36","02-04-2025 12:19:23","02-04-2025 12:53:10",=
"Grid outage, Site went down because Gen started and stopped due to Hybrid =
System malfunction//He reset and manually start the Gen","Fanda Brice","Equ=
ipment Repair","Passive","Hybrid","Hybrid Module","Grid outage, Site went d=
own because Gen started and stopped due to Hybrid System malfunction//He re=
set and manually start the Gen","cedric.tiani@matech-cameroun.com","1214","=
02-04-2025 12:39:36","MATECH CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0004708708","S=
apeur","","02-04-2025 11:54:45","02-04-2025 11:28:33","02-04-2025 12:45:46"=
,"Grid outage site went down before Gen start due to poor Battery backup// =
Gen started manually","Mboua Thierry","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage site went down before Ge=
n start due to poor Battery backup// Gen started manually","cedric.tiani@ma=
tech-cameroun.com","1573","02-04-2025 11:54:45","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004708704","E=
MANA BILICK CITY","","02-04-2025 11:54:06","02-04-2025 11:41:55","02-04-202=
5 12:50:18","Grid outage.gen failed to start due to automation malfunctionn=
ing//Gen manually started ","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","ATS-AMF Issue","Grid outage.gen failed to start due to aut=
omation malfunctionning//Gen manually started ","cedric.tiani@matech-camero=
un.com","733","02-04-2025 11:54:06","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004708642","Oko=
lo Kilombo","","02-04-2025 11:51:25","02-04-2025 11:46:27","02-04-2025 13:0=
6:27","Grid outage, site went down because gen fails to start due to Gen ca=
ble faulty // He bypassed gen cable and gen manually started","Fabrice Poua=
kam","Equipment Repair","Passive","Infrastructure","Armoured Cable","Grid o=
utage, site went down because gen fails to start due to Gen cable faulty //=
 He bypassed gen cable and gen manually started","cedric.tiani@matech-camer=
oun.com","299","02-04-2025 11:51:25","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004708626","Ako=
k Ndoe Yde","","02-04-2025 11:47:25","02-04-2025 11:30:14","02-04-2025 12:2=
2:15","Grid outage, Site down due to poor battery backup // Gen started aut=
omatically","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site down due to poor battery ba=
ckup // Gen started automatically","cedric.tiani@matech-cameroun.com","1032=
","02-04-2025 11:47:25","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004708619","Nko=
abang2","","02-04-2025 11:46:30","02-04-2025 11:34:20","02-04-2025 11:50:59=
","Grid outage, Site went down because Gen stopped due to overload(20kva, 3=
00A) SS IHS Alphonse Deffo is confirmed  // Grid Restored","Mba Lazare Herv=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, =
Site went down because Gen stopped due to overload(20kva, 300A) SS IHS Alph=
onse Deffo is confirmed  // Grid Restored","cedric.tiani@matech-cameroun.co=
m","732","02-04-2025 11:46:30","MATECH CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0004708534","N=
goum","","02-04-2025 11:33:59","02-04-2025 11:04:46","02-04-2025 13:10:15",=
"Solar Hybrid GEN site, No power issue site on Solar, with U=3D52.7V. The T=
x Fme Gregoire (654547479) from Huawei informed","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Solar Hybrid GEN site, No power issue site on Solar, with U=3D52.7V. The =
Tx Fme Gregoire (654547479) from Huawei informed","cedric.tiani@matech-came=
roun.com","1755","02-04-2025 11:33:59","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004708506","E=
kombitie","","02-04-2025 11:27:56","02-04-2025 11:24:46","02-04-2025 15:17:=
53","Grid fluctuation, Site went down because gen failed to start due to gr=
id bad voltage,no rcp// He bypassed the Grid and site on Gen","Fabrice Poua=
kam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, Site went down because gen failed to start due to gri=
d bad voltage,no rcp// He bypassed the Grid and site on Gen","cedric.tiani@=
matech-cameroun.com","191","02-04-2025 11:27:56","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004708497","M=
essassi okolo","","02-04-2025 11:26:17","02-04-2025 11:17:07","02-04-2025 1=
2:53:29","Grid outage,Site went down because static charger cable is faulty=
 which causes battery GE discharged /He started the Gen manually with an ex=
ternal battery","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Battery","Grid outage,Site went down because static charge=
r cable is faulty which causes battery GE discharged /He started the Gen ma=
nually with an external battery","cedric.tiani@matech-cameroun.com","552","=
02-04-2025 11:26:17","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004708446","Meh=
anda 1","","02-04-2025 11:17:30","02-04-2025 11:13:19","02-04-2025 15:04:55=
","Grid outage gen failed to start due to pear faulty //Grid return ","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Lifting Pum=
p Faulty","Grid outage gen failed to start due to pear faulty //Grid return=
 ","cedric.tiani@matech-cameroun.com","251","02-04-2025 11:17:30","MATECH C=
MR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004708410","Imm=
-Olympique","","02-04-2025 11:12:33","02-04-2025 11:06:23","02-04-2025 11:1=
6:50","Grid fluctuation , site went down before Gen started due to poor bat=
tery backup// Grid Power return","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid fluctuation , site wen=
t down before Gen started due to poor battery backup// Grid Power return","=
cedric.tiani@matech-cameroun.com","371","02-04-2025 11:12:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0004708383","Messassi=
 2","","02-04-2025 11:06:42","02-04-2025 09:59:36","02-04-2025 11:50:17","S=
ite went down due to rectifiers dysfunctionning //We reset rectifiers and s=
ite on grid ","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to rectifiers dysfunctionning //We res=
et rectifiers and site on grid ","joelle.ekessi@ihstowers.com","4027","02-0=
4-2025 11:06:42","MATECH CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004708338","M=
ontee-Anne-Rouge","","02-04-2025 10:58:30","02-04-2025 10:41:56","02-04-202=
5 12:13:07","Grid outage no space to deploy mobile gen//Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e no space to deploy mobile gen//Grid return","cedric.tiani@matech-cameroun=
.com","995","02-04-2025 10:58:30","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004708194","Cit=
e des nations","","02-04-2025 10:47:59","02-04-2025 10:45:50","02-04-2025 1=
1:03:07","Site went down due to insufficient rectifiers(02/03) Faulty on si=
te//Site stabilised","Paul BIBOUM","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to insufficient rectifiers(02/03) F=
aulty on site//Site stabilised","cedric.tiani@matech-cameroun.com","130","0=
2-04-2025 10:47:59","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004708186","Ron=
d Point Express1114","","02-04-2025 10:46:58","02-04-2025 10:43:36","02-04-=
2025 10:49:14","Grid outage, Site down due to poor battery backup // Gen st=
art automatically","Hyemafo Gildas","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site down due to poor bat=
tery backup // Gen start automatically","cedric.tiani@matech-cameroun.com",=
"202","02-04-2025 10:46:58","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004708143","Bas=
tos-BAT","","02-04-2025 10:42:12","02-04-2025 10:33:07","03-04-2025 10:47:0=
4","Grid outage , site went down before Gen started due to poor battery bac=
kup// Grid Power return","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage , site went down befo=
re Gen started due to poor battery backup// Grid Power return","cedric.tian=
i@matech-cameroun.com","546","02-04-2025 10:42:12","MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0004708029","Mvo=
g Betsi Hospital","","02-04-2025 10:24:13","02-04-2025 10:22:02","02-04-202=
5 11:29:23","Grid outage,gen ran till fuel shortage//Refueling done","Hyema=
fo Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,ge=
n ran till fuel shortage//Refueling done","cedric.tiani@matech-cameroun.com=
","131","02-04-2025 10:24:13","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004707946","M=
essa-Carriere OCM","","02-04-2025 10:08:43","02-04-2025 10:03:25","02-04-20=
25 12:45:42","No power issue site on grid with U=3D53.7v Lionnel Steeve fro=
m Huawei is informed","","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D5=
3.7v Lionnel Steeve from Huawei is informed","cedric.tiani@matech-cameroun.=
com","320","02-04-2025 10:08:43","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004707910","Nko=
lnda","","02-04-2025 09:59:57","02-04-2025 09:51:37","02-04-2025 11:04:15",=
"Grid fluctuation, Site went down because gen fails to start due to grid ba=
d voltage// He bypasse the Grid and site on Gen","Albran Byorel","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid fluctuation,=
 Site went down because gen fails to start due to grid bad voltage// He byp=
asse the Grid and site on Gen","cedric.tiani@matech-cameroun.com","501","02=
-04-2025 09:59:57","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004707501","M=
arche Odza","","02-04-2025 08:42:30","02-04-2025 08:34:26","02-04-2025 11:1=
4:25","Grid outage gen failed to start due to charging alternator faulty//G=
rid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Charging Alternator","Grid outage gen failed to start due to charging alte=
rnator faulty//Grid return","joelle.ekessi@ihstowers.com","486","02-04-2025=
 08:42:30","MATECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0004707496","N=
koa Ayos","","02-04-2025 08:41:38","02-04-2025 08:13:33","02-04-2025 13:20:=
39","ACTIVE// Tx issue: Ubaie=3D55.5V site on Grid The TX fme Lionel Tchatc=
houa/694693436/ of Huawei is inform","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// T=
x issue: Ubaie=3D55.5V site on Grid The TX fme Lionel Tchatchoua/694693436/=
 of Huawei is inform","joelle.ekessi@ihstowers.com","1686","02-04-2025 08:4=
1:38","MATECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0004707427","GSO=
","","02-04-2025 08:28:12","02-04-2025 07:54:01","02-04-2025 11:47:52","Gri=
d fluctuation, Site went down because gen failed to start due to grid bad v=
oltage// He bypassed the Grid and site on Gen","MINKA NICOLAS","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion, Site went down because gen failed to start due to grid bad voltage// H=
e bypassed the Grid and site on Gen","cedric.tiani@matech-cameroun.com","20=
52","02-04-2025 08:28:12","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004707373","N=
kolfon Cimencam","","02-04-2025 08:18:09","02-04-2025 08:10:00","02-04-2025=
 08:15:25","Active//No power issue, Site on Grid Ubai=3D 52,8V. Notice that=
 it is impacted by Afanoya II The Tx FME Fulbert from Huawei is informed","=
Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 52=
,8V. Notice that it is impacted by Afanoya II The Tx FME Fulbert from Huawe=
i is informed","cedric.tiani@matech-cameroun.com","490","02-04-2025 08:18:0=
9","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004707317","Nko=
lnda","","02-04-2025 08:09:08","02-04-2025 08:02:55","02-04-2025 09:26:40",=
"Grid outage.gen ran until fuel shortage//Refueling done","Albran Byorel","=
Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until =
fuel shortage//Refueling done","cedric.tiani@matech-cameroun.com","374","02=
-04-2025 08:09:08","MATECH CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0004707245","NKO=
NGKARAK","","02-04-2025 07:54:24","02-04-2025 07:38:55","02-04-2025 08:05:0=
2","Hybrid gen site  gen start and stopped due to pellet pierced causing ra=
diator leakage //We add water and gen manually started ","TIENTCHEU NZETCHI=
EU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator Leakage",=
"Grid outage gen start and stopped due to pellet pierced//We add water and =
gen manually started ","cedric.tiani@matech-cameroun.com","930","02-04-2025=
 07:54:24","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004707205","Imm=
-Olympique","","02-04-2025 07:44:00","02-04-2025 07:38:14","02-04-2025 09:5=
2:16","Grid outage.gen ran until fuel shortage//Refueling done","Paul BIBOU=
M","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran un=
til fuel shortage//Refueling done","cedric.tiani@matech-cameroun.com","347"=
,"02-04-2025 07:44:00","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004707125","Man=
guiers Dispensaire","","02-04-2025 07:23:20","02-04-2025 07:17:06","02-04-2=
025 07:27:39","Site went down due to 3/4 rectifier faulty on site // He res=
et rectifiers  Rectifier: Site on grid","Fabrice Pouakam","Equipment Repair=
","Passive","Rectifier","Rectifier Module","Site went down due to 3/4 recti=
fier faulty on site // He reset rectifiers  Rectifier: Site on grid","cedri=
c.tiani@matech-cameroun.com","374","02-04-2025 07:23:20","MATECH CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0004706831","Eto=
ug-Ebe 2","","02-04-2025 06:00:55","02-04-2025 05:53:44","02-04-2025 11:18:=
22","Grid only site ,No space to deploy  mobile gen//Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only sit=
e ,No space to deploy  mobile gen//Grid return","olivier.kwedi@ihstowers.co=
m","432","02-04-2025 06:00:55","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004706651","Ole=
mbe MTN","","02-04-2025 04:41:05","02-04-2025 04:27:57","02-04-2025 06:04:2=
9","Site went down due to insufficiency of rectifiers on site // site stabi=
lized(need to add 01 rectifier)","Fabrice Pouakam","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","Site went down due to insufficiency of=
 rectifiers on site // site stabilized(need to add 01 rectifier)","olivier.=
kwedi@ihstowers.com","788","02-04-2025 04:41:05","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004706635","B=
arriere IHS","","02-04-2025 04:34:42","01-04-2025 22:06:26","02-04-2025 02:=
25:03","Site went down because CB (125A) tripped in PWC who feeds equipment=
s OCM // CB rearmed","Hyemafo Gildas","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Circuit Breaker Issue","Site went down because CB =
(125A) tripped in PWC who feeds equipments OCM // CB rearmed","ludivine.nga=
maleu@ihstowers.com","23297","02-04-2025 04:34:42","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004706568","F=
ouda-New","","02-04-2025 04:04:10","02-04-2025 03:37:53","02-04-2025 05:25:=
44","Site went down due to MPR dyfunctionning //We reset rectifiers for res=
cue the site ","Delor Telezing","Equipment Repair","Passive","Rectifier","R=
ectifier Cabinet","Site went down due to MPR dyfunctionning //We reset rect=
ifiers for rescue the site ","ludivine.ngamaleu@ihstowers.com","24540","02-=
04-2025 04:04:10","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004706458","Aka=
k-Nkozoa-MTN-IHS","","02-04-2025 03:12:05","02-04-2025 02:25:50","02-04-202=
5 02:49:50","Access issue at night due to Landlord Grid outage, site went d=
own because gen failed to start due to PWC ZTE malfunctionning// He reset c=
ontroller and gen manually started","Fabrice Pouakam","Access Denial","Leas=
e Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access is=
sue at night due to Landlord Grid outage, site went down because gen failed=
 to start due to PWC ZTE malfunctionning// He reset controller and gen manu=
ally started","olivier.kwedi@ihstowers.com","31177","02-04-2025 03:12:05","=
MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004706343","Ngoum","=
","02-04-2025 02:25:51","02-04-2025 00:51:35","02-04-2025 08:18:52","Cascad=
ed Incident from TTO4794905","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Griid outage,site went down because Gen r=
an until Fuel shortage / Refueling will be done by Edonde","system","292306=
","02-04-2025 02:25:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004706344","Yoko MTN=
","","02-04-2025 02:25:51","02-04-2025 00:51:35","02-04-2025 08:18:52","Cas=
caded Incident from TTO4794905","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Griid outage,site went down because Ge=
n ran until Fuel shortage / Refueling will be done by Edonde","system","292=
306","02-04-2025 02:25:51","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004706160","Elig Edz=
oa","","02-04-2025 01:50:56","02-04-2025 01:24:51","02-04-2025 03:32:03","C=
ascaded Incident from TTO4794912","Delor Telezing","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site T :53.6 V ,Site=
 on grid, Brice tsague is informed","system","268770","02-04-2025 01:50:56"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_134","NOCINC0004706156","Vallee B=
astos MTN","","02-04-2025 01:50:55","02-04-2025 01:24:51","02-04-2025 03:32=
:03","Cascaded Incident from TTO4794912","Mboua Thierry","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site T :53.6 V=
 ,Site on grid, Brice tsague is informed","system","268767","02-04-2025 01:=
50:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_009","NOCINC0004706155","CLE Buil=
ding","","02-04-2025 01:50:55","02-04-2025 01:24:51","02-04-2025 03:32:03",=
"Cascaded Incident from TTO4794912","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue on site T :53.6 V ,Site on grid, Br=
ice tsague is informed","system","268765","02-04-2025 01:50:55","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0004706157","Nsam esc=
ale LP","","02-04-2025 01:50:55","02-04-2025 01:24:51","02-04-2025 03:32:03=
","Cascaded Incident from TTO4794912","","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue on site T :53.6 V ,Site on grid, =
Brice tsague is informed","system","268770","02-04-2025 01:50:55","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0004706158","Hopital =
Central","","02-04-2025 01:50:55","02-04-2025 01:24:51","02-04-2025 03:32:0=
3","Cascaded Incident from TTO4794912","","Cascade Outage","Active","Cascad=
e Active","Cascade Active","No power issue on site T :53.6 V ,Site on grid,=
 Brice tsague is informed","system","268771","02-04-2025 01:50:55","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0004706159","Charles-=
Atangana","","02-04-2025 01:50:55","02-04-2025 01:24:51","02-04-2025 03:32:=
03","Cascaded Incident from TTO4794912","","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site T :53.6 V ,Site on grid=
, Brice tsague is informed","system","268768","02-04-2025 01:50:55","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_016","NOCINC0004706154","Maetur",=
"","02-04-2025 01:50:54","02-04-2025 01:24:51","02-04-2025 03:32:03","Casca=
ded Incident from TTO4794912","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site T :53.6 V ,Site on g=
rid, Brice tsague is informed","system","268771","02-04-2025 01:50:54","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0004706153","ELIg-Ess=
ono","","02-04-2025 01:50:54","02-04-2025 01:24:51","02-04-2025 03:32:03","=
Cascaded Incident from TTO4794912","Delor Telezing","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site T :53.6 V ,Sit=
e on grid, Brice tsague is informed","system","268769","02-04-2025 01:50:54=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0004706150","HOPITAL =
DE LA CAISSE","","02-04-2025 01:50:54","02-04-2025 01:24:51","02-04-2025 03=
:32:03","Cascaded Incident from TTO4794912","Delor Telezing","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site T :53=
.6 V ,Site on grid, Brice tsague is informed","system","268765","02-04-2025=
 01:50:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0004706152","Garbati =
building","","02-04-2025 01:50:54","02-04-2025 01:24:51","02-04-2025 03:32:=
03","Cascaded Incident from TTO4794912","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site T :53.6 V=
 ,Site on grid, Brice tsague is informed","system","268769","02-04-2025 01:=
50:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_013","NOCINC0004706151","Laborato=
ire T.Bella","","02-04-2025 01:50:54","02-04-2025 01:24:51","02-04-2025 03:=
32:03","Cascaded Incident from TTO4794912","Paul BIBOUM","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site T :53.6 V=
 ,Site on grid, Brice tsague is informed","system","268767","02-04-2025 01:=
50:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_091","NOCINC0004706147","Jouvence=
 2000","","02-04-2025 01:50:53","02-04-2025 01:24:51","02-04-2025 03:32:03"=
,"Cascaded Incident from TTO4794912","Delor Telezing","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue on site T :53.6 V ,S=
ite on grid, Brice tsague is informed","system","268766","02-04-2025 01:50:=
53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0004706146","Mamch Bu=
ilding","","02-04-2025 01:50:53","02-04-2025 01:24:51","02-04-2025 03:32:03=
","Cascaded Incident from TTO4794912","Mboua Thierry","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue on site T :53.6 V ,S=
ite on grid, Brice tsague is informed","system","268767","02-04-2025 01:50:=
53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_049","NOCINC0004706148","Etoa-Mek=
i","","02-04-2025 01:50:53","02-04-2025 01:24:51","02-04-2025 03:32:03","Ca=
scaded Incident from TTO4794912","Delor Telezing","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site T :53.6 V ,Site =
on grid, Brice tsague is informed","system","268769","02-04-2025 01:50:53",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0004706149","POLYCLIN=
IQUE TSINGA","","02-04-2025 01:50:53","02-04-2025 01:24:51","02-04-2025 03:=
32:03","Cascaded Incident from TTO4794912","Mboua Thierry","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site T :53.6=
 V ,Site on grid, Brice tsague is informed","system","268770","02-04-2025 0=
1:50:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_084","NOCINC0004706144","Briquett=
erie","","02-04-2025 01:50:52","02-04-2025 01:24:51","02-04-2025 03:32:03",=
"Cascaded Incident from TTO4794912","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue on site T :53.6 V ,Site on grid, Br=
ice tsague is informed","system","268768","02-04-2025 01:50:52","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004706145","Bastos B=
ethesda","","02-04-2025 01:50:52","02-04-2025 01:24:51","02-04-2025 03:32:0=
3","Cascaded Incident from TTO4794912","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site T :53.6 V ,=
Site on grid, Brice tsague is informed","system","268772","02-04-2025 01:50=
:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0004706143","H-Franco=
 New","","02-04-2025 01:50:52","02-04-2025 01:24:51","02-04-2025 03:32:03",=
"Cascaded Incident from TTO4794912","Delor Telezing","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site T :53.6 V ,Si=
te on grid, Brice tsague is informed","system","268766","02-04-2025 01:50:5=
2","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_790","NOCINC0004706142","TRB Cent=
re ville","","02-04-2025 01:50:52","02-04-2025 01:24:51","02-04-2025 03:32:=
03","Cascaded Incident from TTO4794912","Yamen Herman","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site T :53.6 V ,=
Site on grid, Brice tsague is informed","system","268766","02-04-2025 01:50=
:52","MATECH CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0004706110","Hot=
el de Ville Yde","IHS_YND_790, IHS_YND_711, IHS_YND_460, IHS_YND_084, IHS_Y=
ND_563, IHS_YND_051, IHS_YND_091, IHS_YND_049, IHS_YND_086, IHS_YND_064, IH=
S_YND_013, IHS_YND_024, IHS_YND_014, IHS_YND_016, IHS_YND_009, IHS_YND_134,=
 IHS_YND_732, IHS_YND_027, IHS_YND_125, IHS_YND_504","02-04-2025 01:39:58",=
"02-04-2025 01:24:51","02-04-2025 03:32:03","No power issue on site T :53.6=
 V ,Site on grid, Brice tsague is informed","Paul BIBOUM","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site T :53.6 V ,Site on grid, Brice tsague is informed","olivi=
er.kwedi@ihstowers.com","907","02-04-2025 01:39:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004706106","Ngouetou=
","","02-04-2025 01:38:02","02-04-2025 00:51:35","02-04-2025 08:18:30","Cas=
caded Incident from TTO4794782","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Griid outage,site went down because Ge=
n ran until Fuel shortage / Refueling will be done by Edonde","system","124=
1735","02-04-2025 01:38:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0004706105","Yoko OCM=
","","02-04-2025 01:38:01","02-04-2025 00:51:35","02-04-2025 08:18:30","Cas=
caded Incident from TTO4794782","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Griid outage,site went down because Ge=
n ran until Fuel shortage / Refueling will be done by Edonde","system","124=
1736","02-04-2025 01:38:01","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004706104","Matsari"=
,"","02-04-2025 01:38:01","02-04-2025 00:51:35","02-04-2025 08:18:30","Casc=
aded Incident from TTO4794782","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","No power issue on site T :53.6 V ,Site =
on grid, Brice tsague is informed","system","1241735","02-04-2025 01:38:01"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0004705988","M=
BIMBIM","IHS_YND_475, IHS_YND_460, IHS_YND_474, IHS_YND_454, IHS_YND_473","=
02-04-2025 01:04:51","02-04-2025 00:51:35","02-04-2025 08:18:52","Griid out=
age,site went down because Gen ran until Fuel shortage / Refueling will be =
done by Edonde","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Griid outage,site went down because Gen ran until Fuel shortage / Re=
fueling will be done by Edonde","ludivine.ngamaleu@ihstowers.com","797","02=
-04-2025 01:04:51","MATECH CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004705933","Meh=
anda 1","","02-04-2025 00:48:05","01-04-2025 23:39:54","02-04-2025 09:16:43=
","Fme reported acces issue on site at Night Due to landlord//Site went dow=
n because Gen failed to start due to Grid bad voltage,no rcp on site// He b=
ypassed the Grid and site on Gen","Albran Byorel","Access Denial","Lease Or=
 Legal","Landlord Related Issues","Access Issue - Land Lord","Fme reported =
acces issue on site at Night Due to landlord//Site went down because Gen fa=
iled to start due to Grid bad voltage,no rcp on site// He bypassed the Grid=
 and site on Gen","olivier.kwedi@ihstowers.com","4092","02-04-2025 00:48:05=
","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004705883","M=
arche Odza","","02-04-2025 00:28:37","01-04-2025 20:48:10","02-04-2025 01:4=
5:31","Grid Low voltage, Gen fail to start // Grid return","Albran Byorel",=
"Grid Supply","Passive","Grid","National Grid - Low Current Supply","Grid L=
ow voltage, Gen fail to start // Grid return","ludivine.ngamaleu@ihstowers.=
com","13228","02-04-2025 00:28:37","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004705777","O=
lembe-Terminus","","02-04-2025 00:07:34","01-04-2025 20:08:21","01-04-2025 =
20:10:28","No power issue site on grid with U=3D54.85v Symphorien(650257151=
) from Huawei was working on site ","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue site on grid with U=3D54.85v Symphorien(650257151) from Huawei was wo=
rking on site ","etienne.itondo@ihstowers.com","14355","02-04-2025 00:07:34=
","MATECH CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004705467","Ona=
ngondi (melen bikop)","","01-04-2025 23:03:50","01-04-2025 22:20:25","01-04=
-2025 23:23:33","Hybrid gen site.site went down due to hybrid system malfun=
ctionning // Gen manually started","Fanda Brice","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Hybrid gen site.site went down due to=
 hybrid system malfunctionning // Gen manually started","olivier.kwedi@ihst=
owers.com","2606","01-04-2025 23:03:50","MATECH CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004705465","C=
ite-Verte","","01-04-2025 23:03:43","01-04-2025 22:26:26","02-04-2025 03:42=
:02","Access issue at night due to landlord //Site went down due to CB((125=
A)*(63A)) which powered OCM equipements tripped//CB rearmed","","Access Den=
ial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord",=
"Access issue at night due to landlord //Site went down due to CB((125A)*(6=
3A)) which powered OCM equipements tripped//CB rearmed","ludivine.ngamaleu@=
ihstowers.com","2238","01-04-2025 23:03:43","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004705463","Mon=
tee Jouvence","","01-04-2025 23:02:55","01-04-2025 22:01:45","01-04-2025 23=
:11:25","Grid outage,, Gen failed to start due to poor Battery  backup // H=
e started the Gen manually","Hyemafo Gildas","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage,, Gen failed to s=
tart due to poor Battery  backup // He started the Gen manually","olivier.k=
wedi@ihstowers.com","3671","01-04-2025 23:02:55","MATECH CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0004705340","I=
mm-Olympique","","01-04-2025 22:35:19","01-04-2025 14:25:45","02-04-2025 02=
:40:19","OCM CB Tripped / OCM BTS CB rearmed, No power issue on site ,Brice=
 tchague is informed by SMS","Paul BIBOUM","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","OCM CB Tripped / OCM=
 BTS CB rearmed, No power issue on site ","cedric.tiani@matech-cameroun.com=
","29375","01-04-2025 22:35:19","MATECH CMR"
"Closed Complete","Site Down","T1591","IHS_YND_172","NOCINC0004705022","Tra=
dex-Nkomo","","01-04-2025 21:30:28","01-04-2025 20:20:15","01-04-2025 20:21=
:21","No power issue site on grid with U=3D53.7v Lionnel Steeve(655184876) =
from Huawei is informed","Albran Byorel","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with U=3D53.7v Lionnel Steeve(655184876) from Huawei is informed","lo=
ic.noumsi@matech-cameroun.com","4214","01-04-2025 21:30:28","MATECH CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004705021","E=
beba","","01-04-2025 21:28:47","01-04-2025 16:57:47","01-04-2025 20:18:10",=
"Low level of water in the radiator // Water add and Gen start manually","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","Low =
level of water in the radiator // Water add and Gen start manually
","cedric.tiani@matech-cameroun.com","16261","01-04-2025 21:28:47","MATECH =
CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004704727","UPA=
C LP","","01-04-2025 20:33:19","01-04-2025 20:13:10","01-04-2025 20:49:04",=
"Grid outage,no space to deploy MDG // Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage,no space to dep=
loy MDG // Grid return","cedric.tiani@matech-cameroun.com","1210","01-04-20=
25 20:33:19","MATECH CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004704682","B=
arriere IHS","","01-04-2025 20:20:19","01-04-2025 19:24:06","01-04-2025 20:=
24:06","No power issue T: 58.5 V Load:91.5 A, OCM CB Tripped // OCM BTS rea=
rmed. Synphorien is informed","Hyemafo Gildas","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue T=
: 58.5 V Load:91.5 A, OCM CB Tripped // OCM BTS rearmed. Synphorien is info=
rmed","cedric.tiani@matech-cameroun.com","3375","01-04-2025 20:20:19","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004704664","S=
OA TOWN","","01-04-2025 20:19:05","01-04-2025 19:40:51","01-04-2025 21:41:3=
8","Disjunction in the Bay due to insufficiency of rectifiers // Disjunctor=
 rearmed","Siligap Boris","Equipment Repair","Passive","Control Panel","Rec=
tifier Battery Breaker Tripped","Disjunction in the Bay due to insufficienc=
y of rectifiers // Disjunctor rearmed","cedric.tiani@matech-cameroun.com","=
2296","01-04-2025 20:19:05","MATECH CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004704586","M=
ontee-Anne-Rouge","","01-04-2025 20:00:12","01-04-2025 17:49:54","02-04-202=
5 10:24:01","Grid outage,no space to deploy MDG .///grid power return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age,no space to deploy MDG .///grid power return","cedric.tiani@matech-came=
roun.com","7819","01-04-2025 20:00:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004704486","Entree C=
ite Verte","","01-04-2025 19:35:13","01-04-2025 14:02:53","01-04-2025 17:49=
:47","Cascaded Incident from TTO4791741","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bec=
ause Gen failed to start  due to fuse of  gen card is faulty// He made a br=
idge of fuse, Site on gen","system","280895","01-04-2025 19:35:13","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0004704485","Dagobert=
","","01-04-2025 19:35:12","01-04-2025 14:02:53","01-04-2025 17:49:47","Cas=
caded Incident from TTO4791741","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down=
 because Gen failed to start  due to fuse of  gen card is faulty// He made =
a bridge of fuse, Site on gen","system","280896","01-04-2025 19:35:12","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0004704483","Crf-Nkol=
bisson","","01-04-2025 19:35:12","01-04-2025 14:02:53","01-04-2025 17:49:47=
","Cascaded Incident from TTO4791741","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, Site wen=
t down because Gen failed to start  due to fuse of  gen card is faulty// He=
 made a bridge of fuse, Site on gen","system","280892","01-04-2025 19:35:12=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004704484","Tsinga",=
"","01-04-2025 19:35:12","01-04-2025 14:02:53","01-04-2025 17:49:47","Casca=
ded Incident from TTO4791741","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, Site went down because Gen =
failed to start  due to fuse of  gen card is faulty// He made a bridge of f=
use, Site on gen","system","280892","01-04-2025 19:35:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0004704479","Bastos-N=
ylon","","01-04-2025 19:35:11","01-04-2025 14:02:53","01-04-2025 17:49:47",=
"Cascaded Incident from TTO4791741","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen failed to start  due to fuse of  gen card is faulty// He made a bridg=
e of fuse, Site on gen","system","280893","01-04-2025 19:35:11","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004704478","Nkomkana=
","","01-04-2025 19:35:11","01-04-2025 14:02:53","01-04-2025 17:49:47","Cas=
caded Incident from TTO4791741","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage, Site went down because Gen failed to s=
tart  due to fuse of  gen card is faulty// He made a bridge of fuse, Site o=
n gen","system","280894","01-04-2025 19:35:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0004704482","Yona Hot=
el","","01-04-2025 19:35:11","01-04-2025 14:02:53","01-04-2025 17:49:47","C=
ascaded Incident from TTO4791741","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went do=
wn because Gen failed to start  due to fuse of  gen card is faulty// He mad=
e a bridge of fuse, Site on gen","system","280896","01-04-2025 19:35:12","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004704481","Bastos B=
ethesda","","01-04-2025 19:35:11","01-04-2025 14:02:53","01-04-2025 17:49:4=
7","Cascaded Incident from TTO4791741","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bec=
ause Gen failed to start  due to fuse of  gen card is faulty// He made a br=
idge of fuse, Site on gen","system","280891","01-04-2025 19:35:11","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0004704480","Meyong-M=
eyeme","","01-04-2025 19:35:11","01-04-2025 14:02:53","01-04-2025 17:49:47"=
,"Cascaded Incident from TTO4791741","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went=
 down because Gen failed to start  due to fuse of  gen card is faulty// He =
made a bridge of fuse, Site on gen","system","280892","01-04-2025 19:35:11"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0004704477","Cite-Ver=
te","","01-04-2025 19:35:10","01-04-2025 14:02:53","01-04-2025 17:49:47","C=
ascaded Incident from TTO4791741","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, Site went down because Gen failed to=
 start  due to fuse of  gen card is faulty// He made a bridge of fuse, Site=
 on gen","system","280894","01-04-2025 19:35:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004704474","Golf Qua=
ter","","01-04-2025 19:35:10","01-04-2025 14:02:53","01-04-2025 17:49:47","=
Cascaded Incident from TTO4791741","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen failed to start  due to fuse of  gen card is faulty// He made a bridge=
 of fuse, Site on gen","system","280893","01-04-2025 19:35:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004704476","Nkomkana=
 2","","01-04-2025 19:35:10","01-04-2025 14:02:53","01-04-2025 17:49:47","C=
ascaded Incident from TTO4791741","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
Gen failed to start  due to fuse of  gen card is faulty// He made a bridge =
of fuse, Site on gen","system","280895","01-04-2025 19:35:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004704475","AFEME NO=
RD","","01-04-2025 19:35:10","01-04-2025 14:02:53","01-04-2025 17:49:47","C=
ascaded Incident from TTO4791741","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went do=
wn because Gen failed to start  due to fuse of  gen card is faulty// He mad=
e a bridge of fuse, Site on gen","system","280891","01-04-2025 19:35:10","M=
ATECH CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0004704473","Nkolbi-B=
oss","","01-04-2025 19:35:09","01-04-2025 14:02:53","01-04-2025 17:49:47","=
Cascaded Incident from TTO4791741","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went d=
own because Gen failed to start  due to fuse of  gen card is faulty// He ma=
de a bridge of fuse, Site on gen","system","280895","01-04-2025 19:35:09","=
MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004704468","Nlo=
ngkak","","01-04-2025 19:33:55","01-04-2025 16:56:32","01-04-2025 17:14:12"=
,"Grid outage, Site down due to poor battery backup // Gen start automatica=
lly","Delor Telezing","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, Site down due to poor battery backup //=
 Gen start automatically
","cedric.tiani@matech-cameroun.com","9444","01-04-2025 19:33:55","MATECH C=
MR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004704436","E=
koumdoum","","01-04-2025 19:30:39","01-04-2025 19:12:07","01-04-2025 19:34:=
51","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS Pa=
scaline is informed and confirmed//Grid return","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down=
 due to Gen overload(20kva,280 A) IHS SS Pascaline is informed and confirme=
d//Grid return","cedric.tiani@matech-cameroun.com","1113","01-04-2025 19:30=
:39","MATECH CMR"
"Closed Complete","Site Down","CTR_339","IHS_YND_073","NOCINC0004704424","C=
hapelle-Obili","","01-04-2025 19:28:10","01-04-2025 14:25:58","01-04-2025 1=
4:30:53","No power issue site on grid with U=3D54.6v Mbah Osiah from Huawei=
 is informed","Paul BIBOUM","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54.6v Mbah Osiah from Huawei is informed","cedric.tiani@matech-cameroun.=
com","18132","01-04-2025 19:28:10","MATECH CMR"
"Closed Complete","Site Down","T0535","IHS_YND_234","NOCINC0004704362","Oyo=
mabang MTN","","01-04-2025 19:12:39","01-04-2025 15:51:41","01-04-2025 18:4=
8:48","Grid Outage Site went down because Gen failed To start due to Alarm =
""Underfrequency//He started manually gen","TIENTCHEU NZETCHIEU GAEL","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage Site=
 went down because Gen failed To start due to Alarm ""Underfrequency//He st=
arted manually gen","loic.noumsi@matech-cameroun.com","12058","01-04-2025 1=
9:12:39","MATECH CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0004704359","Jou=
vence 2000","","01-04-2025 19:11:40","01-04-2025 15:25:13","01-04-2025 19:0=
1:32","site down due to fuel // Refueling done (100L)","Delor Telezing","Fu=
el Outage","Passive","Diesel","Diesel Outage","site down due to fuel // Ref=
ueling done (100L)","cedric.tiani@matech-cameroun.com","13588","01-04-2025 =
19:11:40","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004704229","E=
kombitie","","01-04-2025 18:48:16","01-04-2025 17:48:05","01-04-2025 18:49:=
50","Active: no power issue, site is on Gen with Ubaie=3D54,5V, Symphorien(=
650257151) from huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: n=
o power issue, site is on Gen with Ubaie=3D54,5V, Symphorien(650257151) fro=
m huawei is informed
","cedric.tiani@matech-cameroun.com","3612","01-04-2025 18:48:16","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0004704020","NTUI TOW=
N","","01-04-2025 17:53:37","01-04-2025 17:18:24","01-04-2025 18:05:38","Ca=
scaded Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site impcted by 3rd party","system","=
269168","01-04-2025 17:53:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004704021","Yoko MTN=
","","01-04-2025 17:53:37","01-04-2025 17:18:24","01-04-2025 18:05:38","Cas=
caded Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site impcted by 3rd party","system","2=
69169","01-04-2025 17:53:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004704019","Dong",""=
,"01-04-2025 17:53:37","01-04-2025 17:18:24","01-04-2025 18:05:38","Cascade=
d Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","site impcted by 3rd party","system","26917=
3","01-04-2025 17:53:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0004704017","Nkol-Meb=
anga","","01-04-2025 17:53:36","01-04-2025 17:18:24","01-04-2025 18:05:38",=
"Cascaded Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site impcted by 3rd party","system=
","269172","01-04-2025 17:53:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004704018","Donga","=
","01-04-2025 17:53:36","01-04-2025 17:18:24","01-04-2025 18:05:38","Cascad=
ed Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site impcted by 3rd party","system","2691=
70","01-04-2025 17:53:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004704016","SAA Entr=
ance","","01-04-2025 17:53:36","01-04-2025 17:18:24","01-04-2025 18:05:38",=
"Cascaded Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site impcted by 3rd party","system=
","269171","01-04-2025 17:53:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_690","NOCINC0004704015","Ntui adm=
inistration","","01-04-2025 17:53:36","01-04-2025 17:18:24","01-04-2025 18:=
05:38","Cascaded Incident from TTO4792363","Parker Tchoup","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site impcted by 3rd party",=
"system","269168","01-04-2025 17:53:36","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004704012","Carrefou=
r Ayissi Ele","","01-04-2025 17:53:35","01-04-2025 17:18:24","01-04-2025 18=
:05:38","Cascaded Incident from TTO4792363","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","site impcted by 3rd party"=
,"system","269172","01-04-2025 17:53:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004704013","Ngoum","=
","01-04-2025 17:53:35","01-04-2025 17:18:24","01-04-2025 18:05:38","Cascad=
ed Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site impcted by 3rd party","system","2691=
70","01-04-2025 17:53:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004704011","SAA 2","=
","01-04-2025 17:53:35","01-04-2025 17:18:24","01-04-2025 18:05:38","Cascad=
ed Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site impcted by 3rd party","system","2691=
71","01-04-2025 17:53:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004704014","Ngouetou=
","","01-04-2025 17:53:35","01-04-2025 17:18:24","01-04-2025 18:05:38","Cas=
caded Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site impcted by 3rd party","system","2=
69167","01-04-2025 17:53:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0004704008","Nguila",=
"","01-04-2025 17:53:34","01-04-2025 17:18:24","01-04-2025 18:05:38","Casca=
ded Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site impcted by 3rd party","system","269=
169","01-04-2025 17:53:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004704010","Matsari"=
,"","01-04-2025 17:53:34","01-04-2025 17:18:24","01-04-2025 18:05:38","Casc=
aded Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site impcted by 3rd party","system","26=
9169","01-04-2025 17:53:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004704009","MBIMBIM"=
,"","01-04-2025 17:53:34","01-04-2025 17:18:24","01-04-2025 18:05:38","Casc=
aded Incident from TTO4792363","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site impcted by 3rd party","system","26=
9171","01-04-2025 17:53:34","MATECH CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004703905","Saa=
","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_404, IHS_YND_810, IHS_YND=
_475, IHS_YND_454, IHS_YND_690, IHS_YND_542, IHS_YND_809, IHS_YND_434, IHS_=
YND_444, IHS_YND_403, IHS_YND_473","01-04-2025 17:26:32","01-04-2025 17:18:=
24","01-04-2025 18:05:38","site impcted by 3rd party","Parker Tchoup","3RD =
Party Power Failure","Passive","Power Provided By 3RD Party","Power Provide=
d By 3RD Party","site impcted by 3rd party","cedric.tiani@matech-cameroun.c=
om","489","01-04-2025 17:26:32","MATECH CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004703813","M=
ontesquieux","","01-04-2025 17:03:09","01-04-2025 15:07:56","01-04-2025 17:=
33:19","Grid outage, Gen stopped due to alarm undervoltage (impacted by ) /=
/ Gen cart reset, on rectifier remouve, site is now on 03 rectifiers, and s=
ite is on Gen","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG =
- Under Voltage","Grid outage, Gen stopped due to alarm undervoltage (impac=
ted by ) // Gen cart reset, on rectifier remouve, site is now on 03 rectifi=
ers, and site is on Gen","cedric.tiani@matech-cameroun.com","6914","01-04-2=
025 17:03:09","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004703802","A=
WAE OCM","","01-04-2025 17:00:15","01-04-2025 16:09:04","01-04-2025 18:18:4=
2","bay malfunction // Bay reactivated","Mba Lazare Herve","Equipment Repai=
r","Passive","Hybrid","Site Down - Low Voltage","bay malfunction // Bay rea=
ctivated","cedric.tiani@matech-cameroun.com","17325","01-04-2025 17:00:15",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0004703512","Oyomaban=
g Ecole","","01-04-2025 16:04:01","01-04-2025 14:02:00","01-04-2025 16:09:4=
0","Active//No power issue, Site on Gen and Ubaie=3D 54,1V The TX Mouhamado=
u (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue, Site on Gen and Ubaie=3D 54,1V The TX Mouhamadou =
(6144435) from Huawei is informed.","system","7321","01-04-2025 16:04:01","=
MATECH CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004703495","N=
kolafeme","","01-04-2025 15:59:59","01-04-2025 14:02:53","01-04-2025 17:49:=
47","Grid outage, Site went down because Gen failed to start  because the f=
use of  gen card is faulty// He made a bridge of fuse, Site on gen","TIENTC=
HEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, Site went down because Gen failed to start  because t=
he fuse of  gen card is faulty// He made a bridge of fuse, Site on gen","ce=
dric.tiani@matech-cameroun.com","8364","01-04-2025 15:59:59","MATECH CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0004703360","O=
yomabang OCM","IHS_YND_273, IHS_YND_220, IHS_YND_519, IHS_YND_138, IHS_YND_=
202, IHS_YND_200, IHS_YND_287, IHS_YND_126, IHS_YND_230, IHS_YND_563, IHS_Y=
ND_271, IHS_YND_232, IHS_YND_127, IHS_YND_286, IHS_YND_543","01-04-2025 15:=
37:06","01-04-2025 14:02:53","01-04-2025 17:49:47","Grid outage, Site went =
down because Gen failed to start  due to fuse of  gen card is faulty// He m=
ade a bridge of fuse, Site on gen","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went d=
own because Gen failed to start  due to fuse of  gen card is faulty// He ma=
de a bridge of fuse, Site on gen","mouliom.anselme@matech-cameroun.com","56=
53","01-04-2025 15:37:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004703131","Angongo"=
,"","01-04-2025 14:55:08","01-04-2025 14:08:48","01-04-2025 14:53:32","Casc=
aded Incident from TTO4791300","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Gen failed to start due to g=
enerator cosse dirty and loosened // Generator cosse cleaned, tighten and G=
en start manually","system","287523","01-04-2025 14:55:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_310","NOCINC0004703130","Nomayos"=
,"","01-04-2025 14:55:08","01-04-2025 14:08:48","01-04-2025 14:53:32","Casc=
aded Incident from TTO4791300","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Gen failed to start due to g=
enerator cosse dirty and loosened // Generator cosse cleaned, tighten and G=
en start manually","system","287522","01-04-2025 14:55:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004703128","Mbankomo=
 IHS","","01-04-2025 14:55:08","01-04-2025 14:08:48","01-04-2025 14:53:32",=
"Cascaded Incident from TTO4791300","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Gen failed to start due=
 to generator cosse dirty and loosened // Generator cosse cleaned, tighten =
and Gen start manually","system","287523","01-04-2025 14:55:08","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004703129","Ebeba","=
","01-04-2025 14:55:08","01-04-2025 14:08:48","01-04-2025 14:53:32","Cascad=
ed Incident from TTO4791300","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Gen failed to start due to gen=
erator cosse dirty and loosened // Generator cosse cleaned, tighten and Gen=
 start manually","system","287522","01-04-2025 14:55:08","MATECH CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0004702965","OKO=
A Peage","IHS_YND_695, IHS_YND_339, IHS_YND_310, IHS_YND_335","01-04-2025 1=
4:20:56","01-04-2025 14:08:48","01-04-2025 14:53:32","Grid outage, Gen fail=
ed to start due to generator cosse dirty and loosened // Generator cosse cl=
eaned, tighten and Gen start manually","Fanda Brice","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen failed to start =
due to generator cosse dirty and loosened // Generator cosse cleaned, tight=
en and Gen start manually","cedric.tiani@matech-cameroun.com","729","01-04-=
2025 14:20:56","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004702956","N=
kolfon Cimencam","","01-04-2025 14:18:43","01-04-2025 14:10:32","01-04-2025=
 14:15:51","Active//No power issue, Site on Grid Ubai=3D 52,8V. Notice that=
 it is impacted by Afanoya II The Tx FME Fulbert from Huawei is informed","=
Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 52=
,8V. Notice that it is impacted by Afanoya II The Tx FME Fulbert from Huawe=
i is informed","cedric.tiani@matech-cameroun.com","492","01-04-2025 14:18:4=
3","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004702872","Beh=
ind P T school Yde","","01-04-2025 14:03:58","01-04-2025 13:44:46","01-04-2=
025 16:06:06","Grid outage.gen ran until fuel shortage//Refueling done","Pa=
ul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.ge=
n ran until fuel shortage//Refueling done","cedric.tiani@matech-cameroun.co=
m","1153","01-04-2025 14:03:58","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004702821","N=
kolondom","","01-04-2025 13:55:22","01-04-2025 13:52:13","01-04-2025 20:46:=
36","Grid outage, Site went down because Gen failed to start due to ATS mal=
functionning// He reset ATS and Gen manually started","Fabrice Pouakam","In=
stallation Activity","Passive","Planned Activity","Installation Activity","=
Felix Bate is on site with MTN and Huawei","cedric.tiani@matech-cameroun.co=
m","190","01-04-2025 13:55:22","MATECH CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0004702812","S=
apeur","","01-04-2025 13:53:42","01-04-2025 12:36:16","01-04-2025 13:32:53"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen st=
arted automatically","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup // Gen started automatically","kouoh.jean@ihstow=
ers.com","4648","01-04-2025 13:53:42","MATECH CMR"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0004702730","Nko=
lndom","","01-04-2025 13:42:13","01-04-2025 13:31:03","01-04-2025 13:35:25"=
,"No power issue site on grid with U=3D51.7v Sinclair(677550019) from MTN w=
as working for secure transmission","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue site on grid with U=3D51.7v Sinclair(677550019) from MTN was working =
for secure transmission","cedric.tiani@matech-cameroun.com","671","01-04-20=
25 13:42:13","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004702665","B=
iteng-Maetur","","01-04-2025 13:30:14","01-04-2025 13:27:59","01-04-2025 17=
:55:25","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the=
 load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen started and stopped due t=
o Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced th=
e load","cedric.tiani@matech-cameroun.com","136","01-04-2025 13:30:14","MAT=
ECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0004702659","N=
koa Ayos","","01-04-2025 13:28:49","01-04-2025 13:09:17","01-04-2025 13:43:=
41","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Site went down because Gen failed to start due to ATS disfuncti=
on// He reset ATS and started Gen manualy","kouoh.jean@ihstowers.com","3275=
58","01-04-2025 13:28:49","MATECH CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0004702656","K=
amajou Building","IHS_YND_085","01-04-2025 13:28:14","01-04-2025 13:09:52",=
"01-04-2025 17:36:17","No power issue site on grid wit U=3D53.7v site up at=
 05.36 PM Mbah Osiah from Huawei ","Paul BIBOUM","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 site on grid wit U=3D53.7v site up at 05.36 PM Mbah Osiah from Huawei ","k=
ouoh.jean@ihstowers.com","1103","01-04-2025 13:28:14","MATECH CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0004702654","H=
-Deputes","","01-04-2025 13:27:29","01-04-2025 13:06:53","01-04-2025 16:40:=
53","No power issue on site U=3D55v site on grid Brice stague 650214096 of =
huawei is informed,notice that disjunction of CB in BTS OCM","","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site U=3D55v site on grid Brice stague 650214096 of huaw=
ei is informed,notice that disjunction of CB in BTS OCM","kouoh.jean@ihstow=
ers.com","1237","01-04-2025 13:27:29","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0004702641","G=
SO","IHS_YND_067","01-04-2025 13:24:26","01-04-2025 13:09:17","01-04-2025 1=
3:43:41","Site went down because Gen failed to start due to ATS malfunction=
// He reset ATS and started Gen manually","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","ATS-AMF Issue","Site went down because Gen fai=
led to start due to ATS malfunction// He reset ATS and started Gen manually=
","cedric.tiani@matech-cameroun.com","910","01-04-2025 13:24:26","MATECH CM=
R"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004702623","B=
riqueterie","","01-04-2025 13:21:11","01-04-2025 13:09:52","01-04-2025 17:3=
6:17","Grid outage.no space to deploy mobile gen//Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no s=
pace to deploy mobile gen//Grid return","cedric.tiani@matech-cameroun.com",=
"7195","01-04-2025 13:21:11","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004702619","B=
itoto","","01-04-2025 13:19:25","01-04-2025 13:17:08","01-04-2025 15:02:52"=
,"Grid outage, site went down because gen failed to start due to PWC ZTE ma=
lfunction // He reset controller and gen manually started","Mba Lazare Herv=
e","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Grid outage, site went down because gen failed to start due to PWC ZTE malf=
unction // He reset controller and gen manually started","cedric.tiani@mate=
ch-cameroun.com","139","01-04-2025 13:19:25","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004702569","Ron=
d Point Express1114","","01-04-2025 13:08:45","01-04-2025 13:00:23","01-04-=
2025 13:12:24","Grid outage Site went down before Gen started due to poor b=
attery backup // Gen start automatically","Hyemafo Gildas","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage Sit=
e went down before Gen started due to poor battery backup // Gen start auto=
matically","cedric.tiani@matech-cameroun.com","502","01-04-2025 13:08:45","=
MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004702551","Cit=
e des nations","","01-04-2025 13:04:19","01-04-2025 13:00:11","01-04-2025 1=
3:58:30","Site went down due to insufficient rectifiers(02/03) Faulty on si=
te//Site stabilised","Paul BIBOUM","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to insufficient rectifiers(02/03) F=
aulty on site//Site stabilised","cedric.tiani@matech-cameroun.com","249","0=
1-04-2025 13:04:19","MATECH CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0004702534","Oss=
ombe","","01-04-2025 12:59:07","01-04-2025 12:45:01","01-04-2025 15:40:35",=
"Site went down due to disjunction of Cb(32A) Gen // He reamed Cb(32A), sit=
e on gen(investigation ongoing)","Parker Tchoup","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Load Breaker","Site went down due to disjunction of C=
b(32A) Gen // He reamed Cb(32A), site on gen(investigation ongoing)","cedri=
c.tiani@matech-cameroun.com","3008","01-04-2025 12:59:07","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004702514","N=
goulmekong-Nord","","01-04-2025 12:54:02","01-04-2025 12:51:54","01-04-2025=
 12:54:35","Grid outage, site went down due to Gen overload(12.5kva,210 A) =
IHS SS Blaise Raoul is informed and confirmed//Grid return","Siligap Boris"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, si=
te went down due to Gen overload(12.5kva,210 A) IHS SS Blaise Raoul is info=
rmed and confirmed//Grid return","cedric.tiani@matech-cameroun.com","130","=
01-04-2025 12:54:02","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004702484","ODZ=
A MINKAN EDIBI ASSI","","01-04-2025 12:46:44","01-04-2025 12:32:31","01-04-=
2025 14:37:16","Site went down due to trip of CB (125A) which powered MTN e=
quipment // He replaced by Cb(2*63A), site on grid","Albran Byorel","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issu=
e","Site went down due to trip of CB (125A) which powered MTN equipment // =
He replaced by Cb(2*63A), site on grid","cedric.tiani@matech-cameroun.com",=
"854","01-04-2025 12:46:44","MATECH CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0004702464","Djo=
nassi-Yde","","01-04-2025 12:38:58","01-04-2025 12:35:45","01-04-2025 12:36=
:59","No power issue site on grid with U=3D54.1v Symphorien(650257151) from=
 Huawei is informed ","Fabrice Pouakam","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D54.1v Symphorien(650257151) from Huawei is informed ","cedric=
.tiani@matech-cameroun.com","194","01-04-2025 12:38:58","MATECH CMR"
"Closed Complete","Site Down","CTR_011","IHS_YND_196","NOCINC0004702410","P=
DC","","01-04-2025 12:27:14","01-04-2025 12:24:43","01-04-2025 12:27:33","N=
o power issue site on grid with U=3D53.7v Eloundou Bertrand(652586578) from=
 Huawei is informed site up at 12:27 PM","Mboua Thierry","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue site on grid with U=3D53.7v Eloundou Bertrand(652586578) from Huaw=
ei is informed site up at 12:27 PM","cedric.tiani@matech-cameroun.com","152=
","01-04-2025 12:27:14","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004702279","Mon=
tee-Jouvence-II","","01-04-2025 12:05:35","01-04-2025 12:00:41","01-04-2025=
 12:05:51","Grid outage, Site went down because Gen overload (15kva, 250A) =
SS IHS Felix Zambe is informed // GRid power return","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen overload (15kva, 250A) SS IHS Felix Zambe is informed //=
 GRid power return","cedric.tiani@matech-cameroun.com","295","01-04-2025 12=
:05:35","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004702243","Mon=
tee Jouvence","","01-04-2025 12:03:51","01-04-2025 11:58:56","01-04-2025 12=
:38:01","Grid outage gen failed to start due to alarm high temp//We add wat=
er and gen manually started ","Hyemafo Gildas","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage ge=
n failed to start due to alarm high temp//We add water and gen manually sta=
rted ","cedric.tiani@matech-cameroun.com","296","01-04-2025 12:03:51","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004702242","C=
omplexe-BEAC","","01-04-2025 12:03:43","29-03-2025 19:44:41","29-03-2025 21=
:17:11","No power issue site on grid with U=3D51.7v Lionnel Steeve from Hua=
wei is informed","Albran Byorel","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wi=
th U=3D51.7v Lionnel Steeve from Huawei is informed","mouliom.anselme@matec=
h-cameroun.com","231542","01-04-2025 12:03:43","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004702241","E=
koumdoum","","01-04-2025 12:03:20","29-03-2025 13:45:48","29-03-2025 14:17:=
48","","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High=
 Engine Temp - Coolant Level Issue","Grid outage.gen start and stopped due =
to high temp alarm//We add water and gen manually started","kouoh.jean@ihst=
owers.com","253053","01-04-2025 12:03:20","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004702234","Men=
dong vallee","","01-04-2025 12:02:23","01-04-2025 11:58:59","01-04-2025 12:=
02:41","Grid outage site went down because Gen over load (20KVA; 300A) // G=
rid return IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site we=
nt down because Gen over load (20KVA; 300A) // Grid return IHS F=E9lix Zamb=
=E9 is informed and confirmed","cedric.tiani@matech-cameroun.com","205","01=
-04-2025 12:02:23","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004702232","ETO=
UDI Entree du palais","","01-04-2025 12:01:33","01-04-2025 11:52:04","01-04=
-2025 12:04:10","Grid outage, Site went down before Gen start due to poor b=
ackup // Gen started manually","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Gen started manually","cedric.tia=
ni@matech-cameroun.com","570","01-04-2025 12:01:33","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004702216","E=
koumdoum","","01-04-2025 11:57:06","29-03-2025 06:55:39","29-03-2025 10:42:=
39","","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High=
 Engine Temp - Coolant Level Issue","Grid outage.gen start and stopped due =
to high temp alarm//We add water and gen manually starte","kouoh.jean@ihsto=
wers.com","277288","01-04-2025 11:57:06","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004702188","M=
essassi okolo","","01-04-2025 11:53:31","29-03-2025 06:46:55","29-03-2025 1=
0:42:55","","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Grid outage, site went down because gen failed to start =
(Investigation ongoing) // Grid return","kouoh.jean@ihstowers.com","277596"=
,"01-04-2025 11:53:31","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004702162","E=
mana Lycee","","01-04-2025 11:46:21","27-03-2025 20:41:51","27-03-2025 20:4=
9:51","","Fabrice Pouakam","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie=
=3D50 V site on Grid ,TX FME Synphorien (691316854) from Huawei is informed=
. Notice that we have","kouoh.jean@ihstowers.com","399870","01-04-2025 11:4=
6:21","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004702130","Ole=
mbe MTN","","01-04-2025 11:36:48","01-04-2025 11:29:42","01-04-2025 11:33:0=
4","Site went down due to insufficiency of rectifiers on site // site stabi=
lized(need to add 01 rectifier)","Fabrice Pouakam","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","Site went down due to insufficiency of=
 rectifiers on site // site stabilized(need to add 01 rectifier)","cedric.t=
iani@matech-cameroun.com","427","01-04-2025 11:36:48","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004702081","O=
lembe-Terminus","","01-04-2025 11:31:07","01-04-2025 11:29:51","01-04-2025 =
11:32:19","Grid fluctuation, Site went down Gen failed to start due to Grid=
 bad voltage,// Grid return","Fabrice Pouakam","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Grid fluctuation, Site went d=
own Gen failed to start due to Grid bad voltage,// Grid return","cedric.tia=
ni@matech-cameroun.com","78","01-04-2025 11:31:07","MATECH CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004701993","Sap=
eur","","01-04-2025 11:23:46","01-04-2025 11:20:38","01-04-2025 11:28:43","=
Grid Outage, site went down before gen start due to poor battery backup // =
Gen started automatically","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid Outage, site went down bef=
ore gen start due to poor battery backup // Gen started automatically","ced=
ric.tiani@matech-cameroun.com","190","01-04-2025 11:23:46","MATECH CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004701990","Nko=
zoa","","01-04-2025 11:22:57","01-04-2025 11:20:49","01-04-2025 11:28:56","=
 Site went down Gen failed to start due to Grid bad voltage,no rcp on site/=
/ Grid return","Fabrice Pouakam","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty"," Site went down Gen failed to start due to =
Grid bad voltage,no rcp on site// Grid return","cedric.tiani@matech-camerou=
n.com","130","01-04-2025 11:22:57","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004701928","NYO=
M FACE MAETUR","","01-04-2025 11:09:49","01-04-2025 11:08:40","01-04-2025 1=
1:48:44","Grid fluctuation,Site went down because Gen failed to start due t=
o grid bad voltage(lack of 02 phases)// He did a bridge on the good phase",=
"Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation,Site went down because Gen failed to star=
t due to grid bad voltage(lack of 02 phases)// He did a bridge on the good =
phase","cedric.tiani@matech-cameroun.com","70","01-04-2025 11:09:49","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0004701850","H=
-Progres","","01-04-2025 11:00:48","01-04-2025 09:53:27","01-04-2025 14:25:=
54","Grid outage no space to deploy mobile gen//Grid return ","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy mobile gen//Grid return ","kouoh.jean@ihstowers.com","4042","=
01-04-2025 11:00:48","MATECH CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0004701842","C=
NDH","","01-04-2025 10:59:46","01-04-2025 09:53:00","08-04-2025 22:29:00","=
Traffic rerouted by OCM on Mobile BTS not power managed by IHS.","Paul BIBO=
UM","Customer Equipment Failure","Active","Active Equipment Failure","Affec=
ted by 3rd Party Site","Traffic rerouted by OCM on Mobile BTS not power man=
aged by IHS.","kouoh.jean@ihstowers.com","4006","01-04-2025 10:59:46","MATE=
CH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004701745","SOA VILL=
AGE","","01-04-2025 10:39:04","01-04-2025 10:34:26","01-04-2025 13:11:54","=
Cascaded Incident from TTO4789831","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,gen ran till fuel short=
age//Refueling done","system","286067","01-04-2025 10:39:04","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004701739","S=
OA TOWN","IHS_YND_323","01-04-2025 10:38:31","01-04-2025 10:34:26","01-04-2=
025 13:11:54","Grid outage,gen ran till fuel shortage//Refueling done","Sil=
igap Boris","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,g=
en ran till fuel shortage//Refueling done","cedric.tiani@matech-cameroun.co=
m","247","01-04-2025 10:38:31","MATECH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0004701638","O=
ssombe","","01-04-2025 10:22:05","01-04-2025 09:56:51","01-04-2025 10:00:01=
","Active //No power issue, site on Battery with Ubaie=3D50,4V, The TX FME =
Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active //No power issue, site on Battery with Ubaie=3D50,4V, The TX FME Gre=
goire (654547479) from Huawei is informed.","cedric.tiani@matech-cameroun.c=
om","1515","01-04-2025 10:22:05","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004701630","M=
essa-Carriere OCM","","01-04-2025 10:20:35","01-04-2025 09:54:07","01-04-20=
25 17:29:50","Grid outage.no space to deploy mobile gen//.grid power return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage.no space to deploy mobile gen//.grid power return","cedric.tiani@=
matech-cameroun.com","1589","01-04-2025 10:20:35","MATECH CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0004701525","B=
ATA-Mokolo","","01-04-2025 09:57:53","01-04-2025 09:54:39","01-04-2025 14:2=
8:59","Grid outage.no space to deploy mobile gen//.grid power return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge.no space to deploy mobile gen//.grid power return","cedric.tiani@matech-=
cameroun.com","195","01-04-2025 09:57:53","MATECH CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004701430","Sap=
eur","","01-04-2025 09:42:06","01-04-2025 09:41:56","01-04-2025 09:56:51","=
 Site went down Gen failed to start due to Grid bad voltage,// Grid return"=
,"Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty"," Site went down Gen failed to start due to Grid bad voltage=
,// Grid return","cedric.tiani@matech-cameroun.com","11","01-04-2025 09:42:=
06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_792","NOCINC0004701384","NKOABANG=
 NKOLO 3","","01-04-2025 09:32:14","01-04-2025 09:09:43","01-04-2025 09:29:=
20","Cascaded Incident from TTO4789390","Mba Lazare Herve","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active: no power issue, site i=
s on grid with Ubaie=3D53V, Lionel steeve(655184876) from Huawei is informe=
d","system","269709","01-04-2025 09:32:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_795","NOCINC0004701385","Lada I Y=
de","","01-04-2025 09:32:14","01-04-2025 09:09:43","01-04-2025 09:29:20","C=
ascaded Incident from TTO4789390","Mba Lazare Herve","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active: no power issue, site is on g=
rid with Ubaie=3D53V, Lionel steeve(655184876) from Huawei is informed","sy=
stem","269710","01-04-2025 09:32:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0004701386","Biteng",=
"","01-04-2025 09:32:14","01-04-2025 09:09:43","01-04-2025 09:29:20","Casca=
ded Incident from TTO4789390","Mba Lazare Herve","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active: no power issue, site is on grid =
with Ubaie=3D53V, Lionel steeve(655184876) from Huawei is informed","system=
","269708","01-04-2025 09:32:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_750","NOCINC0004701383","Nkoabang=
 entree carriere","","01-04-2025 09:32:14","01-04-2025 09:09:43","01-04-202=
5 09:29:20","Cascaded Incident from TTO4789390","Mba Lazare Herve","Cascade=
 Outage","Active","Cascade Active","Cascade Active","Active: no power issue=
, site is on grid with Ubaie=3D53V, Lionel steeve(655184876) from Huawei is=
 informed","system","269707","01-04-2025 09:32:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0004701381","Biteng-M=
aetur","","01-04-2025 09:32:13","01-04-2025 09:09:43","01-04-2025 09:29:20"=
,"Cascaded Incident from TTO4789390","Mba Lazare Herve","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active: no power issue, site is o=
n grid with Ubaie=3D53V, Lionel steeve(655184876) from Huawei is informed",=
"system","269708","01-04-2025 09:32:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0004701382","Nkoabang=
2","","01-04-2025 09:32:13","01-04-2025 09:09:43","01-04-2025 09:29:20","Ca=
scaded Incident from TTO4789390","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active: no power issue, site is on gr=
id with Ubaie=3D53V, Lionel steeve(655184876) from Huawei is informed","sys=
tem","269707","01-04-2025 09:32:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004701380","Bitoto",=
"","01-04-2025 09:32:13","01-04-2025 09:09:43","01-04-2025 09:29:20","Casca=
ded Incident from TTO4789390","Mba Lazare Herve","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active: no power issue, site is on grid =
with Ubaie=3D53V, Lionel steeve(655184876) from Huawei is informed","system=
","269709","01-04-2025 09:32:13","MATECH CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004701356","Nko=
abang MTN","IHS_YND_292, IHS_YND_249, IHS_YND_526, IHS_YND_750, IHS_YND_792=
, IHS_YND_795, IHS_YND_248","01-04-2025 09:23:54","01-04-2025 09:09:43","01=
-04-2025 11:04:27","Active: no power issue, site is on grid with Ubaie=3D53=
V, Lionel steeve(655184876) from Huawei is informed","Mba Lazare Herve","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active: no power issue, site is on grid with Ubaie=3D53V, Lionel s=
teeve(655184876) from Huawei is informed","cedric.tiani@matech-cameroun.com=
","852","01-04-2025 09:23:54","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004701339","M=
arche Odza","","01-04-2025 09:17:09","29-03-2025 19:46:47","29-03-2025 20:0=
4:47","Grid outage.site went down due to gen failed to start//Grid return(i=
nvestigation ongoing)","Albran Byorel","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage.site went down due to gen failed to=
 start//Grid return(investigation ongoing)","kouoh.jean@ihstowers.com","221=
424","01-04-2025 09:17:09","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0004701265","A=
battoir","","01-04-2025 08:59:00","30-03-2025 15:29:15","30-03-2025 18:01:3=
1","Grid outage .gen failed to start due alarm high temp//We add water and =
gen manually started","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage .gen fail=
ed to start due alarm high temp//We add water and gen manually started","ko=
uoh.jean@ihstowers.com","149386","01-04-2025 08:59:00","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004701112","Man=
guiers Dispensaire","","01-04-2025 08:12:09","01-04-2025 08:10:01","01-04-2=
025 08:55:25","Site went down due to  03/04 rectifiers dysfunction //he res=
et it","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to  03/04 rectifiers dysfunction //he reset i=
t","cedric.tiani@matech-cameroun.com","129","01-04-2025 08:12:09","MATECH C=
MR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004701103","Cit=
e des nations","","01-04-2025 08:10:21","01-04-2025 08:02:13","01-04-2025 1=
0:27:19","Site went down due to insufficient rectifiers(02/03) Faulty on si=
te//Site stabilised	","Paul BIBOUM","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down due to insufficient rectifiers(02/03) =
Faulty on site//Site stabilised	","cedric.tiani@matech-cameroun.com","489",=
"01-04-2025 08:10:21","MATECH CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004701096","Ron=
d Point Express1114","","01-04-2025 08:08:29","01-04-2025 08:03:17","01-04-=
2025 08:56:36","Grid outage Site went down before Gen started due to poor b=
attery backup // Gen start automatically","Hyemafo Gildas","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage Sit=
e went down before Gen started due to poor battery backup // Gen start auto=
matically","cedric.tiani@matech-cameroun.com","312","01-04-2025 08:08:29","=
MATECH CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0004701093","B=
astos-BAT","","01-04-2025 08:07:11","01-04-2025 08:02:01","01-04-2025 08:50=
:44","Grid fluctuation,Site went down due to Grid bad voltage//Grid return"=
,"Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Grid Outag=
e Issue","Grid fluctuation,Site went down due to Grid bad voltage//Grid ret=
urn","cedric.tiani@matech-cameroun.com","312","01-04-2025 08:07:11","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004701045","S=
hell-Nsimeyong","","01-04-2025 07:53:31","01-04-2025 07:49:21","01-04-2025 =
09:53:14","Active//No power issue on site ,site on Grid, Ubaie=3D51V The Tx=
 Technician Huawei Hosiah//674007438 is informed","MINKA NICOLAS","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site ,site on Grid, Ubaie=3D51V The Tx Technic=
ian Huawei Hosiah//674007438 is informed","cedric.tiani@matech-cameroun.com=
","251","01-04-2025 07:53:31","MATECH CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0004700971","CLE=
 Building","","01-04-2025 07:36:33","01-04-2025 07:31:52","01-04-2025 09:32=
:16","Grid outage,no space to deploy MDG //Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage,no space to=
 deploy MDG //Grid return","edwige.kapawo@matech-cameroun.com","282","01-04=
-2025 07:36:33","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004700888","F=
ouda-New","","01-04-2025 07:13:08","01-04-2025 07:06:46","01-04-2025 08:42:=
19","Site went down due to MPR  dysfunction// He reset the MPR","Delor Tele=
zing","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","Site we=
nt down due to MPR  dysfunction// He reset the MPR","edwige.kapawo@matech-c=
ameroun.com","383","01-04-2025 07:13:08","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004700842","Pha=
rmacie Bleue","","01-04-2025 06:59:51","01-04-2025 06:58:37","01-04-2025 07=
:22:15","Site went down Gen failed to start due to Grid bad voltage,no rcp =
on site// Grid return","Siligap Boris","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","Site went down Gen failed to start du=
e to Grid bad voltage,no rcp on site// Grid return","edwige.kapawo@matech-c=
ameroun.com","75","01-04-2025 06:59:51","MATECH CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004700835","Sap=
eur","","01-04-2025 06:58:49","01-04-2025 06:57:24","01-04-2025 07:14:56","=
Grid outage, Site went down before Gen start due to poor backup // Gen star=
ted Manually","Mboua Thierry","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup // Gen started Manually","edwige.kapawo@matech-cameroun=
.com","86","01-04-2025 06:58:49","MATECH CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004700822","BAT=
A Mokolo OCM","","01-04-2025 06:53:03","01-04-2025 06:51:46","01-04-2025 16=
:47:49","Grid outage.no space to deploy mobile gen//Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no=
 space to deploy mobile gen//Grid return","edwige.kapawo@matech-cameroun.co=
m","78","01-04-2025 06:53:03","MATECH CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004700811","AKA=
K Nkozoa","","01-04-2025 06:50:00","01-04-2025 06:03:37","03-04-2025 14:49:=
08","Access issue due to landlord//Grid outage, site went down due to refus=
al from landlord to start gen//WE start manually gen according to approval =
of landlord","Fabrice Pouakam","Access Denial","Lease Or Legal","Landlord R=
elated Issues","Access Issue - Land Lord","Access issue due to landlord//Gr=
id outage, site went down due to refusal from landlord to start gen//WE sta=
rt manually gen according to approval of landlord","landry.etame@ihstowers.=
com","2784","01-04-2025 06:50:00","MATECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004700772","HOP=
ITAL GENERAL RAIL YDE","","01-04-2025 06:40:58","01-04-2025 06:39:44","01-0=
4-2025 08:22:46","Grid outage, site went down due to gen Overload(09kva,160=
A), Bernard IHS is informed // Grid return","Delor Telezing","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down du=
e to gen Overload(09kva,160A), Bernard IHS is informed // Grid return","ger=
ard.tchangoue@matech-cameroun.com","75","01-04-2025 06:40:58","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004700770","E=
koumdoum OCM","","01-04-2025 06:40:28","01-04-2025 06:34:15","01-04-2025 16=
:34:38","Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline i=
s informed and confirmed//site  stabilised","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Site went down due to Gen overl=
oad(20kva,280 A) IHS SS Pascaline is informed and confirmed//site  stabilis=
ed","edwige.kapawo@matech-cameroun.com","374","01-04-2025 06:40:28","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004700765","C=
omplexe-BEAC","","01-04-2025 06:38:26","01-04-2025 05:45:07","01-04-2025 06=
:00:55","Active //No power issue on site ,site on Grid with U=3D54v The Tx =
FME Lionnel// 655184876 from Huawei is informed(two circuit breakers faulty=
 at the BTS OCMTELIS is informed)","Albran Byorel","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //No =
power issue on site ,site on Grid with U=3D54v The Tx FME Lionnel// 6551848=
76 from Huawei is informed(two circuit breakers faulty at the BTS OCMTELIS =
is informed)","edwige.kapawo@matech-cameroun.com","3200","01-04-2025 06:38:=
26","MATECH CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004700584","Fla=
menco","","01-04-2025 05:35:43","01-04-2025 05:25:37","01-04-2025 05:47:04"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen st=
arted Manually","Mboua Thierry","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup // Gen started Manually","rouselle.schoune@ihstowers.=
com","607","01-04-2025 05:35:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0004700534","Nkoa Ayo=
s","","01-04-2025 05:15:15","31-03-2025 23:15:22","01-04-2025 07:51:13","Ca=
scaded Incident from TTO4787753","MINKA NICOLAS","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down because G=
en failed to start due to ATS disfunction// He reset ATS and started Gen ma=
nualy","system","298061","01-04-2025 05:15:15","MATECH CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004700521","Mes=
sa Carriere","","01-04-2025 05:11:37","01-04-2025 05:01:50","01-04-2025 05:=
41:44","Grid outage site went down because Gen failed to start due to Gen c=
ard faulty // Gen Manually Started","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage site went down because=
 Gen failed to start due to Gen card faulty // Gen Manually Started","rouse=
lle.schoune@ihstowers.com","588","01-04-2025 05:11:37","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004700517","OBA=
M NGOLA OCM","","01-04-2025 05:10:49","01-04-2025 05:01:41","01-04-2025 07:=
39:38","Grid outage,gen ran till fuel shortage//Refueling done","MINKA NICO=
LAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran =
till fuel shortage//Refueling done","rouselle.schoune@ihstowers.com","549",=
"01-04-2025 05:10:49","MATECH CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004700480","Sap=
eur","","01-04-2025 04:53:26","01-04-2025 04:48:11","01-04-2025 04:56:44","=
Site went Down due to poor backup // Gen started automatically","Mboua Thie=
rry","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Site went Down due to poor backup // Gen started automatically","rous=
elle.schoune@ihstowers.com","316","01-04-2025 04:53:26","MATECH CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004700466","Ako=
k Ndoe Yde","","01-04-2025 04:49:43","01-04-2025 04:44:37","01-04-2025 05:3=
8:39","Grid outage site went down before Gen stated due to poor battery bac=
kyup // Grid power return","Hyemafo Gildas","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage site went down bef=
ore Gen stated due to poor battery backyup // Grid power return","rouselle.=
schoune@ihstowers.com","307","01-04-2025 04:49:43","MATECH CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004700461","CRH=
-Etoug-Ebe","","01-04-2025 04:48:59","01-04-2025 04:41:52","01-04-2025 04:5=
5:41","Eneo outage,sitedown due to poor backup // Grid return","Hyemafo Gil=
das","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Eneo outage,sitedown due to poor backup // Grid return","rouselle.sch=
oune@ihstowers.com","428","01-04-2025 04:48:59","MATECH CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004700458","Beh=
ind P T school Yde","","01-04-2025 04:47:39","01-04-2025 04:40:33","01-04-2=
025 06:45:06","Acces issue due to landlord  Grid outage site went down due =
to no automatisme on site //Gen manually started","Paul BIBOUM","Access Den=
ial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord",=
"Grid outage site went down due to no automatisme on site //Gen manually st=
arted","rouselle.schoune@ihstowers.com","427","01-04-2025 04:47:39","MATECH=
 CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004700392","UPA=
C LP","","01-04-2025 04:03:14","01-04-2025 04:00:07","01-04-2025 04:40:03",=
"Grid outage no space to deploy mobile gen//Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space t=
o deploy mobile gen//Grid return","rouselle.schoune@ihstowers.com","188","0=
1-04-2025 04:03:14","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004700316","C=
omplexe-BEAC","","01-04-2025 03:31:49","31-03-2025 18:27:12","31-03-2025 21=
:04:03","Eneo fluctuations, site down due to Disjonction of the OCM CB //Si=
te on GEN and CB rearmed","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","BTS Breaker Tripped","Eneo fluctuations, site down due to Disj=
onction of the OCM CB //Site on GEN and CB rearmed","stephane.nkamwa@ihstow=
ers.com","32678","01-04-2025 03:31:49","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004700312","N=
koabang Ebolmedjock","","01-04-2025 03:30:29","31-03-2025 21:13:02","31-03-=
2025 22:03:30","Grid outage site went down due to gen failed to start//Grid=
 return(investigation ongoing)","Mba Lazare Herve","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage site went down due to g=
en failed to start//Grid return(investigation ongoing)","stephane.nkamwa@ih=
stowers.com","22648","01-04-2025 03:30:29","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004700149","Man=
guiers Dispensaire","","01-04-2025 01:57:01","01-04-2025 01:55:41","01-04-2=
025 03:16:47","site down due to rectifiers issue // rectifier reset ","Fabr=
ice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","s=
ite down due to rectifiers crashed // rectifier reset ","rouselle.schoune@i=
hstowers.com","80","01-04-2025 01:57:01","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004700056","ETO=
UDI Entree du palais","","01-04-2025 01:18:24","01-04-2025 01:14:19","01-04=
-2025 01:42:16","Grid outage, site went down because gen start and stopped =
with over voltage alarm // He reset it and manually start the gen","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, site went down because gen start and stopped with over voltage =
alarm // He reset it and manually start the gen","rouselle.schoune@ihstower=
s.com","246","01-04-2025 01:18:24","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004700051","Pha=
rmacie Bleue","","01-04-2025 01:13:08","01-04-2025 01:03:06","01-04-2025 01=
:30:29","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, Site went down because Gen overload //Grid Res=
tored","rouselle.schoune@ihstowers.com","270005","01-04-2025 01:13:08","MAT=
ECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004700036","HOP=
ITAL GENERAL RAIL YDE","IHS_YND_210","01-04-2025 01:04:12","01-04-2025 01:0=
3:06","01-04-2025 01:30:29","Grid outage, Site went down because Gen overlo=
ad //Grid Restored","Delor Telezing","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid outage, Site went down because Gen overload //Gri=
d Restored","rouselle.schoune@ihstowers.com","66","01-04-2025 01:04:12","MA=
TECH CMR"
"Closed Complete","Site Down","T3170","IHS_YND_066","NOCINC0004699964","GSO=
","IHS_YND_067","01-04-2025 00:23:28","31-03-2025 23:15:22","01-04-2025 07:=
51:41","Access issue at Night Grid outage, Site went down because Gen faile=
d to start due to ATS disfunction// He reset ATS and started Gen manualy","=
MINKA NICOLAS","Access Denial","Lease Or Legal","Landlord Related Issues","=
Access Issue - Land Lord","Grid outage, Site went down because Gen failed t=
o start due to ATS disfunction// He reset ATS and started Gen manualy","rou=
selle.schoune@ihstowers.com","4087","01-04-2025 00:23:28","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004699961","Mon=
tee Jouvence","","01-04-2025 00:22:08","31-03-2025 23:22:01","01-04-2025 00=
:24:48","Eneo fluctuation, Gen failed to start due to poor backup // Grid r=
estauration","Hyemafo Gildas","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Eneo fluctuation, Gen failed to start due to=
 poor backup // Grid restauration","rouselle.schoune@ihstowers.com","3608",=
"01-04-2025 00:22:08","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004699565","B=
iteng-Maetur","","31-03-2025 22:24:06","31-03-2025 17:14:59","31-03-2025 18=
:38:46","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the=
 load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen started and stopped due t=
o Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced th=
e load","ludivine.ngamaleu@ihstowers.com","18548","31-03-2025 22:24:06","MA=
TECH CMR"
"Closed Complete","Site Down","T1411","IHS_YND_543","NOCINC0004699448","Ent=
ree Cite Verte","","31-03-2025 21:59:41","31-03-2025 21:34:35","31-03-2025 =
23:32:52","Grid outage site went down due to gen failed to start //Grid ret=
urn(investigation ongoing)","Paul BIBOUM","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage site went down due to gen failed=
 to start //Grid return(investigation ongoing)","olivier.kwedi@ihstowers.co=
m","1507","31-03-2025 21:59:41","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004699192","Aka=
k-Nkozoa-MTN-IHS","","31-03-2025 21:15:58","31-03-2025 20:36:35","31-03-202=
5 21:36:22","Grid outage, Site went down because Gen failed to start with "=
"overcurrent"" alarm// He reset Gen card and started Gen manually","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, Site went down because Gen failed to start with ""overcurrent""=
 alarm// He reset Gen card and started Gen manually","olivier.kwedi@ihstowe=
rs.com","2364","31-03-2025 21:15:58","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004698997","E=
mana Lycee","","31-03-2025 20:42:57","31-03-2025 20:32:59","31-03-2025 21:0=
8:45","Active//No power issue on site Ubaie=3D50 V site on Grid ,TX FME Syn=
phorien (691316854) from Huawei is informed. Notice that we have","Fabrice =
Pouakam","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active//No power issue on site Ubaie=3D50 V site on Gr=
id ,TX FME Synphorien (691316854) from Huawei is informed. Notice that we h=
ave","ludivine.ngamaleu@ihstowers.com","599","31-03-2025 20:42:57","MATECH =
CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004698823","AKA=
K Nkozoa","","31-03-2025 20:11:34","31-03-2025 19:42:25","31-03-2025 22:24:=
52","Grid outage, site went down gen start and stopped with alarm over curr=
ent // He reset gen card and gen manually","Fabrice Pouakam","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went do=
wn gen start and stopped with alarm over current // He reset gen card and g=
en manually","olivier.kwedi@ihstowers.com","1749","31-03-2025 20:11:34","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004698661","Ngouetou=
","","31-03-2025 19:45:14","31-03-2025 19:21:47","31-03-2025 19:36:49","Cas=
caded Incident from TTO4786154","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site up without intervention , site im=
pacted by Ntui T187 wich is not manage by IHS","system","276146","31-03-202=
5 19:45:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004698663","Yoko MTN=
","","31-03-2025 19:45:14","31-03-2025 19:21:47","31-03-2025 19:36:49","Cas=
caded Incident from TTO4786154","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site up without intervention , site im=
pacted by Ntui T187 wich is not manage by IHS","system","276148","31-03-202=
5 19:45:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004698660","Ngoum","=
","31-03-2025 19:45:14","31-03-2025 19:21:47","31-03-2025 19:36:49","Cascad=
ed Incident from TTO4786154","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site up without intervention , site impac=
ted by Ntui T187 wich is not manage by IHS","system","276146","31-03-2025 1=
9:45:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004698662","Donga","=
","31-03-2025 19:45:14","31-03-2025 19:21:47","31-03-2025 19:36:49","Cascad=
ed Incident from TTO4786154","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site up without intervention , site impac=
ted by Ntui T187 wich is not manage by IHS","system","276148","31-03-2025 1=
9:45:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0004698657","Nguila",=
"","31-03-2025 19:45:13","31-03-2025 19:21:47","31-03-2025 19:36:49","Casca=
ded Incident from TTO4786154","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site up without intervention , site impa=
cted by Ntui T187 wich is not manage by IHS","system","276146","31-03-2025 =
19:45:13","MATECH CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0004698612","O=
ssombe","IHS_YND_433, IHS_LMB_003, IHS_YND_392, IHS_YND_475, IHS_YND_454, I=
HS_YND_434, IHS_YND_473, IHS_YND_585, IHS_YND_782","31-03-2025 19:32:02","3=
1-03-2025 19:21:47","31-03-2025 20:50:53","Site up without intervention , s=
ite impacted by Ntui T187 wich is not manage by IHS","Parker Tchoup","3RD P=
arty Power Failure","Passive","Power Provided By 3RD Party","Power Provided=
 By 3RD Party","Site up without intervention , site impacted by Ntui T187 w=
ich is not manage by IHS","ludivine.ngamaleu@ihstowers.com","616","31-03-20=
25 19:32:02","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004698342","Mon=
tee Jouvence","","31-03-2025 18:37:49","31-03-2025 18:10:44","31-03-2025 20=
:00:23","Eneo fluctuations, Site went Down due to grid contactor not excite=
d // He excited Grid contactor","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","ATS-AMF Issue","Eneo fluctuations, Site went Down due t=
o grid contactor not excited // He excited Grid contactor","olivier.kwedi@i=
hstowers.com","1626","31-03-2025 18:37:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004698133","SOA VILL=
AGE","","31-03-2025 17:59:05","31-03-2025 16:31:36","31-03-2025 19:39:44","=
Cascaded Incident from TTO4785466","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // He added water and manually =
start the gen","system","300675","31-03-2025 17:59:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_321","NOCINC0004698118","Soa","",=
"31-03-2025 17:57:31","31-03-2025 17:44:30","31-03-2025 18:41:02","Cascaded=
 Incident from TTO4785557","Siligap Boris","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage ,gen fail to start due to an un=
dervoltage alarm/ Grid otage","system","1224107","31-03-2025 17:57:31","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_317","NOCINC0004698119","Soa-Sofa=
mac","","31-03-2025 17:57:31","31-03-2025 17:44:30","31-03-2025 18:41:02","=
Cascaded Incident from TTO4785557","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage ,gen fail to start due =
to an undervoltage alarm/ Grid otage","system","1224106","31-03-2025 17:57:=
31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004698121","SOA UNIV=
ERSITY STADIUM","","31-03-2025 17:57:31","31-03-2025 17:44:30","31-03-2025 =
18:41:02","Cascaded Incident from TTO4785557","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage ,gen fail to=
 start due to an undervoltage alarm/ Grid otage","system","1224107","31-03-=
2025 17:57:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004698120","Akak-Nko=
zoa-MTN-IHS","","31-03-2025 17:57:31","31-03-2025 17:44:30","31-03-2025 18:=
41:02","Cascaded Incident from TTO4785557","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage ,gen fail to =
start due to an undervoltage alarm/ Grid otage","system","1224106","31-03-2=
025 17:57:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0004698117","NYOM 2 I=
HS","","31-03-2025 17:57:30","31-03-2025 17:44:30","31-03-2025 18:41:02","C=
ascaded Incident from TTO4785557","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage ,gen fail to start due=
 to an undervoltage alarm/ Grid otage","system","1224105","31-03-2025 17:57=
:30","MATECH CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0004698085","S=
OA 2","IHS_YND_703, IHS_YND_707, IHS_YND_321, IHS_YND_317, IHS_YND_390, IHS=
_YND_552, IHS_YND_316, IHS_YND_351, IHS_YND_720, IHS_YND_324","31-03-2025 1=
7:50:41","31-03-2025 17:44:30","31-03-2025 18:41:02","Grid outage ,gen fail=
 to start due to an undervoltage alarm/ Grid otage","Siligap Boris","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,gen f=
ail to start due to an undervoltage alarm/ Grid otage","ludivine.ngamaleu@i=
hstowers.com","372","31-03-2025 17:50:41","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004698016","N=
kozoa","","31-03-2025 17:41:40","31-03-2025 17:36:28","31-03-2025 18:56:46"=
,"Grid outage, site went down due to gen overload (20kva, 340A) // He reduc=
ed the load and site on GEN","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen overl=
oad (20kva, 340A) // He reduced the load and site on GENGrid outage, site w=
ent down due to gen overload (20kva, 340A) // He reduced the load and site =
on GEN","ludivine.ngamaleu@ihstowers.com","313","31-03-2025 17:41:40","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004698002","S=
OA TOWN","IHS_YND_323","31-03-2025 17:39:47","31-03-2025 16:31:36","31-03-2=
025 19:39:47","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // He added water and manually start the gen","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Co=
olant Level Issue","Grid outage, site went down because gen start and stopp=
ed with high temp alarm // He added water and manually start the gen","ludi=
vine.ngamaleu@ihstowers.com","4093","31-03-2025 17:39:47","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004697947","N=
goulmekong-Nord","","31-03-2025 17:28:10","31-03-2025 17:16:03","31-03-2025=
 18:37:50","Grid Outage, Site went Down due to Gen Overload // Grid restaur=
ation","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid Outage, Site went Down due to Gen Overload // Grid restauration=
","ludivine.ngamaleu@ihstowers.com","728","31-03-2025 17:28:10","MATECH CMR=
"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0004697937","E=
bogo","","31-03-2025 17:25:56","31-03-2025 17:16:51","31-03-2025 19:14:12",=
"Grid outage, Site went down before Gen start due to poor backup // Gen sta=
rted automatically","Siligap Boris","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen started automatically","ludivine.ngamaleu@=
ihstowers.com","547","31-03-2025 17:25:56","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004697908","B=
itoto","","31-03-2025 17:21:58","31-03-2025 17:08:46","31-03-2025 18:21:26"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen st=
art automatically","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Gen start automatically","ludivine.ngamaleu@=
ihstowers.com","793","31-03-2025 17:21:58","MATECH CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0004697897","A=
RMP","","31-03-2025 17:20:03","29-03-2025 15:05:06","29-03-2025 17:14:44","=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id Outage //Grid return","kouoh.jean@ihstowers.com","180897","31-03-2025 17=
:20:03","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004697876","N=
kolbong","","31-03-2025 17:16:08","29-03-2025 10:41:08","29-03-2025 10:56:0=
8","","Delor Telezing","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage, site went down before gen start due to=
 poor battery backup // Gen Started automatically","kouoh.jean@ihstowers.co=
m","196501","31-03-2025 17:16:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004697846","Manguier=
","","31-03-2025 17:11:26","29-03-2025 06:56:12","29-03-2025 10:41:12","Cas=
caded Incident from TTO4785267","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to g=
en overload (22kva, 340A) S// He reduced the load","system","507967","31-03=
-2025 17:11:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004697845","Omnispor=
t-Rail","","31-03-2025 17:11:26","29-03-2025 06:56:12","29-03-2025 10:41:12=
","Cascaded Incident from TTO4785267","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen overload (22kva, 340A) S// He reduced the load","system","507967","=
31-03-2025 17:11:26","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004697839","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","31-03-2025 17:10:08","29-03-=
2025 06:56:12","29-03-2025 10:41:12","Grid outage, site went down due to ge=
n overload (22kva, 340A) S// He reduced the load","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went =
down due to gen overload (22kva, 340A) S// He reduced the load","kouoh.jean=
@ihstowers.com","209637","31-03-2025 17:10:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004697801","Emana Ly=
cee","","31-03-2025 17:03:31","29-03-2025 06:49:28","29-03-2025 09:41:28","=
Cascaded Incident from TTO4785219","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation, site went down =
because Gen failed to start due to grid bad voltage and no Rcp // He bypass=
ed Grid and started Gen manually","system","472274","31-03-2025 17:03:31","=
MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004697796","E=
mana lycee 2","IHS_YND_274","31-03-2025 17:02:53","29-03-2025 06:49:28","29=
-03-2025 09:41:28","","Fabrice Pouakam","Grid Supply","Passive","Grid","Nat=
ional Grid - Low Current Supply","Grid fluctuation, site went down because =
Gen failed to start due to grid bad voltage and no Rcp // He bypassed Grid =
and started Gen manually","kouoh.jean@ihstowers.com","209605","31-03-2025 1=
7:02:53","MATECH CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004697751","B=
astos Bir","","31-03-2025 16:56:10","28-03-2025 11:57:02","28-03-2025 14:17=
:12","","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Hig=
h Engine Temp - Coolant Level Issue","Grid outage,gen start and  stopped wi=
th alarm high temp//he added water in radiator","kouoh.jean@ihstowers.com",=
"277148","31-03-2025 16:56:10","MATECH CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0004697668","M=
VAN SACEL","","31-03-2025 16:42:41","27-03-2025 23:25:10","28-03-2025 02:33=
:52","","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down due to insufficiency of rectifiers on site SS IHS =
Pascaline is confirm // Grid return","kouoh.jean@ihstowers.com","321451","3=
1-03-2025 16:42:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004697618","SAA Entr=
ance","","31-03-2025 16:33:16","31-03-2025 15:43:21","31-03-2025 16:21:00",=
"Cascaded Incident from TTO4785004","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because rectifier d=
isfunctionning // He reset it: Site on grid","system","303410","31-03-2025 =
16:33:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_190","NOCINC0004697579","Ngousso-=
II","","31-03-2025 16:25:40","31-03-2025 15:59:53","31-03-2025 19:58:53","C=
ascaded Incident from TTO4784923","MFOUAGUEGUE MATHIEU","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on grid with =
U=3D517v Symphorien from Huawei is informed","system","417942","31-03-2025 =
16:25:40","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004697545","N=
kolbong","","31-03-2025 16:18:02","28-03-2025 09:37:55","28-03-2025 13:51:1=
6","","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid outage, Site went down because , Gen failed to start due G=
en card dysfunction// He reset Gen card and started Gen manually ","kouoh.j=
ean@ihstowers.com","283207","31-03-2025 16:18:02","MATECH CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0004697534","N=
kolmesseng","IHS_YND_190","31-03-2025 16:16:08","31-03-2025 15:59:53","31-0=
3-2025 19:58:53","No power issue site on grid with U=3D54.1v site up at 07:=
58 PM ","Siligap Boris","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D54=
.1v site up at 07:58 PM ","ludivine.ngamaleu@ihstowers.com","975","31-03-20=
25 16:16:08","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004697457","N=
kolbong","","31-03-2025 16:03:54","28-03-2025 19:31:41","28-03-2025 19:46:4=
1","","Delor Telezing","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage, site went down before gen start due to=
 poor battery backup // Gen Started automatically","kouoh.jean@ihstowers.co=
m","246734","31-03-2025 16:03:54","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004697446","NTU=
I TOWN","","31-03-2025 16:02:15","31-03-2025 15:29:03","31-03-2025 16:08:31=
","Grid outage.gen ran until fuel shortage//Refueling done","Parker Tchoup"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unti=
l fuel shortage//Refueling done","olivier.kwedi@ihstowers.com","1993","31-0=
3-2025 16:02:15","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004697344","S=
AA 2","IHS_YND_542","31-03-2025 15:47:33","31-03-2025 15:43:21","31-03-2025=
 16:24:30","Site went down because rectifier disfunctionning // He reset it=
: Site on grid","Parker Tchoup","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down because rectifier disfunctionning // He re=
set it: Site on grid","ludivine.ngamaleu@ihstowers.com","253","31-03-2025 1=
5:47:33","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004697222","N=
kolbong","","31-03-2025 15:28:04","28-03-2025 14:13:17","28-03-2025 14:28:1=
7","","Delor Telezing","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage, site went down before gen start due to=
 poor battery backup // Gen Started automatically","kouoh.jean@ihstowers.co=
m","263687","31-03-2025 15:28:04","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004697156","N=
kolbong","","31-03-2025 15:18:31","27-03-2025 22:29:00","28-03-2025 08:45:1=
6","","Delor Telezing","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage, site went down before gen start due to=
 poor battery backup // Gen started automatically. OCM CB went down","kouoh=
.jean@ihstowers.com","319771","31-03-2025 15:18:31","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004697051","Eko=
mbitie","","31-03-2025 15:06:03","31-03-2025 14:51:43","31-03-2025 15:47:47=
","Site went Down due to CB Disjoction in the power bay  / CB rearmed","Fab=
rice Pouakam","Equipment Repair","Passive","Control Panel","Circuit Breaker=
 Tripped","Grid gen site , CB Disjoction in the power bay  / CB rearmed","o=
livier.kwedi@ihstowers.com","861","31-03-2025 15:06:03","MATECH CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004697007","N=
goulmekong-Nord","","31-03-2025 14:56:39","27-03-2025 13:59:16","27-03-2025=
 17:27:16","","Siligap Boris","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down due to insufficience of rectifers (05) due t=
o load increase Blaise Raoul confirmed// He reduiced load","kouoh.jean@ihst=
owers.com","349043","31-03-2025 14:56:39","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004696833","M=
essassi 2","","31-03-2025 14:34:17","31-03-2025 14:30:06","31-03-2025 14:35=
:55","Site went down due to insufficience of rectifier// He reduiced load",=
"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficience of rectifier// He reduiced load","l=
udivine.ngamaleu@ihstowers.com","253","31-03-2025 14:34:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_159","NOCINC0004696704","Complexe=
-BEAC","","31-03-2025 14:14:48","27-03-2025 08:29:01","27-03-2025 15:51:01"=
,"","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid =
outage,gen ran till fuel shortage//Refueling done","kouoh.jean@ihstowers.co=
m","366347","31-03-2025 14:14:48","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004696602","N=
kozoa","","31-03-2025 13:56:52","27-03-2025 10:19:56","27-03-2025 13:15:38"=
,"","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Grid outage, site went down due to gen overload (20kva, 340A) SS HIS =
Felix bateu is informed and confirmed// grid return","kouoh.jean@ihstowers.=
com","358616","31-03-2025 13:56:52","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004696487","Angongo"=
,"","31-03-2025 13:46:10","27-03-2025 09:53:34","27-03-2025 14:15:34","Casc=
aded Incident from TTO4783760","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site was on Gen due to Grid outage, Site =
went down because Gen stopped with ""High temp ""alarm // He added water an=
d manually start the Gen","system","619865","31-03-2025 13:46:10","MATECH C=
MR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004696480","E=
beba","IHS_YND_335","31-03-2025 13:45:39","27-03-2025 09:53:34","27-03-2025=
 14:15:34","","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG -=
 High Engine Temp - Coolant Level Issue","Site was on Gen due to Grid outag=
e, Site went down because Gen stopped with ""High temp ""alarm // He added =
water and manually start the Gen","kouoh.jean@ihstowers.com","359525","31-0=
3-2025 13:45:39","MATECH CMR"
"Closed Complete","Site Down","CTR_115","IHS_YND_375","NOCINC0004696404","N=
goung","","31-03-2025 13:35:46","27-03-2025 09:05:54","27-03-2025 11:40:54"=
,"","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - Gener=
ator Battery","Grid outage gen failed to start due to battery GE discharged=
 //Gen manually started with external battery","kouoh.jean@ihstowers.com","=
361792","31-03-2025 13:35:46","MATECH CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004696305","N=
kolfon Cimencam","","31-03-2025 13:17:41","31-03-2025 13:04:38","31-03-2025=
 13:49:04","Site impacted by Afanoyoa CTR_463","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","Affected by 3rd Part=
y Site","Sitebimpacted by Afanoyoa CTR_463
","alexandre.kamal@ihstowers.com","784","31-03-2025 13:17:41","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004696268","Manguier=
","","31-03-2025 13:10:25","27-03-2025 18:19:36","27-03-2025 23:25:36","Cas=
caded Incident from TTO4783515","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","GGrid outage, Site went down because=
 Gen overload IHS Bernard Atangana is informed //Grid Restored","system","5=
89371","31-03-2025 13:10:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004696267","Omnispor=
t-Rail","","31-03-2025 13:10:24","27-03-2025 18:19:36","27-03-2025 23:25:36=
","Cascaded Incident from TTO4783515","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","GGrid outage, Site went down be=
cause Gen overload IHS Bernard Atangana is informed //Grid Restored","syste=
m","589371","31-03-2025 13:10:24","MATECH CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004696262","M=
ANGUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","31-03-2025 13:09:33","27-03-=
2025 18:19:36","27-03-2025 23:25:36","","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","GGrid outage, Site went down beca=
use Gen overload IHS Bernard Atangana is informed //Grid Restored","kouoh.j=
ean@ihstowers.com","326997","31-03-2025 13:09:33","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004696147","A=
WAE OCM","","31-03-2025 12:44:43","31-03-2025 12:37:34","31-03-2025 12:44:3=
4","Grid outage, Site went down because Gen failed to start due to PWC dysf=
unctionning// He reset PWC, Site on Grid","Mba Lazare Herve","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, Site=
 went down because Gen failed to start due to PWC dysfunctionning// He rese=
t PWC, Site on Grid","alexandre.kamal@ihstowers.com","430","31-03-2025 12:4=
4:43","MATECH CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0004696138","G=
SO","","31-03-2025 12:42:50","31-03-2025 12:34:47","31-03-2025 14:52:47","e=
neo outage, ATS  failed to send boot order // ATS bypass mode, site on Gen"=
,"MINKA NICOLAS","Equipment Repair","Passive","Control Panel","ATS-AMF Issu=
e","eneo outage, ATS  failed to send boot order // ATS bypass mode, site on=
 Gen","alexandre.kamal@ihstowers.com","484","31-03-2025 12:42:50","MATECH C=
MR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0004696054","C=
arrefourt Nkomo","","31-03-2025 12:36:56","27-03-2025 03:05:56","27-03-2025=
 03:06:59","","Mba Lazare Herve","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubay: 5=
3.4V site Grid, Lionel Adjex (655184876/Huawei) is informed","kouoh.jean@ih=
stowers.com","379860","31-03-2025 12:36:56","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004695976","N=
KOLMEKONG YDE","","31-03-2025 12:25:54","31-03-2025 12:20:45","31-03-2025 1=
2:25:17","Eneo outage, site down before Gen start due to poor Battery backu=
p // Gen start automatically","Fabrice Pouakam","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Eneo outage, site down bef=
ore Gen start due to poor Battery backup // Gen start automatically
","alexandre.kamal@ihstowers.com","310","31-03-2025 12:25:54","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004695971","B=
iteng-Maetur","","31-03-2025 12:24:30","31-03-2025 12:07:06","31-03-2025 14=
:11:06","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid restorati=
on","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid restoration=
","alexandre.kamal@ihstowers.com","1045","31-03-2025 12:24:30","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004695969","S=
OA TOWN","","31-03-2025 12:23:35","31-03-2025 12:06:16","31-03-2025 12:53:1=
6","Site down due to high temp /  radiator  cooled with water","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","Site down du=
e to high temp /  radiator  cooled with water","alexandre.kamal@ihstowers.c=
om","1040","31-03-2025 12:23:35","MATECH CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004695741","A=
kak-Nkozoa-MTN-IHS","","31-03-2025 11:41:54","31-03-2025 11:34:49","31-03-2=
025 11:44:36","Gen stopped due to low level of oil (leak of oil) // oil add=
 and Gen start manually","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Oil Leakage","Gen stopped due to low level of oil (leak of =
oil) // oil add and Gen start manually
","alexandre.kamal@ihstowers.com","426","31-03-2025 11:41:54","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004695681","N=
kolondom","","31-03-2025 11:29:06","31-03-2025 10:27:58","31-03-2025 10:42:=
58","Malfunction of ATS in the ZTE BTS due to Eneo fluctuation // ATS Reset=
","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF I=
ssue","Malfunction of ATS in the ZTE BTS due to Eneo fluctuation // ATS Res=
et","alexandre.kamal@ihstowers.com","3670","31-03-2025 11:29:06","MATECH CM=
R"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004695540","M=
essa-Carriere OCM","","31-03-2025 10:55:25","31-03-2025 10:49:19","31-03-20=
25 11:54:19","No power issue on site Ubaie 54V site Grid, Mouamadou (691144=
435/Huawei) is informed   ","","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie 54V=
 site Grid, Mouamadou (691144435/Huawei) is informed  =20
","alexandre.kamal@ihstowers.com","367","31-03-2025 10:55:25","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004695397","O=
LAMA","","31-03-2025 10:31:58","31-03-2025 10:21:59","31-03-2025 11:45:18",=
"No power issue on site Ubaie 54V site on Gen Henry (691145055/Huawei) is i=
nformed","Fanda Brice","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue on site Ubaie 54V site on=
 Gen Henry (691145055/Huawei) is informed","alexandre.kamal@ihstowers.com",=
"600","31-03-2025 10:31:58","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004695320","N=
koabang Ebolmedjock","","31-03-2025 10:12:10","31-03-2025 09:53:05","31-03-=
2025 10:36:43","Grid outage  disjonction on gen / Gen CB rearmed","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage  disjonction on gen / Gen CB rearmed","alexandre.kamal@ihstowers=
.com","1146","31-03-2025 10:12:10","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004694871","Ole=
mbe MTN","","31-03-2025 08:53:05","31-03-2025 08:15:49","31-03-2025 14:07:2=
4","Site went down due to insufficiency of rectifiers on site  // site stab=
ilized(need to add 01 rectifier)","Fabrice Pouakam","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Site went down due to insufficiency o=
f rectifiers on site  // site stabilized(need to add 01 rectifier)","kamga.=
virgile@ihstowers.com","2237","31-03-2025 08:53:05","MATECH CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0004694818","E=
kie sud","","31-03-2025 08:38:05","31-03-2025 08:23:16","31-03-2025 08:52:1=
5","Site down due to fuel Shortage // Refueling done","Albran Byorel","Fuel=
 Outage","Passive","Diesel","Diesel Outage","Site down due to fuel Shortage=
 // Refueling done","alexandre.kamal@ihstowers.com","890","31-03-2025 08:38=
:05","MATECH CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004694814","N=
YOM 2 IHS","","31-03-2025 08:36:14","31-03-2025 08:07:08","31-03-2025 11:36=
:20","Site down due to disjunction in the OCM BAY  //  OCM CB switch on","F=
abrice Pouakam","Equipment Repair","Passive","Control Panel","BTS Breaker -=
 Off By Unknown","Site down due to disjunction in the OCM BAY  //  OCM CB s=
witch on","alexandre.kamal@ihstowers.com","1747","31-03-2025 08:36:14","MAT=
ECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004694558","Ebeba","=
","31-03-2025 07:27:09","31-03-2025 06:39:25","31-03-2025 07:28:32","Cascad=
ed Incident from TTO4781440","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Eneo outage, site down due to Gen card faul=
ty// Card blocked","system","271454","31-03-2025 07:27:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004694557","Mbankomo=
 IHS","","31-03-2025 07:27:09","31-03-2025 06:39:25","31-03-2025 07:28:32",=
"Cascaded Incident from TTO4781440","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Eneo outage, site down due to Gen ca=
rd faulty// Card blocked","system","271455","31-03-2025 07:27:09","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004694559","Angongo"=
,"","31-03-2025 07:27:09","31-03-2025 06:39:25","31-03-2025 07:28:32","Casc=
aded Incident from TTO4781440","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Eneo outage, site down due to Gen card fa=
ulty// Card blocked","system","271455","31-03-2025 07:27:09","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0004694438","O=
KOA Peage","IHS_YND_695, IHS_YND_339, IHS_YND_335","31-03-2025 07:07:37","3=
1-03-2025 06:39:25","31-03-2025 07:28:32","Eneo outage, site down due to Ge=
n card faulty// Card blocked","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Eneo outage, site down due to Gen card fau=
lty// Card blocked","alexandre.kamal@ihstowers.com","1693","31-03-2025 07:0=
7:37","MATECH CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0004694322","Bar=
riere IHS","","31-03-2025 06:37:21","31-03-2025 06:29:15","31-03-2025 07:58=
:47","site down due t fuse Eneo faulty, // site on Gen and two rack of batt=
ery mouve due to Gen overload","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","site down due t fuse Eneo faulty, // site o=
n Gen and two rack of battery mouve due to Gen overload","kamga.virgile@ihs=
towers.com","740","31-03-2025 06:37:21","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004694230","F=
ouda-New","","31-03-2025 06:09:48","31-03-2025 06:04:41","31-03-2025 09:19:=
06","site down due to MPR dysfunctionment // end of work","Delor Telezing",=
"Equipment Replacement","Passive","Planned Activity","Planned Activity - Pa=
ssive","site down due to MPR dysfunctionment // end of work","edwige.kapawo=
@matech-cameroun.com","307","31-03-2025 06:09:48","MATECH CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004694189","N=
koabang Ebolmedjock","","31-03-2025 05:56:00","31-03-2025 04:59:53","31-03-=
2025 05:56:43","Site went down due to trip of Genset Circuit Breker (invest=
igation ongoing) // He reamed GE breaker ","Mba Lazare Herve","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Main Breaker Tripped","Site went down du=
e to trip of Genset Circuit Breker (investigation ongoing) // He reamed GE =
breaker ","joelle.ekessi@ihstowers.com","3368","31-03-2025 05:56:00","MATEC=
H CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004694141","MBA=
LNGONG LYCEE","","31-03-2025 05:38:11","31-03-2025 05:30:02","31-03-2025 07=
:52:32","Grid Outage Site went down due to Gen overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went d=
own due to Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and conf=
irmed // Grid return","christian.fonkou@ihstowers.com","491","31-03-2025 05=
:38:11","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004693871","Eto=
ug ebe biscuiterie","","31-03-2025 04:05:58","31-03-2025 03:52:46","31-03-2=
025 14:18:35","site down due to 1/3 rectifiers faulty // rectifiers replace=
d, site on Grid","Hyemafo Gildas","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","site down due to 1/3 rectifiers faulty // rectifiers re=
placed, site on Grid","christian.fonkou@ihstowers.com","793","31-03-2025 04=
:05:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004693784","Mbeng","=
","31-03-2025 03:34:07","30-03-2025 20:43:55","31-03-2025 07:33:49","Eneo o=
utage, Site Down due to fuel shortage// refueling Done","Fanda Brice","Fuel=
 Outage","Passive","Diesel","Diesel Outage","Eneo outage, Site Down due to =
fuel shortage// refueling Done","joelle.ekessi@ihstowers.com","24613","31-0=
3-2025 03:34:07","MATECH CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004693661","Bit=
eng-Maetur","","31-03-2025 02:40:19","31-03-2025 02:12:03","31-03-2025 05:4=
4:46","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the l=
oad","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, Site went down because Gen started and stopped due to =
Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the =
load","christian.fonkou@ihstowers.com","1697","31-03-2025 02:40:19","MATECH=
 CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004693637","Sap=
eur","","31-03-2025 02:24:07","31-03-2025 02:16:03","31-03-2025 02:28:14","=
Grid outage, site down due to poor backup// eneo return","Mboua Thierry","E=
quipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","G=
rid outage, site down due to poor backup// eneo return","christian.fonkou@i=
hstowers.com","485","31-03-2025 02:24:07","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004693554","Aka=
k-Nkozoa-MTN-IHS","","31-03-2025 02:04:09","31-03-2025 01:57:56","31-03-202=
5 02:09:04","Grid outage, Gen fails to start due to overcurent alarm/ Gen c=
ard reset and manually stared","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage, Gen fails to start due to ove=
rcurent alarm/ Gen card reset and manually stared","christian.fonkou@ihstow=
ers.com","375","31-03-2025 02:04:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004693458","Golf Qua=
ter","","31-03-2025 01:22:10","30-03-2025 13:09:03","30-03-2025 15:58:57","=
site down due to fuel shortage // Refueling done","Mboua Thierry","Fuel Out=
age","Passive","Diesel","Diesel Outage","site down due to fuel shortage // =
Refueling done","joelle.ekessi@ihstowers.com","43988","31-03-2025 01:22:10"=
,"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_005","NOCINC0004693450","Imm-Olym=
pique","","31-03-2025 01:18:23","28-03-2025 02:30:16","28-03-2025 03:06:10"=
,"No power issue on site. Ubaie:54,6V site on Grid FME Tx is informed","Pau=
l BIBOUM","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue on site. Ubaie:54,6V site on Grid FME =
Tx is informed","joelle.ekessi@ihstowers.com","254888","31-03-2025 01:18:23=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_796","NOCINC0004693441","Nkoabang=
 Ebolmedjock","","31-03-2025 01:15:48","27-03-2025 18:09:29","27-03-2025 19=
:09:29","No power issue on site. Ubaie:53,5V site on Grid,  Lionel Adjex( 6=
55184876/ Huawei) is informed.","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site. Ubaie:53,5V site on Grid,  Lionel Adjex( 655184876/ Huawei) is =
informed.","joelle.ekessi@ihstowers.com","284780","31-03-2025 01:15:48","MA=
TECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004692957","Odz=
a II OCM","","30-03-2025 22:53:04","30-03-2025 22:27:58","30-03-2025 23:56:=
34","Grid outage, site went down because gen started and stopped with alarm=
 over current // He reset gen card and gen manually started","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge, site went down because gen started and stopped with alarm over current =
// He reset gen card and gen manually started","christian.fonkou@ihstowers.=
com","1507","30-03-2025 22:53:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0004692932","Mbedoumo=
u - Ekali","","30-03-2025 22:47:49","30-03-2025 22:26:11","30-03-2025 23:55=
:35","Cascaded Incident from TTO4779683","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down g=
en start and stopped with alarm over current // He reset gen card and gen m=
anually","system","272290","30-03-2025 22:47:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004692934","Mehanda =
1","","30-03-2025 22:47:49","30-03-2025 22:26:11","30-03-2025 23:55:35","Ca=
scaded Incident from TTO4779683","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down gen start=
 and stopped with alarm over current // He reset gen card and gen manually"=
,"system","272288","30-03-2025 22:47:49","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004692909","Nko=
lnda","IHS_YND_343, IHS_YND_385, IHS_YND_746, IHS_YND_553, IHS_YND_410, IHS=
_EBO_015, IHS_DLA_485, IHS_YND_411","30-03-2025 22:43:16","30-03-2025 22:26=
:11","30-03-2025 23:55:35","Grid outage, site went down gen start and stopp=
ed with alarm over current // He reset gen card and gen manually","Albran B=
yorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage, site went down gen start and stopped with alarm over current // He=
 reset gen card and gen manually","christian.fonkou@ihstowers.com","1026","=
30-03-2025 22:43:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004692767","Emana Ly=
cee","","30-03-2025 22:12:27","30-03-2025 16:37:07","30-03-2025 18:52:07","=
Cascaded Incident from TTO4777485","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down becau=
se Gen failed to start with ""overcurrent"" alarm// He reset Gen card and s=
tarted Gen manualy","system","278628","30-03-2025 22:12:27","MATECH CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004692737","Eto=
ug ebe biscuiterie","","30-03-2025 22:06:27","30-03-2025 21:49:06","31-03-2=
025 01:44:38","site down due to 1/3 rectifiers faulty // rectifiers replace=
d, site on Grid","Hyemafo Gildas","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","site down due to 1/3 rectifiers faulty // rectifiers re=
placed, site on Grid","rouselle.schoune@ihstowers.com","1042","30-03-2025 2=
2:06:27","MATECH CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004692466","CRH=
-Etoug-Ebe","","30-03-2025 21:18:39","30-03-2025 21:00:18","30-03-2025 21:1=
4:18","No power issue, Site on Grid Ubai=3D 54V The TX Mahamadou (691144435=
) from Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, Sit=
e on Grid Ubai=3D 54V The TX Mahamadou (691144435) from Huawei is informed"=
,"rouselle.schoune@ihstowers.com","1102","30-03-2025 21:18:39","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004692412","N=
kolondom","","30-03-2025 21:09:48","30-03-2025 20:21:20","30-03-2025 23:41:=
48","Site down due to Malfunction of the ZTE PWC automation system // Reset=
 ATS controller, gen start automatically","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","ATS-AMF Issue","Site down due to Malfunction=
 of the ZTE PWC automation system // Reset ATS controller, gen start automa=
tically
","stephane.nkamwa@ihstowers.com","2909","30-03-2025 21:09:48","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0004692401","EMANA BI=
LICK CITY","","30-03-2025 21:08:21","30-03-2025 20:20:59","30-03-2025 22:35=
:47","Cascaded Incident from TTO4779037","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage.gen failed to s=
tart due to alarm ""overcurrent""//We reset card GE and gen manually starte=
d","system","279700","30-03-2025 21:08:21","MATECH CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0004692376","O=
kolo","IHS_YND_523","30-03-2025 21:04:13","30-03-2025 20:20:59","30-03-2025=
 22:35:47","Grid outage.gen failed to start due to alarm ""overcurrent""//W=
e reset card GE and gen manually started","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to =
start due to alarm ""overcurrent""//We reset card GE and gen manually start=
ed","stephane.nkamwa@ihstowers.com","2595","30-03-2025 21:04:13","MATECH CM=
R"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004692232","Ole=
mbe MTN","","30-03-2025 20:43:37","30-03-2025 18:54:32","30-03-2025 22:06:2=
4","Site went down due to insufficiency of rectifiers on site SS IHS Pascal=
ine is confirm // He reduced the load","Fabrice Pouakam","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down due to insufficie=
ncy of rectifiers on site SS IHS Pascaline is confirm // He reduced the loa=
d","rouselle.schoune@ihstowers.com","6546","30-03-2025 20:43:37","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004691920","Mehanda =
1","","30-03-2025 20:03:30","30-03-2025 18:43:37","30-03-2025 19:57:37","Ca=
scaded Incident from TTO4778501","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Bad grid voltgage, Site put on Gen ",=
"system","278353","30-03-2025 20:03:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0004691917","Mbedoumo=
u - Ekali","","30-03-2025 20:03:29","30-03-2025 18:43:37","30-03-2025 19:57=
:37","Cascaded Incident from TTO4778501","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Bad grid voltgage, Site put o=
n Gen ","system","278352","30-03-2025 20:03:29","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004691904","S=
atcom","","30-03-2025 20:01:12","30-03-2025 19:44:55","30-03-2025 20:10:28"=
,"no power issue on site Ubaie =3D 54V site on grid, site up without interv=
ention","Delor Telezing","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","no power issue on site Ubaie =3D 54V s=
ite on grid, site up without intervention
","stephane.nkamwa@ihstowers.com","978","30-03-2025 20:01:12","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004691902","Nko=
lnda","IHS_YND_343, IHS_YND_723, IHS_YND_385, IHS_YND_746, IHS_YND_410, IHS=
_YND_595, IHS_EBO_015, IHS_YND_344, IHS_YND_411","30-03-2025 19:59:57","30-=
03-2025 18:43:37","30-03-2025 19:57:37","Site went down because Gen failed =
to start due to bad grid voltage // He bypassed grid and manually starts th=
e Gen ","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Site went down because Gen failed to start due to ba=
d grid voltage // He bypassed grid and manually starts the Gen ","rouselle.=
schoune@ihstowers.com","4581","30-03-2025 19:59:57","MATECH CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0004691448","O=
lembe","","30-03-2025 18:37:31","30-03-2025 18:03:17","30-03-2025 19:39:17"=
,"Site went down due to insufficiency of rectifiers on site SS IHS Pascalin=
e is confirm // He reduced the load","Fabrice Pouakam","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down due to insufficienc=
y of rectifiers on site SS IHS Pascaline is confirm // He reduced the load"=
,"stephane.nkamwa@ihstowers.com","2055","30-03-2025 18:37:31","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004691435","Eki=
e sud","","30-03-2025 18:33:25","30-03-2025 18:02:20","30-03-2025 19:32:20"=
,"Grid over voltage /Grid stabilise","Albran Byorel","Grid Supply","Passive=
","Grid","National Grid - Grid Over Voltage","Grid over voltage /Grid stabi=
lise","rouselle.schoune@ihstowers.com","1866","30-03-2025 18:33:25","MATECH=
 CMR"
"Closed Complete","Site Down","T1622","IHS_YND_186","NOCINC0004691299","Ngo=
usso Carrefour","","30-03-2025 18:01:43","30-03-2025 17:36:36","30-03-2025 =
19:22:36","Disjunction in the power bay //  CB switched on","Siligap Boris"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Brea=
ker Issue","Disjunction in the power bay //  CB switched on","rouselle.scho=
une@ihstowers.com","1508","30-03-2025 18:01:43","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004691296","N=
kolondom","","30-03-2025 18:00:34","30-03-2025 17:50:09","30-03-2025 18:08:=
12","Site went down because gen failed to start due to grid bad voltage // =
Grid return","Fabrice Pouakam","Grid Supply","Passive","Grid","National Gri=
d - Low Current Supply","Site went down because gen failed to start due to =
grid bad voltage // Grid return","stephane.nkamwa@ihstowers.com","627","30-=
03-2025 18:00:34","MATECH CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004691272","C=
rf-Nkolbisson","","30-03-2025 17:57:56","30-03-2025 17:24:32","30-03-2025 1=
8:29:48","Disjunction in the energie bay due to the site load which increas=
ed there from 03 days ago (we need second depart)// disjunctor rearm","TIEN=
TCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","Circuit=
 Breaker Tripped","Disjunction in the energie bay due to the site load whic=
h increased there from 03 days ago (we need second depart)// disjunctor rea=
rm","stephane.nkamwa@ihstowers.com","2005","30-03-2025 17:57:56","MATECH CM=
R"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004691263","B=
iteng-Maetur","","30-03-2025 17:56:11","30-03-2025 17:09:49","30-03-2025 21=
:06:32","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the=
 load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen started and stopped due t=
o Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced th=
e load","stephane.nkamwa@ihstowers.com","2783","30-03-2025 17:56:11","MATEC=
H CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004691202","NYO=
M FACE MAETUR","","30-03-2025 17:47:43","30-03-2025 16:36:38","30-03-2025 2=
0:18:38","Grid outage, Site went down because Gen failed to start due Gen c=
ard Faulty// Grid Restored","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, Site went down because Gen =
failed to start due Gen card Faulty// Grid Restored","rouselle.schoune@ihst=
owers.com","4267","30-03-2025 17:47:43","MATECH CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0004691025","O=
kolo","IHS_YND_274","30-03-2025 17:06:28","30-03-2025 16:37:07","30-03-2025=
 18:52:07","Grid outage.gen failed to start due to alarm ""overcurrent""//W=
e reset card GE and gen manually started","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went dow=
n because Gen failed to start with ""overcurrent"" alarm// He reset Gen car=
d and started Gen manualy","stephane.nkamwa@ihstowers.com","1762","30-03-20=
25 17:06:28","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004690992","E=
kombitie","","30-03-2025 17:00:20","30-03-2025 15:14:59","30-03-2025 23:56:=
45","Site went down because Gen failed to start due to ATS OF Zte malfuncti=
on // He reset the ATS and configured it","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","ATS-AMF Issue","Site went down because Gen f=
ailed to start due to ATS OF Zte malfunction // He reset the ATS and config=
ured it","stephane.nkamwa@ihstowers.com","6322","30-03-2025 17:00:20","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004690983","M=
essassi 2","","30-03-2025 16:59:01","30-03-2025 14:42:39","30-03-2025 15:17=
:39","site down due to insufficient rectifiers // on rectifier added, site =
on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifi=
er Cabinet","site down due to insufficient rectifiers // on rectifier added=
, site on Gen","stephane.nkamwa@ihstowers.com","8184","30-03-2025 16:59:01"=
,"MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004690918","Mes=
sassi okolo","","30-03-2025 16:48:25","30-03-2025 15:18:13","30-03-2025 18:=
51:13","Grid outage , poor battery backup // Gen manually started","Fabrice=
 Pouakam","Equipment Repair","Passive","Control Panel","Power Cabinet - Bat=
tery Low","Grid outage , poor battery backup // Gen manually started","rous=
elle.schoune@ihstowers.com","5413","30-03-2025 16:48:25","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004690548","E=
mana Lycee","","30-03-2025 16:00:12","30-03-2025 15:44:53","30-03-2025 15:4=
9:53","Tx issue T57 V Site on grid, Sipofo is informed","Fabrice Pouakam","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Tx issue T57 V Site on grid, Sipofo is informed","stephane.nkamw=
a@ihstowers.com","920","30-03-2025 16:00:12","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004690501","E=
mana lycee 2","","30-03-2025 15:54:27","30-03-2025 15:43:13","30-03-2025 18=
:51:13","Grid fluctuation, site went down because Gen failed to start due t=
o grid bad voltage and no Rcp // He bypassed Grid and started Gen manually"=
,"Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Low Curr=
ent Supply","Grid fluctuation, site went down because Gen failed to start d=
ue to grid bad voltage and no Rcp // He bypassed Grid and started Gen manua=
lly","stephane.nkamwa@ihstowers.com","675","30-03-2025 15:54:27","MATECH CM=
R"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004690167","Men=
dong vallee","","30-03-2025 15:13:40","30-03-2025 15:08:32","30-03-2025 15:=
37:32","Site went down because Gen overload(15kva,200 A)  // Grid return","=
Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Sit=
e went down because Gen overload(15kva,200 A)  // Grid return","rouselle.sc=
houne@ihstowers.com","309","30-03-2025 15:13:40","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004690121","Nko=
l-Mbanda","","30-03-2025 15:03:18","30-03-2025 14:15:11","30-03-2025 15:47:=
11","Grid outage.gen ran until fuel shortage//Refueling done","MINKA NICOLA=
S","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran un=
til fuel shortage//Refueling done","rouselle.schoune@ihstowers.com","2888",=
"30-03-2025 15:03:18","MATECH CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0004690106","N=
komo","","30-03-2025 14:59:41","30-03-2025 14:42:18","30-03-2025 15:03:18",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Gen start automatically","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen start due to poor battery backup // Gen start automatically","ste=
phane.nkamwa@ihstowers.com","1044","30-03-2025 14:59:41","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004689681","F=
ouda-New","","30-03-2025 13:42:05","30-03-2025 13:33:47","30-03-2025 13:56:=
45","Grid outage, site went down because rectifier went hanging  // rectifi=
er reset done","Delor Telezing","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Grid outage, site went down because rectifier went hangin=
g  // rectifier reset done","ludivine.ngamaleu@ihstowers.com","499","30-03-=
2025 13:42:05","MATECH CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004689539","S=
hell-Nsimeyong","","30-03-2025 13:11:54","30-03-2025 13:06:32","30-03-2025 =
13:13:55","No power isssue on site Ubaie 54V site on Grid, site Up without =
intervention.","MINKA NICOLAS","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power isssue on site Ubaie 54=
V site on Grid, site Up without intervention.","ludivine.ngamaleu@ihstowers=
.com","323","30-03-2025 13:11:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0004689448","NYOM 2 I=
HS","","30-03-2025 12:51:05","30-03-2025 12:24:48","30-03-2025 12:52:41","C=
ascaded Incident from TTO4775593","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site down due to High temp // Wate=
r add and Gen start","system","265020","30-03-2025 12:51:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_305","NOCINC0004689449","NYOM",""=
,"30-03-2025 12:51:05","30-03-2025 12:24:48","30-03-2025 12:52:41","Cascade=
d Incident from TTO4775593","Fabrice Pouakam","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site down due to High temp // Water add =
and Gen start","system","265021","30-03-2025 12:51:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_802","NOCINC0004689446","NYOM FAC=
E MAETUR","","30-03-2025 12:51:04","30-03-2025 12:24:48","30-03-2025 12:52:=
41","Cascaded Incident from TTO4775593","Fabrice Pouakam","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","site down due to High temp /=
/ Water add and Gen start","system","265019","30-03-2025 12:51:04","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004689444","SOA VILL=
AGE","","30-03-2025 12:51:04","30-03-2025 12:24:48","30-03-2025 13:15:07","=
Cascaded Incident from TTO4775593 - Cascade Removed From TTO4775593","Silig=
ap Boris","Cascade Outage","Passive","Cascade Passive","Cascade Passive","S=
ite down due to High temp // radiator cleaned, Water added and Gen Started"=
,"system","264964","30-03-2025 12:51:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0004689447","Nkolondo=
m","","30-03-2025 12:51:04","30-03-2025 12:24:48","30-03-2025 12:52:41","Ca=
scaded Incident from TTO4775593","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site down due to High temp // Water=
 add and Gen start","system","265025","30-03-2025 12:51:04","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0004689445","Messassi=
 Ngonlonk","","30-03-2025 12:51:04","30-03-2025 12:24:48","30-03-2025 12:52=
:41","Cascaded Incident from TTO4775593","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site down due to High temp =
// Water add and Gen start","system","265024","30-03-2025 12:51:04","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004689441","Emana Ly=
cee","","30-03-2025 12:51:03","30-03-2025 12:24:48","30-03-2025 12:52:41","=
Cascaded Incident from TTO4775593","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site down due to High temp // Wat=
er add and Gen start","system","265021","30-03-2025 12:51:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_733","NOCINC0004689442","Nkog-Edz=
en","","30-03-2025 12:51:03","30-03-2025 12:24:48","30-03-2025 12:52:41","C=
ascaded Incident from TTO4775593","Parker Tchoup","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site down due to High temp // Water =
add and Gen start","system","265023","30-03-2025 12:51:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0004689443","Messassi=
","","30-03-2025 12:51:03","30-03-2025 12:24:48","30-03-2025 12:52:41","Cas=
caded Incident from TTO4775593","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site down due to High temp // Water =
add and Gen start","system","265024","30-03-2025 12:51:03","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0004689439","Nkozoa",=
"","30-03-2025 12:51:02","30-03-2025 12:24:48","30-03-2025 12:52:41","Casca=
ded Incident from TTO4775593","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site down due to High temp // Water ad=
d and Gen start","system","265022","30-03-2025 12:51:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004689436","SOA TOWN=
","IHS_YND_323","30-03-2025 12:51:02","30-03-2025 12:24:48","30-03-2025 13:=
15:07","Site down due to High temp // radiator cleaned, Water added and Gen=
 Started","Siligap Boris","Equipment Repair","Passive","ACDG Gen","Gen Temp=
 High","Site down due to High temp // radiator cleaned, Water added and Gen=
 Started","system","1574","30-03-2025 12:51:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_761","NOCINC0004689438","Djonassi=
-Yde","","30-03-2025 12:51:02","30-03-2025 12:24:48","30-03-2025 12:52:41",=
"Cascaded Incident from TTO4775593","Fabrice Pouakam","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","site down due to High temp // Wa=
ter add and Gen start","system","265023","30-03-2025 12:51:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0004689437","Emana ly=
cee 2","","30-03-2025 12:51:02","30-03-2025 12:24:48","30-03-2025 12:52:41"=
,"Cascaded Incident from TTO4775593","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site down due to High temp // W=
ater add and Gen start","system","265020","30-03-2025 12:51:02","MATECH CMR=
"
"Closed Complete","Site Down","","IHS_YND_298","NOCINC0004689435","Olembe",=
"","30-03-2025 12:51:01","30-03-2025 12:24:48","30-03-2025 12:52:41","Casca=
ded Incident from TTO4775593","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site down due to High temp // Water ad=
d and Gen start","system","265026","30-03-2025 12:51:01","MATECH CMR"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0004689415","Nko=
lndom","IHS_YND_298, IHS_YND_685, IHS_YND_761, IHS_YND_306, IHS_YND_398, IH=
S_YND_274, IHS_YND_681, IHS_YND_733, IHS_YND_297, IHS_YND_799, IHS_YND_802,=
 IHS_YND_304, IHS_YND_707, IHS_YND_305, IHS_YND_324","30-03-2025 12:44:58",=
"30-03-2025 12:24:48","30-03-2025 12:52:41","site down due to High temp // =
Water add and Gen started manually","Fabrice Pouakam","Equipment Repair","P=
assive","ACDG Gen","Gen Temp High","site down due to High temp // Water add=
 and Gen start","olivier.kwedi@ihstowers.com","1211","30-03-2025 12:44:58",=
"MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_305","NOCINC0004688807","NYOM",""=
,"30-03-2025 10:36:55","30-03-2025 10:16:17","30-03-2025 11:06:30","Cascade=
d Incident from TTO4774854","Fabrice Pouakam","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site down due to fuel shortage // Refuel=
ing done","system","265494","30-03-2025 10:36:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0004688806","NYOM 2 I=
HS","","30-03-2025 10:36:55","30-03-2025 10:16:17","30-03-2025 11:06:30","C=
ascaded Incident from TTO4774854","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site down due to fuel shortage // =
Refueling done","system","265496","30-03-2025 10:36:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0004688803","Messassi=
","","30-03-2025 10:36:54","30-03-2025 10:16:17","30-03-2025 11:06:30","Cas=
caded Incident from TTO4774854","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site down due to fuel shortage // Re=
fueling done","system","265491","30-03-2025 10:36:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004688801","Emana Ly=
cee","","30-03-2025 10:36:54","30-03-2025 10:16:17","30-03-2025 11:06:30","=
Cascaded Incident from TTO4774854","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site down due to fuel shortage //=
 Refueling done","system","265495","30-03-2025 10:36:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0004688805","Nkolondo=
m","","30-03-2025 10:36:54","30-03-2025 10:16:17","30-03-2025 11:06:30","Ca=
scaded Incident from TTO4774854","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site down due to fuel shortage // R=
efueling done","system","265496","30-03-2025 10:36:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0004688804","Messassi=
 Ngonlonk","","30-03-2025 10:36:54","30-03-2025 10:16:17","30-03-2025 11:06=
:30","Cascaded Incident from TTO4774854","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site down due to fuel short=
age // Refueling done","system","265498","30-03-2025 10:36:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_733","NOCINC0004688802","Nkog-Edz=
en","","30-03-2025 10:36:54","30-03-2025 10:16:17","30-03-2025 11:06:30","C=
ascaded Incident from TTO4774854","Parker Tchoup","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site down due to fuel shortage // Re=
fueling done","system","265493","30-03-2025 10:36:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0004688799","Nkozoa",=
"","30-03-2025 10:36:53","30-03-2025 10:16:17","30-03-2025 11:06:30","Casca=
ded Incident from TTO4774854","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site down due to fuel shortage // Refu=
eling done","system","265490","30-03-2025 10:36:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0004688797","Emana ly=
cee 2","","30-03-2025 10:36:53","30-03-2025 10:16:17","30-03-2025 11:06:30"=
,"Cascaded Incident from TTO4774854","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site down due to fuel shortage =
// Refueling done","system","265493","30-03-2025 10:36:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_761","NOCINC0004688798","Djonassi=
-Yde","","30-03-2025 10:36:53","30-03-2025 10:16:17","30-03-2025 11:06:30",=
"Cascaded Incident from TTO4774854","Fabrice Pouakam","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","site down due to fuel shortage /=
/ Refueling done","system","265490","30-03-2025 10:36:53","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_298","NOCINC0004688796","Olembe",=
"","30-03-2025 10:36:52","30-03-2025 10:16:17","30-03-2025 11:06:30","Casca=
ded Incident from TTO4774854","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site down due to fuel shortage // Refu=
eling done","system","265495","30-03-2025 10:36:52","MATECH CMR"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0004688761","Nko=
lndom","IHS_YND_298, IHS_YND_685, IHS_YND_761, IHS_YND_306, IHS_YND_398, IH=
S_YND_274, IHS_YND_681, IHS_YND_733, IHS_YND_220, IHS_YND_297, IHS_YND_799,=
 IHS_YND_304, IHS_YND_707, IHS_YND_305, IHS_YND_324","30-03-2025 10:30:27",=
"30-03-2025 10:16:17","30-03-2025 11:06:30","site down due to fuel shortage=
 // Refueling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Die=
sel Outage","site down due to fuel shortage // Refueling done","olivier.kwe=
di@ihstowers.com","851","30-03-2025 10:30:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0004688740","Ekoumdou=
m OCM","","30-03-2025 10:26:41","30-03-2025 10:20:08","30-03-2025 11:09:59"=
,"Cascaded Incident from TTO4774823","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive"," site down due to rectifier plant=
ed // rectifier rearm","system","272517","30-03-2025 10:26:41","MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0004688733","O=
dza-PK10","IHS_YND_527, IHS_YND_291","30-03-2025 10:25:19","30-03-2025 10:2=
0:08","30-03-2025 11:09:59","Rectifier hanging // Rectifier reset","Albran =
Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet"," site=
 down due to rectifier planted // rectifier rearm","ludivine.ngamaleu@ihsto=
wers.com","312","30-03-2025 10:25:19","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004688513","E=
kombitie","","30-03-2025 09:45:10","30-03-2025 09:26:57","30-03-2025 13:13:=
40","Grid gen site , Grid instability / Grid restoration","Fabrice Pouakam"=
,"Grid Supply","Passive","Grid","National Grid - Low Current Supply","Grid =
gen site , Grid instability / Grid restoration","ludivine.ngamaleu@ihstower=
s.com","1094","30-03-2025 09:45:10","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004688374","M=
essa-Carriere OCM","","30-03-2025 09:08:49","30-03-2025 08:57:33","30-03-20=
25 09:46:43","No power issue on site Ubaie 54V site Grid, Mouamadou (691144=
435/Huawei) is informed","","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie 54V si=
te Grid, Mouamadou (691144435/Huawei) is informed","ludivine.ngamaleu@ihsto=
wers.com","678","30-03-2025 09:08:49","MATECH CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004688355","Eki=
e sud","","30-03-2025 09:02:08","30-03-2025 08:09:01","30-03-2025 10:21:57"=
,"Site down due to Absence of phase // bridge made","Albran Byorel","Grid S=
upply","Passive","Grid","National Grid - Grid Incomplete Phase","Site down =
due to Absence of phase // bridge made","olivier.kwedi@ihstowers.com","3188=
","30-03-2025 09:02:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_801","NOCINC0004688255","HOPITAL =
GENERAL RAIL YDE","","30-03-2025 08:23:59","30-03-2025 08:18:47","30-03-202=
5 09:24:46","Cascaded Incident from TTO4774290","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","site down due to rect=
ifiers issue // Site stabilzated","system","279913","30-03-2025 08:23:59","=
MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004688248","Pha=
rmacie Bleue","IHS_YND_801","30-03-2025 08:22:14","30-03-2025 08:18:47","30=
-03-2025 08:24:46","site down due to rectifiers issue // Site stabilzated",=
"Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Cabinet=
","site down due to rectifiers issue // Site stabilzated","gerard.tchangoue=
@matech-cameroun.com","208","30-03-2025 08:22:14","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004688063","Aka=
k-Nkozoa-MTN-IHS","","30-03-2025 07:39:41","30-03-2025 06:52:24","30-03-202=
5 09:49:33","site down due to bad Eneo voltage // site put on Gen","Fabrice=
 Pouakam","Grid Supply","Passive","Grid","National Grid - Unstable Grid Sup=
ply Issue","site down due to bad Eneo voltage // site put on Gen","olivier.=
kwedi@ihstowers.com","2839","30-03-2025 07:39:41","MATECH CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0004687705","A=
RMP","","30-03-2025 05:50:53","30-03-2025 05:48:45","30-03-2025 05:59:35","=
Grid outage//MDG of 20ka has deployed","","Grid Supply","Passive","Grid","N=
ational Grid - Grid Outage Issue","Grid outage//MDG of 20ka has deployed","=
kouoh.jean@ihstowers.com","129","30-03-2025 05:50:53","MATECH CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004687593","SOA=
 UNIVERSITY STADIUM","","30-03-2025 05:13:15","30-03-2025 04:59:09","30-03-=
2025 11:23:30","GEN OVERLOAD // Load reduced","Siligap Boris","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","GEN OVERLOAD // Load reduced"=
,"landry.etame@ihstowers.com","9000","30-03-2025 05:13:15","MATECH CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004687528","Nko=
lmvack","","30-03-2025 04:19:56","30-03-2025 04:14:45","30-03-2025 06:14:31=
","Grid outage, Site went down because Gen start and stopped with ""High te=
mps ""alarm // he added water and manually start the Gen	","Parker Tchoup",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, Site went down because Gen start and stopped wit=
h ""High temps ""alarm // he added water and manually start the Gen	","land=
ry.etame@ihstowers.com","312","30-03-2025 04:19:56","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004687491","B=
iteng-Maetur","","30-03-2025 04:06:25","29-03-2025 08:48:14","30-03-2025 09=
:40:13","Gen overload // Load reduced, grid return and reset of BTS perform=
ed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Gen overload // Load reduced, grid return and reset of BTS performed=
","kouoh.jean@ihstowers.com","69589","30-03-2025 04:06:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004687263","AWAE OCM=
","","30-03-2025 01:47:26","29-03-2025 08:48:14","29-03-2025 08:57:41","Cas=
caded Incident from TTO4773161","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site down due to fuel shortage // R=
efueling done","system","364525","30-03-2025 01:47:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004687258","Bitoto",=
"","30-03-2025 01:45:27","29-03-2025 06:36:25","30-03-2025 08:37:57","Casca=
ded Incident from TTO4773161","Mba Lazare Herve","Cascade Outage","Active",=
"Cascade Active","Cascade Active","fuel shortage // Refueling done","system=
","69216","30-03-2025 01:45:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004687254","Essomba"=
,"","30-03-2025 01:42:02","29-03-2025 07:25:14","30-03-2025 08:37:57","Casc=
aded Incident from TTO4773161","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site down due to fuel shortage // Re=
fueling done","system","369505","30-03-2025 01:42:02","MATECH CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004687250","B=
iteng","IHS_YND_292, IHS_YND_173, IHS_YND_179, IHS_YND_249","30-03-2025 01:=
39:21","29-03-2025 07:25:14","30-03-2025 08:37:57","Site down due to fuel s=
hortage // Refueling done","Mba Lazare Herve","Fuel Outage","Passive","Dies=
el","Diesel Outage","Site down due to fuel shortage // Refueling done","kou=
oh.jean@ihstowers.com","65649","30-03-2025 01:39:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004687233","Bitoto",=
"","30-03-2025 01:30:10","28-03-2025 21:28:35","28-03-2025 22:04:04","Casca=
ded Incident from TTO4764420","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n failed to start due PWC dysfonction // He reset the PWC, grid return","sy=
stem","361991","30-03-2025 01:30:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004687196","Odza II =
OCM","","30-03-2025 01:13:29","29-03-2025 21:08:09","30-03-2025 11:09:59","=
Cascaded Incident from TTO4772431","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Rectifier hanging // Rectifier rese=
t","system","341572","30-03-2025 01:13:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004687195","Mehanda =
1","","30-03-2025 01:13:29","29-03-2025 21:08:09","29-03-2025 23:01:09","Ca=
scaded Incident from TTO4772431","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuation, site went down beca=
use Gen failed to start due to grid bad voltage No Rcp// He bypassed grid a=
nd started Gen manually","system","341570","30-03-2025 01:13:29","MATECH CM=
R"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0004687192","Mbedoumo=
u - Ekali","","30-03-2025 01:13:28","29-03-2025 21:08:09","29-03-2025 23:01=
:09","Cascaded Incident from TTO4772431","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Gen failed to start due to grid bad voltage No Rcp// He bypasse=
d grid and started Gen manually","system","341571","30-03-2025 01:13:28","M=
ATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004687156","Cit=
e des nations","","30-03-2025 00:56:28","30-03-2025 00:54:22","30-03-2025 0=
3:10:34","Site went down due to insufficient rectifiers on site//Site stabi=
lised","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficient rectifiers on site//Site stabilis=
ed","landry.etame@ihstowers.com","126","30-03-2025 00:56:28","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004687132","F=
ouda-New","","30-03-2025 00:47:24","29-03-2025 21:39:55","29-03-2025 23:45:=
55","","Delor Telezing","Access Denial","Lease Or Legal","Landlord Related =
Issues","Access Issue - Land Lord","Access issue during the night Grid outa=
ge .gen failed to start due to card GE dysfunctionning//Grid return","kouoh=
.jean@ihstowers.com","11250","30-03-2025 00:47:24","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004687115","M=
EHANDAN","","30-03-2025 00:39:26","29-03-2025 20:05:02","30-03-2025 12:37:0=
2","Site went down due to insufficient rectifiers on site//site stabilised"=
,"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient rectifiers on site//site stabilised",=
"kouoh.jean@ihstowers.com","16466","30-03-2025 00:39:26","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004686981","E=
mana Lycee","","30-03-2025 00:01:36","29-03-2025 21:39:15","30-03-2025 10:0=
5:41","TX,NO POWER ISSUE on site Ubay =3D 57V site on grid Symphorien (650 =
25 71 51/HUAWEI) is informed","Fabrice Pouakam","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","TX,NO POWER ISS=
UE on site Ubay =3D 57V site on grid Symphorien (650 25 71 51/HUAWEI) is in=
formed","kouoh.jean@ihstowers.com","8543","30-03-2025 00:01:36","MATECH CMR=
"
"Closed Complete","Site Down","CTR_481","IHS_YND_574","NOCINC0004686969","C=
rf-Mbankolo-IHS","","29-03-2025 23:54:48","29-03-2025 19:14:35","30-03-2025=
 15:36:35","site down due to insufficient rectifiers on site // site stabil=
ised","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Site went down due to insufficient rectifiers on site//site stabili=
sed","kouoh.jean@ihstowers.com","16814","29-03-2025 23:54:48","MATECH CMR"
"Closed Complete","Site Down","CTR_481","IHS_YND_574","NOCINC0004686948","C=
rf-Mbankolo-IHS","","29-03-2025 23:51:18","29-03-2025 14:01:15","29-03-2025=
 15:38:12","","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rec=
tifier Cabinet","Site went down due to MPR disfunction SS IHS Bernard Atang=
ana confirmed//Site stabilized with power reset done","kouoh.jean@ihstowers=
.com","35404","29-03-2025 23:51:18","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0004686824","Ekoumdou=
m OCM","","29-03-2025 23:04:50","29-03-2025 15:02:09","29-03-2025 15:09:09"=
,"Cascaded Incident from TTO4772597","Albran Byorel","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active//No power issue on site U=3D5=
4,5V site on Grid The Rm Alain (691144423) of huawei is informed and notice=
 thad disjunction in OCM Equipment ","system","298976","29-03-2025 23:04:50=
","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004686823","MEHANDAN=
","","29-03-2025 23:04:50","29-03-2025 15:02:09","29-03-2025 15:09:09","Cas=
caded Incident from TTO4772597","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site U=3D54,5V =
site on Grid The Rm Alain (691144423) of huawei is informed and notice thad=
 disjunction in OCM Equipment ","system","298976","29-03-2025 23:04:50","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004686820","Odza II =
OCM","","29-03-2025 23:03:47","29-03-2025 13:29:09","29-03-2025 13:33:09","=
Cascaded Incident from TTO4772597","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue on site U=3D54,=
5V site on Grid The Rm Alain (691144423) of huawei is informed and notice t=
had disjunction in OCM Equipment ","system","304556","29-03-2025 23:03:47",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0004686757","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","29-03-2025 22:47:25","29=
-03-2025 13:29:09","29-03-2025 13:40:09","","Albran Byorel","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue on site U=3D54,5V site on Grid The Rm Alain (691144423)=
 of huawei is informed and notice thad disjunction in OCM Equipment ","kouo=
h.jean@ihstowers.com","39939","29-03-2025 22:47:25","MATECH CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004686724","Mel=
en Ba'aba","","29-03-2025 22:44:57","29-03-2025 22:35:52","30-03-2025 00:00=
:56","Grid outage,gen ran till fuel shortage//Refueling done","Siligap Bori=
s","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran ti=
ll fuel shortage//Refueling done","landry.etame@ihstowers.com","580","29-03=
-2025 22:44:57","MATECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004686618","Nko=
lnda","IHS_YND_343, IHS_YND_723, IHS_YND_385, IHS_YND_746, IHS_YND_527, IHS=
_YND_410, IHS_YND_595, IHS_YND_344, IHS_YND_411","29-03-2025 22:22:18","29-=
03-2025 21:08:09","29-03-2025 23:01:09","Grid fluctuation, site went down b=
ecause Gen failed to start due to grid bad voltage No Rcp// He bypassed gri=
d and started Gen manually","Albran Byorel","Grid Supply","Passive","Grid",=
"National Grid - Grid Over Voltage","Grid fluctuation, site went down becau=
se Gen failed to start due to grid bad voltage No Rcp// He bypassed grid an=
d started Gen manually","christian.fonkou@ihstowers.com","4450","29-03-2025=
 22:22:18","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004686414","E=
vodoula OCM","","29-03-2025 21:43:13","29-03-2025 20:49:06","29-03-2025 23:=
14:30","Site went down Gen failed to start due to Grid bad voltage// He byp=
asse the Grid and site on Gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Site went down Gen=
 failed to start due to Grid bad voltage// He bypasse the Grid and site on =
Gen","joelle.ekessi@ihstowers.com","3248","29-03-2025 21:43:13","MATECH CMR=
"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004686059","M=
essa-Carriere OCM","","29-03-2025 20:53:55","29-03-2025 20:24:51","30-03-20=
25 05:11:08","Grid  outage, no space to deploy MDG // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid  outage=
, no space to deploy MDG // Grid return","joelle.ekessi@ihstowers.com","174=
5","29-03-2025 20:53:55","MATECH CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0004685919","A=
battoir","","29-03-2025 20:23:56","29-03-2025 20:21:52","30-03-2025 00:51:5=
2","Grid outage, site went down because gen start and stopped with high tem=
p alarm // he added water and manually start the gen","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Radiator","Grid outage, site w=
ent down because gen start and stopped with high temp alarm // he added wat=
er and manually start the gen","joelle.ekessi@ihstowers.com","125","29-03-2=
025 20:23:56","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004685837","Mon=
tee Jouvence","","29-03-2025 20:07:44","29-03-2025 19:59:34","29-03-2025 21=
:04:29","Grid fluctuation, Site went down because gen fails to start due to=
 grid bad voltage// He bypasse the Grid and site on Gen","Hyemafo Gildas","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, Site went down because gen fails to start due to grid bad v=
oltage// He bypasse the Grid and site on Gen","christian.fonkou@ihstowers.c=
om","491","29-03-2025 20:07:44","MATECH CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004685778","Eko=
mbitie","","29-03-2025 19:53:44","29-03-2025 19:44:38","29-03-2025 20:14:19=
","No power issue site on gen with U=3D54.5V site on Gen THE TX Synphorien =
691316854 of Huawei is informed","Fabrice Pouakam","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on gen with U=3D54.5V site on Gen THE TX Synphorien 691316854 of Hu=
awei is informed","christian.fonkou@ihstowers.com","547","29-03-2025 19:53:=
44","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004685686","NYO=
M FACE MAETUR","","29-03-2025 19:36:27","29-03-2025 19:25:20","30-03-2025 0=
6:17:38","Grid outage //Grid return","Fabrice Pouakam","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage //Grid return",=
"christian.fonkou@ihstowers.com","668","29-03-2025 19:36:27","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004685647","M=
endong vallee","","29-03-2025 19:26:23","29-03-2025 19:24:16","29-03-2025 2=
0:02:11","Rectifiers issue // Rectifiers reset","Fanda Brice","Equipment Re=
pair","Passive","Rectifier","Rectifier Cabinet","Rectifiers issue // Rectif=
iers reset","joelle.ekessi@ihstowers.com","128","29-03-2025 19:26:23","MATE=
CH CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0004685516","S=
apeur Mimboman","","29-03-2025 18:58:33","29-03-2025 18:18:30","29-03-2025 =
21:33:30","Eneo outage,the site down due to GEN overload // eneo return","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Eneo outage,the site down due to GEN overload // eneo return","joelle.ekes=
si@ihstowers.com","2404","29-03-2025 18:58:33","MATECH CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004685322","SAA=
 Entrance","","29-03-2025 18:20:01","29-03-2025 18:15:53","30-03-2025 08:17=
:22","Active//No power issue on site Ubaie=3D54.1V site on Gen Tx FME Grego=
ire /654547479/Huawei is informed.","Parker Tchoup","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie=3D54.1V site on Gen Tx FME Gregoire /654547479/Hu=
awei is informed.","christian.fonkou@ihstowers.com","250","29-03-2025 18:20=
:01","MATECH CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004685211","MBI=
MBIM","","29-03-2025 18:02:14","29-03-2025 17:48:42","30-03-2025 06:39:52",=
"Grid outage.site went down due to gen failed to start //Grid return(invest=
igation ongoing)","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Grid outage.site went down due to gen failed to star=
t //Grid return (investigation ongoing)","christian.fonkou@ihstowers.com","=
813","29-03-2025 18:02:14","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004684997","Aka=
k-Nkozoa-MTN-IHS","","29-03-2025 17:27:37","29-03-2025 17:14:24","29-03-202=
5 20:54:48","Site went down due to PWC Huawei malfunction SS IHS Felix Bate=
u confirmed //Grid return","Fabrice Pouakam","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down due to PWC Huawei =
malfunction SS IHS Felix Bateu confirmed //Grid return","christian.fonkou@i=
hstowers.com","6621","29-03-2025 17:27:37","MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0004684880","M=
beng","","29-03-2025 17:06:53","29-03-2025 16:47:46","29-03-2025 19:19:17",=
"site Went Down due to fuel shortage // Grid restauration (refueling ongoin=
g)","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","site We=
nt Down due to fuel shortage // Grid restauration (refueling ongoing)","joe=
lle.ekessi@ihstowers.com","1148","29-03-2025 17:06:53","MATECH CMR"
"Closed Complete","Site Down","T0578","IHS_YND_375","NOCINC0004684860","Ngo=
ung","","29-03-2025 17:02:12","29-03-2025 16:46:56","29-03-2025 17:46:56","=
Active// No power issue, site is on Grid with Ubaie=3D55,6V The TX FME Etie=
nne //695033981// from Huawei is informed","Kemeni Franklin","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue, site is on Grid with Ubaie=3D55,6V The TX FME Etienn=
e //695033981// from Huawei is informed","christian.fonkou@ihstowers.com","=
917","29-03-2025 17:02:12","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004684730","Mambine"=
,"","29-03-2025 16:42:26","29-03-2025 15:34:28","29-03-2025 17:03:21","Casc=
aded Incident from TTO4770253","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active // no power issue, site is on grid wi=
th No com, transmission card burnt ,The Tx FME Etienne 695033981 of huawei =
is informed","system","397743","29-03-2025 16:42:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004684729","Mandoumb=
a OCM","","29-03-2025 16:42:26","29-03-2025 15:34:28","29-03-2025 17:03:21"=
,"Cascaded Incident from TTO4770253","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active // no power issue, site is =
on grid with No com, transmission card burnt ,The Tx FME Etienne 695033981 =
of huawei is informed","system","397744","29-03-2025 16:42:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004684731","Nkongtoc=
k","","29-03-2025 16:42:26","29-03-2025 15:34:28","29-03-2025 17:03:21","Ca=
scaded Incident from TTO4770253","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active // no power issue, site is on g=
rid with No com, transmission card burnt ,The Tx FME Etienne 695033981 of h=
uawei is informed","system","397743","29-03-2025 16:42:26","MATECH CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0004684722","N=
kenglikok","IHS_YND_367, IHS_YND_350, IHS_YND_349","29-03-2025 16:41:43","2=
9-03-2025 15:34:28","29-03-2025 17:03:21","Active // no power issue, site i=
s on grid with No com, transmission card burnt ,The Tx FME Etienne 69503398=
1 of huawei is informed","Kemeni Franklin","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active // no power i=
ssue, site is on grid with No com, transmission card burnt ,The Tx FME Etie=
nne 695033981 of huawei is informed","joelle.ekessi@ihstowers.com","4036","=
29-03-2025 16:41:43","MATECH CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0004684523","Bas=
tos Bir","","29-03-2025 16:05:58","29-03-2025 15:51:19","29-03-2025 16:45:1=
9","Grid outage,gen start and stopped with alarm high temp//he added water =
in radiator","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG =
- High Engine Temp - Coolant Level Issue","Grid outage,gen start and stoppe=
d with alarm high temp//he added water in radiator","christian.fonkou@ihsto=
wers.com","880","29-03-2025 16:05:58","MATECH CMR"
"Closed Complete","Site Down","T3150","IHS_YND_214","NOCINC0004684496","Nko=
lmesseng-II","","29-03-2025 16:01:30","29-03-2025 15:39:17","29-03-2025 16:=
04:17","Eneo outage,  site down due to poor backup // Eneo return","Siligap=
 Boris","Equipment Repair","Passive","Control Panel","Power Cabinet - Batte=
ry Low","Eneo outage,  site down due to poor backup // Eneo return","christ=
ian.fonkou@ihstowers.com","1334","29-03-2025 16:01:30","MATECH CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004683920","Nko=
abang entree carriere","","29-03-2025 14:36:07","29-03-2025 13:53:01","29-0=
3-2025 14:15:01","Grid outage,gen ran till fuel shortage//Refueling done","=
Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid ou=
tage,gen ran till fuel shortage//Refueling done","rouselle.schoune@ihstower=
s.com","2586","29-03-2025 14:36:07","MATECH CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004683908","Nko=
ulou Carriere carrefourt","","29-03-2025 14:35:24","29-03-2025 13:46:46","2=
9-03-2025 14:11:46","Grid outage, site went down due to Gen overload(20kva,=
310 A) IHS SS Alphonse is informed// Grid return","Mba Lazare Herve","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went=
 down due to Gen overload(20kva,310 A) IHS SS Alphonse is informed// Grid r=
eturn","rouselle.schoune@ihstowers.com","2919","29-03-2025 14:35:24","MATEC=
H CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0004683875","NYO=
M","","29-03-2025 14:30:03","29-03-2025 11:43:49","29-03-2025 22:07:06","Gr=
id outage,site went down because Gen ran untill fuel shortage// Refueling D=
one","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage,site went down because Gen ran untill fuel shortage// Refueling D=
one","rouselle.schoune@ihstowers.com","9974","29-03-2025 14:30:03","MATECH =
CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004683854","M=
ontee-Anne-Rouge","","29-03-2025 14:23:06","29-03-2025 13:39:49","29-03-202=
5 14:21:51","Grid outage, No space to deploy MDG // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MDG // Grid return","stephane.nkamwa@ihstowers.com","2598=
","29-03-2025 14:23:06","MATECH CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004683834","S=
imbock OCM","","29-03-2025 14:18:05","29-03-2025 13:39:39","29-03-2025 14:3=
2:02","Site went down because gen fails to start due to grid bad voltage //=
 He bypass grid and manually start the gen","Hyemafo Gildas","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Site went down =
because gen fails to start due to grid bad voltage // He bypass grid and ma=
nually start the gen","stephane.nkamwa@ihstowers.com","2307","29-03-2025 14=
:18:05","MATECH CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0004683811","M=
fou EPC","","29-03-2025 14:13:59","29-03-2025 13:52:48","29-03-2025 14:24:4=
8","Eneo outage, MGE turned until fuel shortage // eneo return","Mba Lazare=
 Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Eneo outage, MGE =
turned until fuel shortage // eneo return","stephane.nkamwa@ihstowers.com",=
"1272","29-03-2025 14:13:59","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004683508","O=
lembe-Terminus","","29-03-2025 13:17:41","29-03-2025 12:44:14","29-03-2025 =
13:14:24","Grid outage,gen ran till fuel shortage//Refueling done","Fabrice=
 Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen=
 ran till fuel shortage//Refueling done","stephane.nkamwa@ihstowers.com","2=
008","29-03-2025 13:17:41","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0004683357","C=
harles-Atangana","IHS_YND_051","29-03-2025 12:50:56","29-03-2025 12:29:37",=
"30-03-2025 01:46:48","Grid outage no space to deploy mobile gen // Grid re=
turn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Grid outage no space to deploy mobile gen // Grid return","stephane.nkamw=
a@ihstowers.com","1280","29-03-2025 12:50:56","MATECH CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004683331","NKO=
MKANA ELIZA HOTEL","","29-03-2025 12:47:37","29-03-2025 12:11:28","29-03-20=
25 12:46:35","Eneo outage and Grid only, no space to deployed MGE // Grid r=
eturned","","Grid Supply","Passive","Grid","National Grid - Grid Outage Iss=
ue","Eneo outage and Grid only, no space to deployed MGE // Grid returned",=
"rouselle.schoune@ihstowers.com","2170","29-03-2025 12:47:37","MATECH CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004683265","N=
yom OCM","","29-03-2025 12:38:11","29-03-2025 11:04:27","29-03-2025 11:10:2=
7","Active//No power issue on site ,Site on grid Ubaie=3D54,2v,dcload=3D43,=
1A armand//699949553 from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site ,Site on grid Ubaie=3D54,2v,dcload=3D43,1A =
armand//699949553 from Huawei is informed","stephane.nkamwa@ihstowers.com",=
"5626","29-03-2025 12:38:11","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004683229","N=
kolondom","","29-03-2025 12:36:08","29-03-2025 11:04:45","29-03-2025 14:59:=
35","Site went down because PWC  dysfunction on site //He reset it","Fabric=
e Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Overl=
oaded","Site went down because PWC  dysfunction on site //He reset it","ste=
phane.nkamwa@ihstowers.com","5484","29-03-2025 12:36:08","MATECH CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004683224","N=
KOLMEKONG YDE","","29-03-2025 12:34:25","29-03-2025 11:04:05","30-03-2025 1=
2:52:41","Site down due to PM (Poor battery backup) // End of work","Fabric=
e Pouakam","Equipment Repair","Passive","Control Panel","Power Cabinet - Ba=
ttery Low","Site down due to PM (Poor battery backup) // End of work
","stephane.nkamwa@ihstowers.com","5422","29-03-2025 12:34:25","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004683190","Mon=
tee-Jouvence-II","","29-03-2025 12:25:07","29-03-2025 12:22:02","29-03-2025=
 16:06:02","Grid outage, Site went down because Gen overload (15kva, 250A) =
SS IHS Felix Zambe is informed // GRid power return","Hyemafo Gildas","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid out=
age, Site went down because Gen overload (15kva, 250A) SS IHS Felix Zambe i=
s informed // GRid power return","rouselle.schoune@ihstowers.com","186","29=
-03-2025 12:25:07","MATECH CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0004682938","Mvo=
g Betsi Hospital","","29-03-2025 11:52:09","29-03-2025 11:31:04","29-03-202=
5 13:20:13","Grid fluctuations,DG turned until fuel shortage // Eneo return=
, refueling ongoing","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Die=
sel Outage","Grid fluctuations,DG turned until fuel shortage // Eneo return=
, refueling ongoing","rouselle.schoune@ihstowers.com","1265","29-03-2025 11=
:52:09","MATECH CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0004682919","Cit=
e des nations","","29-03-2025 11:48:50","29-03-2025 11:03:35","29-03-2025 1=
4:25:35","Grid only, site down due to 1/3 rectifier faulty //  rectifier is=
sue resolved","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Grid only, site down due to 1/3 rectifier faulty //  rectifie=
r issue resolved","rouselle.schoune@ihstowers.com","2716","29-03-2025 11:48=
:50","MATECH CMR"
"Closed Complete","Site Down","T0051","IHS_YND_297","NOCINC0004682900","Mes=
sassi","","29-03-2025 11:45:52","29-03-2025 11:03:47","29-03-2025 14:06:47"=
,"Eneo outage, Site Down due to fuel shortage// refueling Done","Fabrice Po=
uakam","Fuel Outage","Passive","Diesel","Diesel Outage","Eneo outage, Site =
Down due to fuel shortage// refueling Done","rouselle.schoune@ihstowers.com=
","2526","29-03-2025 11:45:52","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004682887","Aka=
k-Nkozoa-MTN-IHS","","29-03-2025 11:44:46","29-03-2025 11:03:33","29-03-202=
5 14:06:33","Eneo outage, Site Down due to fuel shortage// refueling Done",=
"Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Eneo ou=
tage, Site Down due to fuel shortage// refueling Done","rouselle.schoune@ih=
stowers.com","2475","29-03-2025 11:44:46","MATECH CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004682874","MEH=
ANDAN","","29-03-2025 11:43:37","29-03-2025 10:45:31","29-03-2025 15:01:31"=
,"","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficient rectifiers on site//site stabilise=
d","rouselle.schoune@ihstowers.com","3487","29-03-2025 11:43:37","MATECH CM=
R"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0004682627","Car=
refour Ayissi Ele","","29-03-2025 11:05:28","29-03-2025 10:11:17","29-03-20=
25 14:09:17","No power issue site on solar with U=3D53v Gregroire(652070658=
) from Huawei is informed","Parker Tchoup","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on solar with U=3D53v Gregroire(652070658) from Huawei is informed","rousel=
le.schoune@ihstowers.com","3252","29-03-2025 11:05:28","MATECH CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0004682598","Nko=
langaa","","29-03-2025 11:04:27","29-03-2025 10:13:18","30-03-2025 01:09:16=
","Active//No power issue on site Ubaie =3D53V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed. ","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue on site Ubaie =3D53V site on Grid The TX FME Henri (699=
949693) from Huawei is informed. ","rouselle.schoune@ihstowers.com","3070",=
"29-03-2025 11:04:27","MATECH CMR"
"Closed Complete","Site Down","T1739","IHS_YND_691","NOCINC0004682586","Mba=
lla 2 REGIE","","29-03-2025 11:01:12","29-03-2025 09:30:57","29-03-2025 11:=
19:57","Grid outage.gen ran until fuel shortage//Refueling done","Delor Tel=
ezing","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ra=
n until fuel shortage//Refueling done","rouselle.schoune@ihstowers.com","54=
16","29-03-2025 11:01:12","MATECH CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0004682549","M=
beng","IHS_YND_553","29-03-2025 10:53:59","26-03-2025 14:53:27","26-03-2025=
 16:10:27","","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage=
","Fuel shortage // Refueling done","kouoh.jean@ihstowers.com","244833","29=
-03-2025 10:53:59","MATECH CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0004682528","A=
bom","","29-03-2025 10:50:44","29-03-2025 10:32:25","29-03-2025 11:25:46","=
No power issue Ubaie:52.7V site on Grid. Symphorien(691316854/Huawei ) is i=
nformed.","Siligap Boris","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue Ubaie:52.7V site on Gr=
id. Symphorien(691316854/Huawei ) is informed.","stephane.nkamwa@ihstowers.=
com","1100","29-03-2025 10:50:44","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004682511","S=
AA 2","","29-03-2025 10:48:16","29-03-2025 10:09:08","29-03-2025 15:06:53",=
"Grid outage,Site went down because Gen failed to start due to Grid bad vol=
tage//He bypassed the Grid and site on Gen","Parker Tchoup","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Grid outage,Site=
 went down because Gen failed to start due to Grid bad voltage//He bypassed=
 the Grid and site on Gen","stephane.nkamwa@ihstowers.com","2349","29-03-20=
25 10:48:16","MATECH CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0004682509","M=
VAN SACEL","","29-03-2025 10:48:02","27-03-2025 16:50:07","27-03-2025 17:52=
:06","","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down due to insufficiency of rectifiers on site SS IHS =
Pascaline is confirm // Grid return","kouoh.jean@ihstowers.com","151075","2=
9-03-2025 10:48:02","MATECH CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0004682491","M=
VAN SACEL","","29-03-2025 10:45:36","26-03-2025 15:41:15","26-03-2025 16:29=
:54","","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down due to insufficiency of rectifiers on site SS IHS =
Pascaline is confirm // Grid return","kouoh.jean@ihstowers.com","241461","2=
9-03-2025 10:45:36","MATECH CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0004682485","M=
vog-Ebanda","","29-03-2025 10:44:00","29-03-2025 10:31:51","29-03-2025 18:2=
6:00","no power issue on site Ubaie =3D51.5V site on Grid. Symphorien(69131=
6854) from Huawei is working on site","Siligap Boris","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power =
issue on site Ubaie =3D51.5V site on Grid. Symphorien(691316854) from Huawe=
i is working on site","stephane.nkamwa@ihstowers.com","730","29-03-2025 10:=
44:00","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004682463","E=
koumdoum","","29-03-2025 10:39:33","26-03-2025 14:02:44","26-03-2025 16:38:=
23","","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High=
 Engine Temp - Clogged Radiator","Grid outage.gen start and stopped due to =
high temp alarm//We add water and gen manually started ","kouoh.jean@ihstow=
ers.com","247009","29-03-2025 10:39:33","MATECH CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0004682455","C=
arrefourt Nkomo","","29-03-2025 10:36:57","29-03-2025 10:19:53","30-03-2025=
 11:04:41","No power issue on site Ubay: 53.4V site Grid, Lionel Adjex (655=
184876/Huawei) is informed","Mba Lazare Herve","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site Ubay: 53.4V site Grid, Lionel Adjex (655184876/Huawei) is informed",=
"stephane.nkamwa@ihstowers.com","1025","29-03-2025 10:36:57","MATECH CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0004682452","N=
koa Ayos","","29-03-2025 10:35:15","29-03-2025 10:05:00","29-03-2025 11:59:=
43","eneo bad phases, the GEN failed to start.  // Eneo shut down and site =
manually put on GEN","MINKA NICOLAS","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Incomplete Phase","eneo bad phases, the GEN failed to start.=
  // Eneo shut down and site manually put on GEN","stephane.nkamwa@ihstower=
s.com","1816","29-03-2025 10:35:15","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004682449","N=
kolondom","","29-03-2025 10:34:12","28-03-2025 16:34:38","28-03-2025 16:55:=
38","","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-=
AMF Issue","Site went down because gen failed to start due to grid bad volt=
age and ATS malfunction // He reset ATS, Grid return","kouoh.jean@ihstowers=
.com","64776","29-03-2025 10:34:12","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004682441","N=
kolondom","","29-03-2025 10:32:57","27-03-2025 03:33:56","27-03-2025 06:56:=
59","","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-=
AMF Issue","te went down because gen failed to start due to grid bad voltag=
e and ATS malfunction // He reset ATS, Grid return","kouoh.jean@ihstowers.c=
om","197941","29-03-2025 10:32:57","MATECH CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0004682435","M=
VAN SACEL","","29-03-2025 10:32:13","29-03-2025 10:01:53","29-03-2025 12:16=
:33","Site went down due to insufficient rectifier on site//He reset the it=
","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficient rectifier on site//He reset the it",=
"stephane.nkamwa@ihstowers.com","1821","29-03-2025 10:32:13","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004682416","N=
kolondom","","29-03-2025 10:28:08","26-03-2025 14:45:55","26-03-2025 15:45:=
39","","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation, Site went down because Gen failed=
 to start due to Grid bad voltage and No RCP on site // He bypassed the Gri=
d and Gen manually started","kouoh.jean@ihstowers.com","243733","29-03-2025=
 10:28:08","MATECH CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004682127","Tou=
ring Club International","","29-03-2025 09:52:04","29-03-2025 08:55:45","29=
-03-2025 12:00:45","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed // Grid return","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went down=
 because Gen overload (20Kw, 270A) SS IHS Pascaline confirmed // Grid retur=
n","rouselle.schoune@ihstowers.com","3380","29-03-2025 09:52:04","MATECH CM=
R"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004682126","O=
mnisport 3","","29-03-2025 09:52:03","27-03-2025 10:37:51","27-03-2025 21:4=
4:08","","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to insufficiency of rectifiers on site SS IH=
S Blaise Pascale is inform // He reduced the load","kouoh.jean@ihstowers.co=
m","170053","29-03-2025 09:52:03","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004682101","A=
wae Escalier","","29-03-2025 09:47:25","29-03-2025 09:03:07","29-03-2025 11=
:43:14","Grid outage,Site went down before Gen started due to Poor battery =
backup //He start the Gen manuallly","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage,Site went=
 down before Gen started due to Poor battery backup //He start the Gen manu=
allly","stephane.nkamwa@ihstowers.com","2659","29-03-2025 09:47:25","MATECH=
 CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004682083","MONTEE N=
KONDENGUI","","29-03-2025 09:45:49","29-03-2025 09:00:01","29-03-2025 10:52=
:35","Cascaded Incident from TTO4767212","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Cascaded Incident from TTO476=
7212","system","320601","29-03-2025 09:45:49","MATECH CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004682080","M=
obil-Kondengui","IHS_YND_682","29-03-2025 09:45:13","29-03-2025 09:00:01","=
29-03-2025 11:45:36","Grid outage // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage // Grid return","=
stephane.nkamwa@ihstowers.com","2713","29-03-2025 09:45:13","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_691","NOCINC0004682042","Mballa 2=
 REGIE","","29-03-2025 09:40:26","26-03-2025 20:12:49","27-03-2025 02:15:44=
","Cascaded Incident from TTO4767152","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to insuffici=
ency of rectifiers on site SS IHS Blaise Pascale is inform // He reduced th=
e load","system","481718","29-03-2025 09:40:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_135","NOCINC0004682043","Nlongkak=
","","29-03-2025 09:40:26","26-03-2025 20:12:49","27-03-2025 02:15:44","Cas=
caded Incident from TTO4767152","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to insufficiency o=
f rectifiers on site SS IHS Blaise Pascale is inform // He reduced the load=
","system","481718","29-03-2025 09:40:26","MATECH CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004682025","O=
mnisport 3","IHS_YND_691, IHS_YND_135","29-03-2025 09:36:15","26-03-2025 20=
:12:49","27-03-2025 02:15:44","","Delor Telezing","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to insufficiency of =
rectifiers on site SS IHS Blaise Pascale is inform // He reduced the load",=
"kouoh.jean@ihstowers.com","221007","29-03-2025 09:36:15","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004681991","AWAE OCM=
","","29-03-2025 09:27:58","28-03-2025 21:01:35","28-03-2025 22:04:04","Cas=
caded Incident from TTO4764420","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC dysfonction // He reset the PWC, grid return","=
system","363612","29-03-2025 09:27:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004681898","MEHANDAN=
","","29-03-2025 09:09:07","28-03-2025 15:02:01","29-03-2025 05:22:23","","=
Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to insufficient rectifiers on site//site stabilised","k=
ouoh.jean@ihstowers.com","65226","29-03-2025 09:09:07","MATECH CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004681859","M=
imboman-Village","","29-03-2025 09:02:54","29-03-2025 08:29:35","29-03-2025=
 18:06:02","Grid outage site went down because Gen failed to start due PWC =
dysfonction // He reset the PWC and Gen manually started","Mba Lazare Herve=
","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","G=
rid outage site went down because Gen failed to start due PWC dysfonction /=
/ He reset the PWC and Gen manually started","stephane.nkamwa@ihstowers.com=
","2001","29-03-2025 09:02:54","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004681856","M=
essa-Carriere OCM","","29-03-2025 09:01:54","29-03-2025 08:09:33","29-03-20=
25 15:46:55","No power issue on site. Ubaie:52,1V site on Grid,  Mahamado (=
691144435/Huawei) is informed.","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site. Ubai=
e:52,1V site on Grid,  mohamado Huawei is informed.","stephane.nkamwa@ihsto=
wers.com","3142","29-03-2025 09:01:54","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004681854","MEHANDAN=
","","29-03-2025 09:00:55","26-03-2025 18:59:35","27-03-2025 07:57:51","Cas=
caded Incident from TTO4766887","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Fuel shortage  // Refueling done","sys=
tem","486094","29-03-2025 09:00:55","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0004681831","Mballa 4=
","","29-03-2025 08:56:26","29-03-2025 08:29:56","29-03-2025 09:21:52","Cas=
caded Incident from TTO4766927","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Gen fails to start due t=
o undervoltage alarm/ Gen card reset and manually stared","system","272125"=
,"29-03-2025 08:56:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0004681830","Ekombiti=
e","","29-03-2025 08:56:25","29-03-2025 08:29:56","29-03-2025 09:21:52","Ca=
scaded Incident from TTO4766927","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Gen fails to start due=
 to undervoltage alarm/ Gen card reset and manually stared","system","27212=
5","29-03-2025 08:56:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0004681828","Ekoumdou=
m OCM","","29-03-2025 08:56:25","29-03-2025 08:29:56","29-03-2025 14:25:52"=
,"Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS Pasca=
line is informed and confirmed//We reduce load and gen manually started","A=
lbran Byorel","Unlisted RCA","Others","Others","Others","Site up awaiting f=
eedback","system","1589","29-03-2025 08:56:25","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004681829","Ngoulmek=
ong-Nord","","29-03-2025 08:56:25","29-03-2025 08:29:56","29-03-2025 09:21:=
52","Cascaded Incident from TTO4766927","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Gen fails to star=
t due to undervoltage alarm/ Gen card reset and manually stared","system","=
272126","29-03-2025 08:56:25","MATECH CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0004681823","San=
ta Barbara Yde","IHS_YND_277, IHS_YND_276, IHS_YND_242","29-03-2025 08:55:0=
6","29-03-2025 08:29:56","29-03-2025 09:21:52","Grid outage, Gen fails to s=
tart due to undervoltage alarm/ Gen card reset and manually stared","Delor =
Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, Gen fails to start due to undervoltage alarm/ Gen card reset an=
d manually stared","rouselle.schoune@ihstowers.com","1510","29-03-2025 08:5=
5:06","MATECH CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004681797","Par=
adis Hotel","","29-03-2025 08:47:07","29-03-2025 08:18:59","29-03-2025 13:2=
0:59","Gen stopped  with alarm  under frequency ( fuel leakage) // fuel pip=
e connected correctly and Gen started ","Siligap Boris","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Fuel Leakage","Gen stopped  with alarm  under =
frequency ( fuel leakage) // fuel pipe connected correctly and Gen  started=
=20
","rouselle.schoune@ihstowers.com","1689","29-03-2025 08:47:07","MATECH CMR=
"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004681791","O=
dza II OCM","IHS_YND_528","29-03-2025 08:45:21","26-03-2025 18:59:35","27-0=
3-2025 07:57:51","","Albran Byorel","Fuel Outage","Passive","Diesel","Diese=
l Outage","Fuel shortage  // Refueling done","kouoh.jean@ihstowers.com","22=
2346","29-03-2025 08:45:21","MATECH CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004681755","A=
wae Ewonkan","","29-03-2025 08:38:28","26-03-2025 18:46:44","26-03-2025 20:=
04:22","","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen overload(20KVA,310A) SS I=
HS Alphonse DEFFO is informed//We reduce load and gen manually started ","k=
ouoh.jean@ihstowers.com","222704","29-03-2025 08:38:28","MATECH CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004681737","M=
ontesquieux","","29-03-2025 08:32:43","29-03-2025 07:44:17","29-03-2025 08:=
59:12","site down due to 1/4 rectifiers faulty // rectifiers replaced, site=
 on Grid","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier=
 Cabinet","site down due to 1/4 rectifiers faulty // rectifiers replaced, s=
ite on Grid","stephane.nkamwa@ihstowers.com","2907","29-03-2025 08:32:43","=
MATECH CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004681733","M=
vog-Ada_OCM","","29-03-2025 08:31:59","29-03-2025 07:44:38","29-03-2025 11:=
59:23","Grid outage,no space to deploy a mobil gen//grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no=
 space to deploy a mobil gen//grid return","stephane.nkamwa@ihstowers.com",=
"2842","29-03-2025 08:31:59","MATECH CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0004681719","T=
radex-Nkomo","","29-03-2025 08:29:37","29-03-2025 07:26:14","29-03-2025 08:=
02:57","Site went down because gen start an stopped due to water mixed fuel=
 // He purged and Gen manually started","Albran Byorel","Fuel Outage (Proba=
ble)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","Site wen=
t down because gen start an stopped due to water mixed fuel // He purged an=
d Gen manually started","stephane.nkamwa@ihstowers.com","3804","29-03-2025 =
08:29:37","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004681703","F=
ouda-New","","29-03-2025 08:25:25","29-03-2025 06:56:00","29-03-2025 12:03:=
58","","Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage gen ran until fuel shortage//Refueling done","stephane.nkamwa@ih=
stowers.com","5366","29-03-2025 08:25:25","MATECH CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0004681700","Mam=
ch Building","","29-03-2025 08:24:04","29-03-2025 08:12:59","30-03-2025 01:=
46:48","Grid outage .site went down due to gen failed to start //Grid retur=
n (investigation ongoing)","Mboua Thierry","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage .site went down due to gen fail=
ed to start //Grid return (investigation ongoing)","rouselle.schoune@ihstow=
ers.com","666","29-03-2025 08:24:04","MATECH CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0004681689","San=
ta Barbara Gottam","","29-03-2025 08:21:48","29-03-2025 07:50:40","29-03-20=
25 10:41:40","Grid outage, Site went down because Gen failed to start with =
""overcurrent"" alarm// He reset Gen card and started Gen manually","Delor =
Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, Site went down because Gen failed to start with ""overcurrent""=
 alarm// He reset Gen card and started Gen manually","rouselle.schoune@ihst=
owers.com","1869","29-03-2025 08:21:48","MATECH CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0004681622","Nko=
mo stade","","29-03-2025 08:04:24","29-03-2025 07:06:14","29-03-2025 18:22:=
14","No power issue site on grid with U=3D54V Flubert from Huawei is inform=
ed","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D54V=
 Flubert from Huawei is informed","rouselle.schoune@ihstowers.com","3490","=
29-03-2025 08:04:24","MATECH CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004681608","Ngo=
usso Vallee","","29-03-2025 08:00:34","29-03-2025 06:55:26","29-03-2025 13:=
22:26","Eneo outage, GE did not start because of the GE card left in stop m=
ode by the APS agent // GE put back in auto mode","Siligap Boris","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Eneo outage, GE did =
not start because of the GE card left in stop mode by the APS agent // GE p=
ut back in auto mode
","rouselle.schoune@ihstowers.com","3908","29-03-2025 08:00:34","MATECH CMR=
"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004681606","Awa=
e Ewonkan","","29-03-2025 07:59:32","29-03-2025 06:47:23","29-03-2025 14:16=
:23","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed//We reduce load and gen manually started","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage, Site went down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO=
 is informed//We reduce load and gen manually started","rouselle.schoune@ih=
stowers.com","4330","29-03-2025 07:59:32","MATECH CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004681484","AWA=
E OCM","","29-03-2025 07:21:10","29-03-2025 06:35:57","29-03-2025 07:31:37"=
,"","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier =
Module Overloaded","Grid outage, site went down before gen start due to poo=
r battery backup // Gen start automatically","rouselle.schoune@ihstowers.co=
m","2714","29-03-2025 07:21:10","MATECH CMR"
"Closed Complete","Site Down","T1549","IHS_YND_295","NOCINC0004681454","NGO=
NA","","29-03-2025 07:10:20","29-03-2025 06:58:14","29-03-2025 10:42:14","G=
rid outage,site went down because Gen failed to start due to battery ge dis=
charge //he started with an external battery","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage,site =
went down because Gen failed to start due to battery ge discharge //he star=
ted with an external battery","rouselle.schoune@ihstowers.com","727","29-03=
-2025 07:10:20","MATECH CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004681441","Nko=
abang2","","29-03-2025 07:06:58","29-03-2025 06:59:51","29-03-2025 08:53:51=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","rouselle=
.schoune@ihstowers.com","428","29-03-2025 07:06:58","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004681422","B=
iteng-Maetur","","29-03-2025 07:02:41","29-03-2025 06:33:04","29-03-2025 08=
:48:04","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the=
 load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen started and stopped due t=
o Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced th=
e load","stephane.nkamwa@ihstowers.com","2771","29-03-2025 07:02:41","MATEC=
H CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004681337","M=
EHANDAN","","29-03-2025 06:43:39","29-03-2025 06:33:24","29-03-2025 08:29:1=
6","","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Site went down due to insufficient rectifiers on site//site stabili=
sed","stephane.nkamwa@ihstowers.com","617","29-03-2025 06:43:39","MATECH CM=
R"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004680847","Sim=
bock MTN","","29-03-2025 04:32:26","29-03-2025 04:31:51","29-03-2025 07:05:=
51","Grid outage.site went down due to gen failed to start //Grid return(in=
vestigation ongoing)","Fanda Brice","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage.site went down due to gen failed to st=
art //Grid return(investigation ongoing)","kamga.virgile@ihstowers.com","36=
","29-03-2025 04:32:26","MATECH CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0004680682","M=
VAN SACEL","","29-03-2025 02:47:57","26-03-2025 18:06:55","27-03-2025 00:40=
:55","","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down because 01/06 rectifiers went faulty// He removed =
rectifier faulty(site on 05)","kouoh.jean@ihstowers.com","204062","29-03-20=
25 02:47:57","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004680641","A=
wae Escalier","","29-03-2025 02:25:56","26-03-2025 17:08:29","26-03-2025 21=
:39:29","","Albran Byorel","Equipment Repair","Passive","Control Panel","AT=
S-AMF Issue","Grid outage, site went down because gen failed to start due t=
o grid contactor faulty // He bypassed it and Gen manually started","kouoh.=
jean@ihstowers.com","206247","29-03-2025 02:25:56","MATECH CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0004680554","O=
kola OCM","","29-03-2025 01:44:38","26-03-2025 16:35:15","27-03-2025 11:23:=
48","Grid outage gen ran until fuel shortage//Refueling done","TIENTCHEU NZ=
ETCHIEU GAEL","Unlisted RCA","Others","Others","Others","RCA awaited from m=
atech","kouoh.jean@ihstowers.com","205764","29-03-2025 01:44:38","MATECH CM=
R"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004680408","E=
vodoula OCM","","29-03-2025 00:46:51","26-03-2025 15:53:38","26-03-2025 21:=
53:38","Grid outage gen ran until fuel shortage//Refueling done ","TIENTCHE=
U NZETCHIEU GAEL","Unlisted RCA","Others","Others","Others","RCA awaied fro=
m Matech","kouoh.jean@ihstowers.com","204794","29-03-2025 00:46:51","MATECH=
 CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004680395","N=
koabang Ebolmedjock","","29-03-2025 00:36:56","26-03-2025 14:03:03","26-03-=
2025 14:06:03","Active//No power issue, Site on Gen. The Tx FME Brice Tsagu=
e(650214096) from Huawei is informed. Notice that it is impacted by Nkolmes=
seng-Abom Not Manager By IHS","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","Active=
//No power issue, Site on Gen. The Tx FME Brice Tsague(650214096) from Huaw=
ei is informed. Notice that it is impacted by Nkolmesseng-Abom Not Manager =
By IHS","kouoh.jean@ihstowers.com","210834","29-03-2025 00:36:56","MATECH C=
MR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004680114","M=
ontee-Des-Soeurs","","28-03-2025 23:16:17","28-03-2025 22:51:08","28-03-202=
5 23:00:30","No power Issue Site on Grid Ubai =3D54.3 V. The TX FME Mbah Ho=
siah (674007438) is informed","Hyemafo Gildas","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power Issue S=
ite on Grid Ubai =3D54.3 V. The TX FME Mbah Hosiah (674007438) is informed"=
,"alexandre.kamal@ihstowers.com","1510","28-03-2025 23:16:17","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004679956","Essomba"=
,"","28-03-2025 22:18:24","28-03-2025 21:01:35","28-03-2025 22:04:04","Casc=
aded Incident from TTO4764420","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due PWC dysfonction // He reset the PWC, grid return","s=
ystem","363612","28-03-2025 22:18:24","MATECH CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004679890","Lad=
a I Yde","","28-03-2025 22:02:27","28-03-2025 21:58:20","29-03-2025 14:18:2=
0","Grid outage, Site went down because Gen failed to start for unknow reas=
en// Grid return ","Mba Lazare Herve","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage, Site went down because Gen failed t=
o start for unknow reasen// Grid return ","landry.etame@ihstowers.com","248=
","28-03-2025 22:02:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004679713","Angongo"=
,"","28-03-2025 21:29:17","28-03-2025 21:09:45","28-03-2025 22:04:45","Casc=
aded Incident from TTO4764554","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site was on Gen due to Grid outage, Site =
went down because Gen stopped with ""High temp ""alarm // He added water an=
d manually start the Gen","system","377546","28-03-2025 21:29:17","MATECH C=
MR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004679703","E=
beba","IHS_YND_335","28-03-2025 21:27:53","28-03-2025 21:09:45","28-03-2025=
 22:04:45","Site was on Gen due to Grid outage, Site went down because Gen =
stopped with ""High temp ""alarm // He added water and manually start the G=
en","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engi=
ne Temp - Coolant Level Issue","Site was on Gen due to Grid outage, Site we=
nt down because Gen stopped with ""High temp ""alarm // He added water and =
manually start the Gen","kouoh.jean@ihstowers.com","1088","28-03-2025 21:27=
:53","MATECH CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004679590","B=
iteng","IHS_YND_292, IHS_YND_173, IHS_YND_179","28-03-2025 21:04:42","28-03=
-2025 21:01:35","28-03-2025 22:04:04","","Mba Lazare Herve","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down beca=
use Gen failed to start due PWC dysfonction // He reset the PWC, grid retur=
n","kouoh.jean@ihstowers.com","102519","28-03-2025 21:04:42","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004679583","B=
iteng-Maetur","","28-03-2025 21:03:38","28-03-2025 20:34:11","28-03-2025 22=
:53:03","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the=
 load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen started and stopped due t=
o Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced th=
e load","kouoh.jean@ihstowers.com","1768","28-03-2025 21:03:38","MATECH CMR=
"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004679469","Ole=
mbe MTN","","28-03-2025 20:46:29","28-03-2025 20:42:23","28-03-2025 20:58:2=
3","Site went down due to insufficiency of rectifiers on site SS IHS felix =
Zambe is informed//site stabilized(need to add 01 rectifier)","Fabrice Poua=
kam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went=
 down due to insufficiency of rectifiers on site SS IHS felix Zambe is info=
rmed//site stabilized(need to add 01 rectifier)","landry.etame@ihstowers.co=
m","247","28-03-2025 20:46:29","MATECH CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0004679448","Bit=
oto","","28-03-2025 20:41:10","28-03-2025 20:27:05","28-03-2025 21:27:05","=
No power issue on site. Ubaie =3D 56,35V on GRID. Henry (691145055/Tele inf=
ra) is informed ","Mba Lazare Herve","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site. Ub=
aie =3D 56,35V on GRID. Henry (691145055/Tele infra) is informed ","landry.=
etame@ihstowers.com","846","28-03-2025 20:41:10","MATECH CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0004679429","M=
atomb","","28-03-2025 20:34:19","28-03-2025 19:43:52","28-03-2025 19:46:52"=
,"site Down due to Relais faulty // Site put on Gen ","Kemeni Franklin","Eq=
uipment Repair","Passive","Control Panel","Relay","site Down due to Relais =
faulty // Site put on Gen=20
","kouoh.jean@ihstowers.com","3028","28-03-2025 20:34:19","MATECH CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004679179","Nko=
g-Edzen","","28-03-2025 20:04:46","28-03-2025 19:51:40","28-03-2025 20:51:4=
0","No power issue on site, site on Gen with U=3D54v  The Tx Fme Gregoire (=
654547479) from Huawei is informed.","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site, site on Gen with U=3D54v  The Tx Fme Gregoire (654547479) fro=
m Huawei is informed.","landry.etame@ihstowers.com","787","28-03-2025 20:04=
:46","MATECH CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0004678789","O=
lezoa OCM","","28-03-2025 18:56:38","28-03-2025 13:16:30","29-03-2025 00:13=
:40","Grid outage,no space to deploy MDG//Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage,no space to =
deploy MDG//Grid return","kouoh.jean@ihstowers.com","20409","28-03-2025 18:=
56:38","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_165","NOCINC0004678772","Ahala","=
","28-03-2025 18:52:35","28-03-2025 14:42:52","28-03-2025 14:50:52","Cascad=
ed Incident from TTO4762491","MINKA NICOLAS","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on grid with U=3D54.4v M=
bah Osiah from Huawei is informed","system","307121","28-03-2025 18:52:35",=
"MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004678763","S=
atcom","","28-03-2025 18:50:14","28-03-2025 17:11:59","28-03-2025 17:20:05"=
,"ACTIVE No power issue on site U=3D 52,7V site on grid the TX fme Lionnel =
Steve / 655184876 from huawei is informed","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACT=
IVE No power issue on site U=3D 52,7V site on grid the TX fme Lionnel Steve=
 / 655184876 from huawei is informed","kouoh.jean@ihstowers.com","5896","28=
-03-2025 18:50:14","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004678741","M=
EHANDAN","","28-03-2025 18:46:07","28-03-2025 14:06:38","28-03-2025 14:57:1=
9","Site went down due to insufficient rectifiers on site//site stabilised"=
,"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficient rectifiers on site//site stabilised",=
"kouoh.jean@ihstowers.com","68225","28-03-2025 18:46:07","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0004678709","Mes=
sassi Ngonlonk","","28-03-2025 18:41:10","28-03-2025 18:19:02","28-03-2025 =
23:14:31","Grid outage,Site went down because Gen failed to start due to Gr=
id contactor not excited //He excited and Grid return","Fabrice Pouakam","E=
quipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,Sit=
e went down because Gen failed to start due to Grid contactor not excited /=
/He excited and Grid return","landry.etame@ihstowers.com","1329","28-03-202=
5 18:41:10","MATECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004678670","HOP=
ITAL GENERAL RAIL YDE","","28-03-2025 18:34:16","28-03-2025 18:28:10","29-0=
3-2025 05:35:14","Grid outage, site went down due to gen Overload(09kva,160=
A), Bernard IHS is informed // Grid return","Delor Telezing","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down du=
e to gen Overload(09kva,160A), Bernard IHS is informed // Grid return","lan=
dry.etame@ihstowers.com","367","28-03-2025 18:34:16","MATECH CMR"
"Closed Complete","Site Down","CTR_481","IHS_YND_574","NOCINC0004678611","C=
rf-Mbankolo-IHS","","28-03-2025 18:12:49","28-03-2025 16:36:20","28-03-2025=
 19:59:46","insufficient rectifierFME is on the way ETA 7:15 PM","Mboua Thi=
erry","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","Site we=
nt down due to MPR disfunction SS IHS Bernard Atangana confirmed//Site stab=
ilized with power reset done","kouoh.jean@ihstowers.com","5790","28-03-2025=
 18:12:49","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_583","NOCINC0004678603","Nsam Sof=
avinc T0","","28-03-2025 18:11:08","28-03-2025 14:42:52","28-03-2025 14:50:=
52","Cascaded Incident from TTO4762491","MINKA NICOLAS","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Cascaded Incident from TTO4762491=
","system","307121","28-03-2025 18:11:08","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004678598","S=
AA 2","","28-03-2025 18:10:17","28-03-2025 17:52:00","28-03-2025 18:58:37",=
"Site went down due to 02/03 rectifiers dysunctionning//He reset it ","Park=
er Tchoup","Equipment Repair","Passive","Rectifier","Rectifier Module","Sit=
e went down due to 02/03 rectifiers dysunctionning//He reset it ","kouoh.je=
an@ihstowers.com","1098","28-03-2025 18:10:17","MATECH CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004678561","S=
AA 2","","28-03-2025 18:05:18","27-03-2025 03:51:00","27-03-2025 07:39:00",=
"Site went down because rectifier disfunctionning // He reset it: Site on g=
rid","Parker Tchoup","Unlisted RCA","Others","Others","Others","RCA awaited=
 from MATECH","kouoh.jean@ihstowers.com","137660","28-03-2025 18:05:18","MA=
TECH CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004678497","Emana Ly=
cee","","28-03-2025 17:52:08","28-03-2025 17:02:57","28-03-2025 19:31:57","=
Cascaded Incident from TTO4763138","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","RCA Awaited from MATECH","system"=
,"370791","28-03-2025 17:52:08","MATECH CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004678476","E=
mana lycee 2","IHS_YND_274","28-03-2025 17:49:30","28-03-2025 17:02:57","28=
-03-2025 19:31:57","Grid outage , site went down before Gen started due to =
poor battery backup//Gen started manualy","Fabrice Pouakam","Unlisted RCA",=
"Others","Others","Others","RCA Awaited from MATECH","kouoh.jean@ihstowers.=
com","2794","28-03-2025 17:49:30","MATECH CMR"
"Closed Complete","Warning","T0341","IHS_YND_270","NOCINC0004678441","Santa=
 Barbara Yde","","28-03-2025 17:44:15","","","eneo outage // eneo return","=
Delor Telezing","Warning","Warning","POWER","Warning - Site on Battery","en=
eo outage // eneo return","gerard.tchangoue@matech-cameroun.com","4840","28=
-03-2025 17:44:15","MATECH CMR"
"Closed Complete","Site Down","CTR_525","IHS_YND_544","NOCINC0004678379","J=
ean Vespa 2","","28-03-2025 17:39:06","28-03-2025 16:49:53","28-03-2025 17:=
55:56","Grid outage,gen ran till fuel shortage//Refueling done","Mboua Thie=
rry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran =
till fuel shortage//Refueling done","kouoh.jean@ihstowers.com","2954","28-0=
3-2025 17:39:06","MATECH CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004678357","Mam=
bine","","28-03-2025 17:35:11","28-03-2025 17:27:49","28-03-2025 18:46:34",=
"Grid outage, Site went down because Gen started and stopped due to Hybrid =
System disfunction//He reset and manualy start the Gen","Fanda Brice","Equi=
pment Repair","Passive","Hybrid","Hybrid Module","Grid outage, Site went do=
wn because Gen started and stopped due to Hybrid System disfunction//He res=
et and manualy start the Gen","landry.etame@ihstowers.com","442","28-03-202=
5 17:35:11","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004678348","M=
essassi okolo","","28-03-2025 17:33:26","28-03-2025 16:24:18","28-03-2025 1=
9:40:07","Grid outage , site went down before Gen started due to poor batte=
ry backup // Gen Manually started","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage , site we=
nt down before Gen started due to poor battery backup // Gen Manually start=
ed","kouoh.jean@ihstowers.com","4149","28-03-2025 17:33:26","MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004678258","M=
essassi 2","","28-03-2025 17:22:31","28-03-2025 16:12:45","28-03-2025 20:09=
:03","Grid gen site ,   Rectifier issue / Rectifier remplacement ongoing","=
Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Rectifier Ba=
ttery Breaker Faulty","Grid gen site ,   Rectifier issue / Rectifier rempla=
cement ongoing","kouoh.jean@ihstowers.com","4188","28-03-2025 17:22:31","MA=
TECH CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004678126","Nko=
lnda","IHS_YND_385, IHS_YND_528, IHS_YND_410, IHS_YND_595, IHS_EBO_015, IHS=
_YND_411","28-03-2025 17:09:51","28-03-2025 17:01:47","28-03-2025 18:01:47"=
,"No power issue on site. Ubaie:54V site Grid,  Lionnel Ajep(655184876/ Hua=
wei) is informed.","Albran Byorel","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site. Ubai=
e:54V site Grid,  Lionnel Ajep(655184876/ Huawei) is informed.","landry.eta=
me@ihstowers.com","485","28-03-2025 17:09:51","MATECH CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0004678124","A=
RMP","","28-03-2025 17:09:35","28-03-2025 16:19:43","28-03-2025 18:03:33","=
Grid Outage //Grid return","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","Grid Outage //Grid return","kouoh.jean@ihstowers.com=
","2993","28-03-2025 17:09:35","MATECH CMR"
"Closed Complete","Site Down","CTR_115","IHS_YND_375","NOCINC0004678088","N=
goung","","28-03-2025 17:03:18","28-03-2025 16:40:57","28-03-2025 17:32:59"=
,"Site went down because Gen failed to start due to Grid bad voltage//He by=
passed the Grid and site on GEN","Kemeni Franklin","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Site went down because Ge=
n failed to start due to Grid bad voltage//He bypassed the Grid and site on=
 GEN","kouoh.jean@ihstowers.com","1342","28-03-2025 17:03:18","MATECH CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004678020","Oko=
lo Kilombo","","28-03-2025 16:52:06","28-03-2025 16:35:59","28-03-2025 19:3=
1:49","Grid outage, site went down because gen fails to start due to Gen ca=
ble faulty // He bypassed gen cable and gen manually started","Fabrice Poua=
kam","Equipment Repair","Passive","Infrastructure","Armoured Cable","Grid o=
utage, site went down because gen fails to start due to Gen cable faulty //=
 He bypassed gen cable and gen manually started","landry.etame@ihstowers.co=
m","968","28-03-2025 16:52:06","MATECH CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0004677893","Dra=
gage","","28-03-2025 16:46:15","28-03-2025 16:36:08","28-03-2025 20:05:56",=
"Active//No power issue, site is on Gen with Ubaie=3D5.1 V, Eloundou bertra=
nt(652586578) from Huawei is informed","Mboua Thierry","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue, site is on Gen with Ubaie=3D50 V, Eloundou bertrant(6525865=
78) from Huawei is informed","landry.etame@ihstowers.com","608","28-03-2025=
 16:46:15","MATECH CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0004677884","E=
BOM","IHS_YND_583, IHS_YND_165","28-03-2025 16:43:05","28-03-2025 14:42:52"=
,"28-03-2025 14:50:52","","Hyemafo Gildas","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on grid with U=3D54.4v Mbah Osiah from Huawei is informed","kouoh.jean@ihst=
owers.com","7214","28-03-2025 16:43:05","MATECH CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004677882","Bas=
tos-BAT","","28-03-2025 16:42:46","28-03-2025 16:29:08","28-03-2025 21:10:3=
3","Active// No power issue, site is on grid with Ubaie=3D54,9 V The Tx Fme=
, Eloundou(652586578) from Huawei is informed","Mboua Thierry","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power issue, site is on grid with Ubaie=3D54,9 V The Tx Fme, El=
oundou(652586578) from Huawei is informed","landry.etame@ihstowers.com","81=
8","28-03-2025 16:42:46","MATECH CMR"
"Closed Complete","Site Down","T0772","IHS_YND_207","NOCINC0004677878","ARM=
P Building","","28-03-2025 16:41:38","28-03-2025 16:29:29","28-03-2025 17:0=
7:04","Site went down due to rectifiers dysfunctionning //Reset rectifiers =
and site on grid.","Mboua Thierry","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to rectifiers dysfunctionning //Res=
et rectifiers and site on grid.","landry.etame@ihstowers.com","729","28-03-=
2025 16:41:38","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004677827","A=
WAE OCM","","28-03-2025 16:31:58","28-03-2025 15:57:10","28-03-2025 20:42:1=
0","Grid outage, Site went down because Gen failed to start due to PWC dysf=
unctionning// He reset PWC, Site on Grid","Mba Lazare Herve","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, Site=
 went down because Gen failed to start due to PWC dysfunctionning// He rese=
t PWC, Site on Grid","kouoh.jean@ihstowers.com","13507","28-03-2025 16:31:5=
8","MATECH CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004677805","Nko=
lbong","","28-03-2025 16:28:23","28-03-2025 16:17:17","28-03-2025 16:31:17"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen Started automatically","Delor Telezing","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen Started automatically","=
landry.etame@ihstowers.com","667","28-03-2025 16:28:23","MATECH CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0004677658","M=
atomb","","28-03-2025 15:58:55","28-03-2025 15:48:39","28-03-2025 18:20:06"=
,"Grid outage.gen failed to start due to airintake//We purged and gen manua=
lly started","Kemeni Franklin","Fuel Outage (Probable)","Passive","ACDG Gen=
","ACDG - Air Intake","Grid outage.gen failed to start due to airintake//We=
 purged and gen manually started","kouoh.jean@ihstowers.com","616","28-03-2=
025 15:58:55","MATECH CMR"
"Closed Complete","Warning","T0772","IHS_YND_207","NOCINC0004677644","ARMP =
Building","","28-03-2025 15:57:32","","","eneo outage // eneo return","Mbou=
a Thierry","Warning","Warning","POWER","Warning - Site on Battery","eneo ou=
tage // eneo return","gerard.tchangoue@matech-cameroun.com","1842","28-03-2=
025 15:57:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004677624","Crf-Mban=
kolo-IHS","","28-03-2025 15:56:06","28-03-2025 11:34:58","28-03-2025 16:36:=
19","Cascaded Incident from TTO4760844","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage // MDG deployed","=
system","282362","28-03-2025 15:56:06","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004677614","Omnispor=
t-Rail","","28-03-2025 15:53:45","28-03-2025 15:25:14","28-03-2025 16:29:14=
","Cascaded Incident from TTO4762148","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage , Poor battery back=
up/ Gen started manually","system","340508","28-03-2025 15:53:45","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004677615","Manguier=
","","28-03-2025 15:53:45","28-03-2025 15:25:14","28-03-2025 16:29:14","Cas=
caded Incident from TTO4762148","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage , Poor battery backup/ G=
en started manually","system","340508","28-03-2025 15:53:45","MATECH CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0004677560","Bas=
tos Bir","","28-03-2025 15:45:18","28-03-2025 15:35:13","28-03-2025 18:38:3=
1","Grid outage,gen start and  stopped with alarm high temp//he added water=
 in radiator","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG=
 - High Engine Temp - Coolant Level Issue","Grid outage,gen stopped with al=
arm high temp//he added water in radiator","landry.etame@ihstowers.com","66=
7","28-03-2025 15:45:18","MATECH CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004677510","MAN=
GUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","28-03-2025 15:33:36","28-03-20=
25 15:25:14","28-03-2025 16:29:14","Grid outage , Poor battery backup/ Gen =
started manually","Fabrice Pouakam","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage , Poor battery backup/ Gen=
 started manually","landry.etame@ihstowers.com","503","28-03-2025 15:33:36"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004677331","K=
oweit City","","28-03-2025 15:09:02","28-03-2025 14:27:44","28-03-2025 17:2=
4:09","Grid outage.gen failed to start due to card GE dysfunctionned //We r=
eset card GE and gen manually started","Albran Byorel","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to start=
 due to card GE dysfunctionned //We reset card GE and gen manually started"=
,"kouoh.jean@ihstowers.com","2479","28-03-2025 15:09:02","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004677283","M=
arche Odza","","28-03-2025 15:02:59","28-03-2025 14:05:42","28-03-2025 17:2=
3:02","Fuel shortage// Refueling done","Albran Byorel","Fuel Outage","Passi=
ve","Diesel","Diesel Outage","Fuel shortage// Refueling done","kouoh.jean@i=
hstowers.com","3439","28-03-2025 15:02:59","MATECH CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004677270","ETO=
UDI Entree du palais","","28-03-2025 15:00:20","28-03-2025 14:52:11","28-03=
-2025 21:26:11","Grid outage, Site went down before Gen start due to poor b=
ackup // Gen started manually","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Gen started manually","landry.eta=
me@ihstowers.com","490","28-03-2025 15:00:20","MATECH CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004677117","S=
OA TOWN","","28-03-2025 14:28:37","28-03-2025 07:58:30","28-03-2025 08:10:1=
7","Grid outage, Site went because Gen started and stopped with ""high temp=
"" alarm// He added water and started Gen manually","Siligap Boris","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Grid outage, Site went because Gen started and stopped with ""high t=
emp"" alarm// He added water and started Gen manually","joelle.ekessi@ihsto=
wers.com","23408","28-03-2025 14:28:37","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004676457","Jean Ves=
pa 2","","28-03-2025 12:55:38","28-03-2025 11:34:58","28-03-2025 16:36:19",=
"Cascaded Incident from TTO4760844","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage // MDG deployed","syst=
em","282362","28-03-2025 12:55:38","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004676454","J=
-Vespa","IHS_YND_574, IHS_YND_544","28-03-2025 12:55:03","28-03-2025 11:34:=
58","28-03-2025 16:36:19","","Mboua Thierry","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid outage // MDG deployed","joelle.=
ekessi@ihstowers.com","4806","28-03-2025 12:55:03","MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004676448","C=
omplexe-BEAC","","28-03-2025 12:53:37","28-03-2025 12:33:33","28-03-2025 15=
:12:17","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started manually","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup // Gen started manually","joelle.ekessi@ihstow=
ers.com","1205","28-03-2025 12:53:37","MATECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004676201","HOP=
ITAL GENERAL RAIL YDE","","28-03-2025 12:15:47","27-03-2025 16:23:38","28-0=
3-2025 09:14:25","Grid outage gen run until fuel shortage//refueling done",=
"Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age gen run until fuel shortage//refueling done","christian.fonkou@ihstower=
s.com","71530","28-03-2025 12:15:47","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004676086","B=
iteng-Maetur","","28-03-2025 12:00:02","28-03-2025 10:03:55","28-03-2025 10=
:53:55","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the=
 load","Mba Lazare Herve","Unlisted RCA","Others","Others","Others","RCA aw=
aited from Matech","joelle.ekessi@ihstowers.com","6969","28-03-2025 12:00:0=
2","MATECH CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004676053","Jea=
n Vespa","","28-03-2025 11:52:46","28-03-2025 11:48:33","28-03-2025 17:46:5=
4","Grid outage,gen ran till fuel shortage//Refueling done","Mboua Thierry"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran till=
 fuel shortage//Refueling done","christian.fonkou@ihstowers.com","254","28-=
03-2025 11:52:46","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0004675837","Ema=
na lycee 2","","28-03-2025 11:22:16","28-03-2025 11:16:07","28-03-2025 13:3=
2:27","Grid outage, site went down because gen start and stopped with high =
temp alarm // He added water and manually start the gen","Fabrice Pouakam",=
"Unlisted RCA","Others","Others","Others","RCA Awaited from MATECH","christ=
ian.fonkou@ihstowers.com","370","28-03-2025 11:22:16","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_515","NOCINC0004675502","Etoug eb=
e Meweulo","","28-03-2025 10:35:18","28-03-2025 10:24:14","28-03-2025 16:15=
:06","Grid fluctuation, Site went down because Gen started and stopped due =
to Grid bad voltage//He bypassed Grid and started Gen manually","Hyemafo Gi=
ldas","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, Site went down because Gen started and stopped due t=
o Grid bad voltage//He bypassed Grid and started Gen manually","joelle.ekes=
si@ihstowers.com","665","28-03-2025 10:35:18","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004675346","E=
MANA BILICK CITY","","28-03-2025 10:13:47","28-03-2025 10:04:42","28-03-202=
5 11:39:09","Grid outage.site went down due to gen failed to start //Grid r=
eturn (investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage.site went down due to gen=
 failed to start //Grid return (investigation ongoing)","joelle.ekessi@ihst=
owers.com","546","28-03-2025 10:13:47","MATECH CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004675161","N=
kolondom","","28-03-2025 09:43:08","28-03-2025 09:33:00","28-03-2025 10:18:=
51","Grid fluctuation, Site went down because gen fails to start due to gri=
d bad voltage,// He bypasse the Grid and site on Gen","Fabrice Pouakam","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuation, Site went down because gen fails to start due to grid bad vol=
tage,// He bypasse the Grid and site on Gen","joelle.ekessi@ihstowers.com",=
"609","28-03-2025 09:43:08","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004675159","NYO=
M FACE MAETUR","","28-03-2025 09:42:47","28-03-2025 09:31:39","28-03-2025 1=
2:34:23","Grid outage, Site went down because Gen failed to start due Gen c=
ard Faulty// Grid Restored","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, Site went down because Gen =
failed to start due Gen card Faulty// Grid Restored","christian.fonkou@ihst=
owers.com","669","28-03-2025 09:42:47","MATECH CMR"
"Closed Complete","Site Down","T2292","IHS_YND_453","NOCINC0004675116","Son=
g-bong","","28-03-2025 09:32:24","28-03-2025 07:48:12","28-03-2025 10:54:08=
","Hybrid gen site, Site went down because gen overload(09KVa, 70A) due to =
Old generator // Load reduice: Site on gen","Kemeni Franklin","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Hybrid gen site, Site went do=
wn because gen overload(09KVa, 70A) due to Old generator // Load reduice: S=
ite on gen","christian.fonkou@ihstowers.com","6253","28-03-2025 09:32:24","=
MATECH CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004674826","M=
essassi 2","","28-03-2025 08:48:30","28-03-2025 08:46:26","28-03-2025 14:14=
:26","Grid outage gen ran until fuel shortage//Refueling done","Fabrice Pou=
akam","Unlisted RCA","Others","Others","Others","RCA awaiting from MATECH",=
"joelle.ekessi@ihstowers.com","125","28-03-2025 08:48:30","MATECH CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004674813","Odz=
a Minkan IHS","","28-03-2025 08:45:44","28-03-2025 08:22:39","28-03-2025 09=
:16:01","Site went down because 2CB(50A) tripped in PWC// CB put back on","=
Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Circuit Breaker Issue","Site went down because 2CB(50A) tripped in PWC// =
CB put back on","christian.fonkou@ihstowers.com","1386","28-03-2025 08:45:4=
4","MATECH CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0004674635","Ese=
ka MTN","","28-03-2025 07:56:20","28-03-2025 07:35:13","28-03-2025 07:50:51=
","Active//No power issues on site U=3D54.6v.FME TX Etienne /695033981 is i=
nformed.","Kemeni Franklin","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Active//No power issues on site U=
=3D54.6v.FME TX Etienne /695033981 is informed.","christian.fonkou@ihstower=
s.com","1268","28-03-2025 07:56:20","MATECH CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0004674625","Dag=
obert","","28-03-2025 07:52:35","28-03-2025 07:45:29","28-03-2025 09:53:45"=
,"Grid outage, site went down because gen stopped with under voltage alarm =
// Reset done and gen started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down =
because gen stopped with under voltage alarm // Reset done and gen started"=
,"christian.fonkou@ihstowers.com","427","28-03-2025 07:52:35","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0004674513","EBOM",""=
,"28-03-2025 07:27:14","28-03-2025 07:04:43","28-03-2025 08:21:31","Cascade=
d Incident from TTO4758566","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage gen failed to start due to al=
arm high temp//We add water and gen manually started ","system","277080","2=
8-03-2025 07:27:14","MATECH CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0004674476","Nsi=
meyong","IHS_YND_698, IHS_YND_261","28-03-2025 07:17:49","28-03-2025 07:04:=
43","28-03-2025 08:21:31","Grid outage gen failed to start due to alarm hig=
h temp//We added water and gen manually started ","MINKA NICOLAS","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid outage gen failed to start due to alarm high temp//We added water=
 and gen manually started ","christian.fonkou@ihstowers.com","787","28-03-2=
025 07:17:49","MATECH CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004674378","D=
onga","","28-03-2025 06:55:22","28-03-2025 06:42:18","28-03-2025 08:09:07",=
" site went down because gen ran untill fuel shortage // Refueling Done","P=
arker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage"," site went =
down because gen ran untill fuel shortage // Refueling Done","joelle.ekessi=
@ihstowers.com","786","28-03-2025 06:55:22","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004674095","Pha=
rmacie Bleue","","28-03-2025 05:36:53","28-03-2025 05:29:44","28-03-2025 12=
:39:36","Site went down because insufficient of rectifier on site SS IHS Bl=
aise Raoul is informed//grid return","Siligap Boris","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","Site went down because insufficient =
of rectifier on site SS IHS Blaise Raoul is informed//grid return","olivier=
.kwedi@ihstowers.com","430","28-03-2025 05:36:53","MATECH CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0004674001","C=
hapelle-Nsimeyong","","28-03-2025 05:03:04","28-03-2025 04:00:43","28-03-20=
25 07:54:18","Grid outage.gen ran until fuel shortage//Refueling done","MIN=
KA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.g=
en ran until fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.co=
m","3742","28-03-2025 05:03:04","MATECH CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004673905","Nko=
l-Mbanda","","28-03-2025 04:12:57","28-03-2025 04:00:51","28-03-2025 08:02:=
55","Grid outage.gen ran until fuel shortage//Refueling done","MINKA NICOLA=
S","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran un=
til fuel shortage//Refueling done","olivier.kwedi@ihstowers.com","727","28-=
03-2025 04:12:57","MATECH CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004673891","A=
ccacia New","","28-03-2025 04:07:39","28-03-2025 03:59:26","28-03-2025 08:4=
9:13","Grid outage.no space to deploy mobile gen //Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deploy mobile gen //Grid return","ludivine.ngamaleu@ihstowers.com"=
,"495","28-03-2025 04:07:39","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004673853","NKONGKAR=
AK","","28-03-2025 03:53:32","28-03-2025 03:41:24","28-03-2025 06:53:14","C=
ascaded Incident from TTO4757833","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because PW=
C dysfunctioning // Reconfigation of PWC done, Site on Gen","system","59874=
2","28-03-2025 03:53:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0004673852","Ekekam",=
"","28-03-2025 03:53:32","28-03-2025 03:41:24","28-03-2025 06:53:14","Casca=
ded Incident from TTO4757833","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because PWC dy=
sfunctioning // Reconfigation of PWC done, Site on Gen","system","598743","=
28-03-2025 03:53:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0004673851","Lobo 2",=
"","28-03-2025 03:53:31","28-03-2025 03:41:24","28-03-2025 06:53:14","Casca=
ded Incident from TTO4757833","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because PWC dy=
sfunctioning // Reconfigation of PWC done, Site on Gen","system","598743","=
28-03-2025 03:53:31","MATECH CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0004673834","LOB=
O MTN","IHS_YND_783, IHS_YND_714, IHS_YND_713","28-03-2025 03:51:36","28-03=
-2025 03:41:24","28-03-2025 06:53:14","Site went down because PWC dysfuncti=
oning // Reconfigation of PWC done, Site on Gen","TIENTCHEU NZETCHIEU GAEL"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Si=
te went down because PWC dysfunctioning // Reconfigation of PWC done, Site =
on Gen","olivier.kwedi@ihstowers.com","612","28-03-2025 03:51:36","MATECH C=
MR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004673795","S=
hell-Nsimeyong","","28-03-2025 03:39:06","28-03-2025 03:35:39","28-03-2025 =
03:39:47","Grid outage, site went down because the generator  cable damaged=
 //Grid return","MINKA NICOLAS","Equipment Repair","Passive","Infrastructur=
e","Armoured Cable","Grid outage, site went down because the generator  cab=
le damaged //Grid return","ludivine.ngamaleu@ihstowers.com","208","28-03-20=
25 03:39:06","MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004673617","A=
wae Escalier","","28-03-2025 02:20:33","28-03-2025 02:07:07","28-03-2025 02=
:44:26","Site went down due to disjunction of Cb(32A) in PWC // He reamed C=
b(80A), site on grid","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to disj=
unction of Cb(32A) in PWC // He reamed Cb(80A), site on grid","ludivine.nga=
maleu@ihstowers.com","807","28-03-2025 02:20:33","MATECH CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004673544","Odz=
a petit marche new","","28-03-2025 02:04:50","28-03-2025 01:46:36","28-03-2=
025 03:10:36","Grid fluctuation, Site went down because Gen failed to start=
 due to Grid bad voltage No RCP// He bypassed Grid and started Gen manually=
","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation, Site went down because Gen failed to sta=
rt due to Grid bad voltage No RCP// He bypassed Grid and started Gen manual=
ly","olivier.kwedi@ihstowers.com","1095","28-03-2025 02:04:50","MATECH CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004673543","M=
EHANDAN","","28-03-2025 02:04:38","28-03-2025 01:39:24","28-03-2025 03:55:2=
8","","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Rectifier issue // rectifier reset","ludivine.ngamaleu@ihstowers.co=
m","1516","28-03-2025 02:04:38","MATECH CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004673434","Odz=
a II OCM","","28-03-2025 01:55:21","28-03-2025 01:39:00","28-03-2025 04:55:=
42","Grid outage gen ran until fuel shortage//Refueling done","Albran Byore=
l","Unlisted RCA","Others","Others","Others","Site up awaiting feedback","o=
livier.kwedi@ihstowers.com","1475","28-03-2025 01:55:21","MATECH CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004673383","UPA=
C LP","","28-03-2025 01:48:03","28-03-2025 00:54:56","28-03-2025 01:29:39",=
"Grid outage no space to deploy mobile gen//Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space t=
o deploy mobile gen//Grid return","olivier.kwedi@ihstowers.com","3188","28-=
03-2025 01:48:03","MATECH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004673363","Com=
plex Beac II","","28-03-2025 01:41:18","27-03-2025 21:57:07","28-03-2025 04=
:19:11","Grid outage site went down because Gen failed to start due to Gen =
card faulty // Gen Manually Started","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage site went down becaus=
e Gen failed to start due to Gen card faulty // Gen Manually Started","oliv=
ier.kwedi@ihstowers.com","13452","28-03-2025 01:41:18","MATECH CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004673356","Men=
dong NB","","28-03-2025 01:36:33","27-03-2025 15:14:24","28-03-2025 10:52:5=
4","Grid outage no space to deployed a mobile Gen // Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage n=
o space to deployed a mobile Gen // Grid return","olivier.kwedi@ihstowers.c=
om","37330","28-03-2025 01:36:33","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_670","NOCINC0004673336","BOBOCK",=
"","28-03-2025 01:28:11","28-03-2025 00:59:54","28-03-2025 01:01:09","Casca=
ded Incident from TTO4757212","Kemeni Franklin","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on gen with U=3D54v G=
regoire(654547479) from Huawei is informed and will be intervene at early m=
orning","system","298907","28-03-2025 01:28:11","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_532","NOCINC0004673333","NKOLOSSA=
N OKOK","","28-03-2025 01:28:10","28-03-2025 00:59:54","28-03-2025 01:01:09=
","Cascaded Incident from TTO4757212","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue site on gen with U=
=3D54v Gregoire(654547479) from Huawei is informed and will be intervene at=
 early morning","system","298914","28-03-2025 01:28:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0004673331","Monatele=
 MTN","","28-03-2025 01:28:10","28-03-2025 00:59:54","28-03-2025 01:01:09",=
"Cascaded Incident from TTO4757212","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on gen with U=3D5=
4v Gregoire(654547479) from Huawei is informed and will be intervene at ear=
ly morning","system","298907","28-03-2025 01:28:10","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0004673329","Monatele=
","","28-03-2025 01:28:09","28-03-2025 00:59:54","28-03-2025 01:01:09","Cas=
caded Incident from TTO4757212","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on gen with U=3D54v G=
regoire(654547479) from Huawei is informed and will be intervene at early m=
orning","system","298911","28-03-2025 01:28:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_052","NOCINC0004673330","Nyahoo",=
"","28-03-2025 01:28:09","28-03-2025 00:59:54","28-03-2025 01:01:09","Casca=
ded Incident from TTO4757212","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue site on gen with =
U=3D54v Gregoire(654547479) from Huawei is informed and will be intervene a=
t early morning","system","298909","28-03-2025 01:28:09","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0004673325","Talla Mo=
natele","","28-03-2025 01:28:08","28-03-2025 00:59:54","28-03-2025 01:01:09=
","Cascaded Incident from TTO4757212","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue site on gen with U=
=3D54v Gregoire(654547479) from Huawei is informed and will be intervene at=
 early morning","system","298910","28-03-2025 01:28:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_408","NOCINC0004673323","Evodoula=
 MTN","","28-03-2025 01:28:08","28-03-2025 00:59:54","28-03-2025 01:01:09",=
"Cascaded Incident from TTO4757212","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue site on gen=
 with U=3D54v Gregoire(654547479) from Huawei is informed and will be inter=
vene at early morning","system","298915","28-03-2025 01:28:08","MATECH CMR"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0004673321","NYANON/D=
EMBO","","28-03-2025 01:28:07","28-03-2025 00:59:54","28-03-2025 01:01:09",=
"Cascaded Incident from TTO4757212","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue site on gen=
 with U=3D54v Gregoire(654547479) from Huawei is informed and will be inter=
vene at early morning","system","298910","28-03-2025 01:28:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_337","NOCINC0004673320","Okola","=
","28-03-2025 01:28:07","28-03-2025 00:59:54","28-03-2025 01:01:09","Cascad=
ed Incident from TTO4757212","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on gen with U=
=3D54v Gregoire(654547479) from Huawei is informed and will be intervene at=
 early morning","system","298911","28-03-2025 01:28:07","MATECH CMR"
"Closed Complete","Site Down","T0211","IHS_YND_393","NOCINC0004673274","Eze=
zang","IHS_YND_703, IHS_YND_337, IHS_EDA_102, IHS_BMD_320, IHS_YND_408, IHS=
_EDA_049, IHS_YND_387, IHS_YND_530, IHS_EDA_048, IHS_YND_472, IHS_YND_406, =
IHS_EDA_052, IHS_YND_407, IHS_YND_390, IHS_YND_532, IHS_YND_705, IHS_YND_67=
0","28-03-2025 01:20:08","28-03-2025 00:59:54","28-03-2025 01:01:09","No po=
wer issue site on gen with U=3D54v Gregoire(654547479) from Huawei is infor=
med and will be intervene at early morning","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue site on gen with U=3D54v Gregoire(654547479) from Huawei is inf=
ormed and will be intervene at early morning","olivier.kwedi@ihstowers.com"=
,"1214","28-03-2025 01:20:08","MATECH CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004673044","A=
WAE OCM","","28-03-2025 00:04:51","27-03-2025 23:57:12","28-03-2025 00:04:3=
8","Grid outage, Site went down because Gen failed to start due to PWC dysf=
unctionning// He reset PWC, Site on Grid","Mba Lazare Herve","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, Site=
 went down because Gen failed to start due to PWC dysfunctionning// He rese=
t PWC, Site on Grid","ludivine.ngamaleu@ihstowers.com","461","28-03-2025 00=
:04:51","MATECH CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0004673020","O=
lezoa OCM","","28-03-2025 00:01:21","27-03-2025 23:34:03","28-03-2025 03:07=
:35","Grid outage.no space to deploy mobile gen //Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no s=
pace to deploy mobile gen //Grid return","ludivine.ngamaleu@ihstowers.com",=
"1639","28-03-2025 00:01:21","MATECH CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0004672243","Feb=
e Village","","27-03-2025 21:26:43","27-03-2025 20:46:16","27-03-2025 22:42=
:45","Grid outage.site went down because gen failed to start //Grid return =
(investigation ongoing)","Mboua Thierry","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid outage.site went down because gen failed=
 to start //Grid return (investigation ongoing)","kamga.virgile@ihstowers.c=
om","2516","27-03-2025 21:26:43","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004672054","Jean Ves=
pa 2","","27-03-2025 20:58:23","27-03-2025 18:08:31","27-03-2025 22:34:31",=
"Cascaded Incident from TTO4755829","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel sho=
rtage//Refueling done","system","10192","27-03-2025 20:58:23","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004672047","J=
-Vespa","IHS_YND_544","27-03-2025 20:56:55","27-03-2025 18:08:31","27-03-20=
25 22:34:31","Grid outage.gen ran until fuel shortage//Refueling done","Mbo=
ua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.g=
en ran until fuel shortage//Refueling done","alexandre.kamal@ihstowers.com"=
,"10105","27-03-2025 20:56:55","MATECH CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004671896","N=
kolo II New","","27-03-2025 20:42:32","27-03-2025 20:34:28","28-03-2025 09:=
32:57","Grid outage.gen ran until fuel shortage//Refueling done","Mba Lazar=
e Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen =
ran until fuel shortage//Refueling done","alexandre.kamal@ihstowers.com","4=
85","27-03-2025 20:42:32","MATECH CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004671548","ODZ=
A MINKAN EDIBI ASSI","","27-03-2025 19:46:03","27-03-2025 19:24:53","28-03-=
2025 18:49:04","Site went down due to MPR malfunctioning // He reset it","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet",=
"Site went down due to MPR malfunctioning // He reset it","kamga.virgile@ih=
stowers.com","1271","27-03-2025 19:46:03","MATECH CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004671289","M=
essassi okolo","","27-03-2025 18:59:04","27-03-2025 18:21:27","28-03-2025 1=
2:12:00","Grid outage gen ran until fuel shortage//Refueling done","Fabrice=
 Pouakam","Unlisted RCA","Others","Others","Others","RCA awaiting from MATE=
CH","alexandre.kamal@ihstowers.com","2258","27-03-2025 18:59:04","MATECH CM=
R"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0004671260","M=
VAN SACEL","","27-03-2025 18:48:24","27-03-2025 18:29:07","27-03-2025 19:34=
:38","Site went down due to insufficiency of rectifiers on site SS IHS Pasc=
aline is confirm // Grid return","MINKA NICOLAS","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to insufficiency of r=
ectifiers on site SS IHS Pascaline is confirm // He reduced the load","alex=
andre.kamal@ihstowers.com","1158","27-03-2025 18:48:24","MATECH CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004671254","O=
dza II","","27-03-2025 18:44:12","27-03-2025 18:36:02","27-03-2025 23:36:48=
","Grid outage.gen ran until fuel shortage //Refueling done","Albran Byorel=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unt=
il fuel shortage //Refueling done","alexandre.kamal@ihstowers.com","492","2=
7-03-2025 18:44:12","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004671236","N=
kozoa","","27-03-2025 18:41:45","27-03-2025 18:15:39","27-03-2025 22:11:39"=
,"Grid Outage Site went down because Gen Overload  SS IHS Alphonse Deffo co=
nfirmed//Grid return ","Fabrice Pouakam","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Grid Outage Site went down because Gen Overload  S=
S IHS Alphonse Deffo confirmed//Grid return ","alexandre.kamal@ihstowers.co=
m","1568","27-03-2025 18:41:45","MATECH CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004671228","M=
arche Odza","","27-03-2025 18:39:07","27-03-2025 18:09:59","28-03-2025 03:1=
5:50","","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","=
Fuel shortage// Refueling done","alexandre.kamal@ihstowers.com","1749","27-=
03-2025 18:39:07","MATECH CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004671218","E=
koumdoum OCM","","27-03-2025 18:38:02","27-03-2025 17:59:53","27-03-2025 20=
:07:07","Grid outage, Site went down because Gen overload (20kva, 300A) SS =
IHS alphonse confirmed// Grid return","Albran Byorel","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because G=
en overload (20kva, 300A) SS IHS alphonse confirmed// Grid return","alexand=
re.kamal@ihstowers.com","2290","27-03-2025 18:38:02","MATECH CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004671214","E=
koumdoum","","27-03-2025 18:36:27","27-03-2025 17:46:16","27-03-2025 18:46:=
03","Grid fluctuation, Site went down because gen fails to start due to gri=
d bad voltage,no rcp// He bypassed the Grid and site on Gen","Albran Byorel=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation, Site went down because gen fails to start due to grid ba=
d voltage,no rcp// He bypassed the Grid and site on Gen","alexandre.kamal@i=
hstowers.com","3012","27-03-2025 18:36:27","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004670912","K=
oweit City","","27-03-2025 17:40:48","27-03-2025 17:26:44","27-03-2025 19:4=
5:44","Grid outage .gen failed to start due to card GE dysfunctionning//We =
reset card GE and gen manually started ","Albran Byorel","Unlisted RCA","Ot=
hers","Others","Others","Waiting RCA matech","alexandre.kamal@ihstowers.com=
","845","27-03-2025 17:40:48","MATECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004670905","Men=
dong vallee","","27-03-2025 17:38:04","27-03-2025 17:30:13","27-03-2025 17:=
41:35","Site went down due to Gen Overload(20kva//300A)//he reduced the loa=
d and manually start the Gen","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Site went down due to Gen Overload(20kva//300A)=
//he reduced the load and manually start the Gen","kamga.virgile@ihstowers.=
com","472","27-03-2025 17:38:04","MATECH CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004670870","Mim=
boman4","","27-03-2025 17:34:50","27-03-2025 17:30:39","27-03-2025 17:31:23=
","No power issue site on grid with U=3D54v Notice that site is impacted by=
 Nkolo II","Mba Lazare Herve","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with =
U=3D54v Notice that site is impacted by Nkolo II","kamga.virgile@ihstowers.=
com","253","27-03-2025 17:34:50","MATECH CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004670534","Ntu=
i administration","","27-03-2025 16:46:01","27-03-2025 16:07:33","27-03-202=
5 18:03:32","Grid outage.gen ran until fuel shortage//Refueling done","Park=
er Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.ge=
n ran until fuel shortage//Refueling done","kamga.virgile@ihstowers.com","2=
309","27-03-2025 16:46:01","MATECH CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004670411","B=
riqueterie","","27-03-2025 16:20:31","27-03-2025 16:08:28","27-03-2025 19:1=
3:58","Grid outage no space to deploy mobile gen ,// Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage n=
o space to deploy mobile gen ,// Grid return","alexandre.kamal@ihstowers.co=
m","724","27-03-2025 16:20:31","MATECH CMR"
"Closed Complete","Site Down","T1739","IHS_YND_691","NOCINC0004670338","Mba=
lla 2 REGIE","","27-03-2025 16:08:21","27-03-2025 15:29:08","27-03-2025 20:=
11:50","Grid outage.gen ran until fuel shortage//Refueling done","Delor Tel=
ezing","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ra=
n until fuel shortage//Refueling done","edwige.kapawo@matech-cameroun.com",=
"2354","27-03-2025 16:08:21","MATECH CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004670276","N=
koabang2","","27-03-2025 15:56:11","27-03-2025 15:51:08","27-03-2025 17:08:=
41","Grid outage.gen ran until fuel shortage//Refueling done","Mba Lazare H=
erve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran=
 until fuel shortage//Refueling done","alexandre.kamal@ihstowers.com","305"=
,"27-03-2025 15:56:11","MATECH CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004670120","Eto=
udi2","","27-03-2025 15:45:16","27-03-2025 14:01:04","27-03-2025 22:05:39",=
"Grid outage.gen ran until fuel shortage//Refueling done","Delor Telezing",=
"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until=
 fuel shortage//Refueling done","kamga.virgile@ihstowers.com","6253","27-03=
-2025 15:45:16","MATECH CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0004670047","C=
harles-Atangana","","27-03-2025 15:35:21","27-03-2025 15:22:15","27-03-2025=
 20:54:35","Grid outage no space to deploy mobile gen // Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge no space to deploy mobile gen // Grid return","alexandre.kamal@ihstowers=
.com","787","27-03-2025 15:35:21","MATECH CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004670044","B=
arriere","","27-03-2025 15:34:25","27-03-2025 15:00:15","28-03-2025 08:21:3=
1"," Grid outage, Site went down because Gen overload (20kva, 400A) SS IHS =
Felix ZAMBE confirmed// Grid return","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload"," Grid outage, Site went down because =
Gen overload (20kva, 400A) SS IHS Felix ZAMBE confirmed// Grid return","ale=
xandre.kamal@ihstowers.com","2051","27-03-2025 15:34:25","MATECH CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0004669562","B=
ondjock","","27-03-2025 14:44:26","27-03-2025 13:56:36","27-03-2025 20:25:5=
1","Grid outage Site went down because Gen ran till fuel shortage// refueli=
ng done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage Site went down because Gen ran till fuel shortage// refueling don=
e","kouoh.jean@ihstowers.com","2871","27-03-2025 14:44:26","MATECH CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004669125","NTE=
MASSI","","27-03-2025 13:28:28","27-03-2025 13:02:23","27-03-2025 13:03:32"=
,"No power issue site on grid with U=3D54v Notice that site is impacted by =
Ngousso MTN ","Delor Telezing","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with=
 U=3D54v Notice that site is impacted by Ngousso MTN ","landry.etame@ihstow=
ers.com","1566","27-03-2025 13:28:28","MATECH CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0004669029","Ngo=
usso MTN","","27-03-2025 13:20:47","27-03-2025 13:02:41","27-03-2025 19:44:=
49","Grid outage no space to deploy mobile gen//Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spa=
ce to deploy mobile gen//Grid return","landry.etame@ihstowers.com","1086","=
27-03-2025 13:20:47","MATECH CMR"
"Closed Complete","Warning","T0543","IHS_YND_135","NOCINC0004668610","Nlong=
kak","","27-03-2025 12:47:08","","","Site went alarming due to insufficienc=
e of rectifier SS IHS Bernard ATANGANA is informed","Delor Telezing","Warni=
ng","Warning","POWER","Warning - Rectifier Module","Site went alarming due =
to insufficience of rectifier SS IHS Bernard ATANGANA is informed","gerard.=
tchangoue@matech-cameroun.com","2021","27-03-2025 12:47:08","MATECH CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004668525","C=
RH-Etoug-Ebe","","27-03-2025 12:34:36","27-03-2025 12:24:25","27-03-2025 13=
:41:11","Grid outage, Site went before Gen start due to poor backup// Gen s=
tarted manually","Hyemafo Gildas","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went before Gen start =
due to poor backup// Gen started manually","kouoh.jean@ihstowers.com","612"=
,"27-03-2025 12:34:36","MATECH CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0004668322","EKI=
E","","27-03-2025 12:04:29","27-03-2025 11:57:21","27-03-2025 15:52:46","Si=
te went down because gen failed to start due to grid bad voltage and no RCP=
 // Gen manually started","Albran Byorel","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Site went down because gen failed =
to start due to grid bad voltage and no RCP // Gen manually started","landr=
y.etame@ihstowers.com","429","27-03-2025 12:04:29","MATECH CMR"
"Closed Complete","Site Down","T0216","IHS_YND_032","NOCINC0004668281","Kam=
ajou Building","","27-03-2025 11:58:00","27-03-2025 11:49:54","27-03-2025 1=
4:40:35","Grid outage,gen ran till fuel shortage//Refueling done","Paul BIB=
OUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran =
till fuel shortage//Refueling done","landry.etame@ihstowers.com","487","27-=
03-2025 11:58:00","MATECH CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0004668222","A=
bome","","27-03-2025 11:47:14","27-03-2025 11:29:03","27-03-2025 11:30:50",=
"No power issue siote on grid with U=3D53.2v Mbah Osiah from Huawei site up=
 at 11:58 AM","MINKA NICOLAS","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue siote on grid with=
 U=3D53.2v Mbah Osiah from Huawei site up at 11:58 AM","kouoh.jean@ihstower=
s.com","1093","27-03-2025 11:47:14","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004668046","Essomba"=
,"","27-03-2025 11:24:42","27-03-2025 10:58:11","27-03-2025 13:34:06","Casc=
aded Incident from TTO4751332","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due PWC dysfonction // He reset the PWC, grid return","s=
ystem","378354","27-03-2025 11:24:42","MATECH CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004667972","B=
iteng","IHS_YND_179","27-03-2025 11:21:08","27-03-2025 10:58:11","27-03-202=
5 13:34:06","Grid outage site went down because Gen failed to start due PWC=
 dysfonction // He reset the PWC, grid return","Mba Lazare Herve","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage =
site went down because Gen failed to start due PWC dysfonction // He reset =
the PWC, grid return","kouoh.jean@ihstowers.com","1379","27-03-2025 11:21:0=
8","MATECH CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0004667603","OLA=
MA","","27-03-2025 10:23:05","27-03-2025 08:42:55","27-03-2025 17:23:48","G=
rid outage,Gen ran until fuel shortage//Refueling done","Fanda Brice","Fuel=
 Outage","Passive","Diesel","Diesel Outage","Grid outage,Gen ran until fuel=
 shortage//Refueling done","landry.etame@ihstowers.com","19024","27-03-2025=
 10:23:05","MATECH CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004667576","Nko=
abang Alembe","","27-03-2025 10:16:40","27-03-2025 09:43:21","27-03-2025 14=
:34:17","Grid outage.gen ran until fuel shortage//Refueling done","Mba Laza=
re Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen=
 ran until fuel shortage//Refueling done","landry.etame@ihstowers.com","200=
0","27-03-2025 10:16:40","MATECH CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004667465","Mon=
tee-Jouvence-II","","27-03-2025 10:04:37","27-03-2025 09:59:30","27-03-2025=
 10:19:45","Grid outage, Site went down because Gen overload (15kva, 250A) =
SS IHS Felix Zambe is informed // GRid power return","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen overload (15kva, 250A) SS IHS Felix Zambe is informed //=
 GRid power return","landry.etame@ihstowers.com","308","27-03-2025 10:04:37=
","MATECH CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004667454","M=
essa-Carriere OCM","","27-03-2025 10:02:34","27-03-2025 09:44:05","27-03-20=
25 11:45:52","Grid outage,no space to deploy a mobil gen // grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage,no space to deploy a mobil gen // grid return","kouoh.jean@ihstowers.=
com","1111","27-03-2025 10:02:34","MATECH CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004667439","M=
endong vallee","","27-03-2025 09:59:55","27-03-2025 09:55:34","27-03-2025 1=
1:14:31","Grid outage site went down because Gen over load (20KVA; 300A) //=
 Grid return IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site =
went down because Gen over load (20KVA; 300A) // Grid return IHS F=E9lix Za=
mb=E9 is informed and confirmed","kouoh.jean@ihstowers.com","263","27-03-20=
25 09:59:55","MATECH CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004667283","Aha=
la Echangeur","","27-03-2025 09:29:30","27-03-2025 09:13:23","27-03-2025 10=
:26:44","Site went down Gen failed to start due to Grid bad voltage(lack of=
 02 phases on site)// He did a bridge on the Good phase","MINKA NICOLAS","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Sit=
e went down Gen failed to start due to Grid bad voltage(lack of 02 phases o=
n site)// He did a bridge on the Good phase","landry.etame@ihstowers.com","=
968","27-03-2025 09:29:30","MATECH CMR"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0004667111","COR=
NIERS","","27-03-2025 09:00:59","26-03-2025 18:06:48","26-03-2025 19:40:28"=
,"Grid outage.no space to deploy mobile gen//Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no space =
to deploy mobile gen//Grid return","landry.etame@ihstowers.com","53654","27=
-03-2025 09:00:59","MATECH CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004666945","B=
iteng-Maetur","","27-03-2025 08:36:02","27-03-2025 08:31:49","27-03-2025 13=
:59:53","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the=
 load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen started and stopped due t=
o Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced th=
e load","kouoh.jean@ihstowers.com","254","27-03-2025 08:36:02","MATECH CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004666933","Mon=
tee Jouvence","","27-03-2025 08:31:58","27-03-2025 08:09:28","27-03-2025 10=
:26:21","Grid fluctuation, Site went down because gen fails to start due to=
 grid bad voltage// He bypasse the Grid and site on Gen","Hyemafo Gildas","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, Site went down because gen fails to start due to grid bad v=
oltage// He bypasse the Grid and site on Gen","edwige.kapawo@matech-camerou=
n.com","1352","27-03-2025 08:31:58","MATECH CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004666932","B=
itoto","","27-03-2025 08:31:40","27-03-2025 08:19:29","27-03-2025 18:52:45"=
,"Grid outage.gen ran until fuel shortage//Refueling done","Mba Lazare Herv=
e","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran un=
til fuel shortage//Refueling done","kouoh.jean@ihstowers.com","732","27-03-=
2025 08:31:40","MATECH CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004666859","V=
allee-Bastos OCM","","27-03-2025 08:22:53","27-03-2025 08:16:42","27-03-202=
5 08:28:30","Grid outage//Grid return","","Grid Supply","Passive","Grid","N=
ational Grid - Grid Outage Issue","Grid outage//Grid return","kouoh.jean@ih=
stowers.com","372","27-03-2025 08:22:53","MATECH CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004666775","O=
lembe-Terminus","","27-03-2025 08:00:27","27-03-2025 07:55:19","27-03-2025 =
07:58:55","No power issue site on gen with U=3D53.4v  Lionnel Steeve from H=
uawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gen=
 with U=3D53.4v  Lionnel Steeve from Huawei is informed","kouoh.jean@ihstow=
ers.com","311","27-03-2025 08:00:27","MATECH CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004666730","Pha=
rmacie Bleue","","27-03-2025 07:50:07","27-03-2025 07:48:46","27-03-2025 07=
:54:23","Site went down due to 01/02 rectifiers dysfunctionning//he reset i=
t","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site went down due to 01/02 rectifiers dysfunctionning//he reset it","=
landry.etame@ihstowers.com","82","27-03-2025 07:50:07","MATECH CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004666554","Man=
guiers Dispensaire","","27-03-2025 07:24:14","27-03-2025 07:13:06","27-03-2=
025 23:52:59","Grid outage,Gen ran until fuel shortage//Refueling done ","F=
abrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge,Gen ran until fuel shortage//Refueling done ","landry.etame@ihstowers.co=
m","669","27-03-2025 07:24:14","MATECH CMR"
"Closed Complete","Site Down","T1071","IHS_YND_343","NOCINC0004666062","Mbe=
doumou - Ekali","IHS_YND_723, IHS_YND_385, IHS_YND_410, IHS_YND_595, IHS_EB=
O_015, IHS_YND_411","27-03-2025 05:10:32","27-03-2025 02:49:18","27-03-2025=
 08:08:17","Grid outage .gen ran until fuel shortage//Refueling done","Albr=
an Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage .g=
en ran until fuel shortage//Refueling done","rouselle.schoune@ihstowers.com=
","8475","27-03-2025 05:10:32","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004666021","Saa","",=
"27-03-2025 04:44:58","27-03-2025 03:51:03","27-03-2025 07:35:05","Cascaded=
 Incident from TTO4749231","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen fai=
ls to start due to battery ge discharged // Gen start with battery backup(I=
nvestigation ongoing)","system","403804","27-03-2025 04:44:58","MATECH CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0004665941","ELO=
UMDEM CARRIERE 2","","27-03-2025 04:11:17","27-03-2025 03:59:09","27-03-202=
5 04:59:30","Grid outage.gen ran until fuel shortage//Refueling done","Fand=
a Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen =
ran until fuel shortage//Refueling done","rouselle.schoune@ihstowers.com","=
729","27-03-2025 04:11:17","MATECH CMR"
"Closed Complete","Site Down","T1747","IHS_YND_728","NOCINC0004665916","TRO=
PICANA NEW","","27-03-2025 04:02:00","27-03-2025 03:15:51","27-03-2025 09:1=
4:22","Grid outage gen ran until fuel shortage//Refueling done","MINKA NICO=
LAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran =
until fuel shortage//Refueling done","rouselle.schoune@ihstowers.com","2770=
","27-03-2025 04:02:00","MATECH CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004665664","Ole=
mbe MTN","","27-03-2025 02:58:38","26-03-2025 14:35:28","27-03-2025 02:47:4=
9","Grid outage,gen ran till fuel shortage//Refueling done","Fabrice Pouaka=
m","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran ti=
ll fuel shortage//Refueling done","rouselle.schoune@ihstowers.com","44591",=
"27-03-2025 02:58:38","MATECH CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004665662","O=
LAMA","","27-03-2025 02:58:20","27-03-2025 02:11:06","27-03-2025 03:38:07",=
" No power issue, Site on Gen, The FME Tx Etienne/695033981 From Huawei is =
informed ","Fanda Brice","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm"," No power issue, Site on Gen, The FME =
Tx Etienne/695033981 From Huawei is informed ","stephane.nkamwa@ihstowers.c=
om","2835","27-03-2025 02:58:20","MATECH CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004665436","Nsi=
meyong Shell","","27-03-2025 01:33:13","27-03-2025 01:29:06","27-03-2025 01=
:29:42","","MINKA NICOLAS","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No Power Issue on Site, U =3D 52.1V =
and Site is on GRID. FME TX FME Francois NDOUNGOU	657108640 of HUAWEI is in=
formed.	","rouselle.schoune@ihstowers.com","248","27-03-2025 01:33:13","MAT=
ECH CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004665414","Men=
dong vallee","","27-03-2025 01:25:10","27-03-2025 01:06:31","27-03-2025 03:=
52:13","Site went down because Gen overload(15kva,200 A) IHS SS Felix Zambe=
 is informed and confirmed // Grid return","Fanda Brice","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Site went down because Gen overloa=
d(15kva,200 A) IHS SS Felix Zambe is informed and confirmed // Grid return"=
,"rouselle.schoune@ihstowers.com","1120","27-03-2025 01:25:10","MATECH CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004665408","Fou=
da Quarter","","27-03-2025 01:21:23","27-03-2025 01:13:18","27-03-2025 02:4=
2:34","Grid outage.gen ran until fuel shortage//Refueling done","Delor Tele=
zing","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran=
 until fuel shortage//Refueling done","rouselle.schoune@ihstowers.com","486=
","27-03-2025 01:21:23","MATECH CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004665381","MAN=
GUIERS CHAPELLE","","27-03-2025 01:09:43","26-03-2025 15:52:34","27-03-2025=
 16:16:37","GGrid outage, Site went down because Gen overload IHS Bernard A=
tangana is informed //Grid Restored","Fabrice Pouakam","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","GGrid outage, Site went down because=
 Gen overload IHS Bernard Atangana is informed //Grid Restored","rouselle.s=
choune@ihstowers.com","33430","27-03-2025 01:09:43","MATECH CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004665376","Nlo=
ngkak","","27-03-2025 01:08:48","26-03-2025 15:51:53","26-03-2025 15:52:00"=
,"No power issue site on grid with U=3D54.8v Mohamadou from Huawei is infor=
med","Delor Telezing","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D54.8=
v Mohamadou from Huawei is informed","rouselle.schoune@ihstowers.com","3341=
6","27-03-2025 01:08:48","MATECH CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0004665324","Jou=
vence 2000","","27-03-2025 00:53:16","27-03-2025 00:49:11","28-03-2025 00:5=
0:59","No power issue site on grid with U=3D49.7v Armand Nguetsa from Huawe=
i is informed","Delor Telezing","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wit=
h U=3D49.7v Armand Nguetsa from Huawei is informed","rouselle.schoune@ihsto=
wers.com","247","27-03-2025 00:53:16","MATECH CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0004665237","C=
arington","","27-03-2025 00:30:10","26-03-2025 23:29:56","28-03-2025 16:02:=
11","Grid outage//Grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage//Grid return","stephane.nkamwa@ihsto=
wers.com","3615","27-03-2025 00:30:10","MATECH CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004665211","Com=
plex Beac II","","27-03-2025 00:19:02","26-03-2025 22:18:51","27-03-2025 09=
:21:15","Grid outage gen ran until fuel shortage//Refueling done","Albran B=
yorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ra=
n until fuel shortage//Refueling done","rouselle.schoune@ihstowers.com","72=
12","27-03-2025 00:19:02","MATECH CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0004665149","M=
ontee-Jouvence","","26-03-2025 23:58:45","26-03-2025 22:23:19","27-03-2025 =
00:31:47","Grid outage,Site went down because Gen failed to start due to Gr=
id contactor dysfunctionning // He bypass it and gen manually started","Hye=
mafo Gildas","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","=
Grid outage,Site went down because Gen failed to start due to Grid contacto=
r dysfunctionning // He bypass it and gen manually started","stephane.nkamw=
a@ihstowers.com","5727","26-03-2025 23:58:45","MATECH CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0004665004","T=
alla Monatele","","26-03-2025 23:12:30","26-03-2025 22:13:55","27-03-2025 0=
3:40:38","Grid outage.gen ran until fuel shortage//Refueling done","Parker =
Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen r=
an until fuel shortage//Refueling done","stephane.nkamwa@ihstowers.com","35=
16","26-03-2025 23:12:30","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004664871","Angongo"=
,"","26-03-2025 22:42:27","26-03-2025 16:51:50","26-03-2025 18:38:28","Casc=
aded Incident from TTO4747922","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage.gen failed to start due to ca=
rd GE dysfunctionned//We reset card GE and gen manually started","system","=
349820","26-03-2025 22:42:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004664870","Mambine"=
,"","26-03-2025 22:42:27","26-03-2025 16:51:50","26-03-2025 18:38:28","Casc=
aded Incident from TTO4747922","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage.gen failed to start due to ca=
rd GE dysfunctionned//We reset card GE and gen manually started","system","=
349818","26-03-2025 22:42:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004664872","Nkongtoc=
k","","26-03-2025 22:42:27","26-03-2025 16:51:50","26-03-2025 18:38:28","Ca=
scaded Incident from TTO4747922","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due=
 to card GE dysfunctionned//We reset card GE and gen manually started","sys=
tem","349819","26-03-2025 22:42:27","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004664867","Mbankomo=
 IHS","","26-03-2025 22:42:26","26-03-2025 16:51:50","26-03-2025 18:38:28",=
"Cascaded Incident from TTO4747922","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due =
to card GE dysfunctionned//We reset card GE and gen manually started","syst=
em","349818","26-03-2025 22:42:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004664868","Nkenglik=
ok","","26-03-2025 22:42:26","26-03-2025 16:51:50","26-03-2025 18:38:28","C=
ascaded Incident from TTO4747922","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start du=
e to card GE dysfunctionned//We reset card GE and gen manually started","sy=
stem","349820","26-03-2025 22:42:26","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004664869","Ebeba","=
","26-03-2025 22:42:26","26-03-2025 16:51:50","26-03-2025 18:38:28","Cascad=
ed Incident from TTO4747922","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen failed to start due to card=
 GE dysfunctionned//We reset card GE and gen manually started","system","34=
9819","26-03-2025 22:42:26","MATECH CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0004664856","O=
KOA Peage","IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_350, IHS_YND_335=
, IHS_YND_349","26-03-2025 22:40:07","26-03-2025 16:51:50","26-03-2025 18:3=
8:28","Grid outage.gen failed to start due to card GE dysfunctionned//We re=
set card GE and gen manually started","Fanda Brice","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to start du=
e to card GE dysfunctionned//We reset card GE and gen manually started","lu=
divine.ngamaleu@ihstowers.com","20898","26-03-2025 22:40:07","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004664851","Nomayos-=
IHS","","26-03-2025 22:39:42","26-03-2025 17:20:14","26-03-2025 17:23:13","=
Cascaded Incident from TTO4747915","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue site on Grid with U=3D54.=
2v Flubert from Huawei is informed","system","348321","26-03-2025 22:39:42"=
,"MATECH CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004664849","N=
omayos","IHS_YND_697","26-03-2025 22:38:31","26-03-2025 17:20:14","26-03-20=
25 17:23:13","No power issue site on Grid with U=3D54.2v Flubert from Huawe=
i is informed","Fanda Brice","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on Grid with U=
=3D54.2v Flubert from Huawei is informed","ludivine.ngamaleu@ihstowers.com"=
,"19098","26-03-2025 22:38:31","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0004664776","NKOLMEKO=
NG YDE","","26-03-2025 22:23:36","26-03-2025 21:38:10","26-03-2025 23:33:52=
","Cascaded Incident from TTO4747809","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel=
 shortage//Refueling done","system","347138","26-03-2025 22:23:36","MATECH =
CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0004664777","Messassi=
","","26-03-2025 22:23:36","26-03-2025 21:38:10","26-03-2025 23:33:52","Cas=
caded Incident from TTO4747809","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel short=
age//Refueling done","system","347137","26-03-2025 22:23:36","MATECH CMR"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0004664766","Nko=
lndom","IHS_YND_398, IHS_YND_274, IHS_YND_681, IHS_YND_297, IHS_YND_324","2=
6-03-2025 22:20:32","26-03-2025 21:38:10","26-03-2025 23:33:52","Grid outag=
e.gen ran until fuel shortage//Refueling done","Fabrice Pouakam","Fuel Outa=
ge","Passive","Diesel","Diesel Outage","Grid outage.gen ran until fuel shor=
tage//Refueling done","olivier.kwedi@ihstowers.com","2543","26-03-2025 22:2=
0:32","MATECH CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0004664718","Mes=
sassi Ngonlonk","","26-03-2025 22:10:02","26-03-2025 21:37:45","26-03-2025 =
23:34:04","Grid outage .gen ran until fuel shortage//Grid return","Fabrice =
Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage .gen=
 ran until fuel shortage//Grid return","olivier.kwedi@ihstowers.com","1938"=
,"26-03-2025 22:10:02","MATECH CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004664707","Mes=
sassi okolo","","26-03-2025 22:07:13","26-03-2025 21:36:04","26-03-2025 23:=
38:01","Grid outage.gen ran until fuel shortage//Refueling done","Fabrice P=
ouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen r=
an until fuel shortage//Refueling done","olivier.kwedi@ihstowers.com","1871=
","26-03-2025 22:07:13","MATECH CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0004664667","Ema=
na lycee 2","","26-03-2025 21:59:08","26-03-2025 21:16:01","26-03-2025 23:3=
6:39","No power issue site on grid with U=3D54.4v Symphorien from Huawei is=
 informed","Fabrice Pouakam","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54.4v Symphorien from Huawei is informed","olivier.kwedi@ihstowers.com",=
"2588","26-03-2025 21:59:08","MATECH CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004664502","E=
mana Lycee","","26-03-2025 21:26:25","26-03-2025 20:59:07","26-03-2025 21:4=
0:57","No power issue site on grid with U=3D54.1v Symphorien from Huawei is=
 informed","Fabrice Pouakam","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54.1v Symphorien from Huawei is informed","ludivine.ngamaleu@ihstowers.c=
om","1639","26-03-2025 21:26:25","MATECH CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0004664496","M=
VAN","","26-03-2025 21:24:44","26-03-2025 20:46:33","26-03-2025 23:06:04","=
Grid outage.gen ran until fuel shortage //Refueling done","MINKA NICOLAS","=
Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until =
fuel shortage //Refueling done","ludivine.ngamaleu@ihstowers.com","2292","2=
6-03-2025 21:24:44","MATECH CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004664472","N=
kolbong","","26-03-2025 21:20:13","26-03-2025 20:21:00","27-03-2025 03:25:2=
1","Grid outage.gen ran until fuel shortage//Refueling done","Delor Telezin=
g","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran un=
til fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.com","3554"=
,"26-03-2025 21:20:13","MATECH CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004664335","Nta=
ba","","26-03-2025 20:50:38","26-03-2025 20:12:18","26-03-2025 20:56:02","G=
rid outage.gen ran until fuel shortage//Refueling done","Delor Telezing","F=
uel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until f=
uel shortage//Refueling done","olivier.kwedi@ihstowers.com","2301","26-03-2=
025 20:50:38","MATECH CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0004663762","N=
dogbessol","","26-03-2025 19:08:13","26-03-2025 18:14:56","26-03-2025 18:20=
:23","No power issue on site U=3D54,6V site on Gen , The Tx FME Etienne/651=
320188/ from Huawei is informed","Kemeni Franklin","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site U=3D54,6V site on Gen , The Tx FME Etienne/651320188/ from Huawe=
i is informed","ludivine.ngamaleu@ihstowers.com","3198","26-03-2025 19:08:1=
3","MATECH CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004663731","O=
dza II","","26-03-2025 19:03:30","26-03-2025 18:44:09","26-03-2025 23:26:53=
","Grid outage.gen ran until fuel shortage //Refueling done","Albran Byorel=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unt=
il fuel shortage //Refueling done","ludivine.ngamaleu@ihstowers.com","1163"=
,"26-03-2025 19:03:30","MATECH CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004663712","K=
oweit City","","26-03-2025 19:00:16","26-03-2025 18:35:56","26-03-2025 20:4=
4:17","Grid outage.gen failed to start due to card GE dysfunctionned //We r=
eset card GE and gen manually started ","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to star=
t due to card GE dysfunctionned //We reset card GE and gen manually started=
 ","ludivine.ngamaleu@ihstowers.com","1461","26-03-2025 19:00:16","MATECH C=
MR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0004663704","Sapeur",=
"","26-03-2025 18:58:58","26-03-2025 18:17:58","26-03-2025 19:24:14","Casca=
ded Incident from TTO4746584","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage no space to deploy mobile ge=
n//Grid retuirn","system","1286961","26-03-2025 18:58:58","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_030","NOCINC0004663703","E-Police=
","","26-03-2025 18:58:58","26-03-2025 18:17:58","26-03-2025 19:24:14","Cas=
caded Incident from TTO4746584","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage no space to deploy mobile gen//Grid ret=
uirn","system","1286961","26-03-2025 18:58:58","MATECH CMR"
"Closed Complete","Site Down","CTR_323","IHS_YND_043","NOCINC0004663700","E=
mia","IHS_YND_030, IHS_YND_029","26-03-2025 18:58:04","26-03-2025 18:17:58"=
,"26-03-2025 19:24:48","Grid outage no space to deploy mobile gen//Grid ret=
uirn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Grid outage no space to deploy mobile gen//Grid retuirn","ludivine.ngamal=
eu@ihstowers.com","2407","26-03-2025 18:58:04","MATECH CMR"
"Closed Complete","Site Down","T0139","IHS_YND_381","NOCINC0004663697","Bou=
mnyebel","","26-03-2025 18:57:25","26-03-2025 18:19:19","26-03-2025 23:54:2=
3","Grid outage .gen ran until fuel shortage//Refueling done","Kemeni Frank=
lin","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage .gen ran=
 until fuel shortage//Refueling done","olivier.kwedi@ihstowers.com","2287",=
"26-03-2025 18:57:25","MATECH CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004663662","HOP=
ITAL GENERAL RAIL YDE","","26-03-2025 18:50:50","26-03-2025 18:14:40","27-0=
3-2025 11:32:00","Grid outage.gen ran until fuel shortage//Refueling done",=
"Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age.gen ran until fuel shortage//Refueling done","olivier.kwedi@ihstowers.c=
om","2170","26-03-2025 18:50:50","MATECH CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0004663618","Ngo=
um","","26-03-2025 18:47:25","26-03-2025 18:05:19","26-03-2025 18:10:38","N=
o power issue site on gen with U=3D54v Gregoire from Huawei is informed","P=
arker Tchoup","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","No power issue site on gen with U=3D54v Gregoire =
from Huawei is informed","olivier.kwedi@ihstowers.com","2527","26-03-2025 1=
8:47:25","MATECH CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004663416","M=
amch Building","","26-03-2025 18:06:22","26-03-2025 17:47:15","26-03-2025 1=
7:50:32","No power issue site on grid with U=3D54v Notice that site is impa=
cted by Charles Atangana ","Mboua Thierry","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on grid with U=3D54v Notice that site is impacted by Charles Atangana ","lu=
divine.ngamaleu@ihstowers.com","1148","26-03-2025 18:06:22","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_583","NOCINC0004663357","Nsam Sof=
avinc T0","","26-03-2025 18:02:29","26-03-2025 17:36:57","26-03-2025 18:30:=
29","Cascaded Incident from TTO4746150","MINKA NICOLAS","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel=
 shortage//Refueling done","system","433516","26-03-2025 18:02:29","MATECH =
CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004663328","C=
rf-Nsam","IHS_YND_161, IHS_YND_583","26-03-2025 18:00:02","26-03-2025 17:36=
:57","26-03-2025 18:30:55","Grid outage.gen ran until fuel shortage//Refuel=
ing done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage.gen ran until fuel shortage//Refueling done","ludivine.ngamale=
u@ihstowers.com","1387","26-03-2025 18:00:02","MATECH CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004663318","NYO=
M FACE MAETUR","","26-03-2025 17:58:57","26-03-2025 17:16:49","26-03-2025 1=
8:04:29","Grid outage site went down because Gen failed to start due to Gen=
 card faulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start due to Gen card faulty // Grid return","olivier.kwedi@ihsto=
wers.com","2529","26-03-2025 17:58:57","MATECH CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0004663305","E=
BOM","","26-03-2025 17:54:06","26-03-2025 17:20:53","26-03-2025 17:25:23","=
No power issue site on grid with U=3D54.4v Mbah Osiah from Huawei is inform=
ed","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D54.4v=
 Mbah Osiah from Huawei is informed","ludivine.ngamaleu@ihstowers.com","199=
3","26-03-2025 17:54:06","MATECH CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004663114","Elo=
umdem stade","","26-03-2025 17:24:34","26-03-2025 16:37:15","26-03-2025 17:=
58:47","Grid outage.gen ran until fuel shortage//Refueling done","Fanda Bri=
ce","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran u=
ntil fuel shortage//Refueling done","olivier.kwedi@ihstowers.com","2840","2=
6-03-2025 17:24:34","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0004663007","H-Franco=
 New","","26-03-2025 17:09:22","26-03-2025 16:51:44","26-03-2025 18:58:58",=
"Cascaded Incident from TTO4745766","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel sh=
ortage//Refueling done","system","774660","26-03-2025 17:09:22","MATECH CMR=
"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0004663004","D=
joungolo","IHS_YND_711","26-03-2025 17:08:49","26-03-2025 16:51:44","26-03-=
2025 18:58:58","Grid outage.gen ran until fuel shortage//Refueling done","M=
boua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage=
.gen ran until fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.=
com","1026","26-03-2025 17:08:49","MATECH CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004662999","N=
kozoa","","26-03-2025 17:07:15","26-03-2025 16:33:07","27-03-2025 02:07:00"=
,"Grid outage, Site went down because Gen overload SS IHS Bernard Atangana/=
/We reduce load and gen manually started ","Fabrice Pouakam","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down be=
cause Gen overload SS IHS Bernard Atangana//We reduce load and gen manually=
 started ","ludivine.ngamaleu@ihstowers.com","2050","26-03-2025 17:07:15","=
MATECH CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004662996","C=
omplexe-BEAC","","26-03-2025 17:05:45","26-03-2025 16:29:31","26-03-2025 18=
:29:04","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started manually","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Circuit Breaker Issue","Grid outage, Site went do=
wn before Gen start due to poor backup // Gen started manually","ludivine.n=
gamaleu@ihstowers.com","2175","26-03-2025 17:05:45","MATECH CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004662995","Sof=
avinc","","26-03-2025 17:05:29","26-03-2025 14:52:21","26-03-2025 18:30:39"=
,"Grid outage.gen ran until fuel shortage//Refueling done","MINKA NICOLAS",=
"Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage=
.gen ran until fuel shortage//Refueling done","olivier.kwedi@ihstowers.com"=
,"7989","26-03-2025 17:05:29","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004662987","Tsinga",=
"","26-03-2025 17:03:21","26-03-2025 16:07:59","01-04-2025 09:42:53","Casca=
ded Incident from TTO4745435","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site burned,Transmission route behind an=
other site,   Team is managing to relocate the site.","system","762773","26=
-03-2025 17:03:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_087","NOCINC0004662986","Camp-Sic=
-Tsinga","","26-03-2025 17:03:21","26-03-2025 16:07:59","01-04-2025 09:42:5=
3","Cascaded Incident from TTO4745435","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Site burned,Transmission route behind anothe=
r site,   Team is managing to relocate the site.","system","762772","26-03-=
2025 17:03:21","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_028","NOCINC0004662985","H-Centra=
l","","26-03-2025 17:03:20","26-03-2025 16:07:59","01-04-2025 09:42:53","Ca=
scaded Incident from TTO4745435","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site burned,Transmission route behind a=
nother site,   Team is managing to relocate the site.","system","762775","2=
6-03-2025 17:03:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_002","NOCINC0004662983","Yde-M-Ce=
ntral","","26-03-2025 17:03:20","26-03-2025 16:07:59","01-04-2025 09:42:53"=
,"Cascaded Incident from TTO4745435","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Site burned,Transmission route behind another =
site,   Team is managing to relocate the site.","system","762771","26-03-20=
25 17:03:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_010","NOCINC0004662982","CNR","",=
"26-03-2025 17:03:20","26-03-2025 16:07:59","01-04-2025 09:42:53","Cascaded=
 Incident from TTO4745435","Mboua Thierry","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site burned,Transmission route behind anoth=
er site,   Team is managing to relocate the site.","system","762774","26-03=
-2025 17:03:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_083","NOCINC0004662984","H-Progre=
s","","26-03-2025 17:03:20","26-03-2025 16:07:59","27-03-2025 11:33:59","Ca=
scaded Incident from TTO4745435","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Cascaded Incident from TTO4745435","system","76277=
4","26-03-2025 17:03:20","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_017","NOCINC0004662978","H-Depute=
s","","26-03-2025 17:03:19","26-03-2025 16:07:59","01-04-2025 09:42:53","Ca=
scaded Incident from TTO4745435","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site burned,Transmission route behind another site=
,   Team is managing to relocate the site.","system","762775","26-03-2025 1=
7:03:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004662981","Bastos B=
ethesda","","26-03-2025 17:03:19","26-03-2025 16:07:59","01-04-2025 09:42:5=
3","Cascaded Incident from TTO4745435","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site burned,Transmission route =
behind another site,   Team is managing to relocate the site.","system","76=
2772","26-03-2025 17:03:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0004662980","Bastos-N=
ylon","","26-03-2025 17:03:19","26-03-2025 16:07:59","01-04-2025 09:42:53",=
"Cascaded Incident from TTO4745435","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site burned,Transmission route beh=
ind another site,   Team is managing to relocate the site.","system","76277=
6","26-03-2025 17:03:19","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004662979","Golf Qua=
ter","","26-03-2025 17:03:19","30-03-2025 10:16:17","30-03-2025 11:06:30","=
yve is on site ","Mboua Thierry","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","site down due to fuel shortage // Refueling done","sy=
stem","265492","26-03-2025 17:03:19","MATECH CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004662973","NTU=
I TOWN","","26-03-2025 17:02:28","26-03-2025 14:44:23","26-03-2025 15:05:48=
","Grid outage.gen ran until fuel shortage//Refueling done","Parker Tchoup"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unti=
l fuel shortage//Refueling done","olivier.kwedi@ihstowers.com","8287","26-0=
3-2025 17:02:28","MATECH CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0004662947","F=
ebe Village","","26-03-2025 16:57:08","26-03-2025 15:56:55","26-03-2025 19:=
54:48","Grid outage site went down because Relay 220V faulty due to lightni=
ng // he replaced the relay and site on Grid","Mboua Thierry","Force Majeur=
e","Natural Disaster","Thunderstrike","Equipment Damaged","Grid outage site=
 went down because Relay 220V faulty due to lightning // he replaced the re=
lay and site on Grid","ludivine.ngamaleu@ihstowers.com","3614","26-03-2025 =
16:57:08","MATECH CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004662912","Crf=
-Mbankolo-IHS","","26-03-2025 16:52:16","26-03-2025 14:11:08","26-03-2025 1=
6:38:17","Grid outage site went down because the MPR dysfonction // He rese=
t the MPR","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Cabinet","Grid outage site went down because the MPR dysfonction // He =
reset the MPR","olivier.kwedi@ihstowers.com","9669","26-03-2025 16:52:16","=
MATECH CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004662882","E=
lig-Edzoa","","26-03-2025 16:44:02","26-03-2025 15:46:56","27-03-2025 14:53=
:07","Grid outage //Grid return","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Outage Issue","Grid outage //Grid return","ludivine.ngamaleu@=
ihstowers.com","3428","26-03-2025 16:44:02","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004662878","ARMP",""=
,"26-03-2025 16:43:05","26-03-2025 15:49:47","26-03-2025 23:01:51","Cascade=
d Incident from TTO4745618","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage gen ran until fuel shortage//Refueling done=
","system","3198","26-03-2025 16:43:05","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004662877","Bastos B=
ir","","26-03-2025 16:43:05","26-03-2025 15:49:47","26-03-2025 23:01:51","C=
ascaded Incident from TTO4745618","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage gen ran until fuel short=
age//Refueling done","system","3198","26-03-2025 16:43:05","MATECH CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004662872","D=
ragage","IHS_YND_704, IHS_YND_208","26-03-2025 16:41:52","26-03-2025 15:49:=
47","26-03-2025 23:01:51","Grid outage gen ran until fuel shortage//Refueli=
ng done","Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage gen ran until fuel shortage//Refueling done","ludivine.ngamaleu=
@ihstowers.com","3126","26-03-2025 16:41:52","MATECH CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0004662720","C=
NDH","IHS_YND_017, IHS_YND_220, IHS_YND_126, IHS_YND_563, IHS_YND_010, IHS_=
YND_002, IHS_YND_083, IHS_YND_028, IHS_YND_087, IHS_YND_127","26-03-2025 16=
:10:17","26-03-2025 16:07:59","01-04-2025 09:42:53","","Paul BIBOUM","Fire =
on Site","Passive","Infrastructure","Fire - Burned","Site burned,Transmissi=
on route behind another site,   Team is managing to relocate the site.02 si=
te remain down CTR_002 CNR, CTR_759 Croix Rouge","edwige.kapawo@matech-came=
roun.com","139","26-03-2025 16:10:17","MATECH CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004662686","L=
abogenie","","26-03-2025 16:07:47","26-03-2025 15:28:41","26-03-2025 16:36:=
16","Grid outage, no space to deploy mobile gen // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no=
 space to deploy mobile gen // Grid return","ludivine.ngamaleu@ihstowers.co=
m","2348","26-03-2025 16:07:47","MATECH CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004662679","Mfo=
u EPC","","26-03-2025 16:06:45","26-03-2025 15:47:31","26-03-2025 18:24:46"=
,"Grid outage site went down because Gen failed to start due PWC dysfonctio=
nned // Grid power return","Mba Lazare Herve","Equipment Repair","Passive",=
"Rectifier","Rectifier Module Overloaded","Grid outage site went down becau=
se Gen failed to start due PWC dysfonctionned // Grid power return","edwige=
.kapawo@matech-cameroun.com","1156","26-03-2025 16:06:45","MATECH CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004662664","J=
-Vespa","","26-03-2025 16:04:05","26-03-2025 14:07:48","26-03-2025 14:12:20=
","site went down because Gen failed to start due to Gen contactor faulty /=
/ Grid power return","Mboua Thierry","Equipment Repair","Passive","ACDG Gen=
","ACDG - Load Contactor","site went down because Gen failed to start due t=
o Gen contactor faulty // Grid power return","edwige.kapawo@matech-cameroun=
.com","6978","26-03-2025 16:04:05","MATECH CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004662635","F=
ouda-New","","26-03-2025 15:59:40","26-03-2025 15:44:36","27-03-2025 13:22:=
11","Grid outage gen ran until fuel shortage//Refueling done","Delor Telezi=
ng","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran u=
ntil fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.com","905"=
,"26-03-2025 15:59:40","MATECH CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004662616","O=
mnisport-Rail","","26-03-2025 15:56:42","26-03-2025 15:40:27","27-03-2025 0=
2:41:27","Grid outage.gen ran until fuel shortage//Refueling done","Delor T=
elezing","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen =
ran until fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.com",=
"976","26-03-2025 15:56:42","MATECH CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004662600","Ngoulmek=
ong-Nord","","26-03-2025 15:55:15","26-03-2025 15:40:39","26-03-2025 15:45:=
05","Cascaded Incident from TTO4745300","Siligap Boris","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue site on  grid with=
 U=3D50v site up at 08:40 PM Aemand Nguets from Huawei is informed","system=
","447694","26-03-2025 15:55:15","MATECH CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004662593","E=
leveur","IHS_YND_277","26-03-2025 15:54:44","26-03-2025 15:40:39","26-03-20=
25 15:45:05","No power issue site on  grid with U=3D50v site up at 08:40 PM=
 Armand Nguetsa from Huawei is informed","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue site on  grid with U=3D50v site up at 08:40 PM Armand Nguetsa from=
 Huawei is informed","ludivine.ngamaleu@ihstowers.com","846","26-03-2025 15=
:54:44","MATECH CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0004662592","Don=
g","","26-03-2025 15:54:27","26-03-2025 15:20:20","26-03-2025 17:41:59","si=
te went down because gen ran untill fuel shortage // Refueling done","Parke=
r Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","site went down =
because gen ran untill fuel shortage // Refueling done","edwige.kapawo@mate=
ch-cameroun.com","2048","26-03-2025 15:54:27","MATECH CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004662586","B=
ATA Mokolo OCM","","26-03-2025 15:53:01","26-03-2025 15:39:06","26-03-2025 =
17:24:50","Grid outage,no space to deploy MDG//Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no spac=
e to deploy MDG//Grid return","ludivine.ngamaleu@ihstowers.com","836","26-0=
3-2025 15:53:01","MATECH CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004662579","S=
atcom","","26-03-2025 15:50:43","26-03-2025 15:35:28","26-03-2025 15:37:58"=
,"No power issue site on gen with U=3D54.8v Armand Nguetsa from Huawei is i=
nformed","Delor Telezing","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue site on gen with U=3D5=
4.8v Armand Nguetsa from Huawei is informed","ludivine.ngamaleu@ihstowers.c=
om","915","26-03-2025 15:50:43","MATECH CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0004662555","A=
nguissa New","","26-03-2025 15:47:34","26-03-2025 15:31:21","26-03-2025 15:=
40:26","No power issue site on grid with U=3D53.4v Armand Nguetsa from Huaw=
ei is informed","MINKA NICOLAS","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wit=
h U=3D53.4v Armand Nguetsa from Huawei is informed","ludivine.ngamaleu@ihst=
owers.com","974","26-03-2025 15:47:34","MATECH CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004662546","O=
dza","","26-03-2025 15:46:12","26-03-2025 15:29:59","26-03-2025 16:38:29","=
Grid outage.site went down due to gen failed to start//Grid return","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage.site went down due to gen failed to start//Grid return","ludivine=
.ngamaleu@ihstowers.com","974","26-03-2025 15:46:12","MATECH CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004662518","M=
ontee-Anne-Rouge","","26-03-2025 15:42:05","26-03-2025 15:07:53","26-03-202=
5 17:44:03","Grid outage, No space to deploy MDG // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MDG // Grid return","ludivine.ngamaleu@ihstowers.com","20=
53","26-03-2025 15:42:05","MATECH CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004662509","E=
MANA BILICK CITY","","26-03-2025 15:39:41","26-03-2025 15:03:29","26-03-202=
5 21:37:57","Grid outage gen failed to start due to card GE dysfunctionned/=
/Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","AC=
DG - Control Panel","Grid outage gen failed to start due to card GE dysfunc=
tionned//Grid return","ludivine.ngamaleu@ihstowers.com","2174","26-03-2025 =
15:39:41","MATECH CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004662474","E=
kombitie","","26-03-2025 15:35:19","26-03-2025 15:00:04","26-03-2025 23:49:=
08","Grid outage.gen ran until fuel shortage//Refueling done","Fabrice Poua=
kam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran =
until fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.com","211=
6","26-03-2025 15:35:19","MATECH CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0004662467","E=
kie sud","","26-03-2025 15:33:44","26-03-2025 14:55:36","26-03-2025 16:43:3=
3","Grid outage.site went down due to gen failed to start //Grid return","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","Grid outage.site went down due to gen failed to start //Grid return","lu=
divine.ngamaleu@ihstowers.com","2290","26-03-2025 15:33:44","MATECH CMR"
"Closed Complete","Site Down","T1591","IHS_YND_172","NOCINC0004662353","Tra=
dex-Nkomo","","26-03-2025 15:22:34","26-03-2025 15:05:22","26-03-2025 16:40=
:48","Grid outage .gen ran until fuel shortage //Refueling done","Albran By=
orel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage .gen ra=
n until fuel shortage //Refueling done","edwige.kapawo@matech-cameroun.com"=
,"1033","26-03-2025 15:22:34","MATECH CMR"
"Closed Complete","Site Down","T0288","IHS_YND_001","NOCINC0004662272","Roy=
al Hotel Yde","","26-03-2025 15:06:35","26-03-2025 14:03:13","26-03-2025 17=
:30:48"," Fuel shortage due to long Eneo outage //refuelling done","Paul BI=
BOUM","Fuel Outage","Passive","Diesel","Diesel Outage"," Fuel shortage due =
to long Eneo outage //refuelling done","edwige.kapawo@matech-cameroun.com",=
"3803","26-03-2025 15:06:35","MATECH CMR"
"Closed Complete","Site Down","T1333","IHS_YND_174","NOCINC0004661809","Car=
refourt Nkomo","","26-03-2025 13:56:45","26-03-2025 13:11:20","26-03-2025 1=
7:45:20","Grid outage.site went down due to gen failed to start //Grid retu=
rn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid outage.site went down due to gen failed to start //Grid re=
turn","landry.etame@ihstowers.com","430368","26-03-2025 13:56:45","MATECH C=
MR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004661461","M=
EHANDAN","","26-03-2025 12:58:10","26-03-2025 09:07:48","26-03-2025 09:10:3=
4","No power issue site on grid with U=3D52.4v Notice that site is impacted=
 by OdzAII ","Albran Byorel","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D52.4v Notice that site is impacted by OdzAII ","edwige.kapawo@matech-cam=
eroun.com","13824","26-03-2025 12:58:10","MATECH CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0004661400","Nko=
mo","","26-03-2025 12:47:56","26-03-2025 12:44:22","27-03-2025 12:45:20","N=
o power issue site on grid with U=3D54V Flubert from Huawei is informed","M=
ba Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue site on grid with U=3D54V Flube=
rt from Huawei is informed","gerard.tchangoue@matech-cameroun.com","215","2=
6-03-2025 12:47:56","MATECH CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0004661337","Mae=
tur","","26-03-2025 12:36:14","26-03-2025 12:14:02","26-03-2025 15:47:16","=
site down due to fuel shortage // refueling done","Mboua Thierry","Fuel Out=
age","Passive","Diesel","Diesel Outage","site down due to fuel shortage // =
refueling done","landry.etame@ihstowers.com","1333","26-03-2025 12:36:14","=
MATECH CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004661328","A=
wae Escalier","","26-03-2025 12:35:02","26-03-2025 12:31:40","26-03-2025 17=
:01:35","Grid outage, site went down because gen failed to start due to gri=
d contactor faulty // He bypassed it and Gen manually started","Albran Byor=
el","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outa=
ge, site went down because gen failed to start due to grid contactor faulty=
 // He bypassed it and Gen manually started","edwige.kapawo@matech-cameroun=
.com","204","26-03-2025 12:35:02","MATECH CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004661287","Imm=
-Olympique","","26-03-2025 12:27:03","26-03-2025 12:23:50","26-03-2025 17:3=
0:45","Grid outage,gen ran till fuel shortage//Refueling done","Paul BIBOUM=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran til=
l fuel shortage//Refueling done","gerard.tchangoue@matech-cameroun.com","19=
4","26-03-2025 12:27:03","MATECH CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004661261","TSI=
NGA VILLAGE 2","","26-03-2025 12:22:15","26-03-2025 12:16:56","26-03-2025 2=
3:01:16","Grid outage gen ran until Fuel shortage // Refueling done","Delor=
 Telezing","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage ge=
n ran until Fuel shortage // Refueling done","gerard.tchangoue@matech-camer=
oun.com","320","26-03-2025 12:22:15","MATECH CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004661251","E=
vodoula OCM","","26-03-2025 12:20:12","26-03-2025 11:49:58","26-03-2025 14:=
44:23","Grid outage site went Gen ran until fuel shortage // Refueling done=
","TIENTCHEU NZETCHIEU GAEL","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage site went Gen ran until fuel shortage // Refueling done","e=
dwige.kapawo@matech-cameroun.com","1815","26-03-2025 12:20:12","MATECH CMR"
"Closed Complete","Site Down","T3180","IHS_YND_253","NOCINC0004661244","Clg=
e-Advantiste","","26-03-2025 12:17:24","26-03-2025 12:13:58","26-03-2025 13=
:32:42","Grid outage.gen failed to start due to battery GE faulty //Gen man=
ually started with external battery","MINKA NICOLAS","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Generator Battery","Grid outage.gen failed to sta=
rt due to battery GE faulty //Gen manually started with external battery","=
gerard.tchangoue@matech-cameroun.com","207","26-03-2025 12:17:24","MATECH C=
MR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0004661143","A=
hala","","26-03-2025 12:02:51","26-03-2025 11:31:38","26-03-2025 12:32:44",=
"site went down due to insufficiency of rectifiers, Pascaline Ihs is inform=
ed // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","site went down due to insufficiency of rectifiers, Pas=
caline Ihs is informed // Grid return","edwige.kapawo@matech-cameroun.com",=
"1874","26-03-2025 12:02:51","MATECH CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004661132","Aka=
k-Nkozoa-MTN-IHS","","26-03-2025 12:00:54","26-03-2025 11:56:59","26-03-202=
5 12:50:34","Grid outage site went down because Gen failed to start due PWC=
 dysfonction // He reset the PWC, grid return","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage s=
ite went down because Gen failed to start due PWC dysfonction // He reset t=
he PWC, grid return","gerard.tchangoue@matech-cameroun.com","237","26-03-20=
25 12:00:54","MATECH CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004661105","Eko=
umdoum OCM","","26-03-2025 11:54:48","26-03-2025 11:34:37","26-03-2025 13:5=
4:59","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS =
Pascaline is informed and confirmed//Grid return","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went do=
wn due to Gen overload(20kva,280 A) IHS SS Pascaline is informed and confir=
med//Grid return","gerard.tchangoue@matech-cameroun.com","1212","26-03-2025=
 11:54:48","MATECH CMR"
"Closed Complete","Site Down","T1113","IHS_YND_105","NOCINC0004660996","Omn=
isport 3","","26-03-2025 11:28:42","26-03-2025 11:17:23","26-03-2025 19:26:=
06","Site went down due to insufficiency of rectifiers on site  IHS SS Raou=
l is confirmed// Site stabilized","Delor Telezing","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","Site went down due to insufficiency of=
 rectifiers on site  IHS SS Raoul is confirmed// Site stabilized","edwige.k=
apawo@matech-cameroun.com","680","26-03-2025 11:28:42","MATECH CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0004660955","MVA=
N SACEL","","26-03-2025 11:23:52","26-03-2025 11:09:25","26-03-2025 11:27:1=
9","rectifier failure","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","rectifier failure","gerard.tchangoue@matech-camero=
un.com","868","26-03-2025 11:23:52","MATECH CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004660825","OBA=
M NGOLA OCM","","26-03-2025 11:05:43","26-03-2025 10:49:11","26-03-2025 19:=
20:58","Grid outage gen ran until fuel shortage//Refueling done","MINKA NIC=
OLAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran=
 until fuel shortage//Refueling done","ludovic-anselme.mouliom-mapoure@sage=
mcom","994","26-03-2025 11:05:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004660649","S=
OA TOWN","","26-03-2025 10:43:02","26-03-2025 10:41:51","26-03-2025 11:10:3=
0","Grid outage gen ran until fuel shortage//Refueling done","Siligap Boris=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran unt=
il fuel shortage//Refueling done","ludovic-anselme.mouliom-mapoure@sagemcom=
","72","26-03-2025 10:43:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0004660637","A=
bome","","26-03-2025 10:41:59","26-03-2025 10:37:44","26-03-2025 13:37:57",=
"Fuel shortage","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Fuel shortage // Refueling ","ludovic-anselme.mouliom-mapoure@sagemc=
om","257","26-03-2025 10:41:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004660614","C=
rf-Nkolbisson","","26-03-2025 10:40:11","26-03-2025 10:34:49","26-03-2025 1=
0:35:04","No power issue site on grid with U=3D55.4v Mohamdou from Huawei i=
s informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D55.4v Mohamdou from Huawei is informed","ludovic-anselme.mouli=
om-mapoure@sagemcom","323","26-03-2025 10:40:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0004660583","N=
simalen OCM","","26-03-2025 10:37:13","26-03-2025 10:25:46","26-03-2025 10:=
26:06","No power issue site on grid with U=3D50.8v Notice that site is impa=
cted by NKOLDA","Albran Byorel","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wit=
h U=3D50.8v Notice that site is impacted by NKOLDA","ludovic-anselme.moulio=
m-mapoure@sagemcom","688","26-03-2025 10:37:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004660569","N=
kolda","","26-03-2025 10:34:36","26-03-2025 10:26:26","26-03-2025 12:14:47"=
,"Site went Down due to Fuel shortage // Grid return (refueling Ongoing)","=
Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Site went =
Down due to Fuel shortage // Grid return (refueling Ongoing)","ludovic-anse=
lme.mouliom-mapoure@sagemcom","491","26-03-2025 10:34:36","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004660126","ETO=
UDI Entree du palais","","26-03-2025 09:39:36","26-03-2025 09:38:24","26-03=
-2025 13:11:06","Grid outage, Site went down before Gen start due to poor b=
ackup // Gen started manually","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down before Ge=
n start due to poor backup // Gen started manually","ludovic-anselme.moulio=
m-mapoure@sagemcom","73","26-03-2025 09:39:36","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004660023","Acc=
acia New","","26-03-2025 09:22:23","26-03-2025 09:06:59","26-03-2025 10:22:=
40","Grid outage.no space to deploy mobile gen //Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no sp=
ace to deploy mobile gen //Grid return","ludovic-anselme.mouliom-mapoure@sa=
gemcom","926","26-03-2025 09:22:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004660008","O=
dza II OCM","","26-03-2025 09:18:02","26-03-2025 09:14:59","26-03-2025 10:2=
6:51","Grid outage .gen gailed to start due to card GE dysfunctionning //We=
 reset card GE and gen manually started ","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage .gen gailed to s=
tart due to card GE dysfunctionning //We reset card GE and gen manually sta=
rted ","ludovic-anselme.mouliom-mapoure@sagemcom","185","26-03-2025 09:18:0=
2","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004659844","Ole=
mbe MTN","","26-03-2025 08:37:12","26-03-2025 08:28:59","26-03-2025 13:42:5=
1","Grid outage,gen ran till fuel shortage//Grid Restored","Fabrice Pouakam=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran til=
l fuel shortage//Grid Restored","ludovic-anselme.mouliom-mapoure@sagemcom",=
"494","26-03-2025 08:37:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004659830","Mbeng","=
","26-03-2025 08:34:33","26-03-2025 08:25:39","26-03-2025 14:52:28","Cascad=
ed Incident from TTO4742217","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage gen ran until fuel shortage//Re=
fueling done","system","1329629","26-03-2025 08:34:33","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004659824","Tou=
ring Club International","","26-03-2025 08:33:20","26-03-2025 08:25:59","26=
-03-2025 14:08:39","Site went down due to Gen overload (20kva/20A) HIS SS p=
ascaline confirmed//Grid return ","Albran Byorel","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Site went down due to Gen overload (20kva=
/20A) HIS SS pascaline confirmed//Grid return ","ludovic-anselme.mouliom-ma=
poure@sagemcom","442","26-03-2025 08:33:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004659810","M=
om","IHS_YND_369","26-03-2025 08:27:52","26-03-2025 08:25:39","27-03-2025 1=
4:52:01","Grid outage gen ran until fuel shortage//Refueling done","Fanda B=
rice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen ran=
 until fuel shortage//Refueling done","ludovic-anselme.mouliom-mapoure@sage=
mcom","135","26-03-2025 08:27:52","Sagemcom CMR"
"Closed Complete","Site Down","T3446","IHS_YND_712","NOCINC0004659789","Nko=
lkoumou OCM","","26-03-2025 08:21:42","26-03-2025 08:16:30","27-03-2025 11:=
36:23","Site went down because Gen failed to start due to Grid bad voltage =
and No RCP on site // He bypass the Grid and Gen manaually started","TIENTC=
HEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Site went down because Gen failed to start due to Grid b=
ad voltage and No RCP on site // He bypass the Grid and Gen manaually start=
ed","ludovic-anselme.mouliom-mapoure@sagemcom","313","26-03-2025 08:21:42",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004659769","E=
ssomba","","26-03-2025 08:12:53","26-03-2025 08:07:42","26-03-2025 09:44:37=
","Site went down due to Fuel shortage //  Refueling done","Mba Lazare Herv=
e","Fuel Outage","Passive","Diesel","Diesel Outage","Site went down due to =
Fuel shortage //  Refueling done","ludovic-anselme.mouliom-mapoure@sagemcom=
","313","26-03-2025 08:12:53","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004659722","NYO=
M 2 IHS","","26-03-2025 08:02:58","26-03-2025 08:00:51","26-03-2025 08:30:4=
3","Grid outage.gen start and stopped due to alarm high temp //We add water=
 and gen manually started ","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.gen=
 start and stopped due to alarm high temp //We add water and gen manually s=
tarted ","landry.etame@ihstowers.com","129","26-03-2025 08:02:58","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0004659587","O=
kola OCM","","26-03-2025 07:36:24","26-03-2025 06:45:05","26-03-2025 08:08:=
58","Grid outage site went Gen ran until fuel shortage // Refueling done","=
TIENTCHEU NZETCHIEU GAEL","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage site went Gen ran until fuel shortage // Refueling done","ludo=
vic-anselme.mouliom-mapoure@sagemcom","3080","26-03-2025 07:36:24","Sagemco=
m CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004659586","AWA=
E OCM","","26-03-2025 07:35:44","26-03-2025 07:27:59","27-03-2025 13:31:47"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen start automatically","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen start automatically","lu=
dovic-anselme.mouliom-mapoure@sagemcom","466","26-03-2025 07:35:44","Sagemc=
om CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0004659565","Ole=
mbe","","26-03-2025 07:29:08","26-03-2025 07:17:55","27-03-2025 08:39:19","=
Site went down due to insufficiency of rectifiers // Site stabilized","Fabr=
ice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","S=
ite went down due to insufficiency of rectifiers // Site stabilized","ludov=
ic-anselme.mouliom-mapoure@sagemcom","674","26-03-2025 07:29:08","Sagemcom =
CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0004659527","Nko=
mo stade","","26-03-2025 07:21:32","26-03-2025 06:54:20","26-03-2025 06:55:=
40","No power issue site on grid with U=3D54V Flubert from Huawei is inform=
ed","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D54V=
 Flubert from Huawei is informed","landry.etame@ihstowers.com","1633","26-0=
3-2025 07:21:32","Sagemcom CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0004659520","Djo=
nassi-Yde","","26-03-2025 07:20:19","26-03-2025 06:36:24","26-03-2025 13:47=
:27","Grid outage .gen ran until fuel shortage//Refueling done","Fabrice Po=
uakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage .gen r=
an until fuel shortage//Refueling done","landry.etame@ihstowers.com","2635"=
,"26-03-2025 07:20:19","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004659504","SAA=
 Entrance","","26-03-2025 07:18:11","26-03-2025 06:31:05","26-03-2025 09:50=
:24","Grid outage.gen ran until fuel shortage//Refueling done","Parker Tcho=
up","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran u=
ntil fuel shortage//Refueling done","landry.etame@ihstowers.com","2828","26=
-03-2025 07:18:11","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004659502","BIY=
EMASSI NIKI","","26-03-2025 07:17:29","26-03-2025 06:26:23","26-03-2025 10:=
22:04","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d, F=E9lix Zambe is informed and confirmed","Hyemafo Gildas","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Site went down du=
e to PWC overloaded (12kva 250 A) //Site stabilized, F=E9lix Zambe is infor=
med and confirmed","landry.etame@ihstowers.com","3067","26-03-2025 07:17:29=
","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004659270","Awa=
e Ewonkan","","26-03-2025 06:12:52","26-03-2025 04:02:44","26-03-2025 09:07=
:48","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed//We reduce load and gen manually started ","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, Site went down because Gen overload(20KVA,310A) SS IHS Alphonse DEFF=
O is informed//We reduce load and gen manually started ","ferot.nongni-djio=
gap@sagemcom.com","7809","26-03-2025 06:12:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_169","NOCINC0004659179","Ekoumdou=
m","","26-03-2025 05:39:24","26-03-2025 03:56:18","26-03-2025 03:59:58","Gr=
id outage.gen start and stopped due to high temp alarm//We add water and ge=
n manually started ","Albran Byorel","Equipment Repair","Passive","ACDG Gen=
","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.gen start an=
d stopped due to high temp alarm//We add water and gen manually started ","=
joelle.ekessi@ihstowers.com","6187","26-03-2025 05:39:24","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004659152","Lad=
a I Yde","","26-03-2025 05:23:29","26-03-2025 04:53:10","26-03-2025 06:01:5=
7","Grid outage.gen ran until fuel shortage//Refueling done","Mba Lazare He=
rve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran =
until fuel shortage//Refueling done","ferot.nongni-djiogap@sagemcom.com","1=
820","26-03-2025 05:23:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004659002","Angongo"=
,"","26-03-2025 04:20:24","26-03-2025 04:07:09","26-03-2025 09:37:30","Casc=
aded Incident from TTO4741310","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Coupure ENEO et infiltration d'eau dans l=
a carte du GE // Demarrage du GE en mode force et trobleshooting de la cart=
e du GE","system","795","26-03-2025 04:20:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004659000","Nkenglik=
ok","","26-03-2025 04:20:23","26-03-2025 04:07:09","26-03-2025 09:37:30","C=
ascaded Incident from TTO4741310","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Coupure ENEO et infiltration d'eau=
 dans la carte du GE // Demarrage du GE en mode force et trobleshooting de =
la carte du GE","system","794","26-03-2025 04:20:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004658999","Mbankomo=
 IHS","","26-03-2025 04:20:23","26-03-2025 04:07:09","26-03-2025 09:37:30",=
"Cascaded Incident from TTO4741310","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Coupure ENEO et infiltration d'eau d=
ans la carte du GE // Demarrage du GE en mode force et trobleshooting de la=
 carte du GE","system","794","26-03-2025 04:20:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004659001","Mambine"=
,"","26-03-2025 04:20:23","26-03-2025 04:07:09","26-03-2025 09:37:30","Casc=
aded Incident from TTO4741310","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Coupure ENEO et infiltration d'eau dans l=
a carte du GE // Demarrage du GE en mode force et trobleshooting de la cart=
e du GE","system","794","26-03-2025 04:20:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0004658996","O=
KOA Peage","IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_350, IHS_YND_335=
, IHS_YND_349","26-03-2025 04:18:15","26-03-2025 04:07:09","26-03-2025 09:3=
7:30","Coupure ENEO et infiltration d'eau dans la carte du GE // Demarrage =
du GE en mode force et trobleshooting de la carte du GE","Fanda Brice","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Governor","Coupure ENEO et infi=
ltration d'eau dans la carte du GE // Demarrage du GE en mode force et trob=
leshooting de la carte du GE","ferot.nongni-djiogap@sagemcom.com","667","26=
-03-2025 04:18:15","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004658950","Ngo=
usso Vallee","","26-03-2025 03:54:39","26-03-2025 03:40:27","26-03-2025 07:=
28:42","Grid outage gen failed to start due to card GE dysfunctionned//We r=
eset card GE and gen manually started","Siligap Boris","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed to start=
 due to card GE dysfunctionned//We reset card GE and gen manually started",=
"ferot.nongni-djiogap@sagemcom.com","852","26-03-2025 03:54:39","Sagemcom C=
MR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004658946","Nko=
g-Edzen","","26-03-2025 03:53:48","26-03-2025 03:46:41","26-03-2025 03:47:0=
8","No power issue site on gen with U=3D54v Gregoire from Huawei is informe=
d","Parker Tchoup","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue site on gen with U=3D54v Greg=
oire from Huawei is informed","ferot.nongni-djiogap@sagemcom.com","428","26=
-03-2025 03:53:48","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004658942","Mes=
sa Carriere","","26-03-2025 03:51:25","26-03-2025 03:39:13","26-03-2025 04:=
43:13"," Site down due to rectifier issue // We have added a rectifier","Mb=
oua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module"," =
Site down due to rectifier issue // We have added a rectifier","ferot.nongn=
i-djiogap@sagemcom.com","733","26-03-2025 03:51:25","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004658939","Nko=
londom","","26-03-2025 03:50:27","26-03-2025 03:40:22","26-03-2025 04:03:22=
","Grid fluctuation, Site went down because Gen failed to start due to Grid=
 bad voltage and No RCP on site // He bypassed the Grid and Gen manually st=
arted","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation, Site went down because Gen failed=
 to start due to Grid bad voltage and No RCP on site // He bypassed the Gri=
d and Gen manually started","ferot.nongni-djiogap@sagemcom.com","607","26-0=
3-2025 03:50:27","Sagemcom CMR"
"Closed Complete","Site Down","T0578","IHS_YND_375","NOCINC0004658521","Ngo=
ung","","26-03-2025 01:43:30","26-03-2025 01:02:25","26-03-2025 08:03:23","=
Grid outage gen failed to start due to battery GE discharged //Gen manually=
 started with external battery","Kemeni Franklin","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Generator Battery","Grid outage gen failed to start =
due to battery GE discharged //Gen manually started with external battery",=
"ferot.nongni-djiogap@sagemcom.com","2466","26-03-2025 01:43:30","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0004658218","Nkolanga=
a","","26-03-2025 00:39:10","26-03-2025 00:17:55","26-03-2025 11:39:55","Ca=
scaded Incident from TTO4740410","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel sho=
rtage//Refueling done","system","1275","26-03-2025 00:39:10","Sagemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0004658186","Aba=
ng","IHS_YND_289","26-03-2025 00:29:04","26-03-2025 00:17:55","26-03-2025 1=
1:39:55","Grid outage.gen ran until fuel shortage//Refueling done","Mba Laz=
are Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.ge=
n ran until fuel shortage//Refueling done","ferot.nongni-djiogap@sagemcom.c=
om","670","26-03-2025 00:29:04","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004658183","OTE=
LE MTN","","26-03-2025 00:28:07","25-03-2025 23:59:57","26-03-2025 16:06:29=
","DG failed to start due low oil level in the engine  //  Oil added and ma=
nual start of DG","Fanda Brice","Equipment Repair","Passive","ACDG Gen","AC=
DG - Low Oil Pressure","DG failed to start due low oil level in the engine =
 //  Oil added and manual start of DG","ferot.nongni-djiogap@sagemcom.com",=
"1691","26-03-2025 00:28:07","Sagemcom CMR"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0004658078","COR=
NIERS","","25-03-2025 23:53:14","25-03-2025 23:41:38","26-03-2025 09:54:17"=
,"Grid outage no space to deploy mobile gen// Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","site Unstable/Grid o=
utage no space to deploy mobile gen ,awaiting Grid return","ferot.nongni-dj=
iogap@sagemcom.com","697","25-03-2025 23:53:14","Sagemcom CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0004657907","NYO=
M","","25-03-2025 23:13:20","25-03-2025 22:37:06","26-03-2025 11:45:30","DG=
 failed to start due to bad voltage eneo // eneo stabilized","Fabrice Pouak=
am","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply Is=
sue","DG failed to start due to bad voltage eneo // eneo stabilized","ferot=
.nongni-djiogap@sagemcom.com","2174","25-03-2025 23:13:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004657595","N=
kolfon Cimencam","","25-03-2025 22:02:05","25-03-2025 20:26:55","25-03-2025=
 20:27:11","No power issue site on grid with U=3D54v Mbah Osiah from Huawei=
 is informed Notice that site is the repetivie issue ","Hyemafo Gildas","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue site on grid with U=3D54v Mbah Osiah from Huawei is=
 informed Notice that site is the repetivie issue ","ferot.nongni-djiogap@s=
agemcom.com","5711","25-03-2025 22:02:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0004657323","M=
asque","","25-03-2025 21:32:59","25-03-2025 16:53:42","26-03-2025 00:40:24"=
,"Grid outage, site went down because gen ran untill fuel shortage // Refue=
ling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage, site went down because gen ran untill fuel shortage // Ref=
ueling done","el-dalile@sagemcom.com","16759","25-03-2025 21:32:59","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004657219","O=
mnisport-Rail","","25-03-2025 21:10:47","25-03-2025 20:43:40","25-03-2025 2=
1:58:57","Site went down due to insufficiency of rectifiers due to increase=
 load (SS IHS BERNAD is informed) // Load reduice: Site on grid","Delor Tel=
ezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Site we=
nt down due to insufficiency of rectifiers due to increase load (SS IHS BER=
NAD is informed) // Load reduice: Site on grid","mariam.tchonang@sagemcom.c=
om","1659","25-03-2025 21:10:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004657090","Bitoto",=
"","25-03-2025 20:49:04","25-03-2025 20:18:00","25-03-2025 20:52:20","Casca=
ded Incident from TTO4739139","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down because g=
en fails to start // Grid return (Investigation ongoing)","system","665391"=
,"25-03-2025 20:49:04","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004657043","Nko=
abang MTN","IHS_YND_292, IHS_YND_796","25-03-2025 20:44:16","25-03-2025 20:=
18:00","25-03-2025 20:52:20","Grid outage, site went down because gen fails=
 to start // Grid return (Investigation ongoing)","Mba Lazare Herve","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went=
 down because gen fails to start // Grid return (Investigation ongoing)","f=
erot.nongni-djiogap@sagemcom.com","1577","25-03-2025 20:44:16","Sagemcom CM=
R"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004656993","Nom=
ayos montee Meche","","25-03-2025 20:34:00","25-03-2025 16:49:31","28-03-20=
25 12:09:26","Access issue due to noise because landlord refuse to start ge=
n //Grid return","Fanda Brice","Access Denial","Lease Or Legal","Landlord R=
elated Issues","Access Issue - Land Lord","Access issue due to noise becaus=
e landlord refuse to start gen ","ferot.nongni-djiogap@sagemcom.com","13470=
","25-03-2025 20:34:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004656924","S=
AA 2","IHS_YND_405","25-03-2025 20:15:33","25-03-2025 18:49:03","25-03-2025=
 22:30:06","Ulrich is informed and says that, no car to reach on site, our =
supervisor is informed","Parker Tchoup","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid outage, site went down because gen fails =
to start due to battery ge discharged // Gen start with battery backup(Inve=
stigation ongoing)","stephane.nkamwa@ihstowers.com","5191","25-03-2025 20:1=
5:33","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004656789","Nko=
ulou Carriere carrefourt","","25-03-2025 19:51:53","25-03-2025 19:29:37","2=
5-03-2025 21:13:37","Site went down due to 2/4 Rectifiers Dysfunctionning /=
/ He reset it: Site on grid","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Cabinet","Site went down due to 2/4 Rectifiers Dys=
functionning // He reset it: Site on grid","el-dalile@sagemcom.com","1337",=
"25-03-2025 19:51:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0004656583","T=
SINGA VILLAGE 2","","25-03-2025 19:17:32","25-03-2025 19:11:12","25-03-2025=
 20:41:36","Site went down because gen start an stopped due to water infilt=
ration in tank // He purged The tank and Gen manually started","Delor Telez=
ing","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Wate=
r In The Fuel","Site went down because gen start an stopped due to water in=
filtration in tank // He purged The tank and Gen manually started","ferot.n=
ongni-djiogap@sagemcom.com","381","25-03-2025 19:17:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004656487","S=
imbock OCM","","25-03-2025 19:01:00","25-03-2025 17:55:44","25-03-2025 21:5=
8:06","Site went down because gen fails to start due to grid bad voltage //=
 He bypass grid and manually start the gen","Hyemafo Gildas","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Site went down =
because gen fails to start due to grid bad voltage // He bypass grid and ma=
nually start the gen","stephane.nkamwa@ihstowers.com","3917","25-03-2025 19=
:01:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0004656359","Mendong =
Maeture","","25-03-2025 18:40:02","25-03-2025 16:51:33","25-03-2025 19:29:5=
8","Cascaded Incident from TTO4738049","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,gen ran till fuel =
shortage//Grid return
","system","277934","25-03-2025 18:40:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0004656360","Montee-J=
ouvence","","25-03-2025 18:40:02","25-03-2025 16:51:33","25-03-2025 19:29:5=
8","Cascaded Incident from TTO4738049","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,gen ran till fuel =
shortage//Grid return
","system","277935","25-03-2025 18:40:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0004656358","Mendong =
vallee","","25-03-2025 18:40:02","25-03-2025 16:51:33","25-03-2025 19:29:58=
","Cascaded Incident from TTO4738049","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,gen ran till fuel shor=
tage//Grid return
","system","277935","25-03-2025 18:40:02","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004656273","Car=
refour Simbock","","25-03-2025 18:24:20","25-03-2025 17:30:37","26-03-2025 =
03:32:37","Grid outage gen ran until fuel shortage//Refueling done","Hyemaf=
o Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen=
 ran until fuel shortage//Refueling done","ferot.nongni-djiogap@sagemcom.co=
m","3224","25-03-2025 18:24:20","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004656134","Men=
dong NB","","25-03-2025 17:55:11","25-03-2025 17:32:53","25-03-2025 18:10:5=
3","Grid only, Eneo outage, no space to deploy MGE // eneo return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only, E=
neo outage, no space to deploy MGE // eneo return","el-dalile@sagemcom.com"=
,"1339","25-03-2025 17:55:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004656103","N=
gouetou","","25-03-2025 17:49:15","25-03-2025 15:41:01","25-03-2025 17:45:3=
8","Site went down because gen start and stopped with high temp alarm // He=
 added water and manually start the gen","Parker Tchoup","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Site=
 went down because gen start and stopped with high temp alarm // He added w=
ater and manually start the gen","el-dalile@sagemcom.com","7696","25-03-202=
5 17:49:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004656072","M=
endong","IHS_YND_692, IHS_YND_569, IHS_YND_236","25-03-2025 17:42:45","25-0=
3-2025 16:51:33","25-03-2025 19:29:58","Grid outage,gen ran till fuel short=
age//Grid return","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage,gen ran till fuel shortage//Grid return
","el-dalile@sagemcom.com","3073","25-03-2025 17:42:45","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004655782","Mes=
sassi 2","","25-03-2025 16:49:12","25-03-2025 16:44:59","26-03-2025 21:30:5=
9","Grid outage, site went down because gen start and stopped due to high t=
emp // He added water and manually start the gen","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, site went do=
wn because gen start and stopped due to high temp // He added water and man=
ually start the gen","el-dalile@sagemcom.com","254","25-03-2025 16:49:12","=
Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004655768","Mvo=
g-Manga","","25-03-2025 16:45:53","25-03-2025 16:25:37","27-03-2025 01:26:3=
7","Grid outage.gen start and stopped due to alarm high temp //We add water=
 and gen manually started ","Albran Byorel","Equipment Repair","Passive","A=
CDG Gen","ACDG - High Engine Temp - Coolant Level Issue"," Grid outage.gen =
start and stopped due to alarm high temp //We add water and gen manually st=
arted ","rouselle.schoune@ihstowers.com","1218","25-03-2025 16:45:53","Sage=
mcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004655678","Mon=
tee Jouvence","","25-03-2025 16:31:51","25-03-2025 16:15:39","26-03-2025 02=
:04:31","Grid outage, site went down because gen ran untill fuel shortage /=
/ Grid power return (Refueling ongoing)","Hyemafo Gildas","Fuel Outage","Pa=
ssive","Diesel","Diesel Outage","Grid outage, site went down because gen ra=
n untill fuel shortage // Grid power return (Refueling ongoing)","ferot.non=
gni-djiogap@sagemcom.com","973","25-03-2025 16:31:51","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004655646","Ako=
k Ndoe Yde","","25-03-2025 16:26:23","25-03-2025 15:11:10","25-03-2025 17:0=
5:54","Grid outage,gen ran till fuel shortage//Grid return","Hyemafo Gildas=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran til=
l fuel shortage//Grid return
","el-dalile@sagemcom.com","4514","25-03-2025 16:26:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004655504","B=
iteng","","25-03-2025 16:06:47","25-03-2025 15:37:22","25-03-2025 16:42:47"=
,"Grid outage site went down because Gen failed to start due PWC dysfonctio=
n // He reset the PWC and Gen manually started","Mba Lazare Herve","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage=
 site went down because Gen failed to start due PWC dysfonction // He reset=
 the PWC and Gen manually started","mariam.tchonang@sagemcom.com","1805","2=
5-03-2025 16:06:47","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004655442","Bit=
eng-Maetur","","25-03-2025 16:03:11","25-03-2025 15:18:33","25-03-2025 17:4=
6:32","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the l=
oad","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, Site went down because Gen started and stopped due to =
Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the =
load","el-dalile@sagemcom.com","2680","25-03-2025 16:03:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004655430","Akono","=
","25-03-2025 16:00:55","25-03-2025 15:18:12","25-03-2025 16:01:18","Cascad=
ed Incident from TTO4737162","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue : site on grid, 54.3 V. TX FME =
681953783/Huawei was working in the site ","system","369914","25-03-2025 16=
:00:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004655431","NKONGKAR=
AK","","25-03-2025 16:00:55","25-03-2025 15:18:12","25-03-2025 16:01:18","C=
ascaded Incident from TTO4737162","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue : site on gri=
d, 54.3 V. TX FME 681953783/Huawei was working in the site ","system","3699=
19","25-03-2025 16:00:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0004655429","LOBO MTN=
","","25-03-2025 16:00:54","25-03-2025 15:18:12","25-03-2025 16:01:18","Cas=
caded Incident from TTO4737162","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue : site on grid,=
 54.3 V. TX FME 681953783/Huawei was working in the site ","system","369915=
","25-03-2025 16:00:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_310","NOCINC0004655427","Nomayos"=
,"","25-03-2025 16:00:54","25-03-2025 15:18:12","25-03-2025 16:01:18","Casc=
aded Incident from TTO4737162","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue : site on grid, 54.3 V. TX FM=
E 681953783/Huawei was working in the site ","system","369917","25-03-2025 =
16:00:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0004655428","Ekekam",=
"","25-03-2025 16:00:54","25-03-2025 15:18:12","25-03-2025 16:01:18","Casca=
ded Incident from TTO4737162","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue : site on grid, 5=
4.3 V. TX FME 681953783/Huawei was working in the site ","system","369915",=
"25-03-2025 16:00:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004655426","Nkongtoc=
k","","25-03-2025 16:00:54","25-03-2025 15:18:12","26-03-2025 09:37:30","Ca=
scaded Incident from TTO4737162","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue : site on grid, 54.3 V.=
 TX FME 681953783/Huawei was working in the site ","system","369920","25-03=
-2025 16:00:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004655422","Ebeba","=
","25-03-2025 16:00:53","25-03-2025 15:18:12","26-03-2025 09:37:30","Cascad=
ed Incident from TTO4737162","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue : site on grid, 54.3 V. TX FME =
681953783/Huawei was working in the site ","system","369918","25-03-2025 16=
:00:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_706","NOCINC0004655425","Mbankomo=
 CAF","","25-03-2025 16:00:53","25-03-2025 15:18:12","25-03-2025 16:01:18",=
"Cascaded Incident from TTO4737162","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue : site on grid, 54.3 V. =
TX FME 681953783/Huawei was working in the site ","system","369914","25-03-=
2025 16:00:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0004655423","Bot Maka=
k","","25-03-2025 16:00:53","25-03-2025 15:18:12","25-03-2025 16:01:18","Ca=
scaded Incident from TTO4737162","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","No power issue : site on grid, 54.3 V. TX FME 6819537=
83/Huawei was working in the site ","system","369916","25-03-2025 16:00:53"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004655419","OLAMA","=
","25-03-2025 16:00:52","25-03-2025 15:18:12","25-03-2025 16:01:18","Cascad=
ed Incident from TTO4737162","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue : site on grid, 54.3 V. TX FME =
681953783/Huawei was working in the site ","system","369916","25-03-2025 16=
:00:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0004655420","Nkeng li=
kok","","25-03-2025 16:00:52","25-03-2025 15:18:12","25-03-2025 16:01:18","=
Cascaded Incident from TTO4737162","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue : site on grid, 54.3 =
V. TX FME 681953783/Huawei was working in the site ","system","369920","25-=
03-2025 16:00:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0004655421","Ngog Map=
ubi","","25-03-2025 16:00:52","25-03-2025 15:18:12","25-03-2025 16:01:18","=
Cascaded Incident from TTO4737162","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue : site on grid, 54.3 =
V. TX FME 681953783/Huawei was working in the site ","system","369917","25-=
03-2025 16:00:52","Sagemcom CMR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0004655292","Sou=
s Prefecture","IHS_YND_687, IHS_YND_347, IHS_YND_419, IHS_YND_339, IHS_YND_=
421, IHS_YND_706, IHS_YND_371, IHS_YND_349, IHS_YND_310, IHS_YND_714, IHS_Y=
ND_342, IHS_YND_365, IHS_YND_713","25-03-2025 15:43:44","25-03-2025 15:18:1=
2","25-03-2025 16:01:18","No power issue : site on grid, 54.3 V. TX FME 681=
953783/Huawei was working in the site ","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue : site on grid, 54.3 V. TX FME 681953783/Huawei was working in the si=
te ","el-dalile@sagemcom.com","1533","25-03-2025 15:43:44","Sagemcom CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0004655181","OKO=
A Peage","","25-03-2025 15:26:29","25-03-2025 15:07:05","25-03-2025 20:30:2=
2","Grid outage, site went down because gen ran untill fuel shortage // Ref=
ueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage, site went down because gen ran untill fuel shortage // Refue=
ling done","ferot.nongni-djiogap@sagemcom.com","1165","25-03-2025 15:26:29"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0004655179","EBOM",""=
,"25-03-2025 15:26:03","25-03-2025 15:08:25","25-03-2025 18:38:55","Cascade=
d Incident from TTO4736991","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid Outage Site went down due to Main Ge=
n Faulty//Grid Restored (SS Fran=E7ois is informed and Confirmed)","system"=
,"284176","25-03-2025 15:26:03","Sagemcom CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0004655146","Nsi=
meyong","IHS_YND_698, IHS_YND_261","25-03-2025 15:19:34","25-03-2025 15:08:=
25","25-03-2025 18:38:55","Grid Outage Site went down due to Main Gen Fault=
y//Grid Restored (SS Fran=E7ois is informed and Confirmed)","MINKA NICOLAS"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid Ou=
tage Site went down due to Main Gen Faulty//Grid Restored (SS Fran=E7ois is=
 informed and Confirmed)","ferot.nongni-djiogap@sagemcom.com","670","25-03-=
2025 15:19:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004655128","N=
koabang Ebolmedjock","","25-03-2025 15:16:09","25-03-2025 15:02:02","25-03-=
2025 20:20:20","No power issue site on grid with U=3D54v Notice that site i=
s impacted by Nkolmesseng Abom which is not our responsability","Mba Lazare=
 Herve","Cascade Outage","Passive","Cascade Passive","Cascade Passive","No =
power issue site on grid with U=3D54v Notice that site is impacted by Nkolm=
esseng Abom which is not our responsability","ferot.nongni-djiogap@sagemcom=
.com","847","25-03-2025 15:16:09","Sagemcom CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004654962","Imm=
-Olympique","","25-03-2025 14:48:59","25-03-2025 14:31:50","25-03-2025 16:3=
1:50","Grid outage,gen failed to start due to alarm overccurent//he reset i=
t and started the gen","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen=
","ACDG - Control Panel","Grid outage,gen failed to start due to alarm over=
ccurent//he reset it and started the gen","el-dalile@sagemcom.com","1030","=
25-03-2025 14:48:59","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004654768","Jou=
vence Mbenda","","25-03-2025 14:13:52","25-03-2025 14:11:38","25-03-2025 19=
:06:26","Grid outage .gen ran until fuel shortage//Refueling done","Hyemafo=
 Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage .gen=
 ran until fuel shortage//Refueling done","danick.tchakouani@sagemcom.com",=
"135","25-03-2025 14:13:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_201","IHS_YND_368","NOCINC0004654716","O=
tele","","25-03-2025 14:04:21","25-03-2025 13:45:04","25-03-2025 17:02:11",=
"Grid outage, Site went down because Gen failed to start due to battery Gen=
 faulty// He started Gen with external battery","Fanda Brice","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, Site we=
nt down because Gen failed to start due to battery Gen faulty// He started =
Gen with external battery","ludivine.ngamaleu@ihstowers.com","1158","25-03-=
2025 14:04:21","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004654644","Ole=
mbe MTN","","25-03-2025 13:54:37","25-03-2025 13:47:11","25-03-2025 17:32:2=
9","Site went down due to insufficiency of rectifiers on site SS IHS felix =
Zambe is informed//site stabilized(need to add 01 rectifier)","Fabrice Poua=
kam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went=
 down due to insufficiency of rectifiers on site SS IHS felix Zambe is info=
rmed//site stabilized(need to add 01 rectifier)","danick.tchakouani@sagemco=
m.com","447","25-03-2025 13:54:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004654502","Barriere=
 IHS","","25-03-2025 13:34:24","25-03-2025 13:11:12","25-03-2025 14:33:37",=
"Cascaded Incident from TTO4736232","Hyemafo Gildas","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because Gen overlo=
ad(15kva,200 A) IHS SS Felix Zambe is informed and confirmed // Grid return=
","system","427793","25-03-2025 13:34:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004654495","M=
efou-Assi","IHS_YND_696","25-03-2025 13:33:37","25-03-2025 13:11:12","25-03=
-2025 14:33:37","Site went down because Gen overload(15kva,200 A) IHS SS Fe=
lix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Site went down because Ge=
n overload(15kva,200 A) IHS SS Felix Zambe is informed and confirmed // Gri=
d return","danick.tchakouani@sagemcom.com","1346","25-03-2025 13:33:37","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2795","IHS_YND_070","NOCINC0004654437","Efo=
ulan","","25-03-2025 13:22:37","25-03-2025 13:16:15","25-03-2025 13:31:15",=
"Grid outage,gen ran till fuel shortage//Refueling done","MINKA NICOLAS","F=
uel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran till fu=
el shortage//Refueling done","danick.tchakouani@sagemcom.com","384","25-03-=
2025 13:22:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004654434","Minka","=
","25-03-2025 13:22:10","25-03-2025 13:13:37","25-03-2025 17:13:47","Cascad=
ed Incident from TTO4736127","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by OTELE Camarail no manager by IHS
","system","377394","25-03-2025 13:22:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004654433","Mbeng","=
","25-03-2025 13:22:10","25-03-2025 13:13:37","25-03-2025 17:13:47","Cascad=
ed Incident from TTO4736127","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Grid with U=3D5=
3,3 V The FME TX Etienne(695033981) From Huawei is informed. Site impacted =
by OTELE Camarail no manager by IHS
","system","312541","25-03-2025 13:22:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004654409","M=
om","IHS_YND_369, IHS_YND_371","25-03-2025 13:19:48","25-03-2025 13:13:37",=
"25-03-2025 13:20:47","Active//No power issue site on Grid with U=3D53,3 V =
The FME TX Etienne(695033981) From Huawei is informed. Site impacted by OTE=
LE Camarail no manager by IHS","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue site on Grid with U=3D53,3 V The FME TX Etienne(695033981) From Huawei=
 is informed. Site impacted by OTELE Camarail no manager by IHS
","mariam.tchonang@sagemcom.com","373","25-03-2025 13:19:48","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004654406","Men=
dong3","","25-03-2025 13:18:12","25-03-2025 13:02:00","25-03-2025 19:03:21"=
,"Grid outage, no space to deploy MDG // Grid return ","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage, no space to=
 deploy MDG // Grid return ","danick.tchakouani@sagemcom.com","973","25-03-=
2025 13:18:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0004654320","C=
hapelle-Nsimeyong","","25-03-2025 13:02:36","25-03-2025 12:41:18","25-03-20=
25 13:08:03","Grid outage,gen ran till fuel shortage//Refueling done","MINK=
A NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,ge=
n ran till fuel shortage//Refueling done","mariam.tchonang@sagemcom.com","1=
279","25-03-2025 13:02:36","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004654318","Mam=
bine","","25-03-2025 13:01:56","25-03-2025 12:53:38","25-03-2025 13:17:38",=
"Grid outage site went down because Gen failed to start // Grid return (inv=
estigation ongoing)","Fanda Brice","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Grid outage site went down because Gen failed to st=
art // Grid return (investigation ongoing)","danick.tchakouani@sagemcom.com=
","499","25-03-2025 13:01:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004654279","N=
koabang Ebolmedjock","","25-03-2025 12:54:43","25-03-2025 12:45:59","25-03-=
2025 12:46:59","Active//No power issue, Site on Gen. The Tx FME Brice Tsagu=
e(650214096) from Huawei is informed. Notice that it is impacted by Nkolmes=
seng-Abom Not Manager By IHS","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue, Site on Gen. The Tx FME Brice Tsague(650214096) from Huawei is in=
formed. Notice that it is impacted by Nkolmesseng-Abom Not Manager By IHS",=
"danick.tchakouani@sagemcom.com","525","25-03-2025 12:54:43","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004654265","MBA=
LNGONG LYCEE","","25-03-2025 12:51:31","25-03-2025 12:43:11","25-03-2025 17=
:39:12","Grid Outage Site went down due to Gen overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went d=
own due to Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and conf=
irmed // Grid return","danick.tchakouani@sagemcom.com","501","25-03-2025 12=
:51:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004654097","M=
essa-Carriere OCM","","25-03-2025 12:25:48","25-03-2025 12:11:59","26-03-20=
25 15:17:00","Grid only, Eneo outage, no space to deploy MGE // eneo return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id only, Eneo outage, no space to deploy MGE // eneo return","danick.tchako=
uani@sagemcom.com","830","25-03-2025 12:25:48","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004654088","Beh=
ind P T school Yde","","25-03-2025 12:23:28","25-03-2025 12:11:12","25-03-2=
025 15:22:52","Site went down because 01/03 rectifiers went faulty// He add=
ed 1 rectifier","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down because 01/03 rectifiers went faulty// He ad=
ded 1 rectifier","danick.tchakouani@sagemcom.com","737","25-03-2025 12:23:2=
8","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004653733","A=
wae Ewonkan","","25-03-2025 12:00:05","25-03-2025 11:55:28","25-03-2025 12:=
17:28","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // =
He reduced the load","mariam.tchonang@sagemcom.com","279","25-03-2025 12:00=
:05","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004653716","NYO=
M 2 IHS","","25-03-2025 11:59:19","25-03-2025 11:50:59","25-03-2025 13:21:5=
9","Grid outage,gen stopped with alarm high temp//he added water in radiato=
r","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","Grid outage,gen stopped with alarm high =
temp//he added water in radiator","danick.tchakouani@sagemcom.com","502","2=
5-03-2025 11:59:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004653663","E=
koumdoum","","25-03-2025 11:56:04","25-03-2025 11:46:59","25-03-2025 12:14:=
59","Grid fluctuation, Site went down because gen fails to start due to gri=
d bad voltage,no rcp// He bypassed the Grid and site on Gen","Albran Byorel=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation, Site went down because gen fails to start due to grid ba=
d voltage,no rcp// He bypassed the Grid and site on Gen","danick.tchakouani=
@sagemcom.com","546","25-03-2025 11:56:04","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004653645","Tou=
ring Club International","","25-03-2025 11:52:35","25-03-2025 11:47:58","25=
-03-2025 11:51:58","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed // Grid return","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went down=
 because Gen overload (20Kw, 270A) SS IHS Pascaline confirmed // Grid retur=
n","danick.tchakouani@sagemcom.com","278","25-03-2025 11:52:35","Sagemcom C=
MR"
"Closed Complete","Warning","T0351","IHS_YND_146","NOCINC0004653642","Nsime=
yong","","25-03-2025 11:52:26","","","eneo outage // eneo return","MINKA NI=
COLAS","Warning","Warning","POWER","Warning - Site on Battery","eneo outage=
 // eneo return","cedric.tiani@sagemcom.com","2171","25-03-2025 11:52:26","=
Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0004653636","Nko=
mo stade","","25-03-2025 11:51:06","25-03-2025 11:46:58","25-03-2025 12:20:=
58","Grid outage, Site went down before Gen start due to poor backup/ // Ge=
n automatically started","Mba Lazare Herve","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup/ // Gen automatically started","danick.tc=
hakouani@sagemcom.com","248","25-03-2025 11:51:06","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0004653594","MVA=
N SACEL","","25-03-2025 11:44:24","25-03-2025 11:35:51","25-03-2025 11:53:5=
1","Site went down because 01/06 rectifiers went faulty// He removed rectif=
ier faulty(site on 05)","MINKA NICOLAS","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down because 01/06 rectifiers went faul=
ty// He removed rectifier faulty(site on 05)","danick.tchakouani@sagemcom.c=
om","514","25-03-2025 11:44:24","Sagemcom CMR"
"Closed Complete","Warning","CTR_046","IHS_YND_008","NOCINC0004653554","CND=
H","","25-03-2025 11:39:51","","","site on battery // Alarm cleared","Paul =
BIBOUM","Warning","Warning","POWER","Warning - Battery Failure","site on ba=
ttery // Alarm cleared","cedric.tiani@sagemcom.com","1332","25-03-2025 11:3=
9:51","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004653519","AWA=
E OCM","","25-03-2025 11:34:33","25-03-2025 11:25:59","25-03-2025 11:35:59"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen st=
arted automatically","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Gen started automatically","danick.tchakou=
ani@sagemcom.com","515","25-03-2025 11:34:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004653497","B=
iteng-Maetur","","25-03-2025 11:30:44","25-03-2025 11:29:29","25-03-2025 12=
:21:48","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the=
 load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen started and stopped due t=
o Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced th=
e load","mariam.tchonang@sagemcom.com","77","25-03-2025 11:30:44","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004653489","M=
ontee-Des-Soeurs","","25-03-2025 11:29:14","25-03-2025 11:23:20","25-03-202=
5 13:15:59","Grid outage, site went down before gen start due to poor batte=
ry backup // Gen start manually","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // Gen start manually","mar=
iam.tchonang@sagemcom.com","355","25-03-2025 11:29:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004653485","M=
EHANDAN","","25-03-2025 11:27:52","25-03-2025 11:23:39","25-03-2025 12:45:3=
9","Site went down due to insufficiency of rectifiers on site SS IHS Pascal=
ine is confirm // He reduced the load","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down due to insufficienc=
y of rectifiers on site SS IHS Pascaline is confirm // He reduced the load"=
,"mariam.tchonang@sagemcom.com","255","25-03-2025 11:27:52","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004653400","NTU=
I TOWN","","25-03-2025 11:07:06","25-03-2025 10:57:59","25-03-2025 13:45:20=
","Grid outage.Gen ran until fuelsfortage//Grid Restored","Parker Tchoup","=
Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.Gen ran until =
fuelsfortage//Grid Restored","danick.tchakouani@sagemcom.com","548","25-03-=
2025 11:07:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004653249","M=
vog-Manga","","25-03-2025 10:45:33","25-03-2025 10:36:19","25-03-2025 11:08=
:19","Site went down because gen fails to start due to grid bad voltage // =
He bypass grid and manually start the gen","Albran Byorel","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Site went down because =
gen fails to start due to grid bad voltage // He bypass grid and manually s=
tart the gen","mariam.tchonang@sagemcom.com","556","25-03-2025 10:45:33","S=
agemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004653015","Nom=
ayos montee Meche","","25-03-2025 10:18:00","25-03-2025 10:15:31","25-03-20=
25 11:45:31","Grid outage, site went down because gen start and stopped wit=
h emergency stop alarm // He manually start the gen(Investigation ongoing)"=
,"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, site went down because gen start and stopped with emergenc=
y stop alarm // He manually start the gen(Investigation ongoing)","danick.t=
chakouani@sagemcom.com","150","25-03-2025 10:18:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_258","NOCINC0004652920","Mefou-As=
si","IHS_YND_696","25-03-2025 09:59:34","25-03-2025 09:44:10","25-03-2025 1=
0:28:10","Grid outage, site went down because gen fails to start due to gen=
 overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // He reduice the loa=
d and manually start the gen","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, site went down because gen fails t=
o start due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // =
He reduice the load and manually start the gen","system","924","25-03-2025 =
09:59:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004652881","M=
EFOU ASSI","","25-03-2025 09:56:13","25-03-2025 09:44:56","25-03-2025 10:28=
:56","Grid fluctuation,Site went down because Gen failed to start due to Gr=
id bad voltage, on site//He bypassed the Grid and gen manually started","Fa=
nda Brice","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","Grid fluctuation,Site went down because Gen failed to start due t=
o Grid bad voltage, on site//He bypassed the Grid and gen manually started"=
,"mariam.tchonang@sagemcom.com","1088","25-03-2025 09:56:13","Sagemcom CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0004652873","TON=
GOLO SNEC","","25-03-2025 09:54:56","25-03-2025 09:53:29","25-03-2025 10:51=
:02","Grid outage.gen ran until fuel shortage//Refueling done","Fabrice Pou=
akam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran=
 until fuel shortage//Refueling done","danick.tchakouani@sagemcom.com","88"=
,"25-03-2025 09:54:56","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004652848","Men=
dong vallee","","25-03-2025 09:50:17","25-03-2025 09:43:06","25-03-2025 10:=
47:06","Grid outage site went down because Gen over load (20KVA; 300A) // G=
rid return IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site we=
nt down because Gen over load (20KVA; 300A) // Grid return IHS F=E9lix Zamb=
=E9 is informed and confirmed","danick.tchakouani@sagemcom.com","432","25-0=
3-2025 09:50:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004652836","B=
arriere IHS","","25-03-2025 09:48:25","25-03-2025 09:44:10","25-03-2025 10:=
28:10","Grid outage, site went down because gen fails to start due to gen o=
verload(15Kva, 200A) SS IHS FELIX ZAMBE is informed // He reduice the load =
and manually start the gen","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen f=
ails to start due to gen overload(15Kva, 200A) SS IHS FELIX ZAMBE is inform=
ed // He reduice the load and manually start the gen","mariam.tchonang@sage=
mcom.com","267507","25-03-2025 09:48:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_546","IHS_YND_419","NOCINC0004652825","N=
gog Mapubi","","25-03-2025 09:45:58","25-03-2025 09:36:21","25-03-2025 12:4=
4:51","Active// No power issue on site ,site on Gen with Ubaie=3D 54,6V The=
 fme tx Etienne fopa // 695033981 of huawei is informed ","Kemeni Franklin"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active// No power issue on site ,site on Gen with Ubaie=3D 54,=
6V The fme tx Etienne fopa // 695033981 of huawei is informed ","mariam.tch=
onang@sagemcom.com","578","25-03-2025 09:45:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004652743","S=
hell-Nsimeyong","","25-03-2025 09:34:05","25-03-2025 09:30:58","25-03-2025 =
11:45:55","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed. Repetitive Issue","MINKA NICOL=
AS","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosi=
ah (674007438/699699694) from Huawei is informed. Repetitive Issue","mariam=
.tchonang@sagemcom.com","189","25-03-2025 09:34:05","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004652647","SIM=
BOCK BONAMBAPE","IHS_YND_537","25-03-2025 09:24:34","25-03-2025 09:15:56","=
25-03-2025 10:28:56","Grid outage.gen ran until fuel shortage ","Hyemafo Gi=
ldas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran=
 until fuel shortage ","danick.tchakouani@sagemcom.com","519","25-03-2025 0=
9:24:34","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004652417","Elo=
umdem stade","","25-03-2025 08:27:35","25-03-2025 08:21:17","25-03-2025 11:=
19:17","Grid outage, site went down because gen ran until fuel shortage // =
Refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran until fuel shortage // Ref=
ueling done","danick.tchakouani@sagemcom.com","379","25-03-2025 08:27:35","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004652396","M=
ontee-Jouvence-II","","25-03-2025 08:24:48","25-03-2025 08:19:27","25-03-20=
25 10:06:27","Site went down due to PWC Overloaded (12K, 250A) // site stab=
ilized SS IHS Alphonse confirmed //He reduice Load and manually started gen=
","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","Site went down due to PWC Overloaded (12K, 250A) // site st=
abilized SS IHS Alphonse confirmed //He reduice Load and manually started g=
en","mariam.tchonang@sagemcom.com","323","25-03-2025 08:24:48","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0004652137","Monatele=
","","25-03-2025 07:09:55","25-03-2025 06:59:56","25-03-2025 09:43:14","Cas=
caded Incident from TTO4733587","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage.Gen ran until fuelsfortage=
//Grid Restored","system","277389","25-03-2025 07:09:55","Sagemcom CMR"
"Closed Complete","Site Down","T0053","IHS_YND_407","NOCINC0004652135","Mon=
atele MTN","IHS_YND_406","25-03-2025 07:09:15","25-03-2025 06:59:56","25-03=
-2025 09:49:38","Grid outage.Gen ran until fuelsfortage//Grid Restored","Pa=
rker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.=
Gen ran until fuelsfortage//Grid Restored","danick.tchakouani@sagemcom.com"=
,"560","25-03-2025 07:09:15","Sagemcom CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004652003","Pha=
rmacie Bleue","","25-03-2025 06:42:00","25-03-2025 06:17:46","25-03-2025 07=
:57:53","Site went down Gen failed to start due to Grid bad voltage(lack of=
 02 phases on site)// He did a bridge on the Good phase","Siligap Boris","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Sit=
e went down Gen failed to start due to Grid bad voltage(lack of 02 phases o=
n site)// He did a bridge on the Good phase","mariam.tchonang@sagemcom.com"=
,"1455","25-03-2025 06:42:00","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0004651879","San=
ta Barbara Gottam","","25-03-2025 05:48:07","25-03-2025 05:42:56","25-03-20=
25 06:04:23","Grid outage, Site went down because Gen failed to start with =
""overcurrent"" alarm// He reset Gen card and started Gen manually","Delor =
Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, Site went down because Gen failed to start with ""overcurrent""=
 alarm// He reset Gen card and started Gen manually","ferot.nongni-djiogap@=
sagemcom.com","312","25-03-2025 05:48:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0004651787","Lobo 2",=
"","25-03-2025 05:17:51","25-03-2025 04:51:24","25-03-2025 09:29:24","Casca=
ded Incident from TTO4733199","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because PWC dy=
sfunctioning // Reconfigation of PWC done, Site on Gen","system","285081","=
25-03-2025 05:17:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004651788","NKONGKAR=
AK","","25-03-2025 05:17:51","25-03-2025 04:51:24","25-03-2025 09:29:24","C=
ascaded Incident from TTO4733199","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because PW=
C dysfunctioning // Reconfigation of PWC done, Site on Gen","system","28508=
1","25-03-2025 05:17:51","Sagemcom CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0004651779","LOB=
O MTN","IHS_YND_783, IHS_YND_714, IHS_YND_713","25-03-2025 05:15:41","25-03=
-2025 04:51:24","25-03-2025 09:29:24","Site went down because PWC dysfuncti=
oning // Reconfigation of PWC done, Site on Gen","TIENTCHEU NZETCHIEU GAEL"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Si=
te went down because PWC dysfunctioning // Reconfigation of PWC done, Site =
on Gen","ferot.nongni-djiogap@sagemcom.com","1458","25-03-2025 05:15:41","S=
agemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004651770","Ngo=
usso Vallee","","25-03-2025 05:12:40","25-03-2025 04:40:30","25-03-2025 06:=
43:43","Grid outage, Site went down because Gen started and stopped with ""=
low oil pressure"" alarm// He reset card GE and gen manually started","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, Site went down because Gen started and stopped with ""low oil =
pressure"" alarm// He reset card GE and gen manually started","ferot.nongni=
-djiogap@sagemcom.com","1931","25-03-2025 05:12:40","Sagemcom CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004651763","NTE=
MASSI","","25-03-2025 05:10:53","25-03-2025 04:25:40","25-03-2025 06:01:34"=
,"Grid outage site went down because Gen failed to start due to Gen card fa=
ulty // Gen Manually Started","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start due to Gen card faulty // Gen Manually Started","ferot.nong=
ni-djiogap@sagemcom.com","2714","25-03-2025 05:10:53","Sagemcom CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004651739","Eke=
kam","","25-03-2025 04:56:56","25-03-2025 04:51:24","25-03-2025 09:29:24","=
","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Site went down because PWC dysfunctioning // Reconfigatio=
n of PWC done, Site on Gen","el-dalile@sagemcom.com","285082","25-03-2025 0=
4:56:56","Sagemcom CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004651732","Saa=
","","25-03-2025 04:51:08","25-03-2025 04:44:02","25-03-2025 04:47:17","","=
Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Site went down because rectifier disfunctionning // He reset it: Site o=
n grid","el-dalile@sagemcom.com","263982","25-03-2025 04:51:08","Sagemcom C=
MR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004651728","SAA=
 2","IHS_YND_405","25-03-2025 04:48:09","25-03-2025 04:44:02","25-03-2025 0=
4:47:17","Site went down because rectifier disfunctionning // He reset it: =
Site on grid","Parker Tchoup","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down because rectifier disfunctionning // He rese=
t it: Site on grid","el-dalile@sagemcom.com","249","25-03-2025 04:48:09","S=
agemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004651655","ETO=
UDI Entree du palais","","25-03-2025 04:25:37","25-03-2025 04:23:26","25-03=
-2025 04:25:14","Grid outage, site went down before Gen start due to poor b=
attery backup // Gen start automatically","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite went down before Gen start due to poor battery backup // Gen start auto=
matically","el-dalile@sagemcom.com","132","25-03-2025 04:25:37","Sagemcom C=
MR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0004651499","NKO=
ABANG NKOLO 3","","25-03-2025 03:25:01","25-03-2025 03:22:53","25-03-2025 0=
8:12:53","Grid outage, site went down because gen fails to start // Grid re=
turn (Investigation ongoing)","Mba Lazare Herve","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because g=
en fails to start // Grid return (Investigation ongoing)","el-dalile@sagemc=
om.com","129","25-03-2025 03:25:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004651380","O=
lembe-Terminus","","25-03-2025 02:38:50","25-03-2025 02:37:42","25-03-2025 =
06:49:42","Grid outage, site went down because gen start and stopped due to=
 high temp // He added water and manually start the gen","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, site went down because gen start and stopped due=
 to high temp // He added water and manually start the gen","ferot.nongni-d=
jiogap@sagemcom.com","69","25-03-2025 02:38:50","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004651320","UPA=
C LP","","25-03-2025 02:20:33","25-03-2025 02:11:27","25-03-2025 02:47:43",=
"Grid outage, no space to deploy// grid return ","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage, no space to deplo=
y// grid return ","ferot.nongni-djiogap@sagemcom.com","547","25-03-2025 02:=
20:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004651087","N=
yom OCM","","25-03-2025 00:57:20","25-03-2025 00:57:42","25-03-2025 00:58:2=
1","No power issue site on grid with U=3D54v Symphorien from Huawei is info=
rmed","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D54=
v Symphorien from Huawei is informed","el-dalile@sagemcom.com","8211","25-0=
3-2025 00:57:20","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004650952","UPA=
C LP","","25-03-2025 00:09:55","25-03-2025 00:07:37","25-03-2025 00:44:14",=
"Grid outage, no space to deploy// grid return ","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage, no space to deplo=
y// grid return ","ferot.nongni-djiogap@sagemcom.com","139","25-03-2025 00:=
09:55","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004650949","Ole=
mbe MTN","","25-03-2025 00:08:37","24-03-2025 23:57:22","25-03-2025 01:38:3=
1","Grid outage, site went down because gen failed to start due to grid con=
tactor faulty // He bypassed grid contactor and gen manually started","Fabr=
ice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","=
Grid outage, site went down because gen failed to start due to grid contact=
or faulty // He bypassed grid contactor and gen manually started","ferot.no=
ngni-djiogap@sagemcom.com","676","25-03-2025 00:08:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004650902","Manguier=
","","24-03-2025 23:51:27","24-03-2025 21:36:29","24-03-2025 21:40:23","Cas=
caded Incident from TTO4732229","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue U=3D51,1V on Gri=
d The fme Tx Armand ngeutsa From huawei is informed","system","282279","24-=
03-2025 23:51:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004650899","MEHANDAN=
","","24-03-2025 23:50:17","24-03-2025 22:05:36","24-03-2025 23:29:41","Cas=
caded Incident from TTO4732200","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to dysjunction of C=
B(125A) in PWC // CB put back on","system","6281","24-03-2025 23:50:17","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004650896","M=
ANGUIERS CHAPELLE","IHS_YND_209","24-03-2025 23:49:38","24-03-2025 21:36:29=
","24-03-2025 21:40:23","Active//No power issue U=3D51,1V on Grid The fme T=
x Armand ngeutsa From huawei is informed","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue U=3D51,1V on Grid The fme Tx Armand ngeutsa From huawei=
 is informed","ferot.nongni-djiogap@sagemcom.com","7990","24-03-2025 23:49:=
38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004650892","Manguier=
","","24-03-2025 23:47:03","24-03-2025 18:47:35","24-03-2025 20:12:25","Cas=
caded Incident from TTO4730597","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen failed to start // Grid return(investigation ongoing)","system","278089=
","24-03-2025 23:47:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004650869","O=
dza II OCM","IHS_YND_528","24-03-2025 23:33:49","24-03-2025 22:05:36","24-0=
3-2025 23:29:41","Site went down due to dysjunction of CB(125A) in PWC // C=
B put back on","Albran Byorel","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Circuit Breaker Issue","Site went down due to dysjunction=
 of CB(125A) in PWC // CB put back on","el-dalile@sagemcom.com","5294","24-=
03-2025 23:33:49","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004650802","HOP=
ITAL GENERAL RAIL YDE","","24-03-2025 23:11:34","24-03-2025 23:08:27","25-0=
3-2025 07:56:13","Grid outage, site went down due to gen Overload(09kva,160=
A), Bernard IHS is informed // Grid return","Delor Telezing","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down du=
e to gen Overload(09kva,160A), Bernard IHS is informed // Grid return","el-=
dalile@sagemcom.com","188","24-03-2025 23:11:34","Sagemcom CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0004650799","Mba=
lla 4","","24-03-2025 23:10:55","24-03-2025 23:07:47","24-03-2025 23:11:34"=
,"Site went down due to insufficiency of rectifiers, Bernard IHS is informe=
d // Added rectifiers ongoing","Delor Telezing","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down due to insufficiency of re=
ctifiers, Bernard IHS is informed // Added rectifiers ongoing","el-dalile@s=
agemcom.com","189","24-03-2025 23:10:55","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004650789","ETO=
UDI Entree du palais","","24-03-2025 23:06:03","24-03-2025 23:05:54","24-03=
-2025 23:11:53","Grid outage, Site went down before Gen start due to poor b=
ackup/ // Gen automatically started","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site w=
ent down before Gen start due to poor backup/ // Gen automatically started"=
,"ferot.nongni-djiogap@sagemcom.com","10","24-03-2025 23:06:03","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004650707","H=
-General-Yde","","24-03-2025 22:44:44","24-03-2025 22:40:37","24-03-2025 23=
:47:27","Grid outage, Site went down because gen failed to start due to gen=
 overload(13KVA, 160A), Blaise IHS is informed // Grid return","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,=
 Site went down because gen failed to start due to gen overload(13KVA, 160A=
), Blaise IHS is informed // Grid return","el-dalile@sagemcom.com","248","2=
4-03-2025 22:44:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004650179","S=
OA UNIVERSITY STADIUM","","24-03-2025 20:58:35","24-03-2025 20:53:30","24-0=
3-2025 22:01:29","Grid outage, site went down because due to PWC malfunctio=
n // He reset ATS and gen manually started","Siligap Boris","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site =
went down because due to PWC malfunction // He reset ATS and gen manually s=
tarted","el-dalile@sagemcom.com","306","24-03-2025 20:58:35","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004650164","Nom=
ayos montee Meche","","24-03-2025 20:57:18","24-03-2025 20:03:12","25-03-20=
25 01:30:08","Grid outage, Site went down because Gen started and stopped d=
ue emergency stop button was activeted// He actived the button and started =
Gen manualy","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - =
Emergency Stop","Grid outage, Site went down because Gen started and stoppe=
d due emergency stop button was activeted// He actived the button and start=
ed Gen manualy","el-dalile@sagemcom.com","3247","24-03-2025 20:57:18","Sage=
mcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004649949","Mes=
sa Carriere","","24-03-2025 20:14:40","24-03-2025 20:00:20","24-03-2025 20:=
19:28","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty // Grid return","Mboua Thierry","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because Gen=
 failed to started due to Gen card faullty // Grid return","el-dalile@sagem=
com.com","861","24-03-2025 20:14:40","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004649830","Tou=
ring Club International","","24-03-2025 19:46:28","24-03-2025 19:31:10","24=
-03-2025 21:05:57","site went down due to PWC Huawei malfunction //he reset=
 it and site is on Grid","Albran Byorel","Equipment Repair","Passive","Rect=
ifier","Rectifier Module Overloaded","site went down due to PWC Huawei malf=
unction //he reset it and site is on Grid","wilfried.kameni@sagemcom.com","=
919","24-03-2025 19:46:28","Sagemcom CMR"
"Closed Complete","Warning","T1259","IHS_YND_424","NOCINC0004649801","Ossom=
be","","24-03-2025 19:41:34","","","eneo outage // eneo return","Parker Tch=
oup","Warning","Warning","POWER","Warning - Site on Battery","eneo outage /=
/ eneo return","ludovic-anselme.mouliom-mapoure@sagemcom","3556","24-03-202=
5 19:41:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004649449","M=
ANGUIERS CHAPELLE","IHS_YND_209","24-03-2025 18:51:40","24-03-2025 18:47:35=
","24-03-2025 20:12:58","Grid outage, site went down because gen failed to =
start // Grid return(investigation ongoing)","Fabrice Pouakam","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went =
down because gen failed to start // Grid return(investigation ongoing)","el=
-dalile@sagemcom.com","247","24-03-2025 18:51:40","Sagemcom CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004649279","Nta=
ba","","24-03-2025 18:25:34","24-03-2025 18:08:58","24-03-2025 18:26:14",""=
,"Delor Telezing","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Site went down due to insufficiency of rectifiers on site SS IHS Bla=
ise Pascale is inform // He reduced the load","wilfried.kameni@sagemcom.com=
","273312","24-03-2025 18:25:34","Sagemcom CMR"
"Closed Complete","Site Down","T1739","IHS_YND_691","NOCINC0004649271","Mba=
lla 2 REGIE","","24-03-2025 18:24:51","24-03-2025 18:08:58","24-03-2025 18:=
26:14","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Site went down due to insufficiency of rectifiers on site S=
S IHS Blaise Pascale is inform // He reduced the load","wilfried.kameni@sag=
emcom.com","273312","24-03-2025 18:24:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004649267","O=
mnisport 3","IHS_YND_102, IHS_YND_691, IHS_YND_135","24-03-2025 18:24:16","=
24-03-2025 18:08:58","24-03-2025 20:16:36","Site went down due to insuffici=
ency of rectifiers on site SS IHS Blaise Pascale is inform // He reduced th=
e load","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficiency of rectifiers on site SS IHS=
 Blaise Pascale is inform // He reduced the load","el-dalile@sagemcom.com",=
"919","24-03-2025 18:24:16","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004649263","Nlo=
ngkak","","24-03-2025 18:24:02","24-03-2025 18:08:58","24-03-2025 18:26:14"=
,"","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Site went down due to insufficiency of rectifiers on site SS IHS =
Blaise Pascale is inform // He reduced the load","wilfried.kameni@sagemcom.=
com","273311","24-03-2025 18:24:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004649092","O=
mnisport-Rail","","24-03-2025 17:49:55","24-03-2025 17:34:49","24-03-2025 2=
0:12:49","Site went down due to insufficiency of rectifiers due to increase=
 load (SS IHS BERNAD is informed) // Load reduice: Site on grid","Delor Tel=
ezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Site we=
nt down due to insufficiency of rectifiers due to increase load (SS IHS BER=
NAD is informed) // Load reduice: Site on grid","el-dalile@sagemcom.com","9=
07","24-03-2025 17:49:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004648825","K=
oweit City","","24-03-2025 17:21:21","24-03-2025 17:17:15","24-03-2025 17:4=
4:57","Site went down because gen failed to start due to grid bad voltage /=
/ Grid return","Albran Byorel","Grid Supply","Passive","Grid","National Gri=
d - Phase Controller Faulty","Site went down because gen failed to start du=
e to grid bad voltage // Grid return","el-dalile@sagemcom.com","247","24-03=
-2025 17:21:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004648653","O=
dza II","","24-03-2025 17:03:50","24-03-2025 16:48:42","24-03-2025 20:47:26=
","Site went down because gen failed to start due to grid bad voltage // Ge=
n manually started","Albran Byorel","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Site went down because gen failed to sta=
rt due to grid bad voltage // Gen manually started","el-dalile@sagemcom.com=
","910","24-03-2025 17:03:50","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004648645","Beh=
ind P T school Yde","","24-03-2025 17:02:26","24-03-2025 16:58:32","24-03-2=
025 19:28:01","Grid outage, site went down because gen failed to start due =
to gen card faulty //Grid restored","Paul BIBOUM","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
gen failed to start due to gen card faulty //Grid restored","ludovic-anselm=
e.mouliom-mapoure@sagemcom","235","24-03-2025 17:02:26","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004648297","Mon=
tee Jouvence","","24-03-2025 16:13:13","24-03-2025 16:03:04","24-03-2025 17=
:23:04","Grid outage,Site went down because gen fails to start due to grid =
bad voltage // Grid bypass and gen started manually","Hyemafo Gildas","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid o=
utage,Site went down because gen fails to start due to grid bad voltage // =
Grid bypass and gen started manually","ludovic-anselme.mouliom-mapoure@sage=
mcom","610","24-03-2025 16:13:13","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004647766","Tou=
ring Club International","","24-03-2025 14:56:50","24-03-2025 14:16:30","24=
-03-2025 15:24:37","Grid fluctuation, Site went down because gen fails to s=
tart due to grid bad voltage  // We bypassed grid and gen manually started =
","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation, Site went down because gen fails to star=
t due to grid bad voltage  // We bypass grid and gen manually started ","lu=
dovic-anselme.mouliom-mapoure@sagemcom","2421","24-03-2025 14:56:50","Sagem=
com CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004647698","Av =
Kennedy","","24-03-2025 14:46:47","24-03-2025 14:39:38","28-03-2025 21:20:2=
6","Eneo outage, no space to deploy MGE //  Eneo return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Eneo outage, no space =
to deploy MGE //  Eneo return","ludovic-anselme.mouliom-mapoure@sagemcom","=
430","24-03-2025 14:46:47","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004647674","Nko=
abang MTN","","24-03-2025 14:45:22","24-03-2025 14:18:13","24-03-2025 16:20=
:30","Grid outage.gen ran until fuel shortage//Refueling done ","Mba Lazare=
 Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen r=
an until fuel shortage//Refueling done ","ludovic-anselme.mouliom-mapoure@s=
agemcom","1630","24-03-2025 14:45:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004647321","MEHANDAN=
","","24-03-2025 13:58:38","24-03-2025 13:22:45","24-03-2025 19:56:47","Cas=
caded Incident from TTO4728119","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel shortag=
e//Refueling done","system","297579","24-03-2025 13:58:38","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004647279","Bon=
djock","","24-03-2025 13:56:01","24-03-2025 13:20:54","24-03-2025 13:55:54"=
,"Grid outage, Site went down because Gen failed to start// Grid return","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, Site went down because Gen failed to start// Grid return","lu=
dovic-anselme.mouliom-mapoure@sagemcom","2109","24-03-2025 13:56:01","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004647277","O=
dza II OCM","IHS_YND_528","24-03-2025 13:55:52","24-03-2025 13:22:45","24-0=
3-2025 19:56:47","Grid outage.gen ran until fuel shortage//Refueling done",=
"Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge.gen ran until fuel shortage//Refueling done","el-dalile@sagemcom.com","1=
989","24-03-2025 13:55:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_401","IHS_YND_041","NOCINC0004647019","L=
ycee Leclerc School","","24-03-2025 13:19:35","24-03-2025 12:44:27","24-03-=
2025 15:49:27","No power issue on site,site on Grid with Ubaie=3D51.5 V The=
 Tx Fme Mbah hosiah(674007438) from Huawei is informed. Notice that CB trip=
 at OCM Equipment","Paul BIBOUM","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue on site,site on=
 Grid with Ubaie=3D51.5 V The Tx Fme Mbah hosiah(674007438) from Huawei is =
informed. Notice that CB trip at OCM Equipment","el-dalile@sagemcom.com","2=
109","24-03-2025 13:19:35","Sagemcom CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004646987","Nko=
abang Alembe","","24-03-2025 13:11:29","24-03-2025 13:10:19","24-03-2025 18=
:23:48","Grid outage, Site went down because Gen ran until fuel shortage// =
Refueling Done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage, Site went down because Gen ran until fuel shortage//=
 Refueling Done","ludovic-anselme.mouliom-mapoure@sagemcom","70","24-03-202=
5 13:11:29","Sagemcom CMR"
"Closed Complete","Site Down","T0578","IHS_YND_375","NOCINC0004646973","Ngo=
ung","","24-03-2025 13:10:28","24-03-2025 12:28:14","24-03-2025 14:04:59","=
Grid outage, Site went down because Gen failed to start due to battery Gen =
Faulty// He started Gen with external battery","Kemeni Franklin","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, Site=
 went down because Gen failed to start due to battery Gen Faulty// He start=
ed Gen with external battery","ludovic-anselme.mouliom-mapoure@sagemcom","2=
535","24-03-2025 13:10:28","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004646875","Bri=
quetterie","","24-03-2025 12:50:18","24-03-2025 12:21:00","24-03-2025 12:59=
:01","Grid outage no space to deploy mobile gen//Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy mobile gen//Grid return","ludovic-anselme.mouliom-mapoure@sag=
emcom","1760","24-03-2025 12:50:18","Sagemcom CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0004646784","NYO=
M","","24-03-2025 12:45:13","24-03-2025 12:39:04","24-03-2025 15:11:43","Gr=
id outage.gen ran until fuel shortage//Refueling done","Fabrice Pouakam","F=
uel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until f=
uel shortage//Refueling done","ludovic-anselme.mouliom-mapoure@sagemcom","3=
70","24-03-2025 12:45:13","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004646558","Men=
dong vallee","","24-03-2025 12:04:03","24-03-2025 12:02:55","24-03-2025 22:=
58:55","Grid outage site went down because Gen over load (20KVA; 300A) // G=
rid return IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site we=
nt down because Gen over load (20KVA; 300A) // Grid return IHS F=E9lix Zamb=
=E9 is informed and confirmed","ludovic-anselme.mouliom-mapoure@sagemcom","=
69","24-03-2025 12:04:03","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004646265","Tou=
ring Club International","","24-03-2025 11:09:56","24-03-2025 10:53:40","24=
-03-2025 12:25:47","site went down due to PWC Huawei Disfutionning //he res=
et it and site is on Grid","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","site went down due to PWC Huawei Di=
sfutionning //he reset it and site is on Grid","ludovic-anselme.mouliom-map=
oure@sagemcom","977","24-03-2025 11:09:56","Sagemcom CMR"
"Cancelled","Warning","T0053","IHS_YND_407","NOCINC0004646240","Monatele MT=
N","","24-03-2025 11:08:08","","","wrongly ticket","Parker Tchoup","","",""=
,"","","ludovic-anselme.mouliom-mapoure@sagemcom","855","24-03-2025 11:08:0=
8","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004645981","Aka=
k-Nkozoa-MTN-IHS","","24-03-2025 10:14:01","24-03-2025 09:58:45","24-03-202=
5 12:32:05","Grid outage, site went down due to PWC malfunction // Gen manu=
ally started","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","R=
ectifier Module Overloaded","Grid outage, site went down due to PWC malfunc=
tion // Gen manually started","ludovic-anselme.mouliom-mapoure@sagemcom","9=
19","24-03-2025 10:14:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004645743","M=
arche Odza","","24-03-2025 09:26:38","24-03-2025 09:22:24","24-03-2025 10:0=
3:53","Grid fluctuation, Site went down because Gen failed to start due to =
Grid bad voltage// He bypassed Grid and started Gen manually","Albran Byore=
l","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, Site went down because Gen failed to start due to Grid =
bad voltage// He bypassed Grid and started Gen manually","el-dalile@sagemco=
m.com","256","24-03-2025 09:26:38","Sagemcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004645736","TSI=
NGA VILLAGE 2","","24-03-2025 09:24:30","24-03-2025 09:22:20","24-03-2025 1=
1:09:56","Site went down due to CB(125A)tripped in the PWC//he reamed it an=
d Site is on Grid","Delor Telezing","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Circuit Breaker Issue","Site went down due to CB(125=
A)tripped in the PWC//he reamed it and Site is on Grid","ludovic-anselme.mo=
uliom-mapoure@sagemcom","131","24-03-2025 09:24:30","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004645701","NYO=
M FACE MAETUR","","24-03-2025 09:17:27","24-03-2025 09:05:18","24-03-2025 0=
9:18:16","Grid outage, Site went down because Gen failed to start due Gen c=
ard Faulty// Grid Restored","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, Site went down because Gen =
failed to start due Gen card Faulty// Grid Restored","ludovic-anselme.mouli=
om-mapoure@sagemcom","731","24-03-2025 09:17:27","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004645666","Nko=
londom","","24-03-2025 09:11:53","24-03-2025 09:08:33","24-03-2025 09:27:33=
","Site went down because gen failed to start due to grid bad voltage and A=
TS malfunction // He reset ATS, Grid return","Fabrice Pouakam","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Site went dow=
n because gen failed to start due to grid bad voltage and ATS malfunction /=
/ He reset ATS, Grid return","ludovic-anselme.mouliom-mapoure@sagemcom","20=
2","24-03-2025 09:11:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004645556","N=
kolbong","","24-03-2025 08:49:30","24-03-2025 08:39:22","24-03-2025 21:00:4=
7","ACTIVE No power issue U=3D52,6V site on Grid The TX FME   Symphorien / =
675295205 from Huawei is informed","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No p=
ower issue U=3D52,6V site on Grid The TX FME   Symphorien / 675295205 from =
Huawei is informed","ludovic-anselme.mouliom-mapoure@sagemcom","609","24-03=
-2025 08:49:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004645482","B=
riqueterie","","24-03-2025 08:31:21","24-03-2025 08:14:11","24-03-2025 12:5=
7:11","Grid outage, no space to deploy a MDG ,// Grid return ","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no =
space to deploy a MDG ,// Grid return ","el-dalile@sagemcom.com","1031","24=
-03-2025 08:31:21","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004645359","Nlo=
ngkak","","24-03-2025 07:59:55","24-03-2025 07:54:17","24-03-2025 08:14:34"=
,"Site went down due to insufficience of rectifier SS IHS Bernard ATANGANA =
is informed//He reduice the Load and Site is on Grid","Delor Telezing","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module","Site went down due=
 to insufficience of rectifier SS IHS Bernard ATANGANA is informed//He redu=
ice the Load and Site is on Grid","ludovic-anselme.mouliom-mapoure@sagemcom=
","339","24-03-2025 07:59:55","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004645298","SOA=
 TOWN","IHS_YND_323","24-03-2025 07:47:11","24-03-2025 07:36:01","24-03-202=
5 08:42:58","Grid outage,gen stopped with alarm high temp//he added water i=
n radiator","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG -=
 High Engine Temp - Coolant Level Issue","Grid outage,gen stopped with alar=
m high temp//he added water in radiator","ludovic-anselme.mouliom-mapoure@s=
agemcom","672","24-03-2025 07:47:11","Sagemcom CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004645292","SOA=
 VILLAGE","","24-03-2025 07:45:58","24-03-2025 07:36:01","24-03-2025 08:42:=
58","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid outage,gen stopped with alarm high temp//he added water in=
 radiator","ludovic-anselme.mouliom-mapoure@sagemcom","267964","24-03-2025 =
07:45:58","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004645128","Nlo=
ngkak","","24-03-2025 07:05:37","24-03-2025 07:01:26","24-03-2025 07:21:24"=
,"Site went down due to insufficience of rectifier SS IHS Bernard ATANGANA =
is informed// He reduiced load","Delor Telezing","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to insufficience of r=
ectifier SS IHS Bernard ATANGANA is informed// He reduiced load","el-dalile=
@sagemcom.com","253","24-03-2025 07:05:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004644994","M=
EHANDAN","","24-03-2025 06:35:30","24-03-2025 06:19:20","24-03-2025 09:06:2=
4","Grid Outage Site went down due to Automastism Dysfuntionning on Site//H=
e bypass it and Manually Started the Gen ","Albran Byorel","Equipment Repai=
r","Passive","Control Panel","ATS-AMF Issue","Grid Outage Site went down du=
e to Automastism Dysfuntionning on Site//He bypass it and Manually Started =
the Gen ","el-dalile@sagemcom.com","971","24-03-2025 06:35:30","Sagemcom CM=
R"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004644952","Mes=
sassi 2","","24-03-2025 06:27:53","24-03-2025 06:11:40","24-03-2025 11:53:4=
0","Grid outage.Gen ran until fuelsfortage//Grid Restored","Fabrice Pouakam=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.Gen ran unt=
il fuelsfortage//Grid Restored","ludovic-anselme.mouliom-mapoure@sagemcom",=
"974","24-03-2025 06:27:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004644884","A=
wae Escalier","","24-03-2025 06:04:03","24-03-2025 05:37:53","24-03-2025 07=
:49:19","Grid outage, Site went down because Gen failed to start due to Gri=
d contactor faulty// he bypassed it and started Gen manually","Albran Byore=
l","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outag=
e, Site went down because Gen failed to start due to Grid contactor faulty/=
/ he bypassed it and started Gen manually","yves.djomo@sagemcom.com","1571"=
,"24-03-2025 06:04:03","Sagemcom CMR"
"Closed Complete","Site Down","T0537","IHS_YND_225","NOCINC0004644721","Sci=
ence","","24-03-2025 05:29:02","24-03-2025 05:20:58","24-03-2025 09:27:55",=
"Grid outage,gen ran till fuel shortage//Refueling done","TIENTCHEU NZETCHI=
EU GAEL","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen =
ran till fuel shortage//Refueling done","yves.djomo@sagemcom.com","485","24=
-03-2025 05:29:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004644712","Carrefou=
r Ayissi Ele","","24-03-2025 05:25:34","24-03-2025 05:15:20","24-03-2025 05=
:55:26","Cascaded Incident from TTO4725253","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down because 23 =
rectifier disfunctionning Felix BATEU is informed// He reset rectifiers and=
 site on grid ","system","276454","24-03-2025 05:25:34","Sagemcom CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004644709","Saa=
","IHS_YND_810","24-03-2025 05:24:26","24-03-2025 05:15:20","24-03-2025 05:=
55:26","Site went down because 23 rectifier disfunctionning Felix BATEU is =
informed// He reset rectifiers and site on grid ","Parker Tchoup","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module","Site went down because =
23 rectifier disfunctionning Felix BATEU is informed// He reset rectifiers =
and site on grid ","yves.djomo@sagemcom.com","547","24-03-2025 05:24:26","S=
agemcom CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004644626","Odz=
a petit marche new","","24-03-2025 04:51:36","24-03-2025 04:49:21","24-03-2=
025 08:10:26","(Grid fluctuation, Site went down because Gen failed to star=
t due to Grid bad voltage No RCP// He bypassed Grid and started Gen manuall=
y","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","(Grid fluctuation, Site went down because Gen failed to s=
tart due to Grid bad voltage No RCP// He bypassed Grid and started Gen manu=
ally","yves.djomo@sagemcom.com","136","24-03-2025 04:51:36","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004644511","Ole=
mbe MTN","","24-03-2025 03:55:11","24-03-2025 03:53:07","24-03-2025 05:57:3=
5","Site went down because 1/2 rectifier faultySS IHS Felix is informed//Gr=
id return","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down because 1/2 rectifier faultySS IHS Felix is i=
nformed//Grid return","yves.djomo@sagemcom.com","125","24-03-2025 03:55:11"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004644368","NTU=
I TOWN","","24-03-2025 03:07:39","24-03-2025 02:55:29","24-03-2025 06:05:35=
","Grid outage.gen ran until fuel shortage//Refueling done","Parker Tchoup"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unti=
l fuel shortage//Refueling done","yves.djomo@sagemcom.com","731","24-03-202=
5 03:07:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004644328","Minka","=
","24-03-2025 02:50:33","24-03-2025 02:40:37","24-03-2025 02:51:27","Cascad=
ed Incident from TTO4724828","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Site went down because Gen fai=
led to start due to battery Gen discharged// He started Gen with external b=
attery (investigation ongoing)","system","264197","24-03-2025 02:50:33","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004644327","Mbeng","=
","24-03-2025 02:50:33","24-03-2025 02:40:37","24-03-2025 02:51:27","Cascad=
ed Incident from TTO4724828","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Site went down because Gen fai=
led to start due to battery Gen discharged// He started Gen with external b=
attery (investigation ongoing)","system","264196","24-03-2025 02:50:33","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_201","IHS_YND_368","NOCINC0004644324","O=
tele","IHS_YND_370, IHS_YND_369, IHS_YND_371","24-03-2025 02:48:50","24-03-=
2025 02:40:37","24-03-2025 02:51:27","Grid outage, Site went down because G=
en failed to start due to battery Gen discharged// He started Gen with exte=
rnal battery (investigation ongoing)","Fanda Brice","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Generator Battery","Grid outage, Site went down be=
cause Gen failed to start due to battery Gen discharged// He started Gen wi=
th external battery (investigation ongoing)","yves.djomo@sagemcom.com","493=
","24-03-2025 02:48:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004644316","M=
om","","24-03-2025 02:42:16","24-03-2025 02:40:37","24-03-2025 02:51:27",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid outage, Site went down because Gen failed to start due to battery =
Gen discharged// He started Gen with external battery (investigation ongoin=
g)","yves.djomo@sagemcom.com","264196","24-03-2025 02:42:16","Sagemcom CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0004644291","NKO=
ABANG NKOLO 3","","24-03-2025 02:25:20","24-03-2025 02:20:15","24-03-2025 0=
6:32:55","Grid outage.gen ran until fuelsfortage//Refueling done","Mba Laza=
re Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen=
 ran until fuelsfortage//Refueling done","yves.djomo@sagemcom.com","305","2=
4-03-2025 02:25:20","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004644261","Aha=
la Echangeur","","24-03-2025 02:05:41","24-03-2025 01:57:33","24-03-2025 06=
:53:39","Access issue during the night (Grid fluctuation, Site went down be=
cause Gen failed to start due to Grid bad voltage No RCP// He bypassed Grid=
 and started Gen manually)","MINKA NICOLAS","Access Denial","Lease Or Legal=
","Landlord Related Issues","Access Issue - Land Lord","Access issue during=
 the night (Grid fluctuation, Site went down because Gen failed to start du=
e to Grid bad voltage No RCP// He bypassed Grid and started Gen manually)",=
"yves.djomo@sagemcom.com","489","24-03-2025 02:05:41","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004644245","Mam=
bine","","24-03-2025 01:56:25","24-03-2025 01:50:11","24-03-2025 02:04:15",=
"Grid outage, Site went down because Gen ran until fuel shortage// Refuelin=
g ongoing","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, Site went down because Gen ran until fuel shortage// Refueling=
 ongoing","yves.djomo@sagemcom.com","375","24-03-2025 01:56:25","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004644068","A=
wae Escalier","","24-03-2025 00:41:54","24-03-2025 00:37:43","24-03-2025 05=
:09:55","Grid outage, site went down because gen failed to start due to neu=
tral of gen contactor dysfonction // He bypassed it and started Gen manuall=
y","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Load Con=
tactor","Grid outage, site went down because gen failed to start due to neu=
tral of gen contactor dysfonction // He bypassed it and started Gen manuall=
y","yves.djomo@sagemcom.com","252","24-03-2025 00:41:54","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004644034","Beh=
ind P T school Yde","","24-03-2025 00:30:48","24-03-2025 00:27:43","24-03-2=
025 00:31:44","Grid outage, site went down because gen failed to start due =
to gen card faulty //Grid restored","Paul BIBOUM","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
gen failed to start due to gen card faulty //Grid restored","yves.djomo@sag=
emcom.com","186","24-03-2025 00:30:48","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004643724","Nlo=
ngkak","","23-03-2025 22:51:48","23-03-2025 22:43:10","24-03-2025 00:16:09"=
,"Site went down due to insufficience of rectifier SS IHS Bernard ATANGANA =
is informed// He reduiced load","Delor Telezing","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to insufficience of r=
ectifier SS IHS Bernard ATANGANA is informed// He reduiced load","yves.djom=
o@sagemcom.com","519","23-03-2025 22:51:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004643639","Manguier=
","","23-03-2025 22:23:11","23-03-2025 21:45:46","23-03-2025 21:50:56","Cas=
caded Incident from TTO4724014","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue U=3D51,1V on Gri=
d The fme Tx Armand ngeutsa From huawei is informed","system","2245","23-03=
-2025 22:23:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0004643634","M=
ANGUIERS CHAPELLE","IHS_YND_209","23-03-2025 22:22:02","23-03-2025 21:45:46=
","23-03-2025 21:50:56","Active//No power issue U=3D51,1V on Grid The fme T=
x Armand ngeutsa From huawei is informed","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue U=3D51,1V on Grid The fme Tx Armand ngeutsa From huawei=
 is informed","danick.tchakouani@sagemcom.com","2177","23-03-2025 22:22:02"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0004643562","S=
cience","","23-03-2025 22:04:47","23-03-2025 21:46:37","23-03-2025 23:36:39=
","Eneo Cable burned, Site went down because Gen started and stopped with a=
larm ""undervoltage""// He reset Gen card and started gen manually","TIENTC=
HEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","Eneo Cable burned, Site went down because Gen started and stopped =
with alarm ""undervoltage""// He reset Gen card and started gen manually","=
danick.tchakouani@sagemcom.com","1090","23-03-2025 22:04:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004643441","M=
essassi 2","","23-03-2025 21:40:28","23-03-2025 21:35:19","23-03-2025 21:43=
:02","Grid fluctuation, Site went down because Gen started  due to Grid bad=
 voltage// Grid stabilized","Fabrice Pouakam","Equipment Repair","Passive",=
"Rectifier","Rectifier Module Overloaded","Site went down because PWC disfu=
nctionning// He reset PWC","kouoh.jean@ihstowers.com","310","23-03-2025 21:=
40:28","Sagemcom CMR"
"Closed Complete","Site Down","T0530","IHS_YND_252","NOCINC0004643417","Kow=
eit City","","23-03-2025 21:36:31","23-03-2025 21:25:59","23-03-2025 22:55:=
05","Grid outage, Site went down because Gen started and stopped with ""Low=
 fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","Al=
bran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage, Site went down because Gen started and stopped with ""Low fu=
el"" alarm (unprouven) // He reset Gen card and started Gen manualy","danic=
k.tchakouani@sagemcom.com","633","23-03-2025 21:36:31","Sagemcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004643274","TSI=
NGA VILLAGE 2","","23-03-2025 21:14:05","23-03-2025 21:00:00","23-03-2025 2=
1:10:32","Active// No power issue, Site on gen Ubai=3D 51.2V, The Tx FME Sy=
mphorien/650257151 From Huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue, Site on gen Ubai=3D 51.2V, The Tx FME Symphorien/650=
257151 From Huawei is informed","el-dalile@sagemcom.com","846","23-03-2025 =
21:14:05","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004643173","Aka=
k-Nkozoa-MTN-IHS","","23-03-2025 20:54:02","23-03-2025 20:47:31","23-03-202=
5 21:12:41","Site went down because PWC disfunctionning// He reset PWC","Fa=
brice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Site went down because PWC disfunctionning// He reset PWC","dan=
ick.tchakouani@sagemcom.com","393","23-03-2025 20:54:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004643060","MEHANDAN=
","","23-03-2025 20:37:30","23-03-2025 20:23:59","24-03-2025 03:01:58","Gri=
d Outage site went down because Gen Failed to Start //Grid Restored( deep i=
nvestigation ongoing)","Albran Byorel","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid Outage site went down because Gen Failed t=
o Start //Grid Restored( deep investigation ongoing)","system","811","23-03=
-2025 20:37:30","Sagemcom CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004643037","Odz=
a Minkan IHS","","23-03-2025 20:34:01","23-03-2025 20:03:46","23-03-2025 21=
:37:44","Site went down because 2CB(50A) tripped in PWC// CB put back on","=
Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Circuit Breaker Issue","Site went down because 2CB(50A) tripped in PWC// =
CB put back on","danick.tchakouani@sagemcom.com","1816","23-03-2025 20:34:0=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004643033","O=
dza II OCM","","23-03-2025 20:32:56","23-03-2025 20:23:59","23-03-2025 22:2=
6:00","Grid outage, Site went down because Gen ran until fuel shortage// Re=
fueling Done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, Site went down because Gen ran until fuel shortage// Refu=
eling Done","danick.tchakouani@sagemcom.com","539","23-03-2025 20:32:56","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0004642951","M=
VAN SACEL","","23-03-2025 20:15:07","23-03-2025 19:25:50","23-03-2025 22:09=
:53","Grid fluctuation, Site went down because Gen started and stopped due =
to Grid bad voltage// He bypassed Grid and started Gen manually","MINKA NIC=
OLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, Site went down because Gen started and stopped due t=
o Grid bad voltage// He bypassed Grid and started Gen manually","danick.tch=
akouani@sagemcom.com","2958","23-03-2025 20:15:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004642889","S=
OA TOWN","","23-03-2025 20:03:02","23-03-2025 19:32:31","23-03-2025 21:34:4=
5","Site went down because CB (125A) tripped in PWC who feeds equipments OC=
M// CB put back on","Siligap Boris","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Circuit Breaker Issue","Site went down because CB (1=
25A) tripped in PWC who feeds equipments OCM// CB put back on","danick.tcha=
kouani@sagemcom.com","1832","23-03-2025 20:03:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004642855","E=
koumdoum","","23-03-2025 19:53:24","23-03-2025 13:52:12","23-03-2025 17:06:=
24","Grid outage, site went down because gen start and stopped due to high =
temp // He oppened all the doors","Albran Byorel","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage=
, site went down because gen start and stopped due to high temp // He oppen=
ed all the doors","kouoh.jean@ihstowers.com","21673","23-03-2025 19:53:24",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0004642779","Ngo=
g Mapubi","","23-03-2025 19:32:30","23-03-2025 19:23:59","23-03-2025 20:48:=
51","Grid fluctuation, Site went down because Gen failed to start due to Gr=
id bad voltage No RCP// He bypassed Grid and started Gen manually","Kemeni =
Franklin","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation, Site went down because Gen failed to start due t=
o Grid bad voltage No RCP// He bypassed Grid and started Gen manually","dan=
ick.tchakouani@sagemcom.com","512","23-03-2025 19:32:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004642719","AWAE OCM=
","","23-03-2025 19:21:17","23-03-2025 19:15:39","23-03-2025 20:13:39","Cas=
caded Incident from TTO4722923","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC dysfonction // He reset the PWC and Gen manuall=
y started","system","319638","23-03-2025 19:21:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004642720","Essomba"=
,"","23-03-2025 19:21:17","23-03-2025 19:15:39","23-03-2025 20:13:39","Casc=
aded Incident from TTO4722923","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due PWC dysfonction // He reset the PWC and Gen manually=
 started","system","319637","23-03-2025 19:21:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004642715","B=
iteng","IHS_YND_292, IHS_YND_173, IHS_YND_179","23-03-2025 19:18:46","23-03=
-2025 19:15:39","23-03-2025 20:13:39","Grid outage site went down because G=
en failed to start due PWC dysfonction // He reset the PWC and Gen manually=
 started","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rect=
ifier Module Overloaded","Grid outage site went down because Gen failed to =
start due PWC dysfonction // He reset the PWC and Gen manually started","el=
-dalile@sagemcom.com","189","23-03-2025 19:18:46","Sagemcom CMR"
"Closed Complete","Warning","T2581","IHS_YND_750","NOCINC0004642656","Nkoab=
ang entree carriere","","23-03-2025 19:14:07","","","eneo outage // eneo re=
turn","Mba Lazare Herve","Warning","Warning","POWER","Warning - Site on Bat=
tery","eneo outage // eneo return","ferot.nongni-djiogap@sagemcom.com","416=
5","23-03-2025 19:14:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004642654","Bitoto",=
"","23-03-2025 19:13:41","23-03-2025 18:38:16","23-03-2025 20:13:39","Casca=
ded Incident from TTO4722692","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down because G=
en overload(20, 300A) SS IHS Alphonse DEFFO is informed// He reduiced load =
and started Gen manualy","system","321879","23-03-2025 19:13:41","Sagemcom =
CMR"
"Closed Complete","Site Down","T2564","IHS_YND_739","NOCINC0004642646","NKO=
LMESSING rue Manguier","","23-03-2025 19:11:47","23-03-2025 18:15:25","23-0=
3-2025 22:43:54","Site went down because CB(125A) tripped in PWC due to loa=
d increase// He did a bridge with another CB","Siligap Boris","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Si=
te went down because CB(125A) tripped in PWC due to load increase// He did =
a bridge with another CB","danick.tchakouani@sagemcom.com","3383","23-03-20=
25 19:11:47","Sagemcom CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0004642518","Ese=
ka Town","","23-03-2025 18:46:25","23-03-2025 18:41:16","23-03-2025 18:53:1=
6","Active// No power issue, Site on Gen, The FME Tx Etienne/695033981 From=
 Huawei is informed and up at 06:53 PM","Kemeni Franklin","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue, Site on Gen, The FME Tx Etienne/695033981 From Huawei i=
s informed and up at 06:53 PM","danick.tchakouani@sagemcom.com","310","23-0=
3-2025 18:46:25","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004642515","Nko=
abang MTN","IHS_YND_292, IHS_YND_796","23-03-2025 18:45:32","23-03-2025 18:=
38:16","23-03-2025 19:08:16","Grid outage, Site went down because Gen overl=
oad(20, 300A) SS IHS Alphonse DEFFO is informed// He reduiced load and star=
ted Gen manualy","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage, Site went down because Gen overload(20, 30=
0A) SS IHS Alphonse DEFFO is informed// He reduiced load and started Gen ma=
nualy","danick.tchakouani@sagemcom.com","437","23-03-2025 18:45:32","Sagemc=
om CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004642418","Bit=
eng-Maetur","","23-03-2025 18:27:48","23-03-2025 18:25:34","23-03-2025 20:1=
0:16","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the l=
oad","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, Site went down because Gen started and stopped due to =
Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the =
load","danick.tchakouani@sagemcom.com","136","23-03-2025 18:27:48","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004642416","M=
EFOU ASSI","","23-03-2025 18:27:15","23-03-2025 18:14:55","23-03-2025 18:27=
:55","Grid fluctuation, Site went down because Gen failed to start due to b=
ad voltage // Grid stabilized","Fanda Brice","Grid Supply","Passive","Grid"=
,"National Grid - Phase Controller Faulty","Grid fluctuation, Site went dow=
n because Gen failed to start due to bad voltage // Grid stabilized","el-da=
lile@sagemcom.com","741","23-03-2025 18:27:15","Sagemcom CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004642413","Sca=
lom","","23-03-2025 18:26:51","23-03-2025 18:17:42","23-03-2025 18:27:10","=
Grid Outage, site went down before gen start due to poor battery backup // =
Gen started automatically","Paul BIBOUM","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid Outage, site went down befor=
e gen start due to poor battery backup // Gen started automatically","danic=
k.tchakouani@sagemcom.com","550","23-03-2025 18:26:51","Sagemcom CMR"
"Closed Complete","Warning","CTR_414","IHS_YND_202","NOCINC0004642389","Cit=
e-Verte","","23-03-2025 18:20:38","","","Grid outag// MDG 20 KVA to deploy"=
,"","Warning","Warning","POWER","Warning - National Grid - Grid Outage Issu=
e","Grid outag// MDG 20 KVA to deploy","ferot.nongni-djiogap@sagemcom.com",=
"3130","23-03-2025 18:20:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_159","NOCINC0004642316","Complexe=
-BEAC","","23-03-2025 18:09:03","23-03-2025 16:45:06","23-03-2025 17:59:06"=
,"Cascaded Incident from TTO4722464","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down becau=
se Gen ran until fuel shortage// Refueling Done","system","321666","23-03-2=
025 18:09:03","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004642314","NYO=
M FACE MAETUR","","23-03-2025 18:08:43","23-03-2025 17:58:58","23-03-2025 2=
0:12:01","Grid outage site went down because Gen failed to start due to gen=
 card and solenoid faulty // Gen manually started","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site =
went down because Gen failed to start due to gen card and solenoid faulty /=
/ Gen manually started","danick.tchakouani@sagemcom.com","586","23-03-2025 =
18:08:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004642312","E=
kie-Elegance","IHS_YND_159","23-03-2025 18:08:24","23-03-2025 16:45:06","23=
-03-2025 17:59:06","Grid outage, Site went down because Gen ran until fuel =
shortage// Refueling Done","Albran Byorel","Fuel Outage","Passive","Diesel"=
,"Diesel Outage","Grid outage, Site went down because Gen ran until fuel sh=
ortage// Refueling Done","kouoh.jean@ihstowers.com","4999","23-03-2025 18:0=
8:24","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004642277","Bon=
djock","","23-03-2025 17:58:03","23-03-2025 17:43:20","23-03-2025 18:10:29"=
,"Grid outage, Site went down because Gen failed to start// Grid return","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, Site went down because Gen failed to start// Grid return","da=
nick.tchakouani@sagemcom.com","1138","23-03-2025 17:58:03","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004642260","Mes=
sa Carriere","","23-03-2025 17:55:52","23-03-2025 17:37:43","23-03-2025 18:=
39:43","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty // Grid return","Mboua Thierry","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because Gen=
 failed to started due to Gen card faullty // Grid return","danick.tchakoua=
ni@sagemcom.com","1090","23-03-2025 17:55:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004642258","N=
kolbong","","23-03-2025 17:54:43","23-03-2025 17:35:35","23-03-2025 19:00:3=
5","Grid outage, Site went down because Gen failed to start due Gen card di=
sfunction// He reset Gen card and started Gen manually	","Delor Telezing","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
 Site went down because Gen failed to start due Gen card disfunction// He r=
eset Gen card and started Gen manually	","danick.tchakouani@sagemcom.com","=
1149","23-03-2025 17:54:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_545","NOCINC0004642257","Nkolbiss=
on usine des eaux","IHS_YND_712","23-03-2025 17:54:25","23-03-2025 17:17:33=
","23-03-2025 19:02:33","Grid outage, site went down because gen failed to =
start and stopped with alarm over current due to load // He reduced the loa=
d, site on gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Grid outage, site went down because gen failed t=
o start and stopped with alarm over current due to load // He reduced the l=
oad, site on gen","kouoh.jean@ihstowers.com","2213","23-03-2025 17:54:25","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004642173","N=
goulmekong-Nord","","23-03-2025 17:39:43","23-03-2025 17:27:29","23-03-2025=
 20:58:54","Site went down due to insufficience of rectifers (05) due to lo=
ad increase Blaise Raoul confirmed// He reduiced load","Siligap Boris","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module","Site went down due=
 to insufficience of rectifers (05) due to load increase Blaise Raoul confi=
rmed// He reduiced load","danick.tchakouani@sagemcom.com","735","23-03-2025=
 17:39:43","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004642103","SOA=
 UNIVERSITY STADIUM","","23-03-2025 17:24:01","23-03-2025 17:04:52","23-03-=
2025 17:10:52","Active// No power issue on site, Site on Grid Ubai=3D 54V T=
he Tx FME Julien/693095849 From Huawei is informed","Siligap Boris","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power issue on site, Site on Grid Ubai=3D 54V The Tx FME J=
ulien/693095849 From Huawei is informed","danick.tchakouani@sagemcom.com","=
1150","23-03-2025 17:24:01","Sagemcom CMR"
"Closed Complete","Warning","T0105","IHS_YND_321","NOCINC0004641987","Soa",=
"","23-03-2025 17:03:50","","","Grid outage, site alarm because gen stopped=
 with alarm under frequency // He reset gen card and gen manually started",=
"Siligap Boris","Warning","Warning","POWER","Warning - ACDG - Under Frequen=
cy","Grid outage, site alarm because gen stopped with alarm under frequency=
 // He reset gen card and gen manually started","ferot.nongni-djiogap@sagem=
com.com","853","23-03-2025 17:03:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004641960","C=
amp-Sic-Tsinga","","23-03-2025 16:56:27","23-03-2025 16:41:20","24-03-2025 =
18:27:52","Grid outage.no space to deploy mobile gen // grid power ","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e.no space to deploy mobile gen // grid power ","el-dalile@sagemcom.com","9=
08","23-03-2025 16:56:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0004641885","E=
kie sud","","23-03-2025 16:45:34","23-03-2025 16:30:25","23-03-2025 18:09:5=
4","Site went down because gen failed to start due to Hybrid system malfunc=
tion // He reset hybrid system and gen manuallys started","Albran Byorel","=
Equipment Repair","Passive","Hybrid","Hybrid Module","Site went down becaus=
e gen failed to start due to Hybrid system malfunction // He reset hybrid s=
ystem and gen manuallys started","danick.tchakouani@sagemcom.com","910","23=
-03-2025 16:45:34","Sagemcom CMR"
"Closed Complete","Warning","T0139","IHS_YND_381","NOCINC0004641876","Boumn=
yebel","","23-03-2025 16:43:28","","","Site alarm due to grid bad voltage /=
/Grid return","Kemeni Franklin","Warning","Warning","POWER","Warning - Nati=
onal Grid - Grid Incomplete Phase","Site alarm due to grid bad voltage //Gr=
id return","ferot.nongni-djiogap@sagemcom.com","906","23-03-2025 16:43:28",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0004641869","B=
astos-BAT","","23-03-2025 16:41:50","23-03-2025 16:35:44","23-03-2025 17:35=
:44","Grid outage.gen failed to start due to ""high temp"" alarm//We add wa=
ter and gen manually started","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.gen=
 failed to start due to ""high temp"" alarm//We add water and gen manually =
started","el-dalile@sagemcom.com","366","23-03-2025 16:41:50","Sagemcom CMR=
"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004641848","Nko=
lbisson usines des eaux 2","","23-03-2025 16:39:46","23-03-2025 16:32:32","=
23-03-2025 17:52:32","Grdi fluctuation, Site went down because Gen failed t=
o start due to grid bad voltage No crcp // He bypassed the Grid and started=
 Gen manually","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Grdi fluctuation, Site went down b=
ecause Gen failed to start due to grid bad voltage No crcp // He bypassed t=
he Grid and started Gen manually","danick.tchakouani@sagemcom.com","435","2=
3-03-2025 16:39:46","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004641709","Aha=
la Echangeur","","23-03-2025 16:13:17","23-03-2025 15:49:57","23-03-2025 17=
:32:21","Grid fluctuation, Site went down because gen faild to start due to=
 grid bad voltage and no RCP // He bypassed Grid Gen manually started","MIN=
KA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation, Site went down because gen faild to start due =
to grid bad voltage and no RCP // He bypassed Grid Gen manually started","d=
anick.tchakouani@sagemcom.com","1401","23-03-2025 16:13:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004641696","B=
arriere","","23-03-2025 16:10:28","23-03-2025 15:52:09","25-03-2025 18:38:5=
5","	grid outage, Site went down because Gen overload(20kva,400 A) IHS SS F=
elix Zambe is informed and confirmed // He reduced the load and gen manuall=
y started","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","	grid outage, Site went down because Gen overload(20kva,400 A) =
IHS SS Felix Zambe is informed and confirmed // He reduced the load and gen=
 manually started","danick.tchakouani@sagemcom.com","1100","23-03-2025 16:1=
0:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0004641687","T=
radex-Nkomo","","23-03-2025 16:08:44","23-03-2025 15:50:14","23-03-2025 17:=
08:11","Site went down because gen start an stopped due to water mixed fuel=
  // He purged  and Gen manually started","Albran Byorel","Fuel Outage (Pro=
bable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","Site w=
ent down because gen start an stopped due to water mixed fuel  // He purged=
  and Gen manually started","danick.tchakouani@sagemcom.com","1111","23-03-=
2025 16:08:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004641646","ELOUMDEM=
 CARRIERE 2","","23-03-2025 15:58:11","23-03-2025 15:53:57","23-03-2025 16:=
23:57","Cascaded Incident from TTO4721697","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen ran untill fuel shortage // Refuelling done","system","274097","=
23-03-2025 15:58:11","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004641640","MEF=
OU ASSI","IHS_YND_768","23-03-2025 15:57:03","23-03-2025 15:53:57","23-03-2=
025 16:23:57","Grid outage, site went down because gen ran untill fuel shor=
tage // Refuelling done","Fanda Brice","Fuel Outage","Passive","Diesel","Di=
esel Outage","Grid outage, site went down because gen ran untill fuel short=
age // Refuelling done","danick.tchakouani@sagemcom.com","187","23-03-2025 =
15:57:03","Sagemcom CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004641547","Eki=
e sud","","23-03-2025 15:40:01","23-03-2025 15:25:38","23-03-2025 16:23:38"=
,"Site went down because Gen failed to start due to Hybrid system dysfoncti=
on // Gen manually started","Albran Byorel","Equipment Repair","Passive","H=
ybrid","Hybrid Module","Site went down because Gen failed to start due to H=
ybrid system dysfonction // Gen manually started","danick.tchakouani@sagemc=
om.com","865","23-03-2025 15:40:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004641539","M=
vog-Manga","","23-03-2025 15:38:44","23-03-2025 15:36:04","23-03-2025 17:15=
:04","Grid outage, site went down because gen start and stopped with high t=
emp alarm // Grid return","Albran Byorel","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage, site went down because gen star=
t and stopped with high temp alarm // Grid return","danick.tchakouani@sagem=
com.com","162","23-03-2025 15:38:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0004641497","Hotel de=
 Ville Yde","","23-03-2025 15:27:33","23-03-2025 15:19:14","23-03-2025 17:3=
2:14","Cascaded Incident from TTO4721514","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage // Grid power retu=
rn","system","283426","23-03-2025 15:27:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0004641476","N=
R-Bastos","IHS_YND_019","23-03-2025 15:24:29","23-03-2025 15:19:14","23-03-=
2025 17:32:14","Grid outage // Grid power return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage // Grid power ret=
urn","danick.tchakouani@sagemcom.com","317","23-03-2025 15:24:29","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_159","NOCINC0004641406","Complexe=
-BEAC","","23-03-2025 15:08:02","23-03-2025 14:12:42","23-03-2025 15:53:18"=
,"Cascaded Incident from TTO4721421","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down becau=
se Gen failed to start due to charging alternator what didn't feeds site// =
He regularised it and started Gen manualy","system","1229616","23-03-2025 1=
5:08:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004641397","E=
kie-Elegance","IHS_YND_159","23-03-2025 15:06:50","23-03-2025 14:12:42","23=
-03-2025 15:53:18","","Albran Byorel","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Charging Alternator","Grid outage, Site went down because Gen fa=
iled to start due to charging alternator what didn't feeds site// He regula=
rised it and started Gen manualy","danick.tchakouani@sagemcom.com","3249","=
23-03-2025 15:06:50","Sagemcom CMR"
"Closed Complete","Site Down","T3446","IHS_YND_712","NOCINC0004641390","Nko=
lkoumou OCM","","23-03-2025 15:02:53","23-03-2025 17:17:33","23-03-2025 19:=
02:33","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen failed to=
 start and stopped with alarm over current due to load // He reduced the lo=
ad, site on gen","danick.tchakouani@sagemcom.com","305228","23-03-2025 15:0=
2:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004641367","C=
amp-Sic-Tsinga","","23-03-2025 14:58:13","23-03-2025 14:02:51","23-03-2025 =
15:03:55","Grid outage, no space to deploy a mobil gen // Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age, no space to deploy a mobil gen // Grid return","danick.tchakouani@sage=
mcom.com","3323","23-03-2025 14:58:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004641360","A=
wae Ewonkan","","23-03-2025 14:56:48","23-03-2025 14:47:59","23-03-2025 18:=
48:59","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // =
He reduced the load","danick.tchakouani@sagemcom.com","530","23-03-2025 14:=
56:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004641353","Carrefou=
r Ayissi Ele","","23-03-2025 14:54:51","23-03-2025 14:50:05","23-03-2025 15=
:24:05","Cascaded Incident from TTO4721358","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site impacted by Saa T0142=
 ( site went down due to 02/03 rectifiers malfunction // He reset rectifier=
s, site on grid","system","285303","23-03-2025 14:54:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004641354","SAA Entr=
ance","","23-03-2025 14:54:51","23-03-2025 14:50:05","23-03-2025 15:24:05",=
"Cascaded Incident from TTO4721358","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site impacted by Saa T0142 ( site =
went down due to 02/03 rectifiers malfunction // He reset rectifiers, site =
on grid","system","285303","23-03-2025 14:54:51","Sagemcom CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004641349","Saa=
","IHS_YND_810, IHS_YND_542","23-03-2025 14:53:21","23-03-2025 14:50:05","2=
3-03-2025 15:24:05","Site impacted by Saa T0142 ( site went down due to 02/=
03 rectifiers malfunction // He reset rectifiers, site on grid","Parker Tch=
oup","Equipment Repair","Passive","Rectifier","Rectifier Module","Site impa=
cted by Saa T0142 ( site went down due to 02/03 rectifiers malfunction // H=
e reset rectifiers, site on grid","danick.tchakouani@sagemcom.com","197","2=
3-03-2025 14:53:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004641330","O=
dza II","","23-03-2025 14:49:30","23-03-2025 14:46:13","23-03-2025 14:46:14=
","No power issue on site U=3D52.4 V site on Grid The TX Lionel steve //655=
184876 from Huawei is informed.Notice that we have disjunction in OCM equip=
ment.","Albran Byorel","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue on site U=3D52.4 V site o=
n Grid The TX Lionel steve //655184876 from Huawei is informed.Notice that =
we have disjunction in OCM equipment.","danick.tchakouani@sagemcom.com","19=
9","23-03-2025 14:49:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004641313","N=
koabang Ebolmedjock","","23-03-2025 14:46:43","23-03-2025 14:29:26","23-03-=
2025 19:08:16","ACTIVE//No power issue on site. Site on grid with Ubaie=3D5=
3.5 V. The FME TX Lionel Adjeb /655184876// from huawei is informed","Mba L=
azare Herve","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","ACTIVE//No power issue on site. Site on grid with =
Ubaie=3D53.5 V. The FME TX Lionel Adjeb /655184876// from huawei is informe=
d","danick.tchakouani@sagemcom.com","1038","23-03-2025 14:46:43","Sagemcom =
CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004641309","Eto=
 koss Yde","","23-03-2025 14:45:29","23-03-2025 14:32:12","23-03-2025 14:47=
:12","Grid outage, Site went down because gen failed to start // Grid retur=
n (investigation ongoing)","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid outage, Site went down because gen faile=
d to start // Grid return (investigation ongoing)","danick.tchakouani@sagem=
com.com","799","23-03-2025 14:45:29","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004641302","Aha=
la Echangeur","","23-03-2025 14:44:35","23-03-2025 14:12:19","23-03-2025 15=
:38:19","Site went down because gen failde to start due to grid bad voltage=
 and no RCP // Gen manually started","MINKA NICOLAS","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Site went down because =
gen failde to start due to grid bad voltage and no RCP // Gen manually star=
ted","danick.tchakouani@sagemcom.com","1937","23-03-2025 14:44:35","Sagemco=
m CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004641000","Bas=
tos Amb Coree","","23-03-2025 13:55:11","23-03-2025 13:48:59","23-03-2025 1=
7:32:19","Grid outage, no space to deploy// grid return ","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space=
 to deploy// grid return ","charly.diekem-yemeli@sagemcom.com","373","23-03=
-2025 13:55:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004640965","E=
kombitie","","23-03-2025 13:49:28","23-03-2025 13:34:11","23-03-2025 13:34:=
12","No power issue site on gen with U=3D54.5V site on Gen THE TX Synphorie=
n 691316854 of Huawei is informed","Fabrice Pouakam","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue site on gen with U=3D54.5V site on Gen THE TX Synphorien 691316854 of =
Huawei is informed","charly.diekem-yemeli@sagemcom.com","918","23-03-2025 1=
3:49:28","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004640863","ODZ=
A CITE MBIA","","23-03-2025 13:39:10","23-03-2025 11:46:56","23-03-2025 16:=
30:56","Grid outage, site went down because gen ran until fuel shortage // =
Refueling done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage, site went down because gen ran until fuel shortage // R=
efueling done","charly.diekem-yemeli@sagemcom.com","6735","23-03-2025 13:39=
:10","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0004640779","Sap=
eur Mimboman","","23-03-2025 13:16:48","23-03-2025 13:06:31","23-03-2025 19=
:43:52","access issues due to the Landloord( ALPHOSE DEFFO is informed ), G=
rid outage, site went down because gen failed to start // Grid return (Inve=
stigation ongoing)","Mba Lazare Herve","Access Denial","Lease Or Legal","La=
ndlord Related Issues","Access Issue - Land Lord","access issues due to the=
 Landloord( ALPHOSE DEFFO is informed ), Grid outage, site went down becaus=
e gen failed to start // Grid return (Investigation ongoing)","charly.dieke=
m-yemeli@sagemcom.com","668","23-03-2025 13:16:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004640721","L=
abogenie","IHS_YND_568","23-03-2025 13:03:19","23-03-2025 12:48:08","23-03-=
2025 17:29:03","access issues due to the Landloord( ALPHOSE DEFFO is inform=
ed ),Grid outage, no space to deploy// grid return ","","Access Denial","Le=
ase Or Legal","Landlord Related Issues","Access Issue - Land Lord","access =
issues due to the Landloord( ALPHOSE DEFFO is informed ),Grid outage, no sp=
ace to deploy// grid return ","el-dalile@sagemcom.com","913","23-03-2025 13=
:03:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0004640676","A=
nguissa New","","23-03-2025 13:01:22","23-03-2025 12:48:08","23-03-2025 17:=
29:03","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","access issues due to the Landloord( ALPHOSE DEFFO is informe=
d ),Grid outage, no space to deploy// grid return ","charly.diekem-yemeli@s=
agemcom.com","292499","23-03-2025 13:01:22","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004640548","Tou=
ring Club International","","23-03-2025 12:50:22","23-03-2025 12:34:14","23=
-03-2025 16:31:14","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed // Grid return","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went down=
 because Gen overload (20Kw, 270A) SS IHS Pascaline confirmed // Grid retur=
n","charly.diekem-yemeli@sagemcom.com","969","23-03-2025 12:50:22","Sagemco=
m CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004640545","Bar=
riere","","23-03-2025 12:49:39","23-03-2025 12:34:26","23-03-2025 15:40:26"=
,"grid outage, Site went down because Gen overload(20kva,400 A) IHS SS Feli=
x Zambe is informed and confirmed // He reduced the load and gen manually s=
tarted","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","grid outage, Site went down because Gen overload(20kva,400 A) IHS =
SS Felix Zambe is informed and confirmed // He reduced the load and gen man=
ually started","charly.diekem-yemeli@sagemcom.com","914","23-03-2025 12:49:=
39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004640538","MEHANDAN=
","","23-03-2025 12:47:19","23-03-2025 12:31:02","23-03-2025 16:14:02","Cas=
caded Incident from TTO4720423","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n ran until fuel shortage // Refueling done","system","293580","23-03-2025 =
12:47:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004640528","O=
dza II OCM","IHS_YND_528","23-03-2025 12:45:16","23-03-2025 12:31:02","23-0=
3-2025 16:14:02","Grid outage, site went down because gen ran until fuel sh=
ortage // Refueling done","Albran Byorel","Fuel Outage","Passive","Diesel",=
"Diesel Outage","Grid outage, site went down because gen ran until fuel sho=
rtage // Refueling done","charly.diekem-yemeli@sagemcom.com","856","23-03-2=
025 12:45:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004640507","O=
dza","","23-03-2025 12:41:39","23-03-2025 12:25:23","23-03-2025 17:17:23","=
Grid outage, site went down because gen start and stopped with high temp al=
arm // Reset done and gen started","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because=
 gen start and stopped with high temp alarm // Reset done and gen started",=
"charly.diekem-yemeli@sagemcom.com","977","23-03-2025 12:41:39","Sagemcom C=
MR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004640495","NYO=
M 2 IHS","","23-03-2025 12:39:16","23-03-2025 12:30:08","23-03-2025 15:51:3=
8","Grid outage, site went down because gen start and stopped due to alarm"=
"high temp""//We added water and gen manually started","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Le=
vel Issue","Grid outage, site went down because gen start and stopped due t=
o alarm""high temp""//We added water and gen manually started","charly.diek=
em-yemeli@sagemcom.com","626","23-03-2025 12:39:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004640471","N=
kolondom","","23-03-2025 12:37:07","23-03-2025 12:21:21","23-03-2025 13:38:=
36","Site went down because gen failed to start due to ATS malfunction caus=
ing by grid bad voltage // He reset ATS and gen manually started","Fabrice =
Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Site=
 went down because gen failed to start due to ATS malfunction causing by gr=
id bad voltage // He reset ATS and gen manually started","charly.diekem-yem=
eli@sagemcom.com","1005","23-03-2025 12:37:07","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004640312","ETO=
UDI Entree du palais","","23-03-2025 12:05:57","23-03-2025 11:52:43","23-03=
-2025 13:39:43","Site went down because gen fails to start due to grid bad =
voltage and poor battery backup // He bypass grid and manually start the ge=
n","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Site went down because gen fails to start due to grid b=
ad voltage and poor battery backup // He bypass grid and manually start the=
 gen","charly.diekem-yemeli@sagemcom.com","795","23-03-2025 12:05:57","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0004640307","T=
radex-Nkomo","","23-03-2025 12:04:45","23-03-2025 11:54:30","23-03-2025 15:=
17:30","Grid outage, site went down because gen faisl to start due to water=
 in the tank // He purged it and manually start the gen","Albran Byorel","F=
uel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In Th=
e Fuel","Grid outage, site went down because gen faisl to start due to wate=
r in the tank // He purged it and manually start the gen","charly.diekem-ye=
meli@sagemcom.com","616","23-03-2025 12:04:45","Sagemcom CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004640299","Eki=
e sud","","23-03-2025 12:02:29","23-03-2025 11:36:14","23-03-2025 13:10:24"=
,"Site went down because Gen failed to start due to Hybrid system dysfoncti=
on // Gen manually started","Albran Byorel","Equipment Repair","Passive","H=
ybrid","Hybrid Module","Site went down because Gen failed to start due to H=
ybrid system dysfonction // Gen manually started","charly.diekem-yemeli@sag=
emcom.com","1576","23-03-2025 12:02:29","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004640294","Ole=
mbe MTN","","23-03-2025 12:01:06","23-03-2025 11:57:44","23-03-2025 23:38:0=
1","Site went down due to insufficience of rectifier SS IHS Felix confiurme=
d // He reduiced load (Rectifer to be added)","Fabrice Pouakam","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down due to ins=
ufficience of rectifier SS IHS Felix confiurmed // He reduiced load (Rectif=
er to be added)","charly.diekem-yemeli@sagemcom.com","203","23-03-2025 12:0=
1:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004640235","M=
endong","","23-03-2025 11:40:18","23-03-2025 10:51:03","23-03-2025 11:06:33=
","Grid fluctuation, Site went down because Gen failed to start due to Grid=
 bad voltage No RCP//  He bypassed the grid and gen manually started","Hyem=
afo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation, Site went down because Gen failed to start due=
 to Grid bad voltage No RCP//  He bypassed the grid and gen manually starte=
d","el-dalile@sagemcom.com","2956","23-03-2025 11:40:18","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004639889","Eko=
umdoum OCM","","23-03-2025 10:27:24","23-03-2025 10:10:18","23-03-2025 11:4=
0:15","Grid outage, Site went down because Gen overload (20kva, 300A) SS IH=
S alphonse confirmed// site on GEN","Albran Byorel","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen=
 overload (20kva, 300A) SS IHS alphonse confirmed// site on GEN","charly.di=
ekem-yemeli@sagemcom.com","1027","23-03-2025 10:27:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004639706","E=
koumdoum","","23-03-2025 09:47:26","23-03-2025 09:30:20","23-03-2025 10:55:=
20","Grid outage, site went down because gen start and stopped due to high =
temp // He oppened all the doors","Albran Byorel","Equipment Repair","Passi=
ve","ACDG Gen","Gen Temp High","Grid outage, site went down because gen sta=
rt and stopped due to high temp // He oppened all the doors","el-dalile@sag=
emcom.com","1027","23-03-2025 09:47:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0004639705","O=
kola OCM","","23-03-2025 09:47:03","23-03-2025 09:25:55","23-03-2025 10:06:=
51","Grid outage, Site went down because Gen start and stopped with ""High =
temps ""alarm // he added water and manually start the Gen","TIENTCHEU NZET=
CHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Tem=
p - Coolant Level Issue","Grid outage, Site went down because Gen start and=
 stopped with ""High temps ""alarm // he added water and manually start the=
 Gen","charly.diekem-yemeli@sagemcom.com","1270","23-03-2025 09:47:03","Sag=
emcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004639698","Nko=
lmvack","","23-03-2025 09:45:54","23-03-2025 09:42:37","23-03-2025 10:19:21=
","Site went down because gen start and stopped with alarm low oil pressure=
//he added 2L oil and started the gen ","Parker Tchoup","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Low Oil Pressure","Site went down because gen =
start and stopped with alarm low oil pressure//he added 2L oil and started =
the gen ","charly.diekem-yemeli@sagemcom.com","198","23-03-2025 09:45:54","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004639631","M=
endong","","23-03-2025 09:32:46","23-03-2025 09:15:38","23-03-2025 09:38:34=
","Grid fluctuation, Site went down because Gen failed to start due to Grid=
 bad voltage No RCP// Grid Restored","Hyemafo Gildas","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site=
 went down because Gen failed to start due to Grid bad voltage No RCP// Gri=
d Restored","el-dalile@sagemcom.com","1029","23-03-2025 09:32:46","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0004639622","Nkoulou =
Carriere carrefourt","","23-03-2025 09:29:48","23-03-2025 09:19:22","23-03-=
2025 10:24:27","Cascaded Incident from TTO4719340","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","Site went down b=
ecause 2/6 rectifier disfunctionning SS IHS Alphonse Deffo is informed//he =
reset the reset the rectifiers","system","269280","23-03-2025 09:29:48","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0004639585","Aba=
ng","IHS_YND_794","23-03-2025 09:21:40","23-03-2025 09:19:22","23-03-2025 1=
0:24:27","Site went down because 2/6 rectifier disfunctionning SS IHS Alpho=
nse Deffo is informed//he reset the reset the rectifiers","Mba Lazare Herve=
","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went do=
wn because 2/6 rectifier disfunctionning SS IHS Alphonse Deffo is informed/=
/he reset the reset the rectifiers","el-dalile@sagemcom.com","139","23-03-2=
025 09:21:40","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004639536","OBA=
M NGOLA OCM","","23-03-2025 09:13:34","23-03-2025 09:10:26","23-03-2025 14:=
20:26","Grid outage, Site went down because gen start and stopped due to ov=
er voltage // Reset of gen card done and gen started","MINKA NICOLAS","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Sit=
e went down because gen start and stopped due to over voltage // Reset of g=
en card done and gen started","charly.diekem-yemeli@sagemcom.com","189","23=
-03-2025 09:13:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004639504","B=
riqueterie","","23-03-2025 09:06:55","23-03-2025 08:58:44","24-03-2025 01:0=
5:14","Grid outage, No space to deploy MDG // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spac=
e to deploy MDG // Grid return","el-dalile@sagemcom.com","492","23-03-2025 =
09:06:55","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004639387","Elo=
umdem stade","","23-03-2025 08:50:46","23-03-2025 08:39:35","23-03-2025 12:=
14:30","Grid bad voltage,and gen failed to start,no rcp // bypassed grid an=
d started the gen","Fanda Brice","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid bad voltage,and gen failed to start,no=
 rcp // bypassed grid and started the gen","charly.diekem-yemeli@sagemcom.c=
om","672","23-03-2025 08:50:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004639378","N=
kozoa","","23-03-2025 08:49:18","23-03-2025 08:47:10","23-03-2025 10:23:23"=
,"Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Feli=
x bateu is informed and confirmed// grid return","Fabrice Pouakam","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went d=
own due to gen overload (20kva, 340A) SS HIS Felix bateu is informed and co=
nfirmed// grid return","el-dalile@sagemcom.com","130","23-03-2025 08:49:18"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004639337","Bri=
quetterie","","23-03-2025 08:42:52","23-03-2025 08:26:40","23-03-2025 15:14=
:01","Grid outage, No space to deploy MDG // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space=
 to deploy MDG // Grid return","charly.diekem-yemeli@sagemcom.com","973","2=
3-03-2025 08:42:52","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004639332","ODZ=
A MINKAN EDIBI ASSI","","23-03-2025 08:42:08","23-03-2025 08:25:01","23-03-=
2025 12:23:40","Site went  down due to MPR malfunctioning // He reset it ",=
"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Cabinet=
","Site went  down due to MPR malfunctioning // He reset it ","charly.dieke=
m-yemeli@sagemcom.com","1029","23-03-2025 08:42:08","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004639138","Ole=
mbe MTN","","23-03-2025 08:02:35","23-03-2025 07:42:25","23-03-2025 11:15:3=
9","Site went down because 1/2 rectifier faultySS IHS Felix is informed//he=
 remove the faulty rectifier(remplacment ongoing)","Fabrice Pouakam","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down becau=
se 1/2 rectifier faultySS IHS Felix is informed//he remove the faulty recti=
fier(remplacment ongoing)","charly.diekem-yemeli@sagemcom.com","1212","23-0=
3-2025 08:02:35","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004639128","Nom=
ayos montee Meche","","23-03-2025 08:00:46","23-03-2025 07:37:35","23-03-20=
25 15:32:53","Grid outage, Site went down because Gen started and stopped d=
ue emergency stop button was activeted// He actived the button and started =
Gen manualy","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - =
Emergency Stop","Grid outage, Site went down because Gen started and stoppe=
d due emergency stop button was activeted// He actived the button and start=
ed Gen manualy","charly.diekem-yemeli@sagemcom.com","1392","23-03-2025 08:0=
0:46","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004639099","ETO=
UDI Entree du palais","","23-03-2025 07:50:31","23-03-2025 07:32:21","23-03=
-2025 10:01:09","Grid outage,gen failed to start because Grid contactor did=
 not excite//FME  excited manually :site on grid","Fabrice Pouakam","Equipm=
ent Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,gen fail=
ed to start because Grid contactor did not excite//FME  excited manually :s=
ite on grid","charly.diekem-yemeli@sagemcom.com","1092","23-03-2025 07:50:3=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004639093","K=
oweit City","","23-03-2025 07:49:19","23-03-2025 07:44:12","23-03-2025 09:5=
8:26","Grid outage, Site went down because Gen started and stopped with ""L=
ow fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, Site went down because Gen started and stopped with ""Low =
fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","el-=
dalile@sagemcom.com","308","23-03-2025 07:49:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004639086","Manguier=
","","23-03-2025 07:47:58","23-03-2025 07:24:27","23-03-2025 09:40:19","Cas=
caded Incident from TTO4718780 - Cascade Removed From TTO4718780","Fabrice =
Pouakam","Cascade Outage","Passive","Cascade Passive","Cascade Passive","	G=
rid outage, site went down due to gen overload (22kva, 340A) SS HISBernard =
ATANGANA is informed and confirmed// He reduced the load","system","319064"=
,"23-03-2025 07:47:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_509","NOCINC0004639085","MANGUIER=
S CHAPELLE","IHS_YND_506, IHS_YND_209","23-03-2025 07:47:58","23-03-2025 07=
:24:27","23-03-2025 09:40:19","	Grid outage, site went down due to gen over=
load (22kva, 340A) SS HISBernard ATANGANA is informed and confirmed// He re=
duced the load","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","	Grid outage, site went down due to gen overload (22kva, =
340A) SS HISBernard ATANGANA is informed and confirmed// He reduced the loa=
d","system","1411","23-03-2025 07:47:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004639080","O=
mnisport-Rail","","23-03-2025 07:46:35","23-03-2025 07:24:27","23-03-2025 0=
9:40:19","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","	Grid outage, site went down due to gen overload (22kva, =
340A) SS HISBernard ATANGANA is informed and confirmed// He reduced the loa=
d","el-dalile@sagemcom.com","1329","23-03-2025 07:46:35","Sagemcom CMR"
"Closed Complete","Warning","T0462","IHS_YND_123","NOCINC0004639075","Nkomo=
 II","","23-03-2025 07:45:49","","","eneo outage // eneo return","Albran By=
orel","Warning","Warning","POWER","Warning - Site on Battery","eneo outage =
// eneo return","charly.diekem-yemeli@sagemcom.com","2297","23-03-2025 07:4=
5:49","Sagemcom CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0004638680","Ngo=
usso MTN","","23-03-2025 06:03:40","22-03-2025 21:59:20","23-03-2025 10:05:=
53","Grid outage, no space to deploy // Grid return ","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, no space to =
deploy // Grid return ","cedric.tiani@sagemcom.com","29061","23-03-2025 06:=
03:40","Sagemcom CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004638673","Nta=
ba","","23-03-2025 05:57:36","23-03-2025 05:50:11","23-03-2025 08:18:41","G=
rid outage, Site went down because Gen ran until fuel shortage// Refueling =
Done","Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage, Site went down because Gen ran until fuel shortage// Refueling D=
one","mariam.tchonang@sagemcom.com","446","23-03-2025 05:57:36","Sagemcom C=
MR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004638582","Ole=
mbe MTN","","23-03-2025 05:24:47","23-03-2025 04:06:15","23-03-2025 06:36:3=
4","Site went down because 1/2 rectifer went faulty SS IHS felix ZAMBE is i=
nformed// He removed rectifier faulty","Fabrice Pouakam","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down because 1/2 recti=
fer went faulty SS IHS felix ZAMBE is informed// He removed rectifier fault=
y","mariam.tchonang@sagemcom.com","4713","23-03-2025 05:24:47","Sagemcom CM=
R"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004638547","ETO=
UDI Entree du palais","","23-03-2025 05:07:02","23-03-2025 05:05:45","23-03=
-2025 05:11:45","Grid fluctuation, site went down before gen start due to p=
oor battery backup // Gen start automatically","Fabrice Pouakam","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid fluc=
tuation, site went down before gen start due to poor battery backup // Gen =
start automatically","mariam.tchonang@sagemcom.com","78","23-03-2025 05:07:=
02","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004638475","Com=
plex Beac II","","23-03-2025 04:39:38","23-03-2025 04:34:41","23-03-2025 05=
:12:04","Grid outage, site went down because the generator card cable is fa=
ulty //grid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage, site went down because the generator =
card cable is faulty //grid return","mariam.tchonang@sagemcom.com","298","2=
3-03-2025 04:39:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_100","NOCINC0004638449","Shell-Ns=
imeyong","","23-03-2025 04:24:09","23-03-2025 04:09:26","23-03-2025 04:54:5=
8","Cascaded Incident from TTO4718017","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","access issue during the night  =
(Grid outage, Site went down because gen failed to start due to grid bad vo=
ltgae and no RCP // Grid Restored)","system","273433","23-03-2025 04:24:09"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004638446","NYO=
M FACE MAETUR","","23-03-2025 04:22:09","23-03-2025 04:04:58","23-03-2025 0=
8:25:40","Grid outage site went down because Gen failed to start due to fau=
lty Gen card // Grid return","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start due to faulty Gen card // Grid return","cedric.tiani@sagemc=
om.com","1033","23-03-2025 04:22:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0004638439","Montee-J=
ouvence","","23-03-2025 04:21:30","23-03-2025 04:09:26","23-03-2025 04:54:5=
8","Cascaded Incident from TTO4718017","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","access issue during the night =
 (Grid outage, Site went down because gen failed to start due to grid bad v=
oltgae and no RCP // Grid Restored)","system","273433","23-03-2025 04:21:30=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0004638433","Mendong =
Maeture","","23-03-2025 04:19:29","23-03-2025 04:09:26","23-03-2025 04:54:5=
8","Cascaded Incident from TTO4718017","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","access issue during the night =
 (Grid outage, Site went down because gen failed to start due to grid bad v=
oltgae and no RCP // Grid Restored)","system","273434","23-03-2025 04:19:29=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0004638432","Mendong =
vallee","","23-03-2025 04:19:29","23-03-2025 04:09:26","23-03-2025 19:51:26=
","Grid outage site went down because Gen over load (20KVA; 300A) // Grid r=
eturn IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Brice","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went do=
wn because Gen over load (20KVA; 300A) // Grid return IHS F=E9lix Zamb=E9 i=
s informed and confirmed","system","603","23-03-2025 04:19:29","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004638419","N=
kolondom","","23-03-2025 04:13:54","23-03-2025 04:09:26","23-03-2025 08:25:=
48","Grid bad voltage,and gen failed to start//bypassed grid and started th=
e gen manually started","Fabrice Pouakam","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Grid bad voltage,and gen failed to=
 start//bypassed grid and started the gen manually started","mariam.tchonan=
g@sagemcom.com","450","23-03-2025 04:13:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004638415","M=
endong","IHS_YND_569, IHS_YND_236, IHS_YND_100","23-03-2025 04:11:36","23-0=
3-2025 04:09:26","23-03-2025 04:54:58","access issue during the night  (Gri=
d outage, Site went down because gen failed to start due to grid bad voltga=
e and no RCP // Grid Restored)","Hyemafo Gildas","Access Denial","Lease Or =
Legal","Landlord Related Issues","Access Issue - Land Lord","access issue d=
uring the night  (Grid outage, Site went down because gen failed to start d=
ue to grid bad voltgae and no RCP // Grid Restored)","cedric.tiani@sagemcom=
.com","131","23-03-2025 04:11:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004638378","MBIMBIM"=
,"","23-03-2025 03:56:51","23-03-2025 03:51:51","23-03-2025 03:51:52","Casc=
aded Incident from TTO4717969","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on solar ;=
 Ubaie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.=
","system","267115","23-03-2025 03:56:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004638373","Ngoum","=
","23-03-2025 03:56:50","23-03-2025 03:51:51","23-03-2025 03:51:52","Cascad=
ed Incident from TTO4717969","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on solar ; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","267118","23-03-2025 03:56:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0004638375","Yoko OCM=
","","23-03-2025 03:56:50","23-03-2025 03:51:51","23-03-2025 03:51:52","Cas=
caded Incident from TTO4717969","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on solar =
; Ubaie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed=
.","system","267116","23-03-2025 03:56:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004638376","Ngouetou=
","","23-03-2025 03:56:50","23-03-2025 03:51:51","23-03-2025 03:51:52","Cas=
caded Incident from TTO4717969","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on solar =
; Ubaie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed=
.","system","267117","23-03-2025 03:56:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004638374","Matsari"=
,"","23-03-2025 03:56:50","23-03-2025 03:51:51","23-03-2025 03:51:52","Casc=
aded Incident from TTO4717969","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on solar ;=
 Ubaie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.=
","system","267117","23-03-2025 03:56:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0004638231","A=
bome","","23-03-2025 02:50:34","23-03-2025 02:43:05","23-03-2025 03:15:15",=
"Grid fluctuation, Site went down because Gen failed to start due to Grid b=
ad voltage No rcp// He bypassed Grid and started Gen manually","MINKA NICOL=
AS","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, Site went down because Gen failed to start due to Grid=
 bad voltage No rcp// He bypassed Grid and started Gen manually","mariam.tc=
honang@sagemcom.com","451","23-03-2025 02:50:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004638002","C=
omplexe-BEAC","","23-03-2025 01:32:00","23-03-2025 01:27:49","23-03-2025 04=
:39:09","Grid outage,gen ran till fuel shortage//Refueling done","Albran By=
orel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran=
 till fuel shortage//Refueling done","cedric.tiani@sagemcom.com","252","23-=
03-2025 01:32:00","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004637663","OTE=
LE MTN","","23-03-2025 00:08:58","22-03-2025 23:59:26","23-03-2025 02:07:26=
","Grid outage, Site went down because gen start and stoppen with alarm low=
 oil pressure // He added oil pressure (3L) and gen manually started","Fand=
a Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure",=
"Grid outage, Site went down because gen start and stoppen with alarm low o=
il pressure // He added oil pressure (3L) and gen manually started","mariam=
.tchonang@sagemcom.com","573","23-03-2025 00:08:58","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004637546","ETO=
UDI Entree du palais","","22-03-2025 23:47:19","22-03-2025 23:38:54","23-03=
-2025 00:08:41","Grid fluctuation, site went down before gen start due to p=
oor battery backup // Gen start automatically","Fabrice Pouakam","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctu=
ation, site went down before gen start due to poor battery backup // Gen st=
art automatically","mariam.tchonang@sagemcom.com","506","22-03-2025 23:47:1=
9","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004637498","M=
essa-Carriere OCM","","22-03-2025 23:28:04","22-03-2025 23:19:49","22-03-20=
25 23:20:49","No Power issue on site Ubaie=3D55.2V site on Gen The TX Fme M=
ohamadou 691144435 of huawei is informed.","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No Power issue on=
 site Ubaie=3D55.2V site on Gen The TX Fme Mohamadou 691144435 of huawei is=
 informed.","mariam.tchonang@sagemcom.com","496","22-03-2025 23:28:04","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0004637492","Hotel de=
 Ville Yde","","22-03-2025 23:26:08","22-03-2025 23:03:27","22-03-2025 23:1=
0:06","Cascaded Incident from TTO4716935","Paul BIBOUM","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue on site Ubaie =3D5=
2.4V site on grid=20

TX Fme Eloundou(652586578) from Huawei is informed
","system","269976","22-03-2025 23:26:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0004637482","N=
R-Bastos","IHS_YND_019","22-03-2025 23:23:47","22-03-2025 23:03:27","23-03-=
2025 00:57:06","No power issue on site Ubaie =3D52.4V site on grid   TX Fme=
 Eloundou(652586578) from Huawei is informed","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site Ubaie =3D52.4V site on grid=20

TX Fme Eloundou(652586578) from Huawei is informed
","mariam.tchonang@sagemcom.com","1221","22-03-2025 23:23:47","Sagemcom CMR=
"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004637435","Abo=
me","","22-03-2025 23:14:45","22-03-2025 22:19:27","23-03-2025 00:50:46","G=
rid fluctuation, Site went down because Gen failed to start due to Grid bad=
 voltage No rcp//  He bypassed Grid and started Gen manually","MINKA NICOLA=
S","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, Site went down because Gen failed to start due to Grid =
bad voltage No rcp//  He bypassed Grid and started Gen manually","mariam.tc=
honang@sagemcom.com","3319","22-03-2025 23:14:45","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004637119","NYO=
M 2 IHS","","22-03-2025 22:16:36","22-03-2025 22:09:23","22-03-2025 22:51:2=
4","Site went down because Gen failed to start due to Grid bad voltage // h=
e bypass the Grid and Gen manually started","Fabrice Pouakam","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Site went down=
 because Gen failed to start due to Grid bad voltage // he bypass the Grid =
and Gen manually started","yves.djomo@sagemcom.com","434","22-03-2025 22:16=
:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0004637116","Nkoulou =
Carriere carrefourt","","22-03-2025 22:16:07","22-03-2025 22:10:13","22-03-=
2025 23:38:38","Cascaded Incident from TTO4716487","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","Site went down b=
ecause gen failed to start due to grid bad voltage and no RCP // Gen manual=
ly started","system","280458","22-03-2025 22:16:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0004637117","Nkolanga=
a","","22-03-2025 22:16:07","22-03-2025 22:10:13","22-03-2025 23:38:38","Ca=
scaded Incident from TTO4716487","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because gen failed =
to start due to grid bad voltage and no RCP // Gen manually started","syste=
m","280458","22-03-2025 22:16:07","Sagemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0004637112","Aba=
ng","IHS_YND_794, IHS_YND_289","22-03-2025 22:15:16","22-03-2025 22:10:13",=
"22-03-2025 23:38:38","Grid outage, Site went down because gen failed to st=
art due to grid bad voltage and  RCP // Gen manually started","Mba Lazare H=
erve","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Site went down because gen failed to start due to grid bad voltage and=
 no RCP // Gen manually started","yves.djomo@sagemcom.com","305","22-03-202=
5 22:15:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004637110","S=
OA TOWN","","22-03-2025 22:14:20","22-03-2025 22:05:16","22-03-2025 22:55:2=
8","Grid outage, site went down because gen start and stopped with high tem=
p alarm // He added water and manually start the gen","Siligap Boris","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // He added water and manually start the gen","yves.djomo@sage=
mcom.com","545","22-03-2025 22:14:20","Sagemcom CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004636541","MEH=
ANDAN","","22-03-2025 21:07:24","22-03-2025 20:53:16","22-03-2025 22:41:25"=
,"Site went down due to insufficiency of rectifiers on site SS IHS Pascalin=
e is confirm // He reduced the load","Albran Byorel","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","Site went down due to insufficiency =
of rectifiers on site SS IHS Pascaline is confirm // He reduced the load","=
yves.djomo@sagemcom.com","849","22-03-2025 21:07:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004636504","E=
kombitie","","22-03-2025 20:59:11","22-03-2025 20:49:02","22-03-2025 21:10:=
40","Grid outage, site went down because Gen started and stopped to start d=
ue to grid bad voltage and Rcp// He bypassed the grid and started Gen manua=
lly","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid outage, site went down because Gen started and s=
topped to start due to grid bad voltage and Rcp// He bypassed the grid and =
started Gen manually","ferot.nongni-djiogap@sagemcom.com","610","22-03-2025=
 20:59:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004636469","O=
dza II OCM","","22-03-2025 20:54:01","22-03-2025 20:25:55","22-03-2025 23:3=
7:30","Site went down because CB 2*125A tripped in Pwc//He reamed the CB","=
Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Circuit Breaker Issue","Site went down because CB 2*125A tripped in Pwc//=
He reamed the CB","yves.djomo@sagemcom.com","1687","22-03-2025 20:54:01","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004636466","O=
lembe-Terminus","","22-03-2025 20:53:42","22-03-2025 20:51:35","22-03-2025 =
20:56:02","No power issue, site on Grid with Ubaie=3D 53.3 V.   The Fme Tx =
Symphorien (650257151/ 675295205) from Huawei is informed. ","Fabrice Pouak=
am","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue, site on Grid with Ubaie=3D 53.3 V.   The Fm=
e Tx Symphorien (650257151/ 675295205) from Huawei is informed. ","ferot.no=
ngni-djiogap@sagemcom.com","128","22-03-2025 20:53:42","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004636393","Ole=
mbe MTN","","22-03-2025 20:38:31","22-03-2025 20:35:25","23-03-2025 01:26:1=
6","Site went down because 1/3 rectifer went faulty SS IHS felix ZAMBE is i=
nformed// He removed rectifier faulty","Fabrice Pouakam","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down because 1/3 recti=
fer went faulty SS IHS felix ZAMBE is informed// He removed rectifier fault=
y","yves.djomo@sagemcom.com","187","22-03-2025 20:38:31","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004636375","MAN=
GUIERS CHAPELLE","","22-03-2025 20:33:24","22-03-2025 20:02:38","23-03-2025=
 01:58:09","Grid outage, site went down due to gen overload (22kva, 340A) S=
S HISBernard ATANGANA  is informed and confirmed// He reduced the load","Fa=
brice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid outage, site went down due to gen overload (22kva, 340A) SS HISBernard =
ATANGANA  is informed and confirmed// He reduced the load","yves.djomo@sage=
mcom.com","1847","22-03-2025 20:33:24","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004636222","Eto=
ug ebe biscuiterie","","22-03-2025 20:14:30","22-03-2025 20:09:25","22-03-2=
025 21:59:28","Grid outage, Site went down before Gen start due to poor bac=
kup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went =
down before Gen start due to poor backup // Gen started automatically","yve=
s.djomo@sagemcom.com","306","22-03-2025 20:14:30","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004635947","Nsi=
meyong Terre Rouge","","22-03-2025 19:33:21","22-03-2025 19:27:17","22-03-2=
025 19:53:42","Grid outage, Site went down because Gen ran until fuel short=
age// Refueling Done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Die=
sel Outage","Grid outage, Site went down because Gen ran until fuel shortag=
e// Refueling Done","yves.djomo@sagemcom.com","365","22-03-2025 19:33:21","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004635843","O=
dza II","","22-03-2025 19:14:30","22-03-2025 18:50:24","23-03-2025 01:10:12=
","No power issue on site U=3D52.4 V site on Grid  The TX Lionel steve //65=
5184876 from Huawei is informed.Notice that we have disjunction in OCM equi=
pment.","Albran Byorel","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52.4 V site =
on Grid  The TX Lionel steve //655184876 from Huawei is informed.Notice tha=
t we have disjunction in OCM equipment.","yves.djomo@sagemcom.com","1448","=
22-03-2025 19:14:30","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004635803","Nko=
l-Mbanda","","22-03-2025 19:11:00","22-03-2025 19:02:56","22-03-2025 19:44:=
15","Grid outage, Site went down because Gen ran until fuel shortage// Refu=
eling Done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid outage, Site went down because Gen ran until fuel shortage// Refuel=
ing Done","yves.djomo@sagemcom.com","485","22-03-2025 19:11:00","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004635739","N=
komkana 2","","22-03-2025 18:56:49","22-03-2025 18:17:45","22-03-2025 22:22=
:45","Access issue during the night;Site went down because the section of p=
ower cable supplying  the inverter box got burnt//he cut the affected secti=
on  and reconnected it","Mboua Thierry","Access Denial","Lease Or Legal","L=
andlord Related Issues","Access Issue - Land Lord","Access issue during the=
 night;Site went down because the section of power cable supplying  the inv=
erter box got burnt//he cut the affected section  and reconnected it","yves=
.djomo@sagemcom.com","2345","22-03-2025 18:56:49","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004635539","Nko=
zoa","","22-03-2025 18:21:01","22-03-2025 18:00:55","22-03-2025 18:57:13","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and site on GEN","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to gen overload (20kva, 340A) SS HIS Felix ba=
teu is informed and confirmed// He reduced the load and site on GEN","yves.=
djomo@sagemcom.com","1207","22-03-2025 18:21:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0004635364","Nkolfoul=
ou Tsinga Village","","22-03-2025 17:54:21","22-03-2025 17:44:59","22-03-20=
25 18:00:27","Cascaded Incident from TTO4714438","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid fluctuation, Sit=
e went down because CB Battery tripped due to Grid fluctuation// Grid stabi=
lized and CB Baterry rearmed","system","274838","22-03-2025 17:54:21","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_296","NOCINC0004635363","Nkolfoul=
ou","","22-03-2025 17:54:20","22-03-2025 17:44:59","22-03-2025 18:00:27","C=
ascaded Incident from TTO4714438","Siligap Boris","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down bec=
ause CB Battery tripped due to Grid fluctuation// Grid stabilized and CB Ba=
terry rearmed","system","274838","22-03-2025 17:54:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004635361","SOA VILL=
AGE","","22-03-2025 17:54:20","22-03-2025 17:44:59","22-03-2025 18:00:27","=
Cascaded Incident from TTO4714438","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down be=
cause CB Battery tripped due to Grid fluctuation// Grid stabilized and CB B=
aterry rearmed","system","274836","22-03-2025 17:54:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004635359","Mvog-Eba=
nda","","22-03-2025 17:54:20","22-03-2025 17:44:59","22-03-2025 18:00:27","=
Cascaded Incident from TTO4714438","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down be=
cause CB Battery tripped due to Grid fluctuation// Grid stabilized and CB B=
aterry rearmed","system","274837","22-03-2025 17:54:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004635360","TSINGA V=
ILLAGE 2","","22-03-2025 17:54:20","22-03-2025 17:44:59","22-03-2025 18:00:=
27","Cascaded Incident from TTO4714438","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, Site went d=
own because CB Battery tripped due to Grid fluctuation// Grid stabilized an=
d CB Baterry rearmed","system","274835","22-03-2025 17:54:20","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_758","NOCINC0004635362","Nkolfoul=
ou CSD MTN","","22-03-2025 17:54:20","22-03-2025 17:44:59","22-03-2025 18:0=
0:27","Cascaded Incident from TTO4714438","Siligap Boris","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid fluctuation, Site went =
down because CB Battery tripped due to Grid fluctuation// Grid stabilized a=
nd CB Baterry rearmed","system","274837","22-03-2025 17:54:20","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0004635358","FOUGEROL=
E","","22-03-2025 17:54:19","22-03-2025 17:44:59","22-03-2025 18:00:27","Ca=
scaded Incident from TTO4714438","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuation, Site went down beca=
use CB Battery tripped due to Grid fluctuation// Grid stabilized and CB Bat=
erry rearmed","system","274836","22-03-2025 17:54:19","Sagemcom CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0004635327","Nko=
lfoulou 2","IHS_YND_561, IHS_YND_269, IHS_YND_719, IHS_YND_323, IHS_YND_758=
, IHS_YND_296, IHS_YND_759","22-03-2025 17:49:06","22-03-2025 17:44:59","22=
-03-2025 18:00:41","Grid fluctuation, Site went down because CB Battery tri=
pped due to Grid fluctuation// Grid stabilized and CB Baterry rearmed","Sil=
igap Boris","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation, Site went down because CB Battery tripped due =
to Grid fluctuation// Grid stabilized and CB Baterry rearmed","yves.djomo@s=
agemcom.com","247","22-03-2025 17:49:06","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004635107","ODZ=
A MINKAN EDIBI ASSI","","22-03-2025 17:26:43","22-03-2025 17:10:36","22-03-=
2025 17:15:57","Active// No power issue on site, Site on grid Ubai=3D 54.6V=
 Technician Aurelien Ruchel/681953783/ SIMIDETICH working on site","Albran =
Byorel","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active// No power issue on site, Site on grid Ubai=3D 5=
4.6V Technician Aurelien Ruchel/681953783/ SIMIDETICH working on site","yve=
s.djomo@sagemcom.com","968","22-03-2025 17:26:43","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0004635014","MVA=
N SACEL","","22-03-2025 17:09:29","22-03-2025 16:45:16","22-03-2025 17:51:5=
5","	Grid outage, Gen ran until fuel shortage// Refueling Done","MINKA NICO=
LAS","Fuel Outage","Passive","Diesel","Diesel Outage","	Grid outage, Gen ra=
n until fuel shortage// Refueling Done","yves.djomo@sagemcom.com","1455","2=
2-03-2025 17:09:29","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004634892","Mon=
tee Jouvence","","22-03-2025 16:57:43","22-03-2025 16:51:33","22-03-2025 20=
:03:14","Grid outage, Gen ran until fuel shortage// Refueling Done","Hyemaf=
o Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, Ge=
n ran until fuel shortage// Refueling Done","yves.djomo@sagemcom.com","371"=
,"22-03-2025 16:57:43","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004634688","Bon=
djock","","22-03-2025 16:41:18","22-03-2025 16:40:13","22-03-2025 17:10:54"=
,"Grid outage, site went down because gen ran untill fuel shorateg // Refue=
ling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, site went down because gen ran untill fuel shorateg // Refueli=
ng done","yves.djomo@sagemcom.com","66","22-03-2025 16:41:18","Sagemcom CMR=
"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0004634679","Ngo=
uetou","","22-03-2025 16:39:14","22-03-2025 16:37:06","22-03-2025 16:57:47"=
,"Site went down because gen start and stopped with high temp alarm // He a=
dded water and manually start the gen","Parker Tchoup","Equipment Repair","=
Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Site w=
ent down because gen start and stopped with high temp alarm // He added wat=
er and manually start the gen","yves.djomo@sagemcom.com","129","22-03-2025 =
16:39:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_520","NOCINC0004634666","SIMBOCK =
BONAMBAPE","","22-03-2025 16:38:04","22-03-2025 16:07:11","22-03-2025 17:35=
:46","Cascaded Incident from TTO4713543","Hyemafo Gildas","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down =
because Gen ran until fuel shortage// Refueling ongoing","system","280471",=
"22-03-2025 16:38:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004634622","B=
arriere IHS","","22-03-2025 16:27:36","22-03-2025 16:07:11","22-03-2025 17:=
35:46","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, Site went down because Gen ran until fuel shor=
tage// Refueling ongoing","ferot.nongni-djiogap@sagemcom.com","280471","22-=
03-2025 16:27:36","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004634559","Ngu=
ila","","22-03-2025 16:15:13","22-03-2025 16:12:16","22-03-2025 17:19:53","=
Site went down because gen failed to start with alarm undervoltage // He re=
set gen card and gen manually started","Parker Tchoup","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Site went down because gen fail=
ed to start with alarm undervoltage // He reset gen card and gen manually s=
tarted","yves.djomo@sagemcom.com","178","22-03-2025 16:15:13","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004634553","M=
efou-Assi","IHS_YND_520, IHS_YND_696","22-03-2025 16:14:20","22-03-2025 16:=
07:11","22-03-2025 17:35:46","Grid outage, Site went down because Gen ran u=
ntil fuel shortage// Refueling ongoing","Fanda Brice","Fuel Outage","Passiv=
e","Diesel","Diesel Outage","Grid outage, Site went down because Gen ran un=
til fuel shortage// Refueling ongoing","ferot.nongni-djiogap@sagemcom.com",=
"430","22-03-2025 16:14:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0004634480","N=
komo","","22-03-2025 15:57:40","22-03-2025 15:54:28","22-03-2025 16:17:48",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Gen start automatically","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore Gen start due to poor battery backup // Gen start automatically","fer=
ot.nongni-djiogap@sagemcom.com","193","22-03-2025 15:57:40","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004634429","OBA=
M NGOLA OCM","","22-03-2025 15:49:24","22-03-2025 15:45:14","22-03-2025 16:=
19:04","Grid outage site went down because Gen failed to start due to Gen b=
attery discharged causing by charging alternator faulty // Gen manually sta=
rted with external battery","MINKA NICOLAS","Equipment Repair","Passive","A=
CDG Gen","ACDG - Charging Alternator","Grid outage site went down because G=
en failed to start due to Gen battery discharged causing by charging altern=
ator faulty // Gen manually started with external battery","yves.djomo@sage=
mcom.com","251","22-03-2025 15:49:24","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004634312","Nko=
lbong","","22-03-2025 15:24:51","22-03-2025 15:18:46","22-03-2025 16:46:59"=
,"Grid outage, Site went down because Gen failed to start due Gen card disf=
unction// He reset Gen card and started Gen manually","Delor Telezing","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Si=
te went down because Gen failed to start due Gen card disfunction// He rese=
t Gen card and started Gen manually","yves.djomo@sagemcom.com","367","22-03=
-2025 15:24:51","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0004634275","Ole=
mbe","","22-03-2025 15:18:45","22-03-2025 15:11:41","22-03-2025 15:34:49","=
Grid outage, Site went down because Gen ran until fuel shortage// Refueling=
 ongoing","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid outage, Site went down because Gen ran until fuel shortage// Refuel=
ing ongoing","yves.djomo@sagemcom.com","426","22-03-2025 15:18:45","Sagemco=
m CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004634244","Ole=
mbe MTN","","22-03-2025 15:11:26","22-03-2025 15:08:22","22-03-2025 17:14:3=
7","Site went down because 1/3 rectifer went faulty SS IHS felix ZAMBE is i=
nformed// He removed rectifier faulty","Fabrice Pouakam","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down because 1/3 recti=
fer went faulty SS IHS felix ZAMBE is informed// He removed rectifier fault=
y","yves.djomo@sagemcom.com","185","22-03-2025 15:11:26","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004634087","ODZ=
A MINKAN EDIBI ASSI","","22-03-2025 14:50:50","22-03-2025 14:47:45","22-03-=
2025 15:04:26","Grid outage, Site went down because gen failed to start due=
 to grid bad voltgae and no RCP // Grid stabilized","Albran Byorel","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid out=
age, Site went down because gen failed to start due to grid bad voltgae and=
 no RCP // Grid stabilized","yves.djomo@sagemcom.com","186","22-03-2025 14:=
50:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004633834","K=
oweit City","","22-03-2025 14:09:47","22-03-2025 13:22:39","22-03-2025 15:1=
5:06","Grid outage, Site went down because Gen started and stopped with ""L=
ow fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, Site went down because Gen started and stopped with ""Low =
fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","fer=
ot.nongni-djiogap@sagemcom.com","2828","22-03-2025 14:09:47","Sagemcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004633783","Ron=
d Point Express1114","","22-03-2025 14:01:26","22-03-2025 13:54:16","22-03-=
2025 14:12:35","Grid outage, site went down before gen start due to poor ba=
ttery backup // Gen start automatically","Hyemafo Gildas","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen start automa=
tically","ferot.nongni-djiogap@sagemcom.com","431","22-03-2025 14:01:26","S=
agemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004633774","Men=
dong3","","22-03-2025 13:59:16","22-03-2025 13:42:08","22-03-2025 20:50:38"=
,"Grid outage, no space to deploy MDG // Grid return ","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage, no space to=
 deploy MDG // Grid return ","ferot.nongni-djiogap@sagemcom.com","1029","22=
-03-2025 13:59:16","Sagemcom CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0004633717","Cam=
p-Sonel","","22-03-2025 13:49:17","22-03-2025 12:34:09","22-03-2025 12:40:4=
3","No power issue on site U=3D54;3v site on grid tx FME armand Nguetsa of =
huawei is informed","Siligap Boris","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D=
54;3v site on grid tx FME armand Nguetsa of huawei is informed","ferot.nong=
ni-djiogap@sagemcom.com","4509","22-03-2025 13:49:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004633582","O=
LAMA","","22-03-2025 13:22:08","22-03-2025 12:42:51","22-03-2025 13:17:06",=
"Grid outage, site went down because gen ran untill fuel shorateg // Refuel=
ing done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage, site went down because gen ran untill fuel shorateg // Refuelin=
g done","ferot.nongni-djiogap@sagemcom.com","2358","22-03-2025 13:22:08","S=
agemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004633542","Abo=
me","","22-03-2025 13:18:36","22-03-2025 13:14:25","22-03-2025 13:36:33","G=
rid fluctuation, Site went down because gen fails to start due to grid bad =
voltage,no rcp// He bypasse the Grid and site on Gen","MINKA NICOLAS","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid f=
luctuation, Site went down because gen fails to start due to grid bad volta=
ge,no rcp// He bypasse the Grid and site on Gen","ferot.nongni-djiogap@sage=
mcom.com","295","22-03-2025 13:18:36","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004633511","Aha=
la Echangeur","","22-03-2025 13:13:12","22-03-2025 12:27:59","22-03-2025 14=
:15:13","Site went down because gen start an stopped due to water infiltrat=
ion in tank // He purged The tank and Gen manually started","MINKA NICOLAS"=
,"Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In=
 The Fuel","Site went down because gen start an stopped due to water infilt=
ration in tank // He purged The tank and Gen manually started","ferot.nongn=
i-djiogap@sagemcom.com","2714","22-03-2025 13:13:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0004633413","N=
ew-Marche-Melen","","22-03-2025 12:54:45","22-03-2025 11:46:37","22-03-2025=
 11:50:37","No power Issue Site on Grid Ubai =3D54.3 V. The TX FME Mbah Hos=
iah (674007438) is informed","Paul BIBOUM","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power Issue Site =
on Grid Ubai =3D54.3 V. The TX FME Mbah Hosiah (674007438) is informed","fe=
rot.nongni-djiogap@sagemcom.com","4088","22-03-2025 12:54:45","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004633402","O=
lembe-Terminus","","22-03-2025 12:52:18","22-03-2025 12:14:12","22-03-2025 =
15:09:24","Grid outage, site went down because gen start and stopped due to=
 high temp // He added water and manually start the gen","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, site went down because gen start and stopped due=
 to high temp // He added water and manually start the gen","ferot.nongni-d=
jiogap@sagemcom.com","2287","22-03-2025 12:52:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004633364","F=
ouda-New","","22-03-2025 12:46:25","22-03-2025 12:37:10","22-03-2025 13:18:=
06","Grid outage.gen ran until fuel shortage//Refueling done","Delor Telezi=
ng","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran u=
ntil fuel shortage//Refueling done","ferot.nongni-djiogap@sagemcom.com","55=
6","22-03-2025 12:46:25","Sagemcom CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0004633337","NYO=
M","","22-03-2025 12:43:25","22-03-2025 12:18:11","22-03-2025 14:38:40","Gr=
id outage, Gen ran until fuel shortage// refueling Done","Fabrice Pouakam",=
"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, Gen ran unti=
l fuel shortage// refueling Done","ferot.nongni-djiogap@sagemcom.com","1514=
","22-03-2025 12:43:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004633331","E=
lig-Edzoa","","22-03-2025 12:41:37","22-03-2025 12:34:15","23-03-2025 13:04=
:08","No free mobil gen waiting grid return","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","No free mobil gen waiting grid ret=
urn","kouoh.jean@ihstowers.com","444","22-03-2025 12:41:37","Sagemcom CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004633244","Odz=
a petit marche new","","22-03-2025 12:27:42","22-03-2025 12:16:37","22-03-2=
025 13:58:49","Grid outage, Site went down because Gen failed to start due =
to 1/3 fuse faulty// He replaced fuse and started Gen manualy","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid out=
age, Site went down because Gen failed to start due to 1/3 fuse faulty// He=
 replaced fuse and started Gen manualy","ferot.nongni-djiogap@sagemcom.com"=
,"666","22-03-2025 12:27:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0004633196","A=
n-Marche-Melen","","22-03-2025 12:16:08","22-03-2025 11:47:02","23-03-2025 =
17:28:25","Grid outage, No space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No =
space to deploy MDG // Grid return","ferot.nongni-djiogap@sagemcom.com","17=
47","22-03-2025 12:16:08","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004633128","ETO=
UDI Entree du palais","","22-03-2025 11:59:17","22-03-2025 11:54:04","22-03=
-2025 12:01:09","Grid outage, Site went down before Gen start due to poor b=
ackup // Gen start automatically","Fabrice Pouakam","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen start automatically","fero=
t.nongni-djiogap@sagemcom.com","314","22-03-2025 11:59:17","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0004632937","MVA=
N SACEL","","22-03-2025 11:25:24","22-03-2025 11:17:18","22-03-2025 12:24:3=
9","Site went down because 01/06 rectifiers went faulty// He removed rectif=
ier faulty(site on 05)","MINKA NICOLAS","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down because 01/06 rectifiers went faul=
ty// He removed rectifier faulty(site on 05)","ferot.nongni-djiogap@sagemco=
m.com","601","22-03-2025 11:25:24","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004632555","Com=
plex Beac II","","22-03-2025 10:16:09","22-03-2025 09:53:01","22-03-2025 11=
:09:23","Grid outage site went down because Gen failed to start due to Gen =
card faulty // Gen Manually Started","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage site went down becaus=
e Gen failed to start due to Gen card faulty // Gen Manually Started","fero=
t.nongni-djiogap@sagemcom.com","1389","22-03-2025 10:16:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_159","NOCINC0004632449","Complexe=
-BEAC","","22-03-2025 10:00:27","22-03-2025 09:53:30","22-03-2025 11:23:39"=
,"Cascaded Incident from TTO4711204","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down becau=
se Gen failed to start due to charging alternator what didn't feeds site// =
He regularised it and started Gen manualy","system","295834","22-03-2025 10=
:00:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004632445","E=
kie-Elegance","IHS_YND_159","22-03-2025 09:59:35","22-03-2025 09:53:30","22=
-03-2025 11:23:39","Grid outage, Site went down because Gen failed to start=
 due to charging alternator what didn't feeds site// He regularised it and =
started Gen manualy","Albran Byorel","Equipment Repair","Passive","ACDG Gen=
","ACDG - Charging Alternator","Grid outage, Site went down because Gen fai=
led to start due to charging alternator what didn't feeds site// He regular=
ised it and started Gen manualy","ferot.nongni-djiogap@sagemcom.com","366",=
"22-03-2025 09:59:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004632402","Nkolfon =
Cimencam","","22-03-2025 09:51:56","22-03-2025 09:37:17","22-03-2025 11:40:=
42","Cascaded Incident from TTO4711090","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen failed due to gen overload(17KVA, 190A) //He reduiced the load, =
site on gen","system","304082","22-03-2025 09:51:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0004632400","Ahala","=
","22-03-2025 09:51:55","22-03-2025 09:37:17","22-03-2025 11:40:42","Cascad=
ed Incident from TTO4711090","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
failed due to gen overload(17KVA, 190A) //He reduiced the load, site on gen=
","system","304081","22-03-2025 09:51:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004632401","Afanoya"=
,"","22-03-2025 09:51:55","22-03-2025 09:37:17","22-03-2025 11:40:42","Casc=
aded Incident from TTO4711090","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed due to gen overload(17KVA, 190A) //He reduiced the load, site on g=
en","system","304081","22-03-2025 09:51:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004632354","M=
eyo","IHS_YND_257, IHS_YND_313, IHS_YND_762","22-03-2025 09:43:21","22-03-2=
025 09:37:17","22-03-2025 12:22:05","Grid outage, site went down because ge=
n failed due to gen overload(17KVA, 190A) //He reduiced the load, site on g=
en","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overlo=
ad","Grid outage, site went down because gen failed due to gen overload(17K=
VA, 190A) //He reduiced the load, site on gen","ferot.nongni-djiogap@sagemc=
om.com","365","22-03-2025 09:43:21","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004632344","Jou=
vence Mbenda","","22-03-2025 09:41:10","22-03-2025 09:34:05","22-03-2025 12=
:42:53","Grid fluctuation, site went down because Gen failed to start due t=
o grid bad voltage No Rcp // Grid stabilized","Hyemafo Gildas","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion, site went down because Gen failed to start due to grid bad voltage No =
Rcp // Grid stabilized","ferot.nongni-djiogap@sagemcom.com","426","22-03-20=
25 09:41:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004632167","S=
hell-Nsimeyong","","22-03-2025 09:11:49","22-03-2025 09:08:42","22-03-2025 =
09:13:56","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed. Repetitive Issue","MINKA NICOL=
AS","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosi=
ah (674007438/699699694) from Huawei is informed. Repetitive Issue","ferot.=
nongni-djiogap@sagemcom.com","188","22-03-2025 09:11:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004632141","MEHANDAN=
","","22-03-2025 09:06:17","22-03-2025 08:49:52","22-03-2025 09:26:48","Cas=
caded Incident from TTO4710808","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n ran untill fuel shortage // refuelling done","system","278067","22-03-202=
5 09:06:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004632088","E=
koumdoum OCM","","22-03-2025 08:57:24","22-03-2025 08:49:52","22-03-2025 09=
:26:48","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, site went down because gen ran untill fuel sho=
rtage // refuelling done","ferot.nongni-djiogap@sagemcom.com","278068","22-=
03-2025 08:57:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004632070","Odza II =
OCM","","22-03-2025 08:54:55","22-03-2025 08:49:52","22-03-2025 09:26:48","=
Cascaded Incident from TTO4710808","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen ran untill fuel shortage // refuelling done","system","278067","22-03-=
2025 08:54:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0004632066","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","22-03-2025 08:53:41","22=
-03-2025 08:49:52","22-03-2025 09:26:48","Grid outage, site went down becau=
se gen ran untill fuel shortage // refuelling done","Albran Byorel","Fuel O=
utage","Passive","Diesel","Diesel Outage","Grid outage, site went down beca=
use gen ran untill fuel shortage // refuelling done","ferot.nongni-djiogap@=
sagemcom.com","230","22-03-2025 08:53:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004632003","ELOUMDEM=
 CARRIERE 2","","22-03-2025 08:44:34","22-03-2025 08:41:51","22-03-2025 12:=
24:10","Cascaded Incident from TTO4710723","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage;gen failed to sta=
rt due to Gen card disfunctionning//gen manually started","system","1300011=
","22-03-2025 08:44:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004632002","Eto koss=
 Yde","","22-03-2025 08:44:34","22-03-2025 08:41:51","22-03-2025 12:24:10",=
"Cascaded Incident from TTO4710723","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage;gen failed to start due =
to Gen card disfunctionning//gen manually started","system","1300011","22-0=
3-2025 08:44:34","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004631988","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","22-03-2025 08:42:58","22-03-2025 08:41=
:51","22-03-2025 12:24:10","grid outage;gen failed to start due to Gen card=
 malfunctioning//gen manually started","Fanda Brice","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","grid outage;gen failed to start d=
ue to Gen card malfunctioning//gen manually started","ferot.nongni-djiogap@=
sagemcom.com","69","22-03-2025 08:42:58","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004631979","Mon=
tee-Jouvence-II","","22-03-2025 08:41:05","22-03-2025 08:29:00","22-03-2025=
 09:33:15","Site went down due to PWC Overloaded (12K, 250A) // site stabil=
ized SS IHS Alphonse confirmed //He reduice Load  and manually started gen =
","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","Site went down due to PWC Overloaded (12K, 250A) // site st=
abilized SS IHS Alphonse confirmed //He reduice Load  and manually started =
gen ","ferot.nongni-djiogap@sagemcom.com","726","22-03-2025 08:41:05","Sage=
mcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004631966","Bar=
riere","","22-03-2025 08:38:36","22-03-2025 08:29:31","22-03-2025 10:23:42"=
,"Site went down because Gen overload(20kva,400 A) IHS SS Felix Zambe is in=
formed and confirmed // Grid return","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Site went down because Gen overload(2=
0kva,400 A) IHS SS Felix Zambe is informed and confirmed // Grid return","f=
erot.nongni-djiogap@sagemcom.com","546","22-03-2025 08:38:36","Sagemcom CMR=
"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004631961","ELO=
UMDEM CARRIERE","","22-03-2025 08:36:45","22-03-2025 08:28:40","22-03-2025 =
09:17:40","Grid outage,site went down because gen failed to start //grid re=
turn(investigation ongoing)","Fanda Brice","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage,site went down because gen fail=
ed to start //grid return(investigation ongoing)","ferot.nongni-djiogap@sag=
emcom.com","487","22-03-2025 08:36:45","Sagemcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004631901","Ntu=
i administration","","22-03-2025 08:19:30","22-03-2025 08:01:25","22-03-202=
5 11:35:58","Grid outage.gen ran until fuel shortage//Refueling done","Park=
er Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.ge=
n ran until fuel shortage//Refueling done","ferot.nongni-djiogap@sagemcom.c=
om","1086","22-03-2025 08:19:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004631899","Manguier=
","","22-03-2025 08:18:26","22-03-2025 07:37:58","22-03-2025 08:43:34","Cas=
caded Incident from TTO4710620","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen fails to start due to battery ge faulty // Gen start with battery backu=
p","system","1217271","22-03-2025 08:18:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004631872","O=
mnisport-Rail","","22-03-2025 08:13:08","22-03-2025 07:36:01","22-03-2025 0=
8:43:56","No power issue on site U=3D54.5 V , Site is on Grid The FME TX Ar=
mand Nguesta (699949553) From Huawei is informed.","Delor Telezing","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power issue on site U=3D54.5 V , Site is on Grid The FME TX Armand =
Nguesta (699949553) From Huawei is informed.","ferot.nongni-djiogap@sagemco=
m.com","2229","22-03-2025 08:13:08","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004631845","Nom=
ayos montee Meche","","22-03-2025 08:08:52","22-03-2025 08:03:46","22-03-20=
25 09:41:46","Grid outage, site went down because gen failed to start // Gr=
id return(investigation ongoing)","Fanda Brice","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because ge=
n failed to start // Grid return(investigation ongoing)","ferot.nongni-djio=
gap@sagemcom.com","307","22-03-2025 08:08:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004631837","K=
oweit City","","22-03-2025 08:05:42","22-03-2025 07:16:35","22-03-2025 09:1=
1:37","Grid outage, Site went down because Gen started and stopped with ""L=
ow fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, Site went down because Gen started and stopped with ""Low =
fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","fer=
ot.nongni-djiogap@sagemcom.com","2948","22-03-2025 08:05:42","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004631805","MAN=
GUIERS CHAPELLE","IHS_YND_209","22-03-2025 07:55:18","22-03-2025 07:37:58",=
"22-03-2025 08:44:19","Grid outage, site went down because gen fails to sta=
rt due to battery ge faulty // Gen start with battery backup","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Gr=
id outage, site went down because gen fails to start due to battery ge faul=
ty // Gen start with battery backup","ferot.nongni-djiogap@sagemcom.com","2=
404","22-03-2025 07:55:18","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004631802","Man=
guiers Dispensaire","","22-03-2025 07:53:47","22-03-2025 07:40:35","22-03-2=
025 09:06:01","Grid outage, site went down because gen failed to start due =
to grid contactor faulty // He bypassed grid contactor and gen manually sta=
rted","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-A=
MF Issue","Grid outage, site went down because gen failed to start due to g=
rid contactor faulty // He bypassed grid contactor and gen manually started=
","ferot.nongni-djiogap@sagemcom.com","793","22-03-2025 07:53:47","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004631796","Nko=
abang MTN","","22-03-2025 07:51:58","22-03-2025 07:43:49","22-03-2025 08:17=
:31","Grid outage, Site went down because Gen overload(20, 300A) SS IHS Alp=
honse DEFFO is informed// He reduiced load and started Gen manualy","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen overload(20, 300A) SS IHS Alphonse DEFF=
O is informed// He reduiced load and started Gen manualy","ferot.nongni-dji=
ogap@sagemcom.com","489","22-03-2025 07:51:58","Sagemcom CMR"
"Closed Complete","Warning","T1545","IHS_YND_237","NOCINC0004631698","Carre=
four Simbock","","22-03-2025 07:23:13","","","Eneo outage // eneo return","=
Hyemafo Gildas","Warning","Warning","POWER","Warning - Site on Battery","En=
eo outage // eneo return","ferot.nongni-djiogap@sagemcom.com","725","22-03-=
2025 07:23:13","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004631631","Nko=
g-Edzen","","22-03-2025 07:10:57","22-03-2025 07:07:52","23-03-2025 03:15:4=
5","No power issue on site, site on Gen  The Tx Fme Gregoire (654547479) fr=
om Huawei is informed. ","Parker Tchoup","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
, site on Gen  The Tx Fme Gregoire (654547479) from Huawei is informed. ","=
ferot.nongni-djiogap@sagemcom.com","186","22-03-2025 07:10:57","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004631562","C=
omplexe-BEAC","","22-03-2025 06:57:09","22-03-2025 06:54:00","22-03-2025 06=
:57:00","Grid Outage, site went down before gen start due to poor battery b=
ackup // Gen started automatically","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid Outage, site went=
 down before gen start due to poor battery backup // Gen started automatica=
lly","ferot.nongni-djiogap@sagemcom.com","190","22-03-2025 06:57:09","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0004631338","Mendong =
Maeture","","22-03-2025 05:45:04","22-03-2025 05:38:03","22-03-2025 07:13:1=
4","Cascaded Incident from TTO4710030","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause gen start and stopped with high temp alarm // he added water and manu=
ally start the gen","system","332758","22-03-2025 05:45:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004631333","M=
endong","IHS_YND_692, IHS_YND_569","22-03-2025 05:43:14","22-03-2025 05:38:=
03","22-03-2025 07:13:14","Grid outage, site went down because gen start an=
d stopped with high temp alarm // he added water and manually start the gen=
","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Eng=
ine Temp - Coolant Level Issue","Grid outage, site went down because gen st=
art and stopped with high temp alarm // he added water and manually start t=
he gen","danick.tchakouani@sagemcom.com","312","22-03-2025 05:43:14","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004631316","M=
EHANDAN","","22-03-2025 05:39:17","22-03-2025 02:08:06","22-03-2025 08:37:3=
1","Grid outage, site went down due to insufficiency of rectifiers, Pascali=
ne Ihs is informed // Added rectifiers ongoing","Albran Byorel","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Grid outage, site went do=
wn due to insufficiency of rectifiers, Pascaline Ihs is informed // Added r=
ectifiers ongoing","wilfried.kameni@sagemcom.com","12672","22-03-2025 05:39=
:17","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0004631118","Lob=
o 2","","22-03-2025 04:31:12","22-03-2025 04:19:03","22-03-2025 08:17:03","=
site went down because gen started and stopped with alarm low oil pressure/=
/he reset it and stared the gen manually","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","site went down=
 because gen started and stopped with alarm low oil pressure//he reset it a=
nd stared the gen manually","wilfried.kameni@sagemcom.com","730","22-03-202=
5 04:31:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004630939","Carrefou=
r Ayissi Ele","","22-03-2025 03:38:46","22-03-2025 03:18:05","22-03-2025 04=
:03:05","Cascaded Incident from TTO4709582","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n because because gen start and stopped due to gen card dysfunctionning // =
Reset of gen card done and gen started","system","269025","22-03-2025 03:38=
:46","Sagemcom CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004630935","Saa=
","IHS_YND_810","22-03-2025 03:37:19","22-03-2025 03:18:05","22-03-2025 04:=
03:05","Grid outage, site went down because because gen start and stopped d=
ue to gen card dysfunctionning // Reset of gen card done and gen started","=
Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, site went down because because gen start and stopped due t=
o gen card dysfunctionning // Reset of gen card done and gen started","wilf=
ried.kameni@sagemcom.com","1155","22-03-2025 03:37:19","Sagemcom CMR"
"Closed Complete","Site Down","T0107","IHS_YND_271","NOCINC0004630770","Yon=
a Hotel","","22-03-2025 02:03:22","22-03-2025 01:59:04","22-03-2025 04:53:1=
3","Access issue during the Night,Grid outage,gen stopped with alarm high t=
emp//he added water in radiator","TIENTCHEU NZETCHIEU GAEL","Access Denial"=
,"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Acc=
ess issue during the Night,Grid outage,gen stopped with alarm high temp//he=
 added water in radiator","wilfried.kameni@sagemcom.com","259","22-03-2025 =
02:03:22","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004630767","Fla=
menco","","22-03-2025 02:02:21","22-03-2025 01:27:10","22-03-2025 04:11:10"=
,"Access issue during the Night due to landlord,grid outage,gen failed to s=
tart due to card ge faulty//Grid return","Mboua Thierry","Access Denial","L=
ease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access=
 issue during the Night due to landlord,grid outage,gen failed to start due=
 to card ge faulty//Grid return","wilfried.kameni@sagemcom.com","2112","22-=
03-2025 02:02:21","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004630630","Ebo=
go","","22-03-2025 01:07:01","22-03-2025 00:17:44","22-03-2025 05:17:45","A=
ctive//No power issue on site, Site on Grid UBAIE=3D54V synphorien (6752952=
05) From huawei is informed","Siligap Boris","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue on site, Site on Grid UBAIE=3D54V synphorien (675295205) From huawei i=
s informed","wilfried.kameni@sagemcom.com","2958","22-03-2025 01:07:01","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004630381","Saa=
","","21-03-2025 23:53:18","21-03-2025 23:51:56","22-03-2025 01:23:54","Gri=
d outage, site went down because gen ran untill fuel shortage // Refueling =
done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Gri=
d outage, site went down because gen ran untill fuel shortage // Refueling =
done","wilfried.kameni@sagemcom.com","83","21-03-2025 23:53:18","Sagemcom C=
MR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004630308","Abo=
me","","21-03-2025 23:37:21","21-03-2025 23:27:01","22-03-2025 00:00:53","G=
rid fluctuation, Site went down because gen fails to start due to grid bad =
voltage,no rcp// He bypasse the Grid and site on Gen","MINKA NICOLAS","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid f=
luctuation, Site went down because gen fails to start due to grid bad volta=
ge,no rcp// He bypasse the Grid and site on Gen","wilfried.kameni@sagemcom.=
com","622","21-03-2025 23:37:21","Sagemcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004630172","Ntu=
i administration","","21-03-2025 23:28:41","21-03-2025 22:57:23","21-03-202=
5 23:37:23","Grid outage, site went down because gen ran untill fuel shorta=
ge // Refueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Die=
sel Outage","Grid outage, site went down because gen ran untill fuel shorta=
ge // Refueling done","wilfried.kameni@sagemcom.com","1879","21-03-2025 23:=
28:41","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004630163","Ole=
mbe MTN","","21-03-2025 23:26:27","21-03-2025 22:47:13","22-03-2025 01:27:0=
4","Site went down due to insufficiency of rectifiers , Bernard IHS is info=
rmed // Added rectifiers ongoing","Fabrice Pouakam","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Site went down due to insufficiency o=
f rectifiers , Bernard IHS is informed // Added rectifiers ongoing","wilfri=
ed.kameni@sagemcom.com","2355","21-03-2025 23:26:27","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004630150","SAA=
 Entrance","","21-03-2025 23:23:57","21-03-2025 22:06:28","22-03-2025 20:19=
:25","Grid outage, Site went down because Main Gen faulty// He replaced Mai=
n Gen ","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Gen=
erator Faulty","Grid outage, Site went down because Main Gen faulty// He re=
placed Main Gen ","wilfried.kameni@sagemcom.com","4651","21-03-2025 23:23:5=
7","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_187","NOCINC0004630131","NTEMASSI=
","","21-03-2025 23:19:59","21-03-2025 21:59:48","21-03-2025 21:59:49","Cas=
caded Incident from TTO4708682","Delor Telezing","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site U=3D53,2v site on=
 grid Synphorien of Huawei is informed","system","288151","21-03-2025 23:19=
:59","Sagemcom CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0004630128","Ngo=
usso MTN","IHS_YND_187","21-03-2025 23:19:07","21-03-2025 21:59:48","21-03-=
2025 21:59:49","No power issue on site U=3D53,2v site on grid Synphorien of=
 Huawei is informed","","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53,2v site o=
n grid Synphorien of Huawei is informed","wilfried.kameni@sagemcom.com","47=
60","21-03-2025 23:19:07","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004630123","Eto=
ug ebe biscuiterie","","21-03-2025 23:17:48","21-03-2025 21:56:36","21-03-2=
025 21:56:37","Active: No power issue, site is on Gen with Ubaie=3D53,2V, T=
X RM martial(690087047) from Huawei is informed","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active: No power issue, site is on Gen with Ubaie=3D53,2V, TX RM martial=
(690087047) from Huawei is informed","wilfried.kameni@sagemcom.com","4872",=
"21-03-2025 23:17:48","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004630106","Eko=
mbitie","","21-03-2025 23:14:26","21-03-2025 21:35:46","22-03-2025 01:58:56=
","grid very bad voltage ( lack of 01 phase), site went down because Gen st=
art and ran until fuel shortage// He make a bridge on a good phases , site =
on grid","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","grid very bad voltage ( lack of 01 phase), site w=
ent down because Gen start and ran until fuel shortage// He make a bridge o=
n a good phases , site on grid","wilfried.kameni@sagemcom.com","5921","21-0=
3-2025 23:14:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004630042","ODZA MIN=
KAN EDIBI ASSI","","21-03-2025 23:01:01","21-03-2025 21:31:43","21-03-2025 =
22:55:43","Cascaded Incident from TTO4708509","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage, site went d=
own before gen start due to all batteries backup faulty // Gen manually sta=
rted","system","289847","21-03-2025 23:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004630040","Mehanda =
1","","21-03-2025 23:01:00","21-03-2025 21:31:43","21-03-2025 22:55:43","Ca=
scaded Incident from TTO4708509","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down before ge=
n start due to all batteries backup faulty // Gen manually started","system=
","289847","21-03-2025 23:01:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004630041","Odza Min=
kan IHS","","21-03-2025 23:01:00","21-03-2025 21:31:43","21-03-2025 22:55:4=
3","Cascaded Incident from TTO4708509","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to all batteries backup faulty // Gen manually started","=
system","289848","21-03-2025 23:01:00","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004629975","Nko=
lnda","IHS_YND_746, IHS_YND_715, IHS_YND_749","21-03-2025 22:48:10","21-03-=
2025 21:31:43","21-03-2025 22:55:43","Grid outage, site went down before ge=
n start due to all batteries backup faulty // Gen manually started","Albran=
 Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","Grid outage, site went down before gen start due to all batteries=
 backup faulty // Gen manually started","danick.tchakouani@sagemcom.com","4=
588","21-03-2025 22:48:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004629705","O=
lembe-Terminus","","21-03-2025 21:50:04","21-03-2025 20:54:40","21-03-2025 =
21:00:42","Active: no power issue, site is on grid with Ubaie=3D53V, Sympho=
rien(650257151) from Huawei is informed,Notice that we have disjunction Cb(=
2*100A)  at BTS OCM","Fabrice Pouakam","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, =
site is on grid with Ubaie=3D53V, Symphorien(650257151) from Huawei is info=
rmed,Notice that we have disjunction Cb(2*100A)  at BTS OCM","mariam.tchona=
ng@sagemcom.com","3325","21-03-2025 21:50:04","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004629658","NTU=
I TOWN","","21-03-2025 21:40:34","21-03-2025 21:00:21","21-03-2025 23:01:21=
","Grid outage, site went down because gen ran untill fuel shortage // Refu=
eling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid outage, site went down because gen ran untill fuel shortage // Refu=
eling done","el-dalile@sagemcom.com","2414","21-03-2025 21:40:34","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004629407","H=
-General-Yde","","21-03-2025 20:59:13","21-03-2025 20:48:01","21-03-2025 22=
:26:01","Grid outage, site went down because gen ran untill fuel shortage /=
/ Refueling Done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage, site went down because gen ran untill fuel shortage /=
/ Refueling Done","mariam.tchonang@sagemcom.com","672","21-03-2025 20:59:13=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004629383","N=
goulmekong-Nord","","21-03-2025 20:56:18","21-03-2025 20:13:51","21-03-2025=
 21:13:51","Grid outage, site went down because gen start and stopped with =
over voltage alarm // He reset it and manually start the gen","Siligap Bori=
s","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, site went down because gen start and stopped with over voltage alarm /=
/ He reset it and manually start the gen","mariam.tchonang@sagemcom.com","2=
548","21-03-2025 20:56:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004629260","O=
dza II OCM","","21-03-2025 20:39:48","21-03-2025 20:23:39","21-03-2025 20:2=
3:40","Active// No power issue on site,site on Grid,Ubaie=3D54,7V,Lionnel//=
655184876 from Huawei is informed","Albran Byorel","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No =
power issue on site,site on Grid,Ubaie=3D54,7V,Lionnel//655184876 from Huaw=
ei is informed","el-dalile@sagemcom.com","970","21-03-2025 20:39:48","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004629224","E=
MANA BILICK CITY","","21-03-2025 20:36:45","21-03-2025 20:24:19","22-03-202=
5 04:00:45","No power issue site on grid with U=3D53,4V. The Tx FME Symphor=
ien (691316854) from Huawei is informed.","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue site on grid with U=3D53,4V. The Tx FME Symphorien (691316854) =
from Huawei is informed","mariam.tchonang@sagemcom.com","748","21-03-2025 2=
0:36:45","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0004629134","San=
ta Barbara Gottam","","21-03-2025 20:25:31","21-03-2025 20:24:19","21-03-20=
25 20:38:59","Grid outage, Site went down before Gen start due to poor back=
up // Gen started automatically","Delor Telezing","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen started automatically","el-d=
alile@sagemcom.com","73","21-03-2025 20:25:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004629128","N=
kolo II New","","21-03-2025 20:24:32","21-03-2025 20:13:02","21-03-2025 20:=
58:05","Grid outage, Site went down because Gen failed to start due to PWC =
dysfunctionning// He reset PWC, Site on Grid","Mba Lazare Herve","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, =
Site went down because Gen failed to start due to PWC dysfunctionning// He =
reset PWC, Site on Grid","mariam.tchonang@sagemcom.com","691","21-03-2025 2=
0:24:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004629068","A=
kak-Nkozoa-MTN-IHS","","21-03-2025 20:11:16","21-03-2025 19:49:41","22-03-2=
025 13:07:25","Grid outage.gen ran until fuel shortage//Refueling done","Fa=
brice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outag=
e.gen ran until fuel shortage//Refueling done","mariam.tchonang@sagemcom.co=
m","1297","21-03-2025 20:11:16","Sagemcom CMR"
"Closed Complete","Site Down","T1323","IHS_YND_288","NOCINC0004629045","Mey=
ong Plateau","","21-03-2025 20:07:59","21-03-2025 19:30:29","21-03-2025 21:=
00:31","Grid outage, site went down because gen failed to start with alarm =
Over voltaged // He reset gen card and gen manually started","TIENTCHEU NZE=
TCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage, site went down because gen failed to start with alarm Over v=
oltaged // He reset gen card and gen manually started","mariam.tchonang@sag=
emcom.com","2251","21-03-2025 20:07:59","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004628947","Jou=
vence Mbenda","","21-03-2025 19:49:21","21-03-2025 18:17:06","21-03-2025 19=
:43:36","Grid outage.gen start and stopped due to alarm""high temp""//We ad=
ded water and gen manually started","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age.gen start and stopped due to alarm""high temp""//We added water and gen=
 manually started","olivier.kwedi@ihstowers.com","5536","21-03-2025 19:49:2=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004628877","N=
kolbong","","21-03-2025 19:35:39","21-03-2025 19:29:06","21-03-2025 21:30:3=
4","Grid outage, site went down because gen failed to start due to gen card=
 malfunction // Gen manually started","Delor Telezing","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down bec=
ause gen failed to start due to gen card malfunction // Gen manually starte=
d","el-dalile@sagemcom.com","394","21-03-2025 19:35:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004628864","M=
ambine","","21-03-2025 19:32:32","21-03-2025 18:56:18","21-03-2025 19:34:05=
","Grid outage site went down because Gen failed to start due to Hybrid sys=
tem malfunction // He reset the hybrid system and Gen manually started","Fa=
nda Brice","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid outa=
ge site went down because Gen failed to start due to Hybrid system malfunct=
ion // He reset the hybrid system and Gen manually started","ludivine.ngama=
leu@ihstowers.com","2176","21-03-2025 19:32:32","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004628862","Nko=
lbisson usines des eaux 2","","21-03-2025 19:32:26","21-03-2025 19:14:49","=
21-03-2025 20:26:14","Grid Outage Site went down because Gen Overload (12.5=
KVA, 275A) SS IHS Felix Pascaline confirmed// He reduiced The load and Manu=
ally Started the Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid Outage Site went down because Gen Ove=
rload (12.5KVA, 275A) SS IHS Felix Pascaline confirmed// He reduiced The lo=
ad and Manually Started the Gen","el-dalile@sagemcom.com","1058","21-03-202=
5 19:32:26","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004628568","Men=
dong3","","21-03-2025 18:38:10","21-03-2025 18:35:00","21-03-2025 19:58:38"=
,"Grid outage, no space to deploy// grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage, no space to deplo=
y// grid return","el-dalile@sagemcom.com","190","21-03-2025 18:38:10","Sage=
mcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004628435","Nko=
zoa","","21-03-2025 18:27:53","21-03-2025 18:19:35","21-03-2025 18:50:54","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and site on GEN","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to gen overload (20kva, 340A) SS HIS Felix ba=
teu is informed and confirmed// He reduced the load and site on GEN","el-da=
lile@sagemcom.com","500","21-03-2025 18:27:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004628296","N=
kolondom","","21-03-2025 18:07:41","21-03-2025 18:05:20","21-03-2025 19:07:=
04","Grid fluctuation, Site went down because gen fails to start due to gri=
d bad voltage,no rcp// He bypassed the Grid and site on Gen","Fabrice Pouak=
am","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, Site went down because gen fails to start due to grid =
bad voltage,no rcp// He bypassed the Grid and site on Gen","mariam.tchonang=
@sagemcom.com","142","21-03-2025 18:07:41","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004628286","MBA=
LNGONG LYCEE","","21-03-2025 18:05:56","21-03-2025 17:56:20","21-03-2025 23=
:16:20","Grid Outage Site went down due to Gen overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed // Grid return","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went d=
own due to Gen overload(9kva, 130A) SS IHS Felix Zambe is informed and conf=
irmed // Grid return","el-dalile@sagemcom.com","578","21-03-2025 18:05:56",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0004628148","S=
ous Prefecture","","21-03-2025 17:48:27","21-03-2025 17:15:16","21-03-2025 =
17:30:41","ACTIVE//No power issue site on Grid Ubaie =3D55.2V, The tx Huawe=
i Fulbert (654266068) is informed","Fanda Brice","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No pow=
er issue site on Grid Ubaie =3D55.2V, The tx Huawei Fulbert (654266068) is =
informed","ludivine.ngamaleu@ihstowers.com","1992","21-03-2025 17:48:27","S=
agemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004628144","Men=
dong vallee","","21-03-2025 17:47:53","21-03-2025 17:10:44","22-03-2025 07:=
13:14","Grid outage site went down because Gen over load (20KVA; 300A) // G=
rid return IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site we=
nt down because Gen over load (20KVA; 300A) // Grid return IHS F=E9lix Zamb=
=E9 is informed and confirmed","el-dalile@sagemcom.com","2230","21-03-2025 =
17:47:53","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004628127","Jea=
n Vespa","","21-03-2025 17:44:30","21-03-2025 17:08:23","21-03-2025 17:49:1=
6","Grid outage, site went down because gen failed to start due to GEN cont=
actor faulty // Grid return","Mboua Thierry","Equipment Repair","Passive","=
ACDG Gen","ACDG - Load Contactor","Grid outage, site went down because gen =
failed to start due to GEN contactor faulty // Grid return","olivier.kwedi@=
ihstowers.com","2168","21-03-2025 17:44:30","Sagemcom CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0004628104","Dag=
obert","","21-03-2025 17:42:19","21-03-2025 16:56:06","21-03-2025 19:51:21"=
,"Grid outage, site went down because gen stopped with under voltage alarm =
// Reset done and gen started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down =
because gen stopped with under voltage alarm // Reset done and gen started"=
,"olivier.kwedi@ihstowers.com","3710","21-03-2025 17:42:19","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004628080","Mes=
sa Carriere","","21-03-2025 17:38:51","21-03-2025 16:52:24","21-03-2025 17:=
42:24","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty //Grid outage","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because Gen =
failed to started due to Gen card faullty //Grid outage","olivier.kwedi@ihs=
towers.com","2788","21-03-2025 17:38:51","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004628027","NYO=
M FACE MAETUR","","21-03-2025 17:24:40","21-03-2025 16:36:25","22-03-2025 1=
5:34:55","Grid outage, Site went down because Gen failed to start due to Fu=
el filter faulty// He replaced fuel filter, added oil and started Gen manua=
lly","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel=
 Filter","Grid outage, Site went down because Gen failed to start due to Fu=
el filter faulty// He replaced fuel filter, added oil and started Gen manua=
lly","el-dalile@sagemcom.com","2896","21-03-2025 17:24:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004628022","ETOUDI C=
HAPELLE","","21-03-2025 17:23:47","21-03-2025 16:50:12","21-03-2025 17:30:1=
6","Cascaded Incident from TTO4706165","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause gen failed to start with alarm undervoltage // He reset gen card and =
gen manually started","system","278033","21-03-2025 17:23:47","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0004628023","Etoudi 2=
","","21-03-2025 17:23:47","21-03-2025 16:50:12","21-03-2025 17:30:16","Cas=
caded Incident from TTO4706165","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen failed to start with alarm undervoltage // He reset gen card and gen ma=
nually started","system","278034","21-03-2025 17:23:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004628021","Abattoir=
","","21-03-2025 17:23:47","21-03-2025 16:50:12","21-03-2025 17:30:16","Cas=
caded Incident from TTO4706165","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen failed to start with alarm undervoltage // He reset gen card and gen ma=
nually started","system","278033","21-03-2025 17:23:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_296","NOCINC0004627998","Nkolfoul=
ou","","21-03-2025 17:18:18","21-03-2025 16:51:58","21-03-2025 17:51:56","C=
ascaded Incident from TTO4706145","Siligap Boris","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid OUtage Site went down because G=
en Failed to Start due to relay Time Faulty on Site//He bypass it and Manua=
lly Started the Gen ","system","1580","21-03-2025 17:18:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0004627999","Nkolfoul=
ou Tsinga Village","","21-03-2025 17:18:18","21-03-2025 16:51:58","21-03-20=
25 17:51:56","Cascaded Incident from TTO4706145","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid OUtage Site went=
 down because Gen Failed to Start due to relay Time Faulty on Site//He bypa=
ss it and Manually Started the Gen ","system","1580","21-03-2025 17:18:18",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_758","NOCINC0004627997","Nkolfoul=
ou CSD MTN","","21-03-2025 17:18:17","21-03-2025 16:51:58","21-03-2025 17:5=
1:56","Cascaded Incident from TTO4706145","Siligap Boris","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid OUtage Site went down b=
ecause Gen Failed to Start due to relay Time Faulty on Site//He bypass it a=
nd Manually Started the Gen ","system","1579","21-03-2025 17:18:17","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004627996","SOA VILL=
AGE","","21-03-2025 17:18:17","21-03-2025 16:51:58","21-03-2025 17:51:56","=
Cascaded Incident from TTO4706145","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid OUtage Site went down because =
Gen Failed to Start due to relay Time Faulty on Site//He bypass it and Manu=
ally Started the Gen ","system","1579","21-03-2025 17:18:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004627995","SOA UNIV=
ERSITY STADIUM","","21-03-2025 17:18:17","21-03-2025 16:51:58","21-03-2025 =
17:51:56","Cascaded Incident from TTO4706145","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid OUtage Site went do=
wn because Gen Failed to Start due to relay Time Faulty on Site//He bypass =
it and Manually Started the Gen ","system","1579","21-03-2025 17:18:17","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004627994","TSINGA V=
ILLAGE 2","","21-03-2025 17:18:16","21-03-2025 16:51:58","21-03-2025 17:51:=
56","Cascaded Incident from TTO4706145","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid OUtage Site went down be=
cause Gen Failed to Start due to relay Time Faulty on Site//He bypass it an=
d Manually Started the Gen ","system","1578","21-03-2025 17:18:16","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004627993","Mvog-Eba=
nda","","21-03-2025 17:18:16","21-03-2025 16:51:58","21-03-2025 17:51:56","=
Cascaded Incident from TTO4706145","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid OUtage Site went down because =
Gen Failed to Start due to relay Time Faulty on Site//He bypass it and Manu=
ally Started the Gen ","system","1578","21-03-2025 17:18:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0004627992","FOUGEROL=
E","","21-03-2025 17:18:16","21-03-2025 16:51:58","21-03-2025 17:51:56","Ca=
scaded Incident from TTO4706145","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid OUtage Site went down because Ge=
n Failed to Start due to relay Time Faulty on Site//He bypass it and Manual=
ly Started the Gen ","system","1578","21-03-2025 17:18:16","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004627917","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","21-03-2025 17:08:30","21-03-2=
025 16:50:12","21-03-2025 17:30:16","Grid outage, site went down because ge=
n failed to start with alarm undervoltage // He reset gen card and gen manu=
ally started","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","AC=
DG - Control Panel","Grid outage, site went down because gen failed to star=
t with alarm undervoltage // He reset gen card and gen manually started","m=
ariam.tchonang@sagemcom.com","1099","21-03-2025 17:08:30","Sagemcom CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0004627903","Nko=
lfoulou 2","IHS_YND_561, IHS_YND_269, IHS_YND_719, IHS_YND_720, IHS_YND_323=
, IHS_YND_758, IHS_YND_296, IHS_YND_759","21-03-2025 17:04:49","21-03-2025 =
16:51:58","21-03-2025 17:51:56","Grid OUtage Site went down because Gen Fai=
led to Start due to relay Time Faulty on Site//He bypass it and Manually St=
arted the Gen ","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Relay Faulty","Grid OUtage Site went down because Gen Failed to Start =
due to relay Time Faulty on Site//He bypass it and Manually Started the Gen=
 ","cedric.tiani@sagemcom.com","772","21-03-2025 17:04:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004627832","M=
essassi 2","","21-03-2025 16:56:18","21-03-2025 16:47:06","21-03-2025 17:28=
:42","Grid outage, site went down because gen ran untill fuel shortage // R=
efueling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down because gen ran untill fuel shortage //=
 Refueling done","mariam.tchonang@sagemcom.com","553","21-03-2025 16:56:18"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0004627633","Mendong =
Maeture","","21-03-2025 16:22:16","21-03-2025 15:44:24","21-03-2025 16:22:0=
9","Cascaded Incident from TTO4705614","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage Site went down bec=
ause gen start and stopped with high temp alarm // He added water and manua=
lly","system","267587","21-03-2025 16:22:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0004627632","Mendong =
vallee","","21-03-2025 16:22:16","21-03-2025 15:44:24","21-03-2025 16:22:09=
","Cascaded Incident from TTO4705614","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage Site went down because=
 gen start and stopped with high temp alarm // He added water and manually"=
,"system","267588","21-03-2025 16:22:16","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004627453","OBA=
M NGOLA OCM","","21-03-2025 15:49:07","21-03-2025 15:14:46","21-03-2025 16:=
21:23","Grid outage site went down because Gen failed to start due to Gen b=
attery discharged causing by charging alternator faulty // Gen manually sta=
rted with external battery","MINKA NICOLAS","Equipment Repair","Passive","A=
CDG Gen","ACDG - Charging Alternator","Grid outage site went down because G=
en failed to start due to Gen battery discharged causing by charging altern=
ator faulty // Gen manually started with external battery","el-dalile@sagem=
com.com","2062","21-03-2025 15:49:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004627447","M=
endong","IHS_YND_692, IHS_YND_569","21-03-2025 15:48:39","21-03-2025 15:44:=
24","21-03-2025 16:22:09","Grid Outage Site went down because gen start and=
 stopped with high temp alarm // He added water and manually","Hyemafo Gild=
as","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid Outage Site went down because gen start and stopped =
with high temp alarm // He added water and manually","mariam.tchonang@sagem=
com.com","256","21-03-2025 15:48:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004627394","O=
bobogo","","21-03-2025 15:38:41","21-03-2025 15:07:15","21-03-2025 15:41:46=
","Grid outage, Site went down before Gen start due to poor backup // Gen s=
tarted automatically","MINKA NICOLAS","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Gen started automatically","mariam.tchonang@=
sagemcom.com","1887","21-03-2025 15:38:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0004627332","T=
alla Monatele","","21-03-2025 15:31:40","21-03-2025 15:20:35","21-03-2025 1=
6:54:35","Grid outage, site went down because gen ran untill fuel shortage =
// Refueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage, site went down because gen ran untill fuel shortage =
// Refueling done","ludivine.ngamaleu@ihstowers.com","666","21-03-2025 15:3=
1:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0004627260","M=
ontee-Jouvence","","21-03-2025 15:15:47","21-03-2025 14:56:34","21-03-2025 =
15:32:46","Grid outage, site went down because gen ran untill fuel shortage=
 // Refueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Dies=
el Outage","Grid outage, site went down because gen ran untill fuel shortag=
e // Refueling done","el-dalile@sagemcom.com","1154","21-03-2025 15:15:47",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004627226","M=
essa-Carriere OCM","","21-03-2025 15:08:14","21-03-2025 14:37:55","21-03-20=
25 21:25:24","No Power issue on site Ubaie=3D55.2V site  on Gen The TX Fme =
Mohamadou 691144435 of huawei is informed. ","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No Power issue =
on site Ubaie=3D55.2V site  on Gen
The TX Fme Mohamadou 691144435 of huawei is informed.=20

","el-dalile@sagemcom.com","1820","21-03-2025 15:08:14","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004627110","Com=
plex Beac II","","21-03-2025 14:48:55","21-03-2025 14:00:36","21-03-2025 15=
:34:36","Grid outage, site went down because the generator card cable is fa=
ulty // He manually start the GEN","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because=
 the generator card cable is faulty //he manually start the GEN","el-dalile=
@sagemcom.com","2900","21-03-2025 14:48:55","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004627076","Men=
dong NB","","21-03-2025 14:44:57","21-03-2025 14:38:43","21-03-2025 16:00:5=
4","Grid outage, no space to deploy a MDG//Grid return ","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy a MDG//Grid return ","cedric.tiani@sagemcom.com","375","21-03-202=
5 14:44:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004626877","K=
oweit City","","21-03-2025 14:10:37","21-03-2025 13:59:25","21-03-2025 15:2=
5:34","Grid outage, site went down because gen start and stopped with alarm=
 low fuel // He reset gen card and gen manually started","Albran Byorel","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, =
site went down because gen start and stopped with alarm low fuel // He rese=
t gen card and gen manually started","ferot.nongni-djiogap@sagemcom.com","6=
73","21-03-2025 14:10:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004626827","Saa","",=
"21-03-2025 13:58:52","21-03-2025 13:16:50","21-03-2025 13:41:11","Cascaded=
 Incident from TTO4704865","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage,Site went down because gen ran =
untill fuel shortage//Refueling done","system","269161","21-03-2025 13:58:5=
2","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004626826","SAA Entr=
ance","","21-03-2025 13:58:52","21-03-2025 13:16:50","21-03-2025 13:41:11",=
"Cascaded Incident from TTO4704865","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,Site went down because=
 gen ran untill fuel shortage//Refueling done","system","269161","21-03-202=
5 13:58:52","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004626822","SAA=
 2","IHS_YND_542, IHS_YND_405","21-03-2025 13:57:56","21-03-2025 13:16:50",=
"21-03-2025 13:54:30","Grid outage,Site went down because gen ran untill fu=
el shortage//Refueling done","Parker Tchoup","Fuel Outage","Passive","Diese=
l","Diesel Outage","Grid outage,Site went down because gen ran untill fuel =
shortage//Refueling done","ferot.nongni-djiogap@sagemcom.com","2467","21-03=
-2025 13:57:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004626772","M=
EHANDAN","","21-03-2025 13:48:43","21-03-2025 13:47:36","21-03-2025 14:55:0=
8","Site went down due to insufficience of rectifiers on site SS IHS Pascal=
ine is informed // He reset the rectifier","Albran Byorel","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Site went down due to insuffic=
ience of rectifiers on site SS IHS Pascaline is informed // He reset the re=
ctifier","ferot.nongni-djiogap@sagemcom.com","69","21-03-2025 13:48:43","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0004626760","EKI=
E","","21-03-2025 13:48:02","21-03-2025 13:15:52","21-03-2025 17:28:45","Si=
te went down because gen fails to start due to grid bad voltage // He bypas=
s grid and manually start the gen","Albran Byorel","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Site went down because ge=
n fails to start due to grid bad voltage // He bypass grid and manually sta=
rt the gen","ferot.nongni-djiogap@sagemcom.com","1930","21-03-2025 13:48:02=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004626628","C=
omplexe-BEAC","","21-03-2025 13:31:59","21-03-2025 13:29:45","21-03-2025 13=
:29:46","Active//no power issue on site U=3D54,6v site on grid Lionnel stee=
ve 655184876 of Huawei is informed","Albran Byorel","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//no =
power issue on site U=3D54,6v site on grid Lionnel steeve 655184876 of Huaw=
ei is informed","ferot.nongni-djiogap@sagemcom.com","135","21-03-2025 13:31=
:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004626453","E=
koumdoum","","21-03-2025 12:47:38","21-03-2025 12:29:31","21-03-2025 13:05:=
31","Grid fluctuation, Site went down because gen fails to start due to gri=
d bad voltage,no rcp// He bypassed the Grid and site on Gen","Albran Byorel=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation, Site went down because gen fails to start due to grid ba=
d voltage,no rcp// He bypassed the Grid and site on Gen","ferot.nongni-djio=
gap@sagemcom.com","1088","21-03-2025 12:47:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004626432","F=
ouda-New","","21-03-2025 12:39:27","21-03-2025 12:36:20","21-03-2025 15:37:=
20","Grid outage, site went down due to 01/04 rectifiers faulty // He remov=
ed 01 rectifiers, site on grid in 03 rectifiers","Delor Telezing","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module","Grid outage, site went =
down due to 01/04 rectifiers faulty // He removed 01 rectifiers, site on gr=
id in 03 rectifiers","ferot.nongni-djiogap@sagemcom.com","188","21-03-2025 =
12:39:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004626035","A=
wae Escalier","","21-03-2025 11:24:52","21-03-2025 11:17:38","21-03-2025 12=
:01:49","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup // Gen started automatically","ferot.nong=
ni-djiogap@sagemcom.com","435","21-03-2025 11:24:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004626019","A=
wae Ewonkan","","21-03-2025 11:22:17","21-03-2025 11:14:12","21-03-2025 11:=
42:32","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // =
He reduced the load","ferot.nongni-djiogap@sagemcom.com","486","21-03-2025 =
11:22:17","Sagemcom CMR"
"Closed Complete","Warning","T0462","IHS_YND_123","NOCINC0004626018","Nkomo=
 II","","21-03-2025 11:22:10","","","Grid outage, site alarming because gen=
 failed to start // Grid return (investigation ongoing)","Albran Byorel","W=
arning","Warning","POWER","Warning - Site on Battery","Grid outage, site al=
arming because gen failed to start // Grid return (investigation ongoing)",=
"mariam.tchonang@sagemcom.com","1507","21-03-2025 11:22:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004625997","S=
tade-Abega","","21-03-2025 11:20:55","21-03-2025 11:10:38","21-03-2025 11:4=
0:20","Grid outage, site went down because gen failed to start due to Pwc Z=
TE dysfunction // Grid return","Mba Lazare Herve","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Grid outage, site went down =
because gen failed to start due to Pwc ZTE dysfunction // Grid return","fer=
ot.nongni-djiogap@sagemcom.com","618","21-03-2025 11:20:55","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004625860","AWA=
E OCM","","21-03-2025 11:14:15","21-03-2025 11:06:55","21-03-2025 11:16:11"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen st=
arted automatically","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Gen started automatically","ferot.nongni-d=
jiogap@sagemcom.com","441","21-03-2025 11:14:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004625826","M=
ontee-Des-Soeurs","","21-03-2025 11:12:58","21-03-2025 11:04:52","21-03-202=
5 11:18:28","Grid outage, Site went down before Gen start due to poor backu=
p // Gen Manually started","Hyemafo Gildas","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup // Gen Manually started","ferot.nongni-dj=
iogap@sagemcom.com","488","21-03-2025 11:12:58","Sagemcom CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004625614","Bas=
tos-BAT","","21-03-2025 10:35:38","21-03-2025 10:13:25","21-03-2025 10:13:2=
6","Active// No power issue, site is on grid with Ubaie=3D54,9 V The Tx Fme=
, Eloundou(652586578) from Huawei is informed","Mboua Thierry","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power issue, site is on grid with Ubaie=3D54,9 V The Tx Fme, El=
oundou(652586578) from Huawei is informed","ferot.nongni-djiogap@sagemcom.c=
om","1333","21-03-2025 10:35:38","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004625428","Mon=
tee-Jouvence-II","","21-03-2025 10:13:22","21-03-2025 09:10:15","21-03-2025=
 10:53:41","Grid outage, Site went down because Gen overload (15kva, 250A) =
SS IHS Felix Zambe is informed // GRid power return","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen overload (15kva, 250A) SS IHS Felix Zambe is informed //=
 GRid power return","ferot.nongni-djiogap@sagemcom.com","3789","21-03-2025 =
10:13:22","Sagemcom CMR"
"Closed Complete","Warning","T0058","IHS_YND_293","NOCINC0004625276","Nkoab=
ang MTN","","21-03-2025 09:39:00","","","Grid outage, site alarming because=
 gen failed to start due to gen overload // He reduced the load and gen man=
ually started","Mba Lazare Herve","Warning","Warning","POWER","Warning - Si=
te on Battery","Grid outage site alarming because gen failed to start due t=
o gen overload // He reduced the load and gen manually started","mariam.tch=
onang@sagemcom.com","548","21-03-2025 09:39:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004624857","B=
iteng-Maetur","","21-03-2025 08:21:28","21-03-2025 08:07:09","21-03-2025 08=
:10:37","No power issue site on gen with U=3D54v Flubert(654266068) from Hu=
awei is informed,Notice that we have disjunction at BTS OCM","Mba Lazare He=
rve","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue site on gen with U=3D54v Flubert(654266068)=
 from Huawei is informed,Notice that we have disjunction at BTS OCM","yves.=
djomo@sagemcom.com","860","21-03-2025 08:21:28","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004624823","Ole=
mbe MTN","","21-03-2025 08:12:57","21-03-2025 08:07:49","21-03-2025 18:32:3=
1","Grid outage, site went down because gen failed to start due to grid con=
tactor faulty // He bypassed ATS and Gen manually started","Fabrice Pouakam=
","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage=
, site went down because gen failed to start due to grid contactor faulty /=
/ He bypassed ATS and Gen manually started","ferot.nongni-djiogap@sagemcom.=
com","309","21-03-2025 08:12:57","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004624704","Nko=
ulou Carriere carrefourt","","21-03-2025 07:49:08","21-03-2025 07:47:56","2=
1-03-2025 09:14:19","Grid outage, site went down because due to Gen overloa=
d(20kva,310 A) IHS SS Alphonse is informed// Grid return","Mba Lazare Herve=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, s=
ite went down because due to Gen overload(20kva,310 A) IHS SS Alphonse is i=
nformed// Grid return","yves.djomo@sagemcom.com","73","21-03-2025 07:49:08"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004624659","S=
hell-Nsimeyong","","21-03-2025 07:37:10","21-03-2025 07:33:54","21-03-2025 =
07:35:23","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed. Repetitive Issue","MINKA NICOL=
AS","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosi=
ah (674007438/699699694) from Huawei is informed. Repetitive Issue","yves.d=
jomo@sagemcom.com","198","21-03-2025 07:37:10","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004624472","Nko=
abang2","","21-03-2025 06:56:17","21-03-2025 06:44:03","21-03-2025 06:50:50=
","Active//No power issue site on Battery with U=3D49,2 V Lionel Adjep(6551=
84876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue site on Battery with U=3D49,2 V Lionel Adjep(655184876) from Hua=
wei is informed","ferot.nongni-djiogap@sagemcom.com","736","21-03-2025 06:5=
6:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004624406","Eseka To=
wn","","21-03-2025 06:45:45","21-03-2025 06:19:00","21-03-2025 07:02:33","C=
ascaded Incident from TTO4701903","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // Refueling done","system","272857","21-03-=
2025 06:45:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004624407","NKONGKAR=
AK","","21-03-2025 06:45:45","21-03-2025 06:19:00","21-03-2025 07:02:33","C=
ascaded Incident from TTO4701903","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site went do=
wn because gen ran untill fuel shortage // Refueling done","system","272870=
","21-03-2025 06:45:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0004624403","Eseka MT=
N","","21-03-2025 06:45:44","21-03-2025 06:19:00","21-03-2025 07:02:33","Ca=
scaded Incident from TTO4701903","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen ran untill fuel shortage // Refueling done","system","272855","21-03-2=
025 06:45:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004624401","Akono","=
","21-03-2025 06:45:44","21-03-2025 06:19:00","21-03-2025 07:02:33","Cascad=
ed Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen ran=
 untill fuel shortage // Refueling done","system","272864","21-03-2025 06:4=
5:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004624402","Nomayos-=
IHS","","21-03-2025 06:45:44","21-03-2025 06:19:00","21-03-2025 07:02:33","=
Cascaded Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down because g=
en ran untill fuel shortage // Refueling done","system","272859","21-03-202=
5 06:45:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0004624396","Ekekam",=
"","21-03-2025 06:45:43","21-03-2025 06:19:00","21-03-2025 07:02:33","Casca=
ded Incident from TTO4701903","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen ran untill fuel shortage // Refueling done","system","272856","2=
1-03-2025 06:45:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004624395","Nkolfon =
Cimencam","","21-03-2025 06:45:43","21-03-2025 06:19:00","21-03-2025 07:02:=
33","Cascaded Incident from TTO4701903","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen ran untill fuel shortage // Refueling done","system","272860","2=
1-03-2025 06:45:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004624399","Mom","",=
"21-03-2025 06:45:43","21-03-2025 06:19:00","21-03-2025 07:02:33","Cascaded=
 Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, site went down because gen ran u=
ntill fuel shortage // Refueling done","system","272868","21-03-2025 06:45:=
43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0004624398","LOBO MTN=
","","21-03-2025 06:45:43","21-03-2025 06:19:00","21-03-2025 07:02:33","Cas=
caded Incident from TTO4701903","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 because gen ran untill fuel shortage // Refueling done","system","272869",=
"21-03-2025 06:45:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_310","NOCINC0004624394","Nomayos"=
,"","21-03-2025 06:45:42","21-03-2025 06:19:00","21-03-2025 07:02:33","Casc=
aded Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen r=
an untill fuel shortage // Refueling done","system","272860","21-03-2025 06=
:45:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004624393","Nkongtoc=
k","","21-03-2025 06:45:42","21-03-2025 06:19:00","21-03-2025 07:02:33","Ca=
scaded Incident from TTO4701903","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen ran untill fuel shortage // Refueling done","system","272855","21-03-2=
025 06:45:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004624391","Angongo"=
,"","21-03-2025 06:45:42","21-03-2025 06:19:00","21-03-2025 07:02:33","Casc=
aded Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen r=
an untill fuel shortage // Refueling done","system","272863","21-03-2025 06=
:45:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004624392","Minka","=
","21-03-2025 06:45:42","21-03-2025 06:19:00","21-03-2025 07:02:33","Cascad=
ed Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen ran=
 untill fuel shortage // Refueling done","system","272859","21-03-2025 06:4=
5:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004624390","Bondjock=
","","21-03-2025 06:45:42","21-03-2025 06:19:00","21-03-2025 07:02:33","Cas=
caded Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
ran untill fuel shortage // Refueling done","system","272867","21-03-2025 0=
6:45:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004624387","OTELE MT=
N","","21-03-2025 06:45:41","21-03-2025 06:19:00","21-03-2025 07:02:33","Ca=
scaded Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down because gen=
 ran untill fuel shortage // Refueling done","system","272863","21-03-2025 =
06:45:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_706","NOCINC0004624386","Mbankomo=
 CAF","","21-03-2025 06:45:41","21-03-2025 06:19:00","21-03-2025 07:02:33",=
"Cascaded Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen ran untill fuel shortage // Refueling done","system","272866","21-03-20=
25 06:45:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_366","NOCINC0004624382","Mandoumb=
a MTN","","21-03-2025 06:45:40","21-03-2025 06:19:00","21-03-2025 07:02:33"=
,"Cascaded Incident from TTO4701903","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause gen ran untill fuel shortage // Refueling done","system","272862","21-=
03-2025 06:45:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0004624384","Ndogbess=
ol","","21-03-2025 06:45:40","21-03-2025 06:19:00","21-03-2025 07:02:33","C=
ascaded Incident from TTO4701903","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // Refueling done","system","272858","21-03-=
2025 06:45:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004624383","Mambine"=
,"","21-03-2025 06:45:40","21-03-2025 06:19:00","21-03-2025 07:02:33","Casc=
aded Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen r=
an untill fuel shortage // Refueling done","system","272863","21-03-2025 06=
:45:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004624379","Ebeba","=
","21-03-2025 06:45:39","21-03-2025 06:19:00","21-03-2025 07:02:33","Cascad=
ed Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen ran=
 untill fuel shortage // Refueling done","system","272862","21-03-2025 06:4=
5:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004624378","Song-bon=
g","","21-03-2025 06:45:39","21-03-2025 06:19:00","21-03-2025 07:02:33","Ca=
scaded Incident from TTO4701903","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen ran untill fuel shortage // Refueling done","system","272866","21-03-2=
025 06:45:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0004624380","Bot Maka=
k","","21-03-2025 06:45:39","21-03-2025 06:19:00","21-03-2025 07:02:33","Ca=
scaded Incident from TTO4701903","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, site went down because gen ran untill=
 fuel shortage // Refueling done","system","272858","21-03-2025 06:45:39","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0004624377","Ngog Map=
ubi","","21-03-2025 06:45:38","21-03-2025 06:19:00","21-03-2025 07:02:33","=
Cascaded Incident from TTO4701903","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen ran untill fuel shortage // Refueling done","system","272872","21-03=
-2025 06:45:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0004624376","Nkeng li=
kok","","21-03-2025 06:45:38","21-03-2025 06:19:00","21-03-2025 07:02:33","=
Cascaded Incident from TTO4701903","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen ran untill fuel shortage // Refueling done","system","272871","21-03=
-2025 06:45:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0004624375","Lobo 2",=
"","21-03-2025 06:45:38","21-03-2025 06:19:00","21-03-2025 07:02:33","Casca=
ded Incident from TTO4701903","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen ran untill fuel shortage // Refueling done","system","272857","2=
1-03-2025 06:45:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004624374","Nomayos =
montee Meche","","21-03-2025 06:45:38","21-03-2025 06:19:00","21-03-2025 07=
:02:33","Cascaded Incident from TTO4701903","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
because gen ran untill fuel shortage // Refueling done","system","272861","=
21-03-2025 06:45:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004624370","OLAMA","=
","21-03-2025 06:45:37","21-03-2025 06:19:00","21-03-2025 07:02:33","Cascad=
ed Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen ran=
 untill fuel shortage // Refueling done","system","272861","21-03-2025 06:4=
5:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004624369","OKOA Pea=
ge","","21-03-2025 06:45:37","21-03-2025 06:19:00","21-03-2025 07:02:33","C=
ascaded Incident from TTO4701903","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n ran untill fuel shortage // Refueling done","system","272865","21-03-2025=
 06:45:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_373","NOCINC0004624371","Maloun",=
"","21-03-2025 06:45:37","21-03-2025 06:19:00","21-03-2025 07:02:33","Casca=
ded Incident from TTO4701903","Kemeni Franklin","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n ran untill fuel shortage // Refueling done","system","272871","21-03-2025=
 06:45:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_781","NOCINC0004624367","BIBOMDJI=
DJIEL","","21-03-2025 06:45:36","21-03-2025 06:19:00","21-03-2025 07:02:33"=
,"Cascaded Incident from TTO4701903","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause gen ran untill fuel shortage // Refueling done","system","272856","21-=
03-2025 06:45:36","Sagemcom CMR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0004624230","Sou=
s Prefecture","IHS_YND_781, IHS_EDA_041, IHS_YND_330, IHS_YND_687, IHS_YND_=
373, IHS_YND_538, IHS_YND_701, IHS_YND_791, IHS_YND_783, IHS_YND_347, IHS_Y=
ND_419, IHS_YND_453, IHS_YND_339, IHS_YND_421, IHS_EDA_043, IHS_YND_366, IH=
S_YND_350, IHS_EDA_056, IHS_EDA_032, IHS_YND_706, IHS_YND_531, IHS_EDA_101,=
 IHS_EDA_069, IHS_YND_372, IHS_YND_335, IHS_YND_371, IHS_YND_349, IHS_YND_3=
10, IHS_YND_762, IHS_YND_714, IHS_YND_342, IHS_YND_370, IHS_YND_593, IHS_YN=
D_365, IHS_YND_697, IHS_YND_379, IHS_EDA_045, IHS_EDA_114, IHS_YND_378, IHS=
_YND_713","21-03-2025 06:22:05","21-03-2025 06:19:00","21-03-2025 08:17:56"=
,"Grid outage, site went down because gen ran untill fuel shortage // Refue=
ling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, site went down because gen ran untill fuel shortage // Refueli=
ng done","yves.djomo@sagemcom.com","186","21-03-2025 06:22:05","Sagemcom CM=
R"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004624143","Oko=
lo Kilombo","","21-03-2025 05:44:24","21-03-2025 05:37:03","21-03-2025 07:3=
5:41","Grid outage, site went down because gen fails to start due to Gen ca=
ble faulty // He bypassed gen cable and gen manually started","Fabrice Poua=
kam","Equipment Repair","Passive","Infrastructure","Armoured Cable","Grid o=
utage, site went down because gen fails to start due to Gen cable faulty //=
 He bypassed gen cable and gen manually started","yves.djomo@sagemcom.com",=
"442","21-03-2025 05:44:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0004624042","M=
fou EPC","","21-03-2025 05:08:58","21-03-2025 04:59:40","21-03-2025 14:01:1=
0","Grid outage, site went down because gen ran until fuel shortage // Refu=
eling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, site went down because gen ran until fuel shortage // Re=
fueling done","yves.djomo@sagemcom.com","559","21-03-2025 05:08:58","Sagemc=
om CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004623709","Ole=
mbe MTN","","21-03-2025 03:10:01","21-03-2025 03:02:53","21-03-2025 05:00:3=
1","Grid outage, site went down because gen failed to start due to grid con=
tactor faulty // He bypassed ATS and Gen manually started","Fabrice Pouakam=
","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage=
, site went down because gen failed to start due to grid contactor faulty /=
/ He bypassed ATS and Gen manually started","yves.djomo@sagemcom.com","429"=
,"21-03-2025 03:10:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004623475","MEHANDAN=
","","21-03-2025 01:38:54","21-03-2025 01:28:39","21-03-2025 03:24:42","Cas=
caded Incident from TTO4701046","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,gen ran till fuel shortage=
//Refueling done","system","275744","21-03-2025 01:38:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004623470","O=
dza II OCM","IHS_YND_528","21-03-2025 01:37:52","21-03-2025 01:28:39","21-0=
3-2025 03:24:42","Grid outage,gen ran till fuel shortage//Refueling done","=
Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outag=
e,gen ran till fuel shortage//Refueling done","yves.djomo@sagemcom.com","55=
4","21-03-2025 01:37:52","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004623182","Nko=
londom","","21-03-2025 00:40:45","21-03-2025 00:38:41","21-03-2025 00:48:29=
","Grid fluctuation, Site went down because Gen failed to start due to Grid=
 bad voltage and No RCP on site // He bypassed the Grid and Gen manually st=
arted","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation, Site went down because Gen failed=
 to start due to Grid bad voltage and No RCP on site // He bypassed the Gri=
d and Gen manually started","yves.djomo@sagemcom.com","125","21-03-2025 00:=
40:45","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004623157","NYO=
M FACE MAETUR","","21-03-2025 00:34:27","21-03-2025 00:28:22","21-03-2025 0=
0:43:07","Grid outage site went down because Gen failed to start due to Gen=
 card faulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start due to Gen card faulty // Grid return","yves.djomo@sagemcom=
.com","366","21-03-2025 00:34:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0004623060","Nkoulou =
Carriere carrefourt","","21-03-2025 00:18:41","21-03-2025 00:11:36","21-03-=
2025 00:14:08","Cascaded Incident from TTO4700585","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","Grid fluctuation=
, Site went because Gen failed to start due to Grid bad voltage No rcp//  H=
e bypassed Grid and started Gen manually","system","1222531","21-03-2025 00=
:18:41","Sagemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0004623057","Aba=
ng","IHS_YND_794","21-03-2025 00:17:39","21-03-2025 00:11:36","21-03-2025 0=
0:14:08","Grid fluctuation, Site went down because Gen failed to start due =
to Grid bad voltage No rcp//  He bypassed Grid and started Gen manually","M=
ba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid fluctuation, Site went down because Gen failed to star=
t due to Grid bad voltage No rcp//  He bypassed Grid and started Gen manual=
ly","yves.djomo@sagemcom.com","364","21-03-2025 00:17:39","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004622726","NYO=
M FACE MAETUR","","20-03-2025 22:56:17","20-03-2025 22:48:04","20-03-2025 2=
3:26:19","Grid outage site went down because Gen failed to start due to Gen=
 card faulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start due to Gen card faulty // Grid return","el-dalile@sagemcom.=
com","495","20-03-2025 22:56:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004622353","E=
kombitie","","20-03-2025 21:44:15","20-03-2025 21:35:47","20-03-2025 22:32:=
48","Grid fluctuation, Site went down because Gen failed to start due to Gr=
id bad voltage and No RCP on site // He bypassed the Grid and Gen manually =
started","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","Grid fluctuation, Site went down because Gen fail=
ed to start due to Grid bad voltage and No RCP on site // He bypassed the G=
rid and Gen manually started","danick.tchakouani@sagemcom.com","509","20-03=
-2025 21:44:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004622345","E=
mana Lycee","","20-03-2025 21:42:15","20-03-2025 21:17:58","20-03-2025 21:2=
5:56","Active//No power issue on site Ubaie=3D54,6 V site on Grid ,TX FME S=
ynphorien (691316854) from Huawei is informed. Notice that we have disjunct=
ion at BTS","Fabrice Pouakam","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site Ub=
aie=3D54,6 V site on Grid ,TX FME Synphorien (691316854) from Huawei is inf=
ormed. Notice that we have disjunction at BTS","danick.tchakouani@sagemcom.=
com","1458","20-03-2025 21:42:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004622129","S=
calom","","20-03-2025 21:11:37","20-03-2025 21:10:09","20-03-2025 21:14:05"=
,"Grid Outage, site went down before gen start due to poor battery backup /=
/ Gen started automatically","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid Outage, site went down bef=
ore gen start due to poor battery backup // Gen started automatically","dan=
ick.tchakouani@sagemcom.com","89","20-03-2025 21:11:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004622103","N=
kolfon Cimencam","","20-03-2025 21:06:27","20-03-2025 20:01:13","20-03-2025=
 20:01:14","Active//No power issue, Site on Grid Ubai=3D 50,8V. Notice that=
 it is impacted by Afanoya II Flubert from Huawei is informed","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 50,8V. Notice=
 that it is impacted by Afanoya II Flubert from Huawei is informed","danick=
.tchakouani@sagemcom.com","3915","20-03-2025 21:06:27","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004622067","Nko=
abang2","","20-03-2025 21:01:40","20-03-2025 20:56:16","20-03-2025 21:00:45=
","Active//No power issue site on Battery with U=3D49,2 V Lionel Adjep(6551=
84876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue site on Battery with U=3D49,2 V Lionel Adjep(655184876) from Hua=
wei is informed","danick.tchakouani@sagemcom.com","326","20-03-2025 21:01:4=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004621957","B=
iteng-Maetur","","20-03-2025 20:45:01","20-03-2025 20:42:50","20-03-2025 23=
:05:58","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","danick.=
tchakouani@sagemcom.com","133","20-03-2025 20:45:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004621902","A=
kak-Nkozoa-MTN-IHS","","20-03-2025 20:36:04","20-03-2025 20:31:38","20-03-2=
025 20:45:38"," site went down due to PWC dysfunctionning, // He Reset it a=
nd site is on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded"," site went down due to PWC dysfunctionni=
ng, // He Reset it and site is on Grid","danick.tchakouani@sagemcom.com","4=
84","20-03-2025 20:36:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004621896","N=
YOM 2 IHS","","20-03-2025 20:34:25","20-03-2025 20:24:59","21-03-2025 01:30=
:46","Site went down because CB (80A) tripped in PWC who feeds equipments O=
CM due to load increase// He bypassed CB","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site=
 went down because CB (80A) tripped in PWC who feeds equipments OCM due to =
load increase// He bypassed CB","danick.tchakouani@sagemcom.com","568","20-=
03-2025 20:34:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004621890","C=
omplexe-BEAC","","20-03-2025 20:33:44","20-03-2025 20:24:59","20-03-2025 20=
:25:46","Active//No power issue U=3D54.7 V site on B and The TX FME Leonel =
Steve (655184876) from huawei is informed  and Notice that we have disjunct=
ion at BTS","Albran Byorel","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Active//No power issue U=3D50.7 V s=
ite on Battery and The TX FME Leonel Steve (655184876) from huawei is infor=
med  and Notice that we have disjunction at BTS","danick.tchakouani@sagemco=
m.com","526","20-03-2025 20:33:44","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004621883","Elo=
umdem stade","","20-03-2025 20:32:17","20-03-2025 20:31:06","20-03-2025 20:=
43:14","Grid bad voltage, Site went down before Gen start due to poor backu=
p // Gen start automatically","Fanda Brice","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid bad voltage, Site went do=
wn before Gen start due to poor backup // Gen start automatically","danick.=
tchakouani@sagemcom.com","73","20-03-2025 20:32:17","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004621562","EMA=
NA BILICK CITY","","20-03-2025 19:22:28","20-03-2025 19:12:59","20-03-2025 =
21:40:20","Grid outage, site went down because gen ran untill fuel shortage=
 // Refueling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Die=
sel Outage","Grid outage, site went down because gen ran untill fuel shorta=
ge // Refueling done","danick.tchakouani@sagemcom.com","605","20-03-2025 19=
:22:28","Sagemcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004621388","Ron=
d Point Express1114","","20-03-2025 18:53:32","20-03-2025 18:42:59","20-03-=
2025 19:00:59","Grid outage, site went down before gen start due to poor ba=
ttery backup // Gen start automatically","Hyemafo Gildas","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen start automa=
tically","danick.tchakouani@sagemcom.com","634","20-03-2025 18:53:32","Sage=
mcom CMR"
"Closed Complete","Site Down","T3206","IHS_YND_759","NOCINC0004621234","Nko=
lfoulou Tsinga Village","","20-03-2025 18:16:32","20-03-2025 18:13:25","20-=
03-2025 19:51:25","Site went down due to 01 Rectifier  Faulty on Site //He =
removed the Faulty rectifier and Site is on Grid  (01 Rectifier to be add )=
","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to 01 Rectifier  Faulty on Site //He removed the Fau=
lty rectifier and Site is on Grid  (01 Rectifier to be add )","danick.tchak=
ouani@sagemcom.com","188","20-03-2025 18:16:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004621226","M=
ontee-Jouvence-II","","20-03-2025 18:14:36","20-03-2025 18:12:07","20-03-20=
25 19:58:07","Site went down due to PWC Overloaded (12K, 250A) // site stab=
ilized SS IHS Alphonse confirmed // Load reduice and gen started","Hyemafo =
Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module Overload=
ed","Site went down due to PWC Overloaded (12K, 250A) // site stabilized SS=
 IHS Alphonse confirmed // Load reduice and gen started","danick.tchakouani=
@sagemcom.com","150","20-03-2025 18:14:36","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004621176","Eko=
umdoum OCM","","20-03-2025 18:05:08","20-03-2025 18:02:55","21-03-2025 13:0=
5:43","Grid outage, Site went down because Gen overload (20kva, 300A) SS IH=
S alphonse confirmed// site on GEN","Albran Byorel","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen=
 overload (20kva, 300A) SS IHS alphonse confirmed// site on GEN","danick.tc=
hakouani@sagemcom.com","134","20-03-2025 18:05:08","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004621152","SAA=
 Entrance","","20-03-2025 18:01:41","20-03-2025 17:55:47","20-03-2025 18:36=
:47","Grid outage site went down because Gen failed to start due to Gen bat=
tery faulty // Grid return","Parker Tchoup","Equipment Repair","Passive","A=
CDG Gen","ACDG - Generator Battery","Grid outage site went down because Gen=
 failed to start due to Gen battery faulty // Grid return","danick.tchakoua=
ni@sagemcom.com","355","20-03-2025 18:01:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004620925","Bitoto",=
"","20-03-2025 17:26:37","20-03-2025 17:19:36","20-03-2025 17:26:36","Casca=
ded Incident from TTO4698063","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage. site went down due to Ge=
n overload(20Kva,230A)//We reduce load and gen manually started","system","=
276040","20-03-2025 17:26:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_796","NOCINC0004620908","Nkoabang=
 Ebolmedjock","","20-03-2025 17:22:22","20-03-2025 17:19:36","20-03-2025 17=
:26:36","Cascaded Incident from TTO4698063","Mba Lazare Herve","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Grid outage. site went =
down due to Gen overload(20Kva,230A)//We reduce load and gen manually start=
ed","system","276040","20-03-2025 17:22:22","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004620895","Nko=
abang MTN","IHS_YND_292, IHS_YND_796","20-03-2025 17:20:48","20-03-2025 17:=
19:36","20-03-2025 17:26:36","Grid outage. site went down due to Gen overlo=
ad(20Kva,230A)//We reduce load and gen manually started","Mba Lazare Herve"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage. si=
te went down due to Gen overload(20Kva,230A)//We reduce load and gen manual=
ly started","danick.tchakouani@sagemcom.com","73","20-03-2025 17:20:48","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0004620873","N=
GONA","","20-03-2025 17:16:02","20-03-2025 17:09:56","20-03-2025 18:33:50",=
"Grid outage,site went down because Gen failed to start due to battery ge d=
ischarge //he started with an external battery","Mba Lazare Herve","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage,sit=
e went down because Gen failed to start due to battery ge discharge //he st=
arted with an external battery","danick.tchakouani@sagemcom.com","428","20-=
03-2025 17:16:02","Sagemcom CMR"
"Closed Complete","Warning","T0058","IHS_YND_293","NOCINC0004620832","Nkoab=
ang MTN","","20-03-2025 17:10:52","","","Eneo outage // eneo return","Mba L=
azare Herve","Warning","Warning","POWER","Warning - Site on Battery","Eneo =
outage // eneo return","mariam.tchonang@sagemcom.com","795","20-03-2025 17:=
10:52","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004620687","NTU=
I TOWN","","20-03-2025 16:49:53","20-03-2025 16:48:35","20-03-2025 17:23:35=
","Grid fructuation site went down because Gen failed to start due to Grid =
bad voltage // He bypass the Grid site on Gen","Parker Tchoup","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fructuat=
ion site went down because Gen failed to start due to Grid bad voltage // H=
e bypass the Grid site on Gen","danick.tchakouani@sagemcom.com","79","20-03=
-2025 16:49:53","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004620410","Nko=
abang2","","20-03-2025 16:17:48","20-03-2025 16:09:39","20-03-2025 16:09:40=
","Error","Mba Lazare Herve","Incorrectly Logged Tickets","Error","Error","=
Error","Error","danick.tchakouani@sagemcom.com","490","20-03-2025 16:17:48"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004619964","S=
calom-IHS","","20-03-2025 15:05:44","20-03-2025 15:00:31","20-03-2025 19:39=
:24","No power issue on site Ubaie=3D53V site on Grid. The Tx FME Hosiah //=
699699694 from Huawei is informed.","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
baie=3D53V site on Grid. The Tx FME Hosiah //699699694 from Huawei is infor=
med.","danick.tchakouani@sagemcom.com","315","20-03-2025 15:05:44","Sagemco=
m CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004619942","ODZ=
A MINKAN EDIBI ASSI","","20-03-2025 15:02:24","20-03-2025 14:59:11","20-03-=
2025 18:39:12","ACTIVE//No power issue on site ,site on Grid with Ubaie=3D =
54,6V The Tx FME Leonel Adjep /655184876/From HUAWEI is informed ","Albran =
Byorel","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","ACTIVE//No power issue on site ,site on Grid with Ubaie=
=3D 54,6V The Tx FME Leonel Adjep /655184876/From HUAWEI is informed ","dan=
ick.tchakouani@sagemcom.com","194","20-03-2025 15:02:24","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004619936","BIY=
EMASSI NIKI","IHS_YND_546","20-03-2025 15:01:38","20-03-2025 14:48:16","20-=
03-2025 17:50:16","Site went down due to PWC overloaded (12kva 250 A) //Sit=
e stabilized, F=E9lix Zambe is informed and confirmed / Load reduice and ge=
n started","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Recti=
fier Module Overloaded","Site went down due to PWC overloaded (12kva 250 A)=
 //Site stabilized, F=E9lix Zambe is informed and confirmed / Load reduice =
and gen started","danick.tchakouani@sagemcom.com","3550","20-03-2025 15:01:=
38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004619928","O=
mnisport-Rail","","20-03-2025 15:00:04","20-03-2025 14:49:18","20-03-2025 1=
5:58:18","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, site went down because gen fails to start du=
e to battery ge faulty // Gen start with battery backup","danick.tchakouani=
@sagemcom.com","285280","20-03-2025 15:00:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004619910","B=
iyemassi LAC","","20-03-2025 14:57:06","20-03-2025 14:48:16","20-03-2025 17=
:50:16","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","Site went down due to PWC overloaded (12kva 250 A) //Site stabilized, F=
=E9lix Zambe is informed and confirmed / Load reduice and gen started","dan=
ick.tchakouani@sagemcom.com","285260","20-03-2025 14:57:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_209","NOCINC0004619904","Manguier=
","","20-03-2025 14:56:44","20-03-2025 14:49:18","20-03-2025 15:58:18","Cas=
caded Incident from TTO4696895","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen fails to start due to battery ge faulty // Gen start with battery backu=
p","system","285281","20-03-2025 14:56:44","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004619880","MAN=
GUIERS CHAPELLE","IHS_YND_506, IHS_YND_209","20-03-2025 14:54:29","20-03-20=
25 14:49:18","20-03-2025 15:59:18","Grid outage, site went down because gen=
 fails to start due to battery ge faulty // Gen start with battery backup",=
"Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator=
 Battery","Grid outage, site went down because gen fails to start due to ba=
ttery ge faulty // Gen start with battery backup","danick.tchakouani@sagemc=
om.com","312","20-03-2025 14:54:29","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004619772","Mon=
tee Jouvence","","20-03-2025 14:37:39","20-03-2025 14:25:25","20-03-2025 15=
:29:25","Grid outage, site went down because gen start and stopped due to h=
igh temp // He added water and manually start the gen","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Grid outage, site went down because gen start and stopped due to=
 high temp // He added water and manually start the gen","danick.tchakouani=
@sagemcom.com","734","20-03-2025 14:37:39","Sagemcom CMR"
"Closed Complete","Site Down","T0715","IHS_YND_406","NOCINC0004619756","Mon=
atele","","20-03-2025 14:36:42","20-03-2025 14:29:49","20-03-2025 15:05:55"=
,"","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down because gen ran until fuel shortage //=
 Refueling done","cedric.tiani@sagemcom.com","723","20-03-2025 14:36:42","S=
agemcom CMR"
"Closed Complete","Site Down","T0053","IHS_YND_407","NOCINC0004619753","Mon=
atele MTN","IHS_YND_406","20-03-2025 14:36:01","20-03-2025 14:29:49","20-03=
-2025 15:05:55","Grid outage, site went down because gen ran until fuel sho=
rtage // Refueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","=
Diesel Outage","Grid outage, site went down because gen ran until fuel shor=
tage // Refueling done","cedric.tiani@sagemcom.com","373","20-03-2025 14:36=
:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004619718","S=
hell-Nsimeyong","","20-03-2025 14:28:54","20-03-2025 14:25:45","20-03-2025 =
14:30:53","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed. Repetitive Issue","MINKA NICOL=
AS","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosi=
ah (674007438/699699694) from Huawei is informed. Repetitive Issue","cedric=
.tiani@sagemcom.com","190","20-03-2025 14:28:54","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004619717","Ole=
mbe MTN","","20-03-2025 14:28:50","20-03-2025 14:24:43","20-03-2025 14:28:4=
3","Site went down because Gen failed to start due to Grid bad voltage and =
RCP on site // He bypass the Grid and Gen manually Started","Fabrice Pouaka=
m","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Site went down because Gen failed to start due to Grid bad voltage and RC=
P on site // He bypass the Grid and Gen manually Started","danick.tchakouan=
i@sagemcom.com","248","20-03-2025 14:28:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_401","IHS_YND_041","NOCINC0004619686","L=
ycee Leclerc School","","20-03-2025 14:22:48","20-03-2025 12:21:35","20-03-=
2025 17:25:35","No power issue on site,site on Grid with Ubaie=3D52.3 V The=
 Tx Fme Mbah hosiah(674007438) from Huawei is informed. Notice that dysjunc=
tion at OCM Equipment","Paul BIBOUM","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site,sit=
e on Grid with Ubaie=3D52.3 V The Tx Fme Mbah hosiah(674007438) from Huawei=
 is informed. Notice that dysjunction at OCM Equipment","ludovic-anselme.mo=
uliom-mapoure@sagemcom","7274","20-03-2025 14:22:48","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004619484","Mam=
bine","","20-03-2025 13:41:43","20-03-2025 13:36:30","20-03-2025 14:06:30",=
"Grid outage, site went down because gen ran until fuel shortage // Refueli=
ng done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage, site went down because gen ran until fuel shortage // Refueling =
done","ludovic-anselme.mouliom-mapoure@sagemcom","314","20-03-2025 13:41:43=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0004619427","A=
n-Marche-Melen","","20-03-2025 13:32:16","20-03-2025 13:27:00","20-03-2025 =
16:22:00","Grid outage, No space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No =
space to deploy MDG // Grid return","yves.djomo@sagemcom.com","318","20-03-=
2025 13:32:16","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004619256","Jou=
vence Mbenda","","20-03-2025 13:01:15","20-03-2025 12:30:59","20-03-2025 14=
:13:59","Grid outage, site went down because gen fails to start due to batt=
ery ge faulty // Gen start with battery backup","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, site=
 went down because gen fails to start due to battery ge faulty // Gen start=
 with battery backup","ludovic-anselme.mouliom-mapoure@sagemcom","1818","20=
-03-2025 13:01:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004618950","Saa","",=
"20-03-2025 12:18:51","20-03-2025 07:39:51","20-03-2025 07:43:29","Cascaded=
 Incident from TTO4693442","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because rectifier disfunctio=
nning // He reset it: Site on grid ","system","289440","20-03-2025 12:18:51=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004618949","SAA Entr=
ance","","20-03-2025 12:18:51","20-03-2025 07:39:51","20-03-2025 07:43:29",=
"Cascaded Incident from TTO4693442","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because rectifier d=
isfunctionning // He reset it: Site on grid ","system","289440","20-03-2025=
 12:18:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004618948","Carrefou=
r Ayissi Ele","","20-03-2025 12:18:51","20-03-2025 07:39:51","20-03-2025 07=
:43:29","Cascaded Incident from TTO4693442","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down because rec=
tifier disfunctionning // He reset it: Site on grid ","system","289440","20=
-03-2025 12:18:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004618946","Angongo"=
,"","20-03-2025 12:18:38","20-03-2025 07:07:50","20-03-2025 07:51:24","Casc=
aded Incident from TTO4693348","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Gen only site, Site went down because gen=
 fails to start due to hybrid systeme dysfunctionning // Reset done and gen=
 started","system","313016","20-03-2025 12:18:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0004618729","N=
gousso-II","","20-03-2025 11:53:18","20-03-2025 11:41:07","20-03-2025 12:35=
:40","No power issue site on grid with U=3D52.7v Notice that site is impact=
ed by Nkoabang EBULMEDJOCK site up at 11:56 AM","MFOUAGUEGUE MATHIEU","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue site on grid with U=3D52.7v Notice that site is impac=
ted by Nkoabang EBULMEDJOCK site up at 11:56 AM","yves.djomo@sagemcom.com",=
"732","20-03-2025 11:53:18","Sagemcom CMR"
"Closed Complete","Site Down","T3446","IHS_YND_712","NOCINC0004618213","Nko=
lkoumou OCM","","20-03-2025 10:47:08","20-03-2025 10:43:57","20-03-2025 12:=
45:44","No power issue site on grid with U=3D54.5V DJILANE(655578762) from =
TELIS is wirking on microwave link (Nkolkoumou-Nkolbisson usine des eaux)",=
"TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54.5V DJILANE(655578762) from TELIS is wirking on microwave link (Nkolko=
umou-Nkolbisson usine des eaux)","ludovic-anselme.mouliom-mapoure@sagemcom"=
,"192","20-03-2025 10:47:08","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004618174","Eko=
umdoum OCM","","20-03-2025 10:41:47","20-03-2025 10:35:36","20-03-2025 11:2=
3:49","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS =
Pascaline is informed and confirmed//We reduce load and gen manually starte=
d ","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS Pas=
caline is informed and confirmed//We reduce load and gen manually started "=
,"ludovic-anselme.mouliom-mapoure@sagemcom","620","20-03-2025 10:41:47","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004617964","Ngu=
ila","","20-03-2025 10:16:36","20-03-2025 10:11:26","20-03-2025 11:35:05","=
Grid outage, site went down because gen failed to start with alarm undervol=
tage // He reset gen card and gen manually started","Parker Tchoup","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site =
went down because gen failed to start with alarm undervoltage // He reset g=
en card and gen manually started","ludovic-anselme.mouliom-mapoure@sagemcom=
","312","20-03-2025 10:16:36","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0004617758","N=
yanon","","20-03-2025 10:08:01","20-03-2025 09:59:46","20-03-2025 12:51:44"=
,"Site went down because gen start and stopped with high temp alarm // He a=
dded water and manually","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Site went=
 down because gen start and stopped with high temp alarm // He added water =
and manually","yves.djomo@sagemcom.com","497","20-03-2025 10:08:01","Sagemc=
om CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004617645","Men=
dong NB","","20-03-2025 09:57:25","20-03-2025 09:54:08","20-03-2025 11:30:5=
1","Grid outage.no space to deploy mobile gen //Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no spa=
ce to deploy mobile gen //Grid return","ludovic-anselme.mouliom-mapoure@sag=
emcom","198","20-03-2025 09:57:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004617360","E=
ssomba","","20-03-2025 09:26:16","20-03-2025 09:07:03","20-03-2025 09:27:43=
","Grid outage.site went down due to gen failed to start //Grid return(inve=
stigation ongoing)","Mba Lazare Herve","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage.site went down due to gen failed to=
 start //Grid return(investigation ongoing)","yves.djomo@sagemcom.com","115=
5","20-03-2025 09:26:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004617180","S=
hell-Nsimeyong","","20-03-2025 08:58:41","20-03-2025 08:55:54","20-03-2025 =
08:57:37","Active//No power issue U =3D52.2V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue site =
up at 09:00 AM","MINKA NICOLAS","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active//No power issue U =3D52.=
2V site on Grid.The FME TX Mbah Hosiah (674007438/699699694) from Huawei is=
 informed. Repetitive Issue site up at 09:00 AM","yves.djomo@sagemcom.com",=
"168","20-03-2025 08:58:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004617155","M=
ontee-Jouvence-II","","20-03-2025 08:53:20","20-03-2025 08:50:03","20-03-20=
25 11:57:35","Grid outage, Site went down because Gen overload (15kva, 250A=
) SS IHS Felix Zambe is informed // GRid power return","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site w=
ent down because Gen overload (15kva, 250A) SS IHS Felix Zambe is informed =
// GRid power return","yves.djomo@sagemcom.com","199","20-03-2025 08:53:20"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004617110","Car=
refour Simbock","","20-03-2025 08:44:41","20-03-2025 08:35:34","20-03-2025 =
11:31:47","Grid outage gen ran until fuel shortage//Refueling done","Hyemaf=
o Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage gen=
 ran until fuel shortage//Refueling done","wilfried.kameni@sagemcom.com","5=
48","20-03-2025 08:44:41","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004617021","AKA=
K Nkozoa","","20-03-2025 08:32:02","20-03-2025 08:27:54","20-03-2025 11:26:=
08","Site down due to work done by  ROMEL DJOMAGUE(678131047): swapp of cir=
buit breaker//End of work ","Fabrice Pouakam","Installation Activity","Pass=
ive","Planned Activity","Installation Activity","Site down due to work done=
 by  ROMEL DJOMAGUE(678131047): swapp of cirbuit breaker//End of work ","lu=
dovic-anselme.mouliom-mapoure@sagemcom","249","20-03-2025 08:32:02","Sagemc=
om CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004616857","SAA=
 2","IHS_YND_810, IHS_YND_542, IHS_YND_405","20-03-2025 07:44:05","20-03-20=
25 07:39:51","20-03-2025 07:43:29","Site went down because rectifier disfun=
ctionning // He reset it: Site on grid ","Parker Tchoup","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down because rectifier=
 disfunctionning // He reset it: Site on grid ","ludovic-anselme.mouliom-ma=
poure@sagemcom","255","20-03-2025 07:44:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004616768","E=
beba","IHS_YND_335","20-03-2025 07:12:04","20-03-2025 07:07:50","20-03-2025=
 07:51:24","Gen only site, Site went down because gen fails to start due to=
 hybrid systeme dysfunctionning // Reset done and gen started","Fanda Brice=
","Equipment Repair","Passive","Hybrid","Hybrid Module","Gen only site, Sit=
e went down because gen fails to start due to hybrid systeme dysfunctionnin=
g // Reset done and gen started","yves.djomo@sagemcom.com","255","20-03-202=
5 07:12:04","Sagemcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004616752","TSI=
NGA VILLAGE 2","","20-03-2025 07:05:09","20-03-2025 06:51:52","20-03-2025 0=
7:51:43"," site went down because gen start an stopped due to water infiltr=
ation in tank // He purged The tank and Gen manually started","Delor Telezi=
ng","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water=
 In The Fuel"," site went down because gen start an stopped due to water in=
filtration in tank // He purged The tank and Gen manually started","ludovic=
-anselme.mouliom-mapoure@sagemcom","799","20-03-2025 07:05:09","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004616709","S=
hell-Nsimeyong","","20-03-2025 06:48:52","20-03-2025 06:47:37","20-03-2025 =
06:55:21","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","yves.djomo@sagemcom.com","76","20-03-2025 06:48:52","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0004616672","E=
toug ebe Meweulo","","20-03-2025 06:30:38","20-03-2025 06:24:29","20-03-202=
5 07:55:04","Grid outage.gen ran until fuel shortage//Grid return","Hyemafo=
 Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen =
ran until fuel shortage//Grid return","yves.djomo@sagemcom.com","370","20-0=
3-2025 06:30:38","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004616611","Obo=
bogo","","20-03-2025 05:58:33","20-03-2025 05:52:27","20-03-2025 06:00:35",=
"Grid outage, Site went down before Gen start due to poor backup // Gen sta=
rted automatically","MINKA NICOLAS","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen started automatically","yves.djomo@sagemco=
m.com","367","20-03-2025 05:58:33","Sagemcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004616445","TSI=
NGA VILLAGE 2","","20-03-2025 04:55:07","20-03-2025 04:47:56","20-03-2025 0=
6:51:06","site went down because gen start an stopped due to water infiltra=
tion in tank // He purged The tank and Gen manually started","Delor Telezin=
g","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water =
In The Fuel","site went down because gen start an stopped due to water infi=
ltration in tank // He purged The tank and Gen manually started","wilfried.=
kameni@sagemcom.com","432","20-03-2025 04:55:07","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004616323","Abo=
me","","20-03-2025 03:38:57","20-03-2025 03:31:24","20-03-2025 04:37:59","G=
rid fluctuation, Site went down because gen fails to start due to grid bad =
voltage,no rcp// He bypassed the Grid and site on Gen","MINKA NICOLAS","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation, Site went down because gen fails to start due to grid bad volt=
age,no rcp// He bypassed the Grid and site on Gen","wilfried.kameni@sagemco=
m.com","454","20-03-2025 03:38:57","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004616304","Lad=
a I Yde","","20-03-2025 03:29:52","20-03-2025 03:24:31","20-03-2025 03:47:4=
1"," Grid outage, site went down Gen fialed to start due to Gen contacteur =
no excited // He excited the Gen coantactor and Gen manually started","Mba =
Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contacto=
r"," Grid outage, site went down Gen fialed to start due to Gen contacteur =
no excited // He excited the Gen coantactor and Gen manually started","wilf=
ried.kameni@sagemcom.com","322","20-03-2025 03:29:52","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004616213","EMA=
NA BILICK CITY","","20-03-2025 02:42:11","20-03-2025 02:40:06","20-03-2025 =
05:11:35","Grid outage, site went down because gen ran untill fuel shortage=
 // Refueling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Die=
sel Outage","Grid outage, site went down because gen ran untill fuel shorta=
ge // Refueling done","yves.djomo@sagemcom.com","127","20-03-2025 02:42:11"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004615535","N=
kolfon Cimencam","","20-03-2025 01:26:15","20-03-2025 01:19:10","20-03-2025=
 01:25:00","No power issue on site, site on Grid.The Tx FME  Fulbert  (6542=
66068) of huawei is informed. Notice that site is impacted by Afanoya II wh=
o is not our responsability","Hyemafo Gildas","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site, site on Grid.The Tx FME  Fulbert  (654266068) of huawei is informed.=
 Notice that site is impacted by Afanoya II who is not our responsability",=
"yves.djomo@sagemcom.com","426","20-03-2025 01:26:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004615347","S=
hell-Nsimeyong","","20-03-2025 00:28:25","20-03-2025 00:23:21","20-03-2025 =
02:27:39","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed","MINKA NICOLAS","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah Hosiah=
 (674007438/699699694) from Huawei is informed","yves.djomo@sagemcom.com","=
305","20-03-2025 00:28:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004615121","O=
dza","","19-03-2025 23:44:39","19-03-2025 23:39:19","20-03-2025 00:14:07","=
Grid fluctuation, Site went down because gen failed to start due to 01 lack=
 phase No RCp on site // He did a bridge on a Good phase","Albran Byorel","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, Site went down because gen failed to start due to 01 lack p=
hase No RCp on site // He did a bridge on a Good phase","yves.djomo@sagemco=
m.com","321","19-03-2025 23:44:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004614848","B=
iteng-Maetur","","19-03-2025 22:46:17","19-03-2025 22:21:08","20-03-2025 00=
:35:48","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","wilfrie=
d.kameni@sagemcom.com","1511","19-03-2025 22:46:17","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004614827","Men=
dong3","","19-03-2025 22:42:49","19-03-2025 22:38:43","19-03-2025 23:56:29"=
,"Grid outage No space to deploy // Grid power return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage No space to =
deploy // Grid power return","wilfried.kameni@sagemcom.com","247","19-03-20=
25 22:42:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_745","NOCINC0004614774","Okolo Ki=
lombo","","19-03-2025 22:32:40","19-03-2025 22:03:21","19-03-2025 22:35:42"=
,"Grid outage, site went down because gen fails to start due to Gen cable f=
aulty // Grid pwer return","Fabrice Pouakam","Equipment Repair","Passive","=
Infrastructure","Armoured Cable","Grid outage, site went down because gen f=
ails to start due to Gen cable faulty // Grid pwer return","el-dalile@sagem=
com.com","1760","19-03-2025 22:32:40","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004614742","Ngu=
ila","","19-03-2025 22:27:25","19-03-2025 22:17:59","20-03-2025 01:31:39","=
Gen only: Site went down because Gen start and stopped with alarm ""Under-V=
oltage' Unprouven alarm // He Reset the Gen Card and manually start the gen=
","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Gen only: Site went down because Gen start and stopped with alarm ""=
Under-Voltage' Unprouven alarm // He Reset the Gen Card and manually start =
the gen","danick.tchakouani@sagemcom.com","567","19-03-2025 22:27:25","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004614428","N=
YOM 2 IHS","","19-03-2025 21:36:35","19-03-2025 21:34:21","19-03-2025 23:27=
:23","Site went down because CB (80A) tripped in PWC who feeds equipments O=
CM due to load increase// CB put back on","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site=
 went down because CB (80A) tripped in PWC who feeds equipments OCM due to =
load increase// CB put back on","danick.tchakouani@sagemcom.com","136","19-=
03-2025 21:36:35","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004614419","Beh=
ind P T school Yde","","19-03-2025 21:34:49","19-03-2025 21:27:38","20-03-2=
025 08:15:05","Access issue during the Night Grid outage, site went down be=
cause gen fails to start due to gen card faulty // Gen manually started","P=
aul BIBOUM","Access Denial","Lease Or Legal","Landlord Related Issues","Acc=
ess Issue - Land Lord","Access issue during the Night Grid outage, site wen=
t down because gen fails to start due to gen card faulty // Gen manually st=
arted","danick.tchakouani@sagemcom.com","432","19-03-2025 21:34:49","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004614104","MONTEE N=
KONDENGUI","","19-03-2025 20:38:30","19-03-2025 20:30:55","19-03-2025 20:38=
:55","Cascaded Incident from TTO4690217","Albran Byorel","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active//No power issue, site is =
on Grid with Ubaie=3D52,3 V, Eloundou bertrant(652586578) from Huawei is in=
formed","system","293545","19-03-2025 20:38:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004614102","M=
obil-Kondengui","IHS_YND_682","19-03-2025 20:38:01","19-03-2025 20:30:55","=
19-03-2025 20:38:55","Active//No power issue, site is on Grid with Ubaie=3D=
52,3 V, Eloundou bertrant(652586578) from Huawei is informed","","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue, site is on Grid with Ubaie=3D52,3 V, Eloundou ber=
trant(652586578) from Huawei is informed","danick.tchakouani@sagemcom.com",=
"427","19-03-2025 20:38:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004613937","Essomba"=
,"","19-03-2025 20:09:21","19-03-2025 19:55:40","19-03-2025 20:20:40","Casc=
aded Incident from TTO4690004","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due PWC dysfonction // He reset the PWC, grid return","s=
ystem","821","19-03-2025 20:09:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004613936","Tradex-N=
komo","","19-03-2025 20:09:21","19-03-2025 19:55:40","19-03-2025 20:20:40",=
"Cascaded Incident from TTO4690004","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen failed to start due PWC dysfonction // He reset the PWC, grid return",=
"system","821","19-03-2025 20:09:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004613935","Bitoto",=
"","19-03-2025 20:09:20","19-03-2025 19:55:40","19-03-2025 20:20:40","Casca=
ded Incident from TTO4690004","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n failed to start due PWC dysfonction // He reset the PWC, grid return","sy=
stem","820","19-03-2025 20:09:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004613915","B=
iteng","IHS_YND_292, IHS_YND_172, IHS_YND_179","19-03-2025 20:07:23","19-03=
-2025 19:55:40","19-03-2025 20:20:40","Grid outage site went down because G=
en failed to start due PWC dysfonction // He reset the PWC, grid return","M=
ba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","Grid outage site went down because Gen failed to start due PW=
C dysfonction // He reset the PWC, grid return","danick.tchakouani@sagemcom=
.com","705","19-03-2025 20:07:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004613763","Emana Ly=
cee","","19-03-2025 19:48:21","19-03-2025 19:06:18","19-03-2025 19:45:18","=
Cascaded Incident from TTO4689831","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to disjunction=
 of Cb(80A) in PWC // He reamed Cb(80A), site on grid","system","277003","1=
9-03-2025 19:48:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004613754","E=
mana lycee 2","IHS_YND_274","19-03-2025 19:45:48","19-03-2025 19:06:18","19=
-03-2025 19:45:18","Site went down due to disjunction of Cb(80A) in PWC // =
He reamed Cb(80A), site on grid","Fabrice Pouakam","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went dow=
n due to disjunction of Cb(80A) in PWC // He reamed Cb(80A), site on grid",=
"danick.tchakouani@sagemcom.com","2371","19-03-2025 19:45:48","Sagemcom CMR=
"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004613721","SOA=
 VILLAGE","","19-03-2025 19:38:15","19-03-2025 19:35:02","19-03-2025 19:35:=
03","Error","Siligap Boris","Incorrectly Logged Tickets","Error","Error","E=
rror","Error","el-dalile@sagemcom.com","194","19-03-2025 19:38:15","Sagemco=
m CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004613666","Bit=
eng-Maetur","","19-03-2025 19:22:52","19-03-2025 19:15:47","19-03-2025 20:3=
6:47","Grid outage, site went down because gen ran untill fuel shorateg // =
Refueling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage, site went down because gen ran untill fuel shorateg =
// Refueling done","danick.tchakouani@sagemcom.com","427","19-03-2025 19:22=
:52","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004613587","Elo=
umdem stade","","19-03-2025 19:09:51","19-03-2025 18:59:59","19-03-2025 19:=
41:59","Site went down because Gen failed to start due to Grid bad voltage =
and no RCP on site // He bypass the Grid and GEN manually started ","Fanda =
Brice","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Site went down because Gen failed to start due to Grid bad voltage an=
d no RCP on site // He bypass the Grid and GEN manually started ","danick.t=
chakouani@sagemcom.com","593","19-03-2025 19:09:51","Sagemcom CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0004613349","Bas=
tos-BAT","","19-03-2025 18:38:30","19-03-2025 18:18:18","20-03-2025 13:00:2=
0","No power issue on site U=3D54,6v site on grid Tx fme Eloundou of huawei=
 is informed","Mboua Thierry","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,6v =
site on grid Tx fme Eloundou of huawei is informed","el-dalile@sagemcom.com=
","1213","19-03-2025 18:38:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_745","NOCINC0004613265","Okolo Ki=
lombo","","19-03-2025 18:24:56","19-03-2025 18:08:44","19-03-2025 20:24:44"=
,"Grid outage, site went down because gen fails to start due to Gen cable f=
aulty // Gen manualy started with cable backup","Fabrice Pouakam","Equipmen=
t Repair","Passive","Infrastructure","Armoured Cable","Grid outage, site we=
nt down because gen fails to start due to Gen cable faulty // Gen manualy s=
tarted with cable backup","el-dalile@sagemcom.com","973","19-03-2025 18:24:=
56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004613109","O=
dza II OCM","","19-03-2025 18:05:06","19-03-2025 17:58:54","19-03-2025 19:0=
4:46","Grid outage, Site went down due to hybrid system dysfunctionning // =
He reset and Gen started manaully","Albran Byorel","Equipment Repair","Pass=
ive","Hybrid","Hybrid Module","Grid outage, Site went down due to hybrid sy=
stem dysfunctionning // He reset and Gen started manaully","el-dalile@sagem=
com.com","373","19-03-2025 18:05:06","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004613063","Mes=
sassi 2","","19-03-2025 17:57:51","19-03-2025 17:43:36","19-03-2025 20:06:3=
6","Grid outage, site went down because gen start and stopped due to high t=
emp // He added water and manually start the gen","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Grid outage, site went down because gen start and stopped due to hig=
h temp // He added water and manually start the gen","el-dalile@sagemcom.co=
m","857","19-03-2025 17:57:51","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004613018","NKO=
LMEKONG YDE","","19-03-2025 17:47:17","19-03-2025 17:40:00","19-03-2025 17:=
50:30","Grid outage, Site went down before Gen start due to poor backup/ //=
 Gen automatically started","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup/ // Gen automatically started","el-dali=
le@sagemcom.com","439","19-03-2025 17:47:17","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004612940","OTE=
LE MTN","","19-03-2025 17:34:44","19-03-2025 17:26:12","19-03-2025 18:57:25=
","Grid outage, site went down because gen ran untill fuel shorateg // Refu=
eling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran untill fuel shorateg // Refuel=
ing done","el-dalile@sagemcom.com","513","19-03-2025 17:34:44","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0004612723","N=
omayos-IHS","","19-03-2025 17:05:36","19-03-2025 16:58:21","19-03-2025 17:1=
8:21","	Grid outage, site went down due to gen Overload(15KVA, 170A), Felix=
 Zambe IHS is informed // Grid return","Fanda Brice","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","	Grid outage, site went down due to ge=
n Overload(15KVA, 170A), Felix Zambe IHS is informed // Grid return","danic=
k.tchakouani@sagemcom.com","436","19-03-2025 17:05:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004612436","K=
oweit City","","19-03-2025 16:21:46","19-03-2025 16:09:36","19-03-2025 17:3=
6:48","Site went down because Gen failed to start due to Grid bad voltage a=
nd No RCP on site // He bypass the Grid and Gen manually started","Albran B=
yorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Site went down because Gen failed to start due to Grid bad voltage an=
d No RCP on site // He bypass the Grid and Gen manually started","danick.tc=
hakouani@sagemcom.com","731","19-03-2025 16:21:46","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004612382","CRH=
-Etoug-Ebe","","19-03-2025 16:16:58","19-03-2025 16:04:46","19-03-2025 19:0=
5:23","Active//No power issue, Site on Grid Ubai=3D 55,9V The TX Mouhamadou=
 (6144435) from Huawei is informed ","Hyemafo Gildas","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue, Site on Grid Ubai=3D 55,9V The TX Mouhamadou (6144435) from =
Huawei is informed ","el-dalile@sagemcom.com","733","19-03-2025 16:16:58","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0004612306","M=
fou OCM","","19-03-2025 16:05:40","19-03-2025 16:00:21","19-03-2025 18:38:2=
1","Grid outage, site went down because gen ran untill fuel shorateg // Ref=
ueling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage, site went down because gen ran untill fuel shorateg // =
Refueling done","danick.tchakouani@sagemcom.com","320","19-03-2025 16:05:40=
","Sagemcom CMR"
"Closed Complete","Site Down","T0351","IHS_YND_146","NOCINC0004612304","Nsi=
meyong","","19-03-2025 16:05:26","19-03-2025 15:05:02","19-03-2025 15:05:06=
","SITE ON BATERRY","MINKA NICOLAS","Incorrectly Logged Tickets","Error","E=
rror","Error","Incorrectly Logged Tickets","ferot.nongni-djiogap@sagemcom.c=
om","3624","19-03-2025 16:05:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004612160","M=
essa-Carriere OCM","","19-03-2025 15:42:59","19-03-2025 15:34:46","19-03-20=
25 15:56:46","Grid outage, no space to deploy mobile gen // Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy mobile gen // Grid return","danick.tchakouani@sag=
emcom.com","495","19-03-2025 15:42:59","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004612158","MBA=
LNGONG LYCEE","","19-03-2025 15:42:40","19-03-2025 15:36:56","19-03-2025 17=
:25:04","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid return","Fan=
da Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, Site went down because Gen stopped due to overload(9kva, 130A) SS IH=
S Felix Zambe is informed and confirmed // Grid return","ferot.nongni-djiog=
ap@sagemcom.com","345","19-03-2025 15:42:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004612001","M=
EHANDAN","","19-03-2025 15:18:37","19-03-2025 15:15:55","19-03-2025 16:46:5=
5","Site went down due to insufficiency of rectifiers on site SS IHS Pascal=
ine is confirm // He reduced the load","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down due to insufficienc=
y of rectifiers on site SS IHS Pascaline is confirm // He reduced the load"=
,"ferot.nongni-djiogap@sagemcom.com","163","19-03-2025 15:18:37","Sagemcom =
CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004611958","AWA=
E OCM","","19-03-2025 15:14:10","19-03-2025 15:06:59","19-03-2025 15:19:59"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen st=
art automatically","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Gen start automatically","ferot.nongni-djiog=
ap@sagemcom.com","433","19-03-2025 15:14:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004611835","NKONGKAR=
AK","","19-03-2025 14:54:40","19-03-2025 14:41:06","19-03-2025 14:41:07","C=
ascaded Incident from TTO4687552","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active//No power issue, Site=
 on Gen and Ubaie=3D 55,1V The TX Mouhamadou (6144435) from Huawei is infor=
med.","system","278701","19-03-2025 14:54:40","Sagemcom CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0004611822","LOB=
O MTN","IHS_YND_713","19-03-2025 14:53:21","19-03-2025 14:41:06","19-03-202=
5 17:45:07","Active//No power issue, Site on Gen and Ubaie=3D 55,1V The TX =
Mouhamadou (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue, Site on Gen and Ubaie=3D 55,1V The TX Mo=
uhamadou (6144435) from Huawei is informed.","ferot.nongni-djiogap@sagemcom=
.com","737","19-03-2025 14:53:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_201","IHS_YND_368","NOCINC0004611783","O=
tele","IHS_YND_370, IHS_YND_369, IHS_YND_372","19-03-2025 14:48:01","19-03-=
2025 14:38:44","19-03-2025 18:11:44","Grid outage, site went down because g=
en ran untill fuel shorateg // Refueling done","Fanda Brice","Fuel Outage",=
"Passive","Diesel","Diesel Outage","Grid outage, site went down because gen=
 ran untill fuel shorateg // Refueling done
","cedric.tiani@sagemcom.com","558","19-03-2025 14:48:01","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0004611732","Eli=
g Edzoa","","19-03-2025 14:44:21","19-03-2025 14:37:04","19-03-2025 15:24:0=
4","Grid outage, site went down because gen failed to start due to PWC malf=
unction // He reset controller and gen manually started","Delor Telezing","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage, site went down because gen failed to start due to PWC malfunction =
// He reset controller and gen manually started","ferot.nongni-djiogap@sage=
mcom.com","438","19-03-2025 14:44:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004611575","Bondjock=
","","19-03-2025 14:19:51","19-03-2025 14:38:44","19-03-2025 18:11:44","Cas=
caded Incident from TTO4687264 - Cascade Removed From TTO4687264","Fanda Br=
ice","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid o=
utage, site went down because gen ran untill fuel shorateg // Refueling don=
e
","system","278860","19-03-2025 14:19:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004611574","Mbeng","=
","19-03-2025 14:19:50","19-03-2025 14:38:44","19-03-2025 18:11:44","Cascad=
ed Incident from TTO4687264 - Cascade Removed From TTO4687264","Fanda Brice=
","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid outa=
ge, site went down because gen ran untill fuel shorateg // Refueling done
","system","278860","19-03-2025 14:19:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004611570","M=
om","","19-03-2025 14:18:43","19-03-2025 14:38:44","19-03-2025 18:11:44",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid outage, site went down because gen ran untill fuel shorateg // Ref=
ueling done
","cedric.tiani@sagemcom.com","278860","19-03-2025 14:18:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_401","IHS_YND_041","NOCINC0004611474","L=
ycee Leclerc School","","19-03-2025 14:10:30","19-03-2025 13:59:13","19-03-=
2025 19:00:14","No power issue on site,site on Grid with Ubaie=3D52.3 V The=
 Tx Fme Mbah hosiah(674007438) from Huawei is informed. Notice that dysjunc=
tion at OCM Equipment","Paul BIBOUM","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site,sit=
e on Grid with Ubaie=3D52.3 V The Tx Fme Mbah hosiah(674007438) from Huawei=
 is informed. Notice that dysjunction at OCM Equipment","cedric.tiani@sagem=
com.com","678","19-03-2025 14:10:30","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004611062","Nko=
lmvack","","19-03-2025 13:30:05","19-03-2025 13:26:58","19-03-2025 14:26:59=
","Grid outage, Site went down because Gen start and stopped with ""High te=
mps ""alarm // he added water and manually start the Gen","Parker Tchoup","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, Site went down because Gen start and stopped with=
 ""High temps ""alarm // he added water and manually start the Gen","ferot.=
nongni-djiogap@sagemcom.com","188","19-03-2025 13:30:05","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004611040","Ngu=
ila","","19-03-2025 13:24:56","19-03-2025 13:17:39","19-03-2025 14:09:39","=
Grid outage, site went down because Gen start and stopped with  alarm ""Gen=
 under-Voltage' Unproved alarmes // He Reset the Gen Card and manually star=
t the gen","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid outage, site went down because Gen start and stopped w=
ith  alarm ""Gen under-Voltage' Unproved alarmes // He Reset the Gen Card a=
nd manually start the gen","ferot.nongni-djiogap@sagemcom.com","438","19-03=
-2025 13:24:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004610736","N=
koabang Ebolmedjock","","19-03-2025 12:31:43","19-03-2025 11:47:26","19-03-=
2025 12:00:11","ACTIVE//No power issue on site. Site on grid with Ubaie=3D5=
3.5 V. The FME TX Lionel Adjeb /655184876// from huawei is informed","Mba L=
azare Herve","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","ACTIVE//No power issue on site. Site on grid with =
Ubaie=3D53.5 V. The FME TX Lionel Adjeb /655184876// from huawei is informe=
d","cedric.tiani@sagemcom.com","2658","19-03-2025 12:31:43","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004610705","An-=
Marche-Melen","","19-03-2025 12:28:17","19-03-2025 12:27:07","19-03-2025 23=
:25:08","Grid outage, No space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No sp=
ace to deploy MDG // Grid return","cedric.tiani@sagemcom.com","71","19-03-2=
025 12:28:17","Sagemcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004610574","Ron=
d Point Express1114","","19-03-2025 12:00:29","19-03-2025 11:55:12","19-03-=
2025 12:13:07","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup // Gen start automatically","cedric=
.tiani@sagemcom.com","318","19-03-2025 12:00:29","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004609835","Aka=
k-Nkozoa-MTN-IHS","","19-03-2025 11:02:04","19-03-2025 10:55:54","19-03-202=
5 11:29:15","Site went down due to work SS IHS Felix Mbateu and Fabrice/SAG=
EMCOM working on site//End of work","Fabrice Pouakam","Installation Activit=
y","Passive","Planned Activity","Installation Activity","Site went down due=
 to work SS IHS Felix Mbateu and Fabrice/SAGEMCOM working on site//End of w=
ork","ferot.nongni-djiogap@sagemcom.com","372","19-03-2025 11:02:04","Sagem=
com CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0004609757","Ako=
no","","19-03-2025 10:57:18","","","Eneo outage // eneo return ","Fanda Bri=
ce","Warning","Warning","POWER","Warning - Site on Battery","Eneo outage //=
 eneo return ","ferot.nongni-djiogap@sagemcom.com","1211","19-03-2025 10:57=
:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0004609652","A=
bome","","19-03-2025 10:38:28","19-03-2025 10:34:13","19-03-2025 11:56:27",=
"Grid fluctuation, Site went down because gen fails to start due to grid ba=
d voltage,no rcp// He bypasse the Grid and site on Gen","MINKA NICOLAS","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuation, Site went down because gen fails to start due to grid bad vol=
tage,no rcp// He bypasse the Grid and site on Gen","ferot.nongni-djiogap@sa=
gemcom.com","256","19-03-2025 10:38:28","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004609517","Mfo=
u EPC","","19-03-2025 10:13:17","19-03-2025 10:08:07","19-03-2025 16:10:07"=
,"Grid outage, site went down because gen ran untill fuel shorateg // Refue=
ling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran untill fuel shorateg // Re=
fueling done","ferot.nongni-djiogap@sagemcom.com","311","19-03-2025 10:13:1=
7","Sagemcom CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004609445","Nsi=
malen MTN","","19-03-2025 09:57:59","19-03-2025 09:55:52","19-03-2025 10:19=
:39","Grid outage, site went down because Gen failed to start with alarm un=
der-Frequency // He reset the Gen card and Gen manually started","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Under Frequency","Gri=
d outage, site went down because Gen failed to start with alarm under-Frequ=
ency // He reset the Gen card and Gen manually started","ferot.nongni-djiog=
ap@sagemcom.com","128","19-03-2025 09:57:59","Sagemcom CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004609265","Par=
adis Hotel","","19-03-2025 09:24:57","19-03-2025 09:22:53","19-03-2025 19:4=
0:53","Site went down due to work Boris/657100525/Sagemcom is working on si=
te (Installation of MPR) // End of work","Siligap Boris","Installation Acti=
vity","Passive","Planned Activity","Installation Activity","Site went down =
due to work Boris/657100525/Sagemcom is working on site (Installation of MP=
R) // End of work","cedric.tiani@sagemcom.com","124","19-03-2025 09:24:57",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004608925","Nsi=
meyong Terre Rouge","","19-03-2025 08:25:00","19-03-2025 08:24:56","19-03-2=
025 09:27:58","Grid fluctuation,Site went down because Gen failed to start =
due to Grid bad voltage,no rcp on site//He bypassed the Grid and site on GE=
N","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation,Site went down because Gen failed to sta=
rt due to Grid bad voltage,no rcp on site//He bypassed the Grid and site on=
 GEN","ferot.nongni-djiogap@sagemcom.com","5","19-03-2025 08:25:00","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0004608917","Obobogo"=
,"","19-03-2025 08:23:00","19-03-2025 08:17:52","19-03-2025 08:26:40","Grid=
 outage, Site went down before Gen start due to poor backup // Gen started =
automatically","MINKA NICOLAS","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, Site went down before Gen star=
t due to poor backup // Gen started automatically","system","1387","19-03-2=
025 08:23:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004608484","S=
hell-Nsimeyong","","19-03-2025 07:21:49","19-03-2025 07:19:34","19-03-2025 =
07:23:00","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed Uptime   07:23:53 AM. R=
epetitive Issue","MINKA NICOLAS","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue U =3D52=
.1V site on Grid.The FME TX Mbah Hosiah (674007438/699699694) from Huawei i=
s informed Uptime   07:23:53 AM. Repetitive Issue","cedric.tiani@sagemcom.c=
om","136","19-03-2025 07:21:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004607748","M=
ontee-Jouvence-II","","19-03-2025 03:47:58","18-03-2025 20:30:29","19-03-20=
25 12:08:00","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid outage, no space to deploy mobile gen // Grid re=
turn","alexandre.kamal@ihstowers.com","322516","19-03-2025 03:47:58","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0004607746","B=
IYEMASSI NIKI","","19-03-2025 03:46:49","18-03-2025 20:29:40","19-03-2025 1=
2:08:44","Grid outage, site went down down due PWC overloaded (12 kw 250A) =
 Fran=E7ois NDOUNGOU confirmed // Grid power return","Hyemafo Gildas","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid out=
age, site went down down due PWC overloaded (12 kw 250A)  Fran=E7ois NDOUNG=
OU confirmed // Grid power return","alexandre.kamal@ihstowers.com","26230",=
"19-03-2025 03:46:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004607710","Biyemass=
i LAC","","19-03-2025 03:29:00","18-03-2025 20:30:29","19-03-2025 12:08:00"=
,"Cascaded Incident from TTO4681104","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage, no space to deploy mobile gen // =
Grid return","system","322517","19-03-2025 03:29:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004607037","O=
mnisport-Rail","","18-03-2025 23:55:49","18-03-2025 23:53:44","18-03-2025 2=
3:55:53","Site went down due to insuffuciency of rectifier, Bernard Atangan=
a is informed // Added rectifier ongoing, site on grid","Delor Telezing","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went down d=
ue to insuffuciency of rectifier, Bernard Atangana is informed // Added rec=
tifier ongoing, site on grid","yves.djomo@sagemcom.com","152","18-03-2025 2=
3:55:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0004606901","B=
astos Bethesda","","18-03-2025 23:28:00","18-03-2025 23:16:55","19-03-2025 =
00:59:16","Grid outage, site went down because gen failed to start due to b=
attery gen faulty // Gen manually with external battery","Mboua Thierry","E=
quipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outa=
ge, site went down because gen failed to start due to battery gen faulty //=
 Gen manually with external battery","ferot.nongni-djiogap@sagemcom.com","6=
67","18-03-2025 23:28:00","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004606804","Bas=
tos Amb Coree","","18-03-2025 23:10:28","18-03-2025 23:02:22","18-03-2025 2=
3:34:31","Grid outage, No space to deploy MDG // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No s=
pace to deploy MDG // Grid return","yves.djomo@sagemcom.com","487","18-03-2=
025 23:10:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004606774","B=
iteng-Maetur","","18-03-2025 23:05:09","18-03-2025 22:05:55","18-03-2025 22=
:58:20","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the=
 load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen started and stopped due t=
o Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced th=
e load","ferot.nongni-djiogap@sagemcom.com","3556","18-03-2025 23:05:09","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004606762","AWAE OCM=
","","18-03-2025 23:02:31","18-03-2025 22:06:11","18-03-2025 22:56:56","Cas=
caded Incident from TTO4681796","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC dysfonction // He reset the PWC, grid return","=
system","280535","18-03-2025 23:02:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004606763","Essomba"=
,"","18-03-2025 23:02:31","18-03-2025 22:06:11","18-03-2025 22:56:56","Casc=
aded Incident from TTO4681796","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due PWC dysfonction // He reset the PWC, grid return","s=
ystem","280535","18-03-2025 23:02:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004606753","B=
iteng","IHS_YND_292, IHS_YND_173, IHS_YND_179","18-03-2025 22:59:23","18-03=
-2025 22:06:11","18-03-2025 22:56:56","Grid outage site went down because G=
en failed to start due PWC dysfonction // He reset the PWC, grid return","M=
ba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","Grid outage site went down because Gen failed to start due PW=
C dysfonction // He reset the PWC, grid return","ferot.nongni-djiogap@sagem=
com.com","3194","18-03-2025 22:59:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004606720","S=
hell-Nsimeyong","","18-03-2025 22:50:48","18-03-2025 22:47:34","18-03-2025 =
22:50:10","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","ferot.nongni-djiogap@sagemcom.com","195","18-03-2025 22:50:48","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0004606591","A=
n-Marche-Melen","","18-03-2025 22:20:29","18-03-2025 22:18:23","18-03-2025 =
22:51:54","Grid outage, No space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No =
space to deploy MDG // Grid return","yves.djomo@sagemcom.com","127","18-03-=
2025 22:20:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004606525","Accacia =
New","","18-03-2025 22:05:10","18-03-2025 20:30:29","19-03-2025 12:08:00","=
Cascaded Incident from TTO4681104 - Cascade Removed From TTO4681104","","Ca=
scade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage, n=
o space to deploy mobile gen // Grid return","system","322515","18-03-2025 =
22:05:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0004606526","Damas","=
","18-03-2025 22:05:10","18-03-2025 20:30:29","19-03-2025 12:08:00","Impact=
ed by Pond Point Express//Grid outage, no space to deploy mobile gen // Gri=
d return","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage, no space to deploy mobile gen // Grid return","=
system","322515","18-03-2025 22:05:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0004606527","Tamtam W=
eekend","","18-03-2025 22:05:10","18-03-2025 20:30:29","19-03-2025 12:08:00=
","Impacted by Pond Point Express//Grid outage, no space to deploy mobile g=
en // Grid return","Hyemafo Gildas","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, no space to deploy mobile gen // Grid=
 return","system","322516","18-03-2025 22:05:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004606520","B=
riqueterie","","18-03-2025 22:02:50","18-03-2025 21:50:43","18-03-2025 23:3=
3:00","Grid outage, No space to deploy MDG // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spac=
e to deploy MDG // Grid return","yves.djomo@sagemcom.com","728","18-03-2025=
 22:02:50","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004606493","Jou=
vence Mbenda","","18-03-2025 21:58:35","18-03-2025 21:40:31","18-03-2025 22=
:48:40","Grid fluctuation, Site went down because gen fails to start due to=
 grid bad voltage// He bypasse the Grid and site on Gen","Hyemafo Gildas","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, Site went down because gen fails to start due to grid bad v=
oltage// He bypasse the Grid and site on Gen","yves.djomo@sagemcom.com","10=
85","18-03-2025 21:58:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004606430","Emana Ly=
cee","","18-03-2025 21:43:20","18-03-2025 21:34:50","18-03-2025 22:05:24","=
Cascaded Incident from TTO4681391","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to disjunction=
 of Cb(80A) in PWC // He reamed Cb(80A), site on grid","system","275267","1=
8-03-2025 21:43:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004606426","E=
mana lycee 2","IHS_YND_274","18-03-2025 21:42:54","18-03-2025 21:34:50","18=
-03-2025 22:05:24","Site went down due to disjunction of Cb(80A) in PWC // =
He reamed Cb(80A), site on grid","Fabrice Pouakam","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went dow=
n due to disjunction of Cb(80A) in PWC // He reamed Cb(80A), site on grid",=
"yves.djomo@sagemcom.com","485","18-03-2025 21:42:54","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0004606415","Eli=
g Edzoa","","18-03-2025 21:40:40","18-03-2025 21:31:33","18-03-2025 22:48:0=
9","Grid outage, site went down because gen failed to start due to PWC malf=
unction // He reset controller and gen manually started","Delor Telezing","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage, site went down because gen failed to start due to PWC malfunction =
// He reset controller and gen manually started","yves.djomo@sagemcom.com",=
"548","18-03-2025 21:40:40","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004606355","Nom=
ayos montee Meche","","18-03-2025 21:28:21","18-03-2025 21:12:09","18-03-20=
25 21:58:49","Grid outage, site went down because gen failed to start // Gr=
id return(investigation ongoing)","Fanda Brice","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because ge=
n failed to start // Grid return(investigation ongoing)","el-dalile@sagemco=
m.com","21628","18-03-2025 21:28:21","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004606344","Bri=
quetterie","","18-03-2025 21:26:19","18-03-2025 21:18:08","18-03-2025 23:33=
:12","Grid outage, No space to deploy MDG // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space=
 to deploy MDG // Grid return","el-dalile@sagemcom.com","492","18-03-2025 2=
1:26:19","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004606287","ODZ=
A MINKAN EDIBI ASSI","","18-03-2025 21:12:01","18-03-2025 21:03:51","18-03-=
2025 22:52:43","Site went down due to insufficiency of rectifiers, Pascalin=
e IHS is informed // Added rectifier ongoing","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down due to insuf=
ficiency of rectifiers, Pascaline IHS is informed // Added rectifier ongoin=
g","el-dalile@sagemcom.com","492","18-03-2025 21:12:01","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004606281","Eko=
umdoum OCM","","18-03-2025 21:10:51","18-03-2025 21:04:36","19-03-2025 08:5=
6:59","	Grid outage, site went down due to Gen overload(20kva,280 A) IHS SS=
 Pascaline is informed and confirmed//Grid return","Albran Byorel","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","	Grid outage, site went =
down due to Gen overload(20kva,280 A) IHS SS Pascaline is informed and conf=
irmed//Grid return","el-dalile@sagemcom.com","375","18-03-2025 21:10:51","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0004606189","R=
d-Pt-Express","IHS_YND_562, IHS_YND_166, IHS_YND_151, IHS_YND_546, IHS_YND_=
518","18-03-2025 20:55:32","18-03-2025 20:30:29","19-03-2025 12:08:00","Gri=
d outage, no space to deploy mobile gen // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage, no space t=
o deploy mobile gen // Grid return","yves.djomo@sagemcom.com","1504","18-03=
-2025 20:55:32","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004606136","Aha=
la Echangeur","","18-03-2025 20:48:34","18-03-2025 20:43:10","18-03-2025 20=
:50:59","Site went down because gen failed to start due to 01 lack phase  /=
/ He did a bridge on a Good phase","MINKA NICOLAS","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Site went down because ge=
n failed to start due to 01 lack phase  // He did a bridge on a Good phase"=
,"yves.djomo@sagemcom.com","324","18-03-2025 20:48:34","Sagemcom CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0004605940","EKI=
E","","18-03-2025 20:13:55","18-03-2025 20:07:43","18-03-2025 21:38:59","Si=
te went down because gen failed to start due to grid bad voltage and no RCP=
 // Gen manually started","Albran Byorel","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Site went down because gen failed =
to start due to grid bad voltage and no RCP // Gen manually started","el-da=
lile@sagemcom.com","372","18-03-2025 20:13:55","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0004605904","Bit=
oto","","18-03-2025 20:09:57","18-03-2025 19:21:35","18-03-2025 22:56:56","=
Grid outage site went down because Gen failed to start due PWC dysfonction =
// He reset the PWC, grid return","Mba Lazare Herve","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage site went down becaus=
e Gen failed to start due PWC dysfonction // He reset the PWC, grid return"=
,"el-dalile@sagemcom.com","2903","18-03-2025 20:09:57","Sagemcom CMR"
"Closed Complete","Site Down","T0526","IHS_YND_088","NOCINC0004605776","Elo=
bi Mokolo","","18-03-2025 19:51:55","18-03-2025 19:50:50","18-03-2025 20:23=
:11","Grid fluctuation, Site went down because gen fails to start due to gr=
id bad voltage,no rcp on site// He bypasse the Grid and site on Gen","Mboua=
 Thierry","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation, Site went down because gen fails to start due to=
 grid bad voltage,no rcp on site// He bypasse the Grid and site on Gen","yv=
es.djomo@sagemcom.com","66","18-03-2025 19:51:55","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004605733","AKA=
K Nkozoa","","18-03-2025 19:47:07","18-03-2025 19:38:01","18-03-2025 20:31:=
55","Grid outage, site went down gen start and stopped with alarm over curr=
ent // He reset gen card and gen manually","Fabrice Pouakam","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went do=
wn gen start and stopped with alarm over current // He reset gen card and g=
en manually","yves.djomo@sagemcom.com","547","18-03-2025 19:47:07","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004605631","O=
LAMA","","18-03-2025 19:27:30","18-03-2025 18:49:25","18-03-2025 20:31:40",=
"Active//No power issue on site, Site on Battery, UBAIE=3D51.1V.( the start=
ing threshold ubaie=3D47.5 VThe TX FME Henri (699949693) from Huawei is inf=
ormed","Fanda Brice","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active//No power issue on site, Site on Ba=
ttery, UBAIE=3D51.1V.( the starting threshold ubaie=3D47.5 VThe TX FME Henr=
i (699949693) from Huawei is informed","yves.djomo@sagemcom.com","2286","18=
-03-2025 19:27:30","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004605591","Bri=
quetterie","","18-03-2025 19:20:20","18-03-2025 19:04:08","18-03-2025 19:51=
:00","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space=
 to deploy a MDG//Grid Restored","yves.djomo@sagemcom.com","973","18-03-202=
5 19:20:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004605583","ODZA MIN=
KAN EDIBI ASSI","","18-03-2025 19:18:51","18-03-2025 19:03:14","18-03-2025 =
19:33:27","Cascaded Incident from TTO4680362","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down due to li=
ghtning (04/04 rectifiers faulty, PSC 3, lightning arrester and 02 relay 22=
0 V faulty) // He replaced 03 rectifers, Site on Gen ","system","269975","1=
8-03-2025 19:18:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004605582","Mehanda =
1","","18-03-2025 19:18:51","18-03-2025 19:03:14","18-03-2025 19:33:27","Ca=
scaded Incident from TTO4680362","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to lightning (04/0=
4 rectifiers faulty, PSC 3, lightning arrester and 02 relay 220 V faulty) /=
/ He replaced 03 rectifers, Site on Gen ","system","269976","18-03-2025 19:=
18:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_328","NOCINC0004605581","Nsimalen=
 MTN","","18-03-2025 19:18:50","18-03-2025 19:03:14","18-03-2025 19:33:27",=
"Cascaded Incident from TTO4680362","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to lightning (0=
4/04 rectifiers faulty, PSC 3, lightning arrester and 02 relay 220 V faulty=
) // He replaced 03 rectifers, Site on Gen ","system","269975","18-03-2025 =
19:18:50","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004605534","Nko=
lnda","IHS_YND_328, IHS_YND_746, IHS_YND_715, IHS_YND_749","18-03-2025 19:1=
4:22","18-03-2025 19:03:14","18-03-2025 19:57:27","Site went down due to li=
ghtning (04/04 rectifiers faulty, PSC 3, lightning arrester and 02 relay 22=
0 V faulty) // He replaced 03 rectifers, Site on Gen ","Albran Byorel","For=
ce Majeure","Natural Disaster","Thunderstrike","Equipment Damaged","Site we=
nt down due to lightning (04/04 rectifiers faulty, PSC 3, lightning arreste=
r and 02 relay 220 V faulty) // He replaced 03 rectifers, Site on Gen ","el=
-dalile@sagemcom.com","669","18-03-2025 19:14:22","Sagemcom CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004605502","Odz=
a Minkan IHS","","18-03-2025 19:07:34","18-03-2025 19:03:14","18-03-2025 19=
:33:27","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Site went down due to lightning (04/04 rectifiers faulty, P=
SC 3, lightning arrester and 02 relay 220 V faulty) // He replaced 03 recti=
fers, Site on Gen ","el-dalile@sagemcom.com","269977","18-03-2025 19:07:34"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004605442","E=
koumdoum OCM","","18-03-2025 18:56:54","18-03-2025 18:50:41","18-03-2025 20=
:52:37","Grid outage, site went down due to Gen overload(20kva,280 A) IHS S=
S Pascaline is informed and confirmed // Grid return","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site wen=
t down due to Gen overload(20kva,280 A) IHS SS Pascaline is informed and co=
nfirmed // Grid return","el-dalile@sagemcom.com","437","18-03-2025 18:56:54=
","Sagemcom CMR"
"Closed Complete","Site Down","T1577","IHS_YND_086","NOCINC0004605355","POL=
YCLINIQUE TSINGA","","18-03-2025 18:36:53","18-03-2025 18:27:46","18-03-202=
5 18:43:07","Site went down due to Insufficience of rectifers SS IHS Bernar=
d ATANGANA is informed and Confirmed it// He reduice the Load and Site IS O=
N Grid","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down due to Insufficience of rectifers SS IHS Bernard A=
TANGANA is informed and Confirmed it// He reduice the Load and Site IS ON G=
rid","el-dalile@sagemcom.com","548","18-03-2025 18:36:53","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0004605351","Fou=
da rue des g=E9n=E9raux","","18-03-2025 18:36:08","18-03-2025 18:26:54","18=
-03-2025 19:02:27","Grid outage, Site went down because Gen failed to start=
 due to battery Gen discharged// He started Gen with external battery (inve=
stigation ongoing)","Delor Telezing","Equipment Repair","Passive","ACDG Gen=
","ACDG - Generator Battery","Grid outage, Site went down because Gen faile=
d to start due to battery Gen discharged// He started Gen with external bat=
tery (investigation ongoing)","el-dalile@sagemcom.com","555","18-03-2025 18=
:36:08","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004605196","Ngu=
ila","","18-03-2025 18:10:11","18-03-2025 18:01:02","18-03-2025 19:03:27","=
Grid outage, site went down because gen start and stopped due to high temp =
// He added water and manually start the gen","Parker Tchoup","Equipment Re=
pair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue",=
"Grid outage, site went down because gen start and stopped due to high temp=
 // He added water and manually start the gen","el-dalile@sagemcom.com","55=
0","18-03-2025 18:10:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004605161","SOA VILL=
AGE","","18-03-2025 18:04:41","18-03-2025 17:52:29","18-03-2025 18:16:57","=
Cascaded Incident from TTO4679907","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen failed due to fuse of contactor gen faulty// He made a brigde of fuse,=
 Site on gen","system","267131","18-03-2025 18:04:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004605160","Mvog-Eba=
nda","","18-03-2025 18:04:41","18-03-2025 17:52:29","18-03-2025 18:16:57","=
Cascaded Incident from TTO4679907","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen failed due to fuse of contactor gen faulty// He made a brigde of fuse,=
 Site on gen","system","267132","18-03-2025 18:04:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0004605163","Nkolfoul=
ou Tsinga Village","","18-03-2025 18:04:41","18-03-2025 17:52:29","18-03-20=
25 18:16:57","Cascaded Incident from TTO4679907","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, Site wen=
t down because Gen failed due to fuse of contactor gen faulty// He made a b=
rigde of fuse, Site on gen","system","267131","18-03-2025 18:04:41","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_758","NOCINC0004605162","Nkolfoul=
ou CSD MTN","","18-03-2025 18:04:41","18-03-2025 17:52:29","18-03-2025 18:1=
6:57","Cascaded Incident from TTO4679907","Siligap Boris","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down =
because Gen failed due to fuse of contactor gen faulty// He made a brigde o=
f fuse, Site on gen","system","267131","18-03-2025 18:04:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0004605159","FOUGEROL=
E","","18-03-2025 18:04:40","18-03-2025 17:52:29","18-03-2025 18:16:57","Ca=
scaded Incident from TTO4679907","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down because G=
en failed due to fuse of contactor gen faulty// He made a brigde of fuse, S=
ite on gen","system","267130","18-03-2025 18:04:40","Sagemcom CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0004605147","Nko=
lfoulou 2","IHS_YND_561, IHS_YND_269, IHS_YND_323, IHS_YND_758, IHS_YND_296=
, IHS_YND_759","18-03-2025 18:01:41","18-03-2025 17:52:29","18-03-2025 18:1=
6:57","Grid outage, Site went down because Gen failed due to fuse of contac=
tor gen faulty// He made a brigde of fuse, Site on gen","Siligap Boris","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, =
Site went down because Gen failed due to fuse of contactor gen faulty// He =
made a brigde of fuse, Site on gen","el-dalile@sagemcom.com","553","18-03-2=
025 18:01:41","Sagemcom CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004605142","Nko=
lfoulou","","18-03-2025 18:00:31","18-03-2025 17:52:29","18-03-2025 18:16:5=
7","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage, Site went down because Gen failed due to fuse of co=
ntactor gen faulty// He made a brigde of fuse, Site on gen","el-dalile@sage=
mcom.com","267130","18-03-2025 18:00:31","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004605053","Mon=
tee Jouvence","","18-03-2025 17:45:26","18-03-2025 17:32:57","18-03-2025 18=
:42:24","Grid outage, Site went down before Gen start due to poor backup //=
 Gen Manually started","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Gen Manually started","el-dalile@sagemcom.=
com","750","18-03-2025 17:45:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004605023","C=
omplexe-BEAC","","18-03-2025 17:42:06","18-03-2025 17:31:02","18-03-2025 18=
:59:02","Grid outage, site went down before gen start due to poor battery b=
ackup and the Cb(100A) of battery dysjuncted  // Gen start automatically an=
d reamed  the Cb","Albran Byorel","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, site went down before gen s=
tart due to poor battery backup and the Cb(100A) of battery dysjuncted  // =
Gen start automatically and reamed  the Cb","yves.djomo@sagemcom.com","665"=
,"18-03-2025 17:42:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004605007","S=
tade-Abega","","18-03-2025 17:37:53","18-03-2025 17:17:40","18-03-2025 17:4=
9:14","Grid outage site went down because Gen failed to start due PWC dysfo=
nction // Grid power return","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Grid outage site went down bec=
ause Gen failed to start due PWC dysfonction // Grid power return","el-dali=
le@sagemcom.com","1214","18-03-2025 17:37:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004605002","Accacia =
New","","18-03-2025 17:37:10","18-03-2025 17:17:25","18-03-2025 19:36:48","=
Cascaded Incident from TTO4679725","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage, Site went down before Gen start due=
 to poor backup // Gen Manually started","system","276162","18-03-2025 17:3=
7:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0004605003","Damas","=
","18-03-2025 17:37:10","18-03-2025 17:17:25","18-03-2025 19:36:48","Cascad=
ed Incident from TTO4679725","MINKA NICOLAS","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down before Gen st=
art due to poor backup // Gen Manually started","system","276162","18-03-20=
25 17:37:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004604986","T=
amtam Weekend","IHS_YND_562, IHS_YND_166","18-03-2025 17:34:33","18-03-2025=
 17:17:25","18-03-2025 19:36:48","Grid outage, Site went down before Gen st=
art due to poor backup // Gen Manually started","Hyemafo Gildas","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge, Site went down before Gen start due to poor backup // Gen Manually star=
ted","el-dalile@sagemcom.com","1029","18-03-2025 17:34:33","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0004604927","Bit=
oto","","18-03-2025 17:24:41","18-03-2025 17:19:29","18-03-2025 17:25:34","=
Grid outage, Site went down before Gen start due to poor backup // Gen star=
t automatically","Mba Lazare Herve","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen start automatically","el-dalile@sagemcom.c=
om","313","18-03-2025 17:24:41","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0004604913","Bit=
eng","","18-03-2025 17:22:57","18-03-2025 17:14:47","18-03-2025 17:49:54","=
Grid outage site went down because Gen failed to start due PWC dysfonction =
// Grid power return","Mba Lazare Herve","Equipment Repair","Passive","Rect=
ifier","Rectifier Module Overloaded","Grid outage site went down because Ge=
n failed to start due PWC dysfonction // Grid power return","el-dalile@sage=
mcom.com","491","18-03-2025 17:22:57","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004604904","Com=
plex Beac II","","18-03-2025 17:21:50","18-03-2025 17:13:36","18-03-2025 17=
:39:55","Grid outage site went down because Gen failed to start due to Gen =
card faulty // Gen Manually Started","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage site went down becaus=
e Gen failed to start due to Gen card faulty // Gen Manually Started","el-d=
alile@sagemcom.com","496","18-03-2025 17:21:50","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004604895","Nko=
ulou Carriere carrefourt","","18-03-2025 17:20:27","18-03-2025 17:13:16","1=
8-03-2025 17:52:04","Grid outage, site went down because due to Gen overloa=
d(20kva,310 A) IHS SS Alphonse is informed// Grid power return","Mba Lazare=
 Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, site went down because due to Gen overload(20kva,310 A) IHS SS Alphons=
e is informed// Grid power return","el-dalile@sagemcom.com","432","18-03-20=
25 17:20:27","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004604888","AWA=
E OCM","","18-03-2025 17:19:15","18-03-2025 17:13:02","18-03-2025 17:23:37"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen st=
art automatically","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Gen start automatically","el-dalile@sagemcom=
.com","375","18-03-2025 17:19:15","Sagemcom CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004604875","NTE=
MASSI","","18-03-2025 17:17:56","18-03-2025 17:12:47","18-03-2025 17:34:39"=
,"Grid outage site went down because Gen failed to start due to Gen card fa=
ulty // Gen Manually Started","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start due to Gen card faulty // Gen Manually Started","el-dalile@=
sagemcom.com","310","18-03-2025 17:17:56","Sagemcom CMR"
"Closed Complete","Site Down","T2818","IHS_YND_527","NOCINC0004604869","Odz=
a II OCM","","18-03-2025 17:16:57","18-03-2025 17:11:40","19-03-2025 00:07:=
42","Site went down because (ATS, ENEO meter, Gen card, static charger, Cb =
of grid) faulty impacted by lightning  // Gen manually started, Power issue=
 resolved at OCM but remains down at MTN LIONEL STEEVE(","Albran Byorel","F=
orce Majeure","Natural Disaster","Thunderstrike","Equipment Damaged","Site =
went down because (ATS, ENEO meter, Gen card, static charger, Cb of grid) f=
aulty impacted by lightning  // Gen manually started, Power issue resolved =
at OCM but remains down at MTN LIONEL STEEVE(6655184876) from Huawei is inf=
ormed","el-dalile@sagemcom.com","318","18-03-2025 17:16:57","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004604860","ETO=
UDI Entree du palais","","18-03-2025 17:15:34","18-03-2025 17:10:21","18-03=
-2025 17:16:34","Grid outage, Site went down before Gen start due to poor b=
ackup // Gen started automatically","Fabrice Pouakam","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site we=
nt down before Gen start due to poor backup // Gen started automatically","=
el-dalile@sagemcom.com","314","18-03-2025 17:15:34","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004604835","ELO=
UMDEM CARRIERE","","18-03-2025 17:11:58","18-03-2025 16:59:40","18-03-2025 =
17:34:40","Grid outage, site went down because gen failed to start due to g=
en contactor dysfonction  // Grid power return","Fanda Brice","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, site went =
down because gen failed to start due to gen contactor dysfonction  // Grid =
power return","el-dalile@sagemcom.com","740","18-03-2025 17:11:58","Sagemco=
m CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004604830","Men=
dong3","","18-03-2025 17:10:09","18-03-2025 17:00:58","18-03-2025 17:32:43"=
,"Grid outage no space to deploy a MDG // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage no space to =
deploy a MDG // Grid return","el-dalile@sagemcom.com","552","18-03-2025 17:=
10:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004604822","K=
oweit City","","18-03-2025 17:08:03","18-03-2025 16:56:51","18-03-2025 18:5=
5:19","Grid outage, Site went down because Gen started and stopped with ""L=
ow fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, Site went down because Gen started and stopped with ""Low =
fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","el-=
dalile@sagemcom.com","673","18-03-2025 17:08:03","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004604815","MEF=
OU ASSI","","18-03-2025 17:06:50","18-03-2025 17:01:46","18-03-2025 17:07:3=
3","Active// No power issue on site Ubaie=3D51.8V site On Grid.The Tx FME F=
ulbert (654266068) of Huawei is informed.","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue on site Ubaie=3D51.8V site On Grid.The Tx FME Fulbert (65=
4266068) of Huawei is informed.","yves.djomo@sagemcom.com","306","18-03-202=
5 17:06:50","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004604809","Mes=
sassi 2","","18-03-2025 17:05:54","18-03-2025 17:01:43","18-03-2025 17:52:5=
3","Grid outage site went down because Gen failed to start // Grid power re=
turn (Investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen=
 failed to start // Grid power return (Investigation ongoing)","el-dalile@s=
agemcom.com","252","18-03-2025 17:05:54","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004604808","Jou=
vence Mbenda","","18-03-2025 17:05:49","18-03-2025 16:39:44","18-03-2025 19=
:13:41","Grid outage, site went down because gen ran until fuel shortage //=
 Refueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage, site went down because gen ran until fuel shortage //=
 Refueling done","yves.djomo@sagemcom.com","1565","18-03-2025 17:05:49","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004604790","B=
iyemassi LAC","","18-03-2025 17:03:53","18-03-2025 16:01:48","18-03-2025 18=
:21:51","Grid outage ,no space to deploy mobile gen //Grid power restored",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage ,no space to deploy mobile gen //Grid power restored","yves.djomo@s=
agemcom.com","3726","18-03-2025 17:03:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004604779","B=
arriere","","18-03-2025 17:02:16","18-03-2025 17:00:13","18-03-2025 17:34:4=
4","Site went down because Gen overload(20kva,400 A) IHS SS Felix Zambe is =
informed and confirmed // Grid power return","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Site went down because Gen ov=
erload(20kva,400 A) IHS SS Felix Zambe is informed and confirmed // Grid po=
wer return","yves.djomo@sagemcom.com","124","18-03-2025 17:02:16","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004604746","M=
ontee-Des-Soeurs","","18-03-2025 16:56:45","18-03-2025 16:41:40","18-03-202=
5 18:10:35","Grid outage, Site went down before Gen start due to poor backu=
p // Gen Manually started","Hyemafo Gildas","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup // Gen Manually started","yves.djomo@sage=
mcom.com","906","18-03-2025 16:56:45","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004604740","Mon=
tee-Jouvence-II","","18-03-2025 16:55:34","18-03-2025 16:45:40","18-03-2025=
 19:08:39","Grid outage, Site went down because Gen overload (15kva, 250A) =
SS IHS Felix Zambe is informed // GRid power return","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen overload (15kva, 250A) SS IHS Felix Zambe is informed //=
 GRid power return","yves.djomo@sagemcom.com","595","18-03-2025 16:55:34","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004604643","M=
vog-Manga","","18-03-2025 16:40:40","18-03-2025 16:30:56","18-03-2025 17:02=
:45","Grid outage, site went down because gen failed to start due to gen ca=
rd malfunction // He reset gen card and gen manually started","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, site went down because gen failed to start due to gen card malfunction=
 // He reset gen card and gen manually started","el-dalile@sagemcom.com","5=
86","18-03-2025 16:40:40","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004604635","Ebo=
go","","18-03-2025 16:39:02","18-03-2025 16:28:58","18-03-2025 17:01:38","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed automatically","Siligap Boris","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Gen started automatically","el-dalile@sagemcom.c=
om","605","18-03-2025 16:39:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004604619","M=
ini-Ferme","","18-03-2025 16:36:45","18-03-2025 16:23:34","19-03-2025 00:07=
:27","Grid outage.no space to deploy mobile gen // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deploy mobile gen // Grid return","el-dalile@sagemcom.com","792","=
18-03-2025 16:36:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004604591","S=
OA UNIVERSITY STADIUM","","18-03-2025 16:33:38","18-03-2025 16:18:29","18-0=
3-2025 20:45:01","No power issue, site is on Gen with Ubaie=3D51.2V,TX FME =
Julien(693095849) from Huawei is informed","Siligap Boris","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue, site is on Gen with Ubaie=3D51.2V,TX FME Julien(693095849) from=
 Huawei is informed","el-dalile@sagemcom.com","910","18-03-2025 16:33:38","=
Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004604525","NKO=
MEKUI OCM","","18-03-2025 16:24:06","18-03-2025 16:21:59","18-03-2025 16:22=
:22","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted b=
y Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted =
by Mbankolo Camtel and not managing by IHS","el-dalile@sagemcom.com","128",=
"18-03-2025 16:24:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0004604454","S=
ous Prefecture","","18-03-2025 16:15:06","18-03-2025 16:11:02","18-03-2025 =
19:13:14","ACTIVE//No power issue site on Gen Ubaie =3D53.7 V, The tx Huawe=
i Fulbert (654266068) is working on site (swapp ODU)","Fanda Brice","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","ACTIVE//No power issue site on Gen Ubaie =3D53.7 V, The tx Huawei Fulb=
ert (654266068) is working on site (swapp ODU)","yves.djomo@sagemcom.com","=
245","18-03-2025 16:15:06","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004604439","BIY=
EMASSI NIKI","","18-03-2025 16:12:24","18-03-2025 16:04:16","18-03-2025 18:=
22:22","Grid outage, site went down down due PWC overloaded (12 kw 250A)  F=
ran=E7ois NDOUNGOU confirmed // Gri power return","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went d=
own down due PWC overloaded (12 kw 250A)  Fran=E7ois NDOUNGOU confirmed // =
Gri power return","el-dalile@sagemcom.com","489","18-03-2025 16:12:24","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_745","NOCINC0004604435","Okolo Ki=
lombo","","18-03-2025 16:11:29","18-03-2025 16:06:22","18-03-2025 17:24:31"=
,"Grid outage, site went down because gen fails to start due to Gen cable f=
aulty // Gen manualy started with cable backup","Fabrice Pouakam","Equipmen=
t Repair","Passive","Infrastructure","Armoured Cable","Grid outage, site we=
nt down because gen fails to start due to Gen cable faulty // Gen manualy s=
tarted with cable backup","yves.djomo@sagemcom.com","307","18-03-2025 16:11=
:29","Sagemcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004604430","Ron=
d Point Express1114","","18-03-2025 16:10:28","18-03-2025 16:02:15","18-03-=
2025 16:10:27","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Gen started automatically","el=
-dalile@sagemcom.com","493","18-03-2025 16:10:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0004604380","M=
volye-New","","18-03-2025 15:58:42","18-03-2025 15:50:35","18-03-2025 19:55=
:29","No power issue on site,site on Grid with Ubaie=3D51.3 V The Tx Fme Mb=
ah hosiah(674007438) from Huawei is informed","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site,site on Grid with Ubaie=3D51.3 V The Tx Fme Mbah hosiah(674007438)=
 from Huawei is informed","el-dalile@sagemcom.com","488","18-03-2025 15:58:=
42","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004604246","Bit=
eng-Maetur","","18-03-2025 15:34:20","18-03-2025 15:12:13","18-03-2025 16:3=
3:56","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the l=
oad","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, Site went down because Gen started and stopped due to =
Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the =
load","yves.djomo@sagemcom.com","1329","18-03-2025 15:34:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_143","NOCINC0004604036","Byemassi=
 Carrefour","","18-03-2025 15:03:10","18-03-2025 14:55:51","18-03-2025 14:5=
8:23","Cascaded Incident from TTO4678579","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen failed to start due to Gen battery discharged // Gen manually star=
ted with external battery ( deep investiguetion ongoing)","system","263072"=
,"18-03-2025 15:03:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_747","NOCINC0004604037","Akok Ndo=
e Yde","","18-03-2025 15:03:10","18-03-2025 14:55:51","18-03-2025 14:58:23"=
,"Cascaded Incident from TTO4678579","Hyemafo Gildas","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage site went down becau=
se Gen failed to start due to Gen battery discharged // Gen manually starte=
d with external battery ( deep investiguetion ongoing)","system","263071","=
18-03-2025 15:03:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_741","NOCINC0004604035","Mvog Bet=
si Hospital","","18-03-2025 15:03:10","18-03-2025 14:55:51","18-03-2025 14:=
58:23","Cascaded Incident from TTO4678579","Hyemafo Gildas","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage site went down=
 because Gen failed to start due to Gen battery discharged // Gen manually =
started with external battery ( deep investiguetion ongoing)","system","263=
071","18-03-2025 15:03:10","Sagemcom CMR"
"Closed Complete","Site Down","T0370","IHS_YND_227","NOCINC0004604010","Mvo=
g Betsi","IHS_YND_741, IHS_YND_143, IHS_YND_747","18-03-2025 15:00:15","18-=
03-2025 14:55:51","18-03-2025 15:01:14","Grid outage site went down because=
 Gen failed to start due to Gen battery discharged // Gen manually started =
with external battery ( deep investiguetion ongoing)","Hyemafo Gildas","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage=
 site went down because Gen failed to start due to Gen battery discharged /=
/ Gen manually started with external battery ( deep investiguetion ongoing)=
","el-dalile@sagemcom.com","265","18-03-2025 15:00:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0004603974","N=
ew-Marche-Melen","","18-03-2025 14:54:21","18-03-2025 14:05:04","18-03-2025=
 14:10:46","No power issue on site U=3D53,8v site on Grid Tx fme Mohamadou =
of huawei is informed	","Paul BIBOUM","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53,8v site on Grid Tx fme Mohamadou of huawei is informed	","el-dalile@s=
agemcom.com","2958","18-03-2025 14:54:21","Sagemcom CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0004603886","Eto=
ug ebe Meweulo","","18-03-2025 14:48:13","18-03-2025 14:45:53","18-03-2025 =
16:44:46","Grid outage.gen ran until fuel shortage//Refueling done","Hyemaf=
o Gildas","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen=
 ran until fuel shortage//Refueling done","el-dalile@sagemcom.com","141","1=
8-03-2025 14:48:13","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004603750","Nko=
lbisson usines des eaux 2","","18-03-2025 14:34:59","18-03-2025 14:30:48","=
18-03-2025 15:20:31","Grid Outage Site went down because Gen Overload (12.5=
KVA, 275A) SS IHS Felix Pascaline confirmed// He reduiced The load and Manu=
ally Started the Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid Outage Site went down because Gen Ove=
rload (12.5KVA, 275A) SS IHS Felix Pascaline confirmed// He reduiced The lo=
ad and Manually Started the Gen","el-dalile@sagemcom.com","253","18-03-2025=
 14:34:59","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004603584","An-=
Marche-Melen","","18-03-2025 14:13:10","18-03-2025 14:05:59","18-03-2025 17=
:07:24","Grid outage ,no space to deploy mobile gen //Grid power restored",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage ,no space to deploy mobile gen //Grid power restored
","danick.tchakouani@sagemcom.com","432","18-03-2025 14:13:10","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004603571","Tradex-N=
komo","","18-03-2025 14:10:10","18-03-2025 13:59:27","18-03-2025 14:57:30",=
"Cascaded Incident from TTO4678062","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen failed to start due PWC dysfonction // He reset the PWC and Gen manual=
ly started","system","266701","18-03-2025 14:10:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004603570","Bitoto",=
"","18-03-2025 14:10:10","18-03-2025 13:59:27","18-03-2025 14:57:30","Casca=
ded Incident from TTO4678062","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n failed to start due PWC dysfonction // He reset the PWC and Gen manually =
started","system","266701","18-03-2025 14:10:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004603572","AWAE OCM=
","","18-03-2025 14:10:10","18-03-2025 13:59:27","18-03-2025 14:57:30","Cas=
caded Incident from TTO4678062","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC dysfonction // He reset the PWC and Gen manuall=
y started","system","266701","18-03-2025 14:10:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004603551","B=
iteng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179, IHS_YND_249","1=
8-03-2025 14:06:43","18-03-2025 13:59:27","18-03-2025 14:57:30","Grid outag=
e site went down because Gen failed to start due PWC dysfonction // He rese=
t the PWC and Gen manually started","Mba Lazare Herve","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid outage site went d=
own because Gen failed to start due PWC dysfonction // He reset the PWC and=
 Gen manually started","danick.tchakouani@sagemcom.com","437","18-03-2025 1=
4:06:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004603520","E=
ssomba","","18-03-2025 14:02:41","18-03-2025 13:59:27","18-03-2025 14:57:30=
","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage site went down because Gen failed to start due PWC=
 dysfonction // He reset the PWC and Gen manually started","mariam.tchonang=
@sagemcom.com","266702","18-03-2025 14:02:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004603476","B=
iteng-Maetur","","18-03-2025 13:59:03","18-03-2025 13:59:27","18-03-2025 14=
:54:18","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage site went down because Gen failed to start d=
ue PWC dysfonction // He reset the PWC and Gen manually started","danick.tc=
hakouani@sagemcom.com","266702","18-03-2025 13:59:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004603358","O=
lembe-Terminus","","18-03-2025 13:36:21","18-03-2025 13:27:06","18-03-2025 =
14:39:36","Grid outage, site went down because gen start and stopped due to=
 high temp caused by by pierced radator // He added water and manually star=
t the gen(Radiator to be repaired)","Fabrice Pouakam","Equipment Repair","P=
assive","ACDG Gen","ACDG - Radiator Leakage","Grid outage, site went down b=
ecause gen start and stopped due to high temp caused by by pierced radator =
// He added water and manually start the gen(Radiator to be repaired)","mar=
iam.tchonang@sagemcom.com","557","18-03-2025 13:36:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0004603231","M=
volye-New","","18-03-2025 13:22:08","18-03-2025 12:12:47","18-03-2025 13:25=
:48","No power issue on site,site on Grid with Ubaie=3D51.6 V The Tx Fme Mb=
ah hosiah(674007438) from Huawei is informed","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site,site on Grid with Ubaie=3D51.6 V The Tx Fme Mbah hosiah(674007438)=
 from Huawei is informed","mariam.tchonang@sagemcom.com","4162","18-03-2025=
 13:22:08","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004603149","Jou=
vence Mbenda","","18-03-2025 13:09:59","18-03-2025 13:01:41","18-03-2025 15=
:20:12","Grid fluctuation, site went down because Gen failed to start due t=
o grid bad voltage No Rcp // Grid stabilized","Hyemafo Gildas","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion, site went down because Gen failed to start due to grid bad voltage No =
Rcp // Grid stabilized","danick.tchakouani@sagemcom.com","499","18-03-2025 =
13:09:59","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004603074","Com=
plex Beac II","","18-03-2025 12:54:27","18-03-2025 12:43:55","18-03-2025 13=
:11:55","Grid outage site went down because Gen failed to start due to Gen =
card dysfonction // He reset the Gen card and Gen manually started","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage site went down because Gen failed to start due to Gen card dysfon=
ction // He reset the Gen card and Gen manually started","danick.tchakouani=
@sagemcom.com","634","18-03-2025 12:54:27","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004603022","Man=
guiers Dispensaire","","18-03-2025 12:52:32","18-03-2025 12:43:55","18-03-2=
025 12:43:56","Error","Fabrice Pouakam","Incorrectly Logged Tickets","Error=
","Error","Error","Error","danick.tchakouani@sagemcom.com","519","18-03-202=
5 12:52:32","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004602974","An-=
Marche-Melen","","18-03-2025 12:44:18","18-03-2025 12:37:28","18-03-2025 12=
:44:28","Grid outage, No space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No sp=
ace to deploy MDG // Grid return","danick.tchakouani@sagemcom.com","459","1=
8-03-2025 12:44:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004602971","K=
oweit City","","18-03-2025 12:44:07","18-03-2025 12:38:46","18-03-2025 13:0=
3:18","Grid outage, Site went down because Gen started and stopped with ""L=
ow fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, Site went down because Gen started and stopped with ""Low =
fuel"" alarm (unprouven) // He reset Gen card and started Gen manualy","mar=
iam.tchonang@sagemcom.com","322","18-03-2025 12:44:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004602587","N=
koabang Ebolmedjock","","18-03-2025 11:42:31","18-03-2025 11:34:25","18-03-=
2025 11:34:26","Active//No power issue, Site on Gen. The Tx FME Brice Tsagu=
e(650214096) from Huawei is informed. Notice that it is impacted by Nkolmes=
seng-Abom Not Manager By IHS","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue, Site on Gen. The Tx FME Brice Tsague(650214096) from Huawei is in=
formed. Notice that it is impacted by Nkolmesseng-Abom Not Manager By IHS",=
"danick.tchakouani@sagemcom.com","488","18-03-2025 11:42:31","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004602281","Bit=
eng-Maetur","","18-03-2025 10:59:20","18-03-2025 10:53:02","18-03-2025 12:5=
4:02","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the l=
oad","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, Site went down because Gen started and stopped due to =
Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the =
load","danick.tchakouani@sagemcom.com","416","18-03-2025 10:59:20","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004602091","M=
ontee-Jouvence-II","","18-03-2025 10:36:34","18-03-2025 10:29:44","18-03-20=
25 11:24:44","Grid outage, Site went down because Gen overload (15kva, 250A=
) SS IHS Felix Zambe is informed // Grid return","Hyemafo Gildas","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went do=
wn because Gen overload (15kva, 250A) SS IHS Felix Zambe is informed // Gri=
d return","mariam.tchonang@sagemcom.com","412","18-03-2025 10:36:34","Sagem=
com CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004601886","Av =
Kennedy","","18-03-2025 10:18:44","18-03-2025 10:16:27","18-03-2025 10:19:2=
7","Grid outage.no space to deploy mobile gen // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no sp=
ace to deploy mobile gen // Grid return","mariam.tchonang@sagemcom.com","13=
9","18-03-2025 10:18:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0004601640","N=
goum","","18-03-2025 09:55:47","18-03-2025 09:46:06","18-03-2025 10:01:40",=
"Solar Hybrid GEN site, No power issue site on Solar, with U=3D52.7V. The T=
x Fme Gregoire (654547479) from Huawei informed","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Solar Hybrid GEN site, No power issue site on Solar, with U=3D52.7V. The =
Tx Fme Gregoire (654547479) from Huawei informed","mariam.tchonang@sagemcom=
.com","583","18-03-2025 09:55:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0004601397","C=
NR","","18-03-2025 09:16:47","18-03-2025 09:14:23","18-03-2025 09:18:55","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed automatically","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Gen started automatically","mariam.tchonang@sage=
mcom.com","145","18-03-2025 09:16:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004600905","O=
lembe-Terminus","","18-03-2025 07:25:38","18-03-2025 07:17:12","18-03-2025 =
07:49:12","Grid outage, site went down because gen start and stopped due to=
 high temp caused by by pierced radator // He added water and manually star=
t the gen(Radiator to be replace)","Fabrice Pouakam","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Radiator Leakage","Grid outage=
, site went down because gen start and stopped due to high temp caused by b=
y pierced radator // He added water and manually start the gen(Radiator to =
be replace)","mariam.tchonang@sagemcom.com","508","18-03-2025 07:25:38","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004600671","Ole=
mbe MTN","","18-03-2025 06:19:19","18-03-2025 06:14:11","18-03-2025 07:17:4=
4","Grid outage, site went down because gen failed to start due to gen cont=
actor faulty // He bypassed gen contactor and gen manually started","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor",=
"Grid outage, site went down because gen failed to start due to gen contact=
or faulty // He bypassed gen contactor and gen manually started","danick.tc=
hakouani@sagemcom.com","309","18-03-2025 06:19:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004600571","S=
hell-Nsimeyong","","18-03-2025 05:47:33","18-03-2025 05:44:17","18-03-2025 =
05:47:58","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","yves.djomo@sagemcom.com","197","18-03-2025 05:47:33","Sagemcom CM=
R"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004600529","Bit=
eng-Maetur","","18-03-2025 05:29:48","18-03-2025 05:19:40","18-03-2025 06:2=
0:44","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the l=
oad","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, Site went down because Gen started and stopped due to =
Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the =
load","ludovic-anselme.mouliom-mapoure@sagemcom","609","18-03-2025 05:29:48=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0004600294","E=
zezang","","18-03-2025 03:56:26","18-03-2025 03:48:10","18-03-2025 04:22:55=
","Grid Outage Site went down because Gen Failed to Start due to Relay 220V=
 faulty // He bypass Relay and Manually Started the Gen","Parker Tchoup","E=
quipment Repair","Passive","ACDG Gen","ACDG - Relay Faulty","Grid Outage Si=
te went down because Gen Failed to Start due to Relay 220V faulty // He byp=
ass Relay and Manually Started the Gen","yves.djomo@sagemcom.com","496","18=
-03-2025 03:56:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004600180","E=
ssomba","","18-03-2025 02:50:01","18-03-2025 02:44:47","18-03-2025 03:56:30=
","Grid outage.site went down due to gen failed to start//Grid return(inves=
tigation ongoing) ","Mba Lazare Herve","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage.site went down due to gen failed to=
 start//Grid return(investigation ongoing) ","yves.djomo@sagemcom.com","316=
","18-03-2025 02:50:01","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004600141","Nko=
lbisson usines des eaux 2","","18-03-2025 02:26:44","18-03-2025 02:13:25","=
18-03-2025 07:15:45","Access issues during Night, Grid fluctuatuation, site=
 went down due to gen overload (12KVA,270A), Pascaline IHS is informed //He=
 reduced the load","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen overlo=
ad (12KVA,270A), Pascaline IHS is informed //He reduced the load","yves.djo=
mo@sagemcom.com","801","18-03-2025 02:26:44","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004600138","NYO=
M FACE MAETUR","","18-03-2025 02:23:47","18-03-2025 02:07:30","18-03-2025 0=
2:53:52","Grid outage site went down because Gen failed to start due to Gen=
 card faulty // Gen Manually Started","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down bec=
ause Gen failed to start due to Gen card faulty // Gen Manually Started","y=
ves.djomo@sagemcom.com","979","18-03-2025 02:23:47","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004600037","MBA=
LNGONG LYCEE","","18-03-2025 01:43:37","18-03-2025 01:34:19","18-03-2025 01=
:47:48","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, Site went down because Gen stopped due to overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed//Grid return","yves.djomo@sagemcom.co=
m","559","18-03-2025 01:43:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004599993","S=
hell-Nsimeyong","","18-03-2025 01:32:03","18-03-2025 01:29:53","18-03-2025 =
01:59:37","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","ludovic-anselme.mouliom-mapoure@sagemcom","131","18-03-2025 01:32=
:03","Sagemcom CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0004599929","Mba=
nkomo CAF","","18-03-2025 01:09:26","18-03-2025 00:55:54","18-03-2025 01:21=
:28","Grid outage.gen failed to start due to automation malfunctionning//Ge=
n manually started (investigation ongoing)","Fanda Brice","Equipment Repair=
","Passive","Control Panel","ATS-AMF Issue","Grid outage.gen failed to star=
t due to automation malfunctionning//Gen manually started (investigation on=
going)","yves.djomo@sagemcom.com","813","18-03-2025 01:09:26","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004599705","B=
iteng-Maetur","","17-03-2025 23:53:02","17-03-2025 21:18:30","18-03-2025 05=
:13:20","No power issue site on gen  with U=3D54v Flubert(654266068) from H=
uawei is informed site up at 02:34 AM","Mba Lazare Herve","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue site on gen  with U=3D54v Flubert(654266068) from Huawei is infor=
med site up at 02:34 AM","yves.djomo@sagemcom.com","9273","17-03-2025 23:53=
:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004599588","N=
YOM 2 IHS","","17-03-2025 23:09:11","17-03-2025 20:42:58","17-03-2025 23:42=
:20","Site went down because CB (63*63 A) tripped in PWC who feeds equipmen=
ts OCM// CB put back on ","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Circuit Breaker Issue","Site went down becau=
se CB (63*63 A) tripped in PWC who feeds equipments OCM// CB put back on ",=
"ludovic-anselme.mouliom-mapoure@sagemcom","8775","17-03-2025 23:09:11","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0004599543","N=
ew-Marche-Melen","","17-03-2025 22:56:00","17-03-2025 22:52:51","18-03-2025=
 07:00:28","No power issue site on grid with U=3D54v Notice that site is im=
pacted by OBILI GP who is not our responsability","Paul BIBOUM","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue site on grid with U=3D54v Notice that site is impacted by O=
BILI GP who is not our responsability","yves.djomo@sagemcom.com","190","17-=
03-2025 22:56:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004598709","Nkolkoum=
ou OCM","","17-03-2025 20:43:22","17-03-2025 19:19:39","17-03-2025 19:34:39=
","Cascaded Incident from TTO4671555","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down because gen failed to start and stopped with alarm over current due =
to load // He reduced the load, site on gen","system","312045","17-03-2025 =
20:43:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004598489","SOA VILL=
AGE","","17-03-2025 20:36:41","17-03-2025 17:52:04","17-03-2025 18:48:03","=
Cascaded Incident from TTO4670973","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen failed to start due to gen card faulty // Gen manually started","syste=
m","274248","17-03-2025 20:36:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004598395","AWAE OCM=
","","17-03-2025 20:30:29","17-03-2025 17:12:16","17-03-2025 17:24:17","Cas=
caded Incident from TTO4670718","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC malfunction // He reset the PWC and Grid return=
","system","262441","17-03-2025 20:30:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004598393","Bitoto",=
"","17-03-2025 20:30:29","17-03-2025 17:12:16","17-03-2025 17:24:17","Casca=
ded Incident from TTO4670718","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n failed to start due PWC malfunction // He reset the PWC and Grid return",=
"system","262441","17-03-2025 20:30:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004598394","Tradex-N=
komo","","17-03-2025 20:30:29","17-03-2025 17:12:16","17-03-2025 17:24:17",=
"Cascaded Incident from TTO4670718","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen failed to start due PWC malfunction // He reset the PWC and Grid retur=
n","system","262440","17-03-2025 20:30:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004598396","Essomba"=
,"","17-03-2025 20:30:29","17-03-2025 17:12:16","17-03-2025 17:24:17","Casc=
aded Incident from TTO4670718","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due PWC malfunction // He reset the PWC and Grid return"=
,"system","262441","17-03-2025 20:30:30","Sagemcom CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0004598306","Eto=
ug ebe Meweulo","","17-03-2025 20:27:01","17-03-2025 20:25:55","17-03-2025 =
21:13:55","Grid fluctuation site went down because Gen started and stopped =
due to Grid bad voltage and no RCP on site // He bypass the Grid and Gen ma=
nually started","Hyemafo Gildas","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation site went down because Gen=
 started and stopped due to Grid bad voltage and no RCP on site // He bypas=
s the Grid and Gen manually started","ferot.nongni-djiogap@sagemcom.com","6=
7","17-03-2025 20:27:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004598028","Saa","",=
"17-03-2025 19:59:11","17-03-2025 15:26:37","17-03-2025 15:44:47","Cascaded=
 Incident from TTO4669972","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to work(Felix Bateu (655=
999887)/ IHS) // End of work","system","16354","17-03-2025 19:59:11","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004598027","SAA Entr=
ance","","17-03-2025 19:59:10","17-03-2025 15:26:37","17-03-2025 15:44:47",=
"Cascaded Incident from TTO4669972","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work(Felix B=
ateu (655999887)/ IHS) // End of work","system","16353","17-03-2025 19:59:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004598010","Obo=
bogo","","17-03-2025 19:55:28","17-03-2025 19:46:11","17-03-2025 19:54:39",=
"Grid outage, Site went down before Gen start due to poor backup // Gen sta=
rted automatically","MINKA NICOLAS","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen started automatically","ferot.nongni-djiog=
ap@sagemcom.com","558","17-03-2025 19:55:28","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004597843","Nko=
lbisson usines des eaux 2","","17-03-2025 19:28:27","17-03-2025 19:20:21","=
17-03-2025 20:02:48","Grid fluctuation, site went down due to gen overload =
(12KVA,270A), Bascaline IHS is informed // Grid return","TIENTCHEU NZETCHIE=
U GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid flu=
ctuation, site went down due to gen overload (12KVA,270A), Bascaline IHS is=
 informed // Grid return","ferot.nongni-djiogap@sagemcom.com","487","17-03-=
2025 19:28:27","Sagemcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0004597830","Nko=
lbisson usine des eaux","IHS_YND_712","17-03-2025 19:26:51","17-03-2025 19:=
19:39","17-03-2025 19:34:39","Grid outage, site went down because gen faile=
d to start and stopped with alarm over current due to load // He reduced th=
e load, site on gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage, site went down because gen fai=
led to start and stopped with alarm over current due to load // He reduced =
the load, site on gen","ferot.nongni-djiogap@sagemcom.com","433","17-03-202=
5 19:26:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004597665","M=
EHANDAN","","17-03-2025 19:02:55","17-03-2025 19:00:49","17-03-2025 22:43:4=
9","Site went down due to insufficiency of rectifiers on site SS IHS Pascal=
ine is confirm // He reduced the load","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down due to insufficienc=
y of rectifiers on site SS IHS Pascaline is confirm // He reduced the load"=
,"yves.djomo@sagemcom.com","128","17-03-2025 19:02:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0004597638","O=
lembe","","17-03-2025 18:59:17","17-03-2025 18:54:11","17-03-2025 18:56:37"=
,"Site went down because gen failed to start due to grid bad voltage // Gen=
 manually started","Fabrice Pouakam","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","Site went down because gen failed to st=
art due to grid bad voltage // Gen manually started","yves.djomo@sagemcom.c=
om","307","17-03-2025 18:59:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004597552","M=
imboman-Ecole","","17-03-2025 18:38:38","17-03-2025 18:34:57","17-03-2025 1=
9:15:56","Grid outage,Site went down because gen ran untill fuel shortage//=
Refueling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage,Site went down because gen ran untill fuel shortage//=
Refueling done","yves.djomo@sagemcom.com","223","17-03-2025 18:38:38","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0004597456","Y=
ona Hotel","","17-03-2025 18:18:01","17-03-2025 18:09:54","17-03-2025 18:15=
:51","Active: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(6=
91144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(69114443=
5) from Huawei is informed","ferot.nongni-djiogap@sagemcom.com","488","17-0=
3-2025 18:18:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004597331","S=
OA TOWN","IHS_YND_323","17-03-2025 17:53:11","17-03-2025 17:49:04","17-03-2=
025 18:48:37","Grid outage, site went down because gen failed to start due =
to gen card faulty // Gen manually started","Siligap Boris","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went dow=
n because gen failed to start due to gen card faulty // Gen manually starte=
d","ferot.nongni-djiogap@sagemcom.com","248","17-03-2025 17:53:11","Sagemco=
m CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0004597105","Bit=
eng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179","17-03-2025 17:16=
:29","17-03-2025 17:12:16","17-03-2025 17:24:17","Grid outage site went dow=
n because Gen failed to start due PWC malfunction // He reset the PWC and G=
rid return","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Grid outage site went down because Gen failed t=
o start due PWC malfunction // He reset the PWC and Grid return","ferot.non=
gni-djiogap@sagemcom.com","458","17-03-2025 17:16:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004597010","S=
hell-Nsimeyong","","17-03-2025 17:00:08","17-03-2025 16:57:00","17-03-2025 =
17:00:35","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","ferot.nongni-djiogap@sagemcom.com","189","17-03-2025 17:00:08","S=
agemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004596938","Mel=
en Ba'aba","","17-03-2025 16:53:57","17-03-2025 16:47:50","17-03-2025 18:15=
:31","Grid outage.gen ran until fuel shortage//Refueling done","Siligap Bor=
is","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran u=
ntil fuel shortage//Refueling done","ferot.nongni-djiogap@sagemcom.com","54=
5","17-03-2025 16:53:57","Sagemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004596794","Nko=
abang entree carriere","","17-03-2025 16:26:36","17-03-2025 16:13:29","17-0=
3-2025 18:17:15","Grid outage, site went down because gen start and stopped=
 with high temp alarm // He added water and manually start the gen","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Tem=
p - Coolant Level Issue","Grid outage, site went down because gen start and=
 stopped with high temp alarm // He added water and manually start the gen"=
,"ferot.nongni-djiogap@sagemcom.com","788","17-03-2025 16:26:36","Sagemcom =
CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004596550","Nko=
lbisson usines des eaux 2","","17-03-2025 15:43:29","17-03-2025 15:38:22","=
17-03-2025 16:19:03","Grid bad voltage, site went down because Gen failed t=
o start due to lack of 01 phase // He did a bridge on the good phase","TIEN=
TCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid bad voltage, site went down because Gen failed to=
 start due to lack of 01 phase // He did a bridge on the good phase","ferot=
.nongni-djiogap@sagemcom.com","309","17-03-2025 15:43:29","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004596460","SAA=
 2","IHS_YND_542, IHS_YND_405","17-03-2025 15:28:47","17-03-2025 15:26:37",=
"17-03-2025 15:44:47","Site went down due to work(Felix Bateu (655999887)/ =
IHS) // End of work","Parker Tchoup","Installation Activity","Passive","Pla=
nned Activity","Installation Activity","Site went down due to work(Felix Ba=
teu (655999887)/ IHS) // End of work","ferot.nongni-djiogap@sagemcom.com","=
131","17-03-2025 15:28:47","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004596403","OTE=
LE MTN","","17-03-2025 15:17:18","17-03-2025 15:12:10","17-03-2025 17:29:20=
","Grid outage, Site went down because gen start and stoppen with alarm low=
 oil pressure // He added oil pressure (3L) and gen manually started","Fand=
a Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure",=
"Grid outage, Site went down because gen start and stoppen with alarm low o=
il pressure // He added oil pressure (3L) and gen manually started","ferot.=
nongni-djiogap@sagemcom.com","310","17-03-2025 15:17:18","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004596320","Man=
guiers Dispensaire","","17-03-2025 15:04:50","17-03-2025 15:00:44","17-03-2=
025 15:24:32","Grid Fluctuation, Site went down before Gen start due to poo=
r backup // Grid return (Investigation ongoing)","Fabrice Pouakam","Equipme=
nt Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid Fl=
uctuation, Site went down before Gen start due to poor backup // Grid retur=
n (Investigation ongoing)","ferot.nongni-djiogap@sagemcom.com","247","17-03=
-2025 15:04:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0004596289","A=
n-Marche-Melen","","17-03-2025 14:59:53","17-03-2025 14:58:48","17-03-2025 =
22:57:48","Grid Fluctuation, No space to deploy MDG // Grid Stabilized","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Fl=
uctuation, No space to deploy MDG // Grid Stabilized","yves.djomo@sagemcom.=
com","66","17-03-2025 14:59:53","Sagemcom CMR"
"Closed Complete","Site Down","T3206","IHS_YND_759","NOCINC0004596226","Nko=
lfoulou Tsinga Village","","17-03-2025 14:49:50","17-03-2025 14:22:44","17-=
03-2025 15:50:51","Site went down because Gen failed due Lack of 02 phase a=
nd Gen battery faulty// He made a bridge with a Good phases","Siligap Boris=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Site went down because Gen failed due Lack of 02 phase and Gen battery fau=
lty// He made a bridge with a Good phases","ferot.nongni-djiogap@sagemcom.c=
om","1627","17-03-2025 14:49:50","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0004596076","Feb=
e Village","","17-03-2025 14:30:35","17-03-2025 14:27:27","17-03-2025 17:55=
:27","Grid fluctuation, site went down because Gen failed to start due to g=
rid bad voltage No Rcp // He bypassed the grid and started Gen manually","M=
boua Thierry","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because Gen failed to start d=
ue to grid bad voltage No Rcp // He bypassed the grid and started Gen manua=
lly","el-dalile@sagemcom.com","189","17-03-2025 14:30:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004594786","O=
dza II OCM","","17-03-2025 12:46:40","17-03-2025 12:36:40","17-03-2025 12:4=
9:03","Grid outage, Site went down before Gen start due to poor backup // G=
en started automaticaly","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen started automaticaly","yves.djomo@sag=
emcom.com","602","17-03-2025 12:46:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004594754","M=
vog-Manga","","17-03-2025 12:38:33","17-03-2025 12:30:26","17-03-2025 12:52=
:26","Grid outage, Site went down because gen failed to start // Grid retur=
n (Investigation ongoing)","Albran Byorel","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage, Site went down because gen fai=
led to start // Grid return (Investigation ongoing)","el-dalile@sagemcom.co=
m","489","17-03-2025 12:38:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004594723","S=
tade-Abega","","17-03-2025 12:33:17","17-03-2025 12:24:12","17-03-2025 12:4=
8:19","Grid outage site went down because Gen failed to start due PWC ZTE d=
ysfonction // Grid return","Mba Lazare Herve","Equipment Repair","Passive",=
"Rectifier","Rectifier Module Overloaded","Grid outage site went down becau=
se Gen failed to start due PWC ZTE dysfonction // Grid return","yves.djomo@=
sagemcom.com","547","17-03-2025 12:33:17","Sagemcom CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0004594707","Nya=
hoo","IHS_YND_670","17-03-2025 12:31:13","17-03-2025 12:25:40","17-03-2025 =
15:05:54","Grid outage.gen start and stopped due to alarm""high temp""//We =
added water and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment=
 Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issu=
e","Grid outage.gen start and stopped due to alarm""high temp""//We added w=
ater and gen manually started","el-dalile@sagemcom.com","334","17-03-2025 1=
2:31:13","Sagemcom CMR"
"Closed Complete","Site Down","T1597","IHS_YND_670","NOCINC0004594700","BOB=
OCK","","17-03-2025 12:28:46","17-03-2025 12:25:40","17-03-2025 15:05:54","=
Grid outage.gen start and stopped due to alarm""high temp""//We added water=
 and gen manually started","Kemeni Franklin","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage.gen start and stopped due to =
alarm""high temp""//We added water and gen manually started","yves.djomo@sa=
gemcom.com","279610","17-03-2025 12:28:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0004594688","O=
lembe","","17-03-2025 12:27:13","17-03-2025 12:26:09","17-03-2025 12:55:45"=
,"Site went down Because gen fails to start due to lack of 1 phases on site=
 // He make the bridge with a good phase: Site on grid","Fabrice Pouakam","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Si=
te went down Because gen fails to start due to lack of 1 phases on site // =
He make the bridge with a good phase: Site on grid","yves.djomo@sagemcom.co=
m","66","17-03-2025 12:27:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_115","NOCINC0004594686","Labogeni=
e","","17-03-2025 12:25:50","17-03-2025 09:42:39","17-03-2025 09:42:40","",=
"","Incorrectly Logged Tickets","Error","Error","Error","Error","system","9=
791","17-03-2025 12:25:50","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004594685","Nko=
ulou Carriere carrefourt","","17-03-2025 12:25:48","17-03-2025 12:17:40","1=
7-03-2025 12:51:18","Grid outage, site went down because due to Gen overloa=
d(20kva,310 A) IHS SS Alphonse is informed// Grid return","Mba Lazare Herve=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, s=
ite went down because due to Gen overload(20kva,310 A) IHS SS Alphonse is i=
nformed// Grid return","el-dalile@sagemcom.com","489","17-03-2025 12:25:48"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004594679","O=
LAMA","","17-03-2025 12:24:14","17-03-2025 12:12:08","17-03-2025 13:37:16",=
"Grid outage, site went down because gen failed to start due hybrid system =
malfunction // He reset hybrid system and gen manually started","Fanda Bric=
e","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid outage, site=
 went down because gen failed to start due hybrid system malfunction // He =
reset hybrid system and gen manually started","yves.djomo@sagemcom.com","22=
472","17-03-2025 12:24:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004594673","C=
rf-Nsam","","17-03-2025 12:23:29","17-03-2025 12:14:21","17-03-2025 12:47:0=
6","Grid outage, Site went down before Gen start due to poor backup // Gen =
started automatically (Awaitting Configuration of battery backup)","MINKA N=
ICOLAS","Equipment Repair","Passive","Control Panel","Power Cabinet - Batte=
ry Low","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started automatically (Awaitting Configuration of battery backup)","yv=
es.djomo@sagemcom.com","550","17-03-2025 12:23:29","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004594670","AWA=
E OCM","","17-03-2025 12:22:53","17-03-2025 12:17:44","17-03-2025 12:48:08"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen st=
arted automaticaly","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup // Gen started automaticaly","el-dalile@sagemc=
om.com","311","17-03-2025 12:22:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004594643","M=
ontee-Des-Soeurs","","17-03-2025 12:19:29","17-03-2025 12:14:25","17-03-202=
5 12:53:31","Grid outage, Site went down before Gen start due to poor backu=
p// Gen started manually","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen started manually","yves.djomo@sagemc=
om.com","306","17-03-2025 12:19:29","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004594502","Av =
Kennedy","","17-03-2025 11:52:35","17-03-2025 11:50:30","17-03-2025 19:04:3=
0","Grid outage.no space to deploy mobile gen // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no sp=
ace to deploy mobile gen // Grid return","yves.djomo@sagemcom.com","126","1=
7-03-2025 11:52:35","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004594149","Nko=
g-Edzen","","17-03-2025 11:01:23","17-03-2025 10:56:16","17-03-2025 13:56:2=
1","Grid outage, Site went down because gen stopped due to belt cut // He c=
hanged belt and Gen manually started","Parker Tchoup","Equipment Repair","P=
assive","ACDG Gen","ACDG - Fan Belt","Grid outage, Site went down because g=
en stopped due to belt cut // He changed belt and Gen manually started","yv=
es.djomo@sagemcom.com","309","17-03-2025 11:01:23","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004594081","SOA=
 UNIVERSITY STADIUM","","17-03-2025 10:43:02","17-03-2025 10:40:58","17-03-=
2025 11:18:58","Grid outage site went down Because Gen disfunctionning  and=
 does not support the load //He reduice The Load and Site is on GEN ","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage site went down Because Gen disfunctionning  and does not support the=
 load //He reduice The Load and Site is on GEN ","yves.djomo@sagemcom.com",=
"125","17-03-2025 10:43:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0004593961","F=
ebe Village","","17-03-2025 10:18:52","17-03-2025 10:16:47","17-03-2025 11:=
43:45","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage No Rcp // He bypassed the grid and started Gen manually",=
"Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid fluctuation, site went down because Gen failed to start=
 due to grid bad voltage No Rcp // He bypassed the grid and started Gen man=
ually","yves.djomo@sagemcom.com","126","17-03-2025 10:18:52","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004593937","NTU=
I TOWN","","17-03-2025 10:14:49","17-03-2025 10:13:29","17-03-2025 11:38:35=
","Site went down due to 1/3 rectifier disfunction // He reset rectifiers",=
"Parker Tchoup","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to 1/3 rectifier disfunction // He reset rectifiers","=
el-dalile@sagemcom.com","81","17-03-2025 10:14:49","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004593835","Men=
dong vallee","","17-03-2025 09:56:40","17-03-2025 09:53:29","17-03-2025 12:=
17:46","Site went down due to insufficience of rectifiers SS IHS Felix ZAMB=
E confirmed// He reduiced load","Fanda Brice","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","Site went down due to insufficience of rect=
ifiers SS IHS Felix ZAMBE confirmed// He reduiced load","yves.djomo@sagemco=
m.com","193","17-03-2025 09:56:40","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004593819","Nko=
lbong","","17-03-2025 09:52:53","17-03-2025 09:49:34","17-03-2025 11:45:01"=
,"Grid outage, site went down Gen failed to start due to Gen Card dysfuncti=
oning on Site // He reset it and Site is on Gen","Delor Telezing","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site we=
nt down Gen failed to start due to Gen Card dysfunctioning on Site // He re=
set it and Site is on Gen","yves.djomo@sagemcom.com","201","17-03-2025 09:5=
2:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004593717","A=
kak-Nkozoa-MTN-IHS","","17-03-2025 09:33:39","17-03-2025 09:27:34","17-03-2=
025 15:19:00","Site went down because gen failed to start due to grid bad v=
oltage // Gen manually started","Fabrice Pouakam","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Site went down because gen=
 failed to start due to grid bad voltage // Gen manually started","yves.djo=
mo@sagemcom.com","368","17-03-2025 09:33:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0004593547","C=
NR","","17-03-2025 09:06:06","17-03-2025 09:00:03","17-03-2025 09:10:03","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
 automatically","Mboua Thierry","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup // Gen start automatically","yves.djomo@sagemcom.com"=
,"364","17-03-2025 09:06:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004593386","O=
LAMA","","17-03-2025 08:20:52","17-03-2025 08:14:49","17-03-2025 09:59:17",=
"Active//No power issue on site Ubaie =3D54.1V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.1V site on Grid The TX FME Henri (69994969=
3) from Huawei is informed","yves.djomo@sagemcom.com","364","17-03-2025 08:=
20:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004593297","Crf-Mban=
kolo-IHS","","17-03-2025 07:56:20","17-03-2025 07:04:52","17-03-2025 12:07:=
16","Site went down due to work SS IHS Bernard and Our FME Thierry (6768725=
15/SAGEMCOM) is working on Site  (Replacement of MPR)// End of work","Mboua=
 Thierry","Installation Activity","Passive","Planned Activity","Installatio=
n Activity","Site went down due to work SS IHS Bernard and Our FME Thierry =
(676872515/SAGEMCOM) is working on Site  (Replacement of MPR)// End of work=
","system","3088","17-03-2025 07:56:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004593267","Nkolkoum=
ou OCM","","17-03-2025 07:50:01","17-03-2025 07:46:16","17-03-2025 08:34:32=
","Cascaded Incident from TTO4666466","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","gen ower curent ","sy=
stem","274533","17-03-2025 07:50:01","Sagemcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0004593264","Nko=
lbisson usine des eaux","IHS_YND_712","17-03-2025 07:49:19","17-03-2025 07:=
46:16","17-03-2025 08:34:32","Grid outage, site went down because gen faile=
d to start and stopped with alarm over current due to Gen overload // He re=
duced the load, site on gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down because=
 gen failed to start and stopped with alarm over current due to Gen overloa=
d // He reduced the load, site on gen","yves.djomo@sagemcom.com","185","17-=
03-2025 07:49:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_140","NOCINC0004593220","BISCUITE=
RIE","","17-03-2025 07:44:40","17-03-2025 07:38:29","17-03-2025 08:45:48","=
Cascaded Incident from TTO4666422","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage,Site went down because ge=
n ran untill fuel shortage//Refueling done","system","267935","17-03-2025 0=
7:44:40","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004593210","Mvo=
g-Betsi","IHS_YND_140","17-03-2025 07:42:34","17-03-2025 07:38:29","17-03-2=
025 08:48:23","Grid outage,Site went down because gen ran untill fuel short=
age//Refueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Die=
sel Outage","Grid outage,Site went down because gen ran untill fuel shortag=
e//Refueling done","yves.djomo@sagemcom.com","246","17-03-2025 07:42:34","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004593147","B=
iteng-Maetur","","17-03-2025 07:26:46","16-03-2025 15:10:41","16-03-2025 15=
:50:08","Grid outage, Site went down because Gen overload(20kva, 280A) SS I=
HS Alphonse DEFFO confirmed// Grid return. Power issue resolved at 03:50 PM=
 but site remains down after power reset at OCM The FME TX ","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
, Site went down because Gen overload(20kva, 280A) SS IHS Alphonse DEFFO co=
nfirmed// Grid return. Power issue resolved at 03:50 PM but site remains do=
wn after power reset at OCM The FME TX Lionel Adjep (694693436) of Huawei i=
s informed","yves.djomo@sagemcom.com","58567","17-03-2025 07:26:46","Sagemc=
om CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004593017","Nsi=
malen MTN","","17-03-2025 06:56:34","17-03-2025 06:53:31","17-03-2025 08:05=
:20","Grid outage.Gen failed to start due alrm ""low oil pressure""//We add=
 oil and Gen manually started","Albran Byorel","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Low Oil Pressure","Grid outage.Gen failed to start due =
alrm ""low oil pressure""//We add oil and Gen manually started","yves.djomo=
@sagemcom.com","184","17-03-2025 06:56:34","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004592974","Crf=
-Mbankolo-IHS","","17-03-2025 06:42:40","17-03-2025 06:16:37","17-03-2025 0=
6:44:37","Site went down due to MPR DYSFONNCTION on site SS IHS Bernard ATA=
NGANA confirmed // He reset the MPR","Mboua Thierry","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Cabinet","Site went down due to MPR DYSFONNCT=
ION on site SS IHS Bernard ATANGANA confirmed // He reset the MPR","yves.dj=
omo@sagemcom.com","1564","17-03-2025 06:42:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004592717","Saa","",=
"17-03-2025 05:30:01","17-03-2025 05:25:58","17-03-2025 05:39:58","Cascaded=
 Incident from TTO4665868","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen fai=
ls to start due to battery ge discharged // Gen start with battery backup(I=
nvestigation ongoing)","system","275748","17-03-2025 05:30:01","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004592716","SAA Entr=
ance","","17-03-2025 05:30:01","17-03-2025 05:25:58","17-03-2025 05:39:58",=
"Cascaded Incident from TTO4665868","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen fails to start due to battery ge discharged // Gen start with battery=
 backup(Investigation ongoing)","system","275747","17-03-2025 05:30:01","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004592715","Carrefou=
r Ayissi Ele","","17-03-2025 05:30:00","17-03-2025 05:25:58","17-03-2025 05=
:39:58","Cascaded Incident from TTO4665868","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n because gen fails to start due to battery ge discharged // Gen start with=
 battery backup(Investigation ongoing)","system","275747","17-03-2025 05:30=
:00","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004592710","SAA=
 2","IHS_YND_810, IHS_YND_542, IHS_YND_405","17-03-2025 05:29:09","17-03-20=
25 05:25:58","17-03-2025 05:39:58","Grid outage, site went down because gen=
 fails to start due to battery ge discharged // Gen start with battery back=
up(Investigation ongoing)","Parker Tchoup","Equipment Repair","Passive","AC=
DG Gen","ACDG - Generator Battery","Grid outage, site went down because gen=
 fails to start due to battery ge discharged // Gen start with battery back=
up(Investigation ongoing)","ludovic-anselme.mouliom-mapoure@sagemcom","192"=
,"17-03-2025 05:29:09","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004592707","Nko=
lbisson usines des eaux 2","","17-03-2025 05:27:14","17-03-2025 05:24:36","=
17-03-2025 05:30:23","Site went down because Gen failed to start due to gri=
d bad voltage No crcp // He bypassed the Grid and started Gen manually	","T=
IENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Site went down because Gen failed to start due to g=
rid bad voltage No crcp // He bypassed the Grid and started Gen manually	",=
"ludovic-anselme.mouliom-mapoure@sagemcom","159","17-03-2025 05:27:14","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004592433","M=
ontee-Jouvence-II","","17-03-2025 03:27:50","17-03-2025 02:45:34","17-03-20=
25 05:13:54","ACTIVE// No power issue on site, site on Grid with Ubaie=3D54=
.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed","Hyemafo G=
ildas","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE// No power issue on site, site on Grid with Ubaie=
=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed","cedr=
ic.tiani@sagemcom.com","2537","17-03-2025 03:27:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004592429","A=
ccacia New","","17-03-2025 03:25:26","17-03-2025 02:45:12","17-03-2025 05:1=
4:05","Active// No power Issue Site on Grid Ubai =3D54,6V,The FME The TX FM=
E Mbah Hosiah (674007438) is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power Iss=
ue Site on Grid Ubai =3D54,6V,The FME The TX FME Mbah Hosiah (674007438) is=
 informed","cedric.tiani@sagemcom.com","2416","17-03-2025 03:25:26","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004592426","D=
amas","","17-03-2025 03:24:37","17-03-2025 02:45:26","17-03-2025 03:00:51",=
"Active//No power issue on site, site on Grid with Ubaie=3D 53.6 V TX Huawe=
i Mbah Osiah (674007438)// from Huawei is informed","MINKA NICOLAS","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site, site on Grid with Ubaie=3D 53.6 V TX H=
uawei Mbah Osiah (674007438)// from Huawei is informed","cedric.tiani@sagem=
com.com","2352","17-03-2025 03:24:37","Sagemcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004592408","Tam=
tam Weekend","","17-03-2025 03:13:06","17-03-2025 02:51:39","17-03-2025 05:=
15:39","Site went down due to 01/08 rectifiers faulty // He remove the faul=
ty rectifier:Site on grid(replacement ongoing)","Hyemafo Gildas","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","Site went down due to 01=
/08 rectifiers faulty // He remove the faulty rectifier:Site on grid(replac=
ement ongoing)","ludovic-anselme.mouliom-mapoure@sagemcom","1288","17-03-20=
25 03:13:06","Sagemcom CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004592317","Odz=
a Minkan IHS","","17-03-2025 02:23:54","17-03-2025 02:14:19","17-03-2025 02=
:17:20","Site went down because CB 32A disjuncted in Pwc due to lighting//H=
e reamed the CB","Albran Byorel","Equipment Repair","Passive","Rectifier","=
Rectifier - Circuit Breaker","Site went down because CB 32A disjuncted in P=
wc due to lighting//He reamed the CB","ludovic-anselme.mouliom-mapoure@sage=
mcom","576","17-03-2025 02:23:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0004592211","LOBO MTN=
","","17-03-2025 01:40:12","17-03-2025 00:42:13","17-03-2025 02:02:25","Cas=
caded Incident from TTO4665073","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to work(=
Brice William 673923777)/BOTCOM/ Swapp of batteries) // End of work","syste=
m","1227798","17-03-2025 01:40:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004592212","NKONGKAR=
AK","","17-03-2025 01:40:12","17-03-2025 00:42:13","17-03-2025 02:02:25","C=
ascaded Incident from TTO4665073","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down due to wor=
k(Brice William 673923777)/BOTCOM/ Swapp of batteries) // End of work","sys=
tem","1227796","17-03-2025 01:40:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_366","NOCINC0004592206","Mandoumb=
a MTN","","17-03-2025 01:40:11","17-03-2025 00:42:13","17-03-2025 02:02:25"=
,"Cascaded Incident from TTO4665073","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to work(Bric=
e William 673923777)/BOTCOM/ Swapp of batteries) // End of work","system","=
1227801","17-03-2025 01:40:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004592209","Nkongtoc=
k","","17-03-2025 01:40:11","17-03-2025 00:42:13","17-03-2025 02:02:25","Ca=
scaded Incident from TTO4665073","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work(Brice Wi=
lliam 673923777)/BOTCOM/ Swapp of batteries) // End of work","system","1227=
805","17-03-2025 01:40:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004592207","Mambine"=
,"","17-03-2025 01:40:11","17-03-2025 00:42:13","17-03-2025 02:02:25","Casc=
aded Incident from TTO4665073","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to work(Brice William =
673923777)/BOTCOM/ Swapp of batteries) // End of work","system","1227802","=
17-03-2025 01:40:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0004592210","Ekekam",=
"","17-03-2025 01:40:11","17-03-2025 00:42:13","17-03-2025 02:02:25","Casca=
ded Incident from TTO4665073","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work(Br=
ice William 673923777)/BOTCOM/ Swapp of batteries) // End of work","system"=
,"1227802","17-03-2025 01:40:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0004592203","Nkeng li=
kok","","17-03-2025 01:40:10","17-03-2025 00:42:13","17-03-2025 02:02:25","=
Cascaded Incident from TTO4665073","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to work(Brice =
William 673923777)/BOTCOM/ Swapp of batteries) // End of work","system","12=
27798","17-03-2025 01:40:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0004592202","Lobo 2",=
"","17-03-2025 01:40:10","17-03-2025 00:42:13","17-03-2025 02:02:25","Casca=
ded Incident from TTO4665073","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work(Br=
ice William 673923777)/BOTCOM/ Swapp of batteries) // End of work","system"=
,"1227804","17-03-2025 01:40:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0004592204","Ngog Map=
ubi","","17-03-2025 01:40:10","17-03-2025 00:42:13","17-03-2025 02:02:25","=
Cascaded Incident from TTO4665073","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to work(Brice =
William 673923777)/BOTCOM/ Swapp of batteries) // End of work","system","12=
27795","17-03-2025 01:40:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0004592205","Bot Maka=
k","","17-03-2025 01:40:10","17-03-2025 00:42:13","17-03-2025 02:02:25","Ca=
scaded Incident from TTO4665073","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site went down due to work(Brice William 673923777=
)/BOTCOM/ Swapp of batteries) // End of work","system","1227804","17-03-202=
5 01:40:10","Sagemcom CMR"
"Closed Complete","Site Down","T0236","IHS_YND_373","NOCINC0004592185","Mal=
oun","","17-03-2025 01:30:43","17-03-2025 00:42:13","17-03-2025 02:02:25","=
","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Site went down due to work(Brice William 673923777)/BOTCOM/ Swapp =
of batteries) // End of work","ludovic-anselme.mouliom-mapoure@sagemcom","1=
227799","17-03-2025 01:30:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004592146","Nkolfon =
Cimencam","","17-03-2025 01:21:31","17-03-2025 00:42:13","17-03-2025 02:02:=
25","Cascaded Incident from TTO4665073","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work(Br=
ice William 673923777)/BOTCOM/ Swapp of batteries) // End of work","system"=
,"1227799","17-03-2025 01:21:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_310","NOCINC0004592145","Nomayos"=
,"","17-03-2025 01:21:31","17-03-2025 00:42:13","17-03-2025 02:02:25","Casc=
aded Incident from TTO4665073","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to work(Brice William =
673923777)/BOTCOM/ Swapp of batteries) // End of work","system","1227800","=
17-03-2025 01:21:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004592144","Bondjock=
","","17-03-2025 01:21:31","17-03-2025 00:42:13","17-03-2025 02:02:25","Cas=
caded Incident from TTO4665073","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to work(Brice William=
 673923777)/BOTCOM/ Swapp of batteries) // End of work","system","1227803",=
"17-03-2025 01:21:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_706","NOCINC0004592143","Mbankomo=
 CAF","","17-03-2025 01:21:31","17-03-2025 00:42:13","17-03-2025 02:02:25",=
"Cascaded Incident from TTO4665073","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work(Brice Wil=
liam 673923777)/BOTCOM/ Swapp of batteries) // End of work","system","12278=
02","17-03-2025 01:21:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004592142","Nomayos =
montee Meche","","17-03-2025 01:21:30","17-03-2025 00:42:13","17-03-2025 02=
:02:25","Cascaded Incident from TTO4665073","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down due to work(B=
rice William 673923777)/BOTCOM/ Swapp of batteries) // End of work","system=
","1227797","17-03-2025 01:21:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004592128","Minka","=
","17-03-2025 01:17:41","17-03-2025 00:42:13","17-03-2025 02:02:25","Cascad=
ed Incident from TTO4665073","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to work(Brice William 67=
3923777)/BOTCOM/ Swapp of batteries) // End of work","system","1227805","17=
-03-2025 01:17:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004592130","Akono","=
","17-03-2025 01:17:41","17-03-2025 00:42:13","17-03-2025 02:02:25","Cascad=
ed Incident from TTO4665073","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to work(Brice William 67=
3923777)/BOTCOM/ Swapp of batteries) // End of work","system","1227800","17=
-03-2025 01:17:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004592129","Mom","",=
"17-03-2025 01:17:41","17-03-2025 00:42:13","17-03-2025 02:02:25","Cascaded=
 Incident from TTO4665073","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Site went down due to work(Brice William 6739=
23777)/BOTCOM/ Swapp of batteries) // End of work","system","1227803","17-0=
3-2025 01:17:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004592127","OTELE MT=
N","","17-03-2025 01:17:40","17-03-2025 00:42:13","17-03-2025 02:02:25","Ca=
scaded Incident from TTO4665073","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down due to work(Brice Willia=
m 673923777)/BOTCOM/ Swapp of batteries) // End of work","system","1227799"=
,"17-03-2025 01:17:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004592125","OKOA Pea=
ge","","17-03-2025 01:17:40","17-03-2025 00:42:13","17-03-2025 02:02:25","C=
ascaded Incident from TTO4665073","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work(Brice Willi=
am 673923777)/BOTCOM/ Swapp of batteries) // End of work","system","1227797=
","17-03-2025 01:17:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004592126","OLAMA","=
","17-03-2025 01:17:40","17-03-2025 00:42:13","17-03-2025 02:02:25","Cascad=
ed Incident from TTO4665073","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to work(Brice William 67=
3923777)/BOTCOM/ Swapp of batteries) // End of work","system","1227801","17=
-03-2025 01:17:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004592072","c=
hina embassy yde","","17-03-2025 01:00:06","17-03-2025 00:51:39","17-03-202=
5 00:52:33","Active//No power issue site on Grid with U=3D52.3V The Tx FME =
Eloundou Bertrand from Huawei is informed","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power =
issue site on Grid with U=3D52.3V The Tx FME Eloundou Bertrand from Huawei =
is informed","ludovic-anselme.mouliom-mapoure@sagemcom","508","17-03-2025 0=
1:00:06","Sagemcom CMR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0004592048","Sou=
s Prefecture","IHS_YND_330, IHS_YND_687, IHS_YND_373, IHS_YND_791, IHS_YND_=
783, IHS_YND_347, IHS_YND_419, IHS_YND_421, IHS_YND_366, IHS_YND_350, IHS_Y=
ND_706, IHS_YND_531, IHS_EDA_101, IHS_YND_372, IHS_YND_335, IHS_YND_371, IH=
S_YND_349, IHS_YND_310, IHS_YND_345, IHS_YND_762, IHS_YND_714, IHS_YND_342,=
 IHS_YND_370, IHS_YND_365, IHS_YND_713","17-03-2025 00:49:24","17-03-2025 0=
0:42:13","17-03-2025 02:02:43","Site went down due to work(Brice William 67=
3923777)/BOTCOM/ Swapp of batteries) // End of work Power issue resolved at=
 MTN  but remains down at OCM flulbert(654266068) from HUAWEI is informed "=
,"Fanda Brice","Installation Activity","Passive","Planned Activity","Instal=
lation Activity","Site went down due to work(Brice William 673923777)/BOTCO=
M/ Swapp of batteries) // End of work Power issue resolved at MTN  but rema=
ins down at OCM flulbert(654266068) from HUAWEI is informed ","ludovic-anse=
lme.mouliom-mapoure@sagemcom","432","17-03-2025 00:49:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0004591810","O=
kolo","IHS_YND_242","16-03-2025 23:27:18","16-03-2025 21:55:00","16-03-2025=
 22:58:32","Grid outage, Site went down because Gen failed to start with ""=
overcurrent"" alarm// He reset Gen card and started Gen manualy","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage, Site went down because Gen failed to start with ""overcurrent"" a=
larm// He reset Gen card and started Gen manualy","ludovic-anselme.mouliom-=
mapoure@sagemcom","5539","16-03-2025 23:27:18","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004591616","Men=
dong vallee","","16-03-2025 22:50:21","16-03-2025 22:49:10","16-03-2025 23:=
08:33","Grid outage site went down because Gen over load (20KVA; 300A)//Gri=
d power return SS IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Bri=
ce","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage =
site went down because Gen over load (20KVA; 300A)//Grid power return SS IH=
S F=E9lix Zamb=E9 is informed and confirmed","ludovic-anselme.mouliom-mapou=
re@sagemcom","72","16-03-2025 22:50:21","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004591535","Crf=
-Mbankolo-IHS","","16-03-2025 22:34:52","16-03-2025 22:30:26","17-03-2025 0=
5:43:21","Site went down due to MPR DYSFONNCTION on site SS IHS Bernard ATA=
NGANA confirmed // He reset the MPR","Mboua Thierry","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Cabinet","Site went down due to MPR DYSFONNCT=
ION on site SS IHS Bernard ATANGANA confirmed // He reset the MPR","ludovic=
-anselme.mouliom-mapoure@sagemcom","267","16-03-2025 22:34:52","Sagemcom CM=
R"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0004591516","San=
ta Barbara Yde","","16-03-2025 22:31:48","16-03-2025 22:07:39","16-03-2025 =
23:56:00","Grid outage, site went down because gen failed to started due to=
 pear faulty // He bypassed pear and gen manually started","Delor Telezing"=
,"Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Fuel Pump","Grid out=
age, site went down because gen failed to started due to pear faulty // He =
bypassed pear and gen manually started","ludovic-anselme.mouliom-mapoure@sa=
gemcom","1450","16-03-2025 22:31:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004591439","M=
essassi okolo","","16-03-2025 22:18:00","16-03-2025 21:55:44","16-03-2025 2=
2:00:41","Active//No power issue on site Ubaie=3D53,9 V site on Gen ,TX FME=
 Synphorien (691316854) from Huawei is informed","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active//No power issue on site Ubaie=3D53,9 V site on Gen ,TX FME Synph=
orien (691316854) from Huawei is informed","ludivine.ngamaleu@ihstowers.com=
","1337","16-03-2025 22:18:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004591420","O=
dza II OCM","","16-03-2025 22:15:57","16-03-2025 21:55:44","16-03-2025 21:5=
9:54","Site went down due to hybrid system dysfunctionning // He reset and =
Gen started manaully","Albran Byorel","Equipment Repair","Passive","Hybrid"=
,"Hybrid Module","Site went down due to hybrid system dysfunctionning // He=
 reset and Gen started manaully","ludivine.ngamaleu@ihstowers.com","1215","=
16-03-2025 22:15:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004591414","M=
balla 4","","16-03-2025 22:14:56","16-03-2025 21:55:00","16-03-2025 22:58:3=
2","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid outage, Site went down because Gen failed to start with ""=
overcurrent"" alarm// He reset Gen card and started Gen manualy","ludivine.=
ngamaleu@ihstowers.com","274026","16-03-2025 22:14:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004591383","Tradex-N=
komo","","16-03-2025 22:05:00","16-03-2025 21:54:20","16-03-2025 22:32:36",=
"Cascaded Incident from TTO4664285","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen failed to start due PWC dysfonction // He reset the PWC and Gen manual=
ly started","system","295567","16-03-2025 22:05:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004591382","Bitoto",=
"","16-03-2025 22:05:00","16-03-2025 21:54:20","16-03-2025 22:32:36","Casca=
ded Incident from TTO4664285","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n failed to start due PWC dysfonction // He reset the PWC and Gen manually =
started","system","295566","16-03-2025 22:05:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004591384","AWAE OCM=
","","16-03-2025 22:05:00","16-03-2025 21:54:20","16-03-2025 22:32:36","Cas=
caded Incident from TTO4664285","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC dysfonction // He reset the PWC and Gen manuall=
y started","system","295568","16-03-2025 22:05:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004591365","B=
iteng","IHS_YND_292, IHS_YND_172, IHS_YND_173","16-03-2025 22:00:32","16-03=
-2025 21:54:20","16-03-2025 22:32:36","Grid outage site went down because G=
en failed to start due PWC dysfonction // He reset the PWC and Gen manually=
 started","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rect=
ifier Module Overloaded","Grid outage site went down because Gen failed to =
start due PWC dysfonction // He reset the PWC and Gen manually started","lu=
divine.ngamaleu@ihstowers.com","374","16-03-2025 22:00:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004591344","E=
ssomba","","16-03-2025 21:56:44","16-03-2025 21:54:38","16-03-2025 22:32:29=
","Grid outage site went down because Gen failed to start due PWC dysfoncti=
on // He reset the PWC and Gen manually started","Mba Lazare Herve","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outag=
e site went down because Gen failed to start due PWC dysfonction // He rese=
t the PWC and Gen manually started","yves.djomo@sagemcom.com","128","16-03-=
2025 21:56:44","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004591334","Nko=
zoa","","16-03-2025 21:54:32","16-03-2025 21:47:38","16-03-2025 21:55:30","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and site on GEN","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to gen overload (20kva, 340A) SS HIS Felix ba=
teu is informed and confirmed// He reduced the load and site on GEN","ferot=
.nongni-djiogap@sagemcom.com","415","16-03-2025 21:54:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004591329","E=
mana Lycee","","16-03-2025 21:53:49","16-03-2025 21:39:33","16-03-2025 21:4=
5:04","Active//No power issue on site Ubaie=3D50,6 V site on Gen ,TX FME Sy=
nphorien (691316854) from Huawei is informed. Notice that we have disjuncti=
on at BTS OCM","Fabrice Pouakam","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site=
 Ubaie=3D50,6 V site on Gen ,TX FME Synphorien (691316854) from Huawei is i=
nformed. Notice that we have disjunction at BTS OCM","ludivine.ngamaleu@ihs=
towers.com","857","16-03-2025 21:53:49","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004591327","Mfo=
u EPC","","16-03-2025 21:53:43","16-03-2025 21:40:37","16-03-2025 21:41:27"=
,"Active//No power issue on site, Site on Gen UBAIE=3D51.4V The RM Martial =
(650252214) from Huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue on site, Site on Gen UBAIE=3D51.4V The RM Martial (65025221=
4) from Huawei is informed","yves.djomo@sagemcom.com","788","16-03-2025 21:=
53:43","Sagemcom CMR"
"Closed Complete","Site Down","T0144","IHS_YND_333","NOCINC0004591248","Mfo=
u MTN","","16-03-2025 21:34:04","16-03-2025 21:32:00","16-03-2025 21:33:42"=
,"Active//No power issue U=3D50.7 V site on Battery  and The  TX FME Leonel=
 Steve (655184876) from huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue U=3D50.7 V site on Battery  and The  TX FME Leonel S=
teve (655184876) from huawei is informed","yves.djomo@sagemcom.com","125","=
16-03-2025 21:34:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004591191","S=
OA UNIVERSITY STADIUM","","16-03-2025 21:27:30","16-03-2025 21:11:25","16-0=
3-2025 21:15:33","Active//No power issue on site Ubaie =3D56,3V site on Gen=
 The TX RM Alain (691144423) from Huawei is informed and Up at 09:50 PM","S=
iligap Boris","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active//No power issue on site Ubaie =3D56,3V sit=
e on Gen The TX RM Alain (691144423) from Huawei is informed and Up at 09:5=
0 PM","yves.djomo@sagemcom.com","966","16-03-2025 21:27:30","Sagemcom CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004591056","Oko=
lo Kilombo","","16-03-2025 21:09:15","16-03-2025 20:38:59","16-03-2025 22:3=
4:59","Grid outage, site went down because gen fails to start due to Gen ca=
ble faulty // Gen manualy started with cable backup","Fabrice Pouakam","Equ=
ipment Repair","Passive","Infrastructure","Armoured Cable","Grid outage, si=
te went down because gen fails to start due to Gen cable faulty // Gen manu=
aly started with cable backup","ferot.nongni-djiogap@sagemcom.com","1816","=
16-03-2025 21:09:15","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004590976","Ole=
mbe MTN","","16-03-2025 20:51:29","16-03-2025 20:43:19","16-03-2025 21:49:1=
9","Grid outage, site went down because gen failed to start due to gen cont=
actor faulty // He bypassed gen contactor and gen manually started","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor",=
"Grid outage, site went down because gen failed to start due to gen contact=
or faulty // He bypassed gen contactor and gen manually started","ferot.non=
gni-djiogap@sagemcom.com","491","16-03-2025 20:51:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_311","IHS_YND_453","NOCINC0004590953","S=
ong-bong","","16-03-2025 20:47:57","16-03-2025 20:38:52","17-03-2025 08:48:=
52","Hybrid gen site, Site went down because  gen overload(09KVa, 70A) due =
to Old generator, SS IHS FELIX ZAMBE is informed // Load reduice: Site on g=
en","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Hybrid gen site, Site went down because  gen overload(09KVa, 70A) due=
 to Old generator, SS IHS FELIX ZAMBE is informed // Load reduice: Site on =
gen","ludivine.ngamaleu@ihstowers.com","545","16-03-2025 20:47:57","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0004590892","F=
ebe Village","","16-03-2025 20:30:11","16-03-2025 20:27:06","16-03-2025 21:=
46:12","Grid Outage Site went down because Gen Failed to Start  due to Rela=
y 220V faulty caused by heavy rain and lightning strike on site// He bypass=
 Relay and Manually Started the Gen ","Mboua Thierry","Force Majeure","Natu=
ral Disaster","Thunderstrike","Equipment Damaged","Grid Outage Site went do=
wn because Gen Failed to Start  due to Relay 220V faulty caused by heavy ra=
in and lightning strike on site// He bypass Relay and Manually Started the =
Gen ","ludivine.ngamaleu@ihstowers.com","186","16-03-2025 20:30:11","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004590885","E=
MANA BILICK CITY","","16-03-2025 20:28:22","16-03-2025 20:22:08","16-03-202=
5 21:13:08","Grid outage, site went down because gen start and stopped due =
to high temp // He added water and manually start the gen","Fabrice Pouakam=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid outage, site went down because gen start and stopped d=
ue to high temp // He added water and manually start the gen","ludivine.nga=
maleu@ihstowers.com","376","16-03-2025 20:28:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004590759","Angongo"=
,"","16-03-2025 20:05:21","16-03-2025 19:32:02","17-03-2025 02:02:25","Casc=
aded Incident from TTO4663515","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to work(Brice William =
673923777)/BOTCOM/ Swapp of batteries) // End of work","system","1246406","=
16-03-2025 20:05:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004590719","E=
beba","IHS_YND_335","16-03-2025 20:04:17","16-03-2025 19:32:02","16-03-2025=
 20:26:02","Gen only site, Site went down because gen fails to start due to=
 hybrid systeme dysfunctionning // Reset done and gen started","Fanda Brice=
","Equipment Repair","Passive","Hybrid","Hybrid Module","Gen only site, Sit=
e went down because gen fails to start due to hybrid systeme dysfunctionnin=
g // Reset done and gen started","ludivine.ngamaleu@ihstowers.com","1936","=
16-03-2025 20:04:17","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004590410","Jou=
vence Mbenda","","16-03-2025 19:16:48","16-03-2025 19:16:39","16-03-2025 19=
:52:39","Site went down because gen fails to start due to grid bad voltage =
// He bypass grid and manually start the gen","Hyemafo Gildas","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Site went dow=
n because gen fails to start due to grid bad voltage // He bypass grid and =
manually start the gen","ferot.nongni-djiogap@sagemcom.com","10","16-03-202=
5 19:16:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0004590342","A=
fanoya","","16-03-2025 18:56:11","16-03-2025 18:05:20","16-03-2025 19:48:20=
","Grid outage, site went down because gen failed due to gen overload(17KVA=
, 190A) //He reduiced the load, site on gen","Hyemafo Gildas","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage, site went d=
own because gen failed due to gen overload(17KVA, 190A) //He reduiced the l=
oad, site on gen","ludivine.ngamaleu@ihstowers.com","323936","16-03-2025 18=
:56:11","Sagemcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004590338","Ron=
d Point Express1114","","16-03-2025 18:54:26","16-03-2025 18:52:17","16-03-=
2025 19:20:06","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Circuit Breaker Issue","Grid outage, S=
ite went down before Gen start due to poor backup // Gen start automaticall=
y","ferot.nongni-djiogap@sagemcom.com","129","16-03-2025 18:54:26","Sagemco=
m CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004590267","MBI=
MBIM","","16-03-2025 18:46:28","16-03-2025 18:38:20","16-03-2025 20:11:49",=
"Grid outage, Site went down before Gen start due to poor backup // Gen sta=
rt manually","Parker Tchoup","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup // Gen start manually","ferot.nongni-djiogap@sagemcom.co=
m","489","16-03-2025 18:46:28","Sagemcom CMR"
"Closed Complete","Site Down","T2222","IHS_YND_697","NOCINC0004590221","Nom=
ayos-IHS","","16-03-2025 18:37:35","16-03-2025 18:27:29","16-03-2025 19:28:=
29","Site went down because gen fails to start due to lack of phase on site=
 // Normalization done and gen started","Fanda Brice","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Site went down because=
 gen fails to start due to lack of phase on site // Normalization done and =
gen started","ferot.nongni-djiogap@sagemcom.com","607","16-03-2025 18:37:35=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004590147","M=
eyo","IHS_YND_313","16-03-2025 18:24:24","16-03-2025 18:05:20","16-03-2025 =
19:48:20","Grid outage, site went down because gen failed due to gen overlo=
ad(17KVA, 190A) //He reduiced the load, site on gen","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site wen=
t down because gen failed due to gen overload(17KVA, 190A) //He reduiced th=
e load, site on gen","yves.djomo@sagemcom.com","1145","16-03-2025 18:24:24"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004590069","NTU=
I TOWN","","16-03-2025 18:16:00","16-03-2025 18:09:53","16-03-2025 18:13:16=
","Grid outage, Site went down before Gen start due to poor backup // Gen s=
tart automatically","Parker Tchoup","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup // Gen start automatically","ferot.nongni-djiogap=
@sagemcom.com","369","16-03-2025 18:16:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0004589997","A=
n-Marche-Melen","IHS_YND_141","16-03-2025 18:04:13","16-03-2025 18:01:03","=
16-03-2025 23:25:15","Grid outage, No space to deploy MDG // Grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage, No space to deploy MDG // Grid return","yves.djomo@sagemcom.com","1=
91","16-03-2025 18:04:13","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004589859","ODZ=
A CITE MBIA","","16-03-2025 17:42:42","16-03-2025 14:21:28","16-03-2025 18:=
03:02","Site went down due to disjunction of Cb(125A) faulty in PWC // He r=
eplaced it","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier - Circuit Breaker","Site went down due to disjunction of Cb(125A) faul=
ty in PWC // He replaced it","ferot.nongni-djiogap@sagemcom.com","12075","1=
6-03-2025 17:42:42","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004589827","Ole=
mbe MTN","","16-03-2025 17:38:11","16-03-2025 17:34:06","16-03-2025 17:43:0=
5","Grid outage, site went down because gen failed to start due to grid con=
tactor faulty //He bypassed grid contactor and gen manually started","Fabri=
ce Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","G=
rid outage, site went down because gen failed to start due to grid contacto=
r faulty //He bypassed grid contactor and gen manually started","ferot.nong=
ni-djiogap@sagemcom.com","246","16-03-2025 17:38:11","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004589550","UPA=
C LP","","16-03-2025 16:52:35","16-03-2025 16:43:25","16-03-2025 16:43:26",=
"	Active, no power issue, site on grid with U=3D55V Tx FME mand Ngetsa (??6=
99949553??) From Huawei is informed.","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","	Active, no power issu=
e, site on grid with U=3D55V Tx FME mand Ngetsa (??699949553??) From Huawei=
 is informed.","ferot.nongni-djiogap@sagemcom.com","551","16-03-2025 16:52:=
35","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004589342","Lad=
a I Yde","","16-03-2025 16:25:49","16-03-2025 15:43:37","16-03-2025 15:45:3=
9","Active//No power issue site on Grid with U=3D53.4V Lionel Adjep(6551848=
76) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue site on Grid with U=3D53.4V Lionel Adjep(655184876) from Huawei is =
informed","ferot.nongni-djiogap@sagemcom.com","2533","16-03-2025 16:25:49",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004589289","Mon=
tee Jouvence","","16-03-2025 16:19:06","16-03-2025 15:56:46","16-03-2025 17=
:14:44","Site went down due to insufficiency of rectifiers SS IHS Felix ZAM=
BE confirmed // He reduced the load","Hyemafo Gildas","Equipment Repair","P=
assive","Rectifier","Rectifier Module","Site went down due to insufficiency=
 of rectifiers SS IHS Felix ZAMBE confirmed // He reduced the load","ferot.=
nongni-djiogap@sagemcom.com","1341","16-03-2025 16:19:06","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004589275","Man=
guiers Dispensaire","","16-03-2025 16:17:09","16-03-2025 15:53:02","16-03-2=
025 16:53:39","Grid outage, site went down because gen failed to start due =
to grid contactor faulty // He bypassed grid contactor and gen manually sta=
rted","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-A=
MF Issue","Grid outage, site went down because gen failed to start due to g=
rid contactor faulty // He bypassed grid contactor and gen manually started=
","ferot.nongni-djiogap@sagemcom.com","1448","16-03-2025 16:17:09","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0004589243","A=
hala","","16-03-2025 16:10:58","16-03-2025 16:03:08","16-03-2025 16:20:32",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down because Gen overload (17kva, 250A) SS =
IHS Felix ZAMBE confirmed// Grid return","yves.djomo@sagemcom.com","273464"=
,"16-03-2025 16:10:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004589239","N=
kolfon Cimencam","","16-03-2025 16:09:53","16-03-2025 16:03:08","16-03-2025=
 16:20:32","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down because Gen overload (17kva=
, 250A) SS IHS Felix ZAMBE confirmed// Grid return","yves.djomo@sagemcom.co=
m","273464","16-03-2025 16:09:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004589238","N=
koabang Ebolmedjock","","16-03-2025 16:09:27","16-03-2025 15:23:19","16-03-=
2025 15:25:53","Active//No power issue, Site on Gen. The Tx FME Brice Tsagu=
e(650214096) from Huawei is informed. Notice that it is impacted by Nkolmes=
seng-Abom Not Manager By IHS","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","Affected by 3rd Party Site","Active=
//No power issue, Site on Gen. The Tx FME Brice Tsague(650214096) from Huaw=
ei is informed. Notice that it is impacted by Nkolmesseng-Abom Not Manager =
By IHS","ludivine.ngamaleu@ihstowers.com","2769","16-03-2025 16:09:27","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004589220","M=
eyo","IHS_YND_257, IHS_YND_762","16-03-2025 16:08:13","16-03-2025 16:03:08"=
,"16-03-2025 16:20:32","Grid outage, site went down because Gen overload (1=
7kva, 250A) SS IHS Felix ZAMBE confirmed// Grid return","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site =
went down because Gen overload (17kva, 250A) SS IHS Felix ZAMBE confirmed//=
 Grid return","yves.djomo@sagemcom.com","306","16-03-2025 16:08:13","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004589208","N=
goulmekong-Nord","","16-03-2025 16:06:46","16-03-2025 15:54:36","16-03-2025=
 17:14:55","Site went down due to disjunction of Cb(125A) in PWC // He ream=
ed Cb(125A), site on grid","Siligap Boris","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to disjunction of Cb(125=
A) in PWC // He reamed Cb(125A), site on grid","yves.djomo@sagemcom.com","5=
8502","16-03-2025 16:06:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0004589194","K=
ondengui","","16-03-2025 16:04:52","16-03-2025 15:43:46","18-03-2025 00:36:=
26","Active//No power issue, site is on grid with Ubaie=3D54V, Eloundou ber=
trant(652586578) from Huawei is informed","Albran Byorel","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue, site is on grid with Ubaie=3D54V, Eloundou bertrant(6525=
86578) from Huawei is informed","yves.djomo@sagemcom.com","1267","16-03-202=
5 16:04:52","Sagemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0004589191","Aba=
ng","","16-03-2025 16:04:23","16-03-2025 15:35:08","16-03-2025 15:36:17","A=
ctive//No power issue site on Battery  with U=3D49.6V ,The  FME TX Henri (6=
91145055) from Huawei is informed","Mba Lazare Herve","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue site on Battery  with U=3D49.6V ,The  FME TX Henri (691145055=
) from Huawei is informed","ferot.nongni-djiogap@sagemcom.com","1756","16-0=
3-2025 16:04:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004589186","E=
leveur","IHS_YND_277","16-03-2025 16:03:43","16-03-2025 15:54:36","16-03-20=
25 17:14:55","Site went down due to disjunction of Cb(125A) in PWC // He re=
amed Cb(125A), site on grid","Siligap Boris","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Site went down due to disjunc=
tion of Cb(125A) in PWC // He reamed Cb(125A), site on grid","yves.djomo@sa=
gemcom.com","548","16-03-2025 16:03:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004589174","E=
mana lycee 2","IHS_YND_274","16-03-2025 16:01:28","16-03-2025 15:33:20","16=
-03-2025 17:24:36","Site went down due to disjunction of  Cb(80A)  in PWC /=
/ He bypassed Cb(80A), site on grid","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went=
 down due to disjunction of  Cb(80A)  in PWC // He bypassed Cb(80A), site o=
n grid","yves.djomo@sagemcom.com","1689","16-03-2025 16:01:28","Sagemcom CM=
R"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004589169","Com=
plex Beac II","","16-03-2025 16:00:37","16-03-2025 15:12:25","16-03-2025 16=
:27:39","Grid outage, Site went down before Gen start due to poor backup //=
 Gen manually started","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup // Gen manually started","ferot.nongni-djiogap=
@sagemcom.com","2893","16-03-2025 16:00:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004589162","E=
mana Lycee","","16-03-2025 15:59:08","16-03-2025 15:33:20","16-03-2025 17:2=
4:36","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive"," Site went down due to disjunction of CB 80 A in PWC // He =
bypassed CB 80 A, site on grid","yves.djomo@sagemcom.com","275518","16-03-2=
025 15:59:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004589146","B=
astos Bir","","16-03-2025 15:57:18","16-03-2025 15:31:13","16-03-2025 15:59=
:50","grid outage, Site went down because gen failed to start due to increa=
se in load// He reduced rectifiers, site on gen","Mboua Thierry","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","grid outage, Site went dow=
n because gen failed to start due to increase in load// He reduced rectifie=
rs, site on gen","ferot.nongni-djiogap@sagemcom.com","1566","16-03-2025 15:=
57:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0004589105","N=
ew-Marche-Melen","","16-03-2025 15:50:50","16-03-2025 18:01:03","16-03-2025=
 23:25:15","Grid outage, No space to deploy MDG // Grid return","Paul BIBOU=
M","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid out=
age, No space to deploy MDG // Grid return","ludivine.ngamaleu@ihstowers.co=
m","316930","16-03-2025 15:50:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004589024","M=
vog-Manga","","16-03-2025 15:43:20","16-03-2025 15:09:11","16-03-2025 16:09=
:07","Grid outage, site went down because gen fails to start due to gen car=
d dysfunctionning // Gen manually started","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down=
 because gen fails to start due to gen card dysfunctionning // Gen manually=
 started","ferot.nongni-djiogap@sagemcom.com","2051","16-03-2025 15:43:20",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004589015","S=
OA TOWN","","16-03-2025 15:41:49","16-03-2025 15:07:43","16-03-2025 19:52:3=
6","Site went down due to disjunction of Cb(125A) faulty in PWC // He chang=
ed with Cb(2*63A), site on grid","Siligap Boris","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down =
due to disjunction of Cb(125A) faulty in PWC // He changed with Cb(2*63A), =
site on grid","ferot.nongni-djiogap@sagemcom.com","2047","16-03-2025 15:41:=
49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004588946","S=
tade-Abega","","16-03-2025 15:33:03","16-03-2025 15:01:58","16-03-2025 15:4=
6:03","Grid outage site went down because Gen failed to start due PWC dysfo=
nction // He reset the PWC and Gen manually started","Mba Lazare Herve","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid o=
utage site went down because Gen failed to start due PWC dysfonction // He =
reset the PWC and Gen manually started","ferot.nongni-djiogap@sagemcom.com"=
,"1866","16-03-2025 15:33:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004588847","M=
ini-Ferme","","16-03-2025 15:24:46","16-03-2025 14:58:29","16-03-2025 16:05=
:59","Grid outage.no space to deploy mobile gen // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deploy mobile gen // Grid return","ludivine.ngamaleu@ihstowers.com=
","1578","16-03-2025 15:24:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004588842","S=
atcom","","16-03-2025 15:23:44","16-03-2025 14:58:36","16-03-2025 14:59:13"=
,"Active//No power issue site on Grid with U=3D50,06 V. The Tx Fme Armand N=
gestsa (691144412) of Huawei is informed.","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue site on Grid with U=3D50,06 V. The Tx Fme Armand Ngests=
a (691144412) of Huawei is informed.","ludivine.ngamaleu@ihstowers.com","15=
09","16-03-2025 15:23:44","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004588821","Awa=
e Ewonkan","","16-03-2025 15:22:08","16-03-2025 15:04:45","16-03-2025 15:50=
:55","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed// He reduced load and started Gen manualy","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, Site went down because Gen overload(20KVA,310A) SS IHS Alphonse DEFF=
O is informed// He reduced load and started Gen manualy","ferot.nongni-djio=
gap@sagemcom.com","1044","16-03-2025 15:22:08","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004588773","Ebo=
go","","16-03-2025 15:15:44","16-03-2025 15:02:30","16-03-2025 15:24:30","G=
rid outage, Site went down before Gen start due to poor backup// Gen start =
automatically","Siligap Boris","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, Site went down before Gen star=
t due to poor backup// Gen start automatically","ferot.nongni-djiogap@sagem=
com.com","795","16-03-2025 15:15:44","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004588764","Beh=
ind P T school Yde","","16-03-2025 15:15:03","16-03-2025 15:02:50","16-03-2=
025 16:00:09","Grid outage, site went down because gen fails to start due t=
o gen card faulty // Gen manually started","Paul BIBOUM","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down b=
ecause gen fails to start due to gen card faulty // Gen manually started","=
ferot.nongni-djiogap@sagemcom.com","734","16-03-2025 15:15:03","Sagemcom CM=
R"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004588748","Bar=
riere","","16-03-2025 15:12:46","16-03-2025 14:58:38","16-03-2025 16:20:38"=
,"Site went down because Gen overload(20kva,400 A) IHS SS Felix Zambe is in=
formed and confirmed // Grid return","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Site went down because Gen overload(2=
0kva,400 A) IHS SS Felix Zambe is informed and confirmed // Grid return","f=
erot.nongni-djiogap@sagemcom.com","1529","16-03-2025 15:12:46","Sagemcom CM=
R"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004588745","ELO=
UMDEM CARRIERE","","16-03-2025 15:11:31","16-03-2025 15:00:23","16-03-2025 =
16:21:23","Grid outage, site went down because gen fails to start // Grid r=
eturn(Investigation ongoing)","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage, site went down because gen fa=
ils to start // Grid return(Investigation ongoing)","ferot.nongni-djiogap@s=
agemcom.com","669","16-03-2025 15:11:31","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004588740","ETO=
UDI Entree du palais","","16-03-2025 15:10:28","16-03-2025 15:00:18","16-03=
-2025 16:44:25","Grid ouatge, site went down because gen failed to start du=
e to  gen card malfunction // He reset gen card, site on grid","Fabrice Pou=
akam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
ouatge, site went down because gen failed to start due to  gen card malfunc=
tion // He reset gen card, site on grid","ferot.nongni-djiogap@sagemcom.com=
","611","16-03-2025 15:10:28","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004588695","Mes=
sassi 2","","16-03-2025 15:05:08","16-03-2025 15:00:49","16-03-2025 15:46:0=
5","Grid outage, Site went down due to PWC overload(12 kilo, 260A), Felix b=
ateu IHS is informed //He reset the rectifiers, Gen manully started","Fabri=
ce Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Over=
loaded","Grid outage, Site went down due to PWC overload(12 kilo, 260A), Fe=
lix bateu IHS is informed //He reset the rectifiers, Gen manully started","=
ferot.nongni-djiogap@sagemcom.com","261","16-03-2025 15:05:08","Sagemcom CM=
R"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004588682","Tou=
ring Club International","","16-03-2025 15:02:41","16-03-2025 14:56:26","16=
-03-2025 15:40:15","Grid Outage Site went down because Gen overload (20KVA,=
 270A) SS IHS Pascaline confirmed // Grid return","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went dow=
n because Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // Grid ret=
urn","ferot.nongni-djiogap@sagemcom.com","376","16-03-2025 15:02:41","Sagem=
com CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004588667","Nko=
ulou Carriere carrefourt","","16-03-2025 15:01:40","16-03-2025 14:55:30","1=
6-03-2025 14:58:36","Grid outage, site went down because due to Gen overloa=
d(20kva,310 A) IHS SS Alphonse is informed// We reduce load and gen manuall=
y started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage, site went down because due to Gen overload(20kva=
,310 A) IHS SS Alphonse is informed// We reduce load and gen manually start=
ed","ferot.nongni-djiogap@sagemcom.com","371","16-03-2025 15:01:40","Sagemc=
om CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004588649","Crf=
-Nsam","","16-03-2025 14:58:33","16-03-2025 14:53:23","16-03-2025 16:20:45"=
,"Grid outage,DG failed to start // Grid restored (investigationg ongoing).=
","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid outage,DG failed to start // Grid restored (investigationg ongo=
ing).","ferot.nongni-djiogap@sagemcom.com","918","16-03-2025 14:58:33","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004588611","M=
EHANDAN","","16-03-2025 14:56:03","16-03-2025 14:53:51","16-03-2025 14:57:4=
5","Site went down due to insufficiency of rectifiers on site SS IHS Pascal=
ine is confirm // He reduced the load","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down due to insufficienc=
y of rectifiers on site SS IHS Pascaline is confirm // He reduced the load"=
,"ferot.nongni-djiogap@sagemcom.com","134","16-03-2025 14:56:03","Sagemcom =
CMR"
"Closed Complete","Warning","CTR_414","IHS_YND_202","NOCINC0004588566","Cit=
e-Verte","","16-03-2025 14:47:52","","","Grid outage//grid return","","Warn=
ing","Warning","POWER","Warning - Site on Battery","Grid outage//grid retur=
n","ferot.nongni-djiogap@sagemcom.com","1865","16-03-2025 14:47:52","Sagemc=
om CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004588529","Jea=
n Vespa","","16-03-2025 14:42:05","16-03-2025 14:37:41","16-03-2025 15:31:4=
1","Site went down because gen failed to start due to grid bad voltage and =
no RCP // Gen manually started","Mboua Thierry","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","Site went down because gen f=
ailed to start due to grid bad voltage and no RCP // Gen manually started",=
"ferot.nongni-djiogap@sagemcom.com","265","16-03-2025 14:42:05","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004588465","Jean Ves=
pa 2","","16-03-2025 14:35:01","16-03-2025 14:29:55","16-03-2025 15:23:45",=
"Cascaded Incident from TTO4660893","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because gen failed =
to start due to grid bad voltage and no RCP // Gen manually started","syste=
m","272138","16-03-2025 14:35:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004588458","J=
-Vespa","IHS_YND_544","16-03-2025 14:34:01","16-03-2025 14:29:55","16-03-20=
25 15:23:45","Site went down because gen failed to start due to grid bad vo=
ltage and no RCP // Gen manually started","Mboua Thierry","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Site went down bec=
ause gen failed to start due to grid bad voltage and no RCP // Gen manually=
 started","ferot.nongni-djiogap@sagemcom.com","247","16-03-2025 14:34:01","=
Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004588305","Mes=
sa Carriere","","16-03-2025 14:06:41","16-03-2025 13:57:27","16-03-2025 15:=
31:27","grid outage, site went dow because gen failed to start due to gen c=
ard faulty // Gen manually started","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","grid outage, site went dow because=
 gen failed to start due to gen card faulty // Gen manually started","yves.=
djomo@sagemcom.com","555","16-03-2025 14:06:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004588273","Eto koss=
 Yde","","16-03-2025 14:01:50","16-03-2025 12:51:51","16-03-2025 16:17:40",=
"Cascaded Incident from TTO4660222","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work: SS IHS A=
lphone DEFFO and Felix ZAMBE working on site","system","299357","16-03-2025=
 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004588274","ELOUMDEM=
 CARRIERE 2","","16-03-2025 14:01:50","16-03-2025 12:51:51","16-03-2025 16:=
17:40","Cascaded Incident from TTO4660222","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work: S=
S IHS Alphone DEFFO and Felix ZAMBE working on site","system","299357","16-=
03-2025 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004588057","Mon=
tee Jouvence","","16-03-2025 13:24:05","16-03-2025 13:19:01","16-03-2025 13=
:37:09","Site went down due to insufficiency of rectifiers SS IHS Felix ZAM=
BE confirmed // He reduced the load","Hyemafo Gildas","Equipment Repair","P=
assive","Rectifier","Rectifier Module","Site went down due to insufficiency=
 of rectifiers SS IHS Felix ZAMBE confirmed // He reduced the load","yves.d=
jomo@sagemcom.com","305","16-03-2025 13:24:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004587938","N=
koabang Ebolmedjock","","16-03-2025 13:08:20","16-03-2025 13:03:17","16-03-=
2025 13:10:47","Active//No power issue, Site on Gen. The Tx FME Brice Tsagu=
e(650214096) from Huawei is informed. Notice that it is impacted by Nkolmes=
seng-Abom Not Manager By IHS","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue, Site on Gen. The Tx FME Brice Tsague(650214096) from Huawei is in=
formed. Notice that it is impacted by Nkolmesseng-Abom Not Manager By IHS",=
"yves.djomo@sagemcom.com","304","16-03-2025 13:08:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004587889","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","16-03-2025 12:56:56","16-03-2025 12:51=
:51","16-03-2025 16:17:40","Site went down due to work: SS IHS Alphone DEFF=
O and Felix ZAMBE working on site","Fanda Brice","Installation Activity","P=
assive","Planned Activity","Installation Activity","Site went down due to w=
ork: SS IHS Alphone DEFFO and Felix ZAMBE working on site","yves.djomo@sage=
mcom.com","307","16-03-2025 12:56:56","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004587882","ODZ=
A CITE MBIA","","16-03-2025 12:55:34","16-03-2025 12:52:23","16-03-2025 13:=
52:22","Site went down due to CB(125A)faulty in the DC-BOX// He replaced th=
e CB(125 A) and Site is on Grid ","Albran Byorel","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down=
 due to CB(125A)faulty in the DC-BOX// He replaced the CB(125 A) and Site i=
s on Grid ","el-dalile@sagemcom.com","192","16-03-2025 12:55:34","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004587858","C=
omplexe-BEAC","","16-03-2025 12:51:42","16-03-2025 12:49:32","16-03-2025 12=
:52:11","Grid Outage, site went down before gen start due to poor battery b=
ackup // Gen started automatically","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid Outage, site went=
 down before gen start due to poor battery backup // Gen started automatica=
lly","yves.djomo@sagemcom.com","131","16-03-2025 12:51:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004587666","M=
efou-Assi","","16-03-2025 12:16:42","16-03-2025 12:13:38","16-03-2025 12:14=
:45","Error ticket","Fanda Brice","Incorrectly Logged Tickets","Error","Err=
or","Error","Error ticket","yves.djomo@sagemcom.com","185","16-03-2025 12:1=
6:42","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004587438","Man=
guiers Dispensaire","","16-03-2025 11:37:04","16-03-2025 11:34:59","16-03-2=
025 11:49:56","Grid outage site went down because Gen failed to start due t=
o grid contactor faulty // Grid return","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","ATS-AMF Issue","Grid outage site went down bec=
ause Gen failed to start due to grid contactor faulty // Grid return","yves=
.djomo@sagemcom.com","126","16-03-2025 11:37:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004587425","B=
iteng-Maetur","","16-03-2025 11:33:14","16-03-2025 10:59:01","16-03-2025 13=
:56:48","Grid outage, Site went down because  Gen overload(20kva, 280A) SS =
IHS Alphonse DEFFO confirmed //Grid return","Mba Lazare Herve","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down =
because  Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed //Grid r=
eturn","yves.djomo@sagemcom.com","2055","16-03-2025 11:33:14","Sagemcom CMR=
"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004587344","Lad=
a I Yde","","16-03-2025 11:24:20","16-03-2025 11:21:03","16-03-2025 11:56:4=
8","Site went down because 2/3 rectifiers disfunctionning due to Grid bad v=
oltage// He reset rectifiers, Site on Gen","Mba Lazare Herve","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down because 2/3 =
rectifiers disfunctionning due to Grid bad voltage// He reset rectifiers, S=
ite on Gen","el-dalile@sagemcom.com","198","16-03-2025 11:24:20","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004587294","B=
iyemassi LAC","","16-03-2025 11:14:42","16-03-2025 11:07:30","16-03-2025 14=
:13:52","Grid outage ,no space to deploy mobile gen //Grid power restored",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage ,no space to deploy mobile gen //Grid power restored","el-dalile@sa=
gemcom.com","433","16-03-2025 11:14:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004587168","Emana Ly=
cee","","16-03-2025 10:55:20","16-03-2025 10:52:51","16-03-2025 11:49:54","=
Cascaded Incident from TTO4659381","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because CB(80A) tr=
ipped in PWC who feeds equipments OCM due to Grid bad voltage  // CB put ba=
ck on, site on Gen ","system","270750","16-03-2025 10:55:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004587164","E=
mana lycee 2","IHS_YND_274","16-03-2025 10:54:54","16-03-2025 10:52:51","16=
-03-2025 11:49:54","Site went down because CB(80A) tripped in PWC who feeds=
 equipments OCM due to Grid bad voltage  // CB put back on, site on Gen ","=
Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Circuit Breaker Issue","Site went down because CB(80A) tripped in PWC w=
ho feeds equipments OCM due to Grid bad voltage  // CB put back on, site on=
 Gen ","yves.djomo@sagemcom.com","124","16-03-2025 10:54:54","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004587095","Beh=
ind P T school Yde","","16-03-2025 10:43:37","16-03-2025 10:39:22","16-03-2=
025 10:48:12","Grid outage, site went down because gen failed to start due =
to gen card faulty //Grid restored","Paul BIBOUM","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
gen failed to start due to gen card faulty //Grid restored","el-dalile@sage=
mcom.com","256","16-03-2025 10:43:37","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004587087","Mes=
sassi 2","","16-03-2025 10:42:07","16-03-2025 10:34:48","16-03-2025 10:52:0=
9","Site went down due to PWC overload(12 kilo, 260A), Felix bateu IHS conf=
irmed// he reduiced the load","Fabrice Pouakam","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Site went down due to PWC over=
load(12 kilo, 260A), Felix bateu IHS confirmed// he reduiced the load","el-=
dalile@sagemcom.com","440","16-03-2025 10:42:07","Sagemcom CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004587086","Sca=
lom","","16-03-2025 10:41:55","16-03-2025 10:37:51","16-03-2025 10:53:01","=
Grid Outage, site went down before gen start due to poor battery backup // =
Gen started automatically","Paul BIBOUM","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid Outage, site went down befor=
e gen start due to poor battery backup // Gen started automatically","yves.=
djomo@sagemcom.com","245","16-03-2025 10:41:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_005","NOCINC0004586729","Imm-Olym=
pique","","16-03-2025 09:27:11","16-03-2025 08:35:33","16-03-2025 08:40:03"=
,"Cascaded Incident from TTO4658518","Paul BIBOUM","Cascade Outage","Active=
","Cascade Active","Cascade Active","ACTIVE// No power issue site on Grid w=
ith U=3D53.7v The FME TX Brice stague(65072631) from HUAWEI is informed. Im=
pacted by CNPS nodal No manager by IHS","system","264546","16-03-2025 09:27=
:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004586528","B=
iteng-Maetur","","16-03-2025 08:49:36","16-03-2025 08:41:32","16-03-2025 10=
:53:00","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the=
 load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, Site went down because Gen started and stopped due t=
o Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced th=
e load","yves.djomo@sagemcom.com","485","16-03-2025 08:49:36","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_014","IHS_YND_003","NOCINC0004586414","M=
ercure","IHS_YND_007, IHS_YND_005, IHS_YND_012","16-03-2025 08:42:37","16-0=
3-2025 08:35:33","16-03-2025 08:40:03","ACTIVE// No power issue site on Gri=
d with U=3D53.7v The FME TX Brice stague(65072631) from HUAWEI is informed.=
 Impacted by CNPS nodal No manager by IHS","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No power=
 issue site on Grid with U=3D53.7v The FME TX Brice stague(65072631) from H=
UAWEI is informed. Impacted by CNPS nodal No manager by IHS","yves.djomo@sa=
gemcom.com","424","16-03-2025 08:42:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004586166","T=
amtam Weekend","","16-03-2025 07:49:32","16-03-2025 07:10:30","16-03-2025 1=
4:29:19","Site will be stiil down at ocm due to insufficiency of rectifiers=
 (2/8 rectififiers faulties) IHS SS Felix Zambe is confirmed//we replace th=
ese rectifiers ","Hyemafo Gildas","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site will be stiil down at ocm due to insufficiency of =
rectifiers (2/8 rectififiers faulties) IHS SS Felix Zambe is confirmed//we =
replace these rectifiers ","yves.djomo@sagemcom.com","2343","16-03-2025 07:=
49:32","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004586122","Crf=
-Mbankolo-IHS","","16-03-2025 07:39:23","15-03-2025 23:50:15","16-03-2025 0=
3:52:59","Site went down due to MPR DYSFONNCTION on site SS IHS Bernard ATA=
NGANA confirmed // He reset the MPR","Mboua Thierry","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Cabinet","Site went down due to MPR DYSFONNCT=
ION on site SS IHS Bernard ATANGANA confirmed // He reset the MPR","yves.dj=
omo@sagemcom.com","28149","16-03-2025 07:39:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0004586099","Damas","=
","16-03-2025 07:29:50","16-03-2025 07:07:02","16-03-2025 07:10:10","Cascad=
ed Incident from TTO4658127","MINKA NICOLAS","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE// No power issue on site, site on Gri=
d with Ubaie=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is inf=
ormed","system","262853","16-03-2025 07:29:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0004586100","Tamtam W=
eekend","","16-03-2025 07:29:50","16-03-2025 07:07:02","16-03-2025 07:10:10=
","Cascaded Incident from TTO4658127","Hyemafo Gildas","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","ACTIVE// No power issue on site, s=
ite on Grid with Ubaie=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUA=
WEI is informed","system","262854","16-03-2025 07:29:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004586098","Accacia =
New","","16-03-2025 07:29:50","16-03-2025 07:07:02","16-03-2025 07:10:10","=
Cascaded Incident from TTO4658127","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","ACTIVE// No power issue on site, site on Grid with =
Ubaie=3D54.1V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed",=
"system","262853","16-03-2025 07:29:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004586070","M=
ontee-Jouvence-II","IHS_YND_562, IHS_YND_166, IHS_YND_151","16-03-2025 07:2=
1:14","16-03-2025 07:07:02","16-03-2025 07:10:10","ACTIVE// No power issue =
on site, site on Grid with Ubaie=3D54.1V The Tx Fme Mbah Hosiah //674007438=
/ from HUAWEI is informed","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No power i=
ssue on site, site on Grid with Ubaie=3D54.1V The Tx Fme Mbah Hosiah //6740=
07438/ from HUAWEI is informed","yves.djomo@sagemcom.com","854","16-03-2025=
 07:21:14","Sagemcom CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004585929","Eto=
ug ebe Carrefour","","16-03-2025 06:49:42","16-03-2025 06:46:29","16-03-202=
5 08:36:10","Grid outage, Site went down because Gen failed to start due to=
 Grid bad voltage(LACK 02 PHASE ) and poor backup //He bypassed Grid and st=
arted Gen manualy","Hyemafo Gildas","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Grid outage, Site went down because Gen =
failed to start due to Grid bad voltage(LACK 02 PHASE ) and poor backup //H=
e bypassed Grid and started Gen manualy","el-dalile@sagemcom.com","193","16=
-03-2025 06:49:42","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004585773","Ole=
mbe MTN","","16-03-2025 06:05:51","16-03-2025 05:59:35","16-03-2025 07:57:5=
2","Grid outage, site went down because gen failed to start due to grid con=
tactor faulty // He bypassed ATS and Gen manually started","Fabrice Pouakam=
","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage=
, site went down because gen failed to start due to grid contactor faulty /=
/ He bypassed ATS and Gen manually started","ferot.nongni-djiogap@sagemcom.=
com","377","16-03-2025 06:05:51","Sagemcom CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004585376","Eto=
ug ebe Carrefour","","16-03-2025 03:33:04","16-03-2025 03:15:57","16-03-202=
5 03:33:57","Grid outage, Site went down before Gen start due to poor backu=
p// Gen Automatically Started","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup// Gen Automatically Started","ferot.n=
ongni-djiogap@sagemcom.com","1028","16-03-2025 03:33:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004585366","Mambine"=
,"","16-03-2025 03:32:01","16-03-2025 03:15:45","16-03-2025 03:56:38","Casc=
aded Incident from TTO4657320","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","grid bad voltage,and gen failed to start =
//he did a bridge on good phase","system","1225782","16-03-2025 03:32:01","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004585363","Sous Pre=
fecture","","16-03-2025 03:32:00","16-03-2025 03:15:45","16-03-2025 03:56:3=
8","Cascaded Incident from TTO4657320","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid bad voltage,and gen failed t=
o start //he did a bridge on good phase","system","1225782","16-03-2025 03:=
32:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004585365","Nomayos-=
IHS","","16-03-2025 03:32:00","16-03-2025 03:15:45","16-03-2025 03:56:38","=
Cascaded Incident from TTO4657320","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid bad voltage,and gen failed to st=
art //he did a bridge on good phase","system","1225783","16-03-2025 03:32:0=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004585364","Mbankomo=
 IHS","","16-03-2025 03:32:00","16-03-2025 03:15:45","16-03-2025 03:56:38",=
"Cascaded Incident from TTO4657320","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid bad voltage,and gen failed to s=
tart //he did a bridge on good phase","system","1225783","16-03-2025 03:32:=
00","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004585359","Lad=
a I Yde","","16-03-2025 03:29:21","16-03-2025 03:22:14","16-03-2025 05:34:3=
4","Grid outage, Site went down because Gen failed to start// Grid return (=
investigation ongoing)","Mba Lazare Herve","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage, Site went down because Gen fai=
led to start// Grid return (investigation ongoing)","ferot.nongni-djiogap@s=
agemcom.com","428","16-03-2025 03:29:21","Sagemcom CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004585357","Nom=
ayos","IHS_YND_314, IHS_YND_695, IHS_YND_697, IHS_YND_350","16-03-2025 03:2=
7:55","16-03-2025 03:15:45","16-03-2025 04:06:08","Grid bad voltage,and gen=
 failed to start //he did a bridge on good phase","Fanda Brice","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid bad vol=
tage,and gen failed to start //he did a bridge on good phase","ferot.nongni=
-djiogap@sagemcom.com","775","16-03-2025 03:27:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004585277","B=
iteng","","16-03-2025 02:55:43","16-03-2025 02:49:35","16-03-2025 02:59:43"=
,"Grid outage site went down because Gen failed to start due PWC dysfonctio=
n // He reset the PWC and Gen manually started","Mba Lazare Herve","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage=
 site went down because Gen failed to start due PWC dysfonction // He reset=
 the PWC and Gen manually started","ferot.nongni-djiogap@sagemcom.com","369=
","16-03-2025 02:55:43","Sagemcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0004585273","Nko=
lbisson usine des eaux","","16-03-2025 02:52:40","16-03-2025 02:40:35","16-=
03-2025 06:46:47","Grid outage, site went down because gen failed to start =
and stopped with alarm over current due to Gen overload // He reduced the l=
oad, site on gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage, site went down because gen failed=
 to start and stopped with alarm over current due to Gen overload // He red=
uced the load, site on gen","ferot.nongni-djiogap@sagemcom.com","811","16-0=
3-2025 02:52:40","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004585122","OTE=
LE MTN","","16-03-2025 01:41:32","16-03-2025 01:38:25","16-03-2025 02:20:31=
","Grid outage.gen failed to start due to automatism malfunctionning//Gen m=
anually started","Fanda Brice","Equipment Repair","Passive","Control Panel"=
,"ATS-AMF Issue","Grid outage.gen failed to start due to automatism malfunc=
tionning//Gen manually started","ferot.nongni-djiogap@sagemcom.com","188","=
16-03-2025 01:41:32","Sagemcom CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004585117","Eto=
ug ebe Carrefour","","16-03-2025 01:40:49","16-03-2025 01:30:25","16-03-202=
5 01:48:25","Grid outage, Site went down before Gen start due to poor backu=
p // Gen started automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup // Gen started automatically","ferot=
.nongni-djiogap@sagemcom.com","625","16-03-2025 01:40:49","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004584794","Nko=
lmvack","","16-03-2025 00:10:42","16-03-2025 00:09:35","16-03-2025 00:59:52=
","Site went down because gen stopped with alarm high temp//he added water =
in radiator","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG =
- High Engine Temp - Coolant Level Issue","Site went down because gen stopp=
ed with alarm high temp//he added water in radiator","ferot.nongni-djiogap@=
sagemcom.com","68","16-03-2025 00:10:42","Sagemcom CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004584722","Eto=
ug ebe Carrefour","","15-03-2025 23:52:55","15-03-2025 23:49:48","16-03-202=
5 00:07:21","Grid outage, Site went down before Gen start due to poor backu=
p/ // Gen automatically started","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup/ // Gen automatically started","fer=
ot.nongni-djiogap@sagemcom.com","187","15-03-2025 23:52:55","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004584303","Crf=
-Mbankolo-IHS","","15-03-2025 22:15:27","15-03-2025 16:03:37","15-03-2025 2=
3:18:46","Site went down due to MPR DYSFONNCTION on site SS IHS Bernard ATA=
NGANA confirmed // He reset the MPR","Mboua Thierry","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Cabinet","Site went down due to MPR DYSFONNCT=
ION on site SS IHS Bernard ATANGANA confirmed // He reset the MPR","cedric.=
tiani@sagemcom.com","142485","15-03-2025 22:15:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004583915","C=
amp-Sic-Tsinga","","15-03-2025 21:10:37","15-03-2025 21:05:32","15-03-2025 =
21:15:32","No power issue on site U=3D54,5v site on grid Tx fme Brice stagu=
e of huawei is informed","","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,5v si=
te on grid Tx fme Brice stague of huawei is informed","ferot.nongni-djiogap=
@sagemcom.com","306","15-03-2025 21:10:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_110","IHS_YND_028","NOCINC0004583912","H=
-Central","","15-03-2025 21:09:30","15-03-2025 21:04:24","16-03-2025 02:19:=
24","No power issue on site U=3D53,3v site on grid Tx fme Mohamadou of huaw=
ei is informed","Paul BIBOUM","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53,3v =
site on grid Tx fme Mohamadou of huawei is informed","ferot.nongni-djiogap@=
sagemcom.com","306","15-03-2025 21:09:30","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004583878","Beh=
ind P T school Yde","","15-03-2025 21:01:28","15-03-2025 20:55:13","15-03-2=
025 21:01:13","Grid outage,gen failed to start due to card Ge faulty//Ge ma=
nually started","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Grid outage,gen failed to start due to card Ge faulty//G=
e manually started","ferot.nongni-djiogap@sagemcom.com","375","15-03-2025 2=
1:01:28","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004583843","Nko=
lbisson usines des eaux 2","","15-03-2025 20:55:46","15-03-2025 20:48:37","=
16-03-2025 07:02:50","Access isue du to landlord Site went down because CB(=
125A) tripped in PWC due to load increase// CB put back on ","TIENTCHEU NZE=
TCHIEU GAEL","Access Denial","Lease Or Legal","Landlord Related Issues","Ac=
cess Issue - Land Lord","Access isue du to landlord Site went down because =
CB(125A) tripped in PWC due to load increase// CB put back on ","ferot.nong=
ni-djiogap@sagemcom.com","430","15-03-2025 20:55:46","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004583838","Mes=
sa Carriere","","15-03-2025 20:54:44","15-03-2025 20:45:33","15-03-2025 20:=
55:33","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty //Grid return","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because Gen =
failed to started due to Gen card faullty //Grid return","ferot.nongni-djio=
gap@sagemcom.com","552","15-03-2025 20:54:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004583483","M=
ontee-Jouvence-II","","15-03-2025 19:47:50","15-03-2025 19:44:45","15-03-20=
25 21:23:45","Grid outage, Site went down because Gen overload (15kva, 250A=
)  SS IHS Felix Zambe is informed//Grid return","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went dow=
n because Gen overload (15kva, 250A)  SS IHS Felix Zambe is informed//Grid =
return","ferot.nongni-djiogap@sagemcom.com","186","15-03-2025 19:47:50","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004583477","Nko=
ulou Carriere carrefourt","","15-03-2025 19:46:30","15-03-2025 19:45:25","1=
5-03-2025 20:27:25","Access issue due to land load Grid outage, site went d=
own because due to Gen overload(20kva,310 A) IHS SS Alphonse is informed// =
We reduce load and gen manually started","Mba Lazare Herve","Access Denial"=
,"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Acc=
ess issue due to land load Grid outage, site went down because due to Gen o=
verload(20kva,310 A) IHS SS Alphonse is informed// We reduce load and gen m=
anually started","ferot.nongni-djiogap@sagemcom.com","66","15-03-2025 19:46=
:30","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004583470","NKO=
MEKUI OCM","","15-03-2025 19:45:24","15-03-2025 19:40:16","15-03-2025 20:50=
:52","No power issue on site U=3D54.5 V site on Gen.Site impacted by Mbanko=
lo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site U=3D54.5 V site on Gen.Site impacted by Mbankolo Camt=
el and not managing by IHS","ferot.nongni-djiogap@sagemcom.com","310","15-0=
3-2025 19:45:24","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0004583446","Mim=
boman3","","15-03-2025 19:38:52","15-03-2025 12:38:10","15-03-2025 15:21:56=
","","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier=
 Module Overloaded","Grid outage, site went down due to PWC ZTE malfunction=
 // He reset controller and gen manually started","kouoh.jean@ihstowers.com=
","25243","15-03-2025 19:38:52","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004583111","Av =
Kennedy","","15-03-2025 18:46:57","15-03-2025 18:44:51","15-03-2025 19:39:4=
1","Grid outage no space to deploy a MDG // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space t=
o deploy a MDG // Grid return","ferot.nongni-djiogap@sagemcom.com","127","1=
5-03-2025 18:46:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004582612","S=
OA UNIVERSITY STADIUM","","15-03-2025 17:23:17","15-03-2025 15:11:21","15-0=
3-2025 17:27:23","Grid outage, site went down due to gen Overload(20KVA, 13=
0A), Blaise IHS is informed// He reduced the load and gen manually started"=
,"Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage, site went down due to gen Overload(20KVA, 130A), Blaise IHS i=
s informed// He reduced the load and gen manually started","ferot.nongni-dj=
iogap@sagemcom.com","8477","15-03-2025 17:23:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004582581","D=
amas","","15-03-2025 17:16:55","15-03-2025 17:04:50","15-03-2025 17:24:50",=
"Active//No power issue on site, site on Grid with Ubaie=3D 53.6 V TX Huawe=
i Mbah Osiah (674007438)// from Huawei is informed","MINKA NICOLAS","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site, site on Grid with Ubaie=3D 53.6 V TX H=
uawei Mbah Osiah (674007438)// from Huawei is informed","ferot.nongni-djiog=
ap@sagemcom.com","726","15-03-2025 17:16:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004582546","S=
OA TOWN","","15-03-2025 17:13:29","15-03-2025 17:06:16","15-03-2025 17:42:5=
9","Grid outage, site went down because gen fails to start due to gen card =
faulty // Gen manually started","Siligap Boris","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because ge=
n fails to start due to gen card dysfunctionning // Gen manually started","=
ferot.nongni-djiogap@sagemcom.com","434","15-03-2025 17:13:29","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004582422","Nkolkoum=
ou OCM","","15-03-2025 16:45:20","15-03-2025 16:34:26","15-03-2025 17:28:12=
","Cascaded Incident from TTO4653834","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down because gen failed to start and stopped with alarm over current due =
to load // He reduced the load, site on gen","system","278885","15-03-2025 =
16:45:20","Sagemcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0004582420","Nko=
lbisson usine des eaux","IHS_YND_712","15-03-2025 16:44:36","15-03-2025 16:=
34:26","15-03-2025 17:28:12","Grid outage, site went down because gen faile=
d to start and stopped with alarm over current due to load // He reduced th=
e load, site on gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage, site went down because gen fai=
led to start and stopped with alarm over current due to load // He reduced =
the load, site on gen","ferot.nongni-djiogap@sagemcom.com","612","15-03-202=
5 16:44:36","Sagemcom CMR"
"Closed Complete","Site Down","T0537","IHS_YND_225","NOCINC0004582049","Sci=
ence","","15-03-2025 16:03:33","15-03-2025 15:56:24","15-03-2025 18:10:54",=
"Active: No power issue, site is on grid with Ubaie=3D53V, Mbamassa(6580102=
82) / Telis working on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active:=
 No power issue, site is on grid with Ubaie=3D53V, Mbamassa(658010282) / Te=
lis working on site","ferot.nongni-djiogap@sagemcom.com","430","15-03-2025 =
16:03:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004581977","S=
calom-IHS","","15-03-2025 15:56:42","15-03-2025 15:42:22","17-03-2025 11:44=
:42","Grid outage, No space to deploy MDG // Grid return ","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spac=
e to deploy MDG // Grid return ","ferot.nongni-djiogap@sagemcom.com","861",=
"15-03-2025 15:56:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004581905","H=
-Paradis","","15-03-2025 15:38:21","15-03-2025 14:50:58","15-03-2025 15:44:=
29","Grid outage //Grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","Grid outage //Grid return","ferot.nongni-djioga=
p@sagemcom.com","2844","15-03-2025 15:38:21","Sagemcom CMR"
"Closed Complete","Warning","T0351","IHS_YND_146","NOCINC0004581879","Nsime=
yong","","15-03-2025 15:32:48","","","Grid outage,Site went on alarming due=
 to ''high temp''// He added water and start the Gen manually","MINKA NICOL=
AS","Warning","Warning","POWER","Warning - Gen Temp High","Grid outage,Site=
 went on alarming due to ''high temp''// He added water and start the Gen m=
anually","cedric.tiani@sagemcom.com","2470","15-03-2025 15:32:48","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004581871","C=
omplexe-BEAC","","15-03-2025 15:31:35","15-03-2025 14:32:18","15-03-2025 15=
:55:19","Grid outage, site went down before Gen started due to poor battery=
 backup//He start the Gen manually","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before Gen started due to poor battery backup//He start the Gen manua=
lly","danick.tchakouani@sagemcom.com","3558","15-03-2025 15:31:35","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004581855","E=
MANA BILICK CITY","","15-03-2025 15:28:43","15-03-2025 14:52:24","15-03-202=
5 17:01:24","Grid outage.gen ran until fuel shortage//Refueling done","Fabr=
ice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.=
gen ran until fuel shortage//Refueling done","danick.tchakouani@sagemcom.co=
m","2181","15-03-2025 15:28:43","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004581849","Nko=
lbong","","15-03-2025 15:27:38","15-03-2025 15:17:27","15-03-2025 15:31:05"=
,"Grid outage, site went down before gen start due to poor battery back up =
// Grid return","Delor Telezing","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, site went down before gen st=
art due to poor battery back up // Grid return","wilfried.kameni@sagemcom.c=
om","612","15-03-2025 15:27:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004581800","E=
kie-Elegance","","15-03-2025 15:19:37","15-03-2025 15:17:09","15-03-2025 15=
:57:35","Site went down because gen failed to start due to grid bad voltage=
 and no RCP // Gen manually started","Albran Byorel","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Site went down because =
gen failed to start due to grid bad voltage and no RCP // Gen manually star=
ted","danick.tchakouani@sagemcom.com","149","15-03-2025 15:19:37","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004581798","Ole=
mbe MTN","","15-03-2025 15:19:24","15-03-2025 15:13:07","15-03-2025 15:34:3=
5","Grid outage, site went down because gen failed to start due to grid con=
tactor faulty // He bipassed ATS and Gen manually started","Fabrice Pouakam=
","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage=
, site went down because gen failed to start due to grid contactor faulty /=
/ He bipassed ATS and Gen manually started","wilfried.kameni@sagemcom.com",=
"377","15-03-2025 15:19:24","Sagemcom CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0004581783","Ngo=
ulmekong-Nord","","15-03-2025 15:15:35","15-03-2025 15:12:20","15-03-2025 1=
5:18:11","Grid outage, site went down because due to Gen overload(12.5kva,2=
00 A) IHS SS pascaline is informed// We reduce load and gen manually starte=
d","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","Grid outage, site went down because due to Gen overload(12.5kva,200 A) I=
HS SS pascaline is informed// We reduce load and gen manually started","wil=
fried.kameni@sagemcom.com","196","15-03-2025 15:15:35","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004581763","Mes=
sassi 2","","15-03-2025 15:11:33","15-03-2025 15:02:15","15-03-2025 17:08:0=
3","Grid outage, Site went down due to PWC overload(12 kilo, 260A), Felix b=
ateu IHS is informed //He reset the rectifiers, Gen manully started","Fabri=
ce Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Over=
loaded","Grid outage, Site went down due to PWC overload(12 kilo, 260A), Fe=
lix bateu IHS is informed //He reset the rectifiers, Gen manully started","=
wilfried.kameni@sagemcom.com","559","15-03-2025 15:11:33","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004581754","Mon=
tee Jouvence","","15-03-2025 15:09:19","15-03-2025 14:58:07","15-03-2025 22=
:53:26","Site went down due to insufficiency of rectifiers SS IHS Felix ZAM=
BE confirmed // He reduced the load , site on grid","Hyemafo Gildas","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down due t=
o insufficiency of rectifiers SS IHS Felix ZAMBE confirmed // He reduced th=
e load , site on grid","wilfried.kameni@sagemcom.com","673","15-03-2025 15:=
09:19","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004581745","Car=
refour Simbock","IHS_YND_153","15-03-2025 15:07:21","15-03-2025 14:41:00","=
15-03-2025 20:32:16","Grid outage, site went down due to gen overload(17KVA=
,200A), Felix IHS is informed //Grid return","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down d=
ue to gen overload(17KVA,200A), Felix IHS is informed //Grid return","wilfr=
ied.kameni@sagemcom.com","1582","15-03-2025 15:07:21","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004581733","OBA=
M NGOLA OCM","","15-03-2025 15:05:46","15-03-2025 14:56:28","15-03-2025 15:=
52:09","Grid outage site went down because Gen failed to start due to Gen b=
attery discharged causing by charging alternator faulty // Gen manually sta=
rted with external battery","MINKA NICOLAS","Equipment Repair","Passive","A=
CDG Gen","ACDG - Charging Alternator","Grid outage site went down because G=
en failed to start due to Gen battery discharged causing by charging altern=
ator faulty // Gen manually started with external battery","wilfried.kameni=
@sagemcom.com","558","15-03-2025 15:05:46","Sagemcom CMR"
"Closed Complete","Site Down","T0461","IHS_YND_054","NOCINC0004581727","Ole=
zoa MTN","","15-03-2025 15:04:29","15-03-2025 14:57:08","15-03-2025 18:05:0=
8","Site went down due to work: SS IHS FRANCOIS working on site (Change the=
 MPR)// end Of Work","MINKA NICOLAS","Installation Activity","Passive","Pla=
nned Activity","Installation Activity","Site went down due to work: SS IHS =
FRANCOIS working on site (Change the MPR)// end Of Work","wilfried.kameni@s=
agemcom.com","442","15-03-2025 15:04:29","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0004581706","Sap=
eur Mimboman","","15-03-2025 15:01:11","15-03-2025 14:10:30","15-03-2025 15=
:25:51","Grid outage, site went down due to gen overload(20KVA,300A), Alpho=
nse IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to g=
en overload(20KVA,300A), Alphonse IHS is informed // Grid return","wilfried=
.kameni@sagemcom.com","3184","15-03-2025 15:01:11","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004581693","Nko=
zoa","","15-03-2025 14:58:34","15-03-2025 14:26:06","15-03-2025 15:28:36","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed // Grid return","Fabrice Pouakam","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went do=
wn due to gen overload (20kva, 340A) SS HIS Felix bateu is informed and con=
firmed // Grid return","wilfried.kameni@sagemcom.com","2018","15-03-2025 14=
:58:34","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004581680","Com=
plex Beac II","","15-03-2025 14:55:39","15-03-2025 14:34:32","15-03-2025 15=
:36:32","	Site went down because Gen failed to start due to Grid bad voltag=
e  // he bypass the Grid and Gen manually started","Albran Byorel","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","	Site wen=
t down because Gen failed to start due to Grid bad voltage and no RCP on si=
te // he bypass the Grid and Gen manually started","wilfried.kameni@sagemco=
m.com","1268","15-03-2025 14:55:39","Sagemcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004581648","Ron=
d Point Express1114","","15-03-2025 14:52:05","15-03-2025 14:41:00","15-03-=
2025 20:32:16","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage, site went down due to gen overload(17K=
VA,200A), Felix IHS is informed //Grid return","wilfried.kameni@sagemcom.co=
m","300191","15-03-2025 14:52:05","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004581639","Men=
dong vallee","","15-03-2025 14:50:25","15-03-2025 14:37:08","15-03-2025 16:=
07:08","Grid outage, site went down due to gen overload(17KVA,200A), Felix =
IHS is informed//Grid return","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, site went down due to gen overload=
(17KVA,200A), Felix IHS is informed//Grid return","wilfried.kameni@sagemcom=
.com","799","15-03-2025 14:50:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004581443","B=
arriere IHS","","15-03-2025 14:16:26","15-03-2025 13:55:15","15-03-2025 18:=
34:22","Active//No power issue site on Grid with U=3D51,6V.The FME TX  Mbah=
 Osiah (674007438) from Huawei is informed","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue site on Grid with U=3D51,6V.The FME TX  Mbah Osiah (67=
4007438) from Huawei is informed","wilfried.kameni@sagemcom.com","1272","15=
-03-2025 14:16:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004581435","M=
efou-Assi","","15-03-2025 14:15:13","15-03-2025 13:54:03","15-03-2025 15:17=
:07","Grid outage,Site went down due to double disjunction CB(125A*125A) in=
 PWC//He reamed and site on Grid","Fanda Brice","Equipment Repair","Passive=
","Rectifier","Rectifier - Circuit Breaker","Grid outage,Site went down due=
 to double disjunction(125A*125A) in PWC//He reamed and site on Grid","wilf=
ried.kameni@sagemcom.com","1271","15-03-2025 14:15:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0004581430","MEFOU AS=
SI","","15-03-2025 14:14:10","15-03-2025 13:54:54","15-03-2025 15:35:47","C=
ascaded Incident from TTO4652676","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage, site went down due to gen=
 overload(17KVA, 200A), Felix Ngambe IHS is informed // He reduced the load=
, site on gen","system","273944","15-03-2025 14:14:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004581419","S=
IMBOCK BONAMBAPE","IHS_YND_537","15-03-2025 14:12:03","15-03-2025 13:54:54"=
,"15-03-2025 15:35:47","grid outage, site went down due to gen overload(17K=
VA, 200A), Felix Ngambe IHS is informed // He reduced the load, site on gen=
","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","grid outage, site went down due to gen overload(17KVA, 200A), Felix Ngam=
be IHS is informed // He reduced the load, site on gen","wilfried.kameni@sa=
gemcom.com","1030","15-03-2025 14:12:03","Sagemcom CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0004581407","TON=
GOLO SNEC","","15-03-2025 14:09:00","15-03-2025 13:49:37","15-03-2025 15:03=
:56","Grid outage site went because gen ran until fuel shortage//Grid power=
 return","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage site went because gen ran until fuel shortage//Grid power ret=
urn","wilfried.kameni@sagemcom.com","1163","15-03-2025 14:09:00","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_758","NOCINC0004581350","Nkolfoul=
ou CSD MTN","","15-03-2025 13:55:51","15-03-2025 13:47:07","15-03-2025 14:1=
9:51","Cascaded Incident from TTO4652571","Siligap Boris","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
because gen(overload) failed to start due to High temperature// He added wa=
ter and gen manually started","system","281709","15-03-2025 13:55:51","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0004581352","Nkolfoul=
ou Tsinga Village","","15-03-2025 13:55:51","15-03-2025 13:47:07","15-03-20=
25 14:19:51","Cascaded Incident from TTO4652571","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down because gen(overload) failed to start due to High temperature// He a=
dded water and gen manually started","system","281709","15-03-2025 13:55:51=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_296","NOCINC0004581351","Nkolfoul=
ou","","15-03-2025 13:55:51","15-03-2025 13:47:07","15-03-2025 14:19:51","C=
ascaded Incident from TTO4652571","Siligap Boris","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen(overload) failed to start due to High temperature// He added water and =
gen manually started","system","281710","15-03-2025 13:55:51","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004581347","Mvog-Eba=
nda","","15-03-2025 13:55:50","15-03-2025 13:47:07","15-03-2025 14:19:51","=
Cascaded Incident from TTO4652571","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen(overload) failed to start due to High temperature// He added water and=
 gen manually started","system","281710","15-03-2025 13:55:50","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0004581346","FOUGEROL=
E","","15-03-2025 13:55:50","15-03-2025 13:47:07","15-03-2025 14:19:51","Ca=
scaded Incident from TTO4652571","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down because g=
en(overload) failed to start due to High temperature// He added water and g=
en manually started","system","281708","15-03-2025 13:55:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004581349","SOA VILL=
AGE","","15-03-2025 13:55:50","15-03-2025 13:47:07","15-03-2025 14:19:51","=
Cascaded Incident from TTO4652571","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen(overload) failed to start due to High temperature// He added water and=
 gen manually started","system","281708","15-03-2025 13:55:50","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004581348","TSINGA V=
ILLAGE 2","","15-03-2025 13:55:50","15-03-2025 13:47:07","15-03-2025 14:19:=
51","Cascaded Incident from TTO4652571","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen(overload) failed to start due to High temperature// He added wat=
er and gen manually started","system","281708","15-03-2025 13:55:50","Sagem=
com CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0004581336","Nko=
lfoulou 2","IHS_YND_561, IHS_YND_269, IHS_YND_719, IHS_YND_323, IHS_YND_758=
, IHS_YND_296, IHS_YND_759","15-03-2025 13:53:33","15-03-2025 13:47:07","15=
-03-2025 15:06:47","Grid outage, site went down because gen(overload) faile=
d to start due to High temperature// He added water and gen manually starte=
d","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - High Eng=
ine Temp - Coolant Level Issue","Grid outage, site went down because gen(ov=
erload) failed to start due to High temperature// He added water and gen ma=
nually started","wilfried.kameni@sagemcom.com","387","15-03-2025 13:53:33",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0004581234","E=
mombo","","15-03-2025 13:27:53","15-03-2025 13:25:48","15-03-2025 15:23:48"=
,"GRID outage, site went down because gen ran untill fuel shortage // refue=
ling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","GRID outage, site went down because gen ran untill fuel shortage // re=
fueling done","danick.tchakouani@sagemcom.com","126","15-03-2025 13:27:53",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004580979","M=
imboman-Ecole","","15-03-2025 12:50:04","15-03-2025 12:40:35","15-03-2025 1=
5:24:54","Grid outage, site went down because gen ran untill fuel shortage =
// refuelling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Di=
esel Outage","Grid outage, site went down because gen ran untill fuel short=
age // refuelling done","wilfried.kameni@sagemcom.com","571","15-03-2025 12=
:50:04","Sagemcom CMR"
"Cancelled","Warning","T0533","IHS_YND_181","NOCINC0004580964","Mimboman3",=
"","15-03-2025 12:48:23","","","Grid outage, site went down due to PWC ZTE =
malfunction // He reset controller and gen manually started","Mba Lazare He=
rve","","","","","","wilfried.kameni@sagemcom.com","550","15-03-2025 12:48:=
23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0004580953","E=
lig-Essono","","15-03-2025 12:47:22","15-03-2025 12:14:21","16-03-2025 08:4=
0:03","","Paul BIBOUM","Cascade Outage","Active","Cascade Active","Cascade =
Active","ACTIVE// No power issue site on grid with U=3D54.3v The FME TX Bri=
ce stague(65072631) from HUAWEI is  informed. Impacted by CNPS nodal No man=
ager by IHS","wilfried.kameni@sagemcom.com","337818","15-03-2025 12:47:22",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004580945","M=
ontee-Anne-Rouge","","15-03-2025 12:44:39","15-03-2025 12:14:21","16-03-202=
5 08:40:03","ACTIVE// No power issue site on grid with U=3D54.3v The FME TX=
 Brice stague(65072631) from HUAWEI is  informed. Impacted by CNPS nodal No=
 manager by IHS","","Cascade Outage","Active","Cascade Active","Cascade Act=
ive","ACTIVE// No power issue site on grid with U=3D54.3v The FME TX Brice =
stague(65072631) from HUAWEI is  informed. Impacted by CNPS nodal No manage=
r by IHS","wilfried.kameni@sagemcom.com","337819","15-03-2025 12:44:39","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0004580942","I=
mm-Olympique","IHS_YND_007, IHS_YND_012","15-03-2025 12:43:33","15-03-2025 =
12:14:21","15-03-2025 12:20:07","ACTIVE// No power issue site on grid with =
U=3D54.3v The FME TX Brice stague(65072631) from HUAWEI is  informed. Impac=
ted by CNPS nodal No manager by IHS","Paul BIBOUM","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No =
power issue site on grid with U=3D54.3v The FME TX Brice stague(65072631) f=
rom HUAWEI is  informed. Impacted by CNPS nodal No manager by IHS","wilfrie=
d.kameni@sagemcom.com","1753","15-03-2025 12:43:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004580906","Carrefou=
r Ayissi Ele","","15-03-2025 12:35:40","15-03-2025 12:25:48","15-03-2025 12=
:47:59","Cascaded Incident from TTO4652021","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage.gen start and =
stopped due to alarm""high temp""//We added water and gen manually started"=
,"system","272154","15-03-2025 12:35:40","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004580892","Av =
Kennedy","","15-03-2025 12:32:02","15-03-2025 12:22:48","15-03-2025 16:20:3=
5","grid outage, no space to deploy a mobil gen , // grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, =
no space to deploy a mobil gen , // grid return","wilfried.kameni@sagemcom.=
com","555","15-03-2025 12:32:02","Sagemcom CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004580886","Saa=
","IHS_YND_810","15-03-2025 12:31:07","15-03-2025 12:25:48","15-03-2025 12:=
47:59","Grid outage.gen start and stopped due to alarm""high temp""//We add=
ed water and gen manually started","Parker Tchoup","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outag=
e.gen start and stopped due to alarm""high temp""//We added water and gen m=
anually started","wilfried.kameni@sagemcom.com","320","15-03-2025 12:31:07"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004580754","Par=
adis Hotel","","15-03-2025 12:05:03","15-03-2025 11:36:54","15-03-2025 15:4=
7:30","Grid Outage Site went down because Gen FAILED To start due to Alarms=
 ""Underfrequency//He  Manually Started the Gen","Siligap Boris","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage Site went=
 down because Gen FAILED To start due to Alarms ""Underfrequency//He  Manua=
lly Started the Gen","wilfried.kameni@sagemcom.com","1690","15-03-2025 12:0=
5:03","Sagemcom CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0004580695","ESS=
OS OASIS 1111","","15-03-2025 11:54:39","15-03-2025 11:51:34","15-03-2025 1=
2:04:51","Grid outage, Site went down before Gen start due to poor backup/ =
// Gen automatically started","Siligap Boris","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup/ // Gen automatically started","danick.=
tchakouani@sagemcom.com","218","15-03-2025 11:54:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004580658","S=
OA TOWN","","15-03-2025 11:50:39","15-03-2025 11:46:33","15-03-2025 12:27:0=
6","Grid outage.gen start and stopped due to alarm""high temp""//We added w=
ater and gen manually started","Siligap Boris","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.ge=
n start and stopped due to alarm""high temp""//We added water and gen manua=
lly started","danick.tchakouani@sagemcom.com","247","15-03-2025 11:50:39","=
Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004580538","Beh=
ind P T school Yde","","15-03-2025 11:32:19","15-03-2025 11:23:53","15-03-2=
025 13:04:37","Grid outage, site went down because gen failed to start due =
to gen card faulty //Gen manually started","Paul BIBOUM","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down b=
ecause gen failed to start due to gen card faulty //Gen manually started","=
wilfried.kameni@sagemcom.com","507","15-03-2025 11:32:19","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004580524","Eko=
mbitie","","15-03-2025 11:29:33","15-03-2025 11:24:17","15-03-2025 12:22:44=
","Grid outage, Site went down because Gen started and stopped with ""low o=
il pressure"" alarm// He added oil and started Gen manualy","Fabrice Pouaka=
m","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid =
outage, Site went down because Gen started and stopped with ""low oil press=
ure"" alarm// He added oil and started Gen manualy","wilfried.kameni@sagemc=
om.com","378","15-03-2025 11:29:33","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004580273","Men=
dong3","","15-03-2025 10:59:05","15-03-2025 10:50:51","15-03-2025 20:45:19"=
,"Grid outage no space to deploy a mobil gen,// grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spa=
ce to deploy a mobil gen,// grid return","wilfried.kameni@sagemcom.com","49=
5","15-03-2025 10:59:05","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004580125","Elo=
umdem stade","","15-03-2025 10:34:40","15-03-2025 10:26:25","15-03-2025 11:=
04:05","Site went down because the Gen does not support the load // He redu=
ced the load ","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Site went down because the Gen does not support the load // He=
 reduced the load ","wilfried.kameni@sagemcom.com","496","15-03-2025 10:34:=
40","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004580092","HOP=
ITAL GENERAL RAIL YDE","","15-03-2025 10:33:40","15-03-2025 10:17:18","15-0=
3-2025 16:31:35","Grid outage, site went down due to gen Overload(09kva,160=
A), Bernard IHS is informed // Grid return","Delor Telezing","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down du=
e to gen Overload(09kva,160A), Bernard IHS is informed // Grid return","wil=
fried.kameni@sagemcom.com","983","15-03-2025 10:33:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004580089","M=
endong vallee","","15-03-2025 10:32:27","15-03-2025 10:24:14","15-03-2025 1=
1:46:07","Grid outage, site went down because gen start and stopped due to =
high temp // He added water and manually start the gen","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because gen start and stopped due to h=
igh temp // He added water and manually start the gen","wilfried.kameni@sag=
emcom.com","494","15-03-2025 10:32:27","Sagemcom CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004580008","NTE=
MASSI","","15-03-2025 10:17:45","15-03-2025 08:58:29","15-03-2025 10:12:58"=
,"Grid outage, site went down because gen failed start due to gen card faul=
ty // Gen manually started","Delor Telezing","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen f=
ailed start due to gen card faulty // Gen manually started","wilfried.kamen=
i@sagemcom.com","4757","15-03-2025 10:17:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004579990","B=
ATA Mokolo OCM","","15-03-2025 10:16:03","15-03-2025 10:13:49","15-03-2025 =
12:38:26","Grid outage.no space to deploy mobile gen // Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e.no space to deploy mobile gen // Grid return","danick.tchakouani@sagemcom=
.com","135","15-03-2025 10:16:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004579970","M=
ini-Ferme","","15-03-2025 10:13:23","15-03-2025 09:52:15","15-03-2025 10:57=
:55","Grid outage no space to deploy a MDG // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space=
 to deploy a MDG // Grid return","danick.tchakouani@sagemcom.com","1269","1=
5-03-2025 10:13:23","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004579921","CRH=
-Etoug-Ebe","","15-03-2025 10:05:04","15-03-2025 09:56:47","15-03-2025 10:1=
1:17","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"wilfried.kameni@sagemcom.com","499","15-03-2025 10:05:04","Sagemcom CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004579860","Efo=
ulan MTN","","15-03-2025 09:55:51","15-03-2025 09:52:44","15-03-2025 09:57:=
43","Active: no power issue, site is ongrid with Ubaie=3D53V, TX Fme Brice =
Tsague of huawei is informed","MINKA NICOLAS","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power =
issue, site is ongrid with Ubaie=3D53V, TX Fme Brice Tsague of huawei is in=
formed","wilfried.kameni@sagemcom.com","187","15-03-2025 09:55:51","Sagemco=
m CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004579834","Men=
dong NB","","15-03-2025 09:48:52","15-03-2025 09:41:34","15-03-2025 09:50:3=
5","No power issue on site ,site on Gen with Ubaie=3D53.5V The Tx FME Hosia=
h (674007438)  from Huawei is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on si=
te ,site on Gen with Ubaie=3D53.5V The Tx FME Hosiah (674007438)  from Huaw=
ei is informed","wilfried.kameni@sagemcom.com","439","15-03-2025 09:48:52",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0004579831","Mes=
sassi Ngonlonk","","15-03-2025 09:48:24","15-03-2025 09:36:12","15-03-2025 =
10:48:46","Grid outage  site went down because Gen failed to start due to b=
attery GE faulty //Gen manually started with external battery","Fabrice Pou=
akam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","G=
rid outage  site went down because Gen failed to start due to battery GE fa=
ulty //Gen manually started with external battery","danick.tchakouani@sagem=
com.com","733","15-03-2025 09:48:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004579723","K=
oweit City","","15-03-2025 09:29:17","15-03-2025 09:27:03","15-03-2025 09:5=
1:29","Grid outage site went Down because Gen failed to start with alarm lo=
w fuel // He reset the Gen card and Gen manually started","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage =
site went Down because Gen failed to start with alarm low fuel // He reset =
the Gen card and Gen manually started","wilfried.kameni@sagemcom.com","135"=
,"15-03-2025 09:29:17","Sagemcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004579722","Ntu=
i administration","","15-03-2025 09:29:09","15-03-2025 09:24:04","15-03-202=
5 10:42:28","Grid outage, Site went down because gen stopped due to belt cu=
t // He changed belt and Gen manually started","Parker Tchoup","Equipment R=
epair","Passive","ACDG Gen","ACDG - Fan Belt","Grid outage, Site went down =
because gen stopped due to belt cut // He changed belt and Gen manually sta=
rted","danick.tchakouani@sagemcom.com","305","15-03-2025 09:29:09","Sagemco=
m CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004579685","Ngo=
usso Vallee","","15-03-2025 09:19:49","15-03-2025 09:10:39","15-03-2025 10:=
27:13","Grid outage site went down because Gen failed with alarm low fuel /=
/ He reset the Gen card and Gen manually started","Siligap Boris","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site wen=
t down because Gen failed with alarm low fuel // He reset the Gen card and =
Gen manually started","wilfried.kameni@sagemcom.com","551","15-03-2025 09:1=
9:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004579680","N=
kozoa","","15-03-2025 09:18:20","15-03-2025 09:09:15","15-03-2025 11:35:39"=
,"Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Feli=
x bateu is informed and confirmed// He reduced the load and site on GEN","F=
abrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and site on GEN","dan=
ick.tchakouani@sagemcom.com","547","15-03-2025 09:18:20","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004579655","Nko=
lbisson usines des eaux 2","","15-03-2025 09:13:32","15-03-2025 09:01:23","=
15-03-2025 10:22:22","Grid outage, site went down because gen start an stop=
ped with alarm under voltage // He reset gen card and gen manually started"=
,"TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","Grid outage, site went down because gen start an stopped w=
ith alarm under voltage // He reset gen card and gen manually started","wil=
fried.kameni@sagemcom.com","730","15-03-2025 09:13:32","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004579613","Pha=
rmacie SION","","15-03-2025 09:06:49","15-03-2025 08:59:35","15-03-2025 09:=
10:42","Grid outage, site went down before gen start due to poor battery ba=
ck up // Grid return","Paul BIBOUM","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery back up // Grid return","wilfried.kameni@sagemco=
m.com","435","15-03-2025 09:06:49","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004579545","Beh=
ind P T school Yde","","15-03-2025 08:54:21","15-03-2025 08:50:12","15-03-2=
025 10:30:48","Grid outage, site went down because gen failed to start due =
to gen card faulty //Gen manually started","Paul BIBOUM","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down b=
ecause gen failed to start due to gen card faulty //Gen manually started","=
wilfried.kameni@sagemcom.com","250","15-03-2025 08:54:21","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004579542","ODZ=
A CITE MBIA","","15-03-2025 08:53:27","15-03-2025 08:47:16","15-03-2025 10:=
11:17",",site went down because Gen failed to start due to Grid bad voltage=
  //He bypassed the Grid and sarted gen manaully","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","site went =
down because Gen failed to start due to Grid bad voltage  //He bypassed the=
 Grid and sarted gen manaully","wilfried.kameni@sagemcom.com","372","15-03-=
2025 08:53:27","Sagemcom CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004579536","Sca=
lom","","15-03-2025 08:52:23","15-03-2025 08:48:08","15-03-2025 08:52:37","=
Grid outage site went down because Gen failed to start // Grid power return=
 (investigation ongoing)","Paul BIBOUM","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid outage site went down because Gen failed =
to start // Grid power return (investigation ongoing)","wilfried.kameni@sag=
emcom.com","256","15-03-2025 08:52:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004579535","A=
ccacia New","","15-03-2025 08:51:10","15-03-2025 08:44:03","15-03-2025 12:5=
1:38","Active// No power Issue Site on Grid Ubai =3D54,6V,The FME The TX FM=
E Mbah Hosiah (674007438) is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power Iss=
ue Site on Grid Ubai =3D54,6V,The FME The TX FME Mbah Hosiah (674007438) is=
 informed","wilfried.kameni@sagemcom.com","428","15-03-2025 08:51:10","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004579526","M=
ontee-Jouvence-II","","15-03-2025 08:50:04","15-03-2025 08:44:58","15-03-20=
25 12:50:08","ACTIVE// No  power issue on site, site on Grid with Ubaie=3D5=
4.1V The Tx Fme Mbah Hosiah //674007438/  from HUAWEI is informed","Hyemafo=
 Gildas","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","ACTIVE// No  power issue on site, site on Grid with Ub=
aie=3D54.1V The Tx Fme Mbah Hosiah //674007438/  from HUAWEI is informed","=
wilfried.kameni@sagemcom.com","307","15-03-2025 08:50:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004579524","T=
amtam Weekend","","15-03-2025 08:49:15","15-03-2025 08:44:10","15-03-2025 1=
2:20:27","Site went down due to insufficiency of rectifiers, Felix Zambeu i=
s informed // added oingoing","Hyemafo Gildas","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module","Site went down due to insufficiency of rec=
tifiers, Felix Zambeu is informed // added oingoing","wilfried.kameni@sagem=
com.com","306","15-03-2025 08:49:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004579518","D=
amas","","15-03-2025 08:47:46","15-03-2025 08:44:34","15-03-2025 12:48:59",=
"Active//No  power issue on site, site on Grid with Ubaie=3D 53.6 V TX Huaw=
ei Mbah Osiah (674007438)// from Huawei is informed","MINKA NICOLAS","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No  power issue on site, site on Grid with Ubaie=3D 53.6 V TX=
 Huawei Mbah Osiah (674007438)// from Huawei is informed","wilfried.kameni@=
sagemcom.com","193","15-03-2025 08:47:46","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004579460","Crf=
-Mbankolo-IHS","","15-03-2025 08:36:57","15-03-2025 08:35:47","15-03-2025 0=
8:43:44","Site went down due to MPR DYSFONNCTION on site SS IHS Bernard ATA=
NGANA confirmed // He reset the MPR","Mboua Thierry","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Cabinet","Site went down due to MPR DYSFONNCT=
ION on site SS IHS Bernard ATANGANA confirmed // He reset the MPR","wilfrie=
d.kameni@sagemcom.com","71","15-03-2025 08:36:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_745","NOCINC0004579424","Okolo Ki=
lombo","","15-03-2025 08:21:12","15-03-2025 08:13:03","15-03-2025 09:57:44"=
,"Grid outage, site went down because gen fails to start due to Gen cable f=
aulty // Gen manualy started","Fabrice Pouakam","Equipment Repair","Passive=
","Infrastructure","Armoured Cable","Grid outage, site went down because ge=
n fails to start due to Gen cable faulty // Gen manualy started","wilfried.=
kameni@sagemcom.com","490","15-03-2025 08:21:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0004579247","M=
bedoumou - Ekali","","15-03-2025 07:56:17","15-03-2025 07:50:08","15-03-202=
5 12:18:49","No  power Ubaie=3D53,4V site on GRID The Tx FME Rodrigue (6551=
02999)from Huawei is informed.","Albran Byorel","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No  power Ubaie=
=3D53,4V site on GRID The Tx FME Rodrigue (655102999)from Huawei is informe=
d.","danick.tchakouani@sagemcom.com","370","15-03-2025 07:56:17","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004579170","E=
foulan","","15-03-2025 07:36:41","15-03-2025 04:35:27","15-03-2025 18:35:13=
","BACK TRACKING Active: no power issue, site is on Grid with Ubaie=3D55V. =
 The TX Fme Brice Tsague of Huawei is informed.","MINKA NICOLAS","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active: no power issue, site is on Grid with Ubaie=3D55V.

The TX Fme Brice Tsague of Huawei is informed.

","danick.tchakouani@sagemcom.com","10875","15-03-2025 07:36:41","Sagemcom =
CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004579118","Aka=
k-Nkozoa-MTN-IHS","","15-03-2025 07:29:40","15-03-2025 07:20:26","15-03-202=
5 08:42:34","Grid very unstable, site went down because Gen failed to start=
 due to Grid bad voltage// Grid bypassed and gen manually started","Fabrice=
 Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid very unstable, site went down because Gen failed to start due=
 to Grid bad voltage// Grid bypassed and gen manually started","wilfried.ka=
meni@sagemcom.com","556","15-03-2025 07:29:40","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004578874","Crf=
-Mbankolo-IHS","","15-03-2025 06:27:30","15-03-2025 06:21:19","15-03-2025 0=
7:33:15","Site went down due to MPR faulty on site SS IHS Bernard ATANGANA =
confirmed // He reset the MPR","Mboua Thierry","Equipment Repair","Passive"=
,"Rectifier","Rectifier Cabinet","Site went down due to MPR faulty on site =
SS IHS Bernard ATANGANA confirmed // He reset the MPR","wilfried.kameni@sag=
emcom.com","372","15-03-2025 06:27:30","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004578385","Ole=
mbe MTN","","15-03-2025 04:02:00","15-03-2025 03:54:36","15-03-2025 04:45:3=
6","	Grid Outage Site went down due to Grid Contactors Faulty on Site//He B=
ypass it and Site is on Gen","Fabrice Pouakam","Equipment Repair","Passive"=
,"Control Panel","ATS-AMF Issue","	Grid Outage Site went down due to Grid C=
ontactors Faulty on Site//He Bypass it and Site is on Gen","danick.tchakoua=
ni@sagemcom.com","445","15-03-2025 04:02:00","Sagemcom CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004578272","MEH=
ANDAN","","15-03-2025 02:55:05","14-03-2025 21:41:49","14-03-2025 23:41:49"=
,"Site went down due to insufficiency of rectifiers on site SS IHS Pascalin=
e is confirm // He reduced the load","Albran Byorel","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","Site went down due to insufficiency =
of rectifiers on site SS IHS Pascaline is confirm // He reduced the load","=
danick.tchakouani@sagemcom.com","18797","15-03-2025 02:55:05","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004578032","Ngouetou=
","","15-03-2025 01:22:41","15-03-2025 00:56:25","15-03-2025 00:57:25","Cas=
caded Incident from TTO4648604","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","270531","15-03-2025 01:22:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004578033","MBIMBIM"=
,"","15-03-2025 01:22:41","15-03-2025 00:56:25","15-03-2025 00:57:25","Casc=
aded Incident from TTO4648604","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","270530","15-03-2025 01:22:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004578031","Matsari"=
,"","15-03-2025 01:22:40","15-03-2025 00:56:25","15-03-2025 00:57:25","Casc=
aded Incident from TTO4648604","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","270530","15-03-2025 01:22:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004577979","S=
hell-Nsimeyong","","15-03-2025 01:02:14","15-03-2025 00:59:05","15-03-2025 =
04:29:23","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","danick.tchakouani@sagemcom.com","190","15-03-2025 01:02:14","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004577954","T=
amtam Weekend","","15-03-2025 00:55:32","14-03-2025 16:22:19","15-03-2025 0=
8:37:22","Site is unstable due to insufficiency of rectifiers (4/6 rectifif=
iers faulties) IHS SS Felix Zambe is confirmed // he reset","Hyemafo Gildas=
","Equipment Repair","Passive","Rectifier","Rectifier Module","Site is unst=
able due to insufficiency of rectifiers (4/6 rectififiers faulties) IHS SS =
Felix Zambe is confirmed // he reset","kouoh.jean@ihstowers.com","30794","1=
5-03-2025 00:55:32","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004577921","Man=
guiers Dispensaire","","15-03-2025 00:41:59","15-03-2025 00:34:52","15-03-2=
025 02:03:18","Grid outage site went down because Gen failed to start due t=
o grid contactor faulty // Gen manually started","Fabrice Pouakam","Equipme=
nt Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage site went=
 down because Gen failed to start due to grid contactor faulty // Gen manua=
lly started","danick.tchakouani@sagemcom.com","428","15-03-2025 00:41:59","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004577748","C=
rf-Nsam","","14-03-2025 23:45:57","14-03-2025 23:41:46","14-03-2025 23:46:4=
6","Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline co=
nfirmed// He reset PWC","MINKA NICOLAS","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Site went down because PWC(24kilo) dys=
functionning, IHS SS Pascaline confirmed// He reset PWC","ludovic-anselme.m=
ouliom-mapoure@sagemcom","252","14-03-2025 23:45:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0004577690","Hotel de=
 Ville Yde","","14-03-2025 23:28:41","14-03-2025 23:17:59","14-03-2025 23:2=
5:01","","Paul BIBOUM","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue on site Ubaie =3D52.4V site on grid TX Fme Eloundou=
(652586578) from Huawei is informed","system","312309","14-03-2025 23:28:41=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0004577689","N=
R-Bastos","IHS_YND_019","14-03-2025 23:27:43","14-03-2025 23:17:59","15-03-=
2025 12:17:38","No power issue on site Ubaie =3D52.4V site on grid TX Fme E=
loundou(652586578) from Huawei is informed","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site Ubaie =3D52.4V site on grid TX Fme Eloundou(652586578) from Huawei i=
s informed","danick.tchakouani@sagemcom.com","585","14-03-2025 23:27:43","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004577532","D=
amas","","14-03-2025 22:42:31","14-03-2025 22:33:20","14-03-2025 22:53:20",=
"ACTIVE// No power issue on site, site on Grid with Ubaie=3D 54V The Tx Fme=
 Mbah Hosiah //674007438/ from HUAWEI is informed","MINKA NICOLAS","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE// No power issue on site, site on Grid with Ubaie=3D 54V The Tx =
Fme Mbah Hosiah //674007438/ from HUAWEI is informed","danick.tchakouani@sa=
gemcom.com","552","14-03-2025 22:42:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004577529","M=
ontee-Jouvence-II","","14-03-2025 22:41:41","14-03-2025 22:33:35","14-03-20=
25 22:43:35","ACTIVE// No power issue on site, site on Grid with Ubaie=3D 5=
4V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed.","Hyemafo G=
ildas","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE// No power issue on site, site on Grid with Ubaie=
=3D 54V The Tx Fme Mbah Hosiah //674007438/ from HUAWEI is informed.","dani=
ck.tchakouani@sagemcom.com","487","14-03-2025 22:41:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004577524","A=
ccacia New","","14-03-2025 22:40:47","14-03-2025 22:33:33","14-03-2025 22:3=
3:34","Active// No power Issue Site on Grid Ubai =3D54,6V, The FME The TX F=
ME Mbah Hosiah (674007438) is informed.","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power I=
ssue Site on Grid Ubai =3D54,6V, The FME The TX FME Mbah Hosiah (674007438)=
 is informed.","danick.tchakouani@sagemcom.com","435","14-03-2025 22:40:47"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004577461","Mes=
sassi 2","","14-03-2025 22:34:34","14-03-2025 22:08:27","15-03-2025 09:42:0=
3","Grid outage  site went down because PWC overload (12 kilo, 300A) , SS I=
HS Bernard ATANGANA confirmed // He reset and Gen manually started","Fabric=
e Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Overl=
oaded","Grid outage  site went down because PWC overload (12 kilo, 300A) , =
SS IHS Bernard ATANGANA confirmed // He reset and Gen manually started","lu=
dovic-anselme.mouliom-mapoure@sagemcom","1568","14-03-2025 22:34:34","Sagem=
com CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004577345","Crf=
-Mbankolo-IHS","","14-03-2025 22:10:05","14-03-2025 20:10:46","15-03-2025 0=
2:44:46","Site went down due to MPR DYSFONNCTION on site SS IHS Bernard ATA=
NGANA confirmed// He reset MPR","Mboua Thierry","Equipment Repair","Passive=
","Rectifier","Rectifier Cabinet","Site went down due to MPR DYSFONNCTION o=
n site SS IHS Bernard ATANGANA confirmed// He reset MPR","ludovic-anselme.m=
ouliom-mapoure@sagemcom","7160","14-03-2025 22:10:05","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004577273","NYO=
M FACE MAETUR","","14-03-2025 21:58:39","14-03-2025 21:57:32","14-03-2025 2=
3:09:32","Grid outage site went down because Gen failed to start due to Gen=
 card faulty // Gen Manually Started","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down bec=
ause Gen failed to start due to Gen card faulty // Gen Manually Started","l=
udovic-anselme.mouliom-mapoure@sagemcom","68","14-03-2025 21:58:39","Sagemc=
om CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004577269","NYO=
M 2 IHS","","14-03-2025 21:57:51","14-03-2025 21:54:44","14-03-2025 22:03:4=
4","Site went down because Gen failed to start due to Grid bad voltage // h=
e bypass the Grid and Gen manually started","Fabrice Pouakam","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Site went down=
 because Gen failed to start due to Grid bad voltage // he bypass the Grid =
and Gen manually started","ludovic-anselme.mouliom-mapoure@sagemcom","188",=
"14-03-2025 21:57:51","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004577219","Nko=
ulou Carriere carrefourt","","14-03-2025 21:50:03","14-03-2025 21:41:51","1=
5-03-2025 07:03:59","Access issue due to land load Grid outage, site went d=
own because due to Gen overload(20kva,310 A)  IHS SS Alphonse is informed//=
 We reduce load and gen manually started ","Mba Lazare Herve","Access Denia=
l","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","A=
ccess issue due to land load Grid outage, site went down because due to Gen=
 overload(20kva,310 A)  IHS SS Alphonse is informed// We reduce load and ge=
n manually started","ludovic-anselme.mouliom-mapoure@sagemcom","493","14-03=
-2025 21:50:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004576747","MONTEE N=
KONDENGUI","","14-03-2025 20:47:20","14-03-2025 20:42:52","14-03-2025 21:28=
:52","Cascaded Incident from TTO4647136","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage // Grid return","=
system","285590","14-03-2025 20:47:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004576738","M=
obil-Kondengui","IHS_YND_682","14-03-2025 20:46:04","14-03-2025 20:42:52","=
14-03-2025 21:28:52","Grid outage // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage // Grid return","=
cedric.tiani@sagemcom.com","193","14-03-2025 20:46:04","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004576705","Nko=
zoa","","14-03-2025 20:39:44","14-03-2025 20:30:14","14-03-2025 20:38:35","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and site on GEN","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to gen overload (20kva, 340A) SS HIS Felix ba=
teu is informed and confirmed// He reduced the load and site on GEN","ludov=
ic-anselme.mouliom-mapoure@sagemcom","571","14-03-2025 20:39:44","Sagemcom =
CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004576681","Ntu=
i administration","","14-03-2025 20:37:52","14-03-2025 20:34:31","14-03-202=
5 20:39:31","Grid outage, site went down because gen fails to start // Grid=
 return (Investigation ongoing)","Parker Tchoup","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because g=
en fails to start // Grid return (Investigation ongoing)","ludovic-anselme.=
mouliom-mapoure@sagemcom","201","14-03-2025 20:37:52","Sagemcom CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004576613","Sof=
avinc","","14-03-2025 20:28:05","14-03-2025 20:23:57","14-03-2025 21:33:57"=
,"Site went down because Gen failed to start due to Grid bad voltage(LACK O=
F PHASE )//He did a bridge on a Good phase","MINKA NICOLAS","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Site went down b=
ecause Gen failed to start due to Grid bad voltage(LACK OF PHASE )//He did =
a bridge on a Good phase","ludovic-anselme.mouliom-mapoure@sagemcom","248",=
"14-03-2025 20:28:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004576482","M=
arche Odza","","14-03-2025 20:08:42","14-03-2025 19:57:21","14-03-2025 20:4=
0:56","Grid fluctuation, Site went down because gen fails to start due to g=
rid bad voltage,no rcp on site// He bypasse the Grid and site on Gen","Albr=
an Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","Grid fluctuation, Site went down because gen fails to start due t=
o grid bad voltage,no rcp on site// He bypasse the Grid and site on Gen","l=
udovic-anselme.mouliom-mapoure@sagemcom","682","14-03-2025 20:08:42","Sagem=
com CMR"
"Closed Complete","Site Down","T1577","IHS_YND_086","NOCINC0004576341","POL=
YCLINIQUE TSINGA","","14-03-2025 19:45:01","14-03-2025 19:37:38","14-03-202=
5 20:15:24","Site on gen due to grid outage, site went down due to Gen cont=
acteur no excited // Grid return","Mboua Thierry","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Load Contactor","Site on gen due to grid outage, sit=
e went down due to Gen contacteur no excited // Grid return","ludovic-ansel=
me.mouliom-mapoure@sagemcom","444","14-03-2025 19:45:01","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004575917","Crf=
-Mbankolo-IHS","","14-03-2025 18:48:07","14-03-2025 18:43:53","14-03-2025 1=
9:52:56","Site went down due to MPR disfunction SS IHS Bernard Atangana con=
firmed//Site stabilized with power reset done","Mboua Thierry","Equipment R=
epair","Passive","Rectifier","Rectifier Cabinet","Site went down due to MPR=
 disfunction SS IHS Bernard Atangana confirmed//Site stabilized with power =
reset done","ludovic-anselme.mouliom-mapoure@sagemcom","256","14-03-2025 18=
:48:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004575711","A=
kak-Nkozoa-MTN-IHS","","14-03-2025 18:09:50","14-03-2025 09:19:34","14-03-2=
025 17:59:12","Site went down due to PWC Huawei malfunction SS IHS Felix Ba=
teu confirmed //Grid return","Fabrice Pouakam","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Site went down due to PWC Huawe=
i malfunction SS IHS Felix Bateu confirmed //Grid return","ludovic-anselme.=
mouliom-mapoure@sagemcom","31818","14-03-2025 18:09:50","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004575593","Mon=
tee Jouvence","","14-03-2025 17:46:52","14-03-2025 17:41:43","14-03-2025 17=
:47:08","Site went down due to insufficiency of rectifiers SS IHS Felix ZAM=
BE confirmed // He reduced the load , site on grid","Hyemafo Gildas","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down due t=
o insufficiency of rectifiers SS IHS Felix ZAMBE confirmed // He reduced th=
e load , site on grid","ludovic-anselme.mouliom-mapoure@sagemcom","309","14=
-03-2025 17:46:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004575462","OLAMA","=
","14-03-2025 17:25:21","14-03-2025 17:00:33","14-03-2025 17:03:27","Cascad=
ed Incident from TTO4645619","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D551.v Eti=
enne Fopa(651320188) from Huawei is informed site up at 06:06 PM","system",=
"270343","14-03-2025 17:25:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004575463","Bondjock=
","","14-03-2025 17:25:21","14-03-2025 17:00:33","14-03-2025 17:03:27","Cas=
caded Incident from TTO4645619","Fanda Brice","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue site on grid with U=3D551.v =
Etienne Fopa(651320188) from Huawei is informed site up at 06:06 PM","syste=
m","270343","14-03-2025 17:25:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_368","NOCINC0004575460","Otele","=
","14-03-2025 17:25:20","14-03-2025 17:00:33","14-03-2025 17:03:27","Cascad=
ed Incident from TTO4645619","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D551.v Eti=
enne Fopa(651320188) from Huawei is informed site up at 06:06 PM","system",=
"270345","14-03-2025 17:25:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004575461","Mbeng","=
","14-03-2025 17:25:20","14-03-2025 17:00:33","14-03-2025 17:03:27","Cascad=
ed Incident from TTO4645619","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D551.v Eti=
enne Fopa(651320188) from Huawei is informed site up at 06:06 PM","system",=
"270344","14-03-2025 17:25:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_063","IHS_YND_365","NOCINC0004575442","A=
kono","IHS_YND_370, IHS_YND_368, IHS_YND_369, IHS_YND_687, IHS_YND_372","14=
-03-2025 17:22:00","14-03-2025 17:00:33","14-03-2025 19:03:27","No power is=
sue site on grid with U=3D551.v Etienne Fopa(651320188) from Huawei is info=
rmed site up at 06:06 PM","Fanda Brice","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D551.v Etienne Fopa(651320188) from Huawei is informed site up=
 at 06:06 PM","cedric.tiani@sagemcom.com","1288","14-03-2025 17:22:00","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004575341","M=
om","","14-03-2025 17:06:24","14-03-2025 17:00:33","14-03-2025 20:30:27","N=
o power issue site on grid with U=3D551.v Etienne Fopa(651320188) from Huaw=
ei is informed ","Fanda Brice","Cascade Outage","Active","Cascade Active","=
Cascade Active","No power issue site on grid with U=3D551.v Etienne Fopa(65=
1320188) from Huawei is informed","ludovic-anselme.mouliom-mapoure@sagemcom=
","270344","14-03-2025 17:06:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004575337","M=
ontee-Jouvence-II","","14-03-2025 17:04:40","14-03-2025 17:00:15","14-03-20=
25 20:02:17","ACTIVE// No  power issue on site, site on Grid with Ubaie=3D =
54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed.","Hyema=
fo Gildas","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","ACTIVE// No  power issue on site, site on Grid with =
Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed=
.","ludovic-anselme.mouliom-mapoure@sagemcom","267","14-03-2025 17:04:40","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004575334","D=
amas","","14-03-2025 17:03:31","14-03-2025 17:00:21","14-03-2025 21:02:07",=
"ACTIVE// No power issue on site, site on Grid with Ubaie=3D 54V The Tx Fme=
 Mbah Hosiah //674007438/ from HUAWEI is informed","MINKA NICOLAS","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE// No power issue on site, site on Grid with Ubaie=3D 54V The Tx =
Fme Mbah Hosiah //674007438/ from HUAWEI is informed","ludovic-anselme.moul=
iom-mapoure@sagemcom","192","14-03-2025 17:03:31","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004575306","Ebo=
go","","14-03-2025 16:59:53","14-03-2025 16:57:44","14-03-2025 17:01:07","G=
rid outage, Site went down before Gen start due to poor backup/ // Gen auto=
matically started","Siligap Boris","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup/ // Gen automatically started","ludovic-anselme.mo=
uliom-mapoure@sagemcom","462","14-03-2025 16:59:53","Sagemcom CMR"
"Closed Complete","Site Down","T1579","IHS_YND_480","NOCINC0004575300","Sic=
 Cite Verte Matgenie","","14-03-2025 16:57:10","14-03-2025 16:54:02","14-03=
-2025 18:10:23","Grid outage.no space to deploy mobile gen//Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage.no space to deploy mobile gen//Grid return","ludovic-anselme.mouliom-=
mapoure@sagemcom","189","14-03-2025 16:57:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004575283","B=
ATA Mokolo OCM","","14-03-2025 16:52:44","14-03-2025 16:26:37","14-03-2025 =
23:41:37","Grid outage.no space to deploy mobile gen // Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e.no space to deploy mobile gen // Grid return","ludovic-anselme.mouliom-ma=
poure@sagemcom","1568","14-03-2025 16:52:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004575271","Nkongtoc=
k","","14-03-2025 16:49:11","14-03-2025 16:00:16","14-03-2025 21:04:37","Ca=
scaded Incident from TTO4645327","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to Insufficient =
rectifiers    02 /03 faulty on site  SS HIS Felix Zambe is informed and con=
firmed //He added 01 rectifiers","system","281129","14-03-2025 16:49:11","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004575270","Mandoumb=
a OCM","","14-03-2025 16:49:10","14-03-2025 16:00:16","14-03-2025 21:04:37"=
,"Cascaded Incident from TTO4645327","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to Insuffici=
ent rectifiers    02 /03 faulty on site  SS HIS Felix Zambe is informed and=
 confirmed //He added 01 rectifiers","system","281129","14-03-2025 16:49:10=
","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004575244","Aha=
la Echangeur","","14-03-2025 16:43:34","14-03-2025 16:33:22","14-03-2025 17=
:05:49","Site went down because Gen failed to start due to Grid bad voltage=
(LACK OF PHASE ), no rcp on site//He did a bridge on a Good phase","MINKA N=
ICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Site went down because Gen failed to start due to Grid bad voltage(L=
ACK OF PHASE ), no rcp on site//He did a bridge on a Good phase","ludovic-a=
nselme.mouliom-mapoure@sagemcom","613","14-03-2025 16:43:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0004575192","N=
kenglikok","IHS_YND_367, IHS_YND_350, IHS_YND_349","14-03-2025 16:33:26","1=
4-03-2025 16:00:16","14-03-2025 21:04:37","Site went down due to Insufficie=
nt rectifiers    02 /03 faulty on site  SS HIS Felix Zambe is informed and =
confirmed //He added 01 rectifiers","Kemeni Franklin","Equipment Repair","P=
assive","Rectifier","Rectifier Module","Site went down due to Insufficient =
rectifiers    02 /03 faulty on site  SS HIS Felix Zambe is informed and con=
firmed //He added 01 rectifiers","cedric.tiani@sagemcom.com","1991","14-03-=
2025 16:33:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004575182","M=
essa-Carriere OCM","","14-03-2025 16:31:49","14-03-2025 16:22:44","14-03-20=
25 20:55:00","No power issue site on gen with U=3D52.1v Mohamadou(691144435=
) from Huawei is informed ","","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue site on gen with =
U=3D52.1v Mohamadou(691144435) from Huawei is informed ","ludovic-anselme.m=
ouliom-mapoure@sagemcom","547","14-03-2025 16:31:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004575122","M=
ambine","","14-03-2025 16:22:31","14-03-2025 16:00:16","14-03-2025 21:04:37=
","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Site went down due to Insufficient rectifiers    02 /03 faulty on s=
ite  SS HIS Felix Zambe is informed and confirmed //He added 01 rectifiers"=
,"ludovic-anselme.mouliom-mapoure@sagemcom","281129","14-03-2025 16:22:31",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0004574972","Nko=
mo stade","","14-03-2025 16:05:34","14-03-2025 15:55:20","14-03-2025 16:01:=
18","Grid outage, Site went down before Gen start due to poor backup/ // Ge=
n automatically started","Mba Lazare Herve","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup/ // Gen automatically started","ludovic-a=
nselme.mouliom-mapoure@sagemcom","615","14-03-2025 16:05:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004574934","T=
amtam Weekend","","14-03-2025 15:58:56","14-03-2025 15:55:50","14-03-2025 1=
6:06:50","Site will be stiil down at ocm due to insufficiency of rectifiers=
 (4/6 rectififiers faulties) IHS SS  Felix Zambe is confirmed // He reduice=
 the load","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site will be stiil down at ocm due to insufficiency of rectif=
iers (4/6 rectififiers faulties) IHS SS  Felix Zambe is confirmed // He red=
uice the load","ludovic-anselme.mouliom-mapoure@sagemcom","187","14-03-2025=
 15:58:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_745","NOCINC0004574707","Okolo Ki=
lombo","","14-03-2025 15:25:07","14-03-2025 15:21:57","14-03-2025 15:37:59"=
,"Grid outage, site went down because gen fails to start due to Gen cable f=
aulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid outage, site went down because gen fails =
to start due to Gen cable faulty // Grid return","ludovic-anselme.mouliom-m=
apoure@sagemcom","190","14-03-2025 15:25:07","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004574572","Pha=
rmacie SION","","14-03-2025 14:55:05","14-03-2025 14:48:26","14-03-2025 14:=
58:59","Grid outage, site went down before gen start due to poor battery ba=
ck up // Grid return","Paul BIBOUM","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery back up // Grid return","ludovic-anselme.mouliom=
-mapoure@sagemcom","400","14-03-2025 14:55:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004574564","B=
astos Bir","","14-03-2025 14:53:52","14-03-2025 14:37:41","14-03-2025 15:38=
:21","Active//No power issue, site is on Gen with Ubaie=3D50 V, Eloundou be=
rtrant(652586578) from Huawei is informed Notice that it is a repetitive is=
sue","Mboua Thierry","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active//No power issue, site is on Gen wit=
h Ubaie=3D50 V, Eloundou bertrant(652586578) from Huawei is informed Notice=
 that it is a repetitive issue","ludovic-anselme.mouliom-mapoure@sagemcom",=
"973","14-03-2025 14:53:52","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004574522","Mes=
sassi 2","","14-03-2025 14:47:26","14-03-2025 14:44:06","14-03-2025 17:33:3=
7","Site went down because PWC overload (12 kilo, 300A) , SS IHS Bernard AT=
ANGANA confirmed// He reset it and  start the Gen manually","Fabrice Pouaka=
m","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","=
Site went down because PWC overload (12 kilo, 300A) , SS IHS Bernard ATANGA=
NA confirmed// He reset it and  start the Gen manually","ludovic-anselme.mo=
uliom-mapoure@sagemcom","202","14-03-2025 14:47:26","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004574338","UPA=
C LP","","14-03-2025 14:13:55","14-03-2025 14:01:50","14-03-2025 14:37:35",=
"Grid outage .no space to deploy mobile gen//Grid return ","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage .no spac=
e to deploy mobile gen//Grid return ","ferot.nongni-djiogap@sagemcom.com","=
726","14-03-2025 14:13:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004574287","AWAE OCM=
","","14-03-2025 14:02:21","14-03-2025 13:55:53","14-03-2025 14:57:41","Cas=
caded Incident from TTO4644240","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due PWC dysfonction // He reset the PWC and Gen manuall=
y started","system","266980","14-03-2025 14:02:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004574288","Essomba"=
,"","14-03-2025 14:02:21","14-03-2025 13:55:53","14-03-2025 14:57:41","Casc=
aded Incident from TTO4644240","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due PWC dysfonction // He reset the PWC and Gen manually=
 started","system","266979","14-03-2025 14:02:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0004574289","Biteng-M=
aetur","","14-03-2025 14:02:21","14-03-2025 13:55:53","14-03-2025 14:57:41"=
,"Cascaded Incident from TTO4644240","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen failed to start due PWC dysfonction // He reset the PWC and Gen ma=
nually started","system","266980","14-03-2025 14:02:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004574285","Bitoto",=
"","14-03-2025 14:02:20","14-03-2025 13:55:53","14-03-2025 14:57:41","Casca=
ded Incident from TTO4644240","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n failed to start due PWC dysfonction // He reset the PWC and Gen manually =
started","system","266979","14-03-2025 14:02:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004574286","Tradex-N=
komo","","14-03-2025 14:02:20","14-03-2025 13:55:53","14-03-2025 14:57:41",=
"Cascaded Incident from TTO4644240","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen failed to start due PWC dysfonction // He reset the PWC and Gen manual=
ly started","system","266979","14-03-2025 14:02:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004574272","B=
iteng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179, IHS_YND_249","1=
4-03-2025 13:59:13","14-03-2025 13:55:53","14-03-2025 14:57:41","Grid outag=
e site went down because Gen failed to start due PWC dysfonction // He rese=
t the PWC and Gen manually started","Mba Lazare Herve","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid outage site went d=
own because Gen failed to start due PWC dysfonction // He reset the PWC and=
 Gen manually started","ferot.nongni-djiogap@sagemcom.com","201","14-03-202=
5 13:59:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004574108","N=
yom OCM","","14-03-2025 13:38:47","14-03-2025 13:22:33","14-03-2025 13:43:3=
1","Grid outge .gen failed to start due to alarm ""high temp""//We add wate=
r and gen manually started ","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outge .ge=
n failed to start due to alarm ""high temp""//We add water and gen manually=
 started ","ferot.nongni-djiogap@sagemcom.com","975","14-03-2025 13:38:47",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004574042","TSI=
NGA VILLAGE 2","","14-03-2025 13:31:01","14-03-2025 13:26:52","14-03-2025 1=
4:00:49","Grid outage gen failed to start due to battery GE faulty //Gen ma=
nually started with external battery ","Delor Telezing","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Generator Battery","Grid outage gen failed to =
start due to battery GE faulty //Gen manually started with external battery=
 ","ferot.nongni-djiogap@sagemcom.com","250","14-03-2025 13:31:01","Sagemco=
m CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004573764","NTU=
I TOWN","","14-03-2025 13:02:00","14-03-2025 12:10:52","14-03-2025 12:50:28=
","Grid outage, site went down because gen ran untill fuel shortage // Refu=
eling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid outage, site went down because gen ran untill fuel shortage // Refu=
eling done","ferot.nongni-djiogap@sagemcom.com","3070","14-03-2025 13:02:00=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0004573710","H-Franco=
 New","","14-03-2025 12:58:40","14-03-2025 12:42:52","14-03-2025 12:53:07",=
"Cascaded Incident from TTO4643591","Delor Telezing","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue, site is on Grid with=
 Ubaie =3D49,1V. The TX brice  (650214096) from Huawei is informed.","syste=
m","948","14-03-2025 12:58:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0004573689","D=
joungolo","IHS_YND_711","14-03-2025 12:55:58","14-03-2025 12:42:52","14-03-=
2025 14:01:11","No power issue, site is on Grid with Ubaie =3D49,1V. The TX=
 brice  (650214096) from Huawei is informed.","Mboua Thierry","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue, site is on Grid with Ubaie =3D49,1V. The TX brice  (65021409=
6) from Huawei is informed.","ferot.nongni-djiogap@sagemcom.com","787","14-=
03-2025 12:55:58","Sagemcom CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0004573619","Ako=
no","","14-03-2025 12:39:58","","","site on alarm due to grid outage//gen s=
tarted","Fanda Brice","Warning","Warning","POWER","Warning - Site on Batter=
y","site on alarm due to grid outage//gen started","ferot.nongni-djiogap@sa=
gemcom.com","545","14-03-2025 12:39:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004573614","A=
wae Escalier","","14-03-2025 12:38:50","14-03-2025 12:29:43","14-03-2025 13=
:09:08","Grid bad voltage, Site went down before Gen start due to poor back=
up // Gen manually started","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid bad voltage, Site went do=
wn before Gen start due to poor backup // Gen manually started","ferot.nong=
ni-djiogap@sagemcom.com","549","14-03-2025 12:38:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004573613","M=
ontee-Jouvence-II","","14-03-2025 12:38:40","13-03-2025 16:12:49","13-03-20=
25 16:18:47","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed // he reduced the load, site on grid","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix Zamb=
=E9 confirmed // he reduced the load, site on grid","yves.djomo@sagemcom.co=
m","73553","14-03-2025 12:38:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004573436","C=
rf-Nsam","","14-03-2025 12:07:39","14-03-2025 12:03:20","14-03-2025 12:09:0=
5","Grid outage, Site went down before Gen start due to poor backup// Gen a=
utomatically started","MINKA NICOLAS","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup// Gen automatically started","yves.djomo@sagemc=
om.com","261","14-03-2025 12:07:39","Sagemcom CMR"
"Closed Complete","Site Down","T0236","IHS_YND_373","NOCINC0004573431","Mal=
oun","IHS_YND_783, IHS_YND_347, IHS_YND_419, IHS_YND_339, IHS_YND_421, IHS_=
EDA_101, IHS_YND_714, IHS_YND_342, IHS_YND_713","14-03-2025 12:05:36","14-0=
3-2025 11:34:29","14-03-2025 11:47:41","Site went down due to PWC Huawei ma=
lfunction // He reset controller, site on grid","Kemeni Franklin","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went do=
wn due to PWC Huawei malfunction // He reset controller, site on grid","fer=
ot.nongni-djiogap@sagemcom.com","1868","14-03-2025 12:05:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004573419","NKONGKAR=
AK","","14-03-2025 12:04:02","14-03-2025 11:34:29","14-03-2025 11:47:41",""=
,"TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Site went down due to PWC Huawei malfunction // He reset c=
ontroller, site on grid","system","275357","14-03-2025 12:04:02","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0004573418","LOBO MTN=
","","14-03-2025 12:04:01","14-03-2025 11:34:29","14-03-2025 11:47:41","","=
TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Site went down due to PWC Huawei malfunction // He reset con=
troller, site on grid","system","275358","14-03-2025 12:04:01","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0004573417","Ekekam",=
"","14-03-2025 12:04:01","14-03-2025 11:34:29","14-03-2025 11:47:41","","TI=
ENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Site went down due to PWC Huawei malfunction // He reset contr=
oller, site on grid","system","275359","14-03-2025 12:04:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0004573415","Bot Maka=
k","","14-03-2025 12:04:01","14-03-2025 11:34:29","14-03-2025 11:47:41","",=
"","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Site wen=
t down due to PWC Huawei malfunction // He reset controller, site on grid",=
"system","275357","14-03-2025 12:04:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0004573413","Nkeng li=
kok","","14-03-2025 12:04:00","14-03-2025 11:34:29","14-03-2025 11:47:41","=
","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Site went down due to PWC Huawei malfunction // He reset controlle=
r, site on grid","system","275359","14-03-2025 12:04:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004573414","Ebeba","=
","14-03-2025 12:04:00","14-03-2025 11:34:29","14-03-2025 11:47:41","","Fan=
da Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passive","S=
ite went down due to PWC Huawei malfunction // He reset controller, site on=
 grid","system","275359","14-03-2025 12:04:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0004573412","Lobo 2",=
"","14-03-2025 12:04:00","14-03-2025 11:34:29","14-03-2025 11:47:41","","TI=
ENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Site went down due to PWC Huawei malfunction // He reset contr=
oller, site on grid","system","275358","14-03-2025 12:04:00","Sagemcom CMR"
"Closed Complete","Warning","T0236","IHS_YND_373","NOCINC0004573394","Malou=
n","","14-03-2025 11:59:42","","","hybrid gen site //gen started and alarm =
cleared","Kemeni Franklin","Warning","Warning","POWER","Warning - Site on B=
attery","hybrid gen site //gen started and alarm cleared","ferot.nongni-dji=
ogap@sagemcom.com","1986","14-03-2025 11:59:42","Sagemcom CMR"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0004573354","Ngo=
g Mapubi","","14-03-2025 11:54:22","14-03-2025 11:34:29","14-03-2025 11:47:=
41","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Site went down due to PWC Huawei malfunction // He reset cont=
roller, site on grid","ferot.nongni-djiogap@sagemcom.com","275356","14-03-2=
025 11:54:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0004573187","N=
kolbi-Boss","","14-03-2025 11:19:13","14-03-2025 11:10:46","14-03-2025 12:1=
3:35","Grid outage, site went down because gen start an stopped with alarm =
under voltage // He reset gen card and gen manually started","TIENTCHEU NZE=
TCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage, site went down because gen start an stopped with alarm under=
 voltage // He reset gen card and gen manually started","ferot.nongni-djiog=
ap@sagemcom.com","508","14-03-2025 11:19:13","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004572866","NTU=
I TOWN","","14-03-2025 10:35:12","14-03-2025 10:21:00","14-03-2025 11:22:29=
","Grid outage, site site went down gen failed to start // grid return(Inve=
stigation ongoing)","Parker Tchoup","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage, site site went down gen failed to sta=
rt // grid return(Investigation ongoing)","ferot.nongni-djiogap@sagemcom.co=
m","853","14-03-2025 10:35:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004572224","N=
kolfon Cimencam","","14-03-2025 08:18:28","14-03-2025 08:13:22","14-03-2025=
 09:16:49","Grid outage, site went down because gen failed to start // Grid=
 retrun (investigation ongoing)","Hyemafo Gildas","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
gen failed to start // Grid retrun (investigation ongoing)","ferot.nongni-d=
jiogap@sagemcom.com","307","14-03-2025 08:18:28","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004572210","NKO=
LMEKONG YDE","","14-03-2025 08:14:57","14-03-2025 08:13:47","14-03-2025 08:=
15:07","Grid outage, Site went down before Gen start due to poor backup/ //=
 Gen automatically started","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup/ // Gen automatically started","ferot.n=
ongni-djiogap@sagemcom.com","72","14-03-2025 08:14:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004572145","S=
hell-Nsimeyong","","14-03-2025 08:00:04","14-03-2025 07:55:55","14-03-2025 =
08:00:23","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","yves.djomo@sagemcom.com","251","14-03-2025 08:00:04","Sagemcom CM=
R"
"Closed Complete","Site Down","T1577","IHS_YND_086","NOCINC0004572144","POL=
YCLINIQUE TSINGA","","14-03-2025 07:59:39","14-03-2025 07:57:14","14-03-202=
5 08:43:20","Site on gen due to grid outage, site went down due to Gen cont=
acteur no excited // He excited gen contactor site on gen","Mboua Thierry",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Site on ge=
n due to grid outage, site went down due to Gen contacteur no excited // He=
 excited gen contactor site on gen","ferot.nongni-djiogap@sagemcom.com","14=
6","14-03-2025 07:59:39","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004572129","Nom=
ayos montee Meche","","14-03-2025 07:55:13","14-03-2025 07:48:02","14-03-20=
25 09:28:05","Grid outage, site went down because gen failed to start // Gr=
id return(investigation ongoing)","Fanda Brice","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because ge=
n failed to start // Grid return(investigation ongoing)","ferot.nongni-djio=
gap@sagemcom.com","432","14-03-2025 07:55:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004572090","M=
essassi 2","","14-03-2025 07:43:13","14-03-2025 07:35:37","14-03-2025 07:41=
:54","Site went down due to pwc overload(12k, 300A) SS IHS Bernard is infor=
med // Load reduice: site on grid","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","Site went down due to pwc overload(1=
2k, 300A) SS IHS Bernard is informed // Load reduice: site on grid","ferot.=
nongni-djiogap@sagemcom.com","458","14-03-2025 07:43:13","Sagemcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004572080","Ntu=
i administration","","14-03-2025 07:38:04","14-03-2025 07:34:53","14-03-202=
5 09:08:11","Grid outage.gen ran until fuel shortage//Refueling done","Park=
er Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.ge=
n ran until fuel shortage//Refueling done","ferot.nongni-djiogap@sagemcom.c=
om","192","14-03-2025 07:38:04","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004571914","Nko=
londom","","14-03-2025 06:50:20","14-03-2025 06:45:13","14-03-2025 09:03:42=
","Grid outage, site went down because gen failed to start due to ATS malfu=
nction // He reset ATS and Gen started","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down be=
cause gen failed to start due to ATS malfunction // He reset ATS and Gen st=
arted","ferot.nongni-djiogap@sagemcom.com","309","14-03-2025 06:50:20","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004571845","S=
aa","","14-03-2025 06:30:28","14-03-2025 06:26:13","14-03-2025 06:30:14","N=
o power issue on site U=3D53,6v site on gen Tx fme Gregoire of huawei is in=
formed","Parker Tchoup","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53,6v site o=
n gen Tx fme Gregoire of huawei is informed","ferot.nongni-djiogap@sagemcom=
.com","256","14-03-2025 06:30:28","Sagemcom CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004571698","Nko=
abang Alembe","","14-03-2025 05:45:33","14-03-2025 05:44:24","14-03-2025 06=
:02:12","Site went down due to 01/02 rectifiers faulty, Alphonse IHS is inf=
ormed // He changed 01 rectifier , site on site","Mba Lazare Herve","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site went down due to=
 01/02 rectifiers faulty, Alphonse IHS is informed // He changed 01 rectifi=
er , site on site","el-dalile@sagemcom.com","70","14-03-2025 05:45:33","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004571632","SAA 2","=
","14-03-2025 05:12:20","14-03-2025 05:05:14","14-03-2025 05:10:26","Cascad=
ed Incident from TTO4641185","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site U=3D53,6v site on gen=
 Tx fme Gregoire of huawei is informed","system","1212133","14-03-2025 05:1=
2:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004571629","S=
aa","IHS_YND_404","14-03-2025 05:11:21","14-03-2025 05:05:14","14-03-2025 0=
5:10:26","No power issue on site U=3D53,6v site on gen Tx fme Gregoire of h=
uawei is informed","Parker Tchoup","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
3,6v site on gen Tx fme Gregoire of huawei is informed","yves.djomo@sagemco=
m.com","368","14-03-2025 05:11:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004571487","S=
hell-Nsimeyong","","14-03-2025 03:41:31","14-03-2025 03:39:22","14-03-2025 =
03:40:38","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","el-dalile@sagemcom.com","130","14-03-2025 03:41:31","Sagemcom CMR=
"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004570999","NKO=
LOSSAN OKOK","","14-03-2025 01:22:51","14-03-2025 01:20:46","14-03-2025 02:=
10:22","Grid outage,site went down because Gen failed to start due due GEN =
battery Faulty//He started the Gen with external battery (Gen battery to be=
 replaced)","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Generator Battery","Grid outage,site went down because Gen failed to start=
 due due GEN battery Faulty//He started the Gen with external battery (Gen =
battery to be replaced)","yves.djomo@sagemcom.com","126","14-03-2025 01:22:=
51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004570990","M=
EHANDAN","","14-03-2025 01:19:34","14-03-2025 01:14:30","14-03-2025 02:53:3=
0","Site went down because CB(25A) of rectifier tripped causing by Grid Ove=
rvoltage// CB of rectifier put back on ","Albran Byorel","Equipment Repair"=
,"Passive","Rectifier","Rectifier - Circuit Breaker","Site went down becaus=
e CB(25A) of rectifier tripped causing by Grid Overvoltage// CB of rectifie=
r put back on ","yves.djomo@sagemcom.com","305","14-03-2025 01:19:34","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004570714","O=
lembe-Terminus","","14-03-2025 00:16:17","14-03-2025 00:09:08","14-03-2025 =
02:03:56","Grid outage since 03 days, Site went down because Gen stopped wi=
th ""high temp"" alarm // He added water and started Gen manualy","Fabrice =
Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp -=
 Coolant Level Issue","Grid outage since 03 days, Site went down because Ge=
n stopped with ""high temp"" alarm // He added water and started Gen manual=
y","ludovic-anselme.mouliom-mapoure@sagemcom","431","14-03-2025 00:16:17","=
Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004570593","NYO=
M FACE MAETUR","","13-03-2025 23:40:07","13-03-2025 23:34:03","14-03-2025 0=
1:00:32","Grid outage site went down because Gen failed to start due to Gen=
 card faulty // Gen Manually Started","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down bec=
ause Gen failed to start due to Gen card faulty // Gen Manually Started","y=
ves.djomo@sagemcom.com","365","13-03-2025 23:40:07","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004570559","Ole=
mbe MTN","","13-03-2025 23:27:11","13-03-2025 23:23:59","13-03-2025 23:57:2=
3","Grid Outage Site went down because Gen failed to start due to Grid Cont=
actors Faulty // He started Gen manualy","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","ATS-AMF Issue","Grid Outage Site went down be=
cause Gen failed to start due to Grid Contactors Faulty // He started Gen m=
anualy","ludovic-anselme.mouliom-mapoure@sagemcom","192","13-03-2025 23:27:=
11","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004570510","Nko=
zoa","","13-03-2025 23:13:30","13-03-2025 23:09:19","13-03-2025 23:31:05","=
Grid outage site went down because Gen overload(20KVA,340A) SS IHS F=E9lix =
Bateu is informed and Is confirmed// He reduced the load on site and starte=
d gen manualy","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage site went down because Gen overload(20KVA,340A=
) SS IHS F=E9lix Bateu is informed and Is confirmed// He reduced the load o=
n site and started gen manualy","ludovic-anselme.mouliom-mapoure@sagemcom",=
"253","13-03-2025 23:13:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004570345","A=
wae Escalier","","13-03-2025 22:33:43","13-03-2025 22:27:39","14-03-2025 01=
:26:37","Grid fluctuation,site went down because Gen failed to start due to=
 Grid bad voltage No Rcp //He bypassed the Grid and sarted gen manaully","A=
lbran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation,site went down because Gen failed to start du=
e to Grid bad voltage No Rcp //He bypassed the Grid and sarted gen manaully=
","yves.djomo@sagemcom.com","365","13-03-2025 22:33:43","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004570248","AWA=
E OCM","","13-03-2025 22:20:36","13-03-2025 22:13:26","13-03-2025 22:28:46"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen au=
atomatically started","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup // Gen auatomatically started","ludovic-anse=
lme.mouliom-mapoure@sagemcom","431","13-03-2025 22:20:36","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004569675","Mon=
tee Jouvence","","13-03-2025 21:40:32","13-03-2025 21:36:24","13-03-2025 22=
:21:01","Site went down because PWC Overload (12kva, 300A) SS IHS Felix ZAM=
BE confirmed// He reduiced load","Hyemafo Gildas","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down because PWC O=
verload (12kva, 300A) SS IHS Felix ZAMBE confirmed// He reduiced load","lud=
ovic-anselme.mouliom-mapoure@sagemcom","249","13-03-2025 21:40:32","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004569669","MONTEE N=
KONDENGUI","","13-03-2025 21:40:20","13-03-2025 21:09:07","13-03-2025 21:15=
:31","Cascaded Incident from TTO4638593","Albran Byorel","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active//No power issue, site is =
on Grid with Ubaie=3D52,3 V, Eloundou bertrant(652586578) from Huawei is in=
formed","system","276962","13-03-2025 21:40:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004569484","M=
ini-Ferme","","13-03-2025 21:30:52","13-03-2025 21:24:40","13-03-2025 21:31=
:36","Site went down due to insufficient rectifier on site,RM Bikek //He re=
duced the load and site on grid","","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down due to insufficient rectifier on site,=
RM Bikek //He reduced the load and site on grid","charly.diekem-yemeli@sage=
mcom.com","373","13-03-2025 21:30:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004569369","M=
obil-Kondengui","IHS_YND_682","13-03-2025 21:10:21","13-03-2025 21:09:07","=
13-03-2025 21:15:31","Active//No power issue, site is on Grid with Ubaie=3D=
52,3 V, Eloundou bertrant(652586578) from Huawei is informed","","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue, site is on Grid with Ubaie=3D52,3 V, Eloundou ber=
trant(652586578) from Huawei is informed","charly.diekem-yemeli@sagemcom.co=
m","75","13-03-2025 21:10:21","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004569222","Nko=
l-Mbanda","","13-03-2025 20:53:45","13-03-2025 20:40:31","13-03-2025 21:42:=
17","Site went down because CB 125A disjuncted in Pwc//He reamed the CB","M=
INKA NICOLAS","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Circuit Breaker Issue","Site went down because CB 125A disjuncted in Pwc//=
He reamed the CB","ludovic-anselme.mouliom-mapoure@sagemcom","795","13-03-2=
025 20:53:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004569105","N=
YOM 2 IHS","","13-03-2025 20:29:04","13-03-2025 19:51:24","13-03-2025 22:04=
:52","Site went down because CB (63*63 A) tripped in PWC who feeds equipmen=
ts OCM// CB put back on (CB to be upgraded) ","Fabrice Pouakam","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","=
Site went down because CB (63*63 A) tripped in PWC who feeds equipments OCM=
// CB put back on (CB to be upgraded) ","ludovic-anselme.mouliom-mapoure@sa=
gemcom","2261","13-03-2025 20:29:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004568922","SAA 2","=
","13-03-2025 19:55:31","13-03-2025 19:22:17","13-03-2025 19:32:17","Cascad=
ed Incident from TTO4638057","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site U=3D53,6v site on gen=
 Tx fme Gregoire of huawei is informed","system","268932","13-03-2025 19:55=
:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004568910","S=
aa","IHS_YND_726, IHS_YND_404","13-03-2025 19:52:23","13-03-2025 19:22:17",=
"13-03-2025 19:32:17","No power issue on site U=3D53,6v site on gen Tx fme =
Gregoire of huawei is informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site U=3D53,6v site on gen Tx fme Gregoire of huawei is informed","ludov=
ic-anselme.mouliom-mapoure@sagemcom","1807","13-03-2025 19:52:23","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004568449","Ngoum","=
","13-03-2025 18:38:20","13-03-2025 14:14:48","13-03-2025 14:16:49","	Solar=
 Hybrid GEN site, No power issue site on Solar, with U=3D52.7V. The Tx Fme =
Gregoire (654547479) from Huawei informed","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Sol=
ar Hybrid GEN site, No power issue site on Solar, with U=3D52.7V. The Tx Fm=
e Gregoire (654547479) from Huawei informed","system","15844","13-03-2025 1=
8:38:20","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004568383","Obo=
bogo","","13-03-2025 18:24:49","13-03-2025 18:20:40","13-03-2025 18:28:40",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
ted automatically","MINKA NICOLAS","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen started automatically","ludovic-anselme.moul=
iom-mapoure@sagemcom","250","13-03-2025 18:24:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0004567991","Elig-Edz=
oa","","13-03-2025 17:24:10","13-03-2025 17:14:48","13-03-2025 18:26:44","C=
ascaded Incident from TTO4636962","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Site went down due to cable burned in PWC  // Bur=
ned cable replaced: site on grid","system","283845","13-03-2025 17:24:10","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004567992","Elig Edz=
oa","","13-03-2025 17:24:10","13-03-2025 17:14:48","13-03-2025 18:26:44","C=
ascaded Incident from TTO4636962","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to cable burned =
in PWC  // Burned cable replaced: site on grid","system","283845","13-03-20=
25 17:24:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0004567985","N=
taba","IHS_YND_133, IHS_YND_504","13-03-2025 17:22:54","13-03-2025 17:14:48=
","13-03-2025 18:26:44","Site went down due to cable burned in PWC  // Burn=
ed cable replaced: site on grid","Delor Telezing","Fire on Site","Passive",=
"Infrastructure","Fire - Burned","Site went down due to cable burned in PWC=
  // Burned cable replaced: site on grid","ludovic-anselme.mouliom-mapoure@=
sagemcom","487","13-03-2025 17:22:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004567850","TSINGA V=
ILLAGE 2","","13-03-2025 17:07:40","13-03-2025 17:00:40","13-03-2025 17:35:=
22","Cascaded Incident from TTO4636781","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen fails to start due to PWC dysfunctionning, IHS SS BLAISE RAOUL i=
s informed // Grid return","system","1234005","13-03-2025 17:07:40","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004567849","Melen Ba=
'aba","","13-03-2025 17:07:40","13-03-2025 17:00:40","13-03-2025 17:35:22",=
"Cascaded Incident from TTO4636781","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen fails to start due to PWC dysfunctionning, IHS SS BLAISE RAOUL is inf=
ormed // Grid return","system","1234005","13-03-2025 17:07:40","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004567835","N=
kolfoulou","IHS_YND_308, IHS_YND_719","13-03-2025 17:05:49","13-03-2025 17:=
00:40","13-03-2025 17:38:03","Grid outage, site went down because gen fails=
 to start due to PWC dysfunctionning, IHS SS BLAISE RAOUL is informed // Gr=
id return","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectif=
ier Module Overloaded","Grid outage, site went down because gen fails to st=
art due to PWC dysfunctionning, IHS SS BLAISE RAOUL is informed // Grid ret=
urn","ludovic-anselme.mouliom-mapoure@sagemcom","311","13-03-2025 17:05:49"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004567718","O=
lembe-Terminus","","13-03-2025 17:00:30","13-03-2025 16:54:56","13-03-2025 =
17:29:16","Grid outage,gen stopped with alarm high temp//he added water in =
radiator","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG -=
 High Engine Temp - Coolant Level Issue","Grid outage,gen stopped with alar=
m high temp//he added water in radiator","cedric.tiani@sagemcom.com","336",=
"13-03-2025 17:00:30","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004567652","Car=
refour Simbock","","13-03-2025 16:54:06","13-03-2025 16:52:58","13-03-2025 =
16:55:58","Site went down because gen start and stopped due to grid bad vol=
tage // Gen start automatically","Hyemafo Gildas","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Site went down because gen=
 start and stopped due to grid bad voltage // Gen start automatically","lud=
ovic-anselme.mouliom-mapoure@sagemcom","68","13-03-2025 16:54:06","Sagemcom=
 CMR"
"Closed Complete","Warning","T1545","IHS_YND_237","NOCINC0004567585","Carre=
four Simbock","","13-03-2025 16:43:35","","","Site went alarm because gen s=
tart and stopped due to grid bad voltage // Gen start automatically","Hyema=
fo Gildas","Warning","Warning","POWER","Warning - Battery Low Voltage","Sit=
e went alarm because gen start and stopped due to grid bad voltage // Gen s=
tart automatically","danick.tchakouani@sagemcom.com","3","13-03-2025 16:43:=
35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004567380","A=
kak-Nkozoa-MTN-IHS","","13-03-2025 16:24:18","13-03-2025 16:06:06","14-03-2=
025 09:11:50","Site went down due to PWC Huawei malfunction SS IHS Felix Ba=
teu confirmed //Grid return","Fabrice Pouakam","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Site went down due to PWC Huawe=
i malfunction SS IHS Felix Bateu confirmed //Grid return","cedric.tiani@sag=
emcom.com","1094","13-03-2025 16:24:18","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004567174","Ole=
mbe MTN","","13-03-2025 15:56:29","13-03-2025 15:53:23","13-03-2025 17:03:2=
9","Grid Outage Site went down due to Grid Contactors Faulty on Site//He By=
pass it and Site is on Gen","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","ATS-AMF Issue","Grid Outage Site went down due to Grid Con=
tactors Faulty on Site//He Bypass it and Site is on Gen","ludovic-anselme.m=
ouliom-mapoure@sagemcom","187","13-03-2025 15:56:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004567168","L=
eboudi","","13-03-2025 15:55:25","13-03-2025 15:38:15","13-03-2025 15:38:16=
","Active//No power issue site on grid, Team jean herve 697305221  from ZTE=
 was  working on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No po=
wer issue site on grid, Team jean herve 697305221  from ZTE was  working on=
 site","cedric.tiani@sagemcom.com","1031","13-03-2025 15:55:25","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_004","NOCINC0004567146","Av Kenne=
dy","","13-03-2025 15:54:10","13-03-2025 15:49:21","13-03-2025 18:11:25","C=
ascaded Incident from TTO4636003","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage,no space to deploy a mobil gen//grid =
return","system","274407","13-03-2025 15:54:10","Sagemcom CMR"
"Closed Complete","Site Down","T0470","IHS_YND_022","NOCINC0004567139","Mvo=
g Ada","IHS_YND_004","13-03-2025 15:53:27","13-03-2025 15:49:21","13-03-202=
5 18:11:25","Grid outage,no space to deploy a mobil gen//grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge,no space to deploy a mobil gen//grid return","ludovic-anselme.mouliom-ma=
poure@sagemcom","247","13-03-2025 15:53:27","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004566845","Pha=
rmacie SION","","13-03-2025 15:12:37","13-03-2025 15:08:30","13-03-2025 15:=
20:30","Grid outage, Site went down before Gen start due to poor backup// G=
en Automatically Started","Paul BIBOUM","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen Automatically Started","ludovic-anselme=
.mouliom-mapoure@sagemcom","248","13-03-2025 15:12:37","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004566833","NYO=
M 2 IHS","","13-03-2025 15:10:49","13-03-2025 14:36:41","13-03-2025 17:33:3=
5","Grid outage,gen stopped with alarm high temp//he added water in radiato=
r","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","Grid outage,gen stopped with alarm high =
temp//he added water in radiator","ludovic-anselme.mouliom-mapoure@sagemcom=
","2081","13-03-2025 15:10:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004566565","B=
astos Bir","","13-03-2025 14:47:32","13-03-2025 14:31:13","13-03-2025 14:41=
:13","Active//No power issue, site is on Gen with Ubaie=3D50 V, Eloundou be=
rtrant(652586578) from Huawei is informed	","Mboua Thierry","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue, site is on Gen with Ubaie=3D50 V, Eloundou bertrant(65=
2586578) from Huawei is informed	","cedric.tiani@sagemcom.com","981","13-03=
-2025 14:47:32","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004566407","CRH=
-Etoug-Ebe","","13-03-2025 14:28:59","13-03-2025 14:16:48","13-03-2025 14:3=
2:48","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"cedric.tiani@sagemcom.com","732","13-03-2025 14:28:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004566290","N=
kozoa","","13-03-2025 14:14:43","13-03-2025 14:00:27","13-03-2025 15:26:27"=
,"Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Feli=
x bateu is informed and confirmed// He reduced the load and site on GEN","F=
abrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and site on GEN","lud=
ovic-anselme.mouliom-mapoure@sagemcom","858","13-03-2025 14:14:43","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004566197","Saa","",=
"13-03-2025 13:58:10","13-03-2025 13:49:05","13-03-2025 17:22:57","Cascaded=
 Incident from TTO4634890","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site on gen due to grid outage,site went do=
wn due to relay Q11 of  behind the rectifiers barette disfunctionning//he b=
ypassed it","system","545","13-03-2025 13:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004566195","Carrefou=
r Ayissi Ele","","13-03-2025 13:58:10","13-03-2025 13:49:05","13-03-2025 17=
:22:57","Cascaded Incident from TTO4634890","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site on gen due to grid ou=
tage,site went down due to relay Q11 of  behind the rectifiers barette disf=
unctionning//he bypassed it","system","545","13-03-2025 13:58:10","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004566196","SAA Entr=
ance","","13-03-2025 13:58:10","13-03-2025 13:49:05","13-03-2025 17:22:57",=
"Cascaded Incident from TTO4634890","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site on gen due to grid outage,sit=
e went down due to relay Q11 of  behind the rectifiers barette disfunctionn=
ing//he bypassed it","system","545","13-03-2025 13:58:10","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004566181","Elo=
umdem stade","","13-03-2025 13:56:52","13-03-2025 13:54:40","13-03-2025 14:=
25:07","Grid fluctuation, Site went down because gen fails to start due to =
grid bad voltage// He did a bridge with a good phase","Fanda Brice","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid flu=
ctuation, Site went down because gen fails to start due to grid bad voltage=
// He did a bridge with a good phase","ludovic-anselme.mouliom-mapoure@sage=
mcom","133","13-03-2025 13:56:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004566165","S=
AA 2","IHS_YND_810, IHS_YND_542, IHS_YND_405","13-03-2025 13:55:30","13-03-=
2025 13:49:05","13-03-2025 17:22:57","Site on gen due to grid outage,site w=
ent down due to relay Q11 of  behind the rectifiers barette disfunctionning=
//he bypassed it","Parker Tchoup","Equipment Repair","Passive","Control Pan=
el","Relay","Site on gen due to grid outage,site went down due to relay Q11=
 of  behind the rectifiers barette disfunctionning//he bypassed it","ludovi=
c-anselme.mouliom-mapoure@sagemcom","387","13-03-2025 13:55:30","Sagemcom C=
MR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0004565772","Mvo=
g-Ada_OCM","","13-03-2025 13:17:10","13-03-2025 13:15:00","13-03-2025 18:08=
:25","Grid outage,no space to deploy a mobil gen//grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no s=
pace to deploy a mobil gen//grid return","ludovic-anselme.mouliom-mapoure@s=
agemcom","132","13-03-2025 13:17:10","Sagemcom CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0004565711","EKI=
E","","13-03-2025 13:10:22","13-03-2025 13:05:12","13-03-2025 14:46:17","Si=
te was gen due to grid outage, site went down because Gen failed to start d=
ue to grid contactor faulty // He replaced the contactor and started Gen ma=
nualy","Albran Byorel","Equipment Repair","Passive","Control Panel","ATS-AM=
F Issue","Site was gen due to grid outage, site went down because Gen faile=
d to start due to grid contactor faulty // He replaced the contactor and st=
arted Gen manualy","ludovic-anselme.mouliom-mapoure@sagemcom","311","13-03-=
2025 13:10:22","Sagemcom CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0004565650","Av-=
Germaine","","13-03-2025 13:04:06","13-03-2025 12:59:00","13-03-2025 18:07:=
49","Grid outage,no space to deploy a mobil gen//grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no sp=
ace to deploy a mobil gen//grid return","ludovic-anselme.mouliom-mapoure@sa=
gemcom","343","13-03-2025 13:04:06","Sagemcom CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0004565646","Oss=
ombe","","13-03-2025 13:03:31","13-03-2025 12:56:19","13-03-2025 13:00:57",=
"No power issue hybrid gen site on gen  with U=3D54.2v site up at 01:02 PM =
Notice that repetitive issue ","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue h=
ybrid gen site on gen  with U=3D54.2v site up at 01:02 PM Notice that repet=
itive issue ","ludovic-anselme.mouliom-mapoure@sagemcom","433","13-03-2025 =
13:03:31","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004565631","Nko=
lbisson IITA LP","","13-03-2025 13:01:42","13-03-2025 12:56:24","13-03-2025=
 12:58:35","No power issue site on grid Ubaie=3D53,8V Mohamadou 691144435 f=
rom HAUWEI is informed. Notice that site impacted by Nkolbisson 2 OCM (Not =
managing by IHS)","","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue site on grid Ubaie=3D53,8V =
Mohamadou 691144435 from HAUWEI is informed. Notice that site impacted by N=
kolbisson 2 OCM (Not managing by IHS)","ludovic-anselme.mouliom-mapoure@sag=
emcom","319","13-03-2025 13:01:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004565576","B=
astos Bir","","13-03-2025 12:50:45","13-03-2025 12:45:18","13-03-2025 13:00=
:25","Active//No power issue, site is on Gen with Ubaie=3D50 V, Eloundou be=
rtrant(652586578) from Huawei is informed","Mboua Thierry","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue, site is on Gen with Ubaie=3D50 V, Eloundou bertrant(652=
586578) from Huawei is informed","ludovic-anselme.mouliom-mapoure@sagemcom"=
,"328","13-03-2025 12:50:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004565567","N=
YOM 2 IHS","","13-03-2025 12:47:51","13-03-2025 12:44:38","13-03-2025 14:05=
:20","Grid outage, site went down because gen start and stopped due to high=
 temp // He added water and manually start the gen","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because gen start and stopped due to h=
igh temp // He added water and manually start the gen","ludovic-anselme.mou=
liom-mapoure@sagemcom","226","13-03-2025 12:47:51","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004565560","Nko=
g-Edzen","","13-03-2025 12:45:52","13-03-2025 12:39:34","13-03-2025 12:40:3=
7","No power issue site on Gen. The Tx Fme Gregoire (654547479) from Huawei=
 informed site up at 12:47 AM","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on Gen. The Tx Fme Gregoire (654547479) from Huawei informed site up at=
 12:47 AM","ludovic-anselme.mouliom-mapoure@sagemcom","380","13-03-2025 12:=
45:52","Sagemcom CMR"
"Closed Complete","Site Down","T1577","IHS_YND_086","NOCINC0004565545","POL=
YCLINIQUE TSINGA","","13-03-2025 12:43:26","13-03-2025 12:40:18","13-03-202=
5 14:20:56","Access Issue due to Landlord, Grid outage, Site went down beca=
use Gen failed to start due to fuse of contactor gen faulty// He made a bri=
dge and started Gen manualy ","Mboua Thierry","Access Denial","Lease Or Leg=
al","Landlord Related Issues","Access Issue - Land Lord","Access Issue due =
to Landlord, Grid outage, Site went down because Gen failed to start due to=
 fuse of contactor gen faulty// He made a bridge and started Gen manualy ",=
"ludovic-anselme.mouliom-mapoure@sagemcom","189","13-03-2025 12:43:26","Sag=
emcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004565465","NYO=
M FACE MAETUR","","13-03-2025 12:29:10","13-03-2025 12:27:00","13-03-2025 1=
3:43:30","Grid outage, Site went down because Gen failed to start due to Ge=
n card faulty // He started Gen manualy","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down=
 because Gen failed to start due to Gen card faulty // He started Gen manua=
ly","ludovic-anselme.mouliom-mapoure@sagemcom","132","13-03-2025 12:29:10",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004565307","Saa","",=
"13-03-2025 12:11:18","13-03-2025 12:00:55","13-03-2025 12:06:51","Cascaded=
 Incident from TTO4633894","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because 1/2 rectifier disfun=
ctionning SS IHS Felix Bateu is informed//He reset rectifier and site on ge=
n","system","266439","13-03-2025 12:11:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004565306","SAA Entr=
ance","","13-03-2025 12:11:17","13-03-2025 12:00:55","13-03-2025 12:06:51",=
"Cascaded Incident from TTO4633894","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because 1/2 rectifi=
er disfunctionning SS IHS Felix Bateu is informed//He reset rectifier and s=
ite on gen","system","266439","13-03-2025 12:11:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004565298","S=
AA 2","IHS_YND_542, IHS_YND_405","13-03-2025 12:09:43","13-03-2025 12:00:55=
","13-03-2025 12:06:51","Site went down because 1/2 rectifier disfunctionni=
ng SS IHS Felix Bateu is informed//He reset rectifier and site on gen","Par=
ker Tchoup","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down because 1/2 rectifier disfunctionning SS IHS Felix Bateu is in=
formed//He reset rectifier and site on gen","ludovic-anselme.mouliom-mapour=
e@sagemcom","530","13-03-2025 12:09:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004564974","M=
essassi 2","","13-03-2025 11:36:54","13-03-2025 11:33:40","13-03-2025 11:38=
:40","Site went down due to pwc overload(12k, 300A) SS IHS Bernard is infor=
med // Load reduice: site on grid","Fabrice Pouakam","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Site went down due to pwc overload(12k=
, 300A) SS IHS Bernard is informed // Load reduice: site on grid","cedric.t=
iani@sagemcom.com","195","13-03-2025 11:36:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004564953","M=
om","","13-03-2025 11:31:25","13-03-2025 11:27:06","13-03-2025 12:30:20","W=
RONGLY TICKETS","Fanda Brice","Incorrectly Logged Tickets","Error","Error",=
"Error","WRONGLY TICKETS","cedric.tiani@sagemcom.com","261","13-03-2025 11:=
31:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004564197","SAA Entr=
ance","","13-03-2025 09:49:35","13-03-2025 09:42:00","13-03-2025 10:57:13",=
"Cascaded Incident from TTO4632608","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because 01/02 recti=
fier dysfunctionned // We reset rectifiers and site on grid","system","455"=
,"13-03-2025 09:49:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004564198","Saa","",=
"13-03-2025 09:49:35","13-03-2025 09:42:00","13-03-2025 10:57:13","Cascaded=
 Incident from TTO4632608","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because 01/02 rectifier dysf=
unctionned // We reset rectifiers and site on grid","system","455","13-03-2=
025 09:49:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004564196","Carrefou=
r Ayissi Ele","","13-03-2025 09:49:34","13-03-2025 09:42:00","13-03-2025 10=
:57:13","Cascaded Incident from TTO4632608","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down because 01/=
02 rectifier dysfunctionned // We reset rectifiers and site on grid","syste=
m","454","13-03-2025 09:49:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004564169","S=
AA 2","IHS_YND_810, IHS_YND_542, IHS_YND_405","13-03-2025 09:44:18","13-03-=
2025 09:42:00","13-03-2025 10:57:49","Site went down because 01/02 rectifie=
r dysfunctionned // We reset rectifiers and site on grid","Parker Tchoup","=
Equipment Repair","Passive","Rectifier","Rectifier Module","Site went down =
because 01/02 rectifier dysfunctionned // We reset rectifiers and site on g=
rid","ludovic-anselme.mouliom-mapoure@sagemcom","140","13-03-2025 09:44:18"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004564102","Mam=
bine","","13-03-2025 09:41:58","13-03-2025 09:39:23","13-03-2025 10:18:44",=
"Hybrid Gen Site, site went down due to hybrid system dysfunctionning//He r=
eset and Gen started manually","Fanda Brice","Equipment Repair","Passive","=
Hybrid","Hybrid Module","Hybrid Gen Site, site went down due to hybrid syst=
em dysfunctionning//He reset and Gen started manually","ludovic-anselme.mou=
liom-mapoure@sagemcom","156","13-03-2025 09:41:58","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004563715","Tou=
ring Club International","","13-03-2025 08:35:40","13-03-2025 08:14:32","13=
-03-2025 08:37:05","Grid Outage Site went down because Gen overload (20KVA,=
 270A) SS IHS Pascaline confirmed // Grid return","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went dow=
n because Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // Grid ret=
urn","ludovic-anselme.mouliom-mapoure@sagemcom","1269","13-03-2025 08:35:40=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004563683","S=
tade-Abega","","13-03-2025 08:27:55","13-03-2025 08:22:48","13-03-2025 08:3=
7:19","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // He reset the controller, grid return","Mba Lazare Herve",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gri=
d outage, site went down because gen failed to start due to PWC ZTE malfunc=
tion // He reset the controller, grid return","ludovic-anselme.mouliom-mapo=
ure@sagemcom","308","13-03-2025 08:27:55","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004563671","Awa=
e Ewonkan","","13-03-2025 08:25:31","13-03-2025 08:20:18","13-03-2025 08:39=
:35","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed// He reduced load and started Gen manualy","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, Site went down because Gen overload(20KVA,310A) SS IHS Alphonse DEFF=
O is informed// He reduced load and started Gen manualy","ludovic-anselme.m=
ouliom-mapoure@sagemcom","728","13-03-2025 08:25:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004563668","M=
ontee-Des-Soeurs","","13-03-2025 08:24:20","13-03-2025 08:09:51","13-03-202=
5 08:36:08","Grid outage, Site went down before Gen start due to poor backu=
p// Gen started manually","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen started manually","cedric.tiani@sage=
mcom.com","871","13-03-2025 08:24:20","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004563651","AWA=
E OCM","","13-03-2025 08:18:04","13-03-2025 08:12:59","13-03-2025 08:46:14"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, site went down before gen s=
tart due to poor battery backup // Grid return","ludovic-anselme.mouliom-ma=
poure@sagemcom","307","13-03-2025 08:18:04","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004563649","Awa=
e Escalier","","13-03-2025 08:17:28","13-03-2025 08:09:18","13-03-2025 08:3=
8:11","Grid outage, Site went down before Gen start due to poor backup// Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup// Grid return","ludovic-anselme.mouliom-mapoure@sagemcom",=
"1304","13-03-2025 08:17:28","Sagemcom CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0004562942","Don=
g","","13-03-2025 07:16:45","13-03-2025 07:03:32","13-03-2025 08:22:55","Hy=
brid gen site .gen ran until fuel shortage//Refueling done","Parker Tchoup"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Hybrid gen site .gen ran=
 until fuel shortage//Refueling done","ludovic-anselme.mouliom-mapoure@sage=
mcom","825","13-03-2025 07:16:45","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004562839","Aka=
k-Nkozoa-MTN-IHS","","13-03-2025 06:48:35","13-03-2025 06:46:30","13-03-202=
5 08:55:23","Site went down due to PWC Huawei malfunction // He reduced pow=
er red, site on grid","Fabrice Pouakam","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Site went down due to PWC Huawei malfu=
nction // He reduced power red, site on grid","ludovic-anselme.mouliom-mapo=
ure@sagemcom","127","13-03-2025 06:48:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004562815","M=
efou-Assi","","13-03-2025 06:40:15","13-03-2025 06:36:01","13-03-2025 08:41=
:40","Active// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME=
 Fulbert(654266068) of huawei is informed and Uptime=3D06:41 AM","Fanda Bri=
ce","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// No power issue on site Ubaie=3D54.5V site On Grid =
The Tx FME Fulbert(654266068) of huawei is informed and Uptime=3D06:41 AM",=
"ludovic-anselme.mouliom-mapoure@sagemcom","255","13-03-2025 06:40:15","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0004562802","M=
bedoumou - Ekali","","13-03-2025 06:37:14","13-03-2025 06:03:58","13-03-202=
5 08:30:35","ACTIVE//No  power Ubaie=3D53,4V site on GRID The Tx FME Rodrig=
ue (655102999)from Huawei is informed","Albran Byorel","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//=
No  power Ubaie=3D53,4V site on GRID The Tx FME Rodrigue (655102999)from Hu=
awei is informed","cedric.tiani@sagemcom.com","1997","13-03-2025 06:37:14",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004562762","S=
hell-Nsimeyong","","13-03-2025 06:22:21","13-03-2025 06:21:08","13-03-2025 =
07:22:23","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","yves.djomo@sagemcom.com","74","13-03-2025 06:22:21","Sagemcom CMR=
"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004562559","Aka=
k-Nkozoa-MTN-IHS","","13-03-2025 05:27:43","13-03-2025 05:20:38","13-03-202=
5 05:29:31","Site went down due to PWC Huawei malfunction // He reset PWC",=
"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e Overloaded","Site went down due to PWC Huawei malfunction // He reset PWC=
","yves.djomo@sagemcom.com","426","13-03-2025 05:27:43","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004562558","Man=
guiers Dispensaire","","13-03-2025 05:26:59","13-03-2025 05:22:51","13-03-2=
025 06:31:32","Grid outage,site went down because Gen started and stopped w=
ith alarm ''low oil pressure''//he reset the Gen Card and site on Grid ","F=
abrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Grid outage,site went down because Gen started and stopped with alarm =
''low oil pressure''//he reset the Gen Card and site on Grid ","yves.djomo@=
sagemcom.com","249","13-03-2025 05:26:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004562550","Minka","=
","13-03-2025 05:20:31","13-03-2025 05:15:46","13-03-2025 07:04:14","Cascad=
ed Incident from TTO4630786","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen ran until fuel shortage//Re=
fueling done","system","285","13-03-2025 05:20:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004562549","Mbeng","=
","13-03-2025 05:20:31","13-03-2025 05:15:46","13-03-2025 07:04:14","Cascad=
ed Incident from TTO4630786","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen ran until fuel shortage//Re=
fueling done","system","285","13-03-2025 05:20:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004562551","Bondjock=
","","13-03-2025 05:20:31","13-03-2025 05:15:46","13-03-2025 07:04:14","Cas=
caded Incident from TTO4630786","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage.gen ran until fuel shortage/=
/Refueling done","system","285","13-03-2025 05:20:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004562548","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_372","13-03-2025 05:19:50","13-03-20=
25 05:15:46","13-03-2025 07:04:42","Grid outage.gen ran until fuel shortage=
//Refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage.gen ran until fuel shortage//Refueling done","yves.djomo=
@sagemcom.com","246","13-03-2025 05:19:50","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004562238","Nko=
lbisson IITA LP","","13-03-2025 04:31:22","13-03-2025 04:27:15","13-03-2025=
 04:30:41","No power issue site on grid Ubaie=3D53,8V Mohamadou 691144435 f=
rom HAUWEI is informed.","","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on grid Ubaie=
=3D53,8V Mohamadou 691144435 from HAUWEI is informed.","yves.djomo@sagemcom=
.com","248","13-03-2025 04:31:22","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004562013","MBA=
LNGONG LYCEE","","13-03-2025 02:41:06","13-03-2025 02:37:58","13-03-2025 03=
:13:50","Grid outage, Site went down because Gen stopped due to Gen overloa=
d(9kva, 130A) SS IHS Felix Zambe is informed and confirmed// Grid return","=
Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gri=
d outage, Site went down because Gen stopped due to Gen overload(9kva, 130A=
) SS IHS Felix Zambe is informed and confirmed// Grid return","yves.djomo@s=
agemcom.com","189","13-03-2025 02:41:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004561920","M=
ambine","","13-03-2025 02:17:44","13-03-2025 02:14:39","13-03-2025 02:20:03=
","Grid outage site went down because Gen failed to start due to Hybrid sys=
tem dysfonction // He reset the hybrid system and Gen manually started","Fa=
nda Brice","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid outa=
ge site went down because Gen failed to start due to Hybrid system dysfonct=
ion // He reset the hybrid system and Gen manually started","yves.djomo@sag=
emcom.com","186","13-03-2025 02:17:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004561865","S=
hell-Nsimeyong","","13-03-2025 02:06:55","13-03-2025 02:05:50","13-03-2025 =
02:25:43","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","yves.djomo@sagemcom.com","66","13-03-2025 02:06:55","Sagemcom CMR=
"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004561856","Aka=
k-Nkozoa-MTN-IHS","","13-03-2025 02:00:11","13-03-2025 01:57:05","13-03-202=
5 02:09:33","Site went down due to PWC Huawei malfunction // He reset PWC",=
"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e Overloaded","Site went down due to PWC Huawei malfunction // He reset PWC=
","yves.djomo@sagemcom.com","187","13-03-2025 02:00:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0004561734","M=
bedoumou - Ekali","","13-03-2025 01:39:55","13-03-2025 01:20:48","13-03-202=
5 02:24:07","Active// No power issue on site Ubaie=3D53.4V site On Grid The=
 Tx FME Rodrigue (655102999)from Huawei is informed","Albran Byorel","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue on site Ubaie=3D53.4V site On Grid The Tx FME=
 Rodrigue (655102999)from Huawei is informed","yves.djomo@sagemcom.com","11=
48","13-03-2025 01:39:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004561467","M=
efou-Assi","","13-03-2025 00:14:20","13-03-2025 00:12:15","13-03-2025 00:15=
:43","Active// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME=
 Fulbert(654266068) of huawei is informed. Repetitive issue","Fanda Brice",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active// No power issue on site Ubaie=3D54.5V site On Grid The =
Tx FME Fulbert(654266068) of huawei is informed. Repetitive issue","yves.dj=
omo@sagemcom.com","126","13-03-2025 00:14:20","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004561446","Aka=
k-Nkozoa-MTN-IHS","","13-03-2025 00:08:21","13-03-2025 00:02:13","13-03-202=
5 00:12:18","Site went down due to PWC Huawei malfunction // He reset PWC",=
"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e Overloaded","Site went down due to PWC Huawei malfunction // He reset PWC=
","wilfried.kameni@sagemcom.com","369","13-03-2025 00:08:21","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004561196","Ole=
mbe MTN","","12-03-2025 23:16:36","12-03-2025 23:14:20","12-03-2025 23:24:0=
6","Grid outage, site went because gen failed to start due to grid contacto=
r faulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","ATS-AMF Issue","Grid outage, site went because gen failed to =
start due to grid contactor faulty // Grid return","wilfried.kameni@sagemco=
m.com","137","12-03-2025 23:16:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004561167","O=
lembe-Terminus","","12-03-2025 23:10:00","12-03-2025 23:01:56","12-03-2025 =
23:11:01","Grid outage, Site went down because Gen failed to start// Grid r=
eturn (investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down because G=
en failed to start// Grid return (investigation ongoing)","yves.djomo@sagem=
com.com","485","12-03-2025 23:10:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004560951","M=
essa-Carriere OCM","","12-03-2025 22:24:39","12-03-2025 21:47:34","13-03-20=
25 07:22:45","Grid outage.no space to deploy mobile gen//Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge.no space to deploy mobile gen//Grid return","yves.djomo@sagemcom.com","2=
226","12-03-2025 22:24:39","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0004560613","MIM=
BOMAN LIBERTE","","12-03-2025 21:50:56","12-03-2025 21:46:47","12-03-2025 2=
2:05:56","Site went down because PWC disfunctionning// He reconfigurated th=
e PWC","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Site went down because PWC disfunctionning// He reco=
nfigurated the PWC","ludovic-anselme.mouliom-mapoure@sagemcom","480","12-03=
-2025 21:50:56","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004560608","Mon=
tee Jouvence","","12-03-2025 21:48:29","12-03-2025 21:44:14","12-03-2025 22=
:41:57","Site went down because PWC Overload (12kva, 300A) SS IHS Felix ZAM=
BE confirmed// He reduiced load","Hyemafo Gildas","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down because PWC O=
verload (12kva, 300A) SS IHS Felix ZAMBE confirmed// He reduiced load","lud=
ovic-anselme.mouliom-mapoure@sagemcom","256","12-03-2025 21:48:29","Sagemco=
m CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004560586","NYO=
M FACE MAETUR","","12-03-2025 21:44:57","12-03-2025 21:28:49","12-03-2025 2=
2:08:56","Grid outage, Site went down because Gen failed to start due to Ge=
n card faulty // He started Gen manualy ","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went dow=
n because Gen failed to start due to Gen card faulty // He started Gen manu=
aly ","ludovic-anselme.mouliom-mapoure@sagemcom","969","12-03-2025 21:44:57=
","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004560290","Pha=
rmacie SION","","12-03-2025 20:50:48","12-03-2025 20:45:33","12-03-2025 20:=
56:33","Grid outage, site went down before gen start due to poor battery ba=
ck up // Gen started automatically","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery back up // Gen started automatical=
ly","ludovic-anselme.mouliom-mapoure@sagemcom","316","12-03-2025 20:50:48",=
"Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004560284","Mes=
sassi 2","","12-03-2025 20:49:48","12-03-2025 20:42:39","12-03-2025 20:52:0=
4","Site went down due to pwc overload(12k, 300A) SS IHS Bernard is informe=
d // Load reduice: site on grid","Fabrice Pouakam","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Site went down due to pwc o=
verload(12k, 300A) SS IHS Bernard is informed // Load reduice: site on grid=
","ludovic-anselme.mouliom-mapoure@sagemcom","430","12-03-2025 20:49:48","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0004560231","T=
ongolo OCM","","12-03-2025 20:39:28","12-03-2025 20:29:59","12-03-2025 22:0=
1:53","Site went down because Gen failed to start due to Grid bad voltage a=
nd no RCP on site // he bypass the Grid and Gen manually started","Delor Te=
lezing","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Site went down because Gen failed to start due to Grid bad voltage a=
nd no RCP on site // he bypass the Grid and Gen manually started","danick.t=
chakouani@sagemcom.com","570","12-03-2025 20:39:28","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004560210","Man=
guiers Dispensaire","","12-03-2025 20:33:48","12-03-2025 20:07:40","12-03-2=
025 21:09:04","Grid outage site went down because Gen failed to start due t=
o grid contactor faulty// Gen manually started","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage site went =
down because Gen failed to start due to grid contactor faulty// Gen manuall=
y started","ludovic-anselme.mouliom-mapoure@sagemcom","1569","12-03-2025 20=
:33:48","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004560179","Nko=
zoa","","12-03-2025 20:22:51","12-03-2025 20:15:29","12-03-2025 22:49:33","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and site on GEN","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down due to gen overload (20kva, 340A) SS HIS Felix ba=
teu is informed and confirmed// He reduced the load and site on GEN","ludov=
ic-anselme.mouliom-mapoure@sagemcom","443","12-03-2025 20:22:51","Sagemcom =
CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0004560178","Djo=
nassi-Yde","","12-03-2025 20:21:53","12-03-2025 20:12:43","12-03-2025 21:43=
:53","Grid outage, site went down because gen ran untill fuel shortage // R=
efueling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down because gen ran untill fuel shortage //=
 Refueling done","ludovic-anselme.mouliom-mapoure@sagemcom","551","12-03-20=
25 20:21:53","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004560137","Nom=
ayos montee Meche","","12-03-2025 20:10:53","12-03-2025 19:59:25","12-03-20=
25 20:05:29","ACTIVE//No power issue on site Gen , Ubaie=3D54.5V site On Gr=
id The Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","ACTIVE//No power issue on site Gen , Ubaie=3D54.5V site On Grid Th=
e Tx FME Fulbert(654266068) from Huawei is informed","danick.tchakouani@sag=
emcom.com","689","12-03-2025 20:10:53","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004559735","Mes=
sa Carriere","","12-03-2025 19:19:20","12-03-2025 19:15:10","12-03-2025 19:=
28:39","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty //Grid return","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because Gen =
failed to started due to Gen card faullty //Grid return","ludovic-anselme.m=
ouliom-mapoure@sagemcom","252","12-03-2025 19:19:20","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004559724","Ngu=
ila","","12-03-2025 19:18:06","12-03-2025 19:10:59","12-03-2025 19:34:59","=
Gen only site, site went down because gen stopped with under voltage alarm =
(Unpruven alarm) // Reset done and gen started","Parker Tchoup","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Gen only site, site we=
nt down because gen stopped with under voltage alarm (Unpruven alarm) // Re=
set done and gen started","ludovic-anselme.mouliom-mapoure@sagemcom","464",=
"12-03-2025 19:18:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004559721","N=
YOM 2 IHS","","12-03-2025 19:18:00","12-03-2025 17:52:44","12-03-2025 17:52=
:45","Active//No power issue on site Ubaie=3D54.8 V site on Grid ,TX FME Sy=
nphorien (691316854) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site Ubaie=3D54.8 V site on Grid ,TX FME Synphor=
ien (691316854) from Huawei is informed","danick.tchakouani@sagemcom.com","=
5118","12-03-2025 19:18:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004558198","Akak-Nko=
zoa-MTN-IHS","","12-03-2025 17:32:10","12-03-2025 17:17:34","12-03-2025 17:=
53:34","Cascaded Incident from TTO4625725","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because PW=
C dysfunctionning // He reset it","system","276455","12-03-2025 17:32:10","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0004558133","S=
oa-II","IHS_YND_316, IHS_YND_324","12-03-2025 17:21:44","12-03-2025 17:17:3=
4","12-03-2025 17:53:34","Site went down because PWC dysfunctionning // He =
reset it","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Site went down because PWC dysfunctionning // He res=
et it","danick.tchakouani@sagemcom.com","251","12-03-2025 17:21:44","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_070","NOCINC0004557964","Efoulan"=
,"","12-03-2025 16:53:09","12-03-2025 16:04:34","12-03-2025 16:04:35","Casc=
aded Incident from TTO4625157","MINKA NICOLAS","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on grid with Ubai1=3D5=
4.9V,Site on Grid The TX Fme Hosiah / 674007438// from huawei is informed",=
"system","266530","12-03-2025 16:53:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004557640","O=
bobogo","IHS_YND_070","12-03-2025 16:29:41","12-03-2025 16:04:34","12-03-20=
25 16:04:35","No power issue site on grid with Ubai1=3D54.9V,Site on Grid T=
he TX Fme Hosiah / 674007438// from huawei is informed","MINKA NICOLAS","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue site on grid with Ubai1=3D54.9V,Site on Grid The TX=
 Fme Hosiah / 674007438// from huawei is informed","danick.tchakouani@sagem=
com.com","1508","12-03-2025 16:29:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004557180","AWAE OCM=
","","12-03-2025 16:15:30","12-03-2025 16:04:05","12-03-2025 16:33:05","Gri=
d outage, Site went down before gen start due to poor battery backup // Gen=
 started automatically","Mba Lazare Herve","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore gen start due to poor battery backup // Gen started automatically","sys=
tem","685","12-03-2025 16:15:30","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004557174","Awa=
e Escalier","","12-03-2025 16:14:13","12-03-2025 16:04:05","12-03-2025 16:2=
4:05","Grid outage, site went down before gen start due to poor battery bac=
k up // Grid return","Albran Byorel","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before ge=
n start due to poor battery back up // Grid return","ludovic-anselme.moulio=
m-mapoure@sagemcom","610","12-03-2025 16:14:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004557125","Dong",""=
,"12-03-2025 16:08:20","12-03-2025 14:33:49","12-03-2025 14:33:50","Cascade=
d Incident from TTO4624601","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue with U=3D51.4V //site =
on Gen THe fme tx Gregoire 652070658 from Huawei is informed","system","271=
798","12-03-2025 16:08:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004557120","D=
onga","IHS_YND_444","12-03-2025 16:07:41","12-03-2025 14:33:49","12-03-2025=
 14:33:50","Active//No power issue with U=3D51.4V //site on Gen THe fme tx =
Gregoire 652070658 from Huawei is informed","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue with U=3D51.4V //site on Gen THe fme tx Gregoire 652070=
658 from Huawei is informed","ludovic-anselme.mouliom-mapoure@sagemcom","56=
33","12-03-2025 16:07:41","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004557093","Ebo=
go","","12-03-2025 16:03:35","12-03-2025 15:55:26","12-03-2025 16:18:03","G=
rid outage, site went down before gen start due to poor battery backup //gr=
id return","Siligap Boris","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, site went down before gen start du=
e to poor battery backup //grid return","ludovic-anselme.mouliom-mapoure@sa=
gemcom","818","12-03-2025 16:03:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004556962","B=
astos Bir","","12-03-2025 15:51:05","12-03-2025 15:33:59","12-03-2025 15:34=
:01","Active//No power issue, site is on Gen with Ubaie=3D50 V, Eloundou be=
rtrant(652586578) from Huawei is informed	","Mboua Thierry","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue, site is on Gen with Ubaie=3D50 V, Eloundou bertrant(65=
2586578) from Huawei is informed	","danick.tchakouani@sagemcom.com","1028",=
"12-03-2025 15:51:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004556955","E=
vodoula OCM","","12-03-2025 15:49:37","12-03-2025 15:41:32","12-03-2025 15:=
51:32","No power issue on site U=3D54,4v site on gen Tx fme Mohamadou of hu=
awei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site U=3D54,4v site on gen Tx fme Mohamadou of huawei is informed","ludovic=
-anselme.mouliom-mapoure@sagemcom","486","12-03-2025 15:49:37","Sagemcom CM=
R"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004556931","Mfo=
u EPC","","12-03-2025 15:45:40","12-03-2025 15:34:24","12-03-2025 17:19:17"=
,"Grid outage, site went down because gen start and stopped due to high tem=
p // He added water and manually start the gen","Mba Lazare Herve","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Is=
sue","Grid outage, site went down because gen start and stopped due to high=
 temp // He added water and manually start the gen","ludovic-anselme.moulio=
m-mapoure@sagemcom","677","12-03-2025 15:45:40","Sagemcom CMR"
"Closed Complete","Site Down","T1543","IHS_YND_336","NOCINC0004556923","EKI=
E","","12-03-2025 15:44:41","12-03-2025 15:38:31","12-03-2025 17:32:44","Si=
te on gen due to grid outage,  site went down due to grid contactor faulty =
// He bypass it: site on gen","Albran Byorel","Equipment Repair","Passive",=
"Control Panel","ATS-AMF Issue","Site on gen due to grid outage,  site went=
 down due to grid contactor faulty // He bypass it: site on gen","ludovic-a=
nselme.mouliom-mapoure@sagemcom","370","12-03-2025 15:44:41","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004556820","Nko=
ulou Carriere carrefourt","","12-03-2025 15:28:18","12-03-2025 16:07:05","1=
2-03-2025 16:23:05","Grid outage, site went down because due to Gen overloa=
d(20kva,310 A) // We reduce load and gen manually started IHS SS Alphonse i=
s informed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage, site went down because due to Gen overload(20kv=
a,310 A) // We reduce load and gen manually started IHS SS Alphonse is info=
rmed","ludovic-anselme.mouliom-mapoure@sagemcom","637","12-03-2025 15:28:18=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004556752","N=
koabang Ebolmedjock","","12-03-2025 15:15:58","12-03-2025 15:01:54","12-03-=
2025 15:01:55","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Gen. Notice that it is impacted b=
y Nkolmesseng-Abom(CTR-711) Not Manager By IHS","danick.tchakouani@sagemcom=
.com","845","12-03-2025 15:15:58","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004556602","Ngo=
a Ekelle","","12-03-2025 15:02:19","12-03-2025 14:58:07","12-03-2025 15:55:=
03","Site went down because Gen failed to start due to Relay (220V) ATS fau=
lty // He bypass it and Gen manually started","Paul BIBOUM","Equipment Repa=
ir","Passive","Control Panel","Relay","Site went down because Gen failed to=
 start due to Relay (220V) ATS faulty // He bypass it and Gen manually star=
ted","ludovic-anselme.mouliom-mapoure@sagemcom","254","12-03-2025 15:02:19"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004556532","SOA=
 TOWN","","12-03-2025 14:49:17","12-03-2025 14:40:07","12-03-2025 15:10:17"=
,"Grid outage,gen ran till fuel shortage//Refueling done","Siligap Boris","=
Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran till f=
uel shortage//Refueling done","danick.tchakouani@sagemcom.com","589","12-03=
-2025 14:49:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004556527","NKONGKAR=
AK","","12-03-2025 14:48:51","12-03-2025 14:31:29","12-03-2025 16:11:27","C=
ascaded Incident from TTO4623899","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive"," Site went down due to hy=
brid syst=E8m dysfunctionning //he reset it and started the gen","system","=
279185","12-03-2025 14:48:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0004556525","Lobo 2",=
"","12-03-2025 14:48:50","12-03-2025 14:31:29","12-03-2025 16:11:27","Casca=
ded Incident from TTO4623899","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive"," Site went down due to hybrid=
 syst=E8m dysfunctionning //he reset it and started the gen","system","2791=
85","12-03-2025 14:48:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0004556526","Ekekam",=
"","12-03-2025 14:48:50","12-03-2025 14:31:29","12-03-2025 16:11:27","Casca=
ded Incident from TTO4623899","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive"," Site went down due to hybrid=
 syst=E8m dysfunctionning //he reset it and started the gen","system","2791=
86","12-03-2025 14:48:50","Sagemcom CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0004556516","LOB=
O MTN","IHS_YND_783, IHS_YND_714, IHS_YND_713","12-03-2025 14:47:41","12-03=
-2025 14:31:29","12-03-2025 16:11:27"," Site went down due to hybrid syst=
=E8m dysfunctionning //he reset it and started the gen","TIENTCHEU NZETCHIE=
U GAEL","Equipment Repair","Passive","Hybrid","Hybrid Module"," Site went d=
own due to hybrid syst=E8m dysfunctionning //he reset it and started the ge=
n","danick.tchakouani@sagemcom.com","973","12-03-2025 14:47:41","Sagemcom C=
MR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004556399","Sap=
eur","","12-03-2025 14:27:33","12-03-2025 14:22:19","12-03-2025 18:34:12","=
Grid outage, site went down before gen start due to poor battery back up //=
 Grid return","Mboua Thierry","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, site went down before gen start=
 due to poor battery back up // Grid return","danick.tchakouani@sagemcom.co=
m","315","12-03-2025 14:27:33","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004556279","Nko=
g-Edzen","","12-03-2025 13:59:23","12-03-2025 13:55:00","12-03-2025 14:00:1=
0","No power issue site on Gen. The Tx Fme Gregoire (654547479) from Huawei=
 informed ","Parker Tchoup","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on Gen. The Tx =
Fme Gregoire (654547479) from Huawei informed ","mariam.tchonang@sagemcom.c=
om","264","12-03-2025 13:59:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0004556217","BATA Mok=
olo OCM","","12-03-2025 13:44:10","12-03-2025 13:34:48","14-03-2025 16:18:5=
9","Grid outage.no space to deploy mobile gen//Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no spac=
e to deploy mobile gen//Grid return","system","603","12-03-2025 13:44:10","=
Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004556183","AKA=
K Nkozoa","","12-03-2025 13:38:48","12-03-2025 13:30:31","12-03-2025 16:29:=
36","Site went down because Gen started and stopped due emergency stop butt=
on was activeted// He bypassed it and started Gen manualy","Fabrice Pouakam=
","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Site wen=
t down because Gen started and stopped due emergency stop button was active=
ted// He bypassed it and started Gen manualy","mariam.tchonang@sagemcom.com=
","498","12-03-2025 13:38:48","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004556040","Mes=
sassi 2","","12-03-2025 13:13:26","12-03-2025 13:07:14","12-03-2025 15:42:4=
6","Site went down due to pwc overload(12k, 300A) SS IHS Bernard is informe=
d // Load reduice: site on grid","Fabrice Pouakam","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Site went down due to pwc o=
verload(12k, 300A) SS IHS Bernard is informed // Load reduice: site on grid=
","ludovic-anselme.mouliom-mapoure@sagemcom","374","12-03-2025 13:13:26","S=
agemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004555420","Mes=
sassi 2","","12-03-2025 11:29:07","12-03-2025 11:21:46","12-03-2025 12:49:5=
2","Site went down because 04/05 rectifier dysfunctionned // We reset recti=
fiers and site on grid ","Fabrice Pouakam","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down because 04/05 rectifier dysfunc=
tionned // We reset rectifiers and site on grid ","mariam.tchonang@sagemcom=
.com","480","12-03-2025 11:29:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004555333","Nkongtoc=
k","","12-03-2025 11:14:23","12-03-2025 10:21:51","12-03-2025 10:22:21","Ca=
scaded Incident from TTO4622259","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue site on grid with U=3D5=
4v Notice that site is impacted by Messamendongo who is not our responsabil=
ity ","system","265487","12-03-2025 11:14:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004555331","Mambine"=
,"","12-03-2025 11:14:22","12-03-2025 10:21:51","12-03-2025 10:22:21","Casc=
aded Incident from TTO4622259","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on grid with U=3D54v Not=
ice that site is impacted by Messamendongo who is not our responsability ",=
"system","265487","12-03-2025 11:14:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004555330","Nomayos-=
IHS","","12-03-2025 11:14:22","12-03-2025 10:21:51","12-03-2025 10:22:21","=
Cascaded Incident from TTO4622259","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue site on grid with U=3D54v=
 Notice that site is impacted by Messamendongo who is not our responsabilit=
y ","system","265484","12-03-2025 11:14:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004555332","Angongo"=
,"","12-03-2025 11:14:22","12-03-2025 10:21:51","12-03-2025 10:22:21","Casc=
aded Incident from TTO4622259","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on grid with U=3D54v Not=
ice that site is impacted by Messamendongo who is not our responsability ",=
"system","265485","12-03-2025 11:14:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004555328","Nkenglik=
ok","","12-03-2025 11:14:22","12-03-2025 10:21:51","12-03-2025 10:22:21","C=
ascaded Incident from TTO4622259","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
54v Notice that site is impacted by Messamendongo who is not our responsabi=
lity ","system","265488","12-03-2025 11:14:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004555329","Ebeba","=
","12-03-2025 11:14:22","12-03-2025 10:21:51","12-03-2025 10:22:21","Cascad=
ed Incident from TTO4622259","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Notic=
e that site is impacted by Messamendongo who is not our responsability ","s=
ystem","265489","12-03-2025 11:14:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004555326","Mandoumb=
a OCM","","12-03-2025 11:14:21","12-03-2025 10:21:51","12-03-2025 10:22:21"=
,"Cascaded Incident from TTO4622259","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D54v Notice that site is impacted by Messamendongo who is not our respons=
ability ","system","265486","12-03-2025 11:14:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004555327","Mbankomo=
 IHS","","12-03-2025 11:14:21","12-03-2025 10:21:51","12-03-2025 10:22:21",=
"Cascaded Incident from TTO4622259","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D54=
v Notice that site is impacted by Messamendongo who is not our responsabili=
ty ","system","265486","12-03-2025 11:14:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004555325","Sous Pre=
fecture","","12-03-2025 11:14:21","12-03-2025 10:21:51","12-03-2025 10:22:2=
1","Cascaded Incident from TTO4622259","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D54v Notice that site is impacted by Messamendongo who is not our respons=
ability ","system","265486","12-03-2025 11:14:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004555190","B=
ATA Mokolo OCM","","12-03-2025 10:50:59","12-03-2025 10:44:49","12-03-2025 =
13:19:15","Grid outage.no space to deploy mobile gen.grid power awaited",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage.no space to deploy mobile gen   //  grid  return ","mariam.tchonang@s=
agemcom.com","371","12-03-2025 10:50:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004555147","N=
omayos","IHS_YND_314, IHS_YND_334, IHS_YND_367, IHS_YND_674, IHS_YND_695, I=
HS_YND_348, IHS_YND_339, IHS_YND_697, IHS_YND_350, IHS_YND_335, IHS_YND_349=
","12-03-2025 10:45:38","12-03-2025 10:21:51","12-03-2025 10:22:21","No pow=
er issue site on grid with U=3D54v Notice that site is impacted by Messamen=
dongo who is not our responsability ","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue site on grid with U=3D54v Notice that site is impacted by Messamendongo=
 who is not our responsability ","mariam.tchonang@sagemcom.com","1428","12-=
03-2025 10:45:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0004555140","Mfou EPC=
","","12-03-2025 10:44:00","12-03-2025 10:21:51","12-03-2025 10:22:21","Cas=
caded Incident from TTO4622244 - Cascade Removed From TTO4622244","Mba Laza=
re Herve","Cascade Outage","Active","Cascade Active","Cascade Active","No p=
ower issue site on grid with U=3D54v Notice that site is impacted by Messam=
endongo who is not our responsability ","system","265489","12-03-2025 10:44=
:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0004555135","M=
fou OCM","","12-03-2025 10:43:13","12-03-2025 10:21:51","12-03-2025 10:22:2=
1","","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Cascad=
e Active","No power issue site on grid with U=3D54v Notice that site is imp=
acted by Messamendongo who is not our responsability ","mariam.tchonang@sag=
emcom.com","265488","12-03-2025 10:43:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004555076","L=
abogenie","","12-03-2025 10:41:21","12-03-2025 10:31:09","12-03-2025 10:36:=
07","No power issue U =3D54,5V site on Grid. The Tx FME Eloundou (693212405=
 )from Huawei is informed","","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D54,5V site on=
 Grid. The Tx FME Eloundou (693212405 )from Huawei is informed
","mariam.tchonang@sagemcom.com","614","12-03-2025 10:41:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0004554697","MBALNGON=
G LYCEE","","12-03-2025 09:46:21","12-03-2025 09:42:55","12-03-2025 11:28:1=
6","Cascaded Incident from TTO4621747","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel sh=
ortage//Refueling done","system","267644","12-03-2025 09:46:21","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0004554696","ELOUMDEM=
 CARRIERE","","12-03-2025 09:46:21","12-03-2025 09:42:55","12-03-2025 11:28=
:16","Cascaded Incident from TTO4621747","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel =
shortage//Refueling done","system","267645","12-03-2025 09:46:21","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004554698","Afanoya"=
,"","12-03-2025 09:46:21","12-03-2025 09:42:55","12-03-2025 11:28:16","Casc=
aded Incident from TTO4621747","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel shortag=
e//Refueling done","system","267645","12-03-2025 09:46:21","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004554688","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","12-03-2025 09:45:06","12-03-20=
25 09:42:55","12-03-2025 11:28:16","Grid outage.gen ran until fuel shortage=
//Refueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage.gen ran until fuel shortage//Refueling done","ludovic=
-anselme.mouliom-mapoure@sagemcom","134","12-03-2025 09:45:06","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004554670","Ngoum","=
","12-03-2025 09:43:00","12-03-2025 09:17:44","12-03-2025 13:42:46","Cascad=
ed Incident from TTO4621609","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage .gen failed to start due to a=
larm ""low oil pressure""//We add oil and gen manually started ","system","=
1233025","12-03-2025 09:43:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004554603","Mambine"=
,"","12-03-2025 09:29:11","12-03-2025 09:09:23","12-03-2025 09:20:23","Casc=
aded Incident from TTO4621467","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage.gen failed to start due to al=
arm ""high temp"" //We add water and gen manually started ","system","26950=
9","12-03-2025 09:29:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004554604","Nkongtoc=
k","","12-03-2025 09:29:11","12-03-2025 09:09:23","12-03-2025 09:20:23","Ca=
scaded Incident from TTO4621467","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due=
 to alarm ""high temp"" //We add water and gen manually started ","system",=
"269510","12-03-2025 09:29:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004554602","Nkenglik=
ok","","12-03-2025 09:29:11","12-03-2025 09:09:23","12-03-2025 09:20:23","C=
ascaded Incident from TTO4621467","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start du=
e to alarm ""high temp"" //We add water and gen manually started ","system"=
,"269509","12-03-2025 09:29:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004554601","Mbankomo=
 IHS","","12-03-2025 09:29:10","12-03-2025 09:09:23","12-03-2025 09:20:23",=
"Cascaded Incident from TTO4621467","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due =
to alarm ""high temp"" //We add water and gen manually started ","system","=
269510","12-03-2025 09:29:10","Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0004554567","Yok=
o MTN","IHS_YND_475","12-03-2025 09:23:01","12-03-2025 09:17:44","12-03-202=
5 13:42:46","Grid outage .gen failed to start due to alarm ""low oil pressu=
re""//We add oil and gen manually started ","Parker Tchoup","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage .gen failed=
 to start due to alarm ""low oil pressure""//We add oil and gen manually st=
arted ","mariam.tchonang@sagemcom.com","319","12-03-2025 09:23:01","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0004554425","O=
KOA Peage","IHS_YND_695, IHS_YND_348, IHS_YND_350, IHS_YND_349","12-03-2025=
 09:11:32","12-03-2025 09:09:23","12-03-2025 09:20:23","Grid outage.gen fai=
led to start due to alarm ""high temp"" //We add water and gen manually sta=
rted ","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Radiat=
or","Grid outage.gen failed to start due to alarm ""high temp"" //We add wa=
ter and gen manually started ","mariam.tchonang@sagemcom.com","130","12-03-=
2025 09:11:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004554335","N=
YOM 2 IHS","","12-03-2025 08:57:41","11-03-2025 21:35:17","11-03-2025 21:40=
:18","Grid outage.gen failed to start due to poor battery backup//Gen start=
 automatically Power issue resolved at 09:45 PM  but site remains down powe=
r reset has done ","Fabrice Pouakam","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage.gen failed to start due t=
o poor battery backup//Gen start automatically Power issue resolved at 09:4=
5 PM  but site remains down power reset has done ","ludovic-anselme.mouliom=
-mapoure@sagemcom","40946","12-03-2025 08:57:41","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004554315","Elo=
umdem stade","","12-03-2025 08:55:50","12-03-2025 08:36:40","12-03-2025 09:=
31:56","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage  // Grid power stabilized","Fanda Brice","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,=
 site went down because Gen failed to start due to grid bad voltage  // Gri=
d power stabilized","ludovic-anselme.mouliom-mapoure@sagemcom","1152","12-0=
3-2025 08:55:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004554260","O=
LAMA","","12-03-2025 08:45:48","12-03-2025 08:36:43","12-03-2025 08:41:49",=
"Active//No power issue on site Ubaie =3D54.9V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.9V site on Grid The TX FME Henri (69994969=
3) from Huawei is informed","mariam.tchonang@sagemcom.com","546","12-03-202=
5 08:45:48","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004554153","OBA=
M NGOLA OCM","","12-03-2025 08:27:49","12-03-2025 08:21:40","12-03-2025 10:=
14:10","Grid outage.gen failed to start due to batter GE discharged causing=
 by  charging alternator faulty //Gen manually started with external batter=
y","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Charging=
 Alternator","Grid outage.gen failed to start due to batter GE discharged c=
ausing by  charging alternator faulty //Gen manually started with external =
battery","ludovic-anselme.mouliom-mapoure@sagemcom","370","12-03-2025 08:27=
:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0004554149","O=
kola OCM","","12-03-2025 08:27:00","12-03-2025 07:56:48","12-03-2025 12:11:=
13","Grid outage.gen failed to start due to radiator leakage//We fixed radi=
ator and gen manually started ","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Radiator Leakage","Grid outage.gen failed t=
o start due to radiator leakage//We fixed radiator and gen manually started=
 ","mariam.tchonang@sagemcom.com","1814","12-03-2025 08:27:00","Sagemcom CM=
R"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004554031","Nko=
ulou Carriere carrefourt","","12-03-2025 08:01:21","12-03-2025 07:57:47","1=
2-03-2025 10:38:16","Grid outage, site went down because due to Gen overloa=
d(20kva,310 A) //We reduce load and gen manually started  IHS SS Alphonse i=
s informed ","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, site went down because due to Gen overload(20k=
va,310 A) //We reduce load and gen manually started  IHS SS Alphonse is inf=
ormed ","ludovic-anselme.mouliom-mapoure@sagemcom","216","12-03-2025 08:01:=
21","Sagemcom CMR"
"Closed Complete","Warning","CTR_541","IHS_YND_330","NOCINC0004553901","OKO=
A Peage","","12-03-2025 07:35:21","","","Grid outage,site went on alarm bec=
ause Gen start and stopped due to high temp //He add water and manually sta=
rt the Gen","Fanda Brice","Warning","Warning","POWER","Warning - Gen Temp H=
igh","Grid outage,site went on alarm because Gen start and stopped due to h=
igh temp //He add water and manually start the Gen","cedric.tiani@sagemcom.=
com","8851","12-03-2025 07:35:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004553795","M=
efou-Assi","","12-03-2025 07:10:03","12-03-2025 07:08:48","12-03-2025 07:11=
:53","Active// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME=
 Fulbert(654266068) of huawei is informed","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME Fulbert(654=
266068) of huawei is informed","mariam.tchonang@sagemcom.com","76","12-03-2=
025 07:10:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004553753","S=
hell-Nsimeyong","","12-03-2025 06:59:10","12-03-2025 06:53:04","12-03-2025 =
07:08:14","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed. Repetitive Issue site up at 06=
:57 AM","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue U =3D52.2V site on Grid.=
The FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repet=
itive Issue site up at 06:57 AM","ludovic-anselme.mouliom-mapoure@sagemcom"=
,"367","12-03-2025 06:59:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004553676","Dong",""=
,"12-03-2025 06:38:50","12-03-2025 05:59:25","12-03-2025 06:04:38","Cascade=
d Incident from TTO4620494","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue with U=3D51.4V //site =
on Gen THe fme tx Gregoire 652070658 from Huawei is informed","system","266=
779","12-03-2025 06:38:50","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004553657","Mam=
bine","","12-03-2025 06:35:10","12-03-2025 06:27:00","12-03-2025 08:15:26",=
"Grid outage, site went down because gen ran untill fuel shortage // refuel=
ling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, site went down because gen ran untill fuel shortage // refuell=
ing done","ludovic-anselme.mouliom-mapoure@sagemcom","491","12-03-2025 06:3=
5:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004553543","D=
onga","IHS_YND_444","12-03-2025 06:03:33","12-03-2025 05:59:25","12-03-2025=
 07:38:39","Active//No power issue with U=3D51.4V //site on Gen THe fme tx =
Gregoire 652070658 from Huawei is informed","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue with U=3D51.4V //site on Gen THe fme tx Gregoire 652070=
658 from Huawei is informed","yves.djomo@sagemcom.com","249","12-03-2025 06=
:03:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0004553505","S=
ous Prefecture","","12-03-2025 05:49:50","11-03-2025 22:25:40","11-03-2025 =
22:30:00","ACTIVE//No power issue site on Grid Ubaie =3D53.7 V, The tx Huaw=
ei Fulbert (654266068) is informed","Fanda Brice","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No po=
wer issue site on Grid Ubaie =3D53.7 V, The tx Huawei Fulbert (654266068) i=
s informed","ferot.nongni-djiogap@sagemcom.com","26651","12-03-2025 05:49:5=
0","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004553467","NYO=
M FACE MAETUR","","12-03-2025 05:28:23","12-03-2025 05:19:17","12-03-2025 0=
7:11:08","Grid outage, site went down because Gen failed to started due to =
Gen card faullty //Gen manualy started","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down =
because Gen failed to started due to Gen card faullty //Gen manualy started=
","yves.djomo@sagemcom.com","547","12-03-2025 05:28:23","Sagemcom CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004553466","Nko=
abang Alembe","","12-03-2025 05:27:07","12-03-2025 05:12:01","13-03-2025 17=
:45:34","Site went down because 01/02 rectifier faulty IHS SS Alphonse DEFF=
O confirmed//He replaced rectifier faulty","Mba Lazare Herve","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down because 01/0=
2 rectifier faulty IHS SS Alphonse DEFFO confirmed//He replaced rectifier f=
aulty","yves.djomo@sagemcom.com","907","12-03-2025 05:27:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0004553282","M=
bankomo IHS","","12-03-2025 04:22:16","12-03-2025 04:20:10","12-03-2025 05:=
00:07","Grid outage.gen failed to start due to air intake//We purged and ge=
n manually started ","Fanda Brice","Fuel Outage (Probable)","Passive","ACDG=
 Gen","ACDG - Air Intake","Grid outage.gen failed to start due to air intak=
e//We purged and gen manually started ","yves.djomo@sagemcom.com","127","12=
-03-2025 04:22:16","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004552862","Mes=
sa Carriere","","12-03-2025 01:20:58","12-03-2025 01:09:51","12-03-2025 01:=
28:19","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty //Grid outage","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because Gen =
failed to started due to Gen card faullty //Grid outage","yves.djomo@sagemc=
om.com","668","12-03-2025 01:20:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004552835","c=
hina embassy yde","","12-03-2025 01:14:37","12-03-2025 01:09:29","12-03-202=
5 03:35:57","Active//No power issue site on grid with U=3D52.4V The Tx FME =
 Eloundou Bertrand from Huawei is informed","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power=
 issue site on grid with U=3D52.4V The Tx FME  Eloundou Bertrand from Huawe=
i is informed","yves.djomo@sagemcom.com","309","12-03-2025 01:14:37","Sagem=
com CMR"
"Closed Complete","Site Down","T1739","IHS_YND_691","NOCINC0004552769","Mba=
lla 2 REGIE","","12-03-2025 00:58:05","12-03-2025 00:56:58","12-03-2025 02:=
14:49","Site went down due to 01/03 rectifiers burned, Bernard Atanga IHS i=
s informed// Site on grid with 02 rectifiers","Delor Telezing","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down due to 01/0=
3 rectifiers burned, Bernard Atanga IHS is informed// Site on grid with 02 =
rectifiers","ferot.nongni-djiogap@sagemcom.com","67","12-03-2025 00:58:05",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004552732","M=
efou-Assi","","12-03-2025 00:48:52","12-03-2025 00:44:48","12-03-2025 02:45=
:47","Active// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME=
 Fulbert(654266068) of huawei is informed","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME Fulbert(654=
266068) of huawei is informed","yves.djomo@sagemcom.com","245","12-03-2025 =
00:48:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004552138","Mambine"=
,"","11-03-2025 22:17:42","11-03-2025 22:04:01","11-03-2025 22:24:19","Casc=
aded Incident from TTO4618724","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down due to main g=
en faulty // Grid return","system","273495","11-03-2025 22:17:42","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004552139","Angongo"=
,"","11-03-2025 22:17:42","11-03-2025 22:04:01","11-03-2025 22:24:19","Casc=
aded Incident from TTO4618724","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down due to main g=
en faulty // Grid return","system","273493","11-03-2025 22:17:42","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004552136","Nkenglik=
ok","","11-03-2025 22:17:42","11-03-2025 22:04:01","11-03-2025 22:24:19","C=
ascaded Incident from TTO4618724","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 main gen faulty // Grid return","system","273492","11-03-2025 22:17:42","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004552137","Ebeba","=
","11-03-2025 22:17:42","11-03-2025 22:04:01","11-03-2025 22:24:19","Cascad=
ed Incident from TTO4618724","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down due to main gen=
 faulty // Grid return","system","273494","11-03-2025 22:17:42","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004552135","Mbankomo=
 IHS","","11-03-2025 22:17:41","11-03-2025 22:04:01","11-03-2025 22:24:19",=
"Cascaded Incident from TTO4618724","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to m=
ain gen faulty // Grid return","system","273492","11-03-2025 22:17:41","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004552134","Sous Pre=
fecture","","11-03-2025 22:17:41","11-03-2025 22:04:01","11-03-2025 22:24:1=
9","Cascaded Incident from TTO4618724","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down due t=
o main gen faulty // Grid return","system","273494","11-03-2025 22:17:41","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004552095","N=
omayos","IHS_YND_314, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_350, I=
HS_YND_335","11-03-2025 22:13:07","11-03-2025 18:55:49","11-03-2025 22:57:3=
7","Grid outage, site went down due to main gen faulty // Grid return","Fan=
da Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty"=
,"Grid outage, site went down due to main gen faulty // Grid return","yves.=
djomo@sagemcom.com","12032","11-03-2025 22:13:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004552075","O=
bobogo","","11-03-2025 22:09:14","11-03-2025 21:53:10","12-03-2025 01:53:09=
","Active// No power issue site on grid with Ubai1=3D54.9V, Ubai2=3D53.5V S=
ite on Gen The TX Fme Hosiah / 674007438// from huawei is informed by sms",=
"MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active// No power issue site on grid with Ubai1=
=3D54.9V, Ubai2=3D53.5V Site on Gen The TX Fme Hosiah / 674007438// from hu=
awei is informed by sms","yves.djomo@sagemcom.com","965","11-03-2025 22:09:=
14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004552025","E=
foulan","","11-03-2025 21:58:35","11-03-2025 21:52:31","12-03-2025 01:53:32=
","Active: no power issue, site is ongrid with Ubaie=3D53V, TX Fme Brice Ts=
ague of huawei is informed","MINKA NICOLAS","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power is=
sue, site is ongrid with Ubaie=3D53V, TX Fme Brice Tsague of huawei is info=
rmed","yves.djomo@sagemcom.com","365","11-03-2025 21:58:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0004551919","N=
omayos-IHS","","11-03-2025 21:45:47","11-03-2025 21:41:42","11-03-2025 22:2=
6:05","Grid outage, site went down due to gen Overload(15KVA, 170A), Felix =
Zambe IHS is informed // Grid return","Fanda Brice","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
Overload(15KVA, 170A), Felix Zambe IHS is informed // Grid return","yves.dj=
omo@sagemcom.com","245","11-03-2025 21:45:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004551770","B=
ATA Mokolo OCM","","11-03-2025 21:26:42","11-03-2025 21:24:38","12-03-2025 =
00:15:57","Grid outage, No space to deploy a mobil gen //Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, No space to deploy a mobil gen //Grid return","yves.djomo@sagemcom.com"=
,"125","11-03-2025 21:26:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0004551724","Ekoumdou=
m OCM","","11-03-2025 21:20:50","11-03-2025 20:35:29","11-03-2025 23:11:17"=
,"Cascaded Incident from TTO4618142 - Cascade Removed From TTO4618142","Alb=
ran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Grid outage, site went down because gen start and stopped with alarm Low o=
il pressure // He reset gen card and gen manually started","system","278973=
","11-03-2025 21:20:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_255","NOCINC0004551723","Odza-PK1=
0","IHS_YND_527, IHS_YND_528, IHS_YND_291","11-03-2025 21:20:50","11-03-202=
5 20:35:29","11-03-2025 23:11:17","Grid outage, site went down because gen =
start and stopped with alarm Low oil pressure // He reset gen card and gen =
manually started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Grid outage, site went down because gen start and st=
opped with alarm Low oil pressure // He reset gen card and gen manually sta=
rted","system","2721","11-03-2025 21:20:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004551722","MEHANDAN=
","","11-03-2025 21:20:50","11-03-2025 20:35:29","11-03-2025 23:11:17","Cas=
caded Incident from TTO4618142 - Cascade Removed From TTO4618142","Albran B=
yorel","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid=
 outage, site went down because gen start and stopped with alarm Low oil pr=
essure // He reset gen card and gen manually started","system","278972","11=
-03-2025 21:20:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004551721","Odza II =
OCM","","11-03-2025 21:20:50","11-03-2025 20:35:29","11-03-2025 23:11:17","=
Cascaded Incident from TTO4618142 - Cascade Removed From TTO4618142","Albra=
n Byorel","Cascade Outage","Passive","Cascade Passive","Cascade Passive","G=
rid outage, site went down because gen start and stopped with alarm Low oil=
 pressure // He reset gen card and gen manually started","system","278972",=
"11-03-2025 21:20:50","Sagemcom CMR"
"Closed Complete","Site Down","T1333","IHS_YND_174","NOCINC0004551653","Car=
refourt Nkomo","","11-03-2025 21:03:43","11-03-2025 20:52:39","11-03-2025 2=
1:59:49","Site went down because gen failed to start due to grid bad voltag=
e // Gen manually started","Mba Lazare Herve","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Site went down because gen fai=
led to start due to grid bad voltage // Gen manually started","yves.djomo@s=
agemcom.com","666","11-03-2025 21:03:43","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004551640","Jou=
vence Mbenda","","11-03-2025 21:01:38","11-03-2025 20:56:31","11-03-2025 21=
:26:46","Grid outage.gen failed to start due to ""high temp"" alarm // We a=
dd water and gen manually started","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outa=
ge.gen failed to start due to ""high temp"" alarm // We add water and gen m=
anually started","yves.djomo@sagemcom.com","308","11-03-2025 21:01:38","Sag=
emcom CMR"
"Closed Complete","Site Down","T0539","IHS_YND_034","NOCINC0004551616","EMI=
A MTN","","11-03-2025 20:58:17","11-03-2025 20:34:12","12-03-2025 07:53:09"=
,"Grid Outage No Space to deploy a MDG //Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space to d=
eploy a MDG //Grid return","yves.djomo@sagemcom.com","1446","11-03-2025 20:=
58:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004551586","O=
dza","","11-03-2025 20:53:32","11-03-2025 20:35:29","11-03-2025 22:17:47","=
Grid outage, site went down because gen faile to start due theft battery ge=
n//Grid return","Albran Byorel","Site Asset Theft","Theft","Theft","Generat=
or Battery Theft","Grid outage, site went down because gen faile to start d=
ue theft battery gen//Grid return","yves.djomo@sagemcom.com","1084","11-03-=
2025 20:53:32","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004551561","Elo=
umdem stade","","11-03-2025 20:48:57","11-03-2025 20:04:55","11-03-2025 23:=
59:57","Site went down because gen failed to start due to grid bad voltage =
// Gen manually started","Fanda Brice","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","Site went down because gen failed to =
start due to grid bad voltage // Gen manually started","yves.djomo@sagemcom=
.com","2644","11-03-2025 20:48:57","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004551326","Nko=
ulou Carriere carrefourt","","11-03-2025 20:05:52","11-03-2025 19:43:25","1=
1-03-2025 21:27:30","Site went down due to malfunction of 02/04 rectifiers =
 // He reset 02 rectifiers, site on grid","Mba Lazare Herve","Equipment Rep=
air","Passive","Rectifier","Rectifier Module","Site went down due to malfun=
ction of 02/04 rectifiers  // He reset 02 rectifiers, site on grid","el-dal=
ile@sagemcom.com","1348","11-03-2025 20:05:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004551283","MONTEE N=
KONDENGUI","","11-03-2025 20:00:50","11-03-2025 19:52:06","11-03-2025 19:58=
:44","Cascaded Incident from TTO4617792","Albran Byorel","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active//No power issue, site is =
on Grid with Ubaie=3D54,5 V, Eloundou bertrant(652586578) from Huawei is in=
formed","system","266951","11-03-2025 20:00:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004551280","M=
obil-Kondengui","IHS_YND_682","11-03-2025 20:00:11","11-03-2025 19:52:06","=
11-03-2025 20:20:44","Active//No power issue, site is on Grid with Ubaie=3D=
54,5 V, Eloundou bertrant(652586578) from Huawei is informed","","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue, site is on Grid with Ubaie=3D54,5 V, Eloundou ber=
trant(652586578) from Huawei is informed","yves.djomo@sagemcom.com","486","=
11-03-2025 20:00:11","Sagemcom CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004551226","Mes=
sassi okolo","","11-03-2025 19:47:34","11-03-2025 19:37:30","11-03-2025 20:=
39:45","Grid outage, site went down because gen start and stopped with alar=
m Low oil pressure // He reset gen card and gen manually started","Fabrice =
Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage, site went down because gen start and stopped with alarm Low oil =
pressure // He reset gen card and gen manually started","yves.djomo@sagemco=
m.com","605","11-03-2025 19:47:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004551221","E=
mana lycee 2","","11-03-2025 19:46:32","11-03-2025 19:37:28","11-03-2025 20=
:55:25","Grid outage, Site went because Gen started and stopped with ""High=
 temp"" alarm // He added water and started Gen manualy","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, Site went because Gen started and stopped with "=
"High temp"" alarm // He added water and started Gen manualy","yves.djomo@s=
agemcom.com","545","11-03-2025 19:46:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004551161","N=
kozoa","","11-03-2025 19:35:49","11-03-2025 19:10:46","11-03-2025 23:13:48"=
,"Site went down due disjunction of Cb(2*63A) in PWC // He bypassed Cb(2*63=
A) , site on grid","Fabrice Pouakam","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Circuit Breaker Issue","Site went down due disjunct=
ion of Cb(2*63A) in PWC // He bypassed Cb(2*63A) , site on grid","yves.djom=
o@sagemcom.com","1505","11-03-2025 19:35:49","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004551136","Men=
dong3","","11-03-2025 19:31:48","11-03-2025 19:27:37","12-03-2025 08:27:29"=
,"Grid Outage No Space to deploy a MDG // Grid Restored","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space t=
o deploy a MDG // Grid Restored","el-dalile@sagemcom.com","252","11-03-2025=
 19:31:48","Sagemcom CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0004550930","Ema=
na Lycee","","11-03-2025 19:04:21","11-03-2025 18:48:16","11-03-2025 20:28:=
33","Grid outage, Site went down because Gen ran until fuel shortage// Refu=
eling Done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, Site went down because Gen ran until fuel shortage// Refu=
eling Done","yves.djomo@sagemcom.com","967","11-03-2025 19:04:21","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004550807","Sof=
avinc","","11-03-2025 18:41:37","11-03-2025 18:33:33","11-03-2025 19:25:50"=
,"Grid outage, site went down because gen failed to start due to gen contac=
tor faulty // He bypassed gen contactor and gen manually started","MINKA NI=
COLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Gri=
d outage, site went down because gen failed to start due to gen contactor f=
aulty // He bypassed gen contactor and gen manually started","yves.djomo@sa=
gemcom.com","485","11-03-2025 18:41:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004550804","Nomayos =
montee Meche","","11-03-2025 18:40:32","11-03-2025 18:24:58","11-03-2025 18=
:54:48","Cascaded Incident from TTO4617197","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went alarm=
 because main gen faulty // MDG 20Kva has deployed. But MTN still down beca=
use Gen does not support load","system","272455","11-03-2025 18:40:32","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004550772","Angongo"=
,"","11-03-2025 18:37:55","11-03-2025 18:24:58","11-03-2025 18:54:33","Casc=
aded Incident from TTO4617122","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went alarm because main=
 gen faulty // MDG 20Kva has deployed. But MTN still down because Gen does =
not support load","system","272455","11-03-2025 18:37:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004550771","Donga","=
","11-03-2025 18:37:55","11-03-2025 18:24:58","11-03-2025 18:54:33","Cascad=
ed Incident from TTO4617122","Parker Tchoup","Equipment Repair","Passive","=
ACDG Gen","ACDG - Generator Faulty","Grid outage, site went alarm because m=
ain gen faulty // MDG 20Kva has deployed. But MTN still down because Gen do=
es not support load","system","777","11-03-2025 18:37:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004550773","Nkongtoc=
k","","11-03-2025 18:37:55","11-03-2025 18:24:58","11-03-2025 18:54:33","Ca=
scaded Incident from TTO4617122","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went alarm becaus=
e main gen faulty // MDG 20Kva has deployed. But MTN still down because Gen=
 does not support load","system","272454","11-03-2025 18:37:55","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004550768","Mandoumb=
a OCM","","11-03-2025 18:37:54","11-03-2025 18:24:58","11-03-2025 18:54:33"=
,"Cascaded Incident from TTO4617122","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went alarm be=
cause main gen faulty // MDG 20Kva has deployed. But MTN still down because=
 Gen does not support load","system","272454","11-03-2025 18:37:54","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004550767","Sous Pre=
fecture","","11-03-2025 18:37:54","11-03-2025 18:24:58","11-03-2025 18:54:3=
3","Cascaded Incident from TTO4617122","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went alarm beca=
use main gen faulty // MDG 20Kva has deployed. But MTN still down because G=
en does not support load","system","272455","11-03-2025 18:37:54","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004550770","Nkenglik=
ok","","11-03-2025 18:37:54","11-03-2025 18:24:58","11-03-2025 18:54:33","C=
ascaded Incident from TTO4617122","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went alarm becau=
se main gen faulty // MDG 20Kva has deployed. But MTN still down because Ge=
n does not support load","system","272455","11-03-2025 18:37:54","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004550769","Mbankomo=
 IHS","","11-03-2025 18:37:54","11-03-2025 18:24:58","11-03-2025 18:54:33",=
"Cascaded Incident from TTO4617122","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went alarm because=
 main gen faulty // MDG 20Kva has deployed. But MTN still down because Gen =
does not support load","system","272456","11-03-2025 18:37:54","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004550721","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_791, IHS_YND_695, IHS_YND_348, I=
HS_YND_762, IHS_YND_335, IHS_YND_349","11-03-2025 18:29:02","11-03-2025 18:=
24:58","11-03-2025 18:54:48","Grid outage, site went down because main gen =
faulty // MDG 20Kva has deployed. But MTN still down because Gen does not s=
upport load","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - =
Generator Faulty","Grid outage, site went down because main gen faulty // M=
DG 20Kva has deployed. But MTN still down because Gen does not support load=
","yves.djomo@sagemcom.com","245","11-03-2025 18:29:02","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004550678","Aka=
k-Nkozoa-MTN-IHS","","11-03-2025 18:20:53","11-03-2025 17:43:34","11-03-202=
5 23:46:25","Site went down due to PWC Huawei malfunction // He reduced pow=
er red, site on grid","Fabrice Pouakam","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Site went down due to PWC Huawei malfu=
nction // He reduced power red, site on grid","el-dalile@sagemcom.com","224=
1","11-03-2025 18:20:53","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004550611","Eto=
 koss Yde","","11-03-2025 18:09:26","11-03-2025 18:00:06","11-03-2025 18:28=
:31","Grid outage, site went down because gen failed to start // Grid retur=
n (Investigation ongoing)","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid outage, site went down because gen faile=
d to start // Grid return (Investigation ongoing)","el-dalile@sagemcom.com"=
,"561","11-03-2025 18:09:26","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004550585","Car=
refour Simbock","","11-03-2025 18:04:53","11-03-2025 17:53:34","11-03-2025 =
18:50:19","Grid outage, site went down due to gen overload(17KVA,200A), Fel=
ix IHS is informed // He reduced the load and gen manually started","Hyemaf=
o Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, site went down due to gen overload(17KVA,200A), Felix IHS is informe=
d // He reduced the load and gen manually started","el-dalile@sagemcom.com"=
,"680","11-03-2025 18:04:53","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004550553","MBA=
LNGONG LYCEE","","11-03-2025 17:56:48","11-03-2025 17:35:39","11-03-2025 22=
:26:20","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, Site went down because Gen stopped due to overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed//Grid return","el-dalile@sagemcom.com=
","1271","11-03-2025 17:56:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004550463","Dong",""=
,"11-03-2025 17:40:13","11-03-2025 15:07:46","11-03-2025 17:39:23","Cascade=
d Incident from TTO4615487","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Hybrid Gen: Site went down because started=
 and stopped due to 'overcurrent"" alarm// He purged circuit fuel, reset Ge=
n card and started Gen manualy","system","276939","11-03-2025 17:40:13","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004550462","Donga","=
","11-03-2025 17:40:13","11-03-2025 15:07:46","11-03-2025 17:39:23","Cascad=
ed Incident from TTO4615487","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Hybrid Gen: Site went down because starte=
d and stopped due to 'overcurrent"" alarm// He purged circuit fuel, reset G=
en card and started Gen manualy","system","276939","11-03-2025 17:40:13","S=
agemcom CMR"
"Closed Complete","Site Down","T0107","IHS_YND_271","NOCINC0004550370","Yon=
a Hotel","","11-03-2025 17:26:31","11-03-2025 17:05:27","11-03-2025 18:01:1=
5","Grid outage, site went down because gen failed to start due to grid con=
tactor faulty // He bipassed grid contactor and gen manually started","TIEN=
TCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","ATS-AMF=
 Issue","Grid outage, site went down because gen failed to start due to gri=
d contactor faulty // He bipassed grid contactor and gen manually started",=
"yves.djomo@sagemcom.com","36764","11-03-2025 17:26:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004550361","O=
LAMA","","11-03-2025 17:24:11","11-03-2025 17:19:07","11-03-2025 17:23:59",=
"Active//No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri (699949693)=
 from Huawei is informed","yves.djomo@sagemcom.com","305","11-03-2025 17:24=
:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004550229","B=
astos Bir","","11-03-2025 17:03:08","11-03-2025 15:27:00","12-03-2025 05:47=
:24","Active//No power issue, site is on Gen with Ubaie=3D50 V, Eloundou be=
rtrant(652586578) from Huawei is informed","Mboua Thierry","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active//No power issue, site i=
s on Gen with Ubaie=3D50 V, Eloundou bertrant(652586578) from Huawei is inf=
ormed","ludivine.ngamaleu@ihstowers.com","282917","11-03-2025 17:03:08","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_137","NOCINC0004550216","Masque",=
"","11-03-2025 17:01:30","11-03-2025 15:27:00","11-03-2025 15:30:28","Casca=
ded Incident from TTO4615776","Fabrice Pouakam","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue, site is on Gen wi=
th Ubaie=3D50 V, Eloundou bertrant(652586578) from Huawei is informed","sys=
tem","282917","11-03-2025 17:01:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004550217","ARMP",""=
,"11-03-2025 17:01:30","11-03-2025 15:27:00","11-03-2025 15:30:28","Cascade=
d Incident from TTO4615776","","Cascade Outage","Active","Cascade Active","=
Cascade Active","Active//No power issue, site is on Gen with Ubaie=3D50 V, =
Eloundou bertrant(652586578) from Huawei is informed","system","282917","11=
-03-2025 17:01:30","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004550147","Elo=
umdem stade","","11-03-2025 16:48:59","11-03-2025 16:13:55","11-03-2025 17:=
48:48","Grid outage, Site went down because Gen failed to start// Grid retu=
rn (investigation ongoing) ","Fanda Brice","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage, Site went down because Gen fai=
led to start// Grid return (investigation ongoing) ","yves.djomo@sagemcom.c=
om","2105","11-03-2025 16:48:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004550123","N=
kolfon Cimencam","","11-03-2025 16:44:16","11-03-2025 16:29:12","11-03-2025=
 18:54:48","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went alarm because main gen faulty //=
 MDG 20Kva has deployed. But MTN still down because Gen does not support lo=
ad","yves.djomo@sagemcom.com","905","11-03-2025 16:44:16","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004550064","Ako=
k Ndoe Yde","","11-03-2025 16:36:09","11-03-2025 16:24:57","11-03-2025 16:5=
8:04","Grid outage, site went down before gen start due to poor battery bac=
kup // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before ge=
n start due to poor battery backup // Grid return","el-dalile@sagemcom.com"=
,"673","11-03-2025 16:36:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004550059","N=
kolbong","","11-03-2025 16:35:12","11-03-2025 16:27:07","11-03-2025 16:39:4=
3","Grid outage, site went down before gen start due to poor battery backup=
 // Gen started automatically","Delor Telezing","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen started automatically"=
,"yves.djomo@sagemcom.com","486","11-03-2025 16:35:12","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004550054","HOP=
ITAL GENERAL RAIL YDE","","11-03-2025 16:33:46","11-03-2025 16:27:42","11-0=
3-2025 18:47:14","Grid outage, site went down due to gen Overload(09kva,160=
A), Bernard IHS is informed // Grid return","Delor Telezing","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down du=
e to gen Overload(09kva,160A), Bernard IHS is informed // Grid return","yve=
s.djomo@sagemcom.com","364","11-03-2025 16:33:46","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0004550048","San=
ta Barbara Gottam","","11-03-2025 16:32:22","11-03-2025 16:19:18","11-03-20=
25 17:26:06","Grid outage, site went down because gen start and stopped wit=
h alarm overcurrent // He reset gen card and gen manually started","Delor T=
elezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage, site went down because gen start and stopped with alarm overcurr=
ent // He reset gen card and gen manually started","yves.djomo@sagemcom.com=
","785","11-03-2025 16:32:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004550014","M=
ontee-Jouvence-II","","11-03-2025 16:25:23","11-03-2025 16:13:20","11-03-20=
25 17:09:48","Grid outage, Site went down because Gen overload (15kva, 250A=
)  SS IHS Felix Zambe is informed// He started gen manualy","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, S=
ite went down because Gen overload (15kva, 250A)  SS IHS Felix Zambe is inf=
ormed// He started gen manualy","yves.djomo@sagemcom.com","725","11-03-2025=
 16:25:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004549989","E=
kounou","","11-03-2025 16:22:51","11-03-2025 16:11:48","11-03-2025 16:45:55=
","Grid fluctuation,Site went down because Gen failed to start due to grid =
bad voltage and no RCP //","Albran Byorel","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","Grid fluctuation,Site went down b=
ecause Gen failed to start due to grid bad voltage and no RCP //Grid Restor=
ed","yves.djomo@sagemcom.com","664","11-03-2025 16:22:51","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004549963","ELO=
UMDEM CARRIERE","","11-03-2025 16:17:46","11-03-2025 16:07:33","11-03-2025 =
18:28:50"," Grid outage Site went down because Gen failed to start // Grid =
power return (Investigation ongoing)","Fanda Brice","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel"," Grid outage Site went down becaus=
e Gen failed to start // Grid power return (Investigation ongoing)","el-dal=
ile@sagemcom.com","615","11-03-2025 16:17:46","Sagemcom CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0004549936","Eto=
udi 2","","11-03-2025 16:16:10","11-03-2025 16:05:59","11-03-2025 16:30:29"=
,"Grid outage, site went down because gen start and stopper with alarl Over=
current // He reset gen card and gen manually started","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, =
site went down because gen start and stopper with alarl Overcurrent // He r=
eset gen card and gen manually started","el-dalile@sagemcom.com","612","11-=
03-2025 16:16:10","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004549912","Beh=
ind P T school Yde","","11-03-2025 16:12:33","11-03-2025 15:59:08","11-03-2=
025 17:49:24","Grid outage, site went down because gen failed to start due =
to gen card faulty //Gen manually started","Paul BIBOUM","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down b=
ecause gen failed to start due to gen card faulty //Gen manually started","=
el-dalile@sagemcom.com","806","11-03-2025 16:12:33","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004549891","Mes=
sa Carriere","","11-03-2025 16:11:04","11-03-2025 15:57:49","11-03-2025 16:=
19:45","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty //Gen manually started","Mboua Thierry","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down bec=
ause Gen failed to started due to Gen card faullty //Gen manually started",=
"el-dalile@sagemcom.com","796","11-03-2025 16:11:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0004549887","M=
adagascar-Yde-New","","11-03-2025 16:10:54","11-03-2025 15:40:49","11-03-20=
25 19:09:13","Grid outage no space to deploy a mobil gen// Grid return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage no space to deploy a mobil gen// Grid return","yves.djomo@sagemcom.com=
","1806","11-03-2025 16:10:54","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004549869","SOA=
 TOWN","","11-03-2025 16:07:46","11-03-2025 15:57:55","11-03-2025 16:24:30"=
,"Gri doutage, site went down because gen failed to start gen card faulty /=
/ Gen manuallys started","Siligap Boris","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Gri doutage, site went down because gen faile=
d to start gen card faulty // Gen manuallys started","el-dalile@sagemcom.co=
m","592","11-03-2025 16:07:46","Sagemcom CMR"
"Closed Complete","Site Down","T1579","IHS_YND_480","NOCINC0004549826","Sic=
 Cite Verte Matgenie","","11-03-2025 16:05:15","11-03-2025 15:53:00","14-03=
-2025 11:10:54","Grid bad voltage, No Space to deploy a MDG // gid return",=
"","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid bad voltage, No Space to deploy a MDG // gid return","el-dalile@sage=
mcom.com","736","11-03-2025 16:05:15","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004549807","ODZ=
A CITE MBIA","","11-03-2025 16:03:54","11-03-2025 15:52:39","11-03-2025 18:=
06:01","Site went down because gen failed to start due to grid bad voltage =
and no RCP// He bypassed the grid and gen manually started","Albran Byorel"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Site went down because gen failed to start due to grid bad voltage and no R=
CP// He bypassed the grid and gen manually started","el-dalile@sagemcom.com=
","676","11-03-2025 16:03:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004549806","M=
ini-Ferme","","11-03-2025 16:03:37","11-03-2025 15:27:30","11-03-2025 17:02=
:51","Grid outage no space to deploy a MDG // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space=
 to deploy a MDG // Grid return","yves.djomo@sagemcom.com","2168","11-03-20=
25 16:03:37","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004549797","Bar=
riere","","11-03-2025 16:02:29","11-03-2025 15:52:25","11-03-2025 18:28:31"=
,"Grid outage, Site went because Gen started and stopped due Gen Overload (=
20KVA, 450A) SS IHS Felix Zambe confirmed// Grid power return","Hyemafo Gil=
das","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
, Site went because Gen started and stopped due Gen Overload (20KVA, 450A) =
SS IHS Felix Zambe confirmed// Grid power return","yves.djomo@sagemcom.com"=
,"605","11-03-2025 16:02:29","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004549767","NYO=
M FACE MAETUR","","11-03-2025 15:59:44","11-03-2025 15:47:34","11-03-2025 1=
6:12:11","Grid outage, site went down because Gen failed to started due to =
Gen card faullty //Grid return","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
Gen failed to started due to Gen card faullty //Grid return","el-dalile@sag=
emcom.com","731","11-03-2025 15:59:44","Sagemcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004549744","Tam=
tam Weekend","","11-03-2025 15:58:16","11-03-2025 15:45:58","11-03-2025 15:=
45:59","Active//No power issue site on Grid with U=3D54.5 V   The TX FME Mb=
ah Hosiah (674007438) FROM Huawei is informed. ","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue site on Grid with U=3D54.5 V   The TX FME Mbah Ho=
siah (674007438) FROM Huawei is informed. ","el-dalile@sagemcom.com","739",=
"11-03-2025 15:58:16","Sagemcom CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0004549723","Dag=
obert","","11-03-2025 15:57:01","11-03-2025 15:44:46","11-03-2025 15:50:41"=
,"Active: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(69114=
4435) from Huawei is infomred","TIENTCHEU NZETCHIEU GAEL","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435) f=
rom Huawei is infomred","el-dalile@sagemcom.com","736","11-03-2025 15:57:01=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004549719","Essomba"=
,"","11-03-2025 15:56:09","11-03-2025 15:46:06","11-03-2025 16:34:07","Casc=
aded Incident from TTO4615927","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down Gen fail=
ed to start due to PWC ZTE malfunction // Grid return","system","274504","1=
1-03-2025 15:56:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004549713","B=
iteng","IHS_YND_292, IHS_YND_179","11-03-2025 15:55:10","11-03-2025 15:46:0=
6","11-03-2025 16:34:07","Grid outage, site went down Gen failed to start d=
ue to PWC ZTE malfunction // Grid return","Mba Lazare Herve","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site=
 went down Gen failed to start due to PWC ZTE malfunction // Grid return","=
yves.djomo@sagemcom.com","546","11-03-2025 15:55:10","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004549702","NYO=
M 2 IHS","","11-03-2025 15:52:33","11-03-2025 15:44:16","11-03-2025 16:20:1=
6","Grid outage, Site went down because Gen failed to start  // Grid return=
 (investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage, Site went down because Gen fa=
iled to start  // Grid return (investigation ongoing)","el-dalile@sagemcom.=
com","498","11-03-2025 15:52:33","Sagemcom CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004549680","Par=
adis Hotel","","11-03-2025 15:50:29","11-03-2025 15:43:21","11-03-2025 17:4=
2:16","Grid outage, site went down because gen start and stopped with alarm=
 under frequency // He reduced the load and reset gen card, site on gen","S=
iligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Under Frequen=
cy","Grid outage, site went down because gen start and stopped with alarm u=
nder frequency // He reduced the load and reset gen card, site on gen","el-=
dalile@sagemcom.com","429","11-03-2025 15:50:29","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004549625","Av =
Kennedy","","11-03-2025 15:42:30","11-03-2025 15:35:16","11-03-2025 15:40:3=
1","Active//No power issue, site is on Grid with Ubaie=3D53 V, Eloundou ber=
trant(652586578) from Huawei is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue, site is on Grid with Ubaie=3D53 V, Eloundou bertrant(652586578) from =
Huawei is informed","el-dalile@sagemcom.com","435","11-03-2025 15:42:30","S=
agemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004549620","Ebo=
go","","11-03-2025 15:42:05","11-03-2025 15:35:02","11-03-2025 16:23:50","G=
rid outage, Site went down before Gen start due to poor backup// Gen Automa=
tically Started","Siligap Boris","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup// Gen Automatically Started","yves.djomo@sagemcom.co=
m","425","11-03-2025 15:42:05","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004549596","An-=
Marche-Melen","","11-03-2025 15:40:13","11-03-2025 15:33:01","11-03-2025 23=
:22:49","Site went down due to insufficiency of rectifiers, Francois IHS //=
 He reduced the load	","","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to insufficiency of rectifiers, Francois IHS=
 // He reduced the load	","el-dalile@sagemcom.com","433","11-03-2025 15:40:=
13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0004549587","Mbankolo=
 petit paris","","11-03-2025 15:39:11","11-03-2025 15:31:12","11-03-2025 15=
:35:40","Cascaded Incident from TTO4615773","Mboua Thierry","Cascade Outage=
","Active","Cascade Active","Cascade Active","Active; no power issue site o=
n Grid with U=3D54,1 V;The fme TX Mohammadou 691144435 of huawei is informe=
d","system","282575","11-03-2025 15:39:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004549585","D=
ragage","IHS_YND_704, IHS_YND_137, IHS_YND_208","11-03-2025 15:39:04","11-0=
3-2025 15:27:00","11-03-2025 15:30:28","Active//No power issue, site is on =
Gen with Ubaie=3D50 V, Eloundou bertrant(652586578) from Huawei is informed=
","Mboua Thierry","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active//No power issue, site is on Gen with U=
baie=3D50 V, Eloundou bertrant(652586578) from Huawei is informed","yves.dj=
omo@sagemcom.com","725","11-03-2025 15:39:04","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0004549582","AFE=
ME NORD","IHS_YND_808","11-03-2025 15:38:20","11-03-2025 15:31:12","11-03-2=
025 15:35:40","Active; no power issue site on Grid with U=3D54,1 V;The fme =
TX Mohammadou 691144435 of huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active; no power issue site on Grid with U=3D54,1 V;The fme TX M=
ohammadou 691144435 of huawei is informed","el-dalile@sagemcom.com","429","=
11-03-2025 15:38:20","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004549563","CRH=
-Etoug-Ebe","","11-03-2025 15:37:22","11-03-2025 15:29:09","11-03-2025 15:4=
5:14","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"el-dalile@sagemcom.com","494","11-03-2025 15:37:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0004549485","Carrefou=
rt Nkomo","","11-03-2025 15:29:40","11-03-2025 15:24:03","11-03-2025 16:32:=
28","Cascaded Incident from TTO4615661","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went beca=
use Gen ran until fuel shortage//Refueling Done","system","276125","11-03-2=
025 15:29:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0004549479","N=
komo","IHS_YND_174","11-03-2025 15:29:06","11-03-2025 15:24:03","11-03-2025=
 16:32:28","Grid outage, Site went because Gen ran until fuel shortage//Ref=
ueling Done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage, Site went because Gen ran until fuel shortage//Refuelin=
g Done","yves.djomo@sagemcom.com","304","11-03-2025 15:29:06","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004549454","S=
OA UNIVERSITY STADIUM","","11-03-2025 15:26:03","11-03-2025 15:12:59","11-0=
3-2025 20:39:52","Active//No power issue on site Ubaie =3D56,3V site on Gen=
 The TX RM Alain (691144423) from Huawei is informed","Siligap Boris","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site Ubaie =3D56,3V site on Gen The TX RM =
Alain (691144423) from Huawei is informed","yves.djomo@sagemcom.com","785",=
"11-03-2025 15:26:03","Sagemcom CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004549394","NTE=
MASSI","","11-03-2025 15:20:28","11-03-2025 15:15:24","11-03-2025 17:02:39"=
,"Grid outage, site went down because gen failed start due to gen card faul=
ty // Gen manually started","Delor Telezing","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen f=
ailed start due to gen card faulty // Gen manually started","yves.djomo@sag=
emcom.com","305","11-03-2025 15:20:28","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004549382","Awa=
e Ewonkan","","11-03-2025 15:18:57","11-03-2025 15:14:54","11-03-2025 16:33=
:50","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went do=
wn because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // He=
 reduced the load","yves.djomo@sagemcom.com","245","11-03-2025 15:18:57","S=
agemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004549358","Nko=
ulou Carriere carrefourt","","11-03-2025 15:15:42","11-03-2025 15:11:35","1=
1-03-2025 15:37:53","Site went down because gen overload (13Kw, 180A) SS IH=
S Alphonse DEFFO is informed// he Reduice the Load and Site is on Gen","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","S=
ite went down because gen overload (13Kw, 180A) SS IHS Alphonse DEFFO is in=
formed// he Reduice the Load and Site is on Gen","el-dalile@sagemcom.com","=
248","11-03-2025 15:15:42","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004549326","Ngu=
ila","IHS_YND_434, IHS_YND_444","11-03-2025 15:12:55","11-03-2025 15:07:46"=
,"11-03-2025 17:43:06","Hybrid Gen: Site went down because started and stop=
ped due to 'overcurrent"" alarm// He purged circuit fuel, reset Gen card an=
d started Gen manualy","Parker Tchoup","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Hybrid Gen: Site went down because started and =
stopped due to 'overcurrent"" alarm// He purged circuit fuel, reset Gen car=
d and started Gen manualy","el-dalile@sagemcom.com","311","11-03-2025 15:12=
:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004549304","S=
tade-Abega","","11-03-2025 15:08:33","11-03-2025 15:05:29","11-03-2025 16:3=
2:55","Grid outage, site went down because gen failed to start due to Pwc Z=
TE dysfunction// He reset it and started Gen manualy","Mba Lazare Herve","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid =
outage, site went down because gen failed to start due to Pwc ZTE dysfuncti=
on// He reset it and started Gen manualy","yves.djomo@sagemcom.com","185","=
11-03-2025 15:08:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004549281","B=
iteng-Maetur","","11-03-2025 15:06:13","11-03-2025 14:51:09","11-03-2025 17=
:51:29","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","yves.dj=
omo@sagemcom.com","906","11-03-2025 15:06:13","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0004549241","Bit=
oto","","11-03-2025 15:00:54","11-03-2025 14:56:41","11-03-2025 16:06:48","=
","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Cascade =
Passive","Grid outage, site went down Gen failed to start due to PWC ZTE ma=
lfunction // Grid return","el-dalile@sagemcom.com","254","11-03-2025 15:00:=
54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004549118","Emana Ly=
cee","","11-03-2025 14:47:53","11-03-2025 14:41:48","11-03-2025 16:34:44","=
Cascaded Incident from TTO4615220","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen start and stopped with alarm ""high temp"" // He added water and man=
ually start the Gen","system","278571","11-03-2025 14:47:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004549096","E=
mana lycee 2","IHS_YND_274","11-03-2025 14:43:52","11-03-2025 14:41:48","11=
-03-2025 16:34:44","Grid outage, site went down because gen start and stopp=
ed with alarm ""high temp"" // He added water and manually start the Gen","=
Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engin=
e Temp - Coolant Level Issue","Grid outage, site went down because gen star=
t and stopped with alarm ""high temp"" // He added water and manually start=
 the Gen","yves.djomo@sagemcom.com","125","11-03-2025 14:43:52","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_159","NOCINC0004549042","Complexe=
-BEAC","","11-03-2025 14:32:41","11-03-2025 14:19:30","11-03-2025 16:45:49"=
,"Cascaded Incident from TTO4615133","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because gen failed=
 to start due to grid bad voltage and no RCP// He bypassed the grid and gen=
 manually started","system","287011","11-03-2025 14:32:41","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004549040","Aka=
k-Nkozoa-MTN-IHS","","11-03-2025 14:31:51","11-03-2025 14:26:42","11-03-202=
5 16:26:14","Grid fluctuation, site went down because Gen started and stopp=
ed to start due to grid bad voltage// He bypassed the grid and started Gen =
manually","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Grid fluctuation, site went down because Gen sta=
rted and stopped to start due to grid bad voltage// He bypassed the grid an=
d started Gen manually","el-dalile@sagemcom.com","311","11-03-2025 14:31:51=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004549026","E=
kie-Elegance","IHS_YND_159","11-03-2025 14:29:18","11-03-2025 14:19:30","11=
-03-2025 16:45:49","Site went down because gen failed to start due to grid =
bad voltage and no RCP// He bypassed the grid and gen manually started","Al=
bran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Site went down because gen failed to start due to grid bad volt=
age and no RCP// He bypassed the grid and gen manually started","yves.djomo=
@sagemcom.com","589","11-03-2025 14:29:18","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004548851","AWA=
E OCM","","11-03-2025 14:09:35","11-03-2025 13:59:25","11-03-2025 14:16:07"=
,"Grid outage, Site went down before gen start due to poor battery backup /=
/ Gen started automatically","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before gen start due to poor battery backup // Gen started automatically"=
,"ludovic-anselme.mouliom-mapoure@sagemcom","611","11-03-2025 14:09:35","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004548838","Bit=
eng-Maetur","","11-03-2025 14:08:18","11-03-2025 14:02:13","11-03-2025 14:0=
9:21","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","Mb=
a Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage, Site went down because Gen started and stopped due to Gen over=
load(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","ludovic-a=
nselme.mouliom-mapoure@sagemcom","389","11-03-2025 14:08:18","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004548831","Awa=
e Escalier","","11-03-2025 14:07:13","11-03-2025 14:05:08","11-03-2025 16:3=
6:26","Grid outage, site went down because gen failed to start // Grid retu=
rn (Investigation ongoing)","Albran Byorel","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage, site went down because gen fa=
iled to start // Grid return (Investigation ongoing)","ludovic-anselme.moul=
iom-mapoure@sagemcom","126","11-03-2025 14:07:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004548806","M=
ontee-Des-Soeurs","","11-03-2025 14:03:32","11-03-2025 13:57:29","11-03-202=
5 14:08:33","Grid outage, Site went down before gen start due to poor batte=
ry backup // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore gen start due to poor battery backup // Grid return","mariam.tchonang@s=
agemcom.com","365","11-03-2025 14:03:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004548611","B=
ATA Mokolo OCM","","11-03-2025 13:41:59","11-03-2025 12:50:49","11-03-2025 =
20:46:20","Grid outage no space to deploy a mobil gen // Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge no space to deploy a mobil gen // Grid return","ludovic-anselme.mouliom-=
mapoure@sagemcom","3071","11-03-2025 13:41:59","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004548306","Mam=
bine","","11-03-2025 13:17:34","11-03-2025 13:05:24","11-03-2025 15:27:33",=
"Hybrid Gen Site, site went down due to hybrid system dysfunctionning//He r=
eset and Gen started manaully","Fanda Brice","Equipment Repair","Passive","=
Hybrid","Hybrid Module","Hybrid Gen Site, site went down due to hybrid syst=
em dysfunctionning//He reset and Gen started manaully","ludovic-anselme.mou=
liom-mapoure@sagemcom","806","11-03-2025 13:17:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004547490","Saa","",=
"11-03-2025 12:00:35","11-03-2025 11:22:26","11-03-2025 11:43:05","Cascaded=
 Incident from TTO4613344","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to work: SS IHS Felix BA=
TEU working on site// End of work","system","2289","11-03-2025 12:00:35","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004547489","SAA Entr=
ance","","11-03-2025 12:00:35","11-03-2025 11:22:26","11-03-2025 11:43:05",=
"Cascaded Incident from TTO4613344","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work: SS IHS=
 Felix BATEU working on site// End of work","system","2289","11-03-2025 12:=
00:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004547482","S=
AA 2","IHS_YND_542, IHS_YND_405","11-03-2025 11:59:35","11-03-2025 11:22:26=
","11-03-2025 11:43:05","Site went down due to work: SS IHS Felix BATEU wor=
king on site// End of work","Parker Tchoup","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to work: =
SS IHS Felix BATEU working on site// End of work","ludovic-anselme.mouliom-=
mapoure@sagemcom","2231","11-03-2025 11:59:35","Sagemcom CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0004547169","NKO=
NGKARAK","","11-03-2025 11:55:48","11-03-2025 11:52:34","11-03-2025 14:10:1=
8","Site went down because Gen started and stopped due to pierced pellet //=
 he glued the Pellet and Manually Started The Gen","TIENTCHEU NZETCHIEU GAE=
L","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","Site went dow=
n because Gen started and stopped due to pierced pellet // he glued the Pel=
let and Manually Started The Gen","ludovic-anselme.mouliom-mapoure@sagemcom=
","195","11-03-2025 11:55:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004546997","E=
kombitie","","11-03-2025 11:47:32","11-03-2025 11:45:23","11-03-2025 12:36:=
43","Site went down because gen fails to start due to grid bad voltage // H=
e bypass grid and manually start the gen","Fabrice Pouakam","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Site went down b=
ecause gen fails to start due to grid bad voltage // He bypass grid and man=
ually start the gen","ludovic-anselme.mouliom-mapoure@sagemcom","130","11-0=
3-2025 11:47:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004546989","E=
vodoula OCM","","11-03-2025 11:46:13","11-03-2025 11:41:04","11-03-2025 11:=
41:05","No power issue site and with Ubaie=3D54.4 V site on Gen The FME TX =
Mouamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue site and with Ubaie=3D54.4 V site on Gen The FME =
TX Mouamadou/658791013 //From Huawei is informed","mariam.tchonang@sagemcom=
.com","310","11-03-2025 11:46:13","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004546980","OTE=
LE MTN","","11-03-2025 11:45:44","11-03-2025 11:42:35","11-03-2025 12:01:05=
","Site went down due to work: SS IHS Felix Zambe working on site(replaceme=
nt of rectifier)// End of work","Fanda Brice","Installation Activity","Pass=
ive","Planned Activity","Installation Activity","Site went down due to work=
: SS IHS Felix Zambe working on site(replacement of rectifier)// End of wor=
k","ludovic-anselme.mouliom-mapoure@sagemcom","190","11-03-2025 11:45:44","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_745","NOCINC0004546895","Okolo Ki=
lombo","","11-03-2025 11:37:41","11-03-2025 11:22:29","11-03-2025 12:08:40"=
,"Grid outage, site went down because gen fails to start due to Gen cable f=
aulty // Gen manualy started","Fabrice Pouakam","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because ge=
n fails to start due to Gen cable faulty // Gen manualy started","ludovic-a=
nselme.mouliom-mapoure@sagemcom","912","11-03-2025 11:37:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0004546718","Mballa 4=
","","11-03-2025 10:57:02","11-03-2025 10:44:15","11-03-2025 11:33:02","Cas=
caded Incident from TTO4612474","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage.gen failed to start due t=
o alarm ""overcurrent""//We reset card GE and gen manually started ","syste=
m","271205","11-03-2025 10:57:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0004546719","EMANA BI=
LICK CITY","","11-03-2025 10:57:02","11-03-2025 10:44:15","11-03-2025 11:33=
:02","Cascaded Incident from TTO4612474","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage.gen failed to s=
tart due to alarm ""overcurrent""//We reset card GE and gen manually starte=
d ","system","271206","11-03-2025 10:57:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0004546640","O=
kolo","IHS_YND_242, IHS_YND_523","11-03-2025 10:48:22","11-03-2025 10:44:15=
","11-03-2025 11:33:02","Grid outage.gen failed to start due to alarm ""ove=
rcurrent""//We reset card GE and gen manually started ","Fabrice Pouakam","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.=
gen failed to start due to alarm ""overcurrent""//We reset card GE and gen =
manually started ","mariam.tchonang@sagemcom.com","248","11-03-2025 10:48:2=
2","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0004546607","Mfou EPC=
","","11-03-2025 10:45:11","11-03-2025 10:22:03","11-03-2025 11:57:03","Cas=
caded Incident from TTO4612429","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because CB rectifier=
s tripped // CB put back on (investigation ongoing)","system","308633","11-=
03-2025 10:45:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0004546599","M=
fou OCM","IHS_YND_674","11-03-2025 10:43:16","11-03-2025 10:22:03","11-03-2=
025 11:57:03","Site went down because CB rectifiers tripped // CB put back =
on (investigation ongoing)","Mba Lazare Herve","Equipment Repair","Passive"=
,"Rectifier","Rectifier - Circuit Breaker","Site went down because CB recti=
fiers tripped // CB put back on (investigation ongoing)","ludovic-anselme.m=
ouliom-mapoure@sagemcom","1273","11-03-2025 10:43:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004546375","B=
ATA Mokolo OCM","","11-03-2025 10:18:26","11-03-2025 10:09:12","11-03-2025 =
11:57:32","Grid outage no space to deploye a mobil gen //grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge no space to deploye a mobil gen //grid return","mariam.tchonang@sagemcom=
.com","555","11-03-2025 10:18:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004546101","S=
hell-Nsimeyong","","11-03-2025 09:37:50","11-03-2025 09:33:38","11-03-2025 =
10:35:24","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","mariam.tchonang@sagemcom.com","253","11-03-2025 09:37:50","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004546048","Carrefou=
r Ayissi Ele","","11-03-2025 09:29:20","11-03-2025 09:04:48","11-03-2025 10=
:51:08","Cascaded Incident from TTO4611671","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down because 23 =
rectifier disfunctionning Felix BATEU is informed// He replaced these recti=
fiers  it by another","system","1472","11-03-2025 09:29:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004545927","S=
aa","IHS_YND_810","11-03-2025 09:08:50","11-03-2025 09:04:48","11-03-2025 1=
0:51:08","Site went down because 23 rectifier disfunctionning Felix BATEU i=
s informed// He replaced these rectifiers  it by another","Parker Tchoup","=
Equipment Repair","Passive","Rectifier","Rectifier Module","Site went down =
because 23 rectifier disfunctionning Felix BATEU is informed// He replaced =
these rectifiers  it by another","mariam.tchonang@sagemcom.com","243","11-0=
3-2025 09:08:50","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004545577","Elo=
umdem stade","","11-03-2025 08:05:56","11-03-2025 08:02:18","11-03-2025 08:=
16:48","Grid fluctuation, Site went down because Gen failed to start due to=
 Grid bad voltage and RCP on site // Grid stabilized","Fanda Brice","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid flu=
ctuation, Site went down because Gen failed to start due to Grid bad voltag=
e and RCP on site // Grid stabilized","ludovic-anselme.mouliom-mapoure@sage=
mcom","219","11-03-2025 08:05:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004545508","M=
efou-Assi","","11-03-2025 07:49:22","11-03-2025 07:46:05","11-03-2025 07:50=
:14","ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid.The =
Tx FME Fulbert (654266068) from Huawei is informed. Notice that we have rep=
etitive issue","Fanda Brice","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue on site GRI=
D , Ubaie=3D54.5V site On Grid.The Tx FME Fulbert (654266068) from Huawei i=
s informed. Notice that we have repetitive issue","mariam.tchonang@sagemcom=
.com","198","11-03-2025 07:49:22","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004545376","Bon=
djock","","11-03-2025 07:19:35","11-03-2025 07:14:26","11-03-2025 07:26:52"=
,"Grid outage, Site went down because Gen failed to start due to gen contac=
tor no excited // He excited gen contactor, site on gen","Fanda Brice","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, S=
ite went down because Gen failed to start due to gen contactor no excited /=
/ He excited gen contactor, site on gen","ludovic-anselme.mouliom-mapoure@s=
agemcom","311","11-03-2025 07:19:35","Sagemcom CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0004545274","Car=
refour Ayissi Ele","","11-03-2025 06:57:08","11-03-2025 06:49:53","11-03-20=
25 08:50:29","No power issue site on solar with U=3D49v Gregroire(652070658=
) from Huawei is informed ","Parker Tchoup","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on solar with U=3D49v Gregroire(652070658) from Huawei is informed ","ludo=
vic-anselme.mouliom-mapoure@sagemcom","436","11-03-2025 06:57:08","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004545265","Aka=
k-Nkozoa-MTN-IHS","","11-03-2025 06:54:35","11-03-2025 06:49:26","11-03-202=
5 06:59:47","Grid fluctuation, site went down because Gen started and stopp=
ed to start due to grid bad voltage// He bypassed the grid and started Gen =
manually","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Grid fluctuation, site went down because Gen sta=
rted and stopped to start due to grid bad voltage// He bypassed the grid an=
d started Gen manually","ludovic-anselme.mouliom-mapoure@sagemcom","310","1=
1-03-2025 06:54:35","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004545094","Mom=
","","11-03-2025 05:51:13","11-03-2025 05:43:07","11-03-2025 07:02:15","Gri=
d outage.gen ran until fuel shortage//Refuelng done","Fanda Brice","Fuel Ou=
tage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until fuel sh=
ortage//Refuelng done","wilfried.kameni@sagemcom.com","510","11-03-2025 05:=
51:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004544968","S=
hell-Nsimeyong","","11-03-2025 05:23:44","11-03-2025 05:17:31","11-03-2025 =
05:25:42","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed. Repetitive Issue","MINKA NICOL=
AS","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosi=
ah (674007438/699699694) from Huawei is informed. Repetitive Issue","danick=
.tchakouani@sagemcom.com","374","11-03-2025 05:23:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004544702","E=
kombitie","","11-03-2025 04:01:05","11-03-2025 03:34:41","11-03-2025 03:40:=
23","No power issue site on gen with U=3D54.5V site on Gen  THE TX Synphori=
en 691316854 of Huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue site on gen with U=3D54.5V site on Gen  THE TX Synphorien 691316854 o=
f Huawei is informed","danick.tchakouani@sagemcom.com","1585","11-03-2025 0=
4:01:05","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004544370","Nko=
ulou Carriere carrefourt","","11-03-2025 02:36:21","11-03-2025 02:33:30","1=
1-03-2025 06:41:46","Grid outage site went down due to 01/04 rectifiers ala=
rming on site //he reset","Mba Lazare Herve","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Grid outage site went down due to 01/04 rect=
ifiers alarming on site //he reset","wilfried.kameni@sagemcom.com","172","1=
1-03-2025 02:36:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004544330","E=
vodoula OCM","","11-03-2025 02:29:33","11-03-2025 02:24:14","11-03-2025 04:=
25:35","No power issue site and  with Ubaie=3D54.4  V site on Gen The  FME =
TX Mouamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue site and  with Ubaie=3D54.4  V site on Gen The=
  FME TX Mouamadou/658791013 //From Huawei is informed","danick.tchakouani@=
sagemcom.com","320","11-03-2025 02:29:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004543850","E=
kie-Elegance","","11-03-2025 01:05:49","11-03-2025 01:04:40","11-03-2025 01=
:41:40","Access Issue during the Night: Site went down because gen fails to=
 start due to grid bad voltage( Lack of 2 phase on site) // He did a bridge=
 with a good phase","Albran Byorel","Access Denial","Lease Or Legal","Landl=
ord Related Issues","Access Issue - Land Lord","Access Issue during the Nig=
ht: Site went down because gen fails to start due to grid bad voltage( Lack=
 of 2 phase on site) // He did a bridge with a good phase","danick.tchakoua=
ni@sagemcom.com","70","11-03-2025 01:05:49","Sagemcom CMR"
"Closed Complete","Warning","T0105","IHS_YND_321","NOCINC0004543415","Soa",=
"","10-03-2025 23:42:17","","","site alarming on grid outage//alarm cleared=
 with gen manually started","Siligap Boris","Warning","Warning","POWER","Wa=
rning - National Grid - Grid Outage Issue","site alarming on grid outage//a=
larm cleared with gen manually started","danick.tchakouani@sagemcom.com","1=
0157","10-03-2025 23:42:17","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004543216","Fla=
menco","","10-03-2025 23:10:27","10-03-2025 22:52:10","11-03-2025 00:51:20"=
,"Grid outage site went down because Gen failed to start // Grid power retu=
rn (investigation ongoing)","Mboua Thierry","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage site went down because Gen fai=
led to start // Grid power return (investigation ongoing)","wilfried.kameni=
@sagemcom.com","1098","10-03-2025 23:10:27","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004542830","Elo=
umdem stade","","10-03-2025 21:51:53","10-03-2025 21:41:46","10-03-2025 23:=
38:29","ite went down because Gen failed to start due to grid bad voltage N=
o Rcp// Grid power","Fanda Brice","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","ite went down because Gen failed to start =
due to grid bad voltage No Rcp// He bypassed the grid and started Gen manua=
lly","danick.tchakouani@sagemcom.com","608","10-03-2025 21:51:53","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004542507","Mon=
tee Jouvence","","10-03-2025 20:57:06","10-03-2025 20:52:59","10-03-2025 21=
:10:10","Site went down due to insufficiency of rectifiers SS IHS Felix ZAM=
BE confirmed // He reduced the load , site on grid","Hyemafo Gildas","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down due t=
o insufficiency of rectifiers SS IHS Felix ZAMBE confirmed // He reduced th=
e load , site on grid","yves.djomo@sagemcom.com","248","10-03-2025 20:57:06=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004542489","E=
kounou","","10-03-2025 20:52:43","10-03-2025 20:28:39","10-03-2025 21:48:54=
","Site went down because CB(125*125A) tripped in PWC who feeds equipments =
OCM due to Grid bad voltage// CB put back on ans site on Gen","Albran Byore=
l","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Br=
eaker Issue","Site went down because CB(125*125A) tripped in PWC who feeds =
equipments OCM due to Grid bad voltage// CB put back on ans site on Gen","y=
ves.djomo@sagemcom.com","1445","10-03-2025 20:52:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004542329","Odza Min=
kan IHS","","10-03-2025 20:35:44","10-03-2025 19:18:00","10-03-2025 20:34:5=
5","Cascaded Incident from TTO4606701","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation, site went dow=
n because Gen failed to start due to grid bad voltage No Rcp// He bypassed =
grid and started Gen manually","system","269168","10-03-2025 20:35:44","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004542328","Odza II =
OCM","","10-03-2025 20:35:44","10-03-2025 19:18:00","10-03-2025 20:34:55","=
Cascaded Incident from TTO4606701","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause Gen failed to start due to grid bad voltage No Rcp// He bypassed grid=
 and started Gen manually","system","269167","10-03-2025 20:35:44","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004542330","ODZA MIN=
KAN EDIBI ASSI","","10-03-2025 20:35:44","10-03-2025 19:18:00","10-03-2025 =
20:34:55","Cascaded Incident from TTO4606701","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site w=
ent down because Gen failed to start due to grid bad voltage No Rcp// He by=
passed grid and started Gen manually","system","269169","10-03-2025 20:35:4=
4","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004542326","MEHANDAN=
","","10-03-2025 20:35:43","10-03-2025 19:18:00","10-03-2025 20:34:55","Cas=
caded Incident from TTO4606701","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se Gen failed to start due to grid bad voltage No Rcp// He bypassed grid an=
d started Gen manually","system","269167","10-03-2025 20:35:43","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004542327","Mehanda =
1","","10-03-2025 20:35:43","10-03-2025 19:18:00","10-03-2025 20:34:55","Ca=
scaded Incident from TTO4606701","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuation, site went down beca=
use Gen failed to start due to grid bad voltage No Rcp// He bypassed grid a=
nd started Gen manually","system","269168","10-03-2025 20:35:43","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_328","NOCINC0004542325","Nsimalen=
 MTN","","10-03-2025 20:35:43","10-03-2025 19:18:00","10-03-2025 20:34:55",=
"Cascaded Incident from TTO4606701","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause Gen failed to start due to grid bad voltage No Rcp// He bypassed gri=
d and started Gen manually","system","269169","10-03-2025 20:35:43","Sagemc=
om CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004542023","NYO=
M 2 IHS","","10-03-2025 20:09:12","10-03-2025 20:04:04","10-03-2025 20:12:5=
0","Site went down because Gen failed to start due to Grid bad voltage // h=
e bypass the Grid and Gen manually started","Fabrice Pouakam","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Site went down=
 because Gen failed to start due to Grid bad voltage // he bypass the Grid =
and Gen manually started","yves.djomo@sagemcom.com","309","10-03-2025 20:09=
:12","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004542020","Elo=
umdem stade","","10-03-2025 20:08:10","10-03-2025 20:05:02","10-03-2025 21:=
03:41","Grid bad voltage, Site went down Because gen fails to start due to =
lack of 01 phase on site // He bypassed Grid and started Gen manualy","Fand=
a Brice","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid bad voltage, Site went down Because gen fails to start due to =
lack of 01 phase on site // He bypassed Grid and started Gen manualy","yves=
.djomo@sagemcom.com","189","10-03-2025 20:08:10","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004541717","Nko=
lnda","IHS_YND_328, IHS_YND_528, IHS_YND_746, IHS_YND_527, IHS_YND_715, IHS=
_YND_749","10-03-2025 19:25:05","10-03-2025 19:18:00","10-03-2025 20:34:55"=
,"Grid fluctuation, site went down because Gen failed to start due to grid =
bad voltage No Rcp// He bypassed grid and started Gen manually","Albran Byo=
rel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, site went down because Gen failed to start due to gri=
d bad voltage No Rcp// He bypassed grid and started Gen manually","yves.djo=
mo@sagemcom.com","427","10-03-2025 19:25:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004541680","K=
oweit City","","10-03-2025 19:19:22","10-03-2025 19:12:18","10-03-2025 19:3=
2:12","Grid fluctuation, Site went down because Gen failed to start due to =
Grid bad voltage and RCP on site // Grid stabilized","Albran Byorel","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation, Site went down because Gen failed to start due to Grid bad volta=
ge and RCP on site // Grid stabilized","yves.djomo@sagemcom.com","425","10-=
03-2025 19:19:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004541491","E=
kounou","","10-03-2025 19:03:40","10-03-2025 18:59:27","10-03-2025 19:17:53=
","Grid fluctuation, Site went down because Gen started and stopped due to =
Grid bad voltage// Grid stabilized","Albran Byorel","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site w=
ent down because Gen started and stopped due to Grid bad voltage// Grid sta=
bilized","danick.tchakouani@sagemcom.com","254","10-03-2025 19:03:40","Sage=
mcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004541297","Tou=
ring Club International","","10-03-2025 18:29:13","10-03-2025 18:20:02","10=
-03-2025 18:33:30","Grid outage, Site went down before Gen start due to poo=
r backup// Grid return","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Grid return","yves.djomo@sagemcom.com","552=
","10-03-2025 18:29:13","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004541285","Nko=
zoa","","10-03-2025 18:28:29","10-03-2025 18:25:21","10-03-2025 21:02:48","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load ","Fabrice Pouakam","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site=
 went down due to gen overload (20kva, 340A) SS HIS Felix bateu is informed=
 and confirmed// He reduced the load ","yves.djomo@sagemcom.com","190","10-=
03-2025 18:28:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004541149","A=
wae Ewonkan","","10-03-2025 18:08:17","10-03-2025 17:22:12","10-03-2025 19:=
01:09","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // =
He reduced the load","yves.djomo@sagemcom.com","2766","10-03-2025 18:08:17"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004540749","C=
ite-Verte","","10-03-2025 17:19:03","10-03-2025 17:00:57","10-03-2025 17:05=
:01","Active: no power issue, site is ongrid with Ubaie=3D53.6V, TX Fme Bri=
ce Tsague of huawei is informed. Notice that we have disjunction at BTS OCM=
","","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active: no power issue, site is ongrid with Ubaie=3D53.6V,=
 TX Fme Brice Tsague of huawei is informed. Notice that we have disjunction=
 at BTS OCM","danick.tchakouani@sagemcom.com","1087","10-03-2025 17:19:03",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004540556","EMA=
NA BILICK CITY","","10-03-2025 16:49:26","10-03-2025 16:47:18","10-03-2025 =
18:57:12","Site went down due to work: Our Technician Fabrice/SAGEMCOM/6571=
08613 working on site (replacement of ATS)// End of work","Fabrice Pouakam"=
,"Installation Activity","Passive","Planned Activity","Installation Activit=
y","Site went down due to work: Our Technician Fabrice/SAGEMCOM/657108613 w=
orking on site (replacement of ATS)// End of work","yves.djomo@sagemcom.com=
","130","10-03-2025 16:49:26","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0004540547","Evo=
doula MTN","","10-03-2025 16:47:52","10-03-2025 16:44:47","10-03-2025 18:42=
:19","Grid outage, site went down because gen start and stopped with Under =
voltage alarm //  he Reset the Gen card and gen started","TIENTCHEU NZETCHI=
EU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage, site went down because gen start and stopped with Under voltage =
alarm //  he Reset the Gen card and gen started","yves.djomo@sagemcom.com",=
"186","10-03-2025 16:47:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0004540526","Nkolanga=
a","","10-03-2025 16:44:21","10-03-2025 16:35:02","10-03-2025 17:53:18","Ca=
scaded Incident from TTO4605309","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // Refuelling done","system","285928","10-03=
-2025 16:44:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0004540525","Nkoulou =
Carriere carrefourt","","10-03-2025 16:44:20","10-03-2025 16:35:02","10-03-=
2025 17:53:18","Cascaded Incident from TTO4605309","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage, sit=
e went down because gen ran untill fuel shortage // Refuelling done","syste=
m","285927","10-03-2025 16:44:20","Sagemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0004540518","Aba=
ng","IHS_YND_794, IHS_YND_289","10-03-2025 16:43:11","10-03-2025 16:35:02",=
"10-03-2025 17:53:18","Grid outage, site went down because gen ran untill f=
uel shortage // Refuelling done","Mba Lazare Herve","Fuel Outage","Passive"=
,"Diesel","Diesel Outage","Grid outage, site went down because gen ran unti=
ll fuel shortage // Refuelling done","yves.djomo@sagemcom.com","490","10-03=
-2025 16:43:11","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004540483","Aka=
k-Nkozoa-MTN-IHS","","10-03-2025 16:32:47","10-03-2025 16:16:34","10-03-202=
5 17:42:17","Grid fluctuation, site went down because Gen started and stopp=
ed to start due to grid bad voltage// He bypassed the grid and started Gen =
manually","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Grid fluctuation, site went down because Gen sta=
rted and stopped to start due to grid bad voltage// He bypassed the grid an=
d started Gen manually","yves.djomo@sagemcom.com","975","10-03-2025 16:32:4=
7","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004540450","ELO=
UMDEM CARRIERE","","10-03-2025 16:26:56","10-03-2025 16:19:50","10-03-2025 =
16:47:49","Grid outage, Site went down because Gen failed to start due to R=
elay R2 48V Faulty// He bypassed it and started Gen manualy (Relay R2 to be=
 replaced)","Fanda Brice","Equipment Repair","Passive","Control Panel","Rel=
ay","Grid outage, Site went down because Gen failed to start due to Relay R=
2 48V Faulty// He bypassed it and started Gen manualy (Relay R2 to be repla=
ced)","danick.tchakouani@sagemcom.com","428","10-03-2025 16:26:56","Sagemco=
m CMR"
"Closed Complete","Warning","T3232","IHS_YND_767","NOCINC0004540400","ELOUM=
DEM CARRIERE","","10-03-2025 16:20:00","","","Grid outage, Site went on ala=
rm because Gen failed to start due to Relay R2 48V Faulty// He bypassed it =
and started Gen manualy (Relay R2 to be replaced)","Fanda Brice","Warning",=
"Warning","POWER","Warning - ATS-AMF Issue","Grid outage, Site went down be=
cause Gen failed to start due to Relay R2 48V Faulty// He bypassed it and s=
tarted Gen manualy (Relay R2 to be replaced)","yves.djomo@sagemcom.com","60=
4","10-03-2025 16:20:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004540228","Carrefou=
r Ayissi Ele","","10-03-2025 15:59:40","10-03-2025 15:55:10","10-03-2025 17=
:44:55","Cascaded Incident from TTO4604922","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down because 1/3=
 rectifier disfunctionning Felix BATEU is informed// He replaced it by anot=
her","system","270","10-03-2025 15:59:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004540175","S=
aa","IHS_YND_810","10-03-2025 15:55:19","10-03-2025 15:50:10","10-03-2025 1=
7:44:55","Site went down because 1/3 rectifier disfunctionning Felix BATEU =
is informed// He replaced it by another","Parker Tchoup","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down because 1/3 recti=
fier disfunctionning Felix BATEU is informed// He replaced it by another","=
danick.tchakouani@sagemcom.com","310","10-03-2025 15:55:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0004540165","E=
ntree Cite Verte","","10-03-2025 15:53:30","10-03-2025 15:34:24","10-03-202=
5 18:38:56","Active: no power issue, site is on grid with Ubaie=3D53V, TX F=
me Brice Tsague/654419973 of huawei is informed. Notice that we have disjun=
ction at BTS OCM","Paul BIBOUM","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, site is=
 on grid with Ubaie=3D53V, TX Fme Brice Tsague/654419973 of huawei is infor=
med. Notice that we have disjunction at BTS OCM","yves.djomo@sagemcom.com",=
"1148","10-03-2025 15:53:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004539926","C=
ite-Verte","","10-03-2025 15:28:38","10-03-2025 15:24:30","10-03-2025 15:48=
:25","Site went down due to work: SS IHS Bernard ATANGANA working on site /=
/ End of work","","Installation Activity","Passive","Planned Activity","Ins=
tallation Activity","Site went down due to work: SS IHS Bernard ATANGANA wo=
rking on site // End of work","danick.tchakouani@sagemcom.com","250","10-03=
-2025 15:28:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004539874","M=
ini-Ferme","","10-03-2025 15:22:03","10-03-2025 15:19:54","10-03-2025 17:51=
:58","Grid outage, No space to deploy MDG // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space=
 to deploy MDG // Grid return","danick.tchakouani@sagemcom.com","130","10-0=
3-2025 15:22:03","Sagemcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0004539671","Bar=
riere IHS","","10-03-2025 14:50:20","10-03-2025 14:44:09","10-03-2025 15:02=
:18","Site went down because Gen failed to start due to PWC dysfunctionning=
 IHS Supervisor Felix Zambe confirmed // He reduced the load ","Hyemafo Gil=
das","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded"=
,"Site went down because Gen failed to start due to PWC dysfunctionning IHS=
 Supervisor Felix Zambe confirmed // He reduced the load ","yves.djomo@sage=
mcom.com","372","10-03-2025 14:50:20","Sagemcom CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0004539236","Nko=
mo","","10-03-2025 14:13:44","10-03-2025 14:08:33","10-03-2025 14:14:47","G=
rid outage, site went down before Gen start due to poor battery backup // G=
en start automatically","Mba Lazare Herve","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen start due to poor battery backup // Gen start automatically","el-da=
lile@sagemcom.com","312","10-03-2025 14:13:44","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004539160","Nko=
g-Edzen","","10-03-2025 13:58:21","10-03-2025 13:33:48","10-03-2025 13:58:5=
2","Active// No power issue on site, Site on Grid FME TEUKEU Aubin/ 6944279=
63/From I-eng working (Swapp Mw)","Parker Tchoup","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No p=
ower issue on site, Site on Grid FME TEUKEU Aubin/ 694427963/From I-eng wor=
king (Swapp Mw)","vanessa.nen-ext@sagemcom.com","1630","10-03-2025 13:58:21=
","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004539147","Lab=
oratoire  Meka","","10-03-2025 13:56:06","10-03-2025 09:58:45","10-03-2025 =
16:19:02","Grid Outage//Grid Restored","","Grid Supply","Passive","Grid","N=
ational Grid - Grid Outage Issue","Grid Outage//Grid Restored","danick.tcha=
kouani@sagemcom.com","14242","10-03-2025 13:56:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004539095","S=
tade-Abega","","10-03-2025 13:47:45","10-03-2025 13:34:25","10-03-2025 14:1=
1:14","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // He reset the controller, grid return","Mba Lazare Herve",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gri=
d outage, site went down because gen failed to start due to PWC ZTE malfunc=
tion // He reset the controller, grid return","danick.tchakouani@sagemcom.c=
om","801","10-03-2025 13:47:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004539082","N=
koabang Ebolmedjock","","10-03-2025 13:46:35","10-03-2025 13:37:30","10-03-=
2025 13:37:31","Active// No power issue, site is on Gen with Ubaie=3D53,6V,=
 Lionel Adjep(655184876) from Huawei is informed. Notice that we have repet=
itive issue","Mba Lazare Herve","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","	Active// No power issue, site =
is on Gen with Ubaie=3D53,6V, Lionel Adjep(655184876) from Huawei is inform=
ed. Notice that we have repetitive issue","danick.tchakouani@sagemcom.com",=
"546","10-03-2025 13:46:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004539076","A=
wae Ewonkan","","10-03-2025 13:45:46","10-03-2025 13:34:39","10-03-2025 16:=
58:25","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // =
He reduced the load","danick.tchakouani@sagemcom.com","668","10-03-2025 13:=
45:46","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004539070","Fla=
menco","","10-03-2025 13:45:34","10-03-2025 11:39:58","10-03-2025 13:21:58"=
,"Grid outage, Site went down because Gen started and stopped due to High T=
emp // He open the Gate of the Gen and started Gen manualy","Mboua Thierry"=
,"Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, Site=
 went down because Gen started and stopped due to High Temp // He open the =
Gate of the Gen and started Gen manualy","vanessa.nen-ext@sagemcom.com","75=
37","10-03-2025 13:45:34","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004538985","Mel=
en Ba'aba","","10-03-2025 13:26:40","10-03-2025 13:21:32","10-03-2025 13:30=
:10","Active// No power issue, site is on GEN with Ubaie=3D50.5 V TX FME Ju=
lien(693095849) from Huawei is informed","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue, site is on GEN with Ubaie=3D50.5 V TX FME Julien(6930958=
49) from Huawei is informed","el-dalile@sagemcom.com","309","10-03-2025 13:=
26:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004538909","Saa","",=
"10-03-2025 13:15:31","10-03-2025 13:11:15","10-03-2025 14:31:57","Cascaded=
 Incident from TTO4603457","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Site went down because Gen sta=
rted and stopped with ""overcurrent"" alarm// He deconnected Aircon, reset =
gen card  and started gen manualy","system","256","10-03-2025 13:15:31","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004538902","SAA=
 2","IHS_YND_405","10-03-2025 13:14:46","10-03-2025 13:11:15","10-03-2025 1=
4:32:24","Grid outage, Site went down because Gen started and stopped with =
""overcurrent"" alarm// He deconnected Aircon, reset gen card  and started =
gen manualy","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG =
- Control Panel","Grid outage, Site went down because Gen started and stopp=
ed with ""overcurrent"" alarm// He deconnected Aircon, reset gen card  and =
started gen manualy","el-dalile@sagemcom.com","213","10-03-2025 13:14:46","=
Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004538761","AKA=
K Nkozoa","","10-03-2025 12:53:06","10-03-2025 12:29:56","10-03-2025 15:13:=
07","Grid outage site went down because Gen started and stopped with alarm =
Gen over current // He reset the Gen card and Gen manually started","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage site went down because Gen started and stopped with alarm Gen o=
ver current // He reset the Gen card and Gen manually started","danick.tcha=
kouani@sagemcom.com","1391","10-03-2025 12:53:06","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004538732","NKO=
MKANA ELIZA HOTEL","","10-03-2025 12:51:28","10-03-2025 12:26:21","10-03-20=
25 20:50:25","Grid outage, No space to deploy MDG // Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
No space to deploy MDG // Grid return","danick.tchakouani@sagemcom.com","15=
08","10-03-2025 12:51:28","Sagemcom CMR"
"Closed Complete","Warning","T0029","IHS_YND_357","NOCINC0004538338","Sacre=
 Coeur Catholic Church","","10-03-2025 11:58:29","","","Grid outage ,Site a=
larming because site on battery// Dg is started automatically	","Mboua Thie=
rry","Warning","Warning","POWER","Warning - Site on Battery","Grid outage ,=
Site alarming because site on battery// Dg is started automatically	","el-d=
alile@sagemcom.com","799","10-03-2025 11:58:29","Sagemcom CMR"
"Closed Complete","Site Down","T0123","IHS_YND_013","NOCINC0004538243","Lab=
oratoire T.Bella","","10-03-2025 11:39:46","10-03-2025 11:36:25","10-03-202=
5 12:04:25","Grid outage//MDG of 20 kva has deployed","Paul BIBOUM","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage//M=
DG of 20 kva has deployed","danick.tchakouani@sagemcom.com","202","10-03-20=
25 11:39:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0004538018","M=
adagascar-Yde-New","","10-03-2025 11:06:21","10-03-2025 10:58:12","11-03-20=
25 01:43:52","Grid outage,no space to deploy a mobile DG,// Grid power retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage,no space to deploy a mobile DG,// Grid power return","danick.tc=
hakouani@sagemcom.com","490","10-03-2025 11:06:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0004537925","B=
astos Ekoudou","","10-03-2025 10:53:25","10-03-2025 10:44:08","10-03-2025 1=
2:09:00","Grid outage.gen failed to start due to ""high temp"" alarm // We =
add water and gen manually started","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outa=
ge.gen failed to start due to ""high temp"" alarm // We add water and gen m=
anually started","danick.tchakouani@sagemcom.com","559","10-03-2025 10:53:2=
5","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0004537849","B=
ATA-Mokolo","","10-03-2025 10:39:10","10-03-2025 10:25:55","11-03-2025 01:4=
3:58","Grid outage,no space to deploy a mobile DG,// Grid power return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage,no space to deploy a mobile DG,// Grid power return","danick.tchakouan=
i@sagemcom.com","832","10-03-2025 10:39:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0004537822","H=
-Progres","","10-03-2025 10:31:31","10-03-2025 10:25:26","11-03-2025 01:40:=
49","Grid outage,no space to deploy a mobile DG,// Grid power return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge,no space to deploy a mobile DG,// Grid power return","danick.tchakouani@=
sagemcom.com","367","10-03-2025 10:31:31","Sagemcom CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0004537743","Mai=
son komkana New","","10-03-2025 10:13:52","10-03-2025 10:00:32","10-03-2025=
 11:14:46","Grid outage,gen failed to start due to no battery GE //Gen manu=
ally started with external battery","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Generator Battery","Grid outage,gen failed to star=
t due to no battery GE //Gen manually started with external battery","danic=
k.tchakouani@sagemcom.com","801","10-03-2025 10:13:52","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004537733","Fla=
menco","","10-03-2025 10:12:32","10-03-2025 10:05:26","10-03-2025 10:57:30"=
,"Grid outage,DG failed to start due to ACDG Control Panel Faulty //Manuall=
y start of DG","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Grid outage,DG failed to start due to ACDG Control Pane=
l Faulty //Manually start of DG","danick.tchakouani@sagemcom.com","427","10=
-03-2025 10:12:32","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004537723","Aka=
k-Nkozoa-MTN-IHS","","10-03-2025 10:11:43","10-03-2025 09:51:07","10-03-202=
5 11:04:39","Grid fluctuation, site went down because Gen started and stopp=
ed to start due to grid bad voltage// He bypassed the grid and started Gen =
manually","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Grid fluctuation, site went down because Gen sta=
rted and stopped to start due to grid bad voltage// He bypassed the grid an=
d started Gen manually","el-dalile@sagemcom.com","1238","10-03-2025 10:11:4=
3","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004537703","c=
hina embassy yde","","10-03-2025 10:08:15","10-03-2025 09:59:16","10-03-202=
5 13:47:42","Grid outage, No space to deploy MDG// Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No=
 space to deploy MDG// Grid return","danick.tchakouani@sagemcom.com","540",=
"10-03-2025 10:08:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004537678","Nkomkana=
 2","","10-03-2025 10:03:20","10-03-2025 09:50:58","10-03-2025 20:47:41","C=
ascaded Incident from TTO4601977","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, No space to deploy MDG/=
/ Grid return","system","310237","10-03-2025 10:03:20","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0004537648","Nko=
mkana","IHS_YND_138","10-03-2025 10:00:04","10-03-2025 09:50:58","10-03-202=
5 20:50:41","Grid outage, No space to deploy MDG// Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No=
 space to deploy MDG// Grid return","danick.tchakouani@sagemcom.com","550",=
"10-03-2025 10:00:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004537275","Nkomkana=
 2","","10-03-2025 08:56:20","10-03-2025 07:47:06","10-03-2025 08:49:06","C=
ascaded Incident from TTO4601182","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, No space to deploy MDG =
// Grid return","system","267380","10-03-2025 08:56:20","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004537255","Fla=
menco","","10-03-2025 08:54:59","10-03-2025 08:53:41","10-03-2025 08:54:41"=
,"Grid outage, site went down because gen failed to start due to gen card f=
aulty // Grid restored","Mboua Thierry","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid outage, site went down because gen failed=
 to start due to gen card faulty // Grid restored","danick.tchakouani@sagem=
com.com","79","10-03-2025 08:54:59","Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0004537231","Ang=
uissa New","","10-03-2025 08:48:49","10-03-2025 08:43:14","10-03-2025 10:29=
:42","Error","MINKA NICOLAS","Incorrectly Logged Tickets","Error","Error","=
Error","Error","danick.tchakouani@sagemcom.com","336","10-03-2025 08:48:49"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0526","IHS_YND_088","NOCINC0004537104","Elo=
bi Mokolo","","10-03-2025 08:23:35","10-03-2025 08:17:28","10-03-2025 09:02=
:28","Site went down because gen fails to start due to grid bad voltage // =
He bypass grid and manually start the gen","Mboua Thierry","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Site went down be=
cause gen fails to start due to grid bad voltage // He bypass grid and manu=
ally start the gen","danick.tchakouani@sagemcom.com","368","10-03-2025 08:2=
3:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004536966","c=
hina embassy yde","","10-03-2025 07:55:21","10-03-2025 07:49:15","10-03-202=
5 09:18:15","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage N=
o Space to deploy a MDG//Grid Restored","danick.tchakouani@sagemcom.com","3=
67","10-03-2025 07:55:21","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0004536956","Nko=
mkana","IHS_YND_138","10-03-2025 07:54:14","10-03-2025 07:47:06","10-03-202=
5 09:01:19","Grid outage, No space to deploy MDG // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MDG // Grid return","el-dalile@sagemcom.com","430","10-03=
-2025 07:54:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_131","NOCINC0004536849","Laborato=
ire  Meka","IHS_YND_193","10-03-2025 07:33:40","10-03-2025 07:29:44","10-03=
-2025 09:24:54","Grid Outage//Grid Restored","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid Outage//Grid Restored","syste=
m","236","10-03-2025 07:33:40","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0004536844","Bas=
tos Ekoudou","","10-03-2025 07:32:52","10-03-2025 07:29:44","10-03-2025 09:=
24:54","Grid Outage//Grid Restored","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage//Grid Restored","el-da=
lile@sagemcom.com","275846","10-03-2025 07:32:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004536569","Bondjock=
","","10-03-2025 06:30:30","10-03-2025 05:46:21","10-03-2025 06:15:21","Cas=
caded Incident from TTO4600724","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage.gen failed to start due to "=
"high temp"" alarm//We add water and gen manually started","system","274449=
","10-03-2025 06:30:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004536568","Minka","=
","10-03-2025 06:30:30","10-03-2025 05:46:21","10-03-2025 06:15:21","Cascad=
ed Incident from TTO4600724","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen failed to start due to ""hi=
gh temp"" alarm//We add water and gen manually started","system","274450","=
10-03-2025 06:30:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004536566","N=
komkana 2","","10-03-2025 06:27:46","10-03-2025 06:04:38","10-03-2025 07:31=
:38","Grid outage, gen failed to start due to Gen overload(17kva,200A) SS I=
HS BERNARD IS INFORMED // He reduce the load on site","Mboua Thierry","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, gen fail=
ed to start due to Gen overload(17kva,200A) SS IHS BERNARD IS INFORMED // H=
e reduce the load on site","cedric.tiani@sagemcom.com","1389","10-03-2025 0=
6:27:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004536558","M=
vog-Manga","","10-03-2025 06:24:37","10-03-2025 06:01:17","10-03-2025 07:03=
:33","Grid outage.Gen failed to start due alrm ""low oil pressure""//We add=
 oil and gen manually started","Albran Byorel","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Low Oil Pressure","Grid outage.Gen failed to start due =
alrm ""low oil pressure""//We add oil and gen manually started","cedric.tia=
ni@sagemcom.com","1957","10-03-2025 06:24:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004536554","M=
om","IHS_YND_371, IHS_YND_372","10-03-2025 06:23:31","10-03-2025 05:46:21",=
"10-03-2025 06:15:21","Grid outage.gen failed to start due to ""high temp""=
 alarm // We add water and gen manually started","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"Grid outage.gen failed to start due to ""high temp"" alarm//We add water =
and gen manually started","cedric.tiani@sagemcom.com","2232","10-03-2025 06=
:23:31","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004536312","Tou=
ring Club International","","10-03-2025 05:02:44","10-03-2025 04:53:17","10=
-03-2025 05:23:56","Grid Outage Site went down because Gen overload (20KVA,=
 270A) SS IHS Pascaline confirmed // He reduced the load and start the Gen =
Manually","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid Outage Site went down because Gen overload (20KVA, 270A) SS =
IHS Pascaline confirmed // He reduced the load and start the Gen Manually",=
"cedric.tiani@sagemcom.com","568","10-03-2025 05:02:44","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004536273","Fla=
menco","","10-03-2025 04:38:58","10-03-2025 04:34:48","10-03-2025 08:06:48"=
,"Access issue during the night, Grid outage site went down because Gen fai=
led to start due to Gen card faulty // Gen manually started","Mboua Thierry=
","Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue =
- Land Lord","Access issue during the night, Grid outage site went down bec=
ause Gen failed to start due to Gen card faulty // Gen manually started","c=
edric.tiani@sagemcom.com","251","10-03-2025 04:38:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004536149","Bondjock=
","","10-03-2025 04:01:01","10-03-2025 03:54:13","10-03-2025 04:43:47","Cas=
caded Incident from TTO4600225","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage.gen failed to start due to "=
"high temp"" alarm//We add water and gen manually started","system","274480=
","10-03-2025 04:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004536147","Mbeng","=
","10-03-2025 04:01:01","10-03-2025 03:54:13","10-03-2025 04:43:47","Cascad=
ed Incident from TTO4600225","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen failed to start due to ""hi=
gh temp"" alarm//We add water and gen manually started","system","274480","=
10-03-2025 04:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004536148","Minka","=
","10-03-2025 04:01:01","10-03-2025 03:54:13","10-03-2025 04:43:47","Cascad=
ed Incident from TTO4600225","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen failed to start due to ""hi=
gh temp"" alarm//We add water and gen manually started","system","274481","=
10-03-2025 04:01:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004536143","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_372","10-03-2025 03:59:25","10-03-20=
25 03:54:13","10-03-2025 04:43:47","Grid outage.gen failed to start due to =
""high temp"" alarm//We add water and gen manually started","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage.gen failed to start due to ""high temp"" alarm//We=
 add water and gen manually started","cedric.tiani@sagemcom.com","314","10-=
03-2025 03:59:25","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004536140","SAA=
 2","","10-03-2025 03:57:12","10-03-2025 03:06:03","10-03-2025 05:02:31","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed Manually","Parker Tchoup","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup // Gen started Manually","cedric.tiani@sagemcom.com","30=
70","10-03-2025 03:57:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004536039","K=
oweit City","","10-03-2025 03:34:59","10-03-2025 02:59:45","10-03-2025 04:2=
5:10","Grid outage, Site went down because Gen ran until fuel shortage// Re=
fueling Done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, Site went down because Gen ran until fuel shortage// Refu=
eling Done","cedric.tiani@sagemcom.com","2115","10-03-2025 03:34:59","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004535940","O=
lembe-Terminus","","10-03-2025 03:05:22","10-03-2025 02:14:06","10-03-2025 =
03:23:06","	Grid outage, site went down because gen start and stopped with =
alarm overcurrent // He reset gen card and gen manually started","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","	Gr=
id outage, site went down because gen start and stopped with alarm overcurr=
ent // He reset gen card and gen manually started","cedric.tiani@sagemcom.c=
om","3078","10-03-2025 03:05:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004535931","Minka","=
","10-03-2025 02:58:31","10-03-2025 01:36:39","10-03-2025 02:24:19","Cascad=
ed Incident from TTO4599917","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen failed to start due to ""hi=
gh temp"" alarm//We add water and gen manually started","system","268078","=
10-03-2025 02:58:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004535930","Mbeng","=
","10-03-2025 02:58:31","10-03-2025 01:36:39","10-03-2025 02:24:19","Cascad=
ed Incident from TTO4599917","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage.gen failed to start due to ""hi=
gh temp"" alarm//We add water and gen manually started","system","268079","=
10-03-2025 02:58:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004535892","Bondjock=
","","10-03-2025 02:43:10","10-03-2025 01:36:39","10-03-2025 02:24:19","Cas=
caded Incident from TTO4599917","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage.gen failed to start due to "=
"high temp"" alarm//We add water and gen manually started","system","268078=
","10-03-2025 02:43:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004535885","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_372","10-03-2025 02:39:03","10-03-20=
25 01:36:39","10-03-2025 02:24:37","Grid outage.gen failed to start due to =
""high temp"" alarm//We add water and gen manually started","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage.gen failed to start due to ""high temp"" alarm//We=
 add water and gen manually started","cedric.tiani@sagemcom.com","3745","10=
-03-2025 02:39:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004535830","Bondjock=
","","10-03-2025 02:19:03","09-03-2025 21:35:49","09-03-2025 22:04:46","Cas=
caded Incident from TTO4598517","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
failed to start // Grid return","system","282288","10-03-2025 02:19:03","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004535762","Ngouetou=
","","10-03-2025 01:59:31","10-03-2025 01:30:32","10-03-2025 02:30:32","Cas=
caded Incident from TTO4599733","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen, Hybrid system malfunction =
// Hybrid module reset and Gen started","system","268272","10-03-2025 01:59=
:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004535763","MBIMBIM"=
,"","10-03-2025 01:59:31","10-03-2025 01:30:32","10-03-2025 02:30:32","Casc=
aded Incident from TTO4599733","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid Gen, Hybrid system malfunction /=
/ Hybrid module reset and Gen started","system","268270","10-03-2025 01:59:=
31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004535760","Matsari"=
,"","10-03-2025 01:59:30","10-03-2025 01:30:32","10-03-2025 02:30:32","Casc=
aded Incident from TTO4599733","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid Gen, Hybrid system malfunction /=
/ Hybrid module reset and Gen started","system","268271","10-03-2025 01:59:=
30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0004535761","Yoko OCM=
","","10-03-2025 01:59:30","10-03-2025 01:30:32","10-03-2025 02:30:32","Cas=
caded Incident from TTO4599733","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen, Hybrid system malfunction =
// Hybrid module reset and Gen started","system","268270","10-03-2025 01:59=
:30","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004535698","Eko=
umdoum OCM","","10-03-2025 01:41:20","10-03-2025 01:36:07","10-03-2025 02:2=
3:13","Grid outage, site went down due to  Gen overload(20kva,280 A) IHS SS=
 Pascaline is informed and confirmed// Grid return","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went =
down due to  Gen overload(20kva,280 A) IHS SS Pascaline is informed and con=
firmed// Grid return","ferot.nongni-djiogap@sagemcom.com","468","10-03-2025=
 01:41:20","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004535692","Ole=
mbe MTN","","10-03-2025 01:40:02","10-03-2025 01:32:53","10-03-2025 02:31:2=
4","Grid outage, site alarm because gen failed to start due to grid contact=
or faulty // He bypassed Grid contactor and started Gen manualy","Fabrice P=
ouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid =
outage, site alarm because gen failed to start due to grid contactor faulty=
 // He bypassed Grid contactor and started Gen manualy","ferot.nongni-djiog=
ap@sagemcom.com","430","10-03-2025 01:40:02","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004535672","NKO=
MEKUI OCM","","10-03-2025 01:31:34","10-03-2025 01:25:24","10-03-2025 05:55=
:57","Grid outage.gen failed to start due to ""high temp"" alarm // We add =
water and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","DCGG Gen","DCGG - High Engine Temp - Clogged Radiator","ajout=
 d'eau ","cedric.tiani@sagemcom.com","372","10-03-2025 01:31:34","Sagemcom =
CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004535623","Nko=
zoa","","10-03-2025 01:07:20","10-03-2025 01:00:45","10-03-2025 02:03:48","=
	Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix=
 bateu is informed and confirmed// He reduced the load and site on GEN","Fa=
brice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","	=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and site on GEN","ced=
ric.tiani@sagemcom.com","695","10-03-2025 01:07:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004535578","Bitoto",=
"","10-03-2025 00:50:41","10-03-2025 00:39:39","10-03-2025 01:30:23","Casca=
ded Incident from TTO4599514","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down because G=
en failed to start due to PWC dysfunctionning // grid return","system","122=
0962","10-03-2025 00:50:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004535579","Tradex-N=
komo","","10-03-2025 00:50:41","10-03-2025 00:39:39","10-03-2025 01:30:23",=
"Cascaded Incident from TTO4599514","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen failed to start due to PWC dysfunctionning // grid return","system","=
1220961","10-03-2025 00:50:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004535554","B=
iteng","IHS_YND_292, IHS_YND_172","10-03-2025 00:46:49","10-03-2025 00:39:3=
9","10-03-2025 01:30:23","Grid outage, Site went down because Gen failed to=
 start due to PWC dysfunctionning // grid return","Mba Lazare Herve","Equip=
ment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outa=
ge, Site went down because Gen failed to start due to PWC dysfunctionning /=
/ grid return","ferot.nongni-djiogap@sagemcom.com","431","10-03-2025 00:46:=
49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004535482","E=
koumdoum","","10-03-2025 00:25:13","09-03-2025 23:59:55","10-03-2025 00:58:=
53","Grid outage, Site went down because Gen fails to start due to  Battery=
 gen discharged // Gen start with battery back up (investigation ongoing)",=
"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator B=
attery","Grid outage, Site went down because Gen fails to start due to  Bat=
tery gen discharged // Gen start with battery back up (investigation ongoin=
g)","cedric.tiani@sagemcom.com","1519","10-03-2025 00:25:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004535467","A=
wae Ewonkan","","10-03-2025 00:18:22","09-03-2025 23:48:38","10-03-2025 01:=
32:54","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // =
He reduced the load","kouoh.jean@ihstowers.com","1785","10-03-2025 00:18:22=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004535432","E=
vodoula OCM","","10-03-2025 00:10:04","09-03-2025 23:59:45","10-03-2025 01:=
10:48","No power issue site and  with Ubaie=3D54.4  V site on Gen The  FME =
TX Mouamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue site and  with Ubaie=3D54.4  V site on Gen The=
  FME TX Mouamadou/658791013 //From Huawei is informed","cedric.tiani@sagem=
com.com","620","10-03-2025 00:10:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004535418","A=
kak-Nkozoa-MTN-IHS","","10-03-2025 00:06:58","09-03-2025 23:57:44","10-03-2=
025 01:37:31","Grid fluctuation, site went down because Gen started and sto=
pped to start due to grid bad voltage// He bypassed the grid and started Ge=
n manually","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid=
 - Phase Controller Faulty","Grid fluctuation, site went down because Gen s=
tarted and stopped to start due to grid bad voltage// He bypassed the grid =
and started Gen manually","cedric.tiani@sagemcom.com","556","10-03-2025 00:=
06:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004535414","O=
lembe-Terminus","","10-03-2025 00:05:24","09-03-2025 23:57:02","10-03-2025 =
01:12:53","	Grid outage, site went down because gen start and stopped with =
alarm overcurrent // He reset gen card and gen manually started","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","	Gr=
id outage, site went down because gen start and stopped with alarm overcurr=
ent // He reset gen card and gen manually started","cedric.tiani@sagemcom.c=
om","504","10-03-2025 00:05:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004535409","C=
rf-Nsam","","10-03-2025 00:05:15","09-03-2025 23:39:59","10-03-2025 01:29:3=
0","Site went down Because The Slot off Rectifier is overload // Grid retur=
n SS Ihs Pascaline is informed and is confirmed","MINKA NICOLAS","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went dow=
n Because The Slot off Rectifier is overload // Grid return SS Ihs Pascalin=
e is informed and is confirmed","kouoh.jean@ihstowers.com","1517","10-03-20=
25 00:05:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004535397","S=
AA 2","","10-03-2025 00:00:49","09-03-2025 23:54:31","10-03-2025 01:00:57",=
"Grid outage site went down because Gen Started and Stop due to ALARMS Over=
-Current //He Reset the Gen Card and Manually Started It","Parker Tchoup","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage =
site went down because Gen Started and Stop due to ALARMS Over-Current //He=
 Reset the Gen Card and Manually Started It","cedric.tiani@sagemcom.com","3=
79","10-03-2025 00:00:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004535322","S=
tade-Abega","","09-03-2025 23:51:42","09-03-2025 23:49:34","10-03-2025 01:3=
0:41","Grid outage, site went down Gen failed to start due to PWC ZTE malfu=
nction // He reset it and started Gen manualy","Mba Lazare Herve","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage,=
 site went down Gen failed to start due to PWC ZTE malfunction // He reset =
it and started Gen manualy","cedric.tiani@sagemcom.com","129","09-03-2025 2=
3:51:42","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004535317","AWA=
E OCM","","09-03-2025 23:50:44","09-03-2025 23:41:02","10-03-2025 01:40:59"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automatically","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automatically","cedric.tiani@sag=
emcom.com","584","09-03-2025 23:50:44","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004535296","Nko=
lnda","","09-03-2025 23:46:51","09-03-2025 23:43:36","10-03-2025 00:34:10",=
"Grid outage, Site went down before gen start due to poor battery backup //=
 Gen automatically started.leading to disjunction at ocm equipment","Albran=
 Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","Grid outage, Site went down before gen start due to poor battery =
backup // Gen automatically started.leading to disjunction at ocm equipment=
","cedric.tiani@sagemcom.com","196","09-03-2025 23:46:51","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004535291","Bit=
eng-Maetur","","09-03-2025 23:46:00","09-03-2025 23:41:09","10-03-2025 01:5=
7:29","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the l=
oad","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, Site went down because Gen started and stopped due to =
Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// He reduced the =
load","cedric.tiani@sagemcom.com","10372","09-03-2025 23:46:00","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004535282","M=
ontee-Des-Soeurs","","09-03-2025 23:43:23","09-03-2025 23:39:12","09-03-202=
5 23:39:15","No power Issue Site on Grid Ubai =3D54.3 V. The TX FME Mbah Ho=
siah (674007438) is informed","Hyemafo Gildas","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power Issue S=
ite on Grid Ubai =3D54.3 V. The TX FME Mbah Hosiah (674007438) is informed"=
,"cedric.tiani@sagemcom.com","252","09-03-2025 23:43:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004535264","A=
wae Escalier","","09-03-2025 23:42:04","09-03-2025 23:39:42","10-03-2025 01=
:29:59","Grid fluctuation,site went dowwn because Gen failed to start due t=
o Grid bad voltage//He bypassed the Grid and sarted gen manaully","Albran B=
yorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation,site went dowwn because Gen failed to start due to G=
rid bad voltage//He bypassed the Grid and sarted gen manaully","cedric.tian=
i@sagemcom.com","143","09-03-2025 23:42:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004535173","N=
kolfon Cimencam","","09-03-2025 23:18:33","09-03-2025 22:58:10","09-03-2025=
 23:10:59","Active//No power issue, Site on Grid. Notice that it is impacte=
d by Afanoya II The Tx FME Fulbert from Huawei is informed","Hyemafo Gildas=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","Active//No power issue, Site on Grid. Notice that it is impac=
ted by Afanoya II The Tx FME Fulbert from Huawei is informed","cedric.tiani=
@sagemcom.com","1224","09-03-2025 23:18:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004535121","N=
YOM 2 IHS","","09-03-2025 23:10:36","09-03-2025 19:38:52","09-03-2025 19:45=
:46","BACK TRACKING  Active//No power issue on site Ubaie=3D54.8 V site on =
Grid ,TX FME Synphorien (691316854) from Huawei is informed","Fabrice Pouak=
am","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue on site Ubaie=3D54.8 V site on Grid =
,TX FME Synphorien (691316854) from Huawei is informed","cedric.tiani@sagem=
com.com","12705","09-03-2025 23:10:36","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004535043","AKA=
K Nkozoa","","09-03-2025 22:54:41","09-03-2025 22:05:33","09-03-2025 23:14:=
59","Grid fluctuation, site went down because Gen started and stopped to st=
art due to grid bad voltage // He bypassed the grid and started Gen manuall=
y","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid fluctuation, site went down because Gen started an=
d stopped to start due to grid bad voltage // He bypassed the grid and star=
ted Gen manually","el-dalile@sagemcom.com","2949","09-03-2025 22:54:41","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004534730","Mbeng","=
","09-03-2025 21:55:31","09-03-2025 21:35:49","09-03-2025 22:04:46","Cascad=
ed Incident from TTO4598517","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen fai=
led to start // Grid return","system","282287","09-03-2025 21:55:31","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004534731","Minka","=
","09-03-2025 21:55:31","09-03-2025 21:35:49","09-03-2025 22:04:46","Cascad=
ed Incident from TTO4598517","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen fai=
led to start // Grid return","system","282287","09-03-2025 21:55:31","Sagem=
com CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004534644","Mom=
","IHS_YND_369, IHS_YND_371, IHS_YND_372","09-03-2025 21:42:58","09-03-2025=
 21:35:49","09-03-2025 22:04:57","Grid outage, site went down because gen f=
ailed to start(investigation on going)  // Grid return","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, sit=
e went down because gen failed to start(investigation on going)  // Grid re=
turn","wilfried.kameni@sagemcom.com","430","09-03-2025 21:42:58","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0004534517","B=
ONAS YDE","","09-03-2025 21:19:25","09-03-2025 21:04:21","09-03-2025 23:37:=
21","Site went down due to disjunction of Cb(125A) in PWC // He reamedCb(12=
5A)","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Circuit Breaker Issue","Site went down due to disjunction of Cb(125A)=
 in PWC // He reamedCb(125A)","wilfried.kameni@sagemcom.com","905","09-03-2=
025 21:19:25","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004534313","Nko=
ulou Carriere carrefourt","","09-03-2025 20:56:13","09-03-2025 20:09:56","1=
0-03-2025 09:26:56","Access issue during the night, Site went down due to 2=
/4 Rectifiers Dysfunctionning // He reset it: Site on grid","Mba Lazare Her=
ve","Access Denial","Lease Or Legal","Landlord Related Issues","Access Issu=
e - Land Lord","Access issue during the night, Site went down due to 2/4 Re=
ctifiers Dysfunctionning // He reset it: Site on grid","wilfried.kameni@sag=
emcom.com","2778","09-03-2025 20:56:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004534273","M=
arche Odza","","09-03-2025 20:51:40","09-03-2025 20:25:14","09-03-2025 21:1=
8:13","Gri outage, site went down due to Cb(63AA) of rectifiers in PWC malf=
unction // He reset Cb(63A) , site on gen","Albran Byorel","Equipment Repai=
r","Passive","Rectifier","Rectifier - Circuit Breaker","Gri outage, site we=
nt down due to Cb(63AA) of rectifiers in PWC malfunction // He reset Cb(63A=
) , site on gen","yves.djomo@sagemcom.com","1587","09-03-2025 20:51:40","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004534179","E=
kie-Elegance","IHS_YND_159","09-03-2025 20:26:10","09-03-2025 19:39:03","09=
-03-2025 21:00:03","Site on gen due to grid outage, site went down because =
gen stopped by landlord // Gen manuallystarted (investigation ongoing)","Al=
bran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop=
","Site on gen due to grid outage, site went down because gen stopped by la=
ndlord // Gen manuallystarted (investigation ongoing)","wilfried.kameni@sag=
emcom.com","2828","09-03-2025 20:26:10","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004533977","CRH=
-Etoug-Ebe","","09-03-2025 20:03:06","09-03-2025 19:55:56","09-03-2025 20:1=
1:01","Grid outage, Site went down before Gen start due to poor backup // G=
en started automatically","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup // Gen started automatically","wilfried.ka=
meni@sagemcom.com","431","09-03-2025 20:03:06","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004533968","Nko=
lnda","","09-03-2025 20:01:47","09-03-2025 19:48:28","09-03-2025 21:40:18",=
"Site went down because the Cb(125A) of PWC dysjuncted due load // He reame=
d","Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Circuit Breaker Issue","Site went down because the Cb(125A) of PWC dy=
sjuncted due load // He reamed","wilfried.kameni@sagemcom.com","800","09-03=
-2025 20:01:47","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004533883","Ona=
ngondi (melen bikop)","","09-03-2025 19:47:45","09-03-2025 19:05:39","09-03=
-2025 20:55:20","Site went down because Gen fails to start due to hybrid sy=
stem malfunctionning//He RESET THE hybrid system and Gen manually started",=
"Fanda Brice","Equipment Repair","Passive","Hybrid","Hybrid Module","Site w=
ent down because Gen fails to start due to hybrid system malfunctionning//H=
e RESET THE hybrid system and Gen manually started","yves.djomo@sagemcom.co=
m","2527","09-03-2025 19:47:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004533863","C=
omplexe-BEAC","","09-03-2025 19:43:24","09-03-2025 19:39:03","09-03-2025 21=
:00:03","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Site on gen due to grid outage, site went down because gen =
stopped by landlord // Gen manuallystarted (investigation ongoing)","yves.d=
jomo@sagemcom.com","304295","09-03-2025 19:43:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004533238","E=
ssomba","","09-03-2025 18:34:58","09-03-2025 15:29:51","09-03-2025 15:35:49=
","Active: No power issue, site is on Grid with Ubaie=3D54.1V,  The fme tx =
George //697461814//from Huawei is informed. Notice Dysjunction at the BTS =
OCM","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active: No power issue, site is on Grid=
 with Ubaie=3D54.1V,  The fme tx George //697461814//from Huawei is informe=
d. Notice Dysjunction at the BTS OCM","wilfried.kameni@sagemcom.com","11109=
","09-03-2025 18:34:58","Sagemcom CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0004533211","Ese=
ka Town","","09-03-2025 18:29:23","09-03-2025 18:20:07","09-03-2025 19:32:1=
4","Grid outage.gen failed to start due to ""high temp"" alarm//We add wate=
r and gen manually started","Kemeni Franklin","Equipment Repair","Passive",=
"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.gen=
 failed to start due to ""high temp"" alarm//We add water and gen manually =
started","wilfried.kameni@sagemcom.com","556","09-03-2025 18:29:23","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004532678","O=
bobogo","","09-03-2025 17:08:07","09-03-2025 16:40:45","09-03-2025 16:50:17=
","Active// No power issue site on grid with Ubai1=3D54.9V, Ubai2=3D53.5V S=
ite on Gen The TX Fme Hosiah / 674007438// from huawei is informed by sms",=
"MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active// No power issue site on grid with Ubai1=
=3D54.9V, Ubai2=3D53.5V Site on Gen The TX Fme Hosiah / 674007438// from hu=
awei is informed by sms","wilfried.kameni@sagemcom.com","1643","09-03-2025 =
17:08:07","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004532590","Eko=
mbitie","","09-03-2025 16:59:20","09-03-2025 16:02:12","09-03-2025 17:45:10=
","site went down because Gen started and stopped to start due to grid bad =
voltage and Rcp// He bypassed the grid and started Gen manually","Fabrice P=
ouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","site went down because Gen started and stopped to start due to grid =
bad voltage and Rcp// He bypassed the grid and started Gen manually","wilfr=
ied.kameni@sagemcom.com","3430","09-03-2025 16:59:20","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004532574","Mon=
tee Jouvence","","09-03-2025 16:58:03","09-03-2025 16:38:45","09-03-2025 16=
:56:20","Site went down due to insufficiency of rectifiers // He reduced th=
e load , site on grid","Hyemafo Gildas","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down due to insufficiency of rectifiers=
 // He reduced the load , site on grid","wilfried.kameni@sagemcom.com","115=
8","09-03-2025 16:58:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_508","NOCINC0004532467","Crf-Nsam=
","","09-03-2025 16:41:00","09-03-2025 16:33:47","09-03-2025 18:36:47","","=
MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Site went down because PWC(24kilo) dysfunctionning, IHS SS Pasc=
aline confirmed // He reset PWC","system","433","09-03-2025 16:41:00","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004532464","E=
foulan","","09-03-2025 16:40:02","09-03-2025 16:33:47","09-03-2025 17:21:47=
","Grid outage, site went down before gen start due to poor battery backup =
 // Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup  // Gen start automatically","wi=
lfried.kameni@sagemcom.com","376","09-03-2025 16:40:02","Sagemcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0004532213","Bar=
riere IHS","","09-03-2025 16:03:19","09-03-2025 15:55:04","09-03-2025 17:54=
:46","Grid outage, Site went down because Gen failed to start due to PWC dy=
sfunctionning IHS Supervisor Felix Zambe confirmed // He reduced the load a=
nd Gen manually started","Hyemafo Gildas","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","Grid outage, Site went down because =
Gen failed to start due to PWC dysfunctionning IHS Supervisor Felix Zambe c=
onfirmed // He reduced the load and Gen manually started","wilfried.kameni@=
sagemcom.com","496","09-03-2025 16:03:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004531942","B=
iteng-Maetur","","09-03-2025 15:28:58","09-03-2025 15:19:54","09-03-2025 15=
:25:56","No power issue on site U=3D53.3 V site on Grid The FME TX Lionel A=
djep (694693436) of Huawei is informed","Mba Lazare Herve","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site U=3D53.3 V site on Grid The FME TX Lionel Adjep (6946934=
36) of Huawei is informed","wilfried.kameni@sagemcom.com","545","09-03-2025=
 15:28:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004531751","M=
EHANDAN","","09-03-2025 15:02:37","09-03-2025 14:57:17","09-03-2025 16:13:3=
8","Site went down due to insufficiency of rectifiers on site SS IHS Pascal=
ine is confirm, Francois IHS // He reduced the load","Albran Byorel","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down due t=
o insufficiency of rectifiers on site SS IHS Pascaline is confirm, Francois=
 IHS // He reduced the load","wilfried.kameni@sagemcom.com","321","09-03-20=
25 15:02:37","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004531626","Bon=
djock","","09-03-2025 14:43:49","09-03-2025 14:37:37","09-03-2025 16:22:48"=
,"Grid outage, site went down because gen failed to start // Grid return (i=
nvestigation ongoing)","Fanda Brice","Equipment Repair","Passive","ACDG Gen=
","ACDG - Control Panel","Grid outage, site went down because gen failed to=
 start // Grid return (investigation ongoing)","wilfried.kameni@sagemcom.co=
m","373","09-03-2025 14:43:49","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004531575","Nko=
lnda","","09-03-2025 14:33:23","09-03-2025 14:28:15","09-03-2025 15:25:11",=
"Grid outage, Site went down before gen start due to poor battery backup //=
 Gen automatically started.leading to disjunction at ocm equipment","Albran=
 Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","Grid outage, Site went down before gen start due to poor battery =
backup // Gen automatically started.leading to disjunction at ocm equipment=
","yves.djomo@sagemcom.com","308","09-03-2025 14:33:23","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004531547","Aka=
k-Nkozoa-MTN-IHS","","09-03-2025 14:29:47","09-03-2025 14:25:42","09-03-202=
5 14:34:33","Grid fluctuation,Site went down because GEN failed to start du=
e to grid bad voltage(lack of 01 phase)// He did a bridge on the good phase=
","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation,Site went down because GEN failed to st=
art due to grid bad voltage(lack of 01 phase)// He did a bridge on the good=
 phase","yves.djomo@sagemcom.com","247","09-03-2025 14:29:47","Sagemcom CMR=
"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004531261","Nko=
lnda","","09-03-2025 13:48:30","09-03-2025 13:46:20","09-03-2025 13:49:56",=
"Grid outage, Site went down before Gen start due to poor backup // Grid re=
turn","Albran Byorel","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, Site went down before Gen start due to =
poor backup // Grid return","el-dalile@sagemcom.com","131","09-03-2025 13:4=
8:30","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004531213","Awa=
e Escalier","","09-03-2025 13:38:11","09-03-2025 13:23:55","09-03-2025 14:1=
9:59","Grid outage, Site went down before gen start due to poor battery bac=
kup // Gen started Manually","Albran Byorel","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down b=
efore gen start due to poor battery backup // Gen started Manually","el-dal=
ile@sagemcom.com","857","09-03-2025 13:38:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004531190","C=
omplexe-BEAC","","09-03-2025 13:33:44","09-03-2025 13:29:36","09-03-2025 14=
:01:59","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started automaticaly","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup // Gen started automaticaly","el-dalile@sa=
gemcom.com","249","09-03-2025 13:33:44","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004531180","ODZ=
A CITE MBIA","","09-03-2025 13:32:22","09-03-2025 13:30:11","09-03-2025 14:=
35:07","Site went down because the Cb(125A) of PWC dysjuncted due to load i=
ncreased // He reamed the CB","Albran Byorel","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down bec=
ause the Cb(125A) of PWC dysjuncted due to load increased // He reamed the =
CB","el-dalile@sagemcom.com","132","09-03-2025 13:32:22","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004531128","Eko=
mbitie","","09-03-2025 13:24:33","09-03-2025 13:20:22","09-03-2025 14:39:55=
","Grid fluctuation, site went down because Gen started and stopped to star=
t due to grid bad voltage and  Rcp// He bypassed the grid and started Gen m=
anually","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","Grid fluctuation, site went down because Gen star=
ted and stopped to start due to grid bad voltage and  Rcp// He bypassed the=
 grid and started Gen manually","el-dalile@sagemcom.com","252","09-03-2025 =
13:24:33","Sagemcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0004531079","Bar=
riere IHS","","09-03-2025 13:16:10","09-03-2025 13:14:05","09-03-2025 14:32=
:11","Grid outage, Site went down because Gen failed to start due to PWC dy=
sfunctionning IHS Supervisor Felix Zambe confirmed // grid return","Hyemafo=
 Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Grid outage, Site went down because Gen failed to start due to PWC dy=
sfunctionning IHS Supervisor Felix Zambe confirmed // grid return","yves.dj=
omo@sagemcom.com","126","09-03-2025 13:16:10","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004531018","Nko=
lnda","","09-03-2025 13:03:06","09-03-2025 12:59:59","09-03-2025 13:05:49",=
"Grid outage, Site went down before gen start due to poor battery backup //=
 Grid return","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before gen start=
 due to poor battery backup // Grid return","yves.djomo@sagemcom.com","187"=
,"09-03-2025 13:03:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004531013","M=
ontee-Des-Soeurs","","09-03-2025 13:02:31","09-03-2025 12:55:26","09-03-202=
5 13:02:56","Grid outage, Site went down before gen start due to poor batte=
ry backup // Grid return","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore gen start due to poor battery backup // Grid return","yves.djomo@sagemc=
om.com","427","09-03-2025 13:02:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004530976","A=
wae Ewonkan","","09-03-2025 12:57:26","09-03-2025 12:53:13","09-03-2025 13:=
25:05","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO confirmed// Grid return","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becaus=
e Gen overload(20KVA,310A) SS IHS Alphonse DEFFO confirmed// Grid return","=
el-dalile@sagemcom.com","254","09-03-2025 12:57:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004530925","MONTEE N=
KONDENGUI","","09-03-2025 12:47:50","09-03-2025 12:42:50","09-03-2025 12:45=
:53","Cascaded Incident from TTO4594021","Albran Byorel","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site , site on=
 Grid  with Ubaie=3D54.5 V.The Tx FME  Eloundou  //693212405 of Huawei is i=
nformed","system","286013","09-03-2025 12:47:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004530914","M=
obil-Kondengui","IHS_YND_682","09-03-2025 12:46:57","09-03-2025 12:42:50","=
09-03-2025 19:00:53","No power issue on site , site on Grid  with Ubaie=3D5=
4.5 V.The Tx FME  Eloundou  //693212405 of Huawei is informed","","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site , site on Grid  with Ubaie=3D54.5 V.The Tx FME  E=
loundou  //693212405 of Huawei is informed","el-dalile@sagemcom.com","248",=
"09-03-2025 12:46:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004530906","S=
tade-Abega","","09-03-2025 12:45:36","09-03-2025 12:40:28","09-03-2025 13:2=
3:26","Grid outage, site went down Gen failed to start due to PWC ZTE malfu=
nction // He reset it and started Gen manualy","Mba Lazare Herve","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage,=
 site went down Gen failed to start due to PWC ZTE malfunction // He reset =
it and started Gen manualy","yves.djomo@sagemcom.com","309","09-03-2025 12:=
45:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004530896","E=
ssomba","","09-03-2025 12:45:20","09-03-2025 12:39:12","09-03-2025 12:45:10=
","Active // No power issue site on Gen with U=3D51.6 V Tx Fme Henri(691145=
055) of Huawei is informed. Notice that we have disjunction at BTS OCM","Mb=
a Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active // No power issue site on Gen with U=3D5=
1.6 V Tx Fme Henri(691145055) of Huawei is informed. Notice that we have di=
sjunction at BTS OCM","el-dalile@sagemcom.com","369","09-03-2025 12:45:20",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004530795","A=
WAE OCM","","09-03-2025 12:30:15","09-03-2025 12:26:08","09-03-2025 12:52:4=
6","Grid outage, Site went down before gen start due to poor battery backup=
 // Gen started automatically","Mba Lazare Herve","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before gen start due to poor battery backup // Gen started automaticall=
y","el-dalile@sagemcom.com","249","09-03-2025 12:30:15","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004530754","Nko=
zoa","","09-03-2025 12:20:59","09-03-2025 12:19:47","09-03-2025 15:23:46","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and Gen manually star=
ted","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, site went down due to gen overload (20kva, 340A) SS HIS=
 Felix bateu is informed and confirmed// He reduced the load and Gen manual=
ly started","el-dalile@sagemcom.com","74","09-03-2025 12:20:59","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004530561","B=
iteng-Maetur","","09-03-2025 11:40:50","09-03-2025 11:38:43","09-03-2025 13=
:30:34","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","el-dali=
le@sagemcom.com","129","09-03-2025 11:40:50","Sagemcom CMR"
"Closed Complete","Warning","T0091","IHS_YND_314","NOCINC0004530529","Sous =
Prefecture","","09-03-2025 11:37:23","","","Site went alarmes due to Gen Ca=
rd dysfonction//he Manually Started the Gen ","Fanda Brice","Warning","Warn=
ing","POWER","Warning - Site on Battery","Site went alarmes due to Gen Card=
 dysfonction//he Manually Started the Gen ","el-dalile@sagemcom.com","1285"=
,"09-03-2025 11:37:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004530330","M=
arche Odza","","09-03-2025 11:12:24","09-03-2025 11:09:56","09-03-2025 11:2=
4:19","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started automaticaly","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automaticaly","yves.djomo@sagem=
com.com","149","09-03-2025 11:12:24","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004530226","Aka=
k-Nkozoa-MTN-IHS","","09-03-2025 10:51:29","09-03-2025 10:48:06","09-03-202=
5 11:54:55","Grid fluctuation,Site went down because GEN failed to start du=
e to grid bad voltage(lack of 01 phase)// He did a bridge on the good phase=
","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation,Site went down because GEN failed to st=
art due to grid bad voltage(lack of 01 phase)// He did a bridge on the good=
 phase","el-dalile@sagemcom.com","205","09-03-2025 10:51:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004530046","Nomayos =
montee Meche","","09-03-2025 10:21:42","09-03-2025 09:56:21","09-03-2025 16=
:30:10","Cascaded Incident from TTO4592714","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
due to main gen faulty // Grid return","system","302827","09-03-2025 10:21:=
42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004530047","Nkolfon =
Cimencam","","09-03-2025 10:21:42","09-03-2025 09:56:21","09-03-2025 16:30:=
10","Cascaded Incident from TTO4592714","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to main gen faulty // Grid return","system","302826","09-03-2025 10:21:4=
2","Sagemcom CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004529790","Nom=
ayos","IHS_YND_791, IHS_YND_762","09-03-2025 09:58:39","09-03-2025 09:56:21=
","09-03-2025 16:30:10","Grid outage, site went down due to main gen faulty=
 // Grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACD=
G - Generator Faulty","Grid outage, site went down due to main gen faulty /=
/ Grid return","el-dalile@sagemcom.com","139","09-03-2025 09:58:39","Sagemc=
om CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004529442","MBA=
LNGONG LYCEE","","09-03-2025 09:12:30","09-03-2025 09:03:55","09-03-2025 18=
:40:03","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe confirmed // Grid power return","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Sit=
e went down because Gen stopped due to overload(9kva, 130A) SS IHS Felix Za=
mbe confirmed // Grid power return","el-dalile@sagemcom.com","516","09-03-2=
025 09:12:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004529027","S=
hell-Nsimeyong","","09-03-2025 08:34:48","09-03-2025 08:33:43","09-03-2025 =
09:44:38","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","el-dalile@sagemcom.com","66","09-03-2025 08:34:48","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004529016","NKO=
LMEKONG YDE","","09-03-2025 08:31:36","09-03-2025 08:30:23","09-03-2025 08:=
33:08","Grid outage, Site went down because PWC dysfunctionning IHS SS BERN=
ARD ATANGANA confirmed// Grid return","Fabrice Pouakam","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Grid outage, Site went=
 down because PWC dysfunctionning IHS SS BERNARD ATANGANA confirmed// Grid =
return","el-dalile@sagemcom.com","74","09-03-2025 08:31:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004528730","Dong",""=
,"09-03-2025 07:55:20","09-03-2025 07:54:21","09-03-2025 07:58:51","Cascade=
d Incident from TTO4591580","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue with U=3D51.4V //site =
on Gen THe fme tx Gregoire 652070658 from Huawei is informed","system","267=
018","09-03-2025 07:55:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004528728","D=
onga","IHS_YND_444","09-03-2025 07:54:33","09-03-2025 07:54:21","09-03-2025=
 07:58:51","Active//No power issue with U=3D51.4V //site on Gen THe fme tx =
Gregoire 652070658 from Huawei is informed","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue with U=3D51.4V //site on Gen THe fme tx Gregoire 652070=
658 from Huawei is informed","yves.djomo@sagemcom.com","13","09-03-2025 07:=
54:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004528670","N=
koabang Ebolmedjock","","09-03-2025 07:46:56","09-03-2025 07:45:52","09-03-=
2025 07:48:05","Active// No power issue, site is on Gen with Ubaie=3D53,6V,=
 Lionel Adjep(655184876) from Huawei is informed. Notice that we have repet=
itive issue","Mba Lazare Herve","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active// No power issue, site i=
s on Gen with Ubaie=3D53,6V, Lionel Adjep(655184876) from Huawei is informe=
d. Notice that we have repetitive issue","yves.djomo@sagemcom.com","65","09=
-03-2025 07:46:56","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004528596","Crf=
-Nsam","","09-03-2025 07:25:20","09-03-2025 07:23:16","09-03-2025 08:52:15"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline conf=
irmed// He reset PWC","MINKA NICOLAS","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down because PWC(24kilo) dysfu=
nctionning, IHS SS Pascaline confirmed// He reset PWC","yves.djomo@sagemcom=
.com","124","09-03-2025 07:25:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004528433","M=
efou-Assi","","09-03-2025 06:53:54","09-03-2025 06:50:48","09-03-2025 06:51=
:14","ACTIVE//No power issue on site GRID , Ubaie=3D54.3V site On Grid The =
Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//No power issue on site GRID , Ubaie=3D54.3V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed","el-dalile@sagemcom.com","18=
7","09-03-2025 06:53:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004528212","N=
yom OCM","","09-03-2025 05:41:14","09-03-2025 05:32:19","09-03-2025 07:16:1=
6","Grid fluctuation, site went down because Gen failed to start due to gri=
d bad voltage No RCP // He bypassed grid and started Gen manually","Fabrice=
 Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation, site went down because Gen failed to start due t=
o grid bad voltage No RCP // He bypassed grid and started Gen manually","ma=
riam.tchonang@sagemcom.com","536","09-03-2025 05:41:14","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004527887","NYO=
M FACE MAETUR","","09-03-2025 03:30:43","09-03-2025 03:22:30","09-03-2025 1=
4:16:30","Site went down due to 03 Rectifiers faulty caused by heavy rain, =
SS IHS Bernard Atangana confirmed // He added 02 rectifiers","Fabrice Pouak=
am","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went =
down due to 03 Rectifiers faulty caused by heavy rain, SS IHS Bernard Atang=
ana confirmed // He added 02 rectifiers","mariam.tchonang@sagemcom.com","49=
4","09-03-2025 03:30:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004527623","M=
essassi 2","","09-03-2025 01:57:31","09-03-2025 01:48:20","09-03-2025 06:47=
:23","Site went down because PWC overload (12 kilo, 300A) , SS IHS Bernard =
ATANGANA confirmed// He reset PWC","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Site went down because PW=
C overload (12 kilo, 300A) , SS IHS Bernard ATANGANA confirmed// He reset P=
WC","mariam.tchonang@sagemcom.com","553","09-03-2025 01:57:31","Sagemcom CM=
R"
"Closed Complete","Site Down","T3206","IHS_YND_759","NOCINC0004527503","Nko=
lfoulou Tsinga Village","","09-03-2025 00:58:44","09-03-2025 00:55:02","09-=
03-2025 02:05:00","Grid fluctuation, Site went down because Gen failed to s=
tart due to Grid bad voltage(lack of two  phase )  // He made a bridge with=
 a good phase","Siligap Boris","Grid Supply","Passive","Grid","National Gri=
d - Phase Controller Faulty","Grid fluctuation, Site went down because Gen =
failed to start due to Grid bad voltage(lack of two  phase )  // He made a =
bridge with a good phase","mariam.tchonang@sagemcom.com","223","09-03-2025 =
00:58:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004526892","M=
efou-Assi","","08-03-2025 22:20:42","08-03-2025 22:18:31","08-03-2025 22:23=
:41","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME=
 Fulbert(654266068) from Huawei is informed","cedric.tiani@sagemcom.com","1=
32","08-03-2025 22:20:42","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004526679","An-=
Marche-Melen","","08-03-2025 21:42:26","08-03-2025 16:22:14","08-03-2025 23=
:26:26","Site went down due to insufficiency of rectifiers, Francois IHS //=
 He reduced the load","","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficiency of rectifiers, Francois IHS =
// He reduced the load","ferot.nongni-djiogap@sagemcom.com","19213","08-03-=
2025 21:42:26","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004526534","Ona=
ngondi (melen bikop)","","08-03-2025 21:15:32","08-03-2025 21:12:27","08-03=
-2025 21:32:32","Hybrid gen site.site went down due to hybrid system malfun=
ctionning//Gen manually started","Fanda Brice","Equipment Repair","Passive"=
,"Hybrid","Hybrid Module","Hybrid gen site.site went down due to hybrid sys=
tem malfunctionning//Gen manually started","ferot.nongni-djiogap@sagemcom.c=
om","186","08-03-2025 21:15:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0004526492","A=
hala","","08-03-2025 21:09:39","08-03-2025 20:50:23","08-03-2025 21:45:58",=
"Grid fluctuation,site went down because gen failed to start due to Grid ba=
d voltage(lack of one phase)//He did a bridge with the Good phase","MINKA N=
ICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation,site went down because gen failed to start due to G=
rid bad voltage(lack of one phase)//He did a bridge with the Good phase","c=
edric.tiani@sagemcom.com","1156","08-03-2025 21:09:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004526409","B=
ATA Mokolo OCM","","08-03-2025 20:55:50","08-03-2025 13:35:25","10-03-2025 =
09:02:54","Access Issue during the Weekend (Grid outage, No space to deploy=
 MDG // Grid return)  ","","Access Denial","Lease Or Legal","Landlord Relat=
ed Issues","Access Issue - Land Lord","Access Issue during the Weekend (Gri=
d outage, No space to deploy MDG // Grid return)  ","cedric.tiani@sagemcom.=
com","26426","08-03-2025 20:55:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004526317","M=
ini-Ferme","","08-03-2025 20:42:36","08-03-2025 20:41:24","08-03-2025 20:43=
:27","Grid outage No space // Grid power return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage No space // Grid p=
ower return","cedric.tiani@sagemcom.com","73","08-03-2025 20:42:36","Sagemc=
om CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004526218","Crf=
-Mbankolo-IHS","","08-03-2025 20:16:55","08-03-2025 20:11:49","08-03-2025 2=
1:08:35","Site went down due to MPR disfunction SS IHS Bernard Atangana con=
firmed//Site stabilized with power reset done","Mboua Thierry","Equipment R=
epair","Passive","Rectifier","Rectifier Cabinet","Site went down due to MPR=
 disfunction SS IHS Bernard Atangana confirmed//Site stabilized with power =
reset done","ferot.nongni-djiogap@sagemcom.com","307","08-03-2025 20:16:55"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004525912","Mam=
bine","","08-03-2025 19:19:32","08-03-2025 18:57:25","08-03-2025 20:34:44",=
"Site went down because Gen fails to start due to hybrid system malfunction=
ning//hE RESET THE hybrid system and Gen manually started","Fanda Brice","E=
quipment Repair","Passive","Control Panel","ATS-AMF Issue","Site went down =
because Gen fails to start due to hybrid system malfunctionning//hE RESET T=
HE hybrid system and Gen manually started","ferot.nongni-djiogap@sagemcom.c=
om","1361","08-03-2025 19:19:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004525890","E=
ssomba","","08-03-2025 19:16:12","08-03-2025 13:21:31","08-03-2025 13:30:41=
","BACK TRACKING Active: No power issue, site is on Grid with Ubaie=3D54.1V=
, The fme tx George //697461814//from Huawei is informed. Notice Dysjunctio=
n at the BTS OCM","Mba Lazare Herve","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issue, si=
te is on Grid with Ubaie=3D54.1V, The fme tx George //697461814//from Huawe=
i is informed. Notice Dysjunction at the BTS OCM","cedric.tiani@sagemcom.co=
m","21282","08-03-2025 19:16:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0004525865","Nkolondo=
m","","08-03-2025 19:12:01","08-03-2025 18:21:31","08-03-2025 19:16:30","Ca=
scaded Incident from TTO4587785","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with alarm high temperature // He opened the shelter=
 doors and gen manually started","system","272650","08-03-2025 19:12:01","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0004525863","NKOLMEKO=
NG YDE","","08-03-2025 19:12:01","08-03-2025 18:21:31","08-03-2025 19:16:30=
","Cascaded Incident from TTO4587785","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause gen start and stopped with alarm high temperature // He opened the sh=
elter doors and gen manually started","system","272650","08-03-2025 19:12:0=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0004525864","Nyom OCM=
","","08-03-2025 19:12:01","08-03-2025 18:21:31","08-03-2025 19:16:30","Cas=
caded Incident from TTO4587785","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen start and stopped with alarm high temperature // He opened the shelter =
doors and gen manually started","system","272650","08-03-2025 19:12:01","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0004525862","Ekombiti=
e","","08-03-2025 19:12:00","08-03-2025 18:21:31","08-03-2025 19:16:30","Ca=
scaded Incident from TTO4587785","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with alarm high temperature // He opened the shelter=
 doors and gen manually started","system","272651","08-03-2025 19:12:00","S=
agemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004525564","Mon=
tee Jouvence","","08-03-2025 18:33:48","08-03-2025 18:30:43","08-03-2025 18=
:36:01","Site went down due to insufficiency of rectifiers // He reduced th=
e load , site on grid","Hyemafo Gildas","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down due to insufficiency of rectifiers=
 // He reduced the load , site on grid","ferot.nongni-djiogap@sagemcom.com"=
,"186","08-03-2025 18:33:48","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0004525521","Ole=
mbe","IHS_YND_276, IHS_YND_681, IHS_YND_303, IHS_YND_304","08-03-2025 18:23=
:54","08-03-2025 18:21:31","08-03-2025 19:16:30","Grid outage, site went do=
wn because gen start and stopped with alarm high temperature // He opened t=
he shelter doors and gen manually started","Fabrice Pouakam","Equipment Rep=
air","Passive","ACDG Gen","Gen Temp High","Grid outage, site went down beca=
use gen start and stopped with alarm high temperature // He opened the shel=
ter doors and gen manually started","cedric.tiani@sagemcom.com","145","08-0=
3-2025 18:23:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004525378","M=
ontee-Des-Soeurs","","08-03-2025 17:57:36","08-03-2025 17:45:13","08-03-202=
5 17:50:11","No power Issue Site on Grid Ubai =3D54.3 V. The TX FME Mbah Ho=
siah (674007438) is informed .Uptime 02:46 PM","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power Issue Site on Grid Ubai =3D54.3 V. The TX FME Mbah Hosiah (674007=
438) is informed .Uptime 02:46 PM","cedric.tiani@sagemcom.com","744","08-03=
-2025 17:57:36","Sagemcom CMR"
"Closed Complete","Site Down","T1071","IHS_YND_343","NOCINC0004525353","Mbe=
doumou - Ekali","","08-03-2025 17:53:57","08-03-2025 17:46:51","08-03-2025 =
18:12:33","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Site went down due to 01/4 rectifiers faulty // site on g=
rid on 03 rectifiers","ferot.nongni-djiogap@sagemcom.com","267240","08-03-2=
025 17:53:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004525343","Mehanda =
1","","08-03-2025 17:52:31","08-03-2025 17:46:51","08-03-2025 18:12:33","Ca=
scaded Incident from TTO4587518","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to 01/4 rectifiers=
 faulty // site on grid on 03 rectifiers","system","267241","08-03-2025 17:=
52:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004525345","Odza Min=
kan IHS","","08-03-2025 17:52:31","08-03-2025 17:46:51","08-03-2025 18:12:3=
3","Cascaded Incident from TTO4587518","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to 01/4 rect=
ifiers faulty // site on grid on 03 rectifiers","system","267241","08-03-20=
25 17:52:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004525346","ODZA MIN=
KAN EDIBI ASSI","","08-03-2025 17:52:31","08-03-2025 17:46:51","08-03-2025 =
18:12:33","Cascaded Incident from TTO4587518","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down due to 01=
/4 rectifiers faulty // site on grid on 03 rectifiers","system","267242","0=
8-03-2025 17:52:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004525344","Odza II =
OCM","","08-03-2025 17:52:31","08-03-2025 17:46:51","08-03-2025 18:12:33","=
Cascaded Incident from TTO4587518","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to 01/4 rectifie=
rs faulty // site on grid on 03 rectifiers","system","267242","08-03-2025 1=
7:52:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004525342","MEHANDAN=
","","08-03-2025 17:52:30","08-03-2025 17:46:51","08-03-2025 18:12:33","Cas=
caded Incident from TTO4587518","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to 01/4 rectifiers =
faulty // site on grid on 03 rectifiers","system","267240","08-03-2025 17:5=
2:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_328","NOCINC0004525341","Nsimalen=
 MTN","","08-03-2025 17:52:30","08-03-2025 17:46:51","08-03-2025 18:12:33",=
"Cascaded Incident from TTO4587518","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to 01/4 rectifi=
ers faulty // site on grid on 03 rectifiers","system","267241","08-03-2025 =
17:52:30","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004525304","Nko=
lnda","IHS_YND_343, IHS_YND_328, IHS_YND_528, IHS_YND_746, IHS_YND_527, IHS=
_YND_715, IHS_YND_749","08-03-2025 17:49:57","08-03-2025 17:46:51","08-03-2=
025 18:12:33","Site went down due to 01/4 rectifiers faulty // site on grid=
 on 03 rectifiers","Albran Byorel","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to 01/4 rectifiers faulty // site o=
n grid on 03 rectifiers","ferot.nongni-djiogap@sagemcom.com","186","08-03-2=
025 17:49:57","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004524766","Mfo=
u EPC","","08-03-2025 16:34:04","08-03-2025 16:31:59","08-03-2025 16:35:05"=
,"Active//No power issue on site, Site on Gen UBAIE=3D51.4V The RM Martial =
(650252214) from Huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue on site, Site on Gen UBAIE=3D51.4V The RM Martial (65025221=
4) from Huawei is informed","ferot.nongni-djiogap@sagemcom.com","126","08-0=
3-2025 16:34:04","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004524752","NYO=
M 2 IHS","","08-03-2025 16:32:00","08-03-2025 16:28:47","08-03-2025 16:37:0=
9","Grid outage, Site went down before Gen start due to poor backup // Gen =
started automaticaly","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Gen started automaticaly","cedric.tiani@sa=
gemcom.com","194","08-03-2025 16:32:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004524739","C=
RH-Etoug-Ebe","","08-03-2025 16:30:36","08-03-2025 16:21:18","08-03-2025 16=
:39:35","Grid outage, Site went down before Gen start due to poor backup// =
Gen manually started","Hyemafo Gildas","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen manually started","cedric.tiani@sagemcom=
.com","559","08-03-2025 16:30:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004524736","N=
kolfoulou","","08-03-2025 16:29:30","08-03-2025 16:27:17","08-03-2025 16:32=
:17","Grid fluctuation, Site went down before Gen start due to poor backup/=
/ GEN started automatically(Investigation ongoing)","Siligap Boris","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid fluctuation, =
Site went down before Gen start due to poor backup// GEN started automatica=
lly(Investigation ongoing)","cedric.tiani@sagemcom.com","134","08-03-2025 1=
6:29:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004524668","B=
iteng-Maetur","","08-03-2025 16:20:10","08-03-2025 15:05:55","08-03-2025 18=
:32:14","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","cedric.=
tiani@sagemcom.com","4456","08-03-2025 16:20:10","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004524484","Elo=
umdem stade","","08-03-2025 16:01:33","08-03-2025 15:53:14","08-03-2025 17:=
41:00","Site went down because gen failed to start due to grid bad voltage =
// Gen manually started","Fanda Brice","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","Site went down because gen failed to =
start due to grid bad voltage // Gen manually started","ferot.nongni-djioga=
p@sagemcom.com","500","08-03-2025 16:01:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004524162","N=
gouetou","","08-03-2025 15:12:33","08-03-2025 14:49:31","08-03-2025 19:43:1=
1","","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","No Power issue on site, Site is on GEN; Ubaie =3D 53V. TX FME TX FM=
E WILLY NGOUNI 655999839 of HUAWEI is informed.","ferot.nongni-djiogap@sage=
mcom.com","278283","08-03-2025 15:12:33","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004524084","Mel=
en Ba'aba","","08-03-2025 14:58:34","08-03-2025 14:51:29","08-03-2025 14:57=
:08"," Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME J=
ulien(693095849) from Huawei is informed ","Siligap Boris","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," Act=
ive// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Julien(6930=
95849) from Huawei is informed ","wilfried.kameni@sagemcom.com","426","08-0=
3-2025 14:58:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004523802","M=
essassi 2","","08-03-2025 14:10:29","08-03-2025 13:19:15","08-03-2025 15:31=
:26","Grid outage, Site went down because Gen start and stopped with ""High=
 temps ""alarm // He added water and manually start the Gen","Fabrice Pouak=
am","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid outage, Site went down because Gen start and stopped=
 with ""High temps ""alarm // He added water and manually start the Gen","d=
anick.tchakouani@sagemcom.com","3076","08-03-2025 14:10:29","Sagemcom CMR"
"Closed Complete","Warning","T0103","IHS_YND_110","NOCINC0004523616","Camp-=
Sonel","","08-03-2025 13:39:45","","","Site alarm due to work(Justin (65710=
0524) / Sagemcom, draining )) // End of work","Siligap Boris","Warning","Wa=
rning","POWER","Warning - Planned Activity - Passive","Site alarm due to wo=
rk(Justin (657100524) / Sagemcom, draining )) // End of work","wilfried.kam=
eni@sagemcom.com","7636","08-03-2025 13:39:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0004523400","Olembe-T=
erminus","","08-03-2025 13:23:57","08-03-2025 13:09:25","08-03-2025 14:06:3=
6","Cascaded Incident from TTO4585213","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage.gen failed to sta=
rt due alrm ""low oil pressure""//We add oil and gen manually started","sys=
tem","269522","08-03-2025 13:23:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0004523363","O=
lembe","IHS_YND_300","08-03-2025 13:17:30","08-03-2025 13:09:25","08-03-202=
5 14:06:36","Grid outage.gen failed to start due alrm ""low oil pressure""/=
/We add oil and gen manually started","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage.gen failed to s=
tart due alrm ""low oil pressure""//We add oil and gen manually started","d=
anick.tchakouani@sagemcom.com","487","08-03-2025 13:17:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004523164","SOA TOWN=
","","08-03-2025 12:59:01","08-03-2025 12:16:29","08-03-2025 12:59:04","Cas=
caded Incident from TTO4584697","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down because ge=
n stopped due to belt cut // He changed belt and Gen manually started","sys=
tem","265581","08-03-2025 12:59:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004523162","SOA UNIV=
ERSITY STADIUM","","08-03-2025 12:59:01","08-03-2025 12:16:29","08-03-2025 =
12:59:04","Cascaded Incident from TTO4584697","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went d=
own because gen stopped due to belt cut // He changed belt and Gen manually=
 started","system","265582","08-03-2025 12:59:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_317","NOCINC0004523160","Soa-Sofa=
mac","","08-03-2025 12:59:00","08-03-2025 12:16:29","08-03-2025 12:59:04","=
Cascaded Incident from TTO4584697","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 gen stopped due to belt cut // He changed belt and Gen manually started","=
system","265581","08-03-2025 12:59:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004523161","Ebogo","=
","08-03-2025 12:59:00","08-03-2025 12:16:29","08-03-2025 12:59:04","Cascad=
ed Incident from TTO4584697","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because gen s=
topped due to belt cut // He changed belt and Gen manually started","system=
","265580","08-03-2025 12:59:00","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004523104","Nko=
zoa","","08-03-2025 12:54:32","08-03-2025 12:46:19","08-03-2025 15:07:58","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// grid return","Fabrice Pouakam","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went dow=
n due to gen overload (20kva, 340A) SS HIS Felix bateu is informed and conf=
irmed// grid return","wilfried.kameni@sagemcom.com","495","08-03-2025 12:54=
:32","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004523081","Ole=
mbe MTN","","08-03-2025 12:49:56","08-03-2025 12:31:42","08-03-2025 15:43:1=
8","Grid Outage Site went down due to Grid Contactors Faulty on Site//He By=
pass it and Site is on Gen","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","ATS-AMF Issue","Grid Outage Site went down due to Grid Con=
tactors Faulty on Site//He Bypass it and Site is on Gen","wilfried.kameni@s=
agemcom.com","1095","08-03-2025 12:49:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0004522928","S=
OA 2","IHS_YND_317, IHS_YND_307, IHS_YND_720, IHS_YND_326, IHS_YND_320","08=
-03-2025 12:25:37","08-03-2025 12:16:29","08-03-2025 12:59:04","Grid outage=
, Site went down because gen stopped due to belt cut // He changed belt and=
 Gen manually started","Siligap Boris","Equipment Repair","Passive","ACDG G=
en","ACDG - Fan Belt","Grid outage, Site went down because gen stopped due =
to belt cut // He changed belt and Gen manually started","wilfried.kameni@s=
agemcom.com","549","08-03-2025 12:25:37","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004522848","EMA=
NA BILICK CITY","","08-03-2025 12:19:37","08-03-2025 12:12:27","08-03-2025 =
16:18:03","Grid outage, Site went down because Gen failed to start due to A=
TS faulty// He bypassed ATS and started  Gen manualy","Fabrice Pouakam","Eq=
uipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Sit=
e went down because Gen failed to start due to ATS faulty// He bypassed ATS=
 and started  Gen manualy","wilfried.kameni@sagemcom.com","432","08-03-2025=
 12:19:37","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004522780","NTU=
I TOWN","","08-03-2025 12:08:10","08-03-2025 11:59:01","08-03-2025 15:30:05=
","Grid outage, Site went because Gen ran until fuel shortage// Refueling D=
one","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid=
 outage, Site went because Gen ran until fuel shortage// Refueling Done","w=
ilfried.kameni@sagemcom.com","550","08-03-2025 12:08:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004522614","B=
ATA Mokolo OCM","","08-03-2025 11:43:35","08-03-2025 11:41:26","08-03-2025 =
13:31:59","Grid outage, No space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No =
space to deploy MDG // Grid return","danick.tchakouani@sagemcom.com","130",=
"08-03-2025 11:43:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004522329","E=
vodoula OCM","","08-03-2025 11:15:02","08-03-2025 11:12:57","08-03-2025 11:=
48:11","Grid outage, site went down because gen failed to start due to sole=
noid valve // He bypassed solenoid valve and Gen manually started","TIENTCH=
EU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Solenoid=
 Coil","Grid outage, site went down because gen failed to start due to sole=
noid valve // He bypassed solenoid valve and Gen manually started","danick.=
tchakouani@sagemcom.com","126","08-03-2025 11:15:02","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004522234","Aka=
k-Nkozoa-MTN-IHS","","08-03-2025 11:02:35","08-03-2025 10:54:23","08-03-202=
5 18:09:49","Gen started due to grid outage, site went down because disfunc=
tionning of PWC// He disconnected controller, site on gen(investigation ong=
oing)","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Gen started due to grid outage, site went down becaus=
e disfunctionning of PWC// He disconnected controller, site on gen(investig=
ation ongoing)","wilfried.kameni@sagemcom.com","494","08-03-2025 11:02:35",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004522087","Nkolfon =
Cimencam","","08-03-2025 10:44:13","08-03-2025 10:37:00","08-03-2025 17:29:=
33","Cascaded Incident from TTO4583601","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to main gen faulty // Grid return","system","293192","08-03-2025 10:44:1=
3","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004522086","Nomayos =
montee Meche","","08-03-2025 10:44:12","08-03-2025 10:37:00","08-03-2025 17=
:29:33","Cascaded Incident from TTO4583601","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
due to main gen faulty // Grid return","system","293192","08-03-2025 10:44:=
12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004522001","Nkenglik=
ok","","08-03-2025 10:39:26","08-03-2025 10:33:00","08-03-2025 11:04:03","C=
ascaded Incident from TTO4583575","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down due to =
Main Gen faulty // he 20KVA has ddeploy","system","293434","08-03-2025 10:3=
9:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004522004","Nkongtoc=
k","","08-03-2025 10:39:26","08-03-2025 10:33:00","08-03-2025 11:04:03","Ca=
scaded Incident from TTO4583575","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down due to M=
ain Gen faulty // he 20KVA has ddeploy","system","293433","08-03-2025 10:39=
:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004522003","Mambine"=
,"","08-03-2025 10:39:26","08-03-2025 10:33:00","08-03-2025 11:04:03","Casc=
aded Incident from TTO4583575","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down due to Main Ge=
n faulty // he 20KVA has ddeploy","system","293434","08-03-2025 10:39:26","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004522002","Nomayos-=
IHS","","08-03-2025 10:39:26","08-03-2025 11:08:00","08-03-2025 11:46:07","=
Grid outage site went down due to Gen overload (15Kva, 170A) SS IHS f=E9lix=
 Zamb=E9 is confirm // He reduced the load on site","Fanda Brice","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went dow=
n due to Gen overload (15Kva, 170A) SS IHS f=E9lix Zamb=E9 is confirm // He=
 reduced the load on site","system","896","08-03-2025 10:39:26","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004521999","Mandoumb=
a OCM","","08-03-2025 10:39:25","08-03-2025 10:33:00","08-03-2025 11:04:03"=
,"Cascaded Incident from TTO4583575","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down due =
to Main Gen faulty // he 20KVA has ddeploy","system","293433","08-03-2025 1=
0:39:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004522000","Mbankomo=
 IHS","","08-03-2025 10:39:25","08-03-2025 10:33:00","08-03-2025 11:04:03",=
"Cascaded Incident from TTO4583575","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down due to Ma=
in Gen faulty // he 20KVA has ddeploy","system","293435","08-03-2025 10:39:=
25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004521990","N=
omayos","IHS_YND_367, IHS_YND_791, IHS_YND_695, IHS_YND_348, IHS_YND_339, I=
HS_YND_762, IHS_YND_350, IHS_YND_349","08-03-2025 10:38:05","08-03-2025 10:=
33:00","08-03-2025 17:29:33","Grid outage, site went down due to main gen f=
aulty // Grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Faulty","Grid outage, site went down due to main gen fau=
lty // Grid return","wilfried.kameni@sagemcom.com","306","08-03-2025 10:38:=
05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004521964","E=
beba","","08-03-2025 10:34:50","08-03-2025 10:33:00","08-03-2025 11:04:03",=
"","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage site went down due to Main Gen faulty // he 20KVA has dde=
ploy","danick.tchakouani@sagemcom.com","293434","08-03-2025 10:34:50","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004521862","S=
calom","","08-03-2025 10:24:57","08-03-2025 10:21:52","08-03-2025 10:25:22"=
,"Grid Outage, site went down before gen start due to poor battery backup /=
/ Grid return","Paul BIBOUM","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid Outage, site went down before gen start =
due to poor battery backup // Grid return","danick.tchakouani@sagemcom.com"=
,"186","08-03-2025 10:24:57","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004521498","AKA=
K Nkozoa","","08-03-2025 09:57:27","08-03-2025 09:26:22","08-03-2025 09:59:=
48","	Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Sy=
mphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"	Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Sympho=
rien (650257151) from Huawei is informed","danick.tchakouani@sagemcom.com",=
"1866","08-03-2025 09:57:27","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004521370","MBA=
LNGONG LYCEE","","08-03-2025 09:54:43","08-03-2025 09:42:37","08-03-2025 17=
:21:06","	Grid outage, Site went down because Gen stopped due to overload(9=
kva, 130A) SS IHS Felix Zambe is informed and confirmed//Grid return","Fand=
a Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","	Grid o=
utage, Site went down because Gen stopped due to overload(9kva, 130A) SS IH=
S Felix Zambe is informed and confirmed//Grid return","danick.tchakouani@sa=
gemcom.com","727","08-03-2025 09:54:43","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004521296","Nsi=
meyong Shell","","08-03-2025 09:53:25","08-03-2025 09:41:20","08-03-2025 14=
:00:47","No power issue, site on Grid With Ubaie=3D54.5 V, The Tx FME Hosia=
h (674007438) from Huawei is informed","MINKA NICOLAS","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue, site on Grid With Ubaie=3D54.5 V, The Tx FME Hosiah (674007438) fro=
m Huawei is informed
","danick.tchakouani@sagemcom.com","727","08-03-2025 09:53:25","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004520996","M=
efou-Assi","","08-03-2025 09:33:51","08-03-2025 09:30:45","08-03-2025 09:35=
:52","Active// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME=
 Fulbert(654266068) of huawei is informed","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME Fulbert(654=
266068) of huawei is informed","danick.tchakouani@sagemcom.com","187","08-0=
3-2025 09:33:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004520947","B=
arriere IHS","","08-03-2025 09:26:05","08-03-2025 09:19:24","08-03-2025 11:=
21:23","Grid outage, Site went down because Gen failed to start due to PWC =
dysfunctionning IHS Supervisor Felix Zambe confirmed // grid return","Hyema=
fo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module Overl=
oaded","Grid outage, Site went down because Gen failed to start due to PWC =
dysfunctionning IHS Supervisor Felix Zambe confirmed // grid return","wilfr=
ied.kameni@sagemcom.com","403","08-03-2025 09:26:05","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004520906","Mfo=
u EPC","","08-03-2025 09:16:51","08-03-2025 09:12:44","08-03-2025 10:10:16"=
,"Active//No power issue on site, Site on Gen UBAIE=3D51.4V The RM Martial =
(650252214) from Huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue on site, Site on Gen UBAIE=3D51.4V The RM Martial (65025221=
4) from Huawei is informed","wilfried.kameni@sagemcom.com","249","08-03-202=
5 09:16:51","Sagemcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004520732","Ntu=
i administration","","08-03-2025 08:46:53","08-03-2025 08:45:47","08-03-202=
5 09:22:56","Grid outage, Site went down before Gen start due to poor backu=
p // Grid return","Parker Tchoup","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup // Grid return","wilfried.kameni@sagemcom.com","67"=
,"08-03-2025 08:46:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004520157","S=
hell-Nsimeyong","","08-03-2025 07:02:14","08-03-2025 06:58:52","08-03-2025 =
07:05:19","No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed. ","MINKA NICOLAS","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (674007438/69=
9699694) from Huawei is informed. ","wilfried.kameni@sagemcom.com","204","0=
8-03-2025 07:02:14","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004519769","Nko=
lnda","","08-03-2025 05:40:34","08-03-2025 05:36:27","08-03-2025 06:36:06",=
"Grid outage site went down because Gen stopped with alarm HIGH temp due to=
 Radiator pierced // He glue the radiator and added water Gen manually star=
ted","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","Grid outage site went down because Gen s=
topped with alarm HIGH temp due to Radiator pierced // He glue the radiator=
 and added water Gen manually started","danick.tchakouani@sagemcom.com","24=
8","08-03-2025 05:40:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0004519597","NYANON/D=
EMBO","","08-03-2025 05:00:40","08-03-2025 04:20:13","08-03-2025 10:07:40",=
"Cascaded Incident from TTO4580818","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Grid outage site went d=
own because Gen failed to start due to =E9lectrovane Stop faulty // Gen man=
ually started","system","287262","08-03-2025 05:00:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_670","NOCINC0004519596","BOBOCK",=
"","08-03-2025 04:59:10","08-03-2025 04:20:13","08-03-2025 10:07:40","Casca=
ded Incident from TTO4580818","Kemeni Franklin","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 failed to start due to =E9lectrovane Stop faulty // Gen manually started",=
"system","287262","08-03-2025 04:59:10","Sagemcom CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0004519581","Nya=
hoo","IHS_EDA_102, IHS_EDA_049, IHS_YND_670","08-03-2025 04:51:24","08-03-2=
025 04:20:13","08-03-2025 10:07:40","Grid outage site went down because Gen=
 failed to start due to =E9lectrovane Stop faulty // Gen manually started",=
"TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - =
Solenoid Coil","Grid outage site went down because Gen failed to start due =
to =E9lectrovane Stop faulty // Gen manually started","ludovic-anselme.moul=
iom-mapoure@sagemcom","1872","08-03-2025 04:51:24","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004519448","NYO=
M FACE MAETUR","","08-03-2025 04:03:05","08-03-2025 04:00:59","09-03-2025 0=
3:15:51","Site went down due to 03 Rectifiers faulty caused by heavy rain, =
SS IHS Bernard Atangana confirmed.//Grid return","Fabrice Pouakam","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","Site went down due to =
03 Rectifiers faulty caused by heavy rain, SS IHS Bernard Atangana confirme=
d.//Grid return","danick.tchakouani@sagemcom.com","128","08-03-2025 04:03:0=
5","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004519330","Crf=
-Nsam","","08-03-2025 03:19:00","08-03-2025 03:17:46","08-03-2025 06:17:49"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline conf=
irmed//Grid return","MINKA NICOLAS","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Site went down because PWC(24kilo) dysfunc=
tionning, IHS SS Pascaline confirmed//Grid return","danick.tchakouani@sagem=
com.com","75","08-03-2025 03:19:00","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0004519072","Fou=
da rue des g=E9n=E9raux","","08-03-2025 01:34:12","08-03-2025 01:30:05","08=
-03-2025 02:19:05","Site went down because gen start and stopped due to gri=
d bad voltage // He bypass grid and manually start the gen","Delor Telezing=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Site went down because gen start and stopped due to grid bad voltage // He=
 bypass grid and manually start the gen","danick.tchakouani@sagemcom.com","=
247","08-03-2025 01:34:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004519050","Scalom-I=
HS","","08-03-2025 01:28:31","08-03-2025 00:01:53","08-03-2025 04:55:53","C=
ascaded Incident from TTO4579703","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Site went down because Power cable has been stole=
n on Site (power cable between the PWC and the DC-box ) // He replaced the =
power cable between the DC-Box and PWC","system","288231","08-03-2025 01:28=
:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0004519051","Scalom",=
"","08-03-2025 01:28:31","08-03-2025 00:01:53","08-03-2025 04:55:53","Casca=
ded Incident from TTO4579703","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Site went down because Power cable has bee=
n stolen on Site (power cable between the PWC and the DC-box ) // He replac=
ed the power cable between the DC-Box and PWC","system","288231","08-03-202=
5 01:28:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_070","NOCINC0004519049","Efoulan"=
,"IHS_YND_155","08-03-2025 01:28:31","08-03-2025 00:01:53","08-03-2025 00:0=
1:54","	Active: no power issue, site is ongrid with Ubaie=3D53V, TX Fme Bri=
ce Tsague of huawei is informed","MINKA NICOLAS","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Active: no po=
wer issue, site is ongrid with Ubaie=3D53V, TX Fme Brice Tsague of huawei i=
s informed","system","5198","08-03-2025 01:28:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0004519052","Obobogo"=
,"","08-03-2025 01:28:31","08-03-2025 00:01:53","08-03-2025 00:01:54","Casc=
aded Incident from TTO4579703","MINKA NICOLAS","Cascade Outage","Active","C=
ascade Active","Cascade Active","	Active: no power issue, site is ongrid wi=
th Ubaie=3D53V, TX Fme Brice Tsague of huawei is informed","system","273753=
","08-03-2025 01:28:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0004518911","Y=
ona Hotel","","08-03-2025 01:01:46","08-03-2025 00:57:55","08-03-2025 09:23=
:38","Access issue during the night fme will be reach Site went down becaus=
e Grid contactor, Gen battery and CB(60A) faulty due to Grid bad voltage //=
 he bypass it and Gen manually started","TIENTCHEU NZETCHIEU GAEL","Access =
Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lor=
d","Access issue during the night fme will be reach Site went down because =
Grid contactor, Gen battery and CB(60A) faulty due to Grid bad voltage // h=
e bypass it and Gen manually started","danick.tchakouani@sagemcom.com","232=
","08-03-2025 01:01:46","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004518891","Nsi=
meyong Shell","","08-03-2025 00:50:52","08-03-2025 00:48:46","08-03-2025 03=
:20:46","Site went down because Power cable has been stolen on Site (power =
cable between the PWC and the DC-box ) // He replaced the power cable betwe=
en the DC-Box and PWC","MINKA NICOLAS","Site Asset Theft","Theft","Theft","=
DC Cable Stolen","Site went down because Power cable has been stolen on Sit=
e (power cable between the PWC and the DC-box ) // He replaced the power ca=
ble between the DC-Box and PWC","danick.tchakouani@sagemcom.com","127","08-=
03-2025 00:50:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0004518736","N=
GONA","","08-03-2025 00:25:05","08-03-2025 00:16:59","08-03-2025 01:44:59",=
"Site went down because the site was vandalized // We fixe the Cable: Site =
on grid","Mba Lazare Herve","Site Intrusion","Intrusion On Site","Intrusion=
 On Site","Intrusion - Vandalism/Sabotage","Site went down because the site=
 was vandalized // We fixe the Cable: Site on grid","danick.tchakouani@sage=
mcom.com","487","08-03-2025 00:25:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004518631","S=
hell-Nsimeyong","IHS_YND_505, IHS_YND_071","08-03-2025 00:03:59","08-03-202=
5 00:01:53","08-03-2025 04:55:53","Site went down because Power cable has b=
een stolen on Site (power cable between the PWC and the DC-box ) // He repl=
aced the power cable between the DC-Box and PWC","MINKA NICOLAS","Site Asse=
t Theft","Theft","Theft","DC Cable Stolen","Site went down because Power ca=
ble has been stolen on Site (power cable between the PWC and the DC-box ) /=
/ He replaced the power cable between the DC-Box and PWC","danick.tchakouan=
i@sagemcom.com","127","08-03-2025 00:03:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004518598","Donga","=
","07-03-2025 23:55:22","07-03-2025 23:36:49","07-03-2025 23:36:50","Cascad=
ed Incident from TTO4579619","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active: No power issue, site on battery With=
 Ubaie=3D50.5V, The Tx FME Gregoire (654547479) from Huawei is informed","s=
ystem","275164","07-03-2025 23:55:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0004518593","Nguila",=
"","07-03-2025 23:55:21","07-03-2025 23:36:49","07-03-2025 23:36:50","Casca=
ded Incident from TTO4579619","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active: No power issue, site on battery Wit=
h Ubaie=3D50.5V, The Tx FME Gregoire (654547479) from Huawei is informed","=
system","275165","07-03-2025 23:55:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004518562","D=
ong","IHS_YND_433, IHS_YND_592, IHS_YND_431, IHS_YND_443, IHS_YND_432, IHS_=
YND_434, IHS_YND_402","07-03-2025 23:44:56","07-03-2025 23:36:49","07-03-20=
25 23:36:50","Active: No power issue, site on battery With Ubaie=3D50.5V, T=
he Tx FME Gregoire (654547479) from Huawei is informed","Parker Tchoup","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active: No power issue, site on battery With Ubaie=3D50.5V, The Tx=
 FME Gregoire (654547479) from Huawei is informed","danick.tchakouani@sagem=
com.com","488","07-03-2025 23:44:56","Sagemcom CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004518429","Efo=
ulan MTN","","07-03-2025 23:28:10","07-03-2025 23:23:03","08-03-2025 00:51:=
53","Grid outage, Site went down because Gen failed to start due to Kick st=
arter faulty// He started Gen manualy with external Kick started","MINKA NI=
COLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid =
outage, Site went down because Gen failed to start due to Kick starter faul=
ty// He started Gen manualy with external Kick started","ludovic-anselme.mo=
uliom-mapoure@sagemcom","307","07-03-2025 23:28:10","Sagemcom CMR"
"Cancelled","Warning","T1366","IHS_YND_804","NOCINC0004518405","BEATITUDE E=
NTR=C9E PAVE","","07-03-2025 23:21:29","","","Error","TIENTCHEU NZETCHIEU G=
AEL","","","","","","ludovic-anselme.mouliom-mapoure@sagemcom","488","07-03=
-2025 23:21:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004518285","M=
efou-Assi","","07-03-2025 22:55:06","07-03-2025 22:50:49","08-03-2025 04:56=
:14","Active// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME=
 Fulbert(654266068) of huawei is informed","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME Fulbert(654=
266068) of huawei is informed","danick.tchakouani@sagemcom.com","259","07-0=
3-2025 22:55:06","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004518140","Beh=
ind P T school Yde","","07-03-2025 22:29:59","07-03-2025 22:23:52","08-03-2=
025 00:25:15","	Grid outage, site went down because gen failed to start due=
 to gen card faulty //Gen manually started","Paul BIBOUM","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down =
because gen failed to start due to gen card faulty // Gen manually started"=
,"danick.tchakouani@sagemcom.com","368","07-03-2025 22:29:59","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004517792","M=
ini-Ferme","","07-03-2025 21:34:17","07-03-2025 21:32:03","07-03-2025 21:55=
:00","Grid outage.no space to deploy mobile gen// grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no s=
pace to deploy mobile gen// grid return","ferot.nongni-djiogap@sagemcom.com=
","135","07-03-2025 21:34:17","Sagemcom CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0004517672","Ese=
ka Town","","07-03-2025 21:14:18","07-03-2025 21:02:02","07-03-2025 23:41:0=
2","Grid outage, Site went down because Gen start and stopped with ""High t=
emps ""alarm // he added water and manually start the Gen","Kemeni Franklin=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid outage, Site went down because Gen start and stopped w=
ith ""High temps ""alarm // he added water and manually start the Gen","fer=
ot.nongni-djiogap@sagemcom.com","813","07-03-2025 21:14:18","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004517655","Mfo=
u EPC","","07-03-2025 21:10:52","07-03-2025 21:05:43","07-03-2025 21:42:49"=
,"Active//No power issue on site, Site on Grid UBAIE=3D51.4V and Geoges (69=
7461814) From huawei is informed","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site, Site on Grid UBAIE=3D51.4V and Geoges (697461814) Fro=
m huawei is informed","ferot.nongni-djiogap@sagemcom.com","310","07-03-2025=
 21:10:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004517478","M=
efou-Assi","","07-03-2025 20:47:06","07-03-2025 20:42:01","07-03-2025 20:50=
:15","Active// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME=
 Fulbert(654266068) of huawei is informed","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME Fulbert(654=
266068) of huawei is informed","cedric.tiani@sagemcom.com","306","07-03-202=
5 20:47:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004517469","N=
yom OCM","","07-03-2025 20:45:28","07-03-2025 20:39:15","07-03-2025 21:30:1=
5","Site went down because gen fails to start due to grid bad voltage // He=
 bypass grid and manually start the gen, But the site remained down Power i=
ssue resolved at 09h30 PM FME TX Symphorien/675295205 ","Fabrice Pouakam","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Si=
te went down because gen fails to start due to grid bad voltage // He bypas=
s grid and manually start the gen, But the site remained down Power issue r=
esolved at 09h30 PM FME TX Symphorien/675295205 From huawei is informed","c=
edric.tiani@sagemcom.com","374","07-03-2025 20:45:28","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0004517452","Nko=
abang Ebolmedjock","","07-03-2025 20:41:19","07-03-2025 20:36:27","08-03-20=
25 00:14:16","Site went down because Gen failed to start due to CB Gen (32A=
) tripped // He rearmed CB and site on gen(Investigation ongoing)","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","S=
ite went down because Gen failed to start due to CB Gen (32A) tripped // He=
 rearmed CB and site on gen(Investigation ongoing)","cedric.tiani@sagemcom.=
com","293","07-03-2025 20:41:19","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004517358","An-=
Marche-Melen","","07-03-2025 20:27:06","07-03-2025 20:26:57","07-03-2025 23=
:09:57","Grid outage, No space to to deploy MDG // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No=
 space to to deploy MDG // Grid return","ferot.nongni-djiogap@sagemcom.com"=
,"10","07-03-2025 20:27:06","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004517355","Tou=
ring Club International","","07-03-2025 20:26:21","07-03-2025 20:25:12","07=
-03-2025 20:27:34","Ubiae=3D51,3 V,Site on Grid TX FME Lionel Steeve 655184=
876 of Huawei is informed and uptime 20:27:29 PM","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Ubiae=3D51,3 V,Site on Gr=
id
TX FME Lionel Steeve 655184876 of Huawei is informed and uptime 20:27:29 PM
","ferot.nongni-djiogap@sagemcom.com","70","07-03-2025 20:26:21","Sagemcom =
CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004517252","SOA=
 TOWN","","07-03-2025 20:08:57","07-03-2025 19:42:00","07-03-2025 20:26:51"=
,"Grid outage.gen failed to, start due to, ""high temp"" alarm// We add wat=
er and gen manually started ","Siligap Boris","Equipment Repair","Passive",=
"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.gen=
 failed to, start due to, ""high temp"" alarm// We add water and gen manual=
ly started ","wilfried.kameni@sagemcom.com","1654","07-03-2025 20:08:57","S=
agemcom CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0004517205","Mam=
ch Building","","07-03-2025 20:03:08","07-03-2025 19:47:40","07-03-2025 21:=
02:57","Grid outage,Site went down because Gen failed to start due to no au=
tomatism on site//He started the Gen manually","Mboua Thierry","Equipment R=
epair","Passive","Control Panel","ATS-AMF Issue","Grid outage,Site went dow=
n because Gen failed to start due to no automatism on site//He started the =
Gen manually","wilfried.kameni@sagemcom.com","929","07-03-2025 20:03:08","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004517180","N=
kolo II New","","07-03-2025 19:58:36","07-03-2025 19:19:35","07-03-2025 21:=
24:07","Grid outage, Site went down because Gen failed to start due to PWC =
dysfunctionning// He reset PWC, Site on Grid","Mba Lazare Herve","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, Site wen=
t down because Gen failed to start due to PWC dysfunctionning// He reset PW=
C, Site on Grid","wilfried.kameni@sagemcom.com","46799","07-03-2025 19:58:3=
6","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004517156","M=
imboman-Village","IHS_YND_709","07-03-2025 19:54:46","07-03-2025 19:19:35",=
"07-03-2025 21:24:07","Grid outage, site went down because gen failed to st=
art due to Pwc ZTE dysfunction// he reset it and started Gen manualy","Mba =
Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module Ov=
erloaded","Grid outage, site went down because gen failed to start due to P=
wc ZTE dysfunction// he reset it and started Gen manualy","cedric.tiani@sag=
emcom.com","2112","07-03-2025 19:54:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004517090","MONTEE N=
KONDENGUI","","07-03-2025 19:48:20","07-03-2025 19:42:41","07-03-2025 19:42=
:42","Cascaded Incident from TTO4577898","Albran Byorel","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site , site on=
 Grid with Ubaie=3D54.2 V. The Tx FME Eloundou //693212405 of Huawei is inf=
ormed","system","296473","07-03-2025 19:48:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004517081","M=
obil-Kondengui","IHS_YND_682","07-03-2025 19:47:54","07-03-2025 19:42:41","=
08-03-2025 04:52:12","No power issue on site , site on Grid with Ubaie=3D54=
.2 V. The Tx FME Eloundou //693212405 of Huawei is informed","","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site , site on Grid with Ubaie=3D54.2 V. The Tx FME Elou=
ndou //693212405 of Huawei is informed","cedric.tiani@sagemcom.com","314","=
07-03-2025 19:47:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004516980","V=
allee-Bastos OCM","","07-03-2025 19:33:28","07-03-2025 19:25:16","07-03-202=
5 22:46:15","Grid outage, No space to deploy MDG // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Over Voltage","Grid outage, N=
o space to deploy MDG // Grid return","cedric.tiani@sagemcom.com","493","07=
-03-2025 19:33:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0004516713","B=
ondjock","","07-03-2025 18:49:09","07-03-2025 18:40:53","07-03-2025 19:09:3=
9","Site went down due to Cb(32A) disjuncted in TGBT // He reamed cb(32A), =
site on grid","Fanda Brice","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Circuit Breaker Issue","Site went down due to Cb(32A) disjun=
cted in TGBT // He reamed cb(32A), site on grid","cedric.tiani@sagemcom.com=
","497","07-03-2025 18:49:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0004516439","A=
n-Marche-Melen","","07-03-2025 18:07:53","07-03-2025 18:05:41","07-03-2025 =
18:57:22","Grid outage, No space to to deploy MDG // Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
No space to to deploy MDG // Grid return","cedric.tiani@sagemcom.com","133"=
,"07-03-2025 18:07:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004516138","S=
tade-Abega","","07-03-2025 17:47:39","07-03-2025 16:47:31","07-03-2025 17:4=
0:50","Grid outage, site went down because gen failed to start due to PWC Z=
TE malfunction // He resert the controller, grid return","Mba Lazare Herve"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage, site went down because gen failed to start due to PWC ZTE malfun=
ction // He resert the controller, grid return","ferot.nongni-djiogap@sagem=
com.com","3609","07-03-2025 17:47:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004515978","S=
hell-Nsimeyong","","07-03-2025 17:40:47","07-03-2025 17:37:13","07-03-2025 =
17:45:59","No power issue U =3D52.2 V site on Grid. The FME TX Mbah Hosiah =
(674007438/699699694) from Huawei is informed. Repetitive Issue","MINKA NIC=
OLAS","Customer Equipment Failure","Active","Active Equipment Failure","Aff=
ected by 3rd Party Site","No power issue U =3D52.2 V site on Grid. The FME =
TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitive Is=
sue","cedric.tiani@sagemcom.com","215","07-03-2025 17:40:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004515972","MONTEE N=
KONDENGUI","","07-03-2025 17:40:01","07-03-2025 15:52:34","07-03-2025 15:57=
:35","Cascaded Incident from TTO4575538","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage // Grid return","=
system","274396","07-03-2025 17:40:01","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0004515567","Nko=
mo stade","","07-03-2025 17:06:06","07-03-2025 16:59:46","07-03-2025 17:41:=
56","Grid outage, site went down because gen stopped with alarm ""high temp=
"" // He added water and manually start the Gen	","Mba Lazare Herve","Equip=
ment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level =
Issue","Grid outage, site went down because gen stopped with alarm ""high t=
emp"" // He added water and manually start the Gen	","ferot.nongni-djiogap@=
sagemcom.com","381","07-03-2025 17:06:06","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004515529","Mam=
bine","","07-03-2025 17:00:00","07-03-2025 16:49:54","07-03-2025 17:32:40",=
"	Grid outage site went down because Gen failed to start due to Hybride sys=
tem dysfonction // He reset the hybrid system and Gen manually started","Fa=
nda Brice","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","	G=
rid outage site went down because Gen failed to start due to Hybride system=
 dysfonction // He reset the hybrid system and Gen manually started","ferot=
.nongni-djiogap@sagemcom.com","693","07-03-2025 17:00:00","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004515483","Awa=
e Ewonkan","","07-03-2025 16:51:00","07-03-2025 16:48:48","07-03-2025 18:52=
:55","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went do=
wn because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // He=
 reduced the load","ferot.nongni-djiogap@sagemcom.com","133","07-03-2025 16=
:51:00","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004515470","AWA=
E OCM","","07-03-2025 16:47:14","07-03-2025 16:37:50","07-03-2025 16:49:30"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen automatically started","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen automatically started"=
,"ferot.nongni-djiogap@sagemcom.com","1049","07-03-2025 16:47:14","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004515378","E=
kombitie","","07-03-2025 16:32:07","07-03-2025 16:24:40","07-03-2025 16:41:=
44","Grid fluctuations, site went down because Gen failed to start due to g=
rid bad voltage // He bypassed the grid and started Gen manually","Fabrice =
Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuations, site went down because Gen failed to start due t=
o grid bad voltage // He bypassed the grid and started Gen manually","cedri=
c.tiani@sagemcom.com","448","07-03-2025 16:32:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004515182","V=
allee-Bastos OCM","","07-03-2025 16:11:05","07-03-2025 15:35:38","07-03-202=
5 19:09:02","Grid outage, no space to deploy a mobil gen // grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy a mobil gen // grid return","cedric.tiani@sagemco=
m.com","2128","07-03-2025 16:11:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0004515173","N=
sam Sofavinc T0","","07-03-2025 16:09:17","07-03-2025 15:44:02","07-03-2025=
 16:14:19","Site went down because gen failed to start due to grid bad volt=
age and no RCP// Gen manually started","MINKA NICOLAS","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Site went down becaus=
e gen failed to start due to grid bad voltage and no RCP// Gen manually sta=
rted","cedric.tiani@sagemcom.com","1516","07-03-2025 16:09:17","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004514992","M=
obil-Kondengui","IHS_YND_682","07-03-2025 15:54:44","07-03-2025 15:52:34","=
07-03-2025 15:57:35","Grid outage // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage // Grid return","=
kouoh.jean@ihstowers.com","131","07-03-2025 15:54:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0004514878","E=
mombo 2","","07-03-2025 15:47:16","07-03-2025 15:45:04","07-03-2025 17:50:4=
8","Active // No power issue site on Grid with U=3D54,7 V Tx Fme Henri(6911=
45055) of huawei is informed","MINKA NICOLAS","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No powe=
r issue site on Grid with U=3D54,7 V Tx Fme Henri(691145055) of huawei is i=
nformed","cedric.tiani@sagemcom.com","133","07-03-2025 15:47:16","Sagemcom =
CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004514389","SAA=
 Entrance","","07-03-2025 15:12:42","07-03-2025 15:08:55","07-03-2025 15:12=
:42","No power issue, site is on Gen with Ubaie=3D53V, Charly/656097386/Tel=
is working on site","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on =
Gen with Ubaie=3D53V, Charly/656097386/Telis working on site","cedric.tiani=
@sagemcom.com","228","07-03-2025 15:12:42","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004514041","Mel=
en Ba'aba","","07-03-2025 14:56:03","07-03-2025 14:52:55","07-03-2025 15:50=
:21"," Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME J=
ulien(693095849) from Huawei is informed ","Siligap Boris","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," Act=
ive// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Julien(6930=
95849) from Huawei is informed ","ferot.nongni-djiogap@sagemcom.com","189",=
"07-03-2025 14:56:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004513629","Carrefou=
r Ayissi Ele","","07-03-2025 14:43:42","07-03-2025 14:33:55","07-03-2025 15=
:12:17","Cascaded Incident from TTO4574027","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n because gen start and stopped with alarm overcurrent // He reset gen card=
 and gen manually started","system","587","07-03-2025 14:43:42","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004513630","Saa","",=
"07-03-2025 14:43:42","07-03-2025 14:33:55","07-03-2025 15:12:17","Cascaded=
 Incident from TTO4574027","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen sta=
rt and stopped with alarm overcurrent // He reset gen card and gen manually=
 started","system","587","07-03-2025 14:43:42","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004513614","SAA=
 2","IHS_YND_810, IHS_YND_405","07-03-2025 14:42:00","07-03-2025 14:33:55",=
"07-03-2025 15:12:17","Grid outage, site went down because gen start and st=
opped with alarm overcurrent // He reset gen card and gen manually started"=
,"Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, site went down because gen start and stopped with alarm =
overcurrent // He reset gen card and gen manually started","wilfried.kameni=
@sagemcom.com","487","07-03-2025 14:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_113","NOCINC0004513504","Emombo 2=
","","07-03-2025 14:26:50","07-03-2025 13:57:56","07-03-2025 14:27:01","Cas=
caded Incident from TTO4573732","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// No power issue, site is on GRID =
with U=3D54.3 V.  The TX FME  Lionel Adjep (655184876) from Huawei is worki=
ng on site.","system","266947","07-03-2025 14:26:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_680","NOCINC0004513503","MIMBOMAN=
 LIBERTE","","07-03-2025 14:26:50","07-03-2025 13:57:56","07-03-2025 14:27:=
01","Cascaded Incident from TTO4573732","Mba Lazare Herve","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active// No power issue, site =
is on GRID with U=3D54.3 V.  The TX FME  Lionel Adjep (655184876) from Huaw=
ei is working on site.","system","266948","07-03-2025 14:26:50","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0004513358","NGONA","=
","07-03-2025 14:08:30","07-03-2025 13:57:56","07-03-2025 14:27:01","Cascad=
ed Incident from TTO4573732","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// No power issue, site is on GRID =
with U=3D54.3 V.  The TX FME  Lionel Adjep (655184876) from Huawei is worki=
ng on site.","system","266948","07-03-2025 14:08:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0004513359","Nkoabang=
2","","07-03-2025 14:08:30","07-03-2025 13:57:56","07-03-2025 14:27:01","Ca=
scaded Incident from TTO4573732","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active// No power issue, site is on G=
RID with U=3D54.3 V.  The TX FME  Lionel Adjep (655184876) from Huawei is w=
orking on site.","system","266948","07-03-2025 14:08:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0004513351","N=
koabang","IHS_YND_295, IHS_YND_526, IHS_YND_680, IHS_YND_113","07-03-2025 1=
4:07:03","07-03-2025 13:57:56","07-03-2025 14:27:01","Active// No power iss=
ue, site is on GRID with U=3D54.3 V.  The TX FME  Lionel Adjep (655184876) =
from Huawei is working on site.","Mba Lazare Herve","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No=
 power issue, site is on GRID with U=3D54.3 V.  The TX FME  Lionel Adjep (6=
55184876) from Huawei is working on site.","wilfried.kameni@sagemcom.com","=
548","07-03-2025 14:07:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0004513338","E=
SSOS OASIS 1111","","07-03-2025 14:05:50","07-03-2025 13:57:43","07-03-2025=
 14:00:19","ACTIVE No power issue on site, site on Grid with Ubaie=3D53.2 V=
 Tx fme Armand Nguetsa /699949553/ from Huawei is informed","Siligap Boris"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","ACTIVE No power issue on site, site on Grid with Ubaie=3D53.2 =
V Tx fme Armand Nguetsa /699949553/ from Huawei is informed","wilfried.kame=
ni@sagemcom.com","488","07-03-2025 14:05:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004513146","B=
ATA Mokolo OCM","","07-03-2025 13:26:01","07-03-2025 12:56:54","07-03-2025 =
13:31:56","	Grid outage, No space to deploy MDG // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","	Grid outage, N=
o space to deploy MDG // Grid return","wilfried.kameni@sagemcom.com","1748"=
,"07-03-2025 13:26:01","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_051","NOCINC0004512955","Mamch Building",=
"","07-03-2025 12:58:20","","","Cascaded Incident from TTO4573025","Mboua T=
hierry","","","","","","system","2191","07-03-2025 12:58:20","Sagemcom CMR"
"Closed Complete","Site Down","T0573","IHS_YND_387","NOCINC0004512833","Tal=
la Monatele","","07-03-2025 12:41:48","07-03-2025 12:30:37","07-03-2025 12:=
36:55","Active: no power issue, site is on grid with Ubaie=3D53V, Gregoir (=
654547479) from Huawei working on site","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active:=
 no power issue, site is on grid with Ubaie=3D53V, Gregoir (654547479) from=
 Huawei working on site","wilfried.kameni@sagemcom.com","672","07-03-2025 1=
2:41:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004512807","Minka","=
","07-03-2025 12:36:22","07-03-2025 11:29:49","07-03-2025 11:43:49","Cascad=
ed Incident from TTO4573067 - Cascade Removed From TTO4573067","Fanda Brice=
","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Site went=
 down due to work:Brice Fanda // 657108549 from Sagemcom working on site (P=
M)// End of work","system","282740","07-03-2025 12:36:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004512806","Mbeng","=
","07-03-2025 12:36:21","07-03-2025 11:29:49","07-03-2025 11:43:49","Cascad=
ed Incident from TTO4573067 - Cascade Removed From TTO4573067","Fanda Brice=
","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Site went=
 down due to work:Brice Fanda // 657108549 from Sagemcom working on site (P=
M)// End of work","system","282740","07-03-2025 12:36:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004512805","Mom","IH=
S_YND_369, IHS_YND_371, IHS_YND_372","07-03-2025 12:36:21","07-03-2025 11:2=
9:49","07-03-2025 11:43:49","Site went down due to work:Brice Fanda // 6571=
08549 from Sagemcom working on site (PM)// End of work","Fanda Brice","Inst=
allation Activity","Passive","Planned Activity","Installation Activity","Si=
te went down due to work:Brice Fanda // 657108549 from Sagemcom working on =
site (PM)// End of work","system","3992","07-03-2025 12:36:21","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0004512787","B=
ondjock","","07-03-2025 12:34:08","07-03-2025 11:29:49","07-03-2025 11:43:4=
9","Site went down due to work:Brice Fanda // 657108549 from Sagemcom worki=
ng on site (PM)// End of work","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to work:Brice Fanda //=
 657108549 from Sagemcom working on site (PM)// End of work","wilfried.kame=
ni@sagemcom.com","282740","07-03-2025 12:34:08","Sagemcom CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004512755","Cha=
rles-Atangana","IHS_YND_051","07-03-2025 12:27:08","07-03-2025 12:21:49","0=
7-03-2025 13:29:17","Grid Outage, No free MDG to deploy // Grid Restored","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
Outage, No free MDG to deploy // Grid Restored","wilfried.kameni@sagemcom.c=
om","321","07-03-2025 12:27:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004512576","E=
mana Lycee","","07-03-2025 11:50:03","07-03-2025 11:39:11","07-03-2025 12:2=
4:17","Grid outage, site went down because gen start and stopped with alarm=
 ""high temp"" // he added water and manually start the Gen","Fabrice Pouak=
am","Cascade Outage","Active","Cascade Active","Cascade Active","Grid outag=
e, site went down because gen start and stopped with alarm ""high temp"" //=
 he added water and manually start the Gen","wilfried.kameni@sagemcom.com",=
"275189","07-03-2025 11:50:03","Sagemcom CMR"
"Closed Complete","Warning","T0123","IHS_YND_013","NOCINC0004512561","Labor=
atoire T.Bella","","07-03-2025 11:48:41","","","Grid Outage,//Grid restored=
","Paul BIBOUM","Warning","Warning","POWER","Warning - Site on Battery","Gr=
id Outage,//Grid restored","ferot.nongni-djiogap@sagemcom.com","1332","07-0=
3-2025 11:48:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004512557","E=
mana lycee 2","IHS_YND_274","07-03-2025 11:48:24","07-03-2025 11:39:11","07=
-03-2025 12:24:17","Grid outage, site went down because gen start and stopp=
ed with alarm ""high temp"" // he added water and manually start the Gen","=
Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engin=
e Temp - Coolant Level Issue","Grid outage, site went down because gen star=
t and stopped with alarm ""high temp"" // he added water and manually start=
 the Gen","wilfried.kameni@sagemcom.com","554","07-03-2025 11:48:24","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004512342","S=
hell-Nsimeyong","","07-03-2025 11:17:50","07-03-2025 11:13:38","07-03-2025 =
11:20:42","No power issue U =3D52.2V site on Grid.  The FME TX Mbah Hosiah =
(674007438/699699694) from Huawei is informed. Repetitive Issue","MINKA NIC=
OLAS","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue U =3D52.2V site on Grid. The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","wil=
fried.kameni@sagemcom.com","254","07-03-2025 11:17:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0004512336","M=
volye-New","","07-03-2025 11:16:56","07-03-2025 10:58:44","07-03-2025 11:10=
:03","No power issue on site,site on Grid with Ubaie=3D51.6 V  The Tx Fme M=
bah hosiah(674007438) from Huawei is informed","","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site,site on Grid with Ubaie=3D51.6 V The Tx Fme Mbah hosiah(674007438=
) from Huawei is informed
","wilfried.kameni@sagemcom.com","1094","07-03-2025 11:16:56","Sagemcom CMR=
"
"Closed Complete","Warning","T0712","IHS_YND_319","NOCINC0004512240","SOA 2=
","","07-03-2025 11:00:01","","","unpruven alarm","Siligap Boris","Warning"=
,"Warning","POWER","Warning - Site on Battery","unpruven alarm","ferot.nong=
ni-djiogap@sagemcom.com","2242","07-03-2025 11:00:01","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004512223","Awa=
e Escalier","","07-03-2025 10:58:04","07-03-2025 10:55:56","07-03-2025 13:0=
5:45","Site went down because gen failed to start due to grid bad voltage /=
/ Gen manually started","Albran Byorel","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","Site went down because gen failed to=
 start due to grid bad voltage // Gen manually started","wilfried.kameni@sa=
gemcom.com","129","07-03-2025 10:58:04","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004512118","AWA=
E OCM","","07-03-2025 10:45:35","07-03-2025 10:40:23","07-03-2025 11:06:37"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automatically","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automatically
","wilfried.kameni@sagemcom.com","313","07-03-2025 10:45:35","Sagemcom CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0004512020","Mam=
ch Building","","07-03-2025 10:32:49","07-03-2025 09:59:24","07-03-2025 11:=
05:33","Grid outage, site went down because gen failed to start due to Grid=
 contactor faulty // He bypass the Grid contactor and Gen manually started"=
,"Mboua Thierry","Equipment Repair","Passive","Control Panel","ATS-AMF Issu=
e","Grid outage, site went down because gen failed to start due to Grid con=
tactor faulty // He bypass the Grid contactor and Gen manually started","wi=
lfried.kameni@sagemcom.com","8955","07-03-2025 10:32:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004511806","M=
efou-Assi","","07-03-2025 10:08:31","07-03-2025 10:04:27","07-03-2025 10:09=
:46","ACTIVE//No power issue on site GRID , Ubaie=3D54.3V site On Grid The =
Tx FME Fulbert(654266068) from Huawei is informed. Repetitive issue","Fanda=
 Brice","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D54.3V sit=
e On Grid The Tx FME Fulbert(654266068) from Huawei is informed. Repetitive=
 issue","wilfried.kameni@sagemcom.com","245","07-03-2025 10:08:31","Sagemco=
m CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004511786","Nko=
g-Edzen","","07-03-2025 10:03:18","07-03-2025 09:52:08","07-03-2025 10:10:5=
7","No power issue on site, site on Gen  The Team aubin (694427963 ) from I=
-ENG  is Working on site","Parker Tchoup","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e, site on Gen The Team aubin (694427963 ) from I-ENG  is Working on site",=
"wilfried.kameni@sagemcom.com","671","07-03-2025 10:03:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004511627","B=
ATA Mokolo OCM","","07-03-2025 09:51:37","07-03-2025 09:41:31","07-03-2025 =
11:35:49","Grid outage, No space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No =
space to deploy MDG // Grid return","wilfried.kameni@sagemcom.com","607","0=
7-03-2025 09:51:37","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004511604","NKO=
LMEKONG YDE","","07-03-2025 09:50:00","07-03-2025 09:42:50","07-03-2025 11:=
30:15","Site went down Because the PWC and rectifier dysfonction // He rese=
t the rectifier and Grid power return","Fabrice Pouakam","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Site went down Becaus=
e the PWC and rectifier dysfonction // He reset the rectifier and Grid powe=
r return","wilfried.kameni@sagemcom.com","432","07-03-2025 09:50:00","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004511039","S=
atcom","","07-03-2025 09:03:03","07-03-2025 08:59:41","07-03-2025 09:00:26"=
,"No power issue site on Grid with U=3D50,06 V.The Tx Fme Armand Ngestsa (6=
91144412) of Huawei is informed","Delor Telezing","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e site on Grid with U=3D50,06 V.The Tx Fme Armand Ngestsa (691144412) of Hu=
awei is informed","wilfried.kameni@sagemcom.com","203","07-03-2025 09:03:03=
","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004510946","Elo=
umdem stade","","07-03-2025 08:51:45","07-03-2025 08:50:27","07-03-2025 09:=
10:17","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage No crcp // He bypassed the grid and started Gen manually"=
,"Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, site went down because Gen failed to start =
due to grid bad voltage No crcp // He bypassed the grid and started Gen man=
ually
","wilfried.kameni@sagemcom.com","79","07-03-2025 08:51:45","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004510896","Nko=
ulou Carriere carrefourt","","07-03-2025 08:39:14","07-03-2025 08:30:50","0=
7-03-2025 08:58:26","Site went down because gen  overload (13Kw, 180A) SS I=
HS Alphonse DEFFO is informed// he Reduice the Load and Site is on Gen","Mb=
a Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Site went down because gen  overload (13Kw, 180A) SS IHS Alphonse DEFFO is =
informed// he Reduice the Load and Site is on Gen","wilfried.kameni@sagemco=
m.com","505","07-03-2025 08:39:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0004510810","M=
VAN SACEL","","07-03-2025 08:11:53","07-03-2025 07:59:40","07-03-2025 08:00=
:22","No power issue on site Ubaie =3D54.6V site on Grid  The TX FME Martia=
l //690087047  from huawei is informed. notice that dysjunction at ocm equi=
pment","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue on site Ubaie =3D54.6V si=
te on Grid The TX FME Martial //690087047  from huawei is informed. notice =
that dysjunction at ocm equipment","wilfried.kameni@sagemcom.com","734","07=
-03-2025 08:11:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004510577","ELOUMDEM=
 CARRIERE 2","","07-03-2025 07:19:30","07-03-2025 07:16:21","07-03-2025 08:=
18:00","Cascaded Incident from TTO4570532","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen ran untill fuel shortage // Refuelling done","system","276539","=
07-03-2025 07:19:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004510576","Eto koss=
 Yde","","07-03-2025 07:19:30","07-03-2025 07:16:21","07-03-2025 08:18:00",=
"Cascaded Incident from TTO4570532","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen ran untill fuel shortage // Refuelling done","system","276538","07-03-2=
025 07:19:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004510566","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","07-03-2025 07:17:42","07-03-2025 07:14=
:21","07-03-2025 08:31:36","Grid outage, site went down because gen ran unt=
ill fuel shortage // Refuelling done","Fanda Brice","Fuel Outage","Passive"=
,"Diesel","Diesel Outage","Grid outage, site went down because gen ran unti=
ll fuel shortage // Refuelling done","wilfried.kameni@sagemcom.com","269","=
07-03-2025 07:17:42","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004510502","Mam=
bine","","07-03-2025 07:10:20","07-03-2025 07:04:54","07-03-2025 07:38:15",=
"Grid outage site went down because Gen failed to start due to Hybride syst=
em dysfonction // He reset the hybrid system and Gen manually started","Fan=
da Brice","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid outag=
e site went down because Gen failed to start due to Hybride system dysfonct=
ion // He reset the hybrid system and Gen manually started","wilfried.kamen=
i@sagemcom.com","386","07-03-2025 07:10:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004510453","S=
hell-Nsimeyong","","07-03-2025 07:00:01","07-03-2025 06:57:56","07-03-2025 =
07:01:04","No power issue U =3D52.2 V site on Grid. The FME TX Mbah Hosiah =
(674007438/699699694) from Huawei is informed. Repetitive Issue","MINKA NIC=
OLAS","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue U =3D52.2 V site on Grid. The FME TX Mbah =
Hosiah (674007438/699699694) from Huawei is informed. Repetitive Issue","yv=
es.djomo@sagemcom.com","126","07-03-2025 07:00:01","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004510385","Crf=
-Nsam","","07-03-2025 06:51:32","07-03-2025 06:50:24","07-03-2025 07:03:24"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline conf=
irmed // He reset PWC","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Site went down because PWC(24kilo) dysf=
unctionning, IHS SS Pascaline confirmed // He reset PWC","yves.djomo@sagemc=
om.com","69","07-03-2025 06:51:32","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004510123","Nom=
ayos montee Meche","","07-03-2025 06:11:40","07-03-2025 06:03:27","07-03-20=
25 08:37:57","Grid outage site went down because Gen failed to start due to=
 pipe return pierced // he did the standardization on site","Fanda Brice","=
Fuel Outage (Probable)","Passive","Diesel","Fuel Line Issue","Grid outage s=
ite went down because Gen failed to start due to pipe return pierced // he =
did the standardization on site","el-dalile@sagemcom.com","494","07-03-2025=
 06:11:40","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004510114","Bar=
riere","","07-03-2025 06:09:55","07-03-2025 06:03:28","07-03-2025 10:14:46"=
,"site went down because Gen failed to start due to grid bad voltage No crc=
p // He bypassed the grid and started Gen manually","Hyemafo Gildas","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","site we=
nt down because Gen failed to start due to grid bad voltage No crcp // He b=
ypassed the grid and started Gen manually","el-dalile@sagemcom.com","387","=
07-03-2025 06:09:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004510068","O=
LAMA","","07-03-2025 05:57:31","07-03-2025 05:55:26","07-03-2025 05:57:41",=
"Active//No power issue on site Ubaie =3D54.9V site on Gen The TX FME Henri=
 (699949693) from Huawei is informed and up at 05:57 AM","Fanda Brice","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active//No power issue on site Ubaie =3D54.9V site on Gen The TX FM=
E Henri (699949693) from Huawei is informed and up at 05:57 AM","yves.djomo=
@sagemcom.com","125","07-03-2025 05:57:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004509721","M=
efou-Assi","","07-03-2025 03:45:57","07-03-2025 03:42:49","07-03-2025 03:43=
:43","Active// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME=
 Fulbert(654266068) of huawei is informed","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue on site Ubaie=3D54.5V site On Grid The Tx FME Fulbert(654=
266068) of huawei is informed","el-dalile@sagemcom.com","189","07-03-2025 0=
3:45:57","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004509638","Crf=
-Nsam","","07-03-2025 03:01:46","07-03-2025 02:52:35","07-03-2025 03:25:31"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline conf=
irmed // He reset PWC","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Site went down because PWC(24kilo) dysf=
unctionning, IHS SS Pascaline confirmed // He reset PWC","yves.djomo@sagemc=
om.com","552","07-03-2025 03:01:46","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004509540","NYO=
M FACE MAETUR","","07-03-2025 02:18:49","07-03-2025 02:16:45","07-03-2025 0=
3:08:13","Site went down due to 03 Rectifiers faulty caused by heavy rain, =
SS IHS Bernard Atangana confirmed.//Grid return ","Fabrice Pouakam","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site went down due to=
 03 Rectifiers faulty caused by heavy rain, SS IHS Bernard Atangana confirm=
ed.//Grid return ","yves.djomo@sagemcom.com","125","07-03-2025 02:18:49","S=
agemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004509320","Nko=
ulou Carriere carrefourt","","07-03-2025 01:37:10","07-03-2025 01:28:06","0=
7-03-2025 02:43:05","Grid outage, Site went down because Gen failed to star=
t due to gen contactor no excited // He excited gen contactor, site on gen"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Load Co=
ntactor","Grid outage, Site went down because Gen failed to start due to ge=
n contactor no excited // He excited gen contactor, site on gen","yves.djom=
o@sagemcom.com","545","07-03-2025 01:37:10","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004509270","Man=
guiers Dispensaire","","07-03-2025 01:19:31","07-03-2025 01:17:26","07-03-2=
025 01:19:32","Grid outage, site went down because Gen failed to start due =
to Grid contactor faulty // Grid return","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down b=
ecause Gen failed to start due to Grid contactor faulty // Grid return","yv=
es.djomo@sagemcom.com","126","07-03-2025 01:19:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004509059","S=
hell-Nsimeyong","","07-03-2025 00:34:36","07-03-2025 00:33:28","07-03-2025 =
02:59:02","No power issue U =3D52.2 V site on Grid. The FME TX Mbah Hosiah =
(674007438/699699694) from Huawei is informed. Repetitive Issue","MINKA NIC=
OLAS","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue U =3D52.2 V site on Grid. The FME TX Mbah =
Hosiah (674007438/699699694) from Huawei is informed. Repetitive Issue","el=
-dalile@sagemcom.com","69","07-03-2025 00:34:36","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004509038","Crf=
-Mbankolo-IHS","","07-03-2025 00:28:53","07-03-2025 00:26:48","07-03-2025 0=
0:33:20","Site went down due to MPR DYSFONNCTION on site SS IHS Bernard ATA=
NGANA confirmed// He reset MPR","Mboua Thierry","Equipment Repair","Passive=
","Rectifier","Rectifier Cabinet","Site went down due to MPR DYSFONNCTION o=
n site SS IHS Bernard ATANGANA confirmed// He reset MPR","yves.djomo@sagemc=
om.com","126","07-03-2025 00:28:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004508949","Bitoto",=
"","07-03-2025 00:02:00","06-03-2025 23:47:51","07-03-2025 05:38:22","Casca=
ded Incident from TTO4568657","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Fire on site: PWC BURNED","system","2=
81546","07-03-2025 00:02:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004508950","Tradex-N=
komo","","07-03-2025 00:02:00","06-03-2025 23:47:51","07-03-2025 05:38:22",=
"Cascaded Incident from TTO4568657","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Fire on site: PWC BURNED","system"=
,"281547","07-03-2025 00:02:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004508951","Essomba"=
,"","07-03-2025 00:02:00","06-03-2025 23:47:51","07-03-2025 05:38:22","Casc=
aded Incident from TTO4568657","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Fire on site: PWC BURNED","system","=
281547","07-03-2025 00:02:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004508937","B=
iteng","IHS_YND_292, IHS_YND_172, IHS_YND_179","06-03-2025 23:55:55","06-03=
-2025 23:11:51","07-03-2025 05:38:22","Fire on Site: Site went down because=
 Power Cabinet burned ( Rectifiers and cable DC and AC burned)// He replace=
d rectifiers and cables DC and AC (Power cabinet to be normalized)","Mba La=
zare Herve","Fire on Site","Passive","Infrastructure","Fire - Burned","Fire=
 on Site: Site went down because Power Cabinet burned ( Rectifiers and cabl=
e DC and AC burned)// He replaced rectifiers and cables DC and AC (Power ca=
binet to be normalized)","yves.djomo@sagemcom.com","2897","06-03-2025 23:55=
:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004508929","E=
vodoula OCM","","06-03-2025 23:49:40","06-03-2025 23:47:35","07-03-2025 00:=
16:48","Grid outage.site went down due to gen failed to start//Gen manualy =
started (investigation ongoing)","TIENTCHEU NZETCHIEU GAEL","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.site went down=
 due to gen failed to start//Gen manualy started (investigation ongoing)","=
yves.djomo@sagemcom.com","126","06-03-2025 23:49:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004508916","S=
tade-Abega","","06-03-2025 23:44:56","06-03-2025 23:27:52","07-03-2025 00:5=
2:30","Grid outage, site went down Gen failed to start due to PWC ZTE malfu=
nction // Grid return","Mba Lazare Herve","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","Grid outage, site went down Gen fail=
ed to start due to PWC ZTE malfunction // Grid return","yves.djomo@sagemcom=
.com","1025","06-03-2025 23:44:56","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004508774","SIM=
BOCK BONAMBAPE","","06-03-2025 23:09:11","06-03-2025 23:05:02","07-03-2025 =
00:45:48","Grid outage, Site went down because Gen Overload (20kva, 350A) S=
S IHS Felix ZAMBE confirmed// He reduiced load and started Gen manualy","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, Site went down because Gen Overload (20kva, 350A) SS IHS Felix Z=
AMBE confirmed// He reduiced load and started Gen manualy","ludovic-anselme=
.mouliom-mapoure@sagemcom","250","06-03-2025 23:09:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004508752","M=
ontee-Jouvence-II","","06-03-2025 23:02:46","06-03-2025 22:36:31","06-03-20=
25 22:41:32","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed // He reset and started the Gen manually","Hyemafo Gildas=
","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","S=
ite went down due to PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirm=
ed // He reset and started the Gen manually","ludovic-anselme.mouliom-mapou=
re@sagemcom","1577","06-03-2025 23:02:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004508624","M=
essa-Carriere OCM","","06-03-2025 22:33:04","06-03-2025 22:11:52","07-03-20=
25 08:09:36","Grid outage No space to deploy // Grid power return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
No space to deploy // Grid power return","ludovic-anselme.mouliom-mapoure@s=
agemcom","1273","06-03-2025 22:33:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004508469","S=
tade-Abega","","06-03-2025 22:02:29","06-03-2025 21:54:02","06-03-2025 22:3=
1:29","Grid outage, site went down Gen failed to start due to PWC ZTE malfu=
nction // He reset controller and gen manually started","Mba Lazare Herve",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gri=
d outage, site went down Gen failed to start due to PWC ZTE malfunction // =
He reset controller and gen manually started","mariam.tchonang@sagemcom.com=
","508","06-03-2025 22:02:29","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004508421","Awa=
e Ewonkan","","06-03-2025 21:56:23","06-03-2025 21:07:49","06-03-2025 22:53=
:38","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went do=
wn because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // He=
 reduced the load","ludovic-anselme.mouliom-mapoure@sagemcom","2915","06-03=
-2025 21:56:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0004508406","S=
ous Prefecture","","06-03-2025 21:52:09","06-03-2025 17:45:05","06-03-2025 =
17:45:06","ACTIVE//No power issue site on Grid Ubaie =3D53.7 V, The tx Huaw=
ei Fulbert (654266068) is informed","Fanda Brice","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No po=
wer issue site on Grid Ubaie =3D53.7 V, The tx Huawei Fulbert (654266068) i=
s informed","ludovic-anselme.mouliom-mapoure@sagemcom","14825","06-03-2025 =
21:52:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004508387","N=
YOM 2 IHS","","06-03-2025 21:50:19","06-03-2025 21:41:02","06-03-2025 22:40=
:14","Site went down because CB (63*63 A) tripped in PWC who feeds equipmen=
ts OCM//CB put back on","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down because=
 CB (63*63 A) tripped in PWC who feeds equipments OCM//CB put back on","mar=
iam.tchonang@sagemcom.com","558","06-03-2025 21:50:19","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004508300","Bon=
djock","","06-03-2025 21:36:39","06-03-2025 21:25:26","07-03-2025 00:46:37"=
,"Grid bad voltage,and gen failed to start,no rcp // Bypassed grid and star=
ted the gen","Fanda Brice","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","Grid bad voltage,and gen failed to start,no rcp /=
/ Bypassed grid and started the gen","ludovic-anselme.mouliom-mapoure@sagem=
com","674","06-03-2025 21:36:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004508178","B=
iteng-Maetur","","06-03-2025 21:14:55","06-03-2025 21:00:41","06-03-2025 22=
:48:02","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","ludovic=
-anselme.mouliom-mapoure@sagemcom","855","06-03-2025 21:14:55","Sagemcom CM=
R"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004508004","AWA=
E OCM","","06-03-2025 20:48:37","06-03-2025 20:41:27","06-03-2025 22:11:28"=
,"Grid outage, site went down because Gen failed to start due to dysfunctio=
nning of  PWC ZTE // He reset PWC Gen manually started","Mba Lazare Herve",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gri=
d outage, site went down because Gen failed to start due to dysfunctionning=
 of  PWC ZTE // He reset PWC Gen manually started","ludovic-anselme.mouliom=
-mapoure@sagemcom","432","06-03-2025 20:48:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0004507912","N=
komo","","06-03-2025 20:33:39","06-03-2025 17:33:14","06-03-2025 20:14:23",=
"Grid outage, site went down because gen ran untill fuel shortage // Refuel=
ling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran untill fuel shortage // Re=
fuelling done","ludovic-anselme.mouliom-mapoure@sagemcom","10826","06-03-20=
25 20:33:39","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004507902","ELO=
UMDEM CARRIERE","","06-03-2025 20:30:51","06-03-2025 19:35:35","07-03-2025 =
04:30:20","Access issue during the Night Grid outage Site went down because=
 Gen failed to start // Grid power return (Investigation ongoing)","Fanda B=
rice","Access Denial","Lease Or Legal","Landlord Related Issues","Access Is=
sue - Land Lord","Access issue during the Night Grid outage Site went down =
because Gen failed to start // Grid power return (Investigation ongoing)","=
ludovic-anselme.mouliom-mapoure@sagemcom","3317","06-03-2025 20:30:51","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004507886","M=
obil-Kondengui","","06-03-2025 20:28:28","06-03-2025 20:20:03","06-03-2025 =
21:41:30","Grid outage // Grid return","","Grid Supply","Passive","Grid","N=
ational Grid - Grid Outage Issue","Grid outage // Grid return","mariam.tcho=
nang@sagemcom.com","506","06-03-2025 20:28:28","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004507801","Mam=
bine","","06-03-2025 20:08:04","06-03-2025 19:46:00","06-03-2025 20:17:49",=
"Grid outage site went down because Gen failed to start due to hybrid syste=
m dysfunction // He manually started the Gen","Fanda Brice","Equipment Repa=
ir","Passive","Hybrid","Hybrid Module","Grid outage site went down because =
Gen failed to start due to hybrid system dysfunction // He manually started=
 the Gen","ludovic-anselme.mouliom-mapoure@sagemcom","1325","06-03-2025 20:=
08:04","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004507760","MBA=
LNGONG LYCEE","","06-03-2025 20:01:18","06-03-2025 19:46:54","06-03-2025 20=
:10:04","Grid Outage Site went alarms because Gen Failed to Start due to Ge=
n Overload//Grid Restored","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Over Voltage","Grid Outage Site went alarms because Gen Faile=
d to Start due to Gen Overload//Grid Restored","mariam.tchonang@sagemcom.co=
m","866","06-03-2025 20:01:18","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004507672","Elo=
umdem stade","","06-03-2025 19:42:29","06-03-2025 19:17:14","06-03-2025 20:=
01:15","Site went down because Gen fails to start due to Grid bad voltage /=
/ He bypass the Grid and Gen manually started","Fanda Brice","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Site went down =
because Gen fails to start due to Grid bad voltage // He bypass the Grid an=
d Gen manually started","ludovic-anselme.mouliom-mapoure@sagemcom","1516","=
06-03-2025 19:42:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004507543","J=
-Vespa","","06-03-2025 19:19:35","06-03-2025 19:10:03","06-03-2025 19:11:34=
","Active// No power issue, site is on Grid with Ubaie=3D54,2V, Brice Tsagu=
e(650214096) from Huawei is informed","Mboua Thierry","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// =
No power issue, site is on Grid with Ubaie=3D54,2V, Brice Tsague(650214096)=
 from Huawei is informed","mariam.tchonang@sagemcom.com","573","06-03-2025 =
19:19:35","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004507419","Bon=
djock","","06-03-2025 18:58:38","06-03-2025 18:39:24","06-03-2025 19:08:24"=
,"Grid bad voltage,and gen failed to start,no rcp // Bypassed grid and star=
ted the gen","Fanda Brice","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","Grid bad voltage,and gen failed to start,no rcp /=
/ Bypassed grid and started the gen","ludovic-anselme.mouliom-mapoure@sagem=
com","1256","06-03-2025 18:58:38","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004506833","Pha=
rmacie SION","","06-03-2025 17:24:35","06-03-2025 17:20:28","06-03-2025 17:=
30:28","Grid outage, Site went down before Gen start due to poor backup// G=
en started automatically","Paul BIBOUM","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automatically","ludovic-anselme=
.mouliom-mapoure@sagemcom","248","06-03-2025 17:24:35","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004506829","Nko=
g-Edzen","","06-03-2025 17:23:01","06-03-2025 17:15:48","06-03-2025 18:34:4=
3","Active//No power issue site on Gen. The Team aubin (694427963 ) from I-=
ENG is Working on site","Parker Tchoup","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue =
site on Gen. The Team aubin (694427963 ) from I-ENG is Working on site","lu=
dovic-anselme.mouliom-mapoure@sagemcom","435","06-03-2025 17:23:01","Sagemc=
om CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004506767","Awa=
e Ewonkan","","06-03-2025 17:11:44","06-03-2025 17:06:33","06-03-2025 18:15=
:58","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went do=
wn because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // He=
 reduced the load","ludovic-anselme.mouliom-mapoure@sagemcom","359","06-03-=
2025 17:11:44","Sagemcom CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0004506721","Nko=
langaa","","06-03-2025 17:07:22","06-03-2025 16:56:04","06-03-2025 19:40:04=
","Grid outage gen failedto start due to overheating vausing by headgasket =
issue //we fixed the issue and gen manually started ","Mba Lazare Herve","E=
quipment Repair","Passive","ACDG Gen","ACDG - Radiator Leakage","Grid outag=
e gen failedto start due to overheating vausing by headgasket issue //we fi=
xed the issue and gen manually started ","ludovic-anselme.mouliom-mapoure@s=
agemcom","679","06-03-2025 17:07:22","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004506550","Elo=
umdem stade","","06-03-2025 16:39:44","06-03-2025 16:23:47","06-03-2025 17:=
21:53","Grid fluctuation, Site went down because Gen fails to start due to =
Grid bad voltage  // He bypass the Grid and Gen manually started","Fanda Br=
ice","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, Site went down because Gen fails to start due to Grid=
 bad voltage  // He bypass the Grid and Gen manually started","ludovic-anse=
lme.mouliom-mapoure@sagemcom","958","06-03-2025 16:39:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004506541","Nkolfon =
Cimencam","","06-03-2025 16:38:21","06-03-2025 15:22:28","06-03-2025 20:48:=
00","Cascaded Incident from TTO4565680","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","	Grid Outage site went down d=
ue to Main Gen Faulty//Grid Restored","system","283117","06-03-2025 16:38:2=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004506529","Nkongtoc=
k","","06-03-2025 16:36:02","06-03-2025 15:22:28","06-03-2025 15:48:31","Ca=
scaded Incident from TTO4565679","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","	Grid Outage site went down due to =
Main Gen Faulty//Grid Restored","system","283120","06-03-2025 16:36:02","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004506528","Angongo"=
,"","06-03-2025 16:36:02","06-03-2025 15:22:28","06-03-2025 15:48:31","Casc=
aded Incident from TTO4565679","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","	Grid Outage site went down due to Main G=
en Faulty//Grid Restored","system","283118","06-03-2025 16:36:02","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004506527","OKOA Pea=
ge","","06-03-2025 16:36:02","06-03-2025 15:22:28","06-03-2025 15:48:31","C=
ascaded Incident from TTO4565679","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Grid Outage site went down due to Mai=
n Gen Faulty//Grid Restored","system","283118","06-03-2025 16:36:02","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004506525","Nkenglik=
ok","","06-03-2025 16:36:01","06-03-2025 15:22:28","06-03-2025 15:48:31","C=
ascaded Incident from TTO4565679","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","	Grid Outage site went down due to=
 Main Gen Faulty//Grid Restored","system","283118","06-03-2025 16:36:01","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004506523","Mandoumb=
a OCM","","06-03-2025 16:36:01","06-03-2025 15:22:28","06-03-2025 15:48:31"=
,"Cascaded Incident from TTO4565679","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","	Grid Outage site went down due=
 to Main Gen Faulty//Grid Restored","system","283119","06-03-2025 16:36:01"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004506526","Ebeba","=
","06-03-2025 16:36:01","06-03-2025 17:45:28","06-03-2025 19:13:51","Site w=
ent down because gen fails to start due to grid bad voltage // He bypass gr=
id and manually start the gen","Fanda Brice","Grid Supply","Passive","Grid"=
,"National Grid - Phase Controller Faulty","Site went down because gen fail=
s to start due to grid bad voltage // He bypass grid and manually start the=
 gen","system","7594","06-03-2025 16:36:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004506524","Mbankomo=
 IHS","","06-03-2025 16:36:01","06-03-2025 15:22:28","06-03-2025 15:48:31",=
"Cascaded Incident from TTO4565679","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","	Grid Outage site went down due to M=
ain Gen Faulty//Grid Restored","system","283119","06-03-2025 16:36:01","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004506522","Sous Pre=
fecture","","06-03-2025 16:36:00","06-03-2025 15:22:28","06-03-2025 15:48:3=
1","Cascaded Incident from TTO4565679","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","	Grid Outage site went down due t=
o Main Gen Faulty//Grid Restored","system","283119","06-03-2025 16:36:00","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004506462","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_762, I=
HS_YND_330, IHS_YND_335, IHS_YND_349","06-03-2025 16:27:02","06-03-2025 15:=
22:28","06-03-2025 20:48:00","	Grid Outage site went down due to Main Gen F=
aulty//Grid Restored","Fanda Brice","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Faulty","	Grid Outage site went down due to Main Gen Fau=
lty//Grid Restored","ludovic-anselme.mouliom-mapoure@sagemcom","3875","06-0=
3-2025 16:27:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004506033","B=
arriere IHS","","06-03-2025 15:20:45","06-03-2025 15:17:20","06-03-2025 17:=
13:04","Grid outage, Site went down because Gen failed to start due to PWC =
dysfunctionning IHS Supervisor Felix Zambe confirmed// He reset it and redu=
ced the load, site is on Gen","Hyemafo Gildas","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage, Site went down bec=
ause Gen failed to start due to PWC dysfunctionning IHS Supervisor Felix Za=
mbe confirmed// He reset it and reduced the load, site is on Gen","ludovic-=
anselme.mouliom-mapoure@sagemcom","206","06-03-2025 15:20:45","Sagemcom CMR=
"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004505932","Tsi=
nga village","","06-03-2025 15:05:37","06-03-2025 12:55:26","06-03-2025 15:=
33:37","Site went down because due to insufficiency of rectifiers due to lo=
ad // He reduced the load, site on grid","Delor Telezing","Equipment Repair=
","Passive","Rectifier","Rectifier Module","Site went down because due to i=
nsufficiency of rectifiers due to load // He reduced the load, site on grid=
","ludovic-anselme.mouliom-mapoure@sagemcom","7812","06-03-2025 15:05:37","=
Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004505908","Nko=
ulou Carriere carrefourt","","06-03-2025 15:03:22","06-03-2025 14:58:07","0=
6-03-2025 18:38:51","Grid outage, Site went down because Gen failed to star=
t due to gen contactor no excited // He excited gen contactor, site on gen"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Load Co=
ntactor","Grid outage, Site went down because Gen failed to start due to ge=
n contactor no excited // He excited gen contactor, site on gen","ludovic-a=
nselme.mouliom-mapoure@sagemcom","317","06-03-2025 15:03:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004505895","B=
arriere","","06-03-2025 15:00:48","06-03-2025 14:53:29","06-03-2025 15:14:5=
2","Grid outage, Site went because Gen started and stopped due Gen Overload=
 (20KVA, 450A) SS IHS Felix Zambe confirmed// Grid power return","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge, Site went because Gen started and stopped due Gen Overload (20KVA, 450A=
) SS IHS Felix Zambe confirmed// Grid power return","mariam.tchonang@sagemc=
om.com","440","06-03-2025 15:00:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004505891","ETOUDI C=
HAPELLE","","06-03-2025 14:59:50","06-03-2025 14:56:38","06-03-2025 15:02:5=
9","Cascaded Incident from TTO4564990","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work: SS=
 IHS Bernard ATANGANA working on site// End of work","system","284796","06-=
03-2025 14:59:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_132","NOCINC0004505890","Manguier=
s Dispensaire","","06-03-2025 14:59:50","06-03-2025 14:56:38","06-03-2025 1=
5:02:59","Cascaded Incident from TTO4564990","Fabrice Pouakam","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Site went down due to w=
ork: SS IHS Bernard ATANGANA working on site// End of work","system","28479=
7","06-03-2025 14:59:50","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004505884","Eto=
udi","IHS_YND_132, IHS_YND_694","06-03-2025 14:58:44","06-03-2025 14:56:38"=
,"06-03-2025 15:02:59","Site went down due to work: SS IHS Bernard ATANGANA=
 working on site// End of work","Fabrice Pouakam","Installation Activity","=
Passive","Planned Activity","Installation Activity","Site went down due to =
work: SS IHS Bernard ATANGANA working on site// End of work","ludovic-ansel=
me.mouliom-mapoure@sagemcom","127","06-03-2025 14:58:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004505829","Eseka To=
wn","","06-03-2025 14:49:30","06-03-2025 12:57:29","06-03-2025 13:03:58","C=
ascaded Incident from TTO4564157","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen started=
 and stopped due to pierced pellet // he glued the Pellet and Manually Star=
ted The Gen","system","284789","06-03-2025 14:49:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004505763","Nkolfon =
Cimencam","","06-03-2025 14:37:10","06-03-2025 12:35:57","06-03-2025 13:42:=
45","Cascaded Incident from TTO4563977","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Outage site went down du=
e to Main Gen Faulty//Grid Restored","system","7273","06-03-2025 14:37:10",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004505728","Nkongtoc=
k","","06-03-2025 14:32:22","06-03-2025 12:50:15","06-03-2025 13:35:49","Ca=
scaded Incident from TTO4564756","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage site went down due to M=
ain Gen Faulty//Grid Restored","system","277805","06-03-2025 14:32:22","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004505727","Angongo"=
,"","06-03-2025 14:32:22","06-03-2025 12:50:15","06-03-2025 13:35:49","Casc=
aded Incident from TTO4564756","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid Outage site went down due to Main Ge=
n Faulty//Grid Restored","system","277807","06-03-2025 14:32:22","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004505725","Ebeba","=
","06-03-2025 14:32:21","06-03-2025 12:50:15","06-03-2025 13:35:49","Cascad=
ed Incident from TTO4564756","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid Outage site went down due to Main Gen =
Faulty//Grid Restored","system","277806","06-03-2025 14:32:21","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004505724","Mbankomo=
 IHS","","06-03-2025 14:32:21","06-03-2025 12:50:15","06-03-2025 13:35:49",=
"Cascaded Incident from TTO4564756","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage site went down due to Ma=
in Gen Faulty//Grid Restored","system","277802","06-03-2025 14:32:21","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004505723","Mandoumb=
a OCM","","06-03-2025 14:32:21","06-03-2025 12:50:15","06-03-2025 13:35:49"=
,"Cascaded Incident from TTO4564756","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage site went down due =
to Main Gen Faulty//Grid Restored","system","277804","06-03-2025 14:32:21",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004505726","OKOA Pea=
ge","","06-03-2025 14:32:21","06-03-2025 12:50:15","06-03-2025 13:35:49","C=
ascaded Incident from TTO4564756","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage site went down due to Main=
 Gen Faulty//Grid Restored","system","277803","06-03-2025 14:32:21","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004505722","Sous Pre=
fecture","","06-03-2025 14:32:20","06-03-2025 12:50:15","06-03-2025 13:35:4=
9","Cascaded Incident from TTO4564756","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage site went down due to=
 Main Gen Faulty//Grid Restored","system","277805","06-03-2025 14:32:20","S=
agemcom CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0004505653","NKO=
NGKARAK","","06-03-2025 14:21:22","06-03-2025 13:32:06","06-03-2025 15:22:0=
6","Site went down because Gen started and stopped due to pierced pellet //=
 he glued the Pellet and Manually Started The Gen","TIENTCHEU NZETCHIEU GAE=
L","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Radia=
tor Leakage","Site went down because Gen started and stopped due to pierced=
 pellet // he glued the Pellet and Manually Started The Gen","ferot.nongni-=
djiogap@sagemcom.com","2957","06-03-2025 14:21:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004505571","Minka","=
","06-03-2025 14:09:25","06-03-2025 11:45:31","06-03-2025 13:20:26","Cascad=
ed Incident from TTO4563605","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen fai=
ls to start due to gen card dysfunctionning // Gen manually started","syste=
m","289005","06-03-2025 14:09:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004505572","Bondjock=
","","06-03-2025 14:09:25","06-03-2025 11:45:31","06-03-2025 13:20:26","Cas=
caded Incident from TTO4563605","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
fails to start due to gen card dysfunctionning // Gen manually started","sy=
stem","289005","06-03-2025 14:09:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004505570","Mbeng","=
","06-03-2025 14:09:24","06-03-2025 11:45:31","06-03-2025 13:20:26","Cascad=
ed Incident from TTO4563605","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen fai=
ls to start due to gen card dysfunctionning // Gen manually started","syste=
m","289006","06-03-2025 14:09:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004505569","Mom","",=
"06-03-2025 14:09:24","06-03-2025 11:45:31","06-03-2025 13:20:26","Cascaded=
 Incident from TTO4563605","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, site went down because gen fails=
 to start due to gen card dysfunctionning // Gen manually started","system"=
,"289005","06-03-2025 14:09:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004505469","S=
hell-Nsimeyong","","06-03-2025 13:56:36","06-03-2025 13:53:09","06-03-2025 =
14:00:25","No power issue site on grid with U=3D52.1v Site up at 01:57 PM M=
bah Osiah from Huawei is informed ","MINKA NICOLAS","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue site on grid with U=3D52.1v Site up at 01:57 PM Mbah Osiah from Huawei =
is informed ","cedric.tiani@sagemcom.com","208","06-03-2025 13:56:36","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0004505416","Nkolfoul=
ou Tsinga Village","","06-03-2025 13:45:21","06-03-2025 13:31:12","06-03-20=
25 13:31:13","Cascaded Incident from TTO4564436","Siligap Boris","Cascade O=
utage","Active","Cascade Active","Cascade Active","Active//No power issue U=
=3D54 on grid The fme tx Julien From huawei is informed","system","289956",=
"06-03-2025 13:45:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004505413","Mvog-Eba=
nda","","06-03-2025 13:45:20","06-03-2025 13:31:12","06-03-2025 13:31:13","=
Cascaded Incident from TTO4564436","Siligap Boris","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue U=3D54 on grid =
The fme tx Julien From huawei is informed","system","289955","06-03-2025 13=
:45:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004505414","TSINGA V=
ILLAGE 2","","06-03-2025 13:45:20","06-03-2025 13:31:12","06-03-2025 13:31:=
13","Cascaded Incident from TTO4564436","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active//No power issue U=3D54 on=
 grid The fme tx Julien From huawei is informed","system","289955","06-03-2=
025 13:45:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004505415","SOA VILL=
AGE","","06-03-2025 13:45:20","06-03-2025 13:31:12","06-03-2025 13:31:13","=
Cascaded Incident from TTO4564436","Siligap Boris","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue U=3D54 on grid =
The fme tx Julien From huawei is informed","system","289955","06-03-2025 13=
:45:20","Sagemcom CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004505410","Nko=
lfoulou","IHS_YND_269, IHS_YND_719, IHS_YND_323, IHS_YND_759","06-03-2025 1=
3:43:23","06-03-2025 13:31:12","06-03-2025 13:31:13","Active//No power issu=
e U=3D54 on grid The fme tx Julien From huawei is informed","Siligap Boris"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue U=3D54 on grid The fme tx Julien From h=
uawei is informed","ferot.nongni-djiogap@sagemcom.com","732","06-03-2025 13=
:43:23","Sagemcom CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0004505173","Ese=
ka MTN","IHS_YND_378","06-03-2025 13:06:51","06-03-2025 12:57:29","06-03-20=
25 13:03:58","Site went down because Gen started and stopped due to pierced=
 pellet // he glued the Pellet and Manually Started The Gen","Kemeni Frankl=
in","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator Leakage","Site=
 went down because Gen started and stopped due to pierced pellet // he glue=
d the Pellet and Manually Started The Gen","cedric.tiani@sagemcom.com","563=
","06-03-2025 13:06:51","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004505076","Eto=
 koss Yde","","06-03-2025 12:50:09","06-03-2025 12:46:53","06-03-2025 12:50=
:46","Avtive: No power issue, site is on grid with Ubaie=3D53V, Fulbert (65=
4266068) from Huawei is informed","Fanda Brice","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Avtive: No powe=
r issue, site is on grid with Ubaie=3D53V, Fulbert (654266068) from Huawei =
is informed","ferot.nongni-djiogap@sagemcom.com","197","06-03-2025 12:50:09=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0004505064","N=
omayos-IHS","","06-03-2025 12:47:02","06-03-2025 12:29:47","06-03-2025 12:3=
0:36","Incorrectly logged tickets","Fanda Brice","Incorrectly Logged Ticket=
s","Error","Error","Error","Incorrectly logged tickets","cedric.tiani@sagem=
com.com","1036","06-03-2025 12:47:02","Sagemcom CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004505019","Nom=
ayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_339, IHS_YND_762, IHS=
_YND_330, IHS_YND_335, IHS_YND_349","06-03-2025 12:42:09","06-03-2025 12:35=
:57","06-03-2025 13:42:45","Grid Outage site went down due to Main Gen Faul=
ty//Grid Restored","Fanda Brice","Equipment Repair","Passive","ACDG Gen","A=
CDG - Generator Faulty","Grid Outage site went down due to Main Gen Faulty/=
/Grid Restored","ferot.nongni-djiogap@sagemcom.com","373","06-03-2025 12:42=
:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_201","IHS_YND_368","NOCINC0004504688","O=
tele","IHS_YND_370, IHS_YND_369, IHS_YND_371, IHS_YND_372","06-03-2025 11:5=
7:48","06-03-2025 11:45:31","06-03-2025 13:20:26","Grid outage, site went d=
own because gen fails to start due to gen card dysfunctionning // Gen manua=
lly started","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid outage, site went down because gen fails to start due =
to gen card dysfunctionning // Gen manually started","cedric.tiani@sagemcom=
.com","737","06-03-2025 11:57:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004504615","N=
koabang Ebolmedjock","","06-03-2025 11:51:59","06-03-2025 11:19:46","06-03-=
2025 18:38:59","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Gen. Notice that it is impacted b=
y Nkolmesseng-Abom(CTR-711) Not Manager By IHS","cedric.tiani@sagemcom.com"=
,"1933","06-03-2025 11:51:59","Sagemcom CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0004504481","Nko=
mo","","06-03-2025 11:34:29","06-03-2025 10:51:20","06-03-2025 11:45:25","G=
rid outage, Site went down because Gen ran until fuel shortage// Refueling =
Done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, Site went down because Gen ran until fuel shortage// Refueling=
 Done","ferot.nongni-djiogap@sagemcom.com","2734","06-03-2025 11:34:29","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004504420","Bondjock=
","","06-03-2025 11:24:30","06-03-2025 11:12:00","06-03-2025 11:20:27","Cas=
caded Incident from TTO4563226","Fanda Brice","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active// No power issue on site ,site on Gr=
id with Ubaie=3D 54,1V
The fme tx Etienne fopa // 695033981 of huawei is informed and Site,Noticed=
 that it is impacted by Otele camrail","system","1218974","06-03-2025 11:24=
:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004504389","Nomayos =
montee Meche","","06-03-2025 11:20:40","06-03-2025 10:57:30","06-03-2025 13=
:43:58","Cascaded Incident from TTO4563259 - Cascade Removed From TTO456325=
9","Fanda Brice","Equipment Repair","Passive","Control Panel","ATS-AMF Issu=
e","Grid outage.gen failed to start due to automation malfunctionning//Gen =
manually started ","system","1390","06-03-2025 11:20:40","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004504384","ELO=
UMDEM CARRIERE","","06-03-2025 11:19:42","06-03-2025 10:57:30","06-03-2025 =
18:40:13","No power issue , Site on Grid and Ubaie=3D55V The Tx Fme Fulbert=
 //654266068 from Huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue , Site on Grid and Ubaie=3D55V The Tx Fme Fulbert //654266068 from Huaw=
ei is informed","ferot.nongni-djiogap@sagemcom.com","1334","06-03-2025 11:1=
9:42","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004504372","Awa=
e Ewonkan","","06-03-2025 11:17:52","06-03-2025 11:14:05","06-03-2025 12:19=
:55","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went do=
wn because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // He=
 reduced the load","cedric.tiani@sagemcom.com","229","06-03-2025 11:17:52",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004504362","M=
om","IHS_YND_372","06-03-2025 11:16:17","06-03-2025 11:12:00","06-03-2025 1=
1:20:27","Active// No power issue on site ,site on Grid with Ubaie=3D 54,1V=
 The fme tx Etienne fopa // 695033981 of huawei is informed and Site,Notice=
d that it is impacted by Otele camrail","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// =
No power issue on site ,site on Grid with Ubaie=3D 54,1V
The fme tx Etienne fopa // 695033981 of huawei is informed and Site,Noticed=
 that it is impacted by Otele camrail","cedric.tiani@sagemcom.com","258","0=
6-03-2025 11:16:17","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004504279","Bar=
riere","","06-03-2025 11:08:03","06-03-2025 10:57:28","06-03-2025 11:02:55"=
,"Grid fluctuation, site went down due to Gen Gen Overload (20KVA, 450A) SS=
 IHS Felix Zambe confirmed// Grid power return","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuation, site wen=
t down due to Gen Gen Overload (20KVA, 450A) SS IHS Felix Zambe confirmed//=
 Grid power return","ferot.nongni-djiogap@sagemcom.com","697","06-03-2025 1=
1:08:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004504267","E=
foulan","","06-03-2025 11:06:56","06-03-2025 10:26:39","06-03-2025 17:41:18=
","Active: no power issue, site is ongrid with Ubaie=3D53V, TX Fme Brice Ts=
ague of huawei is informed","MINKA NICOLAS","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power is=
sue, site is ongrid with Ubaie=3D53V, TX Fme Brice Tsague of huawei is info=
rmed","cedric.tiani@sagemcom.com","2418","06-03-2025 11:06:56","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004504105","O=
bobogo","","06-03-2025 10:40:40","06-03-2025 10:25:20","06-03-2025 17:42:36=
","No power issue site on grid with Ubai1=3D54.9V,Site on Grid  The TX Fme =
Hosiah / 674007438// from huawei is informed","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue site on grid with Ubai1=3D54.9V,Site on GridThe TX Fme Hosiah=
 / 674007438// from huawei is informed
","cedric.tiani@sagemcom.com","921","06-03-2025 10:40:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004503955","MONTEE N=
KONDENGUI","","06-03-2025 10:16:20","06-03-2025 10:06:20","06-03-2025 10:19=
:57","Cascaded Incident from TTO4562732","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage // Grid return","=
system","273288","06-03-2025 10:16:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004503953","M=
obil-Kondengui","IHS_YND_682","06-03-2025 10:15:40","06-03-2025 10:06:20","=
06-03-2025 10:19:57","Grid outage // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage // Grid return","=
cedric.tiani@sagemcom.com","561","06-03-2025 10:15:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004503932","B=
ATA Mokolo OCM","","06-03-2025 10:12:09","06-03-2025 09:44:44","06-03-2025 =
17:16:43","Grid outage, No space to deploy MDG //Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No s=
pace to deploy MDG //Grid return","cedric.tiani@sagemcom.com","1646","06-03=
-2025 10:12:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004503894","S=
tade-Abega","","06-03-2025 10:04:22","06-03-2025 09:55:04","06-03-2025 10:5=
4:02","Grid outage, site went down due to PWC ZTE malfunction // He reset c=
ontroller and gen manually started","Mba Lazare Herve","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site went =
down due to PWC ZTE malfunction // He reset controller and gen manually sta=
rted","cedric.tiani@sagemcom.com","559","06-03-2025 10:04:22","Sagemcom CMR=
"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004503848","Crf=
-Mbankolo-IHS","","06-03-2025 09:57:14","06-03-2025 09:52:04","06-03-2025 2=
0:41:04","Site went down due to MPR DYSFONNCTION on site SS IHS Bernard ATA=
NGANA confirmed // He reset the MPR and Site is on Grid","Mboua Thierry","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site =
went down due to MPR DYSFONNCTION on site SS IHS Bernard ATANGANA confirmed=
 // He reset the MPR and Site is on Grid","ferot.nongni-djiogap@sagemcom.co=
m","311","06-03-2025 09:57:14","Sagemcom CMR"
"Closed Complete","Site Down","T0566","IHS_YND_421","NOCINC0004503648","Bot=
 Makak","IHS_EDA_101","06-03-2025 09:20:08","06-03-2025 09:01:55","06-03-20=
25 09:10:04","Active: no power issue, site is on grid with Ubaie =3D 54.5V,=
   The Tx FME Etienne 695033981 of huawei is informed","","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: no power issue, site is on grid with Ubaie =3D 54.5V,=20

The Tx FME Etienne 695033981 of huawei is informed
","wilfried.kameni@sagemcom.com","1093","06-03-2025 09:20:08","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0004503434","Etoudi 2=
","","06-03-2025 08:25:01","06-03-2025 08:23:58","06-03-2025 08:25:34","Cas=
caded Incident from TTO4562121","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active: no power issue, site is on grid=
 with Ubaie Ubaie=3D53V, Armand Nguetsa(691144412) from Huawei is informed"=
,"system","272240","06-03-2025 08:25:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004503432","Abattoir=
","","06-03-2025 08:25:01","06-03-2025 08:23:58","06-03-2025 08:25:34","Cas=
caded Incident from TTO4562121","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active: no power issue, site is on grid=
 with Ubaie Ubaie=3D53V, Armand Nguetsa(691144412) from Huawei is informed"=
,"system","272240","06-03-2025 08:25:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004503433","ETOUDI C=
HAPELLE","","06-03-2025 08:25:01","06-03-2025 08:23:58","06-03-2025 08:25:3=
4","Cascaded Incident from TTO4562121","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active: no power issue, site is o=
n grid with Ubaie Ubaie=3D53V, Armand Nguetsa(691144412) from Huawei is inf=
ormed","system","272241","06-03-2025 08:25:01","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004503429","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","06-03-2025 08:24:06","06-03-2=
025 08:23:58","06-03-2025 08:25:34","Active: no power issue, site is on gri=
d with Ubaie Ubaie=3D53V, Armand Nguetsa(691144412) from Huawei is informed=
","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active: no power issue, site is on grid wit=
h Ubaie Ubaie=3D53V, Armand Nguetsa(691144412) from Huawei is informed","fe=
rot.nongni-djiogap@sagemcom.com","9","06-03-2025 08:24:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004503358","O=
LAMA","","06-03-2025 08:08:32","06-03-2025 06:59:01","06-03-2025 07:05:03",=
"Active//No power issue on site Ubaie =3D54.9V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.9V site on Grid The TX FME Henri (69994969=
3) from Huawei is informed","cedric.tiani@sagemcom.com","4171","06-03-2025 =
08:08:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004503270","N=
kolfon Cimencam","","06-03-2025 07:57:50","06-03-2025 07:24:37","06-03-2025=
 07:30:13","Active//No power issue, Site on Grid. Notice that it is impacte=
d by Afanoya II The Tx FME Fulbert from Huawei is informed","Hyemafo Gildas=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","Active//No power issue, Site on Grid. Notice that it is impac=
ted by Afanoya II The Tx FME Fulbert from Huawei is informed","cedric.tiani=
@sagemcom.com","1994","06-03-2025 07:57:50","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004503034","Crf=
-Mbankolo-IHS","","06-03-2025 07:17:00","06-03-2025 07:11:49","06-03-2025 0=
8:07:06","Site went down due to MPR DYSFONNCTION on site SS IHS Bernard ATA=
NGANA confirmed // He reset the MPR","Mboua Thierry","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Cabinet","Site went down due to MPR DYSFONNCT=
ION on site SS IHS Bernard ATANGANA confirmed // He reset the MPR","ferot.n=
ongni-djiogap@sagemcom.com","343","06-03-2025 07:17:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0004503002","Olezoa O=
CM","","06-03-2025 07:09:40","06-03-2025 06:49:36","06-03-2025 07:48:22","C=
ascaded Incident from TTO4561616","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Site was on Gen due to Grid outage, site went dow=
n because gen stopped with alarm ""high temp"" // He added water and manual=
ly start the Gen","system","270705","06-03-2025 07:09:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0004502996","Acropole=
","","06-03-2025 07:08:11","06-03-2025 06:49:36","06-03-2025 07:48:22","Cas=
caded Incident from TTO4561616","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site was on Gen due to Grid outage, si=
te went down because gen stopped with alarm ""high temp"" // He added water=
 and manually start the Gen","system","270706","06-03-2025 07:08:11","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0004502997","C-Suprem=
e","","06-03-2025 07:08:11","06-03-2025 06:49:36","06-03-2025 07:48:22","Ca=
scaded Incident from TTO4561616","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site was on Gen due to Grid outage, site went down=
 because gen stopped with alarm ""high temp"" // He added water and manuall=
y start the Gen","system","270705","06-03-2025 07:08:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0004502986","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","06-03-2025 07:06:59",=
"06-03-2025 06:49:36","06-03-2025 07:48:22","Site was on Gen due to Grid ou=
tage, site went down because gen stopped with alarm ""high temp"" // He add=
ed water and manually start the Gen","MINKA NICOLAS","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Site was=
 on Gen due to Grid outage, site went down because gen stopped with alarm "=
"high temp"" // He added water and manually start the Gen","cedric.tiani@sa=
gemcom.com","1044","06-03-2025 07:06:59","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004502896","Mam=
bine","","06-03-2025 06:56:59","06-03-2025 06:54:44","06-03-2025 09:15:26",=
"Grid outage, site went down because gen failed to start due to Hybrid syst=
em malfunction // Gen manually started","Fanda Brice","Equipment Repair","P=
assive","Hybrid","Hybrid Module","Grid outage, site went down because gen f=
ailed to start due to Hybrid system malfunction // Gen manually started","e=
l-dalile@sagemcom.com","136","06-03-2025 06:56:59","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004502882","Eko=
umdoum OCM","","06-03-2025 06:55:00","06-03-2025 06:51:51","06-03-2025 07:1=
3:34","Grid bad voltage, Site went down due to Gen overload(20kva,280 A) IH=
S SS Pascaline is informed and confirmed// Grid return","Albran Byorel","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid bad voltage, S=
ite went down due to Gen overload(20kva,280 A) IHS SS Pascaline is informed=
 and confirmed// Grid return","el-dalile@sagemcom.com","421","06-03-2025 06=
:55:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004502810","MONTEE N=
KONDENGUI","","06-03-2025 06:45:40","06-03-2025 06:30:31","06-03-2025 06:56=
:07","Cascaded Incident from TTO4561414","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage // Grid return","=
system","271814","06-03-2025 06:45:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004502803","M=
obil-Kondengui","IHS_YND_682","06-03-2025 06:45:01","06-03-2025 06:30:31","=
06-03-2025 06:56:07","Grid outage // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage // Grid return","=
yves.djomo@sagemcom.com","871","06-03-2025 06:45:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004502660","E=
ssomba","","06-03-2025 05:59:05","06-03-2025 05:57:02","06-03-2025 09:47:51=
","Site went down because failed to start due to grid bad voltage // Gen ma=
nually started","Mba Lazare Herve","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Site went down because failed to start du=
e to grid bad voltage // Gen manually started","yves.djomo@sagemcom.com","1=
24","06-03-2025 05:59:05","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004502577","Mel=
en Ba'aba","","06-03-2025 05:37:28","06-03-2025 05:31:19","06-03-2025 06:59=
:17","Grid outage, site went down because gen start and stopped with Alarm =
Under frequency // He reset gen card and gen manually started","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage, site went down because gen start and stopped with Alarm Under frequen=
cy // He reset gen card and gen manually started","yves.djomo@sagemcom.com"=
,"371","06-03-2025 05:37:28","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004502392","Nko=
ulou Carriere carrefourt","","06-03-2025 04:49:11","06-03-2025 04:34:57","0=
6-03-2025 08:34:35","Gen started due to Grid outage, site went down because=
 gen contactor no excited // He excited gen contactor, site on gen ","Mba L=
azare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor=
","Gen started due to Grid outage, site went down because gen contactor no =
excited // He excited gen contactor, site on gen ","yves.djomo@sagemcom.com=
","855","06-03-2025 04:49:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004502339","S=
calom","","06-03-2025 04:19:37","06-03-2025 04:16:31","06-03-2025 11:06:01"=
,"Site went down due to insufficiency of rectifiers, Francois IHS // He red=
uced the load","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to insufficiency of rectifiers, Francois =
IHS // He reduced the load","yves.djomo@sagemcom.com","187","06-03-2025 04:=
19:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_509","NOCINC0004502189","MANGUIER=
S CHAPELLE","","06-03-2025 02:53:11","05-03-2025 18:15:36","05-03-2025 18:2=
0:35","Cascaded Incident from TTO4560668","Fabrice Pouakam","Cascade Outage=
","Active","Cascade Active","Cascade Active","Active//No power issue U=3D51=
,1V on Grid The fme Tx Armand ngeutsa From huawei is informed","system","29=
4421","06-03-2025 02:53:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0004502188","Omnispor=
t-Rail","","06-03-2025 02:53:10","05-03-2025 18:15:36","05-03-2025 18:20:35=
","Cascaded Incident from TTO4560668","Delor Telezing","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue U=3D51,1V o=
n Grid The fme Tx Armand ngeutsa From huawei is informed","system","294421"=
,"06-03-2025 02:53:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0004502185","M=
anguier","IHS_YND_506, IHS_YND_509","06-03-2025 02:51:54","05-03-2025 18:15=
:36","06-03-2025 02:20:35","Active//No power issue U=3D51,1V on Grid The fm=
e Tx Armand ngeutsa From huawei is informed","Fabrice Pouakam","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue U=3D51,1V on Grid The fme Tx Armand ngeutsa From hua=
wei is informed","yves.djomo@sagemcom.com","30979","06-03-2025 02:51:54","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004501732","MONTEE N=
KONDENGUI","","06-03-2025 01:28:30","06-03-2025 01:17:43","06-03-2025 01:42=
:41","Cascaded Incident from TTO4560200","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage// Grid return","s=
ystem","269146","06-03-2025 01:28:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004501731","M=
obil-Kondengui","IHS_YND_682","06-03-2025 01:27:49","06-03-2025 01:17:43","=
06-03-2025 01:42:41","Grid outage// Grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage// Grid return","yv=
es.djomo@sagemcom.com","607","06-03-2025 01:27:49","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004501722","Tou=
ring Club International","","06-03-2025 01:23:11","06-03-2025 01:21:58","06=
-03-2025 01:44:21","Grid Outage Site went down because Gen overload (20KVA,=
 270A) SS IHS Pascaline confirmed // Grid return","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went dow=
n because Gen overload (20KVA, 270A) SS IHS Pascaline confirmed // Grid ret=
urn","el-dalile@sagemcom.com","74","06-03-2025 01:23:11","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004501721","Crf=
-Nsam","","06-03-2025 01:22:56","06-03-2025 01:14:51","06-03-2025 03:50:36"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline conf=
irmed// He reset PWC","MINKA NICOLAS","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down because PWC(24kilo) dysfu=
nctionning, IHS SS Pascaline confirmed// He reset PWC","yves.djomo@sagemcom=
.com","486","06-03-2025 01:22:56","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004501715","AWA=
E OCM","","06-03-2025 01:21:24","06-03-2025 01:15:19","06-03-2025 01:26:29"=
,"Grid outage, Site went down before Gen start due to poor backup // Grid r=
eturn","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage, Site went down before Gen start due=
 to poor backup // Grid return","yves.djomo@sagemcom.com","366","06-03-2025=
 01:21:24","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004501512","Beh=
ind P T school Yde","","06-03-2025 00:07:44","05-03-2025 23:26:23","06-03-2=
025 04:53:32","Grid outage, site went down because gen failed to start due =
to gen card faulty //Gen manually started","Paul BIBOUM","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down b=
ecause gen failed to start due to gen card faulty //Gen manually started","=
el-dalile@sagemcom.com","2482","06-03-2025 00:07:44","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004501454","Crf=
-Mbankolo-IHS","","05-03-2025 23:52:08","05-03-2025 23:20:56","06-03-2025 0=
0:35:36","Site went down due to MPR DYSFONNCTION on site SS IHS Bernard ATA=
NGANA confirmed // He reset the MPR","Mboua Thierry","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Cabinet","Site went down due to MPR DYSFONNCT=
ION on site SS IHS Bernard ATANGANA confirmed // He reset the MPR","yves.dj=
omo@sagemcom.com","1873","05-03-2025 23:52:08","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004501367","Man=
guiers Dispensaire","","05-03-2025 23:30:44","05-03-2025 16:46:39","05-03-2=
025 16:48:12","Active // No power issue site on grid with U=3D54,5 V Tx Fme=
 Armand Ngestsa (691144412) of huawei is informed","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active // No power issue site on grid with U=3D54,5 V Tx Fme Armand N=
gestsa (691144412) of huawei is informed","yves.djomo@sagemcom.com","24246"=
,"05-03-2025 23:30:44","Sagemcom CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004501344","Sca=
lom","","05-03-2025 23:27:58","05-03-2025 16:59:51","06-03-2025 01:43:36","=
Site went down because CB tripped in PWC who feeds equipments MTN// CB put =
back on (CB to be upgraded)","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Circuit Breaker Issue","Site went down becaus=
e CB tripped in PWC who feeds equipments MTN// CB put back on (CB to be upg=
raded)","yves.djomo@sagemcom.com","23323","05-03-2025 23:27:58","Sagemcom C=
MR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0004501198","Ngo=
usso-Savana","","05-03-2025 23:05:46","05-03-2025 22:49:38","05-03-2025 23:=
07:56","Grid Outage, site went down before gen start due to poor battery ba=
ckup // Gen start automatically","Siligap Boris","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"yves.djomo@sagemcom.com","969","05-03-2025 23:05:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004501165","TSINGA V=
ILLAGE 2","","05-03-2025 23:01:20","05-03-2025 22:33:44","05-03-2025 22:40:=
11","Cascaded Incident from TTO4559499","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue, site on Gen with=
 Ubaie=3D56,5 V, Yannick MBA(698270715) from Huawei is informed by Message"=
,"system","271687","05-03-2025 23:01:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004501164","Mvog-Eba=
nda","","05-03-2025 23:01:20","05-03-2025 22:33:44","05-03-2025 22:40:11","=
Cascaded Incident from TTO4559499","Siligap Boris","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue, site on Gen with Ubaie=
=3D56,5 V, Yannick MBA(698270715) from Huawei is informed by Message","syst=
em","271687","05-03-2025 23:01:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0004501166","Nkolfoul=
ou Tsinga Village","","05-03-2025 23:01:20","05-03-2025 22:33:44","05-03-20=
25 22:40:11","Cascaded Incident from TTO4559499","Siligap Boris","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue, site on =
Gen with Ubaie=3D56,5 V, Yannick MBA(698270715) from Huawei is informed by =
Message","system","271688","05-03-2025 23:01:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0004501141","E=
toudi 2","","05-03-2025 22:55:31","05-03-2025 21:53:22","06-03-2025 00:02:4=
7","Grid outage, site went down because gen start and stopped with over cur=
rent alarm(Unpruven alarm) // Reset of gen card done and gen started","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage, site went down because gen start and stopped with over curre=
nt alarm(Unpruven alarm) // Reset of gen card done and gen started","yves.d=
jomo@sagemcom.com","3730","05-03-2025 22:55:31","Sagemcom CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004501131","Nko=
lfoulou","IHS_YND_269, IHS_YND_719, IHS_YND_759","05-03-2025 22:52:52","05-=
03-2025 22:33:44","06-03-2025 00:40:41","Active//No power issue U=3D54 on g=
rid The fme tx Julien From huawei is informed","Siligap Boris","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue U=3D54 on grid The fme tx Julien From huawei is info=
rmed","yves.djomo@sagemcom.com","1149","05-03-2025 22:52:52","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004500987","HOP=
ITAL GENERAL RAIL YDE","","05-03-2025 22:28:16","05-03-2025 22:05:37","06-0=
3-2025 07:46:18","Grid outage, site went down due to gen Overload(09kva,160=
A), Bernard IHS is informed // Grid return","Delor Telezing","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down du=
e to gen Overload(09kva,160A), Bernard IHS is informed // Grid return","lud=
ovic-anselme.mouliom-mapoure@sagemcom","1360","05-03-2025 22:28:16","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004500942","M=
eyo","IHS_YND_257","05-03-2025 22:20:09","05-03-2025 22:01:59","05-03-2025 =
22:59:17","Grid outage, site went down because Gen overload (17kva, 250A) S=
S IHS Felix ZAMBE confirmed// He reduiced load and started Gen manualy","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down because Gen overload (17kva, 250A) SS IHS Felix Z=
AMBE confirmed// He reduiced load and started Gen manualy","danick.tchakoua=
ni@sagemcom.com","1091","05-03-2025 22:20:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0004500920","A=
hala","","05-03-2025 22:16:12","05-03-2025 22:01:59","05-03-2025 22:56:02",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site went down because Gen overload (17kva, 250A) SS =
IHS Felix ZAMBE confirmed// He reduiced load and started Gen manualy","dani=
ck.tchakouani@sagemcom.com","1223092","05-03-2025 22:16:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004500878","Minka","=
","05-03-2025 22:09:11","05-03-2025 21:59:57","05-03-2025 22:21:08","Cascad=
ed Incident from TTO4559198","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Site went down because gen sta=
rt and stopped with alarm"" High temps""// he added water and manually star=
t the Gen","system","266493","05-03-2025 22:09:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004500877","Mbeng","=
","05-03-2025 22:09:11","05-03-2025 21:59:57","05-03-2025 22:21:08","Cascad=
ed Incident from TTO4559198","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Site went down because gen sta=
rt and stopped with alarm"" High temps""// he added water and manually star=
t the Gen","system","266493","05-03-2025 22:09:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004500865","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_372","05-03-2025 22:07:21","05-03-20=
25 21:59:57","05-03-2025 22:21:08","Grid outage, Site went down because gen=
 start and stopped with alarm"" High temps""// he added water and manually =
start the Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG =
- High Engine Temp - Coolant Level Issue","Grid outage, Site went down beca=
use gen start and stopped with alarm"" High temps""// he added water and ma=
nually start the Gen","ludovic-anselme.mouliom-mapoure@sagemcom","446","05-=
03-2025 22:07:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004500624","S=
imbock OCM","","05-03-2025 21:30:54","05-03-2025 21:11:47","06-03-2025 00:1=
8:14","Access issue during the night Grid fluctuation, Site went down becau=
se Gen started and stopped due to grid bad voltage// Grid stabilized .","Hy=
emafo Gildas","Access Denial","Lease Or Legal","Landlord Related Issues","A=
ccess Issue - Land Lord","Acces issues during the Night(","danick.tchakouan=
i@sagemcom.com","1148","05-03-2025 21:30:54","Sagemcom CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004500484","SOA=
 VILLAGE","","05-03-2025 21:05:42","05-03-2025 20:42:17","06-03-2025 02:43:=
34","Active//No power issue, site is on Grid with Ubaie=3D54,6V The TX Synp=
horien / 675295205/ Huawei is informed","Siligap Boris","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue, site is on Grid with Ubaie=3D54,6V The TX Synphorien / 675=
295205/ Huawei is informed","ludovic-anselme.mouliom-mapoure@sagemcom","140=
6","05-03-2025 21:05:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004500365","H=
-Paradis","","05-03-2025 20:54:20","05-03-2025 20:40:22","05-03-2025 20:41:=
27","Active // No power issue site on grid with U=3D50,5 V Tx Fme Armand Ng=
estsa (691144412) of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power =
issue site on grid with U=3D50,5 V Tx Fme Armand Ngestsa (691144412) of hua=
wei is informed","danick.tchakouani@sagemcom.com","839","05-03-2025 20:54:2=
0","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004500137","Nko=
g-Edzen","","05-03-2025 20:19:52","05-03-2025 20:15:33","06-03-2025 02:48:5=
8","Active//No power issue site on Gen. The Team aubin (694427963 ) from I-=
ENG is Working on site","Parker Tchoup","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue =
site on Gen. The Team aubin (694427963 ) from I-ENG is Working on site","lu=
dovic-anselme.mouliom-mapoure@sagemcom","260","05-03-2025 20:19:52","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004500122","A=
ccacia New","","05-03-2025 20:18:01","05-03-2025 20:14:54","05-03-2025 22:5=
9:55","Active// No power Issue Site on Grid Ubai =3D54,6V, The FME The TX F=
ME Mbah Hosiah (674007438) is informed.","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power I=
ssue Site on Grid Ubai =3D54,6V, The FME The TX FME Mbah Hosiah (674007438)=
 is informed.","danick.tchakouani@sagemcom.com","188","05-03-2025 20:18:01"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004500082","M=
essa-Carriere OCM","","05-03-2025 20:12:23","05-03-2025 19:09:38","06-03-20=
25 08:28:55","Grid outage.no space to deploy mobile gen//grid power ","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge.no space to deploy mobile gen//grid power ","ludovic-anselme.mouliom-map=
oure@sagemcom","3766","05-03-2025 20:12:23","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004499879","Men=
dong3","","05-03-2025 19:34:07","05-03-2025 15:52:48","05-03-2025 19:56:57"=
,"Grid outage.no space to deploy mobile gen//Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no space =
to deploy mobile gen//Grid return","ludovic-anselme.mouliom-mapoure@sagemco=
m","13280","05-03-2025 19:34:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0004499495","Obobogo"=
,"","05-03-2025 18:36:30","05-03-2025 16:59:05","05-03-2025 16:59:06","Casc=
aded Incident from TTO4557604","MINKA NICOLAS","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site U=3D54,1v site on g=
rid Brice Tsague of huawei is informed","system","284790","05-03-2025 18:36=
:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004499489","E=
foulan","IHS_YND_155","05-03-2025 18:35:14","05-03-2025 16:59:05","05-03-20=
25 16:59:06","No power issue on site U=3D54,1v site on grid Brice Tsague of=
 huawei is informed","MINKA NICOLAS","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,1v site on grid Brice Tsague of huawei is informed","danick.tchakouan=
i@sagemcom.com","5770","05-03-2025 18:35:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0004499366","M=
asque","","05-03-2025 18:11:21","05-03-2025 15:31:03","05-03-2025 18:57:58"=
,"Grid outage, Site went down because Gen failed to start due to Gen card d=
isfunction// He reset Gen card and  started Gen manualy","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
, Site went down because Gen failed to start due to Gen card disfunction// =
He reset Gen card and  started Gen manualy","ludovic-anselme.mouliom-mapour=
e@sagemcom","9620","05-03-2025 18:11:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0004499337","M=
anguier","","05-03-2025 18:08:43","05-03-2025 17:15:32","05-03-2025 18:14:2=
1","Grid outage, site went down before gen start due to poor battery backup=
 // Grid return. Power issue resolved at 06:14 PM but the site still down T=
X FME Armand Nguets/691144412/ From huawei is informed","Fabrice Pouakam","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","=
Grid outage, site went down before gen start due to poor battery backup // =
Grid return. Power issue resolved at 06:14 PM but the site still down TX FM=
E Armand Nguets/691144412/ From huawei is informed","ludovic-anselme.moulio=
m-mapoure@sagemcom","3191","05-03-2025 18:08:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004499259","N=
komkana 2","","05-03-2025 17:57:20","05-03-2025 14:41:09","05-03-2025 17:41=
:10","No power issue on site ,site on Grid with Ubaie=3D52,8 V The TX fme B=
rice Drague//650214096/690286359 from huawei is informed R=E9p=E9titif issu=
e","Mboua Thierry","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue on site ,site on Grid with Ub=
aie=3D52,8 V The TX fme Brice Drague//650214096/690286359 from huawei is in=
formed R=E9p=E9titif issue","danick.tchakouani@sagemcom.com","11772","05-03=
-2025 17:57:20","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004499113","Nsi=
meyong Shell","","05-03-2025 17:32:47","05-03-2025 16:58:36","05-03-2025 20=
:57:51","Grid outage,Gen failed to start because there is no gen cable to s=
tart the GEN // MDG 30Kva deployed","MINKA NICOLAS","Equipment Repair","Pas=
sive","Infrastructure","Armoured Cable","Grid outage,Gen failed to start be=
cause there is no gen cable to start the GEN // MDG 30Kva deployed","ludovi=
c-anselme.mouliom-mapoure@sagemcom","2053","05-03-2025 17:32:47","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0004499037","Ngog Map=
ubi","","05-03-2025 17:20:10","05-03-2025 16:59:51","05-03-2025 17:27:22","=
Cascaded Incident from TTO4556947","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuations, site went down=
 because Gen failed to start due to grid bad voltage // He bypassed the gri=
d and started Gen manually","system","1219729","05-03-2025 17:20:10","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0004499038","Ekekam",=
"","05-03-2025 17:20:10","05-03-2025 16:59:51","05-03-2025 17:27:22","Casca=
ded Incident from TTO4556947","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuations, site went =
down because Gen failed to start due to grid bad voltage // He bypassed the=
 grid and started Gen manually","system","1219725","05-03-2025 17:20:10","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0004499019","Akono","=
","05-03-2025 17:19:12","05-03-2025 16:59:51","05-03-2025 17:27:22","Cascad=
ed Incident from TTO4556947","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuations, site went down because G=
en failed to start due to grid bad voltage // He bypassed the grid and star=
ted Gen manually","system","1219728","05-03-2025 17:19:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004499020","NKONGKAR=
AK","","05-03-2025 17:19:12","05-03-2025 16:59:51","05-03-2025 17:27:22","C=
ascaded Incident from TTO4556947","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid fluctuations, site w=
ent down because Gen failed to start due to grid bad voltage // He bypassed=
 the grid and started Gen manually","system","1219724","05-03-2025 17:19:12=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004499016","Minka","=
","05-03-2025 17:19:12","05-03-2025 16:59:51","05-03-2025 17:27:22","Cascad=
ed Incident from TTO4556947","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuations, site went down because G=
en failed to start due to grid bad voltage // He bypassed the grid and star=
ted Gen manually","system","1219726","05-03-2025 17:19:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004499017","Nkongtoc=
k","","05-03-2025 17:19:12","05-03-2025 16:59:51","05-03-2025 17:27:22","Ca=
scaded Incident from TTO4556947","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuations, site went down b=
ecause Gen failed to start due to grid bad voltage // He bypassed the grid =
and started Gen manually","system","1219730","05-03-2025 17:19:12","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004499018","Mom","",=
"05-03-2025 17:19:12","05-03-2025 16:59:51","05-03-2025 17:27:22","Cascaded=
 Incident from TTO4556947","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid fluctuations, site went down because Gen=
 failed to start due to grid bad voltage // He bypassed the grid and starte=
d Gen manually","system","1219730","05-03-2025 17:19:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004499014","OTELE MT=
N","","05-03-2025 17:19:11","05-03-2025 16:59:51","05-03-2025 17:27:22","Ca=
scaded Incident from TTO4556947","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid fluctuations, site went down becau=
se Gen failed to start due to grid bad voltage // He bypassed the grid and =
started Gen manually","system","1219723","05-03-2025 17:19:11","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0004499012","Bot Maka=
k","","05-03-2025 17:19:11","05-03-2025 16:59:51","05-03-2025 17:27:22","Ca=
scaded Incident from TTO4556947","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuations, site went down because Gen fail=
ed to start due to grid bad voltage // He bypassed the grid and started Gen=
 manually","system","1219727","05-03-2025 17:19:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_706","NOCINC0004499013","Mbankomo=
 CAF","","05-03-2025 17:19:11","05-03-2025 16:59:51","05-03-2025 17:27:22",=
"Cascaded Incident from TTO4556947","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuations, site went down be=
cause Gen failed to start due to grid bad voltage // He bypassed the grid a=
nd started Gen manually","system","1219726","05-03-2025 17:19:11","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004499015","Angongo"=
,"","05-03-2025 17:19:11","05-03-2025 16:59:51","05-03-2025 17:27:22","Casc=
aded Incident from TTO4556947","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid fluctuations, site went down because=
 Gen failed to start due to grid bad voltage // He bypassed the grid and st=
arted Gen manually","system","1219731","05-03-2025 17:19:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004499011","Ebeba","=
","05-03-2025 17:19:10","05-03-2025 16:59:51","05-03-2025 17:27:22","Cascad=
ed Incident from TTO4556947","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuations, site went down because G=
en failed to start due to grid bad voltage // He bypassed the grid and star=
ted Gen manually","system","1219723","05-03-2025 17:19:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004499010","OLAMA","=
","05-03-2025 17:19:10","05-03-2025 16:59:51","05-03-2025 17:27:22","Cascad=
ed Incident from TTO4556947","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuations, site went down because G=
en failed to start due to grid bad voltage // He bypassed the grid and star=
ted Gen manually","system","1219725","05-03-2025 17:19:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004499009","OKOA Pea=
ge","","05-03-2025 17:19:10","05-03-2025 16:59:51","05-03-2025 17:27:22","C=
ascaded Incident from TTO4556947","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuations, site went down beca=
use Gen failed to start due to grid bad voltage // He bypassed the grid and=
 started Gen manually","system","1219728","05-03-2025 17:19:10","Sagemcom C=
MR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0004498946","Sou=
s Prefecture","IHS_YND_330, IHS_YND_687, IHS_YND_419, IHS_YND_339, IHS_YND_=
421, IHS_YND_706, IHS_YND_531, IHS_YND_335, IHS_YND_371, IHS_YND_349, IHS_Y=
ND_714, IHS_YND_370, IHS_YND_365, IHS_YND_713","05-03-2025 17:07:29","05-03=
-2025 16:59:51","05-03-2025 17:27:22","Grid fluctuations, site went down be=
cause Gen failed to start due to grid bad voltage // He bypassed the grid a=
nd started Gen manually","Fanda Brice","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","Grid fluctuations, site went down bec=
ause Gen failed to start due to grid bad voltage // He bypassed the grid an=
d started Gen manually","ludovic-anselme.mouliom-mapoure@sagemcom","459","0=
5-03-2025 17:07:29","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004498387","Mon=
tee Jouvence","","05-03-2025 15:48:55","05-03-2025 15:36:48","05-03-2025 16=
:46:33","Grid outage gen failed to start due to ""high temp"" alarm//We add=
 water and gen manually started ","Hyemafo Gildas","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outag=
e gen failed to sstart due to ""high temp"" alarm//We add water and gen man=
ually started ","ludovic-anselme.mouliom-mapoure@sagemcom","728","05-03-202=
5 15:48:55","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004498282","Man=
guiers Dispensaire","","05-03-2025 15:32:03","05-03-2025 15:08:44","05-03-2=
025 16:45:59","Grid outage, site went down because gen fails to start due t=
o Grid contactor faulty // Gen manually started, power issue resolved at 04=
:45 PM. Site remained down FME TX Armand ngeuts from huawei is i","Fabrice =
Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid=
 outage, site went down because gen fails to start due to Grid contactor fa=
ulty // Gen manually started, power issue resolved at 04:45 PM. Site remain=
ed down FME TX Armand ngeuts from huawei is informed","ludovic-anselme.moul=
iom-mapoure@sagemcom","1400","05-03-2025 15:32:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0004498271","N=
kolso","","05-03-2025 15:30:18","05-03-2025 14:59:53","05-03-2025 15:10:44"=
,"Active// No power issue on Site, Site Gen : Tecnician Ako Arthur/65571342=
9/ Telis working on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// N=
o power issue on Site, Site Gen : Tecnician Ako Arthur/655713429/ Telis wor=
king on site","danick.tchakouani@sagemcom.com","1826","05-03-2025 15:30:18"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0004498272","Feb=
e Village","","05-03-2025 15:30:18","05-03-2025 15:22:03","05-03-2025 15:54=
:56","Grid fluctuation, site went down because Gen failed to start due to g=
rid bad voltage No Rcp // He bypassed the grid and started Gen manually","M=
boua Thierry","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because Gen failed to start d=
ue to grid bad voltage No Rcp // He bypassed the grid and started Gen manua=
lly","ludovic-anselme.mouliom-mapoure@sagemcom","497","05-03-2025 15:30:18"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004498218","N=
omayos","","05-03-2025 15:20:01","05-03-2025 14:43:35","05-03-2025 14:59:06=
","Grid Outage site went down due to Main Gen Faulty//Grid Restored","Fanda=
 Brice","Force Majeure","Natural Disaster","Thunderstrike","Equipment Damag=
ed","Grid Outage site went down due to Main Gen Faulty//Grid Restored","lud=
ovic-anselme.mouliom-mapoure@sagemcom","2188","05-03-2025 15:20:01","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004498012","N=
kolbong","","05-03-2025 14:56:04","05-03-2025 14:47:46","05-03-2025 15:02:5=
1","Grid outage, site went down before gen start due to poor battery backup=
 // Gen start automatically","Delor Telezing","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen start automatically","da=
nick.tchakouani@sagemcom.com","500","05-03-2025 14:56:04","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004497872","Tsi=
nga village","","05-03-2025 14:33:09","05-03-2025 14:25:58","05-03-2025 16:=
52:49","Grid outage, site went down because gen failed to start due to Grid=
 contactor faulty // He bypass the Grid contactor and Site is on Grid","Del=
or Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor=
","Grid outage, site went down because gen failed to start due to Grid cont=
actor faulty // He bypass the Grid contactor and Site is on Grid","cedric.t=
iani@sagemcom.com","432","05-03-2025 14:33:09","Sagemcom CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004497846","Odz=
a Minkan IHS","","05-03-2025 14:27:39","05-03-2025 14:24:17","05-03-2025 14=
:25:03","Active//No Power issue on site U=3D54.2V site on Grid.  The Tx Fme=
 Lionel Adjep/655184876/From HUAWEI is informed and Site UP at=3D02:49 PM",=
"Albran Byorel","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active//No Power issue on site U=3D54.2V site o=
n Grid.  The Tx Fme Lionel Adjep/655184876/From HUAWEI is informed and Site=
 UP at=3D02:49 PM","wilfried.kameni@sagemcom.com","203","05-03-2025 14:27:3=
9","Sagemcom CMR"
"Closed Complete","Warning","T3220","IHS_YND_765","NOCINC0004497800","MBALN=
GONG LYCEE","","05-03-2025 14:19:37","","","Grid Outage Site went alarms be=
cause Gen Failed to Start due to Gen Overload//Grid Restored","Fanda Brice"=
,"Warning","Warning","POWER","Warning - Low Voltage","Grid Outage Site went=
 alarms because Gen Failed to Start due to Gen Overload//Grid Restored","ce=
dric.tiani@sagemcom.com","905","05-03-2025 14:19:37","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004497796","Ole=
mbe MTN","","05-03-2025 14:19:02","05-03-2025 13:58:47","05-03-2025 14:48:3=
0","Grid outage, site alarm because gen failed to start due to grid contact=
or faulty // He bypassed Grid contactor and started Gen manualy","Fabrice P=
ouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid =
outage, site alarm because gen failed to start due to grid contactor faulty=
 // He bypassed Grid contactor and started Gen manualy","cedric.tiani@sagem=
com.com","1216","05-03-2025 14:19:02","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004497747","Mvo=
g-Manga","","05-03-2025 14:12:31","05-03-2025 13:48:15","05-03-2025 16:41:4=
0"," Site went down due to CB (80A) Disjunted in the DC-Box because  the Lo=
ad Increase //He reamed the CB(80A)","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Circuit Breaker Issue"," Site went =
down due to CB (80A) Disjunted in the DC-Box because  the Load Increase //H=
e reamed the CB(80A)","cedric.tiani@sagemcom.com","1458","05-03-2025 14:12:=
31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004497716","ETOUDI C=
HAPELLE","","05-03-2025 14:06:31","05-03-2025 13:47:40","05-03-2025 14:37:1=
9","Cascaded Incident from TTO4555412","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage.gen failed to star=
t due to card Ge Dysfunctionning//We reset card GE and gen manually started=
 ","system","288871","05-03-2025 14:06:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004497715","Abattoir=
","","05-03-2025 14:06:31","05-03-2025 13:47:40","05-03-2025 14:37:19","Cas=
caded Incident from TTO4555412","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due =
to card Ge Dysfunctionning//We reset card GE and gen manually started ","sy=
stem","288872","05-03-2025 14:06:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0004497717","Etoudi 2=
","","05-03-2025 14:06:31","05-03-2025 13:47:40","05-03-2025 14:37:19","Cas=
caded Incident from TTO4555412","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due =
to card Ge Dysfunctionning//We reset card GE and gen manually started ","sy=
stem","288872","05-03-2025 14:06:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0004497712","B=
otmakak","IHS_EDA_101","05-03-2025 14:06:03","05-03-2025 13:57:40","05-03-2=
025 13:59:51","Active//No power issue on site U=3D54V site on Gen , The Tx =
FME Etienne/651320188/ from Huawei is informed and Site UP at=3D02;15 PM","=
Kemeni Franklin","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active//No power issue on site U=3D54V site on=
 Gen , The Tx FME Etienne/651320188/ from Huawei is informed and Site UP at=
=3D02;15 PM","mariam.tchonang@sagemcom.com","504","05-03-2025 14:06:03","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0004497706","San=
ta Barbara Gottam","","05-03-2025 14:04:00","05-03-2025 13:55:19","05-03-20=
25 15:53:08","Grid outage, Site went down because Gen started and stopped w=
ith alarm ""under current""// He reset Gen card and started Gen manualy","D=
elor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, Site went down because Gen started and stopped with alarm =
""under current""// He reset Gen card and started Gen manualy","cedric.tian=
i@sagemcom.com","522","05-03-2025 14:04:00","Sagemcom CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004497693","Par=
adis Hotel","","05-03-2025 14:01:20","05-03-2025 13:51:05","05-03-2025 16:0=
3:23","Grid outage site went down because Gen failed to start due to static=
 charger faulty //Gen manually started with external battery","Siligap Bori=
s","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid=
 outage site went down because Gen failed to start due to static charger fa=
ulty //Gen manually started with external battery","cedric.tiani@sagemcom.c=
om","616","05-03-2025 14:01:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0004497648","Nyom OCM=
","","05-03-2025 13:55:29","05-03-2025 12:56:24","05-03-2025 14:40:41","Cas=
caded Incident from TTO4555399","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen start and stopped du=
e to solenoid issue //We fixed solenoid and gen manually started","system",=
"291823","05-03-2025 13:55:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0004497649","Messassi=
 2","","05-03-2025 13:55:29","05-03-2025 12:56:24","05-03-2025 14:40:41","C=
ascaded Incident from TTO4555399","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen start and stopped =
due to solenoid issue //We fixed solenoid and gen manually started","system=
","291824","05-03-2025 13:55:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0004497646","Olembe-T=
erminus","","05-03-2025 13:55:29","05-03-2025 12:56:24","05-03-2025 14:40:4=
1","Cascaded Incident from TTO4555399","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage.gen start and sto=
pped due to solenoid issue //We fixed solenoid and gen manually started","s=
ystem","291824","05-03-2025 13:55:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0004497647","Messassi=
","","05-03-2025 13:55:29","05-03-2025 12:56:24","05-03-2025 14:40:41","Cas=
caded Incident from TTO4555399","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen start and stopped du=
e to solenoid issue //We fixed solenoid and gen manually started","system",=
"291823","05-03-2025 13:55:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0004497641","F=
OUGEROLE","","05-03-2025 13:54:28","05-03-2025 13:49:11","05-03-2025 15:07:=
31","Grid outage, site went down because gen fails to start due to High tem=
p // He added water and manually start the gen","Siligap Boris","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","Grid outage, site went down because gen fails to start due to High temp =
// He added water and manually start the gen","mariam.tchonang@sagemcom.com=
","318","05-03-2025 13:54:28","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004497630","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","05-03-2025 13:52:03","05-03-2=
025 13:47:40","05-03-2025 14:37:19","Grid outage.gen failed to start due to=
 card Ge Dysfunctionning//We reset card GE and gen manually started ","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage.gen failed to start due to card Ge Dysfunctionning//We reset =
card GE and gen manually started ","cedric.tiani@sagemcom.com","264","05-03=
-2025 13:52:03","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004497622","NKO=
MEKUI OCM","","05-03-2025 13:49:14","05-03-2025 13:45:00","05-03-2025 13:46=
:15","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted b=
y Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted =
by Mbankolo Camtel and not managing by IHS","cedric.tiani@sagemcom.com","25=
5","05-03-2025 13:49:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004497616","Crf-Mban=
kolo-IHS","","05-03-2025 13:48:10","05-03-2025 13:35:11","05-03-2025 13:47:=
37","Cascaded Incident from TTO4555280","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation, site went do=
wn because Gen failed to start due to grid bad voltage No crcp // He bypass=
ed the grid and started Gen manually","system","296975","05-03-2025 13:48:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004497517","Jea=
n Vespa","IHS_YND_574","05-03-2025 13:39:54","05-03-2025 13:35:11","05-03-2=
025 13:47:37","Grid fluctuation, site went down because Gen failed to start=
 due to grid bad voltage No crcp // He bypassed the grid and started Gen ma=
nually","Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid fluctuation, site went down because Gen failed =
to start due to grid bad voltage No crcp // He bypassed the grid and starte=
d Gen manually","cedric.tiani@sagemcom.com","284","05-03-2025 13:39:54","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0004497451","E=
mombo 2","","05-03-2025 13:35:15","05-03-2025 13:31:53","05-03-2025 13:32:2=
3","Active//No power issue, U=3D54 V Site on Grid The TX FME Armand (691144=
412) from Huawei is informed ","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power=
 issue, U=3D54 V Site on Grid The TX FME Armand (691144412) from Huawei is =
informed ","mariam.tchonang@sagemcom.com","203","05-03-2025 13:35:15","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004497341","N=
kozoa","","05-03-2025 13:32:55","05-03-2025 13:30:45","05-03-2025 14:40:12"=
,"Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Feli=
x bateu is informed and confirmed// He reduced the load and gen manually st=
arted","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage, site went down due to gen overload (20kva, 340A) SS H=
IS Felix bateu is informed and confirmed// He reduced the load and gen manu=
ally started","mariam.tchonang@sagemcom.com","132","05-03-2025 13:32:55","S=
agemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0004497319","AFE=
ME NORD","","05-03-2025 13:31:22","05-03-2025 13:07:12","05-03-2025 13:08:2=
2","Active//No power issue, Site on Gen and Ubaie=3D 54,6V The TX Mouhamado=
u (6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue, Site on Gen and Ubaie=3D 54,6V The TX Mouhamadou =
(6144435) from Huawei is informed.","cedric.tiani@sagemcom.com","1451","05-=
03-2025 13:31:22","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004497276","NKO=
LMEKONG YDE","","05-03-2025 13:29:50","05-03-2025 12:56:24","05-03-2025 14:=
40:41","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid outage.gen start and stopped due to solenoid issue //=
We fixed solenoid and gen manually started","cedric.tiani@sagemcom.com","20=
07","05-03-2025 13:29:50","Sagemcom CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0004497273","Mba=
lla 4","","05-03-2025 13:29:00","05-03-2025 13:27:49","05-03-2025 13:43:32"=
,"Grid outage, Site went down because Gen failed to start// Grid return (in=
vestigation ongoing)","Delor Telezing","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage, Site went down because Gen failed =
to start// Grid return (investigation ongoing)","cedric.tiani@sagemcom.com"=
,"72","05-03-2025 13:29:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004497266","Jean Ves=
pa 2","","05-03-2025 13:27:40","05-03-2025 13:14:10","05-03-2025 13:38:39",=
"Cascaded Incident from TTO4554995","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause Gen failed to start due to grid bad voltage No Rcp // He bypassed th=
e grid and started Gen manually","system","305347","05-03-2025 13:27:40","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004497263","J=
-Vespa","IHS_YND_544","05-03-2025 13:27:17","05-03-2025 13:14:10","05-03-20=
25 13:38:39","Grid fluctuation, site went down because Gen failed to start =
due to grid bad voltage No Rcp // He bypassed the grid and started Gen manu=
ally","Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid fluctuation, site went down because Gen failed to=
 start due to grid bad voltage No Rcp // He bypassed the grid and started G=
en manually","mariam.tchonang@sagemcom.com","788","05-03-2025 13:27:17","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004497243","Nko=
lnda","","05-03-2025 13:25:00","05-03-2025 13:16:43","05-03-2025 14:49:27",=
"Site went down because Gen failed to start due to CB Gen (32A) tripped due=
 to lightning// He rearmed CB and site on gen","Albran Byorel","Force Majeu=
re","Natural Disaster","Thunderstrike","Equipment Damaged","Site went down =
because Gen failed to start due to CB Gen (32A) tripped due to lightning// =
He rearmed CB and site on gen","cedric.tiani@sagemcom.com","498","05-03-202=
5 13:25:00","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004497238","Nko=
londom","","05-03-2025 13:24:11","05-03-2025 13:15:54","05-03-2025 14:05:54=
","Site went down because gen fails to start due to grid bad voltage // He =
bypass grid and manually start the gen","Fabrice Pouakam","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Site went down bec=
ause gen fails to start due to grid bad voltage // He bypass grid and manua=
lly start the gen","cedric.tiani@sagemcom.com","499","05-03-2025 13:24:11",=
"Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004497236","Nko=
abang2","","05-03-2025 13:23:37","05-03-2025 13:07:24","05-03-2025 16:45:20=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","cedric.t=
iani@sagemcom.com","974","05-03-2025 13:23:37","Sagemcom CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0004497223","LOB=
O MTN","","05-03-2025 13:21:57","05-03-2025 12:50:37","05-03-2025 12:52:29"=
,"Active//No power issue, Site on Gen and Ubaie=3D 55,1V The TX Mouhamadou =
(6144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue, Site on Gen and Ubaie=3D 55,1V The TX Mouhamadou (6=
144435) from Huawei is informed.","cedric.tiani@sagemcom.com","1881","05-03=
-2025 13:21:57","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004497218","NYO=
M FACE MAETUR","","05-03-2025 13:21:03","05-03-2025 13:03:53","06-03-2025 1=
3:14:54","Site went down due to 03 Rectifiers faulty caused by heavy rain, =
SS IHS Bernard Atangana confirmed","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","Site went down due to 03 Rectifiers =
faulty caused by heavy rain, SS IHS Bernard Atangana confirmed","cedric.tia=
ni@sagemcom.com","1031","05-03-2025 13:21:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004497209","N=
kolfon Cimencam","","05-03-2025 13:19:18","05-03-2025 13:01:02","05-03-2025=
 13:10:07","Active//No power issue, Site on Grid Ubai=3D 52,8V. Notice that=
 it is impacted by Afanoya II The Tx FME Fulbert from Huawei is informed","=
Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 52=
,8V. Notice that it is impacted by Afanoya II The Tx FME Fulbert from Huawe=
i is informed","mariam.tchonang@sagemcom.com","1097","05-03-2025 13:19:18",=
"Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004497198","Ngo=
usso Vallee","","05-03-2025 13:18:24","05-03-2025 12:59:09","05-03-2025 16:=
06:31","Grid Outage  Site went down because Gen stopped with alarm"" low oi=
l pressure "" (unprouven Alarm)  //He reset Gen card and started Gen manaul=
ly","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","Grid Outage  Site went down because Gen stopped with alarm"" low o=
il pressure "" (unprouven Alarm)  //He reset Gen card and started Gen manau=
lly","cedric.tiani@sagemcom.com","1156","05-03-2025 13:18:24","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004497196","B=
arriere IHS","","05-03-2025 13:17:41","05-03-2025 12:59:30","05-03-2025 15:=
21:14","Grid outage, Site went down because Gen failed to start due to PWC =
dysfunctionning IHS Supervisor Felix Zambe confirmed// He reset it and redu=
ced the load, site is on Gen","Hyemafo Gildas","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage, Site went down bec=
ause Gen failed to start due to PWC dysfunctionning IHS Supervisor Felix Za=
mbe confirmed// He reset it and reduced the load, site is on Gen","mariam.t=
chonang@sagemcom.com","1093","05-03-2025 13:17:41","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004497194","Nom=
ayos montee Meche","","05-03-2025 13:17:32","05-03-2025 12:59:15","05-03-20=
25 13:00:28","ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On G=
rid The Tx FME Fulbert(654266068) from Huawei is informed and Site up at =
=3D01:31 PM","Fanda Brice","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue on site GRID =
, Ubaie=3D54.5V site On Grid The Tx FME Fulbert(654266068) from Huawei is i=
nformed and Site up at =3D01:31 PM","cedric.tiani@sagemcom.com","1098","05-=
03-2025 13:17:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004497177","B=
iyemassi LAC","","05-03-2025 13:14:52","05-03-2025 12:57:19","05-03-2025 13=
:35:24","Grid outage ,no space to deploy mobile gen //Grid power restored",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage ,no space to deploy mobile gen //Grid power restored","mariam.tchon=
ang@sagemcom.com","1054","05-03-2025 13:14:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004497165","B=
arriere","","05-03-2025 13:13:06","05-03-2025 12:56:49","05-03-2025 13:29:4=
3","Grid outage, Site went because Gen started and stopped due Gen Overload=
 (20KVA, 450A) SS IHS Felix Zambe confirmed// Grid power return","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge, Site went because Gen started and stopped due Gen Overload (20KVA, 450A=
) SS IHS Felix Zambe confirmed// Grid power return","mariam.tchonang@sagemc=
om.com","978","05-03-2025 13:13:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004497154","M=
ini-Ferme","","05-03-2025 13:11:51","05-03-2025 12:55:14","05-03-2025 13:39=
:32","Grid outage, No space to deploy MDG// Grid restored","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spac=
e to deploy MDG// Grid restored","mariam.tchonang@sagemcom.com","998","05-0=
3-2025 13:11:51","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004497151","Beh=
ind P T school Yde","","05-03-2025 13:11:06","05-03-2025 13:06:40","05-03-2=
025 16:04:31","Grid outage, site went down because gen failed to start due =
to gen card faulty //Gen manually started","Paul BIBOUM","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down b=
ecause gen failed to start due to gen card faulty //Gen manually started","=
cedric.tiani@sagemcom.com","267","05-03-2025 13:11:06","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004497140","Ako=
k Ndoe Yde","","05-03-2025 13:09:18","05-03-2025 14:54:34","05-03-2025 17:1=
3:35","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start manualy","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start manualy","cedric.tian=
i@sagemcom.com","52629","05-03-2025 13:09:18","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004497130","BIY=
EMASSI NIKI","","05-03-2025 13:06:45","05-03-2025 12:59:28","05-03-2025 13:=
38:30","Grid outage, site went down down due PWC overloaded (12 kw 250A) //=
 Load reduice and Site is on Grid","Hyemafo Gildas","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Grid outage, site went dow=
n down due PWC overloaded (12 kw 250A) // Load reduice and Site is on Grid"=
,"cedric.tiani@sagemcom.com","438","05-03-2025 13:06:45","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004497124","CRH=
-Etoug-Ebe","","05-03-2025 13:05:42","05-03-2025 12:58:24","05-03-2025 13:1=
5:07","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen automatically started","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen automatically start=
ed","cedric.tiani@sagemcom.com","439","05-03-2025 13:05:42","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0004497120","Ole=
mbe","IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_303, IHS_YND_280","05-=
03-2025 13:04:42","05-03-2025 12:56:24","05-03-2025 14:40:41","Grid outage.=
gen start and stopped due to solenoid issue //We fixed solenoid and gen man=
ually started","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Solenoid Coil","Grid outage.gen start and stopped due to solenoid iss=
ue //We fixed solenoid and gen manually started","cedric.tiani@sagemcom.com=
","3240","05-03-2025 13:04:42","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004497119","Nko=
ulou Carriere carrefourt","","05-03-2025 13:03:47","05-03-2025 12:53:27","0=
5-03-2025 13:04:34","Active//No power issue, U=3D53,3 on Gen, Tx FME lionel=
 steve adjep/655124876/ From huawei is informed and up at 01:04 PM","Mba La=
zare Herve","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue, U=3D53,3 on Gen, Tx FME lio=
nel steve adjep/655124876/ From huawei is informed and up at 01:04 PM","ced=
ric.tiani@sagemcom.com","621","05-03-2025 13:03:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004497095","E=
MANA BILICK CITY","","05-03-2025 12:57:46","05-03-2025 12:48:26","05-03-202=
5 14:46:15","Grid outage, Site went down because Gen failed to start due to=
 ATS faulty// Grid Restored","Fabrice Pouakam","Equipment Repair","Passive"=
,"Control Panel","ATS-AMF Issue","Grid outage, Site went down because Gen f=
ailed to start due to ATS faulty// Grid Restored","mariam.tchonang@sagemcom=
.com","561","05-03-2025 12:57:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0004497092","E=
mombo","","05-03-2025 12:56:13","05-03-2025 12:47:53","05-03-2025 12:50:51"=
,"Active// No power issue, site is on Grid with Ubaie=3D54,6V, Lionel Adjep=
(655184876) from Huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power issue, site is on Grid with Ubaie=3D54,6V, Lionel Adjep(65518487=
6) from Huawei is informed","mariam.tchonang@sagemcom.com","501","05-03-202=
5 12:56:13","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004497084","Tou=
ring Club International","","05-03-2025 12:54:09","05-03-2025 12:53:58","05=
-03-2025 16:01:58","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed // Grid return	","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went dow=
n because Gen overload (20Kw, 270A) SS IHS Pascaline confirmed // Grid retu=
rn	","cedric.tiani@sagemcom.com","12","05-03-2025 12:54:09","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004497076","Pha=
rmacie SION","","05-03-2025 12:53:09","05-03-2025 12:50:57","05-03-2025 13:=
00:51","Grid outage, Site went down before Gen start due to poor backup// G=
en started automatically","Paul BIBOUM","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automatically","cedric.tiani@sa=
gemcom.com","134","05-03-2025 12:53:09","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004497074","Ebo=
go","","05-03-2025 12:52:31","05-03-2025 12:39:15","05-03-2025 12:52:57","G=
rid outage, Site went down before Gen start due to poor backup // Gen start=
ed automaticaly","Siligap Boris","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup // Gen started automaticaly","cedric.tiani@sagemcom.=
com","42337","05-03-2025 12:52:31","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004497069","NYO=
M 2 IHS","","05-03-2025 12:51:46","05-03-2025 12:45:22","05-03-2025 13:07:2=
6","Grid outage, site went down before Gen started because CB battery tripp=
ed // Gen started automatically(investigation ongoing)","Fabrice Pouakam","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breake=
r Issue","Grid outage, site went down before Gen started because CB battery=
 tripped // Gen started automatically(investigation ongoing)","cedric.tiani=
@sagemcom.com","385","05-03-2025 12:51:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0004497061","Nkolfoul=
ou Tsinga Village","","05-03-2025 12:50:40","05-03-2025 12:41:15","05-03-20=
25 12:42:21","Cascaded Incident from TTO4554743","Siligap Boris","Cascade O=
utage","Active","Cascade Active","Cascade Active","Active//No power issue U=
=3D54 on grid The fme tx Julien From huawei is informed","system","300212",=
"05-03-2025 12:50:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004497057","S=
OA TOWN","","05-03-2025 12:49:46","05-03-2025 12:42:35","05-03-2025 15:19:1=
4","Site went down due to works our FME Boris (696061575) and Our RM  is wo=
rking on site(Replaced the Gen Card On Site)// End Off work","Siligap Boris=
","Installation Activity","Passive","Planned Activity","Installation Activi=
ty","Site went down due to works our FME Boris (696061575) and Our RM  is w=
orking on site(Replaced the Gen Card On Site)// End Off work","mariam.tchon=
ang@sagemcom.com","432","05-03-2025 12:49:46","Sagemcom CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004497055","Nko=
lfoulou","IHS_YND_759","05-03-2025 12:49:31","05-03-2025 12:41:15","05-03-2=
025 12:42:21","Active//No power issue U=3D54 on grid The fme tx Julien From=
 huawei is informed","Siligap Boris","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue U=
=3D54 on grid The fme tx Julien From huawei is informed","cedric.tiani@sage=
mcom.com","497","05-03-2025 12:49:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004496887","E=
kombitie","","05-03-2025 12:23:42","05-03-2025 12:20:31","05-03-2025 12:25:=
38","Active: no power issue, site is on Gen with Ubaie=3D54,5V, Symphorien(=
650257151) from huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","Affected by 3rd Party Site","A=
ctive: no power issue, site is on Gen with Ubaie=3D54,5V, Symphorien(650257=
151) from huawei is informed","cedric.tiani@sagemcom.com","193","05-03-2025=
 12:23:42","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004496860","ETO=
UDI Entree du palais","","05-03-2025 12:19:46","05-03-2025 12:14:35","05-03=
-2025 12:20:29","Grid outage, Site went down before Gen start due to poor b=
ackup // Grid return","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup // Grid return","cedric.tiani@sagemcom.com","=
313","05-03-2025 12:19:46","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004496737","Sap=
eur","","05-03-2025 11:54:03","05-03-2025 11:47:31","05-03-2025 11:55:25","=
Grid outage, Site went down before Gen start due to poor backup// Gen start=
ed automatically","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup// Gen started automatically","cedric.tiani@sagemcom=
.com","393","05-03-2025 11:54:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004496590","M=
imboman-Ecole","","05-03-2025 11:40:33","05-03-2025 11:32:46","05-03-2025 1=
3:31:31","Site went down because CB rectifiers tripped // CB put back on (i=
nvestigation ongoing)","Mba Lazare Herve","Equipment Repair","Passive","Rec=
tifier","Rectifier - Circuit Breaker","Site went down because CB rectifiers=
 tripped // CB put back on (investigation ongoing)","mariam.tchonang@sagemc=
om.com","469","05-03-2025 11:40:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004496426","E=
vodoula OCM","","05-03-2025 11:17:08","05-03-2025 10:38:34","05-03-2025 13:=
26:19","Grid Outage Site went down because Gen stopped with alarm under-vol=
tage //We reset card GE and Gen manually started","TIENTCHEU NZETCHIEU GAEL=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outa=
ge Site went down because Gen stopped with alarm under-voltage //We reset c=
ard GE and Gen manually started","mariam.tchonang@sagemcom.com","2315","05-=
03-2025 11:17:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004496242","B=
ATA Mokolo OCM","","05-03-2025 10:50:34","05-03-2025 10:46:00","06-03-2025 =
00:30:28","Grid outage, No space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No =
space to deploy MDG // Grid return","cedric.tiani@sagemcom.com","275","05-0=
3-2025 10:50:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004495845","Ebeba","=
","05-03-2025 10:38:28","05-03-2025 09:11:10","05-03-2025 09:44:09","Cascad=
ed Incident from TTO4552680","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Site went down before Gen star=
t due to poor backup // Gen started automatically","system","269702","05-03=
-2025 10:38:28","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004495831","Bit=
eng-Maetur","","05-03-2025 10:37:42","05-03-2025 10:34:02","05-03-2025 12:5=
1:01","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","Mb=
a Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage, Site went down because Gen started and stopped due to Gen over=
load(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","cedric.ti=
ani@sagemcom.com","221","05-03-2025 10:37:42","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0004495637","Jou=
vence 2000","","05-03-2025 10:31:43","05-03-2025 10:16:19","05-03-2025 11:1=
4:20","Grid outage.gen failed to start due to battery GE faulty//Gen manual=
ly started with external battery","Delor Telezing","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Generator Battery","Grid outage.gen failed to start=
 due to battery GE faulty//Gen manually started with external battery","ced=
ric.tiani@sagemcom.com","925","05-03-2025 10:31:43","Sagemcom CMR"
"Closed Complete","Site Down","T1107-1","IHS_YND_217","NOCINC0004495364","A=
bom","","05-03-2025 09:58:32","05-03-2025 09:53:11","05-03-2025 09:55:59","=
No power issue site on grid with U=3D54.8V,Symphorien(675295205) from Huawe=
i is informed","Siligap Boris","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with=
 U=3D54.8V,Symphorien(675295205) from Huawei is informed","cedric.tiani@sag=
emcom.com","322","05-03-2025 09:58:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004495245","S=
hell-Nsimeyong","","05-03-2025 09:38:03","05-03-2025 09:33:37","05-03-2025 =
09:37:14","No power issue U =3D52.1V site on Grid.  The FME TX Mbah Hosiah =
(674007438/699699694) from Huawei is informed. Repetitive Issue","MINKA NIC=
OLAS","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue U =3D52.1V site on Grid.The FME TX Mbah Ho=
siah (674007438/699699694) from Huawei is informed. Repetitive Issue","cedr=
ic.tiani@sagemcom.com","267","05-03-2025 09:38:03","Sagemcom CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0004495208","Nke=
ng likok","IHS_YND_339","05-03-2025 09:29:37","05-03-2025 09:11:10","05-03-=
2025 09:44:09","Grid outage, Site went down before Gen start due to poor ba=
ckup // Gen started automatically","Kemeni Franklin","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site wen=
t down before Gen start due to poor backup // Gen started automatically","c=
edric.tiani@sagemcom.com","1108","05-03-2025 09:29:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004494903","E=
ssomba","","05-03-2025 08:11:03","05-03-2025 08:04:36","05-03-2025 17:04:11=
","Site went down due to MPR disfunction SS IHS Alphonse DEFFO confirmed //=
 He replaced MPR ","Mba Lazare Herve","Equipment Repair","Passive","Rectifi=
er","Rectifier Cabinet","Site went down due to MPR disfunction SS IHS Alpho=
nse DEFFO confirmed // He replaced MPR ","mariam.tchonang@sagemcom.com","38=
8","05-03-2025 08:11:03","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004494873","Elo=
umdem stade","","05-03-2025 08:01:32","05-03-2025 07:58:12","05-03-2025 08:=
05:44","Grid outage, Site went down before Gen start due to poor backup// G=
en started automatically","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automatically","mariam.tchonang=
@sagemcom.com","201","05-03-2025 08:01:32","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004494826","Nko=
l-Mbanda","","05-03-2025 07:50:31","05-03-2025 07:45:19","05-03-2025 21:45:=
35","Site went down due to insuffience of rectifier SS IHS FRANCOIS confirm=
ed// He added 01 rectifier","MINKA NICOLAS","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down due to insuffience of rectifie=
r SS IHS FRANCOIS confirmed// He added 01 rectifier","cedric.tiani@sagemcom=
.com","313","05-03-2025 07:50:31","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004494818","Nko=
g-Edzen","","05-03-2025 07:47:34","05-03-2025 07:44:57","05-03-2025 07:58:4=
9","Active: No power issue on site, site on Gen  The Team aubin (694427963 =
) from I-ENG  is Working on site","Parker Tchoup","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No po=
wer issue on site, site on Gen  The Team aubin (694427963 ) from I-ENG  is =
Working on site","cedric.tiani@sagemcom.com","158","05-03-2025 07:47:34","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004494815","M=
ini-Ferme","","05-03-2025 07:46:26","05-03-2025 07:45:15","05-03-2025 07:47=
:07","Site went down due to insufficient rectifier on site,RM Bikek //He re=
duced the load and site on grid","","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down due to insufficient rectifier on site,=
RM Bikek //He reduced the load and site on grid","cedric.tiani@sagemcom.com=
","72","05-03-2025 07:46:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004494807","A=
kak-Nkozoa-MTN-IHS","","05-03-2025 07:43:57","05-03-2025 07:41:25","05-03-2=
025 08:57:49","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid Gen, Site down due to disjunction in the DC bo=
x // We have lifted the circuit breaker","cedric.tiani@sagemcom.com","26781=
1","05-03-2025 07:43:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004494791","O=
LAMA","","05-03-2025 07:40:17","05-03-2025 07:35:02","05-03-2025 07:40:24",=
"Active//No power issue on site Ubaie =3D54.9V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.9V site on Grid The TX FME Henri (69994969=
3) from Huawei is informed","mariam.tchonang@sagemcom.com","316","05-03-202=
5 07:40:17","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004494682","Mes=
sassi 2","","05-03-2025 07:36:47","05-03-2025 07:34:31","05-03-2025 07:44:1=
3","ACTIVE//No power issue iste on grid with U=3D52.7V  FME  Symphorien (69=
1316854) from Huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No =
power issue iste on grid with U=3D52.7V  FME  Symphorien (691316854) from H=
uawei is informed","cedric.tiani@sagemcom.com","138","05-03-2025 07:36:47",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004494487","M=
efou-Assi","","05-03-2025 06:59:24","05-03-2025 06:54:07","05-03-2025 07:00=
:44","Active// No power issue on site  Ubaie=3D54.5V site On battery The Tx=
 FME Fulbert(654266068) of huawei is informed","Fanda Brice","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue on site  Ubaie=3D54.5V site On battery The Tx FME Ful=
bert(654266068) of huawei is informed","mariam.tchonang@sagemcom.com","319"=
,"05-03-2025 06:59:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004494470","M=
imboman-Ecole","","05-03-2025 06:55:34","05-03-2025 06:52:22","05-03-2025 0=
6:56:31","Grid outage, Site went down before Gen start due to poor backup /=
/ Gen started automaticaly","Mba Lazare Herve","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor backup // Gen started automaticaly","mariam.t=
chonang@sagemcom.com","193","05-03-2025 06:55:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0004494384","T=
SINGA VILLAGE 2","","05-03-2025 06:36:29","05-03-2025 06:30:15","05-03-2025=
 07:59:52","Site went down because gen start and stopped with alarm ''Faile=
d to start'' //He reset the Gen card","Delor Telezing","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Site went down because gen star=
t and stopped with alarm ''Failed to start'' //He reset the Gen card","mari=
am.tchonang@sagemcom.com","375","05-03-2025 06:36:29","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004494121","Bon=
djock","","05-03-2025 06:13:20","05-03-2025 05:26:50","05-03-2025 22:21:08"=
,"","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Grid outage, Site went down because gen start and stopped with alarm=
"" High temps""// he added water and manually start the Gen","wilfried.kame=
ni@sagemcom.com","2791","05-03-2025 06:13:20","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004493846","Nko=
lmvack","","05-03-2025 04:29:16","05-03-2025 04:22:18","05-03-2025 05:24:28=
","Grid outage, site went down because gen start and stopped with high temp=
 alarm // He added water and Gen started manually","Parker Tchoup","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Is=
sue","Grid outage, site went down because gen start and stopped with high t=
emp alarm // He added water and Gen started manually","wilfried.kameni@sage=
mcom.com","419","05-03-2025 04:29:16","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004493792","AKA=
K Nkozoa","","05-03-2025 04:04:19","05-03-2025 03:55:08","05-03-2025 04:51:=
20","Grid outage, site went down because gen start and stopped with over cu=
rrent alarm(Unpruven alarm) // Reset of gen card done and gen started","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","Grid outage, site went down because gen start and stopped with over curr=
ent alarm(Unpruven alarm) // Reset of gen card done and gen started","wilfr=
ied.kameni@sagemcom.com","552","05-03-2025 04:04:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004493610","M=
efou-Assi","","05-03-2025 02:42:57","05-03-2025 02:38:49","05-03-2025 02:43=
:58","ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The =
Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed","yves.djomo@sagemcom.com","2=
49","05-03-2025 02:42:57","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004493481","An-=
Marche-Melen","","05-03-2025 01:46:15","05-03-2025 01:39:07","06-03-2025 13=
:40:46","Grid Outage No Space to deploy a MDG //Grid return ","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Sp=
ace to deploy a MDG //Grid return ","wilfried.kameni@sagemcom.com","3091","=
05-03-2025 01:46:15","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004493136","Nko=
l-Mbanda","","04-03-2025 23:59:41","04-03-2025 23:57:32","05-03-2025 07:18:=
23","Site went down due to insufficient rectifiers on site,SS HIS Francois =
is informed and confirmed//He reset it","MINKA NICOLAS","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","Site went down due to insufficien=
t rectifiers on site,SS HIS Francois is informed and confirmed//He reset it=
","wilfried.kameni@sagemcom.com","130","04-03-2025 23:59:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004493098","E=
ssomba","","04-03-2025 23:48:18","04-03-2025 23:39:08","05-03-2025 00:13:43=
","Site went dosn because the  MPR Dysfonction on site due load // He reset=
 the MPR on site","Mba Lazare Herve","Equipment Repair","Passive","Rectifie=
r","Rectifier Cabinet","Site went dosn because the  MPR Dysfonction on site=
 due load // He reset the MPR on site","wilfried.kameni@sagemcom.com","552"=
,"04-03-2025 23:48:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004492942","B=
ATA Mokolo OCM","","04-03-2025 23:11:51","04-03-2025 23:10:45","04-03-2025 =
23:35:45","Grid outage, No space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No =
space to deploy MDG // Grid return","yves.djomo@sagemcom.com","67","04-03-2=
025 23:11:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004492863","S=
hell-Nsimeyong","","04-03-2025 22:54:30","04-03-2025 22:53:23","04-03-2025 =
22:59:23","no power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed. Notice that we have repetitive=
 issue","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","no power issue U =3D52.2V site on Grid.=
The FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Notic=
e that we have repetitive issue","yves.djomo@sagemcom.com","68","04-03-2025=
 22:54:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004492252","A=
wae Ewonkan","","04-03-2025 21:14:09","04-03-2025 21:13:05","04-03-2025 22:=
34:37","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // =
He reduced the load","yves.djomo@sagemcom.com","65","04-03-2025 21:14:09","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004492091","E=
kombitie","","04-03-2025 20:44:17","04-03-2025 20:29:54","04-03-2025 20:35:=
18","Active: no power issue, site is on Gen with Ubaie=3D55V, Symphorien(65=
0257151) from huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no =
power issue, site is on Gen with Ubaie=3D55V, Symphorien(650257151) from hu=
awei is informed","yves.djomo@sagemcom.com","864","04-03-2025 20:44:17","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004491990","E=
ssomba","","04-03-2025 20:20:05","04-03-2025 20:10:00","04-03-2025 20:15:42=
","Active: No power issue, site is on Grid with Ubaie=3D54.1V, The fme tx G=
eorge //697461814//from Huawei is informed. Notice Dysjunction at the BTS O=
CM","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Active: No power issue, site is on Grid =
with Ubaie=3D54.1V, The fme tx George //697461814//from Huawei is informed.=
 Notice Dysjunction at the BTS OCM","yves.djomo@sagemcom.com","607","04-03-=
2025 20:20:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_288","NOCINC0004491904","Meyong P=
lateau","","04-03-2025 20:04:20","04-03-2025 19:18:38","04-03-2025 19:52:44=
","Cascaded Incident from TTO4548419","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Site went down becaus=
e cable burned in PWC due to load increase// He replaced cable burned ","sy=
stem","269231","04-03-2025 20:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_729","NOCINC0004491546","Nkolbiss=
on IITA LP","","04-03-2025 19:22:11","04-03-2025 19:18:38","04-03-2025 19:5=
2:44","Cascaded Incident from TTO4548419","","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because cable burned in PW=
C due to load increase// He replaced cable burned ","system","269231","04-0=
3-2025 19:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0004491548","Nkolbiss=
on usines des eaux 2","","04-03-2025 19:22:11","04-03-2025 19:18:38","04-03=
-2025 19:52:44","Cascaded Incident from TTO4548419","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Site we=
nt down because cable burned in PWC due to load increase// He replaced cabl=
e burned ","system","269233","04-03-2025 19:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004491547","AFEME NO=
RD","","04-03-2025 19:22:11","04-03-2025 19:18:38","04-03-2025 19:52:44","C=
ascaded Incident from TTO4548419","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because ca=
ble burned in PWC due to load increase// He replaced cable burned ","system=
","269230","04-03-2025 19:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_285","NOCINC0004491545","Nkolbiss=
on","","04-03-2025 19:22:11","04-03-2025 19:18:38","04-03-2025 19:52:44","C=
ascaded Incident from TTO4548419","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because ca=
ble burned in PWC due to load increase// He replaced cable burned ","system=
","269232","04-03-2025 19:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0004491544","Oyomaban=
g Ecole","","04-03-2025 19:22:10","04-03-2025 19:18:38","04-03-2025 19:52:4=
4","Cascaded Incident from TTO4548419","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Passive","Cascade Passive","Cascade Passive","Site went down becau=
se cable burned in PWC due to load increase// He replaced cable burned ","s=
ystem","269233","04-03-2025 19:22:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0004491541","Mbankolo=
 petit paris","","04-03-2025 19:22:10","04-03-2025 19:18:38","04-03-2025 19=
:52:44","Cascaded Incident from TTO4548419","Mboua Thierry","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down because cab=
le burned in PWC due to load increase// He replaced cable burned ","system"=
,"269230","04-03-2025 19:22:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0004491542","Nkolbi-B=
oss","","04-03-2025 19:22:10","04-03-2025 19:18:38","04-03-2025 19:52:44","=
Cascaded Incident from TTO4548419","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down because c=
able burned in PWC due to load increase// He replaced cable burned ","syste=
m","269232","04-03-2025 19:22:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004491543","Nkolkoum=
ou OCM","","04-03-2025 19:22:10","04-03-2025 19:18:38","04-03-2025 19:52:44=
","Cascaded Incident from TTO4548419","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Site went down becaus=
e cable burned in PWC due to load increase// He replaced cable burned ","sy=
stem","269231","04-03-2025 19:22:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0004491530","N=
kolso","IHS_YND_808, IHS_YND_273, IHS_YND_712, IHS_YND_686, IHS_YND_288, IH=
S_YND_285, IHS_YND_729, IHS_YND_519, IHS_YND_763","04-03-2025 19:19:46","04=
-03-2025 19:18:38","04-03-2025 19:52:44","Site went down because cable burn=
ed in PWC due to load increase// He replaced cable burned ","TIENTCHEU NZET=
CHIEU GAEL","Equipment Repair","Passive","Infrastructure","Armoured Cable",=
"Site went down because cable burned in PWC due to load increase// He repla=
ced cable burned ","yves.djomo@sagemcom.com","69","04-03-2025 19:19:46","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004491528","Bon=
djock","","04-03-2025 19:19:07","04-03-2025 19:16:45","04-03-2025 19:38:21"=
,"Grid outage site went down because Gen failed to start // Grid return (in=
vestigation ongoing)","Fanda Brice","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage site went down because Gen failed to s=
tart // Grid return (investigation ongoing)","danick.tchakouani@sagemcom.co=
m","143","04-03-2025 19:19:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004491350","O=
LAMA","","04-03-2025 18:45:16","04-03-2025 18:33:05","04-03-2025 19:40:52",=
"Active//No power issue on site Ubaie =3D54.9V site on Grid The TX FME Henr=
i (699949693) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie =3D54.9V site on Grid The TX FME Henri (69994969=
3) from Huawei is informed","yves.djomo@sagemcom.com","732","04-03-2025 18:=
45:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0004491234","Mfou EPC=
","","04-03-2025 18:28:11","04-03-2025 18:12:20","04-03-2025 20:36:09","Cas=
caded Incident from TTO4548056","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went because Gen =
ran until fuel shortage//Refueling Done","system","273026","04-03-2025 18:2=
8:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0004491231","M=
fou OCM","IHS_YND_674","04-03-2025 18:27:27","04-03-2025 18:12:20","04-03-2=
025 20:36:09","Grid outage, Site went because Gen ran until fuel shortage//=
Refueling Done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage, Site went because Gen ran until fuel shortage//Refue=
ling Done","yves.djomo@sagemcom.com","908","04-03-2025 18:27:27","Sagemcom =
CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004490913","Nko=
abang2","","04-03-2025 17:43:52","04-03-2025 17:24:42","04-03-2025 17:39:40=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // He reduced the load and gen manually started","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, site went down due to gen overload (22KVA, 330A), SS Blaise IHS is i=
nformed // He reduced the load and gen manually started","el-dalile@sagemco=
m.com","24136","04-03-2025 17:43:52","Sagemcom CMR"
"Closed Complete","Site Down","T1107-1","IHS_YND_217","NOCINC0004490790","A=
bom","","04-03-2025 17:23:27","04-03-2025 17:08:01","04-03-2025 21:15:12","=
Active//No power issue, site is on Grid with Ubaie=3D53,2V The TX Synphorie=
n / 675295205/ Huawei is informed","Siligap Boris","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue, site is on Grid with Ubaie=3D53,2V The TX Synphorien / 67529520=
5/ Huawei is informed","danick.tchakouani@sagemcom.com","927","04-03-2025 1=
7:23:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004490706","SOA VILL=
AGE","","04-03-2025 17:15:24","04-03-2025 16:53:34","04-03-2025 17:30:59","=
Cascaded Incident from TTO4547320","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation site went down bec=
ause Gen failed to start due to Grid bad voltage NO RCP ON SITE // he bypas=
s the Grid and Gen manully started","system","270562","04-03-2025 17:15:24"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004490674","SAA=
 2","","04-03-2025 17:10:18","04-03-2025 16:25:58","04-03-2025 16:35:41","S=
ite went down due to work: SS IHS Felix BATEU working on site// End of work=
","Parker Tchoup","Installation Activity","Passive","Planned Activity","Ins=
tallation Activity","Site went down due to work: SS IHS Felix BATEU working=
 on site// End of work","el-dalile@sagemcom.com","4923","04-03-2025 17:10:1=
8","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004490612","Lad=
a I Yde","","04-03-2025 17:00:58","04-03-2025 16:58:36","04-03-2025 17:10:0=
2","Site went down due to works our FME Herv=E9(657108482) is working on si=
te(Replaced the CB in the DC BOX)// end Off work ","Mba Lazare Herve","Equi=
pment Replacement","Passive","Planned Activity","Planned Activity - Passive=
","Site went down due to works our FME Herv=E9(657108482) is working on sit=
e(Replaced the CB in the DC BOX)// end Off work ","el-dalile@sagemcom.com",=
"143","04-03-2025 17:00:58","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004490607","SOA=
 TOWN","IHS_YND_323","04-03-2025 16:59:45","04-03-2025 16:53:34","04-03-202=
5 17:30:59","Grid fluctuation site went down because Gen failed to start du=
e to Grid bad voltage NO RCP ON SITE // he bypass the Grid and Gen manully =
started","Siligap Boris","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation site went down because Gen failed =
to start due to Grid bad voltage NO RCP ON SITE // he bypass the Grid and G=
en manully started","yves.djomo@sagemcom.com","372","04-03-2025 16:59:45","=
Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004490518","Ngu=
ila","","04-03-2025 16:43:53","04-03-2025 16:39:30","04-03-2025 16:43:31","=
Hybrid Gen: Site went down because started and stopped due to 'High temp"" =
alarm// He added water and started Gen manualy (investigation ongoing)","Pa=
rker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Te=
mp - Coolant Level Issue","Hybrid Gen: Site went down because started and s=
topped due to 'High temp"" alarm// He added water and started Gen manualy (=
investigation ongoing)","el-dalile@sagemcom.com","264","04-03-2025 16:43:53=
","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004490420","EMA=
NA BILICK CITY","","04-03-2025 16:28:47","04-03-2025 16:16:59","04-03-2025 =
16:34:06","Grid outage, Site went down because Gen failed to start due to A=
TS faulty// Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","ATS-AMF Issue","Grid outage, Site went down because Gen fai=
led to start due to ATS faulty// Grid Restored","el-dalile@sagemcom.com","7=
09","04-03-2025 16:28:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004490247","N=
koabang Ebolmedjock","","04-03-2025 16:06:37","04-03-2025 12:25:10","04-03-=
2025 19:26:59","Active// No power issue on site U=3D54.5 V site on Gen.Site=
 impacted by Nkolmesseng-Abom and not managing by IHS","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active// No power issue on site U=3D54.5 V site on Gen.Site impa=
cted by Nkolmesseng-Abom and not managing by IHS","el-dalile@sagemcom.com",=
"13288","04-03-2025 16:06:37","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004490006","NYO=
M FACE MAETUR","","04-03-2025 15:46:17","04-03-2025 15:27:13","04-03-2025 1=
8:34:00","Grid outage, site went down because Gen failed to started due to =
Gen card faullty //Gen manualy started","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down =
because Gen failed to started due to Gen card faullty //Gen manualy started=
","yves.djomo@sagemcom.com","1145","04-03-2025 15:46:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_745","NOCINC0004489969","Okolo Ki=
lombo","","04-03-2025 15:43:57","04-03-2025 13:35:52","04-03-2025 14:55:08"=
,"Grid outage, site went down because gen fails to start due to Gen cable f=
aulty // Gen manualy started","Fabrice Pouakam","Equipment Repair","Passive=
","Infrastructure","Armoured Cable","Grid outage, site went down because ge=
n fails to start due to Gen cable faulty // Gen manualy started","yves.djom=
o@sagemcom.com","7686","04-03-2025 15:43:57","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0004489922","Sap=
eur Mimboman","","04-03-2025 15:41:42","04-03-2025 13:21:19","04-03-2025 15=
:14:25"," Grid outage Site went down because Gen overload (20KVA, 300A) SS =
IHS Alphonse DEFFO confirmed// Grid return. ","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload"," Grid outage Site went dow=
n because Gen overload (20KVA, 300A) SS IHS Alphonse DEFFO confirmed// Grid=
 return. ","el-dalile@sagemcom.com","8425","04-03-2025 15:41:42","Sagemcom =
CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004489399","Mes=
sassi 2","","04-03-2025 15:12:13","04-03-2025 15:07:05","04-03-2025 15:18:0=
5","Site went down due to insuffience of rectifier (04)// He added 01 recti=
fier (05)","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to insuffience of rectifier (04)// He add=
ed 01 rectifier (05)","yves.djomo@sagemcom.com","14816","04-03-2025 15:12:1=
3","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004489284","An-=
Marche-Melen","","04-03-2025 15:08:14","04-03-2025 15:01:54","04-03-2025 18=
:42:57","Gri outage, no space to deploy a mobile gen // Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Over Voltage","Gri outage=
, no space to deploy a mobile gen // Grid return","el-dalile@sagemcom.com",=
"381","04-03-2025 15:08:14","Sagemcom CMR"
"Closed Complete","Site Down","T1502","IHS_YND_685","NOCINC0004489168","Ema=
na lycee 2","","04-03-2025 14:59:02","04-03-2025 14:44:43","04-03-2025 15:0=
7:13","Grid outage, site went down because gen start and stopped with high =
temp alarm // He added water and Gen started manually","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Le=
vel Issue","Grid outage, site went down because gen start and stopped with =
high temp alarm // He added water and Gen started manually","el-dalile@sage=
mcom.com","860","04-03-2025 14:59:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0004489140","Mamch Bu=
ilding","","04-03-2025 14:51:51","04-03-2025 14:42:28","04-03-2025 14:55:37=
","Cascaded Incident from TTO4545739","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid Outage//Grid Restored","sys=
tem","278407","04-03-2025 14:51:51","Sagemcom CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004489136","Cha=
rles-Atangana","IHS_YND_051","04-03-2025 14:50:50","04-03-2025 14:42:28","0=
4-03-2025 14:58:38","Grid Outage//Grid Restored","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid Outage//Grid Restored","w=
ilfried.kameni@sagemcom.com","503","04-03-2025 14:50:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004488882","Dong",""=
,"04-03-2025 14:27:41","04-03-2025 14:16:55","04-03-2025 14:16:56","Cascade=
d Incident from TTO4545449","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue with U=3D52.9V //site =
on Gen THe fme tx Gregoire 652070658 from Huawei is informed","system","279=
829","04-03-2025 14:27:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004488874","D=
onga","IHS_YND_444","04-03-2025 14:27:00","04-03-2025 14:16:55","04-03-2025=
 19:00:56","Active//No power issue with U=3D52.9V //site on Gen THe fme tx =
Gregoire 652070658 from Huawei is informed","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue with U=3D52.9V //site on Gen THe fme tx Gregoire 652070=
658 from Huawei is informed","mariam.tchonang@sagemcom.com","607","04-03-20=
25 14:27:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004488873","Nkolfon =
Cimencam","","04-03-2025 14:26:50","04-03-2025 14:04:06","04-03-2025 14:46:=
02","Cascaded Incident from TTO4545347","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Outage site went down du=
e to Main Gen Faulty//Grid Restored","system","266797","04-03-2025 14:26:50=
","Sagemcom CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004488784","Nom=
ayos","IHS_YND_791, IHS_YND_762","04-03-2025 14:15:02","04-03-2025 14:04:06=
","04-03-2025 14:46:02","Grid Outage site went down due to Main Gen Faulty/=
/Grid Restored","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Generator Faulty","Grid Outage site went down due to Main Gen Faulty//Gr=
id Restored","ludovic-anselme.mouliom-mapoure@sagemcom","657","04-03-2025 1=
4:15:02","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004488758","Com=
plex Beac II","","04-03-2025 14:11:47","04-03-2025 13:54:32","04-03-2025 14=
:27:22","Site went down due to Work Our RM Kamga and SS Judigael are workin=
g On Site (Replaced the Gen Card)// End Off Work","Albran Byorel","Equipmen=
t Replacement","Passive","Planned Activity","Planned Activity - Passive","S=
ite went down due to Work Our RM Kamga and SS Judigael are working On Site =
(Replaced the Gen Card)// End Off Work","ludovic-anselme.mouliom-mapoure@sa=
gemcom","1036","04-03-2025 14:11:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004488706","M=
vog-Ada_OCM","","04-03-2025 14:01:43","04-03-2025 13:20:23","04-03-2025 14:=
21:59","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"Site went down due to work: Our Technician Justin/657100524/SAGEMCOM work=
ing on site (Swapp MPR)// End of work","mariam.tchonang@sagemcom.com","2905=
43","04-03-2025 14:01:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004488697","M=
ontesquieux","IHS_YND_042","04-03-2025 14:00:36","04-03-2025 13:20:23","04-=
03-2025 14:21:59","Site went down due to work: Our Technician Justin/657100=
524/SAGEMCOM working on site (Swapp MPR)// End of work","Paul BIBOUM","Inst=
allation Activity","Passive","Planned Activity","Installation Activity","Si=
te went down due to work: Our Technician Justin/657100524/SAGEMCOM working =
on site (Swapp MPR)// End of work","mariam.tchonang@sagemcom.com","2414","0=
4-03-2025 14:00:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004488544","SAA 2","=
","04-03-2025 13:40:01","04-03-2025 09:53:58","04-03-2025 10:00:06","Cascad=
ed Incident from TTO4543029","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went donw due to works SS IHS FELIX =
is working on Site// and off work","system","288512","04-03-2025 13:40:01",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0004488438","Bar=
riere IHS","","04-03-2025 13:30:04","04-03-2025 13:19:58","04-03-2025 14:41=
:42","Grid outage, Site went down because Gen failed to start due to PWC dy=
sfunctionning IHS Supervisor Felix Zambe confirmed// He reset it and reduce=
d the load, site is on Gen","Hyemafo Gildas","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Grid outage, Site went down becau=
se Gen failed to start due to PWC dysfunctionning IHS Supervisor Felix Zamb=
e confirmed// He reset it and reduced the load, site is on Gen","ludovic-an=
selme.mouliom-mapoure@sagemcom","658","04-03-2025 13:30:04","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004488326","AWA=
E OCM","","04-03-2025 13:15:15","04-03-2025 12:53:46","04-03-2025 12:58:25"=
,"Grid outage, Site went down before Gen start due to poor backup // Gen au=
atomatically started ","Mba Lazare Herve","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen auatomatically started ","ludovic-an=
selme.mouliom-mapoure@sagemcom","1291","04-03-2025 13:15:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004488163","N=
kolangaa","","04-03-2025 12:58:29","04-03-2025 12:36:59","04-03-2025 13:40:=
22"," Site went down due to PSC3 Controller dysfunctionning// He reset it",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel"," Site went down due to PSC3 Controller dysfunctionning// He reset i=
t","mariam.tchonang@sagemcom.com","1291","04-03-2025 12:58:29","Sagemcom CM=
R"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004488151","Nom=
ayos montee Meche","","04-03-2025 12:54:30","04-03-2025 14:04:06","04-03-20=
25 14:46:02","","Fanda Brice","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid Outage site went down due to Main Gen Faulty//Grid =
Restored","ludovic-anselme.mouliom-mapoure@sagemcom","266797","04-03-2025 1=
2:54:30","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004488146","EMA=
NA BILICK CITY","","04-03-2025 12:53:22","04-03-2025 12:49:11","04-03-2025 =
14:09:50","Grid outage, Site went down because Gen failed to start due to A=
TS faulty// He bypassed ATS and started  Gen manualy","Fabrice Pouakam","Eq=
uipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Sit=
e went down because Gen failed to start due to ATS faulty// He bypassed ATS=
 and started  Gen manualy","ludovic-anselme.mouliom-mapoure@sagemcom","283"=
,"04-03-2025 12:53:22","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004488089","Bar=
riere","","04-03-2025 12:42:24","04-03-2025 12:36:13","04-03-2025 15:01:42"=
,"Grid outage, Site went because Gen started and stopped due Gen Overload (=
20KVA, 450A) SS IHS Felix Zambe confirmed// Grid power return","Hyemafo Gil=
das","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
, Site went because Gen started and stopped due Gen Overload (20KVA, 450A) =
SS IHS Felix Zambe confirmed// Grid power return","ludovic-anselme.mouliom-=
mapoure@sagemcom","401","04-03-2025 12:42:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004488080","Mehanda =
1","","04-03-2025 12:41:11","04-03-2025 12:27:21","04-03-2025 13:25:39","Ca=
scaded Incident from TTO4544446","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site  went down because Eneo Meter,Gr=
id Contactors,Gen contactors,Relay 48,Relay 220V  and Air Conditionar  faul=
ty due to lightning // Gen manually started ( all equipement faulty to be r=
eplaced)","system","293656","04-03-2025 12:41:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004488083","ODZA MIN=
KAN EDIBI ASSI","","04-03-2025 12:41:11","04-03-2025 12:27:21","04-03-2025 =
13:25:39","Cascaded Incident from TTO4544446","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site  went down because =
Eneo Meter,Grid Contactors,Gen contactors,Relay 48,Relay 220V  and Air Cond=
itionar  faulty due to lightning // Gen manually started ( all equipement f=
aulty to be replaced)","system","293655","04-03-2025 12:41:11","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004488081","Odza Min=
kan IHS","","04-03-2025 12:41:11","04-03-2025 12:27:21","04-03-2025 13:25:3=
9","Cascaded Incident from TTO4544446","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site  went down because Eneo Me=
ter,Grid Contactors,Gen contactors,Relay 48,Relay 220V  and Air Conditionar=
  faulty due to lightning // Gen manually started ( all equipement faulty t=
o be replaced)","system","293655","04-03-2025 12:41:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004488079","MEHANDAN=
","","04-03-2025 12:41:10","04-03-2025 12:27:21","04-03-2025 13:25:39","Cas=
caded Incident from TTO4544446","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site  went down because Eneo Meter,Gri=
d Contactors,Gen contactors,Relay 48,Relay 220V  and Air Conditionar  fault=
y due to lightning // Gen manually started ( all equipement faulty to be re=
placed)","system","293655","04-03-2025 12:41:10","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004488002","Nko=
lnda","IHS_YND_528, IHS_YND_746, IHS_YND_715, IHS_YND_749","04-03-2025 12:3=
0:32","04-03-2025 12:27:21","04-03-2025 13:25:39","Site  went down because =
Eneo Meter,Grid Contactors,Gen contactors,Relay 48,Relay 220V  and Air Cond=
itionar  faulty due to lightning // Gen manually started ( all equipement f=
aulty to be replaced)","Albran Byorel","Force Majeure","Natural Disaster","=
Thunderstrike","Equipment Damaged","Site  went down because Eneo Meter,Grid=
 Contactors,Gen contactors,Relay 48,Relay 220V  and Air Conditionar  faulty=
 due to lightning // Gen manually started ( all equipement faulty to be rep=
laced)","ludovic-anselme.mouliom-mapoure@sagemcom","192","04-03-2025 12:30:=
32","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004487990","Nko=
g-Edzen","","04-03-2025 12:28:18","04-03-2025 12:20:43","04-03-2025 20:20:4=
4","No power issue site on Gen. The Team aubin (694427963 ) from I-ENG  is =
Working on site","Parker Tchoup","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue site on Gen. Th=
e Team aubin (694427963 ) from I-ENG  is Working on site","ludovic-anselme.=
mouliom-mapoure@sagemcom","457","04-03-2025 12:28:18","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004487929","NKO=
LOSSAN OKOK","","04-03-2025 12:20:13","04-03-2025 12:07:04","04-03-2025 12:=
43:48","Grid outage, Site went down because gen stopped due to belt cut // =
He changed belt and Gen manually started","Parker Tchoup","Equipment Repair=
","Passive","ACDG Gen","ACDG - Fan Belt","Grid outage, Site went down becau=
se gen stopped due to belt cut // He changed belt and Gen manually started"=
,"ludovic-anselme.mouliom-mapoure@sagemcom","790","04-03-2025 12:20:13","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004487928","B=
ATA Mokolo OCM","","04-03-2025 12:19:18","04-03-2025 09:14:37","04-03-2025 =
21:39:37","Grid outage.no space to deploy mobile gen // grid power","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.no space to deploy mobile gen // grid power","ludovic-anselme.mouliom-mapo=
ure@sagemcom","11082","04-03-2025 12:19:18","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004487646","Sap=
eur","","04-03-2025 11:46:01","04-03-2025 11:41:49","04-03-2025 12:09:53","=
Grid outage, Site went down before Gen start due to poor backup/ // Gen aut=
omatically started","Mboua Thierry","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Gen automatically started","ludovic-anselme.m=
ouliom-mapoure@sagemcom","253","04-03-2025 11:46:01","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004487640","Awa=
e Escalier","","04-03-2025 11:44:51","04-03-2025 11:42:39","04-03-2025 13:1=
4:40","Grid outage, Site went down before Gen start due to poor backup // G=
en manually started ","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup // Gen manually started ","ludovic-anselme.moul=
iom-mapoure@sagemcom","133","04-03-2025 11:44:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_545","NOCINC0004487570","Nkolbiss=
on usine des eaux","","04-03-2025 11:36:37","04-03-2025 11:10:56","04-03-20=
25 11:12:23","Cascaded Incident from TTO4543679","TIENTCHEU NZETCHIEU GAEL"=
,"Cascade Outage","Active","Cascade Active","Cascade Active","No power issu=
e on site Mohamadou(691144435) from Huawei was working on site ","system","=
262455","04-03-2025 11:36:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004487573","AFEME NO=
RD","","04-03-2025 11:36:37","04-03-2025 11:10:56","04-03-2025 11:12:23","C=
ascaded Incident from TTO4543679","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Moham=
adou(691144435) from Huawei was working on site ","system","262455","04-03-=
2025 11:36:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_285","NOCINC0004487571","Nkolbiss=
on","","04-03-2025 11:36:37","04-03-2025 11:10:56","04-03-2025 11:12:23","C=
ascaded Incident from TTO4543679","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Moham=
adou(691144435) from Huawei was working on site ","system","262453","04-03-=
2025 11:36:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_729","NOCINC0004487572","Nkolbiss=
on IITA LP","","04-03-2025 11:36:37","04-03-2025 11:10:56","04-03-2025 11:1=
2:23","Cascaded Incident from TTO4543679","","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Mohamadou(691144435) =
from Huawei was working on site ","system","262454","04-03-2025 11:36:37","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0004487569","Oyomaban=
g Ecole","","04-03-2025 11:36:36","04-03-2025 11:10:56","04-03-2025 11:12:2=
3","Cascaded Incident from TTO4543679","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Active","Cascade Active","Cascade Active","No power issue on site =
Mohamadou(691144435) from Huawei was working on site ","system","262454","0=
4-03-2025 11:36:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004487568","Nkolkoum=
ou OCM","","04-03-2025 11:36:36","04-03-2025 11:10:56","04-03-2025 11:12:23=
","Cascaded Incident from TTO4543679","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue on site M=
ohamadou(691144435) from Huawei was working on site ","system","262453","04=
-03-2025 11:36:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0004487567","Mbankolo=
 petit paris","","04-03-2025 11:36:36","04-03-2025 11:10:56","04-03-2025 11=
:12:23","Cascaded Incident from TTO4543679","Mboua Thierry","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue on site Mohama=
dou(691144435) from Huawei was working on site ","system","262452","04-03-2=
025 11:36:36","Sagemcom CMR"
"Closed Complete","Site Down","T0292","IHS_YND_231","NOCINC0004487328","Nko=
lso","IHS_YND_808, IHS_YND_712, IHS_YND_686, IHS_YND_545, IHS_YND_285, IHS_=
YND_729, IHS_YND_519","04-03-2025 11:13:05","04-03-2025 11:10:56","04-03-20=
25 11:50:23","No power issue on site Mohamadou(691144435) from Huawei was w=
orking on site ","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite Mohamadou(691144435) from Huawei was working on site ","ludovic-anselme=
.mouliom-mapoure@sagemcom","130","04-03-2025 11:13:05","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004487280","Nko=
londom","","04-03-2025 11:06:57","04-03-2025 10:51:44","04-03-2025 12:08:14=
","Grid fluctuation, site went down because Gen failed to start due to grid=
 bad voltage No crcp // He bypassed the grid and started Gen manually","Fab=
rice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because Gen failed to start d=
ue to grid bad voltage No crcp // He bypassed the grid and started Gen manu=
ally","ludovic-anselme.mouliom-mapoure@sagemcom","915","04-03-2025 11:06:57=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004487143","N=
YOM 2 IHS","","04-03-2025 10:42:47","04-03-2025 10:33:36","04-03-2025 11:18=
:00","Site went down because the CB(100A) of Battery dysjoncted due to load=
 // he bypass the Cb","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Circuit Breaker Issue","Site went down because t=
he CB(100A) of Battery dysjoncted due to load // he bypass the Cb","mariam.=
tchonang@sagemcom.com","552","04-03-2025 10:42:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004487112","M=
essassi 2","","04-03-2025 10:37:23","04-03-2025 10:28:09","04-03-2025 12:25=
:14","Grid outage, Site went down because 4/5 rectifiers disfunctionning// =
He reset it","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Grid outage, Site went down because 4/5 rectifiers disfunc=
tionning// He reset it","mariam.tchonang@sagemcom.com","556","04-03-2025 10=
:37:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004486755","S=
aa","IHS_YND_404","04-03-2025 09:59:12","04-03-2025 09:53:58","04-03-2025 1=
0:00:06","Site went donw due to works SS IHS FELIX is working on Site// and=
 off work","Parker Tchoup","Installation Activity","Passive","Planned Activ=
ity","Installation Activity","Site went donw due to works SS IHS FELIX is w=
orking on Site// and off work","mariam.tchonang@sagemcom.com","315","04-03-=
2025 09:59:12","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004486502","NYO=
M FACE MAETUR","","04-03-2025 09:26:50","04-03-2025 09:25:41","04-03-2025 1=
1:19:52","Grid outage, site went down because Gen failed to started due to =
Gen card faullty //Gen manualy started","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down =
because Gen failed to started due to Gen card faullty //Gen manualy started=
","ludovic-anselme.mouliom-mapoure@sagemcom","70","04-03-2025 09:26:50","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0004486377","Sap=
eur Mimboman","","04-03-2025 09:05:49","04-03-2025 09:03:40","04-03-2025 12=
:45:52"," Grid outage Site went down because Gen overload (20KVA, 300A) SS =
IHS Alphonse DEFFO confirmed// He Reduice the Load and Gen Manually Started=
","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overlo=
ad"," Grid outage Site went down because Gen overload (20KVA, 300A) SS IHS =
Alphonse DEFFO confirmed// He Reduice the Load and Gen Manually Started","l=
udovic-anselme.mouliom-mapoure@sagemcom","131","04-03-2025 09:05:49","Sagem=
com CMR"
"Closed Complete","Site Down","T1937","IHS_YND_232","NOCINC0004486305","Crf=
-Nkolbisson","","04-03-2025 08:52:06","04-03-2025 08:41:56","04-03-2025 08:=
44:57","wrongly ticket","TIENTCHEU NZETCHIEU GAEL","Incorrectly Logged Tick=
ets","Error","Error","Error","wrongly ticket","ludovic-anselme.mouliom-mapo=
ure@sagemcom","674","04-03-2025 08:52:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004485896","Dong",""=
,"04-03-2025 07:37:10","04-03-2025 06:57:06","04-03-2025 08:03:37","Cascade=
d Incident from TTO4541919","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue with U=3D48.9V //site =
on Battery THe fme tx Gregoire 652070658 from Huawei is informed","system",=
"270295","04-03-2025 07:37:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004485879","M=
efou-Assi","","04-03-2025 07:33:47","04-03-2025 07:30:19","04-03-2025 08:28=
:53","ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The =
Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed","wilfried.kameni@sagemcom.co=
m","209","04-03-2025 07:33:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004485779","D=
onga","IHS_YND_444","04-03-2025 07:05:48","04-03-2025 06:57:06","04-03-2025=
 08:30:23","Active//No power issue with U=3D48.9V //site on Battery THe fme=
 tx Gregoire 652070658 from Huawei is informed","Parker Tchoup","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue with U=3D48.9V //site on Battery THe fme tx Gregoir=
e 652070658 from Huawei is informed","wilfried.kameni@sagemcom.com","523","=
04-03-2025 07:05:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0004485461","M=
beng","","04-03-2025 05:38:33","04-03-2025 05:29:23","04-03-2025 07:18:10",=
"Grid outage.gen failed to start due to automation malfunctionning//Gen man=
ually started","Fanda Brice","Equipment Repair","Passive","Control Panel","=
ATS-AMF Issue","Grid outage.gen failed to start due to automation malfuncti=
onning//Gen manually started","wilfried.kameni@sagemcom.com","551","04-03-2=
025 05:38:33","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004485452","SAA=
 Entrance","","04-03-2025 05:35:31","04-03-2025 05:26:01","04-03-2025 06:23=
:41","Grid outage.gen failed to start due to automation malfunctionning//Ge=
n manually started","Parker Tchoup","Equipment Repair","Passive","Control P=
anel","ATS-AMF Issue","Grid outage.gen failed to start due to automation ma=
lfunctionning//Gen manually started","wilfried.kameni@sagemcom.com","571","=
04-03-2025 05:35:31","Sagemcom CMR"
"Closed Complete","Site Down","T0532","IHS_YND_239","NOCINC0004485445","Men=
dong2","","04-03-2025 05:34:24","04-03-2025 04:56:09","04-03-2025 08:36:25"=
,"Site went down due to insufficience of rectifiers on site(02/03) SS IHS F=
rancois is informed and confirmed// We add one rectifier and site on grid",=
"Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to insufficience of rectifiers on site(02/03) SS IHS =
Francois is informed and confirmed// We add one rectifier and site on grid"=
,"wilfried.kameni@sagemcom.com","2296","04-03-2025 05:34:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0004485344","A=
n-Marche-Melen","","04-03-2025 04:58:22","04-03-2025 04:47:07","04-03-2025 =
09:29:15","Grid outage.no space to deploy mobile gen.//Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.no space to deploy mobile gen.//Grid return","el-dalile@sagemcom.com","676=
","04-03-2025 04:58:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004485219","L=
abogenie","IHS_YND_568","04-03-2025 03:48:49","04-03-2025 03:20:20","04-03-=
2025 03:22:35","No  power issue U =3D54,5V site on Grid. The Tx FME  Elound=
ou (693212405 )from Huawei is informed. Notice that it is the repetitive is=
sue","","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No  power issue U =3D54,5V site on Grid. The Tx FME  El=
oundou (693212405 )from Huawei is informed. Notice that it is the repetitiv=
e issue","wilfried.kameni@sagemcom.com","1710","04-03-2025 03:48:49","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0004485205","A=
nguissa New","","04-03-2025 03:40:29","04-03-2025 03:20:20","04-03-2025 08:=
31:57","No power issue, site is on grid with Ubaie=3D53V, Eloundou bertrant=
(652586578) from Huawei is informed","MINKA NICOLAS","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue, site is on grid with=
 Ubaie=3D53V, Eloundou bertrant(652586578) from Huawei is informed","wilfri=
ed.kameni@sagemcom.com","283402","04-03-2025 03:40:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004485008","S=
hell-Nsimeyong","","04-03-2025 01:39:43","04-03-2025 01:35:18","04-03-2025 =
01:40:13","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","el-dalile@sagemcom.com","266","04-03-2025 01:39:43","Sagemcom CMR=
"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004484985","Nko=
lmvack","","04-03-2025 01:20:12","04-03-2025 01:10:02","04-03-2025 02:49:29=
","Site went down because Gen started and stopped due to pellet radiator pi=
erced // he glued the Radiator and Manually Started The Gen","Parker Tchoup=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Radiat=
or Leakage","Site went down because Gen started and stopped due to pellet r=
adiator pierced // he glued the Radiator and Manually Started The Gen","wil=
fried.kameni@sagemcom.com","611","04-03-2025 01:20:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004484583","V=
allee-Bastos OCM","","03-03-2025 23:05:23","03-03-2025 21:52:05","04-03-202=
5 11:58:33","There is no power issue on site There was water infiltration i=
n the BTS OCM after heavy rain  Huawei guys was alert for that","","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","There is no power issue on site
There was water infiltration in the BTS OCM after heavy rain=20
Huawei guys was alert for that","wilfried.kameni@sagemcom.com","4399","03-0=
3-2025 23:05:23","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004484368","Ebo=
go","","03-03-2025 22:15:25","03-03-2025 21:56:09","03-03-2025 22:05:54","n=
o power issue on site Ubaie: 59.2V;  site on BATTERY. The TX FME Symphorien=
 (675295205) From huawei is informed","Siligap Boris","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power =
issue on site Ubaie: 59.2V;  site on BATTERY. The TX FME Symphorien (675295=
205) From huawei is informed","el-dalile@sagemcom.com","1157","03-03-2025 2=
2:15:25","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004484273","Aha=
la","","03-03-2025 22:05:58","03-03-2025 21:10:41","03-03-2025 23:12:07","S=
ite went down because 4/8 rectifiers disfunctionning// He reset it and site=
 on Grid","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down because 4/8 rectifiers disfunctionning// He res=
et it and site on Grid","el-dalile@sagemcom.com","3318","03-03-2025 22:05:5=
8","Sagemcom CMR"
"Closed Complete","Site Down","T1652","IHS_YND_273","NOCINC0004483407","Nko=
lbi-Boss","","03-03-2025 20:21:50","03-03-2025 20:12:40","03-03-2025 20:25:=
36","No power issue on site U=3D52.9V  Site on Grid. The FME TX Mohamadou (=
691144435)from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site U=3D52.9V  Site on Grid. The FME TX Mohamadou (691144=
435)from Huawei is informed","el-dalile@sagemcom.com","551","03-03-2025 20:=
21:50","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004483394","ELO=
UMDEM CARRIERE","","03-03-2025 20:17:13","03-03-2025 20:08:52","03-03-2025 =
20:17:47","No power issue , Site on Grid and Ubaie=3D55V The Tx Fme  Fulber=
t //654266068 from  Huawei is inform","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue , Site on Grid and Ubaie=3D55V The Tx Fme  Fulbert //654266068 from  Hu=
awei is inform","el-dalile@sagemcom.com","503","03-03-2025 20:17:13","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0004483290","H=
-Franco New","","03-03-2025 20:06:48","03-03-2025 19:56:55","03-03-2025 21:=
50:37","Grid outage, Site went down because GEN OVERLOAD (20KVA, 320A) RM I=
HS BATE is informed// Grid return","Delor Telezing","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Grid outage, Site went dow=
n because GEN OVERLOAD (20KVA, 320A) RM IHS BATE is informed// Grid return"=
,"el-dalile@sagemcom.com","594","03-03-2025 20:06:48","Sagemcom CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0004483271","Omn=
isport-Rail","","03-03-2025 20:01:51","03-03-2025 19:57:37","03-03-2025 21:=
30:10","Site went down due to 02/06 rectifiers burned, Bernard Atangana is =
informed // He reduise the load, Power Issues resolved at 09:30PM But the s=
ite still down after power reset done The FME TX ARMAND Ng","Delor Telezing=
","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went do=
wn due to 02/06 rectifiers burned, Bernard Atangana is informed // He redui=
se the load, Power Issues resolved at 09:30PM But the site still down after=
 power reset done The FME TX ARMAND Nguetsa (691144412)  From huawei is inf=
ormed","el-dalile@sagemcom.com","255","03-03-2025 20:01:51","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004483231","Lad=
a I Yde","","03-03-2025 19:54:19","03-03-2025 19:49:00","03-03-2025 19:55:5=
5","No power issue site on grid with U=3D54v Lionel Adjep(655184876) from H=
uawei is informed//site up","Mba Lazare Herve","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on grid with U=3D54v Lionel Adjep(655184876) from Huawei is informed//s=
ite up","el-dalile@sagemcom.com","320","03-03-2025 19:54:19","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004482820","UPA=
C LP","","03-03-2025 18:40:59","03-03-2025 18:34:50","03-03-2025 21:51:39",=
"Grid outage.no space to deploy mobile gen //Grid return Power issue resolv=
ed at 09:51 PM but site remains down Armand Nguetsa(691144412) from Huawei =
is informed","","Grid Supply","Passive","Grid","National Grid - Grid Outage=
 Issue","Grid outage.no space to deploy mobile gen //Grid return Power issu=
e resolved at 09:51 PM but site remains down Armand Nguetsa(691144412) from=
 Huawei is informed","wilfried.kameni@sagemcom.com","370","03-03-2025 18:40=
:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004482640","N=
YOM 2 IHS","","03-03-2025 18:10:37","03-03-2025 18:03:32","03-03-2025 18:13=
:36","Grid outage, Site went down before Gen start due to poor backup // Ge=
n started automaticaly","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen started automaticaly","el-dalile@sag=
emcom.com","426","03-03-2025 18:10:37","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004482633","NYO=
M FACE MAETUR","","03-03-2025 18:09:36","03-03-2025 18:07:30","03-03-2025 1=
8:14:31","Grid outage, site went down because Gen failed to started due to =
Gen card faullty //Grid return","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
Gen failed to started due to Gen card faullty //Grid return","el-dalile@sag=
emcom.com","127","03-03-2025 18:09:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004482623","A=
wae Escalier","","03-03-2025 18:07:15","03-03-2025 18:03:09","03-03-2025 18=
:32:51","Grid outage, Site went down before Gen start due to poor backup //=
 Gen started automaticaly","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup // Gen started automaticaly","el-dalile@sa=
gemcom.com","247","03-03-2025 18:07:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004482551","M=
amch Building","","03-03-2025 17:54:50","03-03-2025 17:49:42","03-03-2025 1=
8:35:13","Grid fluctuation,Site went down because Gen failed to start due t=
o grid bad voltage  //he bypassed the Grid and started the Gen manually","M=
boua Thierry","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation,Site went down because Gen failed to start du=
e to grid bad voltage  //he bypassed the Grid and started the Gen manually"=
,"wilfried.kameni@sagemcom.com","309","03-03-2025 17:54:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004482545","Dong",""=
,"03-03-2025 17:53:51","03-03-2025 17:44:39","03-03-2025 18:45:11","Cascade=
d Incident from TTO4538094","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue  with U=3D48.9V //site=
 on Battery THe fme tx Gregoire 652070658 from Huawei is informed","system"=
,"1252897","03-03-2025 17:53:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004482540","Donga","=
IHS_YND_444","03-03-2025 17:52:51","03-03-2025 17:44:39","03-03-2025 17:50:=
11","Active//No power issue  with U=3D48.9V //site on Battery THe fme tx Gr=
egoire 652070658 from Huawei is informed","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue  with U=3D48.9V //site on Battery THe fme tx Gregoire 652=
070658 from Huawei is informed","system","492","03-03-2025 17:52:51","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004482513","M=
essassi 2","","03-03-2025 17:47:46","03-03-2025 17:44:39","03-03-2025 18:39=
:25","Site went down because PWC overload (12 kilo, 300A) , SS IHS Bernard =
ATANGANA confirmed// He reset the rectifier","Fabrice Pouakam","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Site went down =
because PWC overload (12 kilo, 300A) , SS IHS Bernard ATANGANA confirmed// =
He reset the rectifier","el-dalile@sagemcom.com","188","03-03-2025 17:47:46=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004482485","B=
arriere","","03-03-2025 17:42:49","03-03-2025 16:46:37","03-03-2025 18:30:0=
6","Grid outage, Site went because Gen started and stopped due Gen Overload=
 (20KVA, 450A) SS IHS Felix Zambe confirmed// Grid power return","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge, Site went because Gen started and stopped due Gen Overload (20KVA, 450A=
) SS IHS Felix Zambe confirmed// Grid power return","wilfried.kameni@sagemc=
om.com","3373","03-03-2025 17:42:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004482455","Akak-Nko=
zoa-MTN-IHS","IHS_YND_324","03-03-2025 17:35:33","03-03-2025 17:29:09","03-=
03-2025 18:23:05","Grid fluctuation Site went down because Gen failed to st=
art due to Grid bad voltage // Grid stabilized power reset has been done bu=
t the site remain down .  The Tx FME ARMAND Nguetsa (691144412) from ","Fab=
rice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation Site went down because Gen failed to start du=
e to Grid bad voltage // Grid stabilized power reset has been done but the =
site remain down .The Tx FME Symphorien(675295205) from Huawei is informed"=
,"system","384","03-03-2025 17:35:33","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004482321","SOA=
 UNIVERSITY STADIUM","","03-03-2025 17:18:01","03-03-2025 17:06:51","03-03-=
2025 17:18:51","Grid outage, site went down because gen failed to start due=
 to Pwc ZTE dysfunction// He reset it and started Gen manualy","Siligap Bor=
is","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid outage, site went down because gen failed to start due to Pwc ZTE dys=
function// He reset it and started Gen manualy","danick.tchakouani@sagemcom=
.com","671","03-03-2025 17:18:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004482295","B=
iteng","","03-03-2025 17:13:10","03-03-2025 16:07:58","03-03-2025 16:13:48"=
,"Active// No power issue, site is on Grid with Ubaie=3D56,2V, Lionel Adjep=
(655184876) from Huawei is informed. Notice that we have disjunction at BTS=
 OM","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active// No power issue, site is on Gri=
d with Ubaie=3D56,2V, Lionel Adjep(655184876) from Huawei is informed. Noti=
ce that we have disjunction at BTS OM","wilfried.kameni@sagemcom.com","3914=
","03-03-2025 17:13:10","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004482206","Eto=
 koss Yde","","03-03-2025 16:57:54","03-03-2025 16:49:35","03-03-2025 17:09=
:44","Grid outage, Site went down before Gen start due to poor backup // Gr=
id return","Fanda Brice","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, Site went down before Gen start due =
to poor backup // Grid return","danick.tchakouani@sagemcom.com","501","03-0=
3-2025 16:57:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004482101","M=
efou-Assi","","03-03-2025 16:38:17","03-03-2025 16:34:07","03-03-2025 16:35=
:41","ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The =
Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed","wilfried.kameni@sagemcom.co=
m","251","03-03-2025 16:38:17","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004481926","Aha=
la","","03-03-2025 16:18:39","03-03-2025 16:08:39","03-03-2025 16:28:00","S=
ite went down because 4/8 rectifiers disfunctionning// He reset it and site=
 on Grid ","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down because 4/8 rectifiers disfunctionning// He re=
set it and site on Grid ","danick.tchakouani@sagemcom.com","601","03-03-202=
5 16:18:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004481808","N=
koabang Ebolmedjock","","03-03-2025 16:09:02","03-03-2025 15:28:34","03-03-=
2025 15:29:28","Active//No power issue, Site on Gen. Notice that it is impa=
cted by Nkolmesseng-Abom(CTR-711) Not Manager By IHS","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue, Site on Gen. Notice that it is impacted b=
y Nkolmesseng-Abom(CTR-711) Not Manager By IHS","danick.tchakouani@sagemcom=
.com","2429","03-03-2025 16:09:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0004481741","BATA Mok=
olo OCM","","03-03-2025 15:59:30","03-03-2025 15:22:19","03-03-2025 16:30:3=
5","","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Grid outage, No space to deploy MDG// Grid return","system","2256","03-03=
-2025 15:59:30","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004481608","Crf=
-Nsam","","03-03-2025 15:42:05","03-03-2025 15:39:55","03-03-2025 15:42:12"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline conf=
irmed// He reset PWC","MINKA NICOLAS","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down because PWC(24kilo) dysfu=
nctionning, IHS SS Pascaline confirmed// He reset PWC","wilfried.kameni@sag=
emcom.com","131","03-03-2025 15:42:05","Sagemcom CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0004481578","Mam=
ch Building","","03-03-2025 15:35:38","03-03-2025 15:31:25","03-03-2025 16:=
20:26","Grid outage, site went down because gen start and stopped with over=
 current alarm(Unpruven alarm) // Reset of gen card done and gen started","=
Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, site went down because gen start and stopped with over cur=
rent alarm(Unpruven alarm) // Reset of gen card done and gen started","wilf=
ried.kameni@sagemcom.com","254","03-03-2025 15:35:38","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004481510","Mel=
en Ba'aba","","03-03-2025 15:20:09","03-03-2025 15:13:57","03-03-2025 15:15=
:15","Active//No power issue, site is on Gen with Ubaie=3D53V,1 TX FME Juli=
en(693095849) from Huawei is informed","Siligap Boris","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue, site is on Gen with Ubaie=3D53V,1 TX FME Julien(693095849) =
from Huawei is informed","wilfried.kameni@sagemcom.com","373","03-03-2025 1=
5:20:09","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004481480","Bar=
riere","","03-03-2025 15:13:28","03-03-2025 15:08:19","03-03-2025 15:28:00"=
,"Grid outage, Site went because Gen started and stopped due Gen Overload (=
20KVA, 450A) SS IHS Felix Zambe confirmed// Grid power return","Hyemafo Gil=
das","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
, Site went because Gen started and stopped due Gen Overload (20KVA, 450A) =
SS IHS Felix Zambe confirmed// Grid power return","wilfried.kameni@sagemcom=
.com","310","03-03-2025 15:13:28","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004481476","Mes=
sa Carriere","","03-03-2025 15:12:17","03-03-2025 15:09:07","03-03-2025 15:=
59:19","Grid outage, site went down because Gen failed to started due to Ge=
n card faullty //Gen manually started","Mboua Thierry","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down bec=
ause Gen failed to started due to Gen card faullty //Gen manually started",=
"wilfried.kameni@sagemcom.com","191","03-03-2025 15:12:17","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004481247","MBA=
LNGONG LYCEE","","03-03-2025 15:01:17","03-03-2025 14:54:53","03-03-2025 18=
:23:43","Grid Outage Site went down due to Gen overload(9kva, 130A) SS IHS =
Felix Zambe is informed and confirmed awaiting Grid return","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site =
went down due to Gen overload(9kva, 130A) SS IHS Felix Zambe is informed an=
d confirmed awaiting Grid return","wilfried.kameni@sagemcom.com","385","03-=
03-2025 15:01:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0004481011","H=
-Prince","","03-03-2025 14:48:50","03-03-2025 14:45:40","03-03-2025 15:28:0=
8","Site went down due to works Our FME Thierry from Sagemcom is working on=
 Site(Replaced the Grid contactors)//end off works ","Mboua Thierry","Equip=
ment Replacement","Passive","Planned Activity","Planned Activity - Passive"=
,"Site went down due to works Our FME Thierry from Sagemcom is working on S=
ite(Replaced the Grid contactors)//end off works ","wilfried.kameni@sagemco=
m.com","191","03-03-2025 14:48:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004481005","S=
atcom","","03-03-2025 14:47:59","03-03-2025 14:43:36","03-03-2025 14:44:09"=
,"Active // No power issue site on Grid with U=3D50,61 V Tx Fme Armand Nges=
tsa (691144412) of huawei is informed ","Delor Telezing","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue site on Grid with U=3D50,61 V Tx Fme Armand Ngestsa (691=
144412) of huawei is informed ","wilfried.kameni@sagemcom.com","265","03-03=
-2025 14:47:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004480740","MONTEE N=
KONDENGUI","","03-03-2025 14:34:03","03-03-2025 13:48:27","03-03-2025 14:02=
:21","Cascaded Incident from TTO4535502","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage// Grid return","s=
ystem","288797","03-03-2025 14:34:03","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004480445","Aha=
la","","03-03-2025 14:23:15","03-03-2025 14:16:05","03-03-2025 14:43:46","S=
ite went down because 4/8 rectifiers disfunctionning// He reset it and site=
 on Grid ","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down because 4/8 rectifiers disfunctionning// He re=
set it and site on Grid ","wilfried.kameni@sagemcom.com","431","03-03-2025 =
14:23:15","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004480246","Mel=
en Ba'aba","","03-03-2025 13:59:28","03-03-2025 13:54:24","03-03-2025 14:00=
:28"," Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME J=
ulien(693095849) from Huawei is informed and up 02:00 PM","Siligap Boris","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm"," Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX =
FME Julien(693095849) from Huawei is informed and up 02:00 PM","yves.djomo@=
sagemcom.com","305","03-03-2025 13:59:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004480216","M=
obil-Kondengui","IHS_YND_682","03-03-2025 13:54:31","03-03-2025 13:48:27","=
03-03-2025 14:02:21","Grid outage// Grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage// Grid return","yv=
es.djomo@sagemcom.com","365","03-03-2025 13:54:31","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004480126","BAT=
A Mokolo OCM","","03-03-2025 13:31:02","03-03-2025 13:23:57","03-03-2025 14=
:36:47","","","Grid Supply","Passive","Grid","National Grid - Grid Outage I=
ssue","Grid outage, No space to deploy MDG// Grid return","yves.djomo@sagem=
com.com","426","03-03-2025 13:31:02","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004480023","Sap=
eur","","03-03-2025 13:04:53","03-03-2025 12:57:47","03-03-2025 13:45:56","=
Grid outage, site went down because gen start and stopped with high temp al=
arm // He added water and manually","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outa=
ge, site went down because gen start and stopped with high temp alarm // He=
 added water and manually","yves.djomo@sagemcom.com","427","03-03-2025 13:0=
4:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004479828","B=
iteng","","03-03-2025 12:35:45","03-03-2025 12:22:35","03-03-2025 12:25:20"=
,"Active// No power issue, site is on Grid with Ubaie=3D56,2V, Lionel Adjep=
(655184876) from Huawei is informed. Notice that we have disjunction at BTS=
 OM","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active// No power issue, site is on Gri=
d with Ubaie=3D56,2V, Lionel Adjep(655184876) from Huawei is informed. Noti=
ce that we have disjunction at BTS OM","yves.djomo@sagemcom.com","792","03-=
03-2025 12:35:45","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004479712","Mom=
","","03-03-2025 12:27:58","03-03-2025 12:21:49","03-03-2025 13:01:49","Gri=
d outage, site went down because gen failed to start due to Gen contactor n=
o excited // He excited Gen contactor and put Site on Gen","Fanda Brice","E=
quipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, si=
te went down because gen failed to start due to Gen contactor no excited //=
 He excited Gencontactor and Site is on Gen","danick.tchakouani@sagemcom.co=
m","403","03-03-2025 12:27:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004479696","TSINGA V=
ILLAGE 2","","03-03-2025 12:26:00","03-03-2025 12:16:21","03-03-2025 12:26:=
20","Cascaded Incident from TTO4534718","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work: C=
HE CLODAH 674307687 From GAIO working on site (restored CMS in site)// End =
of work","system","265519","03-03-2025 12:26:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004479695","Nkolfoul=
ou 2","","03-03-2025 12:26:00","03-03-2025 12:16:21","03-03-2025 12:26:20",=
"Cascaded Incident from TTO4534718","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work: CHE CL=
ODAH 674307687 From GAIO working on site (restored CMS in site)// End of wo=
rk","system","265518","03-03-2025 12:26:00","Sagemcom CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004479631","Nko=
lfoulou","IHS_YND_278, IHS_YND_719","03-03-2025 12:20:33","03-03-2025 12:16=
:21","03-03-2025 12:26:21","Site went down due to work: CHE CLODAH 67430768=
7 From GAIO working on site (restored CMS in site)// End of work","Siligap =
Boris","Installation Activity","Passive","Planned Activity","Installation A=
ctivity","Site went down due to work: CHE CLODAH 674307687 From GAIO workin=
g on site (restored CMS in site)// End of work","danick.tchakouani@sagemcom=
.com","286","03-03-2025 12:20:33","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004479121","Sap=
eur","","03-03-2025 12:01:21","03-03-2025 11:59:09","03-03-2025 12:05:09","=
Grid outage, Site went down before Gen start due to poor backup/ // Gen aut=
omatically started","Mboua Thierry","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Gen automatically started","danick.tchakouani=
@sagemcom.com","135","03-03-2025 12:01:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004478847","Nkolfon =
Cimencam","","03-03-2025 11:40:30","03-03-2025 11:34:22","03-03-2025 17:17:=
35","Cascaded Incident from TTO4533956","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","(Main Gen faulty) Mobile Gen =
installed overload (20KVA, 300A) RM Armel BITEK confirmed, waitting Grid re=
turn","system","296896","03-03-2025 11:40:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004478846","Nomayos =
montee Meche","","03-03-2025 11:40:30","03-03-2025 11:34:22","03-03-2025 17=
:17:35","Cascaded Incident from TTO4533956","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","(Main Gen faulty) Mobile Gen=
 installed overload (20KVA, 300A) RM Armel BITEK confirmed, waitting Grid r=
eturn","system","296896","03-03-2025 11:40:30","Sagemcom CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004478828","Nom=
ayos","IHS_YND_791, IHS_YND_762","03-03-2025 11:37:31","03-03-2025 11:34:22=
","03-03-2025 17:17:35","Grid Outage (Main Gen faulty) Mobile Gen installed=
 overload (20KVA, 300A) RM Armel BITEK confirmed,// Grid return","Fanda Bri=
ce","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage =
(Main Gen faulty) Mobile Gen installed overload (20KVA, 300A) RM Armel BITE=
K confirmed,// Grid return","danick.tchakouani@sagemcom.com","190","03-03-2=
025 11:37:31","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0004478719","N=
dogbessol","","03-03-2025 11:25:11","03-03-2025 11:10:04","03-03-2025 13:10=
:05","No power issue on site U=3D54,6V site on Gen , The Tx FME Etienne/651=
320188/ from Huawei is informed","Kemeni Franklin","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site U=3D54,6V site on Gen , The Tx FME Etienne/651320188/ from Huawe=
i is informed","yves.djomo@sagemcom.com","909","03-03-2025 11:25:11","Sagem=
com CMR"
"Closed Complete","Warning","CTR_062","IHS_YND_310","NOCINC0004478197","Nom=
ayos","","03-03-2025 10:58:50","","","Grid outage, site went alarm because =
main gen faulty // MDG 20Kva has deployed","Fanda Brice","Warning","Warning=
","POWER","Warning - Site on Battery","Grid outage, site went alarm because=
 main gen faulty // MDG 20Kva has deployed","danick.tchakouani@sagemcom.com=
","33","03-03-2025 10:58:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004478154","M=
essassi 2","","03-03-2025 10:54:28","03-03-2025 10:51:17","03-03-2025 11:33=
:30","Site went down due to rectifiers disfunction (05/05) SS IHS Bernard A=
tangana confirmed// He reset rectifiers (Rectifiers to be replaced)","Fabri=
ce Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Distributio=
n","Site went down due to rectifiers disfunction (05/05) SS IHS Bernard Ata=
ngana confirmed// He reset rectifiers (Rectifiers to be replaced)","yves.dj=
omo@sagemcom.com","193","03-03-2025 10:54:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_068","IHS_YND_109","NOCINC0004477983","M=
obil-Essos","","03-03-2025 10:48:40","03-03-2025 10:45:29","03-03-2025 11:1=
5:30","Grid outage, Site went down because Gen ran until fuel shortage// Re=
fueling Done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, Site went down because Gen ran until fuel shortage// Refu=
eling Done","yves.djomo@sagemcom.com","193","03-03-2025 10:48:40","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004477758","MONTEE N=
KONDENGUI","","03-03-2025 10:31:40","03-03-2025 10:25:07","03-03-2025 11:34=
:25","Cascaded Incident from TTO4532779","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage// Grid return","s=
ystem","272339","03-03-2025 10:31:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004477753","M=
obil-Kondengui","IHS_YND_682","03-03-2025 10:31:12","03-03-2025 10:25:07","=
03-03-2025 11:34:25","Grid outage// Grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage// Grid return","yv=
es.djomo@sagemcom.com","366","03-03-2025 10:31:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004477409","B=
ATA Mokolo OCM","","03-03-2025 09:52:13","03-03-2025 09:49:03","03-03-2025 =
12:26:51","Grid outage, No space to deploy MDG// Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No s=
pace to deploy MDG// Grid return","yves.djomo@sagemcom.com","191","03-03-20=
25 09:52:13","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004477344","MBA=
LNGONG LYCEE","","03-03-2025 09:41:00","03-03-2025 09:36:47","03-03-2025 14=
:05:49","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed//Load Reduice and Si=
te is on Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid outage, Site went down because Gen stopped due to overload=
(9kva, 130A) SS IHS Felix Zambe is informed and confirmed//Load Reduice and=
 Site is on Gen","danick.tchakouani@sagemcom.com","255","03-03-2025 09:41:0=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004477293","Dong",""=
,"03-03-2025 09:32:10","03-03-2025 09:29:42","03-03-2025 09:35:19","Cascade=
d Incident from TTO4532268","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue with U=3D48,8V (start =
threshold U=3D47,9V), site on Battery Gregoire from Huawei is informed","sy=
stem","261353","03-03-2025 09:32:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004477286","D=
onga","IHS_YND_444","03-03-2025 09:30:49","03-03-2025 09:29:42","03-03-2025=
 09:35:19","Active//No power issue with U=3D48,8V (start threshold U=3D47,9=
V), site on Battery Gregoire from Huawei is informed","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue with U=3D48,8V (start threshold U=3D47,9V), s=
ite on Battery Gregoire from Huawei is informed","yves.djomo@sagemcom.com",=
"69","03-03-2025 09:30:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004477144","B=
arriere IHS","","03-03-2025 09:14:57","03-03-2025 09:08:47","03-03-2025 12:=
41:51","Grid outage, Site went down because Gen failed to start due to PWC =
dysfunctionning IHS Supervisor Felix Zambe confirmed// He reset it and redu=
ced the load, site is on Gen","Hyemafo Gildas","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage, Site went down bec=
ause Gen failed to start due to PWC dysfunctionning IHS Supervisor Felix Za=
mbe confirmed// He reset it and reduced the load, site is on Gen","danick.t=
chakouani@sagemcom.com","372","03-03-2025 09:14:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004477137","B=
iteng","","03-03-2025 09:12:36","03-03-2025 09:05:17","03-03-2025 11:10:43"=
,"Active// No power issue, site is on Grid with Ubaie=3D53,2V, Lionel Adjep=
(655184876) from Huawei is informed. Notice that we have disjunction at BTS=
 OM","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active// No power issue, site is on Gri=
d with Ubaie=3D53,2V, Lionel Adjep(655184876) from Huawei is informed. Noti=
ce that we have disjunction at BTS OM","danick.tchakouani@sagemcom.com","44=
1","03-03-2025 09:12:36","Sagemcom CMR"
"Closed Complete","Warning","T0236","IHS_YND_373","NOCINC0004477114","Malou=
n","","03-03-2025 09:08:22","","","Site alarming on battery because Our FME=
 Kemeni Francklin From SAGEMCOM was on site for PM // End of work	","Kemeni=
 Franklin","Warning","Warning","POWER","Warning - Site on Battery","Site al=
arming on battery because Our FME Kemeni Francklin From SAGEMCOM was on sit=
e for PM // End of work	","yves.djomo@sagemcom.com","187","03-03-2025 09:08=
:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004477026","MBIMBIM"=
,"","03-03-2025 08:52:11","03-03-2025 08:41:50","03-03-2025 08:42:28","Casc=
aded Incident from TTO4531949","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
54V Hybrid Gen site with threshold =3D 47.5V). TX FME WILLY 650254398 of Hu=
awei is informed.","system","1213576","03-03-2025 08:52:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004477025","Ngouetou=
","","03-03-2025 08:52:10","03-03-2025 08:41:50","03-03-2025 08:42:28","Cas=
caded Incident from TTO4531949","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 54V Hybrid Gen site with threshold =3D 47.5V). TX FME WILLY 650254398 of H=
uawei is informed.","system","1213573","03-03-2025 08:52:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0004477024","Yoko OCM=
","","03-03-2025 08:52:10","03-03-2025 08:41:50","03-03-2025 08:42:28","Cas=
caded Incident from TTO4531949","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 54V Hybrid Gen site with threshold =3D 47.5V). TX FME WILLY 650254398 of H=
uawei is informed.","system","1213575","03-03-2025 08:52:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004477022","Ngoum","=
","03-03-2025 08:52:10","03-03-2025 08:41:50","03-03-2025 08:42:28","Cascad=
ed Incident from TTO4531949","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Gen with U =3D 54=
V Hybrid Gen site with threshold =3D 47.5V). TX FME WILLY 650254398 of Huaw=
ei is informed.","system","1213574","03-03-2025 08:52:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004477023","Matsari"=
,"","03-03-2025 08:52:10","03-03-2025 08:41:50","03-03-2025 08:42:28","Casc=
aded Incident from TTO4531949","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
54V Hybrid Gen site with threshold =3D 47.5V). TX FME WILLY 650254398 of Hu=
awei is informed.","system","1213574","03-03-2025 08:52:10","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004476764","Aha=
la Echangeur","","03-03-2025 08:01:37","02-03-2025 18:36:30","02-03-2025 18=
:37:10","BACK TRAKING (Site down at 02:50 PM and Up at 06:35 PM): Site went=
 down because 2/2 rectifier disfunctionning SS IHS Pascaline MANDA is infor=
med// He reset rectifiers","MINKA NICOLAS","Equipment Repair","Passive","Re=
ctifier","Rectifier Distribution","BACK TRAKING (Site down at 02:50 PM and =
Up at 06:35 PM): Site went down because 2/2 rectifier disfunctionning SS IH=
S Pascaline MANDA is informed// He reset rectifiers","yves.djomo@sagemcom.c=
om","48308","03-03-2025 08:01:37","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004476731","Awa=
e Escalier","","03-03-2025 07:53:28","03-03-2025 07:45:26","03-03-2025 07:5=
2:51","Grid outage, Site went down before Gen start due to poor backup// Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup// Grid return","yves.djomo@sagemcom.com","484","03-03-2025=
 07:53:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004476634","N=
kolfon Cimencam","","03-03-2025 07:18:24","03-03-2025 07:14:21","03-03-2025=
 08:14:04","Active//No power issue, Site on Grid. Notice that it is impacte=
d by Afanoya II The Tx FME Fulbert from Huawei is informed","Hyemafo Gildas=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","Active//No power issue, Site on Grid. Notice that it is impac=
ted by Afanoya II The Tx FME Fulbert from Huawei is informed","yves.djomo@s=
agemcom.com","244","03-03-2025 07:18:24","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004476559","Crf=
-Nsam","","03-03-2025 06:52:58","03-03-2025 06:50:53","03-03-2025 07:38:12"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline conf=
irmed// He reset PWC","MINKA NICOLAS","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down because PWC(24kilo) dysfu=
nctionning, IHS SS Pascaline confirmed// He reset PWC","yves.djomo@sagemcom=
.com","126","03-03-2025 06:52:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004476516","SOA VILL=
AGE","","03-03-2025 06:35:10","03-03-2025 06:33:29","03-03-2025 07:13:06","=
Cascaded Incident from TTO4531406","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause Gen failed to start due to grid bad voltage // He bypassed the grid a=
nd started Gen manually","system","1221156","03-03-2025 06:35:10","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004476513","SOA=
 TOWN","IHS_YND_323","03-03-2025 06:34:33","03-03-2025 06:30:29","03-03-202=
5 07:13:19","Grid fluctuation, site went down because Gen failed to start d=
ue to grid bad voltage // He bypassed the grid and started Gen manually","S=
iligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because Gen failed to start d=
ue to grid bad voltage // He bypassed the grid and started Gen manually","y=
ves.djomo@sagemcom.com","299","03-03-2025 06:34:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004476418","M=
efou-Assi","","03-03-2025 06:00:14","03-03-2025 05:58:01","03-03-2025 06:10=
:30","ACTIVE//No power issue on site GRID , Ubaie=3D54.3V site On Grid The =
Tx FME Fulbert(654266068) from Huawei is informed. Repetitive issue","Fanda=
 Brice","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D54.3V sit=
e On Grid The Tx FME Fulbert(654266068) from Huawei is informed. Repetitive=
 issue","cedric.tiani@sagemcom.com","134","03-03-2025 06:00:14","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004476410","M=
ambine","","03-03-2025 05:53:37","03-03-2025 05:44:15","03-03-2025 07:23:37=
","Grid Hybrid Gen: Site went down because Gen ran until fuel shortage// Re=
fueling Done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid Hybrid Gen: Site went down because Gen ran until fuel shortage// Re=
fueling Done","cedric.tiani@sagemcom.com","563","03-03-2025 05:53:37","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004476206","O=
mnisport-Rail","","03-03-2025 04:47:44","03-03-2025 04:44:15","03-03-2025 0=
5:14:32","	Site went down due to 02/06 rectifiers burned, Bernard Atangana =
is informed // He reduise the load, Site on grid","Delor Telezing","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","	Site went down due to=
 02/06 rectifiers burned, Bernard Atangana is informed // He reduise the lo=
ad, Site on grid","cedric.tiani@sagemcom.com","210","03-03-2025 04:47:44","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004476042","N=
kolfon Cimencam","","03-03-2025 03:38:54","03-03-2025 02:14:27","03-03-2025=
 02:20:16","Active//No power issue, Site on Grid Ubai=3D 52,8V. Notice that=
 it is impacted by Afanoya II The Tx FME Fulbert from Huawei is informed","=
Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 52=
,8V. Notice that it is impacted by Afanoya II The Tx FME Fulbert from Huawe=
i is informed","cedric.tiani@sagemcom.com","5068","03-03-2025 03:38:54","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004476018","Crf=
-Nsam","","03-03-2025 03:23:45","03-03-2025 03:14:38","03-03-2025 03:38:28"=
,"Site went down Because The Slot off Rectifier is overload // Grid return =
SS Ihs Pascaline is informed and is confirmed","MINKA NICOLAS","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down Because The=
 Slot off Rectifier is overload // Grid return SS Ihs Pascaline is informed=
 and is confirmed","ferot.nongni-djiogap@sagemcom.com","548","03-03-2025 03=
:23:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004475886","S=
hell-Nsimeyong","","03-03-2025 02:09:32","03-03-2025 02:07:22","03-03-2025 =
02:15:05","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","cedric.tiani@sagemcom.com","131","03-03-2025 02:09:32","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004475869","Dong",""=
,"03-03-2025 02:00:20","03-03-2025 01:57:22","03-03-2025 02:10:51","Cascade=
d Incident from TTO4530618","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue with U=3D54V //site on=
 gen Gregoire from Huawei is informed","system","266663","03-03-2025 02:00:=
20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004475865","D=
onga","IHS_YND_444","03-03-2025 01:59:34","03-03-2025 01:57:22","03-03-2025=
 02:10:51","Active//No power issue with U=3D54V //site on gen Gregoire from=
 Huawei is informed","Parker Tchoup","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue wit=
h U=3D54V //site on gen Gregoire from Huawei is informed","cedric.tiani@sag=
emcom.com","133","03-03-2025 01:59:34","Sagemcom CMR"
"Closed Complete","Site Down","T0123","IHS_YND_013","NOCINC0004475824","Lab=
oratoire T.Bella","","03-03-2025 01:42:19","03-03-2025 01:33:11","03-03-202=
5 03:05:17","Grid outage, site went down because gen ran untill fuel shorta=
ge // Refueling done","Paul BIBOUM","Fuel Outage","Passive","Diesel","Diese=
l Outage","Grid outage, site went down because gen ran untill fuel shortage=
 // Refueling done","ferot.nongni-djiogap@sagemcom.com","549","03-03-2025 0=
1:42:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0004475775","B=
iteng","","03-03-2025 01:09:55","02-03-2025 17:19:28","02-03-2025 17:25:58"=
,"Active// No power issue, site is on Grid with Ubaie=3D56V, Lionel Adjep(6=
55184876) from Huawei is informed. Notice that we have disjunction at BTS O=
M","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","Active// No power issue, site is on Grid =
with Ubaie=3D56V, Lionel Adjep(655184876) from Huawei is informed. Notice t=
hat we have disjunction at BTS OM","cedric.tiani@sagemcom.com","28228","03-=
03-2025 01:09:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004475698","E=
koumdoum OCM","","03-03-2025 00:46:25","03-03-2025 00:42:00","03-03-2025 01=
:20:50","	Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline =
is informed and confirmed// He reduced the load an manually started GEN","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","	S=
ite went down due to Gen overload(20kva,280 A) IHS SS Pascaline is informed=
 and confirmed// He reduced the load an manually started GEN","cedric.tiani=
@sagemcom.com","266","03-03-2025 00:46:25","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004475508","MBA=
LNGONG LYCEE","","02-03-2025 23:58:34","02-03-2025 23:44:27","03-03-2025 04=
:47:40","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen stopped due to overload(9kva, 130A) SS IHS Felix Zambe i=
s informed and confirmed","ferot.nongni-djiogap@sagemcom.com","848","02-03-=
2025 23:58:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004475483","E=
leveur","IHS_YND_277","02-03-2025 23:50:58","02-03-2025 17:15:52","02-03-20=
25 22:22:50","Grid outage;Site went down because Gen started and stopped du=
e to Gen overload(20 Kva ,290 A)//Grid return SS IHS Blaise Raoul is inform=
ed and confirmed.","Siligap Boris","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage;Site went down because Gen started and stopp=
ed due to Gen overload(20 Kva ,290 A)//Grid return SS IHS Blaise Raoul is i=
nformed and confirmed.","ferot.nongni-djiogap@sagemcom.com","23707","02-03-=
2025 23:50:58","Sagemcom CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0004475420","Ngo=
ulmekong-Nord","","02-03-2025 23:35:48","02-03-2025 17:15:52","02-03-2025 2=
2:22:50","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid outage;Site went down because Gen started and stopped=
 due to Gen overload(20 Kva ,290 A)//Grid return SS IHS Blaise Raoul is inf=
ormed and confirmed.","ferot.nongni-djiogap@sagemcom.com","290725","02-03-2=
025 23:35:48","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004475316","NYO=
M 2 IHS","","02-03-2025 23:03:30","02-03-2025 22:54:16","02-03-2025 23:03:1=
4","No power issue site on grid with U=3D54.8v Site up at 11:03 PM Symphori=
en(675295205) from Huawei is informed","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue site on grid with U=3D54.8v Site up at 11:03 PM Symphorien(6752952=
05) from Huawei is informed","cedric.tiani@sagemcom.com","555","02-03-2025 =
23:03:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004475216","M=
essa-Carriere OCM","","02-03-2025 22:51:34","02-03-2025 22:50:20","03-03-20=
25 10:08:13","Grid outage, No space to to deploy MDG awaiting Grid return (=
ETA=3D08:00)","","Grid Supply","Passive","Grid","National Grid - Grid Outag=
e Issue","Grid outage, No space to deploy MDG // Grid return","cedric.tiani=
@sagemcom.com","76","02-03-2025 22:51:34","Sagemcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0004475207","Bar=
riere IHS","","02-03-2025 22:48:14","02-03-2025 22:44:07","03-03-2025 00:44=
:42","Site went down due to PWC dysfunctionning IHS Supervisor Felix Zambe =
is informed//he reset it and site is on Gen","Hyemafo Gildas","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Site went down d=
ue to PWC dysfunctionning IHS Supervisor Felix Zambe is informed//he reset =
it and site is on Gen","ferot.nongni-djiogap@sagemcom.com","381","02-03-202=
5 22:48:14","Sagemcom CMR"
"Cancelled","Warning","T1248","IHS_YND_797","NOCINC0004475205","Fouda rue d=
es g=E9n=E9raux","","02-03-2025 22:47:04","","","incorrectly logged tickets=
","Delor Telezing","","","","","","ferot.nongni-djiogap@sagemcom.com","82",=
"02-03-2025 22:47:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0004474821","E=
BOM","","02-03-2025 21:20:55","02-03-2025 21:17:37","02-03-2025 21:19:42","=
Grid fluctuation, Site went down because Gen failed to start due to Grid ba=
d voltage and No RCP on site // Grid stabilized","Hyemafo Gildas","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation, Site went down because Gen failed to start due to Grid bad voltage =
and No RCP on site // Grid stabilized","danick.tchakouani@sagemcom.com","21=
9","02-03-2025 21:20:55","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004474031","Nko=
lnda","","02-03-2025 19:15:49","02-03-2025 19:10:38","02-03-2025 20:38:25",=
"Site went down due to disjunction of Cb(125A) in DC BOX // He reamed Cb(12=
5A), site on grid","Albran Byorel","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Circuit Breaker Issue","Site went down due to disjunc=
tion of Cb(125A) in DC BOX // He reamed Cb(125A), site on grid","wilfried.k=
ameni@sagemcom.com","312","02-03-2025 19:15:49","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004473926","Crf=
-Mbankolo-IHS","","02-03-2025 18:55:29","02-03-2025 18:48:22","02-03-2025 1=
9:52:15","Site went dosn due to MPR DYSFONNCTion on site // He reset the MP=
R site on Gen ","Mboua Thierry","Equipment Repair","Passive","Rectifier","R=
ectifier Cabinet","Site went dosn due to MPR DYSFONNCTion on site // He res=
et the MPR site on Gen ","wilfried.kameni@sagemcom.com","428","02-03-2025 1=
8:55:29","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004473920","NKO=
MEKUI OCM","","02-03-2025 18:53:06","02-03-2025 18:49:40","02-03-2025 18:55=
:07","No power issue on site U=3D54.5 V site on Gen.Site impacted by Mbanko=
lo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site U=3D54.5 V site on Gen.Site impacted by Mbankolo Camt=
el and not managing by IHS","wilfried.kameni@sagemcom.com","207","02-03-202=
5 18:53:06","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004473728","Eko=
mbitie","","02-03-2025 18:24:05","02-03-2025 18:14:49","02-03-2025 20:35:10=
","Grid fluctuations, site went down because Gen failed to start due to gri=
d bad voltage // He bypassed the grid and started Gen manually","Fabrice Po=
uakam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuations, site went down because Gen failed to start due to =
grid bad voltage // He bypassed the grid and started Gen manually","wilfrie=
d.kameni@sagemcom.com","576","02-03-2025 18:24:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0004473681","B=
ONAS YDE","","02-03-2025 18:16:19","02-03-2025 17:49:49","02-03-2025 18:43:=
33","	Grid fluctuation, Site went down because Gen started and stopped due =
to Grid bad voltage// Grid stabilized","Paul BIBOUM","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","	Grid fluctuation, Site=
 went down because Gen started and stopped due to Grid bad voltage// Grid s=
tabilized","wilfried.kameni@sagemcom.com","1591","02-03-2025 18:16:19","Sag=
emcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004473589","Eko=
umdoum OCM","","02-03-2025 17:53:38","02-03-2025 17:07:11","02-03-2025 18:1=
3:26","	Site went down due to Gen overload(20kva,280 A) IHS SS Pascaline is=
 informed and confirmed// Grid return","Albran Byorel","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","	Site went down due to Gen overload(=
20kva,280 A) IHS SS Pascaline is informed and confirmed// Grid return","wil=
fried.kameni@sagemcom.com","2807","02-03-2025 17:53:38","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004473574","Ngu=
ila","","02-03-2025 17:50:34","02-03-2025 17:44:24","02-03-2025 18:31:17","=
Grid outage, site went down because gen start and stopped with high temp al=
arm // He added water and manually","Parker Tchoup","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outa=
ge, site went down because gen start and stopped with high temp alarm // He=
 added water and manually","wilfried.kameni@sagemcom.com","371","02-03-2025=
 17:50:34","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004473472","Lad=
a I Yde","","02-03-2025 17:26:18","02-03-2025 17:22:59","02-03-2025 17:30:5=
6","No power issue site on grid with U=3D54v Lionel Adjep(655184876) from H=
uawei is informed//site up at 06:35 PM","Mba Lazare Herve","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue site on grid with U=3D54v Lionel Adjep(655184876) from Huawei is=
 informed//site up at 06:35 PM","wilfried.kameni@sagemcom.com","200","02-03=
-2025 17:26:18","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004473261","Eto=
 koss Yde","","02-03-2025 16:44:46","02-03-2025 16:26:33","02-03-2025 17:16=
:19","grid outage, site went down because gen failed to start due to RCP fa=
ulty // Gen manually started","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Relay Faulty","grid outage, site went down because gen fai=
led to start due to RCP faulty // Gen manually started","wilfried.kameni@sa=
gemcom.com","1095","02-03-2025 16:44:46","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004473042","NKO=
LMEKONG YDE","","02-03-2025 16:15:28","02-03-2025 16:13:09","02-03-2025 16:=
15:09","Site went down because PWC dysfunctionning IHS SS BERNARD ATANGANA =
is informed and confirmed// grid return","Fabrice Pouakam","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","Site went down beca=
use PWC dysfunctionning IHS SS BERNARD ATANGANA is informed and confirmed//=
 grid return","wilfried.kameni@sagemcom.com","139","02-03-2025 16:15:28","S=
agemcom CMR"
"Closed Complete","Site Down","T0050","IHS_YND_039","NOCINC0004473024","Sia=
ntou Radio TV","","02-03-2025 16:13:10","02-03-2025 16:05:02","02-03-2025 1=
6:14:39","Grid outage no space to deploy a mobil gen // Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e no space to deploy a mobil gen // Grid return","wilfried.kameni@sagemcom.=
com","489","02-03-2025 16:13:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004473014","AFEME NO=
RD","","02-03-2025 16:11:50","02-03-2025 15:56:48","02-03-2025 16:18:42","C=
ascaded Incident from TTO4527223","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site went dow=
n because Gen stopped with alarm high temp //He added water and Gen manuall=
y started","system","274006","02-03-2025 16:11:50","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004473006","Nko=
lafeme","IHS_YND_519","02-03-2025 16:11:01","02-03-2025 15:56:48","02-03-20=
25 16:18:42","Grid outage site went down because Gen stopped with alarm hig=
h temp //He added water and Gen manually started","TIENTCHEU NZETCHIEU GAEL=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid outage site went down because Gen stopped with alarm h=
igh temp //He added water and Gen manually started","wilfried.kameni@sagemc=
om.com","854","02-03-2025 16:11:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0004472989","C=
hapelle-Nsimeyong","","02-03-2025 16:08:17","02-03-2025 15:21:36","02-03-20=
25 15:25:22","AcTIVE: no power issue, site is on grid with Ubaie=3D53V, Hos=
iah(699699694) from Huawei is informed","MINKA NICOLAS","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","AcTIVE:=
 no power issue, site is on grid with Ubaie=3D53V, Hosiah(699699694) from H=
uawei is informed","wilfried.kameni@sagemcom.com","2802","02-03-2025 16:08:=
17","Sagemcom CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0004472835","Omn=
isport-Rail","","02-03-2025 15:51:34","02-03-2025 15:49:21","02-03-2025 18:=
12:44","Site went down due to 02/06 rectifiers burned, Bernard Atangana is =
informed // He withdrawn 02 rectifiers, site on grid with 04 rectifiers","D=
elor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to 02/06 rectifiers burned, Bernard Atangana is informe=
d // He withdrawn 02 rectifiers, site on grid with 04 rectifiers","wilfried=
.kameni@sagemcom.com","134","02-03-2025 15:51:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004472818","C=
omplexe-BEAC","","02-03-2025 15:50:16","02-03-2025 15:47:54","02-03-2025 15=
:53:34","Grid outage , Site went down before Gen start due to poor backup//=
 GEN started automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage , Site went down b=
efore Gen start due to poor backup// GEN started automatically","wilfried.k=
ameni@sagemcom.com","143","02-03-2025 15:50:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004472811","S=
calom-IHS","","02-03-2025 15:49:04","02-03-2025 15:44:58","02-03-2025 19:51=
:12","Site went down because CB(63A) tripped in DC Box who feeds equipments=
 OCM// He installed a CB(125A) and made a bridge with CB(63A)","","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue"=
,"Site went down because CB(63A) tripped in DC Box who feeds equipments OCM=
// He installed a CB(125A) and made a bridge with CB(63A)","wilfried.kameni=
@sagemcom.com","248","02-03-2025 15:49:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004472754","M=
ontee-Anne-Rouge","","02-03-2025 15:40:02","02-03-2025 15:33:51","02-03-202=
5 16:42:56","Grid outage, No space to deploy MDG // Grid Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, No space to deploy MDG // Grid Grid return","wilfried.kameni@sagemcom.c=
om","372","02-03-2025 15:40:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004472728","O=
dza","","02-03-2025 15:35:37","02-03-2025 14:08:29","02-03-2025 15:48:08","=
Grid outage, site went down because gen failed to start due to hybrid syste=
m malfunction // Gen manually started","Albran Byorel","Equipment Repair","=
Passive","Hybrid","Hybrid Module","Grid outage, site went down because gen =
failed to start due to hybrid system malfunction // Gen manually started","=
wilfried.kameni@sagemcom.com","43609","02-03-2025 15:35:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004472721","A=
ccacia New","","02-03-2025 15:34:41","02-03-2025 15:25:35","02-03-2025 15:3=
5:33","Active// No power Issue Site on Grid Ubai =3D54,6V, The FME The TX F=
ME Mbah Hosiah (674007438) is informed.","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power I=
ssue Site on Grid Ubai =3D54,6V, The FME The TX FME Mbah Hosiah (674007438)=
 is informed.","wilfried.kameni@sagemcom.com","547","02-03-2025 15:34:41","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0004472716","T=
radex-Nkomo","","02-03-2025 15:33:27","02-03-2025 15:19:16","02-03-2025 16:=
35:54","Grid outage, site went down because gen failed to start // Grid ret=
urn (Investigation ongoing)","Albran Byorel","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen f=
ailed to start // Grid return (Investigation ongoing)","wilfried.kameni@sag=
emcom.com","852","02-03-2025 15:33:27","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004472663","Mam=
bine","","02-03-2025 15:20:51","02-03-2025 15:12:20","02-03-2025 16:01:00",=
"Grid outage, site went down because gen failed to start due to hybrid syst=
em malfunction // Gen manually started","Fanda Brice","Equipment Repair","P=
assive","Hybrid","Hybrid Module","Grid outage, site went down because gen f=
ailed to start due to hybrid system malfunction // Gen manually started","w=
ilfried.kameni@sagemcom.com","512","02-03-2025 15:20:51","Sagemcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004472660","Tam=
tam Weekend","","02-03-2025 15:18:56","02-03-2025 15:10:38","02-03-2025 15:=
20:21","No power issue site on Grid with U=3D56.7 V   The TX FME Mbah Hosia=
h (674007438) FROM Huawei is informed","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on Grid with U=3D56.7 V  The TX FME Mbah Hosiah (674007438) FR=
OM Huawei is informed
","wilfried.kameni@sagemcom.com","499","02-03-2025 15:18:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004472643","V=
allee-Bastos OCM","","02-03-2025 15:14:53","02-03-2025 15:07:39","02-03-202=
5 15:18:26","Grid outage // Grid power return","","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","Grid outage // Grid power return=
","wilfried.kameni@sagemcom.com","435","02-03-2025 15:14:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0004472628","N=
gousso-Savana","","02-03-2025 15:11:59","02-03-2025 14:58:50","02-03-2025 1=
8:58:05","Grid outage, site went down before gen start due to poor battery =
backup // Gen automatically started, Notice that we have disjunction at BTS=
 OCM","Siligap Boris","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, site went down before gen start due to =
poor battery backup // Gen automatically started, Notice that we have disju=
nction at BTS OCM","wilfried.kameni@sagemcom.com","790","02-03-2025 15:11:5=
9","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0004472608","Nko=
l-Mbanda","","02-03-2025 15:08:30","02-03-2025 14:57:53","02-03-2025 18:17:=
47","Grid fluctuation,Site went down because Gen failed to start due to gri=
d bad voltage and no RCP //he bypassed the Grid and started the Gen manuall=
y","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation,Site went down because Gen failed to sta=
rt due to grid bad voltage and no RCP //he bypassed the Grid and started th=
e Gen manually","wilfried.kameni@sagemcom.com","638","02-03-2025 15:08:30",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004472600","Nko=
lbong","","02-03-2025 15:06:10","02-03-2025 14:54:02","02-03-2025 15:35:57"=
,"Grid outage, site went down because gen stopped with alarm ""high temp"" =
// He added water and manually start the Gen","Delor Telezing","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"Grid outage, site went down because gen stopped with alarm ""high temp"" =
// He added water and manually start the Gen","wilfried.kameni@sagemcom.com=
","729","02-03-2025 15:06:10","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004472533","Com=
plex Beac II","","02-03-2025 14:54:45","02-03-2025 14:45:36","02-03-2025 15=
:41:26","Grid outage, site went down because gen failed to start due to gen=
 card faulty // Grid return","Albran Byorel","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen f=
ailed to start due to gen card faulty // Grid return","wilfried.kameni@sage=
mcom.com","550","02-03-2025 14:54:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004472509","M=
imboman-Village","","02-03-2025 14:50:58","02-03-2025 14:41:39","02-03-2025=
 16:51:07","Grid outage, site went down because gen failed to start due to =
Pwc ZTE dysfunction// he reset it and  started Gen manualy","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid outage, site went down because gen failed to start due to Pwc ZTE dys=
function// he reset it and  started Gen manualy","wilfried.kameni@sagemcom.=
com","560","02-03-2025 14:50:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_393","NOCINC0004472474","Ezezang"=
,"","02-03-2025 14:47:50","02-03-2025 14:26:33","02-03-2025 16:25:17","Erro=
r","Parker Tchoup","Incorrectly Logged Tickets","Error","Error","Error","Si=
te was on Gen due to Grid outage, site went down because gen stopped with a=
larm ""high temp"" // He added water and manually start the Gen","system","=
1277","02-03-2025 14:47:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0004472463","M=
vog Mbi New","","02-03-2025 14:45:39","02-03-2025 14:26:33","02-03-2025 16:=
25:17","Site was on Gen due to Grid outage, site went down because gen stop=
ped with alarm ""high temp"" // He added water and manually start the Gen",=
"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine=
 Temp - Coolant Level Issue","Site was on Gen due to Grid outage, site went=
 down because gen stopped with alarm ""high temp"" // He added water and ma=
nually start the Gen","wilfried.kameni@sagemcom.com","1147","02-03-2025 14:=
45:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004472452","E=
ssomba","","02-03-2025 14:43:28","02-03-2025 14:27:21","02-03-2025 16:02:18=
","Site went down because PWC overload (12Kw, 250A) SS IHS Alphonse DEFFO c=
onfirmed// he Reduice the Load and Site is on Gen","Mba Lazare Herve","Equi=
pment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site wen=
t down because PWC overload (12Kw, 250A) SS IHS Alphonse DEFFO confirmed// =
he Reduice the Load and Site is on Gen","wilfried.kameni@sagemcom.com","968=
","02-03-2025 14:43:28","Sagemcom CMR"
"Closed Complete","Site Down","T1549","IHS_YND_295","NOCINC0004472441","NGO=
NA","","02-03-2025 14:41:56","02-03-2025 14:37:49","02-03-2025 17:33:42","G=
rid outage, site went down because gen start and stopped with high temp ala=
rm // He added water and Gen manually started","Mba Lazare Herve","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid outage, site went down because gen start and stopped with high te=
mp alarm // He added water and Gen manuallystarted","wilfried.kameni@sagemc=
om.com","248","02-03-2025 14:41:56","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004472440","Mvo=
g-Manga","","02-03-2025 14:41:41","02-03-2025 13:46:59","02-03-2025 15:05:5=
5","Grid outage, site went down because gen start and stopped with alarm hi=
gh temperature // He opened the shelter doors and gen manually started","Al=
bran Byorel","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid =
outage, site went down because gen start and stopped with alarm high temper=
ature // He opened the shelter doors and gen manually started","kouoh.jean@=
ihstowers.com","3284","02-03-2025 14:41:41","Sagemcom CMR"
"Closed Complete","Site Down","T3175","IHS_YND_566","NOCINC0004472436","Crf=
 Cornier","","02-03-2025 14:40:28","02-03-2025 14:10:19","02-03-2025 15:38:=
02","Grid outage site went down because Gen failed to start due to Gen batt=
ery discharged causing by charging alternator faulty // Gen manually starte=
d with external battery	","MINKA NICOLAS","Equipment Repair","Passive","ACD=
G Gen","ACDG - Charging Alternator","Grid outage site went down because Gen=
 failed to start due to Gen battery discharged causing by charging alternat=
or faulty // Gen manually started with external battery	","wilfried.kameni@=
sagemcom.com","1810","02-03-2025 14:40:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0004472420","Messassi=
 2","","02-03-2025 14:37:00","02-03-2025 13:39:43","02-03-2025 15:37:06","S=
ite went down because PWC overload (12 kilo, 300A) , SS IHS Bernard ATANGAN=
A confirmed// He reset the rectifier	","Fabrice Pouakam","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Site went down becaus=
e PWC overload (12 kilo, 300A) , SS IHS Bernard ATANGANA confirmed// He res=
et the rectifier	","kouoh.jean@ihstowers.com","3438","02-03-2025 14:37:00",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004472405","M=
vog-Ada_OCM","","02-03-2025 14:33:06","02-03-2025 12:45:48","02-03-2025 15:=
21:28","Grid outage, No space to deploy a MDG // Grid Restored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No=
 space to deploy a MDG // Grid Restored","kouoh.jean@ihstowers.com","6439",=
"02-03-2025 14:33:06","Sagemcom CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0004472296","ESS=
OS OASIS 1111","","02-03-2025 14:16:30","02-03-2025 14:09:17","02-03-2025 1=
7:27:12","Site went down because the PWC dysfonction due to load // He rese=
t the PWC AND Grid power return","Siligap Boris","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Site went down because the PW=
C dysfonction due to load // He reset the PWC AND Grid power return","el-da=
lile@sagemcom.com","434","02-03-2025 14:16:30","Sagemcom CMR"
"Closed Complete","Site Down","T1832","IHS_YND_216","NOCINC0004472287","Ele=
veur","","02-03-2025 14:15:24","02-03-2025 14:05:17","02-03-2025 15:22:26",=
"Grid outage;Site went down because Gen started and stopped due to Gen over=
load(20 Kva ,290 A)//Grid return SS IHS Blaise Raoul is informed and confir=
med.","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Grid outage;Site went down because Gen started and stopped due to Gen=
 overload(20 Kva ,290 A)//Grid return SS IHS Blaise Raoul is informed and c=
onfirmed.","el-dalile@sagemcom.com","24558","02-03-2025 14:15:24","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004472192","Mom","",=
"02-03-2025 13:57:40","02-03-2025 13:42:28","02-03-2025 14:20:44","Cascaded=
 Incident from TTO4526182","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, site went down because gen start=
 and stopped with alarm Memory correction // He reset gen card and Gen manu=
ally started","system","310885","02-03-2025 13:57:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004472193","Bondjock=
","","02-03-2025 13:57:40","02-03-2025 13:42:28","02-03-2025 14:20:44","Cas=
caded Incident from TTO4526182","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
start and stopped with alarm Memory correction // He reset gen card and Gen=
 manually started","system","310885","02-03-2025 13:57:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004472187","Emana Ly=
cee","","02-03-2025 13:55:40","02-03-2025 13:14:22","02-03-2025 15:30:19","=
Cascaded Incident from TTO4526215","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen start and stopped due to high temp // He added water and manually st=
art the gen","system","319747","02-03-2025 13:55:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004472178","E=
mana lycee 2","IHS_YND_274","02-03-2025 13:54:29","02-03-2025 13:14:22","02=
-03-2025 15:30:19","Grid outage, site went down because gen start and stopp=
ed due to high temp // He added water and manually start the gen","Fabrice =
Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp -=
 Coolant Level Issue","Grid outage, site went down because gen start and st=
opped due to high temp // He added water and manually start the gen","kouoh=
.jean@ihstowers.com","2408","02-03-2025 13:54:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004472167","M=
amch Building","","02-03-2025 13:53:54","02-03-2025 13:14:40","02-03-2025 1=
5:18:27","Grid outage, site went down because gen stopped with alarm ""high=
 temp"" // He added water and manually start the Gen","Mboua Thierry","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because gen stopped with alarm ""high =
temp"" // He added water and manually start the Gen","kouoh.jean@ihstowers.=
com","2355","02-03-2025 13:53:54","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0004472149","Sap=
eur Mimboman","","02-03-2025 13:50:39","02-03-2025 12:54:38","03-03-2025 07=
:10:57","ACCESS ISSUES DUE TO LANDLORD, Grid outage Site went down because =
Gen overload (20KVA, 300A) SS IHS Alphonse DEFFO confirmed// Grid return. B=
ut Site remains Down, Site up after power reset","Mba Lazare Herve","Access=
 Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lo=
rd","ACCESS ISSUES DUE TO LANDLORD, Grid outage Site went down because Gen =
overload (20KVA, 300A) SS IHS Alphonse DEFFO confirmed// Grid return. But S=
ite remains Down, Site up after power reset","kouoh.jean@ihstowers.com","28=
277","02-03-2025 13:50:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_201","IHS_YND_368","NOCINC0004472148","O=
tele","IHS_YND_370, IHS_YND_372","02-03-2025 13:50:37","02-03-2025 13:42:28=
","02-03-2025 14:20:44","Grid outage, site went down because gen start and =
stopped with alarm Memory correction // He reset gen card and Gen manually =
started","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid outage, site went down because gen start and stopped with =
alarm Memory correction // He reset gen card and Gen manually started","el-=
dalile@sagemcom.com","490","02-03-2025 13:50:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0004472136","O=
lezoa OCM","","02-03-2025 13:49:17","02-03-2025 13:29:11","02-03-2025 16:23=
:06","Grid outage no space to deploy a mobil gen // grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no=
 space to deploy a mobil gen // grid return","danick.tchakouani@sagemcom.co=
m","1207","02-03-2025 13:49:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0004472062","K=
ondengui","","02-03-2025 13:34:52","02-03-2025 12:54:22","02-03-2025 16:55:=
54","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid outage no space to deploy mobile gen.//Grid retun","danick=
.tchakouani@sagemcom.com","292144","02-03-2025 13:34:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0004472054","E=
mombo-Tchad","IHS_YND_114","02-03-2025 13:32:30","02-03-2025 12:54:22","02-=
03-2025 16:55:54","Grid outage no space to deploy mobile gen.//Grid retun",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage no space to deploy mobile gen.//Grid retun","danick.tchakouani@sage=
mcom.com","2289","02-03-2025 13:32:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004472041","H=
-Paradis","","02-03-2025 13:30:54","02-03-2025 12:50:44","02-03-2025 15:19:=
39","grid outage//grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","grid outage//grid return","danick.tchakouani@sag=
emcom.com","2411","02-03-2025 13:30:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0004471983","Anguissa=
 New","","02-03-2025 13:27:45","02-03-2025 12:58:11","02-03-2025 16:31:11",=
"Cascaded Incident from TTO4525890 - Cascade Removed From TTO4525890","MINK=
A NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid outage, no space to deploy a  mobile gen // GRID RETURN","system","327=
869","02-03-2025 13:27:45","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0004471952","MIM=
BOMAN LIBERTE","","02-03-2025 13:25:00","02-03-2025 13:07:52","02-03-2025 1=
5:06:29","Grid outage, site went down gen failed to start // Gen manually s=
tarted (Investigation ongoing)","Mba Lazare Herve","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down gen fai=
led to start // Gen manually started (Investigation ongoing)","el-dalile@sa=
gemcom.com","1030","02-03-2025 13:25:00","Sagemcom CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0004471926","Ngo=
usso MTN","","02-03-2025 13:22:49","02-03-2025 13:03:38","02-03-2025 15:21:=
24","Grid outage // Grid return","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Outage Issue","Grid outage // Grid return","el-dalile@sagemco=
m.com","1151","02-03-2025 13:22:49","Sagemcom CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0004471920","Ngo=
ulmekong-Nord","","02-03-2025 13:21:47","02-03-2025 12:57:39","02-03-2025 1=
5:26:29","Grid outage, site went down because gen start and stoppen with Al=
arm undervoltage // He reset gen card and gen manually started","Siligap Bo=
ris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage, site went down because gen start and stoppen with Alarm undervoltage=
 // He reset gen card and gen manually started","el-dalile@sagemcom.com","2=
340","02-03-2025 13:21:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004471894","L=
abogenie","IHS_YND_568","02-03-2025 13:17:21","02-03-2025 12:58:11","02-03-=
2025 16:31:11","Grid outage, no space to deploy a  mobile gen // GRID RETUR=
N","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid outage, no space to deploy a  mobile gen // GRID RETURN","danick.tchako=
uani@sagemcom.com","1151","02-03-2025 13:17:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_758","NOCINC0004471745","Nkolfoul=
ou CSD MTN","","02-03-2025 13:06:40","02-03-2025 12:50:57","02-03-2025 13:0=
7:43","Cascaded Incident from TTO4525700","Siligap Boris","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage.gen started and =
stoped due to alarm ""low oil pressure""//He reset card GE and gen manually=
 started","system","306630","02-03-2025 13:06:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0004471741","F=
OUGEROLE","","02-03-2025 13:04:34","02-03-2025 12:16:18","02-03-2025 13:17:=
41","Grid outage, site went down because gen start and stopped with high te=
mp alarm // He added water and manually","Siligap Boris","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid=
 outage, site went down because gen start and stopped with high temp alarm =
// He added water and manually","kouoh.jean@ihstowers.com","2897","02-03-20=
25 13:04:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_759","NOCINC0004471737","Nkolfoul=
ou Tsinga Village","","02-03-2025 13:03:51","02-03-2025 12:50:57","02-03-20=
25 13:07:43","Cascaded Incident from TTO4525700","Siligap Boris","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage.gen start=
ed and stoped due to alarm ""low oil pressure""//He reset card GE and gen m=
anually started","system","306631","02-03-2025 13:03:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_296","NOCINC0004471736","Nkolfoul=
ou","","02-03-2025 13:03:51","02-03-2025 12:50:57","02-03-2025 13:07:43","C=
ascaded Incident from TTO4525700","Siligap Boris","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen started and stoped d=
ue to alarm ""low oil pressure""//He reset card GE and gen manually started=
","system","306632","02-03-2025 13:03:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004471735","TSINGA V=
ILLAGE 2","","02-03-2025 13:03:51","02-03-2025 12:50:57","02-03-2025 13:07:=
43","Cascaded Incident from TTO4525700","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage.gen started and s=
toped due to alarm ""low oil pressure""//He reset card GE and gen manually =
started","system","306632","02-03-2025 13:03:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004471734","Mvog-Eba=
nda","","02-03-2025 13:03:50","02-03-2025 12:50:57","02-03-2025 13:07:43","=
Cascaded Incident from TTO4525700","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen started and stoped =
due to alarm ""low oil pressure""//He reset card GE and gen manually starte=
d","system","306631","02-03-2025 13:03:50","Sagemcom CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0004471727","Nko=
lfoulou 2","IHS_YND_269, IHS_YND_719, IHS_YND_758, IHS_YND_296, IHS_YND_759=
","02-03-2025 13:02:13","02-03-2025 12:50:57","02-03-2025 13:07:43","Grid o=
utage.gen started and stoped due to alarm ""low oil pressure""//He reset ca=
rd GE and gen manually started","Siligap Boris","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage.gen started and stoped due=
 to alarm ""low oil pressure""//He reset card GE and gen manually started",=
"stephane.nkamwa@ihstowers.com","677","02-03-2025 13:02:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004471712","E=
MANA BILICK CITY","","02-03-2025 12:59:48","02-03-2025 12:29:33","02-03-202=
5 14:02:25","Grid outage, Site went down because Gen started and stopped du=
e to Gen overload(20kva, 340A) SS IHS Bernad Atagana is informed// he Redui=
ce the Load and site is on Gen","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen s=
tarted and stopped due to Gen overload(20kva, 340A) SS IHS Bernad Atagana i=
s informed// he Reduice the Load and site is on Gen","kouoh.jean@ihstowers.=
com","1817","02-03-2025 12:59:48","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004471700","Nko=
ulou Carriere carrefourt","","02-03-2025 12:57:44","02-03-2025 12:31:15","0=
2-03-2025 14:59:23","Site went down insuffinsufficient of rectifier , SS De=
ffo IHS is informed // He reduced the load, site on grid","Mba Lazare Herve=
","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went do=
wn insuffinsufficient of rectifier , SS Deffo IHS is informed // He reduced=
 the load, site on grid","stephane.nkamwa@ihstowers.com","1590","02-03-2025=
 12:57:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0004471676","N=
sam Sofavinc T0","","02-03-2025 12:53:39","02-03-2025 12:10:28","02-03-2025=
 15:31:33","Grid outage, site went down because gen failed to start due to =
fuel pump faulty // Grid return ( Fuel pump to be replaced)","MINKA NICOLAS=
","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Fuel Pump","Grid ou=
tage, site went down because gen failed to start due to fuel pump faulty //=
 Grid return ( Fuel pump to be replaced)","kouoh.jean@ihstowers.com","2592"=
,"02-03-2025 12:53:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004471582","AFEME NO=
RD","","02-03-2025 12:33:40","02-03-2025 12:18:36","02-03-2025 13:36:53","C=
ascaded Incident from TTO4525526","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","	Grid outage, site went d=
own because gen start and stopped with alarm ""high temp"" due to load // h=
e added water and manually start the Gen","system","272803","02-03-2025 12:=
33:40","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004471575","Nko=
lafeme","IHS_YND_519, IHS_YND_309","02-03-2025 12:32:02","02-03-2025 12:18:=
36","02-03-2025 13:36:53","Grid outage, site went down because gen start an=
d stopped with alarm ""high temp"" due to load // he added water and manual=
ly start the Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","=
ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","	Grid outage, si=
te went down because gen start and stopped with alarm ""high temp"" due to =
load // he added water and manually start the Gen","el-dalile@sagemcom.com"=
,"807","02-03-2025 12:32:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004471570","M=
adison","","02-03-2025 12:31:01","02-03-2025 12:19:51","02-03-2025 14:13:24=
","Grid outage, site went down due to gen Overload(20KVA,220A) and gen card=
 malfunction, SS  Alphose  IHS confirmed // Grid return","MFOUAGUEGUE MATHI=
EU","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,=
 site went down due to gen Overload(20KVA,220A) and gen card malfunction, S=
S  Alphose  IHS confirmed // Grid return","kouoh.jean@ihstowers.com","671",=
"02-03-2025 12:31:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004471549","L=
eboudi","","02-03-2025 12:25:58","02-03-2025 12:18:36","02-03-2025 13:36:53=
","	Grid outage, site went down because gen start and stopped with alarm ""=
high temp"" due to load // he added water and manually start the Gen","TIEN=
TCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","	Grid outage, site went down because gen start and stopped with =
alarm ""high temp"" due to load // he added water and manually start the Ge=
n","danick.tchakouani@sagemcom.com","272803","02-03-2025 12:25:58","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004471545","N=
koabang Ebolmedjock","","02-03-2025 12:23:59","02-03-2025 12:08:51","02-03-=
2025 12:15:47","Active// No power issue, site is on Gen with Ubaie=3D53,6V,=
 Lionel Adjep(655184876) from Huawei is informed. Notice that we have repet=
itive issue","Mba Lazare Herve","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active// No power issue, site i=
s on Gen with Ubaie=3D53,6V, Lionel Adjep(655184876) from Huawei is informe=
d. Notice that we have repetitive issue","el-dalile@sagemcom.com","909","02=
-03-2025 12:23:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004471544","E=
lig-Edzoa","","02-03-2025 12:22:45","02-03-2025 12:05:38","02-03-2025 15:20=
:51","Grid outage // Grid return","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid outage // Grid return","el-dalile@sagemc=
om.com","1029","02-03-2025 12:22:45","Sagemcom CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004471427","Eki=
e sud","","02-03-2025 12:14:48","02-03-2025 12:10:30","02-03-2025 13:16:22"=
,"Grid outage, site went down because gen failed to start gen card and hybr=
id system malfunction // He reset gen card and gen manually started","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, site went down because gen failed to start gen card and hybrid =
system malfunction // He reset gen card and gen manually started","el-dalil=
e@sagemcom.com","259","02-03-2025 12:14:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004471371","B=
ATA Mokolo OCM","","02-03-2025 12:04:09","02-03-2025 11:53:58","02-03-2025 =
12:14:02","	Grid outage,no space to deploy a mobile DG // Grid restored.","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid=
 outage,no space to deploy a mobile DG // Grid restored.","danick.tchakouan=
i@sagemcom.com","612","02-03-2025 12:04:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004471237","A=
wae Ewonkan","","02-03-2025 11:34:15","02-03-2025 10:41:04","02-03-2025 21:=
04:07","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO confirmed","Albran Byorel","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Grid outage, Site went down because Gen overload=
(20KVA,310A) SS IHS Alphonse DEFFO confirmed","el-dalile@sagemcom.com","319=
2","02-03-2025 11:34:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004471232","M=
ontesquieux","IHS_YND_042","02-03-2025 11:33:18","02-03-2025 11:09:12","02-=
03-2025 12:36:12","","Paul BIBOUM","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down because rectifier disfunctionning // He=
 reset it: Site on grid ","danick.tchakouani@sagemcom.com","1447","02-03-20=
25 11:33:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004471196","M=
ontee-Des-Soeurs","","02-03-2025 11:31:40","02-03-2025 11:22:34","02-03-202=
5 11:57:21","Grid outage, Site went down before Gen start due to poor backu=
p// Gen started manually","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen started manually","danick.tchakouani=
@sagemcom.com","547","02-03-2025 11:31:40","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004471058","Mvo=
g-Manga","","02-03-2025 11:22:44","02-03-2025 11:16:34","02-03-2025 12:23:3=
4","","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Gri=
d outage, site went down because gen ran untill fuel shortage // Refueling =
done","el-dalile@sagemcom.com","372","02-03-2025 11:22:44","Sagemcom CMR"
"Closed Complete","Site Down","T0290","IHS_YND_067","NOCINC0004470977","Nko=
a Ayos","","02-03-2025 11:20:12","02-03-2025 11:04:00","02-03-2025 12:38:48=
","Grid outage, site went down because gen start an stopped due to water in=
filtration in tank // He purged The tank and Gen manually started","MINKA N=
ICOLAS","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - W=
ater In The Fuel","Grid outage, site went down because gen start an stopped=
 due to water infiltration in tank // He purged The tank and Gen manually s=
tarted","el-dalile@sagemcom.com","973","02-03-2025 11:20:12","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0004470884","Sap=
eur Mimboman","","02-03-2025 11:08:09","02-03-2025 11:00:54","02-03-2025 12=
:07:54","","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Site down because 02/07 rectifiers Hanging causi=
ng by increase load on site//He reset rectifiers ,site on Gen","el-dalile@s=
agemcom.com","437","02-03-2025 11:08:09","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004470839","Mon=
tee Jouvence","","02-03-2025 11:05:28","02-03-2025 10:53:10","02-03-2025 11=
:48:55","Grid outage,Site went down due to grid bad volage // grid bypass a=
nd gen started manually","Hyemafo Gildas","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Grid outage,Site went down due to =
grid bad volage // grid bypass and gen started manually","el-dalile@sagemco=
m.com","739","02-03-2025 11:05:28","Sagemcom CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0004470827","Av-=
Germaine","","02-03-2025 11:04:11","02-03-2025 10:53:51","02-03-2025 15:22:=
20","Grid outage, No space to deploy a MDG // Grid Restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No sp=
ace to deploy a MDG // Grid Restored","el-dalile@sagemcom.com","621","02-03=
-2025 11:04:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0004470773","N=
GONA","","02-03-2025 10:59:20","02-03-2025 10:54:52","02-03-2025 10:54:54",=
"","Mba Lazare Herve","Incorrectly Logged Tickets","Error","Error","Error",=
"Errr TT","kouoh.jean@ihstowers.com","269","02-03-2025 10:59:20","Sagemcom =
CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004470772","Mel=
en Ba'aba","","02-03-2025 10:58:50","02-03-2025 10:52:28","02-03-2025 10:55=
:29"," Active// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME J=
ulien(693095849) from Huawei is informed","Siligap Boris","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," Acti=
ve// No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Julien(69309=
5849) from Huawei is informed","stephane.nkamwa@ihstowers.com","383","02-03=
-2025 10:58:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004470754","N=
kolfon Cimencam","","02-03-2025 10:56:12","02-03-2025 10:47:04","02-03-2025=
 10:55:54","No power issue on site U=3D52 V site on Grid.  The Tx FME  Fulb=
ert  (654266068) of huawei is informed. Repetitive Issue Notice that site i=
s impacted by AfanoyaII who is not our responsability","Hyemafo Gildas","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue on site U=3D52 V site on Grid. The Tx FME  Fulbert =
 (654266068) of huawei is informed. Repetitive Issue Notice that site is im=
pacted by AfanoyaII who is not our responsability
","danick.tchakouani@sagemcom.com","549","02-03-2025 10:56:12","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0004470743","N=
gousso-II","","02-03-2025 10:54:59","02-03-2025 10:49:53","02-03-2025 12:13=
:43","Grid outage, site went down because gen ran untill fuel shortage // R=
efueling done","MFOUAGUEGUE MATHIEU","Fuel Outage","Passive","Diesel","Dies=
el Outage","Grid outage, site went down because gen ran untill fuel shortag=
e // Refueling done","danick.tchakouani@sagemcom.com","306","02-03-2025 10:=
54:59","Sagemcom CMR"
"Closed Complete","Site Down","T1622","IHS_YND_186","NOCINC0004470728","Ngo=
usso Carrefour","","02-03-2025 10:53:40","02-03-2025 10:50:32","02-03-2025 =
12:04:11","Grid outage, site went down because gen ran untill fuel shortage=
 // Refueling done","Siligap Boris","Fuel Outage","Passive","Diesel","Diese=
l Outage","Grid outage, site went down because gen ran untill fuel shortage=
 // Refueling done","danick.tchakouani@sagemcom.com","189","02-03-2025 10:5=
3:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004470521","M=
ontesquieux","IHS_YND_042","02-03-2025 10:24:15","02-03-2025 10:15:09","02-=
03-2025 10:26:09","Site went down because rectifier disfunctionning // He r=
eset it: Site on grid ","Paul BIBOUM","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down because rectifier disfunctionning //=
 He reset it: Site on grid ","danick.tchakouani@sagemcom.com","546","02-03-=
2025 10:24:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004470517","M=
vog-Ada_OCM","","02-03-2025 10:23:15","02-03-2025 10:15:09","02-03-2025 12:=
36:12","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive"=
,"Site went down because rectifier disfunctionning // He reset it: Site on =
grid ","danick.tchakouani@sagemcom.com","280232","02-03-2025 10:23:15","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_068","IHS_YND_109","NOCINC0004470437","M=
obil-Essos","","02-03-2025 10:15:43","02-03-2025 10:08:36","02-03-2025 11:0=
8:13","Grid outage, Site went down because gen start and stopped with alarm=
"" High temps""// he added water and manually start the gen","Siligap Boris=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid outage, Site went down because gen start and stopped w=
ith alarm"" High temps""// he added water and manually start the gen","el-d=
alile@sagemcom.com","428","02-03-2025 10:15:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004470418","E=
koumdoum","","02-03-2025 10:07:44","02-03-2025 10:00:39","02-03-2025 10:57:=
15","Grid Outage, site went down because Gen start and stopped with ""high =
temp"" alarm due to accordion cut // He oppened the doors and manually star=
t the gen (Accordion to be replace)","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Exhaust","Grid Outage, site went down because Gen=
 start and stopped with ""high temp"" alarm due to accordion cut // He oppe=
ned the doors and manually start the gen (Accordion to be replace)","danick=
.tchakouani@sagemcom.com","426","02-03-2025 10:07:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0004470413","Biteng",=
"","02-03-2025 10:06:20","02-03-2025 09:47:39","02-03-2025 12:38:07","Grid =
outage site went down because Gen failed to start due PWC dysfonction // He=
 reset the PWC and Gen manually started	","Mba Lazare Herve","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage site =
went down because Gen failed to start due PWC dysfonction // He reset the P=
WC and Gen manually started	","system","1121","02-03-2025 10:06:20","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004470376","E=
kounou","","02-03-2025 09:55:44","02-03-2025 09:47:39","02-03-2025 09:50:19=
","No power issue, site is on grid with Ubaie=3D53V, Eloundou(693212405) fr=
om Huawei is informed,Notice that we have disjunction at BTS OCM","Albran B=
yorel","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue, site is on grid with Ubaie=3D53V, Elound=
ou(693212405) from Huawei is informed,Notice that we have disjunction at BT=
S OCM","danick.tchakouani@sagemcom.com","486","02-03-2025 09:55:44","Sagemc=
om CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004470348","Mes=
sassi okolo","","02-03-2025 09:52:01","02-03-2025 09:45:39","02-03-2025 10:=
39:58","Grid outage, Site went because Gen ran until fuel shortage// Refuel=
ing Done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid outage, Site went because Gen ran until fuel shortage// Refueling D=
one","danick.tchakouani@sagemcom.com","383","02-03-2025 09:52:01","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0288","IHS_YND_001","NOCINC0004470249","Roy=
al Hotel Yde","","02-03-2025 09:32:04","02-03-2025 09:29:59","02-03-2025 09=
:41:51","Grid outage, Site went down before Gen start due to poor backup //=
 Grid return (Investigation ongoing)","Paul BIBOUM","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup // Grid return (Investigation ong=
oing)","danick.tchakouani@sagemcom.com","126","02-03-2025 09:32:04","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004470209","E=
ssomba","","02-03-2025 09:25:05","02-03-2025 09:21:58","02-03-2025 11:07:45=
","Site went down because PWC overload (12Kw, 250A) SS IHS Alphonse DEFFO c=
onfirmed// he Reduice the Load and Site is on Gen ","Mba Lazare Herve","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site we=
nt down because PWC overload (12Kw, 250A) SS IHS Alphonse DEFFO confirmed//=
 he Reduice the Load and Site is on Gen ","el-dalile@sagemcom.com","189","0=
2-03-2025 09:25:05","Sagemcom CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0004470126","Mam=
ch Building","","02-03-2025 09:08:13","02-03-2025 08:55:53","02-03-2025 09:=
22:43","Grid outage site went down because Gen stopped with ''Alarm' Over-C=
urrent // he reset the Gen Card and manually started","Mboua Thierry","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site=
 went down because Gen stopped with ''Alarm' Over-Current // he reset the G=
en Card and manually started","el-dalile@sagemcom.com","741","02-03-2025 09=
:08:13","Sagemcom CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0004470104","TON=
GOLO SNEC","","02-03-2025 09:05:04","02-03-2025 09:01:51","02-03-2025 10:51=
:33","Grid outage, site went down because Gen stopped with 'Over-Voltage' a=
larm // He reset the Gen card and Gen manually started","Fabrice Pouakam","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
 site went down because Gen stopped with 'Over-Voltage' alarm // He reset t=
he Gen card and Gen manually started","el-dalile@sagemcom.com","194","02-03=
-2025 09:05:04","Sagemcom CMR"
"Closed Complete","Warning","T0183","IHS_YND_184","NOCINC0004470092","Nkolm=
esseng","","02-03-2025 09:03:11","","","Site went aarm due to PWC overload(=
12K, 230A) // Site stabilized","Siligap Boris","Warning","Warning","POWER",=
"Warning - Rectifier Module Overloaded","	Site went aarm due to PWC overloa=
d(12K, 230A) // Site stabilized","el-dalile@sagemcom.com","1692","02-03-202=
5 09:03:11","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004470056","Mim=
boman4","","02-03-2025 08:52:10","02-03-2025 08:38:27","02-03-2025 09:06:03=
","Grid outage, site went down because gen stopped with alarm ""high temp""=
 // He added water and manually start the Gen","Mba Lazare Herve","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid outage, site went down because gen stopped with alarm ""high temp=
"" // He added water and manually start the Gen","stephane.nkamwa@ihstowers=
.com","824","02-03-2025 08:52:10","Sagemcom CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0004470044","Par=
adis Hotel","","02-03-2025 08:48:58","02-03-2025 08:43:51","02-03-2025 11:2=
8:49","Grid outage, site went down because gen failed to start // Gen manua=
lly started (Investigation ongoing)","Siligap Boris","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down becau=
se gen failed to start // Gen manually started (Investigation ongoing)","da=
nick.tchakouani@sagemcom.com","307","02-03-2025 08:48:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0004470027","Crf-Nkol=
bisson","","02-03-2025 08:44:42","02-03-2025 08:33:11","02-03-2025 09:16:52=
","Cascaded Incident from TTO4523749","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage site went=
 down because Gen failed to start due to Gen battery faulty // Gen manually=
 started with external battery","system","271778","02-03-2025 08:44:42","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004470030","Entree C=
ite Verte","","02-03-2025 08:44:42","02-03-2025 08:33:11","02-03-2025 09:16=
:52","Cascaded Incident from TTO4523749","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen failed to start due to Gen battery faulty // Gen manually started w=
ith external battery","system","271779","02-03-2025 08:44:42","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0004470029","Dagobert=
","","02-03-2025 08:44:42","02-03-2025 08:33:11","02-03-2025 09:16:52","Cas=
caded Incident from TTO4523749","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage site went down =
because Gen failed to start due to Gen battery faulty // Gen manually start=
ed with external battery","system","271781","02-03-2025 08:44:42","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004470028","Nkongtoc=
k","","02-03-2025 08:44:42","02-03-2025 08:33:11","02-03-2025 09:16:52","Er=
ror","Kemeni Franklin","Incorrectly Logged Tickets","Error","Error","Error"=
,"Grid outage site went down because Gen failed to start due to Gen battery=
 faulty // Gen manually started with external battery","system","691","02-0=
3-2025 08:44:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004470022","Nkomkana=
","","02-03-2025 08:44:41","02-03-2025 08:33:11","02-03-2025 09:16:52","Cas=
caded Incident from TTO4523749","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage site went down because Gen failed to st=
art due to Gen battery faulty // Gen manually started with external battery=
","system","271776","02-03-2025 08:44:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0004470024","BATA Mok=
olo OCM","","02-03-2025 08:44:41","02-03-2025 08:33:11","02-03-2025 09:16:5=
2","Cascaded Incident from TTO4523749","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid outage site went down because Gen faile=
d to start due to Gen battery faulty // Gen manually started with external =
battery","system","271775","02-03-2025 08:44:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0004470025","Meyong-M=
eyeme","","02-03-2025 08:44:41","02-03-2025 08:33:11","02-03-2025 09:16:52"=
,"Cascaded Incident from TTO4523749","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid outage site went =
down because Gen failed to start due to Gen battery faulty // Gen manually =
started with external battery","system","271782","02-03-2025 08:44:41","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0004470023","Oyomaban=
g Ecole","","02-03-2025 08:44:41","02-03-2025 08:33:11","02-03-2025 09:16:5=
2","Cascaded Incident from TTO4523749","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Passive","Cascade Passive","Cascade Passive","Grid outage site wen=
t down because Gen failed to start due to Gen battery faulty // Gen manuall=
y started with external battery","system","271777","02-03-2025 08:44:41","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0004470026","Yona Hot=
el","","02-03-2025 08:44:41","02-03-2025 08:33:11","02-03-2025 09:16:52","C=
ascaded Incident from TTO4523749","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site went dow=
n because Gen failed to start due to Gen battery faulty // Gen manually sta=
rted with external battery","system","271780","02-03-2025 08:44:41","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004470019","AFEME NO=
RD","","02-03-2025 08:44:40","02-03-2025 08:33:11","02-03-2025 09:16:52","C=
ascaded Incident from TTO4523749","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site went dow=
n because Gen failed to start due to Gen battery faulty // Gen manually sta=
rted with external battery","system","271781","02-03-2025 08:44:40","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0004470021","Cite-Ver=
te","","02-03-2025 08:44:40","02-03-2025 08:33:11","02-03-2025 09:16:52","C=
ascaded Incident from TTO4523749","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage site went down because Gen failed to =
start due to Gen battery faulty // Gen manually started with external batte=
ry","system","271775","02-03-2025 08:44:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004470020","Nkomkana=
 2","","02-03-2025 08:44:40","02-03-2025 08:33:11","02-03-2025 09:16:52","C=
ascaded Incident from TTO4523749","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due to Gen battery faulty // Gen manually started with e=
xternal battery","system","271779","02-03-2025 08:44:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0004470018","Nkolbi-B=
oss","","02-03-2025 08:44:40","02-03-2025 08:33:11","02-03-2025 09:16:52","=
Cascaded Incident from TTO4523749","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage site went do=
wn because Gen failed to start due to Gen battery faulty // Gen manually st=
arted with external battery","system","271776","02-03-2025 08:44:40","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0004469983","O=
yomabang OCM","IHS_YND_273, IHS_YND_519, IHS_YND_138, IHS_YND_202, IHS_YND_=
200, IHS_YND_686, IHS_YND_559, IHS_YND_230, IHS_YND_271, IHS_YND_232, IHS_Y=
ND_286, IHS_YND_543","02-03-2025 08:36:18","02-03-2025 08:33:11","02-03-202=
5 09:16:52","Grid outage site went down because Gen failed to start due to =
Gen battery faulty // Gen manually started with external battery","TIENTCHE=
U NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Generator=
 Battery","Grid outage site went down because Gen failed to start due to Ge=
n battery faulty // Gen manually started with external battery","danick.tch=
akouani@sagemcom.com","188","02-03-2025 08:36:18","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0004469967","Jou=
vence 2000","","02-03-2025 08:33:19","02-03-2025 08:25:53","02-03-2025 10:2=
0:25","Grid outage site went down because Gen failed to start due to Gen ba=
ttery faulty // Gen manually started with external battery","Delor Telezing=
","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid =
outage site went down because Gen failed to start due to Gen battery faulty=
 // Gen manually started with external battery","stephane.nkamwa@ihstowers.=
com","447","02-03-2025 08:33:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0004469964","F=
OUGEROLE","","02-03-2025 08:32:50","02-03-2025 08:31:46","02-03-2025 10:30:=
43","Grid Outage Site went down because Gen stopped with alarm undervoltage=
 //He Reset the Gen Card and Gen manually started","Siligap Boris","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage Site we=
nt down because Gen stopped with alarm undervoltage //He Reset the Gen Card=
 and Gen manually started","danick.tchakouani@sagemcom.com","122","02-03-20=
25 08:32:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004469957","Jean Ves=
pa 2","","02-03-2025 08:31:30","02-03-2025 08:26:52","02-03-2025 16:01:20",=
"Cascaded Incident from TTO4523701","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage // Grid return","syste=
m","293671","02-03-2025 08:31:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004469949","M=
obil-Kondengui","IHS_YND_544","02-03-2025 08:27:58","02-03-2025 08:26:52","=
02-03-2025 16:01:20","Grid outage // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage // Grid return","=
danick.tchakouani@sagemcom.com","67","02-03-2025 08:27:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0004469918","N=
gousso OCM","","02-03-2025 08:23:19","02-03-2025 08:19:11","02-03-2025 10:0=
9:32","Grid outage, Site went down because gen fails to start due to Batter=
y ge discharged // Gen start with battery back up","Siligap Boris","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, Si=
te went down because gen fails to start due to Battery ge discharged // Gen=
 start with battery back up","el-dalile@sagemcom.com","249","02-03-2025 08:=
23:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0004469899","A=
cropole","","02-03-2025 08:21:52","02-03-2025 08:18:44","02-03-2025 09:56:2=
2","Grid outage site went down because Gen started and stopped with alarm u=
nder frequency // He reset the Gen Card  and Gen manually started","MINKA N=
ICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage site went down because Gen started and stopped with alarm under fr=
equency // He reset the Gen Card  and Gen manually started","el-dalile@sage=
mcom.com","189","02-03-2025 08:21:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_745","NOCINC0004469877","Okolo Ki=
lombo","","02-03-2025 08:13:46","02-03-2025 08:11:41","02-03-2025 10:47:12"=
,"Grid Outage site went down because gen ran untill fuel shortage // refuel=
ing done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid Outage site went down because gen ran untill fuel shortage // refue=
ling done","danick.tchakouani@sagemcom.com","125","02-03-2025 08:13:46","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004469867","SOA VILL=
AGE","","02-03-2025 08:10:41","02-03-2025 08:03:24","02-03-2025 08:47:34","=
Cascaded Incident from TTO4523604","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due to Gen card FAULTY // Gen manually started","system=
","324055","02-03-2025 08:10:41","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004469864","SOA=
 TOWN","IHS_YND_323","02-03-2025 08:09:36","02-03-2025 08:03:24","02-03-202=
5 08:47:51","Grid outage site went down because Gen failed to start due to =
Gen card FAULTY // Gen manually started","Siligap Boris","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down be=
cause Gen failed to start due to Gen card FAULTY // Gen manually started","=
el-dalile@sagemcom.com","373","02-03-2025 08:09:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004469855","A=
wae Ewonkan","","02-03-2025 08:07:20","02-03-2025 07:59:10","02-03-2025 10:=
33:39","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed //He reduice the Load and Manually Started the =
Gen ","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed //He reduice the Load and Manually Started the Ge=
n ","kouoh.jean@ihstowers.com","491","02-03-2025 08:07:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004469853","F=
ouda-New","","02-03-2025 08:06:17","02-03-2025 07:57:00","02-03-2025 12:57:=
44","Grid outage site went down because Gen failed to start with Gen failed=
 // He reset the Gen card and Gen manually started","Delor Telezing","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site =
went down because Gen failed to start with Gen failed // He reset the Gen c=
ard and Gen manually started","kouoh.jean@ihstowers.com","558","02-03-2025 =
08:06:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0004469851","EMANA BI=
LICK CITY","","02-03-2025 08:05:40","02-03-2025 07:48:31","02-03-2025 11:19=
:11","Grid outage, Site went down because Gen started and stopped due to Ge=
n overload(20kva, 340A) SS IHS Bernad Atagana is informed// he Reduice the =
Load and site is on Gen","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Grid outage, Site went down because Gen started =
and stopped due to Gen overload(20kva, 340A) SS IHS Bernad Atagana is infor=
med// he Reduice the Load and site is on Gen","system","1029","02-03-2025 0=
8:05:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004469833","Akak-Nko=
zoa-MTN-IHS","","02-03-2025 08:00:40","02-03-2025 07:48:31","02-03-2025 08:=
16:52","Cascaded Incident from TTO4523563","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because PW=
C dysfunctionning // He reset it ","system","332058","02-03-2025 08:00:40",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_322","NOCINC0004469826","Soa-II",=
"IHS_YND_316, IHS_YND_324","02-03-2025 07:58:10","02-03-2025 07:48:31","02-=
03-2025 08:16:52","Site went down because PWC dysfunctionning // He reset i=
t ","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down because PWC dysfunctionning // He reset it =
","system","579","02-03-2025 07:58:10","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004469821","Tou=
ring Club International","","02-03-2025 07:54:17","02-03-2025 07:45:11","02=
-03-2025 08:20:39","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed // Grid return","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went down=
 because Gen overload (20Kw, 270A) SS IHS Pascaline confirmed // Grid retur=
n","danick.tchakouani@sagemcom.com","547","02-03-2025 07:54:17","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004469795","N=
koabang2","","02-03-2025 07:51:09","02-03-2025 07:42:00","02-03-2025 08:32:=
46","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // He reduced the load and gen manually started","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, site went down due to gen overload (22KVA, 330A), SS Blaise IHS is=
 informed // He reduced the load and gen manually started","danick.tchakoua=
ni@sagemcom.com","550","02-03-2025 07:51:09","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004469746","Ngo=
usso Vallee","","02-03-2025 07:41:08","02-03-2025 07:36:59","02-03-2025 09:=
37:20","Grid outage.gen started and stoped due to alarm ""low oil pressure"=
"//He reset card GE and gen manually started","Siligap Boris","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen started =
and stoped due to alarm ""low oil pressure""//He reset card GE and gen manu=
ally started","danick.tchakouani@sagemcom.com","250","02-03-2025 07:41:08",=
"Sagemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004469728","Nko=
abang entree carriere","","02-03-2025 07:37:35","02-03-2025 07:35:20","02-0=
3-2025 08:48:13","Grid outage, site went down because gen fails to start du=
e to battery Gen faulty // Gen start with external battery","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Gri=
d outage, site went down because gen fails to start due to battery Gen faul=
ty // Gen start with external battery","danick.tchakouani@sagemcom.com","13=
5","02-03-2025 07:37:35","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004469722","AWA=
E OCM","","02-03-2025 07:36:18","02-03-2025 07:33:13","02-03-2025 07:44:23"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen automatically started","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen automatically started"=
,"danick.tchakouani@sagemcom.com","187","02-03-2025 07:36:18","Sagemcom CMR=
"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004469713","Tsi=
nga village","","02-03-2025 07:34:25","02-03-2025 07:28:14","02-03-2025 14:=
49:06","Site unstable due to insufficience of rectifer SS IHS Bernard ATANG=
ANA confirmed // He reset the rectifier","Delor Telezing","Equipment Repair=
","Passive","Rectifier","Rectifier Module","Site unstable due to insufficie=
nce of rectifer SS IHS Bernard ATANGANA confirmed // He reset the rectifier=
","el-dalile@sagemcom.com","371","02-03-2025 07:34:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004469712","B=
iteng-Maetur","","02-03-2025 07:34:13","02-03-2025 07:31:08","02-03-2025 13=
:26:21","Grid outage site went down due to Gen overload(20kva, 280A) SS IHS=
 Alphonse DEFFO confirmed // He reduced the load","Mba Lazare Herve","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went =
down due to Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed // He=
 reduced the load","danick.tchakouani@sagemcom.com","187","02-03-2025 07:34=
:13","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004469704","Mes=
sassi 2","","02-03-2025 07:33:14","02-03-2025 07:27:04","02-03-2025 07:31:4=
1","Site went down due to rectifiers disfunction (01/04) SS IHS Bernard Ata=
ngana confirmed// He reset rectifiers (Rectifiers to be replaced)","Fabrice=
 Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site=
 went down due to rectifiers disfunction (01/04) SS IHS Bernard Atangana co=
nfirmed// He reset rectifiers (Rectifiers to be replaced)","danick.tchakoua=
ni@sagemcom.com","371","02-03-2025 07:33:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004469702","O=
mnisport-Rail","","02-03-2025 07:32:29","02-03-2025 07:25:20","02-03-2025 0=
8:36:20","Site went down due to 02/06 rectifiers burned, Bernard Atangana i=
s informed // He reduise the load, Site on grid","Delor Telezing","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module","Site went down due to 0=
2/06 rectifiers burned, Bernard Atangana is informed // He reduise the load=
, Site on grid","danick.tchakouani@sagemcom.com","430","02-03-2025 07:32:29=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004469697","S=
atcom","","02-03-2025 07:31:18","02-03-2025 07:25:13","02-03-2025 15:15:23"=
,"No power issue site on Grid with U=3D53,02 V. The Tx Fme Armand Ngestsa (=
691144412) of Huawei is informed","Delor Telezing","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on Grid with U=3D53,02 V. The Tx Fme Armand Ngestsa (691144412) of =
Huawei is informed","danick.tchakouani@sagemcom.com","366","02-03-2025 07:3=
1:18","Sagemcom CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004469695","NTE=
MASSI","","02-03-2025 07:30:39","02-03-2025 07:26:27","02-03-2025 09:21:42"=
,"Grid outage site went down because Gen failed to start due to Gen card FA=
ULTY // Gen manually started","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start due to Gen card FAULTY // Gen manually started","danick.tch=
akouani@sagemcom.com","253","02-03-2025 07:30:39","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004469683","Nko=
lo II New","","02-03-2025 07:28:00","02-03-2025 07:24:49","02-03-2025 07:32=
:25","Grid outage, site went down because gen failed to start due to PWC ma=
lfunction // Gen manually started","Mba Lazare Herve","Equipment Repair","P=
assive","Rectifier","Rectifier Module Overloaded","Grid outage, site went d=
own because gen failed to start due to PWC malfunction // Gen manually star=
ted","danick.tchakouani@sagemcom.com","193","02-03-2025 07:28:00","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004469579","M=
imboman-Ecole","","02-03-2025 07:16:54","02-03-2025 07:14:37","02-03-2025 0=
7:18:23","Grid outage, Site went down before Gen start due to poor backup/ =
// Gen automatically started","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup/ // Gen automatically started","dani=
ck.tchakouani@sagemcom.com","138","02-03-2025 07:16:54","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004469508","Aha=
la Echangeur","","02-03-2025 07:03:39","02-03-2025 07:01:18","02-03-2025 18=
:35:53","Site went down due to insufficiency of rectifier // He reduced the=
 load , site on grid","MINKA NICOLAS","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down due to insufficiency of rectifier //=
 He reduced the load , site on grid","el-dalile@sagemcom.com","142","02-03-=
2025 07:03:39","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004469385","NYO=
M FACE MAETUR","","02-03-2025 06:34:14","02-03-2025 06:32:02","02-03-2025 0=
6:49:02","Grid outage, site went down because Gen failed to started due to =
Gen card faullty //Gen manually started","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down=
 because Gen failed to started due to Gen card faullty //Gen manually start=
ed","danick.tchakouani@sagemcom.com","133","02-03-2025 06:34:14","Sagemcom =
CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004469366","NYO=
M 2 IHS","","02-03-2025 06:29:37","02-03-2025 06:25:16","02-03-2025 06:46:3=
6","Grid Outage Site went down due to CB Rectifier (100A)  Disjunted in the=
 PWC//He reamed the CB and Site is on Gen","Fabrice Pouakam","Equipment Rep=
air","Passive","Rectifier","Rectifier - Circuit Breaker","Grid Outage Site =
went down due to CB Rectifier (100A)  Disjunted in the PWC//He reamed the C=
B and Site is on Gen","danick.tchakouani@sagemcom.com","262","02-03-2025 06=
:29:37","Sagemcom CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0004469288","ELO=
UMDEM CARRIERE 2","","02-03-2025 05:58:48","02-03-2025 05:53:15","02-03-202=
5 07:13:41","Grid outage, site went down because gen ran untill fuel shorta=
ge // Refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diese=
l Outage","Grid outage, site went down because gen ran untill fuel shortage=
 // Refueling done","ludovic-anselme.mouliom-mapoure@sagemcom","335","02-03=
-2025 05:58:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_520","NOCINC0004469262","SIMBOCK =
BONAMBAPE","","02-03-2025 05:50:10","02-03-2025 05:42:49","02-03-2025 05:50=
:57","ACTIVE// No  power issue on site, site on Grid with Ubaie=3D 54,4V Th=
e Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed.","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","ACTIVE// No  power issue on site, site on Grid with Ubaie=
=3D 54,4V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed.",=
"system","441","02-03-2025 05:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0004469263","Eloumdem=
 stade","","02-03-2025 05:50:10","02-03-2025 05:42:49","02-03-2025 06:22:59=
","Cascaded Incident from TTO4522912","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // Refueling done","system","267729","02-03-=
2025 05:50:10","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004469258","Sim=
bock MTN","IHS_YND_793","02-03-2025 05:48:13","02-03-2025 05:42:49","02-03-=
2025 06:22:59","Grid outage, site went down because gen ran untill fuel sho=
rtage // Refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Di=
esel Outage","Grid outage, site went down because gen ran untill fuel short=
age // Refueling done","mariam.tchonang@sagemcom.com","325","02-03-2025 05:=
48:13","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004469209","Men=
dong NB","","02-03-2025 05:28:40","02-03-2025 05:08:30","02-03-2025 08:49:3=
4","Grid outage.no space to deploy a MDG// Grid Restored","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no space =
to deploy a MDG// Grid Restored","ludovic-anselme.mouliom-mapoure@sagemcom"=
,"1211","02-03-2025 05:28:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004469086","M=
ontee-Jouvence-II","","02-03-2025 05:06:50","02-03-2025 04:59:24","02-03-20=
25 06:07:02","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed//the Load reduice and Site is on Grid","Hyemafo Gildas","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site=
 went down due to PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed/=
/the Load reduice and Site is on Grid","ludovic-anselme.mouliom-mapoure@sag=
emcom","448","02-03-2025 05:06:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0004469083","E=
mombo 2","","02-03-2025 05:03:23","02-03-2025 04:30:04","02-03-2025 04:35:1=
7","Active // No power issue site on Grid with U=3D54,7 V Tx Fme Armand Nge=
stsa (691144412) of huawei is informed","MINKA NICOLAS","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue site on Grid with U=3D54,7 V Tx Fme Armand Ngestsa (69114=
4412) of huawei is informed","mariam.tchonang@sagemcom.com","2000","02-03-2=
025 05:03:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004469059","S=
hell-Nsimeyong","","02-03-2025 04:52:33","02-03-2025 04:51:17","02-03-2025 =
04:52:27","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","ludovic-anselme.mouliom-mapoure@sagemcom","77","02-03-2025 04:52:=
33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004469042","N=
KOLMEKONG YDE","","02-03-2025 04:48:27","02-03-2025 04:41:41","02-03-2025 0=
4:49:26","Site went down because PWC dysfunctionning IHS SS BERNARD ATANGAN=
A is informed and confirmed// grid return","Fabrice Pouakam","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Site went down be=
cause PWC dysfunctionning IHS SS BERNARD ATANGANA is informed and confirmed=
// grid return","mariam.tchonang@sagemcom.com","407","02-03-2025 04:48:27",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004469028","O=
mnisport-Rail","","02-03-2025 04:42:53","02-03-2025 04:33:36","02-03-2025 0=
4:47:18","Site went down due to 02/06 rectifiers burned, Bernard Atangana i=
s informed // He withdrawn 02 rectifiers, site on grid with 04 rectifiers",=
"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to 02/06 rectifiers burned, Bernard Atangana is infor=
med // He withdrawn 02 rectifiers, site on grid with 04 rectifiers","mariam=
.tchonang@sagemcom.com","558","02-03-2025 04:42:53","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004469022","MAN=
GUIERS CHAPELLE","","02-03-2025 04:39:05","02-03-2025 04:30:50","02-03-2025=
 04:49:25","Grid outage .gen failed to start due to battery GE faulty//Grid=
 return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - =
Generator Battery","Grid outage .gen failed to start due to battery GE faul=
ty//Grid return","ludovic-anselme.mouliom-mapoure@sagemcom","576","02-03-20=
25 04:39:05","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004468878","OTE=
LE MTN","","02-03-2025 03:44:42","02-03-2025 03:35:26","02-03-2025 04:18:20=
","Grid outage.gen failed to start due to automation malfunctionning//Gen m=
anually started ","Fanda Brice","Equipment Repair","Passive","Control Panel=
","ATS-AMF Issue","Grid outage.gen failed to start due to automation malfun=
ctionning//Gen manually started ","mariam.tchonang@sagemcom.com","557","02-=
03-2025 03:44:42","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004468829","Mes=
sassi 2","","02-03-2025 03:19:47","02-03-2025 03:12:34","02-03-2025 03:17:0=
0","No power issue iste on grid with U=3D52.6v FME Synphorien (691316854) f=
rom Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue iste o=
n grid with U=3D52.6v FME Synphorien (691316854) from Huawei is informed","=
mariam.tchonang@sagemcom.com","435","02-03-2025 03:19:47","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004468814","Jou=
vence Mbenda","","02-03-2025 03:08:13","02-03-2025 03:03:53","02-03-2025 05=
:36:11","Site was on Gen due to Grid outage, site went down because gen sto=
pped with alarm ""high temp"" // He added water and manually start the Gen"=
,"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engi=
ne Temp - Coolant Level Issue","Site was on Gen due to Grid outage, site we=
nt down because gen stopped with alarm ""high temp"" // He added water and =
manually start the Gen","mariam.tchonang@sagemcom.com","261","02-03-2025 03=
:08:13","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004468751","Mon=
tee Jouvence","","02-03-2025 02:26:51","02-03-2025 02:16:42","02-03-2025 04=
:46:48","Site was on Gen due to Grid outage, site went down because gen sto=
pped with alarm ""high temp"" // He added water and manually start the Gen"=
,"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engi=
ne Temp - Coolant Level Issue","Site was on Gen due to Grid outage, site we=
nt down because gen stopped with alarm ""high temp"" // He added water and =
manually start the Gen","ludovic-anselme.mouliom-mapoure@sagemcom","610","0=
2-03-2025 02:26:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0004468723","M=
ontee-Jouvence","","02-03-2025 02:03:34","02-03-2025 01:58:16","02-03-2025 =
04:38:04","Grid outage, site went down because gen failed to start due to b=
attery GE faulty // Gen manually started with external battery","Hyemafo Gi=
ldas","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","G=
rid outage, site went down because gen failed to start due to battery GE fa=
ulty // Gen manually started with external battery","mariam.tchonang@sagemc=
om.com","319","02-03-2025 02:03:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004468600","M=
amch Building","","02-03-2025 00:57:23","01-03-2025 22:11:30","02-03-2025 0=
0:02:34","Grid outage, site went down because gen start and stopped with ov=
er current alarm(Unpruven alarm) // Reset of gen card done and gen started"=
,"Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, site went down because gen start and stopped with over c=
urrent alarm(Unpruven alarm) // Reset of gen card done and gen started","ma=
riam.tchonang@sagemcom.com","9955","02-03-2025 00:57:23","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004468522","UPA=
C LP","","02-03-2025 00:28:52","02-03-2025 00:24:28","02-03-2025 09:56:40",=
"Grid outage no space -to deploy a mobil // Gen.grid power ","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spa=
ce -to deploy a mobil // Gen.grid power ","ludovic-anselme.mouliom-mapoure@=
sagemcom","265","02-03-2025 00:28:52","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004468436","Men=
dong3","","01-03-2025 23:50:14","01-03-2025 23:48:59","02-03-2025 09:51:07"=
,"Grid outage,no space to deploy a mobile DG // Grid restored.","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no =
space to deploy a mobile DG // Grid restored.","ludovic-anselme.mouliom-map=
oure@sagemcom","76","01-03-2025 23:50:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004468399","E=
kombitie","","01-03-2025 23:43:00","01-03-2025 23:36:28","02-03-2025 01:38:=
03","Grid fluctuations, site went down because Gen failed to start due to g=
rid bad voltage  // He bypassed the grid and started Gen manually","Fabrice=
 Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuations, site went down because Gen failed to start due =
to grid bad voltage  // He bypassed the grid and started Gen manually","mar=
iam.tchonang@sagemcom.com","394","01-03-2025 23:43:00","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004468328","Mes=
sassi 2","","01-03-2025 23:21:00","01-03-2025 23:12:51","02-03-2025 00:45:5=
1","No power issue iste on grid with U=3D52.6v  FME  Synphorien (691316854)=
 from Huawei is informed site up at 11:21 PM","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue iste on grid with U=3D52.6v  FME  Synphorien (691316854) fr=
om Huawei is informed site up at 11:21 PM","ludovic-anselme.mouliom-mapoure=
@sagemcom","490","01-03-2025 23:21:00","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004468327","NYO=
M FACE MAETUR","","01-03-2025 23:20:14","01-03-2025 23:09:02","02-03-2025 0=
0:01:42","Grid outage.gen failed to start due to card GE faulty //Gen manua=
lly started ","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","AC=
DG - Control Panel","Grid outage.gen failed to start due to card GE faulty =
//Gen manually started ","ludovic-anselme.mouliom-mapoure@sagemcom","673","=
01-03-2025 23:20:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004468326","N=
kolondom","","01-03-2025 23:18:56","01-03-2025 23:11:40","02-03-2025 00:30:=
22","Grid fluctuation, Site went down because Gen failed to start due to gr=
id bad voltage,// He bypass grid and manually start the gen","Fabrice Pouak=
am","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, Site went down because Gen failed to start due to grid=
 bad voltage,// He bypass grid and manually start the gen","mariam.tchonang=
@sagemcom.com","437","01-03-2025 23:18:56","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004468294","NYO=
M 2 IHS","","01-03-2025 23:14:00","01-03-2025 23:09:43","01-03-2025 23:19:1=
5"," Site went down due to disjunction of Rectifier CB(40) // CB put back o=
n","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier - =
Circuit Breaker"," Site went down due to disjunction of Rectifier CB(40) //=
 CB put back on","ludovic-anselme.mouliom-mapoure@sagemcom","258","01-03-20=
25 23:14:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004468225","S=
atcom","","01-03-2025 22:53:00","01-03-2025 21:54:13","02-03-2025 01:56:52"=
,"Active // No power issue site on Grid with U=3D53,02 V Tx Fme Armand Nges=
tsa (691144412) of huawei is informed site up at 11:35 PM","Delor Telezing"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active // No power issue site on Grid with U=3D53,02 V Tx Fme =
Armand Ngestsa (691144412) of huawei is informed site up at 11:35 PM","ludo=
vic-anselme.mouliom-mapoure@sagemcom","3528","01-03-2025 22:53:00","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004468222","B=
iteng-Maetur","","01-03-2025 22:50:31","01-03-2025 21:38:08","01-03-2025 23=
:08:54","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Over Volt=
age","Grid outage, Site went down because Gen started and stopped due to Ge=
n overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","lud=
ovic-anselme.mouliom-mapoure@sagemcom","4345","01-03-2025 22:50:31","Sagemc=
om CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004468111","Cha=
rles-Atangana","","01-03-2025 22:30:22","01-03-2025 22:12:05","02-03-2025 0=
0:04:03","Grid outage.//Grid return","","Grid Supply","Passive","Grid","Nat=
ional Grid - Grid Outage Issue","Grid outage.//Grid return","ludovic-anselm=
e.mouliom-mapoure@sagemcom","1234","01-03-2025 22:30:22","Sagemcom CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0004468097","RUE=
 FOE","","01-03-2025 22:28:23","01-03-2025 22:03:12","02-03-2025 06:55:28",=
"Access issue during the night (Grid outage, site went down because Gen sto=
pped with 'Over-Voltage' alarm // He reset the Gen card and Gen manually st=
arted)","Delor Telezing","Access Denial","Lease Or Legal","Landlord Related=
 Issues","Access Issue - Land Lord","Access issue during the night (Grid ou=
tage, site went down because Gen stopped with 'Over-Voltage' alarm // He re=
set the Gen card and Gen manually started)","ludovic-anselme.mouliom-mapour=
e@sagemcom","1512","01-03-2025 22:28:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004467927","M=
vog-Ada_OCM","","01-03-2025 21:59:06","01-03-2025 16:16:51","01-03-2025 22:=
14:57","Grid outage.no space to deploy a mobile gen//Grid return ","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.=
no space to deploy a mobile gen//Grid return ","cedric.tiani@sagemcom.com",=
"20536","01-03-2025 21:59:06","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004467848","Eto=
 koss Yde","","01-03-2025 21:43:58","01-03-2025 21:35:46","01-03-2025 22:28=
:53","Grid outage, site went down because gen failed to start due to Grid c=
ontactor no excited // He excited Grid contactor and Site is on Grid","Fand=
a Brice","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid=
 outage, site went down because gen failed to start due to Grid contactor n=
o excited // He excited Grid contactor and Site is on Grid","ferot.nongni-d=
jiogap@sagemcom.com","493","01-03-2025 21:43:58","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004467789","Ema=
na","","01-03-2025 21:29:18","01-03-2025 19:32:56","01-03-2025 20:54:04","S=
ite went down due to work (Fabrice(657108613) / Sagemcom, SWAP of PWC )// E=
nd of work ","Fabrice Pouakam","Equipment Replacement","Passive","Planned A=
ctivity","Planned Activity - Passive","Site went down due to work (Fabrice(=
657108613) / Sagemcom, SWAP of PWC )// End of work ","ferot.nongni-djiogap@=
sagemcom.com","6983","01-03-2025 21:29:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004467754","Dong",""=
,"01-03-2025 21:22:40","01-03-2025 21:16:23","01-03-2025 21:18:23","Cascade=
d Incident from TTO4521112","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue with U=3D54V //site on=
 gen  Site up at 09:18 PM Gregoire from Huawei is informed ","system","2908=
01","01-03-2025 21:22:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004467749","D=
onga","IHS_YND_444","01-03-2025 21:21:36","01-03-2025 21:16:23","01-03-2025=
 21:18:23","Active//No power issue with U=3D54V //site on gen  Site up at 0=
9:18 PM Gregoire from Huawei is informed ","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue with U=3D54V //site on gen  Site up at 09:18 PM Gregoire=
 from Huawei is informed ","cedric.tiani@sagemcom.com","314","01-03-2025 21=
:21:36","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004467544","Com=
plex Beac II","","01-03-2025 20:48:19","01-03-2025 20:32:13","01-03-2025 21=
:18:56","Grid outage site went down because Gen failed to start due to Gen =
card dysfonction // He reset the Gen card and Gen manually started","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage site went down because Gen failed to start due to Gen card dysfon=
ction // He reset the Gen card and Gen manually started","ferot.nongni-djio=
gap@sagemcom.com","967","01-03-2025 20:48:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0004467537","MBALNGON=
G LYCEE","","01-03-2025 20:47:51","01-03-2025 20:37:57","01-03-2025 20:45:4=
7","Cascaded Incident from TTO4520845","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because 4/8 rectif=
iers disfunctionning// He reset it and site on grid ","system","1235293","0=
1-03-2025 20:47:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0004467536","ELOUMDEM=
 CARRIERE","","01-03-2025 20:47:50","01-03-2025 20:37:57","01-03-2025 20:45=
:47","Cascaded Incident from TTO4520845","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because 4/8 rect=
ifiers disfunctionning// He reset it and site on grid ","system","1235293",=
"01-03-2025 20:47:50","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004467513","Lad=
a I Yde","","01-03-2025 20:45:25","01-03-2025 20:22:11","01-03-2025 20:25:0=
3","No power issue site on grid with U=3D54v Lionel Adjep(655184876) from H=
uawei is informed//site up at 09:07 PM ","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue site on grid with U=3D54v Lionel Adjep(655184876) from Huawei i=
s informed//site up at 09:07 PM ","ferot.nongni-djiogap@sagemcom.com","1395=
","01-03-2025 20:45:25","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004467510","Aha=
la","IHS_YND_767, IHS_YND_765","01-03-2025 20:45:12","01-03-2025 20:37:57",=
"01-03-2025 20:45:47","Site went down because 4/8 rectifiers disfunctionnin=
g// He reset it and site on grid ","Hyemafo Gildas","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Site went down because 4/8 rectifiers=
 disfunctionning// He reset it and site on grid ","cedric.tiani@sagemcom.co=
m","437","01-03-2025 20:45:12","Sagemcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004467484","Tam=
tam Weekend","","01-03-2025 20:39:56","01-03-2025 20:21:48","01-03-2025 21:=
07:23","Site went down due to CB (63A) Disjunted in the DC-Box because the =
Load Increase //He reamed the CB(63A)","Hyemafo Gildas","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site wen=
t down due to CB (63A) Disjunted in the DC-Box because the Load Increase //=
He reamed the CB(63A)","ferot.nongni-djiogap@sagemcom.com","1089","01-03-20=
25 20:39:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004467099","M=
amch Building","","01-03-2025 19:32:55","01-03-2025 19:11:44","01-03-2025 2=
0:47:49","Grid outage, site went down because gen start and stopped with ov=
er current alarm(Unpruven alarm) // Reset of gen card done and gen started"=
,"Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, site went down because gen start and stopped with over c=
urrent alarm(Unpruven alarm) // Reset of gen card done and gen started","ce=
dric.tiani@sagemcom.com","1273","01-03-2025 19:32:55","Sagemcom CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004467059","Cha=
rles-Atangana","","01-03-2025 19:24:32","01-03-2025 19:12:26","01-03-2025 2=
0:50:57","Grid outage // MDG of 20 KVA has deployed","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage // MDG of 20 K=
VA has deployed","ferot.nongni-djiogap@sagemcom.com","773","01-03-2025 19:2=
4:32","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0004466983","AFE=
ME NORD","IHS_YND_808","01-03-2025 19:11:05","01-03-2025 16:23:35","01-03-2=
025 16:26:24","Active: no power issue, site is on grid with Ubaie=3D54V, Mo=
hamadou((691144435) from Huawie is informed, site impacted by rain","TIENTC=
HEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active: no power issue, site is on grid wit=
h Ubaie=3D54V, Mohamadou((691144435) from Huawie is informed, site impacted=
 by rain","ferot.nongni-djiogap@sagemcom.com","10051","01-03-2025 19:11:05"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0004466897","B=
ONAS YDE","","01-03-2025 18:47:52","01-03-2025 18:46:32","01-03-2025 18:48:=
27","Grid fluctuation, Site went down because Gen started and stopped due t=
o Grid bad voltage// Grid stabilized","Paul BIBOUM","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site w=
ent down because Gen started and stopped due to Grid bad voltage// Grid sta=
bilized","cedric.tiani@sagemcom.com","80","01-03-2025 18:47:52","Sagemcom C=
MR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004466896","Ole=
mbe MTN","","01-03-2025 18:47:35","01-03-2025 18:43:27","01-03-2025 19:08:4=
4","Grid outage, site went down before gen start due to poor battery backup=
 // Gen started automatically","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen started automatically=
","ferot.nongni-djiogap@sagemcom.com","249","01-03-2025 18:47:35","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004466891","Nko=
zoa","","01-03-2025 18:46:13","01-03-2025 18:42:04","01-03-2025 18:50:29","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// grid return","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, =
site went down due to gen overload (20kva, 340A) SS HIS Felix bateu is info=
rmed and confirmed// grid return","ferot.nongni-djiogap@sagemcom.com","250"=
,"01-03-2025 18:46:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004466737","S=
hell-Nsimeyong","","01-03-2025 18:15:54","01-03-2025 18:11:38","01-03-2025 =
18:20:34","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","cedric.tiani@sagemcom.com","257","01-03-2025 18:15:54","Sagemcom =
CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004466598","Ema=
na","","01-03-2025 17:48:43","01-03-2025 17:42:36","01-03-2025 17:54:16","G=
rid outage, site went down before gen start due to poor battery backup // G=
en automatically started","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen automatically started","fe=
rot.nongni-djiogap@sagemcom.com","368","01-03-2025 17:48:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004466501","A=
wae Ewonkan","","01-03-2025 17:32:25","01-03-2025 17:07:07","01-03-2025 20:=
19:59","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // He reduced the load","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went =
down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // =
He reduced the load","cedric.tiani@sagemcom.com","1519","01-03-2025 17:32:2=
5","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004466371","C=
omplexe-BEAC","","01-03-2025 17:10:03","01-03-2025 17:01:27","01-03-2025 17=
:23:17","Grid outage , Site went down before Gen start due to poor backup//=
 GEN started automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage , Site went down b=
efore Gen start due to poor backup// GEN started automatically","cedric.tia=
ni@sagemcom.com","517","01-03-2025 17:10:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0004466365","C=
arrefourt Nkomo","","01-03-2025 17:08:57","01-03-2025 16:49:48","01-03-2025=
 16:50:17","No power issue site on grid with U=3D53v Lionnel Steeve from Hu=
awei  site up at 05:59 PM","Mba Lazare Herve","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on grid with U=3D53v Lionnel Steeve from Huawei  site up at 05:59 PM","f=
erot.nongni-djiogap@sagemcom.com","1151","01-03-2025 17:08:57","Sagemcom CM=
R"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004466276","Mes=
sassi 2","","01-03-2025 16:59:51","01-03-2025 16:55:40","01-03-2025 17:03:1=
7","Site went down because PWC overload (12 kilo, 300A) , SS IHS Bernard AT=
ANGANA confirmed// He reset the rectifier","Fabrice Pouakam","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Site went down be=
cause PWC overload (12 kilo, 300A) , SS IHS Bernard ATANGANA confirmed// He=
 reset the rectifier","cedric.tiani@sagemcom.com","253","01-03-2025 16:59:5=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0004466268","N=
komo","","01-03-2025 16:57:48","01-03-2025 16:50:38","01-03-2025 18:00:25",=
"Grid outage, Site went because Gen ran until fuel shortage// Refueling Don=
e","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outage","Gri=
d outage, Site went because Gen ran until fuel shortage// Refueling Done","=
cedric.tiani@sagemcom.com","430","01-03-2025 16:57:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004466251","V=
allee-Bastos OCM","","01-03-2025 16:54:55","01-03-2025 16:14:49","01-03-202=
5 16:18:45","Active: no power issue, site is on grid with Ubaie=3D53V, Arma=
nd Nguetsa(691144412) from Huawei is informed, rain  found in BTS OCM","","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active: no power issue, site is on grid with Ubaie=3D53V, Armand=
 Nguetsa(691144412) from Huawei is informed, rain  found in BTS OCM","olivi=
er.kwedi@ihstowers.com","2407","01-03-2025 16:54:55","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004466249","Nko=
lbisson usines des eaux 2","","01-03-2025 16:54:16","01-03-2025 16:47:08","=
01-03-2025 17:28:02","Grid outage, site went down because gen failed to sta=
rt with alarm undervoltage // He reset gen card and gen manually started","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - C=
ontrol Panel","Grid outage, site went down because gen failed to start with=
 alarm undervoltage // He reset gen card and gen manually started","ferot.n=
ongni-djiogap@sagemcom.com","429","01-03-2025 16:54:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004466237","E=
MANA BILICK CITY","","01-03-2025 16:52:16","01-03-2025 16:06:42","01-03-202=
5 17:09:30","Grid outage, Site went down because Landlord forbidden to star=
t the Gen due to Noise // grid return","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Emergency Stop","Grid outage, Site went down =
because Landlord forbidden to start the Gen due to Noise // grid return","c=
edric.tiani@sagemcom.com","2736","01-03-2025 16:52:16","Sagemcom CMR"
"Closed Complete","Site Down","T3446","IHS_YND_712","NOCINC0004466232","Nko=
lkoumou OCM","","01-03-2025 16:51:31","01-03-2025 16:40:31","01-03-2025 17:=
03:09","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down because gen start and=
 stopped with alarm over current // He reduced the load and gen manually st=
arted","ferot.nongni-djiogap@sagemcom.com","271374","01-03-2025 16:51:31","=
Sagemcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0004466219","Nko=
lbisson usine des eaux","IHS_YND_712","01-03-2025 16:49:37","01-03-2025 16:=
38:31","01-03-2025 17:03:24","Grid outage, site went down because gen start=
 and stopped with alarm over current // He reduced the load and gen manuall=
y started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage, site went down because gen start an=
d stopped with alarm over current // He reduced the load and gen manually s=
tarted","ferot.nongni-djiogap@sagemcom.com","709","01-03-2025 16:49:37","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004466202","M=
ontee-Jouvence-II","","01-03-2025 16:45:11","01-03-2025 16:42:54","01-03-20=
25 19:51:48","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed // he reset and started the Gen manually","Hyemafo Gildas=
","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","S=
ite went down due to PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirm=
ed // he reset and started the Gen manually","cedric.tiani@sagemcom.com","1=
38","01-03-2025 16:45:11","Sagemcom CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0004466185","Oko=
lo Kilombo","","01-03-2025 16:42:57","01-03-2025 16:35:48","01-03-2025 16:5=
4:06","Grid outage, site went down because gen fails to start due to Gen ca=
ble faulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive","=
Infrastructure","Armoured Cable","Grid outage, site went down because gen f=
ails to start due to Gen cable faulty // Grid return","ferot.nongni-djiogap=
@sagemcom.com","430","01-03-2025 16:42:57","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0004466144","Bit=
oto","","01-03-2025 16:34:50","01-03-2025 16:30:38","01-03-2025 18:06:37","=
Grid outage, site went down because gen failed to start due to PWC ZTE malf=
unction and battery backup burned // He reset the controller and gen manual=
ly started","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Grid outage, site went down because gen failed =
to start due to PWC ZTE malfunction and battery backup burned // He reset t=
he controller and gen manually started","ferot.nongni-djiogap@sagemcom.com"=
,"253","01-03-2025 16:34:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004466142","M=
imboman-Village","","01-03-2025 16:34:12","01-03-2025 16:31:02","01-03-2025=
 18:15:29","Grid outage, site went down because gen failed to start due to =
Pwc ZTE dysfunction// he reset it and  started Gen manualy","Mba Lazare Her=
ve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded",=
"Grid outage, site went down because gen failed to start due to Pwc ZTE dys=
function// he reset it and  started Gen manualy","cedric.tiani@sagemcom.com=
","191","01-03-2025 16:34:12","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004466136","Nko=
abang2","","01-03-2025 16:32:18","01-03-2025 16:26:06","01-03-2025 17:04:39=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // He reduced the load and gen manually started","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, site went down due to gen overload (22KVA, 330A), SS Blaise IHS is i=
nformed // He reduced the load and gen manually started","ferot.nongni-djio=
gap@sagemcom.com","395","01-03-2025 16:32:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004466129","O=
mnisport-Rail","","01-03-2025 16:31:17","01-03-2025 16:24:04","01-03-2025 1=
7:02:58","Site went down due to 02/06 rectifiers burned, Bernard Atangana i=
s informed  // He withdrawn 02 rectifiers, site on grid with 04 rectifiers"=
,"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to 02/06 rectifiers burned, Bernard Atangana is info=
rmed  // He withdrawn 02 rectifiers, site on grid with 04 rectifiers","cedr=
ic.tiani@sagemcom.com","434","01-03-2025 16:31:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004466113","B=
ATA Mokolo OCM","","01-03-2025 16:29:07","01-03-2025 15:35:51","01-03-2025 =
19:12:59","Grid outage, no space to deploy a mobile gen // Grid return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage, no space to deploy a mobile gen // Grid return","cedric.tiani@sagemco=
m.com","3196","01-03-2025 16:29:07","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0004466112","Mba=
nkolo petit paris","","01-03-2025 16:29:04","01-03-2025 16:23:35","01-03-20=
25 16:26:24","Active: no power issue, site is on grid with Ubaie=3D54V, Moh=
amadou((691144435) from Huawie is informed,","Mboua Thierry","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active: no power issue, site=
 is on grid with Ubaie=3D54V, Mohamadou((691144435) from Huawie is informed=
, site impacted by rain","ferot.nongni-djiogap@sagemcom.com","279395","01-0=
3-2025 16:29:04","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004466085","Ngo=
usso Vallee","","01-03-2025 16:26:07","01-03-2025 16:01:38","01-03-2025 16:=
53:58","Grid outage, site went down because gen start and stoppen with alar=
m low oil pressure // He reset gen card and gen manually started","Siligap =
Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage, site went down because gen start and stoppen with alarm low oil pr=
essure // He reset gen card and gen manually started","ferot.nongni-djiogap=
@sagemcom.com","1470","01-03-2025 16:26:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004466066","B=
arriere","","01-03-2025 16:25:28","01-03-2025 16:21:15","01-03-2025 19:20:3=
9","Grid outage, Site went because Gen started and stopped due Gen Overload=
 (20KVA, 450A) SS IHS Felix Zambe confirmed// Grid power return","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge, Site went because Gen started and stopped due Gen Overload (20KVA, 450A=
) SS IHS Felix Zambe confirmed// Grid power return","cedric.tiani@sagemcom.=
com","254","01-03-2025 16:25:28","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004466061","Mes=
sa Carriere","","01-03-2025 16:24:55","01-03-2025 16:19:45","01-03-2025 17:=
05:00","Grid outage, site went down because gen failed to start due to gen =
card faulty // Grid return","Mboua Thierry","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage, site went down because gen fa=
iled to start due to gen card faulty // Grid return","ferot.nongni-djiogap@=
sagemcom.com","311","01-03-2025 16:24:55","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004466057","Nko=
ulou Carriere carrefourt","","01-03-2025 16:24:14","01-03-2025 16:06:16","0=
1-03-2025 19:02:04","Grid outage, site went down because gen failed to star=
t due to PWC malfunction // Grid return","Mba Lazare Herve","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n because gen failed to start due to PWC malfunction // Grid return","ferot=
.nongni-djiogap@sagemcom.com","9221","01-03-2025 16:24:14","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004466050","AWA=
E OCM","","01-03-2025 16:22:48","01-03-2025 16:14:38","01-03-2025 16:26:21"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automatically","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automatically","ferot.nongni-dji=
ogap@sagemcom.com","8485","01-03-2025 16:22:48","Sagemcom CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004466000","NTE=
MASSI","","01-03-2025 16:15:54","01-03-2025 16:10:48","01-03-2025 16:52:06"=
,"Grid outage, site went down because gen failed to start du to Gen card fa=
ulty // Grid return","Delor Telezing","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage, site went down because gen failed t=
o start du to Gen card faulty // Grid return","ferot.nongni-djiogap@sagemco=
m.com","307","01-03-2025 16:15:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004465999","A=
wae Escalier","","01-03-2025 16:15:45","01-03-2025 16:14:16","01-03-2025 16=
:16:37","Grid outage, Site went down before Gen start due to poor backup// =
Gen started automatically","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen started automatically","cedric.tiani=
@sagemcom.com","90","01-03-2025 16:15:45","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004465992","Mim=
boman4","","01-03-2025 16:13:59","01-03-2025 16:06:16","01-03-2025 16:14:47=
","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, site went down because gen failed to start due to=
 PWC malfunction // Grid return","ferot.nongni-djiogap@sagemcom.com","28061=
9","01-03-2025 16:13:59","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004465991","Nko=
lo II New","IHS_YND_266","01-03-2025 16:13:23","01-03-2025 16:06:16","01-03=
-2025 16:14:47","Grid outage, site went down because gen failed to start du=
e to PWC malfunction // Grid return","Mba Lazare Herve","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site went=
 down because gen failed to start due to PWC malfunction // Grid return","f=
erot.nongni-djiogap@sagemcom.com","428","01-03-2025 16:13:23","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004465986","N=
kolondom","","01-03-2025 16:12:50","01-03-2025 16:03:39","01-03-2025 17:12:=
05","Site went down because gen failed to start due to grid bad voltage // =
Grid return","Fabrice Pouakam","Grid Supply","Passive","Grid","National Gri=
d - Phase Controller Faulty","Site went down because gen failed to start du=
e to grid bad voltage // Grid return","cedric.tiani@sagemcom.com","553","01=
-03-2025 16:12:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0004465936","C=
rf Cornier","","01-03-2025 16:09:10","01-03-2025 16:07:59","01-03-2025 16:5=
7:51","Active, No power issue site on battery with U=3D54VTX FME Armand Nge=
stsa (691144412)From huawei is informed","MINKA NICOLAS","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
, No power issue site on battery with U=3D54VTX FME Armand Ngestsa (6911444=
12)From huawei is informed","cedric.tiani@sagemcom.com","72","01-03-2025 16=
:09:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004465923","S=
atcom","","01-03-2025 16:07:44","01-03-2025 15:52:55","01-03-2025 16:00:30"=
,"Active // No power issue site on Grid with U=3D53,02 V Tx Fme Armand Nges=
tsa (691144412) of huawei is informed ","Delor Telezing","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue site on Grid with U=3D53,02 V Tx Fme Armand Ngestsa (691=
144412) of huawei is informed ","cedric.tiani@sagemcom.com","890","01-03-20=
25 16:07:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004465911","E=
leveur","","01-03-2025 16:05:41","01-03-2025 16:01:00","01-03-2025 16:08:37=
","GrGrid outage, site went down because gen start but did not debit // Gri=
d return (Investigation ongoing)","Siligap Boris","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because =
gen start but did not debit // Grid return (Investigation ongoing)","wilfri=
ed.kameni@sagemcom.com","282","01-03-2025 16:05:41","Sagemcom CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0004465850","Aba=
ttoir","","01-03-2025 15:58:38","01-03-2025 15:44:21","01-03-2025 15:50:05"=
,"No power issue site on grid with U=3D54v Symphorien(691316854) from Huawe=
i is informed, site up at 03:56 PM","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue site on grid with U=3D54v Symphorien(691316854) from Huawei is inform=
ed, site up at 03:56 PM","cedric.tiani@sagemcom.com","15835","01-03-2025 15=
:58:38","Sagemcom CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0004465762","Ema=
na Lycee","","01-03-2025 15:51:42","01-03-2025 15:44:21","01-03-2025 15:50:=
05","No power issue site on grid with U=3D54v Symphorien(691316854) from Hu=
awei is informed, site up at 03:56 PM, ","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue site on grid with U=3D54v Symphorien(691316854) from Huawei is i=
nformed, site up at 03:56 PM","cedric.tiani@sagemcom.com","442","01-03-2025=
 15:51:42","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004465759","NYO=
M FACE MAETUR","","01-03-2025 15:50:43","01-03-2025 15:45:27","01-03-2025 1=
7:05:17","Grid outage, site went down because Gen failed to start due to Ge=
n card and solenoid faulty// Gen manually started","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site=
 went down because Gen failed to start due to Gen card and solenoid faulty/=
/ Gen manually started","cedric.tiani@sagemcom.com","317","01-03-2025 15:50=
:43","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004465752","Nko=
lbong","","01-03-2025 15:49:52","01-03-2025 15:46:34","01-03-2025 18:00:57"=
,"Grid outage, site went down because gen failed to start due to gen card m=
alfunction // He reset gen card and gen manually started","Delor Telezing",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
, site went down because gen failed to start due to gen card malfunction //=
 He reset gen card and gen manually started","cedric.tiani@sagemcom.com","1=
99","01-03-2025 15:49:52","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004465735","Pha=
rmacie SION","","01-03-2025 15:48:54","01-03-2025 15:45:33","01-03-2025 15:=
57:45","Grid outage, Site went down before Gen start due to poor backup/ //=
 Gen automatically started","Paul BIBOUM","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup/ // Gen automatically started","cedric.tian=
i@sagemcom.com","202","01-03-2025 15:48:54","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004465734","Ema=
na","","01-03-2025 15:48:09","01-03-2025 16:06:58","01-03-2025 16:16:56","G=
rid outage, site went down before gen start due to poor battery backup // G=
en started automatically","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","ce=
dric.tiani@sagemcom.com","4385","01-03-2025 15:48:09","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004465661","Ebo=
go","","01-03-2025 15:36:02","01-03-2025 15:33:36","01-03-2025 15:35:12","G=
rid outage, Site went down before Gen start due to poor backup// Grid retur=
n","Siligap Boris","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Battery Low","Grid outage, Site went down before Gen start due to poo=
r backup// Grid return","cedric.tiani@sagemcom.com","147","01-03-2025 15:36=
:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004465659","S=
OA UNIVERSITY STADIUM","","01-03-2025 15:35:04","01-03-2025 15:33:18","01-0=
3-2025 15:35:12","No power issue, site is on grid with Ubaie=3D53V, TX FME =
Julien(693095849) from Huawei is informed","Siligap Boris","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue, site is on grid with Ubaie=3D53V, TX FME Julien(693095849) from=
 Huawei is informed","cedric.tiani@sagemcom.com","107","01-03-2025 15:35:04=
","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004465610","Elo=
umdem stade","","01-03-2025 15:27:14","01-03-2025 15:25:03","01-03-2025 15:=
27:38","Grid outage, Site went down before Gen start due to poor backup// G=
en started automatically","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automatically","ferot.nongni-dj=
iogap@sagemcom.com","132","01-03-2025 15:27:14","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004465317","Aha=
la Echangeur","","01-03-2025 14:44:27","01-03-2025 14:42:17","01-03-2025 14=
:44:23"," Site went down due to insufficiency of rectifier // He reduced th=
e load , site on grid","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module"," Site went down due to insufficiency of rectifier =
// He reduced the load , site on grid","ferot.nongni-djiogap@sagemcom.com",=
"131","01-03-2025 14:44:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004465315","M=
ontee-Des-Soeurs","","01-03-2025 14:43:35","01-03-2025 14:37:23","01-03-202=
5 14:40:48","Active: no power issue, site is on grid with Ubaie=3D53V, TX F=
me Hosiah / 674007438// from huawei is informed and up at 02:46 PM","Hyemaf=
o Gildas","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active: no power issue, site is on grid with Ubaie=3D=
53V, TX Fme Hosiah / 674007438// from huawei is informed and up at 02:46 PM=
","cedric.tiani@sagemcom.com","373","01-03-2025 14:43:35","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004465302","Mel=
en Ba'aba","","01-03-2025 14:42:07","01-03-2025 14:39:50","01-03-2025 14:45=
:37","No power issue, site is on grid wit Ubaie=3D53V, Julien(693095849) fr=
om Huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site is =
on grid wit Ubaie=3D53V, Julien(693095849) from Huawei is informed","cedric=
.tiani@sagemcom.com","138","01-03-2025 14:42:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004464962","B=
iteng-Maetur","","01-03-2025 13:57:43","01-03-2025 13:55:36","01-03-2025 21=
:26:23","	Grid outage, Site went down because Gen started and stopped due t=
o Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// he Reduice th=
e Load and Manually Started the Gen","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","	Grid outage, Site went down becaus=
e Gen started and stopped due to Gen overload(20kva, 280A) SS IHS Alphonse =
DEFFO confirmed// he Reduice the Load and Manually Started the Gen","yves.d=
jomo@sagemcom.com","129","01-03-2025 13:57:43","Sagemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004464849","Nko=
abang entree carriere","","01-03-2025 13:55:05","01-03-2025 13:53:42","01-0=
3-2025 14:52:30","Grid outage, site went down because gen failed to start d=
ue to gen card faulty // Grid return","Mba Lazare Herve","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down b=
ecause gen failed to start due to gen card faulty // Grid return","wilfried=
.kameni@sagemcom.com","83","01-03-2025 13:55:05","Sagemcom CMR"
"Closed Complete","Site Down","T0836","IHS_YND_109","NOCINC0004464382","Mob=
il-Essos","","01-03-2025 13:08:36","01-03-2025 13:00:25","01-03-2025 13:10:=
27","Active// No power issue on site U=3D53,6V site on Grid The FME TX Char=
ly Donald (656097386) of ste telise WORKING ON SITE","Siligap Boris","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue on site U=3D53,6V site on Grid The FME TX Cha=
rly Donald (656097386) of ste telise WORKING ON SITE","wilfried.kameni@sage=
mcom.com","492","01-03-2025 13:08:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004464069","M=
essassi 2","","01-03-2025 12:12:01","01-03-2025 11:34:54","01-03-2025 12:54=
:20","Site went down because PWC overload (12 kilo, 300A) , SS IHS Bernard =
ATANGANA confirmed// He reset the rectifier","Fabrice Pouakam","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Site went down =
because PWC overload (12 kilo, 300A) , SS IHS Bernard ATANGANA confirmed// =
He reset the rectifier","yves.djomo@sagemcom.com","2229","01-03-2025 12:12:=
01","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004464055","Aha=
la Echangeur","","01-03-2025 12:09:07","01-03-2025 11:59:55","01-03-2025 13=
:16:57","Grid outage ,site went down because Gen failed to started due to G=
en contactor Faulty // He bypass the Gen contactor and Gen manually started=
","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Load Cont=
actor","Grid outage ,site went down because Gen failed to started due to Ge=
n contactor Faulty // He bypass the Gen contactor and Gen manually started"=
,"wilfried.kameni@sagemcom.com","552","01-03-2025 12:09:07","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004463920","OBA=
M NGOLA OCM","","01-03-2025 11:43:10","01-03-2025 11:37:58","01-03-2025 18:=
37:34","Acces Issue due to landlord(  Site went down due to PSC3 Controller=
 dysfunctionning// He reset it)","MINKA NICOLAS","Access Denial","Lease Or =
Legal","Landlord Related Issues","Access Issue - Land Lord","Acces Issue du=
e to landlord(  Site went down due to PSC3 Controller dysfunctionning// He =
reset it)","wilfried.kameni@sagemcom.com","313","01-03-2025 11:43:10","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004463870","Dong",""=
,"01-03-2025 11:35:01","01-03-2025 10:25:16","01-03-2025 10:30:40","Cascade=
d Incident from TTO4516309","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue  with U=3D49.1V //site=
 on Battery Site down because is impacted by Mbandjock and not managing by =
IHS
","system","4185","01-03-2025 11:35:01","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004463756","Mel=
en Ba'aba","","01-03-2025 11:14:27","01-03-2025 11:07:19","01-03-2025 11:22=
:00","Grid fluctuation, Site went down because gen start and stopped due to=
 grid bad voltage and RCP o,n site  // Grid power return","Siligap Boris","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, Site went down because gen start and stopped due to grid ba=
d voltage and RCP o,n site  // Grid power return","wilfried.kameni@sagemcom=
.com","430","01-03-2025 11:14:27","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004463624","CRH=
-Etoug-Ebe","","01-03-2025 10:41:45","01-03-2025 10:38:32","01-03-2025 10:5=
4:55","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen automatically started","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen automatically start=
ed","wilfried.kameni@sagemcom.com","194","01-03-2025 10:41:45","Sagemcom CM=
R"
"Closed Complete","Site Down","T1107-1","IHS_YND_217","NOCINC0004463611","A=
bom","","01-03-2025 10:38:11","01-03-2025 10:30:26","01-03-2025 10:40:25","=
Active// No power issue on site U=3D53,6V site on Grid The FME TX Augustin(=
691720864) of e-engenenig WORKING ON SITE ","Siligap Boris","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive// No power issue on site U=3D53,6V site on Grid The FME TX Augustin(691=
720864) of e-engenenig WORKING ON SITE ","wilfried.kameni@sagemcom.com","46=
6","01-03-2025 10:38:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0004463564","D=
onga","IHS_YND_444","01-03-2025 10:29:25","01-03-2025 10:25:16","01-03-2025=
 12:10:40","Active//No power issue  with U=3D49.1V //site on Battery  Site =
down because is impacted by Mbandjock and not managing by IHS","Parker Tcho=
up","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue  with U=3D49.1V //site on Battery Si=
te down because is impacted by Mbandjock and not managing by IHS
","yves.djomo@sagemcom.com","250","01-03-2025 10:29:25","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004463244","Aha=
la Echangeur","","01-03-2025 09:32:13","01-03-2025 08:45:56","01-03-2025 10=
:05:24","Grid outage ,site went down because Gen failed to started due to G=
en contactor Faulty // He bypass the Gen contactor and Gen manually started=
","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Load Cont=
actor","Grid outage ,site went down because Gen failed to started due to Ge=
n contactor Faulty // He bypass the Gen contactor and Gen manually started"=
,"wilfried.kameni@sagemcom.com","2778","01-03-2025 09:32:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004463145","B=
ATA Mokolo OCM","","01-03-2025 09:18:12","01-03-2025 09:09:47","01-03-2025 =
09:55:09","Grid outage No space to deploy // Grid power return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No =
space to deploy // Grid power return","wilfried.kameni@sagemcom.com","506",=
"01-03-2025 09:18:12","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004463031","Eto=
 koss Yde","","01-03-2025 08:55:49","01-03-2025 08:50:51","01-03-2025 09:10=
:58","Site went down because Gen failed to start due to Relay (220V) ATS fa=
ulty // he replaced the Relay and Gen manually started","Fanda Brice","Equi=
pment Repair","Passive","Control Panel","ATS Relay Faulty","Site went down =
because Gen failed to start due to Relay (220V) ATS faulty // he replaced t=
he Relay and Gen manually started","wilfried.kameni@sagemcom.com","300","01=
-03-2025 08:55:49","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004462868","Men=
dong3","","01-03-2025 08:15:19","01-03-2025 08:09:22","01-03-2025 09:08:47"=
,"Grid outage no space to deploy mobile gen.//Grid retun","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space =
to deploy mobile gen.//Grid retun","wilfried.kameni@sagemcom.com","358","01=
-03-2025 08:15:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004462626","M=
efou-Assi","","01-03-2025 07:25:46","01-03-2025 07:21:39","01-03-2025 07:24=
:18","ACTIVE//No power issue on site GRID , Ubaie=3D54.3V site On Grid The =
Tx FME Fulbert(654266068) from Huawei is informed. Repetitive issue","Fanda=
 Brice","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D54.3V sit=
e On Grid The Tx FME Fulbert(654266068) from Huawei is informed. Repetitive=
 issue","yves.djomo@sagemcom.com","248","01-03-2025 07:25:46","Sagemcom CMR=
"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004462471","Elo=
umdem stade","","01-03-2025 06:53:34","01-03-2025 06:52:25","01-03-2025 06:=
54:40","Grid outage, Site went down before Gen start due to poor backup// G=
en started automatically","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automatically","wilfried.kameni=
@sagemcom.com","70","01-03-2025 06:53:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004462450","B=
arriere","","01-03-2025 06:48:28","01-03-2025 06:44:15","01-03-2025 09:51:1=
9","Grid outage, Site went because Gen started and stopped due Gen Overload=
 (20KVA, 450A) SS IHS Felix Zambe confirmed// Grid power return","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge, Site went because Gen started and stopped due Gen Overload (20KVA, 450A=
) SS IHS Felix Zambe confirmed// Grid power return","wilfried.kameni@sagemc=
om.com","254","01-03-2025 06:48:28","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004462180","Crf=
-Nsam","","01-03-2025 05:27:11","01-03-2025 05:25:06","01-03-2025 05:28:29"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline is i=
nformed// He reset it","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Site went down because PWC(24kilo) dysf=
unctionning, IHS SS Pascaline is informed// He reset it","yves.djomo@sagemc=
om.com","126","01-03-2025 05:27:11","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004461830","Mon=
tee-Jouvence-II","","01-03-2025 02:32:43","01-03-2025 02:26:37","01-03-2025=
 02:32:26","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix Za=
mb=E9 confirmed // he reset and  started the Gen manually","Hyemafo Gildas"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Si=
te went down due to PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirme=
d // he reset and  started the Gen manually","yves.djomo@sagemcom.com","367=
","01-03-2025 02:32:43","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004461743","Crf=
-Nsam","","01-03-2025 02:02:44","01-03-2025 02:01:35","01-03-2025 02:48:08"=
,"Site went down Because The Slot off Rectifier is overload // Grid return =
SS Ihs Pascaline is informed and is confirmed","MINKA NICOLAS","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Site went down =
Because The Slot off Rectifier is overload // Grid return SS Ihs Pascaline =
is informed and is confirmed","ludovic-anselme.mouliom-mapoure@sagemcom","7=
0","01-03-2025 02:02:44","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004461709","Men=
dong3","","01-03-2025 01:48:12","01-03-2025 01:44:07","01-03-2025 03:32:39"=
,"Grid outage no space to deploy mobile gen.//Grid retun","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space =
to deploy mobile gen.//Grid retun","yves.djomo@sagemcom.com","245","01-03-2=
025 01:48:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004461597","N=
gouetou","","01-03-2025 00:58:41","01-03-2025 00:50:35","01-03-2025 00:55:4=
1","ACTIVE//No power issue site on gen with U=3D54V The Tx FME Gregoire/654=
547479/ from huawei is informed. Notice that we have a fog in Area","Parker=
 Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","ACTIVE//No power issue site on gen with U=3D54V The Tx=
 FME Gregoire/654547479/ from huawei is informed. Notice that we have a fog=
 in Area","yves.djomo@sagemcom.com","487","01-03-2025 00:58:41","Sagemcom C=
MR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0004461587","Bit=
oto","","01-03-2025 00:54:09","01-03-2025 00:48:03","01-03-2025 02:35:37","=
Grid outage site went down because Gen failed to start due PWC ZTE dysfonct=
ion // He reset the PWC, Site on Grid","Mba Lazare Herve","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","Grid outage site wen=
t down because Gen failed to start due PWC ZTE dysfonction // He reset the =
PWC, Site on Grid","yves.djomo@sagemcom.com","368","01-03-2025 00:54:09","S=
agemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004461576","Mon=
tee Jouvence","","01-03-2025 00:48:35","01-03-2025 00:45:28","01-03-2025 01=
:59:02","Site was on Gen due to Grid outage, site went down because gen sto=
pped with alarm ""high temp"" // He added water and manually start the Gen"=
,"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engi=
ne Temp - Coolant Level Issue","Site was on Gen due to Grid outage, site we=
nt down because gen stopped with alarm ""high temp"" // He added water and =
manually start the Gen","yves.djomo@sagemcom.com","188","01-03-2025 00:48:3=
5","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004461475","B=
ATA Mokolo OCM","","01-03-2025 00:04:14","01-03-2025 00:01:09","01-03-2025 =
00:24:32","Grid outage no space to deploy MDG //Grid return ","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy MDG //Grid return ","yves.djomo@sagemcom.com","186","01-03-20=
25 00:04:14","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004461459","Elo=
umdem stade","","28-02-2025 23:57:34","28-02-2025 23:54:10","01-03-2025 00:=
09:40","Grid fluctuation, Site went down because gen start and stopped due =
to grid bad voltage // He bypass grid and manually start the gen","Fanda Br=
ice","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, Site went down because gen start and stopped due to g=
rid bad voltage // He bypass grid and manually start the gen","ludovic-anse=
lme.mouliom-mapoure@sagemcom","205","28-02-2025 23:57:34","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004461444","Bar=
riere","","28-02-2025 23:54:55","28-02-2025 23:49:37","01-03-2025 02:32:46"=
,"Grid outage, Site went because Gen started and stopped due Gen Overload (=
20KVA, 450A) SS IHS Felix Zambe confirmed// Gen manualy started","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge, Site went because Gen started and stopped due Gen Overload (20KVA, 450A=
) SS IHS Felix Zambe confirmed// Gen manualy started","ludovic-anselme.moul=
iom-mapoure@sagemcom","364","28-02-2025 23:54:55","Sagemcom CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0004461398","Kon=
dengui MTN","","28-02-2025 23:46:12","28-02-2025 23:44:03","01-03-2025 00:0=
6:18","Grid fluctuation, site went down because Gen failed to start due to =
lack of 02 phase // He did a bridge on the good phase","Albran Byorel","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation, site went down because Gen failed to start due to lack of 02 p=
hase // He did a bridge on the good phase","ludovic-anselme.mouliom-mapoure=
@sagemcom","130","28-02-2025 23:46:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004461245","S=
hell-Nsimeyong","","28-02-2025 23:04:27","28-02-2025 22:59:16","28-02-2025 =
23:05:55","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed. Repetitive Issue","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U =3D52.1V site on Grid.The =
FME TX Mbah Hosiah (674007438/699699694) from Huawei is informed. Repetitiv=
e Issue","yves.djomo@sagemcom.com","312","28-02-2025 23:04:27","Sagemcom CM=
R"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004461087","Sof=
avinc","","28-02-2025 22:28:11","28-02-2025 22:23:54","28-02-2025 23:58:24"=
,"Grid fluctuation, site went down because Gen failed to start due to lack =
of 01 phase and No RCP // He did a bridge on the good phase","MINKA NICOLAS=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation, site went down because Gen failed to start due to lack o=
f 01 phase and No RCP // He did a bridge on the good phase","ludovic-anselm=
e.mouliom-mapoure@sagemcom","258","28-02-2025 22:28:11","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004461061","Aha=
la","","28-02-2025 22:17:34","28-02-2025 22:09:10","28-02-2025 22:17:38","S=
ite went down because 04/08 rectifiers dysfunctionned // He reset it: and S=
ite on grid","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down because 04/08 rectifiers dysfunctionned // H=
e reset it: and Site on grid","el-dalile@sagemcom.com","505","28-02-2025 22=
:17:34","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004461008","Nko=
lmvack","","28-02-2025 22:04:02","28-02-2025 21:56:53","28-02-2025 22:22:19=
","hybrid gen site .gen failed to start due to alarm ""high temp"" causing =
by  radiator pierced// We add water and gen manually started ","Parker Tcho=
up","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator Leakage","hybr=
id gen site .gen failed to start due to alarm ""high temp"" causing by  rad=
iator pierced// We add water and gen manually started ","el-dalile@sagemcom=
.com","430","28-02-2025 22:04:02","Sagemcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004460981","Tam=
tam Weekend","","28-02-2025 21:52:46","28-02-2025 21:46:28","28-02-2025 22:=
41:38","Site went down due to CB (63A) Disjunted in the DC-Box because the =
Load Increase //He reamed the CB(63A)","Hyemafo Gildas","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site wen=
t down due to CB (63A) Disjunted in the DC-Box because the Load Increase //=
He reamed the CB(63A)","ervine.mbezele@sagemcom.com","378","28-02-2025 21:5=
2:46","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004460957","OBA=
M NGOLA OCM","","28-02-2025 21:49:00","28-02-2025 21:43:32","28-02-2025 22:=
16:22","Site went down due to PSC3 dysfonctionned SS IHS Pascaline confirme=
d// He Reset it and Site is on Grid","MINKA NICOLAS","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Site went down due to PSC3 dysfon=
ctionned SS IHS Pascaline confirmed// He Reset it and Site is on Grid","erv=
ine.mbezele@sagemcom.com","329","28-02-2025 21:49:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004460651","M=
efou-Assi","","28-02-2025 20:46:09","28-02-2025 20:44:56","28-02-2025 20:50=
:38","ACTIVE//No power issue on site GRID , Ubaie=3D53.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed. Repetitive issue","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D53.V site =
On Grid The Tx FME Fulbert(654266068) from Huawei is informed. Repetitive i=
ssue","cedric.tiani@sagemcom.com","74","28-02-2025 20:46:09","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004460642","Mel=
en Ba'aba","","28-02-2025 20:43:59","28-02-2025 20:41:51","28-02-2025 21:15=
:51","Grid bad voltage, Site went down because Main GEN  faulty (15 KVA) HI=
S SS Alphonse Deffo confirmed// He replaced it by another Main Gen (20KVA) =
","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Generator=
 Faulty","Grid bad voltage, Site went down because Main GEN  faulty (15 KVA=
) HIS SS Alphonse Deffo confirmed// He replaced it by another Main Gen (20K=
VA) ","el-dalile@sagemcom.com","129","28-02-2025 20:43:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004460572","O=
mnisport-Rail","","28-02-2025 20:29:01","28-02-2025 20:24:46","28-02-2025 2=
1:17:08","Site went down because CB(125A) tripped in PWC who feeds equipmen=
ts OCM due to load increase// CB put back on","Delor Telezing","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","S=
ite went down because CB(125A) tripped in PWC who feeds equipments OCM due =
to load increase// CB put back on","cedric.tiani@sagemcom.com","257","28-02=
-2025 20:29:01","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004460416","Lad=
a I Yde","","28-02-2025 19:59:52","28-02-2025 19:52:35","28-02-2025 22:55:2=
5","Active// No power issue, site is on Grid with Ubaie=3D50,2V, Lionel Adj=
ep(655184876) from Huawei is informed","Mba Lazare Herve","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue, site is on Grid with Ubaie=3D50,2V, Lionel Adjep(655184=
876) from Huawei is informed","cedric.tiani@sagemcom.com","438","28-02-2025=
 19:59:52","Sagemcom CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004460374","Sof=
avinc","","28-02-2025 19:53:27","28-02-2025 19:49:06","28-02-2025 19:55:41"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automatically","MINKA NICOLAS","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup// Gen started automatically","el-dalile@sagemcom.=
com","262","28-02-2025 19:53:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004460371","c=
hina embassy yde","","28-02-2025 19:52:24","28-02-2025 19:47:07","03-03-202=
5 14:21:11","The landlord stopped Eneo Meter because Awaiting normalisation=
 from IHS Bernard ATANGANA confirmed//Still down(still waiting Normalisatio=
n)//Eneo Normalized the Issues","","Access Denial","Lease Or Legal","Landlo=
rd Related Issues","Access Issue - Land Lord","The landlord stopped Eneo Me=
ter because Awaiting normalisation from IHS Bernard ATANGANA confirmed//Sti=
ll down(still waiting Normalisation)//Eneo Normalized the Issues","cedric.t=
iani@sagemcom.com","318","28-02-2025 19:52:24","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004460329","OBA=
M NGOLA OCM","","28-02-2025 19:42:46","28-02-2025 19:39:36","28-02-2025 20:=
57:04","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 He Reset it and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Site went down due to PSC3 dysfoncti=
on SS IHS Pascaline confirmed// He Reset it and Site is on Grid","el-dalile=
@sagemcom.com","191","28-02-2025 19:42:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004460319","N=
kolda","","28-02-2025 19:40:29","28-02-2025 19:38:15","28-02-2025 19:40:05"=
,"Grid fluctuation, site went down because Gen fails to start due to Grid b=
ad voltage  // Grid stabilised","Albran Byorel","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","Grid fluctuation, site went =
down because Gen fails to start due to Grid bad voltage  // Grid stabilised=
","cedric.tiani@sagemcom.com","135","28-02-2025 19:40:29","Sagemcom CMR"
"Closed Complete","Site Down","T1850","IHS_YND_376","NOCINC0004460060","Mam=
b","","28-02-2025 19:06:49","28-02-2025 18:58:36","28-02-2025 19:41:35","Gr=
id outage.site went due do Gen CB(63 A) down   //We rearmed the CB and site=
 on gen (investigation ongoing)","Kemeni Franklin","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Load Breaker","Grid outage.site went due do Gen CB(=
63 A) down   //We rearmed the CB and site on gen (investigation ongoing)","=
el-dalile@sagemcom.com","494","28-02-2025 19:06:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004459973","S=
hell-Nsimeyong","","28-02-2025 18:46:33","28-02-2025 18:43:21","28-02-2025 =
19:51:33","	no power issue U =3D52.1V site on Grid.The FME TX Mbah Hosiah (=
674007438/699699694) from Huawei is informed","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	=
no power issue U =3D52.1V site on Grid.The FME TX Mbah Hosiah (674007438/69=
9699694) from Huawei is informed","cedric.tiani@sagemcom.com","193","28-02-=
2025 18:46:33","Sagemcom CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004459967","Sof=
avinc","","28-02-2025 18:45:38","28-02-2025 18:39:21","28-02-2025 18:45:53"=
,"Grid Outage, site went down before gen start due to poor battery backup /=
/ Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid Outage, site went down bef=
ore gen start due to poor battery backup // Gen start automatically","cedri=
c.tiani@sagemcom.com","377","28-02-2025 18:45:38","Sagemcom CMR"
"Closed Complete","Site Down","T2183","IHS_YND_089","NOCINC0004459712","H-P=
rince","","28-02-2025 18:08:46","28-02-2025 17:45:27","28-02-2025 20:40:56"=
,"Active//No power issue on site, site on Grid  with U=3D54,9 V The TX FME =
Brice/650214096 from huawei is informed.","Mboua Thierry","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site, site on Grid  with U=3D54,9 V The TX FME Brice/6=
50214096 from huawei is informed.","el-dalile@sagemcom.com","1400","28-02-2=
025 18:08:46","Sagemcom CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0004459597","Saa=
","","28-02-2025 17:48:30","28-02-2025 17:28:08","28-02-2025 21:31:10","Act=
ive//No power issue U =3D53.1V site on Grid. The Team Aubain (694427963) fr=
om Huawei is working on Site( Microwave-Installation).","Parker Tchoup","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue U =3D53.1V site on Grid. The Team Aubain (6=
94427963) from Huawei is working on Site( Microwave-Installation).","cedric=
.tiani@sagemcom.com","1223","28-02-2025 17:48:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004459340","M=
essassi 2","","28-02-2025 17:10:20","28-02-2025 17:08:11","28-02-2025 18:52=
:34","Site went down because PWC overload (12 kilo, 300A) , SS IHS Bernard =
ATANGANA confirmed// He reset it","Fabrice Pouakam","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Site went down because PWC=
 overload (12 kilo, 300A) , SS IHS Bernard ATANGANA confirmed// He reset it=
","el-dalile@sagemcom.com","131","28-02-2025 17:10:20","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004459195","OBA=
M NGOLA OCM","","28-02-2025 16:45:35","28-02-2025 16:37:26","28-02-2025 18:=
55:35","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 He Reset it and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due to PSC3 d=
ysfonction SS IHS Pascaline confirmed// He Reset it and Site is on Grid","e=
l-dalile@sagemcom.com","490","28-02-2025 16:45:35","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004458933","Man=
guiers Dispensaire","","28-02-2025 16:10:10","28-02-2025 16:01:58","28-02-2=
025 20:18:02","Active//No power issue, site is on Grid with Ubaie=3D55V The=
 Tx FME Armand Nguetsa / 691144412/ from Huawei is informed","Fabrice Pouak=
am","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue, site is on Grid with Ubaie=3D55V Th=
e Tx FME Armand Nguetsa / 691144412/ from Huawei is informed","el-dalile@sa=
gemcom.com","493","28-02-2025 16:10:10","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004458892","Nko=
g-Edzen","","28-02-2025 16:05:01","28-02-2025 16:00:33","28-02-2025 21:33:1=
3","No power issue site on Gen. The Tx Fme Gregoire (654547479) from Huawei=
 informed ","Parker Tchoup","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on Gen. The Tx =
Fme Gregoire (654547479) from Huawei informed ","cedric.tiani@sagemcom.com"=
,"269","28-02-2025 16:05:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0004458891","E=
toudi 2","","28-02-2025 16:04:45","28-02-2025 15:50:32","28-02-2025 21:00:5=
0","Active//No power issue, site is on Grid with Ubaie=3D53,7V The Tx FME A=
rmand Nguetsa / 691144412/ from Huawei is informed","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue, site is on Grid with Ubaie=3D53,7V The Tx FM=
E Armand Nguetsa / 691144412/ from Huawei is informed","wilfried.kameni@sag=
emcom.com","854","28-02-2025 16:04:45","Sagemcom CMR"
"Closed Complete","Site Down","T2292","IHS_YND_453","NOCINC0004458881","Son=
g-bong","","28-02-2025 16:02:09","28-02-2025 15:58:09","28-02-2025 16:57:54=
",".site went down due to PSC3 Controller dysfunctionning // He Reset it an=
d Site is on Gen","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel",".site went down due to PSC3 Controller dysfunction=
ning // He Reset it and Site is on Gen","cedric.tiani@sagemcom.com","241","=
28-02-2025 16:02:09","Sagemcom CMR"
"Closed Complete","Site Down","T0526","IHS_YND_088","NOCINC0004458861","Elo=
bi Mokolo","","28-02-2025 15:57:26","28-02-2025 15:52:38","28-02-2025 20:15=
:43","Active//No power issue on site, site on Grid  with U=3D52,9 V The TX =
FME Brice/650214096// from huawei is informed.","Mboua Thierry","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site, site on Grid  with U=3D52,9 V The TX FME B=
rice/650214096// from huawei is informed.","cedric.tiani@sagemcom.com","289=
","28-02-2025 15:57:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0004458804","N=
kolkoumou OCM","","28-02-2025 15:45:43","28-02-2025 15:37:26","28-02-2025 2=
0:14:00","No power issue on site ,site on Grid with Ubaie=3D54,5 V The Tx F=
ME Mouahamadou  (691144435) of Huawei is informed  UPTIME 15:59 PM","TIENTC=
HEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue on site ,site on Grid with U=
baie=3D54,5 V The Tx FME Mouahamadou  (691144435) of Huawei is informed  UP=
TIME 15:59 PM","cedric.tiani@sagemcom.com","498","28-02-2025 15:45:43","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004458578","M=
ini-Ferme","","28-02-2025 15:21:50","28-02-2025 13:32:25","28-02-2025 13:40=
:32","back tracking  Actives, no power issue on site, Ubaie=3D55.7V TheTX F=
ME Mohamadou(691144435) from hauwei is informed","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Actives, no=
 power issue on site, Ubaie=3D55.7V TheTX FME Mohamadou(691144435) from hau=
wei is informed","cedric.tiani@sagemcom.com","6566","28-02-2025 15:21:50","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004458512","Scalom-I=
HS","","28-02-2025 15:13:40","28-02-2025 15:03:44","28-02-2025 15:39:00","C=
ascaded Incident from TTO4510400","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid Outage//Grid Restored","system","1219460","2=
8-02-2025 15:13:40","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004458461","Acc=
acia New","IHS_YND_505","28-02-2025 15:05:56","28-02-2025 15:03:44","28-02-=
2025 15:39:00","Grid Outage//Grid Restored","","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue","Grid Outage//Grid Restored","wilfri=
ed.kameni@sagemcom.com","134","28-02-2025 15:05:56","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004458335","Com=
plex Beac II","","28-02-2025 14:57:48","28-02-2025 14:54:25","28-02-2025 15=
:12:18","	Grid outage site went down because Gen failed to start due to Gen=
 card dysfonction // He reset the Gen card and Gen manually started","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","	=
Grid outage site went down because Gen failed to start due to Gen card dysf=
onction // He reset the Gen card and Gen manually started","wilfried.kameni=
@sagemcom.com","204","28-02-2025 14:57:48","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004458191","Aha=
la Echangeur","","28-02-2025 14:48:48","28-02-2025 14:46:36","28-02-2025 15=
:58:27","Site went down due to insufficience of rectifiers SS IHS Pascaline=
 MANDA is informed (01 )// The Load Reduice and site UP","MINKA NICOLAS","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went down d=
ue to insufficience of rectifiers SS IHS Pascaline MANDA is informed (01 )/=
/ The Load Reduice and site UP","el-dalile@sagemcom.com","133","28-02-2025 =
14:48:48","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004458155","Mel=
en Ba'aba","","28-02-2025 14:47:03","28-02-2025 14:43:47","28-02-2025 19:38=
:07","Grid Outage Site went down due to Main Gen Faulty(SS IHS Alphonse Def=
fo is informed and Confirmed it)//Grid Restored","Siligap Boris","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid Outage Site w=
ent down due to Main Gen Faulty(SS IHS Alphonse Deffo is informed and Confi=
rmed it)//Grid Restored","el-dalile@sagemcom.com","197","28-02-2025 14:47:0=
3","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004458116","T=
singa","","28-02-2025 14:44:59","28-02-2025 14:31:37","28-02-2025 16:04:59"=
,"Site went down due to CB 125 (A) Disjunted because Load increase//he made=
 the Briged with another 80(A)","Mboua Thierry","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down d=
ue to CB 125 (A) Disjunted because Load increase//he made the Briged with a=
nother 80(A)","yves.djomo@sagemcom.com","804","28-02-2025 14:44:59","Sagemc=
om CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004458066","Tam=
tam Weekend","","28-02-2025 14:39:25","28-02-2025 14:38:51","28-02-2025 14:=
58:13","Site went down due to the Gen does not support the load on Site//He=
 reduice the Load and Site is on GEN","Hyemafo Gildas","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Site went down due to the Gen does n=
ot support the load on Site//He reduice the Load and Site is on GEN","ervin=
e.mbezele@sagemcom.com","35","28-02-2025 14:39:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004458060","C=
omplexe-BEAC","","28-02-2025 14:38:12","28-02-2025 14:36:53","28-02-2025 14=
:39:55","Grid Outage  Site went down before Gen start due to poor backup// =
Gen automatically started","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid Outage  Site went down bef=
ore Gen start due to poor backup// Gen automatically started","yves.djomo@s=
agemcom.com","80","28-02-2025 14:38:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0004458012","N=
kolso","","28-02-2025 14:32:31","28-02-2025 14:29:26","28-02-2025 21:35:23"=
,"Active//No power issue on site ,site on Grid with Ubaie=3D53,5 V The Tx F=
ME Mouahamadou (691144435) of Huawei is informed UPTIME 02:33 PM","TIENTCHE=
U NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid =
with Ubaie=3D53,5 V The Tx FME Mouahamadou (691144435) of Huawei is informe=
d UPTIME 02:33 PM","yves.djomo@sagemcom.com","186","28-02-2025 14:32:31","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004457917","Saa","",=
"28-02-2025 14:15:51","28-02-2025 14:07:16","28-02-2025 15:47:40","Cascaded=
 Incident from TTO4509788","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage site went down because Gen Star=
ted and Stop due to ALARMS Over-Current //He Reset the Gen Card and Manuall=
y Started It","system","1229878","28-02-2025 14:15:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004457916","SAA Entr=
ance","","28-02-2025 14:15:51","28-02-2025 14:07:16","28-02-2025 15:47:40",=
"Cascaded Incident from TTO4509788","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen Started and Stop due to ALARMS Over-Current //He Reset the Gen Card an=
d Manually Started It","system","1229878","28-02-2025 14:15:51","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004457915","Carrefou=
r Ayissi Ele","","28-02-2025 14:15:50","28-02-2025 14:07:16","28-02-2025 15=
:47:40","Cascaded Incident from TTO4509788","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage site went down=
 because Gen Started and Stop due to ALARMS Over-Current //He Reset the Gen=
 Card and Manually Started It","system","1229877","28-02-2025 14:15:50","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004457905","SAA=
 2","IHS_YND_810, IHS_YND_542, IHS_YND_405","28-02-2025 14:14:28","28-02-20=
25 14:07:16","28-02-2025 15:47:40","Grid outage site went down because Gen =
Started and Stop due to ALARMS Over-Current //He Reset the Gen Card and Man=
ually Started It","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Grid outage site went down because Gen Started and S=
top due to ALARMS Over-Current //He Reset the Gen Card and Manually Started=
 It","wilfried.kameni@sagemcom.com","433","28-02-2025 14:14:28","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004457790","Minka","=
","28-02-2025 13:54:41","28-02-2025 13:33:43","28-02-2025 14:13:51","Cascad=
ed Incident from TTO4509608","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen sta=
rt and stopped with alarm ""memory corruption"" // he reset  and manually s=
tart the Gen  ","system","1224767","28-02-2025 13:54:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004457789","Mbeng","=
","28-02-2025 13:54:40","28-02-2025 13:33:43","28-02-2025 14:13:51","Cascad=
ed Incident from TTO4509608","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen sta=
rt and stopped with alarm ""memory corruption"" // he reset  and manually s=
tart the Gen  ","system","1224766","28-02-2025 13:54:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_201","IHS_YND_368","NOCINC0004457740","O=
tele","IHS_YND_370, IHS_YND_369, IHS_YND_371, IHS_YND_372","28-02-2025 13:5=
3:02","28-02-2025 13:33:43","28-02-2025 14:13:51","Grid outage, site went d=
own because gen start and stopped with alarm ""memory corruption"" // he re=
set  and manually start the Gen  ","Fanda Brice","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because g=
en start and stopped with alarm ""memory corruption"" // he reset  and manu=
ally start the Gen  ","wilfried.kameni@sagemcom.com","1160","28-02-2025 13:=
53:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0004457691","Nkolbi-B=
oss","","28-02-2025 13:47:51","28-02-2025 13:35:44","28-02-2025 13:37:26","=
Cascaded Incident from TTO4509522","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","Active//No power issue, Sit=
e on Grid Ubai=3D 55,9V The TX Mouhamadou (6144435) from Huawei is informed=
. Notice that it is impacted by Nkolbisson Nodal (not manager by IHS)","sys=
tem","289462","28-02-2025 13:47:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_545","NOCINC0004457692","Nkolbiss=
on usine des eaux","","28-02-2025 13:47:51","28-02-2025 13:35:44","28-02-20=
25 13:37:26","Cascaded Incident from TTO4509522","TIENTCHEU NZETCHIEU GAEL"=
,"Cascade Outage","Active","Cascade Active","Cascade Active","Active//No po=
wer issue, Site on Grid Ubai=3D 55,9V The TX Mouhamadou (6144435) from Huaw=
ei is informed. Notice that it is impacted by Nkolbisson Nodal (not manager=
 by IHS)","system","289462","28-02-2025 13:47:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004457665","N=
kolafeme","IHS_YND_273, IHS_YND_545","28-02-2025 13:45:50","28-02-2025 13:3=
5:44","28-02-2025 13:37:26","Active//No power issue, Site on Grid Ubai=3D 5=
5,9V The TX Mouhamadou (6144435) from Huawei is informed. Notice that it is=
 impacted by Nkolbisson Nodal (not manager by IHS)","TIENTCHEU NZETCHIEU GA=
EL","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 55,9V The TX M=
ouhamadou (6144435) from Huawei is informed. Notice that it is impacted by =
Nkolbisson Nodal (not manager by IHS)","yves.djomo@sagemcom.com","607","28-=
02-2025 13:45:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004457551","Bondjock=
","","28-02-2025 13:23:41","28-02-2025 13:33:43","28-02-2025 14:13:51","Cas=
caded Incident from TTO4509327 - Cascade Removed From TTO4509327","Fanda Br=
ice","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid o=
utage, site went down because gen start and stopped with alarm ""memory cor=
ruption"" // he reset  and manually start the Gen  ","system","1224768","28=
-02-2025 13:23:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004457547","B=
arriere IHS","","28-02-2025 13:23:29","28-02-2025 13:21:18","28-02-2025 13:=
30:32","Site went down due to PWC dysfunctionning IHS Supervisor Felix Zamb=
e is informed//he reset it and site is on Gen ","Hyemafo Gildas","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went dow=
n due to PWC dysfunctionning IHS Supervisor Felix Zambe is informed//he res=
et it and site is on Gen ","yves.djomo@sagemcom.com","132","28-02-2025 13:2=
3:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004457508","M=
om","","28-02-2025 13:20:15","28-02-2025 13:33:43","28-02-2025 14:13:51",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid outage, site went down because gen start and stopped with alarm ""=
memory corruption"" // he reset  and manually start the Gen  ","wilfried.ka=
meni@sagemcom.com","1224767","28-02-2025 13:20:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004457250","TSINGA V=
ILLAGE 2","","28-02-2025 12:36:53","28-02-2025 12:15:10","28-02-2025 13:08:=
00","Cascaded Incident from TTO4508924","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage.gen started and s=
toped due to alarm ""low oil pressure""//He reset card GE and gen manually =
started","system","1303","28-02-2025 12:36:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004457249","Nkolfoul=
ou 2","","28-02-2025 12:36:53","28-02-2025 12:15:10","28-02-2025 13:08:00",=
"Cascaded Incident from TTO4508924","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen started and stoped=
 due to alarm ""low oil pressure""//He reset card GE and gen manually start=
ed","system","1303","28-02-2025 12:36:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004457172","N=
kolfoulou","IHS_YND_278, IHS_YND_719","28-02-2025 12:21:18","28-02-2025 12:=
15:10","28-02-2025 13:13:29","Grid outage.gen started and stoped due to ala=
rm ""low oil pressure""//He reset card GE and gen manually started","Siliga=
p Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage.gen started and stoped due to alarm ""low oil pressure""//He rese=
t card GE and gen manually started","wilfried.kameni@sagemcom.com","369","2=
8-02-2025 12:21:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004457167","S=
hell-Nsimeyong","","28-02-2025 12:20:33","28-02-2025 12:19:26","28-02-2025 =
12:25:30","no power issue U =3D52.1V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no=
 power issue U =3D52.1V site on Grid.The FME TX Mbah Hosiah (674007438/6996=
99694) from Huawei is informed","yves.djomo@sagemcom.com","68","28-02-2025 =
12:20:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0004456789","A=
bome","","28-02-2025 11:30:35","28-02-2025 11:27:29","28-02-2025 11:58:12",=
"Grid fluctuation, site went down because Gen fails to start due to Grid ba=
d voltage,no RCP on site  // He bypassed the Grid and site on GEN","MINKA N=
ICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, site went down because Gen fails to start due to G=
rid bad voltage,no RCP on site  // He bypassed the Grid and site on GEN","y=
ves.djomo@sagemcom.com","187","28-02-2025 11:30:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0004456668","E=
mombo","","28-02-2025 11:19:35","28-02-2025 11:11:28","28-02-2025 11:30:43"=
,"Grid outage, site went down because gen start and stopped with alarm ""hi=
gh temp"" // he added water and manually start the Gen","Mba Lazare Herve",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, site went down because gen start and stopped wit=
h alarm ""high temp"" // he added water and manually start the Gen","wilfri=
ed.kameni@sagemcom.com","488","28-02-2025 11:19:35","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004456082","OBA=
M NGOLA OCM","","28-02-2025 10:55:01","28-02-2025 10:50:51","28-02-2025 13:=
45:17","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 He Reset it and Site is on Grid	","MINKA NICOLAS","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Site went down due to PSC3 dysfonct=
ion SS IHS Pascaline confirmed// He Reset it and Site is on Grid	","wilfrie=
d.kameni@sagemcom.com","251","28-02-2025 10:55:01","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004455879","AWA=
E OCM","","28-02-2025 10:43:18","28-02-2025 10:34:06","28-02-2025 10:46:52"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automatically","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automatically","yves.djomo@sagem=
com.com","554","28-02-2025 10:43:18","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004455716","Awa=
e Escalier","","28-02-2025 10:34:56","28-02-2025 10:31:46","28-02-2025 10:3=
4:51","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started automatically","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Gen started automatically","wilfried.kamen=
i@sagemcom.com","222","28-02-2025 10:34:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_515","NOCINC0004455513","Etoug eb=
e Meweulo","","28-02-2025 10:24:15","28-02-2025 10:19:43","28-02-2025 10:24=
:42","Grid outage, Site went down before Gen start due to poor backup// Gen=
 started automatically","Hyemafo Gildas","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Gen started automatically","yves.djomo@sag=
emcom.com","273","28-02-2025 10:24:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004455417","M=
efou-Assi","","28-02-2025 10:07:22","28-02-2025 10:04:50","28-02-2025 10:10=
:57","No power issue on site Ubaie=3D54.3V site On Gen.The Tx FME Fulbert (=
654266068) from Huawei is informed. Notice that we have repetitive issue","=
Fanda Brice","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","No power issue on site Ubaie=3D54.3V site On Gen.T=
he Tx FME Fulbert (654266068) from Huawei is informed. Notice that we have =
repetitive issue","wilfried.kameni@sagemcom.com","153","28-02-2025 10:07:22=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004455379","B=
ATA Mokolo OCM","","28-02-2025 10:01:30","28-02-2025 09:22:18","28-02-2025 =
11:59:01","Grid outage,no space to deploy a mobile DG // Grid restored.",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage,no space to deploy a mobile DG // Grid restored.","yves.djomo@sagemco=
m.com","2353","28-02-2025 10:01:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004455342","O=
LAMA","","28-02-2025 09:59:20","28-02-2025 09:42:09","28-02-2025 09:55:55",=
"Active//No power issue on site, Site on Grid, UBAIE=3D54.9V. The Tx FME Et=
ienne/651320188/ from Huawei is informed","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue on site, Site on Grid, UBAIE=3D54.9V. The Tx FME Etienne/65=
1320188/ from Huawei is informed","yves.djomo@sagemcom.com","1031","28-02-2=
025 09:59:20","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004454906","Mel=
en Ba'aba","","28-02-2025 08:50:23","28-02-2025 08:42:11","28-02-2025 10:31=
:27","Grid outage site went down because Gen faulty // Grid power return","=
Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fa=
ulty","Grid outage site went down because Gen faulty // Grid power return",=
"wilfried.kameni@sagemcom.com","494","28-02-2025 08:50:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0004454780","M=
fou OCM","","28-02-2025 08:23:13","28-02-2025 08:15:07","28-02-2025 09:01:5=
7","Grid outage.gen started and stoped due to alarm ""low oil pressure""//H=
e reset card GE and gen manually started","Mba Lazare Herve","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen started a=
nd stoped due to alarm ""low oil pressure""//He reset card GE and gen manua=
lly started","wilfried.kameni@sagemcom.com","487","28-02-2025 08:23:13","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0004454276","M=
volye-New","","28-02-2025 06:43:14","28-02-2025 06:41:57","28-02-2025 06:50=
:17","Active// No power issue U =3D52.1V site on Grid.The FME TX Mbah Hosia=
h (674007438/699699694) from Huawei is informed","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No=
 power issue U =3D52.1V site on Grid.The FME TX Mbah Hosiah (674007438/6996=
99694) from Huawei is informed","wilfried.kameni@sagemcom.com","78","28-02-=
2025 06:43:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004454243","M=
essassi 2","","28-02-2025 06:34:48","28-02-2025 06:33:39","28-02-2025 10:11=
:55","	Site went down because PWC overload (12 kilo, 300A) , SS IHS Bernard=
 ATANGANA confirmed// He reset it","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","	Site went down because P=
WC overload (12 kilo, 300A) , SS IHS Bernard ATANGANA confirmed// He reset =
it","yves.djomo@sagemcom.com","70","28-02-2025 06:34:48","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004453960","Mfo=
u EPC","","28-02-2025 05:09:30","28-02-2025 05:05:18","28-02-2025 06:56:24"=
,"Grid outage, site went down because gen start and stopped with alarm ""hi=
gh temp"" // he added water and manually start the Gen","Mba Lazare Herve",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, site went down because gen start and stopped wit=
h alarm ""high temp"" // he added water and manually start the Gen","el-dal=
ile@sagemcom.com","253","28-02-2025 05:09:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_360","IHS_YND_373","NOCINC0004453830","M=
aloun","","28-02-2025 04:33:25","28-02-2025 03:57:17","28-02-2025 04:00:52"=
,"No power issue on site U=3D54,6V site on Gen , The Tx FME Etienne/6513201=
88/ from Huawei is informed","Kemeni Franklin","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D54,6V site on Gen , The Tx FME Etienne/651320188/ from Huawei is=
 informed","yves.djomo@sagemcom.com","2168","28-02-2025 04:33:25","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004453767","M=
essassi 2","","28-02-2025 04:17:56","28-02-2025 04:12:51","28-02-2025 04:33=
:05","Site went down because PWC overload (12 kilo, 300A) , SS IHS Bernard =
ATANGANA confirmed// He reset it","Fabrice Pouakam","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Site went down because PWC=
 overload (12 kilo, 300A) , SS IHS Bernard ATANGANA confirmed// He reset it=
","yves.djomo@sagemcom.com","306","28-02-2025 04:17:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0004453686","O=
bili Carrefour","","28-02-2025 03:39:43","28-02-2025 03:37:33","28-02-2025 =
03:40:57","Active//No power issue U =3D53,4V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed","Paul BIBOUM","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active//No power issue U =3D53,4V site on Grid.The FME TX Mbah Hosiah (=
674007438/699699694) from Huawei is informed","el-dalile@sagemcom.com","130=
","28-02-2025 03:39:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004453270","M=
efou-Assi","","28-02-2025 01:34:49","28-02-2025 01:32:41","28-02-2025 01:35=
:49","ACTIVE//No power issue on site GRID , Ubaie=3D53.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed. Repetitive issue","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D53.V site =
On Grid The Tx FME Fulbert(654266068) from Huawei is informed. Repetitive i=
ssue","yves.djomo@sagemcom.com","129","28-02-2025 01:34:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004453131","Eto koss=
 Yde","","28-02-2025 01:09:30","28-02-2025 01:03:35","28-02-2025 01:12:02",=
"Cascaded Incident from TTO4504367","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation,Site went down beca=
use Gen failed to start due to grid bad voltage// He bypassed the Grid and =
started the Gen manually","system","262738","28-02-2025 01:09:30","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004453132","ELOUMDEM=
 CARRIERE 2","","28-02-2025 01:09:30","28-02-2025 01:03:35","28-02-2025 01:=
12:02","Cascaded Incident from TTO4504367","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation,Site went do=
wn because Gen failed to start due to grid bad voltage// He bypassed the Gr=
id and started the Gen manually","system","262738","28-02-2025 01:09:30","S=
agemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004453105","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","28-02-2025 01:07:52","28-02-2025 01:03=
:35","28-02-2025 01:12:02","Grid fluctuation,Site went down because Gen fai=
led to start due to grid bad voltage// He bypassed the Grid and started the=
 Gen manually","Fanda Brice","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Grid fluctuation,Site went down because Gen fai=
led to start due to grid bad voltage// He bypassed the Grid and started the=
 Gen manually","el-dalile@sagemcom.com","259","28-02-2025 01:07:52","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004453094","B=
riqueterie","","28-02-2025 01:03:52","28-02-2025 00:54:55","28-02-2025 01:0=
0:33","Active// No power issue, site is on Grid with Ubaie=3D53,6V, Brice T=
sague(650214096) from Huawei is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power =
issue, site is on Grid with Ubaie=3D53,6V, Brice Tsague(650214096) from Hua=
wei is informed","el-dalile@sagemcom.com","538","28-02-2025 01:03:52","Sage=
mcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004453040","Aha=
la Echangeur","","28-02-2025 00:45:51","28-02-2025 00:40:33","28-02-2025 07=
:16:36","Access Issue during the Night Grid outage ,site went down because =
Gen failed to started due to  Gen contactor Faulty // He bypass the Gen con=
tactor and Gen manually started","MINKA NICOLAS","Access Denial","Lease Or =
Legal","Landlord Related Issues","Access Issue - Land Lord","Access Issue d=
uring the Night Grid outage ,site went down because Gen failed to started d=
ue to  Gen contactor Faulty // He bypass the Gen contactor and Gen manually=
 started","el-dalile@sagemcom.com","319","28-02-2025 00:45:51","Sagemcom CM=
R"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004452922","Nko=
g-Edzen","","28-02-2025 00:10:51","28-02-2025 00:07:40","28-02-2025 00:12:5=
8","No power issue site on Gen. The Tx Fme Gregoire (654547479) from Huawei=
 informed and up at 12:12 AM","Parker Tchoup","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on Gen. The Tx Fme Gregoire (654547479) from Huawei informed and up at 1=
2:12 AM","el-dalile@sagemcom.com","192","28-02-2025 00:10:51","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004452751","M=
elen Ba'aba","","27-02-2025 23:13:04","27-02-2025 21:56:58","28-02-2025 08:=
02:59","Grid outage, site went down due to gen overload(15kva, 216A), Blais=
e IHS confirm // Grid power return","Siligap Boris","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload(15kva, 216A), Blaise IHS confirm // Grid power return","yves.djomo=
@sagemcom.com","4567","27-02-2025 23:13:04","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004452588","OBA=
M NGOLA OCM","","27-02-2025 22:30:57","27-02-2025 22:25:43","27-02-2025 23:=
29:51","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 He Reset it and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Site went down due to PSC3 dysfoncti=
on SS IHS Pascaline confirmed// He Reset it and Site is on Grid","wilfried.=
kameni@sagemcom.com","315","27-02-2025 22:30:57","Sagemcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004452398","Tam=
tam Weekend","","27-02-2025 21:43:17","27-02-2025 21:42:56","27-02-2025 21:=
58:48"," Site went down due to CB (63A) Disjunted in the DC-Box because  th=
e Load Increase //He reamed the CB(63A)","Hyemafo Gildas","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue"," Site =
went down due to CB (63A) Disjunted in the DC-Box because  the Load Increas=
e //He reamed the CB(63A)","wilfried.kameni@sagemcom.com","22","27-02-2025 =
21:43:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004452329","S=
hell-Nsimeyong","","27-02-2025 21:33:29","27-02-2025 21:25:15","27-02-2025 =
21:26:15","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed","MINKA NICOLAS","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue U =3D52.1V site on Grid.The FME TX Mbah Hosiah=
 (674007438/699699694) from Huawei is informed","danick.tchakouani@sagemcom=
.com","494","27-02-2025 21:33:29","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004452290","Aha=
la Echangeur","","27-02-2025 21:25:38","27-02-2025 21:06:31","27-02-2025 22=
:14:12"," Grid outage ,site went down because Gen contactor Faulty // He by=
pass it and Manully Start the Gen","MINKA NICOLAS","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Load Contactor"," Grid outage ,site went down becau=
se Gen contactor Faulty // He bypass it and Manully Start the Gen","wilfrie=
d.kameni@sagemcom.com","1148","27-02-2025 21:25:38","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004452184","Lad=
a I Yde","","27-02-2025 21:10:07","27-02-2025 20:59:53","28-02-2025 00:21:4=
4","Active// No power issue, site is on Grid with Ubaie=3D54,5V, Lionel Adj=
ep(655184876) from Huawei is informed","Mba Lazare Herve","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue, site is on Grid with Ubaie=3D54,5V, Lionel Adjep(655184=
876) from Huawei is informed","wilfried.kameni@sagemcom.com","615","27-02-2=
025 21:10:07","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004452144","Crf=
-Mbankolo-IHS","","27-02-2025 21:05:12","27-02-2025 20:55:22","27-02-2025 2=
2:13:52","Site went down due to MPR disfunction SS IHS Bernard Atangana con=
firmed/ / He reset it","Mboua Thierry","Equipment Repair","Passive","Rectif=
ier","Rectifier Cabinet","Site went down due to MPR disfunction SS IHS Bern=
ard Atangana confirmed/ / He reset it","wilfried.kameni@sagemcom.com","591"=
,"27-02-2025 21:05:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004452075","M=
endong vallee","","27-02-2025 20:50:24","27-02-2025 20:46:46","28-02-2025 0=
5:59:57","Grid outage, Site went down due to gen Overload(20KVA; 300A) IHS =
F=E9lix Zamb=E9 is informed and confirmed// Grid return","Fanda Brice","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site we=
nt down due to gen Overload(20KVA; 300A) IHS F=E9lix Zamb=E9 is informed an=
d confirmed// Grid return","danick.tchakouani@sagemcom.com","219","27-02-20=
25 20:50:24","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004452022","Mel=
en Ba'aba","","27-02-2025 20:45:27","27-02-2025 20:06:20","27-02-2025 21:50=
:35","Grid outage, site went down due to gen overload(15kva, 216A), Blaise =
IHS confirmed// Grid return","Siligap Boris","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen overloa=
d(15kva, 216A), Blaise IHS confirmed// Grid return","danick.tchakouani@sage=
mcom.com","2348","27-02-2025 20:45:27","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004451952","Mon=
tee Jouvence","","27-02-2025 20:37:55","27-02-2025 20:34:48","27-02-2025 21=
:28:23","Grid fluctuation, site went down because Gen fails to start  due t=
o Grid bad voltage and no RCP on site // HE bypassed Grid and Gen manually =
started","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","Grid fluctuation, site went down because Gen fails=
 to start  due to Grid bad voltage and no RCP on site // HE bypassed Grid a=
nd Gen manually started","danick.tchakouani@sagemcom.com","188","27-02-2025=
 20:37:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004451810","N=
koabang Ebolmedjock","","27-02-2025 20:07:45","27-02-2025 19:36:36","27-02-=
2025 19:40:26","Active// No power issue, site is on Gen with Ubaie=3D53,6V,=
 Lionel Adjep(655184876) from Huawei is informed","Mba Lazare Herve","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue, site is on Gen with Ubaie=3D53,6V, Lionel Ad=
jep(655184876) from Huawei is informed","danick.tchakouani@sagemcom.com","1=
870","27-02-2025 20:07:45","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004451806","SIM=
BOCK BONAMBAPE","","27-02-2025 20:07:01","27-02-2025 19:48:48","27-02-2025 =
21:35:14","Grid outage, Site went down because Gen started and stopped due =
to Gen overload(20kva, 380A) SS IHS Alphonse DEFFO confirmed.// He reduiced=
 load and started Gen manualy","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen sta=
rted and stopped due to Gen overload(20kva, 380A) SS IHS Alphonse DEFFO con=
firmed.// He reduiced load and started Gen manualy","ludovic-anselme.moulio=
m-mapoure@sagemcom","1094","27-02-2025 20:07:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004451194","N=
YOM 2 IHS","","27-02-2025 18:34:32","27-02-2025 18:30:38","27-02-2025 19:50=
:38","Grid outage, site went down because gen start and stopped with over v=
oltage alarm(unpruven) // Reset done and gen started","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, s=
ite went down because gen start and stopped with over voltage alarm(unpruve=
n) // Reset done and gen started","danick.tchakouani@sagemcom.com","235","2=
7-02-2025 18:34:32","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004451168","Mes=
sa Carriere","","27-02-2025 18:29:49","27-02-2025 18:21:43","27-02-2025 19:=
43:49","Site went down because gen start and stopped due to grid bad voltag=
e // He bypass grid and manually start the gen","Mboua Thierry","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Site went do=
wn because gen start and stopped due to grid bad voltage // He bypass grid =
and manually start the gen","ludovic-anselme.mouliom-mapoure@sagemcom","130=
02","27-02-2025 18:29:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004451160","ELOUMDEM=
 CARRIERE 2","","27-02-2025 18:29:01","27-02-2025 18:27:03","27-02-2025 19:=
49:08","Cascaded Incident from TTO4502111","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage,gen ran until fue=
l shortage//Refueling done","system","272046","27-02-2025 18:29:01","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004451159","Eto koss=
 Yde","","27-02-2025 18:29:00","27-02-2025 18:27:03","27-02-2025 19:49:08",=
"Cascaded Incident from TTO4502111","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,gen ran until fuel short=
age//Refueling done","system","272046","27-02-2025 18:29:00","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004451147","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","27-02-2025 18:28:09","27-02-2025 18:27=
:03","27-02-2025 19:49:38","Grid outage,gen ran until fuel shortage//Refuel=
ing done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage,gen ran until fuel shortage//Refueling done","danick.tchakouani@=
sagemcom.com","68","27-02-2025 18:28:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004450861","N=
gouetou","","27-02-2025 17:38:38","27-02-2025 17:29:26","27-02-2025 20:32:4=
1","No power issue site on Gen with U=3D54v  The Tx FME Gregoire/654547479/=
 from Huawei is informed .","Parker Tchoup","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on Gen with U=3D54v  The Tx FME Gregoire/654547479/ from Huawei is informe=
d .","danick.tchakouani@sagemcom.com","553","27-02-2025 17:38:38","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004450724","c=
hina embassy yde","","27-02-2025 17:12:36","27-02-2025 17:09:12","28-02-202=
5 08:10:25","ACCESS ISSSUE DUE TO  The landlord stopped Eneo Meter because =
Awaitting normalisation from IHS Bernard ATANGANA confirmed // Grid power r=
eturn","","Access Denial","Lease Or Legal","Landlord Related Issues","Acces=
s Issue - Land Lord","ACCESS ISSSUE DUE TO  The landlord stopped Eneo Meter=
 because Awaitting normalisation from IHS Bernard ATANGANA confirmed // Gri=
d power return","danick.tchakouani@sagemcom.com","205","27-02-2025 17:12:36=
","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004450589","Mes=
sa Carriere","","27-02-2025 16:53:40","27-02-2025 16:52:29","27-02-2025 17:=
51:50","Grid outage, site went down because gen failed to start due toGen c=
ard faulty //Gen manually started","Mboua Thierry","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because=
 gen failed to start due toGen card faulty //Gen manually started","ludovic=
-anselme.mouliom-mapoure@sagemcom","72","27-02-2025 16:53:40","Sagemcom CMR=
"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0004450555","OTE=
LE MTN","","27-02-2025 16:46:35","27-02-2025 16:42:14","27-02-2025 18:07:51=
","Grid outage, site went down because gen fails to start due to battery ge=
 discharged // Gen start with battery backup","Fanda Brice","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, site went=
 down because gen fails to start due to battery ge discharged // Gen start =
with battery backup","danick.tchakouani@sagemcom.com","262","27-02-2025 16:=
46:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0004450542","N=
goum","","27-02-2025 16:43:13","27-02-2025 16:24:07","27-02-2025 19:00:23",=
"Solar Hybrid GEN site, No power issue site on Solar, with U=3D52.7V. The T=
x Fme Gregoire (654547479) from Huawei informed","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Solar Hybrid GEN site, No power issue site on Solar, with U=3D52.7V. The =
Tx Fme Gregoire (654547479) from Huawei informed","danick.tchakouani@sagemc=
om.com","1147","27-02-2025 16:43:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004450457","E=
foulan","","27-02-2025 16:26:04","27-02-2025 16:05:56","27-02-2025 16:10:09=
","No power issue on site U=3D54,1v site on grid Brice Tsague of huawei is =
informed","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,1v site=
 on grid Brice Tsague of huawei is informed","danick.tchakouani@sagemcom.co=
m","1209","27-02-2025 16:26:04","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004450429","Nko=
g-Edzen","","27-02-2025 16:22:51","27-02-2025 16:15:41","27-02-2025 18:20:1=
7","No power issue site on Solar, with U=3D52.7V. The Tx Fme Gregoire (6545=
47479) from Huawei informed","Parker Tchoup","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on Solar, with U=3D52.7V. The Tx Fme Gregoire (654547479) from Huawei inf=
ormed","danick.tchakouani@sagemcom.com","431","27-02-2025 16:22:51","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004450358","O=
bobogo","","27-02-2025 16:14:32","27-02-2025 16:05:23","27-02-2025 19:00:09=
","No power issue on site U=3D54,1v site on grid Brice Tsague of huawei is =
informed","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,1v site=
 on grid Brice Tsague of huawei is informed","danick.tchakouani@sagemcom.co=
m","550","27-02-2025 16:14:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004449957","O=
LAMA","","27-02-2025 15:07:38","27-02-2025 14:59:28","27-02-2025 16:00:29",=
"No power issue on site U=3D54,9 V site on Gen , The Tx FME Etienne/6513201=
88/ from Huawei is informed","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on si=
te U=3D54,9 V site on Gen , The Tx FME Etienne/651320188/ from Huawei is in=
formed","danick.tchakouani@sagemcom.com","490","27-02-2025 15:07:38","Sagem=
com CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004449942","Nom=
ayos montee Meche","","27-02-2025 15:07:10","27-02-2025 15:06:51","27-02-20=
25 19:08:51","No power issue on site Ubaie=3D53.5V site on Grid.   The Tx F=
ME Fulbert /654266068 From Huawei is informed. ","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site Ubaie=3D53.5V site on Grid.   The Tx FME Fulbert /65=
4266068 From Huawei is informed. ","ludovic-anselme.mouliom-mapoure@sagemco=
m","20","27-02-2025 15:07:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004449859","B=
arriere","","27-02-2025 15:02:46","27-02-2025 15:00:38","27-02-2025 16:33:4=
9","Grid outage ,site went down because Gen Overload (20KVA, 450A) Felix Za=
mbe confirmed (After Jouvence Mbenda) // Grid return","Hyemafo Gildas","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,site we=
nt down because Gen Overload (20KVA, 450A) Felix Zambe confirmed (After Jou=
vence Mbenda) // Grid return","danick.tchakouani@sagemcom.com","129","27-02=
-2025 15:02:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004449702","B=
ATA Mokolo OCM","","27-02-2025 14:57:31","27-02-2025 14:54:16","27-02-2025 =
17:53:47","Grid outage.no space to deploy mobile Gen  // Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge.no space to deploy mobile Gen  // Grid return","danick.tchakouani@sagemc=
om.com","195","27-02-2025 14:57:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004449697","M=
efou-Assi","","27-02-2025 14:56:30","27-02-2025 14:52:24","27-02-2025 16:32=
:25","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME=
 Fulbert(654266068) from Huawei is informed","danick.tchakouani@sagemcom.co=
m","247","27-02-2025 14:56:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004449636","Emana Ly=
cee","","27-02-2025 14:47:40","27-02-2025 14:42:50","27-02-2025 15:56:58","=
Cascaded Incident from TTO4500372","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation, site went down =
because Gen failed to start due to grid bad voltage and  no Rcp // He bypas=
sed  Grid and started Gen manually","system","285552","27-02-2025 14:47:40"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004449617","E=
mana lycee 2","IHS_YND_274","27-02-2025 14:47:03","27-02-2025 14:42:50","27=
-02-2025 15:56:58","Grid fluctuation, site went down because Gen failed to =
start due to grid bad voltage and  no Rcp // He bypassed  Grid and started =
Gen manually","Fabrice Pouakam","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Grid fluctuation, site went down because Gen=
 failed to start due to grid bad voltage and  no Rcp // He bypassed  Grid a=
nd started Gen manually","danick.tchakouani@sagemcom.com","254","27-02-2025=
 14:47:03","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004449581","Mel=
en Ba'aba","","27-02-2025 14:44:32","27-02-2025 14:38:04","27-02-2025 15:57=
:28","Grid outage, site went down due to gen overload(15kva, 216A), Blaise =
IHS confirm // Grid return","Siligap Boris","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, site went down due to gen overload=
(15kva, 216A), Blaise IHS confirm // Grid return","wilfried.kameni@sagemcom=
.com","389","27-02-2025 14:44:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0004449326","Lobo OCM=
","","27-02-2025 13:58:50","27-02-2025 13:43:33","27-02-2025 18:55:33","Cas=
caded Incident from TTO4500012","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 because gen start and stopped due to high temp // He added water and manua=
lly start the gen","system","289131","27-02-2025 13:58:50","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004449313","NKO=
MEKUI OCM","IHS_YND_341","27-02-2025 13:57:40","27-02-2025 13:43:33","27-02=
-2025 18:55:33","Grid outage, site went down because gen start and stopped =
due to high temp // He added water and manually start the gen","TIENTCHEU N=
ZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine =
Temp - Coolant Level Issue","Grid outage, site went down because gen start =
and stopped due to high temp // He added water and manually start the gen",=
"ludovic-anselme.mouliom-mapoure@sagemcom","915","27-02-2025 13:57:40","Sag=
emcom CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0004449133","NKO=
NGKARAK","","27-02-2025 13:20:22","27-02-2025 13:14:13","27-02-2025 19:10:1=
9","	Site went down because Gen started and stopped due to pierced pellet /=
/ he glued the Pellet and Manually Started The Gen","TIENTCHEU NZETCHIEU GA=
EL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Radi=
ator Leakage","	Site went down because Gen started and stopped due to pierc=
ed pellet // he glued the Pellet and Manually Started The Gen","ludovic-ans=
elme.mouliom-mapoure@sagemcom","370","27-02-2025 13:20:22","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004449129","Men=
dong3","","27-02-2025 13:19:39","27-02-2025 13:17:29","27-02-2025 15:03:01"=
,"Grid outage.no space to deploy mobile gen// grid power ","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no space=
 to deploy mobile gen// grid power ","ludovic-anselme.mouliom-mapoure@sagem=
com","131","27-02-2025 13:19:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004449122","O=
lembe-Terminus","","27-02-2025 13:18:18","27-02-2025 13:09:04","27-02-2025 =
13:36:53","Site went down due to work SS his Bernard was working on site ( =
Swapp of Gen) // End of work","Fabrice Pouakam","Installation Activity","Pa=
ssive","Planned Activity","Installation Activity","Site went down due to wo=
rk SS his Bernard was working on site ( Swapp of Gen) // End of work","cedr=
ic.tiani@sagemcom.com","556","27-02-2025 13:18:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004449000","Nkolkoum=
ou OCM","","27-02-2025 12:55:30","27-02-2025 12:46:07","27-02-2025 17:00:49=
","Cascaded Incident from TTO4499638","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","	Grid outage site wen=
t down because Gen started and stopped with  alarm ""over current""  due to=
 increase load on site // He reset  Gen Card and Gen manaully started","sys=
tem","292437","27-02-2025 12:55:30","Sagemcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0004448990","Nko=
lbisson usine des eaux","IHS_YND_712","27-02-2025 12:54:19","27-02-2025 12:=
44:07","27-02-2025 17:55:37","	Grid outage site went down because Gen start=
ed and stopped with  alarm ""over current""  due to increase load on site /=
/ He reset  Gen Card and Gen manaully started","TIENTCHEU NZETCHIEU GAEL","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","	Grid outage=
 site went down because Gen started and stopped with  alarm ""over current"=
"  due to increase load on site // He reset  Gen Card and Gen manaully star=
ted","ludovic-anselme.mouliom-mapoure@sagemcom","973","27-02-2025 12:54:19"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004448987","BAT=
A Mokolo OCM","","27-02-2025 12:53:27","27-02-2025 12:48:18","27-02-2025 13=
:20:16","Grid outage.no space to deploy mobile gen.//Grid return ","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.=
no space to deploy mobile gen.//Grid return ","ludovic-anselme.mouliom-mapo=
ure@sagemcom","311","27-02-2025 12:53:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004448976","M=
efou-Assi","","27-02-2025 12:49:38","27-02-2025 12:44:24","27-02-2025 12:50=
:54","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME=
 Fulbert(654266068) from Huawei is informed","cedric.tiani@sagemcom.com","3=
15","27-02-2025 12:49:38","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004448860","SIM=
BOCK BONAMBAPE","","27-02-2025 12:25:26","27-02-2025 12:16:14","27-02-2025 =
14:23:14","Site went down due to 1/7 rectifier faulty on site IHS Felix Zam=
b=E9 is informed  // Site up ( Rectifier module to be replace)","Hyemafo Gi=
ldas","Equipment Repair","Passive","Rectifier","Rectifier Module","Site wen=
t down due to 1/7 rectifier faulty on site IHS Felix Zamb=E9 is informed  /=
/ Site up ( Rectifier module to be replace)","ludovic-anselme.mouliom-mapou=
re@sagemcom","553","27-02-2025 12:25:26","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004448855","Tou=
ring Club International","","27-02-2025 12:22:59","27-02-2025 12:10:37","27=
-02-2025 12:14:52","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed// Grid return","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went down =
because Gen overload (20Kw, 270A) SS IHS Pascaline confirmed// Grid return"=
,"cedric.tiani@sagemcom.com","743","27-02-2025 12:22:59","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004448833","Elo=
umdem stade","","27-02-2025 12:19:05","27-02-2025 12:01:55","27-02-2025 13:=
51:50","Grid fluctuation, Site went down because Gen fails to start  due to=
 Grid bad voltage and NO RCP on site / He bypassed Grid and started Gen man=
ualy","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation, Site went down because Gen fails to st=
art  due to Grid bad voltage and NO RCP on site / He bypassed Grid and star=
ted Gen manualy","ludovic-anselme.mouliom-mapoure@sagemcom","1031","27-02-2=
025 12:19:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0004448781","M=
ontee-Jouvence","","27-02-2025 12:12:54","27-02-2025 11:57:27","27-02-2025 =
12:47:47","Site went down because gen start and stopped due to grid bad vol=
tage // He bypass grid and manually start the gen","Hyemafo Gildas","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Site wen=
t down because gen start and stopped due to grid bad voltage // He bypass g=
rid and manually start the gen","cedric.tiani@sagemcom.com","928","27-02-20=
25 12:12:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004448776","M=
ontee-Des-Soeurs","","27-02-2025 12:11:30","27-02-2025 12:05:17","27-02-202=
5 12:13:34","Grid outage, Site went down before Gen start due to poor backu=
p// Gen started manually","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen started manually","cedric.tiani@sage=
mcom.com","375","27-02-2025 12:11:30","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004448768","AWA=
E OCM","","27-02-2025 12:10:22","27-02-2025 12:08:06","27-02-2025 12:49:33"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automatically","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automatically","cedric.tiani@sag=
emcom.com","137","27-02-2025 12:10:22","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004448764","NKO=
LMEKONG YDE","","27-02-2025 12:09:27","27-02-2025 12:03:19","27-02-2025 12:=
11:40","Site went down because PWC dysfunctionning IHS SS BERNARD ATANGANA =
is informed and confirmed// Site stabilized","Fabrice Pouakam","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Site went down =
because PWC dysfunctionning IHS SS BERNARD ATANGANA is informed and confirm=
ed// Site stabilized","ludovic-anselme.mouliom-mapoure@sagemcom","369","27-=
02-2025 12:09:27","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004448756","NYO=
M FACE MAETUR","","27-02-2025 12:07:53","27-02-2025 12:05:47","27-02-2025 1=
3:05:56","Grid outage, site went down because Gen failed to start due to Ge=
n card and solenoid faulty// Grid return","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went dow=
n because Gen failed to start due to Gen card and solenoid faulty// Grid re=
turn","ludovic-anselme.mouliom-mapoure@sagemcom","127","27-02-2025 12:07:53=
","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004448647","OBA=
M NGOLA OCM","","27-02-2025 11:49:44","27-02-2025 11:40:33","27-02-2025 11:=
58:16","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed /=
/ Grid return","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down due to PSC3 dysfonction SS IHS Pascaline co=
nfirmed // Grid return","cedric.tiani@sagemcom.com","552","27-02-2025 11:49=
:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004448610","L=
abogenie","","27-02-2025 11:44:01","20-02-2025 19:02:07","20-02-2025 19:10:=
31","No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (6932124=
05 )from Huawei is informed","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No  power issue U =3D54,5V site=
 on Grid. The Tx FME  Eloundou (693212405 )from Huawei is informed","alwine=
.fambou@ihstowers.com","651678","27-02-2025 11:44:01","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004448172","OBA=
M NGOLA OCM","","27-02-2025 10:47:53","27-02-2025 10:33:17","27-02-2025 10:=
51:39","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 Grid return ","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Site went down due to PSC3 dysfonction SS IHS Pascaline=
 confirmed// Grid return ","cedric.tiani@sagemcom.com","877","27-02-2025 10=
:47:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0004448150","Mvog-Eba=
nda","","27-02-2025 10:44:20","27-02-2025 10:34:18","27-02-2025 11:00:30","=
Cascaded Incident from TTO4498666","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.site went down due to g=
en failed to start //Grid return(investigation ongoing)","system","271636",=
"27-02-2025 10:44:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0004448146","A=
bom","IHS_YND_269","27-02-2025 10:43:26","27-02-2025 10:34:18","27-02-2025 =
11:00:30","Grid outage.site went down due to gen failed to start //Grid ret=
urn(investigation ongoing)","Siligap Boris","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage.site went down due to gen fail=
ed to start //Grid return(investigation ongoing)","ludovic-anselme.mouliom-=
mapoure@sagemcom","549","27-02-2025 10:43:26","Sagemcom CMR"
"Closed Complete","Site Down","T1411","IHS_YND_543","NOCINC0004447970","Ent=
ree Cite Verte","","27-02-2025 10:16:38","27-02-2025 10:14:49","27-02-2025 =
13:15:37","No power issue site on grid with U=3D54v Martial(690087047) from=
 Huawei is informed","Paul BIBOUM","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D54v Martial(690087047) from Huawei is informed","cedric.tiani@sage=
mcom.com","110","27-02-2025 10:16:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_406","IHS_YND_456","NOCINC0004447927","M=
BIMBIM","","27-02-2025 10:08:43","18-02-2025 04:45:27","18-02-2025 04:46:24=
","No power issue hybrid gen site on gen with U=3D53.2v Geroire from Huawei=
 is informed ","Parker Tchoup","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue hybrid gen site o=
n gen with U=3D53.2v Geroire from Huawei is informed ","ludovic-anselme.mou=
liom-mapoure@sagemcom","796997","27-02-2025 10:08:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0004447876","Y=
oko OCM","","27-02-2025 10:02:01","18-02-2025 04:46:45","18-02-2025 04:50:3=
1","No power issue site on gen with U=3D54v Gregoire from Huawei is informe=
d","Parker Tchoup","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue site on gen with U=3D54v Greg=
oire from Huawei is informed","ludovic-anselme.mouliom-mapoure@sagemcom","7=
96517","27-02-2025 10:02:01","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004447859","SIM=
BOCK BONAMBAPE","","27-02-2025 09:57:11","27-02-2025 09:53:32","27-02-2025 =
09:57:35","Site went down because Gen fails to start due to Grid bad voltag=
e // Grid stabilized","Hyemafo Gildas","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","Site went down because Gen fails to s=
tart due to Grid bad voltage // Grid stabilized","cedric.tiani@sagemcom.com=
","220","27-02-2025 09:57:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0004447610","M=
amch Building","","27-02-2025 09:13:03","20-02-2025 19:46:33","20-02-2025 1=
9:49:33","No, power issue site on grid with U=3D54v Mohamadou from Huawei i=
s informed(bactracking)","Mboua Thierry","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No, power issue site o=
n grid with U=3D54v Mohamadou from Huawei is informed(bactracking)","ludovi=
c-anselme.mouliom-mapoure@sagemcom","566792","27-02-2025 09:13:03","Sagemco=
m CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0004447579","Sim=
bock Maetur","IHS_YND_259","27-02-2025 09:06:27","27-02-2025 08:57:05","27-=
02-2025 09:22:59","Site went down because Gen fails to start due to Grid ba=
d voltage // He bypass the Grid and Gen manually started","Hyemafo Gildas",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","S=
ite went down because Gen fails to start due to Grid bad voltage // He bypa=
ss the Grid and Gen manually started","cedric.tiani@sagemcom.com","563","27=
-02-2025 09:06:27","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004447554","OBA=
M NGOLA OCM","","27-02-2025 09:04:40","27-02-2025 09:02:05","27-02-2025 09:=
26:49","Grid outage, Site went down because Gen ran until fuel shortage// R=
efueling Done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, Site went down because Gen ran until fuel shortage// Ref=
ueling Done","ludovic-anselme.mouliom-mapoure@sagemcom","156","27-02-2025 0=
9:04:40","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004447548","Sim=
bock MTN","","27-02-2025 09:02:01","27-02-2025 08:57:05","27-02-2025 09:22:=
59","Site went down because Gen fails to start due to Grid bad voltage // H=
e bypass the Grid and Gen manually started","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down because Gen f=
ails to start due to Grid bad voltage // He bypass the Grid and Gen manuall=
y started","cedric.tiani@sagemcom.com","270293","27-02-2025 09:02:01","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004447414","S=
hell-Nsimeyong","","27-02-2025 08:39:21","27-02-2025 08:37:11","27-02-2025 =
10:26:03","Active//No power issue U =3D52.2V site on Grid.The FME TX Mbah H=
osiah (674007438/699699694) from Huawei is informed","MINKA NICOLAS","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah=
 (674007438/699699694) from Huawei is informed","cedric.tiani@sagemcom.com"=
,"131","27-02-2025 08:39:21","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004447333","Mon=
tee Jouvence","","27-02-2025 08:17:51","27-02-2025 08:14:44","27-02-2025 08=
:30:59","Grid fluctuation, Site went down because Gen fails to start due to=
 Grid bad voltage // He bypass the Grid and Gen manually started","Hyemafo =
Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, Site went down because Gen fails to start due to G=
rid bad voltage // He bypass the Grid and Gen manually started","ludovic-an=
selme.mouliom-mapoure@sagemcom","188","27-02-2025 08:17:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004447323","M=
endong","","27-02-2025 08:13:45","27-02-2025 08:07:09","27-02-2025 08:43:28=
","Site went down because Gen fails to start due to Grid bad voltage // He =
bypass the Grid and Gen manually started","Hyemafo Gildas","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Site went down be=
cause Gen fails to start due to Grid bad voltage // He bypass the Grid and =
Gen manually started","cedric.tiani@sagemcom.com","398","27-02-2025 08:13:4=
5","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004447078","Men=
dong vallee","","27-02-2025 07:37:23","27-02-2025 07:34:12","27-02-2025 08:=
53:47","Site went down due to gen Overload(20KVA; 300A) IHS F=E9lix Zamb=E9=
 is informed and confirmed//he Reduice the Load and Manually Started the Ge=
n","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Site went down due to gen Overload(20KVA; 300A) IHS F=E9lix Zamb=E9 is inf=
ormed and confirmed//he Reduice the Load and Manually Started the Gen","lud=
ovic-anselme.mouliom-mapoure@sagemcom","223","27-02-2025 07:37:23","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004447014","Eto koss=
 Yde","","27-02-2025 07:23:50","27-02-2025 07:14:23","27-02-2025 11:34:23",=
"Cascaded Incident from TTO4497371","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to insufficiency =
of rectifiers//We reset rectifiers site on grid ","system","305447","27-02-=
2025 07:23:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004447015","ELOUMDEM=
 CARRIERE 2","","27-02-2025 07:23:50","27-02-2025 07:14:23","27-02-2025 11:=
34:23","Cascaded Incident from TTO4497371","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to insuffi=
ciency of rectifiers//We reset rectifiers site on grid ","system","305447",=
"27-02-2025 07:23:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004446986","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","27-02-2025 07:17:41","27-02-2025 07:=
14:23","27-02-2025 11:34:49","Site went down due to insufficiency of rectif=
iers//We reset rectifiers site on grid ","Fanda Brice","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down due to insufficienc=
y of rectifiers//We reset rectifiers site on grid ","cedric.tiani@sagemcom.=
com","200","27-02-2025 07:17:41","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004446728","Mon=
tee-Jouvence-II","","27-02-2025 06:35:28","27-02-2025 06:23:11","27-02-2025=
 07:31:42","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix Za=
mb=E9 confirmed // he reset and  started the Gen manually","Hyemafo Gildas"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Si=
te went down due to PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirme=
d // he reset and  started the Gen manually","danick.tchakouani@sagemcom.co=
m","738","27-02-2025 06:35:28","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0004446700","Evo=
doula MTN","","27-02-2025 06:31:43","27-02-2025 06:11:17","27-02-2025 06:53=
:06","Grid outage gen failed to start due to alarm""undervoltage""//We rese=
t card GE and gen manually started ","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage gen failed=
 to start due to alarm""undervoltage""//We reset card GE and gen manually s=
tarted ","danick.tchakouani@sagemcom.com","1227","27-02-2025 06:31:43","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004446595","O=
LAMA","","27-02-2025 06:03:07","27-02-2025 04:48:23","27-02-2025 04:48:24",=
"No power issue on site U=3D54,9 V site on Gen , The Tx FME Etienne/6513201=
88/ from Huawei is informed","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on si=
te U=3D54,9 V site on Gen , The Tx FME Etienne/651320188/ from Huawei is in=
formed","danick.tchakouani@sagemcom.com","4485","27-02-2025 06:03:07","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004446521","N=
YOM 2 IHS","","27-02-2025 05:30:47","27-02-2025 05:26:41","27-02-2025 05:41=
:50","Grid outage site went down because Gen failed to start // Grid return=
 (Investigatin on going)","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage site went down because Gen fai=
led to start // Grid return (Investigatin on going)","danick.tchakouani@sag=
emcom.com","275","27-02-2025 05:30:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0004445982","M=
beng","","27-02-2025 02:11:34","27-02-2025 02:03:09","27-02-2025 04:57:09",=
"Grid outage, site went down because gen ran untill fuel shortage // Refuel=
ing done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage, site went down because gen ran untill fuel shortage // Refuelin=
g done","danick.tchakouani@sagemcom.com","506","27-02-2025 02:11:34","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004445957","M=
essassi 2","","27-02-2025 02:00:37","27-02-2025 01:58:12","27-02-2025 02:51=
:12","Site went down because 02/05 rectifiers dysfunction// He reset it: Si=
te on grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down because 02/05 rectifiers dysfunction// He re=
set it: Site on grid","danick.tchakouani@sagemcom.com","146","27-02-2025 02=
:00:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004445531","M=
efou-Assi","","27-02-2025 00:00:22","26-02-2025 23:58:55","26-02-2025 23:58=
:56","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME=
 Fulbert(654266068) from Huawei is informed","danick.tchakouani@sagemcom.co=
m","88","27-02-2025 00:00:22","Sagemcom CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0004445485","NKO=
NGKARAK","","26-02-2025 23:44:36","26-02-2025 23:18:19","27-02-2025 00:16:1=
0","Site went down because Gen started and stopped due to pierced pellet //=
 he glued the Pellet and Manually Started The Gen","TIENTCHEU NZETCHIEU GAE=
L","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Radia=
tor Leakage","Site went down because Gen started and stopped due to pierced=
 pellet // he glued the Pellet and Manually Started The Gen","danick.tchako=
uani@sagemcom.com","1578","26-02-2025 23:44:36","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004445464","Nko=
lmvack","","26-02-2025 23:36:37","26-02-2025 23:32:17","27-02-2025 00:29:16=
","Hybrid gen site.gen started and stopped due to ""high temp"" alarm//We a=
dd water and gen manually started ","Parker Tchoup","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Hybrid ge=
n site.gen started and stopped due to ""high temp"" alarm//We add water and=
 gen manually started ","danick.tchakouani@sagemcom.com","261","26-02-2025 =
23:36:37","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004445431","Mam=
bine","","26-02-2025 23:33:37","26-02-2025 23:25:50","27-02-2025 02:15:01",=
"Grid outage site went down because Gen failed to start due to Battery ge f=
aulty //Grid power return","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Generator Faulty","Grid outage site went down because Gen fai=
led to start due to Battery ge faulty //Grid power return","danick.tchakoua=
ni@sagemcom.com","468","26-02-2025 23:33:37","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004445360","Men=
dong NB","","26-02-2025 23:17:37","26-02-2025 22:53:26","26-02-2025 23:53:1=
2","Grid outage, no space to deploy a mobil gen // grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no=
 space to deploy a mobil gen // grid return","danick.tchakouani@sagemcom.co=
m","1452","26-02-2025 23:17:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004444935","M=
endong vallee","","26-02-2025 22:00:03","26-02-2025 21:21:47","26-02-2025 2=
2:29:47","Site went down due to gen Overload(20KVA; 300A) IHS F=E9lix Zamb=
=E9 is informed and confirmed//he Reduice the Load and Manually Started the=
 Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Site went down due to gen Overload(20KVA; 300A) IHS F=E9lix Zamb=E9 is =
informed and confirmed//he Reduice the Load and Manually Started the Gen","=
el-dalile@sagemcom.com","2298","26-02-2025 22:00:03","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004444872","Nko=
londom","","26-02-2025 21:48:26","26-02-2025 21:38:50","26-02-2025 21:57:50=
","Site went down because Gen fails to start due to Grid bad voltage // He =
bypass the Grid and Gen manually started","Fabrice Pouakam","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Site went down b=
ecause Gen fails to start due to Grid bad voltage // He bypass the Grid and=
 Gen manually started","yves.djomo@sagemcom.com","577","26-02-2025 21:48:26=
","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004444796","Men=
dong3","","26-02-2025 21:38:41","26-02-2025 21:31:26","26-02-2025 22:27:42"=
,"Grid outage, No space to deploy MDG //  Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage, No space to=
 deploy MDG //  Grid return","el-dalile@sagemcom.com","435","26-02-2025 21:=
38:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004444726","C=
omplexe-BEAC","","26-02-2025 21:31:11","26-02-2025 21:21:30","26-02-2025 22=
:30:30","Grid outage, site went down because gen fails to start // Grid ret=
urn (investigation ongoing)","Albran Byorel","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen f=
ails to start // Grid return (investigation ongoing)","yves.djomo@sagemcom.=
com","582","26-02-2025 21:31:11","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004444720","NYO=
M FACE MAETUR","","26-02-2025 21:29:19","26-02-2025 21:19:05","26-02-2025 2=
1:48:05","Grid outage site went down because Gen failed to start due to Gen=
 card faulty //Grid power return","Fabrice Pouakam","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage site went down because=
 Gen failed to start due to Gen card faulty //Grid power return","el-dalile=
@sagemcom.com","616","26-02-2025 21:29:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004444539","B=
ATA Mokolo OCM","","26-02-2025 21:04:56","26-02-2025 21:02:51","27-02-2025 =
00:10:03","Grid outage, no space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no =
space to deploy MDG // Grid return","yves.djomo@sagemcom.com","126","26-02-=
2025 21:04:56","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004444527","MEF=
OU ASSI","","26-02-2025 21:03:01","26-02-2025 20:59:32","27-02-2025 00:00:3=
6","Grid fluctuation, Site went down because Gen failed to start due to bad=
 voltage // He bypassed Grid and started Gen manualy","Fanda Brice","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid flu=
ctuation, Site went down because Gen failed to start due to bad voltage // =
He bypassed Grid and started Gen manualy","el-dalile@sagemcom.com","211","2=
6-02-2025 21:03:01","Sagemcom CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0004444206","Eto=
udi 2","","26-02-2025 20:02:59","26-02-2025 19:58:40","26-02-2025 20:59:40"=
,"Grid outage, site went down because gen start and stopped with over curen=
t alarm(unpruven) // Reset of gen card done and gen started(Investigation o=
ngoing)","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid outage, site went down because gen start and stopped w=
ith over curent alarm(unpruven) // Reset of gen card done and gen started(I=
nvestigation ongoing)","el-dalile@sagemcom.com","260","26-02-2025 20:02:59"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004444204","Nko=
zoa","","26-02-2025 20:01:38","26-02-2025 19:54:19","26-02-2025 20:05:28","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and gen manually star=
ted","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, site went down due to gen overload (20kva, 340A) SS HIS=
 Felix bateu is informed and confirmed// He reduced the load and gen manual=
ly started","el-dalile@sagemcom.com","4106","26-02-2025 20:01:38","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_363","NOCINC0004444196","Onangond=
i (melen bikop)","","26-02-2025 19:59:50","26-02-2025 19:47:00","26-02-2025=
 20:47:34","Cascaded Incident from TTO4494165","Fanda Brice","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","GE card found in stop mod=
e // GE put auto mode and it started by itself. ","system","317784","26-02-=
2025 19:59:50","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004444178","Mon=
tee Jouvence","","26-02-2025 19:54:49","26-02-2025 19:48:45","26-02-2025 22=
:00:37","Grid fluctuation, Site went down because Gen fails to start due to=
 Grid bad voltage // He bypass the Grid and Gen manually started","Hyemafo =
Gildas","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid fluctuation, Site went down because Gen fails to start due to Grid ba=
d voltage // He bypass the Grid and Gen manually started","yves.djomo@sagem=
com.com","364","26-02-2025 19:54:49","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004444096","Car=
refour Simbock","","26-02-2025 19:44:34","26-02-2025 19:39:21","26-02-2025 =
22:34:21","Grid fluctuation, Site went down because Gen fails to start due =
to Grid bad voltage // He bypass the Grid and Gen manually started","Hyemaf=
o Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation, Site went down because Gen fails to start due to=
 Grid bad voltage // He bypass the Grid and Gen manually started","el-dalil=
e@sagemcom.com","313","26-02-2025 19:44:34","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004444061","Men=
dong vallee","","26-02-2025 19:40:01","26-02-2025 19:35:54","26-02-2025 19:=
45:54","Site went down due to gen Overload(20KVA; 300A)   IHS F=E9lix Zamb=
=E9 is informed and confirmed//he Reduice the Load and Manually Started the=
 Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Site went down due to gen Overload(20KVA; 300A)   IHS F=E9lix Zamb=E9 i=
s informed and confirmed//he Reduice the Load and Manually Started the Gen"=
,"yves.djomo@sagemcom.com","249","26-02-2025 19:40:01","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004444018","Jou=
vence Mbenda","","26-02-2025 19:36:22","26-02-2025 19:29:08","26-02-2025 22=
:00:08","Grid fluctuation, Site went down because Gen fails to start due to=
 Grid bad voltage // He bypass the Grid and Gen manually started","Hyemafo =
Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, Site went down because Gen fails to start due to G=
rid bad voltage // He bypass the Grid and Gen manually started","yves.djomo=
@sagemcom.com","435","26-02-2025 19:36:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004443896","O=
bobogo","","26-02-2025 19:20:17","26-02-2025 19:08:11","26-02-2025 19:38:11=
","Grid outage, Site went down before Gen start due to poor backup// Grid r=
eturn","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage, Site went down before Gen start due to=
 poor backup// Grid return","yves.djomo@sagemcom.com","727","26-02-2025 19:=
20:17","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004443894","Bar=
riere","","26-02-2025 19:20:04","26-02-2025 19:06:53","26-02-2025 21:50:38"=
,"Gen Overload (20KVA, 450A) Felix Zambe confirmed (After Jouvence Mbenda) =
//  Grid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Gen Overload (20KVA, 450A) Felix Zambe confirmed (After J=
ouvence Mbenda) //  Grid return","el-dalile@sagemcom.com","792","26-02-2025=
 19:20:04","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004443884","Nom=
ayos montee Meche","","26-02-2025 19:18:29","26-02-2025 19:06:19","27-02-20=
25 00:10:23","Site went down because Gen started and stopped due emergency =
stop button was activeted// He bypassed it and started Gen manualy","Fanda =
Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Sit=
e went down because Gen started and stopped due emergency stop button was a=
ctiveted// He bypassed it and started Gen manualy","el-dalile@sagemcom.com"=
,"731","26-02-2025 19:18:29","Sagemcom CMR"
"Closed Complete","Site Down","T2795","IHS_YND_070","NOCINC0004443865","Efo=
ulan","","26-02-2025 19:17:03","26-02-2025 19:09:55","26-02-2025 19:41:00",=
"Grid fluctuation,Site went down because Gen failed to start due to grid ba=
d voltage No Rcp // He bypassed the Grid and started the Gen manually","MIN=
KA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation,Site went down because Gen failed to start due =
to grid bad voltage No Rcp // He bypassed the Grid and started the Gen manu=
ally","yves.djomo@sagemcom.com","428","26-02-2025 19:17:03","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004443837","Mel=
en Ba'aba","","26-02-2025 19:11:39","26-02-2025 19:03:18","26-02-2025 19:11=
:18","Grid outage, site went down due to gen overload(15kva, 216A), Blaise =
IHS confirm // Grid return","Siligap Boris","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, site went down due to gen overload=
(15kva, 216A), Blaise IHS confirm // Grid return","el-dalile@sagemcom.com",=
"502","26-02-2025 19:11:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004443814","M=
ontesquieux","","26-02-2025 19:03:52","26-02-2025 18:07:45","26-02-2025 20:=
02:21","Site went down due to MPR  disfunctionning SS IHS Blaise Raoul conf=
irmed // He reset it and Site is on GRID","Paul BIBOUM","Equipment Repair",=
"Passive","Rectifier","Rectifier Cabinet","Site went down due to MPR  disfu=
nctionning SS IHS Blaise Raoul confirmed // He reset it and Site is on GRID=
","yves.djomo@sagemcom.com","3368","26-02-2025 19:03:52","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004443390","Sap=
eur","","26-02-2025 18:32:02","26-02-2025 18:25:58","26-02-2025 18:43:31","=
Grid outage, Site went down before Gen start due to poor backup// Grid retu=
rn","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Battery Low","Grid outage, Site went down before Gen start due to po=
or backup// Grid return","yves.djomo@sagemcom.com","365","26-02-2025 18:32:=
02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004443241","E=
kombitie","","26-02-2025 18:14:19","26-02-2025 18:09:07","26-02-2025 20:17:=
10","Grid outage, site went down because Gen failed to start due to Grid co=
ntactor faulty // He bypassed the Grid contactor and started Gen manually",=
"Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Iss=
ue","Grid outage, site went down because Gen failed to start due to Grid co=
ntactor faulty // He bypassed the Grid contactor and started Gen manually",=
"yves.djomo@sagemcom.com","313","26-02-2025 18:14:19","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004443238","Nko=
lbong","","26-02-2025 18:13:37","26-02-2025 18:07:23","26-02-2025 18:28:52"=
,"Grid outage site went down because Gen failed to start due to Gen card Fa=
uly // Grid Restored","Delor Telezing","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage site went down because Gen failed t=
o start due to Gen card Fauly // Grid Restored","el-dalile@sagemcom.com","3=
75","26-02-2025 18:13:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004443196","E=
mana lycee 2","IHS_YND_274","26-02-2025 18:09:02","26-02-2025 17:53:57","26=
-02-2025 18:32:03","Grid fluctuation,Site went down because Gen failed to s=
tart due to grid bad voltage No Rcp // He bypassed the Grid and started the=
 Gen manually","Fabrice Pouakam","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation,Site went down because Gen=
 failed to start due to grid bad voltage No Rcp // He bypassed the Grid and=
 started the Gen manually","yves.djomo@sagemcom.com","906","26-02-2025 18:0=
9:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004443192","E=
mana Lycee","","26-02-2025 18:08:26","26-02-2025 17:53:57","26-02-2025 18:3=
2:03","Grid fluctuation,Site went down because Gen failed to start due to g=
rid bad voltage No Rcp // He bypassed the Grid and started the Gen manually=
","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid fluctuation,Site went down because Gen failed to start due to=
 grid bad voltage No Rcp // He bypassed the Grid and started the Gen manual=
ly","yves.djomo@sagemcom.com","274136","26-02-2025 18:08:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004442570","C=
rf-Nsam","","26-02-2025 16:47:13","26-02-2025 08:51:08","26-02-2025 09:00:0=
8","Active//No power issue on site Ubaie =3D52.4V site on Grid The TX FME H=
enri (699949693) from Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site Ubaie =3D52.4V site on Grid The TX FME Henri (699=
949693) from Huawei is informed","yves.djomo@sagemcom.com","28566","26-02-2=
025 16:47:13","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004442551","Obo=
bogo","","26-02-2025 16:43:26","26-02-2025 16:42:01","26-02-2025 16:48:54",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","el-dal=
ile@sagemcom.com","86","26-02-2025 16:43:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004442488","A=
ccacia New","","26-02-2025 16:34:00","26-02-2025 16:32:46","26-02-2025 17:3=
6:53","Grid outage// Grid return","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid outage// Grid return","el-dalile@sagemco=
m.com","76","26-02-2025 16:34:00","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0004442428","Bit=
oto","","26-02-2025 16:22:35","26-02-2025 16:14:21","26-02-2025 17:01:45","=
Grid outage site went down because Gen failed to start due PWC ZTE dysfonct=
ion // He reset the PWC and Gen manually started","Mba Lazare Herve","Equip=
ment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outa=
ge site went down because Gen failed to start due PWC ZTE dysfonction // He=
 reset the PWC and Gen manually started","el-dalile@sagemcom.com","495","26=
-02-2025 16:22:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004442419","B=
arriere","","26-02-2025 16:20:59","26-02-2025 16:18:35","26-02-2025 16:27:3=
7","Grid Outage Site went down due to Gen overload (20KVA, 450A) the ss IHS=
 Felix is informed//Grid Restored","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid Outage Site went down due to Gen o=
verload (20KVA, 450A) the ss IHS Felix is informed//Grid Restored","yves.dj=
omo@sagemcom.com","145","26-02-2025 16:20:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004442389","B=
iteng-Maetur","","26-02-2025 16:15:48","26-02-2025 15:59:23","26-02-2025 18=
:29:26","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// he Reduice the=
 Load and Manually Started the Gen ","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because=
 Gen started and stopped due to Gen overload(20kva, 280A) SS IHS Alphonse D=
EFFO confirmed// he Reduice the Load and Manually Started the Gen ","el-dal=
ile@sagemcom.com","986","26-02-2025 16:15:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004442148","S=
hell-Nsimeyong","","26-02-2025 15:37:06","26-02-2025 15:33:55","26-02-2025 =
15:34:00","Active//No power issue U =3D52.1V site on Grid. The FME TX Mbah =
Hosiah (674007438/699699694) from Huawei is informed.","MINKA NICOLAS","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active//No power issue U =3D52.1V site on Grid. The FME TX Mbah Hos=
iah (674007438/699699694) from Huawei is informed.","el-dalile@sagemcom.com=
","192","26-02-2025 15:37:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004442071","B=
ATA Mokolo OCM","","26-02-2025 15:20:52","26-02-2025 11:56:39","26-02-2025 =
20:32:11","Grid outage, no space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no =
space to deploy MDG // Grid return","el-dalile@sagemcom.com","12253","26-02=
-2025 15:20:52","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004441993","Lad=
a I Yde","","26-02-2025 15:03:32","26-02-2025 14:57:21","26-02-2025 16:04:1=
3","Grid fluctuation, Site went down because Gen fails  to start due to Gri=
d bad voltage and no RCP on site // He bypass the Grid and Gen manually sta=
rted","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation, Site went down because Gen fails =
 to start due to Grid bad voltage and no RCP on site // He bypass the Grid =
and Gen manually started","yves.djomo@sagemcom.com","372","26-02-2025 15:03=
:32","Sagemcom CMR"
"Cancelled","Warning","T1486","IHS_YND_683","NOCINC0004441959","BONAS YDE",=
"","26-02-2025 14:58:24","","","Site went down due to insufficience of rect=
ifier (06) RM IHS Armel BITEK is informed// He added 02 rectifiers (08)","P=
aul BIBOUM","","","","","","el-dalile@sagemcom.com","191","26-02-2025 14:58=
:24","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004441928","AKA=
K Nkozoa","","26-02-2025 14:52:51","26-02-2025 14:48:47","26-02-2025 16:24:=
34","Grid outage, Site went down because Gen failed to start with ""overcur=
rent"" alarm// He reset Gen card and started Gen manualy","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e, Site went down because Gen failed to start with ""overcurrent"" alarm// =
He reset Gen card and started Gen manualy","yves.djomo@sagemcom.com","245",=
"26-02-2025 14:52:51","Sagemcom CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0004441727","ENA=
M","","26-02-2025 14:13:27","26-02-2025 14:09:09","26-02-2025 14:12:04",": =
No power issue on site Ubaie=3D52 V  site on Grid .   The TX fme  Hosiah //=
699699694 of huawei is informed.","","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm",": No power issue on site U=
baie=3D52 V  site on Grid .   The TX fme  Hosiah //699699694 of huawei is i=
nformed.","ludovic-anselme.mouliom-mapoure@sagemcom","259","26-02-2025 14:1=
3:27","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004441683","NTU=
I TOWN","","26-02-2025 14:02:23","26-02-2025 13:54:11","26-02-2025 14:55:20=
",", Site went because Gen ran until fuel shortage//Refueling Done","Parker=
 Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage",", Site went beca=
use Gen ran until fuel shortage//Refueling Done","ludovic-anselme.mouliom-m=
apoure@sagemcom","493","26-02-2025 14:02:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0004441152","Obobogo"=
,"","26-02-2025 12:39:20","26-02-2025 11:09:19","26-02-2025 11:12:56","Casc=
aded Incident from TTO4490091","MINKA NICOLAS","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active// No power issue site on grid with =
Ubai1=3D55.1V, Site on GRID  The TX Fme Hosiah / 674007438// from huawei is=
 informed ","system","1219225","26-02-2025 12:39:20","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004440983","Mam=
bine","","26-02-2025 12:13:35","26-02-2025 12:00:20","26-02-2025 13:16:04",=
"Site went down because Gen fails to start due to hybrid system malfunction=
ning//hE RESET THE hybrid system and Gen manually started","Fanda Brice","E=
quipment Repair","Passive","Hybrid","Hybrid Module","Site went down because=
 Gen fails to start due to hybrid system malfunctionning//hE RESET THE hybr=
id system and Gen manually started","ludovic-anselme.mouliom-mapoure@sagemc=
om","3453","26-02-2025 12:13:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004440598","E=
foulan","IHS_YND_155","26-02-2025 11:19:31","26-02-2025 11:09:19","26-02-20=
25 11:45:23","Active// No power issue site on grid with Ubai1=3D55.1V, Site=
 on GRID  The TX Fme Hosiah / 674007438// from huawei is informed ","MINKA =
NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active// No power issue site on grid with Ubai1=3D55.1=
V, Site on GRID  The TX Fme Hosiah / 674007438// from huawei is informed ",=
"ludovic-anselme.mouliom-mapoure@sagemcom","613","26-02-2025 11:19:31","Sag=
emcom CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0004440483","Ako=
no","","26-02-2025 11:00:30","","","Grid outage, site went Gen ran until fu=
el shortage //Refueling done","Fanda Brice","Warning","Warning","DIESEL","W=
arning - Low Fuel Level","Grid outage, site went Gen ran until fuel shortag=
e //Refueling done","ervine.mbezele@sagemcom.com","731","26-02-2025 11:00:3=
0","Sagemcom CMR"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0004440325","Nko=
lndom","","26-02-2025 10:38:41","25-02-2025 06:11:15","25-02-2025 06:30:42"=
,"Grid outage.gen ran until fuel shortage//Refueling done (BACKTRACKING)","=
Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age.gen ran until fuel shortage//Refueling done (BACKTRACKING)","ludovic-an=
selme.mouliom-mapoure@sagemcom","102446","26-02-2025 10:38:41","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004440252","S=
IMBOCK BONAMBAPE","","26-02-2025 10:27:33","26-02-2025 10:24:28","26-02-202=
5 10:58:47","Grid outage, Site went down before Gen start due to poor backu=
p/ // Gen automatically started","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup/ // Gen automatically started","ced=
ric.tiani@sagemcom.com","187","26-02-2025 10:27:33","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004440238","Men=
dong3","","26-02-2025 10:25:33","26-02-2025 10:24:22","26-02-2025 11:35:05"=
,"Grid outage.nospace to deploy mobile gen//Grid return ","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage.nospace t=
o deploy mobile gen//Grid return ","ludovic-anselme.mouliom-mapoure@sagemco=
m","71","26-02-2025 10:25:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004440011","S=
OA UNIVERSITY STADIUM","","26-02-2025 09:54:30","26-02-2025 09:05:54","26-0=
2-2025 10:46:46","Grid outage, site went down because gen failed to start d=
ue to Pwc ZTE dysfunction// He reset it and started Gen manualy","Siligap B=
oris","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, site went down because gen failed to start due to Pwc ZTE d=
ysfunction// He reset it and started Gen manualy","ludovic-anselme.mouliom-=
mapoure@sagemcom","2917","26-02-2025 09:54:30","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004439975","Bit=
eng-Maetur","","26-02-2025 09:52:27","26-02-2025 09:18:41","26-02-2025 11:4=
1:00","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","Mb=
a Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage, Site went down because Gen started and stopped due to Gen over=
load(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","ludovic-a=
nselme.mouliom-mapoure@sagemcom","2028","26-02-2025 09:52:27","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004439901","E=
vodoula OCM","","26-02-2025 09:44:31","26-02-2025 09:38:18","26-02-2025 10:=
44:27","Grid outage.site went down due to gen failed to start//Grrid return=
 (investigation ongoing)","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage.site went down due to=
 gen failed to start//Grrid return (investigation ongoing)","ludovic-anselm=
e.mouliom-mapoure@sagemcom","374","26-02-2025 09:44:31","Sagemcom CMR"
"Closed Complete","Warning","T0636","IHS_YND_299","NOCINC0004439872","Olemb=
e MTN","","26-02-2025 09:40:40","","","grid outage, site alarm because gen =
failed to start due to grid contactor faulty // grid return","Fabrice Pouak=
am","Warning","Warning","POWER","Warning - Site on Battery","grid outage, s=
ite alarm because gen failed to start due to grid contactor faulty // grid =
return","ervine.mbezele@sagemcom.com","2529","26-02-2025 09:40:40","Sagemco=
m CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004439845","Sap=
eur","","26-02-2025 09:38:42","26-02-2025 09:34:14","26-02-2025 09:44:45","=
Grid outage, Site went down before Gen start due to poor backup/ // Gen aut=
omatically started","Mboua Thierry","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup/ // Gen automatically started","ludovic-anselme.m=
ouliom-mapoure@sagemcom","269","26-02-2025 09:38:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004439760","Eto koss=
 Yde","","26-02-2025 09:26:00","26-02-2025 09:20:50","26-02-2025 09:54:41",=
"Cascaded Incident from TTO4489106","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because gen failed to=
 start due to grid fluctuation // Gen manually started","system","275999","=
26-02-2025 09:26:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004439761","ELOUMDEM=
 CARRIERE 2","","26-02-2025 09:26:00","26-02-2025 09:20:50","26-02-2025 09:=
54:41","Cascaded Incident from TTO4489106","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because gen fa=
iled to start due to grid fluctuation // Gen manually started","system","27=
5998","26-02-2025 09:26:00","Sagemcom CMR"
"Closed Complete","Warning","T2581","IHS_YND_750","NOCINC0004439757","Nkoab=
ang entree carriere","","26-02-2025 09:25:30","","","Grid outage, site alar=
m because gen start and stopped with alarm low oil pressure // He added oil=
 pressure and gen manually started","Mba Lazare Herve","Warning","Warning",=
"POWER","Warning - Site on Battery","Grid outage, site alarm because gen st=
art and stopped with alarm low oil pressure // He added oil pressure and ge=
n manually started","ervine.mbezele@sagemcom.com","2828","26-02-2025 09:25:=
30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004439746","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","26-02-2025 09:24:24","26-02-2025 09:=
19:50","26-02-2025 09:54:41","Site went down because gen failed to start du=
e to grid fluctuation // Gen manually started","Fanda Brice","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Site went down =
because gen failed to start due to grid fluctuation // Gen manually started=
","ludovic-anselme.mouliom-mapoure@sagemcom","319","26-02-2025 09:24:24","S=
agemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004439733","Nko=
lo II New","","26-02-2025 09:21:07","26-02-2025 09:13:45","26-02-2025 09:59=
:53","Grid outage, Site went down because Gen failed to start due to PWC dy=
sfunctionning// He reset PWC, Site on Grid","Mba Lazare Herve","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, Si=
te went down because Gen failed to start due to PWC dysfunctionning// He re=
set PWC, Site on Grid","ludovic-anselme.mouliom-mapoure@sagemcom","443","26=
-02-2025 09:21:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004439704","B=
itoto","","26-02-2025 09:16:07","26-02-2025 09:03:48","26-02-2025 10:11:10"=
,"	Grid outage site went down because Gen failed to start due PWC dysfoncti=
on // He reset the PWC and Gen manually started	","Mba Lazare Herve","Equip=
ment Repair","Passive","Rectifier","Rectifier Module Overloaded","	Grid out=
age site went down because Gen failed to start due PWC dysfonction // He re=
set the PWC and Gen manually started	","ludovic-anselme.mouliom-mapoure@sag=
emcom","741","26-02-2025 09:16:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004439677","B=
arriere","","26-02-2025 09:14:18","26-02-2025 09:03:07","26-02-2025 10:32:2=
5","Gid outage site went down due to Gen Overload (20KVA, 450A) Felix Zambe=
 confirmed // Site stabilized","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Gid outage site went down due to Gen Overlo=
ad (20KVA, 450A) Felix Zambe confirmed // Site stabilized","ludovic-anselme=
.mouliom-mapoure@sagemcom","672","26-02-2025 09:14:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0004439489","B=
ONAS YDE","","26-02-2025 08:49:48","26-02-2025 08:48:14","26-02-2025 08:49:=
31","Grid fluctuation, Site went down because Gen started and stopped due t=
o Grid bad voltage// Grid stabilized","Paul BIBOUM","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site w=
ent down because Gen started and stopped due to Grid bad voltage// Grid sta=
bilized","cedric.tiani@sagemcom.com","95","26-02-2025 08:49:48","Sagemcom C=
MR"
"Closed Complete","Site Down","T0123","IHS_YND_013","NOCINC0004439138","Lab=
oratoire T.Bella","","26-02-2025 07:52:10","26-02-2025 07:50:00","26-02-202=
5 08:51:00","Grid outage.gen ran until fuel shortage//Refueling done","Paul=
 BIBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen =
ran until fuel shortage//Refueling done","ludovic-anselme.mouliom-mapoure@s=
agemcom","131","26-02-2025 07:52:10","Sagemcom CMR"
"Closed Complete","Warning","T0123","IHS_YND_013","NOCINC0004439046","Labor=
atoire T.Bella","","26-02-2025 07:33:07","","","Grid outage,site alarm Gen =
ran until fuel shortage //Refueling done","Paul BIBOUM","Warning","Warning"=
,"DIESEL","Warning - Low Fuel Level","Grid outage,site alarm Gen ran until =
fuel shortage //Refueling done","ervine.mbezele@sagemcom.com","502","26-02-=
2025 07:33:07","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004439041","Ona=
ngondi (melen bikop)","","26-02-2025 07:32:38","26-02-2025 07:01:29","26-02=
-2025 09:01:01","Grid outage.gen ran until fuel shortage//Refueling done","=
Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.=
gen ran until fuel shortage//Refueling done","ludovic-anselme.mouliom-mapou=
re@sagemcom","1870","26-02-2025 07:32:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0004438914","Nsam esc=
ale LP","","26-02-2025 07:14:21","26-02-2025 06:42:18","26-02-2025 06:58:10=
","Cascaded Incident from TTO4487909","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage site went Gen ran until fuel shor=
tage //Refueling done","system","285682","26-02-2025 07:14:21","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004438714","M=
efou-Assi","","26-02-2025 06:58:17","26-02-2025 06:54:04","26-02-2025 07:00=
:04","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME=
 Fulbert(654266068) from Huawei is informed","wilfried.kameni@sagemcom.com"=
,"255","26-02-2025 06:58:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004438693","N=
kolbong","","26-02-2025 06:51:35","26-02-2025 06:47:26","26-02-2025 07:43:2=
3","Grid outage.gen failed to start due to card GE dysfunctionning//We rese=
t card GE and gen manually started ","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to start =
due to card GE dysfunctionning//We reset card GE and gen manually started "=
,"ludovic-anselme.mouliom-mapoure@sagemcom","250","26-02-2025 06:51:35","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0004438674","Nsa=
m Sofavinc","IHS_YND_732","26-02-2025 06:45:29","26-02-2025 06:42:18","26-0=
2-2025 06:58:10","Grid outage site went Gen ran until fuel shortage //Refue=
ling done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage site went Gen ran until fuel shortage //Refueling done","ludo=
vic-anselme.mouliom-mapoure@sagemcom","192","26-02-2025 06:45:29","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004438612","A=
ccacia New","","26-02-2025 06:29:25","26-02-2025 06:22:11","26-02-2025 06:2=
3:41","No power issue site on grid with U=3D53.2v Mbah Osiah(674007438) fro=
m Huawei is informed ","","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D=
53.2v Mbah Osiah(674007438) from Huawei is informed ","wilfried.kameni@sage=
mcom.com","435","26-02-2025 06:29:25","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0004438608","EBO=
M","","26-02-2025 06:28:49","26-02-2025 06:22:40","26-02-2025 08:38:37"," G=
rid outage site went Gen ran until fuel shortage //Refueling done","Hyemafo=
 Gildas","Fuel Outage","Passive","Diesel","Diesel Outage"," Grid outage sit=
e went Gen ran until fuel shortage //Refueling done","ludovic-anselme.mouli=
om-mapoure@sagemcom","440","26-02-2025 06:28:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004438607","D=
amas","","26-02-2025 06:28:35","26-02-2025 06:23:22","26-02-2025 07:45:11",=
"	Grid outage.gen failed to start due to battery GE faulty//Gen manually st=
arted with external battery","MINKA NICOLAS","Equipment Repair","Passive","=
ACDG Gen","ACDG - Generator Battery","	Grid outage.gen failed to start due =
to battery GE faulty//Gen manually started with external battery","wilfried=
.kameni@sagemcom.com","314","26-02-2025 06:28:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004438604","M=
ontee-Jouvence-II","","26-02-2025 06:27:44","26-02-2025 06:23:32","26-02-20=
25 06:24:03","ACTIVE// No  power issue on site, site on Grid with Ubaie=3D =
54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed.","Hyema=
fo Gildas","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","ACTIVE// No  power issue on site, site on Grid with =
Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed=
.","wilfried.kameni@sagemcom.com","253","26-02-2025 06:27:44","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004438430","O=
LAMA","","26-02-2025 05:45:15","26-02-2025 05:36:08","26-02-2025 07:06:45",=
"Grid outage site went Gen ran until fuel shortage //Refueling done","Fanda=
 Brice","Fuel Outage","Passive","Diesel","Diesel Outage","     Grid outage =
site went Gen ran until fuel shortage //Refueling done","wilfried.kameni@sa=
gemcom.com","548","26-02-2025 05:45:15","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004438395","Eko=
mbitie","","26-02-2025 05:32:27","26-02-2025 05:29:17","26-02-2025 06:21:45=
","	Grid outage, site went down because Gen failed to start due to Grid con=
tactor faulty // He bypassed the Grid contactor and started Gen manually","=
Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issu=
e","	Grid outage, site went down because Gen failed to start due to Grid co=
ntactor faulty // He bypassed the Grid contactor and started Gen manually",=
"wilfried.kameni@sagemcom.com","210","26-02-2025 05:32:27","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004438373","Ema=
na","","26-02-2025 05:20:29","26-02-2025 05:09:22","26-02-2025 05:21:39","G=
rid outage, site went down before gen start due to poor battery backup // G=
en started automatically","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","wi=
lfried.kameni@sagemcom.com","668","26-02-2025 05:20:29","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004438161","Abo=
me","","26-02-2025 03:30:57","26-02-2025 03:27:47","26-02-2025 04:43:46","G=
rid outage.gen failed to start due to fuel shortage//Refueling done","MINKA=
 NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen=
 failed to start due to fuel shortage//Refueling done","wilfried.kameni@sag=
emcom.com","216","26-02-2025 03:30:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004438144","M=
ambine","","26-02-2025 03:26:33","26-02-2025 03:22:27","26-02-2025 03:40:27=
","Site went down because Gen failed to start due to hybrid system malfunct=
ionning//hE RESET THE hybrid system and Gen manually started","Fanda Brice"=
,"Equipment Repair","Passive","Hybrid","Hybrid Module","Site went down beca=
use Gen failed to start due to hybrid system malfunctionning//hE RESET THE =
hybrid system and Gen manually started","wilfried.kameni@sagemcom.com","247=
","26-02-2025 03:26:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004437973","M=
efou-Assi","","26-02-2025 02:42:08","26-02-2025 02:38:02","26-02-2025 02:43=
:49","No power issue on site Ubaie=3D54.5V site On Grid.The Tx FME Fulbert =
(654266068) from Huawei is informed. ","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site Ubaie=3D54.5V site On Grid.The Tx FME Fulbert (654266068) from=
 Huawei is informed. ","wilfried.kameni@sagemcom.com","247","26-02-2025 02:=
42:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004437930","C=
rf-Nsam","","26-02-2025 02:24:45","26-02-2025 02:20:48","26-02-2025 08:50:2=
8","Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline is=
 informed and confirmed // Site stabilized. Power issue resolved at 08:50 A=
M but site remains down The Tx FME Hugo (699949693) fr","MINKA NICOLAS","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site w=
ent down because PWC(24kilo) dysfunctionning, IHS SS Pascaline is informed =
and confirmed // Site stabilized. Power issue resolved at 08:50 AM but site=
 remains down The Tx FME Hugo (699949693) from Huawei is informed","wilfrie=
d.kameni@sagemcom.com","6574","26-02-2025 02:24:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004437916","S=
calom-IHS","","26-02-2025 02:18:44","26-02-2025 02:17:36","26-02-2025 02:24=
:44","No power issue, site on Grid with U=3D52.5V.The TX Fme Hosiah (674007=
438) from Huawei is informed. ","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue, site on Grid=
 with U=3D52.5V.The TX Fme Hosiah (674007438) from Huawei is informed. ","w=
ilfried.kameni@sagemcom.com","70","26-02-2025 02:18:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004437858","S=
hell-Nsimeyong","","26-02-2025 02:05:44","26-02-2025 02:00:36","26-02-2025 =
02:10:13","no power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no=
 power issue U =3D52.2V site on Grid.The FME TX Mbah Hosiah (674007438/6996=
99694) from Huawei is informed","wilfried.kameni@sagemcom.com","309","26-02=
-2025 02:05:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004437856","E=
foulan","","26-02-2025 02:04:55","26-02-2025 01:56:48","26-02-2025 02:00:09=
","Active// No power issue site on grid with Ubai1=3D55.1V, Site on GRID  T=
he TX Fme Hosiah / 674007438// from huawei is informed by sms","MINKA NICOL=
AS","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// No power issue site on grid with Ubai1=3D55.1V, Si=
te on GRID  The TX Fme Hosiah / 674007438// from huawei is informed by sms"=
,"wilfried.kameni@sagemcom.com","488","26-02-2025 02:04:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004437855","S=
calom","","26-02-2025 02:04:54","26-02-2025 01:56:48","26-02-2025 03:31:57"=
,"No power issue , Ubaie=3D54.5 V site on GRID.The FME TX Mbah Hosiah (6740=
07438) from Huawei is informed.","Paul BIBOUM","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue ,=
 Ubaie=3D54.5 V site on GRID.The FME TX Mbah Hosiah (674007438) from Huawei=
 is informed.","wilfried.kameni@sagemcom.com","487","26-02-2025 02:04:54","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004437853","O=
bobogo","","26-02-2025 02:03:41","26-02-2025 01:56:23","26-02-2025 03:23:41=
","Active// No power issue site on grid with Ubai1=3D54.9V, Ubai2=3D53.5V S=
ite on Gen   The TX Fme Hosiah / 674007438// from huawei is informed by sms=
","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active// No power issue site on grid with Uba=
i1=3D54.9V, Ubai2=3D53.5V Site on Gen  The TX Fme Hosiah / 674007438// from=
 huawei is informed by sms
","wilfried.kameni@sagemcom.com","439","26-02-2025 02:03:41","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004437734","Bon=
djock","","26-02-2025 01:09:42","26-02-2025 01:01:34","26-02-2025 03:14:57"=
,"Grid outage.Gen failed to starrt due to automation malfunctionning//Gen m=
anually started","Fanda Brice","Equipment Repair","Passive","Control Panel"=
,"ATS-AMF Issue","Grid outage.Gen failed to starrt due to automation malfun=
ctionning//Gen manually started","wilfried.kameni@sagemcom.com","489","26-0=
2-2025 01:09:42","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004437223","Nom=
ayos montee Meche","","25-02-2025 23:14:55","25-02-2025 23:11:48","25-02-20=
25 23:12:46","No power issue site on grid with U=3D53v Flubert(654266068) f=
rom Huawei is informed ","Fanda Brice","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D53v Flubert(654266068) from Huawei is informed ","wilfried.kam=
eni@sagemcom.com","188","25-02-2025 23:14:55","Sagemcom CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0004437170","Eto=
udi 2","","25-02-2025 22:56:57","25-02-2025 22:49:45","25-02-2025 23:41:24"=
,"Grid outage, site went down because Gen start and stopped with alarm  Gen=
 Over voltage // He reset Gen card and Gen manually started","Fabrice Pouak=
am","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Grid out=
age, site went down because Gen start and stopped with alarm  Gen Over volt=
age // He reset Gen card and Gen manually started","wilfried.kameni@sagemco=
m.com","6347","25-02-2025 22:56:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004437148","M=
ontee-Jouvence-II","","25-02-2025 22:51:51","25-02-2025 22:49:44","26-02-20=
25 00:11:23","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed // Site stabilized","Hyemafo Gildas","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Site went down due to P=
WC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site stabilized"=
,"wilfried.kameni@sagemcom.com","128","25-02-2025 22:51:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004436874","B=
iteng-Maetur","","25-02-2025 21:53:49","25-02-2025 21:44:00","25-02-2025 22=
:11:00","","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Gen:20kva
load:300A
Site indoor
","danick.tchakouani@sagemcom.com","647","25-02-2025 21:53:49","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0004436836","Eloumdem=
 stade","","25-02-2025 21:48:11","25-02-2025 21:40:43","26-02-2025 00:01:08=
","Site went down due to insufficiency of rectifier due to load increase, I=
HS SS FELIX ZAMBE is confirmed// Site stabilized","Fanda Brice","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down due to ins=
ufficiency of rectifier due to load increase, IHS SS FELIX ZAMBE is confirm=
ed// Site stabilized","system","448","25-02-2025 21:48:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004436834","Eto koss=
 Yde","","25-02-2025 21:48:10","25-02-2025 21:40:43","25-02-2025 23:54:59",=
"Cascaded Incident from TTO4485745","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down Insufficiency of reti=
fier on site SS IHS Felix Zamb=E9 is informed and confirmed //Site stabiliz=
ed","system","289175","25-02-2025 21:48:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004436835","ELOUMDEM=
 CARRIERE 2","","25-02-2025 21:48:10","25-02-2025 21:40:43","25-02-2025 23:=
54:59","Cascaded Incident from TTO4485745","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down Insufficiency =
of retifier on site SS IHS Felix Zamb=E9 is informed and confirmed //Site s=
tabilized","system","289175","25-02-2025 21:48:10","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004436819","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","25-02-2025 21:46:50","25-02-2025 21:40=
:43","25-02-2025 23:54:59","Site went down Insufficiency of retifier on sit=
e SS IHS Felix Zamb=E9 is informed and confirmed //Site stabilized","Fanda =
Brice","Equipment Repair","Passive","Rectifier","Rectifier Module","Site we=
nt down Insufficiency of retifier on site SS IHS Felix Zamb=E9 is informed =
and confirmed //Site stabilized","danick.tchakouani@sagemcom.com","369","25=
-02-2025 21:46:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_115","NOCINC0004436689","Labogeni=
e","IHS_YND_568","25-02-2025 21:41:20","25-02-2025 21:23:28","26-02-2025 07=
:02:03","Grid outage.no space to deploy mobile gen//grid power ","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no=
 space to deploy mobile gen//grid power ","system","1072","25-02-2025 21:41=
:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004436647","B=
itoto","","25-02-2025 21:38:26","25-02-2025 21:35:19","25-02-2025 22:35:24"=
,"Grid outage site went down because Gen failed to start due PWC dysfonctio=
n // He reset the PWC and Gen manually started","Mba Lazare Herve","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage=
 site went down because Gen failed to start due PWC dysfonction // He reset=
 the PWC and Gen manually started","danick.tchakouani@sagemcom.com","189","=
25-02-2025 21:38:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0004436576","A=
nguissa New","","25-02-2025 21:32:41","25-02-2025 21:23:28","26-02-2025 07:=
02:03","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage.no space to deploy mobile gen//grid power ","mar=
iam.tchonang@sagemcom.com","312118","25-02-2025 21:32:41","Sagemcom CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0004436574","Car=
refour Ayissi Ele","","25-02-2025 21:31:50","25-02-2025 21:29:39","25-02-20=
25 21:31:39","No power issue site on battery with U=3D49v Gregoire(65207065=
8) from  Huawei is informed ","Parker Tchoup","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on battery with U=3D49v Gregoire(652070658) from  Huawei is informed ","=
danick.tchakouani@sagemcom.com","132","25-02-2025 21:31:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004436448","S=
calom-IHS","","25-02-2025 21:15:46","25-02-2025 21:14:59","25-02-2025 21:20=
:42","No power issue, site on Grid with U=3D52..5 V.  The TX Fme Hosiah (67=
4007438) from Huawei is informed. ","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site on =
Grid with U=3D52..5 V.  The TX Fme Hosiah (674007438) from Huawei is inform=
ed","mariam.tchonang@sagemcom.com","49","25-02-2025 21:15:46","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_259","NOCINC0004436356","Simbock =
MTN","","25-02-2025 20:59:40","25-02-2025 20:47:39","25-02-2025 21:07:44","=
Cascaded Incident from TTO4485191","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down before ge=
n start due to poor batterie backup // Gen start automatically","system","2=
63752","25-02-2025 20:59:40","Sagemcom CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0004436333","Sim=
bock Maetur","IHS_YND_259","25-02-2025 20:56:45","25-02-2025 20:47:39","25-=
02-2025 21:07:44","Grid outage, site went down before gen start due to poor=
 batterie backup // Gen start automatically","Hyemafo Gildas","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,=
 site went down before gen start due to poor batterie backup // Gen start a=
utomatically","danick.tchakouani@sagemcom.com","546","25-02-2025 20:56:45",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004436324","ELOUMDEM=
 CARRIERE 2","","25-02-2025 20:55:41","25-02-2025 20:50:38","25-02-2025 20:=
58:17","Cascaded Incident from TTO4485168","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup// Grid power return","system","303","25-=
02-2025 20:55:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004436323","Eto koss=
 Yde","","25-02-2025 20:55:40","25-02-2025 20:50:38","25-02-2025 20:58:17",=
"Cascaded Incident from TTO4485168","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup// Grid power return","system","302","25-02-2025=
 20:55:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004436313","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","25-02-2025 20:53:45","25-02-2025 20:=
48:38","25-02-2025 20:58:47","Grid outage, Site went down before Gen start =
due to poor backup// Grid power return","Fanda Brice","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site we=
nt down before Gen start due to poor backup// Grid power return","danick.tc=
hakouani@sagemcom.com","309","25-02-2025 20:53:45","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004436285","NYO=
M FACE MAETUR","","25-02-2025 20:47:49","25-02-2025 20:40:23","25-02-2025 2=
1:24:18","Grid fluctuation, site went down because Gen failed to start due =
to Grid bad voltage and No RCP // Grid stabilized","Fabrice Pouakam","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation, site went down because Gen failed to start due to Grid bad volta=
ge and No RCP // Grid stabilized","danick.tchakouani@sagemcom.com","447","2=
5-02-2025 20:47:49","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004436047","NYO=
M 2 IHS","","25-02-2025 20:09:50","25-02-2025 20:05:45","25-02-2025 20:13:4=
5","Site went down because the Cb(80A) of DCbox dysjuncted due to Grid bad =
voltage // He reamed the cb","Fabrice Pouakam","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down be=
cause the Cb(80A) of DCbox dysjuncted due to Grid bad voltage // He reamed =
the cb","danick.tchakouani@sagemcom.com","246","25-02-2025 20:09:50","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_259","NOCINC0004436019","Simbock =
MTN","","25-02-2025 20:04:31","25-02-2025 19:56:11","25-02-2025 20:20:46","=
Cascaded Incident from TTO4484822","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site on gen due to grid outage: grid =
return, site went down due to poor battery backup // grid return","system",=
"1216371","25-02-2025 20:04:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_520","NOCINC0004436018","SIMBOCK =
BONAMBAPE","","25-02-2025 20:04:30","25-02-2025 19:56:11","25-02-2025 20:20=
:46","Cascaded Incident from TTO4484822","Hyemafo Gildas","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site on gen due to grid outa=
ge: grid return, site went down due to poor battery backup // grid return",=
"system","1216370","25-02-2025 20:04:30","Sagemcom CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0004436009","Sim=
bock Maetur","IHS_YND_520, IHS_YND_259","25-02-2025 20:03:22","25-02-2025 1=
9:56:11","25-02-2025 20:20:46","Site on gen due to grid outage: grid return=
, site went down due to poor battery backup // grid return","Hyemafo Gildas=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low=
","Site on gen due to grid outage: grid return, site went down due to poor =
battery backup // grid return","danick.tchakouani@sagemcom.com","432","25-0=
2-2025 20:03:22","Sagemcom CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004435924","Odz=
a petit marche new","","25-02-2025 19:46:24","25-02-2025 19:39:08","25-02-2=
025 20:13:08","Grid outage, Site went down because Gen stopped with alarm l=
ow oil pressure(not unproven)//He reset it and started Manually the Gen","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","Grid outage, Site went down because Gen stopped with alarm low oil press=
ure(not unproven)//He reset it and started Manually the Gen","danick.tchako=
uani@sagemcom.com","437","25-02-2025 19:46:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0004435892","G=
SO","","25-02-2025 19:41:46","25-02-2025 19:39:31","25-02-2025 19:41:49","N=
o  power issue U =3D54,5V site on Grid.   The Tx FME  Eloundou (652586578 )=
from Huawei is informed.","MINKA NICOLAS","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No  power issue U =3D=
54,5V site on Grid.   The Tx FME  Eloundou (652586578 )from Huawei is infor=
med.","mariam.tchonang@sagemcom.com","136","25-02-2025 19:41:46","Sagemcom =
CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004435820","Elo=
umdem stade","","25-02-2025 19:31:08","25-02-2025 19:22:40","25-02-2025 21:=
00:04","Grid fluctuation, site went down because Gen start and stopped due =
Grid bad voltage  // He bypassed Grid and started Gen manually","Fanda Bric=
e","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, site went down because Gen start and stopped due Grid b=
ad voltage  // He bypassed Grid and started Gen manually","danick.tchakouan=
i@sagemcom.com","509","25-02-2025 19:31:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004435726","M=
elen Ba'aba","","25-02-2025 19:13:31","25-02-2025 19:11:19","25-02-2025 22:=
43:21","Grid outage, site went down due to gen overload(15kva, 216A), Blais=
e IHS confirm  // Site stabilized","Siligap Boris","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen o=
verload(15kva, 216A), Blaise IHS confirm  // Site stabilized","mariam.tchon=
ang@sagemcom.com","133","25-02-2025 19:13:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004435672","E=
kombitie","","25-02-2025 19:04:43","25-02-2025 19:01:30","25-02-2025 20:49:=
30","Grid outage, site went down because Gen failed to start due to Grid co=
ntactor faulty // He bypassed the Grid contactor and started Gen manually",=
"Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Iss=
ue","Grid outage, site went down because Gen failed to start due to Grid co=
ntactor faulty // He bypassed the Grid contactor and started Gen manually",=
"danick.tchakouani@sagemcom.com","194","25-02-2025 19:04:43","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004435632","Aka=
k-Nkozoa-MTN-IHS","","25-02-2025 18:56:06","25-02-2025 18:49:56","25-02-202=
5 19:05:06","Site went down because Gen failed to start due to Grid bad vol=
tage  // Grid stabilized","Fabrice Pouakam","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Site went down because Gen faile=
d to start due to Grid bad voltage  // Grid stabilized","danick.tchakouani@=
sagemcom.com","372","25-02-2025 18:56:06","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004435593","Mon=
tee Jouvence","","25-02-2025 18:44:59","25-02-2025 18:38:50","25-02-2025 19=
:04:06","Grid outage, Site went down because gen start and stopped with ala=
rm""  High temps""// he added water and manually start the gen","Hyemafo Gi=
ldas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Co=
olant Level Issue","Grid outage, Site went down because gen start and stopp=
ed with alarm""  High temps ""// he added water and manually start the gen"=
,"danick.tchakouani@sagemcom.com","370","25-02-2025 18:44:59","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004435443","Mimboman=
4","","25-02-2025 18:19:20","25-02-2025 18:11:30","25-02-2025 18:11:31","Ca=
scaded Incident from TTO4484164","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on Gen with U=3D5=
2.2V The FME Tx Lionel Steve /655184876/ From huawei is informed.","system"=
,"265952","25-02-2025 18:19:20","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004435441","Nko=
lo II New","IHS_YND_266","25-02-2025 18:18:53","25-02-2025 18:11:30","25-02=
-2025 18:11:31","No power issue site on Gen with U=3D52.2V The FME Tx Lione=
l Steve /655184876/ From huawei is informed.","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue site on Gen with U=3D52.2V The FME Tx Lionel Steve /655184=
876/ From huawei is informed.","danick.tchakouani@sagemcom.com","445","25-0=
2-2025 18:18:53","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004435336","EMA=
NA BILICK CITY","","25-02-2025 18:06:26","25-02-2025 18:01:10","25-02-2025 =
21:25:48","Grid outage Site went down because Landlord forbidden to start t=
he Gen due to Noise  //Grid return","Fabrice Pouakam","Equipment Repair","P=
assive","ACDG Gen","ACDG - Emergency Stop","Grid outage Site went down beca=
use Landlord forbidden to start the Gen due to Noise  //Grid return","danic=
k.tchakouani@sagemcom.com","318","25-02-2025 18:06:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_159","NOCINC0004435301","Complexe=
-BEAC","","25-02-2025 17:59:21","25-02-2025 17:50:38","25-02-2025 18:26:17"=
,"Cascaded Incident from TTO4484003","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to disjunction=
 of CB(125A) in PWC // CB put back on","system","274461","25-02-2025 17:59:=
21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004435297","E=
kie-Elegance","IHS_YND_159","25-02-2025 17:58:45","25-02-2025 17:50:38","25=
-02-2025 18:26:17","Site went down due to disjunction of CB(125A) in PWC //=
 CB put back on","Albran Byorel","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Circuit Breaker Issue","Site went down due to disjuncti=
on of CB(125A) in PWC // CB put back on","danick.tchakouani@sagemcom.com","=
487","25-02-2025 17:58:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0004435234","C=
NDH","","25-02-2025 17:49:18","25-02-2025 17:47:01","25-02-2025 17:47:02","=
No power issue on site U=3D54,1v site on grid Brice Tsague of huawei is inf=
ormed","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,1v site on g=
rid Brice Tsague of huawei is informed","mariam.tchonang@sagemcom.com","138=
","25-02-2025 17:49:18","Sagemcom CMR"
"Closed Complete","Site Down","T1107-1","IHS_YND_217","NOCINC0004434900","A=
bom","","25-02-2025 17:35:54","25-02-2025 17:28:43","25-02-2025 17:35:34","=
No power issue on site ,site on Grid  The Team augustin// 655989322 from E-=
ingeniering is working on site  (swap the transmission)","Siligap Boris","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site ,site on Grid  The Team augustin// 6559893=
22 from E-ingeniering is working on site  (swap the transmission)","danick.=
tchakouani@sagemcom.com","432","25-02-2025 17:35:54","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004434778","Ngo=
a Ekelle","","25-02-2025 17:17:25","25-02-2025 17:15:12","25-02-2025 17:21:=
12","Grid outage, Site went down before Gen start due to poor backup/ // Ge=
n automatically started","Paul BIBOUM","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup/ // Gen automatically started","danick.tchakou=
ani@sagemcom.com","134","25-02-2025 17:17:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004434743","E=
MANA BILICK CITY","","25-02-2025 17:11:52","25-02-2025 17:09:30","25-02-202=
5 17:14:58","Active//No power issue on site Ubaie =3D53.4V site on Grid The=
 TX FME Synphorien (650257151) from Huawei is informed","Fabrice Pouakam","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site Ubaie =3D53.4V site on Grid The T=
X FME Synphorien (650257151) from Huawei is informed","mariam.tchonang@sage=
mcom.com","143","25-02-2025 17:11:52","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004434718","Jou=
vence Mbenda","","25-02-2025 17:08:57","25-02-2025 17:06:42","25-02-2025 17=
:54:18","Grid outage, Site went down because Gen fails to start due to  Bat=
tery Gen discharged  // Gen manually started with external battery","Hyemaf=
o Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery=
","Grid outage, Site went down because Gen fails to start due to  Battery G=
en discharged  // Gen manually started with external battery","danick.tchak=
ouani@sagemcom.com","136","25-02-2025 17:08:57","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004434710","SIM=
BOCK BONAMBAPE","","25-02-2025 17:07:29","25-02-2025 17:05:21","25-02-2025 =
17:24:21","Grid outage, Site went down because Gen started and stopped due =
to Gen overload(20kva, 380A) SS IHS Alphonse DEFFO confirmed.// He reduiced=
 load and started Gen manualy","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen sta=
rted and stopped due to Gen overload(20kva, 380A) SS IHS Alphonse DEFFO con=
firmed.// He reduiced load and started Gen manualy","danick.tchakouani@sage=
mcom.com","128","25-02-2025 17:07:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004434588","B=
ATA Mokolo OCM","","25-02-2025 16:52:55","25-02-2025 16:32:35","25-02-2025 =
18:25:35","Gri outage, no space to deploy a mobile gen  // Grid return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri out=
age, no space to deploy a mobile gen  // Grid return","danick.tchakouani@sa=
gemcom.com","1221","25-02-2025 16:52:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004434463","Bondjock=
","","25-02-2025 16:33:21","25-02-2025 16:22:11","25-02-2025 16:34:38","Cas=
caded Incident from TTO4483022","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to work our Technicia=
n  Brice Fanda 657108549//Sagemcom, (  doing PM) // Enf of work","system","=
265313","25-02-2025 16:33:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0004434462","Nkoabang=
2","","25-02-2025 16:33:21","25-02-2025 16:22:11","25-02-2025 16:34:38","Gr=
id outage, Site went down because Gen stopped due to overload(20kva, 300A) =
SS IHS Alphonse Deffo is confirmed  // Grid Restored","Mba Lazare Herve","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went down due=
 to work our Technician  Brice Fanda 657108549//Sagemcom, (  doing PM) // E=
nf of work","system","670","25-02-2025 16:33:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004434461","Mbeng","=
","25-02-2025 16:33:20","25-02-2025 16:22:11","25-02-2025 16:34:38","Cascad=
ed Incident from TTO4483022","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to work our Technician  =
Brice Fanda 657108549//Sagemcom, (  doing PM) // Enf of work","system","265=
314","25-02-2025 16:33:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004434438","M=
om","IHS_YND_369, IHS_YND_372","25-02-2025 16:30:22","25-02-2025 16:22:11",=
"25-02-2025 16:34:38","Site went down due to work our Technician  Brice Fan=
da 657108549//Sagemcom, (  doing PM) // Enf of work","Fanda Brice","Equipme=
nt Replacement","Passive","Planned Activity","Planned Activity - Passive","=
Site went down due to work our Technician  Brice Fanda 657108549//Sagemcom,=
 (  doing PM) // Enf of work","mariam.tchonang@sagemcom.com","492","25-02-2=
025 16:30:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004434303","B=
arriere","","25-02-2025 16:17:53","25-02-2025 16:14:41","25-02-2025 21:59:3=
7","Gid outage site went down due to Gen Overload (20KVA, 450A) Felix Zambe=
 confirmed // Site stabilized","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Gid outage site went down due to Gen Overlo=
ad (20KVA, 450A) Felix Zambe confirmed // Site stabilized","mariam.tchonang=
@sagemcom.com","193","25-02-2025 16:17:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004434230","M=
efou-Assi","","25-02-2025 16:06:55","25-02-2025 16:03:25","25-02-2025 16:10=
:23","No power issue on site Ubaie=3D54.5V site On Grid.  The Tx FME Fulber=
t (654266068) from Huawei is informed. Repetitive issue","Fanda Brice","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue on site Ubaie=3D54.5V site On Grid.The Tx FME Fulber=
t (654266068) from Huawei is informed. Repetitive issue","danick.tchakouani=
@sagemcom.com","211","25-02-2025 16:06:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004434184","M=
ontesquieux","","25-02-2025 15:58:19","25-02-2025 15:57:14","25-02-2025 15:=
58:05","Site went down due to mpr dysfunction disfunctionning SS IHS Blaise=
 Raoul confirmed // Site stabilized","Paul BIBOUM","Equipment Repair","Pass=
ive","Rectifier","Rectifier Cabinet","Site went down due to mpr dysfunction=
 disfunctionning SS IHS Blaise Raoul confirmed // Site stabilized","danick.=
tchakouani@sagemcom.com","66","25-02-2025 15:58:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004434176","M=
vog-Manga","","25-02-2025 15:56:25","25-02-2025 15:49:17","25-02-2025 16:27=
:27","Grid outage, site went down because gen start and stopped with high t=
emp alarm // He oppened the doors","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","Gen Temp High","Grid outage, site went down because gen st=
art and stopped with high temp alarm // He oppened the doors","danick.tchak=
ouani@sagemcom.com","430","25-02-2025 15:56:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004434116","N=
goulmekong-Nord","","25-02-2025 15:52:52","25-02-2025 15:49:38","25-02-2025=
 15:49:39","Error","Siligap Boris","Incorrectly Logged Tickets","Error","Er=
ror","Error","Error","danick.tchakouani@sagemcom.com","195","25-02-2025 15:=
52:52","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004434099","Tou=
ring Club International","","25-02-2025 15:51:29","25-02-2025 15:49:58","25=
-02-2025 16:31:27","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed// He reduced load and started Gen manualy"=
,"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid Outage Site went down because Gen overload (20Kw, 270A) SS IHS Pascal=
ine confirmed// He reduced load and started Gen manualy","danick.tchakouani=
@sagemcom.com","92","25-02-2025 15:51:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0004434045","H=
-Prince","","25-02-2025 15:43:06","25-02-2025 15:30:54","25-02-2025 16:53:4=
2","Grid outage, site went down because gen fails to start due to grid cont=
actor faulty //  He bypassed it and started Gen manually ","Mboua Thierry",=
"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, =
site went down because gen fails to start due to grid contactor faulty //  =
He bypassed it and started Gen manually ","danick.tchakouani@sagemcom.com",=
"733","25-02-2025 15:43:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0004433784","Mendong =
vallee","","25-02-2025 15:03:10","25-02-2025 14:53:20","25-02-2025 15:35:51=
","Cascaded Incident from TTO4482249","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen start and stopped with high temp alarm // He added water and manually=
 start the gen","system","270716","25-02-2025 15:03:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0004433785","Mendong =
Maeture","","25-02-2025 15:03:10","25-02-2025 14:53:20","25-02-2025 15:35:5=
1","Cascaded Incident from TTO4482249","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause gen start and stopped with high temp alarm // He added water and manu=
ally start the gen","system","270716","25-02-2025 15:03:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0004433776","B=
ONAS YDE","","25-02-2025 15:02:03","25-02-2025 15:00:57","25-02-2025 15:11:=
57","Grid fluctuation, Site went down because Gen started and stopped due t=
o Grid bad voltage// Grid stabilized","Paul BIBOUM","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site w=
ent down because Gen started and stopped due to Grid bad voltage// Grid sta=
bilized","mariam.tchonang@sagemcom.com","67","25-02-2025 15:02:03","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004433760","M=
endong","IHS_YND_692, IHS_YND_569","25-02-2025 14:59:26","25-02-2025 14:53:=
20","25-02-2025 15:35:51","Grid outage, site went down because gen start an=
d stopped with high temp alarm // He added water and manually start the gen=
","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Eng=
ine Temp - Coolant Level Issue","Grid outage, site went down because gen st=
art and stopped with high temp alarm // He added water and manually start t=
he gen","danick.tchakouani@sagemcom.com","367","25-02-2025 14:59:26","Sagem=
com CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004433155","Mel=
en Ba'aba","","25-02-2025 14:21:28","25-02-2025 14:15:24","25-02-2025 14:15=
:25","No ACTIVE // Active// No power issue, site is on GEN with Ubaie=3D54,=
4 V TX FME Julien(693095849) from Huawei is informed","Siligap Boris","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No ACTIVE // Active// No power issue, site is on GEN with Ubaie=3D54=
,4 V TX FME Julien(693095849) from Huawei is informed","yves.djomo@sagemcom=
.com","365","25-02-2025 14:21:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0004433143","Carrefou=
rt Nkomo","","25-02-2025 14:19:06","25-02-2025 12:58:12","25-02-2025 13:21:=
29","Cascaded Incident from TTO4481030","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 because Gen start and stopped with  Alarm ""high temp "" // he added water=
 and manually start the gen","system","277641","25-02-2025 14:19:06","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004433041","B=
ATA Mokolo OCM","","25-02-2025 14:07:52","25-02-2025 13:24:35","25-02-2025 =
15:15:35","Grid outage.no space to deploy mobile gen//Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.=
no space to deploy mobile gen//Grid return","ludovic-anselme.mouliom-mapour=
e@sagemcom","2598","25-02-2025 14:07:52","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004433031","Abo=
me","","25-02-2025 14:05:24","25-02-2025 14:00:11","25-02-2025 14:52:11","G=
rid outage, Site went down because Gen ran until fuel shortage// Refueling =
Done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage","Gri=
d outage, Site went down because Gen ran until fuel shortage// Refueling Do=
ne","ludovic-anselme.mouliom-mapoure@sagemcom","2803","25-02-2025 14:05:24"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004432910","M=
ontee-Anne-Rouge","","25-02-2025 13:43:43","25-02-2025 13:23:36","26-02-202=
5 10:11:10"," Grid outage, No space to deploy MDG // Grid Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"," Grid ou=
tage, No space to deploy MDG // Grid Grid return","ludovic-anselme.mouliom-=
mapoure@sagemcom","1208","25-02-2025 13:43:43","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004432824","Mon=
tee-Jouvence-II","","25-02-2025 13:32:18","25-02-2025 13:17:39","25-02-2025=
 15:09:29","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix Za=
mb=E9 confirmed // Site stabilized","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Site went down due to PWC=
 Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site stabilized","=
yves.djomo@sagemcom.com","880","25-02-2025 13:32:18","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004432694","Ona=
ngondi (melen bikop)","","25-02-2025 13:11:28","25-02-2025 13:07:09","25-02=
-2025 13:31:15","Hybrid gen site.site went down due to hybrid system malfun=
ctionning // Gen manually started","Fanda Brice","Equipment Repair","Passiv=
e","Hybrid","Hybrid Module","Hybrid gen site.site went down due to hybrid s=
ystem malfunctionning // Gen manually started","ludovic-anselme.mouliom-map=
oure@sagemcom","260","25-02-2025 13:11:28","Sagemcom CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004432685","Emo=
mbo Esssomba","","25-02-2025 13:10:05","25-02-2025 13:06:58","25-02-2025 13=
:37:28","Grid outage, Site went down because Gen ran until fuel shortage// =
Grid return (Refueling ongoing)","Mba Lazare Herve","Fuel Outage","Passive"=
,"Diesel","Diesel Outage","Grid outage, Site went down because Gen ran unti=
l fuel shortage// Grid return (Refueling ongoing)","ludovic-anselme.mouliom=
-mapoure@sagemcom","188","25-02-2025 13:10:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0004432664","N=
komo","IHS_YND_174","25-02-2025 13:04:25","25-02-2025 12:58:12","25-02-2025=
 13:21:29","Grid outage, site went down because Gen start and stopped with =
 Alarm ""high temp "" // he added water and manually start the gen","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Tem=
p - Coolant Level Issue","Grid outage, site went down because Gen start and=
 stopped with  Alarm ""high temp "" // he added water and manually start th=
e gen","yves.djomo@sagemcom.com","374","25-02-2025 13:04:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004432580","M=
vog-Manga","","25-02-2025 12:57:09","25-02-2025 12:47:05","25-02-2025 13:33=
:51","Grid outage, Site went down because Gen ran until fuel shortage// Ref=
ueling Done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage, Site went down because Gen ran until fuel shortage// Refue=
ling Done","yves.djomo@sagemcom.com","607","25-02-2025 12:57:09","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004432478","E=
kombitie","","25-02-2025 12:37:03","25-02-2025 12:34:56","25-02-2025 14:11:=
45","Grid outage, Site went down because Gen failed to start due to Grid co=
ntactor faulty// He bypassed Grid contactor and started Gen manualy","Fabri=
ce Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","G=
rid outage, Site went down because Gen failed to start due to Grid contacto=
r faulty// He bypassed Grid contactor and started Gen manualy","ludovic-ans=
elme.mouliom-mapoure@sagemcom","128","25-02-2025 12:37:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004432474","S=
tade-Abega","","25-02-2025 12:35:43","25-02-2025 12:26:27","25-02-2025 13:2=
2:21","Grid outage,gen failed to start due to PWC ZTE disfunctionning //Gri=
d Restored","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Grid outage,gen failed to start due to PWC ZTE =
disfunctionning //Grid Restored","ludovic-anselme.mouliom-mapoure@sagemcom"=
,"557","25-02-2025 12:35:43","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004432463","ODZ=
A CITE MBIA","","25-02-2025 12:34:31","25-02-2025 12:29:13","25-02-2025 14:=
03:59","Grid outage site went down because Gen ran until fuel shortage //Re=
fueling done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage site went down because Gen ran until fuel shortage //Refue=
ling done","ludovic-anselme.mouliom-mapoure@sagemcom","319","25-02-2025 12:=
34:31","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004432454","Awa=
e Ewonkan","","25-02-2025 12:32:15","25-02-2025 12:26:59","25-02-2025 13:24=
:08","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed // Grid power return","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down=
 because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // Grid=
 power return","ludovic-anselme.mouliom-mapoure@sagemcom","388","25-02-2025=
 12:32:15","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004432445","Nko=
lmvack","","25-02-2025 12:31:18","25-02-2025 12:27:10","25-02-2025 13:33:39=
","hybrid gen site gen failed to start due to alarm ""low oil pressure""//W=
e add oil and gen manually started ","Parker Tchoup","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Low Oil Pressure","hybrid gen site gen failed to =
start due to alarm ""low oil pressure""//We add oil and gen manually starte=
d ","ludovic-anselme.mouliom-mapoure@sagemcom","249","25-02-2025 12:31:18",=
"Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004432421","AWA=
E OCM","","25-02-2025 12:28:02","25-02-2025 12:18:53","25-02-2025 12:28:44"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automatically","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automatically","ludovic-anselme.=
mouliom-mapoure@sagemcom","551","25-02-2025 12:28:02","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004432410","Ema=
na","","25-02-2025 12:26:37","25-02-2025 12:19:29","25-02-2025 12:29:28","G=
rid outage, Site went down before Gen start due to poor backup// Gen starte=
d automatically","Fabrice Pouakam","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen started automatically","ludovic-anselme.moul=
iom-mapoure@sagemcom","429","25-02-2025 12:26:37","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004432404","Pha=
rmacie SION","","25-02-2025 12:25:38","25-02-2025 12:24:31","25-02-2025 12:=
35:28","Grid outage, Site went down before Gen start due to poor backup/ //=
 Gen automatically started","Paul BIBOUM","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup/ // Gen automatically started","ludovic-ans=
elme.mouliom-mapoure@sagemcom","68","25-02-2025 12:25:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_273","IHS_YND_214","NOCINC0004432384","N=
kolmesseng-II","","25-02-2025 12:24:31","25-02-2025 12:19:25","25-02-2025 1=
2:32:57","Grid outage.Site went down because Gen started and stopped due to=
 air intake // We purged and gen manually started ","Siligap Boris","Fuel O=
utage (Probable)","Passive","ACDG Gen","ACDG - Air Intake","Grid outage.Sit=
e went down because Gen started and stopped due to air intake // We purged =
and gen manually started ","yves.djomo@sagemcom.com","307","25-02-2025 12:2=
4:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004432323","A=
wae Escalier","","25-02-2025 12:19:53","25-02-2025 12:15:28","25-02-2025 12=
:18:45","Grid outage, site went down before gen start due to poor battery b=
ackup // gen start automatically","Albran Byorel","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // gen start automatically"=
,"ludovic-anselme.mouliom-mapoure@sagemcom","266","25-02-2025 12:19:53","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004432287","Nsi=
meyong Terre Rouge","","25-02-2025 12:16:18","25-02-2025 12:08:10","25-02-2=
025 12:24:40","Site went down due to PWC dysfunction, SS IHS Fran=E7ois NDO=
UNGOU is informed and confirmed// Site stabilized","MINKA NICOLAS","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went d=
own due to PWC dysfunction, SS IHS Fran=E7ois NDOUNGOU is informed and conf=
irmed// Site stabilized","ludovic-anselme.mouliom-mapoure@sagemcom","489","=
25-02-2025 12:16:18","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004431937","Nko=
londom","","25-02-2025 11:55:26","25-02-2025 11:49:17","25-02-2025 12:15:08=
","Grid fluctuation, Site went down because Gen failed to start due to grid=
 bad voltage, no rcp on site // He bypass grid and manually start the gen",=
"Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation, Site went down because Gen failed to sta=
rt due to grid bad voltage, no rcp on site // He bypass grid and manually s=
tart the gen","yves.djomo@sagemcom.com","389","25-02-2025 11:55:26","Sagemc=
om CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004431864","Com=
plex Beac II","","25-02-2025 11:47:27","25-02-2025 11:43:17","25-02-2025 13=
:13:47","Grid outage.gen ran until fuel  shortage//Refueling done","Albran =
Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen r=
an until fuel  shortage//Refueling done","ludovic-anselme.mouliom-mapoure@s=
agemcom","251","25-02-2025 11:47:27","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004431799","Nko=
ulou Carriere carrefourt","","25-02-2025 11:36:39","25-02-2025 11:07:30","2=
5-02-2025 13:09:47","Grid outage, site went down because gen failed to star=
t due to AVR dysfunctionned // He adjusted voltage tensions of AVR and gen =
manually started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen=
","ACDG - AVR","Grid outage, site went down because gen failed to start due=
 to AVR dysfunctionned // He adjusted voltage tensions of AVR and gen manua=
lly started","ludovic-anselme.mouliom-mapoure@sagemcom","1750","25-02-2025 =
11:36:39","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004431583","NYO=
M FACE MAETUR","","25-02-2025 11:02:41","25-02-2025 11:01:33","25-02-2025 1=
1:40:35","Grid Outage Gen Failed to Gen Card Faulty//Gen Manually Started",=
"Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid Outage Gen Failed to Gen Card Faulty//Gen Manually Started","lu=
dovic-anselme.mouliom-mapoure@sagemcom","70","25-02-2025 11:02:41","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004431569","ELOUMDEM=
 CARRIERE 2","","25-02-2025 10:57:40","25-02-2025 10:51:28","25-02-2025 11:=
42:43","Cascaded Incident from TTO4479788","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, Site went d=
own because Gen failed to start due to bad voltage No Rcp// He bypassed Gri=
d and started Gen manualy","system","278172","25-02-2025 10:57:40","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004431568","Eto koss=
 Yde","","25-02-2025 10:57:40","25-02-2025 10:51:28","25-02-2025 11:42:43",=
"Cascaded Incident from TTO4479788","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down bec=
ause Gen failed to start due to bad voltage No Rcp// He bypassed Grid and s=
tarted Gen manualy","system","278172","25-02-2025 10:57:40","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004431559","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","25-02-2025 10:55:40","25-02-2025 10:49=
:28","25-02-2025 11:42:43","Grid fluctuation, Site went down because Gen fa=
iled to start due to bad voltage No Rcp// He bypassed Grid and started Gen =
manualy","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation, Site went down because Gen failed t=
o start due to bad voltage No Rcp// He bypassed Grid and started Gen manual=
y","ludovic-anselme.mouliom-mapoure@sagemcom","446","25-02-2025 10:55:40","=
Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004431549","SIM=
BOCK BONAMBAPE","","25-02-2025 10:53:40","25-02-2025 10:52:31","25-02-2025 =
12:04:05","Grid outage, Site went down because Gen started and stopped due =
to Gen overload(20kva, 380A) SS IHS Alphonse DEFFO confirmed.// He reduiced=
 load and started Gen manualy","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen sta=
rted and stopped due to Gen overload(20kva, 380A) SS IHS Alphonse DEFFO con=
firmed.// He reduiced load and started Gen manualy","ludovic-anselme.moulio=
m-mapoure@sagemcom","70","25-02-2025 10:53:40","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004431537","NYO=
M 2 IHS","","25-02-2025 10:51:43","25-02-2025 10:48:35","25-02-2025 11:46:3=
8","Grid outage, site went down because gen fails to start due to card Gen =
disfunction // He reset of Gen card done and Gen started","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e, site went down because gen fails to start due to card Gen disfunction //=
 He reset of Gen card done and Gen started","ludovic-anselme.mouliom-mapour=
e@sagemcom","353","25-02-2025 10:51:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004431482","B=
ATA Mokolo OCM","","25-02-2025 10:39:04","25-02-2025 10:10:51","25-02-2025 =
12:02:25","Grid outage.no space to deploy mobile gen//Grid return ","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.no space to deploy mobile gen//Grid return ","yves.djomo@sagemcom.com","16=
94","25-02-2025 10:39:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004431401","MEHANDAN=
","","25-02-2025 10:27:52","25-02-2025 10:21:42","25-02-2025 10:34:14","Cas=
caded Incident from TTO4479588","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work: SS IHS Pas=
caline MANDA working on site// End of work","system","1214867","25-02-2025 =
10:27:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004431391","O=
dza II OCM","IHS_YND_528","25-02-2025 10:26:56","25-02-2025 10:21:42","25-0=
2-2025 10:35:56","Site went down due to work: SS IHS Pascaline MANDA workin=
g on site// End of work","Albran Byorel","Installation Activity","Passive",=
"Planned Activity","Installation Activity","Site went down due to work: SS =
IHS Pascaline MANDA working on site// End of work","yves.djomo@sagemcom.com=
","316","25-02-2025 10:26:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004431356","Akak-Nko=
zoa-MTN-IHS","","25-02-2025 10:24:51","25-02-2025 10:15:41","25-02-2025 10:=
19:29","Cascaded Incident from TTO4479538","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid fluctuations, site d=
own due to poor backup // Grid return","system","265805","25-02-2025 10:24:=
51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004431232","Nkongtoc=
k","","25-02-2025 10:11:32","25-02-2025 10:01:40","25-02-2025 10:05:00","Ca=
scaded Incident from TTO4479362","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID , =
Ubaie=3D54.2 V site On Grid The Tx FME Fulbert(654266068) from Huawei is in=
formed and Up at 10:32 AM","system","266730","25-02-2025 10:11:32","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004431229","Nomayos-=
IHS","","25-02-2025 10:11:31","25-02-2025 10:01:40","25-02-2025 10:05:00","=
Cascaded Incident from TTO4479362","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID , Ub=
aie=3D54.2 V site On Grid The Tx FME Fulbert(654266068) from Huawei is info=
rmed and Up at 10:32 AM","system","266729","25-02-2025 10:11:31","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004431227","Ebeba","=
","25-02-2025 10:11:31","25-02-2025 10:01:40","25-02-2025 10:05:00","Cascad=
ed Incident from TTO4479362","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","ACTIVE//No power issue on site GRID , Ubaie=3D=
54.2 V site On Grid The Tx FME Fulbert(654266068) from Huawei is informed a=
nd Up at 10:32 AM","system","266730","25-02-2025 10:11:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004431231","Angongo"=
,"","25-02-2025 10:11:31","25-02-2025 10:01:40","25-02-2025 10:05:00","Casc=
aded Incident from TTO4479362","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE//No power issue on site GRID , Ubaie=
=3D54.2 V site On Grid The Tx FME Fulbert(654266068) from Huawei is informe=
d and Up at 10:32 AM","system","266731","25-02-2025 10:11:31","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004431230","Mambine"=
,"","25-02-2025 10:11:31","25-02-2025 10:01:40","25-02-2025 10:05:00","Casc=
aded Incident from TTO4479362","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE//No power issue on site GRID , Ubaie=
=3D54.2 V site On Grid The Tx FME Fulbert(654266068) from Huawei is informe=
d and Up at 10:32 AM","system","266728","25-02-2025 10:11:31","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004431226","Nkenglik=
ok","","25-02-2025 10:11:30","25-02-2025 10:01:40","25-02-2025 10:05:00","C=
ascaded Incident from TTO4479362","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID ,=
 Ubaie=3D54.2 V site On Grid The Tx FME Fulbert(654266068) from Huawei is i=
nformed and Up at 10:32 AM","system","266731","25-02-2025 10:11:30","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004431223","Sous Pre=
fecture","","25-02-2025 10:11:30","25-02-2025 10:01:40","25-02-2025 10:05:0=
0","Cascaded Incident from TTO4479362","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID =
, Ubaie=3D54.2 V site On Grid The Tx FME Fulbert(654266068) from Huawei is =
informed and Up at 10:32 AM","system","266728","25-02-2025 10:11:30","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004431224","Mandoumb=
a OCM","","25-02-2025 10:11:30","25-02-2025 10:01:40","25-02-2025 10:05:00"=
,"Cascaded Incident from TTO4479362","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","ACTIVE//No power issue on site GRI=
D , Ubaie=3D54.2 V site On Grid The Tx FME Fulbert(654266068) from Huawei i=
s informed and Up at 10:32 AM","system","266731","25-02-2025 10:11:30","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004431225","Mbankomo=
 IHS","","25-02-2025 10:11:30","25-02-2025 10:01:40","25-02-2025 10:05:00",=
"Cascaded Incident from TTO4479362","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID , U=
baie=3D54.2 V site On Grid The Tx FME Fulbert(654266068) from Huawei is inf=
ormed and Up at 10:32 AM","system","266729","25-02-2025 10:11:30","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004431182","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, I=
HS_YND_697, IHS_YND_350, IHS_YND_335, IHS_YND_349","25-02-2025 10:05:44","2=
5-02-2025 10:01:40","25-02-2025 10:05:00","ACTIVE//No power issue on site G=
RID , Ubaie=3D54.2 V site On Grid The Tx FME Fulbert(654266068) from Huawei=
 is informed and Up at 10:32 AM","Fanda Brice","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power=
 issue on site GRID , Ubaie=3D54.2 V site On Grid The Tx FME Fulbert(654266=
068) from Huawei is informed and Up at 10:32 AM","yves.djomo@sagemcom.com",=
"245","25-02-2025 10:05:44","Sagemcom CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0004431099","Djo=
nassi-Yde","","25-02-2025 09:53:30","25-02-2025 09:49:12","25-02-2025 10:33=
:12","Site went down because CB(63A) tripped in DC BOX tripped in DC BOX// =
He replaced it by CB(80A)","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down beca=
use CB(63A) tripped in DC BOX tripped in DC BOX// He replaced it by CB(80A)=
","ludovic-anselme.mouliom-mapoure@sagemcom","258","25-02-2025 09:53:30","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004431083","Eseka To=
wn","","25-02-2025 09:51:05","25-02-2025 09:44:15","25-02-2025 10:17:55","C=
ascaded Incident from TTO4479233","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue on site ,site =
on Gen  wiith  Ubaie=3D52.4 V The TX FME Etienne/ 695033981 FROM  Huawei is=
 informed and Up at 10:17 AM","system","281966","25-02-2025 09:51:05","Sage=
mcom CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0004431067","Ese=
ka MTN","IHS_YND_378","25-02-2025 09:49:20","25-02-2025 09:44:15","25-02-20=
25 10:17:55","Active//No power issue on site ,site on Gen  wiith  Ubaie=3D5=
2.4 V The TX FME Etienne/ 695033981 FROM  Huawei is informed and Up at 10:1=
7 AM","Kemeni Franklin","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active//No power issue on site ,site on=
 Gen  wiith  Ubaie=3D52.4 V The TX FME Etienne/ 695033981 FROM  Huawei is i=
nformed and Up at 10:17 AM","yves.djomo@sagemcom.com","306","25-02-2025 09:=
49:20","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004430843","Mvo=
g-Manga","","25-02-2025 09:25:10","25-02-2025 09:00:06","25-02-2025 09:42:5=
9","Grid outage, site went down because gen ran untill fuel shortage // Ref=
ueling done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage, site went down because gen ran untill fuel shortage // Ref=
ueling done","yves.djomo@sagemcom.com","1555","25-02-2025 09:25:10","Sagemc=
om CMR"
"Closed Complete","Site Down","T1557","IHS_YND_313","NOCINC0004430808","Afa=
noya","","25-02-2025 09:16:50","25-02-2025 09:10:31","25-02-2025 10:52:41",=
"Grid outage.gen ran until fuel shortage//Refueling done","Hyemafo Gildas",=
"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran until=
 fuel shortage//Refueling done","yves.djomo@sagemcom.com","430","25-02-2025=
 09:16:50","Sagemcom CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0004430698","Nko=
abang Alembe","","25-02-2025 08:59:14","25-02-2025 08:47:07","25-02-2025 09=
:29:09","Site went down because Gen failed to start due to CB Gen (32A) tri=
pped due to grid fluctutions// He rearmed CB and site on gen","Mba Lazare H=
erve","Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Site w=
ent down because Gen failed to start due to CB Gen (32A) tripped due to gri=
d fluctutions// He rearmed CB and site on gen","ludovic-anselme.mouliom-map=
oure@sagemcom","727","25-02-2025 08:59:14","Sagemcom CMR"
"Closed Complete","Warning","T0288","IHS_YND_001","NOCINC0004430679","Royal=
 Hotel Yde","","25-02-2025 08:56:24","","","Site went Alarmes because Gen f=
ailed to start due to Grid bad voltage // He bypassed the Grid and Gen manu=
ally started","Paul BIBOUM","Warning","Warning","POWER","Warning - Site on =
Battery","Site went Alarmes because Gen failed to start due to Grid bad vol=
tage // He bypassed the Grid and Gen manually started","el-dalile@sagemcom.=
com","2410","25-02-2025 08:56:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004430634","N=
kolfon Cimencam","","25-02-2025 08:50:22","25-02-2025 08:40:50","25-02-2025=
 08:42:46","Active//No power issue, Site on Grid Ubai=3D 52,8V. Notice that=
 it is impacted by Afanoya II The Tx FME Fulbert from Huawei is informed","=
Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 52=
,8V. Notice that it is impacted by Afanoya II The Tx FME Fulbert from Huawe=
i is informed","yves.djomo@sagemcom.com","573","25-02-2025 08:50:22","Sagem=
com CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004430508","Nom=
ayos montee Meche","","25-02-2025 08:22:07","24-02-2025 23:01:54","25-02-20=
25 08:09:54","Access issue during the night Grid ouatge.gen ran until fuel =
shortage//Refueling done","Fanda Brice","Access Denial","Lease Or Legal","L=
andlord Related Issues","Access Issue - Land Lord","Access issue during the=
 night Grid ouatge.gen ran until fuel shortage//Refueling done","yves.djomo=
@sagemcom.com","33614","25-02-2025 08:22:07","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004430496","ELO=
UMDEM CARRIERE","","25-02-2025 08:19:01","25-02-2025 08:00:49","25-02-2025 =
09:13:33","Site went down due to 1/1 rectifier faulty SS IHS Felix ZAMBE is=
 informed// He replaced rectifier faulty","Fanda Brice","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","Site went down due to 1/1 rectifi=
er faulty SS IHS Felix ZAMBE is informed// He replaced rectifier faulty","l=
udovic-anselme.mouliom-mapoure@sagemcom","1093","25-02-2025 08:19:01","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004430385","B=
arriere","","25-02-2025 07:55:08","25-02-2025 07:47:05","25-02-2025 14:16:1=
4","Site went down because Gen overload(20kva,400 A) IHS SS Felix Zambe is =
informed and confirmed","Hyemafo Gildas","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Site went down because Gen overload(20kva,400 A) I=
HS SS Felix Zambe is informed and confirmed","yves.djomo@sagemcom.com","484=
","25-02-2025 07:55:08","Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_274","NOCINC0004430366","=
Emana Lycee","","25-02-2025 07:52:40","25-02-2025 06:12:29","25-02-2025 06:=
30:23","Cascaded Incident from TTO4477881 - Cascade Removed From TTO4477881=
","Fabrice Pouakam","","","","","Grid outage, site went down because gen ra=
n untill fuel shortage // Refueling done","system","6011","25-02-2025 07:52=
:40","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004430282","Nko=
zoa","","25-02-2025 07:39:43","25-02-2025 07:31:30","25-02-2025 09:52:55","=
Grid fluctuation, Site went down because Gen failed to start due to Grid ba=
d voltage and no RCP on site // He bypass the Grid and Gen manually started=
","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation, Site went down because Gen failed to s=
tart due to Grid bad voltage and no RCP on site // He bypass the Grid and G=
en manually started","yves.djomo@sagemcom.com","495","25-02-2025 07:39:43",=
"Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004430220","Ako=
k Ndoe Yde","","25-02-2025 07:20:46","25-02-2025 07:01:37","25-02-2025 07:5=
3:50","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start manualy","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start manualy","ludovic-ans=
elme.mouliom-mapoure@sagemcom","1150","25-02-2025 07:20:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004430133","M=
ontee-Des-Soeurs","","25-02-2025 07:02:19","25-02-2025 07:00:13","25-02-202=
5 07:03:04","Grid outage, site went down before Gen start due to poor batte=
ry backup // Gen start automatically","Hyemafo Gildas","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before Gen start due to poor battery backup // Gen start automatic=
ally","yves.djomo@sagemcom.com","127","25-02-2025 07:02:19","Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_305","NOCINC0004430086","=
NYOM","","25-02-2025 06:54:43","25-02-2025 06:12:29","25-02-2025 06:30:23",=
"Cascaded Incident from TTO4477881 - Cascade Removed From TTO4477881","Fabr=
ice Pouakam","","","","","Grid outage, site went down because gen ran until=
l fuel shortage // Refueling done","system","2534","25-02-2025 06:54:43","S=
agemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_279","NOCINC0004430087","=
Messassi okolo","","25-02-2025 06:54:43","25-02-2025 06:12:29","25-02-2025 =
06:30:23","Cascaded Incident from TTO4477881 - Cascade Removed From TTO4477=
881","Fabrice Pouakam","","","","","Grid outage, site went down because gen=
 ran untill fuel shortage // Refueling done","system","2534","25-02-2025 06=
:54:43","Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_299","NOCINC0004430085","=
Olembe MTN","","25-02-2025 06:54:42","25-02-2025 06:12:29","25-02-2025 06:3=
0:23","Cascaded Incident from TTO4477881 - Cascade Removed From TTO4477881"=
,"Fabrice Pouakam","","","","","Grid outage, site went down because gen ran=
 untill fuel shortage // Refueling done","system","2533","25-02-2025 06:54:=
42","Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_681","NOCINC0004430082","=
NKOLMEKONG YDE","","25-02-2025 06:54:42","25-02-2025 06:12:29","25-02-2025 =
06:30:23","Cascaded Incident from TTO4477881 - Cascade Removed From TTO4477=
881","Fabrice Pouakam","","","","","Grid outage, site went down because gen=
 ran untill fuel shortage // Refueling done","system","2533","25-02-2025 06=
:54:42","Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_297","NOCINC0004430083","=
Messassi","","25-02-2025 06:54:42","25-02-2025 06:12:29","25-02-2025 06:30:=
23","Cascaded Incident from TTO4477881 - Cascade Removed From TTO4477881","=
Fabrice Pouakam","","","","","Grid outage, site went down because gen ran u=
ntill fuel shortage // Refueling done","system","2533","25-02-2025 06:54:42=
","Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_280","NOCINC0004430084","=
Messassi 2","","25-02-2025 06:54:42","25-02-2025 06:12:29","25-02-2025 06:3=
0:23","Cascaded Incident from TTO4477881 - Cascade Removed From TTO4477881"=
,"Fabrice Pouakam","","","","","Grid outage, site went down because gen ran=
 untill fuel shortage // Refueling done","system","2533","25-02-2025 06:54:=
42","Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_298","NOCINC0004430078","=
Olembe","","25-02-2025 06:54:41","25-02-2025 06:12:29","25-02-2025 06:30:23=
","Cascaded Incident from TTO4477881 - Cascade Removed From TTO4477881","Fa=
brice Pouakam","","","","","Grid outage, site went down because gen ran unt=
ill fuel shortage // Refueling done","system","2532","25-02-2025 06:54:41",=
"Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_761","NOCINC0004430081","=
Djonassi-Yde","","25-02-2025 06:54:41","25-02-2025 06:12:29","25-02-2025 06=
:30:23","Cascaded Incident from TTO4477881 - Cascade Removed From TTO447788=
1","Fabrice Pouakam","","","","","Grid outage, site went down because gen r=
an untill fuel shortage // Refueling done","system","2532","25-02-2025 06:5=
4:41","Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_316","NOCINC0004430079","=
Akak-Nkozoa-MTN-IHS","","25-02-2025 06:54:41","25-02-2025 06:12:29","25-02-=
2025 06:30:23","Cascaded Incident from TTO4477881 - Cascade Removed From TT=
O4477881","Fabrice Pouakam","","","","","Grid outage, site went down becaus=
e gen ran untill fuel shortage // Refueling done","system","2532","25-02-20=
25 06:54:41","Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_685","NOCINC0004430080","=
Emana lycee 2","","25-02-2025 06:54:41","25-02-2025 06:12:29","25-02-2025 0=
6:30:23","Cascaded Incident from TTO4477881 - Cascade Removed From TTO44778=
81","Fabrice Pouakam","","","","","Grid outage, site went down because gen =
ran untill fuel shortage // Refueling done","system","2532","25-02-2025 06:=
54:41","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004430012","AKA=
K Nkozoa","","25-02-2025 06:40:12","25-02-2025 06:28:53","25-02-2025 08:54:=
27","Grid outage, Site went down because gen stopped due to belt cut // He =
changed belt and Gen manually started","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Fan Belt","Grid outage, Site went down becaus=
e gen stopped due to belt cut // He changed belt and Gen manually started",=
"ervine.mbezele@sagemcom.com","680","25-02-2025 06:40:12","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004429889","Nko=
londom","","25-02-2025 06:14:46","25-02-2025 06:12:29","25-02-2025 06:30:23=
","Grid outage, site went down because gen ran untill fuel shortage // Refu=
eling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran untill fuel shortage // Re=
fueling done","mariam.tchonang@sagemcom.com","138","25-02-2025 06:14:46","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004429724","K=
oweit City","","25-02-2025 05:21:11","25-02-2025 05:06:13","25-02-2025 09:1=
7:55","Grid outage, Site went down because Gen failed to start due to Pre-f=
ilter fauly// He replaced it and and started Gen manualy","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Filter","Grid outage, S=
ite went down because Gen failed to start due to Pre-filter fauly// He repl=
aced it and and started Gen manualy","mariam.tchonang@sagemcom.com","899","=
25-02-2025 05:21:11","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004429677","ODZ=
A MINKAN EDIBI ASSI","","25-02-2025 05:02:04","25-02-2025 04:54:52","25-02-=
2025 05:42:44","Grid outage, Site went down because Gen start and stopped w=
ith ""High temps ""alarm due to overload// he added water and manually star=
t the Gen","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
High Engine Temp - Coolant Level Issue","Grid outage, Site went down becaus=
e Gen start and stopped with ""High temps ""alarm due to overload// he adde=
d water and manually start the Gen","mariam.tchonang@sagemcom.com","433","2=
5-02-2025 05:02:04","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004429524","ODZ=
A CITE MBIA","","25-02-2025 04:01:44","25-02-2025 03:55:31","25-02-2025 04:=
23:21","Grid outage, Site went because Gen ran until fuel shortage// Refuel=
ing Done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, Site went because Gen ran until fuel shortage// Refueling Don=
e","wilfried.kameni@sagemcom.com","374","25-02-2025 04:01:44","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004429451","M=
imboman-Village","","25-02-2025 03:27:16","25-02-2025 03:18:02","25-02-2025=
 03:39:54","Site went down because The PWC dysfonction //  GEn manually sta=
rted","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Site went down because The PWC dysfonction //  GEn ma=
nually started","wilfried.kameni@sagemcom.com","555","25-02-2025 03:27:16",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004429283","E=
kie-Elegance","IHS_YND_159","25-02-2025 02:20:36","25-02-2025 01:01:18","25=
-02-2025 07:02:05","Access Issue during the Night, Site was on Gen due to G=
rid outage, site went down because gen stopped with 'Emergency stop' alarm =
// He reset the Gen card and Gen manually started","Albran Byorel","Access =
Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lor=
d","Access Issue during the Night, Site was on Gen due to Grid outage, site=
 went down because gen stopped with 'Emergency stop' alarm // He reset the =
Gen card and Gen manually started","wilfried.kameni@sagemcom.com","4759","2=
5-02-2025 02:20:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004429064","C=
omplexe-BEAC","","25-02-2025 01:29:02","25-02-2025 01:01:18","25-02-2025 07=
:02:05","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Access Issue during the Night, Site was on Gen due to Grid =
outage, site went down because gen stopped with 'Emergency stop' alarm // H=
e reset the Gen card and Gen manually started","wilfried.kameni@sagemcom.co=
m","284484","25-02-2025 01:29:02","Sagemcom CMR"
"Closed Complete","Site Down","T0539","IHS_YND_034","NOCINC0004428922","EMI=
A MTN","","25-02-2025 00:43:28","25-02-2025 00:25:16","25-02-2025 10:09:00"=
,"Grid outage no space to deploy a mobil Gen// Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spac=
e to deploy a mobil Gen// Grid return","wilfried.kameni@sagemcom.com","1092=
","25-02-2025 00:43:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004428916","O=
dza","","25-02-2025 00:42:07","25-02-2025 00:18:59","25-02-2025 01:50:58","=
Grid outage,Site went down because Gen  failed to start due to PWC  disfunc=
tionning //He reset the controller and started the Gen","Albran Byorel","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid o=
utage,Site went down because Gen  failed to start due to PWC  disfunctionni=
ng //He reset the controller and started the Gen","wilfried.kameni@sagemcom=
.com","1389","25-02-2025 00:42:07","Sagemcom CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004428700","Eki=
e sud","","24-02-2025 23:27:22","24-02-2025 23:19:15","25-02-2025 00:28:46"=
,"Grid outage site went down because Gen failed to start due to Gen card dy=
sfonction // He reset the Gen card and Gen manually started","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge site went down because Gen failed to start due to Gen card dysfonction /=
/ He reset the Gen card and Gen manually started","wilfried.kameni@sagemcom=
.com","488","24-02-2025 23:27:22","Sagemcom CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0004428613","Men=
dong Maeture","","24-02-2025 23:06:59","24-02-2025 22:58:39","24-02-2025 23=
:56:03","Grid Outage Site went down due to Gen Contactors No existed //he B=
ybass it and Manually Started the Gen","Hyemafo Gildas","Equipment Repair",=
"Passive","Control Panel","ATS-AMF Issue","Grid Outage Site went down due t=
o Gen Contactors No existed //he Bybass it and Manually Started the Gen","r=
ouselle.schoune@ihstowers.com","501","24-02-2025 23:06:59","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004428605","Nko=
londom","","24-02-2025 23:03:51","24-02-2025 23:01:37","24-02-2025 23:52:21=
","Grid fluctuation, Site went down because Gen failed to start due to Grid=
 bad voltage and  RCP on site // he bypass the Grid and Gen manually starte=
d","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid fluctuation, Site went down because Gen failed to =
start due to Grid bad voltage and  RCP on site // he bypass the Grid and Ge=
n manually started","wilfried.kameni@sagemcom.com","135","24-02-2025 23:03:=
51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004428564","O=
mnisport-Rail","","24-02-2025 22:51:08","24-02-2025 22:42:51","24-02-2025 2=
3:34:02","Site went down due to insufficiency of rectifier IHS SS Bernard A=
tangana is informed // he reduced the load","Delor Telezing","Equipment Rep=
air","Passive","Rectifier","Rectifier Module","Site went down due to insuff=
iciency of rectifier IHS SS Bernard Atangana is informed // he reduced the =
load","wilfried.kameni@sagemcom.com","498","24-02-2025 22:51:08","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004428418","Mimboman=
4","","24-02-2025 22:25:59","24-02-2025 21:48:18","24-02-2025 21:55:16","Ca=
scaded Incident from TTO4475944","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Grid outage site went down because Ge=
n failed to start due to RCP faulty // he bypass the RCP and site on Grid P=
ower issue resolved at site up 21:38 PM But Site remains down ocm after pow=
er reset the fme tx BRUNO (698 756768) from HUAWEI is informed.","system","=
288880","24-02-2025 22:25:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0004428321","Ekekam",=
"","24-02-2025 22:19:25","24-02-2025 19:41:25","24-02-2025 21:05:25","Casca=
ded Incident from TTO4475022","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because fuel s=
pill due to burst return pipe // he replaced the return pipe and Gen manual=
ly started  Power issue resolved at site up 21:05 PM But Site remains down =
ocm after power reset The Tx FME Fulbert (654266068) from Huawei is informe=
d","system","289179","24-02-2025 22:19:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004428323","Nomayos-=
IHS","","24-02-2025 22:19:25","24-02-2025 19:41:25","24-02-2025 21:05:25","=
Cascaded Incident from TTO4475022","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site went down because fuel spill due=
 to burst return pipe // he replaced the return pipe and Gen manually start=
ed  Power issue resolved at site up 21:05 PM But Site remains down ocm afte=
r power reset The Tx FME Fulbert (654266068) from Huawei is informed","syst=
em","289183","24-02-2025 22:19:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0004428322","LOBO MTN=
","","24-02-2025 22:19:25","24-02-2025 19:41:25","24-02-2025 21:05:25","Cas=
caded Incident from TTO4475022","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site went down because fuel=
 spill due to burst return pipe // he replaced the return pipe and Gen manu=
ally started  Power issue resolved at site up 21:05 PM But Site remains dow=
n ocm after power reset The Tx FME Fulbert (654266068) from Huawei is infor=
med","system","289182","24-02-2025 22:19:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004428319","Minka","=
","24-02-2025 22:19:24","24-02-2025 19:41:25","24-02-2025 21:05:25","Cascad=
ed Incident from TTO4475022","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down because fuel spill due to bu=
rst return pipe // he replaced the return pipe and Gen manually started  Po=
wer issue resolved at site up 21:05 PM But Site remains down ocm after powe=
r reset The Tx FME Fulbert (654266068) from Huawei is informed","system","2=
89178","24-02-2025 22:19:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_366","NOCINC0004428317","Mandoumb=
a MTN","","24-02-2025 22:19:24","24-02-2025 19:41:25","24-02-2025 21:05:25"=
,"Cascaded Incident from TTO4475022","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down because fuel spi=
ll due to burst return pipe // he replaced the return pipe and Gen manually=
 started  Power issue resolved at site up 21:05 PM But Site remains down oc=
m after power reset The Tx FME Fulbert (654266068) from Huawei is informed"=
,"system","289184","24-02-2025 22:19:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004428320","Nkongtoc=
k","","24-02-2025 22:19:24","24-02-2025 19:41:25","24-02-2025 21:05:25","Ca=
scaded Incident from TTO4475022","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because fuel spill d=
ue to burst return pipe // he replaced the return pipe and Gen manually sta=
rted  Power issue resolved at site up 21:05 PM But Site remains down ocm af=
ter power reset The Tx FME Fulbert (654266068) from Huawei is informed","sy=
stem","289181","24-02-2025 22:19:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0004428313","Lobo 2",=
"","24-02-2025 22:19:23","24-02-2025 19:41:25","24-02-2025 21:05:25","Casca=
ded Incident from TTO4475022","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because fuel s=
pill due to burst return pipe // he replaced the return pipe and Gen manual=
ly started  Power issue resolved at site up 21:05 PM But Site remains down =
ocm after power reset The Tx FME Fulbert (654266068) from Huawei is informe=
d","system","289185","24-02-2025 22:19:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0004428315","Ngog Map=
ubi","","24-02-2025 22:19:23","24-02-2025 19:41:25","24-02-2025 21:05:25","=
Cascaded Incident from TTO4475022","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because fuel spill=
 due to burst return pipe // he replaced the return pipe and Gen manually s=
tarted  Power issue resolved at site up 21:05 PM But Site remains down ocm =
after power reset The Tx FME Fulbert (654266068) from Huawei is informed","=
system","289181","24-02-2025 22:19:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004428316","Ebeba","=
","24-02-2025 22:19:23","24-02-2025 19:41:25","24-02-2025 21:05:25","Cascad=
ed Incident from TTO4475022","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down because fuel spill due to bu=
rst return pipe // he replaced the return pipe and Gen manually started  Po=
wer issue resolved at site up 21:05 PM But Site remains down ocm after powe=
r reset The Tx FME Fulbert (654266068) from Huawei is informed","system","2=
89180","24-02-2025 22:19:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0004428314","Nkeng li=
kok","","24-02-2025 22:19:23","24-02-2025 19:41:25","24-02-2025 21:05:25","=
Cascaded Incident from TTO4475022","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because fuel spill=
 due to burst return pipe // he replaced the return pipe and Gen manually s=
tarted  Power issue resolved at site up 21:05 PM But Site remains down ocm =
after power reset The Tx FME Fulbert (654266068) from Huawei is informed","=
system","289177","24-02-2025 22:19:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004428312","Nomayos =
montee Meche","","24-02-2025 22:19:23","24-02-2025 19:41:25","24-02-2025 21=
:05:25","Cascaded Incident from TTO4475022","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","site went down because fuel =
spill due to burst return pipe // he replaced the return pipe and Gen manua=
lly started  Power issue resolved at site up 21:05 PM But Site remains down=
 ocm after power reset The Tx FME Fulbert (654266068) from Huawei is inform=
ed","system","289183","24-02-2025 22:19:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_373","NOCINC0004428311","Maloun",=
"","24-02-2025 22:19:22","24-02-2025 19:41:25","24-02-2025 21:05:25","Casca=
ded Incident from TTO4475022","Kemeni Franklin","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because fuel spill due =
to burst return pipe // he replaced the return pipe and Gen manually starte=
d  Power issue resolved at site up 21:05 PM But Site remains down ocm after=
 power reset The Tx FME Fulbert (654266068) from Huawei is informed","syste=
m","289179","24-02-2025 22:19:22","Sagemcom CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0004428286","RUE=
 FOE","","24-02-2025 22:16:07","24-02-2025 21:48:43","25-02-2025 07:43:43",=
"Access issue during the night, CB Eneo Meter down, Site went down because =
Gen started and stopped with ""overvoltage"" alarm// He reset Gen card and =
started Gen manualy","Delor Telezing","Access Denial","Lease Or Legal","Lan=
dlord Related Issues","Access Issue - Land Lord","Access issue during the n=
ight, CB Eneo Meter down, Site went down because Gen started and stopped wi=
th ""overvoltage"" alarm// He reset Gen card and started Gen manualy","ludi=
vine.ngamaleu@ihstowers.com","1645","24-02-2025 22:16:07","Sagemcom CMR"
"Closed Complete","Site Down","T0530","IHS_YND_252","NOCINC0004428223","Kow=
eit City","","24-02-2025 21:58:41","24-02-2025 21:51:28","24-02-2025 22:40:=
27","Grid outage site went down because Gen started and stopped with alarm =
Gen under voltage // He RESET the Gen card and Gen manually started","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage site went down because Gen started and stopped with alarm Gen un=
der voltage // He RESET the Gen card and Gen manually started","ludivine.ng=
amaleu@ihstowers.com","7210","24-02-2025 21:58:41","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004428213","Nko=
lo II New","IHS_YND_266","24-02-2025 21:56:31","24-02-2025 21:48:18","24-02=
-2025 21:55:16","No power issue site on Gen with U=3D52.2V The FME Tx  Lion=
el Steve /655184876/ From huawei is informed.","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue site on Gen with U=3D52.2V The FME Tx  Lionel Steve /6551=
84876/ From huawei is informed.","ludivine.ngamaleu@ihstowers.com","494","2=
4-02-2025 21:56:31","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004428201","Lad=
a I Yde","","24-02-2025 21:53:44","24-02-2025 21:46:33","24-02-2025 22:30:4=
1","Grid outage, site went down because Gen start and stopped with  high te=
mp alarm // He added water and manually start the Gen","Mba Lazare Herve","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, site went down because Gen start and stopped with=
  high temp alarm // He added water and manually start the Gen","ludivine.n=
gamaleu@ihstowers.com","432","24-02-2025 21:53:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004428162","M=
vog-Manga","","24-02-2025 21:47:37","24-02-2025 21:48:21","25-02-2025 01:37=
:06","Grid outage site went down because Gen started and stopped due to ala=
rm ((not unproven) // He reset the Gen card and Gen manaully started","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage site went down because Gen started and stopped due to alarm ((n=
ot unproven) // He reset the Gen card and Gen manaully started","danick.tch=
akouani@sagemcom.com","16801","24-02-2025 21:47:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004428159","E=
kie-Elegance","","24-02-2025 21:45:58","24-02-2025 21:31:51","24-02-2025 21=
:58:31","Grid outage site went down because Gen started and stoopped due to=
 button emergency stop activated // He desactivated the  Emergency stop and=
 Gen manually started","Albran Byorel","Equipment Repair","Passive","ACDG G=
en","ACDG - Emergency Stop","Grid outage site went down because Gen started=
 and stoopped due to button emergency stop activated // He desactivated the=
  Emergency stop and Gen manually started","danick.tchakouani@sagemcom.com"=
,"848","24-02-2025 21:45:58","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004428140","ELO=
UMDEM CARRIERE","","24-02-2025 21:41:46","24-02-2025 21:28:28","25-02-2025 =
03:08:41","Grid outage.site went down due to gen failed to start //Grid ret=
urn(investigation ongoing)","Fanda Brice","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage.site went down due to gen failed=
 to start //Grid return(investigation ongoing)","ludivine.ngamaleu@ihstower=
s.com","799","24-02-2025 21:41:46","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004428138","Mvo=
g-Betsi","","24-02-2025 21:41:14","24-02-2025 21:37:02","24-02-2025 21:56:1=
8","Site went down because Gen failed to start due to Grid bad voltage and =
RCP on site // Grid stabilized","Hyemafo Gildas","Grid Supply","Passive","G=
rid","National Grid - Grid Outage Issue","Site went down because Gen failed=
 to start due to Grid bad voltage and RCP on site // Grid stabilized","dani=
ck.tchakouani@sagemcom.com","681","24-02-2025 21:41:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004428118","B=
arriere IHS","","24-02-2025 21:35:35","24-02-2025 21:25:14","24-02-2025 21:=
35:05","ACTIVE //No power issue U=3D 54,6v Site on Grid   The Tx Fme George=
s /6974661814 from huawei is informed","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE =
//No power issue U=3D 54,6v Site on Grid   The Tx Fme Georges /6974661814 f=
rom huawei is informed","danick.tchakouani@sagemcom.com","622","24-02-2025 =
21:35:35","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004428077","NYO=
M FACE MAETUR","","24-02-2025 21:30:20","24-02-2025 21:15:06","24-02-2025 2=
2:15:40","Grid outage, site went down because Gen failed to start due to Ge=
n card and solenoid faulty// Gen Manually Started","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Solenoid Coil","Grid outage, site=
 went down because Gen failed to start due to Gen card and solenoid faulty/=
/ Gen Manually Started","ludivine.ngamaleu@ihstowers.com","915","24-02-2025=
 21:30:20","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004427993","Men=
dong3","","24-02-2025 21:16:24","24-02-2025 21:09:14","25-02-2025 20:17:04"=
,"Grid outage..no space to deploy mobile gen // grid return ","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage..no s=
pace to deploy mobile gen // grid return ","danick.tchakouani@sagemcom.com"=
,"430","24-02-2025 21:16:24","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004427987","NYO=
M 2 IHS","","24-02-2025 21:15:26","24-02-2025 21:06:20","24-02-2025 22:56:4=
0","Grid outage, site went down because gen fails to start due to card Gen =
disfunction // He reset of Gen card done and Gen started","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e, site went down because gen fails to start due to card Gen disfunction //=
 He reset of Gen card done and Gen started","danick.tchakouani@sagemcom.com=
","547","24-02-2025 21:15:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0004427943","A=
hala","","24-02-2025 21:07:22","24-02-2025 20:56:10","24-02-2025 22:43:28",=
"Grid fluctuation, Site went down because Gen failed to start due to Grid b=
ad voltage and no RCP on site // he bypass the Grid and Gen manually starte=
d","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation, Site went down because Gen failed to s=
tart due to Grid bad voltage and no RCP on site // he bypass the Grid and G=
en manually started","danick.tchakouani@sagemcom.com","673","24-02-2025 21:=
07:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0004427914","MVAN SAC=
EL","","24-02-2025 21:05:00","24-02-2025 19:32:36","24-02-2025 20:27:25","C=
ascaded Incident from TTO4474967","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage Site went down because G=
en Failed due to Gen Contactors dysfonction /He Bypass it and Manually Star=
ted the Gen","system","297063","24-02-2025 21:05:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004427847","ELOUMDEM=
 CARRIERE 2","","24-02-2025 20:58:14","24-02-2025 19:20:14","24-02-2025 19:=
25:48","Cascaded Incident from TTO4474845","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down Insufficiency =
of retifier on site SS IHS Felix Zamb=E9 is informed and confirmed //Site s=
tabilized","system","5880","24-02-2025 20:58:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0004427814","B=
ondjock","","24-02-2025 20:52:30","24-02-2025 19:51:19","24-02-2025 23:04:2=
9","Grid outage site went down because Gen stopped due to air intake  // We=
 purged and Gen manually started","Fanda Brice","Fuel Outage (Probable)","P=
assive","ACDG Gen","ACDG - Air Intake","Grid outage site went down because =
Gen stopped due to air intake  // We purged and Gen manually started","dani=
ck.tchakouani@sagemcom.com","6423","24-02-2025 20:52:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004427777","M=
eyo","IHS_YND_762","24-02-2025 20:43:46","24-02-2025 20:39:16","24-02-2025 =
20:45:49","ACTIVE //No power issue U=3D 54,6v Site on Grid   The Tx Fme Geo=
rges /6974661814 from huawei is informed","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTI=
VE //No power issue U=3D 54,6v Site on Grid   The Tx Fme Georges /697466181=
4 from huawei is informed","mariam.tchonang@sagemcom.com","271","24-02-2025=
 20:43:46","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0004427657","OLA=
MA","","24-02-2025 20:28:34","24-02-2025 19:41:25","24-02-2025 21:05:25",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","site went down because fuel spill due to burst return pipe // he replac=
ed the return pipe and Gen manually started  Power issue resolved at site u=
p 21:05 PM But Site remains down ocm after power reset The Tx FME Fulbert (=
654266068) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","2891=
78","24-02-2025 20:28:34","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004427643","Ako=
no","","24-02-2025 20:26:14","24-02-2025 19:41:25","24-02-2025 21:05:25",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","site went down because fuel spill due to burst return pipe // he replac=
ed the return pipe and Gen manually started  Power issue resolved at site u=
p 21:05 PM But Site remains down ocm after power reset The Tx FME Fulbert (=
654266068) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","2891=
82","24-02-2025 20:26:14","Sagemcom CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0004427626","OKO=
A Peage","","24-02-2025 20:22:21","24-02-2025 19:41:25","24-02-2025 21:05:2=
5","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","site went down because fuel spill due to burst return pipe // he r=
eplaced the return pipe and Gen manually started  Power issue resolved at s=
ite up 21:05 PM But Site remains down ocm after power reset The Tx FME Fulb=
ert (654266068) from Huawei is informed","ludivine.ngamaleu@ihstowers.com",=
"289177","24-02-2025 20:22:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004427537","S=
OA TOWN","","24-02-2025 20:08:17","24-02-2025 20:00:03","24-02-2025 20:33:2=
7","Grid outage, Site went down because Gen stopped with ""overload"" alarm=
 // He reset Gen card and started Gen manualy","Siligap Boris","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went =
down because Gen stopped with ""overload"" alarm // He reset Gen card and s=
tarted Gen manualy","danick.tchakouani@sagemcom.com","495","24-02-2025 20:0=
8:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004427471","C=
omplexe-BEAC","","24-02-2025 19:52:13","24-02-2025 19:37:06","24-02-2025 19=
:40:24","No power issue UBaie=3D54.7V  site on Gen The Fme TX Lionel steeve=
 /655184876 of Huawei is informed.Notice that we have disjunction in OCM eq=
uipment","Albran Byorel","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue UBaie=3D54.7V  site on =
Gen The Fme TX Lionel steeve /655184876 of Huawei is informed.Notice that w=
e have disjunction in OCM equipment","danick.tchakouani@sagemcom.com","907"=
,"24-02-2025 19:52:13","Sagemcom CMR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0004427437","Sou=
s Prefecture","IHS_YND_330, IHS_YND_687, IHS_YND_373, IHS_YND_791, IHS_YND_=
783, IHS_YND_347, IHS_YND_419, IHS_YND_339, IHS_YND_366, IHS_EDA_101, IHS_Y=
ND_372, IHS_YND_371, IHS_YND_349, IHS_YND_762, IHS_YND_714, IHS_YND_342, IH=
S_YND_365, IHS_YND_697","24-02-2025 19:48:30","24-02-2025 19:37:25","24-02-=
2025 21:05:43","site went down because fuel spill due to burst return pipe =
// he replaced the return pipe and Gen manually started  Power issue resolv=
ed at site up 21:05 PM But Site remains down ocm after power reset","Fanda =
Brice","Fuel Outage (Probable)","Passive","Diesel","Fuel Line Issue","site =
went down because fuel spill due to burst return pipe // he replaced the re=
turn pipe and Gen manually started  Power issue resolved at site up 21:05 P=
M But Site remains down ocm after power reset The Tx FME Fulbert (654266068=
) from Huawei is informed","danick.tchakouani@sagemcom.com","2753","24-02-2=
025 19:48:30","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004427434","Bar=
riere","","24-02-2025 19:47:24","24-02-2025 19:35:14","24-02-2025 23:03:17"=
,"Site went down due to pwc overload (20k, 450A) the ss IHS Felix is inform=
ed//Site stabilized","Hyemafo Gildas","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","Site went down due to pwc overload (20k, 450A) the ss=
 IHS Felix is informed//Site stabilized","danick.tchakouani@sagemcom.com","=
731","24-02-2025 19:47:24","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0004427388","MVA=
N","IHS_YND_510","24-02-2025 19:40:43","24-02-2025 19:32:36","24-02-2025 20=
:27:25","Grid Outage Site went down because Gen Failed due to Gen Contactor=
s dysfonction /He Bypass it and Manually Started the Gen","MINKA NICOLAS","=
Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid Outage=
 Site went down because Gen Failed due to Gen Contactors dysfonction /He By=
pass it and Manually Started the Gen","danick.tchakouani@sagemcom.com","488=
","24-02-2025 19:40:43","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004427377","Mon=
tee Jouvence","","24-02-2025 19:38:37","24-02-2025 19:29:31","24-02-2025 20=
:54:47","Grid outage gen failed to start due to ""high temp"" alarm//we add=
 water and gen manually started ","Hyemafo Gildas","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outag=
e gen failed to start due to ""high temp"" alarm//we add water and gen manu=
ally started ","danick.tchakouani@sagemcom.com","547","24-02-2025 19:38:37"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004427303","Ako=
k Ndoe Yde","","24-02-2025 19:27:21","24-02-2025 19:20:09","24-02-2025 20:4=
2:50","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started manually","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// Gen started manually","danick.tchakouani@sagem=
com.com","432","24-02-2025 19:27:21","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004427297","Beh=
ind P T school Yde","","24-02-2025 19:26:01","24-02-2025 19:20:54","24-02-2=
025 20:14:33","Grid outage site went down because Gen failed to start due t=
o Gen card dysfonction // He reset the Gen card and Gen manually started","=
Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage site went down because Gen failed to start due to Gen card dy=
sfonction // He reset the Gen card and Gen manually started","danick.tchako=
uani@sagemcom.com","308","24-02-2025 19:26:01","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004427293","MEF=
OU ASSI","IHS_YND_768","24-02-2025 19:24:24","24-02-2025 19:20:14","24-02-2=
025 19:25:48","Site went down Insufficiency of retifier on site SS IHS Feli=
x Zamb=E9 is informed and confirmed //Site stabilized","Fanda Brice","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down Insuf=
ficiency of retifier on site SS IHS Felix Zamb=E9 is informed and confirmed=
 //Site stabilized","danick.tchakouani@sagemcom.com","252","24-02-2025 19:2=
4:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004427275","M=
vog-Ada_OCM","","24-02-2025 19:23:11","24-02-2025 19:16:54","24-02-2025 19:=
25:54","Active // No power issue site on grid with U=3D54,6 V Tx Fme Armand=
 Ngestsa (691144412) of huawei is informed","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No pow=
er issue site on grid with U=3D54,6 V Tx Fme Armand Ngestsa (691144412) of =
huawei is informed","mariam.tchonang@sagemcom.com","378","24-02-2025 19:23:=
11","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004427265","Obo=
bogo","","24-02-2025 19:21:55","24-02-2025 19:17:48","24-02-2025 19:23:48",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
ted automaticaly","MINKA NICOLAS","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup// Gen started automaticaly","danick.tchakouani@sage=
mcom.com","248","24-02-2025 19:21:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004427259","M=
elen Ba'aba","","24-02-2025 19:20:16","24-02-2025 19:16:56","24-02-2025 19:=
58:40","Grid outage, site went down due to gen overload(15kva, 216A), Blais=
e IHS confirm // Grid return","Siligap Boris","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen overlo=
ad(15kva, 216A), Blaise IHS confirm // Grid return","mariam.tchonang@sagemc=
om.com","202","24-02-2025 19:20:16","Sagemcom CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004427241","Sof=
avinc","","24-02-2025 19:17:01","24-02-2025 19:14:47","24-02-2025 19:18:47"=
,"Grid Outage Site went down because Gen Failed due to Gen Contactors Fault=
y//He Bypass it and Manually Started the Gen","MINKA NICOLAS","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Load Contactor","Grid Outage Site went d=
own because Gen Failed due to Gen Contactors Faulty//He Bypass it and Manua=
lly Started the Gen","danick.tchakouani@sagemcom.com","135","24-02-2025 19:=
17:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004427239","E=
mana Lycee","","24-02-2025 19:16:46","24-02-2025 19:11:30","24-02-2025 20:4=
0:33","Grid outage.site went down due to gen failed to start //Grid return =
(investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage.site went down due to gen faile=
d to start //Grid return (investigation ongoing)","mariam.tchonang@sagemcom=
.com","317","24-02-2025 19:16:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004427231","E=
mana lycee 2","","24-02-2025 19:15:30","24-02-2025 19:10:59","24-02-2025 20=
:03:26","Site went down due to disjunction of Cb (100A) in PWC  // He reame=
 Cb","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Circuit Breaker Issue","Site went down due to disjunction of Cb (=
100A) in PWC  // He reame Cb","mariam.tchonang@sagemcom.com","272","24-02-2=
025 19:15:30","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004427212","Abo=
me","","24-02-2025 19:13:40","24-02-2025 19:08:27","24-02-2025 19:15:38","G=
rid outage, Site went down before Gen start due to poor backup// Gen starte=
d automaticaly","MINKA NICOLAS","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup// Gen started automaticaly","danick.tchakouani@sagemc=
om.com","314","24-02-2025 19:13:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004427211","E=
kombitie","","24-02-2025 19:13:35","24-02-2025 19:10:09","24-02-2025 23:23:=
52","Grid fluctuation, Site went down because Gen failed to start due to Gr=
id bad voltage and  RCP on site // he bypass the Grid and Gen manually star=
ted","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation, Site went down because Gen failed t=
o start due to Grid bad voltage and  RCP on site // he bypass the Grid and =
Gen manually started","mariam.tchonang@sagemcom.com","207","24-02-2025 19:1=
3:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004427132","N=
kolbong","","24-02-2025 19:11:54","24-02-2025 19:05:47","24-02-2025 20:01:5=
8","Grid outage site went down because Gen failed to start due to Gen card =
dysfonction // He reset the Gen card and Gen manually started","Delor Telez=
ing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage site went down because Gen failed to start due to Gen card dysfonctio=
n // He reset the Gen card and Gen manually started","mariam.tchonang@sagem=
com.com","368","24-02-2025 19:11:54","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004427129","Nko=
ulou Carriere carrefourt","","24-02-2025 19:10:37","24-02-2025 19:01:26","2=
5-02-2025 08:32:04","Access issue during the night  Site went down due to d=
isjunction of Rectifier CB(40 A)causing by grid fluctuations // CB put back=
 on","Mba Lazare Herve","Access Denial","Lease Or Legal","Landlord Related =
Issues","Access Issue - Land Lord","Access issue during the night  Site wen=
t down due to disjunction of Rectifier CB(40 A)causing by grid fluctuations=
 // CB put back on","danick.tchakouani@sagemcom.com","552","24-02-2025 19:1=
0:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004427127","A=
wae Ewonkan","","24-02-2025 19:10:01","24-02-2025 19:05:38","24-02-2025 21:=
41:47","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // Grid power return","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went do=
wn because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // Gr=
id power return","mariam.tchonang@sagemcom.com","264","24-02-2025 19:10:01"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004427125","AWA=
E OCM","","24-02-2025 19:09:36","24-02-2025 19:02:23","24-02-2025 19:32:51"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automaticaly","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup// Gen started automaticaly","danick.tchakouani@=
sagemcom.com","434","24-02-2025 19:09:36","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004427120","Awa=
e Escalier","","24-02-2025 19:07:42","24-02-2025 19:00:11","24-02-2025 21:2=
5:48","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started Manually","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup// Gen started Manually","danick.tchakouani@sagemc=
om.com","452","24-02-2025 19:07:42","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004427113","Ema=
na","","24-02-2025 19:05:37","24-02-2025 19:00:27","24-02-2025 19:06:51","G=
rid outage, Site went down before Gen start due to poor backup// Grid power=
 return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup// Grid power return","danick.tchakouani@sagemcom.com","311=
","24-02-2025 19:05:37","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004427076","Elo=
umdem stade","","24-02-2025 18:58:04","24-02-2025 18:57:50","24-02-2025 19:=
23:48","Grid outage, Site went down before Gen start due to poor backup// G=
rid power return","Fanda Brice","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup// Grid power return","danick.tchakouani@sagemcom.com"=
,"15","24-02-2025 18:58:04","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004427062","Aka=
k-Nkozoa-MTN-IHS","","24-02-2025 18:56:41","24-02-2025 18:51:25","24-02-202=
5 19:09:31","Site went down because Gen failed to start due to Grid bad vol=
tage and no RCP on site // Grid stabilized","Fabrice Pouakam","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Site went down=
 because Gen failed to start due to Grid bad voltage and no RCP on site // =
Grid stabilized","danick.tchakouani@sagemcom.com","317","24-02-2025 18:56:4=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004426831","N=
koabang2","","24-02-2025 18:43:29","24-02-2025 18:37:38","24-02-2025 20:15:=
38","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed// Site stabilize","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (22KVA, 330A), SS Blaise IHS is informed// Site stabilize","da=
nick.tchakouani@sagemcom.com","353","24-02-2025 18:43:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004426801","B=
itoto","","24-02-2025 18:41:25","24-02-2025 18:34:13","24-02-2025 20:11:20"=
,"Grid outage,Gen failed to start due to PWC ZTE disfunctionning //He reset=
 the controller and started the Gen","Mba Lazare Herve","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Grid outage,Gen failed=
 to start due to PWC ZTE disfunctionning //He reset the controller and star=
ted the Gen","danick.tchakouani@sagemcom.com","433","24-02-2025 18:41:25","=
Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004426798","Ona=
ngondi (melen bikop)","","24-02-2025 18:41:20","24-02-2025 18:19:11","24-02=
-2025 19:01:11","Hybrid gen site.site went down due to hybrid system malfun=
ctionning//Gen manually started","Fanda Brice","Equipment Repair","Passive"=
,"Hybrid","Hybrid Module","Hybrid gen site.site went down due to hybrid sys=
tem malfunctionning//Gen manually started","mariam.tchonang@sagemcom.com","=
1330","24-02-2025 18:41:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004426670","S=
calom","","24-02-2025 18:31:17","24-02-2025 18:29:02","24-02-2025 22:18:55"=
,"site went down due to Rectifier Issues SS IHS Francois is Informed and Co=
nfirmed it//Site Stablized","Paul BIBOUM","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","site went down due to Rectifier Issues SS IHS F=
rancois is Informed and Confirmed it//Site Stablized","mariam.tchonang@sage=
mcom.com","136","24-02-2025 18:31:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004426603","N=
kolfon Cimencam","","24-02-2025 18:21:35","24-02-2025 19:41:25","24-02-2025=
 21:05:25","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","=
Cascade Active","site went down because fuel spill due to burst return pipe=
 // he replaced the return pipe and Gen manually started  Power issue resol=
ved at site up 21:05 PM But Site remains down ocm after power reset The Tx =
FME Fulbert (654266068) from Huawei is informed","mariam.tchonang@sagemcom.=
com","296461","24-02-2025 18:21:35","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004426435","Awa=
e Escalier","","24-02-2025 18:02:47","24-02-2025 17:55:29","24-02-2025 18:0=
5:29","Grid outage, Site went down before Gen start due to poor backup // G=
rid return","Albran Byorel","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage, Site went down before Gen start d=
ue to poor backup // Grid return","danick.tchakouani@sagemcom.com","439","2=
4-02-2025 18:02:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0004426297","M=
beng","IHS_YND_553","24-02-2025 17:50:07","24-02-2025 17:47:50","24-02-2025=
 18:09:09","Grid outage.en failed to satrt due to automation malfunctionnin=
g//Gen manually started ","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","ATS-AMF Issue","Grid outage.en failed to satrt due to automation=
 malfunctionning//Gen manually started ","mariam.tchonang@sagemcom.com","13=
8","24-02-2025 17:50:07","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004425886","Nko=
abang2","","24-02-2025 17:30:20","24-02-2025 17:25:12","24-02-2025 17:41:12=
","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blaise=
 IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen =
overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","danick.t=
chakouani@sagemcom.com","310","24-02-2025 17:30:20","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004425798","MBA=
LNGONG LYCEE","","24-02-2025 17:20:39","24-02-2025 16:51:22","24-02-2025 20=
:35:02","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed  // Site stabilized"=
,"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid outage, Site went down because Gen stopped due to overload(9kva, 130A) =
SS IHS Felix Zambe is informed and confirmed  // Site stabilized","danick.t=
chakouani@sagemcom.com","1759","24-02-2025 17:20:39","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004425763","Crf=
-Nsam","","24-02-2025 17:16:48","24-02-2025 17:09:34","24-02-2025 19:52:38"=
,"Site went down  because PWC(24kilo) dysfunctionning, IHS SS Pascaline con=
firmed// Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","Site went down  because PWC(24kilo) =
dysfunctionning, IHS SS Pascaline confirmed// Site stabilized","danick.tcha=
kouani@sagemcom.com","435","24-02-2025 17:16:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004425750","A=
wae Ewonkan","","24-02-2025 17:14:59","24-02-2025 17:12:34","24-02-2025 17:=
39:12","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed // site stabilized","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down=
 because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // site=
 stabilized","mariam.tchonang@sagemcom.com","177","24-02-2025 17:14:59","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004425749","Bit=
eng-Maetur","","24-02-2025 17:14:53","24-02-2025 17:11:35","25-02-2025 00:5=
3:50","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed // Grid power retu=
rn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed // Grid power retu=
rn","danick.tchakouani@sagemcom.com","199","24-02-2025 17:14:53","Sagemcom =
CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004425740","Tou=
ring Club International","","24-02-2025 17:13:55","24-02-2025 17:08:45","24=
-02-2025 17:37:33","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed// He reduced load and started Gen manualy"=
,"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid Outage Site went down because Gen overload (20Kw, 270A) SS IHS Pascal=
ine confirmed// He reduced load and started Gen manualy","danick.tchakouani=
@sagemcom.com","311","24-02-2025 17:13:55","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004425732","AWA=
E OCM","","24-02-2025 17:12:18","24-02-2025 17:03:09","24-02-2025 17:15:09"=
,"	Grid outage, Site went down before Gen start due to poor backup// Gen st=
arted automaticaly","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","	Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automaticaly","danick.tchakouan=
i@sagemcom.com","2068","24-02-2025 17:12:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004425727","Mimboman=
4","","24-02-2025 17:11:31","24-02-2025 17:02:40","24-02-2025 17:33:40","Ca=
scaded Incident from TTO4473116","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue U=3D52.2 V sit=
e on Gen. TX FME Leonel Steve (655184876) from huawei is informed","system"=
,"270176","24-02-2025 17:11:31","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004425722","Nko=
lo II New","IHS_YND_266","24-02-2025 17:10:50","24-02-2025 17:02:40","24-02=
-2025 18:20:41","Active//No power issue U=3D52.2 V site on Gen. TX FME Leon=
el Steve (655184876) from huawei is informed","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue U=3D52.2 V site on Gen. TX FME Leonel Steve (65518=
4876) from huawei is informed","danick.tchakouani@sagemcom.com","491","24-0=
2-2025 17:10:50","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004425704","Nko=
ulou Carriere carrefourt","","24-02-2025 17:08:53","24-02-2025 17:05:45","2=
4-02-2025 18:19:45","Grid outage, site went down because gen fails to start=
 due to card gen faulty // Gen manually started","Mba Lazare Herve","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site =
went down because gen fails to start due to card gen faulty // Gen manually=
 started","danick.tchakouani@sagemcom.com","1244","24-02-2025 17:08:53","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004425683","A=
wae Escalier","","24-02-2025 17:05:52","24-02-2025 17:01:39","24-02-2025 17=
:38:12","Grid outage, Site went down before Gen start due to poor backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup // Gen start automatically","mariam.tchonan=
g@sagemcom.com","254","24-02-2025 17:05:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004425570","K=
oweit City","","24-02-2025 16:55:29","24-02-2025 16:41:19","24-02-2025 17:1=
2:05","Site went down because Gen failed to start due to Grid bad voltage a=
nd RCP on site // Grid stabilized","Albran Byorel","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Site went down because Ge=
n failed to start due to Grid bad voltage and RCP on site // Grid stabilize=
d","danick.tchakouani@sagemcom.com","851","24-02-2025 16:55:29","Sagemcom C=
MR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004425378","Tsi=
nga village","","24-02-2025 16:22:46","24-02-2025 16:21:34","24-02-2025 16:=
23:34","Site went down due to insufficiency of rectifier (Site on 02 rectif=
iers) SS IHS Bernard Atangana is informed and confirmed // Site stabilized"=
,"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","	Site went down due to insufficiency of rectifier (Site on 02 rectifier=
s) SS IHS Bernard Atangana is informed and confirmed // Site stabilized","d=
anick.tchakouani@sagemcom.com","73","24-02-2025 16:22:46","Sagemcom CMR"
"Closed Complete","Site Down","T1669","IHS_YND_195","NOCINC0004424686","chi=
na embassy yde","","24-02-2025 15:22:22","24-02-2025 15:19:08","26-02-2025 =
15:37:57","Eneo Distributer burned on site, No space to deploy MDG // Eneo =
normalized Distributer","","Grid Supply","Passive","Grid","National Grid - =
Transformer Issue","Eneo Distributer burned on site, No space to deploy MDG=
 // Eneo normalized Distributer","danick.tchakouani@sagemcom.com","426","24=
-02-2025 15:22:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004424647","M=
ontesquieux","","24-02-2025 15:17:40","24-02-2025 15:14:22","24-02-2025 15:=
18:56","Site went down due to mpr dysfunction disfunctionning SS IHS Blaise=
 Raoul confirmed //  Site stabilized","Paul BIBOUM","Equipment Repair","Pas=
sive","Rectifier","Rectifier Cabinet","Site went down due to mpr dysfunctio=
n disfunctionning SS IHS Blaise Raoul confirmed //  Site stabilized","maria=
m.tchonang@sagemcom.com","198","24-02-2025 15:17:40","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004424519","Aha=
la Echangeur","","24-02-2025 15:06:25","24-02-2025 15:04:18","24-02-2025 16=
:28:18","Site went down due to insufficience of rectifiers SS IHS Pascaline=
 MANDA is informed (01 ) // He added 01 rectifier ","MINKA NICOLAS","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site went down due to=
 insufficience of rectifiers SS IHS Pascaline MANDA is informed (01 ) // He=
 added 01 rectifier ","danick.tchakouani@sagemcom.com","128","24-02-2025 15=
:06:25","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004424424","Com=
plex Beac II","","24-02-2025 14:53:15","24-02-2025 14:47:05","24-02-2025 15=
:22:05","Grid outage site went down because Gen failed to start due to Gen =
card dysfonction // He reset the Gen card and Gen manually started","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage site went down because Gen failed to start due to Gen card dysfon=
ction // He reset the Gen card and Gen manually started","danick.tchakouani=
@sagemcom.com","371","24-02-2025 14:53:15","Sagemcom CMR"
"Cancelled","Warning","CTR_381","IHS_YND_303","NOCINC0004424376","Nyom OCM"=
,"","24-02-2025 14:48:23","","","Error","Fabrice Pouakam","","","","","","d=
anick.tchakouani@sagemcom.com","250","24-02-2025 14:48:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004424323","M=
efou-Assi","","24-02-2025 14:43:03","24-02-2025 14:40:12","24-02-2025 14:45=
:23","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME=
 Fulbert(654266068) from Huawei is informed","mariam.tchonang@sagemcom.com"=
,"172","24-02-2025 14:43:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004424301","M=
vog-Ada_OCM","","24-02-2025 14:40:04","24-02-2025 14:36:54","24-02-2025 15:=
40:54","Active//No power issue on site U=3D52.5V site on grid TX FME Armand=
 Ngetsa/691144412 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site U=3D52.5V site on grid TX FME Armand Ngetsa/691144412 of huawei=
 is informed","danick.tchakouani@sagemcom.com","191","24-02-2025 14:40:04",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004424275","N=
koabang Ebolmedjock","","24-02-2025 14:36:57","24-02-2025 14:21:14","24-02-=
2025 14:21:15","	Active// No power issue, site is on Gen with Ubaie=3D53,6V=
, Lionel Adjep(655184876) from Huawei is informed","Mba Lazare Herve","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","	Active// No power issue, site is on Gen with Ubaie=3D53,6V, Lionel =
Adjep(655184876) from Huawei is informed","danick.tchakouani@sagemcom.com",=
"943","24-02-2025 14:36:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0004424166","N=
kolbi-Boss","","24-02-2025 14:16:44","23-02-2025 18:28:34","23-02-2025 18:3=
5:30","Active//No power issue on site Ubaie =3D52,9V site on Grid The TX  R=
M Alain (691144423) from Huawei is informed. Notice that we have disjunctio=
n at BTS OCM","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue=
 on site Ubaie =3D52,9V site on Grid The TX  RM Alain (691144423) from Huaw=
ei is informed. Notice that we have disjunction at BTS OCM","yves.djomo@sag=
emcom.com","71291","24-02-2025 14:16:44","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004424078","Awa=
e Escalier","","24-02-2025 13:57:43","24-02-2025 13:53:28","24-02-2025 14:3=
0:28","Site went down due to work: Our FME Herv=E9 Lazarre//SAGEMCOM workin=
g on site (remplacement of Grid contactor) // End of work","Albran Byorel",=
"Installation Activity","Passive","Planned Activity","Installation Activity=
","Site went down due to work: Our FME Herv=E9 Lazarre//SAGEMCOM working on=
 site (remplacement of Grid contactor) // End of work","el-dalile@sagemcom.=
com","256","24-02-2025 13:57:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004424049","O=
lembe-Terminus","","24-02-2025 13:52:26","24-02-2025 13:42:50","24-02-2025 =
13:47:02","No power issue, site on Grid with Ubaie=3D 53.5 V. The Fme Tx Sy=
mphorien (650257151/ 675295205) from Huawei is informed. ","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue, site on Grid with Ubaie=3D 53.5 V. The Fme Tx=
 Symphorien (650257151/ 675295205) from Huawei is informed. ","yves.djomo@s=
agemcom.com","578","24-02-2025 13:52:26","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004423952","Av =
Kennedy","","24-02-2025 13:32:46","24-02-2025 13:28:32","24-02-2025 13:35:0=
8","Active//No power issue, site is on Grid with Ubaie=3D50 V, Eloundou ber=
trant(652586578) from Huawei is informed and up at 01:40 PM","","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue, site is on Grid with Ubaie=3D50 V, Eloundou bertra=
nt(652586578) from Huawei is informed and up at 01:40 PM","el-dalile@sagemc=
om.com","255","24-02-2025 13:32:46","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004423810","BIY=
EMASSI NIKI","","24-02-2025 13:11:47","24-02-2025 13:10:34","24-02-2025 13:=
11:56","Grid outage, site went down down due PWC overloaded (12 kw 250A) //=
Site Stabilized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier",=
"Rectifier Module Overloaded","Grid outage, site went down down due PWC ove=
rloaded (12 kw 250A) //Site Stabilized","el-dalile@sagemcom.com","74","24-0=
2-2025 13:11:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004423788","S=
calom-IHS","","24-02-2025 13:02:33","24-02-2025 13:00:29","24-02-2025 13:10=
:30","ACTIVE// No power issue on site Ubaie =3D52.5V site on Grid The TX Fm=
e Hosiah / 674007438// from huawei is informed and up at 01:54 PM","","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","ACTIVE// No power issue on site Ubaie =3D52.5V site on Grid The TX F=
me Hosiah / 674007438// from huawei is informed and up at 01:54 PM","yves.d=
jomo@sagemcom.com","126","24-02-2025 13:02:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004423718","Melen Ba=
'aba","","24-02-2025 12:48:30","24-02-2025 12:42:38","24-02-2025 12:47:13",=
"Cascaded Incident from TTO4470850","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen failed to start with ""overcurrent"" alarm// Grid return","system","2=
63962","24-02-2025 12:48:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0004423717","Nkolfoul=
ou 2","","24-02-2025 12:48:30","24-02-2025 12:42:38","24-02-2025 12:47:13",=
"Cascaded Incident from TTO4470850","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen failed to start with ""overcurrent"" alarm// Grid return","system","2=
63963","24-02-2025 12:48:30","Sagemcom CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004423706","Nko=
lfoulou","IHS_YND_278, IHS_YND_308","24-02-2025 12:45:51","24-02-2025 12:42=
:38","24-02-2025 12:50:55","Grid outage, Site went down because Gen failed =
to start with ""overcurrent"" alarm// Grid return","Siligap Boris","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site w=
ent down because Gen failed to start with ""overcurrent"" alarm// Grid retu=
rn","el-dalile@sagemcom.com","194","24-02-2025 12:45:51","Sagemcom CMR"
"Closed Complete","Site Down","T2564","IHS_YND_739","NOCINC0004423570","NKO=
LMESSING rue Manguier","","24-02-2025 12:36:40","24-02-2025 12:30:26","24-0=
2-2025 12:32:30","Active//No power issue on site U=3D53.2 V Site on GRID. T=
he Team SALOMOMN //694452220// from Ei-Ingeering  is working on site.","Sil=
igap Boris","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue on site U=3D53.2 V Site on G=
RID. The Team SALOMOMN //694452220// from Ei-Ingeering  is working on site.=
","el-dalile@sagemcom.com","375","24-02-2025 12:36:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004423408","B=
ATA Mokolo OCM","","24-02-2025 12:10:51","24-02-2025 12:02:47","24-02-2025 =
16:34:15","Grid outage No space to deploy // Grid power return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No =
space to deploy // Grid power return","yves.djomo@sagemcom.com","485","24-0=
2-2025 12:10:51","Sagemcom CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0004423134","Dra=
gage","","24-02-2025 11:22:34","24-02-2025 11:19:30","24-02-2025 11:20:13",=
"Active//No power issue, site is on Grid with Ubaie=3D54.5V, Eloundou bertr=
ant(652586578) from Huawei is informed","Mboua Thierry","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue, site is on Grid with Ubaie=3D54.5V, Eloundou bertrant(6525=
86578) from Huawei is informed","yves.djomo@sagemcom.com","185","24-02-2025=
 11:22:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004423119","O=
mnisport 3","","24-02-2025 11:20:45","24-02-2025 11:17:40","24-02-2025 11:2=
4:52","Active // No power issue site on grid with U=3D54,6 V Tx Fme Armand =
Ngestsa (691144412) of huawei is informed and up at 11:24 AM","Delor Telezi=
ng","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active // No power issue site on grid with U=3D54,6 V Tx Fm=
e Armand Ngestsa (691144412) of huawei is informed and up at 11:24 AM","yve=
s.djomo@sagemcom.com","186","24-02-2025 11:20:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004422975","Abang","=
","24-02-2025 10:58:00","24-02-2025 10:54:59","24-02-2025 10:56:59","Cascad=
ed Incident from TTO4470013","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site Ubaie =3D5=
3.4V site on Grid The TX FME Henri (699949693) from Huawei is informed. Not=
ice that we have cable burned in BTS OCM","system","270327","24-02-2025 10:=
58:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004422970","N=
kolangaa","IHS_YND_290","24-02-2025 10:56:03","24-02-2025 10:54:59","24-02-=
2025 10:56:59","Active//No power issue on site Ubaie =3D53.4V site on Grid =
The TX FME Henri (699949693) from Huawei is informed. Notice that we have c=
able burned in BTS OCM","Mba Lazare Herve","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power iss=
ue on site Ubaie =3D53.4V site on Grid The TX FME Henri (699949693) from Hu=
awei is informed. Notice that we have cable burned in BTS OCM","yves.djomo@=
sagemcom.com","65","24-02-2025 10:56:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004422817","M=
efou-Assi","","24-02-2025 10:28:29","24-02-2025 10:24:25","24-02-2025 10:30=
:02","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed. Repetitive issue","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site =
On Grid The Tx FME Fulbert(654266068) from Huawei is informed. Repetitive i=
ssue","yves.djomo@sagemcom.com","245","24-02-2025 10:28:29","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004422782","AWA=
E OCM","","24-02-2025 10:24:53","24-02-2025 10:17:37","24-02-2025 10:30:42"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automaticaly","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup// Gen started automaticaly","el-dalile@sagemcom=
.com","1230","24-02-2025 10:24:53","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004422647","Awa=
e Escalier","","24-02-2025 09:59:17","24-02-2025 09:55:12","24-02-2025 10:0=
1:12","Grid outage, Site went down before Gen start due to poor backup// Gr=
id return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup// Grid return","yves.djomo@sagemcom.com","246","24-02-2025=
 09:59:17","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004422572","Crf=
-Nsam","","24-02-2025 09:45:58","24-02-2025 09:44:52","24-02-2025 09:46:40"=
,"Site went down  because PWC(24kilo) dysfunctionning, IHS SS Pascaline con=
firmed// Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","Site went down  because PWC(24kilo) =
dysfunctionning, IHS SS Pascaline confirmed// Site stabilized","yves.djomo@=
sagemcom.com","67","24-02-2025 09:45:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0004422375","M=
essassi","","24-02-2025 09:07:06","24-02-2025 09:01:02","24-02-2025 09:15:0=
1","Active//No power issue on site Ubaie =3D53,2 V site on Grid The TX FME =
Synphorien (650257151) from Huawei is informed and up at 09:17 AM","Fabrice=
 Pouakam","Customer Equipment Failure","Active","Active Equipment Failure",=
"Affected by 3rd Party Site","Active//No power issue on site Ubaie =3D53,2 =
V site on Grid The TX FME Synphorien (650257151) from Huawei is informed an=
d up at 09:17 AM","yves.djomo@sagemcom.com","366","24-02-2025 09:07:06","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004422343","N=
KOLMEKONG YDE","","24-02-2025 09:00:26","24-02-2025 08:55:21","24-02-2025 0=
9:00:06","Active//No power issue on site Ubaie =3D53,2 V site on Grid The T=
X FME Synphorien (650257151) from Huawei is informed","Fabrice Pouakam","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site Ubaie =3D53,2 V site on Grid The TX=
 FME Synphorien (650257151) from Huawei is informed","yves.djomo@sagemcom.c=
om","307","24-02-2025 09:00:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004422270","N=
kolfon Cimencam","","24-02-2025 08:40:40","24-02-2025 08:37:35","24-02-2025=
 08:40:24","No power issue on site U=3D52 V site on Grid.The Tx FME  Fulber=
t  (654266068) of huawei is informed. Repetitive Issue Notice that site is =
impacted by AfanoyaII who is not our responsability","Hyemafo Gildas","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site U=3D52 V site on Grid.The Tx FME  Fulbert  (6=
54266068) of huawei is informed. Repetitive Issue Notice that site is impac=
ted by AfanoyaII who is not our responsability","yves.djomo@sagemcom.com","=
186","24-02-2025 08:40:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004422211","N=
yom OCM","","24-02-2025 08:25:33","24-02-2025 08:19:24","24-02-2025 08:25:4=
9","Active//No power issue on site Ubaie =3D54,2 V site on Gen The TX FME S=
ynphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site Ubaie =3D54,2 V site on Gen The TX FME Syn=
phorien (650257151) from Huawei is informed","el-dalile@sagemcom.com","370"=
,"24-02-2025 08:25:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0004422210","O=
lembe","","24-02-2025 08:24:42","24-02-2025 08:20:36","24-02-2025 08:25:04"=
,"Active//No power issue on site Ubaie =3D53.4V site on Grid The TX FME Syn=
phorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site Ubaie =3D53.4V site on Grid The TX FME Synph=
orien (650257151) from Huawei is informed","yves.djomo@sagemcom.com","247",=
"24-02-2025 08:24:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0004422182","B=
ondjock","","24-02-2025 08:14:25","24-02-2025 08:12:21","24-02-2025 08:57:3=
0","Grid outage, site went down because gen started and stopped with  high =
temp alarm // He added water and manually start the gen","Fanda Brice","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Leve=
l Issue","Grid outage, site went down because gen started and stopped with =
 high temp alarm // He added water and manually start the gen","yves.djomo@=
sagemcom.com","125","24-02-2025 08:14:25","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004422126","Aha=
la Echangeur","","24-02-2025 08:00:28","24-02-2025 07:58:15","24-02-2025 08=
:56:28","Site went down due to insufficience of rectifiers SS IHS Pascaline=
 MANDA is informed (01 )// He added 01 rectifier (01 rectifier to be added)=
","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficience of rectifiers SS IHS Pascaline MAND=
A is informed (01 )// He added 01 rectifier (01 rectifier to be added)","el=
-dalile@sagemcom.com","133","24-02-2025 08:00:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004422109","E=
kombitie","","24-02-2025 07:56:19","24-02-2025 07:32:10","24-02-2025 07:35:=
55","ACTIVE//No power issue on site GRID , Ubaie=3D54.6V site On Grid The T=
x RM Alain(691144423) from Huawei is informed","Fabrice Pouakam","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//No power issue on site GRID , Ubaie=3D54.6V site On Grid The Tx R=
M Alain(691144423) from Huawei is informed","el-dalile@sagemcom.com","1450"=
,"24-02-2025 07:56:19","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004421808","Crf=
-Nsam","","24-02-2025 06:52:45","24-02-2025 06:51:41","24-02-2025 06:53:31"=
,"Site went down  because PWC(24kilo) dysfunctionning, IHS SS Pascaline con=
firmed// Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","Site went down  because PWC(24kilo) =
dysfunctionning, IHS SS Pascaline confirmed// Site stabilized","yves.djomo@=
sagemcom.com","65","24-02-2025 06:52:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004421672","M=
efou-Assi","","24-02-2025 06:11:21","24-02-2025 06:08:13","24-02-2025 06:10=
:46","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME=
 Fulbert(654266068) from Huawei is informed","ludovic-anselme.mouliom-mapou=
re@sagemcom","189","24-02-2025 06:11:21","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004421636","Eko=
mbitie","","24-02-2025 05:59:20","24-02-2025 05:56:48","24-02-2025 07:16:57=
","Grid bad voltage, Site went down because Gen failed to start due to Grid=
 contactor faulty// He bypassed it, Site on grid","Fabrice Pouakam","Equipm=
ent Repair","Passive","Control Panel","ATS-AMF Issue","Grid bad voltage, Si=
te went down because Gen failed to start due to Grid contactor faulty// He =
bypassed it, Site on grid","mariam.tchonang@sagemcom.com","153","24-02-2025=
 05:59:20","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004421620","Nko=
lnda","","24-02-2025 05:48:22","24-02-2025 05:46:06","24-02-2025 06:03:48",=
"Grid outage, site went down because gen start and stopped with  high temp =
alarm // He added water and manually start the gen (investigation ongoing)"=
,"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High Engin=
e Temp - Coolant Level Issue","Grid outage, site went down because gen star=
t and stopped with  high temp alarm // He added water and manually start th=
e gen (investigation ongoing)","mariam.tchonang@sagemcom.com","137","24-02-=
2025 05:48:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004421516","A=
wae Ewonkan","","24-02-2025 05:09:10","23-02-2025 15:01:51","24-02-2025 08:=
49:09","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO confirmed// Grid return. Site up after power reset","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage, Site went down because Gen overload(20KVA,310A) SS IHS Alphonse DEFFO=
 confirmed// Grid return. Site up after power reset","ludovic-anselme.mouli=
om-mapoure@sagemcom","50840","24-02-2025 05:09:10","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004421497","NTU=
I TOWN","","24-02-2025 05:01:59","24-02-2025 04:58:39","24-02-2025 05:59:35=
","Grid outage.gen ran until fuel shortage//Refueling done","Parker Tchoup"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unti=
l fuel shortage//Refueling done","mariam.tchonang@sagemcom.com","201","24-0=
2-2025 05:01:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004421470","Nsimalen=
 OCM","","24-02-2025 04:48:41","24-02-2025 04:34:31","24-02-2025 05:47:30",=
"Cascaded Incident from TTO4468242","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // refueling done","system","271901","24-02-=
2025 04:48:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004421437","N=
kolda","IHS_YND_327","24-02-2025 04:40:53","24-02-2025 04:34:31","24-02-202=
5 05:47:30","Grid outage, site went down because gen ran untill fuel shorta=
ge // refueling done","Albran Byorel","Fuel Outage","Passive","Diesel","Die=
sel Outage","Grid outage, site went down because gen ran untill fuel shorta=
ge // refueling done","mariam.tchonang@sagemcom.com","383","24-02-2025 04:4=
0:53","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004421374","Crf=
-Nsam","","24-02-2025 04:17:47","24-02-2025 04:14:35","24-02-2025 04:16:04"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline is i=
nformed//site stabilised","MINKA NICOLAS","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","Site went down because PWC(24kilo) d=
ysfunctionning, IHS SS Pascaline is informed//site stabilised","mariam.tcho=
nang@sagemcom.com","193","24-02-2025 04:17:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004421330","M=
efou-Assi","","24-02-2025 04:05:31","24-02-2025 04:00:19","24-02-2025 04:05=
:15","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed..","Fanda Brice","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed..","mariam.tchonang@sagemcom.=
com","313","24-02-2025 04:05:31","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004421255","Crf=
-Nsam","","24-02-2025 03:42:29","24-02-2025 03:34:20","24-02-2025 03:36:21"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline is i=
nformed//site stabilised","MINKA NICOLAS","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","Site went down because PWC(24kilo) d=
ysfunctionning, IHS SS Pascaline is informed//site stabilised","mariam.tcho=
nang@sagemcom.com","490","24-02-2025 03:42:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004421247","Eto koss=
 Yde","","24-02-2025 03:36:30","24-02-2025 03:30:28","24-02-2025 04:04:36",=
"Cascaded Incident from TTO4468018","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because 03/07 rectifi=
ers dysfunction//he reset it","system","268320","24-02-2025 03:36:30","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004421248","ELOUMDEM=
 CARRIERE 2","","24-02-2025 03:36:30","24-02-2025 03:30:28","24-02-2025 04:=
04:36","Cascaded Incident from TTO4468018","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because 03/07 =
rectifiers dysfunction//he reset it","system","268320","24-02-2025 03:36:30=
","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004421246","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","24-02-2025 03:35:42","24-02-2025 03:28=
:28","24-02-2025 04:04:36","Site went down because 03/07 rectifiers dysfunc=
tion//he reset it","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down because 03/07 rectifiers dysfunction//he =
reset it","mariam.tchonang@sagemcom.com","541","24-02-2025 03:35:42","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004420913","M=
endong vallee","","24-02-2025 01:41:03","24-02-2025 01:39:52","24-02-2025 0=
1:46:58","ACTIVE//No power issues on site u=3D54.3V site on Gen,  The Tx FM=
E Hosiah//699699694 is informed ","Fanda Brice","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No powe=
r issues on site u=3D54.3V site on Gen,=20
The Tx FME Hosiah//699699694 is informed ","mariam.tchonang@sagemcom.com","=
72","24-02-2025 01:41:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004420228","E=
kombitie","","23-02-2025 22:49:51","23-02-2025 22:46:40","23-02-2025 23:39:=
41","Grid fluctuations site went down because Gen failed to start due to la=
ck of  phases on site // he did a bridge with a good phase ","Fabrice Pouak=
am","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuations site went down because Gen failed to start due to lack=
 of  phases on site // he did a bridge with a good phase ","ludovic-anselme=
.mouliom-mapoure@sagemcom","192","23-02-2025 22:49:51","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004420152","Crf=
-Mbankolo-IHS","","23-02-2025 22:31:51","23-02-2025 22:25:43","24-02-2025 0=
0:17:22","Site went down due to MPR disfunction SS IHS Bernard Atangana con=
firmed//Site stabilized with power reset done","Mboua Thierry","Equipment R=
epair","Passive","Rectifier","Rectifier Cabinet","Site went down due to MPR=
 disfunction SS IHS Bernard Atangana confirmed//Site stabilized with power =
reset done","ludovic-anselme.mouliom-mapoure@sagemcom","369","23-02-2025 22=
:31:51","Sagemcom CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0004420148","Djo=
nassi-Yde","","23-02-2025 22:31:04","23-02-2025 22:22:44","24-02-2025 04:58=
:47","Site went down due to 02/04 rectifier faulty on site SS IIHS bernard =
Atangana is confirm  // He added 02 rectifiers","Fabrice Pouakam","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module","Site went down due to 0=
2/04 rectifier faulty on site SS IIHS bernard Atangana is confirm  // He ad=
ded 02 rectifiers","ludovic-anselme.mouliom-mapoure@sagemcom","501","23-02-=
2025 22:31:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004420062","T=
amtam Weekend","","23-02-2025 22:17:18","23-02-2025 22:08:02","24-02-2025 0=
0:10:29","No power issue iste on grid with U=3D56.3v Mbah Osiah(674007438) =
from Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue iste o=
n grid with U=3D56.3v Mbah Osiah(674007438) from Huawei is informed","danic=
k.tchakouani@sagemcom.com","557","23-02-2025 22:17:18","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004419689","Mon=
tee Jouvence","","23-02-2025 21:16:04","23-02-2025 21:11:57","23-02-2025 21=
:17:01","Grid fluctuation, Site went down because Gen failed to start due t=
o Grid bad voltage // GRid stabilized","Hyemafo Gildas","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Si=
te went down because Gen failed to start due to Grid bad voltage // GRid st=
abilized","wilfried.kameni@sagemcom.com","248","23-02-2025 21:16:04","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004419527","O=
mnisport-Rail","","23-02-2025 20:43:04","23-02-2025 20:40:40","23-02-2025 2=
2:07:05","Site went down due to insufficiency of rectifier IHS SS Bernard A=
tangana is informed // Site stabilized","Delor Telezing","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down due to insufficie=
ncy of rectifier IHS SS Bernard Atangana is informed // Site stabilized","w=
ilfried.kameni@sagemcom.com","145","23-02-2025 20:43:04","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004419465","Eto=
ug ebe biscuiterie","","23-02-2025 20:31:42","23-02-2025 20:01:34","23-02-2=
025 23:06:27","Grid fluctuation, Site went down because Gen failed to start=
 due to Grid bad voltage(lack of one  phase )  // He made a bridge with a g=
ood phase","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Grid fluctuation, Site went down because Gen fai=
led to start due to Grid bad voltage(lack of one  phase )  // He made a bri=
dge with a good phase","wilfried.kameni@sagemcom.com","1808","23-02-2025 20=
:31:42","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004419386","Mel=
en Ba'aba","","23-02-2025 20:23:21","23-02-2025 19:52:25","23-02-2025 20:08=
:40","Grid outage, site went down due to gen overload(15kva, 216A), Blaise =
IHS confirm // site stabilized","Siligap Boris","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen over=
load(15kva, 216A), Blaise IHS confirm // site stabilized","wilfried.kameni@=
sagemcom.com","1857","23-02-2025 20:23:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0004419315","MVAN SAC=
EL","","23-02-2025 20:11:00","23-02-2025 19:54:21","23-02-2025 20:54:13","C=
ascaded Incident from TTO4465762","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage Site went down Because G=
en Failed to Start due to Gen Contators Faulty//He Bypass Gen contactor and=
 site on Gen","system","267024","23-02-2025 20:11:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0004419313","M=
VAN","IHS_YND_510","23-02-2025 20:10:29","23-02-2025 19:54:21","23-02-2025 =
20:55:28","Grid Outage Site went down Because Gen Failed to Start due to Ge=
n Contators Faulty//He Bypass Gen contactor and site on Gen","MINKA NICOLAS=
","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid Out=
age Site went down Because Gen Failed to Start due to Gen Contators Faulty/=
/He Bypass Gen contactor and site on Gen","danick.tchakouani@sagemcom.com",=
"969","23-02-2025 20:10:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004419305","S=
imbock OCM","","23-02-2025 20:09:40","23-02-2025 19:53:17","23-02-2025 23:5=
8:05","ACTIVE//No power issue on site. Site on Grid with Ubaie=3D56V The tx=
 Fme Hosiah (6 74 00 74 38) from Huawei is informed","Hyemafo Gildas","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","ACTIVE//No power issue on site. Site on Grid with Ubaie=3D56V The tx=
 Fme Hosiah (6 74 00 74 38) from Huawei is informed","danick.tchakouani@sag=
emcom.com","984","23-02-2025 20:09:40","Sagemcom CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0004419294","Men=
dong Plateau","","23-02-2025 20:06:33","23-02-2025 19:57:03","23-02-2025 19=
:59:04","No power issue site on grid with U=3D51.2v Notice that we have dys=
junction at MTN Equipements  site up at 09:40 PM  Mbah Osiah from Huawei wa=
s informed ","Hyemafo Gildas","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with =
U=3D51.2v Notice that we have dysjunction at MTN Equipements  site up at 09=
:40 PM  Mbah Osiah from Huawei was informed ","wilfried.kameni@sagemcom.com=
","571","23-02-2025 20:06:33","Sagemcom CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0004419162","Djo=
nassi-Yde","","23-02-2025 19:40:17","23-02-2025 19:35:09","23-02-2025 21:05=
:06","Site went down because the 02/04 rectifier faulty on site SS IIHS ber=
nard Atangana is confirm  // site stabilized","Fabrice Pouakam","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down because th=
e 02/04 rectifier faulty on site SS IIHS bernard Atangana is confirm  // si=
te stabilized","wilfried.kameni@sagemcom.com","308","23-02-2025 19:40:17","=
Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004419147","Elo=
umdem stade","","23-02-2025 19:36:47","23-02-2025 19:17:31","23-02-2025 19:=
52:58","Grid fluctuation, Site went down because Gen failed to start due to=
 Grid bad voltage and no RCP on site  // he bypassed Grid and site on Gen",=
"Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, Site went down because Gen failed to start d=
ue to Grid bad voltage and no RCP on site  // he bypassed Grid and site on =
Gen","danick.tchakouani@sagemcom.com","1157","23-02-2025 19:36:47","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0004419051","C=
arrefourt Nkomo","","23-02-2025 19:22:57","23-02-2025 19:14:39","23-02-2025=
 20:53:47","Grid outage.gen failed to start due to alarm ""low oil pressure=
""//We add oil and gen manually started ","Mba Lazare Herve","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage.gen failed=
 to start due to alarm ""low oil pressure""//We add oil and gen manually st=
arted ","danick.tchakouani@sagemcom.com","499","23-02-2025 19:22:57","Sagem=
com CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004418986","NYO=
M 2 IHS","","23-02-2025 19:12:00","23-02-2025 19:05:48","23-02-2025 19:25:1=
5","Grid fluctuation, Site went down because Gen failed to start due to Gri=
d bad voltage // GRid stabilized","Fabrice Pouakam","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site w=
ent down because Gen failed to start due to Grid bad voltage // GRid stabil=
ized","danick.tchakouani@sagemcom.com","373","23-02-2025 19:12:00","Sagemco=
m CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0004418913","Dra=
gage","","23-02-2025 18:56:18","23-02-2025 18:48:56","23-02-2025 19:02:48",=
"Grid outage, site went down before gen start due to poor battery backup //=
 gen start automatically","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // gen start automatically","wilfri=
ed.kameni@sagemcom.com","443","23-02-2025 18:56:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004418650","B=
iteng-Maetur","","23-02-2025 18:13:24","23-02-2025 18:07:18","23-02-2025 20=
:18:18","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","danick.=
tchakouani@sagemcom.com","367","23-02-2025 18:13:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004418333","ELOUMDEM=
 CARRIERE 2","","23-02-2025 17:18:41","23-02-2025 17:13:39","23-02-2025 21:=
36:14","Cascaded Incident from TTO4464590","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down Insufficiency =
of retifier on site SS IHS Felix Zamb=E9 is informed and confirmed //Site s=
tabilized","system","276601","23-02-2025 17:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004418332","Eto koss=
 Yde","","23-02-2025 17:18:40","23-02-2025 17:13:39","23-02-2025 21:36:14",=
"Cascaded Incident from TTO4464590","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down Insufficiency of reti=
fier on site SS IHS Felix Zamb=E9 is informed and confirmed //Site stabiliz=
ed","system","276601","23-02-2025 17:18:40","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004418323","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","23-02-2025 17:16:53","23-02-2025 17:13=
:39","23-02-2025 21:36:14","Site went down Insufficiency of retifier on sit=
e SS IHS Felix Zamb=E9 is informed and confirmed //Site stabilized","Fanda =
Brice","Equipment Repair","Passive","Rectifier","Rectifier Module","Site we=
nt down Insufficiency of retifier on site SS IHS Felix Zamb=E9 is informed =
and confirmed //Site stabilized","wilfried.kameni@sagemcom.com","196","23-0=
2-2025 17:16:53","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004418227","Mel=
en Ba'aba","","23-02-2025 16:56:03","23-02-2025 16:50:56","23-02-2025 17:22=
:02","(Grid outage, Site went down because Gen overload (15 KVA, 215A) SS I=
HS Blaise Raoul is informed and confirmed//he reduice the Load and Manually=
 started the Gen)","Siligap Boris","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","Grid outage No space to deploy // Grid power re=
turn","wilfried.kameni@sagemcom.com","308","23-02-2025 16:56:03","Sagemcom =
CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004418107","Pha=
rmacie SION","","23-02-2025 16:36:18","23-02-2025 16:35:10","23-02-2025 16:=
46:31","Grid outage site went down before gen start due to poor battery bac=
kup // Geen auatomatically started","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage site went do=
wn before gen start due to poor battery backup // Geen auatomatically start=
ed","wilfried.kameni@sagemcom.com","69","23-02-2025 16:36:18","Sagemcom CMR=
"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004417878","Eto=
ug ebe biscuiterie","","23-02-2025 16:03:26","23-02-2025 15:58:08","23-02-2=
025 17:07:17",",Site went dwn because Gen failed to start due to bad voltag=
e//he made a bridge with a good phase","Hyemafo Gildas","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty",",Site went dwn becau=
se Gen failed to start due to bad voltage//he made a bridge with a good pha=
se","wilfried.kameni@sagemcom.com","318","23-02-2025 16:03:26","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004417863","M=
ontee-Des-Soeurs","","23-02-2025 16:01:03","23-02-2025 15:58:43","23-02-202=
5 15:58:44","No power Issue Site on Grid Ubai =3D54.3 V. The TX FME Mbah Ho=
siah (674007438) is informed .","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power Issue=
 Site on Grid Ubai =3D54.3 V. The TX FME Mbah Hosiah (674007438) is informe=
d .","danick.tchakouani@sagemcom.com","141","23-02-2025 16:01:03","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004417746","Entree C=
ite Verte","","23-02-2025 15:40:51","23-02-2025 15:08:59","23-02-2025 16:07=
:45","Cascaded Incident from TTO4463873","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid otage // Grid power return=
","system","269508","23-02-2025 15:40:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004417744","Nkomkana=
 2","","23-02-2025 15:40:51","23-02-2025 15:08:59","23-02-2025 16:07:45","C=
ascaded Incident from TTO4463873","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid otage // Grid power return","sy=
stem","269509","23-02-2025 15:40:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004417745","Nkomkana=
","","23-02-2025 15:40:51","23-02-2025 15:08:59","23-02-2025 16:07:45","Cas=
caded Incident from TTO4463873","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid otage // Grid power return","system","269508",=
"23-02-2025 15:40:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004417689","C=
ite-Verte","IHS_YND_138, IHS_YND_200, IHS_YND_543","23-02-2025 15:39:11","2=
3-02-2025 15:08:59","23-02-2025 16:07:45","Grid otage // Grid power return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d otage // Grid power return","wilfried.kameni@sagemcom.com","1813","23-02-=
2025 15:39:11","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004417432","Com=
plex Beac II","","23-02-2025 15:09:20","23-02-2025 14:28:09","23-02-2025 16=
:05:09","Grid outage site went down because Gen failed to start due to Gen =
card dysfonction // He reset the Gen card and Gen manually started","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage site went down because Gen failed to start due to Gen card dysfon=
ction // He reset the Gen card and Gen manually started","wilfried.kameni@s=
agemcom.com","2472","23-02-2025 15:09:20","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004417400","NYO=
M FACE MAETUR","","23-02-2025 15:05:12","23-02-2025 15:01:03","23-02-2025 1=
5:24:44","Grid outage site went down because Gen failed to start due to Gen=
 card faulty //Grid power return","Fabrice Pouakam","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage site went down because=
 Gen failed to start due to Gen card faulty //Grid power return","wilfried.=
kameni@sagemcom.com","250","23-02-2025 15:05:12","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004417320","NYO=
M 2 IHS","","23-02-2025 14:49:31","23-02-2025 14:44:18","23-02-2025 15:24:4=
7","Grid fluctuation, Site went down because Gen failed to start due to Gri=
d bad voltage  // GRid stabilized","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site =
went down because Gen failed to start due to Grid bad voltage  // GRid stab=
ilized","wilfried.kameni@sagemcom.com","343","23-02-2025 14:49:31","Sagemco=
m CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004417247","Odz=
a petit marche new","","23-02-2025 14:32:58","23-02-2025 14:29:49","23-02-2=
025 15:56:29","Grid fluctuation, Site went down because Gen failed to start=
 due to Grid bad voltage  // he bypassed Grid and site on Gen","Albran Byor=
el","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, Site went down because Gen failed to start due to Grid=
 bad voltage  // he bypassed Grid and site on Gen","wilfried.kameni@sagemco=
m.com","190","23-02-2025 14:32:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0004417157","Eloumdem=
 stade","","23-02-2025 14:16:40","23-02-2025 13:54:58","23-02-2025 13:54:59=
","Cascaded Incident from TTO4463203","Fanda Brice","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue iste on gen with U=3D5=
4v site up at 01:53 AM Flubert from Huawei is informed","system","274232","=
23-02-2025 14:16:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_260","NOCINC0004417128","Simbock =
Maetur","","23-02-2025 14:09:21","23-02-2025 13:54:58","23-02-2025 13:54:59=
","Cascaded Incident from TTO4463203","Hyemafo Gildas","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue iste on gen with U=
=3D54v site up at 01:53 AM Flubert from Huawei is informed","system","27423=
1","23-02-2025 14:09:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_520","NOCINC0004417127","SIMBOCK =
BONAMBAPE","","23-02-2025 14:09:20","23-02-2025 13:54:58","23-02-2025 13:54=
:59","Cascaded Incident from TTO4463203","Hyemafo Gildas","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue iste on gen with=
 U=3D54v site up at 01:53 AM Flubert from Huawei is informed","system","274=
232","23-02-2025 14:09:20","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004417122","Sim=
bock MTN","IHS_YND_520, IHS_YND_260, IHS_YND_793","23-02-2025 14:08:22","23=
-02-2025 13:54:58","23-02-2025 13:54:59","No power issue iste on gen with U=
=3D54v TX FME Flubert from Huawei is informed","Fanda Brice","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue iste on gen with U=3D54v FME TX Flubert from Huawei is informe=
d","wilfried.kameni@sagemcom.com","805","23-02-2025 14:08:22","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004416993","S=
calom-IHS","","23-02-2025 13:41:41","23-02-2025 13:22:24","23-02-2025 13:22=
:25","ACTIVE// No power issue on site Ubaie =3D50.8V site on Grid The TX Fm=
e Hosiah / 674007438// from huawei is informed","","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No =
power issue on site Ubaie =3D50.8V site on Grid The TX Fme Hosiah / 6740074=
38// from huawei is informed","mariam.tchonang@sagemcom.com","1159","23-02-=
2025 13:41:41","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004416950","Mvo=
g-Betsi","","23-02-2025 13:33:58","23-02-2025 13:25:32","23-02-2025 13:43:3=
4","Site went down due to 4/8 rectifier dysfunction // reset done and gen s=
tarted","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to 4/8 rectifier dysfunction // reset done an=
d gen started","wilfried.kameni@sagemcom.com","506","23-02-2025 13:33:58","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004416918","Leboudi"=
,"","23-02-2025 13:29:16","23-02-2025 12:23:27","23-02-2025 14:52:48","Casc=
aded Incident from TTO4462561","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
due to gen gen overload(20Kva, 380A), SS IHS Pascaline is informed// Grid p=
ower return","system","279603","23-02-2025 13:29:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_261","NOCINC0004416875","Barriere=
","","23-02-2025 13:22:00","23-02-2025 13:18:48","23-02-2025 13:24:48","Cas=
caded Incident from TTO4462901","Hyemafo Gildas","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to PWC Overloaded =
(12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site stabilized","system","124=
0033","23-02-2025 13:22:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004416871","M=
ontee-Jouvence-II","IHS_YND_261","23-02-2025 13:21:00","23-02-2025 13:16:48=
","23-02-2025 13:24:48","Site went down due to PWC Overloaded (12K, 250A)SS=
 IHS Felix Zamb=E9 confirmed // Site stabilized","Hyemafo Gildas","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went do=
wn due to PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site =
stabilized","mariam.tchonang@sagemcom.com","356","23-02-2025 13:21:00","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004416808","A=
WAE OCM","","23-02-2025 13:06:29","23-02-2025 13:03:03","23-02-2025 13:47:0=
3","Grid outage, site went down due to PWC ZTE malfunction // Gen manually =
started","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Recti=
fier Module Overloaded","Grid outage, site went down due to PWC ZTE malfunc=
tion // Gen manually started","mariam.tchonang@sagemcom.com","207","23-02-2=
025 13:06:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004416779","N=
kolfoulou","IHS_YND_719","23-02-2025 12:59:51","23-02-2025 12:58:38","23-02=
-2025 13:00:33","Grid outage site went down because Gen failed to start due=
 to ATS dysfonction // Grid power return and Reset the ATS","Siligap Boris"=
,"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage =
site went down because Gen failed to start due to ATS dysfonction // Grid p=
ower return and Reset the ATS","mariam.tchonang@sagemcom.com","74","23-02-2=
025 12:59:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0004416675","A=
FEME NORD","","23-02-2025 12:39:12","23-02-2025 12:23:27","23-02-2025 14:53=
:40","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage, site went down due to gen gen overload=
(20Kva, 380A), SS IHS Pascaline is informed// Grid power return","mariam.tc=
honang@sagemcom.com","279602","23-02-2025 12:39:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004416599","A=
wae Escalier","","23-02-2025 12:26:24","23-02-2025 12:23:12","23-02-2025 13=
:49:20","Grid outage, site went down because gen ran untill fuel shortage /=
/ refueling done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage, site went down because gen ran untill fuel shortage /=
/ refueling done","mariam.tchonang@sagemcom.com","193","23-02-2025 12:26:24=
","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004416592","Nko=
lafeme","IHS_YND_309, IHS_YND_519","23-02-2025 12:26:05","23-02-2025 12:23:=
27","23-02-2025 14:53:40","Grid outage, site went down due to gen gen overl=
oad(20Kva, 380A), SS IHS Pascaline is informed// Grid power return","TIENTC=
HEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Grid outage, site went down due to gen gen overload(20Kva, 380A), SS IH=
S Pascaline is informed// Grid power return","ervine.mbezele@sagemcom.com",=
"159","23-02-2025 12:26:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0004416580","Dagobert=
","","23-02-2025 12:24:10","23-02-2025 11:36:45","23-02-2025 11:36:46","Cas=
caded Incident from TTO4462231","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D54v=
 site on grid Tx fme Mohamadou of huawei is informed","system","282208","23=
-02-2025 12:24:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0004416286","N=
kolbi-Boss","IHS_YND_286","23-02-2025 12:00:03","23-02-2025 11:36:45","23-0=
2-2025 11:36:46","No power issue on site U=3D54v site on grid Tx fme Mohama=
dou of huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site U=3D54v site on grid Tx fme Mohamadou of huawei is informed",=
"mariam.tchonang@sagemcom.com","1400","23-02-2025 12:00:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004416229","Nkomkana=
","","23-02-2025 11:49:51","23-02-2025 11:16:02","23-02-2025 12:38:30","Cas=
caded Incident from TTO4462047","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage site went down because Gen failed to st=
art with alarm Gen under voltage // He reset the Gen card and Gen manually =
started","system","276498","23-02-2025 11:49:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004416230","Entree C=
ite Verte","","23-02-2025 11:49:51","23-02-2025 11:16:02","23-02-2025 12:38=
:30","Cascaded Incident from TTO4462047","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen failed to start with alarm Gen under voltage // He reset the Gen ca=
rd and Gen manually started","system","276497","23-02-2025 11:49:51","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004416199","M=
essa-Carriere OCM","","23-02-2025 11:43:37","23-02-2025 11:37:37","24-02-20=
25 07:44:13","Grid outage, No space to deploy MDG// Grid power return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age, No space to deploy MDG// Grid power return","mariam.tchonang@sagemcom.=
com","361","23-02-2025 11:43:37","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004416157","BAT=
A Mokolo OCM","","23-02-2025 11:33:27","23-02-2025 11:16:02","23-02-2025 12=
:38:30","Grid outage.no space to deploy mobile gen//Grid return","","Cascad=
e Outage","Passive","Cascade Passive","Cascade Passive","Grid outage site w=
ent down because Gen failed to start with alarm Gen under voltage // He res=
et the Gen card and Gen manually started","ervine.mbezele@sagemcom.com","10=
46","23-02-2025 11:33:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004416153","Mimboman=
4","","23-02-2025 11:31:41","23-02-2025 11:23:36","23-02-2025 12:53:32","Ca=
scaded Incident from TTO4462067","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went because the PWC DYSFONCT=
ION due to load increased // he repaired the PWC ","system","283413","23-02=
-2025 11:31:41","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004416146","Nko=
lo II New","IHS_YND_266","23-02-2025 11:30:58","23-02-2025 11:23:36","23-02=
-2025 12:53:32","Site went because the PWC DYSFONCTION due to load increase=
d // he repaired the PWC ","Mba Lazare Herve","Equipment Repair","Passive",=
"Rectifier","Rectifier Module Overloaded","Site went because the PWC DYSFON=
CTION due to load increased // he repaired the PWC ","ervine.mbezele@sagemc=
om.com","443","23-02-2025 11:30:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_122","IHS_YND_230","NOCINC0004416127","M=
eyong-Meyeme","IHS_YND_202, IHS_YND_200, IHS_YND_559, IHS_YND_543","23-02-2=
025 11:25:22","23-02-2025 11:16:02","23-02-2025 12:38:30","Grid outage site=
 went down because Gen stopped with alarm Gen over current // He reset the =
Gen card and Gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went do=
wn because Gen failed to start with alarm Gen under voltage // He reset the=
 Gen card and Gen manually started","mariam.tchonang@sagemcom.com","1705","=
23-02-2025 11:25:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004416085","C=
ite-Verte","","23-02-2025 11:18:05","23-02-2025 11:16:02","23-02-2025 12:38=
:30","Grid outage site went down because Gen failed to start with alarm Gen=
 under voltage // He reset the Gen card and Gen manually started","","Casca=
de Outage","Passive","Cascade Passive","Cascade Passive","Grid outage site =
went down because Gen failed to start with alarm Gen under voltage // He re=
set the Gen card and Gen manually started","mariam.tchonang@sagemcom.com","=
276497","23-02-2025 11:18:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0004415986","T=
SINGA VILLAGE 2","","23-02-2025 11:02:38","23-02-2025 12:58:38","23-02-2025=
 13:00:33","","Delor Telezing","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage site went down because Gen failed to start =
due to ATS dysfonction // Grid power return and Reset the ATS","mariam.tcho=
nang@sagemcom.com","284826","23-02-2025 11:02:38","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004415962","Com=
plex Beac II","","23-02-2025 10:58:47","23-02-2025 10:55:32","23-02-2025 12=
:15:27","Site went down due to work: Our Technician Albran/657108542/SAGEMC=
OM working on site (He Normalized ATS )//end off Work","Albran Byorel","Equ=
ipment Repair","Passive","Planned Activity","Planned Activity - DCGG Gen","=
Site went down due to work: Our Technician Albran/657108542/SAGEMCOM workin=
g on site (He Normalized ATS )//end off Work","ervine.mbezele@sagemcom.com"=
,"196","23-02-2025 10:58:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004415874","E=
kombitie","","23-02-2025 10:44:43","23-02-2025 10:41:23","23-02-2025 10:46:=
54","Active// No power issue site on grid with U=3D54,5v Symphorien from Hu=
awei is informed","Fabrice Pouakam","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue sit=
e on grid with U=3D54,5v Symphorien from Huawei is informed","mariam.tchona=
ng@sagemcom.com","201","23-02-2025 10:44:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0004415778","N=
kolbi-Boss","","23-02-2025 10:27:48","23-02-2025 10:16:34","23-02-2025 10:4=
1:46","Grid Outage  Site went down because Gen stopped with alarm undervolt=
age  //He Reset  the Gen Card  and  Gen manually started  ","TIENTCHEU NZET=
CHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid Outage  Site went down because Gen stopped with alarm undervoltage  /=
/He Reset  the Gen Card  and  Gen manually started  ","mariam.tchonang@sage=
mcom.com","675","23-02-2025 10:27:48","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004415776","OBA=
M NGOLA OCM","","23-02-2025 10:27:04","23-02-2025 10:25:55","23-02-2025 13:=
15:23","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed  =
// Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Site went down due to PSC3 dysfonction SS IHS Pasc=
aline confirmed  // Site stabilized","ervine.mbezele@sagemcom.com","69","23=
-02-2025 10:27:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004415774","Entree C=
ite Verte","","23-02-2025 10:26:51","23-02-2025 10:06:10","23-02-2025 10:38=
:13","Cascaded Incident from TTO4461581","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage// He deployed MDG o=
f 20 KVA","system","1215668","23-02-2025 10:26:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0004415773","BATA Mok=
olo OCM","","23-02-2025 10:26:51","23-02-2025 10:06:10","23-02-2025 10:38:1=
3","Cascaded Incident from TTO4461581","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid outage// He deployed MDG of 20 KVA","sy=
stem","1215669","23-02-2025 10:26:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004415772","Nkomkana=
","","23-02-2025 10:26:50","23-02-2025 10:06:10","23-02-2025 10:38:13","Cas=
caded Incident from TTO4461581","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage// He deployed MDG of 20 KVA","system","=
1215667","23-02-2025 10:26:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004415703","C=
ite-Verte","IHS_YND_138, IHS_YND_200, IHS_YND_559, IHS_YND_543","23-02-2025=
 10:12:27","23-02-2025 10:06:10","23-02-2025 10:38:13","Grid outage// He de=
ployed MDG of 20 KVA","","Grid Supply","Passive","Grid","National Grid - Gr=
id Outage Issue","Grid outage// He deployed MDG of 20 KVA","mariam.tchonang=
@sagemcom.com","378","23-02-2025 10:12:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004415698","N=
komkana 2","","23-02-2025 10:11:24","23-02-2025 10:06:10","23-02-2025 10:38=
:13","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage// He deployed MDG of 20 KVA","mariam.tchonang@sage=
mcom.com","1215667","23-02-2025 10:11:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004414927","Ngoum","=
","23-02-2025 08:13:40","23-02-2025 08:11:49","23-02-2025 09:41:33","Cascad=
ed Incident from TTO4460742","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went because Gen ran un=
til fuel shortage// Refueling Done","system","272983","23-02-2025 08:13:40"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0004414914","Yok=
o MTN","IHS_YND_475","23-02-2025 08:13:04","23-02-2025 08:11:49","23-02-202=
5 09:41:33","Grid outage, Site went because Gen ran until fuel shortage// R=
efueling Done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, Site went because Gen ran until fuel shortage// Refuelin=
g Done","ervine.mbezele@sagemcom.com","76","23-02-2025 08:13:04","Sagemcom =
CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004414862","Awa=
e Ewonkan","","23-02-2025 08:02:15","23-02-2025 07:59:08","23-02-2025 11:38=
:34","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed // site stabilized","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down b=
ecause Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed // site s=
tabilized","ervine.mbezele@sagemcom.com","386","23-02-2025 08:02:15","Sagem=
com CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004414844","Mes=
sa Carriere","","23-02-2025 07:58:05","23-02-2025 07:56:55","23-02-2025 08:=
21:30","Grid outage, site went down because gen failed to start due to Gen =
card faulty  SS IHS  Pascalin is informed and confirmed/Gen manually starte=
d","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid outage, site went down because gen failed to start due to Gen =
card faulty  SS IHS  Pascalin is informed and confirmed/Gen manually starte=
d","ervine.mbezele@sagemcom.com","71","23-02-2025 07:58:05","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004414742","Nko=
g-Edzen","","23-02-2025 07:44:27","23-02-2025 07:41:19","23-02-2025 08:37:5=
8","Grid outage, site went down because gen start and stopped with high tem=
p alarm // he added water and manually start the Gen","Parker Tchoup","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // he added water and manually start the Gen","ervine.mbezele@=
sagemcom.com","189","23-02-2025 07:44:27","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004414431","Nko=
ulou Carriere carrefourt","","23-02-2025 06:44:33","23-02-2025 06:41:02","2=
3-02-2025 11:17:02","Grid outage, site went down because gen fails to start=
 due to battery gen faulty // Gen start with batterie backup","Mba Lazare H=
erve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","G=
rid outage, site went down because gen fails to start due to battery gen fa=
ulty // Gen start with batterie backup","ervine.mbezele@sagemcom.com","212"=
,"23-02-2025 06:44:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004414430","M=
efou-Assi","","23-02-2025 06:44:32","23-02-2025 06:40:12","23-02-2025 06:45=
:33","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed..","Fanda Brice","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed..","mariam.tchonang@sagemcom.=
com","261","23-02-2025 06:44:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0004414397","Carrefou=
rt Nkomo","","23-02-2025 06:36:10","23-02-2025 06:16:08","23-02-2025 07:14:=
16","Cascaded Incident from TTO4460165","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 because gen start and stopped with high temp alarm // he added water and m=
anually start the Gen","system","272858","23-02-2025 06:36:10","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0004414391","N=
komo","IHS_YND_174","23-02-2025 06:32:59","23-02-2025 06:16:08","23-02-2025=
 07:17:34","Grid outage, site went down because gen start and stopped with =
high temp alarm // he added water and manually start the Gen","Mba Lazare H=
erve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Co=
olant Level Issue","Grid outage, site went down because gen start and stopp=
ed with high temp alarm // he added water and manually start the Gen","mari=
am.tchonang@sagemcom.com","1012","23-02-2025 06:32:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004414380","N=
KOLMEKONG YDE","","23-02-2025 06:30:28","23-02-2025 06:25:10","23-02-2025 0=
6:31:03","Site went down because PWC dysfunctionning IHS SS BERNARD ATANGAN=
A is informed and confirmed// Site stabilized","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went dow=
n because PWC dysfunctionning IHS SS BERNARD ATANGANA is informed and confi=
rmed// Site stabilized","mariam.tchonang@sagemcom.com","319","23-02-2025 06=
:30:28","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004414127","AWA=
E OCM","","23-02-2025 05:14:02","23-02-2025 05:09:52","23-02-2025 06:24:41"=
,"Grid outage, site went down due to PWC ZTE malfunction // Gen manually st=
arted","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Grid outage, site went down due to PWC ZTE malfuncti=
on // Gen manually started","ludovic-anselme.mouliom-mapoure@sagemcom","252=
","23-02-2025 05:14:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004413960","A=
wae Escalier","","23-02-2025 04:29:04","23-02-2025 04:17:55","23-02-2025 06=
:27:23","Grid outage, Site went because Gen ran until fuel shortage//Refuel=
ing Done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, Site went because Gen ran until fuel shortage//Refueling Done=
","cedric.tiani@sagemcom.com","670","23-02-2025 04:29:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004413917","O=
dza II OCM","","23-02-2025 04:23:41","23-02-2025 04:17:24","23-02-2025 04:1=
8:33","wrongly ticket","Albran Byorel","Incorrectly Logged Tickets","Error"=
,"Error","Error","wrongly ticket","cedric.tiani@sagemcom.com","3257","23-02=
-2025 04:23:41","Sagemcom CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0004413700","Kon=
dengui MTN","","23-02-2025 02:45:21","22-02-2025 02:26:53","23-02-2025 05:1=
0:19","Grid outage.gen failed to start due to battery GE faulty//Gen manual=
ly started with external battery ","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Generator Battery","Grid outage.gen failed to start=
 due to battery GE faulty//Gen manually started with external battery ","lu=
dovic-anselme.mouliom-mapoure@sagemcom","87509","23-02-2025 02:45:21","Sage=
mcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004413372","Elo=
umdem stade","","23-02-2025 00:55:19","23-02-2025 00:39:00","23-02-2025 01:=
56:44","No power issue site on grid with U=3D56.5v Notice that site is impa=
cted by Simbock Maetur ","Fanda Brice","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D56.5v Notice that site is impacted by Simbock Maetur ","mariam=
.tchonang@sagemcom.com","980","23-02-2025 00:55:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_520","NOCINC0004413364","SIMBOCK =
BONAMBAPE","","23-02-2025 00:54:20","23-02-2025 00:39:31","23-02-2025 01:53=
:14","Cascaded Incident from TTO4458983","Hyemafo Gildas","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage.site went down d=
ue to gen failed to start //Grid retur(investigation ongoing)","system","27=
8453","23-02-2025 00:54:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_259","NOCINC0004413365","Simbock =
MTN","","23-02-2025 00:54:20","23-02-2025 00:39:31","23-02-2025 05:27:50","=
No power issue iste on gen  with U=3D54v site up at 01:53 AM Flubert from H=
uawei is informed","Fanda Brice","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue iste on gen  wi=
th U=3D54v site up at 01:53 AM Flubert from Huawei is informed","system","8=
89","23-02-2025 00:54:20","Sagemcom CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0004413361","Sim=
bock Maetur","IHS_YND_520","23-02-2025 00:52:46","23-02-2025 00:39:31","23-=
02-2025 01:53:14","Grid outage.site went down due to gen failed to start //=
Grid return(investigation ongoing)","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage.site went down due to=
 gen failed to start //Grid retur(investigation ongoing)","mariam.tchonang@=
sagemcom.com","796","23-02-2025 00:52:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004413145","M=
efou-Assi","","23-02-2025 00:18:10","23-02-2025 00:16:03","23-02-2025 00:21=
:03","ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The =
Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed","cedric.tiani@sagemcom.com",=
"128","23-02-2025 00:18:10","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004413092","Bar=
riere","","23-02-2025 00:06:18","22-02-2025 23:56:01","23-02-2025 00:24:54"=
,"Site went down due to pwc overload (20k,  450A) the ss IHS Felix is infor=
med//Site stabilized","Hyemafo Gildas","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Site went down due to pwc overload (20k=
,  450A) the ss IHS Felix is informed//Site stabilized","ludovic-anselme.mo=
uliom-mapoure@sagemcom","617","23-02-2025 00:06:18","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004413080","Mon=
tee Jouvence","","23-02-2025 00:03:36","22-02-2025 23:56:08","23-02-2025 01=
:56:21","Grid outage.gen failed to start causing by  to high temp alam//we =
add water and gen manually started","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age.gen failed to start causing by  to high tep alam//w edd water and gen m=
anually started","ludovic-anselme.mouliom-mapoure@sagemcom","448","23-02-20=
25 00:03:36","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004413010","Acc=
acia New","","22-02-2025 23:41:09","22-02-2025 23:32:58","22-02-2025 23:42:=
51","Grid outage.no space to deploy mobile gen//grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no spa=
ce to deploy mobile gen//grid return","ludovic-anselme.mouliom-mapoure@sage=
mcom","493","22-02-2025 23:41:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004412872","S=
calom-IHS","","22-02-2025 23:13:08","22-02-2025 23:11:53","22-02-2025 23:12=
:46","ACTIVE// No power issue on site Ubaie =3D50.8V site on Grid The TX Fm=
e Hosiah / 674007438// from huawei is informed.site up at 11:17 PM","","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","ACTIVE// No power issue on site Ubaie =3D50.8V site on Grid The TX =
Fme Hosiah / 674007438// from huawei is informed.site up at 11:17 PM","mari=
am.tchonang@sagemcom.com","76","22-02-2025 23:13:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004412836","K=
oweit City","","22-02-2025 23:07:37","22-02-2025 23:05:17","22-02-2025 23:2=
2:17","Site went down because Gen failed to start due to Grid bad voltage a=
nd RCP on site // Grid stabilized","Albran Byorel","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Site went down because Ge=
n failed to start due to Grid bad voltage and RCP on site // Grid stabilize=
d","ludovic-anselme.mouliom-mapoure@sagemcom","141","22-02-2025 23:07:37","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0004412773","N=
ew-Marche-Melen","","22-02-2025 22:59:00","22-02-2025 22:56:35","22-02-2025=
 23:57:22","Grid outage.gen ran until fuel shortage//Refueling done Power i=
ssue resolved but site remains down at MTN at 11:57 AM Power reset has done=
 ","Paul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age.gen ran until fuel shortage//Refueling done Power issue resolved but si=
te remains down at MTN at 11:57 AM Power reset has done ","mariam.tchonang@=
sagemcom.com","146","22-02-2025 22:59:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004412748","Afanoya"=
,"","22-02-2025 22:55:11","22-02-2025 22:50:37","22-02-2025 23:00:36","Casc=
aded Incident from TTO4458277","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, Site went down becau=
se Gen failed to start due to Grid bad voltage  // Grid stabilized","system=
","1213042","22-02-2025 22:55:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0004412747","MBALNGON=
G LYCEE","","22-02-2025 22:55:11","22-02-2025 22:50:37","22-02-2025 23:00:3=
6","Cascaded Incident from TTO4458277","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down =
because Gen failed to start due to Grid bad voltage  // Grid stabilized","s=
ystem","1213042","22-02-2025 22:55:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0004412745","ELOUMDEM=
 CARRIERE","","22-02-2025 22:55:10","22-02-2025 22:50:37","22-02-2025 23:00=
:36","Cascaded Incident from TTO4458277","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation, Site went dow=
n because Gen failed to start due to Grid bad voltage  // Grid stabilized",=
"system","1213043","22-02-2025 22:55:10","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004412735","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","22-02-2025 22:53:54","22-02-20=
25 22:50:37","22-02-2025 23:00:37","Grid fluctuation, Site went down becaus=
e Gen failed to start due to Grid bad voltage  // Grid stabilized","Hyemafo=
 Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation, Site went down because Gen failed to start due to=
 Grid bad voltage  // Grid stabilized","ludovic-anselme.mouliom-mapoure@sag=
emcom","198","22-02-2025 22:53:54","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0004412697","Mvo=
g-Betsi","","22-02-2025 22:47:06","22-02-2025 22:41:55","22-02-2025 22:59:3=
7","Grid fluctuation, Site went down because Gen failed to start due to Gri=
d bad voltage  // Grid stabilized","Hyemafo Gildas","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, Site w=
ent down because Gen failed to start due to Grid bad voltage  // Grid stabi=
lized","ludovic-anselme.mouliom-mapoure@sagemcom","312","22-02-2025 22:47:0=
6","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004412687","MEF=
OU ASSI","","22-02-2025 22:45:13","22-02-2025 22:37:03","22-02-2025 22:49:2=
9","Site went down Insufficiency of retifier on site SS IHS Felix Zamb=E9 i=
s informed and confirmed //Site stabilized","Fanda Brice","Equipment Repair=
","Passive","Rectifier","Rectifier Module","Site went down Insufficiency of=
 retifier on site SS IHS Felix Zamb=E9 is informed and confirmed //Site sta=
bilized","ludovic-anselme.mouliom-mapoure@sagemcom","492","22-02-2025 22:45=
:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0004412648","B=
ISCUITERIE","","22-02-2025 22:43:27","22-02-2025 22:41:06","22-02-2025 22:4=
4:46","No power issue site on grid with U=3D52.2v Mbah Osiah(674007438) fro=
m Huawei is informed site up at 10:44 PM","Paul BIBOUM","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on grid with U=3D52.2v Mbah Osiah(674007438) from Huawei is in=
formed site up at 10:44 PM","mariam.tchonang@sagemcom.com","142","22-02-202=
5 22:43:27","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004412309","Acc=
acia New","","22-02-2025 22:06:19","22-02-2025 22:05:07","22-02-2025 22:23:=
08","Grid outage//Grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage//Grid return","ferot.nongni-djiogap@=
sagemcom.com","74","22-02-2025 22:06:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004412158","Eto koss=
 Yde","","22-02-2025 21:42:00","22-02-2025 21:37:35","22-02-2025 21:41:41",=
"Cascaded Incident from TTO4457636","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down Insufficiency of reti=
fier on site SS IHS Felix Zamb=E9 is informed and confirmed waiting site St=
abilized","system","267785","22-02-2025 21:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004412160","ELOUMDEM=
 CARRIERE 2","","22-02-2025 21:42:00","22-02-2025 21:37:35","22-02-2025 21:=
41:41","Cascaded Incident from TTO4457636","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down Insufficiency =
of retifier on site SS IHS Felix Zamb=E9 is informed and confirmed waiting =
site Stabilized","system","267784","22-02-2025 21:42:00","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004412154","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","22-02-2025 21:40:41","22-02-2025 21:37=
:35","22-02-2025 21:41:41","Site went down Insufficiency of retifier on sit=
e SS IHS Felix Zamb=E9 is informed and confirmed waiting site Stabilized","=
Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Module","S=
ite went down Insufficiency of retifier on site SS IHS Felix Zamb=E9 is inf=
ormed and confirmed waiting site Stabilized","ferot.nongni-djiogap@sagemcom=
.com","187","22-02-2025 21:40:41","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004412102","Mon=
tee Jouvence","","22-02-2025 21:36:07","22-02-2025 21:34:55","22-02-2025 21=
:40:16","Site went down because gen failed to start due to grid bad voltage=
 //  site stabilised  and on Grid","Hyemafo Gildas","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Site went down because g=
en failed to start due to grid bad voltage //  site stabilised  and on Grid=
","ferot.nongni-djiogap@sagemcom.com","73","22-02-2025 21:36:07","Sagemcom =
CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004412090","Eto=
ug ebe biscuiterie","","22-02-2025 21:34:14","22-02-2025 21:28:07","22-02-2=
025 21:34:26","Site went down due to Insufficiency of rectifiers, SS IHS Fr=
an=E7ois NDOUNGOU confirmed// Site stabilized","Hyemafo Gildas","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down due to Ins=
ufficiency of rectifiers, SS IHS Fran=E7ois NDOUNGOU confirmed// Site stabi=
lized","ferot.nongni-djiogap@sagemcom.com","367","22-02-2025 21:34:14","Sag=
emcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004411884","Com=
plex Beac II","","22-02-2025 21:01:51","22-02-2025 20:59:40","22-02-2025 21=
:59:32","Site went down due to  32A CB  in  PWC faulty// he bypassed it  ",=
"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier - Circu=
it Breaker","Site went down due to  32A CB  in  PWC faulty// he bypassed it=
  ","ferot.nongni-djiogap@sagemcom.com","132","22-02-2025 21:01:51","Sagemc=
om CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004411623","Crf=
-Nsam","","22-02-2025 20:19:56","22-02-2025 20:14:51","22-02-2025 23:26:33"=
,"Site went down because MPR  dysfunctionning, IHS SS Pascaline is informed=
 and confirmed // site stabilized","MINKA NICOLAS","Equipment Repair","Pass=
ive","Rectifier","Rectifier Cabinet","Site went down because MPR  dysfuncti=
onning, IHS SS Pascaline is informed and confirmed // site stabilized","fer=
ot.nongni-djiogap@sagemcom.com","306","22-02-2025 20:19:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004411622","M=
elen Ba'aba","","22-02-2025 20:19:33","22-02-2025 20:15:11","22-02-2025 21:=
25:51","Grid outage, site went down due to gen overload(15kva, 216A), Blais=
e IHS confirm // Grid return","Siligap Boris","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage, site went down due to gen overlo=
ad(15kva, 216A), Blaise IHS confirm // Grid return","cedric.tiani@sagemcom.=
com","263","22-02-2025 20:19:33","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004411593","Elo=
umdem stade","","22-02-2025 20:15:57","22-02-2025 20:14:41","22-02-2025 21:=
11:57","Site went down because gen failed to start due to grid bad voltage =
// Gen manually started","Fanda Brice","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","Site went down because gen failed to =
start due to grid bad voltage // Gen manually started","cedric.tiani@sagemc=
om.com","77","22-02-2025 20:15:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004411544","N=
kolfon Cimencam","","22-02-2025 20:08:44","22-02-2025 20:05:39","22-02-2025=
 20:10:41","Site impacted by afanoya 2(is not managed by IHS)","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","Affe=
cted by 3rd Party Site","Site impacted by afanoya 2(is not managed by IHS)"=
,"ferot.nongni-djiogap@sagemcom.com","186","22-02-2025 20:08:44","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004411439","E=
koumdoum","","22-02-2025 19:53:56","22-02-2025 19:46:38","22-02-2025 20:24:=
10","Grid fluctuation,Site went down because GEN failed to start due to gri=
d bad voltage(lack of 2 phase)//he bypassed the Grid site on GEN","Albran B=
yorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation,Site went down because GEN failed to start due to gr=
id bad voltage(lack of 2 phase)//he bypassed the Grid site on GEN","cedric.=
tiani@sagemcom.com","439","22-02-2025 19:53:56","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004411355","Ngo=
a Ekelle","","22-02-2025 19:35:00","22-02-2025 19:28:53","22-02-2025 19:40:=
52","Grid flutuation, Site went down before Gen start due to poor backup/ /=
/ Gen automatically started","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid flutuation, Site went down=
 before Gen start due to poor backup/ // Gen automatically started","ferot.=
nongni-djiogap@sagemcom.com","368","22-02-2025 19:35:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004411310","A=
wae Ewonkan","","22-02-2025 19:26:30","22-02-2025 19:23:17","22-02-2025 19:=
31:48","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS=
 Alphonse DEFFO is informed//site stabilized","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down b=
ecause Gen overload(20KVA,310A) SS IHS Alphonse DEFFO is informed//site sta=
bilized","cedric.tiani@sagemcom.com","194","22-02-2025 19:26:30","Sagemcom =
CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004410784","Acc=
acia New","","22-02-2025 18:13:29","22-02-2025 18:08:10","22-02-2025 18:26:=
50","Grid outage, no space to deploy a mobil gen // grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, n=
o space to deploy a mobil gen // grid return","cedric.tiani@sagemcom.com","=
321","22-02-2025 18:13:29","Sagemcom CMR"
"Closed Complete","Site Down","T1746","IHS_YND_178","NOCINC0004410660","Emo=
mbo","","22-02-2025 17:49:06","22-02-2025 17:19:46","22-02-2025 19:24:31","=
ACTIVE//No power issue on site U=3D54,6 V site on Grid ,FME ivan kamlo (678=
945713) from IENG Working on site(working on transmission)","Mba Lazare Her=
ve","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","ACTIVE//No power issue on site U=3D54,6 V site on Grid ,FME=
 ivan kamlo (678945713) from IENG Working on site(working on transmission)"=
,"cedric.tiani@sagemcom.com","1760","22-02-2025 17:49:06","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004410014","Ako=
k Ndoe Yde","","22-02-2025 16:17:44","22-02-2025 16:06:36","22-02-2025 17:0=
5:21","Grid outage, Site went down before Gen start due to poor backup// Ge=
n manually started","Hyemafo Gildas","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// Gen manually started","wilfried.kameni@sagemco=
m.com","669","22-02-2025 16:17:44","Sagemcom CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0004409965","Sim=
e Building","","22-02-2025 16:09:43","22-02-2025 15:44:25","22-02-2025 18:3=
5:58","Grid outage, Site went because Gen ran until fuel shortage// Refueli=
ng Done","Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, Site went because Gen ran until fuel shortage// Refueling Done=
","cedric.tiani@sagemcom.com","1518","22-02-2025 16:09:43","Sagemcom CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0004409733","Eto=
ug-Ebe 2","","22-02-2025 15:40:41","22-02-2025 15:38:34","22-02-2025 18:30:=
51","Grid outage, no space to deploy a mobil gen // grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, n=
o space to deploy a mobil gen // grid return","wilfried.kameni@sagemcom.com=
","128","22-02-2025 15:40:41","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004409709","NKO=
MKANA ELIZA HOTEL","","22-02-2025 15:35:57","22-02-2025 15:25:48","22-02-20=
25 15:30:52","Site went down because gen failed to start due to grid bad vo=
ltgae // Grid stabilized","","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Site went down because gen failed to start due =
to grid bad voltgae // Grid stabilized","wilfried.kameni@sagemcom.com","299=
2","22-02-2025 15:35:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004409648","A=
kak-Nkozoa-MTN-IHS","","22-02-2025 15:30:06","22-02-2025 15:25:00","22-02-2=
025 15:30:00","Grid flutuation ,Site went down because Gen failed to start =
due to grid bad voltage // Grid stabilized","Fabrice Pouakam","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid flutuatio=
n ,Site went down because Gen failed to start due to grid bad voltage // Gr=
id stabilized","wilfried.kameni@sagemcom.com","307","22-02-2025 15:30:06","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004409573","S=
calom-IHS","","22-02-2025 15:18:05","22-02-2025 14:20:56","22-02-2025 16:42=
:05","Grid outage No space to deploy a mobil gen // Grid power return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age No space to deploy a mobil gen // Grid power return","wilfried.kameni@s=
agemcom.com","3431","22-02-2025 15:18:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_044","NOCINC0004409434","Polytech=
nique","","22-02-2025 14:55:00","22-02-2025 14:45:43","22-02-2025 15:09:36"=
,"Cascaded Incident from TTO4454488","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Site went down because Gen started and stopped=
 due to pellet radiator pierced// he glued the Pellet and Manually Started =
The Gen","system","1227868","22-02-2025 14:55:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_076","NOCINC0004409433","Le Flamb=
oyant","","22-02-2025 14:55:00","22-02-2025 14:45:43","22-02-2025 15:09:36"=
,"Cascaded Incident from TTO4454488","Paul BIBOUM","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because Gen started =
and stopped due to pellet radiator pierced// he glued the Pellet and Manual=
ly Started The Gen","system","1227868","22-02-2025 14:55:00","Sagemcom CMR"
"Closed Complete","Site Down","T0817","IHS_YND_061","NOCINC0004409402","Yde=
 University","IHS_YND_076, IHS_YND_043, IHS_YND_044","22-02-2025 14:49:57",=
"22-02-2025 14:45:43","22-02-2025 17:00:36","Site went down because Gen sta=
rted and stopped due to pellet radiator pierced// he glued the Pellet and M=
anually Started The Gen","Paul BIBOUM","Equipment Repair","Passive","ACDG G=
en","ACDG - High Engine Temp - Radiator Leakage","Site went down because Ge=
n started and stopped due to pellet radiator pierced// he glued the Pellet =
and Manually Started The Gen","wilfried.kameni@sagemcom.com","254","22-02-2=
025 14:49:57","Sagemcom CMR"
"Closed Complete","Site Down","T3172","IHS_YND_043","NOCINC0004409391","Emi=
a","","22-02-2025 14:47:14","22-02-2025 14:45:43","22-02-2025 15:09:36","",=
"","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Site wen=
t down because Gen started and stopped due to pellet radiator pierced// he =
glued the Pellet and Manually Started The Gen","wilfried.kameni@sagemcom.co=
m","1227869","22-02-2025 14:47:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004409329","N=
komkana 2","","22-02-2025 14:38:07","22-02-2025 13:20:43","22-02-2025 16:54=
:56","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage No space // Grid power return","wilfried.kameni@sa=
gemcom.com","276076","22-02-2025 14:38:07","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004409158","OBA=
M NGOLA OCM","","22-02-2025 14:14:42","22-02-2025 13:59:26","22-02-2025 14:=
27:47","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed /=
/ Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Site went down due to PSC3 dysfonction SS IHS Pasca=
line confirmed // Site stabilized","wilfried.kameni@sagemcom.com","917","22=
-02-2025 14:14:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0004409131","B=
iyemassi LAC","","22-02-2025 14:09:06","22-02-2025 14:05:27","22-02-2025 18=
:10:27","Active: no power issue, site is on grid with Ubaie=3D53V; Hosiah(6=
74007438) from Huawei is informed","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, s=
ite is on grid with Ubaie=3D53V; Hosiah(674007438) from Huawei is informed"=
,"wilfried.kameni@sagemcom.com","220","22-02-2025 14:09:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004409109","B=
iteng-Maetur","","22-02-2025 14:06:28","22-02-2025 13:57:08","22-02-2025 19=
:03:24","Grid outage, Site went down due to Gen overload(20KVA, 260A) SS IH=
S Blaise confirmed// grid return","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to Gen=
 overload(20KVA, 260A) SS IHS Blaise confirmed// grid return","wilfried.kam=
eni@sagemcom.com","562","22-02-2025 14:06:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0004409041","Kondengu=
i","","22-02-2025 13:52:50","22-02-2025 13:44:56","22-02-2025 16:54:47","Ca=
scaded Incident from TTO4454024","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage No space //Grid power ret=
urn","system","274797","22-02-2025 13:52:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0004409015","E=
mombo-Tchad","IHS_YND_114","22-02-2025 13:51:12","22-02-2025 13:44:56","22-=
02-2025 16:54:47","Grid outage No space //Grid power return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No spa=
ce //Grid power return","mariam.tchonang@sagemcom.com","377","22-02-2025 13=
:51:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0004408977","A=
n-Marche-Melen","","22-02-2025 13:44:24","22-02-2025 13:41:11","22-02-2025 =
16:58:50","Grid outage, no space to deploy a mobil gen // Grid return ","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage, no space to deploy a mobil gen // Grid return ","mariam.tchonang@sage=
mcom.com","194","22-02-2025 13:44:24","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004408969","Crf=
-Mbankolo-IHS","","22-02-2025 13:44:00","22-02-2025 13:36:53","22-02-2025 1=
6:58:28","Grid outage, site went down due to Gen overload(15kva,240A), Bern=
ar IHS is informed// Grid return","Mboua Thierry","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage, site went down due to Gen ov=
erload(15kva,240A), Bernar IHS is informed// Grid return","wilfried.kameni@=
sagemcom.com","428","22-02-2025 13:44:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0004408961","M=
adagascar-Yde-New","IHS_YND_138","22-02-2025 13:42:50","22-02-2025 13:20:43=
","22-02-2025 16:54:56","BACKTRACKING .Grid outage No space // Grid power r=
eturn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Grid outage No space // Grid power return","wilfried.kameni@sagemcom.com=
","1328","22-02-2025 13:42:50","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0004408851","Eko=
mbitie","","22-02-2025 13:24:44","22-02-2025 13:20:35","22-02-2025 15:41:27=
","Site went down because gen failed to start due to grd bad voltage // Gen=
 manually started","Fabrice Pouakam","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","Site went down because gen failed to st=
art due to grd bad voltage // Gen manually started","wilfried.kameni@sagemc=
om.com","285","22-02-2025 13:24:44","Sagemcom CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0004408846","Eto=
udi 2","","22-02-2025 13:23:26","22-02-2025 13:07:15","22-02-2025 15:12:34"=
,"Active // No power issue site on Gen with U=3D53,5 V Tx Fme Armand Ngests=
a (691144412) of huawei is informed ","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue site on Gen with U=3D53,5 V Tx Fme Armand Ngestsa (691144=
412) of huawei is informed ","wilfried.kameni@sagemcom.com","972","22-02-20=
25 13:23:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004408592","Abang","=
","22-02-2025 12:59:09","22-02-2025 12:53:26","22-02-2025 12:58:15","Cascad=
ed Incident from TTO4453517","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE//U=3D 53.2V site on GRID.Georges (=
 691145055) /From HUAWEI is informed ","system","277921","22-02-2025 12:59:=
09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004408567","N=
kolangaa","IHS_YND_290","22-02-2025 12:54:37","22-02-2025 12:53:26","22-02-=
2025 15:58:15","ACTIVE//U=3D 53.2V site on GRID.Georges ( 691145055) /From =
HUAWEI is informed ","Mba Lazare Herve","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//U=3D 53.2V site=
 on GRID.Georges ( 691145055) /From HUAWEI is informed ","wilfried.kameni@s=
agemcom.com","72","22-02-2025 12:54:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0004408458","B=
ATA-Mokolo","","22-02-2025 12:34:05","22-02-2025 12:25:57","22-02-2025 16:5=
4:36","Grid outage, no space to deploy a mobil gen // grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 no space to deploy a mobil gen // grid return","wilfried.kameni@sagemcom.c=
om","489","22-02-2025 12:34:05","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004408395","Pha=
rmacie SION","","22-02-2025 12:24:26","22-02-2025 12:17:07","22-02-2025 12:=
28:07","Grid outage, Site went down before Gen start due to poor backup// G=
en started automaticaly","Paul BIBOUM","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automaticaly","wilfried.kameni@s=
agemcom.com","440","22-02-2025 12:24:26","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004408385","Nsi=
meyong Shell","","22-02-2025 12:23:30","22-02-2025 12:15:22","22-02-2025 16=
:38:44","Grid outage,Gen failed to start because there is no gen cable to s=
tart the GEN//grid return","MINKA NICOLAS","Equipment Repair","Passive","Co=
ntrol Panel","ATS-AMF Issue","Grid outage,Gen failed to start because there=
 is no gen cable to start the GEN//grid return","wilfried.kameni@sagemcom.c=
om","489","22-02-2025 12:23:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004408368","S=
hell-Nsimeyong","","22-02-2025 12:21:43","22-02-2025 12:13:33","22-02-2025 =
16:34:01","Grid outage,Gen failed to start because there is no gen cable to=
 start the GEN//grid return","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","ATS-AMF Issue","Grid outage,Gen failed to start because the=
re is no gen cable to start the GEN//grid return","wilfried.kameni@sagemcom=
.com","491","22-02-2025 12:21:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004408355","S=
calom","","22-02-2025 12:20:01","22-02-2025 12:11:54","22-02-2025 12:11:55"=
,"No power issue , Ubaie=3D54.5 V site on Gen.The FME TX Mbah Hosiah (67400=
7438) from Huawei is informed","Paul BIBOUM","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue , U=
baie=3D54.5 V site on Gen.The FME TX Mbah Hosiah (674007438) from Huawei is=
 informed","wilfried.kameni@sagemcom.com","488","22-02-2025 12:20:01","Sage=
mcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004408290","Sap=
eur","","22-02-2025 12:09:09","22-02-2025 12:05:36","22-02-2025 12:19:36","=
Grid outage, Site went down before Gen start due to poor backup// Gen start=
ed automaticaly","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup// Gen started automaticaly","wilfried.kameni@sagemco=
m.com","215","22-02-2025 12:09:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004408229","B=
iteng-Maetur","","22-02-2025 12:03:07","22-02-2025 11:57:56","22-02-2025 13=
:23:56","Grid outage, Site went down due to Gen overload(20KVA, 260A) SS IH=
S Blaise confirmed// Grid return","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to Gen=
 overload(20KVA, 260A) SS IHS Blaise confirmed// Grid return","wilfried.kam=
eni@sagemcom.com","312","22-02-2025 12:03:07","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004408184","Eto=
ug ebe biscuiterie","","22-02-2025 11:58:31","22-02-2025 11:51:24","22-02-2=
025 17:54:11","Site went down due to Insufficiency of rectifiers, SS IHS Fr=
an=E7ois NDOUNGOU  confirmed// Site stabilized","Hyemafo Gildas","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","Site went down due to In=
sufficiency of rectifiers, SS IHS Fran=E7ois NDOUNGOU  confirmed// Site sta=
bilized","wilfried.kameni@sagemcom.com","427","22-02-2025 11:58:31","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_520","NOCINC0004408172","SIMBOCK =
BONAMBAPE","","22-02-2025 11:55:00","22-02-2025 11:43:19","22-02-2025 11:48=
:53","Cascaded Incident from TTO4453034","Hyemafo Gildas","Cascade Outage",=
"Active","Cascade Active","Cascade Active","ACTIVE//No power issue on site =
GRID , Ubaie=3D54.5V site On Grid The Tx FME Fulbert(654266068) from Huawei=
 is informed","system","281894","22-02-2025 11:55:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0004408173","Eloumdem=
 stade","","22-02-2025 11:55:00","22-02-2025 11:43:19","22-02-2025 11:48:53=
","Cascaded Incident from TTO4453034","Fanda Brice","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID ,=
 Ubaie=3D54.5V site On Grid The Tx FME Fulbert(654266068) from Huawei is in=
formed","system","281895","22-02-2025 11:55:00","Sagemcom CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0004408167","Mai=
son komkana New","","22-02-2025 11:53:38","22-02-2025 11:45:29","22-02-2025=
 17:02:29","Grid outage site went down before gen start due to poor battery=
 backup // Geen manually started","Mboua Thierry","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","Grid outage, no space to deploy =
a mobil gen // grid return","wilfried.kameni@sagemcom.com","489","22-02-202=
5 11:53:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0004408158","H=
-Progres","","22-02-2025 11:52:06","22-02-2025 11:43:40","22-02-2025 16:52:=
40","Grid outage, no space ti deploy a mobil gen // grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, n=
o space ti deploy a mobil gen // grid return","wilfried.kameni@sagemcom.com=
","507","22-02-2025 11:52:06","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004408150","Sim=
bock MTN","IHS_YND_520, IHS_YND_793","22-02-2025 11:49:28","22-02-2025 11:4=
3:19","22-02-2025 14:48:53","ACTIVE//No power issue on site GRID , Ubaie=3D=
54.5V site On Grid The Tx FME Fulbert(654266068) from Huawei is informed","=
Fanda Brice","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D54.5=
V site On Grid The Tx FME Fulbert(654266068) from Huawei is informed","wilf=
ried.kameni@sagemcom.com","370","22-02-2025 11:49:28","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0004408142","Nko=
mkana","","22-02-2025 11:46:54","22-02-2025 11:41:43","22-02-2025 16:54:46"=
,"Grid outage, no space to deploy a mobil gen // grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no s=
pace to deploy a mobil gen // grid return","wilfried.kameni@sagemcom.com","=
432","22-02-2025 11:46:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_369","IHS_YND_019","NOCINC0004408090","H=
otel de Ville Yde","","22-02-2025 11:38:34","22-02-2025 11:30:10","22-02-20=
25 11:30:11","Active // No power issue on site U=3D54V on grid Team Antoine=
/657011008/ from I-Ing is working on site","Paul BIBOUM","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue on site U=3D54V on grid Team Antoine/657011008/ from I-I=
ng is working on site","wilfried.kameni@sagemcom.com","505","22-02-2025 11:=
38:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0004408084","Bastos E=
koudou","","22-02-2025 11:36:44","22-02-2025 11:30:23","22-02-2025 14:44:26=
","Cascaded Incident from TTO4452880","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage No space // Grid pow=
er return","system","282697","22-02-2025 11:36:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004408069","M=
efou-Assi","","22-02-2025 11:35:09","22-02-2025 11:30:02","22-02-2025 11:40=
:22","No power issue on site Ubaie=3D54.5V site On Grid.  The Tx FME Fulber=
t (654266068) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site Ubaie=3D54.5V site On Grid.The Tx FME Fulbert (654266068) from=
 Huawei is informed","wilfried.kameni@sagemcom.com","307","22-02-2025 11:35=
:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004408053","c=
hina embassy yde","","22-02-2025 11:34:24","22-02-2025 11:29:17","22-02-202=
5 16:53:14","Grid outage, no space to deploy a mobil gen // grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy a mobil gen // grid return","wilfried.kameni@sage=
mcom.com","308","22-02-2025 11:34:24","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004408013","Lab=
oratoire  Meka","IHS_YND_193","22-02-2025 11:32:51","22-02-2025 11:30:23","=
22-02-2025 14:44:26","Grid outage No space // Grid power return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No=
 space // Grid power return","mariam.tchonang@sagemcom.com","149","22-02-20=
25 11:32:51","Sagemcom CMR"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0004407934","COR=
NIERS","","22-02-2025 11:27:45","22-02-2025 11:26:37","22-02-2025 14:38:38"=
,"Grid outage, no space to deploy a mobil gen // grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no s=
pace to deploy a mobil gen // grid return","wilfried.kameni@sagemcom.com","=
69","22-02-2025 11:27:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004407469","E=
ssomba","","22-02-2025 10:50:16","22-02-2025 09:49:21","22-02-2025 11:23:21=
","Site went down because 02/05 rectifier dysfonction on site due to load i=
ncreased // He reset the rectifier on site","Mba Lazare Herve","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down because 02/=
05 rectifier dysfonction on site due to load increased // He reset the rect=
ifier on site","wilfried.kameni@sagemcom.com","3657","22-02-2025 10:50:16",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0004407336","M=
ini-Ferme","","22-02-2025 10:40:42","22-02-2025 10:32:35","22-02-2025 15:34=
:46","Grid outage No space //Grid power return","","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid outage No space //Grid pow=
er return","wilfried.kameni@sagemcom.com","488","22-02-2025 10:40:42","Sage=
mcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004407284","Tou=
ring Club International","","22-02-2025 10:31:41","22-02-2025 10:23:16","22=
-02-2025 10:47:16","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed// He reduced load and started Gen manualy"=
,"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid Outage Site went down because Gen overload (20Kw, 270A) SS IHS Pascal=
ine confirmed// He reduced load and started Gen manualy","wilfried.kameni@s=
agemcom.com","505","22-02-2025 10:31:41","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004407272","NKO=
LOSSAN OKOK","","22-02-2025 10:28:42","22-02-2025 10:19:37","22-02-2025 11:=
17:55","Grid outage, Site went down because Gen ran untill fuel shortage// =
Refueling ongoing","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage, Site went down because Gen ran untill fuel shortage/=
/ Refueling ongoing","wilfried.kameni@sagemcom.com","546","22-02-2025 10:28=
:42","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004407053","Eto=
ug ebe biscuiterie","","22-02-2025 09:53:43","22-02-2025 09:51:28","22-02-2=
025 11:09:30","Grid fluctuation, site went down because Gen failed to start=
 due to Grid bad voltage and No RCP // Grid stabilized","Hyemafo Gildas","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d fluctuation, site went down because Gen failed to start due to Grid bad v=
oltage and No RCP // Grid stabilized","wilfried.kameni@sagemcom.com","136",=
"22-02-2025 09:53:43","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004407040","AWA=
E OCM","","22-02-2025 09:50:48","22-02-2025 09:47:40","22-02-2025 10:46:55"=
,"Grid outage, site went down due to PWC ZTE malfunction // Gen manually st=
arted","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Grid outage, site went down due to PWC ZTE malfunction // Gen m=
anually started","wilfried.kameni@sagemcom.com","212","22-02-2025 09:50:48"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0004407038","Lob=
o 2","","22-02-2025 09:50:14","22-02-2025 09:46:05","22-02-2025 13:01:20","=
Grid outage, site went down because Gen STARTED and stopped due to ""high t=
emp"" alarm // We add water and gen manually started","TIENTCHEU NZETCHIEU =
GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Co=
olant Level Issue","Grid outage, site went down because Gen STARTED and sto=
pped due to ""high temp"" alarm // We add water and gen manually started","=
wilfried.kameni@sagemcom.com","250","22-02-2025 09:50:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0004406980","B=
ONAS YDE","","22-02-2025 09:41:05","22-02-2025 09:39:50","22-02-2025 09:49:=
14","Grid outage, Site went because Gen ran until fuel shortage//Refueling =
Done","Paul BIBOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid =
outage, Site went because Gen ran until fuel shortage//Refueling Done","mar=
iam.tchonang@sagemcom.com","75","22-02-2025 09:41:05","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004406810","Fla=
menco","","22-02-2025 09:10:20","22-02-2025 09:07:01","22-02-2025 10:19:51"=
,"Grid outage site went down because Gen failed to start due to Gen card fa=
ulty // Gen manually started","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen f=
ailed to start due to Gen card faulty // Gen manually started","wilfried.ka=
meni@sagemcom.com","200","22-02-2025 09:10:20","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004406726","Nko=
lbisson usines des eaux 2","","22-02-2025 08:57:40","22-02-2025 08:53:26","=
22-02-2025 10:13:35","Grid outage site went down because Gen failed to star=
t  // Gen manually started (investigation ongoing)","TIENTCHEU NZETCHIEU GA=
EL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage site went down because Gen failed to start  // Gen manually started (i=
nvestigation ongoing)","wilfried.kameni@sagemcom.com","255","22-02-2025 08:=
57:40","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0004406700","AFE=
ME NORD","IHS_YND_808","22-02-2025 08:50:47","22-02-2025 08:44:37","22-02-2=
025 11:50:25","Site unstable due to 02/05 rectifiers faulty SS IHS Pascalin=
e is informed // site stabilized","TIENTCHEU NZETCHIEU GAEL","Equipment Rep=
air","Passive","Rectifier","Rectifier Module","Site unstable due to 02/05 r=
ectifiers faulty SS IHS Pascaline is informed // site stabilized","wilfried=
.kameni@sagemcom.com","371","22-02-2025 08:50:47","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004406670","BAT=
A Mokolo OCM","","22-02-2025 08:42:38","22-02-2025 08:35:28","22-02-2025 16=
:58:51","Grid outage, no space to deploy a mobil gen// Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, no space to deploy a mobil gen// Grid return","wilfried.kameni@sagemcom.c=
om","431","22-02-2025 08:42:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004406493","C=
RH-Etoug-Ebe","","22-02-2025 08:13:53","22-02-2025 08:08:46","22-02-2025 08=
:24:41","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen automatically started","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down before gen start due to poor battery backup // Gen automatically sta=
rted","wilfried.kameni@sagemcom.com","308","22-02-2025 08:13:53","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0004406467","C=
NR","","22-02-2025 08:07:43","22-02-2025 08:04:25","22-02-2025 08:09:36","G=
rid outage, Site went down before Gen start due to poor backup// Gen automa=
tically started","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup// Gen automatically started","wilfried.kameni@sagemc=
om.com","198","22-02-2025 08:07:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004406384","M=
ontee-Des-Soeurs","","22-02-2025 07:53:07","22-02-2025 07:39:59","22-02-202=
5 09:30:34","Grid outage, site went down before gen start due to poor batte=
ry backup // Gen manually started","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // Gen manually started",=
"wilfried.kameni@sagemcom.com","790","22-02-2025 07:53:07","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004406171","SIM=
BOCK BONAMBAPE","","22-02-2025 07:09:41","22-02-2025 07:01:22","22-02-2025 =
07:46:17","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, Site went because Gen ran until fuel shorta=
ge// Refueling Done","wilfried.kameni@sagemcom.com","1219620","22-02-2025 0=
7:09:41","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004406148","Sim=
bock MTN","IHS_YND_520, IHS_YND_793","22-02-2025 07:07:29","22-02-2025 07:0=
1:22","22-02-2025 07:46:17","Grid outage, Site went because Gen ran until f=
uel shortage// Refueling Done","Fanda Brice","Fuel Outage","Passive","Diese=
l","Diesel Outage","Grid outage, Site went because Gen ran until fuel short=
age// Refueling Done","wilfried.kameni@sagemcom.com","368","22-02-2025 07:0=
7:29","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004406142","Elo=
umdem stade","","22-02-2025 07:06:43","22-02-2025 07:01:22","22-02-2025 07:=
46:17","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, Site went because Gen ran until fuel shortage// R=
efueling Done","wilfried.kameni@sagemcom.com","1219620","22-02-2025 07:06:4=
3","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004406089","Aha=
la Echangeur","","22-02-2025 06:55:14","22-02-2025 06:52:04","22-02-2025 12=
:56:02","Site went down because 01/02 rectictiers faulty SS IHS Pascaline i=
s informed// Site stabilized (rectifier to be replaced)","MINKA NICOLAS","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went down b=
ecause 01/02 rectictiers faulty SS IHS Pascaline is informed// Site stabili=
zed (rectifier to be replaced)","wilfried.kameni@sagemcom.com","190","22-02=
-2025 06:55:14","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004405867","OBA=
M NGOLA OCM","","22-02-2025 06:27:05","22-02-2025 06:23:59","22-02-2025 12:=
23:06","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed /=
/ Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Site went down due to PSC3 dysfonction SS IHS Pasca=
line confirmed // Site stabilized","yves.djomo@sagemcom.com","187","22-02-2=
025 06:27:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004405833","C=
rf-Nsam","","22-02-2025 06:19:51","22-02-2025 06:13:43","22-02-2025 06:20:1=
0","Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline is=
 informed and confirmed // site stabilized","MINKA NICOLAS","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Site went down bec=
ause PWC(24kilo) dysfunctionning, IHS SS Pascaline is informed and confirme=
d // site stabilized","yves.djomo@sagemcom.com","369","22-02-2025 06:19:51"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0004405689","AFE=
ME NORD","IHS_YND_808","22-02-2025 05:18:51","22-02-2025 05:16:47","22-02-2=
025 08:03:08","Site  unstable due to 02/05 rectifiers faulty SS IHS Pascali=
ne is informed // site stabilized","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site  unstable due to 02/05=
 rectifiers faulty SS IHS Pascaline is informed // site stabilized","yves.d=
jomo@sagemcom.com","125","22-02-2025 05:18:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004405664","M=
efou-Assi","","22-02-2025 05:09:33","22-02-2025 05:06:28","22-02-2025 05:10=
:46","ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The =
Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed","yves.djomo@sagemcom.com","1=
85","22-02-2025 05:09:33","Sagemcom CMR"
"Closed Complete","Site Down","T1747","IHS_YND_728","NOCINC0004405082","TRO=
PICANA NEW","","22-02-2025 00:14:39","22-02-2025 00:08:21","22-02-2025 04:1=
4:53","Site went down because CB(80A) tripped in PWC due to load increase//=
 CB put back on ","MINKA NICOLAS","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","Site went down because CB(80A)=
 tripped in PWC due to load increase// CB put back on ","el-dalile@sagemcom=
.com","379","22-02-2025 00:14:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004405010","N=
kolfon Cimencam","","21-02-2025 23:47:08","21-02-2025 23:36:04","21-02-2025=
 23:40:47","No power issue on site U=3D50.8 V site on Grid.The Tx FME  Fulb=
ert  (654266068) of huawei is informed. Repetitive Issue Notice that site i=
s impacted by AfanoyaII who is not our responsability","Hyemafo Gildas","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue on site U=3D50.8 V site on Grid.The Tx FME  Fulbert=
  (654266068) of huawei is informed. Repetitive Issue Notice that site is i=
mpacted by AfanoyaII who is not our responsability","yves.djomo@sagemcom.co=
m","664","21-02-2025 23:47:08","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004404996","Nko=
ulou Carriere carrefourt","","21-02-2025 23:40:22","21-02-2025 22:53:02","2=
2-02-2025 00:02:59","Grid outage, site went down because gen fails to start=
 due to card gen faulty // Grid return","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down=
 because gen fails to start due to card gen faulty // Grid return","el-dali=
le@sagemcom.com","2841","21-02-2025 23:40:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004404886","Afanoya"=
,"","21-02-2025 23:06:20","21-02-2025 23:02:49","22-02-2025 01:58:15","Casc=
aded Incident from TTO4449376","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because 4/8 rectifiers =
disfunctionning SS IHS Felix ZAMBE confirmed// He reset rectifiers","system=
","277223","21-02-2025 23:06:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0004404884","ELOUMDEM=
 CARRIERE","","21-02-2025 23:06:20","21-02-2025 23:02:49","22-02-2025 01:58=
:15","Cascaded Incident from TTO4449376","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because 4/8 rect=
ifiers disfunctionning SS IHS Felix ZAMBE confirmed// He reset rectifiers",=
"system","277224","21-02-2025 23:06:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0004404885","MBALNGON=
G LYCEE","","21-02-2025 23:06:20","21-02-2025 23:02:49","22-02-2025 01:58:1=
5","Cascaded Incident from TTO4449376","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because 4/8 rectif=
iers disfunctionning SS IHS Felix ZAMBE confirmed// He reset rectifiers","s=
ystem","277223","21-02-2025 23:06:20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004404866","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","21-02-2025 23:05:04","21-02-20=
25 23:02:49","22-02-2025 01:58:15","Site went down because 4/8 rectifiers d=
isfunctionning SS IHS Felix ZAMBE confirmed// He reset rectifiers","Hyemafo=
 Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","Site =
went down because 4/8 rectifiers disfunctionning SS IHS Felix ZAMBE confirm=
ed// He reset rectifiers","el-dalile@sagemcom.com","136","21-02-2025 23:05:=
04","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004404856","Mom=
","","21-02-2025 23:02:21","21-02-2025 22:56:54","21-02-2025 23:00:59","Act=
ive//No power issue site on Grid with U=3D53,6 v Etienne(695033981) From Hu=
awei is informed by message","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power iss=
ue site on Grid with U=3D53,6 v Etienne(695033981) From Huawei is informed =
by message","el-dalile@sagemcom.com","328","21-02-2025 23:02:21","Sagemcom =
CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004404585","Eto=
ug ebe biscuiterie","","21-02-2025 22:34:28","21-02-2025 22:32:18","22-02-2=
025 02:19:49","Site went down due to Insufficiency of rectifiers, SS IHS Fr=
an=E7ois NDOUNGOU  confirmed// Site stabilized","Hyemafo Gildas","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","Site went down due to In=
sufficiency of rectifiers, SS IHS Fran=E7ois NDOUNGOU  confirmed// Site sta=
bilized","yves.djomo@sagemcom.com","131","21-02-2025 22:34:28","Sagemcom CM=
R"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0004404484","MVA=
N","","21-02-2025 22:15:18","21-02-2025 22:13:06","21-02-2025 22:15:06","Gr=
id Outage Site went down Because Gen Failed to Start due to Gen Contators F=
aulty//He Bypass it and Site is on Grid","MINKA NICOLAS","Equipment Repair"=
,"Passive","Control Panel","ATS-AMF Issue","Grid Outage Site went down Beca=
use Gen Failed to Start due to Gen Contators Faulty//He Bypass it and Site =
is on Grid","ludovic-anselme.mouliom-mapoure@sagemcom","13590","21-02-2025 =
22:15:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004404386","E=
koumdoum","","21-02-2025 21:54:28","21-02-2025 21:44:15","21-02-2025 22:40:=
01","Grid fluctuation, Site went down because Gen failed to start due to la=
ck of 02 phases// He did a bridge, Site on Grid","Albran Byorel","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctu=
ation, Site went down because Gen failed to start due to lack of 02 phases/=
/ He did a bridge, Site on Grid","ludovic-anselme.mouliom-mapoure@sagemcom"=
,"614","21-02-2025 21:54:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004404272","E=
koumdoum OCM","","21-02-2025 21:47:39","21-02-2025 21:34:29","21-02-2025 23=
:00:17","Grid fluctuation, Site went down because Gen failed to start due t=
o lack of 02 phases// He did a bridge, Site on Grid","Albran Byorel","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation, Site went down because Gen failed to start due to lack of 02 pha=
ses// He did a bridge, Site on Grid","wilfried.kameni@sagemcom.com","791","=
21-02-2025 21:47:39","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004403171","CRH=
-Etoug-Ebe","","21-02-2025 19:29:21","21-02-2025 19:20:13","21-02-2025 19:3=
7:20","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"ludovic-anselme.mouliom-mapoure@sagemcom","549","21-02-2025 19:29:21","Sag=
emcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004403161","Elo=
umdem stade","","21-02-2025 19:26:33","21-02-2025 19:13:23","21-02-2025 20:=
12:37","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage  // He bypass grid and started Gen manually","Fanda Brice=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation, site went down because Gen failed to start due to grid b=
ad voltage  // He bypass grid and started Gen manually","ludovic-anselme.mo=
uliom-mapoure@sagemcom","790","21-02-2025 19:26:33","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004403081","Nsi=
meyong Terre Rouge","","21-02-2025 19:12:58","21-02-2025 18:56:07","21-02-2=
025 21:05:12","Site went down due to PWC dysfunction, SS IHS Fran=E7ois NDO=
UNGOU is informed and confirmed// Site stabilized","MINKA NICOLAS","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went d=
own due to PWC dysfunction, SS IHS Fran=E7ois NDOUNGOU is informed and conf=
irmed// Site stabilized","ludovic-anselme.mouliom-mapoure@sagemcom","1012",=
"21-02-2025 19:12:58","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004402900","Obo=
bogo","","21-02-2025 18:40:57","21-02-2025 18:36:48","21-02-2025 18:42:02",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
ted automatically","MINKA NICOLAS","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen started automatically","ludovic-anselme.moul=
iom-mapoure@sagemcom","250","21-02-2025 18:40:57","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004402709","MBA=
LNGONG LYCEE","","21-02-2025 18:24:36","21-02-2025 18:17:27","21-02-2025 20=
:09:30","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid Restored","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid Restored","ludovic-anselm=
e.mouliom-mapoure@sagemcom","431","21-02-2025 18:24:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004402616","H=
-General-Yde","","21-02-2025 18:08:54","21-02-2025 18:00:44","21-02-2025 19=
:09:53","Grid fluctuation, Site went down because Gen started and stopped d=
ue to Grid bad voltage and poor backup// Grid stabilized","Siligap Boris","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, Site went down because Gen started and stopped due to Grid =
bad voltage and poor backup// Grid stabilized","wilfried.kameni@sagemcom.co=
m","491","21-02-2025 18:08:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004402528","S=
OA UNIVERSITY STADIUM","","21-02-2025 17:51:39","21-02-2025 17:46:19","21-0=
2-2025 17:50:31","No power issue site on grid with U=3D54v Armand Nguetsa f=
rom Huawei is informed Site up at 06:14 PM","Siligap Boris","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue site on grid with U=3D54v Armand Nguetsa from Huawei is informe=
d Site up at 06:14 PM","wilfried.kameni@sagemcom.com","321","21-02-2025 17:=
51:39","Sagemcom CMR"
"Closed Complete","Site Down","T1113","IHS_YND_105","NOCINC0004402508","Omn=
isport 3","","21-02-2025 17:44:49","21-02-2025 17:33:35","21-02-2025 18:51:=
39","Grid outage, site went down because gen failed to start due to Grid co=
ntactor no excited // He excited Grid contactor and Site is on Grid","Delor=
 Telezing","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gr=
id outage, site went down because gen failed to start due to Grid contactor=
 no excited // He excited Grid contactor and Site is on Grid","ludovic-anse=
lme.mouliom-mapoure@sagemcom","675","21-02-2025 17:44:49","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004402474","Sap=
eur","","21-02-2025 17:38:28","21-02-2025 17:21:19","21-02-2025 17:33:43","=
Grid outage, Site went down before Gen start due to poor backup// Gen manua=
lly started","Mboua Thierry","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup// Gen manually started","ludovic-anselme.mouliom-mapoure=
@sagemcom","1030","21-02-2025 17:38:28","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004402412","Pha=
rmacie SION","","21-02-2025 17:29:59","21-02-2025 17:26:44","21-02-2025 17:=
36:58","Grid outage, Site went down before Gen start due to poor backup// G=
en started automaticaly","Paul BIBOUM","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automaticaly","wilfried.kameni@s=
agemcom.com","196","21-02-2025 17:29:59","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004402023","Ngo=
a Ekelle","","21-02-2025 16:28:54","21-02-2025 15:24:35","21-02-2025 16:22:=
06","Grid outage.gen failed to star due to card GE dysfunctionning//We rese=
t card GE and gen manually started (investigation ongoing)","Paul BIBOUM","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.=
gen failed to star due to card GE dysfunctionning//We reset card GE and gen=
 manually started (investigation ongoing)","ludovic-anselme.mouliom-mapoure=
@sagemcom","3860","21-02-2025 16:28:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004401988","A=
wae Escalier","","21-02-2025 16:21:14","21-02-2025 16:19:00","21-02-2025 22=
:32:53","Grid bad voltage, Site went down because Gen failed to start due t=
o  Grid contactor faulty// He bypassed grid and started Gen manualy","Albra=
n Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gri=
d bad voltage, Site went down because Gen failed to start due to  Grid cont=
actor faulty// He bypassed grid and started Gen manualy","ludovic-anselme.m=
ouliom-mapoure@sagemcom","135","21-02-2025 16:21:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004401973","M=
efou-Assi","","21-02-2025 16:19:43","21-02-2025 16:18:20","21-02-2025 16:23=
:44","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME=
 Fulbert(654266068) from Huawei is informed","wilfried.kameni@sagemcom.com"=
,"84","21-02-2025 16:19:43","Sagemcom CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0004401746","Omn=
isport-Rail","","21-02-2025 15:47:40","21-02-2025 15:42:32","21-02-2025 15:=
51:16","Grid outage site went down because Gen failed to start due to stati=
c charger faulty //Gen manually started with external battery","Delor Telez=
ing","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator","=
Grid outage site went down because Gen failed to start due to static charge=
r faulty //Gen manually started with external battery","ludovic-anselme.mou=
liom-mapoure@sagemcom","339","21-02-2025 15:47:40","Sagemcom CMR"
"Closed Complete","Site Down","T3175","IHS_YND_566","NOCINC0004401672","Crf=
 Cornier","","21-02-2025 15:40:52","21-02-2025 15:28:44","21-02-2025 15:35:=
54","No power issue site on grid with U=3D52v Armand Nguetsa from Huawei is=
 informed","MINKA NICOLAS","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D52v Armand Nguetsa from Huawei is informed","ludovic-anselme.mouliom-map=
oure@sagemcom","729","21-02-2025 15:40:52","Sagemcom CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004401661","Nsi=
malen MTN","","21-02-2025 15:38:21","21-02-2025 15:19:10","21-02-2025 15:39=
:25","Grid Outage Site went down because Gen Failed to Start due to CB(32A)=
 Gen disjunted // He reamed the Gen CB and Site is on GEN","Albran Byorel",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Grid Outage =
Site went down because Gen Failed to Start due to CB(32A) Gen disjunted // =
He reamed the Gen CB and Site is on GEN","ludovic-anselme.mouliom-mapoure@s=
agemcom","1151","21-02-2025 15:38:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004401597","M=
vog-Ada_OCM","","21-02-2025 15:24:25","21-02-2025 11:56:05","21-02-2025 18:=
00:36","Grid outage.no space to deploy mobile gen//Grid return ","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no=
 space to deploy mobile gen//Grid return ","ludovic-anselme.mouliom-mapoure=
@sagemcom","12501","21-02-2025 15:24:25","Sagemcom CMR"
"Closed Complete","Warning","T0055","IHS_YND_328","NOCINC0004401583","Nsima=
len MTN","","21-02-2025 15:22:22","","","Site alarming due to Grid outage /=
/ Gen started","Albran Byorel","Warning","Warning","POWER","Warning - AC Fa=
ilure","Site alarming due to Grid outage // Gen started","ervine.mbezele@sa=
gemcom.com","3548","21-02-2025 15:22:22","Sagemcom CMR"
"Closed Complete","Warning","T0351","IHS_YND_146","NOCINC0004401529","Nsime=
yong","","21-02-2025 15:19:51","","","Grid fluctuation, Site alarming due t=
o grid bad voltage // Grid stabilized","MINKA NICOLAS","Warning","Warning",=
"POWER","Warning - Site on Battery","Grid fluctuation, Site alarming due to=
 grid bad voltage // Grid stabilized","ervine.mbezele@sagemcom.com","1448",=
"21-02-2025 15:19:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004401481","O=
LAMA","","21-02-2025 15:14:18","21-02-2025 13:16:38","21-02-2025 13:21:47",=
"No power issue on site U=3D54,9 V site on Gen , The Tx RM Alain/691144423/=
 from Huawei is informed","Fanda Brice","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D54,9 V site on Gen , The Tx RM Alain/691144423/ from Huawei is informed=
","wilfried.kameni@sagemcom.com","7061","21-02-2025 15:14:18","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004401265","S=
calom-IHS","","21-02-2025 14:46:50","21-02-2025 14:35:33","21-02-2025 14:40=
:47","ACTIVE// No power issue on site Ubaie =3D52.5V site on Grid The TX Fm=
e Hosiah / 674007438// from huawei is informed.","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No=
 power issue on site Ubaie =3D52.5V site on Grid The TX Fme Hosiah / 674007=
438// from huawei is informed.","kouoh.jean@ihstowers.com","678","21-02-202=
5 14:46:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004401196","Abattoir=
","","21-02-2025 14:39:00","21-02-2025 14:23:49","21-02-2025 14:34:10","Cas=
caded Incident from TTO4445153","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work: SS IHS B=
ernard ATANGANA working on site// End of work","system","308318","21-02-202=
5 14:39:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004401197","ETOUDI C=
HAPELLE","","21-02-2025 14:39:00","21-02-2025 14:23:49","21-02-2025 14:34:1=
0","Cascaded Incident from TTO4445153","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work: SS=
 IHS Bernard ATANGANA working on site// End of work","system","308318","21-=
02-2025 14:39:00","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0004401174","EBO=
M","","21-02-2025 14:35:00","21-02-2025 14:25:17","21-02-2025 15:23:55","Gr=
id fluctuation, Site went down because Gen failed to start due to Grid bad =
voltage and No RCP on site // Grid stabilized","Hyemafo Gildas","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tion, Site went down because Gen failed to start due to Grid bad voltage an=
d No RCP on site // Grid stabilized","wilfried.kameni@sagemcom.com","584","=
21-02-2025 14:35:00","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004401162","Eto=
udi","IHS_YND_244, IHS_YND_694","21-02-2025 14:34:01","21-02-2025 14:23:49"=
,"21-02-2025 14:34:10","Site went down due to work: SS IHS Bernard ATANGANA=
 working on site// End of work","Fabrice Pouakam","Installation Activity","=
Passive","Planned Activity","Installation Activity","Site went down due to =
work: SS IHS Bernard ATANGANA working on site// End of work","wilfried.kame=
ni@sagemcom.com","613","21-02-2025 14:34:01","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0004400889","Eli=
g Edzoa","","21-02-2025 14:13:26","21-02-2025 13:54:08","21-02-2025 18:25:3=
8","Site went down due to work: SS IHS Bernard Atangana working on site (Re=
configuration Power limitation)// End of work","Delor Telezing","Equipment =
Replacement","Passive","Planned Activity","Planned Activity - Passive","Sit=
e went down due to work: SS IHS Bernard Atangana working on site (Reconfigu=
ration Power limitation)// End of work","ferot.nongni-djiogap@sagemcom.com"=
,"1182","21-02-2025 14:13:26","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004400830","Man=
guiers Dispensaire","","21-02-2025 14:00:47","21-02-2025 13:04:27","21-02-2=
025 13:48:59","GrId outage, site went down because gen failed to start due =
to gen contactor faulty // He bypassed gen contactor and gen manually start=
ed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Load =
Contactor","GrId outage, site went down because gen failed to start due to =
gen contactor faulty // He bypassed gen contactor and gen manually started"=
,"ferot.nongni-djiogap@sagemcom.com","3381","21-02-2025 14:00:47","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004400735","OBA=
M NGOLA OCM","","21-02-2025 13:47:07","21-02-2025 13:29:51","21-02-2025 14:=
25:57","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Site went down due to PSC3 dysfonction SS IHS Pascal=
ine confirmed// Site stabilized","ferot.nongni-djiogap@sagemcom.com","1037"=
,"21-02-2025 13:47:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0004400731","A=
cropole","","21-02-2025 13:46:04","21-02-2025 12:27:38","21-02-2025 12:47:1=
9","Grid fluctuation, Site went down because Gen failed to start due to Gri=
d bad voltage and No RCP on site // Grid stabilized","MINKA NICOLAS","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation, Site went down because Gen failed to start due to Grid bad volta=
ge and No RCP on site // Grid stabilized","wilfried.kameni@sagemcom.com","4=
707","21-02-2025 13:46:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004400643","Crf-Mban=
kolo-IHS","","21-02-2025 13:23:10","21-02-2025 13:02:18","21-02-2025 13:25:=
18","Cascaded Incident from TTO4444532","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work: SS=
 IHS Blaise Raoul working (check MPR)// End of work","system","327759","21-=
02-2025 13:23:10","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004400638","Jea=
n Vespa","IHS_YND_574","21-02-2025 13:22:44","21-02-2025 13:07:35","21-02-2=
025 13:25:18","Site went down due to work: SS IHS Blaise Raoul working (che=
ck MPR)// End of work","Mboua Thierry","Installation Activity","Passive","P=
lanned Activity","Installation Activity","Site went down due to work: SS IH=
S Blaise Raoul working (check MPR)// End of work","ferot.nongni-djiogap@sag=
emcom.com","910","21-02-2025 13:22:44","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004400592","BIY=
EMASSI NIKI","","21-02-2025 13:15:15","21-02-2025 11:44:07","21-02-2025 12:=
56:42","Grid outage, site went down down due PWC overloaded (12 kw 250A) //=
Manually start of DG ,he reduiced the load.","Hyemafo Gildas","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down down due PWC overloaded (12 kw 250A) //Manually start of DG ,he=
 reduiced the load.","ferot.nongni-djiogap@sagemcom.com","5518","21-02-2025=
 13:15:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004400581","Jean Ves=
pa 2","","21-02-2025 13:13:13","21-02-2025 13:02:18","21-02-2025 13:16:11",=
"Cascaded Incident from TTO4444443","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work: SS IHS=
 Blaise Raoul working (check MPR)// End of work","system","320279","21-02-2=
025 13:13:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004400558","J=
-Vespa","IHS_YND_574, IHS_YND_544","21-02-2025 13:07:37","21-02-2025 13:02:=
18","21-02-2025 13:16:11","Site went down due to work: SS IHS Blaise Raoul =
working (check MPR)// End of work","Mboua Thierry","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Site went down due to=
 work: SS IHS Blaise Raoul working (check MPR)// End of work","ferot.nongni=
-djiogap@sagemcom.com","320","21-02-2025 13:07:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004400546","O=
lembe-Terminus","","21-02-2025 13:06:44","21-02-2025 12:57:34","21-02-2025 =
13:02:12","ACTIVE No power issue on site on  Grid Ubaie=3D 53.5 V. The  Fme=
 Tx symphorien / 650257151/ 675295205 from Huawei is informed ","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE No power issue on site on  Grid Ubaie=3D28.5 V. T=
he  Fme Tx symphorien / 650257151/ 675295205 from Huawei is informed ","fer=
ot.nongni-djiogap@sagemcom.com","552","21-02-2025 13:06:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0004400459","Melen Ba=
'aba","","21-02-2025 13:02:50","21-02-2025 12:15:54","21-02-2025 15:45:30",=
"Cascaded Incident from TTO4444067","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","fire on sit","system","323263","21=
-02-2025 13:02:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0004400460","TSINGA V=
ILLAGE 2","","21-02-2025 13:02:50","21-02-2025 12:15:54","21-02-2025 15:45:=
30","Cascaded Incident from TTO4444067","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","fire on sit","system","323263=
","21-02-2025 13:02:50","Sagemcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004400395","Ron=
d Point Express1114","","21-02-2025 12:58:02","21-02-2025 12:52:40","21-02-=
2025 12:59:01","No power issue on site Ubaie =3D54.5V site on Grid TX Fme H=
osiah / 674007438// from huawei is informed and up at 12:59 PM","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site Ubaie =3D54.5V site on Grid TX Fme=
 Hosiah / 674007438// from huawei is informed and up at 12:59 PM","ferot.no=
ngni-djiogap@sagemcom.com","323","21-02-2025 12:58:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0004400388","Abang","=
","21-02-2025 12:57:00","21-02-2025 11:58:11","21-02-2025 14:42:39","Cascad=
ed Incident from TTO4444056","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because the Cb(125A) of=
 PWC dysfonction due to load increased // He reamed the Cb","system","34571=
7","21-02-2025 12:57:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0004400364","M=
vog-Ebanda","","21-02-2025 12:53:10","21-02-2025 11:56:33","21-02-2025 12:2=
2:32","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, Site went down because Gen was on Manual Mode// =
Grid return and site put on Auto Mode (investigation ongoing)","ferot.nongn=
i-djiogap@sagemcom.com","324228","21-02-2025 12:53:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004400362","N=
kolbong","","21-02-2025 12:53:02","21-02-2025 12:09:51","21-02-2025 14:10:4=
2","Grid outage.gen failed to start due to card GE dysfunctionning//We rese=
t card GE and gen manually started ","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to start =
due to card GE dysfunctionning//We reset card GE and gen manually started "=
,"wilfried.kameni@sagemcom.com","2592","21-02-2025 12:53:02","Sagemcom CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004400359","Efo=
ulan MTN","","21-02-2025 12:52:24","21-02-2025 12:50:17","21-02-2025 13:04:=
28","Grid outage, Site went because Gen ran until fuel shortage// Refueling=
 Done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage, Site went because Gen ran until fuel shortage// Refueling Done",=
"ferot.nongni-djiogap@sagemcom.com","127","21-02-2025 12:52:24","Sagemcom C=
MR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004400325","Sap=
eur","","21-02-2025 12:48:18","21-02-2025 12:43:02","21-02-2025 12:55:30","=
Grid outage, site went down because Gen failed to start due to poor battery=
 backup // Gen automatically started","Mboua Thierry","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down because Gen failed to start due to poor battery backup // Gen autom=
atically started","ferot.nongni-djiogap@sagemcom.com","317","21-02-2025 12:=
48:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004400318","AWAE OCM=
","","21-02-2025 12:46:31","21-02-2025 12:33:19","21-02-2025 12:41:53","Cas=
caded Incident from TTO4444164","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.site went down due to P=
SC3 Controller dysfunctionning // Site stabilized","system","322115","21-02=
-2025 12:46:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004400317","Tradex-N=
komo","","21-02-2025 12:46:30","21-02-2025 12:33:19","21-02-2025 12:41:53",=
"Cascaded Incident from TTO4444164","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.site went down due to =
PSC3 Controller dysfunctionning // Site stabilized","system","322114","21-0=
2-2025 12:46:30","Sagemcom CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0004400314","Nko=
mo II","IHS_YND_172, IHS_YND_173","21-02-2025 12:45:32","21-02-2025 12:33:1=
9","21-02-2025 12:41:53","Grid outage.site went down due to PSC3 Controller=
 dysfunctionning // Site stabilized","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage.site went down due to=
 PSC3 Controller dysfunctionning // Site stabilized","ferot.nongni-djiogap@=
sagemcom.com","734","21-02-2025 12:45:32","Sagemcom CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0004400304","Eto=
udi 2","","21-02-2025 12:44:07","21-02-2025 12:31:54","21-02-2025 12:41:34"=
,"Active // No power issue site on Gen with U=3D53,5 V Tx Fme Armand Ngests=
a (691144412) of huawei is informed and up at 12:41 PM","Fabrice Pouakam","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active // No power issue site on Gen with U=3D53,5 V Tx Fme Arma=
nd Ngestsa (691144412) of huawei is informed and up at 12:41 PM","ferot.non=
gni-djiogap@sagemcom.com","734","21-02-2025 12:44:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004400299","E=
MANA BILICK CITY","","21-02-2025 12:43:22","21-02-2025 12:02:13","21-02-202=
5 12:07:37","Active//No power issue on site Ubaie =3D53.4V site on Grid The=
 TX FME Synphorien (650257151) from Huawei is informed","Fabrice Pouakam","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site Ubaie =3D53.4V site on Grid The T=
X FME Synphorien (650257151) from Huawei is informed","wilfried.kameni@sage=
mcom.com","2471","21-02-2025 12:43:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004400291","D=
amas","","21-02-2025 12:41:41","21-02-2025 11:57:40","21-02-2025 12:02:50",=
"","MINKA NICOLAS","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","No power issue site on Grid with U=3D56.9 V=20
 The TX FME Mbah Hosiah (674007438) FROM Huawei is informed.=20

","wilfried.kameni@sagemcom.com","295534","21-02-2025 12:41:41","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0004400282","R=
d-Pt-Express","","21-02-2025 12:40:46","21-02-2025 11:59:33","21-02-2025 15=
:17:48","Grid outage.no space to deploy mobile gen//Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no=
 space to deploy,waiting for Grid restored.","wilfried.kameni@sagemcom.com"=
,"2474","21-02-2025 12:40:46","Sagemcom CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0004400244","Mba=
lla 4","","21-02-2025 12:37:26","21-02-2025 12:13:15","21-02-2025 12:36:58"=
,"Site went down due to PSC3 malfunction on Site// He reset it and Site is =
on Grid","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - C=
ontrol Panel","Site went down due to PSC3 malfunction on Site// He reset it=
 and Site is on Grid","ferot.nongni-djiogap@sagemcom.com","2783","21-02-202=
5 12:37:26","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004400236","Pha=
rmacie SION","","21-02-2025 12:36:39","21-02-2025 12:08:28","21-02-2025 12:=
36:30","Grid outage, site went down before gen start due to poor battery ba=
ckup // gen start automatically","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // gen start automatically","f=
erot.nongni-djiogap@sagemcom.com","1692","21-02-2025 12:36:39","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0004400226","N=
kolfoulou","IHS_YND_308, IHS_YND_719","21-02-2025 12:34:01","21-02-2025 12:=
15:54","21-02-2025 23:32:04","Site went down due to Fire on site: Power cab=
inet (24kw) burned// He replaced it by another (24kw)","Siligap Boris","Fir=
e on Site","Passive","Infrastructure","Fire - Burned","Site went down due t=
o Fire on site: Power cabinet (24kw) burned// He replaced it by another (24=
kw)","wilfried.kameni@sagemcom.com","1089","21-02-2025 12:34:01","Sagemcom =
CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004400225","NYO=
M FACE MAETUR","","21-02-2025 12:33:06","21-02-2025 12:06:55","21-02-2025 1=
3:03:00","Grid outage, site went down because Gen failed to start due to Ge=
n card and solenoid faulty// Grid return","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went dow=
n because Gen failed to start due to Gen card and solenoid faulty// Grid re=
turn","ferot.nongni-djiogap@sagemcom.com","1573","21-02-2025 12:33:06","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0004400219","N=
kolangaa","IHS_YND_290","21-02-2025 12:31:19","21-02-2025 11:58:11","21-02-=
2025 14:42:39","Site went down because the Cb(125A) of PWC dysfonction due =
to load increased // He reamed the Cb","Mba Lazare Herve","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site w=
ent down because the Cb(125A) of PWC dysfonction due to load increased // H=
e reamed the Cb","wilfried.kameni@sagemcom.com","1989","21-02-2025 12:31:19=
","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004400209","Mes=
sa Carriere","","21-02-2025 12:29:54","21-02-2025 12:00:49","21-02-2025 12:=
48:29","Grid outage, site went down because Gen failed to start due to Gen =
card faulty // Grid Restored","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because Gen =
failed to start due to Gen card faulty // Grid Restored","ferot.nongni-djio=
gap@sagemcom.com","1746","21-02-2025 12:29:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004400205","A=
ccacia New","","21-02-2025 12:28:12","21-02-2025 11:58:54","21-02-2025 15:1=
8:24","Grid outage//Grid return","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Outage Issue","Grid outage//Grid return","wilfried.kameni@sag=
emcom.com","1760","21-02-2025 12:28:12","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004400201","Awa=
e Ewonkan","","21-02-2025 12:27:46","21-02-2025 11:56:37","21-02-2025 13:06=
:28","Grid outage, Site went down because Gen overload(20KVA,310A) SS IHS A=
lphonse DEFFO is informed// He reduiced load and started Gen manualy","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage, Site went down because Gen overload(20KVA,310A) SS IHS Alphonse DEF=
FO is informed// He reduiced load and started Gen manualy","ferot.nongni-dj=
iogap@sagemcom.com","1870","21-02-2025 12:27:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004400195","T=
amtam Weekend","IHS_YND_166","21-02-2025 12:26:49","21-02-2025 11:57:40","2=
1-02-2025 12:02:50","No power issue site on Grid with U=3D56.9 V   The TX F=
ME Mbah Hosiah (674007438) FROM Huawei is informed. ","Hyemafo Gildas","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue site on Grid with U=3D56.9 V=20
 The TX FME Mbah Hosiah (674007438) FROM Huawei is informed.=20

","wilfried.kameni@sagemcom.com","1749","21-02-2025 12:26:49","Sagemcom CMR=
"
"Closed Complete","Site Down","T0530","IHS_YND_252","NOCINC0004400193","Kow=
eit City","","21-02-2025 12:26:33","21-02-2025 11:52:09","21-02-2025 12:59:=
34","Grid Outage site went down because Gen Failed to Start //Grid Restored=
( deep investiguation ongoing)","Albran Byorel","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid Outage site went down because Gen=
 Failed to Start //Grid Restored( deep investiguation ongoing)","ferot.nong=
ni-djiogap@sagemcom.com","2064","21-02-2025 12:26:33","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004400184","Nko=
ulou Carriere carrefourt","","21-02-2025 12:25:06","21-02-2025 11:48:51","2=
1-02-2025 13:04:06","Grid outage, site went down because gen fails to start=
 due to card gen faulty // Grid return","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down=
 because gen fails to start due to card gen faulty // Grid return","ferot.n=
ongni-djiogap@sagemcom.com","2176","21-02-2025 12:25:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0004400145","A=
bom","IHS_YND_269","21-02-2025 12:19:47","21-02-2025 11:56:33","21-02-2025 =
12:22:32","Grid outage, Site went down because Gen was on Manual Mode// Gri=
d return and site put on Auto Mode (investigation ongoing)","Siligap Boris"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e, Site went down because Gen was on Manual Mode// Grid return and site put=
 on Auto Mode (investigation ongoing)","wilfried.kameni@sagemcom.com","1395=
","21-02-2025 12:19:47","Sagemcom CMR"
"Closed Complete","Site Down","T2585","IHS_YND_744","NOCINC0004400125","Ele=
veur Meec Bon Berger","","21-02-2025 12:17:22","21-02-2025 11:47:12","21-02=
-2025 12:35:32","Grid outage, Site went down because Gen failed to start// =
Grid return (investigation ongoing)","Siligap Boris","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down becau=
se Gen failed to start// Grid return (investigation ongoing)","ferot.nongni=
-djiogap@sagemcom.com","1811","21-02-2025 12:17:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004400086","M=
ontee-Anne-Rouge","","21-02-2025 12:12:46","21-02-2025 11:46:34","21-02-202=
5 11:51:39"," Active// No power issue on site, Ubaie=3D54,7V site on Grid .=
 Tx FME Brice (650214096) from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," Active//=
 No power issue on site, Ubaie=3D54,7V site on Grid . Tx FME Brice (6502140=
96) from Huawei is informed","wilfried.kameni@sagemcom.com","1573","21-02-2=
025 12:12:46","Sagemcom CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0004400083","Av-=
Germaine","","21-02-2025 12:12:12","21-02-2025 11:47:00","21-02-2025 12:00:=
18","The site was not down","","Incorrectly Logged Tickets","Error","Error"=
,"Error","The site was not down","ferot.nongni-djiogap@sagemcom.com","1513"=
,"21-02-2025 12:12:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004400079","M=
ontee-Des-Soeurs","","21-02-2025 12:11:34","21-02-2025 11:45:25","21-02-202=
5 12:42:29","Grid outage, Site went down before Gen start due to poor backu=
p// Gen manually started","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen manually started","wilfried.kameni@s=
agemcom.com","1570","21-02-2025 12:11:34","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0004400072","Mba=
nkolo petit paris","","21-02-2025 12:10:30","21-02-2025 11:47:52","22-02-20=
25 11:50:25","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Site went down due to 02/05 rectifiers faulty SS IHS P=
ascaline is informed// Site stabilized","ferot.nongni-djiogap@sagemcom.com"=
,"1303252","21-02-2025 12:10:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0004400069","A=
FEME NORD","IHS_YND_808","21-02-2025 12:10:00","21-02-2025 11:47:52","21-02=
-2025 12:59:10","Site went down due to 02/05 rectifiers faulty SS IHS Pasca=
line is informed// Site stabilized","TIENTCHEU NZETCHIEU GAEL","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down due to 02/0=
5 rectifiers faulty SS IHS Pascaline is informed// Site stabilized","wilfri=
ed.kameni@sagemcom.com","1330","21-02-2025 12:10:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004400065","S=
atcom","","21-02-2025 12:08:14","21-02-2025 11:41:04","21-02-2025 11:46:48"=
,"Tx","Delor Telezing","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Tx","wilfried.kameni@sagemcom.com","1631=
","21-02-2025 12:08:14","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004400062","Beh=
ind P T school Yde","","21-02-2025 12:08:01","21-02-2025 11:47:47","21-02-2=
025 12:32:30","Grid outage, Site went down because Gen started and stopped =
due emergency stop button was activeted// He bypassed it and started Gen ma=
nualy (investigatigation ongoing)","Paul BIBOUM","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Emergency Stop","Grid outage, Site went down because =
Gen started and stopped due emergency stop button was activeted// He bypass=
ed it and started Gen manualy (investigatigation ongoing)","ferot.nongni-dj=
iogap@sagemcom.com","1214","21-02-2025 12:08:01","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004400051","Tou=
ring Club International","","21-02-2025 12:06:44","21-02-2025 11:49:30","21=
-02-2025 12:27:05","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline confirmed// He reduced load and started Gen manualy"=
,"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid Outage Site went down because Gen overload (20Kw, 270A) SS IHS Pascal=
ine confirmed// He reduced load and started Gen manualy","wilfried.kameni@s=
agemcom.com","1035","21-02-2025 12:06:44","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004400048","Tsi=
nga village","","21-02-2025 12:05:44","21-02-2025 11:47:32","21-02-2025 12:=
41:44","Site went down due to insufficiency of rectifier (Site on 02 rectif=
iers) SS IHS Bernard Atangana is informed and confirmed // Site stabilized"=
,"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficiency of rectifier (Site on 02 rectifiers=
) SS IHS Bernard Atangana is informed and confirmed // Site stabilized","fe=
rot.nongni-djiogap@sagemcom.com","1093","21-02-2025 12:05:44","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004399905","A=
wae Escalier","","21-02-2025 11:40:40","21-02-2025 11:37:35","21-02-2025 12=
:43:36","Grid outage.site went down due to gen failed to start //Grid retur=
n(investigation ongoing)","Albran Byorel","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage.site went down due to gen failed=
 to start //Grid return(investigation ongoing)","wilfried.kameni@sagemcom.c=
om","187","21-02-2025 11:40:40","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004399760","Ema=
na","","21-02-2025 11:19:26","21-02-2025 11:16:19","21-02-2025 11:26:59","G=
rid outage, Site went down before Gen start due to poor backup// Gen starte=
d automaticaly","Fabrice Pouakam","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup// Gen started automaticaly","ferot.nongni-djiogap@s=
agemcom.com","189","21-02-2025 11:19:26","Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0004399617","Ang=
uissa New","","21-02-2025 10:55:25","21-02-2025 10:48:10","21-02-2025 10:50=
:01","No power issue, site is on grid with Ubaie=3D53V, Eloundou bertrant(6=
52586578) from Huawei is informed","MINKA NICOLAS","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue, site is on grid with Ubaie=3D53V, Eloundou bertrant(652586578) from Hua=
wei is informed","ferot.nongni-djiogap@sagemcom.com","436","21-02-2025 10:5=
5:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_118","NOCINC0004399531","ESSOS OA=
SIS 1111","","21-02-2025 10:44:20","21-02-2025 10:35:44","21-02-2025 11:13:=
49","No power issue, U=3D53. 2 V Site on Grid  The TX FME Armand (691144412=
) from Huawei is informed","Siligap Boris","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Grid outage, site we=
nt down because gen failed to start due to GEN contactor faulty // He bypas=
sed gen contactor and gen manually started","system","516","21-02-2025 10:4=
4:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0004399529","C=
lge-Advantiste","","21-02-2025 10:43:54","21-02-2025 10:38:42","21-02-2025 =
12:29:20","Grid bad voltage, lack of ENEO phases, no RCP on site,DG failed =
to start  // Bypass Grid and manually start of DG.","MINKA NICOLAS","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid bad=
 voltage, lack of ENEO phases, no RCP on site,DG failed to start  // Bypass=
 Grid and manually start of DG.","ferot.nongni-djiogap@sagemcom.com","350",=
"21-02-2025 10:43:54","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0004399477","MVA=
N","","21-02-2025 10:31:56","21-02-2025 10:27:44","21-02-2025 11:22:06","Gr=
id outage, site went down because gen failed to start due to GEN contactor =
faulty // He bypassed gen contactor and gen manually started","MINKA NICOLA=
S","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid ou=
tage, site went down because gen failed to start due to GEN contactor fault=
y // He bypassed gen contactor and gen manually started","ferot.nongni-djio=
gap@sagemcom.com","253","21-02-2025 10:31:56","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004399424","Aha=
la Echangeur","","21-02-2025 10:24:51","21-02-2025 10:17:42","22-02-2025 03=
:18:55","Site went down because 01/02 rectictiers faulty SS IHS Pascaline i=
s informed// Site stabilized (rectifier to be replaced)","MINKA NICOLAS","E=
quipment Repair","Passive","Rectifier","Rectifier Module","Site went down b=
ecause 01/02 rectictiers faulty SS IHS Pascaline is informed// Site stabili=
zed (rectifier to be replaced)","ferot.nongni-djiogap@sagemcom.com","430","=
21-02-2025 10:24:51","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004399395","Ngo=
a Ekelle","","21-02-2025 10:19:58","21-02-2025 10:11:45","21-02-2025 12:01:=
07","Grid outage.site went down and gen fails to start //grid return(invest=
igation ongoing)","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","AC=
DG - Control Panel","Grid outage.site went down and gen fails to start //gr=
id return(investigation ongoing)","ferot.nongni-djiogap@sagemcom.com","494"=
,"21-02-2025 10:19:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004399250","S=
aa","","21-02-2025 09:54:22","21-02-2025 09:46:16","21-02-2025 09:50:03","T=
wx Issue :Site on Grid,Ubaie:54.2V; Gregoire is informed.","Parker Tchoup",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Twx Issue :Site on Grid,Ubaie:54.2V; Gregoire is informed.","wi=
lfried.kameni@sagemcom.com","487","21-02-2025 09:54:22","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004399179","Mes=
sassi 2","","21-02-2025 09:44:54","21-02-2025 09:43:41","21-02-2025 12:13:4=
6","Site went down because PWC overload (12 kilo, 300A) , SS IHS Felix BATE=
U confirmed //Site stabilized","Fabrice Pouakam","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Site went down because PWC ov=
erload (12 kilo, 300A) , SS IHS Felix BATEU confirmed //Site stabilized","f=
erot.nongni-djiogap@sagemcom.com","74","21-02-2025 09:44:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_935","IHS_YND_559","NOCINC0004399176","B=
ATA Mokolo OCM","","21-02-2025 09:43:52","21-02-2025 09:35:24","21-02-2025 =
12:59:13","Grid outage, no space to deploy a mobile gen// Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age, no space to deploy a mobile gen// Grid return","wilfried.kameni@sagemc=
om.com","509","21-02-2025 09:43:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004399124","E=
ssomba","","21-02-2025 09:38:34","21-02-2025 09:29:26","21-02-2025 11:47:14=
","Site went down because PWC overload (12Kw, 250A) SS IHS Alphonse DEFFO c=
onfirmed// Site stabilized","Mba Lazare Herve","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Site went down because PWC over=
load (12Kw, 250A) SS IHS Alphonse DEFFO confirmed// Site stabilized","wilfr=
ied.kameni@sagemcom.com","549","21-02-2025 09:38:34","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0004398746","N=
dogbessol","","21-02-2025 09:03:28","21-02-2025 08:55:15","21-02-2025 11:10=
:18","Active//No power issue on site ,site on battery  wiith  Ubaie=3D52.4 =
V The TX FME Etienne/ 695033981/  Huawei is informed","Kemeni Franklin","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site ,site on battery  wiith  Ubaie=3D52=
.4 V The TX FME Etienne/ 695033981/  Huawei is informed","wilfried.kameni@s=
agemcom.com","494","21-02-2025 09:03:28","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004398481","Ema=
na","","21-02-2025 08:09:23","21-02-2025 08:05:10","21-02-2025 08:15:11","G=
rid outage, Site went down before Gen start due to poor backup// Grid power=
 return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup// Grid power return
","ferot.nongni-djiogap@sagemcom.com","254","21-02-2025 08:09:23","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0004398459","N=
goum","","21-02-2025 08:03:53","21-02-2025 07:38:28","21-02-2025 10:55:54",=
"Solar Hybrid GEN site,  No power issue site on Solar, with U=3D52.7V.    T=
he Tx Fme Gregoire (654547479) from Huawei informed ","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Solar Hybrid GEN site,  No power issue site on Solar, with U=3D52.7V=
.  The Tx Fme Gregoire (654547479) from Huawei informed=20
","wilfried.kameni@sagemcom.com","1526","21-02-2025 08:03:53","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004398430","B=
iteng-Maetur","","21-02-2025 07:57:36","21-02-2025 06:52:26","21-02-2025 10=
:55:27","No power issue on site U=3D53 V site on GenThe FME TX Lionel Adjep=
 (694693436) of Huawei is informed","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site U=3D53 V site on GenThe FME TX Lionel Adjep (694693436) of H=
uawei is informed","wilfried.kameni@sagemcom.com","3911","21-02-2025 07:57:=
36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004398212","N=
kolfon Cimencam","","21-02-2025 07:04:15","21-02-2025 06:48:05","21-02-2025=
 06:55:08","No power issue on site U=3D50.8 V site on Grid.  The Tx FME  Fu=
lbert  (654266068) of huawei is informed. Repetitive Issue Notice that site=
 is impacted by AfanoyaII who is not our responsability","Hyemafo Gildas","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue on site U=3D50.8 V site on Grid.The Tx FME  Fulbe=
rt  (654266068) of huawei is informed. Repetitive Issue Notice that site is=
 impacted by AfanoyaII who is not our responsability","ferot.nongni-djiogap=
@sagemcom.com","972","21-02-2025 07:04:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004397929","Odza II =
OCM","","21-02-2025 05:44:31","21-02-2025 05:26:46","21-02-2025 06:14:10","=
Cascaded Incident from TTO4441412","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went because Gen =
ran until fuel shortage//Refueling Done","system","275955","21-02-2025 05:4=
4:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0004397922","O=
dza-PK10","IHS_YND_527, IHS_YND_528","21-02-2025 05:40:51","21-02-2025 05:2=
6:46","21-02-2025 06:14:10","Grid outage, Site went because Gen ran until f=
uel shortage//Refueling Done","Albran Byorel","Fuel Outage","Passive","Dies=
el","Diesel Outage","Grid outage, Site went because Gen ran until fuel shor=
tage//Refueling Done","yves.djomo@sagemcom.com","846","21-02-2025 05:40:51"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004397902","Bon=
djock","","21-02-2025 05:31:24","21-02-2025 05:22:20","21-02-2025 05:30:14"=
,"Grid outage, site went down because gen start and stopped with high temp =
alarm // he added water and manually start the gen","Fanda Brice","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid outage, site went down because gen start and stopped with high te=
mp alarm // he added water and manually start the gen","yves.djomo@sagemcom=
.com","545","21-02-2025 05:31:24","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004397684","Ona=
ngondi (melen bikop)","","21-02-2025 04:03:56","21-02-2025 04:01:49","21-02=
-2025 04:18:08","Site went down because Gen failed to start due to Hybrid s=
ystem dysfonction// He reset it and Gen manually started","Fanda Brice","Eq=
uipment Repair","Passive","Hybrid","Hybrid Module","Site went down because =
Gen failed to start due to Hybrid system dysfonction// He reset it and Gen =
manually started","yves.djomo@sagemcom.com","128","21-02-2025 04:03:56","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0004397577","MVAN SAC=
EL","","21-02-2025 02:59:50","21-02-2025 02:47:17","21-02-2025 03:18:01","C=
ascaded Incident from TTO4440996","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage Site went down Because G=
en Failed to Start due to Gen Contators Faulty//He Bypass it and Site is on=
 Gen","system","270813","21-02-2025 02:59:50","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0004397574","MVA=
N","IHS_YND_510","21-02-2025 02:58:29","21-02-2025 02:47:17","21-02-2025 03=
:19:39","Grid Outage Site went down Because Gen Failed to Start due to Gen =
Contators Faulty//He Bypass it and Site is on Gen","MINKA NICOLAS","Equipme=
nt Repair","Passive","Control Panel","ATS-AMF Issue","Grid Outage Site went=
 down Because Gen Failed to Start due to Gen Contators Faulty//He Bypass it=
 and Site is on Gen","wilfried.kameni@sagemcom.com","673","21-02-2025 02:58=
:29","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004397338","Bit=
eng-Maetur","","21-02-2025 01:26:59","20-02-2025 23:54:55","20-02-2025 23:5=
9:09","Grid outage, Site went down because Gen started and stopped due to G=
en overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Site stabilized"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","Grid outage, Site went down because Gen started and stopped due to Gen =
overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Site stabilized","l=
udivine.ngamaleu@ihstowers.com","5526","21-02-2025 01:26:59","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004397330","Bon=
djock","","21-02-2025 01:25:33","20-02-2025 20:15:25","20-02-2025 23:08:47"=
,"Grid outage, Site went down because Gen failed to start due to Relay 220V=
 faulty// he replaced it and started Gen manualy","Fanda Brice","Equipment =
Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site went d=
own because Gen failed to start due to Relay 220V faulty// he replaced it a=
nd started Gen manualy","yves.djomo@sagemcom.com","18609","21-02-2025 01:25=
:33","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004397285","Eto=
ug ebe biscuiterie","","21-02-2025 01:11:49","21-02-2025 01:02:33","21-02-2=
025 03:21:32","Grid fluctuation, Site went down because Gen failed to start=
 due to lack of 02 phases// He did a bridge with a good phase","Hyemafo Gil=
das","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, Site went down because Gen failed to start due to lac=
k of 02 phases// He did a bridge with a good phase","wilfried.kameni@sagemc=
om.com","557","21-02-2025 01:11:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004397243","M=
arche Odza","","21-02-2025 01:03:50","21-02-2025 00:50:38","21-02-2025 01:5=
0:02","Grid outage, Site went down because Gen stopped with alarm"" low oil=
 pressure "" (unprouven Alarm) //He reset Gen card and started Gen manaully=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid outage, Site went down because Gen stopped with alarm"" low oil=
 pressure "" (unprouven Alarm) //He reset Gen card and started Gen manaully=
","wilfried.kameni@sagemcom.com","793","21-02-2025 01:03:50","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004397215","AWA=
E OCM","","21-02-2025 00:57:11","20-02-2025 20:40:47","21-02-2025 00:51:38"=
,"Grid fluctuation, site went down because Gen fails to start  due to Grid =
bad voltage and no RCP on site // HE bypassed Grid and Gen manually started=
","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid fluctuation, site went down because Gen fails to s=
tart  due to Grid bad voltage and no RCP on site // HE bypassed Grid and Ge=
n manually started","wilfried.kameni@sagemcom.com","15385","21-02-2025 00:5=
7:11","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004397163","Aha=
la Echangeur","","21-02-2025 00:48:39","21-02-2025 00:45:30","21-02-2025 06=
:51:10","Access during the night site Grid outage site  went down because  =
inverter and rectifier(02) faulty due to lightning // Gen manually started"=
,"MINKA NICOLAS","Access Denial","Lease Or Legal","Landlord Related Issues"=
,"Access Issue - Land Lord","Access during the night site Grid outage site =
 went down because  inverter and rectifier(02) faulty due to lightning // G=
en manually started","wilfried.kameni@sagemcom.com","190","21-02-2025 00:48=
:39","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004397156","Nko=
lmvack","","21-02-2025 00:46:30","21-02-2025 00:39:13","21-02-2025 01:20:11=
","Grid outage,Gen start and stopped due to ""high temp"" alarm//We add wat=
er and Gen manually started","Parker Tchoup","Equipment Repair","Passive","=
ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage,Gen =
start and stopped due to ""high temp"" alarm//We add water and Gen manually=
 started","wilfried.kameni@sagemcom.com","438","21-02-2025 00:46:30","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004397049","M=
arche Odza","","21-02-2025 00:32:42","21-02-2025 00:31:34","21-02-2025 00:3=
8:11","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started automaticaly","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automaticaly","wilfried.kameni@=
sagemcom.com","69","21-02-2025 00:32:42","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004396874","BAT=
A Mokolo OCM","","20-02-2025 23:54:39","20-02-2025 23:03:23","21-02-2025 09=
:13:50","Grid outage, no space to deploy a mobile gen // Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, no space to deploy a mobile gen // Grid return","ludivine.ngamaleu@ihst=
owers.com","3078","20-02-2025 23:54:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0004396647","S=
ofavinc","","20-02-2025 22:50:59","20-02-2025 22:44:43","20-02-2025 23:55:4=
6","Grid Outage Site went down because Gen Failed due to Gen Contactors Fau=
lty//He Bypass it and Manually Started the Gen ","MINKA NICOLAS","Equipment=
 Repair","Passive","Control Panel","ATS-AMF Issue","Grid Outage Site went d=
own because Gen Failed due to Gen Contactors Faulty//He Bypass it and Manua=
lly Started the Gen ","olivier.kwedi@ihstowers.com","471","20-02-2025 22:50=
:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004396603","N=
kolfon Cimencam","","20-02-2025 22:43:53","20-02-2025 22:37:44","21-02-2025=
 04:58:55","Active//No power issue, Site on Grid Ubai=3D 50,8V. Notice that=
 it is impacted by Afanoya II( Not Manged by IHS)","Hyemafo Gildas","Custom=
er Equipment Failure","Active","Active Equipment Failure","Affected by 3rd =
Party Site","Active//No power issue, Site on Grid Ubai=3D 50,8V. Notice tha=
t it is impacted by Afanoya II( Not Manged by IHS)","wilfried.kameni@sagemc=
om.com","370","20-02-2025 22:43:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0004396600","Carrefou=
rt Nkomo","","20-02-2025 22:42:40","20-02-2025 22:19:52","21-02-2025 02:28:=
13","Cascaded Incident from TTO4439858","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went=
 down because Gen failed to start due to Grid bad voltage and No RCP // He =
bypassed Grid and started Gen manualy","system","286830","20-02-2025 22:42:=
40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0004396594","N=
komo","IHS_YND_174","20-02-2025 22:41:04","20-02-2025 22:19:52","21-02-2025=
 02:31:45","Grid fluctuation, site went down because Gen failed to start du=
e to Grid bad voltage and No RCP // He bypassed Grid and started Gen manual=
y","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid fluctuation, site went down because Gen failed to=
 start due to Grid bad voltage and No RCP // He bypassed Grid and started G=
en manualy","wilfried.kameni@sagemcom.com","1273","20-02-2025 22:41:04","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0004396557","ODZ=
A BORNE 10","","20-02-2025 22:33:25","20-02-2025 21:57:09","21-02-2025 00:0=
0:32","site went down because 02/03 Rectifier malfunction// he reset it and=
 Site is on Gen","Albran Byorel","Equipment Repair","Passive","Rectifier","=
Rectifier Module","site went down because 02/03 Rectifier malfunction// he =
reset it and Site is on Gen","ludivine.ngamaleu@ihstowers.com","2176","20-0=
2-2025 22:33:25","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0004396540","Eto=
ug ebe biscuiterie","","20-02-2025 22:30:56","20-02-2025 22:28:51","20-02-2=
025 23:52:41","Grid outage, Site went down because gen failed to start due =
to grid bad voltage and no RCP// He bypassed the grid and gen manually star=
ted","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid outage, Site went down because gen failed to star=
t due to grid bad voltage and no RCP// He bypassed the grid and gen manuall=
y started","yves.djomo@sagemcom.com","126","20-02-2025 22:30:56","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004396446","ELOUMDEM=
 CARRIERE 2","","20-02-2025 22:10:31","20-02-2025 22:05:01","20-02-2025 23:=
21:53","Cascaded Incident from TTO4439681","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down Insufficiency =
of retifier on site SS IHS Felix Zamb=E9 is informed and confirmed // site =
Stabilized","system","287777","20-02-2025 22:10:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004396445","Eto koss=
 Yde","","20-02-2025 22:10:30","20-02-2025 22:05:01","20-02-2025 23:21:53",=
"Cascaded Incident from TTO4439681","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down Insufficiency of reti=
fier on site SS IHS Felix Zamb=E9 is informed and confirmed // site Stabili=
zed","system","287777","20-02-2025 22:10:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004396440","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","20-02-2025 22:09:13","20-02-2025 22:05=
:01","20-02-2025 23:21:53","Site went down Insufficiency of retifier on sit=
e SS IHS Felix Zamb=E9 is informed and confirmed // site Stabilized","Fanda=
 Brice","Equipment Repair","Passive","Rectifier","Rectifier Module","Site w=
ent down Insufficiency of retifier on site SS IHS Felix Zamb=E9 is informed=
 and confirmed // site Stabilized","ervine.mbezele@sagemcom.com","254","20-=
02-2025 22:09:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_159","NOCINC0004396412","Complexe=
-BEAC","","20-02-2025 22:04:31","20-02-2025 21:56:35","20-02-2025 23:05:11"=
,"Cascaded Incident from TTO4439646","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen stopped with 'Emergency stop' alarm // He reset the Gen card and Gen=
 manually started","system","273816","20-02-2025 22:04:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004396409","E=
kie-Elegance","IHS_YND_159","20-02-2025 22:03:51","20-02-2025 21:56:35","20=
-02-2025 23:05:11","Grid outage, site went down because gen stopped with 'E=
mergency stop' alarm // He reset the Gen card and Gen manually started","Al=
bran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage, site went down because gen stopped with 'Emergency stop' ala=
rm // He reset the Gen card and Gen manually started","ludovic-anselme.moul=
iom-mapoure@sagemcom","437","20-02-2025 22:03:51","Sagemcom CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0004396184","Odz=
a petit marche new","","20-02-2025 21:39:07","20-02-2025 21:33:49","20-02-2=
025 23:39:09","Grid outage, Site went down because Gen stopped with alarm l=
ow oil pressure(not unproven)//He reset it and started Manually the Gen","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","Grid outage, Site went down because Gen stopped with alarm low oil press=
ure(not unproven)//He reset it and started Manually the Gen","wilfried.kame=
ni@sagemcom.com","319","20-02-2025 21:39:07","Sagemcom CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0004396032","Eki=
e sud","","20-02-2025 21:18:35","20-02-2025 21:13:23","20-02-2025 22:03:43"=
,"Grid Outage Site went douwn due to Controlers PSC3 dysfunction // He Rese=
t it and Site is on Grid","Albran Byorel","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid Outage Site went douwn due to Controler=
s PSC3 dysfunction // He Reset it and Site is on Grid","ervine.mbezele@sage=
mcom.com","313","20-02-2025 21:18:35","Sagemcom CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0004396027","Men=
dong Maeture","","20-02-2025 21:17:46","20-02-2025 21:10:26","21-02-2025 12=
:04:45","Site went down because rectifiers burned (07 rectifers),SS IHS Fra=
n=E7ois NDOUNGOU confirmed // He add 05 rectifier on site","Hyemafo Gildas"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module","Site went dow=
n because rectifiers burned (07 rectifers),SS IHS Fran=E7ois NDOUNGOU confi=
rmed // He add 05 rectifier on site
","ervine.mbezele@sagemcom.com","441","20-02-2025 21:17:46","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004396022","Awa=
e Escalier","","20-02-2025 21:16:17","20-02-2025 21:03:06","21-02-2025 01:5=
9:33","Grid bad voltage, Site went down because Gen failed to start due to =
 Grid contactor faulty// He bypassed grid and started Gen manualy","Albran =
Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid =
bad voltage, Site went down because Gen failed to start due to  Grid contac=
tor faulty// He bypassed grid and started Gen manualy","ervine.mbezele@sage=
mcom.com","792","20-02-2025 21:16:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004396005","D=
amas","","20-02-2025 21:14:10","20-02-2025 20:54:45","20-02-2025 21:42:31",=
"Acces isssues durring the Night (IHS SS Pascaline is informed and Confirme=
d it) Grid Outage and Gen Failed to Start //Grid Restored (deep investiguet=
ion ongoing)","MINKA NICOLAS","Access Denial","Lease Or Legal","Landlord Re=
lated Issues","Access Issue - Land Lord","Acces isssues durring the Night (=
IHS SS Pascaline is informed and Confirmed it) Grid Outage and Gen Failed t=
o Start //Grid Restored (deep investiguetion ongoing)","ludovic-anselme.mou=
liom-mapoure@sagemcom","1166","20-02-2025 21:14:10","Sagemcom CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0004395867","Ngo=
usso-Savana","","20-02-2025 20:52:45","20-02-2025 20:51:33","20-02-2025 20:=
54:42","Active: no power issue, site is on grid with Ubaie=3D53V, Symphorie=
n(650257151) from huawei is informed","Siligap Boris","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: n=
o power issue, site is on grid with Ubaie=3D53V, Symphorien(650257151) from=
 huawei is informed","ervine.mbezele@sagemcom.com","72","20-02-2025 20:52:4=
5","Sagemcom CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0004395856","M=
eyo","","20-02-2025 20:50:57","20-02-2025 20:14:28","20-02-2025 22:42:56","=
Grid outage,  site went down because Gen overload (17kva, 250A) SS IHS Feli=
x ZAMBE confirmed// He reduiced load and started Gen manualy","Hyemafo Gild=
as","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,=
  site went down because Gen overload (17kva, 250A) SS IHS Felix ZAMBE conf=
irmed// He reduiced load and started Gen manualy","ludovic-anselme.mouliom-=
mapoure@sagemcom","2190","20-02-2025 20:50:57","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004395771","Tou=
ring Club International","","20-02-2025 20:38:07","20-02-2025 20:30:46","20=
-02-2025 21:32:15","Site went down due to Gen overload (20 KVA, 270A) SS IH=
S renaud confirmed//we reduce load and gen manuylly started ","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site went dow=
n due to Gen overload (20 KVA, 270A) SS IHS renaud confirmed//we reduce loa=
d and gen manuylly started ","ervine.mbezele@sagemcom.com","442","20-02-202=
5 20:38:07","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0004395678","MVA=
N","","20-02-2025 20:20:17","20-02-2025 20:11:02","20-02-2025 20:37:29","Gr=
id Outage Site went down Because Gen Failed to Start due to Gen Contators F=
aulty//He Bypass it and Site is on Grid ","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","ATS-AMF Issue","Grid Outage Site went down Bec=
ause Gen Failed to Start due to Gen Contators Faulty//He Bypass it and Site=
 is on Grid ","ervine.mbezele@sagemcom.com","556","20-02-2025 20:20:17","Sa=
gemcom CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0004395055","Cha=
rles-Atangana","","20-02-2025 19:41:23","20-02-2025 19:33:54","20-02-2025 2=
1:47:32","Grid outage // MDG of 20 KVA has deployed","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage // MDG of 20 K=
VA has deployed","ervine.mbezele@sagemcom.com","451","20-02-2025 19:41:23",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004394980","Men=
dong3","","20-02-2025 19:29:45","20-02-2025 19:17:23","21-02-2025 02:55:14"=
,"Grid Outage No Space to deploy a MDG//Grid Resored","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space to d=
eploy a MDG//Grid Resored","ervine.mbezele@sagemcom.com","743","20-02-2025 =
19:29:45","Sagemcom CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0004394729","Kon=
dengui MTN","","20-02-2025 19:14:29","20-02-2025 19:11:59","20-02-2025 20:1=
5:58","Site went down because Gen failed to started due to Grid bad voltage=
 and No RCP on site // He bypass the Grid and Gen manually started","Albran=
 Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Site went down because Gen failed to started due to Grid bad voltag=
e and No RCP on site // He bypass the Grid and Gen manually started","ervin=
e.mbezele@sagemcom.com","151","20-02-2025 19:14:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004394728","S=
calom","","20-02-2025 19:14:21","20-02-2025 19:09:12","20-02-2025 21:41:04"=
,"site went down due to Rectifier Issues SS IHS Francois is Informed and Co=
nfirmed it//Site Stablized ","Paul BIBOUM","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","site went down due to Rectifier Issues SS IHS =
Francois is Informed and Confirmed it//Site Stablized","ludovic-anselme.mou=
liom-mapoure@sagemcom","310","20-02-2025 19:14:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004394706","M=
efou-Assi","","20-02-2025 19:08:26","20-02-2025 19:04:20","21-02-2025 05:00=
:47","ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The =
Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//No power issue on site GRID , Ubaie=3D54.5V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed","ludovic-anselme.mouliom-map=
oure@sagemcom","248","20-02-2025 19:08:26","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004394684","Nko=
ulou Carriere carrefourt","","20-02-2025 19:02:56","20-02-2025 19:00:07","2=
0-02-2025 20:38:56","Grid outage, site went down because gen fails to start=
 due to card gen faulty // Grid return","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down=
 because gen fails to start due to card gen faulty // Grid return","ervine.=
mbezele@sagemcom.com","170","20-02-2025 19:02:56","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0004394622","Odz=
a II","","20-02-2025 18:48:00","20-02-2025 18:39:47","20-02-2025 19:23:31",=
"Grid outage, Site went down due to pwc ZTE dysfunction// He bypassed it an=
d started Gen manualy","Albran Byorel","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Grid outage, Site went down due to pwc =
ZTE dysfunction// He bypassed it and started Gen manualy","ervine.mbezele@s=
agemcom.com","553","20-02-2025 18:48:00","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004394584","MBA=
LNGONG LYCEE","","20-02-2025 18:39:10","20-02-2025 18:26:01","20-02-2025 19=
:48:24",",Site went down because Gen overload(9kva,130 A)  waitng IHS SS Fe=
lix Zambe confirmed ","Fanda Brice","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload",",Site went down because Gen overload(9kva,130 A)  waitn=
g IHS SS Felix Zambe confirmed ","ervine.mbezele@sagemcom.com","791","20-02=
-2025 18:39:10","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004394540","Eko=
umdoum OCM","","20-02-2025 18:28:41","20-02-2025 18:17:30","20-02-2025 20:0=
4:31","Site went down due to  Gen overload(20kva,280 A) IHS SS Pascaline is=
 informed and confirmed// Grid return","Albran Byorel","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Site went down due to  Gen overload(=
20kva,280 A) IHS SS Pascaline is informed and confirmed// Grid return","wil=
fried.kameni@sagemcom.com","1718","20-02-2025 18:28:41","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004394484","Tsi=
nga village","","20-02-2025 18:13:54","20-02-2025 18:12:43","21-02-2025 05:=
01:05","Active // No power issue UBaie =3D54,7V site on Grid The FME TX SYM=
PHORIEN (675295205) From Huawei is informed and up at 06:14 PM","Delor Tele=
zing","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active // No power issue UBaie =3D54,7V site on Grid The =
FME TX SYMPHORIEN (675295205) From Huawei is informed and up at 06:14 PM","=
ervine.mbezele@sagemcom.com","71","20-02-2025 18:13:54","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004394479","Nom=
ayos montee Meche","","20-02-2025 18:12:53","20-02-2025 18:10:39","21-02-20=
25 05:01:23","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On G=
rid The Tx FME Fulbert(654266068) from Huawei is informed AND UP AT 06:12 P=
M","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D=
53.5V site On Grid The Tx FME Fulbert(654266068) from Huawei is informed AN=
D UP AT 06:12 PM","ervine.mbezele@sagemcom.com","135","20-02-2025 18:12:53"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004394471","Mon=
tee-Jouvence-II","","20-02-2025 18:11:48","20-02-2025 18:10:17","20-02-2025=
 18:11:52","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix Za=
mb=E9 confirmed // Site stabilized","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Site went down due to PWC=
 Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site stabilized","=
ervine.mbezele@sagemcom.com","92","20-02-2025 18:11:48","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004394451","Jou=
vence Mbenda","","20-02-2025 18:06:42","20-02-2025 18:01:20","20-02-2025 18=
:10:49","site went down because gen failed to start due to grid fluctuation=
 // Grid stabilized","Hyemafo Gildas","Grid Supply","Passive","Grid","Natio=
nal Grid - Phase Controller Faulty","site went down because gen failed to s=
tart due to grid fluctuation // Grid stabilized","ervine.mbezele@sagemcom.c=
om","323","20-02-2025 18:06:42","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004394446","Aha=
la Echangeur","","20-02-2025 18:05:03","20-02-2025 18:01:13","20-02-2025 20=
:48:30","Grid Outage Site went Down Because Gen Failed to Sart due to  Cont=
actort Grid/Gen Faulty and Rectifier Faulty on Site during the Rain and lig=
htning struck // he Normalized It and Add new Rectifier ","MINKA NICOLAS","=
Force Majeure","Natural Disaster","Thunderstrike","Equipment Damaged","Grid=
 Outage Site went Down Because Gen Failed to Sart due to  Contactort Grid/G=
en Faulty and Rectifier Faulty on Site during the Rain and lightning struck=
 // he Normalized It and Add new Rectifier ","wilfried.kameni@sagemcom.com"=
,"231","20-02-2025 18:05:03","Sagemcom CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004394440","MEH=
ANDAN","","20-02-2025 18:02:20","20-02-2025 17:59:54","20-02-2025 18:05:03"=
,"Grid Outage Site went down because Gen Failed to Start due to Alarm''No s=
tart-up''//He reset the Gen Card and Manually Started the Gen ","Albran Byo=
rel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid O=
utage Site went down because Gen Failed to Start due to Alarm''No start-up'=
'//He reset the Gen Card and Manually Started the Gen ","ervine.mbezele@sag=
emcom.com","147","20-02-2025 18:02:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004394390","B=
arriere","","20-02-2025 17:52:20","20-02-2025 17:42:13","20-02-2025 18:02:1=
9","Grid fluctuation, site went down because Gen failed to start due to Gri=
d bad voltage and No RCP // Grid stabilized","Hyemafo Gildas","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on, site went down because Gen failed to start due to Grid bad voltage and =
No RCP // Grid stabilized","ludovic-anselme.mouliom-mapoure@sagemcom","608"=
,"20-02-2025 17:52:20","Sagemcom CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0004394389","San=
ta Barbara Yde","IHS_YND_740","20-02-2025 17:52:02","20-02-2025 17:39:45","=
20-02-2025 17:40:14","Active//No power issue on site; Ubaie: 54.8 V site on=
 Grid The FME Synphorien//691316854// from Huawei is informed. and Notice t=
hat there is rain in the area","Delor Telezing","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue on site; Ubaie: 54.8 V site on Grid The FME Synphorien//691316854//=
 from Huawei is informed. and Notice that there is rain in the area","ervin=
e.mbezele@sagemcom.com","738","20-02-2025 17:52:02","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0004394362","San=
ta Barbara Gottam","","20-02-2025 17:48:10","20-02-2025 17:39:45","20-02-20=
25 17:40:14","","Delor Telezing","Cascade Outage","Active","Cascade Active"=
,"Cascade Active","Active//No power issue on site; Ubaie: 54.8 V site on Gr=
id The FME Synphorien//691316854// from Huawei is informed. and Notice that=
 there is rain in the area","ervine.mbezele@sagemcom.com","303813","20-02-2=
025 17:48:10","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004394272","Awa=
e Ewonkan","","20-02-2025 17:33:53","20-02-2025 17:32:46","20-02-2025 18:52=
:33","Grid outage ,Site went down because Gen overload(20kva,390 A)  waitin=
g IHS SS Aphonsine  confirmed","Albran Byorel","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage ,Site went down because Gen over=
load(20kva,390 A)  waiting IHS SS Aphonsine  confirmed","wilfried.kameni@sa=
gemcom.com","68","20-02-2025 17:33:53","Sagemcom CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0004394229","Odz=
a Minkan IHS","","20-02-2025 17:25:59","20-02-2025 17:23:47","20-02-2025 17=
:25:34","Grid outage,site went down due to pwc ZTE dysfunction// he reset i=
t and site is on Gen","Albran Byorel","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Grid outage,site went down due to pwc ZT=
E dysfunction// he reset it and site is on Gen","ervine.mbezele@sagemcom.co=
m","133","20-02-2025 17:25:59","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004394224","Eto=
udi","","20-02-2025 17:24:49","20-02-2025 17:20:40","20-02-2025 18:34:40","=
Grid outage, site went down because Gen overload( 20kva,360A) IHS SS Bernar=
d Atangana has confirmed //  We reduce load and gen manually strtaed ","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, site went down because Gen overload( 20kva,360A) IHS SS Bernard =
Atangana has confirmed //  We reduce load and gen manually strtaed ","ervin=
e.mbezele@sagemcom.com","250","20-02-2025 17:24:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004394218","B=
arriere IHS","","20-02-2025 17:24:13","20-02-2025 17:21:00","20-02-2025 21:=
28:00","Grid outage, site we,nt down due to gen overload(20KVA, 240A),SS Fe=
lix IHS // Grid return","Hyemafo Gildas","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Grid outage, site we,nt down due to gen overload(2=
0KVA, 240A),SS Felix IHS // Grid return","ludovic-anselme.mouliom-mapoure@s=
agemcom","194","20-02-2025 17:24:13","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004394212","Com=
plex Beac II","","20-02-2025 17:23:57","20-02-2025 17:19:39","20-02-2025 20=
:57:13","Grid Outage Site went Down Because Gen Failed to Sart due to Relay=
 Faulty and 02 Rectifier Faulty on Site during the Rain and lightning struc=
k // he Normalized It and Add new Rectifier ","Albran Byorel","Force Majeur=
e","Natural Disaster","Thunderstrike","Equipment Damaged","Grid Outage Site=
 went Down Because Gen Failed to Sart due to Relay Faulty and 02 Rectifier =
Faulty on Site during the Rain and lightning struck // he Normalized It and=
 Add new Rectifier ","ervine.mbezele@sagemcom.com","259","20-02-2025 17:23:=
57","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004394205","OBA=
M NGOLA OCM","","20-02-2025 17:22:38","20-02-2025 17:18:14","20-02-2025 19:=
22:52","Grid outage, Site went because Gen ran until fuel shortage// Refuel=
ing Done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, Site went because Gen ran until fuel shortage// Refueling Don=
e","ervine.mbezele@sagemcom.com","265","20-02-2025 17:22:38","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004394165","Abo=
me","","20-02-2025 17:16:26","20-02-2025 17:12:17","20-02-2025 17:43:32","S=
ite went down because Gen stopped with alarm low oil pressure(not unproven)=
//He reset it and started Manually the Gen","MINKA NICOLAS","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Site went down because Gen=
 stopped with alarm low oil pressure(not unproven)//He reset it and started=
 Manually the Gen","ervine.mbezele@sagemcom.com","250","20-02-2025 17:16:26=
","Sagemcom CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0004394155","Eto=
udi 2","","20-02-2025 17:14:47","20-02-2025 17:08:31","20-02-2025 17:09:11"=
,"Active // No power issue site on Gen with U=3D52,3 V Tx Fme Armand Ngests=
a (691144412) of huawei is informed and Notice that there is rain in the ar=
ea","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","Active // No power issue site on Gen with=
 U=3D52,3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed and Not=
ice that there is rain in the area","ervine.mbezele@sagemcom.com","377","20=
-02-2025 17:14:47","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004394079","Nsi=
meyong Terre Rouge","","20-02-2025 17:10:39","20-02-2025 17:08:32","21-02-2=
025 12:01:17","Site went down due to PWC dysfunction, SS IHS Fran=E7ois NDO=
UNGOU is informed and confirmed// Site stabilized","MINKA NICOLAS","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went d=
own due to PWC dysfunction, SS IHS Fran=E7ois NDOUNGOU is informed and conf=
irmed// Site stabilized","wilfried.kameni@sagemcom.com","128","20-02-2025 1=
7:10:39","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004394064","AWA=
E OCM","","20-02-2025 17:09:19","20-02-2025 17:04:11","20-02-2025 17:15:01"=
,"Grid outage, Site went down before Gen start due to poor backup// Grid re=
turn","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, Site went down before Gen start due =
to poor backup// Grid return","wilfried.kameni@sagemcom.com","309","20-02-2=
025 17:09:19","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004394059","Mom=
","","20-02-2025 17:08:25","20-02-2025 17:03:17","21-02-2025 05:02:25","Act=
ive//No power issue site on Grid with U=3D53,6 v Etienne(695033981) From Hu=
awei is informed and up at 07:39 PM","Fanda Brice","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue site on Grid with U=3D53,6 v Etienne(695033981) From Huawei is i=
nformed and up at 07:39 PM","wilfried.kameni@sagemcom.com","310","20-02-202=
5 17:08:25","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004394058","Obo=
bogo","","20-02-2025 17:07:28","20-02-2025 17:04:12","20-02-2025 17:10:17",=
"Grid outage, Site went down before Gen start due to poor backup/ // Grid p=
ower return","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup/ // Grid power return","wilfried.kameni@sagemcom.com","1=
97","20-02-2025 17:07:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004394057","B=
iteng-Maetur","","20-02-2025 17:07:15","20-02-2025 17:03:03","20-02-2025 21=
:53:55","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// HE reduiced lo=
ad and started Gen (Site up at OCM after power reset done)","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,=
 Site went down because Gen started and stopped due to Gen overload(20kva, =
280A) SS IHS Alphonse DEFFO confirmed// HE reduiced load and started Gen (S=
ite up at OCM after power reset done)","ludovic-anselme.mouliom-mapoure@sag=
emcom","253","20-02-2025 17:07:15","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004394053","Pha=
rmacie SION","","20-02-2025 17:06:38","20-02-2025 17:02:17","20-02-2025 17:=
13:48","Grid outage, Site went down before Gen start due to poor backup// G=
en started automaticaly","Paul BIBOUM","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automaticaly","wilfried.kameni@s=
agemcom.com","262","20-02-2025 17:06:38","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004394042","Crf=
-Nsam","","20-02-2025 17:04:58","20-02-2025 17:02:25","20-02-2025 18:09:24"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline is i=
nformed and confirmed // Site stabilized","MINKA NICOLAS","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","Site went down becau=
se PWC(24kilo) dysfunctionning, IHS SS Pascaline is informed and confirmed =
// Site stabilized","wilfried.kameni@sagemcom.com","154","20-02-2025 17:04:=
58","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004394010","Ngo=
usso Vallee","","20-02-2025 17:01:23","20-02-2025 16:56:06","20-02-2025 18:=
34:14","Grid outage, site went down because gen start and stopped with alar=
m low oil pressure // He reset gen card and gen manually started","Siligap =
Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage, site went down because gen start and stopped with alarm low oil pr=
essure // He reset gen card and gen manually started","wilfried.kameni@sage=
mcom.com","317","20-02-2025 17:01:23","Sagemcom CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0004394003","ETO=
UDI CHAPELLE","","20-02-2025 16:58:16","20-02-2025 16:51:58","20-02-2025 18=
:59:12","Grid outahe, site went down because Gen failed to start due to Gen=
 battery faulty // Gen manually started with external battery","Delor Telez=
ing","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Gr=
id outahe, site went down because Gen failed to start due to Gen battery fa=
ulty // Gen manually started with external battery","wilfried.kameni@sagemc=
om.com","379","20-02-2025 16:58:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004393991","M=
ontee-Des-Soeurs","","20-02-2025 16:56:48","20-02-2025 16:33:08","20-02-202=
5 17:27:57","Grid outage, Site went down before Gen start due to poor backu=
p// Gen manually started ","Hyemafo Gildas","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup// Gen manually started ","ludovic-anselme=
.mouliom-mapoure@sagemcom","1421","20-02-2025 16:56:48","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004393979","Mes=
sa Carriere","","20-02-2025 16:55:05","20-02-2025 16:50:46","20-02-2025 17:=
16:37","Grid outage,gen failed to start due to card GE dysfunctionning//We =
reset card GE and gen manually started ","Mboua Thierry","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to sta=
rt due to card GE dysfunctionning//We reset card GE and gen manually starte=
d ","wilfried.kameni@sagemcom.com","261","20-02-2025 16:55:05","Sagemcom CM=
R"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004393965","BAT=
A Mokolo OCM","","20-02-2025 16:53:47","20-02-2025 16:50:29","20-02-2025 17=
:36:50","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Sp=
ace to deploy a MDG//Grid Restored","ervine.mbezele@sagemcom.com","199","20=
-02-2025 16:53:47","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004393892","UPA=
C LP","","20-02-2025 16:50:17","20-02-2025 16:32:54","20-02-2025 16:51:28",=
"Grid outage, no space to deploy MDG// Grid return ","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage, no space to d=
eploy MDG// Grid return ","wilfried.kameni@sagemcom.com","1044","20-02-2025=
 16:50:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004393874","E=
MANA BILICK CITY","","20-02-2025 16:45:41","20-02-2025 16:23:35","20-02-202=
5 16:24:12","Active//No power issue on site Ubaie =3D53.4V site on Grid The=
 TX FME Synphorien (650257151) from Huawei is informed and up at 05:07 PM",=
"Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie =3D53.4V=
 site on Grid The TX FME Synphorien (650257151) from Huawei is informed and=
 up at 05:07 PM","ludovic-anselme.mouliom-mapoure@sagemcom","1328","20-02-2=
025 16:45:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0004393861","N=
ew-Marche-Melen","","20-02-2025 16:42:10","20-02-2025 16:34:00","20-02-2025=
 16:40:02","No power issue site on grid with U=3D54v Notice that site is im=
pacted by OBILI GP who is not our responsability","Paul BIBOUM","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue site on grid with U=3D54v Notice that site is impacted by O=
BILI GP who is not our responsability","ludovic-anselme.mouliom-mapoure@sag=
emcom","490","20-02-2025 16:42:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004393832","E=
ssomba","","20-02-2025 16:37:33","20-02-2025 16:31:08","20-02-2025 17:05:36=
","Site went down because PWC overload (12Kw, 250A) SS IHS Alphonse DEFFO c=
onfirmed// Site stabilized","Mba Lazare Herve","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Site went down because PWC over=
load (12Kw, 250A) SS IHS Alphonse DEFFO confirmed// Site stabilized","ludov=
ic-anselme.mouliom-mapoure@sagemcom","387","20-02-2025 16:37:33","Sagemcom =
CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004393824","Beh=
ind P T school Yde","","20-02-2025 16:37:01","20-02-2025 16:30:42","20-02-2=
025 17:27:14","Grid outage site went down because Gen failed to start due t=
o emergy stop activated // He desactivated the emergy stop and Gen manually=
 started","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Eme=
rgency Stop","Grid outage site went down because Gen failed to start due to=
 emergy stop activated // He desactivated the emergy stop and Gen manually =
started","wilfried.kameni@sagemcom.com","380","20-02-2025 16:37:01","Sagemc=
om CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004393803","CRH=
-Etoug-Ebe","","20-02-2025 16:35:57","20-02-2025 16:32:11","20-02-2025 16:4=
9:17","Grid outage, Site went down before Gen start due to poor backup/ // =
Gen automatically started","Hyemafo Gildas","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor backup/ // Gen automatically started","wilfried.=
kameni@sagemcom.com","227","20-02-2025 16:35:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0004393797","S=
apeur","","20-02-2025 16:34:14","20-02-2025 16:31:07","20-02-2025 16:52:55"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automaticaly","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen started automaticaly","ludovic-anselme.mouli=
om-mapoure@sagemcom","188","20-02-2025 16:34:14","Sagemcom CMR"
"Closed Complete","Site Down","T2104","IHS_YND_711","NOCINC0004393642","H-F=
ranco New","","20-02-2025 16:28:30","20-02-2025 16:26:06","20-02-2025 16:51=
:42","Site went down due to  Gen overload (20Kva .350A) SS IHS Bernad is In=
formed // Grid Restored","Delor Telezing","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Site went down due to  Gen overload (20Kva .350A)=
 SS IHS Bernad is Informed // Grid Restored","wilfried.kameni@sagemcom.com"=
,"605","20-02-2025 16:28:30","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004393621","ETO=
UDI Entree du palais","","20-02-2025 16:25:20","20-02-2025 16:20:52","20-02=
-2025 16:26:25","Grid outage ,gen failed to start due to card GE  dysfuncti=
onning//We reset card GE and gen manually started ","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,gen=
 failed to start due to card GE  dysfunctionning//We reset card GE and gen =
manually started ","wilfried.kameni@sagemcom.com","269","20-02-2025 16:25:2=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004393603","S=
atcom","","20-02-2025 16:22:15","20-02-2025 16:15:05","20-02-2025 16:20:46"=
,"Active // No power issue site on Grid with U=3D53,02 V Tx Fme Armand Nges=
tsa (691144412) of huawei is informed notice that heavy rain on the area","=
Delor Telezing","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active // No power issue site on Grid with U=3D=
53,02 V Tx Fme Armand Ngestsa (691144412) of huawei is informed notice that=
 heavy rain on the area","ludovic-anselme.mouliom-mapoure@sagemcom","431","=
20-02-2025 16:22:15","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004393538","NKO=
LMEKONG YDE","","20-02-2025 16:12:34","20-02-2025 16:10:18","20-02-2025 16:=
26:00","Site went down due to PWC Huawei malfunction// he Reset it and Site=
 is on Grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Site went down due to PWC Huawei malfunction// =
he Reset it and Site is on Grid","wilfried.kameni@sagemcom.com","137","20-0=
2-2025 16:12:34","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004393472","Mes=
sassi 2","","20-02-2025 16:03:47","20-02-2025 16:01:37","20-02-2025 16:04:5=
3","Site went down because PWC overload (12 kilo, 300A) , SS IHS Felix BATE=
U confirmed //Site stabilized","Fabrice Pouakam","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Site went down because PWC ov=
erload (12 kilo, 300A) , SS IHS Felix BATEU confirmed //Site stabilized","w=
ilfried.kameni@sagemcom.com","131","20-02-2025 16:03:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004393031","N=
koabang2","","20-02-2025 15:40:08","20-02-2025 15:33:00","20-02-2025 16:33:=
59","Grid outage, site went down due to gen overload (22KVA, 330A), SS Blai=
se IHS is informed // Grid return","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (22KVA, 330A), SS Blaise IHS is informed // Grid return","ludovi=
c-anselme.mouliom-mapoure@sagemcom","429","20-02-2025 15:40:08","Sagemcom C=
MR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004392738","BIY=
EMASSI NIKI","","20-02-2025 15:17:48","20-02-2025 15:14:36","20-02-2025 16:=
33:39","Grid outage, site went down down due PWC overloaded (12 kw 250A) //=
Manually start of DG ,he reduiced the load.","Hyemafo Gildas","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Grid outage, site went down=
 down due PWC overloaded (12 kw 250A) //Manually start of DG ,he reduiced t=
he load.","wilfried.kameni@sagemcom.com","193","20-02-2025 15:17:48","Sagem=
com CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0004392645","Ese=
ka MTN","","20-02-2025 15:06:03","20-02-2025 15:03:32","20-02-2025 15:09:58=
","No power issue site on grid with U=3D 54 Etienne Fopa(695033981) is work=
ing on site  site up at 03:09 pm","Kemeni Franklin","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue site on grid with U=3D 54 Etienne Fopa(695033981) is working on site  s=
ite up at 03:09 pm","ervine.mbezele@sagemcom.com","152","20-02-2025 15:06:0=
3","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004392386","O=
LAMA","","20-02-2025 14:44:49","20-02-2025 14:40:42","21-02-2025 04:52:26",=
"No power issue on site U=3D54,9 V site on Gen , The Tx RM Alain/691144423/=
 from Huawei is informed","Fanda Brice","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D54,9 V site on Gen , The Tx RM Alain/691144423/ from Huawei is informed=
","ludovic-anselme.mouliom-mapoure@sagemcom","248","20-02-2025 14:44:49","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004392190","S=
calom-IHS","","20-02-2025 14:19:57","20-02-2025 14:10:44","20-02-2025 14:24=
:15","ACTIVE// No power issue on site Ubaie =3D52.3V site on Grid The TX Fm=
e Hosiah / 674007438// from huawei is informed.","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No=
 power issue on site Ubaie =3D52.3V site on Grid The TX Fme Hosiah / 674007=
438// from huawei is informed.","cedric.tiani@sagemcom.com","555","20-02-20=
25 14:19:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0004392133","B=
ondjock","","20-02-2025 14:10:05","20-02-2025 13:37:56","20-02-2025 14:00:4=
7","Grid outage, Site went down Gen failed to start due to Rcp faulty// He =
activated manually grid contactor and put site on grid ","Fanda Brice","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
outage, Site went down Gen failed to start due to Rcp faulty// He activated=
 manually grid contactor and put site on grid ","cedric.tiani@sagemcom.com"=
,"1931","20-02-2025 14:10:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0004392004","OLAMA","=
","20-02-2025 13:57:50","20-02-2025 09:30:10","20-02-2025 09:44:44","Cascad=
ed Incident from TTO4431966","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen fai=
led to start // Gen started (Investigation ongoing)","system","275425","20-=
02-2025 13:57:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004391500","M=
ontee-Anne-Rouge","","20-02-2025 13:07:28","20-02-2025 13:01:12","20-02-202=
5 18:34:33","Grid outage, No space to deploy MDG // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MDG // Grid return","cedric.tiani@sagemcom.com","376","20=
-02-2025 13:07:28","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004391490","Ole=
mbe MTN","","20-02-2025 13:05:43","20-02-2025 12:57:32","20-02-2025 15:28:3=
5","Grid Outage Site went down due to Grid Contactors Faulty on Site//He By=
pass it and Site is on Gen","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","ATS-AMF Issue","Grid Outage Site went down due to Grid Con=
tactors Faulty on Site//He Bypass it and Site is on Gen","ferot.nongni-djio=
gap@sagemcom.com","492","20-02-2025 13:05:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004390795","C=
rf-Nsam","","20-02-2025 11:34:09","20-02-2025 11:31:31","20-02-2025 12:08:3=
5","Site went down because MPR  dysfunctionning, IHS SS Pascaline is inform=
ed and confirmed // Site on Gen","MINKA NICOLAS","Equipment Repair","Passiv=
e","Rectifier","Rectifier Cabinet","Site went down because MPR  dysfunction=
ning, IHS SS Pascaline is informed and confirmed // Site on Gen","cedric.ti=
ani@sagemcom.com","159","20-02-2025 11:34:09","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004390792","AWA=
E OCM","","20-02-2025 11:33:21","20-02-2025 11:18:11","20-02-2025 11:42:41"=
,"Grid outage, Site went down before Gen start due to poor backup// DG star=
ted automatically.","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Grid return","ferot.nongni-djiogap@sagemcom.=
com","1629","20-02-2025 11:33:21","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004390537","Man=
guiers Dispensaire","","20-02-2025 11:00:23","20-02-2025 10:58:07","20-02-2=
025 12:23:47","Site went went down because gen failed to start due to grid =
bad voltage // Gen manually started","Fabrice Pouakam","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Site went went down b=
ecause gen failed to start due to grid bad voltage // Gen manually started"=
,"cedric.tiani@sagemcom.com","137","20-02-2025 11:00:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004390298","M=
efou-Assi","","20-02-2025 10:36:04","20-02-2025 10:32:58","20-02-2025 10:34=
:57","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME=
 Fulbert(654266068) from Huawei is informed","cedric.tiani@sagemcom.com","1=
87","20-02-2025 10:36:04","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004390212","Ole=
mbe MTN","","20-02-2025 10:30:44","20-02-2025 10:25:31","20-02-2025 11:19:2=
3","Site went down due to work(Fabrice(692852620) /Sagemcom, PM) // Enf of =
work","Fabrice Pouakam","Equipment Replacement","Passive","Planned Activity=
","Planned Activity - Passive","Site went down due to work(Fabrice(69285262=
0) /Sagemcom, PM) // Enf of work","cedric.tiani@sagemcom.com","314","20-02-=
2025 10:30:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004389984","M=
essassi 2","","20-02-2025 10:13:51","20-02-2025 10:05:41","20-02-2025 11:30=
:17","Site went down because PWC overload (12 kilo, 300A) , SS IHS Felix BA=
TEU confirmed //Site stabilized","Fabrice Pouakam","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Site went down because PWC =
overload (12 kilo, 300A) , SS IHS Felix BATEU confirmed //Site stabilized",=
"ferot.nongni-djiogap@sagemcom.com","492","20-02-2025 10:13:51","Sagemcom C=
MR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004389738","Bon=
djock","IHS_YND_687","20-02-2025 09:40:23","20-02-2025 09:30:10","20-02-202=
5 09:45:21","Grid outage, site went down because gen failed to start // Gen=
 started (Investigation ongoing)","Fanda Brice","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because ge=
n failed to start // Gen started (Investigation ongoing)","ferot.nongni-dji=
ogap@sagemcom.com","647","20-02-2025 09:40:23","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004389122","Ema=
na","","20-02-2025 08:03:48","20-02-2025 07:54:32","20-02-2025 08:04:14","G=
rid outage, Site went down before Gen start due to poor backup/ // Gen auto=
matically started","Fabrice Pouakam","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup/ // Gen automatically started","ferot.nongni-dji=
ogap@sagemcom.com","557","20-02-2025 08:03:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004389019","C=
RF Nkoabang","","20-02-2025 07:44:59","20-02-2025 07:41:41","20-02-2025 09:=
05:20","Grid outage No space to deploy // Grid power return","Mba Lazare He=
rve","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage No space to deploy // Grid power return","cedric.tiani@sagemcom.c=
om","199","20-02-2025 07:44:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004388844","H=
-General-Yde","","20-02-2025 07:00:32","20-02-2025 06:55:19","20-02-2025 08=
:11:47","Grid fluctuation, Site went down because Gen failed to start due t=
o bad voltage (absense of 2 phases)// He bypassed Grid and started Gen manu=
aly","Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid fluctuation, Site went down because Gen failed to =
start due to bad voltage (absense of 2 phases)// He bypassed Grid and start=
ed Gen manualy","ferot.nongni-djiogap@sagemcom.com","314","20-02-2025 07:00=
:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0004388761","N=
kolso","","20-02-2025 06:47:13","20-02-2025 06:45:04","20-02-2025 06:45:57"=
,"Active: no power , site is on grid with Ubaie=3D53V, Mohamadou(691144435)=
 from Huawei is inormed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no =
power , site is on grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei =
is inormed","ferot.nongni-djiogap@sagemcom.com","130","20-02-2025 06:47:13"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0004388465","Bon=
djock","","20-02-2025 06:06:17","20-02-2025 05:58:56","20-02-2025 06:22:23"=
,"GrId outage, site went down because gen failed to start // Gen manually s=
tarted (Investigation ongoing)","Fanda Brice","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","GrId outage, site went down because gen =
failed to start // Gen manually started (Investigation ongoing)","danick.tc=
hakouani@sagemcom.com","442","20-02-2025 06:06:17","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004388428","Ngo=
a Ekelle","","20-02-2025 05:57:18","20-02-2025 05:56:10","20-02-2025 06:22:=
28","ACTIVE//No power issue U =3D54,5V site on Grid.The TX FME Mbah Hosiah =
(674007438) from Huawei is informed","Paul BIBOUM","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No p=
ower issue U =3D54,5V site on Grid.The TX FME Mbah Hosiah (674007438) from =
Huawei is informed","danick.tchakouani@sagemcom.com","69","20-02-2025 05:57=
:18","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004388298","Ole=
mbe MTN","","20-02-2025 05:11:08","20-02-2025 05:02:51","20-02-2025 05:47:2=
5","Grid fluctuation, Site went down because Gen failed to start due to lac=
k of 02 phases// he bypass Grid and manually start the gen","Fabrice Pouaka=
m","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, Site went down because Gen failed to start due to lack =
of 02 phases// he bypass Grid and manually start the gen","mariam.tchonang@=
sagemcom.com","497","20-02-2025 05:11:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004388267","E=
mana lycee 2","","20-02-2025 04:53:19","20-02-2025 04:48:15","20-02-2025 06=
:50:28","Grid outage,Gen start and stopped due to ""high temp"" alarm//We a=
dd water and Gen manually started","Fabrice Pouakam","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age,Gen start and stopped due to ""high temp"" alarm//We add water and Gen =
manually started","danick.tchakouani@sagemcom.com","306","20-02-2025 04:53:=
19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004388228","M=
essassi 2","","20-02-2025 04:40:51","20-02-2025 04:38:34","20-02-2025 08:17=
:07","Site went down due to dysfunctionning of 5/5 rectifiers // He reset r=
ectifiers, site on grid ","Fabrice Pouakam","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down due to dysfunctionning of 5/5 =
rectifiers // He reset rectifiers, site on grid ","mariam.tchonang@sagemcom=
.com","138","20-02-2025 04:40:51","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004388218","SAA=
 Entrance","","20-02-2025 04:35:09","20-02-2025 04:28:47","20-02-2025 05:30=
:34","Grid outage .gen failed to start due to starter relay faulty // He by=
pass it and gen manually started","Parker Tchoup","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Relay Faulty","Grid outage .gen failed to start due =
to starter relay faulty // He bypass it and gen manually started","danick.t=
chakouani@sagemcom.com","384","20-02-2025 04:35:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004388193","O=
LAMA","","20-02-2025 04:27:48","20-02-2025 04:04:30","20-02-2025 04:09:22",=
"No power issue on site U=3D54,9 V site on Gen , The Tx RM Alain/691144423/=
 from Huawei is informed","Fanda Brice","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D54,9 V site on Gen , The Tx RM Alain/691144423/ from Huawei is informed=
","mariam.tchonang@sagemcom.com","1399","20-02-2025 04:27:48","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004388137","Accacia =
New","","20-02-2025 03:51:31","20-02-2025 03:10:39","20-02-2025 03:10:40","=
Cascaded Incident from TTO4430143","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","ACTIVE// No  power issue on site, site on Grid with=
 Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informe=
d. impacted by Nkolzie","system","269389","20-02-2025 03:51:31","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_152","NOCINC0004388138","Rd-Pt-Ex=
press","","20-02-2025 03:51:31","20-02-2025 03:10:39","20-02-2025 03:10:40"=
,"Cascaded Incident from TTO4430143","","Cascade Outage","Active","Cascade =
Active","Cascade Active","ACTIVE// No  power issue on site, site on Grid wi=
th Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is infor=
med. impacted by Nkolzie","system","269387","20-02-2025 03:51:31","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0004388110","Tamtam W=
eekend","","20-02-2025 03:34:30","20-02-2025 03:10:39","20-02-2025 03:10:40=
","Cascaded Incident from TTO4430143","Hyemafo Gildas","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","ACTIVE// No  power issue on site, =
site on Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from =
HUAWEI is informed. impacted by Nkolzie","system","269388","20-02-2025 03:3=
4:30","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004388092","Nsi=
meyong Terre Rouge","","20-02-2025 03:25:01","20-02-2025 03:23:50","20-02-2=
025 03:37:50","Site went down due to PWC dysfunction, SS IHS Fran=E7ois NDO=
UNGOU is informed and confirmed// Site stabilized","MINKA NICOLAS","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went d=
own due to PWC dysfunction, SS IHS Fran=E7ois NDOUNGOU is informed and conf=
irmed// Site stabilized","danick.tchakouani@sagemcom.com","72","20-02-2025 =
03:25:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004388084","Biyemass=
i LAC","","20-02-2025 03:20:00","20-02-2025 03:10:39","20-02-2025 03:10:40"=
,"Cascaded Incident from TTO4430143","","Cascade Outage","Active","Cascade =
Active","Cascade Active","ACTIVE// No  power issue on site, site on Grid wi=
th Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is infor=
med. impacted by Nkolzie","system","269389","20-02-2025 03:20:00","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0004388085","Montee-J=
ouvence-II","","20-02-2025 03:20:00","20-02-2025 03:10:39","20-02-2025 03:1=
0:40","Cascaded Incident from TTO4430143","Hyemafo Gildas","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","ACTIVE// No  power issue on si=
te, site on Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   f=
rom HUAWEI is informed. impacted by Nkolzie","system","269388","20-02-2025 =
03:20:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004388082","D=
amas","IHS_YND_562, IHS_YND_152, IHS_YND_151, IHS_YND_546, IHS_YND_518","20=
-02-2025 03:18:02","20-02-2025 03:10:39","20-02-2025 04:10:40","ACTIVE// No=
  power issue on site, site on Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosi=
ah //674007438/   from HUAWEI is informed. impacted by Nkolzie","MINKA NICO=
LAS","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","ACTIVE// No  power issue on site, site on Grid with Ubaie=
=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed. imp=
acted by Nkolzie","danick.tchakouani@sagemcom.com","444","20-02-2025 03:18:=
02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004387935","M=
efou-Assi","","20-02-2025 01:55:51","20-02-2025 01:51:31","20-02-2025 01:56=
:54","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME=
 Fulbert(654266068) from Huawei is informed","mariam.tchonang@sagemcom.com"=
,"261","20-02-2025 01:55:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004387929","S=
IMBOCK BONAMBAPE","","20-02-2025 01:51:44","20-02-2025 01:44:30","20-02-202=
5 01:50:06","Active//No power issue site on grid with U=3D56,5 V Mbah Osiah=
 from Huawei is informed Notice that it is the repetitive issu","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active//No power issue site on grid with U=3D56,5 V Mbah =
Osiah from Huawei is informed Notice that it is the repetitive issu","danic=
k.tchakouani@sagemcom.com","435","20-02-2025 01:51:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0004387759","Nkozoa",=
"","20-02-2025 00:47:41","19-02-2025 23:59:12","20-02-2025 00:55:26","Casca=
ded Incident from TTO4429493","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n fails to start (failed to start alarm) // Reset of gen card done and gen =
started (Investigation ongoing)","system","273911","20-02-2025 00:47:41","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0004387760","Nkolondo=
m","","20-02-2025 00:47:41","19-02-2025 23:59:12","20-02-2025 00:55:26","Ca=
scaded Incident from TTO4429493","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen fails to start (failed to start alarm) // Reset of gen card done and g=
en started (Investigation ongoing)","system","273911","20-02-2025 00:47:41"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0004387758","Messassi=
","","20-02-2025 00:47:41","19-02-2025 23:59:12","20-02-2025 00:55:26","Cas=
caded Incident from TTO4429493","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen fails to start (failed to start alarm) // Reset of gen card done and ge=
n started (Investigation ongoing)","system","273910","20-02-2025 00:47:41",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0004387757","Olembe-T=
erminus","","20-02-2025 00:47:40","19-02-2025 23:59:12","20-02-2025 00:55:2=
6","Cascaded Incident from TTO4429493","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen fails to start (failed to start alarm) // Reset of gen card done=
 and gen started (Investigation ongoing)","system","273912","20-02-2025 00:=
47:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0004387756","Ekombiti=
e","","20-02-2025 00:47:40","19-02-2025 23:59:12","20-02-2025 00:55:26","Ca=
scaded Incident from TTO4429493","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen fails to start (failed to start alarm) // Reset of gen card done and g=
en started (Investigation ongoing)","system","273912","20-02-2025 00:47:40"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004387566","M=
essassi 2","","20-02-2025 00:13:27","20-02-2025 00:11:07","20-02-2025 01:59=
:26","Site went down because PWC overload (12 kilo, 300A) , SS IHS Felix BA=
TEU confirmed //Site stabilized","Fabrice Pouakam","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Site went down because PWC =
overload (12 kilo, 300A) , SS IHS Felix BATEU confirmed //Site stabilized",=
"mariam.tchonang@sagemcom.com","141","20-02-2025 00:13:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0004387540","O=
lembe","IHS_YND_276, IHS_YND_300, IHS_YND_297, IHS_YND_306, IHS_YND_304","2=
0-02-2025 00:07:34","19-02-2025 23:59:12","20-02-2025 00:55:26","Grid outag=
e, site went down because gen fails to start (failed to start alarm) // Res=
et of gen card done and gen started (Investigation ongoing)","Fabrice Pouak=
am","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage, site went down because gen fails to start (failed to start alarm) // =
Reset of gen card done and gen started (Investigation ongoing)","mariam.tch=
onang@sagemcom.com","8199","20-02-2025 00:07:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_088","NOCINC0004387447","Elobi Mo=
kolo","","19-02-2025 23:42:21","19-02-2025 23:31:34","19-02-2025 23:31:35",=
"Cascaded Incident from TTO4429367","Mboua Thierry","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active// No power issue on site, Ubai=
e=3D54,7V site on Grid . Tx FME Brice (650214096) from Huawei is informed",=
"system","268231","19-02-2025 23:42:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_089","NOCINC0004387449","H-Prince=
","","19-02-2025 23:42:21","19-02-2025 23:31:34","19-02-2025 23:31:35","Cas=
caded Incident from TTO4429367","Mboua Thierry","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// No power issue on site, Ubaie=3D=
54,7V site on Grid . Tx FME Brice (650214096) from Huawei is informed","sys=
tem","268230","19-02-2025 23:42:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_201","NOCINC0004387450","Cite Ver=
te","","19-02-2025 23:42:21","19-02-2025 23:31:34","19-02-2025 23:31:35","C=
ascaded Incident from TTO4429367","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Active// No power issue on site, Ubaie=3D54,7V site =
on Grid . Tx FME Brice (650214096) from Huawei is informed","system","26822=
9","19-02-2025 23:42:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004387448","Nkomkana=
 2","","19-02-2025 23:42:21","19-02-2025 23:31:34","19-02-2025 23:31:35","C=
ascaded Incident from TTO4429367","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active// No power issue on site, Ubaie=
=3D54,7V site on Grid . Tx FME Brice (650214096) from Huawei is informed","=
system","268230","19-02-2025 23:42:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004387445","Entree C=
ite Verte","","19-02-2025 23:42:20","19-02-2025 23:31:34","19-02-2025 23:31=
:35","Cascaded Incident from TTO4429367","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active// No power issue on site, U=
baie=3D54,7V site on Grid . Tx FME Brice (650214096) from Huawei is informe=
d","system","268230","19-02-2025 23:42:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_559","NOCINC0004387446","BATA Mok=
olo OCM","","19-02-2025 23:42:20","19-02-2025 23:31:34","19-02-2025 23:31:3=
5","Cascaded Incident from TTO4429367","","Cascade Outage","Active","Cascad=
e Active","Cascade Active","Active// No power issue on site, Ubaie=3D54,7V =
site on Grid . Tx FME Brice (650214096) from Huawei is informed","system","=
268229","19-02-2025 23:42:20","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0004387439","Tsi=
nga","IHS_YND_543, IHS_YND_559, IHS_YND_088, IHS_YND_138, IHS_YND_089, IHS_=
YND_201","19-02-2025 23:39:53","19-02-2025 23:31:34","19-02-2025 23:31:35",=
"Active// No power issue on site, Ubaie=3D54,7V site on Grid . Tx FME Brice=
 (650214096) from Huawei is informed (Site impacted by sacre Coeur)","Mboua=
 Thierry","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active// No power issue on site, Ubaie=3D54,7V site o=
n Grid . Tx FME Brice (650214096) from Huawei is informed","danick.tchakoua=
ni@sagemcom.com","500","19-02-2025 23:39:53","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004387359","Ngo=
a Ekelle","","19-02-2025 23:28:37","19-02-2025 23:25:23","19-02-2025 23:39:=
23","Site went down because gen fails to start due to grid bad voltage, no =
RCP on site // Grid return","Paul BIBOUM","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Site went down because gen fails t=
o start due to grid bad voltage, no RCP on site // Grid return","danick.tch=
akouani@sagemcom.com","194","19-02-2025 23:28:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004387136","ELOUMDEM=
 CARRIERE 2","","19-02-2025 22:41:10","19-02-2025 22:35:52","19-02-2025 23:=
10:52","Cascaded Incident from TTO4429002","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down Insufficiency =
of retifier on site SS IHS Felix Zamb=E9 is informed and confirmed // site =
Stabilized","system","278776","19-02-2025 22:41:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004387135","Eto koss=
 Yde","","19-02-2025 22:41:10","19-02-2025 22:35:52","19-02-2025 23:10:52",=
"Cascaded Incident from TTO4429002","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down Insufficiency of reti=
fier on site SS IHS Felix Zamb=E9 is informed and confirmed // site Stabili=
zed","system","278777","19-02-2025 22:41:10","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004387120","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","19-02-2025 22:39:12","19-02-2025 22:35=
:52","19-02-2025 23:10:52","Site went down Insufficiency of retifier on sit=
e SS IHS Felix Zamb=E9 is informed and confirmed // site Stabilized","Fanda=
 Brice","Equipment Repair","Passive","Rectifier","Rectifier Module","Site w=
ent down Insufficiency of retifier on site SS IHS Felix Zamb=E9 is informed=
 and confirmed // site Stabilized","danick.tchakouani@sagemcom.com","201","=
19-02-2025 22:39:12","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004386543","Mel=
en Ba'aba","","19-02-2025 21:10:17","19-02-2025 21:05:08","19-02-2025 21:51=
:39","Grid outage site went down because Gen started and Stopped with alarm=
 under voltage // He reset the Gen card and Gen manually started","Siligap =
Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage site went down because Gen started and Stopped with alarm under vol=
tage // He reset the Gen card and Gen manually started","yves.djomo@sagemco=
m.com","343","19-02-2025 21:10:17","Sagemcom CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0004386452","Car=
refour Ayissi Ele","","19-02-2025 21:00:04","19-02-2025 20:56:59","19-02-20=
25 21:02:35","Active//No Power issue on site , site on battery with Ubaie=
=3D49,9 V The Tx Gregoire(654547479) from Huawei is informed and up at 09:0=
2 PM","Parker Tchoup","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","Active//No Power issue on site , site on =
battery with Ubaie=3D49,9 V The Tx Gregoire(654547479) from Huawei is infor=
med and up at 09:02 PM","yves.djomo@sagemcom.com","185","19-02-2025 21:00:0=
4","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0004386419","M=
fou EPC","","19-02-2025 20:52:52","19-02-2025 20:39:48","19-02-2025 20:58:4=
8","Grid outage, site went down because gen fails to start // Grid return (=
investigation ongoing)","Mba Lazare Herve","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage, site went down because gen fai=
ls to start // Grid return (investigation ongoing)","yves.djomo@sagemcom.co=
m","786","19-02-2025 20:52:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004386182","N=
KOLMEKONG YDE","","19-02-2025 20:12:28","19-02-2025 19:35:24","19-02-2025 2=
0:13:44","Site went down because PWC dysfunctionning IHS SS BERNARD ATANGAN=
A is informed and confirmed// Site stabilized","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went dow=
n because PWC dysfunctionning IHS SS BERNARD ATANGANA is informed and confi=
rmed// Site stabilized","yves.djomo@sagemcom.com","2225","19-02-2025 20:12:=
28","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004386168","Elo=
umdem stade","","19-02-2025 20:10:29","19-02-2025 20:06:17","19-02-2025 22:=
33:17","Grid bad voltage,and gen failed to start,no rcp // He Bypassed grid=
 started the gen","Fanda Brice","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Grid bad voltage,and gen failed to start,no =
rcp // He Bypassed grid started the gen","yves.djomo@sagemcom.com","253","1=
9-02-2025 20:10:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004386121","C=
rf-Nsam","","19-02-2025 20:06:54","19-02-2025 20:05:49","19-02-2025 20:07:2=
8","Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline is=
 informed and confirmed // Site stabilized","MINKA NICOLAS","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","Site went down bec=
ause PWC(24kilo) dysfunctionning, IHS SS Pascaline is informed and confirme=
d // Site stabilized","yves.djomo@sagemcom.com","66","19-02-2025 20:06:54",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004385885","O=
LAMA","","19-02-2025 19:31:02","19-02-2025 19:01:58","19-02-2025 19:05:38",=
"No power issue on site U=3D54,9 V site on Gen , The Tx RM Alain/691144423/=
 from Huawei is informed","Fanda Brice","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D54,9 V site on Gen , The Tx RM Alain/691144423/ from Huawei is informed=
","yves.djomo@sagemcom.com","1744","19-02-2025 19:31:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004385575","M=
essassi 2","","19-02-2025 18:31:08","19-02-2025 18:26:00","19-02-2025 18:42=
:37","Site went down because PWC overload (12 kilo, 300A) , SS IHS Felix BA=
TEU confirmed //Site stabilized","Fabrice Pouakam","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Site went down because PWC =
overload (12 kilo, 300A) , SS IHS Felix BATEU confirmed //Site stabilized",=
"el-dalile@sagemcom.com","310","19-02-2025 18:31:08","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004385563","AWA=
E OCM","","19-02-2025 18:29:09","19-02-2025 18:22:54","19-02-2025 18:48:17"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen start automatically","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen start automatically","el=
-dalile@sagemcom.com","376","19-02-2025 18:29:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004385396","Biyemass=
i LAC","","19-02-2025 18:03:41","19-02-2025 17:51:16","19-02-2025 18:01:39"=
,"Cascaded Incident from TTO4426923","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage, site went down before gen start d=
ue to poor battery backup //He bypassed Grid and started Gen manualy","syst=
em","266960","19-02-2025 18:03:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0004385398","Behind P=
 T school Yde","","19-02-2025 18:03:41","19-02-2025 17:51:16","19-02-2025 1=
8:01:39","Cascaded Incident from TTO4426923","Paul BIBOUM","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup //He bypassed Grid and started=
 Gen manualy","system","266959","19-02-2025 18:03:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0004385397","BONAS YD=
E","","19-02-2025 18:03:41","19-02-2025 17:51:16","19-02-2025 18:01:39","Ca=
scaded Incident from TTO4426923","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down before gen =
start due to poor battery backup //He bypassed Grid and started Gen manualy=
","system","266958","19-02-2025 18:03:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0004385395","Ngoa Eke=
lle","","19-02-2025 18:03:40","19-02-2025 17:51:16","19-02-2025 18:01:39","=
Cascaded Incident from TTO4426923","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down before ge=
n start due to poor battery backup //He bypassed Grid and started Gen manua=
ly","system","266959","19-02-2025 18:03:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0004385394","Obili Ch=
apelle","","19-02-2025 18:03:40","19-02-2025 17:51:16","19-02-2025 18:01:39=
","Cascaded Incident from TTO4426923","Paul BIBOUM","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 gen start due to poor battery backup //He bypassed Grid and started Gen ma=
nualy","system","266958","19-02-2025 18:03:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0004385393","Scalom",=
"","19-02-2025 18:03:40","19-02-2025 17:51:16","19-02-2025 18:01:39","Casca=
ded Incident from TTO4426923","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, site went down before gen sta=
rt due to poor battery backup //He bypassed Grid and started Gen manualy","=
system","266957","19-02-2025 18:03:40","Sagemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0004385374","Nlo=
ng Mvolye New","IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND_546, IHS_YND=
_683, IHS_YND_805","19-02-2025 17:59:27","19-02-2025 17:51:16","19-02-2025 =
18:01:39","Grid outage, site went down before gen start due to poor battery=
 backup //He bypassed Grid and started Gen manualy","Paul BIBOUM","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, site went down before gen start due to poor battery backup //He bypass=
ed Grid and started Gen manualy","el-dalile@sagemcom.com","491","19-02-2025=
 17:59:27","Sagemcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004385338","Ron=
d Point Express1114","","19-02-2025 17:50:16","19-02-2025 17:45:43","19-02-=
2025 17:56:27","Grid fluctuation, Site went down because Gen started and st=
opped due to Grid bad voltage // Site stabilized","Hyemafo Gildas","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation, Site went down because Gen started and stopped due to Grid bad vol=
tage // Site stabilized","el-dalile@sagemcom.com","274","19-02-2025 17:50:1=
6","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0004385056","BIYEMASS=
I NIKI","","19-02-2025 17:08:43","19-02-2025 15:51:15","19-02-2025 16:40:57=
","Cascaded Incident from TTO4426498","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage , Site went down be=
fore Gen start due to poor backup// Grid return","system","267058","19-02-2=
025 17:08:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004385053","Biyemass=
i LAC","","19-02-2025 17:08:42","19-02-2025 15:51:15","19-02-2025 16:40:57"=
,"Cascaded Incident from TTO4426498","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage , Site went down before Gen start =
due to poor backup// Grid return","system","267056","19-02-2025 17:08:42","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0004385054","Behind P=
 T school Yde","","19-02-2025 17:08:42","19-02-2025 15:51:15","19-02-2025 1=
6:40:57","Cascaded Incident from TTO4426498","Paul BIBOUM","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage , Site went dow=
n before Gen start due to poor backup// Grid return","system","267057","19-=
02-2025 17:08:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_507","NOCINC0004385055","BIYEM AS=
SI LYCEE","","19-02-2025 17:08:42","19-02-2025 15:51:15","19-02-2025 16:40:=
57","Cascaded Incident from TTO4426498","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage , Site went down =
before Gen start due to poor backup// Grid return","system","267057","19-02=
-2025 17:08:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0004385052","Ngoa Eke=
lle","","19-02-2025 17:08:42","19-02-2025 15:51:15","19-02-2025 16:40:57","=
Cascaded Incident from TTO4426498","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage , Site went down before G=
en start due to poor backup// Grid return","system","267057","19-02-2025 17=
:08:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0004385050","Scalom",=
"","19-02-2025 17:08:41","19-02-2025 15:51:15","19-02-2025 16:40:57","Casca=
ded Incident from TTO4426498","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage , Site went down before Gen st=
art due to poor backup// Grid return","system","267056","19-02-2025 17:08:4=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0004385051","Obili Ch=
apelle","","19-02-2025 17:08:41","19-02-2025 15:51:15","19-02-2025 16:40:57=
","Cascaded Incident from TTO4426498","Paul BIBOUM","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage , Site went down befor=
e Gen start due to poor backup// Grid return","system","267056","19-02-2025=
 17:08:41","Sagemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0004385021","Nlo=
ng Mvolye New","IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND_546, IHS_YND=
_805, IHS_YND_507, IHS_YND_724","19-02-2025 17:03:30","19-02-2025 15:51:15"=
,"19-02-2025 16:40:57","Grid outage , Site went down before Gen start due t=
o poor backup// Grid return","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage , Site went down be=
fore Gen start due to poor backup// Grid return","el-dalile@sagemcom.com","=
4336","19-02-2025 17:03:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004384988","C=
RH-Etoug-Ebe","","19-02-2025 16:57:21","19-02-2025 16:54:12","19-02-2025 17=
:40:00","Site went down due to work Our FME Mathieu (676774570) is on Site(=
 he add the second power departure)//  And off work","Hyemafo Gildas","Inst=
allation Activity","Passive","Planned Activity","Installation Activity","Si=
te went down due to work Our FME Mathieu (676774570) is on Site( he add the=
 second power departure)//  And off work","el-dalile@sagemcom.com","190","1=
9-02-2025 16:57:21","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004384895","Acc=
acia New","","19-02-2025 16:43:29","19-02-2025 16:39:23","19-02-2025 18:15:=
48","Grid outage// Grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","Grid outage// Grid return","yves.djomo@sagemcom=
.com","247","19-02-2025 16:43:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004384875","S=
calom-IHS","","19-02-2025 16:39:47","19-02-2025 16:31:40","19-02-2025 16:35=
:05","No power issue site on grid with U=3D52.1v site up The TX Fme Hosiah =
/ 674007438// from huawei is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site o=
n grid with U=3D52.1v site up The TX Fme Hosiah / 674007438// from huawei i=
s informed","yves.djomo@sagemcom.com","489","19-02-2025 16:39:47","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004384819","Tsi=
nga village","","19-02-2025 16:33:43","19-02-2025 16:30:33","19-02-2025 16:=
32:22","Site went down due to insufficiency of rectifier (Site on 02 rectif=
iers) SS IHS Bernard Atangana is informed and confirmed // Site stabilized"=
,"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to insufficiency of rectifier (Site on 02 rectifiers=
) SS IHS Bernard Atangana is informed and confirmed // Site stabilized","el=
-dalile@sagemcom.com","191","19-02-2025 16:33:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0004384783","H=
-Prince","","19-02-2025 16:27:37","19-02-2025 16:14:32","19-02-2025 16:30:1=
0","Site went down due to work SS IHS Bernard Atangana  is working on site =
// End of work","Mboua Thierry","Equipment Replacement","Passive","Planned =
Activity","Planned Activity - Passive","Site went down due to work SS IHS B=
ernard Atangana  is working on site // End of work","yves.djomo@sagemcom.co=
m","786","19-02-2025 16:27:37","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0004384679","Jou=
vence 2000","","19-02-2025 16:07:54","19-02-2025 16:01:44","19-02-2025 16:2=
0:30","Grid fluctuation, Site went down because Gen started and stopped due=
 to Grid bad voltage// He bypassed Grid and started Gen manualy","Delor Tel=
ezing","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, Site went down because Gen started and stopped due =
to Grid bad voltage// He bypassed Grid and started Gen manualy","el-dalile@=
sagemcom.com","371","19-02-2025 16:07:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004384673","Nomayos =
montee Meche","","19-02-2025 16:07:00","19-02-2025 16:00:09","19-02-2025 16=
:01:51","Cascaded Incident from TTO4426107","Fanda Brice","Cascade Outage",=
"Active","Cascade Active","Cascade Active","Active//No power issues iste on=
 Grid with U=3D53.4V ,The FME TX Fulbert (654266068) from Huawei is working=
 on site","system","266474","19-02-2025 16:07:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004384674","Nkolfon =
Cimencam","","19-02-2025 16:07:00","19-02-2025 16:00:09","19-02-2025 16:01:=
51","Cascaded Incident from TTO4426107","Hyemafo Gildas","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active//No power issues iste on =
Grid with U=3D53.4V ,The FME TX Fulbert (654266068) from Huawei is working =
on site","system","266474","19-02-2025 16:07:00","Sagemcom CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004384670","Nom=
ayos","IHS_YND_791, IHS_YND_762","19-02-2025 16:05:27","19-02-2025 16:00:09=
","19-02-2025 16:01:51","Active//No power issues iste on Grid with U=3D53.4=
V ,The FME TX Fulbert (654266068) from Huawei is working on site","Fanda Br=
ice","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active//No power issues iste on Grid with U=3D53.4V ,The F=
ME TX Fulbert (654266068) from Huawei is working on site","el-dalile@sagemc=
om.com","319","19-02-2025 16:05:27","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0004384605","Nko=
mo stade","","19-02-2025 15:56:00","19-02-2025 15:51:52","19-02-2025 16:11:=
18","Grid outage, site went down before gen start due to poor battery backu=
p // Gen start automatically","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"el-dalile@sagemcom.com","249","19-02-2025 15:56:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004384279","M=
ontee-Des-Soeurs","","19-02-2025 15:24:20","19-02-2025 15:15:12","19-02-202=
5 15:24:17","Grid outage, Site went down before Gen start due to poor backu=
p// GEN automatically started","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before Gen start due to poor backup// GEN automatically started","yves.dj=
omo@sagemcom.com","550","19-02-2025 15:24:20","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004384276","Tou=
ring Club International","","19-02-2025 15:23:39","19-02-2025 15:19:28","19=
-02-2025 15:27:39","Grid Outage Site went down because Gen overload (20Kw, =
270A) SS IHS Pascaline is informed// Grid Restored","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage Site went d=
own because Gen overload (20Kw, 270A) SS IHS Pascaline is informed// Grid R=
estored","el-dalile@sagemcom.com","252","19-02-2025 15:23:39","Sagemcom CMR=
"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004384254","AWA=
E OCM","","19-02-2025 15:21:50","19-02-2025 15:16:31","19-02-2025 15:33:43"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen start automatically","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen start automatically","el=
-dalile@sagemcom.com","320","19-02-2025 15:21:50","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004384111","AKA=
K Nkozoa","","19-02-2025 15:07:32","19-02-2025 14:50:27","19-02-2025 16:03:=
23","Grid outage,DG started and stopped due to Alarm overcurrent // He bypa=
ssed captor of current, reset Gen card and manually start of DG.","Fabrice =
Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage,DG started and stopped due to Alarm overcurrent // He bypassed ca=
ptor of current, reset Gen card and manually start of DG.","yves.djomo@sage=
mcom.com","1025","19-02-2025 15:07:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0004384020","BONAS YD=
E","","19-02-2025 14:57:24","19-02-2025 14:53:11","19-02-2025 15:31:55","Ca=
scaded Incident from TTO4425298","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, Site went down because Gen=
 failed to start due to battery Gen discharged// He started Gen with extern=
al battery (investigation ongoing)","system","270669","19-02-2025 14:57:24"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0004384022","BIYEMASS=
I NIKI","","19-02-2025 14:57:24","19-02-2025 14:53:11","19-02-2025 15:31:55=
","Cascaded Incident from TTO4425298","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bec=
ause Gen failed to start due to battery Gen discharged// He started Gen wit=
h external battery (investigation ongoing)","system","270671","19-02-2025 1=
4:57:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0004384021","Behind P=
 T school Yde","","19-02-2025 14:57:24","19-02-2025 14:53:11","19-02-2025 1=
5:31:55","Cascaded Incident from TTO4425298","Paul BIBOUM","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down=
 because Gen failed to start due to battery Gen discharged// He started Gen=
 with external battery (investigation ongoing)","system","270672","19-02-20=
25 14:57:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0004384016","Obili Ch=
apelle","","19-02-2025 14:57:23","19-02-2025 14:53:11","19-02-2025 15:31:55=
","Cascaded Incident from TTO4425298","Paul BIBOUM","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen failed to start due to battery Gen discharged// He started Gen with e=
xternal battery (investigation ongoing)","system","270671","19-02-2025 14:5=
7:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004384018","Accacia =
New","","19-02-2025 14:57:23","19-02-2025 14:53:11","19-02-2025 15:31:55","=
Cascaded Incident from TTO4425298","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage, Site went down because Gen failed t=
o start due to battery Gen discharged// He started Gen with external batter=
y (investigation ongoing)","system","270669","19-02-2025 14:57:23","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004384019","Biyemass=
i LAC","","19-02-2025 14:57:23","19-02-2025 14:53:11","19-02-2025 15:31:55"=
,"Cascaded Incident from TTO4425298","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage, Site went down because Gen failed=
 to start due to battery Gen discharged// He started Gen with external batt=
ery (investigation ongoing)","system","270669","19-02-2025 14:57:23","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0004384017","Ngoa Eke=
lle","","19-02-2025 14:57:23","19-02-2025 14:53:11","19-02-2025 15:31:55","=
Cascaded Incident from TTO4425298","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down because G=
en failed to start due to battery Gen discharged// He started Gen with exte=
rnal battery (investigation ongoing)","system","270670","19-02-2025 14:57:2=
3","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0004384015","Scalom",=
"","19-02-2025 14:57:22","19-02-2025 14:53:11","19-02-2025 15:31:55","Casca=
ded Incident from TTO4425298","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, Site went down because Gen fa=
iled to start due to battery Gen discharged// He started Gen with external =
battery (investigation ongoing)","system","270670","19-02-2025 14:57:22","S=
agemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0004383950","Nlo=
ng Mvolye New","IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND_562, IHS_YND=
_546, IHS_YND_683, IHS_YND_805, IHS_YND_724","19-02-2025 14:54:44","19-02-2=
025 14:53:11","19-02-2025 15:31:55","Grid outage, Site went down because Ge=
n failed to start due to battery Gen discharged// He started Gen with exter=
nal battery (investigation ongoing)","Paul BIBOUM","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Generator Battery","Grid outage, Site went down bec=
ause Gen failed to start due to battery Gen discharged// He started Gen wit=
h external battery (investigation ongoing)","el-dalile@sagemcom.com","93","=
19-02-2025 14:54:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004383900","B=
arriere","","19-02-2025 14:50:07","19-02-2025 14:42:04","19-02-2025 14:59:3=
6","Site went down because gen failed tos tart due to grid bad voltgae and =
no RCP // Grid Stabilized","Hyemafo Gildas","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Site went down because gen faile=
d tos tart due to grid bad voltgae and no RCP // Grid Stabilized","yves.djo=
mo@sagemcom.com","484","19-02-2025 14:50:07","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004383822","MBA=
LNGONG LYCEE","","19-02-2025 14:41:33","19-02-2025 14:39:28","19-02-2025 14=
:43:28","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and confirmed // Grid Restored","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage, Site went down because Gen stopped due to overload(9kva, 130A) SS =
IHS Felix Zambe is informed and confirmed // Grid Restored","yves.djomo@sag=
emcom.com","126","19-02-2025 14:41:33","Sagemcom CMR"
"Closed Complete","Site Down","T1751","IHS_YND_213","NOCINC0004383594","Nko=
lmesseng","","19-02-2025 14:08:37","19-02-2025 14:00:29","19-02-2025 14:05:=
04","ACTIVE// No Power issue on site ,site on Grid with Ubaie=3D54,5 VThe T=
x FME RM TX Martial 650252214// From  Huawei is informed","Siligap Boris","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","ACTIVE// No Power issue on site ,site on Grid with Ubaie=3D54,5 =
VThe Tx FME RM TX Martial 650252214// From  Huawei is informed","ludovic-an=
selme.mouliom-mapoure@sagemcom","489","19-02-2025 14:08:37","Sagemcom CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0004383411","Bye=
massi Carrefour","","19-02-2025 13:39:54","19-02-2025 13:35:42","19-02-2025=
 14:24:39","Site went down due to work : Our Tecnician Paul Biboum/SAGEMCOM=
/ 690625920 with SS IHS Fran=E7ois NDOUNGOU working on site (replacement of=
 DC cable)// End of work","Paul BIBOUM","Installation Activity","Passive","=
Planned Activity","Installation Activity","Site went down due to work : Our=
 Tecnician Paul Biboum/SAGEMCOM/ 690625920 with SS IHS Fran=E7ois NDOUNGOU =
working on site (replacement of DC cable)// End of work","ludovic-anselme.m=
ouliom-mapoure@sagemcom","253","19-02-2025 13:39:54","Sagemcom CMR"
"Cancelled","Warning","T1367","IHS_YND_805","NOCINC0004383375","Behind P T =
school Yde","","19-02-2025 13:32:56","","","WRONGLY TICKET","Paul BIBOUM","=
","","","","","ludovic-anselme.mouliom-mapoure@sagemcom","312","19-02-2025 =
13:32:56","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004383201","NYO=
M 2 IHS","","19-02-2025 13:06:56","19-02-2025 13:05:32","19-02-2025 13:10:4=
2","No power issue site on grid with U=3D53v TSOMO(693877192) from TELIS is=
 working on site  ","Fabrice Pouakam","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gr=
id with U=3D53v TSOMO(693877192) from TELIS is working on site  ","ludovic-=
anselme.mouliom-mapoure@sagemcom","85","19-02-2025 13:06:56","Sagemcom CMR"
"Closed Complete","Site Down","T0290","IHS_YND_067","NOCINC0004382740","Nko=
a Ayos","","19-02-2025 12:07:59","19-02-2025 11:56:42","19-02-2025 12:00:25=
","No power issue site on grid with U=3D53.2v site up 12:08 PM Eloundou Ber=
trand from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on grid with U=3D53.2v site up 12:08 PM Eloundou Bertrand from Huawei i=
s informed","ludovic-anselme.mouliom-mapoure@sagemcom","678","19-02-2025 12=
:07:59","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004382571","Crf=
-Nsam","","19-02-2025 11:42:12","19-02-2025 11:35:03","19-02-2025 11:38:58"=
,"Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline is i=
nformed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Site went down because PWC(24kilo) dysfunctionning, I=
HS SS Pascaline is informed","ludovic-anselme.mouliom-mapoure@sagemcom","43=
0","19-02-2025 11:42:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0004382544","MBALNGON=
G LYCEE","","19-02-2025 11:38:50","19-02-2025 11:31:12","19-02-2025 11:32:3=
2","Cascaded Incident from TTO4423650","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D54v Notice that site is impacted by AHALA who Augustin Nongni(682246750)=
 from Teliinfra is working on site ","system","268233","19-02-2025 11:38:50=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0004382543","ELOUMDEM=
 CARRIERE","","19-02-2025 11:38:50","19-02-2025 11:31:12","19-02-2025 11:32=
:32","Cascaded Incident from TTO4423650","Fanda Brice","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D54v Notice that site is impacted by AHALA who Augustin Nongni(682246750)=
 from Teliinfra is working on site ","system","268233","19-02-2025 11:38:50=
","Sagemcom CMR"
"Closed Complete","Site Down","T1557","IHS_YND_313","NOCINC0004382528","Afa=
noya","IHS_YND_767, IHS_YND_765","19-02-2025 11:37:20","19-02-2025 11:31:12=
","19-02-2025 11:32:32","No power issue site on grid with U=3D54v Notice th=
at site is impacted by AHALA who Augustin Nongni(682246750) from Teliinfra =
is working on site ","Hyemafo Gildas","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gr=
id with U=3D54v Notice that site is impacted by AHALA who Augustin Nongni(6=
82246750) from Teliinfra is working on site ","ludovic-anselme.mouliom-mapo=
ure@sagemcom","415","19-02-2025 11:37:20","Sagemcom CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0004382425","Djo=
nassi-Yde","","19-02-2025 11:21:20","19-02-2025 11:19:13","19-02-2025 11:21=
:07","No power issue site on grid with U=3D53.2v site up at 11:21 AM Sympho=
rien from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
site on grid with U=3D53.2v site up at 11:21 AM Symphorien from Huawei is i=
nformed","ludovic-anselme.mouliom-mapoure@sagemcom","128","19-02-2025 11:21=
:20","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004382422","OBA=
M NGOLA OCM","","19-02-2025 11:20:29","19-02-2025 11:17:18","19-02-2025 12:=
01:20","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Site went down due to PSC3 dysfonction SS IHS Pascal=
ine confirmed// Site stabilized","ludovic-anselme.mouliom-mapoure@sagemcom"=
,"192","19-02-2025 11:20:29","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004382193","Nsi=
meyong Terre Rouge","","19-02-2025 10:46:26","19-02-2025 10:41:17","19-02-2=
025 11:32:01","Site went down due to PWC dysfunction, SS IHS Fran=E7ois NDO=
UNGOU is informed and confirmed// Site stabilized","MINKA NICOLAS","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went d=
own due to PWC dysfunction, SS IHS Fran=E7ois NDOUNGOU is informed and conf=
irmed// Site stabilized","ludovic-anselme.mouliom-mapoure@sagemcom","310","=
19-02-2025 10:46:26","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004382117","NYO=
M FACE MAETUR","","19-02-2025 10:34:01","19-02-2025 10:25:53","19-02-2025 1=
1:18:45","Grid outage,site went down due to Gen failed to start  //Grid ret=
urn (Investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage,site went down due to Gen f=
ailed to start  //Grid return (Investigation ongoing)","ludovic-anselme.mou=
liom-mapoure@sagemcom","489","19-02-2025 10:34:01","Sagemcom CMR"
"Closed Complete","Site Down","T0395","IHS_YND_065","NOCINC0004382031","Ess=
os DCS","","19-02-2025 10:24:48","19-02-2025 10:22:34","19-02-2025 16:31:58=
","Site went down due to insufficience of  rectifier on site causing by loa=
d increase SS HIS Alphonse Deffo  is informed and confirmed// He added 01 r=
ectifier. But site remains down and Site up after Pow","Delor Telezing","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module","Site went down du=
e to insufficience of  rectifier on site causing by load increase SS HIS Al=
phonse Deffo  is informed and confirmed// He added 01 rectifier. But site r=
emains down and Site up after Power reset","cedric.tiani@sagemcom.com","135=
","19-02-2025 10:24:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004382021","M=
essassi 2","","19-02-2025 10:23:56","19-02-2025 10:22:44","19-02-2025 10:31=
:09","Site went down due to disfunctionning of PWC (12 kilo) , bernard IHS =
confirmed //Site stabilized","Fabrice Pouakam","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Site went down due to disfuncti=
onning of PWC (12 kilo) , bernard IHS confirmed //Site stabilized","cedric.=
tiani@sagemcom.com","73","19-02-2025 10:23:56","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004381563","Ebo=
go","","19-02-2025 09:17:24","19-02-2025 09:15:17","19-02-2025 09:16:17","G=
rid fluctuation, site went down before gen start due to poor battery backup=
 // Gen start automatically","Siligap Boris","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid fluctuation, site went d=
own before gen start due to poor battery backup // Gen start automatically"=
,"ludovic-anselme.mouliom-mapoure@sagemcom","129","19-02-2025 09:17:24","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004381211","H=
-General-Yde","","19-02-2025 08:34:27","19-02-2025 08:32:55","19-02-2025 08=
:38:53"," site went down because Gen fails to start  due to Grid bad voltag=
e  //Grid return(investigation ongoing)","Siligap Boris","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel"," site went down because Gen f=
ails to start  due to Grid bad voltage  //Grid return(investigation ongoing=
)","ludovic-anselme.mouliom-mapoure@sagemcom","93","19-02-2025 08:34:27","S=
agemcom CMR"
"Closed Complete","Site Down","T0395","IHS_YND_065","NOCINC0004380955","Ess=
os DCS","","19-02-2025 07:38:09","19-02-2025 07:35:01","19-02-2025 08:32:44=
","Site went down due to insufficient rectifier on site due to charge incre=
ase SS  HIS  Alphonse Deffo  is informed and confirmed//site stabilised","D=
elor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to insufficient rectifier on site due to charge increas=
e SS  HIS  Alphonse Deffo  is informed and confirmed//site stabilised","lud=
ovic-anselme.mouliom-mapoure@sagemcom","189","19-02-2025 07:38:09","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004380862","M=
ontee-Jouvence-II","","19-02-2025 07:26:29","19-02-2025 07:24:52","19-02-20=
25 07:26:19","	Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix=
 Zamb=E9 confirmed // Site stabilized","Hyemafo Gildas","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","	Site went down due to=
 PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site stabilize=
d","cedric.tiani@sagemcom.com","98","19-02-2025 07:26:29","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004380712","NYO=
M FACE MAETUR","","19-02-2025 06:53:50","19-02-2025 06:51:44","19-02-2025 0=
8:24:04","Grid outage,Gen failed to start  //Grid return (Investigation ong=
oing)","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid outage,Gen failed to start  //Grid return (Investigation=
 ongoing)","ludovic-anselme.mouliom-mapoure@sagemcom","128","19-02-2025 06:=
53:50","Sagemcom CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0004380470","Kon=
dengui MTN","","19-02-2025 06:04:34","19-02-2025 05:57:23","19-02-2025 06:3=
4:00","Site went down because Gen failed to start due to lack of 01 phase o=
n site // He did a bridge with a good phase","Albran Byorel","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Site went down =
because Gen failed to start due to lack of 01 phase on site // He did a bri=
dge with a good phase","wilfried.kameni@sagemcom.com","432","19-02-2025 06:=
04:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004380173","N=
KOLMEKONG YDE","","19-02-2025 04:41:53","19-02-2025 04:35:44","19-02-2025 1=
9:31:31","Site went down because PWC dysfunctionning IHS SS BERNARD ATANGAN=
A is informed and confirmed// Site stabilized. Site Up after Power reset","=
Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","Site went down because PWC dysfunctionning IHS SS BERNARD ATA=
NGANA is informed and confirmed// Site stabilized. Site Up after Power rese=
t","danick.tchakouani@sagemcom.com","370","19-02-2025 04:41:53","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004379893","F=
ouda-New","","19-02-2025 03:23:21","19-02-2025 03:21:15","19-02-2025 04:53:=
05","Access issue during the night Grid outage .gen failed to start due to =
card GE dysfunctionning//Grid return","Delor Telezing","Access Denial","Sec=
urity","Security Concerns In Site Environs","Access Issue - Security","Acce=
ss issue during the night Grid outage .gen failed to start due to card GE d=
ysfunctionning//Grid return","danick.tchakouani@sagemcom.com","127","19-02-=
2025 03:23:21","Sagemcom CMR"
"Closed Complete","Site Down","T0395","IHS_YND_065","NOCINC0004379787","Ess=
os DCS","","19-02-2025 02:38:15","19-02-2025 02:30:03","19-02-2025 02:40:03=
","access isuue due to land load grid outage, site went down because gen fa=
ild to start//Grid return (investigation ongoing)","Delor Telezing","Access=
 Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lo=
rd","access isuue due to land load grid outage, site went down because gen =
faild to start//Grid return (investigation ongoing)","danick.tchakouani@sag=
emcom.com","493","19-02-2025 02:38:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004379686","MEHANDAN=
","","19-02-2025 01:55:10","19-02-2025 01:12:08","19-02-2025 01:12:09","Cas=
caded Incident from TTO4420353","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue, site is on grid with Ubai=
e=3D55,1V, site up at 01:22 AM, Lionel Steeve(655184876) from Huawei is inf=
ormed","system","262182","19-02-2025 01:55:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_800","NOCINC0004379638","ODZA CIT=
E MBIA","","19-02-2025 01:32:50","19-02-2025 01:12:08","19-02-2025 01:12:09=
","Cascaded Incident from TTO4420353","Albran Byorel","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue, site is on grid wit=
h Ubaie=3D55,1V, site up at 01:22 AM, Lionel Steeve(655184876) from Huawei =
is informed","system","262183","19-02-2025 01:32:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_730","NOCINC0004379639","Odza pet=
it marche new","","19-02-2025 01:32:50","19-02-2025 01:12:08","19-02-2025 0=
1:12:09","Cascaded Incident from TTO4420353","Albran Byorel","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue, site is on g=
rid with Ubaie=3D55,1V, site up at 01:22 AM, Lionel Steeve(655184876) from =
Huawei is informed","system","262179","19-02-2025 01:32:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004379621","Odza II =
OCM","","19-02-2025 01:21:41","19-02-2025 01:12:08","19-02-2025 01:12:09","=
Cascaded Incident from TTO4420353","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue, site is on grid with U=
baie=3D55,1V, site up at 01:22 AM, Lionel Steeve(655184876) from Huawei is =
informed","system","262185","19-02-2025 01:21:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004379622","Odza Min=
kan IHS","","19-02-2025 01:21:41","19-02-2025 01:12:08","19-02-2025 01:12:0=
9","Cascaded Incident from TTO4420353","Albran Byorel","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue, site is on grid wi=
th Ubaie=3D55,1V, site up at 01:22 AM, Lionel Steeve(655184876) from Huawei=
 is informed","system","262184","19-02-2025 01:21:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004379620","Mehanda =
1","","19-02-2025 01:21:41","19-02-2025 01:12:08","19-02-2025 01:12:09","Ca=
scaded Incident from TTO4420353","Albran Byorel","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue, site is on grid with Uba=
ie=3D55,1V, site up at 01:22 AM, Lionel Steeve(655184876) from Huawei is in=
formed","system","262180","19-02-2025 01:21:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004379623","ODZA MIN=
KAN EDIBI ASSI","","19-02-2025 01:21:41","19-02-2025 01:12:08","19-02-2025 =
01:12:09","Cascaded Incident from TTO4420353","Albran Byorel","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","No power issue, site is on =
grid with Ubaie=3D55,1V, site up at 01:22 AM, Lionel Steeve(655184876) from=
 Huawei is informed","system","262181","19-02-2025 01:21:41","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004379611","Nko=
lnda","IHS_YND_800, IHS_YND_730, IHS_YND_723, IHS_SGM_007, IHS_YND_528, IHS=
_YND_746, IHS_SGM_108, IHS_YND_527, IHS_YND_410, IHS_YND_715, IHS_SGM_009, =
IHS_SGM_109, IHS_YND_749, IHS_EBO_015, IHS_SGM_004, IHS_BER_085, IHS_SGM_01=
4","19-02-2025 01:20:19","19-02-2025 01:12:08","19-02-2025 01:12:09","No po=
wer issue, site is on grid with Ubaie=3D55,1V, site up at 01:22 AM, Lionel =
Steeve(655184876) from Huawei is informed","Albran Byorel","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue, site is on grid with Ubaie=3D55,1V, site up at 01:22 AM, Lionel=
 Steeve(655184876) from Huawei is informed","wilfried.kameni@sagemcom.com",=
"492","19-02-2025 01:20:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004379256","Saa","",=
"18-02-2025 23:54:50","18-02-2025 23:49:11","19-02-2025 00:04:18","Cascaded=
 Incident from TTO4419938","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen sta=
rt and stopped with high temp alarm // He oppened the doors and Gen manuall=
y started","system","267335","18-02-2025 23:54:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004379255","SAA Entr=
ance","","18-02-2025 23:54:50","18-02-2025 23:49:11","19-02-2025 00:04:18",=
"Cascaded Incident from TTO4419938","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen start and stopped with high temp alarm // He oppened the doors and Ge=
n manually started","system","267335","18-02-2025 23:54:50","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004379252","SAA=
 2","IHS_YND_542, IHS_YND_405","18-02-2025 23:53:38","18-02-2025 23:46:11",=
"19-02-2025 00:04:35","Grid outage, site went down because gen start and st=
opped with high temp alarm // He oppened the doors and Gen manually started=
","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","Gen Temp High","=
Grid outage, site went down because gen start and stopped with high temp al=
arm // He oppened the doors and Gen manually started","wilfried.kameni@sage=
mcom.com","472","18-02-2025 23:53:38","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004379005","Lab=
oratoire  Meka","","18-02-2025 22:49:47","18-02-2025 22:47:20","18-02-2025 =
22:50:07","Active// No power issue U=3D54.5V site on Grid The FME TX eloudo=
u (693212405) From Huawei is informed.","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power is=
sue U=3D54.5V site on Grid The FME TX eloudou (693212405) From Huawei is in=
formed.","wilfried.kameni@sagemcom.com","148","18-02-2025 22:49:47","Sagemc=
om CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004378898","Pha=
rmacie SION","","18-02-2025 22:38:13","18-02-2025 22:29:06","18-02-2025 22:=
39:39","Grid outage, Site went down before Gen start due to poor backup// G=
rid power return","Paul BIBOUM","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup// Grid power return","ludovic-anselme.mouliom-mapoure=
@sagemcom","548","18-02-2025 22:38:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004378429","A=
wae Ewonkan","","18-02-2025 21:39:53","18-02-2025 21:25:31","18-02-2025 21:=
49:45","Grid outage, Site went down before Gen start due to poor backup// G=
rid power return","Albran Byorel","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup// Grid power return","ferot.nongni-djiogap@sagemcom=
.com","863","18-02-2025 21:39:53","Sagemcom CMR"
"Cancelled","Warning","T1571","IHS_YND_535","NOCINC0004378368","Awae Ewonka=
n","","18-02-2025 21:31:49","","","FME IS ON THE way to site ETA=3D10:20 pm=
","Albran Byorel","","","","","","ludovic-anselme.mouliom-mapoure@sagemcom"=
,"249","18-02-2025 21:31:49","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004378229","AWA=
E OCM","","18-02-2025 21:16:33","18-02-2025 21:14:26","18-02-2025 21:24:38"=
,"Grid outage, Site went down before Gen start due to poor backup// Grid po=
wer return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, Site went down before Gen star=
t due to poor backup// Grid power return","ludovic-anselme.mouliom-mapoure@=
sagemcom","128","18-02-2025 21:16:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004378024","Eto koss=
 Yde","","18-02-2025 20:50:40","18-02-2025 20:45:15","18-02-2025 20:49:45",=
"Cascaded Incident from TTO4418492","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down Insufficiency of reti=
fier on site SS IHS Felix Zamb=E9 is informed and confirmed // site Stabili=
zed","system","278407","18-02-2025 20:50:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004378025","ELOUMDEM=
 CARRIERE 2","","18-02-2025 20:50:40","18-02-2025 20:45:15","18-02-2025 20:=
49:45","Cascaded Incident from TTO4418492","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down Insufficiency =
of retifier on site SS IHS Felix Zamb=E9 is informed and confirmed // site =
Stabilized","system","278407","18-02-2025 20:50:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004378006","C=
RH-Etoug-Ebe","","18-02-2025 20:49:01","18-02-2025 20:38:56","18-02-2025 20=
:50:56","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen start automatically=
","ferot.nongni-djiogap@sagemcom.com","606","18-02-2025 20:49:01","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004378004","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","18-02-2025 20:48:42","18-02-2025 20:45=
:15","18-02-2025 22:59:45","Site went down Insufficiency of retifier on sit=
e SS IHS Felix Zamb=E9 is informed and confirmed // site Stabilized","Fanda=
 Brice","Equipment Repair","Passive","Rectifier","Rectifier Module","Site w=
ent down Insufficiency of retifier on site SS IHS Felix Zamb=E9 is informed=
 and confirmed // site Stabilized","ludovic-anselme.mouliom-mapoure@sagemco=
m","209","18-02-2025 20:48:42","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004377997","Lad=
a I Yde","","18-02-2025 20:47:39","18-02-2025 20:43:13","18-02-2025 21:01:0=
3","Active//No power issue site on Gen Ubaie=3D54.3V  The tx fme Lionel ste=
ve ADJEP/655184876/ from Huawei is informed ","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue site on Gen Ubaie=3D54.3V  The tx fme Lionel steve=
 ADJEP/655184876/ from Huawei is informed ","ludovic-anselme.mouliom-mapour=
e@sagemcom","267","18-02-2025 20:47:39","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004377974","OBA=
M NGOLA OCM","","18-02-2025 20:43:19","18-02-2025 20:38:12","18-02-2025 21:=
34:37","	Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed/=
/ Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","	Site went down due to PSC3 dysfonction SS IHS Pasc=
aline confirmed// Site stabilized","ludovic-anselme.mouliom-mapoure@sagemco=
m","308","18-02-2025 20:43:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004377835","M=
ontee-Jouvence-II","","18-02-2025 20:17:34","18-02-2025 20:16:27","18-02-20=
25 22:54:27","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed // Site stabilized","Hyemafo Gildas","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Site went down due to P=
WC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site stabilized"=
,"ferot.nongni-djiogap@sagemcom.com","68","18-02-2025 20:17:34","Sagemcom C=
MR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004377760","SOA=
 VILLAGE","","18-02-2025 20:08:13","18-02-2025 20:05:06","18-02-2025 20:35:=
47","	Site went down because Gen stopped with alarm"" low oil pressure "" (=
unprouven Alarm) because oil sensor faulty //He reset Gen card and started =
Gen manaully","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","	Site went down because Gen stopped with alarm"" low oil=
 pressure "" (unprouven Alarm) because oil sensor faulty //He reset Gen car=
d and started Gen manaully","ludovic-anselme.mouliom-mapoure@sagemcom","188=
","18-02-2025 20:08:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_621","IHS_YND_278","NOCINC0004377680","N=
kolfoulou 2","","18-02-2025 19:57:45","18-02-2025 19:51:39","18-02-2025 20:=
02:04","incorrectly  logged ticket","Siligap Boris","Incorrectly Logged Tic=
kets","Error","Error","Error","incorrectly  logged ticket","ferot.nongni-dj=
iogap@sagemcom.com","366","18-02-2025 19:57:45","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004377658","Aka=
k-Nkozoa-MTN-IHS","","18-02-2025 19:54:15","18-02-2025 19:50:03","18-02-202=
5 19:54:33","Grid outage, Site went down because Gen stopped due to chargin=
g alternator disfunction SS Felix Bateu is informed //Grid return","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternat=
or","Grid outage, Site went down because Gen stopped due to charging altern=
ator disfunction SS Felix Bateu is informed //Grid return","ludovic-anselme=
.mouliom-mapoure@sagemcom","253","18-02-2025 19:54:15","Sagemcom CMR"
"Closed Complete","Site Down","T2585","IHS_YND_744","NOCINC0004377631","Ele=
veur Meec Bon Berger","","18-02-2025 19:49:43","18-02-2025 19:47:27","18-02=
-2025 19:49:57","Grid outage, site went down before gen start due to poor b=
attery backup // Gen start automatically","Siligap Boris","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen start automa=
tically","ludovic-anselme.mouliom-mapoure@sagemcom","137","18-02-2025 19:49=
:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004377589","N=
KOLMEKONG YDE","","18-02-2025 19:40:45","18-02-2025 19:33:36","19-02-2025 0=
0:11:27","Site unstable because PWC dysfunctionning IHS SS BERNARD ATANGANA=
 is informed and confirmed // site stabilized","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site unstable=
 because PWC dysfunctionning IHS SS BERNARD ATANGANA is informed and confir=
med // site stabilized","ferot.nongni-djiogap@sagemcom.com","430","18-02-20=
25 19:40:45","Sagemcom CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004377351","Eke=
kam","","18-02-2025 19:04:00","18-02-2025 19:02:49","18-02-2025 19:10:02","=
ACTIVE// No power issue  U=3D 51.9V site on Battery(Hybrid Gen Site   start=
 threshold=3D.50 V) The  FME TX Mouamadou/658791013 //From Huawei is inform=
ed ","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No power issue  U=3D 5=
1.9V site on Battery(Hybrid Gen Site   start threshold=3D.50 V) The  FME TX=
 Mouamadou/658791013 //From Huawei is informed ","ludovic-anselme.mouliom-m=
apoure@sagemcom","72","18-02-2025 19:04:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0004377291","Mballa 4=
","","18-02-2025 19:01:03","18-02-2025 18:55:34","18-02-2025 18:59:50","Cas=
caded Incident from TTO4417597","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down because due to insuffi=
ciency of rectifiers due to load, Alphose IHS confirm // He reduced the loa=
d, site on grid","system","270271","18-02-2025 19:01:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004377287","Ngoulmek=
ong-Nord","","18-02-2025 19:01:02","18-02-2025 18:55:34","18-02-2025 18:59:=
50","Cascaded Incident from TTO4417597","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down because due to =
insufficiency of rectifiers due to load, Alphose IHS confirm // He reduced =
the load, site on grid","system","270271","18-02-2025 19:01:02","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0004377289","Ekombiti=
e","","18-02-2025 19:01:02","18-02-2025 18:55:34","18-02-2025 18:59:50","Ca=
scaded Incident from TTO4417597","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because due to insuf=
ficiency of rectifiers due to load, Alphose IHS confirm // He reduced the l=
oad, site on grid","system","270272","18-02-2025 19:01:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_275","NOCINC0004377288","Nkolbong=
","","18-02-2025 19:01:02","18-02-2025 18:55:34","18-02-2025 18:59:50","Cas=
caded Incident from TTO4417597","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down because due to insuffi=
ciency of rectifiers due to load, Alphose IHS confirm // He reduced the loa=
d, site on grid","system","270272","18-02-2025 19:01:02","Sagemcom CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0004377246","San=
ta Barbara Yde","IHS_YND_277, IHS_YND_275, IHS_YND_276, IHS_YND_242","18-02=
-2025 18:57:41","18-02-2025 18:55:34","18-02-2025 18:59:50","Site went down=
 because due to insufficiency of rectifiers due to load, Alphose IHS confir=
m // He reduced the load, site on grid","Delor Telezing","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down because due to in=
sufficiency of rectifiers due to load, Alphose IHS confirm // He reduced th=
e load, site on grid","ludovic-anselme.mouliom-mapoure@sagemcom","128","18-=
02-2025 18:57:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004376985","L=
eboudi","","18-02-2025 18:19:51","18-02-2025 18:04:40","18-02-2025 18:07:16=
","Active: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(6911=
44435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435) =
from Huawei is informed","ferot.nongni-djiogap@sagemcom.com","912","18-02-2=
025 18:19:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004376957","N=
kolafeme","","18-02-2025 18:15:33","18-02-2025 18:07:28","18-02-2025 18:10:=
25","Active: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(69=
1144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435=
) from Huawei is informed","ferot.nongni-djiogap@sagemcom.com","486","18-02=
-2025 18:15:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0004376954","N=
sam Sofavinc T0","","18-02-2025 18:14:41","18-02-2025 18:05:36","18-02-2025=
 19:23:22","Site went down due to disjunction of Cb in PWC ZTE // He reame =
Cb, site on grid","MINKA NICOLAS","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","Site went down due to disjunct=
ion of Cb in PWC ZTE // He reame Cb, site on grid","ferot.nongni-djiogap@sa=
gemcom.com","546","18-02-2025 18:14:41","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004376951","SIM=
BOCK BONAMBAPE","","18-02-2025 18:13:45","18-02-2025 18:10:27","18-02-2025 =
22:20:03","Site went down because 1/8 rectifier disfunctionning SS IHS is i=
nformed // Site stabilized","Hyemafo Gildas","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Site went down because 1/8 rectifier disfunc=
tionning SS IHS is informed // Site stabilized","ludovic-anselme.mouliom-ma=
poure@sagemcom","199","18-02-2025 18:13:45","Sagemcom CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0004376740","Ema=
na Lycee","","18-02-2025 17:35:04","18-02-2025 17:31:57","18-02-2025 18:42:=
50","No power issue, site is on grid with Ubaie=3D53V, Mbamassa /658010282/=
TELIS working on site","Fabrice Pouakam","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site i=
s on grid with Ubaie=3D53V, Mbamassa /658010282/TELIS working on site","lud=
ovic-anselme.mouliom-mapoure@sagemcom","188","18-02-2025 17:35:04","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004376678","M=
essassi 2","","18-02-2025 17:26:34","18-02-2025 17:25:24","18-02-2025 20:28=
:18","Site went down due to disfunctionning of PWC (12 kilo) , bernard IHS =
confirmed // He reset controller, site on grid","Fabrice Pouakam","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went do=
wn due to disfunctionning of PWC (12 kilo) , bernard IHS confirmed // He re=
set controller, site on grid","ferot.nongni-djiogap@sagemcom.com","71","18-=
02-2025 17:26:34","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004376289","NKO=
MEKUI OCM","","18-02-2025 16:44:31","18-02-2025 16:38:03","18-02-2025 16:40=
:34","No power issue on site U=3D54.3 V site on Gen. Site impacted by Mbank=
olo Camtel and not managed by HIS.","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site U=3D54.3 V site on Gen. Site impacted by Mbankolo Ca=
mtel and not managed by HIS.","ludovic-anselme.mouliom-mapoure@sagemcom","3=
89","18-02-2025 16:44:31","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004376253","Beh=
ind P T school Yde","","18-02-2025 16:41:21","18-02-2025 16:38:11","18-02-2=
025 18:46:41","Grid bad voltage,site went down because Gen fails to start d=
u to Landlord // Grid stabilized","Paul BIBOUM","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","Grid bad voltage,site went d=
own because Gen fails to start du to Landlord // Grid stabilized","ludovic-=
anselme.mouliom-mapoure@sagemcom","191","18-02-2025 16:41:21","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004375936","Nkolkoum=
ou OCM","","18-02-2025 15:48:25","18-02-2025 15:21:42","18-02-2025 15:49:31=
","incorrectly logged tickets","TIENTCHEU NZETCHIEU GAEL","Incorrectly Logg=
ed Tickets","Error","Error","Error","incorrectly logged tickets","system","=
1603","18-02-2025 15:48:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004374926","S=
tade-Abega","","18-02-2025 14:40:45","18-02-2025 14:35:26","18-02-2025 14:4=
0:43","No power issue on site Ubaie=3D53.7V;  site on Gen . The FME Leonel =
ADJEP/ 655184876/  Huawei is informed. ","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site Ubaie=3D53.7V;  site on Gen .The FME Leonel ADJEP/ 6551=
84876/  Huawei is informed. ","ferot.nongni-djiogap@sagemcom.com","321","18=
-02-2025 14:40:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004374915","S=
calom-IHS","","18-02-2025 14:38:32","18-02-2025 14:34:26","18-02-2025 15:33=
:24","No power issue, site on grid with U=3D52.5 V.  The TX Fme Hosiah (674=
007438) from Huawei is informed. ","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site on g=
rid with U=3D52.5 V.  The TX Fme Hosiah (674007438) from Huawei is informed=
. ","ferot.nongni-djiogap@sagemcom.com","248","18-02-2025 14:38:32","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004374673","N=
KOLMEKONG YDE","","18-02-2025 14:02:18","18-02-2025 13:53:06","18-02-2025 1=
7:07:44","Site unstable because PWC dysfunctionning IHS SS BERNARD ATANGANA=
 is informed and confirmed // Site stabilized","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site unstable=
 because PWC dysfunctionning IHS SS BERNARD ATANGANA is informed and confir=
med // Site stabilized","ludovic-anselme.mouliom-mapoure@sagemcom","553","1=
8-02-2025 14:02:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004374655","C=
rf-Nsam","","18-02-2025 13:58:21","18-02-2025 13:55:15","18-02-2025 15:05:2=
0","Site went down because PWC(24kilo) dysfunctionning, IHS SS Pascaline is=
 informed // He reduced the load, site on grid ","MINKA NICOLAS","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went dow=
n because PWC(24kilo) dysfunctionning, IHS SS Pascaline is informed // He r=
educed the load, site on grid ","ludovic-anselme.mouliom-mapoure@sagemcom",=
"187","18-02-2025 13:58:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0004374481","S=
apeur","","18-02-2025 13:25:28","18-02-2025 13:23:14","18-02-2025 13:30:39"=
,"Grid outage , Site went down before Gen start due to poor backup// Grid r=
eturn","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage , Site went down before Gen start due t=
o poor backup// Grid return","yves.djomo@sagemcom.com","136","18-02-2025 13=
:25:28","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004374119","SIM=
BOCK BONAMBAPE","","18-02-2025 12:51:46","18-02-2025 12:47:38","18-02-2025 =
13:10:28","Site went down due to (1/8) rectifiers dysfunctionning Felix Zam=
be IHS confirm // We resey this srectifier and site on grid ","Hyemafo Gild=
as","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went =
down due to (1/8) rectifiers dysfunctionning Felix Zambe IHS confirm // We =
resey this srectifier and site on grid ","ludovic-anselme.mouliom-mapoure@s=
agemcom","249","18-02-2025 12:51:46","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004374061","ETO=
UDI Entree du palais","","18-02-2025 12:37:37","18-02-2025 12:32:29","18-02=
-2025 12:38:08","Grid outage, Site went down before Gen start because  CB b=
attery tripped// Grid return (investigation ongoing)","Fabrice Pouakam","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker =
Issue","Grid outage, Site went down before Gen start because  CB battery tr=
ipped// Grid return (investigation ongoing)","ludovic-anselme.mouliom-mapou=
re@sagemcom","310","18-02-2025 12:37:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004374060","S=
calom-IHS","","18-02-2025 12:37:34","18-02-2025 12:30:24","18-02-2025 12:31=
:37","No power issue site on grid with U=3D52.3v site up AT 12:43 AM Fme Ho=
siah / 674007438// from huawei is informed","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on grid with U=3D52.3v site up AT 12:43 AM Fme Hosiah / 674007438// fro=
m huawei is informed","yves.djomo@sagemcom.com","431","18-02-2025 12:37:34"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0004373982","Sap=
eur Mimboman","","18-02-2025 12:24:07","18-02-2025 12:21:00","18-02-2025 14=
:38:00","Site down because 02/07 rectifiers Hanging causing by increase loa=
d on site//He reset rectifiers ,site on Gen","Mba Lazare Herve","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site down because 02/07 r=
ectifiers Hanging causing by increase load on site//He reset rectifiers ,si=
te on Gen","yves.djomo@sagemcom.com","188","18-02-2025 12:24:07","Sagemcom =
CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004373940","NYO=
M 2 IHS","","18-02-2025 12:17:46","18-02-2025 12:13:37","18-02-2025 12:15:3=
6","No power issue site on grid with U=3D54.8v Site up at 12:19 PM Symphori=
en(675295205) from Huawei is informed","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue site on grid with U=3D54.8v Site up et 12:19 AM Symphorien(6752952=
05) from Huawei is informed","ludovic-anselme.mouliom-mapoure@sagemcom","25=
0","18-02-2025 12:17:46","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0004373841","Mes=
sassi 2","","18-02-2025 12:02:42","18-02-2025 12:00:18","18-02-2025 12:06:0=
9","Active// No power issue on site Ubaie =3D52,7 V site on Gen. FRANK EBAN=
GO / 694829780/ from TELIS working on site (Full Swap)","Fabrice Pouakam","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active// No power issue on site Ubaie =3D52,7 V site on Gen. FRA=
NK EBANGO / 694829780/ from TELIS working on site (Full Swap)","ludovic-ans=
elme.mouliom-mapoure@sagemcom","145","18-02-2025 12:02:42","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004373829","SIM=
BOCK BONAMBAPE","","18-02-2025 11:59:14","18-02-2025 11:55:00","18-02-2025 =
12:00:32","Grid outage, Site went down before Gen start due to poor backup/=
/ Grid return","Hyemafo Gildas","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup// Grid return","ludovic-anselme.mouliom-mapoure@sagem=
com","320","18-02-2025 11:59:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004373819","E=
MANA BILICK CITY","","18-02-2025 11:59:07","16-02-2025 18:46:53","18-02-202=
5 12:40:51","Lack of Neutral on site, Site went down because Landlord forbi=
dden to start the Gen due to Noise // Eneo normalized the neutral ","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop",=
"Lack of Neutral on site, Site went down because Landlord forbidden to star=
t the Gen due to Noise // Eneo normalized the neutral ","yves.djomo@sagemco=
m.com","148336","18-02-2025 11:59:07","Sagemcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004373597","Ron=
d Point Express1114","","18-02-2025 11:26:09","18-02-2025 11:18:04","18-02-=
2025 13:09:07","No power issue on site Ubaie =3D54.5V site on Grid TX Fme H=
osiah / 674007438// from huawei is informed and up at 11:36 AM","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site Ubaie =3D54.5V site on Grid TX Fme=
 Hosiah / 674007438// from huawei is informed and up at 11:36 AM","yves.djo=
mo@sagemcom.com","486","18-02-2025 11:26:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0004373586","S=
apeur","","18-02-2025 11:21:41","18-02-2025 11:17:25","18-02-2025 11:23:02"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Grid return","Mboua Thierry","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before gen star=
t due to poor battery backup // Grid return","ludovic-anselme.mouliom-mapou=
re@sagemcom","258","18-02-2025 11:21:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004373284","B=
arriere","","18-02-2025 10:33:41","18-02-2025 10:31:19","18-02-2025 10:57:1=
1","ACTIVE//No power issue U=3D 49,6V Site on Grid The TX FME Lionnel /6551=
84876 from huawei is informed and up at 10:43 AM","Hyemafo Gildas","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue U=3D 49,6V Site on Grid The TX FME Lionnel /6551=
84876 from huawei is informed and up at 10:43 AM","ludovic-anselme.mouliom-=
mapoure@sagemcom","143","18-02-2025 10:33:41","Sagemcom CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0004373259","Ele=
veurs","","18-02-2025 10:29:42","18-02-2025 10:28:32","18-02-2025 10:30:28"=
,"No power issue site on grid with U=3D54v William(697200294) from IENGINEE=
RING is working on site from microwave link (Nkomesseng-Eleveurs) site up a=
t 11:18 AM","Siligap Boris","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54v William(697200294) from IENGINEERING is working on site from microwa=
ve link (Nkomesseng-Eleveurs) site up at 11:18 AM","ludovic-anselme.mouliom=
-mapoure@sagemcom","71","18-02-2025 10:29:42","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004373244","Nsi=
meyong Terre Rouge","","18-02-2025 10:27:28","18-02-2025 10:25:23","18-02-2=
025 10:39:26","Site went down due to PWC dysfunction, SS IHS Fran=E7ois NDO=
UNGOU is informed and confirmed// Site stabilized","MINKA NICOLAS","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went d=
own due to PWC dysfunction, SS IHS Fran=E7ois NDOUNGOU is informed and conf=
irmed// Site stabilized","yves.djomo@sagemcom.com","126","18-02-2025 10:27:=
28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004373218","N=
KOLMEKONG YDE","","18-02-2025 10:21:42","18-02-2025 10:17:38","18-02-2025 1=
3:30:55","Site went down because PWC dysfunctionning IHS SS BERNARD ATANGAN=
A is informed and confirmed// Site stabilized","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went dow=
n because PWC dysfunctionning IHS SS BERNARD ATANGANA is informed and confi=
rmed// Site stabilized","yves.djomo@sagemcom.com","245","18-02-2025 10:21:4=
2","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004373045","C=
omplexe-BEAC","","18-02-2025 09:54:56","18-02-2025 09:49:51","18-02-2025 09=
:57:53","Grid outage , Site went down before Gen start due to poor backup//=
 Grid return","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage , Site went down before Gen star=
t due to poor backup// Grid return","yves.djomo@sagemcom.com","306","18-02-=
2025 09:54:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0004373014","N=
goum","","18-02-2025 09:47:39","18-02-2025 09:33:29","18-02-2025 09:40:14",=
"Active//No Power issue on site , site on Solar with Ubaie=3D52.7V The Tx G=
regoire(654547479) from Huawei is informed and up at 09:50 AM","Parker Tcho=
up","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No Power issue on site , site on Solar with Ubaie=
=3D52.7V The Tx Gregoire(654547479) from Huawei is informed and up at 09:50=
 AM","yves.djomo@sagemcom.com","851","18-02-2025 09:47:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004372999","E=
ssomba","","18-02-2025 09:45:57","18-02-2025 09:42:52","18-02-2025 10:32:46=
","Site went down because PWC overload (12Kw, 250A) SS IHS Alphonse DEFFO c=
onfirmed// Site stabilized","Mba Lazare Herve","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Site went down because PWC over=
load (12Kw, 250A) SS IHS Alphonse DEFFO confirmed// Site stabilized","yves.=
djomo@sagemcom.com","186","18-02-2025 09:45:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0004372736","C=
NR","","18-02-2025 09:10:47","18-02-2025 09:09:40","18-02-2025 09:17:46","G=
rid outage, Site went down before Gen start due to poor backup// Gen start =
automatically","Mboua Thierry","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, Site went down before Gen star=
t due to poor backup// Gen start automatically","yves.djomo@sagemcom.com","=
68","18-02-2025 09:10:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0004372511","C=
rf-Nkolbisson","","18-02-2025 08:35:29","18-02-2025 08:29:23","18-02-2025 0=
8:35:33","Active// No power issue, site is on grid with Ubaie=3D55,4 V, Moh=
amadou(691144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue, site is on grid with Ubaie=3D55,4 V, Mohama=
dou(691144435) from Huawei is informed","ludovic-anselme.mouliom-mapoure@sa=
gemcom","367","18-02-2025 08:35:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004371731","N=
KOLMEKONG YDE","","18-02-2025 06:09:20","18-02-2025 06:03:03","18-02-2025 0=
9:57:49","Site went down because PWC dysfunctionning IHS SS BERNARD ATANGAN=
A is informed and confirmed// Site stabilized","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went dow=
n because PWC dysfunctionning IHS SS BERNARD ATANGANA is informed and confi=
rmed// Site stabilized","mariam.tchonang@sagemcom.com","378","18-02-2025 06=
:09:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0004371673","M=
beng","IHS_YND_553","18-02-2025 05:50:56","18-02-2025 05:40:36","18-02-2025=
 08:27:18","Site went down because 1/2 rectifier disfunctionning SS IHS Fel=
ix ZAMBE is informed// He reset it","Fanda Brice","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down because 1/2 rectifier di=
sfunctionning SS IHS Felix ZAMBE is informed// He reset it","mariam.tchonan=
g@sagemcom.com","621","18-02-2025 05:50:56","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004371404","Sim=
bock MTN","","18-02-2025 04:03:59","18-02-2025 03:59:29","18-02-2025 04:56:=
09","site went down because Gen failed to start due to lack of 01 phase on =
site // he did a bridge with a good phase ","Fanda Brice","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","site went down bec=
ause Gen failed to start due to lack of 01 phase on site // he did a bridge=
 with a good phase ","mariam.tchonang@sagemcom.com","271","18-02-2025 04:03=
:59","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004371401","Elo=
umdem stade","","18-02-2025 04:02:34","18-02-2025 03:38:11","18-02-2025 03:=
43:55","No power issue, site is on Grid and Ubaie=3D56.5V, The FME TX  Geor=
ges (657108549)  of huawei is informed.","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue, site is on Grid and Ubaie=3D56.5V, The FME TX  Georges (657108549) =
 of huawei is informed.","mariam.tchonang@sagemcom.com","1464","18-02-2025 =
04:02:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004371108","N=
KOLMEKONG YDE","","18-02-2025 02:52:52","18-02-2025 02:44:31","18-02-2025 0=
3:37:31","Site went down because PWC dysfunctionning IHS SS BERNARD is info=
rmed ","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Site went down because PWC dysfunctionning// site sta=
bilised","mariam.tchonang@sagemcom.com","502","18-02-2025 02:52:52","Sagemc=
om CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004370646","Acc=
acia New","","18-02-2025 01:03:42","18-02-2025 00:54:11","18-02-2025 01:04:=
09","Grid outage ,no space to deploy a mobil gen // grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,n=
o space to deploy a mobil gen // grid return","mariam.tchonang@sagemcom.com=
","573","18-02-2025 01:03:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004370583","N=
kolafeme","","18-02-2025 00:37:52","17-02-2025 22:37:19","17-02-2025 22:41:=
58","No power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435)=
 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei is=
 informed","mariam.tchonang@sagemcom.com","7234","18-02-2025 00:37:52","Sag=
emcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004370146","SOA=
 UNIVERSITY STADIUM","","17-02-2025 23:02:18","17-02-2025 22:44:06","17-02-=
2025 23:45:14","Site on gen due to grid outage, site went down because disf=
unctionning of gen card due to load // He reduced the racks of battery and =
gen manually started","Siligap Boris","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Site on gen due to grid outage, site went down b=
ecause disfunctionning of gen card due to load // He reduced the racks of b=
attery and gen manually started","wilfried.kameni@sagemcom.com","1145","17-=
02-2025 23:02:18","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004369959","SIM=
BOCK BONAMBAPE","","17-02-2025 22:25:48","17-02-2025 22:15:28","18-02-2025 =
00:29:25","Site went down due to insufficient of rectifiers, Francois IHS c=
onfirm // Site stabiliezed","Hyemafo Gildas","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Site went down due to insufficient of rectif=
iers, Francois IHS confirm // Site stabiliezed","wilfried.kameni@sagemcom.c=
om","620","17-02-2025 22:25:48","Sagemcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004369954","TSI=
NGA VILLAGE 2","","17-02-2025 22:24:59","17-02-2025 22:00:53","17-02-2025 2=
3:41:20","Grid outage,gen failed to start due to battery GE faulty//Gen man=
ually started with external battery","Delor Telezing","Equipment Repair","P=
assive","ACDG Gen","ACDG - Generator Battery","Grid outage,gen failed to st=
art due to battery GE faulty//Gen manually started with external battery","=
wilfried.kameni@sagemcom.com","1447","17-02-2025 22:24:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004369443","E=
kounou","","17-02-2025 21:19:50","17-02-2025 20:57:25","17-02-2025 22:11:06=
","Site went down because Gen failed to start due to grid bad voltage // He=
 did a bridge with a good phase, site on grid","Albran Byorel","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Site went dow=
n because Gen failed to start due to grid bad voltage // He did a bridge wi=
th a good phase, site on grid","danick.tchakouani@sagemcom.com","1346","17-=
02-2025 21:19:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004369313","N=
kolda","","17-02-2025 21:01:00","17-02-2025 20:57:52","17-02-2025 22:58:52"=
,"Site went down due to (2/5)Rectifier dysfunctionning because The Load Inc=
rease //he reset the Rectifier and Site is on Grid","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site went down due to=
 (2/5)Rectifier dysfunctionning because The Load Increase //he reset the Re=
ctifier and Site is on Grid","danick.tchakouani@sagemcom.com","189","17-02-=
2025 21:01:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004369279","C=
RH-Etoug-Ebe","","17-02-2025 20:54:57","17-02-2025 20:48:48","17-02-2025 20=
:50:52","Active: no power issue, site is on grid with Ubaie=3D53V, Mohamado=
u(691144435) from Huawei is informed. Notice that we have disjunction in OC=
M equipment","Hyemafo Gildas","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, site is o=
n grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei is informed. Noti=
ce that we have disjunction in OCM equipment","danick.tchakouani@sagemcom.c=
om","370","17-02-2025 20:54:57","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004369167","Mel=
en Ba'aba","","17-02-2025 20:34:26","17-02-2025 20:31:09","17-02-2025 20:44=
:38","Grid outage, site went down because gen start and stopped with high t=
emp alarm //  He oppened the doors and manually start the gen","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid outage, s=
ite went down because gen start and stopped with high temp alarm //  He opp=
ened the doors and manually start the gen","wilfried.kameni@sagemcom.com","=
234","17-02-2025 20:34:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004369164","N=
kolafeme","IHS_YND_309","17-02-2025 20:33:42","17-02-2025 20:11:30","17-02-=
2025 20:16:47","No power issue, site is on grid with Ubaie=3D53V, Mohamadou=
(691144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435) fro=
m Huawei is informed","wilfried.kameni@sagemcom.com","1333","17-02-2025 20:=
33:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004369064","L=
eboudi","","17-02-2025 20:19:10","17-02-2025 20:11:30","17-02-2025 20:16:47=
","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade Active",=
"Cascade Active","No power issue, site is on grid with Ubaie=3D53V, Mohamad=
ou(691144435) from Huawei is informed","danick.tchakouani@sagemcom.com","28=
0250","17-02-2025 20:19:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0004368983","B=
yemassi Carrefour","","17-02-2025 20:02:11","17-02-2025 19:59:57","17-02-20=
25 21:14:46","Grid outage site went down because Gen Started and stopped wi=
th alarm high temps // He reset the Gen card and Gen manually started","Pau=
l BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage site went down because Gen Started and stopped with alarm high t=
emps // He reset the Gen card and Gen manually started","danick.tchakouani@=
sagemcom.com","134","17-02-2025 20:02:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004368978","S=
OA UNIVERSITY STADIUM","","17-02-2025 20:00:57","17-02-2025 19:56:33","17-0=
2-2025 20:40:35","Grid outage, site went down because gen failed to start /=
/ Grid return(investigation ongoing)","Siligap Boris","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down beca=
use gen failed to start // Grid return(investigation ongoing)","danick.tcha=
kouani@sagemcom.com","265","17-02-2025 20:00:57","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004368912","NKO=
MEKUI OCM","","17-02-2025 19:50:24","17-02-2025 19:46:14","17-02-2025 21:55=
:25","No power issue on site U=3D54.5 V site on Gen.Site impacted by Mbanko=
lo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site U=3D54.5 V site on Gen.Site impacted by Mbankolo Camt=
el and not managing by IHS","wilfried.kameni@sagemcom.com","252","17-02-202=
5 19:50:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004368745","ELOUMDEM=
 CARRIERE 2","","17-02-2025 19:38:17","17-02-2025 19:23:00","17-02-2025 20:=
27:47","Cascaded Incident from TTO4407824","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down Insufficiency =
of retifier on site SS IHS Felix Zamb=E9 is informed and confirmed","system=
","283202","17-02-2025 19:38:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004368743","Eto koss=
 Yde","","17-02-2025 19:38:17","17-02-2025 19:23:00","17-02-2025 20:27:47",=
"Cascaded Incident from TTO4407824","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down Insufficiency of reti=
fier on site SS IHS Felix Zamb=E9 is informed and confirmed","system","2832=
02","17-02-2025 19:38:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004368700","Elig Edz=
oa","","17-02-2025 19:34:37","17-02-2025 19:01:16","17-02-2025 21:10:28","C=
ascaded Incident from TTO4407637 - Cascade Removed From TTO4407637","Delor =
Telezing","Cascade Outage","Active","Cascade Active","Cascade Active","ACTI=
VE No power issue U=3D57V site on grid TX FME Armand Nguetsa /691144412 fro=
m huawei is informed
","system","270071","17-02-2025 19:34:37","Sagemcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004368602","TSI=
NGA VILLAGE 2","","17-02-2025 19:26:38","17-02-2025 19:25:30","17-02-2025 2=
0:39:35","Grid outage site went down because Gen failed to start due to Gen=
 battery faulty // Gen manually started with external battery","Delor Telez=
ing","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Gr=
id outage site went down because Gen failed to start due to Gen battery fau=
lty // Gen manually started with external battery","wilfried.kameni@sagemco=
m.com","69","17-02-2025 19:26:38","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004368589","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","17-02-2025 19:25:08","17-02-2025 19:23=
:00","17-02-2025 20:27:47","Site went down Insufficiency of retifier on sit=
e SS IHS Felix Zamb=E9 is informed and confirmed","Fanda Brice","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down Insufficie=
ncy of retifier on site SS IHS Felix Zamb=E9 is informed and confirmed","wi=
lfried.kameni@sagemcom.com","130","17-02-2025 19:25:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0004368470","N=
R-Omnisport","","17-02-2025 19:16:16","17-02-2025 19:01:16","17-02-2025 19:=
10:28","","Delor Telezing","Cascade Outage","Active","Cascade Active","Casc=
ade Active","ACTIVE No power issue U=3D57V site on grid TX FME Armand Nguet=
sa /691144412 from huawei is informed
","danick.tchakouani@sagemcom.com","270072","17-02-2025 19:16:16","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0004368458","C=
arington","","17-02-2025 19:15:15","17-02-2025 19:01:16","17-02-2025 19:10:=
28","","","Cascade Outage","Active","Cascade Active","Cascade Active","ACTI=
VE No power issue U=3D57V site on grid TX FME Armand Nguetsa /691144412 fro=
m huawei is informed
","danick.tchakouani@sagemcom.com","270072","17-02-2025 19:15:15","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0004368442","N=
taba","IHS_YND_104, IHS_YND_133, IHS_YND_107, IHS_YND_504","17-02-2025 19:1=
2:29","17-02-2025 19:01:16","17-02-2025 21:10:28","ACTIVE No power issue U=
=3D57V   site on grid TX FME Armand Nguetsa /691144412 from huawei is infor=
med","Delor Telezing","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","ACTIVE No power issue U=3D57V site on gri=
d TX FME Armand Nguetsa /691144412 from huawei is informed
","danick.tchakouani@sagemcom.com","674","17-02-2025 19:12:29","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004368419","E=
lig-Edzoa","","17-02-2025 19:08:48","17-02-2025 19:01:16","17-02-2025 19:10=
:28","","","Cascade Outage","Active","Cascade Active","Cascade Active","ACT=
IVE No power issue U=3D57V site on grid TX FME Armand Nguetsa /691144412 fr=
om huawei is informed
","danick.tchakouani@sagemcom.com","270071","17-02-2025 19:08:48","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004368175","B=
arriere","","17-02-2025 18:19:09","17-02-2025 18:11:01","17-02-2025 20:56:0=
0","Site went down due to PWC overload the ss IHS Felix is informed // site=
 stabilized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Site went down due to PWC overload the ss IHS Fe=
lix is informed // site stabilized","wilfried.kameni@sagemcom.com","488","1=
7-02-2025 18:19:09","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004367674","Nsi=
meyong Terre Rouge","","17-02-2025 17:54:39","17-02-2025 17:50:30","17-02-2=
025 18:35:25","Site went down due to PWC of Huawei Disfunction, SS IHS Fran=
=E7ois is confirmed//Grid return","MINKA NICOLAS","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due to PWC of=
 Huawei Disfunction, SS IHS Fran=E7ois is confirmed//Grid return","wilfried=
.kameni@sagemcom.com","250","17-02-2025 17:54:39","Sagemcom CMR"
"Closed Complete","Site Down","T2795","IHS_YND_070","NOCINC0004367617","Efo=
ulan","","17-02-2025 17:50:52","17-02-2025 17:44:44","17-02-2025 17:50:23",=
"Grid outage, Site went down before Gen start due to poor  backup// Grid re=
turn. Power issue resolved at 05:50PM But Site remains down at OCM after re=
set  Hosiah / 674007438// from huawei is informe","MINKA NICOLAS","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, Site went down before Gen start due to poor  backup// Grid return. Pow=
er issue resolved at 05:50PM But Site remains down at OCM after reset  Hosi=
ah / 674007438// from huawei is informed","wilfried.kameni@sagemcom.com","3=
85","17-02-2025 17:50:52","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004367597","Obo=
bogo","","17-02-2025 17:49:28","17-02-2025 17:46:18","17-02-2025 17:52:30",=
"Grid outage, Site went down before Gen start due to poor backup/ // Grid p=
ower return","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup/ // Grid power return","wilfried.kameni@sagemcom.com","1=
91","17-02-2025 17:49:28","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0004367593","Fou=
da rue des g=E9n=E9raux","","17-02-2025 17:48:51","17-02-2025 17:40:38","17=
-02-2025 19:39:59","Site went down because Gen failed to start due to Grid =
bad voltage and no RCP on site //  he did a bridge with a good phase ","Del=
or Telezing","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Site went down because Gen failed to start due to Grid bad volt=
age and no RCP on site //  he did a bridge with a good phase ","wilfried.ka=
meni@sagemcom.com","494","17-02-2025 17:48:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_745","NOCINC0004367321","Okolo Ki=
lombo","","17-02-2025 17:30:00","17-02-2025 17:26:52","17-02-2025 17:31:02"=
,"Grid outage, site went down because gen fails to start due to Gen cable f=
aulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive","Infra=
structure","Armoured Cable","Grid outage, site went down because gen fails =
to start due to Gen cable faulty // Grid return","wilfried.kameni@sagemcom.=
com","189","17-02-2025 17:30:00","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004367295","Tsi=
nga village","","17-02-2025 17:25:58","17-02-2025 17:24:49","17-02-2025 20:=
30:12"," Active // No power issue UBaie =3D54,7V site on Grid The FME TX SY=
MPHORIEN (675295205) From Huawei is informed.","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
" Active // No power issue UBaie =3D54,7V site on Grid The FME TX SYMPHORIE=
N (675295205) From Huawei is informed.","wilfried.kameni@sagemcom.com","70"=
,"17-02-2025 17:25:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0004367243","Etoudi 2=
","","17-02-2025 17:17:01","17-02-2025 17:13:11","17-02-2025 17:31:10","Cas=
caded Incident from TTO4406318","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to pwc dysfunctio=
nning // He reset it and manually start the gen","system","276664","17-02-2=
025 17:17:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004367241","Abattoir=
","","17-02-2025 17:17:00","17-02-2025 17:13:11","17-02-2025 17:31:10","Cas=
caded Incident from TTO4406318","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to pwc dysfunctio=
nning // He reset it and manually start the gen","system","276664","17-02-2=
025 17:17:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004367242","ETOUDI C=
HAPELLE","","17-02-2025 17:17:00","17-02-2025 17:13:11","17-02-2025 17:31:1=
0","Cascaded Incident from TTO4406318","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to pwc dysf=
unctionning // He reset it and manually start the gen","system","276664","1=
7-02-2025 17:17:00","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004367235","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","17-02-2025 17:15:32","17-02-2=
025 17:13:11","17-02-2025 17:31:10","Site went down due to pwc dysfunctionn=
ing // He reset it and manually start the gen","Fabrice Pouakam","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went dow=
n due to pwc dysfunctionning // He reset it and manually start the gen","wi=
lfried.kameni@sagemcom.com","142","17-02-2025 17:15:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004367188","Angongo"=
,"","17-02-2025 17:10:26","17-02-2025 16:54:39","17-02-2025 17:20:23","Casc=
aded Incident from TTO4406130","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Gen only site: Site went down du to hybri=
d systeme dysfunction // He reset it and manually start the gen","system","=
270839","17-02-2025 17:10:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0004367076","E=
beba","IHS_YND_335","17-02-2025 16:59:47","17-02-2025 16:54:39","17-02-2025=
 17:20:23","Hybrid gen site: Site went down du to hybrid systeme dysfunctio=
n // He reset it and manually start the gen","Fanda Brice","Equipment Repai=
r","Passive","Hybrid","Hybrid Module","Hybrid gen site: Site went down du t=
o hybrid systeme dysfunction // He reset it and manually start the gen","da=
nick.tchakouani@sagemcom.com","309","17-02-2025 16:59:47","Sagemcom CMR"
"Closed Complete","Site Down","T0055","IHS_YND_328","NOCINC0004367050","Nsi=
malen MTN","","17-02-2025 16:54:23","17-02-2025 16:47:12","17-02-2025 17:17=
:42","Site went down because Gen started and stopped due to pear blocked// =
he he cleaned the pear and Gen manually started","Albran Byorel","Fuel Outa=
ge (Probable)","Passive","Diesel","Fuel Line Issue","Site went down because=
 Gen started and stopped due to pear blocked// he he cleaned the pear and G=
en manually started","wilfried.kameni@sagemcom.com","432","17-02-2025 16:54=
:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0004366928","N=
R-Omnisport","","17-02-2025 16:31:57","17-02-2025 16:25:51","17-02-2025 17:=
38:10","Grid outage, site went down because gen start and stopped with unde=
r frequency alarm // He cleaned fuel filter and manually start the gen","De=
lor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Under Frequen=
cy","Grid outage, site went down because gen start and stopped with under f=
requency alarm // He cleaned fuel filter and manually start the gen","wilfr=
ied.kameni@sagemcom.com","366","17-02-2025 16:31:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004366545","N=
KOLMEKONG YDE","","17-02-2025 16:02:34","17-02-2025 15:03:27","18-02-2025 0=
0:30:53","Site went down because PWC dysfunctionning// site stabilised","Fa=
brice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Site went down because PWC dysfunctionning// site stabilised","=
wilfried.kameni@sagemcom.com","3548","17-02-2025 16:02:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0004366065","Nkolbiss=
on usines des eaux 2","","17-02-2025 15:12:30","17-02-2025 15:10:28","17-02=
-2025 16:35:44","Cascaded Incident from TTO4404974","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Site we=
nt down because the Cb(3*63 A) of Gen dysjuncted due to load increased // H=
e reamed the CB","system","269402","17-02-2025 15:12:30","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0004366059","Nko=
lbisson","IHS_YND_763","17-02-2025 15:11:44","17-02-2025 15:10:28","17-02-2=
025 16:35:44","Site went down because the Cb(3*63 A) of Gen dysjuncted due =
to load increased // He reamed the CB","TIENTCHEU NZETCHIEU GAEL","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Load Breaker","Site went down becaus=
e the Cb(3*63 A) of Gen dysjuncted due to load increased // He reamed the C=
B","wilfried.kameni@sagemcom.com","77","17-02-2025 15:11:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004365976","Akak-Nko=
zoa-MTN-IHS","","17-02-2025 15:02:00","17-02-2025 14:50:32","17-02-2025 14:=
52:47","Cascaded Incident from TTO4404772","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Grid Outage, site Down due t=
o poor backup // Grid return","system","1220364","17-02-2025 15:02:00","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004365879","S=
calom-IHS","","17-02-2025 14:48:22","17-02-2025 14:43:00","17-02-2025 19:50=
:09","No power issue on site Ubaie =3D50.9V site on Grid  TX Fme Hosiah / 6=
74007438// from huawei is informed","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
baie =3D50.9V site on Grid TX Fme Hosiah / 674007438// from huawei is infor=
med
","danick.tchakouani@sagemcom.com","324","17-02-2025 14:48:22","Sagemcom CM=
R"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004365856","Nko=
lafeme","","17-02-2025 14:45:47","17-02-2025 14:42:23","17-02-2025 14:48:21=
","Grid outage, site went down due to gen gen overload(20Kva, 375A), SS IHS=
 Pascaline is informed// Grid power return","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site we=
nt down due to gen gen overload(20Kva, 375A), SS IHS Pascaline is informed/=
/ Grid power return","wilfried.kameni@sagemcom.com","205","17-02-2025 14:45=
:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_234","NOCINC0004365837","Oyomaban=
g MTN","","17-02-2025 14:42:51","17-02-2025 14:29:14","17-02-2025 14:51:51"=
,"Cascaded Incident from TTO4404556","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went=
 down before Gen start due to poor backup/ // Grid power return","system","=
264785","17-02-2025 14:42:51","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004365748","Bas=
tos Amb Coree","","17-02-2025 14:33:52","17-02-2025 14:32:43","17-02-2025 1=
5:34:05","Grid outage No space to deploy // Grid power return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No s=
pace to deploy // Grid power return","wilfried.kameni@sagemcom.com","70","1=
7-02-2025 14:33:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0004365739","BIYEMASS=
I NIKI","","17-02-2025 14:33:23","17-02-2025 14:29:14","17-02-2025 14:51:51=
","Cascaded Incident from TTO4404556","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bef=
ore Gen start due to poor backup/ // Grid power return","system","264782","=
17-02-2025 14:33:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_507","NOCINC0004365738","BIYEM AS=
SI LYCEE","","17-02-2025 14:33:23","17-02-2025 14:29:14","17-02-2025 14:51:=
51","Cascaded Incident from TTO4404556","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup/ // Grid power return","system","264784"=
,"17-02-2025 14:33:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0004365735","BONAS YD=
E","","17-02-2025 14:33:22","17-02-2025 14:29:14","17-02-2025 14:51:51","Ca=
scaded Incident from TTO4404556","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, Site went down before Gen =
start due to poor backup/ // Grid power return","system","264781","17-02-20=
25 14:33:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004365736","ODZA MIN=
KAN EDIBI ASSI","","17-02-2025 14:33:22","17-02-2025 14:29:14","17-02-2025 =
14:51:51","Cascaded Incident from TTO4404556","Albran Byorel","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went d=
own before Gen start due to poor backup/ // Grid power return","system","26=
4787","17-02-2025 14:33:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0004365737","Behind P=
 T school Yde","","17-02-2025 14:33:22","17-02-2025 14:29:14","17-02-2025 1=
4:51:51","Cascaded Incident from TTO4404556","Paul BIBOUM","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down=
 before Gen start due to poor backup/ // Grid power return","system","26478=
6","17-02-2025 14:33:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004365734","Biyemass=
i LAC","","17-02-2025 14:33:22","17-02-2025 14:29:14","17-02-2025 14:51:51"=
,"Cascaded Incident from TTO4404556","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage, Site went down before Gen start d=
ue to poor backup/ // Grid power return","system","264785","17-02-2025 14:3=
3:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0004365730","Scalom",=
"","17-02-2025 14:33:21","17-02-2025 14:29:14","17-02-2025 14:51:51","Casca=
ded Incident from TTO4404556","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, Site went down before Gen sta=
rt due to poor backup/ // Grid power return","system","264786","17-02-2025 =
14:33:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004365733","Accacia =
New","","17-02-2025 14:33:21","17-02-2025 14:29:14","17-02-2025 14:51:51","=
Cascaded Incident from TTO4404556","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage, Site went down before Gen start due=
 to poor backup/ // Grid power return","system","264783","17-02-2025 14:33:=
21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0004365731","Obili Ch=
apelle","","17-02-2025 14:33:21","17-02-2025 14:29:14","17-02-2025 14:51:51=
","Cascaded Incident from TTO4404556","Paul BIBOUM","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down before=
 Gen start due to poor backup/ // Grid power return","system","264781","17-=
02-2025 14:33:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0004365732","Ngoa Eke=
lle","","17-02-2025 14:33:21","17-02-2025 14:29:14","17-02-2025 14:51:51","=
Cascaded Incident from TTO4404556","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down before Ge=
n start due to poor backup/ // Grid power return","system","264782","17-02-=
2025 14:33:21","Sagemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0004365709","Nlo=
ng Mvolye New","IHS_YND_234, IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND=
_562, IHS_YND_546, IHS_YND_683, IHS_YND_749, IHS_YND_805, IHS_YND_507, IHS_=
YND_724","17-02-2025 14:30:22","17-02-2025 14:29:14","17-02-2025 14:51:51",=
"Grid outage, Site went down before Gen start due to poor backup/ // Grid p=
ower return","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, Site went down before Gen start du=
e to poor backup/ // Grid power return","wilfried.kameni@sagemcom.com","69"=
,"17-02-2025 14:30:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004365686","SOA VILL=
AGE","","17-02-2025 14:26:11","17-02-2025 14:24:35","17-02-2025 15:16:24","=
Cascaded Incident from TTO4404520","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation site went down bec=
ause Gen failed to start due to Grid bad voltage and no Rcp on site // He b=
ypass the Grid and Gen manually started","system","1236042","17-02-2025 14:=
26:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004365644","S=
OA TOWN","IHS_YND_323","17-02-2025 14:23:51","17-02-2025 14:22:35","17-02-2=
025 15:17:10","Grid fluctuation site went down because Gen failed to start =
due to Grid bad voltage and no Rcp on site // He bypass the Grid and Gen ma=
nually started","Siligap Boris","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Grid fluctuation site went down because Gen =
failed to start due to Grid bad voltage and no Rcp on site // He bypass the=
 Grid and Gen manually started","danick.tchakouani@sagemcom.com","77","17-0=
2-2025 14:23:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004364927","S=
calom-IHS","","17-02-2025 12:50:43","17-02-2025 12:40:37","17-02-2025 12:45=
:43","ACTIVE// No power issue on site Ubaie =3D52.3V site on Grid The TX Fm=
e Hosiah / 674007438// from huawei is informed.","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No=
 power issue on site Ubaie =3D52.3V site on Grid The TX Fme Hosiah / 674007=
438// from huawei is informed.","yves.djomo@sagemcom.com","608","17-02-2025=
 12:50:43","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004364605","AWA=
E OCM","","17-02-2025 12:09:34","17-02-2025 12:04:15","17-02-2025 12:18:28"=
,"Grid outage, Site went down before Gen start due to poor backup/ // Gen a=
utomatically started","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup/ // Gen automatically started","el-dalile@sa=
gemcom.com","440","17-02-2025 12:09:34","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004364214","CRH=
-Etoug-Ebe","","17-02-2025 11:13:08","17-02-2025 11:09:57","17-02-2025 11:2=
3:36","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"el-dalile@sagemcom.com","192","17-02-2025 11:13:08","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004364072","BAT=
A Mokolo OCM","","17-02-2025 10:54:42","17-02-2025 10:49:26","17-02-2025 11=
:08:34","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Sp=
ace to deploy a MDG//Grid Restored","el-dalile@sagemcom.com","358","17-02-2=
025 10:54:42","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004363928","Beh=
ind P T school Yde","","17-02-2025 10:27:19","17-02-2025 10:24:10","17-02-2=
025 11:29:51","Grid bad voltage, Site went down because Landlord forbidden =
to start the Gen due to Noise// Grid stabilized","Paul BIBOUM","Equipment R=
epair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid bad voltage, Site=
 went down because Landlord forbidden to start the Gen due to Noise// Grid =
stabilized","yves.djomo@sagemcom.com","189","17-02-2025 10:27:19","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004363594","Aka=
k-Nkozoa-MTN-IHS","","17-02-2025 09:58:40","17-02-2025 09:54:36","17-02-202=
5 09:57:57","Grid outage, Site went down because Gen stopped due to chargin=
g alternator disfunction SS Felix Bateu is informed// Grid return","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternat=
or","Grid outage, Site went down because Gen stopped due to charging altern=
ator disfunction SS Felix Bateu is informed// Grid return","yves.djomo@sage=
mcom.com","290","17-02-2025 09:58:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004363585","O=
lembe-Terminus","","17-02-2025 09:56:11","17-02-2025 09:54:56","17-02-2025 =
09:56:24","Grid outage, Site went down because Gen failed to start// Grid r=
eturn (investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down because G=
en failed to start// Grid return (investigation ongoing)","yves.djomo@sagem=
com.com","76","17-02-2025 09:56:11","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004362826","Nom=
ayos montee Meche","","17-02-2025 08:14:24","17-02-2025 08:13:06","17-02-20=
25 08:20:02","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On G=
rid The Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D53.5V site On Grid =
The Tx FME Fulbert(654266068) from Huawei is informed","el-dalile@sagemcom.=
com","78","17-02-2025 08:14:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004362768","E=
kombitie","","17-02-2025 08:09:15","17-02-2025 07:50:02","17-02-2025 07:55:=
52","Active// No power issue site on grid with U=3D54,5v Symphorien from Hu=
awei is informed","Fabrice Pouakam","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue sit=
e on grid with U=3D54,5v Symphorien from Huawei is informed","el-dalile@sag=
emcom.com","1154","17-02-2025 08:09:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004362607","B=
arriere","","17-02-2025 07:24:40","16-02-2025 22:20:56","16-02-2025 22:22:2=
8","ACTIVE//No power issue U=3D 53.4V Site on Grid The TX FME Lionnel /6946=
93436 from huawei is informed. Notice that we have disjunction at BTS OCM",=
"Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","ACTIVE//No power issue U=3D 53.4V Site on Grid=
 The TX FME Lionnel /694693436 from huawei is informed. Notice that we have=
 disjunction at BTS OCM","yves.djomo@sagemcom.com","32625","17-02-2025 07:2=
4:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0004362403","C=
rf Cornier","","17-02-2025 06:55:22","17-02-2025 04:23:01","17-02-2025 06:0=
6:59","Grid fluctuation, Site went down because Gen failed to start due to =
bad voltage No Rcp// He bypassed Grid and started Gen manualy","MINKA NICOL=
AS","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, Site went down because Gen failed to start due to bad =
voltage No Rcp// He bypassed Grid and started Gen manualy","wilfried.kameni=
@sagemcom.com","9143","17-02-2025 06:55:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004362053","N=
gouetou","","17-02-2025 05:25:20","17-02-2025 05:17:14","17-02-2025 05:20:5=
8","ACTIVE//No power issue site on gen with U=3D54V The Tx FME Gregoire/654=
547479/ from huawei is informed. Notice that we have a fog in Area","Parker=
 Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","ACTIVE//No power issue site on gen with U=3D54V The Tx=
 FME Gregoire/654547479/ from huawei is informed. Notice that we have a fog=
 in Area","cedric.tiani@sagemcom.com","487","17-02-2025 05:25:20","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004362011","Ngoum","=
","17-02-2025 05:05:30","17-02-2025 05:01:29","17-02-2025 05:10:32","Cascad=
ed Incident from TTO4400410","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE//  no  power issue U =3D53.6V site on=
 gen. Tx Fme Gregroire 654547479 of huawei is  informed","system","1219616"=
,"17-02-2025 05:05:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004362010","Matsari"=
,"","17-02-2025 05:05:30","17-02-2025 05:01:29","17-02-2025 05:10:32","Casc=
aded Incident from TTO4400410","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","ACTIVE//  no  power issue U =3D53.6V site =
on gen. Tx Fme Gregroire 654547479 of huawei is  informed","system","121961=
7","17-02-2025 05:05:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004362012","Yoko MTN=
","","17-02-2025 05:05:30","17-02-2025 05:01:29","17-02-2025 05:10:32","Cas=
caded Incident from TTO4400410","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE//  no  power issue U =3D53.6V site=
 on gen. Tx Fme Gregroire 654547479 of huawei is  informed","system","12196=
15","17-02-2025 05:05:30","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004362009","MBI=
MBIM","IHS_YND_460, IHS_YND_475, IHS_YND_473","17-02-2025 05:04:42","17-02-=
2025 05:01:29","17-02-2025 06:25:32","ACTIVE//  no  power issue U =3D53.6V =
site on gen. Tx Fme Gregroire 654547479 of huawei is  informed","Parker Tch=
oup","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","ACTIVE//  no  power issue U =3D53.6V site on gen. Tx Fme G=
regroire 654547479 of huawei is  informed","cedric.tiani@sagemcom.com","194=
","17-02-2025 05:04:42","Sagemcom CMR"
"Closed Complete","Site Down","T0395","IHS_YND_065","NOCINC0004361971","Ess=
os DCS","","17-02-2025 04:49:34","17-02-2025 04:48:03","17-02-2025 04:55:10=
","Active// No power issue, Site on Grid Ubai 50,8 V Technicians working on=
 site. The Tx FME Armand Nguetsa/691144412 From HUAWEI is informed","Delor =
Telezing","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active// No power issue, Site on Grid Ubai 50,8 V Tec=
hnicians working on site. The Tx FME Armand Nguetsa/691144412 From HUAWEI i=
s informed","cedric.tiani@sagemcom.com","91","17-02-2025 04:49:34","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_513","NOCINC0004361890","Maison-B=
lanche-IHS","","17-02-2025 03:53:42","17-02-2025 03:38:34","17-02-2025 03:4=
2:26","Cascaded Incident from TTO4400239","","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE// No  power issue on site, site on Gr=
id with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is =
informed. impacted by Nkolzie","system","267805","17-02-2025 03:53:42","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_258","NOCINC0004361888","Mefou-As=
si","","17-02-2025 03:53:42","17-02-2025 03:38:34","17-02-2025 03:42:26","C=
ascaded Incident from TTO4400239","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE// No  power issue on site, site on=
 Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI =
is informed. impacted by Nkolzie","system","267806","17-02-2025 03:53:42","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004361889","Biyemass=
i LAC","","17-02-2025 03:53:42","17-02-2025 03:38:34","17-02-2025 03:42:26"=
,"Cascaded Incident from TTO4400239","","Cascade Outage","Active","Cascade =
Active","Cascade Active","ACTIVE// No  power issue on site, site on Grid wi=
th Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is infor=
med. impacted by Nkolzie","system","267807","17-02-2025 03:53:42","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004361891","Barriere=
 IHS","","17-02-2025 03:53:42","17-02-2025 03:38:34","17-02-2025 03:42:26",=
"Cascaded Incident from TTO4400239","Hyemafo Gildas","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","ACTIVE// No  power issue on site, si=
te on Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HU=
AWEI is informed. impacted by Nkolzie","system","267806","17-02-2025 03:53:=
42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0004361886","Montee-J=
ouvence","","17-02-2025 03:53:41","17-02-2025 03:38:34","17-02-2025 03:42:2=
6","Cascaded Incident from TTO4400239","Hyemafo Gildas","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","ACTIVE// No  power issue on site,=
 site on Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from=
 HUAWEI is informed. impacted by Nkolzie","system","267809","17-02-2025 03:=
53:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0004361884","MEFOU AS=
SI","","17-02-2025 03:53:41","17-02-2025 03:38:34","17-02-2025 03:42:26","C=
ascaded Incident from TTO4400239","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE// No  power issue on site, site on=
 Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI =
is informed. impacted by Nkolzie","system","267810","17-02-2025 03:53:41","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_264","NOCINC0004361887","Simbock =
OCM","","17-02-2025 03:53:41","17-02-2025 03:38:34","17-02-2025 03:42:26","=
Cascaded Incident from TTO4400239","Hyemafo Gildas","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","ACTIVE// No  power issue on site, sit=
e on Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUA=
WEI is informed. impacted by Nkolzie","system","267808","17-02-2025 03:53:4=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_238","NOCINC0004361885","Mendong"=
,"","17-02-2025 03:53:41","17-02-2025 03:38:34","17-02-2025 03:42:26","Casc=
aded Incident from TTO4400239","Hyemafo Gildas","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE// No  power issue on site, site on=
 Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI =
is informed. impacted by Nkolzie","system","267804","17-02-2025 03:53:41","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_152","NOCINC0004361882","Rd-Pt-Ex=
press","","17-02-2025 03:53:41","17-02-2025 03:38:34","17-02-2025 03:42:26"=
,"Cascaded Incident from TTO4400239","","Cascade Outage","Active","Cascade =
Active","Cascade Active","ACTIVE// No  power issue on site, site on Grid wi=
th Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is infor=
med. impacted by Nkolzie","system","267805","17-02-2025 03:53:41","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_150","NOCINC0004361883","Nkol-Mba=
nda","","17-02-2025 03:53:41","17-02-2025 03:38:34","17-02-2025 03:42:26","=
Cascaded Incident from TTO4400239","MINKA NICOLAS","Cascade Outage","Active=
","Cascade Active","Cascade Active","ACTIVE// No  power issue on site, site=
 on Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAW=
EI is informed. impacted by Nkolzie","system","267808","17-02-2025 03:53:41=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_229","NOCINC0004361880","CRH-Etou=
g-Ebe","","17-02-2025 03:53:40","17-02-2025 03:38:34","17-02-2025 03:42:26"=
,"Cascaded Incident from TTO4400239","Hyemafo Gildas","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","ACTIVE// No  power issue on site, s=
ite on Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from H=
UAWEI is informed. impacted by Nkolzie","system","267809","17-02-2025 03:53=
:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_148","NOCINC0004361881","Chapelle=
-Nsimeyong","","17-02-2025 03:53:40","17-02-2025 03:38:34","17-02-2025 03:4=
2:26","Cascaded Incident from TTO4400239","MINKA NICOLAS","Cascade Outage",=
"Active","Cascade Active","Cascade Active","ACTIVE// No  power issue on sit=
e, site on Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   fr=
om HUAWEI is informed. impacted by Nkolzie","system","267806","17-02-2025 0=
3:53:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004361879","Accacia =
New","","17-02-2025 03:53:40","17-02-2025 03:38:34","17-02-2025 03:42:26","=
Cascaded Incident from TTO4400239","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","ACTIVE// No  power issue on site, site on Grid with=
 Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informe=
d. impacted by Nkolzie","system","267804","17-02-2025 03:53:40","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004361859","M=
ontee-Jouvence-II","IHS_YND_562, IHS_YND_229, IHS_YND_148, IHS_YND_152, IHS=
_YND_150, IHS_YND_537, IHS_YND_238, IHS_YND_236, IHS_YND_264, IHS_YND_258, =
IHS_YND_546, IHS_YND_513, IHS_YND_696","17-02-2025 03:43:51","17-02-2025 03=
:38:34","17-02-2025 03:42:26","ACTIVE// No  power issue on site, site on Gr=
id with Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is =
informed. impacted by Nkolzie","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No  po=
wer issue on site, site on Grid with Ubaie=3D 54V The Tx Fme  Mbah Hosiah /=
/674007438/   from HUAWEI is informed. impacted by Nkolzie","cedric.tiani@s=
agemcom.com","318","17-02-2025 03:43:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004361797","C=
RF Nkoabang","","17-02-2025 03:18:06","17-02-2025 03:15:59","17-02-2025 05:=
47:19","Grid outage No space to deploy // Grid power return","Mba Lazare He=
rve","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage No space to deploy // Grid power return","wilfried.kameni@sagemco=
m.com","128","17-02-2025 03:18:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004361787","D=
amas","","17-02-2025 03:12:37","17-02-2025 03:10:23","17-02-2025 03:15:46",=
"ACTIVE//No power issue u=3D56V site on GRID,The Tx FME Hosiah//699699694 i=
s informed ","MINKA NICOLAS","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue u=3D56V sit=
e on GRID,The Tx FME Hosiah//699699694 is informed ","wilfried.kameni@sagem=
com.com","135","17-02-2025 03:12:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0004361741","M=
ontee-Jouvence","","17-02-2025 03:02:14","17-02-2025 02:52:46","17-02-2025 =
02:57:07","ACTIVE//No power issue u=3D54.2V site on GRID,The Tx FME Hosiah/=
/699699694 is informed ","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issu=
e u=3D54.2V site on GRID,The Tx FME Hosiah//699699694 is informed ","wilfri=
ed.kameni@sagemcom.com","569","17-02-2025 03:02:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004361674","M=
ontee-Jouvence-II","","17-02-2025 02:25:43","17-02-2025 02:08:07","17-02-20=
25 02:09:45","No power issue on the site. Bay:54.1V, site on Grid","Hyemafo=
 Gildas","Incorrectly Logged Tickets","Error","Error","Error","incorrectly =
logged tickets","wilfried.kameni@sagemcom.com","1057","17-02-2025 02:25:43"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_281","NOCINC0004361275","Odza II"=
,"","17-02-2025 00:15:22","16-02-2025 23:43:33","16-02-2025 23:45:13","Casc=
aded Incident from TTO4399432","Albran Byorel","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue, site is on grid with Ubaie=
=3D53V, site up at  00:01 AM, Lionel Steeve(655184876) from Huawei is infor=
med","system","267631","17-02-2025 00:15:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004361274","Odza Min=
kan IHS","","17-02-2025 00:15:22","16-02-2025 23:43:33","16-02-2025 23:45:1=
3","Cascaded Incident from TTO4399432","Albran Byorel","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue, site is on grid wi=
th Ubaie=3D53V, site up at  00:01 AM, Lionel Steeve(655184876) from Huawei =
is informed","system","267629","17-02-2025 00:15:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004361276","ODZA MIN=
KAN EDIBI ASSI","","17-02-2025 00:15:22","16-02-2025 23:43:33","16-02-2025 =
23:45:13","Cascaded Incident from TTO4399432","Albran Byorel","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","No power issue, site is on =
grid with Ubaie=3D53V, site up at  00:01 AM, Lionel Steeve(655184876) from =
Huawei is informed","system","267629","17-02-2025 00:15:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0004361270","Mbedoumo=
u - Ekali","","17-02-2025 00:15:21","16-02-2025 23:43:33","16-02-2025 23:45=
:13","Cascaded Incident from TTO4399432","Albran Byorel","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue, site is on grid =
with Ubaie=3D53V, site up at  00:01 AM, Lionel Steeve(655184876) from Huawe=
i is informed","system","267630","17-02-2025 00:15:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004361271","MEHANDAN=
","","17-02-2025 00:15:21","16-02-2025 23:43:33","16-02-2025 23:45:13","Cas=
caded Incident from TTO4399432","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue, site is on grid with Ubai=
e=3D53V, site up at  00:01 AM, Lionel Steeve(655184876) from Huawei is info=
rmed","system","267632","17-02-2025 00:15:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0004361272","Mehanda =
1","","17-02-2025 00:15:21","16-02-2025 23:43:33","16-02-2025 23:45:13","Ca=
scaded Incident from TTO4399432","Albran Byorel","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue, site is on grid with Uba=
ie=3D53V, site up at  00:01 AM, Lionel Steeve(655184876) from Huawei is inf=
ormed","system","267631","17-02-2025 00:15:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_524","NOCINC0004361273","ODZA BOR=
NE 10","","17-02-2025 00:15:21","16-02-2025 23:43:33","16-02-2025 23:45:13"=
,"Cascaded Incident from TTO4399432","Albran Byorel","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue, site is on grid with=
 Ubaie=3D53V, site up at  00:01 AM, Lionel Steeve(655184876) from Huawei is=
 informed","system","267630","17-02-2025 00:15:21","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004361135","Nko=
lnda","IHS_YND_343, IHS_YND_528, IHS_YND_746, IHS_YND_524, IHS_YND_715, IHS=
_YND_281, IHS_YND_749","17-02-2025 00:02:35","16-02-2025 23:43:33","16-02-2=
025 23:45:13","No power issue, site is on grid with Ubaie=3D53V, site up at=
  00:01 AM, Lionel Steeve(655184876) from Huawei is informed","Albran Byore=
l","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue, site is on grid with Ubaie=3D53V, site up at=
  00:01 AM, Lionel Steeve(655184876) from Huawei is informed","wilfried.kam=
eni@sagemcom.com","1142","17-02-2025 00:02:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004361048","N=
gouetou","","16-02-2025 23:50:15","16-02-2025 23:36:02","16-02-2025 23:40:0=
2","Active//No power issue site on gen with U=3D54v Gregoire/652070658/ fro=
m Huawei is informed","Parker Tchoup","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue si=
te on gen with U=3D54v Gregoire/652070658/ from Huawei is informed","wilfri=
ed.kameni@sagemcom.com","854","16-02-2025 23:50:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_058","NOCINC0004361039","Mvolye",=
"","16-02-2025 23:46:00","16-02-2025 23:28:32","16-02-2025 23:30:30","Casca=
ded Incident from TTO4399324","MINKA NICOLAS","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue, site is on grid with Ubaie=
=3D53V, site impacted by Lycee Leclerci is no down, site up at 11:36 PM","s=
ystem","268297","16-02-2025 23:46:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_018","NOCINC0004361038","P&T Buil=
ding","","16-02-2025 23:46:00","16-02-2025 23:28:32","16-02-2025 23:30:30",=
"Cascaded Incident from TTO4399324","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue, site is on grid with Ubaie=3D53V, =
site impacted by Lycee Leclerci is no down, site up at 11:36 PM","system","=
268296","16-02-2025 23:46:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0004361040","Acropole=
","","16-02-2025 23:46:00","16-02-2025 23:28:32","16-02-2025 23:30:30","Cas=
caded Incident from TTO4399324","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue, site is on grid with Ubai=
e=3D53V, site impacted by Lycee Leclerci is no down, site up at 11:36 PM","=
system","268296","16-02-2025 23:46:00","Sagemcom CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0004361035","Eto=
ug-Ebe 2","IHS_YND_018, IHS_YND_058, IHS_YND_036","16-02-2025 23:44:54","16=
-02-2025 23:28:32","16-02-2025 23:30:30","No power issue, site is on grid w=
ith Ubaie=3D53V, site impacted by Lycee Leclerci is no down, site up at 11:=
36 PM","","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue, site is on grid with Ubaie=3D53V, sit=
e impacted by Lycee Leclerci is no down, site up at 11:36 PM","wilfried.kam=
eni@sagemcom.com","983","16-02-2025 23:44:54","Sagemcom CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0004360928","Kon=
dengui MTN","","16-02-2025 23:19:11","16-02-2025 23:16:01","17-02-2025 00:3=
2:08","Grid outage, Site went because Gen ran until fuel shortage//Refuelin=
g Done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage, Site went because Gen ran until fuel shortage//Refueling Done",=
"wilfried.kameni@sagemcom.com","191","16-02-2025 23:19:11","Sagemcom CMR"
"Closed Complete","Site Down","T1085","IHS_YND_130","NOCINC0004360891","Bas=
tos usine","","16-02-2025 23:12:11","16-02-2025 23:09:43","16-02-2025 23:12=
:39","Active// No power issue U=3D54.4V site on Grid The FME TX eloudou (69=
3212405) From Huawei is informed.","Mboua Thierry","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No =
power issue U=3D54.4V site on Grid The FME TX eloudou (693212405) From Huaw=
ei is informed.","wilfried.kameni@sagemcom.com","148","16-02-2025 23:12:11"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004360867","Mes=
sa Carriere","","16-02-2025 23:10:27","16-02-2025 23:07:54","16-02-2025 23:=
11:26","ACTIVE//No power issue, site is on Grid with Ubaie=3D54.5V Mohamado=
u/691144435 of huawei is informed","Mboua Thierry","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No p=
ower issue, site is on Grid with Ubaie=3D54.5V Mohamadou/691144435 of huawe=
i is informed","wilfried.kameni@sagemcom.com","154","16-02-2025 23:10:27","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004360178","E=
lig-Edzoa","","16-02-2025 21:20:12","16-02-2025 21:11:06","16-02-2025 21:16=
:56","ACTIVE// No Power issue on site ,site on Grid with Ubaie=3D54,4 VThe =
Tx FME Armand Nguetsa // 699949553// From  Huawei is informed Notice that t=
he DC cable in the BTS OCM was burnt","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No Power issu=
e on site ,site on Grid with Ubaie=3D54,4 VThe Tx FME Armand Nguetsa // 699=
949553// From  Huawei is informed Notice that the DC cable in the BTS OCM w=
as burnt","wilfried.kameni@sagemcom.com","547","16-02-2025 21:20:12","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004360166","Mimboman=
4","","16-02-2025 21:19:20","16-02-2025 21:14:26","16-02-2025 21:20:38","Ca=
scaded Incident from TTO4398318","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause Gen failed to start due to bad voltage//Site stabilised","system","2=
76608","16-02-2025 21:19:20","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004360163","Nko=
lo II New","IHS_YND_266","16-02-2025 21:18:48","16-02-2025 21:14:26","16-02=
-2025 22:15:04","Grid fluctuation, site went down because Gen failed to sta=
rt due to bad voltage//Site stabilised","Mba Lazare Herve","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,=
 site went down because Gen failed to start due to bad voltage//Site stabil=
ised","wilfried.kameni@sagemcom.com","263","16-02-2025 21:18:48","Sagemcom =
CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004360065","SIM=
BOCK BONAMBAPE","","16-02-2025 21:04:15","16-02-2025 20:55:40","16-02-2025 =
22:46:03","Grid outage, Site went down before Gen start due to poor backup/=
/ Gen started manually","Hyemafo Gildas","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Gen started manually","wilfried.kameni@sag=
emcom.com","516","16-02-2025 21:04:15","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004360060","Nsi=
meyong Terre Rouge","","16-02-2025 21:02:05","16-02-2025 20:57:53","16-02-2=
025 23:38:54","Site went down due to PWC of huawei dysfunction, ss ihs Fran=
=E7ois is informed and confirmed//Grid return","MINKA NICOLAS","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Site went down =
due to PWC of huawei dysfunction, ss ihs Fran=E7ois is informed and confirm=
ed//Grid return","wilfried.kameni@sagemcom.com","253","16-02-2025 21:02:05"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004360054","Leboudi"=
,"","16-02-2025 21:01:41","16-02-2025 20:49:57","16-02-2025 21:50:29","Casc=
aded Incident from TTO4398154","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","Active: no power issue, site is=
 on grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei is informed, No=
tice that cable burned in BTS OCM","system","270872","16-02-2025 21:01:41",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004360048","MEHANDAN=
","","16-02-2025 21:00:50","16-02-2025 19:52:34","16-02-2025 20:05:00","Cas=
caded Incident from TTO4398176","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","no  power issue U =3D54.8V site on grid. =
no power issue U=3D54,8V site on Grid. TX FME Leonel Steve (655184876) from=
 Huawei is informed by sms. Notice that we have disjunction in OCM equipm",=
"system","267033","16-02-2025 21:00:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0004360047","Odza II =
OCM","","16-02-2025 21:00:50","16-02-2025 19:52:34","16-02-2025 20:05:00","=
Cascaded Incident from TTO4398176","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","no  power issue U =3D54.8V site on gri=
d. no power issue U=3D54,8V site on Grid. TX FME Leonel Steve (655184876) f=
rom Huawei is informed by sms. Notice that we have disjunction in OCM equip=
m","system","267034","16-02-2025 21:00:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0004360042","O=
dza-PK10","IHS_YND_527, IHS_YND_528","16-02-2025 20:59:52","16-02-2025 19:5=
2:34","16-02-2025 20:05:00","no  power issue U =3D54.8V site on grid.  no p=
ower issue U=3D54,8V site on Grid.TX FME Leonel Steve (655184876) from Huaw=
ei is informed by sms. Notice that we have disjunction in OCM equipment","A=
lbran Byorel","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","no  power issue U =3D54.8V site on grid. no power=
 issue U=3D54,8V site on Grid. TX FME Leonel Steve (655184876) from Huawei =
is informed by sms. Notice that we have disjunction in OCM equipm","wilfrie=
d.kameni@sagemcom.com","4039","16-02-2025 20:59:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004360025","N=
kolafeme","IHS_YND_309","16-02-2025 20:56:05","16-02-2025 20:49:57","16-02-=
2025 21:50:29","Active: no power issue, site is on grid with Ubaie=3D53V, M=
ohamadou(691144435) from Huawei is informed,Notice that disjunction in BTS =
Ocm","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, site is=
 on grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei is informed, No=
tice that cable burned in BTS OCM","wilfried.kameni@sagemcom.com","368","16=
-02-2025 20:56:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004359928","N=
kolda","","16-02-2025 20:43:44","16-02-2025 20:35:39","16-02-2025 20:43:20"=
,"Site went down due to (2/5)Rectifier dysfunctionning because The Load Inc=
rease //he reset the Rectifier and Site is on Grid","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site went down due to=
 (2/5)Rectifier dysfunctionning because The Load Increase //he reset the Re=
ctifier and Site is on Grid","wilfried.kameni@sagemcom.com","486","16-02-20=
25 20:43:44","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004359868","UPA=
C LP","","16-02-2025 20:33:42","16-02-2025 20:28:35","16-02-2025 21:08:27",=
"Grid outage  No space ton deploy // Grid power return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage  No space t=
on deploy // Grid power return","wilfried.kameni@sagemcom.com","308","16-02=
-2025 20:33:42","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004359863","AWA=
E OCM","","16-02-2025 20:32:46","16-02-2025 20:26:35","16-02-2025 20:34:29"=
,"Grid outage, site went down becfore gen start due to poor battery backup =
// Grid power return","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down becfo=
re gen start due to poor battery backup // Grid power return","wilfried.kam=
eni@sagemcom.com","372","16-02-2025 20:32:46","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004359672","ODZ=
A CITE MBIA","","16-02-2025 20:06:11","16-02-2025 20:01:23","16-02-2025 20:=
02:51","Active//power issue U =3D54.8V site on Grid. No power issue U=3D54,=
8V site on Grid.TX FME Leonel Steve (655184876) from Huawei is informed and=
 Site Up at=3D08:49 PM","Albran Byorel","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active//power issue U =
=3D54.8V site on Grid. No power issue U=3D54,8V site on Grid.TX FME Leonel =
Steve (655184876) from Huawei is informed and Site Up at=3D08:49 PM","wilfr=
ied.kameni@sagemcom.com","289","16-02-2025 20:06:11","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004359655","Mon=
tee-Jouvence-II","","16-02-2025 20:02:50","16-02-2025 19:58:37","16-02-2025=
 23:22:59","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix Za=
mb=E9 confirmed//Grid return","Hyemafo Gildas","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Site went down due to PWC Overl=
oaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed//Grid return","wilfried.kam=
eni@sagemcom.com","297","16-02-2025 20:02:50","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004359581","Bar=
riere","","16-02-2025 19:51:50","16-02-2025 19:30:39","16-02-2025 19:52:16"=
,"Site went down due to PWC overload the ss IHS Felix is informed // site s=
tabilized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Recti=
fier Module Overloaded","Site went down due to PWC overload the ss IHS Feli=
x is informed // site stabilized","wilfried.kameni@sagemcom.com","1337","16=
-02-2025 19:51:50","Sagemcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004359541","Tam=
tam Weekend","","16-02-2025 19:45:51","16-02-2025 19:37:28","16-02-2025 22:=
15:54","Site went down due to disjunction of 63A CB in PWC that feed MTN du=
e to charge increase //he did a bridge with another 63A","Hyemafo Gildas","=
Equipment Repair","Passive","Rectifier","Rectifier - Circuit Breaker","Site=
 went down due to disjunction of 63A CB in PWC that feed MTN due to charge =
increase //he did a bridge with another 63A","wilfried.kameni@sagemcom.com"=
,"504","16-02-2025 19:45:51","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004359487","Mes=
sa Carriere","","16-02-2025 19:38:14","16-02-2025 19:34:05","16-02-2025 20:=
37:28","Site went down because Gen failed to started due to Grid bad voltag=
e and no RCP on site // He bypass the Grid and Gen manually started","Mboua=
 Thierry","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Site went down because Gen failed to started due to Grid bad volta=
ge and no RCP on site // He bypass the Grid and Gen manually started","wilf=
ried.kameni@sagemcom.com","250","16-02-2025 19:38:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004359479","E=
ssomba","","16-02-2025 19:36:20","16-02-2025 19:30:28","16-02-2025 21:45:16=
","	Site went down because 02/05rectifiers dysfunctionned// He reset rectif=
iers,site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","	Site went down because 02/05rectifiers dysfunction=
ned// He reset rectifiers,site on Grid","mariam.tchonang@sagemcom.com","354=
","16-02-2025 19:36:20","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004359282","NKO=
MEKUI OCM","","16-02-2025 19:12:05","16-02-2025 19:07:55","16-02-2025 21:55=
:34","no power issue on site U=3D54.3 V site on Gen. Site impacted by Mbank=
olo Camtel and not managed by HIS","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","n=
o power issue on site U=3D54.3 V site on Gen.Site impacted by Mbankolo Camt=
el and not managed by HIS","wilfried.kameni@sagemcom.com","251","16-02-2025=
 19:12:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004359185","SOA VILL=
AGE","","16-02-2025 18:57:10","16-02-2025 18:43:31","16-02-2025 19:09:19","=
Cascaded Incident from TTO4397163","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen started and  stopped with alarm under voltage (unpruvent) // He reset t=
he Gen card and Gen manually started","system","271005","16-02-2025 18:57:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004359173","SOA=
 TOWN","IHS_YND_323","16-02-2025 18:55:50","16-02-2025 18:43:31","16-02-202=
5 19:09:19","Grid outage site went down because Gen started and  stopped wi=
th alarm under voltage (unpruvent) // He reset the Gen card and Gen manuall=
y started","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid outage site went down because Gen started and  stopped=
 with alarm under voltage (unpruvent) // He reset the Gen card and Gen manu=
ally started","wilfried.kameni@sagemcom.com","740","16-02-2025 18:55:50","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0004359160","Behind P=
 T school Yde","","16-02-2025 18:53:41","16-02-2025 18:39:04","16-02-2025 1=
8:49:47","Cascaded Incident from TTO4397083","Paul BIBOUM","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down=
 before Gen start due to poor backup/ // Grid power return","system","26449=
1","16-02-2025 18:53:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0004359138","BIYEMASS=
I NIKI","","16-02-2025 18:48:51","16-02-2025 18:39:04","16-02-2025 18:49:47=
","Cascaded Incident from TTO4397083","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bef=
ore Gen start due to poor backup/ // Grid power return","system","264493","=
16-02-2025 18:48:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0004359136","BONAS YD=
E","","16-02-2025 18:48:51","16-02-2025 18:39:04","16-02-2025 18:49:47","Ca=
scaded Incident from TTO4397083","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, Site went down before Gen =
start due to poor backup/ // Grid power return","system","264491","16-02-20=
25 18:48:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004359134","Accacia =
New","","16-02-2025 18:48:51","16-02-2025 18:39:04","16-02-2025 18:49:47","=
Cascaded Incident from TTO4397083","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage, Site went down before Gen start due=
 to poor backup/ // Grid power return","system","264492","16-02-2025 18:48:=
51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_507","NOCINC0004359137","BIYEM AS=
SI LYCEE","","16-02-2025 18:48:51","16-02-2025 18:39:04","16-02-2025 18:49:=
47","Cascaded Incident from TTO4397083","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
efore Gen start due to poor backup/ // Grid power return","system","264490"=
,"16-02-2025 18:48:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0004359135","Biyemass=
i LAC","","16-02-2025 18:48:51","16-02-2025 18:39:04","16-02-2025 18:49:47"=
,"Cascaded Incident from TTO4397083","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage, Site went down before Gen start d=
ue to poor backup/ // Grid power return","system","264492","16-02-2025 18:4=
8:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0004359132","Obili Ch=
apelle","","16-02-2025 18:48:50","16-02-2025 18:39:04","16-02-2025 18:49:47=
","Cascaded Incident from TTO4397083","Paul BIBOUM","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down before=
 Gen start due to poor backup/ // Grid power return","system","264490","16-=
02-2025 18:48:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0004359133","Ngoa Eke=
lle","","16-02-2025 18:48:50","16-02-2025 18:39:04","16-02-2025 18:49:47","=
Cascaded Incident from TTO4397083","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down before Ge=
n start due to poor backup/ // Grid power return","system","264491","16-02-=
2025 18:48:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0004359131","Scalom",=
"","16-02-2025 18:48:50","16-02-2025 18:39:04","16-02-2025 18:49:47","Casca=
ded Incident from TTO4397083","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, Site went down before Gen sta=
rt due to poor backup/ // Grid power return","system","264490","16-02-2025 =
18:48:50","Sagemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0004359101","Nlo=
ng Mvolye New","IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND_562, IHS_YND=
_546, IHS_YND_683, IHS_YND_805, IHS_YND_507, IHS_YND_724","16-02-2025 18:44=
:15","16-02-2025 18:39:04","16-02-2025 18:49:47","Grid outage, Site went do=
wn before Gen start due to poor backup/ // Grid power return","Paul BIBOUM"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"Grid outage, Site went down before Gen start due to poor backup/ // Grid =
power return","wilfried.kameni@sagemcom.com","311","16-02-2025 18:44:15","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004359042","Akak-Nko=
zoa-MTN-IHS","","16-02-2025 18:36:30","16-02-2025 18:08:57","16-02-2025 18:=
12:45","Cascaded Incident from TTO4396804","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage , Site down b=
efore Gen Start due to poor battery backup //  Gen start automatically","sy=
stem","265955","16-02-2025 18:36:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004358704","M=
EHANDAN","","16-02-2025 17:49:17","16-02-2025 17:42:10","16-02-2025 19:38:0=
1","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Site went down because the rectifier dysfonction on site due to =
load increased // He reset the rectifier ","wilfried.kameni@sagemcom.com","=
274868","16-02-2025 17:49:17","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004358695","ODZ=
A MINKAN EDIBI ASSI","","16-02-2025 17:47:25","16-02-2025 17:44:18","16-02-=
2025 18:26:14","Site went down because gen failed tos tart due to grid bad =
voltgae and no RCP // Gen manually started","Albran Byorel","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Site went down b=
ecause gen failed tos tart due to grid bad voltgae and no RCP // Gen manual=
ly started","wilfried.kameni@sagemcom.com","188","16-02-2025 17:47:25","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004358682","O=
dza II OCM","","16-02-2025 17:45:29","16-02-2025 17:42:10","16-02-2025 19:3=
8:01","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Site went down because the rectifier dysfonction on site due =
to load increased // He reset the rectifier ","wilfried.kameni@sagemcom.com=
","274868","16-02-2025 17:45:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0004358676","O=
dza-PK10","IHS_YND_527, IHS_YND_528","16-02-2025 17:44:15","16-02-2025 17:4=
2:10","16-02-2025 19:38:01","Site went down because the rectifier dysfoncti=
on on site due to load increased // He reset the rectifier ","Albran Byorel=
","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went do=
wn because the rectifier dysfonction on site due to load increased // He re=
set the rectifier ","wilfried.kameni@sagemcom.com","126","16-02-2025 17:44:=
15","Sagemcom CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0004358665","Eto=
udi 2","","16-02-2025 17:41:26","16-02-2025 17:31:09","16-02-2025 20:34:13"=
,"Grid outage site went down because Gen started and Stopped with alarm und=
er voltage // He reset the Gen card and Gen manually started","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage site went down because Gen started and Stopped with alarm under volta=
ge // He reset the Gen card and Gen manually started","wilfried.kameni@sage=
mcom.com","926","16-02-2025 17:41:26","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004358658","Nko=
ulou Carriere carrefourt","","16-02-2025 17:40:01","16-02-2025 17:32:52","1=
6-02-2025 20:24:56","Grid outage, site went down because gen fails to start=
 due to card gen faulty // Gen manually started","Mba Lazare Herve","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site =
went down because gen fails to start due to card gen faulty // Gen manually=
 started","wilfried.kameni@sagemcom.com","430","16-02-2025 17:40:01","Sagem=
com CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004358652","Nsi=
meyong Terre Rouge","","16-02-2025 17:37:56","16-02-2025 17:17:43","16-02-2=
025 20:05:56","Site went down due to PWC of Huawei Disfunction, SS IHS Fran=
=E7ois is confirmed //Site Stabilized","MINKA NICOLAS","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Site went down due to P=
WC of Huawei Disfunction, SS IHS Fran=E7ois is confirmed //Site Stabilized"=
,"wilfried.kameni@sagemcom.com","1214","16-02-2025 17:37:56","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004358415","Mom=
","","16-02-2025 16:58:26","16-02-2025 16:40:19","16-02-2025 16:45:53","No =
Power issue on site ,site on Grid with Ubaie=3D53.3 V The Tx  FME Salomon 6=
94452220 from I-Eng work on site","Fanda Brice","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No Power issue =
on site ,site on Grid with Ubaie=3D53.3 V The Tx  FME Salomon 694452220 fro=
m I-Eng work on site","wilfried.kameni@sagemcom.com","1088","16-02-2025 16:=
58:26","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004358280","Awa=
e Ewonkan","","16-02-2025 16:42:57","16-02-2025 16:38:30","16-02-2025 18:39=
:00","Site went down due to insufficiency rectifiers (06 rectfiers) due to =
load increase on site IHS SS Alphonse is informed // site stabilized","Albr=
an Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","Sit=
e went down due to insufficiency rectifiers (06 rectfiers) due to load incr=
ease on site IHS SS Alphonse is informed // site stabilized","wilfried.kame=
ni@sagemcom.com","290","16-02-2025 16:42:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004358221","A=
WAE OCM","","16-02-2025 16:33:01","16-02-2025 16:31:35","16-02-2025 16:42:0=
3","Grid outage, Site went down before Gen start due to poor backup// Grid =
power return","Mba Lazare Herve","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup// Grid power return","mariam.tchonang@sagemcom.com",=
"88","16-02-2025 16:33:01","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004358087","Beh=
ind P T school Yde","","16-02-2025 16:23:22","16-02-2025 16:13:15","16-02-2=
025 16:51:34","Grid outage , Site went down because Gen Ran till fuel short=
age//Refueling done","Paul BIBOUM","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage , Site went down because Gen Ran till fuel shortage//=
Refueling done","wilfried.kameni@sagemcom.com","608","16-02-2025 16:23:22",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004357924","Eto koss=
 Yde","","16-02-2025 16:08:50","16-02-2025 15:51:23","16-02-2025 16:25:12",=
"Cascaded Incident from TTO4395724","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work(SS Daniel=
 fomekong(656072361)/Sagemcom, working on site(injection pump faulty replac=
ed ongoing))// End of work","system","274437","16-02-2025 16:08:50","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004357925","ELOUMDEM=
 CARRIERE 2","","16-02-2025 16:08:50","16-02-2025 15:51:23","16-02-2025 16:=
25:12","Cascaded Incident from TTO4395724","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work(SS=
 Daniel fomekong(656072361)/Sagemcom, working on site(injection pump faulty=
 replaced ongoing))// End of work","system","274437","16-02-2025 16:08:50",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004357913","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","16-02-2025 16:07:36","16-02-2025 15:50=
:23","16-02-2025 16:25:29","	Site went down due to work(SS Daniel fomekong(=
656072361)/Sagemcom, working on site(injection pump faulty replaced ongoing=
))// End of work","Fanda Brice","Installation Activity","Passive","Planned =
Activity","Installation Activity","Site went down due to work(SS Daniel fom=
ekong(656072361)/Sagemcom, working on site(injection pump faulty replaced o=
ngoing))// End of work","wilfried.kameni@sagemcom.com","1054","16-02-2025 1=
6:07:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004357848","M=
essassi 2","","16-02-2025 15:57:38","16-02-2025 15:54:20","16-02-2025 16:39=
:54","Site went down due to (2/5)Rectifier dysfunctionning because The Load=
 Increase //he reset the Rectifier and Site is on Grid","Fabrice Pouakam","=
Equipment Repair","Passive","Rectifier","Rectifier Module","Site went down =
due to (2/5)Rectifier dysfunctionning because The Load Increase //he reset =
the Rectifier and Site is on Grid","mariam.tchonang@sagemcom.com","200","16=
-02-2025 15:57:38","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004357717","AKA=
K Nkozoa","","16-02-2025 15:36:56","16-02-2025 15:31:46","16-02-2025 15:41:=
12","Grid outage, site went down bacuse gen failed to start  // Gen manuall=
y started ( Investigation and going)","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down ba=
cuse gen failed to start  // Gen manually started ( Investigation and going=
)","wilfried.kameni@sagemcom.com","311","16-02-2025 15:36:56","Sagemcom CMR=
"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004357424","Beh=
ind P T school Yde","","16-02-2025 14:59:51","16-02-2025 14:55:45","16-02-2=
025 15:59:48","Grid bad voltage site went down because gen ran untill fuel =
shortage // he did a bridge with a good phase (refueling ongoing)","Paul BI=
BOUM","Fuel Outage","Passive","Diesel","Diesel Outage","Grid bad voltage si=
te went down because gen ran untill fuel shortage // he did a bridge with a=
 good phase (refueling ongoing)","wilfried.kameni@sagemcom.com","247","16-0=
2-2025 14:59:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004357352","M=
ontee-Jouvence-II","","16-02-2025 14:52:46","16-02-2025 14:49:08","16-02-20=
25 15:34:48","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed//Site stabilized","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Site went down due to PWC=
 Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed//Site stabilized","ma=
riam.tchonang@sagemcom.com","219","16-02-2025 14:52:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004357351","C=
RH-Etoug-Ebe","","16-02-2025 14:52:36","16-02-2025 14:46:26","16-02-2025 14=
:51:00","Active: no power issue, site is on grid with Ubaie=3D53V, Mohamado=
u(691144435) from Huawei is informed. Notice that we have disjunction in OC=
M equipment","Hyemafo Gildas","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, site is o=
n grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei is informed. Noti=
ce that we have disjunction in OCM equipment","wilfried.kameni@sagemcom.com=
","371","16-02-2025 14:52:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004356984","B=
arriere","","16-02-2025 14:10:29","16-02-2025 14:03:15","16-02-2025 14:10:2=
0","No power issue U=3D 51.9V Site on Grid   The TX FME Lionnel /694693436 =
from huawei is informed.Notice that we have disjunction in OCM equipment","=
Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","No power issue U=3D 51.9V Site on Grid The TX F=
ME Lionnel /694693436 from huawei is informed.Notice that we have disjuncti=
on in OCM equipment
","danick.tchakouani@sagemcom.com","435","16-02-2025 14:10:29","Sagemcom CM=
R"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004356619","Nsi=
meyong Terre Rouge","","16-02-2025 13:44:14","16-02-2025 13:35:50","16-02-2=
025 15:02:44","Site went down due to PWC of Huawei  Disfunction, SS IHS Fra=
n=E7ois is confirmed //Site Stabilized","MINKA NICOLAS","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Site went down due to =
PWC of Huawei  Disfunction, SS IHS Fran=E7ois is confirmed //Site Stabilize=
d","wilfried.kameni@sagemcom.com","505","16-02-2025 13:44:14","Sagemcom CMR=
"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004356467","Bas=
tos Amb Coree","","16-02-2025 13:23:54","16-02-2025 13:20:44","16-02-2025 1=
3:30:07","No power issue on site Ubaie =3D50 V site on Grid The TX FME Elou=
ndou/693212405  from huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite Ubaie =3D50 V site on Grid The TX FME Eloundou/693212405  from huawei i=
s informed","wilfried.kameni@sagemcom.com","192","16-02-2025 13:23:54","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004356422","MONTEE N=
KONDENGUI","","16-02-2025 13:12:18","16-02-2025 13:05:05","16-02-2025 13:10=
:48","Cascaded Incident from TTO4393973","Albran Byorel","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site , site on=
 Grid  with Ubaie=3D54.2 V.The Tx FME  Eloundou  //693212405 of Huawei is i=
nformed
","system","291652","16-02-2025 13:12:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004356417","M=
obil-Kondengui","IHS_YND_682","16-02-2025 13:11:24","16-02-2025 13:05:05","=
16-02-2025 13:10:48","No power issue on site , site on Grid  with Ubaie=3D5=
4.2 V. The Tx FME  Eloundou  //693212405 of Huawei is informed","","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site , site on Grid  with Ubaie=3D54.2 V.The Tx FME  =
Eloundou  //693212405 of Huawei is informed
","danick.tchakouani@sagemcom.com","380","16-02-2025 13:11:24","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004356410","N=
kolbong","","16-02-2025 13:10:31","16-02-2025 13:04:24","16-02-2025 13:58:3=
2","Grid outage, Site went down before Gen start due to poor backup// Gen s=
tarted automatically Power reset has done to rescue the site","Delor Telezi=
ng","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery L=
ow","Grid outage, Site went down before Gen start due to poor backup// Gen =
started automatically Power reset has done to rescue the site","danick.tcha=
kouani@sagemcom.com","368","16-02-2025 13:10:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0004356361","N=
kolso","","16-02-2025 13:04:08","16-02-2025 12:59:48","16-02-2025 13:05:08"=
,"Active// No power issue, site is on Grid with Ubaie=3D54,3V, Mohamadou(69=
1144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue, site is on Grid with Ubaie=3D54,3V, Mohamadou(691144=
435) from Huawei is informed","danick.tchakouani@sagemcom.com","261","16-02=
-2025 13:04:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004355532","S=
OA UNIVERSITY STADIUM","","16-02-2025 11:26:17","16-02-2025 11:24:05","16-0=
2-2025 11:34:46","Grid outage, site went down because gen failed to start d=
ue to Pwc ZTE dysfunction// He reset it and started Gen manualy","Siligap B=
oris","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, site went down because gen failed to start due to Pwc ZTE d=
ysfunction// He reset it and started Gen manualy","danick.tchakouani@sagemc=
om.com","313","16-02-2025 11:26:17","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0004355454","Mom=
","","16-02-2025 11:13:19","16-02-2025 10:58:54","16-02-2025 11:00:41","No =
power issue on site ,site on Grid with Ubaie=3D 53.5 V The fme tx Etienne f=
opa // 695033981 of huawei is informed and Site on Grid","Fanda Brice","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue on site ,site on Grid with Ubaie=3D 53.5 V The fme t=
x Etienne fopa // 695033981 of huawei is informed and Site on Grid","wilfri=
ed.kameni@sagemcom.com","866","16-02-2025 11:13:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004355435","MEHANDAN=
","","16-02-2025 11:09:40","16-02-2025 11:04:39","16-02-2025 11:54:39","Cas=
caded Incident from TTO4392868","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to hybrid system dy=
sfunctionning // He reset and Gen started manaully","system","270081","16-0=
2-2025 11:09:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004355432","O=
dza II OCM","IHS_YND_528","16-02-2025 11:08:49","16-02-2025 11:04:39","16-0=
2-2025 11:54:39","Site went down due to hybrid system dysfunctionning // He=
 reset and Gen started manaully","Albran Byorel","Equipment Repair","Passiv=
e","Hybrid","Hybrid Module","Site went down due to hybrid system dysfunctio=
nning // He reset and Gen started manaully","danick.tchakouani@sagemcom.com=
","252","16-02-2025 11:08:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004355363","ELOUMDEM=
 CARRIERE 2","","16-02-2025 10:59:31","16-02-2025 10:44:19","16-02-2025 11:=
17:58","Cascaded Incident from TTO4392572","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work(SS=
 Daniel fomekong(656072361)/Sagemcom, working on site)// End of work","syst=
em","285708","16-02-2025 10:59:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004355362","Eto koss=
 Yde","","16-02-2025 10:59:30","16-02-2025 10:44:19","16-02-2025 11:17:58",=
"Cascaded Incident from TTO4392572","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work(SS Daniel=
 fomekong(656072361)/Sagemcom, working on site)// End of work","system","28=
5708","16-02-2025 10:59:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004355168","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","16-02-2025 10:38:50","16-02-2025 10:35=
:19","16-02-2025 14:13:21","Site went down due to work(SS Daniel fomekong(6=
56072361)/Sagemcom, working on site)// End of work","Fanda Brice","Installa=
tion Activity","Passive","Planned Activity","Installation Activity","Site w=
ent down due to work(SS Daniel fomekong(656072361)/Sagemcom, working on sit=
e)// End of work","wilfried.kameni@sagemcom.com","212","16-02-2025 10:38:50=
","Sagemcom CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0004355019","Mae=
tur","","16-02-2025 10:16:15","16-02-2025 10:12:09","16-02-2025 10:38:48","=
Grid outage,Gen failed to start due to  Gen CB 32A disjuncted//he reamed th=
e CB","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Load =
Breaker","Grid outage,Gen failed to start due to  Gen CB 32A disjuncted//he=
 reamed the CB","danick.tchakouani@sagemcom.com","247","16-02-2025 10:16:15=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004354914","C=
RH-Etoug-Ebe","","16-02-2025 09:58:55","16-02-2025 09:54:46","16-02-2025 10=
:08:46","Grid outage, Site went down before Gen start due to poor backup/ /=
/ Gen automatically started","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup/ // Gen automatically started","danick.=
tchakouani@sagemcom.com","250","16-02-2025 09:58:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004354900","Dong",""=
,"16-02-2025 09:55:11","16-02-2025 09:03:59","16-02-2025 09:42:13","Cascade=
d Incident from TTO4391990","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Site impacted by CTR_032 batchenga, No power =
issue, Ubaie: 55V site on Battery. ","system","270006","16-02-2025 09:55:11=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004354899","Donga","=
","16-02-2025 09:55:10","16-02-2025 09:03:59","16-02-2025 09:42:13","Cascad=
ed Incident from TTO4391990","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by CTR_032 batchenga, No power=
 issue, Ubaie: 55V site on Battery. ","system","270010","16-02-2025 09:55:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0004354898","Nguila",=
"","16-02-2025 09:55:10","16-02-2025 09:03:59","16-02-2025 09:42:13","Casca=
ded Incident from TTO4391990","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Site impacted by CTR_032 batchenga, No powe=
r issue, Ubaie: 55V site on Battery. ","system","270009","16-02-2025 09:55:=
10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_424","NOCINC0004354897","Ossombe"=
,"","16-02-2025 09:55:10","16-02-2025 09:03:59","16-02-2025 09:42:13","Casc=
aded Incident from TTO4391990","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by CTR_032 batchenga, No pow=
er issue, Ubaie: 55V site on Battery. ","system","270007","16-02-2025 09:55=
:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004354824","E=
ssomba","","16-02-2025 09:47:40","16-02-2025 09:39:34","16-02-2025 11:40:34=
","Site went down because all rectifiers dysfunctionned// He reset rectifie=
rs,site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down because all rectifiers dysfunctionned/=
/ He reset rectifiers,site on Grid","danick.tchakouani@sagemcom.com","487",=
"16-02-2025 09:47:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0004354694","N=
kolndongo","","16-02-2025 09:23:08","16-02-2025 09:21:55","16-02-2025 09:32=
:55","Grid outage,gen failed to start due to CB 63A alimented the ATS disju=
ncted//he reamed the CB","MINKA NICOLAS","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Grid outage,gen failed =
to start due to CB 63A alimented the ATS disjuncted//he reamed the CB","dan=
ick.tchakouani@sagemcom.com","74","16-02-2025 09:23:08","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004354532","AWA=
E OCM","","16-02-2025 08:53:41","16-02-2025 08:49:17","16-02-2025 08:58:35"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen start automatically","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen start automatically","wi=
lfried.kameni@sagemcom.com","304","16-02-2025 08:53:41","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004354527","Ema=
na","","16-02-2025 08:52:13","16-02-2025 08:50:06","16-02-2025 09:00:25","	=
Grid outage, site went down before gen fails to start due to poor battery b=
ackup // Gen started automatically","Fabrice Pouakam","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","	Grid outage, site w=
ent down before gen fails to start due to poor battery backup // Gen starte=
d automatically","wilfried.kameni@sagemcom.com","128","16-02-2025 08:52:13"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004354397","OBA=
M NGOLA OCM","","16-02-2025 08:24:16","16-02-2025 08:21:54","16-02-2025 08:=
39:24","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Site went down due to PSC3 dysfonction SS IHS Pascal=
ine confirmed// Site stabilized","wilfried.kameni@sagemcom.com","143","16-0=
2-2025 08:24:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0004354122","E=
mombo","","16-02-2025 07:33:14","16-02-2025 07:24:45","16-02-2025 07:31:45"=
,"","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid outage, Site went down before Gen start due to poor backup=
/ // Gen automatically started","danick.tchakouani@sagemcom.com","283098","=
16-02-2025 07:33:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004354080","M=
imboman-Ecole","IHS_YND_178","16-02-2025 07:25:54","16-02-2025 07:24:45","1=
6-02-2025 07:31:45","Grid outage, Site went down before Gen start due to po=
or backup/ // Gen automatically started","Mba Lazare Herve","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, S=
ite went down before Gen start due to poor backup/ // Gen automatically sta=
rted","danick.tchakouani@sagemcom.com","70","16-02-2025 07:25:54","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004354076","Sim=
bock MTN","IHS_YND_793","16-02-2025 07:24:54","16-02-2025 07:03:45","16-02-=
2025 07:47:32","Grid outage ,Site went down because Gen stopped with alarm =
high temp//he open all the door and started the gen","Fanda Brice","Equipme=
nt Repair","Passive","ACDG Gen","Gen Temp High","Grid outage ,Site went dow=
n because Gen stopped with alarm high temp//he open all the door and starte=
d the gen","wilfried.kameni@sagemcom.com","1270","16-02-2025 07:24:54","Sag=
emcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004354056","Elo=
umdem stade","","16-02-2025 07:18:30","16-02-2025 07:03:45","16-02-2025 07:=
47:32","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage ,Site went down because Gen stopped with alarm hig=
h temp//he open all the door and started the gen","danick.tchakouani@sagemc=
om.com","277248","16-02-2025 07:18:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004353982","N=
KOLMEKONG YDE","","16-02-2025 06:59:53","16-02-2025 06:55:47","16-02-2025 0=
9:41:00","Site went down because PWC dysfunctionning IHS SS BERNARD is info=
rmed // reset done, site on gen","Fabrice Pouakam","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Site went down because PWC =
dysfunctionning IHS SS BERNARD is informed // reset done, site on gen","dan=
ick.tchakouani@sagemcom.com","247","16-02-2025 06:59:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0004353893","MONTEE N=
KONDENGUI","","16-02-2025 06:30:20","16-02-2025 06:00:24","16-02-2025 06:57=
:24","Cascaded Incident from TTO4391146","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage // Grid return","=
system","288203","16-02-2025 06:30:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004353891","M=
obil-Kondengui","IHS_YND_682","16-02-2025 06:29:43","16-02-2025 06:00:24","=
16-02-2025 06:57:24","Grid outage // Grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage // Grid return","=
danick.tchakouani@sagemcom.com","1760","16-02-2025 06:29:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004353372","L=
eboudi","","16-02-2025 02:35:54","15-02-2025 21:04:34","15-02-2025 21:05:39=
","No power issue site and with Ubaie=3D54.4 V site on Gen The FME TX Mouam=
adou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue site and with Ubaie=3D54.4 V site on Gen The FME TX Mo=
uamadou/658791013 //From Huawei is informed","wilfried.kameni@sagemcom.com"=
,"19881","16-02-2025 02:35:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004353082","N=
KOLMEKONG YDE","","16-02-2025 00:45:26","16-02-2025 00:37:17","16-02-2025 0=
0:53:22","Site went down because PWC dysfunctionning// site stabilised","Fa=
brice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Site went down because PWC dysfunctionning// site stabilised","=
wilfried.kameni@sagemcom.com","490","16-02-2025 00:45:26","Sagemcom CMR"
"Closed Complete","Site Down","T1577","IHS_YND_086","NOCINC0004353004","POL=
YCLINIQUE TSINGA","","16-02-2025 00:19:39","16-02-2025 00:15:33","16-02-202=
5 00:20:33","No power issus site on grid with U=3D53.9v Eloundou Bertand(65=
2586578) from Huawei ","Mboua Thierry","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issus site on g=
rid with U=3D53.9v Eloundou Bertand(652586578) from Huawei ","ludivine.ngam=
aleu@ihstowers.com","247","16-02-2025 00:19:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_131","NOCINC0004352983","Laborato=
ire  Meka","","16-02-2025 00:16:21","15-02-2025 23:51:58","15-02-2025 23:55=
:58","Cascaded Incident from TTO4390017","","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue site on grid wth U=3D54v site =
up at 12:00 PM Mohamadou( from Huawei is informed","system","288590","16-02=
-2025 00:16:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004352981","Bastos B=
ir","","16-02-2025 00:16:21","15-02-2025 23:51:58","15-02-2025 23:55:58","C=
ascaded Incident from TTO4390017","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid wth U=3D54v=
 site up at 12:00 PM Mohamadou( from Huawei is informed","system","288592",=
"16-02-2025 00:16:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_514","NOCINC0004352982","Etoudi2"=
,"","16-02-2025 00:16:21","15-02-2025 23:51:58","15-02-2025 23:55:58","Casc=
aded Incident from TTO4390017","Delor Telezing","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on grid wth U=3D54v s=
ite up at 12:00 PM Mohamadou( from Huawei is informed","system","288591","1=
6-02-2025 00:16:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_229","NOCINC0004352979","CRH-Etou=
g-Ebe","","16-02-2025 00:16:20","15-02-2025 23:51:58","15-02-2025 23:55:58"=
,"Cascaded Incident from TTO4390017","Hyemafo Gildas","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue site on grid wth U=
=3D54v site up at 12:00 PM Mohamadou( from Huawei is informed","system","28=
8591","16-02-2025 00:16:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0004352980","Bastos E=
koudou","","16-02-2025 00:16:20","15-02-2025 23:51:58","15-02-2025 23:55:58=
","Cascaded Incident from TTO4390017","Mboua Thierry","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue site on grid wth U=
=3D54v site up at 12:00 PM Mohamadou( from Huawei is informed","system","28=
8592","16-02-2025 00:16:20","Sagemcom CMR"
"Closed Complete","Site Down","T0209","IHS_YND_197","NOCINC0004352896","Pal=
ais Des Congres","IHS_YND_229, IHS_YND_193, IHS_YND_704, IHS_YND_514, IHS_Y=
ND_131","16-02-2025 00:05:23","15-02-2025 23:51:58","15-02-2025 23:55:58","=
No power issue site on grid wth U=3D54v site up at 12:00 PM Eloundou(652586=
578) from Huawei is informed","Mboua Thierry","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on grid wth U=3D54v site up at 12:00 PM Mohamadou( from Huawei is inform=
ed","ludivine.ngamaleu@ihstowers.com","806","16-02-2025 00:05:23","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0467","IHS_YND_077","NOCINC0004352714","Obi=
li Carrefour","","15-02-2025 23:38:37","15-02-2025 23:31:22","16-02-2025 01=
:29:25","No power issu site on grid with U=3D49.4v Mbah Osiah from Huawei i=
s informed site up at 11:36 PM","Paul BIBOUM","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu sit=
e on grid with U=3D49.4v Mbah Osiah from Huawei is informed site up at 11:3=
6 PM","wilfried.kameni@sagemcom.com","436","15-02-2025 23:38:37","Sagemcom =
CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004352705","NKO=
LOSSAN OKOK","","15-02-2025 23:36:47","15-02-2025 23:33:35","15-02-2025 23:=
35:21","No power issue site on grid with U=3D54v  Gregoire from Huawei is i=
nformed","Parker Tchoup","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D5=
4v  Gregoire from Huawei is informed","wilfried.kameni@sagemcom.com","193",=
"15-02-2025 23:36:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_322","NOCINC0004352416","Soa-II",=
"","15-02-2025 22:30:33","15-02-2025 20:12:12","15-02-2025 20:38:25","Casca=
ded Incident from TTO4389222","Siligap Boris","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
failed to start due to gen overload(20KVA, 270A) // He reconfigured gen car=
d, site on gen","system","280212","15-02-2025 22:30:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004352415","SOA UNIV=
ERSITY STADIUM","","15-02-2025 22:30:33","15-02-2025 20:12:12","15-02-2025 =
20:38:25","Cascaded Incident from TTO4389222","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage, site went d=
own because gen failed to start due to gen overload(20KVA, 270A) // He reco=
nfigured gen card, site on gen","system","280211","15-02-2025 22:30:33","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004352414","Akak-Nko=
zoa-MTN-IHS","","15-02-2025 22:30:33","15-02-2025 20:12:12","15-02-2025 20:=
38:25","Cascaded Incident from TTO4389222","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site went do=
wn because gen failed to start due to gen overload(20KVA, 270A) // He recon=
figured gen card, site on gen","system","280212","15-02-2025 22:30:33","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004352413","Ebogo","=
","15-02-2025 22:30:33","15-02-2025 20:12:12","15-02-2025 20:38:25","Cascad=
ed Incident from TTO4389222","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen f=
ailed to start due to gen overload(20KVA, 270A) // He reconfigured gen card=
, site on gen","system","280211","15-02-2025 22:30:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004352417","SOA TOWN=
","","15-02-2025 22:30:33","15-02-2025 20:12:12","15-02-2025 20:38:25","Cas=
caded Incident from TTO4389222","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to gen overload(20KVA, 270A) // He reconfigured gen c=
ard, site on gen","system","280211","15-02-2025 22:30:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_321","NOCINC0004352411","Soa","",=
"15-02-2025 22:30:32","15-02-2025 20:12:12","15-02-2025 20:38:25","Cascaded=
 Incident from TTO4389222","Siligap Boris","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen fai=
led to start due to gen overload(20KVA, 270A) // He reconfigured gen card, =
site on gen","system","280212","15-02-2025 22:30:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_317","NOCINC0004352412","Soa-Sofa=
mac","","15-02-2025 22:30:32","15-02-2025 20:12:12","15-02-2025 20:38:25","=
Cascaded Incident from TTO4389222","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen failed to start due to gen overload(20KVA, 270A) // He reconfigured ge=
n card, site on gen","system","280213","15-02-2025 22:30:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004352397","N=
kolafeme","","15-02-2025 22:26:27","15-02-2025 21:07:51","15-02-2025 21:11:=
34","No power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435)=
 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei is=
 informed","mariam.tchonang@sagemcom.com","4716","15-02-2025 22:26:27","Sag=
emcom CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0004352375","Ele=
veurs","","15-02-2025 22:21:07","15-02-2025 20:40:38","15-02-2025 20:45:07"=
," ACTIVE// No power issue site on grid with U=3D54.4 V  The Tx FME Synphor=
ien//691316854 from Huawei is informed.","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," ACTIV=
E// No power issue site on grid with U=3D54.4 V  The Tx FME Synphorien//691=
316854 from Huawei is informed.","wilfried.kameni@sagemcom.com","6030","15-=
02-2025 22:21:07","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004352349","Nsi=
meyong Terre Rouge","","15-02-2025 22:13:04","15-02-2025 21:53:52","15-02-2=
025 22:11:07","Site went down due to PWC of Huawei  Disfunction, SS IHS Fra=
n=E7ois is confirmed//Site Stabilized","MINKA NICOLAS","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Site went down due to P=
WC of Huawei  Disfunction, SS IHS Fran=E7ois is confirmed//Site Stabilized"=
,"wilfried.kameni@sagemcom.com","1153","15-02-2025 22:13:04","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004352287","Sim=
bock MTN","","15-02-2025 22:01:42","15-02-2025 20:42:09","15-02-2025 22:00:=
15","Grid outage, site went down because gen start and stopped with high te=
mp alarm // he added water and manually start the gen","Fanda Brice","Equip=
ment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level =
Issue","Grid outage, site went down because gen start and stopped with high=
 temp alarm // he added water and manually start the gen","mariam.tchonang@=
sagemcom.com","4774","15-02-2025 22:01:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0004352283","E=
mana Lycee","","15-02-2025 22:00:05","15-02-2025 21:04:57","15-02-2025 21:0=
4:58","No power issue on site Ubaie=3D54.2V, site on Gen //The TX Fme Synph=
orien 691316854 of Huewai is informed","Fabrice Pouakam","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site Ubaie=3D54.2V, site on Gen //The TX Fme Synphorien 6913168=
54 of Huewai is informed","mariam.tchonang@sagemcom.com","3309","15-02-2025=
 22:00:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004352273","E=
mana lycee 2","","15-02-2025 21:57:39","15-02-2025 21:04:42","15-02-2025 21=
:05:38","No power isssue site on grid with U=3D54v Symphorien from Huawei i=
s informed","Fabrice Pouakam","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power isssue site on grid with=
 U=3D54v Symphorien from Huawei is informed","mariam.tchonang@sagemcom.com"=
,"3178","15-02-2025 21:57:39","Sagemcom CMR"
"Closed Complete","Site Down","T0712","IHS_YND_319","NOCINC0004352216","SOA=
 2","IHS_YND_321, IHS_YND_317, IHS_YND_307, IHS_YND_316, IHS_YND_720, IHS_Y=
ND_322, IHS_YND_320","15-02-2025 21:49:25","15-02-2025 20:12:12","15-02-202=
5 20:38:25","Grid outage, site went down because gen failed to start due to=
 gen overload(20KVA, 270A) // He reconfigured gen card, site on gen","Silig=
ap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage, site went down because gen failed to start due to gen overload(20KVA=
, 270A) // He reconfigured gen card, site on gen","wilfried.kameni@sagemcom=
.com","5900","15-02-2025 21:49:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004352116","M=
essassi 2","","15-02-2025 21:33:47","15-02-2025 21:14:15","15-02-2025 22:03=
:15","Grid outage, site went down because gen failed to start due to Grid c=
ontactor no excited // He excited Grid contactor and Site is on Grid","Fabr=
ice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","=
Grid outage, site went down because gen failed to start due to Grid contact=
or no excited // He excited Grid contactor and Site is on Grid","mariam.tch=
onang@sagemcom.com","1173","15-02-2025 21:33:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004352059","D=
ong","","15-02-2025 21:26:10","15-02-2025 20:59:55","15-02-2025 21:04:01","=
Active: No power issue, site on battery With Ubaie=3D50.5V, The Tx FME Greg=
oire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue, site on battery With Ubaie=3D50.5V, The Tx FME Gregoire =
(654547479) from Huawei is informed","mariam.tchonang@sagemcom.com","1576",=
"15-02-2025 21:26:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0004351954","Nkolbiss=
on usines des eaux 2","","15-02-2025 21:11:32","15-02-2025 20:55:21","15-02=
-2025 20:55:22","Cascaded Incident from TTO4388920","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Active","Cascade Active","Cascade Active","Active: no=
 power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435) from H=
uawei is informed. Notice that we have disjunction in OCM equipment","syste=
m","306326","15-02-2025 21:11:32","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0004351950","Nko=
lbisson","IHS_YND_763","15-02-2025 21:09:40","15-02-2025 20:55:21","16-02-2=
025 08:10:22","Active: no power issue, site is on grid with Ubaie=3D53V, Mo=
hamadou(691144435) from Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active: no power issue, site is on grid with Ubaie=3D53V, Mohamado=
u(691144435) from Huawei is informed.","wilfried.kameni@sagemcom.com","860"=
,"15-02-2025 21:09:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0004351843","C-Suprem=
e","","15-02-2025 21:02:20","15-02-2025 20:41:06","15-02-2025 20:45:18","Ca=
scaded Incident from TTO4388696","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","Active: no power issue, site is on grid with Ubaie=3D=
53V, site impacted by MVog ada new(This site is not managed by ihs)","syste=
m","285637","15-02-2025 21:02:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0004351842","Acropole=
","","15-02-2025 21:02:20","15-02-2025 20:41:06","15-02-2025 20:45:18","Cas=
caded Incident from TTO4388696","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active: no power issue, site is on grid w=
ith Ubaie=3D53V, site impacted by MVog ada new(This site is not managed by =
ihs)","system","285637","15-02-2025 21:02:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004351762","M=
ontee-Jouvence-II","","15-02-2025 20:57:44","15-02-2025 20:55:33","15-02-20=
25 21:00:43","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed//Site stabilized","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Site went down due to PWC=
 Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed//Site stabilized","ma=
riam.tchonang@sagemcom.com","132","15-02-2025 20:57:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0004351738","N=
kolndongo","IHS_YND_036, IHS_YND_021","15-02-2025 20:53:19","15-02-2025 20:=
41:06","15-02-2025 20:45:18","Active: no power issue, site is on grid with =
Ubaie=3D53V, site impacted by MVog ada new(This site is not managed by ihs)=
","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active: no power issue, site is on grid with =
Ubaie=3D53V, site impacted by MVog ada new(This site is not managed by ihs)=
","wilfried.kameni@sagemcom.com","734","15-02-2025 20:53:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004351325","B=
arriere","","15-02-2025 20:12:26","15-02-2025 19:36:18","15-02-2025 22:57:2=
1","Grid fluctuation,Site went down because gen failed to start due to grid=
 bad voltages //He bypass grid and Gen manually started","Hyemafo Gildas","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation,Site went down because gen failed to start due to grid bad v=
oltages //He bypass grid and Gen manually started","wilfried.kameni@sagemco=
m.com","2169","15-02-2025 20:12:26","Sagemcom CMR"
"Cancelled","Warning","CTR_234","IHS_YND_415","NOCINC0004351259","Boga-Maho=
le","","15-02-2025 20:03:22","","","incorrectly logged ticket","Kemeni Fran=
klin","","","","","","wilfried.kameni@sagemcom.com","1628","15-02-2025 20:0=
3:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0004351094","E=
foulan","","15-02-2025 19:43:35","15-02-2025 19:26:22","15-02-2025 19:51:29=
","Grid outage, Site went because Gen ran until fuel shortage//Refueling Do=
ne","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel Outage","Grid =
outage, Site went because Gen ran until fuel shortage//Refueling Done","wil=
fried.kameni@sagemcom.com","1034","15-02-2025 19:43:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004351063","C=
rf-Nsam","","15-02-2025 19:37:57","15-02-2025 19:20:52","15-02-2025 19:51:5=
2","Site went down Because The Slot of Rectifier is overload //site stabili=
zed SS Ihs Pascaline is informed and is confirmed","MINKA NICOLAS","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","Site went down Because=
 The Slot of Rectifier is overload //site stabilized SS Ihs Pascaline is in=
formed and is confirmed","wilfried.kameni@sagemcom.com","1026","15-02-2025 =
19:37:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004351042","Akak-Nko=
zoa-MTN-IHS","","15-02-2025 19:35:31","15-02-2025 18:40:51","15-02-2025 19:=
05:56","Cascaded Incident from TTO4387592","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because ge=
n failed to start due to grid bad voltage // Gen automatically started","sy=
stem","271469","15-02-2025 19:35:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004351045","SOA TOWN=
","","15-02-2025 19:35:31","15-02-2025 18:40:51","15-02-2025 19:05:56","Cas=
caded Incident from TTO4387592","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because gen failed to s=
tart due to grid bad voltage // Gen automatically started","system","271468=
","15-02-2025 19:35:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004351043","SOA UNIV=
ERSITY STADIUM","","15-02-2025 19:35:31","15-02-2025 18:40:51","15-02-2025 =
19:05:56","Cascaded Incident from TTO4387592","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down because g=
en failed to start due to grid bad voltage // Gen automatically started","s=
ystem","271469","15-02-2025 19:35:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_322","NOCINC0004351044","Soa-II",=
"","15-02-2025 19:35:31","15-02-2025 18:40:51","15-02-2025 19:05:56","Casca=
ded Incident from TTO4387592","Siligap Boris","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down because gen failed to sta=
rt due to grid bad voltage // Gen automatically started","system","271469",=
"15-02-2025 19:35:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_317","NOCINC0004351039","Soa-Sofa=
mac","","15-02-2025 19:35:30","15-02-2025 18:40:51","15-02-2025 19:05:56","=
Cascaded Incident from TTO4387592","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because gen failed t=
o start due to grid bad voltage // Gen automatically started","system","271=
470","15-02-2025 19:35:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004351040","Ebogo","=
","15-02-2025 19:35:30","15-02-2025 18:40:51","15-02-2025 19:05:56","Cascad=
ed Incident from TTO4387592","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because gen failed to star=
t due to grid bad voltage // Gen automatically started","system","271471","=
15-02-2025 19:35:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_321","NOCINC0004351038","Soa","",=
"15-02-2025 19:35:30","15-02-2025 18:40:51","15-02-2025 19:05:56","Cascaded=
 Incident from TTO4387592","Siligap Boris","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because gen failed to start =
due to grid bad voltage // Gen automatically started","system","271470","15=
-02-2025 19:35:30","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0004350844","Ess=
os Marche","","15-02-2025 19:06:46","15-02-2025 18:46:36","15-02-2025 20:04=
:36","Grid outage, site went down due to gen overload(20Kva, 230A) // He re=
duice the load and manually start the gen","Delor Telezing","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due=
 to gen overload(20Kva, 230A) // He reduice the load and manually start the=
 gen","wilfried.kameni@sagemcom.com","1211","15-02-2025 19:06:46","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0004350795","M=
vog Mbi New","","15-02-2025 18:58:49","15-02-2025 18:40:28","15-02-2025 18:=
45:22","Active// No power issue, site is on Grid with Ubaie=3D53,5V, Brice =
Tsague(650214096) from Huawei is informed","MINKA NICOLAS","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power issue, site is on Grid with Ubaie=3D53,5V, Brice Tsague(65021=
4096) from Huawei is informed","mariam.tchonang@sagemcom.com","1102","15-02=
-2025 18:58:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0004350760","S=
OA 2","IHS_YND_321, IHS_YND_317, IHS_YND_307, IHS_YND_316, IHS_YND_720, IHS=
_YND_322, IHS_YND_320","15-02-2025 18:53:17","15-02-2025 18:40:51","15-02-2=
025 19:05:56","Site went down because gen failed to start due to grid bad v=
oltage // Gen automatically started","Siligap Boris","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Site went down because =
gen failed to start due to grid bad voltage // Gen automatically started","=
wilfried.kameni@sagemcom.com","746","15-02-2025 18:53:17","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004350668","AWA=
E OCM","","15-02-2025 18:42:40","15-02-2025 18:31:30","15-02-2025 18:39:42"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ gen start manually","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // gen start manually","wilfried.kam=
eni@sagemcom.com","672","15-02-2025 18:42:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0004350540","O=
lezoa OCM","","15-02-2025 18:25:07","15-02-2025 18:21:54","15-02-2025 18:25=
:45","No power issue site on battery with U=3D49,1v Lionnel Steeve from Hua=
wei is informed","","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D52,1v =
Lionnel Steeve from Huawei is informed","wilfried.kameni@sagemcom.com","194=
","15-02-2025 18:25:07","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004350202","Obo=
bogo","","15-02-2025 17:53:10","15-02-2025 17:42:43","15-02-2025 17:47:28",=
"No power issue , Ubaie=3D54.5 V site on GRID.The FME TX Mbah Hosiah (67400=
7438) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue ,=
 Ubaie=3D54.5 V site on GRID.The FME TX Mbah Hosiah (674007438) from Huawei=
 is informed","mariam.tchonang@sagemcom.com","628","15-02-2025 17:53:10","S=
agemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004350169","Ako=
k Ndoe Yde","","15-02-2025 17:47:52","15-02-2025 17:44:42","15-02-2025 17:5=
9:35","Grid outage, site went down before gen fails to start due to poor ba=
ttery backup // Gen started automatically","Hyemafo Gildas","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite went down before gen fails to start due to poor battery backup // Gen s=
tarted automatically","wilfried.kameni@sagemcom.com","191","15-02-2025 17:4=
7:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0004349089","E=
lig Edzoa","","15-02-2025 16:17:54","15-02-2025 16:04:35","15-02-2025 16:39=
:43","Grid outage site went down because Gen failed to start due to pwc dys=
fonction, no automatism, Gen does not support the load SS IHS Bernard Atang=
ana is confirmed // Gen manually started","Delor Telezing","Equipment Repai=
r","Passive","Control Panel","ATS-AMF Issue","Grid outage site went down be=
cause Gen failed to start due to pwc dysfonction, no automatism, Gen does n=
ot support the load SS IHS Bernard Atangana is confirmed // Gen manually st=
arted","mariam.tchonang@sagemcom.com","800","15-02-2025 16:17:54","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0004349076","E=
mombo-Tchad","","15-02-2025 16:15:42","15-02-2025 16:00:20","15-02-2025 17:=
55:48","Grid outage, No space to deploy MDG // Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spa=
ce to deploy MDG // Grid return","mariam.tchonang@sagemcom.com","923","15-0=
2-2025 16:15:42","Sagemcom CMR"
"Closed Complete","Site Down","T1652","IHS_YND_273","NOCINC0004349009","Nko=
lbi-Boss","","15-02-2025 16:09:27","15-02-2025 15:16:57","15-02-2025 15:20:=
20","No power issue, site is on grid with Ubaie=3D53V, Andelli (697768366) =
from I-Eng work on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue, site is on grid with Ubaie=3D53V, Andelli (697768366) from I-Eng work =
on site","wilfried.kameni@sagemcom.com","3151","15-02-2025 16:09:27","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004348854","S=
calom-IHS","","15-02-2025 15:47:57","15-02-2025 15:40:37","15-02-2025 15:45=
:52","ACTIVE// No power issue on site Ubaie =3D52.5V site on GridTX Fme Hos=
iah / 674007438// from huawei is informed. ","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No pow=
er issue on site Ubaie =3D52.5V site on GridTX Fme Hosiah / 674007438// fro=
m huawei is informed. ","mariam.tchonang@sagemcom.com","442","15-02-2025 15=
:47:57","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004348773","Pha=
rmacie SION","","15-02-2025 15:35:33","15-02-2025 15:29:24","15-02-2025 15:=
40:11","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen started automatically","Paul BIBOUM","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen started automatically=
","wilfried.kameni@sagemcom.com","370","15-02-2025 15:35:33","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0004348596","Ole=
mbe MTN","","15-02-2025 15:12:56","15-02-2025 15:05:38","15-02-2025 15:46:4=
3","Grid outage, site went down because gen start and stopped with alarm ov=
er current // He reset gen card and manually started","Fabrice Pouakam","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gr=
id outage, site went down because gen start and stopped with alarm over cur=
rent // He reset gen card and manually started","wilfried.kameni@sagemcom.c=
om","439","15-02-2025 15:12:56","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004348368","Acc=
acia New","","15-02-2025 14:42:27","15-02-2025 14:35:21","15-02-2025 14:45:=
24","Grid outage, no space to deploy a mobil gen // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, n=
o space to deploy a mobil gen // Grid return","wilfried.kameni@sagemcom.com=
","427","15-02-2025 14:42:27","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004348287","Nko=
abang2","","15-02-2025 14:32:50","15-02-2025 14:14:41","15-02-2025 15:24:03=
","Grid outage,site went down because gen failed to start due to grid bad v=
oltage//he did a bridge with the good phase","Mba Lazare Herve","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid outage,=
site went down because gen failed to start due to grid bad voltage//he did =
a bridge with the good phase","wilfried.kameni@sagemcom.com","1131","15-02-=
2025 14:32:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004348202","C=
omplexe-BEAC","","15-02-2025 14:16:43","15-02-2025 14:14:30","15-02-2025 15=
:02:32","Grid outage, Site went down before gen start due to poor battery b=
ackup and disjunction of 02 Cb(100A) of battery due to insufficiency of rec=
tifiers  // He reamed 02 Cb(100A) and gen manually started","Albran Byorel"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"Grid outage, Site went down before gen start due to poor battery backup a=
nd disjunction of 02 Cb(100A) of battery due to insufficiency of rectifiers=
  // He reamed 02 Cb(100A) and gen manually started","danick.tchakouani@sag=
emcom.com","134","15-02-2025 14:16:43","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0004348195","Ess=
os Marche","","15-02-2025 14:15:42","15-02-2025 14:11:33","15-02-2025 15:24=
:07","Site went down due to dysjunctions of 02 CB(125A) in PWC due to load =
// He reamed 02 Cb(125A), site on grid","Delor Telezing","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site we=
nt down due to dysjunctions of 02 CB(125A) in PWC due to load // He reamed =
02 Cb(125A), site on grid","wilfried.kameni@sagemcom.com","250","15-02-2025=
 14:15:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004347999","O=
lembe-Terminus","","15-02-2025 13:31:00","15-02-2025 12:53:51","15-02-2025 =
12:58:45","No power issue site on grid with U=3D54v //site up at 10:21 AM S=
ymphorien(675295205) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"""N o power issue site on grid with U=3D54v //site up at 10:21 AM Symphori=
en(675295205) from Huawei is informed	""
","danick.tchakouani@sagemcom.com","2231","15-02-2025 13:31:00","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0004347887","Mobil-Es=
sos","","15-02-2025 13:17:10","15-02-2025 12:57:32","15-02-2025 17:00:47","=
Cascaded Incident from TTO4384273","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to dysjunctions =
of 02 CB(125A) in PWC due to load // He reamed 02 Cb(125A), site on grid","=
system","284915","15-02-2025 13:17:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004347879","M=
adison","IHS_YND_109, IHS_YND_566","15-02-2025 13:16:05","15-02-2025 12:57:=
32","15-02-2025 17:00:47","Site went down due to dysjunctions of 02 CB(125A=
) in PWC due to load // He reamed 02 Cb(125A), site on grid","MFOUAGUEGUE M=
ATHIEU","Equipment Repair","Passive","Control Panel","Power Cabinet - Circu=
it Breaker Issue","Site went down due to dysjunctions of 02 CB(125A) in PWC=
 due to load // He reamed 02 Cb(125A), site on grid","danick.tchakouani@sag=
emcom.com","1114","15-02-2025 13:16:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004347749","E=
lig-Edzoa","","15-02-2025 12:45:16","15-02-2025 12:36:01","15-02-2025 13:10=
:55","Grid outage // Grid return","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid outage // Grid return","danick.tchakouan=
i@sagemcom.com","556","15-02-2025 12:45:16","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0004347724","Feb=
e Village","","15-02-2025 12:41:18","15-02-2025 12:34:56","15-02-2025 12:41=
:03","Site went down because gen failed to start due to grid bad voltage //=
 Gen started","Mboua Thierry","Grid Supply","Passive","Grid","National Grid=
 - Phase Controller Faulty","Site went down because gen failed to start due=
 to grid bad voltage // Gen started","wilfried.kameni@sagemcom.com","12758"=
,"15-02-2025 12:41:18","Sagemcom CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0004347710","Ngo=
ulmekong-Nord","","15-02-2025 12:37:56","15-02-2025 12:27:43","15-02-2025 1=
2:30:20","No power issue, site is on grid with Ubaie=3D53V, Alain RM(691144=
423) from Huawei is informed","Siligap Boris","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, s=
ite is on grid with Ubaie=3D53V, Alain RM(691144423) from Huawei is informe=
d","wilfried.kameni@sagemcom.com","614","15-02-2025 12:37:56","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0004347672","E=
lig Edzoa","","15-02-2025 12:31:42","15-02-2025 12:24:36","15-02-2025 13:25=
:24","Grid outage site went down because Gen failed to start  due to pwc dy=
sfonction, no automatism, Gen does not support the load SS IHS Bernard Atan=
gana is confirmed // Gen manually started","Delor Telezing","Equipment Repa=
ir","Passive","Control Panel","ATS-AMF Issue","Grid outage site went down b=
ecause Gen failed to start  due to pwc dysfonction, no automatism, Gen does=
 not support the load SS IHS Bernard Atangana is confirmed // Gen manually =
started","danick.tchakouani@sagemcom.com","427","15-02-2025 12:31:42","Sage=
mcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004347539","AWA=
E OCM","","15-02-2025 12:14:06","15-02-2025 12:06:56","15-02-2025 12:20:18"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automatically","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automatically","wilfried.kameni@=
sagemcom.com","431","15-02-2025 12:14:06","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004347531","Fou=
da Quarter","","15-02-2025 12:13:23","15-02-2025 12:10:14","15-02-2025 13:1=
2:04","Grid outage, Site went down because Gen ran until fuel shortage// re=
fueling Done","Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, Site went down because Gen ran until fuel shortage// ref=
ueling Done","wilfried.kameni@sagemcom.com","190","15-02-2025 12:13:23","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004347524","NKO=
MEKUI OCM","","15-02-2025 12:12:23","15-02-2025 12:05:06","15-02-2025 12:10=
:17","Grid outage, Site went down before Gen start due to poor backup// Gen=
 started automatically","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Grid outage,=
 Site went down before Gen start due to poor backup// Gen started automatic=
ally","wilfried.kameni@sagemcom.com","438","15-02-2025 12:12:23","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004347511","E=
kombitie","","15-02-2025 12:10:36","15-02-2025 12:00:30","15-02-2025 12:05:=
18","No power issue site on grid with U=3D54,5v Symphorien from Huawei is i=
nformed","Fabrice Pouakam","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54,5v Symphorien from Huawei is informed","danick.tchakouani@sagemcom.co=
m","607","15-02-2025 12:10:36","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004347507","MAN=
GUIERS CHAPELLE","IHS_YND_506","15-02-2025 12:10:19","15-02-2025 12:01:08",=
"15-02-2025 13:24:49","Grid outage, site went down because Gen started and =
stopped  with  alarm ""overvoltage""//Grid powe return","Fabrice Pouakam","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
 site went down because Gen started and stopped  with  alarm ""overvoltage"=
"//Grid powe return","wilfried.kameni@sagemcom.com","585","15-02-2025 12:10=
:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004347503","O=
mnisport-Rail","","15-02-2025 12:09:36","15-02-2025 12:01:08","15-02-2025 1=
3:24:49","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, site went down because Gen started and stopp=
ed  with  alarm ""overvoltage""//Grid powe return","danick.tchakouani@sagem=
com.com","273753","15-02-2025 12:09:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004347464","ELOUMDEM=
 CARRIERE 2","","15-02-2025 12:03:20","15-02-2025 11:56:35","15-02-2025 13:=
34:35","Cascaded Incident from TTO4383694","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because gen fa=
ils to start due to grid bad voltage // He bypass grid and manually start t=
he gen","system","324457","15-02-2025 12:03:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004347463","Eto koss=
 Yde","","15-02-2025 12:03:20","15-02-2025 11:56:35","15-02-2025 13:34:35",=
"Cascaded Incident from TTO4383694","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because gen fails to =
start due to grid bad voltage // He bypass grid and manually start the gen"=
,"system","324456","15-02-2025 12:03:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004347388","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","15-02-2025 11:58:44","15-02-2025 11:54=
:35","15-02-2025 13:34:35","Site went down because gen fails to start due t=
o grid bad voltage // He bypass grid and manually start the gen","Fanda Bri=
ce","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Site went down because gen fails to start due to grid bad voltage // He =
bypass grid and manually start the gen","wilfried.kameni@sagemcom.com","280=
","15-02-2025 11:58:44","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004347192","BAT=
A Mokolo OCM","","15-02-2025 11:42:26","15-02-2025 11:34:10","15-02-2025 11=
:40:37","Grid outage, No space to deploy MDG // grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No sp=
ace to deploy MDG // grid return","wilfried.kameni@sagemcom.com","497","15-=
02-2025 11:42:26","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004346878","SAA=
 Entrance","","15-02-2025 10:48:57","15-02-2025 10:25:48","15-02-2025 13:27=
:45","Grid Outage, site went down because Gen start and stopped with ""high=
 temp"" alarm due to accordion cut // He oppened the doors and Grid power r=
eturn (Accordion to be replace)","Parker Tchoup","Equipment Repair","Passiv=
e","ACDG Gen","Gen Temp High","Grid Outage, site went down because Gen star=
t and stopped with ""high temp"" alarm due to accordion cut // He oppened t=
he doors and Grid power return (Accordion to be replace)","wilfried.kameni@=
sagemcom.com","1390","15-02-2025 10:48:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004346741","O=
lembe-Terminus","","15-02-2025 10:30:39","15-02-2025 10:17:23","15-02-2025 =
11:21:23","","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Grid outage,DG started and stopped due to Alarm overcur=
rent ( Alarm not proven,Old Generator )//Reset DG card and manually start o=
f DG.","danick.tchakouani@sagemcom.com","797","15-02-2025 10:30:39","Sagemc=
om CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004346738","Nko=
londom","","15-02-2025 10:30:22","15-02-2025 10:20:08","15-02-2025 11:50:54=
","Grid outage site went down because because Gen failed to start due to AT=
S dysfonction // He reset the  ATS and Gen manually started","Fabrice Pouak=
am","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outa=
ge site went down because because Gen failed to start due to ATS dysfonctio=
n // He reset the  ATS and Gen manually started","wilfried.kameni@sagemcom.=
com","652","15-02-2025 10:30:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004346718","Akak-Nko=
zoa-MTN-IHS","","15-02-2025 10:27:30","15-02-2025 10:17:05","15-02-2025 11:=
12:06","Cascaded Incident from TTO4382768","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage , Site down b=
efore Gen Start due to poor battery backup // Gen start automatically","sys=
tem","272690","15-02-2025 10:27:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004345847","ELOUMDEM=
 CARRIERE 2","","15-02-2025 09:13:00","15-02-2025 08:58:12","15-02-2025 10:=
12:02","Cascaded Incident from TTO4381899","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, Site went d=
own because Gen failed to start due to bad voltage No Rcp// He bypassed Gri=
d and started Gen manualy","system","270311","15-02-2025 09:13:00","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004345846","Eto koss=
 Yde","","15-02-2025 09:13:00","15-02-2025 08:58:12","15-02-2025 10:12:02",=
"Cascaded Incident from TTO4381899","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down bec=
ause Gen failed to start due to bad voltage No Rcp// He bypassed Grid and s=
tarted Gen manualy","system","270311","15-02-2025 09:13:00","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004345837","ODZ=
A MINKAN EDIBI ASSI","","15-02-2025 09:11:17","15-02-2025 09:06:56","15-02-=
2025 10:24:52","Site went down because gen failed tos tart due to grid bad =
voltgae and no RCP // Gen manually started","Albran Byorel","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Site went down b=
ecause gen failed tos tart due to grid bad voltgae and no RCP // Gen manual=
ly started","wilfried.kameni@sagemcom.com","262","15-02-2025 09:11:17","Sag=
emcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004345833","SAA=
 Entrance","","15-02-2025 09:10:13","15-02-2025 09:01:48","15-02-2025 09:33=
:03","Grid Outage, site went down because Gen start and stopped with ""high=
 temp"" alarm due to accordion cut // He oppened the doors and manually sta=
rt the gen (Accordion to be replace)","Parker Tchoup","Equipment Repair","P=
assive","ACDG Gen","Gen Temp High","Grid Outage, site went down because Gen=
 start and stopped with ""high temp"" alarm due to accordion cut // He oppe=
ned the doors and manually start the gen (Accordion to be replace)","wilfri=
ed.kameni@sagemcom.com","506","15-02-2025 09:10:13","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004345821","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","15-02-2025 09:08:23","15-02-2025 08:56=
:12","15-02-2025 10:12:02","Grid fluctuation, Site went down because Gen fa=
iled to start due to bad voltage No Rcp// He bypassed Grid and started Gen =
manualy","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation, Site went down because Gen failed t=
o start due to bad voltage No Rcp// He bypassed Grid and started Gen manual=
y","wilfried.kameni@sagemcom.com","756","15-02-2025 09:08:23","Sagemcom CMR=
"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004345378","Man=
guiers Dispensaire","","15-02-2025 08:18:42","15-02-2025 08:13:37","15-02-2=
025 10:20:19","Site went down because Gen failed to start due to bad voltag=
e No Rcp// He bypassed Grid and started Gen manualy","Fabrice Pouakam","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site =
went down because Gen failed to start due to bad voltage No Rcp// He bypass=
ed Grid and started Gen manualy","danick.tchakouani@sagemcom.com","306","15=
-02-2025 08:18:42","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004345292","Nsi=
meyong Terre Rouge","","15-02-2025 08:10:20","15-02-2025 08:02:01","15-02-2=
025 10:27:17","Site went down due to PWC Disfunction, SS IHS Fran=E7ois is =
confirmed // Site stabilized","MINKA NICOLAS","Equipment Repair","Passive",=
"Rectifier","Rectifier Module Overloaded","Site went down due to PWC Disfun=
ction, SS IHS Fran=E7ois is confirmed // Site stabilized","danick.tchakouan=
i@sagemcom.com","500","15-02-2025 08:10:20","Sagemcom CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0004345228","Dag=
obert","","15-02-2025 08:04:06","15-02-2025 08:02:57","15-02-2025 08:03:06"=
,"error","TIENTCHEU NZETCHIEU GAEL","Incorrectly Logged Tickets","Error","E=
rror","Error","error","wilfried.kameni@sagemcom.com","70","15-02-2025 08:04=
:06","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004345207","Obo=
bogo","","15-02-2025 08:00:15","15-02-2025 07:57:00","15-02-2025 08:03:21",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen manually started","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
gen start due to poor battery backup // Gen manually started","wilfried.kam=
eni@sagemcom.com","196","15-02-2025 08:00:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0004345064","M=
obil-Kondengui","IHS_YND_682","15-02-2025 07:37:14","15-02-2025 07:30:09","=
15-02-2025 15:09:40","Grid outage// He deployed MDG of 20 KVA","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage// He=
 deployed MDG of 20 KVA","danick.tchakouani@sagemcom.com","426","15-02-2025=
 07:37:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0004345025","M=
ONTEE NKONDENGUI","","15-02-2025 07:30:25","15-02-2025 07:30:09","15-02-202=
5 15:09:40","","Albran Byorel","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage// He deployed MDG of 20 KVA","danick.tchako=
uani@sagemcom.com","289961","15-02-2025 07:30:25","Sagemcom CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0004344942","Ele=
veurs","","15-02-2025 07:09:16","15-02-2025 06:54:54","15-02-2025 07:10:14"=
,"Active// No power issue on site Ubaie=3D54.2V site On Grid The Tx FME bok=
ali 697200294 from I-ENG working on site","Siligap Boris","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue on site Ubaie=3D54.2V site On Grid The Tx FME bokali 697=
200294 from I-ENG working on site","wilfried.kameni@sagemcom.com","863","15=
-02-2025 07:09:16","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004344884","SOA=
 UNIVERSITY STADIUM","","15-02-2025 06:56:28","15-02-2025 06:50:10","15-02-=
2025 07:33:57","Grid outage, site went down because gen failed to start due=
 to Pwc ZTE dysfunction// He reset it and  started Gen manualy","Siligap Bo=
ris","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded"=
,"Grid outage, site went down because gen failed to start due to Pwc ZTE dy=
sfunction// He reset it and  started Gen manualy","wilfried.kameni@sagemcom=
.com","403","15-02-2025 06:56:28","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004344595","NKO=
MEKUI OCM","","15-02-2025 06:05:35","15-02-2025 06:01:22","15-02-2025 06:06=
:19","ACTIVE//No power issue on site U=3D54.5 V site on Gen.Site impacted b=
y Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","ACTIVE//No power issue on site U=3D54.5 V site on Gen.Site impacted =
by Mbankolo Camtel and not managing by IHS","wilfried.kameni@sagemcom.com",=
"254","15-02-2025 06:05:35","Sagemcom CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0004344498","Ele=
veurs","","15-02-2025 05:36:42","15-02-2025 05:33:26","15-02-2025 05:40:08"=
,"Active// No power issue on site Ubaie=3D54.2V site On Grid The Tx FME bok=
ali 697200294 from I-ENG working on site","Siligap Boris","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue on site Ubaie=3D54.2V site On Grid The Tx FME bokali 697=
200294 from I-ENG working on site","wilfried.kameni@sagemcom.com","196","15=
-02-2025 05:36:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004344483","N=
gouetou","","15-02-2025 05:29:03","15-02-2025 05:27:48","15-02-2025 05:27:4=
9","Active//No power issue site on gen with U=3D54v Gregoire/652070658/ fro=
m Huawei is informed","Parker Tchoup","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue si=
te on gen with U=3D54v Gregoire/652070658/ from Huawei is informed","wilfri=
ed.kameni@sagemcom.com","76","15-02-2025 05:29:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004344452","Matsari"=
,"","15-02-2025 05:17:40","15-02-2025 05:10:12","15-02-2025 05:18:02","Casc=
aded Incident from TTO4380387","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","ACTIVE//  no  power issue U =3D53.6V site =
on gen. Tx Fme Gregroire 654547479 of huawei is  informed and up at   05:18=
:41","system","262353","15-02-2025 05:17:40","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004344447","MBI=
MBIM","IHS_YND_460","15-02-2025 05:16:33","15-02-2025 05:10:12","15-02-2025=
 05:18:02","ACTIVE//  no  power issue U =3D53.6V site on gen. Tx Fme Gregro=
ire 654547479 of huawei is  informed and up at   05:18:41","Parker Tchoup",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","ACTIVE//  no  power issue U =3D53.6V site on gen. Tx Fme Gregro=
ire 654547479 of huawei is  informed and up at   05:18:41","wilfried.kameni=
@sagemcom.com","382","15-02-2025 05:16:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0004344221","C=
RF Nkoabang","","15-02-2025 03:54:03","15-02-2025 02:30:41","15-02-2025 09:=
24:02","Grid outage No space to deploy // Grid power return","Mba Lazare He=
rve","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage No space to deploy // Grid power return","wilfried.kameni@sagemco=
m.com","5003","15-02-2025 03:54:03","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004343828","NKO=
LOSSAN OKOK","","15-02-2025 01:51:35","15-02-2025 01:48:18","15-02-2025 02:=
18:01","Active// No power issue, on site site on Gen with Ubaie=3D52 V The =
 FME Tx GreGoire Huawei//654-54-74-79 is informed.","Parker Tchoup","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power issue, on site site on Gen with Ubaie=3D52 V
The  FME Tx GreGoire Huawei//654-54-74-79 is informed.","wilfried.kameni@sa=
gemcom.com","197","15-02-2025 01:51:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004342859","B=
iteng-Maetur","","14-02-2025 22:32:16","14-02-2025 22:27:07","15-02-2025 00=
:45:43","Active // No power issue site on Grid with U=3D53,6 V ,The FME Tx =
Leonel Steve  (655184876) of huawei is informed","Mba Lazare Herve","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active // No power issue site on Grid with U=3D53,6 V ,The FME Tx Leon=
el Steve  (655184876) of huawei is informed","wilfried.kameni@sagemcom.com"=
,"310","14-02-2025 22:32:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004342480","C=
RH-Etoug-Ebe","","14-02-2025 21:38:37","14-02-2025 21:12:25","14-02-2025 21=
:56:34","	Grid outage, site went down before gen start due to poor battery =
backup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","	Grid outage, site wen=
t down before gen start due to poor battery backup // Gen start automatical=
ly","wilfried.kameni@sagemcom.com","1573","14-02-2025 21:38:37","Sagemcom C=
MR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004341909","Crf=
-Mbankolo-IHS","","14-02-2025 20:48:45","14-02-2025 20:35:35","14-02-2025 2=
2:48:46","Site went down due to MPR disfunction SS IHS Bernard Atangana con=
firmed/ / Site stabilized","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Cabinet","Site went down due to MPR disfunction SS IHS =
Bernard Atangana confirmed/ / Site stabilized","wilfried.kameni@sagemcom.co=
m","854","14-02-2025 20:48:45","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0004341869","Feb=
e Village","","14-02-2025 20:44:51","14-02-2025 20:39:34","14-02-2025 21:59=
:13","Grid outage, Site went down because Gen overload (15 KVA, 210A) SS IH=
S Bernard Atangana is informed//He reduiced load and started Gen manualy","=
Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid outage, Site went down because Gen overload (15 KVA, 210A) SS IHS Berna=
rd Atangana is informed//He reduiced load and started Gen manualy","wilfrie=
d.kameni@sagemcom.com","318","14-02-2025 20:44:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004341436","Abattoir=
","","14-02-2025 19:56:10","14-02-2025 19:46:06","14-02-2025 19:56:35","Cas=
caded Incident from TTO4376888","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active, no power issu, site is on grid =
with Ubaie=3D53V, Armand Nguetsa(699949553) from Huawei is informed ","syst=
em","267365","14-02-2025 19:56:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004341437","ETOUDI C=
HAPELLE","","14-02-2025 19:56:10","14-02-2025 19:46:06","14-02-2025 19:56:3=
5","Cascaded Incident from TTO4376888","Delor Telezing","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active, no power issu, site is on=
 grid with Ubaie=3D53V, Armand Nguetsa(699949553) from Huawei is informed "=
,"system","267364","14-02-2025 19:56:10","Sagemcom CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0004341431","Eto=
udi 2","IHS_YND_244, IHS_YND_694","14-02-2025 19:55:18","14-02-2025 19:46:0=
6","14-02-2025 19:56:35","Active, no power issu, site is on grid with Ubaie=
=3D53V, Armand Nguetsa(699949553) from Huawei is informed ","Fabrice Pouaka=
m","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active, no power issu, site is on grid with Ubaie=3D53V, Arm=
and Nguetsa(699949553) from Huawei is informed ","wilfried.kameni@sagemcom.=
com","553","14-02-2025 19:55:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004341321","C=
ite-Verte","","14-02-2025 19:38:00","14-02-2025 18:59:25","14-02-2025 20:32=
:09","Grid outage// He deployed MDG of 20 KVA","","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","Grid outage// He deployed MDG of=
 20 KVA","wilfried.kameni@sagemcom.com","2317","14-02-2025 19:38:00","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0004341289","O=
dza","","14-02-2025 19:34:44","14-02-2025 19:13:38","14-02-2025 20:42:03","=
Eneo Meter CB down, Site went down because Gen failed to start due to  Hybr=
id System disfunction// Eneo Meter CB put back on","Albran Byorel","Equipme=
nt Repair","Passive","Hybrid","Hybrid Module","Eneo Meter CB down, Site wen=
t down because Gen failed to start due to  Hybrid System disfunction// Eneo=
 Meter CB put back on","wilfried.kameni@sagemcom.com","1267","14-02-2025 19=
:34:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004341055","M=
ontee-Jouvence-II","","14-02-2025 18:59:15","14-02-2025 18:49:10","14-02-20=
25 20:54:40","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed//Site Stabilized","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Site went down due to PWC Overloaded (=
12K, 250A)SS IHS Felix Zamb=E9 confirmed//Site Stabilized","wilfried.kameni=
@sagemcom.com","606","14-02-2025 18:59:15","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004340848","Mes=
sa Carriere","","14-02-2025 18:30:25","14-02-2025 18:22:59","14-02-2025 18:=
54:48","Site went down due to insufficiency of rectifier Fran=E7ois IHS con=
firmed // Site stabilized","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficiency of rectifi=
er Fran=E7ois IHS confirmed // Site stabilized","ludivine.ngamaleu@ihstower=
s.com","447","14-02-2025 18:30:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004339864","N=
KOLMEKONG YDE","","14-02-2025 16:18:18","14-02-2025 10:39:47","14-02-2025 1=
2:26:32","Site went down because 4/7 rectifiers alarming because of the PWC=
 which is disfonctionning // he reset rectifiers","Fabrice Pouakam","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went =
down because 4/7 rectifiers alarming because of the PWC which is disfonctio=
nning // he reset rectifiers","wilfried.kameni@sagemcom.com","20312","14-02=
-2025 16:18:18","Sagemcom CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0004339579","Ele=
veurs","","14-02-2025 15:44:43","14-02-2025 15:42:36","14-02-2025 15:47:20"=
," ACTIVE// No power issue site on grid with U=3D54.4 V  The Tx FME Synphor=
ien//691316854 from Huawei is informed.","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," ACTIV=
E// No power issue site on grid with U=3D54.4 V  The Tx FME Synphorien//691=
316854 from Huawei is informed.","wilfried.kameni@sagemcom.com","128","14-0=
2-2025 15:44:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0004339355","MEFOU AS=
SI","","14-02-2025 15:30:30","14-02-2025 14:12:03","14-02-2025 14:20:00","C=
ascaded Incident from TTO4373941","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID , Uba=
ie=3D54.V site On Grid The Tx FME Fulbert(654266068) from Huawei is informe=
d","system","272971","14-02-2025 15:30:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004339295","B=
arriere IHS","","14-02-2025 15:21:58","14-02-2025 14:12:03","14-02-2025 14:=
20:00","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","Casc=
ade Active","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Gri=
d The Tx FME Fulbert(654266068) from Huawei is informed","wilfried.kameni@s=
agemcom.com","272971","14-02-2025 15:21:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004339217","C=
omplexe-BEAC","","14-02-2025 15:09:34","14-02-2025 13:53:08","14-02-2025 14=
:20:00","Grid outage, site went down before gen start due to poor battery b=
ackup // gen start automatically","Albran Byorel","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // gen start automatically"=
,"wilfried.kameni@sagemcom.com","4587","14-02-2025 15:09:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004339175","Angongo"=
,"","14-02-2025 15:02:50","14-02-2025 14:23:48","14-02-2025 15:50:00","Casc=
aded Incident from TTO4374248","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site was on Gen due to Grid outage, Site =
went down because Gen stopped with ""High temp ""alarm // He added water an=
d manually start the Gen","system","272180","14-02-2025 15:02:50","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0004339172","Ebe=
ba","IHS_YND_335","14-02-2025 15:01:55","14-02-2025 14:23:48","14-02-2025 1=
5:51:45","Site was on Gen due to Grid outage, Site went down because Gen st=
opped with ""High temp ""alarm // He added water and manually start the Gen=
","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine=
 Temp - Coolant Level Issue","Site was on Gen due to Grid outage, Site went=
 down because Gen stopped with ""High temp ""alarm // He added water and ma=
nually start the Gen","wilfried.kameni@sagemcom.com","2334","14-02-2025 15:=
01:55","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004339103","ODZ=
A MINKAN EDIBI ASSI","","14-02-2025 14:50:11","14-02-2025 14:35:08","14-02-=
2025 15:14:23","Grid fluctuation, Site went down because Gen failed to star=
t due to Grid bad voltage and No RCP on site // He bypassed Grid and starte=
d Gen manually","Albran Byorel","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Grid fluctuation, Site went down because Gen=
 failed to start due to Grid bad voltage and No RCP on site // He bypassed =
Grid and started Gen manually","wilfried.kameni@sagemcom.com","904","14-02-=
2025 14:50:11","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004339059","HOP=
ITAL GENERAL RAIL YDE","","14-02-2025 14:42:36","14-02-2025 14:23:29","14-0=
2-2025 17:07:46","Grid outage, Site went down because Gen overload (9kva,16=
0A) SS IHS Bernard ATANGANA confirmed// Grid return","Delor Telezing","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site wen=
t down because Gen overload (9kva,160A) SS IHS Bernard ATANGANA confirmed//=
 Grid return","wilfried.kameni@sagemcom.com","1148","14-02-2025 14:42:36","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004338929","M=
efou-Assi","IHS_YND_537, IHS_YND_696","14-02-2025 14:16:17","14-02-2025 14:=
12:03","14-02-2025 14:20:00","ACTIVE//No power issue on site GRID , Ubaie=
=3D54.V site On Grid The Tx FME Fulbert(654266068) from Huawei is informed"=
,"Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D54=
.V site On Grid The Tx FME Fulbert(654266068) from Huawei is informed","mar=
iam.tchonang@sagemcom.com","256","14-02-2025 14:16:17","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004338802","ETO=
UDI Entree du palais","","14-02-2025 13:47:44","14-02-2025 11:48:34","14-02=
-2025 12:49:59","Grid outage, site went down because Gen fails to start due=
 to Gen card  dysfunction //  He Reset The Gen card done and Gen started","=
Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","Grid outage, site went down because Gen fails to start due to Gen car=
d  dysfunction //  He Reset The Gen card done and Gen started","wilfried.ka=
meni@sagemcom.com","7151","14-02-2025 13:47:44","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004338738","Awa=
e Ewonkan","","14-02-2025 13:32:48","14-02-2025 12:12:32","14-02-2025 12:22=
:01","Site went down due to insufficiency rectifiers (06 rectfiers) due to =
load increase on site IHS SS Alphonse is informed // site stabilized","Albr=
an Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","Sit=
e went down due to insufficiency rectifiers (06 rectfiers) due to load incr=
ease on site IHS SS Alphonse is informed // site stabilized","wilfried.kame=
ni@sagemcom.com","4817","14-02-2025 13:32:48","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004338733","Obo=
bogo","","14-02-2025 13:31:18","14-02-2025 12:09:58","14-02-2025 12:15:31",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
ted automatically","MINKA NICOLAS","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen started automatically","wilfried.kameni@sage=
mcom.com","4881","14-02-2025 13:31:18","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004338727","Mon=
tee-Jouvence-II","","14-02-2025 13:30:09","14-02-2025 12:01:50","14-02-2025=
 12:15:21","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix Za=
mb=E9 confirmed // Site stabilized","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Site went down due to PWC=
 Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site stabilized","=
wilfried.kameni@sagemcom.com","5300","14-02-2025 13:30:09","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004338699","Nsi=
meyong Terre Rouge","","14-02-2025 13:26:05","14-02-2025 11:57:06","14-02-2=
025 12:09:20","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen manually started","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down before gen start due to poor battery backup // Gen manually started"=
,"wilfried.kameni@sagemcom.com","5340","14-02-2025 13:26:05","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004338685","Ema=
na","","14-02-2025 13:24:07","14-02-2025 12:07:50","14-02-2025 12:17:21","G=
rid outage, site went down before gen start due to poor battery backup // G=
rid power return","Fabrice Pouakam","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery backup // Grid power return","wilfried.kameni@sa=
gemcom.com","4579","14-02-2025 13:24:07","Sagemcom CMR"
"Closed Complete","Site Down","T2585","IHS_YND_744","NOCINC0004338682","Ele=
veur Meec Bon Berger","","14-02-2025 13:22:44","14-02-2025 12:12:31","14-02=
-2025 12:22:55","Grid outage, site went down before gen start due to poor b=
attery backup // Gen start automatically","Siligap Boris","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen start automa=
tically","wilfried.kameni@sagemcom.com","4214","14-02-2025 13:22:44","Sagem=
com CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004338529","Nko=
abang MTN","","14-02-2025 13:03:39","14-02-2025 12:57:21","14-02-2025 13:37=
:42","Site went down because gen failed to start due to grid bad voltage //=
 Gen manually started","Mba Lazare Herve","Grid Supply","Passive","Grid","N=
ational Grid - Grid Outage Issue","Site went down because gen failed to sta=
rt due to grid bad voltage // Gen manually started","wilfried.kameni@sagemc=
om.com","379","14-02-2025 13:03:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004338376","F=
ouda-New","","14-02-2025 12:46:28","14-02-2025 11:55:20","14-02-2025 21:30:=
02","Active: no power issue, site  is on battery with Ubaie=3D48V, Armand N=
guetsa(691144412) from Huawei is informed","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: no power issue, site  is on battery with Ubaie=3D48V, Armand Nguetsa(6=
91144412) from Huawei is informed","wilfried.kameni@sagemcom.com","3069","1=
4-02-2025 12:46:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004338348","O=
lembe-Terminus","","14-02-2025 12:42:41","14-02-2025 12:30:31","14-02-2025 =
12:51:58","Grid outage,DG started and stopped due to Alarm overcurrent ( Al=
arm not proven,Old Generator )//Reset DG card and manually start of DG.","F=
abrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Grid outage,DG started and stopped due to Alarm overcurrent ( Alarm no=
t proven,Old Generator )//Reset DG card and manually start of DG.","wilfrie=
d.kameni@sagemcom.com","731","14-02-2025 12:42:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004338323","B=
iteng-Maetur","","14-02-2025 12:40:44","14-02-2025 12:09:19","14-02-2025 15=
:03:54","Grid outage, Site went down due to Gen overload(20KVA, 260A) SS IH=
S Blaise confirmed// Grid return","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to Gen=
 overload(20KVA, 260A) SS IHS Blaise confirmed// Grid return.","mariam.tcho=
nang@sagemcom.com","1887","14-02-2025 12:40:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0004338289","Eloumdem=
 stade","","14-02-2025 12:38:50","14-02-2025 12:36:22","14-02-2025 14:23:22=
","Cascaded Incident from TTO4373168","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen start and stopped with ""High temps ""alarm // he added water and man=
ually start the Gen","system","307659","14-02-2025 12:38:50","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004338284","Sim=
bock MTN","IHS_YND_793","14-02-2025 12:37:29","14-02-2025 12:36:22","14-02-=
2025 14:23:22","Grid outage, Site went down because Gen start and stopped w=
ith ""High temps ""alarm // he added water and manually start the Gen","Fan=
da Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Grid outage, Site went down because Gen start and s=
topped with ""High temps ""alarm // he added water and manually start the G=
en","wilfried.kameni@sagemcom.com","68","14-02-2025 12:37:29","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004338259","M=
vog-Ada_OCM","","14-02-2025 12:33:28","14-02-2025 11:55:09","14-02-2025 18:=
05:20","Grid outage, No space to deploy MDG// Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spac=
e to deploy MDG// Grid return","mariam.tchonang@sagemcom.com","2300","14-02=
-2025 12:33:28","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004338244","Mvo=
g-Manga","","14-02-2025 12:31:25","14-02-2025 12:07:06","14-02-2025 12:45:5=
8","Grid outage, Site went down before gen start due to poor battery backup=
 // Gen start automatically","Albran Byorel","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down b=
efore gen start due to poor battery backup // Gen start automatically","wil=
fried.kameni@sagemcom.com","1516","14-02-2025 12:31:25","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004338229","Man=
guiers Dispensaire","","14-02-2025 12:29:04","14-02-2025 12:15:32","14-02-2=
025 12:28:33","Gen stopped due to grid return, Site went down because grid =
contcator faulty // He bypassed contactor, site on grid","Fabrice Pouakam",=
"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gen stopped d=
ue to grid return, Site went down because grid contcator faulty // He bypas=
sed contactor, site on grid","wilfried.kameni@sagemcom.com","813","14-02-20=
25 12:29:04","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004338145","Pha=
rmacie SION","","14-02-2025 12:26:21","14-02-2025 12:14:42","14-02-2025 12:=
25:13","Grid outage, Site went down before Gen start due to poor backup// G=
en started automaticaly","Paul BIBOUM","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automaticaly","wilfried.kameni@s=
agemcom.com","700","14-02-2025 12:26:21","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004338112","BIY=
EMASSI NIKI","","14-02-2025 12:22:13","14-02-2025 12:04:01","14-02-2025 13:=
45:06","Grid outage, site went down down due PWC overloaded (12 kw 250A) //=
Manually start of DG ,he reduiced the load.","Hyemafo Gildas","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, sit=
e went down down due PWC overloaded (12 kw 250A) //Manually start of DG ,he=
 reduiced the load.","wilfried.kameni@sagemcom.com","1133","14-02-2025 12:2=
2:13","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004338101","Nlo=
ngkak","","14-02-2025 12:21:23","14-02-2025 12:05:09","14-02-2025 12:33:12"=
,"Grid outage,DG   started and stopped due to alarm oil pressure( Alarm not=
 proven) // Reset DG card and started DG manually","Delor Telezing","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,DG   s=
tarted and stopped due to alarm oil pressure( Alarm not proven) // Reset DG=
 card and started DG manually.","wilfried.kameni@sagemcom.com","975","14-02=
-2025 12:21:23","Sagemcom CMR"
"Closed Complete","Site Down","T3149","IHS_YND_044","NOCINC0004338095","Pol=
ytechnique","","14-02-2025 12:20:35","14-02-2025 11:51:33","14-02-2025 11:5=
5:57","","","Cascade Outage","Active","Cascade Active","Cascade Active","No=
 power issue, site is on grid with Ubaie=3D53V, Yannick nana (674971093) fr=
om I-eng working on site","wilfried.kameni@sagemcom.com","295811","14-02-20=
25 12:20:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004338094","C=
rf-Nsam","","14-02-2025 12:20:29","14-02-2025 11:48:07","14-02-2025 12:25:3=
1","Site went down Because The Slot of Rectifier is overload //site stabili=
zed SS Ihs Pascaline is informed and is confirmed","MINKA NICOLAS","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","	Site went down Becaus=
e The Slot of Rectifier is overload //site stabilized SS Ihs Pascaline is i=
nformed and is confirmed","mariam.tchonang@sagemcom.com","1943","14-02-2025=
 12:20:29","Sagemcom CMR"
"Closed Complete","Site Down","T0036","IHS_YND_076","NOCINC0004338091","Le =
Flamboyant","","14-02-2025 12:19:41","14-02-2025 11:51:33","14-02-2025 11:5=
5:57","","Paul BIBOUM","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue, site is on grid with Ubaie=3D53V, Yannick nana (67=
4971093) from I-eng working on site","wilfried.kameni@sagemcom.com","295811=
","14-02-2025 12:19:41","Sagemcom CMR"
"Closed Complete","Site Down","T3172","IHS_YND_043","NOCINC0004338086","Emi=
a","","14-02-2025 12:18:43","14-02-2025 11:51:33","14-02-2025 11:55:57","",=
"","Cascade Outage","Active","Cascade Active","Cascade Active","No power is=
sue, site is on grid with Ubaie=3D53V, Yannick nana (674971093) from I-eng =
working on site","wilfried.kameni@sagemcom.com","295812","14-02-2025 12:18:=
43","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004338079","An-=
Marche-Melen","","14-02-2025 12:17:44","14-02-2025 11:51:33","14-02-2025 14=
:06:08","Grid outage, no space to deploy a mobil gen// Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, no space to deploy a mobil gen// Grid return","wilfried.kameni@sagemcom.c=
om","1572","14-02-2025 12:17:44","Sagemcom CMR"
"Closed Complete","Site Down","T0817","IHS_YND_061","NOCINC0004338076","Yde=
 University","IHS_YND_076, IHS_YND_043, IHS_YND_044","14-02-2025 12:16:48",=
"14-02-2025 11:51:33","14-02-2025 11:55:57","No power issue, site is on gri=
d with Ubaie=3D53V, Yannick nana (674971093) from I-eng working on site","P=
aul BIBOUM","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","No power issue, site is on grid with Ubaie=3D53V, Y=
annick nana (674971093) from I-eng working on site","wilfried.kameni@sagemc=
om.com","1515","14-02-2025 12:16:48","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004338067","Beh=
ind P T school Yde","","14-02-2025 12:14:44","14-02-2025 11:50:32","14-02-2=
025 13:09:05","Grid outage,DG failed to start due to poor Battery backup//G=
rid restored.","Paul BIBOUM","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage,DG failed to start due to poor Ba=
ttery backup//Grid restored.","wilfried.kameni@sagemcom.com","1453","14-02-=
2025 12:14:44","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004338065","AWA=
E OCM","","14-02-2025 12:13:34","14-02-2025 11:50:20","14-02-2025 13:30:21"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen Manually started ","Mba Lazare Herve","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen Manually started ","wilfri=
ed.kameni@sagemcom.com","1396","14-02-2025 12:13:34","Sagemcom CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004337955","Sca=
lom","","14-02-2025 12:05:43","14-02-2025 11:47:26","14-02-2025 12:33:14","=
Grid outage, site went down because gen failed to start // Grid return (Inv=
estigation ongoing)","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Grid outage, site went down because gen failed to s=
tart // Grid return (Investigation ongoing)","wilfried.kameni@sagemcom.com"=
,"1122","14-02-2025 12:05:43","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004337940","Sap=
eur","","14-02-2025 12:03:21","14-02-2025 11:47:08","14-02-2025 12:04:59","=
Grid outage, site went down because Gen failed to start due to poor battery=
 backup // Gen automatically started","Mboua Thierry","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down because Gen failed to start due to poor battery backup // Gen autom=
atically started","wilfried.kameni@sagemcom.com","17979","14-02-2025 12:03:=
21","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0004337926","Ole=
mbe","","14-02-2025 12:01:15","14-02-2025 11:49:03","14-02-2025 13:44:57","=
Site  went down due to work(Fabrice(672225561)/Sagemcom, PM)// End of work"=
,"Fabrice Pouakam","Equipment Replacement","Passive","Planned Activity","Pl=
anned Activity - Passive","Site  went down due to work(Fabrice(672225561)/S=
agemcom, PM)// End of work","wilfried.kameni@sagemcom.com","776","14-02-202=
5 12:01:15","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004337902","NKO=
MEKUI OCM","","14-02-2025 11:56:47","14-02-2025 11:48:27","14-02-2025 11:58=
:19","No power issue  ","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","tx
","wilfried.kameni@sagemcom.com","501","14-02-2025 11:56:47","Sagemcom CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0004337859","Ebe=
ba","","14-02-2025 11:49:37","14-02-2025 11:14:29","14-02-2025 12:20:07"," =
Site went because Gen ran until fuel shortage//Refueling Done","Fanda Brice=
","Fuel Outage","Passive","Diesel","Diesel Outage"," Site went because Gen =
ran until fuel shortage//Refueling Done","wilfried.kameni@sagemcom.com","99=
47","14-02-2025 11:49:37","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004337667","Nko=
lbong","","14-02-2025 11:15:45","14-02-2025 11:11:39","14-02-2025 12:34:57"=
,"Grid fluctuation, site went down before gen start due to poor battery bac=
kup // gen start automatically","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid fluctuation, site we=
nt down before gen start due to poor battery backup // gen start automatica=
lly","wilfried.kameni@sagemcom.com","247","14-02-2025 11:15:45","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_085","NOCINC0004337270","Briquete=
rie","","14-02-2025 10:12:00","14-02-2025 10:04:18","14-02-2025 10:10:57","=
Cascaded Incident from TTO4371974","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","Active; no power issue site on grid with U=3D54,3V;=
The fme TX Hosiah 674007438 of huawei is informed ","system","266480","14-0=
2-2025 10:12:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0004337269","K=
amajou Building","IHS_YND_085","14-02-2025 10:11:34","14-02-2025 10:04:18",=
"14-02-2025 10:10:57","Active; no power issue site on grid with U=3D54,3V;T=
he fme TX Hosiah 674007438 of huawei is informed ","Paul BIBOUM","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active; no power issue site on grid with U=3D54,3V;The fme TX Hosiah 6740=
07438 of huawei is informed ","wilfried.kameni@sagemcom.com","437","14-02-2=
025 10:11:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0004337114","M=
ambine","","14-02-2025 09:52:17","14-02-2025 09:39:39","14-02-2025 11:21:54=
","Grid outage, Site went because Gen ran until fuel shortage//Refueling Do=
ne","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid ou=
tage, Site went because Gen ran until fuel shortage//Refueling Done","maria=
m.tchonang@sagemcom.com","784","14-02-2025 09:52:17","Sagemcom CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004336842","Eto=
udi2","","14-02-2025 09:23:15","14-02-2025 09:03:09","14-02-2025 09:57:57",=
"Site went down due to insufficiency of rectifier (Site on 01 Rectifiers ) =
SS IHS Bernard Atagana is informed and confimed // Site Stabilized","Delor =
Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Site=
 went down due to insufficiency of rectifier (Site on 01 Rectifiers ) SS IH=
S Bernard Atagana is informed and confimed // Site Stabilized","wilfried.ka=
meni@sagemcom.com","1207","14-02-2025 09:23:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0004336733","Nguila",=
"","14-02-2025 09:18:40","14-02-2025 09:06:30","14-02-2025 09:54:01","site =
went down because gen ran untill fuel shortage // Refueling done. Refueling=
 is managed by edonde","Parker Tchoup","Fuel Outage","Passive","Diesel","Di=
esel Outage","site went down because gen ran untill fuel shortage // Refuel=
ing done. Refueling is managed by edonde","system","1298","14-02-2025 09:18=
:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004336266","D=
ong","","14-02-2025 08:00:15","14-02-2025 07:33:06","14-02-2025 07:40:56","=
Active: No power issue, site on battery  With Ubaie=3D50.5V, The Tx FME Gre=
goire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: No power issue, site on battery  With Ubaie=3D50.5V, The Tx FME Gregoir=
e (654547479) from Huawei is informed","wilfried.kameni@sagemcom.com","1630=
","14-02-2025 08:00:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004336032","N=
KOLMEKONG YDE","","14-02-2025 07:21:19","14-02-2025 07:14:53","14-02-2025 0=
8:49:58","Site went down because 4/7 rectifiers alarming because of the PWC=
 which is disfonctionning  // he reset rectifiers","Fabrice Pouakam","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down becau=
se 4/7 rectifiers alarming because of the PWC which is disfonctionning  // =
he reset rectifiers","mariam.tchonang@sagemcom.com","387","14-02-2025 07:21=
:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004335938","N=
gouetou","","14-02-2025 06:59:01","14-02-2025 06:54:52","14-02-2025 07:05:0=
7","ACTIVE//No power issue on site, site on Gen The Tx FME Gregoire/6545474=
79/ from huawei is informed. Repetitive issue","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE//No power issue on site, site on Gen The Tx FME Gregoire/654547479/ =
from huawei is informed. Repetitive issue","wilfried.kameni@sagemcom.com","=
251","14-02-2025 06:59:01","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004335805","Nsi=
meyong Terre Rouge","","14-02-2025 06:39:16","14-02-2025 06:35:08","14-02-2=
025 06:48:02","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen manually started","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down before gen start due to poor battery backup // Gen manually started"=
,"wilfried.kameni@sagemcom.com","249","14-02-2025 06:39:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0004335412","A=
n-Marche-Melen","","14-02-2025 04:37:12","13-02-2025 20:19:46","13-02-2025 =
20:20:13","Active//No power issue site and  with Ubaie=3D50.4V site on Grid=
 The  FME TX Mouamadou/658791013 //From Huawei is informed ","","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue site and  with Ubaie=3D50.4V site on Grid The  FME =
TX Mouamadou/658791013 //From Huawei is informed ","wilfried.kameni@sagemco=
m.com","29847","14-02-2025 04:37:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004335141","D=
ong","","14-02-2025 02:53:28","14-02-2025 02:48:20","14-02-2025 02:50:12","=
No power issue hybrid gen site on battery with U=3D50.1v Gregoire from Huaw=
ei is informed ","Parker Tchoup","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue hybrid gen site=
 on battery with U=3D50.1v Gregoire from Huawei is informed ","wilfried.kam=
eni@sagemcom.com","309","14-02-2025 02:53:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0004335089","N=
kolso","","14-02-2025 02:34:40","14-02-2025 02:09:26","14-02-2025 02:16:16"=
,"Active// No power issue, site is on Grid with Ubaie=3D54,8V, Mohamadou(69=
1144435) from Huawei is informed site up at 03:30 AM","TIENTCHEU NZETCHIEU =
GAEL","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active// No power issue, site is on Grid with Ubaie=3D54,=
8V, Mohamadou(691144435) from Huawei is informed site up at 03:30 AM","wilf=
ried.kameni@sagemcom.com","1515","14-02-2025 02:34:40","Sagemcom CMR"
"Closed Complete","Site Down","T0638","IHS_YND_318","NOCINC0004334964","SOA=
 University","","14-02-2025 01:50:00","14-02-2025 01:43:42","14-02-2025 02:=
36:50","Site went down because gen start and stopped due to Grid bad voltag=
e, No RCP on site // Grid Restored","Siligap Boris","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Site went down because g=
en start and stopped due to Grid bad voltage, No RCP on site // Grid Restor=
ed","wilfried.kameni@sagemcom.com","379","14-02-2025 01:50:00","Sagemcom CM=
R"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0004334602","COR=
NIERS","","14-02-2025 00:24:16","13-02-2025 18:42:54","14-02-2025 02:00:05"=
,"Active//No power issue on site U=3D52.9 V Site on Grid . the FME TX Arman=
d Nguetsa (699949553) is informed","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on=
 site U=3D52.9 V Site on Grid . the FME TX Armand Nguetsa (699949553) is in=
formed","wilfried.kameni@sagemcom.com","20483","14-02-2025 00:24:16","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004334461","N=
KOLMEKONG YDE","","13-02-2025 23:27:50","13-02-2025 23:13:39","14-02-2025 0=
1:12:39","Site went down because PWC dysfunctionning// site stabilised","Fa=
brice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Site went down because PWC dysfunctionning// site stabilised","=
wilfried.kameni@sagemcom.com","852","13-02-2025 23:27:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004334338","B=
iteng-Maetur","","13-02-2025 23:00:24","13-02-2025 21:56:16","13-02-2025 22=
:05:27","Active// No power issue, site is on Grid with Ubaie=3D53,6V, Lione=
l Adjep(655184876) from Huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power issue, site is on Grid with Ubaie=3D53,6V, Lionel Adjep(6=
55184876) from Huawei is informed","wilfried.kameni@sagemcom.com","3850","1=
3-02-2025 23:00:24","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0004334273","Mam=
bine","","13-02-2025 22:49:27","13-02-2025 21:26:43","13-02-2025 23:01:20",=
"site went down because gen ran untill fuel shortage // Refueling done","Fa=
nda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","site went down=
 because gen ran untill fuel shortage // Refueling done","wilfried.kameni@s=
agemcom.com","5345","13-02-2025 22:49:27","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004333852","Nko=
lnda","","13-02-2025 21:48:59","13-02-2025 21:05:15","13-02-2025 21:10:42",=
"No po=E0wer issue site on grid with U=3D54v Martial from Huawei is informe=
d ","Albran Byorel","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No po=E0wer issue site on grid with U=3D54v=
 Martial from Huawei is informed ","wilfried.kameni@sagemcom.com","2625","1=
3-02-2025 21:48:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004333837","N=
kolda","","13-02-2025 21:47:24","13-02-2025 21:44:18","13-02-2025 21:48:49"=
,"Site went down due to (1/4)Rectifier dysfunctionning because The Load Inc=
rease //he reset the Rectifier and Site is on Grid","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site went down due to=
 (1/4)Rectifier dysfunctionning because The Load Increase //he reset the Re=
ctifier and Site is on Grid","wilfried.kameni@sagemcom.com","187","13-02-20=
25 21:47:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_044","NOCINC0004333149","Polytech=
nique","","13-02-2025 20:04:10","13-02-2025 19:37:48","13-02-2025 21:05:41"=
,"Cascaded Incident from TTO4367044","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Site went down Because the CB(63 A) of the PWC=
 dysjoncted due to load increased // He replaced it to the CB (80 A)","syst=
em","303928","13-02-2025 20:04:10","Sagemcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0004333018","ODZ=
A BORNE 10","","13-02-2025 19:49:02","13-02-2025 19:15:40","13-02-2025 20:4=
9:09","Grid outage site went down due to 02/03 rectifiers alarming on site =
//he reset","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Grid outage site went down due to 02/03 rectifiers alarming o=
n site //he reset","wilfried.kameni@sagemcom.com","2002","13-02-2025 19:49:=
02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_076","NOCINC0004333016","Le Flamb=
oyant","","13-02-2025 19:48:33","13-02-2025 19:37:48","13-02-2025 21:05:41"=
,"Cascaded Incident from TTO4366989 - Cascade Removed From TTO4366989","Pau=
l BIBOUM","Cascade Outage","Passive","Cascade Passive","Cascade Passive","S=
ite went down Because the CB(63 A) of the PWC dysjoncted due to load increa=
sed // He replaced it to the CB (80 A)","system","303927","13-02-2025 19:48=
:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_061","NOCINC0004333017","Yde Univ=
ersity","IHS_YND_076, IHS_YND_043, IHS_YND_044","13-02-2025 19:48:33","13-0=
2-2025 19:37:48","13-02-2025 21:05:41","Site went down Because the CB(63 A)=
 of the PWC dysjoncted due to load increased // He replaced it to the CB (8=
0 A)","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Circuit Breaker Issue","Site went down Because the CB(63 A) of the P=
WC dysjoncted due to load increased // He replaced it to the CB (80 A)","sy=
stem","645","13-02-2025 19:48:33","Sagemcom CMR"
"Closed Complete","Site Down","T3172","IHS_YND_043","NOCINC0004332969","Emi=
a","","13-02-2025 19:41:56","13-02-2025 19:37:48","13-02-2025 21:05:41","",=
"","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Site wen=
t down Because the CB(63 A) of the PWC dysjoncted due to load increased // =
He replaced it to the CB (80 A)","wilfried.kameni@sagemcom.com","303927","1=
3-02-2025 19:41:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004332863","N=
KOLMEKONG YDE","","13-02-2025 19:25:31","13-02-2025 19:13:26","13-02-2025 1=
9:29:16","Site went down because PWC dysfunctionning// site stabilised","Fa=
brice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Site went down because PWC dysfunctionning// site stabilised","=
wilfried.kameni@sagemcom.com","726","13-02-2025 19:25:31","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004332600","SOA=
 UNIVERSITY STADIUM","","13-02-2025 18:48:02","13-02-2025 18:24:26","13-02-=
2025 19:30:13","Grid outage, site went down because gen failed to start due=
 to Pwc ZTE dysfunction// He reset it and  started Gen manualy","Siligap Bo=
ris","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded"=
,"Grid outage, site went down because gen failed to start due to Pwc ZTE dy=
sfunction// He reset it and  started Gen manualy","wilfried.kameni@sagemcom=
.com","1417","13-02-2025 18:48:02","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004332256","ODZ=
A MINKAN EDIBI ASSI","","13-02-2025 17:57:03","13-02-2025 17:47:49","13-02-=
2025 18:46:42","	Grid fluctuation, Site went down because Gen started and s=
topped due to Grid bad voltag and No RCP on site // He bypassed Grid and st=
arted Gen manually","Albran Byorel","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","	Grid fluctuation, Site went down becaus=
e Gen started and stopped due to Grid bad voltag and No RCP on site // He b=
ypassed Grid and started Gen manually","wilfried.kameni@sagemcom.com","555"=
,"13-02-2025 17:57:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_141","NOCINC0004331864","New-Marc=
he-Melen","","13-02-2025 17:12:40","13-02-2025 14:29:01","13-02-2025 20:19:=
45","Cascaded Incident from TTO4365719","Paul BIBOUM","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage, no space to deploy =
a mobil //Grid return Power issue resolved at MTN  at 08:19 AMbut site rema=
ins down at OCM and power reset has done","system","315063","13-02-2025 17:=
12:40","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004331856","Nko=
lbisson usines des eaux 2","","13-02-2025 17:08:56","13-02-2025 15:53:12","=
13-02-2025 17:31:15","Grid outage,site went down because  Gen stopped with =
 alarm"" undervoltage""//He reset Gen card   and Gen manually started","TIE=
NTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid outage,site went down because  Gen stopped with  alarm"" u=
ndervoltage""//He reset Gen card   and Gen manually started","wilfried.kame=
ni@sagemcom.com","4545","13-02-2025 17:08:56","Sagemcom CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0004331843","San=
ta Barbara Yde","","13-02-2025 17:05:34","13-02-2025 17:04:23","13-02-2025 =
19:10:50","No power issue on site; Ubaie: 52.4 V site on Grid  The FME Symp=
horien (691316854) from Huawei is informed.","Delor Telezing","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site; Ubaie: 52.4 V site on Grid  The FME Symphorien (6913=
16854) from Huawei is informed.","wilfried.kameni@sagemcom.com","72","13-02=
-2025 17:05:34","Sagemcom CMR"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0004331778","COR=
NIERS","","13-02-2025 16:49:23","13-02-2025 16:42:36","13-02-2025 18:41:49"=
,"Grid Outage No space to deploy a MDG // Grid Restored Power issue resolve=
d at 06:41 PM But Site remains down after power reset done the FME TX Arman=
d Nguetsa (699949553) is informed","","Grid Supply","Passive","Grid","Natio=
nal Grid - Grid Outage Issue","Grid Outage No space to deploy a MDG // Grid=
 Restored Power issue resolved at 06:41 PM But Site remains down after powe=
r reset done the FME TX Armand Nguetsa (699949553) is informed","wilfried.k=
ameni@sagemcom.com","408","13-02-2025 16:49:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004331471","M=
EFOU ASSI","","13-02-2025 16:16:57","13-02-2025 16:13:39","13-02-2025 16:20=
:40","No power issue on site Ubaie=3D52.6V site On Grid   The Tx FME Fulber=
t(654266068) of huawei is informed.","Fanda Brice","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site Ubaie=3D52.6V site On Grid   The Tx FME Fulbert(654266068) of hu=
awei is informed.","wilfried.kameni@sagemcom.com","200","13-02-2025 16:16:5=
7","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0004331232","Monatele=
","","13-02-2025 15:48:40","13-02-2025 15:38:11","13-02-2025 16:45:20","Cas=
caded Incident from TTO4364976","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage , Site went down because G=
en Ran till fuel shortage//Refueling done","system","267776","13-02-2025 15=
:48:40","Sagemcom CMR"
"Closed Complete","Site Down","T0053","IHS_YND_407","NOCINC0004331209","Mon=
atele MTN","IHS_YND_406","13-02-2025 15:45:39","13-02-2025 15:34:11","13-02=
-2025 16:45:20","Grid outage , Site went down because Gen Ran till fuel sho=
rtage//Refueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Di=
esel Outage","Grid outage , Site went down because Gen Ran till fuel shorta=
ge//Refueling done","wilfried.kameni@sagemcom.com","836","13-02-2025 15:45:=
39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0004331207","E=
toudi","","13-02-2025 15:45:35","13-02-2025 15:42:55","13-02-2025 15:44:44"=
,"Grid outage ,site went down because Gen fails to start//Grid return (Inve=
stigation ongoing)","Fabrice Pouakam","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage ,site went down because Gen fails to=
 start//Grid return (Investigation ongoing)","wilfried.kameni@sagemcom.com"=
,"161","13-02-2025 15:45:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0004331177","S=
oa-II","","13-02-2025 15:42:49","13-02-2025 15:16:28","13-02-2025 16:18:00"=
,"Grid outage, Site went down because Gen failed to start due to  PWC ZTE d=
ysfunctionning// He reset PWC, Site on Grid","Siligap Boris","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, Site=
 went down because Gen failed to start due to  PWC ZTE dysfunctionning// He=
 reset PWC, Site on Grid","wilfried.kameni@sagemcom.com","1582","13-02-2025=
 15:42:49","Sagemcom CMR"
"Closed Complete","Site Down","T0287","IHS_YND_038","NOCINC0004331076","Sia=
ntou Inferieur","","13-02-2025 15:30:43","13-02-2025 15:26:35","13-02-2025 =
18:18:18","Grid outage ,no space to deploy MDG //  Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,no=
 space to deploy MDG //  Grid return","wilfried.kameni@sagemcom.com","248",=
"13-02-2025 15:30:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004331008","M=
efou-Assi","","13-02-2025 15:17:04","13-02-2025 15:03:00","13-02-2025 15:10=
:45","No power issue on site Ubaie=3D54.5V site On Grid  The Tx FME Fulbert=
 (654266068) of Huawei is informed.","Fanda Brice","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site Ubaie=3D54.5V site On Grid  The Tx FME Fulbert (654266068) of Hu=
awei is informed.","wilfried.kameni@sagemcom.com","846","13-02-2025 15:17:0=
4","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004330943","B=
arriere IHS","","13-02-2025 15:11:28","13-02-2025 15:04:13","13-02-2025 15:=
17:34","Site went down due to disfunction of PWC  SS IHS Felix Zambe confir=
med// Site stabilized","Hyemafo Gildas","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Site went down due to disfunction of P=
WC  SS IHS Felix Zambe confirmed// Site stabilized","wilfried.kameni@sagemc=
om.com","436","13-02-2025 15:11:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004330785","N=
kolbong","","13-02-2025 14:57:37","13-02-2025 14:49:19","13-02-2025 15:04:5=
4","Grid outage, site went down before gen start due to poor battery backup=
 // Gen Started automatically","Delor Telezing","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen Started automatically"=
,"wilfried.kameni@sagemcom.com","499","13-02-2025 14:57:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004330762","F=
ouda-New","","13-02-2025 14:54:15","13-02-2025 14:05:04","13-02-2025 14:10:=
53","No power issue on site Ubaie=3D50.5V site on Gen.  The Tx Fme Armand N=
guetsa (691144412) from Huawei is informed.","Delor Telezing","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site Ubaie=3D50.5V site on Gen. The Tx Fme Armand Nguetsa =
(691144412) from Huawei is informed.


","wilfried.kameni@sagemcom.com","2952","13-02-2025 14:54:15","Sagemcom CMR=
"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004330758","Car=
refour Simbock","","13-02-2025 14:53:39","13-02-2025 14:24:31","13-02-2025 =
14:36:50","Grid outage, site went down because Gen overload(17 kva ,170 A)/=
/ He reduced load in site waiting SS IHS  Felix Zambe CONFIRMED","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outa=
ge, site went down because Gen overload(17 kva ,170 A)// He reduced load in=
 site waiting SS IHS  Felix Zambe CONFIRMED","wilfried.kameni@sagemcom.com"=
,"1749","13-02-2025 14:53:39","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004330751","Awa=
e Ewonkan","","13-02-2025 14:52:37","13-02-2025 14:23:24","13-02-2025 14:33=
:49","Site went down due to insufficiency rectifiers (06 rectfiers) due to =
load increase on site IHS SS Alphonse is informed // site stabilized","Albr=
an Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","Sit=
e went down due to insufficiency rectifiers (06 rectfiers) due to load incr=
ease on site IHS SS Alphonse is informed // site stabilized","wilfried.kame=
ni@sagemcom.com","1754","13-02-2025 14:52:37","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004330737","Awa=
e Escalier","","13-02-2025 14:51:26","13-02-2025 14:05:19","13-02-2025 14:3=
2:48","Grid outage, site went down before gen start due to poor battery bac=
kup // gen start automatically","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // gen start automatically","=
wilfried.kameni@sagemcom.com","6121","13-02-2025 14:51:26","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004330732","Man=
guiers Dispensaire","","13-02-2025 14:50:03","13-02-2025 14:26:51","13-02-2=
025 14:31:14","Grid outage.site went down because gen failed to start //Gri=
d return(investigation ongoing)","Fabrice Pouakam","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage.site went down because =
gen failed to start //Grid return(investigation ongoing)","wilfried.kameni@=
sagemcom.com","1393","13-02-2025 14:50:03","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004330720","Pha=
rmacie SION","","13-02-2025 14:48:57","13-02-2025 14:18:49","13-02-2025 14:=
28:19","Grid outage, Site went down before Gen start due to poor backup// G=
en started automaticaly","Paul BIBOUM","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automaticaly","wilfried.kameni@s=
agemcom.com","1809","13-02-2025 14:48:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004330717","C=
omplexe-BEAC","","13-02-2025 14:48:34","13-02-2025 14:32:22","13-02-2025 15=
:09:45","Grid fluctuation, Site went down before Gen start due to poor back=
up// Gen automatically started","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid fluctuation, Site wen=
t down before Gen start due to poor backup// Gen automatically started","wi=
lfried.kameni@sagemcom.com","973","13-02-2025 14:48:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0004330690","D=
joungolo","IHS_YND_711","13-02-2025 14:47:09","13-02-2025 14:10:37","13-02-=
2025 15:20:52","Grid outgae ;Site went down because  Gen CB  (32A) disjunct=
ed // He rearmed CB, Site on Grid","Mboua Thierry","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Load Contactor","Grid outgae ;Site went down becaus=
e  Gen CB  (32A) disjuncted // He rearmed CB, Site on Grid","wilfried.kamen=
i@sagemcom.com","2192","13-02-2025 14:47:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0004330669","H=
-Franco New","","13-02-2025 14:45:46","13-02-2025 14:10:37","13-02-2025 15:=
20:52","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outgae ;Site went down because  Gen CB  (32A) disjunct=
ed // He rearmed CB, Site on Grid","wilfried.kameni@sagemcom.com","287516",=
"13-02-2025 14:45:46","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004330665","An-=
Marche-Melen","IHS_YND_141","13-02-2025 14:44:30","13-02-2025 14:29:01","13=
-02-2025 20:19:45","grid outage, no space to deploy a mobil //Grid return P=
ower issue resolved at MTN  at 08:19 AMbut site remains down at OCM and pow=
er reset has done","","Grid Supply","Passive","Grid","National Grid - Grid =
Outage Issue","grid outage, no space to deploy a mobil //Grid return Power =
issue resolved at MTN  at 08:19 AMbut site remains down at OCM and power re=
set has done","wilfried.kameni@sagemcom.com","9594","13-02-2025 14:44:30","=
Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004330662","Av =
Kennedy","","13-02-2025 14:43:37","13-02-2025 14:27:23","13-02-2025 18:41:2=
1","Grid outage, no space to deploy a mobile gen,// grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, n=
o space to deploy a mobile gen,// grid return","wilfried.kameni@sagemcom.co=
m","974","13-02-2025 14:43:37","Sagemcom CMR"
"Closed Complete","Site Down","T0470","IHS_YND_022","NOCINC0004330620","Mvo=
g Ada","","13-02-2025 14:40:32","13-02-2025 14:27:19","13-02-2025 18:41:05"=
,"Grid outage, no space to deploy a mobil gen//, grid return ","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no =
space to deploy a mobil gen//, grid return ","wilfried.kameni@sagemcom.com"=
,"794","13-02-2025 14:40:32","Sagemcom CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004330611","Eto=
udi2","","13-02-2025 14:39:26","13-02-2025 14:25:16","13-02-2025 15:55:57",=
"Site went down due to insufficiency of rectifier  (Site on 02 Rectifiers )=
   SS IHS   Bernard Atagana is informed and  confimed // Site Stabilized","=
Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to insufficiency of rectifier  (Site on 02 Rectifiers =
)   SS IHS   Bernard Atagana is informed and  confimed // Site Stabilized",=
"wilfried.kameni@sagemcom.com","851","13-02-2025 14:39:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0004330575","Bastos E=
koudou","","13-02-2025 14:35:00","13-02-2025 14:14:05","13-02-2025 15:31:38=
","Cascaded Incident from TTO4364247","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","	Grid Outage No Space to deploy =
a MDG//Grid Restored","system","308858","13-02-2025 14:35:00","Sagemcom CMR=
"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004330572","Lab=
oratoire  Meka","IHS_YND_193","13-02-2025 14:34:22","13-02-2025 14:14:05","=
13-02-2025 15:31:38","	Grid Outage No Space to deploy a MDG//Grid Restored"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","	Gr=
id Outage No Space to deploy a MDG//Grid Restored","wilfried.kameni@sagemco=
m.com","1217","13-02-2025 14:34:22","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004330566","Mes=
sa Carriere","","13-02-2025 14:33:20","13-02-2025 14:12:13","13-02-2025 14:=
42:21","Site went down due to insufficiency of rectifier Fran=E7ois IHS con=
firmed // Site stabilized","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficiency of rectifi=
er Fran=E7ois IHS confirmed // Site stabilized","wilfried.kameni@sagemcom.c=
om","1268","13-02-2025 14:33:20","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004330555","Bit=
eng-Maetur","","13-02-2025 14:30:25","13-02-2025 14:05:19","13-02-2025 17:4=
7:53","Grid outage, Site went down due to Gen overload(20KVA, 260A) SS IHS =
Blaise confirmed// he Reduice the Load and Manually Started the Gen ","Mba =
Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, Site went down due to Gen overload(20KVA, 260A) SS IHS Blaise co=
nfirmed// he Reduice the Load and Manually Started the Gen ","wilfried.kame=
ni@sagemcom.com","1633","13-02-2025 14:30:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004330550","O=
dza II OCM","","13-02-2025 14:29:55","13-02-2025 14:05:15","13-02-2025 14:3=
8:44","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen start automatically","=
mariam.tchonang@sagemcom.com","1482","13-02-2025 14:29:55","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004330549","Nsi=
meyong Terre Rouge","","13-02-2025 14:29:33","13-02-2025 14:04:24","13-02-2=
025 14:44:50","  Site went down because the 05/08 slots  of rectifiers faul=
ty // Site Stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","  Site went down because the 05/08 slots  of recti=
fiers faulty // Site Stabilized","wilfried.kameni@sagemcom.com","1510","13-=
02-2025 14:29:33","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004330508","Ngo=
a Ekelle","","13-02-2025 14:28:24","13-02-2025 14:04:16","13-02-2025 15:42:=
59","Grid outage,site went down because Gen stopped with alarm ""overcurren=
t and insufficience of rectifier(Site on 02 rectifiers) //He reset Gen card=
 and started Gen manually","Paul BIBOUM","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid outage,site went down because Gen stoppe=
d with alarm ""overcurrent and insufficience of rectifier(Site on 02 rectif=
iers) //He reset Gen card and started Gen manually","wilfried.kameni@sagemc=
om.com","1449","13-02-2025 14:28:24","Sagemcom CMR"
"Closed Complete","Site Down","T2585","IHS_YND_744","NOCINC0004330458","Ele=
veur Meec Bon Berger","","13-02-2025 14:25:16","13-02-2025 13:57:08","13-02=
-2025 14:24:12","Grid outage, site went down before gen start due to poor b=
attery backup // Gen start automatically","Siligap Boris","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen start automa=
tically","wilfried.kameni@sagemcom.com","1689","13-02-2025 14:25:16","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004330457","B=
astos Bir","","13-02-2025 14:25:05","13-02-2025 13:59:43","13-02-2025 15:39=
:43","Grid outage, Site went down because Gen start and stopped with ""High=
 temp ""alarm // He added water and manually start the Gen","Mboua Thierry"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","Grid outage, Site went down because Gen start and stopped wi=
th ""High temp ""alarm // He added water and manually start the Gen","maria=
m.tchonang@sagemcom.com","1523","13-02-2025 14:25:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004330436","C=
rf-Nsam","","13-02-2025 14:22:37","13-02-2025 13:55:09","13-02-2025 14:32:2=
4","Site went down Because The Slot off Rectifier is overload // he reduced=
 the load and Gen manually started","MINKA NICOLAS","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Site went down Because The=
 Slot off Rectifier is overload // he reduced the load and Gen manually sta=
rted","mariam.tchonang@sagemcom.com","1649","13-02-2025 14:22:37","Sagemcom=
 CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004330434","BIY=
EMASSI NIKI","","13-02-2025 14:22:13","13-02-2025 13:56:02","13-02-2025 14:=
42:46","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d, F=E9lix Zambe is informed and confirmed","Hyemafo Gildas","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Site went down du=
e to PWC overloaded (12kva 250 A) //Site stabilized, F=E9lix Zambe is infor=
med and confirmed","wilfried.kameni@sagemcom.com","1572","13-02-2025 14:22:=
13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0004330429","Nkolbiss=
on usines des eaux 2","","13-02-2025 14:22:01","13-02-2025 13:56:20","13-02=
-2025 14:00:33","Cascaded Incident from TTO4364083","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Active","Cascade Active","Cascade Active",". No power=
 issue on site u=3D54.5V site on Grid.  MOHAMADOU of Huawei is informed.","=
system","274019","13-02-2025 14:22:01","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0004330422","Nko=
lbisson","IHS_YND_763","13-02-2025 14:20:27","13-02-2025 13:56:20","13-02-2=
025 14:00:33",". No power issue on site u=3D54.5V site on Grid.  MOHAMADOU =
of Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm",". No power i=
ssue on site u=3D54.5V site on Grid.  MOHAMADOU of Huawei is informed.","wi=
lfried.kameni@sagemcom.com","1449","13-02-2025 14:20:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004330420","M=
ontee-Des-Soeurs","","13-02-2025 14:20:12","13-02-2025 13:55:52","13-02-202=
5 14:00:23","No power Issue Site on Grid Ubai =3D54.3 V.   The TX FME Mbah =
Hosiah (674007438) is informed .","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power Iss=
ue Site on Grid Ubai =3D54.3 V.   The TX FME Mbah Hosiah (674007438) is inf=
ormed .","mariam.tchonang@sagemcom.com","1461","13-02-2025 14:20:12","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004330377","M=
imboman-Ecole","","13-02-2025 14:16:23","13-02-2025 13:54:02","13-02-2025 1=
4:32:59","	Grid outage site went down before gen start due to poor battery =
backup // Gen auatomatically started","Mba Lazare Herve","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","	Grid outage site=
 went down before gen start due to poor battery backup // Gen auatomaticall=
y started","mariam.tchonang@sagemcom.com","1342","13-02-2025 14:16:23","Sag=
emcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004330358","Ron=
d Point Express1114","","13-02-2025 14:14:20","13-02-2025 13:54:09","13-02-=
2025 15:22:38","Grid outage, site went down because gen start and stopped w=
ith alarm ""emergency stop"" // He  reset  Gen card  and gen started","Hyem=
afo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop"=
,"Grid outage, site went down because gen start and stopped with alarm ""em=
ergency stop"" // He  reset  Gen card  and gen started","wilfried.kameni@sa=
gemcom.com","1211","13-02-2025 14:14:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004330350","S=
atcom","","13-02-2025 14:12:02","13-02-2025 13:54:35","13-02-2025 14:00:16"=
,"No power issue on site, site on Grid ubaie =3D53.02V . The Tx Fme Armand =
nguetsa (691144412) from Huawei is informed.","Delor Telezing","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site, site on Grid ubaie =3D53.02V .The Tx Fme Armand ngu=
etsa (691144412) from Huawei is informed.

","mariam.tchonang@sagemcom.com","1048","13-02-2025 14:12:02","Sagemcom CMR=
"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004330312","Tou=
ring Club International","","13-02-2025 14:06:02","13-02-2025 13:59:51","13=
-02-2025 14:21:18","Grid Outage Site went down because Gen stopped with ala=
rm undervoltage //He Reset the Gen Card and Gen manually started","Albran B=
yorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 Outage Site went down because Gen stopped with alarm undervoltage //He Res=
et the Gen Card and Gen manually started","wilfried.kameni@sagemcom.com","3=
72","13-02-2025 14:06:02","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004329842","MBA=
LNGONG LYCEE","","13-02-2025 13:30:05","13-02-2025 13:17:50","13-02-2025 13=
:45:57","Grid outage, Site went down because Gen stopped due to overload(9k=
va, 130A) SS IHS Felix Zambe is informed and  confirmed // Grid Restored","=
Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gri=
d outage, Site went down because Gen stopped due to overload(9kva, 130A) SS=
 IHS Felix Zambe is informed and  confirmed // Grid Restored","mariam.tchon=
ang@sagemcom.com","737","13-02-2025 13:30:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004329587","Crf-Mban=
kolo-IHS","","13-02-2025 13:04:21","13-02-2025 12:56:22","13-02-2025 13:00:=
13","Cascaded Incident from TTO4363122","Mboua Thierry","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active// No power issue, site is =
on Grid with Ubaie=3D53,2 V, Brice Tsague(650214096) from Huawei is informe=
d","system","299036","13-02-2025 13:04:21","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004329573","Jea=
n Vespa","IHS_YND_574","13-02-2025 13:01:31","13-02-2025 12:56:22","13-02-2=
025 13:08:13","    ACTIVE//No power issue on site U=3D53,4 V  Site on Grid.=
 OBAMA//655948994  from I- Engenere working on site","Mboua Thierry","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","    ACTIVE//No power issue on site U=3D53,4 V  Site on Grid. OBAMA//6=
55948994  from I- Engenere working on site","wilfried.kameni@sagemcom.com",=
"310","13-02-2025 13:01:31","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0004329513","Sap=
eur Mimboman","","13-02-2025 12:52:00","13-02-2025 12:28:53","13-02-2025 22=
:58:49","Site unstable  due to insufficiency of rectifier Alphonse DEFFO IH=
S confirmed//We add one rectifier for rescue the site ","Mba Lazare Herve",=
"Equipment Repair","Passive","Rectifier","Rectifier Module","Site unstable =
 due to insufficiency of rectifier Alphonse DEFFO IHS confirmed//We add one=
 rectifier for rescue the site ","wilfried.kameni@sagemcom.com","1388","13-=
02-2025 12:52:00","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004329500","Nom=
ayos montee Meche","","13-02-2025 12:47:58","13-02-2025 12:35:40","13-02-20=
25 12:40:46","Active: No power issue, site is on grid with Ubaie=3D53V, Flu=
bert(654266068) from Huawei is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No power issue, site is on grid with Ubaie=3D53V, Flubert(654266068) from H=
uawei is informed","wilfried.kameni@sagemcom.com","739","13-02-2025 12:47:5=
8","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0004329151","M=
vog-Ada_OCM","","13-02-2025 11:46:05","13-02-2025 11:32:59","13-02-2025 18:=
37:44","Grid outage, No space to deploy a mobil gen//grid return awaited","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage, No space to deploy a mobil gen//grid return awaited","wilfried.kame=
ni@sagemcom.com","787","13-02-2025 11:46:05","Sagemcom CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0004329052","Av-=
Germaine","","13-02-2025 11:29:10","13-02-2025 11:11:00","13-02-2025 20:42:=
50","Grid outage, no space to deploy a mobil gen//, grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, n=
o space to deploy a mobil gen//, grid return","wilfried.kameni@sagemcom.com=
","2066","13-02-2025 11:29:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004328618","O=
dza II OCM","","13-02-2025 10:15:32","13-02-2025 10:03:55","13-02-2025 10:2=
5:28","Grid outage, site went down because gen failed to start due to gen c=
ard faulty //Grid return","Albran Byorel","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage, site went down because gen fail=
ed to start due to gen card faulty //Grid return","wilfried.kameni@sagemcom=
.com","699","13-02-2025 10:15:32","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004328593","An-=
Marche-Melen","","13-02-2025 10:11:46","13-02-2025 09:57:35","13-02-2025 11=
:24:14","Grid outage, No space to deploy a mobil gen// grid return ","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e, No space to deploy a mobil gen// grid return ","wilfried.kameni@sagemcom=
.com","907","13-02-2025 10:11:46","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004328386","Pha=
rmacie SION","","13-02-2025 09:42:16","13-02-2025 09:37:05","13-02-2025 09:=
53:24","Grid outage, Site went down before Gen start due to poor backup// G=
en started automaticaly","Paul BIBOUM","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automaticaly","wilfried.kameni@s=
agemcom.com","312","13-02-2025 09:42:16","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004328320","Nko=
lbisson usines des eaux 2","","13-02-2025 09:30:48","13-02-2025 09:22:10","=
13-02-2025 09:29:49","Site went down due to Cb(80A) burnd in PWC // He chan=
ged Cb(80A) by Cb(100A), site on site","TIENTCHEU NZETCHIEU GAEL","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue"=
,"Site went down due to Cb(80A) burnd in PWC // He changed Cb(80A) by Cb(10=
0A), site on site","wilfried.kameni@sagemcom.com","520","13-02-2025 09:30:4=
8","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004328049","MBA=
LNGONG LYCEE","","13-02-2025 08:47:08","13-02-2025 08:43:02","13-02-2025 09=
:37:55","Grid outage, Site went down because  the landlord turned off the g=
en because of the noise//Gen manually started","Fanda Brice","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Emergency Stop","Grid outage, Site went d=
own because  the landlord turned off the gen because of the noise//Gen manu=
ally started","wilfried.kameni@sagemcom.com","247","13-02-2025 08:47:08","S=
agemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004327829","Aka=
k-Nkozoa-MTN-IHS","","13-02-2025 08:03:16","13-02-2025 07:43:58","13-02-202=
5 09:56:27","Gen started due to grid outage, site went down because disfunc=
tionning of PWC// He disconnected controller, site on gen(investigation ong=
oing)","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Gen started due to grid outage, site went down becaus=
e disfunctionning of PWC// He disconnected controller, site on gen(investig=
ation ongoing)","wilfried.kameni@sagemcom.com","3146","13-02-2025 08:03:16"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004327818","Nko=
zoa","","13-02-2025 07:59:45","13-02-2025 07:41:16","13-02-2025 08:14:56","=
Grid outage site went down because Gen stopped with alarm high temp //He ad=
ded water and Gen manually started","Fabrice Pouakam","Equipment Repair","P=
assive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid ou=
tage site went down because Gen stopped with alarm high temp //He added wat=
er and Gen manually started","wilfried.kameni@sagemcom.com","1111","13-02-2=
025 07:59:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0004327435","Bastos E=
koudou","","13-02-2025 06:39:00","13-02-2025 06:18:20","13-02-2025 08:32:20=
","Cascaded Incident from TTO4360564","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage//he deploy 20kva","s=
ystem","272813","13-02-2025 06:39:00","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004327348","Lab=
oratoire  Meka","IHS_YND_193","13-02-2025 06:23:30","13-02-2025 06:18:20","=
13-02-2025 08:32:20","Grid outage//he deploy 20kva","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage//he deploy 20kv=
a","wilfried.kameni@sagemcom.com","311","13-02-2025 06:23:30","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004327238","N=
gouetou","","13-02-2025 05:40:36","13-02-2025 05:36:30","13-02-2025 05:40:2=
1","ACTIVE//No power issue on site, site on Gen The Tx FME Gregoire/6545474=
79/ from huawei is informed and up at 05:45 AM. Repetitive issue","Parker T=
choup","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE//No power issue on site, site on Gen The Tx FME G=
regoire/654547479/ from huawei is informed and up at 05:45 AM. Repetitive i=
ssue","wilfried.kameni@sagemcom.com","247","13-02-2025 05:40:36","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004327152","A=
kak-Nkozoa-MTN-IHS","","13-02-2025 05:14:18","13-02-2025 05:05:51","13-02-2=
025 07:35:09","Grid Outage Site went down because Gen stopped du to low oil=
 pressure // he added oil and Gen manually started","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid Outage S=
ite went down because Gen stopped du to low oil pressure // he added oil an=
d Gen manually started","wilfried.kameni@sagemcom.com","509","13-02-2025 05=
:14:18","Sagemcom CMR"
"Closed Complete","Warning","T1059","IHS_YND_434","NOCINC0004327052","Donga=
","","13-02-2025 04:18:05","","","Hybrid gen site, site went alarm because =
gen stopped with high temp alarm // he added water and manually start the g=
en","Parker Tchoup","Warning","Warning","POWER","Warning - Site on Battery"=
,"Hybrid gen site, site went alarm because gen stopped with high temp alarm=
 // he added water and manually start the gen","danick.tchakouani@sagemcom.=
com","10","13-02-2025 04:18:05","Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0004327043","Don=
ga","","13-02-2025 04:15:39","13-02-2025 04:14:53","13-02-2025 04:14:54","I=
ncorrectly logged Tickets","Parker Tchoup","Incorrectly Logged Tickets","Er=
ror","Error","Error","Incorrectly logged Tickets","danick.tchakouani@sagemc=
om.com","47","13-02-2025 04:15:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004327002","N=
kolfon Cimencam","","13-02-2025 03:58:06","13-02-2025 03:51:55","13-02-2025=
 03:55:17","Active//No power issue, Site on Grid Ubai=3D 52,8V. Notice that=
 it is impacted by Afanoya II The Tx FME Fulbert from Huawei is informed","=
Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 52=
,8V. Notice that it is impacted by Afanoya II The Tx FME Fulbert from Huawe=
i is informed","wilfried.kameni@sagemcom.com","372","13-02-2025 03:58:06","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0004326603","N=
kolso","","13-02-2025 01:12:27","13-02-2025 00:53:18","13-02-2025 01:00:12"=
,"Active// No power issue, site is on Grid with Ubaie=3D54,3V, Mohamadou(69=
1144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue, site is on Grid with Ubaie=3D54,3V, Mohamadou(691144=
435) from Huawei is informed","danick.tchakouani@sagemcom.com","1149","13-0=
2-2025 01:12:27","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004326593","Nsi=
meyong Terre Rouge","","13-02-2025 01:08:27","13-02-2025 00:59:16","13-02-2=
025 01:13:47","Site went down due to PWC Disfunction, SS IHS Fran=E7ois is =
confirmed// Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down due to PWC Disfunc=
tion, SS IHS Fran=E7ois is confirmed// Site stabilized","danick.tchakouani@=
sagemcom.com","551","13-02-2025 01:08:27","Sagemcom CMR"
"Closed Complete","Site Down","T1549","IHS_YND_295","NOCINC0004326583","NGO=
NA","","13-02-2025 01:05:52","13-02-2025 00:59:30","13-02-2025 00:59:31","I=
ncorrectly Logged Tickets","Mba Lazare Herve","Incorrectly Logged Tickets",=
"Error","Error","Error","Incorrectly Logged Tickets","danick.tchakouani@sag=
emcom.com","383","13-02-2025 01:05:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004326448","N=
KOLMEKONG YDE","","13-02-2025 00:31:45","13-02-2025 00:17:08","13-02-2025 0=
0:32:08","Site went down due to insufficience of rectifiers (02/07 disfunct=
ion) SS IHS Bernard Atangana confirmed // Site stabilized","Fabrice Pouakam=
","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went do=
wn due to insufficience of rectifiers (02/07 disfunction) SS IHS Bernard At=
angana confirmed // Site stabilized","danick.tchakouani@sagemcom.com","879"=
,"13-02-2025 00:31:45","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004326436","NKO=
LOSSAN OKOK","","13-02-2025 00:30:18","13-02-2025 00:20:11","13-02-2025 02:=
13:07","Site went down because CB (16A) of rectifiers tripped// CB put back=
 on (investigation ongoing)","Parker Tchoup","Equipment Repair","Passive","=
Rectifier","Rectifier - Circuit Breaker","Site went down because CB (16A) o=
f rectifiers tripped// CB put back on (investigation ongoing)","danick.tcha=
kouani@sagemcom.com","608","13-02-2025 00:30:18","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004326183","Mes=
sa Carriere","","12-02-2025 23:49:27","12-02-2025 23:43:10","12-02-2025 23:=
55:13","Site went down due to insufficiency of rectifier Fran=E7ois IHS con=
firmed  // Site stabilized","Mboua Thierry","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down due to insufficiency of rectif=
ier Fran=E7ois IHS confirmed  // Site stabilized","danick.tchakouani@sagemc=
om.com","378","12-02-2025 23:49:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0004326088","Mobil-Es=
sos","","12-02-2025 23:26:00","12-02-2025 23:22:11","13-02-2025 15:36:48","=
Cascaded Incident from TTO4359082","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage//Grid return","system",=
"348155","12-02-2025 23:26:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0004326089","Crf Corn=
ier","","12-02-2025 23:26:00","12-02-2025 23:22:11","15-02-2025 17:00:47","=
Cascaded Incident from TTO4359082","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Cascaded Incident from TTO4359082",=
"system","229","12-02-2025 23:26:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004326079","M=
adison","IHS_YND_109, IHS_YND_566","12-02-2025 23:23:31","12-02-2025 23:22:=
11","13-02-2025 15:36:48","Grid outage//Grid return","MFOUAGUEGUE MATHIEU",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage//Grid return","danick.tchakouani@sagemcom.com","81","12-02-2025 23:23:=
31","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0004325964","Ess=
os Marche","","12-02-2025 22:55:36","12-02-2025 22:53:24","13-02-2025 09:40=
:09","Grid outage,Site went down due to ACGD overload (20 kva, 240A) //He r=
eduiced the load,siteon DG","Delor Telezing","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage,Site went down due to ACGD overloa=
d (20 kva, 240A) //He reduiced the load,siteon DG","danick.tchakouani@sagem=
com.com","133","12-02-2025 22:55:36","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004325836","NYO=
M 2 IHS","","12-02-2025 22:35:56","12-02-2025 22:29:46","12-02-2025 23:29:4=
7","Grid outage, site went down because gen fails to start due to card ge d=
isfunction // He reset of gen card done and gen started","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
, site went down because gen fails to start due to card ge disfunction // H=
e reset of gen card done and gen started","danick.tchakouani@sagemcom.com",=
"464","12-02-2025 22:35:56","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004325737","OBA=
M NGOLA OCM","","12-02-2025 22:16:35","12-02-2025 22:09:28","12-02-2025 22:=
58:27","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Site went down due to PSC3 dysfonction SS IHS Pascal=
ine confirmed// Site stabilized","wilfried.kameni@sagemcom.com","428","12-0=
2-2025 22:16:35","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004325029","Mes=
sa Carriere","","12-02-2025 20:07:31","12-02-2025 19:47:12","12-02-2025 21:=
43:12","Site went down because 01/03 rectifier faulty SS IHS Fran=E7ois is =
informed and confirmed //Site stabilized","Mboua Thierry","Equipment Repair=
","Passive","Rectifier","Rectifier Module","Site went down because 01/03 re=
ctifier faulty SS IHS Fran=E7ois is informed and confirmed //Site stabilize=
d","wilfried.kameni@sagemcom.com","1220","12-02-2025 20:07:31","Sagemcom CM=
R"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004324492","Aka=
k-Nkozoa-MTN-IHS","","12-02-2025 18:46:36","12-02-2025 18:44:16","12-02-202=
5 20:56:43","	Grid fluctuation, site went down because Gen start and stoppe=
d due to Grid bad voltage // he bypass Grid and manually start the Gen","Fa=
brice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","	Grid fluctuation, site went down because Gen start and stopp=
ed due to Grid bad voltage // he bypass Grid and manually start the Gen","w=
ilfried.kameni@sagemcom.com","141","12-02-2025 18:46:36","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0004324271","Ess=
os Marche","","12-02-2025 18:34:19","12-02-2025 18:31:46","12-02-2025 18:33=
:50","No power issue on site, site on Grid Ubaie=3D52.3 V  Tx fme Armand Ng=
euts/699949553/ from Huawei is Informed","Delor Telezing","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site, site on Grid Ubaie=3D52.3 V  Tx fme Armand Ngeuts/699949=
553/ from Huawei is Informed","wilfried.kameni@sagemcom.com","154","12-02-2=
025 18:34:19","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004323480","Nko=
g-Edzen","","12-02-2025 17:37:32","12-02-2025 17:36:10","12-02-2025 17:40:2=
7","No power issue on site, site on Gen The Tx FME Gregoire/654547479/ from=
 huawei is informed. ","Parker Tchoup","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, =
site on Gen The Tx FME Gregoire/654547479/ from huawei is informed. ","wilf=
ried.kameni@sagemcom.com","83","12-02-2025 17:37:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004322991","MEHANDAN=
","","12-02-2025 17:05:01","12-02-2025 16:54:14","12-02-2025 17:47:31","Cas=
caded Incident from TTO4355566","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to gen card faulty //Grid return","system","292069","=
12-02-2025 17:05:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004322969","O=
dza II OCM","IHS_YND_528","12-02-2025 17:03:37","12-02-2025 16:54:14","12-0=
2-2025 17:47:31","Grid outage, site went down because gen failed to start d=
ue to gen card faulty //We reset card GE and gen manually started ","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage, site went down because gen failed to start due to gen card fault=
y //Grid return","wilfried.kameni@sagemcom.com","564","12-02-2025 17:03:37"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004322787","Eto koss=
 Yde","","12-02-2025 16:45:30","12-02-2025 16:21:14","12-02-2025 16:59:31",=
"Cascaded Incident from TTO4355354","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen start and stopped with high temp alarm // he added water and manually s=
tart the gen","system","272378","12-02-2025 16:45:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004322788","ELOUMDEM=
 CARRIERE 2","","12-02-2025 16:45:30","12-02-2025 16:21:14","12-02-2025 16:=
59:31","Cascaded Incident from TTO4355354","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen start and stopped with high temp alarm // he added water and man=
ually start the gen","system","272378","12-02-2025 16:45:30","Sagemcom CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004322785","Eke=
kam","","12-02-2025 16:45:26","12-02-2025 16:30:19","12-02-2025 16:35:56","=
No power issue hybrid gen site on battery with U=3D54v Fotso(675201448)from=
 IENGINEERING is working onsite","TIENTCHEU NZETCHIEU GAEL","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue hybrid gen site on battery with U=3D54v Fotso(675201448)from IE=
NGINEERING is working onsite","wilfried.kameni@sagemcom.com","908","12-02-2=
025 16:45:26","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004322782","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","12-02-2025 16:44:23","12-02-2025 16:21=
:14","12-02-2025 16:59:31","Grid outage, site went down because gen start a=
nd stopped with high temp alarm // he added water and manually start the ge=
n","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engin=
e Temp - Coolant Level Issue","Grid outage, site went down because gen star=
t and stopped with high temp alarm // he added water and manually start the=
 gen","wilfried.kameni@sagemcom.com","1390","12-02-2025 16:44:23","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004322703","S=
calom-IHS","","12-02-2025 16:24:52","12-02-2025 16:16:42","12-02-2025 16:20=
:39","ACTIVE// No power issue on site Ubaie =3D52.5V site on GridTX Fme Hos=
iah / 674007438// from huawei is informed. ","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No pow=
er issue on site Ubaie =3D52.5V site on GridTX Fme Hosiah / 674007438// fro=
m huawei is informed. ","wilfried.kameni@sagemcom.com","492","12-02-2025 16=
:24:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004322410","E=
kombitie","","12-02-2025 15:52:11","12-02-2025 15:43:03","12-02-2025 15:50:=
57","No power issue site on grid with U=3D54,5v Symphorien from Huawei is i=
nformed","Fabrice Pouakam","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54,5v Symphorien from Huawei is informed","wilfried.kameni@sagemcom.com"=
,"549","12-02-2025 15:52:11","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004322260","Mes=
sa Carriere","","12-02-2025 15:42:29","12-02-2025 15:37:09","12-02-2025 15:=
49:51","Site went down because 01/03 rectifier faulty SS IHS Fran=E7ois is =
informed and confirmed  //Site stabilized","Mboua Thierry","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Site went down because 01/03 r=
ectifier faulty SS IHS Fran=E7ois is informed and confirmed  //Site stabili=
zed","wilfried.kameni@sagemcom.com","321","12-02-2025 15:42:29","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004322254","Crf-Mban=
kolo-IHS","","12-02-2025 15:41:40","12-02-2025 15:26:59","12-02-2025 15:36:=
19","Cascaded Incident from TTO4354691","Mboua Thierry","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active// No power issue, site is =
on Grid with Ubaie=3D53,2 V, Brice Tsague(650214096) from Huawei is informe=
d","system","283003","12-02-2025 15:41:40","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004322202","Jea=
n Vespa","IHS_YND_574","12-02-2025 15:34:29","12-02-2025 15:26:59","12-02-2=
025 21:20:19","Active// No power issue, site is on Grid with Ubaie=3D53,2 V=
, Brice Tsague(650214096) from Huawei is informed","Mboua Thierry","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active// No power issue, site is on Grid with Ubaie=3D53,2 V, Brice Tsa=
gue(650214096) from Huawei is informed","wilfried.kameni@sagemcom.com","451=
","12-02-2025 15:34:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0004322031","N=
kolndongo","","12-02-2025 15:04:01","12-02-2025 14:35:47","12-02-2025 15:30=
:39","Grid fluctuation, Site went down because Gen started and stopped due =
to Grid bad voltage// He bypassed Grid and started Gen manually","MINKA NIC=
OLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, Site went down because Gen started and stopped due t=
o Grid bad voltage// He bypassed Grid and started Gen manually","wilfried.k=
ameni@sagemcom.com","1695","12-02-2025 15:04:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004321627","C=
omplexe-BEAC","","12-02-2025 14:21:35","12-02-2025 13:59:26","12-02-2025 14=
:30:46","No power issue UBaie=3D54.7V  site on Gen The Fme TX Lionel steeve=
 /655184876 of Huawei is informed.","Albran Byorel","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue UBaie=3D54.7V  site on Gen The Fme TX Lionel steeve /655184876 of Huawe=
i is informed.","wilfried.kameni@sagemcom.com","1330","12-02-2025 14:21:35"=
,"Sagemcom CMR"
"Closed Complete","Warning","CTR_155","IHS_YND_505","NOCINC0004321605","Sca=
lom-IHS","","12-02-2025 14:19:25","","","site alarming because Grid outage =
No space to deploy // Grid power return and alarm cleared","","Warning","Wa=
rning","POWER","Warning - Site on Battery","site alarming because Grid outa=
ge No space to deploy // Grid power return and alarm cleared","wilfried.kam=
eni@sagemcom.com","186","12-02-2025 14:19:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004321557","O=
mnisport-Rail","","12-02-2025 14:16:52","12-02-2025 14:06:45","12-02-2025 1=
4:10:48","No power issue on site U=3D54.5 V , Site is on Grid  The FME TX A=
rmand Nguesta (699949553) From Huawei is informed. ","Delor Telezing","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site U=3D54.5 V , Site is on Grid  The FME TX Arma=
nd Nguesta (699949553) From Huawei is informed. ","wilfried.kameni@sagemcom=
.com","608","12-02-2025 14:16:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004321483","E=
kie-Elegance","","12-02-2025 14:08:33","12-02-2025 14:00:25","12-02-2025 16=
:17:25","Grid outage, site went down because gen stopped with 'Emergency st=
op' alarm // He reset the Gen card and Gen manually started","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid out=
age, site went down because gen stopped with 'Emergency stop' alarm // He r=
eset the Gen card and Gen manually started","wilfried.kameni@sagemcom.com",=
"489","12-02-2025 14:08:33","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004321479","Mon=
tee Jouvence","","12-02-2025 14:07:31","12-02-2025 14:01:15","12-02-2025 15=
:03:22","Grid outage gen failed to start due to  alarm""high temp"" //We ad=
d water and gen manually started ","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outa=
ge gen failed to start due to  alarm""high temp"" //We add water and gen ma=
nually started ","el-dalile@sagemcom.com","377","12-02-2025 14:07:31","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0004321475","O=
mnisport 3","","12-02-2025 14:06:06","12-02-2025 13:05:56","12-02-2025 13:1=
0:39","Tx Issue: site on Grid,Ubaie:54.2V; Armand Nguetsa /691-14-44-12 is =
informed.","Delor Telezing","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Tx Issue: site on Grid,Ubaie:54.2V;=
 Armand Nguetsa /691-14-44-12 is informed.","wilfried.kameni@sagemcom.com",=
"3611","12-02-2025 14:06:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0004321455","O=
ssombe","","12-02-2025 14:03:23","12-02-2025 13:54:11","12-02-2025 14:00:55=
","No power issue hybrid gen site on battery with U=3D54v  The Tx FME Grego=
ire/654547479/ from huawei is informed. site up at 01:46 ","Parker Tchoup",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","No power issue hybrid gen site on battery with U=3D54v  The Tx =
FME Gregoire/654547479/ from huawei is informed. site up at 01:46 ","wilfri=
ed.kameni@sagemcom.com","553","12-02-2025 14:03:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004321413","Eto koss=
 Yde","","12-02-2025 13:58:11","12-02-2025 13:39:37","12-02-2025 14:02:08",=
"Cascaded Incident from TTO4353708","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
Gen start and stopped with ""High temp ""alarm // He added water and manual=
ly start the Gen","system","275011","12-02-2025 13:58:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004321414","ELOUMDEM=
 CARRIERE 2","","12-02-2025 13:58:11","12-02-2025 13:39:37","12-02-2025 14:=
02:08","Cascaded Incident from TTO4353708","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
ecause Gen start and stopped with ""High temp ""alarm // He added water and=
 manually start the Gen","system","275010","12-02-2025 13:58:11","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004321361","NKONGKAR=
AK","","12-02-2025 13:53:13","12-02-2025 13:01:25","12-02-2025 13:01:26","C=
ascaded Incident from TTO4353750","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","ACTIVE//No power issue on si=
te, site on Grid The Tx RM  Martial /650252214/ from huawei is informed.","=
system","277421","12-02-2025 13:53:13","Sagemcom CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0004321354","LOB=
O MTN","IHS_YND_713","12-02-2025 13:52:33","12-02-2025 13:01:25","12-02-202=
5 13:01:26","ACTIVE//No power issue on site, site on Grid The Tx RM  Martia=
l /650252214/ from huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid The Tx RM  Martial /650252=
214/ from huawei is informed.","el-dalile@sagemcom.com","3069","12-02-2025 =
13:52:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004321313","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","12-02-2025 13:47:56","12-02-2025 13:=
37:37","12-02-2025 14:02:08","Grid outage, Site went down because Gen start=
 and stopped with ""High temp ""alarm // He added water and manually start =
the Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High=
 Engine Temp - Coolant Level Issue","Grid outage, Site went down because Ge=
n start and stopped with ""High temp ""alarm // He added water and manually=
 start the Gen","wilfried.kameni@sagemcom.com","621","12-02-2025 13:47:56",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004321087","S=
calom-IHS","","12-02-2025 13:22:23","12-02-2025 13:10:08","12-02-2025 13:15=
:02","ACTIVE// No power issue on site Ubaie =3D52.5V site on GridTX Fme Hos=
iah / 674007438// from huawei is informed. ","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No pow=
er issue on site Ubaie =3D52.5V site on GridTX Fme Hosiah / 674007438// fro=
m huawei is informed. ","el-dalile@sagemcom.com","737","12-02-2025 13:22:23=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004320790","V=
allee-Bastos OCM","","12-02-2025 12:49:03","12-02-2025 12:09:38","12-02-202=
5 12:14:16",": ACTIVE No power issue on site Ubaie=3D53,7v site on grid The=
 tx Fme  Eloundou Bertrand //652586578//  from Huawei is informed.","","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm",": ACTIVE No power issue on site Ubaie=3D53,7v site on grid The tx F=
me  Eloundou Bertrand //652586578//  from Huawei is informed.","wilfried.ka=
meni@sagemcom.com","2367","12-02-2025 12:49:03","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0004320131","Odz=
a II","","12-02-2025 11:11:43","12-02-2025 11:04:17","12-02-2025 12:26:50",=
"Grid outage,site went because Gen start and stopped  with  ""failed to loa=
d""  alarm// he reset the Gen card","Albran Byorel","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage,site went because Gen =
start and stopped  with  ""failed to load""  alarm// he reset the Gen card"=
,"wilfried.kameni@sagemcom.com","448","12-02-2025 11:11:43","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004319896","Men=
dong3","","12-02-2025 10:38:59","12-02-2025 10:29:42","12-02-2025 18:35:30"=
,"Grid Outage No Space to deploy a MDG // Grid Restored","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space t=
o deploy a MDG // Grid Restored","wilfried.kameni@sagemcom.com","558","12-0=
2-2025 10:38:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_042","NOCINC0004319626","Mvog-Ada=
_OCM","","12-02-2025 10:01:50","12-02-2025 06:17:35","12-02-2025 06:18:20",=
"Cascaded Incident from TTO4351545","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","Active // No power issue site on grid with U=3D54,=
3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed *BACK Tranking*=
 ","system","279914","12-02-2025 10:01:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004319608","M=
ontee-Jouvence-II","","12-02-2025 09:58:41","12-02-2025 09:46:31","12-02-20=
25 11:33:26","site went down because pwc overload(12k/250A) // he reset it"=
,"Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e Overloaded","site went down because pwc overload(12k/250A) // he reset it=
","el-dalile@sagemcom.com","731","12-02-2025 09:58:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004319599","M=
adison","IHS_YND_566","12-02-2025 09:57:40","12-02-2025 09:45:34","12-02-20=
25 10:07:34","Grid outage // grid return","MFOUAGUEGUE MATHIEU","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went=
 down because Gen stopped with 'Over-Voltage' alarm // He reset the Gen car=
d and Gen manually started","wilfried.kameni@sagemcom.com","727","12-02-202=
5 09:57:40","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0004319586","Ess=
os Marche","","12-02-2025 09:53:23","12-02-2025 09:47:11","12-02-2025 10:10=
:52","Grid outage, site went down because Gen stopped with 'Over-Voltage' a=
larm // He reset the Gen card and Gen manually started","Delor Telezing","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, =
site went down because Gen stopped with 'Over-Voltage' alarm // He reset th=
e Gen card and Gen manually started","el-dalile@sagemcom.com","373","12-02-=
2025 09:53:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0004319564","Olezoa O=
CM","","12-02-2025 09:50:35","12-02-2025 06:17:35","12-02-2025 06:18:20","C=
ascaded Incident from TTO4351545","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Active // No power issue site on grid with U=3D54,3 =
V Tx Fme Armand Ngestsa (691144412) of huawei is informed *BACK Tranking* "=
,"system","279915","12-02-2025 09:50:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0004319567","C-Suprem=
e","","12-02-2025 09:50:35","12-02-2025 06:17:35","12-02-2025 06:18:20","Ca=
scaded Incident from TTO4351545","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","Active // No power issue site on grid with U=3D54,3 V=
 Tx Fme Armand Ngestsa (691144412) of huawei is informed *BACK Tranking* ",=
"system","279913","12-02-2025 09:50:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_023","NOCINC0004319566","Montesqu=
ieux","","12-02-2025 09:50:35","12-02-2025 06:17:35","12-02-2025 06:18:20",=
"Cascaded Incident from TTO4351545","Paul BIBOUM","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active // No power issue site on grid w=
ith U=3D54,3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed *BAC=
K Tranking* ","system","279913","12-02-2025 09:50:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0004319565","Acropole=
","","12-02-2025 09:50:35","12-02-2025 06:17:35","12-02-2025 06:18:20","Cas=
caded Incident from TTO4351545","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active // No power issue site on grid wit=
h U=3D54,3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed *BACK =
Tranking* ","system","279913","12-02-2025 09:50:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_564","NOCINC0004319563","Mvog Mbi=
 New","","12-02-2025 09:50:34","12-02-2025 06:17:35","12-02-2025 06:18:20",=
"Cascaded Incident from TTO4351545","MINKA NICOLAS","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active // No power issue site on grid=
 with U=3D54,3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed *B=
ACK Tranking* ","system","279914","12-02-2025 09:50:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0004319549","C=
rf Cornier","","12-02-2025 09:48:56","12-02-2025 09:45:34","12-02-2025 10:0=
7:34","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, site went down because Gen stopped with 'Over-Vo=
ltage' alarm // He reset the Gen card and Gen manually started","wilfried.k=
ameni@sagemcom.com","267528","12-02-2025 09:48:56","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004319489","Aha=
la Echangeur","","12-02-2025 09:40:18","12-02-2025 09:38:08","12-02-2025 18=
:44:30","Site went down because GEN Overload9kva//150A SS IHS Felix Zambe  =
is informed and confirmed//Grid power return","MINKA NICOLAS","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Site went down because GEN Ov=
erload9kva//150A SS IHS Felix Zambe  is informed and confirmed//Grid power =
return","wilfried.kameni@sagemcom.com","131","12-02-2025 09:40:18","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0004319401","N=
kolndongo","IHS_YND_042, IHS_YND_564, IHS_YND_055, IHS_YND_036, IHS_YND_023=
, IHS_YND_021","12-02-2025 09:31:25","12-02-2025 06:17:35","12-02-2025 06:1=
8:20","Active // No power issue site on grid with U=3D54,3 V Tx Fme Armand =
Ngestsa (691144412) of huawei is informed *BACK Tranking* ","MINKA NICOLAS"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active // No power issue site on grid with U=3D54,3 V Tx Fme A=
rmand Ngestsa (691144412) of huawei is informed *BACK Tranking* ","el-dalil=
e@sagemcom.com","11631","12-02-2025 09:31:25","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004319337","ODZ=
A CITE MBIA","","12-02-2025 09:16:19","12-02-2025 09:06:09","12-02-2025 09:=
56:21","Grid outage site went down because Gen stopped with ''Alarm' Over-C=
urrent // he reset the Gen Card and manually started","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site=
 went down because Gen stopped with ''Alarm' Over-Current // he reset the G=
en Card and manually started","wilfried.kameni@sagemcom.com","611","12-02-2=
025 09:16:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004319224","M=
endong vallee","","12-02-2025 08:57:54","12-02-2025 08:54:33","12-02-2025 0=
9:46:55","Site went down due to gen Overload(20KVA; 300A)   IHS F=E9lix Zam=
b=E9 is informed and confirmed//he Reduice the Load and Manually Started th=
e Gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overlo=
ad","Site went down due to gen Overload(20KVA; 300A)   IHS F=E9lix Zamb=E9 =
is informed and confirmed//he Reduice the Load and Manually Started the Gen=
","wilfried.kameni@sagemcom.com","202","12-02-2025 08:57:54","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004319131","Com=
plex Beac II","","12-02-2025 08:36:38","12-02-2025 08:33:24","12-02-2025 09=
:42:12","Grid outage, Site went down because Gen failed to start due to Gen=
 Battery discharged // He started Gen manualy with external battery(deep in=
vestigation ongoing)","Albran Byorel","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Generator Faulty","Grid outage, Site went down because Gen faile=
d to start due to Gen Battery discharged // He started Gen manualy with ext=
ernal battery(deep investigation ongoing)","wilfried.kameni@sagemcom.com","=
195","12-02-2025 08:36:38","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004318887","Nsi=
meyong Terre Rouge","","12-02-2025 07:34:39","12-02-2025 07:32:26","12-02-2=
025 08:38:22","Site went down due to PWC Disfunction, SS IHS Fran=E7ois is =
informed // Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down due to PWC Disfunc=
tion, SS IHS Fran=E7ois is informed // Site stabilized","el-dalile@sagemcom=
.com","134","12-02-2025 07:34:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004318880","A=
kak-Nkozoa-MTN-IHS","","12-02-2025 07:32:44","12-02-2025 07:30:22","12-02-2=
025 07:33:08","Grid fluctuation, Site went down because Gen started and sto=
pped due to Grid bad voltage// He bypassed Grid and started Gen manualy","F=
abrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid fluctuation, Site went down because Gen started and sto=
pped due to Grid bad voltage// He bypassed Grid and started Gen manualy","w=
ilfried.kameni@sagemcom.com","144","12-02-2025 07:32:44","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004318827","Av =
Kennedy","","12-02-2025 07:22:02","12-02-2025 07:19:26","12-02-2025 16:06:4=
8","Grid Outage No Space to deploy a MDG // Grid Restored","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space=
 to deploy a MDG // Grid Restored","wilfried.kameni@sagemcom.com","157","12=
-02-2025 07:22:02","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004318776","OBA=
M NGOLA OCM","","12-02-2025 07:09:52","12-02-2025 07:06:04","12-02-2025 08:=
08:39","Grid outage, site went down because Gen ran untill fuel shortage //=
 Refueling Done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down because Gen ran untill fuel shortage //=
 Refueling Done","wilfried.kameni@sagemcom.com","229","12-02-2025 07:09:52"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0004318013","Nkoa Ayo=
s","","12-02-2025 03:22:50","12-02-2025 02:49:08","12-02-2025 02:55:24","Ca=
scaded Incident from TTO4349809","MINKA NICOLAS","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active // No power issue site on grid wi=
th U=3D54,3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed ","sy=
stem","278017","12-02-2025 03:22:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0004317946","C-Suprem=
e","","12-02-2025 03:01:12","12-02-2025 02:49:08","12-02-2025 02:55:24","Ca=
scaded Incident from TTO4349809","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","Active // No power issue site on grid with U=3D54,3 V=
 Tx Fme Armand Ngestsa (691144412) of huawei is informed ","system","278016=
","12-02-2025 03:01:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_023","NOCINC0004317945","Montesqu=
ieux","","12-02-2025 03:01:12","12-02-2025 02:49:08","12-02-2025 02:55:24",=
"Cascaded Incident from TTO4349809","Paul BIBOUM","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active // No power issue site on grid w=
ith U=3D54,3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed ","s=
ystem","278015","12-02-2025 03:01:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0004317944","Acropole=
","","12-02-2025 03:01:11","12-02-2025 02:49:08","12-02-2025 02:55:24","Cas=
caded Incident from TTO4349809","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active // No power issue site on grid wit=
h U=3D54,3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed ","sys=
tem","278016","12-02-2025 03:01:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0004317943","Olezoa O=
CM","","12-02-2025 03:01:11","12-02-2025 02:49:08","12-02-2025 02:55:24","C=
ascaded Incident from TTO4349809","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Active // No power issue site on grid with U=3D54,3 =
V Tx Fme Armand Ngestsa (691144412) of huawei is informed ","system","27801=
7","12-02-2025 03:01:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_042","NOCINC0004317941","Mvog-Ada=
_OCM","","12-02-2025 03:01:11","12-02-2025 02:49:08","12-02-2025 02:55:24",=
"Cascaded Incident from TTO4349809","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","Active // No power issue site on grid with U=3D54,=
3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed ","system","278=
015","12-02-2025 03:01:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_564","NOCINC0004317942","Mvog Mbi=
 New","","12-02-2025 03:01:11","12-02-2025 02:49:08","12-02-2025 02:55:24",=
"Cascaded Incident from TTO4349809","MINKA NICOLAS","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active // No power issue site on grid=
 with U=3D54,3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed ",=
"system","278017","12-02-2025 03:01:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0004317930","N=
kolndongo","IHS_YND_042, IHS_YND_564, IHS_YND_055, IHS_YND_036, IHS_YND_023=
, IHS_YND_067, IHS_YND_021","12-02-2025 02:55:03","12-02-2025 02:49:08","12=
-02-2025 02:55:24","Active // No power issue site on grid with U=3D54,3 V T=
x Fme Armand Ngestsa (691144412) of huawei is informed ","MINKA NICOLAS","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active // No power issue site on grid with U=3D54,3 V Tx Fme Arma=
nd Ngestsa (691144412) of huawei is informed ","danick.tchakouani@sagemcom.=
com","356","12-02-2025 02:55:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004317784","N=
gouetou","","12-02-2025 02:10:46","12-02-2025 02:06:38","12-02-2025 02:06:3=
9","ACTIVE//No power issue on site, site on Gen The Tx FME Gregoire/6545474=
79/ from huawei is informed. Repetitive issue","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE//No power issue on site, site on Gen The Tx FME Gregoire/654547479/ =
from huawei is informed. Repetitive issue","danick.tchakouani@sagemcom.com"=
,"249","12-02-2025 02:10:46","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004317764","Obo=
bogo","","12-02-2025 02:02:32","12-02-2025 01:59:23","12-02-2025 02:05:57",=
"Grid outage, Site went down before Gen start due to poor backup// Gen Manu=
ally started","MINKA NICOLAS","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup// Gen Manually started","wilfried.kameni@sagemcom.com",=
"190","12-02-2025 02:02:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0004317371","Crf Corn=
ier","","12-02-2025 00:16:20","11-02-2025 23:33:58","12-02-2025 01:11:11","=
Cascaded Incident from TTO4349160","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because CB(125*80A) =
tripped in PWC// CB put back on","system","282527","12-02-2025 00:16:20","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0004317370","Mobil-Es=
sos","","12-02-2025 00:16:20","11-02-2025 23:33:58","12-02-2025 01:11:11","=
Cascaded Incident from TTO4349160","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because CB(125*80A) =
tripped in PWC// CB put back on","system","282527","12-02-2025 00:16:20","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004317367","M=
adison","IHS_YND_109, IHS_YND_566","12-02-2025 00:15:07","11-02-2025 23:33:=
58","12-02-2025 01:11:11","Site went down because CB(125*80A) tripped in PW=
C// CB put back on","MFOUAGUEGUE MATHIEU","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down because=
 CB(125*80A) tripped in PWC// CB put back on","wilfried.kameni@sagemcom.com=
","2470","12-02-2025 00:15:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0004317071","Bastos E=
koudou","","11-02-2025 23:07:50","11-02-2025 22:49:57","12-02-2025 11:54:33=
","Cascaded Incident from TTO4348737","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, No space to deploy =
MDG // Grid return","system","313889","11-02-2025 23:07:50","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004317002","Lab=
oratoire  Meka","IHS_YND_193","11-02-2025 22:58:08","11-02-2025 22:49:57","=
12-02-2025 11:54:33","Grid outage//he deploy 20kva","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage//he deploy 20kv=
a","wilfried.kameni@sagemcom.com","492","11-02-2025 22:58:08","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0004316686","S=
apeur Mimboman","","11-02-2025 22:03:46","11-02-2025 22:01:42","11-02-2025 =
23:45:42","Site unstable  due to insufficiency of rectifier Alphonse DEFFO =
IHS confirmed // site stabilized","Mba Lazare Herve","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","Site unstable  due to insufficiency =
of rectifier Alphonse DEFFO IHS confirmed // site stabilized","wilfried.kam=
eni@sagemcom.com","125","11-02-2025 22:03:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004316584","N=
kolbong","","11-02-2025 21:48:38","11-02-2025 21:37:14","11-02-2025 22:26:3=
2","Grid outage, site went down before gen start due to poor battery backup=
 // Grid power return(Site up at OCM after power reset done)","Delor Telezi=
ng","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery L=
ow","Grid outage, site went down before gen start due to poor battery backu=
p // Grid power return(Site up at OCM after power reset done)","wilfried.ka=
meni@sagemcom.com","685","11-02-2025 21:48:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0004316567","Mobil-Es=
sos","","11-02-2025 21:45:20","11-02-2025 21:33:54","11-02-2025 22:33:06","=
Cascaded Incident from TTO4348207","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage// Grid return","system"=
,"275353","11-02-2025 21:45:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0004316568","Crf Corn=
ier","","11-02-2025 21:45:20","11-02-2025 21:33:54","11-02-2025 22:33:06","=
Cascaded Incident from TTO4348207","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage// Grid return","system"=
,"275353","11-02-2025 21:45:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004316559","M=
adison","IHS_YND_109, IHS_YND_566","11-02-2025 21:44:06","11-02-2025 21:33:=
54","11-02-2025 22:33:06","Grid outage// Grid return","MFOUAGUEGUE MATHIEU"=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage// Grid return","wilfried.kameni@sagemcom.com","613","11-02-2025 21:44=
:06","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004316159","SAA=
 Entrance","","11-02-2025 21:12:38","11-02-2025 21:06:24","11-02-2025 21:06=
:25","Active//No power issue on site Ubaie=3D54.1V site on Gen Tx FME Grego=
ire /654547479/Huawei is informed.","Parker Tchoup","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie=3D54.1V site on Gen Tx FME Gregoire /654547479/Hu=
awei is informed.","ludovic-anselme.mouliom-mapoure@sagemcom","375","11-02-=
2025 21:12:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004316051","ELOUMDEM=
 CARRIERE 2","","11-02-2025 20:52:21","11-02-2025 20:48:36","11-02-2025 20:=
51:01","Cascaded Incident from TTO4347694","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down du to insuffic=
iency of rectifier, IHS SS FELIX ZAMBE is informed // site stabilized","sys=
tem","263744","11-02-2025 20:52:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004316050","Eto koss=
 Yde","","11-02-2025 20:52:20","11-02-2025 20:48:36","11-02-2025 20:51:01",=
"Cascaded Incident from TTO4347694","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down du to insufficiency o=
f rectifier, IHS SS FELIX ZAMBE is informed // site stabilized","system","2=
63744","11-02-2025 20:52:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004316040","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","11-02-2025 20:50:44","11-02-2025 20:48=
:36","11-02-2025 20:51:01","Site went down du to insufficiency of rectifier=
, IHS SS FELIX ZAMBE is informed // site stabilized","Fanda Brice","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","Site went down du to i=
nsufficiency of rectifier, IHS SS FELIX ZAMBE is informed // site stabilize=
d","ludovic-anselme.mouliom-mapoure@sagemcom","130","11-02-2025 20:50:44","=
Sagemcom CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0004315964","Eto=
ug ebe Meweulo","","11-02-2025 20:30:18","11-02-2025 20:07:06","11-02-2025 =
21:43:45","Grid fluctuation site went down because Gen started and stopped =
due to Grid bad voltage and RCP on site // He bypass the Grid and Gen manua=
lly started","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid=
 - Phase Controller Faulty","Grid fluctuation site went down because Gen st=
arted and stopped due to Grid bad voltage and RCP on site // He bypass the =
Grid and Gen manually started","ludovic-anselme.mouliom-mapoure@sagemcom","=
5795","11-02-2025 20:30:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004315943","N=
kolfon Cimencam","","11-02-2025 20:26:30","11-02-2025 19:59:04","11-02-2025=
 20:00:35","Active//No power issue, Site on Grid Ubai=3D 50,8V. Notice that=
 it is impacted by Afanoya II Flubert from Huawei is informed","Hyemafo Gil=
das","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active//No power issue, Site on Grid Ubai=3D 50,8V. Notice=
 that it is impacted by Afanoya II Flubert from Huawei is informed","ludovi=
c-anselme.mouliom-mapoure@sagemcom","1647","11-02-2025 20:26:30","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004315934","N=
kolbong","","11-02-2025 20:25:04","11-02-2025 19:19:46","11-02-2025 21:14:2=
8","Grid outage, Site went down before Gen start due to poor  backup// Grid=
 return. Power issue resolved at 07:22 PM But Site remains down at OCM. Sit=
e Up after power reset","Delor Telezing","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor  backup// Grid return. Power issue resolved at 07:2=
2 PM But Site remains down at OCM. Site Up after power reset","ludovic-anse=
lme.mouliom-mapoure@sagemcom","3919","11-02-2025 20:25:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004315895","S=
imbock OCM","","11-02-2025 20:18:28","11-02-2025 19:32:23","12-02-2025 07:4=
0:10","Access issue during the Night due to Landlord(Grid Outage Site went =
down Because Gen Failed to Start //Grid Restored) Deep investigation ongoin=
g ","Hyemafo Gildas","Access Denial","Lease Or Legal","Landlord Related Iss=
ues","Access Issue - Land Lord","Access issue during the Night due to Landl=
ord(Grid Outage Site went down Because Gen Failed to Start //Grid Restored)=
 Deep investigation ongoing ","wilfried.kameni@sagemcom.com","2766","11-02-=
2025 20:18:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004315856","SOA VILL=
AGE","","11-02-2025 20:12:30","11-02-2025 20:07:46","11-02-2025 20:53:33","=
Cascaded Incident from TTO4347476","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive"," Grid outage, Site went down becaus=
e Gen stopped due to overload(13kva, 190A) SS IHS Blaise Raoul is  confirme=
d // We reduce load and gen manually started","system","266179","11-02-2025=
 20:12:30","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004315850","SOA=
 TOWN","IHS_YND_323","11-02-2025 20:11:56","11-02-2025 20:04:46","11-02-202=
5 20:53:33"," Grid outage, Site went down because Gen stopped due to overlo=
ad(13kva, 190A) SS IHS Blaise Raoul is  confirmed // We reduce load and gen=
 manually started","Siligap Boris","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload"," Grid outage, Site went down because Gen stopped due to =
overload(13kva, 190A) SS IHS Blaise Raoul is  confirmed // We reduce load a=
nd gen manually started","ludovic-anselme.mouliom-mapoure@sagemcom","1080",=
"11-02-2025 20:11:56","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004315621","Mes=
sa Carriere","","11-02-2025 19:39:58","11-02-2025 19:24:47","11-02-2025 19:=
42:20","Site went down due to insufficiency of rectifier Fran=E7ois IHS con=
firmed// Site stablized","Mboua Thierry","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Site went down due to insufficiency of rectifier=
 Fran=E7ois IHS confirmed// Site stablized","wilfried.kameni@sagemcom.com",=
"912","11-02-2025 19:39:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004315371","M=
essassi 2","","11-02-2025 19:00:31","11-02-2025 18:52:15","11-02-2025 18:58=
:34","Grid fluctuation, Site went down because Gen started and stopped due =
to Grid bad voltage and no RCP // Grid stabilized","Fabrice Pouakam","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation, Site went down because Gen started and stopped due to Grid bad v=
oltage and no RCP // Grid stabilized","wilfried.kameni@sagemcom.com","497",=
"11-02-2025 19:00:31","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004315336","Aka=
k-Nkozoa-MTN-IHS","","11-02-2025 18:54:00","11-02-2025 18:51:42","11-02-202=
5 19:15:30","Grid fluctuation, Site went down because Gen started and stopp=
ed due to Grid bad voltage// He bypassed Grid and started Gen manualy","Fab=
rice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, Site went down because Gen started and stopp=
ed due to Grid bad voltage// He bypassed Grid and started Gen manualy","lud=
ovic-anselme.mouliom-mapoure@sagemcom","139","11-02-2025 18:54:00","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004315196","N=
KOLMEKONG YDE","","11-02-2025 18:32:34","11-02-2025 16:40:27","11-02-2025 1=
6:45:45","Active//No Power issue on Site, site on Grid and Ubaie=3D53,4 V, =
The FME TX RM Alain(691144423) from Huawei is informed. Notice that we have=
 CB at BTS OCM faulty","Fabrice Pouakam","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active//No Power issue=
 on Site, site on Grid and Ubaie=3D53,4 V, The FME TX RM Alain(691144423) f=
rom Huawei is informed. Notice that we have CB at BTS OCM faulty","wilfried=
.kameni@sagemcom.com","6728","11-02-2025 18:32:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004314988","N=
koabang2","","11-02-2025 17:52:15","11-02-2025 17:44:05","11-02-2025 20:13:=
54","Grid fluctuation, Site went down because Gen failed to start due to ba=
d voltage No Rcp// He bypassed Grid and started Gen manualy","Mba Lazare He=
rve","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, Site went down because Gen failed to start due to bad=
 voltage No Rcp// He bypassed Grid and started Gen manualy","wilfried.kamen=
i@sagemcom.com","491","11-02-2025 17:52:15","Sagemcom CMR"
"Closed Complete","Site Down","T1652","IHS_YND_273","NOCINC0004314775","Nko=
lbi-Boss","","11-02-2025 17:26:27","11-02-2025 17:01:23","11-02-2025 17:02:=
15","No power issue site on grid with U=3D53.4v Antoine(697768366) from IEn=
gineering is working on site ","TIENTCHEU NZETCHIEU GAEL","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue site on grid with U=3D53.4v Antoine(697768366) from IEngineering =
is working on site ","wilfried.kameni@sagemcom.com","1505","11-02-2025 17:2=
6:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004314762","Mimboman=
4","","11-02-2025 17:25:41","11-02-2025 17:14:03","11-02-2025 18:28:46","Ca=
scaded Incident from TTO4346192","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to dysjunction =
of CB(63 A) which is faulty  // He change with CB (125 A)","system","276376=
","11-02-2025 17:25:41","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004314749","Nko=
lo II New","IHS_YND_266","11-02-2025 17:24:09","11-02-2025 17:14:03","11-02=
-2025 18:28:46","Site went down due to dysjunction of CB(63 A) which is fau=
lty  // He change with CB (125 A) site on grid ","Mba Lazare Herve","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issu=
e","Site went down due to dysjunction of CB(63 A) which is faulty  // He ch=
ange with CB (125 A) site on grid ","wilfried.kameni@sagemcom.com","608","1=
1-02-2025 17:24:09","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004314368","Men=
dong vallee","","11-02-2025 17:00:38","11-02-2025 16:57:01","11-02-2025 16:=
59:00","Site went down because due to insufficient rectifiers SS HIS Felix =
confirmed//site stabilised","Fanda Brice","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down because due to insufficient rect=
ifiers SS HIS Felix confirmed//site stabilised","ludovic-anselme.mouliom-ma=
poure@sagemcom","218","11-02-2025 17:00:38","Sagemcom CMR"
"Closed Complete","Warning","CTR_154","IHS_YND_518","NOCINC0004314262","Mon=
tee-Jouvence-II","","11-02-2025 16:49:00","","","Site alarmes because the S=
S IHS Felix Zamb=E9 are working on Site// end off Work","Hyemafo Gildas","W=
arning","Warning","POWER","Warning - Planned Activity - Passive","Site alar=
mes because the SS IHS Felix Zamb=E9 are working on Site// end off Work","l=
udovic-anselme.mouliom-mapoure@sagemcom","20","11-02-2025 16:49:00","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004314159","M=
ontee-Jouvence-II","","11-02-2025 16:32:48","11-02-2025 16:31:40","11-02-20=
25 17:07:31","Site went due to work: SS IHS Fran=E7ois Ndoungou working on =
site// End of work ","Hyemafo Gildas","Installation Activity","Passive","Pl=
anned Activity","Installation Activity","Site went due to work: SS IHS Fran=
=E7ois Ndoungou working on site// End of work ","ludovic-anselme.mouliom-ma=
poure@sagemcom","69","11-02-2025 16:32:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004314057","N=
KOLMEKONG YDE","","11-02-2025 16:08:20","11-02-2025 15:58:14","11-02-2025 1=
6:39:21","Site went down due to insufficience of rectifiers (02/07 disfunct=
ion) SS IHS Bernard Atangana confirmed// He reduiced the load and site stab=
ilized.Power issue resolved at 04:38 PM but site remains dow","Fabrice Poua=
kam","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went=
 down due to insufficience of rectifiers (02/07 disfunction) SS IHS Bernard=
 Atangana confirmed// He reduiced the load and site stabilized.Power issue =
resolved at 04:38 PM but site remains down RM Alain (691144423) from Huawei=
 is informed","wilfried.kameni@sagemcom.com","607","11-02-2025 16:08:20","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004314031","ELOUMDEM=
 CARRIERE 2","","11-02-2025 16:00:51","11-02-2025 15:55:33","11-02-2025 16:=
05:00","Cascaded Incident from TTO4345381","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down du to insuffic=
iency of rectifier, IHS SS FELIX ZAMBE is informed // site stabilized","sys=
tem","266673","11-02-2025 16:00:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004314030","Eto koss=
 Yde","","11-02-2025 16:00:50","11-02-2025 15:55:33","11-02-2025 16:05:00",=
"Cascaded Incident from TTO4345381","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down du to insufficiency o=
f rectifier, IHS SS FELIX ZAMBE is informed // site stabilized","system","2=
66674","11-02-2025 16:00:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004314022","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","11-02-2025 15:59:46","11-02-2025 15:55=
:33","11-02-2025 16:05:00","Site went down du to insufficiency of rectifier=
, IHS SS FELIX ZAMBE is informed // site stabilized","Fanda Brice","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","Site went down du to i=
nsufficiency of rectifier, IHS SS FELIX ZAMBE is informed // site stabilize=
d","ludovic-anselme.mouliom-mapoure@sagemcom","255","11-02-2025 15:59:46","=
Sagemcom CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0004313930","Bye=
massi Carrefour","","11-02-2025 15:49:07","11-02-2025 15:45:46","11-02-2025=
 17:25:08","Site went down because CB(125A) tripped in PWC who feeds equipm=
ents MTN // CB put back on","Paul BIBOUM","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down because=
 CB(125A) tripped in PWC who feeds equipments MTN // CB put back on","ludov=
ic-anselme.mouliom-mapoure@sagemcom","202","11-02-2025 15:49:07","Sagemcom =
CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004313712","OBA=
M NGOLA OCM","","11-02-2025 15:30:11","11-02-2025 15:24:40","11-02-2025 15:=
44:58","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Site went down due to PSC3 dysfonction SS IHS Pascal=
ine confirmed// Site stabilized","ludovic-anselme.mouliom-mapoure@sagemcom"=
,"332","11-02-2025 15:30:11","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004313691","Mes=
sa Carriere","","11-02-2025 15:26:34","11-02-2025 15:20:22","11-02-2025 15:=
32:20","Site went down due to insufficiency of rectifier Fran=E7ois IHS con=
firmed // Site stabilized","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficiency of rectifi=
er Fran=E7ois IHS confirmed // Site stabilized","ludovic-anselme.mouliom-ma=
poure@sagemcom","373","11-02-2025 15:26:34","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004313509","MBA=
LNGONG LYCEE","","11-02-2025 14:54:26","11-02-2025 14:50:16","11-02-2025 16=
:06:01","Grid outage, site went down due to gen overload (9kva, 130A) IHS S=
S Felix ZAMBE is informed and confirmed// He reduced the load and gen manua=
lly started","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, site went down due to gen overload (9kva, 130A) IHS=
 SS Felix ZAMBE is informed and confirmed// He reduced the load and gen man=
ually started","ludovic-anselme.mouliom-mapoure@sagemcom","252","11-02-2025=
 14:54:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004313501","B=
arriere IHS","","11-02-2025 14:52:54","11-02-2025 14:48:50","11-02-2025 14:=
53:33","Site went down due to disfunction of PWC  SS IHS Felix Zambe confir=
med// Site stabilized","Hyemafo Gildas","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","Site went down due to disfunction of P=
WC  SS IHS Felix Zambe confirmed// Site stabilized","wilfried.kameni@sagemc=
om.com","246","11-02-2025 14:52:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004313465","N=
KOLMEKONG YDE","","11-02-2025 14:44:31","11-02-2025 14:36:27","11-02-2025 1=
5:46:07","Site went down due to insufficience of rectifiers (02/07 disfunct=
ion) SS IHS Bernard Atangana confirmed// He reduced 01 rack of battery","Fa=
brice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to insufficience of rectifiers (02/07 disfunction) SS I=
HS Bernard Atangana confirmed// He reduced 01 rack of battery","wilfried.ka=
meni@sagemcom.com","486","11-02-2025 14:44:31","Sagemcom CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004313408","Eke=
kam","","11-02-2025 14:36:43","11-02-2025 14:15:32","11-02-2025 14:20:14","=
Active// No power issue, site is on Battery with Ubaie=3D51,9V, Mohamadou(6=
91144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive// No power issue, site is on Battery with Ubaie=3D51,9V, Mohamadou(69=
1144435) from Huawei is informed","wilfried.kameni@sagemcom.com","1272","11=
-02-2025 14:36:43","Sagemcom CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0004313137","Ngo=
usso-Savana","","11-02-2025 14:04:38","11-02-2025 13:57:40","11-02-2025 13:=
58:11","Active// No power issue, Site on Grid Ubai=3D51.4V FME DIN CHARLY /=
656097386// From  TELIS working on site (ODU Updrage)","Siligap Boris","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active// No power issue, Site on Grid Ubai=3D51.4V FME DIN CHARLY /=
656097386// From  TELIS working on site (ODU Updrage)","el-dalile@sagemcom.=
com","419","11-02-2025 14:04:38","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004313060","BIY=
EMASSI NIKI","","11-02-2025 13:55:03","11-02-2025 13:46:47","11-02-2025 14:=
00:15","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d, F=E9lix Zambe is confirmed","Hyemafo Gildas","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Site went down due to PWC over=
loaded (12kva 250 A) //Site stabilized, F=E9lix Zambe is confirmed","wilfri=
ed.kameni@sagemcom.com","497","11-02-2025 13:55:03","Sagemcom CMR"
"Closed Complete","Warning","T0139","IHS_YND_381","NOCINC0004312901","Boumn=
yebel","","11-02-2025 13:32:58","","","Site is on Battery due to Grid Outag=
e // Gen start automatically","Kemeni Franklin","Warning","Warning","POWER"=
,"Warning - Site on Battery","Site is on Battery due to Grid Outage // Gen =
start automatically","wilfried.kameni@sagemcom.com","1147","11-02-2025 13:3=
2:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0004312817","S=
apeur Mimboman","","11-02-2025 13:20:00","11-02-2025 12:29:34","11-02-2025 =
14:36:43","Site went down due to insufficiency of rectifier Alphonse DEFFO =
IHS confirmed// Site stabilized","Mba Lazare Herve","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Site went down due to insufficiency o=
f rectifier Alphonse DEFFO IHS confirmed// Site stabilized","el-dalile@sage=
mcom.com","3028","11-02-2025 13:20:00","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004312658","Men=
dong vallee","","11-02-2025 12:59:38","11-02-2025 12:56:33","11-02-2025 12:=
58:45","Site went down because due to insufficient rectifiers SS HIS Felix =
confirmed//site stabilised","Fanda Brice","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down because due to insufficient rect=
ifiers SS HIS Felix confirmed//site stabilised","wilfried.kameni@sagemcom.c=
om","187","11-02-2025 12:59:38","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004312635","Mes=
sa Carriere","","11-02-2025 12:55:19","11-02-2025 12:52:13","11-02-2025 13:=
04:29","Site went down due to insufficiency of rectifier Fran=E7ois IHS con=
firmed // Site stabilized","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficiency of rectifi=
er Fran=E7ois IHS confirmed // Site stabilized","wilfried.kameni@sagemcom.c=
om","187","11-02-2025 12:55:19","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004312510","Nko=
zoa","","11-02-2025 12:32:52","11-02-2025 12:24:33","11-02-2025 14:16:19","=
Grid outage, Site went down because Gen start and stopped with ""High temp =
""alarm // He added water and manually start the Gen","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Grid outage, Site went down because Gen start and stopped with "=
"High temp ""alarm // He added water and manually start the Gen","el-dalile=
@sagemcom.com","500","11-02-2025 12:32:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0004312471","H=
-Prince","","11-02-2025 12:27:33","11-02-2025 12:25:19","11-02-2025 12:27:1=
3","Grid outage, site went down before gen start due to poor battery backup=
 // Gen start automatically","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // Gen start automatically","wil=
fried.kameni@sagemcom.com","135","11-02-2025 12:27:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004312449","M=
ontee-Jouvence-II","","11-02-2025 12:25:06","11-02-2025 12:21:59","11-02-20=
25 12:43:56","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed  // Site stabilized","Hyemafo Gildas","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Site went down due to =
PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed  // Site stabilize=
d","wilfried.kameni@sagemcom.com","188","11-02-2025 12:25:06","Sagemcom CMR=
"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004312088","Mes=
sa Carriere","","11-02-2025 11:46:22","11-02-2025 11:42:12","11-02-2025 12:=
00:44","Site went down due to insufficiency of rectifier Fran=E7ois IHS con=
firmed // Site stabilized","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficiency of rectifi=
er Fran=E7ois IHS confirmed // Site stabilized","wilfried.kameni@sagemcom.c=
om","251","11-02-2025 11:46:22","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004311972","Nko=
zoa","","11-02-2025 11:32:25","11-02-2025 11:29:05","11-02-2025 11:33:42","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed // Site stabilized","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site wen=
t down due to gen overload (20kva, 340A) SS HIS Felix bateu is informed and=
 confirmed // Site stabilized","el-dalile@sagemcom.com","201","11-02-2025 1=
1:32:25","Sagemcom CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0004311919","Bye=
massi Carrefour","","11-02-2025 11:27:44","11-02-2025 11:17:31","11-02-2025=
 12:37:13","Grid outage, site went down before gen start due to poor batter=
y backup  // Gen start automatically","Paul BIBOUM","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // Gen start automaticall=
y","el-dalile@sagemcom.com","614","11-02-2025 11:27:44","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004311789","Elo=
umdem stade","","11-02-2025 11:01:20","11-02-2025 10:59:07","11-02-2025 11:=
04:53","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automatically","Fanda Brice","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automatically","e=
l-dalile@sagemcom.com","134","11-02-2025 11:01:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0004311781","S=
apeur Mimboman","","11-02-2025 10:59:25","11-02-2025 10:56:11","11-02-2025 =
10:59:21","Site went down due to insufficiency of rectifier Alphonse DEFFO =
IHS confirmed // Site stabilized","Mba Lazare Herve","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","Site went down due to insufficiency =
of rectifier Alphonse DEFFO IHS confirmed // Site stabilized","wilfried.kam=
eni@sagemcom.com","196","11-02-2025 10:59:25","Sagemcom CMR"
"Closed Complete","Site Down","T1652","IHS_YND_273","NOCINC0004311774","Nko=
lbi-Boss","","11-02-2025 10:57:15","11-02-2025 10:53:01","11-02-2025 11:20:=
47","ACTIVE//No power issue on site U=3D53.4V  Site on grid.moumadou(699949=
072)from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE/=
/No power issue on site U=3D53.4V  Site on grid.moumadou(699949072)from Hua=
wei is informed","wilfried.kameni@sagemcom.com","255","11-02-2025 10:57:15"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004311393","Aka=
k-Nkozoa-MTN-IHS","","11-02-2025 09:47:41","11-02-2025 09:45:33","11-02-202=
5 09:49:06","Grid fluctuation, Site went down because Gen started and stopp=
ed due to Grid bad voltage// He bypassed Grid and started Gen manualy","Fab=
rice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, Site went down because Gen started and stopp=
ed due to Grid bad voltage// He bypassed Grid and started Gen manualy","wil=
fried.kameni@sagemcom.com","129","11-02-2025 09:47:41","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004311129","AWA=
E OCM","","11-02-2025 09:25:34","11-02-2025 09:16:27","11-02-2025 09:32:53"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen started automatically","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen started automatically"=
,"wilfried.kameni@sagemcom.com","1106","11-02-2025 09:25:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004310603","Mbeng","=
","11-02-2025 08:05:10","10-02-2025 19:36:03","10-02-2025 19:37:50","Cascad=
ed Incident from TTO4341482","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Gen  with U=3D5=
0.1v Etienne(695033981) From Huawei is informed and Site UP at=3D07:48 PM",=
"system","1260539","11-02-2025 08:05:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004310604","Minka","=
","11-02-2025 08:05:10","10-02-2025 19:36:03","10-02-2025 19:37:50","Cascad=
ed Incident from TTO4341482","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active//No power issue site on Gen  with U=3D5=
0.1v Etienne(695033981) From Huawei is informed and Site UP at=3D07:48 PM",=
"system","1260539","11-02-2025 08:05:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004310577","M=
om","IHS_YND_369, IHS_YND_371","11-02-2025 08:00:22","10-02-2025 19:36:03",=
"10-02-2025 19:37:50","Active//No power issue site on Gen  with U=3D50.1v E=
tienne(695033981) From Huawei is informed and Site UP at=3D07:48 PM","Fanda=
 Brice","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No power issue site on Gen  with U=3D50.1v Etie=
nne(695033981) From Huawei is informed and Site UP at=3D07:48 PM","el-dalil=
e@sagemcom.com","44660","11-02-2025 08:00:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004310308","N=
KOLMEKONG YDE","","11-02-2025 07:04:25","10-02-2025 22:20:01","10-02-2025 2=
2:20:03","Active//No Power issues on Site site is on Grid and Ubaie=3D49.3V=
, The  FME TX Symphorien(650257151) from Huawei is informed","Fabrice Pouak=
am","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No Power issues on Site site is on Grid and Ubaie=
=3D49.3V, The  FME TX Symphorien(650257151) from Huawei is informed","el-da=
lile@sagemcom.com","31466","11-02-2025 07:04:25","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004309900","MBA=
LNGONG LYCEE","","11-02-2025 05:14:08","11-02-2025 05:05:43","11-02-2025 05=
:42:08","Grid outage, site went down due to gen overload (9kva, 130A) IHS S=
S Felix ZAMBE is informed and confirmed// He reduced the load and gen manua=
lly started","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, site went down due to gen overload (9kva, 130A) IHS=
 SS Felix ZAMBE is informed and confirmed// He reduced the load and gen man=
ually started","danick.tchakouani@sagemcom.com","507","11-02-2025 05:14:08"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004309539","Nko=
g-Edzen","","11-02-2025 02:53:03","11-02-2025 02:50:55","11-02-2025 05:11:4=
2","No power issue on site, site on Gen The Tx FME Gregoire/654547479/ from=
 huawei is informed.","Parker Tchoup","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, s=
ite on Gen The Tx FME Gregoire/654547479/ from huawei is informed.","wilfri=
ed.kameni@sagemcom.com","129","11-02-2025 02:53:03","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004309327","Men=
dong vallee","","11-02-2025 01:10:07","10-02-2025 23:35:21","10-02-2025 23:=
49:10","Site went down because due to insufficient rectifiers SS HIS Felix =
confirmed//site stabilised","Fanda Brice","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down because due to insufficient rect=
ifiers SS HIS Felix confirmed//site stabilised","danick.tchakouani@sagemcom=
.com","6432","11-02-2025 01:10:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004308911","N=
kolfon Cimencam","","10-02-2025 23:34:37","10-02-2025 23:24:24","11-02-2025=
 00:30:48","Active//No power issue, Site on Grid Ubai=3D 50,8V. Notice that=
 it is impacted by Afanoya II","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue, Site on Grid Ubai=3D 50,8V. Notice that it is impacted by Afanoya =
II","wilfried.kameni@sagemcom.com","614","10-02-2025 23:34:37","Sagemcom CM=
R"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004308078","Aka=
k-Nkozoa-MTN-IHS","","10-02-2025 21:13:11","10-02-2025 21:09:00","11-02-202=
5 00:02:31","Grid fluctuation, Site went down because Gen started and stopp=
ed due to Grid bad voltage// He bypassed Grid and started Gen manualy","Fab=
rice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, Site went down because Gen started and stopp=
ed due to Grid bad voltage// He bypassed Grid and started Gen manualy","wil=
fried.kameni@sagemcom.com","253","10-02-2025 21:13:11","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0004308039","MBA=
LNGONG LYCEE","","10-02-2025 21:07:23","10-02-2025 20:56:15","10-02-2025 21=
:32:37","Grid outage, site went down due to gen overload(9Kva, 130A), IHS S=
S Felix ZAMBE is informed // Grid return","Fanda Brice","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload(9Kva, 130A), IHS SS Felix ZAMBE is informed // Grid return","w=
ilfried.kameni@sagemcom.com","669","10-02-2025 21:07:23","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004307881","Nlo=
ngkak","","10-02-2025 20:40:32","10-02-2025 20:18:18","10-02-2025 20:43:35"=
,"Grid outage, site went down becfore gen start due to poor battery backup =
// Grid power return","Delor Telezing","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down becfore=
 gen start due to poor battery backup // Grid power return","wilfried.kamen=
i@sagemcom.com","1335","10-02-2025 20:40:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004307757","S=
atcom","","10-02-2025 20:23:48","10-02-2025 19:59:41","10-02-2025 20:10:50"=
,"Active // No power issue site on Grid with U=3D53,02 V Tx Fme Armand Nges=
tsa (691144412) of huawei is informed","Delor Telezing","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
// No power issue site on Grid with U=3D53,02 V Tx Fme Armand Ngestsa (6911=
44412) of huawei is informed","wilfried.kameni@sagemcom.com","1448","10-02-=
2025 20:23:48","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004307622","Mes=
sa Carriere","","10-02-2025 20:03:14","10-02-2025 19:53:03","10-02-2025 21:=
11:54","Site went down due to insufficiency of rectifier Fran=E7ois IHS con=
firmed // Site stabilized","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficiency of rectifi=
er Fran=E7ois IHS confirmed // Site stabilized","wilfried.kameni@sagemcom.c=
om","612","10-02-2025 20:03:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004307535","N=
KOLMEKONG YDE","","10-02-2025 19:45:18","10-02-2025 19:30:54","10-02-2025 2=
2:19:42","Site went down due to disfunctionning of PWC // He reset controll=
er, site on grid,Power issue resolved at 10:19 PM but site remains down Sym=
phorien(650257151) from Huawei is informed","Fabrice Pouakam","Equipment Re=
pair","Passive","Rectifier","Rectifier Module Overloaded","Site went down d=
ue to disfunctionning of PWC // He reset controller, site on grid,Power iss=
ue resolved at 10:19 PM but site remains down Symphorien(650257151) from Hu=
awei is informed","danick.tchakouani@sagemcom.com","865","10-02-2025 19:45:=
18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_177","NOCINC0004307335","Awae-Yde=
","IHS_YND_171","10-02-2025 19:16:00","10-02-2025 16:47:09","10-02-2025 19:=
00:09","Grid outage, site went down due to Gen Ovaloard(12KVa, 150A), SS IH=
S Alphonse DEFFO is informed //  Grid return","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down d=
ue to Gen Ovaloard(12KVa, 150A), SS IHS Alphonse DEFFO is informed //  Grid=
 return","system","8931","10-02-2025 19:16:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004306475","O=
LAMA","","10-02-2025 17:33:33","10-02-2025 17:16:22","10-02-2025 17:20:54",=
"Active//No power issue on site, Site on Gen, UBAIE=3D47.6V (it starts at t=
he threshold ubaie=3D47 V)The Tx RM Alain/691144423/ from Huawei is informe=
d","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active//No power issue on site, Site on Gen, U=
BAIE=3D47.6V (it starts at the threshold ubaie=3D47 V)The Tx RM Alain/69114=
4423/ from Huawei is informed","wilfried.kameni@sagemcom.com","1032","10-02=
-2025 17:33:33","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004306381","ODZ=
A MINKAN EDIBI ASSI","","10-02-2025 17:20:58","10-02-2025 17:16:51","10-02-=
2025 18:50:21","Site went down because Gen Failed to start due to Grid cont=
actor Dysfonction // He excited grid  contactor (investigation ongoing) ","=
Albran Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue"=
,"Site went down because Gen Failed to start due to Grid contactor Dysfonct=
ion // He excited grid  contactor (investigation ongoing) ","wilfried.kamen=
i@sagemcom.com","248","10-02-2025 17:20:58","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004306270","Aka=
k-Nkozoa-MTN-IHS","","10-02-2025 17:12:54","10-02-2025 17:03:49","10-02-202=
5 18:22:37","Site went down because the Cb(80A) of PWC dysjuncted // He rea=
med the Cb (investigation ongoing)","Fabrice Pouakam","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went =
down because the Cb(80A) of PWC dysjuncted // He reamed the Cb (investigati=
on ongoing)","wilfried.kameni@sagemcom.com","547","10-02-2025 17:12:54","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004306220","Eto koss=
 Yde","","10-02-2025 17:01:00","10-02-2025 16:55:05","10-02-2025 17:49:40",=
"Cascaded Incident from TTO4336255","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down du to insufficiency o=
f rectifier, IHS SS FELIX ZAMBE is informed // site stabilized","system","2=
70582","10-02-2025 17:01:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004306221","ELOUMDEM=
 CARRIERE 2","","10-02-2025 17:01:00","10-02-2025 16:55:05","10-02-2025 17:=
49:40","Cascaded Incident from TTO4336255","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down du to insuffic=
iency of rectifier, IHS SS FELIX ZAMBE is informed // site stabilized","sys=
tem","270582","10-02-2025 17:01:00","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004306208","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","10-02-2025 16:59:30","10-02-2025 16:55=
:05","10-02-2025 17:49:40","Site went down du to insufficiency of rectifier=
, IHS SS FELIX ZAMBE is informed // site stabilized","Fanda Brice","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","Site went down du to i=
nsufficiency of rectifier, IHS SS FELIX ZAMBE is informed // site stabilize=
d","wilfried.kameni@sagemcom.com","266","10-02-2025 16:59:30","Sagemcom CMR=
"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004306202","Awa=
e Escalier","","10-02-2025 16:57:37","10-02-2025 16:47:09","10-02-2025 19:1=
7:31","ACTIVE// No power issue on site Ubaie =3D54.1V site on Grid  The TX =
FME Lionel adjep//655-18-48-76 from huawei is informed","Albran Byorel","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","ACTIVE// No power issue on site Ubaie =3D54.1V site on Grid  The T=
X FME Lionel adjep//655-18-48-76 from huawei is informed","wilfried.kameni@=
sagemcom.com","655","10-02-2025 16:57:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004306029","S=
hell-Nsimeyong","","10-02-2025 16:41:30","10-02-2025 16:35:23","10-02-2025 =
16:40:20","no power issue U =3D51.9V site on Grid.The FME TX Mbah Hosiah (6=
74007438/699699694) from Huawei is informed","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no=
 power issue U =3D51.9V site on Grid.The FME TX Mbah Hosiah (674007438/6996=
99694) from Huawei is informed","danick.tchakouani@sagemcom.com","368","10-=
02-2025 16:41:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004306019","S=
calom","","10-02-2025 16:39:31","10-02-2025 16:35:20","10-02-2025 16:40:52"=
,"No power issue , Ubaie=3D54.5 V site on Gen.The FME TX Mbah Hosiah (67400=
7438) from Huawei is informed","Paul BIBOUM","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue , U=
baie=3D54.5 V site on Gen.The FME TX Mbah Hosiah (674007438) from Huawei is=
 informed","wilfried.kameni@sagemcom.com","252","10-02-2025 16:39:31","Sage=
mcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0004306013","Bar=
riere IHS","","10-02-2025 16:38:25","10-02-2025 16:35:21","10-02-2025 16:38=
:53","Grid outage, Site went down because PWC dysfunctionning  // site stab=
ilized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Grid outage, Site went down because PWC dysfunctionni=
ng  // site stabilized","wilfried.kameni@sagemcom.com","185","10-02-2025 16=
:38:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_750","NOCINC0004306002","Nkoabang=
 entree carriere","","10-02-2025 16:37:11","10-02-2025 16:34:03","10-02-202=
5 17:12:44","Grid outage, site went down because Gen failed to start due to=
 Gen battery faulty (SS ihs  is informed Alphonse deffo is informed)// Grid=
 power return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Battery","Grid outage, site went down because Gen failed t=
o start due to Gen battery faulty (SS ihs  is informed Alphonse deffo is in=
formed)// Grid power return","wilfried.kameni@sagemcom.com","188","10-02-20=
25 16:37:11","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004305752","Nko=
ulou Carriere carrefourt","","10-02-2025 16:05:47","10-02-2025 16:03:40","1=
0-02-2025 18:39:19","Grid outage site went down because failed to start due=
 Gen Card faulty(theft)(SS ihs  is informed Alphonse deffo is informed) // =
Grid power return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage site went down because failed to sta=
rt due Gen Card faulty(theft)(SS ihs  is informed Alphonse deffo is informe=
d) // Grid power return","wilfried.kameni@sagemcom.com","128","10-02-2025 1=
6:05:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004305585","A=
WAE OCM","","10-02-2025 15:41:07","10-02-2025 15:33:03","10-02-2025 15:53:4=
9","Grid outage, site went down becfore gen start due to poor battery backu=
p // Gen start automatically","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn becfore gen start due to poor battery backup // Gen start automatically"=
,"wilfried.kameni@sagemcom.com","486","10-02-2025 15:41:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004305581","B=
iteng-Maetur","","10-02-2025 15:40:30","10-02-2025 15:31:19","10-02-2025 20=
:58:19","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return (S=
ite up at OCM after power reset done)","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down becau=
se Gen started and stopped due to Gen overload(20kva, 280A) SS IHS Alphonse=
 DEFFO confirmed// Grid return (Site up at OCM after power reset done)","da=
nick.tchakouani@sagemcom.com","553","10-02-2025 15:40:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_246","NOCINC0004305492","Emana","=
","10-02-2025 15:26:47","10-02-2025 15:09:42","10-02-2025 15:19:48","Grid o=
utage, site went down before gen start due to poor battery backup // Grid p=
ower return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before gen star=
t due to poor battery backup // Grid power returnly","wilfried.kameni@sagem=
com.com","1026","10-02-2025 15:26:47","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004305388","Pha=
rmacie SION","","10-02-2025 15:16:48","10-02-2025 15:14:43","10-02-2025 15:=
24:49","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automatically","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automatically","w=
ilfried.kameni@sagemcom.com","126","10-02-2025 15:16:48","Sagemcom CMR"
"Closed Complete","Site Down","T1557","IHS_YND_313","NOCINC0004305377","Afa=
noya","","10-02-2025 15:14:39","10-02-2025 15:07:11","10-02-2025 15:29:25",=
"Site went down because Gen failed to start due to CB Gen (40A) tripped due=
 to Grid bad bad voltage// He rearmed CB and site on gen","Hyemafo Gildas",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Site went do=
wn because Gen failed to start due to CB Gen (40A) tripped due to Grid bad =
bad voltage// He rearmed CB and site on gen","wilfried.kameni@sagemcom.com"=
,"518","10-02-2025 15:14:39","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004305277","Mes=
sa Carriere","","10-02-2025 15:02:32","10-02-2025 15:00:26","10-02-2025 15:=
16:00","Site went down due to insufficient rectifiers on site caused by inc=
rease in load .SS IHS Francois is confirmed //Site Stabilized","Mboua Thier=
ry","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went =
down due to insufficient rectifiers on site caused by increase in load .SS =
IHS Francois is confirmed //Site Stabilized","wilfried.kameni@sagemcom.com"=
,"128","10-02-2025 15:02:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004305019","OKOA Pea=
ge","","10-02-2025 14:44:22","10-02-2025 14:00:42","10-02-2025 14:54:42","C=
ascaded Incident from TTO4334880","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","	Site went down because MPR disfunctio=
nning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed//=
 He reset rectifier","system","601040","10-02-2025 14:44:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004305022","Nkongtoc=
k","","10-02-2025 14:44:22","10-02-2025 14:00:42","10-02-2025 14:54:42","Ca=
scaded Incident from TTO4334880","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","	Site went down because MPR disfunc=
tionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirme=
d// He reset rectifier","system","601042","10-02-2025 14:44:22","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004305020","Mambine"=
,"","10-02-2025 14:44:22","10-02-2025 14:00:42","10-02-2025 14:54:42","Casc=
aded Incident from TTO4334880","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","	Site went down because MPR disfunctionni=
ng and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He=
 reset rectifier","system","601044","10-02-2025 14:44:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004305021","Angongo"=
,"","10-02-2025 14:44:22","10-02-2025 14:00:42","10-02-2025 14:54:42","Casc=
aded Incident from TTO4334880","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","	Site went down because MPR disfunctionni=
ng and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He=
 reset rectifier","system","601043","10-02-2025 14:44:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004305018","Nomayos-=
IHS","","10-02-2025 14:44:21","10-02-2025 14:00:42","10-02-2025 14:54:42","=
Cascaded Incident from TTO4334880","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","	Site went down because MPR disfuncti=
onning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed/=
/ He reset rectifier","system","601042","10-02-2025 14:44:21","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004305015","Mbankomo=
 IHS","","10-02-2025 14:44:21","10-02-2025 14:00:42","10-02-2025 14:54:42",=
"Cascaded Incident from TTO4334880","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","	Site went down because MPR disfunct=
ionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed=
// He reset rectifier","system","601041","10-02-2025 14:44:21","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004305017","Ebeba","=
","10-02-2025 14:44:21","10-02-2025 14:00:42","10-02-2025 14:54:42","Cascad=
ed Incident from TTO4334880","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","	Site went down because MPR disfunctionning=
 and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He r=
eset rectifier","system","601043","10-02-2025 14:44:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004305016","Nkenglik=
ok","","10-02-2025 14:44:21","10-02-2025 14:00:42","10-02-2025 14:54:42","C=
ascaded Incident from TTO4334880","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","	Site went down because MPR disfun=
ctionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirm=
ed// He reset rectifier","system","601041","10-02-2025 14:44:21","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004305014","Mandoumb=
a OCM","","10-02-2025 14:44:20","10-02-2025 14:00:42","10-02-2025 14:54:42"=
,"Cascaded Incident from TTO4334880","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","	Site went down because MPR dis=
functionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE conf=
irmed// He reset rectifier","system","601042","10-02-2025 14:44:20","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004305013","Sous Pre=
fecture","","10-02-2025 14:44:20","10-02-2025 14:00:42","10-02-2025 14:54:4=
2","Cascaded Incident from TTO4334880","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","	Site went down because MPR disfu=
nctionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confir=
med// He reset rectifier","system","601040","10-02-2025 14:44:20","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004304985","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, I=
HS_YND_697, IHS_YND_330, IHS_YND_350, IHS_YND_335, IHS_YND_349","10-02-2025=
 14:40:52","10-02-2025 14:00:42","10-02-2025 15:15:42","	Site went down bec=
ause MPR disfunctionning and causing 1/6 rectifiers disfunction SS IHS Feli=
x ZAMBE confirmed// He reset rectifier","Fanda Brice","Equipment Repair","P=
assive","Rectifier","Rectifier Distribution","	Site went down because MPR d=
isfunctionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE co=
nfirmed// He reset rectifier","wilfried.kameni@sagemcom.com","2411","10-02-=
2025 14:40:52","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004304730","NKO=
MEKUI OCM","","10-02-2025 14:17:20","10-02-2025 14:10:11","10-02-2025 14:12=
:31","No power issue on site U=3D54.5  V site on Gen. Site impacted by Mban=
kolo Camtel and not managed by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site U=3D54.5  V site on Gen. Site impacted by Mbankolo C=
amtel and not managed by IHS","ervine.mbezele@sagemcom.com","430","10-02-20=
25 14:17:20","Sagemcom CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0004304331","Nko=
lfoulou","","10-02-2025 13:20:57","10-02-2025 13:12:41","10-02-2025 13:20:0=
4","Active//No power issue, U=3D54V on grid Team Frank/690175109 / From e-e=
ngenering is working on site","Siligap Boris","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power =
issue, U=3D54V on grid Team Frank/690175109 / From e-engenering is working =
on site","wilfried.kameni@sagemcom.com","496","10-02-2025 13:20:57","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004304156","Nkongtoc=
k","","10-02-2025 12:50:32","10-02-2025 12:34:38","10-02-2025 12:38:29","Ca=
scaded Incident from TTO4333857","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because MPR disfunct=
ionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed=
// He reset rectifier","system","606171","10-02-2025 12:50:32","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004304155","Angongo"=
,"","10-02-2025 12:50:32","10-02-2025 12:34:38","10-02-2025 12:38:29","Casc=
aded Incident from TTO4333857","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because MPR disfunctionnin=
g and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He =
reset rectifier","system","606173","10-02-2025 12:50:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004304154","Mambine"=
,"","10-02-2025 12:50:31","10-02-2025 12:34:38","10-02-2025 12:38:29","Casc=
aded Incident from TTO4333857","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because MPR disfunctionnin=
g and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He =
reset rectifier","system","606170","10-02-2025 12:50:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004304152","Nkenglik=
ok","","10-02-2025 12:50:31","10-02-2025 12:34:38","10-02-2025 12:38:29","C=
ascaded Incident from TTO4333857","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because MPR disfunc=
tionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirme=
d// He reset rectifier","system","606172","10-02-2025 12:50:31","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004304151","Mbankomo=
 IHS","","10-02-2025 12:50:31","10-02-2025 12:34:38","10-02-2025 12:38:29",=
"Cascaded Incident from TTO4333857","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because MPR disfuncti=
onning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed/=
/ He reset rectifier","system","606171","10-02-2025 12:50:31","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004304153","Ebeba","=
","10-02-2025 12:50:31","10-02-2025 12:34:38","10-02-2025 12:38:29","Cascad=
ed Incident from TTO4333857","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because MPR disfunctionning =
and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He re=
set rectifier","system","606170","10-02-2025 12:50:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004304149","Sous Pre=
fecture","","10-02-2025 12:50:30","10-02-2025 12:34:38","10-02-2025 12:38:2=
9","Cascaded Incident from TTO4333857","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because MPR disfun=
ctionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirm=
ed// He reset rectifier","system","606170","10-02-2025 12:50:30","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004304150","Mandoumb=
a OCM","","10-02-2025 12:50:30","10-02-2025 12:34:38","10-02-2025 12:38:29"=
,"Cascaded Incident from TTO4333857","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because MPR disf=
unctionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confi=
rmed// He reset rectifier","system","606172","10-02-2025 12:50:30","Sagemco=
m CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004304098","Nom=
ayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS=
_YND_350, IHS_YND_335, IHS_YND_349","10-02-2025 12:42:43","10-02-2025 12:34=
:38","10-02-2025 12:58:13","Site went down because MPR disfunctionning and =
causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He reset =
rectifier","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifie=
r Distribution","Site went down because MPR disfunctionning and causing 1/6=
 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He reset rectifier",=
"wilfried.kameni@sagemcom.com","486","10-02-2025 12:42:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0004303621","S=
apeur Mimboman","","10-02-2025 11:28:33","10-02-2025 11:25:29","10-02-2025 =
19:06:02","Site went down due to insufficiency of rectifiers due to load in=
crease SS IHS Alphonse DEFFO confirmed// site stabilized","Mba Lazare Herve=
","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went do=
wn due to insufficiency of rectifiers due to load increase SS IHS Alphonse =
DEFFO confirmed// site stabilized","wilfried.kameni@sagemcom.com","185","10=
-02-2025 11:28:33","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004303543","Mes=
sa Carriere","","10-02-2025 11:21:16","10-02-2025 11:18:30","10-02-2025 11:=
34:57","Site went down due to insufficient rectifiers on site caused by inc=
rease in load .SS IHS Francois is confirmed //Site Stabilized","Mboua Thier=
ry","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went =
down due to insufficient rectifiers on site caused by increase in load .SS =
IHS Francois is confirmed //Site Stabilized","ervine.mbezele@sagemcom.com",=
"167","10-02-2025 11:21:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004303529","Angongo"=
,"","10-02-2025 11:18:12","10-02-2025 11:14:07","10-02-2025 11:17:29","Casc=
aded Incident from TTO4333143","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because MPR disfunctionnin=
g and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He =
reset rectifier","system","610970","10-02-2025 11:18:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004303527","Ebeba","=
","10-02-2025 11:18:12","10-02-2025 11:14:07","10-02-2025 11:17:29","Cascad=
ed Incident from TTO4333143","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because MPR disfunctionning =
and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He re=
set rectifier","system","610971","10-02-2025 11:18:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004303528","Mambine"=
,"","10-02-2025 11:18:12","10-02-2025 11:14:07","10-02-2025 11:17:29","Casc=
aded Incident from TTO4333143","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because MPR disfunctionnin=
g and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He =
reset rectifier","system","610971","10-02-2025 11:18:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004303530","Nkongtoc=
k","","10-02-2025 11:18:12","10-02-2025 11:14:07","10-02-2025 11:17:29","Ca=
scaded Incident from TTO4333143","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because MPR disfunct=
ionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed=
// He reset rectifier","system","610969","10-02-2025 11:18:12","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004303525","Mbankomo=
 IHS","","10-02-2025 11:18:11","10-02-2025 11:14:07","10-02-2025 11:17:29",=
"Cascaded Incident from TTO4333143","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because MPR disfuncti=
onning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed/=
/ He reset rectifier","system","610970","10-02-2025 11:18:11","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004303524","Mandoumb=
a OCM","","10-02-2025 11:18:11","10-02-2025 11:14:07","10-02-2025 11:17:29"=
,"Cascaded Incident from TTO4333143","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because MPR disf=
unctionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confi=
rmed// He reset rectifier","system","610971","10-02-2025 11:18:11","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004303526","Nkenglik=
ok","","10-02-2025 11:18:11","10-02-2025 11:14:07","10-02-2025 11:17:29","C=
ascaded Incident from TTO4333143","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because MPR disfunc=
tionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirme=
d// He reset rectifier","system","610969","10-02-2025 11:18:11","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004303523","Sous Pre=
fecture","","10-02-2025 11:18:11","10-02-2025 11:14:07","10-02-2025 11:17:2=
9","Cascaded Incident from TTO4333143","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because MPR disfun=
ctionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirm=
ed// He reset rectifier","system","610969","10-02-2025 11:18:11","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004303318","Nkolfon =
Cimencam","","10-02-2025 11:02:00","10-02-2025 10:57:07","10-02-2025 11:25:=
03","Cascaded Incident from TTO4332989","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because MPR di=
sfunctionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE con=
firmed// He reset rectifier","system","270184","10-02-2025 11:02:00","Sagem=
com CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004303315","Nom=
ayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS=
_YND_762, IHS_YND_350, IHS_YND_335, IHS_YND_349","10-02-2025 11:01:26","10-=
02-2025 10:57:07","10-02-2025 11:25:03","Site went down because MPR disfunc=
tionning and causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirme=
d// He reset rectifier","Fanda Brice","Equipment Repair","Passive","Rectifi=
er","Rectifier Distribution","Site went down because MPR disfunctionning an=
d causing 1/6 rectifiers disfunction SS IHS Felix ZAMBE confirmed// He rese=
t rectifier","wilfried.kameni@sagemcom.com","260","10-02-2025 11:01:26","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004303292","A=
wae Ewonkan","","10-02-2025 10:55:58","10-02-2025 10:29:43","10-02-2025 14:=
40:33","Site went down due to insufficiency rectifiers (06 rectfiers) due t=
o load increase on site IHS SS Alphonse is informed and is confirmed//Site =
stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to insufficiency rectifiers (06 rectfiers)=
 due to load increase on site IHS SS Alphonse is informed and is confirmed/=
/Site stabilized","wilfried.kameni@sagemcom.com","1576","10-02-2025 10:55:5=
8","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004303203","Fou=
da Quarter","","10-02-2025 10:38:01","10-02-2025 10:31:49","10-02-2025 10:5=
1:07","Site went down due to insuffience of rectifiers (02) on site SS IHS =
Bernard Atangana confirmed// Site stabilized","Delor Telezing","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down due to insu=
ffience of rectifiers (02) on site SS IHS Bernard Atangana confirmed// Site=
 stabilized","ervine.mbezele@sagemcom.com","373","10-02-2025 10:38:01","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004303071","C=
RH-Etoug-Ebe","","10-02-2025 10:15:49","10-02-2025 10:03:38","10-02-2025 10=
:11:19","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen start automatically=
","wilfried.kameni@sagemcom.com","733","10-02-2025 10:15:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004302977","N=
YOM 2 IHS","","10-02-2025 10:00:42","10-02-2025 09:54:21","10-02-2025 10:04=
:01","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automatically","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"wilfried.kameni@sagemcom.com","382","10-02-2025 10:00:42","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004302798","Elo=
umdem stade","","10-02-2025 09:40:40","10-02-2025 09:38:34","10-02-2025 10:=
06:52","Site went down due to insufficiency of rectifier due to load increa=
se, IHS SS FELIX ZAMBE is confirmed//site stabilised","Fanda Brice","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site went down due to=
 insufficiency of rectifier due to load increase, IHS SS FELIX ZAMBE is con=
firmed//site stabilised","wilfried.kameni@sagemcom.com","127","10-02-2025 0=
9:40:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004302593","O=
LAMA","","10-02-2025 09:06:09","10-02-2025 06:09:55","10-02-2025 06:15:02",=
"No power issue on site U=3D54,9 V site on Grid , The Tx RM Alain/691144423=
/ from Huawei is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 U=3D54,9 V site on Grid , The Tx RM Alain/691144423/ from Huawei is inform=
ed","wilfried.kameni@sagemcom.com","10575","10-02-2025 09:06:09","Sagemcom =
CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004302443","SAA=
 Entrance","","10-02-2025 08:36:08","10-02-2025 08:34:36","10-02-2025 09:01=
:52","Grid outage site went down because Gen failed to start due to Gen bat=
tery faulty // Gen manually started with external battery","Parker Tchoup",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid ou=
tage site went down because Gen failed to start due to Gen battery faulty /=
/ Gen manually started with external battery","ervine.mbezele@sagemcom.com"=
,"93","10-02-2025 08:36:08","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0004302401","Feb=
e Village","","10-02-2025 08:27:40","10-02-2025 08:23:32","10-02-2025 10:36=
:25","Site went down because CB(125A) and (100A) tripped in DC BOX who feed=
s equipments MTN due to load increase// CB put back on","Mboua Thierry","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker =
Issue","Site went down because CB(125A) and (100A) tripped in DC BOX who fe=
eds equipments MTN due to load increase// CB put back on","wilfried.kameni@=
sagemcom.com","249","10-02-2025 08:27:40","Sagemcom CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004302378","Eke=
kam","","10-02-2025 08:23:55","10-02-2025 08:18:51","10-02-2025 08:37:12","=
Hybrid Gen Site, site went down due to hybrid system dysfunctionning//He re=
set and Gen started manaully","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Hybrid","Hybrid Module","Hybrid Gen Site, site went down due to=
 hybrid system dysfunctionning//He reset, and Gen started manaully","wilfri=
ed.kameni@sagemcom.com","305","10-02-2025 08:23:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004302354","N=
gouetou","","10-02-2025 08:20:53","10-02-2025 08:17:44","10-02-2025 08:21:1=
0","ACTIVE//No power issue on site, site on Gen The Tx FME Gregoire/6545474=
79/ from huawei is informed and up at 08:21 AM.Notice that we have cloud in=
 Area","Parker Tchoup","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","ACTIVE//No power issue on site, site on =
Gen The Tx FME Gregoire/654547479/ from huawei is informed and up at 08:21 =
AM.Notice that we have cloud in Area","wilfried.kameni@sagemcom.com","191",=
"10-02-2025 08:20:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0004302167","C-Suprem=
e","","10-02-2025 07:40:11","10-02-2025 07:29:16","10-02-2025 07:35:26","Ca=
scaded Incident from TTO4331682","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","Active// No power issue, site is on Grid with Ubaie=
=3D53,5V, Brice Tsague(650214096) from Huawei is informed","system","268448=
","10-02-2025 07:40:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_037","NOCINC0004302164","Nkolndon=
go","","10-02-2025 07:40:11","10-02-2025 07:29:16","10-02-2025 07:35:26","C=
ascaded Incident from TTO4331682","MINKA NICOLAS","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active// No power issue, site is on Gri=
d with Ubaie=3D53,5V, Brice Tsague(650214096) from Huawei is informed","sys=
tem","268447","10-02-2025 07:40:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0004302166","Acropole=
","","10-02-2025 07:40:11","10-02-2025 07:29:16","10-02-2025 07:35:26","Cas=
caded Incident from TTO4331682","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// No power issue, site is on Grid =
with Ubaie=3D53,5V, Brice Tsague(650214096) from Huawei is informed","syste=
m","268449","10-02-2025 07:40:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0004302165","Olezoa O=
CM","","10-02-2025 07:40:11","10-02-2025 07:29:16","10-02-2025 07:35:26","C=
ascaded Incident from TTO4331682","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Active// No power issue, site is on Grid with Ubaie=
=3D53,5V, Brice Tsague(650214096) from Huawei is informed","system","268448=
","10-02-2025 07:40:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_042","NOCINC0004302163","Mvog-Ada=
_OCM","","10-02-2025 07:40:10","10-02-2025 07:29:16","10-02-2025 07:35:26",=
"Cascaded Incident from TTO4331682","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","Active// No power issue, site is on Grid with Ubai=
e=3D53,5V, Brice Tsague(650214096) from Huawei is informed","system","26844=
7","10-02-2025 07:40:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0004302157","M=
vog Mbi New","IHS_YND_042, IHS_YND_037, IHS_YND_055, IHS_YND_036, IHS_YND_0=
21","10-02-2025 07:38:31","10-02-2025 07:29:16","10-02-2025 07:35:26","Acti=
ve// No power issue, site is on Grid with Ubaie=3D53,5V, Brice Tsague(65021=
4096) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No powe=
r issue, site is on Grid with Ubaie=3D53,5V, Brice Tsague(650214096) from H=
uawei is informed","wilfried.kameni@sagemcom.com","556","10-02-2025 07:38:3=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004301475","M=
efou-Assi","IHS_YND_696","10-02-2025 04:58:16","10-02-2025 02:17:38","10-02=
-2025 02:23:20","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On=
 Grid The Tx FME Fulbert(654266068) from Huawei is informed","Fanda Brice",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid=
 The Tx FME Fulbert(654266068) from Huawei is informed","wilfried.kameni@sa=
gemcom.com","9639","10-02-2025 04:58:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004301470","Yoko MTN=
","","10-02-2025 04:56:11","10-02-2025 04:38:51","10-02-2025 04:39:23","Cas=
caded Incident from TTO4330863","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE//No power issue on site, site on G=
en The Tx FME Gregoire/654547479/ from huawei is informed. Repetitive issue=
 Site up at 04:53 AM","system","264216","10-02-2025 04:56:11","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004301468","Matsari"=
,"","10-02-2025 04:56:10","10-02-2025 04:38:51","10-02-2025 04:39:23","Casc=
aded Incident from TTO4330863","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","ACTIVE//No power issue on site, site on Ge=
n The Tx FME Gregoire/654547479/ from huawei is informed. Repetitive issue =
Site up at 04:53 AM","system","264216","10-02-2025 04:56:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004301469","Ngoum","=
","10-02-2025 04:56:10","10-02-2025 04:38:51","10-02-2025 04:39:23","Cascad=
ed Incident from TTO4330863","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE//No power issue on site, site on Gen =
The Tx FME Gregoire/654547479/ from huawei is informed. Repetitive issue Si=
te up at 04:53 AM","system","264215","10-02-2025 04:56:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004301467","MBIMBIM"=
,"","10-02-2025 04:56:10","10-02-2025 04:38:51","10-02-2025 04:39:23","Casc=
aded Incident from TTO4330863","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","ACTIVE//No power issue on site, site on Ge=
n The Tx FME Gregoire/654547479/ from huawei is informed. Repetitive issue =
Site up at 04:53 AM","system","264215","10-02-2025 04:56:10","Sagemcom CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0004301459","Ngo=
uetou","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_473","10-02-2025 04:=
53:03","10-02-2025 04:38:51","10-02-2025 04:39:23","ACTIVE//No power issue =
on site, site on Gen The Tx FME Gregoire/654547479/ from huawei is informed=
. Repetitive issue Site up at 04:53 AM","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE/=
/No power issue on site, site on Gen The Tx FME Gregoire/654547479/ from hu=
awei is informed. Repetitive issue Site up at 04:53 AM","danick.tchakouani@=
sagemcom.com","853","10-02-2025 04:53:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004301293","N=
kolfon Cimencam","","10-02-2025 03:55:01","10-02-2025 03:09:36","10-02-2025=
 04:22:06","Active//No power issue, Site on Grid Ubai=3D 50,8V. Notice that=
 it is impacted by Afanoya II","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue, Site on Grid Ubai=3D 50,8V. Notice that it is impacted by Afanoya =
II","wilfried.kameni@sagemcom.com","2726","10-02-2025 03:55:01","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004301033","O=
LAMA","","10-02-2025 02:34:05","10-02-2025 01:14:36","10-02-2025 02:55:58",=
"Active: no power issue, site is on gen  with Ubaie=3D54.9V, Alain RM(69114=
4423) from Huawei is informed","Fanda Brice","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power i=
ssue, site is on gen  with Ubaie=3D54.9V, Alain RM(691144423) from Huawei i=
s informed","danick.tchakouani@sagemcom.com","4769","10-02-2025 02:34:05","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004301005","B=
arriere IHS","","10-02-2025 02:17:40","10-02-2025 02:17:38","10-02-2025 02:=
23:20","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The=
 Tx FME Fulbert(654266068) from Huawei is informed","Hyemafo Gildas","Casca=
de Outage","Active","Cascade Active","Cascade Active","ACTIVE//No power iss=
ue on site GRID , Ubaie=3D54.V site On Grid The Tx FME Fulbert(654266068) f=
rom Huawei is informed","wilfried.kameni@sagemcom.com","272566","10-02-2025=
 02:17:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004300712","M=
EHANDAN","","10-02-2025 00:57:09","09-02-2025 23:06:27","10-02-2025 02:57:5=
0","No poer issue site on grid with U=3D54.5v Notice tha site is impacted b=
y Odza II","Albran Byorel","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No poer issue site on grid with U=3D=
54.5v Notice tha site is impacted by Odza II","wilfried.kameni@sagemcom.com=
","6644","10-02-2025 00:57:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004300648","Nkolkoum=
ou OCM","","10-02-2025 00:38:21","10-02-2025 00:23:43","10-02-2025 02:05:48=
","Cascaded Incident from TTO4329906","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, Site wen=
t down because Gen fails to start due to ATS damaged // He bypass it and ma=
nually start the gen","system","272235","10-02-2025 00:38:21","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0004300623","N=
kolbisson usine des eaux","IHS_YND_712","10-02-2025 00:33:15","10-02-2025 0=
0:21:43","10-02-2025 02:05:48","Grid outage, Site went down because Gen fai=
ls to start due to ATS damaged // He bypass it and manually start the gen",=
"TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","AT=
S-AMF Issue","Grid outage, Site went down because Gen fails to start due to=
 ATS damaged // He bypass it and manually start the gen","wilfried.kameni@s=
agemcom.com","693","10-02-2025 00:33:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004300473","Mom","",=
"09-02-2025 23:42:30","09-02-2025 23:20:48","09-02-2025 23:21:33","Cascaded=
 Incident from TTO4329693","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on grid with U=3D50.1v Etien=
ne(695033981) from Huawei is informed","system","268844","09-02-2025 23:42:=
30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004300472","OTELE MT=
N","","09-02-2025 23:42:30","09-02-2025 23:20:48","09-02-2025 23:21:33","Ca=
scaded Incident from TTO4329693","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on grid with U=3D50.1v=
 Etienne(695033981) from Huawei is informed","system","268843","09-02-2025 =
23:42:30","Sagemcom CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0004300450","Min=
ka","IHS_YND_531, IHS_YND_370","09-02-2025 23:37:04","09-02-2025 23:20:48",=
"10-02-2025 01:10:33","No power issue site on grid with U=3D50.1v Etienne(6=
95033981) from Huawei is informed","Fanda Brice","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 site on grid with U=3D50.1v Etienne(695033981) from Huawei is informed","d=
anick.tchakouani@sagemcom.com","977","09-02-2025 23:37:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004300379","B=
iteng-Maetur","","09-02-2025 23:15:52","09-02-2025 21:45:40","09-02-2025 23=
:22:16","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","danick.=
tchakouani@sagemcom.com","5413","09-02-2025 23:15:52","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004300298","Aka=
k-Nkozoa-MTN-IHS","","09-02-2025 22:58:14","09-02-2025 22:27:46","10-02-202=
5 00:53:44","Site went down because CB (80A) tripped in PWC // He did a bri=
dge with a CB(80A)","Fabrice Pouakam","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Circuit Breaker Issue","Site went down because CB =
(80A) tripped in PWC // He did a bridge with a CB(80A)","danick.tchakouani@=
sagemcom.com","1829","09-02-2025 22:58:14","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0004300203","Abo=
me","","09-02-2025 22:39:40","09-02-2025 22:19:24","09-02-2025 23:07:26","G=
rid outage,site went down because gen failed to start due to grid bad volta=
ge//he did a bridge with the good phase","MINKA NICOLAS","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid outage,site we=
nt down because gen failed to start due to grid bad voltage//he did a bridg=
e with the good phase","danick.tchakouani@sagemcom.com","1273","09-02-2025 =
22:39:40","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004299915","Nko=
ulou Carriere carrefourt","","09-02-2025 21:57:57","09-02-2025 21:38:50","0=
9-02-2025 22:44:40","Grid outage,site went down because main gen faulty//Gr=
id return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Generator Faulty","Grid outage,site went down because main gen faulty//G=
rid return","wilfried.kameni@sagemcom.com","1148","09-02-2025 21:57:57","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004299892","Tou=
ring Club International","","09-02-2025 21:53:50","09-02-2025 21:40:39","09=
-02-2025 22:24:48","Grid Outage Site went down because Gen stopped with ala=
rm undervoltage //He Reset the Gen Card and Gen manually started","Albran B=
yorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 Outage Site went down because Gen stopped with alarm undervoltage //He Res=
et the Gen Card and Gen manually started","wilfried.kameni@sagemcom.com","7=
92","09-02-2025 21:53:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004299848","O=
dza II OCM","","09-02-2025 21:48:19","09-02-2025 21:42:06","09-02-2025 23:0=
5:39","Grid outage, site went down because gen failed to start due to gen c=
ard faulty //Grid return","Albran Byorel","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage, site went down because gen fail=
ed to start due to gen card faulty //Grid return","wilfried.kameni@sagemcom=
.com","375","09-02-2025 21:48:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004299839","A=
wae Escalier","","09-02-2025 21:46:01","09-02-2025 21:39:54","09-02-2025 21=
:55:10","Grid outage, site went down before gen start due to poor battery b=
ackup // gen start automatically","Albran Byorel","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // gen start automatically"=
,"wilfried.kameni@sagemcom.com","368","09-02-2025 21:46:01","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004299781","Mes=
sa Carriere","","09-02-2025 21:35:14","09-02-2025 21:28:01","09-02-2025 23:=
36:52","Site went down due to insufficiency of rectifier Fran=E7ois IHS con=
firmed // Site stabilized","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficiency of rectifi=
er Fran=E7ois IHS confirmed // Site stabilized","danick.tchakouani@sagemcom=
.com","434","09-02-2025 21:35:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004299591","N=
YOM 2 IHS","","09-02-2025 21:03:52","09-02-2025 21:00:46","09-02-2025 21:10=
:42","Active//No power issue on site Ubaie=3D54.8  V site on Grid ,TX  FME =
 Synphorien (691316854) from Huawei is informed","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active//No power issue on site Ubaie=3D53.5  V site on Grid ,TX  FME  S=
ynphorien (691316854) from Huawei is informed","wilfried.kameni@sagemcom.co=
m","187","09-02-2025 21:03:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004299454","Mimboman=
4","","09-02-2025 20:37:31","09-02-2025 20:13:58","09-02-2025 22:32:43","Ca=
scaded Incident from TTO4328473","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because CB 63A disj=
uncted in Pwc due to load increase//he did a bridge with another CB 63A","s=
ystem","294558","09-02-2025 20:37:31","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004299452","Nko=
lo II New","IHS_YND_266","09-02-2025 20:37:10","09-02-2025 20:13:58","09-02=
-2025 22:32:43","Site went down because CB 63A disjuncted in Pwc due to loa=
d increase//he did a bridge with another CB 63A","Mba Lazare Herve","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issu=
e","Site went down because CB 63A disjuncted in Pwc due to load increase//h=
e did a bridge with another CB 63A","danick.tchakouani@sagemcom.com","1393"=
,"09-02-2025 20:37:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004299156","Angongo"=
,"","09-02-2025 19:57:34","09-02-2025 19:37:11","09-02-2025 19:39:01","Casc=
aded Incident from TTO4328078","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Gen started due to grid outage, site went=
 down because 02/06 rectifiers dysfunctionning // He reset 02 rectifiers, s=
ite on gen","system","1217372","09-02-2025 19:57:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004299153","Nomayos-=
IHS","","09-02-2025 19:57:33","09-02-2025 19:37:11","09-02-2025 19:39:01","=
Cascaded Incident from TTO4328078","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Gen started due to grid outage, site =
went down because 02/06 rectifiers dysfunctionning // He reset 02 rectifier=
s, site on gen","system","1217373","09-02-2025 19:57:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004299152","Ebeba","=
","09-02-2025 19:57:33","09-02-2025 19:37:11","09-02-2025 19:39:01","Cascad=
ed Incident from TTO4328078","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Gen started due to grid outage, site went d=
own because 02/06 rectifiers dysfunctionning // He reset 02 rectifiers, sit=
e on gen","system","1217370","09-02-2025 19:57:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004299154","OKOA Pea=
ge","","09-02-2025 19:57:33","09-02-2025 19:37:11","09-02-2025 19:39:01","C=
ascaded Incident from TTO4328078","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Gen started due to grid outage, site w=
ent down because 02/06 rectifiers dysfunctionning // He reset 02 rectifiers=
, site on gen","system","1217371","09-02-2025 19:57:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004299155","Mambine"=
,"","09-02-2025 19:57:33","09-02-2025 19:37:11","09-02-2025 19:39:01","Casc=
aded Incident from TTO4328078","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Gen started due to grid outage, site went=
 down because 02/06 rectifiers dysfunctionning // He reset 02 rectifiers, s=
ite on gen","system","1217373","09-02-2025 19:57:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004299151","Nkenglik=
ok","","09-02-2025 19:57:32","09-02-2025 19:37:11","09-02-2025 19:39:01","C=
ascaded Incident from TTO4328078","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Gen started due to grid outage, si=
te went down because 02/06 rectifiers dysfunctionning // He reset 02 rectif=
iers, site on gen","system","1217371","09-02-2025 19:57:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004299149","Mandoumb=
a OCM","","09-02-2025 19:57:32","09-02-2025 19:37:11","09-02-2025 19:39:01"=
,"Cascaded Incident from TTO4328078","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Gen started due to grid outage,=
 site went down because 02/06 rectifiers dysfunctionning // He reset 02 rec=
tifiers, site on gen","system","1217370","09-02-2025 19:57:32","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004299150","Mbankomo=
 IHS","","09-02-2025 19:57:32","09-02-2025 19:37:11","09-02-2025 19:39:01",=
"Cascaded Incident from TTO4328078","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Gen started due to grid outage, site=
 went down because 02/06 rectifiers dysfunctionning // He reset 02 rectifie=
rs, site on gen","system","1217372","09-02-2025 19:57:32","Sagemcom CMR"
"Closed Complete","Site Down","T0638","IHS_YND_318","NOCINC0004299041","SOA=
 University","","09-02-2025 19:36:20","09-02-2025 19:25:08","09-02-2025 19:=
37:57","Site went down because gen failed to start due to grid bad voltage(=
02 phases off) and no RCP// He did a bridge with the good phase","Siligap B=
oris","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Site went down because gen failed to start due to grid bad voltage(02 =
phases off) and no RCP// He did a bridge with the good phase","danick.tchak=
ouani@sagemcom.com","673","09-02-2025 19:36:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004299022","Nomayos =
montee Meche","","09-02-2025 19:31:59","09-02-2025 19:23:11","09-02-2025 19=
:47:28","Cascaded Incident from TTO4327923","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Gen started due to grid outa=
ge, site went down because 02/06 rectifiers dysfunctionning // He reset 02 =
rectifiers, site on gen","system","268766","09-02-2025 19:31:59","Sagemcom =
CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004298988","Nom=
ayos","IHS_YND_367, IHS_YND_791, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS=
_YND_697, IHS_YND_330, IHS_YND_350, IHS_YND_335","09-02-2025 19:26:17","09-=
02-2025 19:23:11","09-02-2025 19:47:28","Gen started due to grid outage, si=
te went down because 02/06 rectifiers dysfunctionning // He reset 02 rectif=
iers, site on gen","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Gen started due to grid outage, site went down because 0=
2/06 rectifiers dysfunctionning // He reset 02 rectifiers, site on gen","da=
nick.tchakouani@sagemcom.com","186","09-02-2025 19:26:17","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004298955","NKO=
MEKUI OCM","","09-02-2025 19:19:31","09-02-2025 19:13:18","09-02-2025 20:18=
:25","No power issue, site is on grid with Ubaie=3D53V, site impacted by Mb=
ankolo camtel","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site =
is on grid with Ubaie=3D53V, site impacted by Mbankolo camtel","danick.tcha=
kouani@sagemcom.com","374","09-02-2025 19:19:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004298873","O=
LAMA","","09-02-2025 19:11:03","09-02-2025 18:44:55","09-02-2025 18:50:26",=
"Active// No power issue , Site on grid Harry Kenfack From Huawei working o=
n site and RM Alain (691144423) confirmed.","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue , Site on grid Harry Kenfack From Huawei working on site=
 and RM Alain (691144423) confirmed.","wilfried.kameni@sagemcom.com","1569"=
,"09-02-2025 19:11:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0004298395","S=
apeur Mimboman","","09-02-2025 17:58:03","09-02-2025 17:55:58","10-02-2025 =
00:06:52","Access issue due to landlord","Mba Lazare Herve","Access Denial"=
,"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Acc=
ess issue due to landlord","wilfried.kameni@sagemcom.com","126","09-02-2025=
 17:58:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004298343","M=
arche Odza","","09-02-2025 17:51:37","09-02-2025 17:49:31","09-02-2025 18:2=
1:34","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started manually","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen=
 start due to poor backup// Gen started manually","danick.tchakouani@sagemc=
om.com","127","09-02-2025 17:51:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004298195","ELOUMDEM=
 CARRIERE 2","","09-02-2025 17:35:00","09-02-2025 17:32:11","09-02-2025 17:=
55:59","Cascaded Incident from TTO4326949","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down du to insuffic=
iency of rectifier, IHS SS FELIX ZAMBE is informed // site stabilized","sys=
tem","297111","09-02-2025 17:35:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004298194","Eto koss=
 Yde","","09-02-2025 17:35:00","09-02-2025 17:32:11","09-02-2025 17:55:59",=
"Cascaded Incident from TTO4326949","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down du to insufficiency o=
f rectifier, IHS SS FELIX ZAMBE is informed // site stabilized","system","2=
97111","09-02-2025 17:35:00","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004298191","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","09-02-2025 17:34:17","09-02-2025 17:32=
:11","09-02-2025 18:16:47","Site went down du to insufficiency of rectifier=
, IHS SS FELIX ZAMBE is informed //Site stabilized","Fanda Brice","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module","Site went down du to in=
sufficiency of rectifier, IHS SS FELIX ZAMBE is informed //Site stabilized"=
,"wilfried.kameni@sagemcom.com","128","09-02-2025 17:34:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004297792","S=
hell-Nsimeyong","","09-02-2025 16:38:33","09-02-2025 16:21:23","09-02-2025 =
16:25:09","Active: no power issue, site is on grid with Ubaie=3D53V, Mbah H=
osiah (674007438/699699694) from Huawei is informed.","MINKA NICOLAS","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active: no power issue, site is on grid with Ubaie=3D53V, Mbah Hosia=
h (674007438/699699694) from Huawei is informed.","wilfried.kameni@sagemcom=
.com","1031","09-02-2025 16:38:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0004297787","OTELE MT=
N","","09-02-2025 16:37:40","09-02-2025 16:02:28","09-02-2025 16:07:29","Ca=
scaded Incident from TTO4326420","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active: no power issue, site on battery wi=
th Ubaie=3D49.5V, Etienne(695033981) from Huawei is informed","system","288=
029","09-02-2025 16:37:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0004297788","Mom","",=
"09-02-2025 16:37:40","09-02-2025 16:02:28","09-02-2025 16:07:29","Cascaded=
 Incident from TTO4326420","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Active: no power issue, site on battery with Uba=
ie=3D49.5V, Etienne(695033981) from Huawei is informed","system","288029","=
09-02-2025 16:37:40","Sagemcom CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0004297753","Min=
ka","IHS_YND_531, IHS_YND_370","09-02-2025 16:32:36","09-02-2025 16:02:28",=
"09-02-2025 16:07:29","Active: no power issue, site on battery with Ubaie=
=3D49.5V, Etienne(695033981) from Huawei is informed","Fanda Brice","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: no power issue, site on battery with Ubaie=3D49.5V, Etienne(69=
5033981) from Huawei is informed","wilfried.kameni@sagemcom.com","1808","09=
-02-2025 16:32:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004297706","S=
calom","","09-02-2025 16:27:17","09-02-2025 16:19:12","09-02-2025 16:22:43"=
,"Active//No power issue on site ,site on Grid with Ubaie=3D54,5V The TX FM=
E Mbah Hosiah (674007438) from Huawei is informed","Paul BIBOUM","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site ,site on Grid with Ubaie=3D54,5V The TX FM=
E Mbah Hosiah (674007438) from Huawei is informed","wilfried.kameni@sagemco=
m.com","486","09-02-2025 16:27:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004297472","Akak-Nko=
zoa-MTN-IHS","","09-02-2025 15:48:30","09-02-2025 15:36:48","09-02-2025 16:=
24:44","Cascaded Incident from TTO4326028","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went be=
cause Gen ran until fuel shortage//Refueling Done","system","275186","09-02=
-2025 15:48:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0004297448","S=
oa-II","IHS_YND_316, IHS_YND_324","09-02-2025 15:44:54","09-02-2025 15:36:4=
8","09-02-2025 16:24:44","Grid outage, Site went because Gen ran until fuel=
 shortage//Refueling Done","Siligap Boris","Fuel Outage","Passive","Diesel"=
,"Diesel Outage","Grid outage, Site went because Gen ran until fuel shortag=
e//Refueling Done","wilfried.kameni@sagemcom.com","486","09-02-2025 15:44:5=
4","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0004297272","Hotel de=
 Ville Yde","","09-02-2025 15:17:00","09-02-2025 15:04:42","09-02-2025 15:4=
5:58","Cascaded Incident from TTO4325799","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage // Grid power retu=
rn","system","277084","09-02-2025 15:17:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0004297259","N=
R-Bastos","IHS_YND_019","09-02-2025 15:15:47","09-02-2025 15:04:42","09-02-=
2025 15:45:58","Grid outage // Grid power return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage // Grid power ret=
urn","wilfried.kameni@sagemcom.com","666","09-02-2025 15:15:47","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004297135","L=
eboudi","","09-02-2025 14:56:53","09-02-2025 14:52:39","09-02-2025 20:55:39=
","No power issue site and  with Ubaie=3D54.4  V site on Gen The  FME TX Mo=
uamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue site and  with Ubaie=3D54.4  V site on Gen The  FME=
 TX Mouamadou/658791013 //From Huawei is informed","wilfried.kameni@sagemco=
m.com","255","09-02-2025 14:56:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004296907","N=
kolafeme","","09-02-2025 14:37:44","09-02-2025 14:32:39","09-02-2025 14:35:=
02","No power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435)=
 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei is=
 informed","wilfried.kameni@sagemcom.com","306","09-02-2025 14:37:44","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004296890","S=
OA UNIVERSITY STADIUM","","09-02-2025 14:34:11","09-02-2025 14:29:00","09-0=
2-2025 14:37:41","Site on gen due to  grid outage, site went down because d=
isfunctionning of gen card // Grid return","Siligap Boris","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Site on gen due to  grid ou=
tage, site went down because disfunctionning of gen card // Grid return","w=
ilfried.kameni@sagemcom.com","25428","09-02-2025 14:34:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0004296854","C=
amp-Sic-Tsinga","","09-02-2025 14:31:02","09-02-2025 14:05:56","09-02-2025 =
15:41:07","Grid outage, no space to deploy a mobil gen // Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age, no space to deploy a mobil gen // Grid return","wilfried.kameni@sagemc=
om.com","1507","09-02-2025 14:31:02","Sagemcom CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004296390","Mes=
sassi okolo","","09-02-2025 13:30:55","09-02-2025 13:24:47","09-02-2025 13:=
30:51","ACTIVE//No power issue on site Ubaie=3D54.4V, site on Grid  The TX =
Fme Synphorien 691316854 of Huawei is informed","Fabrice Pouakam","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE//No power issue on site Ubaie=3D54.4V, site on Grid  The TX Fme S=
ynphorien 691316854 of Huawei is informed","danick.tchakouani@sagemcom.com"=
,"369","09-02-2025 13:30:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004296344","O=
LAMA","","09-02-2025 13:25:17","09-02-2025 12:54:56","09-02-2025 13:00:42",=
"Active// No power issue , Site on grid Harry Kenfack From Huawei working o=
n site and RM Alain (691144423) confirmed.","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue , Site on grid Harry Kenfack From Huawei working on site=
 and RM Alain (691144423) confirmed.","wilfried.kameni@sagemcom.com","1822"=
,"09-02-2025 13:25:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0004296131","M=
aison-Blanche-IHS","","09-02-2025 12:53:28","09-02-2025 12:41:15","09-02-20=
25 14:39:51","Grid outage, No space to deploy MDG // Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
No space to deploy MDG // Grid return","wilfried.kameni@sagemcom.com","734"=
,"09-02-2025 12:53:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004295993","Bastos B=
ir","","09-02-2025 12:38:41","09-02-2025 12:25:21","09-02-2025 13:30:07","C=
ascaded Incident from TTO4324267","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because 1/4 rectifier=
 faulty SS IHS Bernard Atangana is informed and confirmed// He removed rect=
ifier faulty (rectifier to be replaced)","system","265112","09-02-2025 12:3=
8:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004295994","ARMP",""=
,"09-02-2025 12:38:41","09-02-2025 12:25:21","09-02-2025 13:30:07","Cascade=
d Incident from TTO4324267","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down because 1/4 rectifier faulty SS IHS Bern=
ard Atangana is informed and confirmed// He removed rectifier faulty (recti=
fier to be replaced)","system","265112","09-02-2025 12:38:41","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004295973","D=
ragage","IHS_YND_704, IHS_YND_208","09-02-2025 12:36:27","09-02-2025 12:25:=
21","09-02-2025 13:31:19","Site went down because 1/4 rectifier faulty SS I=
HS Bernard Atangana is informed and confirmed// He removed rectifier faulty=
 (rectifier to be replaced)","Mboua Thierry","Equipment Repair","Passive","=
Rectifier","Rectifier Module","Site went down because 1/4 rectifier faulty =
SS IHS Bernard Atangana is informed and confirmed// He removed rectifier fa=
ulty (rectifier to be replaced)","danick.tchakouani@sagemcom.com","667","09=
-02-2025 12:36:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004295965","Nkolkoum=
ou OCM","","09-02-2025 12:35:10","09-02-2025 12:29:16","09-02-2025 12:35:55=
","Cascaded Incident from TTO4324256","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","Active// No power issue,=
 Site on Grid Ubai=3D 52,5V. FME AMBELE Antoine/690031442 From I ENG workin=
g on site (Swap Mw)","system","264656","09-02-2025 12:35:10","Sagemcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0004295963","Nko=
lbisson usine des eaux","IHS_YND_712","09-02-2025 12:34:36","09-02-2025 12:=
29:16","09-02-2025 12:35:55","Active// No power issue, Site on Grid Ubai=3D=
 52,5V. FME AMBELE Antoine/690031442 From I ENG working on site (Swap Mw)",=
"TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active// No power issue, Site on Gri=
d Ubai=3D 52,5V. FME AMBELE Antoine/690031442 From I ENG working on site (S=
wap Mw)","wilfried.kameni@sagemcom.com","320","09-02-2025 12:34:36","Sagemc=
om CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004295866","Mes=
sa Carriere","","09-02-2025 12:11:53","09-02-2025 12:05:41","09-02-2025 12:=
21:41","Site went down due to insufficiency of rectifier Fran=E7ois IHS con=
firmed // Site stabilized","Mboua Thierry","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down due to insufficiency of rectifi=
er Fran=E7ois IHS confirmed // Site stabilized","danick.tchakouani@sagemcom=
.com","372","09-02-2025 12:11:53","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004295621","ETO=
UDI Entree du palais","","09-02-2025 11:46:43","09-02-2025 11:40:32","09-02=
-2025 12:14:38","Site was on Gen due to Grid outage, Grid return but did no=
t feed the site due to ENEO contactor not exicited //He exicited the Grid c=
ontactor","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","A=
TS-AMF Issue","Site was on Gen due to Grid outage, Grid return but did not =
feed the site due to ENEO contactor not exicited //He exicited the Grid con=
tactor","danick.tchakouani@sagemcom.com","372","09-02-2025 11:46:43","Sagem=
com CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004295501","Mfo=
u EPC","","09-02-2025 11:32:48","09-02-2025 11:26:34","09-02-2025 11:42:34"=
,"Grid outage, Site went down because Gen start and stopped with ""High tem=
p ""alarm // He added water and manually start the Gen","Mba Lazare Herve",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, Site went down because Gen start and stopped wit=
h ""High temp ""alarm // He added water and manually start the Gen","danick=
.tchakouani@sagemcom.com","375","09-02-2025 11:32:48","Sagemcom CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0004295298","Ema=
na Lycee","","09-02-2025 10:58:40","09-02-2025 10:47:26","09-02-2025 10:50:=
17","No power issue on site Ubaie=3D54.2V, site on Gen  //The TX Fme Synpho=
rien 691316854 of Huewai is informed","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site Ubaie=3D54.2V, site on Gen  //The TX Fme Synphorien 6913168=
54 of Huewai is informed","wilfried.kameni@sagemcom.com","675","09-02-2025 =
10:58:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004295194","SOA VILL=
AGE","","09-02-2025 10:34:10","09-02-2025 10:27:39","09-02-2025 10:35:12","=
Cascaded Incident from TTO4323353","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 gen start and stopped with High temp alarm // he added water 01L and Gen m=
anually started","system","272246","09-02-2025 10:34:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004295190","S=
OA TOWN","IHS_YND_323","09-02-2025 10:33:06","09-02-2025 10:24:39","09-02-2=
025 10:35:55","Grid outage, Site went down because gen start and stopped wi=
th High temp alarm // he added water 01L and Gen manually started","Siligap=
 Boris","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - =
Coolant Level Issue","Grid outage, Site went down because gen start and sto=
pped with High temp alarm // he added water 01L and Gen manually started","=
danick.tchakouani@sagemcom.com","508","09-02-2025 10:33:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0004295181","Nkolo II=
 New","","09-02-2025 10:31:50","09-02-2025 10:23:52","09-02-2025 10:50:50",=
"Cascaded Incident from TTO4323335","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause gen failed to start due to Pwc ZTE dysfunction// he reset it and  star=
ted Gen manualy","system","272439","09-02-2025 10:31:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004295178","M=
imboman-Village","IHS_YND_709","09-02-2025 10:31:07","09-02-2025 10:23:52",=
"09-02-2025 10:50:50","Grid outage, site went down because gen failed to st=
art due to Pwc ZTE dysfunction// he reset it and  started Gen manualy","Mba=
 Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Grid outage, site went down because gen failed to start due to =
Pwc ZTE dysfunction// he reset it and  started Gen manualy","danick.tchakou=
ani@sagemcom.com","436","09-02-2025 10:31:07","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004294923","SOA=
 UNIVERSITY STADIUM","","09-02-2025 09:51:48","09-02-2025 09:44:34","09-02-=
2025 10:09:34","Grid outage, site went down because gen failed to start due=
 to Pwc ZTE dysfunction// He reset it and  started Gen manualy","Siligap Bo=
ris","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded"=
,"Grid outage, site went down because gen failed to start due to Pwc ZTE dy=
sfunction// He reset it and  started Gen manualy","danick.tchakouani@sagemc=
om.com","459","09-02-2025 09:51:48","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004294868","Nko=
g-Edzen","","09-02-2025 09:46:01","09-02-2025 09:40:51","09-02-2025 10:18:1=
5","Hybrid Gen: Site went down because gen stopped with high temp alarm due=
 to radiator pierced // He added water  2L and Gen manually started ","Park=
er Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator Leakage=
","Hybrid Gen: Site went down because gen stopped with high temp alarm due =
to radiator pierced // He added water  2L and Gen manually started ","danic=
k.tchakouani@sagemcom.com","311","09-02-2025 09:46:01","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004294861","OBA=
M NGOLA OCM","","09-02-2025 09:45:10","09-02-2025 09:38:03","09-02-2025 12:=
08:23","Site went down due to PSC3 dysfonction SS IHS Pascaline confirmed//=
 Site stabilized.Power resolved at 10:15 AM But site still down and up afte=
r power reset","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Site went down due to PSC3 dysfonction SS IHS Pascaline=
 confirmed// Site stabilized.Power resolved at 10:15 AM But site still down=
 and up after power reset","danick.tchakouani@sagemcom.com","428","09-02-20=
25 09:45:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_973","IHS_YND_796","NOCINC0004294708","N=
koabang Ebolmedjock","","09-02-2025 09:25:33","09-02-2025 09:17:16","09-02-=
2025 09:17:17","Active// No power issue, site is on Gen with Ubaie=3D53,6V,=
 Lionel Adjep(655184876) from Huawei is informed","Mba Lazare Herve","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue, site is on Gen with Ubaie=3D53,6V, Lionel Ad=
jep(655184876) from Huawei is informed","danick.tchakouani@sagemcom.com","4=
98","09-02-2025 09:25:33","Sagemcom CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004294496","Eke=
kam","","09-02-2025 08:51:50","09-02-2025 08:43:38","09-02-2025 10:07:28","=
Hybrid Gen Site, site went down due to hybrid system dysfunctionning//He re=
set and Gen started manaully","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Hybrid","Hybrid Module","Hybrid Gen Site, site went down due to=
 hybrid system dysfunctionning//He reset and Gen started manaully","danick.=
tchakouani@sagemcom.com","493","09-02-2025 08:51:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004294454","A=
kak-Nkozoa-MTN-IHS","","09-02-2025 08:47:09","09-02-2025 08:39:55","09-02-2=
025 08:49:17","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid Outage, site Down due to poor backup // eneo r=
eturn","danick.tchakouani@sagemcom.com","264120","09-02-2025 08:47:09","Sag=
emcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004294439","Elo=
umdem stade","","09-02-2025 08:43:36","09-02-2025 08:37:27","09-02-2025 08:=
53:02","Site went down due to insufficiency of rectifier due to load increa=
se, IHS SS FELIX ZAMBE is confirmed// Site stabilized","Fanda Brice","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down due t=
o insufficiency of rectifier due to load increase, IHS SS FELIX ZAMBE is co=
nfirmed// Site stabilized","danick.tchakouani@sagemcom.com","370","09-02-20=
25 08:43:36","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004294326","Bri=
quetterie","","09-02-2025 08:32:11","09-02-2025 08:28:02","09-02-2025 08:54=
:02","Grid outage, no space to deploy a mobile gen // Grid restored","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e, no space to deploy a mobile gen // Grid restored","danick.tchakouani@sag=
emcom.com","250","09-02-2025 08:32:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004294189","M=
imboman-Ecole","","09-02-2025 08:14:53","09-02-2025 08:07:35","09-02-2025 0=
8:13:35","Grid outage site went down before gen start due to poor battery b=
ackup // Gen auatomatically started","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site w=
ent down before gen start due to poor battery backup // Gen auatomatically =
started","danick.tchakouani@sagemcom.com","439","09-02-2025 08:14:53","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0004294074","H=
-Prince","","09-02-2025 08:01:44","09-02-2025 07:59:34","09-02-2025 08:01:4=
2","Grid outage, site went down before gen start due to poor battery backup=
 // Gen start automatically","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // Gen start automatically","dan=
ick.tchakouani@sagemcom.com","131","09-02-2025 08:01:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004294005","M=
ontee-Des-Soeurs","","09-02-2025 07:50:45","09-02-2025 07:41:34","09-02-202=
5 09:03:16","Grid outage, site went down before gen start due to poor batte=
ry backup and which completely turned off equipments // Gen manually starte=
d","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Battery Low","Grid outage, site went down before gen start due to po=
or battery backup and which completely turned off equipments // Gen manuall=
y started","danick.tchakouani@sagemcom.com","552","09-02-2025 07:50:45","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004293746","Barriere=
 IHS","","09-02-2025 07:11:00","09-02-2025 06:35:46","09-02-2025 06:38:18",=
"Cascaded Incident from TTO4321520","Hyemafo Gildas","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID =
, Ubaie=3D54.V site On Grid The Tx FME Fulbert(654266068) from Huawei is in=
formed","system","264637","09-02-2025 07:11:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0004293745","MEFOU AS=
SI","","09-02-2025 07:11:00","09-02-2025 06:35:46","09-02-2025 06:38:18","C=
ascaded Incident from TTO4321520","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID , Uba=
ie=3D54.V site On Grid The Tx FME Fulbert(654266068) from Huawei is informe=
d","system","264638","09-02-2025 07:11:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004293612","M=
efou-Assi","IHS_YND_537, IHS_YND_696","09-02-2025 06:40:00","09-02-2025 06:=
35:46","09-02-2025 06:38:18","ACTIVE//No power issue on site GRID , Ubaie=
=3D54.V site On Grid The Tx FME Fulbert(654266068) from Huawei is informed"=
,"Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D54=
.V site On Grid The Tx FME Fulbert(654266068) from Huawei is informed","wil=
fried.kameni@sagemcom.com","255","09-02-2025 06:40:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0004293431","S=
ous Prefecture","","09-02-2025 05:54:51","09-02-2025 03:37:37","09-02-2025 =
03:42:00",":   No power issue on site Ubaie:53,7V;  site on Grid.The Tx FME=
 Georges ( 697461814)) from Huawei is informed","Fanda Brice","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",":=
   No power issue on site Ubaie:53,7V;  site on Grid.The Tx FME Georges ( 6=
97461814)) from Huawei is informed","wilfried.kameni@sagemcom.com","8235","=
09-02-2025 05:54:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004293417","N=
kolfon Cimencam","","09-02-2025 05:49:51","09-02-2025 03:15:26","09-02-2025=
 03:20:19","ACTIVE//No power issue on site U=3D54,5v site on Gen FME Fulber=
t (654266068) of huawei is informed.Notice that site is impacted by Afanoya=
 II Who is not our responsability","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No =
power issue on site U=3D54,5v site on Gen FME Fulbert (654266068) of huawei=
 is informed.Notice that site is impacted by Afanoya II Who is not our resp=
onsability","wilfried.kameni@sagemcom.com","9266","09-02-2025 05:49:51","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004293307","Mes=
sa Carriere","","09-02-2025 05:15:55","08-02-2025 22:05:31","08-02-2025 22:=
17:44","Site went down due to insufficiency of rectifier  Fran=E7ois IHS co=
nfirmed // Site stabilized","Mboua Thierry","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down due to insufficiency of rectif=
ier  Fran=E7ois IHS confirmed // Site stabilized","wilfried.kameni@sagemcom=
.com","25825","09-02-2025 05:15:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004293292","M=
efou-Assi","","09-02-2025 05:06:09","09-02-2025 04:59:56","09-02-2025 05:04=
:59","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed..","Fanda Brice","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed..","wilfried.kameni@sagemcom.=
com","374","09-02-2025 05:06:09","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004293199","Nko=
lmvack","","09-02-2025 04:32:05","09-02-2025 04:15:41","09-02-2025 04:59:48=
","site went down because gen start and stopped with high temp alarm // he =
added water  2L and manually start the gen","Parker Tchoup","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","s=
ite went down because gen start and stopped with high temp alarm // he adde=
d water  2L and manually start the gen","wilfried.kameni@sagemcom.com","985=
","09-02-2025 04:32:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0004292353","M=
arche Odza","","09-02-2025 00:31:27","09-02-2025 00:15:08","09-02-2025 07:2=
1:50","Access issue during the night due to landlord  Grid bad voltage, Sit=
e went down because Gen failed to start causing by bad voltage// He bypasse=
d Grid and started Gen manualy","Albran Byorel","Access Denial","Lease Or L=
egal","Landlord Related Issues","Access Issue - Land Lord","Access issue du=
ring the night due to landlord  Grid bad voltage, Site went down because Ge=
n failed to start causing by bad voltage// He bypassed Grid and started Gen=
 manualy","wilfried.kameni@sagemcom.com","980","09-02-2025 00:31:27","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004292304","Nomayos =
montee Meche","","09-02-2025 00:21:31","09-02-2025 00:08:22","09-02-2025 00=
:32:09","Cascaded Incident from TTO4319969","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went =
down because gen started and stopped due to grid bad voltage // He bypassed=
 Grid and started Gen manualy","system","280446","09-02-2025 00:21:31","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004292305","Nkolfon =
Cimencam","","09-02-2025 00:21:31","09-02-2025 00:08:22","09-02-2025 00:32:=
09","Cascaded Incident from TTO4319969","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because gen started and stopped due to grid bad voltage // He bypassed =
Grid and started Gen manualy","system","280446","09-02-2025 00:21:31","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004292296","Nkenglik=
ok","","09-02-2025 00:20:18","09-02-2025 00:03:22","09-02-2025 00:33:07","C=
ascaded Incident from TTO4319772","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause gen started and stopped due to grid bad voltage // He bypassed Grid =
and started Gen manualy","system","280745","09-02-2025 00:20:18","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004292299","Mambine"=
,"","09-02-2025 00:20:18","09-02-2025 00:03:22","09-02-2025 00:33:07","Casc=
aded Incident from TTO4319772","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid fluctuation, site went down because =
gen started and stopped due to grid bad voltage // He bypassed Grid and sta=
rted Gen manualy","system","280743","09-02-2025 00:20:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004292297","Ebeba","=
","09-02-2025 00:20:18","09-02-2025 00:03:22","09-02-2025 00:33:07","Cascad=
ed Incident from TTO4319772","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuation, site went down because ge=
n started and stopped due to grid bad voltage // He bypassed Grid and start=
ed Gen manualy","system","280744","09-02-2025 00:20:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004292298","Nomayos-=
IHS","","09-02-2025 00:20:18","09-02-2025 00:03:22","09-02-2025 00:33:07","=
Cascaded Incident from TTO4319772","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuation, site went down beca=
use gen started and stopped due to grid bad voltage // He bypassed Grid and=
 started Gen manualy","system","280743","09-02-2025 00:20:18","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004292293","Sous Pre=
fecture","","09-02-2025 00:20:17","09-02-2025 00:03:22","09-02-2025 00:33:0=
7","Cascaded Incident from TTO4319772","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation, site went down =
because gen started and stopped due to grid bad voltage // He bypassed Grid=
 and started Gen manualy","system","280744","09-02-2025 00:20:17","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004292295","Mbankomo=
 IHS","","09-02-2025 00:20:17","09-02-2025 00:03:22","09-02-2025 00:33:07",=
"Cascaded Incident from TTO4319772","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause gen started and stopped due to grid bad voltage // He bypassed Grid an=
d started Gen manualy","system","280745","09-02-2025 00:20:17","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004292294","Mandoumb=
a OCM","","09-02-2025 00:20:17","09-02-2025 00:03:22","09-02-2025 00:33:07"=
,"Cascaded Incident from TTO4319772","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation, site went dow=
n because gen started and stopped due to grid bad voltage // He bypassed Gr=
id and started Gen manualy","system","280743","09-02-2025 00:20:17","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004292210","Eto koss=
 Yde","","09-02-2025 00:17:05","08-02-2025 23:05:56","08-02-2025 23:08:58",=
"Cascaded Incident from TTO4318966","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down du to insufficiency o=
f rectifier IHS SS FELIX ZAMBE is informed // site stabilized","system","27=
6877","09-02-2025 00:17:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004292211","ELOUMDEM=
 CARRIERE 2","","09-02-2025 00:17:05","08-02-2025 23:05:56","08-02-2025 23:=
08:58","Cascaded Incident from TTO4318966","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down du to insuffic=
iency of rectifier IHS SS FELIX ZAMBE is informed // site stabilized","syst=
em","276877","09-02-2025 00:17:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004292093","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_791, IHS_YND_695, IHS_YND_348, I=
HS_YND_339, IHS_YND_697, IHS_YND_762, IHS_YND_350","09-02-2025 00:12:33","0=
9-02-2025 00:03:22","09-02-2025 00:33:07","Grid fluctuation, site went down=
 because gen started and stopped due to grid bad voltage // He bypassed Gri=
d and started Gen manualy","Fanda Brice","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","Grid fluctuation, site went down be=
cause gen started and stopped due to grid bad voltage // He bypassed Grid a=
nd started Gen manualy","wilfried.kameni@sagemcom.com","552","09-02-2025 00=
:12:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004291692","Jean Ves=
pa 2","","08-02-2025 23:29:32","08-02-2025 18:44:55","08-02-2025 19:13:35",=
"Cascaded Incident from TTO4316992","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to cable burnt =
at ATS//We change cable and site on grid ","system","270938","08-02-2025 23=
:29:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004291682","Crf-Mban=
kolo-IHS","","08-02-2025 23:29:12","08-02-2025 18:53:39","08-02-2025 19:21:=
57","Cascaded Incident from TTO4316946","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to cable bu=
rnt at ATS//We change cable and site on grid ","system","270614","08-02-202=
5 23:29:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004291642","Eto koss=
 Yde","","08-02-2025 23:22:26","08-02-2025 18:37:24","08-02-2025 19:20:54",=
"Cascaded Incident from TTO4316838","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because gen failed to=
 start due to grid bad voltage // Gen manually started","system","1221090",=
"08-02-2025 23:22:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004291276","Mambine"=
,"","08-02-2025 23:09:58","08-02-2025 16:15:41","08-02-2025 17:03:35","Casc=
aded Incident from TTO4315941","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","08/02/2025  17:03:30","system","1222213",=
"08-02-2025 23:09:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004291278","Nkongtoc=
k","","08-02-2025 23:09:58","08-02-2025 16:15:41","08-02-2025 17:03:35","Ca=
scaded Incident from TTO4315941","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","08/02/2025  17:03:30","system","122=
2214","08-02-2025 23:09:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004291277","Angongo"=
,"","08-02-2025 23:09:58","08-02-2025 16:15:41","08-02-2025 17:03:35","Casc=
aded Incident from TTO4315941","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","08/02/2025  17:03:30","system","1222215",=
"08-02-2025 23:09:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004291271","Mandoumb=
a OCM","","08-02-2025 23:09:57","08-02-2025 16:15:41","08-02-2025 17:03:35"=
,"Cascaded Incident from TTO4315941","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","08/02/2025  17:03:30","system",=
"1222214","08-02-2025 23:09:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004291275","OKOA Pea=
ge","","08-02-2025 23:09:57","08-02-2025 16:15:41","08-02-2025 17:03:35","C=
ascaded Incident from TTO4315941","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","08/02/2025  17:03:30","system","122221=
4","08-02-2025 23:09:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004291272","Nkenglik=
ok","","08-02-2025 23:09:57","08-02-2025 16:15:41","08-02-2025 17:03:35","C=
ascaded Incident from TTO4315941","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","08/02/2025  17:03:30","system","12=
22213","08-02-2025 23:09:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004291273","Ebeba","=
","08-02-2025 23:09:57","08-02-2025 16:15:41","08-02-2025 17:03:35","Cascad=
ed Incident from TTO4315941","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","08/02/2025  17:03:30","system","1222212","0=
8-02-2025 23:09:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004291274","Nomayos-=
IHS","","08-02-2025 23:09:57","08-02-2025 16:15:41","08-02-2025 17:03:35","=
Cascaded Incident from TTO4315941","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","08/02/2025  17:03:30","system","12222=
15","08-02-2025 23:09:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004291270","Sous Pre=
fecture","","08-02-2025 23:09:56","08-02-2025 16:15:41","08-02-2025 17:03:3=
5","Cascaded Incident from TTO4315941","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","08/02/2025  17:03:30","system","1=
222212","08-02-2025 23:09:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004291261","Nomayos =
montee Meche","","08-02-2025 23:08:33","08-02-2025 16:15:41","08-02-2025 17=
:29:19","Cascaded Incident from TTO4315935","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","08/02/2025  17:03:30","syste=
m","265534","08-02-2025 23:08:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004291262","Nkolfon =
Cimencam","","08-02-2025 23:08:33","08-02-2025 16:15:41","08-02-2025 17:29:=
19","Cascaded Incident from TTO4315935","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","08/02/2025  17:03:30","system=
","265534","08-02-2025 23:08:33","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004291259","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","08-02-2025 23:08:20","08-02-2025 23:05=
:56","08-02-2025 23:08:58","Site went down du to insufficiency of rectifier=
, IHS SS FELIX ZAMBE is informed // site stabilized","Fanda Brice","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","Site went down du to i=
nsufficiency of rectifier IHS SS FELIX ZAMBE is informed // site stabilized=
","wilfried.kameni@sagemcom.com","146","08-02-2025 23:08:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004290426","N=
gouetou","","08-02-2025 21:40:32","08-02-2025 20:55:23","08-02-2025 21:00:5=
0","ACTIVE//No power issue on site, site on Gen The Tx FME Gregoire/6545474=
79/ from huawei is informed. Repetitive issue","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE//No power issue on site, site on Gen The Tx FME Gregoire/654547479/ =
from huawei is informed. Repetitive issue","wilfried.kameni@sagemcom.com","=
2711","08-02-2025 21:40:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004290164","S=
imbock OCM","","08-02-2025 20:58:46","08-02-2025 20:53:31","08-02-2025 21:5=
2:29","Access issue due to landlord, Site went down because gen start and s=
topped due to grid bad voltage // Grid stabilized","Hyemafo Gildas","Access=
 Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lo=
rd","Access issue due to landlord, Site went down because gen start and sto=
pped due to grid bad voltage // Grid stabilized","wilfried.kameni@sagemcom.=
com","316","08-02-2025 20:58:46","Sagemcom CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004290154","Mes=
sassi okolo","","08-02-2025 20:56:06","08-02-2025 20:50:57","08-02-2025 20:=
55:09","ACTIVE//No power issue on site Ubaie=3D54.5V, site on Grid  The TX =
Fme Synphorien 691316854 of Huewai is informed","Fabrice Pouakam","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE//No power issue on site Ubaie=3D54.5V, site on Grid  The TX Fme S=
ynphorien 691316854 of Huewai is informed","wilfried.kameni@sagemcom.com","=
311","08-02-2025 20:56:06","Sagemcom CMR"
"Closed Complete","Site Down","T0638","IHS_YND_318","NOCINC0004290149","SOA=
 University","","08-02-2025 20:55:05","08-02-2025 20:48:58","08-02-2025 22:=
04:21","Grid Outage Site went down due to Gen Contactors No existed //he By=
bass it and Manually Started the Gen","Siligap Boris","Equipment Repair","P=
assive","ACDG Gen","ACDG - Load Contactor","Grid Outage Site went down due =
to Gen Contactors No existed //he Bybass it and Manually Started the Gen","=
wilfried.kameni@sagemcom.com","368","08-02-2025 20:55:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004290049","O=
LAMA","","08-02-2025 20:36:45","08-02-2025 19:36:33","08-02-2025 19:41:22",=
"No power issue site on gen with U=3D54,5v RM Alain Tchaptchet(691144423)  =
from Huawei is informed ","Fanda Brice","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
gen with U=3D54,5v RM Alain Tchaptchet(691144423)  from Huawei is informed =
","wilfried.kameni@sagemcom.com","3613","08-02-2025 20:36:45","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004290034","B=
iteng-Maetur","","08-02-2025 20:34:58","08-02-2025 20:27:53","08-02-2025 21=
:33:36","Site went down due to 01 rctifiers faulty // He changed 01 rectifi=
er, site on grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to 01 rctifiers faulty // He chan=
ged 01 rectifier, site on grid","wilfried.kameni@sagemcom.com","426","08-02=
-2025 20:34:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004290002","A=
wae Ewonkan","","08-02-2025 20:25:45","08-02-2025 20:19:39","08-02-2025 22:=
45:50","Site went down due to insufficiency rectifiers (06 rectfiers) due t=
o load increase on site IHS SS Alphonse is informed and is confirmed//Site =
stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to insufficiency rectifiers (06 rectfiers)=
 due to load increase on site IHS SS Alphonse is informed and is confirmed/=
/Site stabilized","wilfried.kameni@sagemcom.com","367","08-02-2025 20:25:45=
","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004289671","Aka=
k-Nkozoa-MTN-IHS","","08-02-2025 19:22:07","08-02-2025 19:16:57","08-02-202=
5 19:25:22","Grid fluctuation, site went down because gen started and stopp=
ed due to grid bad voltage // He bypassed Grid and started Gen manualy","Fa=
brice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, site went down because gen started and stop=
ped due to grid bad voltage // He bypassed Grid and started Gen manualy","w=
ilfried.kameni@sagemcom.com","312","08-02-2025 19:22:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004289464","J=
-Vespa","IHS_YND_544","08-02-2025 19:08:46","08-02-2025 18:44:55","08-02-20=
25 19:13:35","Site went down due to cable burnt at ATS//We change cable and=
 site on grid ","Mboua Thierry","Equipment Repair","Passive","Infrastructur=
e","Armoured Cable","Site went down due to cable burnt at ATS//We change ca=
ble and site on grid ","wilfried.kameni@sagemcom.com","1432","08-02-2025 19=
:08:46","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004289426","Jea=
n Vespa","IHS_YND_574","08-02-2025 18:59:01","08-02-2025 18:53:39","08-02-2=
025 19:21:57","Site went down due to cable burnt at ATS//We change cable an=
d site on grid ","Mboua Thierry","Equipment Repair","Passive","Infrastructu=
re","Armoured Cable","Site went down due to cable burnt at ATS//We change c=
able and site on grid ","wilfried.kameni@sagemcom.com","323","08-02-2025 18=
:59:01","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004289351","MEF=
OU ASSI","IHS_YND_737","08-02-2025 18:41:31","08-02-2025 18:37:24","08-02-2=
025 19:20:54","Site went down because gen failed to start due to grid bad v=
oltage // Gen manually started","Fanda Brice","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Site went down because gen fai=
led to start due to grid bad voltage // Gen manually started","wilfried.kam=
eni@sagemcom.com","249","08-02-2025 18:41:31","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004289074","NKO=
MEKUI OCM","","08-02-2025 17:46:58","08-02-2025 17:44:49","08-02-2025 17:45=
:25","No power issue on site U=3D54.5 V site on Gen.Site impacted by Mbanko=
lo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site U=3D54.5 V site on Gen.Site impacted by Mbankolo Camt=
el and not managing by IHS","wilfried.kameni@sagemcom.com","130","08-02-202=
5 17:46:58","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004289055","OBA=
M NGOLA OCM","","08-02-2025 17:43:34","08-02-2025 17:33:25","08-02-2025 17:=
36:10","Active: no power issue, site is on grid with Ubaie=3D53V, Martial(6=
90087047) from Huawei is informed","MINKA NICOLAS","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no p=
ower issue, site is on grid with Ubaie=3D53V, Martial(690087047) from Huawe=
i is informed","wilfried.kameni@sagemcom.com","610","08-02-2025 17:43:34","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004288854","S=
IMBOCK BONAMBAPE","","08-02-2025 17:16:12","08-02-2025 16:34:36","08-02-202=
5 17:41:51","Active//No power issue site on grid with U=3D56,5 V Mbah Osiah=
 from Huawei is informed Notice that it is the repetitive issue","Hyemafo G=
ildas","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No power issue site on grid with U=3D56,5 V Mbah=
 Osiah from Huawei is informed Notice that it is the repetitive issue","wil=
fried.kameni@sagemcom.com","2497","08-02-2025 17:16:12","Sagemcom CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0004288802","Ema=
na Lycee","","08-02-2025 17:07:13","08-02-2025 16:54:49","08-02-2025 17:02:=
24","No power issue on site Ubaie=3D54.4V, site on Gen  //The TX Fme Synpho=
rien 691316854 of Huewai is informed","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site Ubaie=3D54.4V, site on Gen  //The TX Fme Synphorien 6913168=
54 of Huewai is informed","wilfried.kameni@sagemcom.com","745","08-02-2025 =
17:07:13","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004288784","Ngu=
ila","","08-02-2025 17:03:44","08-02-2025 16:53:20","08-02-2025 17:07:50","=
Grid outage, Site went down because Gen stopped with ""High temp""// He ope=
n door and started Gen manually","Parker Tchoup","Equipment Repair","Passiv=
e","ACDG Gen","Gen Temp High","Grid outage, Site went down because Gen stop=
ped with ""High temp""// He open door and started Gen manually","wilfried.k=
ameni@sagemcom.com","625","08-02-2025 17:03:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0004288703","F=
ebe Village","","08-02-2025 16:48:28","08-02-2025 16:40:54","08-02-2025 17:=
42:13","Grid outage.gen failed to start due to alarm""high temp""//We add w=
ater and gen manually started ","Mboua Thierry","Equipment Repair","Passive=
","ACDG Gen","ACDG - Radiator","Grid outage.gen failed to start due to alar=
m""high temp""//We add water and gen manually started ","wilfried.kameni@sa=
gemcom.com","527","08-02-2025 16:48:28","Sagemcom CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0004288617","Nom=
ayos","IHS_YND_314, IHS_YND_367, IHS_YND_791, IHS_YND_348, IHS_YND_339, IHS=
_YND_697, IHS_YND_762, IHS_YND_330, IHS_YND_350, IHS_YND_335, IHS_YND_349",=
"08-02-2025 16:33:02","08-02-2025 16:15:41","08-02-2025 17:29:19","Site wen=
t down because 02/07 rectifiers dysfunctionned// He reset rectifiers,site o=
n Grid","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","08/02/2025  17:03:30","wilfried.kameni@sagemcom.com","1042","08-02-=
2025 16:33:02","Sagemcom CMR"
"Closed Complete","Site Down","T1861","IHS_YND_682","NOCINC0004288494","MON=
TEE NKONDENGUI","","08-02-2025 16:09:58","08-02-2025 16:05:39","08-02-2025 =
16:10:48","No power issue site on grid with U=3D54v Eloundou from Huawei is=
 informed	","Albran Byorel","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54v Eloundou from Huawei is informed	","wilfried.kameni@sagemcom.com","2=
59","08-02-2025 16:09:58","Sagemcom CMR"
"Closed Complete","Warning","T0108","IHS_YND_235","NOCINC0004288427","Etoug=
-Ebe 2","","08-02-2025 15:51:34","","","site went on Batterry due To Grid O=
utage //Grid Power Restored","","Warning","Warning","POWER","Warning - Site=
 on Battery","site went on Batterry due To Grid Outage //Grid Power Restore=
d","wilfried.kameni@sagemcom.com","358364","08-02-2025 15:51:34","Sagemcom =
CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004288390","Elo=
umdem stade","","08-02-2025 15:47:52","08-02-2025 15:40:26","08-02-2025 15:=
54:11","Site went down due to inssufisence of rectifier // site stabilized"=
,"Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to inssufisence of rectifier // site stabilized","wilfr=
ied.kameni@sagemcom.com","447","08-02-2025 15:47:52","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004288180","Mes=
sa Carriere","","08-02-2025 15:29:01","08-02-2025 15:26:50","08-02-2025 15:=
26:51","Incorrectly Logged Tickets","Mboua Thierry","Incorrectly Logged Tic=
kets","Error","Error","Error","Incorrectly Logged Tickets","wilfried.kameni=
@sagemcom.com","132","08-02-2025 15:29:01","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004287972","CRH=
-Etoug-Ebe","","08-02-2025 15:13:25","08-02-2025 15:09:16","08-02-2025 15:2=
4:30","Grid outage, site went down before gen start due to poor battery bac=
kup // gen start automatically(investigation ongoing)","Hyemafo Gildas","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gr=
id outage, site went down before gen start due to poor battery backup // ge=
n start automatically(investigation ongoing)","wilfried.kameni@sagemcom.com=
","290","08-02-2025 15:13:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004287952","L=
eboudi","","08-02-2025 15:09:41","08-02-2025 14:38:11","08-02-2025 14:42:31=
","No power issue site and  with Ubaie=3D54.4  V site on Gen The  FME TX Mo=
uamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue site and  with Ubaie=3D54.4  V site on Gen The  FME=
 TX Mouamadou/658791013 //From Huawei is informed","wilfried.kameni@sagemco=
m.com","1891","08-02-2025 15:09:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004287888","B=
arriere","","08-02-2025 15:03:15","08-02-2025 14:18:43","08-02-2025 14:22:2=
8","Active: No power issue, site is on grid with Ubaie=3D53V,Rm Alain (6911=
44423) from Huawei is informed","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No pow=
er issue, site is on grid with Ubaie=3D53V,Rm Alain (691144423) from Huawei=
 is informed","wilfried.kameni@sagemcom.com","2674","08-02-2025 15:03:15","=
Sagemcom CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0004287818","Kon=
dengui MTN","","08-02-2025 14:56:16","08-02-2025 14:48:02","08-02-2025 14:5=
0:44","No power issue site on grid with U=3D54.5v KOKAK(694569589) From Tel=
is is working on site","Albran Byorel","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D54.5v KOKAK(694569589) From Telis is working on site","wilfrie=
d.kameni@sagemcom.com","495","08-02-2025 14:56:16","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004287746","Nko=
lafeme","","08-02-2025 14:48:50","08-02-2025 14:41:38","08-02-2025 17:43:50=
","Grid outage, site went down due to gen gen overload(20Kva, 375A), SS IHS=
 Pascaline is informed//Site stabilized","TIENTCHEU NZETCHIEU GAEL","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went =
down due to gen gen overload(20Kva, 375A), SS IHS Pascaline is informed//Si=
te stabilized","wilfried.kameni@sagemcom.com","433","08-02-2025 14:48:50","=
Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004287739","Bas=
tos Amb Coree","","08-02-2025 14:47:25","08-02-2025 14:39:17","08-02-2025 1=
4:44:49","ACTIVE//No power issue on site Ubaie =3D54.4V site on GridThe TX =
FME Eloundou/693212405  from huawei is informed","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No =
power issue on site Ubaie =3D54.4V site on GridThe TX FME Eloundou/69321240=
5  from huawei is informed","wilfried.kameni@sagemcom.com","489","08-02-202=
5 14:47:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0004287715","F=
ebe Village","","08-02-2025 14:44:22","08-02-2025 14:36:28","08-02-2025 15:=
18:50","Grid outage.gen failed tostart due to alarm""high temp""// We add w=
ater and gen manually started ","Mboua Thierry","Equipment Repair","Passive=
","ACDG Gen","ACDG - Radiator","Grid outage.gen failed tostart due to alarm=
""high temp""// We add water and gen manually started ","wilfried.kameni@sa=
gemcom.com","476","08-02-2025 14:44:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004287683","M=
essa-Carriere OCM","","08-02-2025 14:39:08","08-02-2025 14:25:44","08-02-20=
25 17:37:16","Grid outage.no space to deploy mobile gen //Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age.no space to deploy mobile gen //Grid return","wilfried.kameni@sagemcom.=
com","805","08-02-2025 14:39:08","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004285668","BIY=
EMASSI NIKI","","08-02-2025 12:38:14","08-02-2025 12:29:06","08-02-2025 13:=
46:06","Site went down due to PWC overloaded (12kva 250 A)  F=E9lix Zambe i=
s confirmed // Site stabilized","Hyemafo Gildas","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Site went down due to PWC ove=
rloaded (12kva 250 A)  F=E9lix Zambe is confirmed // Site stabilized","wilf=
ried.kameni@sagemcom.com","593","08-02-2025 12:38:14","Sagemcom CMR"
"Closed Complete","Site Down","T1861","IHS_YND_682","NOCINC0004285533","MON=
TEE NKONDENGUI","","08-02-2025 12:33:53","08-02-2025 12:25:46","08-02-2025 =
12:35:09","No  power issue U =3D52.4V site on Grid. The Tx FME  Eloundou (6=
93212405 )from Huawei is informed","Albran Byorel","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No  power is=
sue U =3D52.4V site on Grid. The Tx FME  Eloundou (693212405 )from Huawei i=
s informed","wilfried.kameni@sagemcom.com","488","08-02-2025 12:33:53","Sag=
emcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004285196","Mes=
sa Carriere","","08-02-2025 11:56:08","08-02-2025 11:47:02","08-02-2025 11:=
59:02","Grid outage, site went down because gen fails to start due to gen c=
ard faulty, IHS SS PASCALINE is informed // Gen manually started","Mboua Th=
ierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage, site went down because gen fails to start due to gen card faulty, =
IHS SS PASCALINE is informed // Gen manually started","wilfried.kameni@sage=
mcom.com","546","08-02-2025 11:56:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004285113","Nkomkana=
 2","","08-02-2025 11:47:37","08-02-2025 11:42:21","08-02-2025 14:01:57","C=
ascaded Incident from TTO4312011","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage//He deployed MDG of 20kv=
a","system","275256","08-02-2025 11:47:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004285114","Nkomkana=
","","08-02-2025 11:47:37","08-02-2025 11:42:21","08-02-2025 14:01:57","Cas=
caded Incident from TTO4312011","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage//He deployed MDG of 20kva","system","27=
5256","08-02-2025 11:47:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004285115","Entree C=
ite Verte","","08-02-2025 11:47:37","08-02-2025 11:42:21","08-02-2025 14:01=
:57","Cascaded Incident from TTO4312011","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage//He deployed MDG of=
 20kva","system","275255","08-02-2025 11:47:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004285096","C=
ite-Verte","IHS_YND_138, IHS_YND_200, IHS_YND_543","08-02-2025 11:44:35","0=
8-02-2025 11:42:21","08-02-2025 14:01:57","Grid outage//He deployed MDG of =
20kva","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Grid outage//He deployed MDG of 20kva","wilfried.kameni@sagemcom.com","1=
36","08-02-2025 11:44:35","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004284769","Nko=
lafeme","","08-02-2025 11:15:21","08-02-2025 10:41:55","08-02-2025 11:10:56=
","Grid outage, site went down due to gen gen overload(20Kva, 375A), SS IHS=
 Pascaline is informed// Grid return","TIENTCHEU NZETCHIEU GAEL","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went dow=
n due to gen gen overload(20Kva, 375A), SS IHS Pascaline is informed// Grid=
 return","wilfried.kameni@sagemcom.com","2031","08-02-2025 11:15:21","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004284417","N=
YOM 2 IHS","","08-02-2025 10:22:35","08-02-2025 10:19:37","08-02-2025 10:19=
:38","N o power issue site on grid with U=3D54v //site up at 10:21 AM Symph=
orien(675295205) from Huawei is informed	","Fabrice Pouakam","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N =
o power issue site on grid with U=3D54v //site up at 10:21 AM Symphorien(67=
5295205) from Huawei is informed	","wilfried.kameni@sagemcom.com","179","08=
-02-2025 10:22:35","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004284303","Mel=
en Ba'aba","","08-02-2025 10:05:57","08-02-2025 09:49:12","08-02-2025 09:49=
:13","No ACTIVE // Active// No power issue, site is on GEN with Ubaie=3D54,=
4 V TX FME Julien(693095849) from Huawei is informed and inform us that pla=
nned works from huawei,","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No ACTIVE // Active// =
No power issue, site is on GEN with Ubaie=3D54,4 V TX FME Julien(693095849)=
 from Huawei is informed and inform us that planned works from huawei,","wi=
lfried.kameni@sagemcom.com","1006","08-02-2025 10:05:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004284300","N=
kozoa","","08-02-2025 10:05:41","08-02-2025 09:55:31","08-02-2025 10:24:31"=
,"Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Feli=
x bateu is informed and confirmed // Site stabilized","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site w=
ent down due to gen overload (20kva, 340A) SS HIS Felix bateu is informed a=
nd confirmed // Site stabilized","danick.tchakouani@sagemcom.com","611","08=
-02-2025 10:05:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004284223","L=
eboudi","","08-02-2025 09:56:09","08-02-2025 09:35:01","08-02-2025 09:40:52=
","No power issue site and  with Ubaie=3D54.4  V site on Gen The  FME TX Mo=
uamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue site and  with Ubaie=3D54.4  V site on Gen The  FME=
 TX Mouamadou/658791013 //From Huawei is informed","wilfried.kameni@sagemco=
m.com","1269","08-02-2025 09:56:09","Sagemcom CMR"
"Closed Complete","Site Down","T1554","IHS_YND_286","NOCINC0004284179","Dag=
obert","","08-02-2025 09:50:13","08-02-2025 09:45:42","08-02-2025 10:38:25"=
,"Grid outage, site went down because gen start and stopped with over coure=
nt alarm (unpruven)  // Reset done and gen started","TIENTCHEU NZETCHIEU GA=
EL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage, site went down because gen start and stopped with over courent alarm =
(unpruven)  // Reset done and gen started","wilfried.kameni@sagemcom.com","=
297","08-02-2025 09:50:13","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004284115","Nko=
lafeme","","08-02-2025 09:41:37","08-02-2025 09:37:12","08-02-2025 09:58:08=
","Grid outage, site went down because gen start and stopped with 'high tem=
p' alarm // He added water and manually start the gen","TIENTCHEU NZETCHIEU=
 GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Grid outage, site went down because gen start and stop=
ped with 'high temp' alarm // He added water and manually start the gen","w=
ilfried.kameni@sagemcom.com","306","08-02-2025 09:41:37","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0004284069","Feb=
e Village","","08-02-2025 09:35:38","08-02-2025 09:30:29","08-02-2025 10:28=
:08","Grid outage, site went down because gen start and stopped with 'high =
temp' alarm // He added water and manually start the gen","Mboua Thierry","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, site went down because gen start and stopped with=
 'high temp' alarm // He added water and manually start the gen","wilfried.=
kameni@sagemcom.com","338","08-02-2025 09:35:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0004283985","Crf-Mban=
kolo-IHS","","08-02-2025 09:23:00","08-02-2025 09:17:43","08-02-2025 10:19:=
38","Cascaded Incident from TTO4310694","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation site went dow=
n because Gen failed to start due to Grid bad voltage and No RCP on site //=
 He bypass the Grid and Gen manually started","system","283391","08-02-2025=
 09:23:00","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004283965","Jea=
n Vespa","IHS_YND_574","08-02-2025 09:21:50","08-02-2025 09:17:43","08-02-2=
025 10:19:38","Grid fluctuation site went down because Gen failed to start =
due to Grid bad voltage and No RCP on site // He bypass the Grid and Gen ma=
nually started","Mboua Thierry","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Grid fluctuation site went down because Gen =
failed to start due to Grid bad voltage and No RCP on site // He bypass the=
 Grid and Gen manually started","wilfried.kameni@sagemcom.com","248","08-02=
-2025 09:21:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004283961","Jean Ves=
pa 2","","08-02-2025 09:21:00","08-02-2025 09:02:56","08-02-2025 10:09:29",=
"Cascaded Incident from TTO4310688","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation site went down be=
cause Gen failed to start due to Grid bad voltage and No RCP on site // He =
bypass the Grid and Gen manually started","system","277279","08-02-2025 09:=
21:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004283959","J=
-Vespa","IHS_YND_544","08-02-2025 09:20:06","08-02-2025 09:02:56","08-02-20=
25 10:09:29","Grid fluctuation site went down because Gen failed to start d=
ue to Grid bad voltage and No RCP on site // He bypass the Grid and Gen man=
ually started","Mboua Thierry","Grid Supply","Passive","Grid","National Gri=
d - Phase Controller Faulty","Grid fluctuation site went down because Gen f=
ailed to start due to Grid bad voltage and No RCP on site // He bypass the =
Grid and Gen manually started","wilfried.kameni@sagemcom.com","1031","08-02=
-2025 09:20:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004283955","O=
dza II","","08-02-2025 09:19:42","08-02-2025 09:06:26","08-02-2025 09:06:27=
","Active//No power issue U =3D54,5V site on Grid. The Tx FME Adjet (655-18=
-48-76 )from Huawei is informed.","Albran Byorel","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No po=
wer issue U =3D54,5V site on Grid. The Tx FME Adjet (655-18-48-76 )from Hua=
wei is informed.","danick.tchakouani@sagemcom.com","798","08-02-2025 09:19:=
42","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004283882","Mes=
sa Carriere","","08-02-2025 09:03:41","08-02-2025 08:54:31","08-02-2025 10:=
28:31","Grid outage, site went down because gen fails to start due to gen c=
ard faulty, IHS SS PASCALINE is informed // Gen manually started","Mboua Th=
ierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage, site went down because gen fails to start due to gen card faulty, =
IHS SS PASCALINE is informed // Gen manually started","wilfried.kameni@sage=
mcom.com","551","08-02-2025 09:03:41","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004283710","NKO=
MEKUI OCM","","08-02-2025 08:44:26","08-02-2025 08:43:17","08-02-2025 08:49=
:57","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted b=
y Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted =
by Mbankolo Camtel and not managing by IHS","wilfried.kameni@sagemcom.com",=
"70","08-02-2025 08:44:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0004283666","NKOLMEKO=
NG YDE","","08-02-2025 08:38:36","08-02-2025 08:31:02","08-02-2025 10:40:15=
","Site went down due to insufficiency of rectifier CAUSING by 02/07 rectif=
ier faulty, SS IHS BERNARD is informed // He added 02 rectifier: Site on gr=
id","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Site went down due to insufficiency of rectifier CAUSING by 02/07 r=
ectifier faulty, SS IHS BERNARD is informed // He added 02 rectifier: Site =
on grid","wilfried.kameni@sagemcom.com","455","08-02-2025 08:38:36","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004283558","Barriere=
 IHS","","08-02-2025 08:16:10","08-02-2025 08:07:13","08-02-2025 08:10:17",=
"Cascaded Incident from TTO4310221","Hyemafo Gildas","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active// No power issue on site Ubai=
e=3D52.6V site On Grid The Tx FME Fulbert(654266068) of huawei is informed"=
,"system","288214","08-02-2025 08:16:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004283548","M=
EFOU ASSI","IHS_YND_696","08-02-2025 08:15:18","08-02-2025 08:07:13","08-02=
-2025 08:10:17","Active// No power issue on site Ubaie=3D52.6V site On Grid=
 The Tx FME Fulbert(654266068) of huawei is informed","Fanda Brice","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power issue on site Ubaie=3D52.6V site On Grid The Tx FME =
Fulbert(654266068) of huawei is informed","wilfried.kameni@sagemcom.com","4=
87","08-02-2025 08:15:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004283529","M=
efou-Assi","","08-02-2025 08:11:47","08-02-2025 08:04:36","08-02-2025 08:10=
:42","Active// No power issue on site Ubaie=3D54.V site On Grid The Tx FME =
Fulbert(654266068) of huawei is informed","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power issue on site Ubaie=3D54.V site On Grid The Tx FME Fulbert(65426=
6068) of huawei is informed","wilfried.kameni@sagemcom.com","432","08-02-20=
25 08:11:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004282691","L=
abogenie","","08-02-2025 05:32:08","08-02-2025 05:27:57","08-02-2025 05:32:=
41","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed. Notice that it is the repetitive issue=
","","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FM=
E  Eloundou (693212405 )from Huawei is informed. Notice that it is the repe=
titive issue","wilfried.kameni@sagemcom.com","252","08-02-2025 05:32:08","S=
agemcom CMR"
"Closed Complete","Site Down","T0638","IHS_YND_318","NOCINC0004282488","SOA=
 University","","08-02-2025 04:51:08","08-02-2025 04:41:56","08-02-2025 04:=
55:49","Grid outage,site went down because gen failed to start due to grid =
bad voltage(02 phases off)//he did a bridge with the good phase","Siligap B=
oris","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid outage,site went down because gen failed to start due to grid bad=
 voltage(02 phases off)//he did a bridge with the good phase","wilfried.kam=
eni@sagemcom.com","553","08-02-2025 04:51:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004282440","S=
IMBOCK BONAMBAPE","","08-02-2025 04:26:28","08-02-2025 06:10:59","08-02-202=
5 06:42:47","Active//No power issue site on grid with U=3D56,5 V Mbah Osiah=
  from Huawei is informed Notice that it is the repetitive issue","Hyemafo =
Gildas","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No power issue site on grid with U=3D56,5 V Mba=
h Osiah  from Huawei is informed Notice that it is the repetitive issue","w=
ilfried.kameni@sagemcom.com","1778","08-02-2025 04:26:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004282418","M=
efou-Assi","","08-02-2025 04:15:05","08-02-2025 04:06:56","08-02-2025 04:11=
:05","ACTIVE//No power issue site on grid with U=3D54,6 V Mbah Osiah  from =
Huawei is informed","Fanda Brice","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue site o=
n grid with U=3D54,6 V Mbah Osiah  from Huawei is informed","ervine.mbezele=
@sagemcom.com","490","08-02-2025 04:15:05","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004282266","Nsi=
meyong Shell","","08-02-2025 03:31:20","08-02-2025 03:09:13","08-02-2025 11=
:31:13","Site went down due to Power cable has been stolen on Site (power c=
able between the PWC and the DC-box ) // he replaced the power cable betwee=
n the DC-Box and PWC","MINKA NICOLAS","Site Asset Theft","Theft","Theft","D=
C Cable Stolen","Site went down due to Power cable has been stolen on Site =
(power cable between the PWC and the DC-box ) // he replaced the power cabl=
e between the DC-Box and PWC","ervine.mbezele@sagemcom.com","1328","08-02-2=
025 03:31:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004282200","N=
kolfon Cimencam","","08-02-2025 03:19:10","08-02-2025 03:13:52","08-02-2025=
 03:18:56","ACTIVE//No power issue on site U=3D54,5v site on Gen FME Fulber=
t (654266068) of huawei is informed.Notice that site is impacted by Afanoya=
 II Who is not our responsability","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No =
power issue on site U=3D54,5v site on Gen FME Fulbert (654266068) of huawei=
 is informed.Notice that site is impacted by Afanoya II Who is not our resp=
onsability","ervine.mbezele@sagemcom.com","319","08-02-2025 03:19:10","Sage=
mcom CMR"
"Closed Complete","Site Down","T0417-1","IHS_YND_220","NOCINC0004282130","G=
olf Quater","","08-02-2025 02:49:55","08-02-2025 02:42:39","08-02-2025 02:4=
9:02","ACTIVE//No Power issue on site Ubaie=3D53,2V site on Grid The Tx FME=
 Eloumdou betrrand//693212405 from Huawei is informed","Mboua Thierry","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","ACTIVE//No Power issue on site Ubaie=3D53,2V site on Grid The Tx FM=
E Eloumdou betrrand//693212405 from Huawei is informed","ervine.mbezele@sag=
emcom.com","437","08-02-2025 02:49:55","Sagemcom CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0004281722","Djo=
nassi-Yde","","08-02-2025 00:35:56","08-02-2025 00:23:31","08-02-2025 00:28=
:14","ACTIVE//No power issue on site Ubaie=3D54.1V site on Grid Symphorien(=
650257151) from Huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//N=
o power issue on site Ubaie=3D54.1V site on Grid Symphorien(650257151) from=
 Huawei is informed","ervine.mbezele@sagemcom.com","746","08-02-2025 00:35:=
56","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004281651","Bas=
tos Amb Coree","","08-02-2025 00:24:00","08-02-2025 00:20:46","08-02-2025 0=
2:22:54","Grid Outage No Space to Deploy a MDG//Grid Restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No S=
pace to Deploy a MDG//Grid Restored","ervine.mbezele@sagemcom.com","196","0=
8-02-2025 00:24:00","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0004281216","Nlo=
ngkak","","07-02-2025 22:58:40","07-02-2025 22:40:29","07-02-2025 23:44:50"=
,"Grid outage, Site went down because Gen start and stopped with ""High tem=
ps ""alarm // he added water and manually start the Gen","Delor Telezing","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, Site went down because Gen start and stopped with=
 ""High temps ""alarm // he added water and manually start the Gen","ervine=
.mbezele@sagemcom.com","1092","07-02-2025 22:58:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0004281101","S=
ous Prefecture","","07-02-2025 22:39:34","07-02-2025 22:15:55","07-02-2025 =
22:20:00","ACTIVE//No power issue site on Grid Ubaie =3D53.7 V, The tx Huaw=
ei  Fulbert  (654266068) is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No =
power issue site on Grid Ubaie =3D53.7 V, The tx Huawei  Fulbert  (65426606=
8) is informed","ervine.mbezele@sagemcom.com","1420","07-02-2025 22:39:34",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004280928","Mel=
en Ba'aba","","07-02-2025 22:08:14","07-02-2025 21:59:03","08-02-2025 00:25=
:36","Site went down because CB 125 (A) Faulty in DC-Box//he bypass it and =
Site is on Grid ","Siligap Boris","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","Site went down because CB 125 =
(A) Faulty in DC-Box//he bypass it and Site is on Grid ","ervine.mbezele@sa=
gemcom.com","553","07-02-2025 22:08:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004280855","S=
IMBOCK BONAMBAPE","","07-02-2025 21:57:08","07-02-2025 21:25:56","07-02-202=
5 21:30:13","Active//No power issue site on grid with U=3D56,5 V Mbah Osiah=
  from Huawei is informed Notice that it is the repetitive issue","Hyemafo =
Gildas","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No power issue site on grid with U=3D56,5 V Mba=
h Osiah  from Huawei is informed Notice that it is the repetitive issue","e=
rvine.mbezele@sagemcom.com","1873","07-02-2025 21:57:08","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004280845","Aka=
k-Nkozoa-MTN-IHS","","07-02-2025 21:56:09","07-02-2025 21:45:02","07-02-202=
5 22:03:27","Grid fluctuation, site went down because gen started and stopp=
ed due to grid bad voltage // He bypassed Grid and started Gen manualy","Fa=
brice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, site went down because gen started and stop=
ped due to grid bad voltage // He bypassed Grid and started Gen manualy","e=
rvine.mbezele@sagemcom.com","668","07-02-2025 21:56:09","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004280273","NKO=
MEKUI OCM","","07-02-2025 20:40:37","07-02-2025 20:33:27","07-02-2025 20:42=
:10","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted b=
y Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","Affected by 3r=
d Party Site","Active//No power issue on site U=3D54.5 V site on Gen.Site i=
mpacted by Mbankolo Camtel and not managing by IHS","ervine.mbezele@sagemco=
m.com","432","07-02-2025 20:40:37","Sagemcom CMR"
"Closed Complete","Site Down","T1591","IHS_YND_172","NOCINC0004279973","Tra=
dex-Nkomo","","07-02-2025 19:52:32","07-02-2025 19:41:21","07-02-2025 20:02=
:20","No power issue site on grid with U=3D53,4v Jordan(651162743) from TEL=
IS  is working on site","Albran Byorel","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D53,4v Jordan(651162743) from TELIS  is working on site","ervi=
ne.mbezele@sagemcom.com","672","07-02-2025 19:52:32","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004279865","Mes=
sa Carriere","","07-02-2025 19:42:27","07-02-2025 19:35:19","07-02-2025 19:=
45:32"," FME informed us that 01/03 rectifier faulty SS IHS Fran=E7ois is i=
nformed and confirmed","Mboua Thierry","Equipment Repair","Passive","Rectif=
ier","Rectifier Module"," FME informed us that 01/03 rectifier faulty SS IH=
S Fran=E7ois is informed and confirmed","ervine.mbezele@sagemcom.com","429"=
,"07-02-2025 19:42:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0004279124","Messassi=
 Ngonlonk","","07-02-2025 17:48:50","07-02-2025 17:28:11","07-02-2025 17:58=
:11","Cascaded Incident from TTO4305028","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue site on grid wi=
th U=3D54v Team I-ENGINEERING /695278990/ working on site ","system","27575=
0","07-02-2025 17:48:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004279123","Akak-Nko=
zoa-MTN-IHS","","07-02-2025 17:48:50","07-02-2025 17:28:11","07-02-2025 17:=
58:11","Cascaded Incident from TTO4305028","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue site on grid =
with U=3D54v Team I-ENGINEERING /695278990/ working on site ","system","275=
750","07-02-2025 17:48:50","Sagemcom CMR"
"Closed Complete","Site Down","T0051","IHS_YND_297","NOCINC0004279112","Mes=
sassi","IHS_YND_316, IHS_YND_799","07-02-2025 17:47:25","07-02-2025 17:28:1=
1","07-02-2025 17:58:11","No power issue site on grid with U=3D54v Team I-E=
NGINEERING /695278990/ working on site ","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue site on grid with U=3D54v Team I-ENGINEERING /695278990/ working=
 on site ","ervine.mbezele@sagemcom.com","1155","07-02-2025 17:47:25","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004279046","Angongo"=
,"","07-02-2025 17:39:02","07-02-2025 17:19:30","07-02-2025 17:31:48","Casc=
aded Incident from TTO4304884","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because 02/07 rectifiers d=
ysfunctionned// He reset rectifiers,site on Grid","system","269157","07-02-=
2025 17:39:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004279045","Mambine"=
,"","07-02-2025 17:39:02","07-02-2025 17:19:30","07-02-2025 17:31:48","Casc=
aded Incident from TTO4304884","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because 02/07 rectifiers d=
ysfunctionned// He reset rectifiers,site on Grid","system","269157","07-02-=
2025 17:39:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0004279043","Nomayos-=
IHS","","07-02-2025 17:39:01","07-02-2025 17:19:30","07-02-2025 17:31:48","=
Cascaded Incident from TTO4304884","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down because 02/07 rectifie=
rs dysfunctionned// He reset rectifiers,site on Grid","system","269159","07=
-02-2025 17:39:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004279041","Nkenglik=
ok","","07-02-2025 17:39:01","07-02-2025 17:19:30","07-02-2025 17:31:48","C=
ascaded Incident from TTO4304884","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because 02/07 recti=
fiers dysfunctionned// He reset rectifiers,site on Grid","system","269157",=
"07-02-2025 17:39:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004279042","Ebeba","=
","07-02-2025 17:39:01","07-02-2025 17:19:30","07-02-2025 17:31:48","Cascad=
ed Incident from TTO4304884","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because 02/07 rectifiers dys=
functionned// He reset rectifiers,site on Grid","system","269156","07-02-20=
25 17:39:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004279044","OKOA Pea=
ge","","07-02-2025 17:39:01","07-02-2025 17:19:30","07-02-2025 17:31:48","C=
ascaded Incident from TTO4304884","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because 02/07 rectifier=
s dysfunctionned// He reset rectifiers,site on Grid","system","269158","07-=
02-2025 17:39:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004279039","Sous Pre=
fecture","","07-02-2025 17:39:00","07-02-2025 17:19:30","07-02-2025 17:31:4=
8","Cascaded Incident from TTO4304884","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because 02/07 rect=
ifiers dysfunctionned// He reset rectifiers,site on Grid","system","269156"=
,"07-02-2025 17:39:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004279040","Mbankomo=
 IHS","","07-02-2025 17:39:00","07-02-2025 17:19:30","07-02-2025 17:31:48",=
"Cascaded Incident from TTO4304884","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because 02/07 rectifi=
ers dysfunctionned// He reset rectifiers,site on Grid","system","269158","0=
7-02-2025 17:39:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004278986","N=
omayos","IHS_YND_314, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_697, I=
HS_YND_330, IHS_YND_350, IHS_YND_335","07-02-2025 17:30:40","07-02-2025 17:=
19:30","07-02-2025 17:31:48","Site went down because 02/07 rectifiers dysfu=
nctionned// He reset rectifiers,site on Grid","Fanda Brice","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module","Site went down because 02/07 =
rectifiers dysfunctionned// He reset rectifiers,site on Grid","ervine.mbeze=
le@sagemcom.com","1163","07-02-2025 17:30:40","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004278956","Nko=
ulou Carriere carrefourt","","07-02-2025 17:25:59","07-02-2025 17:05:52","0=
7-02-2025 17:45:52","Grid outage,site went down because main gen faulty//Gr=
id return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Generator Faulty","Grid outage,site went down because main gen faulty//G=
rid return","ervine.mbezele@sagemcom.com","1209","07-02-2025 17:25:59","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004278923","B=
arriere","","07-02-2025 17:21:01","07-02-2025 17:14:50","07-02-2025 17:16:5=
0","ACTIVE//No power issue U=3D 53.4V Site on Grid The TX FME Lionnel /6946=
93436 from huawei is informed.Noticed dysjunction at the BTS OCM","Hyemafo =
Gildas","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","ACTIVE//No power issue U=3D 53.4V Site on Grid The TX F=
ME Lionnel /694693436 from huawei is informed.Noticed dysjunction at the BT=
S OCM","ervine.mbezele@sagemcom.com","372","07-02-2025 17:21:01","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004278707","L=
abogenie","","07-02-2025 16:42:10","07-02-2025 16:05:05","07-02-2025 16:23:=
33","Active//No power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (=
693212405 )from Huawei is informed. Repetitive Issue","","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (693212405 )=
from Huawei is informed. Repetitive Issue","ervine.mbezele@sagemcom.com","2=
227","07-02-2025 16:42:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004278636","O=
LAMA","","07-02-2025 16:27:03","07-02-2025 15:58:50","07-02-2025 20:25:50",=
"No power issue site on grid with U=3D54,9v Etienne(651320188)  from Huawei=
 is informed ","Fanda Brice","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54,9v Etienne(651320188)  from Huawei is informed ","ervine.mbezele@sage=
mcom.com","1694","07-02-2025 16:27:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0004278552","N=
gousso OCM","","07-02-2025 16:14:41","07-02-2025 16:07:36","07-02-2025 16:3=
5:36","Grid fluctuation, site went down because Gen failed to start due to =
grid bad voltage no Rcp // He bypass grid and started Gen manually","Siliga=
p Boris","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage no Rcp // He bypass grid and started Gen manually","ervin=
e.mbezele@sagemcom.com","426","07-02-2025 16:14:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_187","NOCINC0004278506","NTEMASSI=
","","07-02-2025 16:06:10","07-02-2025 16:00:22","07-02-2025 18:00:03","Cas=
caded Incident from TTO4304295","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage//grid return","system","2=
73792","07-02-2025 16:06:10","Sagemcom CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0004278503","Ngo=
usso MTN","IHS_YND_187","07-02-2025 16:05:29","07-02-2025 16:00:22","07-02-=
2025 18:00:03","Grid outage//grid return","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid outage//grid return","ervine.mbe=
zele@sagemcom.com","308","07-02-2025 16:05:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004278411","B=
arriere IHS","","07-02-2025 15:47:05","07-02-2025 15:39:55","07-02-2025 15:=
48:55","Grid outage, Site went down because PWC dysfunctionning  // He rese=
t PWC ","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Grid outage, Site went down because PWC dysfunctionni=
ng  // He reset PWC ","ervine.mbezele@sagemcom.com","431","07-02-2025 15:47=
:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004278350","N=
kozoa","","07-02-2025 15:38:42","07-02-2025 15:34:25","07-02-2025 16:53:56"=
,"Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Feli=
x bateu is informed and confirmed// He reduced the load and gen manually st=
arted","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage, site went down due to gen overload (20kva, 340A) SS H=
IS Felix bateu is informed and confirmed// He reduced the load and gen manu=
ally started","ervine.mbezele@sagemcom.com","258","07-02-2025 15:38:42","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0004278342","S=
apeur","","07-02-2025 15:37:20","07-02-2025 15:21:02","07-02-2025 16:37:03"=
,"Site went down due to dysjunction of 2*CB(125 A) in Pwc // He Reamed the =
2*CB(125 A)(Investigation ongoing)","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went do=
wn due to dysjunction of 2*CB(125 A) in Pwc // He Reamed the 2*CB(125 A)(In=
vestigation ongoing)","ervine.mbezele@sagemcom.com","979","07-02-2025 15:37=
:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004277917","Nkongtoc=
k","","07-02-2025 15:09:12","07-02-2025 13:47:46","07-02-2025 13:57:46","Ca=
scaded Incident from TTO4302879","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue site on grid with U=3D4=
7v Notice that site is impacted by Messamendongo who is not our responsabil=
ity","system","274593","07-02-2025 15:09:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004277916","Angongo"=
,"","07-02-2025 15:09:11","07-02-2025 13:47:46","07-02-2025 13:57:46","Casc=
aded Incident from TTO4302879","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on grid with U=3D47v Not=
ice that site is impacted by Messamendongo who is not our responsability","=
system","274595","07-02-2025 15:09:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004277913","Afanoya"=
,"","07-02-2025 15:09:11","07-02-2025 13:47:46","07-02-2025 13:57:46","Casc=
aded Incident from TTO4302879","Hyemafo Gildas","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on grid with U=3D47v =
Notice that site is impacted by Messamendongo who is not our responsability=
","system","274595","07-02-2025 15:09:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004277915","Mambine"=
,"","07-02-2025 15:09:11","07-02-2025 13:47:46","07-02-2025 13:57:46","Casc=
aded Incident from TTO4302879","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on grid with U=3D47v Not=
ice that site is impacted by Messamendongo who is not our responsability","=
system","274593","07-02-2025 15:09:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004277914","Mbankomo=
 IHS","","07-02-2025 15:09:11","07-02-2025 13:47:46","07-02-2025 13:57:46",=
"Cascaded Incident from TTO4302879","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D47=
v Notice that site is impacted by Messamendongo who is not our responsabili=
ty","system","274594","07-02-2025 15:09:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004277912","Sous Pre=
fecture","","07-02-2025 15:09:10","07-02-2025 13:47:46","07-02-2025 13:57:4=
6","Cascaded Incident from TTO4302879","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D47v Notice that site is impacted by Messamendongo who is not our respons=
ability","system","274596","07-02-2025 15:09:10","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004277643","Mel=
en Ba'aba","","07-02-2025 14:41:42","07-02-2025 14:06:26","07-02-2025 17:25=
:26","No ACTIVE // Active// No power issue, site is on GEN with Ubaie=3D54,=
4 V TX FME Julien(693095849) from Huawei is informed. ","Siligap Boris","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No ACTIVE // Active// No power issue, site is on GEN with Ubaie=3D=
54,4 V TX FME Julien(693095849) from Huawei is informed. ","ervine.mbezele@=
sagemcom.com","2117","07-02-2025 14:41:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004277296","OKOA Pea=
ge","","07-02-2025 13:58:01","07-02-2025 13:47:46","07-02-2025 13:57:46","C=
ascaded Incident from TTO4302879","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on grid with U=3D47v =
Notice that site is impacted by Messamendongo who is not our responsability=
","system","274594","07-02-2025 13:58:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004277295","Nkenglik=
ok","","07-02-2025 13:58:00","07-02-2025 13:47:46","07-02-2025 13:57:46","C=
ascaded Incident from TTO4302879","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
47v Notice that site is impacted by Messamendongo who is not our responsabi=
lity","system","274596","07-02-2025 13:58:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004277294","Mandoumb=
a OCM","","07-02-2025 13:58:00","07-02-2025 13:47:46","07-02-2025 13:57:46"=
,"Cascaded Incident from TTO4302879","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D47v Notice that site is impacted by Messamendongo who is not our respons=
ability","system","274593","07-02-2025 13:58:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0004277283","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_313, IHS_YND_695, IHS_YND_348, I=
HS_YND_330, IHS_YND_350, IHS_YND_335, IHS_YND_349","07-02-2025 13:55:54","0=
7-02-2025 13:47:46","07-02-2025 13:57:46","No power issue site on grid with=
 U=3D47v Notice that site is impacted by Messamendongo who is not our respo=
nsability","Fanda Brice","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D4=
7v Notice that site is impacted by Messamendongo who is not our responsabil=
ity","ervine.mbezele@sagemcom.com","489","07-02-2025 13:55:54","Sagemcom CM=
R"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004276857","Nko=
ulou Carriere carrefourt","","07-02-2025 12:50:52","07-02-2025 12:47:40","0=
7-02-2025 14:56:11","Grid outage with main gen faulty//Grid return","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fault=
y","Grid outage with main gen faulty//Grid return","ervine.mbezele@sagemcom=
.com","193","07-02-2025 12:50:52","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004276752","Awa=
e Ewonkan","","07-02-2025 12:39:57","07-02-2025 12:33:37","07-02-2025 13:25=
:46","Grid outage , site went down because insufficient of rectifier SS IHS=
 Alphonse confirmed//Site stabilized","Albran Byorel","Equipment Repair","P=
assive","Rectifier","Rectifier Module","Grid outage , site went down becaus=
e insufficient of rectifier SS IHS Alphonse confirmed//Site stabilized","er=
vine.mbezele@sagemcom.com","506","07-02-2025 12:39:57","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004276604","Fou=
da Quarter","","07-02-2025 12:12:29","07-02-2025 12:04:14","07-02-2025 13:5=
8:31","Site went down due to insuffience of rectifiers (02) on site SS IHS =
Blaise Raoul is on informed// we reduce load on site(delete  one rack of ba=
ttery backup)","Delor Telezing","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to insuffience of rectifiers (02) on s=
ite SS IHS Blaise Raoul is on informed// we reduce load on site(delete  one=
 rack of battery backup)","ervine.mbezele@sagemcom.com","496","07-02-2025 1=
2:12:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004276481","L=
abogenie","","07-02-2025 11:53:03","07-02-2025 10:53:54","07-02-2025 11:10:=
43","Active//No power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (=
693212405 )from Huawei is informed. Repetitive Issue","","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (693212405 )=
from Huawei is informed. Repetitive Issue","ervine.mbezele@sagemcom.com","3=
550","07-02-2025 11:53:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004276024","L=
eboudi","","07-02-2025 10:49:46","07-02-2025 10:07:43","07-02-2025 10:12:12=
","No power issue site and  with Ubaie=3D54.4  V site on Grid The  FME TX M=
ouamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue site and  with Ubaie=3D54.4  V site on Grid The  F=
ME TX Mouamadou/658791013 //From Huawei is informed","wilfried.kameni@sagem=
com.com","2524","07-02-2025 10:49:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004275788","O=
LAMA","","07-02-2025 10:03:50","07-02-2025 09:59:42","07-02-2025 10:05:22",=
"Active//No power issue on site, Site on Grid , UBAIE=3D54V and  Fulbert(65=
4266068)  From huawei is informed","Fanda Brice","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue on site, Site on Grid , UBAIE=3D54V and  Fulbert(654266068)  From =
huawei is informed","ervine.mbezele@sagemcom.com","249","07-02-2025 10:03:5=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004275665","S=
IMBOCK BONAMBAPE","","07-02-2025 09:46:45","07-02-2025 08:48:38","07-02-202=
5 08:55:07","Active//No power issue site on grid with U=3D54,4 V Mbah Osiah=
  from Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue site on grid with U=3D54,4 V Mbah Osiah  from Huawei is informed","ervi=
ne.mbezele@sagemcom.com","3488","07-02-2025 09:46:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004275561","SAA Entr=
ance","","07-02-2025 09:28:40","07-02-2025 08:57:42","07-02-2025 09:10:35",=
"Cascaded Incident from TTO4300780","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went because Gen=
 ran until fuel shortage//Refueling Done","system","270430","07-02-2025 09:=
28:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004275562","Saa","",=
"07-02-2025 09:28:40","07-02-2025 08:57:42","07-02-2025 09:10:35","Cascaded=
 Incident from TTO4300780","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Site went because Gen ran unti=
l fuel shortage//Refueling Done","system","270430","07-02-2025 09:28:40","S=
agemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004275467","SAA=
 2","IHS_YND_542, IHS_YND_405","07-02-2025 09:10:29","07-02-2025 08:57:42",=
"07-02-2025 09:10:35","Grid outage, Site went because Gen ran until fuel sh=
ortage//Refueling Done","Parker Tchoup","Fuel Outage","Passive","Diesel","D=
iesel Outage","Grid outage, Site went because Gen ran until fuel shortage//=
Refueling Done","ervine.mbezele@sagemcom.com","768","07-02-2025 09:10:29","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004275420","O=
dza II","","07-02-2025 09:00:11","07-02-2025 08:58:58","07-02-2025 09:05:18=
","Active// No power Issue Site on Grid and Ubai =3D54.4V The TX FME Mbah H=
osiah (674007438)  from Huawei is informed ","Albran Byorel","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power Issue Site on Grid and Ubai =3D54.4V The TX FME Mbah Hosiah=
 (674007438)  from Huawei is informed ","ervine.mbezele@sagemcom.com","84",=
"07-02-2025 09:00:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004275410","O=
lembe-Terminus","","07-02-2025 08:57:02","07-02-2025 08:51:57","07-02-2025 =
08:56:40","Grid outage, Site went down before gen start due to poor battery=
 backup // Gen start automatically","Fabrice Pouakam","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site we=
nt down before gen start due to poor battery backup // Gen start automatica=
lly","ervine.mbezele@sagemcom.com","307","07-02-2025 08:57:02","Sagemcom CM=
R"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004275308","Nsi=
meyong Terre Rouge","","07-02-2025 08:45:02","07-02-2025 08:39:45","07-02-2=
025 08:53:58","Site went down due to PWC Disfunction, SS IHS Fran=E7ois is =
informed // Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down due to PWC Disfunc=
tion, SS IHS Fran=E7ois is informed // Site stabilized","ervine.mbezele@sag=
emcom.com","318","07-02-2025 08:45:02","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004275143","AWA=
E OCM","","07-02-2025 08:13:00","07-02-2025 08:10:52","07-02-2025 08:12:22"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen started automatically","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen started automatically"=
,"ervine.mbezele@sagemcom.com","129","07-02-2025 08:13:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004275129","L=
abogenie","","07-02-2025 08:08:54","07-02-2025 07:32:04","07-02-2025 08:30:=
22","Grid outage No space to deploy // Grid power return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No space =
to deploy // Grid power return","wilfried.kameni@sagemcom.com","2212","07-0=
2-2025 08:08:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004275107","S=
imbock OCM","","07-02-2025 08:04:20","07-02-2025 07:57:46","07-02-2025 08:0=
5:59","Grid fluctuation site went down because Gen started and stopped due =
to Grid bad voltage and RCP on site// He bypass the Grid and Gen manually s=
tarted","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation site went down because Gen started=
 and stopped due to Grid bad voltage and RCP on site// He bypass the Grid a=
nd Gen manually started","ervine.mbezele@sagemcom.com","395","07-02-2025 08=
:04:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004275045","M=
ontee-Des-Soeurs","","07-02-2025 07:54:41","07-02-2025 07:21:27","07-02-202=
5 07:26:13","No power Issue Site on Grid Ubai =3D54.3 V, The FME The TX FME=
 Mbah Hosiah (674007438) is informed.","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r Issue Site on Grid Ubai =3D54.3 V, The FME The TX FME Mbah Hosiah (674007=
438) is informed.","wilfried.kameni@sagemcom.com","1995","07-02-2025 07:54:=
41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004275021","M=
vog-Manga","","07-02-2025 07:49:50","07-02-2025 07:32:34","07-02-2025 08:07=
:47","Grid fluctuation, site went down before gen start due to poor battery=
 backup // Gen start automatically","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid fluctuation, site=
 went down before gen start due to poor battery backup // Gen start automat=
ically","wilfried.kameni@sagemcom.com","1037","07-02-2025 07:49:50","Sagemc=
om CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004275017","Tou=
ring Club International","","07-02-2025 07:47:41","07-02-2025 07:44:36","07=
-02-2025 08:12:57","Grid Outage  Site went down because Gen stopped with al=
arm under-voltage  //Grid power return","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid Outage  Site went down be=
cause Gen stopped with alarm under-voltage  //Grid power return","ervine.mb=
ezele@sagemcom.com","186","07-02-2025 07:47:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004275011","O=
dza II OCM","","07-02-2025 07:47:01","07-02-2025 07:29:11","07-02-2025 08:2=
1:01","Grid outage,gen failed to start due to card GE faulty//we reset card=
 GE and gen manually started","Albran Byorel","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due to c=
ard GE faulty//we reset card GE and gen manually started","wilfried.kameni@=
sagemcom.com","1072","07-02-2025 07:47:01","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004274901","Nko=
g-Edzen","","07-02-2025 07:19:53","07-02-2025 07:16:41","07-02-2025 07:21:5=
1","No power issue on site, site on Gen The Tx FME Gregoire/654547479/ from=
 huawei is informed. ","Parker Tchoup","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, =
site on Gen The Tx FME Gregoire/654547479/ from huawei is informed. ","ervi=
ne.mbezele@sagemcom.com","193","07-02-2025 07:19:53","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004274322","Nko=
zoa","","07-02-2025 04:28:26","07-02-2025 04:22:07","07-02-2025 05:17:01","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and gen manually star=
ted","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, site went down due to gen overload (20kva, 340A) SS HIS=
 Felix bateu is informed and confirmed// He reduced the load and gen manual=
ly started","wilfried.kameni@sagemcom.com","476","07-02-2025 04:28:26","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004274142","O=
LAMA","","07-02-2025 03:28:42","07-02-2025 03:22:38","07-02-2025 03:25:08",=
"Active//No power issue on site, Site on Grid , UBAIE=3D54V and  Fulbert(65=
4266068)  From huawei is informed","Fanda Brice","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue on site, Site on Grid , UBAIE=3D54V and  Fulbert(654266068)  From =
huawei is informed","wilfried.kameni@sagemcom.com","365","07-02-2025 03:28:=
42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004274117","S=
IMBOCK BONAMBAPE","","07-02-2025 03:23:34","07-02-2025 02:54:28","07-02-202=
5 03:00:28","Active//No power issue site on grid with U=3D54,4 V Mbah Osiah=
  from Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue site on grid with U=3D54,4 V Mbah Osiah  from Huawei is informed","wilf=
ried.kameni@sagemcom.com","1747","07-02-2025 03:23:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004274110","c=
hina embassy yde","","07-02-2025 03:21:15","07-02-2025 02:29:59","07-02-202=
5 02:35:40","Active//No power issue site on grid with U=3D52.4V The Tx FME =
 Eloundou Bertrand from Huawei is informed","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power=
 issue site on grid with U=3D52.4V The Tx FME  Eloundou Bertrand from Huawe=
i is informed","wilfried.kameni@sagemcom.com","3077","07-02-2025 03:21:15",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004274084","N=
kolfon Cimencam","","07-02-2025 03:09:07","07-02-2025 02:51:00","07-02-2025=
 02:55:50","No power issue on site U=3D54,5v site on Gen FME Fulbert (65426=
6068) of huawei is informed. Repetitive issue","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site U=3D54,5v site on Gen FME Fulbert (654266068) of hu=
awei is informed. Repetitive issue","wilfried.kameni@sagemcom.com","1088","=
07-02-2025 03:09:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004273877","O=
lembe-Terminus","","07-02-2025 01:56:14","07-02-2025 01:31:48","07-02-2025 =
03:53:38","Grid outage, site went down because gen failed to start due to c=
ard ge disfunction // He reset of gen card done and gen started manualy","F=
abrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Grid outage, site went down because gen failed to start due to card ge=
 disfunction // He reset of gen card done and gen started manualy","wilfrie=
d.kameni@sagemcom.com","1467","07-02-2025 01:56:14","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004273613","Mes=
sa Carriere","","07-02-2025 00:54:33","06-02-2025 18:50:13","06-02-2025 19:=
00:51","Site went down because 01/03 rectifier faulty SS IHS Fran=E7ois is =
informed and confirmed // Site stabilized","Mboua Thierry","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Site went down because 01/03 r=
ectifier faulty SS IHS Fran=E7ois is informed and confirmed // Site stabili=
zed","ervine.mbezele@sagemcom.com","21860","07-02-2025 00:54:33","Sagemcom =
CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004273475","Aka=
k-Nkozoa-MTN-IHS","","07-02-2025 00:20:54","07-02-2025 00:03:24","07-02-202=
5 02:59:01","Grid fluctuation, site went down because gen started and stopp=
ed due to grid bad voltage // He bypassed Grid and started Gen manualy","Fa=
brice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, site went down because gen started and stop=
ped due to grid bad voltage // He bypassed Grid and started Gen manualy","w=
ilfried.kameni@sagemcom.com","1051","07-02-2025 00:20:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004273391","L=
abogenie","","06-02-2025 23:58:51","06-02-2025 23:37:29","06-02-2025 23:50:=
01","Active//No power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (=
693212405 )from Huawei is informed. Repetitive Issue","","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (693212405 )=
from Huawei is informed. Repetitive Issue","wilfried.kameni@sagemcom.com","=
1284","06-02-2025 23:58:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0004273146","C-Suprem=
e","","06-02-2025 23:04:56","06-02-2025 22:27:24","06-02-2025 22:30:22","Ca=
scaded Incident from TTO4298006","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","Active// No power issue, site is on grid with Ubaie=
=3D53,5V, Lionel Adjep(655184876) from Huawei is informed","system","265015=
","06-02-2025 23:04:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_042","NOCINC0004273142","Mvog-Ada=
_OCM","","06-02-2025 23:04:55","06-02-2025 22:27:24","06-02-2025 22:30:22",=
"Cascaded Incident from TTO4298006","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","Active// No power issue, site is on grid with Ubai=
e=3D53,5V, Lionel Adjep(655184876) from Huawei is informed","system","26501=
5","06-02-2025 23:04:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_037","NOCINC0004273143","Nkolndon=
go","","06-02-2025 23:04:55","06-02-2025 22:27:24","06-02-2025 22:30:22","C=
ascaded Incident from TTO4298006","MINKA NICOLAS","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active// No power issue, site is on gri=
d with Ubaie=3D53,5V, Lionel Adjep(655184876) from Huawei is informed","sys=
tem","265014","06-02-2025 23:04:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_023","NOCINC0004273145","Montesqu=
ieux","","06-02-2025 23:04:55","06-02-2025 22:27:24","06-02-2025 22:30:22",=
"Cascaded Incident from TTO4298006","Paul BIBOUM","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active// No power issue, site is on gri=
d with Ubaie=3D53,5V, Lionel Adjep(655184876) from Huawei is informed","sys=
tem","265014","06-02-2025 23:04:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0004273144","Acropole=
","","06-02-2025 23:04:55","06-02-2025 22:27:24","06-02-2025 22:30:22","Cas=
caded Incident from TTO4298006","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// No power issue, site is on grid =
with Ubaie=3D53,5V, Lionel Adjep(655184876) from Huawei is informed","syste=
m","265014","06-02-2025 23:04:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0004273123","M=
vog Mbi New","IHS_YND_042, IHS_YND_037, IHS_YND_036, IHS_YND_023, IHS_YND_0=
21","06-02-2025 23:03:03","06-02-2025 22:27:24","06-02-2025 22:30:22","Acti=
ve// No power issue, site is on grid with Ubaie=3D53,5V, Lionel Adjep(65518=
4876) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No powe=
r issue, site is on grid with Ubaie=3D53,5V, Lionel Adjep(655184876) from H=
uawei is informed","wilfried.kameni@sagemcom.com","2140","06-02-2025 23:03:=
03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004273005","B=
iteng-Maetur","","06-02-2025 22:34:27","06-02-2025 22:05:06","07-02-2025 00=
:56:34","Site went down due to insufficiency of rectifiers (06) due to load=
 increase and causing disjunction at BTS OCM SS IHS Alphonse confirmed// Si=
te stabilized and CB OCM put back on","Mba Lazare Herve","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down due to insufficie=
ncy of rectifiers (06) due to load increase and causing disjunction at BTS =
OCM SS IHS Alphonse confirmed// Site stabilized and CB OCM put back on","wi=
lfried.kameni@sagemcom.com","1763","06-02-2025 22:34:27","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004272802","MEF=
OU ASSI","","06-02-2025 22:02:22","06-02-2025 21:34:10","06-02-2025 21:38:1=
0","Site went down du to insufficiency of rectifier, IHS SS FELIX ZAMBE is =
informed // site stabilized","Fanda Brice","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down du to insufficiency of rectifie=
r, IHS SS FELIX ZAMBE is informed // site stabilized","ervine.mbezele@sagem=
com.com","1693","06-02-2025 22:02:22","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004272697","Nko=
lbisson usines des eaux 2","","06-02-2025 22:00:49","06-02-2025 21:52:38","=
06-02-2025 21:59:11","Site went down because disjunction Cb(125A) in DC BOX=
 due to load // He reamed Cb(125A), site on grid","TIENTCHEU NZETCHIEU GAEL=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Bre=
aker Issue","Site went down because disjunction Cb(125A) in DC BOX due to l=
oad // He reamed Cb(125A), site on grid","ervine.mbezele@sagemcom.com","493=
","06-02-2025 22:00:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004272325","ELOUMDEM=
 CARRIERE 2","","06-02-2025 21:39:20","06-02-2025 21:34:13","06-02-2025 21:=
46:09","Cascaded Incident from TTO4297095","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","wronglit tikect","system","26=
0989","06-02-2025 21:39:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004272324","Eto koss=
 Yde","","06-02-2025 21:39:20","06-02-2025 21:34:13","06-02-2025 21:46:09",=
"Cascaded Incident from TTO4297095","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","wronglit tikect","system","260989","=
06-02-2025 21:39:20","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004272321","Ona=
ngondi (melen bikop)","IHS_YND_737, IHS_YND_768","06-02-2025 21:38:25","06-=
02-2025 21:34:13","06-02-2025 21:46:09","wronglit tikect","Fanda Brice","In=
correctly Logged Tickets","Error","Error","Error","wronglit tikect","ervine=
.mbezele@sagemcom.com","253","06-02-2025 21:38:25","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004272002","Aha=
la Echangeur","","06-02-2025 21:11:20","06-02-2025 19:46:07","06-02-2025 21=
:44:54","Site went down due to insufficiency of rectifiers // Site stabiliz=
ed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficiency of rectifiers // Site stabilized"=
,"stephane.nkamwa@ihstowers.com","5114","06-02-2025 21:11:20","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0004271843","S=
imbock OCM","","06-02-2025 20:51:54","06-02-2025 20:21:13","06-02-2025 20:2=
5:44","No power issue on site. Site on Grid with Ubaie=3D54.9V The tx Fme H=
osiah (6 74 00 74 38) from Huawei is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site. Site on Grid with Ubaie=3D54.9V The tx Fme Hosiah =
(6 74 00 74 38) from Huawei is informed","ervine.mbezele@sagemcom.com","184=
2","06-02-2025 20:51:54","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004271277","Crf=
-Mbankolo-IHS","","06-02-2025 19:37:35","06-02-2025 19:32:27","06-02-2025 1=
9:39:27","Site went down due to MPR disfunction // Site stabilized","Mboua =
Thierry","Equipment Repair","Passive","Rectifier","Rectifier Cabinet","Site=
 went down due to MPR disfunction / Site stabilized","ervine.mbezele@sagemc=
om.com","309","06-02-2025 19:37:35","Sagemcom CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0004271159","Men=
dong Plateau","","06-02-2025 19:30:36","06-02-2025 19:16:30","06-02-2025 20=
:37:49","Site went down because CB 80A disjuncted in Pwc due to load increa=
se//he did a bridge with another CB 80A","Hyemafo Gildas","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site w=
ent down because CB 80A disjuncted in Pwc due to load increase//he did a br=
idge with another CB 80A","ervine.mbezele@sagemcom.com","847","06-02-2025 1=
9:30:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004270802","B=
riqueterie","","06-02-2025 18:52:26","06-02-2025 18:50:20","09-02-2025 07:2=
0:53","Grid outage, No space to deploy MDG // grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spac=
e to deploy MDG // grid return","ervine.mbezele@sagemcom.com","128","06-02-=
2025 18:52:26","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004270656","Bri=
quetterie","","06-02-2025 18:34:54","06-02-2025 18:17:46","09-02-2025 07:23=
:44","Grid outage, No space to deploy MDG // grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space=
 to deploy MDG // grid return","ervine.mbezele@sagemcom.com","1029","06-02-=
2025 18:34:54","Sagemcom CMR"
"Closed Complete","Site Down","T0498","IHS_YND_049","NOCINC0004270490","Eto=
a-Meki","","06-02-2025 18:09:12","06-02-2025 18:01:04","06-02-2025 20:45:24=
","No power issue on site U=3D54v site on grid Tx fme Lionel steeve of huaw=
ei is informed","Delor Telezing","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v=
 site on grid Tx fme Lionel steeve of huawei is informed","ervine.mbezele@s=
agemcom.com","488","06-02-2025 18:09:12","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004270433","Mel=
en Ba'aba","","06-02-2025 17:59:56","06-02-2025 17:42:48","06-02-2025 17:56=
:53","No power issue on site U=3D53,2v site on gen Tx fme Synphorien of hua=
wei is informed","Siligap Boris","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53,=
2v site on gen Tx fme Synphorien of huawei is informed","ervine.mbezele@sag=
emcom.com","1029","06-02-2025 17:59:56","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004270351","BAT=
A Mokolo OCM","","06-02-2025 17:43:03","06-02-2025 17:37:53","07-02-2025 09=
:06:34","Grid outage, No space to deploy MDG // grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No sp=
ace to deploy MDG // grid return","ervine.mbezele@sagemcom.com","311","06-0=
2-2025 17:43:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0004269929","V=
allee-Bastos OCM","","06-02-2025 17:03:25","06-02-2025 16:54:05","06-02-202=
5 18:36:04","Grid outage//MDG 20kva deployed","","Grid Supply","Passive","G=
rid","National Grid - Grid Outage Issue","Grid outage//MDG 20kva deployed",=
"ervine.mbezele@sagemcom.com","561","06-02-2025 17:03:25","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004269884","Mes=
sa Carriere","","06-02-2025 16:56:15","06-02-2025 16:23:00","06-02-2025 16:=
41:38","Grid outage, Site went down because Gen failed to start due to Gen =
card faulty//grid return","Mboua Thierry","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage, Site went down because Gen fail=
ed to start due to Gen card faulty//grid return","ervine.mbezele@sagemcom.c=
om","1996","06-02-2025 16:56:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0004269519","Nkolo II=
 New","","06-02-2025 16:33:21","06-02-2025 16:19:11","06-02-2025 17:38:47",=
"Cascaded Incident from TTO4293848","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to work Team=
 Checolday/GIAO/680881772 working on site(Telemetry) //End of work","system=
","272733","06-02-2025 16:33:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004269515","M=
imboman-Village","IHS_YND_709","06-02-2025 16:32:32","06-02-2025 16:19:11",=
"06-02-2025 17:38:47","Site went down due to work Team Checolday/GIAO/68088=
1772 working on site(Telemetry) //End of work","Mba Lazare Herve","Installa=
tion Activity","Passive","Planned Activity","Installation Activity","Site w=
ent down due to work Team Checolday/GIAO/680881772 working on site(Telemetr=
y) //End of work","ervine.mbezele@sagemcom.com","802","06-02-2025 16:32:32"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004269144","E=
kombitie","","06-02-2025 15:49:27","06-02-2025 15:19:21","06-02-2025 15:29:=
21","No power issue on site U=3D54,6v site on grid Tx fme Synphorien 650257=
151 of Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site U=3D54,6v site on grid Tx fme Synphorien 650257151 of Huawei is inform=
ed","ervine.mbezele@sagemcom.com","1807","06-02-2025 15:49:27","Sagemcom CM=
R"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004269101","Elo=
umdem stade","","06-02-2025 15:43:42","06-02-2025 15:35:22","06-02-2025 15:=
53:19","Grid bad voltage,and gen failed to start,no rcp//bypassed grid star=
ted the gen","Fanda Brice","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","Grid bad voltage,and gen failed to start,no rcp//=
bypassed grid started the gen","ervine.mbezele@sagemcom.com","501","06-02-2=
025 15:43:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0004268920","Afanoya"=
,"","06-02-2025 15:22:51","06-02-2025 15:11:42","06-02-2025 16:22:56","Casc=
aded Incident from TTO4293150","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because 3/8 rectifiers =
disfunctionning//he reset the rectifiers:site on grid","system","276956","0=
6-02-2025 15:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0004268919","MBALNGON=
G LYCEE","","06-02-2025 15:22:51","06-02-2025 15:11:42","06-02-2025 16:22:5=
6","Cascaded Incident from TTO4293150","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because 3/8 rectif=
iers disfunctionning//he reset the rectifiers:site on grid","system","27695=
6","06-02-2025 15:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0004268918","ELOUMDEM=
 CARRIERE","","06-02-2025 15:22:50","06-02-2025 15:11:42","06-02-2025 16:22=
:56","Cascaded Incident from TTO4293150","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because 3/8 rect=
ifiers disfunctionning//he reset the rectifiers:site on grid","system","276=
956","06-02-2025 15:22:50","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0004268907","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","06-02-2025 15:20:55","06-02-20=
25 15:11:42","06-02-2025 16:22:56","Site went down because 3/8 rectifiers d=
isfunctionning//he reset the rectifiers:site on grid","Hyemafo Gildas","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module","Site went down bec=
ause 3/8 rectifiers disfunctionning//he reset the rectifiers:site on grid",=
"ervine.mbezele@sagemcom.com","554","06-02-2025 15:20:55","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004268603","BAT=
A Mokolo OCM","","06-02-2025 14:48:26","06-02-2025 14:39:13","06-02-2025 14=
:50:13","Grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,n=
o space to deploy a mobil gen//grid return","ervine.mbezele@sagemcom.com","=
554","06-02-2025 14:48:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004268491","O=
LAMA","","06-02-2025 14:39:41","06-02-2025 14:19:28","06-02-2025 14:24:10",=
"Active//No power issue on site, Site on Gen , UBAIE=3D54V and  Fulbert(654=
266068)  From huawei is informed","Fanda Brice","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue on site, Site on Gen , UBAIE=3D54V and  Fulbert(654266068)  From hu=
awei is informed","ervine.mbezele@sagemcom.com","1213","06-02-2025 14:39:41=
","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004268486","MAN=
GUIERS CHAPELLE","","06-02-2025 14:38:08","06-02-2025 14:25:54","06-02-2025=
 15:15:29","Grid outage,gen stopped with alarm high temp//he added water in=
 radiator","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG =
- High Engine Temp - Coolant Level Issue","Grid outage,gen stopped with ala=
rm high temp//he added water in radiator","ervine.mbezele@sagemcom.com","76=
7","06-02-2025 14:38:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004268465","O=
mnisport-Rail","","06-02-2025 14:37:18","06-02-2025 14:21:08","06-02-2025 1=
4:21:09","Active // No power issue site on grid with U=3D56,3 V Tx Fme Arma=
nd Ngestsa (691144412) of huawei is informed","Delor Telezing","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue site on grid with U=3D56,3 V Tx Fme Armand Ngestsa=
 (691144412) of huawei is informed","ervine.mbezele@sagemcom.com","971","06=
-02-2025 14:37:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0004268277","C=
arrefourt Nkomo","","06-02-2025 14:10:16","06-02-2025 13:57:45","06-02-2025=
 14:56:45","Grid outage,site went down because gen failed to start due to G=
rid contactor dysfunctionning //he excited the grid contactor siteon Grid "=
,"Mba Lazare Herve","Equipment Repair","Passive","Control Panel","ATS-AMF I=
ssue","Grid outage,site went down because gen failed to start due to Grid c=
ontactor dysfunctionning //he excited the grid contactor siteon Grid ","dan=
ick.tchakouani@sagemcom.com","752","06-02-2025 14:10:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004268170","O=
lembe-Terminus","","06-02-2025 13:54:12","06-02-2025 13:39:42","06-02-2025 =
13:47:59","Grid outage, site went down before gen start due to poor battery=
 backup // grid return","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // grid return","danick.tchakouani@=
sagemcom.com","872","06-02-2025 13:54:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004268121","A=
kak-Nkozoa-MTN-IHS","","06-02-2025 13:48:39","06-02-2025 13:40:00","06-02-2=
025 13:42:32","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage // Grid stabilized","Fabrice Pouakam","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctu=
ation, site went down because gen start and stopped due to grid bad voltage=
 // Grid stabilized","danick.tchakouani@sagemcom.com","632","06-02-2025 13:=
48:39","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004267688","Bas=
tos Amb Coree","","06-02-2025 13:08:17","06-02-2025 13:03:03","06-02-2025 1=
3:17:49","Grid outage .no space to deploy a  mobile Gen//Grid power Restore=
d","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid outage .no space to deploy a  mobile Gen//Grid power Restored","danick.=
tchakouani@sagemcom.com","315","06-02-2025 13:08:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004267619","C=
omplexe-BEAC","","06-02-2025 12:56:39","06-02-2025 10:59:45","06-02-2025 11=
:02:31","Grid outage , Site went down before Gen start due to poor backup//=
 Grid return","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage , Site went down before Gen star=
t due to poor backup// Grid return","danick.tchakouani@sagemcom.com","7015"=
,"06-02-2025 12:56:39","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004267502","BAT=
A Mokolo OCM","","06-02-2025 12:38:24","06-02-2025 10:29:24","06-02-2025 14=
:19:47","Grid outage.no space to deploy mobile gen//.grid power return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage.no space to deploy mobile gen//.grid power return","danick.tchakouani@=
sagemcom.com","7741","06-02-2025 12:38:24","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004267124","Com=
plex Beac II","","06-02-2025 11:48:14","06-02-2025 11:35:38","06-02-2025 13=
:01:00","Site went down due to work: Our Technician Albran/657108542/SAGEMC=
OM working on site (He replaced the Grid Contactor)//end off Work","Albran =
Byorel","Installation Activity","Passive","Planned Activity","Installation =
Activity","Site went down due to work: Our Technician Albran/657108542/SAGE=
MCOM working on site (He replaced the Grid Contactor)//end off Work","danic=
k.tchakouani@sagemcom.com","757","06-02-2025 11:48:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0004266990","O=
mnisport-Rail","","06-02-2025 11:29:19","06-02-2025 11:20:50","06-02-2025 1=
1:23:25","No power issue site on grid with U=3D56.3v Aramand Nguetsa(691144=
412) from Huawei is confirmed","Delor Telezing","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
site on grid with U=3D56.3v Aramand Nguetsa(691144412) from Huawei is confi=
rmed","danick.tchakouani@sagemcom.com","510","06-02-2025 11:29:19","Sagemco=
m CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0004266967","MAN=
GUIERS CHAPELLE","","06-02-2025 11:25:16","06-02-2025 11:21:53","06-02-2025=
 13:27:12","Grid outage site went down because Gen stopped with alarm high =
temp //He added water and Gen manually started","Fabrice Pouakam","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid outage site went down because Gen stopped with alarm high temp //=
He added water and Gen manually started","danick.tchakouani@sagemcom.com","=
356","06-02-2025 11:25:16","Sagemcom CMR"
"Closed Complete","Warning","T0288","IHS_YND_001","NOCINC0004266901","Royal=
 Hotel Yde","","06-02-2025 11:16:18","","","Site went on battery due to lac=
k of 2 phases // He bypassed Grid and manually started the Gen","Paul BIBOU=
M","Warning","Warning","POWER","Warning - Site on Battery","Site went on ba=
ttery due to lack of 2 phases // He bypassed Grid and manually started the =
Gen","wilfried.kameni@sagemcom.com","2002","06-02-2025 11:16:18","Sagemcom =
CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004266828","Com=
plex Beac II","","06-02-2025 11:03:38","06-02-2025 10:56:15","06-02-2025 11=
:10:03","Grid outage, site went down because Gen failed to start due to Gri=
d contactor Faulty // Grid Restored","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","Grid outage, site went down because=
 Gen failed to start due to Grid contactor Faulty // Grid Restored","danick=
.tchakouani@sagemcom.com","444","06-02-2025 11:03:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004266801","O=
dza II","","06-02-2025 10:57:20","06-02-2025 10:43:04","06-02-2025 10:51:47=
","Site went down due to work: Our Technician Albra /657108542/SAGEMCOM wor=
king on site (he connect the Second Generator on Site )// End of work ","Al=
bran Byorel","Installation Activity","Passive","Planned Activity","Installa=
tion Activity","Site went down due to work: Our Technician Albra /657108542=
/SAGEMCOM working on site (he connect the Second Generator on Site )// End =
of work ","danick.tchakouani@sagemcom.com","858","06-02-2025 10:57:20","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004266794","MEHANDAN=
","","06-02-2025 10:56:10","06-02-2025 10:46:35","06-02-2025 11:17:53","Cas=
caded Incident from TTO4290630","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to gen card faulty //Grid return","system","263866","=
06-02-2025 10:56:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004266748","O=
dza II OCM","IHS_YND_528","06-02-2025 10:54:45","06-02-2025 10:46:35","06-0=
2-2025 11:17:53","Grid outage, site went down because gen failed to start d=
ue to gen card faulty //Grid return","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down becau=
se gen failed to start due to gen card faulty //Grid return","danick.tchako=
uani@sagemcom.com","491","06-02-2025 10:54:45","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004266709","Nsi=
meyong Terre Rouge","","06-02-2025 10:49:57","06-02-2025 10:43:32","06-02-2=
025 11:11:07","Site went down due to PWC Disfunction, SS IHS Fran=E7ois is =
informed // Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down due to PWC Disfunc=
tion, SS IHS Fran=E7ois is informed // Site stabilized","danick.tchakouani@=
sagemcom.com","386","06-02-2025 10:49:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004266071","O=
dza II","","06-02-2025 09:43:58","06-02-2025 09:36:36","06-02-2025 09:41:17=
","active// No power issue site on grid with U=3D52v Lionnel Steeve from Hu=
awei is informed","Albran Byorel","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","active// No power issue site =
on grid with U=3D52v Lionnel Steeve from Huawei is informed","danick.tchako=
uani@sagemcom.com","446","06-02-2025 09:43:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004265998","N=
YOM 2 IHS","","06-02-2025 09:34:10","06-02-2025 09:14:37","06-02-2025 10:24=
:01","Grid Outage, site went because Gen stoppen with alarm ""high Temp"" d=
ue to radiator pierced/Grid return","Fabrice Pouakam","Equipment Repair","P=
assive","ACDG Gen","ACDG - Radiator","Grid Outage, site went because Gen st=
oppen with alarm ""high Temp"" due to radiator pierced/Grid return","danick=
.tchakouani@sagemcom.com","1174","06-02-2025 09:34:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004265956","B=
astos Bir","","06-02-2025 09:28:54","06-02-2025 09:11:34","06-02-2025 09:16=
:11","Active//No power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed","Mboua Thierry","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (693212405 )from=
 Huawei is informed","danick.tchakouani@sagemcom.com","1041","06-02-2025 09=
:28:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0004265712","O=
lezoa OCM","","06-02-2025 08:48:56","06-02-2025 08:29:52","06-02-2025 08:30=
:31","Active//No power issue site on Grid wih U=3D52.5V and The FME TX Bric=
e Tsague (690286359) from Huawei is informed","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue site on Grid wih U=3D52.5V and The FME TX Brice Tsague (690286359)=
 from Huawei is informed","danick.tchakouani@sagemcom.com","1145","06-02-20=
25 08:48:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004264978","S=
IMBOCK BONAMBAPE","","06-02-2025 06:45:25","06-02-2025 06:39:00","06-02-202=
5 06:40:00","Active//No power issue site on grid with U=3D52,6 V Mbah Osiah=
  from Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue site on grid with U=3D52,6 V Mbah Osiah  from Huawei is informed","dani=
ck.tchakouani@sagemcom.com","386","06-02-2025 06:45:25","Sagemcom CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0004264621","Ngo=
uetou","","06-02-2025 04:53:00","06-02-2025 04:43:54","06-02-2025 07:50:38"=
,"Hybrid Gen Site: site went down because Gen failed to start due to pellet=
 radiator pierced// he  glued the Pellet and Manually Started The Gen  ","P=
arker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","Hy=
brid Gen Site: site went down because Gen failed to start due to pellet rad=
iator pierced// he  glued the Pellet and Manually Started The Gen  ","wilfr=
ied.kameni@sagemcom.com","574","06-02-2025 04:53:00","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004264586","Nsi=
meyong Terre Rouge","","06-02-2025 04:41:18","06-02-2025 04:31:03","06-02-2=
025 04:45:48","Site went down due to pwc Disfunction, SS IHS Fran=E7ois is =
informed // Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down due to pwc Disfunc=
tion, SS IHS Fran=E7ois is informed // Site stabilized","wilfried.kameni@sa=
gemcom.com","616","06-02-2025 04:41:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004264218","N=
kolondom","","06-02-2025 02:18:19","06-02-2025 02:11:51","06-02-2025 04:05:=
17","Grid fluctuation, site went down because Gen failed to start due to gr=
id bad voltage no Rcp // He bypass grid and started Gen manually","Fabrice =
Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage no Rcp // He bypass grid and started Gen manually","wilfr=
ied.kameni@sagemcom.com","389","06-02-2025 02:18:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004264162","N=
kolfon Cimencam","","06-02-2025 02:03:31","06-02-2025 01:57:25","06-02-2025=
 03:15:26","No power issue on site U=3D54,5v site on Gen FME Fulbert (65426=
6068) of huawei is informed","Hyemafo Gildas","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site U=3D54,5v site on Gen FME Fulbert (654266068) of huawei is informed",=
"wilfried.kameni@sagemcom.com","367","06-02-2025 02:03:31","Sagemcom CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0004263950","Mim=
boman","","06-02-2025 01:19:37","06-02-2025 01:12:23","06-02-2025 01:35:08"=
,"CB Eneo Meter down, Site went down because CB Gen (23A) tripped// He rear=
med CB, Site on Grid (investigation ongoing)","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Load Breaker","CB Eneo Meter down, Si=
te went down because CB Gen (23A) tripped// He rearmed CB, Site on Grid (in=
vestigation ongoing)","danick.tchakouani@sagemcom.com","435","06-02-2025 01=
:19:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0004263906","E=
lig-Edzoa","","06-02-2025 01:06:31","06-02-2025 00:36:15","06-02-2025 03:15=
:43","Site went down because CB (40A) tripped in DC BOX due to Grid bad vol=
tage// CB put back on and Grid stabilized ","","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down be=
cause CB (40A) tripped in DC BOX due to Grid bad voltage// CB put back on a=
nd Grid stabilized ","wilfried.kameni@sagemcom.com","1818","06-02-2025 01:0=
6:31","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0004263905","Jea=
n Vespa","","06-02-2025 01:05:01","05-02-2025 23:10:13","06-02-2025 00:31:2=
4","Site went down because gen start and stopped due to grid bad voltage, n=
o RCP on site // He bypass grid and manualy start the gen","Mboua Thierry",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","S=
ite went down because gen start and stopped due to grid bad voltage, no RCP=
 on site // He bypass grid and manualy start the gen","danick.tchakouani@sa=
gemcom.com","6889","06-02-2025 01:05:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004263700","O=
LAMA","","06-02-2025 00:07:03","05-02-2025 23:27:47","06-02-2025 00:55:09",=
"Active//No power issue on site, Site on Gen , UBAIE=3D54V and  Fulbert(654=
266068)  From huawei is informed","Fanda Brice","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue on site, Site on Gen , UBAIE=3D54V and  Fulbert(654266068)  From hu=
awei is informed","wilfried.kameni@sagemcom.com","2357","06-02-2025 00:07:0=
3","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004263624","E=
vodoula OCM","","05-02-2025 23:37:02","05-02-2025 20:23:28","06-02-2025 06:=
25:48","Site went down because 02/03 rectifiers faulty SS IHS Pascaline is =
informed and confirmed// He added 01 rectifier (Site on 02 rectifier)","TIE=
NTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down because 02/03 rectifiers faulty SS IHS Pascaline is=
 informed and confirmed// He added 01 rectifier (Site on 02 rectifier)","wi=
lfried.kameni@sagemcom.com","11615","05-02-2025 23:37:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0004263497","Jean Ves=
pa 2","","05-02-2025 23:02:00","05-02-2025 22:49:16","06-02-2025 00:31:58",=
"Cascaded Incident from TTO4286938","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because gen start a=
nd stopped due to grid bad voltage // He bypass grid and manualy start the =
gen","system","270695","05-02-2025 23:02:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0004263496","J=
-Vespa","IHS_YND_544","05-02-2025 23:01:24","05-02-2025 22:49:16","06-02-20=
25 00:31:58","Site went down because gen start and stopped due to grid bad =
voltage, no RCP on site // He bypass grid and manualy start the gen","Mboua=
 Thierry","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Site went down because gen start and stopped due to grid bad volta=
ge, no RCP on site // He bypass grid and manualy start the gen","wilfried.k=
ameni@sagemcom.com","729","05-02-2025 23:01:24","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0004263437","Eli=
g Edzoa","","05-02-2025 22:42:41","05-02-2025 22:28:37","06-02-2025 00:16:3=
2","Grid outage, Site went down due to pwc ZTE dysfunction// He bypassed it=
 and started Gen manualy","Delor Telezing","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Grid outage, Site went down due to =
pwc ZTE dysfunction// He bypassed it and started Gen manualy","wilfried.kam=
eni@sagemcom.com","867","05-02-2025 22:42:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0004263319","Acropole=
","","05-02-2025 22:19:51","05-02-2025 21:46:32","05-02-2025 21:50:51","Cas=
caded Incident from TTO4286680","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active // No power issue site on grid wit=
h U=3D54,3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed and up=
 at 10:10 PM","system","1231226","05-02-2025 22:19:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_055","NOCINC0004263318","Olezoa O=
CM","","05-02-2025 22:19:51","05-02-2025 21:46:32","05-02-2025 21:50:51","C=
ascaded Incident from TTO4286680","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Active // No power issue site on grid with U=3D54,3 =
V Tx Fme Armand Ngestsa (691144412) of huawei is informed and up at 10:10 P=
M","system","1231225","05-02-2025 22:19:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0004263320","C-Suprem=
e","","05-02-2025 22:19:51","05-02-2025 21:46:32","05-02-2025 21:50:51","Ca=
scaded Incident from TTO4286680","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","Active // No power issue site on grid with U=3D54,3 V=
 Tx Fme Armand Ngestsa (691144412) of huawei is informed and up at 10:10 PM=
","system","1231226","05-02-2025 22:19:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_564","NOCINC0004263317","Mvog Mbi=
 New","","05-02-2025 22:19:51","05-02-2025 21:46:32","05-02-2025 21:50:51",=
"Cascaded Incident from TTO4286680","MINKA NICOLAS","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active // No power issue site on grid=
 with U=3D54,3 V Tx Fme Armand Ngestsa (691144412) of huawei is informed an=
d up at 10:10 PM","system","1231225","05-02-2025 22:19:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0004263279","N=
kolndongo","IHS_YND_564, IHS_YND_055, IHS_YND_036, IHS_YND_021","05-02-2025=
 22:13:49","05-02-2025 21:46:32","05-02-2025 21:50:51","Active // No power =
issue site on grid with U=3D54,3 V Tx Fme Armand Ngestsa (691144412) of hua=
wei is informed and up at 10:10 PM","MINKA NICOLAS","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // N=
o power issue site on grid with U=3D54,3 V Tx Fme Armand Ngestsa (691144412=
) of huawei is informed and up at 10:10 PM","wilfried.kameni@sagemcom.com",=
"1638","05-02-2025 22:13:49","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004263137","Nko=
ulou Carriere carrefourt","","05-02-2025 21:48:25","05-02-2025 21:07:02","0=
5-02-2025 21:49:06","Grid outage, Site went down Gen failed to start due to=
 no Gen battery // Grid return","Mba Lazare Herve","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Generator Battery","Grid outage, Site went down Gen=
 failed to start due to no Gen battery // Grid return","ervine.mbezele@sage=
mcom.com","2484","05-02-2025 21:48:25","Sagemcom CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0004263111","Omn=
isport-Rail","","05-02-2025 21:43:38","05-02-2025 20:44:24","05-02-2025 21:=
57:12","Grid outage, site went down because gen failed to start due to RCP =
faulty // Gen manually started","Delor Telezing","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Grid outage, site went down=
 because gen failed to start due to RCP faulty // Gen manually started","er=
vine.mbezele@sagemcom.com","3652","05-02-2025 21:43:38","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004263077","Nko=
lbisson usines des eaux 2","","05-02-2025 21:37:26","05-02-2025 20:47:58","=
06-02-2025 07:56:33","ACCESS ISSUE DURING THE NIGHT DUE TO LANDLORD (Site w=
ent down due to CB 125(A) tripped  in the PWC//He reamed and Site is on Gri=
d)","TIENTCHEU NZETCHIEU GAEL","Access Denial","Lease Or Legal","Landlord R=
elated Issues","Access Issue - Land Lord","ACCESS ISSUE DURING THE NIGHT DU=
E TO LANDLORD (Site went down due to CB 125(A) tripped in the PWC//He reame=
d and Site is on Grid)","ervine.mbezele@sagemcom.com","2969","05-02-2025 21=
:37:26","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0004262986","Bas=
tos Amb Coree","","05-02-2025 21:26:16","05-02-2025 20:43:48","05-02-2025 2=
1:43:48","Grid outage, No space to deploy a MDG // grid power return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, No space to deploy a MDG // grid power return","ervine.mbezele@sagemcom=
.com","2550","05-02-2025 21:26:16","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004262820","NKO=
MEKUI OCM","","05-02-2025 21:08:36","05-02-2025 20:10:18","05-02-2025 20:18=
:04","No power issue on site U=3D54.5  V site on Gen. Site impacted by Mban=
kolo Camtel and not managed by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site U=3D54.5  V site on Gen. Site impacted by Mbankolo C=
amtel and not managed by IHS","ervine.mbezele@sagemcom.com","3499","05-02-2=
025 21:08:36","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004262723","Aha=
la Echangeur","","05-02-2025 20:54:15","05-02-2025 19:38:59","05-02-2025 20=
:36:49","Site went down due to insufficiency of rectifier // site stabilize=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site went down due to insufficiency of rectifier // site stabilized","=
ervine.mbezele@sagemcom.com","4517","05-02-2025 20:54:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_217","NOCINC0004262658","Abom",""=
,"05-02-2025 20:43:51","05-02-2025 20:15:06","05-02-2025 20:49:25","Cascade=
d Incident from TTO4285926","Siligap Boris","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Site went down due to PWC overload(12K, 23=
0A) SS Judicael confirmed // Site stabilized ","system","301732","05-02-202=
5 20:43:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_215","NOCINC0004262655","Eleveurs=
","","05-02-2025 20:43:50","05-02-2025 20:15:06","05-02-2025 20:49:25","Cas=
caded Incident from TTO4285926","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to PWC overload(12K=
, 230A) SS Judicael confirmed // Site stabilized ","system","301733","05-02=
-2025 20:43:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_214","NOCINC0004262657","Nkolmess=
eng-II","","05-02-2025 20:43:50","05-02-2025 20:15:06","05-02-2025 20:49:25=
","Cascaded Incident from TTO4285926","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site went down due to PWC overlo=
ad(12K, 230A) SS Judicael confirmed // Site stabilized ","system","301732",=
"05-02-2025 20:43:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_739","NOCINC0004262656","NKOLMESS=
ING rue Manguier","","05-02-2025 20:43:50","05-02-2025 20:15:06","05-02-202=
5 20:49:25","Cascaded Incident from TTO4285926","Siligap Boris","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Site went down due to =
PWC overload(12K, 230A) SS Judicael confirmed // Site stabilized ","system"=
,"301732","05-02-2025 20:43:50","Sagemcom CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0004262607","Nko=
lmesseng","IHS_YND_215, IHS_YND_739, IHS_YND_214, IHS_YND_217","05-02-2025 =
20:37:19","05-02-2025 20:15:06","05-02-2025 20:49:25","Site went down due t=
o PWC overload(12K, 230A) SS Judicael confirmed // Site stabilized ","Silig=
ap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module Overlo=
aded","Site went down due to PWC overload(12K, 230A) SS Judicael confirmed =
// Site stabilized ","ervine.mbezele@sagemcom.com","1334","05-02-2025 20:37=
:19","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004262453","Men=
dong NB","","05-02-2025 20:28:03","05-02-2025 20:09:56","05-02-2025 20:09:5=
7","No power issue on site U=3D54v site on grid Hosiah/674007438 of huawei =
is informed and notice that disjunction in OCM Equipement","","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site U=3D54v site on grid Hosiah/674007438 of huawei is in=
formed and notice that disjunction in OCM Equipement","ervine.mbezele@sagem=
com.com","1088","05-02-2025 20:28:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004262223","MEHANDAN=
","","05-02-2025 19:55:40","05-02-2025 19:49:29","05-02-2025 19:55:29","Cas=
caded Incident from TTO4285450","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to gen card faulty //Grid return","system","288872","=
05-02-2025 19:55:40","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004262195","Nko=
zoa","","05-02-2025 19:55:14","05-02-2025 18:40:48","05-02-2025 19:49:28","=
Grid outage, site went down due to gen overload (20kva, 340A) SS HIS Felix =
bateu is informed and confirmed// He reduced the load and gen manually star=
ted","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, site went down due to gen overload (20kva, 340A) SS HIS=
 Felix bateu is informed and confirmed// He reduced the load and gen manual=
ly started","ervine.mbezele@sagemcom.com","4508","05-02-2025 19:55:14","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004262181","O=
dza II OCM","IHS_YND_528","05-02-2025 19:51:36","05-02-2025 19:49:29","05-0=
2-2025 19:55:29","Grid outage, site went down because gen failed to start d=
ue to gen card faulty //Grid return","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down becau=
se gen failed to start due to gen card faulty //Grid return","wilfried.kame=
ni@sagemcom.com","129","05-02-2025 19:51:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004262157","M=
imboman-Ecole","","05-02-2025 19:48:49","05-02-2025 19:26:44","05-02-2025 1=
9:26:45","No power issue on site Ubaie=3D50.7 V site on Grid. The FME TX El=
oundou Bertrant / 693212405/ From Huawei is Informed.","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue on site Ubaie=3D50.7 V site on Grid. The FME TX E=
loundou Bertrant / 693212405/ From Huawei is Informed.","wilfried.kameni@sa=
gemcom.com","1326","05-02-2025 19:48:49","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004262081","HOP=
ITAL GENERAL RAIL YDE","","05-02-2025 19:35:21","05-02-2025 19:17:10","05-0=
2-2025 20:11:10","Grid outage, Site went down because Gen overload (9kva,16=
0A) SS IHS Bernard ATANGANA is informed// Grid return","Delor Telezing","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site w=
ent down because Gen overload (9kva,160A) SS IHS Bernard ATANGANA is inform=
ed// Grid return","ervine.mbezele@sagemcom.com","1092","05-02-2025 19:35:21=
","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004262027","Elo=
umdem stade","","05-02-2025 19:29:56","05-02-2025 19:15:16","05-02-2025 19:=
31:52","Site went down due to insufficiency of rectifier due to load increa=
se, IHS SS FELIX ZAMBE is confirmed// Site stabilized","Fanda Brice","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down due t=
o insufficiency of rectifier due to load increase, IHS SS FELIX ZAMBE is co=
nfirmed// Site stabilized","ervine.mbezele@sagemcom.com","881","05-02-2025 =
19:29:56","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004262009","Ngo=
usso Vallee","","05-02-2025 19:25:49","05-02-2025 18:54:34","05-02-2025 20:=
03:29","Grid outage ,Site went down because Gen stopped with alarm"" low oi=
l pressure "" (unprouven Alarm)//He reset Gen card and started Gen","Siliga=
p Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage ,Site went down because Gen stopped with alarm"" low oil pressure=
 "" (unprouven Alarm)//He reset Gen card and started Gen","ervine.mbezele@s=
agemcom.com","1876","05-02-2025 19:25:49","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004261950","Nko=
g-Edzen","","05-02-2025 19:13:38","05-02-2025 18:40:02","05-02-2025 19:28:3=
7","No power issue on site with  Ubaie=3D51.4 V site on Battery  (start thr=
eshold ubai=3D50 V) The Tx Fme Gregoire( 652070658)from Huawei is informed.=
 R=E9p=E9titif issue","Parker Tchoup","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site wi=
th  Ubaie=3D51.4 V site on Battery  (start threshold ubai=3D50 V) The Tx Fm=
e Gregoire( 652070658)from Huawei is informed. R=E9p=E9titif issue","ervine=
.mbezele@sagemcom.com","2017","05-02-2025 19:13:38","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004261659","Pha=
rmacie SION","","05-02-2025 18:26:59","05-02-2025 18:17:38","05-02-2025 18:=
27:28","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen started automatically","Paul BIBOUM","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen started automatically=
","ervine.mbezele@sagemcom.com","562","05-02-2025 18:26:59","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004261641","Ema=
na","","05-02-2025 18:24:24","05-02-2025 18:12:58","05-02-2025 18:24:48","G=
rid outage, site went down before gen  fails to start due to poor battery b=
ackup // Gen started automatically","Fabrice Pouakam","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down before gen  fails to start due to poor battery backup // Gen starte=
d automatically","ervine.mbezele@sagemcom.com","687","05-02-2025 18:24:24",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004261627","B=
iteng-Maetur","","05-02-2025 18:23:07","05-02-2025 14:14:59","05-02-2025 14=
:20:14","No power issue, site is on grid with Ubaie=3D53V, Housmanou(694644=
252) from Telis working on site (OUD CHANGE)","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue, site is on grid with Ubaie=3D53V, Housmanou(694644252) fr=
om Telis working on site (OUD CHANGE)","wilfried.kameni@sagemcom.com","1489=
0","05-02-2025 18:23:07","Sagemcom CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004261616","Eto=
udi2","","05-02-2025 18:19:32","05-02-2025 18:02:04","05-02-2025 19:40:29",=
"Site went down due to insufficiency of rectifier // site stabilized","Delo=
r Telezing","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to insufficiency of rectifier // site stabilized","ervine.=
mbezele@sagemcom.com","1049","05-02-2025 18:19:32","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004261097","AWA=
E OCM","","05-02-2025 16:52:55","05-02-2025 16:34:45","05-02-2025 18:36:22"=
,"site went down because Gen failed to start due to lack of 2 phase on site=
 // he did a bridge with a good phase ","Mba Lazare Herve","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","site went down be=
cause Gen failed to start due to lack of 2 phase on site // he did a bridge=
 with a good phase ","ervine.mbezele@sagemcom.com","1252","05-02-2025 16:52=
:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004260210","M=
ontee-Anne-Rouge","","05-02-2025 15:45:25","05-02-2025 13:47:16","06-02-202=
5 03:36:46","Active, no power issue U=3D49 V site on Grid. The Tx Fme Eloun=
dou 652586578 of Huawei is informed.","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issue=
 U=3D49 V site on Grid. The Tx Fme Eloundou 652586578 of Huawei is informed=
.","wilfried.kameni@sagemcom.com","7091","05-02-2025 15:45:25","Sagemcom CM=
R"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004258869","OBA=
M NGOLA OCM","","05-02-2025 14:29:33","05-02-2025 14:01:27","05-02-2025 15:=
27:27","Site went down because CB(80A) tripped in PWC// CB put back on","MI=
NKA NICOLAS","Equipment Repair","Passive","Control Panel","Power Cabinet - =
Circuit Breaker Issue","Site went down because CB(80A) tripped in PWC// CB =
put back on","ervine.mbezele@sagemcom.com","1687","05-02-2025 14:29:33","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004258862","Ona=
ngondi (melen bikop)","","05-02-2025 14:28:43","05-02-2025 14:03:36","05-02=
-2025 15:37:19","Grid outage, Site went down because Gen started and stoppe=
d with ""high temp"" alarm// He added water and started Gen manualy","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - =
Coolant Level Issue","Grid outage, Site went down because Gen started and s=
topped with ""high temp"" alarm// He added water and started Gen manualy","=
ervine.mbezele@sagemcom.com","1508","05-02-2025 14:28:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0004258845","S=
apeur","","05-02-2025 14:25:33","05-02-2025 14:09:18","05-02-2025 21:09:03"=
,"Site went down due to Theft of cable (20mx2) in DC BOX  who feeds equipme=
nts OCM// He replaced cable","Mboua Thierry","Site Asset Theft","Theft","Th=
eft","DC Cable Stolen","Site went down due to Theft of cable (20mx2) in DC =
BOX  who feeds equipments OCM// He replaced cable","kouoh.jean@ihstowers.co=
m","977","05-02-2025 14:25:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004258628","Akak-Nko=
zoa-MTN-IHS","","05-02-2025 13:54:21","05-02-2025 11:07:50","05-02-2025 11:=
17:24","Cascaded Incident from TTO4281371","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid Outage, site Down du=
e to poor backup // Grid return","system","269596","05-02-2025 13:54:21","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004258581","Akak-Nko=
zoa-MTN-IHS","","05-02-2025 13:46:30","05-02-2025 12:34:25","05-02-2025 12:=
38:59","Cascaded Incident from TTO4280716","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid Outage, site Down du=
e to poor backup // Grid return","system","264509","05-02-2025 13:46:30","S=
agemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004258560","BAT=
A Mokolo OCM","","05-02-2025 13:43:18","05-02-2025 13:38:47","05-02-2025 16=
:28:14","Grid outage, no space to deploy a mobile//grid return ","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, n=
o space to deploy a mobile//grid return ","ervine.mbezele@sagemcom.com","27=
2","05-02-2025 13:43:18","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004258522","Aha=
la Echangeur","","05-02-2025 13:38:51","05-02-2025 12:46:39","05-02-2025 13=
:58:33"," Site went down because Gen failed to start due to Gen card dysfun=
ctionning // He rest card GE and started Gen manualy","MINKA NICOLAS","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel"," Site went down =
because Gen failed to start due to Gen card dysfunctionning // He rest card=
 GE and started Gen manualy","ervine.mbezele@sagemcom.com","3132","05-02-20=
25 13:38:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004258411","O=
lembe-Terminus","","05-02-2025 13:31:35","05-02-2025 13:19:22","05-02-2025 =
13:50:12","No power issue on site U=3D53v site on grid Tx fme Armand 671716=
363 of hauwei is informed","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site U=3D53v site on grid Tx fme Armand 671716363 of hauwei is informed","e=
rvine.mbezele@sagemcom.com","734","05-02-2025 13:31:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0004258398","I=
mm-Olympique","","05-02-2025 13:29:29","05-02-2025 13:06:23","06-02-2025 05=
:13:27","Active// No power issue Site on Grid Ubai =3D 54V The FME TX Brice=
 stague(65072631) from HUAWEI is  informed. Notice that disjunction of CB i=
n BTS Ocm","Paul BIBOUM","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active// No power issue Site on Grid U=
bai =3D 54V The FME TX Brice stague(65072631) from HUAWEI is  informed. Not=
ice that disjunction of CB in BTS Ocm","ervine.mbezele@sagemcom.com","1387"=
,"05-02-2025 13:29:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004258380","B=
itoto","","05-02-2025 13:27:23","05-02-2025 12:55:03","05-02-2025 13:44:09"=
,"Grid outage,site went down due to pwc ZTE dysfunction// he reset it and  =
site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","=
Rectifier Module Overloaded","Grid outage,site went down due to pwc ZTE dys=
function// he reset it and  site on Grid","ervine.mbezele@sagemcom.com","19=
42","05-02-2025 13:27:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0004258344","E=
kie sud","","05-02-2025 13:18:04","05-02-2025 12:32:42","05-02-2025 13:32:0=
3","Grid outage, DG failed to start due to ACDG battery faulty // He starte=
d DG with external battery.","Albran Byorel","Equipment Repair","Passive","=
ACDG Gen","ACDG - Generator Battery","Grid outage, DG failed to start due t=
o ACDG battery faulty // He started DG with external battery.","ervine.mbez=
ele@sagemcom.com","2723","05-02-2025 13:18:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004258320","S=
tade-Abega","","05-02-2025 13:14:34","05-02-2025 12:31:19","05-02-2025 13:2=
2:19","Grid outage,site went down because Gen failed to start due to pwc ZT=
E dysfunction// he reset it and started Gen manualy","Mba Lazare Herve","Eq=
uipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid o=
utage,site went down because Gen failed to start due to pwc ZTE dysfunction=
// he reset it and started Gen manualy","ervine.mbezele@sagemcom.com","2596=
","05-02-2025 13:14:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0004258221","E=
lig-Essono","","05-02-2025 13:02:38","05-02-2025 12:22:22","05-02-2025 13:2=
2:26","site went down due to CB(63A) DISJUNTED in the PWC//he Made the Brid=
ge betewen 2*CB (63A)","Paul BIBOUM","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Circuit Breaker Issue","site went down due to CB(63=
A) DISJUNTED in the PWC//he Made the Bridge betewen 2*CB (63A)","ervine.mbe=
zele@sagemcom.com","2417","05-02-2025 13:02:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0004258217","M=
ontee-Anne-Rouge","","05-02-2025 13:01:24","05-02-2025 12:15:09","05-02-202=
5 13:33:19","Grid outage, No space to deploy MDG // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MDG // Grid return","ervine.mbezele@sagemcom.com","2776",=
"05-02-2025 13:01:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004258181","M=
vog-Manga","","05-02-2025 12:56:02","05-02-2025 12:24:42","05-02-2025 14:21=
:19","Grid outage,Gen started and stopped due to high temp because of load =
increase //He opened the doors.","Albran Byorel","Equipment Repair","Passiv=
e","ACDG Gen","Gen Temp High","Grid outage,Gen started and stopped due to h=
igh temp because of load increase //He opened the doors.","ervine.mbezele@s=
agemcom.com","1882","05-02-2025 12:56:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0004258176","E=
zezang","","05-02-2025 12:54:50","05-02-2025 12:44:43","05-02-2025 13:01:02=
","Site went down due to work Ulrich/Sagemcom/656072680 doing the PM//End o=
f work","Parker Tchoup","Installation Activity","Passive","Planned Activity=
","Installation Activity","Site went down due to work Ulrich/Sagemcom/65607=
2680 doing the PM//End of work","kouoh.jean@ihstowers.com","607","05-02-202=
5 12:54:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0004258032","H=
-General-Yde","","05-02-2025 12:39:37","05-02-2025 11:36:29","05-02-2025 13=
:46:54","Grid outage,gen failed to start due to alarm underfrequency//he re=
set it and started the gen","Siligap Boris","Equipment Repair","Passive","A=
CDG Gen","ACDG - Under Frequency","Grid outage,gen failed to start due to a=
larm underfrequency//he reset it and started the gen","ervine.mbezele@sagem=
com.com","3789","05-02-2025 12:39:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0004258017","F=
ouda-New","","05-02-2025 12:36:51","05-02-2025 11:15:43","06-02-2025 02:54:=
26","Active// No power issue, site is on Grid with U=3D52,8 V The Tx Fme Ar=
mand //691144412 from Huawei is informed","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power issue, site is on Grid with U=3D52,8 V The Tx Fme Armand //69=
1144412 from Huawei is informed","ervine.mbezele@sagemcom.com","4869","05-0=
2-2025 12:36:51","Sagemcom CMR"
"Closed Complete","Site Down","T0854","IHS_YND_211","NOCINC0004257945","Eto=
udi 2","","05-02-2025 12:24:27","05-02-2025 12:11:16","05-02-2025 12:33:42"=
,"Grid outage, site went down because gen fails to start due to card ge dis=
function // reset of gen card done and gen started","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, sit=
e went down because gen fails to start due to card ge disfunction // reset =
of gen card done and gen started","ervine.mbezele@sagemcom.com","825","05-0=
2-2025 12:24:27","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004257931","BIY=
EMASSI NIKI","","05-02-2025 12:22:37","05-02-2025 11:11:02","05-02-2025 11:=
12:02","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d, F=E9lix Zambe is informed and confirmed // Site stabilized","Hyemafo Gil=
das","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded"=
,"Site went down due to PWC overloaded (12kva 250 A) //Site stabilized, F=
=E9lix Zambe is informed and confirmed // Site stabilized","ervine.mbezele@=
sagemcom.com","13430","05-02-2025 12:22:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004257927","S=
atcom","","05-02-2025 12:22:21","05-02-2025 11:02:29","06-02-2025 02:55:54"=
,"	No power issue on site, site on Gen with U=3D54v .The Tx Fme Armand ngue=
tsa(691144412) From huawei is informed.","Delor Telezing","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	No p=
ower issue on site, site on Gen with U=3D54v .The Tx Fme Armand nguetsa(691=
144412) From huawei is informed.","rodrigue.nono-ext@sagemcom.com","4793","=
05-02-2025 12:22:21","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004257909","Nko=
lafeme","","05-02-2025 12:21:00","05-02-2025 12:11:46","05-02-2025 12:33:29=
","Grid outage, Site went down due to Gen overload(20KVA, 375A) SS IHS Pasc=
aline confirmed// Grid return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage, Site went do=
wn due to Gen overload(20KVA, 375A) SS IHS Pascaline confirmed// Grid retur=
n","ervine.mbezele@sagemcom.com","555","05-02-2025 12:21:00","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0004257900","Mfo=
u EPC","","05-02-2025 12:19:38","05-02-2025 12:03:23","05-02-2025 12:42:23"=
,"Grid outage,Site went down because Gen stopped with alarm ""high temp""//=
 He added water and started Gen manually","Mba Lazare Herve","Equipment Rep=
air","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","=
Grid outage,Site went down because Gen stopped with alarm ""high temp""// H=
e added water and started Gen manually","ervine.mbezele@sagemcom.com","1413=
","05-02-2025 12:19:38","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004257872","Bit=
eng-Maetur","","05-02-2025 12:16:00","05-02-2025 11:59:52","05-02-2025 13:2=
9:04","Grid outage, site went down due to Gen overload (20kva, 280), Alphon=
se IHS confirm//grid return","Mba Lazare Herve","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage, site went down due to Gen over=
load (20kva, 280), Alphonse IHS confirm//grid return","ervine.mbezele@sagem=
com.com","1020","05-02-2025 12:16:00","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004257835","Nko=
abang2","","05-02-2025 12:12:50","05-02-2025 12:00:41","05-02-2025 12:05:46=
","Active// No Power Issue : Achilles/679-12-41-36 is working at Nkoabang M=
TN ODU change. .","Mba Lazare Herve","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active// No Power Issue : =
Achilles/679-12-41-36 is working at Nkoabang MTN ODU change.
.","ervine.mbezele@sagemcom.com","730","05-02-2025 12:12:50","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004257796","Fla=
menco","","05-02-2025 12:10:30","05-02-2025 11:55:21","05-02-2025 12:45:58"=
,"Grid outage, site went down because gen failed to start due to gen card f=
aulty // Grid restored","Mboua Thierry","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid outage, site went down because gen failed=
 to start due to gen card faulty // Grid restored","ervine.mbezele@sagemcom=
.com","910","05-02-2025 12:10:30","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004257765","Nko=
zoa","","05-02-2025 12:04:23","05-02-2025 11:44:54","05-02-2025 12:37:41","=
Site went down because Gen fails  to start due to lack of 01 phase No rcp//=
He did a bridge with a good phase","Fabrice Pouakam","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Site went down because =
Gen fails  to start due to lack of 01 phase No rcp//He did a bridge with a =
good phase","ervine.mbezele@sagemcom.com","10637","05-02-2025 12:04:23","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004257748","Man=
guiers Dispensaire","","05-02-2025 12:00:59","05-02-2025 11:41:45","05-02-2=
025 12:24:57","Grid outage site went down because Gen failed to start due t=
o grid contactor faulty// Gen manually started","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage site went =
down because Gen failed to start due to grid contactor faulty// Gen manuall=
y started","ervine.mbezele@sagemcom.com","1155","05-02-2025 12:00:59","Sage=
mcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004257740","ODZ=
A MINKAN EDIBI ASSI","","05-02-2025 11:59:46","05-02-2025 11:39:36","05-02-=
2025 15:24:15","Grid outage , DG started but did not feed the site due to E=
NEO contactor HS //Bypass contactor ENEO,site on DG.","Albran Byorel","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage , DG s=
tarted but did not feed the site due to ENEO contactor HS //Bypass contacto=
r ENEO,site on DG.","ervine.mbezele@sagemcom.com","1211","05-02-2025 11:59:=
46","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0004257725","Eko=
umdoum OCM","","05-02-2025 11:56:27","05-02-2025 11:32:05","05-02-2025 13:3=
1:53","Grid outage ,Gen started and stopped due to ACDG overload (20 kva , =
290 A) //Grid restored pascaline confirmed.","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage ,Gen started and s=
topped due to ACDG overload (20 kva , 290 A) //Grid restored pascaline conf=
irmed.","ervine.mbezele@sagemcom.com","1463","05-02-2025 11:56:27","Sagemco=
m CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004257713","Com=
plex Beac II","","05-02-2025 11:53:21","05-02-2025 11:28:09","05-02-2025 14=
:53:48","Grid outage,DG started but did not feed the site due to ENEO conta=
ctor blocked //Grid restored.","Albran Byorel","Equipment Repair","Passive"=
,"Control Panel","ATS-AMF Issue","Grid outage,DG started but did not feed t=
he site due to ENEO contactor blocked //Grid restored.","ervine.mbezele@sag=
emcom.com","1513","05-02-2025 11:53:21","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004257703","Nom=
ayos montee Meche","","05-02-2025 11:50:48","05-02-2025 11:18:40","05-02-20=
25 12:32:53","Grid outage, Site went because Gen failed to start because fu=
el valve closed// He open fuel valve and started Gen manualy (investigation=
 ongoing)","Fanda Brice","Fuel Outage (Probable)","Passive","Diesel","Fuel =
Line Issue","Grid outage, Site went because Gen failed to start because fue=
l valve closed// He open fuel valve and started Gen manualy (investigation =
ongoing)","ervine.mbezele@sagemcom.com","15802","05-02-2025 11:50:48","Sage=
mcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004257698","Nsi=
meyong Terre Rouge","","05-02-2025 11:49:48","05-02-2025 11:19:37","05-02-2=
025 12:41:13","Site went down due to pwc Disfunction, SS IHS Fran=E7ois is =
informed // Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down due to pwc Disfunc=
tion, SS IHS Fran=E7ois is informed // Site stabilized","ervine.mbezele@sag=
emcom.com","1812","05-02-2025 11:49:48","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004257684","Mes=
sa Carriere","","05-02-2025 11:47:19","05-02-2025 11:13:07","05-02-2025 12:=
28:53","Site went down because 01/03 rectifier faulty SS IHS Fran=E7ois is =
informed and confirmed // Site stabilized","Mboua Thierry","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Site went down because 01/03 r=
ectifier faulty SS IHS Fran=E7ois is informed and confirmed // Site stabili=
zed","ervine.mbezele@sagemcom.com","2053","05-02-2025 11:47:19","Sagemcom C=
MR"
"Closed Complete","Site Down","T2585","IHS_YND_744","NOCINC0004257675","Ele=
veur Meec Bon Berger","","05-02-2025 11:45:06","05-02-2025 11:11:00","05-02=
-2025 12:18:06","Grid outage, site went down because gen fails to start due=
 to battery ge discharged // Gen start with battery backup","Siligap Boris"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid o=
utage, site went down because gen fails to start due to battery ge discharg=
ed // Gen start with battery backup","ervine.mbezele@sagemcom.com","2047","=
05-02-2025 11:45:06","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004257664","Ako=
k Ndoe Yde","","05-02-2025 11:42:39","05-02-2025 11:12:08","05-02-2025 12:3=
0:18","Grid outage, Site went down before Gen start due to poor backup// Ge=
n manually started manually","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup// Gen manually started manually","steph=
ane.nkamwa@ihstowers.com","1832","05-02-2025 11:42:39","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004257659","ETO=
UDI Entree du palais","","05-02-2025 11:42:09","05-02-2025 11:09:00","05-02=
-2025 11:49:44","Grid outage, site went down becaus egen fails to start due=
 to card ge dysfunction // reset of gen card done and gen started","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, site went down becaus egen fails to start due to card ge dysfun=
ction // reset of gen card done and gen started","ervine.mbezele@sagemcom.c=
om","1990","05-02-2025 11:42:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004257594","C=
rf-Nsam","","05-02-2025 11:33:40","05-02-2025 11:09:33","05-02-2025 12:32:5=
3","Site went down Because The Slot of Rectifier is overload //site stabili=
zed SS Ihs Pascaline is informed and is confirmed","MINKA NICOLAS","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went d=
own Because The Slot of Rectifier is overload //site stabilized SS Ihs Pasc=
aline is informed and is confirmed","kouoh.jean@ihstowers.com","1448","05-0=
2-2025 11:33:40","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004257496","Nko=
ulou Carriere carrefourt","","05-02-2025 11:20:27","05-02-2025 11:02:18","0=
5-02-2025 16:20:13","Site went down becuse 02/03 rectifiers hanging //he re=
set rectifiers .SIte on Grid","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down becuse 02/03 rectifiers h=
anging //he reset rectifiers .SIte on Grid","ervine.mbezele@sagemcom.com","=
1090","05-02-2025 11:20:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004257134","O=
dza II","","05-02-2025 10:22:50","05-02-2025 10:04:37","05-02-2025 10:10:27=
","Active//No power issue U =3D54,5V site on Grid. The Tx FME Adjet (655-18=
-48-76 )from Huawei is informed.","Albran Byorel","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No po=
wer issue U =3D54,5V site on Grid. The Tx FME Adjet (655-18-48-76 )from Hua=
wei is informed.","ervine.mbezele@sagemcom.com","1095","05-02-2025 10:22:50=
","Sagemcom CMR"
"Closed Complete","Site Down","T1665","IHS_YND_014","NOCINC0004256769","ELI=
g-Essono","","05-02-2025 09:17:06","05-02-2025 09:11:48","05-02-2025 09:58:=
58","Grid outage,gen failed to start due to  Gen CB 32A disjuncted//he ream=
ed the CB","Delor Telezing","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Circuit Breaker Issue","Grid outage,gen failed to start due =
to  Gen CB 32A disjuncted//he reamed the CB","ervine.mbezele@sagemcom.com",=
"319","05-02-2025 09:17:06","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004256647","Elo=
umdem stade","","05-02-2025 08:51:38","05-02-2025 08:38:29","05-02-2025 10:=
01:53","Grid bad voltage,and gen failed to start no rcp//bypassed grid and =
started the gen","Fanda Brice","Grid Supply","Passive","Grid","National Gri=
d - Phase Controller Faulty","Grid bad voltage,and gen failed to start no r=
cp//bypassed grid and started the gen","ervine.mbezele@sagemcom.com","790",=
"05-02-2025 08:51:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0004256542","A=
nguissa New","","05-02-2025 08:32:17","05-02-2025 08:27:09","05-02-2025 09:=
41:03","Grid outage, site went down because gen start but not feed the site=
 due to CB(32A) gen disfunction // Normalization done: site on gen","MINKA =
NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Gri=
d outage, site went down because gen start but not feed the site due to CB(=
32A) gen disfunction // Normalization done: site on gen","ervine.mbezele@sa=
gemcom.com","310","05-02-2025 08:32:17","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004256460","Eko=
unou","","05-02-2025 08:14:00","05-02-2025 08:04:43","05-02-2025 15:57:26",=
"site went down due to work SS IHS Blaise is working on site( SWAP PWC) // =
End of work","Albran Byorel","Equipment Replacement","Passive","Planned Act=
ivity","Planned Activity - Passive","site went down due to work SS IHS Blai=
se is working on site( SWAP PWC) // End of work","ervine.mbezele@sagemcom.c=
om","628","05-02-2025 08:14:00","Sagemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004256439","Nko=
abang entree carriere","","05-02-2025 08:08:48","05-02-2025 08:03:40","05-0=
2-2025 08:47:40","site went down because gen failed to start due to battery=
 Ge faulty,SS IHS Alphonse is informed//he started the gen with battery bac=
kup","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Gen=
erator Battery","site went down because gen failed to start due to battery =
Ge faulty,SS IHS Alphonse is informed//he started the gen with battery back=
up","ervine.mbezele@sagemcom.com","309","05-02-2025 08:08:48","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004256391","B=
arriere IHS","","05-02-2025 07:58:16","05-02-2025 07:49:50","05-02-2025 07:=
54:07","Active//No power issue site on Grid with U=3D51,6V.The FME TX  Mbah=
 Osiah (674007438) from Huawei is informed","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue site on Grid with U=3D51,6V.The FME TX  Mbah Osiah (67=
4007438) from Huawei is informed","el-dalile@sagemcom.com","507","05-02-202=
5 07:58:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004256352","S=
IMBOCK BONAMBAPE","","05-02-2025 07:51:23","05-02-2025 07:38:08","05-02-202=
5 07:50:08","Active//No power issue site on grid with U=3D54,6 V Mbah Osiah=
  from Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue site on grid with U=3D54,6 V Mbah Osiah  from Huawei is informed","el-d=
alile@sagemcom.com","796","05-02-2025 07:51:23","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004256280","ODZ=
A MINKAN EDIBI ASSI","","05-02-2025 07:35:09","05-02-2025 07:28:52","05-02-=
2025 09:16:24","Grid outage,site went down because gen failed to start due =
to grid contactor disfunctionning//he excited the grid contactor","Albran B=
yorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid o=
utage,site went down because gen failed to start due to grid contactor disf=
unctionning//he excited the grid contactor","ervine.mbezele@sagemcom.com","=
378","05-02-2025 07:35:09","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004256238","SAA=
 Entrance","","05-02-2025 07:26:56","05-02-2025 07:25:49","05-02-2025 08:09=
:57","Grid bad voltage,and gen failed to start,no rcp//grid stabilized","Pa=
rker Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid bad voltage,and gen failed to start,no rcp//grid stabilize=
d","ervine.mbezele@sagemcom.com","68","05-02-2025 07:26:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0004256085","B=
riqueterie","","05-02-2025 07:04:03","05-02-2025 06:50:53","05-02-2025 20:3=
0:03","Grid outage, No space to deploy MDG // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spac=
e to deploy MDG // Grid return","ervine.mbezele@sagemcom.com","792","05-02-=
2025 07:04:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004256060","M=
vog-Manga","","05-02-2025 06:59:49","05-02-2025 06:41:14","05-02-2025 07:14=
:20","Grid outage,gen stopped with alarm high temp//he added water in radia=
tor","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","Grid outage,gen stopped with alarm high =
temp//he added water in radiator","el-dalile@sagemcom.com","1116","05-02-20=
25 06:59:49","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004256018","Tou=
ring Club International","","05-02-2025 06:52:18","05-02-2025 06:44:59","05=
-02-2025 08:39:54","Grid outage,gen failed to start due to card ge disfunct=
ionning//Gen manually started","Albran Byorel","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due to =
card ge disfunctionning//Gen manually started","el-dalile@sagemcom.com","43=
9","05-02-2025 06:52:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004255998","M=
ontee-Des-Soeurs","","05-02-2025 06:49:42","05-02-2025 06:39:31","05-02-202=
5 06:59:31","No power Issue Site on Grid Ubai =3D54.3 V, The FME The TX FME=
 Mbah Hosiah (674007438) is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 Issue Site on Grid Ubai =3D54.3 V, The FME The TX FME Mbah Hosiah (6740074=
38) is informed","el-dalile@sagemcom.com","612","05-02-2025 06:49:42","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004255954","M=
elen Ba'aba","","05-02-2025 06:45:21","05-02-2025 06:39:13","05-02-2025 07:=
08:30","Grid bad voltage,and gen failed to start //grid stabilized","Siliga=
p Boris","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid bad voltage,and gen failed to start //grid stabilized","ervine=
.mbezele@sagemcom.com","369","05-02-2025 06:45:21","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004255909","Bri=
quetterie","","05-02-2025 06:35:11","05-02-2025 06:26:00","05-02-2025 20:30=
:14","Grid outage, No space to deploy MDG // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space=
 to deploy MDG // Grid return","ervine.mbezele@sagemcom.com","552","05-02-2=
025 06:35:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0004255792","B=
astos Bir","","05-02-2025 06:01:57","05-02-2025 05:39:47","05-02-2025 06:06=
:00","No power issue on site  U=3D 54.5V site on Grid   FME TX Eloundou (65=
2586578) from Huawei is informed","Mboua Thierry","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site  U=3D 54.5V site on Grid   FME TX Eloundou (652586578) from Huawe=
i is informed","danick.tchakouani@sagemcom.com","1331","05-02-2025 06:01:57=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004255657","S=
IMBOCK BONAMBAPE","","05-02-2025 05:05:21","05-02-2025 04:39:07","05-02-202=
5 04:45:35","No power issue site on grid with U=3D54,6 V Mbah Osiah  from H=
uawei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid=
 with U=3D54,6 V Mbah Osiah  from Huawei is informed","wilfried.kameni@sage=
mcom.com","1575","05-02-2025 05:05:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004255439","N=
kolfon Cimencam","","05-02-2025 03:54:44","05-02-2025 03:27:22","05-02-2025=
 04:08:23","No power issue on site U=3D54,5v site on Gen FME Fulbert (65426=
6068) of huawei is informed.Notice that site is impacted by Afanoya II Who =
is not our responsability","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D54,5v site on Gen FME Fulbert (654266068) of huawei is informed.Not=
ice that site is impacted by AfanoyaII Who is not our responsability","wilf=
ried.kameni@sagemcom.com","1643","05-02-2025 03:54:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004255091","Carrefou=
r Ayissi Ele","","05-02-2025 02:14:40","05-02-2025 01:39:32","05-02-2025 01=
:39:33","Cascaded Incident from TTO4277276","Parker Tchoup","Cascade Outage=
","Active","Cascade Active","Cascade Active","Active//No power issue on sit=
e Ubaie=3D50V site on Solar site impacted by SA=92A ocm Tx FME Gregoire /65=
4547479/Huawei is informed and confirmed","system","267730","05-02-2025 02:=
14:40","Sagemcom CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004255087","Nko=
l-Mebanga","IHS_YND_810","05-02-2025 02:12:44","05-02-2025 01:39:32","05-02=
-2025 01:39:33","Active//No power issue on site Ubaie=3D50V site on Solar s=
ite impacted by SA=92A ocm Tx FME Gregoire /654547479/Huawei is informed an=
d confirmed","Parker Tchoup","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site Uba=
ie=3D50V site on Solar site impacted by SA=92A ocm Tx FME Gregoire /6545474=
79/Huawei is informed and confirmed","danick.tchakouani@sagemcom.com","1992=
","05-02-2025 02:12:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004255084","SAA 2","=
","05-02-2025 02:11:10","05-02-2025 01:58:09","05-02-2025 02:49:09","Cascad=
ed Incident from TTO4277231","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because gen s=
topped due to water mixed with fuel in tank // He purged TANK and started t=
he gen","system","273798","05-02-2025 02:11:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004255049","S=
aa","IHS_YND_404","05-02-2025 02:05:56","05-02-2025 01:58:09","05-02-2025 0=
2:49:09","Grid outage, Site went down because gen stopped due to water mixe=
d with fuel in tank // He purged TANK and started the gen","Parker Tchoup",=
"Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In =
The Fuel","Grid outage, Site went down because gen stopped due to water mix=
ed with fuel in tank // He purged TANK and started the gen","danick.tchakou=
ani@sagemcom.com","468","05-02-2025 02:05:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004254587","L=
abogenie","","04-02-2025 23:48:54","04-02-2025 23:42:46","05-02-2025 00:15:=
19","No power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (69321240=
5 )from Huawei is informed. Repetitive Issue","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 U =3D54,5V site on Grid. The Tx FME  Eloundou (693212405 )from Huawei is i=
nformed. Repetitive Issue","danick.tchakouani@sagemcom.com","369","04-02-20=
25 23:48:54","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004254564","Com=
plex Beac II","","04-02-2025 23:41:19","04-02-2025 23:36:58","05-02-2025 00=
:30:12"," Site went down due to disjunction of Rectifier CB(40) // CB put b=
ack on","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier=
 - Circuit Breaker"," Site went down due to disjunction of Rectifier CB(40)=
 // CB put back on","wilfried.kameni@sagemcom.com","262","04-02-2025 23:41:=
19","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004254539","Nko=
zoa","","04-02-2025 23:30:25","04-02-2025 23:28:08","04-02-2025 23:30:02","=
Grid fluctuation site went down because Gen failed to start due to Grid bad=
 voltage // Grid stabilized","Fabrice Pouakam","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Grid fluctuation site went do=
wn because Gen failed to start due to Grid bad voltage // Grid stabilized",=
"wilfried.kameni@sagemcom.com","138","04-02-2025 23:30:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0004254521","O=
LAMA","","04-02-2025 23:22:57","04-02-2025 21:56:37","04-02-2025 21:56:38",=
"Active//No power issue on site, Site on Gen , UBAIE=3D54V and Geoges (6974=
61814) From huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power =
issue on site, Site on Gen , UBAIE=3D54V and Geoges (697461814) From huawei=
 is informed","danick.tchakouani@sagemcom.com","5181","04-02-2025 23:22:57"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004254460","Bri=
quetterie","","04-02-2025 23:09:05","04-02-2025 22:44:45","05-02-2025 01:25=
:12","Grid outage No space to deploy // Grid power return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No space=
 to deploy // Grid power return","wilfried.kameni@sagemcom.com","1461","04-=
02-2025 23:09:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0004254410","Crf-Nkol=
bisson","","04-02-2025 22:57:50","04-02-2025 22:43:51","04-02-2025 22:56:11=
","Cascaded Incident from TTO4276456","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Site went down du to =
insufficiency of rectifier, IHS SS FELIX ZAMBE is informed // site stabiliz=
ed","system","278361","04-02-2025 22:57:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004254388","M=
EFOU ASSI","IHS_YND_232","04-02-2025 22:55:03","04-02-2025 22:43:51","04-02=
-2025 22:56:11","Site went down du to insufficiency of rectifier, IHS SS FE=
LIX ZAMBE is informed // site stabilized","Fanda Brice","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","Site went down du to insufficienc=
y of rectifier, IHS SS FELIX ZAMBE is informed // site stabilized","wilfrie=
d.kameni@sagemcom.com","673","04-02-2025 22:55:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0004254381","N=
gousso OCM","","04-02-2025 22:52:33","04-02-2025 22:43:06","05-02-2025 00:0=
9:52","Grid outage, site went down because gen ran until fuel shortage // r=
efueling done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, site went down because gen ran until fuel shortage // re=
fueling done","wilfried.kameni@sagemcom.com","568","04-02-2025 22:52:33","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004254060","Barriere=
 IHS","","04-02-2025 21:44:50","04-02-2025 21:31:46","04-02-2025 21:35:54",=
"Cascaded Incident from TTO4276054","Hyemafo Gildas","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active// No power issue on site  Uba=
ie=3D54.3V site On Grid The Tx FME Fulbert(654266068) of huawei is informed=
","system","275392","04-02-2025 21:44:50","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004254059","Nko=
lnda","","04-02-2025 21:44:42","04-02-2025 21:33:37","04-02-2025 22:19:13",=
"Site went down because Gen started and stopped due to pear pierced// he st=
uck the pear and Gen manually started","Albran Byorel","Fuel Outage (Probab=
le)","Passive","Diesel","Fuel Line Issue","Site went down because Gen start=
ed and stopped due to pear pierced// he stuck the pear and Gen manually sta=
rted","ervine.mbezele@sagemcom.com","666","04-02-2025 21:44:42","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004254051","M=
efou-Assi","IHS_YND_696","04-02-2025 21:43:52","04-02-2025 21:31:46","04-02=
-2025 21:35:54","Active// No power issue on site  Ubaie=3D54.3V site On Gri=
d The Tx FME Fulbert(654266068) of huawei is informed","Fanda Brice","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue on site  Ubaie=3D54.3V site On Grid The Tx FM=
E Fulbert(654266068) of huawei is informed","wilfried.kameni@sagemcom.com",=
"727","04-02-2025 21:43:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004253914","MEHANDAN=
","","04-02-2025 21:23:00","04-02-2025 21:11:46","04-02-2025 22:00:23","Cas=
caded Incident from TTO4275894","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to gen card faulty // Gen manually started","system",=
"283970","04-02-2025 21:23:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004253908","O=
dza II OCM","IHS_YND_528","04-02-2025 21:21:53","04-02-2025 21:11:46","04-0=
2-2025 22:00:23","Grid outage, site went down because gen failed to start d=
ue to gen card faulty // Gen manually started","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went =
down because gen failed to start due to gen card faulty // Gen manually sta=
rted","wilfried.kameni@sagemcom.com","608","04-02-2025 21:21:53","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004253616","A=
wae Ewonkan","","04-02-2025 20:48:19","04-02-2025 20:32:13","04-02-2025 22:=
46:07","Site unstable due to insufficiency rectifiers (06 rectfiers) due to=
 load increase on site IHS SS Alphonse is informed and is confirmed // Site=
 stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site unstable due to insufficiency rectifiers (06 rectfiers)=
 due to load increase on site IHS SS Alphonse is informed and is confirmed =
// Site stabilized","wilfried.kameni@sagemcom.com","967","04-02-2025 20:48:=
19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004253503","S=
IMBOCK BONAMBAPE","","04-02-2025 20:29:32","04-02-2025 20:12:37","04-02-202=
5 20:20:39","No power issue site on grid with U=3D54,6 V Mbah Osiah  from H=
uawei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid=
 with U=3D54,6 V Mbah Osiah  from Huawei is informed","wilfried.kameni@sage=
mcom.com","1016","04-02-2025 20:29:32","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004253465","Nko=
lo II New","","04-02-2025 20:21:26","04-02-2025 19:49:47","04-02-2025 21:25=
:18","Active: no power issue, site is on grid with Ubaie=3D53V, Lionel Adje=
p(655184876) from Huawei is informed","Mba Lazare Herve","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
: no power issue, site is on grid with Ubaie=3D53V, Lionel Adjep(655184876)=
 from Huawei is informed","wilfried.kameni@sagemcom.com","1900","04-02-2025=
 20:21:26","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004253380","Aha=
la Echangeur","","04-02-2025 20:10:49","04-02-2025 19:52:24","04-02-2025 21=
:15:47","Grid outage site went down because Gen failed to start due to Gen =
card dysfonction // He reset the Gen Card and Gen manually started","MINKA =
NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage site went down because Gen failed to start due to Gen card dysfon=
ction // He reset the Gen Card and Gen manually started","wilfried.kameni@s=
agemcom.com","1106","04-02-2025 20:10:49","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004253249","ODZ=
A MINKAN EDIBI ASSI","","04-02-2025 19:46:37","04-02-2025 19:35:27","04-02-=
2025 20:37:03","Grid outage site went down because Gen failed to start due =
to grid contactor denergized// He excited grid contactor","Albran Byorel","=
Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage si=
te went down because Gen failed to start due to grid contactor denergized//=
 He excited grid contactor","ervine.mbezele@sagemcom.com","671","04-02-2025=
 19:46:37","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004253187","Eko=
unou","","04-02-2025 19:32:41","04-02-2025 19:25:28","04-02-2025 19:33:09",=
"Site went down due to work: Albran /657108542/SAGEMCOM working on site (Sw=
ap Main Gen)// End of work","Albran Byorel","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to work: =
Albran /657108542/SAGEMCOM working on site (Swap Main Gen)// End of work","=
ervine.mbezele@sagemcom.com","435","04-02-2025 19:32:41","Sagemcom CMR"
"Closed Complete","Warning","T0638","IHS_YND_318","NOCINC0004253027","SOA U=
niversity","","04-02-2025 19:10:26","","","Grid outgae Site alarming becaus=
e Gen failed to start // Gen automatically started and alarm cleared","Sili=
gap Boris","Warning","Warning","POWER","Warning - Site on Battery","Grid ou=
tgae Site alarming because Gen failed to start // Gen automatically started=
 and alarm cleared","wilfried.kameni@sagemcom.com","916","04-02-2025 19:10:=
26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0004252925","H=
-Paradis","","04-02-2025 18:58:56","04-02-2025 18:38:42","04-02-2025 21:40:=
18","Active // No power issue site on grid with U=3D54,6 V Tx Fme Armand Ng=
estsa (691144412) of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active // No power =
issue site on grid with U=3D54,6 V Tx Fme Armand Ngestsa (691144412) of hua=
wei is informed","wilfried.kameni@sagemcom.com","1215","04-02-2025 18:58:56=
","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004252898","Mes=
sa Carriere","","04-02-2025 18:54:51","04-02-2025 18:53:30","04-02-2025 19:=
11:49","Site went down because 01/03 rectifier faulty SS IHS Fran=E7ois is =
informed and confirmed // Site stabilized","Mboua Thierry","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Site went down because 01/03 r=
ectifier faulty SS IHS Fran=E7ois is informed and confirmed // Site stabili=
zed","ervine.mbezele@sagemcom.com","82","04-02-2025 18:54:51","Sagemcom CMR=
"
"Closed Complete","Warning","CTR_154","IHS_YND_518","NOCINC0004252538","Mon=
tee-Jouvence-II","","04-02-2025 17:50:00","","","Site alarming due to PWC O=
verloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed//Site Stabilized and al=
arm cleared","Hyemafo Gildas","Warning","Warning","POWER","Warning - Site o=
n Battery","Site alarming due to PWC Overloaded (12K, 250A)SS IHS Felix Zam=
b=E9 confirmed//Site Stabilized and alarm cleared","wilfried.kameni@sagemco=
m.com","249","04-02-2025 17:50:00","Sagemcom CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0004252532","Sof=
avinc","","04-02-2025 17:47:57","04-02-2025 17:38:51","04-02-2025 18:50:13"=
,"Active: No power issue, site is on grid with Ubaie=3D53V, Rm Alain (69114=
4423) from Huawie is informed","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power=
 issue, site is on grid with Ubaie=3D53V, Rm Alain (691144423) from Huawie =
is informed","ervine.mbezele@sagemcom.com","547","04-02-2025 17:47:57","Sag=
emcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004252302","BAT=
A Mokolo OCM","","04-02-2025 17:18:17","04-02-2025 17:07:46","05-02-2025 11=
:02:26","Grid outage, no space to deploy a mobil gen//grid return ","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, no space to deploy a mobil gen//grid return ","ervine.mbezele@sagemcom.co=
m","633","04-02-2025 17:18:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0004251895","Bastos E=
koudou","","04-02-2025 16:28:10","04-02-2025 16:12:11","05-02-2025 11:31:25=
","Cascaded Incident from TTO4273544","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, no space to deploy =
a mobil gen // Grid restored","system","395426","04-02-2025 16:28:10","Sage=
mcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004251891","Lab=
oratoire  Meka","IHS_YND_193","04-02-2025 16:27:22","04-02-2025 16:12:11","=
05-02-2025 11:31:25","Grid outage // MDG 20Kva has deployed","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage // MDG=
 20Kva has deployed","ervine.mbezele@sagemcom.com","911","04-02-2025 16:27:=
22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004251659","L=
abogenie","","04-02-2025 15:51:35","04-02-2025 15:45:30","04-02-2025 17:20:=
26","No power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (69321240=
5 )from Huawei is informed. Repetitive Issue","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 U =3D54,5V site on Grid. The Tx FME  Eloundou (693212405 )from Huawei is i=
nformed. Repetitive Issue","wilfried.kameni@sagemcom.com","366","04-02-2025=
 15:51:35","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004251540","Ebo=
go","","04-02-2025 15:35:36","04-02-2025 15:33:32","04-02-2025 15:35:46","G=
rid outage, Site went down because Gen failed to start// Grid return (inves=
tigation ongoing)","Siligap Boris","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Grid outage, Site went down because Gen failed to s=
tart// Grid return (investigation ongoing)","wilfried.kameni@sagemcom.com",=
"125","04-02-2025 15:35:36","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004251491","Fou=
da Quarter","","04-02-2025 15:29:48","04-02-2025 15:27:38","04-02-2025 18:1=
5:54","Active// No power issue, Site on Grid Ubai=3D51V. The tecnician Arma=
nd /651316875 From HUAWEI working on site","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive// No power issue, Site on Grid Ubai=3D51V. The tecnician Armand /651316=
875 From HUAWEI working on site","ervine.mbezele@sagemcom.com","131","04-02=
-2025 15:29:48","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004251086","NYO=
M FACE MAETUR","","04-02-2025 14:45:38","04-02-2025 14:39:31","04-02-2025 1=
5:54:03","Grid fluctuation, site went down because gen start and stopped du=
e to grid bad voltage // He bypass grid and manually start the gen","Fabric=
e Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","Grid fluctuation, site went down because gen start and stopped du=
e to grid bad voltage // He bypass grid and manually start the gen","wilfri=
ed.kameni@sagemcom.com","368","04-02-2025 14:45:38","Sagemcom CMR"
"Closed Complete","Site Down","T0638","IHS_YND_318","NOCINC0004250364","SOA=
 University","","04-02-2025 13:04:52","04-02-2025 12:59:39","04-02-2025 13:=
25:13","Grid outage,gen stopped with alarm high temp// he added water in ra=
diator","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Hig=
h Engine Temp - Coolant Level Issue","Grid outage,gen stopped with alarm hi=
gh temp// he added water in radiator","ervine.mbezele@sagemcom.com","314","=
04-02-2025 13:04:52","Sagemcom CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004250339","Nta=
ba","","04-02-2025 13:01:33","04-02-2025 12:50:02","04-02-2025 13:48:05","G=
rid fluctuation, site went down before gen start due to poor battery backup=
 // Gen start automatically","Delor Telezing","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid fluctuation, site went =
down before gen start due to poor battery backup // Gen start automatically=
","ervine.mbezele@sagemcom.com","692","04-02-2025 13:01:33","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004249810","Ngo=
a Ekelle","","04-02-2025 11:54:24","04-02-2025 11:46:09","04-02-2025 12:38:=
56","No power issue on site U=3D54,5v site on grid Tx fme Hosiah of huawei =
is informed","Paul BIBOUM","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,5v sit=
e on grid Tx fme Hosiah of huawei is informed","ervine.mbezele@sagemcom.com=
","496","04-02-2025 11:54:24","Sagemcom CMR"
"Closed Complete","Site Down","T1577","IHS_YND_086","NOCINC0004249696","POL=
YCLINIQUE TSINGA","","04-02-2025 11:46:44","04-02-2025 11:39:28","04-02-202=
5 12:45:24","No power issue on site U=3D54v site on grid Tx fme Brice Nomo =
of huawei is informed","Mboua Thierry","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54v site on grid Tx fme Brice Nomo of huawei is informed","ervine.mbezel=
e@sagemcom.com","437","04-02-2025 11:46:44","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004249501","Ako=
k Ndoe Yde","","04-02-2025 11:28:04","04-02-2025 11:21:55","04-02-2025 12:2=
5:36","Grid outage, Site went down before Gen start due to poor battery bac=
kup//Gen manually started","Hyemafo Gildas","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down be=
fore Gen start due to poor battery backup//Gen manually started","ervine.mb=
ezele@sagemcom.com","370","04-02-2025 11:28:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004249332","L=
abogenie","","04-02-2025 10:59:36","04-02-2025 10:40:21","04-02-2025 11:04:=
59","No power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (69321240=
5 )from Huawei is informed.Site up at 11:04 Am Notice that it is the repeti=
tive issue. ","","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue U =3D54,5V site on Grid. The Tx=
 FME  Eloundou (693212405 )from Huawei is informed.Site up at 11:04 Am Noti=
ce that it is the repetitive issue.=20
","ervine.mbezele@sagemcom.com","1156","04-02-2025 10:59:36","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0004249179","Bri=
quetterie","","04-02-2025 10:40:46","04-02-2025 10:32:29","04-02-2025 21:50=
:41","Grid outage, No space to deploy MDG //  Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spac=
e to deploy MDG //  Grid return","ervine.mbezele@sagemcom.com","498","04-02=
-2025 10:40:46","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004249081","BAT=
A Mokolo OCM","","04-02-2025 10:32:14","04-02-2025 10:27:55","04-02-2025 15=
:03:30","Grid outage, No space to deploy MDG //  Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No s=
pace to deploy MDG //  Grid return","ervine.mbezele@sagemcom.com","260","04=
-02-2025 10:32:14","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004248636","BAT=
A Mokolo OCM","","04-02-2025 09:17:28","04-02-2025 08:54:06","04-02-2025 09=
:53:16","Grid outage, No space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No sp=
ace to deploy MDG // Grid return","ervine.mbezele@sagemcom.com","1403","04-=
02-2025 09:17:28","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004248416","Ema=
na","","04-02-2025 08:46:28","04-02-2025 08:41:19","04-02-2025 08:54:05","G=
rid outage site went down before gen start due to poor battery backup // Ge=
n auatomatiy","Fabrice Pouakam","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage site went down before gen star=
t due to poor battery backup // Gen auatomati","wilfried.kameni@sagemcom.co=
m","310","04-02-2025 08:46:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0004248061","B=
ATA-Mokolo","","04-02-2025 07:53:02","04-02-2025 07:42:18","04-02-2025 08:1=
8:39","Grid outage No space to deploy // Grid power return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No spac=
e to deploy // Grid power return","ervine.mbezele@sagemcom.com","645","04-0=
2-2025 07:53:02","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004247773","BAT=
A Mokolo OCM","","04-02-2025 07:00:53","04-02-2025 06:54:22","04-02-2025 08=
:48:32","Grid outage, No space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No sp=
ace to deploy MDG // Grid return","ervine.mbezele@sagemcom.com","392","04-0=
2-2025 07:00:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0004247748","Dagobert=
","","04-02-2025 06:54:00","04-02-2025 06:38:35","04-02-2025 06:50:02","Cas=
caded Incident from TTO4268844","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D54v=
 site on grid Tx fme Mohamadou of huawei is informed","system","278776","04=
-02-2025 06:54:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0004247744","N=
kolbi-Boss","IHS_YND_286","04-02-2025 06:52:53","04-02-2025 06:38:35","04-0=
2-2025 06:50:02","No power issue on site U=3D54v site on grid Tx fme Mohama=
dou of huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site U=3D54v site on grid Tx fme Mohamadou of huawei is informed",=
"ervine.mbezele@sagemcom.com","859","04-02-2025 06:52:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004247042","N=
kolfon Cimencam","","04-02-2025 03:26:01","04-02-2025 03:18:30","04-02-2025=
 03:25:57","No power issue on site U=3D54,5v site on Gen FME  Fulbert  (654=
266068) of huawei is informed.Notice that site is impacted by AfanoyaII Who=
 is not our responsability","Hyemafo Gildas","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site U=3D54,5v site on Gen FME  Fulbert  (654266068) of huawei is informed.=
Notice that site is impacted by AfanoyaII Who is not our responsability","w=
ilfried.kameni@sagemcom.com","453","04-02-2025 03:26:01","Sagemcom CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0004246944","Nta=
ba","","04-02-2025 02:44:05","04-02-2025 02:22:37","04-02-2025 02:29:24","G=
rid outage site went down before gen start due to poor battery backup // Gr=
id power return","Delor Telezing","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage site went down before gen st=
art due to poor battery backup // Grid power return","wilfried.kameni@sagem=
com.com","1290","04-02-2025 02:44:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004246904","N=
gouetou","","04-02-2025 02:29:44","04-02-2025 02:17:34","04-02-2025 02:23:5=
9","Active//No power issue site on gen with U=3D54v Gregoire/652070658/ fro=
m Huawei is informed","Parker Tchoup","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue si=
te on gen with U=3D54v Gregoire/652070658/ from Huawei is informed","wilfri=
ed.kameni@sagemcom.com","731","04-02-2025 02:29:44","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0004246828","Nko=
abang Ebolmedjock","","04-02-2025 01:53:54","04-02-2025 01:49:46","04-02-20=
25 03:00:03","site went down because Gen stopped due to air intake at the d=
iesel filter // he replaced the gasket and Gen manually started","Mba Lazar=
e Herve","Fuel Outage (Probable)","Passive","Diesel","Fuel Line Issue","sit=
e went down because Gen stopped due to air intake at the diesel filter // h=
e replaced the gasket and Gen manually started","wilfried.kameni@sagemcom.c=
om","249","04-02-2025 01:53:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004246614","L=
abogenie","","04-02-2025 00:46:26","03-02-2025 23:01:43","04-02-2025 00:55:=
33","ACTIVE//No power issue U =3D54,5V site on Grid. The Tx FME Eloundou (6=
93212405 )from Huawei is informed. Notice that it is the repetitive issue",=
"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","ACTIVE//No power issue U =3D54,5V site on Grid. The Tx FME E=
loundou (693212405 )from Huawei is informed. Notice that it is the repetiti=
ve issue","wilfried.kameni@sagemcom.com","6285","04-02-2025 00:46:26","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004246134","B=
iteng-Maetur","","03-02-2025 22:44:54","03-02-2025 22:15:36","03-02-2025 22=
:20:46","No power issue, site is on grid with Ubaie=3D53V, Lionel Adjep(655=
184876) from Huawei is iformed, Notice that we have disjunction at BTS OCM =
","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue, site is on grid with Ubaie=
=3D53V, Lionel Adjep(655184876) from Huawei is iformed, Notice that we have=
 disjunction at BTS OCM ","wilfried.kameni@sagemcom.com","1759","03-02-2025=
 22:44:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004245670","C=
rf-Nsam","","03-02-2025 21:31:39","03-02-2025 20:57:27","03-02-2025 21:47:4=
9","Site went down Because The Slot of Rectifier is overload //site stabili=
zed SS Ihs Pascaline is informed and is confirmed","MINKA NICOLAS","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went d=
own Because The Slot of Rectifier is overload //site stabilized SS Ihs Pasc=
aline is informed and is confirmed","danick.tchakouani@sagemcom.com","2053"=
,"03-02-2025 21:31:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004245665","MEHANDAN=
","","03-02-2025 21:30:40","03-02-2025 21:21:13","03-02-2025 23:40:04","Cas=
caded Incident from TTO4266424","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down because Ge=
n failed to start due to Gen card dysfunctionning // He rest card GE and st=
arted Gen manualy","system","276163","03-02-2025 21:30:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004245656","O=
dza II OCM","IHS_YND_528","03-02-2025 21:29:22","03-02-2025 21:21:13","03-0=
2-2025 23:40:04","Grid outage, Site went down because Gen failed to start d=
ue to Gen card dysfunctionning // He rest card GE and started Gen manualy",=
"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Grid outage, Site went down because Gen failed to start due to Gen car=
d dysfunctionning // He rest card GE and started Gen manualy","danick.tchak=
ouani@sagemcom.com","490","03-02-2025 21:29:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004245528","SOA VILL=
AGE","","03-02-2025 21:09:40","03-02-2025 20:50:15","03-02-2025 21:30:49","=
Cascaded Incident from TTO4266272","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation site went down bec=
ause Gen started and stopped due to Grid bad voltage and RCP ON SITE // He =
bypass the Grid and Gen manually started","system","1227328","03-02-2025 21=
:09:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004245523","S=
OA TOWN","IHS_YND_323","03-02-2025 21:08:26","03-02-2025 20:48:15","03-02-2=
025 21:30:49","Grid fluctuation site went down because Gen started and stop=
ped due to Grid bad voltage and RCP ON SITE // He bypass the Grid and Gen m=
anually started","Siligap Boris","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation site went down because Gen=
 started and stopped due to Grid bad voltage and RCP ON SITE // He bypass t=
he Grid and Gen manually started","danick.tchakouani@sagemcom.com","1212","=
03-02-2025 21:08:26","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004245390","Nko=
ulou Carriere carrefourt","","03-02-2025 20:43:24","03-02-2025 20:28:13","0=
4-02-2025 06:37:01","Access Issue during the Night due to landlord,Site wen=
t down because CB 63*2 A disjuncted in DC-Box//he reamed the CB","Mba Lazar=
e Herve","Access Denial","Lease Or Legal","Landlord Related Issues","Access=
 Issue - Land Lord","Access Issue during the Night due to landlord,Site wen=
t down because CB 63*2 A disjuncted in DC-Box//he reamed the CB","danick.tc=
hakouani@sagemcom.com","912","03-02-2025 20:43:24","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004245216","NYO=
M FACE MAETUR","","03-02-2025 20:18:33","03-02-2025 20:08:26","03-02-2025 2=
1:56:56","Grid fluctuation, Site went down because Gen failed to start due =
to lack of 01 phase// He did a bridge on the good phase","Fabrice Pouakam",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid fluctuation, Site went down because Gen failed to start due to lack of =
01 phase// He did a bridge on the good phase","wilfried.kameni@sagemcom.com=
","608","03-02-2025 20:18:33","Sagemcom CMR"
"Closed Complete","Site Down","T1747","IHS_YND_728","NOCINC0004245171","TRO=
PICANA NEW","","03-02-2025 20:09:30","03-02-2025 20:05:01","03-02-2025 20:1=
0:01","No power issue U =3D52.9V site on Grid.The Tx FME  Rm Martial (69008=
7047 )from Huawei is informed by sms","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue U =3D52.9V site on Grid.The Tx FME  Rm Martial (690087047 )from Huawe=
i is informed by sms","danick.tchakouani@sagemcom.com","270","03-02-2025 20=
:09:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004244800","L=
abogenie","","03-02-2025 19:17:12","03-02-2025 18:38:53","03-02-2025 20:12:=
53","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed. Notice that it is the repetitive issue=
 ","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx F=
ME  Eloundou (693212405 )from Huawei is informed. Notice that it is the rep=
etitive issue ","danick.tchakouani@sagemcom.com","2300","03-02-2025 19:17:1=
2","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004244643","BAT=
A Mokolo OCM","","03-02-2025 18:57:53","03-02-2025 18:32:25","04-02-2025 06=
:36:06","GRID OUTAGE, No space to deploy a mobile gen// grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","GRID OUTAG=
E, No space to deploy a mobile gen// grid return","danick.tchakouani@sagemc=
om.com","1529","03-02-2025 18:57:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0004244531","M=
vog-Ebanda","","03-02-2025 18:41:25","03-02-2025 18:21:16","03-02-2025 19:4=
4:16","Grid fluctuation, Site went down because Gen failed to start due to =
lack of 01 phase// He did a bridge on the good phase","Siligap Boris","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid f=
luctuation, Site went down because Gen failed to start due to lack of 01 ph=
ase// He did a bridge on the good phase","danick.tchakouani@sagemcom.com","=
1211","03-02-2025 18:41:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004244432","B=
arriere IHS","","03-02-2025 18:27:57","03-02-2025 18:14:49","03-02-2025 19:=
11:49","Site went down because 02/06 rectifiers hanging// He resert rectifi=
ers,site on Grid","Hyemafo Gildas","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down because 02/06 rectifiers hanging// He r=
esert rectifiers,site on Grid","danick.tchakouani@sagemcom.com","789","03-0=
2-2025 18:27:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0004244344","Crf Corn=
ier","","03-02-2025 18:13:10","03-02-2025 17:31:03","03-02-2025 18:23:03","=
Cascaded Incident from TTO4264884","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because CB(125*80A) =
tripped in PWC// CB put back on ","system","275347","03-02-2025 18:13:10","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004244336","M=
adison","IHS_YND_566","03-02-2025 18:12:34","03-02-2025 17:31:03","03-02-20=
25 18:23:03","Site went down because CB(125*80A) tripped in PWC// CB put ba=
ck on ","MFOUAGUEGUE MATHIEU","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Circuit Breaker Issue","Site went down because CB(125*80A)=
 tripped in PWC// CB put back on ","wilfried.kameni@sagemcom.com","2492","0=
3-02-2025 18:12:34","Sagemcom CMR"
"Closed Complete","Site Down","T1565","IHS_YND_261","NOCINC0004244324","Bar=
riere","","03-02-2025 18:10:19","03-02-2025 18:04:27","03-02-2025 20:20:54"=
,"ACTIVE//No power issue site on Grid Ubaie =3D54.6 V, The tx Huawei  Fulbe=
rt  (654266068) is informed","Hyemafo Gildas","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power =
issue site on Grid Ubaie =3D54.6 V, The tx Huawei  Fulbert  (654266068) is =
informed","danick.tchakouani@sagemcom.com","353","03-02-2025 18:10:19","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004244171","Elig Edz=
oa","","03-02-2025 17:42:12","03-02-2025 16:32:57","03-02-2025 17:25:57","C=
ascaded Incident from TTO4264117","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because CB (80A) tri=
pped in PWC // He did a bridge with a CB(80A)","system","271662","03-02-202=
5 17:42:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0004244168","HOPITAL =
DE LA CAISSE","","03-02-2025 17:42:11","03-02-2025 16:32:57","03-02-2025 17=
:25:57","Cascaded Incident from TTO4264117","Delor Telezing","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because CB=
 (80A) tripped in PWC // He did a bridge with a CB(80A)","system","271660",=
"03-02-2025 17:42:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0004244170","Charles-=
Atangana","","03-02-2025 17:42:11","03-02-2025 16:32:57","03-02-2025 17:25:=
57","Cascaded Incident from TTO4264117","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because CB (80A) tripped in =
PWC // He did a bridge with a CB(80A)","system","271660","03-02-2025 17:42:=
11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_091","NOCINC0004244167","Jouvence=
 2000","","03-02-2025 17:42:11","03-02-2025 16:32:57","03-02-2025 17:25:57"=
,"Cascaded Incident from TTO4264117","Delor Telezing","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site went down because CB (80A) =
tripped in PWC // He did a bridge with a CB(80A)","system","271661","03-02-=
2025 17:42:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0004244169","ELIg-Ess=
ono","","03-02-2025 17:42:11","03-02-2025 16:32:57","03-02-2025 17:25:57","=
Cascaded Incident from TTO4264117","Delor Telezing","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because CB (80A) tr=
ipped in PWC // He did a bridge with a CB(80A)","system","271661","03-02-20=
25 17:42:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0004244166","Mamch Bu=
ilding","","03-02-2025 17:42:10","03-02-2025 16:32:57","03-02-2025 17:25:57=
","Cascaded Incident from TTO4264117","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site went down because CB (80A) =
tripped in PWC // He did a bridge with a CB(80A)","system","271660","03-02-=
2025 17:42:10","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004244104","Ako=
k Ndoe Yde","","03-02-2025 17:31:43","03-02-2025 17:04:30","03-02-2025 18:1=
0:22","Grid fluctuation, site went down because gen failed to start due to =
grid bad voltage No Rcp on site // He bypassed Grid and started Gen manualy=
","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation, site went down because gen failed to st=
art due to grid bad voltage No Rcp on site // He bypassed Grid and started =
Gen manualy","wilfried.kameni@sagemcom.com","1634","03-02-2025 17:31:43","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004243960","S=
calom","","03-02-2025 17:09:09","03-02-2025 16:54:53","03-02-2025 16:54:54"=
,"Active//No power issue on site ,site on Grid with Ubaie=3D54,5V The TX FM=
E Mbah Hosiah (674007438) from Huawei is informed and notice that disjuncti=
on at COM Equipment","Paul BIBOUM","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on si=
te ,site on Grid with Ubaie=3D54,5V The TX FME Mbah Hosiah (674007438) from=
 Huawei is informed and notice that disjunction at COM Equipment","danick.t=
chakouani@sagemcom.com","857","03-02-2025 17:09:09","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0004243755","Ess=
os Marche","","03-02-2025 16:51:20","03-02-2025 16:46:10","03-02-2025 17:04=
:17","Grid outage, Site went down because Gen failed to start due to PWC ZT=
E disfunction// He started Gen manualy (Configuration PWC ongoing by SS IHS=
 Blaise Raul)","Delor Telezing","Equipment Repair","Passive","Control Panel=
","Panel Distribution Board","Grid outage, Site went down because Gen faile=
d to start due to PWC ZTE disfunction// He started Gen manualy (Configurati=
on PWC ongoing by SS IHS Blaise Raul)","danick.tchakouani@sagemcom.com","31=
2","03-02-2025 16:51:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004243730","C=
RH-Etoug-Ebe","","03-02-2025 16:45:40","03-02-2025 16:34:28","03-02-2025 16=
:56:00","Active: no power issue, site is on grid with Ubaie=3D53V, Mohamado=
u(691144435) from Huawei is informed. Notice that we have disjunction in OC=
M equipment","Hyemafo Gildas","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, site is o=
n grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei is informed. Noti=
ce that we have disjunction in OCM equipment","wilfried.kameni@sagemcom.com=
","673","03-02-2025 16:45:40","Sagemcom CMR"
"Closed Complete","Site Down","T0498","IHS_YND_049","NOCINC0004243673","Eto=
a-Meki","IHS_YND_051, IHS_YND_091, IHS_YND_064, IHS_YND_014, IHS_YND_125, I=
HS_YND_504","03-02-2025 16:37:18","03-02-2025 16:32:57","03-02-2025 17:25:5=
7","Site went down because CB (80A) tripped in PWC // He did a bridge with =
a CB(80A)","Delor Telezing","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Circuit Breaker Issue","Site went down because CB (80A) trip=
ped in PWC // He did a bridge with a CB(80A)","wilfried.kameni@sagemcom.com=
","262","03-02-2025 16:37:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004243638","A=
wae Ewonkan","","03-02-2025 16:30:53","03-02-2025 16:27:45","03-02-2025 20:=
01:14","Site went down due to insufficiency rectifiers (06 rectfiers) due t=
o load increase on site IHS SS Alphonse is informed and is confirmed// Site=
 stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rect=
ifier Module Overloaded","Site went down due to insufficiency rectifiers (0=
6 rectfiers) due to load increase on site IHS SS Alphonse is informed and i=
s confirmed// Site stabilized","wilfried.kameni@sagemcom.com","189","03-02-=
2025 16:30:53","Sagemcom CMR"
"Closed Complete","Site Down","T2795","IHS_YND_070","NOCINC0004243584","Efo=
ulan","","03-02-2025 16:24:43","03-02-2025 16:17:02","03-02-2025 16:17:03",=
"No power issue site on Grid Ubaie =3D54.6 V, The FME The RM Alain (6911444=
23) is informed","MINKA NICOLAS","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue site on Grid Ub=
aie =3D54.6 V, The FME The RM Alain (691144423) is informed","danick.tchako=
uani@sagemcom.com","461","03-02-2025 16:24:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004243471","S=
IMBOCK BONAMBAPE","","03-02-2025 16:09:00","03-02-2025 07:15:38","03-02-202=
5 07:20:07","No power issue site on grid with U=3D52,6 V Mbah Osiah  from H=
uawei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid=
 with U=3D52,6 V Mbah Osiah  from Huawei is informed","wilfried.kameni@sage=
mcom.com","32003","03-02-2025 16:09:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0004243469","Crf Corn=
ier","","03-02-2025 16:08:20","03-02-2025 15:55:43","03-02-2025 17:02:51","=
Cascaded Incident from TTO4263877","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage// Grid return","system"=
,"274188","03-02-2025 16:08:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004243458","M=
adison","IHS_YND_566","03-02-2025 16:07:01","03-02-2025 15:55:43","03-02-20=
25 17:02:51","Grid outage// Grid return","MFOUAGUEGUE MATHIEU","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage// Grid =
return","danick.tchakouani@sagemcom.com","679","03-02-2025 16:07:01","Sagem=
com CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004243428","AKA=
K Nkozoa","","03-02-2025 16:00:31","03-02-2025 15:46:15","03-02-2025 17:18:=
15","Grid outage, site went down because gen start and stopped with emergen=
cy stop alarm // reset of gen card done and gen started","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Site on ge=
n due to grid outage, site went down because land lord stop the gen // Gen =
manually started","danick.tchakouani@sagemcom.com","857","03-02-2025 16:00:=
31","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004243402","Eko=
unou","","03-02-2025 15:54:21","03-02-2025 15:33:30","03-02-2025 17:09:30",=
"Site went down due to disjunction of CB(80) in PWC due to increase load //=
 He did a bridge with another CB(63)A: Site on grid","Albran Byorel","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Iss=
ue","Site went down due to disjunction of CB(80) in PWC due to increase loa=
d // He did a bridge with another CB(63)A: Site on grid","danick.tchakouani=
@sagemcom.com","1253","03-02-2025 15:54:21","Sagemcom CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0004243219","Efo=
ulan MTN","","03-02-2025 15:22:59","03-02-2025 15:15:43","03-02-2025 17:20:=
44","Active, no power issue, U=3D54.3V on grid Tonang Jordan/651162743/Teli=
s is working on site (SWAP MW)","MINKA NICOLAS","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no powe=
r issue, U=3D54.3V on grid Tonang Jordan/651162743/Telis is working on site=
 (SWAP MW)","danick.tchakouani@sagemcom.com","437","03-02-2025 15:22:59","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0004243118","Kondengu=
i","","03-02-2025 15:07:51","03-02-2025 14:44:39","03-02-2025 20:08:35","Ca=
scaded Incident from TTO4263479","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, No space to deploy MDG//=
 Grid return","system","285596","03-02-2025 15:07:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0004243107","E=
mombo-Tchad","IHS_YND_114","03-02-2025 15:05:54","03-02-2025 14:44:39","03-=
02-2025 20:08:35","Grid outage, No space to deploy MDG// Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, No space to deploy MDG// Grid return","wilfried.kameni@sagemcom.com","1=
276","03-02-2025 15:05:54","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004242972","Elo=
umdem stade","","03-02-2025 14:41:39","03-02-2025 14:19:29","03-02-2025 16:=
02:06","Site went down due to insufficiency of rectifier due to load increa=
se, IHS SS FELIX ZAMBE is confirmed// Site stabilized","Fanda Brice","Equip=
ment Repair","Passive","Rectifier","Rectifier Module","Site went down due t=
o insufficiency of rectifier due to load increase, IHS SS FELIX ZAMBE is co=
nfirmed// Site stabilized","danick.tchakouani@sagemcom.com","1331","03-02-2=
025 14:41:39","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004242564","BAT=
A Mokolo OCM","","03-02-2025 13:55:58","03-02-2025 13:28:50","03-02-2025 14=
:21:33","Grid only site ,no sapce to deploy mobile gen  // Grid power  RETU=
RN","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
rid only site ,no sapce to deploy mobile gen  // Grid power  RETURN","ervin=
e.mbezele@sagemcom.com","1629","03-02-2025 13:55:58","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004242342","Fla=
menco","","03-02-2025 13:14:38","03-02-2025 13:11:29","03-02-2025 14:19:18"=
,"Grid outage, site went down because gen failed to start due to gen card f=
aulty // Grid restored","Mboua Thierry","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid outage, site went down because gen failed=
 to start due to gen card faulty // Grid restored","ervine.mbezele@sagemcom=
.com","190","03-02-2025 13:14:38","Sagemcom CMR"
"Closed Complete","Warning","T0029","IHS_YND_357","NOCINC0004242331","Sacre=
 Coeur Catholic Church","","03-02-2025 13:11:28","","","Site alarming high =
temp because air conditionner stopped due to grid outage and gen started an=
d stopped with undervoltage alarm // reset on gen card done and gen manuall=
y started","Mboua Thierry","Warning","Warning","ENVIRONMENT","Warning - Hig=
h Temperature","Site alarming high temp because air conditionner stopped du=
e to grid outage and gen started and stopped with undervoltage alarm // res=
et on gen card done and gen manually started","ervine.mbezele@sagemcom.com"=
,"3733","03-02-2025 13:11:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004242281","A=
kak-Nkozoa-MTN-IHS","","03-02-2025 12:56:39","03-02-2025 12:49:22","03-02-2=
025 13:02:47","Grid fluctuation, site went down because Gen started and sto=
pped due to Grid bad voltage  // He bypassed Grid and Gen manually started"=
,"Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation, site went down because Gen started and =
stopped due to Grid bad voltage  // He bypassed Grid and Gen manually start=
ed","wilfried.kameni@sagemcom.com","439","03-02-2025 12:56:39","Sagemcom CM=
R"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0004242145","Feb=
e Village","","03-02-2025 12:24:53","03-02-2025 12:01:29","03-02-2025 12:07=
:24","ACTIVE//no power issue, site is on Gen THE fme tx Mohamadou (69114413=
5) from Huawei is informed","Mboua Thierry","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no power is=
sue, site is on Gen THE fme tx Mohamadou (691144135) from Huawei is informe=
d","ervine.mbezele@sagemcom.com","1405","03-02-2025 12:24:53","Sagemcom CMR=
"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004242102","AKA=
K Nkozoa","","03-02-2025 12:14:18","03-02-2025 11:44:07","03-02-2025 12:18:=
39","Site went down due to work(Fabrice(657108613) from Sagemcom, Draining =
// End of work","Fabrice Pouakam","Equipment Replacement","Passive","Planne=
d Activity","Planned Activity - Passive","Site went down due to work(Fabric=
e(657108613) from Sagemcom, Draining // End of work","ervine.mbezele@sagemc=
om.com","1812","03-02-2025 12:14:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004242050","E=
kounou","","03-02-2025 12:01:11","03-02-2025 11:45:00","03-02-2025 12:25:36=
","ENEO surge, site went down because gen Overload(20KVA, 300A)//Grid resto=
red.","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","ENEO surge, site went down because gen Overload(20KVA, 300A)//Grid re=
stored.","wilfried.kameni@sagemcom.com","973","03-02-2025 12:01:11","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004241640","M=
imboman-Ecole","","03-02-2025 11:01:00","03-02-2025 10:18:46","03-02-2025 1=
0:29:11","Grid outage site went down before gen start due to poor battery b=
ackup // Gen auatomatically started","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site w=
ent down before gen start due to poor battery backup // Gen auatomatically =
started","wilfried.kameni@sagemcom.com","2537","03-02-2025 11:01:00","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004241566","A=
wae Ewonkan","","03-02-2025 10:46:28","03-02-2025 10:37:20","03-02-2025 12:=
21:07","Site went down due to insufficiency rectifiers (06 rectfiers) due t=
o load increase on site  IHS SS Alphonse is informed and is confirmed // Si=
te stabilized(waiting to add o1 rectifier)","Albran Byorel","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module","Site went down due to insuffi=
ciency rectifiers (06 rectfiers) due to load increase on site  IHS SS Alpho=
nse is informed and is confirmed // Site stabilized(waiting to add o1 recti=
fier)","wilfried.kameni@sagemcom.com","549","03-02-2025 10:46:28","Sagemcom=
 CMR"
"Cancelled","Warning","CTR_632","IHS_YND_721","NOCINC0004241548","VOIRIE MU=
NICIPALE YAOUNDE","","03-02-2025 10:43:22","","","","Paul BIBOUM","","","",=
"","","wilfried.kameni@sagemcom.com","368","03-02-2025 10:43:22","Sagemcom =
CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004241534","Mim=
boman4","","03-02-2025 10:41:37","03-02-2025 10:26:00","03-02-2025 11:24:53=
","No power issue U=3D54V site on Grid. TX FME Leonel Steve// 655184876// /=
 from huawei is informed. Site up at 10:32 AM","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue U=3D54V site on Grid. TX FME Leonel Steve// 655184876// /=
 from huawei is informed. Site up at 10:32 AM","ervine.mbezele@sagemcom.com=
","938","03-02-2025 10:41:37","Sagemcom CMR"
"Closed Complete","Warning","CTR_205","IHS_YND_372","NOCINC0004241114","Bon=
djock","","03-02-2025 09:18:24","","","Grid outgae Site alarming because Ge=
n failed to start // Grid power return and alarm cleared","Fanda Brice","Wa=
rning","Warning","POWER","Warning - Site on Battery","Grid outgae Site alar=
ming because Gen failed to start // Grid power return and alarm cleared","w=
ilfried.kameni@sagemcom.com","4666","03-02-2025 09:18:24","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0004241006","MIM=
BOMAN LIBERTE","","03-02-2025 08:54:08","03-02-2025 08:49:58","03-02-2025 0=
9:39:34","Grid outage site went down because Gen failed to start due to Gen=
 battery faulty // Gen manually started with external battery","Mba Lazare =
Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","=
Grid outage site went down because Gen failed to start due to Gen battery f=
aulty // Gen manually started with external battery","ervine.mbezele@sagemc=
om.com","252","03-02-2025 08:54:08","Sagemcom CMR"
"Closed Complete","Warning","T0104","IHS_YND_113","NOCINC0004240975","Emomb=
o 2","","03-02-2025 08:47:38","","","Site alarming high temp because air co=
nditioning capacitor faulty // capacitor replaced","MINKA NICOLAS","Warning=
","Warning","ENVIRONMENT","Warning - Aircon Condenser Fan Motor Faulty","Si=
te alarming high temp because air conditioning capacitor faulty // capacito=
r replaced","ervine.mbezele@sagemcom.com","49921","03-02-2025 08:47:38","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004240948","Nko=
lbisson IITA LP","","03-02-2025 08:42:39","03-02-2025 08:13:23","03-02-2025=
 09:30:24","No power issue site on grid Ubaie=3D53,8V   Mohamadou 691144435=
 from HAUWEI is informed.","","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid Ubaie=
=3D53,8V   Mohamadou 691144435 from HAUWEI is informed.","ervine.mbezele@sa=
gemcom.com","4496","03-02-2025 08:42:39","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004240845","Com=
plex Beac II","","03-02-2025 08:07:02","03-02-2025 07:58:30","03-02-2025 09=
:14:24","Site on Grid ,Site went down because neutral phase  burned and Gen=
 fails to start due to no RCP //He replaced cable burned ,site on Grid ","A=
lbran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Site on Grid ,Site went down because neutral phase  burned and=
 Gen fails to start due to no RCP //He replaced cable burned ,site on Grid =
","ervine.mbezele@sagemcom.com","513","03-02-2025 08:07:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004240794","L=
abogenie","","03-02-2025 07:49:04","03-02-2025 07:35:42","03-02-2025 07:40:=
19","ACTIVE//No power issue U =3D54,5V site on Grid. The Tx FME Eloundou (6=
93212405 )from Huawei is informed. Notice that it is the repetitive issue	"=
,"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","ACTIVE//No power issue U =3D54,5V site on Grid. The Tx FME =
Eloundou (693212405 )from Huawei is informed. Notice that it is the repetit=
ive issue	","wilfried.kameni@sagemcom.com","803","03-02-2025 07:49:04","Sag=
emcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004240663","NYO=
M FACE MAETUR","","03-02-2025 07:26:14","03-02-2025 06:56:07","03-02-2025 0=
8:49:54","Site went down because Gen failed to start due to lack of 01 phas=
es and no RCP// He did a bridge with a good phase","Fabrice Pouakam","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site we=
nt down because Gen failed to start due to lack of 01 phases and no RCP// H=
e did a bridge with a good phase","wilfried.kameni@sagemcom.com","1808","03=
-02-2025 07:26:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004240394","S=
IMBOCK BONAMBAPE","","03-02-2025 06:45:08","02-02-2025 19:10:27","03-02-202=
5 07:14:37","Site went down due to inssufficiency of rectifier causing by 0=
2/08 rectifier faulty SS IHS Felix Zamb=E9 confirmed // Site","Hyemafo Gild=
as","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went =
down due to inssufficiency of rectifier causing by 02/08 rectifier faulty S=
S IHS Felix Zamb=E9 confirmed // Site","el-dalile@sagemcom.com","41682","03=
-02-2025 06:45:08","Sagemcom CMR"
"Cancelled","Warning","CTR_213","IHS_YND_247","NOCINC0004240235","Okolo",""=
,"03-02-2025 06:11:59","","","","Fabrice Pouakam","","","","","","danick.tc=
hakouani@sagemcom.com","16","03-02-2025 06:11:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004239996","N=
kolfon Cimencam","","03-02-2025 04:52:50","03-02-2025 03:33:19","03-02-2025=
 03:34:54","ACTIVE//No power issue site on Grid Ubaie =3D54.5 V, Noitice  s=
ite is impacted by Afanoya II who is not our responsability","Hyemafo Gilda=
s","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","ACTIVE//No power issue site on Grid Ubaie =3D54.5 V, Noitice=
  site is impacted by Afanoya II who is not our responsability","el-dalile@=
sagemcom.com","4772","03-02-2025 04:52:50","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004239729","AKA=
K Nkozoa","","03-02-2025 03:21:44","03-02-2025 03:10:57","03-02-2025 04:37:=
24","Site went down because CB (40A) of rectifers tripped// CB put back on =
(investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Circuit Breaker Issue","Site went down becaus=
e CB (40A) of rectifers tripped// CB put back on (investigation ongoing)","=
danick.tchakouani@sagemcom.com","648","03-02-2025 03:21:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004239532","B=
iteng-Maetur","","03-02-2025 01:58:34","02-02-2025 22:34:50","03-02-2025 08=
:20:38","No power issue, site is on grid with Ubaie=3D53V, Lionel Adjep(655=
184876) from Huawei is iformed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue, site is on grid with Ubaie=3D53V, Lionel Adjep(655184876) from Huawei i=
s iformed","el-dalile@sagemcom.com","12226","03-02-2025 01:58:34","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0004239421","Y=
de-M-Central","","03-02-2025 01:12:30","03-02-2025 00:55:49","03-02-2025 00=
:56:49","No power issue site on grid with U=3D52.3V Brice Tsague from Huawe=
i is informed ","","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D52.3V B=
rice Tsague from Huawei is informed ","el-dalile@sagemcom.com","1002","03-0=
2-2025 01:12:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0004239361","c=
hina embassy yde","","03-02-2025 00:49:21","03-02-2025 00:10:12","03-02-202=
5 08:20:11","Active//No power issue site on grid with U=3D52.4v site up at =
01:12 AM Eloundou Bertrand from Huawei is informed","","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue site on grid with U=3D52.4v site up at 01:12 AM Eloundou Ber=
trand from Huawei is informed","el-dalile@sagemcom.com","2350","03-02-2025 =
00:49:21","Sagemcom CMR"
"Closed Complete","Site Down","T0638","IHS_YND_318","NOCINC0004239319","SOA=
 University","","03-02-2025 00:33:09","03-02-2025 00:18:00","03-02-2025 01:=
14:06","Grid Outage  site went down because Gen Start and stopped with alar=
m high temps //He added water and Gen manually started","Siligap Boris","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Grid Outage  site went down because Gen Start and stopped with a=
larm high temps //He added water and Gen manually started","danick.tchakoua=
ni@sagemcom.com","910","03-02-2025 00:33:09","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004239126","Nsi=
meyong Terre Rouge","","03-02-2025 00:04:10","02-02-2025 23:47:36","03-02-2=
025 00:01:55","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen started automatically","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen started auto=
matically","danick.tchakouani@sagemcom.com","995","03-02-2025 00:04:10","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004238974","MEF=
OU ASSI","","02-02-2025 23:23:18","02-02-2025 23:19:33","02-02-2025 23:22:2=
0","Site went down du to insufficiency of rectifier, IHS SS FELIX ZAMBE is =
informed // site stabilized","Fanda Brice","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Site went down du to insufficiency of rectifie=
r, IHS SS FELIX ZAMBE is informed // site stabilized","danick.tchakouani@sa=
gemcom.com","227","02-02-2025 23:23:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004238799","L=
abogenie","","02-02-2025 22:58:06","02-02-2025 22:27:53","02-02-2025 22:30:=
54","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed. Notice that it is the repetitive issue=
 ","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx F=
ME  Eloundou (693212405 )from Huawei is informed. Notice that it is the rep=
etitive issue ","wilfried.kameni@sagemcom.com","1814","02-02-2025 22:58:06"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004238691","M=
ontee-Jouvence-II","","02-02-2025 22:35:24","02-02-2025 22:25:13","03-02-20=
25 00:26:14","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed//Site Stabilized","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Site went down due to PWC=
 Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed//Site Stabilized","da=
nick.tchakouani@sagemcom.com","612","02-02-2025 22:35:24","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004238668","ODZ=
A MINKAN EDIBI ASSI","","02-02-2025 22:29:43","02-02-2025 21:57:00","02-02-=
2025 23:39:57","Grid outage site went down because Gen failed  to start due=
 to grid contactor denergized//  He excited grid  contactor (investigation =
ongoing) ","Albran Byorel","Equipment Repair","Passive","Control Panel","AT=
S-AMF Issue","Grid outage site went down because Gen failed  to start due t=
o grid contactor denergized//  He excited grid  contactor (investigation on=
going) ","danick.tchakouani@sagemcom.com","1964","02-02-2025 22:29:43","Sag=
emcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004238618","Nko=
lo II New","","02-02-2025 22:18:09","02-02-2025 21:47:58","02-02-2025 21:49=
:24","Active//No power issue U=3D52.2 V site on Gen. TX FME Leonel Steve (6=
55184876) from huawei is informed ","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue U=3D52.2 V site on Gen. TX FME Leonel Steve (655184876) from=
 huawei is informed ","danick.tchakouani@sagemcom.com","1813","02-02-2025 2=
2:18:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004238402","N=
koabang2","","02-02-2025 21:43:36","02-02-2025 21:35:24","02-02-2025 22:58:=
52","Site went down because Gen failed to start due to Grid bad voltage and=
 No RCP on site // He bypass the Grid and Gen manually started","Mba Lazare=
 Herve","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Site went down because Gen failed to start due to Grid bad voltage and No =
RCP on site // He bypass the Grid and Gen manually started","wilfried.kamen=
i@sagemcom.com","493","02-02-2025 21:43:36","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004238147","Elo=
umdem stade","","02-02-2025 21:06:38","02-02-2025 20:13:27","03-02-2025 00:=
44:16","Site went down du to insufficiency of rectifier, IHS SS FELIX ZAMBE=
 is informed // Site stabilized","Fanda Brice","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module","Site went down du to insufficiency of rect=
ifier, IHS SS FELIX ZAMBE is informed // Site stabilized","danick.tchakouan=
i@sagemcom.com","3192","02-02-2025 21:06:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004237914","SOA VILL=
AGE","","02-02-2025 20:44:40","02-02-2025 20:21:25","02-02-2025 21:09:25","=
Cascaded Incident from TTO4257402","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause Gen fails to start  due to Grid bad voltage  // HE bypassed Grid and =
Gen manually started","system","1229076","02-02-2025 20:44:40","Sagemcom CM=
R"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004237904","SOA=
 TOWN","IHS_YND_323","02-02-2025 20:43:33","02-02-2025 20:21:25","02-02-202=
5 21:09:25","Grid fluctuation, site went down because Gen fails to start  d=
ue to Grid bad voltage  // HE bypassed Grid and Gen manually started","Sili=
gap Boris","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","Grid fluctuation, site went down because Gen fails to start  due =
to Grid bad voltage  // HE bypassed Grid and Gen manually started","danick.=
tchakouani@sagemcom.com","1329","02-02-2025 20:43:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004237847","B=
iteng-Maetur","","02-02-2025 20:30:54","02-02-2025 20:07:35","02-02-2025 22=
:16:20","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed.// He reduiced l=
oad and started Gen manualy","Mba Lazare Herve","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage, Site went down because Gen sta=
rted and stopped due to Gen overload(20kva, 280A) SS IHS Alphonse DEFFO con=
firmed.// He reduiced load and started Gen manualy","wilfried.kameni@sagemc=
om.com","1400","02-02-2025 20:30:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004237714","N=
yom OCM","","02-02-2025 20:10:08","02-02-2025 19:59:12","02-02-2025 19:59:3=
2","Grid fluctuation, site went down because Gen failed to start due to gri=
d bad voltage no Rcp // He bypass grid and started Gen manually","Fabrice P=
ouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, site went down because Gen failed to start due to =
grid bad voltage no Rcp // He bypass grid and started Gen manually","wilfri=
ed.kameni@sagemcom.com","657","02-02-2025 20:10:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004237628","Eto koss=
 Yde","","02-02-2025 19:53:10","02-02-2025 16:32:12","02-02-2025 17:03:12",=
"Cascaded Incident from TTO4257066","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Site went down due to insufficiency of =
rectifier 02 SS IHS Felix Zambe is informed and confirmed // site stabilize=
d","system","271745","02-02-2025 19:53:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004237629","ELOUMDEM=
 CARRIERE 2","","02-02-2025 19:53:10","02-02-2025 16:32:12","02-02-2025 17:=
03:12","Cascaded Incident from TTO4257066","Fanda Brice","Cascade Outage","=
Active","Cascade Active","Cascade Active","Site went down due to insufficie=
ncy of rectifier 02 SS IHS Felix Zambe is informed and confirmed // site st=
abilized","system","271744","02-02-2025 19:53:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004237427","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768, IHS_YND_696","02-02-2025 19:19:22","0=
2-02-2025 16:32:12","02-02-2025 17:03:12","Site went down due to insufficie=
ncy of rectifier 02 SS IHS Felix Zambe is informed and confirmed // site st=
abilized","Fanda Brice","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Site went down due to insufficiency of =
rectifier 02 SS IHS Felix Zambe is informed and confirmed // site stabilize=
d","danick.tchakouani@sagemcom.com","10032","02-02-2025 19:19:22","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0004237305","N=
guila","","02-02-2025 19:03:17","02-02-2025 18:28:31","02-02-2025 19:00:34"=
,"Grid Outage, site went down because Gen start and stopped with ""high tem=
p"" alarm // He oppened the doors and manually start the gen","Parker Tchou=
p","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid Outage, si=
te went down because Gen start and stopped with ""high temp"" alarm // He o=
ppened the doors and manually start the gen","wilfried.kameni@sagemcom.com"=
,"2867","02-02-2025 19:03:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004237122","A=
wae Ewonkan","","02-02-2025 18:23:11","02-02-2025 17:41:46","02-02-2025 20:=
23:30","Site went down due to insufficiency rectifiers IHS SS Alphonse is i=
nformed and is confirmed // Site stabilized","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module","Site went down due to insuff=
iciency rectifiers IHS SS Alphonse is informed and is confirmed // Site sta=
bilized","wilfried.kameni@sagemcom.com","2486","02-02-2025 18:23:11","Sagem=
com CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004237020","Eko=
unou","","02-02-2025 17:52:17","02-02-2025 16:39:31","03-02-2025 11:02:37",=
"ENEO surge, Site went down due to  overload (24KW, 390A) SS IHS Pascaline =
Manda confirmed// grid stabilized","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","ENEO surge, Site went down due to  overl=
oad (24KW, 390A) SS IHS Pascaline Manda confirmed// grid stabilized","danic=
k.tchakouani@sagemcom.com","26080","02-02-2025 17:52:17","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004236987","Elo=
umdem stade","","02-02-2025 17:45:45","02-02-2025 17:01:27","02-02-2025 18:=
41:27","Site went down du to insufficiency of rectifier, IHS SS FELIX ZAMBE=
 is informed // he reduced the load : site on gen","Fanda Brice","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","Site went down du to ins=
ufficiency of rectifier, IHS SS FELIX ZAMBE is informed // he reduced  the =
load : site on gen","danick.tchakouani@sagemcom.com","2659","02-02-2025 17:=
45:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004236675","M=
ontee-Des-Soeurs","","02-02-2025 16:57:02","02-02-2025 16:36:41","02-02-202=
5 20:55:42","No power Issue Site on Grid Ubai =3D54.3 V, The FME The TX FME=
 Mbah Hosiah (674007438) is informed.","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r Issue Site on Grid Ubai =3D54.3 V, The FME The TX FME Mbah Hosiah (674007=
438) is informed.","wilfried.kameni@sagemcom.com","1222","02-02-2025 16:57:=
02","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004236670","Mim=
boman4","","02-02-2025 16:54:43","02-02-2025 16:46:26","02-02-2025 16:46:27=
","No power issue site on grid with U=3D54v//site  Eloundou from Huawei is =
informed","Mba Lazare Herve","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54v//site  Eloundou from Huawei is informed","danick.tchakouani@sagemcom=
.com","498","02-02-2025 16:54:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004236597","B=
arriere IHS","","02-02-2025 16:35:54","02-02-2025 16:32:12","02-02-2025 17:=
03:12","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","Casc=
ade Active","Site went down due to insufficiency of rectifier 02 SS IHS Fel=
ix Zambe is informed and confirmed // site stabilized","wilfried.kameni@sag=
emcom.com","271744","02-02-2025 16:35:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004236419","C=
rf-Nsam","","02-02-2025 16:04:06","02-02-2025 15:57:14","02-02-2025 16:03:1=
4","Site went down Because The Slot off Rectifier is overload //site stabil=
ized SS Ihs Pascaline is informed and is confirmed","MINKA NICOLAS","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went =
down Because The Slot off Rectifier is overload //site stabilized SS Ihs Pa=
scaline is informed and is confirmed","wilfried.kameni@sagemcom.com","413",=
"02-02-2025 16:04:06","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004236343","Nko=
ulou Carriere carrefourt","","02-02-2025 15:51:29","02-02-2025 15:45:21","0=
2-02-2025 18:11:21","Site went down because the CB (63A) tripped in the PWC=
 // He reamed the CB (63A)","Mba Lazare Herve","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down be=
cause the CB (63A) tripped in the PWC // He reamed the CB (63A)","danick.tc=
hakouani@sagemcom.com","368","02-02-2025 15:51:29","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004236195","SIM=
BOCK BONAMBAPE","","02-02-2025 15:28:32","02-02-2025 14:17:17","02-02-2025 =
14:22:50","Site went down due to inssufficiency of rectifier causing by 02/=
08 rectifier faulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","Hye=
mafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","S=
ite went down due to inssufficiency of rectifier causing by 02/08 rectifier=
 faulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","danick.tchakoua=
ni@sagemcom.com","4275","02-02-2025 15:28:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004236002","MEHANDAN=
","","02-02-2025 14:53:10","02-02-2025 14:11:15","02-02-2025 19:35:15","Cas=
caded Incident from TTO4255117","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to gen=
 overload (20kva, 260A) SS IHS Pascaline Manda is informed and confirmed//W=
e reduce load and gen manually started ","system","301860","02-02-2025 14:5=
3:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004235993","O=
dza II OCM","IHS_YND_528","02-02-2025 14:51:19","02-02-2025 14:11:15","02-0=
2-2025 19:35:15","Grid outage, site went down due to gen overload (20kva, 2=
60A) SS IHS Pascaline Manda is informed and confirmed//We reduce load and g=
en manually started ","Albran Byorel","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","Grid outage, site went down due to gen overload (20kv=
a, 260A) SS IHS Pascaline Manda is informed and confirmed//We reduce load a=
nd gen manually started ","wilfried.kameni@sagemcom.com","2405","02-02-2025=
 14:51:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004235974","C=
RH-Etoug-Ebe","","02-02-2025 14:46:10","02-02-2025 14:16:45","02-02-2025 14=
:16:46","No power issue on site U=3D53 V site on Grid , The Tx RM Alain/691=
144423/ from Huawei is informed. Notice that we have disjunction at BTS OCM=
 (repetitive isssues)","Hyemafo Gildas","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D53 V site on Grid , The Tx RM Alain/691144423/ from Huawei is informed.=
 Notice that we have disjunction at BTS OCM (repetitive isssues)","wilfried=
.kameni@sagemcom.com","1766","02-02-2025 14:46:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004235696","ELOUMDEM=
 CARRIERE 2","","02-02-2025 14:02:21","02-02-2025 13:53:26","02-02-2025 14:=
20:26","Cascaded Incident from TTO4254729","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to insuffi=
ciency of rectifier 02 SS IHS Felix Zambe is informed and confirmed // site=
 stabilized","system","281502","02-02-2025 14:02:21","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004235668","MEF=
OU ASSI","IHS_YND_768","02-02-2025 13:57:04","02-02-2025 13:53:26","02-02-2=
025 14:20:26","Site went down due to insufficiency of rectifier 02 SS IHS F=
elix Zambe is informed and confirmed // site stabilized","Fanda Brice","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module","Site went down due=
 to insufficiency of rectifier 02 SS IHS Felix Zambe is informed and confir=
med // site stabilized","ervine.mbezele@sagemcom.com","220","02-02-2025 13:=
57:04","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004235605","Mes=
sa Carriere","","02-02-2025 13:49:24","02-02-2025 13:38:13","02-02-2025 16:=
32:13","Site went down because 01/03 rectifier faulty SS IHS Fran=E7ois is =
informed and confirmed // Site stabilized","Mboua Thierry","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Site went down because 01/03 r=
ectifier faulty SS IHS Fran=E7ois is informed and confirmed // Site stabili=
zed","wilfried.kameni@sagemcom.com","672","02-02-2025 13:49:24","Sagemcom C=
MR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0004235566","Av-=
Germaine","","02-02-2025 13:39:35","02-02-2025 13:28:05","02-02-2025 13:36:=
06","ACTIVE No power issue on site, site on Grid with Ubaie=3D53.4 V  THE T=
x fme Armand Nguetsa /699949553/ from Huawei is informed","","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","AC=
TIVE No power issue on site, site on Grid with Ubaie=3D53.4 V  THE Tx fme A=
rmand Nguetsa /699949553/ from Huawei is informed","ervine.mbezele@sagemcom=
.com","691","02-02-2025 13:39:35","Sagemcom CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004235553","Emo=
mbo Esssomba","","02-02-2025 13:35:02","02-02-2025 13:27:26","02-02-2025 13=
:36:58","No power issue site on Grid and UBAIE=3D54 V  The TX FME Leonel //=
694693436// from Huawei  is informed.Site up at 01:36 PM","Mba Lazare Herve=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue site on Grid and UBAIE=3D54 V  The TX FME Leon=
el //694693436// from Huawei  is informed.Site up at 01:36 PM","ervine.mbez=
ele@sagemcom.com","457","02-02-2025 13:35:02","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004235510","Eko=
unou","","02-02-2025 13:21:26","02-02-2025 13:09:40","02-02-2025 15:47:10",=
"Grid outage, site went down because gen fails to start due to gen overload=
 (20KVA, 310A) SS HIS PASCALINE Confirmed// Grid return","Albran Byorel","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site =
went down because gen fails to start due to gen overload (20KVA, 310A) SS H=
IS PASCALINE Confirmed// Grid return","wilfried.kameni@sagemcom.com","789",=
"02-02-2025 13:21:26","Sagemcom CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0004235414","NYO=
M","","02-02-2025 13:00:13","02-02-2025 12:57:41","02-02-2025 13:19:43","fm=
e is on the way to site ETA=3D01:50 pm","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gri=
d outage, Site went down because gen start and stopped with high temp alarm=
 // he added water and manually start the gen","ervine.mbezele@sagemcom.com=
","153","02-02-2025 13:00:13","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004235155","SIM=
BOCK BONAMBAPE","","02-02-2025 12:04:12","02-02-2025 12:01:04","02-02-2025 =
13:05:07","Site went down due to insufficiency of rectifier causing by  01/=
08 rectifier faulty SS IHS Felix Zamb=E9 confirmed// Site stabilized","Hyem=
afo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to insufficiency of rectifier causing by  01/08 rectifier =
faulty SS IHS Felix Zamb=E9 confirmed// Site stabilized","wilfried.kameni@s=
agemcom.com","189","02-02-2025 12:04:12","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004235137","EMA=
NA BILICK CITY","","02-02-2025 11:59:41","02-02-2025 11:21:10","02-02-2025 =
11:59:40","No power issue on site Ubaie =3D53.4V site on Grid The TX FME Sy=
nphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site Ubaie =3D53.4V site on Grid The TX FME Synphorien (=
650257151) from Huawei is informed","ervine.mbezele@sagemcom.com","2312","0=
2-02-2025 11:59:41","Sagemcom CMR"
"Closed Complete","Warning","T0055","IHS_YND_328","NOCINC0004235057","Nsima=
len MTN","","02-02-2025 11:44:04","","","Site alarming because site on batt=
ery due due Grid outage and Gen fails to start causing by Gen CB(32 A)  dis=
junted// He reamed CB","Albran Byorel","Warning","Warning","POWER","Warning=
 - Site on Battery","Site alarming because site on battery due due Grid out=
age and Gen fails to start causing by Gen CB(32 A)  disjunted// He reamed C=
B","ervine.mbezele@sagemcom.com","3322","02-02-2025 11:44:04","Sagemcom CMR=
"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004234983","SIM=
BOCK BONAMBAPE","","02-02-2025 11:32:27","02-02-2025 11:28:05","02-02-2025 =
11:32:42","	Site went down due to insufficiency of rectifier causing by 01/=
08 rctifier faulty SS IHS Felix Zamb=E9 confirmed // Site Stabilized	","Hye=
mafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","	=
Site went down due to insufficiency of rectifier causing by 01/08 rctifier =
faulty SS IHS Felix Zamb=E9 confirmed // Site Stabilized	","ervine.mbezele@=
sagemcom.com","263","02-02-2025 11:32:27","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004234896","Eto=
 koss Yde","","02-02-2025 11:02:49","01-02-2025 21:01:06","01-02-2025 21:01=
:18","ACTIVE//No power issue site on Grid Ubaie =3D53.4 V, The tx Huawei  F=
ulbert  (654266068) is informed","Fanda Brice","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power=
 issue site on Grid Ubaie =3D53.4 V, The tx Huawei  Fulbert  (654266068) is=
 informed","wilfried.kameni@sagemcom.com","50503","02-02-2025 11:02:49","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004234887","MEHANDAN=
","","02-02-2025 11:00:00","02-02-2025 10:55:11","02-02-2025 13:35:17","Cas=
caded Incident from TTO4253787","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down because Ge=
n card disfunctionning causing by short circuit// He started Gen manualy","=
system","277714","02-02-2025 11:00:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004234881","O=
dza II OCM","IHS_YND_528","02-02-2025 10:58:38","02-02-2025 10:55:11","02-0=
2-2025 13:35:17","Grid outage, Site went down because Gen card disfunctionn=
ing causing by short circuit// He started Gen manualy","Albran Byorel","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Si=
te went down because Gen card disfunctionning causing by short circuit// He=
 started Gen manualy","wilfried.kameni@sagemcom.com","208","02-02-2025 10:5=
8:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004234745","N=
kolo II New","","02-02-2025 10:29:53","02-02-2025 10:22:28","02-02-2025 11:=
30:33","Active//No power issue, U=3D50,7 on Gen, Tx FME lionel steve adjep/=
655124876/ From huawei is informed. Notice that we have disjunction at BTS =
OCM","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active//No power issue, U=3D50,7 on Gen=
, Tx FME lionel steve adjep/655124876/ From huawei is informed. Notice that=
 we have disjunction at BTS OCM","wilfried.kameni@sagemcom.com","447","02-0=
2-2025 10:29:53","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004234460","Mes=
sa Carriere","","02-02-2025 09:25:07","02-02-2025 09:11:35","02-02-2025 12:=
08:18","Site went down because 01/03 rectifier faulty SS IHS Fran=E7ois is =
informed and confirmed// Site stabilized","Mboua Thierry","Equipment Repair=
","Passive","Rectifier","Rectifier Module","Site went down because 01/03 re=
ctifier faulty SS IHS Fran=E7ois is informed and confirmed// Site stabilize=
d","wilfried.kameni@sagemcom.com","813","02-02-2025 09:25:07","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0004234137","E=
lobi Mokolo","","02-02-2025 08:29:33","02-02-2025 08:22:16","02-02-2025 09:=
47:15","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage no Rcp // He bypass grid and started Gen manually","Mboua=
 Thierry","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation, site went down because Gen failed to start due t=
o grid bad voltage no Rcp // He bypass grid and started Gen manually","wilf=
ried.kameni@sagemcom.com","457","02-02-2025 08:29:33","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004234106","Mim=
boman4","","02-02-2025 08:24:58","02-02-2025 08:15:45","02-02-2025 09:38:40=
","No power issue U=3D54V site on Gen. TX FME Leonel Steve// 655184876// / =
from huawei is informed. ","Mba Lazare Herve","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=
=3D54V site on Gen. TX FME Leonel Steve// 655184876// / from huawei is info=
rmed. ","ervine.mbezele@sagemcom.com","554","02-02-2025 08:24:58","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004234012","Obo=
bogo","","02-02-2025 07:51:00","02-02-2025 07:41:52","02-02-2025 07:46:34",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
ted automatically","MINKA NICOLAS","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen started automatically","wilfried.kameni@sage=
mcom.com","867","02-02-2025 07:51:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004233635","L=
abogenie","","02-02-2025 06:41:37","02-02-2025 06:37:23","02-02-2025 06:40:=
42","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed. Notice that it is the repetitive issue=
 ","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx F=
ME  Eloundou (693212405 )from Huawei is informed. Notice that it is the rep=
etitive issue ","wilfried.kameni@sagemcom.com","255","02-02-2025 06:41:37",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004233551","NKO=
LOSSAN OKOK","","02-02-2025 06:28:32","02-02-2025 06:09:10","02-02-2025 07:=
06:42","Grid fluctuation, site went down because Gen failed to start due to=
 grid bad voltage no Rcp // he bypass grid and manually start the gen","Par=
ker Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation, site went down because Gen failed to start due=
 to grid bad voltage no Rcp // he bypass grid and manually start the gen","=
wilfried.kameni@sagemcom.com","1163","02-02-2025 06:28:32","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004233426","SAA=
 Entrance","","02-02-2025 05:59:31","02-02-2025 05:55:17","02-02-2025 06:10=
:59","Grid outage,gen ran until fuel shortage//Refueling done","Parker Tcho=
up","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran u=
ntil fuel shortage//Refueling done","wilfried.kameni@sagemcom.com","255","0=
2-02-2025 05:59:31","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004233319","Mes=
sa Carriere","","02-02-2025 05:16:01","02-02-2025 05:02:50","02-02-2025 07:=
39:57","Site went down because 01/03 rectifier faulty SS IHS Fran=E7ois is =
informed and is confirmed // site stabilized ","Mboua Thierry","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down because 01/=
03 rectifier faulty SS IHS Fran=E7ois is informed and is confirmed // site =
stabilized ","wilfried.kameni@sagemcom.com","792","02-02-2025 05:16:01","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004233082","N=
kolfon Cimencam","","02-02-2025 03:31:59","02-02-2025 03:15:38","02-02-2025=
 03:20:06","ACTIVE//No power issue site on Grid Ubaie =3D54.5 V, The tx Hua=
wei  Fulbert  (654266068) is informed ,Noitice  site is impacted by Afanoya=
 II who is not our responsability","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No =
power issue site on Grid Ubaie =3D54.5 V, The tx Huawei  Fulbert  (65426606=
8) is informed ,Noitice  site is impacted by Afanoya II who is not our resp=
onsability","wilfried.kameni@sagemcom.com","982","02-02-2025 03:31:59","Sag=
emcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004233000","Mes=
sa Carriere","","02-02-2025 03:03:51","02-02-2025 02:46:32","02-02-2025 03:=
56:59","Site went down because 01/03 rectifier faulty // site stabilized SS=
 IHS Fran=E7ois is informed and is confirmed","Mboua Thierry","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down because 01/0=
3 rectifier faulty // site stabilized SS IHS Fran=E7ois is informed and is =
confirmed","wilfried.kameni@sagemcom.com","1039","02-02-2025 03:03:51","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004232946","L=
abogenie","","02-02-2025 02:47:25","02-02-2025 02:35:03","02-02-2025 02:40:=
34","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed. Notice that it is the repetitive issue=
 ","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx F=
ME  Eloundou (693212405 )from Huawei is informed. Notice that it is the rep=
etitive issue ","wilfried.kameni@sagemcom.com","744","02-02-2025 02:47:25",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004232929","Mes=
sa Carriere","","02-02-2025 02:34:55","02-02-2025 01:55:34","02-02-2025 02:=
07:33","Site went down because 01/03 rectifier faulty // site stabilized SS=
 IHS Fran=E7ois is informed and is confirmed/","Mboua Thierry","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down because 01/=
03 rectifier faulty // site stabilized SS IHS Fran=E7ois is informed and is=
 confirmed/","wilfried.kameni@sagemcom.com","2362","02-02-2025 02:34:55","S=
agemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004232595","NKO=
LOSSAN OKOK","","02-02-2025 00:14:44","01-02-2025 23:33:02","02-02-2025 00:=
16:02","No power issue site on grid with U=3D54v  Gregoire from Huawei is i=
nformed","Parker Tchoup","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D5=
4v  Gregoire from Huawei is informed","wilfried.kameni@sagemcom.com","2502"=
,"02-02-2025 00:14:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004232083","SOA VILL=
AGE","","01-02-2025 22:29:21","01-02-2025 21:49:01","01-02-2025 22:30:01","=
Cascaded Incident from TTO4250283","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 Gen started and stopped with alarm ""high temp"" // He added water and Gen=
 started","system","2420","01-02-2025 22:29:21","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004231884","SOA=
 TOWN","IHS_YND_323","01-02-2025 22:08:50","01-02-2025 21:16:01","01-02-202=
5 22:30:01","Grid outage, Site went down because Gen started and stopped wi=
th alarm ""high temp"" // He added water and Gen started","Siligap Boris","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, Site went down because Gen started and stopped wi=
th alarm ""high temp"" // He added water and Gen started","wilfried.kameni@=
sagemcom.com","3197","01-02-2025 22:08:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004231783","M=
essa-Carriere OCM","","01-02-2025 21:57:00","01-02-2025 21:37:40","01-02-20=
25 23:41:01","Site went down because CB 125A faulty in DC-Box due to sectio=
n cable burned// he bypassed the Cb and did a bridge(remplacement ongoing)"=
,"","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit B=
reaker Issue","Site went down because CB 125A faulty in DC-Box due to secti=
on cable burned// he bypassed the Cb and did a bridge(remplacement ongoing)=
","wilfried.kameni@sagemcom.com","1162","01-02-2025 21:57:00","Sagemcom CMR=
"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004231750","Ngo=
a Ekelle","","01-02-2025 21:47:23","01-02-2025 20:56:00","01-02-2025 21:06:=
35","Site went down due to insufficiency rectifiers","Paul BIBOUM","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","Site went down due to =
insufficiency rectifiers","wilfried.kameni@sagemcom.com","3084","01-02-2025=
 21:47:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004231647","L=
abogenie","","01-02-2025 21:35:41","01-02-2025 19:39:34","01-02-2025 19:40:=
58","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed. Notice that it is the repetitive issue=
 ","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx F=
ME  Eloundou (693212405 )from Huawei is informed. Notice that it is the rep=
etitive issue site up at 07:21 AM","wilfried.kameni@sagemcom.com","6968","0=
1-02-2025 21:35:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004231625","M=
ontee-Jouvence-II","","01-02-2025 21:32:58","01-02-2025 21:22:15","01-02-20=
25 21:27:18","ACTIVE// No  power issue on site, site on Grid with Ubaie=3D =
54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed.","Hyema=
fo Gildas","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","ACTIVE// No  power issue on site, site on Grid with =
Ubaie=3D 54V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed=
.","wilfried.kameni@sagemcom.com","644","01-02-2025 21:32:58","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004231606","C=
rf-Nsam","","01-02-2025 21:29:52","01-02-2025 20:39:36","01-02-2025 20:57:0=
9","Site went down Because The Slot off Rectifier is overload //site stabil=
ized SS Ihs Pascaline is informed and is confirmed","MINKA NICOLAS","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went =
down Because The Slot off Rectifier is overload //site stabilized SS Ihs Pa=
scaline is informed and is confirmed","wilfried.kameni@sagemcom.com","3017"=
,"01-02-2025 21:29:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004231515","M=
essassi okolo","","01-02-2025 21:11:01","01-02-2025 20:39:43","01-02-2025 2=
0:49:43","No powerr issue site on grid with U=3D54,5v Tx fme synphorien of =
huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No powerr issue site on g=
rid with U=3D54,5v Tx fme synphorien of huawei is informed","wilfried.kamen=
i@sagemcom.com","1880","01-02-2025 21:11:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004231484","ELOUMDEM=
 CARRIERE 2","","01-02-2025 21:05:50","01-02-2025 21:01:19","01-02-2025 22:=
51:12","Cascaded Incident from TTO4249831","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid bad voltage;and gen fail=
ed to start//bypassed grid and started the gen","system","284453","01-02-20=
25 21:05:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004231483","Eto koss=
 Yde","","01-02-2025 21:05:50","01-02-2025 21:01:19","01-02-2025 22:51:12",=
"Cascaded Incident from TTO4249831","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid bad voltage;and gen failed to s=
tart//bypassed grid and started the gen","system","284453","01-02-2025 21:0=
5:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004231479","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","01-02-2025 21:04:33","01-02-2025 21:01=
:19","01-02-2025 22:51:12","Grid bad voltage;and gen failed to start//bypas=
sed grid and started the gen","Fanda Brice","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid bad voltage;and gen failed =
to start//bypassed grid and started the gen","wilfried.kameni@sagemcom.com"=
,"195","01-02-2025 21:04:33","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004231367","Eko=
unou","","01-02-2025 20:42:52","01-02-2025 20:09:36","02-02-2025 13:07:06",=
"Grid outage, site went down because gen fails to start due to gen overload=
 (20KVA, 310A) SS HIS PASCALINE Confirmed// Grid return","Albran Byorel","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site =
went down because gen fails to start due to gen overload (20KVA, 310A) SS H=
IS PASCALINE Confirmed// Grid return","wilfried.kameni@sagemcom.com","1997"=
,"01-02-2025 20:42:52","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004231327","Nko=
lbisson usines des eaux 2","","01-02-2025 20:35:00","01-02-2025 20:05:53","=
01-02-2025 20:10:22","Active// No power issue, Site on Grid Ubai 53.2V Tech=
nicians working on site (Swap radio)","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active// No power issue, Site on Grid Ubai 53.2V Technicians working on s=
ite (Swap radio)","wilfried.kameni@sagemcom.com","1748","01-02-2025 20:35:0=
0","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004231177","Mes=
sa Carriere","","01-02-2025 20:18:31","01-02-2025 20:11:19","01-02-2025 22:=
17:39","	Site went down because 01/03 rectifier faulty // site stabilized S=
S IHS Fran=E7ois is informed and is confirmed","Mboua Thierry","Equipment R=
epair","Passive","Rectifier","Rectifier Module","	Site went down because 01=
/03 rectifier faulty // site stabilized SS IHS Fran=E7ois is informed and i=
s confirmed","wilfried.kameni@sagemcom.com","433","01-02-2025 20:18:31","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004231136","M=
essa-Carriere OCM","","01-02-2025 20:09:17","01-02-2025 19:32:49","01-02-20=
25 21:22:12","Site went down bacause the Cb(125A) of PWC burn // He bypass =
the Cb (replaced ongoing)","","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Circuit Breaker Issue","Site went down bacause the Cb(125A=
) of PWC burn // He bypass the Cb (replaced ongoing)","wilfried.kameni@sage=
mcom.com","2189","01-02-2025 20:09:17","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004231032","Nko=
ulou Carriere carrefourt","","01-02-2025 19:52:46","01-02-2025 19:39:00","0=
2-02-2025 07:51:12","Acces issue during the night, Site went down because C=
B(63A) tripped in DC BOX due to load increase// CB put back on ","Mba Lazar=
e Herve","Access Denial","Lease Or Legal","Landlord Related Issues","Access=
 Issue - Land Lord","Acces issue during the night, Site went down because C=
B(63A) tripped in DC BOX due to load increase// CB put back on ","wilfried.=
kameni@sagemcom.com","827","01-02-2025 19:52:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004231023","A=
wae Ewonkan","","01-02-2025 19:46:48","01-02-2025 18:47:21","01-02-2025 20:=
18:01","	Site went down due to insufficiency rectifiers IHS SS Alphonse is =
informed and is confirmed // Site stabilized","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","	Site went down due to insu=
fficiency rectifiers IHS SS Alphonse is informed and is confirmed // Site s=
tabilized","wilfried.kameni@sagemcom.com","3568","01-02-2025 19:46:48","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0004230979","T=
amtam Weekend","","01-02-2025 19:34:56","01-02-2025 19:22:25","01-02-2025 1=
9:42:25","No power issue on site U=3D56,7v site on grid  Tx fme Hosiah of h=
uawei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D=
56,7v site on grid  Tx fme Hosiah of huawei is informed","wilfried.kameni@s=
agemcom.com","751","01-02-2025 19:34:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004230968","SOA VILL=
AGE","","01-02-2025 19:32:40","01-02-2025 19:14:23","01-02-2025 20:05:51","=
Cascaded Incident from TTO4249210","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,Gen start and stopped d=
ue to ""high temp"" alarm//We add water and Gen manually started","system",=
"1225882","01-02-2025 19:32:40","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004230932","SOA=
 TOWN","IHS_YND_323","01-02-2025 19:29:45","01-02-2025 19:13:23","01-02-202=
5 20:05:51","Grid outage,Gen start and stopped due to ""high temp"" alarm//=
We add water and Gen manually started","Siligap Boris","Equipment Repair","=
Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid o=
utage,Gen start and stopped due to ""high temp"" alarm//We add water and Ge=
n manually started","wilfried.kameni@sagemcom.com","6131","01-02-2025 19:29=
:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004230909","S=
OA TOWN","","01-02-2025 19:23:18","01-02-2025 15:25:38","01-02-2025 16:26:3=
9","Grid outage, Site went down because Gen failed to start due to PWC ZTE =
disfunction// He reset it, Site on Grid","Siligap Boris","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","Grid outage, Site wen=
t down because Gen failed to start due to PWC ZTE disfunction// He reset it=
, Site on Grid","wilfried.kameni@sagemcom.com","14261","01-02-2025 19:23:18=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004230256","Ngoulmek=
ong-Nord","","01-02-2025 17:07:40","01-02-2025 15:19:37","01-02-2025 15:25:=
34","Cascaded Incident from TTO4248373","Siligap Boris","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","no power issue on site   U=3D48.3=
V site on Grid THE TX  FME SYMPHORIEN (650257151)    from HUAWEI is informe=
d. Notice that we have disjunction in OCM equipment","system","283344","01-=
02-2025 17:07:40","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004230247","Eko=
unou","","01-02-2025 17:06:34","01-02-2025 16:25:14","01-02-2025 19:19:04",=
"site went down because gen fails to start due to gen overload SS HIS PASCA=
LINE Confirmed // Site stabilized","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","site went down because gen fails to star=
t due to gen overload SS HIS PASCALINE Confirmed // Site stabilized","wilfr=
ied.kameni@sagemcom.com","2481","01-02-2025 17:06:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004230246","E=
leveur","IHS_YND_277","01-02-2025 17:06:32","01-02-2025 15:19:37","01-02-20=
25 15:25:34","no power issue on site   U=3D48.3V site on Grid THE TX  FME S=
YMPHORIEN (650257151)    from HUAWEI is informed. Notice that we have disju=
nction in OCM equipment","Siligap Boris","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","no power issue on site=
   U=3D48.3V site on Grid THE TX  FME SYMPHORIEN (650257151)    from HUAWEI=
 is informed. Notice that we have disjunction in OCM equipment","wilfried.k=
ameni@sagemcom.com","6416","01-02-2025 17:06:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004230223","SAA 2","=
","01-02-2025 17:02:10","01-02-2025 16:26:55","01-02-2025 17:15:37","Cascad=
ed Incident from TTO4248339","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grrid outage,Gen start and stopped due to=
 ""high temp"" alarm//We add water and gen manually started ","system","279=
202","01-02-2025 17:02:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004230216","S=
aa","IHS_YND_726, IHS_YND_404","01-02-2025 17:01:12","01-02-2025 16:26:55",=
"01-02-2025 17:15:37","Grrid outage,Gen start and stopped due to ""high tem=
p"" alarm//We add water and gen manually started ","Parker Tchoup","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Is=
sue","Grrid outage,Gen start and stopped due to ""high temp"" alarm//We add=
 water and gen manually started ","wilfried.kameni@sagemcom.com","2058","01=
-02-2025 17:01:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004230175","C=
rf-Nsam","","01-02-2025 16:54:15","01-02-2025 16:07:02","01-02-2025 16:58:5=
9","Site went down Because The Slot off Rectifier is overload //site stabil=
ized SS Ihs Pascaline is informed and is confirmed","MINKA NICOLAS","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went =
down Because The Slot off Rectifier is overload //site stabilized SS Ihs Pa=
scaline is informed and is confirmed","wilfried.kameni@sagemcom.com","2834"=
,"01-02-2025 16:54:15","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004230174","Ngu=
ila","","01-02-2025 16:54:15","01-02-2025 16:38:50","01-02-2025 16:51:13","=
Site went down because gen stopped with alarm high temp//he open all the do=
or and started the gen","Parker Tchoup","Equipment Repair","Passive","ACDG =
Gen","ACDG - High Engine Temp - Coolant Level Issue","Site went down becaus=
e gen stopped with alarm high temp//he open all the door and started the ge=
n","wilfried.kameni@sagemcom.com","926","01-02-2025 16:54:15","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004230160","Carrefou=
r Ayissi Ele","","01-02-2025 16:52:50","01-02-2025 15:37:11","01-02-2025 15=
:45:13","Cascaded Incident from TTO4248249","Parker Tchoup","Cascade Outage=
","Active","Cascade Active","Cascade Active","Active//No power issue on sit=
e Ubaie=3D50V site on Solar site impacted by SA=92A ocm Tx FME Gregoire /65=
4547479/Huawei  is informed and confirmed","system","282366","01-02-2025 16=
:52:50","Sagemcom CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004230143","Nko=
l-Mebanga","IHS_YND_810","01-02-2025 16:50:38","01-02-2025 15:37:11","01-02=
-2025 15:45:13","Active//No power issue on site Ubaie=3D50V site on Solar s=
ite impacted by SA=92A ocm  Tx FME Gregoire /654547479/Huawei  is informed =
and confirmed","Parker Tchoup","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site U=
baie=3D50V site on Solar site impacted by SA=92A ocm Tx FME Gregoire /65454=
7479/Huawei  is informed and confirmed","wilfried.kameni@sagemcom.com","440=
8","01-02-2025 16:50:38","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004229567","Nko=
zoa","","01-02-2025 15:13:11","01-02-2025 14:52:50","01-02-2025 18:14:58","=
Grid outage site went down because Gen overload(20KVA,340A) SS IHS F=E9lix =
Bateu is informed and Is confirmed// He reduced the load on site ","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid o=
utage site went down because Gen overload(20KVA,340A) SS IHS F=E9lix Bateu =
is informed and Is confirmed// He reduced the load on site ","wilfried.kame=
ni@sagemcom.com","1274","01-02-2025 15:13:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004229466","Angongo"=
,"","01-02-2025 14:55:12","01-02-2025 14:03:51","01-02-2025 14:10:31","Casc=
aded Incident from TTO4247390","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active// No power issue on site  Ubaie=3D54.=
3 site On Grid The Tx FME Fulbert(654266068) of huawei is informed","system=
","273637","01-02-2025 14:55:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004229467","Nkongtoc=
k","","01-02-2025 14:55:12","01-02-2025 14:03:51","01-02-2025 14:10:31","Ca=
scaded Incident from TTO4247390","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active// No power issue on site  Ubaie=
=3D54.3 site On Grid The Tx FME Fulbert(654266068) of huawei is informed","=
system","273637","01-02-2025 14:55:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004229465","Mambine"=
,"","01-02-2025 14:55:11","01-02-2025 14:03:51","01-02-2025 14:10:31","Casc=
aded Incident from TTO4247390","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active// No power issue on site  Ubaie=3D54.=
3 site On Grid The Tx FME Fulbert(654266068) of huawei is informed","system=
","273636","01-02-2025 14:55:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004229464","Ebeba","=
","01-02-2025 14:55:11","01-02-2025 14:03:51","01-02-2025 14:10:31","Cascad=
ed Incident from TTO4247390","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active// No power issue on site  Ubaie=3D54.3 =
site On Grid The Tx FME Fulbert(654266068) of huawei is informed","system",=
"273636","01-02-2025 14:55:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004229462","Mbankomo=
 IHS","","01-02-2025 14:55:11","01-02-2025 14:03:51","01-02-2025 14:10:31",=
"Cascaded Incident from TTO4247390","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active// No power issue on site  Ubaie=
=3D54.3 site On Grid The Tx FME Fulbert(654266068) of huawei is informed","=
system","273635","01-02-2025 14:55:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004229463","Nkenglik=
ok","","01-02-2025 14:55:11","01-02-2025 14:03:51","01-02-2025 14:10:31","C=
ascaded Incident from TTO4247390","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active// No power issue on site  Ubai=
e=3D54.3 site On Grid The Tx FME Fulbert(654266068) of huawei is informed",=
"system","273636","01-02-2025 14:55:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004229460","Mandoumb=
a OCM","","01-02-2025 14:55:10","01-02-2025 14:03:51","01-02-2025 14:10:31"=
,"Cascaded Incident from TTO4247390","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active// No power issue on site  U=
baie=3D54.3 site On Grid The Tx FME Fulbert(654266068) of huawei is informe=
d","system","273635","01-02-2025 14:55:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0004229447","O=
KOA Peage","IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_350=
, IHS_YND_335, IHS_YND_349","01-02-2025 14:53:11","01-02-2025 14:03:51","01=
-02-2025 14:10:31","Active// No power issue on site  Ubaie=3D54.3 site On G=
rid The Tx FME Fulbert(654266068) of huawei is informed","Fanda Brice","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active// No power issue on site  Ubaie=3D54.3 site On Grid The Tx F=
ME Fulbert(654266068) of huawei is informed","wilfried.kameni@sagemcom.com"=
,"2961","01-02-2025 14:53:11","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004229398","NKO=
LOSSAN OKOK","","01-02-2025 14:45:54","01-02-2025 14:19:28","01-02-2025 14:=
28:05","No power issue site on grid with U=3D54v site up at 03:13 pm Gre fr=
om Huawei is informed","Parker Tchoup","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D54v site up at 03:13 pm Gre from Huawei is informed","wilfried=
.kameni@sagemcom.com","1587","01-02-2025 14:45:54","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004229380","EMA=
NA BILICK CITY","","01-02-2025 14:43:08","01-02-2025 14:07:35","01-02-2025 =
14:15:17","No power issue on site Ubaie =3D53.4V site on Grid The TX FME Sy=
nphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site Ubaie =3D53.4V site on Grid The TX FME Synphorien (=
650257151) from Huawei is informed","wilfried.kameni@sagemcom.com","2134","=
01-02-2025 14:43:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004229099","N=
yom OCM","","01-02-2025 14:02:02","01-02-2025 13:49:51","01-02-2025 14:19:5=
8","Site went down because Gen failed to start due to Grid bad voltage and =
no Rcp on site // He did a bridge with a good phase","Fabrice Pouakam","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Site =
went down because Gen failed to start due to Grid bad voltage and no Rcp on=
 site // He did a bridge with a good phase","danick.tchakouani@sagemcom.com=
","732","01-02-2025 14:02:02","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004229070","Mes=
sa Carriere","","01-02-2025 13:55:38","01-02-2025 13:44:28","01-02-2025 17:=
36:47","Site went down because 01/03 rectifier faulty // site stabilized SS=
 IHS Fran=E7ois is informed and is confirmed","Mboua Thierry","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down because 01/0=
3 rectifier faulty // site stabilized SS IHS Fran=E7ois is informed and is =
confirmed","el-dalile@sagemcom.com","671","01-02-2025 13:55:38","Sagemcom C=
MR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004229033","Bit=
eng-Maetur","","01-02-2025 13:46:20","01-02-2025 13:34:06","01-02-2025 13:4=
0:58","Active//No power issue, U=3D51.1 on Gen, Tx FME lionel steve adjep/6=
55124876/ From huawei is informed","Mba Lazare Herve","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue, U=3D51.1 on Gen, Tx FME lionel steve adjep/655124876/ From h=
uawei is informed","danick.tchakouani@sagemcom.com","735","01-02-2025 13:46=
:20","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004228910","Eko=
unou","","01-02-2025 13:21:04","01-02-2025 13:01:49","01-02-2025 16:02:33",=
"Grid ouage, site went down because gen fails to start due to gen overload(=
20KvA,300A) SS HIS PASCALINE Confirmed // Load reduiced and gen started","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id ouage, site went down because gen fails to start due to gen overload(20K=
vA,300A) SS HIS PASCALINE Confirmed // Load reduiced and gen started","dani=
ck.tchakouani@sagemcom.com","1157","01-02-2025 13:21:04","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004228476","SIM=
BOCK BONAMBAPE","","01-02-2025 12:07:27","01-02-2025 11:20:42","01-02-2025 =
11:25:24","No power issue site on grid with U=3D48,5v Mbah Osiah from Huawe=
i is informed","Hyemafo Gildas","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wit=
h U=3D48,5v Mbah Osiah from Huawei is informed","danick.tchakouani@sagemcom=
.com","2806","01-02-2025 12:07:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004228453","S=
calom","","01-02-2025 12:03:30","01-02-2025 11:37:01","01-02-2025 13:37:02"=
,"Active//No power issue on site ,site on Grid with Ubaie=3D54,5V The TX FM=
E Mbah Hosiah (674007438) from Huawei is informed and notice that disjuncti=
on at COM Equipment","Paul BIBOUM","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on si=
te ,site on Grid with Ubaie=3D54,5V The TX FME Mbah Hosiah (674007438) from=
 Huawei is informed and notice that disjunction at COM Equipment","danick.t=
chakouani@sagemcom.com","1590","01-02-2025 12:03:30","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004228374","Nsi=
meyong Terre Rouge","","01-02-2025 11:50:17","01-02-2025 11:16:49","01-02-2=
025 11:29:56","Site went down due to pwc Disfunction, SS IHS Fran=E7ois is =
informed // Site stabilized","MINKA NICOLAS","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down due to pwc Disfunc=
tion, SS IHS Fran=E7ois is informed // Site stabilized","danick.tchakouani@=
sagemcom.com","2009","01-02-2025 11:50:17","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004228053","Elo=
umdem stade","","01-02-2025 10:47:46","01-02-2025 10:26:33","01-02-2025 10:=
56:33","Site went down because rectifiers disfunctionning SS IHS Felix conf=
irmed // site stabilised","Fanda Brice","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down because rectifiers disfunctionning=
 SS IHS Felix confirmed // site stabilised","danick.tchakouani@sagemcom.com=
","1274","01-02-2025 10:47:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004227654","C=
RH-Etoug-Ebe","","01-02-2025 09:37:29","01-02-2025 09:24:18","01-02-2025 09=
:35:51","No power issue on site U=3D53 V site on Grid , The Tx RM Alain/691=
144423/ from Huawei is informed. Notice that we have disjunction at BTS OCM=
 (repetitive isssues)","Hyemafo Gildas","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D53 V site on Grid ,The Tx RM Alain/691144423/ from Huawei is informed. =
Notice that we have disjunction at BTS OCM (repetitive isssues)","danick.tc=
hakouani@sagemcom.com","792","01-02-2025 09:37:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004227571","N=
goulmekong-Nord","","01-02-2025 09:17:46","01-02-2025 09:14:28","01-02-2025=
 13:24:29","No power issue site on grid with U=3D54,1v Symphorien from Huaw=
ei is informed.","Siligap Boris","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wi=
th U=3D54,1v Symphorien from Huawei is informed.","danick.tchakouani@sagemc=
om.com","199","01-02-2025 09:17:46","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_381","NOCINC0004227568","Boumnyebel=
","","01-02-2025 09:16:50","","","","Kemeni Franklin","Warning","Warning","=
POWER","Warning - AC Phase 1 Current Low","Alarm cleared","el-dalile@sagemc=
om.com","7","01-02-2025 09:16:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004227492","A=
wae Ewonkan","","01-02-2025 09:00:40","01-02-2025 08:47:22","01-02-2025 09:=
09:30","Site went down due to insufficiency rectifiers IHS SS Alphonse is i=
nformed and is confirmed // Site stabilized","Albran Byorel","Equipment Rep=
air","Passive","Rectifier","Rectifier Module","Site went down due to insuff=
iciency rectifiers IHS SS Alphonse is informed and is confirmed // Site sta=
bilized","christian.fonkou@ihstowers.com","800","01-02-2025 09:00:40","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004227461","MEHANDAN=
","","01-02-2025 08:54:21","01-02-2025 08:44:58","01-02-2025 09:10:05","Cas=
caded Incident from TTO4245029","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, Site went down befor=
e Gen start due to poor backup// Gen started automaticaly","system","271226=
","01-02-2025 08:54:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004227452","O=
dza II OCM","IHS_YND_528","01-02-2025 08:52:03","01-02-2025 08:44:58","01-0=
2-2025 09:10:05","Grid fluctuation, Site went down before Gen start due to =
poor backup// Gen started automaticaly","Albran Byorel","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid fluctuation, =
Site went down before Gen start due to poor backup// Gen started automatica=
ly","christian.fonkou@ihstowers.com","427","01-02-2025 08:52:03","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004227410","A=
kak-Nkozoa-MTN-IHS","","01-02-2025 08:46:04","01-02-2025 08:36:00","01-02-2=
025 09:06:22","Grid fluctuation, site went down because Gen fails to start =
 due to Grid bad voltage  // HE bypassed Grid and Gen manually started","Fa=
brice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, site went down because Gen fails to start  =
due to Grid bad voltage  // HE bypassed Grid and Gen manually started","chr=
istian.fonkou@ihstowers.com","605","01-02-2025 08:46:04","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004227194","SAA=
 Entrance","","01-02-2025 08:00:09","01-02-2025 07:53:58","01-02-2025 08:23=
:26","Grid Outage, site went down because Gen start and stopped with ""high=
 temp"" alarm // He opened the doors and manually start the gen","Parker Tc=
houp","Equipment Repair","Passive","ACDG Gen","Gen Temp High","Grid Outage,=
 site went down because Gen start and stopped with ""high temp"" alarm // H=
e opened the doors and manually start the gen","emmanuel.ghani@ihstowers.co=
m","373","01-02-2025 08:00:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004227067","D=
ong","","01-02-2025 07:31:59","01-02-2025 07:23:52","01-02-2025 07:33:53","=
Active//No power issue, site on Gen With Ubaie=3D55,2V, The Tx FME Gregoire=
 (654547479) from Huawei is informed.","Parker Tchoup","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue, site on Gen With Ubaie=3D55,2V, The Tx FME Gregoire (654547=
479) from Huawei is informed.","christian.fonkou@ihstowers.com","488","01-0=
2-2025 07:31:59","Sagemcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004227022","TSI=
NGA VILLAGE 2","","01-02-2025 07:21:55","01-02-2025 07:05:51","01-02-2025 0=
8:33:59","Site went down because Gen failed to start due to Psc 3 malfuncti=
on  Bernard Atangana is informed // He reset the PSC 3","Delor Telezing","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site =
went down because Gen failed to start due to Psc 3 malfunction Bernard Atan=
gana is informed // He reset the PSC 3","emmanuel.ghani@ihstowers.com","965=
","01-02-2025 07:21:55","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004226749","EMA=
NA BILICK CITY","","01-02-2025 06:11:16","01-02-2025 05:38:05","01-02-2025 =
05:38:06","No power issue on site Ubaie =3D53.4V site on Grid The TX FME Sy=
nphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site Ubaie =3D53.4V site on Grid The TX FME Synphorien (=
650257151) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","1992=
","01-02-2025 06:11:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004226539","S=
aa","IHS_YND_401, IHS_YND_404","01-02-2025 05:02:23","01-02-2025 04:54:09",=
"01-02-2025 05:11:09","Grid outage, site went down because gen ran untill f=
uel shortage // refueling done","Parker Tchoup","Fuel Outage","Passive","Di=
esel","Diesel Outage","Grid outage, site went down because gen ran untill f=
uel shortage // refueling done","olivier.kwedi@ihstowers.com","495","01-02-=
2025 05:02:23","Sagemcom CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0004226531","Car=
refour Ayissi Ele","","01-02-2025 04:57:23","01-02-2025 04:43:12","01-02-20=
25 04:43:13","Active//No power issue on site ,site on Solar with Ubaie=3D 5=
2.9V The Tx FME Gregroire /652070658/From HUAWEI is informed","Parker Tchou=
p","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issue on site ,site on Solar with Ubaie=3D =
52.9V The Tx FME Gregroire /652070658/From HUAWEI is informed","etienne.ito=
ndo@ihstowers.com","851","01-02-2025 04:57:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004226526","S=
AA 2","","01-02-2025 04:54:32","01-02-2025 04:54:09","01-02-2025 05:11:09",=
"","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","olivier.kwedi@ihstowers.com","1234423","01-02-2025 04:54:=
32","Sagemcom CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004226501","Nko=
l-Mebanga","","01-02-2025 04:37:28","01-02-2025 04:29:22","01-02-2025 04:29=
:23","Active//No power issue on site Ubaie=3D50V site on Solar Tx FME Grego=
ire /654547479/Huawei is informed","Parker Tchoup","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue on site Ubaie=3D50V site on Solar Tx FME Gregoire /654547479/Hua=
wei is informed","ludivine.ngamaleu@ihstowers.com","487","01-02-2025 04:37:=
28","Sagemcom CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0004226485","Ngo=
uetou","","01-02-2025 04:30:14","01-02-2025 04:29:08","01-02-2025 08:10:09"=
,"Active//No power issue site on gen with U=3D54v Gregoire/652070658/ from =
Huawei is informed","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue site=
 on gen with U=3D54v Gregoire/652070658/ from Huawei is informed","ludivine=
.ngamaleu@ihstowers.com","67","01-02-2025 04:30:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004226463","A=
kak-Nkozoa-MTN-IHS","","01-02-2025 04:18:33","01-02-2025 02:34:21","01-02-2=
025 03:14:19","Grid fluctuation, site went down because gen start and stopp=
ed due grid bad voltage // he bypass grid and manually start the gen","Fabr=
ice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation, site went down because gen start and stopped =
due grid bad voltage // he bypass grid and manually start the gen","etienne=
.itondo@ihstowers.com","6254","01-02-2025 04:18:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0004226445","Nkoabang=
2","","01-02-2025 04:06:30","01-02-2025 03:57:31","01-02-2025 03:57:32","Ca=
scaded Incident from TTO4243888","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active: No power issue, site is on GR=
ID with U=3D54.9V , The TX FME Lionel adjep //655184876// Huawei is informe=
d","system","274087","01-02-2025 04:06:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0004226440","N=
koabang","IHS_YND_526","01-02-2025 04:05:40","01-02-2025 03:57:31","01-02-2=
025 03:57:32","Active: No power issue, site is on GRID with U=3D54.9V , The=
 TX FME Lionel adjep //655184876// Huawei is informed","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active: No power issue, site is on GRID with U=3D54.9V , The TX =
FME Lionel adjep //655184876// Huawei is informed","olivier.kwedi@ihstowers=
.com","490","01-02-2025 04:05:40","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004226333","Nsi=
meyong Shell","","01-02-2025 03:20:28","01-02-2025 03:10:59","01-02-2025 08=
:55:59","Active// Active: No power issue, site is on Grid with Ubaie=3D53,4=
V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","MINKA NICOLAS=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","Active// Active: No power issue, site is on Grid with Ubaie=
=3D53,4V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","ludivi=
ne.ngamaleu@ihstowers.com","570","01-02-2025 03:20:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004226322","D=
ong","","01-02-2025 03:09:49","01-02-2025 03:00:40","01-02-2025 04:16:20","=
Active//No power issue, site on Gen With Ubaie=3D55,2V, The Tx FME Gregoire=
 (654547479) from Huawei is informed. ","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue, site on Gen With Ubaie=3D55,2V, The Tx FME Gregoire (65454=
7479) from Huawei is informed. ","olivier.kwedi@ihstowers.com","550","01-02=
-2025 03:09:49","Sagemcom CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0004226302","Oko=
la","IHS_YND_703, IHS_YND_530, IHS_YND_390","01-02-2025 03:03:28","01-02-20=
25 02:57:21","01-02-2025 05:30:59","Site went down because the 02 rectifier=
 dysfonction on site, SS IHS PASCALINE // Reset done and gen started","TIEN=
TCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Site went down because the 02 rectifier dysfonction on site, SS IHS=
 PASCALINE // Reset done and gen started","ludivine.ngamaleu@ihstowers.com"=
,"368","01-02-2025 03:03:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004226301","AWAE OCM=
","","01-02-2025 03:02:20","01-02-2025 02:54:22","01-02-2025 03:56:02","Cas=
caded Incident from TTO4243669","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage  Site went down because=
 Gen stopped with alarm "" emergency stop""  //He Reset  the Gen Card  and =
 Gen manually started  ","system","277796","01-02-2025 03:02:20","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004226300","Tradex-N=
komo","","01-02-2025 03:02:20","01-02-2025 02:54:22","01-02-2025 03:56:02",=
"Cascaded Incident from TTO4243669","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage  Site went down becaus=
e Gen stopped with alarm "" emergency stop""  //He Reset  the Gen Card  and=
  Gen manually started  ","system","277797","01-02-2025 03:02:20","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0004226252","Nko=
mo II","IHS_YND_172, IHS_YND_173","01-02-2025 02:58:27","01-02-2025 02:54:2=
2","01-02-2025 03:56:02","Grid Outage  Site went down because Gen stopped w=
ith alarm "" emergency stop""  //He Reset  the Gen Card  and  Gen manually =
started  ","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid Outage  Site went down because Gen stopped with alarm =
"" emergency stop""  //He Reset  the Gen Card  and  Gen manually started  "=
,"ludivine.ngamaleu@ihstowers.com","245","01-02-2025 02:58:27","Sagemcom CM=
R"
"Cancelled","Warning","CTR_259","IHS_YND_169","NOCINC0004226232","Ekoumdoum=
","","01-02-2025 02:46:26","","","","Albran Byorel","","","","","","olivier=
.kwedi@ihstowers.com","548","01-02-2025 02:46:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004226221","MEHANDAN=
","","01-02-2025 02:41:10","01-02-2025 02:28:47","01-02-2025 02:40:27","Cas=
caded Incident from TTO4243616","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // gen start automatically","system","271=
998","01-02-2025 02:41:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004226215","O=
dza II OCM","IHS_YND_528","01-02-2025 02:37:57","01-02-2025 02:28:47","01-0=
2-2025 02:40:27","Grid outage, site went down before gen start due to poor =
battery backup // gen start automatically","Albran Byorel","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before gen start due to poor battery backup // gen start autom=
atically","olivier.kwedi@ihstowers.com","551","01-02-2025 02:37:57","Sagemc=
om CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0004226189","Mvo=
g-Manga","","01-02-2025 02:24:46","01-02-2025 02:19:41","01-02-2025 02:50:5=
1","Grid ouage, site went down because gen start and stopped with alarm Ove=
r current (unprouven alarm)// He reset Gen card , site manually  Gen","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid ouage, site went down because gen start and stopped with alarm Over cu=
rrent (unprouven alarm)// He reset Gen card , site manually  Gen","ludivine=
.ngamaleu@ihstowers.com","307","01-02-2025 02:24:46","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004226183","Tou=
ring Club International","","01-02-2025 02:22:01","01-02-2025 02:13:55","01=
-02-2025 03:00:20","Grid Outage  Site went down because Gen stopped with al=
arm undervoltage  //He Reset  the Gen Card  and  Gen manually started","Alb=
ran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid Outage  Site went down because Gen stopped with alarm undervoltage  /=
/He Reset  the Gen Card  and  Gen manually started","ludivine.ngamaleu@ihst=
owers.com","487","01-02-2025 02:22:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004226180","M=
ontee-Des-Soeurs","","01-02-2025 02:20:49","01-02-2025 02:11:40","01-02-202=
5 02:11:41","No power Issue Site on Grid Ubai =3D54.3 V, The FME The TX FME=
 Mbah Hosiah (674007438) is informed.","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r Issue Site on Grid Ubai =3D54.3 V, The FME The TX FME Mbah Hosiah (674007=
438) is informed.","olivier.kwedi@ihstowers.com","550","01-02-2025 02:20:49=
","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004225851","Mon=
tee-Jouvence-II","","01-02-2025 00:35:33","01-02-2025 00:31:29","01-02-2025=
 00:35:11","site went down because pwc overload(12k/280A) // site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","site went down because pwc overload(12k/280A) // site stab=
ilized","ludivine.ngamaleu@ihstowers.com","245","01-02-2025 00:35:33","Sage=
mcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004225806","EMA=
NA BILICK CITY","","01-02-2025 00:06:39","31-01-2025 20:20:18","31-01-2025 =
20:22:42","Active//No power issues iste on grid with U=3D54,1v  Tchatouang =
Gabi (693846869) from TELIS is working on Site","Fabrice Pouakam","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issues iste on grid with U=3D54,1v  Tchatouang Gabi (69=
3846869) from TELIS is working on Site","ludivine.ngamaleu@ihstowers.com","=
13582","01-02-2025 00:06:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004225679","L=
abogenie","","31-01-2025 23:37:16","31-01-2025 23:33:48","01-02-2025 05:17:=
17","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed. Notice that it is the repetitive issue=
 site up at 11:50 PM","","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","ACTIVE//No  power issue U =3D54,5V sit=
e on Grid. The Tx FME  Eloundou (693212405 )from Huawei is informed. Notice=
 that it is the repetitive issue site up at 11:50 PM","olivier.kwedi@ihstow=
ers.com","209","31-01-2025 23:37:16","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004225525","Eko=
unou","","31-01-2025 22:52:23","31-01-2025 22:47:18","01-02-2025 12:23:23",=
"Grid ouage, site went down because gen fails to start due to gen overload =
SS HIS PASCALINE Confirmed // Load reduiced and gen started","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ouage, si=
te went down because gen fails to start due to gen overload SS HIS PASCALIN=
E Confirmed // Load reduiced and gen started","ludivine.ngamaleu@ihstowers.=
com","307","31-01-2025 22:52:23","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004225374","SIM=
BOCK BONAMBAPE","","31-01-2025 22:23:19","31-01-2025 22:19:14","31-01-2025 =
23:34:20","Site went down due to insufficiency of rectifier causing by  01/=
08 rctifier faulty SS IHS Felix Zamb=E9 confirmed // Site Stabilized","Hyem=
afo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to insufficiency of rectifier causing by  01/08 rctifier f=
aulty SS IHS Felix Zamb=E9 confirmed // Site Stabilized","ludivine.ngamaleu=
@ihstowers.com","246","31-01-2025 22:23:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004225055","S=
calom","","31-01-2025 21:35:09","31-01-2025 21:09:43","31-01-2025 21:09:44"=
,"No power issue, site is on grid with Ubaie=3D53V, Hosiah(674007438) from =
Huawei is informed","Paul BIBOUM","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on gr=
id with Ubaie=3D53V, Hosiah(674007438) from Huawei is informed","alexandre.=
kamal@ihstowers.com","1526","31-01-2025 21:35:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004225050","Scalom-I=
HS","","31-01-2025 21:33:40","31-01-2025 20:27:55","01-02-2025 08:20:43","C=
ascaded Incident from TTO4242228","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid Outage // Grid Restored","system","351394","=
31-01-2025 21:33:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004225049","A=
ccacia New","IHS_YND_505","31-01-2025 21:33:03","31-01-2025 20:27:55","01-0=
2-2025 08:30:43","Grid Outage // Grid Restored","","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid Outage // Grid Restored","=
alexandre.kamal@ihstowers.com","3910","31-01-2025 21:33:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004224994","N=
yom OCM","","31-01-2025 21:28:59","31-01-2025 20:48:49","31-01-2025 21:58:4=
3","Grid fluctuation,Site went down because gen failed to start due to grid=
 bad voltages and no RCP on site //He bypass grid and Gen manually started"=
,"Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation,Site went down because gen failed to sta=
rt due to grid bad voltages and no RCP on site //He bypass grid and Gen man=
ually started","alexandre.kamal@ihstowers.com","2411","31-01-2025 21:28:59"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004224926","Mimboman=
4","","31-01-2025 21:18:50","31-01-2025 17:53:08","31-01-2025 18:47:29","Ca=
scaded Incident from TTO4242092","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work: Our Te=
chnician Herv=E9 /657108482/SAGEMCOM working on site (he add second  starti=
ng power )// End of work","system","302867","31-01-2025 21:18:50","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004224921","Nko=
lo II New","IHS_YND_266","31-01-2025 21:18:18","31-01-2025 17:53:08","31-01=
-2025 18:47:29","Site went down due to work: Our Technician Herv=E9 /657108=
482/SAGEMCOM working on site (he add second  starting power )// End of work=
","Mba Lazare Herve","Installation Activity","Passive","Planned Activity","=
Installation Activity","Site went down due to work: Our Technician Herv=E9 =
/657108482/SAGEMCOM working on site (he add second  starting power )// End =
of work","kamga.virgile@ihstowers.com","12311","31-01-2025 21:18:18","Sagem=
com CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004224812","Mon=
tee-Jouvence-II","","31-01-2025 21:03:00","31-01-2025 20:50:45","31-01-2025=
 21:04:47","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix Za=
mb=E9 confirmed  // Site stabilized","Hyemafo Gildas","Equipment Repair","P=
assive","Rectifier","Rectifier Module Overloaded","Site went down due to PW=
C Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed  // Site stabilized"=
,"kamga.virgile@ihstowers.com","737","31-01-2025 21:03:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004224787","N=
kolfon Cimencam","","31-01-2025 20:57:42","31-01-2025 20:29:36","31-01-2025=
 20:35:36","No power issue site on Grid Ubaie =3D54.5 V, The tx Huawei  Ful=
bert  (654266068) is informed ,Noitice  site is impacted by Afanoya II who =
is not our responsability","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on Grid Ubaie =3D54.5 V, The tx Huawei  Fulbert  (654266068) is informed ,=
Noitice  site is impacted by Afanoya II who is not our responsability","ale=
xandre.kamal@ihstowers.com","1687","31-01-2025 20:57:42","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004224786","Nko=
ulou Carriere carrefourt","","31-01-2025 20:57:31","31-01-2025 20:14:23","0=
1-02-2025 08:51:23","Acces issues during the Night, Site went down because =
the CB (63A) tripped in the PWC // He reamed the CB (63A)","Mba Lazare Herv=
e","Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue=
 - Land Lord","Acces issues during the Night, Site went down because the CB=
 (63A) tripped in the PWC // He reamed the CB (63A)","kamga.virgile@ihstowe=
rs.com","2589","31-01-2025 20:57:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004224784","M=
efou-Assi","","31-01-2025 20:56:56","31-01-2025 20:28:50","31-01-2025 20:35=
:54","Active// No power issue on site  Ubaie=3D49.4V site On battery The Tx=
 FME Fulbert(654266068) of huawei is informed","Fanda Brice","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue on site  Ubaie=3D49.4V site On battery The Tx FME Ful=
bert(654266068) of huawei is informed","alexandre.kamal@ihstowers.com","168=
7","31-01-2025 20:56:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004224332","C=
RH-Etoug-Ebe","","31-01-2025 19:24:52","31-01-2025 19:06:45","31-01-2025 19=
:10:24","No power issue on site U=3D53 V site on Grid , The Tx RM Alain/691=
144423/ from Huawei is informed. Notice that we have disjunction at BTS OCM=
 (repetitive isssues)","Hyemafo Gildas","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D53 V site on Grid ,
The Tx RM Alain/691144423/ from Huawei is informed. Notice that we have dis=
junction at BTS OCM (repetitive isssues)
","alexandre.kamal@ihstowers.com","1088","31-01-2025 19:24:52","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_339","IHS_YND_073","NOCINC0004224107","C=
hapelle-Obili","","31-01-2025 18:32:36","31-01-2025 18:22:56","31-01-2025 1=
9:25:56","Site went down because the Cb(125A) of PWC dysjoncted  due to loa=
d increase//He make the bridge with another  Cb(63*125A) and reamed","Paul =
BIBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet - Circu=
it Breaker Issue","Site went down because the Cb(125A) of PWC dysjoncted  d=
ue to load increase//He make the bridge with another  Cb(63*125A) and reame=
d","alexandre.kamal@ihstowers.com","580","31-01-2025 18:32:36","Sagemcom CM=
R"
"Cancelled","Warning","T1105","IHS_YND_266","NOCINC0004224030","Mimboman4",=
"","31-01-2025 18:15:50","","","","Mba Lazare Herve","","","","","","kamga.=
virgile@ihstowers.com","1403","31-01-2025 18:15:50","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004223860","Ngu=
ila","","31-01-2025 17:44:34","31-01-2025 17:39:24","31-01-2025 17:51:33","=
Site went down because gen stopped with alarm high temp//he open all the do=
or and started the gen","Parker Tchoup","Equipment Repair","Passive","ACDG =
Gen","ACDG - High Engine Temp - Coolant Level Issue","Site went down becaus=
e gen stopped with alarm high temp//he open all the door and started the ge=
n","kamga.virgile@ihstowers.com","311","31-01-2025 17:44:34","Sagemcom CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0004223790","Biy=
emassi LAC","","31-01-2025 17:29:46","31-01-2025 17:13:36","31-01-2025 17:2=
7:06","Grid outage,no space to deploy a mobil gen//grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no =
space to deploy a mobil gen//grid return","kamga.virgile@ihstowers.com","97=
2","31-01-2025 17:29:46","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004223782","BAT=
A Mokolo OCM","","31-01-2025 17:28:22","31-01-2025 17:08:13","31-01-2025 17=
:20:13","Grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,n=
o space to deploy a mobil gen//grid return","kamga.virgile@ihstowers.com","=
1210","31-01-2025 17:28:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0004223567","E=
SSOS OASIS 1111","","31-01-2025 16:47:58","31-01-2025 16:41:55","31-01-2025=
 16:45:08","ACTIVE No power issue on site, site on Grid with Ubaie=3D53.2 V=
 Tx fme Armand Nguetsa /699949553/ from Huawei is informed","Siligap Boris"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","ACTIVE No power issue on site, site on Grid with Ubaie=3D53.2 =
V Tx fme Armand Nguetsa /699949553/ from Huawei is informed","alexandre.kam=
al@ihstowers.com","364","31-01-2025 16:47:58","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004223565","SIM=
BOCK BONAMBAPE","","31-01-2025 16:47:17","31-01-2025 16:42:00","31-01-2025 =
19:13:08","Site went down due to insufficiency of rectifier causing by  01/=
08 rctifier faulty SS IHS Felix Zamb=E9 confirmed // site stabilized","Hyem=
afo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to insufficiency of rectifier causing by  01/08 rctifier f=
aulty SS IHS Felix Zamb=E9 confirmed // site stabilized","kamga.virgile@ihs=
towers.com","318","31-01-2025 16:47:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_744","NOCINC0004223282","Eleveur =
Meec Bon Berger","","31-01-2025 16:02:00","31-01-2025 15:22:18","31-01-2025=
 15:54:58","Cascaded Incident from TTO4240140","Siligap Boris","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Site went down because =
Gen failed to start due to Grid bad voltage and No RCP on site // He bypass=
 the Grid and Gen manually started","system","268906","31-01-2025 16:02:00"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004223145","Fou=
da Quarter","","31-01-2025 15:35:32","31-01-2025 15:25:18","31-01-2025 15:5=
6:52","Site went down due to insuffience of rectifiers (03) on site SS IHS =
Blaise Raoul is on informed// Site stabilized","Delor Telezing","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down due to ins=
uffience of rectifiers (03) on site SS IHS Blaise Raoul is on informed// Si=
te stabilized","kamga.virgile@ihstowers.com","615","31-01-2025 15:35:32","S=
agemcom CMR"
"Cancelled","Warning","","IHS_YND_744","NOCINC0004223139","Eleveur Meec Bon=
 Berger","","31-01-2025 15:34:30","","","Cascaded Incident from TTO4239954 =
- Cascade Removed From TTO4239954","Siligap Boris","","","","","","system",=
"534","31-01-2025 15:34:30","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004223104","Nko=
lbisson IITA LP","","31-01-2025 15:30:31","31-01-2025 15:11:22","31-01-2025=
 15:31:22","No power issue site on grid with U=3D53,8v Mohamadou from HAUWE=
I is informed","","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53,8v Mo=
hamadou from HAUWEI is informed","kamga.virgile@ihstowers.com","1150","31-0=
1-2025 15:30:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004223103","Ngoulmek=
ong-Nord","","31-01-2025 15:30:30","31-01-2025 15:22:18","31-01-2025 15:51:=
30","Cascaded Incident from TTO4239899","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down because Gen fai=
led to start due to Grid bad voltage and No RCP on site // He bypass the Gr=
id and Gen manually started","system","268906","31-01-2025 15:30:30","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004223080","E=
leveur","IHS_YND_277, IHS_YND_744","31-01-2025 15:27:23","31-01-2025 15:22:=
18","31-01-2025 15:54:58","Site went down because Gen failed to start due t=
o Grid bad voltage and No RCP on site // He bypass the Grid and Gen manuall=
y started","Siligap Boris","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","Site went down because Gen failed to start due to=
 Grid bad voltage and No RCP on site // He bypass the Grid and Gen manually=
 started","alexandre.kamal@ihstowers.com","306","31-01-2025 15:27:23","Sage=
mcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0004222946","ODZ=
A BORNE 10","","31-01-2025 14:59:53","31-01-2025 14:29:43","31-01-2025 14:3=
5:29","No power issue site on Gen with U=3D54,3 V the fme Mbamassa 65801028=
2  Telis is working on site","Albran Byorel","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on Gen with U=3D54,3 V the fme Mbamassa 658010282  Telis is working on si=
te","kamga.virgile@ihstowers.com","1811","31-01-2025 14:59:53","Sagemcom CM=
R"
"Closed Complete","Warning","T0091","IHS_YND_314","NOCINC0004222855","Sous =
Prefecture","","31-01-2025 14:55:17","","","site on battery","Fanda Brice",=
"Warning","Warning","POWER","Warning - AC Phase 1 Current Low","Alarm clear=
ed","dorothy.djantio@ihstowers.com","305","31-01-2025 14:55:17","Sagemcom C=
MR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004222504","BIY=
EMASSI NIKI","","31-01-2025 14:04:24","31-01-2025 11:40:18","31-01-2025 15:=
26:04","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d, F=E9lix Zambe is informed and confirmed // Site stabilized","Hyemafo Gil=
das","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded"=
,"Site went down due to PWC overloaded (12kva 250 A) //Site stabilized, F=
=E9lix Zambe is informed and confirmed // Site stabilized","stephane.nkamwa=
@ihstowers.com","8647","31-01-2025 14:04:24","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004222483","EMA=
NA BILICK CITY","","31-01-2025 14:00:56","31-01-2025 13:57:48","31-01-2025 =
14:00:30","No power issue on site Ubaie =3D53.4V site on Grid The TX FME Sy=
nphorien (650257151) from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site Ubaie =3D53.4V site on Grid The TX FME Synphorien (=
650257151) from Huawei is informed","stephane.nkamwa@ihstowers.com","189","=
31-01-2025 14:00:56","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004222403","BAT=
A Mokolo OCM","","31-01-2025 13:46:18","31-01-2025 13:36:07","31-01-2025 14=
:54:21","Grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,n=
o space to deploy a mobil gen//grid return","stephane.nkamwa@ihstowers.com"=
,"612","31-01-2025 13:46:18","Sagemcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004222382","TSI=
NGA VILLAGE 2","","31-01-2025 13:43:16","31-01-2025 13:28:34","31-01-2025 1=
4:37:06","Site went down because Gen failed to start due to Psc 3 DYSFONCTI=
ON // He reset the PSC 3","Delor Telezing","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Site went down because Gen failed to start =
due to Psc 3 DYSFONCTION // He reset the PSC 3","stephane.nkamwa@ihstowers.=
com","883","31-01-2025 13:43:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004222324","S=
calom","","31-01-2025 13:34:41","31-01-2025 13:27:11","31-01-2025 16:01:09"=
,"Site went down because 02/06 rectifier faulty on site // He replaced the =
rectifier faulty and added 01 rectifier","Paul BIBOUM","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down because 02/06 recti=
fier faulty on site // He replaced the rectifier faulty and added 01 rectif=
ier","kouoh.jean@ihstowers.com","451","31-01-2025 13:34:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0004222313","R=
d-Pt-Express","","31-01-2025 13:32:16","31-01-2025 13:17:07","31-01-2025 18=
:26:52","Grid only site ,no sapce to deploy mobile gen //Grid power RETURN"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d only site ,no sapce to deploy mobile gen //Grid power RETURN","kouoh.jean=
@ihstowers.com","910","31-01-2025 13:32:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0004221954","Scalom-I=
HS","","31-01-2025 12:29:51","31-01-2025 12:26:51","31-01-2025 18:24:51","C=
ascaded Incident from TTO4238585","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage // Grid powe return","system","293648=
","31-01-2025 12:29:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0004221949","A=
ccacia New","IHS_YND_505","31-01-2025 12:29:05","31-01-2025 12:26:51","31-0=
1-2025 18:33:28","Grid outage // Grid powe return","","Grid Supply","Passiv=
e","Grid","National Grid - Grid Outage Issue","Grid outage // Grid powe ret=
urn","kouoh.jean@ihstowers.com","135","31-01-2025 12:29:05","Sagemcom CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0004221807","Biy=
emassi LAC","","31-01-2025 12:12:06","31-01-2025 12:03:54","31-01-2025 16:1=
7:17","Grid only site ,no sapce to deploy mobile Gen //Grid power","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid only si=
te ,no sapce to deploy mobile Gen //Grid power","stephane.nkamwa@ihstowers.=
com","493","31-01-2025 12:12:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004221760","B=
arriere IHS","","31-01-2025 12:02:38","31-01-2025 11:36:43","31-01-2025 11:=
42:44","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","Casc=
ade Active","Active//No power issue on site,site on Grid with Ubaie=3D52.8 =
V The TX FME Lionnel//694693436 From Huawei is informed.
","kouoh.jean@ihstowers.com","267837","31-01-2025 12:02:38","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004221726","Ema=
na","","31-01-2025 11:55:11","31-01-2025 11:35:03","31-01-2025 11:49:54","G=
rid outage, site went down before gen start due to poor battery backup // g=
en start automatically","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // gen start automatically","stepha=
ne.nkamwa@ihstowers.com","1209","31-01-2025 11:55:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004221673","M=
efou-Assi","IHS_YND_696","31-01-2025 11:44:10","31-01-2025 11:36:43","31-01=
-2025 11:42:44","Active//No power issue on site,site on Grid with Ubaie=3D5=
2.8 V   The TX FME Lionnel//694693436 From Huawei is informed.","Fanda Bric=
e","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issue on site,site on Grid with Ubaie=3D52.=
8 V The TX FME Lionnel//694693436 From Huawei is informed.
","kouoh.jean@ihstowers.com","448","31-01-2025 11:44:10","Sagemcom CMR"
"Closed Complete","Warning","T1594","IHS_YND_298","NOCINC0004221207","Olemb=
e","","31-01-2025 10:38:27","","","site on battery","Fabrice Pouakam","Warn=
ing","Warning","POWER","Warning - AC Phase 1 Current Low","Alarm cleared","=
dorothy.djantio@ihstowers.com","185","31-01-2025 10:38:27","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004221125","Pha=
rmacie SION","","31-01-2025 10:24:45","31-01-2025 10:15:19","31-01-2025 10:=
33:54","Grid outage, site went down before gen start due to poor battery ba=
ckup // gen start automatically","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // gen start automatically","s=
tephane.nkamwa@ihstowers.com","567","31-01-2025 10:24:45","Sagemcom CMR"
"Closed Complete","Site Down","T1394","IHS_YND_511","NOCINC0004221008","Eto=
ug ebe Carrefour","","31-01-2025 10:13:07","31-01-2025 09:53:54","31-01-202=
5 12:30:11","Grid outage .gen failed to start due to starter relay faulty//=
 We bypass it and gen manually started","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Kick Starter","Grid outage .gen failed to sta=
rt due to starter relay faulty// We bypass it and gen manually started","st=
ephane.nkamwa@ihstowers.com","1154","31-01-2025 10:13:07","Sagemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0004220844","Aba=
ng","","31-01-2025 09:52:57","31-01-2025 09:31:51","31-01-2025 09:53:01","N=
o power issue iste on grid with U=3D54,1v  Tchatouang Gabi (693846869) from=
 TELIS is working on site  site up at 09:53 AM","Mba Lazare Herve","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue iste on grid with U=3D54,1v  Tchatouang Gabi (693846869)=
 from TELIS is working on site  site up at 09:53 AM","stephane.nkamwa@ihsto=
wers.com","1268","31-01-2025 09:52:57","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004220790","Nko=
lbisson IITA LP","","31-01-2025 09:37:58","31-01-2025 09:18:53","31-01-2025=
 09:20:59","No power issue site on grid with U=3D53,8v site up at 09:55 AM =
Mohamadou from HAUWEI is informed","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gr=
id with U=3D53,8v site up at 09:55 AM Mohamadou from HAUWEI is informed","s=
tephane.nkamwa@ihstowers.com","1146","31-01-2025 09:37:58","Sagemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0004220446","CRH=
-Etoug-Ebe","","31-01-2025 08:49:04","31-01-2025 08:44:14","31-01-2025 08:5=
7:30","Grid outage,site went down because gen failed to start //grid return=
(investigation ongoing)","Hyemafo Gildas","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage,site went down because gen faile=
d to start //grid return(investigation ongoing)","stephane.nkamwa@ihstowers=
.com","667","31-01-2025 08:49:04","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004220399","BIY=
EMASSI NIKI","","31-01-2025 08:42:28","31-01-2025 08:34:20","31-01-2025 10:=
38:06","Grid outage,gen failed to start due to battery GE faulty//Gen manua=
lly started with external battery","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Generator Battery","Grid outage,gen failed to star=
t due to battery GE faulty//Gen manually started with external battery","st=
ephane.nkamwa@ihstowers.com","489","31-01-2025 08:42:28","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004220372","Fou=
da Quarter","","31-01-2025 08:37:51","31-01-2025 08:32:43","31-01-2025 08:4=
0:25","ACTIVE//No power issue on site Ubaie=3D54.6V site on Grid, The TX FM=
E Armand Nguetsa  from Huawei (699949553) is informed Site up at 08:50 AM",=
"Delor Telezing","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","ACTIVE//No power issue on site Ubaie=3D54.6V s=
ite on Grid, The TX FME Armand Nguetsa  from Huawei (699949553) is informed=
 Site up at 08:50 AM","stephane.nkamwa@ihstowers.com","309","31-01-2025 08:=
37:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004219727","L=
abogenie","","31-01-2025 06:30:42","31-01-2025 06:20:26","31-01-2025 06:21:=
30","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed. Notice that it is the repetitive issue=
 site up at 07:21 AM","","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","ACTIVE//No  power issue U =3D54,5V sit=
e on Grid. The Tx FME  Eloundou (693212405 )from Huawei is informed. Notice=
 that it is the repetitive issue site up at 07:21 AM","kouoh.jean@ihstowers=
.com","618","31-01-2025 06:30:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004219088","D=
ong","","31-01-2025 02:23:28","31-01-2025 02:19:46","31-01-2025 02:50:07","=
Active: No power issue, site on Battery With Ubaie=3D50,2V, The Tx FME Greg=
oire (654547479) from Huawei is informed.  Notice that site is impacted By =
Mbandjock camrail","Parker Tchoup","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active: No power issue, site=
 on Battery With Ubaie=3D50,2V, The Tx FME Gregoire (654547479) from Huawei=
 is informed.  Notice that site is impacted By Mbandjock camrail","rouselle=
.schoune@ihstowers.com","223","31-01-2025 02:23:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004219047","SAA 2","=
","31-01-2025 02:03:40","30-01-2025 22:31:23","30-01-2025 23:17:00","Cascad=
ed Incident from TTO4235215","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because Gen f=
ailed to start due to Gen card off causing by fuse open // he did a bridge =
and started gen manualy","system","279099","31-01-2025 02:03:40","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004219030","S=
aa","IHS_YND_810, IHS_YND_809, IHS_YND_401, IHS_YND_404","31-01-2025 01:56:=
33","30-01-2025 22:31:06","30-01-2025 23:19:14","Grid outage, Site went dow=
n because Gen failed to start due to Gen card off causing by fuse open // h=
e did a bridge and started gen manualy","Parker Tchoup","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down be=
cause Gen failed to start due to Gen card off causing by fuse open // he di=
d a bridge and started gen manualy","rouselle.schoune@ihstowers.com","13063=
","31-01-2025 01:56:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004218434","B=
arriere","","30-01-2025 22:43:58","30-01-2025 22:36:59","31-01-2025 00:06:5=
3","Grid fluctuation,Site went down because gen failed to start due to grid=
 bad voltages and no RCP on site //He bypass grid and Gen manually started"=
,"Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation,Site went down because gen failed to star=
t due to grid bad voltages and no RCP on site //He bypass grid and Gen manu=
ally started","rouselle.schoune@ihstowers.com","419","30-01-2025 22:43:58",=
"Sagemcom CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0004218414","Car=
refour Ayissi Ele","","30-01-2025 22:37:02","30-01-2025 22:31:06","30-01-20=
25 23:19:14","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","Grid outage, Site went down because Gen failed to star=
t due to Gen card off causing by fuse open // he did a bridge and started g=
en manualy","ange.kongo@ihstowers.com","279115","30-01-2025 22:37:02","Sage=
mcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004218104","Elo=
umdem stade","","30-01-2025 21:59:57","30-01-2025 21:55:52","30-01-2025 22:=
16:48","Grid fluctuation,Site went down because gen failed to start due to =
grid bad voltages and no RCP on site //He bypass grid and Gen manually star=
ted","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation,Site went down because gen failed to sta=
rt due to grid bad voltages and no RCP on site //He bypass grid and Gen man=
ually started","ludivine.ngamaleu@ihstowers.com","246","30-01-2025 21:59:57=
","Sagemcom CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004218087","Nko=
l-Mebanga","","30-01-2025 21:57:17","30-01-2025 22:31:06","30-01-2025 23:19=
:14","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, Site went down because Gen failed to start due to=
 Gen card off causing by fuse open // he did a bridge and started gen manua=
ly","ludivine.ngamaleu@ihstowers.com","279114","30-01-2025 21:57:17","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004217903","N=
kolbong","","30-01-2025 21:29:53","30-01-2025 21:19:59","30-01-2025 21:32:1=
0","Grid outage,gen failed to start due to gen card disfunctionning//He res=
et it and started the gen","Delor Telezing","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due to gen=
 card disfunctionning//He reset it and started the gen","dorothy.djantio@ih=
stowers.com","595","30-01-2025 21:29:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004217860","C=
RH-Etoug-Ebe","","30-01-2025 21:23:24","30-01-2025 20:00:17","30-01-2025 20=
:01:30","Active// No power issue, site is on grid with Ubaie=3D53V, RM  Ala=
in (691144423) from Huawei is informed, Notice that we have disjunction in =
OCM equipment","Hyemafo Gildas","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active// No power issue, site i=
s on grid with Ubaie=3D53V, RM  Alain (691144423) from Huawei is informed, =
Notice that we have disjunction in OCM equipment","dorothy.djantio@ihstower=
s.com","4987","30-01-2025 21:23:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004217834","SAA 2","=
","30-01-2025 21:21:11","30-01-2025 18:50:59","30-01-2025 22:09:19","Cascad=
ed Incident from TTO4232775","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Radiator burst // FME clogged radiator an=
d started GEN manually ( site stayed down due to lack of glue - FME used to=
matoes )","system","285102","30-01-2025 21:21:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004217832","Saa","",=
"30-01-2025 21:21:11","30-01-2025 18:50:59","30-01-2025 22:09:19","Cascaded=
 Incident from TTO4232775","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Radiator burst // FME clogged radiator and =
started GEN manually ( site stayed down due to lack of glue - FME used toma=
toes )","system","285103","30-01-2025 21:21:11","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004217798","Mes=
sa Carriere","","30-01-2025 21:18:20","30-01-2025 21:01:11","30-01-2025 22:=
33:49","Grid outage.gen failed to start due to card GE dysfunctionned //Gen=
 manualy started","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Grid outage.gen failed to start due to card GE dysfu=
nctionned //Gen manualy started","etienne.itondo@ihstowers.com","1030","30-=
01-2025 21:18:20","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_404","NOCINC0004217698","SAA 2","","30-01=
-2025 21:06:20","","","Cascaded Incident from TTO4233661","Parker Tchoup","=
","","","","","system","637","30-01-2025 21:06:20","Sagemcom CMR"
"Cancelled","Warning","CTR_192","IHS_YND_405","NOCINC0004217677","Saa","IHS=
_YND_401, IHS_YND_404","30-01-2025 21:03:50","","","","Parker Tchoup","",""=
,"","","","dorothy.djantio@ihstowers.com","487","30-01-2025 21:03:50","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004217645","Mimboman=
4","","30-01-2025 20:58:20","30-01-2025 20:54:01","30-01-2025 21:19:44","Ca=
scaded Incident from TTO4233621","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because CB (125A) t=
ripped PWC due to load increase// CB put back on","system","1234295","30-01=
-2025 20:58:20","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004217642","Nko=
lo II New","IHS_YND_266","30-01-2025 20:57:06","30-01-2025 20:54:01","30-01=
-2025 21:19:44","Site went down because CB (125A) tripped PWC due to load i=
ncrease// CB put back on","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down beca=
use CB (125A) tripped PWC due to load increase// CB put back on","ludivine.=
ngamaleu@ihstowers.com","187","30-01-2025 20:57:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004217589","L=
abogenie","","30-01-2025 20:51:02","30-01-2025 19:29:56","30-01-2025 19:39:=
56","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed. Notice that it is the repetitive issue=
 ","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx F=
ME  Eloundou (693212405 )from Huawei is informed. Notice that it is the rep=
etitive issue ","dorothy.djantio@ihstowers.com","4867","30-01-2025 20:51:02=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_621","IHS_YND_278","NOCINC0004217408","N=
kolfoulou 2","","30-01-2025 20:21:31","30-01-2025 20:16:23","30-01-2025 20:=
17:37","Error Ticket because site not Down","Siligap Boris","Incorrectly Lo=
gged Tickets","Error","Error","Error","Error Ticket because site not Down",=
"dorothy.djantio@ihstowers.com","309","30-01-2025 20:21:31","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004217367","Nko=
lbisson IITA LP","","30-01-2025 20:16:35","30-01-2025 20:09:28","30-01-2025=
 21:44:09","Grid outage, No space to deploy a MDG grid // Power return ",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, No space to deploy a MDG grid // Power return ","ludivine.ngamaleu@i=
hstowers.com","428","30-01-2025 20:16:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004217180","N=
kolbong","","30-01-2025 19:48:08","30-01-2025 19:43:03","30-01-2025 20:42:4=
9","Grid outage,gen failed to start due to gen card disfunctionning//he res=
et it and started the gen","Delor Telezing","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due to gen=
 card disfunctionning//he reset it and started the gen","dorothy.djantio@ih=
stowers.com","306","30-01-2025 19:48:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0004217083","N=
goulmekong-Nord","","30-01-2025 19:30:23","30-01-2025 19:17:59","30-01-2025=
 20:10:23","","Siligap Boris","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid bad voltage;and gen failed to start,no rcp//bypasse=
d grid and started the gen","dorothy.djantio@ihstowers.com","269160","30-01=
-2025 19:30:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004217066","E=
leveur","IHS_YND_277","30-01-2025 19:27:07","30-01-2025 19:17:59","30-01-20=
25 20:10:23","Grid bad voltage;and gen failed to start,no rcp//bypassed gri=
d and started the gen","Siligap Boris","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","Grid bad voltage;and gen failed to st=
art,no rcp//bypassed grid and started the gen","dorothy.djantio@ihstowers.c=
om","549","30-01-2025 19:27:07","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004217010","NKO=
MEKUI OCM","","30-01-2025 19:18:19","30-01-2025 19:12:12","30-01-2025 19:22=
:12","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted b=
y Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted =
by Mbankolo Camtel and not managing by IHS","ludivine.ngamaleu@ihstowers.co=
m","368","30-01-2025 19:18:19","Sagemcom CMR"
"Closed Complete","Warning","CTR_214","IHS_YND_296","NOCINC0004216939","Nko=
lfoulou","","30-01-2025 19:03:14","","","","Siligap Boris","Warning","Warni=
ng","POWER","Warning - AC Phase 1 Current Low","Alarm cleared","olivier.kwe=
di@ihstowers.com","3","30-01-2025 19:03:14","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004216929","SIM=
BOCK BONAMBAPE","","30-01-2025 18:58:49","30-01-2025 18:46:32","30-01-2025 =
20:26:57","Site went down due to inssufficiency of rectifier causing by 02/=
08 rctifier faulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","Hyem=
afo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to inssufficiency of rectifier causing by 02/08 rctifier f=
aulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","olivier.kwedi@ihs=
towers.com","737","30-01-2025 18:58:49","Sagemcom CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0004216558","Bye=
massi Carrefour","","30-01-2025 17:57:09","30-01-2025 17:55:02","30-01-2025=
 18:00:39","Active// No power issue, Site on Gen U=3D53,5V, The FME Antoine=
 Noumedem (657011008)/From I ENG working on site (swap & installation of eq=
uipments MTN)","Paul BIBOUM","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active// No power issue, Site on G=
en U=3D53,5V, The FME Antoine Noumedem (657011008)/From I ENG working on si=
te (swap & installation of equipments MTN)","ludivine.ngamaleu@ihstowers.co=
m","128","30-01-2025 17:57:09","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_039","NOCINC0004216468","Siantou Ra=
dio TV","","30-01-2025 17:40:45","","","Site alrming because site on batter=
y due to Grid outage //GRID RETURN","","Warning","Warning","POWER","Warning=
 - Site on Battery","Site alrming because site on battery due to Grid outag=
e //GRID RETURN","olivier.kwedi@ihstowers.com","3","30-01-2025 17:40:45","S=
agemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004216330","Awa=
e Ewonkan","","30-01-2025 17:23:42","30-01-2025 17:20:20","30-01-2025 18:18=
:58","Site went down because CB(2*63 A)  disjuncted in PWC who feeds equipm=
ents MTN due to increase load on site /He reamed CB","Albran Byorel","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Iss=
ue","Site went down because CB(2*63 A)  disjuncted in PWC who feeds equipme=
nts MTN due to increase load on site /He reamed CB","ludivine.ngamaleu@ihst=
owers.com","203","30-01-2025 17:23:42","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004216137","Beh=
ind P T school Yde","","30-01-2025 17:03:52","30-01-2025 16:58:42","30-01-2=
025 20:00:12","Site went down due to insufficience of rectifiers on site (0=
2/03)  are faulty ,SS IHS Fran=E7ois  is informed and confirmed. // Site St=
abilized (need  02 rectifiers to be added). ","Paul BIBOUM","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module","Site went down due to insuffi=
cience of rectifiers on site (02/03)  are faulty ,SS IHS Fran=E7ois  is inf=
ormed and confirmed. // Site Stabilized (need  02 rectifiers to be added). =
","ludivine.ngamaleu@ihstowers.com","311","30-01-2025 17:03:52","Sagemcom C=
MR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004216098","Ngu=
ila","","30-01-2025 16:55:04","30-01-2025 16:46:59","30-01-2025 17:01:42","=
Grid outage,gen stopped with alarm high temp//he open all the door and star=
ted the gen","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG =
- High Engine Temp - Coolant Level Issue","Grid outage,gen stopped with ala=
rm high temp//he open all the door and started the gen","ludivine.ngamaleu@=
ihstowers.com","486","30-01-2025 16:55:04","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0004216068","Ngo=
a Ekelle","","30-01-2025 16:51:05","30-01-2025 16:43:59","30-01-2025 17:37:=
05","Site went down because insufficient of rectifier (03) on site SS IHS A=
lphonse is confirmed//he added one rectifier","Paul BIBOUM","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module","Site went down because insuff=
icient of rectifier (03) on site SS IHS Alphonse is confirmed//he added one=
 rectifier","ludivine.ngamaleu@ihstowers.com","427","30-01-2025 16:51:05","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0004215971","Elig Edz=
oa","","30-01-2025 16:40:05","30-01-2025 16:21:07","30-01-2025 16:31:07","C=
ascaded Incident from TTO4231547","Delor Telezing","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D54,5v site =
on grid Tx fme Brice 650214096 of huawei is informed","system","265377","30=
-01-2025 16:40:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0004215970","Charles-=
Atangana","","30-01-2025 16:40:04","30-01-2025 16:21:07","30-01-2025 16:31:=
07","Cascaded Incident from TTO4231547","","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site U=3D54,5v site on grid =
Tx fme Brice 650214096 of huawei is informed","system","265377","30-01-2025=
 16:40:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_134","NOCINC0004215968","Vallee B=
astos MTN","","30-01-2025 16:40:04","30-01-2025 16:21:07","30-01-2025 16:31=
:07","Cascaded Incident from TTO4231547","Mboua Thierry","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site U=3D54,5v=
 site on grid Tx fme Brice 650214096 of huawei is informed","system","26537=
6","30-01-2025 16:40:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_009","NOCINC0004215967","CLE Buil=
ding","","30-01-2025 16:40:04","30-01-2025 16:21:07","30-01-2025 16:31:07",=
"Cascaded Incident from TTO4231547","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue on site U=3D54,5v site on grid Tx f=
me Brice 650214096 of huawei is informed","system","265376","30-01-2025 16:=
40:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_016","NOCINC0004215966","Maetur",=
"","30-01-2025 16:40:04","30-01-2025 16:21:07","30-01-2025 16:31:07","Casca=
ded Incident from TTO4231547","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site U=3D54,5v site on gr=
id Tx fme Brice 650214096 of huawei is informed","system","265375","30-01-2=
025 16:40:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0004215969","Hopital =
Central","","30-01-2025 16:40:04","30-01-2025 16:21:07","30-01-2025 16:31:0=
7","Cascaded Incident from TTO4231547","","Cascade Outage","Active","Cascad=
e Active","Cascade Active","No power issue on site U=3D54,5v site on grid T=
x fme Brice 650214096 of huawei is informed","system","265376","30-01-2025 =
16:40:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0004215962","Sapeur",=
"","30-01-2025 16:40:03","30-01-2025 16:21:07","30-01-2025 16:31:07","Casca=
ded Incident from TTO4231547","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site U=3D54,5v site on gr=
id Tx fme Brice 650214096 of huawei is informed","system","265373","30-01-2=
025 16:40:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_013","NOCINC0004215963","Laborato=
ire T.Bella","","30-01-2025 16:40:03","30-01-2025 16:21:07","30-01-2025 16:=
31:07","Cascaded Incident from TTO4231547","Paul BIBOUM","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site U=3D54,5v=
 site on grid Tx fme Brice 650214096 of huawei is informed","system","26537=
3","30-01-2025 16:40:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0004215965","ELIg-Ess=
ono","","30-01-2025 16:40:03","30-01-2025 16:21:07","30-01-2025 16:31:07","=
Cascaded Incident from TTO4231547","Delor Telezing","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D54,5v site=
 on grid Tx fme Brice 650214096 of huawei is informed","system","265375","3=
0-01-2025 16:40:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0004215964","Garbati =
building","","30-01-2025 16:40:03","30-01-2025 16:21:07","30-01-2025 16:31:=
07","Cascaded Incident from TTO4231547","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site U=3D54,5v=
 site on grid Tx fme Brice 650214096 of huawei is informed","system","26537=
4","30-01-2025 16:40:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_731","NOCINC0004215961","UPAC LP"=
,"","30-01-2025 16:40:02","30-01-2025 16:21:07","30-01-2025 16:31:07","Casc=
aded Incident from TTO4231547","","Cascade Outage","Active","Cascade Active=
","Cascade Active","No power issue on site U=3D54,5v site on grid Tx fme Br=
ice 650214096 of huawei is informed","system","265372","30-01-2025 16:40:02=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0004215960","HOPITAL =
DE LA CAISSE","","30-01-2025 16:40:02","30-01-2025 16:21:07","30-01-2025 16=
:31:07","Cascaded Incident from TTO4231547","Delor Telezing","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site U=3D5=
4,5v site on grid Tx fme Brice 650214096 of huawei is informed","system","2=
65372","30-01-2025 16:40:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_049","NOCINC0004215958","Etoa-Mek=
i","","30-01-2025 16:40:02","30-01-2025 16:21:07","30-01-2025 16:31:07","Ca=
scaded Incident from TTO4231547","Delor Telezing","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site U=3D54,5v site o=
n grid Tx fme Brice 650214096 of huawei is informed","system","265371","30-=
01-2025 16:40:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0004215959","POLYCLIN=
IQUE TSINGA","","30-01-2025 16:40:02","30-01-2025 16:21:07","30-01-2025 16:=
31:07","Cascaded Incident from TTO4231547","Mboua Thierry","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D54,=
5v site on grid Tx fme Brice 650214096 of huawei is informed","system","265=
372","30-01-2025 16:40:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004215955","Bastos B=
ethesda","","30-01-2025 16:40:01","30-01-2025 16:21:07","30-01-2025 16:31:0=
7","Cascaded Incident from TTO4231547","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site U=3D54,5v s=
ite on grid Tx fme Brice 650214096 of huawei is informed","system","265370"=
,"30-01-2025 16:40:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_084","NOCINC0004215954","Briquett=
erie","","30-01-2025 16:40:01","30-01-2025 16:21:07","30-01-2025 16:31:07",=
"Cascaded Incident from TTO4231547","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue on site U=3D54,5v site on grid Tx f=
me Brice 650214096 of huawei is informed","system","265369","30-01-2025 16:=
40:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0004215957","Mamch Bu=
ilding","","30-01-2025 16:40:01","30-01-2025 16:21:07","30-01-2025 16:31:07=
","Cascaded Incident from TTO4231547","Mboua Thierry","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue on site U=3D54,5v si=
te on grid Tx fme Brice 650214096 of huawei is informed","system","265371",=
"30-01-2025 16:40:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_790","NOCINC0004215952","TRB Cent=
re ville","","30-01-2025 16:40:00","30-01-2025 16:21:07","30-01-2025 16:31:=
07","Cascaded Incident from TTO4231547","Yamen Herman","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site U=3D54,5v s=
ite on grid Tx fme Brice 650214096 of huawei is informed","system","265374"=
,"30-01-2025 16:40:00",""
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0004215953","H-Franco=
 New","","30-01-2025 16:40:00","30-01-2025 16:21:07","30-01-2025 16:31:07",=
"Cascaded Incident from TTO4231547","Delor Telezing","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site U=3D54,5v sit=
e on grid Tx fme Brice 650214096 of huawei is informed","system","265369","=
30-01-2025 16:40:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004215908","B=
arriere","","30-01-2025 16:29:52","30-01-2025 16:12:48","30-01-2025 16:38:0=
0","Grid fluctuation, site went down because Gen fails  to start due to Gri=
d bad voltage and no rcp on site  //He bypass the Grid and site on Gen","Hy=
emafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because Gen fails  to start d=
ue to Grid bad voltage and no rcp on site  //He bypass the Grid and site on=
 Gen","dorothy.djantio@ihstowers.com","1025","30-01-2025 16:29:52","Sagemco=
m CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0004215892","Hot=
el de Ville Yde","IHS_YND_790, IHS_YND_711, IHS_YND_084, IHS_YND_563, IHS_D=
LA_298, IHS_YND_051, IHS_YND_049, IHS_YND_086, IHS_YND_064, IHS_YND_731, IH=
S_YND_029, IHS_YND_013, IHS_YND_024, IHS_YND_014, IHS_YND_016, IHS_YND_009,=
 IHS_YND_134, IHS_YND_027, IHS_YND_125, IHS_YND_504","30-01-2025 16:27:12",=
"30-01-2025 16:21:07","30-01-2025 17:35:02","No power issue on site U=3D54,=
5v site on grid Tx fme Brice 650214096 of huawei is informed","Paul BIBOUM"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue on site U=3D54,5v site on grid Tx fme Brice 650=
214096 of huawei is informed","ludivine.ngamaleu@ihstowers.com","366","30-0=
1-2025 16:27:12","Sagemcom CMR"
"Closed Complete","Site Down","T1590","IHS_YND_141","NOCINC0004215874","New=
-Marche-Melen","","30-01-2025 16:23:48","30-01-2025 16:20:43","30-01-2025 1=
6:25:08"," No power issue on site Ubaie =3D53.3 V site on Grid  the FME  Th=
e TX FME Mbah Hosiah (674007438) is informed. ","Paul BIBOUM","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," =
No power issue on site Ubaie =3D53.3 V site on Grid  the FME  The TX FME Mb=
ah Hosiah (674007438) is informed. ","ludivine.ngamaleu@ihstowers.com","186=
","30-01-2025 16:23:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0004215866","E=
SSOS OASIS 1111","","30-01-2025 16:21:46","30-01-2025 16:01:42","30-01-2025=
 18:20:42","No power issue on site U=3D53v site on grid Tx fme Armand of hu=
awei is informed","Siligap Boris","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53=
v site on grid Tx fme Armand of huawei is informed","dorothy.djantio@ihstow=
ers.com","1205","30-01-2025 16:21:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004215778","M=
EFOU ASSI","","30-01-2025 16:05:46","30-01-2025 16:00:42","30-01-2025 20:10=
:42","Active//No power issue on site,site on Gen with Ubaie=3D52.1 V The TX=
 FME Lionnel//694693436 From Huawei is informed","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site,site on Gen with Ubaie=3D52.1 V The TX FME L=
ionnel//694693436 From Huawei is informed","dorothy.djantio@ihstowers.com",=
"305","30-01-2025 16:05:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004215777","Barriere=
 IHS","","30-01-2025 16:05:10","30-01-2025 15:59:05","30-01-2025 16:01:05",=
"Cascaded Incident from TTO4231379","Hyemafo Gildas","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID =
, Ubaie=3D54.V site On Grid The Tx FME Fulbert(654266068) from Huawei is in=
formed..","system","1252083","30-01-2025 16:05:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004215747","M=
efou-Assi","IHS_YND_696","30-01-2025 16:04:13","30-01-2025 15:59:05","30-01=
-2025 16:01:05","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On=
 Grid The Tx FME Fulbert(654266068) from Huawei is informed..","Fanda Brice=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Gr=
id The Tx FME Fulbert(654266068) from Huawei is informed..","dorothy.djanti=
o@ihstowers.com","309","30-01-2025 16:04:13","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004215471","Pha=
rmacie SION","","30-01-2025 15:19:57","30-01-2025 15:15:52","30-01-2025 15:=
26:05","Grid outage, site went down before gen start due to poor battery ba=
ckup // gen start automatically","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // gen start automatically","l=
udivine.ngamaleu@ihstowers.com","246","30-01-2025 15:19:57","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004215460","Ema=
na","","30-01-2025 15:17:47","30-01-2025 15:10:43","30-01-2025 15:22:43","G=
rid outage, site went down before gen start due to poor battery backup // g=
en start automatically","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // gen start automatically","ludivi=
ne.ngamaleu@ihstowers.com","425","30-01-2025 15:17:47","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004215374","SIM=
BOCK BONAMBAPE","","30-01-2025 15:07:36","30-01-2025 15:00:31","30-01-2025 =
17:28:24","Site went down due to inssufficiency of rectifier causing by 02/=
08 rctifier faulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","Hyem=
afo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to inssufficiency of rectifier causing by 02/08 rctifier f=
aulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","ludivine.ngamaleu=
@ihstowers.com","426","30-01-2025 15:07:36","Sagemcom CMR"
"Closed Complete","Warning","CTR_201","IHS_YND_368","NOCINC0004215289","Ote=
le","","30-01-2025 14:51:56","","","Site on Gen due to Grid outage )Site al=
arming because site on battery and  Grid restored but the grid contactor no=
 existed     //He blocked Grid Contactor, Site on Grid","Fanda Brice","Warn=
ing","Warning","POWER","Warning - Site on Battery","Site on Gen due to Grid=
 outage )Site alarming because site on battery and  Grid restored but the g=
rid contactor no existed     //He blocked Grid Contactor, Site on Grid","ol=
ivier.kwedi@ihstowers.com","3","30-01-2025 14:51:56","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004215133","SOA=
 UNIVERSITY STADIUM","","30-01-2025 14:39:08","30-01-2025 14:36:08","30-01-=
2025 16:17:33","Grid outage ,site went down because Gen fails to start due =
to Gen stop mode //He stated Gen manually(investigation ongoing)","Siligap =
Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage ,site went down because Gen fails to start due to Gen stop mode //H=
e stated Gen manually(investigation ongoing)","ludivine.ngamaleu@ihstowers.=
com","429","30-01-2025 14:39:08","Sagemcom CMR"
"Closed Complete","Site Down","T0209","IHS_YND_197","NOCINC0004215131","Pal=
ais Des Congres","","30-01-2025 14:38:26","30-01-2025 14:34:19","30-01-2025=
 14:56:53","No  power issue on site U=3D54,7v site on gen Team DJIOMAGUE/67=
8131047/ I-Engineering working on site","Mboua Thierry","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No  pow=
er issue on site U=3D54,7v site on gen Team DJIOMAGUE/678131047/ I-Engineer=
ing working on site","ludivine.ngamaleu@ihstowers.com","248","30-01-2025 14=
:38:26","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004214951","Fou=
da Quarter","","30-01-2025 14:13:08","30-01-2025 14:10:48","30-01-2025 16:0=
7:17","Site went down due to insuffience of rectifiers (03) on site SS IHS =
Blaise Raoul is on informed// Site stabilized","Delor Telezing","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down due to ins=
uffience of rectifiers (03) on site SS IHS Blaise Raoul is on informed// Si=
te stabilized","ludivine.ngamaleu@ihstowers.com","141","30-01-2025 14:13:08=
","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0004214937","Nko=
abang Ebolmedjock","","30-01-2025 14:11:22","30-01-2025 14:03:37","30-01-20=
25 16:01:59","Site went down because Gen stopped due to fuel filter gasket =
faulty // He replaced the fuel filter gasket and Gen Manually started","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Filter"=
,"Site went down because Gen stopped due to fuel filter gasket faulty // He=
 replaced the fuel filter gasket and Gen Manually started","ludivine.ngamal=
eu@ihstowers.com","1930","30-01-2025 14:11:22","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004214870","ETO=
UDI Entree du palais","","30-01-2025 13:58:48","30-01-2025 13:51:38","30-01=
-2025 15:16:14","Grid outage,gen ran till fuel shortage//Refueling done","F=
abrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge,gen ran till fuel shortage//Refueling done","kamga.virgile@ihstowers.com=
","431","30-01-2025 13:58:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004214368","N=
kolfon Cimencam","","30-01-2025 12:41:16","30-01-2025 12:07:03","30-01-2025=
 12:55:42","Grid outage,gen failed to start due to static charger faulty// =
Grid return (Static charger to be replaced)","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Charging Alternator","Grid outage,gen fa=
iled to start due to static charger faulty// Grid return (Static charger to=
 be replaced)","alexandre.kamal@ihstowers.com","2054","30-01-2025 12:41:16"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004212703","L=
abogenie","","30-01-2025 10:04:46","30-01-2025 09:49:37","30-01-2025 09:55:=
44","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou =
(693212405 )from Huawei is informed. Notice that it is the repetitive issue=
 ","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","ACTIVE//No  power issue U =3D54,5V site on Grid. The Tx F=
ME  Eloundou (693212405 )from Huawei is informed. Notice that it is the rep=
etitive issue ","alexandre.kamal@ihstowers.com","911","30-01-2025 10:04:46"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004212480","Fou=
da Quarter","","30-01-2025 09:29:34","30-01-2025 09:17:24","30-01-2025 09:2=
5:07","ACTIVE//No power issue on site Ubaie=3D54.6V site on Grid, The TX FM=
E Armand Nguetsa  from Huawei (699949553) is informed","Delor Telezing","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","ACTIVE//No power issue on site Ubaie=3D54.6V site on Grid, The TX =
FME Armand Nguetsa  from Huawei (699949553) is informed","kamga.virgile@ihs=
towers.com","731","30-01-2025 09:29:34","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004212044","Nsi=
meyong Terre Rouge","","30-01-2025 08:18:46","30-01-2025 08:14:51","30-01-2=
025 08:26:41","Grid outage, Site went down before gen start due to poor bat=
tery backup // Gen start automatically","MINKA NICOLAS","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site =
went down before gen start due to poor battery backup // Gen start automati=
cally","kamga.virgile@ihstowers.com","236","30-01-2025 08:18:46","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004211973","SOA VILL=
AGE","","30-01-2025 08:03:11","30-01-2025 07:59:11","30-01-2025 08:27:41","=
Cascaded Incident from TTO4227052","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because Gen failed t=
o start due to grid bad voltage an No RCP on site  // He bypass the Grid an=
d Gen manually started","system","266621","30-01-2025 08:03:11","Sagemcom C=
MR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004211971","SOA=
 TOWN","IHS_YND_323","30-01-2025 08:02:26","30-01-2025 07:59:11","30-01-202=
5 08:27:41","Site went down because Gen failed to start due to grid bad vol=
tage an No RCP on site  // He bypass the Grid and Gen manually started","Si=
ligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Site went down because Gen failed to start due to grid bad volt=
age an No RCP on site  // He bypass the Grid and Gen manually started","kam=
ga.virgile@ihstowers.com","196","30-01-2025 08:02:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004211806","M=
EFOU ASSI","","30-01-2025 07:34:05","30-01-2025 07:03:59","30-01-2025 07:10=
:03","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The T=
x FME Fulbert(654266068) from Huawei is informed..","Fanda Brice","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE//No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx F=
ME Fulbert(654266068) from Huawei is informed..","alexandre.kamal@ihstowers=
.com","1807","30-01-2025 07:34:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004211288","M=
ontee-Des-Soeurs","","30-01-2025 05:31:10","30-01-2025 03:55:02","30-01-202=
5 05:35:03","No power Issue Site on Grid Ubai =3D54.3 V, The FME The TX FME=
 Mbah Hosiah (674007438) is informed.","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r Issue Site on Grid Ubai =3D54.3 V, The FME The TX FME Mbah Hosiah (674007=
438) is informed.","christian.fonkou@ihstowers.com","5769","30-01-2025 05:3=
1:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004211287","N=
kolfon Cimencam","","30-01-2025 05:30:26","30-01-2025 04:40:18","30-01-2025=
 04:45:44","No power issue site on Grid Ubaie =3D54.5 V, The FME The RM Ala=
in (691144423) is informed.","Hyemafo Gildas","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on Grid Ubaie =3D54.5 V, The FME The RM Alain (691144423) is informed.",=
"christian.fonkou@ihstowers.com","3009","30-01-2025 05:30:26","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004211010","D=
ong","","30-01-2025 04:08:24","30-01-2025 03:59:16","30-01-2025 03:59:17","=
Active: No power issue, site on Battery With Ubaie=3D50,3V, The Tx FME Greg=
oire (654547479) from Huawei is informed.","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: No power issue, site on Battery With Ubaie=3D50,3V, The Tx FME Gregoire=
 (654547479) from Huawei is informed.","christian.fonkou@ihstowers.com","54=
9","30-01-2025 04:08:24","Sagemcom CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0004211006","Av-=
Germaine","","30-01-2025 04:05:24","30-01-2025 04:02:43","31-01-2025 16:54:=
49","Grid Outage No Space To deploy a MDG //Grid Restored","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space=
 To deploy a MDG //Grid Restored","emmanuel.ghani@ihstowers.com","161","30-=
01-2025 04:05:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004210917","Yoko MTN=
","","30-01-2025 03:46:41","30-01-2025 03:44:02","30-01-2025 03:44:03","Cas=
caded Incident from TTO4225843","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue site on gen with U=
=3D54v Gregoire/652070658/ from Huawei is informed site up at 03:46 AM","sy=
stem","267529","30-01-2025 03:46:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004210915","Matsari"=
,"","30-01-2025 03:46:41","30-01-2025 03:44:02","30-01-2025 03:44:03","Casc=
aded Incident from TTO4225843","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue site on gen with U=
=3D54v Gregoire/652070658/ from Huawei is informed site up at 03:46 AM","sy=
stem","267528","30-01-2025 03:46:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004210914","MBIMBIM"=
,"","30-01-2025 03:46:41","30-01-2025 03:44:02","30-01-2025 03:44:03","Casc=
aded Incident from TTO4225843","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue site on gen with U=
=3D54v Gregoire/652070658/ from Huawei is informed site up at 03:46 AM","sy=
stem","267529","30-01-2025 03:46:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004210916","Ngoum","=
","30-01-2025 03:46:41","30-01-2025 03:44:02","30-01-2025 03:44:03","Cascad=
ed Incident from TTO4225843","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue site on gen with U=3D=
54v Gregoire/652070658/ from Huawei is informed site up at 03:46 AM","syste=
m","267528","30-01-2025 03:46:41","Sagemcom CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0004210912","Ngo=
uetou","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_473","30-01-2025 03:=
45:25","30-01-2025 03:44:02","30-01-2025 04:00:03","Active//No power issue =
site on gen with U=3D54v Gregoire/652070658/ from Huawei is informed ","Par=
ker Tchoup","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue site on gen with U=3D54v Gre=
goire/652070658/ from Huawei is informed site up at 03:46 AM","emmanuel.gha=
ni@ihstowers.com","84","30-01-2025 03:45:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004210708","Barriere=
 IHS","","30-01-2025 02:05:01","30-01-2025 01:54:20","30-01-2025 01:54:21",=
"Cascaded Incident from TTO4225597","Hyemafo Gildas","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID =
, Ubaie=3D54.V site On Grid The Tx FME Fulbert(654266068) from Huawei is in=
formed..","system","274170","30-01-2025 02:05:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0004210707","MEFOU AS=
SI","","30-01-2025 02:05:00","30-01-2025 01:54:20","30-01-2025 01:54:21","C=
ascaded Incident from TTO4225597","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE//No power issue on site GRID , Uba=
ie=3D54.V site On Grid The Tx FME Fulbert(654266068) from Huawei is informe=
d..","system","274170","30-01-2025 02:05:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004210700","M=
efou-Assi","IHS_YND_537, IHS_YND_696","30-01-2025 02:00:29","30-01-2025 01:=
54:20","30-01-2025 01:54:21","ACTIVE//No power issue on site GRID , Ubaie=
=3D54.V site On Grid The Tx FME Fulbert(654266068) from Huawei is informed.=
.","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","ACTIVE//No power issue on site GRID , Ubaie=3D=
54.V site On Grid The Tx FME Fulbert(654266068) from Huawei is informed..",=
"christian.fonkou@ihstowers.com","370","30-01-2025 02:00:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0004210489","NGONA","=
","30-01-2025 01:05:30","30-01-2025 00:53:18","30-01-2025 00:53:19","Cascad=
ed Incident from TTO4225338","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// no power issue on site; U=3D54V =
ON GRID Emmanuel SONKOUE/694567096/ From SNEF is working on site (Upgrade 1=
0G_CorEvo)","system","263233","30-01-2025 01:05:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0004210490","Nkoabang=
2","","30-01-2025 01:05:30","30-01-2025 00:53:18","30-01-2025 00:53:19","Ca=
scaded Incident from TTO4225338","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active// no power issue on site; U=3D=
54V ON GRID Emmanuel SONKOUE/694567096/ From SNEF is working on site (Upgra=
de 10G_CorEvo)","system","263233","30-01-2025 01:05:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0004210478","N=
koabang","IHS_YND_295, IHS_YND_526","30-01-2025 01:01:26","30-01-2025 00:53=
:18","30-01-2025 01:23:19","Active// no power issue on site; U=3D54V ON GRI=
D Emmanuel SONKOUE/694567096/ From SNEF is working on site (Upgrade 10G_Cor=
Evo)","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active// no power issue on site; U=3D5=
4V ON GRID Emmanuel SONKOUE/694567096/ From SNEF is working on site (Upgrad=
e 10G_CorEvo)","christian.fonkou@ihstowers.com","488","30-01-2025 01:01:26"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004210267","EMA=
NA BILICK CITY","","30-01-2025 00:05:33","30-01-2025 00:01:23","30-01-2025 =
02:00:24","No power issue site on gen with U=3D54v Symphorien from Huawei i=
s informed","Fabrice Pouakam","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue site on gen with U=
=3D54v Symphorien from Huawei is informed","emmanuel.ghani@ihstowers.com","=
252","30-01-2025 00:05:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0004210227","NYOM 2 I=
HS","","29-01-2025 23:51:10","29-01-2025 23:47:36","30-01-2025 00:07:14","C=
ascaded Incident from TTO4225037","Fabrice Pouakam","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site Ubaie 53,3V Si=
te on Grid. Guy Roger KENTO(675251183/OMNIACOM) is on site for SWAP, sympho=
rien (691316854/Huawei) is informed","system","267224","29-01-2025 23:51:10=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0004210115","Nkolkoum=
ou OCM","","29-01-2025 23:29:10","29-01-2025 23:24:24","30-01-2025 00:22:24=
","Cascaded Incident from TTO4224914","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","site went down becaus=
e gen failed to start due to Eneo contactor faulty // He bypassed Eneo cont=
actor, site on grid","system","268625","29-01-2025 23:29:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0004210111","N=
kolbisson usine des eaux","IHS_YND_712","29-01-2025 23:26:28","29-01-2025 2=
3:24:24","30-01-2025 00:22:24","site went down because gen failed to start =
due to Eneo contactor faulty // He bypassed Eneo contactor, site on grid","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","ATS=
-AMF Issue","site went down because gen failed to start due to Eneo contact=
or faulty // He bypassed Eneo contactor, site on grid","christian.fonkou@ih=
stowers.com","125","29-01-2025 23:26:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004209637","C=
RH-Etoug-Ebe","","29-01-2025 21:34:07","29-01-2025 21:24:59","29-01-2025 21=
:30:00","Active: no power issue, site is on grid with Ubaie=3D53V, Mohamado=
u(691144435) from Huawei is informed,  Notice that we have disjunction in O=
CM equipment","Hyemafo Gildas","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, site is =
on grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei is informed,  No=
tice that we have disjunction in OCM equipment","rouselle.schoune@ihstowers=
.com","549","29-01-2025 21:34:07","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004209207","OBA=
M NGOLA OCM","","29-01-2025 20:35:17","29-01-2025 20:20:11","29-01-2025 20:=
38:11","Site went down because rectifiers disfunctionning// He reset rectif=
iers","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","Site went down because rectifiers disfunctionning// He reset rectif=
iers","ange.kongo@ihstowers.com","907","29-01-2025 20:35:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0004209200","Nkolo II=
 New","","29-01-2025 20:34:21","29-01-2025 20:03:00","29-01-2025 21:06:09",=
"Cascaded Incident from TTO4223781","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to high temp=
eratures caused by the air conditioner shutting down due to  eneo bad volta=
ge // He opened the shelter door","system","280670","29-01-2025 20:34:21","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0004209201","Biteng",=
"","29-01-2025 20:34:21","29-01-2025 20:03:00","29-01-2025 21:06:09","Casca=
ded Incident from TTO4223781","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to high temperatur=
es caused by the air conditioner shutting down due to  eneo bad voltage // =
He opened the shelter door","system","280670","29-01-2025 20:34:21","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_792","NOCINC0004209199","NKOABANG=
 NKOLO 3","","29-01-2025 20:34:21","29-01-2025 20:03:00","29-01-2025 21:06:=
09","Cascaded Incident from TTO4223781","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to high =
temperatures caused by the air conditioner shutting down due to  eneo bad v=
oltage // He opened the shelter door","system","280673","29-01-2025 20:34:2=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0004209198","Nkoabang=
2","","29-01-2025 20:34:21","29-01-2025 20:03:00","29-01-2025 21:06:09","Ca=
scaded Incident from TTO4223781","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to high tempera=
tures caused by the air conditioner shutting down due to  eneo bad voltage =
// He opened the shelter door","system","280672","29-01-2025 20:34:21","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0004209197","Biteng-M=
aetur","","29-01-2025 20:34:20","29-01-2025 20:03:00","29-01-2025 21:06:09"=
,"Cascaded Incident from TTO4223781","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to high tem=
peratures caused by the air conditioner shutting down due to  eneo bad volt=
age // He opened the shelter door","system","280672","29-01-2025 20:34:20",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0004209195","NGONA","=
","29-01-2025 20:34:20","29-01-2025 20:03:00","29-01-2025 21:06:09","Cascad=
ed Incident from TTO4223781","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to high temperature=
s caused by the air conditioner shutting down due to  eneo bad voltage // H=
e opened the shelter door","system","280673","29-01-2025 20:34:20","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004209196","Mimboman=
4","","29-01-2025 20:34:20","29-01-2025 20:03:00","29-01-2025 21:06:09","Ca=
scaded Incident from TTO4223781","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to high tempera=
tures caused by the air conditioner shutting down due to  eneo bad voltage =
// He opened the shelter door","system","280671","29-01-2025 20:34:20","Sag=
emcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004209187","Nko=
abang MTN","IHS_YND_295, IHS_YND_266, IHS_YND_249, IHS_YND_526, IHS_YND_792=
, IHS_YND_709, IHS_YND_248","29-01-2025 20:32:05","29-01-2025 20:03:00","29=
-01-2025 21:06:09","Site went down due to high temperatures caused by the a=
ir conditioner shutting down due to  eneo bad voltage // He opened the shel=
ter door","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Site went down due to high temperatures caused =
by the air conditioner shutting down due to  eneo bad voltage // He opened =
the shelter door","ange.kongo@ihstowers.com","1746","29-01-2025 20:32:05","=
Sagemcom CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0004209173","Eto=
ug ebe Meweulo","","29-01-2025 20:26:56","29-01-2025 20:03:45","29-01-2025 =
20:10:26","Active//No power issue on site Ubaie=3D54   V site on Grid The  =
RM Martial//650 252214 is informed ","Hyemafo Gildas","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue on site Ubaie=3D54   V site on Grid The  RM Martial//650 2522=
14 is informed ","ange.kongo@ihstowers.com","1392","29-01-2025 20:26:56","S=
agemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004208973","Nko=
abang entree carriere","","29-01-2025 19:56:14","29-01-2025 19:29:01","30-0=
1-2025 01:10:40","no power issue on site ,site on Grid with Ubaie=3D53.5 V =
The Tx FME Eloudou//693212405 from Huawei is informed","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","no power issue on site ,site on Grid with Ubaie=3D53.5 V The Tx =
FME Eloudou//693212405 from Huawei is informed","ange.kongo@ihstowers.com",=
"1634","29-01-2025 19:56:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004208940","N=
yom OCM","","29-01-2025 19:48:29","29-01-2025 19:44:24","29-01-2025 20:28:3=
5","site went down because Gen fails to start  due to Grid bad voltage and =
no RCP on site // HE bypassed Grid and Gen manually started","Fabrice Pouak=
am","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","site went down because Gen fails to start  due to Grid bad voltage and n=
o RCP on site // HE bypassed Grid and Gen manually started","rouselle.schou=
ne@ihstowers.com","246","29-01-2025 19:48:29","Sagemcom CMR"
"Closed Complete","Warning","T0046","IHS_YND_191","NOCINC0004208917","Mball=
a II","","29-01-2025 19:43:47","","","Site alarming because site on battery=
  due grid outage //Gen started automatically","Delor Telezing","Warning","=
Warning","POWER","Warning - Site on Battery","Site alarming because site on=
 battery  due grid outage //Gen started automatically","adonis.defokoua@ihs=
towers.com","436","29-01-2025 19:43:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004208802","K=
oweit City","","29-01-2025 19:24:00","29-01-2025 19:19:55","29-01-2025 20:5=
6:45","Site went down due to insufficient rectifier on site due to charge i=
ncrease SS IHS Pascaline confirmed // site stabilised he need to add 01 rec=
tifier","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down due to insufficient rectifier on site due to charg=
e increase SS IHS Pascaline confirmed // site stabilised he need to add 01 =
rectifier","rouselle.schoune@ihstowers.com","246","29-01-2025 19:24:00","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004208768","Mon=
tee Jouvence","","29-01-2025 19:19:28","29-01-2025 19:13:20","29-01-2025 20=
:44:55","Grid outage site went down because Gen stopped with alarm high tem=
p //He added water and Gen manually started","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue",=
"Grid outage site went down because Gen stopped with alarm high temp //He a=
dded water and Gen manually started","ange.kongo@ihstowers.com","369","29-0=
1-2025 19:19:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004208695","S=
calom","","29-01-2025 19:00:55","29-01-2025 18:58:41","29-01-2025 20:21:17"=
,"site went down due to Rectifier Issues SS IHS Francois is Informed and Co=
nfirmed it//Site Stablized","Paul BIBOUM","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","site went down due to Rectifier Issues SS IHS F=
rancois is Informed and Confirmed it//Site Stablized","rouselle.schoune@ihs=
towers.com","135","29-01-2025 19:00:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004208685","S=
IMBOCK BONAMBAPE","","29-01-2025 18:58:50","29-01-2025 18:49:59","29-01-202=
5 20:00:13","Site went down due to inssufficiency of rectifier causing by 0=
2/08 rectifier faulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","H=
yemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to inssufficiency of rectifier causing by 02/08 rectifi=
er faulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","rouselle.scho=
une@ihstowers.com","531","29-01-2025 18:58:50","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004208587","Awa=
e Ewonkan","","29-01-2025 18:35:56","29-01-2025 18:25:59","29-01-2025 19:14=
:34","Site went down because CB(2*63 A)  disjuncted in PWC  due to increase=
 load on site /He reamed CB","Albran Byorel","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down beca=
use CB(2*63 A)  disjuncted in PWC  due to increase load on site /He reamed =
CB","ange.kongo@ihstowers.com","598","29-01-2025 18:35:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004208583","SOA VILL=
AGE","","29-01-2025 18:35:11","29-01-2025 18:26:30","29-01-2025 18:53:24","=
Cascaded Incident from TTO4223089","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, site went down due to =
gen overload(13KVA,170A) // grid return","system","286433","29-01-2025 18:3=
5:11","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004208533","NKO=
MEKUI OCM","","29-01-2025 18:24:33","29-01-2025 18:17:11","29-01-2025 23:19=
:57","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted b=
y Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site U=3D54.5 V site on Gen.Site impacted =
by Mbankolo Camtel and not managing by IHS","ange.kongo@ihstowers.com","443=
","29-01-2025 18:24:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004208429","S=
OA TOWN","IHS_YND_323","29-01-2025 18:01:14","29-01-2025 17:58:07","29-01-2=
025 18:53:24","grid outage, site went down due to gen overload(13KVA,170A) =
SS IHS BLAISE RAOUL is informed // grid return","Siligap Boris","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","grid outage, site went down=
 due to gen overload(13KVA,170A) // grid return","rouselle.schoune@ihstower=
s.com","188","29-01-2025 18:01:14","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004208413","MEF=
OU ASSI","","29-01-2025 17:56:28","29-01-2025 17:54:09","29-01-2025 20:20:5=
5","Active//No power issue on site Ubaie=3D52.4 V site on Grid  The Tx FME =
Fulbert(654266068) from Huawei is informed..","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue on site Ubaie=3D52.4 V site on Grid  The Tx FME Fulbert=
(654266068) from Huawei is informed..","ange.kongo@ihstowers.com","141","29=
-01-2025 17:56:28","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004208409","BIY=
EMASSI NIKI","","29-01-2025 17:55:57","29-01-2025 17:49:52","29-01-2025 18:=
16:59","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d, F=E9lix Zambe is informed and confirmed","Hyemafo Gildas","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Site went down du=
e to PWC overloaded (12kva 250 A) //Site stabilized, F=E9lix Zambe is infor=
med and confirmed","rouselle.schoune@ihstowers.com","365","29-01-2025 17:55=
:57","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004208399","SIM=
BOCK BONAMBAPE","","29-01-2025 17:55:01","29-01-2025 17:06:54","29-01-2025 =
18:10:18","Site went down due to inssufficiency of rectifier causing by 02/=
08 rctifier faulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","Hyem=
afo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down due to inssufficiency of rectifier causing by 02/08 rctifier f=
aulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","ange.kongo@ihstow=
ers.com","2888","29-01-2025 17:55:01","Sagemcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0004208368","ODZ=
A BORNE 10","","29-01-2025 17:45:28","29-01-2025 17:35:59","29-01-2025 19:5=
3:32","No power issue on site Ubaie =3D54,3V site on Grid   The TX FME Lion=
el //655184876//  from huawei is informed.","Albran Byorel","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site Ubaie =3D54,3V site on Grid   The TX FME Lionel //65518=
4876//  from huawei is informed.","ange.kongo@ihstowers.com","570","29-01-2=
025 17:45:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004208340","O=
dza II OCM","","29-01-2025 17:38:02","29-01-2025 17:30:55","29-01-2025 17:5=
6:41","Grid outage, Site went down before gen start due to poor battery bac=
kup // Gen start automatically","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n before gen start due to poor battery backup // Gen start automatically","=
rouselle.schoune@ihstowers.com","429","29-01-2025 17:38:02","Sagemcom CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004208097","Meh=
anda 1","","29-01-2025 17:10:34","29-01-2025 16:58:22","29-01-2025 17:56:34=
","Grid outage, site went down because Gen stopped with 'Over-Voltage' alar=
m // He reset the Gen card and Gen manually started","Albran Byorel","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site=
 went down because Gen stopped with 'Over-Voltage' alarm // He reset the Ge=
n card and Gen manually started","ange.kongo@ihstowers.com","733","29-01-20=
25 17:10:34","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004207534","Tou=
ring Club International","","29-01-2025 16:28:07","29-01-2025 16:03:02","29=
-01-2025 18:10:54"," Site went down due to CB (125A) Disjunted in the DC-Bo=
x because  the Load Increase //He reamed the CB(125A)","Albran Byorel","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker I=
ssue"," Site went down due to CB (125A) Disjunted in the DC-Box because  th=
e Load Increase //He reamed the CB(125A)","ange.kongo@ihstowers.com","1506"=
,"29-01-2025 16:28:07","Sagemcom CMR"
"Closed Complete","Warning","CTR_201","IHS_YND_368","NOCINC0004207533","Ote=
le","","29-01-2025 16:28:06","","","Site on Gen due to Grid outage )Site al=
arming because site on battery and  Grid restored but the grid contactor no=
 existed     //He blocked Grid Contactor, Site on Grid","Fanda Brice","Warn=
ing","Warning","POWER","Warning - Site on Battery","Site on Gen due to Grid=
 outage )Site alarming because site on battery and  Grid restored but the g=
rid contactor no existed     //He blocked Grid Contactor, Site on Grid","ad=
onis.defokoua@ihstowers.com","486","29-01-2025 16:28:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004207513","MEHANDAN=
","","29-01-2025 16:25:20","29-01-2025 16:09:21","29-01-2025 17:13:26","Gri=
d outage, site went down because Gen stopped with 'Over-Voltage' alarm // H=
e reset the Gen card and Gen manually started","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went =
down because Gen stopped with 'Over-Voltage' alarm // He reset the Gen card=
 and Gen manually started","system","5531","29-01-2025 16:25:20","Sagemcom =
CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004207511","Nko=
lnda","","29-01-2025 16:24:40","29-01-2025 16:14:59","29-01-2025 17:10:31",=
"Grid Outage Site went down due to CB (125A) Disjunted in the DC-Box becaus=
e  poor battery backup //He reamed the CB(125A)","Albran Byorel","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue",=
"Grid Outage Site went down due to CB (125A) Disjunted in the DC-Box becaus=
e  poor battery backup //He reamed the CB(125A)","ange.kongo@ihstowers.com"=
,"582","29-01-2025 16:24:40","Sagemcom CMR"
"Closed Complete","Warning","CTR_339","IHS_YND_073","NOCINC0004207502","Cha=
pelle-Obili","","29-01-2025 16:20:50","","","Site alarming because Site on =
battery due to Grid outage //Gen started automatically","Paul BIBOUM","Warn=
ing","Warning","POWER","Warning - Site on Battery","Site alarming because S=
ite on battery due to Grid outage //Gen started automatically","adonis.defo=
koua@ihstowers.com","498","29-01-2025 16:20:50","Sagemcom CMR"
"Closed Complete","Warning","T0322","IHS_YND_312","NOCINC0004207467","Nkoln=
da","","29-01-2025 16:14:21","","","Site alarming because site on battery d=
ue to Grid outage and  poor battery backup //Gen started automatically","Al=
bran Byorel","Warning","Warning","POWER","Warning - Site on Battery","Site =
alarming because site on battery due to Grid outage and  poor battery backu=
p //Gen started automatically","adonis.defokoua@ihstowers.com","488","29-01=
-2025 16:14:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004207452","O=
bobogo","","29-01-2025 16:11:45","29-01-2025 16:09:35","29-01-2025 16:11:05=
","Grid outage, Site went down before Gen start due to poor backup// Gen st=
arted automatically","MINKA NICOLAS","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// Gen started automatically","rouselle.schoune@i=
hstowers.com","131","29-01-2025 16:11:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0004207168","M=
atomb","","29-01-2025 15:26:03","29-01-2025 15:24:00","29-01-2025 16:23:41"=
,"Site went down due to High temp causing by  contactor Aircon HS //He repl=
aced by CB(2*32 A) ,site on Grid ","Kemeni Franklin","Equipment Repair","Pa=
ssive","Environmental","Aircon Contactor Faulty","Site went down due to Hig=
h temp causing by  contactor Aircon HS //He replaced by CB(2*32 A) ,site on=
 Grid ","rouselle.schoune@ihstowers.com","124","29-01-2025 15:26:03","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004207151","S=
IMBOCK BONAMBAPE","","29-01-2025 15:23:31","29-01-2025 15:11:23","29-01-202=
5 15:56:48","Site went down due to inssufficiency of rectifier causing by 0=
2/08 rctifier faulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","Hy=
emafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down due to inssufficiency of rectifier causing by 02/08 rctifier=
 faulty SS IHS Felix Zamb=E9 confirmed // Site stabilized","rouselle.schoun=
e@ihstowers.com","729","29-01-2025 15:23:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0004207032","N=
goum","","29-01-2025 15:05:52","29-01-2025 14:35:44","29-01-2025 17:18:53",=
"Active//No Power issue on site , site on Gen with Ubaie=3D52.7V The Tx Gre=
goire(654547479) from Huawei is informed","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No Power issue on site , site on Gen with Ubaie=3D52.7V The Tx Gregoire(=
654547479) from Huawei is informed","rouselle.schoune@ihstowers.com","1810"=
,"29-01-2025 15:05:52","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004206581","NYO=
M FACE MAETUR","","29-01-2025 13:34:54","29-01-2025 13:31:48","29-01-2025 1=
6:11:52","Site on Gen due to Grid outage ,site went down because Gen  conta=
ctor dysfonction // He excited Gen contactor ,site on Gen ","Fabrice Pouaka=
m","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Site on=
 Gen due to Grid outage ,site went down because Gen  contactor dysfonction =
// He excited Gen contactor ,site on Gen ","ludivine.ngamaleu@ihstowers.com=
","187","29-01-2025 13:34:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004206544","N=
YOM 2 IHS","","29-01-2025 13:28:10","29-01-2025 13:24:05","29-01-2025 14:53=
:51","Grid outage site went Gen ran until fuel shortage //Refueling done","=
Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age site went Gen ran until fuel shortage //Refueling done","dorothy.djanti=
o@ihstowers.com","246","29-01-2025 13:28:10","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004206496","BIY=
EMASSI NIKI","","29-01-2025 13:21:26","29-01-2025 13:19:19","29-01-2025 13:=
31:44","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d, F=E9lix Zambe is informed and confirmed","Hyemafo Gildas","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Site went down du=
e to PWC overloaded (12kva 250 A) //Site stabilized, F=E9lix Zambe is infor=
med and confirmed","ludivine.ngamaleu@ihstowers.com","128","29-01-2025 13:2=
1:26","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004206482","Nko=
ulou Carriere carrefourt","","29-01-2025 13:18:59","29-01-2025 13:12:52","2=
9-01-2025 13:12:53","Active//No power issue on site U=3D51.1 V Site on Grid=
 Team djoukou/Eiingennerring/ 676576280/ working on site( Installation New =
RRH)","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active//No power issue on site U=3D51.=
1 V Site on Grid Team djoukou/Eiingennerring/ 676576280/ working on site( I=
nstallation New RRH)","ludivine.ngamaleu@ihstowers.com","368","29-01-2025 1=
3:18:59","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004205360","Tou=
ring Club International","","29-01-2025 10:48:40","29-01-2025 10:43:35","29=
-01-2025 11:56:58","Active//No power issue on site U=3D54,1V site on Grid T=
eam djoukou/Eiingennerring/ 676576280/ working on site( Installation New RR=
H)","Albran Byorel","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active//No power issue on site U=3D54,1V si=
te on Grid Team djoukou/Eiingennerring/ 676576280/ working on site( Install=
ation New RRH)","ludivine.ngamaleu@ihstowers.com","306","29-01-2025 10:48:4=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_015","NOCINC0004205275","H-ville"=
,"","29-01-2025 10:33:31","29-01-2025 10:23:03","29-01-2025 12:06:34","Casc=
aded Incident from TTO4219195","Paul BIBOUM","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Gen faulty (PM was ongoing).=
 // Grid returned.","system","272327","29-01-2025 10:33:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004205090","M=
EFOU ASSI","","29-01-2025 10:03:33","29-01-2025 10:02:29","29-01-2025 11:10=
:44","No power issue on site U=3D52,1v site on grid tx fme Fulbert 65426606=
8 of Huawei is informed","Fanda Brice","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D52,1v site on grid tx fme Fulbert 654266068 of Huawei is informed","doro=
thy.djantio@ihstowers.com","66","29-01-2025 10:03:33","Sagemcom CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0004205026","Av-=
Germaine","","29-01-2025 09:49:47","29-01-2025 09:46:29","29-01-2025 19:11:=
34","Grid outage, No space to deploy a MDG // Grid Restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No sp=
ace to deploy a MDG // Grid Restored","ludivine.ngamaleu@ihstowers.com","19=
9","29-01-2025 09:49:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0004204961","Sapeur",=
"","29-01-2025 09:39:30","29-01-2025 08:53:13","29-01-2025 10:05:44","Casca=
ded Incident from TTO4218313","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage,no space to deploy a mobil g=
en//grid retrun","system","277715","29-01-2025 09:39:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0004204474","E=
-Police","","29-01-2025 09:00:44","29-01-2025 08:53:13","29-01-2025 10:05:4=
4","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Gr=
id outage,no space to deploy a mobil gen//grid retrun","dorothy.djantio@ihs=
towers.com","277714","29-01-2025 09:00:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_323","IHS_YND_043","NOCINC0004204470","E=
mia","IHS_YND_030, IHS_YND_029","29-01-2025 08:59:17","29-01-2025 08:53:13"=
,"29-01-2025 10:06:59","Grid outage,no space to deploy a mobil gen//grid re=
trun","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"Grid outage,no space to deploy a mobil gen//grid retrun","dorothy.djantio=
@ihstowers.com","365","29-01-2025 08:59:17","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004204458","Fou=
da Quarter","","29-01-2025 08:55:03","29-01-2025 08:50:55","29-01-2025 10:3=
0:30","No power issue on site Ubaie=3D54.6V site on Grid, The TX FME Armand=
 Nguetsa  from Huawei (699949553) is informed","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site Ubaie=3D54.6V site on Grid, The TX FME Armand Nguet=
sa  from Huawei (699949553) is informed","ludivine.ngamaleu@ihstowers.com",=
"249","29-01-2025 08:55:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004204028","L=
abogenie","","29-01-2025 07:18:27","29-01-2025 07:14:20","29-01-2025 07:31:=
08","No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (6932124=
05 )from Huawei is informed. Notice that it is the repetitive issue ","","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No  power issue U =3D54,5V site on Grid. The Tx FME  Eloundou (69=
3212405 )from Huawei is informed. Notice that it is the repetitive issue ",=
"dorothy.djantio@ihstowers.com","248","29-01-2025 07:18:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0004203968","H=
-Prince","","29-01-2025 07:06:09","29-01-2025 07:04:05","29-01-2025 07:25:2=
2","No power issue on site U=3D54.7V site on GRID. Tx FME Brice (650214096)=
 from Huawei is informed","Mboua Thierry","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54.7V site on GRID. Tx FME Brice (650214096) from Huawei is informed"=
,"dorothy.djantio@ihstowers.com","125","29-01-2025 07:06:09","Sagemcom CMR"
"Closed Complete","Site Down","T1850","IHS_YND_376","NOCINC0004203804","Mam=
b","","29-01-2025 06:23:30","29-01-2025 06:18:04","29-01-2025 07:56:58","Gr=
id outage,site went down because gen start and stopped due to alarm emergen=
cy stop//he reset it and started the gen","Kemeni Franklin","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Emergency Stop","Grid outage,site went dow=
n because gen start and stopped due to alarm emergency stop//he reset it an=
d started the gen","ludivine.ngamaleu@ihstowers.com","548","29-01-2025 06:2=
3:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_030","NOCINC0004203745","E-Police=
","","29-01-2025 06:02:51","29-01-2025 05:58:16","29-01-2025 07:35:11","Cas=
caded Incident from TTO4217459","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","grid outage,no space to deploy a mobil gen//grid re=
turn","system","273838","29-01-2025 06:02:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0004203746","Sapeur",=
"","29-01-2025 06:02:51","29-01-2025 05:58:16","29-01-2025 07:35:11","Casca=
ded Incident from TTO4217459","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","grid outage,no space to deploy a mobil g=
en//grid return","system","273839","29-01-2025 06:02:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_323","IHS_YND_043","NOCINC0004203740","E=
mia","IHS_YND_030, IHS_YND_029","29-01-2025 06:00:55","29-01-2025 05:58:16"=
,"29-01-2025 07:36:26","grid outage,no space to deploy a mobil gen//grid re=
turn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"grid outage,no space to deploy a mobil gen//grid return","kouoh.jean@ihst=
owers.com","160","29-01-2025 06:00:55","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004203204","Eto=
 koss Yde","","29-01-2025 01:11:15","29-01-2025 01:04:06","29-01-2025 01:20=
:05","Grid outage, site went down because gen fails to start due to grid co=
ntactor disfunction // He started Gen manually (investigation ongoing)","Fa=
nda Brice","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gr=
id outage, site went down because gen fails to start due to grid contactor =
disfunction // He started Gen manually (investigation ongoing)","stephane.n=
kamwa@ihstowers.com","430","29-01-2025 01:11:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0004202905","EMANA BI=
LICK CITY","","28-01-2025 22:52:40","28-01-2025 22:43:36","29-01-2025 01:01=
:21","No power issue site on gen with U=3D54v Symphorien from Huawei is inf=
ormed ,site up at 10:54 PM","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on gen with U=3D54v Symphorien from Huawei is informed ,site up at 10:54=
 PM","stephane.nkamwa@ihstowers.com","546","28-01-2025 22:52:40","Sagemcom =
CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004202900","Pha=
rmacie SION","","28-01-2025 22:51:56","28-01-2025 22:43:51","28-01-2025 22:=
57:59","Grid outage, site went down before gen start due to poor battery ba=
ckup // Grid return","Paul BIBOUM","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before gen =
start due to poor battery backup // Grid return","stephane.nkamwa@ihstowers=
.com","486","28-01-2025 22:51:56","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004202892","Ema=
na","","28-01-2025 22:48:23","28-01-2025 22:39:02","28-01-2025 22:49:37","G=
rid outage, site went down before gen start due to poor battery backup // G=
en start automatically","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","stepha=
ne.nkamwa@ihstowers.com","562","28-01-2025 22:48:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004202882","Mimboman=
4","","28-01-2025 22:47:30","28-01-2025 22:19:28","28-01-2025 22:49:21","Ca=
scaded Incident from TTO4216420","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because CB (125A) t=
ripped PWC due to load increase// CB put back on","system","279761","28-01-=
2025 22:47:30","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004202876","Nko=
lo II New","IHS_YND_266","28-01-2025 22:46:39","28-01-2025 22:19:28","28-01=
-2025 22:49:21","Site went down because CB (125A) tripped PWC due to load i=
ncrease// CB put back on","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down beca=
use CB (125A) tripped PWC due to load increase// CB put back on","stephane.=
nkamwa@ihstowers.com","1632","28-01-2025 22:46:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004202623","MEHANDAN=
","","28-01-2025 21:41:20","28-01-2025 21:34:07","28-01-2025 21:41:10","Cas=
caded Incident from TTO4216098","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Grid return","system","282598","28-01-=
2025 21:41:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004202604","O=
dza II OCM","IHS_YND_528","28-01-2025 21:38:12","28-01-2025 21:34:07","28-0=
1-2025 21:41:10","Grid outage, site went down before gen start due to poor =
battery backup // Grid return","Albran Byorel","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Grid return","christian.fon=
kou@ihstowers.com","246","28-01-2025 21:38:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004202595","O=
lembe-Terminus","","28-01-2025 21:35:03","28-01-2025 21:27:57","28-01-2025 =
21:57:05","Grid outage, Gen start and stopped  with  alarm ""overvoltage""/=
/He reset Gen card  and started the gen","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen start and =
stopped  with  alarm ""overvoltage""//He reset Gen card  and started the ge=
n","christian.fonkou@ihstowers.com","427","28-01-2025 21:35:03","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004202419","B=
iteng-Maetur","","28-01-2025 21:00:16","28-01-2025 20:55:08","28-01-2025 22=
:15:57","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, Site went down because Gen started and stopped due to Gen ov=
erload(20kva, 280A) SS IHS Alphonse DEFFO confirmed// Grid return","christi=
an.fonkou@ihstowers.com","309","28-01-2025 21:00:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004202197","N=
KOLMEKONG YDE","","28-01-2025 20:21:25","28-01-2025 19:40:18","28-01-2025 1=
9:41:19","Error Ticket because site not down","Fabrice Pouakam","Incorrectl=
y Logged Tickets","Error","Error","Error","Error Ticket because site not do=
wn","christian.fonkou@ihstowers.com","2468","28-01-2025 20:21:25","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004202185","Mimboman=
4","","28-01-2025 20:20:01","28-01-2025 20:04:38","28-01-2025 21:24:21","Ca=
scaded Incident from TTO4215587","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because CB (125A) t=
ripped PWC due to load increase// CB put back on","system","923","28-01-202=
5 20:20:01","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004202169","Nko=
lo II New","IHS_YND_266","28-01-2025 20:14:43","28-01-2025 20:04:38","28-01=
-2025 21:24:21","Site went down because CB (125A) tripped PWC due to load i=
ncrease// CB put back on","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down beca=
use CB (125A) tripped PWC due to load increase// CB put back on","emmanuel.=
ghani@ihstowers.com","606","28-01-2025 20:14:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0004201932","NYOM 2 I=
HS","","28-01-2025 19:22:31","28-01-2025 19:14:35","28-01-2025 19:21:08","C=
ascaded Incident from TTO4215280","Fabrice Pouakam","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site Ubaie 52,5V Si=
te on Battery. symphorien (691316854/Huawei) is informed","system","1218735=
","28-01-2025 19:22:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004201829","M=
efou-Assi","","28-01-2025 19:00:47","28-01-2025 18:50:41","28-01-2025 20:14=
:41","Grid outage, site went down because gen fails to start due to battery=
 ge faulty SS IHS Felix Zamb=E9  confirm it  // gen start with battery back=
 up","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generato=
r Battery","Grid outage, site went down because gen fails to start due to b=
attery ge faulty SS IHS Felix Zamb=E9  confirm it  // gen start with batter=
y back up","christian.fonkou@ihstowers.com","607","28-01-2025 19:00:47","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004201799","SIM=
BOCK BONAMBAPE","","28-01-2025 18:54:13","28-01-2025 18:48:05","28-01-2025 =
18:54:21","Site went down due to inssufficiency of rectifier causing by  01=
/08 rctifier faulty SS IHS Felix Zamb=E9 confirmed  // Site stabilized","Hy=
emafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down due to inssufficiency of rectifier causing by  01/08 rctifie=
r faulty SS IHS Felix Zamb=E9 confirmed  // Site stabilized","emmanuel.ghan=
i@ihstowers.com","369","28-01-2025 18:54:13","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0004201698","Awa=
e Ewonkan","","28-01-2025 18:37:58","28-01-2025 18:32:53","28-01-2025 19:58=
:53","Site went down because CB(63A) tripped in DC Box // CB put back on","=
Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Circuit Breaker Issue","Site went down because CB(63A) tripped in DC Box =
// CB put back on","emmanuel.ghani@ihstowers.com","306","28-01-2025 18:37:5=
8","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0004201680","Fou=
da rue des g=E9n=E9raux","","28-01-2025 18:34:21","28-01-2025 18:30:13","28=
-01-2025 20:25:14","No power issue site on grid with U=3D54v Armand Nguetsa=
(691144412) from Huawei is informed","Delor Telezing","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue site on grid with U=3D54v Armand Nguetsa(691144412) from Huawei is in=
formed","emmanuel.ghani@ihstowers.com","249","28-01-2025 18:34:21","Sagemco=
m CMR"
"Closed Complete","Warning","T0104","IHS_YND_113","NOCINC0004201404","Emomb=
o 2","","28-01-2025 17:55:51","","","site on alarm due to grid outage// gen=
 started","MINKA NICOLAS","Warning","Warning","POWER","Warning - Site on Ba=
ttery","site on alarm due to grid outage// gen started and Alarm cleared","=
adonis.defokoua@ihstowers.com","2114","28-01-2025 17:55:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0004201163","MEFOU AS=
SI","","28-01-2025 17:18:10","28-01-2025 14:06:07","28-01-2025 16:22:07","C=
ascaded Incident from TTO4213018","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n fails to start due to battery ge faulty SS IHS Felix Zamb=E9  confirm it =
 // gen start with battery back up","system","1230057","28-01-2025 17:18:10=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004201035","B=
arriere","","28-01-2025 16:53:40","28-01-2025 16:49:35","28-01-2025 17:54:4=
0","Grid fluctuation, site went down because gen start and stopped due to g=
rid bad voltage // he bypass grid and manually start the gen","Hyemafo Gild=
as","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage // he bypass grid and manually start the gen","christian.fon=
kou@ihstowers.com","246","28-01-2025 16:53:40","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004200844","Nko=
g-Edzen","","28-01-2025 16:21:58","28-01-2025 16:14:54","28-01-2025 17:39:5=
4","Grid outage ,Site went down because Gen started and stopped with alarm =
under voltage causing by  pear faulty  // he bypassed the pear and Gen manu=
ally started","Parker Tchoup","Fuel Outage (Probable)","Passive","Diesel","=
Fuel Line Issue","Grid outage ,Site went down because Gen started and stopp=
ed with alarm under voltage causing by  pear faulty  // he bypassed the pea=
r and Gen manually started","emmanuel.ghani@ihstowers.com","425","28-01-202=
5 16:21:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0004200808","BIYEMASS=
I NIKI","","28-01-2025 16:12:50","28-01-2025 15:53:15","28-01-2025 16:33:18=
","Cascaded Incident from TTO4213821","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to PWC Overl=
oaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site stabilized ","syste=
m","281431","28-01-2025 16:12:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004200697","M=
ontee-Jouvence-II","IHS_YND_724","28-01-2025 16:00:23","28-01-2025 15:50:15=
","28-01-2025 16:33:18","Site went down due to PWC Overloaded (12K, 250A)SS=
 IHS Felix Zamb=E9 confirmed // Site stabilized ","Hyemafo Gildas","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went d=
own due to PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site=
 stabilized ","christian.fonkou@ihstowers.com","609","28-01-2025 16:00:23",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_744","NOCINC0004200667","Eleveur =
Meec Bon Berger","","28-01-2025 15:54:30","28-01-2025 15:44:30","28-01-2025=
 15:50:46","Cascaded Incident from TTO4213680","Siligap Boris","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Grid outage;Site went d=
own because Gen started and stopped due to  Gen overload(20 Kva ,290 A)//Gr=
id return  SS IHS  Blaise Raoul is informed and confirmed.","system","12170=
60","28-01-2025 15:54:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004200522","Ngoulmek=
ong-Nord","","28-01-2025 15:47:31","28-01-2025 15:44:30","28-01-2025 15:47:=
59","Cascaded Incident from TTO4213628","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage;Site went down bec=
ause Gen started and stopped due to  Gen overload(20 Kva ,290 A)//Grid retu=
rn  SS IHS  Blaise Raoul is informed and confirmed.","system","267578","28-=
01-2025 15:47:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004200518","E=
leveur","IHS_YND_277, IHS_YND_744","28-01-2025 15:46:36","28-01-2025 15:44:=
30","28-01-2025 15:50:46","Grid outage;Site went down because Gen started a=
nd stopped due to  Gen overload(20 Kva ,290 A)//Grid return  SS IHS  Blaise=
 Raoul is informed and confirmed.","Siligap Boris","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid outage;Site went down because Gen s=
tarted and stopped due to  Gen overload(20 Kva ,290 A)//Grid return  SS IHS=
  Blaise Raoul is informed and confirmed.","christian.fonkou@ihstowers.com"=
,"127","28-01-2025 15:46:36","Sagemcom CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0004200517","Imm=
-Olympique","","28-01-2025 15:46:24","28-01-2025 15:42:09","28-01-2025 16:0=
0:36","Site went down because 02/06  rectifiers hanging //He reset rectifie=
rs ,site on Grid","Paul BIBOUM","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down because 02/06  rectifiers hanging //He res=
et rectifiers ,site on Grid","emmanuel.ghani@ihstowers.com","256","28-01-20=
25 15:46:24","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004200226","Beh=
ind P T school Yde","","28-01-2025 14:58:03","28-01-2025 14:54:55","28-01-2=
025 16:07:08","Site went down because 02/03 rectifiers faulty // Site stabi=
lized(waiting to replaced  rectifiers faulty ),Site on GRID.SS IHS F=E9lix =
Zambe is informed and confirmed.","Paul BIBOUM","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down because 02/03 rectifiers f=
aulty // Site stabilized(waiting to replaced  rectifiers faulty ),Site on G=
RID.SS IHS F=E9lix Zambe is informed and confirmed","emmanuel.ghani@ihstowe=
rs.com","189","28-01-2025 14:58:03","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004200081","Fou=
da Quarter","","28-01-2025 14:34:29","28-01-2025 14:27:21","28-01-2025 15:2=
5:32","No power issue on site Ubaie=3D54.6V site on Grid, The TX FME Armand=
 Nguetsa  from Huawei (699949553) is informed","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site Ubaie=3D54.6V site on Grid, The TX FME Armand Nguet=
sa  from Huawei (699949553) is informed","emmanuel.ghani@ihstowers.com","42=
9","28-01-2025 14:34:29","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004200050","Sap=
eur","","28-01-2025 14:31:37","28-01-2025 14:17:28","28-01-2025 14:30:05","=
Grid outage, site went down before gen start due to poor battery backup // =
Gen started automatically","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen started automatically","emm=
anuel.ghani@ihstowers.com","850","28-01-2025 14:31:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004200046","Barriere=
 IHS","","28-01-2025 14:30:50","28-01-2025 14:06:07","28-01-2025 16:22:07",=
"Cascaded Incident from TTO4213018","Hyemafo Gildas","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen fails to start due to battery ge faulty SS IHS Felix Zamb=E9  confir=
m it  // gen start with battery back up","system","1230057","28-01-2025 14:=
30:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004200008","M=
efou-Assi","IHS_YND_537, IHS_YND_696","28-01-2025 14:26:17","28-01-2025 14:=
06:07","28-01-2025 16:22:07","Grid outage, site went down because gen fails=
 to start due to battery ge faulty SS IHS Felix Zamb=E9  confirm it  // gen=
 start with battery back up","Fanda Brice","Equipment Repair","Passive","AC=
DG Gen","ACDG - Generator Battery","Grid outage, site went down because gen=
 fails to start due to battery ge faulty SS IHS Felix Zamb=E9  confirm it  =
// gen start with battery back up","christian.fonkou@ihstowers.com","1211",=
"28-01-2025 14:26:17","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004199875","Tou=
ring Club International","","28-01-2025 14:03:16","28-01-2025 13:58:06","28=
-01-2025 13:59:30","Active//No power issue on site U=3D50,2V site on Grid T=
eam djoukou/Eiingennerring/ 676576280/ working on site( Installation New RR=
H)","Albran Byorel","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active//No power issue on site U=3D50,2V si=
te on Grid Team djoukou/Eiingennerring/ 676576280/ working on site( Install=
ation New RRH)","ange.kongo@ihstowers.com","311","28-01-2025 14:03:16","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004199805","M=
ontee-Jouvence-II","","28-01-2025 13:55:23","28-01-2025 13:47:00","28-01-20=
25 14:22:53","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed // Site stabilized ","Hyemafo Gildas","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Site went down due to =
PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site stabilized=
 ","rouselle.schoune@ihstowers.com","504","28-01-2025 13:55:23","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004199583","S=
IMBOCK BONAMBAPE","","28-01-2025 13:13:20","28-01-2025 13:04:49","28-01-202=
5 13:46:59","Site went down because 01/08 rctifier faulty SS IHS Felix Zamb=
=E9 confirmed  // He reset the rectifier","Hyemafo Gildas","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Site went down because 01/08 r=
ctifier faulty SS IHS Felix Zamb=E9 confirmed  // He reset the rectifier","=
rouselle.schoune@ihstowers.com","1243","28-01-2025 13:13:20","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004199459","Nko=
lmvack","","28-01-2025 12:50:18","28-01-2025 12:17:07","28-01-2025 13:31:19=
","Hybrid Gen site : Site went down because gen stopped du to low oil press=
ure // He added oil and Gen manually started","Parker Tchoup","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Hybrid Gen site : Sit=
e went down because gen stopped du to low oil pressure // He added oil and =
Gen manually started","ange.kongo@ihstowers.com","1992","28-01-2025 12:50:1=
8","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004199422","O=
lembe-Terminus","","28-01-2025 12:45:01","28-01-2025 12:39:53","28-01-2025 =
12:53:37","Grid outage, Gen start and stopped  with  alarm ""overvoltage""/=
/he reset Gen card  and started the gen","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Gen start and =
stopped  with  alarm ""overvoltage""//he reset Gen card  and started the ge=
n","rouselle.schoune@ihstowers.com","309","28-01-2025 12:45:01","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004199289","B=
iteng-Maetur","","28-01-2025 12:26:57","28-01-2025 12:03:50","28-01-2025 12=
:52:41","Grid outage, Site went down due to Gen overload(20KVA, 260A) SS IH=
S Blaise confirmed// he Reduice the Load","Mba Lazare Herve","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down du=
e to Gen overload(20KVA, 260A) SS IHS Blaise confirmed// he Reduice the Loa=
d","rouselle.schoune@ihstowers.com","1388","28-01-2025 12:26:57","Sagemcom =
CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004199079","BIY=
EMASSI NIKI","","28-01-2025 11:55:44","28-01-2025 11:46:39","28-01-2025 12:=
24:40","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d, F=E9lix Zambe is informed and confirmed","Hyemafo Gildas","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Site went down du=
e to PWC overloaded (12kva 250 A) //Site stabilized, F=E9lix Zambe is infor=
med and confirmed","ange.kongo@ihstowers.com","546","28-01-2025 11:55:44","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004198445","S=
OA UNIVERSITY STADIUM","","28-01-2025 10:42:59","28-01-2025 10:40:43","28-0=
1-2025 11:30:31","Site went down due to work SS IHS Blaise Raoul is working=
 (configuration the PWC) //End of work","Siligap Boris","Installation Activ=
ity","Passive","Planned Activity","Installation Activity","Site went down d=
ue to work SS IHS Blaise Raoul is working (configuration the PWC) //End of =
work","rouselle.schoune@ihstowers.com","137","28-01-2025 10:42:59","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0004198275","Nkongtoc=
k","","28-01-2025 10:23:53","28-01-2025 10:09:59","28-01-2025 10:29:59","",=
"Kemeni Franklin","Cascade Outage","Active","Cascade Active","Cascade Activ=
e","No power issue on site U=3D54,5v site on grid Tx fme Fulbert 654266068 =
of huawei is informed","system","266215","28-01-2025 10:23:53","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0004198274","Angongo"=
,"","28-01-2025 10:23:53","28-01-2025 10:09:59","28-01-2025 10:29:59","","F=
anda Brice","Cascade Outage","Active","Cascade Active","Cascade Active","No=
 power issue on site U=3D54,5v site on grid Tx fme Fulbert 654266068 of hua=
wei is informed","system","266214","28-01-2025 10:23:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004198273","Mambine"=
,"","28-01-2025 10:23:53","28-01-2025 10:09:59","28-01-2025 10:29:59","","F=
anda Brice","Cascade Outage","Active","Cascade Active","Cascade Active","No=
 power issue on site U=3D54,5v site on grid Tx fme Fulbert 654266068 of hua=
wei is informed","system","266213","28-01-2025 10:23:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0004198272","OKOA Pea=
ge","","28-01-2025 10:23:52","28-01-2025 10:09:59","28-01-2025 10:29:59",""=
,"Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active",=
"No power issue on site U=3D54,5v site on grid Tx fme Fulbert 654266068 of =
huawei is informed","system","266213","28-01-2025 10:23:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_310","NOCINC0004198271","Nomayos"=
,"IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_=
697, IHS_YND_330, IHS_YND_350, IHS_YND_335, IHS_YND_349","28-01-2025 10:23:=
52","28-01-2025 10:09:59","28-01-2025 10:29:59","No power issue on site U=
=3D54,5v site on grid Tx fme Fulbert 654266068 of huawei is informed","Fand=
a Brice","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","No power issue on site U=3D54,5v site on grid Tx fme F=
ulbert 654266068 of huawei is informed","system","1058","28-01-2025 10:23:5=
2","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004198270","Ebeba","=
","28-01-2025 10:23:52","28-01-2025 10:09:59","28-01-2025 10:29:59","","Fan=
da Brice","Cascade Outage","Active","Cascade Active","Cascade Active","No p=
ower issue on site U=3D54,5v site on grid Tx fme Fulbert 654266068 of huawe=
i is informed","system","266215","28-01-2025 10:23:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0004198269","Nkenglik=
ok","","28-01-2025 10:23:52","28-01-2025 10:09:59","28-01-2025 10:29:59",""=
,"Kemeni Franklin","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","No power issue on site U=3D54,5v site on grid Tx fme Fulbert 654266068=
 of huawei is informed","system","266214","28-01-2025 10:23:52","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0004198267","Mandoumb=
a OCM","","28-01-2025 10:23:51","28-01-2025 10:09:59","28-01-2025 10:29:59"=
,"","Kemeni Franklin","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","No power issue on site U=3D54,5v site on grid Tx fme Fulbert 654266=
068 of huawei is informed","system","266216","28-01-2025 10:23:51","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0004198268","Mbankomo=
 IHS","","28-01-2025 10:23:51","28-01-2025 10:09:59","28-01-2025 10:29:59",=
"","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active=
","No power issue on site U=3D54,5v site on grid Tx fme Fulbert 654266068 o=
f huawei is informed","system","266216","28-01-2025 10:23:51","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0004198266","Sous Pre=
fecture","","28-01-2025 10:23:51","28-01-2025 10:09:59","28-01-2025 10:29:5=
9","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Act=
ive","No power issue on site U=3D54,5v site on grid Tx fme Fulbert 65426606=
8 of huawei is informed","system","266217","28-01-2025 10:23:51","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0004198251","N=
omayos-IHS","","28-01-2025 10:21:18","28-01-2025 10:09:59","28-01-2025 10:2=
9:59","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue on site U=3D54,5v site on grid Tx fme Fulbert 65426=
6068 of huawei is informed","rouselle.schoune@ihstowers.com","266216","28-0=
1-2025 10:21:18","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004198170","Fou=
da Quarter","","28-01-2025 10:14:20","28-01-2025 09:56:12","28-01-2025 10:1=
8:55","No power issue on site Ubaie=3D54.6V site on Grid,  The TX FME Arman=
d Nguetsa  from Huawei (699949553) is informed.","Delor Telezing","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site Ubaie=3D54.6V site on Grid,  The TX FME Armand Ng=
uetsa  from Huawei (699949553) is informed.","ange.kongo@ihstowers.com","10=
89","28-01-2025 10:14:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004197677","E=
vodoula OCM","","28-01-2025 09:00:31","28-01-2025 08:54:20","28-01-2025 09:=
40:17","No power issue site and  with Ubaie=3D54.4  V site on Gen The  FME =
TX Mouamadou/658791013 //From Huawei is informed","TIENTCHEU NZETCHIEU GAEL=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue site and  with Ubaie=3D54.4  V site on Gen The=
  FME TX Mouamadou/658791013 //From Huawei is informed","rouselle.schoune@i=
hstowers.com","373","28-01-2025 09:00:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004197479","Bondjock=
","","28-01-2025 08:16:50","28-01-2025 08:03:53","28-01-2025 08:12:47","Cas=
caded Incident from TTO4210078","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid hybrid Gen : Grid outga site went d=
own because Gen failed to start due to PWC dYsfonction // Grid power return=
","system","273464","28-01-2025 08:16:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004197477","Mbeng","=
","28-01-2025 08:16:50","28-01-2025 08:03:53","28-01-2025 08:12:47","Cascad=
ed Incident from TTO4210078","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid hybrid Gen : Grid outga site went down=
 because Gen failed to start due to PWC dYsfonction // Grid power return","=
system","273465","28-01-2025 08:16:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0004197427","M=
inka","IHS_YND_369, IHS_YND_553, IHS_YND_372","28-01-2025 08:08:57","28-01-=
2025 08:03:53","28-01-2025 08:13:21","Grid hybrid Gen : Grid outga site wen=
t down because Gen failed to start due to PWC dYsfonction // Grid power ret=
urn","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","Grid hybrid Gen : Grid outga site went down because Gen fai=
led to start due to PWC dYsfonction // Grid power return","rouselle.schoune=
@ihstowers.com","305","28-01-2025 08:08:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004197416","Barriere=
 IHS","","28-01-2025 08:07:10","28-01-2025 07:58:06","28-01-2025 08:14:42",=
"Cascaded Incident from TTO4210062","Hyemafo Gildas","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site U=3D54,5v sit=
e on grid Tx fme Patrice 695007608 of huawei is informed","system","266619"=
,"28-01-2025 08:07:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004197412","M=
efou-Assi","IHS_YND_696","28-01-2025 08:06:14","28-01-2025 07:58:06","28-01=
-2025 09:12:42","No power issue on site U=3D54,5v site on grid Tx fme Patri=
ce 695007608 of huawei is informed","Fanda Brice","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site U=3D54,5v site on grid Tx fme Patrice 695007608 of huawei is info=
rmed","rouselle.schoune@ihstowers.com","489","28-01-2025 08:06:14","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0004197363","E=
MANA BILICK CITY","","28-01-2025 07:57:13","28-01-2025 07:53:04","28-01-202=
5 08:35:18","Grid outage site went Gen ran until fuel shortage //Refueling =
done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","G=
rid outage site went Gen ran until fuel shortage //Refueling done","rousell=
e.schoune@ihstowers.com","250","28-01-2025 07:57:13","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_238","NOCINC0004197272","Mendong","=
","28-01-2025 07:36:03","","","Site went alarm because Gen fails to start d=
ue to Grid bad voltage // He bypass the Grid and Gen manually started","Hye=
mafo Gildas","Warning","Warning","POWER","Warning - Site on Battery","Site =
went alarm because Gen fails to start due to Grid bad voltage // He bypass =
the Grid and Gen manually started","joelle.ekessi@ihstowers.com","4","28-01=
-2025 07:36:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_068","IHS_YND_109","NOCINC0004197243","M=
obil-Essos","","28-01-2025 07:30:03","28-01-2025 07:25:57","28-01-2025 09:1=
2:07","No power issue on site U=3D54,5v site on grid Tx fme Armand Nguetsa =
of huawei is informed","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,5v site on grid Tx fme Armand Nguetsa of huawei is informed","rousell=
e.schoune@ihstowers.com","247","28-01-2025 07:30:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0004197242","Crf Corn=
ier","","28-01-2025 07:29:30","28-01-2025 07:24:51","28-01-2025 08:09:40","=
Cascaded Incident from TTO4209869","MINKA NICOLAS","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D53v site on=
 grid Tx fme Armand Nguetsa of huawei is informed","system","1218050","28-0=
1-2025 07:29:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004197238","M=
adison","IHS_YND_566","28-01-2025 07:28:57","28-01-2025 07:24:51","28-01-20=
25 08:29:40","No power issue on site U=3D53v site on grid Tx fme Armand Ngu=
etsa of huawei is informed","MFOUAGUEGUE MATHIEU","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site U=3D53v site on grid Tx fme Armand Nguetsa of huawei is informed"=
,"rouselle.schoune@ihstowers.com","247","28-01-2025 07:28:57","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004197071","L=
abogenie","","28-01-2025 06:51:22","28-01-2025 06:44:59","28-01-2025 07:50:=
59","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hua=
wei is informed","rouselle.schoune@ihstowers.com","384","28-01-2025 06:51:2=
2","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004196809","Ngoulmek=
ong-Nord","","28-01-2025 05:55:51","28-01-2025 04:34:20","28-01-2025 06:41:=
55","Cascaded Incident from TTO4209377","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,site went down bec=
ause Gen Overload(20kva 300A) SS IHS Blaise Raoul Confirmed // He reduced t=
he load","system","286050","28-01-2025 05:55:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_744","NOCINC0004196758","Eleveur =
Meec Bon Berger","","28-01-2025 05:32:21","28-01-2025 04:34:29","28-01-2025=
 06:41:55","Cascaded Incident from TTO4209320","Siligap Boris","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Grid outage,site went d=
own because Gen Overload(20kva 300A) SS IHS Blaise Raoul Confirmed // He re=
duced the load","system","286041","28-01-2025 05:32:21","Sagemcom CMR"
"Closed Complete","Site Down","T1832","IHS_YND_216","NOCINC0004196757","Ele=
veur","IHS_YND_277, IHS_YND_744","28-01-2025 05:31:44","28-01-2025 04:34:20=
","28-01-2025 07:36:55","Grid outage,site went down because Gen Overload(20=
kva 300A) SS IHS Blaise Raoul Confirmed // He reduced the load","Siligap Bo=
ris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
,site went down because Gen Overload(20kva 300A) SS IHS Blaise Raoul Confir=
med // He reduced the load","kamga.virgile@ihstowers.com","4870","28-01-202=
5 05:31:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0004196407","MEFOU AS=
SI","","28-01-2025 02:37:30","28-01-2025 02:16:09","28-01-2025 02:17:22","C=
ascaded Incident from TTO4208915","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site GRID , Ubaie=3D54.=
V site On Grid The Tx FME Georges 697461814 from Huawei is informed..site u=
p at 02:19 AM","system","280037","28-01-2025 02:37:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004196408","Barriere=
 IHS","","28-01-2025 02:37:30","28-01-2025 02:16:09","28-01-2025 02:17:22",=
"Cascaded Incident from TTO4208915","Hyemafo Gildas","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site GRID , Ubaie=
=3D54.V site On Grid The Tx FME Georges 697461814 from Huawei is informed..=
site up at 02:19 AM","system","280037","28-01-2025 02:37:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004196404","M=
efou-Assi","IHS_YND_537, IHS_YND_696","28-01-2025 02:36:18","28-01-2025 02:=
16:09","28-01-2025 02:17:22","No power issue on site GRID , Ubaie=3D54.V si=
te On Grid The Tx FME Georges 697461814 from Huawei is informed..site up at=
 02:19 AM","Fanda Brice","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue on site GRID , Ubaie=3D=
54.V site On Grid The Tx FME Georges 697461814 from Huawei is informed..sit=
e up at 02:19 AM","alexandre.kamal@ihstowers.com","1210","28-01-2025 02:36:=
18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004196369","M=
essassi okolo","","28-01-2025 02:28:02","28-01-2025 02:12:41","28-01-2025 0=
3:51:58","Site went down because Gen Failed to Start due to ATS dysfuntionn=
ing// he disconnected PSC3 it and Manuallly Started The Gen","Fabrice Pouak=
am","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Site went=
 down because Gen Failed to Start due to ATS dysfuntionning// he disconnect=
ed PSC3 it and Manuallly Started The Gen","alexandre.kamal@ihstowers.com","=
1318","28-01-2025 02:28:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004196231","S=
IMBOCK BONAMBAPE","","28-01-2025 01:31:59","28-01-2025 01:25:51","28-01-202=
5 01:30:38","No power issue site on grid with U=3D50,3v Mbah Osiah  from Hu=
awei is informed ,site up at 01:37 AM","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on grid with U=3D50,3v Mbah Osiah  from Huawei is informed ,si=
te up at 01:37 AM","alexandre.kamal@ihstowers.com","369","28-01-2025 01:31:=
59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004196168","M=
essassi 2","","28-01-2025 00:49:24","28-01-2025 00:40:20","28-01-2025 01:57=
:44","Grid outage site went down because Gen stopped with alarm high temp /=
/He added water and Gen manually started","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","G=
rid outage site went down because Gen stopped with alarm high temp //He add=
ed water and Gen manually started","alexandre.kamal@ihstowers.com","545","2=
8-01-2025 00:49:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_217","NOCINC0004195938","Abom",""=
,"28-01-2025 00:03:02","27-01-2025 23:34:54","28-01-2025 00:44:49","Cascade=
d Incident from TTO4208371","Siligap Boris","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive"," Site went down due to disjunction of Rect=
ifier CB(40) // CB put back on","system","567521","28-01-2025 00:03:02","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_213","NOCINC0004195935","Nkolmess=
eng","","28-01-2025 00:03:01","27-01-2025 23:34:54","28-01-2025 00:44:49","=
Cascaded Incident from TTO4208371","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive"," Site went down due to disjunction =
of Rectifier CB(40) // CB put back on","system","567519","28-01-2025 00:03:=
01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_739","NOCINC0004195936","NKOLMESS=
ING rue Manguier","","28-01-2025 00:03:01","27-01-2025 23:34:54","28-01-202=
5 00:44:49","Cascaded Incident from TTO4208371","Siligap Boris","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive"," Site went down due to=
 disjunction of Rectifier CB(40) // CB put back on","system","567520","28-0=
1-2025 00:03:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_214","NOCINC0004195937","Nkolmess=
eng-II","","28-01-2025 00:03:01","27-01-2025 23:34:54","28-01-2025 00:44:49=
","Cascaded Incident from TTO4208371","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive"," Site went down due to disjuncti=
on of Rectifier CB(40) // CB put back on","system","567520","28-01-2025 00:=
03:01","Sagemcom CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0004195931","Nko=
lmesseng","IHS_DLA_129, IHS_YND_213, IHS_YND_739, IHS_YND_214, IHS_YND_217"=
,"28-01-2025 00:01:18","27-01-2025 23:34:54","28-01-2025 00:44:49"," Site w=
ent down due to disjunction of Rectifier CB(40) // CB put back on","Siligap=
 Boris","Equipment Repair","Passive","Control Panel","Power Cabinet - Circu=
it Breaker Issue"," Site went down due to disjunction of Rectifier CB(40) /=
/ CB put back on","kamga.virgile@ihstowers.com","1585","28-01-2025 00:01:18=
","Sagemcom CMR"
"Cancelled","Warning","T1751","IHS_YND_213","NOCINC0004195926","Nkolmesseng=
","","27-01-2025 23:55:02","","","","Siligap Boris","","","","","","kamga.v=
irgile@ihstowers.com","1298","27-01-2025 23:55:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_215","NOCINC0004195456","Eleveurs=
","","27-01-2025 21:52:51","27-01-2025 21:25:29","27-01-2025 22:51:05","Cas=
caded Incident from TTO4207603","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to insufficience of=
 rectifiers on site(04/05)  due to increase load on site SS IHS Blaise Raou=
l is informed and confirmed// We add one rectifier and site on grid","syste=
m","268660","27-01-2025 21:52:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_217","NOCINC0004195457","Abom",""=
,"27-01-2025 21:52:51","27-01-2025 21:25:29","27-01-2025 22:51:05","Cascade=
d Incident from TTO4207603","Siligap Boris","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Site went down due to insufficience of rec=
tifiers on site(04/05)  due to increase load on site SS IHS Blaise Raoul is=
 informed and confirmed// We add one rectifier and site on grid","system","=
268659","27-01-2025 21:52:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_214","NOCINC0004195313","Nkolmess=
eng-II","","27-01-2025 21:34:00","27-01-2025 21:25:29","27-01-2025 22:51:05=
","Cascaded Incident from TTO4207603","Siligap Boris","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site went down due to insufficie=
nce of rectifiers on site(04/05)  due to increase load on site SS IHS Blais=
e Raoul is informed and confirmed// We add one rectifier and site on grid",=
"system","268660","27-01-2025 21:34:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_739","NOCINC0004195312","NKOLMESS=
ING rue Manguier","","27-01-2025 21:34:00","27-01-2025 21:25:29","27-01-202=
5 22:51:05","Cascaded Incident from TTO4207603","Siligap Boris","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Site went down due to =
insufficience of rectifiers on site(04/05)  due to increase load on site SS=
 IHS Blaise Raoul is informed and confirmed// We add one rectifier and site=
 on grid","system","268659","27-01-2025 21:34:00","Sagemcom CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0004195282","Nko=
lmesseng","IHS_YND_215, IHS_YND_739, IHS_YND_214, IHS_YND_217","27-01-2025 =
21:32:35","27-01-2025 21:25:29","27-01-2025 22:51:05","Site went down due t=
o insufficience of rectifiers on site(04/05)  due to increase load on site =
SS IHS Blaise Raoul is informed and confirmed// We add one rectifier and si=
te on grid","Siligap Boris","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to insufficience of rectifiers on site(04/=
05)  due to increase load on site SS IHS Blaise Raoul is informed and confi=
rmed// We add one rectifier and site on grid","stephane.nkamwa@ihstowers.co=
m","426","27-01-2025 21:32:35","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004195271","EMA=
NA BILICK CITY","","27-01-2025 21:30:22","27-01-2025 21:22:17","27-01-2025 =
21:23:21","No power issue site on gen with U=3D54v Symphorien from Huawei i=
s informed ,site up at 11:31 PM","Fabrice Pouakam","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on gen with U=3D54v Symphorien from Huawei is informed ,site up at =
11:31 PM","stephane.nkamwa@ihstowers.com","486","27-01-2025 21:30:22","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004195093","Mimboman=
4","","27-01-2025 21:11:11","27-01-2025 21:01:22","27-01-2025 21:31:37","Ca=
scaded Incident from TTO4207379","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because CB (125A) t=
ripped PWC due to load increase// CB put back on","system","1219642","27-01=
-2025 21:11:11","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004195089","Nko=
lo II New","IHS_YND_266","27-01-2025 21:10:29","27-01-2025 21:01:22","27-01=
-2025 21:31:37","Site went down because CB (125A) tripped PWC due to load i=
ncrease// CB put back on","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down beca=
use CB (125A) tripped PWC due to load increase// CB put back on","stephane.=
nkamwa@ihstowers.com","548","27-01-2025 21:10:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004194661","Donga","=
","27-01-2025 19:57:51","27-01-2025 18:33:01","27-01-2025 18:40:55","Cascad=
ed Incident from TTO4206858","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site, site on Gen Ubai=3D =
50,4 The Tx FME Gregoire/654547479 from huawei is informed. Notice that sit=
e impacted by MBANJOCK CAMRAIL (Not managing by HIS)","system","279064","27=
-01-2025 19:57:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004194662","Dong",""=
,"27-01-2025 19:57:51","27-01-2025 18:33:01","27-01-2025 18:40:55","Cascade=
d Incident from TTO4206858","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site, site on Gen Ubai=3D 5=
0,4 The Tx FME Gregoire/654547479 from huawei is informed. Notice that site=
 impacted by MBANJOCK CAMRAIL (Not managing by HIS)","system","279064","27-=
01-2025 19:57:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0004194636","N=
guila","IHS_YND_434, IHS_YND_444","27-01-2025 19:55:15","27-01-2025 18:33:0=
1","27-01-2025 18:40:55","No power issue on site, site on Gen Ubai=3D 50,4 =
The Tx FME Gregoire/654547479 from huawei is informed. Notice that site imp=
acted by MBANJOCK CAMRAIL (Not managing by HIS)","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site, site on Gen Ubai=3D 50,4 The Tx FME Gregoire/6545=
47479 from huawei is informed. Notice that site impacted by MBANJOCK CAMRAI=
L (Not managing by HIS)","kouoh.jean@ihstowers.com","4935","27-01-2025 19:5=
5:15","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0004194615","Lob=
o 2","","27-01-2025 19:50:53","27-01-2025 19:28:39","27-01-2025 21:03:23","=
Site went down due to disfunctionning of hybrid system // He started Gen ma=
nually","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Hybrid","H=
ybrid Module","Site went down due to disfunctionning of hybrid system // He=
 started Gen manually","stephane.nkamwa@ihstowers.com","1335","27-01-2025 1=
9:50:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004194515","B=
iteng-Maetur","","27-01-2025 19:40:45","27-01-2025 18:45:15","27-01-2025 18=
:50:13","Active//No power issue, U=3D53,9 on Gen, Tx FME lionel steve adjep=
/655124876/ From huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue, U=3D53,9 on Gen, Tx FME lionel steve adjep/655124876/ From=
 huawei is informed","kouoh.jean@ihstowers.com","3331","27-01-2025 19:40:45=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004194491","E=
kounou","","27-01-2025 19:36:39","27-01-2025 18:55:50","27-01-2025 19:16:10=
","Site went down because PWC overload (24KW, 390A) SS IHS Pascaline Manda =
confirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down because PWC overlo=
ad (24KW, 390A) SS IHS Pascaline Manda confirmed// Site stabilized","kouoh.=
jean@ihstowers.com","2451","27-01-2025 19:36:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004194410","E=
kounou","","27-01-2025 19:20:30","27-01-2025 17:51:51","27-01-2025 18:06:05=
","","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","Site went down because PWC overload (24KW, 390A) SS IHS P=
ascaline Manda confirmed// Site stabilized","kouoh.jean@ihstowers.com","532=
0","27-01-2025 19:20:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004194113","M=
essassi okolo","","27-01-2025 18:33:39","27-01-2025 18:27:26","27-01-2025 1=
9:15:35","Site went down because CB (125A) who feeds equipments OCM went fa=
ulty// He bypassed CB","Fabrice Pouakam","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down because =
CB (125A) who feeds equipments OCM went faulty// He bypassed CB","kouoh.jea=
n@ihstowers.com","374","27-01-2025 18:33:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004193928","E=
mana lycee 2","","27-01-2025 18:08:11","27-01-2025 17:58:58","27-01-2025 18=
:12:00","Grid fluctuation, Site went down because Gen failed to start due t=
o lack of 02 phases// Grid stabilized","Fabrice Pouakam","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, S=
ite went down because Gen failed to start due to lack of 02 phases// Grid s=
tabilized","kouoh.jean@ihstowers.com","554","27-01-2025 18:08:11","Sagemcom=
 CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004193768","Sca=
lom","","27-01-2025 17:44:05","27-01-2025 17:37:55","27-01-2025 17:41:33","=
Site went down due to insufficience of rectifiers SS IHS Felix ZAMBE confir=
med// Site stabilized","Paul BIBOUM","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to insufficience of rectifiers SS=
 IHS Felix ZAMBE confirmed// Site stabilized","stephane.nkamwa@ihstowers.co=
m","371","27-01-2025 17:44:05","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004193588","Eko=
unou","","27-01-2025 17:08:53","27-01-2025 16:47:24","27-01-2025 17:03:10",=
"","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le Overloaded","Site went down because PWC overload (24KW, 390A) SS IHS Pas=
caline Manda confirmed// Site stabilized","kouoh.jean@ihstowers.com","1291"=
,"27-01-2025 17:08:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004193453","B=
iteng-Maetur","","27-01-2025 16:48:52","27-01-2025 16:38:45","27-01-2025 18=
:36:47","Grid outage, Site went down because Gen started and stopped due to=
 Gen overload(20kva, 280A) SS IHS Alphonse DEFFO confirmed. Site remains do=
wn at OCM but Up after power reset// He reduiced load and s","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
, Site went down because Gen started and stopped due to Gen overload(20kva,=
 280A) SS IHS Alphonse DEFFO confirmed. Site remains down at OCM but Up aft=
er power reset// He reduiced load and started Gen manualy","kouoh.jean@ihst=
owers.com","608","27-01-2025 16:48:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004193315","M=
ontee-Jouvence-II","","27-01-2025 16:19:00","27-01-2025 16:10:53","27-01-20=
25 16:29:53","Site went down due to PWC Overloaded (12K, 250A)SS IHS Felix =
Zamb=E9 confirmed // Site stabilized ","Hyemafo Gildas","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Site went down due to =
PWC Overloaded (12K, 250A)SS IHS Felix Zamb=E9 confirmed // Site stabilized=
 ","kouoh.jean@ihstowers.com","489","27-01-2025 16:19:00","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004193034","Eko=
unou","","27-01-2025 15:52:30","27-01-2025 15:44:03","27-01-2025 16:04:02",=
"Site went down because PWC overload (24KW, 390A) SS IHS Pascaline Manda co=
nfirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because PWC overload=
 (24KW, 390A) SS IHS Pascaline Manda confirmed// Site stabilized","kouoh.je=
an@ihstowers.com","509","27-01-2025 15:52:30","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004192822","Fou=
da Quarter","","27-01-2025 15:42:03","27-01-2025 15:34:42","27-01-2025 15:4=
0:07","Active// no power issue on site  Ubaie =3D54,4V   site on Grid. Arma=
nd Nguetsa(691144412) from Huawei is informed","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// no power issue on site  Ubaie =3D54,4V   site on Grid. Armand Ngu=
etsa(691144412) from Huawei is informed","stephane.nkamwa@ihstowers.com","4=
42","27-01-2025 15:42:03","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004192394","NKO=
MEKUI OCM","","27-01-2025 15:15:58","27-01-2025 15:08:51","27-01-2025 16:15=
:48","No power issue on site U=3D54.5 V site on Gen.Site impacted by Mbanko=
lo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site U=3D54.5 V site on Gen.Site impacted by Mbankolo Camt=
el and not managing by IHS","stephane.nkamwa@ihstowers.com","428","27-01-20=
25 15:15:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004192329","L=
abogenie","","27-01-2025 15:03:51","27-01-2025 14:49:39","27-01-2025 14:55:=
29","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed. Repetitive Issue","","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundo=
u/693212405 of huawei is informed. Repetitive Issue","kouoh.jean@ihstowers.=
com","853","27-01-2025 15:03:51","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004191915","Eko=
unou","","27-01-2025 14:48:09","27-01-2025 14:43:42","27-01-2025 15:03:05",=
"Site went down because PWC overload (24KW, 390A) SS IHS Pascaline Manda co=
nfirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because PWC overload=
 (24KW, 390A) SS IHS Pascaline Manda confirmed// Site stabilized","stephane=
.nkamwa@ihstowers.com","797","27-01-2025 14:48:09","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004191886","EMA=
NA BILICK CITY","","27-01-2025 14:44:06","27-01-2025 14:36:59","27-01-2025 =
14:40:35","Site went down due to ""Desire(677549842) from IHS and IHS super=
visor Bernard Atangana are working on site for dismantling// Power Restored=
 in the New Site on the 26/01/2025 at 18:51//TX still down","Fabrice Pouaka=
m","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Site went down due to ""Desire(677549842) from IHS and IHS s=
upervisor Bernard Atangana are working on site for dismantling// Power Rest=
ored in the New Site on the 26/01/2025 at 18:51//TX still down","stephane.n=
kamwa@ihstowers.com","428","27-01-2025 14:44:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0004191463","M=
vog Mbi New","","27-01-2025 13:59:43","27-01-2025 13:55:37","27-01-2025 13:=
59:28","Grid outage, Site went down because Gen started and stopped due to =
""High temp"" alarm// He reset Gen card and started Gen manualy (investigat=
ion ongoing)","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Grid outage, Site went down because Gen started and stop=
ped due to ""High temp"" alarm// He reset Gen card and started Gen manualy =
(investigation ongoing)","christian.fonkou@ihstowers.com","247","27-01-2025=
 13:59:43","Sagemcom CMR"
"Closed Complete","Site Down","T2149","IHS_EDA_056","NOCINC0004191393","Ndo=
gbessol","","27-01-2025 13:47:04","27-01-2025 13:44:00","27-01-2025 15:25:5=
4","Site went down because gen failed to start due to gen card issue //He r=
eset gen card and gen manually started (investigation ongoing)","Kemeni Fra=
nklin","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Site=
 went down because gen failed to start due to gen card issue //He reset gen=
 card and gen manually started (investigation ongoing)","emmanuel.ghani@ihs=
towers.com","6421","27-01-2025 13:47:04","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004190637","Men=
dong NB","","27-01-2025 12:20:25","27-01-2025 12:00:21","27-01-2025 13:07:1=
0","Site went down due to CB(80A)faulty in the PWC//He replaced it by the C=
B(125A)","","Equipment Repair","Passive","Control Panel","Power Cabinet - C=
ircuit Breaker Issue","Site went down due to CB(80A)faulty in the PWC//He r=
eplaced it by the CB(125A)","emmanuel.ghani@ihstowers.com","1205","27-01-20=
25 12:20:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_546","IHS_YND_419","NOCINC0004190531","N=
gog Mapubi","","27-01-2025 12:10:18","27-01-2025 12:00:14","27-01-2025 13:2=
9:00","Grid outage, site went down because gen failed to start due to fuse =
of gen contactor went faulty in PWC // He changed fuse and gen manually sta=
rted","Kemeni Franklin","Equipment Repair","Passive","Control Panel","ATS-A=
MF Issue","Grid outage, site went down because gen failed to start due to f=
use of gen contactor went faulty in PWC // He changed fuse and gen manually=
 started","christian.fonkou@ihstowers.com","605","27-01-2025 12:10:18","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004190461","M=
ontee-Des-Soeurs","","27-01-2025 12:04:48","27-01-2025 11:54:42","27-01-202=
5 12:00:42","No power Issue Site on Grid Ubai =3D54.3 V,   The FME  The TX =
FME Mbah Hosiah (674007438) is informed. ","Hyemafo Gildas","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power Issue Site on Grid Ubai =3D54.3 V,   The FME  The TX FME Mbah Hosiah =
(674007438) is informed. ","christian.fonkou@ihstowers.com","607","27-01-20=
25 12:04:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004190426","S=
aa","IHS_YND_404","27-01-2025 11:59:57","27-01-2025 11:54:44","27-01-2025 1=
2:14:02","Grid outage, site went down because gen fails to start due to pel=
let radiator pierced// Grid Restored ","Parker Tchoup","Equipment Repair","=
Passive","ACDG Gen","ACDG - Radiator","Grid outage, site went down because =
gen fails to start due to pellet radiator pierced// Grid Restored","christi=
an.fonkou@ihstowers.com","314","27-01-2025 11:59:57","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004190210","Tou=
ring Club International","","27-01-2025 11:33:59","27-01-2025 11:26:54","27=
-01-2025 11:30:12","Active//No power issue on site U=3D54,1V site on Grid T=
eam djoukou/Eiingennerring/ 676576280/ working on site( Installation New RR=
H)","Albran Byorel","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active//No power issue on site U=3D54,1V si=
te on Grid Team djoukou/Eiingennerring/ 676576280/ working on site( Install=
ation New RRH)","emmanuel.ghani@ihstowers.com","425","27-01-2025 11:33:59",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004190112","E=
kounou","","27-01-2025 11:23:24","27-01-2025 11:19:14","27-01-2025 11:39:37=
","Site went down because PWC overload (24KW, 380A) SS IHS Pascaline Manda =
confirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down because PWC overlo=
ad (24KW, 380A) SS IHS Pascaline Manda confirmed// Site stabilized","christ=
ian.fonkou@ihstowers.com","252","27-01-2025 11:23:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004189884","L=
abogenie","","27-01-2025 11:02:51","27-01-2025 10:57:44","27-01-2025 10:59:=
44","No  power issue U =3D54,6V site on Grid.   The Tx FME  Eloundou (69321=
2405 )from Huawei is informed. Notice that it is the repetitive issue ","",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","No  power issue U =3D54,6V site on Grid.   The Tx FME  Eloundou=
 (693212405 )from Huawei is informed. Notice that it is the repetitive issu=
e ","christian.fonkou@ihstowers.com","308","27-01-2025 11:02:51","Sagemcom =
CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004189786","NYO=
M 2 IHS","","27-01-2025 10:45:46","27-01-2025 10:41:15","27-01-2025 13:52:4=
9","Grid outage, site went down because gen start and stopped with alarm hi=
gh temperature due to accordion of radiator cut  // He welded the accordion=
 and gen manually started","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Radiator","Grid outage, site went down because gen start =
and stopped with alarm high temperature due to accordion of radiator cut  /=
/ He welded the accordion and gen manually started","emmanuel.ghani@ihstowe=
rs.com","272","27-01-2025 10:45:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0004189633","EMANA BI=
LICK CITY","","27-01-2025 10:26:19","26-01-2025 19:00:08","26-01-2025 19:01=
:08","Site went down due to ""Desire(677549842) from IHS and IHS supervisor=
 Bernard Atangana are working on site for dismantling// Power Restored in t=
he New Site on the 26/01/2025 at 18:51//TX still down","Fabrice Pouakam","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","TX","joelle.ekessi@ihstowers.com","55573","27-01-2025 10:26:19","=
Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004189495","Eko=
unou","","27-01-2025 10:01:38","27-01-2025 10:00:58","27-01-2025 10:20:25",=
"site went down due to Pwc Huawei (20kilo) Overload (Pascaline from Ihs con=
firmed) // site stabilized","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","site went down due to Pwc Huawei (=
20kilo) Overload (Pascaline from Ihs confirmed) // site stabilized","emmanu=
el.ghani@ihstowers.com","41","27-01-2025 10:01:38","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004189296","Mon=
tee-Jouvence-II","","27-01-2025 09:32:40","27-01-2025 09:24:36","27-01-2025=
 09:59:28","Site went down due to PWC Overloaded (12K, 250A) // site stabil=
ized  SS IHS Alphonse confirmed","Hyemafo Gildas","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due to PWC Ov=
erloaded (12K, 250A) // site stabilized  SS IHS Alphonse confirmed","emmanu=
el.ghani@ihstowers.com","546","27-01-2025 09:32:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004189095","S=
aa","IHS_YND_404","27-01-2025 09:00:51","27-01-2025 08:57:35","27-01-2025 0=
9:21:26","Grid outage, Site went down because Gen stopped with alarm ""high=
 temp"" caused by radiator pierced // He added water and started Gen manual=
ly","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Radiato=
r Leakage","Grid outage, Site went down because Gen stopped with alarm ""hi=
gh temp"" caused by radiator pierced // He added water and started Gen manu=
ally","christian.fonkou@ihstowers.com","198","27-01-2025 09:00:51","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004189064","S=
AA 2","","27-01-2025 08:56:13","27-01-2025 08:57:35","27-01-2025 09:21:26",=
"","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage, Site went down because Gen stopped with alarm ""high t=
emp"" caused by radiator pierced // He added water and started Gen manually=
","christian.fonkou@ihstowers.com","1302","27-01-2025 08:56:13","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0004189026","M=
fou EPC","","27-01-2025 08:46:23","27-01-2025 08:41:18","27-01-2025 09:08:0=
8","Grid outage,Site went down because Gen stopped with alarm ""high temp""=
// He added water and started Gen manually","Mba Lazare Herve","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"Grid outage,Site went down because Gen stopped with alarm ""high temp""//=
 He added water and started Gen manually","christian.fonkou@ihstowers.com",=
"307","27-01-2025 08:46:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004188874","Akak-Nko=
zoa-MTN-IHS","","27-01-2025 08:13:10","27-01-2025 08:05:24","27-01-2025 08:=
15:01","Cascaded Incident from TTO4200267","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid Outage, site Down du=
e to poor backup // Grid return","system","266308","27-01-2025 08:13:10","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004188648","M=
ontee-Jouvence-II","","27-01-2025 07:15:09","27-01-2025 07:12:05","27-01-20=
25 07:54:55","Site went down due to PWC Overloaded (12K, 250A) // site stab=
ilized  SS IHS Alphonse confirmed","Hyemafo Gildas","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Site went down due to PWC =
Overloaded (12K, 250A) // site stabilized  SS IHS Alphonse confirmed","chri=
stian.fonkou@ihstowers.com","185","27-01-2025 07:15:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004188307","Akak-Nko=
zoa-MTN-IHS","","27-01-2025 05:43:41","27-01-2025 05:34:54","27-01-2025 05:=
43:26","Cascaded Incident from TTO4199611","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid Outage, site Down du=
e to poor backup // Grid return","system","267963","27-01-2025 05:43:41","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004188264","N=
gouetou","","27-01-2025 05:23:21","27-01-2025 05:20:15","27-01-2025 06:55:3=
6","No power issue site on gen with U=3D54v Gregoire from Huawei is informe=
d site up at 05:30 AM","Parker Tchoup","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
en with U=3D54v Gregoire from Huawei is informed","olivier.kwedi@ihstowers.=
com","187","27-01-2025 05:23:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004187472","L=
abogenie","","27-01-2025 00:42:34","27-01-2025 00:37:25","27-01-2025 00:42:=
08","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed,","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hu=
awei is informed,","olivier.kwedi@ihstowers.com","310","27-01-2025 00:42:34=
","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004187439","Eko=
unou","","27-01-2025 00:33:05","27-01-2025 00:26:58","27-01-2025 00:46:43",=
"site went down due to Pwc Huawei (20kilo) Overload (Pascaline from Ihs con=
firmed) // site stabilized","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","site went down due to Pwc Huawei (=
20kilo) Overload (Pascaline from Ihs confirmed) // site stabilized","ludivi=
ne.ngamaleu@ihstowers.com","369","27-01-2025 00:33:05","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004187140","Mon=
tee-Jouvence-II","","26-01-2025 23:19:32","26-01-2025 23:17:23","26-01-2025=
 23:18:39","Site went down due to PWC Overloaded (12K, 250A) // site stabil=
ized  SS IHS Alphonse confirmed","Hyemafo Gildas","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down due to PWC Ov=
erloaded (12K, 250A) // site stabilized  SS IHS Alphonse confirmed","ludivi=
ne.ngamaleu@ihstowers.com","130","26-01-2025 23:19:32","Sagemcom CMR"
"Internal Reconciliation","Site Down","","IHS_YND_320","NOCINC0004187127","=
SOA TOWN","","26-01-2025 23:18:00","26-01-2025 23:13:16","26-01-2025 23:43:=
16","Cascaded Incident from TTO4198195 - Cascade Removed From TTO4198195","=
Siligap Boris","","","","","several grid fluctuation , Gen battery discharg=
ed // manual start Gen with external battery","system","284","26-01-2025 23=
:18:00","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004186884","Eko=
unou","","26-01-2025 22:35:13","26-01-2025 22:29:07","26-01-2025 22:49:57",=
"site went down due to Pwc Huawei (20kilo) Overload (Pascaline from Ihs con=
firmed) // site stabilized","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","site went down due to Pwc Huawei (=
20kilo) Overload (Pascaline from Ihs confirmed) // site stabilized","ludivi=
ne.ngamaleu@ihstowers.com","368","26-01-2025 22:35:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004186157","E=
kounou","","26-01-2025 20:23:48","26-01-2025 20:12:43","26-01-2025 21:38:26=
","site went down due to Pwc Huawei (20kilo) Overload (Pascaline from Ihs c=
onfirmed) // site stabilized","Albran Byorel","Equipment Repair","Passive",=
"Rectifier","Rectifier Module Overloaded","site went down due to Pwc Huawei=
 (20kilo) Overload (Pascaline from Ihs confirmed) // site stabilized","alex=
andre.kamal@ihstowers.com","666","26-01-2025 20:23:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0004185968","M=
essassi okolo","","26-01-2025 19:55:49","26-01-2025 19:47:30","26-01-2025 2=
1:31:59","site went down because CB 125A disjuncted in Dx-Box Ocm//he reame=
d the CB","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Circuit Breaker Issue","site went down because CB 125A disju=
ncted in Dx-Box Ocm//he reamed the CB","alexandre.kamal@ihstowers.com","500=
","26-01-2025 19:55:49","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004185954","NYO=
M FACE MAETUR","","26-01-2025 19:53:09","26-01-2025 19:15:58","26-01-2025 2=
0:53:48","Grid fluctuation, site went down because gen start and stopped du=
e to grid bad voltage // he bypass grid and manually start the gen","Fabric=
e Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","Grid fluctuation, site went down because gen start and stopped du=
e to grid bad voltage // he bypass grid and manually start the gen","kamga.=
virgile@ihstowers.com","2232","26-01-2025 19:53:09","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004185948","Nko=
lo II New","","26-01-2025 19:52:04","26-01-2025 19:10:45","27-01-2025 00:45=
:46","ACTIVE//no power issue site on GEN with U=3D53.2V The FME Tx  Lionel =
Steve /655184876/ From huawei is informed.","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE//no power issue site on GEN with U=3D53.2V The FME Tx  Lionel Steve =
/655184876/ From huawei is informed.","kamga.virgile@ihstowers.com","2480",=
"26-01-2025 19:52:04","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004185687","Mim=
boman4","","26-01-2025 19:20:04","26-01-2025 19:04:54","26-01-2025 19:10:55=
","No power issue U=3D54 V site on Grid. TX FME Leonel Steve// 655184876// =
/ from huawei is informed. ","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
U=3D54 V site on Grid. TX FME Leonel Steve// 655184876// / from huawei is i=
nformed. ","kamga.virgile@ihstowers.com","911","26-01-2025 19:20:04","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0004185421","Boga-Mah=
ole","","26-01-2025 18:36:14","26-01-2025 18:18:14","26-01-2025 18:38:14","=
Cascaded Incident from TTO4196127","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site U=3D56,3v sit=
e on gen Tx fme Freddy 690419006 of huawei is informed","system","265697","=
26-01-2025 18:36:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0004185420","Mamb",""=
,"26-01-2025 18:36:14","26-01-2025 18:18:14","26-01-2025 18:38:14","Cascade=
d Incident from TTO4196127","Kemeni Franklin","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site U=3D56,3v site on ge=
n Tx fme Freddy 690419006 of huawei is informed","system","265696","26-01-2=
025 18:36:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004185418","Song-bon=
g","","26-01-2025 18:36:14","26-01-2025 18:18:14","26-01-2025 18:38:14","Ca=
scaded Incident from TTO4196127","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D56,3v site =
on gen Tx fme Freddy 690419006 of huawei is informed","system","265695","26=
-01-2025 18:36:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0004185417","Eseka OC=
M","","26-01-2025 18:36:13","26-01-2025 18:18:14","26-01-2025 18:38:14","Ca=
scaded Incident from TTO4196127","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D56,3v site =
on gen Tx fme Freddy 690419006 of huawei is informed","system","265693","26=
-01-2025 18:36:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0004185411","Ngog Map=
ubi","","26-01-2025 18:36:12","26-01-2025 18:18:14","26-01-2025 18:38:14","=
Cascaded Incident from TTO4196127","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site U=3D56,3v sit=
e on gen Tx fme Freddy 690419006 of huawei is informed","system","265690","=
26-01-2025 18:36:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0004185412","Boumnyeb=
el","","26-01-2025 18:36:12","26-01-2025 18:18:14","26-01-2025 18:38:14","C=
ascaded Incident from TTO4196127","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D56,3v site=
 on gen Tx fme Freddy 690419006 of huawei is informed","system","265691","2=
6-01-2025 18:36:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0004185408","Ndogbess=
ol","","26-01-2025 18:36:11","26-01-2025 18:18:14","26-01-2025 18:38:14","C=
ascaded Incident from TTO4196127","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D56,3v site=
 on gen Tx fme Freddy 690419006 of huawei is informed","system","265694","2=
6-01-2025 18:36:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004185407","Eseka To=
wn","","26-01-2025 18:36:11","26-01-2025 18:18:14","26-01-2025 18:38:14","C=
ascaded Incident from TTO4196127","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D56,3v site=
 on gen Tx fme Freddy 690419006 of huawei is informed","system","265693","2=
6-01-2025 18:36:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004185154","M=
ontee-Jouvence-II","","26-01-2025 17:53:00","26-01-2025 17:48:49","26-01-20=
25 20:07:52","Site went down due to PWC Overloaded (12K, 250A)  SS IHS Alph=
onse confirmed// site stabilized ","Hyemafo Gildas","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Site went down due to PWC =
Overloaded (12K, 250A)  SS IHS Alphonse confirmed// site stabilized ","alex=
andre.kamal@ihstowers.com","252","26-01-2025 17:53:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004185137","N=
YOM 2 IHS","","26-01-2025 17:48:30","26-01-2025 17:26:21","26-01-2025 18:14=
:00","grid outage,gen stopped with alarm high temp//he added water in radia=
tor","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High=
 Engine Temp - Coolant Level Issue","grid outage,gen stopped with alarm hig=
h temp//he added water in radiator","alexandre.kamal@ihstowers.com","1330",=
"26-01-2025 17:48:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004184713","N=
yom OCM","","26-01-2025 16:44:24","26-01-2025 16:36:18","26-01-2025 17:37:4=
4","grid bad voltage,and gen failed to start,no rcp//bypassed grid and star=
ted","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","grid bad voltage,and gen failed to start,no rcp//bypa=
ssed grid and started","alexandre.kamal@ihstowers.com","487","26-01-2025 16=
:44:24","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004184438","Eko=
unou","","26-01-2025 16:02:32","26-01-2025 15:53:18","26-01-2025 16:13:20",=
"site went down due to Pwc Huawei (20kilo) Overload (Pascaline from Ihs con=
firmed) // site stabilized","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","site went down due to Pwc Huawei (=
20kilo) Overload (Pascaline from Ihs confirmed) // site stabilized","kamga.=
virgile@ihstowers.com","667","26-01-2025 16:02:32","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004184411","Men=
dong NB","","26-01-2025 15:59:35","26-01-2025 15:28:12","27-01-2025 07:44:1=
1","Grid outage, No space to deploy MDG // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage, No space t=
o deploy MDG // Grid return","kamga.virgile@ihstowers.com","1884","26-01-20=
25 15:59:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004184330","O=
lembe-Terminus","","26-01-2025 15:39:46","26-01-2025 14:07:38","26-01-2025 =
15:39:50","grid outage,gen failed to start due to alarm over voltage//he re=
set it and started the gen","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start due to a=
larm over voltage//he reset it and started the gen","alexandre.kamal@ihstow=
ers.com","5530","26-01-2025 15:39:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004184220","L=
abogenie","","26-01-2025 15:24:05","26-01-2025 15:03:01","26-01-2025 15:13:=
01","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hua=
wei is informed","alexandre.kamal@ihstowers.com","1265","26-01-2025 15:24:0=
5","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004184218","M=
essassi 2","","26-01-2025 15:23:29","26-01-2025 15:13:56","26-01-2025 16:16=
:31","grid outage,gen stopped with alarm low oil pressure(not unproven)//he=
 reset it and started the gen","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","grid outage,gen stopped with alarm lo=
w oil pressure(not unproven)//he reset it and started the gen","alexandre.k=
amal@ihstowers.com","575","26-01-2025 15:23:29","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_229","NOCINC0004184206","CRH-Etoug-Ebe","=
","26-01-2025 15:22:30","","","Cascaded Incident from TTO4194827","Hyemafo =
Gildas","","","","","","system","445","26-01-2025 15:22:30","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_713","NOCINC0004184207","NKONGKARAK","","=
26-01-2025 15:22:30","","","Cascaded Incident from TTO4194827","TIENTCHEU N=
ZETCHIEU GAEL","","","","","","system","445","26-01-2025 15:22:30","Sagemco=
m CMR"
"Cancelled","Warning","CTR_056","IHS_YND_100","NOCINC0004184203","Shell-Nsi=
meyong","IHS_YND_229, IHS_YND_713","26-01-2025 15:21:13","","","","MINKA NI=
COLAS","","","","","","alexandre.kamal@ihstowers.com","368","26-01-2025 15:=
21:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0004184166","C=
hapelle-Essos","","26-01-2025 15:15:19","26-01-2025 15:04:14","26-01-2025 1=
6:13:05","site on DG due to theft of Eneo CB 100 A and gen ran till fuel sh=
ortage//he connected it with two domino(refueling ongoing)","Delor Telezing=
","Site Asset Theft","Theft","Theft","Circuit Breaker","site on DG due to t=
heft of Eneo CB 100 A and gen ran till fuel shortage//he connected it with =
two domino(refueling ongoing)","alexandre.kamal@ihstowers.com","666","26-01=
-2025 15:15:19","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0004184083","Fou=
da Quarter","","26-01-2025 15:02:49","26-01-2025 14:56:30","26-01-2025 15:0=
6:42","grid bad voltage,and gen failed to start//grid stabilized","Delor Te=
lezing","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","grid bad voltage,and gen failed to start//grid stabilized","kamga.vi=
rgile@ihstowers.com","379","26-01-2025 15:02:49","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0004184033","NYO=
M 2 IHS","","26-01-2025 14:57:27","26-01-2025 14:44:19","26-01-2025 16:53:1=
2","grid outage,gen stopped with alarm high temp//he added water in radiato=
r","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high =
temp//he added water in radiator","kamga.virgile@ihstowers.com","3431","26-=
01-2025 14:57:27","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004183961","Nko=
lafeme","","26-01-2025 14:42:10","26-01-2025 14:21:39","26-01-2025 15:05:01=
","Grid outage, Site went down due to Gen overload(20KVA, 375A) SS IHS Pasc=
aline confirmed// he Reduice the Load and Manually Started the Gen ","TIENT=
CHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overlo=
ad","Grid outage, Site went down due to Gen overload(20KVA, 375A) SS IHS Pa=
scaline confirmed// he Reduice the Load and Manually Started the Gen ","kam=
ga.virgile@ihstowers.com","1231","26-01-2025 14:42:10","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004183572","Tou=
ring Club International","","26-01-2025 13:41:42","26-01-2025 13:35:33","27=
-01-2025 00:43:54","No power issue on site Ubiae=3D51,3 V,Site on GridTX FM=
E Lionel Steeve 655184876 of Huawei is informed","Albran Byorel","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site Ubiae=3D51,3 V,Site on GridTX FME Lionel Steeve 65=
5184876 of Huawei is informed","stephane.nkamwa@ihstowers.com","369","26-01=
-2025 13:41:42","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0004183367","Evo=
doula MTN","","26-01-2025 13:16:42","26-01-2025 13:09:31","26-01-2025 13:56=
:02","grid outage,gen failed to start due to alarm overccurent//he reset it=
 and started the gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start due t=
o alarm overccurent//he reset it and started the gen","stephane.nkamwa@ihst=
owers.com","469","26-01-2025 13:16:42","Sagemcom CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0004183039","Mba=
lla 4","","26-01-2025 12:25:33","26-01-2025 12:11:54","26-01-2025 13:00:51"=
,"grid outage,gen failed to start due to static charger faulty//he started =
the gen with battery backup","Delor Telezing","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Turbo Charger","grid outage,gen failed to start due to s=
tatic charger faulty//he started the gen with battery backup","stephane.nka=
mwa@ihstowers.com","1089","26-01-2025 12:25:33","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004182903","Nko=
lafeme","IHS_YND_309","26-01-2025 12:09:55","26-01-2025 12:01:08","26-01-20=
25 13:25:37","Grid outage,site went down because Gen overload(20kva;380A) S=
S IHS Pascaline is informed and  confirmed//he reduice the load","TIENTCHEU=
 NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage,site went down because Gen overload(20kva;380A) SS IHS Pascali=
ne is informed and  confirmed//he reduice the load","stephane.nkamwa@ihstow=
ers.com","1387","26-01-2025 12:09:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004182902","L=
eboudi","","26-01-2025 12:09:38","26-01-2025 12:01:08","26-01-2025 13:25:37=
","need to cascade at nkolafeme","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage,site went down=
 because Gen overload(20kva;380A) SS IHS Pascaline is informed and  confirm=
ed//he reduice the load","dorothy.djantio@ihstowers.com","266464","26-01-20=
25 12:09:38","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004182805","Pha=
rmacie SION","","26-01-2025 11:53:46","26-01-2025 11:47:42","26-01-2025 12:=
02:46","Grid outage, Site went down before Gen start due to poor battery ba=
ckup//Gen automatically started","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor battery backup//Gen automatically started","s=
tephane.nkamwa@ihstowers.com","365","26-01-2025 11:53:46","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004182796","ETO=
UDI Entree du palais","","26-01-2025 11:51:49","26-01-2025 11:42:45","26-01=
-2025 12:34:09","Grid outage, Site went down because Gen started and stoppe=
d with alarm ' low oil pressure"" (unprouven)// He reset Gen card and start=
ed Gen manualy","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","Grid outage, Site went down because Gen started and =
stopped with alarm ' low oil pressure"" (unprouven)// He reset Gen card and=
 started Gen manualy","stephane.nkamwa@ihstowers.com","545","26-01-2025 11:=
51:49","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004182793","Ema=
na","","26-01-2025 11:51:09","26-01-2025 11:42:00","26-01-2025 11:54:28","G=
rid outage, Site went down before Gen start due to poor backup// Gen automa=
ticaly started ","Fabrice Pouakam","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen automaticaly started ","stephane.nkamwa@ihst=
owers.com","550","26-01-2025 11:51:09","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004182789","Eko=
unou","","26-01-2025 11:49:22","26-01-2025 11:42:16","26-01-2025 13:00:00",=
"Site went down because PWC overload (24KW, 380A) SS IHS Pascaline Manda co=
nfirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because PWC overload=
 (24KW, 380A) SS IHS Pascaline Manda confirmed// Site stabilized","stephane=
.nkamwa@ihstowers.com","428","26-01-2025 11:49:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0004182313","S=
IMBOCK BONAMBAPE","","26-01-2025 11:01:28","26-01-2025 10:53:23","26-01-202=
5 11:01:23","No power issue on site,   with Ubaie=3D51,4 V The Tx Fme Hosia=
h / 674007438 from huawei is informed. Site up at 11:01 AM","Hyemafo Gildas=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site,   with Ubaie=3D51,4 V The Tx Fme Hosi=
ah / 674007438 from huawei is informed. Site up at 11:01 AM","dorothy.djant=
io@ihstowers.com","486","26-01-2025 11:01:28","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004182175","Eko=
unou","","26-01-2025 10:36:28","26-01-2025 10:27:22","26-01-2025 10:47:32",=
"Site went down because PWC overload (24KW, 380A) SS IHS Pascaline Manda co=
nfirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because PWC overload=
 (24KW, 380A) SS IHS Pascaline Manda confirmed// Site stabilized","stephane=
.nkamwa@ihstowers.com","547","26-01-2025 10:36:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0004182082","Boga-Mah=
ole","","26-01-2025 10:21:04","26-01-2025 09:36:22","26-01-2025 11:00:22","=
Cascaded Incident from TTO4192265","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because Gen starte=
d and stopped due to fuel line faulty// He fixed fuel line and Gen Manually=
 started","system","275223","26-01-2025 10:21:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0004182081","Mamb",""=
,"26-01-2025 10:21:04","26-01-2025 09:36:22","26-01-2025 11:00:22","Cascade=
d Incident from TTO4192265","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down because Gen started and s=
topped due to fuel line faulty// He fixed fuel line and Gen Manually starte=
d","system","275222","26-01-2025 10:21:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0004182079","Song-bon=
g","","26-01-2025 10:21:03","26-01-2025 09:36:22","26-01-2025 11:00:22","Ca=
scaded Incident from TTO4192265","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because Gen started =
and stopped due to fuel line faulty// He fixed fuel line and Gen Manually s=
tarted","system","275221","26-01-2025 10:21:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0004182077","Eseka OC=
M","","26-01-2025 10:21:03","26-01-2025 09:36:22","26-01-2025 11:00:22","Ca=
scaded Incident from TTO4192265","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because Gen started =
and stopped due to fuel line faulty// He fixed fuel line and Gen Manually s=
tarted","system","275227","26-01-2025 10:21:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0004182072","Ngog Map=
ubi","","26-01-2025 10:21:02","26-01-2025 09:36:22","26-01-2025 11:00:22","=
Cascaded Incident from TTO4192265","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because Gen starte=
d and stopped due to fuel line faulty// He fixed fuel line and Gen Manually=
 started","system","275220","26-01-2025 10:21:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0004182073","Boumnyeb=
el","","26-01-2025 10:21:02","26-01-2025 09:36:22","26-01-2025 11:00:22","C=
ascaded Incident from TTO4192265","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen started=
 and stopped due to fuel line faulty// He fixed fuel line and Gen Manually =
started","system","275225","26-01-2025 10:21:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0004182067","Boumnyeb=
el OCM","","26-01-2025 10:21:01","26-01-2025 09:36:22","26-01-2025 11:00:22=
","Cascaded Incident from TTO4192265","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down because Gen sta=
rted and stopped due to fuel line faulty// He fixed fuel line and Gen Manua=
lly started","system","275218","26-01-2025 10:21:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0004182069","Ndogbess=
ol","","26-01-2025 10:21:01","26-01-2025 09:36:22","26-01-2025 11:00:22","C=
ascaded Incident from TTO4192265","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen started=
 and stopped due to fuel line faulty// He fixed fuel line and Gen Manually =
started","system","275219","26-01-2025 10:21:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004182068","Eseka To=
wn","","26-01-2025 10:21:01","26-01-2025 09:36:22","26-01-2025 11:00:22","C=
ascaded Incident from TTO4192265","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen started=
 and stopped due to fuel line faulty// He fixed fuel line and Gen Manually =
started","system","275218","26-01-2025 10:21:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004181836","C=
RH-Etoug-Ebe","","26-01-2025 09:38:33","26-01-2025 09:36:28","26-01-2025 12=
:40:34","Active : no power issue, site is on grid with Ubaie=3D53V, Mohamad=
ou (691144435) from Huawei is infomred","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 : no power issue, site is on grid with Ubaie=3D53V, Mohamadou (691144435) =
from Huawei is infomred","dorothy.djantio@ihstowers.com","126","26-01-2025 =
09:38:33","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004181725","Eko=
unou","","26-01-2025 09:18:42","26-01-2025 09:09:13","26-01-2025 09:29:40",=
"Site went down because PWC overload (24KW, 380A) SS IHS Pascaline Manda co=
nfirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because PWC overload=
 (24KW, 380A) SS IHS Pascaline Manda confirmed// Site stabilized","stephane=
.nkamwa@ihstowers.com","866","26-01-2025 09:18:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004181431","A=
kak-Nkozoa-MTN-IHS","","26-01-2025 08:14:08","26-01-2025 08:01:04","26-01-2=
025 09:19:04","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage // he bypass grid and manually start the gen","F=
abrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage // he bypass grid and manually start the gen
","dorothy.djantio@ihstowers.com","785","26-01-2025 08:14:08","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004181108","N=
kozoa","","26-01-2025 07:10:06","26-01-2025 07:02:57","26-01-2025 08:41:57"=
,"Grid outage, site went down due to gen overload (20kva, 340A) // He reduc=
ed the load and gen manually started SS HIS Felix bateu is informed and con=
firmed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, site went down due to gen overload (20kva, 340A) // =
He reduced the load and gen manually started SS HIS Felix bateu is informed=
 and confirmed","dorothy.djantio@ihstowers.com","431","26-01-2025 07:10:06"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004181082","AWA=
E OCM","","26-01-2025 07:05:36","26-01-2025 06:59:23","26-01-2025 07:07:12"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen aut=
omaticaly started ","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen automaticaly started ","stephane.nkamwa@=
ihstowers.com","374","26-01-2025 07:05:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004180960","L=
abogenie","","26-01-2025 06:26:38","26-01-2025 06:24:31","26-01-2025 12:30:=
31","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed,","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hu=
awei is informed,","dorothy.djantio@ihstowers.com","128","26-01-2025 06:26:=
38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004180957","N=
gouetou","","26-01-2025 06:25:22","26-01-2025 06:24:14","26-01-2025 09:15:1=
4","No power issue on site, site on Gen The Tx FME Gregoire/654547479 from =
huawei is informed","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, sit=
e on Gen The Tx FME Gregoire/654547479 from huawei is informed","dorothy.dj=
antio@ihstowers.com","69","26-01-2025 06:25:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004180821","N=
YOM 2 IHS","","26-01-2025 05:52:11","26-01-2025 05:39:59","26-01-2025 06:32=
:59","Grid outage, site went down because gen start and stopped with high t=
emp alarm // he added water and manually start the gen","Fabrice Pouakam","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, site went down because gen start and stopped with=
 high temp alarm // he added water and manually start the gen","rouselle.sc=
houne@ihstowers.com","774","26-01-2025 05:52:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004180712","L=
abogenie","","26-01-2025 05:19:04","26-01-2025 05:15:57","26-01-2025 05:27:=
39","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed,","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hu=
awei is informed,","rouselle.schoune@ihstowers.com","188","26-01-2025 05:19=
:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004180282","N=
gouetou","","26-01-2025 02:49:11","26-01-2025 02:45:25","26-01-2025 03:30:5=
3","No power issue on site, site on Gen The Tx FME Gregoire/654547479 from =
huawei is informed","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, sit=
e on Gen The Tx FME Gregoire/654547479 from huawei is informed","rouselle.s=
choune@ihstowers.com","228","26-01-2025 02:49:11","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004179734","Eko=
unou","","25-01-2025 23:37:36","25-01-2025 23:26:28","25-01-2025 23:46:10",=
"Site went down because PWC overload (24KW, 380A) SS IHS Pascaline Manda co=
nfirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because PWC overload=
 (24KW, 380A) SS IHS Pascaline Manda confirmed// Site stabilized","ange.kon=
go@ihstowers.com","669","25-01-2025 23:37:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004179634","SAA 2","=
","25-01-2025 23:23:10","25-01-2025 23:13:59","25-01-2025 23:47:26","Cascad=
ed Incident from TTO4189583","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because Gen stopped due to=
 water infiltration into the injectors // he purged the injectors and Gen m=
anually started","system","276603","25-01-2025 23:23:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004179623","S=
aa","IHS_YND_401, IHS_YND_404","25-01-2025 23:21:51","25-01-2025 23:13:59",=
"25-01-2025 23:47:26","Site went down because Gen stopped due to water infi=
ltration into the injectors // he purged the injectors and Gen manually sta=
rted","Parker Tchoup","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG -=
 Injector Pump","Site went down because Gen stopped due to water infiltrati=
on into the injectors // he purged the injectors and Gen manually started",=
"rouselle.schoune@ihstowers.com","472","25-01-2025 23:21:51","Sagemcom CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004179621","Nko=
l-Mebanga","","25-01-2025 23:21:46","25-01-2025 23:05:40","26-01-2025 03:00=
:16","Active//No power issue on site Ubaie=3D50V site on Solar  Tx FME Greg=
oire /654547479/Huawei  is informed ","Parker Tchoup","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue on site Ubaie=3D50V site on Solar  Tx FME Gregoire /654547479=
/Huawei  is informed ","ange.kongo@ihstowers.com","967","25-01-2025 23:21:4=
6","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004179533","O=
bobogo","","25-01-2025 22:58:10","25-01-2025 22:56:05","25-01-2025 23:00:19=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen started automatically","MINKA NICOLAS","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen started automatically","=
rouselle.schoune@ihstowers.com","126","25-01-2025 22:58:10","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004179365","Eko=
unou","","25-01-2025 22:19:48","25-01-2025 22:09:59","25-01-2025 22:29:56",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
ted automatically","Albran Byorel","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen started automatically","ange.kongo@ihstowers=
.com","591","25-01-2025 22:19:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004179096","M=
ontee-Jouvence-II","","25-01-2025 21:33:06","25-01-2025 21:14:02","25-01-20=
25 21:24:23","Site went down due to PWC Overloaded (12K, 250A) // site stab=
ilized  SS IHS Alphonse confirmed//Site stabilized","Hyemafo Gildas","Equip=
ment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site went=
 down due to PWC Overloaded (12K, 250A) // site stabilized  SS IHS Alphonse=
 confirmed//Site stabilized","dorothy.djantio@ihstowers.com","1145","25-01-=
2025 21:33:06","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_319","NOCINC0004178778","SOA 2","",=
"25-01-2025 20:55:34","","","alarm unproven site on grid with U=3D52,4v ","=
Siligap Boris","Warning","Warning","POWER","Warning - Site on Battery","ala=
rm unproven site on grid with U=3D52,4v ","olivier.kwedi@ihstowers.com","5"=
,"25-01-2025 20:55:34","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004178602","NYO=
M FACE MAETUR","","25-01-2025 20:23:45","25-01-2025 20:14:40","25-01-2025 2=
1:32:42","site On DG due to grid outage,site went down because grid contact=
or did not excited//he excited the grid contactor:site on grid(observation =
ongoing)","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","A=
TS-AMF Issue","site On DG due to grid outage,site went down because grid co=
ntactor did not excited//he excited the grid contactor:site on grid(observa=
tion ongoing)","ludivine.ngamaleu@ihstowers.com","546","25-01-2025 20:23:45=
","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0004178482","Nko=
lo II New","","25-01-2025 20:01:40","25-01-2025 19:53:30","25-01-2025 21:07=
:58","Site went down because the CB (125A) dijuncted in the PWC // he reame=
d the CB (125A)","Mba Lazare Herve","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Circuit Breaker Issue","Site went down because the C=
B (125A) dijuncted in the PWC // he reamed the CB (125A)","ludivine.ngamale=
u@ihstowers.com","491","25-01-2025 20:01:40","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0004178427","Mim=
boman4","","25-01-2025 19:58:21","25-01-2025 21:15:50","25-01-2025 21:15:51=
","","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Cascade=
 Active","No power issue. Ubaie: 54V; Gen running, TX FME Jeremiah 69867479=
9 / HUAWEI is informed.","ludivine.ngamaleu@ihstowers.com","261868","25-01-=
2025 19:58:21","Sagemcom CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0004178101","Sca=
lom","","25-01-2025 19:07:04","25-01-2025 19:02:51","25-01-2025 21:17:33","=
Site went down due to insufficience of rectifiers SS IHS Felix ZAMBE confir=
med// he reset the rectifier","Paul BIBOUM","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down due to insufficience of rectif=
iers SS IHS Felix ZAMBE confirmed// he reset the rectifier","ludivine.ngama=
leu@ihstowers.com","253","25-01-2025 19:07:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0004178030","E=
kombitie","","25-01-2025 18:54:47","25-01-2025 18:52:43","25-01-2025 21:20:=
58","No power issue site on grid with U=3D54.6V  Symphorien from Huawei is =
informed","Fabrice Pouakam","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54.6V  Symphorien from Huawei is informed","dorothy.djantio@ihstowers.co=
m","125","25-01-2025 18:54:47","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004177968","Nko=
abang MTN","","25-01-2025 18:44:04","25-01-2025 18:40:55","25-01-2025 21:20=
:57","No power issue site on gris with U=3D54 v NONGNI from TELEINFRA is wo=
rking on site  site up at 06:54 PM","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue site on gris with U=3D54 v NONGNI from TELEINFRA is working on site =
 site up at 06:54 PM","ludivine.ngamaleu@ihstowers.com","189","25-01-2025 1=
8:44:04","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004177401","Eko=
unou","","25-01-2025 17:33:50","25-01-2025 17:22:35","25-01-2025 17:42:05",=
"Site went down because PWC overload (24KW, 380A) SS IHS Pascaline Manda co=
nfirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because PWC overload=
 (24KW, 380A) SS IHS Pascaline Manda confirmed// Site stabilized","ludivine=
.ngamaleu@ihstowers.com","677","25-01-2025 17:33:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_736","NOCINC0004177321","CRF Nkoa=
bang","","25-01-2025 17:17:51","25-01-2025 17:11:02","25-01-2025 17:40:44",=
"Cascaded Incident from TTO4186879","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage.gen failed to start=
 due to card GE dysfunctionning //We reset card GE and gen manually started=
 ","system","276551","25-01-2025 17:17:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0004177319","NGONA","=
","25-01-2025 17:17:50","25-01-2025 17:11:02","25-01-2025 17:40:44","Cascad=
ed Incident from TTO4186879","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage.gen failed to start due to=
 card GE dysfunctionning //We reset card GE and gen manually started ","sys=
tem","276550","25-01-2025 17:17:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0004177320","Nkoabang=
2","","25-01-2025 17:17:50","25-01-2025 17:11:02","25-01-2025 17:40:44","Ca=
scaded Incident from TTO4186879","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start du=
e to card GE dysfunctionning //We reset card GE and gen manually started ",=
"system","276550","25-01-2025 17:17:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0004177310","N=
koabang","IHS_YND_295, IHS_YND_526, IHS_YND_736","25-01-2025 17:16:04","25-=
01-2025 17:11:02","25-01-2025 17:40:44","Grid outage.gen failed to start du=
e to card GE dysfunctionning //We reset card GE and gen manually started ",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid outage.gen failed to start due to card GE dysfunctionning //We=
 reset card GE and gen manually started ","dorothy.djantio@ihstowers.com","=
303","25-01-2025 17:16:04","Sagemcom CMR"
"Cancelled","Warning","CTR_590","IHS_YND_295","NOCINC0004177300","NGONA",""=
,"25-01-2025 17:12:28","","","","Mba Lazare Herve","","","","","","dorothy.=
djantio@ihstowers.com","123","25-01-2025 17:12:28","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004176838","Men=
dong NB","","25-01-2025 16:10:57","25-01-2025 16:03:53","25-01-2025 17:43:2=
5","Grid ooutage.no space to deploy mobile gen//Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid ooutage.no sp=
ace to deploy mobile gen//Grid return","ludivine.ngamaleu@ihstowers.com","4=
24","25-01-2025 16:10:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004176835","L=
abogenie","","25-01-2025 16:10:36","25-01-2025 16:07:34","25-01-2025 18:34:=
44","Active//No power issue on site Ubaie=3D54.5V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed,Notice that it is the repetitive is=
sue","","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No power issue on site Ubaie=3D54.5V site on Gr=
id The Tx Fme Eloundou/693212405 of huawei is informed,Notice that it is th=
e repetitive issue","dorothy.djantio@ihstowers.com","183","25-01-2025 16:10=
:36","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004176800","Nko=
zoa","","25-01-2025 16:02:25","25-01-2025 15:52:59","25-01-2025 16:58:42","=
Grid outage, site went down due to gen overload (20kva, 340A) // He reduced=
 the load and gen manually started SS HIS Felix bateu is informed and confi=
rmed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, site went down due to gen overload (20kva, 340A) // He=
 reduced the load and gen manually started SS HIS Felix bateu is informed a=
nd confirmed","ludivine.ngamaleu@ihstowers.com","567","25-01-2025 16:02:25"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004176681","Mes=
sa Carriere","","25-01-2025 15:50:16","25-01-2025 15:47:23","25-01-2025 16:=
21:23","Grid outage.gen failed to start due to card GE dysfunctionned //Gri=
d return ","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid outage.gen failed to start due to card GE dysfunctionn=
ed //Grid return ","ludivine.ngamaleu@ihstowers.com","174","25-01-2025 15:5=
0:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004176588","SAA 2","=
","25-01-2025 15:43:20","25-01-2025 15:30:29","25-01-2025 16:40:14","Cascad=
ed Incident from TTO4186017","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on grid with U=3D53v Gre=
goire(652070658) from Huawei is working on site","system","268482","25-01-2=
025 15:43:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004176552","S=
aa","IHS_YND_404","25-01-2025 15:42:30","25-01-2025 15:30:29","25-01-2025 1=
6:40:14","No power issue site on grid with U=3D53v Gregoire(652070658) from=
 Huawei is working on site","Parker Tchoup","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on grid with U=3D53v Gregoire(652070658) from Huawei is working on site","=
dorothy.djantio@ihstowers.com","722","25-01-2025 15:42:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004176476","S=
calom","","25-01-2025 15:37:51","25-01-2025 15:27:59","25-01-2025 17:17:40"=
,"Site went down because of dysjunction of  CB (125A)  causing by  iload in=
cresase// We rearmed CB and site on on grid (IHS Supervisor Felix Zambe is =
confirmed)","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Site went down because of dysjunction of  CB (125A)  causing by  =
iload incresase// We rearmed CB and site on on grid (IHS Supervisor Felix Z=
ambe is confirmed)","dorothy.djantio@ihstowers.com","593","25-01-2025 15:37=
:51","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004176277","NKO=
MEKUI OCM","","25-01-2025 15:24:51","25-01-2025 15:18:49","25-01-2025 16:20=
:20","No power issue on site U=3D54.5  V site on Gen.Site impacted by Mbank=
olo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
no power issue on site U=3D54.5  V site on Gen.Site impacted by Mbankolo Ca=
mtel and not managing by IHS","ludivine.ngamaleu@ihstowers.com","363","25-0=
1-2025 15:24:51","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004176239","Eko=
unou","","25-01-2025 15:14:21","25-01-2025 15:05:11","25-01-2025 16:32:54",=
"Site went down because PWC overload (24KW, 380A) SS IHS Pascaline Manda co=
nfirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because PWC overload=
 (24KW, 380A) SS IHS Pascaline Manda confirmed// Site stabilized","ludivine=
.ngamaleu@ihstowers.com","551","25-01-2025 15:14:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004176209","MEHANDAN=
","","25-01-2025 15:07:51","25-01-2025 15:00:39","25-01-2025 16:35:10","Cas=
caded Incident from TTO4185626","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to gen=
 overload (20kva, 260A) // He reduced the load and gen manually started SS =
HIS Pascaline Manda is informed and confirmed","system","284423","25-01-202=
5 15:07:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004176198","O=
dza II OCM","IHS_YND_528","25-01-2025 15:06:40","25-01-2025 15:00:39","25-0=
1-2025 16:35:10","Grid outage, site went down due to gen overload (20kva, 2=
60A) // He reduced the load and gen manually started SS HIS Pascaline Manda=
 is informed and confirmed","Albran Byorel","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, site went down due to gen overload=
 (20kva, 260A) // He reduced the load and gen manually started SS HIS Pasca=
line Manda is informed and confirmed","dorothy.djantio@ihstowers.com","363"=
,"25-01-2025 15:06:40","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0004176034","SIM=
BOCK BONAMBAPE","","25-01-2025 14:44:17","25-01-2025 14:40:45","25-01-2025 =
16:43:54","No power issue site on grid with U=3D51v site up at 02: 48 PM Mb=
ah Osiah from Huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on grid with U=3D51v site up at 02: 48 PM Mbah Osiah from Huawei is=
 informed","ludivine.ngamaleu@ihstowers.com","213","25-01-2025 14:44:17","S=
agemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004175893","Nko=
zoa","","25-01-2025 14:22:30","25-01-2025 14:20:15","25-01-2025 15:46:11","=
Grid outage, site went down due to gen overload (20kva, 340A) // He reduced=
 the load and gen manually started SS HIS Felix bateu is informed and confi=
rmed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, site went down due to gen overload (20kva, 340A) // He=
 reduced the load and gen manually started SS HIS Felix bateu is informed a=
nd confirmed","ludivine.ngamaleu@ihstowers.com","136","25-01-2025 14:22:30"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004175830","Eko=
unou","","25-01-2025 14:12:59","25-01-2025 14:03:53","25-01-2025 14:22:50",=
"Site went down because PWC overload (24KW, 380A) SS IHS Pascaline Manda co=
nfirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because PWC overload=
 (24KW, 380A) SS IHS Pascaline Manda confirmed// Site stabilized","ludivine=
.ngamaleu@ihstowers.com","547","25-01-2025 14:12:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004175753","E=
vodoula OCM","","25-01-2025 14:01:21","25-01-2025 13:58:19","25-01-2025 16:=
30:47","No power issue site on grid with U=3D50.7 v Mohamadou(691144435) fr=
om Huawei was working on site ","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue site on grid with U=3D50.7 v Mohamadou(691144435) from Huawei wa=
s working on site ","alexandre.kamal@ihstowers.com","183","25-01-2025 14:01=
:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004175517","SAA 2","=
","25-01-2025 13:22:21","25-01-2025 13:01:01","25-01-2025 13:02:01","Cascad=
ed Incident from TTO4184715","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue U=3D 54.3V site on Gr=
id The TX FME Gregoire(652070658) from Huawei is working on site","system",=
"263068","25-01-2025 13:22:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004175419","S=
aa","IHS_YND_726, IHS_YND_401, IHS_YND_404","25-01-2025 13:07:04","25-01-20=
25 13:01:01","25-01-2025 13:02:01","Active//No power issue U=3D 54.3V site =
on Grid The TX FME Gregoire(652070658) from Huawei is working on site","Par=
ker Tchoup","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue U=3D 54.3V site on Grid The =
TX FME Gregoire(652070658) from Huawei is working on site","alexandre.kamal=
@ihstowers.com","364","25-01-2025 13:07:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004175205","N=
kolda","","25-01-2025 12:37:37","25-01-2025 12:24:37","25-01-2025 13:34:37"=
,"Grid outage, site went down because gen start and stopped with Over frequ=
ency alarm ( unpruven alarm) // reset of gen card done and gen started","Al=
bran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage, site went down because gen start and stopped with Over frequ=
ency alarm ( unpruven alarm) // reset of gen card done and gen started","al=
exandre.kamal@ihstowers.com","781","25-01-2025 12:37:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004174561","C=
RH-Etoug-Ebe","","25-01-2025 11:18:01","25-01-2025 10:59:57","25-01-2025 10=
:59:58","Active : no power issue, site is on grid with Ubaie=3D53V, Mohamad=
ou (691144435) from Huawei is infomred","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 : no power issue, site is on grid with Ubaie=3D53V, Mohamadou (691144435) =
from Huawei is infomred","alexandre.kamal@ihstowers.com","1085","25-01-2025=
 11:18:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004174558","MEHANDAN=
","","25-01-2025 11:17:31","25-01-2025 11:01:20","25-01-2025 11:35:20","Cas=
caded Incident from TTO4183734","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid bad voltage, Site went down becau=
se Gen failed to start due to ATS disfunction// He bypassed Grid and ATS an=
d started Gen manualy","system","270256","25-01-2025 11:17:31","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004174550","O=
dza II OCM","IHS_YND_528","25-01-2025 11:16:40","25-01-2025 11:01:20","25-0=
1-2025 11:35:20","Grid bad voltage, Site went down because Gen failed to st=
art due to ATS disfunction// He bypassed Grid and ATS and started Gen manua=
ly","Albran Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF I=
ssue","Grid bad voltage, Site went down because Gen failed to start due to =
ATS disfunction// He bypassed Grid and ATS and started Gen manualy","alexan=
dre.kamal@ihstowers.com","922","25-01-2025 11:16:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004174291","E=
kounou","","25-01-2025 10:29:32","25-01-2025 10:26:26","25-01-2025 12:04:26=
","site went down due to Pwc Huawei (20kilo) Overload (Pascaline from Ihs c=
onfirmed) // site stabilized","Albran Byorel","Equipment Repair","Passive",=
"Rectifier","Rectifier Module Overloaded","site went down due to Pwc Huawei=
 (20kilo) Overload (Pascaline from Ihs confirmed) // site stabilized","alex=
andre.kamal@ihstowers.com","187","25-01-2025 10:29:32","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004174153","Nko=
ulou Carriere carrefourt","","25-01-2025 10:06:51","25-01-2025 09:48:33","2=
5-01-2025 11:10:33","site went down due to disjunction Cb(2*63A) in PWC // =
He reamed Cb(2*36A), site on grid","Mba Lazare Herve","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went =
down due to disjunction Cb(2*63A) in PWC // He reamed Cb(2*36A), site on gr=
id","kamga.virgile@ihstowers.com","1099","25-01-2025 10:06:51","Sagemcom CM=
R"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004173972","Elo=
umdem stade","","25-01-2025 09:30:02","25-01-2025 09:10:26","25-01-2025 10:=
31:26","Site went down due to insuffiency of rectifiers, Felix from  IHS is=
 informed // site stabilized","Fanda Brice","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down due to insuffiency of rectifie=
rs, Felix from  IHS is informed // site stabilized","kamga.virgile@ihstower=
s.com","1177","25-01-2025 09:30:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004173881","E=
kounou","","25-01-2025 09:15:22","25-01-2025 09:07:20","25-01-2025 09:27:48=
","site went down due to Pwc Huawei (20kilo) Overload (Pascaline from Ihs c=
onfirmed) // site stabilized","Albran Byorel","Equipment Repair","Passive",=
"Rectifier","Rectifier Module Overloaded","site went down due to Pwc Huawei=
 (20kilo) Overload (Pascaline from Ihs confirmed) // site stabilized","alex=
andre.kamal@ihstowers.com","483","25-01-2025 09:15:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0004173745","N=
simalen OCM","","25-01-2025 08:58:09","25-01-2025 08:47:06","25-01-2025 08:=
47:07","ACTIVE//no power issue, site on grid U=3D54V on grid  tx FME Lionel=
 Steve ADJEP/655184876/ From huawei is informed","Albran Byorel","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE//no power issue, site on grid U=3D54V on grid  tx FME Lionel Steve=
 ADJEP/655184876/ From huawei is informed","alexandre.kamal@ihstowers.com",=
"664","25-01-2025 08:58:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004173643","L=
abogenie","","25-01-2025 08:39:06","25-01-2025 08:37:03","25-01-2025 08:50:=
03","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed,","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hu=
awei is informed,","alexandre.kamal@ihstowers.com","124","25-01-2025 08:39:=
06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004173555","C=
RH-Etoug-Ebe","","25-01-2025 08:21:50","25-01-2025 08:14:45","25-01-2025 08=
:19:01","Active : no power issue, site is on grid with Ubaie=3D53V, Mohamad=
ou (691144435) from Huawei is infomred","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 : no power issue, site is on grid with Ubaie=3D53V, Mohamadou (691144435) =
from Huawei is infomred","alexandre.kamal@ihstowers.com","426","25-01-2025 =
08:21:50","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004172714","AKA=
K Nkozoa","","25-01-2025 04:02:47","25-01-2025 03:34:41","25-01-2025 04:38:=
28","Site went down because CB (40A) of rectifiers tripped// CB put back on=
 (investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passive","R=
ectifier","Rectifier - Circuit Breaker","Site went down because CB (40A) of=
 rectifers tripped// CB put back on (investigation ongoing)","emmanuel.ghan=
i@ihstowers.com","1686","25-01-2025 04:02:47","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004172202","Eko=
unou","","25-01-2025 00:52:48","25-01-2025 00:47:43","25-01-2025 01:07:23",=
"Site went down because PWC overload (24KW, 380A) SS IHS Pascaline Manda co=
nfirmed// Site stabilized","Albran Byorel","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down because PWC overload=
 (24KW, 380A) SS IHS Pascaline Manda confirmed// Site stabilized","emmanuel=
.ghani@ihstowers.com","307","25-01-2025 00:52:48","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004171895","Lab=
oratoire  Meka","IHS_YND_193","24-01-2025 23:15:37","24-01-2025 23:07:34","=
24-01-2025 23:25:26","Grid outage No sp=E2ce to deploy MDG// Grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage No sp=E2ce to deploy MDG// Grid return","emmanuel.ghani@ihstowers.co=
m","484","24-01-2025 23:15:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004171806","E=
kounou","","24-01-2025 22:50:12","24-01-2025 22:41:06","24-01-2025 23:01:59=
","Site went down due to PWC overload( 24Kw,380 A) //Site Stabilized","Albr=
an Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module Overl=
oaded","Site went down due to PWC overload( 24Kw,380 A) //Site Stabilized",=
"christian.fonkou@ihstowers.com","547","24-01-2025 22:50:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004171189","C=
RH-Etoug-Ebe","","24-01-2025 21:06:23","24-01-2025 20:58:07","25-01-2025 00=
:35:26","Active//No power issue on site U=3D53V site on Grid , mouhamadou (=
691144435) of huawei is informed. Notice that we have disjunction at BTS OC=
M","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active//No power issue on site U=3D53V site=
 on Grid , mouhamadou (691144435) of huawei is informed. Notice that we hav=
e disjunction at BTS OCM","ange.kongo@ihstowers.com","497","24-01-2025 21:0=
6:23","Sagemcom CMR"
"Closed Complete","Site Down","T0211","IHS_YND_393","NOCINC0004171057","Eze=
zang","","24-01-2025 20:45:42","24-01-2025 20:38:33","24-01-2025 20:47:59",=
"Grid outage, Site went down because Gen failed to start and no alarm// Gen=
 manualy started (investigation ongoing)","Parker Tchoup","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down =
because Gen failed to start and no alarm// Gen manualy started (investigati=
on ongoing)","rouselle.schoune@ihstowers.com","546","24-01-2025 20:45:42","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004170897","L=
abogenie","","24-01-2025 20:18:40","24-01-2025 19:27:30","24-01-2025 23:48:=
30","Active//No power issue on site Ubaie=3D54.5V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed,","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue on site Ubaie=3D54.5V site on Grid The Tx Fme Eloundou/693212405 of hu=
awei is informed,","ange.kongo@ihstowers.com","3071","24-01-2025 20:18:40",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004170364","Lab=
oratoire  Meka","IHS_YND_193","24-01-2025 18:52:24","24-01-2025 18:44:17","=
24-01-2025 19:24:55","Grid Outage No Space to deploy a MDG//Grid Restored",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 Outage No Space to deploy a MDG//Grid Restored","ange.kongo@ihstowers.com"=
,"488","24-01-2025 18:52:24","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0004170355","Bas=
tos Ekoudou","","24-01-2025 18:50:13","24-01-2025 18:44:17","24-01-2025 23:=
25:26","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Outage No Space to deploy a MDG//Grid Restored","ange.k=
ongo@ihstowers.com","285453","24-01-2025 18:50:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004170195","Ngoulmek=
ong-Nord","","24-01-2025 18:20:50","24-01-2025 16:31:47","24-01-2025 17:37:=
18","Cascaded Incident from TTO4178602","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage,site went down bec=
ause Gen Overload(20kva 280A) SS IHS Blaise Raoul Confirmed it// Grid retur=
n","system","272082","24-01-2025 18:20:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004170181","E=
leveur","IHS_YND_277","24-01-2025 18:17:59","24-01-2025 16:31:47","24-01-20=
25 17:37:18","grid outage,site went down because Gen Overload(20kva 280A) S=
S IHS Blaise Raoul Confirmed it// Grid return","Siligap Boris","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","grid outage,site went down b=
ecause Gen Overload(20kva 280A) SS IHS Blaise Raoul Confirmed it// Grid ret=
urn","rouselle.schoune@ihstowers.com","6373","24-01-2025 18:17:59","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004169808","M=
essa-Carriere OCM","","24-01-2025 17:12:48","24-01-2025 17:05:39","24-01-20=
25 19:04:56","Site went down because 2 CB(125A) tripped in DC BOX due to lo=
ad increase// CB put back on","","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Circuit Breaker Issue","Site went down because 2 CB(125=
A) tripped in DC BOX due to load increase// CB put back on","rouselle.schou=
ne@ihstowers.com","430","24-01-2025 17:12:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0004169305","Entree C=
ite Verte","","24-01-2025 16:13:33","24-01-2025 16:01:59","24-01-2025 17:27=
:09","Cascaded Incident from TTO4177550","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage//MDG 20 Kva deploye=
d","system","266629","24-01-2025 16:13:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0004169303","Nkomkana=
 2","","24-01-2025 16:13:32","24-01-2025 16:01:59","24-01-2025 17:27:09","C=
ascaded Incident from TTO4177550","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage//MDG 20 Kva deployed","s=
ystem","266630","24-01-2025 16:13:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0004169304","Nkomkana=
","","24-01-2025 16:13:32","24-01-2025 16:01:59","24-01-2025 17:27:09","Cas=
caded Incident from TTO4177550","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","grid outage//MDG 20 Kva deployed","system","266629"=
,"24-01-2025 16:13:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0004169281","C=
ite-Verte","IHS_YND_138, IHS_YND_200, IHS_YND_543","24-01-2025 16:11:48","2=
4-01-2025 16:01:59","24-01-2025 16:29:09","grid outage//MDG 20 Kva deployed=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","gr=
id outage//MDG 20 Kva deployed","rouselle.schoune@ihstowers.com","590","24-=
01-2025 16:11:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_744","NOCINC0004168998","Eleveur =
Meec Bon Berger","","24-01-2025 15:23:20","24-01-2025 15:09:58","24-01-2025=
 15:23:52","Cascaded Incident from TTO4177174","Siligap Boris","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","grid bad voltage,and ge=
n failed to start,no rcp//bypassed grid and started the gen","system","2695=
32","24-01-2025 15:23:20","Sagemcom CMR"
"Closed Complete","Site Down","T1832","IHS_YND_216","NOCINC0004168983","Ele=
veur","IHS_YND_744","24-01-2025 15:20:16","24-01-2025 15:09:58","24-01-2025=
 15:23:52","grid bad voltage,and gen failed to start,no rcp//bypassed grid =
and started the gen","Siligap Boris","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","grid bad voltage,and gen failed to star=
t,no rcp//bypassed grid and started the gen","ange.kongo@ihstowers.com","61=
9","24-01-2025 15:20:16","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004168647","Nko=
zoa","","24-01-2025 14:39:11","24-01-2025 14:22:00","24-01-2025 14:46:35","=
Grid outage, site went down due to gen overload (20kva, 340A) // He reduced=
 the load and gen manually started SS HIS Felix bateu is informed and confi=
rmed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, site went down due to gen overload (20kva, 340A) // He=
 reduced the load and gen manually started SS HIS Felix bateu is informed a=
nd confirmed","ange.kongo@ihstowers.com","1033","24-01-2025 14:39:11","Sage=
mcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004168521","Tou=
ring Club International","","24-01-2025 14:20:59","24-01-2025 14:03:49","24=
-01-2025 15:18:01","site went down because CB 2*50A who feeds equipment MTN=
 faulty in Pwc//he changed it with another CB 125A","Albran Byorel","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issu=
e","site went down because CB 2*50A who feeds equipment MTN faulty in Pwc//=
he changed it with another CB 125A","ludivine.ngamaleu@ihstowers.com","1031=
","24-01-2025 14:20:59","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004167822","Obo=
bogo","","24-01-2025 12:35:28","24-01-2025 12:30:23","24-01-2025 13:30:43",=
"No power issue site on gen with U=3D54.7v Mbah osiah from Huawei is inform=
ed site up at 12:35 PM","MINKA NICOLAS","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
gen with U=3D54.7v Mbah osiah from Huawei is informed site up at 12:35 PM",=
"ludivine.ngamaleu@ihstowers.com","306","24-01-2025 12:35:28","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004167625","S=
aa","IHS_YND_404","24-01-2025 12:05:45","24-01-2025 11:48:31","24-01-2025 1=
2:25:13","No power issue site on gen with U=3D55v Gregoire(652070658) from =
Huawei is working on site ","Parker Tchoup","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on gen with U=3D55v Gregoire(652070658) from Huawei is working on site ","=
olivier.kwedi@ihstowers.com","1035","24-01-2025 12:05:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004167349","D=
amas","","24-01-2025 11:26:42","24-01-2025 11:19:38","24-01-2025 11:47:53",=
"Site went down due to work: by Technician Herman Abena/677793603 from GRAT=
O IS  working on site ( Switching of poweron DC Box)// End of work","MINKA =
NICOLAS","Installation Activity","Passive","Planned Activity","Installation=
 Activity","Site went down due to work: by Technician Herman Abena/67779360=
3 from GRATO IS  working on site ( Switching of poweron DC Box)// End of wo=
rk","dorothy.djantio@ihstowers.com","425","24-01-2025 11:26:42","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004167313","N=
kozoa","","24-01-2025 11:21:29","24-01-2025 11:00:12","24-01-2025 12:14:42"=
,"Grid outage, site went down because gen Overload(20KVA, 340A) (Felix Bate=
u ihs confirm) // We reduce load(put off BTS CAMTEL) and site on gen","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gri=
d outage, site went down because gen Overload(20KVA, 340A) (Felix Bateu ihs=
 confirm) // We reduce load(put off BTS CAMTEL) and site on gen","olivier.k=
wedi@ihstowers.com","1279","24-01-2025 11:21:29","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0004166838","EMA=
NA BILICK CITY","","24-01-2025 10:23:57","24-01-2025 10:17:22","26-01-2025 =
18:58:33","Site went down due to ""Desire(677549842) from IHS and IHS super=
visor Bernard Atangana are working on site from dismantling site // Power R=
estored to the New Site ","Fabrice Pouakam","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to ""Desi=
re(677549842) from IHS and IHS supervisor Bernard Atangana are working on s=
ite from dismantling site // Power Restored to the New Site ","ludivine.nga=
maleu@ihstowers.com","908","24-01-2025 10:23:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004165848","N=
kozoa","","24-01-2025 08:37:49","24-01-2025 08:36:44","24-01-2025 09:17:59"=
,"Grid outage, site went down because gen Overload(20KVA, 340A) (Felix Bate=
u ihs confirm) // site stabilized","Fabrice Pouakam","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Grid outage, site went down because ge=
n Overload(20KVA, 340A) (Felix Bateu ihs confirm) // site stabilized","doro=
thy.djantio@ihstowers.com","66","24-01-2025 08:37:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004165528","S=
aa","IHS_YND_810, IHS_YND_809, IHS_YND_401, IHS_YND_404","24-01-2025 07:43:=
22","24-01-2025 07:41:16","24-01-2025 07:50:43"," site went down because ge=
n fails due to disjunction of CB(25 A) GEN // CB put back on ","Parker Tcho=
up","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit B=
reaker Issue"," site went down because gen fails due to disjunction of CB(2=
5 A) GEN // CB put back on ","dorothy.djantio@ihstowers.com","127","24-01-2=
025 07:43:22","Sagemcom CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0004165513","Car=
refour Ayissi Ele","","24-01-2025 07:38:24","24-01-2025 07:41:16","24-01-20=
25 07:50:43","","Parker Tchoup","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive"," site went down because gen fails due to disjunction o=
f CB(25 A) GEN // CB put back on ","ludivine.ngamaleu@ihstowers.com","27501=
5","24-01-2025 07:38:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004165512","S=
AA 2","","24-01-2025 07:38:23","24-01-2025 07:41:16","24-01-2025 11:50:27",=
"","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve"," site went down because gen fails due to disjunction of CB(25 A) GEN /=
/ CB put back on ","dorothy.djantio@ihstowers.com","282319","24-01-2025 07:=
38:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004165486","L=
abogenie","","24-01-2025 07:31:29","24-01-2025 07:25:19","24-01-2025 08:53:=
49","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed. Repetitive Issue site up at 07:33 =
AM","","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No power issue on site Ubaie=3D54.6V site on Gri=
d The Tx Fme Eloundou/693212405 of huawei is informed. Repetitive Issue sit=
e up at 07:33 AM","dorothy.djantio@ihstowers.com","371","24-01-2025 07:31:2=
9","Sagemcom CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004165336","Nko=
l-Mebanga","","24-01-2025 07:02:23","24-01-2025 07:41:16","24-01-2025 07:50=
:43","FME will be manage after Saa","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive"," site went down because gen fails =
due to disjunction of CB(25 A) GEN // CB put back on ","ludivine.ngamaleu@i=
hstowers.com","275015","24-01-2025 07:02:23","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0004164358","Lad=
a I Yde","","24-01-2025 02:21:37","24-01-2025 02:16:26","24-01-2025 02:34:5=
6","Grid outage, Site went down because Gen failed to start due to Gen Batt=
ery discharged// He started Gen manualy with external battery (investigatio=
n ongoing)","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Generator Battery","Grid outage, Site went down because Gen failed to s=
tart due to Gen Battery discharged// He started Gen manualy with external b=
attery (investigation ongoing)","stephane.nkamwa@ihstowers.com","312","24-0=
1-2025 02:21:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_098","NOCINC0004163598","Ekounou"=
,"","23-01-2025 23:13:50","23-01-2025 23:06:38","24-01-2025 02:11:49","Casc=
aded Incident from TTO4170879","Albran Byorel","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Access Issue during the Night due to La=
ndlord","system","313078","23-01-2025 23:13:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0004163599","Nkoa Ayo=
s","","23-01-2025 23:13:50","23-01-2025 23:06:38","24-01-2025 02:11:49","Ca=
scaded Incident from TTO4170879","MINKA NICOLAS","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Access Issue during the Night due to =
Landlord","system","313078","23-01-2025 23:13:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0004163594","G=
SO","IHS_YND_098, IHS_YND_067","23-01-2025 23:12:44","23-01-2025 23:06:38",=
"24-01-2025 12:50:49","No power issue site on grid with U=3D54.5v  Eloundou=
 Bertrand(693212405) from Huawei is informed","MINKA NICOLAS","Access Denia=
l","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","A=
ccess Issue during the Night due to Landlord(No power issue site on grid wi=
th U=3D54.5v  Eloundou Bertrand(693212405) from Huawei is informed)","rouse=
lle.schoune@ihstowers.com","366","23-01-2025 23:12:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004163455","L=
abogenie","","23-01-2025 22:51:48","23-01-2025 22:45:43","23-01-2025 23:30:=
20","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed. Repetitive Issue","","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundo=
u/693212405 of huawei is informed. Repetitive Issue","rouselle.schoune@ihst=
owers.com","366","23-01-2025 22:51:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004163312","MEHANDAN=
","","23-01-2025 22:29:10","23-01-2025 22:27:34","23-01-2025 23:36:21","Cas=
caded Incident from TTO4170557","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid bad voltage, Site went down becau=
se Gen failed to start due to ATS disfunction// He bypassed Grid and ATS an=
d started Gen manualy","system","272040","23-01-2025 22:29:10","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004163309","O=
dza II OCM","IHS_YND_528","23-01-2025 22:28:38","23-01-2025 22:27:34","24-0=
1-2025 00:09:21","Grid bad voltage, Site went down because Gen failed to st=
art due to ATS disfunction// He bypassed Grid and ATS and started Gen manua=
ly","Albran Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF I=
ssue","Grid bad voltage, Site went down because Gen failed to start due to =
ATS disfunction// He bypassed Grid and ATS and started Gen manualy","rousel=
le.schoune@ihstowers.com","65","23-01-2025 22:28:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004162954","N=
kozoa","","23-01-2025 21:32:07","23-01-2025 21:30:03","23-01-2025 21:34:24"=
,"Grid fluctuation site went down because Gen failed to start due to Grid b=
ad voltage and  no RCP on site // He bypass the Grid and Gen manually start=
e","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid fluctuation site went down because Gen failed to s=
tart due to Grid bad voltage and  no RCP on site // He bypass the Grid and =
Gen manually starte","christian.fonkou@ihstowers.com","126","23-01-2025 21:=
32:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004162935","S=
calom","","23-01-2025 21:28:57","23-01-2025 21:21:52","23-01-2025 22:56:10"=
,"Site went due to insufficience of rectifiers SS IHS Felix ZAMBE confirmed=
// Site stabilized","Paul BIBOUM","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site went due to insufficience of rectifiers SS IHS Fel=
ix ZAMBE confirmed// Site stabilized","christian.fonkou@ihstowers.com","426=
","23-01-2025 21:28:57","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004162239","Jou=
vence Mbenda","","23-01-2025 19:59:52","23-01-2025 19:55:20","23-01-2025 21=
:37:45","Grid fluctuation site went down because Gen failed to start due to=
 Grid bad voltage and  no RCP on site // Grid stabilized","Hyemafo Gildas",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid fluctuation site went down because Gen failed to start due to Grid bad =
voltage and  no RCP on site // Grid stabilized","emmanuel.ghani@ihstowers.c=
om","273","23-01-2025 19:59:52","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004162024","Nko=
abang MTN","","23-01-2025 19:30:09","23-01-2025 19:28:55","23-01-2025 20:24=
:22","instabillity on nsite because 04/06 rectifier on site dysfonction due=
 to Cb(10A)  the air extractor dysjoncted // He reamed the Cb and reset the=
 rectifier","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","instabillity on nsite because 04/06 rectifier on site dysf=
onction due to Cb(10A)  the air extractor dysjoncted // He reamed the Cb an=
d reset the rectifier","emmanuel.ghani@ihstowers.com","75","23-01-2025 19:3=
0:09","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004161981","NKO=
MEKUI OCM","","23-01-2025 19:22:45","23-01-2025 19:13:41","23-01-2025 19:25=
:36","ACTIVE//No power issue on site U=3D54,5v site on gen site down becaus=
e is impacted by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCH=
IEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure",=
"Affected by 3rd Party Site","ACTIVE//No power issue on site U=3D54,5v site=
 on gen site down because is impacted by Mbankolo Camtel and not managing b=
y IHS","emmanuel.ghani@ihstowers.com","545","23-01-2025 19:22:45","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004161878","Mes=
sassi okolo","","23-01-2025 19:07:49","23-01-2025 19:01:42","23-01-2025 19:=
51:50","grid outage,gen stopped with alarm low oil pressure//he added oil a=
nd started the gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Low Oil Pressure","grid outage,gen stopped with alarm low oil pr=
esssure//he added oil and started the gen","emmanuel.ghani@ihstowers.com","=
368","23-01-2025 19:07:49","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004161580","Ema=
na","","23-01-2025 18:14:45","23-01-2025 18:12:26","23-01-2025 18:24:58","G=
rid outage,site went down before gen starts due to poor battery backup//Gen=
 started automatically","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage,site went down befor=
e gen starts due to poor battery backup//Gen started automatically","emmanu=
el.ghani@ihstowers.com","140","23-01-2025 18:14:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0004160448","N=
kolafeme","","23-01-2025 16:09:59","23-01-2025 16:01:54","23-01-2025 16:54:=
39","grid outage,gen stopped with alarm high temp//he added water in radiat=
or","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACD=
G - High Engine Temp - Coolant Level Issue","grid outage,gen stopped with a=
larm high temp//he added water in radiator","christian.fonkou@ihstowers.com=
","486","23-01-2025 16:09:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004160422","Eseka To=
wn","","23-01-2025 16:07:15","23-01-2025 15:55:29","23-01-2025 16:01:21","C=
ascaded Incident from TTO4167067","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work: Our Te=
chnician Marcel/657108566/SA and SS Daniel wakam GEMCOM working on site ( S=
WAP OF BATTERY )// End of work","system","274195","23-01-2025 16:07:15","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0004160419","Eseka MT=
N","","23-01-2025 16:07:14","23-01-2025 15:55:29","23-01-2025 16:01:21","Ca=
scaded Incident from TTO4167067","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work: Our Tec=
hnician Marcel/657108566/SA and SS Daniel wakam GEMCOM working on site ( SW=
AP OF BATTERY )// End of work","system","274194","23-01-2025 16:07:14","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0004160413","Ndogbess=
ol","","23-01-2025 16:07:13","23-01-2025 15:55:29","23-01-2025 16:01:21","C=
ascaded Incident from TTO4167067","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work: Our Te=
chnician Marcel/657108566/SA and SS Daniel wakam GEMCOM working on site ( S=
WAP OF BATTERY )// End of work","system","274197","23-01-2025 16:07:13","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0004160409","Boumnyeb=
el","","23-01-2025 16:07:12","23-01-2025 15:55:29","23-01-2025 16:01:21","C=
ascaded Incident from TTO4167067","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work: Our Te=
chnician Marcel/657108566/SA and SS Daniel wakam GEMCOM working on site ( S=
WAP OF BATTERY )// End of work","system","274193","23-01-2025 16:07:12","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_416","NOCINC0004160403","Ngwopi B=
oga","","23-01-2025 16:07:11","23-01-2025 15:55:29","23-01-2025 16:01:21","=
Cascaded Incident from TTO4167067","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to work: Our T=
echnician Marcel/657108566/SA and SS Daniel wakam GEMCOM working on site ( =
SWAP OF BATTERY )// End of work","system","274199","23-01-2025 16:07:11","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0004160405","Ngoung",=
"","23-01-2025 16:07:11","23-01-2025 15:55:29","23-01-2025 16:01:21","Casca=
ded Incident from TTO4167067","Kemeni Franklin","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work: Our Techni=
cian Marcel/657108566/SA and SS Daniel wakam GEMCOM working on site ( SWAP =
OF BATTERY )// End of work","system","274191","23-01-2025 16:07:11","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0004160404","Mamb",""=
,"23-01-2025 16:07:11","23-01-2025 15:55:29","23-01-2025 16:01:21","Cascade=
d Incident from TTO4167067","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to work: Our Technici=
an Marcel/657108566/SA and SS Daniel wakam GEMCOM working on site ( SWAP OF=
 BATTERY )// End of work","system","274196","23-01-2025 16:07:11","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_781","NOCINC0004160402","BIBOMDJI=
DJIEL","","23-01-2025 16:07:11","23-01-2025 15:55:29","23-01-2025 16:01:21"=
,"Cascaded Incident from TTO4167067","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to work: Our=
 Technician Marcel/657108566/SA and SS Daniel wakam GEMCOM working on site =
( SWAP OF BATTERY )// End of work","system","274195","23-01-2025 16:07:11",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0004160386","L=
eboudi","","23-01-2025 16:06:10","23-01-2025 15:59:02","23-01-2025 16:00:16=
","Active//No power issue on site Ubaie=3D54.3V site on Gen THE fme Tx Moua=
madou /691 144 435/ Huawei is informed and Site Up at=3D04:54 PM","TIENTCHE=
U NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie=3D54.3V =
site on Gen THE fme Tx Mouamadou /691 144 435/ Huawei is informed and Site =
Up at=3D04:54 PM","christian.fonkou@ihstowers.com","430","23-01-2025 16:06:=
10","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004160194","ODZ=
A MINKAN EDIBI ASSI","","23-01-2025 15:40:13","23-01-2025 15:38:08","23-01-=
2025 16:02:43","Grid outage, Site went down because Gen started and stopped=
 due to pipe line pierced// Grid power return (pipe line to be repaired)","=
Albran Byorel","Fuel Outage (Probable)","Passive","Diesel","Fuel Line Issue=
","Grid outage, Site went down because Gen started and stopped due to pipe =
line pierced// Grid power return (pipe line to be repaired)","emmanuel.ghan=
i@ihstowers.com","126","23-01-2025 15:40:13","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004159857","Nsi=
meyong Terre Rouge","","23-01-2025 14:57:08","23-01-2025 14:50:03","23-01-2=
025 15:02:30","Grid fluctuation, site went down before gen start due to poo=
r battery backup // Gen start automatically","MINKA NICOLAS","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid fluctuat=
ion, site went down before gen start due to poor battery backup // Gen star=
t automatically","emmanuel.ghani@ihstowers.com","426","23-01-2025 14:57:08"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004159333","Saa","",=
"23-01-2025 13:42:50","23-01-2025 13:34:07","23-01-2025 13:44:31","Cascaded=
 Incident from TTO4165904","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","No Power issue on site , site on Grid with Uba=
ie=3D54.1V The Tx Gregoire(654547479) from Huawei is informed","system","26=
8085","23-01-2025 13:42:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004159332","SAA Entr=
ance","","23-01-2025 13:42:50","23-01-2025 13:34:07","23-01-2025 13:44:31",=
"Cascaded Incident from TTO4165904","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No Power issue on site , site on Grid=
 with Ubaie=3D54.1V The Tx Gregoire(654547479) from Huawei is informed","sy=
stem","268086","23-01-2025 13:42:50","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004159330","SAA=
 2","IHS_YND_542, IHS_YND_405","23-01-2025 13:41:34","23-01-2025 13:34:07",=
"23-01-2025 15:10:31","No Power issue on site , site on Grid with Ubaie=3D5=
4.1V The Tx Gregoire(654547479) from Huawei is informed","Parker Tchoup","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No Power issue on site , site on Grid with Ubaie=3D54.1V The Tx G=
regoire(654547479) from Huawei is informed","ange.kongo@ihstowers.com","448=
","23-01-2025 13:41:34","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004159194","Elo=
umdem stade","","23-01-2025 13:14:28","23-01-2025 13:07:17","23-01-2025 13:=
29:24","site went down because the insufficient the rectifier (02) on site =
// Site stabilized","Fanda Brice","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","site went down because the insufficient the rectifier (=
02) on site // Site stabilized","ange.kongo@ihstowers.com","432","23-01-202=
5 13:14:28","Sagemcom CMR"
"Closed Complete","Site Down","T0566","IHS_YND_421","NOCINC0004159092","Bot=
 Makak","IHS_EDA_101","23-01-2025 13:01:48","23-01-2025 12:56:34","23-01-20=
25 12:57:57","No power issue site on grid with U=3D54.5v//site up at 01:41 =
PM Etienne(695033981) from Huawei is informed ","","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on grid with U=3D54.5v//site up at 01:41 PM Etienne(695033981) from=
 Huawei is informed ","ange.kongo@ihstowers.com","315","23-01-2025 13:01:48=
","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004158998","NYO=
M FACE MAETUR","","23-01-2025 12:45:25","23-01-2025 12:37:19","23-01-2025 1=
3:11:58","Grid fluctuation,Site went down because gen fail to start due  to=
 grid bad voltages//We bypass grid and Gen manually started","Fabrice Pouak=
am","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation,Site went down because gen fail to start due  to grid b=
ad voltages//We bypass grid and Gen manually started","ange.kongo@ihstowers=
.com","488","23-01-2025 12:45:25","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004158996","SOA=
 UNIVERSITY STADIUM","","23-01-2025 12:44:38","23-01-2025 12:35:29","23-01-=
2025 13:21:49","grid outage, site went down due to dysfunctionning of PWC Z=
TE // Gen manually started","Siligap Boris","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","grid outage, site went down due to=
 dysfunctionning of PWC ZTE // Gen manually started","ange.kongo@ihstowers.=
com","550","23-01-2025 12:44:38","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004158427","NKO=
MEKUI OCM","","23-01-2025 11:27:48","23-01-2025 11:24:39","23-01-2025 11:59=
:22","Active// no power issue on site U=3D54.5  V site on Gen.Site impacted=
 by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active// no power issue on site U=3D54.5  V site on Gen.Site impac=
ted by Mbankolo Camtel and not managing by IHS","ange.kongo@ihstowers.com",=
"190","23-01-2025 11:27:48","Sagemcom CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0004158172","Nko=
lfon Cimencam","","23-01-2025 10:56:16","23-01-2025 10:50:51","23-01-2025 1=
2:38:15","Grid outage .gen failed to start due to battery GE discharged cau=
sng by static charger faulty//Gen manually started with external battery","=
Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Generator B=
attery","Grid outage .gen failed to start due to battery GE discharged caus=
ng by static charger faulty//Gen manually started with external battery","a=
nge.kongo@ihstowers.com","536","23-01-2025 10:56:16","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004156882","Elo=
umdem stade","","23-01-2025 07:59:22","23-01-2025 07:55:13","23-01-2025 08:=
06:06","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // he bypass grid and manually start the gen","Fanda Br=
ice","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, site went down because gen start and stopped due to g=
rid bad voltage // he bypass grid and manually start the gen","ange.kongo@i=
hstowers.com","250","23-01-2025 07:59:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_809","NOCINC0004155756","Nkol-Meb=
anga","","23-01-2025 03:22:41","23-01-2025 03:09:27","23-01-2025 04:48:27",=
"Cascaded Incident from TTO4161818","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // refueling done","system","269563","23-01-=
2025 03:22:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004155757","Saa","",=
"23-01-2025 03:22:41","23-01-2025 03:09:27","23-01-2025 04:48:27","Cascaded=
 Incident from TTO4161818","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen ran=
 untill fuel shortage // refueling done","system","269562","23-01-2025 03:2=
2:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004155755","SAA Entr=
ance","","23-01-2025 03:22:41","23-01-2025 03:09:27","23-01-2025 04:48:27",=
"Cascaded Incident from TTO4161818","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // refueling done","system","269562","23-01-=
2025 03:22:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0004155754","Carrefou=
r Ayissi Ele","","23-01-2025 03:22:40","23-01-2025 03:09:27","23-01-2025 04=
:48:27","Cascaded Incident from TTO4161818","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage, site went dow=
n because gen ran untill fuel shortage // refueling done","system","269564"=
,"23-01-2025 03:22:40","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004155751","SAA=
 2","IHS_YND_810, IHS_YND_542, IHS_YND_809, IHS_YND_405","23-01-2025 03:21:=
36","23-01-2025 03:04:57","23-01-2025 04:48:27","Grid outage, site went dow=
n because gen ran untill fuel shortage // refueling done","Parker Tchoup","=
Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, site went dow=
n because gen ran untill fuel shortage // refueling done","kamga.virgile@ih=
stowers.com","3854","23-01-2025 03:21:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004155306","M=
ontee-Des-Soeurs","","23-01-2025 01:20:50","23-01-2025 01:04:43","23-01-202=
5 01:05:43","No power Issue Site on Grid Ubai =3D54.3V, The FME The TX FME =
Mbah Hosiah (674007438) is informed.","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 Issue Site on Grid Ubai =3D54.3V, The FME The TX FME Mbah Hosiah (67400743=
8) is informed.","alexandre.kamal@ihstowers.com","968","23-01-2025 01:20:50=
","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004155264","Elo=
umdem stade","","23-01-2025 01:12:50","23-01-2025 00:32:22","23-01-2025 01:=
23:22","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // he bypass grid and manually start the gen","Fanda Br=
ice","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, site went down because gen start and stopped due to g=
rid bad voltage // he bypass grid and manually start the gen","kamga.virgil=
e@ihstowers.com","2429","23-01-2025 01:12:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0004155152","E=
BOM","","23-01-2025 00:34:42","23-01-2025 00:23:28","23-01-2025 00:24:28","=
ACTIVE / No power issue site on Grid with U=3D50,5 V The Tx FME Tchana Patr=
ice 695007608 of huawei is informed","Hyemafo Gildas","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE / =
No power issue site on Grid with U=3D50,5 V The Tx FME Tchana Patrice 69500=
7608 of huawei is informed","alexandre.kamal@ihstowers.com","675","23-01-20=
25 00:34:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004154810","L=
abogenie","","22-01-2025 23:22:57","22-01-2025 23:11:54","22-01-2025 23:12:=
54","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed, site up at 11:29 PM","","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme Elou=
ndou/693212405 of huawei is informed, site up at 11:29 PM","alexandre.kamal=
@ihstowers.com","665","22-01-2025 23:22:57","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004154731","Aka=
k-Nkozoa-MTN-IHS","","22-01-2025 22:59:20","22-01-2025 22:46:10","22-01-202=
5 23:06:10","Grid outage site went down because Gen Oerload(20kva; 250A), S=
S IHS Felix Bateur is informed and confirmed)// Grid return (Power limitati=
on to be upgraded)","Fabrice Pouakam","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","Grid outage site went down because Gen Oerload(20kva;=
 250A), SS IHS Felix Bateur is informed and confirmed)// Grid return (Power=
 limitation to be upgraded)","kamga.virgile@ihstowers.com","792","22-01-202=
5 22:59:20","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004154698","Elo=
umdem stade","","22-01-2025 22:52:15","22-01-2025 22:28:59","22-01-2025 23:=
10:59","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // he bypass grid and manually start the gen","Fanda Br=
ice","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id fluctuation, site went down because gen start and stopped due to grid ba=
d voltage // he bypass grid and manually start the gen","kamga.virgile@ihst=
owers.com","1397","22-01-2025 22:52:15","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004154462","NYO=
M FACE MAETUR","","22-01-2025 22:04:08","22-01-2025 21:39:54","22-01-2025 2=
2:59:54","Site went down because CB(80A*63A) disjuncted  in DC BOX // He ma=
de a reverse bridge on the same CB(80A*63A), site on Grid","Fabrice Pouakam=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Bre=
aker Issue","Site went down because CB(80A*63A) disjuncted  in DC BOX // He=
 made a reverse bridge on the same CB(80A*63A), site on Grid","stephane.nka=
mwa@ihstowers.com","1455","22-01-2025 22:04:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004154285","SOA VILL=
AGE","","22-01-2025 21:31:20","22-01-2025 21:17:20","22-01-2025 21:28:58","=
Cascaded Incident from TTO4160057","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause gen start and stopped due to grid bad voltage // he bypass grid and m=
anually start the gen","system","1232963","22-01-2025 21:31:20","Sagemcom C=
MR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004154253","SOA=
 TOWN","IHS_YND_323","22-01-2025 21:28:39","22-01-2025 21:17:20","22-01-202=
5 21:28:58","Grid fluctuation, site went down because gen start and stopped=
 due to grid bad voltage // he bypass grid and manually start the gen","Sil=
igap Boris","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation, site went down because gen start and stopped d=
ue to grid bad voltage // he bypass grid and manually start the gen","steph=
ane.nkamwa@ihstowers.com","680","22-01-2025 21:28:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0004154156","N=
simalen OCM","","22-01-2025 21:17:16","22-01-2025 20:45:03","22-01-2025 20:=
46:03","Active // no power issue on site U=3D52.1V on Gen, TX FME LIONEL ST=
EVE ADJEP/ 655184876 From huawei is informed","Albran Byorel","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive // no power issue on site U=3D52.1V on Gen, TX FME LIONEL STEVE ADJEP=
/ 655184876 From huawei is informed","kouoh.jean@ihstowers.com","1934","22-=
01-2025 21:17:16","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004154050","NKO=
MEKUI OCM","","22-01-2025 20:58:56","22-01-2025 20:50:50","22-01-2025 20:55=
:36","Active// no power issue on site U=3D54.5  V site on Gen.Site impacted=
 by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active// no power issue on site U=3D54.5  V site on Gen.Site impac=
ted by Mbankolo Camtel and not managing by IHS","stephane.nkamwa@ihstowers.=
com","487","22-01-2025 20:58:56","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004153854","NYO=
M FACE MAETUR","","22-01-2025 20:30:02","22-01-2025 20:20:49","22-01-2025 2=
1:32:48","Grid fluctuation, site went down because gen failed to start due =
to lack of 01 phase // He did a bridge with a good phase","Fabrice Pouakam"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid fluctuation, site went down because gen failed to start due to lack of=
 01 phase // He did a bridge with a good phase","stephane.nkamwa@ihstowers.=
com","555","22-01-2025 20:30:02","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004153442","Crf=
-Mbankolo-IHS","","22-01-2025 19:31:16","22-01-2025 19:28:07","22-01-2025 1=
9:34:45","Site went down due to MPR disfunction and causing alarming of rec=
tifers SS IHS Bernard Atangana is informed and confirmed// Site stabilized"=
,"Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Distri=
bution","Site went down due to MPR disfunction and causing alarming of rect=
ifers SS IHS Bernard Atangana is informed and confirmed// Site stabilized",=
"stephane.nkamwa@ihstowers.com","190","22-01-2025 19:31:16","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004153315","Aka=
k-Nkozoa-MTN-IHS","","22-01-2025 19:05:47","22-01-2025 18:54:35","22-01-202=
5 20:21:51","Site went down because CB (125A*125A) who feeds equipments MTN=
 tripped in PWC  due to Grid bad voltage// CB put back on and Gen started m=
anualy","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Circuit Breaker Issue","Site went down because CB (125A*125A) =
who feeds equipments MTN tripped in PWC  due to Grid bad voltage// CB put b=
ack on and Gen started manualy","stephane.nkamwa@ihstowers.com","673","22-0=
1-2025 19:05:47","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004153220","ODZ=
A MINKAN EDIBI ASSI","","22-01-2025 18:44:45","22-01-2025 18:38:34","22-01-=
2025 19:19:43","Grid outage, site went down Gen failed to start due to ATS =
dysfonction // He started Gen manualy ","Albran Byorel","Equipment Repair",=
"Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down Gen =
failed to start due to ATS dysfonction // He started Gen manualy ","stephan=
e.nkamwa@ihstowers.com","372","22-01-2025 18:44:45","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0004153078","Nko=
zoa","","22-01-2025 18:22:54","22-01-2025 18:19:47","22-01-2025 19:50:39","=
Site went down because 2CB(16A*16A) tripped in PWC who feeds equipments MTN=
// He replaced it by 2CB(63A*63A)","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went d=
own because 2CB(16A*16A) tripped in PWC who feeds equipments MTN// He repla=
ced it by 2CB(63A*63A)","stephane.nkamwa@ihstowers.com","188","22-01-2025 1=
8:22:54","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004152976","Aka=
k-Nkozoa-MTN-IHS","","22-01-2025 17:55:28","22-01-2025 17:48:18","22-01-202=
5 18:06:32","Grid fluctuation site went down because Gen failed to start du=
e to Grid bad voltage // He bypassed Grid and started Gen manualy","Fabrice=
 Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation site went down because Gen failed to start due to=
 Grid bad voltage // He bypassed Grid and started Gen manualy","stephane.nk=
amwa@ihstowers.com","431","22-01-2025 17:55:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0004152930","B=
arriere","","22-01-2025 17:43:34","22-01-2025 17:24:39","22-01-2025 18:27:1=
0","Grid fluctuation, site went down because gen fails to start due to Grid=
 bad voltage and No RCP on site / /He bypassed Grid and stated Gen","Hyemaf=
o Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation, site went down because gen fails to start due to=
 Grid bad voltage and No RCP on site / /He bypassed Grid and stated Gen","k=
ouoh.jean@ihstowers.com","1136","22-01-2025 17:43:34","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004152780","SOA=
 UNIVERSITY STADIUM","","22-01-2025 17:20:47","22-01-2025 17:13:38","22-01-=
2025 18:26:56","Grid outage, site went down due to dysfunctionning of PWC Z=
TE // Gen manually started","Siligap Boris","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","Grid outage, site went down due to=
 dysfunctionning of PWC ZTE // Gen manually started","stephane.nkamwa@ihsto=
wers.com","430","22-01-2025 17:20:47","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004152753","Mon=
tee-Jouvence-II","","22-01-2025 17:17:04","22-01-2025 17:12:56","22-01-2025=
 17:59:49","Site went down due to PWC over load(12KW.280A) SS IHS Fran=E7oi=
s NDOUNGOU  confirmed // Site stabilized ","Hyemafo Gildas","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Site went down due to PWC over =
load(12KW.280A) SS IHS Fran=E7ois NDOUNGOU  confirmed // Site stabilized ",=
"stephane.nkamwa@ihstowers.com","249","22-01-2025 17:17:04","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004152652","Nko=
g-Edzen","","22-01-2025 17:01:22","22-01-2025 16:58:12","22-01-2025 17:34:3=
1","Grid outage,Site went down because Gen stopped with alarm ""high temp""=
causing by radiator pierced// He added water and started Gen manual (radiat=
or to be repaired)","Parker Tchoup","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Radiator Leakage","Grid outage,Site went down because Gen stopped =
with alarm ""high temp""causing by radiator pierced// He added water and st=
arted Gen manual (radiator to be repaired)","stephane.nkamwa@ihstowers.com"=
,"191","22-01-2025 17:01:22","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004151876","NKO=
LMEKONG YDE","","22-01-2025 15:10:19","22-01-2025 14:59:16","22-01-2025 16:=
30:54","grid outage, site went down because gen failed to start due to gen =
battery faulty // Gen manually started with External battery","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","gr=
id outage, site went down because gen failed to start due to gen battery fa=
ulty // Gen manually started with External battery","stephane.nkamwa@ihstow=
ers.com","729","22-01-2025 15:10:19","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0004151865","Ess=
os Marche","","22-01-2025 15:08:07","22-01-2025 14:55:59","22-01-2025 15:10=
:26","Grid outage, Site went down because Gen failed to start due to PWC ZT=
E disfunction// He started Gen manualy (Configuration PWC ongoing by SS IHS=
 Blaise Raul)","Delor Telezing","Equipment Repair","Passive","Rectifier","R=
ectifier Module Overloaded","Grid outage, Site went down because Gen failed=
 to start due to PWC ZTE disfunction// He started Gen manualy (Configuratio=
n PWC ongoing by SS IHS Blaise Raul)","stephane.nkamwa@ihstowers.com","729"=
,"22-01-2025 15:08:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004151822","M=
endong vallee","","22-01-2025 15:03:00","22-01-2025 14:42:08","22-01-2025 1=
7:39:09"," Grid outage, Site went down because Gen overload (20KVA, 320A) S=
S IHS Felix Zambe confirmed// Grid return ","Fanda Brice","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload"," Grid outage, Site went down beca=
use Gen overload (20KVA, 320A) SS IHS Felix Zambe confirmed// Grid return "=
,"kouoh.jean@ihstowers.com","1254","22-01-2025 15:03:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_632","IHS_YND_721","NOCINC0004151766","V=
OIRIE MUNICIPALE YAOUNDE","","22-01-2025 14:51:28","22-01-2025 14:41:20","2=
2-01-2025 14:51:18","Active// No power issue on site U=3D54,1 V site on gri=
d Brice Tsague (650214096) from huawei is informed","Paul BIBOUM","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power issue on site U=3D54,1 V site on grid Brice Tsague (65=
0214096) from huawei is informed","kouoh.jean@ihstowers.com","609","22-01-2=
025 14:51:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_068","IHS_YND_109","NOCINC0004151549","M=
obil-Essos","","22-01-2025 14:33:06","22-01-2025 14:09:57","22-01-2025 14:1=
5:19","Active// No power issue on site U=3D54,1 V site on grid Brice Tsague=
 (650214096) from huawei is informed","Siligap Boris","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// =
No power issue on site U=3D54,1 V site on grid Brice Tsague (650214096) fro=
m huawei is informed","kouoh.jean@ihstowers.com","1390","22-01-2025 14:33:0=
6","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0004151533","Aka=
k-Nkozoa-MTN-IHS","","22-01-2025 14:32:21","22-01-2025 14:16:53","22-01-202=
5 14:32:26","Grid fluctuation site went down because Gen failed to start du=
e to Grid bad voltage // Grid stabilized","Fabrice Pouakam","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation=
 site went down because Gen failed to start due to Grid bad voltage // Grid=
 stabilized","stephane.nkamwa@ihstowers.com","930","22-01-2025 14:32:21","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0004151523","Crf Corn=
ier","","22-01-2025 14:31:31","22-01-2025 14:09:42","22-01-2025 15:10:52","=
Cascaded Incident from TTO4156803","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage// grid return","system"=
,"273167","22-01-2025 14:31:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0004151514","M=
adison","IHS_YND_566","22-01-2025 14:30:11","22-01-2025 14:09:42","22-01-20=
25 15:10:52","Grid outage// grid return","MFOUAGUEGUE MATHIEU","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage// grid =
return","kouoh.jean@ihstowers.com","1230","22-01-2025 14:30:11","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004151425","E=
vodoula OCM","","22-01-2025 14:22:27","22-01-2025 13:53:03","22-01-2025 15:=
36:17","Site went down due to work  Our FME Gael//657108563  is  Working on=
 Site (Replacement MPR )//End Of work","TIENTCHEU NZETCHIEU GAEL","Equipmen=
t Replacement","Passive","Planned Activity","Planned Activity - Passive","S=
ite went down due to work  Our FME Gael//657108563  is  Working on Site (Re=
placement MPR )//End Of work","kouoh.jean@ihstowers.com","1765","22-01-2025=
 14:22:27","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004151410","Men=
dong3","","22-01-2025 14:20:54","22-01-2025 14:03:40","22-01-2025 18:02:58"=
,"	Grid outage no space to deploy a mobil Gen //grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spa=
ce to deploy a mobil Gen //grid return","stephane.nkamwa@ihstowers.com","10=
35","22-01-2025 14:20:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0004151163","Nsam esc=
ale LP","","22-01-2025 14:05:20","22-01-2025 13:56:57","22-01-2025 15:06:31=
","Cascaded Incident from TTO4156399","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage.Gen failed to start due to batter=
y GE discharged causing by static charger faulty// He replaced static charg=
er faulty and started Gen manualy","system","346066","22-01-2025 14:05:20",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0004151152","Nsa=
m Sofavinc","IHS_YND_732","22-01-2025 14:04:06","22-01-2025 13:56:57","22-0=
1-2025 15:06:31","Grid outage.Gen failed to start due to battery GE dischar=
ged causing by static charger faulty// He replaced static charger faulty an=
d started Gen manualy","MINKA NICOLAS","Equipment Repair","Passive","ACDG G=
en","ACDG - Charging Alternator","Grid outage.Gen failed to start due to ba=
ttery GE discharged causing by static charger faulty// He replaced static c=
harger faulty and started Gen manualy","emmanuel.ghani@ihstowers.com","430"=
,"22-01-2025 14:04:06","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_365","NOCINC0004151074","Akono","",=
"22-01-2025 13:47:59","","","SITE ON ALARM DUE TO SWAP OF BATTERIE BACKUP B=
Y SS IHS FELIX NGANBE//END OF WORK","Fanda Brice","Warning","Warning","POWE=
R","Warning - Battery Failure","SITE ON ALARM DUE TO SWAP OF BATTERIE BACKU=
P BY SS IHS FELIX NGANBE//END OF WORK","joelle.ekessi@ihstowers.com","4","2=
2-01-2025 13:47:59","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_365","NOCINC0004151060","Akono","",=
"22-01-2025 13:46:04","","","SITE ON ALARM DUE TO SWAP OF BATTERIE BACKUP B=
Y SS IHS FELIX NGANBE//END OF WORK","Fanda Brice","Warning","Warning","POWE=
R","Warning - Site on Battery","SITE ON ALARM DUE TO SWAP OF BATTERIE BACKU=
P BY SS IHS FELIX NGANBE//END OF WORK","joelle.ekessi@ihstowers.com","3","2=
2-01-2025 13:46:04","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004150745","Pha=
rmacie SION","","22-01-2025 13:02:05","22-01-2025 12:55:49","22-01-2025 13:=
08:05","Grid outage, Site went down before Gen start due to poor battery ba=
ckup//Gen automatically started","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor battery backup//Gen automatically started","e=
mmanuel.ghani@ihstowers.com","378","22-01-2025 13:02:05","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004150431","NYO=
M FACE MAETUR","","22-01-2025 12:30:56","22-01-2025 12:25:37","22-01-2025 1=
2:55:11","Site went down due to Work SS IHS Bernard Atangana is working on =
Site(Replaced the MPR)//End of work ","Fabrice Pouakam","Installation Activ=
ity","Passive","Planned Activity","Installation Activity","Site went down d=
ue to Work SS IHS Bernard Atangana is working on Site(Replaced the MPR)//En=
d of work ","emmanuel.ghani@ihstowers.com","320","22-01-2025 12:30:56","Sag=
emcom CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0004149917","ELO=
UMDEM CARRIERE 2","","22-01-2025 11:51:55","22-01-2025 11:49:49","22-01-202=
5 12:52:13","site went down because Gen stopped with"" alarm high temp""//H=
e added water and Gen manually started","Fanda Brice","Equipment Repair","P=
assive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","site we=
nt down because Gen stopped with"" alarm high temp""//He added water and Ge=
n manually started","emmanuel.ghani@ihstowers.com","128","22-01-2025 11:51:=
55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0004149525","Montee-J=
ouvence","","22-01-2025 11:30:01","22-01-2025 11:23:46","22-01-2025 11:45:1=
6","Cascaded Incident from TTO4154547","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage  site went down be=
cause Gen stopped with alarm high temps //He added water and Gen manually s=
tarted","system","276020","22-01-2025 11:30:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0004149524","Mendong =
vallee","","22-01-2025 11:30:01","22-01-2025 11:23:46","22-01-2025 11:45:16=
","Cascaded Incident from TTO4154547","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage  site went down becaus=
e Gen stopped with alarm high temps //He added water and Gen manually start=
ed","system","276020","22-01-2025 11:30:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004149510","M=
endong","IHS_YND_692, IHS_YND_236","22-01-2025 11:28:51","22-01-2025 11:23:=
46","22-01-2025 11:45:16","Grid Outage  site went down because Gen stopped =
with alarm high temps //He added water and Gen manually started","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Grid Outage  site went down because Gen stopped with a=
larm high temps //He added water and Gen manually started","christian.fonko=
u@ihstowers.com","306","22-01-2025 11:28:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0004149059","M=
volye-New","","22-01-2025 11:11:14","22-01-2025 11:07:06","22-01-2025 13:07=
:07","Active//No power issue, site is on Grid with Ubaie=3D51,5V,Hosiah(674=
007438) from Huawei is working on site.","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue, site is on Grid with Ubaie=3D51,5V,Hosiah(674007438) from Huawei is wo=
rking on site.","christian.fonkou@ihstowers.com","249","22-01-2025 11:11:14=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004148926","L=
abogenie","","22-01-2025 11:04:05","22-01-2025 11:02:58","22-01-2025 12:16:=
11","Active//No power issue, site is on Grid with Ubaie=3D54,5V,Tchana Patr=
ice(695007608) from Huawei is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power iss=
ue, site is on Grid with Ubaie=3D54,5V,Tchana Patrice(695007608) from Huawe=
i is informed","christian.fonkou@ihstowers.com","68","22-01-2025 11:04:05",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004148013","N=
yom OCM","","22-01-2025 09:54:11","22-01-2025 09:42:59","22-01-2025 09:56:5=
6","Grid Outage Site went down because Gen Failed to start due to Alarmes "=
"Low OIL Pressure""//he add oil and Manually Stated the Gen ","Fabrice Poua=
kam","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Gri=
d Outage Site went down because Gen Failed to start due to Alarmes ""Low OI=
L Pressure""//he add oil and Manually Stated the Gen ","christian.fonkou@ih=
stowers.com","674","22-01-2025 09:54:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0004146185","E=
ntree Cite Verte","","22-01-2025 06:20:20","22-01-2025 06:09:15","22-01-202=
5 07:20:31","Active//No power issue, site is on Grid with Ubaie=3D53,7V,Bri=
se Tsague(650214096) from Huawei is informed","Paul BIBOUM","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue, site is on Grid with Ubaie=3D53,7V,Brise Tsague(650214=
096) from Huawei is informed","christian.fonkou@ihstowers.com","666","22-01=
-2025 06:20:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004146102","N=
KOLMEKONG YDE","","22-01-2025 05:57:03","22-01-2025 05:55:58","22-01-2025 0=
5:59:46","Grid outage, Site went down before Gen start due to poor backup//=
 Grid power return","Fabrice Pouakam","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup// Grid power return","olivier.kwedi@ihstowers.c=
om","66","22-01-2025 05:57:03","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0004145951","Nsi=
meyong Shell","","22-01-2025 05:07:10","22-01-2025 05:02:04","22-01-2025 10=
:59:24","Site went down due to Power cable has been stolen on Site (power c=
able between the PWC and the DC-box and Power Cable Between Gen and PWC) //=
he replaced the power cable between the  DC-Box and PWC","MINKA NICOLAS","S=
ite Asset Theft","Theft","Theft","AC Cable Stolen","Site went down due to P=
ower cable has been stolen on Site (power cable between the PWC and the DC-=
box and Power Cable Between Gen and PWC) //he replaced the power cable betw=
een the  DC-Box and PWC","ludivine.ngamaleu@ihstowers.com","307","22-01-202=
5 05:07:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0004145600","M=
volye-New","","22-01-2025 03:19:23","22-01-2025 03:14:17","22-01-2025 03:20=
:04","Active: No power issue, site is on grid with Ubaie=3D52,5V, Mbah hosi=
ah(699699694) from Huawei is informed","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issu=
e, site is on grid with Ubaie=3D52,5V, Mbah hosiah(699699694) from Huawei i=
s informed","olivier.kwedi@ihstowers.com","307","22-01-2025 03:19:23","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004145112","N=
komkana 2","","22-01-2025 00:09:32","22-01-2025 00:05:25","22-01-2025 01:35=
:12","Access Issue during the Night due to Landlord SS IHS Benard confirmed=
,Grid outage site went down because gen fails to start// Grid return (inves=
tigation ongoing)","Mboua Thierry","Access Denial","Lease Or Legal","Landlo=
rd Related Issues","Access Issue - Land Lord","Access Issue during the Nigh=
t due to Landlord SS IHS Benard confirmed,Grid outage site went down becaus=
e gen fails to start// Grid return (investigation ongoing)","olivier.kwedi@=
ihstowers.com","248","22-01-2025 00:09:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0004143761","Ngoulmek=
ong-Nord","","21-01-2025 20:56:10","21-01-2025 20:29:24","21-01-2025 21:24:=
34","Cascaded Incident from TTO4148095","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down due to disjunct=
ion of Cb(2*125A) in PWC // He reamed Cb(125A), site on grid (investigation=
 ongoing)","system","271969","21-01-2025 20:56:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0004143751","E=
leveur","IHS_YND_277","21-01-2025 20:55:32","21-01-2025 20:29:24","21-01-20=
25 21:24:34","site went down due to disjunction of Cb(2*125A) in PWC // He =
reamed Cb(125A), site on grid (investigation ongoing)","Siligap Boris","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker I=
ssue","site went down due to disjunction of Cb(2*125A) in PWC // He reamed =
Cb(125A), site on grid (investigation ongoing)","alexandre.kamal@ihstowers.=
com","1570","21-01-2025 20:55:32","Sagemcom CMR"
"Cancelled","Warning","CTR_379","IHS_YND_277","NOCINC0004143721","Ngoulmeko=
ng-Nord","","21-01-2025 20:53:55","","","","Siligap Boris","","","","","","=
alexandre.kamal@ihstowers.com","1448","21-01-2025 20:53:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0004142142","N=
koabang2","","21-01-2025 16:43:01","21-01-2025 16:35:57","21-01-2025 18:32:=
45","site went down because gen failed to start due to lack of 02 phase and=
 third phase instability // Gen manually started","Mba Lazare Herve","Grid =
Supply","Passive","Grid","National Grid - Grid Incomplete Phase","site went=
 down because gen failed to start due to lack of 02 phase and third phase i=
nstability  // Gen manually started","alexandre.kamal@ihstowers.com","425",=
"21-01-2025 16:43:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004141215","L=
abogenie","","21-01-2025 14:44:12","21-01-2025 14:35:08","21-01-2025 14:40:=
11","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hua=
wei is informed","alexandre.kamal@ihstowers.com","545","21-01-2025 14:44:12=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_369","IHS_YND_019","NOCINC0004141137","H=
otel de Ville Yde","","21-01-2025 14:33:52","21-01-2025 13:59:46","21-01-20=
25 14:52:44","	site went down because CB  (80A) tripped in Dcbox who feeds =
equipments OCM / //He make the bridge with another  Cb(80A), site on grid",=
"Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Circuit Breaker Issue","	site went down because CB  (80A) tripped in Dcbox=
 who feeds equipments OCM / //He make the bridge with another  Cb(80A), sit=
e on grid","alexandre.kamal@ihstowers.com","2047","21-01-2025 14:33:52","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004140783","D=
amas","","21-01-2025 13:40:11","21-01-2025 13:07:59","21-01-2025 15:53:48",=
"Site went down due to work: Technician Ervan ABENA/699999625 From GRATOS w=
orking on site (Swapp Gen and PWC)// End of work","MINKA NICOLAS","Equipmen=
t Replacement","Passive","Planned Activity","Planned Activity - Passive","S=
ite went down due to work: Technician Ervan ABENA/699999625 From GRATOS wor=
king on site (Swapp Gen and PWC)// End of work","kouoh.jean@ihstowers.com",=
"1933","21-01-2025 13:40:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0004140777","Eloumdem=
 stade","","21-01-2025 13:38:50","21-01-2025 13:28:43","21-01-2025 13:46:52=
","Cascaded Incident from TTO4144641","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work: Our Te=
chnician Brice FANDA/657108549/SAGEMCOM working on site (PM)// End of work"=
,"system","268562","21-01-2025 13:38:50","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004140776","Sim=
bock MTN","IHS_YND_793","21-01-2025 13:37:52","21-01-2025 13:28:43","21-01-=
2025 13:46:52","Site went down due to work: Our Technician Brice FANDA/6571=
08549/SAGEMCOM working on site (PM)// End of work","Fanda Brice","Installat=
ion Activity","Passive","Planned Activity","Installation Activity","Site we=
nt down due to work: Our Technician Brice FANDA/657108549/SAGEMCOM working =
on site (PM)// End of work","stephane.nkamwa@ihstowers.com","550","21-01-20=
25 13:37:52","Sagemcom CMR"
"Closed Complete","Warning","T1552","IHS_YND_281","NOCINC0004140658","Odza =
II","","21-01-2025 13:16:47","","","site on battery due to grid outage//gen=
 started","Albran Byorel","Warning","Warning","POWER","Warning - Site on Ba=
ttery","site on battery due to grid outage//gen started","dorothy.djantio@i=
hstowers.com","308","21-01-2025 13:16:47","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004140590","Tsi=
nga village","","21-01-2025 13:05:02","21-01-2025 12:55:55","21-01-2025 14:=
27:19","Site went down because CB(80A) burned in PWC due to  power cable  h=
as  heated//he normalized the cable and make the brigde with Cb(2*80 A),sit=
e on Grid","Delor Telezing","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Circuit Breaker Issue","Site went down because CB(80A) burne=
d in PWC due to  power cable  has  heated//he normalized the cable and make=
 the brigde with Cb(2*80 A),site on Grid","stephane.nkamwa@ihstowers.com","=
548","21-01-2025 13:05:02","Sagemcom CMR"
"Closed Complete","Site Down","T1114","IHS_YND_153","NOCINC0004140069","Ron=
d Point Express1114","","21-01-2025 11:54:52","21-01-2025 11:48:38","21-01-=
2025 12:49:35","Active: No power issue, site is on grid with Ubaie=3D54,5V,=
 Mbah hosiah(699699694) from Huawei is informed and up at 11:54 AM","Hyemaf=
o Gildas","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active: No power issue, site is on grid with Ubaie=3D=
54,5V, Mbah hosiah(699699694) from Huawei is informed and up at 11:54 AM","=
stephane.nkamwa@ihstowers.com","375","21-01-2025 11:54:52","Sagemcom CMR"
"Closed Complete","Warning","T0197","IHS_YND_263","NOCINC0004139133","Mendo=
ng Plateau","","21-01-2025 10:55:31","","","site alarming because high temp=
 34 C due to air-conditioning piping in poor condition // he replaced the a=
ir-conditioning piping 23 C","Hyemafo Gildas","Warning","Warning","ENVIRONM=
ENT","Warning - High Temperature","site alarming because high temp 34 C due=
 to air-conditioning piping in poor condition // he replaced the air-condit=
ioning piping 23 C","dorothy.djantio@ihstowers.com","305","21-01-2025 10:55=
:31","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004138105","NYO=
M FACE MAETUR","","21-01-2025 09:33:39","21-01-2025 09:32:33","21-01-2025 1=
0:14:50","site went down because 1/4 rectifier disfunctionning//he reset th=
e rectifier,SS IHS Bernard is informed and confirmed//he reset the rectifie=
r","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down because 1/4 rectifier disfunctionning//he reset the r=
ectifier,SS IHS Bernard is informed and confirmed//he reset the rectifier",=
"stephane.nkamwa@ihstowers.com","68","21-01-2025 09:33:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004137926","Ngoum","=
","21-01-2025 09:12:30","21-01-2025 09:06:55","21-01-2025 09:40:38","Cascad=
ed Incident from TTO4141469","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage,  Site went down because Gen =
started and stopped due to ""high temp"" alarm // We add water and gen star=
ted","system","269786","21-01-2025 09:12:30","Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0004137916","Yok=
o MTN","IHS_YND_475","21-01-2025 09:11:03","21-01-2025 09:06:55","21-01-202=
5 09:40:38","Grid outage,  Site went down because Gen started and stopped d=
ue to ""high temp"" alarm // We add water and gen started","Parker Tchoup",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage,  Site went down because Gen started and stopped =
due to ""high temp"" alarm // We add water and gen started","stephane.nkamw=
a@ihstowers.com","250","21-01-2025 09:11:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0004137471","S=
calom-IHS","","21-01-2025 07:26:49","21-01-2025 06:32:39","21-01-2025 06:40=
:46","Active: No power issue, site is on grid with Ubaie=3D52,5V, Mbah hosi=
ah(699699694) from Huawei is informed. Notice that Site impacted by Nkolzie=
 (Not Managing by IHS)","","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active: No power issue, site is on g=
rid with Ubaie=3D52,5V, Mbah hosiah(699699694) from Huawei is informed. Not=
ice that Site impacted by Nkolzie (Not Managing by IHS)","kouoh.jean@ihstow=
ers.com","3251","21-01-2025 07:26:49","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004136875","SAA=
 Entrance","","21-01-2025 05:17:01","21-01-2025 05:12:55","21-01-2025 05:40=
:28"," Grid outage, Site went down because Gen started and stopped due to "=
"high temp"" alarm // We add water and gen started (investigation ongoing)"=
,"Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High Engin=
e Temp - Coolant Level Issue"," Grid outage, Site went down because Gen sta=
rted and stopped due to ""high temp"" alarm // We add water and gen started=
 (investigation ongoing)","ange.kongo@ihstowers.com","248","21-01-2025 05:1=
7:01","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004135846","Nko=
g-Edzen","","20-01-2025 23:13:16","20-01-2025 23:06:08","20-01-2025 23:11:2=
2","ACTIVE//No power issue on site with  Ubaie=3D52.4V site on Gen (start t=
hreshold ubai=3D50 V)The Tx Fme Gregoire( 652070658)from Huawei is informed=
. ","Parker Tchoup","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","ACTIVE//No power issue on site with  Ubaie=
=3D52.4V site on Gen (start threshold ubai=3D50 V)The Tx Fme Gregoire( 6520=
70658)from Huawei is informed. ","ange.kongo@ihstowers.com","429","20-01-20=
25 23:13:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004135683","L=
abogenie","","20-01-2025 22:39:16","20-01-2025 22:29:59","20-01-2025 23:34:=
36","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hua=
wei is informed","rouselle.schoune@ihstowers.com","558","20-01-2025 22:39:1=
6","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0004135622","C=
RH-Etoug-Ebe","","20-01-2025 22:31:10","20-01-2025 22:29:00","21-01-2025 00=
:48:28","Active//No power issue on site U=3D52,7V site on Grid , mouhamadou=
 (691144435) of huawei is informed","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site U=3D52,7V site on Grid , mouhamadou (691144435) of hua=
wei is informed","rouselle.schoune@ihstowers.com","131","20-01-2025 22:31:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0004135076","Crf=
-Mbankolo-IHS","","20-01-2025 21:17:15","20-01-2025 21:04:08","20-01-2025 2=
1:23:08","Site went down due to all rectifier disfunction // reset done: si=
te on gen","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to all rectifier disfunction // reset done:=
 site on gen","ludivine.ngamaleu@ihstowers.com","788","20-01-2025 21:17:15"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004134456","MBI=
MBIM","","20-01-2025 19:25:02","20-01-2025 19:09:55","20-01-2025 20:16:55",=
"Grid outage, site went down because gen fails to start du to battery ge fa=
ulty (SS IHS Felix is informed) // gen start with battery backup","Parker T=
choup","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","=
Grid outage, site went down because gen fails to start du to battery ge fau=
lty (SS IHS Felix is informed) // gen start with battery backup","ludivine.=
ngamaleu@ihstowers.com","908","20-01-2025 19:25:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004134051","Barriere=
 IHS","","20-01-2025 18:23:20","20-01-2025 18:19:08","20-01-2025 18:20:08",=
"Cascaded Incident from TTO4136940","Hyemafo Gildas","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site GRID , Ubaie=
=3D54.V site On Grid The Tx FME Georges 697461814 from Huawei is informed..=
","system","272714","20-01-2025 18:23:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004134026","M=
efou-Assi","IHS_YND_696","20-01-2025 18:21:35","20-01-2025 18:19:08","20-01=
-2025 21:20:08","No power issue on site GRID , Ubaie=3D54.V site On Grid Th=
e Tx FME Georges 697461814 from Huawei is informed..","Fanda Brice","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power issue on site GRID , Ubaie=3D54.V site On Grid The Tx FME Geo=
rges 697461814 from Huawei is informed..","dorothy.djantio@ihstowers.com","=
148","20-01-2025 18:21:35","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004133858","Nko=
lbisson usines des eaux 2","","20-01-2025 17:48:31","20-01-2025 17:46:25","=
20-01-2025 18:43:25","Grid outage, site went down because gen fails to star=
t due to ATS disfunction // normanilization done and gen started","TIENTCHE=
U NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","ATS-AMF Iss=
ue","Grid outage, site went down because gen fails to start due to ATS disf=
unction // normanilization done and gen started","ludivine.ngamaleu@ihstowe=
rs.com","127","20-01-2025 17:48:31","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004133851","UPA=
C LP","","20-01-2025 17:46:37","20-01-2025 17:44:32","20-01-2025 17:46:32",=
"Grid outage, no space to deploy a mobile gen // grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no s=
pace to deploy a mobile gen // grid return","ludivine.ngamaleu@ihstowers.co=
m","126","20-01-2025 17:46:37","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004133478","ODZ=
A MINKAN EDIBI ASSI","","20-01-2025 16:54:00","20-01-2025 16:52:54","20-01-=
2025 17:09:54","Grid outage, site went down because gen fails to start du t=
o battery ge faulty (SS IHS PASCALINE is informed) // gen start with batter=
y backup","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - G=
enerator Battery","Grid outage, site went down because gen fails to start d=
u to battery ge faulty (SS IHS PASCALINE is informed) // gen start with bat=
tery backup","ludivine.ngamaleu@ihstowers.com","67","20-01-2025 16:54:00","=
Sagemcom CMR"
"Closed Complete","Warning","CTR_253","IHS_YND_258","NOCINC0004133394","Mef=
ou-Assi","","20-01-2025 16:39:57","","","","Fanda Brice","Warning","Warning=
","POWER","Warning - AC Phase 1 Current Low","Alamrn cleared","etienne.iton=
do@ihstowers.com","25","20-01-2025 16:39:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004133066","L=
abogenie","","20-01-2025 15:43:29","20-01-2025 15:37:24","20-01-2025 15:42:=
45","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hua=
wei is informed","dorothy.djantio@ihstowers.com","367","20-01-2025 15:43:29=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004130294","O=
dza II","","20-01-2025 10:43:50","20-01-2025 09:06:31","20-01-2025 09:10:31=
","Active // no power issue on site U=3D52.1V on Gen, TX FME LIONEL STEVE A=
DJEP/ 655184876 From huawei is informed","Albran Byorel","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // no power issue on site U=3D52.1V on Gen, TX FME LIONEL STEVE ADJEP/ 655=
184876 From huawei is informed","alexandre.kamal@ihstowers.com","5842","20-=
01-2025 10:43:50","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004129821","Ona=
ngondi (melen bikop)","","20-01-2025 09:32:31","20-01-2025 08:57:14","20-01=
-2025 10:13:41","Grid Hybrid Gen, site went down because gen ran untill fue=
l shortage // refueling done","Fanda Brice","Fuel Outage","Passive","Diesel=
","Diesel Outage","Grid Hybrid Gen, site went down because gen ran untill f=
uel shortage // refueling done","kamga.virgile@ihstowers.com","2118","20-01=
-2025 09:32:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004128970","O=
dza II","","20-01-2025 06:26:45","20-01-2025 06:17:31","20-01-2025 09:05:37=
","Grid outage, Site went because Gen ran until fuel shortage//Refueling Do=
ne. Power issue resolve at 09:05 AM but site remains down at OCM fme Lionel=
 Adjep/ 655184876 from Huawei is informed","Albran Byorel","Fuel Outage","P=
assive","Diesel","Diesel Outage","Grid outage, Site went because Gen ran un=
til fuel shortage//Refueling Done. Power issue resolve at 09:05 AM but site=
 remains down at OCM fme Lionel Adjep/ 655184876 from Huawei is informed","=
alexandre.kamal@ihstowers.com","865","20-01-2025 06:26:45","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004128763","Nsi=
meyong Terre Rouge","","20-01-2025 05:25:12","20-01-2025 05:19:07","20-01-2=
025 05:31:46","Grid outage, Site went down before Gen start due to poor bac=
kup// Gen automatically started ","MINKA NICOLAS","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup// Gen automatically started ","emma=
nuel.ghani@ihstowers.com","366","20-01-2025 05:25:12","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004128383","ODZ=
A CITE MBIA","","20-01-2025 03:06:11","20-01-2025 02:50:02","20-01-2025 04:=
16:19"," Grid outage, site went down because gen stopped with 'Emergency st=
op' alarm // He reset the Gen card and Gen manually started","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"," Grid out=
age, site went down because gen stopped with 'Emergency stop' alarm // He r=
eset the Gen card and Gen manually started","emmanuel.ghani@ihstowers.com",=
"970","20-01-2025 03:06:11","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004128363","Ona=
ngondi (melen bikop)","","20-01-2025 02:44:18","20-01-2025 02:42:08","20-01=
-2025 03:31:22","Grid outage, site went down because gen ran untill fuel sh=
ortage // refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","D=
iesel Outage","Grid outage, site went down because gen ran untill fuel shor=
tage // refueling done","emmanuel.ghani@ihstowers.com","131","20-01-2025 02=
:44:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0004128295","K=
oweit City","","20-01-2025 02:11:03","20-01-2025 02:05:59","20-01-2025 03:5=
2:41","Grid outage, site went down because Gen failed to start due to Gen b=
attery faulty // Gen manually started with External battery","Albran Byorel=
","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid =
outage, site went down because Gen failed to start due to Gen battery fault=
y // Gen manually started with External battery","christian.fonkou@ihstower=
s.com","305","20-01-2025 02:11:03","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004128285","Com=
plex Beac II","","20-01-2025 02:03:25","20-01-2025 02:01:17","20-01-2025 03=
:31:57","Grid outage site went down because Gen failed to start due to Gen =
card dysfonction // He reset the Gen card and Gen manually started","Albran=
 Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage site went down because Gen failed to start due to Gen card dysfon=
ction // He reset the Gen card and Gen manually started","emmanuel.ghani@ih=
stowers.com","129","20-01-2025 02:03:25","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0004128107","UPA=
C LP","","20-01-2025 00:51:16","20-01-2025 00:48:09","20-01-2025 08:55:47",=
"Grid outage, No space to deploy MDG // Grid return","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage, No space to d=
eploy MDG // Grid return","emmanuel.ghani@ihstowers.com","188","20-01-2025 =
00:51:16","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_073","NOCINC0004128029","Chapelle-O=
bili","","20-01-2025 00:27:23","","","","Paul BIBOUM","Warning","Warning","=
POWER","Warning - Rectifier Failure","02 Rectifiers replaced","joelle.ekess=
i@ihstowers.com","68","20-01-2025 00:27:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_067","NOCINC0004127847","Nkoa Ayo=
s","","19-01-2025 23:46:40","19-01-2025 23:41:41","19-01-2025 23:50:15","Ca=
scaded Incident from TTO4129955","MINKA NICOLAS","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active//No power issue, site is on grid =
with Ubaie=3D53,5V, The FME Emmanuel SONKOUE (694567096) from SNEF was work=
ing on site","system","274723","19-01-2025 23:46:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0004127846","G=
SO","IHS_YND_067","19-01-2025 23:45:50","19-01-2025 23:41:41","19-01-2025 2=
3:50:15","Active//No power issue, site is on grid with Ubaie=3D53,5V, The F=
ME Emmanuel SONKOUE (694567096) from SNEF was working on site","MINKA NICOL=
AS","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue, site is on grid with Ubaie=3D53,5V,=
 The FME Emmanuel SONKOUE (694567096) from SNEF was working on site","chris=
tian.fonkou@ihstowers.com","249","19-01-2025 23:45:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0004127764","Eloumdem=
 stade","","19-01-2025 23:17:50","19-01-2025 23:10:10","20-01-2025 00:26:18=
","Cascaded Incident from TTO4129825","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // refueling done","system","269458","19-01-=
2025 23:17:50","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004127736","Sim=
bock MTN","IHS_YND_793","19-01-2025 23:13:15","19-01-2025 23:10:10","20-01-=
2025 00:26:18","Grid outage, site went down because gen ran untill fuel sho=
rtage // refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Di=
esel Outage","Grid outage, site went down because gen ran untill fuel short=
age // refueling done","emmanuel.ghani@ihstowers.com","186","19-01-2025 23:=
13:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004127457","M=
endong vallee","","19-01-2025 22:00:39","19-01-2025 21:59:24","19-01-2025 2=
2:00:26","Site went down because inssufficient the rectifier (07) on site d=
ue to load increased // Site stabilized","Fanda Brice","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down because inssufficie=
nt the rectifier (07) on site due to load increased // Site stabilized","ro=
uselle.schoune@ihstowers.com","76","19-01-2025 22:00:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004126440","S=
tade-Abega","","19-01-2025 18:47:13","19-01-2025 18:44:07","19-01-2025 18:4=
7:52","Grid outage, Site went down before Gen start due to poor backup// Gr=
id return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup// Grid return","rouselle.schoune@ihstowers.com","187","=
19-01-2025 18:47:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004126431","A=
WAE OCM","","19-01-2025 18:46:28","19-01-2025 18:41:18","19-01-2025 18:47:1=
1","Grid outage, site went down before gen start due to poor battery backup=
 // Gen started automatically","Mba Lazare Herve","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // Gen started automaticall=
y","rouselle.schoune@ihstowers.com","312","19-01-2025 18:46:28","Sagemcom C=
MR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004126393","NKO=
MEKUI OCM","","19-01-2025 18:40:08","19-01-2025 18:34:01","19-01-2025 19:07=
:10","ACTIVE//No power issue on site U=3D54,5v site on gen site down becaus=
e is impacted by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCH=
IEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","ACTIVE//No power issue on site U=3D54,5v site on gen =
site down because is impacted by Mbankolo Camtel and not managing by IHS","=
ange.kongo@ihstowers.com","369","19-01-2025 18:40:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004126265","O=
lembe-Terminus","","19-01-2025 18:19:43","19-01-2025 18:17:37","19-01-2025 =
18:20:23","site went down because Gen failed to start due to lack of 1 phas=
e on site // he did a bridge with a good phase","Fabrice Pouakam","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","site went =
down because Gen failed to start due to lack of 1 phase on site // he did a=
 bridge with a good phase","rouselle.schoune@ihstowers.com","128","19-01-20=
25 18:19:43","Sagemcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004125953","Tam=
tam Weekend","","19-01-2025 17:29:29","19-01-2025 17:20:59","19-01-2025 18:=
03:47","Active: No power issue, site is on grid with Ubaie=3D56,5V, Mbah ho=
siah(699699694) from Huawei is informed.","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: No power issue, site is on grid with Ubaie=3D56,5V, Mbah hosiah(6996996=
94) from Huawei is informed.","ange.kongo@ihstowers.com","511","19-01-2025 =
17:29:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004125628","M=
ontee-Jouvence-II","","19-01-2025 16:48:10","19-01-2025 16:46:05","19-01-20=
25 17:14:32","Site went down due to PWC Overloaded (12K, 230A) // site stab=
ilized  SS IHS Alphonse confirmed","Hyemafo Gildas","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Site went down due to PWC =
Overloaded (12K, 230A) // site stabilized  SS IHS Alphonse confirmed","rous=
elle.schoune@ihstowers.com","126","19-01-2025 16:48:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0004125159","N=
kozoa","","19-01-2025 15:37:10","19-01-2025 15:32:04","19-01-2025 15:37:43"=
,"site went down because gen failed to start due to grid bad voltage // gri=
d stabilized","Fabrice Pouakam","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","site went down because gen failed to start d=
ue to grid bad voltage // grid stabilized","rouselle.schoune@ihstowers.com"=
,"307","19-01-2025 15:37:10","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004124343","ODZ=
A MINKAN EDIBI ASSI","","19-01-2025 14:38:17","19-01-2025 14:34:01","19-01-=
2025 15:51:52","Grid outage, site went down Gen failed to start due to ATS =
dysfonction // He started Gen manualy ","Albran Byorel","Equipment Repair",=
"Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down Gen =
failed to start due to ATS dysfonction // He started Gen manualy ","ange.ko=
ngo@ihstowers.com","257","19-01-2025 14:38:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0004124092","E=
vodoula OCM","","19-01-2025 14:27:24","19-01-2025 14:24:19","19-01-2025 14:=
27:22","Grid outage.gen failed to start due to theft of battery GE // Gen m=
anually started with external battery","TIENTCHEU NZETCHIEU GAEL","Site Ass=
et Theft","Theft","Theft","Generator Battery Theft","Grid outage.gen failed=
 to start due to theft of battery GE // Gen manually started with external =
battery","rouselle.schoune@ihstowers.com","186","19-01-2025 14:27:24","Sage=
mcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0004123809","Tam=
tam Weekend","","19-01-2025 13:57:54","19-01-2025 13:54:46","19-01-2025 13:=
59:46","Active: No power issue, site is on grid with Ubaie=3D56,5V, Mbah ho=
siah(699699694) from Huawei is informed.","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: No power issue, site is on grid with Ubaie=3D56,5V, Mbah hosiah(6996996=
94) from Huawei is informed.","ludivine.ngamaleu@ihstowers.com","189","19-0=
1-2025 13:57:54","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004123798","NKO=
MKANA ELIZA HOTEL","","19-01-2025 13:55:50","19-01-2025 13:47:43","19-01-20=
25 14:10:21","grid outage, no space to deploy a mobile// grid return ","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid out=
age, no space to deploy a mobile// grid return ","ludivine.ngamaleu@ihstowe=
rs.com","488","19-01-2025 13:55:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0004123786","B=
ATA-Mokolo","","19-01-2025 13:53:56","19-01-2025 13:51:47","19-01-2025 14:1=
2:30","Grid outage.no space to deploy mobile gen//Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no s=
pace to deploy mobile gen//Grid return","dorothy.djantio@ihstowers.com","13=
0","19-01-2025 13:53:56","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004123691","BAT=
A Mokolo OCM","","19-01-2025 13:39:22","19-01-2025 13:10:16","19-01-2025 14=
:17:36","grid outage, no space to deploy a mobile//grid return ","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, n=
o space to deploy a mobile//grid return ","etienne.itondo@ihstowers.com","1=
747","19-01-2025 13:39:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0004123608","Bastos E=
koudou","","19-01-2025 13:24:50","19-01-2025 13:13:59","19-01-2025 14:21:18=
","Cascaded Incident from TTO4125050","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage, no space to deploy =
a mobile//grid return ","system","276625","19-01-2025 13:24:50","Sagemcom C=
MR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004123605","Lab=
oratoire  Meka","IHS_YND_193","19-01-2025 13:23:57","19-01-2025 13:13:59","=
19-01-2025 14:21:18","grid outage, no space to deploy a mobile//grid return=
 ","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","g=
rid outage, no space to deploy a mobile//grid return ","ludivine.ngamaleu@i=
hstowers.com","599","19-01-2025 13:23:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004123574","O=
bobogo","","19-01-2025 13:17:21","19-01-2025 13:14:16","19-01-2025 13:16:40=
","Grid outage, Site went down before Gen start due to poor backup// grid r=
eturn","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage, Site went down before Gen start due to=
 poor backup// grid return","dorothy.djantio@ihstowers.com","186","19-01-20=
25 13:17:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0004123416","N=
KOLMEKONG YDE","","19-01-2025 12:49:56","19-01-2025 12:33:51","19-01-2025 1=
2:54:30","Grid outage, Site went down before Gen start due to poor backup//=
 Grid power return","Fabrice Pouakam","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup// Grid power return","dorothy.djantio@ihstowers=
.com","966","19-01-2025 12:49:56","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004123408","BAT=
A Mokolo OCM","","19-01-2025 12:48:58","19-01-2025 12:37:49","19-01-2025 12=
:56:47","Grid outage, no space to deploy a mobile, // Grid return ","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, no space to deploy a mobile, // Grid return ","etienne.itondo@ihstowers.c=
om","670","19-01-2025 12:48:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0004123370","Messassi=
 Ngonlonk","","19-01-2025 12:47:20","19-01-2025 12:35:51","19-01-2025 13:01=
:51","Cascaded Incident from TTO4124753","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site on gen due to grid out=
age, site went down due to disjunction of Cb(40A) of rectifiers // He reame=
d Cb(40A), site on grid","system","278813","19-01-2025 12:47:20","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004123369","Akak-Nko=
zoa-MTN-IHS","","19-01-2025 12:47:20","19-01-2025 12:35:51","19-01-2025 13:=
01:51","Cascaded Incident from TTO4124753","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","site on gen due to grid o=
utage, site went down due to disjunction of Cb(40A) of rectifiers // He rea=
med Cb(40A), site on grid","system","278813","19-01-2025 12:47:20","Sagemco=
m CMR"
"Closed Complete","Site Down","T0051","IHS_YND_297","NOCINC0004123343","Mes=
sassi","IHS_YND_316, IHS_YND_799","19-01-2025 12:42:59","19-01-2025 12:32:0=
4","19-01-2025 13:01:51","site on gen due to grid outage, site went down du=
e to disjunction of Cb(40A) of rectifiers // He reamed Cb(40A), site on gri=
d","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Circuit Breaker Issue","site on gen due to grid outage, site went d=
own due to disjunction of Cb(40A) of rectifiers // He reamed Cb(40A), site =
on grid","ludivine.ngamaleu@ihstowers.com","850","19-01-2025 12:42:59","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0004123104","H=
-Progres","","19-01-2025 12:17:53","19-01-2025 11:37:46","19-01-2025 14:09:=
36","Grid outage, No space to deploy MDG// Grid return ","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space =
to deploy MDG// Grid return ","dorothy.djantio@ihstowers.com","2408","19-01=
-2025 12:17:53","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0004122677","Bas=
tos Ekoudou","","19-01-2025 10:54:54","19-01-2025 10:45:00","19-01-2025 11:=
25:16","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage, No space to deploy MDG//Grid return ","ludivine=
.ngamaleu@ihstowers.com","270908","19-01-2025 10:54:54","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004122676","BAT=
A Mokolo OCM","","19-01-2025 10:54:20","19-01-2025 10:45:15","19-01-2025 11=
:15:16","Grid outage, No space to deploy MDG//Grid return ","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spa=
ce to deploy MDG//Grid return ","ludivine.ngamaleu@ihstowers.com","546","19=
-01-2025 10:54:20","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0004122674","Lab=
oratoire  Meka","IHS_YND_193","19-01-2025 10:53:06","19-01-2025 10:45:00","=
19-01-2025 11:25:16","Grid outage, No space to deploy MDG//Grid return ",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, No space to deploy MDG//Grid return ","ludivine.ngamaleu@ihstowers.c=
om","487","19-01-2025 10:53:06","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004122400","NKO=
MKANA ELIZA HOTEL","","19-01-2025 10:06:40","19-01-2025 09:58:19","19-01-20=
25 10:44:15","Grid outage, No space to deploy MDG // Grid return ","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 No space to deploy MDG // Grid return ","ludivine.ngamaleu@ihstowers.com",=
"502","19-01-2025 10:06:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0004122231","N=
komkana","","19-01-2025 09:36:16","19-01-2025 09:29:11","19-01-2025 09:30:3=
2","No power ussue site on battery with U=3D49.8v Brice Tsague(650214096) f=
rom Huawei is informed","","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power ussue site on battery with =
U=3D49.8v Brice Tsague(650214096) from Huawei is informed","dorothy.djantio=
@ihstowers.com","427","19-01-2025 09:36:16","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0004121849","Fla=
menco","","19-01-2025 08:33:22","19-01-2025 08:27:16","19-01-2025 09:36:50"=
,"grid outage, site went down because gen failed to start due to gen card f=
aulty // Gen manually started","Mboua Thierry","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","grid outage, site went down because gen=
 failed to start due to gen card faulty // Gen manually started","ludivine.=
ngamaleu@ihstowers.com","367","19-01-2025 08:33:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0004121785","M=
endong Maeture","","19-01-2025 08:26:50","19-01-2025 08:20:46","19-01-2025 =
08:48:56","site went down because gen failed to start due to grid bad volta=
ge // grid stabilized","Hyemafo Gildas","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","site went down because gen failed to=
 start due to grid bad voltage // grid stabilized","dorothy.djantio@ihstowe=
rs.com","365","19-01-2025 08:26:50","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004121699","NKO=
LMEKONG YDE","","19-01-2025 08:06:47","19-01-2025 08:05:41","19-01-2025 09:=
43:25","Grid outage, site went down because gen ran untill fuel shoratge //=
 refueling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage, site went down because gen ran untill fuel shoratge =
// refueling done","ludivine.ngamaleu@ihstowers.com","67","19-01-2025 08:06=
:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004121495","L=
abogenie","","19-01-2025 07:22:10","19-01-2025 07:18:04","19-01-2025 08:57:=
30","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hua=
wei is informed","dorothy.djantio@ihstowers.com","247","19-01-2025 07:22:10=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004121460","A=
WAE OCM","","19-01-2025 07:15:18","19-01-2025 07:13:13","19-01-2025 07:21:4=
3","Grid outage, Site went down before Gen start due to poor backup// Gen a=
utomaticaly started ","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Gen automaticaly started ","dorothy.djanti=
o@ihstowers.com","127","19-01-2025 07:15:18","Sagemcom CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0004121457","ELO=
UMDEM CARRIERE 2","","19-01-2025 07:14:48","19-01-2025 07:12:39","19-01-202=
5 08:02:44","Gen only site ,site went down because gen ran untill fuel shor=
tage // refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Die=
sel Outage","Gen only site ,site went down because gen ran untill fuel shor=
tage // refueling done","ludivine.ngamaleu@ihstowers.com","131","19-01-2025=
 07:14:48","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004120683","Mon=
tee Jouvence","","19-01-2025 02:51:52","19-01-2025 02:47:43","19-01-2025 03=
:33:40","Site was on Gen due to Grid outage, site went down because gen sto=
pped with high temp alarm // he added water and manually start the gen","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine T=
emp - Coolant Level Issue","Site was on Gen due to Grid outage, site went d=
own because gen stopped with high temp alarm // he added water and manually=
 start the gen","stephane.nkamwa@ihstowers.com","250","19-01-2025 02:51:52"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004120650","Men=
dong3","","19-01-2025 02:38:24","19-01-2025 02:30:31","19-01-2025 08:26:11"=
,"Grid outage, No space to deploy MDG // Grid return ","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage, No space to=
 deploy MDG // Grid return ","stephane.nkamwa@ihstowers.com","473","19-01-2=
025 02:38:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004120630","M=
efou-Assi","","19-01-2025 02:30:30","18-01-2025 21:06:13","19-01-2025 08:53=
:54","No power issue site on gen with U=3D54,3v Notice that site is down be=
hind Nkolzie who is not our responsability ","Fanda Brice","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue site on gen with U=3D54,3v Notice that site is down behind Nkolz=
ie who is not our responsability ","kouoh.jean@ihstowers.com","19458","19-0=
1-2025 02:30:30","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004120597","Elo=
umdem stade","","19-01-2025 02:07:34","19-01-2025 01:52:17","19-01-2025 02:=
12:42","Grid fluctuation,site went down because Gen failed to start due to =
bad voltage,NO RCP// he bypass the Grid and site on Gen","Fanda Brice","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation,site went down because Gen failed to start due to bad voltage,N=
O RCP// he bypass the Grid and site on Gen","stephane.nkamwa@ihstowers.com"=
,"918","19-01-2025 02:07:34","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004119130","MBI=
MBIM","","18-01-2025 20:44:54","18-01-2025 20:42:47","18-01-2025 22:46:45",=
"solar gen site; site went down because gen ran untill fuel shortage // ref=
uelling done (Fuel manage by EDONDE)","Parker Tchoup","Fuel Outage","Passiv=
e","Diesel","Diesel Outage","solar gen site; site went down because gen ran=
 untill fuel shortage // refuelling done (Fuel manage by EDONDE)","emmanuel=
.ghani@ihstowers.com","128","18-01-2025 20:44:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_513","NOCINC0004118999","Maison-B=
lanche-IHS","","18-01-2025 20:25:32","18-01-2025 20:03:58","18-01-2025 20:1=
0:47","No power issue site on gen  with U=3D51.1v Notice thatt site is down=
 behind Nkolzie who is not our responsability","","Customer Equipment Failu=
re","Active","Active Equipment Failure","Affected by 3rd Party Site","No po=
wer issue site on gen  with U=3D51.1v Notice thatt site is down behind Nkol=
zie who is not our responsability","system","1294","18-01-2025 20:25:32","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004119000","Barriere=
 IHS","","18-01-2025 20:25:32","18-01-2025 20:03:58","18-01-2025 20:10:47",=
"No power issue site on gen  with U=3D51.1v Notice thatt site is down behin=
d Nkolzie who is not our responsability","Hyemafo Gildas","Customer Equipme=
nt Failure","Active","Active Equipment Failure","Affected by 3rd Party Site=
","No power issue site on gen  with U=3D51.1v Notice thatt site is down beh=
ind Nkolzie who is not our responsability","system","1294","18-01-2025 20:2=
5:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_264","NOCINC0004118996","Simbock =
OCM","","18-01-2025 20:25:32","18-01-2025 20:03:58","18-01-2025 20:10:47","=
No power issue site on gen  with U=3D51.1v Notice thatt site is down behind=
 Nkolzie who is not our responsability","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","Affected by 3rd Party Site"=
,"No power issue site on gen  with U=3D51.1v Notice thatt site is down behi=
nd Nkolzie who is not our responsability","system","1294","18-01-2025 20:25=
:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_143","NOCINC0004118997","Byemassi=
 Carrefour","","18-01-2025 20:25:32","18-01-2025 20:03:58","18-01-2025 20:1=
0:47","No power issue site on gen  with U=3D51.1v Notice thatt site is down=
 behind Nkolzie who is not our responsability","Paul BIBOUM","Customer Equi=
pment Failure","Active","Active Equipment Failure","Affected by 3rd Party S=
ite","No power issue site on gen  with U=3D51.1v Notice thatt site is down =
behind Nkolzie who is not our responsability","system","1294","18-01-2025 2=
0:25:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_238","NOCINC0004118994","Mendong"=
,"","18-01-2025 20:25:31","18-01-2025 20:03:58","18-01-2025 20:10:47","No p=
ower issue site on gen  with U=3D51.1v Notice thatt site is down behind Nko=
lzie who is not our responsability","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","Affected by 3rd Party Site","No=
 power issue site on gen  with U=3D51.1v Notice thatt site is down behind N=
kolzie who is not our responsability","system","1293","18-01-2025 20:25:31"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_517","NOCINC0004118993","Montee-D=
es-Soeurs","","18-01-2025 20:25:31","18-01-2025 20:03:58","18-01-2025 20:10=
:47","No power issue site on gen  with U=3D51.1v Notice thatt site is down =
behind Nkolzie who is not our responsability","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue site on gen  with U=3D51.1v Notice thatt site is down behind=
 Nkolzie who is not our responsability","system","1293","18-01-2025 20:25:3=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0004118991","Mendong =
Maeture","","18-01-2025 20:25:31","18-01-2025 20:03:58","18-01-2025 20:10:4=
7","No power issue site on gen  with U=3D51.1v Notice thatt site is down be=
hind Nkolzie who is not our responsability","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue site on gen  with U=3D51.1v Notice thatt site is down behind N=
kolzie who is not our responsability","system","1293","18-01-2025 20:25:31"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0004118995","Montee-J=
ouvence","","18-01-2025 20:25:31","18-01-2025 20:03:58","18-01-2025 20:10:4=
7","No power issue site on gen  with U=3D51.1v Notice thatt site is down be=
hind Nkolzie who is not our responsability","Hyemafo Gildas","Customer Equi=
pment Failure","Active","Active Equipment Failure","Affected by 3rd Party S=
ite","No power issue site on gen  with U=3D51.1v Notice thatt site is down =
behind Nkolzie who is not our responsability","system","1293","18-01-2025 2=
0:25:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_229","NOCINC0004118992","CRH-Etou=
g-Ebe","","18-01-2025 20:25:31","18-01-2025 20:03:58","18-01-2025 20:10:47"=
,"No power issue site on gen  with U=3D51.1v Notice thatt site is down behi=
nd Nkolzie who is not our responsability","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","Affected by 3rd Party Sit=
e","No power issue site on gen  with U=3D51.1v Notice thatt site is down be=
hind Nkolzie who is not our responsability","system","1293","18-01-2025 20:=
25:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0004118990","Accacia =
New","","18-01-2025 20:25:30","18-01-2025 20:03:58","18-01-2025 20:10:47","=
No power issue site on gen  with U=3D51.1v Notice thatt site is down behind=
 Nkolzie who is not our responsability","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on gen  with U=3D51.1v Notice thatt site is down behind Nkolzie who is not =
our responsability","system","1292","18-01-2025 20:25:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004118881","M=
EFOU ASSI","","18-01-2025 20:14:04","18-01-2025 20:03:58","18-01-2025 21:10=
:47","No power issue site on gen  with U=3D51.1v Notice thatt site is down =
behind Nkolzie who is not our responsability","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue site on gen  with U=3D51.1v Notice thatt site is down behind Nk=
olzie who is not our responsability","christian.fonkou@ihstowers.com","607"=
,"18-01-2025 20:14:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004118828","M=
efou-Assi","","18-01-2025 20:08:38","18-01-2025 20:03:58","18-01-2025 20:10=
:47","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","No power issue site on gen  with U=3D51.1v Notice thatt site is dow=
n behind Nkolzie who is not our responsability","christian.fonkou@ihstowers=
.com","3573","18-01-2025 20:08:38","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004118369","Mon=
tee Jouvence","","18-01-2025 18:39:56","18-01-2025 18:35:51","18-01-2025 19=
:39:47","Grid outage, site went down because gen failed to start // gen man=
ually started (investigation ongoing)","Hyemafo Gildas","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down be=
cause gen failed to start // gen manually started (investigation ongoing)",=
"emmanuel.ghani@ihstowers.com","246","18-01-2025 18:39:56","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004118136","Nsi=
meyong Terre Rouge","","18-01-2025 17:50:51","18-01-2025 17:43:45","18-01-2=
025 17:55:22","Grid outage, Site went down before Gen start due to poor bac=
kup// Gen automaticaly started ","MINKA NICOLAS","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup// Gen automaticaly started ","emmanu=
el.ghani@ihstowers.com","426","18-01-2025 17:50:51","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004117955","Jou=
vence Mbenda","","18-01-2025 17:30:28","18-01-2025 17:12:13","18-01-2025 17=
:48:45","Grid outage site went down because Gen started and Stopped with al=
arm High temp // he added water and Gen manually started","Hyemafo Gildas",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage site went down because Gen started and Stopped wi=
th alarm High temp // he added water and Gen manually started","emmanuel.gh=
ani@ihstowers.com","1096","18-01-2025 17:30:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0004117935","Biteng",=
"","18-01-2025 17:25:02","18-01-2025 16:53:32","18-01-2025 17:41:50","Casca=
ded Incident from TTO4118271","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down because the rectifier =
dysfonction due to high temp of the Shelter // He reset the rectifier and o=
pen the Shelter","system","277704","18-01-2025 17:25:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_795","NOCINC0004117933","Lada I Y=
de","","18-01-2025 17:25:02","18-01-2025 16:53:32","18-01-2025 17:41:50","C=
ascaded Incident from TTO4118271","Mba Lazare Herve","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because the rectif=
ier dysfonction due to high temp of the Shelter // He reset the rectifier a=
nd open the Shelter","system","277703","18-01-2025 17:25:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0004117934","Nkolo II=
 New","","18-01-2025 17:25:02","18-01-2025 16:53:32","18-01-2025 17:41:50",=
"Cascaded Incident from TTO4118271","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because the rect=
ifier dysfonction due to high temp of the Shelter // He reset the rectifier=
 and open the Shelter","system","277703","18-01-2025 17:25:02","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0004117930","Mimboman=
4","","18-01-2025 17:25:01","18-01-2025 16:53:32","18-01-2025 17:41:50","Ca=
scaded Incident from TTO4118271","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because the rectifi=
er dysfonction due to high temp of the Shelter // He reset the rectifier an=
d open the Shelter","system","277701","18-01-2025 17:25:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0004117929","NGONA","=
","18-01-2025 17:25:01","18-01-2025 16:53:32","18-01-2025 17:41:50","Cascad=
ed Incident from TTO4118271","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because the rectifier d=
ysfonction due to high temp of the Shelter // He reset the rectifier and op=
en the Shelter","system","277701","18-01-2025 17:25:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0004117931","Biteng-M=
aetur","","18-01-2025 17:25:01","18-01-2025 16:53:32","18-01-2025 17:41:50"=
,"Cascaded Incident from TTO4118271","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down because the rec=
tifier dysfonction due to high temp of the Shelter // He reset the rectifie=
r and open the Shelter","system","277702","18-01-2025 17:25:01","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_792","NOCINC0004117932","NKOABANG=
 NKOLO 3","","18-01-2025 17:25:01","18-01-2025 16:53:32","18-01-2025 17:41:=
50","Cascaded Incident from TTO4118271","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down because the =
rectifier dysfonction due to high temp of the Shelter // He reset the recti=
fier and open the Shelter","system","277702","18-01-2025 17:25:01","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0004117827","A=
v-Germaine","","18-01-2025 17:09:27","18-01-2025 17:03:21","18-01-2025 17:1=
7:57","Grid outage.no space tyo deploy mobile gen//Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space tyo deploy mobile gen//Grid return","christian.fonkou@ihstowers.com",=
"367","18-01-2025 17:09:27","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0004117767","Nko=
abang2","IHS_YND_295, IHS_YND_266, IHS_YND_249, IHS_YND_750, IHS_YND_792, I=
HS_YND_795, IHS_YND_709, IHS_YND_248","18-01-2025 17:04:03","18-01-2025 16:=
53:32","18-01-2025 17:41:50","Site went down because the rectifier dysfonct=
ion due to high temp of the Shelter // He reset the rectifier and open the =
Shelter","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down because the rectifier dysfonction due to high =
temp of the Shelter // He reset the rectifier and open the Shelter","emmanu=
el.ghani@ihstowers.com","632","18-01-2025 17:04:03","Sagemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0004117637","Nko=
abang entree carriere","","18-01-2025 16:42:40","18-01-2025 16:53:32","18-0=
1-2025 17:41:50","","Mba Lazare Herve","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","Site went down because the rectifier dysfonctio=
n due to high temp of the Shelter // He reset the rectifier and open the Sh=
elter","emmanuel.ghani@ihstowers.com","277704","18-01-2025 16:42:40","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004117262","L=
abogenie","","18-01-2025 15:30:20","18-01-2025 15:20:15","18-01-2025 18:25:=
11","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hua=
wei is informed","christian.fonkou@ihstowers.com","606","18-01-2025 15:30:2=
0","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004116795","AWA=
E OCM","","18-01-2025 14:44:38","18-01-2025 14:40:30","18-01-2025 15:10:11"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen aut=
omaticaly started ","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, Site went down before =
Gen start due to poor backup// Gen automaticaly started ","emmanuel.ghani@i=
hstowers.com","249","18-01-2025 14:44:38","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004116718","ELO=
UMDEM CARRIERE","","18-01-2025 14:38:41","18-01-2025 14:37:27","18-01-2025 =
15:03:37","Grid outage site went down because Gen started and Stopped with =
alarm Gen over frequency // He reset the Gen card and Gen manually started"=
,"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage site went down because Gen started and Stopped with alarm G=
en over frequency // He reset the Gen card and Gen manually started","emman=
uel.ghani@ihstowers.com","75","18-01-2025 14:38:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0004115194","N=
simalen OCM","","18-01-2025 13:24:59","18-01-2025 13:17:53","18-01-2025 13:=
18:50","No power issue iste on grid with U=3D54.5v Lionnel from Huawei is i=
nformed","Albran Byorel","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue iste on grid with U=3D5=
4.5v Lionnel from Huawei is informed","rouselle.schoune@ihstowers.com","427=
","18-01-2025 13:24:59","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004114682","NKO=
MKANA ELIZA HOTEL","","18-01-2025 12:26:06","18-01-2025 12:19:59","18-01-20=
25 17:06:40","Grid outage, No space to deploy MDG //Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, N=
o space to deploy MDG //Grid return","ange.kongo@ihstowers.com","368","18-0=
1-2025 12:26:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0004114663","M=
EFOU ASSI","","18-01-2025 12:22:31","18-01-2025 12:15:22","18-01-2025 12:45=
:29","Grid outage.gen start and stopped due to alarm ""high temp""// We add=
 water and gen manually started","Fanda Brice","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.ge=
n start and stopped due to alarm ""high temp""// We add water and gen manua=
lly started","rouselle.schoune@ihstowers.com","431","18-01-2025 12:22:31","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0004114646","Barriere=
 IHS","","18-01-2025 12:20:40","18-01-2025 12:14:52","18-01-2025 12:48:40",=
"Cascaded Incident from TTO4114715","Hyemafo Gildas","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen start and stopped with high temp alarm // he added water and manuall=
y start the gen","system","272893","18-01-2025 12:20:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004114640","M=
efou-Assi","IHS_YND_696","18-01-2025 12:20:01","18-01-2025 12:14:52","18-01=
-2025 12:48:40","Grid outage, site went down because gen start and stopped =
with high temp alarm // he added water and manually start the gen","Fanda B=
rice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Co=
olant Level Issue","Grid outage, site went down because gen start and stopp=
ed with high temp alarm // he added water and manually start the gen","rous=
elle.schoune@ihstowers.com","310","18-01-2025 12:20:01","Sagemcom CMR"
"Closed Complete","Warning","CTR_031","IHS_YND_319","NOCINC0004114557","SOA=
 2","","18-01-2025 12:02:25","","","site alarm because high temperature due=
 to air conditioner faulty // shelter open","Siligap Boris","Warning","Warn=
ing","ENVIRONMENT","Warning - High Temperature","site alarm because high te=
mperature due to air conditioner faulty // shelter open","adonis.defokoua@i=
hstowers.com","379","18-01-2025 12:02:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004114521","M=
endong vallee","","18-01-2025 11:58:48","18-01-2025 11:52:28","18-01-2025 1=
3:03:42","Grid outage site went down because Gen over load (20KVA; 300A)//G=
rid return IHS F=E9lix Zamb=E9 is informed and confirmed","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site we=
nt down because Gen over load (20KVA; 300A)//Grid return IHS F=E9lix Zamb=
=E9 is informed and confirmed","rouselle.schoune@ihstowers.com","679","18-0=
1-2025 11:58:48","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004114272","ELO=
UMDEM CARRIERE","","18-01-2025 11:37:52","18-01-2025 11:28:59","18-01-2025 =
12:04:51","grid outage, site went down because gen failed to start due to g=
en battery faulty // Gen manually started with External battery","Fanda Bri=
ce","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","gri=
d outage, site went down because gen failed to start due to gen battery fau=
lty // Gen manually started with External battery","ange.kongo@ihstowers.co=
m","534","18-01-2025 11:37:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004114263","M=
ontesquieux","","18-01-2025 11:35:46","18-01-2025 11:34:41","18-01-2025 11:=
45:37","site went down due to disfunctionning of rectifiers // He reset rec=
tifiers site is on grid","Paul BIBOUM","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","site went down due to disfunctionning of rectifier=
s // He reset rectifiers site is on grid","rouselle.schoune@ihstowers.com",=
"66","18-01-2025 11:35:46","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0004114259","OBA=
M NGOLA OCM","","18-01-2025 11:34:05","18-01-2025 10:34:54","18-01-2025 11:=
16:05","site went down down due to disfunctionning of MPR // He reset recti=
fiers, site on grid","MINKA NICOLAS","Equipment Repair","Passive","Rectifie=
r","Rectifier Distribution","site went down down due to disfunctionning of =
MPR // He reset rectifiers, site on grid","ange.kongo@ihstowers.com","3551"=
,"18-01-2025 11:34:05","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004114214","Men=
dong3","","18-01-2025 11:26:13","18-01-2025 11:19:49","18-01-2025 19:22:52"=
,"Grid outage, No space to deploy MDG//Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage, No space to de=
ploy MDG//Grid return","ange.kongo@ihstowers.com","385","18-01-2025 11:26:1=
3","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004114179","ODZ=
A MINKAN EDIBI ASSI","","18-01-2025 11:21:53","18-01-2025 11:05:48","18-01-=
2025 12:58:00","grid outage,gen failed to start due to bloc contactor(gen a=
nd grid) disfunction/he excited the bloc contactor:site on grid","Albran By=
orel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","grid ou=
tage,gen failed to start due to bloc contactor(gen and grid) disfunction/he=
 excited the bloc contactor:site on grid","ange.kongo@ihstowers.com","966",=
"18-01-2025 11:21:53","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004114031","Men=
dong vallee","","18-01-2025 11:04:14","18-01-2025 10:23:06","18-01-2025 11:=
07:59","grid outae, site went down because gen failed to start due to Gen o=
verload (20KVA, 320A) (Felix Zambo IHS confirm) // Grid return","Fanda Bric=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","grid outae, s=
ite went down because gen failed to start due to Gen overload (20KVA, 320A)=
 (Felix Zambo IHS confirm) // Grid return","ange.kongo@ihstowers.com","2469=
","18-01-2025 11:04:14","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004113723","Mes=
sa Carriere","","18-01-2025 10:15:54","18-01-2025 10:06:59","18-01-2025 11:=
25:20","grid outage, site went dow because gen failed to start due to gen c=
ard faulty // Gen manually started","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","grid outage, site went dow because=
 gen failed to start due to gen card faulty // Gen manually started","ange.=
kongo@ihstowers.com","536","18-01-2025 10:15:54","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004113599","Mon=
tee Jouvence","","18-01-2025 10:02:26","18-01-2025 09:50:15","18-01-2025 10=
:05:56","site went down because gen failed to start due to grid fluctuation=
 // Gen manually started","Hyemafo Gildas","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","site went down because gen failed=
 to start due to grid fluctuation // Gen manually started","ange.kongo@ihst=
owers.com","731","18-01-2025 10:02:26","Sagemcom CMR"
"Closed Complete","Warning","T0459","IHS_YND_240","NOCINC0004113494","Monte=
e Jouvence","","18-01-2025 09:46:12","","","	site alarm because gen failed =
to start due to grid fluctuation // Gen manually started","Hyemafo Gildas",=
"Warning","Warning","POWER","Warning - National Grid - Grid Incomplete Phas=
e","site alarm because gen failed to start due to grid fluctuation // Gen m=
anually started","adonis.defokoua@ihstowers.com","492","18-01-2025 09:46:12=
","Sagemcom CMR"
"Closed Complete","Warning","T0843","IHS_YND_719","NOCINC0004113473","TSING=
A VILLAGE 2","","18-01-2025 09:43:13","","","","Delor Telezing","Warning","=
Warning","ENVIRONMENT","Warning - High Temperature","Alarm cleared","adonis=
.defokoua@ihstowers.com","491","18-01-2025 09:43:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004113431","L=
abogenie","","18-01-2025 09:36:10","18-01-2025 09:30:05","18-01-2025 10:25:=
44","Active//No power issue on site Ubaie=3D54.6V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site Ubaie=3D54.6V site on Grid The Tx Fme Eloundou/693212405 of hua=
wei is informed","rouselle.schoune@ihstowers.com","366","18-01-2025 09:36:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004113341","NKO=
MEKUI OCM","","18-01-2025 09:34:22","18-01-2025 09:28:15","18-01-2025 12:30=
:11","no power issue on site U=3D54.5  V site on Gen.Site impacted by Mbank=
olo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
no power issue on site U=3D54.5  V site on Gen.Site impacted by Mbankolo Ca=
mtel and not managing by IHS","ange.kongo@ihstowers.com","368","18-01-2025 =
09:34:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0004113326","Mendong =
vallee","","18-01-2025 09:33:40","18-01-2025 09:24:38","18-01-2025 09:45:24=
","Cascaded Incident from TTO4113157","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because gen failed =
to start due to grid fluctuation // Gen manually started","system","1218301=
","18-01-2025 09:33:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004113300","M=
endong","IHS_YND_692, IHS_YND_236","18-01-2025 09:32:42","18-01-2025 09:24:=
38","18-01-2025 09:45:24","site went down because gen failed to start due t=
o grid fluctuation // Gen manually started","Hyemafo Gildas","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","site went down =
because gen failed to start due to grid fluctuation // Gen manually started=
","rouselle.schoune@ihstowers.com","485","18-01-2025 09:32:42","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0004113282","M=
ontee-Jouvence","","18-01-2025 09:31:43","18-01-2025 09:24:38","18-01-2025 =
09:45:24","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","site went down because gen failed to start due to grid f=
luctuation // Gen manually started","rouselle.schoune@ihstowers.com","12183=
02","18-01-2025 09:31:43","Sagemcom CMR"
"Closed Complete","Warning","CTR_025","IHS_YND_238","NOCINC0004113231","Men=
dong","","18-01-2025 09:29:28","","","","Hyemafo Gildas","Warning","Warning=
","POWER","Warning - AC Phase 3 Voltage low","Alarm cleared","adonis.defoko=
ua@ihstowers.com","486","18-01-2025 09:29:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0004112145","M=
vog-Ebanda","","18-01-2025 05:59:41","18-01-2025 03:12:57","18-01-2025 06:2=
7:49","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","site went down due to Theft of cable in DC BOX (12m) // He no=
rmalized the cables, site on grid","alexandre.kamal@ihstowers.com","1226126=
","18-01-2025 05:59:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0004111772","A=
bom","IHS_YND_269","18-01-2025 03:40:05","18-01-2025 03:12:57","18-01-2025 =
07:27:49","site went down due to Theft of cable in DC BOX (12m) // He norma=
lized the cables, site on grid","Siligap Boris","Site Asset Theft","Theft",=
"Theft","AC Cable Stolen","site went down due to Theft of cable in DC BOX (=
12m) // He normalized the cables, site on grid","alexandre.kamal@ihstowers.=
com","1629","18-01-2025 03:40:05","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004110371","Men=
dong vallee","","17-01-2025 21:51:15","17-01-2025 21:45:53","17-01-2025 22:=
13:26","Site went down due to insufficience of rectifiers (06) on site, Fel=
ix Zamb=E9 confirmed// Site stabilized","Fanda Brice","Equipment Repair","P=
assive","Rectifier","Rectifier Module","Site went down due to insufficience=
 of rectifiers (06) on site, Felix Zamb=E9 confirmed// Site stabilized","st=
ephane.nkamwa@ihstowers.com","323","17-01-2025 21:51:15","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004110265","NYO=
M FACE MAETUR","","17-01-2025 21:34:08","17-01-2025 21:24:48","17-01-2025 2=
3:12:26","Site went down because CB (150A) burned in pwc //He did a bridge =
a CB(80A) with CB (63*63)","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down beca=
use CB (150A) burned in pwc //He did a bridge a CB(80A) with CB (63*63)","s=
tephane.nkamwa@ihstowers.com","562","17-01-2025 21:34:08","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004109233","Tsi=
nga village","","17-01-2025 19:18:04","17-01-2025 19:12:57","17-01-2025 21:=
00:05","Site went down because the Cb(200A) of second bay burn // He bypass=
 the Cb","Delor Telezing","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Circuit Breaker Issue","Site went down because the Cb(200A) of=
 second bay burn // He bypass the Cb","stephane.nkamwa@ihstowers.com","308"=
,"17-01-2025 19:18:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004109022","Dong",""=
,"17-01-2025 18:39:51","17-01-2025 17:09:27","17-01-2025 17:25:40","Cascade=
d Incident from TTO4108064","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Site went down because Gen started and sto=
pped with alarm under voltage // he cleaned the pear and Gen manually start=
ed","system","276868","17-01-2025 18:39:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004109021","Donga","=
","17-01-2025 18:39:51","17-01-2025 17:09:27","17-01-2025 17:25:40","Cascad=
ed Incident from TTO4108064","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because Gen started and st=
opped with alarm under voltage // he cleaned the pear and Gen manually star=
ted","system","276868","17-01-2025 18:39:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0004109011","N=
guila","IHS_YND_434, IHS_YND_444","17-01-2025 18:37:46","17-01-2025 17:09:2=
7","17-01-2025 17:27:17","Site went down because Gen started and stopped wi=
th alarm under voltage // he reset it and cleaned the pear and Gen manually=
 started","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - C=
ontrol Panel","Site went down because Gen started and stopped with alarm un=
der voltage // he reset it and cleaned the pear and Gen manually started","=
kouoh.jean@ihstowers.com","5300","17-01-2025 18:37:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0004108937","O=
ssombe","","17-01-2025 18:28:19","17-01-2025 15:27:39","17-01-2025 16:00:07=
","Site went down because Gen started and stopped due to fuel filter gasket=
 faulty // He replaced the fuel filter gasket and Gen Manually started","Pa=
rker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Filter","=
Site went down because Gen started and stopped due to fuel filter gasket fa=
ulty // He replaced the fuel filter gasket and Gen Manually started","kouoh=
.jean@ihstowers.com","10841","17-01-2025 18:28:19","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0004108444","Ona=
ngondi (melen bikop)","","17-01-2025 17:00:42","17-01-2025 16:51:34","17-01=
-2025 17:55:22","Grid outage, Site went down because Gen stopped due to ""h=
igh temp"" alarm// we added water and gen manually started ","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, Site went down because Gen stopped due to ""high=
 temp"" alarm// we added water and gen manually started ","stephane.nkamwa@=
ihstowers.com","549","17-01-2025 17:00:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0004108441","Leboudi"=
,"","17-01-2025 17:00:01","17-01-2025 16:23:38","17-01-2025 17:01:20","Casc=
aded Incident from TTO4107152","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","grid outage,site went down b=
ecause gen overload(20kva;380A) SS IHS Blaise confirmed//he reduice the loa=
d","system","279503","17-01-2025 17:00:01","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004108226","Nko=
lafeme","IHS_YND_309","17-01-2025 16:31:44","17-01-2025 16:23:38","17-01-20=
25 17:01:20","grid outage,site went down because gen overload(20kva;380A) S=
S IHS Blaise confirmed//he reduice the load","TIENTCHEU NZETCHIEU GAEL","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","grid outage,site we=
nt down because gen overload(20kva;380A) SS IHS Blaise confirmed//he reduic=
e the load","stephane.nkamwa@ihstowers.com","486","17-01-2025 16:31:44","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004106671","Akak-Nko=
zoa-MTN-IHS","","17-01-2025 13:29:50","17-01-2025 13:25:41","17-01-2025 13:=
34:57","Cascaded Incident from TTO4105293","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","eneo outage, site down du=
e to poor battery back-up // eneo return","system","290324","17-01-2025 13:=
29:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004106423","E=
koumdoum","","17-01-2025 12:47:30","17-01-2025 12:39:22","17-01-2025 13:03:=
22","Grid Outage, site went down because Gen stopped with ""high temp"" ala=
rm due to accordion cut// He reconnected accord=E9on, added water and start=
ed Gen manualy","Albran Byorel","Equipment Repair","Passive","ACDG Gen","AC=
DG - High Engine Temp - Coolant Level Issue","Grid Outage, site went down b=
ecause Gen stopped with ""high temp"" alarm due to accordion cut// He recon=
nected accord=E9on, added water and started Gen manualy","christian.fonkou@=
ihstowers.com","489","17-01-2025 12:47:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0004105994","O=
ssombe","","17-01-2025 11:46:04","17-01-2025 11:39:54","17-01-2025 15:08:37=
","Site went down because Gen started and stopped due to fuel filter gasket=
 faulty // He replaced the fuel filter gasket and Gen Manually started","Pa=
rker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Filter","=
Site went down because Gen started and stopped due to fuel filter gasket fa=
ulty // He replaced the fuel filter gasket and Gen Manually started","chris=
tian.fonkou@ihstowers.com","371","17-01-2025 11:46:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004105470","M=
essa-Carriere OCM","","17-01-2025 10:34:57","17-01-2025 10:27:52","17-01-20=
25 10:30:19","No power issue on site U=3D52v site on grid Tx fme Mohamadou =
of huawei is informed","","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52v site o=
n grid Tx fme Mohamadou of huawei is informed","christian.fonkou@ihstowers.=
com","427","17-01-2025 10:34:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004104553","Saa","",=
"17-01-2025 07:41:21","17-01-2025 07:38:57","17-01-2025 08:54:52","Cascaded=
 Incident from TTO4102852","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outge,Gen Ran till fuel shortage//Refu=
eling done","system","267687","17-01-2025 07:41:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004104552","SAA Entr=
ance","","17-01-2025 07:41:20","17-01-2025 07:38:57","17-01-2025 08:54:52",=
"Cascaded Incident from TTO4102852","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outge,Gen Ran till fuel short=
age//Refueling done","system","267687","17-01-2025 07:41:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004104544","S=
AA 2","IHS_YND_542, IHS_YND_405","17-01-2025 07:38:15","17-01-2025 07:34:57=
","17-01-2025 08:54:52","Grid outge,Gen Ran till fuel shortage//Refueling d=
one","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid=
 outge,Gen Ran till fuel shortage//Refueling done","christian.fonkou@ihstow=
ers.com","199","17-01-2025 07:38:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004104045","C=
rf-Nsam","","17-01-2025 06:00:15","17-01-2025 05:58:50","17-01-2025 07:20:3=
7","ACTIVE / No power issue site on Grid with U=3D50,5 V The Tx FME Tchana =
Patrice 695007608 of huawei is informed","MINKA NICOLAS","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE=
 / No power issue site on Grid with U=3D50,5 V The Tx FME Tchana Patrice 69=
5007608 of huawei is informed","olivier.kwedi@ihstowers.com","86","17-01-20=
25 06:00:15","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0004103772","Nsi=
meyong Terre Rouge","","17-01-2025 04:06:59","17-01-2025 03:59:50","17-01-2=
025 04:11:50","Grid outage, site went down before gen start due to poor bat=
tery backup // gen start automatically","MINKA NICOLAS","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site =
went down before gen start due to poor battery backup // gen start automati=
cally","ludivine.ngamaleu@ihstowers.com","430","17-01-2025 04:06:59","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004103404","E=
koumdoum OCM","","17-01-2025 02:05:24","17-01-2025 02:01:13","17-01-2025 03=
:22:33","Grid outage, Site went down because Gen overload (20kva, 300A) SS =
IHS alphonse confirmed// site on GEN","Albran Byorel","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, Site went down because G=
en overload (20kva, 300A) SS IHS alphonse confirmed// site on GEN","olivier=
.kwedi@ihstowers.com","252","17-01-2025 02:05:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004103395","E=
koumdoum","","17-01-2025 02:03:32","17-01-2025 01:54:23","17-01-2025 03:00:=
57","Grid Outage, site went down because Gen stopped with ""high temp"" ala=
rm due to accordion cut// He reconnected accord=E9on, added water and start=
ed Gen manualy","Albran Byorel","Equipment Repair","Passive","ACDG Gen","AC=
DG - High Engine Temp - Coolant Level Issue","Grid Outage, site went down b=
ecause Gen stopped with ""high temp"" alarm due to accordion cut// He recon=
nected accord=E9on, added water and started Gen manualy","olivier.kwedi@ihs=
towers.com","550","17-01-2025 02:03:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_396","NOCINC0004103362","Nkolmvac=
k","","17-01-2025 01:56:23","17-01-2025 01:41:25","17-01-2025 01:42:12","Ca=
scaded Incident from TTO4101379","Parker Tchoup","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Sites down due to fiber cut between Yaou=
nde and Mbankomo (reported by HUAWEI NOC).","system","267643","17-01-2025 0=
1:56:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0004100813","M=
endong Maeture","","16-01-2025 22:44:00","16-01-2025 22:04:20","16-01-2025 =
22:06:00"," No power issue, site is on grid with Ubaie=3D54,5V, Mbah hosiah=
(699699694) from Huawei is informed.","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No powe=
r issue, site is on grid with Ubaie=3D54,5V, Mbah hosiah(699699694) from Hu=
awei is informed.","olivier.kwedi@ihstowers.com","2381","16-01-2025 22:44:0=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004100780","ELOUMDEM=
 CARRIERE 2","","16-01-2025 22:38:51","16-01-2025 22:35:02","16-01-2025 22:=
56:26","Cascaded Incident from TTO4098687","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because gen start and stopped due to grid bad voltage // he bypassed th=
e Grid and site on GEN","system","293217","16-01-2025 22:38:51","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004100779","Eto koss=
 Yde","","16-01-2025 22:38:50","16-01-2025 22:35:02","16-01-2025 22:56:26",=
"Cascaded Incident from TTO4098687","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause gen start and stopped due to grid bad voltage // he bypassed the Grid =
and site on GEN","system","293217","16-01-2025 22:38:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004100774","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","16-01-2025 22:38:08","16-01-2025 22:35=
:02","16-01-2025 22:56:26","Grid fluctuation, site went down because gen st=
art and stopped due to grid bad voltage // he bypassed the Grid and site on=
 GEN","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation, site went down because gen start and s=
topped due to grid bad voltage // he bypassed the Grid and site on GEN","lu=
divine.ngamaleu@ihstowers.com","188","16-01-2025 22:38:08","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004100167","Elo=
umdem stade","","16-01-2025 21:13:35","16-01-2025 20:47:19","16-01-2025 21:=
23:19","Grid fluctuation,site went down because Gen failed to start due to =
bad voltage,NO RCP// he bypass the Grid and site on Gen","Fanda Brice","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation,site went down because Gen failed to start due to bad voltage,N=
O RCP// he bypass the Grid and site on Gen","kamga.virgile@ihstowers.com","=
1577","16-01-2025 21:13:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004100050","E=
koumdoum","","16-01-2025 20:57:26","16-01-2025 20:14:22","16-01-2025 20:38:=
22","Grid Outage, site went down because Gen stopped with ""high temp"" ala=
rm due to accordion cut// He reconnected accord=E9on, added water and start=
ed Gen manualy","Albran Byorel","Equipment Repair","Passive","ACDG Gen","AC=
DG - High Engine Temp - Coolant Level Issue","Grid Outage, site went down b=
ecause Gen stopped with ""high temp"" alarm due to accordion cut// He recon=
nected accord=E9on, added water and started Gen manualy","alexandre.kamal@i=
hstowers.com","2585","16-01-2025 20:57:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0004099739","A=
wae Ewonkan","","16-01-2025 20:13:11","16-01-2025 20:06:08","16-01-2025 21:=
39:18","Grid outage, Site went down because Gen overload (20kva/270A) causi=
ng by landord which is connected on our link // site on GEN IHS supervisor =
Alphonse has confirmed","Albran Byorel","Equipment Repair","Passive","ACDG =
Gen","ACDG - Overload","Grid outage, Site went down because Gen overload (2=
0kva/270A) causing by landord which is connected on our link // site on GEN=
 IHS supervisor Alphonse has confirmed","alexandre.kamal@ihstowers.com","42=
4","16-01-2025 20:13:11","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004099546","Nko=
lnda","","16-01-2025 19:39:55","16-01-2025 19:22:46","16-01-2025 20:04:51",=
"Site went down due to CB (125A)Disjunted in the DC-Box  causing by Poor Ba=
ttery Backup // he Reamed he CB (125A) and Site is on Gen ","Albran Byorel"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Brea=
ker Issue","Site went down due to CB (125A)Disjunted in the DC-Box  causing=
 by Poor Battery Backup // he Reamed he CB (125A) and Site is on Gen ","kam=
ga.virgile@ihstowers.com","1030","16-01-2025 19:39:55","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004099538","Men=
dong NB","","16-01-2025 19:38:47","16-01-2025 19:18:32","16-01-2025 20:05:1=
3","Site went down due to CB (80A) tripped in DC Box// CB put back on","","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breake=
r Issue","Site went down due to CB (80A) tripped in DC Box// CB put back on=
","kamga.virgile@ihstowers.com","1215","16-01-2025 19:38:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004099465","MEHANDAN=
","","16-01-2025 19:24:10","16-01-2025 19:14:55","16-01-2025 19:35:01","Cas=
caded Incident from TTO4097134","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n start and stopped with alarm ""low oil pressure""(unprouven Alarm)// He r=
eset Gen card and Gen manually started","system","269145","16-01-2025 19:24=
:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004099462","O=
dza II OCM","IHS_YND_528","16-01-2025 19:23:13","16-01-2025 19:14:55","16-0=
1-2025 19:35:01","Grid outage, site went down because gen start and stopped=
 with alarm ""low oil pressure""(unprouven Alarm)// He reset Gen card and G=
en manually started","Albran Byorel","Equipment Repair","Passive","ACDG Gen=
","ACDG - Control Panel","Grid outage, site went down because gen start and=
 stopped with alarm ""low oil pressure""(unprouven Alarm)// He reset Gen ca=
rd and Gen manually started","alexandre.kamal@ihstowers.com","500","16-01-2=
025 19:23:13","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004098113","NYO=
M FACE MAETUR","","16-01-2025 16:27:22","16-01-2025 16:15:14","16-01-2025 1=
6:37:25","Site went down due to work: Our Supervisor Daniel Fomekong/656072=
361/SAGEMCOM working on site (replacement of Gen card)// End of work","Fabr=
ice Pouakam","Equipment Replacement","Passive","Planned Activity","Planned =
Activity - Passive","Site went down due to work: Our Supervisor Daniel Fome=
kong/656072361/SAGEMCOM working on site (replacement of Gen card)// End of =
work","kamga.virgile@ihstowers.com","730","16-01-2025 16:27:22","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004097532","S=
tade-Abega","","16-01-2025 15:04:07","16-01-2025 14:58:01","16-01-2025 15:1=
5:36","Grid outage, Site went down because PWC disfunctionning// He reset P=
WC and started Gen manualy","Mba Lazare Herve","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage, Site went down bec=
ause PWC disfunctionning// He reset PWC and started Gen manualy","alexandre=
.kamal@ihstowers.com","367","16-01-2025 15:04:07","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_263","NOCINC0004096069","Mendong Pl=
ateau","","16-01-2025 13:48:24","","","Felix is on site","Hyemafo Gildas","=
Warning","Warning","POWER","Warning - AC Phase 3 Voltage low","Alarm cleare=
d","kouoh.jean@ihstowers.com","208","16-01-2025 13:48:24","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004095444","Man=
guiers Dispensaire","","16-01-2025 13:29:25","16-01-2025 00:41:59","16-01-2=
025 01:45:00","Grid outage site went down because Gen failed  to start due =
to grid contactor faulty// Gen manually started","Fabrice Pouakam","Equipme=
nt Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage site went=
 down because Gen failed  to start due to grid contactor faulty// Gen manua=
lly started","kouoh.jean@ihstowers.com","46047","16-01-2025 13:29:25","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004095239","M=
balla 4","","16-01-2025 13:04:14","15-01-2025 22:13:48","15-01-2025 22:58:4=
8","Site went down due insufficience of rectifier (06) RM IHS Alphonse DEFF=
O CONFIRMED// He added 01 rectifier ","Delor Telezing","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down due insufficience o=
f rectifier (06) RM IHS Alphonse DEFFO CONFIRMED// He added 01 rectifier ",=
"kouoh.jean@ihstowers.com","53509","16-01-2025 13:04:14","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004095222","ODZ=
A MINKAN EDIBI ASSI","","16-01-2025 13:02:05","16-01-2025 12:54:55","16-01-=
2025 13:40:07","grid outage,gen failed to start due to bloc contactor(gen a=
nd grid) disfunction/he excited the bloc contactor:site on grid","Albran By=
orel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","grid ou=
tage,gen failed to start due to bloc contactor(gen and grid) disfunction/he=
 excited the bloc contactor:site on grid","stephane.nkamwa@ihstowers.com","=
431","16-01-2025 13:02:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0004095057","M=
vog-Ebanda","","16-01-2025 12:33:48","16-01-2025 12:19:22","16-01-2025 12:2=
5:57","no power issue on site  Ubaie =3D54.3V   site on Grid. Symphorien(69=
1316854) from Huawei is working on site","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no pow=
er issue on site  Ubaie =3D54.3V   site on Grid. Symphorien(691316854) from=
 Huawei is working on site","kouoh.jean@ihstowers.com","867","16-01-2025 12=
:33:48","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0004094971","Elo=
umdem stade","","16-01-2025 12:21:14","16-01-2025 12:08:08","16-01-2025 14:=
09:26","Grid outage, Site went down Gen stopped due to Fuel Pipe issue// He=
 normalized Fuel Pipe and started Gen manualy","Fanda Brice","Fuel Outage (=
Probable)","Passive","Diesel","Fuel Line Issue","Grid outage, Site went dow=
n Gen stopped due to Fuel Pipe issue// He normalized Fuel Pipe and started =
Gen manualy","stephane.nkamwa@ihstowers.com","787","16-01-2025 12:21:14","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004094925","Akak-Nko=
zoa-MTN-IHS","","16-01-2025 12:11:30","16-01-2025 11:37:07","16-01-2025 11:=
42:07","Cascaded Incident from TTO4091854","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","grid Outage, Site down du=
e to poor backup // Grid Return","system","289960","16-01-2025 12:11:30","S=
agemcom CMR"
"Closed Complete","Warning","CTR_029","IHS_YND_046","NOCINC0004094835","Djo=
ungolo","","16-01-2025 11:51:39","","","site on battery","Mboua Thierry","W=
arning","Warning","POWER","Warning - AC Phase 3 Current Low","Alarm cleared=
","dorothy.djantio@ihstowers.com","64","16-01-2025 11:51:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004094740","A=
WAE OCM","","16-01-2025 11:39:15","16-01-2025 11:15:51","16-01-2025 11:20:5=
1","Grid outage, Site went down before Gen start due to poor backup// Gen s=
tarted automatically","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Gen started automatically","kouoh.jean@ihs=
towers.com","1405","16-01-2025 11:39:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004094660","E=
kounou","","16-01-2025 11:29:16","15-01-2025 14:41:08","15-01-2025 17:02:08=
","Site went down because 2 CB (125A) Tripped due to load increase// He did=
i a bridge","Albran Byorel","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Circuit Breaker Issue","Site went down because 2 CB (125A) T=
ripped due to load increase// He didi a bridge","dorothy.djantio@ihstowers.=
com","74889","16-01-2025 11:29:16","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004094611","Sap=
eur","","16-01-2025 11:23:35","16-01-2025 11:16:20","16-01-2025 11:24:59","=
Grid outage, Site went down before Gen start due to poor backup// Gen autom=
aticaly started ","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup// Gen automaticaly started ","stephane.nkamwa@ihsto=
wers.com","436","16-01-2025 11:23:35","Sagemcom CMR"
"Closed Complete","Warning","T0217","IHS_YND_018","NOCINC0004094605","P&T B=
uilding","","16-01-2025 11:22:21","","","site on battery due to grid outage=
//grid return","","Warning","Warning","POWER","Warning - Site on Battery","=
site on battery due to grid outage//grid return","dorothy.djantio@ihstowers=
.com","125","16-01-2025 11:22:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004094149","E=
ssomba","","16-01-2025 10:31:19","16-01-2025 10:21:11","16-01-2025 11:13:28=
","site went down due to rectifiers disfunctionning//he reset the rectifier=
s","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","site went down due to rectifiers disfunctionning//he reset the rect=
ifiers","kouoh.jean@ihstowers.com","610","16-01-2025 10:31:19","Sagemcom CM=
R"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004093400","NYO=
M FACE MAETUR","","16-01-2025 08:36:10","16-01-2025 08:29:05","16-01-2025 1=
0:23:33","Grid outage site went down because Gen failed to start due to Gen=
 card faulty // Gen Manually Started","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down bec=
ause Gen failed to start due to Gen card faulty // Gen Manually Started","s=
tephane.nkamwa@ihstowers.com","426","16-01-2025 08:36:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004093225","Ngoum","=
","16-01-2025 08:01:50","16-01-2025 07:51:30","16-01-2025 09:01:24","Cascad=
ed Incident from TTO4089899","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outge,Gen Ran till fuel shortage due=
 to pierced return pipe //he normalized and Refueling done","system","43277=
9","16-01-2025 08:01:50","Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0004093219","Yok=
o MTN","IHS_YND_475","16-01-2025 08:00:47","16-01-2025 07:51:30","16-01-202=
5 09:01:24","Grid outge,Gen Ran till fuel shortage due to pierced return pi=
pe //he normalized and Refueling done","Parker Tchoup","Fuel Outage","Passi=
ve","Diesel","Diesel Outage","Grid outge,Gen Ran till fuel shortage due to =
pierced return pipe //he normalized and Refueling done","stephane.nkamwa@ih=
stowers.com","558","16-01-2025 08:00:47","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0004092880","Ole=
mbe","","16-01-2025 06:51:54","16-01-2025 06:43:36","16-01-2025 06:51:32","=
Site went down because Gen failed to start due to Grid bad voltage and RCP =
faulty on site // He bypass the Grid and Gen manually started","Fabrice Pou=
akam","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Site went down because Gen failed to start due to Grid bad voltage and=
 RCP faulty on site // He bypass the Grid and Gen manually started","stepha=
ne.nkamwa@ihstowers.com","499","16-01-2025 06:51:54","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0004091009","HOP=
ITAL GENERAL RAIL YDE","","15-01-2025 21:42:11","15-01-2025 21:14:12","15-0=
1-2025 22:16:59","site went down because Gen failed to start due to lack of=
 1 phase on site // he did a bridge with a good phase","Delor Telezing","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","site=
 went down because Gen failed to start due to lack of 1 phase on site // he=
 did a bridge with a good phase","ludivine.ngamaleu@ihstowers.com","1680","=
15-01-2025 21:42:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004090184","M=
balla 4","","15-01-2025 20:11:53","15-01-2025 20:08:43","15-01-2025 21:05:0=
8","Site went down due insufficience of rectifier (06) RM IHS Alphonse DEFF=
O CONFIRMED// He added 01 rectifier ","Delor Telezing","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down due insufficience o=
f rectifier (06) RM IHS Alphonse DEFFO CONFIRMED// He added 01 rectifier ",=
"dorothy.djantio@ihstowers.com","192","15-01-2025 20:11:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0004089630","Etoudi 2=
","","15-01-2025 18:26:31","15-01-2025 18:01:10","15-01-2025 18:39:29","Cas=
caded Incident from TTO4085472","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
Gen started and stopped with alarm ' low oil pressure""// He added oil and =
started Gen manualy","system","353283","15-01-2025 18:26:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0004089628","Abattoir=
","","15-01-2025 18:26:31","15-01-2025 18:01:10","15-01-2025 18:39:29","Cas=
caded Incident from TTO4085472","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
Gen started and stopped with alarm ' low oil pressure""// He added oil and =
started Gen manualy","system","353284","15-01-2025 18:26:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0004089629","ETOUDI C=
HAPELLE","","15-01-2025 18:26:31","15-01-2025 18:01:10","15-01-2025 18:39:2=
9","Cascaded Incident from TTO4085472","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
cause Gen started and stopped with alarm ' low oil pressure""// He added oi=
l and started Gen manualy","system","353284","15-01-2025 18:26:31","Sagemco=
m CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0004089505","San=
ta Barbara Yde","","15-01-2025 18:08:03","15-01-2025 18:03:57","15-01-2025 =
18:14:57","ACTIVE//No power issue, site is on grid with Ubaie=3D54,4 V, The=
 Tx FME Synphorien//691316854 from Huawei is informed.","Delor Telezing","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE//No power issue, site is on grid with Ubaie=3D54,4 V, The =
Tx FME Synphorien//691316854 from Huawei is informed.","ludivine.ngamaleu@i=
hstowers.com","247","15-01-2025 18:08:03","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0004089501","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","15-01-2025 18:07:15","15-01-2=
025 18:00:26","15-01-2025 18:39:29","Grid outage, Site went down because Ge=
n started and stopped with alarm ' low oil pressure""// He added oil and st=
arted Gen manualy","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen=
","ACDG - Low Oil Pressure","Grid outage, Site went down because Gen starte=
d and stopped with alarm ' low oil pressure""// He added oil and started Ge=
n manualy","ludivine.ngamaleu@ihstowers.com","1265","15-01-2025 18:07:15","=
Sagemcom CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004089152","Pha=
rmacie Bleue","","15-01-2025 17:09:11","15-01-2025 17:00:56","15-01-2025 18=
:02:56","Grid outage, site went down because gen fails to start due to batt=
ery ge faulty // gen start with battery backup","Siligap Boris","Equipment =
Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, site =
went down because gen fails to start due to battery ge faulty // gen start =
with battery backup","ludivine.ngamaleu@ihstowers.com","495","15-01-2025 17=
:09:11","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0004089140","Ngo=
usso Vallee","","15-01-2025 17:05:37","15-01-2025 17:00:56","15-01-2025 18:=
21:23","Grid outage ,site went down because gen stopped wiyh alarm"" low oi=
l pressure "" (unprouven Alarm)//He reset Gen card and started Gen ","Silig=
ap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage ,site went down because gen stopped wiyh alarm"" low oil pressur=
e "" (unprouven Alarm)//He reset Gen card and started Gen ","ludivine.ngama=
leu@ihstowers.com","972","15-01-2025 17:05:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0004088824","E=
koumdoum OCM","","15-01-2025 16:06:10","15-01-2025 16:00:05","15-01-2025 16=
:05:52","ACTIVE//No power issue on site ,site on Grid with Ubaie=3D 54V The=
 Tx FME Leonel Adjep /655184876/From HUAWEI is informed","Albran Byorel","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE//No power issue on site ,site on Grid with Ubaie=3D 54V Th=
e Tx FME Leonel Adjep /655184876/From HUAWEI is informed","dorothy.djantio@=
ihstowers.com","366","15-01-2025 16:06:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004088188","S=
aa","","15-01-2025 14:29:37","15-01-2025 14:21:31","15-01-2025 15:12:31","G=
rid outage, site went down because gen start and stopped with high temp ala=
rm // he opened the door and manually started","Parker Tchoup","Equipment R=
epair","Passive","ACDG Gen","Gen Temp High","Grid outage, site went down be=
cause gen start and stopped with high temp alarm // he opened the door and =
manually started","dorothy.djantio@ihstowers.com","487","15-01-2025 14:29:3=
7","Sagemcom CMR"
"Closed Complete","Site Down","CTR_360","IHS_YND_373","NOCINC0004088157","M=
aloun","","15-01-2025 14:21:15","15-01-2025 14:14:13","15-01-2025 14:20:13"=
,"Site went down because PWC dysfunctioning // He reduced the load, Site on=
 Gen (PWC to be replace)","Kemeni Franklin","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","Site went down because PWC dysfunc=
tioning // He reduced the load, Site on Gen (PWC to be replace)","dorothy.d=
jantio@ihstowers.com","423","15-01-2025 14:21:15","Sagemcom CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004088135","Nko=
l-Mebanga","","15-01-2025 14:18:09","15-01-2025 14:03:00","15-01-2025 14:10=
:35","ACTIVE // No power issue on site, site on Gen The Tx FME Gregoire/654=
547479 from huawei is informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE // No po=
wer issue on site, site on Gen The Tx FME Gregoire/654547479 from huawei is=
 informed","ludivine.ngamaleu@ihstowers.com","910","15-01-2025 14:18:09","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0004088037","NKONGKAR=
AK","","15-01-2025 14:04:43","15-01-2025 13:29:35","15-01-2025 14:27:31","C=
ascaded Incident from TTO4083663","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because PW=
C dysfunctioning // He reduced the load, Site on Gen (PWC to be replace)","=
system","369440","15-01-2025 14:04:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0004088036","Ekekam",=
"","15-01-2025 14:04:42","15-01-2025 13:29:35","15-01-2025 14:27:31","Casca=
ded Incident from TTO4083663","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because PWC dy=
sfunctioning // He reduced the load, Site on Gen (PWC to be replace)","syst=
em","369439","15-01-2025 14:04:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0004088034","Mambine"=
,"","15-01-2025 14:04:42","15-01-2025 13:29:35","15-01-2025 14:27:31","Casc=
aded Incident from TTO4083663","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because PWC dysfunctioning=
 // He reduced the load, Site on Gen (PWC to be replace)","system","369442"=
,"15-01-2025 14:04:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0004088031","Nkeng li=
kok","","15-01-2025 14:04:41","15-01-2025 13:29:35","15-01-2025 14:27:31","=
Cascaded Incident from TTO4083663","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because PWC dysfun=
ctioning // He reduced the load, Site on Gen (PWC to be replace)","system",=
"369441","15-01-2025 14:04:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0004088032","Ebeba","=
","15-01-2025 14:04:41","15-01-2025 13:29:35","15-01-2025 14:27:31","Cascad=
ed Incident from TTO4083663","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because PWC dysfunctioning /=
/ He reduced the load, Site on Gen (PWC to be replace)","system","369441","=
15-01-2025 14:04:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0004088030","Lobo 2",=
"","15-01-2025 14:04:41","15-01-2025 13:29:35","15-01-2025 14:27:31","Casca=
ded Incident from TTO4083663","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because PWC dy=
sfunctioning // He reduced the load, Site on Gen (PWC to be replace)","syst=
em","369440","15-01-2025 14:04:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0004088033","Bot Maka=
k","","15-01-2025 14:04:41","15-01-2025 13:29:35","15-01-2025 14:27:31","Ca=
scaded Incident from TTO4083663","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site went down because PWC dysfunctioning // He re=
duced the load, Site on Gen (PWC to be replace)","system","369441","15-01-2=
025 14:04:41","Sagemcom CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0004088017","LOB=
O MTN","IHS_EDA_025, IHS_YND_783, IHS_YND_347, IHS_YND_339, IHS_YND_421, IH=
S_YND_350, IHS_EDA_101, IHS_YND_714, IHS_YND_713","15-01-2025 14:01:54","15=
-01-2025 13:29:35","15-01-2025 14:27:31","Site went down because PWC dysfun=
ctioning // He reduced the load, Site on Gen (PWC to be replace)","TIENTCHE=
U NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e Overloaded","Site went down because PWC dysfunctioning // He reduced the =
load, Site on Gen (PWC to be replace)","kamga.virgile@ihstowers.com","1940"=
,"15-01-2025 14:01:54","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004088006","Man=
guiers Dispensaire","","15-01-2025 13:59:14","15-01-2025 13:43:01","15-01-2=
025 14:07:01","Grid bad voltage, site went down because Gen fails to start =
due to lack of 01 phase on site // he did a bridge with a good phase","Fabr=
ice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid bad voltage, site went down because Gen fails to start due=
 to lack of 01 phase on site // he did a bridge with a good phase","kamga.v=
irgile@ihstowers.com","974","15-01-2025 13:59:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004087664","M=
ontee-Des-Soeurs","","15-01-2025 13:13:51","15-01-2025 11:55:44","15-01-202=
5 12:05:28","No power Issue Site on Grid Ubai =3D54.3V,   The FME  The TX F=
ME Mbah Hosiah (674007438) is informed. ","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower Issue Site on Grid Ubai =3D54.3V,   The FME  The TX FME Mbah Hosiah (6=
74007438) is informed. ","alexandre.kamal@ihstowers.com","4688","15-01-2025=
 13:13:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004087635","M=
imboman-Ecole","","15-01-2025 13:10:28","15-01-2025 11:54:38","15-01-2025 1=
2:00:00","No power issue on site Ubaie=3D50.7 V site on Grid.  The FME TX E=
loundou Bertrant / 693212405/  From Huawei  is Informed.","Mba Lazare Herve=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site Ubaie=3D50.7 V site on Grid.  The FME =
TX Eloundou Bertrant / 693212405/  From Huawei  is Informed.","alexandre.ka=
mal@ihstowers.com","4551","15-01-2025 13:10:28","Sagemcom CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0004087626","BEA=
TITUDE ENTR=C9E PAVE","","15-01-2025 13:08:44","15-01-2025 12:20:30","15-01=
-2025 14:00:29","ACTIVE // No power issue on site ,site on Gen with Ubaie=
=3D52.6 V TX FME Mohamadou//691144435 from Huawei is informed.","TIENTCHEU =
NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Cascade Passi=
ve","ACTIVE // No power issue on site ,site on Gen with Ubaie=3D52.6 V TX F=
ME Mohamadou//691144435 from Huawei is informed.","kamga.virgile@ihstowers.=
com","359126","15-01-2025 13:08:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0004087576","Eloumdem=
 stade","","15-01-2025 12:59:10","15-01-2025 12:20:17","15-01-2025 13:25:54=
","Cascaded Incident from TTO4083143","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause gen fails to start due to grid bad voltage and no rcp on site  // Gr=
id stabilized","system","373447","15-01-2025 12:59:10","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0004087574","Sim=
bock MTN","IHS_YND_793","15-01-2025 12:58:26","15-01-2025 12:20:17","15-01-=
2025 13:26:30","Grid fluctuation, site went down because gen fails to start=
 due to grid bad voltage and no rcp on site  // Grid stabilized","Fanda Bri=
ce","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because gen fails to start due to grid =
bad voltage and no rcp on site  // Grid stabilized","kamga.virgile@ihstower=
s.com","2290","15-01-2025 12:58:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_262","NOCINC0004087567","Mendong3=
","","15-01-2025 12:57:03","15-01-2025 12:20:30","15-01-2025 14:00:29","Cas=
caded Incident from TTO4083055","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage, site went down before gen start due to=
 poor battery backup // gen manually started","system","359130","15-01-2025=
 12:57:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0004087564","Tamtam W=
eekend","","15-01-2025 12:57:02","15-01-2025 12:20:30","15-01-2025 14:00:29=
","Cascaded Incident from TTO4083055","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen manually started","system",=
"359129","15-01-2025 12:57:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_237","NOCINC0004087563","Carrefou=
r Simbock","","15-01-2025 12:57:02","15-01-2025 12:20:30","15-01-2025 14:00=
:29","Cascaded Incident from TTO4083055","Hyemafo Gildas","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
before gen start due to poor battery backup // gen manually started","syste=
m","359126","15-01-2025 12:57:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0004087566","Yona Hot=
el","","15-01-2025 12:57:02","15-01-2025 12:20:30","15-01-2025 14:00:29","C=
ascaded Incident from TTO4083055","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site went do=
wn before gen start due to poor battery backup // gen manually started","sy=
stem","359129","15-01-2025 12:57:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0004087560","Mendong =
Maeture","","15-01-2025 12:57:01","15-01-2025 12:20:30","15-01-2025 14:00:2=
9","Cascaded Incident from TTO4083055","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
fore gen start due to poor battery backup // gen manually started","system"=
,"359125","15-01-2025 12:57:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0004087561","Mfou EPC=
","","15-01-2025 12:57:01","15-01-2025 12:20:30","15-01-2025 14:00:29","Cas=
caded Incident from TTO4083055","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down before =
gen start due to poor battery backup // gen manually started","system","359=
125","15-01-2025 12:57:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_748","NOCINC0004087555","Nkoabang=
 Alembe","","15-01-2025 12:57:00","15-01-2025 12:20:30","15-01-2025 14:00:2=
9","Cascaded Incident from TTO4083055","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down =
before gen start due to poor battery backup // gen manually started","syste=
m","359127","15-01-2025 12:57:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_742","NOCINC0004087557","Mendong =
NB","","15-01-2025 12:57:00","15-01-2025 12:20:30","15-01-2025 14:00:29","C=
ascaded Incident from TTO4083055","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage, site went down before gen start due =
to poor battery backup // gen manually started","system","359126","15-01-20=
25 12:57:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_333","NOCINC0004087556","Mfou MTN=
","","15-01-2025 12:57:00","15-01-2025 12:20:30","15-01-2025 14:00:29","Cas=
caded Incident from TTO4083055","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down before =
gen start due to poor battery backup // gen manually started","system","359=
128","15-01-2025 12:57:00","Sagemcom CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0004087504","Men=
dong Plateau","IHS_YND_748, IHS_YND_333, IHS_YND_742, IHS_YND_569, IHS_YND_=
674, IHS_YND_804, IHS_YND_237, IHS_YND_151, IHS_YND_271, IHS_YND_262","15-0=
1-2025 12:47:37","15-01-2025 12:20:30","15-01-2025 14:00:29","Grid outage, =
site went down before gen start due to poor battery backup // gen manually =
started","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage, site went down before gen start due=
 to poor battery backup // gen manually started","kamga.virgile@ihstowers.c=
om","1628","15-01-2025 12:47:37","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004087467","NTU=
I TOWN","","15-01-2025 12:42:00","15-01-2025 12:08:46","15-01-2025 14:24:59=
","	Grid outage, site went down because gen ran untill fuel shortage // ref=
ueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outag=
e","	Grid outage, site went down because gen ran untill fuel shortage // re=
fueling done","kamga.virgile@ihstowers.com","1995","15-01-2025 12:42:00","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0004087420","E=
SSOS OASIS 1111","","15-01-2025 12:36:00","15-01-2025 12:31:51","15-01-2025=
 16:50:51","No power issue on site U=3D53,3v site on grid Tx Armand of huaw=
ei is informed notice that disjonction CB Ocm in BTS","Siligap Boris","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site U=3D53,3v site on grid Tx Armand of huawei is=
 informed notice that disjonction CB Ocm in BTS","alexandre.kamal@ihstowers=
.com","250","15-01-2025 12:36:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004087412","S=
OA UNIVERSITY STADIUM","","15-01-2025 12:34:44","15-01-2025 12:26:39","15-0=
1-2025 12:52:06","Grid outage,site went down because Gen start and stopped/=
/ Grid power return (investigation ongoing)","Siligap Boris","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site went dow=
n because Gen start and stopped// Grid power return (investigation ongoing)=
","alexandre.kamal@ihstowers.com","486","15-01-2025 12:34:44","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004087407","S=
AA 2","IHS_YND_726, IHS_YND_401","15-01-2025 12:34:03","15-01-2025 12:21:59=
","15-01-2025 12:31:59",":  No Power issue on site , site on Grid with Ubai=
e=3D52.7V The Tx  Gregoire(654547479) from Huawei is informed","Parker Tcho=
up","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm",":  No Power issue on site , site on Grid with Ubaie=3D52.7V=
 The Tx  Gregoire(654547479) from Huawei is informed","alexandre.kamal@ihst=
owers.com","725","15-01-2025 12:34:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004087396","N=
kolondom","","15-01-2025 12:31:39","15-01-2025 12:24:31","15-01-2025 12:59:=
16","Grid outage site went down because Gen fails  to start due to ATS dysf=
onction // Gen started manually","Fabrice Pouakam","Equipment Repair","Pass=
ive","Control Panel","ATS-AMF Issue","Grid outage site went down because Ge=
n fails  to start due to ATS dysfonction // Gen started manually","alexandr=
e.kamal@ihstowers.com","430","15-01-2025 12:31:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004087388","S=
atcom","","15-01-2025 12:30:42","15-01-2025 12:06:34","15-01-2025 12:15:34"=
,"No power issue on site, site on Grid with  Ubaie=3D50.6 V . The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site, site on Grid with  Ubaie=3D50.6 V . The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","alexandre.kamal@ihstow=
ers.com","1449","15-01-2025 12:30:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004087379","S=
tade-Abega","","15-01-2025 12:29:43","15-01-2025 12:09:33","15-01-2025 13:1=
3:20","Grid outage, site went down due dysfunctionning of PWC ZTE // Reset =
Pwc zte and gen manually starty	","Mba Lazare Herve","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Grid outage, site went do=
wn due dysfunctionning of PWC ZTE // Reset Pwc zte and gen manually starty	=
","alexandre.kamal@ihstowers.com","1211","15-01-2025 12:29:43","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0004087325","M=
vog-Ebanda","","15-01-2025 12:22:32","15-01-2025 11:59:25","15-01-2025 12:4=
8:37","	Grid outage, site went down because gen start and stopped with alar=
m ""low oil pressure""(unprouven Alarm)// He reset Gen card and Gen manuall=
y started","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","	Grid outage, site went down because gen start and stopped =
with alarm ""low oil pressure""(unprouven Alarm)// He reset Gen card and Ge=
n manually started","alexandre.kamal@ihstowers.com","1388","15-01-2025 12:2=
2:32","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004087216","Ema=
na","","15-01-2025 12:04:26","15-01-2025 11:56:08","15-01-2025 12:04:59","G=
rid outage, Site went down before Gen start due to poor backup// Gen starte=
d manually","Fabrice Pouakam","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup// Gen started manually","kamga.virgile@ihstowers.com","=
499","15-01-2025 12:04:26","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0004087202","ETO=
UDI Entree du palais","","15-01-2025 12:02:02","15-01-2025 11:56:43","15-01=
-2025 12:50:57","Grid outage, site went down because gen start and stopped =
with emergency stop (unprouven) alarm // reset of gen card done and gen sta=
rted","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","Grid outage, site went down because gen start and stopped with=
 emergency stop (unprouven) alarm // reset of gen card done and gen started=
","kamga.virgile@ihstowers.com","321","15-01-2025 12:02:02","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004086841","Ako=
k Ndoe Yde","","15-01-2025 11:37:19","15-01-2025 10:58:01","15-01-2025 12:2=
6:08","Grid outage, Site went down before Gen start due to poor backup// Ge=
n manually started manually","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup// Gen manually started manually","kamga=
.virgile@ihstowers.com","2359","15-01-2025 11:37:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004085981","E=
kounou","","15-01-2025 09:23:36","15-01-2025 09:11:30","15-01-2025 11:31:28=
","site went down because CB 125A who feeds equipment OCm faulty in PWC//he=
 did a bridge with another  Cb 80A (need to change the faulty CB)","Albran =
Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet - Circu=
it Breaker Issue","site went down because CB 125A who feeds equipment OCm f=
aulty in PWC//he did a bridge with another  Cb 80A (need to change the faul=
ty CB)","alexandre.kamal@ihstowers.com","728","15-01-2025 09:23:36","Sagemc=
om CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004085349","Mel=
en Ba'aba","","15-01-2025 07:55:09","15-01-2025 07:48:54","15-01-2025 07:49=
:27","Active//No power issue site on Grid with U=3D54,4V Symphorien(6913168=
54) from Huawei is informed","Siligap Boris","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue site on Grid with U=3D54,4V Symphorien(691316854) from Huawei is infor=
med","kamga.virgile@ihstowers.com","377","15-01-2025 07:55:09","Sagemcom CM=
R"
"Closed Complete","Site Down","T2149","IHS_EDA_056","NOCINC0004085027","Ndo=
gbessol","","15-01-2025 06:39:45","15-01-2025 05:57:31","15-01-2025 06:57:3=
1","Active//No power issue on site U=3D52v site on battery Tx fme Etienne 6=
95033981 of huawei is informed AND Notice that the E-1 Ocm come from Ndobes=
sol MTN","Kemeni Franklin","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active//No power issue on site U=3D5=
2v site on battery Tx fme Etienne 695033981 of huawei is informed AND Notic=
e that the E-1 Ocm come from Ndobessol MTN","kamga.virgile@ihstowers.com","=
2535","15-01-2025 06:39:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0004084815","Eseka To=
wn","","15-01-2025 05:38:55","15-01-2025 05:32:12","15-01-2025 05:56:04","C=
ascaded Incident from TTO4079980","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start du=
e to alarm ""Underfrequency""//We rest card GE and gen manually started ","=
system","268234","15-01-2025 05:38:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0004084812","Eseka MT=
N","","15-01-2025 05:38:54","15-01-2025 05:32:12","15-01-2025 05:56:04","Ca=
scaded Incident from TTO4079980","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen failed to start due=
 to alarm ""Underfrequency""//We rest card GE and gen manually started ","s=
ystem","268228","15-01-2025 05:38:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0004084804","Ndogbess=
ol","","15-01-2025 05:38:53","15-01-2025 05:32:12","15-01-2025 05:56:04","C=
ascaded Incident from TTO4079980","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start du=
e to alarm ""Underfrequency""//We rest card GE and gen manually started ","=
system","268238","15-01-2025 05:38:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0004084800","Boumnyeb=
el","","15-01-2025 05:38:52","15-01-2025 05:32:12","15-01-2025 05:56:04","C=
ascaded Incident from TTO4079980","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start du=
e to alarm ""Underfrequency""//We rest card GE and gen manually started ","=
system","268237","15-01-2025 05:38:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0004084797","Ngoung",=
"","15-01-2025 05:38:51","15-01-2025 05:32:12","15-01-2025 05:56:04","Casca=
ded Incident from TTO4079980","Kemeni Franklin","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage.gen failed to start due to=
 alarm ""Underfrequency""//We rest card GE and gen manually started ","syst=
em","268231","15-01-2025 05:38:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_781","NOCINC0004084793","BIBOMDJI=
DJIEL","","15-01-2025 05:38:50","15-01-2025 05:32:12","15-01-2025 05:56:04"=
,"Cascaded Incident from TTO4079980","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage.gen failed to start=
 due to alarm ""Underfrequency""//We rest card GE and gen manually started =
","system","268232","15-01-2025 05:38:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_416","NOCINC0004084794","Ngwopi B=
oga","","15-01-2025 05:38:50","15-01-2025 05:32:12","15-01-2025 05:56:04","=
Cascaded Incident from TTO4079980","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage.gen failed to start d=
ue to alarm ""Underfrequency""//We rest card GE and gen manually started ",=
"system","268236","15-01-2025 05:38:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0004084795","Mamb",""=
,"15-01-2025 05:38:50","15-01-2025 05:32:12","15-01-2025 05:56:04","Cascade=
d Incident from TTO4079980","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage.gen failed to start due to a=
larm ""Underfrequency""//We rest card GE and gen manually started ","system=
","268230","15-01-2025 05:38:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0004084290","M=
fou EPC","","15-01-2025 02:33:36","15-01-2025 02:31:26","15-01-2025 04:00:1=
4","Grid outage,Site went down because Gen stopped with alarm ""high temp""=
causing by radiator pierced// He repaired radiator, added water and started=
 Gen manualy","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - High Engine Temp - Radiator Leakage","Grid outage,Site went down beca=
use Gen stopped with alarm ""high temp""causing by radiator pierced// He re=
paired radiator, added water and started Gen manualy","christian.fonkou@ihs=
towers.com","131","15-01-2025 02:33:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004084028","N=
gouetou","","15-01-2025 00:47:44","15-01-2025 00:40:38","15-01-2025 00:55:3=
8","No power issue on site, site on Gen The Tx FME Gregoire/654547479 from =
huawei is informed","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, sit=
e on Gen The Tx FME Gregoire/654547479 from huawei is informed","christian.=
fonkou@ihstowers.com","428","15-01-2025 00:47:44","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004083815","Ema=
na","","14-01-2025 23:44:43","14-01-2025 23:40:36","14-01-2025 23:52:15","	=
Grid outage, site went down before gen start due to poor battery backup // =
Grid return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","	Grid outage, site went down before gen sta=
rt due to poor battery backup // Grid return","emmanuel.ghani@ihstowers.com=
","248","14-01-2025 23:44:43","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004083747","NKO=
LMEKONG YDE","","14-01-2025 23:17:21","14-01-2025 23:16:13","14-01-2025 23:=
18:23","Grid outage, site went down before gen start due to poor battery ba=
ckup // Grid return","Fabrice Pouakam","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
gen start due to poor battery backup // Grid return","emmanuel.ghani@ihstow=
ers.com","69","14-01-2025 23:17:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004083743","L=
abogenie","","14-01-2025 23:16:11","14-01-2025 23:11:07","14-01-2025 23:15:=
23","Active//No power issue on site Ubaie=3D54.5V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site Ubaie=3D54.5V site on Grid The Tx Fme Eloundou/693212405 of hua=
wei is informed","christian.fonkou@ihstowers.com","305","14-01-2025 23:16:1=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004082827","M=
imboman-Village","IHS_YND_709","14-01-2025 20:45:45","14-01-2025 20:34:59",=
"14-01-2025 23:09:11","Grid outage, Site went down because Gen failed to st=
art due to PWC ZTE dysfunctionning// He reset PWC, Site on Grid","Mba Lazar=
e Herve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Grid outage, Site went down because Gen failed to start due to PWC ZT=
E dysfunctionning// He reset PWC, Site on Grid","rouselle.schoune@ihstowers=
.com","647","14-01-2025 20:45:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004082648","M=
efou-Assi","","14-01-2025 20:28:31","14-01-2025 20:20:01","14-01-2025 21:03=
:24","site went down because gen failed to start due to grid bad voltage //=
 Grid stabilized","Fanda Brice","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","site went down because gen failed to start d=
ue to grid bad voltage // Grid stabilized","rouselle.schoune@ihstowers.com"=
,"511","14-01-2025 20:28:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004082615","N=
kolo II New","","14-01-2025 20:21:07","14-01-2025 20:34:59","14-01-2025 23:=
09:11","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, Site went down because Gen failed to start d=
ue to PWC ZTE dysfunctionning// He reset PWC, Site on Grid","rouselle.schou=
ne@ihstowers.com","271752","14-01-2025 20:21:07","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004082310","Mel=
en Ba'aba","","14-01-2025 19:24:54","14-01-2025 19:18:47","15-01-2025 02:05=
:46","No power issue site on Gen with U=3D53,4V Symphorien(691316854) from =
Huawei is informed","Siligap Boris","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on Gen =
with U=3D53,4V Symphorien(691316854) from Huawei is informed","ange.kongo@i=
hstowers.com","368","14-01-2025 19:24:54","Sagemcom CMR"
"Closed Complete","Warning","T0105","IHS_YND_321","NOCINC0004082118","Soa",=
"","14-01-2025 18:57:19","","","Site alarming because site on battery due t=
o Grid outage,and  gen ran untill fuel shortage // refueling done","Siligap=
 Boris","Warning","Warning","POWER","Warning - Site on Battery","Site alarm=
ing because site on battery due to Grid outage,and  gen ran untill fuel sho=
rtage // refueling done","adonis.defokoua@ihstowers.com","430","14-01-2025 =
18:57:19","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004081983","NKO=
MEKUI OCM","","14-01-2025 18:50:59","14-01-2025 18:45:43","14-01-2025 19:18=
:22","ACTIVE//No power issue on site U=3D54,5v site on gen site down becaus=
e is impacted by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCH=
IEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","ACTIVE//No power issue on site U=3D54,5v site on gen =
site down because is impacted by Mbankolo Camtel and not managing by IHS","=
ange.kongo@ihstowers.com","317","14-01-2025 18:50:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004081100","S=
OA UNIVERSITY STADIUM","","14-01-2025 18:20:13","14-01-2025 18:18:08","14-0=
1-2025 19:37:49","grid outage, site went down because gen failed to start /=
/ Grid return(investigation ongoing)","Siligap Boris","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","grid outage, site went down beca=
use gen failed to start // Grid return(investigation ongoing)","rouselle.sc=
houne@ihstowers.com","126","14-01-2025 18:20:13","Sagemcom CMR"
"Closed Complete","Warning","T2502","IHS_YND_781","NOCINC0004080379","BIBOM=
DJIDJIEL","","14-01-2025 17:47:27","","","Site alarming because site on bat=
tery due to Our Technician Franklin//690854375/SAGEMCOM working on site (PM=
)// End of work","Kemeni Franklin","Warning","Warning","POWER","Warning - S=
ite on Battery","Site alarming because site on battery due to Our Technicia=
n Franklin//690854375/SAGEMCOM working on site (PM)// End of work","adonis.=
defokoua@ihstowers.com","486","14-01-2025 17:47:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004080335","M=
efou-Assi","IHS_YND_696","14-01-2025 17:42:29","14-01-2025 17:41:25","14-01=
-2025 17:44:24","Grid outage, site went down because gen start and stopped =
with high temp alarm // he added water and manually start the gen","Fanda B=
rice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Co=
olant Level Issue","Grid outage, site went down because gen start and stopp=
ed with high temp alarm // he added water and manually start the gen","rous=
elle.schoune@ihstowers.com","65","14-01-2025 17:42:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0004080253","B=
arriere IHS","","14-01-2025 17:31:12","14-01-2025 17:41:25","14-01-2025 17:=
44:24","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, site went down because gen start and stopped w=
ith high temp alarm // he added water and manually start the gen","rouselle=
.schoune@ihstowers.com","260598","14-01-2025 17:31:12","Sagemcom CMR"
"Closed Complete","Warning","T0843","IHS_YND_719","NOCINC0004079928","TSING=
A VILLAGE 2","","14-01-2025 16:41:52","","","Site alarming because site on =
battery due to SS IHS Berard Atagana  is working on site //End of work","De=
lor Telezing","Warning","Warning","POWER","Warning - Site on Battery","Site=
 alarming because site on battery due to SS IHS Berard Atagana  is working =
on site //End of work","adonis.defokoua@ihstowers.com","431","14-01-2025 16=
:41:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004079682","S=
aa","","14-01-2025 16:14:34","14-01-2025 16:12:29","14-01-2025 17:20:54","A=
ctive//No power issue U=3D 54.3V site on Grid The TX FME Gregoire(654547479=
) from Huawei is informed.","Parker Tchoup","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue U=3D 54.3V site on Grid The TX FME Gregoire(654547479) from Huawei is i=
nformed.","rouselle.schoune@ihstowers.com","126","14-01-2025 16:14:34","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004079568","L=
abogenie","","14-01-2025 15:59:23","14-01-2025 15:56:18","14-01-2025 16:00:=
40","No power issue U =3D54,6V site on grid. The Tx FME Eloundou Bertrand (=
693212405)from Huawei is informed. Repetitive issue","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue U =3D54,6V site on grid. The Tx FME Eloundou Bertrand (693212405)fr=
om Huawei is informed. Repetitive issue","rouselle.schoune@ihstowers.com","=
186","14-01-2025 15:59:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0004079525","O=
lembe-Terminus","","14-01-2025 15:53:21","14-01-2025 15:51:16","14-01-2025 =
16:07:04","site went down because Gen failed to start due to lack of 1 phas=
e on site // he did a bridge with a good phase ","Fabrice Pouakam","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","site went=
 down because Gen failed to start due to lack of 1 phase on site // he did =
a bridge with a good phase ","rouselle.schoune@ihstowers.com","127","14-01-=
2025 15:53:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004079088","E=
ssomba","","14-01-2025 14:48:01","14-01-2025 14:13:56","14-01-2025 15:52:58=
","site went down due to disfunctionning of 02/05 rectifiers // He reset re=
ctifiers, site on grid","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Incorrectly Logged Tickets","rouselle.schoune@=
ihstowers.com","2047","14-01-2025 14:48:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004078995","C=
rf-Nsam","","14-01-2025 14:34:24","14-01-2025 14:07:15","14-01-2025 14:08:1=
7","Incorrectly logged Tickets","MINKA NICOLAS","Incorrectly Logged Tickets=
","Error","Error","Error","Incorrectly logged Tickets","rouselle.schoune@ih=
stowers.com","1631","14-01-2025 14:34:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0004078627","L=
abogenie","","14-01-2025 13:50:46","14-01-2025 13:03:40","14-01-2025 14:09:=
46","No power issue U =3D54,6V site on grid. The Tx FME Eloundou Bertrand (=
693212405)from Huawei is informed. Repetitive issue","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue U =3D54,6V site on grid. The Tx FME Eloundou Bertrand (693212405)fr=
om Huawei is informed. Repetitive issue","olivier.kwedi@ihstowers.com","282=
7","14-01-2025 13:50:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0004078613","H=
-Progres","","14-01-2025 13:48:29","14-01-2025 13:43:15","14-01-2025 13:48:=
30","ACTIVE//No power issue on site U=3D48,7v site on gen Tx fme MOHAMMADOU=
(691144435) of huawei is informed ","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue o=
n site U=3D48,7v site on gen Tx fme MOHAMMADOU(691144435) of huawei is info=
rmed ","olivier.kwedi@ihstowers.com","315","14-01-2025 13:48:29","Sagemcom =
CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004078053","Men=
dong vallee","","14-01-2025 12:45:19","14-01-2025 12:40:28","14-01-2025 13:=
16:10","grid outae, site went down because gen failed to start  due to Gen =
overload (20KVA, 320A) (Felix Zambo IHS confirm) // Grid return","Fanda Bri=
ce","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","grid outae, =
site went down because gen failed to start  due to Gen overload (20KVA, 320=
A) (Felix Zambo IHS confirm) // Grid return","ludivine.ngamaleu@ihstowers.c=
om","1808","14-01-2025 12:45:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004077777","SAA 2","=
","14-01-2025 12:03:42","14-01-2025 11:52:19","14-01-2025 12:10:17","Cascad=
ed Incident from TTO4071913","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid Outage, Site went down because Gen r=
an until fuel shortage// Refueling Done","system","274152","14-01-2025 12:0=
3:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004077768","S=
aa","IHS_YND_401, IHS_YND_404","14-01-2025 12:01:46","14-01-2025 11:52:19",=
"14-01-2025 12:10:17","Grid Outage, Site went down because Gen ran until fu=
el shortage// Refueling Done","Parker Tchoup","Fuel Outage","Passive","Dies=
el","Diesel Outage","Grid Outage, Site went down because Gen ran until fuel=
 shortage// Refueling Done","olivier.kwedi@ihstowers.com","568","14-01-2025=
 12:01:46","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_319","NOCINC0004077661","SOA 2","",=
"14-01-2025 11:44:11","","","","Siligap Boris","Warning","Warning","POWER",=
"Warning - AC Phase 1 Current Low","Alarn cleared","joelle.ekessi@ihstowers=
.com","4","14-01-2025 11:44:11","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0004077646","Av =
Kennedy","","14-01-2025 11:41:49","14-01-2025 11:33:41","14-01-2025 13:46:4=
5","Active // no power issue on site U=3D54V symphorien/650257151/ From hua=
wei is working on site","","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active // no power issue on site U=
=3D54V symphorien/650257151/ From huawei is working on site","ludivine.ngam=
aleu@ihstowers.com","489","14-01-2025 11:41:49","Sagemcom CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004077515","Nko=
l-Mebanga","","14-01-2025 11:17:43","14-01-2025 11:09:36","14-01-2025 13:59=
:47","No power issue on site, site on Gen The Tx FME Gregoire/654547479 fro=
m huawei is informed","Parker Tchoup","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, s=
ite on Gen The Tx FME Gregoire/654547479 from huawei is informed","ludivine=
.ngamaleu@ihstowers.com","488","14-01-2025 11:17:43","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004077003","SOA=
 UNIVERSITY STADIUM","","14-01-2025 10:01:27","14-01-2025 09:52:56","14-01-=
2025 10:31:01","Grid outage, site went down because gen fails to start due =
to ATS disfunctionning // gen manually started","Siligap Boris","Equipment =
Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went d=
own because gen fails to start due to ATS disfunctionning // gen manually s=
tarted","ludivine.ngamaleu@ihstowers.com","512","14-01-2025 10:01:27","Sage=
mcom CMR"
"Closed Complete","Warning","","IHS_YND_302","NOCINC0004076887","Nkolndom",=
"","14-01-2025 09:40:15","","","site on alarm due to grid outage//gen start=
ed","Fabrice Pouakam","Warning","Warning","POWER","Warning - Site on Batter=
y","site on alarm due to grid outage//gen started","joelle.ekessi@ihstowers=
.com","3","14-01-2025 09:40:15","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0004076519","NKO=
LOSSAN OKOK","","14-01-2025 08:39:29","14-01-2025 08:36:23","14-01-2025 10:=
42:23","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","ludivine.ngamaleu@ihstowers.com","187","14-01-2025 08:39:=
29","Sagemcom CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0004076337","Dra=
gage","IHS_YND_208","14-01-2025 08:08:48","14-01-2025 08:01:15","14-01-2025=
 09:09:15","Site went down due to insufficiency of rectifiers(3) SS IHS Ber=
nard Atangana confirmed // He  reduiced the load: site on grid","Mboua Thie=
rry","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went=
 down due to insufficiency of rectifiers(3) SS IHS Bernard Atangana confirm=
ed // He  reduiced the load: site on grid","ludivine.ngamaleu@ihstowers.com=
","554","14-01-2025 08:08:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0004076331","A=
RMP","","14-01-2025 08:07:35","14-01-2025 08:01:15","14-01-2025 09:09:15","=
","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Site w=
ent down due to insufficiency of rectifiers(3) SS IHS Bernard Atangana conf=
irmed // He  reduiced the load: site on grid","olivier.kwedi@ihstowers.com"=
,"266647","14-01-2025 08:07:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004075995","N=
gouetou","","14-01-2025 07:32:13","14-01-2025 07:27:57","14-01-2025 09:24:3=
5","No power issue on site, site on Gen The Tx FME Gregoire/654547479 from =
huawei is informed","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, sit=
e on Gen The Tx FME Gregoire/654547479 from huawei is informed","olivier.kw=
edi@ihstowers.com","258","14-01-2025 07:32:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004075831","Yoko MTN=
","","14-01-2025 06:50:21","14-01-2025 06:48:21","14-01-2025 06:49:21","Cas=
caded Incident from TTO4069707","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active: No power issue, site on Battery  =
With Ubaie=3D53,9V,  Gregoire (654547479) from Huawei is informed","system"=
,"263679","14-01-2025 06:50:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004075830","Ngoum","=
","14-01-2025 06:50:21","14-01-2025 06:48:21","14-01-2025 06:49:21","Cascad=
ed Incident from TTO4069707","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active: No power issue, site on Battery  Wit=
h Ubaie=3D53,9V,  Gregoire (654547479) from Huawei is informed","system","2=
63679","14-01-2025 06:50:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004075829","Matsari"=
,"","14-01-2025 06:50:20","14-01-2025 06:48:21","14-01-2025 06:49:21","Casc=
aded Incident from TTO4069707","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active: No power issue, site on Battery  W=
ith Ubaie=3D53,9V,  Gregoire (654547479) from Huawei is informed","system",=
"263680","14-01-2025 06:50:20","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004075826","MBI=
MBIM","IHS_YND_460, IHS_YND_475, IHS_YND_473","14-01-2025 06:49:26","14-01-=
2025 06:48:21","14-01-2025 07:30:38","Active: No power issue, site on Batte=
ry  With Ubaie=3D53,9V,  Gregoire (654547479) from Huawei is informed","Par=
ker Tchoup","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active: No power issue, site on Battery  With Ubaie=
=3D53,9V,  Gregoire (654547479) from Huawei is informed","ludivine.ngamaleu=
@ihstowers.com","67","14-01-2025 06:49:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004075651","N=
gouetou","","14-01-2025 06:06:06","14-01-2025 05:49:52","14-01-2025 07:20:1=
2","Active//No power issue on site with  Ubaie=3D52.4V site on Gen .The Tx =
Fme Gregoire and Up at 07:15 AM","Parker Tchoup","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue on site with  Ubaie=3D52.4V site on Gen .The Tx Fme Gregoire and U=
p at 07:15 AM","kouoh.jean@ihstowers.com","975","14-01-2025 06:06:06","Sage=
mcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0004075291","TSI=
NGA VILLAGE 2","","14-01-2025 04:10:45","14-01-2025 04:05:37","14-01-2025 0=
4:50:53","Grid outage site went down because Gen started and stopped with a=
larm ""undervoltage""// He reset Gen card and started Gen manualy","Delor T=
elezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage site went down because Gen started and stopped with alarm ""under=
voltage""// He reset Gen card and started Gen manualy","stephane.nkamwa@ihs=
towers.com","309","14-01-2025 04:10:45","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004074705","Nko=
g-Edzen","","14-01-2025 00:57:41","14-01-2025 00:55:29","14-01-2025 02:15:1=
2","No power issue on site with  Ubaie=3D52.4V site on Gen .The Tx Fme Greg=
oire From HUAWEI is informed and Up at 12:57 AM","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site with  Ubaie=3D52.4V site on Gen .The Tx Fme Gregoi=
re From HUAWEI is informed and Up at 12:57 AM","stephane.nkamwa@ihstowers.c=
om","132","14-01-2025 00:57:41","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004074111","NKO=
LMEKONG YDE","","13-01-2025 22:55:20","13-01-2025 22:43:16","13-01-2025 22:=
48:39","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen automatically started","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down before gen start due to poor battery backup // Gen automatically sta=
rted","stephane.nkamwa@ihstowers.com","725","13-01-2025 22:55:20","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0004073621","SOA TOWN=
","","13-01-2025 21:41:33","13-01-2025 21:24:48","13-01-2025 21:49:41","Cas=
caded Incident from TTO4067059","Siligap Boris","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 stopped with alarm High temps // He added water and Gen manually started",=
"system","268732","13-01-2025 21:41:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_322","NOCINC0004073620","Soa-II",=
"","13-01-2025 21:41:33","13-01-2025 21:24:48","13-01-2025 21:49:41","Casca=
ded Incident from TTO4067059","Siligap Boris","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage site went down because Gen s=
topped with alarm High temps // He added water and Gen manually started","s=
ystem","268735","13-01-2025 21:41:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004073615","Akak-Nko=
zoa-MTN-IHS","","13-01-2025 21:41:32","13-01-2025 21:24:48","13-01-2025 21:=
49:41","Cascaded Incident from TTO4067059","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site went dow=
n because Gen stopped with alarm High temps // He added water and Gen manua=
lly started","system","268734","13-01-2025 21:41:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0004073617","SOA UNIV=
ERSITY STADIUM","","13-01-2025 21:41:32","13-01-2025 21:24:48","13-01-2025 =
21:49:41","Cascaded Incident from TTO4067059","Siligap Boris","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage site went do=
wn because Gen stopped with alarm High temps // He added water and Gen manu=
ally started","system","268734","13-01-2025 21:41:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_317","NOCINC0004073611","Soa-Sofa=
mac","","13-01-2025 21:41:31","13-01-2025 21:24:48","13-01-2025 21:49:41","=
Cascaded Incident from TTO4067059","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen stopped with alarm High temps // He added water and Gen manually starte=
d","system","268736","13-01-2025 21:41:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0004073614","Ebogo","=
","13-01-2025 21:41:31","13-01-2025 21:24:48","13-01-2025 21:49:41","Cascad=
ed Incident from TTO4067059","Siligap Boris","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down because Gen st=
opped with alarm High temps // He added water and Gen manually started","sy=
stem","268731","13-01-2025 21:41:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_321","NOCINC0004073610","Soa","",=
"13-01-2025 21:41:31","13-01-2025 21:24:48","13-01-2025 21:49:41","Cascaded=
 Incident from TTO4067059","Siligap Boris","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage site went down because Gen stop=
ped with alarm High temps // He added water and Gen manually started","syst=
em","268732","13-01-2025 21:41:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0004073609","NYOM 2 I=
HS","","13-01-2025 21:41:30","13-01-2025 21:24:48","13-01-2025 21:49:41","C=
ascaded Incident from TTO4067059","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen stopped with alarm High temps // He added water and Gen manually start=
ed","system","268734","13-01-2025 21:41:30","Sagemcom CMR"
"Closed Complete","Site Down","T0712","IHS_YND_319","NOCINC0004073554","SOA=
 2","IHS_YND_703, IHS_YND_707, IHS_YND_321, IHS_YND_317, IHS_YND_390, IHS_Y=
ND_552, IHS_YND_307, IHS_YND_316, IHS_YND_351, IHS_YND_720, IHS_YND_326, IH=
S_YND_324, IHS_YND_322, IHS_YND_320","13-01-2025 21:31:54","13-01-2025 21:2=
4:48","13-01-2025 21:49:41","Grid outage site went down because Gen stopped=
 with alarm High temps // He added water and Gen manually started","Siligap=
 Boris","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - =
Coolant Level Issue","Grid outage site went down because Gen stopped with a=
larm High temps // He added water and Gen manually started","emmanuel.ghani=
@ihstowers.com","531","13-01-2025 21:31:54","Sagemcom CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0004073308","Sim=
bock Maetur","","13-01-2025 20:53:46","13-01-2025 20:43:40","13-01-2025 21:=
09:24","Grid fluctuation, gen start and stopped due to grid bad voltage// h=
e bypass grid and  gen manually started","Hyemafo Gildas","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, =
gen start and stopped due to grid bad voltage// he bypass grid and  gen man=
ually started","emmanuel.ghani@ihstowers.com","606","13-01-2025 20:53:46","=
Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004073273","Ema=
na","","13-01-2025 20:48:36","13-01-2025 20:42:31","13-01-2025 20:53:50","G=
rid outage, site went down before gen start due to poor batteries backup //=
 gen start automatically","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor batteries backup // gen start automatically","em=
manuel.ghani@ihstowers.com","366","13-01-2025 20:48:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004073264","S=
calom","","13-01-2025 20:46:16","13-01-2025 20:44:11","13-01-2025 20:45:41"=
,"No power issue , Ubaie=3D54.2 V site on Grid. The FME TX Mbah Hosiah //67=
4007438// from huawei is informed ","Paul BIBOUM","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e , Ubaie=3D54.2 V site on Grid. The FME TX Mbah Hosiah //674007438// from =
huawei is informed ","christian.fonkou@ihstowers.com","125","13-01-2025 20:=
46:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_299","NOCINC0004072622","Olembe M=
TN","","13-01-2025 19:31:31","13-01-2025 19:14:13","13-01-2025 19:53:20","C=
ascaded Incident from TTO4065950","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start du=
e to automation malfunction causing by  starter order cable disconnected //=
Grid return","system","269211","13-01-2025 19:31:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0004072621","NKOLMEKO=
NG YDE","","13-01-2025 19:31:31","13-01-2025 19:14:13","13-01-2025 19:53:20=
","Cascaded Incident from TTO4065950","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage.gen failed to star=
t due to automation malfunction causing by  starter order cable disconnecte=
d //Grid return","system","269212","13-01-2025 19:31:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004072620","Emana Ly=
cee","","13-01-2025 19:31:30","13-01-2025 19:14:13","13-01-2025 19:53:20","=
Cascaded Incident from TTO4065950","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage.gen failed to start d=
ue to automation malfunction causing by  starter order cable disconnected /=
/Grid return","system","269210","13-01-2025 19:31:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_761","NOCINC0004072619","Djonassi=
-Yde","","13-01-2025 19:31:30","13-01-2025 19:14:13","13-01-2025 19:53:20",=
"Cascaded Incident from TTO4065950","Fabrice Pouakam","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage.gen failed to start =
due to automation malfunction causing by  starter order cable disconnected =
//Grid return","system","269209","13-01-2025 19:31:30","Sagemcom CMR"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0004072599","Nko=
lndom","IHS_YND_761, IHS_YND_274, IHS_YND_681, IHS_YND_220, IHS_YND_299, IH=
S_YND_279","13-01-2025 19:27:21","13-01-2025 19:14:13","13-01-2025 19:53:20=
","Grid outage.gen failed to start due to automation malfunction causing by=
  starter order cable disconnected //Grid return","Fabrice Pouakam","Equipm=
ent Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage.gen fail=
ed to start due to automation malfunction causing by  starter order cable d=
isconnected //Grid return","emmanuel.ghani@ihstowers.com","789","13-01-2025=
 19:27:21","Sagemcom CMR"
"Closed Complete","Site Down","T0417-1","IHS_YND_220","NOCINC0004072543","G=
olf Quater","","13-01-2025 19:15:42","13-01-2025 19:14:13","13-01-2025 19:5=
3:20","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage.gen failed to start due to automation malfunction=
 causing by  starter order cable disconnected //Grid return","emmanuel.ghan=
i@ihstowers.com","269211","13-01-2025 19:15:42","Sagemcom CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0004072537","Mes=
sassi okolo","","13-01-2025 19:14:17","13-01-2025 19:14:13","13-01-2025 19:=
53:20","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid outage.gen failed to start due to automation malfunct=
ion causing by  starter order cable disconnected //Grid return","emmanuel.g=
hani@ihstowers.com","269210","13-01-2025 19:14:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004072518","B=
iteng-Maetur","","13-01-2025 19:09:10","13-01-2025 18:51:48","13-01-2025 20=
:01:48","Grid outage.site went down due to gen overload (20kva,270 A)//We r=
educe load and gen manually started ","Mba Lazare Herve","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage.site went down due to =
gen overload (20kva,270 A)//We reduce load and gen manually started ","chri=
stian.fonkou@ihstowers.com","1044","13-01-2025 19:09:10","Sagemcom CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0004072337","SOA=
 VILLAGE","","13-01-2025 18:29:38","13-01-2025 18:26:29","13-01-2025 18:54:=
44","Grid outage.gen failed to start and stoppe due to alarm""low oil press=
ure'// We add oil and gen manually started ","Siligap Boris","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage.gen failed=
 to start and stoppe due to alarm""low oil pressure'// We add oil and gen m=
anually started ","emmanuel.ghani@ihstowers.com","190","13-01-2025 18:29:38=
","Sagemcom CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0004072054","Emo=
mbo Esssomba","","13-01-2025 17:50:15","13-01-2025 17:43:10","13-01-2025 18=
:44:41","Grid outage.gen failed to start due to battery GE discharged causi=
ng by static charger faulty//Grid return ","Mba Lazare Herve","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage.gen fail=
ed to start due to battery GE discharged causing by static charger faulty//=
Grid return ","emmanuel.ghani@ihstowers.com","425","13-01-2025 17:50:15","S=
agemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004071940","Nko=
lbong","","13-01-2025 17:27:53","13-01-2025 17:21:48","13-01-2025 18:14:54"=
,"Grid outage, Site went down because Gen failed to start due to Gen card d=
ysfunctionning // He rest card GE and  started Gen manualy","Delor Telezing=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge, Site went down because Gen failed to start due to Gen card dysfunctionn=
ing // He rest card GE and  started Gen manualy","emmanuel.ghani@ihstowers.=
com","558","13-01-2025 17:27:53","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004071931","SOA=
 UNIVERSITY STADIUM","","13-01-2025 17:26:45","13-01-2025 17:20:40","13-01-=
2025 19:07:55","Site went down due to work:  by Supervisor  IHS Bernard Ata=
ngana is  working on site // End of work","Siligap Boris","Installation Act=
ivity","Passive","Planned Activity","Installation Activity","Site went down=
 due to work:  by Supervisor  IHS Bernard Atangana is  working on site // E=
nd of work","emmanuel.ghani@ihstowers.com","366","13-01-2025 17:26:45","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0004071914","B=
ATA-Mokolo","","13-01-2025 17:23:52","13-01-2025 17:17:45","14-01-2025 09:3=
4:00","Grid outage.No space to deploy mobile gen .// Grid Restored","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.No space to deploy mobile gen .// Grid Restored","christian.fonkou@ihstowe=
rs.com","368","13-01-2025 17:23:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0004071805","S=
oa-Sofamac","","13-01-2025 17:09:55","13-01-2025 17:03:45","13-01-2025 17:3=
5:51","Grid outage.gen failed to start due to card GE dysfunctionning// We =
reset card GE and gen manually started ","Siligap Boris","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to sta=
rt due to card GE dysfunctionning// We reset card GE and gen manually start=
ed ","christian.fonkou@ihstowers.com","371","13-01-2025 17:09:55","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0004071291","H=
-Progres","","13-01-2025 16:22:24","13-01-2025 16:19:17","14-01-2025 09:33:=
58","Grid outage.No space to deploy mobile gen .// Grid Restored","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.N=
o space to deploy mobile gen .// Grid Restored","christian.fonkou@ihstowers=
.com","188","13-01-2025 16:22:24","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004071229","BAT=
A Mokolo OCM","","13-01-2025 16:12:48","13-01-2025 16:06:43","14-01-2025 09=
:40:32","Grid outage.no space to deploy mobile Gen.//Grid Restored","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.no space to deploy mobile Gen.//Grid Restored","emmanuel.ghani@ihstowers.c=
om","366","13-01-2025 16:12:48","Sagemcom CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0004071215","Sim=
bock Maetur","","13-01-2025 16:09:15","13-01-2025 16:02:10","13-01-2025 18:=
24:34","Grid outage.gen failed to start due to battery GE faulty //Gen manu=
ally started with external battery","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Generator Battery","Grid outage.gen failed to sta=
rt due to battery GE faulty //Gen manually started with external battery","=
emmanuel.ghani@ihstowers.com","426","13-01-2025 16:09:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0004071193","B=
itoto","","13-01-2025 16:06:20","13-01-2025 16:01:12","13-01-2025 17:26:50"=
,"Gen only site, site went down because gen ran until fuel shortage // refu=
eling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Out=
age","Gen only site, site went down because gen ran until fuel shortage // =
refueling done","christian.fonkou@ihstowers.com","309","13-01-2025 16:06:20=
","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004071132","Nko=
abang MTN","","13-01-2025 15:59:23","13-01-2025 15:53:18","13-01-2025 16:27=
:34","Grid outage. site went down due to Gen overload(20Kva,230A)//We reduc=
e load and gen manually started ","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload","Gid outage.site went down due to Gen o=
verload(20Kva,230A)//We reduce load and gen manually started ","emmanuel.gh=
ani@ihstowers.com","366","13-01-2025 15:59:23","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004071084","Nko=
ulou Carriere carrefourt","","13-01-2025 15:53:48","13-01-2025 15:22:22","1=
3-01-2025 16:20:39","Grid outage, Site went down Gen failed to start due to=
  no charging alternator, no Gen battery  // Grid return","Mba Lazare Herve=
","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator","Gri=
d outage, Site went down Gen failed to start due to  no charging alternator=
, no Gen battery  // Grid return","emmanuel.ghani@ihstowers.com","1887","13=
-01-2025 15:53:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004070895","C=
rf-Nsam","","13-01-2025 15:26:31","13-01-2025 15:21:24","13-01-2025 16:33:1=
4","Site went down Because The Slot off Rectifier is overload // he reduced=
 the load and Gen manually started","MINKA NICOLAS","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Site went down Because The=
 Slot off Rectifier is overload // he reduced the load and Gen manually sta=
rted","christian.fonkou@ihstowers.com","308","13-01-2025 15:26:31","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004070753","S=
atcom","","13-01-2025 15:22:10","13-01-2025 15:14:02","13-01-2025 20:28:24"=
,"No power issue on site, site on Gen with U=3D54v .The Tx Fme Armand nguet=
sa(691144412) From huawei is informed.","Delor Telezing","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site, site on Gen with U=3D54v .The Tx Fme Armand nguetsa(69114=
4412) From huawei is informed.","christian.fonkou@ihstowers.com","489","13-=
01-2025 15:22:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004070553","M=
endong vallee","","13-01-2025 14:49:25","13-01-2025 14:44:20","13-01-2025 1=
6:45:27"," Grid outage site went down Gen overload (20KVA,290 A) SS IHS Fel=
ix confirmed// Grid power return","Fanda Brice","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload"," Grid outage site went down Gen overload (2=
0KVA,290 A) SS IHS Felix confirmed// Grid power return","christian.fonkou@i=
hstowers.com","306","13-01-2025 14:49:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004070411","Akak-Nko=
zoa-MTN-IHS","","13-01-2025 14:28:10","13-01-2025 14:24:20","13-01-2025 14:=
26:02","Cascaded Incident from TTO4063406","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
 52,7V Site on GEN. symphorien (650257151/Huawei) is informed.","system","2=
79632","13-01-2025 14:28:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004069947","M=
imboman-Ecole","","13-01-2025 13:12:09","13-01-2025 13:06:03","13-01-2025 1=
3:24:50","Grid outage, site went down before gen start due to poor battery =
backup // Gen started automatically ","Mba Lazare Herve","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // Gen started autom=
atically ","rouselle.schoune@ihstowers.com","368","13-01-2025 13:12:09","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0004069942","EMANA BI=
LICK CITY","","13-01-2025 13:11:41","13-01-2025 13:02:25","13-01-2025 13:50=
:25","Cascaded Incident from TTO4062879","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage .gen failed to =
start due to alarm""high temp""//We add water and gen manually started ","s=
ystem","270153","13-01-2025 13:11:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0004069944","Messassi=
 okolo","","13-01-2025 13:11:41","13-01-2025 13:02:25","13-01-2025 13:50:25=
","Cascaded Incident from TTO4062879","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage .gen failed to sta=
rt due to alarm""high temp""//We add water and gen manually started ","syst=
em","270153","13-01-2025 13:11:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0004069945","Emana ly=
cee 2","","13-01-2025 13:11:41","13-01-2025 13:02:25","13-01-2025 13:50:25"=
,"Cascaded Incident from TTO4062879","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage .gen failed to star=
t due to alarm""high temp""//We add water and gen manually started ","syste=
m","270154","13-01-2025 13:11:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004069943","Emana Ly=
cee","","13-01-2025 13:11:41","13-01-2025 13:02:25","13-01-2025 13:50:25","=
Cascaded Incident from TTO4062879","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage .gen failed to start =
due to alarm""high temp""//We add water and gen manually started ","system"=
,"270153","13-01-2025 13:11:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0004069941","Mballa 4=
","","13-01-2025 13:11:40","13-01-2025 13:02:25","13-01-2025 13:50:25","Cas=
caded Incident from TTO4062879","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage .gen failed to start due =
to alarm""high temp""//We add water and gen manually started ","system","27=
0154","13-01-2025 13:11:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0004069924","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","13=
-01-2025 13:08:32","13-01-2025 13:02:25","13-01-2025 13:50:25","Grid outage=
 .gen failed to start due to alarm""high temp""//We add water and gen manua=
lly started ","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","AC=
DG - High Engine Temp - Coolant Level Issue","Grid outage .gen failed to st=
art due to alarm""high temp""//We add water and gen manually started ","rou=
selle.schoune@ihstowers.com","369","13-01-2025 13:08:32","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004069859","Nko=
lbong","","13-01-2025 12:58:39","13-01-2025 12:53:32","13-01-2025 13:31:32"=
,"Grid outage, Site went down because Gen failed to start due to Gen card f=
aulty (IHS SS Bernard ATANGANA is informed and confirmed) // He started Gen=
 manualy","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid outage, Site went down because Gen failed to start due=
 to Gen card faulty (IHS SS Bernard ATANGANA is informed and confirmed) // =
He started Gen manualy","ange.kongo@ihstowers.com","308","13-01-2025 12:58:=
39","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004069774","Ema=
na","","13-01-2025 12:42:57","13-01-2025 12:38:49","13-01-2025 12:50:40","G=
rid outage, Site went down before Gen start due to poor backup// Gen starte=
d manually","Fabrice Pouakam","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, Site went down before Gen start=
 due to poor backup// Gen started manually","ange.kongo@ihstowers.com","249=
","13-01-2025 12:42:57","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004069406","Sap=
eur","","13-01-2025 11:43:22","13-01-2025 11:40:10","13-01-2025 11:58:10","=
Site on gen due to grid oputage, grid return, site went down due to poor ba=
ttery backup // grid return","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Site on gen due to grid oputa=
ge, grid return, site went down due to poor battery backup // grid return",=
"ange.kongo@ihstowers.com","193","13-01-2025 11:43:22","Sagemcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004069058","Ntu=
i administration","","13-01-2025 11:03:15","13-01-2025 10:55:08","13-01-202=
5 11:47:08","Site went down due to 1/2 retifier disfunction // he reset it =
and site is up","Parker Tchoup","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to 1/2 retifier disfunction // he rese=
t it and site is up","ange.kongo@ihstowers.com","488","13-01-2025 11:03:15"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0004069052","S=
apeur","","13-01-2025 11:02:29","13-01-2025 10:59:22","13-01-2025 11:08:22"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ gen start automatically","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen start automatically","rouse=
lle.schoune@ihstowers.com","189","13-01-2025 11:02:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0004068836","E=
ssomba","","13-01-2025 10:35:14","13-01-2025 10:29:10","13-01-2025 11:47:10=
","Site went down due to 2/5 rectifiers disfunctionning // reset done and g=
en started","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down due to 2/5 rectifiers disfunctionning // re=
set done and gen started","rouselle.schoune@ihstowers.com","365","13-01-202=
5 10:35:14","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004068485","AWA=
E OCM","","13-01-2025 09:44:21","13-01-2025 09:38:16","13-01-2025 09:42:16"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ gen start automatically","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // gen start automatically","an=
ge.kongo@ihstowers.com","366","13-01-2025 09:44:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004068022","N=
kolo II New","","13-01-2025 08:22:10","13-01-2025 08:14:03","13-01-2025 10:=
05:03","Active // no power issue on site U=3D53.5V on grid, TX FME LIONEL S=
TEVE ADJEP/ 655184876  From huawei is informed and notice that disjunction =
in OCM EQUIPMENT","Mba Lazare Herve","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active // no power issue o=
n site U=3D53.5V on grid, TX FME LIONEL STEVE ADJEP/ 655184876  From huawei=
 is informed and notice that disjunction in OCM EQUIPMENT","rouselle.schoun=
e@ihstowers.com","489","13-01-2025 08:22:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004067917","D=
ong","","13-01-2025 07:49:52","13-01-2025 07:46:45","13-01-2025 08:30:25","=
Active: No power issue, site on Battery With Ubaie=3D50,3V,   The Tx FME Gr=
egoire (654547479) from Huawei is informed.","Parker Tchoup","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue, site on Battery With Ubaie=3D50,3V, =20
The Tx FME Gregoire (654547479) from Huawei is informed.
","rouselle.schoune@ihstowers.com","188","13-01-2025 07:49:52","Sagemcom CM=
R"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004067284","Nko=
g-Edzen","","13-01-2025 05:54:49","13-01-2025 05:52:39","13-01-2025 07:49:3=
4","No power issue on site with  Ubaie=3D52.4V site on Gen (start threshold=
 ubai=3D50 V)The Tx Fme Gregoire( 652070658)from Huawei is informed)","Park=
er Tchoup","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","No power issue on site with  Ubaie=3D52.4V site on G=
en (start threshold ubai=3D50 V)The Tx Fme Gregoire( 652070658)from Huawei =
is informed)","kamga.virgile@ihstowers.com","131","13-01-2025 05:54:49","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0004065969","M=
imboman-Village","","12-01-2025 23:03:15","12-01-2025 22:59:10","12-01-2025=
 23:49:24","grid outage, site went down due dysfunctionning of PWC ZTE // R=
eset Pwc zte and gen manually started","Mba Lazare Herve","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","grid outage, site we=
nt down due dysfunctionning of PWC ZTE // Reset Pwc zte and gen manually st=
arted","alexandre.kamal@ihstowers.com","246","12-01-2025 23:03:15","Sagemco=
m CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004065894","Nko=
lbisson usines des eaux 2","","12-01-2025 22:46:14","12-01-2025 22:34:20","=
12-01-2025 23:37:58","Grid outage site went down because Generator faulty /=
/Grid return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Generator Faulty","Grid outage site went down because Generat=
or faulty //Grid return","kamga.virgile@ihstowers.com","715","12-01-2025 22=
:46:14","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004065858","Man=
guiers Dispensaire","","12-01-2025 22:39:24","12-01-2025 22:08:14","12-01-2=
025 23:06:30","grid outage,gen failed to start due to grid contactor faulty=
//gen manually started","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","ATS-AMF Issue","grid outage,gen failed to start due to grid co=
ntactor faulty//gen manually started","kamga.virgile@ihstowers.com","1870",=
"12-01-2025 22:39:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0004065455","N=
kolo II New","","12-01-2025 22:01:44","12-01-2025 21:56:30","12-01-2025 22:=
38:25","site went down because the CB 125A dijuncted in the PWC // he reame=
d the CB 125A","Mba Lazare Herve","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","site went down because the CB =
125A dijuncted in the PWC // he reamed the CB 125A","kouoh.jean@ihstowers.c=
om","315","12-01-2025 22:01:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0004065376","M=
IMBOMAN LIBERTE","","12-01-2025 21:53:17","12-01-2025 21:51:10","12-01-2025=
 23:36:20","Grid outage, Site went down because gen stopped due to water mi=
xed with fuel in tank//he purged TANK and started the gen","Mba Lazare Herv=
e","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water =
In The Fuel","Grid outage, Site went down because gen stopped due to water =
mixed with fuel in tank//he purged TANK and started the gen","kouoh.jean@ih=
stowers.com","129","12-01-2025 21:53:17","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0004065373","Nko=
abang MTN","","12-01-2025 21:52:48","12-01-2025 21:39:39","12-01-2025 21:56=
:39","Grid outage, site went down before gen start due to poor battery back=
up // Gen started automatically","Mba Lazare Herve","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // Gen started automatica=
lly","stephane.nkamwa@ihstowers.com","790","12-01-2025 21:52:48","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004065316","M=
vog-Manga","","12-01-2025 21:45:00","12-01-2025 21:36:51","12-01-2025 22:20=
:15","Site went down Gen started and stopped due to phase imbalance // He r=
educed 01/07 rectiefier on site, site on Gen","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Over Voltage","Site went down Gen starte=
d and stopped due to phase imbalance // He reduced 01/07 rectiefier on site=
, site on Gen","kouoh.jean@ihstowers.com","491","12-01-2025 21:45:00","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0004065154","Nkolbiss=
on usines des eaux 2","","12-01-2025 21:24:41","12-01-2025 21:17:36","12-01=
-2025 21:23:30","Cascaded Incident from TTO4057490","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, site went down before gen start due to poor battery backup // Gen sta=
rted automatically","system","261893","12-01-2025 21:24:41","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0004065149","Nko=
lbisson","IHS_YND_763","12-01-2025 21:23:42","12-01-2025 21:17:36","12-01-2=
025 21:23:30","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen started automatically","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down before gen start due to poor battery backup // Gen s=
tarted automatically","stephane.nkamwa@ihstowers.com","367","12-01-2025 21:=
23:42","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004064598","SAA=
 Entrance","","12-01-2025 20:30:09","12-01-2025 20:25:02","12-01-2025 21:13=
:45","Grid outage .gen failed to start due to starter relay faulty// We byp=
ass it and gen manually started ","Parker Tchoup","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage .gen failed to start due=
 to starter relay faulty// We bypass it and gen manually started ","stephan=
e.nkamwa@ihstowers.com","308","12-01-2025 20:30:09","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004064166","Com=
plex Beac II","","12-01-2025 19:32:35","12-01-2025 19:27:16","12-01-2025 20=
:35:26","Site went down because 1/3 rectifier disfunctionning SS IHS Pascal=
ine Manda confirmed// He reset rectifier ","Albran Byorel","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Site went down because 1/3 rec=
tifier disfunctionning SS IHS Pascaline Manda confirmed// He reset rectifie=
r ","stephane.nkamwa@ihstowers.com","320","12-01-2025 19:32:35","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0004063917","N=
kolbong","","12-01-2025 18:30:32","12-01-2025 18:24:20","12-01-2025 18:38:5=
7","Grid outage, Site went down because Gen failed to start due to Gen card=
 faulty// He started Gen manualy","Delor Telezing","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down because=
 Gen failed to start due to Gen card faulty// He started Gen manualy","kouo=
h.jean@ihstowers.com","373","12-01-2025 18:30:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0004063137","EMANA BI=
LICK CITY","","12-01-2025 16:47:21","12-01-2025 16:34:12","12-01-2025 17:37=
:32","Cascaded Incident from TTO4055101","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive"," Grid outage, site went dow=
n because gen stopped with high temp alarm // he reset Gen card, and manual=
ly Gen started (investigation ongoing)","system","271789","12-01-2025 16:47=
:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0004063140","Emana ly=
cee 2","","12-01-2025 16:47:21","12-01-2025 16:34:12","12-01-2025 17:37:32"=
,"Cascaded Incident from TTO4055101","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive"," Grid outage, site went down be=
cause gen stopped with high temp alarm // he reset Gen card, and manually G=
en started (investigation ongoing)","system","271791","12-01-2025 16:47:21"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004063138","Emana Ly=
cee","","12-01-2025 16:47:21","12-01-2025 16:34:12","12-01-2025 17:37:32","=
Cascaded Incident from TTO4055101","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive"," Grid outage, site went down beca=
use gen stopped with high temp alarm // he reset Gen card, and manually Gen=
 started (investigation ongoing)","system","271789","12-01-2025 16:47:21","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0004063139","Messassi=
 okolo","","12-01-2025 16:47:21","12-01-2025 16:34:12","12-01-2025 17:37:32=
","Cascaded Incident from TTO4055101","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive"," Grid outage, site went down b=
ecause gen stopped with high temp alarm // he reset Gen card, and manually =
Gen started (investigation ongoing)","system","271790","12-01-2025 16:47:21=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0004063136","Mballa 4=
","","12-01-2025 16:47:20","12-01-2025 16:34:12","12-01-2025 17:37:32","Cas=
caded Incident from TTO4055101","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive"," Grid outage, site went down because =
gen stopped with high temp alarm // he reset Gen card, and manually Gen sta=
rted (investigation ongoing)","system","271790","12-01-2025 16:47:20","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0004063114","M=
ontesquieux","","12-01-2025 16:44:36","12-01-2025 16:25:09","12-01-2025 16:=
40:47","Site went down because 2/5 rectifiers disfunctionning SS IHS Blaise=
 Raoul confirmed// He reset rectifiers","Paul BIBOUM","Equipment Repair","P=
assive","Rectifier","Rectifier Module","Site went down because 2/5 rectifie=
rs disfunctionning SS IHS Blaise Raoul confirmed// He reset rectifiers","ko=
uoh.jean@ihstowers.com","1168","12-01-2025 16:44:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0004063099","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","12=
-01-2025 16:41:20","12-01-2025 16:34:12","12-01-2025 17:37:32"," Grid outag=
e, site went down because gen stopped with high temp alarm // he reset Gen =
card, and manually Gen started (investigation ongoing)","Fabrice Pouakam","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"," Grid outage=
, site went down because gen stopped with high temp alarm // he reset Gen c=
ard, and manually Gen started (investigation ongoing)","kouoh.jean@ihstower=
s.com","429","12-01-2025 16:41:20","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004063044","Ema=
na","","12-01-2025 16:28:10","12-01-2025 16:23:02","12-01-2025 16:35:13","G=
rid outage, site went down before gen start due to poor batteries backup //=
 gen start automatically","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor batteries backup // gen start automatically","st=
ephane.nkamwa@ihstowers.com","308","12-01-2025 16:28:10","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0004062658","Nko=
ulou Carriere carrefourt","","12-01-2025 15:19:25","12-01-2025 15:06:17","1=
2-01-2025 17:50:44","Grid outage, Site went down Gen failed to start due to=
  no charging alternator, no Gen battery and causing disjunction at CB PWC =
 SS IHS Alphonse Deffo confirmed // Grid return and CB put back on (Cha","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator =
Faulty","Grid outage, Site went down Gen failed to start due to  no chargin=
g alternator, no Gen battery and causing disjunction at CB PWC  SS IHS Alph=
onse Deffo confirmed // Grid return and CB put back on (Charging alternator=
 to be installed)","stephane.nkamwa@ihstowers.com","789","12-01-2025 15:19:=
25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004062529","E=
koumdoum","","12-01-2025 14:58:11","12-01-2025 14:34:06","12-01-2025 14:54:=
39","Site went down because 2/3 rectifiers disfunctionning SS IHS Pascaline=
 Manda confirmed// He reset rectifiers","Albran Byorel","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","Site went down because 2/3 rectif=
iers disfunctionning SS IHS Pascaline Manda confirmed// He reset rectifiers=
","kouoh.jean@ihstowers.com","1446","12-01-2025 14:58:11","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004062155","NKO=
MEKUI OCM","","12-01-2025 14:34:49","12-01-2025 14:30:40","12-01-2025 14:35=
:58","ACTIVE//no power issue on site U=3D54.5  V site on Gen. Site impacted=
 by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","ACTIVE//no power issue on site U=3D54.5  V site on Gen. Site impac=
ted by Mbankolo Camtel and not managing by IHS","emmanuel.ghani@ihstowers.c=
om","250","12-01-2025 14:34:49","Sagemcom CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0004061758","Mam=
ch Building","","12-01-2025 14:03:29","12-01-2025 13:56:21","12-01-2025 14:=
37:33","Grid outage, site went down because gen start and stopped with alar=
m Over current (unprouven alarm)// He reset gen card , site manually  gen",=
"Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Grid outage, site went down because gen start and stopped with alarm O=
ver current (unprouven alarm)// He reset gen card , site manually  gen","em=
manuel.ghani@ihstowers.com","429","12-01-2025 14:03:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004061656","Bastos B=
ir","","12-01-2025 13:51:11","12-01-2025 13:36:54","12-01-2025 14:26:00","C=
ascaded Incident from TTO4053456","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because 1/3 rectifier=
 faulty SS IHS Bernard Atangana confirmed // He removed rectifier faulty an=
d reduiced the load ","system","282542","12-01-2025 13:51:11","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004061657","ARMP",""=
,"12-01-2025 13:51:11","12-01-2025 13:36:54","12-01-2025 14:26:00","Cascade=
d Incident from TTO4053456","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down because 1/3 rectifier faulty SS IHS Bern=
ard Atangana confirmed // He removed rectifier faulty and reduiced the load=
 ","system","282542","12-01-2025 13:51:11","Sagemcom CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0004061611","Dra=
gage","IHS_YND_704, IHS_YND_208","12-01-2025 13:42:01","12-01-2025 13:26:54=
","12-01-2025 14:31:03","Site went down because 1/3 rectifier faulty SS IHS=
 Bernard Atangana confirmed // He removed rectifier faulty and reduiced the=
 load ","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down because 1/3 rectifier faulty SS IHS Bernard Atanga=
na confirmed // He removed rectifier faulty and reduiced the load ","emmanu=
el.ghani@ihstowers.com","908","12-01-2025 13:42:01","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0004061395","Nko=
lbong","","12-01-2025 13:12:47","12-01-2025 13:05:42","12-01-2025 15:41:22"=
,"Grid outage, Site went down because Gen failed to start due to Gen card f=
aulty// He started Gen manualy","Delor Telezing","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down because G=
en failed to start due to Gen card faulty// He started Gen manualy","emmanu=
el.ghani@ihstowers.com","426","12-01-2025 13:12:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0004061295","Emana ly=
cee 2","","12-01-2025 12:52:51","12-01-2025 12:44:00","12-01-2025 14:31:25"=
,"Cascaded Incident from TTO4053007","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive"," Grid outage, site went down be=
cause gen stopped with high temp alarm // he added water in radiator and ma=
nually started","system","278435","12-01-2025 12:52:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0004061294","Messassi=
 okolo","","12-01-2025 12:52:50","12-01-2025 12:44:00","12-01-2025 14:31:25=
","Cascaded Incident from TTO4053007","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive"," Grid outage, site went down b=
ecause gen stopped with high temp alarm // he added water in radiator and m=
anually started","system","278434","12-01-2025 12:52:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0004061293","Emana Ly=
cee","","12-01-2025 12:52:50","12-01-2025 12:44:00","12-01-2025 14:31:25","=
Cascaded Incident from TTO4053007","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive"," Grid outage, site went down beca=
use gen stopped with high temp alarm // he added water in radiator and manu=
ally started","system","278436","12-01-2025 12:52:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0004061292","EMANA BI=
LICK CITY","","12-01-2025 12:52:50","12-01-2025 12:44:00","12-01-2025 14:31=
:25","Cascaded Incident from TTO4053007","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive"," Grid outage, site went dow=
n because gen stopped with high temp alarm // he added water in radiator an=
d manually started","system","278435","12-01-2025 12:52:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0004061255","O=
kolo","IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","12-01-2025 12:5=
0:05","12-01-2025 12:44:00","12-01-2025 14:31:25"," Grid outage, site went =
down because gen stopped with high temp alarm // he added water in radiator=
 and manually started","Fabrice Pouakam","Equipment Repair","Passive","ACDG=
 Gen","ACDG - High Engine Temp - Coolant Level Issue"," Grid outage, site w=
ent down because gen stopped with high temp alarm // he added water in radi=
ator and manually started","christian.fonkou@ihstowers.com","366","12-01-20=
25 12:50:05","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0004061154","Pha=
rmacie SION","","12-01-2025 12:38:32","12-01-2025 12:34:11","12-01-2025 12:=
44:23","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen started automatically","Paul BIBOUM","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","	Grid outage, site went d=
own before gen start due to poor battery backup // Gen started automaticall=
y","emmanuel.ghani@ihstowers.com","262","12-01-2025 12:38:32","Sagemcom CMR=
"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0004061150","CLE=
 Building","","12-01-2025 12:37:14","12-01-2025 12:31:55","12-01-2025 14:29=
:15","Grid outage, No space to deploy MDG// Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space =
to deploy MDG// Grid return","emmanuel.ghani@ihstowers.com","320","12-01-20=
25 12:37:14","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004061141","Ema=
na","","12-01-2025 12:35:55","12-01-2025 12:29:50","12-01-2025 12:41:23","G=
rid outage, site went down before gen start due to poor batteries backup //=
 gen start automatically","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor batteries backup // gen start automatically","em=
manuel.ghani@ihstowers.com","365","12-01-2025 12:35:55","Sagemcom CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0004061025","Mba=
lla 4","","12-01-2025 12:17:01","12-01-2025 12:10:56","12-01-2025 12:30:21"=
,"grid outage, site went down bacuse gen failed to start due to battery Gen=
 faulty // Gen manually started with external battery","Delor Telezing","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","grid outag=
e, site went down bacuse gen failed to start due to battery Gen faulty // G=
en manually started with external battery","emmanuel.ghani@ihstowers.com","=
366","12-01-2025 12:17:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004060994","SOA VILL=
AGE","","12-01-2025 12:10:00","12-01-2025 12:07:56","12-01-2025 12:27:49","=
Cascaded Incident from TTO4052692","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stopped with high temp alarm // he added water and manually =
start the gen","system","273145","12-01-2025 12:10:00","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004060986","SOA=
 TOWN","IHS_YND_323","12-01-2025 12:09:00","12-01-2025 12:07:56","12-01-202=
5 12:27:49","Grid outage, site went down because gen start and stopped with=
 high temp alarm // he added water and manually start the gen","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid outage, site went down because gen start and stopped=
 with high temp alarm // he added water and manually start the gen","emmanu=
el.ghani@ihstowers.com","65","12-01-2025 12:09:00","Sagemcom CMR"
"Closed Complete","Warning","T0104","IHS_YND_113","NOCINC0004060957","Emomb=
o 2","","12-01-2025 12:04:32","","","site on batter","MINKA NICOLAS","Warni=
ng","Warning","POWER","Warning - AC Phase 1 Current Low","Alarm cleared","d=
orothy.djantio@ihstowers.com","216","12-01-2025 12:04:32","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004060781","SOA=
 UNIVERSITY STADIUM","","12-01-2025 11:23:30","12-01-2025 11:19:25","12-01-=
2025 11:57:06","grid outage, site went down due to dysfunctionning of PWC Z=
TE // Gen manually started","Siligap Boris","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","grid outage, site went down due to=
 dysfunctionning of PWC ZTE // Gen manually started","emmanuel.ghani@ihstow=
ers.com","246","12-01-2025 11:23:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0004060651","S=
tade-Abega","","12-01-2025 10:55:58","12-01-2025 10:52:53","12-01-2025 11:3=
2:29","grid outage, site went down due dysfunctionning of PWC ZTE // Reset =
Pwc zte and gen manually starty","Mba Lazare Herve","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","grid outage, site went dow=
n due dysfunctionning of PWC ZTE // Reset Pwc zte and gen manually starty",=
"christian.fonkou@ihstowers.com","186","12-01-2025 10:55:58","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004060624","AWA=
E OCM","","12-01-2025 10:50:07","12-01-2025 10:45:02","12-01-2025 10:52:32"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rt automatically","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// Gen start automatically","emmanuel.ghani@ihsto=
wers.com","1890","12-01-2025 10:50:07","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004060589","Ebo=
go","","12-01-2025 10:41:14","12-01-2025 10:39:47","12-01-2025 10:41:31","G=
rid outage, Site went down before Gen start due to poor backup// Gen start =
automatically","Siligap Boris","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, Site went down before Gen star=
t due to poor backup// Gen start automatically","emmanuel.ghani@ihstowers.c=
om","88","12-01-2025 10:41:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004060546","M=
vog-Manga","","12-01-2025 10:30:45","12-01-2025 10:20:40","12-01-2025 10:58=
:24","site on grn due to grid outage, site on went down due to disjunction =
Cb(125A) of battery  // He reamed Cb(125A), site on grid","Albran Byorel","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breake=
r Issue","site on grn due to grid outage, site on went down due to disjunct=
ion Cb(125A) of battery  // He reamed Cb(125A), site on grid","christian.fo=
nkou@ihstowers.com","607","12-01-2025 10:30:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004060331","M=
essassi 2","","12-01-2025 10:15:34","12-01-2025 10:04:30","12-01-2025 14:09=
:52","No power issue, site is on grid with Ubaie=3D53V, Symphorien(69131685=
4) from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, s=
ite is on grid with Ubaie=3D53V, Symphorien(691316854) from Huawei is infor=
med","christian.fonkou@ihstowers.com","665","12-01-2025 10:15:34","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004059749","M=
endong vallee","","12-01-2025 08:53:41","12-01-2025 08:50:36","12-01-2025 1=
0:51:04","site went down because Gen failed to start due to lack of 2 phase=
 on site //  Gen manually started","Fanda Brice","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","site went down because Gen =
failed to start due to lack of 2 phase on site //  Gen manually started","c=
hristian.fonkou@ihstowers.com","186","12-01-2025 08:53:41","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0004059543","An-=
Marche-Melen","","12-01-2025 08:06:16","12-01-2025 08:00:11","12-01-2025 10=
:40:22","No power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144=
435) from Huawei is informed","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on gri=
d with Ubaie=3D53V, Mohamadou(691144435) from Huawei is informed","emmanuel=
.ghani@ihstowers.com","366","12-01-2025 08:06:16","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004059393","Nko=
g-Edzen","","12-01-2025 07:31:54","12-01-2025 07:27:48","12-01-2025 08:31:1=
7","grid outage, site went down beacuse gen failed to start due to high tem=
perature // He open the shelter of Gen and gen manually started","Parker Tc=
houp","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","grid outag=
e, site went down beacuse gen failed to start due to high temperature // He=
 open the shelter of Gen and gen manually started","emmanuel.ghani@ihstower=
s.com","247","12-01-2025 07:31:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004059336","Akak-Nko=
zoa-MTN-IHS","","12-01-2025 07:21:50","12-01-2025 07:15:22","12-01-2025 07:=
52:12","Cascaded Incident from TTO4050786","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid Outage, Gen failed t=
o start due to the high temperature // water added and manual start of gen"=
,"system","269187","12-01-2025 07:21:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004059291","D=
ong","","12-01-2025 07:15:41","12-01-2025 07:06:34","12-01-2025 07:37:56","=
Active //No power issue, site on battery  With Ubaie=3D50,2V,  Gregoire (65=
4547479) from Huawei is informed ","Parker Tchoup","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //No =
power issue, site on battery  With Ubaie=3D50,2V,  Gregoire (654547479) fro=
m Huawei is informed ","christian.fonkou@ihstowers.com","548","12-01-2025 0=
7:15:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0004059242","A=
WAE OCM","","12-01-2025 07:02:54","12-01-2025 07:01:50","12-01-2025 07:10:0=
6","Grid outage , Site went down before Gen start due to poor backup// Grid=
 return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage , Site went down before Gen start =
due to poor backup// Grid return","christian.fonkou@ihstowers.com","65","12=
-01-2025 07:02:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0004058829","M=
elen Ba'aba","","12-01-2025 04:39:57","12-01-2025 04:33:47","12-01-2025 06:=
03:43","Grid outage, Site went down because Gen stopped due to ""high temp"=
" alarm// We added water and gen manually started ","Siligap Boris","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Grid outage, Site went down because Gen stopped due to ""high temp""=
 alarm// We added water and gen manually started ","olivier.kwedi@ihstowers=
.com","371","12-01-2025 04:39:57","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0004058499","N=
yanon","","12-01-2025 02:03:05","12-01-2025 01:54:13","12-01-2025 02:33:41"=
,"Acttive//No power issue site on Gen Ubaie=3D 54,6V. The TX FME Gr=E9goire=
 //652070658// from huawei is informed. Repetitive issue","TIENTCHEU NZETCH=
IEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Acttive//No power issue site on Gen Ubaie=3D 54,6V. T=
he TX FME Gr=E9goire //652070658// from huawei is informed. Repetitive issu=
e","olivier.kwedi@ihstowers.com","534","12-01-2025 02:03:05","Sagemcom CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004058366","MEH=
ANDAN","","12-01-2025 01:16:36","12-01-2025 01:12:30","12-01-2025 02:12:58"=
,"site went down because Gen failed to start due to lack of 2 phase on site=
 // he did a bridge with a good phase ","Albran Byorel","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","site went down becau=
se Gen failed to start due to lack of 2 phase on site // he did a bridge wi=
th a good phase ","ludivine.ngamaleu@ihstowers.com","247","12-01-2025 01:16=
:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0004058312","M=
vog-Manga","","12-01-2025 00:53:26","12-01-2025 00:52:20","12-01-2025 01:23=
:48","site went down because insufficiency of rectifiers due to load increa=
se // He added 01 Rectifier, site is on 07 Rectifier ","Albran Byorel","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module","site went down bec=
ause insufficiency of rectifiers due to load increase // He added 01 Rectif=
ier, site is on Grid","olivier.kwedi@ihstowers.com","68","12-01-2025 00:53:=
26","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004058171","NYO=
M FACE MAETUR","","12-01-2025 00:08:42","12-01-2025 00:06:34","12-01-2025 0=
1:06:19","Grid outage site went down because Gen failed to start due to Gen=
 card faulty // Gen manually started","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down bec=
ause Gen failed to start due to Gen card faulty // Gen manually started","l=
udivine.ngamaleu@ihstowers.com","129","12-01-2025 00:08:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004057687","M=
ontee-Jouvence-II","","11-01-2025 22:35:34","11-01-2025 22:22:29","12-01-20=
25 02:30:20","site went down due to PWC Overload (12kw,230A) SS IHS Alphons=
e confirmed //Site Stabilized","Hyemafo Gildas","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","site went down due to PWC Over=
load (12kw,230A) SS IHS Alphonse confirmed //Site Stabilized","olivier.kwed=
i@ihstowers.com","787","11-01-2025 22:35:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004057385","ELOUMDEM=
 CARRIERE 2","","11-01-2025 21:54:41","11-01-2025 21:50:12","11-01-2025 22:=
07:25","Cascaded Incident from TTO4048467","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because gen start and stopped due to grid bad voltage // grid stabilize=
d","system","281405","11-01-2025 21:54:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004057384","Eto koss=
 Yde","","11-01-2025 21:54:40","11-01-2025 21:50:12","11-01-2025 22:07:25",=
"Cascaded Incident from TTO4048467","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause gen start and stopped due to grid bad voltage // grid stabilized","sys=
tem","281405","11-01-2025 21:54:40","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004057374","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","11-01-2025 21:53:22","11-01-2025 21:50=
:12","11-01-2025 22:07:25","Grid fluctuation, site went down because gen st=
art and stopped due to grid bad voltage // grid stabilized","Fanda Brice","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, site went down because gen start and stopped due to grid ba=
d voltage // grid stabilized","kamga.virgile@ihstowers.com","192","11-01-20=
25 21:53:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004056943","E=
koumdoum","","11-01-2025 20:45:33","11-01-2025 20:34:27","11-01-2025 21:17:=
28","Grid Outage, site went down because Gen stopped with ""high temp"" ala=
rm due to accordion cut// He reconnected accord=E9on, added water and start=
ed Gen manualy","Albran Byorel","Equipment Repair","Passive","ACDG Gen","AC=
DG - High Engine Temp - Coolant Level Issue","Grid Outage, site went down b=
ecause Gen stopped with ""high temp"" alarm due to accordion cut// He recon=
nected accord=E9on, added water and started Gen manualy","alexandre.kamal@i=
hstowers.com","667","11-01-2025 20:45:33","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004056923","NTU=
I TOWN","","11-01-2025 20:40:08","11-01-2025 20:32:28","11-01-2025 22:54:46=
","grid outage,gen ran till fuel shortage//refueling done","Parker Tchoup",=
"Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran till =
fuel shortage//refueling done","kamga.virgile@ihstowers.com","461","11-01-2=
025 20:40:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0004056920","M=
vog-Ebanda","","11-01-2025 20:39:37","11-01-2025 20:31:33","12-01-2025 02:1=
5:49","no power issue on site  Ubaie =3D54,6V   site on Grid. Armand Nguets=
a(691144412) from Huawei is informed. Notice that we have disjunction in OC=
M equipment","Siligap Boris","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","no power issue on site  Ubaie =3D5=
4,6V   site on Grid. Armand Nguetsa(691144412) from Huawei is informed. Not=
ice that we have disjunction in OCM equipment","alexandre.kamal@ihstowers.c=
om","485","11-01-2025 20:39:37","Sagemcom CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0004056895","Eto=
udi2","","11-01-2025 20:36:54","11-01-2025 20:28:43","11-01-2025 21:36:04",=
"site went down because Gen failed to start due to lack of 2 phase  // he d=
id a bridge with a good phase on site","Delor Telezing","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","site went down becau=
se Gen failed to start due to lack of 2 phase  // he did a bridge with a go=
od phase on site","kamga.virgile@ihstowers.com","491","11-01-2025 20:36:54"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004056890","Man=
guiers Dispensaire","","11-01-2025 20:35:41","11-01-2025 20:24:26","11-01-2=
025 21:36:58","Grid outage site went down because Gen failed to start due t=
o Grid contactor Faulty  // Grid power return","Fabrice Pouakam","Equipment=
 Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage site went d=
own because Gen failed to start due to Grid contactor Faulty  // Grid power=
 return","kamga.virgile@ihstowers.com","676","11-01-2025 20:35:41","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004056772","M=
essassi 2","","11-01-2025 20:24:00","11-01-2025 20:23:54","12-01-2025 08:28=
:13","Active//No power issue on site Site on Grid Ubae=3D54,64V synphorien(=
6691316854) from Huawei is informed","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue on site Site on Grid Ubae=3D54,64V synphorien(6691316854) fr=
om Huawei is informed","alexandre.kamal@ihstowers.com","8","11-01-2025 20:2=
4:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004056561","Nsimalen=
 OCM","","11-01-2025 20:04:00","11-01-2025 19:56:49","11-01-2025 20:04:35",=
"Cascaded Incident from TTO4047518","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because 3/4 rectifi=
ers disfunctionning//he reset the rectifiers","system","295435","11-01-2025=
 20:04:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004056529","N=
kolda","IHS_YND_327","11-01-2025 20:02:58","11-01-2025 19:56:49","11-01-202=
5 22:31:35","site went down because 3/4 rectifiers disfunctionning//he rese=
t the rectifiers","Albran Byorel","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","site went down because 3/4 rectifiers disfunctionning//=
he reset the rectifiers","alexandre.kamal@ihstowers.com","370","11-01-2025 =
20:02:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004056140","SOA VILL=
AGE","","11-01-2025 19:32:30","11-01-2025 19:12:40","11-01-2025 19:44:09","=
Cascaded Incident from TTO4047066","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause gen start and stopped due to grid bad voltage // he bypass grid and m=
anually start the gen","system","269533","11-01-2025 19:32:30","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004056003","S=
OA TOWN","IHS_YND_323","11-01-2025 19:15:46","11-01-2025 19:09:40","11-01-2=
025 19:44:23","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage // he bypass grid and manually start the gen","S=
iligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because gen start and stopped=
 due to grid bad voltage // he bypass grid and manually start the gen","ale=
xandre.kamal@ihstowers.com","367","11-01-2025 19:15:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0004055662","B=
ONAS YDE","","11-01-2025 18:24:09","11-01-2025 18:14:56","11-01-2025 19:27:=
58","Site went down because 02/06 rectifiers faulty and causing disjunction=
 at BTS OCM  SS IHS Blaise Raoul confirmed// He reset rectifiers and CB OCM=
 put back on (rectifiers to be replaced)","Paul BIBOUM","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","Site went down because 02/06 rect=
ifiers faulty and causing disjunction at BTS OCM  SS IHS Blaise Raoul confi=
rmed// He reset rectifiers and CB OCM put back on (rectifiers to be replace=
d)","alexandre.kamal@ihstowers.com","554","11-01-2025 18:24:09","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004055533","S=
calom","","11-01-2025 18:07:18","11-01-2025 17:56:56","11-01-2025 19:05:33"=
,"Site went down due to insufficience of rectifier (06) SS IHS Blaise Raoul=
 confirmed// He added 01 rectifier (investigation ongoing)","Paul BIBOUM","=
Equipment Repair","Passive","Rectifier","Rectifier Module","Site went down =
due to insufficience of rectifier (06) SS IHS Blaise Raoul confirmed// He a=
dded 01 rectifier (investigation ongoing)","alexandre.kamal@ihstowers.com",=
"6454","11-01-2025 18:07:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004055216","N=
kolondom","","11-01-2025 17:10:31","11-01-2025 17:03:25","11-01-2025 18:01:=
31","Grid outage, site went down because Gen started and stopped with alarm=
 ""overvoltage"" // He reset card GE and gen manually started","Fabrice Pou=
akam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
outage, site went down because Gen started and stopped with alarm ""overvol=
tage"" // He reset card GE and gen manually started","alexandre.kamal@ihsto=
wers.com","428","11-01-2025 17:10:31","Sagemcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0004054575","Ntu=
i administration","","11-01-2025 15:20:51","11-01-2025 15:15:07","11-01-202=
5 15:20:04","Active: No power issue, site on Grid With Ubaie=3D54,9V,  The =
Tx FME Gregoire (654547479) from Huawei is informed, Site impacted by NTUI =
Camtel (Site not managing by IHS)","Parker Tchoup","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No p=
ower issue, site on Grid With Ubaie=3D54,9V,  The Tx FME Gregoire (65454747=
9) from Huawei is informed, Site impacted by NTUI Camtel (Site not managing=
 by IHS)","kamga.virgile@ihstowers.com","345","11-01-2025 15:20:51","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004054445","MEHANDAN=
","","11-01-2025 15:00:41","11-01-2025 14:31:56","11-01-2025 14:51:44","Cas=
caded Incident from TTO4045073","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue, site is on grid with Ubai=
e=3D56,3V, Lionel adjep(655184876) from Huawei is informed","system","12214=
10","11-01-2025 15:00:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004054439","O=
dza II OCM","IHS_YND_528","11-01-2025 15:00:02","11-01-2025 14:31:56","11-0=
1-2025 14:36:44","No power issue, site is on grid with Ubaie=3D56,3V, Lione=
l adjep(655184876) from Huawei is informed","Albran Byorel","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue, site is on grid with Ubaie=3D56,3V, Lionel adjep(655184876) fr=
om Huawei is informed","alexandre.kamal@ihstowers.com","1689","11-01-2025 1=
5:00:02","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0004054303","N=
yanon","","11-01-2025 14:35:52","11-01-2025 14:06:45","11-01-2025 14:10:17"=
,"No power issue site on Gen Ubaie=3D 55,1V. The TX FME Gr=E9goire //652070=
658// from huawei is informed. Repetitive issue","TIENTCHEU NZETCHIEU GAEL"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue site on Gen Ubaie=3D 55,1V. The TX FME Gr=E9goi=
re //652070658// from huawei is informed. Repetitive issue","alexandre.kama=
l@ihstowers.com","1749","11-01-2025 14:35:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_332","NOCINC0004054109","NKOMEKUI=
 OCM","","11-01-2025 14:06:30","11-01-2025 13:57:17","11-01-2025 14:13:00",=
"Cascaded Incident from TTO4044649","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Team is on site for PM =
works // End of works","system","1216124","11-01-2025 14:06:30","Sagemcom C=
MR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0004053589","Meh=
anda 1","","11-01-2025 12:41:15","11-01-2025 12:29:01","11-01-2025 13:30:12=
","Grid outage, site went down because gen failed to start due to pear faul=
ty // He changed the pear and gen manually started","Albran Byorel","Fuel O=
utage (Probable)","Passive","Diesel","Fuel Line Issue","Grid outage, site w=
ent down because gen failed to start due to pear faulty // He changed the p=
ear and gen manually started","stephane.nkamwa@ihstowers.com","735","11-01-=
2025 12:41:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004053342","Dong",""=
,"11-01-2025 12:21:52","11-01-2025 12:08:16","11-01-2025 13:11:40","Cascade=
d Incident from TTO4043717","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active //No power issue, site on Battery  wit=
h Ubaie=3D50,4V,  The TX FME Gregoire (654547479) from Huawei is informed. =
Notice that Site is impacted by NTUI Camtel (Swapp ODU)","system","302386",=
"11-01-2025 12:21:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004053338","Matsari"=
,"","11-01-2025 12:21:51","11-01-2025 12:08:16","11-01-2025 13:11:40","Casc=
aded Incident from TTO4043717","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active //No power issue, site on Battery  =
with Ubaie=3D50,4V,  The TX FME Gregoire (654547479) from Huawei is informe=
d. Notice that Site is impacted by NTUI Camtel (Swapp ODU)","system","30238=
6","11-01-2025 12:21:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004053341","Donga","=
","11-01-2025 12:21:51","11-01-2025 12:08:16","11-01-2025 13:11:40","Cascad=
ed Incident from TTO4043717","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active //No power issue, site on Battery  wi=
th Ubaie=3D50,4V,  The TX FME Gregoire (654547479) from Huawei is informed.=
 Notice that Site is impacted by NTUI Camtel (Swapp ODU)","system","302388"=
,"11-01-2025 12:21:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004053340","Ngouetou=
","","11-01-2025 12:21:51","11-01-2025 12:08:16","11-01-2025 13:11:40","Cas=
caded Incident from TTO4043717","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active //No power issue, site on Battery =
 with Ubaie=3D50,4V,  The TX FME Gregoire (654547479) from Huawei is inform=
ed. Notice that Site is impacted by NTUI Camtel (Swapp ODU)","system","3023=
85","11-01-2025 12:21:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0004053336","Nguila",=
"","11-01-2025 12:21:50","11-01-2025 12:08:16","11-01-2025 13:11:40","Casca=
ded Incident from TTO4043717","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active //No power issue, site on Battery  w=
ith Ubaie=3D50,4V,  The TX FME Gregoire (654547479) from Huawei is informed=
. Notice that Site is impacted by NTUI Camtel (Swapp ODU)","system","302389=
","11-01-2025 12:21:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004053337","MBIMBIM"=
,"","11-01-2025 12:21:50","11-01-2025 12:08:16","11-01-2025 13:11:40","Casc=
aded Incident from TTO4043717","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active //No power issue, site on Battery  =
with Ubaie=3D50,4V,  The TX FME Gregoire (654547479) from Huawei is informe=
d. Notice that Site is impacted by NTUI Camtel (Swapp ODU)","system","30238=
5","11-01-2025 12:21:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004053314","Yoko MTN=
","","11-01-2025 12:19:00","11-01-2025 12:08:16","11-01-2025 13:11:40","Cas=
caded Incident from TTO4043717","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active //No power issue, site on Battery =
 with Ubaie=3D50,4V,  The TX FME Gregoire (654547479) from Huawei is inform=
ed. Notice that Site is impacted by NTUI Camtel (Swapp ODU)","system","3023=
87","11-01-2025 12:19:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004053313","Ngoum","=
","11-01-2025 12:19:00","11-01-2025 12:08:16","11-01-2025 13:11:40","Cascad=
ed Incident from TTO4043717","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active //No power issue, site on Battery  wi=
th Ubaie=3D50,4V,  The TX FME Gregoire (654547479) from Huawei is informed.=
 Notice that Site is impacted by NTUI Camtel (Swapp ODU)","system","302388"=
,"11-01-2025 12:19:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0004053291","O=
ssombe","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_392, IHS_YND_475, I=
HS_YND_454, IHS_YND_434, IHS_YND_444, IHS_YND_473, IHS_YND_782","11-01-2025=
 12:16:34","11-01-2025 12:03:16","11-01-2025 23:22:44","Active //No power i=
ssue, site on Battery  with Ubaie=3D50,4V,  The TX FME Gregoire (654547479)=
 from Huawei is informed. Notice that Site is impacted by NTUI Camtel (Swap=
p ODU)","Parker Tchoup","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active //No power issue, site on Batter=
y  with Ubaie=3D50,4V,  The TX FME Gregoire (654547479) from Huawei is info=
rmed. Notice that Site is impacted by NTUI Camtel (Swapp ODU)","kouoh.jean@=
ihstowers.com","799","11-01-2025 12:16:34","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0004053045","Nko=
lbisson usines des eaux 2","","11-01-2025 11:44:42","11-01-2025 11:39:34","=
11-01-2025 13:02:43","Grid Outage Site Went down because  main alternator f=
aultty//MDG of 20 kva has deployed","TIENTCHEU NZETCHIEU GAEL","Equipment R=
eplacement","Passive","ACDG Gen","ACDG - Main Alternator","Grid Outage Site=
 Went down because  main alternator faultty//MDG of 20 kva has deployed","s=
tephane.nkamwa@ihstowers.com","309","11-01-2025 11:44:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004052899","Nsimalen=
 OCM","","11-01-2025 11:24:10","11-01-2025 11:10:58","11-01-2025 12:10:42",=
"Cascaded Incident from TTO4043258","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen stopped with alarm under frequency // He reset the Gen card and Gen ma=
nually started","system","269532","11-01-2025 11:24:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004052887","N=
kolda","IHS_YND_327","11-01-2025 11:20:52","11-01-2025 11:10:58","11-01-202=
5 12:10:42","Grid outage site went down because Gen stopped with alarm unde=
r frequency // He reset the Gen card and Gen manually started","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage site went down because Gen stopped with alarm under frequency // He re=
set the Gen card and Gen manually started","kouoh.jean@ihstowers.com","595"=
,"11-01-2025 11:20:52","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0004052476","Ako=
no","IHS_YND_687","11-01-2025 10:24:44","11-01-2025 10:08:37","11-01-2025 1=
0:13:04","Grid outage, site went down because gen ran untill fuel shoratge =
// refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down because gen ran untill fuel shoratge //=
 refueling done","stephane.nkamwa@ihstowers.com","968","11-01-2025 10:24:44=
","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0004052333","OLA=
MA","","11-01-2025 10:03:48","11-01-2025 10:08:37","11-01-2025 10:13:04",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid outage, site went down because gen ran untill fuel shoratge // ref=
ueling done","stephane.nkamwa@ihstowers.com","1215388","11-01-2025 10:03:48=
","Sagemcom CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0004052212","Ako=
no","","11-01-2025 09:47:53","","","Grid outage, site went down because gen=
 ran untill fuel shoratge // refueling done","Fanda Brice","Warning","Warni=
ng","DIESEL","Warning - Fuel Level Low","Grid outage, site went down becaus=
e gen ran untill fuel shoratge // refueling done","dorothy.djantio@ihstower=
s.com","306","11-01-2025 09:47:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0004051891","E=
koumdoum","","11-01-2025 08:57:25","11-01-2025 08:34:14","11-01-2025 08:36:=
14","Grid fluctuation site went down because Gen failed  to start due to Gr=
id bad voltage  // Grid stabilized","Albran Byorel","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation site we=
nt down because Gen failed  to start due to Grid bad voltage  // Grid stabi=
lized","kouoh.jean@ihstowers.com","1392","11-01-2025 08:57:25","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0004051619","E=
lobi Mokolo","","11-01-2025 08:15:32","11-01-2025 08:07:22","11-01-2025 09:=
52:26","Site went down because Gen failed to start due to Grid bad voltage =
 // he bypass the Grid and Gen manually started","Mboua Thierry","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","Site went d=
own because Gen failed to start due to Grid bad voltage  // he bypass the G=
rid and Gen manually started","kouoh.jean@ihstowers.com","491","11-01-2025 =
08:15:32","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004051543","Ngu=
ila","","11-01-2025 08:00:24","11-01-2025 07:55:16","11-01-2025 08:00:18","=
Active //No power issue, site on Gen  With Ubaie=3D54,2V,  Gregoire (654547=
479) from Huawei is informed ","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //No powe=
r issue, site on Gen  With Ubaie=3D54,2V,  Gregoire (654547479) from Huawei=
 is informed ","stephane.nkamwa@ihstowers.com","310","11-01-2025 08:00:24",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0004051228","Nko=
ngtock","","11-01-2025 07:11:19","11-01-2025 07:04:11","11-01-2025 07:10:33=
","ACTIVE / No power issue site on solar with U=3D50 V The Tx FME Etienne 6=
95033981 of huawei is informed","Kemeni Franklin","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE / No p=
ower issue site on solar with U=3D50 V The Tx FME Etienne 695033981 of huaw=
ei is informed","stephane.nkamwa@ihstowers.com","429","11-01-2025 07:11:19"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004050689","ARMP",""=
,"11-01-2025 04:40:51","11-01-2025 04:37:25","11-01-2025 04:40:21","Cascade=
d Incident from TTO4040738","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down before gen start due to poo=
r battery backup // gen start automatically","system","264389","11-01-2025 =
04:40:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004050688","Bastos B=
ir","","11-01-2025 04:40:50","11-01-2025 04:37:25","11-01-2025 04:40:21","C=
ascaded Incident from TTO4040738","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before g=
en start due to poor battery backup // gen start automatically","system","2=
64388","11-01-2025 04:40:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004050682","D=
ragage","IHS_YND_704, IHS_YND_208","11-01-2025 04:39:33","11-01-2025 04:37:=
25","11-01-2025 04:40:21","Grid outage, site went down before gen start due=
 to poor battery backup // gen start automatically","Mboua Thierry","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage, site went down before gen start due to poor battery backup // gen st=
art automatically","rouselle.schoune@ihstowers.com","129","11-01-2025 04:39=
:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0004050381","Minka","=
","11-01-2025 02:29:40","11-01-2025 02:13:59","11-01-2025 02:36:59","Cascad=
ed Incident from TTO4040347","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen ran=
 untill fuel shortage // refueling done","system","265762","11-01-2025 02:2=
9:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0004050369","Bondjock=
","","11-01-2025 02:25:31","11-01-2025 02:13:59","11-01-2025 02:36:59","Cas=
caded Incident from TTO4040347","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
ran untill fuel shortage // refueling done","system","265762","11-01-2025 0=
2:25:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0004050367","Mbeng","=
","11-01-2025 02:25:30","11-01-2025 02:13:59","11-01-2025 02:36:59","Cascad=
ed Incident from TTO4040347","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen ran=
 untill fuel shortage // refueling done","system","265761","11-01-2025 02:2=
5:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0004050354","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_553, IHS_YND_372","11-01-2025 02:23:=
28","11-01-2025 02:13:59","11-01-2025 02:36:59","Grid outage, site went dow=
n because gen ran untill fuel shortage // refueling done","Fanda Brice","Fu=
el Outage","Passive","Diesel","Diesel Outage","Grid outage, site went down =
because gen ran untill fuel shortage // refueling done","rouselle.schoune@i=
hstowers.com","570","11-01-2025 02:23:28","Sagemcom CMR"
"Cancelled","Warning","T2760","IHS_YND_370","NOCINC0004050355","Mom","","11=
-01-2025 02:23:28","","","Grid outage, site went down because gen ran until=
l fuel shortage // refueling done","Fanda Brice","","","","","","ange.kongo=
@ihstowers.com","378","11-01-2025 02:23:28","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0004050053","Nko=
lmvack","","11-01-2025 00:57:49","11-01-2025 00:31:42","11-01-2025 01:59:42=
","Hybrid gen site, site went down because gen stopped du to low oil pressu=
re // he added oil and manually start the gen","Parker Tchoup","Equipment R=
epair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Hybrid gen site, sit=
e went down because gen stopped du to low oil pressure // he added oil and =
manually start the gen","ange.kongo@ihstowers.com","1568","11-01-2025 00:57=
:49","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0004049943","AWA=
E OCM","","11-01-2025 00:24:37","11-01-2025 00:22:28","11-01-2025 00:26:28"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ gen start automatically","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // gen start automatically","an=
ge.kongo@ihstowers.com","130","11-01-2025 00:24:37","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004049938","Mon=
tee-Jouvence-II","","11-01-2025 00:22:43","11-01-2025 00:18:35","11-01-2025=
 00:25:28","site went down due to PWC over load(12KW.280A) SS IHS Felix Zam=
b=E9 confirmed // Site stabilized","Hyemafo Gildas","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","site went down due to PWC =
over load(12KW.280A) SS IHS Felix Zamb=E9 confirmed // Site stabilized","an=
ge.kongo@ihstowers.com","306","11-01-2025 00:22:43","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004049640","Com=
plex Beac II","","10-01-2025 23:12:36","10-01-2025 23:06:25","10-01-2025 23=
:18:31","Grid outage, site went down before gen start due to poor battery b=
ackup // gen start automatically","Albran Byorel","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // gen start automatically"=
,"ange.kongo@ihstowers.com","372","10-01-2025 23:12:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0004049437","T=
singa","","10-01-2025 22:27:38","10-01-2025 22:01:31","10-01-2025 23:16:31"=
,"Site on gen due to grid outage, site went down because gen ran until fuel=
 shortage // refueling done","Mboua Thierry","Fuel Outage","Passive","Diese=
l","Diesel Outage","Site on gen due to grid outage, site went down because =
gen ran until fuel shortage // refueling done","rouselle.schoune@ihstowers.=
com","1568","10-01-2025 22:27:38","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004048913","Com=
plex Beac II","","10-01-2025 21:10:03","10-01-2025 21:02:45","10-01-2025 21=
:40:40","grid bad voltage,and gen failed to start,no rcp//bypassed grid and=
 started the gen","Albran Byorel","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","grid bad voltage,and gen failed to start,n=
o rcp//bypassed grid and started the gen","ludivine.ngamaleu@ihstowers.com"=
,"439","10-01-2025 21:10:03","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0004048868","Odz=
a II","","10-01-2025 21:01:58","10-01-2025 21:01:54","10-01-2025 21:35:35",=
"Grid outage, Site went down because PWC dysfunctionning// He reset PWC ","=
Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module O=
verloaded","Grid outage, Site went down because PWC dysfunctionning// He re=
set PWC ","ludivine.ngamaleu@ihstowers.com","6","10-01-2025 21:01:58","Sage=
mcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004048576","NYO=
M FACE MAETUR","","10-01-2025 20:16:55","10-01-2025 20:06:59","10-01-2025 2=
0:32:33","Grid outage site went down because Gen failed to start due to Gen=
 card faulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start due to Gen card faulty // Grid return","ludivine.ngamaleu@i=
hstowers.com","597","10-01-2025 20:16:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0004048156","Nkolbiss=
on usines des eaux 2","","10-01-2025 19:30:30","10-01-2025 19:20:40","10-01=
-2025 19:27:53","Cascaded Incident from TTO4037748","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, site went down before gen start due to poor batteries backup // gen s=
tart automatically","system","268849","10-01-2025 19:30:30","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0004048151","Nko=
lbisson","IHS_YND_763","10-01-2025 19:29:45","10-01-2025 19:20:40","10-01-2=
025 19:27:53","Grid outage, site went down before gen start due to poor bat=
teries backup // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down before gen start due to poor batteries backup // gen=
 start automatically","ludivine.ngamaleu@ihstowers.com","546","10-01-2025 1=
9:29:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0004048134","Nomayos =
montee Meche","","10-01-2025 19:28:05","10-01-2025 18:42:42","10-01-2025 19=
:27:56","grid outage,site went down because gen ran till fuel shortage// Re=
fueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage=
","grid outage,site went down because gen ran till fuel shortage// Refuelin=
g done","etienne.itondo@ihstowers.com","2724","10-01-2025 19:28:05","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0004048011","S=
calom","","10-01-2025 19:03:02","10-01-2025 18:54:56","10-01-2025 19:50:56"=
,"Grid fluctuation site went down because Gen failed  to start due to Grid =
bad voltage and RCP on site // Grid stabilized","Paul BIBOUM","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on site went down because Gen failed  to start due to Grid bad voltage and =
RCP on site // Grid stabilized","dorothy.djantio@ihstowers.com","487","10-0=
1-2025 19:03:02","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004047872","Car=
refour Simbock","","10-01-2025 18:35:24","10-01-2025 18:26:18","10-01-2025 =
19:14:25","grid outage gen failed to start due to alarm undervoltage//he re=
set it and started the gen","Hyemafo Gildas","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","grid outage gen failed to start due to al=
arm undervoltage//he reset it and started the gen","ludivine.ngamaleu@ihsto=
wers.com","546","10-01-2025 18:35:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0004047838","B=
astos Bethesda","","10-01-2025 18:26:11","10-01-2025 18:24:07","10-01-2025 =
18:29:42","Grid Outage, Site went down before Gen start due to poor backup/=
/ Grid power return","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid Outage, Site went down before Ge=
n start due to poor backup// Grid power return","dorothy.djantio@ihstowers.=
com","126","10-01-2025 18:26:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0004047401","S=
apeur","","10-01-2025 17:13:52","10-01-2025 16:25:33","10-01-2025 17:36:17"=
,"","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","site went down because CB 125A faulty in PWC//he changed with anot=
her Cb 125A","dorothy.djantio@ihstowers.com","1221792","10-01-2025 17:13:52=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004047275","M=
essassi 2","","10-01-2025 16:58:50","10-01-2025 16:57:35","10-01-2025 19:30=
:35","No power issue site on Gen with U=3D54,4V Symphorien(691316854) from =
Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on Ge=
n with U=3D54,4V Symphorien(691316854) from Huawei is informed","dorothy.dj=
antio@ihstowers.com","77","10-01-2025 16:58:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0004047087","E=
-Police","IHS_YND_029","10-01-2025 16:33:38","10-01-2025 16:25:33","10-01-2=
025 17:36:17","site went down because CB 125A faulty in PWC//he changed wit=
h another Cb 125A","","Equipment Repair","Passive","Control Panel","Power C=
abinet - Circuit Breaker Issue","site went down because CB 125A faulty in P=
WC//he changed with another Cb 125A","dorothy.djantio@ihstowers.com","486",=
"10-01-2025 16:33:38","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0004046989","Nom=
ayos montee Meche","","10-01-2025 16:11:23","10-01-2025 16:08:17","10-01-20=
25 18:08:39","Grid outage site went down because Gen stopped with alarm Gen=
 under frequency ( Not proven ) // He reset the Gen card and Gen manually s=
tarted","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Grid outage site went down because Gen stopped with alarm Gen un=
der frequency ( Not proven ) // He reset the Gen card and Gen manually star=
ted","ludivine.ngamaleu@ihstowers.com","187","10-01-2025 16:11:23","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004046569","E=
kounou","","10-01-2025 15:02:13","10-01-2025 15:00:09","10-01-2025 15:06:45=
","Grid outage, Site went down before Gen start due to poor backup// Grid p=
ower return","Albran Byorel","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup// Grid power return","dorothy.djantio@ihstowers.com","12=
5","10-01-2025 15:02:13","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0004046508","Tsi=
nga","","10-01-2025 14:50:47","10-01-2025 14:42:38","10-01-2025 14:50:31","=
Grid outage, Site went down before Gen start due to poor backup// Gen start=
ed manually","Mboua Thierry","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup// Gen started manually","ludivine.ngamaleu@ihstowers.com=
","491","10-01-2025 14:50:47","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004046345","Tou=
ring Club International","","10-01-2025 14:28:53","10-01-2025 14:23:48","10=
-01-2025 14:56:20","site went down because the rectifiers disfunctionning c=
ausing by high temp on site //he opened the shelter and reset rectifiers","=
Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"site went down because the rectifiers disfunctionning causing by high temp=
 on site //he opened the shelter and reset rectifiers","ludivine.ngamaleu@i=
hstowers.com","306","10-01-2025 14:28:53","Sagemcom CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0004046169","NTE=
MASSI","IHS_BER_289","10-01-2025 14:07:23","10-01-2025 10:54:52","10-01-202=
5 10:55:25","wrongly ticket","Delor Telezing","Incorrectly Logged Tickets",=
"Error","Error","Error","wrongly ticket","kamga.virgile@ihstowers.com","115=
52","10-01-2025 14:07:23","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0004046138","N=
yanon","","10-01-2025 14:00:45","10-01-2025 13:57:29","10-01-2025 15:38:35"=
,"Active //No power issue, site on Gen  With Ubaie=3D55V,  Gregoire (654547=
479) from Huawei is informed ","TIENTCHEU NZETCHIEU GAEL","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e //No power issue, site on Gen  With Ubaie=3D55V,  Gregoire (654547479) fr=
om Huawei is informed ","alexandre.kamal@ihstowers.com","197","10-01-2025 1=
4:00:45","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004046122","Jou=
vence Mbenda","","10-01-2025 13:58:14","10-01-2025 13:57:04","10-01-2025 14=
:40:46","Grid outage site went down because Gen stopped  with alarm High te=
mp// He added water and Gen manually started","Hyemafo Gildas","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"Grid outage site went down because Gen stopped  with alarm High temp// He=
 added water and Gen manually started","kamga.virgile@ihstowers.com","71","=
10-01-2025 13:58:14","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0004046073","Car=
refour Simbock","","10-01-2025 13:52:33","10-01-2025 13:43:20","10-01-2025 =
15:22:37","Grid outage, site went down because gen ran untill fuel shoratge=
 // refueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Dies=
el Outage","Grid outage, site went down because gen ran untill fuel shoratg=
e // refueling done","kamga.virgile@ihstowers.com","554","10-01-2025 13:52:=
33","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004045404","NYO=
M FACE MAETUR","","10-01-2025 12:20:50","10-01-2025 12:12:35","10-01-2025 1=
2:24:45","Grid outage site went down because Gen failed to start due to Gen=
 card faulty // Grid return","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start due to Gen card faulty // Grid return","kamga.virgile@ihsto=
wers.com","496","10-01-2025 12:20:50","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004045102","Mon=
tee Jouvence","","10-01-2025 11:37:20","10-01-2025 11:29:03","10-01-2025 12=
:31:03","Site was on Gen due to Grid outage, site went down because gen sto=
pped with high temp alarm // he added water and manually start the gen","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine T=
emp - Coolant Level Issue","Site was on Gen due to Grid outage, site went d=
own because gen stopped with high temp alarm // he added water and manually=
 start the gen","kamga.virgile@ihstowers.com","498","10-01-2025 11:37:20","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004045097","Nsimalen=
 OCM","","10-01-2025 11:37:01","10-01-2025 11:31:28","10-01-2025 12:04:31",=
"Cascaded Incident from TTO4034091","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen stopped with alarm under frequency // He reset the Gen card and Gen ma=
nually started","system","268383","10-01-2025 11:37:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004045092","N=
kolda","IHS_YND_327","10-01-2025 11:35:43","10-01-2025 11:31:28","10-01-202=
5 12:04:31","Grid outage site went down because Gen stopped with alarm unde=
r frequency // He reset the Gen card and Gen manually started","Albran Byor=
el","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage site went down because Gen stopped with alarm under frequency // He re=
set the Gen card and Gen manually started","alexandre.kamal@ihstowers.com",=
"256","10-01-2025 11:35:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004045018","MEHANDAN=
","","10-01-2025 11:22:21","10-01-2025 11:14:41","10-01-2025 11:52:33","Cas=
caded Incident from TTO4033990","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down because Ge=
n failed to start due to ATS disfunctionning// He reset ATS and started Gen=
 manually","system","269161","10-01-2025 11:22:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004045010","O=
dza II OCM","IHS_YND_528","10-01-2025 11:21:45","10-01-2025 11:14:41","10-0=
1-2025 11:52:33","Grid outage, Site went down because Gen failed to start d=
ue to ATS disfunctionning// He reset ATS and started Gen manually","Albran =
Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid =
outage, Site went down because Gen failed to start due to ATS disfunctionni=
ng// He reset ATS and started Gen manually","alexandre.kamal@ihstowers.com"=
,"425","10-01-2025 11:21:45","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0004044989","Men=
dong NB","","10-01-2025 11:16:45","10-01-2025 11:08:33","10-01-2025 12:48:4=
7","Grid outage,no space to deploy MDG // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage,no space to =
deploy MDG // Grid return","kamga.virgile@ihstowers.com","493","10-01-2025 =
11:16:45","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0004044900","Ako=
k Ndoe Yde","","10-01-2025 11:00:28","10-01-2025 10:54:16","10-01-2025 11:4=
4:05","Grid bad voltage, site went down because Gen failed to start due to =
Grid bad voltage and poor battery backup//he bypassed Grid and Started Gen"=
,"Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid bad voltage, site went down because Gen failed to sta=
rt due to Grid bad voltage and poor battery backup//he bypassed Grid and St=
arted Gen","kamga.virgile@ihstowers.com","373","10-01-2025 11:00:28","Sagem=
com CMR"
"Cancelled","Warning","T1415","IHS_YND_680","NOCINC0004044858","MIMBOMAN LI=
BERTE","","10-01-2025 10:53:50","","","","Mba Lazare Herve","","","","","",=
"kamga.virgile@ihstowers.com","135","10-01-2025 10:53:50","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0004044435","Mel=
en Ba'aba","","10-01-2025 09:45:22","10-01-2025 09:41:08","10-01-2025 09:48=
:15","Grid fluctuation, site went down down because gen start and stopped d=
ue to grid bad voltage // he bypass grid and manually start the gen","Silig=
ap Boris","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation, site went down down because gen start and stoppe=
d due to grid bad voltage // he bypass grid and manually start the gen","ka=
mga.virgile@ihstowers.com","255","10-01-2025 09:45:22","Sagemcom CMR"
"Closed Complete","Site Down","T5041","IHS_YND_809","NOCINC0004044045","Nko=
l-Mebanga","","10-01-2025 08:55:59","10-01-2025 07:36:48","10-01-2025 07:40=
:11","No power issue on site U=3D50v site on solar Gregoire of huawei is in=
formed and confirmed","Parker Tchoup","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D50v site on solar Gregoire of huawei is informed and confirmed","kamga.v=
irgile@ihstowers.com","4752","10-01-2025 08:55:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0004044000","SAA 2","=
","10-01-2025 08:47:21","10-01-2025 08:26:12","10-01-2025 10:01:33","Cascad=
ed Incident from TTO4032787","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, site went down because gen s=
topped with high temp alarm // he added water in radiator and manually star=
ted","system","272073","10-01-2025 08:47:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0004043992","S=
aa","IHS_YND_726, IHS_YND_401, IHS_YND_404","10-01-2025 08:46:16","10-01-20=
25 08:26:12","10-01-2025 10:01:33","Grid outage, site went down because gen=
 stopped with high temp alarm // he added water in radiator and manually st=
arted","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High=
 Engine Temp - Coolant Level Issue","Grid outage, site went down because ge=
n stopped with high temp alarm // he added water in radiator and manually s=
tarted","alexandre.kamal@ihstowers.com","1205","10-01-2025 08:46:16","Sagem=
com CMR"
"Cancelled","Warning","T5040","IHS_YND_810","NOCINC0004043864","Carrefour A=
yissi Ele","","10-01-2025 08:26:22","","","","Parker Tchoup","","","","",""=
,"kamga.virgile@ihstowers.com","796","10-01-2025 08:26:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004043839","E=
kounou","","10-01-2025 08:20:51","10-01-2025 08:03:16","10-01-2025 08:30:28=
","Grid outage site went down before Gen start due to poor battery backup /=
/ Grid power return","Albran Byorel","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage site went down before Gen=
 start due to poor battery backup // Grid power return","alexandre.kamal@ih=
stowers.com","1056","10-01-2025 08:20:51","Sagemcom CMR"
"Cancelled","Warning","CTR_261","IHS_YND_161","NOCINC0004043804","Sofavinc"=
,"","10-01-2025 08:12:27","","","","MINKA NICOLAS","","","","","","alexandr=
e.kamal@ihstowers.com","545","10-01-2025 08:12:27","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004043087","Eko=
unou","","10-01-2025 05:45:12","10-01-2025 05:43:51","10-01-2025 05:53:48",=
"Grid outage, site went down before gen start due to poor batteries backup =
// gen start automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor batteries backup // gen start automatically","em=
manuel.ghani@ihstowers.com","83","10-01-2025 05:45:12","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0004042986","Nko=
lbisson IITA LP","","10-01-2025 05:14:51","10-01-2025 05:11:41","10-01-2025=
 10:25:21","Grid outage, No space to deploy MDG// Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No =
space to deploy MDG// Grid return","emmanuel.ghani@ihstowers.com","191","10=
-01-2025 05:14:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0004042946","Montee-J=
ouvence","","10-01-2025 05:00:21","10-01-2025 04:55:33","10-01-2025 06:20:4=
1","Cascaded Incident from TTO4031508","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause gen stopped with high temp alarm // he added water and manually start=
 the gen","system","270528","10-01-2025 05:00:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0004042945","Mendong =
vallee","","10-01-2025 05:00:20","10-01-2025 04:55:33","10-01-2025 06:20:41=
","Cascaded Incident from TTO4031508","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen stopped with high temp alarm // he added water and manually start the=
 gen","system","270528","10-01-2025 05:00:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004042942","M=
endong","IHS_YND_692, IHS_YND_236","10-01-2025 04:58:38","10-01-2025 04:55:=
33","10-01-2025 06:20:41","Grid outage, site went down because gen stopped =
with high temp alarm // he added water and manually start the gen","Hyemafo=
 Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp -=
 Coolant Level Issue","Grid outage, site went down because gen stopped with=
 high temp alarm // he added water and manually start the gen","christian.f=
onkou@ihstowers.com","186","10-01-2025 04:58:38","Sagemcom CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004042803","Eke=
kam","","10-01-2025 04:24:29","10-01-2025 03:54:21","10-01-2025 06:46:05","=
Hybrid Gen Site, site went down due to hybrid system dysfunctionning//he re=
set and Gen started manaully","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Hybrid","Hybrid Module","Hybrid Gen Site, site went down due to=
 hybrid system dysfunctionning//he reset and Gen started manaully","emmanue=
l.ghani@ihstowers.com","1809","10-01-2025 04:24:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004042463","D=
ong","","10-01-2025 02:24:48","10-01-2025 02:22:42","10-01-2025 03:24:55","=
Active: No power issue, site on Battery With Ubaie=3D50,3V,  The Tx FME Gre=
goire (654547479) from Huawei is informed.","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue, site on Battery With Ubaie=3D50,3V,  The Tx FME Gregoi=
re (654547479) from Huawei is informed.","christian.fonkou@ihstowers.com","=
127","10-01-2025 02:24:48","Sagemcom CMR"
"Closed Complete","Site Down","T3448","IHS_YND_714","NOCINC0004042400","Eke=
kam","","10-01-2025 02:02:20","10-01-2025 02:01:15","10-01-2025 02:45:37","=
Hybrid Gen Site, site went down due to hybrid system dysfunctionning//he re=
set & Gen started manaully","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","=
Passive","Hybrid","Hybrid Module","Hybrid Gen Site, site went down due to h=
ybrid system dysfunctionning//he reset & Gen started manaully","emmanuel.gh=
ani@ihstowers.com","66","10-01-2025 02:02:20","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004041515","Jou=
vence Mbenda","","09-01-2025 22:55:41","09-01-2025 22:12:37","09-01-2025 23=
:47:47"," grid outage, site went down because gen stopped with high temp al=
arm // he added water in radiator and manually started","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Le=
vel Issue"," grid outage, site went down because gen stopped with high temp=
 alarm // he added water in radiator and manually started","emmanuel.ghani@=
ihstowers.com","2585","09-01-2025 22:55:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004041397","N=
yom OCM","","09-01-2025 22:34:51","09-01-2025 22:26:45","09-01-2025 23:31:3=
1","ACTIVE//no power issue  Ubaie:54.2V   site on Gen,  TX fme symphorien /=
650257151 from huawei is informed","Fabrice Pouakam","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no=
 power issue  Ubaie:54.2V   site on Gen,  TX fme symphorien /650257151 from=
 huawei is informed","christian.fonkou@ihstowers.com","488","09-01-2025 22:=
34:51","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004040931","SAA=
 Entrance","","09-01-2025 21:18:14","09-01-2025 21:10:07","10-01-2025 01:55=
:32","Active//No power issue on site Ubaie=3D54.1V site on Gen Tx FME Grego=
ire /654547479/Huawei  is informed.","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie=3D54.1V site on Gen Tx FME Gregoire /654547479/H=
uawei  is informed.","ange.kongo@ihstowers.com","488","09-01-2025 21:18:14"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0004040908","ODZ=
A CITE MBIA","","09-01-2025 21:17:29","09-01-2025 21:01:19","09-01-2025 21:=
59:19","site went down because gen failed to start due to grid bad voltage =
//Gen manually started","Albran Byorel","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","site went down because gen failed to=
 start due to grid bad voltage //Gen manually started","ange.kongo@ihstower=
s.com","971","09-01-2025 21:17:29","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0004040520","Mok=
olo Yaounde","","09-01-2025 20:21:49","09-01-2025 20:17:41","09-01-2025 20:=
27:29","Grid outage, no space to deploy a mobile gen // grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e, no space to deploy a mobile gen // grid return","ange.kongo@ihstowers.co=
m","249","09-01-2025 20:21:49","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0004040512","Sap=
eur","","09-01-2025 20:20:18","09-01-2025 20:16:07","09-01-2025 20:22:55","=
Grid outage, site went down before gen start due to poor battery backup // =
gen start automatically","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // gen start automatically","ange.ko=
ngo@ihstowers.com","252","09-01-2025 20:20:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0004040484","B=
astos Bethesda","","09-01-2025 20:17:36","09-01-2025 20:14:31","09-01-2025 =
20:26:31","Grid outage, site went down because gen fails to start due to ba=
ttery ge faulty // gen start with battery backup","Mboua Thierry","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, site went down because gen fails to start due to battery ge faulty // =
gen start with battery backup","rouselle.schoune@ihstowers.com","187","09-0=
1-2025 20:17:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004040170","M=
ontee-Jouvence-II","","09-01-2025 19:39:46","09-01-2025 19:34:40","09-01-20=
25 20:16:40","site went down due to PWC over load(12KW.280A) SS IHS Felix Z=
amb=E9  confirmed // Site stabilized ","Hyemafo Gildas","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","site went down due to =
PWC over load(12KW.280A) SS IHS Felix Zamb=E9  confirmed // Site stabilized=
 ","rouselle.schoune@ihstowers.com","307","09-01-2025 19:39:46","Sagemcom C=
MR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004040132","ELO=
UMDEM CARRIERE","","09-01-2025 19:32:58","09-01-2025 19:28:40","09-01-2025 =
19:41:40","Grid outage, site went down because gen fails to start due to ba=
ttery ge faulty // gen start with battery backup","Fanda Brice","Equipment =
Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, site =
went down because gen fails to start due to battery ge faulty // gen start =
with battery backup","ange.kongo@ihstowers.com","259","09-01-2025 19:32:58"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004040129","SOA VILL=
AGE","","09-01-2025 19:32:10","09-01-2025 19:24:27","09-01-2025 20:04:40","=
Cascaded Incident from TTO4028106","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause gen start and stopped due to grid bad voltage // he bypass grid and m=
anually start the gen","system","275910","09-01-2025 19:32:10","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004040085","S=
OA TOWN","IHS_YND_323","09-01-2025 19:25:46","09-01-2025 19:22:40","09-01-2=
025 20:04:40","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage // he bypass grid and manually start the gen","S=
iligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because gen start and stopped=
 due to grid bad voltage // he bypass grid and manually start the gen","rou=
selle.schoune@ihstowers.com","187","09-01-2025 19:25:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0004040030","Awae Ewo=
nkan","","09-01-2025 19:13:10","09-01-2025 19:10:54","09-01-2025 19:40:42",=
"Cascaded Incident from TTO4027983","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e Gen started and stopped with alarm ' low oil pressure""// He did draining=
 and started Gen manualy","system","136","09-01-2025 19:13:10","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0004040031","Awae Esc=
alier","","09-01-2025 19:13:10","09-01-2025 19:10:54","09-01-2025 19:40:42"=
,"Cascaded Incident from TTO4027983","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down becau=
se Gen started and stopped with alarm ' low oil pressure""// He did drainin=
g and started Gen manualy","system","136","09-01-2025 19:13:10","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0004040026","A=
wae-Yde","IHS_YND_535, IHS_YND_171","09-01-2025 19:12:07","09-01-2025 19:10=
:54","09-01-2025 19:40:42","Grid outage, Site went down because Gen started=
 and stopped with alarm ' low oil pressure""// He did draining and started =
Gen manualy","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- Low Oil Pressure","Grid outage, Site went down because Gen started and st=
opped with alarm ' low oil pressure""// He did draining and started Gen man=
ualy","rouselle.schoune@ihstowers.com","74","09-01-2025 19:12:07","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004039928","NKO=
MEKUI OCM","","09-01-2025 18:47:30","09-01-2025 18:41:24","09-01-2025 21:15=
:32","ACTIVE//no power issue on site U=3D54.5 V site on Gen. Site impacted =
by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","ACTIVE//no power issue on site U=3D54.5 V site on Gen. Site impacte=
d by Mbankolo Camtel and not managing by IHS","ange.kongo@ihstowers.com","3=
67","09-01-2025 18:47:30","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004039816","Men=
dong vallee","","09-01-2025 18:24:33","09-01-2025 18:22:21","09-01-2025 18:=
52:21","Grid outage site went down because Gen over load (20KVA; 300A) awai=
ting Grid power return SS IHS F=E9lix Zamb=E9 is informed and confirmed","F=
anda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid=
 outage site went down because Gen over load (20KVA; 300A) awaiting Grid po=
wer return SS IHS F=E9lix Zamb=E9 is informed and confirmed","ange.kongo@ih=
stowers.com","133","09-01-2025 18:24:33","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004039809","Jou=
vence Mbenda","","09-01-2025 18:22:13","09-01-2025 18:17:06","09-01-2025 21=
:30:18","Grid Outage , site went down because Gen Start and sotopped due to=
 alarms  high temp  // he added water and manually start the Gen","Hyemafo =
Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - =
Coolant Level Issue","Grid Outage , site went down because Gen Start and so=
topped due to alarms  high temp  // he added water and manually start the G=
en","ange.kongo@ihstowers.com","308","09-01-2025 18:22:13","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004039798","MBI=
MBIM","","09-01-2025 18:19:45","09-01-2025 18:13:34","09-01-2025 18:31:34",=
"solar gen site; site went down because gen ran untill fuel shortage // ref=
uelling done (Fuel manage by edond=E9)","Parker Tchoup","Fuel Outage","Pass=
ive","Diesel","Diesel Outage","solar gen site; site went down because gen r=
an untill fuel shortage // refuelling done (Fuel manage by edond=E9)","ange=
.kongo@ihstowers.com","372","09-01-2025 18:19:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0004039568","D=
amas","","09-01-2025 17:31:08","09-01-2025 17:26:02","09-01-2025 22:11:35",=
"Grid Outage Site went down because Gen Overload(9Kva,150A), IHS SS PASCALI=
NE is informed and confirmed","MINKA NICOLAS","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid Outage Site went down because Gen Overlo=
ad(9Kva,150A), IHS SS PASCALINE is informed and confirmed","rouselle.schoun=
e@ihstowers.com","306","09-01-2025 17:31:08","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004039046","NYO=
M FACE MAETUR","","09-01-2025 15:58:25","09-01-2025 15:55:19","09-01-2025 1=
7:05:19","grid outage, site down because gen stopped due to emergency stop =
button activated//bypassed emergency stop button and started gen","Fabrice =
Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","g=
rid outage, site down because gen stopped due to emergency stop button acti=
vated//bypassed emergency stop button and started gen","ange.kongo@ihstower=
s.com","187","09-01-2025 15:58:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004038860","Akak-Nko=
zoa-MTN-IHS","","09-01-2025 15:23:50","09-01-2025 15:17:07","09-01-2025 15:=
51:38","Cascaded Incident from TTO4026509","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","grid Outage, Site down du=
e to poor backup // Grid Return","system","283662","09-01-2025 15:23:50","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004038727","MEHANDAN=
","","09-01-2025 15:06:00","09-01-2025 14:55:59","09-01-2025 15:45:31","Cas=
caded Incident from TTO4026371","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down because Ge=
n failed to start due to  PWC ZTE dysfunctionning// He reset PWC, Site on G=
en","system","270435","09-01-2025 15:06:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0004038716","O=
dza II OCM","IHS_YND_528","09-01-2025 15:05:06","09-01-2025 14:55:59","09-0=
1-2025 15:45:31","Grid outage, Site went down because Gen failed to start d=
ue to  PWC ZTE dysfunctionning// He reset PWC, Site on Gen","Albran Byorel"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Gr=
id outage, Site went down because Gen failed to start due to  PWC ZTE dysfu=
nctionning// He reset PWC, Site on Gen","rouselle.schoune@ihstowers.com","5=
48","09-01-2025 15:05:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004038705","N=
yom OCM","","09-01-2025 15:03:57","09-01-2025 14:54:50","09-01-2025 15:22:5=
0","Grid fluctuation, gen start and stopped due to grid bad voltage, no RCP=
 on site // he bypass grid and manually started","Fabrice Pouakam","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation, gen start and stopped due to grid bad voltage, no RCP on site // h=
e bypass grid and manually started","rouselle.schoune@ihstowers.com","548",=
"09-01-2025 15:03:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0004038658","Okola OC=
M","","09-01-2025 14:57:51","09-01-2025 14:48:59","09-01-2025 14:49:59","Ca=
scaded Incident from TTO4026265","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Active","Cascade Active","Cascade Active","Active //No power issue, site=
 on Gen  With Ubaie=3D55V,  Gregoire (654547479) from Huawei is informed ",=
"system","270994","09-01-2025 14:57:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0004038625","E=
zezang","IHS_YND_389, IHS_YND_705, IHS_YND_386, IHS_YND_400, IHS_YND_338, I=
HS_YND_354","09-01-2025 14:55:50","09-01-2025 14:48:59","09-01-2025 16:30:5=
9","Active //No power issue, site on Gen  With Ubaie=3D55V,  Gregoire (6545=
47479) from Huawei is informed ","Parker Tchoup","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //No po=
wer issue, site on Gen  With Ubaie=3D55V,  Gregoire (654547479) from Huawei=
 is informed ","rouselle.schoune@ihstowers.com","412","09-01-2025 14:55:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0004038601","Sim=
bock Maetur","","09-01-2025 14:51:01","09-01-2025 14:44:56","09-01-2025 15:=
00:21","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage, site went down because gen ran untill fuel shortage /=
/ refueling done","ange.kongo@ihstowers.com","365","09-01-2025 14:51:01","S=
agemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0004038464","N=
yanon","","09-01-2025 14:21:41","09-01-2025 14:12:59","09-01-2025 17:13:59"=
,"Active //No power issue, site on Gen  With Ubaie=3D55V,  Gregoire (654547=
479) from Huawei is informed ","TIENTCHEU NZETCHIEU GAEL","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e //No power issue, site on Gen  With Ubaie=3D55V,  Gregoire (654547479) fr=
om Huawei is informed ","rouselle.schoune@ihstowers.com","524","09-01-2025 =
14:21:41","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004038435","Men=
dong vallee","","09-01-2025 14:16:58","09-01-2025 14:14:24","09-01-2025 17:=
32:57","Grid outage site went down because Gen over load (20KVA; 300A) SS I=
HS F=E9lix Zamb=E9 is informed and confirmed//Grid Restored","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site=
 went down because Gen over load (20KVA; 300A) SS IHS F=E9lix Zamb=E9 is in=
formed and confirmed//Grid Restored","ange.kongo@ihstowers.com","155","09-0=
1-2025 14:16:58","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004038423","ODZ=
A MINKAN EDIBI ASSI","","09-01-2025 14:14:36","09-01-2025 14:08:26","09-01-=
2025 14:46:37","site went down because Gen failed to start due to lack of 2=
 phase and No RCP on site // he did a bridge with a good phase on site	","A=
lbran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","site went down because Gen failed to start due to lack of 2 ph=
ase and No RCP on site // he did a bridge with a good phase on site	","ange=
.kongo@ihstowers.com","371","09-01-2025 14:14:36","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0004038172","SAA=
 Entrance","","09-01-2025 13:30:16","09-01-2025 13:26:10","09-01-2025 14:40=
:45","site went down due to 01/02 rectifiers disfunctionning // He reset it=
 and  site is Grid","Parker Tchoup","Equipment Repair","Passive","Rectifier=
","Rectifier Module","site went down due to 01/02 rectifiers disfunctionnin=
g // He reset it and  site is Grid","ludivine.ngamaleu@ihstowers.com","248"=
,"09-01-2025 13:30:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0004038010","O=
bobogo","","09-01-2025 13:04:55","09-01-2025 13:01:51","09-01-2025 13:05:14=
","Grid outage, Site went down before Gen start due to poor backup// Gen st=
arted manually","MINKA NICOLAS","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup// Gen started manually","dorothy.djantio@ihstowers.co=
m","185","09-01-2025 13:04:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0004037997","M=
essassi 2","","09-01-2025 13:03:29","09-01-2025 12:56:21","09-01-2025 14:05=
:28","Site on gen due to grid outage, Site went down because Grid restored =
but the grid contactor disfunction // He blocked Grid Contactor, Site on Gr=
id","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF=
 Issue","Site on gen due to grid outage, Site went down because Grid restor=
ed but the grid contactor disfunction // He blocked Grid Contactor, Site on=
 Grid","dorothy.djantio@ihstowers.com","430","09-01-2025 13:03:29","Sagemco=
m CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0004037917","Ngu=
ila","","09-01-2025 12:49:06","09-01-2025 12:43:00","09-01-2025 13:48:49","=
No power issue on site U=3D54,3v site on gen Tx fme Gregoire of huawei is i=
nformed","Parker Tchoup","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,3v site =
on gen Tx fme Gregoire of huawei is informed","ludivine.ngamaleu@ihstowers.=
com","367","09-01-2025 12:49:06","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0004037570","NKO=
LMEKONG YDE","","09-01-2025 11:48:01","09-01-2025 11:46:56","09-01-2025 11:=
48:56","Grid outage, site went down before gen start due to poor battery ba=
ckup // Grid power return","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // Grid power return","ludivine.=
ngamaleu@ihstowers.com","66","09-01-2025 11:48:01","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004037419","NYO=
M FACE MAETUR","","09-01-2025 11:22:47","09-01-2025 11:21:23","09-01-2025 1=
3:09:02","grid outage,gen failed to start due to card Ge faulty//Gen manual=
ly started","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","grid outage,gen failed to start due to card Ge faulty//G=
en manually started","ludivine.ngamaleu@ihstowers.com","85","09-01-2025 11:=
22:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0004037019","Mballa 4=
","","09-01-2025 10:28:40","09-01-2025 10:14:52","09-01-2025 10:26:45","Cas=
caded Incident from TTO4024301","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive"," grid outage, site went down because =
gen stopped with high temp alarm // he added water in radiator and manually=
 started","system","265736","09-01-2025 10:28:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0004036982","O=
kolo","IHS_YND_242","09-01-2025 10:20:56","09-01-2025 10:14:52","09-01-2025=
 10:26:45"," grid outage, site went down because gen stopped with high temp=
 alarm // he added water in radiator and manually started","Fabrice Pouakam=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue"," grid outage, site went down because gen stopped with high =
temp alarm // he added water in radiator and manually started","dorothy.dja=
ntio@ihstowers.com","365","09-01-2025 10:20:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0004036923","E=
mana lycee 2","","09-01-2025 10:11:25","09-01-2025 10:04:17","09-01-2025 10=
:48:30","grid outage,gen failed to start due to CB 40A Ge disjuncted//he re=
amed the CB","Fabrice Pouakam","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Circuit Breaker Issue","grid outage,gen failed to start d=
ue to CB 40A Ge disjuncted//he reamed the CB","dorothy.djantio@ihstowers.co=
m","429","09-01-2025 10:11:25","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_247","NOCINC0004036866","Okolo","",=
"09-01-2025 10:04:08","",""," site ALARMIING  because gen stopped with high=
 temp alarm // he added water in radiator and manually started and alarm cl=
erared","Fabrice Pouakam","Warning","Warning","POWER","Warning - Site on Ba=
ttery"," site ALARMIING  because gen stopped with high temp alarm // he add=
ed water in radiator and manually started and alarm clerared","olivier.kwed=
i@ihstowers.com","4","09-01-2025 10:04:08","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0004036753","Ema=
na","","09-01-2025 09:45:19","09-01-2025 09:40:13","09-01-2025 09:54:21","G=
rid outage, site went down before gen start due to poor battery backup // G=
en started automatically","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","lu=
divine.ngamaleu@ihstowers.com","307","09-01-2025 09:45:19","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0004036587","Man=
guiers Dispensaire","","09-01-2025 09:30:00","09-01-2025 09:26:54","09-01-2=
025 09:28:33","grid outage,gen failed to start due to grid contactor faulty=
//he blocked the contactor :site on grid ","Fabrice Pouakam","Equipment Rep=
air","Passive","Control Panel","ATS-AMF Issue","grid outage,gen failed to s=
tart due to grid contactor faulty//he blocked the contactor :site on grid "=
,"ludivine.ngamaleu@ihstowers.com","188","09-01-2025 09:30:00","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004036498","Akak-Nko=
zoa-MTN-IHS","","09-01-2025 09:14:20","09-01-2025 09:07:28","09-01-2025 09:=
12:34","Cascaded Incident from TTO4023692","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","grid Outage, Site down du=
e to poor backup // site on Gen ","system","262554","09-01-2025 09:14:20","=
Sagemcom CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0004036424","MEH=
ANDAN","","09-01-2025 08:59:46","09-01-2025 08:58:41","09-01-2025 09:44:37"=
,"site went down because gen start and stopped due to grid bad voltage and =
RCP on site // he bypass grid and manually start the gen","Albran Byorel","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","si=
te went down because gen start and stopped due to grid bad voltage and RCP =
on site // he bypass grid and manually start the gen","ludivine.ngamaleu@ih=
stowers.com","66","09-01-2025 08:59:46","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_311","NOCINC0004036325","Nkolda",""=
,"09-01-2025 08:40:56","","","grid outage, gen failed to start because  Psc=
3 disfunctionning//grid return","Albran Byorel","Warning","Warning","POWER"=
,"Warning - Battery Low Voltage","grid outage, gen failed to start because =
 Psc3 disfunctionning//grid return","olivier.kwedi@ihstowers.com","3","09-0=
1-2025 08:40:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004036320","Nsimalen=
 OCM","","09-01-2025 08:40:20","09-01-2025 08:34:37","09-01-2025 08:37:57",=
"Cascaded Incident from TTO4023485","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, gen failed to start b=
ecause  Psc3 disfunctionning//grid return","system","279078","09-01-2025 08=
:40:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004036301","N=
kolda","IHS_YND_327","09-01-2025 08:35:45","09-01-2025 08:34:37","09-01-202=
5 08:37:57","grid outage, gen failed to start because  Psc3 disfunctionning=
//grid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","grid outage, gen failed to start because  Psc3 disfunct=
ionning//grid return","dorothy.djantio@ihstowers.com","69","09-01-2025 08:3=
5:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004036214","M=
endong vallee","","09-01-2025 08:19:12","09-01-2025 08:16:07","09-01-2025 1=
2:49:04","Grid outage site went down because Gen over load (20KVA; 300A)  S=
S IHS F=E9lix Zamb=E9 is informed and confirmed//he reduice the load","Fand=
a Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage site went down because Gen over load (20KVA; 300A)  SS IHS F=E9lix Zam=
b=E9 is informed and confirmed//he reduice the load","dorothy.djantio@ihsto=
wers.com","186","09-01-2025 08:19:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004036152","MBIMBIM"=
,"IHS_YND_460, IHS_YND_475, IHS_YND_473","09-01-2025 08:04:20","09-01-2025 =
08:00:06","09-01-2025 09:02:22","No power issue on site site on solar with =
U=3D48,1v Tx fme Gregoire of huawei is informed","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site site on solar with U=3D48,1v Tx fme Gregoire of hu=
awei is informed","system","254","09-01-2025 08:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004036153","Matsari"=
,"","09-01-2025 08:04:20","09-01-2025 08:00:06","09-01-2025 08:35:08","Casc=
aded Incident from TTO4023288 - Cascade Removed From TTO4023288","Parker Tc=
houp","Cascade Outage","Active","Cascade Active","Cascade Active","No power=
 issue on site site on solar with U=3D48,1v Tx fme Gregoire of huawei is in=
formed","system","266689","09-01-2025 08:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004036154","Yoko MTN=
","","09-01-2025 08:04:20","09-01-2025 08:00:06","09-01-2025 08:35:08","Cas=
caded Incident from TTO4023288 - Cascade Removed From TTO4023288","Parker T=
choup","Cascade Outage","Active","Cascade Active","Cascade Active","No powe=
r issue on site site on solar with U=3D48,1v Tx fme Gregoire of huawei is i=
nformed","system","266689","09-01-2025 08:04:20","Sagemcom CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0004036149","Ngo=
um","","09-01-2025 08:03:11","09-01-2025 08:00:06","09-01-2025 08:35:08",""=
,"Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active=
","No power issue on site site on solar with U=3D48,1v Tx fme Gregoire of h=
uawei is informed","ludivine.ngamaleu@ihstowers.com","266690","09-01-2025 0=
8:03:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0004035977","Montee-J=
ouvence","","09-01-2025 07:34:21","09-01-2025 07:25:37","09-01-2025 07:39:3=
2","Cascaded Incident from TTO4023065","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage,gen stopped with a=
larm high temp//he added water in radiator","system","261532","09-01-2025 0=
7:34:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0004035959","M=
endong","IHS_YND_236","09-01-2025 07:32:42","09-01-2025 07:25:37","09-01-20=
25 07:39:32","grid outage,gen stopped with alarm high temp//he added water =
in radiator","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG=
 - High Engine Temp - Coolant Level Issue","grid outage,gen stopped with al=
arm high temp//he added water in radiator","dorothy.djantio@ihstowers.com",=
"426","09-01-2025 07:32:42","Sagemcom CMR"
"Closed Complete","Site Down","T0460","IHS_YND_201","NOCINC0004035813","Cit=
e Verte","","09-01-2025 07:13:04","09-01-2025 07:07:59","09-01-2025 08:54:1=
9","grid outage,No space to deploy a mobil gen// grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","grid outage,No sp=
ace to deploy a mobil gen// grid return","ludivine.ngamaleu@ihstowers.com",=
"306","09-01-2025 07:13:04","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0004035669","Men=
dong vallee","","09-01-2025 06:45:31","09-01-2025 06:40:01","09-01-2025 07:=
38:38","grid outage,site went down because Gen overload(20kva,300A)SS IHS F=
elix confirmed//he reduice the load","Fanda Brice","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","grid outage,site went down because Gen o=
verload(20kva,300A)SS IHS Felix confirmed//he reduice the load","ludivine.n=
gamaleu@ihstowers.com","425","09-01-2025 06:45:31","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004034722","Mon=
tee Jouvence","","09-01-2025 01:53:52","09-01-2025 01:52:37","09-01-2025 03=
:12:41","Grid outage, site went down because gen ran unill fuel shortage //=
 refuelling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage, site went down because gen ran unill fuel shortage /=
/ refuelling done","stephane.nkamwa@ihstowers.com","75","09-01-2025 01:53:5=
2","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0004034512","Eto=
 koss Yde","","09-01-2025 00:36:06","09-01-2025 00:33:45","09-01-2025 01:06=
:51"," grid outage, site went down because gen stopped with high temp alarm=
 // he added water in radiator and manually started","Fanda Brice","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Is=
sue"," grid outage, site went down because gen stopped with high temp alarm=
 // he added water in radiator and manually started","stephane.nkamwa@ihsto=
wers.com","143","09-01-2025 00:36:06","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004034295","NKO=
MEKUI OCM","","08-01-2025 23:27:29","08-01-2025 23:20:18","08-01-2025 23:29=
:08","Grid outage, site went down before gen start due to poor battery back=
up // Gen automatically started","TIENTCHEU NZETCHIEU GAEL","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite went down before gen start due to poor battery backup // Gen automatica=
lly started","stephane.nkamwa@ihstowers.com","432","08-01-2025 23:27:29","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004034167","S=
OA TOWN","","08-01-2025 23:02:52","08-01-2025 22:01:30","09-01-2025 01:29:3=
0","grid outage, site went down due to Gen overload (13KVA, 166A) // site s=
tabilized","Siligap Boris","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","grid outage, site went down due to G=
en overload (13KVA, 166A) // site stabilized","kouoh.jean@ihstowers.com","3=
683","08-01-2025 23:02:52","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0004034159","Men=
dong3","","08-01-2025 23:00:47","08-01-2025 22:48:37","08-01-2025 23:25:32"=
,"grid outage, no space to deploy a mobile gen // grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, no =
space to deploy a mobile gen // grid return","stephane.nkamwa@ihstowers.com=
","731","08-01-2025 23:00:47","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0004034151","Mba=
nkolo petit paris","","08-01-2025 22:58:40","08-01-2025 22:36:30","08-01-20=
25 23:52:46","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","grid outage, site went down because gen failed to star=
t due to alarm under voltage // He reset gen card and gen manually started"=
,"stephane.nkamwa@ihstowers.com","271453","08-01-2025 22:58:40","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004034141","ARMP",""=
,"08-01-2025 22:56:50","08-01-2025 21:14:41","08-01-2025 23:09:39","Cascade=
d Incident from TTO4020918","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","site went down due to insufficiency of rectifiers(Berna=
rd IHS confirm) // site stabilized","system","276369","08-01-2025 22:56:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004034140","Bastos B=
ir","","08-01-2025 22:56:50","08-01-2025 21:14:41","08-01-2025 23:09:39","C=
ascaded Incident from TTO4020918","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to insufficiency =
of rectifiers(Bernard IHS confirm) // site stabilized","system","276369","0=
8-01-2025 22:56:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004034135","D=
ragage","IHS_YND_704, IHS_YND_208","08-01-2025 22:55:56","08-01-2025 21:14:=
41","08-01-2025 23:09:39","site went down due to insufficiency of rectifier=
s(Bernard IHS confirm) // site stabilized","Mboua Thierry","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","site went down due to insuffic=
iency of rectifiers(Bernard IHS confirm) // site stabilized","kouoh.jean@ih=
stowers.com","10871","08-01-2025 22:55:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0004034103","A=
FEME NORD","IHS_YND_808","08-01-2025 22:46:44","08-01-2025 22:36:30","08-01=
-2025 23:52:46","grid outage, site went down because gen failed to start du=
e to alarm under voltage // He reset gen card and gen manually started","TI=
ENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","grid outage, site went down because gen failed to start due to=
 alarm under voltage // He reset gen card and gen manually started","kouoh.=
jean@ihstowers.com","615","08-01-2025 22:46:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0004033922","Mamch Bu=
ilding","","08-01-2025 21:58:20","08-01-2025 21:50:35","08-01-2025 22:39:35=
","Cascaded Incident from TTO4020630","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid Outage/ He deploy MDG of 20=
 Kva,","system","465","08-01-2025 21:58:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0004033910","C=
harles-Atangana","IHS_YND_051","08-01-2025 21:56:40","08-01-2025 21:50:35",=
"08-01-2025 22:41:06","Grid Outage/ He deploy MDG of 20 Kva,","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage/ He d=
eploy MDG of 20 Kva,","christian.fonkou@ihstowers.com","366","08-01-2025 21=
:56:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0004033861","M=
EHANDAN","","08-01-2025 21:48:12","08-01-2025 21:26:05","08-01-2025 22:45:0=
5","site went down due to disjunction of Cb(125A, 2*63A) in PWC  // He ream=
ed Cb(125A, 2*63A) , site on grid","Albran Byorel","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went dow=
n due to disjunction of Cb(125A, 2*63A) in PWC  // He reamed Cb(125A, 2*63A=
) , site on grid","christian.fonkou@ihstowers.com","1329","08-01-2025 21:48=
:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004033649","ELOUMDEM=
 CARRIERE 2","","08-01-2025 21:19:30","08-01-2025 21:17:17","08-01-2025 21:=
25:17","Cascaded Incident from TTO4020320","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because gen start and stopped due to grid bad voltage // voltage stabil=
ized","system","262024","08-01-2025 21:19:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004033648","Eto koss=
 Yde","","08-01-2025 21:19:30","08-01-2025 21:17:17","08-01-2025 21:25:17",=
"Cascaded Incident from TTO4020320","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause gen start and stopped due to grid bad voltage // voltage stabilized","=
system","262023","08-01-2025 21:19:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004033639","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","08-01-2025 21:18:25","08-01-2025 21:17=
:17","08-01-2025 21:25:17","Grid fluctuation, site went down because gen st=
art and stopped due to grid bad voltage // voltage stabilized","Fanda Brice=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation, site went down because gen start and stopped due to grid=
 bad voltage // voltage stabilized","emmanuel.ghani@ihstowers.com","70","08=
-01-2025 21:18:25","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004033386","NKO=
MEKUI OCM","","08-01-2025 20:34:42","08-01-2025 20:26:37","08-01-2025 21:10=
:37","ACTIVE//no power issue on site U=3D54.5 V site on Gen. Site impacted =
by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","ACTIVE//no power issue on site U=3D54.5 V site on Gen. Site impacte=
d by Mbankolo Camtel and not managing by IHS","emmanuel.ghani@ihstowers.com=
","486","08-01-2025 20:34:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004033140","SAA Entr=
ance","","08-01-2025 20:05:30","08-01-2025 19:53:02","08-01-2025 20:17:32",=
"Cascaded Incident from TTO4019725","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, site went down becaus=
e gen failed to start due to Start order cable cut // He normalized Cable a=
nd gen manually started","system","281222","08-01-2025 20:05:30","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004033141","Saa","",=
"08-01-2025 20:05:30","08-01-2025 19:53:02","08-01-2025 20:17:32","Cascaded=
 Incident from TTO4019725","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","grid outage, site went down because gen fai=
led to start due to Start order cable cut // He normalized Cable and gen ma=
nually started","system","281222","08-01-2025 20:05:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004033087","S=
AA 2","IHS_YND_542, IHS_YND_405","08-01-2025 19:59:11","08-01-2025 19:52:02=
","08-01-2025 20:17:32","grid outage, site went down because gen failed to =
start due to Start order cable cut // He normalized Cable and gen manually =
started","Parker Tchoup","Equipment Repair","Passive","Infrastructure","Arm=
oured Cable","grid outage, site went down because gen failed to start due t=
o Start order cable cut // He normalized Cable and gen manually started","c=
hristian.fonkou@ihstowers.com","430","08-01-2025 19:59:11","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004032992","NYO=
M FACE MAETUR","","08-01-2025 19:46:07","08-01-2025 19:37:02","08-01-2025 2=
1:08:02","Grid outage, Site went down because Gen failed to start due to Ge=
n card faulty// He started Gen manualy","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down =
because Gen failed to start due to Gen card faulty// He started Gen manualy=
","emmanuel.ghani@ihstowers.com","546","08-01-2025 19:46:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0004032906","N=
gousso-II","","08-01-2025 19:35:05","08-01-2025 19:24:43","08-01-2025 19:39=
:43","Grid outage, site went down because gen start and stopped due to high=
 temp // he added water and manually started","MFOUAGUEGUE MATHIEU","Cascad=
e Outage","Passive","Cascade Passive","Cascade Passive","Grid outage, site =
went down because gen start and stopped due to high temp // he added water =
and manually started","christian.fonkou@ihstowers.com","268876","08-01-2025=
 19:35:05","Sagemcom CMR"
"Closed Complete","Site Down","T1751","IHS_YND_213","NOCINC0004032869","Nko=
lmesseng","IHS_YND_190","08-01-2025 19:29:48","08-01-2025 19:24:43","08-01-=
2025 19:39:43","Grid outage, site went down because gen start and stopped d=
ue to high temp // he added water and manually started","Siligap Boris","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Grid outage, site went down because gen start and stopped due to=
 high temp // he added water and manually started","emmanuel.ghani@ihstower=
s.com","306","08-01-2025 19:29:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004032808","SOA VILL=
AGE","","08-01-2025 19:23:00","08-01-2025 19:17:02","08-01-2025 20:26:02","=
Cascaded Incident from TTO4019344","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause gen start and stopped due to grid bad voltage // he bypass grid and m=
anually start the gen","system","1218530","08-01-2025 19:23:00","Sagemcom C=
MR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0004032803","SOA=
 TOWN","IHS_YND_323","08-01-2025 19:22:07","08-01-2025 19:17:02","08-01-202=
5 20:26:02","Grid fluctuation, site went down because gen start and stopped=
 due to grid bad voltage // he bypass grid and manually start the gen","Sil=
igap Boris","Grid Supply","Passive","Grid","National Grid - Grid Outage Iss=
ue","Grid fluctuation, site went down because gen start and stopped due to =
grid bad voltage // he bypass grid and manually start the gen","emmanuel.gh=
ani@ihstowers.com","307","08-01-2025 19:22:07","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0004032734","Nko=
londom","","08-01-2025 19:10:31","08-01-2025 19:03:26","08-01-2025 20:30:26=
","Grid outage, site went down because gen fails to start due to gen card d=
isfunction // reset done and gen manually started","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site=
 went down because gen fails to start due to gen card disfunction // reset =
done and gen manually started","emmanuel.ghani@ihstowers.com","427","08-01-=
2025 19:10:31","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0004032558","Crf=
-Nsam","","08-01-2025 18:43:19","08-01-2025 18:35:53","08-01-2025 19:18:53"=
,"Site went down Because The Slot off Rectifier is overload // he reduced t=
he load and Gen manually started","MINKA NICOLAS","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module Overloaded","Site went down Because The S=
lot off Rectifier is overload // he reduced the load and Gen manually start=
ed","emmanuel.ghani@ihstowers.com","447","08-01-2025 18:43:19","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0004032455","S=
atcom","","08-01-2025 18:24:05","08-01-2025 18:19:59","08-01-2025 20:25:59"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","christian.fonkou@ihsto=
wers.com","247","08-01-2025 18:24:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_749","NOCINC0004032283","ODZA MIN=
KAN EDIBI ASSI","","08-01-2025 17:56:55","08-01-2025 17:34:30","08-01-2025 =
18:44:30","Cascaded Incident from TTO4018505","Albran Byorel","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","Active // No power issue on=
 site, site on grid Lionel steeve 655184876 of Huawei is working on site","=
system","268022","08-01-2025 17:56:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_283","NOCINC0004032284","Abome","=
","08-01-2025 17:56:55","08-01-2025 17:34:30","08-01-2025 18:44:30","Cascad=
ed Incident from TTO4018505","MINKA NICOLAS","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active // No power issue on site, site on gr=
id Lionel steeve 655184876 of Huawei is working on site","system","268031",=
"08-01-2025 17:56:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_253","NOCINC0004032281","Clge-Adv=
antiste","","08-01-2025 17:56:54","08-01-2025 17:34:30","08-01-2025 18:44:3=
0","Cascaded Incident from TTO4018505","MINKA NICOLAS","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active // No power issue on site, =
site on grid Lionel steeve 655184876 of Huawei is working on site","system"=
,"268021","08-01-2025 17:56:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_807","NOCINC0004032280","Ahala Ec=
hangeur","","08-01-2025 17:56:54","08-01-2025 17:34:30","08-01-2025 18:44:3=
0","Cascaded Incident from TTO4018505","MINKA NICOLAS","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active // No power issue on site, =
site on grid Lionel steeve 655184876 of Huawei is working on site","system"=
,"268021","08-01-2025 17:56:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_281","NOCINC0004032278","Odza II"=
,"","08-01-2025 17:56:54","08-01-2025 17:34:30","08-01-2025 18:44:30","Casc=
aded Incident from TTO4018505","Albran Byorel","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active // No power issue on site, site on =
grid Lionel steeve 655184876 of Huawei is working on site","system","268020=
","08-01-2025 17:56:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0004032282","Awae Ewo=
nkan","","08-01-2025 17:56:54","08-01-2025 17:34:30","08-01-2025 18:44:30",=
"Cascaded Incident from TTO4018505","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active // No power issue on site, sit=
e on grid Lionel steeve 655184876 of Huawei is working on site","system","2=
68022","08-01-2025 17:56:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_336","NOCINC0004032275","EKIE",""=
,"08-01-2025 17:56:53","08-01-2025 17:34:30","08-01-2025 18:44:30","Cascade=
d Incident from TTO4018505","Albran Byorel","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active // No power issue on site, site on gri=
d Lionel steeve 655184876 of Huawei is working on site","system","268023","=
08-01-2025 17:56:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0004032273","Ekoumdou=
m OCM","","08-01-2025 17:56:53","08-01-2025 17:34:30","08-01-2025 18:44:30"=
,"Cascaded Incident from TTO4018505","Albran Byorel","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active // No power issue on site, si=
te on grid Lionel steeve 655184876 of Huawei is working on site","system","=
268025","08-01-2025 17:56:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0004032274","Mvog-Man=
ga","","08-01-2025 17:56:53","08-01-2025 17:34:30","08-01-2025 18:44:30","C=
ascaded Incident from TTO4018505","Albran Byorel","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active // No power issue on site, site =
on grid Lionel steeve 655184876 of Huawei is working on site","system","268=
023","08-01-2025 17:56:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0004032277","Odza Min=
kan IHS","","08-01-2025 17:56:53","08-01-2025 17:34:30","08-01-2025 18:44:3=
0","Cascaded Incident from TTO4018505","Albran Byorel","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active // No power issue on site, =
site on grid Lionel steeve 655184876 of Huawei is working on site","system"=
,"268025","08-01-2025 17:56:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_160","NOCINC0004032269","Complex =
Beac II","","08-01-2025 17:56:52","08-01-2025 17:34:30","08-01-2025 18:44:3=
0","Cascaded Incident from TTO4018505","Albran Byorel","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active // No power issue on site, =
site on grid Lionel steeve 655184876 of Huawei is working on site","system"=
,"268031","08-01-2025 17:56:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0004032271","MEHANDAN=
","","08-01-2025 17:56:52","08-01-2025 17:34:30","08-01-2025 18:44:30","Cas=
caded Incident from TTO4018505","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active // No power issue on site, site on=
 grid Lionel steeve 655184876 of Huawei is working on site","system","26802=
8","08-01-2025 17:56:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0004032272","Nkolanga=
a","","08-01-2025 17:56:52","08-01-2025 17:34:30","08-01-2025 18:44:30","Ca=
scaded Incident from TTO4018505","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active // No power issue on site, sit=
e on grid Lionel steeve 655184876 of Huawei is working on site","system","2=
68029","08-01-2025 17:56:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0004032264","Mbedoumo=
u - Ekali","","08-01-2025 17:56:51","08-01-2025 17:34:30","08-01-2025 18:44=
:30","Cascaded Incident from TTO4018505","Albran Byorel","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active // No power issue on site=
, site on grid Lionel steeve 655184876 of Huawei is working on site","syste=
m","268028","08-01-2025 17:56:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_252","NOCINC0004032267","Koweit C=
ity","","08-01-2025 17:56:51","08-01-2025 17:34:30","08-01-2025 18:44:30","=
Cascaded Incident from TTO4018505","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active // No power issue on site, site=
 on grid Lionel steeve 655184876 of Huawei is working on site","system","26=
8027","08-01-2025 17:56:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_161","NOCINC0004032266","Sofavinc=
","","08-01-2025 17:56:51","08-01-2025 17:34:30","08-01-2025 18:44:30","Cas=
caded Incident from TTO4018505","MINKA NICOLAS","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active // No power issue on site, site on=
 grid Lionel steeve 655184876 of Huawei is working on site","system","26802=
6","08-01-2025 17:56:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0004032263","Carrefou=
rt Nkomo","","08-01-2025 17:56:51","08-01-2025 17:34:30","08-01-2025 18:44:=
30","Cascaded Incident from TTO4018505","Mba Lazare Herve","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active // No power issue on si=
te, site on grid Lionel steeve 655184876 of Huawei is working on site","sys=
tem","268022","08-01-2025 17:56:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_800","NOCINC0004032265","ODZA CIT=
E MBIA","","08-01-2025 17:56:51","08-01-2025 17:34:30","08-01-2025 18:44:30=
","Cascaded Incident from TTO4018505","Albran Byorel","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","Active // No power issue on site, s=
ite on grid Lionel steeve 655184876 of Huawei is working on site","system",=
"268030","08-01-2025 17:56:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0004032258","C-Suprem=
e","","08-01-2025 17:56:03","08-01-2025 17:43:59","08-01-2025 18:23:59","Ca=
scaded Incident from TTO4018664","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage site went down because Gen failed to s=
tart due to relay ge faulty // he bypass it and manually start the gen","sy=
stem","274863","08-01-2025 17:56:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0004032257","Acropole=
","","08-01-2025 17:56:03","08-01-2025 17:43:59","08-01-2025 18:23:59","Cas=
caded Incident from TTO4018664","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 failed to start due to relay ge faulty // he bypass it and manually start =
the gen","system","274863","08-01-2025 17:56:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0004032241","M=
vog Mbi New","IHS_YND_055, IHS_YND_036, IHS_YND_021","08-01-2025 17:54:04",=
"08-01-2025 17:43:59","08-01-2025 18:23:59","Grid outage site went down bec=
ause Gen failed to start due to relay ge faulty // he bypass it and manuall=
y start the gen","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","A=
CDG - Relay Faulty","Grid outage site went down because Gen failed to start=
 due to relay ge faulty // he bypass it and manually start the gen","christ=
ian.fonkou@ihstowers.com","606","08-01-2025 17:54:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0004032153","O=
lezoa OCM","","08-01-2025 17:47:15","08-01-2025 17:43:59","08-01-2025 18:23=
:59","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid outage site went down because Gen failed to start due to relay ge faul=
ty // he bypass it and manually start the gen","christian.fonkou@ihstowers.=
com","274863","08-01-2025 17:47:15","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0004032104","Tou=
ring Club International","IHS_YND_174, IHS_YND_343, IHS_YND_800, IHS_YND_16=
1, IHS_YND_252, IHS_YND_723, IHS_YND_160, IHS_YND_385, IHS_YND_528, IHS_YND=
_289, IHS_YND_291, IHS_YND_254, IHS_YND_336, IHS_YND_410, IHS_YND_715, IHS_=
YND_281, IHS_YND_595, IHS_YND_807, IHS_YND_253, IHS_YND_535, IHS_YND_749, I=
HS_YND_283","08-01-2025 17:39:37","08-01-2025 17:34:30","08-01-2025 19:20:3=
0","Active // No power issue on site, site on grid Lionel steeve 655184876 =
of Huawei is working on site","Albran Byorel","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active // No powe=
r issue on site, site on grid Lionel steeve 655184876 of Huawei is working =
on site","emmanuel.ghani@ihstowers.com","308","08-01-2025 17:39:37","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0004032079","E=
kounou","","08-01-2025 17:35:56","08-01-2025 17:33:49","08-01-2025 18:05:49=
","Grid outage, Site went down before Gen start due to poor backup// Gen st=
arted manually","Albran Byorel","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup// Gen started manually","christian.fonkou@ihstowers.c=
om","128","08-01-2025 17:35:56","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004031657","Nko=
lafeme","","08-01-2025 16:49:48","08-01-2025 16:48:24","08-01-2025 17:38:24=
","Grid outage, site went down because gen fails to srtart due to gen overl=
oad(20Kva, 375A) // grid return","TIENTCHEU NZETCHIEU GAEL","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down bec=
ause gen fails to srtart due to gen overload(20Kva, 375A) // grid return","=
emmanuel.ghani@ihstowers.com","85","08-01-2025 16:49:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0004031627","Nsimalen=
 OCM","","08-01-2025 16:42:20","08-01-2025 16:36:13","08-01-2025 17:24:13",=
"Cascaded Incident from TTO4017869","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","	site went down because Gen fails =
to start due to Grid bad voltage, no rcp on site // Grid stabilized","syste=
m","286073","08-01-2025 16:42:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0004031588","N=
kolda","IHS_YND_327","08-01-2025 16:39:22","08-01-2025 16:36:13","08-01-202=
5 17:24:13","	site went down because Gen fails to start due to Grid bad vol=
tage, no rcp on site // Grid stabilized","Albran Byorel","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","	site went down bec=
ause Gen fails to start due to Grid bad voltage, no rcp on site // Grid sta=
bilized","christian.fonkou@ihstowers.com","190","08-01-2025 16:39:22","Sage=
mcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0004031557","Beh=
ind P T school Yde","","08-01-2025 16:35:21","08-01-2025 16:33:49","08-01-2=
025 17:47:27","Grid outage, site went down because gen stopped with emergen=
cy stop // grid restored","Paul BIBOUM","Equipment Repair","Passive","ACDG =
Gen","ACDG - Emergency Stop","Grid outage, site went down because gen stopp=
ed with emergency stop // grid restored","emmanuel.ghani@ihstowers.com","93=
","08-01-2025 16:35:21","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0004031465","Mes=
sa Carriere","","08-01-2025 16:20:46","08-01-2025 16:19:24","08-01-2025 16:=
44:24","Grid outage, site went down because gen fails to start due to no au=
tomatism on site // gen manually started","Mboua Thierry","Equipment Repair=
","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down be=
cause gen fails to start due to no automatism on site // gen manually start=
ed","emmanuel.ghani@ihstowers.com","83","08-01-2025 16:20:46","Sagemcom CMR=
"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004031431","BIY=
EMASSI NIKI","","08-01-2025 16:15:32","08-01-2025 16:09:27","08-01-2025 17:=
39:27","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Site =
stabilized","emmanuel.ghani@ihstowers.com","366","08-01-2025 16:15:32","Sag=
emcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0004031189","Nko=
lnda","","08-01-2025 15:50:59","08-01-2025 15:49:51","08-01-2025 17:08:51",=
"Grid outage, site went down because gen ran unill fuel shortage // refuell=
ing done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran unill fuel shortage // refuell=
ing done","emmanuel.ghani@ihstowers.com","69","08-01-2025 15:50:59","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004029444","C=
rf-Nsam","","08-01-2025 14:50:21","08-01-2025 14:46:16","08-01-2025 15:02:1=
6","Site went down Because The Slot off Rectifier is overload // he reduced=
 the load and Gen manually started","MINKA NICOLAS","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module Overloaded","Site went down Because The=
 Slot off Rectifier is overload //he reduced the load and Gen manually star=
ted","christian.fonkou@ihstowers.com","246","08-01-2025 14:50:21","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004028775","M=
imboman-Ecole","","08-01-2025 14:26:56","08-01-2025 14:24:51","08-01-2025 2=
0:27:51","Active//No power issue on site Ubaie=3D53.4V site on Grid The Tx =
Fme Eloundou/693212405 of huawei is informed","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site Ubaie=3D53.4V site on Grid The Tx Fme Elou=
ndou/693212405 of huawei is informed","christian.fonkou@ihstowers.com","126=
","08-01-2025 14:26:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_190","NOCINC0004028605","Ngousso-=
II","","08-01-2025 14:14:31","08-01-2025 14:07:35","08-01-2025 14:30:29","C=
ascaded Incident from TTO4014401","MFOUAGUEGUE MATHIEU","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site on gen due to grid outage=
, site went down because gen stopped due to high temp alarm // he added wat=
er and manually start the gen","system","1215659","08-01-2025 14:14:31","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0004028591","N=
kolmesseng","IHS_YND_190","08-01-2025 14:13:14","08-01-2025 14:06:35","08-0=
1-2025 14:30:35","Site on gen due to grid outage, site went down because ge=
n stopped due to high temp alarm // he added water and manually start the g=
en","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - High En=
gine Temp - Coolant Level Issue","Site on gen due to grid outage, site went=
 down because gen stopped due to high temp alarm // he added water and manu=
ally start the gen","christian.fonkou@ihstowers.com","748","08-01-2025 14:1=
3:14","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0004028366","N=
yanon","","08-01-2025 13:36:22","08-01-2025 13:23:15","08-01-2025 13:45:19"=
,"Active //No power issue, site on Gen  With Ubaie=3D55V,  Gregoire (654547=
479) from Huawei is informed ","TIENTCHEU NZETCHIEU GAEL","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e //No power issue, site on Gen  With Ubaie=3D55V,  Gregoire (654547479) fr=
om Huawei is informed ","rouselle.schoune@ihstowers.com","821","08-01-2025 =
13:36:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_043","NOCINC0004028278","Emia",""=
,"08-01-2025 13:18:46","08-01-2025 13:05:29","08-01-2025 13:28:57","Cascade=
d Incident from TTO4013930","","Cascade Outage","Active","Cascade Active","=
Cascade Active","No power issue on site U=3D52,1v site on grid site down be=
cause is imapcted by Ngoa Ekelle New and not managing by IHS","system","262=
624","08-01-2025 13:18:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_225","NOCINC0004028281","Science"=
,"","08-01-2025 13:18:46","08-01-2025 13:05:29","08-01-2025 13:28:57","Casc=
aded Incident from TTO4013930","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue on site U=3D52,1=
v site on grid site down because is imapcted by Ngoa Ekelle New and not man=
aging by IHS","system","262632","08-01-2025 13:18:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_032","NOCINC0004028279","Kamajou =
Building","","08-01-2025 13:18:46","08-01-2025 13:05:29","08-01-2025 13:28:=
57","Cascaded Incident from TTO4013930","Paul BIBOUM","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue on site U=3D52,1v si=
te on grid site down because is imapcted by Ngoa Ekelle New and not managin=
g by IHS","system","262632","08-01-2025 13:18:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0004028282","Dagobert=
","","08-01-2025 13:18:46","08-01-2025 13:05:29","08-01-2025 13:28:57","Cas=
caded Incident from TTO4013930","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D52,=
1v site on grid site down because is imapcted by Ngoa Ekelle New and not ma=
naging by IHS","system","262633","08-01-2025 13:18:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_085","NOCINC0004028280","Briquete=
rie","","08-01-2025 13:18:46","08-01-2025 13:05:29","08-01-2025 13:28:57","=
Cascaded Incident from TTO4013930","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","No power issue on site U=3D52,1v site on grid site =
down because is imapcted by Ngoa Ekelle New and not managing by IHS","syste=
m","262624","08-01-2025 13:18:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_140","NOCINC0004028277","BISCUITE=
RIE","","08-01-2025 13:18:45","08-01-2025 13:05:29","08-01-2025 13:28:57","=
Cascaded Incident from TTO4013930","Paul BIBOUM","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site U=3D52,1v site on=
 grid site down because is imapcted by Ngoa Ekelle New and not managing by =
IHS","system","262631","08-01-2025 13:18:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_061","NOCINC0004028275","Yde Univ=
ersity","","08-01-2025 13:18:45","08-01-2025 13:05:29","08-01-2025 13:28:57=
","Cascaded Incident from TTO4013930","Paul BIBOUM","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D52,1v site=
 on grid site down because is imapcted by Ngoa Ekelle New and not managing =
by IHS","system","262623","08-01-2025 13:18:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0004028276","Crf-Nkol=
bisson","","08-01-2025 13:18:45","08-01-2025 13:05:29","08-01-2025 13:28:57=
","Cascaded Incident from TTO4013930","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D52,1v site on grid site down because is imapcted by Ngoa Ekelle New and =
not managing by IHS","system","262631","08-01-2025 13:18:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0004028274","Yona Hot=
el","","08-01-2025 13:18:45","08-01-2025 13:05:29","08-01-2025 13:28:57","C=
ascaded Incident from TTO4013930","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site U=3D5=
2,1v site on grid site down because is imapcted by Ngoa Ekelle New and not =
managing by IHS","system","262630","08-01-2025 13:18:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0004028272","Scalom",=
"","08-01-2025 13:18:44","08-01-2025 13:05:29","08-01-2025 13:28:57","Casca=
ded Incident from TTO4013930","Paul BIBOUM","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site U=3D52,1v site on grid=
 site down because is imapcted by Ngoa Ekelle New and not managing by IHS",=
"system","262635","08-01-2025 13:18:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_078","NOCINC0004028271","An-March=
e-Melen","","08-01-2025 13:18:44","08-01-2025 13:05:29","08-01-2025 13:28:5=
7","Cascaded Incident from TTO4013930","","Cascade Outage","Active","Cascad=
e Active","Cascade Active","No power issue on site U=3D52,1v site on grid s=
ite down because is imapcted by Ngoa Ekelle New and not managing by IHS","s=
ystem","262627","08-01-2025 13:18:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_141","NOCINC0004028273","New-Marc=
he-Melen","","08-01-2025 13:18:44","08-01-2025 13:05:29","08-01-2025 13:28:=
57","Cascaded Incident from TTO4013930","Paul BIBOUM","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue on site U=3D52,1v si=
te on grid site down because is imapcted by Ngoa Ekelle New and not managin=
g by IHS","system","262623","08-01-2025 13:18:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0004028270","Sapeur",=
"","08-01-2025 13:18:44","08-01-2025 13:05:29","08-01-2025 13:28:57","Casca=
ded Incident from TTO4013930","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site U=3D52,1v site on gr=
id site down because is imapcted by Ngoa Ekelle New and not managing by IHS=
","system","262635","08-01-2025 13:18:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0004028267","Oyomaban=
g Ecole","","08-01-2025 13:18:43","08-01-2025 13:05:29","08-01-2025 13:28:5=
7","Cascaded Incident from TTO4013930","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Active","Cascade Active","Cascade Active","No power issue on site =
U=3D52,1v site on grid site down because is imapcted by Ngoa Ekelle New and=
 not managing by IHS","system","262626","08-01-2025 13:18:43","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_073","NOCINC0004028266","Chapelle=
-Obili","","08-01-2025 13:18:43","08-01-2025 13:05:29","08-01-2025 13:28:57=
","Cascaded Incident from TTO4013930","Paul BIBOUM","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D52,1v site=
 on grid site down because is imapcted by Ngoa Ekelle New and not managing =
by IHS","system","262634","08-01-2025 13:18:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0004028269","Meyong-M=
eyeme","","08-01-2025 13:18:43","08-01-2025 13:05:29","08-01-2025 13:28:57"=
,"Cascaded Incident from TTO4013930","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D52,1v site on grid site down because is imapcted by Ngoa Ekelle New and =
not managing by IHS","system","262627","08-01-2025 13:18:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_090","NOCINC0004028268","BATA-Mok=
olo","","08-01-2025 13:18:43","08-01-2025 13:05:29","08-01-2025 13:28:57","=
Cascaded Incident from TTO4013930","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","No power issue on site U=3D52,1v site on grid site =
down because is imapcted by Ngoa Ekelle New and not managing by IHS","syste=
m","262634","08-01-2025 13:18:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_044","NOCINC0004028264","Polytech=
nique","","08-01-2025 13:18:42","08-01-2025 13:05:29","08-01-2025 13:28:57"=
,"Cascaded Incident from TTO4013930","","Cascade Outage","Active","Cascade =
Active","Cascade Active","No power issue on site U=3D52,1v site on grid sit=
e down because is imapcted by Ngoa Ekelle New and not managing by IHS","sys=
tem","262629","08-01-2025 13:18:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_088","NOCINC0004028263","Elobi Mo=
kolo","","08-01-2025 13:18:42","08-01-2025 13:05:29","08-01-2025 13:28:57",=
"Cascaded Incident from TTO4013930","Mboua Thierry","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D52,1v site=
 on grid site down because is imapcted by Ngoa Ekelle New and not managing =
by IHS","system","262636","08-01-2025 13:18:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0004028265","Cite-Ver=
te","","08-01-2025 13:18:42","08-01-2025 13:05:29","08-01-2025 13:28:57","C=
ascaded Incident from TTO4013930","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","No power issue on site U=3D52,1v site on grid site d=
own because is imapcted by Ngoa Ekelle New and not managing by IHS","system=
","262625","08-01-2025 13:18:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_059","NOCINC0004028262","E-Poste =
2","","08-01-2025 13:18:42","08-01-2025 13:05:29","08-01-2025 13:28:57","Ca=
scaded Incident from TTO4013930","Paul BIBOUM","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site U=3D52,1v site on g=
rid site down because is imapcted by Ngoa Ekelle New and not managing by IH=
S","system","262630","08-01-2025 13:18:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0004028258","BONAS YD=
E","","08-01-2025 13:18:41","08-01-2025 13:05:29","08-01-2025 13:28:57","Ca=
scaded Incident from TTO4013930","Paul BIBOUM","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site U=3D52,1v site on g=
rid site down because is imapcted by Ngoa Ekelle New and not managing by IH=
S","system","262625","08-01-2025 13:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_041","NOCINC0004028261","Lycee Le=
clerc School","","08-01-2025 13:18:41","08-01-2025 13:05:29","08-01-2025 13=
:28:57","Cascaded Incident from TTO4013930","Paul BIBOUM","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue on site U=3D52,1=
v site on grid site down because is imapcted by Ngoa Ekelle New and not man=
aging by IHS","system","262636","08-01-2025 13:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_226","NOCINC0004028259","Mvog-Bet=
si","","08-01-2025 13:18:41","08-01-2025 13:05:29","08-01-2025 13:28:57","C=
ascaded Incident from TTO4013930","Hyemafo Gildas","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D52,1v site =
on grid site down because is imapcted by Ngoa Ekelle New and not managing b=
y IHS","system","262634","08-01-2025 13:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0004028260","AFEME NO=
RD","","08-01-2025 13:18:41","08-01-2025 13:05:29","08-01-2025 13:28:57","C=
ascaded Incident from TTO4013930","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site U=3D5=
2,1v site on grid site down because is imapcted by Ngoa Ekelle New and not =
managing by IHS","system","262629","08-01-2025 13:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_233","NOCINC0004028256","Oyomaban=
g OCM","","08-01-2025 13:18:40","08-01-2025 13:05:29","08-01-2025 13:28:57"=
,"Cascaded Incident from TTO4013930","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D52,1v site on grid site down because is imapcted by Ngoa Ekelle New and =
not managing by IHS","system","262628","08-01-2025 13:18:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0004028257","Nkolbi-B=
oss","","08-01-2025 13:18:40","08-01-2025 13:05:29","08-01-2025 13:28:57","=
Cascaded Incident from TTO4013930","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","No power issue on site U=3D=
52,1v site on grid site down because is imapcted by Ngoa Ekelle New and not=
 managing by IHS","system","262633","08-01-2025 13:18:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0004028207","S=
hell-Nsimeyong","IHS_YND_233, IHS_YND_273, IHS_YND_683, IHS_YND_226, IHS_YN=
D_519, IHS_YND_041, IHS_YND_059, IHS_YND_088, IHS_YND_044, IHS_YND_202, IHS=
_YND_073, IHS_YND_686, IHS_YND_090, IHS_YND_230, IHS_YND_029, IHS_YND_078, =
IHS_YND_071, IHS_YND_141, IHS_YND_271, IHS_YND_061, IHS_YND_232, IHS_YND_14=
0, IHS_YND_043, IHS_YND_032, IHS_YND_085, IHS_YND_225, IHS_YND_286","08-01-=
2025 13:12:32","08-01-2025 13:05:29","08-01-2025 13:28:57","No power issue =
on site U=3D52,1v site on grid site down because is imapcted by Ngoa Ekelle=
 New and not managing by IHS","MINKA NICOLAS","Customer Equipment Failure",=
"Active","Active Equipment Failure","Affected by 3rd Party Site","No power =
issue on site U=3D52,1v site on grid site down because is imapcted by Ngoa =
Ekelle New and not managing by IHS","rouselle.schoune@ihstowers.com","425",=
"08-01-2025 13:12:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_721","NOCINC0004028118","VOIRIE M=
UNICIPALE YAOUNDE","","08-01-2025 13:01:20","08-01-2025 12:54:10","08-01-20=
25 13:18:48","Cascaded Incident from TTO4013818","Paul BIBOUM","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D52,6v site on grid Hosiah of huawei is informed","system","263485","08-0=
1-2025 13:01:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0004028112","E=
NAM","IHS_YND_721","08-01-2025 13:00:18","08-01-2025 12:54:10","08-01-2025 =
13:56:48","No power issue on site U=3D52,6v site on grid Hosiah of huawei i=
s informed","","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","No power issue on site U=3D52,6v site on grid Ho=
siah of huawei is informed","rouselle.schoune@ihstowers.com","371","08-01-2=
025 13:00:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0004028012","M=
imboman-Ecole","","08-01-2025 12:39:49","08-01-2025 12:36:38","08-01-2025 1=
3:29:32","Active//No power issue on site Ubaie=3D53.4V site on Grid The Tx =
Fme Eloundou/693212405 of huawei is informed and Site UP at 12.39 PM","Mba =
Lazare Herve","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active//No power issue on site Ubaie=3D53.4V site=
 on Grid The Tx Fme Eloundou/693212405 of huawei is informed and Site UP at=
 12.39 PM","rouselle.schoune@ihstowers.com","192","08-01-2025 12:39:49","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0004027275","N=
sam Sofavinc T0","","08-01-2025 11:23:57","08-01-2025 11:19:52","08-01-2025=
 11:59:49","Grid outage,site went down because  Gen ran until fuel shortage=
//Refueling done","MINKA NICOLAS","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage,site went down because  Gen ran until fuel shortage//R=
efueling done","rouselle.schoune@ihstowers.com","246","08-01-2025 11:23:57"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0004027249","S=
AA 2","","08-01-2025 11:19:12","08-01-2025 11:15:07","08-01-2025 12:45:14",=
"Site went down due to work SS IHS Felix Bateur is are working on Site//End=
 Off work","Parker Tchoup","Equipment Replacement","Passive","Planned Activ=
ity","Planned Activity - Passive","Site went down due to work SS IHS Felix =
Bateur is are working on Site//End Off work","rouselle.schoune@ihstowers.co=
m","246","08-01-2025 11:19:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004026608","B=
iteng-Maetur","","08-01-2025 09:38:47","08-01-2025 09:29:59","08-01-2025 10=
:22:10","grid outage,site went down because Gen overload (20kv,260A)SS IHS =
Blaise confirmed//he reduice the load on site","Mba Lazare Herve","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","grid outage,site went dow=
n because Gen overload (20kv,260A)SS IHS Blaise confirmed//he reduice the l=
oad on site","rouselle.schoune@ihstowers.com","530","08-01-2025 09:38:47","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004026058","Yoko MTN=
","","08-01-2025 08:03:21","08-01-2025 07:50:39","08-01-2025 08:20:33","Cas=
caded Incident from TTO4011349","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site U=3D53,9v site on =
gen Tx Gregoire of huawei is informed","system","267245","08-01-2025 08:03:=
21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004026057","Ngoum","=
","08-01-2025 08:03:20","08-01-2025 07:50:39","08-01-2025 08:20:33","Cascad=
ed Incident from TTO4011349","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site U=3D53,9v site on gen=
 Tx Gregoire of huawei is informed","system","267245","08-01-2025 08:03:20"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004026056","Matsari"=
,"","08-01-2025 08:03:20","08-01-2025 07:50:39","08-01-2025 08:20:33","Casc=
aded Incident from TTO4011349","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site U=3D53,9v site on g=
en Tx Gregoire of huawei is informed","system","267245","08-01-2025 08:03:2=
0","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0004026041","MBI=
MBIM","IHS_YND_460, IHS_YND_475, IHS_YND_473","08-01-2025 08:01:46","08-01-=
2025 07:50:39","08-01-2025 08:37:03","No power issue on site U=3D53,9v site=
 on gen Tx Gregoire of huawei is informed","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site U=3D53,9v site on gen Tx Gregoire of huawei is informed"=
,"ange.kongo@ihstowers.com","669","08-01-2025 08:01:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004025918","M=
balla 4","","08-01-2025 07:31:58","08-01-2025 07:04:57","08-01-2025 07:59:0=
3","Active// no power issue, U=3D54,3V on grid, The Tx fme synphorien/67529=
5205 from huawei is informed","Delor Telezing","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// no powe=
r issue, U=3D54,3V on grid, The Tx fme synphorien/675295205 from huawei is =
informed","rouselle.schoune@ihstowers.com","1661","08-01-2025 07:31:58","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004025858","ODZ=
A MINKAN EDIBI ASSI","","08-01-2025 07:18:22","08-01-2025 07:15:18","08-01-=
2025 08:57:53","ACTIVE//No power issue on site ,site on Grid with Ubaie=3D =
54,6V The Tx FME Leonel Adjep /655184876/From HUAWEI is informed and Site U=
P at 08:11 AM","Albran Byorel","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue on site ,=
site on Grid with Ubaie=3D 54,6V The Tx FME Leonel Adjep /655184876/From HU=
AWEI is informed and Site UP at 08:11 AM","ange.kongo@ihstowers.com","185",=
"08-01-2025 07:18:22","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0004025620","Eko=
unou","","08-01-2025 06:28:44","08-01-2025 06:23:37","08-01-2025 06:39:59",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
ted automatically","Albran Byorel","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen started automatically","ange.kongo@ihstowers=
.com","309","08-01-2025 06:28:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0004025608","M=
ontee-Des-Soeurs","","08-01-2025 06:26:34","08-01-2025 06:23:51","08-01-202=
5 07:21:59","Grid outage, Site went down before Gen start due to poor backu=
p// Gen started manually","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen started manually","rouselle.schoune@=
ihstowers.com","164","08-01-2025 06:26:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004025443","D=
ong","","08-01-2025 05:49:54","08-01-2025 05:41:51","08-01-2025 05:50:04","=
Active: No power issue, site on Battery  With Ubaie=3D50,3V,  Gregoire (654=
547479) from Huawei is informed and Up at 05:57 AM","Parker Tchoup","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: No power issue, site on Battery  With Ubaie=3D50,3V,  Gregoire=
 (654547479) from Huawei is informed and Up at 05:57 AM","alexandre.kamal@i=
hstowers.com","485","08-01-2025 05:49:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004024393","M=
balla 4","","07-01-2025 23:34:54","07-01-2025 23:26:50","07-01-2025 23:30:2=
8","Active// no power issue, U=3D54,3V on grid, The Tx fme synphorien/67529=
5205 from huawei is informed","Delor Telezing","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// no powe=
r issue, U=3D54,3V on grid, The Tx fme synphorien/675295205 from huawei is =
informed","alexandre.kamal@ihstowers.com","485","07-01-2025 23:34:54","Sage=
mcom CMR"
"Closed Complete","Site Down","T0319","IHS_YND_278","NOCINC0004023920","Nko=
lfoulou 2","","07-01-2025 22:00:31","07-01-2025 21:30:21","07-01-2025 21:35=
:17","wrongly ticket","Siligap Boris","Incorrectly Logged Tickets","Error",=
"Error","Error","wrongly ticket","stephane.nkamwa@ihstowers.com","1811","07=
-01-2025 22:00:31","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004023891","Bit=
eng-Maetur","","07-01-2025 21:55:49","07-01-2025 18:33:41","07-01-2025 19:3=
6:22","Grid outage, site went down due to Gen overload Gen overload(20KVA, =
280A)//Grid return","Mba Lazare Herve","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Grid outage, site went down due to Gen overload Gen =
overload(20KVA, 280A)//Grid return","stephane.nkamwa@ihstowers.com","12129"=
,"07-01-2025 21:55:49","Sagemcom CMR"
"Closed Complete","Warning","T0104","IHS_YND_113","NOCINC0004023496","Emomb=
o 2","","07-01-2025 20:44:15","","","site alarm because disfunctionning of =
02/04 rectifiers due to grid bad voltage // He reset rectifiers, site on gr=
id","MINKA NICOLAS","Warning","Warning","POWER","Warning - Rectifier Module=
","site alarm because disfunctionning of 02/04 rectifiers due to grid bad v=
oltage // He reset rectifiers, site on grid","nadjia.njaya@ihstowers.com","=
249","07-01-2025 20:44:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004023415","SOA VILL=
AGE","","07-01-2025 20:30:00","07-01-2025 20:22:21","07-01-2025 20:53:22","=
Cascaded Incident from TTO4008202","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because gen start an=
d stopped due to grid fluctuation // He bypassed grid and gen manually star=
ted","system","272317","07-01-2025 20:30:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004023392","S=
OA TOWN","IHS_YND_323","07-01-2025 20:26:29","07-01-2025 20:22:21","07-01-2=
025 20:53:22","site went down because gen start and stopped due to grid flu=
ctuation // He bypassed grid and gen manually started","Siligap Boris","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","site =
went down because gen start and stopped due to grid fluctuation // He bypas=
sed grid and gen manually started","kouoh.jean@ihstowers.com","249","07-01-=
2025 20:26:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0004023382","N=
kolondom","","07-01-2025 20:25:11","07-01-2025 20:21:05","07-01-2025 21:58:=
55","Grid fluctuation, site went down because Gen fails to start due to Gri=
d bad voltage no rcp // he bypass Grid and manually start the Gen","Fabrice=
 Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation, site went down because Gen fails to start due to=
 Grid bad voltage no rcp // he bypass Grid and manually start the Gen","kou=
oh.jean@ihstowers.com","248","07-01-2025 20:25:11","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004023311","NYO=
M FACE MAETUR","","07-01-2025 20:19:05","07-01-2025 19:56:56","07-01-2025 2=
3:23:11","Grid outage, Site went down because Gen failed to start due to Ge=
n card faulty// He started Gen manualy","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down =
because Gen failed to start due to Gen card faulty// He started Gen manualy=
","stephane.nkamwa@ihstowers.com","1330","07-01-2025 20:19:05","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004023193","C=
rf-Nsam","","07-01-2025 20:01:10","07-01-2025 19:53:02","07-01-2025 20:06:5=
1","Site went down Because The Slot off Rectifier is overload //he reduced =
the load and Gen manually started","MINKA NICOLAS","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Site went down Because The =
Slot off Rectifier is overload //he reduced the load and Gen manually start=
ed","kouoh.jean@ihstowers.com","489","07-01-2025 20:01:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004022997","M=
balla 4","","07-01-2025 19:32:32","07-01-2025 19:27:28","07-01-2025 19:30:0=
6","Active: no power issue, site is on grid with Ubaie=3D53V, Synphorien(69=
1316854) from Huawei is informed","Delor Telezing","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no p=
ower issue, site is on grid with Ubaie=3D53V, Synphorien(691316854) from Hu=
awei is informed","kouoh.jean@ihstowers.com","305","07-01-2025 19:32:32","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0004022783","S=
OA UNIVERSITY STADIUM","","07-01-2025 18:55:50","07-01-2025 18:54:41","07-0=
1-2025 19:07:38","site went down due to dysfunctioning of PWC ZTE // Grid r=
eturn","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier =
Module Overloaded","site went down due to the dysfunctioning of PWC ZTE // =
Grid return","kouoh.jean@ihstowers.com","70","07-01-2025 18:55:50","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0004022703","A=
wae Escalier","","07-01-2025 18:43:30","07-01-2025 18:29:22","07-01-2025 18=
:45:54","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen start automatically","Albran Byorel","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // Gen start automatically"=
,"kouoh.jean@ihstowers.com","849","07-01-2025 18:43:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0004022601","N=
yom OCM","","07-01-2025 18:18:53","07-01-2025 17:04:45","07-01-2025 17:08:4=
5","No power issue site on Gen with U=3D54,4V Symphorien(691316854) from Hu=
awei is informed,site up at 06:29 pm","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on Gen with U=3D54,4V Symphorien(691316854) from Huawei is inf=
ormed,site up at 06:29 pm","kouoh.jean@ihstowers.com","4450","07-01-2025 18=
:18:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004022368","M=
essa-Carriere OCM","","07-01-2025 17:35:13","07-01-2025 17:27:01","07-01-20=
25 17:30:06","No power issue on site U=3D52v site on grid Tx fme Mohamadou =
of huawei is informed","","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52v site o=
n grid Tx fme Mohamadou of huawei is informed","kouoh.jean@ihstowers.com","=
494","07-01-2025 17:35:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0004022122","Essomba"=
,"","07-01-2025 16:55:10","07-01-2025 16:14:02","07-01-2025 17:06:06","Casc=
aded Incident from TTO4005780","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, site went down due to d=
isfunctionning of PWC ZTE( supervisor Blaise  from IHS confirm) // He reduc=
ed the load, site on grid","system","273025","07-01-2025 16:55:10","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0004022121","AWAE OCM=
","","07-01-2025 16:55:10","07-01-2025 16:14:02","07-01-2025 17:06:06","Cas=
caded Incident from TTO4005780","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, site went down due to =
disfunctionning of PWC ZTE( supervisor Blaise  from IHS confirm) // He redu=
ced the load, site on grid","system","273026","07-01-2025 16:55:10","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0004022119","Bitoto",=
"","07-01-2025 16:55:10","07-01-2025 16:14:02","07-01-2025 17:06:06","Casca=
ded Incident from TTO4005780","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, site went down due to di=
sfunctionning of PWC ZTE( supervisor Blaise  from IHS confirm) // He reduce=
d the load, site on grid","system","273026","07-01-2025 16:55:10","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0004022120","Tradex-N=
komo","","07-01-2025 16:55:10","07-01-2025 16:14:02","07-01-2025 17:06:06",=
"Cascaded Incident from TTO4005780","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, site went down due to=
 disfunctionning of PWC ZTE( supervisor Blaise  from IHS confirm) // He red=
uced the load, site on grid","system","273027","07-01-2025 16:55:10","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004021876","Akak-Nko=
zoa-MTN-IHS","","07-01-2025 16:18:40","07-01-2025 16:13:46","07-01-2025 16:=
28:55","Cascaded Incident from TTO4006345","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid Outage , site down d=
ue to poor backup   //  Grid Return","system","273052","07-01-2025 16:18:40=
","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004021506","Nko=
g-Edzen","","07-01-2025 15:24:52","07-01-2025 15:07:44","07-01-2025 15:30:5=
2","grid outage, site went down because gen start and stopped due to radiat=
or perced // He added water in radiator and gen manuallys started","Parker =
Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","grid out=
age, site went down because gen start and stopped due to radiator perced //=
 He added water in radiator and gen manuallys started","stephane.nkamwa@ihs=
towers.com","1029","07-01-2025 15:24:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0004021488","B=
iteng-Maetur","","07-01-2025 15:20:26","07-01-2025 15:13:08","07-01-2025 17=
:00:25","Grid outage, site went down due to Gen overload Gen overload(20KVA=
, 280A) (Alpjhose IHS confirm)// grid return","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went dow=
n due to Gen overload Gen overload(20KVA, 280A) (Alpjhose IHS confirm)// gr=
id return","kouoh.jean@ihstowers.com","440","07-01-2025 15:20:26","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0004021314","Bit=
eng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179","07-01-2025 14:54=
:38","07-01-2025 14:45:34","07-01-2025 17:06:06","grid outage, site went do=
wn due to disfunctionning of PWC ZTE( supervisor Blaise  from IHS confirm) =
// He reduced the load, site on grid","Mba Lazare Herve","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module Overloaded","grid outage, site wen=
t down due to disfunctionning of PWC ZTE( supervisor Blaise  from IHS confi=
rm) // He reduced the load, site on grid","stephane.nkamwa@ihstowers.com","=
545","07-01-2025 14:54:38","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0004021293","Obo=
bogo","","07-01-2025 14:51:08","07-01-2025 14:42:59","07-01-2025 15:24:35",=
"Grid fluctuation,site went down before gen starts due to poor battery back=
up// grid return","MINKA NICOLAS","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid fluctuation,site went down before g=
en starts due to poor battery backup// grid return","stephane.nkamwa@ihstow=
ers.com","490","07-01-2025 14:51:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_369","IHS_YND_019","NOCINC0004020917","H=
otel de Ville Yde","","07-01-2025 13:58:52","07-01-2025 13:56:47","07-01-20=
25 14:32:48","site went down due to disjunction Cb(2*80A) in DC boss OMC //=
 he made the bridge of Cb(2*80 A) with a another of Cb(2*80A), site on grid=
","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet=
 - Circuit Breaker Issue","site went down due to disjunction Cb(2*80A) in D=
C boss OMC // he made the bridge of Cb(2*80 A) with a another of Cb(2*80A),=
 site on grid","christian.fonkou@ihstowers.com","127","07-01-2025 13:58:52"=
,"Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0004020818","N=
yanon","","07-01-2025 13:40:31","07-01-2025 13:33:25","07-01-2025 13:38:25"=
,"No power issuen, site on gen with Ubaie=3D55V,Gregoire(654547479) from Hu=
awei si informed ","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issuen, =
site on gen with Ubaie=3D55V,Gregoire(654547479) from Huawei si informed ",=
"christian.fonkou@ihstowers.com","428","07-01-2025 13:40:31","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0004020577","Nko=
g-Edzen","","07-01-2025 13:01:22","07-01-2025 12:55:17","07-01-2025 13:21:0=
0","grid outage, site went down because gen stopped with Alarm high tempera=
ture // He open the schelter of gen and gen manually started","Parker Tchou=
p","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","grid outage, =
site went down because gen stopped with Alarm high temperature // He open t=
he schelter of gen and gen manually started","emmanuel.ghani@ihstowers.com"=
,"366","07-01-2025 13:01:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0004020477","Nkolbiss=
on usines des eaux 2","","07-01-2025 12:45:50","07-01-2025 12:38:47","07-01=
-2025 12:44:39","Cascaded Incident from TTO4004640","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, site went down before gen start due to poor battery backup // Gen sta=
rted automatically","system","264362","07-01-2025 12:45:50","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0004020447","Nko=
lbisson","IHS_YND_763","07-01-2025 12:40:53","07-01-2025 12:38:47","07-01-2=
025 12:44:39","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen started automatically","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down before gen start due to poor battery backup // Gen s=
tarted automatically","emmanuel.ghani@ihstowers.com","127","07-01-2025 12:4=
0:53","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_692","NOCINC0004020326","Mendong va=
llee","","07-01-2025 12:21:19","","","Site alarming High Temp because Site =
on Gen and Gen overload// Temp dicrease","Fanda Brice","Warning","Warning",=
"ENVIRONMENT","Warning - High Temperature","Site alarming High Temp because=
 Site on Gen and Gen overload// Temp dicrease","joelle.ekessi@ihstowers.com=
","3","07-01-2025 12:21:19","Sagemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0004019411","Bas=
tos Bir","","07-01-2025 10:07:46","07-01-2025 10:05:22","07-01-2025 10:19:1=
1","Grid outage,site went down before gen starts due to poor battery backup=
//Grid Restored","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage,site went down before gen sta=
rts due to poor battery backup//Grid Restored","emmanuel.ghani@ihstowers.co=
m","145","07-01-2025 10:07:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004019336","M=
essa-Carriere OCM","","07-01-2025 09:58:18","07-01-2025 09:55:10","07-01-20=
25 10:00:01","ACTIVE//No power issue on site U=3D52v site on grid Tx fme Mo=
hamadou of huawei is informed","","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue on sit=
e U=3D52v site on grid Tx fme Mohamadou of huawei is informed","christian.f=
onkou@ihstowers.com","189","07-01-2025 09:58:18","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0004019197","Nko=
abang Ebolmedjock","","07-01-2025 09:32:20","07-01-2025 09:29:12","07-01-20=
25 10:27:07","Grid outage, site went down because Gen stopped with alarm ""=
overcurrent""// He reset Gen card and Gen manually started the site still d=
own at OCM after power issue solved since 10:27 AM and power rest ","Mba La=
zare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, site went down because Gen stopped with alarm ""overcurrent""=
// He reset Gen card and Gen manually started the site still down at OCM af=
ter power issue solved since 10:27 AM and power rest ","emmanuel.ghani@ihst=
owers.com","189","07-01-2025 09:32:20","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0004018999","AKA=
K Nkozoa","","07-01-2025 08:56:54","07-01-2025 08:43:49","07-01-2025 09:59:=
29","Site went down due to work:  Our FME Fabrice/657108613/SAGEMCOM workin=
g on site (He replaced the Gen belt )// End of work","Fabrice Pouakam","Equ=
ipment Replacement","Passive","Planned Activity","Planned Activity - Passiv=
e","Site went down due to work:  Our FME Fabrice/657108613/SAGEMCOM working=
 on site (He replaced the Gen belt )// End of work","emmanuel.ghani@ihstowe=
rs.com","786","07-01-2025 08:56:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004018774","M=
balla 4","","07-01-2025 08:11:10","07-01-2025 08:05:05","07-01-2025 08:40:1=
1","Active// no power issue, U=3D54,3V on grid, The Tx fme synphorien/67529=
5205 from huawei is informed","Delor Telezing","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// no powe=
r issue, U=3D54,3V on grid, The Tx fme synphorien/675295205 from huawei is =
informed","christian.fonkou@ihstowers.com","366","07-01-2025 08:11:10","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0004017687","A=
kak-Nkozoa-MTN-IHS","","07-01-2025 03:32:01","07-01-2025 03:25:50","07-01-2=
025 03:30:53","Active // No power issue UBaie =3D55,5V site on Grid. The FM=
E TX SYMPHORIEN (675295205) From Huawei is informed","Fabrice Pouakam","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active // No power issue UBaie =3D55,5V site on Grid. The FME TX SY=
MPHORIEN (675295205) From Huawei is informed","olivier.kwedi@ihstowers.com"=
,"373","07-01-2025 03:32:01","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0004017581","Bit=
eng-Maetur","","07-01-2025 02:46:36","07-01-2025 02:42:26","07-01-2025 03:5=
9:33","Grid outage, site went down due to Gen overload Gen overload(20KVA, =
280A)// he reduiced the load and started Gen manually","Mba Lazare Herve","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site=
 went down due to Gen overload Gen overload(20KVA, 280A)// he reduiced the =
load and started Gen manually","ludivine.ngamaleu@ihstowers.com","251","07-=
01-2025 02:46:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0004017329","N=
gouetou","","07-01-2025 00:48:30","07-01-2025 00:47:23","07-01-2025 01:00:1=
5","No power issue on site, site on Gen The Tx FME Gregoire/654547479 from =
huawei is informed","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, sit=
e on Gen The Tx FME Gregoire/654547479 from huawei is informed","olivier.kw=
edi@ihstowers.com","69","07-01-2025 00:48:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0004017259","N=
komkana 2","","07-01-2025 00:18:25","07-01-2025 00:16:19","07-01-2025 01:15=
:38","ACTIVE No power issue site on Gen U=3D52,7V tx fme martial//690087047=
 from huawei is informed","Mboua Thierry","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power issue=
 site on Gen U=3D52,7V tx fme martial//690087047 from huawei is informed","=
olivier.kwedi@ihstowers.com","127","07-01-2025 00:18:25","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004015781","NYO=
M FACE MAETUR","","06-01-2025 19:26:32","06-01-2025 19:15:03","06-01-2025 2=
0:55:57","Grid outage.gen failed to start due to card GE dysfunctionning //=
We reset card GE and gen manually started ","Fabrice Pouakam","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed t=
o start due to card GE dysfunctionning //We reset card GE and gen manually =
started ","kamga.virgile@ihstowers.com","690","06-01-2025 19:26:32","Sagemc=
om CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0004015506","Acc=
acia New","","06-01-2025 18:33:50","06-01-2025 18:24:41","06-01-2025 18:26:=
59","No power issue site on gen with U=3D54.5v Mbah Osiah from Huawei is in=
formed and up at 06:38 PM","","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue site on gen with U=
=3D54.5v Mbah Osiah from Huawei is informed and up at 06:38 PM","kamga.virg=
ile@ihstowers.com","550","06-01-2025 18:33:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004015482","Akak-Nko=
zoa-MTN-IHS","","06-01-2025 18:30:40","06-01-2025 18:23:26","06-01-2025 18:=
26:20","Cascaded Incident from TTO3998780","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid Outage,  site down d=
ue to poor battery backup   //   grid return","system","272365","06-01-2025=
 18:30:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0004015288","Saa","",=
"06-01-2025 18:01:01","06-01-2025 17:45:20","06-01-2025 19:16:32","Cascaded=
 Incident from TTO3998533","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because Gen sta=
rted and stopped with alarm ""overvoltage"" // He reset card GE and gen man=
ually started","system","274620","06-01-2025 18:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0004015287","SAA Entr=
ance","","06-01-2025 18:01:00","06-01-2025 17:45:20","06-01-2025 19:16:32",=
"Cascaded Incident from TTO3998533","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e Gen started and stopped with alarm ""overvoltage"" // He reset card GE an=
d gen manually started","system","274620","06-01-2025 18:01:00","Sagemcom C=
MR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0004015276","SAA=
 2","IHS_YND_542, IHS_YND_405","06-01-2025 17:59:34","06-01-2025 17:43:12",=
"06-01-2025 19:17:49","Grid outage, site went down because Gen started and =
stopped with alarm ""overvoltage"" // He reset card GE and gen manually sta=
rted","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Grid outage, site went down because Gen started and stopped with=
 alarm ""overvoltage"" // He reset card GE and gen manually started","kamga=
.virgile@ihstowers.com","1147","06-01-2025 17:59:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_083","NOCINC0004015241","H-Progre=
s","","06-01-2025 17:52:41","06-01-2025 16:11:25","06-01-2025 17:37:25","Ca=
scaded Incident from TTO3998465","","Cascade Outage","Active","Cascade Acti=
ve","Cascade Active","No power issue on site U=3D54,1v site on grid Brice T=
sague of huawei is informed","system","272993","06-01-2025 17:52:41","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_010","NOCINC0004015240","CNR","",=
"06-01-2025 17:52:41","06-01-2025 16:11:25","06-01-2025 17:37:25","Cascaded=
 Incident from TTO3998465","Mboua Thierry","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site U=3D54,1v site on grid =
Brice Tsague of huawei is informed","system","272993","06-01-2025 17:52:41"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_005","NOCINC0004015238","Imm-Olym=
pique","","06-01-2025 17:52:40","06-01-2025 16:11:25","06-01-2025 17:37:25"=
,"Cascaded Incident from TTO3998465","Paul BIBOUM","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D54,1v site =
on grid Brice Tsague of huawei is informed","system","272995","06-01-2025 1=
7:52:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0004015237","Golf Qua=
ter","","06-01-2025 17:52:40","06-01-2025 16:11:25","06-01-2025 17:37:25","=
Cascaded Incident from TTO3998465","Mboua Thierry","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D54,1v site =
on grid Brice Tsague of huawei is informed","system","272992","06-01-2025 1=
7:52:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_007","NOCINC0004015236","Montee-A=
nne-Rouge","","06-01-2025 17:52:40","06-01-2025 16:11:25","06-01-2025 17:37=
:25","Cascaded Incident from TTO3998465","","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site U=3D54,1v site on grid=
 Brice Tsague of huawei is informed","system","272996","06-01-2025 17:52:40=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_012","NOCINC0004015239","Elig-Ess=
ono","","06-01-2025 17:52:40","06-01-2025 16:11:25","06-01-2025 17:37:25","=
Cascaded Incident from TTO3998465","Paul BIBOUM","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site U=3D54,1v site on=
 grid Brice Tsague of huawei is informed","system","272992","06-01-2025 17:=
52:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0004015217","C=
NDH","IHS_YND_007, IHS_YND_003, IHS_YND_220, IHS_YND_005, IHS_YND_126, IHS_=
YND_563, IHS_YND_012, IHS_YND_010, IHS_YND_002, IHS_YND_083, IHS_YND_028, I=
HS_YND_087, IHS_YND_127","06-01-2025 17:49:35","06-01-2025 16:11:25","06-01=
-2025 16:15:25","No power issue on site U=3D54,1v site on grid Brice Tsague=
 of huawei is informed","Paul BIBOUM","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,1v site on grid Brice Tsague of huawei is informed","alexandre.kamal@=
ihstowers.com","5891","06-01-2025 17:49:35","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0004015180","Awa=
e Escalier","","06-01-2025 17:44:36","06-01-2025 17:04:07","06-01-2025 18:5=
0:49","grid outage, sita went down because gen failed to start due to gen c=
ontactor faulty // Grid return(replacement gen contactor ongoing)","Albran =
Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","grid =
outage, sita went down because gen failed to start due to gen contactor fau=
lty // Grid return(replacement gen contactor ongoing)","kamga.virgile@ihsto=
wers.com","2471","06-01-2025 17:44:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_175","NOCINC0004015178","Nkomo","=
","06-01-2025 17:44:10","06-01-2025 17:04:55","06-01-2025 18:40:16","Cascad=
ed Incident from TTO3998414","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because rectifier of CB=
 32A) disjuncted  //he reamed CB(investigation ongoing)","system","276980",=
"06-01-2025 17:44:10","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0004015170","Nko=
mo stade","IHS_YND_175","06-01-2025 17:43:09","06-01-2025 17:04:55","06-01-=
2025 18:40:16","Site went down because rectifier of CB 32A) disjuncted  //h=
e reamed CB(investigation ongoing)","Mba Lazare Herve","Equipment Repair","=
Passive","Control Panel","Rectifier Battery Breaker Tripped","Site went dow=
n because rectifier of CB 32A) disjuncted  //he reamed CB(investigation ong=
oing)","kamga.virgile@ihstowers.com","2295","06-01-2025 17:43:09","Sagemcom=
 CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004015110","ODZ=
A MINKAN EDIBI ASSI","","06-01-2025 17:39:00","06-01-2025 17:26:46","06-01-=
2025 18:20:33","Site went down due to work:  Our FME Albran/657108542/SAGEM=
COM working on site (Issue of bad Voltage on site)// End of work","Albran B=
yorel","Equipment Replacement","Passive","Planned Activity","Planned Activi=
ty - Passive","Site went down due to work:  Our FME Albran/657108542/SAGEMC=
OM working on site (Issue of bad Voltage on site)// End of work","kamga.vir=
gile@ihstowers.com","735","06-01-2025 17:39:00","Sagemcom CMR"
"Cancelled","Warning","T0604","IHS_YND_171","NOCINC0004015032","Awae Escali=
er","","06-01-2025 17:30:55","","","","Albran Byorel","","","","","","kamga=
.virgile@ihstowers.com","1644","06-01-2025 17:30:55","Sagemcom CMR"
"Closed Complete","Site Down","T1486","IHS_YND_683","NOCINC0004015024","BON=
AS YDE","","06-01-2025 17:29:30","06-01-2025 16:56:16","06-01-2025 17:00:57=
","No power issue site on grid with U=3D54.2v Alain(691144423) from Huawei =
is informed ","Paul BIBOUM","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54.2v Alain(691144423) from Huawei is informed ","kamga.virgile@ihstower=
s.com","1994","06-01-2025 17:29:30","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004015018","NTU=
I TOWN","","06-01-2025 17:28:14","06-01-2025 16:51:45","06-01-2025 17:35:34=
","Site went down due to work: Ulrich/656072680/SAGEMCOM working on site (r=
eplacement Battery Gen)// End of work","Parker Tchoup","Installation Activi=
ty","Passive","Planned Activity","Installation Activity","Site went down du=
e to work: Ulrich/656072680/SAGEMCOM working on site (replacement Battery G=
en)// End of work","kamga.virgile@ihstowers.com","2190","06-01-2025 17:28:1=
4","Sagemcom CMR"
"Closed Complete","Site Down","CTR_110","IHS_YND_028","NOCINC0004014946","H=
-Central","","06-01-2025 17:19:40","06-01-2025 16:11:25","06-01-2025 17:37:=
25","","Paul BIBOUM","Cascade Outage","Active","Cascade Active","Cascade Ac=
tive","No power issue on site U=3D54,1v site on grid Brice Tsague of huawei=
 is informed","alexandre.kamal@ihstowers.com","272993","06-01-2025 17:19:40=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_014","IHS_YND_003","NOCINC0004014933","M=
ercure","","06-01-2025 17:17:40","06-01-2025 16:11:25","06-01-2025 17:37:25=
","","","Cascade Outage","Active","Cascade Active","Cascade Active","No pow=
er issue on site U=3D54,1v site on grid Brice Tsague of huawei is informed"=
,"alexandre.kamal@ihstowers.com","272994","06-01-2025 17:17:40","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0004014928","Y=
de-M-Central","","06-01-2025 17:16:56","06-01-2025 16:11:25","06-01-2025 17=
:37:25","","","Cascade Outage","Active","Cascade Active","Cascade Active","=
No power issue on site U=3D54,1v site on grid Brice Tsague of huawei is inf=
ormed","alexandre.kamal@ihstowers.com","272994","06-01-2025 17:16:56","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_087","NOCINC0004014916","Camp-Sic=
-Tsinga","","06-01-2025 17:13:50","06-01-2025 16:11:25","06-01-2025 17:37:2=
5","Cascaded Incident from TTO3998125 - Cascade Removed From TTO3998125",""=
,"Cascade Outage","Active","Cascade Active","Cascade Active","No power issu=
e on site U=3D54,1v site on grid Brice Tsague of huawei is informed","syste=
m","272994","06-01-2025 17:13:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004014915","Bastos B=
ethesda","","06-01-2025 17:13:50","06-01-2025 16:11:25","06-01-2025 17:37:2=
5","Cascaded Incident from TTO3998125 - Cascade Removed From TTO3998125","M=
boua Thierry","Cascade Outage","Active","Cascade Active","Cascade Active","=
No power issue on site U=3D54,1v site on grid Brice Tsague of huawei is inf=
ormed","system","272995","06-01-2025 17:13:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0004014917","Tsinga",=
"","06-01-2025 17:13:50","06-01-2025 16:11:25","06-01-2025 17:37:25","Casca=
ded Incident from TTO3998125 - Cascade Removed From TTO3998125","Mboua Thie=
rry","Cascade Outage","Active","Cascade Active","Cascade Active","No power =
issue on site U=3D54,1v site on grid Brice Tsague of huawei is informed","s=
ystem","272995","06-01-2025 17:13:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0004014912","B=
astos-Nylon","","06-01-2025 17:12:14","06-01-2025 16:11:25","06-01-2025 17:=
37:25","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Casca=
de Active","No power issue on site U=3D54,1v site on grid Brice Tsague of h=
uawei is informed","alexandre.kamal@ihstowers.com","272996","06-01-2025 17:=
12:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0004014793","Lobo OCM=
","","06-01-2025 16:51:11","06-01-2025 16:21:04","06-01-2025 16:25:09","Cas=
caded Incident from TTO3997851","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D54,=
5v site on Gen Tx fme Mohamadou of huawei is informed","system","272400","0=
6-01-2025 16:51:11","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0004014682","N=
KOMEKUI OCM","IHS_YND_341","06-01-2025 16:32:11","06-01-2025 16:21:04","06-=
01-2025 16:25:09","No power issue on site U=3D54,5v site on Gen Tx fme Moha=
madou of huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site U=3D54,5v site on Gen Tx fme Mohamadou of huawei is informe=
d","alexandre.kamal@ihstowers.com","668","06-01-2025 16:32:11","Sagemcom CM=
R"
"Cancelled","Warning","CTR_227","IHS_YND_341","NOCINC0004014673","Lobo OCM"=
,"","06-01-2025 16:30:31","","","","TIENTCHEU NZETCHIEU GAEL","","","","","=
","alexandre.kamal@ihstowers.com","1325","06-01-2025 16:30:31","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0004014524","Yoko MTN=
","","06-01-2025 16:01:52","06-01-2025 15:48:57","06-01-2025 16:22:08","Cas=
caded Incident from TTO3997624","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work: PATRICK es=
somba/697663548 from AFRO is working on site (dismantling equipement)// End=
 of work","system","274412","06-01-2025 16:01:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0004014520","Ngoum","=
","06-01-2025 16:01:51","06-01-2025 15:48:57","06-01-2025 16:22:08","Cascad=
ed Incident from TTO3997624","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to work: PATRICK essom=
ba/697663548 from AFRO is working on site (dismantling equipement)// End of=
 work","system","274414","06-01-2025 16:01:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0004014522","Donga","=
","06-01-2025 16:01:51","06-01-2025 15:48:57","06-01-2025 16:22:08","Cascad=
ed Incident from TTO3997624","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down due to work: PATRICK essom=
ba/697663548 from AFRO is working on site (dismantling equipement)// End of=
 work","system","274411","06-01-2025 16:01:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0004014521","Ngouetou=
","","06-01-2025 16:01:51","06-01-2025 15:48:57","06-01-2025 16:22:08","Cas=
caded Incident from TTO3997624","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work: PATRICK es=
somba/697663548 from AFRO is working on site (dismantling equipement)// End=
 of work","system","274411","06-01-2025 16:01:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0004014523","Dong",""=
,"06-01-2025 16:01:51","06-01-2025 15:48:57","06-01-2025 16:22:08","Cascade=
d Incident from TTO3997624","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Site went down due to work: PATRICK essomb=
a/697663548 from AFRO is working on site (dismantling equipement)// End of =
work","system","274412","06-01-2025 16:01:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0004014519","Matsari"=
,"","06-01-2025 16:01:50","06-01-2025 15:48:57","06-01-2025 16:22:08","Casc=
aded Incident from TTO3997624","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down due to work: PATRICK ess=
omba/697663548 from AFRO is working on site (dismantling equipement)// End =
of work","system","274413","06-01-2025 16:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0004014518","MBIMBIM"=
,"","06-01-2025 16:01:50","06-01-2025 15:48:57","06-01-2025 16:22:08","Casc=
aded Incident from TTO3997624","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down due to work: PATRICK ess=
omba/697663548 from AFRO is working on site (dismantling equipement)// End =
of work","system","274413","06-01-2025 16:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0004014517","Nguila",=
"","06-01-2025 16:01:50","06-01-2025 15:48:57","06-01-2025 16:22:08","Casca=
ded Incident from TTO3997624","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to work: PATRICK esso=
mba/697663548 from AFRO is working on site (dismantling equipement)// End o=
f work","system","274414","06-01-2025 16:01:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0004014468","O=
ssombe","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, I=
HS_YND_434, IHS_YND_444, IHS_YND_473","06-01-2025 15:56:01","06-01-2025 15:=
47:57","06-01-2025 16:22:08","Site went down due to work: PATRICK essomba/6=
97663548 from AFRO is working on site (dismantling equipement)// End of wor=
k","Parker Tchoup","Installation Activity","Passive","Planned Activity","In=
stallation Activity","Site went down due to work: PATRICK essomba/697663548=
 from AFRO is working on site (dismantling equipement)// End of work","alex=
andre.kamal@ihstowers.com","705","06-01-2025 15:56:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004014434","M=
balla 4","","06-01-2025 15:53:08","06-01-2025 15:19:03","06-01-2025 15:20:0=
3","Active// no power issue, U=3D54,3V on grid, The Tx fme synphorien/67529=
5205 from huawei is informed","Delor Telezing","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// no powe=
r issue, U=3D54,3V on grid, The Tx fme synphorien/675295205 from huawei is =
informed","alexandre.kamal@ihstowers.com","2046","06-01-2025 15:53:08","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004013702","C=
omplexe-BEAC","","06-01-2025 13:53:30","06-01-2025 13:41:59","06-01-2025 15=
:46:49","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage//MDG of 20 kva has deployed","kouoh.jean@ihstow=
ers.com","282189","06-01-2025 13:53:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004013685","E=
kie-Elegance","IHS_YND_159","06-01-2025 13:51:06","06-01-2025 13:41:59","06=
-01-2025 15:46:49","Grid outage//MDG of 20 kva has deployed","Albran Byorel=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage//MDG of 20 kva has deployed","kouoh.jean@ihstowers.com","548","06-01=
-2025 13:51:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0004013599","Nkolbiss=
on usines des eaux 2","","06-01-2025 13:34:40","06-01-2025 13:27:28","06-01=
-2025 13:32:31","Cascaded Incident from TTO3996577","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","ACTIVE/=
/No power issue on site u=3D54.5V site on Grid. THE TX FME MOHAMADOU of Hua=
wei is informed.","system","297230","06-01-2025 13:34:40","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0004013595","Nko=
lbisson","IHS_YND_763","06-01-2025 13:33:46","06-01-2025 13:27:28","06-01-2=
025 13:30:31","Grid outage, site went down before Gen start due to poor bac=
kup // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before Gen start due to poor backup // Gen start automatically=
","stephane.nkamwa@ihstowers.com","379","06-01-2025 13:33:46","Sagemcom CMR=
"
"Closed Complete","Warning","T0288","IHS_YND_001","NOCINC0004013272","Royal=
 Hotel Yde","","06-01-2025 13:12:08","","","Grid outage, site alarm due to =
static charging faulty // gen manually started with External battery","Paul=
 BIBOUM","Warning","Warning","POWER","Warning - ACDG - Charging Alternator"=
,"Grid outage, site alarm due to static charging faulty // gen manually sta=
rted with External battery","dorothy.djantio@ihstowers.com","74","06-01-202=
5 13:12:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004012635","M=
essa-Carriere OCM","","06-01-2025 11:40:40","06-01-2025 11:26:32","06-01-20=
25 11:31:08","ACTIVE//No power issue on site U=3D52v site on grid Tx fme Mo=
hamadou of huawei is informed","","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No power issue on sit=
e U=3D52v site on grid Tx fme Mohamadou of huawei is informed","kouoh.jean@=
ihstowers.com","849","06-01-2025 11:40:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004012586","M=
balla 4","","06-01-2025 11:34:26","06-01-2025 11:09:49","06-01-2025 11:14:4=
9","ACIVE//No power issue siteon grid with U=3D54.3v //The FME tx Armand Ng=
uetsa from Huawei is informed","Delor Telezing","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACIVE//No power=
 issue siteon grid with U=3D54.3v //The FME tx Armand Nguetsa from Huawei i=
s informed","kouoh.jean@ihstowers.com","1478","06-01-2025 11:34:26","Sagemc=
om CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0004012520","Bit=
eng","","06-01-2025 11:27:57","06-01-2025 11:20:44","06-01-2025 11:30:53","=
site went down due to work(Lazard(657108482),Second PWC departure for DC bo=
ss) // End of work","Mba Lazare Herve","Equipment Replacement","Passive","P=
lanned Activity","Planned Activity - Passive","site went down due to work(L=
azard(657108482),Second PWC departure for DC boss) // End of work","stephan=
e.nkamwa@ihstowers.com","434","06-01-2025 11:27:57","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0004011892","NKO=
MKANA ELIZA HOTEL","","06-01-2025 09:40:11","06-01-2025 09:33:32","06-01-20=
25 09:53:58","grid outage,no space to deploy MDG// Grid power return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outa=
ge,no space to deploy MDG// Grid power return","stephane.nkamwa@ihstowers.c=
om","400","06-01-2025 09:40:11","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004011871","NKO=
MEKUI OCM","","06-01-2025 09:35:50","06-01-2025 09:31:39","06-01-2025 10:42=
:13","ACTIVE//no power issue on site U=3D54.5  V site on Gen. Site impacted=
 by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","ACTIVE//no power issue on site U=3D54.5  V site on Gen. Site impac=
ted by Mbankolo Camtel and not managing by IHS","stephane.nkamwa@ihstowers.=
com","252","06-01-2025 09:35:50","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0004011789","Evo=
doula MTN","","06-01-2025 09:22:41","06-01-2025 09:06:34","06-01-2025 09:37=
:17","Grid outage, Site went down because Gen started and stopped with alar=
m overvoltage// He reset Gen card and started Gen manualy","TIENTCHEU NZETC=
HIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, Site went down because Gen started and stopped with alarm over=
voltage// He reset Gen card and started Gen manualy","stephane.nkamwa@ihsto=
wers.com","968","06-01-2025 09:22:41","Sagemcom CMR"
"Closed Complete","Warning","T0580","IHS_YND_310","NOCINC0004011403","Nomay=
os","","06-01-2025 08:15:01","","","alarm umprouven, site is on grid with U=
baie=3D51V","Fanda Brice","Warning","Warning","POWER","Warning - Site on Gr=
id","alarm umprouven, site is on grid with Ubaie=3D51V","dorothy.djantio@ih=
stowers.com","261","06-01-2025 08:15:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0004010710","ARMP",""=
,"06-01-2025 05:30:01","06-01-2025 05:25:44","06-01-2025 05:29:44","Cascade=
d Incident from TTO3993320","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down before gen start due to poo=
r battery backup // gen start automatically","system","261262","06-01-2025 =
05:30:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0004010708","Bastos B=
ethesda","","06-01-2025 05:30:01","06-01-2025 05:26:44","06-01-2025 05:34:3=
1","Grid outage, site went down before gen start due to poor battery backup=
 // gen start automatically","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // gen start automatically","sys=
tem","449","06-01-2025 05:30:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0004010707","Bastos B=
ir","","06-01-2025 05:30:00","06-01-2025 05:25:44","06-01-2025 05:29:44","C=
ascaded Incident from TTO3993320","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before g=
en start due to poor battery backup // gen start automatically","system","2=
61262","06-01-2025 05:30:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0004010701","D=
ragage","IHS_YND_704, IHS_YND_208","06-01-2025 05:28:52","06-01-2025 05:25:=
44","06-01-2025 05:29:44","Grid outage, site went down before gen start due=
 to poor battery backup // gen start automatically","Mboua Thierry","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage, site went down before gen start due to poor battery backup // gen st=
art automatically","rouselle.schoune@ihstowers.com","189","06-01-2025 05:28=
:52","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0004010616","BAT=
A Mokolo OCM","","06-01-2025 05:02:11","06-01-2025 04:55:57","06-01-2025 18=
:47:38","access issue due to landlord Grid outage.no space to deploy mobile=
 gen//Grid return","","Access Denial","Lease Or Legal","Landlord Related Is=
sues","Access Issue - Land Lord","access issue due to landlord","ange.kongo=
@ihstowers.com","375","06-01-2025 05:02:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0004009768","D=
ong","","05-01-2025 23:30:20","05-01-2025 23:22:16","05-01-2025 23:50:10","=
No power issue on site U=3D53v site on gen Tx Gregoire 654547479 of huawei =
is informed","Parker Tchoup","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53v sit=
e on gen Tx Gregoire 654547479 of huawei is informed","rouselle.schoune@ihs=
towers.com","486","05-01-2025 23:30:20","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004009273","Jou=
vence Mbenda","","05-01-2025 21:47:01","05-01-2025 21:40:53","05-01-2025 22=
:49:21","grid outage,gen stopped with alarm high temp//he added water in ra=
diator","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Hi=
gh Engine Temp - Coolant Level Issue","grid outage,gen stopped with alarm h=
igh temp//he added water in radiator","ludivine.ngamaleu@ihstowers.com","36=
9","05-01-2025 21:47:01","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0004008876","Bit=
eng","","05-01-2025 20:44:34","05-01-2025 20:41:25","05-01-2025 21:12:12","=
Site went down because CB (125A) tripped in PWC who feeds equipments MTN du=
e to load increase// CB put back on","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site wen=
t down because CB (125A) tripped in PWC who feeds equipments MTN due to loa=
d increase// CB put back on","ludivine.ngamaleu@ihstowers.com","190","05-01=
-2025 20:44:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004008871","ELOUMDEM=
 CARRIERE 2","","05-01-2025 20:43:21","05-01-2025 20:39:50","05-01-2025 21:=
15:44","Cascaded Incident from TTO3991128","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went douwn because Gen s=
tarted and stopped due to Grid bad voltage and  RCP on site// He bypass the=
 Grid and Gen manually started","system","264057","05-01-2025 20:43:21","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004008870","Eto koss=
 Yde","","05-01-2025 20:43:20","05-01-2025 20:39:50","05-01-2025 21:15:44",=
"Cascaded Incident from TTO3991128","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went douwn because Gen started =
and stopped due to Grid bad voltage and  RCP on site// He bypass the Grid a=
nd Gen manually started","system","264057","05-01-2025 20:43:20","Sagemcom =
CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004008862","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","05-01-2025 20:42:02","05-01-2025 20:39=
:50","05-01-2025 21:15:44","site went douwn because Gen started and stopped=
 due to Grid bad voltage and  RCP on site// He bypass the Grid and Gen manu=
ally started","Fanda Brice","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","site went douwn because Gen started and stopped =
due to Grid bad voltage and  RCP on site// He bypass the Grid and Gen manua=
lly started","ludivine.ngamaleu@ihstowers.com","134","05-01-2025 20:42:02",=
"Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0004008445","ELO=
UMDEM CARRIERE","","05-01-2025 19:38:45","05-01-2025 19:32:38","05-01-2025 =
19:56:42","site went douwn because Gen started and stopped due to Grid bad =
voltage and  RCP on site// He bypass the Grid and Gen manually started","Fa=
nda Brice","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","site went douwn because Gen started and stopped due to Grid bad v=
oltage and  RCP on site// He bypass the Grid and Gen manually started","lud=
ivine.ngamaleu@ihstowers.com","369","05-01-2025 19:38:45","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004008396","NYO=
M FACE MAETUR","","05-01-2025 19:29:24","05-01-2025 19:24:18","05-01-2025 2=
1:06:08","Grid outage, site went down because gen fails to start due to no =
automatism on site // Gen started manualy","Fabrice Pouakam","Equipment Rep=
air","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down=
 because gen fails to start due to no automatism on site // Gen started man=
ualy","ludivine.ngamaleu@ihstowers.com","307","05-01-2025 19:29:24","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004008377","M=
ontee-Jouvence-II","","05-01-2025 19:26:05","05-01-2025 19:24:01","05-01-20=
25 21:56:43","Site went down due to PWC Overloaded (12K, 230A) // Site stab=
lized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier=
 Module Overloaded","Site went down due to PWC Overloaded (12K, 230A/// Sit=
e stablized","dorothy.djantio@ihstowers.com","125","05-01-2025 19:26:05","S=
agemcom CMR"
"Cancelled","Warning","T1746","IHS_YND_178","NOCINC0004008354","Emombo","",=
"05-01-2025 19:22:59","","","","Mba Lazare Herve","","","","","","ludivine.=
ngamaleu@ihstowers.com","80","05-01-2025 19:22:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0004008347","C=
rf-Nsam","","05-01-2025 19:21:26","05-01-2025 19:17:21","05-01-2025 20:39:0=
2","Site went down Because The Slot off Rectifier is overload //he reduced =
the load and Gen manually started","MINKA NICOLAS","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Site went down Because The =
Slot off Rectifier is overload //he reduced the load and Gen manually start=
ed","dorothy.djantio@ihstowers.com","246","05-01-2025 19:21:26","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0004008139","B=
ondjock","","05-01-2025 18:56:11","05-01-2025 18:39:06","05-01-2025 21:03:1=
5","grid bad voltage,and gen failed to start,no rcp//bypassed grid and star=
ted the gen","Fanda Brice","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","grid bad voltage,and gen failed to start,no rcp//=
bypassed grid and started the gen","dorothy.djantio@ihstowers.com","1026","=
05-01-2025 18:56:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0004007975","M=
ontee-Jouvence-II","","05-01-2025 18:22:40","05-01-2025 18:20:33","05-01-20=
25 18:30:46","Site went down due to PWC over load(12KW.280A)// Site stabili=
zed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","Site went down due to PWC over load(12KW.280A)// Site st=
abilized","dorothy.djantio@ihstowers.com","128","05-01-2025 18:22:40","Sage=
mcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0004007888","Jou=
vence Mbenda","","05-01-2025 17:59:36","05-01-2025 17:57:28","05-01-2025 19=
:14:06","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // he added water and manually start the gen","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // he added water and manually start the gen","ludivine.=
ngamaleu@ihstowers.com","129","05-01-2025 17:59:36","Sagemcom CMR"
"Closed Complete","Warning","CTR_320","IHS_YND_282","NOCINC0004007856","Mey=
o","","05-01-2025 17:53:11","","","site on battery","Hyemafo Gildas","Warni=
ng","Warning","POWER","Warning - Site on Battery","...","dorothy.djantio@ih=
stowers.com","187","05-01-2025 17:53:11","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004007770","NTU=
I TOWN","","05-01-2025 17:31:34","05-01-2025 17:29:28","05-01-2025 19:11:51=
","Grid outage, site went down because gen failed to start due to Gen batte=
ry faulty // gen manually started with external battery","Parker Tchoup","E=
quipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outa=
ge, site went down because gen failed to start due to Gen battery faulty //=
 gen manually started with external battery","ludivine.ngamaleu@ihstowers.c=
om","127","05-01-2025 17:31:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0004007628","Nkolfon =
Cimencam","","05-01-2025 17:05:30","05-01-2025 16:35:11","05-01-2025 16:40:=
08","Cascaded Incident from TTO3989497","Hyemafo Gildas","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site , Ubaie=
=3D54.4V site On Grid The Tx FME Flobert (654266068) from Huawei is informe=
d.","system","271653","05-01-2025 17:05:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0004007490","M=
efou-Assi","","05-01-2025 16:42:53","05-01-2025 16:24:49","05-01-2025 17:19=
:30","Grid outage, site went down because gen ran untill fuel shortage // G=
rid return (refueling ongoing)","Fanda Brice","Fuel Outage","Passive","Dies=
el","Diesel Outage","Grid outage, site went down because gen ran untill fue=
l shortage // Grid return (refueling ongoing)","dorothy.djantio@ihstowers.c=
om","1085","05-01-2025 16:42:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0004007483","A=
fanoya","IHS_YND_762","05-01-2025 16:41:15","05-01-2025 16:35:11","05-01-20=
25 18:20:08","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FM=
E Flobert (654266068) from Huawei is informed.","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site , Ubaie=3D54.4V site On Grid The Tx FME Flobert (6=
54266068) from Huawei is informed.","dorothy.djantio@ihstowers.com","365","=
05-01-2025 16:41:15","Sagemcom CMR"
"Cancelled","Warning","T1682","IHS_YND_532","NOCINC0004007442","NKOLOSSAN O=
KOK","","05-01-2025 16:36:27","","","","Parker Tchoup","","","","","","ludi=
vine.ngamaleu@ihstowers.com","246","05-01-2025 16:36:27","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0004007428","Ebo=
go","","05-01-2025 16:33:31","05-01-2025 16:32:25","05-01-2025 16:35:43","G=
rid outage, Site went down before Gen start due to poor backup// Gen start =
automatically","Siligap Boris","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, Site went down before Gen star=
t due to poor backup// Gen start automatically","ludivine.ngamaleu@ihstower=
s.com","67","05-01-2025 16:33:31","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0004007414","SOA=
 UNIVERSITY STADIUM","","05-01-2025 16:31:14","05-01-2025 16:32:08","05-01-=
2025 17:05:32","Grid outage site went down because Gen started and stopped =
with alarm under frequency // He purge and Gen manually started","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","ACDG - Under Frequency","Gri=
d outage site went down because Gen started and stopped with alarm under fr=
equency // He purge and Gen manually started","ludivine.ngamaleu@ihstowers.=
com","14971","05-01-2025 16:31:14","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0004007383","BIY=
EMASSI NIKI","","05-01-2025 16:26:49","05-01-2025 16:22:32","05-01-2025 16:=
25:14","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Site =
stabilized","ludivine.ngamaleu@ihstowers.com","258","05-01-2025 16:26:49","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0004007202","Akak-Nko=
zoa-MTN-IHS","","05-01-2025 16:08:30","05-01-2025 16:02:20","05-01-2025 16:=
31:08","Cascaded Incident from TTO3989164","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","site went down because th=
e PWC of ZTE dysfonction // Gen manually started","system","273537","05-01-=
2025 16:08:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0004007195","S=
oa-II","IHS_YND_316, IHS_YND_324","05-01-2025 16:06:24","05-01-2025 16:02:2=
0","05-01-2025 16:31:08","site went down because the PWC of ZTE dysfonction=
 // Gen manually started","Siligap Boris","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","site went down because the PWC of ZT=
E dysfonction // Gen manually started","dorothy.djantio@ihstowers.com","245=
","05-01-2025 16:06:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004006875","M=
balla 4","","05-01-2025 15:19:35","05-01-2025 15:04:31","05-01-2025 18:34:2=
2","Active// No power issue on site U=3D54,2V , Site is on Grid The FME TX =
Armand Nguesta (699949553) From Huawei is informed","Delor Telezing","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue on site U=3D54,2V , Site is on Grid The FME T=
X Armand Nguesta (699949553) From Huawei is informed","dorothy.djantio@ihst=
owers.com","905","05-01-2025 15:19:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0004006810","E=
kie-Elegance","","05-01-2025 15:03:05","05-01-2025 14:31:56","05-01-2025 16=
:33:41","Grid outage//MDG of 20 kva has deployed","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG=
 of 20 kva has deployed","dorothy.djantio@ihstowers.com","1869","05-01-2025=
 15:03:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0004006808","C=
omplexe-BEAC","","05-01-2025 15:02:21","05-01-2025 14:31:10","05-01-2025 18=
:27:37","No power issue on site U=3D50.3v site on gen Tx fme Lionel steeve =
655184876 of huawei is informed","Albran Byorel","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site U=3D50.3v site on gen Tx fme Lionel steeve 655184876 of huawei is =
informed","dorothy.djantio@ihstowers.com","1871","05-01-2025 15:02:21","Sag=
emcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0004006788","Mon=
tee-Jouvence-II","","05-01-2025 14:58:23","05-01-2025 14:56:14","05-01-2025=
 15:12:40","Site went down due to PWC over load(12KW.280A)// Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC over load(12KW.280A)// Site stab=
ilized","ludivine.ngamaleu@ihstowers.com","130","05-01-2025 14:58:23","Sage=
mcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0004006692","Aha=
la Echangeur","","05-01-2025 14:47:41","05-01-2025 13:58:33","05-01-2025 16=
:44:07","Grid outage site went down because gen stopped  due to Gen card dy=
sfonction // He reset the Gen card and Gen manually started","MINKA NICOLAS=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge site went down because gen stopped  due to Gen card dysfonction // He re=
set the Gen card and Gen manually started","ludivine.ngamaleu@ihstowers.com=
","2949","05-01-2025 14:47:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0004006493","M=
essa-Carriere OCM","","05-01-2025 14:05:40","05-01-2025 13:45:30","05-01-20=
25 17:48:50","No Power issue on site Ubaie=3D52.7V site  on GridThe TX Fme =
Mohamadou 691144435 of huawei is informed. ","","Customer Equipment Failure=
","Active","Active Equipment Failure","Affected by 3rd Party Site","No Powe=
r issue on site Ubaie=3D52.7V site  on GridThe TX Fme Mohamadou 691144435 o=
f huawei is informed. ","alexandre.kamal@ihstowers.com","1211","05-01-2025 =
14:05:40","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0004006426","N=
yanon","","05-01-2025 13:53:32","05-01-2025 13:46:19","05-01-2025 13:48:22"=
,"No Power issue on site , site on Gen with Ubaie=3D55.7 V The Tx Gregoire(=
654547479) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No Power issue on site , site on Gen with Ubaie=3D55.7 V The Tx Gregoire(65=
4547479) from Huawei is informed","alexandre.kamal@ihstowers.com","434","05=
-01-2025 13:53:32","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0004006351","Nko=
lafeme","","05-01-2025 13:40:42","05-01-2025 13:39:32","05-01-2025 14:39:05=
","Grid outage site went down because Gen stopped with alarm high temp //He=
 added water and Gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid outage site went down because Gen stopped with alarm high temp //=
He added water and Gen manually started","kamga.virgile@ihstowers.com","70"=
,"05-01-2025 13:40:42","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0004006154","Mon=
tee Jouvence","","05-01-2025 13:01:19","05-01-2025 11:51:07","05-01-2025 11=
:52:25","No power issue site on gen with U=3D54.9v Mbah Osiah from Huawei i=
s informed ","Hyemafo Gildas","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue site on gen with U=
=3D54.9v Mbah Osiah from Huawei is informed ","kamga.virgile@ihstowers.com"=
,"4213","05-01-2025 13:01:19","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0004005972","NTU=
I TOWN","","05-01-2025 12:22:52","05-01-2025 12:12:43","05-01-2025 13:17:22=
","Grid outage.gen ran until fuel sfortage //Grid return(refueing ongoing)"=
,"Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age.gen ran until fuel sfortage //Grid return(refueing ongoing)","kamga.vir=
gile@ihstowers.com","610","05-01-2025 12:22:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0004005947","M=
balla 4","","05-01-2025 12:20:06","05-01-2025 12:06:55","05-01-2025 12:10:2=
7","No power issue siteon grid with U=3D54.3v //site up at 01:16 PM Armand =
Nguetsa from Huawei is informed","Delor Telezing","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e siteon grid with U=3D54.3v //site up at 01:16 PM Armand Nguetsa from Huaw=
ei is informed","alexandre.kamal@ihstowers.com","792","05-01-2025 12:20:06"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0004005875","MVAN SAC=
EL","","05-01-2025 12:02:20","05-01-2025 11:52:47","05-01-2025 16:39:22","C=
ascaded Incident from TTO3987536","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," site went down Gen overload (20KVA,=
290 A) // Grid power return","system","288525","05-01-2025 12:02:20","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0004005866","M=
VAN","IHS_YND_510","05-01-2025 12:01:51","05-01-2025 11:52:47","05-01-2025 =
16:39:22"," Grid outage site went down Gen overload (20KVA,290 A) SS IHS Pa=
scaline confirmed// Grid power return","MINKA NICOLAS","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload"," Grid outage site went down Gen over=
load (20KVA,290 A) SS IHS Pascaline confirmed// Grid power return","alexand=
re.kamal@ihstowers.com","545","05-01-2025 12:01:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0004005848","ELOUMDEM=
 CARRIERE 2","","05-01-2025 11:56:21","05-01-2025 11:49:48","05-01-2025 12:=
25:34","Cascaded Incident from TTO3987506","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage.gen start and sto=
pped due to ""high temp"" alarm// We add water and gen manually started ","=
system","267306","05-01-2025 11:56:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0004005847","Eto koss=
 Yde","","05-01-2025 11:56:20","05-01-2025 11:49:48","05-01-2025 12:25:34",=
"Cascaded Incident from TTO3987506","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage.gen start and stopped du=
e to ""high temp"" alarm// We add water and gen manually started ","system"=
,"267306","05-01-2025 11:56:21","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0004005840","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","05-01-2025 11:54:59","05-01-2025 11:49=
:48","05-01-2025 12:25:34","Grid outage.gen start and stopped due to ""high=
 temp"" alarm// We add water and gen manually started ","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage.gen start and stopped due to ""high temp"" alarm// We =
add water and gen manually started ","kamga.virgile@ihstowers.com","313","0=
5-01-2025 11:54:59","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004005825","ODZ=
A MINKAN EDIBI ASSI","","05-01-2025 11:49:41","05-01-2025 11:39:26","05-01-=
2025 13:00:54","site went down because Gen failed to start due  to lack of =
2 phase  and No RCP on site // he did a bridge with a good phase on site","=
Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","site went down because Gen failed to start due  to lack of 2 =
phase  and No RCP on site // he did a bridge with a good phase on site","ka=
mga.virgile@ihstowers.com","616","05-01-2025 11:49:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0004005804","M=
endong vallee","","05-01-2025 11:44:59","05-01-2025 11:31:55","05-01-2025 1=
6:44:44","Grid outage, Site went down due to gen overload(300A,20KVA) // Gr=
id return SS Ihs Felix Zambe is inform","Fanda Brice","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to ge=
n overload(300A,20KVA) // Grid return SS Ihs Felix Zambe is inform","alexan=
dre.kamal@ihstowers.com","2789","05-01-2025 11:44:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004005554","O=
dza II","","05-01-2025 10:38:53","05-01-2025 10:34:47","05-01-2025 11:18:49=
","Grid fluctuation, site went down before gen start due to poor battery ba=
ckup // grid return","Albran Byorel","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid fluctuation, site went down befo=
re gen start due to poor battery backup // grid return","alexandre.kamal@ih=
stowers.com","248","05-01-2025 10:38:53","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0004004883","NYO=
M FACE MAETUR","","05-01-2025 08:33:36","05-01-2025 08:12:26","05-01-2025 1=
0:36:41","Grid outage site went down because Gen failed to start due to No =
auatomatism on site on site // Gen manually started","Fabrice Pouakam","Equ=
ipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage site =
went down because Gen failed to start due to No auatomatism on site on site=
 // Gen manually started","kamga.virgile@ihstowers.com","1271","05-01-2025 =
08:33:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0004004828","N=
YOM 2 IHS","","05-01-2025 08:19:08","05-01-2025 08:10:02","05-01-2025 10:20=
:28","Grid outage site went down because Gen stopped with alarm high temp d=
ue to exhaust pipe cut // he opened all the doors of the GE","Fabrice Pouak=
am","Equipment Repair","Passive","ACDG Gen","ACDG - Exhaust","Grid outage s=
ite went down because Gen stopped with alarm high temp due to exhaust pipe =
cut // he opened all the doors of the GE","alexandre.kamal@ihstowers.com","=
547","05-01-2025 08:19:08","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004004450","ODZ=
A MINKAN EDIBI ASSI","","05-01-2025 06:55:02","05-01-2025 06:52:53","05-01-=
2025 07:38:11","Grid outage, site went down because gen ran untill fuel sho=
rtage // refueling done","Albran Byorel","Fuel Outage","Passive","Diesel","=
Diesel Outage","Grid outage, site went down because gen ran untill fuel sho=
rtage // refueling done","kamga.virgile@ihstowers.com","130","05-01-2025 06=
:55:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_801","NOCINC0004004447","HOPITAL =
GENERAL RAIL YDE","","05-01-2025 06:54:10","05-01-2025 06:46:20","05-01-202=
5 07:42:14","Cascaded Incident from TTO3985801","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","site went down becaus=
e Gen failed to start due  to lack of 2 phase  and No RCP on site // he did=
 a bridge with a good phase on site","system","306889","05-01-2025 06:54:10=
","Sagemcom CMR"
"Cancelled","Warning","T1266","IHS_YND_801","NOCINC0004004404","HOPITAL GEN=
ERAL RAIL YDE","","05-01-2025 06:49:16","","","","Delor Telezing","","","",=
"","","kamga.virgile@ihstowers.com","190","05-01-2025 06:49:16","Sagemcom C=
MR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0004004401","Pha=
rmacie Bleue","IHS_YND_801","05-01-2025 06:48:29","05-01-2025 06:46:20","05=
-01-2025 07:42:14","site went down because Gen failed to start due  to lack=
 of 2 phase  and No RCP on site // he did a bridge with a good phase on sit=
e","Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","site went down because Gen failed to start due  to lack o=
f 2 phase  and No RCP on site // he did a bridge with a good phase on site"=
,"kamga.virgile@ihstowers.com","130","05-01-2025 06:48:29","Sagemcom CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0004004317","NKO=
NGKARAK","","05-01-2025 06:31:00","05-01-2025 06:04:51","05-01-2025 08:25:5=
3","Grid Outage, site went down because Gen stopped with ""high temp"" alar=
m due to accordion faulty// He added water and started Gen manualy","TIENTC=
HEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High En=
gine Temp - Coolant Level Issue","Grid Outage, site went down because Gen s=
topped with ""high temp"" alarm due to accordion faulty// He added water an=
d started Gen manualy","kamga.virgile@ihstowers.com","1570","05-01-2025 06:=
31:00","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_282","NOCINC0004003719","Meyo","","=
05-01-2025 03:25:04","","","site went alarmes due to work our FME Mathieur =
is are working on Site//end off Work","Hyemafo Gildas","Warning","Warning",=
"POWER","Warning - Grid Low Frequency","site went alarmes due to work our F=
ME Mathieur is are working on Site//end off Work","joelle.ekessi@ihstowers.=
com","65","05-01-2025 03:25:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0004002847","N=
gousso OCM","","04-01-2025 22:42:26","04-01-2025 22:02:18","05-01-2025 01:4=
3:19","Active// No power issue on site U=3D54,5V , Site is on Grid and The =
FME TX Armand Nguesta (699949553) From Huawei is informed and Site Up at=3D=
11:11 PM","Siligap Boris","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Active// No power issue on site U=3D5=
4,5V , Site is on Grid and The FME TX Armand Nguesta (699949553) From Huawe=
i is informed and Site Up at=3D11:11 PM","christian.fonkou@ihstowers.com","=
2409","04-01-2025 22:42:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0004002823","N=
kolfon Cimencam","","04-01-2025 22:39:23","04-01-2025 22:28:04","04-01-2025=
 22:28:05","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","=
Cascade Active","No power issue on site , Ubaie=3D54.4V site On Grid The Tx=
 FME Patrice (695007608) from Huawei is informed. repetitive issue ","chris=
tian.fonkou@ihstowers.com","264777","04-01-2025 22:39:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0004002807","A=
fanoya","IHS_YND_762","04-01-2025 22:35:09","04-01-2025 22:28:04","04-01-20=
25 23:28:05","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FM=
E Patrice (695007608) from Huawei is informed. repetitive issue ","Hyemafo =
Gildas","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site , Ubaie=3D54.4V site On Grid The=
 Tx FME Patrice (695007608) from Huawei is informed. repetitive issue ","ch=
ristian.fonkou@ihstowers.com","426","04-01-2025 22:35:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0004002107","SOA VILL=
AGE","","04-01-2025 20:19:20","04-01-2025 20:06:08","04-01-2025 20:18:23","=
Cascaded Incident from TTO3983143","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation,site went douwn be=
cause Gen started and stopped due to Grid bad voltage and  RCP on site// He=
 bypass the Grid and Gen manually started","system","266204","04-01-2025 20=
:19:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0004002035","S=
OA TOWN","IHS_YND_323","04-01-2025 20:08:29","04-01-2025 20:04:23","04-01-2=
025 20:18:23","Grid fluctuation,site went douwn because Gen started and sto=
pped due to Grid bad voltage and  RCP on site// He bypass the Grid and Gen =
manually started","Siligap Boris","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","Grid fluctuation,site went douwn because G=
en started and stopped due to Grid bad voltage and  RCP on site// He bypass=
 the Grid and Gen manually started","rouselle.schoune@ihstowers.com","247",=
"04-01-2025 20:08:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_190","NOCINC0004001813","Ngousso-=
II","","04-01-2025 19:31:40","04-01-2025 19:24:06","04-01-2025 19:40:54","C=
ascaded Incident from TTO3982794","MFOUAGUEGUE MATHIEU","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen stopped with alarm high temps //He added water and Gen manually st=
arted","system","1218113","04-01-2025 19:31:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0004001805","N=
kolmesseng","IHS_YND_190","04-01-2025 19:30:12","04-01-2025 19:24:06","04-0=
1-2025 19:40:54","Grid outage site went down because Gen stopped with alarm=
 high temps //He added water and Gen manually started","Siligap Boris","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Leve=
l Issue","Grid outage site went down because Gen stopped with alarm high te=
mps //He added water and Gen manually started","rouselle.schoune@ihstowers.=
com","368","04-01-2025 19:30:12","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0004001603","NKO=
MEKUI OCM","","04-01-2025 18:45:36","04-01-2025 18:42:28","04-01-2025 20:50=
:49","no power issue on site U=3D54.5  V site on Gen. Site impacted by Mban=
kolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"no power issue on site U=3D54.5  V site on Gen. Site impacted by Mbankolo =
Camtel and not managing by IHS","ange.kongo@ihstowers.com","189","04-01-202=
5 18:45:36","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0004001599","ODZ=
A MINKAN EDIBI ASSI","","04-01-2025 18:44:38","04-01-2025 18:41:32","04-01-=
2025 19:10:00","site went down because Gen failed to start due to Grid bad =
voltage and no RCP on site // He bypass the Grid and Gen manually started",=
"Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","site went down because Gen failed to start due to Grid bad v=
oltage and no RCP on site // He bypass the Grid and Gen manually started","=
ange.kongo@ihstowers.com","187","04-01-2025 18:44:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0004001302","M=
vog-Ebanda","","04-01-2025 18:13:41","04-01-2025 18:11:36","04-01-2025 19:3=
5:18","no power issue on site  Ubaie =3D52.1V   site on Gen. Armand Nguetsa=
(691144412) from Huawei is informed. Notice that we have disjunction in OCM=
 equipment","Siligap Boris","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","no power issue on site  Ubaie =3D52=
.1V   site on Gen. Armand Nguetsa(691144412) from Huawei is informed. Notic=
e that we have disjunction in OCM equipment","rouselle.schoune@ihstowers.co=
m","126","04-01-2025 18:13:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004000974","O=
dza II","","04-01-2025 17:26:37","04-01-2025 17:10:23","04-01-2025 17:48:45=
","Grid outage, site went down before gen start due to poor battery backup =
and hybrid system dysfonction //he reset the system hybrid and Gen started =
automatically","Albran Byorel","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before gen star=
t due to poor battery backup and hybrid system dysfonction //he reset the s=
ystem hybrid and Gen started automatically","rouselle.schoune@ihstowers.com=
","1215","04-01-2025 17:26:37","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0004000883","Com=
plex Beac II","","04-01-2025 17:10:01","04-01-2025 17:01:52","04-01-2025 18=
:30:38","Grid outage, site went down because Gen stopped  due to gen contac=
tor dysfonction // He excited gen contactor and Site on Grid","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid ou=
tage, site went down because Gen stopped  due to gen contactor dysfonction =
// He excited gen contactor and Site on Grid","ange.kongo@ihstowers.com","4=
90","04-01-2025 17:10:01","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0004000462","Tsi=
nga village","","04-01-2025 16:15:44","04-01-2025 16:06:37","04-01-2025 16:=
40:19","grid outage, site went down because gen start and stopped with alar=
m low oil pressure // He added oil  and gen manually started","Delor Telezi=
ng","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","grid=
 outage, site went down because gen start and stopped with alarm low oil pr=
essure // He added oil  and gen manually started","ange.kongo@ihstowers.com=
","548","04-01-2025 16:15:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0004000300","O=
dza II","","04-01-2025 15:41:52","04-01-2025 15:39:47","04-01-2025 16:15:54=
","Grid outage, site went down before gen start due to poor battery backup =
and hybrid system dysfonction //he reset the system hybrid and Gen started =
automatically","Albran Byorel","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before gen star=
t due to poor battery backup and hybrid system dysfonction //he reset the s=
ystem hybrid and Gen started automatically","rouselle.schoune@ihstowers.com=
","127","04-01-2025 15:41:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0004000260","M=
vog Mbi New","","04-01-2025 15:35:23","04-01-2025 15:29:04","04-01-2025 15:=
37:04","Site went down due to work Our FME Nicolas /657108614/Sagemcom is w=
orking on site(installation of a second departure in the site) // end of wo=
rk","MINKA NICOLAS","Installation Activity","Passive","Planned Activity","I=
nstallation Activity","Site went down due to work Our FME Nicolas /65710861=
4/Sagemcom is working on site(installation of a second departure in the sit=
e) // end of work","rouselle.schoune@ihstowers.com","380","04-01-2025 15:35=
:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0003999727","M=
balla 4","","04-01-2025 14:02:39","04-01-2025 13:58:32","04-01-2025 15:45:0=
7","Active// No power issue on site U=3D54,2V , Site is on GridThe FME TX A=
rmand Nguesta (699949553) From Huawei is informed","Delor Telezing","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power issue on site U=3D54,2V , Site is on GridThe FME TX =
Armand Nguesta (699949553) From Huawei is informed","dorothy.djantio@ihstow=
ers.com","248","04-01-2025 14:02:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003999494","Nkolo II=
 New","IHS_YND_266","04-01-2025 13:24:10","04-01-2025 13:17:56","04-01-2025=
 13:59:44","site went down duE to CB 125A disjuncted in the PWC// he reamed=
 the CB 125A ","Mba Lazare Herve","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","site went down duE to CB 125A =
disjuncted in the PWC// he reamed the CB 125A ","system","374","04-01-2025 =
13:24:10","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003999490","Mim=
boman4","","04-01-2025 13:23:01","04-01-2025 13:17:56","04-01-2025 13:59:44=
","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","site went down duE to CB 125A dijoncted in the PWC// he reamed=
 the CB 125A ","ludivine.ngamaleu@ihstowers.com","290723","04-01-2025 13:23=
:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0003998725","Nkolkoum=
ou OCM","","04-01-2025 11:02:11","04-01-2025 10:55:20","04-01-2025 11:31:03=
","Cascaded Incident from TTO3979198","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down because gen start and stoppen with alarm ""low oil pressure"" (unpro=
ven) // He reset gen card and gen manually started","system","270509","04-0=
1-2025 11:02:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003998723","N=
kolbisson usine des eaux","IHS_YND_712","04-01-2025 11:01:29","04-01-2025 1=
0:55:20","04-01-2025 11:31:03","Grid outage, site went down because gen sta=
rt and stoppen with alarm ""low oil pressure"" (unproven) // He reset gen c=
ard and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down b=
ecause gen start and stoppen with alarm ""low oil pressure"" (unproven) // =
He reset gen card and gen manually started","dorothy.djantio@ihstowers.com"=
,"370","04-01-2025 11:01:29","Sagemcom CMR"
"Cancelled","Warning","CTR_676","IHS_YND_712","NOCINC0003998696","Nkolkoumo=
u OCM","","04-01-2025 10:57:41","","","","TIENTCHEU NZETCHIEU GAEL","","","=
","","","dorothy.djantio@ihstowers.com","306","04-01-2025 10:57:41","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0003998273","ARMP",""=
,"04-01-2025 10:10:01","04-01-2025 10:00:11","04-01-2025 10:04:06","Cascade=
d Incident from TTO3978686","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down before gen start due to poo=
r battery backup // Gen started automatically","system","273739","04-01-202=
5 10:10:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0003998272","Bastos B=
ir","","04-01-2025 10:10:01","04-01-2025 10:00:11","04-01-2025 10:04:06","C=
ascaded Incident from TTO3978686","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before g=
en start due to poor battery backup // Gen started automatically","system",=
"273739","04-01-2025 10:10:01","Sagemcom CMR"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0003998261","Dra=
gage","IHS_YND_704, IHS_YND_208","04-01-2025 10:07:05","04-01-2025 10:00:11=
","04-01-2025 10:04:36","Grid outage, site went down before gen start due t=
o poor battery backup // Gen started automatically","Mboua Thierry","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage, site went down before gen start due to poor battery backup // Gen st=
arted automatically","ludivine.ngamaleu@ihstowers.com","488","04-01-2025 10=
:07:05","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003998104","Ebo=
go","","04-01-2025 09:40:21","04-01-2025 09:27:15","04-01-2025 09:39:25","G=
rid outage, site went down before gen start due to poor battery backup // G=
en started automatically","Siligap Boris","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen started automatically","ludi=
vine.ngamaleu@ihstowers.com","787","04-01-2025 09:40:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003998045","B=
astos Bethesda","","04-01-2025 09:31:19","04-01-2025 09:26:13","04-01-2025 =
09:31:22","Grid outage, site went down before gen start due to poor battery=
 backup // Gen started automatically","Mboua Thierry","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down before gen start due to poor battery backup // Gen started automati=
cally","dorothy.djantio@ihstowers.com","308","04-01-2025 09:31:19","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003997604","Dong",""=
,"04-01-2025 07:55:01","04-01-2025 07:41:46","04-01-2025 08:19:52","Cascade=
d Incident from TTO3977891","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","No power issue site impacted by Mbanjock c=
amrail","system","1217024","04-01-2025 07:55:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003997603","Donga","=
","04-01-2025 07:55:01","04-01-2025 07:41:46","04-01-2025 08:19:52","Cascad=
ed Incident from TTO3977891","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","No power issue site impacted by Mbanjock =
camrail","system","1217023","04-01-2025 07:55:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003997599","Nguila",=
"","04-01-2025 07:55:00","04-01-2025 07:41:46","04-01-2025 08:19:52","Casca=
ded Incident from TTO3977891","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","No power issue site impacted by Mbanjock=
 camrail","system","1217025","04-01-2025 07:55:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003995508","M=
ontee-Jouvence-II","","03-01-2025 21:58:31","03-01-2025 21:54:26","03-01-20=
25 21:57:26","site went down because pwc overload(12k/280A) // site stabili=
zed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","site went down because pwc overload(12k/280A) // site st=
abilized","christian.fonkou@ihstowers.com","246","03-01-2025 21:58:31","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0003995461","Nkolkoum=
ou OCM","","03-01-2025 21:47:00","03-01-2025 21:41:21","03-01-2025 22:34:37=
","Cascaded Incident from TTO3975420","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","site went down becaus=
e gen failed to start due to grid bad voltage and no Rcp // Gen manually st=
arted","system","267660","03-01-2025 21:47:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003995437","N=
kolbisson usine des eaux","IHS_YND_712","03-01-2025 21:43:30","03-01-2025 2=
1:41:21","03-01-2025 22:34:37","site went down because gen failed to start =
due to grid bad voltage and no Rcp // Gen manually started","TIENTCHEU NZET=
CHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","site went down because gen failed to start due to grid bad volta=
ge and no Rcp // Gen manually started","christian.fonkou@ihstowers.com","12=
9","03-01-2025 21:43:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003995144","SOA VILL=
AGE","","03-01-2025 20:55:51","03-01-2025 20:52:38","03-01-2025 21:12:00","=
Cascaded Incident from TTO3975036","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid bad voltage, and gen failed to=
 start//bypassed grid and started the gen","system","270539","03-01-2025 20=
:55:51","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003995135","SOA=
 TOWN","IHS_YND_323","03-01-2025 20:54:43","03-01-2025 20:52:38","03-01-202=
5 21:12:00","grid bad voltage, and gen failed to start//bypassed grid and s=
tarted the gen","Siligap Boris","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","grid bad voltage, and gen failed to start//b=
ypassed grid and started the gen","emmanuel.ghani@ihstowers.com","126","03-=
01-2025 20:54:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003995098","A=
hala","IHS_YND_698","03-01-2025 20:47:35","03-01-2025 20:41:28","03-01-2025=
 20:59:28","Grid outage, site went down due to gen overload(15kva/248A) // =
grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, site went down due to gen overload(15kva/248A) //=
 grid return","christian.fonkou@ihstowers.com","368","03-01-2025 20:47:35",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003995094","Bit=
eng","","03-01-2025 20:46:19","03-01-2025 20:42:12","03-01-2025 22:18:38","=
site went down due to disjunction of Cb(125A) in PWC ZTE // He Reamed Cb(12=
5A) , site on grid","Mba Lazare Herve","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Circuit Breaker Issue","site went down due to dis=
junction of Cb(125A) in PWC ZTE // He Reamed Cb(125A) , site on grid","emma=
nuel.ghani@ihstowers.com","248","03-01-2025 20:46:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0003995085","E=
BOM","","03-01-2025 20:45:16","03-01-2025 20:41:28","03-01-2025 20:59:28","=
","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage, site went down due to gen overload(15kva/248A) // grid=
 return","christian.fonkou@ihstowers.com","271117","03-01-2025 20:45:16","S=
agemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003994853","ODZ=
A MINKAN EDIBI ASSI","","03-01-2025 20:03:28","03-01-2025 19:59:14","03-01-=
2025 20:25:15","Site went down because Gen failed to start due to Grid Bad =
voltage and no Rcp on site // He bypass the Grid and Gen manually started",=
"Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Site went down because Gen failed to start due to Grid Bad v=
oltage and no Rcp on site // He bypass the Grid and Gen manually started","=
emmanuel.ghani@ihstowers.com","255","03-01-2025 20:03:28","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003994339","Pha=
rmacie SION","","03-01-2025 18:15:50","03-01-2025 18:09:44","03-01-2025 19:=
08:47","Grid outage,site went down before Gen start due to poor battery bac=
kup// he started the Gen manually","Paul BIBOUM","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage,site went dow=
n before Gen start due to poor battery backup// he started the Gen manually=
","emmanuel.ghani@ihstowers.com","367","03-01-2025 18:15:50","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003994161","Pha=
rmacie SION","","03-01-2025 17:39:04","03-01-2025 17:35:58","03-01-2025 17:=
45:02","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen started automatically","Paul BIBOUM","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen started automatically=
","emmanuel.ghani@ihstowers.com","186","03-01-2025 17:39:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0003993800","Ekoumdou=
m OCM","","03-01-2025 16:51:10","03-01-2025 16:42:25","03-01-2025 17:08:43"=
,"Cascaded Incident from TTO3973428","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage,gen stopped with alar=
m high temp//he added water in radiator","system","264123","03-01-2025 16:5=
1:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003993799","MEHANDAN=
","","03-01-2025 16:51:10","03-01-2025 16:42:25","03-01-2025 17:08:43","Cas=
caded Incident from TTO3973428","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage,gen stopped with alarm hig=
h temp//he added water in radiator","system","264122","03-01-2025 16:51:10"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0003993787","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","03-01-2025 16:47:34","03=
-01-2025 16:42:25","03-01-2025 17:08:43","grid outage,gen stopped with alar=
m high temp//he added water in radiator","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","grid=
 outage,gen stopped with alarm high temp//he added water in radiator","chri=
stian.fonkou@ihstowers.com","310","03-01-2025 16:47:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003993775","O=
dza II OCM","","03-01-2025 16:45:21","03-01-2025 16:42:25","03-01-2025 17:0=
8:43","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","grid outage,gen stopped with alarm high temp//he added water =
in radiator","christian.fonkou@ihstowers.com","264123","03-01-2025 16:45:21=
","Sagemcom CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0003993771","Odz=
a Minkan IHS","","03-01-2025 16:45:02","03-01-2025 16:41:58","03-01-2025 17=
:30:48","grid outage,gen stopped with alarm low oil pressure(not unpreoven)=
//he reset it and started the gen","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","grid outage,gen stopped with alarm =
low oil pressure(not unpreoven)//he reset it and started the gen","emmanuel=
.ghani@ihstowers.com","185","03-01-2025 16:45:02","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_001","NOCINC0003993532","Royal Hote=
l Yde","","03-01-2025 16:29:24","","","site on alarm due to grid bad voltag=
e//he put site on gen","Paul BIBOUM","Warning","Warning","POWER","Warning -=
 Site on Battery","site on alarm due to grid bad voltage//he put site on ge=
n","joelle.ekessi@ihstowers.com","2","03-01-2025 16:29:24","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003993311","San=
ta Barbara Gottam","","03-01-2025 15:51:18","03-01-2025 15:47:13","03-01-20=
25 15:55:13","site went down due to work Delor/Sagemcom/657108565:doing the=
 2nd depart of cable alimented  in PWC//End of work","Delor Telezing","Inst=
allation Activity","Passive","Planned Activity","Installation Activity","si=
te went down due to work Delor/Sagemcom/657108565:doing the 2nd departof ca=
ble alimented  in PWC//End of work","emmanuel.ghani@ihstowers.com","246","0=
3-01-2025 15:51:18","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003992863","NYO=
M FACE MAETUR","","03-01-2025 14:43:39","03-01-2025 14:40:32","03-01-2025 1=
5:55:32","Grid outage, site went down because gen fails to start due to no =
automatisme on site // Gen started manualy","Fabrice Pouakam","Equipment Re=
pair","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went dow=
n because gen fails to start due to no automatisme on site // Gen started m=
anualy","emmanuel.ghani@ihstowers.com","188","03-01-2025 14:43:39","Sagemco=
m CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003992838","NKO=
MEKUI OCM","","03-01-2025 14:36:37","03-01-2025 14:33:33","03-01-2025 16:10=
:33","No power issue on site U=3D54,3V site on gen site down because is imp=
acted by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL=
","Customer Equipment Failure","Active","Active Equipment Failure","Affecte=
d by 3rd Party Site","No power issue on site U=3D54,3V site on gen site dow=
n because is impacted by Mbankolo Camtel and not managing by IHS","emmanuel=
.ghani@ihstowers.com","185","03-01-2025 14:36:37","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003992821","Men=
dong3","","03-01-2025 14:32:58","03-01-2025 14:25:54","03-01-2025 14:50:54"=
,"grid outage,no space to deploy a mobil gen//grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","grid outage,no space=
 to deploy a mobil gen//grid return","emmanuel.ghani@ihstowers.com","424","=
03-01-2025 14:32:58","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003992815","NYO=
M 2 IHS","","03-01-2025 14:31:31","03-01-2025 14:25:26","03-01-2025 14:39:2=
6","Site went down due to work Our FME Fabrice/657108613/Sagemcom is workin=
g on site(He Upgrade the Power limitation in the PWC) // end of work","Fabr=
ice Pouakam","Equipment Replacement","Passive","Planned Activity","Planned =
Activity - Passive","Site went down due to work Our FME Fabrice/657108613/S=
agemcom is working on site(He Upgrade the Power limitation in the PWC) // e=
nd of work","emmanuel.ghani@ihstowers.com","366","03-01-2025 14:31:31","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003992662","N=
kolda","","03-01-2025 14:00:03","03-01-2025 13:57:56","03-01-2025 15:03:11"=
,"site went down due to insufficient of rectifier '(03)//site stabilized(ne=
ed to added one rectifier)","Albran Byorel","Equipment Repair","Passive","R=
ectifier","Rectifier Module","site went down due to insufficient of rectifi=
er '(03)//site stabilized(need to added one rectifier)","rouselle.schoune@i=
hstowers.com","128","03-01-2025 14:00:03","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003992596","Mes=
sa Carriere","","03-01-2025 13:46:09","03-01-2025 13:42:02","03-01-2025 14:=
00:50","grid outage gen failed to start duen to No automatism on site//Gen =
manually started","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","ATS-AMF Issue","grid outage gen failed to start duen to No automatism =
on site//Gen manually started","ange.kongo@ihstowers.com","248","03-01-2025=
 13:46:09","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0003992446","NKO=
MKANA ELIZA HOTEL","","03-01-2025 13:16:01","03-01-2025 13:06:55","03-01-20=
25 14:34:23","Grid outage.no space to deploy mobil gen //.grid power return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage.no space to deploy mobil gen //.grid power return","ange.kongo@ih=
stowers.com","547","03-01-2025 13:16:01","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003992430","NKO=
MEKUI OCM","","03-01-2025 13:12:31","03-01-2025 13:04:24","03-01-2025 13:37=
:15","No power issue site on gen with U=3D54.5v Notice that site is impacte=
d by Mbankolo Camtel","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 site on gen with U=3D54.5v Notice that site is impacted by Mbankolo Camtel=
","ange.kongo@ihstowers.com","488","03-01-2025 13:12:31","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0003992381","SIM=
BOCK BONAMBAPE","","03-01-2025 13:05:58","03-01-2025 13:04:26","03-01-2025 =
13:14:00","Grid outage, site went down due to Gen overload Gen overload(20K=
VA, 280A)// he reduiced the load and started Gen manually","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, si=
te went down due to Gen overload Gen overload(20KVA, 280A)// he reduiced th=
e load and started Gen manually","ange.kongo@ihstowers.com","308","03-01-20=
25 13:05:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0003992365","Ahala","=
","03-01-2025 13:02:30","03-01-2025 12:31:46","03-01-2025 13:36:46","Cascad=
ed Incident from TTO3971530","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","grid outage,gen failed to start due to a=
larm over ccurent causing by grid bad voltage//he reset the card and starte=
d the gen","system","286167","03-01-2025 13:02:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003992339","S=
OA UNIVERSITY STADIUM","","03-01-2025 12:58:37","03-01-2025 12:52:34","03-0=
1-2025 13:46:56","grid outage,gen failed to start due to alarm underfrequen=
cy//he reset the card and started the gen","Siligap Boris","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","grid outage,gen failed to s=
tart due to alarm underfrequency//he reset the card and started the gen","r=
ouselle.schoune@ihstowers.com","364","03-01-2025 12:58:37","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003992207","ODZ=
A MINKAN EDIBI ASSI","","03-01-2025 12:42:45","03-01-2025 12:35:37","03-01-=
2025 13:38:46","grid bad voltage, and gen failed to start ,no rcp// bypasse=
d grid and started the gen","Albran Byorel","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","grid bad voltage, and gen failed=
 to start ,no rcp// bypassed grid and started the gen","ange.kongo@ihstower=
s.com","429","03-01-2025 12:42:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003992182","C=
RH-Etoug-Ebe","","03-01-2025 12:37:47","03-01-2025 12:36:27","03-01-2025 12=
:50:23","Grid fluctuation,site went douwn because Gen failed to start due t=
o Grid bad voltage and No RCP on site// Grid Restored","Hyemafo Gildas","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuation,site went douwn because Gen failed to start due to Grid bad vo=
ltage and No RCP on site// Grid Restored","rouselle.schoune@ihstowers.com",=
"81","03-01-2025 12:37:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0003992174","EBOM",""=
,"03-01-2025 12:36:30","03-01-2025 12:31:46","03-01-2025 13:36:46","Cascade=
d Incident from TTO3971530","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","grid outage,gen failed to start due to al=
arm over ccurent causing by grid bad voltage//he reset the card and started=
 the gen","system","286167","03-01-2025 12:36:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003992170","A=
hala","IHS_YND_257, IHS_YND_698","03-01-2025 12:35:51","03-01-2025 12:31:46=
","03-01-2025 13:36:46","grid bad voltage,and gen failed to start//bypassed=
 grid and started the gen","MINKA NICOLAS","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","grid bad voltage,and gen failed t=
o start//bypassed grid and started the gen","rouselle.schoune@ihstowers.com=
","246","03-01-2025 12:35:51","Sagemcom CMR"
"Closed Complete","Warning","T0104","IHS_YND_113","NOCINC0003992140","Emomb=
o 2","","03-01-2025 12:28:01","","","Low Voltage Battery","MINKA NICOLAS","=
Warning","Warning","POWER","Warning - AC Phase 3 Current Low","Alarm cleare=
d.","alwine.fambou@ihstowers.com","3","03-01-2025 12:28:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003992128","Afanoya"=
,"","03-01-2025 12:25:20","03-01-2025 12:21:56","03-01-2025 12:51:56","Casc=
aded Incident from TTO3971474","Hyemafo Gildas","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site U=3D50,1v site on =
grid Tx Fme Tchana Patrice 695007603 of huawei is informed,notice that disj=
unction of BTS Ocm","system","279629","03-01-2025 12:25:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0003992129","Nkolfon =
Cimencam","","03-01-2025 12:25:20","03-01-2025 12:21:56","03-01-2025 12:51:=
56","Cascaded Incident from TTO3971474","Hyemafo Gildas","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site U=3D50,1v=
 site on grid Tx Fme Tchana Patrice 695007603 of huawei is informed,notice =
that disjunction of BTS Ocm","system","279629","03-01-2025 12:25:20","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0003992118","M=
eyo","IHS_YND_313, IHS_YND_762","03-01-2025 12:24:03","03-01-2025 12:21:56"=
,"03-01-2025 12:51:56","No power issue on site U=3D50,1v site on grid Tx Fm=
e Tchana Patrice 695007603 of huawei is informed,notice that disjunction of=
 BTS Ocm","Hyemafo Gildas","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D50,1v sit=
e on grid Tx Fme Tchana Patrice 695007603 of huawei is informed,notice that=
 disjunction of BTS Ocm","rouselle.schoune@ihstowers.com","128","03-01-2025=
 12:24:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003992048","S=
oa-II","","03-01-2025 12:10:06","03-01-2025 12:08:00","03-01-2025 12:10:53"=
,"Active // No power issue UBaie =3D54,7V site on Grid. The FME TX SYMPHORI=
EN (675295205) From Huawei is informed and Up at 12:10 PM. Site impacted by=
 SOA Nodal","Siligap Boris","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Active // No power issue UBaie =3D5=
4,7V site on Grid. The FME TX SYMPHORIEN (675295205) From Huawei is informe=
d and Up at 12:10 PM. Site impacted by SOA Nodal","rouselle.schoune@ihstowe=
rs.com","127","03-01-2025 12:10:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003991525","E=
kounou","","03-01-2025 10:37:29","03-01-2025 10:35:23","03-01-2025 10:45:58=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen started automatically","Albran Byorel","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen started automatically","=
rouselle.schoune@ihstowers.com","127","03-01-2025 10:37:29","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003991303","NYO=
M FACE MAETUR","","03-01-2025 09:44:05","03-01-2025 09:40:56","03-01-2025 1=
1:36:12","Grid outage, site went down because gen fails to start due to no =
automatisme on site // gen manually started","Fabrice Pouakam","Equipment R=
epair","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went do=
wn because gen fails to start due to no automatisme on site // gen manually=
 started","ange.kongo@ihstowers.com","190","03-01-2025 09:44:05","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003991237","N=
YOM 2 IHS","","03-01-2025 09:32:17","03-01-2025 09:30:09","03-01-2025 09:33=
:54","Grid outage, site went down before gen start due to poor battery back=
up // Gen started automatically","Fabrice Pouakam","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen started automatical=
ly","rouselle.schoune@ihstowers.com","129","03-01-2025 09:32:17","Sagemcom =
CMR"
"Closed Complete","Warning","CTR_046","IHS_YND_008","NOCINC0003990879","CND=
H","","03-01-2025 08:17:18","","","site went alarm because the air conditio=
ner's electronic card had malfunctioned // reset done and air conditioner r=
estarted","Paul BIBOUM","Warning","Warning","ENVIRONMENT","Warning - High T=
emperature","site went alarm because the air conditioner's electronic card =
had malfunctioned // reset done and air conditioner restarted","alwine.famb=
ou@ihstowers.com","2","03-01-2025 08:17:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0003990754","M=
essassi okolo","","03-01-2025 07:54:20","03-01-2025 07:39:17","03-01-2025 0=
7:59:18","Active// no power issue, U=3D54,4V on grid, tx fme synphorien/675=
295205 from huawei is informed","Fabrice Pouakam","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// no p=
ower issue, U=3D54,4V on grid, tx fme synphorien/675295205 from huawei is i=
nformed","rouselle.schoune@ihstowers.com","905","03-01-2025 07:54:20","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0003990284","Tsinga",=
"","03-01-2025 05:54:51","03-01-2025 05:19:38","03-01-2025 05:25:32","Casca=
ded Incident from TTO3969248 - Cascade Removed From TTO3969248 - Cascade Re=
moved From TTO3969248","Mboua Thierry","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue on site Ubaie=3D53.4V site on Grid =
The Tx Fme Eloundou/693212405 of huawei is informed by message","system","2=
69092","03-01-2025 05:54:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0003990282","Hotel de=
 Ville Yde","","03-01-2025 05:54:50","03-01-2025 05:19:38","03-01-2025 05:2=
5:32","Cascaded Incident from TTO3969248 - Cascade Removed From TTO3969248 =
- Cascade Removed From TTO3969248","Paul BIBOUM","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site Ubaie=3D53.4V sit=
e on Grid The Tx Fme Eloundou/693212405 of huawei is informed by message","=
system","269093","03-01-2025 05:54:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0003990281","Golf Qua=
ter","IHS_YND_019, IHS_YND_126, IHS_YND_563, IHS_YND_127","03-01-2025 05:54=
:50","03-01-2025 05:19:38","03-01-2025 05:25:32","No power issue on site Ub=
aie=3D53.4V site on Grid The Tx Fme Eloundou/693212405 of huawei is informe=
d by message","Mboua Thierry","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie=3D53=
.4V site on Grid The Tx Fme Eloundou/693212405 of huawei is informed by mes=
sage","system","2112","03-01-2025 05:54:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0003990283","Bastos B=
ethesda","","03-01-2025 05:54:50","03-01-2025 05:19:38","03-01-2025 05:25:3=
2","Cascaded Incident from TTO3969248 - Cascade Removed From TTO3969248 - C=
ascade Removed From TTO3969248","Mboua Thierry","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubaie=3D53.4V site=
 on Grid The Tx Fme Eloundou/693212405 of huawei is informed by message","s=
ystem","269092","03-01-2025 05:54:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0003990249","B=
astos-Nylon","","03-01-2025 05:48:49","03-01-2025 05:19:38","03-01-2025 05:=
25:32","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Casca=
de Active","No power issue on site Ubaie=3D53.4V site on Grid The Tx Fme El=
oundou/693212405 of huawei is informed by message","alexandre.kamal@ihstowe=
rs.com","269093","03-01-2025 05:48:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003989485","M=
vog-Manga","","03-01-2025 01:28:29","02-01-2025 22:55:08","02-01-2025 23:03=
:40","Grid fluctuation, site went down due to grid bad voltage//he made a b=
ridge with the Good phase","Albran Byorel","Grid Supply","Passive","Grid","=
National Grid - Grid Incomplete Phase","Grid fluctuation, site went down du=
e to grid bad voltage//he made a bridge with the Good phase","alexandre.kam=
al@ihstowers.com","9203","03-01-2025 01:28:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003989001","N=
kolfon Cimencam","","02-01-2025 22:43:47","02-01-2025 22:30:30","02-01-2025=
 22:35:26","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","=
Cascade Active","No power issue on site , Ubaie=3D54.4V site On Grid The Th=
e Rm Alain (691144423) from Huawei is informed. repetitive issue ","alexand=
re.kamal@ihstowers.com","271915","02-01-2025 22:43:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003988943","A=
fanoya","IHS_YND_762","02-01-2025 22:42:37","02-01-2025 22:30:30","02-01-20=
25 22:35:26","No power issue on site , Ubaie=3D54.4V site On Grid The The R=
m Alain (691144423) from Huawei is informed. repetitive issue ","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site , Ubaie=3D54.4V site On Grid The T=
he Rm Alain (691144423) from Huawei is informed. repetitive issue ","alexan=
dre.kamal@ihstowers.com","728","02-01-2025 22:42:37","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003988358","San=
ta Barbara Gottam","","02-01-2025 21:38:10","02-01-2025 21:26:50","02-01-20=
25 22:55:28","Site went down because the Cb(125A) of PWC dysjoncted due to =
load increased // he made the bridge the Cb(125*63 A) and reamed the Cb","D=
elor Telezing","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Circuit Breaker Issue","Site went down because the Cb(125A) of PWC dysjon=
cted due to load increased // he made the bridge the Cb(125*63 A) and reame=
d the Cb","stephane.nkamwa@ihstowers.com","681","02-01-2025 21:38:10","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003988235","C=
rf-Nsam","","02-01-2025 21:15:38","02-01-2025 21:00:25","02-01-2025 21:47:2=
4","Site went down Because The Slot off Rectifier is overload //he reduced =
the load and Gen manually started","MINKA NICOLAS","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module Overloaded","Site went down Because The =
Slot off Rectifier is overload //he reduced the load and Gen manually start=
ed","kouoh.jean@ihstowers.com","914","02-01-2025 21:15:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003988100","E=
kombitie","","02-01-2025 20:50:39","02-01-2025 20:49:09","02-01-2025 20:55:=
49","Grid fluctuation,site went down because Gen failed to start due to bad=
 voltage, RCP faulty// he bypass the Grid and site on Gen","Fabrice Pouakam=
","Grid Supply","Passive","Grid","National Grid - Grid Incomplete Phase","G=
rid fluctuation,site went down because Gen failed to start due to bad volta=
ge, RCP faulty// he bypass the Grid and site on Gen","kouoh.jean@ihstowers.=
com","91","02-01-2025 20:50:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003987793","K=
oweit City","","02-01-2025 19:49:14","02-01-2025 19:46:26","02-01-2025 19:4=
9:24","site went down because gen failed to start due to grid bad voltage /=
/ Grid stabilized","Albran Byorel","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","site went down because gen failed to star=
t due to grid bad voltage // Grid stabilized","kouoh.jean@ihstowers.com","1=
69","02-01-2025 19:49:14","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003987648","Elo=
umdem stade","","02-01-2025 19:23:37","02-01-2025 19:16:31","02-01-2025 19:=
46:38","Grid fluctuation,site went down because Gen failed to start due to =
bad voltage,NO RCP// he bypass the Grid and site on Gen","Fanda Brice","Gri=
d Supply","Passive","Grid","National Grid - Grid Incomplete Phase","Grid fl=
uctuation,site went down because Gen failed to start due to bad voltage,NO =
RCP// he bypass the Grid and site on Gen","stephane.nkamwa@ihstowers.com","=
427","02-01-2025 19:23:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003987399","A=
fanoya","IHS_YND_762","02-01-2025 18:35:49","02-01-2025 18:27:41","02-01-20=
25 18:30:35","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FM=
E Georges 697461814 from Huawei is informed. repetitive issue ","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site , Ubaie=3D54.4V site On Grid The T=
x FME Georges 697461814 from Huawei is informed. repetitive issue ","kouoh.=
jean@ihstowers.com","489","02-01-2025 18:35:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003987365","E=
kombitie","","02-01-2025 18:24:59","02-01-2025 18:12:06","02-01-2025 19:09:=
51","site went down because gen failed to start due to grid bad voltage // =
grid stabilized","Fabrice Pouakam","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","site went down because gen failed to star=
t due to grid bad voltage // grid stabilized","kouoh.jean@ihstowers.com","7=
74","02-01-2025 18:24:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003987359","Nkongtoc=
k","","02-01-2025 18:22:52","02-01-2025 16:58:52","02-01-2025 17:03:21","Ca=
scaded Incident from TTO3965361","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active: no power issue, site is on gri=
d with Ubaie=3D48V, Rm Alain (691144423) from Huawei is informed","system",=
"270130","02-01-2025 18:22:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0003987358","Angongo"=
,"","02-01-2025 18:22:52","02-01-2025 16:58:52","02-01-2025 17:03:21","Casc=
aded Incident from TTO3965361","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active: no power issue, site is on grid with=
 Ubaie=3D48V, Rm Alain (691144423) from Huawei is informed","system","27013=
3","02-01-2025 18:22:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0003987355","Nomayos-=
IHS","","02-01-2025 18:22:51","02-01-2025 16:58:52","02-01-2025 17:03:21","=
Cascaded Incident from TTO3965361","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active: no power issue, site is on grid =
with Ubaie=3D48V, Rm Alain (691144423) from Huawei is informed","system","2=
70132","02-01-2025 18:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0003987356","OKOA Pea=
ge","","02-01-2025 18:22:51","02-01-2025 16:58:52","02-01-2025 17:03:21","C=
ascaded Incident from TTO3965361","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active: no power issue, site is on grid w=
ith Ubaie=3D48V, Rm Alain (691144423) from Huawei is informed","system","27=
0131","02-01-2025 18:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003987354","Ebeba","=
","02-01-2025 18:22:51","02-01-2025 16:58:52","02-01-2025 17:03:21","Cascad=
ed Incident from TTO3965361","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active: no power issue, site is on grid with U=
baie=3D48V, Rm Alain (691144423) from Huawei is informed","system","270130"=
,"02-01-2025 18:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0003987353","Nkenglik=
ok","","02-01-2025 18:22:51","02-01-2025 16:58:52","02-01-2025 17:03:21","C=
ascaded Incident from TTO3965361","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active: no power issue, site is on gr=
id with Ubaie=3D48V, Rm Alain (691144423) from Huawei is informed","system"=
,"270132","02-01-2025 18:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003987357","Mambine"=
,"","02-01-2025 18:22:51","02-01-2025 16:58:52","02-01-2025 17:03:21","Casc=
aded Incident from TTO3965361","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active: no power issue, site is on grid with=
 Ubaie=3D48V, Rm Alain (691144423) from Huawei is informed","system","27013=
3","02-01-2025 18:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0003987351","Mandoumb=
a OCM","","02-01-2025 18:22:50","02-01-2025 16:58:52","02-01-2025 17:03:21"=
,"Cascaded Incident from TTO3965361","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active: no power issue, site is on=
 grid with Ubaie=3D48V, Rm Alain (691144423) from Huawei is informed","syst=
em","270131","02-01-2025 18:22:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0003987352","Mbankomo=
 IHS","","02-01-2025 18:22:50","02-01-2025 16:58:52","02-01-2025 17:03:21",=
"Cascaded Incident from TTO3965361","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active: no power issue, site is on grid=
 with Ubaie=3D48V, Rm Alain (691144423) from Huawei is informed","system","=
270128","02-01-2025 18:22:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0003987350","Sous Pre=
fecture","","02-01-2025 18:22:50","02-01-2025 16:58:52","02-01-2025 17:03:2=
1","Cascaded Incident from TTO3965361","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active: no power issue, site is on g=
rid with Ubaie=3D48V, Rm Alain (691144423) from Huawei is informed","system=
","270129","02-01-2025 18:22:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003987321","N=
kolfon Cimencam","","02-01-2025 18:15:56","02-01-2025 18:27:41","02-01-2025=
 18:30:35","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","=
Cascade Active","No power issue on site , Ubaie=3D54.4V site On Grid The Tx=
 FME Georges 697461814 from Huawei is informed. repetitive issue ","kouoh.j=
ean@ihstowers.com","272147","02-01-2025 18:15:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003987015","S=
OA UNIVERSITY STADIUM","","02-01-2025 17:28:44","02-01-2025 16:45:02","02-0=
1-2025 16:50:49","ACTIVE//no  power issue UBaie =3D55.2 V site on Grid. The=
 Rm Alain (691144423) from Huawei is informed","Siligap Boris","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE//no  power issue UBaie =3D55.2 V site on Grid. The Rm Alain (6911444=
23) from Huawei is informed","kouoh.jean@ihstowers.com","2623","02-01-2025 =
17:28:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0003987003","S=
OA TOWN","","02-01-2025 17:26:05","02-01-2025 16:44:46","02-01-2025 16:49:5=
6","Active No power issue on site, site on Grid with   Ubaie=3D54.3V The TX=
 FME SYNPHORIEN /615295205 of Huawei is informed.","Siligap Boris","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active No power issue on site, site on Grid with=20

Ubaie=3D54.3V The TX FME SYNPHORIEN /615295205 of Huawei is informed.
","kouoh.jean@ihstowers.com","2480","02-01-2025 17:26:05","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0003986993","Men=
dong NB","","02-01-2025 17:23:52","02-01-2025 17:02:47","02-01-2025 17:07:4=
4","Active: No power issue,site is on grid with Ubaie=3D53V, Hosiah(6996996=
94) from Huawei is informed","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active: No power issue,site is =
on grid with Ubaie=3D53V, Hosiah(699699694) from Huawei is informed","steph=
ane.nkamwa@ihstowers.com","1265","02-01-2025 17:23:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0003986918","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, I=
HS_YND_697, IHS_YND_330, IHS_YND_350, IHS_YND_335, IHS_YND_349","02-01-2025=
 17:08:59","02-01-2025 16:58:52","02-01-2025 17:03:21","Active: no power is=
sue, site is on grid with Ubaie=3D48V, Rm Alain (691144423) from Huawei is =
informed","Fanda Brice","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active: no power issue, site is on grid=
 with Ubaie=3D48V, Rm Alain (691144423) from Huawei is informed","kouoh.jea=
n@ihstowers.com","608","02-01-2025 17:08:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0003986778","SAA 2","=
","02-01-2025 16:30:10","02-01-2025 16:17:54","02-01-2025 16:41:34","Cascad=
ed Incident from TTO3965145","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site on gen due to grid outage, site went=
 down because gen stopped due to hight temperature // He open the shelter o=
f gen and gen manually started","system","272921","02-01-2025 16:30:10","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003986752","S=
aa","IHS_YND_401, IHS_YND_404","02-01-2025 16:26:13","02-01-2025 16:17:54",=
"02-01-2025 16:41:34","site on gen due to grid outage, site went down becau=
se gen stopped due to hight temperature // He open the shelter of gen and g=
en manually started","Parker Tchoup","Equipment Repair","Passive","ACDG Gen=
","ACDG - Radiator","site on gen due to grid outage, site went down because=
 gen stopped due to hight temperature // He open the shelter of gen and gen=
 manually started","kouoh.jean@ihstowers.com","500","02-01-2025 16:26:13","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003986523","E=
kie-Elegance","","02-01-2025 15:43:21","02-01-2025 15:35:13","02-01-2025 16=
:23:53","Grid outage//MDG of 20 kva has deployed","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG=
 of 20 kva has deployed","kouoh.jean@ihstowers.com","489","02-01-2025 15:43=
:21","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0003986494","Eto=
ug ebe biscuiterie","","02-01-2025 15:39:08","02-01-2025 15:33:59","02-01-2=
025 16:21:20","site went down due to disjunctionning of Cb(63A) in PWC // H=
e  he did a bridge with annothe Cb(63A), site on grid","Hyemafo Gildas","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker =
Issue","site went down due to disjunctionning of Cb(63A) in PWC // He  he d=
id a bridge with annothe Cb(63A), site on grid","stephane.nkamwa@ihstowers.=
com","309","02-01-2025 15:39:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003986379","Abattoir=
","","02-01-2025 15:21:30","02-01-2025 14:30:22","02-01-2025 15:20:22","Cas=
caded Incident from TTO3964331","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because gen failed to=
 start due to grid bad voltage // gen manually started","system","279035","=
02-01-2025 15:21:30","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003986077","OBA=
M NGOLA OCM","","02-01-2025 14:50:14","02-01-2025 14:41:06","02-01-2025 18:=
34:32","site went down due to work(Pascaline(677548320)/ IHS, remplacement =
of  MPR) // End of Work","MINKA NICOLAS","Equipment Replacement","Passive",=
"Planned Activity","Planned Activity - Passive","site went down due to work=
(Pascaline(677548320)/ IHS, remplacement of  MPR) // End of Work","stephane=
.nkamwa@ihstowers.com","548","02-01-2025 14:50:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003986055","ETOUDI C=
HAPELLE","","02-01-2025 14:45:10","02-01-2025 14:30:22","02-01-2025 15:20:2=
2","Cascaded Incident from TTO3964331","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down because gen fai=
led to start due to grid bad voltage // gen manually started","system","279=
035","02-01-2025 14:45:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003986056","Etoudi 2=
","","02-01-2025 14:45:10","02-01-2025 14:30:22","02-01-2025 15:20:22","Cas=
caded Incident from TTO3964331","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because gen failed to=
 start due to grid bad voltage // gen manually started","system","279036","=
02-01-2025 14:45:10","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003986048","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","02-01-2025 14:43:44","02-01-2=
025 14:30:22","02-01-2025 15:20:22","site went down because gen failed to s=
tart due to grid bad voltage // gen manually started","Fabrice Pouakam","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","site=
 went down because gen failed to start due to grid bad voltage // gen manua=
lly started","stephane.nkamwa@ihstowers.com","803","02-01-2025 14:43:44","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0003985895","A=
cropole","","02-01-2025 14:23:18","02-01-2025 14:07:10","02-01-2025 14:38:2=
4","grid outage, site went down because gen failed to start due to start fa=
illure // gen manually started(investigation ongoing)","MINKA NICOLAS","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage, si=
te went down because gen failed to start due to start faillure // gen manua=
lly started(investigation ongoing)","kouoh.jean@ihstowers.com","969","02-01=
-2025 14:23:18","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003985603","N=
yanon","","02-01-2025 13:38:19","02-01-2025 13:33:13","02-01-2025 13:59:03"=
,"No power issue  site on Gen  Ubaie=3D 55.5V.  The TX FME Gr=E9goire  //65=
2070658//  from huawei is informed .","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue  site on Gen  Ubaie=3D 55.5V.  The TX FME Gr=E9goire  //65=
2070658//  from huawei is informed","christian.fonkou@ihstowers.com","308",=
"02-01-2025 13:38:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003985530","B=
astos Bethesda","","02-01-2025 13:24:16","02-01-2025 13:18:05","02-01-2025 =
13:26:35","Grid outage, site went down before gen start due to poor battery=
 backup // gen start automatically","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // gen start automaticall=
y","christian.fonkou@ihstowers.com","372","02-01-2025 13:24:16","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003985395","Etoudi 2=
","","02-01-2025 12:50:10","02-01-2025 12:46:59","02-01-2025 13:02:59","Cas=
caded Incident from TTO3963586","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down becazuse=
 gen fails to start due to grid contactor faulty // he bypass it and manual=
ly start the gen","system","270975","02-01-2025 12:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003985393","Abattoir=
","","02-01-2025 12:50:10","02-01-2025 12:46:59","02-01-2025 13:02:59","Cas=
caded Incident from TTO3963586","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down becazuse=
 gen fails to start due to grid contactor faulty // he bypass it and manual=
ly start the gen","system","270975","02-01-2025 12:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003985394","ETOUDI C=
HAPELLE","","02-01-2025 12:50:10","02-01-2025 12:46:59","02-01-2025 13:02:5=
9","Cascaded Incident from TTO3963586","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cazuse gen fails to start due to grid contactor faulty // he bypass it and =
manually start the gen","system","270975","02-01-2025 12:50:10","Sagemcom C=
MR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003985381","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","02-01-2025 12:48:06","02-01-2=
025 12:46:59","02-01-2025 13:02:59","Grid outage, site went down becazuse g=
en fails to start due to grid contactor faulty // he bypass it and manually=
 start the gen","Fabrice Pouakam","Equipment Repair","Passive","Control Pan=
el","ATS-AMF Issue","Grid outage, site went down becazuse gen fails to star=
t due to grid contactor faulty // he bypass it and manually start the gen",=
"emmanuel.ghani@ihstowers.com","68","02-01-2025 12:48:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0003985077","M=
vog Mbi New","","02-01-2025 12:04:53","02-01-2025 11:55:46","02-01-2025 13:=
41:43","Site went down due CB (125A) faulty // he bypass it site on grid","=
MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Circuit Breaker Issue","Site went down due CB (125A) faulty // he bypass =
it site on grid","christian.fonkou@ihstowers.com","548","02-01-2025 12:04:5=
3","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003985049","M=
ontee-Des-Soeurs","","02-01-2025 12:02:11","02-01-2025 11:54:02","02-01-202=
5 12:07:33","Grid outage, site went down before gen start due to poor batte=
ry backup // gen start automatically","Hyemafo Gildas","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup // gen start automatic=
ally","christian.fonkou@ihstowers.com","490","02-01-2025 12:02:11","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003985030","O=
lembe-Terminus","","02-01-2025 11:59:10","02-01-2025 11:54:05","02-01-2025 =
12:11:12","Grid outage, site went down before gen start due to poor battery=
 backup // Gen start automatically","Fabrice Pouakam","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down before gen start due to poor battery backup // Gen start automatica=
lly","christian.fonkou@ihstowers.com","306","02-01-2025 11:59:10","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003985026","Eko=
unou","","02-01-2025 11:58:18","02-01-2025 11:55:30","02-01-2025 12:16:54",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
ted automatically","Albran Byorel","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen started automatically","emmanuel.ghani@ihsto=
wers.com","170","02-01-2025 11:58:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0003984620","B=
ondjock","","02-01-2025 10:47:13","02-01-2025 10:42:04","02-01-2025 10:49:3=
1","Grid outage, site went down before gen start due to poor battery backup=
 // Gen automatically started","Fanda Brice","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // Gen automatically started","c=
hristian.fonkou@ihstowers.com","310","02-01-2025 10:47:13","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0003984426","Beh=
ind P T school Yde","","02-01-2025 10:16:51","02-01-2025 10:14:48","02-01-2=
025 13:02:25","Site went down due to insufficient of retifier (02/3 faulty)=
  // he added 02 rectifiers: site on grid","Paul BIBOUM","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down due to insufficie=
nt of retifier (02/3 faulty)  // he added 02 rectifiers: site on grid","emm=
anuel.ghani@ihstowers.com","124","02-01-2025 10:16:51","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003984381","Mok=
olo Yaounde","","02-01-2025 10:05:44","02-01-2025 10:03:38","02-01-2025 11:=
50:38","Grid outage, no space to deploy MDG // Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spa=
ce to deploy MDG // Grid return","emmanuel.ghani@ihstowers.com","127","02-0=
1-2025 10:05:44","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0003984361","Bas=
tos Bethesda","","02-01-2025 10:04:34","02-01-2025 10:03:30","02-01-2025 10=
:06:30","Grid outage, site went down before gen start due to poor battery b=
ackup // gen start automatically","Mboua Thierry","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // gen start automatically"=
,"emmanuel.ghani@ihstowers.com","65","02-01-2025 10:04:34","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0003984338","SIM=
BOCK BONAMBAPE","","02-01-2025 10:00:46","02-01-2025 09:59:21","02-01-2025 =
10:43:55","site went down because 4/7 rectifier disfunctionning//he reset t=
he rectifiers","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to 4/7 rectifier disfunction // he res=
et it and manually started","emmanuel.ghani@ihstowers.com","86","02-01-2025=
 10:00:46","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003984251","Pha=
rmacie SION","","02-01-2025 09:40:27","02-01-2025 09:34:23","02-01-2025 09:=
44:23","Grid outage, site went down before gen start due to poor battery ba=
ckup // gen start automatically","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // gen start automatically","e=
mmanuel.ghani@ihstowers.com","365","02-01-2025 09:40:27","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003984238","OBA=
M NGOLA OCM","","02-01-2025 09:38:04","02-01-2025 09:26:01","02-01-2025 10:=
06:01","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // he bypass grid and manually starts the gen","MINKA N=
ICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, site went down because gen start and stopped due t=
o grid bad voltage // he bypass grid and manually starts the gen","emmanuel=
.ghani@ihstowers.com","724","02-01-2025 09:38:04","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0003983821","Nko=
lbong","","02-01-2025 08:13:21","02-01-2025 08:10:09","02-01-2025 08:20:09"=
,"Active // No power issue UBaie =3D54,7V site on Grid. The FME TX SYMPHORI=
EN (675295205) From Huawei is informed","Delor Telezing","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue UBaie =3D54,7V site on Grid. The FME TX SYMPHORIEN (6752=
95205) From Huawei is informed","emmanuel.ghani@ihstowers.com","193","02-01=
-2025 08:13:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003983773","ETOUDI C=
HAPELLE","","02-01-2025 08:01:30","02-01-2025 07:57:34","02-01-2025 08:29:3=
4","Cascaded Incident from TTO3961792","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause gen start and stopped with aver current alarm // reset of gen card do=
ne and gen started","system","266772","02-01-2025 08:01:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003983772","Abattoir=
","","02-01-2025 08:01:30","02-01-2025 07:57:34","02-01-2025 08:29:34","Cas=
caded Incident from TTO3961792","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen start and stopped with aver current alarm // reset of gen card done and=
 gen started","system","266773","02-01-2025 08:01:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003983774","Etoudi 2=
","","02-01-2025 08:01:30","02-01-2025 07:57:34","02-01-2025 08:29:34","Cas=
caded Incident from TTO3961792","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen start and stopped with aver current alarm // reset of gen card done and=
 gen started","system","266772","02-01-2025 08:01:30","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003983756","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","02-01-2025 07:59:41","02-01-2=
025 07:57:34","02-01-2025 08:29:34","Grid outage, site went down because ge=
n start and stopped with over current alarm // reset of gen card done and g=
en started","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Grid outage, site went down because gen start and stoppe=
d with over current alarm // reset of gen card done and gen started","emman=
uel.ghani@ihstowers.com","128","02-01-2025 07:59:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003983132","N=
gouetou","","02-01-2025 04:22:31","02-01-2025 04:18:23","02-01-2025 05:34:2=
3","No power issue on site, site on Gen The Tx FME Gregoire/654547479 from =
huawei is informed","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site, sit=
e on Gen The Tx FME Gregoire/654547479 from huawei is informed","olivier.kw=
edi@ihstowers.com","249","02-01-2025 04:22:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0003982784","D=
ong","","02-01-2025 01:37:50","02-01-2025 01:32:41","02-01-2025 03:12:04","=
hybrid-Gen Active: No power issue, site on Battery  With Ubaie=3D51V,  Greg=
oire (654547479) from Huawei is informed","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","hybri=
d-Gen Active: No power issue, site on Battery  With Ubaie=3D51V,  Gregoire =
(654547479) from Huawei is informed","olivier.kwedi@ihstowers.com","310","0=
2-01-2025 01:37:50","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0003982608","Mon=
tee-Jouvence-II","","02-01-2025 00:15:26","02-01-2025 00:10:21","02-01-2025=
 01:03:21","site went down because pwc overload(12k/280A) // Gen manually s=
tarted","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","site went down because pwc overload(12k/280A) // Gen =
manually started","ludivine.ngamaleu@ihstowers.com","306","02-01-2025 00:15=
:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_743","NOCINC0003982518","Ngousso =
Vallee","","01-01-2025 23:36:54","01-01-2025 23:31:49","02-01-2025 02:49:13=
","Active // No power issue UBaie =3D54,2V site on Grid. The FME TX SYMPHOR=
IEN (675295205) From Huawei is informed","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 // No power issue UBaie =3D54,2V site on Grid. The FME TX SYMPHORIEN (6752=
95205) From Huawei is informed","ludivine.ngamaleu@ihstowers.com","305","01=
-01-2025 23:36:54","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0003982508","Tsi=
nga village","","01-01-2025 23:33:57","01-01-2025 23:27:51","02-01-2025 02:=
27:52","Active // No power issue UBaie =3D54,7V site on Grid. The FME TX SY=
MPHORIEN (675295205) From Huawei is informed","Delor Telezing","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No power issue UBaie =3D54,7V site on Grid. The FME TX SYMPHORIEN=
 (675295205) From Huawei is informed","ludivine.ngamaleu@ihstowers.com","36=
6","01-01-2025 23:33:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003982442","ETOUDI C=
HAPELLE","","01-01-2025 23:08:40","01-01-2025 23:00:57","02-01-2025 00:22:3=
0","Cascaded Incident from TTO3960232","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen Failed to start due to Grid contactor faulty // He bypass the Grid=
 contactor and site on Gen","system","463","01-01-2025 23:08:40","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003982441","Abattoir=
","","01-01-2025 23:08:40","01-01-2025 23:00:57","02-01-2025 00:22:30","Cas=
caded Incident from TTO3960232","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en Failed to start due to Grid contactor faulty // He bypass the Grid conta=
ctor and site on Gen","system","463","01-01-2025 23:08:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003982443","Etoudi 2=
","","01-01-2025 23:08:40","01-01-2025 23:00:57","02-01-2025 00:22:30","Cas=
caded Incident from TTO3960232","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en Failed to start due to Grid contactor faulty // He bypass the Grid conta=
ctor and site on Gen","system","463","01-01-2025 23:08:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0003982418","E=
toudi","IHS_YND_244, IHS_YND_694, IHS_YND_211","01-01-2025 23:02:04","01-01=
-2025 23:00:57","02-01-2025 00:22:30","Grid outage site went down because G=
en Failed to start due to Grid contactor faulty // He bypass the Grid conta=
ctor and site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","ATS-AMF Issue","Grid outage site went down because Gen Failed to=
 start due to Grid contactor faulty // He bypass the Grid contactor and sit=
e on Gen","olivier.kwedi@ihstowers.com","68","01-01-2025 23:02:04","Sagemco=
m CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0003982289","SIM=
BOCK BONAMBAPE","","01-01-2025 22:17:04","01-01-2025 22:11:09","01-01-2025 =
23:11:19","site went down because the rectifier dysfonction on site // He r=
eset the rectifier","Hyemafo Gildas","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","site went down because the rectifier dysfonction on =
site // He reset the rectifier","ludivine.ngamaleu@ihstowers.com","790","01=
-01-2025 22:17:04","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003982281","Men=
dong3","","01-01-2025 22:15:34","01-01-2025 22:10:28","02-01-2025 03:00:53"=
,"grid outage no space to deploy a mobil gen // grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","grid outage no spa=
ce to deploy a mobil gen // grid return","ludivine.ngamaleu@ihstowers.com",=
"307","01-01-2025 22:15:34","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003982225","Nsi=
meyong Terre Rouge","","01-01-2025 22:01:37","01-01-2025 21:53:57","01-01-2=
025 22:04:59","Grid outage, Site went down before Gen start due to poor bac=
kup// Grid power return","MINKA NICOLAS","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Grid power return","kamga.virgile@ihstower=
s.com","461","01-01-2025 22:01:37","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0003981958","MBA=
LNGONG LYCEE","","01-01-2025 21:01:58","01-01-2025 20:57:46","01-01-2025 21=
:46:11","Grid outage site went down because Gen started and  stopped due to=
 Grid contactor faulty // He bypass the Grid contactor and site on Grid","F=
anda Brice","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","G=
rid outage site went down because Gen started and  stopped due to Grid cont=
actor faulty // He bypass the Grid contactor and site on Grid","kamga.virgi=
le@ihstowers.com","254","01-01-2025 21:01:58","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0003981629","Eto=
ug ebe biscuiterie","","01-01-2025 20:19:03","01-01-2025 20:01:43","02-01-2=
025 00:06:41","Site went down because Gen Failed to Start due to PSC3 dysfu=
ntionning// he reset the PSC3 and Gen manually started","Hyemafo Gildas","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Site went dow=
n because Gen Failed to Start due to PSC3 dysfuntionning// he reset the PSC=
3 and Gen manually started","kamga.virgile@ihstowers.com","1041","01-01-202=
5 20:19:03","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0003980412","Beh=
ind P T school Yde","","01-01-2025 17:15:34","01-01-2025 17:11:21","01-01-2=
025 18:29:43","site went down due to 01/02 rectifier faulty // He reset con=
troller, site in 01 rectifiers","Paul BIBOUM","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","site went down due to 01/02 rectifier fault=
y // He reset controller, site in 01 rectifiers","kamga.virgile@ihstowers.c=
om","254","01-01-2025 17:15:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0003980243","N=
kolbong","","01-01-2025 16:42:37","01-01-2025 16:01:19","01-01-2025 17:55:3=
2","site on gen due to grid outage, , site went down because (01/08) rectif=
ier faulty // He removed rectifier faulty, site stabilized in 07 rectifiers=
","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","site on gen due to grid outage, , site went down because (01/08) recti=
fier faulty // He removed rectifier faulty, site stabilized in 07 rectifier=
s","alexandre.kamal@ihstowers.com","2479","01-01-2025 16:42:37","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003979920","Emana ly=
cee 2","","01-01-2025 15:41:21","01-01-2025 15:38:14","01-01-2025 17:30:49"=
,"Cascaded Incident from TTO3957355","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down bec=
ause gen failed to start due to hight temperature // He added the water in =
radiator, site on gen","system","275086","01-01-2025 15:41:21","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003979919","Messassi=
 okolo","","01-01-2025 15:41:21","01-01-2025 15:38:14","01-01-2025 17:30:49=
","Cascaded Incident from TTO3957355","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, site went down be=
cause gen failed to start due to hight temperature // He added the water in=
 radiator, site on gen","system","275088","01-01-2025 15:41:21","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003979918","Emana Ly=
cee","","01-01-2025 15:41:21","01-01-2025 15:38:14","01-01-2025 17:30:49","=
Cascaded Incident from TTO3957355","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site went down becau=
se gen failed to start due to hight temperature // He added the water in ra=
diator, site on gen","system","275087","01-01-2025 15:41:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003979916","Mballa 4=
","","01-01-2025 15:41:20","01-01-2025 15:38:14","01-01-2025 17:30:49","Cas=
caded Incident from TTO3957355","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, site went down because g=
en failed to start due to hight temperature // He added the water in radiat=
or, site on gen","system","275086","01-01-2025 15:41:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003979917","EMANA BI=
LICK CITY","","01-01-2025 15:41:20","01-01-2025 15:38:14","01-01-2025 17:30=
:49","Cascaded Incident from TTO3957355","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid outage, site went down=
 because gen failed to start due to hight temperature // He added the water=
 in radiator, site on gen","system","275087","01-01-2025 15:41:20","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003979912","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","01=
-01-2025 15:39:43","01-01-2025 15:38:14","01-01-2025 17:51:24","grid outage=
, site went down because gen failed to start due to hight temperature // He=
 added the water in radiator, site on gen","Fabrice Pouakam","Equipment Rep=
air","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","=
grid outage, site went down because gen failed to start due to hight temper=
ature // He added the water in radiator, site on gen","alexandre.kamal@ihst=
owers.com","90","01-01-2025 15:39:43","Sagemcom CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0003979898","Eto=
udi2","","01-01-2025 15:36:33","01-01-2025 15:18:18","01-01-2025 16:26:20",=
"site went down due to disjunctionning Cb(80A) in PWC //  he did a bridge w=
ith annothe Cb(80A), site on grid","Delor Telezing","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went do=
wn due to disjunctionning Cb(80A) in PWC //  he did a bridge with annothe C=
b(80A), site on grid","kamga.virgile@ihstowers.com","1096","01-01-2025 15:3=
6:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003979827","Akak-Nko=
zoa-MTN-IHS","","01-01-2025 15:26:40","01-01-2025 14:43:14","01-01-2025 14:=
48:05","Cascaded Incident from TTO3957232","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active // No  power issue UB=
aie =3D54,7V site on Grid. The FME TX  SYMPHORIEN (675295205) From Huawei i=
s informed","system","278442","01-01-2025 15:26:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003979811","S=
oa-II","IHS_YND_316, IHS_YND_324","01-01-2025 15:23:34","01-01-2025 14:43:1=
4","01-01-2025 14:48:05","Active // No  power issue UBaie =3D54,7V site on =
Grid. The FME TX  SYMPHORIEN (675295205) From Huawei is informed","Siligap =
Boris","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active // No  power issue UBaie =3D54,7V site on Grid. T=
he FME TX  SYMPHORIEN (675295205) From Huawei is informed","alexandre.kamal=
@ihstowers.com","2421","01-01-2025 15:23:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003979741","N=
kolfon Cimencam","","01-01-2025 15:07:54","01-01-2025 14:11:45","01-01-2025=
 14:16:10","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FME =
Georges 697461814 from Huawei is informed. repetitive issue ","Hyemafo Gild=
as","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site , Ubaie=3D54.4V site On Grid The Tx =
FME Georges 697461814 from Huawei is informed. repetitive issue ","alexandr=
e.kamal@ihstowers.com","3370","01-01-2025 15:07:54","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_316","NOCINC0003979629","Akak-Nkozoa-MTN-=
IHS","","01-01-2025 14:36:20","","","Cascaded Incident from TTO3957013","Fa=
brice Pouakam","","","","","","system","1450","01-01-2025 14:36:20","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_EDA_051","NOCINC0003979432","Nyanon",=
"","01-01-2025 14:03:11","01-01-2025 13:38:31","01-01-2025 13:43:41","No po=
wer issue on site U=3D56,3v site on gen Gregoire of huawei is informed","TI=
ENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site U=3D56,3v site o=
n gen Gregoire of huawei is informed","system","1480","01-01-2025 14:03:11"=
,"Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_263","NOCINC0003979350","Mendong Pl=
ateau","","01-01-2025 13:53:15","","","site alarming due to High temp 43=B0=
 // 27=B0c and alarm cleared","Hyemafo Gildas","Warning","Warning","ENVIRON=
MENT","Warning - High Temperature","site alarming due to High temp 43=B0 //=
 27=B0c and alarm cleared","kouoh.jean@ihstowers.com","185","01-01-2025 13:=
53:15","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_008","NOCINC0003979334","CNDH","","=
01-01-2025 13:51:26","","","site alarming due to High temp 49=B0 // 28=B0c =
 and alarm cleared","Paul BIBOUM","Warning","Warning","ENVIRONMENT","Warnin=
g - High Temperature","site alarming due to High temp 49=B0 // 28=B0c  and =
alarm cleared","kouoh.jean@ihstowers.com","367","01-01-2025 13:51:26","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003979290","A=
fanoya","","01-01-2025 13:36:39","01-01-2025 13:25:24","01-01-2025 13:30:49=
","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FME Georges 6=
97461814 from Huawei is informed. repetitive issue ","Hyemafo Gildas","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FME Georg=
es 697461814 from Huawei is informed. repetitive issue ","stephane.nkamwa@i=
hstowers.com","676","01-01-2025 13:36:39","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0003979216","Ngo=
usso Vallee","","01-01-2025 13:21:44","01-01-2025 12:16:26","01-01-2025 13:=
14:13","grid outage,gen start and stopped with alarm low oil pressure(not u=
nproven)//he reset the card and started the gen","Siligap Boris","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage,gen start=
 and stopped with alarm low oil pressure(not unproven)//he reset the card a=
nd started the gen","landry.etame@ihstowers.com","3918","01-01-2025 13:21:4=
4","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003979198","HOP=
ITAL GENERAL RAIL YDE","","01-01-2025 13:18:15","01-01-2025 13:04:07","01-0=
1-2025 13:38:26","grid outage, site went down due to gen overload (09kva, 1=
60A) // grid return","Delor Telezing","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","grid outage, site went down due to gen overload (09kv=
a, 160A) // grid return","landry.etame@ihstowers.com","849","01-01-2025 13:=
18:15","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003979097","San=
ta Barbara Gottam","","01-01-2025 12:47:19","01-01-2025 12:27:02","01-01-20=
25 13:11:57","site went down because gen failed to start due to grid bad vo=
ltage // Gen manually started","Delor Telezing","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","site went down because gen f=
ailed to start due to grid bad voltage // Gen manually started","landry.eta=
me@ihstowers.com","1218","01-01-2025 12:47:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003979093","Melen Ba=
'aba","","01-01-2025 12:47:11","01-01-2025 12:39:29","01-01-2025 12:52:29",=
"Cascaded Incident from TTO3956385","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen failed to start du=
e to alarm overccurent//he reset the card and started the gen","system","46=
2","01-01-2025 12:47:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003979094","TSINGA V=
ILLAGE 2","","01-01-2025 12:47:11","01-01-2025 12:39:29","01-01-2025 12:52:=
29","Cascaded Incident from TTO3956385","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,gen failed to sta=
rt due to alarm overccurent//he reset the card and started the gen","system=
","462","01-01-2025 12:47:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003979092","Nkolfoul=
ou 2","","01-01-2025 12:47:10","01-01-2025 12:39:29","01-01-2025 12:52:29",=
"Cascaded Incident from TTO3956385","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen failed to start du=
e to alarm overccurent//he reset the card and started the gen","system","46=
1","01-01-2025 12:47:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003979074","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","01-01-2025 12:44:39","0=
1-01-2025 12:39:29","01-01-2025 12:52:29","grid outage,gen failed to start =
due to alarm overccurent//he reset the card and started the gen","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid =
outage,gen failed to start due to alarm overccurent//he reset the card and =
started the gen","stephane.nkamwa@ihstowers.com","310","01-01-2025 12:44:39=
","Sagemcom CMR"
"Closed Complete","Warning","CTR_214","IHS_YND_296","NOCINC0003979057","Nko=
lfoulou","","01-01-2025 12:38:42","","","site on alarm because gen failed t=
o star due to alarm overccurent//he rest the card and started the gen","Sil=
igap Boris","Warning","Warning","POWER","Warning - Low Voltage","site on al=
arm because gen failed to star due to alarm overccurent//he rest the card a=
nd started the gen","kouoh.jean@ihstowers.com","490","01-01-2025 12:38:42",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003978969","H=
-General-Yde","","01-01-2025 12:16:45","01-01-2025 12:10:37","01-01-2025 13=
:16:21","grid outage,gen stopped with alarm high temp//he added water in ra=
diator","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Hig=
h Engine Temp - Coolant Level Issue","grid outage,gen stopped with alarm hi=
gh temp//he added water in radiator","stephane.nkamwa@ihstowers.com","369",=
"01-01-2025 12:16:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003978872","E=
bogo","","01-01-2025 11:55:18","01-01-2025 11:51:05","01-01-2025 11:57:39",=
"Site was on Gen due to Grid outage, Site went down due to poor backup// Ge=
n automatically started","Siligap Boris","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Site was on Gen due to Grid outag=
e, Site went down due to poor backup// Gen automatically started","stephane=
.nkamwa@ihstowers.com","254","01-01-2025 11:55:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0003978742","Carrefou=
rt Nkomo","","01-01-2025 11:33:30","01-01-2025 10:36:26","01-01-2025 13:50:=
19","Cascaded Incident from TTO3955801","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site went down due to (02/0=
5) rectifiers faulty // He changed 02 rectifiers, site on grid ","system","=
293246","01-01-2025 11:33:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0003978575","N=
komo","IHS_YND_174","01-01-2025 10:56:32","01-01-2025 10:36:26","01-01-2025=
 13:50:19","site went down due to (02/05) rectifiers faulty // He changed 0=
2 rectifiers, site on grid ","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module","site went down due to (02/05) rectifiers =
faulty // He changed 02 rectifiers, site on grid ","stephane.nkamwa@ihstowe=
rs.com","1207","01-01-2025 10:56:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003978236","Abattoir=
","","01-01-2025 09:28:10","01-01-2025 09:23:51","01-01-2025 09:37:33","Cas=
caded Incident from TTO3955414","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
Gen fails to start due to Grid contactor dysfunctionned caused by Grid bad =
voltage// He bypass the Grid Contactor, Site on Gen","system","1218159","01=
-01-2025 09:28:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003978238","Etoudi 2=
","","01-01-2025 09:28:10","01-01-2025 09:23:51","01-01-2025 09:37:33","Cas=
caded Incident from TTO3955414","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
Gen fails to start due to Grid contactor dysfunctionned caused by Grid bad =
voltage// He bypass the Grid Contactor, Site on Gen","system","1218158","01=
-01-2025 09:28:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003978237","ETOUDI C=
HAPELLE","","01-01-2025 09:28:10","01-01-2025 09:23:51","01-01-2025 09:37:3=
3","Cascaded Incident from TTO3955414","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
cause Gen fails to start due to Grid contactor dysfunctionned caused by Gri=
d bad voltage// He bypass the Grid Contactor, Site on Gen","system","121816=
0","01-01-2025 09:28:10","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003978231","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","01-01-2025 09:26:57","01-01-2=
025 09:23:51","01-01-2025 10:00:33","Grid outage, Site went down because Ge=
n fails to start due to Grid contactor dysfunctionned caused by Grid bad vo=
ltage// He bypass the Grid Contactor, Site on Gen","Fabrice Pouakam","Equip=
ment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, Site w=
ent down because Gen fails to start due to Grid contactor dysfunctionned ca=
used by Grid bad voltage// He bypass the Grid Contactor, Site on Gen","land=
ry.etame@ihstowers.com","187","01-01-2025 09:26:57","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0003977721","MBA=
LNGONG LYCEE","","01-01-2025 06:50:35","01-01-2025 06:26:31","01-01-2025 07=
:36:58","Grid fluctuation,site went down because Gen failed to start due to=
 bad voltage// he bypass the Grid and site on Gen","Fanda Brice","Grid Supp=
ly","Passive","Grid","National Grid - Grid Incomplete Phase","Grid fluctuat=
ion,site went down because Gen failed to start due to bad voltage// he bypa=
ss the Grid and site on Gen","landry.etame@ihstowers.com","1445","01-01-202=
5 06:50:35","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003977576","San=
ta Barbara Gottam","","01-01-2025 06:01:46","01-01-2025 05:57:37","01-01-20=
25 07:05:52","Grid fluctuation, site went down due to grid bad voltage,no R=
CP on site//he made a bridge with the Good phase","Delor Telezing","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation, site went down due to grid bad voltage,no RCP on site//he made a b=
ridge with the Good phase","rouselle.schoune@ihstowers.com","250","01-01-20=
25 06:01:46","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0003977500","Beh=
ind P T school Yde","","01-01-2025 05:24:19","01-01-2025 05:21:14","01-01-2=
025 06:35:34","Energy Meter disconnected, Site went down due to no automati=
on//Gen manually started","Paul BIBOUM","Equipment Repair","Passive","Contr=
ol Panel","ATS-AMF Issue","Energy Meter disconnected, Site went down due to=
 no automation//Gen manually started","rouselle.schoune@ihstowers.com","186=
","01-01-2025 05:24:19","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0003977349","Bit=
eng-Maetur","","01-01-2025 04:18:11","01-01-2025 04:10:06","01-01-2025 04:2=
1:19","Grid outage, site went down before gen start due to poor battery bac=
kup // Grid restored","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid restored","rouselle.schoune@=
ihstowers.com","486","01-01-2025 04:18:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0003976894","Biteng",=
"","01-01-2025 01:17:09","01-01-2025 00:02:59","01-01-2025 02:08:57","Site =
went down because CB(125A) in PWC due to load increase// CB put back on ","=
Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Circuit Breaker Issue","Site went down because CB(125A) in PWC due to =
load increase// CB put back on ","ange.kongo@ihstowers.com","4452","01-01-2=
025 01:17:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003976572","B=
iteng","","31-12-2024 23:55:12","31-12-2024 23:01:54","31-12-2024 23:41:27"=
,"Grid outage, site went down due to PWC disfunction // He reset PWC, Site =
on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Recti=
fier Module Overloaded","Grid outage, site went down due to PWC disfunction=
 // He reset PWC, Site on Grid","ange.kongo@ihstowers.com","3199","31-12-20=
24 23:55:12","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003976463","SOA=
 UNIVERSITY STADIUM","","31-12-2024 23:20:54","31-12-2024 23:04:47","01-01-=
2025 00:03:22","Grid ouage, site went down because gen start and stopped wi=
th alarm Over current (unprouven alarm)// He reset gen card , site manually=
  gen","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid ouage, site went down because gen start and stopped with a=
larm Over current (unprouven alarm)// He reset gen card , site manually  ge=
n","rouselle.schoune@ihstowers.com","1112","31-12-2024 23:20:54","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003976325","A=
fanoya","IHS_YND_762","31-12-2024 22:44:30","31-12-2024 22:37:26","01-01-20=
25 02:11:35","ACTIVE / No power issue site on Grid with U=3D54,4 V The Tx F=
ME Tchana Patrice 695007608 of huawei is informed","Hyemafo Gildas","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","ACTIVE / No power issue site on Grid with U=3D54,4 V The Tx FME Tchana=
 Patrice 695007608 of huawei is informed","ange.kongo@ihstowers.com","425",=
"31-12-2024 22:44:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003976315","N=
kolfon Cimencam","","31-12-2024 22:42:08","31-12-2024 22:37:26","31-12-2024=
 22:40:24","","Hyemafo Gildas","Cascade Outage","Active","Cascade Active","=
Cascade Active","ACTIVE / No power issue site on Grid with U=3D54,4 V The T=
x FME Tchana Patrice 695007608 of huawei is informed","ange.kongo@ihstowers=
.com","278642","31-12-2024 22:42:08","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0003976030","SAA=
 Entrance","","31-12-2024 21:28:44","31-12-2024 21:06:37","31-12-2024 21:50=
:19","Grid fluctuation,site went down because Gen failed to start due to ba=
d voltage,no RCP on site// he bypass the Grid and site on Gen","Parker Tcho=
up","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation,site went down because Gen failed to start due to bad v=
oltage,no RCP on site// he bypass the Grid and site on Gen","etienne.itondo=
@ihstowers.com","1328","31-12-2024 21:28:44","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003976003","Bit=
eng","","31-12-2024 21:22:49","31-12-2024 21:13:42","31-12-2024 21:55:45","=
Site went down because CB (125A) in PWC due to PWC disfunction// CB put bac=
k on","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Circuit Breaker Issue","Site went down because CB (125A) in PWC=
 due to PWC disfunction// CB put back on","ludivine.ngamaleu@ihstowers.com"=
,"548","31-12-2024 21:22:49","Sagemcom CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0003975948","Emo=
mbo Esssomba","","31-12-2024 21:14:12","31-12-2024 21:05:07","31-12-2024 23=
:19:56","Grid outage, site went down because gen stopped with alarm low oil=
 pressure(alarm unproven)//he reset it and started the gen","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage, site went down because gen stopped with alarm low oil pressure(alarm =
unproven)//he reset it and started the gen","ludivine.ngamaleu@ihstowers.co=
m","546","31-12-2024 21:14:12","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003975933","NKO=
MEKUI OCM","","31-12-2024 21:12:22","31-12-2024 21:04:15","31-12-2024 21:48=
:22","no power issue on site U=3D54.5  V site on Gen.  Site impacted by Mba=
nkolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"no power issue on site U=3D54.5  V site on Gen. Site impacted by Mbankolo=
 Camtel and not managing by IHS
","ludivine.ngamaleu@ihstowers.com","488","31-12-2024 21:12:22","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0003975446","Carrefou=
r Ayissi Ele","","31-12-2024 19:45:10","31-12-2024 18:46:25","31-12-2024 19=
:51:10","Cascaded Incident from TTO3951912","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid fluctuation,site went=
 down because 02/03 rectifiers dysfunction// he reset it and Site is on Gri=
d","system","270833","31-12-2024 19:45:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003975340","A=
fanoya","","31-12-2024 19:21:35","31-12-2024 19:19:24","31-12-2024 21:20:59=
","Active//No power issue on site , Ubaie=3D54.4V site On Grid The Tx RM  A=
LAIN 691144423 from Huawei is informed. repetitive issue ","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue on site , Ubaie=3D54.4V site On Grid Th=
e Tx RM  ALAIN 691144423 from Huawei is informed. repetitive issue ","olivi=
er.kwedi@ihstowers.com","132","31-12-2024 19:21:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0003975318","R=
d-Pt-Express","","31-12-2024 19:16:02","31-12-2024 19:07:51","31-12-2024 20=
:46:01","Grid outage ,no space to deploy MDG// Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,no spa=
ce to deploy MDG// Grid return","olivier.kwedi@ihstowers.com","492","31-12-=
2024 19:16:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003975280","N=
kozoa","","31-12-2024 19:05:05","31-12-2024 19:02:59","31-12-2024 19:32:21"=
,"	site went down because gen failed to start due to grid bad voltage // Gr=
id voltage stabilized","Fabrice Pouakam","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","	site went down because gen failed =
to start due to grid bad voltage // Grid voltage stabilized","olivier.kwedi=
@ihstowers.com","127","31-12-2024 19:05:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003975233","Saa","",=
"31-12-2024 18:52:20","31-12-2024 18:46:25","31-12-2024 19:51:10","Cascaded=
 Incident from TTO3951912","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuation,site went down because 02/=
03 rectifiers dysfunction// he reset it and Site is on Grid","system","2708=
34","31-12-2024 18:52:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0003975232","SAA Entr=
ance","","31-12-2024 18:52:20","31-12-2024 18:46:25","31-12-2024 19:51:10",=
"Cascaded Incident from TTO3951912","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation,site went down be=
cause 02/03 rectifiers dysfunction// he reset it and Site is on Grid","syst=
em","270833","31-12-2024 18:52:20","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0003975226","SAA=
 2","IHS_YND_810, IHS_YND_542, IHS_YND_405","31-12-2024 18:51:30","31-12-20=
24 18:46:25","31-12-2024 19:51:10","Grid fluctuation,site went down because=
 02/03 rectifiers dysfunction// he reset it and Site is on Grid","Parker Tc=
houp","Equipment Repair","Passive","Rectifier","Rectifier Module","Grid flu=
ctuation,site went down because 02/03 rectifiers dysfunction// he reset it =
and Site is on Grid","ludivine.ngamaleu@ihstowers.com","306","31-12-2024 18=
:51:30","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0003975209","Bas=
tos Bethesda","","31-12-2024 18:47:45","31-12-2024 18:40:37","31-12-2024 18=
:47:58","Grid outage, Site went down before Gen start due to poor backup// =
Grid return","Mboua Thierry","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, Site went down before Gen start =
due to poor backup// Grid return","ludivine.ngamaleu@ihstowers.com","429","=
31-12-2024 18:47:45","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003975201","Mok=
olo Yaounde","","31-12-2024 18:46:10","31-12-2024 18:40:05","31-12-2024 18:=
48:36","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spa=
ce to deploy a MDG//Grid Restored","ludivine.ngamaleu@ihstowers.com","367",=
"31-12-2024 18:46:10","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003975052","NKO=
MEKUI OCM","","31-12-2024 18:14:58","31-12-2024 18:10:54","31-12-2024 21:00=
:22","No power issue on site U=3D54,3V site on gen site down because is imp=
acted by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site U=3D54,3V site on gen site down becaus=
e is impacted by Mbankolo Camtel and not managing by IHS","ludivine.ngamale=
u@ihstowers.com","246","31-12-2024 18:14:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003974923","T=
singa","","31-12-2024 17:45:32","31-12-2024 17:39:23","31-12-2024 17:55:10"=
,"Grid outage,site went down before Gen start due to poor battery backup// =
Gen started automatically","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage,site went down befo=
re Gen start due to poor battery backup// Gen started automatically","olivi=
er.kwedi@ihstowers.com","370","31-12-2024 17:45:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003974883","D=
amas","","31-12-2024 17:33:39","31-12-2024 17:23:33","31-12-2024 21:24:13",=
"Active//No power issue on site ,site on Grid with Ubaie=3D54.3 V he FME Th=
e TX FME Mbah Hosiah (674007438) is informed","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue on site ,site on Grid with Ubaie=3D54.3 V he FME The =
TX FME Mbah Hosiah (674007438) is informed","olivier.kwedi@ihstowers.com","=
607","31-12-2024 17:33:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003974862","T=
amtam Weekend","","31-12-2024 17:29:20","31-12-2024 17:21:14","31-12-2024 1=
8:31:36","site went down because gen stopped with alarm high temp// He add =
Water and opened all the door ","Hyemafo Gildas","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","site went do=
wn because gen stopped with alarm high temp// He add Water and opened all t=
he door ","olivier.kwedi@ihstowers.com","487","31-12-2024 17:29:20","Sagemc=
om CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0003974703","Clu=
b France","","31-12-2024 17:01:55","31-12-2024 16:53:45","31-12-2024 20:46:=
13","Grid Outage//Grid Restored","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Outage Issue","Grid Outage//Grid Restored","ludivine.ngamaleu=
@ihstowers.com","491","31-12-2024 17:01:55","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0003974680","Obo=
bogo","","31-12-2024 16:52:10","31-12-2024 16:49:05","31-12-2024 16:53:48",=
"Grid outage,site went down before Gen start due to poor battery backup// G=
en started automatically","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage,site went down befor=
e Gen start due to poor battery backup// Gen started automatically","ludivi=
ne.ngamaleu@ihstowers.com","186","31-12-2024 16:52:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003974564","Akak-Nko=
zoa-MTN-IHS","","31-12-2024 16:33:41","31-12-2024 16:27:30","31-12-2024 17:=
16:49","Cascaded Incident from TTO3951111","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","eneo outage, Site down du=
e to poor backup   //   Grid return","system","264892","31-12-2024 16:33:41=
","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0003974492","Beh=
ind P T school Yde","","31-12-2024 16:23:10","31-12-2024 16:19:03","31-12-2=
024 17:01:21","Site went down because  Fran=E7ois NDOUGOU // 657108640//  f=
rom IHS is working on site (SWAP GEN)//End Off work","Paul BIBOUM","Equipme=
nt Replacement","Passive","Planned Activity","Planned Activity - Passive","=
Site went down because  Fran=E7ois NDOUGOU // 657108640//  from IHS is work=
ing on site (SWAP GEN)//End Off work","ludivine.ngamaleu@ihstowers.com","24=
8","31-12-2024 16:23:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003974483","Scalom-I=
HS","","31-12-2024 16:20:30","31-12-2024 16:18:33","31-12-2024 20:43:14","C=
ascaded Incident from TTO3951010","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid Outage No free MDG to deploy waiting Grid Re=
stored","system","117","31-12-2024 16:20:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0003974480","A=
ccacia New","IHS_YND_505","31-12-2024 16:19:40","31-12-2024 16:18:33","31-1=
2-2024 20:52:41","Grid Outage//Grid Restored","","Grid Supply","Passive","G=
rid","National Grid - Grid Outage Issue","Grid Outage//Grid Restored","oliv=
ier.kwedi@ihstowers.com","68","31-12-2024 16:19:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003974425","N=
YOM 2 IHS","","31-12-2024 16:10:50","31-12-2024 16:02:40","31-12-2024 18:44=
:51","Grid Outage, site went because Gen stoppen with alarm ""high Temp"" d=
ue to Gen accordeon faulty// He added water,Open the Door and started Gen m=
anualy","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - H=
igh Engine Temp - Coolant Level Issue","Grid Outage, site went because Gen =
stoppen with alarm ""high Temp"" due to Gen accordeon faulty// He added wat=
er,Open the Door and started Gen manualy","olivier.kwedi@ihstowers.com","49=
1","31-12-2024 16:10:50","Sagemcom CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0003974254","Biy=
emassi LAC","","31-12-2024 15:43:12","31-12-2024 15:37:35","31-12-2024 20:4=
8:59","Grid Outage No Space to deploy a MDG// Grid Restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spa=
ce to deploy a MDG// Grid Restored","ludivine.ngamaleu@ihstowers.com","446"=
,"31-12-2024 15:43:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0003974025","B=
IYEMASSI NIKI","","31-12-2024 14:54:48","31-12-2024 14:46:40","31-12-2024 2=
0:50:43","Grid Outage Site went down due to PWC overloaded (12kva 250 A) //=
 Site Stabilized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module Overloaded","Grid Outage Site went down due to PWC overl=
oaded (12kva 250 A) // Site Stabilized","olivier.kwedi@ihstowers.com","489"=
,"31-12-2024 14:54:48","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003973758","N=
yanon","","31-12-2024 14:03:28","31-12-2024 13:59:22","31-12-2024 18:07:40"=
,"No Power issue on site , site on Grid with Ubaie=3D52.7 V The Tx Gregoire=
(654547479) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No Power issue on site , site on Grid with Ubaie=3D52.7 V The Tx Gregoire(=
654547479) from Huawei is informed","alexandre.kamal@ihstowers.com","248","=
31-12-2024 14:03:28","Sagemcom CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0003973472","Eto=
ug-Ebe 2","","31-12-2024 12:59:22","29-12-2024 18:29:36","31-12-2024 12:48:=
47","Grid outage, No space to deploy MDG // grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space =
to deploy MDG // grid return","kamga.virgile@ihstowers.com","152987","31-12=
-2024 12:59:22","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003973392","Pha=
rmacie SION","","31-12-2024 12:44:19","31-12-2024 12:34:10","31-12-2024 12:=
44:58","Grid outage, Site went down before Gen start due to poor backup// G=
en start automatically","Paul BIBOUM","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup// Gen start automatically","kamga.virgile@ihsto=
wers.com","610","31-12-2024 12:44:19","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003973385","NYO=
M 2 IHS","","31-12-2024 12:42:15","31-12-2024 11:59:33","31-12-2024 13:20:4=
9","Grid outage site went down because Gen stopped with alarm high temps //=
He added water and Gen manually started","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Gr=
id outage site went down because Gen stopped with alarm high temps //He add=
ed water and Gen manually started","kamga.virgile@ihstowers.com","4820","31=
-12-2024 12:42:15","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003973368","NYO=
M FACE MAETUR","","31-12-2024 12:40:22","31-12-2024 11:54:58","31-12-2024 1=
4:10:58","Grid Outage Gen failed to start due to and Not automatism//Gen Ma=
nually Started","Fabrice Pouakam","Equipment Repair","Passive","Control Pan=
el","ATS-AMF Issue","Grid Outage Gen failed to start due to and Not automat=
ism//Gen Manually Started","kamga.virgile@ihstowers.com","2725","31-12-2024=
 12:40:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003973106","O=
lembe-Terminus","","31-12-2024 11:42:10","31-12-2024 11:04:55","31-12-2024 =
12:40:54","Grid Outage Site went down due to PWC IPT Dysfunction because th=
e and Contactors end of stroke//He Bypass He and Site is on Grid","Fabrice =
Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Module Overloa=
ded","Grid Outage Site went down due to PWC IPT Dysfunction because the and=
 Contactors end of stroke//He Bypass He and Site is on Grid","alexandre.kam=
al@ihstowers.com","2236","31-12-2024 11:42:10","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0003972809","Mel=
en Ba'aba","","31-12-2024 10:51:21","31-12-2024 10:43:11","31-12-2024 10:48=
:30","Active//No power issue on site, Site on Grid UBAIE=3D54V  synphorien =
(675295205) From huawei is informed and Site UP AT=3D10:55 AM","Siligap Bor=
is","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue on site, Site on Grid UBAIE=3D54V  s=
ynphorien (675295205) From huawei is informed and Site UP AT=3D10:55 AM","k=
amga.virgile@ihstowers.com","491","31-12-2024 10:51:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003972546","Nkolo II=
 New","","31-12-2024 09:52:10","31-12-2024 09:13:18","31-12-2024 10:22:52",=
"Cascaded Incident from TTO3948710","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bec=
ause PWC ZTE dysfunctionning// He reset PWC and started Gen manualy","syste=
m","276571","31-12-2024 09:52:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003972534","M=
imboman-Village","IHS_YND_709","31-12-2024 09:49:25","31-12-2024 09:13:18",=
"31-12-2024 10:22:52","Grid outage, Site went down because PWC ZTE dysfunct=
ionning// He reset PWC and started Gen manualy","Mba Lazare Herve","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage=
, Site went down because PWC ZTE dysfunctionning// He reset PWC and started=
 Gen manualy","alexandre.kamal@ihstowers.com","2169","31-12-2024 09:49:25",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0003972533","NKO=
ABANG NKOLO 3","","31-12-2024 09:49:03","31-12-2024 07:37:17","31-12-2024 0=
9:57:08","Grid outage,Gen stopped with alarm high temp(alarm unproven)//he =
reset the gen card and started it","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage,Gen stopped with ala=
rm high temp(alarm unproven)//he reset the gen card and started it","kamga.=
virgile@ihstowers.com","7907","31-12-2024 09:49:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_736","NOCINC0003972530","CRF Nkoa=
bang","","31-12-2024 09:48:31","31-12-2024 09:11:01","31-12-2024 09:27:54",=
"Cascaded Incident from TTO3948680","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down due=
 to gen card dysfunctions// he reset it and gen started manually","system",=
"276820","31-12-2024 09:48:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0003972529","Nkoabang=
2","","31-12-2024 09:48:31","31-12-2024 09:11:01","31-12-2024 09:27:54","Ca=
scaded Incident from TTO3948680","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down due to=
 gen card dysfunctions// he reset it and gen started manually","system","27=
6820","31-12-2024 09:48:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0003972528","NGONA","=
","31-12-2024 09:48:31","31-12-2024 09:11:01","31-12-2024 09:27:54","Cascad=
ed Incident from TTO3948680","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down due to gen=
 card dysfunctions// he reset it and gen started manually","system","276819=
","31-12-2024 09:48:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003972509","N=
koabang","IHS_YND_295, IHS_YND_526, IHS_YND_736","31-12-2024 09:46:16","31-=
12-2024 09:11:01","31-12-2024 09:27:54","Grid outage, site went down due to=
 gen card dysfunctions// he reset it and gen started manually","Mba Lazare =
Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage, site went down due to gen card dysfunctions// he reset it and gen =
started manually","alexandre.kamal@ihstowers.com","2116","31-12-2024 09:46:=
16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003972121","E=
ssomba","","31-12-2024 08:31:18","31-12-2024 08:10:12","31-12-2024 10:38:53=
","Grid outage, site went down due to 02/05 rectifier alarming// he reset i=
t and site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Grid outage, site went down due to 02/05 rectifier=
 alarming// he reset it and site on Grid","alexandre.kamal@ihstowers.com","=
1268","31-12-2024 08:31:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003971648","M=
IMBOMAN LIBERTE","","31-12-2024 07:49:58","31-12-2024 07:44:49","31-12-2024=
 09:05:15","Grid Outage ;site went down because Main Gen faulty // MDG 20 K=
va has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Faulty","Grid Outage ;site went down because Main Gen fa=
ulty // MDG 20 Kva has deployed","alexandre.kamal@ihstowers.com","310","31-=
12-2024 07:49:58","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003971333","NYO=
M FACE MAETUR","","31-12-2024 07:18:50","31-12-2024 07:08:39","31-12-2024 0=
8:41:14","Grid fluctuation,site went down because 04/04 rectifiers dysfunct=
ion// he reset it","Fabrice Pouakam","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","Grid fluctuation,site went down because 0=
4/04 rectifiers dysfunction// he reset it","kamga.virgile@ihstowers.com","6=
12","31-12-2024 07:18:50","Sagemcom CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0003971245","Biy=
emassi LAC","","31-12-2024 06:56:55","31-12-2024 06:49:01","31-12-2024 07:2=
5:21","GRID outage, No space to deploy Mobile generator //Grid returned",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","GRID o=
utage, No space to deploy Mobile generator //Grid returned","kamga.virgile@=
ihstowers.com","726","31-12-2024 06:56:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003970903","S=
calom-IHS","","31-12-2024 05:30:13","31-12-2024 05:26:27","31-12-2024 07:21=
:06","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Access issue during, Grid outage //Grid returned","christian.fonkou@ihstowe=
rs.com","268634","31-12-2024 05:30:13","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0003970894","Acc=
acia New","IHS_YND_505","31-12-2024 05:28:33","31-12-2024 05:26:27","31-12-=
2024 07:29:52","Access issue during, Grid outage //Grid returned","","Acces=
s Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land L=
ord","Access issue during, Grid outage //Grid returned","christian.fonkou@i=
hstowers.com","128","31-12-2024 05:28:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003970799","MBIMBIM"=
,"","31-12-2024 04:41:41","31-12-2024 04:33:22","31-12-2024 04:34:22","Casc=
aded Incident from TTO3946808","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue on site with Ubaie=
=3D54V site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gregoire( 6520=
70658)from Huawei is informed","system","264533","31-12-2024 04:41:41","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003970801","Yoko MTN=
","","31-12-2024 04:41:41","31-12-2024 04:33:22","31-12-2024 04:34:22","Cas=
caded Incident from TTO3946808","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site with Ubaie=
=3D54V site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gregoire( 6520=
70658)from Huawei is informed","system","264533","31-12-2024 04:41:41","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003970800","Ngoum","=
","31-12-2024 04:41:41","31-12-2024 04:33:22","31-12-2024 04:34:22","Cascad=
ed Incident from TTO3946808","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue on site with Ubaie=3D=
54V site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gregoire( 6520706=
58)from Huawei is informed","system","264534","31-12-2024 04:41:41","Sagemc=
om CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0003970793","Mat=
sari","IHS_YND_456, IHS_YND_475, IHS_YND_473","31-12-2024 04:39:28","31-12-=
2024 04:33:22","31-12-2024 05:10:22","Active//No power issue on site with U=
baie=3D54V site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gregoire( =
652070658)from Huawei is informed","Parker Tchoup","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue on site with Ubaie=3D54V site on Gen (start threshold ubai=3D48.=
4V) The Tx Fme Gregoire( 652070658)from Huawei is informed","christian.fonk=
ou@ihstowers.com","367","31-12-2024 04:39:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003970660","Akak-Nko=
zoa-MTN-IHS","","31-12-2024 03:23:10","31-12-2024 03:21:01","31-12-2024 03:=
29:45","Cascaded Incident from TTO3946647","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","eneo outage, Site down du=
e to poor backup // Grid return","system","261757","31-12-2024 03:23:10","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003970613","S=
ous Prefecture","","31-12-2024 03:02:36","31-12-2024 02:55:21","31-12-2024 =
05:30:21","No power issue on site Ubaie:54,7V; site on Grid. The Tx FME Geo=
rges ( 697461814)) from Huawei is informed","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site Ubaie:54,7V; site on Grid. The Tx FME Georges ( 697461814=
)) from Huawei is informed","emmanuel.ghani@ihstowers.com","10272","31-12-2=
024 03:02:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_285","NOCINC0003970450","Nkolbiss=
on","IHS_YND_763","31-12-2024 01:45:20","31-12-2024 01:37:31","31-12-2024 0=
1:45:31","Grid outage, site went down before Gen start due to poor backup /=
/ Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down before Gen start due to poor backup // Gen start automatically","sy=
stem","469","31-12-2024 01:45:20","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003970448","Nko=
lbisson usines des eaux 2","","31-12-2024 01:44:35","31-12-2024 01:37:31","=
31-12-2024 01:45:31","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down before =
Gen start due to poor backup // Gen start automatically","christian.fonkou@=
ihstowers.com","275012","31-12-2024 01:44:35","Sagemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003970446","Bas=
tos Bir","","31-12-2024 01:43:36","31-12-2024 01:35:32","31-12-2024 02:03:3=
2","Grid outage, site went down before gen start due to poor battery backup=
 // Gen started automatically","Mboua Thierry","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Gen started automatically",=
"christian.fonkou@ihstowers.com","485","31-12-2024 01:43:36","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003970445","Mok=
olo Yaounde","","31-12-2024 01:42:32","31-12-2024 01:35:23","31-12-2024 02:=
03:23","Grid outage, No space to deploy a mobil gen // grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, No space to deploy a mobil gen // grid return","christian.fonkou@ihstower=
s.com","430","31-12-2024 01:42:32","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003970443","Sap=
eur","","31-12-2024 01:39:14","31-12-2024 01:33:09","31-12-2024 02:02:09","=
","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Battery Low","Grid outage, site went down before gen start due to poor=
 battery backup // Gen started automatically","christian.fonkou@ihstowers.c=
om","366","31-12-2024 01:39:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003970438","M=
ontee-Des-Soeurs","","31-12-2024 01:38:47","31-12-2024 01:35:42","31-12-202=
4 01:58:42","Grid outage, site went down before gen start due to poor batte=
ry backup // Gen manually started","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // Gen manually started",=
"emmanuel.ghani@ihstowers.com","186","31-12-2024 01:38:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003970435","B=
astos Bethesda","","31-12-2024 01:37:53","31-12-2024 01:34:49","31-12-2024 =
02:02:49","GRID OUTAGE, site went down before gen start due to poor battery=
 backup // gen start automatically","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","GRID OUTAGE, site went=
 down before gen start due to poor battery backup // gen start automaticall=
y","emmanuel.ghani@ihstowers.com","185","31-12-2024 01:37:53","Sagemcom CMR=
"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003970426","NYO=
M FACE MAETUR","","31-12-2024 01:37:01","31-12-2024 01:29:49","31-12-2024 0=
4:11:49","Grid outage, site went down because gen fails to start due to no =
automatisme on site // gen manually started","Fabrice Pouakam","Equipment R=
epair","Passive","Control Panel","ATS-AMF Issue","Grid outage, site went do=
wn because gen fails to start due to no automatisme on site // gen manually=
 started","christian.fonkou@ihstowers.com","433","31-12-2024 01:37:01","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003970425","M=
EHANDAN","","31-12-2024 01:36:55","31-12-2024 01:33:48","31-12-2024 02:53:4=
8","Grid fluctuation, site went down because gen ran untill fuel shortage /=
/ grid stabilize (refueling done)","Albran Byorel","Fuel Outage","Passive",=
"Diesel","Diesel Outage","Grid fluctuation, site went down because gen ran =
untill fuel shortage // grid stabilize (refueling done)","emmanuel.ghani@ih=
stowers.com","188","31-12-2024 01:36:55","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003968983","NKO=
MEKUI OCM","","30-12-2024 21:20:35","30-12-2024 21:12:27","31-12-2024 02:13=
:27","No power issue on site U=3D54,6v site on gen site down because is imp=
acted by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site U=3D54,6v site on gen site down becaus=
e is impacted by Mbankolo Camtel and not managing by IHS","ange.kongo@ihsto=
wers.com","490","30-12-2024 21:20:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003968777","M=
ontee-Jouvence-II","","30-12-2024 21:00:16","30-12-2024 20:59:10","30-12-20=
24 21:25:16","site went down because pwc overload(12k/280A) // site stabili=
zed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","site went down because pwc overload(12k/280A) // site st=
abilized","rouselle.schoune@ihstowers.com","67","30-12-2024 21:00:16","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003968765","O=
lembe-Terminus","","30-12-2024 20:58:45","30-12-2024 20:39:23","30-12-2024 =
21:30:05","Grid fluctuation, site went down because gen start and stopped d=
ue grid bad voltage // Grid stabilized","Fabrice Pouakam","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, =
site went down because gen start and stopped due grid bad voltage // Grid s=
tabilized","rouselle.schoune@ihstowers.com","1163","30-12-2024 20:58:45","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0003968193","Ebogo","=
","30-12-2024 20:01:41","30-12-2024 18:50:27","30-12-2024 19:36:12","Grid f=
luctuation, Site went down because Gen started and stopped due Grid bad vol=
tage and poor backup// He bypassed Grid and started Gen manualy","Siligap B=
oris","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, Site went down because Gen started and stopped due G=
rid bad voltage and poor backup// He bypassed Grid and started Gen manualy"=
,"ange.kongo@ihstowers.com","4275","30-12-2024 20:01:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0003967978","Carrefou=
rt Nkomo","","30-12-2024 19:39:12","30-12-2024 19:21:55","31-12-2024 22:35:=
24","Cascaded Incident from TTO3943217","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Access issue due to Land lo=
ad","system","369550","30-12-2024 19:39:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_800","NOCINC0003967780","ODZA CIT=
E MBIA","","30-12-2024 19:32:24","30-12-2024 18:04:12","30-12-2024 19:52:50=
","Grid Outage Site went down due to Gen overload (10kva, 160A) // Grid Res=
tored","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid Outage Site went down due to Gen overload (10kva, 160A) // Grid=
 Restored","ange.kongo@ihstowers.com","5293","30-12-2024 19:32:24","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003967690","M=
elen Ba'aba","","30-12-2024 19:25:49","30-12-2024 19:23:44","30-12-2024 19:=
28:10","Grid outage, site went down before gen start due to poor battery ba=
ckup // Grid restored","Siligap Boris","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
gen start due to poor battery backup // Grid restored","rouselle.schoune@ih=
stowers.com","126","30-12-2024 19:25:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0003967603","N=
komo","IHS_YND_174","30-12-2024 19:23:00","30-12-2024 19:21:55","31-12-2024=
 22:35:24","Access Issue due to Landlord Site went down because 2/5 rectifi=
ers alarming // he reset rectifiers","Mba Lazare Herve","Access Denial","Le=
ase Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access =
Issue due to Landlord Site went down because 2/5 rectifiers alarming // he =
reset rectifiers","rouselle.schoune@ihstowers.com","66","30-12-2024 19:23:0=
0","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003967275","SOA=
 UNIVERSITY STADIUM","","30-12-2024 19:13:05","30-12-2024 19:08:49","30-12-=
2024 20:03:39","Site went down due to work: Blaise Raoul/Supervisor IHS wor=
king on site (reconfiguration of PWC)//end Off work","Siligap Boris","Equip=
ment Replacement","Passive","Planned Activity","Planned Activity - Passive"=
,"Site went down due to work: Blaise Raoul/Supervisor IHS working on site (=
reconfiguration of PWC)//end Off work","ange.kongo@ihstowers.com","257","30=
-12-2024 19:13:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003966993","Nsimalen=
 OCM","","30-12-2024 18:30:21","30-12-2024 18:26:57","30-12-2024 19:01:22",=
"Cascaded Incident from TTO3942593","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down d=
ue to lack of 02 phases on site due to  work of ENEO// End of ENEO work and=
 Grid stabilized","system","272141","30-12-2024 18:30:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003966989","N=
kolda","IHS_YND_327","30-12-2024 18:29:02","30-12-2024 18:26:57","30-12-202=
4 19:01:22","Grid fluctuation, site went down due to lack of 02 phases on s=
ite due to  work of ENEO// End of ENEO work and Grid stabilized","Albran By=
orel","Grid Supply","Passive","Grid","National Grid - Grid Incomplete Phase=
","Grid fluctuation, site went down due to lack of 02 phases on site due to=
  work of ENEO// End of ENEO work and Grid stabilized","rouselle.schoune@ih=
stowers.com","126","30-12-2024 18:29:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003966982","B=
arriere","","30-12-2024 18:27:15","30-12-2024 18:22:10","30-12-2024 19:39:5=
4","Grid fluctuation site went down because Gen failed to start due to Grid=
 bad voltage // Grid stabilized leading to disjunction in the BTS OCM","Hye=
mafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen failed to start due=
 to Grid bad voltage // Grid stabilized leading to disjunction in the BTS O=
CM","rouselle.schoune@ihstowers.com","306","30-12-2024 18:27:15","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003966883","Akak-Nko=
zoa-MTN-IHS","","30-12-2024 18:02:40","30-12-2024 17:54:39","30-12-2024 18:=
01:44","Cascaded Incident from TTO3942454","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down due to wor=
k: Blaise Raoul/Supervisor IHS working on site (reconfiguration of PWC)// E=
nd of work","system","266881","30-12-2024 18:02:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003966876","S=
oa-II","IHS_YND_316, IHS_YND_324","30-12-2024 18:01:44","30-12-2024 17:54:3=
9","30-12-2024 18:01:44","Site went down due to work: Blaise Raoul/Supervis=
or IHS working on site (reconfiguration of PWC)// End of work","Siligap Bor=
is","Installation Activity","Passive","Planned Activity","Installation Acti=
vity","Site went down due to work: Blaise Raoul/Supervisor IHS working on s=
ite (reconfiguration of PWC)// End of work","rouselle.schoune@ihstowers.com=
","425","30-12-2024 18:01:44","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0003966708","Ako=
k Ndoe Yde","","30-12-2024 17:47:41","30-12-2024 17:44:27","30-12-2024 18:3=
9:31","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started automatically","Hyemafo Gildas","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor backup// Gen started automatically","ange.kongo@ih=
stowers.com","195","30-12-2024 17:47:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003966676","M=
ontee-Des-Soeurs","","30-12-2024 17:43:09","30-12-2024 17:41:04","30-12-202=
4 18:15:00","Grid outage, site went down before gen start due to poor batte=
ry backup // Gen manually started","Hyemafo Gildas","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // Gen manually started",=
"rouselle.schoune@ihstowers.com","126","30-12-2024 17:43:09","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003966456","Ebo=
go","","30-12-2024 16:59:23","30-12-2024 16:54:24","30-12-2024 18:29:50","S=
ite went down due to work: Blaise Raoul/Supervisor IHS working on site (rec=
onfiguration of PWC)// End of work","Siligap Boris","Installation Activity"=
,"Passive","Planned Activity","Installation Activity","Site went down due t=
o work: Blaise Raoul/Supervisor IHS working on site (reconfiguration of PWC=
)// End of work","ange.kongo@ihstowers.com","3020","30-12-2024 16:59:23","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0003966180","M=
volye-New","","30-12-2024 16:09:55","30-12-2024 16:01:59","30-12-2024 17:25=
:43","No power Issue Site on Grid Ubai =3D51.8V, The FME The TX FME Mbah Ho=
siah (674007438) is informed","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power Issue Site on Grid Ub=
ai =3D51.8V, The FME The TX FME Mbah Hosiah (674007438) is informed","rouse=
lle.schoune@ihstowers.com","477","30-12-2024 16:09:55","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003966037","ODZ=
A CITE MBIA","","30-12-2024 15:37:56","30-12-2024 15:34:01","30-12-2024 17:=
57:08","Grid outahge site went down Gen overload(20KVA; 280A) // Grid retur=
n","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","Grid outahge site went down Gen overload(20KVA; 280A) // Grid return","a=
nge.kongo@ihstowers.com","236","30-12-2024 15:37:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003966033","O=
lembe-Terminus","","30-12-2024 15:37:06","30-12-2024 15:34:01","30-12-2024 =
15:39:50","Grid fluctuation, site went down because gen fails to start due =
to grid bad voltage // Site stabilized","Fabrice Pouakam","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, =
site went down because gen fails to start due to grid bad voltage // Site s=
tabilized","rouselle.schoune@ihstowers.com","186","30-12-2024 15:37:06","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003965732","S=
OA UNIVERSITY STADIUM","","30-12-2024 14:50:56","30-12-2024 14:44:51","30-1=
2-2024 16:07:32","Grid outage, Site went down because Gen started and stopp=
ed with alarm 'low oil pressure""// He did draining and started Gen manualy=
","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil P=
ressure","Grid outage, Site went down because Gen started and stopped with =
alarm 'low oil pressure""// He did draining and started Gen manualy","rouse=
lle.schoune@ihstowers.com","365","30-12-2024 14:50:56","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003965677","N=
yanon","","30-12-2024 14:42:39","30-12-2024 14:33:59","30-12-2024 17:10:14"=
,"No power issue site on Gen Ubaie=3D 55,5 V. The TX FME Gr=E9goire //65207=
0658// from huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue site on Gen Ubaie=3D 55,5 V. The TX FME Gr=E9goire //652070658/=
/ from huawei is informed.","rouselle.schoune@ihstowers.com","522","30-12-2=
024 14:42:39","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0003965449","SAA=
 Entrance","","30-12-2024 14:00:15","30-12-2024 13:53:04","30-12-2024 14:11=
:43","Grid fluctuation,site went down because Gen failed to start due to ba=
d voltage,no RCP on site// he bypass the Grid and site on Gen","Parker Tcho=
up","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation,site went down because Gen failed to start due to bad v=
oltage,no RCP on site// he bypass the Grid and site on Gen","dorothy.djanti=
o@ihstowers.com","433","30-12-2024 14:00:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003965444","MVAN SAC=
EL","","30-12-2024 13:59:20","30-12-2024 13:52:42","30-12-2024 14:05:55","C=
ascaded Incident from TTO3940764","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage Site went down because G=
en Oerload(20kva; 290A )// Grid Restored","system","398","30-12-2024 13:59:=
20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003965438","M=
VAN","IHS_YND_510","30-12-2024 13:57:49","30-12-2024 13:52:42","30-12-2024 =
14:05:55","Grid Outage Site went down because Gen Oerload(20kva; 290A )// G=
rid Restored","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid Outage Site went down because Gen Oerload(20kva; 290A )/=
/ Grid Restored","olivier.kwedi@ihstowers.com","308","30-12-2024 13:57:49",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003965300","S=
calom-IHS","","30-12-2024 13:31:50","30-12-2024 13:26:44","30-12-2024 14:51=
:18","Site went down due to work: Ermane Abena/699999625/ from  dowen servi=
ce is working on site (swap pwc) // End of work","","Equipment Replacement"=
,"Passive","Planned Activity","Planned Activity - Passive","Site went down =
due to work: Ermane Abena/699999625/ from  dowen service is working on site=
 (swap pwc) // End of work","olivier.kwedi@ihstowers.com","308","30-12-2024=
 13:31:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003965247","A=
WAE OCM","","30-12-2024 13:23:10","30-12-2024 13:17:03","30-12-2024 13:25:0=
3","Site went down due to Work Blaise /657108509/ SS  from  IHS  working on=
 site//end Off Work","Mba Lazare Herve","Equipment Replacement","Passive","=
Planned Activity","Planned Activity - Passive","Site went down due to Work =
Blaise /657108509/ SS  from  IHS  working on site//end Off Work","olivier.k=
wedi@ihstowers.com","369","30-12-2024 13:23:10","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0003965237","Eto=
ug ebe biscuiterie","","30-12-2024 13:21:05","30-12-2024 13:03:54","30-12-2=
024 14:11:50","Site went down due to work: Stephane Dassi/677548300  Swapp =
From Ieng working on site ( Battery of PWC)// End of work ","Hyemafo Gildas=
","Installation Activity","Passive","Planned Activity","Installation Activi=
ty","Site went down due to work: Stephane Dassi/677548300  Swapp From Ieng =
working on site ( Battery of PWC)// End of work ","dorothy.djantio@ihstower=
s.com","1031","30-12-2024 13:21:05","Sagemcom CMR"
"Closed Complete","Warning","T0091","IHS_YND_314","NOCINC0003964962","Sous =
Prefecture","","30-12-2024 12:45:23","","","Site Alarming because Gen faile=
d to start due to Grid bad voltage // Grid voltage stabilized and alarm cle=
ared","Fanda Brice","Warning","Warning","POWER","Warning - Site on Battery"=
,"Site Alarming because Gen failed to start due to Grid bad voltage // Grid=
 voltage stabilized and alarm cleared","ludivine.ngamaleu@ihstowers.com","6=
05","30-12-2024 12:45:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003964716","M=
elen Ba'aba","","30-12-2024 12:03:39","30-12-2024 11:59:29","30-12-2024 12:=
35:32","Grid outage, site went down before gen start due to poor battery ba=
ckup // gen start automatically","Siligap Boris","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"olivier.kwedi@ihstowers.com","251","30-12-2024 12:03:39","Sagemcom CMR"
"Closed Complete","Warning","T0638","IHS_YND_318","NOCINC0003963970","SOA U=
niversity","","30-12-2024 09:37:50","","","Grid outage ,Site alarming becau=
se site on battery Causing by  Gen start and stopped with high temp alarm /=
/ he added water and manually start the gen","Siligap Boris","Warning","War=
ning","POWER","Warning - Site on Battery","Grid outage ,Site alarming becau=
se site on battery Causing by  Gen start and stopped with high temp alarm /=
/ he added water and manually start the gen","ludivine.ngamaleu@ihstowers.c=
om","606","30-12-2024 09:37:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003963869","M=
ontee-Des-Soeurs","","30-12-2024 09:16:48","30-12-2024 09:01:42","30-12-202=
4 09:53:55","Grid outage, Site went down before Gen start due to poor backu=
p// Gen start manually","Hyemafo Gildas","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Gen start manually","olivier.kwedi@ihstowe=
rs.com","907","30-12-2024 09:16:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003963779","Akak-Nko=
zoa-MTN-IHS","","30-12-2024 08:53:50","30-12-2024 08:44:47","30-12-2024 08:=
58:56","Cascaded Incident from TTO3938872","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","eneo outage, Site down du=
e to poor backup//Gen started automatically","system","543","30-12-2024 08:=
53:50","Sagemcom CMR"
"Closed Complete","Warning","CTR_046","IHS_YND_008","NOCINC0003963656","CND=
H","","30-12-2024 08:29:08","","","Site alarming because high temp 41=B0 //=
 27=B0 C and alarm cleared","Paul BIBOUM","Warning","Warning","ENVIRONMENT"=
,"Warning - High Temperature","Site alarming because high temp 41=B0 // 27=
=B0 C and alarm cleared","ludivine.ngamaleu@ihstowers.com","605","30-12-202=
4 08:29:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003963461","Yoko MTN=
","","30-12-2024 07:36:31","30-12-2024 07:28:31","30-12-2024 07:32:30","Cas=
caded Incident from TTO3938464","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site with Ubaie=3D48.9V=
  site on Battery ( Hybrid Gen siet and start threshold ubai=3D48.4V) The T=
x Fme Gregoire( 652070658)from Huawei is informed.Site up at  07:32 AM","sy=
stem","268522","30-12-2024 07:36:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003963460","Ngouetou=
","","30-12-2024 07:36:30","30-12-2024 07:28:31","30-12-2024 07:32:30","Cas=
caded Incident from TTO3938464","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site with Ubaie=3D48.9V=
  site on Battery ( Hybrid Gen siet and start threshold ubai=3D48.4V) The T=
x Fme Gregoire( 652070658)from Huawei is informed.Site up at  07:32 AM","sy=
stem","268521","30-12-2024 07:36:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003963459","Ngoum","=
","30-12-2024 07:36:30","30-12-2024 07:28:31","30-12-2024 07:32:30","Cascad=
ed Incident from TTO3938464","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site with Ubaie=3D48.9V  s=
ite on Battery ( Hybrid Gen siet and start threshold ubai=3D48.4V) The Tx F=
me Gregoire( 652070658)from Huawei is informed.Site up at  07:32 AM","syste=
m","268521","30-12-2024 07:36:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003963457","MBIMBIM"=
,"","30-12-2024 07:36:30","30-12-2024 07:28:31","30-12-2024 07:32:30","Casc=
aded Incident from TTO3938464","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site with Ubaie=3D48.9V =
 site on Battery ( Hybrid Gen siet and start threshold ubai=3D48.4V) The Tx=
 Fme Gregoire( 652070658)from Huawei is informed.Site up at  07:32 AM","sys=
tem","268520","30-12-2024 07:36:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003963458","Matsari"=
,"","30-12-2024 07:36:30","30-12-2024 07:28:31","30-12-2024 07:32:30","Casc=
aded Incident from TTO3938464","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site with Ubaie=3D48.9V =
 site on Battery ( Hybrid Gen siet and start threshold ubai=3D48.4V) The Tx=
 Fme Gregoire( 652070658)from Huawei is informed.Site up at  07:32 AM","sys=
tem","268520","30-12-2024 07:36:30","Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0003963415","Don=
ga","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_YND_473","30-1=
2-2024 07:29:58","30-12-2024 07:28:31","30-12-2024 08:02:30","No power issu=
e on site with Ubaie=3D48.9V  site on Battery ( Hybrid Gen siet and start t=
hreshold ubai=3D48.4V) The Tx Fme Gregoire( 652070658)from Huawei is inform=
ed.Site up at 07:32 AM","Parker Tchoup","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
with Ubaie=3D48.9V  site on Battery ( Hybrid Gen siet and start threshold u=
bai=3D48.4V) The Tx Fme Gregoire( 652070658)from Huawei is informed.Site up=
 at  07:32 AM","dorothy.djantio@ihstowers.com","88","30-12-2024 07:29:58","=
Sagemcom CMR"
"Closed Complete","Warning","CTR_031","IHS_YND_319","NOCINC0003963274","SOA=
 2","","30-12-2024 06:53:38","","","Grid outage ,site alarming because site=
 on battery and Gen started and stopped  with alarm ""overvoltage""//He res=
et Gen card and site on Gen","Siligap Boris","Warning","Warning","POWER","W=
arning - Site on Battery","Grid outage ,site alarming because site on batte=
ry and Gen started and stopped  with alarm ""overvoltage""//He reset Gen ca=
rd and site on Gen","ludivine.ngamaleu@ihstowers.com","604","30-12-2024 06:=
53:38","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003963241","Ebo=
go","","30-12-2024 06:45:37","30-12-2024 06:42:32","30-12-2024 09:41:35","G=
rid outage, site went down due to dysfunctionning of the PWC ZTE // Gen man=
ually started","Siligap Boris","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Grid outage, site went down due to dysfunctionn=
ing of the PWC ZTE // Gen manually started","dorothy.djantio@ihstowers.com"=
,"186","30-12-2024 06:45:37","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0003962500","Eto=
 koss Yde","","30-12-2024 00:52:30","30-12-2024 00:43:22","30-12-2024 01:21=
:07","grid outage,gen failed to start due to contactor Ge faulty//gen manua=
lly started","Fanda Brice","Equipment Repair","Passive","Control Panel","AT=
S-AMF Issue","grid outage,gen failed to start due to contactor Ge faulty//g=
en manually started","landry.etame@ihstowers.com","550","30-12-2024 00:52:3=
0","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003962491","Elo=
umdem stade","","30-12-2024 00:48:54","30-12-2024 00:34:39","30-12-2024 03:=
08:37","site went down because gen ran till fuel shortage//refueling done",=
"Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","site went d=
own because gen ran till fuel shortage//refueling done","landry.etame@ihsto=
wers.com","856","30-12-2024 00:48:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003962453","M=
arche Odza","","30-12-2024 00:34:16","30-12-2024 00:27:10","30-12-2024 03:3=
9:41","access issue during the night  Grid Outage Gen Failed to Start //Gri=
d Restored (Deep investiguetion Ongoing)","Albran Byorel","Access Denial","=
Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","acces=
s issue during the night  Grid Outage Gen Failed to Start //Grid Restored (=
Deep investiguetion Ongoing)","stephane.nkamwa@ihstowers.com","428","30-12-=
2024 00:34:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003962447","K=
oweit City","","30-12-2024 00:32:34","30-12-2024 00:24:22","30-12-2024 01:5=
3:13","Grid outage, site went down gen start and stopped with alarm ""low f=
uel""(unprouven alarm) // He reset gen card and gen manually started","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, site went down gen start and stopped with alarm ""low fuel""(u=
nprouven alarm) // He reset gen card and gen manually started","stephane.nk=
amwa@ihstowers.com","493","30-12-2024 00:32:34","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0003962347","ELO=
UMDEM CARRIERE","","29-12-2024 23:55:58","29-12-2024 23:50:44","30-12-2024 =
00:42:59","site went down because gen start and stopped with high temp alar=
m // he added water and manually start the gen","Fanda Brice","Equipment Re=
pair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue",=
"site went down because gen start and stopped with high temp alarm // he ad=
ded water and manually start the gen","landry.etame@ihstowers.com","315","2=
9-12-2024 23:55:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003962261","T=
singa","","29-12-2024 23:20:53","29-12-2024 23:16:40","29-12-2024 23:38:40"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen started automatically","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // Gen started automatically","s=
tephane.nkamwa@ihstowers.com","254","29-12-2024 23:20:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0003962210","N=
gousso OCM","","29-12-2024 23:06:07","29-12-2024 22:41:55","30-12-2024 10:4=
5:24","No power issue on site  U=3D53 site on Gen Armand Nguetsa 691 144 41=
2 of Huawei is informed.","Siligap Boris","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e  U=3D53 site on Gen Armand Nguetsa 691 144 412 of Huawei is informed.

 =20


","stephane.nkamwa@ihstowers.com","1452","29-12-2024 23:06:07","Sagemcom CM=
R"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003961981","Men=
dong3","","29-12-2024 22:08:08","29-12-2024 22:01:01","30-12-2024 03:37:16"=
,"grid outage,no space to deploy a mobil gen // grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no spa=
ce to deploy a mobil gen // grid return","christian.fonkou@ihstowers.com","=
428","29-12-2024 22:08:08","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003961949","Nko=
lnda","","29-12-2024 22:00:44","29-12-2024 21:57:36","29-12-2024 22:57:36",=
"No power issue on site U=3D48,7v site on gen Tx fme Lionel steeve 65518487=
6 of huawei is informed notice that disjunction In BTS Mtn","Albran Byorel"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue on site U=3D48,7v site on gen Tx fme Lionel ste=
eve 655184876 of huawei is informed notice that disjunction In BTS Mtn","ch=
ristian.fonkou@ihstowers.com","189","29-12-2024 22:00:44","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0003961945","Mon=
tee Jouvence","","29-12-2024 21:59:43","29-12-2024 21:54:31","29-12-2024 23=
:02:10","grid bad voltage,and gen failed to start//bypassed grid and starte=
d the gen","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","grid bad voltage,and gen failed to start//bypass=
ed grid and started the gen","christian.fonkou@ihstowers.com","313","29-12-=
2024 21:59:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003961918","Akak-Nko=
zoa-MTN-IHS","","29-12-2024 21:54:10","29-12-2024 21:49:51","29-12-2024 23:=
58:00","Cascaded Incident from TTO3936739","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo fluctuations site do=
wn due to poor backup // Eneo shut down site on GEN","system","274304","29-=
12-2024 21:54:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0003961904","N=
gousso OCM","","29-12-2024 21:50:42","29-12-2024 19:15:33","29-12-2024 21:0=
1:09","Site went down because CB(32A) of rectifier tripped due to overload =
on neutral// He rearmed and started Gen manualy","Siligap Boris","Equipment=
 Repair","Passive","Rectifier","Rectifier - Circuit Breaker","Site went dow=
n because CB(32A) of rectifier tripped due to overload on neutral// He rear=
med and started Gen manualy","emmanuel.ghani@ihstowers.com","9310","29-12-2=
024 21:50:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003961884","M=
ontee-Jouvence-II","","29-12-2024 21:45:04","29-12-2024 21:42:55","29-12-20=
24 21:45:04","site went down because pwc overload(12k/280A) // site stabili=
zed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","site went down because pwc overload(12k/280A) // site st=
abilized","emmanuel.ghani@ihstowers.com","130","29-12-2024 21:45:04","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003961882","MVAN SAC=
EL","","29-12-2024 21:44:20","29-12-2024 21:40:02","30-12-2024 03:37:15","C=
ascaded Incident from TTO3936700","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, site went down due to G=
en overload (20KVA,290 A) //Grid return","system","258","29-12-2024 21:44:2=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003961879","M=
VAN","IHS_YND_510","29-12-2024 21:43:06","29-12-2024 21:40:02","30-12-2024 =
03:39:30","grid outage, site went down due to Gen overload (20KVA,290 A) //=
Grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","grid outage, site went down due to Gen overload (20KVA,290 A) =
//Grid return","emmanuel.ghani@ihstowers.com","185","29-12-2024 21:43:06","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003961714","N=
GONA","","29-12-2024 21:08:41","29-12-2024 21:02:32","29-12-2024 21:22:32",=
"ACTIVE no power issue  Site is on Grid and Ubaie =3D55.8V The Tx FME Lione=
l Adjep (655184876)from Huawei is informed. ","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"ACTIVE no power issue  Site is on Grid and Ubaie =3D55.8V The Tx FME Lion=
el Adjep (655184876)from Huawei is informed. ","emmanuel.ghani@ihstowers.co=
m","370","29-12-2024 21:08:41","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003961691","BIY=
EMASSI NIKI","","29-12-2024 21:03:27","29-12-2024 15:38:48","29-12-2024 22:=
34:22","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Site =
stabilized","christian.fonkou@ihstowers.com","19480","29-12-2024 21:03:27",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003961508","Lad=
a I Yde","","29-12-2024 20:26:18","29-12-2024 20:18:13","29-12-2024 20:58:1=
3","Grid fluctuation site went down because Gen fails tto start due to Grid=
 bad voltage and No RCP on site  //He  bypassed Grid and Gen manually start=
ed","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation site went down because Gen fails tto=
 start due to Grid bad voltage and No RCP on site  //He  bypassed Grid and =
Gen manually started","christian.fonkou@ihstowers.com","486","29-12-2024 20=
:26:18","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003961491","Ole=
mbe MTN","","29-12-2024 20:24:44","29-12-2024 20:18:38","29-12-2024 20:56:3=
8","grid outage,gen ran till fuel shortage//refueling done","Fabrice Pouaka=
m","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran ti=
ll fuel shortage//refueling done","christian.fonkou@ihstowers.com","367","2=
9-12-2024 20:24:44","Sagemcom CMR"
"Closed Complete","Site Down","T0535","IHS_YND_234","NOCINC0003961472","Oyo=
mabang MTN","","29-12-2024 20:20:44","29-12-2024 20:17:39","29-12-2024 20:2=
2:39","No power issue on site U=3D53v site on gen Tx Mohamadou of huawei is=
 informed up at 20:22","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site U=3D53v site on gen Tx Mohamadou of huawei is informed up at 20:2=
2","christian.fonkou@ihstowers.com","186","29-12-2024 20:20:44","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003961245","N=
kozoa","","29-12-2024 19:44:06","29-12-2024 19:38:59","29-12-2024 20:35:59"=
,"Grid outage, site went down due to gen overload(20KVA, 340A) // he reduic=
ed the load and started Gen manually","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload(20KVA, 340A) // he reduiced the load and started Gen manually"=
,"emmanuel.ghani@ihstowers.com","308","29-12-2024 19:44:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003961114","Akak-Nko=
zoa-MTN-IHS","","29-12-2024 19:28:00","29-12-2024 19:24:05","29-12-2024 19:=
39:25","Cascaded Incident from TTO3935846","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site down be=
fore DG start due to poor backup	// DG started automatically","system","121=
8164","29-12-2024 19:28:00","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003961055","Mes=
sa Carriere","","29-12-2024 19:14:06","29-12-2024 19:06:01","29-12-2024 19:=
57:01","grid outage,site went down because distributor Eneo burned//bypasse=
d it and started the gen","Mboua Thierry","Fire on Site","Passive","Infrast=
ructure","Fire - Burned","grid outage,site went down because distributor En=
eo burned//bypassed it and started the gen","christian.fonkou@ihstowers.com=
","486","29-12-2024 19:14:06","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003960794","ODZ=
A MINKAN EDIBI ASSI","","29-12-2024 18:21:27","29-12-2024 18:10:23","29-12-=
2024 19:35:39","Grid fluctuation, site went down due to lack of 02 phase on=
 site // he bypassed Grid and started Gen manualy","Albran Byorel","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluc=
tuation, site went down due to lack of 02 phase on site // he bypassed Grid=
 and started Gen manualy","christian.fonkou@ihstowers.com","665","29-12-202=
4 18:21:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0003960648","Carrefou=
rt Nkomo","","29-12-2024 17:50:21","29-12-2024 17:33:04","29-12-2024 18:20:=
04","Cascaded Incident from TTO3935269","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid Outage, site went down=
 because Gen started and stopped with alarm "" High temp""// He added water=
 and started Gen manualy","system","1275178","29-12-2024 17:50:21","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0003960643","N=
komo","IHS_YND_174","29-12-2024 17:49:08","29-12-2024 17:33:04","29-12-2024=
 18:20:04","Grid Outage, site went down because Gen started and stopped wit=
h alarm "" High temp""// He added water and started Gen manualy","Mba Lazar=
e Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp -=
 Coolant Level Issue","Grid Outage, site went down because Gen started and =
stopped with alarm "" High temp""// He added water and started Gen manualy"=
,"emmanuel.ghani@ihstowers.com","965","29-12-2024 17:49:08","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0003960630","Eto=
ug ebe biscuiterie","","29-12-2024 17:46:27","29-12-2024 17:37:22","29-12-2=
024 17:47:26","Site went down due to work: Stephane Dassi/677548300  Swapp =
From Ieng working on site ( Battery of PWC)// End of work ","Hyemafo Gildas=
","Installation Activity","Passive","Planned Activity","Installation Activi=
ty","Site went down due to work: Stephane Dassi/677548300  Swapp From Ieng =
working on site ( Battery of PWC)// End of work ","christian.fonkou@ihstowe=
rs.com","545","29-12-2024 17:46:27","Sagemcom CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0003960608","Biy=
emassi LAC","","29-12-2024 17:41:02","29-12-2024 17:37:58","29-12-2024 18:3=
2:58","Grid outage ,no space to deploy MDG// Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,no space=
 to deploy MDG// Grid return","christian.fonkou@ihstowers.com","186","29-12=
-2024 17:41:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0003960506","M=
vog-Ada_OCM","","29-12-2024 17:17:34","29-12-2024 17:02:28","29-12-2024 17:=
48:28","Grid outage ,no space to deploy MDG// Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage ,no spac=
e to deploy MDG// Grid return","emmanuel.ghani@ihstowers.com","907","29-12-=
2024 17:17:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0003960501","S=
calom","","29-12-2024 17:16:29","29-12-2024 17:01:25","29-12-2024 17:21:25"=
,"No power issue , Ubaie=3D54.2 V site on Grid. The FME TX Mbah Hosiah //67=
4007438// from huawei is informed and Up at 05:20 PM","Paul BIBOUM","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power issue , Ubaie=3D54.2 V site on Grid. The FME TX Mbah Hosiah /=
/674007438// from huawei is informed and Up at 05:20 PM","emmanuel.ghani@ih=
stowers.com","905","29-12-2024 17:16:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0003960494","S=
hell-Nsimeyong","","29-12-2024 17:14:54","29-12-2024 17:01:49","29-12-2024 =
17:22:54","Grid fluctuation, site went because gen start and stopped due to=
 grid bad voltage, no rcp on site // he bypass grid and manually start the =
gen","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid fluctuation, site went because gen start and stopp=
ed due to grid bad voltage, no rcp on site // he bypass grid and manually s=
tart the gen","emmanuel.ghani@ihstowers.com","786","29-12-2024 17:14:54","S=
agemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003960475","Nsi=
meyong Shell","","29-12-2024 17:11:09","29-12-2024 17:01:02","29-12-2024 17=
:25:49","Grid fluctuation, site went because gen start and stopped due to g=
rid bad voltage, no rcp on site // he bypass grid and manually start the ge=
n","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation, site went because gen start and stopped=
 due to grid bad voltage, no rcp on site // he bypass grid and manually sta=
rt the gen","christian.fonkou@ihstowers.com","608","29-12-2024 17:11:09","S=
agemcom CMR"
"Closed Complete","Site Down","T3205","IHS_YND_758","NOCINC0003960447","Nko=
lfoulou CSD MTN","","29-12-2024 17:02:48","29-12-2024 16:48:41","29-12-2024=
 17:30:41","grid outage,gen failed to start due to battery Ge faulty//he st=
arted the gen with battery backup","Siligap Boris","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Generator Battery","grid outage,gen failed to start=
 due to battery Ge faulty//he started the gen with battery backup","christi=
an.fonkou@ihstowers.com","847","29-12-2024 17:02:48","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003960413","Mvo=
g-Betsi","","29-12-2024 16:55:17","29-12-2024 16:45:12","29-12-2024 20:26:5=
9","Site went down because 02/06 rectifiers  hanging // he reset rectifiers=
 ;site on Gen","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down because 02/06 rectifiers  hanging // he re=
set rectifiers ;site on Gen","christian.fonkou@ihstowers.com","606","29-12-=
2024 16:55:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003960263","Yoko MTN=
","","29-12-2024 16:27:02","29-12-2024 15:12:21","29-12-2024 15:13:20","Cas=
caded Incident from TTO3934808","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue hybrid gen site on battery=
 with U=3D51.3v AFRO is working on site for microwave link Ntui-Ossombe","s=
ystem","283682","29-12-2024 16:27:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003960260","Ngoum","=
","29-12-2024 16:27:01","29-12-2024 15:12:21","29-12-2024 15:13:20","Cascad=
ed Incident from TTO3934808","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue hybrid gen site on battery wi=
th U=3D51.3v AFRO is working on site for microwave link Ntui-Ossombe","syst=
em","283683","29-12-2024 16:27:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003960258","MBIMBIM"=
,"","29-12-2024 16:27:01","29-12-2024 15:12:21","29-12-2024 15:13:20","Casc=
aded Incident from TTO3934808","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue hybrid gen site on battery =
with U=3D51.3v AFRO is working on site for microwave link Ntui-Ossombe","sy=
stem","283683","29-12-2024 16:27:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003960262","Ngouetou=
","","29-12-2024 16:27:01","29-12-2024 15:12:21","29-12-2024 15:13:20","Cas=
caded Incident from TTO3934808","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue hybrid gen site on battery=
 with U=3D51.3v AFRO is working on site for microwave link Ntui-Ossombe","s=
ystem","283681","29-12-2024 16:27:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003960259","Matsari"=
,"","29-12-2024 16:27:01","29-12-2024 15:12:21","29-12-2024 15:13:20","Casc=
aded Incident from TTO3934808","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue hybrid gen site on battery =
with U=3D51.3v AFRO is working on site for microwave link Ntui-Ossombe","sy=
stem","283682","29-12-2024 16:27:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003960047","A=
wae Ewonkan","","29-12-2024 15:40:21","29-12-2024 15:37:16","29-12-2024 17:=
28:16","Grid outage ,site went down due to Gen overload  (landlord is conne=
cted to Gen) //he reduced the load on site","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went down due=
 to Gen overload  (landlord is connected to Gen) //he reduced the load on s=
ite","emmanuel.ghani@ihstowers.com","186","29-12-2024 15:40:21","Sagemcom C=
MR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003960040","Nko=
ulou Carriere carrefourt","","29-12-2024 15:38:16","29-12-2024 15:19:12","3=
0-12-2024 07:37:38","access issue due to landlord,Site  went down because  =
PWC of CB(80A) disjunted// he reamed CB,Site on Grid","Mba Lazare Herve","A=
ccess Denial","Lease Or Legal","Landlord Related Issues","Access Issue - La=
nd Lord","access issue due to landlord,Site  went down because  PWC of CB(8=
0A) disjunted// he reamed CB,Site on Grid","christian.fonkou@ihstowers.com"=
,"1145","29-12-2024 15:38:16","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003960001","Nko=
mo stade","","29-12-2024 15:31:46","29-12-2024 15:11:40","29-12-2024 18:41:=
40","Grid outage, site went down because gen ran untill fuel shortage // re=
fueling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","christian.fonkou@ihstowers.com","1207","29-12-2024 15:31:=
46","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003959996","Evo=
doula MTN","","29-12-2024 15:30:40","29-12-2024 15:08:35","29-12-2024 16:16=
:35","site went down because the Mpr disfunction//he reset the rectifiers",=
"TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","site went down because the Mpr disfunction//he reset the recti=
fiers","christian.fonkou@ihstowers.com","1326","29-12-2024 15:30:40","Sagem=
com CMR"
"Closed Complete","Warning","","IHS_YND_727","NOCINC0003959995","Nlong Mvol=
ye New","","29-12-2024 15:30:28","","","unpruven alarm","Paul BIBOUM","Warn=
ing","Warning","ENVIRONMENT","Warning - High Temperature","unpruven alarm",=
"joelle.ekessi@ihstowers.com","68","29-12-2024 15:30:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0003959965","N=
gousso OCM","","29-12-2024 15:23:55","29-12-2024 15:16:50","29-12-2024 16:5=
4:26","Site went down because CB(32A) of rectifier tripped // He rearmed it=
","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier - Cir=
cuit Breaker","Site went down because CB(32A) of rectifier tripped // He re=
armed it","emmanuel.ghani@ihstowers.com","426","29-12-2024 15:23:55","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0003959959","Abang","=
","29-12-2024 15:22:50","29-12-2024 15:07:54","29-12-2024 16:10:54","Cascad=
ed Incident from TTO3934432","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive"," Grid outage,site went down because Ge=
n stopped with ""high temp"" alarm// He added water and started Gen manualy=
","system","334600","29-12-2024 15:22:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0003959951","N=
kolangaa","IHS_YND_290","29-12-2024 15:20:59","29-12-2024 15:07:54","29-12-=
2024 16:10:54"," Grid outage,site went down because Gen stopped with ""high=
 temp"" alarm// He added water and started Gen manualy","Mba Lazare Herve",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue"," Grid outage,site went down because Gen stopped with ""high t=
emp"" alarm// He added water and started Gen manualy","emmanuel.ghani@ihsto=
wers.com","786","29-12-2024 15:20:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003959925","S=
tade-Abega","","29-12-2024 15:17:34","29-12-2024 15:01:31","29-12-2024 16:3=
9:31","Grid outage, site went down due to dysfunctionning of the PWC ZTE //=
 HE reset it and Gen manually started","Mba Lazare Herve","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site we=
nt down due to dysfunctionning of the PWC ZTE // HE reset it and Gen manual=
ly started","emmanuel.ghani@ihstowers.com","964","29-12-2024 15:17:34","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0003959917","O=
ssombe","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_YND_434, I=
HS_YND_473","29-12-2024 15:16:27","29-12-2024 15:12:21","29-12-2024 20:03:4=
4","No power issue hybrid gen site on battery with U=3D51.3v AFRO is workin=
g on site for microwave link (Ntui-Ossombe)","Parker Tchoup","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue hybrid gen site on battery with U=3D51.3v AFRO is working on s=
ite for microwave link (Ntui-Ossombe)","emmanuel.ghani@ihstowers.com","247"=
,"29-12-2024 15:16:27","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_263","NOCINC0003959869","Mendong Pl=
ateau","","29-12-2024 15:05:15","","","site on alarm due to grid outage//ge=
n started","Hyemafo Gildas","Warning","Warning","POWER","Warning - Site on =
Battery","site on alarm due to grid outage//gen started","joelle.ekessi@ihs=
towers.com","64","29-12-2024 15:05:15","Sagemcom CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0003959833","NYO=
M","","29-12-2024 14:58:40","29-12-2024 14:49:37","29-12-2024 15:15:37","Gr=
id outage site went down because gen start and stopped with high temp alarm=
 // grid return (reset done)","Fabrice Pouakam","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage site went down because gen=
 start and stopped with high temp alarm // grid return (reset done)","chris=
tian.fonkou@ihstowers.com","544","29-12-2024 14:58:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003959825","C=
rf-Nsam","","29-12-2024 14:56:52","29-12-2024 14:54:47","29-12-2024 15:31:4=
7","Site went down Because The Slot off Rectifier is overload//he Normalize=
d it and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","Site went down Because The Slot off =
Rectifier is overload//he Normalized it and Site is on Grid","emmanuel.ghan=
i@ihstowers.com","126","29-12-2024 14:56:52","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003959802","MVA=
N","","29-12-2024 14:51:53","29-12-2024 13:21:37","29-12-2024 13:42:37","gr=
id outage,site went down because Gen overload (20KVA,290 A) // Grid return"=
,"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"grid outage,site went down because Gen overload (20KVA,290 A) // Grid retu=
rn","ange.kongo@ihstowers.com","5417","29-12-2024 14:51:53","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_123","NOCINC0003959791","Nkomo II",=
"","29-12-2024 14:50:29","","","site on alarm due to grid outage//gen start=
ed","Albran Byorel","Warning","Warning","POWER","Warning - Site on Battery"=
,"site on alarm due to grid outage//gen started","joelle.ekessi@ihstowers.c=
om","66","29-12-2024 14:50:29","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003959777","Mok=
olo Yaounde","","29-12-2024 14:47:18","29-12-2024 13:23:11","29-12-2024 13:=
24:17","No power issue site on grid with U=3D53.V Mohamadou from Huawei is =
informed","","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.V Mohamado=
u from Huawei is informed","ange.kongo@ihstowers.com","5048","29-12-2024 14=
:47:18","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003959762","MAN=
GUIERS CHAPELLE","","29-12-2024 14:45:04","29-12-2024 13:27:56","29-12-2024=
 13:37:56","Grid outage, site went down before gen start due to poor batter=
y backup // gen start automatically","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup // gen start automatic=
ally","ange.kongo@ihstowers.com","4629","29-12-2024 14:45:04","Sagemcom CMR=
"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003959759","ODZ=
A CITE MBIA","","29-12-2024 14:44:08","29-12-2024 14:12:01","29-12-2024 22:=
56:01","grid outage,Gen overload (10KVA,150 A) //he reduice the load ","Alb=
ran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","grid=
 outage,Gen overload (10KVA,150 A) //he reduice the load ","christian.fonko=
u@ihstowers.com","1928","29-12-2024 14:44:08","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0003959752","Awa=
e Escalier","","29-12-2024 14:41:58","29-12-2024 13:30:45","29-12-2024 13:4=
7:35","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started automatically","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Gen started automatically","ange.kongo@ihs=
towers.com","4273","29-12-2024 14:41:58","Sagemcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0003959722","Nko=
lbisson usine des eaux","","29-12-2024 14:37:10","29-12-2024 13:34:03","29-=
12-2024 14:18:46","Grid outage.Gen started and stopped due to alarm""low oi=
l pressure""// We add oil and gen manually started ","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Gri=
d outage.Gen started and stopped due to alarm""low oil pressure""// We add =
oil and gen manually started ","ange.kongo@ihstowers.com","3788","29-12-202=
4 14:37:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003959717","SOA VILL=
AGE","","29-12-2024 14:36:10","29-12-2024 14:16:12","29-12-2024 15:16:07","=
Cascaded Incident from TTO3934138","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.gen start and stopped d=
ue to alarm""high temp""// We add water and gen manually started ","system"=
,"287274","29-12-2024 14:36:10","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003959703","SOA=
 TOWN","IHS_YND_323","29-12-2024 14:35:22","29-12-2024 14:14:12","29-12-202=
4 15:16:07","Grid outage.gen start and stopped due to alarm""high temp""// =
We add water and gen manually started ","Siligap Boris","Equipment Repair",=
"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid =
outage.gen start and stopped due to alarm""high temp""// We add water and g=
en manually started ","christian.fonkou@ihstowers.com","1346","29-12-2024 1=
4:35:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0003959697","POLYCLIN=
IQUE TSINGA","","29-12-2024 14:33:43","29-12-2024 13:38:35","29-12-2024 14:=
18:35","Grid Outage, site went down because Gen started and stopped with al=
arm"" High temp ""// He added water and started Gen manualy","Mboua Thierry=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid Outage, site went down because Gen started and stopped=
 with alarm"" High temp ""// He added water and started Gen manualy","ange.=
kongo@ihstowers.com","3309","29-12-2024 14:33:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0003959676","Charles-=
Atangana","","29-12-2024 14:31:18","29-12-2024 13:48:10","29-12-2024 14:13:=
39","Grid outage//Grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage//Grid return","ange.kongo@ihstowers.=
com","2589","29-12-2024 14:31:18","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0003959663","Mon=
tee Jouvence","","29-12-2024 14:26:52","29-12-2024 13:52:34","29-12-2024 17=
:16:33","Grid fluctuation, site went down because Gen fails to start du to =
Grid bad voltage // he bypass Grid and manually start the Gen","Hyemafo Gil=
das","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, site went down because Gen fails to start du to Grid =
bad voltage // he bypass Grid and manually start the Gen","ange.kongo@ihsto=
wers.com","2058","29-12-2024 14:26:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003959653","M=
efou-Assi","","29-12-2024 14:25:33","29-12-2024 13:52:20","29-12-2024 16:11=
:20","Grid outage,DG failed to start due to fuel shortage //Refueling done.=
","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge,DG failed to start due to fuel shortage //Refueling done.","rouselle.sch=
oune@ihstowers.com","1993","29-12-2024 14:25:33","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003959638","NYO=
M FACE MAETUR","","29-12-2024 14:22:22","29-12-2024 13:26:09","29-12-2024 2=
3:28:09","Grid Outage Site went Down due to  landlord has forbiden to start=
 the Gen Because  the  Noise //Grid Restored","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid Outage Site went=
 Down due to  landlord has forbiden to start the Gen Because  the  Noise //=
Grid Restored","ange.kongo@ihstowers.com","3374","29-12-2024 14:22:22","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003959606","Bastos E=
koudou","","29-12-2024 14:20:01","29-12-2024 13:52:46","29-12-2024 14:26:09=
","Cascaded Incident from TTO3934019","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage,no space to deploy a=
 mobil gen//Grid power return","system","288610","29-12-2024 14:20:01","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_131","NOCINC0003959599","Laborato=
ire  Meka","IHS_YND_193","29-12-2024 14:18:56","29-12-2024 13:52:46","29-12=
-2024 14:26:09","grid outage,no space to deploy a mobil gen//Grid power ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"grid outage,no space to deploy a mobil gen//Grid power return","ange.kongo=
@ihstowers.com","1571","29-12-2024 14:18:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003959549","A=
hala","","29-12-2024 14:07:14","29-12-2024 13:40:08","29-12-2024 13:50:08",=
"No power issue on site U=3D53v site on grid Tx fme Hosiah of huawei is inf=
ormed","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53v site on =
grid Tx fme Hosiah of huawei is informed","rouselle.schoune@ihstowers.com",=
"1627","29-12-2024 14:07:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0003959541","Nkolfon =
Cimencam","","29-12-2024 14:04:41","29-12-2024 13:39:01","29-12-2024 16:12:=
01","Cascaded Incident from TTO3933931","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid bad voltage, and gen fai=
led to start, no rcp//bypassed grid and started the gen","system","318105",=
"29-12-2024 14:04:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003959540","Afanoya"=
,"","29-12-2024 14:04:40","29-12-2024 13:39:01","29-12-2024 16:12:01","Casc=
aded Incident from TTO3933931","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid bad voltage, and gen failed to st=
art, no rcp//bypassed grid and started the gen","system","318105","29-12-20=
24 14:04:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0003959535","M=
eyo","IHS_YND_313, IHS_YND_762","29-12-2024 14:03:13","29-12-2024 13:39:01"=
,"29-12-2024 16:12:01","grid bad voltage, and gen failed to start, no rcp//=
bypassed grid and started the gen","Hyemafo Gildas","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","grid bad voltage, and ge=
n failed to start, no rcp//bypassed grid and started the gen","rouselle.sch=
oune@ihstowers.com","1453","29-12-2024 14:03:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0003959508","M=
balla 4","","29-12-2024 13:57:44","29-12-2024 13:38:39","29-12-2024 13:58:3=
9","No power issue on site U=3D53v site on grid Tx fme Armand of huawei is =
informed","Delor Telezing","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53v site =
on grid Tx fme Armand of huawei is informed","rouselle.schoune@ihstowers.co=
m","1146","29-12-2024 13:57:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003959498","N=
YOM 2 IHS","","29-12-2024 13:55:40","29-12-2024 13:35:34","29-12-2024 15:13=
:34","Grid Outage, site went because Gen stoppen with alarm ""high Temp"" d=
ue to Gen accordeon cut // He added water,Open the Door and started Gen man=
ualy","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Hig=
h Engine Temp - Coolant Level Issue","Grid Outage, site went because Gen st=
oppen with alarm ""high Temp"" due to Gen accordeon cut// He added water,Op=
en the Door and started Gen manualy","rouselle.schoune@ihstowers.com","1207=
","29-12-2024 13:55:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003959478","O=
kolo","","29-12-2024 13:48:51","29-12-2024 13:38:59","29-12-2024 14:11:59",=
"grid outage, site went down because gen failed to start due to dysfunction=
ing of gen card // he reset the card and started the gen","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outag=
e, site went down because gen failed to start due to dysfunctioning of gen =
card // he reset the card and started the gen","rouselle.schoune@ihstowers.=
com","593","29-12-2024 13:48:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003959462","M=
endong vallee","","29-12-2024 13:45:00","29-12-2024 13:23:48","29-12-2024 1=
4:13:24","grid outage,site went down due to Gen overload (20KVA,340 A) // G=
rid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","grid outage,site went down due to Gen overload (20KVA,340 A) // G=
rid return","rouselle.schoune@ihstowers.com","4565","29-12-2024 13:45:00","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0003959448","O=
bobogo","","29-12-2024 13:41:07","29-12-2024 13:21:59","29-12-2024 15:41:19=
","Grid outage,Site went down before Gen start due to poor backup// Gen sta=
rted automatically. Power reset has done for restore the site ","MINKA NICO=
LAS","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Grid outage,Site went down before Gen start due to poor backup// Gen =
started automatically. Power reset has done for restore the site ","rousell=
e.schoune@ihstowers.com","1149","29-12-2024 13:41:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003959438","O=
lembe-Terminus","","29-12-2024 13:39:32","29-12-2024 13:21:21","29-12-2024 =
13:40:21","Grid outage, site went down because gen start and stopped with A=
larm ""over voltage"" //Grid return","Fabrice Pouakam","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down bec=
ause gen start and stopped with Alarm ""over voltage"" //Grid return","rous=
elle.schoune@ihstowers.com","1093","29-12-2024 13:39:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003959404","M=
ontee-Des-Soeurs","","29-12-2024 13:35:29","29-12-2024 13:21:24","29-12-202=
4 17:24:39","Grid fluctuation, site went down because Gen started and stopp=
ed due to Grid bad voltage and poor battery backup// He bypassed Grid and s=
tarted Gen manualy","Hyemafo Gildas","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid fluctuation, site went down because Gen =
started and stopped due to Grid bad voltage and poor battery backup// He by=
passed Grid and started Gen manualy","rouselle.schoune@ihstowers.com","846"=
,"29-12-2024 13:35:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003959390","E=
bogo","","29-12-2024 13:33:42","29-12-2024 13:21:38","29-12-2024 14:38:38",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started ","Siligap Boris","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before gen star=
t due to poor battery backup // Gen started ","rouselle.schoune@ihstowers.c=
om","725","29-12-2024 13:33:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0003959374","C=
NR","","29-12-2024 13:28:12","29-12-2024 13:21:02","29-12-2024 21:08:41","N=
o power issue site on grid with U=3D53.4V Mohamadou from Huaie is informed/=
/site up at 01:46 PM","Mboua Thierry","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gr=
id with U=3D53.4V Mohamadou from Huaie is informed//site up at 01:46 PM","r=
ouselle.schoune@ihstowers.com","431","29-12-2024 13:28:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003959371","S=
tade-Abega","","29-12-2024 13:27:20","29-12-2024 13:23:05","29-12-2024 13:4=
5:39","Grid outage, site went down due to dysfunctionning of the PWC ZTE //=
 HE reset it and Gen manually started","Mba Lazare Herve","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site we=
nt down due to dysfunctionning of the PWC ZTE // HE reset it and Gen manual=
ly started","rouselle.schoune@ihstowers.com","256","29-12-2024 13:27:20","S=
agemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0003959335","NKO=
LMEKONG YDE","","29-12-2024 13:19:56","29-12-2024 13:12:49","29-12-2024 13:=
23:49","Grid fluctuation, site went down before gen start due to poor batte=
ry backup // grid return","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid fluctuation, site went do=
wn before gen start due to poor battery backup // grid return","ange.kongo@=
ihstowers.com","428","29-12-2024 13:19:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0003959323","A=
v-Germaine","","29-12-2024 13:18:21","29-12-2024 13:17:14","29-12-2024 13:2=
2:51","Grid outage.no space to deploy mobile gen//Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no s=
pace to deploy mobile gen//Grid return","rouselle.schoune@ihstowers.com","6=
8","29-12-2024 13:18:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003959293","O=
mnisport-Rail","","29-12-2024 13:13:04","29-12-2024 12:54:57","29-12-2024 1=
3:17:00","Site went down because 01/05 rectifier faulty // He replace the f=
aulty  rectifier","Delor Telezing","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down because 01/05 rectifier faulty // He re=
place the faulty  rectifier","rouselle.schoune@ihstowers.com","1088","29-12=
-2024 13:13:04","Sagemcom CMR"
"Closed Complete","Site Down","T0287","IHS_YND_038","NOCINC0003959041","Sia=
ntou Inferieur","","29-12-2024 12:26:23","29-12-2024 12:11:17","29-12-2024 =
14:14:17","Site went down due to work: Team Alex kameni  (677548708) From E=
iingenierring  working on site( SWAP PWC )  //  End of work","","Installati=
on Activity","Passive","Planned Activity","Installation Activity","Site wen=
t down due to work: Team Alex kameni  (677548708) From Eiingenierring  work=
ing on site( SWAP PWC )  //  End of work","ange.kongo@ihstowers.com","907",=
"29-12-2024 12:26:23","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0003958753","SAA=
 Entrance","","29-12-2024 11:37:09","29-12-2024 11:26:02","29-12-2024 12:23=
:57","Grid bad voltage, site went down because Gen failed to start due to G=
rid bad voltage // We bypass grid and gen manually started","Parker Tchoup"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid bad voltage, site went down because Gen failed to start due to Grid ba=
d voltage // We bypass grid and gen manually started","ange.kongo@ihstowers=
.com","669","29-12-2024 11:37:09","Sagemcom CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0003958548","Mam=
ch Building","","29-12-2024 10:52:01","29-12-2024 10:46:50","29-12-2024 13:=
10:49"," Grid outage.site went down because Gen started and stopped due to =
air intake causing by fuel pipe pierced // He fixed the fuel pipe and gen m=
anually started","Mboua Thierry","Fuel Outage (Probable)","Passive","Diesel=
","Fuel Line Issue"," Grid outage.site went down because Gen started and st=
opped due to air intake causing by fuel pipe pierced // He fixed the fuel p=
ipe and gen manually started","ange.kongo@ihstowers.com","312","29-12-2024 =
10:52:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0003958497","M=
ontee-Anne-Rouge","","29-12-2024 10:42:46","29-12-2024 10:37:39","29-12-202=
4 12:11:22","Site went down due to work Team ABENA //699999625// From DOWEN=
  working on site (SWAP PWC) // End of work","","Equipment Replacement","Pa=
ssive","Planned Activity","Planned Activity - Passive","Site went down due =
to work Team ABENA //699999625// From DOWEN  working on site (SWAP PWC) // =
End of work","rouselle.schoune@ihstowers.com","308","29-12-2024 10:42:46","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_680","NOCINC0003958477","MIMBOMAN=
 LIBERTE","","29-12-2024 10:38:45","29-12-2024 09:43:25","29-12-2024 11:35:=
09","Grid Outage, Site went down due to Main Gen Faulty//MDG 20Kva has depl=
oyed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ge=
nerator Faulty","Grid Outage, Site went down due to Main Gen Faulty//MDG 20=
Kva has deployed","ange.kongo@ihstowers.com","3322","29-12-2024 10:38:45","=
Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0003958349","Nko=
lo II New","","29-12-2024 10:12:11","29-12-2024 10:02:05","29-12-2024 12:11=
:29","site went down because the Cb(80A) of PWC dysjoncted // He reamed the=
 Cb","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Circuit Breaker Issue","site went down because the Cb(80A) of PW=
C dysjoncted // He reamed the Cb","ange.kongo@ihstowers.com","607","29-12-2=
024 10:12:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003958350","N=
koabang2","","29-12-2024 10:12:11","29-12-2024 10:07:59","29-12-2024 12:28:=
42","Grid outage ,site went down because Gen overload(22 KVA,315 A)//he red=
uced load ","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage ,site went down because Gen overload(22 KVA,315 =
A)//he reduced load ","rouselle.schoune@ihstowers.com","253","29-12-2024 10=
:12:11","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003958344","Mim=
boman4","","29-12-2024 10:11:28","29-12-2024 10:02:21","29-12-2024 10:03:27=
","Active//No power issue on site ubaie=3D54.5V site on grid The Tx FME Lio=
nel adjep(655184876) from Huawei is informed","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site ubaie=3D54.5V site on grid The Tx FME Lion=
el adjep(655184876) from Huawei is informed","ange.kongo@ihstowers.com","54=
8","29-12-2024 10:11:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0003958236","E=
MANA BILICK CITY","","29-12-2024 09:55:27","29-12-2024 09:54:22","29-12-202=
4 11:15:06","site went down because ATS dysfonction // he changed the sourc=
e manually, site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","ATS-AMF Issue","site went down because ATS dysfonction // he =
changed the source manually, site on Gen","rouselle.schoune@ihstowers.com",=
"66","29-12-2024 09:55:27","Sagemcom CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0003957993","Eto=
ug-Ebe 2","","29-12-2024 08:52:23","29-12-2024 08:47:12","29-12-2024 18:28:=
18","Grid Outage No Space to deploy a MDG //Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space t=
o deploy a MDG //Grid return","ange.kongo@ihstowers.com","312","29-12-2024 =
08:52:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003957923","N=
GONA","","29-12-2024 08:36:38","29-12-2024 07:22:08","29-12-2024 08:44:37",=
"Grid outage DG fails to start// Grid return (investigation on going)","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage DG fails to start// Grid return (investigation on going)","=
rouselle.schoune@ihstowers.com","9009","29-12-2024 08:36:38","Sagemcom CMR"
"Closed Complete","Site Down","T2222","IHS_YND_697","NOCINC0003957633","Nom=
ayos-IHS","","29-12-2024 07:47:10","29-12-2024 07:37:01","29-12-2024 08:46:=
40","Grid outage, site went down because gen failed to start due to pear fa=
ulty // He changed the pear and gen manually started","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Fuel Filter","Grid outage, site we=
nt down because gen failed to start due to pear faulty // He changed the pe=
ar and gen manually started","ange.kongo@ihstowers.com","610","29-12-2024 0=
7:47:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003957601","H=
-General-Yde","","29-12-2024 07:40:08","29-12-2024 07:21:38","29-12-2024 08=
:11:26","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // he added water and manually start the gen","Siligap Boris",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, site went down because gen start and stopped wit=
h high temp alarm // he added water and manually start the gen","rouselle.s=
choune@ihstowers.com","1111","29-12-2024 07:40:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003957565","Essomba"=
,"","29-12-2024 07:33:51","29-12-2024 06:59:07","29-12-2024 07:34:31","Casc=
aded Incident from TTO3931627","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down because =
PWC ZTE dysfunctionning// He reset PWC and started Gen manualy","system","1=
255784","29-12-2024 07:33:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003957564","Tradex-N=
komo","","29-12-2024 07:33:51","29-12-2024 06:59:07","29-12-2024 07:34:31",=
"Cascaded Incident from TTO3931627","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down becaus=
e PWC ZTE dysfunctionning// He reset PWC and started Gen manualy","system",=
"1255783","29-12-2024 07:33:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003957566","Biteng-M=
aetur","","29-12-2024 07:33:51","29-12-2024 06:59:07","29-12-2024 07:34:31"=
,"Cascaded Incident from TTO3931627","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
cause PWC ZTE dysfunctionning// He reset PWC and started Gen manualy","syst=
em","1255783","29-12-2024 07:33:51","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003957563","MIM=
BOMAN LIBERTE","","29-12-2024 07:33:30","29-12-2024 07:18:23","29-12-2024 0=
7:38:01","Grid Outage Site went down because Main Gen Faulty//Grid Restored=
","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid Outage Site went down because Main Gen Faulty//Grid Resto=
red","ange.kongo@ihstowers.com","908","29-12-2024 07:33:30","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003957547","NYO=
M FACE MAETUR","","29-12-2024 07:30:54","29-12-2024 07:18:43","29-12-2024 0=
8:10:04","Grid outage landlord has forbiden to start the Gen due to Noise /=
/ Grid restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Emergency Stop","Grid outage landlord has forbiden to start the Gen=
 due to Noise // Grid restored","ange.kongo@ihstowers.com","732","29-12-202=
4 07:30:54","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0003957543","Ako=
k Ndoe Yde","","29-12-2024 07:29:51","29-12-2024 07:17:43","29-12-2024 07:4=
2:11","Grid outage, site went down before gen start due to poor battery bac=
kup // Grid Restored","Hyemafo Gildas","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
gen start due to poor battery backup // Grid Restored","ange.kongo@ihstower=
s.com","729","29-12-2024 07:29:51","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003957532","Nko=
lnda","","29-12-2024 07:25:20","29-12-2024 07:18:12","29-12-2024 08:00:11",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","ange.k=
ongo@ihstowers.com","429","29-12-2024 07:25:20","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003957467","SOA=
 TOWN","","29-12-2024 07:12:36","29-12-2024 07:02:40","29-12-2024 07:38:30"=
,"Grid outage, site went down because gen ran until fuel shortage // refuel=
ing done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran until fuel shortage // refueli=
ng done","ange.kongo@ihstowers.com","1932","29-12-2024 07:12:36","Sagemcom =
CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003957410","Pha=
rmacie SION","","29-12-2024 06:54:23","29-12-2024 06:50:13","29-12-2024 07:=
10:42","Grid outage, site went down before gen start due to poor battery ba=
ckup // Grid Restored","Paul BIBOUM","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before ge=
n start due to poor battery backup // Grid Restored","ange.kongo@ihstowers.=
com","251","29-12-2024 06:54:23","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003957407","BIY=
EMASSI NIKI","","29-12-2024 06:53:21","29-12-2024 06:49:13","29-12-2024 08:=
23:52","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Site =
stabilized","ange.kongo@ihstowers.com","249","29-12-2024 06:53:21","Sagemco=
m CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003957401","MIM=
BOMAN LIBERTE","","29-12-2024 06:51:50","29-12-2024 06:45:43","29-12-2024 0=
7:03:33","Grid Outage Site went down due to Main Gen Faulty//Grid Restored"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generat=
or Faulty","Grid Outage Site went down due to Main Gen Faulty//Grid Restore=
d","ange.kongo@ihstowers.com","368","29-12-2024 06:51:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003957400","MVAN SAC=
EL","","29-12-2024 06:51:40","29-12-2024 06:34:17","29-12-2024 08:05:13","C=
ascaded Incident from TTO3931414","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Grid outage,site went down because =
Gen overload (20KVA,290 A) // Grid return","system","1043","29-12-2024 06:5=
1:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003957393","S=
atcom","","29-12-2024 06:50:39","29-12-2024 06:34:32","29-12-2024 09:36:02"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,7V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","rouselle.schoune@ihsto=
wers.com","968","29-12-2024 06:50:39","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003957389","Nko=
lnda","","29-12-2024 06:49:52","29-12-2024 06:45:42","29-12-2024 07:01:14",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Grid Restored","Albran Byorel","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, site went down before gen sta=
rt due to poor battery backup // Grid Restored","ange.kongo@ihstowers.com",=
"251","29-12-2024 06:49:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003957360","D=
ragage","","29-12-2024 06:47:08","29-12-2024 06:34:03","29-12-2024 07:16:26=
","Grid outage , Site went down before Gen start due to poor backup// Grid =
return","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage , Site went down before Gen start due =
to poor backup// Grid return","rouselle.schoune@ihstowers.com","786","29-12=
-2024 06:47:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003957359","S=
calom-IHS","","29-12-2024 06:46:22","29-12-2024 06:32:13","29-12-2024 07:42=
:28","grid outage,no space to deploy a mobil gen//grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no s=
pace to deploy a mobil gen//grid return","rouselle.schoune@ihstowers.com","=
850","29-12-2024 06:46:22","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003957353","Mvo=
g-Betsi","","29-12-2024 06:45:02","29-12-2024 06:42:57","29-12-2024 06:48:1=
4","Grid fluctuation site went down because Gen failed to start due to Grid=
 bad voltage // Grid stabilized","Hyemafo Gildas","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Grid fluctuation site went=
 down because Gen failed to start due to Grid bad voltage // Grid stabilize=
d","ange.kongo@ihstowers.com","126","29-12-2024 06:45:02","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003957344","MVA=
N","IHS_YND_510","29-12-2024 06:43:55","29-12-2024 06:34:17","29-12-2024 08=
:07:14"," Grid outage,site went down because Gen overload (20KVA,290 A) // =
Grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload"," Grid outage,site went down because Gen overload (20KVA,290 A)=
 // Grid return","ange.kongo@ihstowers.com","905","29-12-2024 06:43:55","Sa=
gemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003957335","Bas=
tos Bir","","29-12-2024 06:39:24","29-12-2024 06:34:03","29-12-2024 08:34:4=
8","Grid outage site went down because gen start and stopped with alarm Ove=
r current // He reset gen card , site manually  gen","Mboua Thierry","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site =
went down because gen start and stopped with alarm Over current // He reset=
 gen card , site manually  gen","ange.kongo@ihstowers.com","323","29-12-202=
4 06:39:24","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003957331","NKO=
MEKUI OCM","","29-12-2024 06:38:31","29-12-2024 06:34:22","29-12-2024 06:54=
:08","Grid outage, site went down before gen start due to poor battery back=
up // Grid Restored","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Grid Restored","ange.kongo=
@ihstowers.com","251","29-12-2024 06:38:31","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003957326","Sap=
eur","","29-12-2024 06:37:30","29-12-2024 06:34:23","29-12-2024 06:42:25","=
Grid outage, site went down before gen start due to poor batteries backup /=
/ gen start automatically","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor batteries backup // gen start automatically","ang=
e.kongo@ihstowers.com","188","29-12-2024 06:37:30","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0003957248","Nko=
mkana","","29-12-2024 06:25:58","29-12-2024 06:17:20","29-12-2024 07:44:57"=
,"Grid outage, no space to deploy MDG // Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, no space to =
deploy MDG // Grid return","ange.kongo@ihstowers.com","787","29-12-2024 06:=
25:58","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003957230","Bit=
eng","IHS_YND_172, IHS_YND_179, IHS_YND_249","29-12-2024 06:23:56","29-12-2=
024 06:18:50","29-12-2024 07:34:57","Grid outage, Site went down because PW=
C ZTE dysfunctionning// He reset PWC and started Gen manualy","Mba Lazare H=
erve","Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded=
","Grid outage, Site went down because PWC ZTE dysfunctionning// He reset P=
WC and started Gen manualy","ange.kongo@ihstowers.com","307","29-12-2024 06=
:23:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0003957229","Nkolkoum=
ou OCM","","29-12-2024 06:23:10","29-12-2024 04:09:05","29-12-2024 06:49:26=
","Cascaded Incident from TTO3930887","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","acces issues during t=
he Night (Grid Outage Site went down due to Main Gen Faulty//Grid Restored)=
","system","302106","29-12-2024 06:23:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003957212","B=
riqueterie","","29-12-2024 06:16:23","29-12-2024 06:08:19","29-12-2024 06:4=
8:39","Grid outage, no space to deploy MDG//Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy MDG//Grid return","alexandre.kamal@ihstowers.com","485","29-12-20=
24 06:16:23","Sagemcom CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0003957187","Sim=
e Building","","29-12-2024 06:11:39","29-12-2024 05:59:30","29-12-2024 06:4=
7:59","Grid outage site went down because Gen stopped with Over-Current // =
he reset the Gen Card and manually started","Mboua Thierry","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down=
 because Gen stopped with Over-Current // he reset the Gen Card and manuall=
y started","ange.kongo@ihstowers.com","730","29-12-2024 06:11:39","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003957175","Evo=
doula MTN","","29-12-2024 06:09:58","29-12-2024 06:08:50","29-12-2024 08:16=
:56","Site went down due to 03/05 Slots on  MPR  Faulty on Site  // he use =
02 Slots remaining and Site is on Grid","TIENTCHEU NZETCHIEU GAEL","Equipme=
nt Repair","Passive","Rectifier","Rectifier Distribution","Site went down d=
ue to 03/05 Slots on  MPR  Faulty on Site  // he use 02 Slots remaining and=
 Site is on Grid","ange.kongo@ihstowers.com","69","29-12-2024 06:09:58","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003957171","Dong",""=
,"29-12-2024 06:08:21","29-12-2024 04:25:48","29-12-2024 06:46:05","Cascade=
d Incident from TTO3931178","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue on site ,Hybrid Gen si=
te, site on Battery with Ubaie=3D48.3V Gregoire(654547479) from Huawei is i=
nformed","system","315314","29-12-2024 06:08:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003957170","Donga","=
","29-12-2024 06:08:20","29-12-2024 04:25:48","29-12-2024 15:13:20","Cascad=
ed Incident from TTO3931178","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue on site ,Hybrid Gen s=
ite, site on Battery with Ubaie=3D48.3V Gregoire(654547479) from Huawei is =
informed","system","322477","29-12-2024 06:08:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003957150","MEHANDAN=
","","29-12-2024 06:01:20","29-12-2024 04:35:57","29-12-2024 06:03:01","Cas=
caded Incident from TTO3931156","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor batteries backup // gen  manually started ","system","31=
4728","29-12-2024 06:01:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003957148","O=
dza II OCM","IHS_YND_528","29-12-2024 06:00:35","29-12-2024 04:35:57","29-1=
2-2024 06:03:01","Grid outage, site went down before gen start due to poor =
batteries backup // gen  manually started ","Albran Byorel","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite went down before gen start due to poor batteries backup // gen  manuall=
y started ","alexandre.kamal@ihstowers.com","5080","29-12-2024 06:00:35","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0003957144","N=
komkana 2","","29-12-2024 05:58:42","29-12-2024 03:21:34","29-12-2024 06:57=
:00","Access issue during the Nigth Grid outage site went down because Gen =
started and stopped with alarm High temp // Grid power return","Mboua Thier=
ry","Access Denial","Lease Or Legal","Landlord Related Issues","Access Issu=
e - Land Lord","Access issue during the Nigth Grid outage site went down be=
cause Gen started and stopped with alarm High temp // Grid power return","a=
lexandre.kamal@ihstowers.com","9428","29-12-2024 05:58:42","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0003957139","Bri=
quetterie","","29-12-2024 05:57:50","29-12-2024 05:51:39","29-12-2024 06:56=
:14","Grid outage, no space to deploy MDG // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space=
 to deploy MDG // Grid return","kamga.virgile@ihstowers.com","372","29-12-2=
024 05:57:50","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0003957133","Beh=
ind P T school Yde","","29-12-2024 05:56:45","29-12-2024 05:46:34","29-12-2=
024 08:10:24","Grid Outage Gen Failed to start due no automatisation to and=
 No  automastism on site// Gen Manually Started","Paul BIBOUM","Equipment R=
epair","Passive","Control Panel","ATS-AMF Issue","Grid Outage Gen Failed to=
 start due to and No  automastism on site// Gen Manually Started","kamga.vi=
rgile@ihstowers.com","612","29-12-2024 05:56:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0003957093","Dagobert=
","","29-12-2024 05:51:01","29-12-2024 03:21:47","29-12-2024 05:02:30","Cas=
caded Incident from TTO3931092","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 because gen stopped with 'Emergency stop' alarm // he reset and site on Ge=
n","system","319277","29-12-2024 05:51:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0003957092","N=
kolbi-Boss","IHS_YND_286","29-12-2024 05:49:53","29-12-2024 03:21:47","29-1=
2-2024 05:04:09","Grid outage, site went down because gen stopped with 'Eme=
rgency stop' alarm // he reset and site on Gen","TIENTCHEU NZETCHIEU GAEL",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
, site went down because gen stopped with 'Emergency stop' alarm // he rese=
t and site on Gen","alexandre.kamal@ihstowers.com","8887","29-12-2024 05:49=
:53","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0003957046","Nko=
zoa","","29-12-2024 05:20:54","29-12-2024 05:06:27","29-12-2024 06:20:06","=
Site went down due to Gen overload(20 KVA,340 A) // he Reduice the Load and=
 Gen Manually Started","Fabrice Pouakam","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Site went down due to Gen overload(20 KVA,340 A) /=
/ he Reduice the Load and Gen Manually Started","kamga.virgile@ihstowers.co=
m","3370","29-12-2024 05:20:54","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0003956989","Ngu=
ila","IHS_YND_401, IHS_YND_434, IHS_YND_444","29-12-2024 04:52:50","29-12-2=
024 04:25:48","29-12-2024 06:46:05","site went down due to work of Felix Ba=
teu (ihs supervisor)//End of work","Parker Tchoup","Installation Activity",=
"Passive","Planned Activity","Installation Activity","site went down due to=
 work of Felix Bateu (ihs supervisor)//End of work","kamga.virgile@ihstower=
s.com","6070","29-12-2024 04:52:50","Sagemcom CMR"
"Closed Complete","Site Down","T1669","IHS_YND_195","NOCINC0003956974","chi=
na embassy yde","","29-12-2024 04:51:50","29-12-2024 04:17:09","29-12-2024 =
07:52:57","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No =
Space to deploy a MDG//Grid Restored","kamga.virgile@ihstowers.com","6008",=
"29-12-2024 04:51:50","Sagemcom CMR"
"Cancelled","Warning","T3446","IHS_YND_712","NOCINC0003956967","Nkolkoumou =
OCM","","29-12-2024 04:49:44","","","","TIENTCHEU NZETCHIEU GAEL","","","",=
"","","kamga.virgile@ihstowers.com","2418","29-12-2024 04:49:44","Sagemcom =
CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0003956918","Nko=
lbisson usine des eaux","IHS_YND_712","29-12-2024 04:25:23","29-12-2024 04:=
07:06","29-12-2024 06:49:57","acces issues during the Night (Grid Outage Si=
te went down due to Main Gen Faulty//Grid Restored)","TIENTCHEU NZETCHIEU G=
AEL","Access Denial","Lease Or Legal","Landlord Related Issues","Access Iss=
ue - Land Lord","acces issues during the Night (Grid Outage Site went down =
due to Main Gen Faulty//Grid Restored)","kamga.virgile@ihstowers.com","6668=
","29-12-2024 04:25:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003956678","O=
lembe-Terminus","","29-12-2024 02:22:10","29-12-2024 02:14:59","29-12-2024 =
02:21:21","Grid outage, site went down because gen start and stopped with A=
larm ""over voltage"" //Grid return","Fabrice Pouakam","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down bec=
ause gen start and stopped with Alarm ""over voltage"" //Grid return","alex=
andre.kamal@ihstowers.com","433","29-12-2024 02:22:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003956607","K=
oweit City","","29-12-2024 01:38:20","29-12-2024 00:38:11","29-12-2024 01:5=
7:04","Grid outage, site went down gen start and stopped with alarm ""low f=
uel""(unprouven alarm) // He reset gen card and gen manually started","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, site went down gen start and stopped with alarm ""low fuel""(u=
nprouven alarm) // He reset gen card and gen manually started","alexandre.k=
amal@ihstowers.com","3610","29-12-2024 01:38:20","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0003956591","Fla=
menco","","29-12-2024 01:29:28","29-12-2024 01:13:04","29-12-2024 03:33:20"=
,"grid outage,gen failed to start due to card faulty//gen manually started"=
,"Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","grid outage,gen failed to start due to card faulty//gen manually star=
ted","kamga.virgile@ihstowers.com","985","29-12-2024 01:29:28","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0003956587","MEFOU AS=
SI","","29-12-2024 01:27:20","29-12-2024 00:55:23","29-12-2024 01:57:09","G=
rid outage, Gen ran until fuel shortage // Refueling done","Fanda Brice","C=
ascade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage, =
Gen ran until fuel shortage // Refueling done","system","284929","29-12-202=
4 01:27:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003956585","M=
efou-Assi","IHS_YND_537","29-12-2024 01:26:31","29-12-2024 00:55:23","29-12=
-2024 01:57:59","Grid outage, Gen ran until fuel shortage // Refueling done=
","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge, Gen ran until fuel shortage // Refueling done","alexandre.kamal@ihstowe=
rs.com","1869","29-12-2024 01:26:31","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003956569","Bit=
oto","","29-12-2024 01:16:11","29-12-2024 01:00:56","29-12-2024 01:38:17","=
grid outage, site went down due to dysfunctionning of PWC// gen manually st=
arted","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","grid outage, site went down due to dysfunctionning o=
f PWC// gen manually started","kamga.virgile@ihstowers.com","916","29-12-20=
24 01:16:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003956562","Bastos E=
koudou","","29-12-2024 01:12:30","29-12-2024 00:54:27","29-12-2024 07:53:15=
","Cascaded Incident from TTO3930472","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid Outage No Space to deploy a=
 MDG//Grid Restored","system","291959","29-12-2024 01:12:30","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003956561","Lab=
oratoire  Meka","IHS_YND_193","29-12-2024 01:11:40","29-12-2024 00:54:27","=
29-12-2024 07:53:15","Grid Outage No Space to deploy a MDG//Grid Restored",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 Outage No Space to deploy a MDG//Grid Restored","kamga.virgile@ihstowers.c=
om","1033","29-12-2024 01:11:40","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003956555","Com=
plex Beac II","","29-12-2024 01:09:42","29-12-2024 00:49:20","29-12-2024 02=
:05:20","Grid Outage, site went down because Gen stopped with ""high temp""=
 alarm due to accordion faulty// He added water and started Gen manualy","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine T=
emp - Coolant Level Issue","Grid Outage, site went down because Gen stopped=
 with ""high temp"" alarm due to accordion faulty// He added water and star=
ted Gen manualy","kamga.virgile@ihstowers.com","1223","29-12-2024 01:09:42"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003956534","Nko=
londom","","29-12-2024 01:05:57","29-12-2024 00:37:49","29-12-2024 02:35:36=
","grid outage, site went down due to dysfunctionning of the PWC ZTE // Gen=
 manually started","Fabrice Pouakam","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","grid outage, site went down due to dysfun=
ctionning of the PWC ZTE // Gen manually started","kamga.virgile@ihstowers.=
com","3132","29-12-2024 01:05:57","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0003956462","Tou=
ring Club International","","29-12-2024 00:40:54","29-12-2024 00:34:43","29=
-12-2024 01:00:31"," grid fluctuation, site went down because gen stopped w=
ith under voltage alarm // RESET OF GEN CARD DONE, GRID STABILIZED: site on=
 grid","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel"," grid fluctuation, site went down because gen stopped with unde=
r voltage alarm // RESET OF GEN CARD DONE, GRID STABILIZED: site on grid","=
kamga.virgile@ihstowers.com","371","29-12-2024 00:40:54","Sagemcom CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0003956459","BIY=
EM ASSI LYCEE","","29-12-2024 00:39:50","29-12-2024 00:21:38","29-12-2024 0=
0:26:05","No power issue on site U=3D54.9v site on grid Tx fme MBAH osiah (=
674007438) of huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site U=3D54.9v site on grid Tx fme MBAH osiah (674007438) of huawei i=
s informed","kamga.virgile@ihstowers.com","1092","29-12-2024 00:39:50","Sag=
emcom CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0003956457","Biy=
emassi LAC","","29-12-2024 00:38:56","29-12-2024 00:21:46","29-12-2024 00:2=
6:03","	No power issue on site U=3D54.9v site on grid Tx fme MBAH osiah (67=
4007438) of huawei is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","	No power issue on site U=3D=
54.9v site on grid Tx fme MBAH osiah (674007438) of huawei is informed","ka=
mga.virgile@ihstowers.com","1031","29-12-2024 00:38:56","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003956452","Men=
dong3","","29-12-2024 00:37:23","29-12-2024 00:20:00","29-12-2024 01:56:21"=
,"grid outage,no space to deploy a mobil gen//grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","grid outage,no space=
 to deploy a mobil gen//grid return","kamga.virgile@ihstowers.com","1043","=
29-12-2024 00:37:23","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0003956449","Men=
dong vallee","","29-12-2024 00:36:01","29-12-2024 00:18:55","29-12-2024 01:=
59:26","grid outage,site ent down due to Gen overload 20kva, 300A//grid ret=
urn","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","grid outage,site ent down due to Gen overload 20kva, 300A//grid return",=
"kamga.virgile@ihstowers.com","4453","29-12-2024 00:36:01","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003956444","Tsi=
nga","","29-12-2024 00:35:01","29-12-2024 00:17:51","29-12-2024 02:13:43","=
Grid fluctuation, sitte went down because gen start and stopped due to grid=
 bad volage // hy bypass grid and manually start the gen","Mboua Thierry","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid flu=
ctuation, sitte went down because gen start and stopped due to grid bad vol=
age // hy bypass grid and manually start the gen","kamga.virgile@ihstowers.=
com","1031","29-12-2024 00:35:01","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003956442","NYO=
M FACE MAETUR","","29-12-2024 00:34:09","29-12-2024 00:15:58","29-12-2024 0=
0:54:44","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen=
 due to Noise // Grid Restored","kamga.virgile@ihstowers.com","1092","29-12=
-2024 00:34:09","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003956441","Mok=
olo Yaounde","","29-12-2024 00:32:59","29-12-2024 00:13:53","29-12-2024 07:=
24:05","Grid outage, no space to deploy MDG // Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spa=
ce to deploy MDG // Grid return","kamga.virgile@ihstowers.com","1147","29-1=
2-2024 00:32:59","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003956405","MIM=
BOMAN LIBERTE","","29-12-2024 00:15:51","28-12-2024 23:58:18","29-12-2024 0=
1:06:45","grid outage,main gen faulty//grid return","Mba Lazare Herve","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","grid outage,=
main gen faulty//grid return","kamga.virgile@ihstowers.com","1054","29-12-2=
024 00:15:51","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003956391","AWA=
E OCM","","29-12-2024 00:11:35","28-12-2024 23:55:41","29-12-2024 02:16:41"=
,"Grid outage,site went down due to pwc ZTE dysfunction// site on Grid","Mb=
a Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module =
Overloaded","Grid outage,site went down due to pwc ZTE dysfunction// site o=
n Grid","kamga.virgile@ihstowers.com","6313","29-12-2024 00:11:35","Sagemco=
m CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003956380","MVA=
N","","29-12-2024 00:08:05","28-12-2024 23:52:41","29-12-2024 01:56:58"," G=
rid outage,site went down because Gen overload (20KVA,290 A)// Grid return"=
,"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
" Grid outage,site went down because Gen overload (20KVA,290 A)// Grid retu=
rn","kamga.virgile@ihstowers.com","925","29-12-2024 00:08:05","Sagemcom CMR=
"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0003956148","Acc=
acia New","","28-12-2024 22:48:32","28-12-2024 22:42:24","29-12-2024 07:21:=
07","access issue during the nigth(Grid Outage//Grid Restored)","","Access =
Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lor=
d","access issue during the nigth(Grid Outage//Grid Restored)","kamga.virgi=
le@ihstowers.com","370","28-12-2024 22:48:32","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0003955943","Mon=
tee-Jouvence-II","","28-12-2024 21:50:10","28-12-2024 21:21:09","28-12-2024=
 22:06:09","Site went down due to PWC over load(12KW.280A)// Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC over load(12KW.280A)// Site stab=
ilized","kouoh.jean@ihstowers.com","1742","28-12-2024 21:50:10","Sagemcom C=
MR"
"Closed Complete","Site Down","T1486","IHS_YND_683","NOCINC0003955901","BON=
AS YDE","","28-12-2024 21:39:00","28-12-2024 21:33:49","28-12-2024 21:53:49=
","No power issue on site U=3D54,6v site on grid Tx fme Hosiah of huawei is=
 informed","Paul BIBOUM","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,6v site =
on grid Tx fme Hosiah of huawei is informed","kouoh.jean@ihstowers.com","31=
2","28-12-2024 21:39:00","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003955661","Eko=
unou","","28-12-2024 20:55:53","28-12-2024 20:50:37","28-12-2024 20:58:37",=
"Grid outage, site went down before gen start due to poor batteries backup =
// gen start automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor batteries backup // gen start automatically","ko=
uoh.jean@ihstowers.com","318","28-12-2024 20:55:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0003955530","Acropole=
","","28-12-2024 20:28:32","28-12-2024 19:59:43","28-12-2024 20:58:44","Cas=
caded Incident from TTO3929266","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage,gen failed to start due to=
 alarm ""full to start""//he reset it and starte the gen","system","345647"=
,"28-12-2024 20:28:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0003955531","C-Suprem=
e","","28-12-2024 20:28:32","28-12-2024 19:59:43","28-12-2024 20:58:44","Ca=
scaded Incident from TTO3929266","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","grid outage,gen failed to start due to alarm ""ful=
l to start""//he reset it and starte the gen","system","345646","28-12-2024=
 20:28:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0003955507","M=
vog Mbi New","IHS_YND_292, IHS_YND_055, IHS_YND_036, IHS_YND_021","28-12-20=
24 20:25:56","28-12-2024 19:59:43","28-12-2024 20:58:44","grid outage,gen f=
ailed to start due to alarm ""full to start""//he reset it and starte the g=
en","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","grid outage,gen failed to start due to alarm ""full to start""//he=
 reset it and starte the gen","stephane.nkamwa@ihstowers.com","1574","28-12=
-2024 20:25:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003955503","N=
kolndongo","","28-12-2024 20:24:37","28-12-2024 20:11:56","28-12-2024 20:35=
:56","grid outage,gen failed to due to CB 63A alimented the ATS disjuncted/=
/he reamed the CB","MINKA NICOLAS","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Circuit Breaker Issue","grid outage,gen failed to due=
 to CB 63A alimented the ATS disjuncted//he reamed the CB","stephane.nkamwa=
@ihstowers.com","762","28-12-2024 20:24:37","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003955454","Bit=
oto","","28-12-2024 20:20:03","28-12-2024 19:59:43","28-12-2024 22:17:49","=
Grid outage,site went down due to pwc ZTE dysfunction//he bypass it and sit=
e on Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rect=
ifier Module Overloaded","Grid outage,site went down due to pwc ZTE dysfunc=
tion//he bypass it and site on Gen","kouoh.jean@ihstowers.com","1221","28-1=
2-2024 20:20:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0003955414","O=
lezoa OCM","","28-12-2024 20:13:45","28-12-2024 19:59:43","28-12-2024 20:58=
:44","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
grid outage,gen failed to start due to alarm ""full to start""//he reset it=
 and starte the gen","stephane.nkamwa@ihstowers.com","345646","28-12-2024 2=
0:13:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0003955398","E=
koumdoum","","28-12-2024 20:10:36","28-12-2024 19:56:26","28-12-2024 20:23:=
25","Grid outage, site went down before gen start due to poor batteries bac=
kup // gen start automatically","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor batteries backup // gen start automatically"=
,"stephane.nkamwa@ihstowers.com","851","28-12-2024 20:10:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003955300","N=
kolfon Cimencam","","28-12-2024 20:01:18","28-12-2024 19:28:08","28-12-2024=
 19:58:08","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FME =
Georges 697461814 from Huawei is informed. repetitive issue ","Hyemafo Gild=
as","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site , Ubaie=3D54.4V site On Grid The Tx =
FME Georges 697461814 from Huawei is informed. repetitive issue ","stephane=
.nkamwa@ihstowers.com","1991","28-12-2024 20:01:18","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003955296","Bit=
eng","","28-12-2024 20:01:02","28-12-2024 19:51:49","28-12-2024 20:29:49","=
Site went down because CB (125A) tripped in DC box who feeds equipments MTN=
// CB put back on","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Circuit Breaker Issue","Site went down because CB =
(125A) tripped in DC box who feeds equipments MTN// CB put back on","kouoh.=
jean@ihstowers.com","554","28-12-2024 20:01:02","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003955287","AWA=
E OCM","","28-12-2024 20:00:03","28-12-2024 19:46:24","28-12-2024 21:39:18"=
,"Grid outage site went down because the PWC Dysfonction  //he reset the PW=
C and  manually started gen","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","Grid outage site went down bec=
ause the PWC Dysfonction  //he reset the PWC and  manually started gen","ko=
uoh.jean@ihstowers.com","820","28-12-2024 20:00:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0003955286","B=
arriere IHS","","28-12-2024 19:59:53","28-12-2024 19:17:45","28-12-2024 19:=
57:45","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FME Geor=
ges 697461814 from Huawei is informed. repetitive issue ","Hyemafo Gildas",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FME =
Georges 697461814 from Huawei is informed. repetitive issue ","stephane.nka=
mwa@ihstowers.com","2529","28-12-2024 19:59:53","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003955282","Eko=
unou","","28-12-2024 19:58:05","28-12-2024 19:44:58","28-12-2024 19:50:09",=
"Grid outage, site went down before gen start due to poor battery backup //=
 gen automatically started","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // gen automatically started","ko=
uoh.jean@ihstowers.com","789","28-12-2024 19:58:05","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003955214","ODZ=
A CITE MBIA","","28-12-2024 19:44:42","28-12-2024 19:22:11","28-12-2024 20:=
50:11","Grid outage, site went down because gen fails to start due to ats d=
isfunction // gen manually started","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","Grid outage, site went down because =
gen fails to start due to ats disfunction // gen manually started","kouoh.j=
ean@ihstowers.com","1352","28-12-2024 19:44:42","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0003955105","Nko=
l-Mbanda","","28-12-2024 19:22:20","28-12-2024 19:18:09","28-12-2024 19:42:=
09","Grid fluctuation,site went douwn due to bad voltage,no RCP on site// h=
e bypass the Grid and site on Gen","MINKA NICOLAS","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid fluctuation,site went douw=
n due to bad voltage,no RCP on site// he bypass the Grid and site on Gen","=
kouoh.jean@ihstowers.com","252","28-12-2024 19:22:20","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003955079","MIM=
BOMAN LIBERTE","","28-12-2024 19:16:38","28-12-2024 19:07:27","28-12-2024 1=
9:25:27","Grid Outage Site went down because Main Gen Faulty // Grid Restor=
ed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Faulty","Grid Outage Site went down because Main Gen Faulty // Grid R=
estored","kouoh.jean@ihstowers.com","552","28-12-2024 19:16:38","Sagemcom C=
MR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003955014","Elo=
umdem stade","","28-12-2024 19:07:57","28-12-2024 19:05:44","28-12-2024 19:=
19:44","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage and no rcp on ste // he bypass grid and manually start =
the gen","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation, site went down because gen start an=
d stopped due to grid bad voltage and no rcp on ste // he bypass grid and m=
anually start the gen","kouoh.jean@ihstowers.com","134","28-12-2024 19:07:5=
7","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0003954600","Mfo=
u EPC","","28-12-2024 18:01:42","28-12-2024 17:55:31","28-12-2024 19:45:31"=
,"grid outage, site went down because gen start and stopped with alarm low =
oil pressure // He reset gen card and gen manually started","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid ou=
tage, site went down because gen start and stopped with alarm low oil press=
ure // He reset gen card and gen manually started","kouoh.jean@ihstowers.co=
m","373","28-12-2024 18:01:42","Sagemcom CMR"
"Closed Complete","Site Down","T1396","IHS_YND_514","NOCINC0003954450","Eto=
udi2","","28-12-2024 17:28:45","28-12-2024 17:19:39","28-12-2024 18:51:15",=
"site went down because hight temperature due to extractor faulty in PWC //=
  He open PWC, site on grid","Delor Telezing","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Fans Faulty","site went down because hight=
 temperature due to fans faulty in PWC //  He open PWC, site on grid","kouo=
h.jean@ihstowers.com","547","28-12-2024 17:28:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003954425","M=
ontee-Jouvence-II","","28-12-2024 17:20:53","28-12-2024 17:16:47","28-12-20=
24 17:23:47","site went down because pwc overload(12k/230A) // site stabili=
zed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","site went down because pwc overload(12k/230A) // site st=
abilized","stephane.nkamwa@ihstowers.com","247","28-12-2024 17:20:53","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003954314","M=
endong vallee","","28-12-2024 17:04:47","28-12-2024 16:39:40","28-12-2024 1=
7:19:42","Grid outage, Site went down because Gen overload (20Kva, 300A)  /=
/ Grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage, Site went down because Gen overload (20Kva, 300A)=
  // Grid return","stephane.nkamwa@ihstowers.com","1509","28-12-2024 17:04:=
47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003954147","MVAN SAC=
EL","","28-12-2024 16:34:30","28-12-2024 16:06:03","28-12-2024 17:52:29","C=
ascaded Incident from TTO3927676","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Grid outage,site went down because =
Gen overload (20KVA,290 A) // Grid return","system","280728","28-12-2024 16=
:34:30","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0003954083","SIM=
BOCK BONAMBAPE","","28-12-2024 16:21:17","28-12-2024 16:05:53","28-12-2024 =
17:21:53","Grid fluctuation, site went down because gen fails to start due =
to grid bad voltage // he bypass grid and manually start the gen","Hyemafo =
Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, site went down because gen fails to start due to g=
rid bad voltage // he bypass grid and manually start the gen","kouoh.jean@i=
hstowers.com","1806","28-12-2024 16:21:17","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003954064","MVA=
N","IHS_YND_510","28-12-2024 16:16:47","28-12-2024 16:04:03","28-12-2024 17=
:52:43"," Grid outage,site went down because Gen overload (20KVA,290 A) // =
Grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload"," Grid outage,site went down because Gen overload (20KVA,290 A)=
 // Grid return","kouoh.jean@ihstowers.com","765","28-12-2024 16:16:47","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0003954028","Montee-J=
ouvence","","28-12-2024 16:07:20","28-12-2024 15:35:59","28-12-2024 16:07:5=
9","Cascaded Incident from TTO3927505","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation, site went do=
wn because gen fails to start due to grid bad voltage // he bypass grid and=
 manually start the gen","system","268110","28-12-2024 16:07:20","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0003953993","M=
endong","IHS_YND_692, IHS_YND_236","28-12-2024 16:02:10","28-12-2024 15:35:=
59","28-12-2024 16:07:59","Grid fluctuation, site went down because gen fai=
ls to start due to grid bad voltage // he bypass grid and manually start th=
e gen","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid fluctuation, site went down because gen fails t=
o start due to grid bad voltage // he bypass grid and manually start the ge=
n","stephane.nkamwa@ihstowers.com","1572","28-12-2024 16:02:10","Sagemcom C=
MR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003953987","ODZ=
A MINKAN EDIBI ASSI","","28-12-2024 16:00:37","28-12-2024 15:51:29","28-12-=
2024 15:52:29","ACTIVE, no power issue , U=3D54V on grid, tx fme Lionel/655=
 18 48 76/ From HUAWEI is informed.","Albran Byorel","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE, no=
 power issue , U=3D54V on grid, tx fme Lionel/655 18 48 76/ From HUAWEI is =
informed.","kouoh.jean@ihstowers.com","549","28-12-2024 16:00:37","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003953970","M=
endong vallee","","28-12-2024 15:58:49","28-12-2024 15:35:59","28-12-2024 1=
6:07:59","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid fluctuation, site went down because gen fails to start =
due to grid bad voltage // he bypass grid and manually start the gen","step=
hane.nkamwa@ihstowers.com","268110","28-12-2024 15:58:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0003953806","SAA 2","=
","28-12-2024 15:28:01","28-12-2024 15:17:45","28-12-2024 16:43:45","Cascad=
ed Incident from TTO3927216","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down due to work(Ulrich/6502915=
74/Sagemcom, replacement of the low hose // End of work","system","283345",=
"28-12-2024 15:28:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003953755","S=
aa","IHS_YND_401, IHS_YND_404","28-12-2024 15:21:55","28-12-2024 15:17:45",=
"28-12-2024 16:43:45","site went down due to work(Ulrich/650291574/Sagemcom=
, replacement of the low hose // End of work","Parker Tchoup","Equipment Re=
placement","Passive","Planned Activity","Planned Activity - Passive","site =
went down due to work(Ulrich/650291574/Sagemcom, replacement of the low hos=
e // End of work","stephane.nkamwa@ihstowers.com","251","28-12-2024 15:21:5=
5","Sagemcom CMR"
"Closed Complete","Warning","T2502","IHS_YND_781","NOCINC0003953717","BIBOM=
DJIDJIEL","","28-12-2024 15:14:00","","","SITE ON BATTERY","Kemeni Franklin=
","Warning","Warning","POWER","Warning - AC Phase 2 Voltage low","Alarm cle=
ared","nadjia.njaya@ihstowers.com","196","28-12-2024 15:14:00","Sagemcom CM=
R"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0003953624","Odz=
a petit marche new","","28-12-2024 14:55:50","28-12-2024 14:22:36","28-12-2=
024 15:03:01","Grid fluctuation, site went down because gen fails to start =
due to grid bad voltage // he bypass grid and manually start the gen","Albr=
an Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","Grid fluctuation, site went down because gen fails to start due t=
o grid bad voltage // he bypass grid and manually start the gen","kouoh.jea=
n@ihstowers.com","1995","28-12-2024 14:55:50","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003953378","Odz=
a II","","28-12-2024 14:01:52","28-12-2024 13:28:32","28-12-2024 14:17:02",=
"Grid outage, Site went down because Gen failed to start due to Hybrid syst=
em dysfonction// He reset Gen and started Gen manualy","Albran Byorel","Equ=
ipment Repair","Passive","Hybrid","Hybrid Module","Grid outage, Site went d=
own because Gen failed to start due to Hybrid system dysfonction// He reset=
 Gen and started Gen manualy","christian.fonkou@ihstowers.com","2003","28-1=
2-2024 14:01:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003953336","M=
elen Ba'aba","","28-12-2024 13:54:50","28-12-2024 13:51:46","28-12-2024 14:=
00:12","Site went down because CB(100A) tripped in DC BOX who feeds equipme=
nts OCM// He did a bridge with another CB(100A)","Siligap Boris","Equipment=
 Repair","Passive","Control Panel","Circuit Breaker Tripped","Site went dow=
n because CB(100A) tripped in DC BOX who feeds equipments OCM// He did a br=
idge with another CB(100A)","emmanuel.ghani@ihstowers.com","186","28-12-202=
4 13:54:50","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003953123","Sim=
bock MTN","","28-12-2024 13:21:21","28-12-2024 13:19:15","28-12-2024 13:32:=
25","site went down because gen failed to start due to grid bad voltage and=
 poor battery backup // Gen manually started","Fanda Brice","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","site went down=
 because gen failed to start due to grid bad voltage and poor battery backu=
p // Gen manually started","christian.fonkou@ihstowers.com","127","28-12-20=
24 13:21:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003953101","E=
bogo","","28-12-2024 13:17:09","28-12-2024 13:15:03","28-12-2024 13:17:46",=
"FME is on the way to the site ETA=3D02:30 PM","Siligap Boris","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
, Site went down before Gen start due to poor backup// Gen start automatica=
lly","emmanuel.ghani@ihstowers.com","128","28-12-2024 13:17:09","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003953086","E=
kie-Elegance","","28-12-2024 13:14:31","28-12-2024 13:07:22","28-12-2024 15=
:06:22","Grid outage//MDG of 20 kva has deployed","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG=
 of 20 kva has deployed","emmanuel.ghani@ihstowers.com","430","28-12-2024 1=
3:14:31","Sagemcom CMR"
"Closed Complete","Site Down","T1669","IHS_YND_195","NOCINC0003953069","chi=
na embassy yde","","28-12-2024 13:11:18","28-12-2024 13:09:11","28-12-2024 =
13:13:59","Site went down due to work: Karimou Ahmadou/680601705 from Prime=
 Africa working on site (Swapp PWC)// End of work","","Installation Activit=
y","Passive","Planned Activity","Installation Activity","Site went down due=
 to work: Karimou Ahmadou/680601705 from Prime Africa working on site (Swap=
p PWC)// End of work","christian.fonkou@ihstowers.com","128","28-12-2024 13=
:11:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0003952986","M=
essassi 2","","28-12-2024 12:53:17","28-12-2024 12:49:13","28-12-2024 15:42=
:36","Grid outage, site went down because gen fails to start due to pierced=
 generator pellet // he plugged the leaks  and Manually Started the Gen","F=
abrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine=
 Temp - Radiator Leakage","Grid outage, site went down because gen fails to=
 start due to pierced generator pellet // he plugged the leaks  and Manuall=
y Started the Gen","emmanuel.ghani@ihstowers.com","245","28-12-2024 12:53:1=
7","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003952921","D=
amas","","28-12-2024 12:45:11","28-12-2024 12:38:05","28-12-2024 13:15:39",=
" Grid Outage Site went down due to Gen Overload(9Kva,150A) // Grid return"=
,"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
" Grid Outage Site went down due to Gen Overload(9Kva,150A) // Grid return"=
,"emmanuel.ghani@ihstowers.com","427","28-12-2024 12:45:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003952747","N=
KOLMEKONG YDE","","28-12-2024 12:10:08","28-12-2024 12:07:02","28-12-2024 1=
2:11:36","Grid outage, Site went down before Gen start due to poor backup//=
 Grid return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, Site went down before Gen sta=
rt due to poor backup// Grid return","emmanuel.ghani@ihstowers.com","187","=
28-12-2024 12:10:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003952733","O=
dza II","","28-12-2024 12:04:32","28-12-2024 11:58:20","28-12-2024 12:28:44=
","Site went down pecause PWC dysfonction//He reconfigured it ,site on Gen"=
,"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","Site went down pecause PWC dysfonction//He reconfigured it ,s=
ite on Gen","emmanuel.ghani@ihstowers.com","374","28-12-2024 12:04:32","Sag=
emcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003952681","ODZ=
A CITE MBIA","","28-12-2024 11:48:30","28-12-2024 11:40:25","28-12-2024 13:=
32:13","Grid OUTAGE, site went down because gen fails to start due to ATS d=
ysfunctionning // Gen manually started","Albran Byorel","Equipment Repair",=
"Passive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down beca=
use gen fails to start due to ATS dysfunctionning // Gen manually started",=
"christian.fonkou@ihstowers.com","486","28-12-2024 11:48:30","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003952573","HOP=
ITAL GENERAL RAIL YDE","","28-12-2024 11:36:47","28-12-2024 11:34:38","28-1=
2-2024 11:58:53","Our Technician Delor/657108565/SAGEMCOM working on site (=
replacement Grid contactor)// End of work","Delor Telezing","Installation A=
ctivity","Passive","Planned Activity","Installation Activity","Our Technici=
an Delor/657108565/SAGEMCOM working on site (replacement Grid contactor)// =
End of work","christian.fonkou@ihstowers.com","130","28-12-2024 11:36:47","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003952509","O=
mnisport-Rail","","28-12-2024 11:27:06","28-12-2024 11:19:03","28-12-2024 1=
1:25:53","Active// No power issue on site U=3D53,4V , Site is on GridThe FM=
E TX Armand Nguesta (699949553) From Huawei is informed","Delor Telezing","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active// No power issue on site U=3D53,4V , Site is on GridThe F=
ME TX Armand Nguesta (699949553) From Huawei is informed","emmanuel.ghani@i=
hstowers.com","484","28-12-2024 11:27:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003952500","M=
ANGUIERS CHAPELLE","","28-12-2024 11:24:03","28-12-2024 11:17:59","28-12-20=
24 11:33:33","Site was on Gen due Grid outage, Site went down before Gen st=
art due to poor backup// Grid power restored","Fabrice Pouakam","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Site was o=
n Gen due Grid outage, Site went down before Gen start due to poor backup//=
 Grid power restored","emmanuel.ghani@ihstowers.com","366","28-12-2024 11:2=
4:03","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003952304","Elo=
umdem stade","","28-12-2024 10:47:07","28-12-2024 10:43:02","28-12-2024 10:=
59:05","Grid fluctuation, site went down because Gen start and stopped due =
to Grid bad voltage no Rcp //He bypass the Grid and Gen manually started","=
Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation, site went down because Gen start and stopped =
due to Grid bad voltage no Rcp //He bypass the Grid and Gen manually starte=
d","emmanuel.ghani@ihstowers.com","246","28-12-2024 10:47:07","Sagemcom CMR=
"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003952196","Mim=
boman3","","28-12-2024 10:25:06","28-12-2024 10:22:56","28-12-2024 10:36:25=
"," Grid outage, Site went down to due to PWC ""ZTE' dysfunction// Grid ret=
urn","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier=
 Module Overloaded"," Grid outage, Site went down to due to PWC ""ZTE' dysf=
unction// Grid return","christian.fonkou@ihstowers.com","131","28-12-2024 1=
0:25:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003952150","E=
bogo","","28-12-2024 10:13:02","28-12-2024 10:10:58","28-12-2024 10:13:54",=
"Grid fluctuation, Site went down before Gen start due to poor backup// Gri=
d return","Siligap Boris","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid fluctuation, Site went down before Gen star=
t due to poor backup// Grid return","emmanuel.ghani@ihstowers.com","125","2=
8-12-2024 10:13:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003951968","K=
oweit City","","28-12-2024 09:38:35","28-12-2024 09:33:31","28-12-2024 09:4=
2:30","Grid outage, site went down gen start and stopped with alarm ""low f=
uel""(unprouven alarm) // He reset gen card and gen manually started","Albr=
an Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage, site went down gen start and stopped with alarm ""low fuel""(u=
nprouven alarm) // He reset gen card and gen manually started","emmanuel.gh=
ani@ihstowers.com","305","28-12-2024 09:38:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003951792","MVAN SAC=
EL","","28-12-2024 09:08:50","28-12-2024 09:06:45","28-12-2024 09:09:38","C=
ascaded Incident from TTO3924861","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation,site went down beca=
use Gen overload (20KVA,290 A) // Grid restored","system","269867","28-12-2=
024 09:08:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003951777","M=
VAN","IHS_YND_510","28-12-2024 09:07:50","28-12-2024 09:06:45","28-12-2024 =
09:10:00","Grid fluctuation,site went down because Gen overload (20KVA,290 =
A) // Grid restored","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid fluctuation,site went down because Gen overload (=
20KVA,290 A) // Grid restored","emmanuel.ghani@ihstowers.com","65","28-12-2=
024 09:07:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003951770","C=
rf-Nsam","","28-12-2024 09:06:58","28-12-2024 09:04:53","28-12-2024 10:20:3=
9","ACTIVE / No power issue site on Grid with U=3D53,2 V The Tx FME Tchana =
Patrice 695007608 of huawei is informed","MINKA NICOLAS","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE=
 / No power issue site on Grid with U=3D53,2 V The Tx FME Tchana Patrice 69=
5007608 of huawei is informed","emmanuel.ghani@ihstowers.com","126","28-12-=
2024 09:06:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003951678","D=
amas","","28-12-2024 08:39:13","28-12-2024 08:37:02","28-12-2024 09:00:04",=
"Grid Outage Site went down because Gen Overload(9Kva,150A)// Grid return",=
"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid Outage Site went down because Gen Overload(9Kva,150A)// Grid return","=
emmanuel.ghani@ihstowers.com","132","28-12-2024 08:39:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003951566","Akak-Nko=
zoa-MTN-IHS","","28-12-2024 08:13:40","28-12-2024 08:09:26","28-12-2024 08:=
13:46","Cascaded Incident from TTO3924618","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site down du=
e to poor backup    //   site on gen","system","266012","28-12-2024 08:13:4=
0","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003951554","Evo=
doula MTN","","28-12-2024 08:11:52","28-12-2024 08:05:44","28-12-2024 09:58=
:01","Grid outage, Site went down because Gen started and stopped due due t=
o fuse of Gen Card faulty// He did a bridge and started Gen manualy ","TIEN=
TCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Grid outage, Site went down because Gen started and stopped due =
due to fuse of Gen Card faulty// He did a bridge and started Gen manualy ",=
"christian.fonkou@ihstowers.com","369","28-12-2024 08:11:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003951480","D=
amas","","28-12-2024 07:52:20","28-12-2024 07:46:15","28-12-2024 07:52:34",=
"Grid Outage Site went down because Gen Overload(9Kva,150A)// Grid return",=
"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid Outage Site went down because Gen Overload(9Kva,150A)// Grid return","=
emmanuel.ghani@ihstowers.com","366","28-12-2024 07:52:20","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003951366","Nko=
lmvack","","28-12-2024 07:34:31","28-12-2024 07:28:25","28-12-2024 08:54:29=
","Grid outage, site went down because gen failed to start due to battery g=
en FAULTY // He replaced battery Gen faulty and started Gen manualy","Parke=
r Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery=
","Grid outage, site went down because gen failed to start due to battery g=
en FAULTY // He replaced battery Gen faulty and started Gen manualy","chris=
tian.fonkou@ihstowers.com","367","28-12-2024 07:34:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003951362","Akak-Nko=
zoa-MTN-IHS","","28-12-2024 07:32:11","28-12-2024 07:29:58","28-12-2024 07:=
30:04","Cascaded Incident from TTO3924392","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Grid outage, site down due t=
o poor backup   //   site on Gen","system","261282","28-12-2024 07:32:11","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003951200","N=
gouetou","","28-12-2024 06:44:52","28-12-2024 06:42:43","28-12-2024 06:45:4=
5","No power issue on site, site on Gen The Tx FME Gregoire/654547479 from =
huawei is informed and up at 06:44 AM","Parker Tchoup","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site, site on Gen The Tx FME Gregoire/654547479 from huawei is in=
formed and up at 06:44 AM","emmanuel.ghani@ihstowers.com","131","28-12-2024=
 06:44:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003950877","N=
gouetou","","28-12-2024 04:35:54","28-12-2024 04:33:40","28-12-2024 04:38:5=
8","ACTIVE//No power issue on site U=3D52V site on Gen The Tx FME Gregoire/=
654547479 from huawei is informed. ","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//No=
 power issue on site U=3D52V site on Gen The Tx FME Gregoire/654547479 from=
 huawei is informed. ","olivier.kwedi@ihstowers.com","135","28-12-2024 04:3=
5:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003950786","Ebeba","=
","28-12-2024 03:34:21","28-12-2024 03:06:33","28-12-2024 03:11:51","Cascad=
ed Incident from TTO3923692","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","ACTIVE / No power issue site on Grid with U=3D=
50 V=20

The Tx FME Etienne 695033981 of huawei is informed
","system","269625","28-12-2024 03:34:21","Sagemcom CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0003950783","Nke=
ng likok","IHS_YND_339","28-12-2024 03:33:38","28-12-2024 03:06:33","28-12-=
2024 05:46:09","ACTIVE / No power issue site on Grid with U=3D50 V   The Tx=
 FME Etienne 695033981 of huawei is informed","Kemeni Franklin","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE / No power issue site on Grid with U=3D50 V=20

The Tx FME Etienne 695033981 of huawei is informed
","ludivine.ngamaleu@ihstowers.com","1626","28-12-2024 03:33:38","Sagemcom =
CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003950645","Nsi=
meyong Terre Rouge","","28-12-2024 02:08:44","28-12-2024 02:06:36","28-12-2=
024 02:18:16","Grid outage, Site went down before Gen start due to poor bac=
kup// Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before Gen start due to poor backup// Gen start automatically","ludivine.n=
gamaleu@ihstowers.com","129","28-12-2024 02:08:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_800","NOCINC0003950511","ODZA CIT=
E MBIA","","28-12-2024 01:18:05","28-12-2024 00:40:54","28-12-2024 01:07:46=
"," grid OUTAGE, site went down because gen fails to start due to ATS disfu=
nctionning // site on Grid","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","ATS-AMF Issue"," grid OUTAGE, site went down because gen fai=
ls to start due to ATS disfunctionning // site on Grid","etienne.itondo@ihs=
towers.com","2232","28-12-2024 01:18:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003950485","M=
ontee-Jouvence-II","","28-12-2024 01:06:21","28-12-2024 00:36:08","28-12-20=
24 00:57:03","grid outage, Site went down due to PWC over load(12KW.280A)//=
 gen manually started","Hyemafo Gildas","Equipment Repair","Passive","Recti=
fier","Rectifier Module Overloaded","grid outage, Site went down due to PWC=
 over load(12KW.280A)// gen manually started","etienne.itondo@ihstowers.com=
","1814","28-12-2024 01:06:21","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003950226","SOA=
 UNIVERSITY STADIUM","","27-12-2024 23:33:43","27-12-2024 23:29:35","28-12-=
2024 00:38:46","site went down because gen ran until fuel shortage // Refue=
ling down","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage,gen ran until fuel shortage//Refueling done","ludivine.ngamal=
eu@ihstowers.com","249","27-12-2024 23:33:43","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003950142","Men=
dong3","","27-12-2024 23:02:40","27-12-2024 21:33:15","28-12-2024 00:35:21"=
,"grid outage, no space to deploy a mobil gen // grid return ","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, no =
space to deploy a mobil gen // grid return ","ludivine.ngamaleu@ihstowers.c=
om","5391","27-12-2024 23:02:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003950115","M=
arche Odza","","27-12-2024 22:53:38","27-12-2024 22:44:32","27-12-2024 22:5=
8:34","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen started automatically","Albran Byorel","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // Gen started automaticall=
y","olivier.kwedi@ihstowers.com","547","27-12-2024 22:53:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003950040","K=
oweit City","","27-12-2024 22:36:24","27-12-2024 22:28:08","27-12-2024 23:3=
6:13","grid ouitage, site went down gen start and stopped with alarm low fu=
el // He reset gen card and gen manually started","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","grid ouitage, site w=
ent down gen start and stopped with alarm low fuel // He reset gen card and=
 gen manually started","olivier.kwedi@ihstowers.com","497","27-12-2024 22:3=
6:24","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0003950036","Eto=
 koss Yde","","27-12-2024 22:35:59","27-12-2024 22:31:55","27-12-2024 23:51=
:48","grid outage, sita went down because gen failed to start due to gen co=
ntactor faulty // He bypassed gen contactor and gen manually started","Fand=
a Brice","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","grid=
 outage, sita went down because gen failed to start due to gen contactor fa=
ulty // He bypassed gen contactor and gen manually started","ludivine.ngama=
leu@ihstowers.com","322","27-12-2024 22:35:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003949987","M=
VAN SACEL","","27-12-2024 22:27:01","27-12-2024 22:16:17","28-12-2024 00:39=
:32","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage ,site went down because Gen start and stopped due =
to Gen overload (20KVA,290 A) // Grid power retuirn","olivier.kwedi@ihstowe=
rs.com","287175","27-12-2024 22:27:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003949980","S=
atcom","","27-12-2024 22:25:42","27-12-2024 22:16:37","28-12-2024 03:21:35"=
,"ACTIVE//No power issue on site, site on Grid Ubaie=3D50,1V .The Tx Fme Ar=
mand nguetsa(691144412) From huawei is informed.","Delor Telezing","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE//No power issue on site, site on Grid Ubaie=3D50,1V .The Tx Fme =
Armand nguetsa(691144412) From huawei is informed.","olivier.kwedi@ihstower=
s.com","546","27-12-2024 22:25:42","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0003949965","Mon=
tee-Jouvence-II","","27-12-2024 22:23:16","27-12-2024 22:18:11","27-12-2024=
 22:25:12","grid outage, Site went down due to PWC over load(12KW.280A)// g=
en manually started","Hyemafo Gildas","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","grid outage, Site went down due to PWC o=
ver load(12KW.280A)// grid return","ludivine.ngamaleu@ihstowers.com","306",=
"27-12-2024 22:23:16","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003949953","MVA=
N","IHS_YND_510","27-12-2024 22:20:23","27-12-2024 22:16:17","28-12-2024 00=
:40:11","Grid outage ,site went down because Gen start and stopped due to G=
en overload (20KVA,290 A) // Grid power retuirn","MINKA NICOLAS","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went dow=
n because Gen start and stopped due to Gen overload (20KVA,290 A) // Grid p=
ower retuirn","ludivine.ngamaleu@ihstowers.com","246","27-12-2024 22:20:23"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0003949938","ELO=
UMDEM CARRIERE","","27-12-2024 22:16:09","27-12-2024 22:13:03","27-12-2024 =
23:20:52","site went down because gen failed to start due to grid bad volta=
ge// Gen manually started","Fanda Brice","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","site went down because gen failed t=
o start due to grid bad voltage// Gen manually started","ludivine.ngamaleu@=
ihstowers.com","187","27-12-2024 22:16:09","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003949926","ODZ=
A CITE MBIA","","27-12-2024 22:14:42","27-12-2024 22:05:38","27-12-2024 22:=
20:51","Gen stopped due to grid return, site went down because gen fails to=
 start due to ats disfunction // He putt site on grid","Albran Byorel","Equ=
ipment Repair","Passive","Control Panel","ATS-AMF Issue","Gen stopped due t=
o grid return, site went down because gen fails to start due to ats disfunc=
tion // He putt site on grid","ludivine.ngamaleu@ihstowers.com","545","27-1=
2-2024 22:14:42","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003949884","N=
yanon","","27-12-2024 22:03:38","27-12-2024 21:52:30","27-12-2024 22:17:41"=
,"site went down because gen stopped with alarm Low oil pressure // He adde=
d oil pressure and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","site went down =
because gen stopped with alarm Low oil pressure // He added oil pressure an=
d gen manually started","alexandre.kamal@ihstowers.com","669","27-12-2024 2=
2:03:38","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0003949830","MBA=
LNGONG LYCEE","","27-12-2024 21:50:37","27-12-2024 21:35:29","27-12-2024 22=
:07:42","grid outage, site went down due to gen overload(09kva, 70A)// He r=
educed the load and gen manually started","Fanda Brice","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","grid outage, site went down due to =
gen overload(09kva, 70A)// He reduced the load and gen manually started","k=
amga.virgile@ihstowers.com","910","27-12-2024 21:50:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003949741","E=
kie-Elegance","","27-12-2024 21:36:08","27-12-2024 21:27:59","28-12-2024 09=
:53:27","Access issue during the night due to landload Grid outage//MDG of =
20 kva has deployed","Albran Byorel","Access Denial","Lease Or Legal","Land=
lord Related Issues","Access Issue - Land Lord","Access issue during the ni=
ght due to landload Grid outage//MDG of 20 kva has deployed","alexandre.kam=
al@ihstowers.com","489","27-12-2024 21:36:08","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003949725","OBA=
M NGOLA OCM","","27-12-2024 21:33:32","27-12-2024 21:23:19","27-12-2024 21:=
51:48","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // Grid power stabilized","MINKA NICOLAS","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on, site went down because gen start and stopped due to grid bad voltage //=
 Grid power stabilized","kamga.virgile@ihstowers.com","614","27-12-2024 21:=
33:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003949652","D=
amas","","27-12-2024 21:17:52","27-12-2024 21:03:49","28-12-2024 00:00:17",=
" grid outage,site went down due to Gen Overload(9Kva,150A) // Grid return"=
,"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
" grid outage,site went down due to Gen Overload(9Kva,150A) // Grid return"=
,"alexandre.kamal@ihstowers.com","844","27-12-2024 21:17:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003949569","M=
ontee-Jouvence-II","","27-12-2024 21:00:37","27-12-2024 20:57:17","27-12-20=
24 21:00:11","site went down because pwc overload(12k/230A) // site stabili=
zed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","site went down because pwc overload(12k/230A) // site st=
abilized","alexandre.kamal@ihstowers.com","201","27-12-2024 21:00:37","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003949561","M=
efou-Assi","","27-12-2024 20:58:30","27-12-2024 20:51:24","27-12-2024 22:43=
:24","site went down because gen failed to start due to grid bad voltage an=
d disjunction at BTS OCM // Gen automatically started","Fanda Brice","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","site we=
nt down because gen failed to start due to grid bad voltage and disjunction=
 at BTS OCM // Gen automatically started","alexandre.kamal@ihstowers.com","=
427","27-12-2024 20:58:30","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003949541","OBA=
M NGOLA OCM","","27-12-2024 20:55:27","27-12-2024 20:51:20","27-12-2024 20:=
57:05","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // Grid power stabilized","MINKA NICOLAS","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on, site went down because gen start and stopped due to grid bad voltage //=
 Grid power stabilized","kamga.virgile@ihstowers.com","248","27-12-2024 20:=
55:27","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003949399","Bit=
eng","","27-12-2024 20:35:22","27-12-2024 20:31:09","27-12-2024 20:57:46","=
Site went down because CB (125A) tripped in DC box who feeds equipments MTN=
// CB put back on","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Circuit Breaker Issue","Site went down because CB =
(125A) tripped in DC box who feeds equipments MTN// CB put back on","kamga.=
virgile@ihstowers.com","254","27-12-2024 20:35:22","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003949381","Nom=
ayos montee Meche","","27-12-2024 20:33:46","27-12-2024 20:16:36","27-12-20=
24 20:46:27","Grid fluctuation, site went down because gen fails to start d=
ue to grid bad voltage //GEN START AUTOMATICALLY","Fanda Brice","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tion, site went down because gen fails to start due to grid bad voltage //G=
EN START AUTOMATICALLY","kamga.virgile@ihstowers.com","1030","27-12-2024 20=
:33:46","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003949368","Evo=
doula MTN","","27-12-2024 20:31:31","27-12-2024 19:47:14","27-12-2024 20:53=
:28","site went down because gen failed to start due to grid bad voltage an=
d no RCP// Gen manually started","TIENTCHEU NZETCHIEU GAEL","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","site went down b=
ecause gen failed to start due to grid bad voltage and no RCP// Gen manuall=
y started","kamga.virgile@ihstowers.com","2658","27-12-2024 20:31:31","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003949300","M=
endong vallee","","27-12-2024 20:21:37","27-12-2024 19:56:32","27-12-2024 2=
3:02:13","Grid Outage Site went down because Gen Overload(20Kva,300A) waiti=
ng  Grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid Outage Site went down because Gen Overload(20Kva,300A) =
waiting  Grid return","alexandre.kamal@ihstowers.com","1506","27-12-2024 20=
:21:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0003949291","S=
apeur Mimboman","","27-12-2024 20:19:49","27-12-2024 19:50:42","28-12-2024 =
04:30:06","access issue during the night due to landload: Site went down be=
cause  rectifier (1/6) went faulty// site stabilized (rectifier to be repla=
ced)","Mba Lazare Herve","Access Denial","Lease Or Legal","Landlord Related=
 Issues","Access Issue - Land Lord","access issue during the night due to l=
andload: Site went down because  rectifier (1/6) went faulty// site stabili=
zed (rectifier to be replaced)","alexandre.kamal@ihstowers.com","1748","27-=
12-2024 20:19:49","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003949238","MAN=
GUIERS CHAPELLE","","27-12-2024 20:11:06","27-12-2024 19:29:52","27-12-2024=
 20:50:26","Grid outage, Site went down before Gen start due to poor backup=
// Gen start automatically","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup// Gen start automatically","kamga.virgi=
le@ihstowers.com","2948","27-12-2024 20:11:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003949229","SOA VILL=
AGE","","27-12-2024 20:09:20","27-12-2024 19:55:03","27-12-2024 20:16:27","=
Cascaded Incident from TTO3921913","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went because=
 gen start and stopped due to grid bad voltage, no rcp on site // he bypass=
ed  Grid and manually start the gen","system","266989","27-12-2024 20:09:20=
","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003949217","SOA=
 TOWN","IHS_YND_323","27-12-2024 20:08:18","27-12-2024 19:54:12","27-12-202=
4 20:16:57","Grid fluctuation, site went because gen start and stopped due =
to grid bad voltage, no rcp on site // he bypassed  Grid and manually start=
 the gen","Siligap Boris","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","Grid fluctuation, site went because gen start and =
stopped due to grid bad voltage, no rcp on site // he bypassed  Grid and ma=
nually start the gen","kamga.virgile@ihstowers.com","1392","27-12-2024 20:0=
8:18","Sagemcom CMR"
"Closed Complete","Site Down","T1579","IHS_YND_480","NOCINC0003948969","Sic=
 Cite Verte Matgenie","","27-12-2024 19:21:24","27-12-2024 19:03:07","27-12=
-2024 20:08:07","Site went down due to work  Karim/680601705(Swap PWC) is w=
orking on site // End of work","","Installation Activity","Passive","Planne=
d Activity","Installation Activity","Site went down due to work  Karim/6806=
01705(Swap PWC) is working on site // End of work","kamga.virgile@ihstowers=
.com","1098","27-12-2024 19:21:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003948661","M=
elen Ba'aba","","27-12-2024 18:35:36","27-12-2024 18:21:31","27-12-2024 18:=
48:10","Grid outage, gen fails to start due to battery ge discharged // gen=
 start with battery backup (investigation ongoing)","Siligap Boris","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage, ge=
n fails to start due to battery ge discharged // gen start with battery bac=
kup (investigation ongoing)","alexandre.kamal@ihstowers.com","846","27-12-2=
024 18:35:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003948494","E=
bogo","","27-12-2024 17:56:35","27-12-2024 17:52:31","27-12-2024 18:25:31",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
t manually","Siligap Boris","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage, Site went down before Gen start d=
ue to poor backup// Gen start manually","alexandre.kamal@ihstowers.com","24=
5","27-12-2024 17:56:35","Sagemcom CMR"
"Closed Complete","Warning","CTR_062","IHS_YND_310","NOCINC0003948460","Nom=
ayos","","27-12-2024 17:45:33","","","Site alarming on battery because rect=
ifiers disfunction due to MPR disfunction// he reset rectifers (MPR to be r=
eplaced)","Fanda Brice","Warning","Warning","POWER","Warning - Site on Batt=
ery","Site alarming on battery because rectifiers disfunction due to MPR di=
sfunction// he reset rectifers (MPR to be replaced)","dorothy.djantio@ihsto=
wers.com","304","27-12-2024 17:45:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0003948451","SAA Entr=
ance","","27-12-2024 17:43:00","27-12-2024 17:38:45","27-12-2024 18:13:59",=
"Cascaded Incident from TTO3921047","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because 02/03 recti=
fiers hanging //He reset rectifiers ;site on Grid","system","275168","27-12=
-2024 17:43:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003948452","Saa","",=
"27-12-2024 17:43:00","27-12-2024 17:38:45","27-12-2024 18:13:59","Cascaded=
 Incident from TTO3921047","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because 02/03 rectifiers han=
ging //He reset rectifiers ;site on Grid","system","275168","27-12-2024 17:=
43:00","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0003948448","SAA=
 2","IHS_YND_542, IHS_YND_405","27-12-2024 17:42:06","27-12-2024 17:33:42",=
"27-12-2024 18:13:59","Site went down because 02/03 rectifiers hanging //He=
 reset rectifiers ;site on Grid","Parker Tchoup","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down because 02/03 rectifiers =
hanging //He reset rectifiers ;site on Grid","kamga.virgile@ihstowers.com",=
"665","27-12-2024 17:42:06","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003948439","ODZ=
A CITE MBIA","","27-12-2024 17:40:26","27-12-2024 17:09:11","27-12-2024 17:=
41:11","Grid outage, site went down because gen fails to start due to ats d=
isfunction // gen manually started","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","Grid outage, site went down because =
gen fails to start due to ats disfunction // gen manually started","kamga.v=
irgile@ihstowers.com","1876","27-12-2024 17:40:26","Sagemcom CMR"
"Closed Complete","Warning","T0091","IHS_YND_314","NOCINC0003948298","Sous =
Prefecture","","27-12-2024 17:12:23","","","Site alarming because site on b=
attery due to 02/ 05 rectifiers  hanging//he reset rectifiers  ,site on gen=
","Fanda Brice","Warning","Warning","POWER","Warning - Site on Battery","Si=
te alarming because site on battery due to 02/ 05 rectifiers  hanging//he r=
eset rectifiers  ,site on gen","dorothy.djantio@ihstowers.com","125","27-12=
-2024 17:12:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0003948166","Omnispor=
t-Rail","","27-12-2024 16:47:30","27-12-2024 16:39:45","27-12-2024 16:55:45=
","Cascaded Incident from TTO3920628","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen start automatically","system","26437=
1","27-12-2024 16:47:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003948091","M=
ANGUIERS CHAPELLE","IHS_YND_506","27-12-2024 16:41:54","27-12-2024 16:39:45=
","27-12-2024 16:55:45","Grid outage, Site went down before Gen start due t=
o poor backup// Gen start automatically","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Si=
te went down before Gen start due to poor backup// Gen start automatically"=
,"alexandre.kamal@ihstowers.com","130","27-12-2024 16:41:54","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003947909","MVA=
N","","27-12-2024 16:20:19","27-12-2024 16:18:11","27-12-2024 16:24:32","Gr=
id outage ,site went down because Gen start and stopped due to  Gen overloa=
d (20KVA,290 A) // Grid power retuirn","MINKA NICOLAS","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went down because =
Gen start and stopped due to  Gen overload (20KVA,290 A) // Grid power retu=
irn","kamga.virgile@ihstowers.com","129","27-12-2024 16:20:19","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003947889","M=
endong vallee","","27-12-2024 16:16:34","27-12-2024 16:06:59","27-12-2024 1=
6:35:47","Grid outage ,site went down because Gen start and stopped due to =
 Gen overload (20KVA,290 A) // Grid power retuirn","Fanda Brice","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went dow=
n because Gen start and stopped due to  Gen overload (20KVA,290 A) // Grid =
power retuirn","alexandre.kamal@ihstowers.com","577","27-12-2024 16:16:34",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003947615","Men=
dong3","","27-12-2024 15:44:24","27-12-2024 15:41:13","27-12-2024 16:31:19"=
,"Grid outage ,no space to deploy MDG// Grid return","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage ,no space to d=
eploy MDG// Grid return","kamga.virgile@ihstowers.com","192","27-12-2024 15=
:44:24","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0003947516","Mon=
tee Jouvence","","27-12-2024 15:37:33","27-12-2024 15:22:23","27-12-2024 15=
:44:23","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // he added water and manually start the gen","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","Grid outage, site went down because gen start and stopped wi=
th high temp alarm // he added water and manually start the gen","kamga.vir=
gile@ihstowers.com","911","27-12-2024 15:37:33","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0003947229","Mvo=
g-Manga","","27-12-2024 14:54:57","27-12-2024 14:46:45","27-12-2024 15:42:4=
9","Grid fluctuation, site went down down because gen start and stopped due=
 to grid bad voltage // he bypass grid and manually start the gen","Albran =
Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, site went down down because gen start and stopped =
due to grid bad voltage // he bypass grid and manually start the gen","kamg=
a.virgile@ihstowers.com","494","27-12-2024 14:54:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0003947178","E=
BOM","","27-12-2024 14:45:14","27-12-2024 14:37:10","27-12-2024 15:23:10","=
Grid outage, site went down because gen start and stopped with high temp al=
arm // he added water and manually start the gen","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Is=
sue","Grid outage, site went down because gen start and stopped with high t=
emp alarm // he added water and manually start the gen","alexandre.kamal@ih=
stowers.com","485","27-12-2024 14:45:14","Sagemcom CMR"
"Closed Complete","Warning","T0459","IHS_YND_240","NOCINC0003947176","Monte=
e Jouvence","","27-12-2024 14:44:45","","","Grid outage, site went alarm be=
cause gen start and stopped with high temp alarm // he added water and manu=
ally start the gen","Hyemafo Gildas","Warning","Warning","POWER","Warning -=
 Site on Battery","Grid outage, site went alarm because gen start and stopp=
ed with high temp alarm // he added water and manually start the gen","doro=
thy.djantio@ihstowers.com","245","27-12-2024 14:44:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003946997","Essomba"=
,"","27-12-2024 14:11:41","27-12-2024 12:58:14","27-12-2024 13:00:00","Casc=
aded Incident from TTO3919045","Mba Lazare Herve","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active, no power issue, site on grid wi=
th U=3D54V, site impacted by Mimboman nodale","system","277642","27-12-2024=
 14:11:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0003946998","Biteng",=
"","27-12-2024 14:11:41","27-12-2024 12:58:14","27-12-2024 13:00:00","Casca=
ded Incident from TTO3919045","Mba Lazare Herve","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active, no power issue, site on grid wit=
h U=3D54V, site impacted by Mimboman nodale","system","277642","27-12-2024 =
14:11:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003946994","Tradex-N=
komo","","27-12-2024 14:11:40","27-12-2024 12:58:14","27-12-2024 13:00:00",=
"Cascaded Incident from TTO3919045","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active, no power issue, site on grid =
with U=3D54V, site impacted by Mimboman nodale","system","277640","27-12-20=
24 14:11:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_166","NOCINC0003946995","Damas","=
","27-12-2024 14:11:40","27-12-2024 12:58:14","27-12-2024 13:00:00","Cascad=
ed Incident from TTO3919045","MINKA NICOLAS","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active, no power issue, site on grid with U=
=3D54V, site impacted by Mimboman nodale","system","277640","27-12-2024 14:=
11:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003946993","Bitoto",=
"","27-12-2024 14:11:40","27-12-2024 12:58:14","27-12-2024 13:00:00","Casca=
ded Incident from TTO3919045","Mba Lazare Herve","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active, no power issue, site on grid wit=
h U=3D54V, site impacted by Mimboman nodale","system","277640","27-12-2024 =
14:11:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003946996","AWAE OCM=
","","27-12-2024 14:11:40","27-12-2024 12:58:14","27-12-2024 13:00:00","Cas=
caded Incident from TTO3919045","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active, no power issue, site on grid w=
ith U=3D54V, site impacted by Mimboman nodale","system","277641","27-12-202=
4 14:11:40","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003946944","MIM=
BOMAN LIBERTE","","27-12-2024 14:00:00","27-12-2024 13:58:34","27-12-2024 1=
5:18:50","Grid outage, Site went down because Main Gen faulty// He deployed=
 MDG of 20Kva","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage, Site went down because Main Gen faul=
ty// He deployed MDG of 20Kva","kouoh.jean@ihstowers.com","89","27-12-2024 =
14:00:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003946728","S=
tade-Abega","","27-12-2024 13:24:48","27-12-2024 12:57:36","27-12-2024 12:5=
8:36","No pwer issus, site is on grid with Ubaie=3D53V site impacted by mim=
boman nodale","Mba Lazare Herve","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No pwer issus, site is on grid=
 with Ubaie=3D53V site impacted by mimboman nodale","stephane.nkamwa@ihstow=
ers.com","1634","27-12-2024 13:24:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0003946725","Abang","=
","27-12-2024 13:23:50","27-12-2024 12:58:14","27-12-2024 13:00:00","Cascad=
ed Incident from TTO3919045","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active, no power issue, site on grid with=
 U=3D54V, site impacted by Mimboman nodale","system","277641","27-12-2024 1=
3:23:50","Sagemcom CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0003946715","Av-=
Germaine","","27-12-2024 13:22:25","27-12-2024 13:19:17","27-12-2024 19:06:=
50","	Grid outage, no space to deploy a mobil gen // grid return ","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 no space to deploy a mobil gen // grid return ","kouoh.jean@ihstowers.com"=
,"189","27-12-2024 13:22:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0003946684","N=
kolangaa","IHS_YND_292, IHS_YND_172, IHS_YND_166, IHS_YND_173, IHS_YND_179,=
 IHS_YND_248, IHS_YND_290","27-12-2024 13:17:33","27-12-2024 12:58:14","27-=
12-2024 13:00:00","Active, no power issue, site on grid with U=3D54V, site =
impacted by Mimboman nodale","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no powe=
r issue, site on grid with U=3D54V, site impacted by Mimboman nodale","step=
hane.nkamwa@ihstowers.com","1160","27-12-2024 13:17:33","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003945699","Nko=
g-Edzen","","27-12-2024 10:32:58","27-12-2024 10:06:30","27-12-2024 11:06:1=
3","site went down because gen start and stopped with 'higth temp' alarm du=
e to pierced radiator // he added water and manualy start the gen (Radiator=
 to be replace)","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","A=
CDG - Radiator Leakage","site went down because gen start and stopped with =
'higth temp' alarm due to pierced radiator // he added water and manualy st=
art the gen (Radiator to be replace)","kouoh.jean@ihstowers.com","1589","27=
-12-2024 10:32:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0003945530","SAA 2","=
","27-12-2024 10:02:40","27-12-2024 09:55:56","27-12-2024 10:24:23","Cascad=
ed Incident from TTO3917774","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue U=3D 54.3V site on Gr=
id The TX FME Gregoire(654547479) from Huawei is informed,site up at 10:05 =
AM","system","273955","27-12-2024 10:02:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003945521","S=
aa","IHS_YND_404","27-12-2024 10:01:07","27-12-2024 09:55:56","27-12-2024 1=
2:30:18","Active//No power issue U=3D 54.3V site on Grid The TX FME Gregoir=
e(654547479) from Huawei is informed,site up at 10:05 AM","Parker Tchoup","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue U=3D 54.3V site on Grid The TX FME Gregoi=
re(654547479) from Huawei is informed,site up at 10:05 AM","stephane.nkamwa=
@ihstowers.com","312","27-12-2024 10:01:07","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003945468","NKO=
MEKUI OCM","","27-12-2024 09:47:34","27-12-2024 09:26:18","27-12-2024 09:28=
:32","No power issue on site U=3D54,5v site on gen site down because is imp=
acted by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site U=3D54,5v site on gen site down becaus=
e is impacted by Mbankolo Camtel and not managing by IHS","kouoh.jean@ihsto=
wers.com","1277","27-12-2024 09:47:34","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0003945415","N=
dogbessol","","27-12-2024 09:33:41","27-12-2024 09:20:27","27-12-2024 09:27=
:35","Active// No power issue, Site on gen Ubai=3D53.5V The FME Tx Etienne/=
699949193/From Huawei is informed","Kemeni Franklin","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// N=
o power issue, Site on gen Ubai=3D53.5V The FME Tx Etienne/699949193/From H=
uawei is informed","stephane.nkamwa@ihstowers.com","795","27-12-2024 09:33:=
41","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003945346","ODZ=
A MINKAN EDIBI ASSI","","27-12-2024 09:17:32","27-12-2024 09:00:27","27-12-=
2024 11:02:20","Grid fluctuation, site went down because Gen failed to star=
t due to Grid bad voltage // he bypass the Grid and Gen manually Started","=
Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, site went down because Gen failed to start =
due to Grid bad voltage // he bypass the Grid and Gen manually Started","la=
ndry.etame@ihstowers.com","1026","27-12-2024 09:17:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0003944569","Behind P=
 T school Yde","","27-12-2024 06:02:31","27-12-2024 05:55:23","27-12-2024 0=
7:34:20","Energy Meter disconnected, Site went down due to no automation//G=
en manually started","Paul BIBOUM","Equipment Repair","Passive","Control Pa=
nel","ATS-AMF Issue","Energy Meter disconnected, Site went down due to no a=
utomation//Gen manually started","ange.kongo@ihstowers.com","429","27-12-20=
24 06:02:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0003944269","Eloumdem=
 stade","","27-12-2024 03:23:41","27-12-2024 03:17:27","27-12-2024 05:15:21=
","Cascaded Incident from TTO3916316","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran until fuel shortage // refueling done","system","297899","27-12-2=
024 03:23:41","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003944266","Sim=
bock MTN","IHS_YND_793","27-12-2024 03:22:56","27-12-2024 03:17:27","27-12-=
2024 05:15:21","Grid outage, site went down because gen ran until fuel shor=
tage // refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Die=
sel Outage","Grid outage, site went down because gen ran until fuel shortag=
e // refueling done","ange.kongo@ihstowers.com","330","27-12-2024 03:22:56"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003944134","T=
singa","","27-12-2024 02:13:16","27-12-2024 02:10:56","27-12-2024 02:33:25"=
,"Grid outage site went down because Gen failed to start poor battery backu=
p // Grid power return","Mboua Thierry","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage site went down because=
 Gen failed to start poor battery backup // Grid power return","rouselle.sc=
houne@ihstowers.com","142","27-12-2024 02:13:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0003944033","E=
vodoula OCM","","27-12-2024 01:32:33","27-12-2024 01:17:19","27-12-2024 09:=
11:42","Site went down because  3/5 slots faulty// He put site on  2/5 slot=
s  (MPR to be replaced)","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","Rectifier","Rectifier Distribution","Site went down because  3/5 slo=
ts faulty// He put site on  2/5 slots  (MPR to be replaced)","rouselle.scho=
une@ihstowers.com","915","27-12-2024 01:32:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0003944019","E=
koumdoum OCM","","27-12-2024 01:25:24","27-12-2024 01:21:19","27-12-2024 08=
:34:45","Grid outage, Site went down because Gen overload (20kva, 300A) //G=
rid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid outage, Site went down because Gen overload (20kva, 300A) =
//Grid return","rouselle.schoune@ihstowers.com","246","27-12-2024 01:25:24"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003943850","S=
ous Prefecture","","27-12-2024 00:50:57","27-12-2024 00:45:50","27-12-2024 =
01:59:40","No power issue on site Ubaie:54,7V; site on Grid. The Tx FME Geo=
rges ( 697461814)) from Huawei is informed","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site Ubaie:54,7V; site on Grid. The Tx FME Georges ( 697461814=
)) from Huawei is informed","rouselle.schoune@ihstowers.com","308","27-12-2=
024 00:50:57","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003943629","NKO=
MEKUI OCM","","27-12-2024 00:02:16","26-12-2024 23:55:01","27-12-2024 00:35=
:41","no power issue on site U=3D54.5  V site on Gen.Site impacted by Mbank=
olo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
no power issue on site U=3D54.5  V site on Gen.Site impacted by Mbankolo Ca=
mtel and not managing by IHS","ange.kongo@ihstowers.com","436","27-12-2024 =
00:02:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_556","NOCINC0003943569","NKOMKANA=
 ELIZA HOTEL","","26-12-2024 23:45:53","26-12-2024 23:40:45","26-12-2024 23=
:54:39","grid aoutage, no space to deploy a MDG// grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid aoutage, no=
 space to deploy a MDG// grid return","ange.kongo@ihstowers.com","309","26-=
12-2024 23:45:53","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0003943487","AFE=
ME NORD","IHS_YND_808","26-12-2024 23:12:55","26-12-2024 22:03:40","26-12-2=
024 23:52:05","site went down because the Cb(65A) of PWC dysjoncted // He r=
eamed he Cb","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Circuit Breaker Issue","site went down because t=
he Cb(65A) of PWC dysjoncted // He reamed he Cb","ange.kongo@ihstowers.com"=
,"4156","26-12-2024 23:12:55","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003943349","ODZ=
A MINKAN EDIBI ASSI","","26-12-2024 22:34:57","26-12-2024 22:24:59","26-12-=
2024 23:01:48","Grid fluctuation site went down becauseGen failed to start =
due Grid bad voltage // he bypass the Grid and Gen manually started","Albra=
n Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation site went down becauseGen failed to start due Gri=
d bad voltage // he bypass the Grid and Gen manually started","ange.kongo@i=
hstowers.com","599","26-12-2024 22:34:57","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0003943329","Mba=
nkolo petit paris","","26-12-2024 22:29:43","26-12-2024 22:03:40","26-12-20=
24 23:52:05","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","site went down because the Cb(65A) of PWC dysjoncted /=
/ He reamed he Cb","ange.kongo@ihstowers.com","288053","26-12-2024 22:29:43=
","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003942656","Lad=
a I Yde","","26-12-2024 21:11:21","26-12-2024 21:02:35","26-12-2024 21:28:4=
4","	Grid fluctuation site went down because Gen and started and stopped du=
e to Grid bad voltage // He bypass the Grid and Gen manually started","Mba =
Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","	Grid fluctuation site went down because Gen and started and s=
topped due to Grid bad voltage // He bypass the Grid and Gen manually start=
ed","ludivine.ngamaleu@ihstowers.com","527","26-12-2024 21:11:21","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0003942598","S=
OA TOWN","","26-12-2024 20:57:06","26-12-2024 20:54:58","26-12-2024 20:56:1=
9","Grid outage, Site went down because Gen overload (13kva, 160A)// Grid r=
eturn","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, Site went down because Gen overload (13kva, 160A)// Gri=
d return","olivier.kwedi@ihstowers.com","129","26-12-2024 20:57:06","Sagemc=
om CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003942580","Mes=
sa Carriere","","26-12-2024 20:53:07","26-12-2024 20:49:02","26-12-2024 22:=
27:44","Grid fluctuation site went down becauseGen failed to start due Grid=
 bad voltage // he bypass the Grid and Gen manually started","Mboua Thierry=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation site went down becauseGen failed to start due Grid bad vo=
ltage // he bypass the Grid and Gen manually started","ludivine.ngamaleu@ih=
stowers.com","245","26-12-2024 20:53:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0003942526","M=
essassi 2","","26-12-2024 20:43:09","26-12-2024 20:37:03","26-12-2024 20:40=
:11","No power issue site on Gen with U=3D54,4V Symphorien(691316854) from =
Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on Ge=
n with U=3D54,4V Symphorien(691316854) from Huawei is informed","olivier.kw=
edi@ihstowers.com","368","26-12-2024 20:43:09","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0003942470","Bri=
quetterie","","26-12-2024 20:34:21","26-12-2024 20:28:15","26-12-2024 20:45=
:46","site went down due to work (Carimo amadou(680 60 17 05) from PRIME af=
rica was working on site (SWAPPED of MTN BAIE=B0)// End of work","","Equipm=
ent Replacement","Passive","Planned Activity","Planned Activity - Passive",=
"site went down due to work (Carimo amadou(680 60 17 05) from PRIME africa =
was working on site (SWAPPED of MTN BAIE=B0)// End of work","ludivine.ngama=
leu@ihstowers.com","367","26-12-2024 20:34:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003942469","M=
elen Ba'aba","","26-12-2024 20:34:09","26-12-2024 20:25:03","26-12-2024 21:=
12:46","Site went down because CB (125A) tripped in DC box who feeds equipm=
ents OCM// CB put back on","Siligap Boris","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Circuit Breaker Issue","Site went down becaus=
e CB (125A) tripped in DC box who feeds equipments OCM// CB put back on","o=
livier.kwedi@ihstowers.com","547","26-12-2024 20:34:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003942435","Nsimalen=
 OCM","","26-12-2024 20:30:20","26-12-2024 20:19:42","26-12-2024 20:23:22",=
"Cascaded Incident from TTO3914207","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because Gen fails t=
o start due to Grid bad voltage, no rcp on site // Grid stabilized","system=
","272659","26-12-2024 20:30:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003942402","N=
kolda","IHS_YND_327","26-12-2024 20:22:48","26-12-2024 20:19:42","26-12-202=
4 20:23:22","site went down because Gen fails to start due to Grid bad volt=
age, no rcp on site // Grid stabilized","Albran Byorel","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","site went down becau=
se Gen fails to start due to Grid bad voltage, no rcp on site // Grid stabi=
lized","olivier.kwedi@ihstowers.com","187","26-12-2024 20:22:48","Sagemcom =
CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003942346","NKO=
MEKUI OCM","","26-12-2024 20:10:34","26-12-2024 20:00:59","26-12-2024 20:10=
:49","no power issue on site U=3D54.5  V site on Gen.Site impacted by Mbank=
olo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
no power issue on site U=3D54.5  V site on Gen.Site impacted by Mbankolo Ca=
mtel and not managing by IHS","ludivine.ngamaleu@ihstowers.com","577","26-1=
2-2024 20:10:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003942203","M=
ontee-Jouvence-II","","26-12-2024 19:43:19","26-12-2024 19:36:53","26-12-20=
24 20:11:56","site went down because pwc overload(12k/230A) // site stabili=
zed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","site went down because pwc overload(12k/230A) // site st=
abilized","olivier.kwedi@ihstowers.com","387","26-12-2024 19:43:19","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003941944","SOA VILL=
AGE","","26-12-2024 18:51:31","26-12-2024 18:44:58","26-12-2024 19:07:21","=
Cascaded Incident from TTO3913662","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuctuation,site went down =
because gen failed to start due grid bad voltage// :He bypassed grid, Gen m=
anually started","system","1220573","26-12-2024 18:51:31","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003941936","SOA=
 TOWN","IHS_YND_323","26-12-2024 18:50:02","26-12-2024 18:40:20","26-12-202=
4 19:07:21","Grid fluctuctuation,site went down because gen failed to start=
 due grid bad voltage// :He bypassed grid, Gen manually started","Siligap B=
oris","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuctuation,site went down because gen failed to start due gri=
d bad voltage// :He bypassed grid, Gen manually started","ludivine.ngamaleu=
@ihstowers.com","1018","26-12-2024 18:50:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003941934","E=
bogo","","26-12-2024 18:49:35","26-12-2024 18:38:28","26-12-2024 18:49:55",=
"Grid fluctuation site went down because Gen failed to start due to Grid ba=
d voltage and poor battery backup // Grid stabilized	","Siligap Boris","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d fluctuation site went down because Gen failed to start due to Grid bad vo=
ltage and poor battery backup // Grid stabilized	","olivier.kwedi@ihstowers=
.com","10528","26-12-2024 18:49:35","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003941880","Bit=
eng","","26-12-2024 18:38:49","26-12-2024 18:32:45","26-12-2024 19:44:25","=
site went down due to Cb(125A) tripped in DC box who feeds equipments MTN /=
/ He reamed Cb(125A), site on grid","Mba Lazare Herve","Equipment Repair","=
Passive","Control Panel","Circuit Breaker Tripped","site went down due to C=
b(125A) tripped in DC box who feeds equipments MTN // He reamed Cb(125A), s=
ite on grid","ludivine.ngamaleu@ihstowers.com","365","26-12-2024 18:38:49",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003941664","E=
bogo","","26-12-2024 18:01:14","26-12-2024 18:00:09","26-12-2024 18:01:59",=
"Grid fluctuation site went down because Gen failed to start due to Grid ba=
d voltage and poor battery backup // Grid stabilized","Siligap Boris","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 fluctuation site went down because Gen failed to start due to Grid bad vol=
tage and poor battery backup // Grid stabilized","olivier.kwedi@ihstowers.c=
om","66","26-12-2024 18:01:14","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0003941600","Lob=
o 2","","26-12-2024 17:46:26","26-12-2024 17:38:21","26-12-2024 18:49:22","=
site went down due to hybride system dysfunction//he reset the gen card & s=
tarted gen manually","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","Hybrid","Hybrid Module","site went down due to hybride system dysfunctio=
n//he reset the gen card & started gen manually","ludivine.ngamaleu@ihstowe=
rs.com","486","26-12-2024 17:46:26","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003941561","Elo=
umdem stade","","26-12-2024 17:38:29","26-12-2024 17:30:10","26-12-2024 18:=
18:00","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage,Gen ran till fuel shortage//Refueling done ","ludi=
vine.ngamaleu@ihstowers.com","275615","26-12-2024 17:38:29","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003941548","Sim=
bock MTN","IHS_YND_793","26-12-2024 17:36:15","26-12-2024 17:30:10","26-12-=
2024 18:18:00","Grid outage,Gen ran till fuel shortage//Refueling done ","F=
anda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,G=
en ran till fuel shortage//Refueling done ","ludivine.ngamaleu@ihstowers.co=
m","365","26-12-2024 17:36:15","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003941230","Nko=
lmvack","","26-12-2024 16:43:50","26-12-2024 16:38:44","26-12-2024 19:55:05=
","grid outage, site went down because gen failed to start due to  battery =
gen FAULTY  // gen manually with external battery","Parker Tchoup","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Generator Battery","grid outage, si=
te went down because gen failed to start due to  battery gen FAULTY  // gen=
 manually with external battery","ludivine.ngamaleu@ihstowers.com","307","2=
6-12-2024 16:43:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003941154","S=
aa","","26-12-2024 16:30:31","26-12-2024 16:15:22","26-12-2024 20:15:58","A=
ctive//No power issue U=3D 54.3V site on Grid The TX FME Gregoire(654547479=
) from Huawei is working on site.","Parker Tchoup","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue U=3D 54.3V site on Grid The TX FME Gregoire(654547479) from Huaw=
ei is working on site.","olivier.kwedi@ihstowers.com","910","26-12-2024 16:=
30:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_797","NOCINC0003941038","Fouda ru=
e des g=E9n=E9raux","","26-12-2024 16:08:41","26-12-2024 15:34:24","26-12-2=
024 16:02:07","Cascaded Incident from TTO3912401","Delor Telezing","Cascade=
 Outage","Passive","Cascade Passive","Cascade Passive","Fuel shortage //  A=
ddded fuel and started DG","system","282405","26-12-2024 16:08:41","Sagemco=
m CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003940193","Mok=
olo Yaounde","","26-12-2024 14:14:35","26-12-2024 14:08:29","26-12-2024 14:=
28:04","Grid outage, no space to deploy MDG// Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spac=
e to deploy MDG// Grid return","ludivine.ngamaleu@ihstowers.com","367","26-=
12-2024 14:14:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003939824","S=
ous Prefecture","","26-12-2024 13:36:24","26-12-2024 13:09:58","26-12-2024 =
13:10:58","No power issue on site Ubaie:54,7V; site on Grid. The Tx FME Geo=
rges ( 697461814)) from Huawei is informed","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site Ubaie:54,7V; site on Grid. The Tx FME Georges ( 697461814=
)) from Huawei is informed","alexandre.kamal@ihstowers.com","1588","26-12-2=
024 13:36:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0003939769","E=
koumdoum OCM","","26-12-2024 13:28:54","26-12-2024 13:19:49","26-12-2024 15=
:46:05","Grid outage, Site went down because Gen overload (20kva, 300A)// G=
rid return","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid outage, Site went down because Gen overload (20kva, 300A)/=
/ Grid return","alexandre.kamal@ihstowers.com","547","26-12-2024 13:28:54",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0003939080","Eloumdem=
 stade","","26-12-2024 11:26:30","26-12-2024 11:18:04","26-12-2024 13:15:32=
","Cascaded Incident from TTO3910467","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because 1/3 rectifi=
er faulty//he changed the faulty rectifier","system","283498","26-12-2024 1=
1:26:30","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003939072","Sim=
bock MTN","IHS_YND_793","26-12-2024 11:25:47","26-12-2024 11:18:04","26-12-=
2024 13:15:32","site went down because 1/3 rectifier faulty//he changed the=
 faulty rectifier","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","site went down because 1/3 rectifier faulty//he changed =
the faulty rectifier","kamga.virgile@ihstowers.com","463","26-12-2024 11:25=
:47","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003938908","Eko=
unou","","26-12-2024 10:51:53","26-12-2024 10:38:34","26-12-2024 11:02:34",=
"Grid outage, site went down before gen start due to poor batteries backup =
// gen start automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor batteries backup // gen start automatically","ka=
mga.virgile@ihstowers.com","800","26-12-2024 10:51:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003938649","M=
essa-Carriere OCM","","26-12-2024 10:21:37","26-12-2024 10:05:31","26-12-20=
24 10:06:31","No power issue on site U=3D52v site on grid Tx fme Mohamadou =
of huawei is informed","","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52v site o=
n grid Tx fme Mohamadou of huawei is informed","alexandre.kamal@ihstowers.c=
om","967","26-12-2024 10:21:37","Sagemcom CMR"
"Closed Complete","Warning","T0772","IHS_YND_207","NOCINC0003938282","ARMP =
Building","","26-12-2024 09:52:02","","","alarm not unproven siye on grid w=
ith U=3D54v ","Mboua Thierry","Warning","Warning","POWER","Warning - Site o=
n Battery","alarm not unproven siye on grid with U=3D54v ","dorothy.djantio=
@ihstowers.com","381","26-12-2024 09:52:02","Sagemcom CMR"
"Closed Complete","Warning","CTR_213","IHS_YND_247","NOCINC0003938227","Oko=
lo","","26-12-2024 09:42:12","","","site on battery due card ge disfunction=
//he reset it and started the gen","Fabrice Pouakam","Warning","Warning","P=
OWER","Warning - Site on Battery","site on battery due card ge disfunction/=
/he reset it and started the gen","dorothy.djantio@ihstowers.com","125","26=
-12-2024 09:42:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003938153","Bastos E=
koudou","","26-12-2024 09:29:00","26-12-2024 09:05:49","26-12-2024 12:11:38=
","Cascaded Incident from TTO3909502","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, site went down due =
to PWC burned caused by short circuit//he balanced the load with another PW=
C on site","system","291266","26-12-2024 09:29:00","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003938148","Lab=
oratoire  Meka","IHS_YND_193","26-12-2024 09:27:14","26-12-2024 09:05:49","=
26-12-2024 12:11:38","Grid outage, site went down due to PWC burned caused =
by short circuit//he balanced the load with another PWC on site","","Fire o=
n Site","Passive","Infrastructure","Fire - Burned","Grid outage, site went =
down due to PWC burned caused by short circuit//he balanced the load with a=
nother PWC on site","kamga.virgile@ihstowers.com","1286","26-12-2024 09:27:=
14","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0003938105","Eko=
umdoum OCM","","26-12-2024 09:16:18","26-12-2024 08:53:42","26-12-2024 10:5=
0:03","grid outage,site went down because Gen overload (20KVA,290 A) // Gri=
d stabilized","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","grid outage,site went down because Gen overload (20KVA,290 A)=
 // Grid stabilized","kamga.virgile@ihstowers.com","1357","26-12-2024 09:16=
:18","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0003937934","Awa=
e Escalier","","26-12-2024 08:43:40","26-12-2024 08:36:32","26-12-2024 09:2=
0:52","Site went down due to all rectifier disfunctionning // reste done an=
d gen started","Albran Byorel","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down due to all rectifier disfunctionning // res=
te done and gen started","kamga.virgile@ihstowers.com","429","26-12-2024 08=
:43:40","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0003937589","Mba=
nkolo petit paris","","26-12-2024 07:26:32","26-12-2024 06:52:19","26-12-20=
24 08:50:27","site went down because gen ran until fuel shortage // refuell=
ing done","Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage",=
"site went down because gen ran until fuel shortage // refuelling done","ka=
mga.virgile@ihstowers.com","2054","26-12-2024 07:26:32","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003937216","NYO=
M FACE MAETUR","","26-12-2024 05:32:46","26-12-2024 05:32:41","26-12-2024 0=
8:04:23","Grid Outage landlord has forbiden to start the Gen Because the No=
ise // Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Emergency Stop","Grid Outage landlord has forbiden to start th=
e Gen Because the Noise // Grid Restored","christian.fonkou@ihstowers.com",=
"6","26-12-2024 05:32:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003937079","Bastos E=
koudou","","26-12-2024 04:54:10","26-12-2024 04:45:25","26-12-2024 08:44:38=
","Cascaded Incident from TTO3908270","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage,no space to deploy a=
 mobil gen//grid return","system","278226","26-12-2024 04:54:10","Sagemcom =
CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003937078","Lab=
oratoire  Meka","IHS_YND_193","26-12-2024 04:53:31","26-12-2024 04:45:25","=
26-12-2024 08:44:38","grid outage,no space to deploy a mobil gen//grid retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid outage,no space to deploy a mobil gen//grid return","christian.fonkou@=
ihstowers.com","487","26-12-2024 04:53:31","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0003937077","Eko=
umdoum OCM","","26-12-2024 04:52:13","26-12-2024 04:48:05","26-12-2024 08:4=
4:05","Grid fluctuation, Site went down due to Gen overload (20KVA,290 A) /=
/ Grid stabilized","Albran Byorel","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid fluctuation, Site went down due to Gen overload (20=
KVA,290 A) // Grid stabilized","christian.fonkou@ihstowers.com","249","26-1=
2-2024 04:52:13","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003936786","Bit=
eng","","26-12-2024 02:06:54","26-12-2024 02:03:46","26-12-2024 03:11:32","=
Site went down because CB(125A) tripped in PWC who feeds equipments MTN// C=
B put back on","Mba Lazare Herve","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","Site went down because CB(125A=
) tripped in PWC who feeds equipments MTN// CB put back on","christian.fonk=
ou@ihstowers.com","189","26-12-2024 02:06:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0003936778","SAA 2","=
","26-12-2024 02:02:01","26-12-2024 01:21:02","26-12-2024 02:30:34","Cascad=
ed Incident from TTO3907909","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage,Site went down because Gen st=
opped with alarm ""high temp""causing by radiator pierced// He added water =
and started Gen manualy (repairment radiator ongoing)","system","268977","2=
6-12-2024 02:02:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003936774","S=
aa","IHS_YND_401, IHS_YND_404","26-12-2024 02:00:20","26-12-2024 01:21:02",=
"26-12-2024 02:30:34","Grid outage,Site went down because Gen stopped with =
alarm ""high temp""causing by radiator pierced// He added water and started=
 Gen manualy (repairment radiator ongoing)","Parker Tchoup","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Radiator Leakage","Grid outage,Site went d=
own because Gen stopped with alarm ""high temp""causing by radiator pierced=
// He added water and started Gen manualy (repairment radiator ongoing)","e=
mmanuel.ghani@ihstowers.com","2359","26-12-2024 02:00:20","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003936766","Tsi=
nga","","26-12-2024 01:53:34","26-12-2024 01:51:26","26-12-2024 02:15:32","=
Grid outage, Site went down before Gen start due to poor backup// Grid rest=
ored","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage, Site went down before Gen start due to =
poor backup// Grid restored","christian.fonkou@ihstowers.com","475","26-12-=
2024 01:53:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003936460","N=
yom OCM","","25-12-2024 23:51:50","25-12-2024 23:46:46","25-12-2024 23:50:1=
9","No power issue site on Gen with U=3D54,4V Symphorien(691316854) from Hu=
awei is informed","Fabrice Pouakam","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on Gen =
with U=3D54,4V Symphorien(691316854) from Huawei is informed","emmanuel.gha=
ni@ihstowers.com","305","25-12-2024 23:51:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0003936455","B=
ondjock","","25-12-2024 23:49:44","25-12-2024 23:47:39","25-12-2024 23:54:4=
5","Grid outage, site went down before gen start due to poor battery backup=
 // Gen start automatically","Fanda Brice","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start automatically","emman=
uel.ghani@ihstowers.com","126","25-12-2024 23:49:44","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0003936336","Jou=
vence Mbenda","","25-12-2024 23:15:25","25-12-2024 23:09:18","26-12-2024 00=
:26:24","Grid Outage, site went down because Gen stopped with ""high temp""=
 alarm// He added water and started Gen manualy","Hyemafo Gildas","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid Outage, site went down because Gen stopped with ""high temp"" ala=
rm// He added water and started Gen manualy","christian.fonkou@ihstowers.co=
m","368","25-12-2024 23:15:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003936240","M=
ontee-Jouvence-II","","25-12-2024 22:56:19","25-12-2024 22:54:16","25-12-20=
24 22:56:05","Site went down due to PWC Overloaded (12K, 230A) // site stab=
ilized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Site went down due to PWC Overloaded (12K, 230A) // s=
ite stabilized","emmanuel.ghani@ihstowers.com","124","25-12-2024 22:56:19",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003936214","Donga","=
","25-12-2024 22:50:31","25-12-2024 22:41:43","25-12-2024 22:45:23","Cascad=
ed Incident from TTO3907200","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active: No power issue, site is on Gen With =
Ubaie=3D54,9V,  Gregoire (654547479) from Huawei is informed Site impacted =
by Mbandjock CTR_030 which is not managed by IHS","system","264063","25-12-=
2024 22:50:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003936209","Nguila",=
"","25-12-2024 22:50:30","25-12-2024 22:41:43","25-12-2024 22:45:23","Casca=
ded Incident from TTO3907200","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active: No power issue, site is on Gen With=
 Ubaie=3D54,9V,  Gregoire (654547479) from Huawei is informed Site impacted=
 by Mbandjock CTR_030 which is not managed by IHS","system","264062","25-12=
-2024 22:50:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0003936167","D=
ong","IHS_YND_433, IHS_YND_592, IHS_YND_431, IHS_YND_443, IHS_YND_432, IHS_=
YND_434, IHS_YND_402, IHS_YND_442","25-12-2024 22:46:47","25-12-2024 22:41:=
43","25-12-2024 23:06:23","Active: No power issue, site is on Gen With Ubai=
e=3D54,9V,  Gregoire (654547479) from Huawei is informed Site impacted by M=
bandjock CTR_030 which is not managed by IHS","Parker Tchoup","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive: No power issue, site is on Gen With Ubaie=3D54,9V,  Gregoire (654547=
479) from Huawei is informed Site impacted by Mbandjock CTR_030 which is no=
t managed by IHS","emmanuel.ghani@ihstowers.com","305","25-12-2024 22:46:47=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003936141","Bastos E=
koudou","","25-12-2024 22:43:27","25-12-2024 22:32:54","25-12-2024 23:23:17=
","Cascaded Incident from TTO3907170","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid Outage No Space to deploy a=
 MDG//Grid Restored","system","279056","25-12-2024 22:43:27","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003936138","Lab=
oratoire  Meka","IHS_YND_193","25-12-2024 22:42:00","25-12-2024 22:32:54","=
25-12-2024 23:23:17","Grid Outage No Space to deploy a MDG//Grid Restored",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 Outage No Space to deploy a MDG//Grid Restored","christian.fonkou@ihstower=
s.com","547","25-12-2024 22:42:00","Sagemcom CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0003936096","Ngo=
ulmekong-Nord","","25-12-2024 22:29:53","25-12-2024 22:23:47","25-12-2024 2=
3:05:54","Grid outage site went down because Gen stopped with alarm under f=
requency (unprouven alarm) // He reset the Gen card and Gen manually starte=
d","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid outage site went down because Gen stopped with alarm under fre=
quency (unprouven alarm) // He reset the Gen card and Gen manually started"=
,"christian.fonkou@ihstowers.com","1108","25-12-2024 22:29:53","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_740","NOCINC0003935357","Santa Ba=
rbara Gottam","","25-12-2024 21:20:57","25-12-2024 17:38:33","25-12-2024 19=
:30:30","site went down because CB(80A) tripped in Dcbox who feeds equipmen=
ts MTN //He replaced with anoter CB(125A)","Delor Telezing","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site=
 went down because CB(80A) tripped in Dcbox who feeds equipments MTN //He r=
eplaced with anoter CB(125A)","ange.kongo@ihstowers.com","13345","25-12-202=
4 21:20:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0003935349","Ekoumdou=
m OCM","","25-12-2024 21:18:56","25-12-2024 20:46:46","25-12-2024 22:19:14"=
,"Grid outage, site went down because Gen overload (20 KVA;290 A)// Load st=
abilized","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid outage, site went down because Gen overload (20 KVA;290 A)//=
 Load stabilized","ange.kongo@ihstowers.com","1931","25-12-2024 21:18:56","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0003935093","M=
essassi 2","","25-12-2024 20:55:58","25-12-2024 20:54:47","25-12-2024 23:40=
:23","Active// No power issue, Site on Grid , The TX FME Synphorien/6913168=
54/ From Huawei is informed and up at 08:56 PM","Fabrice Pouakam","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power issue, Site on Grid , The TX FME Synphorien/691316854/=
 From Huawei is informed and up at 08:56 PM","rouselle.schoune@ihstowers.co=
m","73","25-12-2024 20:55:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0003935045","S=
OA TOWN","","25-12-2024 20:50:09","25-12-2024 20:46:54","25-12-2024 21:20:4=
0","Grid fluctuation, site went down because gen start and stopped due to g=
rid bad voltage // he bypass grid and manually start the gen","Siligap Bori=
s","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, site went down because gen start and stopped due to gri=
d bad voltage // he bypass grid and manually start the gen","rouselle.schou=
ne@ihstowers.com","196","25-12-2024 20:50:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0003934819","A=
wae-Yde","","25-12-2024 20:19:26","25-12-2024 19:40:13","25-12-2024 20:42:1=
3","Site went down because rectifier of CB 32A) disjuncted //he reamed  CB(=
investigation ongoing)","Albran Byorel","Equipment Repair","Passive","Recti=
fier","Rectifier - Circuit Breaker","Site went down because rectifier of CB=
 32A) disjuncted //he reamed  CB(investigation ongoing)","rouselle.schoune@=
ihstowers.com","2353","25-12-2024 20:19:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003934771","C=
ite-Verte","","25-12-2024 20:12:57","25-12-2024 20:05:42","25-12-2024 23:00=
:49","No power issue on site U=3D53,3 V  site on Grid The FME TX Brice Stag=
ue of huawei is informed, Notice that we have disjunction in OCM equipment"=
,"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site U=3D53,3 V  site on Grid The FME TX =
Brice Stague of huawei is informed, Notice that we have disjunction in OCM =
equipment","rouselle.schoune@ihstowers.com","436","25-12-2024 20:12:57","Sa=
gemcom CMR"
"Cancelled","Warning","CTR_374","IHS_YND_173","NOCINC0003934624","AWAE OCM"=
,"","25-12-2024 19:50:34","","","","Mba Lazare Herve","","","","","","rouse=
lle.schoune@ihstowers.com","784","25-12-2024 19:50:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_795","NOCINC0003934598","Lada I Y=
de","","25-12-2024 19:46:37","25-12-2024 16:18:15","25-12-2024 18:40:30","G=
rid fluctuation, site went down because Gen fails to start due to Grid bad =
voltage // he bypass Grid and manually start the Gen","Mba Lazare Herve","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d fluctuation, site went down because Gen fails to start due to Grid bad vo=
ltage // he bypass Grid and manually start the Gen","ange.kongo@ihstowers.c=
om","12503","25-12-2024 19:46:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0003934597","Carrefou=
rt Nkomo","","25-12-2024 19:46:21","25-12-2024 19:37:19","25-12-2024 19:47:=
50","Cascaded Incident from TTO3905409","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before Gen start due to poor battery backup // Gen start automatically","s=
ystem","282194","25-12-2024 19:46:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0003934583","N=
komo","IHS_YND_174","25-12-2024 19:45:24","25-12-2024 19:37:19","25-12-2024=
 19:47:50","Grid outage, site went down before Gen start due to poor batter=
y backup // Gen start automatically","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site =
went down before Gen start due to poor battery backup // Gen start automati=
cally","rouselle.schoune@ihstowers.com","486","25-12-2024 19:45:24","Sagemc=
om CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003934524","NKO=
MEKUI OCM","","25-12-2024 19:35:52","25-12-2024 19:27:44","25-12-2024 19:29=
:04","No power issue on site U=3D54.5  V site on Gen.  Site impacted by Mba=
nkolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site U=3D54.5  V site on Gen.  Site impacted by Mbankol=
o Camtel and not managing by IHS","ange.kongo@ihstowers.com","489","25-12-2=
024 19:35:52","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003934519","ODZ=
A CITE MBIA","","25-12-2024 19:35:00","25-12-2024 19:27:46","25-12-2024 20:=
58:25","Grid OUTAGE, site went down because gen fails to start due to ATS d=
isfunctionning // Gen manually start","Albran Byorel","Equipment Repair","P=
assive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down becaus=
e gen fails to start due to ATS disfunctionning // Gen manually start","ang=
e.kongo@ihstowers.com","435","25-12-2024 19:35:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_802","NOCINC0003934509","NYOM FAC=
E MAETUR","","25-12-2024 19:32:09","25-12-2024 17:32:59","25-12-2024 22:02:=
13","Grid Outage landlord has forbiden to start the Gen Because the Noise//=
 Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen =
Because the Noise// Grid Restored","ange.kongo@ihstowers.com","7151","25-12=
-2024 19:32:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003934320","Bastos E=
koudou","","25-12-2024 18:58:50","25-12-2024 18:54:51","25-12-2024 19:26:29=
","Cascaded Incident from TTO3905097","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, no space to deploy =
a MDG//  grid return","system","277772","25-12-2024 18:58:50","Sagemcom CMR=
"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003934319","Lab=
oratoire  Meka","IHS_YND_193","25-12-2024 18:58:07","25-12-2024 18:54:51","=
25-12-2024 19:26:29","Grid outage, no space to deploy a MDG//  grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d outage, no space to deploy a MDG//  grid return","ange.kongo@ihstowers.co=
m","197","25-12-2024 18:58:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003934273","E=
kounou","","25-12-2024 18:46:28","25-12-2024 18:43:21","25-12-2024 18:53:56=
","Grid outage, Site went down before Gen start due to poor backup// Gen st=
arted automatically","Albran Byorel","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor backup// Gen started automatically","rouselle.schoune@i=
hstowers.com","188","25-12-2024 18:46:28","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003934247","Mvo=
g-Betsi","","25-12-2024 18:40:52","25-12-2024 18:33:45","25-12-2024 18:51:5=
4","Grid fluctuation, site went down because Gen fails to start due to Grid=
 bad voltage // he bypass Grid and manually start the Gen","Hyemafo Gildas"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid fluctuation, site went down because Gen fails to start due to Grid bad=
 voltage // he bypass Grid and manually start the Gen","ange.kongo@ihstower=
s.com","428","25-12-2024 18:40:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003934195","Bastos E=
koudou","","25-12-2024 18:32:00","25-12-2024 18:13:15","25-12-2024 18:27:03=
","Cascaded Incident from TTO3904943","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,no space to deploy a=
 mobil gen,//Grid power ","system","265871","25-12-2024 18:32:00","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003934193","Lab=
oratoire  Meka","IHS_YND_193","25-12-2024 18:31:23","25-12-2024 18:13:15","=
25-12-2024 18:27:03","Grid outage,no space to deploy a mobil gen,//Grid pow=
er ","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid outage,no space to deploy a mobil gen,//Grid power ","ange.kongo@ihst=
owers.com","1089","25-12-2024 18:31:23","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0003933641","Mon=
tee-Jouvence-II","","25-12-2024 17:04:25","25-12-2024 16:53:06","25-12-2024=
 17:55:55","Site went down because CB (63A) tripped in DC box who feeds equ=
ipments  MTN // CB put back on","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down =
because CB (63A) tripped in DC box who feeds equipments  MTN // CB put back=
 on","ange.kongo@ihstowers.com","679","25-12-2024 17:04:25","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0003933607","SIM=
BOCK BONAMBAPE","","25-12-2024 16:58:26","25-12-2024 16:53:17","25-12-2024 =
17:46:08","Grid fluctuation, site went down due to lack of 01 phase on site=
 // he did a bridge with a good phase","Hyemafo Gildas","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, si=
te went down due to lack of 01 phase on site // he did a bridge with a good=
 phase","ange.kongo@ihstowers.com","310","25-12-2024 16:58:26","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003933597","C=
omplexe-BEAC","","25-12-2024 16:56:52","25-12-2024 16:55:33","25-12-2024 17=
:58:07","Site went down due to CB Batterry Backup (100A) dysjunted in the P=
WC because Grid Bad Voltage//He reamed the CB Batterry Backup and Site is o=
n Gen ","Albran Byorel","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Circuit Breaker Issue","Site went down due to CB Batterry Backup=
 (100A) dysjunted in the PWC because Grid Bad Voltage//He reamed the CB Bat=
terry Backup and Site is on Gen ","rouselle.schoune@ihstowers.com","79","25=
-12-2024 16:56:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003933353","MVAN SAC=
EL","","25-12-2024 16:19:50","25-12-2024 16:16:56","25-12-2024 17:55:13","C=
ascaded Incident from TTO3903977","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage ,site went down because =
Gen start and Stopped due to Gen overload(20 KVa ,290 A)//Grid power return=
","system","1229359","25-12-2024 16:19:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003933344","M=
VAN","IHS_YND_510","25-12-2024 16:19:01","25-12-2024 16:16:56","25-12-2024 =
19:25:51","Grid outage ,site went down because Gen start and Stopped due to=
 Gen overload(20 KVa ,290 A)//Grid power return","MINKA NICOLAS","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went dow=
n because Gen start and Stopped due to Gen overload(20 KVa ,290 A)//Grid po=
wer return","rouselle.schoune@ihstowers.com","126","25-12-2024 16:19:01","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003933252","S=
ous Prefecture","","25-12-2024 16:02:50","25-12-2024 15:38:43","25-12-2024 =
16:30:05","No power issue on site Ubaie:54,7V;  site on Grid.  The Tx FME G=
eorges ( 697461814)) from Huawei is informed","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site Ubaie:54,7V;  site on Grid.  The Tx FME Georges ( 69746=
1814)) from Huawei is informed","rouselle.schoune@ihstowers.com","1448","25=
-12-2024 16:02:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003933092","Bastos E=
koudou","","25-12-2024 15:40:20","25-12-2024 15:27:15","25-12-2024 15:51:49=
","Cascaded Incident from TTO3903690","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,no space to deploy a=
 mobil gen//grid return","system","275741","25-12-2024 15:40:20","Sagemcom =
CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003933086","Lab=
oratoire  Meka","IHS_YND_193","25-12-2024 15:39:30","25-12-2024 15:27:15","=
25-12-2024 15:51:49","Grid outage,no space to deploy a mobil gen//grid retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage,no space to deploy a mobil gen//grid return","ange.kongo@ihstow=
ers.com","736","25-12-2024 15:39:30","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003932896","Sim=
bock MTN","","25-12-2024 15:04:34","25-12-2024 14:53:17","25-12-2024 17:03:=
47","Site went down because 01/03 rectifier hanging//He reset rectifier ,Si=
te  on Gen ","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down because 01/03 rectifier hanging//He reset recti=
fier ,Site  on Gen ","ange.kongo@ihstowers.com","678","25-12-2024 15:04:34"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003932875","Elo=
umdem stade","","25-12-2024 15:00:38","25-12-2024 14:53:26","25-12-2024 23:=
59:27","Active//No power issue site on Grid with U=3D56.3V Georges(69746181=
4)from Huawei is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue=
 site on Grid with U=3D56.3V Georges(697461814)from Huawei is informed","an=
ge.kongo@ihstowers.com","433","25-12-2024 15:00:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0003932840","E=
koumdoum OCM","","25-12-2024 14:55:21","25-12-2024 14:51:17","25-12-2024 16=
:09:38","Grid outage,site went down because Gen start and stopped due to Ge=
n overload (20KVA,290 A)//Grid power return","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage,site went down bec=
ause Gen start and stopped due to Gen overload (20KVA,290 A)//Grid power re=
turn","rouselle.schoune@ihstowers.com","245","25-12-2024 14:55:21","Sagemco=
m CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0003932724","Bon=
djock","","25-12-2024 14:37:39","25-12-2024 14:28:34","25-12-2024 14:54:08"=
,"Grid outage, site went down before gen started due to poor battery backup=
// Gen started automatically","Fanda Brice","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen started due to poor battery backup// Gen started automatically","a=
nge.kongo@ihstowers.com","546","25-12-2024 14:37:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003932699","M=
endong vallee","","25-12-2024 14:34:05","25-12-2024 14:24:59","25-12-2024 1=
5:11:33","Grid outage, Site went down because Gen overload (20Kva, 300A) an=
d stopped due to High Temp// He reduiced the load, added water and started =
Gen manualy","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, Site went down because Gen overload (20Kva, 300A) a=
nd stopped due to High Temp// He reduiced the load, added water and started=
 Gen manualy","rouselle.schoune@ihstowers.com","547","25-12-2024 14:34:05",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003932674","N=
kolo II New","","25-12-2024 14:30:04","25-12-2024 13:28:13","25-12-2024 13:=
33:05","Active, no power issue site on Grid with U=3D53.2V The FME Tx  Lion=
el Steve /655184876/ From huawei is informed","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active, no power issue site on Grid with U=3D53.2V The FME Tx  Lionel Ste=
ve /655184876/ From huawei is informed","olivier.kwedi@ihstowers.com","3712=
","25-12-2024 14:30:04","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003932503","Eko=
unou","","25-12-2024 13:58:51","25-12-2024 13:52:47","25-12-2024 14:00:02",=
"Grid outage site went down because Gen failed to start poor battery backup=
 // Grid power return","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage site went down because =
Gen failed to start poor battery backup // Grid power return","dorothy.djan=
tio@ihstowers.com","365","25-12-2024 13:58:51","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0003932499","Sap=
eur Mimboman","","25-12-2024 13:57:43","25-12-2024 13:50:23","25-12-2024 14=
:03:25","Grid outage, Site went down before Gen start due to poor backup// =
Grid power return","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup// Grid power return","dorothy.djantio@ihstowers=
.com","552","25-12-2024 13:57:43","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003932493","Nko=
londom","","25-12-2024 13:56:33","25-12-2024 13:44:55","25-12-2024 15:04:45=
","Grid Outage Site went down due  ATS dysfunctionning // Grid Restored (de=
ep investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","ATS-AMF Issue","Grid Outage Site went down due  ATS dysfunc=
tionning // Grid Restored (deep investigation ongoing)","dorothy.djantio@ih=
stowers.com","790","25-12-2024 13:56:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003932488","A=
wae Escalier","","25-12-2024 13:54:44","25-12-2024 13:27:37","25-12-2024 17=
:04:56","Site went down because  TGBT  Burned  and Grid contactor faulty //=
he bypassed it ,site is on Grid","Albran Byorel","Fire on Site","Passive","=
Infrastructure","Fire - Burned","Site went down because  TGBT  Burned  and =
Grid contactor faulty //he bypassed it ,site is on Grid","olivier.kwedi@ihs=
towers.com","1628","25-12-2024 13:54:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003932478","A=
wae Ewonkan","","25-12-2024 13:52:23","25-12-2024 13:26:34","25-12-2024 13:=
56:15","please cascaded this ticket behind Awae Yde","Albran Byorel","Casca=
de Outage","Passive","Cascade Passive","Cascade Passive","Grid outage, site=
 went down because gen start and stoppen with Alarm ""Low oil pressure"" //=
He added oil and manually start the gen","olivier.kwedi@ihstowers.com","290=
226","25-12-2024 13:52:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0003932434","A=
wae-Yde","IHS_YND_535","25-12-2024 13:47:40","25-12-2024 13:26:34","25-12-2=
024 13:56:15","Grid outage, site went down because gen start and stoppen wi=
th Alarm ""Low oil pressure"" //He added oil and manually start the gen","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Press=
ure","Grid outage, site went down because gen start and stoppen with Alarm =
""Low oil pressure"" //He added oil and manually start the gen","olivier.kw=
edi@ihstowers.com","1267","25-12-2024 13:47:40","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003932414","San=
ta Barbara Gottam","","25-12-2024 13:43:57","25-12-2024 13:37:49","25-12-20=
24 15:53:22","Grid outage, site went down before gen start due to poor batt=
ery backup // Gen manually started","Delor Telezing","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down before gen start due to poor battery backup // Gen manually started"=
,"dorothy.djantio@ihstowers.com","369","25-12-2024 13:43:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003932390","E=
ssomba","","25-12-2024 13:36:13","25-12-2024 13:19:07","25-12-2024 16:31:49=
","Active: No power issue, site is on Grid with Ubaie=3D52.8V,   The fme tx=
 George //697461814//from Huawei is informed. Notice Dysjunction at the BTS=
 OCM","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active: No power issue, site is on Gri=
d with Ubaie=3D52.8V,=20

The fme tx George //697461814//from Huawei is informed. Notice Dysjunction =
at the BTS OCM
","olivier.kwedi@ihstowers.com","1027","25-12-2024 13:36:13","Sagemcom CMR"
"Closed Complete","Warning","T0319","IHS_YND_278","NOCINC0003932382","Nkolf=
oulou 2","","25-12-2024 13:35:18","","","site on alarm due to grid outage//=
gen started","Siligap Boris","Warning","Warning","POWER","Warning - Site on=
 Battery","site on alarm due to grid outage//gen started","ludivine.ngamale=
u@ihstowers.com","3","25-12-2024 13:35:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_512","NOCINC0003932375","Mimboman=
-Ecole","","25-12-2024 13:34:40","25-12-2024 13:12:26","25-12-2024 13:50:53=
","Cascaded Incident from TTO3902824","Mba Lazare Herve","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
ecause failed to start due PWC ZTE disfunction// He reset PWC and started G=
en manualy","system","291094","25-12-2024 13:34:40","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0003932368","Nko=
lbong","","25-12-2024 13:33:15","25-12-2024 13:25:57","25-12-2024 14:01:04"=
,"Grid outage, site went down because Gen failed to start due to dysfunctio=
ning of Gen Card // Grid Restored","Delor Telezing","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down becaus=
e Gen failed to start due to dysfunctioning of Gen Card // Grid Restored","=
dorothy.djantio@ihstowers.com","1209","25-12-2024 13:33:15","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003932363","Nko=
abang2","","25-12-2024 13:32:01","25-12-2024 13:24:56","25-12-2024 14:29:52=
"," Grid otage ,site went down because Gen started and stopped due to Gen o=
verload(22 kva;315 A)//he recuced  load","Mba Lazare Herve","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload"," Grid otage ,site went down bec=
ause Gen started and stopped due to Gen overload(22 kva;315 A)//he recuced =
 load","dorothy.djantio@ihstowers.com","1092","25-12-2024 13:32:01","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003932357","S=
tade-Abega","","25-12-2024 13:30:13","25-12-2024 13:05:06","25-12-2024 13:5=
5:55","Grid outage, site went down due to dysfunctionning of the PWC ZTE //=
  HE reset it and Gen manually started","Mba Lazare Herve","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site w=
ent down due to dysfunctionning of the PWC ZTE //  HE reset it and Gen manu=
ally started","olivier.kwedi@ihstowers.com","1508","25-12-2024 13:30:13","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003932349","O=
mnisport-Rail","","25-12-2024 13:28:21","25-12-2024 13:00:59","25-12-2024 1=
3:05:58","no power issue on site ,site on Grid with Ubaie =3D50.6 V The FME=
 TX Armand Nguesta (699949553) From Huawei is informed, ","Delor Telezing",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","no power issue on site ,site on Grid with Ubaie =3D50.6 V The F=
ME TX Armand Nguesta (699949553) From Huawei is informed, ","olivier.kwedi@=
ihstowers.com","1643","25-12-2024 13:28:21","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003932335","Bit=
oto","","25-12-2024 13:26:19","25-12-2024 13:23:15","25-12-2024 13:55:08","=
Grid outage, Site went down to due to PWC ""ZTE' dysfunction// he reset it =
and started Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectifier=
","Rectifier Module Overloaded","Grid outage, Site went down to due to PWC =
""ZTE' dysfunction// he reset it and started Gen","dorothy.djantio@ihstower=
s.com","1005","25-12-2024 13:26:19","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003932328","MAN=
GUIERS CHAPELLE","","25-12-2024 13:24:08","25-12-2024 13:00:10","25-12-2024=
 14:06:42","	Grid outage, site went down before Gen start due to poor batte=
ry backup // Gen started rmanually","Fabrice Pouakam","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","	Grid outage, site w=
ent down before Gen start due to poor battery backup // Gen started rmanual=
ly","dorothy.djantio@ihstowers.com","1569","25-12-2024 13:24:08","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003932323","C=
rf-Nsam","","25-12-2024 13:23:40","25-12-2024 12:57:31","25-12-2024 13:25:1=
6","Site went down Because The Slot off Rectifier is overload//he Normalize=
d it and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passive","Rec=
tifier","Rectifier Distribution","Site went down Because The Slot off Recti=
fier is overload//he Normalized it and Site is on Grid","olivier.kwedi@ihst=
owers.com","1571","25-12-2024 13:23:40","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003932322","MIM=
BOMAN LIBERTE","","25-12-2024 13:23:31","25-12-2024 13:06:27","25-12-2024 1=
4:24:34","Grid outage, Site went down because Main Gen faulty// He deployed=
 MDG of 20Kva","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage, Site went down because Main Gen faul=
ty// He deployed MDG of 20Kva","dorothy.djantio@ihstowers.com","1025","25-1=
2-2024 13:23:31","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003932320","Mim=
boman3","IHS_YND_512","25-12-2024 13:22:25","25-12-2024 13:12:26","25-12-20=
24 13:54:16","Grid outage, Site went down because failed to start due PWC Z=
TE disfunction// He reset PWC and started Gen manualy","Mba Lazare Herve","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage, Site went down because failed to start due PWC ZTE disfunction// H=
e reset PWC and started Gen manualy","dorothy.djantio@ihstowers.com","1269"=
,"25-12-2024 13:22:25","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003932289","AWA=
E OCM","","25-12-2024 13:18:32","25-12-2024 12:57:20","25-12-2024 13:55:49"=
,"grid outage, Site went down to due to PWC ""ZTE' dysfunction// he reset i=
t and started Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","grid outage, Site went down to due to PW=
C ""ZTE' dysfunction// he reset it and started Gen","dorothy.djantio@ihstow=
ers.com","1333","25-12-2024 13:18:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003932285","S=
atcom","","25-12-2024 13:17:30","25-12-2024 12:57:21","25-12-2024 13:07:21"=
,"Active//No power issue on site Ubaie=3D53,2V site on Grid The tx fme Arma=
nd nguetsa(691144412) is informed","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie=3D53,2V site on Grid The tx fme Armand nguetsa(69=
1144412) is informed","olivier.kwedi@ihstowers.com","1210","25-12-2024 13:1=
7:30","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0003932284","Mel=
en Ba'aba","","25-12-2024 13:17:24","25-12-2024 13:01:35","25-12-2024 13:45=
:28","Grid Outage site went down due to Gen Card Dysfuntionning //He reset =
the Gen Card and Manually Started the Gen ","Siligap Boris","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage site went down=
 due to Gen Card Dysfuntionning //He reset the Gen Card and Manually Starte=
d the Gen ","dorothy.djantio@ihstowers.com","950","25-12-2024 13:17:24","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003932271","Ebo=
go","","25-12-2024 13:15:27","25-12-2024 12:57:50","25-12-2024 13:50:44","G=
rid outage, Site went down before Gen start due to poor backup// Gen start =
manually","Siligap Boris","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage, Site went down before Gen start due=
 to poor backup// Gen start manually","dorothy.djantio@ihstowers.com","1451=
","25-12-2024 13:15:27","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003932229","HOP=
ITAL GENERAL RAIL YDE","","25-12-2024 13:06:23","25-12-2024 13:00:18","25-1=
2-2024 14:29:38"," Grid outage site went down because Gen failed to start d=
ue to Gen contactor faulty //Grid power return","Delor Telezing","Equipment=
 Repair","Passive","Control Panel","ATS-AMF Issue"," Grid outage site went =
down because Gen failed to start due to Gen contactor faulty //Grid power r=
eturn","dorothy.djantio@ihstowers.com","366","25-12-2024 13:06:23","Sagemco=
m CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003932223","Ema=
na","","25-12-2024 13:05:42","25-12-2024 12:58:28","25-12-2024 13:10:11","G=
rid outage, site went down before Gen start due to poor battery backup // G=
en start automatically","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re Gen start due to poor battery backup // Gen start automatically","doroth=
y.djantio@ihstowers.com","435","25-12-2024 13:05:42","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0003932062","NKO=
MKANA ELIZA HOTEL","","25-12-2024 12:27:01","25-12-2024 12:25:53","26-12-20=
24 09:18:40","Grid outage, no space to deploy MDG // Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
no space to deploy MDG // Grid return","dorothy.djantio@ihstowers.com","68"=
,"25-12-2024 12:27:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003932051","Nkolbiss=
on usines des eaux 2","","25-12-2024 12:24:00","25-12-2024 12:18:49","25-12=
-2024 12:25:50","Cascaded Incident from TTO3902416","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","GRID OU=
TAGE, site went down before gen start due to poor battery backup // gen sta=
rt automatically","system","265524","25-12-2024 12:24:00","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003932048","Nko=
lbisson","IHS_YND_763","25-12-2024 12:22:59","25-12-2024 12:18:49","25-12-2=
024 12:25:50","GRID OUTAGE, site went down before gen start due to poor bat=
tery backup // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipme=
nt Repair","Passive","Control Panel","Power Cabinet - Battery Low","GRID OU=
TAGE, site went down before gen start due to poor battery backup // gen sta=
rt automatically","dorothy.djantio@ihstowers.com","252","25-12-2024 12:22:5=
9","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003931902","Ole=
mbe MTN","","25-12-2024 11:35:41","25-12-2024 11:17:35","25-12-2024 12:04:5=
6","grid outage, site went down because gen failed to start due to gen cont=
actor not excited // He excited gen contactor and gen manually started","Fa=
brice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contact=
or","grid outage, site went down because gen failed to start due to gen con=
tactor not excited // He excited gen contactor and gen manually started","d=
orothy.djantio@ihstowers.com","1087","25-12-2024 11:35:41","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0003931699","Jou=
vence Mbenda","","25-12-2024 11:02:12","25-12-2024 10:58:04","25-12-2024 12=
:36:04","Grid Outage, site went down because Gen stopped with ""high temp""=
 alarm// He added water and started Gen manualy","Hyemafo Gildas","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid Outage, site went down because Gen stopped with ""high temp"" ala=
rm// He added water and started Gen manualy","dorothy.djantio@ihstowers.com=
","249","25-12-2024 11:02:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003931576","N=
komkana","","25-12-2024 10:39:58","25-12-2024 10:37:52","26-12-2024 10:16:0=
6","Grid outage, no space to deploy MDG // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage, no space t=
o deploy MDG // Grid return","olivier.kwedi@ihstowers.com","127","25-12-202=
4 10:39:58","Sagemcom CMR"
"Closed Complete","Warning","T0197","IHS_YND_263","NOCINC0003931552","Mendo=
ng Plateau","","25-12-2024 10:36:24","","","site on alarm due to grid outag=
e//gen started","Hyemafo Gildas","Warning","Warning","POWER","Warning - Sit=
e on Battery","site on alarm due to grid outage//gen started","ludivine.nga=
maleu@ihstowers.com","2","25-12-2024 10:36:24","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003931473","ODZ=
A CITE MBIA","","25-12-2024 10:19:06","25-12-2024 10:12:01","25-12-2024 11:=
53:29","Gen stopped and grid return, site went down because gen failed to s=
tart due to dysfunctionning of ATS // he bypassed gen and put on site on gr=
id","Albran Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF I=
ssue","Gen stopped and grid return, site went down because gen failed to st=
art due to dysfunctionning of ATS // he bypassed gen and put on site on gri=
d","dorothy.djantio@ihstowers.com","426","25-12-2024 10:19:06","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003931393","M=
essa-Carriere OCM","","25-12-2024 09:54:57","25-12-2024 09:40:37","25-12-20=
24 11:20:24","No power issue on site U=3D52v site on grid Tx fme Mohamadou =
of huawei is informed","","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52v site o=
n grid Tx fme Mohamadou of huawei is informed","olivier.kwedi@ihstowers.com=
","861","25-12-2024 09:54:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_512","NOCINC0003931387","Mimboman=
-Ecole","","25-12-2024 09:53:51","25-12-2024 09:35:34","25-12-2024 09:54:34=
","Cascaded Incident from TTO3901660","Mba Lazare Herve","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down b=
ecause failed to start due PWC ZTE disfunction// He reset PWC and started G=
en manualy","system","268152","25-12-2024 09:53:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003931370","B=
iteng-Maetur","","25-12-2024 09:46:42","25-12-2024 09:24:37","25-12-2024 09=
:54:37","grid outage,gen stopped with alarm low oil pressure//grid return b=
ut the site remaind down after power reset done and power issue resolved si=
nce 09:54 Tx fme Lionel steeve","Mba Lazare Herve","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Low Oil Pressure","grid outage,gen stopped with ala=
rm low oil pressure//grid return but the site remaind down after power rese=
t done and power issue resolved since 09:54 Tx fme Lionel steeve 655184876 =
of huawei is informed","olivier.kwedi@ihstowers.com","1327","25-12-2024 09:=
46:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003931364","Messassi=
 okolo","","25-12-2024 09:45:41","25-12-2024 09:23:03","25-12-2024 10:27:09=
","Cascaded Incident from TTO3901628","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, site went down be=
cause gen failed to start due to dysfunctioning of gen card // he reset the=
 card and started the gen","system","268893","25-12-2024 09:45:41","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003931362","EMANA BI=
LICK CITY","","25-12-2024 09:45:41","25-12-2024 09:23:03","25-12-2024 10:27=
:09","Cascaded Incident from TTO3901628","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid outage, site went down=
 because gen failed to start due to dysfunctioning of gen card // he reset =
the card and started the gen","system","268892","25-12-2024 09:45:41","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003931363","Emana Ly=
cee","","25-12-2024 09:45:41","25-12-2024 09:23:03","25-12-2024 10:27:09","=
Cascaded Incident from TTO3901628","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site went down becau=
se gen failed to start due to dysfunctioning of gen card // he reset the ca=
rd and started the gen","system","268892","25-12-2024 09:45:41","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003931365","Emana ly=
cee 2","","25-12-2024 09:45:41","25-12-2024 09:23:03","25-12-2024 10:27:09"=
,"Cascaded Incident from TTO3901628","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down bec=
ause gen failed to start due to dysfunctioning of gen card // he reset the =
card and started the gen","system","268893","25-12-2024 09:45:41","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003931361","Mballa 4=
","","25-12-2024 09:45:40","25-12-2024 09:23:03","25-12-2024 10:27:09","Cas=
caded Incident from TTO3901628","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, site went down because g=
en failed to start due to dysfunctioning of gen card // he reset the card a=
nd started the gen","system","268891","25-12-2024 09:45:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003931358","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","25=
-12-2024 09:44:10","25-12-2024 09:23:03","25-12-2024 10:27:09","grid outage=
, site went down because gen failed to start due to dysfunctioning of gen c=
ard // he reset the card and started the gen","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage, site went=
 down because gen failed to start due to dysfunctioning of gen card // he r=
eset the card and started the gen","olivier.kwedi@ihstowers.com","1268","25=
-12-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0003931356","Ole=
mbe","","25-12-2024 09:43:52","25-12-2024 09:33:47","25-12-2024 09:59:47","=
Grid outage, site went down because gen failed to start due to gen contacto=
r not excited // He excited gen contactor and gen manually started","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor",=
"grid outage, site went down because gen failed to start due to gen contact=
or not excited // He excited gen contactor and gen manually started","dorot=
hy.djantio@ihstowers.com","1028","25-12-2024 09:43:52","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003931351","Mim=
boman3","IHS_YND_512","25-12-2024 09:42:13","25-12-2024 09:35:09","25-12-20=
24 10:03:49","Grid outage, Site went down because failed to start due PWC Z=
TE disfunction// He reset PWC and started Gen manualy","Mba Lazare Herve","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid=
 outage, Site went down because failed to start due PWC ZTE disfunction// H=
e reset PWC and started Gen manualy","dorothy.djantio@ihstowers.com","425",=
"25-12-2024 09:42:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003931320","M=
ontee-Des-Soeurs","","25-12-2024 09:37:14","25-12-2024 09:21:08","25-12-202=
4 11:08:08","Active// No power Issue Site on Grid Ubai =3D54,7V, The FME  T=
he TX FME Mbah Hosiah (674007438) is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power Issue Site on Grid Ubai =3D54,7V, The FME  The TX FME Mb=
ah Hosiah (674007438) is informed","olivier.kwedi@ihstowers.com","967","25-=
12-2024 09:37:14","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003931316","Tsi=
nga","","25-12-2024 09:36:01","25-12-2024 09:25:01","25-12-2024 09:59:57","=
Grid outage, site went down before gen start due to poor battery backup // =
Gen start automatically","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen start automatically","dorothy=
.djantio@ihstowers.com","1447","25-12-2024 09:36:01","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003931296","HOP=
ITAL GENERAL RAIL YDE","","25-12-2024 09:33:24","25-12-2024 09:23:59","25-1=
2-2024 10:41:44","site went down because gen failed to start due to grid fl=
uctuation and Eneo contactor faulty // He bypassed Eneo contactor , site on=
 grid","Delor Telezing","Equipment Repair","Passive","Control Panel","ATS-A=
MF Issue","site went down because gen failed to start due to grid fluctuati=
on and Eneo contactor faulty // He bypassed Eneo contactor , site on grid",=
"dorothy.djantio@ihstowers.com","566","25-12-2024 09:33:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003931295","S=
calom-IHS","","25-12-2024 09:33:11","25-12-2024 09:20:57","25-12-2024 09:51=
:57","grid outage,no space to deploy a mobil gen//grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no s=
pace to deploy a mobil gen//grid return","olivier.kwedi@ihstowers.com","736=
","25-12-2024 09:33:11","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003931291","Ema=
na","","25-12-2024 09:32:24","25-12-2024 09:21:59","25-12-2024 09:33:59","G=
RID OUTAGE, site went down before gen start due to poor battery backup // g=
en start automatically","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","GRID OUTAGE, site went down befo=
re gen start due to poor battery backup // gen start automatically","doroth=
y.djantio@ihstowers.com","626","25-12-2024 09:32:24","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003931278","Eko=
unou","","25-12-2024 09:30:13","25-12-2024 09:21:09","25-12-2024 09:33:09",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","do=
rothy.djantio@ihstowers.com","545","25-12-2024 09:30:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003931277","O=
lembe-Terminus","","25-12-2024 09:29:44","25-12-2024 09:20:38","25-12-2024 =
09:54:38","Grid outage, site went down because Gen start and stopped with A=
larm ""over voltage"" // He reset gen card and gen manually started","Fabri=
ce Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, site went down because Gen start and stopped with Alarm ""ove=
r voltage"" // He reset gen card and gen manually started","olivier.kwedi@i=
hstowers.com","547","25-12-2024 09:29:44","Sagemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003931274","Bas=
tos Bir","","25-12-2024 09:28:11","25-12-2024 09:20:07","25-12-2024 10:12:5=
0","GRID OUTAGE, site went down before gen start due to poor battery backup=
 // gen started","Mboua Thierry","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","GRID OUTAGE, site went down before gen st=
art due to poor battery backup // gen started","dorothy.djantio@ihstowers.c=
om","485","25-12-2024 09:28:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003930976","Akak-Nko=
zoa-MTN-IHS","","25-12-2024 08:26:40","25-12-2024 08:22:35","25-12-2024 08:=
33:33","Cascaded Incident from TTO3901202","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site do=
wn due to poor backup // Grid stabilized","system","272524","25-12-2024 08:=
26:40","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0003930518","AKA=
K Nkozoa","","25-12-2024 06:41:33","25-12-2024 06:34:28","25-12-2024 08:09:=
51","site went down because the CB 125A disjuncted in PWc//he reamed the CB=
","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Circuit Breaker Issue","site went down because the CB 125A disjuncte=
d in PWc//he reamed the CB","dorothy.djantio@ihstowers.com","426","25-12-20=
24 06:41:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003930501","Bastos E=
koudou","","25-12-2024 06:34:40","25-12-2024 06:17:52","25-12-2024 14:01:51=
","Cascaded Incident from TTO3900649","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage,no space to deploy a=
 mobil gen//grid return","system","294372","25-12-2024 06:34:40","Sagemcom =
CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003930497","Lab=
oratoire  Meka","IHS_YND_193","25-12-2024 06:33:58","25-12-2024 06:17:52","=
25-12-2024 14:01:51","grid outage,no space to deploy a mobil gen//grid retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid outage,no space to deploy a mobil gen//grid return","dorothy.djantio@i=
hstowers.com","967","25-12-2024 06:33:58","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003930490","Lad=
a I Yde","","25-12-2024 06:32:20","25-12-2024 06:04:14","25-12-2024 07:04:1=
4","Grid outage, site went down because gen failed to start due to gen cont=
actor not excited // He excited gen contactor , site on grid ","Mba Lazare =
Herve","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid o=
utage, site went down because gen failed to start due to gen contactor not =
excited // He excited gen contactor , site on grid ","dorothy.djantio@ihsto=
wers.com","1687","25-12-2024 06:32:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0003930413","S=
OA TOWN","","25-12-2024 06:06:17","25-12-2024 05:10:50","25-12-2024 05:28:2=
1","Grid fluctuation site went down because Gen and started and stopped due=
 to Grid bad voltage // Grid stabilzed","Siligap Boris","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation sit=
e went down because Gen and started and stopped due to Grid bad voltage // =
Grid stabilzed","kouoh.jean@ihstowers.com","3457","25-12-2024 06:06:17","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003930293","Tsi=
nga","","25-12-2024 05:35:56","25-12-2024 05:32:47","25-12-2024 06:26:22","=
Grid fluctuation, site went down before gen start due to poor battery backu=
p // Gen started automatically","Mboua Thierry","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid fluctuation, site wen=
t down before gen start due to poor battery backup // Gen started automatic=
ally","stephane.nkamwa@ihstowers.com","191","25-12-2024 05:35:56","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0003929895","SIM=
BOCK BONAMBAPE","","25-12-2024 02:42:33","25-12-2024 02:29:19","25-12-2024 =
02:43:35","Site was on Gen due to Grid outage, Site went down because Gen s=
topped due to fuse of Gen contactor cut// He did a bridge, Site on Gen","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contacto=
r","Site was on Gen due to Grid outage, Site went down because Gen stopped =
due to fuse of Gen contactor cut// He did a bridge, Site on Gen","stephane.=
nkamwa@ihstowers.com","795","25-12-2024 02:42:33","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0003929792","ELO=
UMDEM CARRIERE","","25-12-2024 01:42:34","25-12-2024 01:34:27","25-12-2024 =
02:01:35","Site was Gen due to Grid outage, site went down because gen stop=
ped with high temp alarm // he added water and manually start the gen","Fan=
da Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Site was Gen due to Grid outage, site went down bec=
ause gen stopped with high temp alarm // he added water and manually start =
the gen","stephane.nkamwa@ihstowers.com","488","25-12-2024 01:42:34","Sagem=
com CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003929449","NYO=
M FACE MAETUR","","24-12-2024 23:41:10","24-12-2024 19:48:43","25-12-2024 1=
2:48:00","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise awaitting Grid return","stephane.nkamwa@ihstowers.com","13948",=
"24-12-2024 23:41:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003928877","M=
ontee-Jouvence-II","","24-12-2024 21:32:22","24-12-2024 21:30:13","24-12-20=
24 21:41:40","site went down because PWC overload (12Kilo, 260A) // site st=
abilized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectif=
ier Module Overloaded","site went down because PWC overload (12Kilo, 260A) =
// site stabilized","emmanuel.ghani@ihstowers.com","130","24-12-2024 21:32:=
22","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0003928730","MBA=
LNGONG LYCEE","","24-12-2024 21:07:08","24-12-2024 21:03:02","24-12-2024 21=
:50:08","Grid outage,site went down before gen failed to start due  to load=
 balanace //We disconnected backup battery backup and site on gen","Fanda B=
rice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outag=
e,site went down before gen failed to start due  to load balanace //We disc=
onnected backup battery backup and site on gen","christian.fonkou@ihstowers=
.com","247","24-12-2024 21:07:08","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003928695","Men=
dong3","","24-12-2024 20:59:37","24-12-2024 20:56:30","25-12-2024 01:21:02"=
,"Grid outage, no space to deploy MDG // Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, no space to =
deploy MDG // Grid return","christian.fonkou@ihstowers.com","188","24-12-20=
24 20:59:37","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003928638","Odz=
a II","","24-12-2024 20:50:15","24-12-2024 20:44:10","24-12-2024 21:48:40",=
"Grid OUTAGE, site went down because gen fails to start due to ATS disfunct=
ionning //we reset ATS and gen manually started ","Albran Byorel","Equipmen=
t Repair","Passive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went=
 down because gen fails to start due to ATS disfunctionning //we reset ATS =
and gen manually started ","christian.fonkou@ihstowers.com","515","24-12-20=
24 20:50:15","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003928427","ODZ=
A CITE MBIA","","24-12-2024 20:05:35","24-12-2024 20:02:29","24-12-2024 20:=
39:29","Grid OUTAGE, site went down because gen fails to start due to ATS d=
isfunctionning // Grid power return","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down because=
 gen fails to start due to ATS disfunctionning // Grid power return","chris=
tian.fonkou@ihstowers.com","187","24-12-2024 20:05:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0003928398","Odza II =
OCM","","24-12-2024 20:01:20","24-12-2024 19:56:55","24-12-2024 21:41:48","=
Cascaded Incident from TTO3898163","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down because=
 gen failed to start // Grid return(investigation ongoing)","system","28107=
4","24-12-2024 20:01:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003928399","MEHANDAN=
","","24-12-2024 20:01:20","24-12-2024 19:56:55","24-12-2024 21:41:48","Cas=
caded Incident from TTO3898163","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down because ge=
n failed to start // Grid return(investigation ongoing)","system","281074",=
"24-12-2024 20:01:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0003928382","O=
dza-PK10","IHS_YND_527, IHS_YND_528","24-12-2024 19:58:03","24-12-2024 19:5=
6:55","24-12-2024 21:41:48","Grid outage, Site went down because gen failed=
 to start // Grid return(investigation ongoing)","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site wen=
t down because gen failed to start // Grid return(investigation ongoing)","=
emmanuel.ghani@ihstowers.com","69","24-12-2024 19:58:03","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0003928366","Awa=
e Ewonkan","","24-12-2024 19:53:12","24-12-2024 19:49:04","24-12-2024 20:05=
:08","Grid outage,site went down before gen starts due to poor battery back=
up//Grid return","Albran Byorel","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage,site went down before gen sta=
rts due to poor battery backup//Grid return","christian.fonkou@ihstowers.co=
m","333","24-12-2024 19:53:12","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003928363","Eko=
unou","","24-12-2024 19:51:04","24-12-2024 19:43:59","24-12-2024 20:09:49",=
"Grid outage site went down because Gen failed to start poor battery backup=
 // Grid power return","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage site went down because =
Gen failed to start poor battery backup // Grid power return","christian.fo=
nkou@ihstowers.com","427","24-12-2024 19:51:04","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003928352","Sap=
eur","","24-12-2024 19:47:01","24-12-2024 19:42:54","24-12-2024 19:48:04","=
Grid outage, the site went down before Gen started due to poor battery back=
up // Gen started automatically","Mboua Thierry","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, the site wen=
t down before Gen started due to poor battery backup // Gen started automat=
ically","christian.fonkou@ihstowers.com","248","24-12-2024 19:47:01","Sagem=
com CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003928319","Nko=
lbisson usines des eaux 2","","24-12-2024 19:39:55","24-12-2024 19:33:47","=
24-12-2024 19:44:13","Grid fluctuation, site went down because gen failed t=
o start due to grid bad voltage and no RCP // Grid stabilized","TIENTCHEU N=
ZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, site went down because gen failed to start =
due to grid bad voltage and no RCP // Grid stabilized","christian.fonkou@ih=
stowers.com","369","24-12-2024 19:39:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003928318","B=
itoto","","24-12-2024 19:39:48","24-12-2024 19:33:44","24-12-2024 22:49:42"=
," grid outage, Site went down to due to PWC ""ZTE' dysfunction// he reset =
it and started Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded"," grid outage, Site went down to due to =
PWC ""ZTE' dysfunction// he reset it and started Gen","emmanuel.ghani@ihsto=
wers.com","366","24-12-2024 19:39:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0003928290","C=
NR","","24-12-2024 19:34:15","24-12-2024 19:30:11","24-12-2024 19:35:11","N=
o power issue site on grid with U=3D53.8v Brice from Huawei is informed .si=
te up at 07:34 PM","Mboua Thierry","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D53.8v Brice Nomo from Huawei is informed .site up at 07:34 PM","em=
manuel.ghani@ihstowers.com","245","24-12-2024 19:34:15","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003928284","Nko=
lnda","","24-12-2024 19:33:32","24-12-2024 19:32:25","24-12-2024 21:14:03",=
"Grid outage, site went down before Gen start due to poor battery backup an=
d causing Disjunction at BTS MTN // Gen start automatically. Site Up after =
Power Reset","Albran Byorel","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, site went down before Gen start =
due to poor battery backup and causing Disjunction at BTS MTN // Gen start =
automatically. Site Up after Power Reset","christian.fonkou@ihstowers.com",=
"67","24-12-2024 19:33:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003928271","M=
imboman-Ecole","","24-12-2024 19:30:13","24-12-2024 19:20:08","24-12-2024 1=
9:38:29","Grid outage,site went down before gen starts due to poor battery =
backup//Grid return","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage,site went down before =
gen starts due to poor battery backup//Gen started automatically","emmanuel=
.ghani@ihstowers.com","607","24-12-2024 19:30:13","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003928269","OBA=
M NGOLA OCM","","24-12-2024 19:29:53","24-12-2024 19:23:47","24-12-2024 19:=
43:20","Grid outage, site went down because Gen stopped with alarm ""overcu=
rrent""// He reset card GE nad gen manually started ","MINKA NICOLAS","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, sit=
e went down because Gen stopped with alarm ""overcurrent""// He reset card =
GE nad gen manually started ","christian.fonkou@ihstowers.com","367","24-12=
-2024 19:29:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0003928261","E=
SSOS OASIS 1111","","24-12-2024 19:28:13","24-12-2024 19:21:10","24-12-2024=
 19:31:17","No power issue, U=3D52.8 V Site on GridThe TX FME Armand Nguets=
a (691144412) from Huawei is informed.Notice that we have dishunction at OC=
M Equipements ","Siligap Boris","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue, U=3D53. 5 V Sit=
e on GridThe TX FME Armand (691144412) from Huawei is informed.Notice that =
we have dishunction at OCM Equipements ","emmanuel.ghani@ihstowers.com","42=
4","24-12-2024 19:28:13","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003928257","Mim=
boman3","","24-12-2024 19:27:50","24-12-2024 19:19:44","24-12-2024 19:47:38=
","Grid outage, Site went down because PWC  ZTE  dysfunctionning// He reset=
 PWC and started Gen manualy","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","Grid outage, Site went down b=
ecause PWC  ZTE  dysfunctionning// He reset PWC and started Gen manualy","c=
hristian.fonkou@ihstowers.com","487","24-12-2024 19:27:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0003928252","E=
koumdoum OCM","","24-12-2024 19:26:58","24-12-2024 19:18:55","24-12-2024 22=
:43:09","Grid outage, Site went down because Gen overload (20kva, 300A)// H=
e reduiced the load and started Gen manualy","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down be=
cause Gen overload (20kva, 300A)// He reduiced the load and started Gen man=
ualy","emmanuel.ghani@ihstowers.com","484","24-12-2024 19:26:58","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003928249","M=
IMBOMAN LIBERTE","","24-12-2024 19:26:10","24-12-2024 19:17:05","24-12-2024=
 19:33:32","Grid Outage Site went down due to Main Gen Faulty//Grid Restore=
d","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Gener=
ator Faulty","Grid Outage Site went down due to Main Gen Faulty//Grid Resto=
red","emmanuel.ghani@ihstowers.com","547","24-12-2024 19:26:10","Sagemcom C=
MR"
"Closed Complete","Warning","","IHS_YND_008","NOCINC0003928243","CNDH","","=
24-12-2024 19:25:01","","","Grid fluctuation, Site alarming because on batt=
ery due to Grid bad voltage// Gen started automatically","Paul BIBOUM","War=
ning","Warning","POWER","Warning - Site on Battery","Grid fluctuation, Site=
 alarming because on battery due to Grid bad voltage// Gen started automati=
cally","joelle.ekessi@ihstowers.com","65","24-12-2024 19:25:01","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003928241","C=
ite-Verte","","24-12-2024 19:24:48","24-12-2024 19:19:43","24-12-2024 19:25=
:36","No power issue on site U=3D49,2 v site on Battery The FME TX Brice St=
ague of huawei is informed, Notice that we have disjunction in OCM equipmen=
t","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site U=3D49,2 v site on Battery The FME=
 TX Brice Stague of huawei is informed, Notice that we have disjunction in =
OCM equipment","emmanuel.ghani@ihstowers.com","306","24-12-2024 19:24:48","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003928238","M=
ANGUIERS CHAPELLE","","24-12-2024 19:23:49","24-12-2024 19:11:45","24-12-20=
24 19:37:53","Grid outage, site went down before Gen start due to poor batt=
ery backup // Gen start automatically","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before Gen start due to poor battery backup // Gen start automat=
ically","emmanuel.ghani@ihstowers.com","726","24-12-2024 19:23:49","Sagemco=
m CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003928226","BAT=
A Mokolo OCM","","24-12-2024 19:23:02","24-12-2024 19:10:52","24-12-2024 19=
:43:31","Grid outage no space to deploy the MDG // Grid power return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge no space to deploy the MDG // Grid power return","christian.fonkou@ihsto=
wers.com","731","24-12-2024 19:23:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003928224","A=
wae Escalier","","24-12-2024 19:22:48","24-12-2024 19:15:43","24-12-2024 20=
:04:54","Grid outage, Site went down before Gen start due to poor backup// =
Gen started automatically","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen started automatically","emmanuel.gha=
ni@ihstowers.com","426","24-12-2024 19:22:48","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003928218","Mok=
olo Yaounde","","24-12-2024 19:21:13","24-12-2024 19:10:06","24-12-2024 19:=
41:48","Grid outage no space to deploy the MDG // Grid power return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e no space to deploy the MDG // Grid power return","christian.fonkou@ihstow=
ers.com","668","24-12-2024 19:21:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003928213","Emana ly=
cee 2","","24-12-2024 19:20:01","24-12-2024 19:13:27","24-12-2024 19:46:14"=
,"Cascaded Incident from TTO3897948","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down bec=
ause gen failed to start due to dysfunctioning of gen card // grid Restored=
","system","269268","24-12-2024 19:20:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003928211","Emana Ly=
cee","","24-12-2024 19:20:01","24-12-2024 19:13:27","24-12-2024 19:46:14","=
Cascaded Incident from TTO3897948","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site went down becau=
se gen failed to start due to dysfunctioning of gen card // grid Restored",=
"system","269267","24-12-2024 19:20:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003928210","EMANA BI=
LICK CITY","","24-12-2024 19:20:01","24-12-2024 19:13:27","24-12-2024 19:46=
:14","Cascaded Incident from TTO3897948","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid outage, site went down=
 because gen failed to start due to dysfunctioning of gen card // grid Rest=
ored","system","269267","24-12-2024 19:20:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003928212","Messassi=
 okolo","","24-12-2024 19:20:01","24-12-2024 19:13:27","24-12-2024 19:46:14=
","Cascaded Incident from TTO3897948","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, site went down be=
cause gen failed to start due to dysfunctioning of gen card // grid Restore=
d","system","269268","24-12-2024 19:20:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003928209","Mballa 4=
","","24-12-2024 19:20:00","24-12-2024 19:13:27","24-12-2024 19:46:14","Cas=
caded Incident from TTO3897948","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, site went down because g=
en failed to start due to dysfunctioning of gen card // grid Restored","sys=
tem","269267","24-12-2024 19:20:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003928204","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","24=
-12-2024 19:18:32","24-12-2024 19:13:27","24-12-2024 19:46:14","grid outage=
, site went down because gen failed to start due to dysfunctioning of gen c=
ard // grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","grid outage, site went down because gen failed=
 to start due to dysfunctioning of gen card // grid Restored","emmanuel.gha=
ni@ihstowers.com","306","24-12-2024 19:18:32","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003928199","Ema=
na","","24-12-2024 19:17:33","24-12-2024 19:07:28","24-12-2024 19:19:55","G=
RID OUTAGE, site went down before gen start due to poor battery backup // g=
en start automatically","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","GRID OUTAGE, site went down befo=
re gen start due to poor battery backup // gen start automatically","christ=
ian.fonkou@ihstowers.com","606","24-12-2024 19:17:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003928196","M=
ontee-Des-Soeurs","","24-12-2024 19:17:02","24-12-2024 19:07:59","24-12-202=
4 19:15:59","Active// No power Issue Site on Grid Ubai =3D54,7V, The FME  T=
he TX FME Mbah Hosiah (674007438) is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power Issue Site on Grid Ubai =3D54,7V, The FME  The TX FME Mb=
ah Hosiah (674007438) is informed","emmanuel.ghani@ihstowers.com","544","24=
-12-2024 19:17:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003928187","MVAN SAC=
EL","","24-12-2024 19:15:30","24-12-2024 19:06:07","24-12-2024 19:38:08","C=
ascaded Incident from TTO3897920","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down due to G=
en overload (20Kva ,290 A)// Grid return","system","291359","24-12-2024 19:=
15:30","Sagemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003928182","Bas=
tos Bir","","24-12-2024 19:14:43","24-12-2024 19:07:37","24-12-2024 19:15:4=
4","Grid outage, site went down before gen start due to poor battery backup=
 // Grid restored","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before gen =
start due to poor battery backup // Grid restored","christian.fonkou@ihstow=
ers.com","427","24-12-2024 19:14:43","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_727","NOCINC0003928176","Nlong Mvol=
ye New","","24-12-2024 19:12:40","","","Site alarming on battery due to gri=
d outage // Dg started automatically","Paul BIBOUM","Warning","Warning","PO=
WER","Warning - Site on Battery","Site alarming on battery due to grid outa=
ge // Dg started automatically","joelle.ekessi@ihstowers.com","66","24-12-2=
024 19:12:40","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003928175","MVA=
N","IHS_YND_510","24-12-2024 19:12:14","24-12-2024 19:06:07","24-12-2024 19=
:39:49","Grid outage, Site went down due to Gen overload (20Kva ,290 A)// G=
rid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid outage, Site went down due to Gen overload (20Kva ,290 A)/=
/ Grid return","christian.fonkou@ihstowers.com","531","24-12-2024 19:12:14"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003928040","E=
bogo","","24-12-2024 18:34:14","24-12-2024 18:29:08","24-12-2024 19:49:25",=
"Grid fluctuation site went down because Gen failed to start due to Grid ba=
d voltage and poor battery backup // Grid stabilized","Siligap Boris","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 fluctuation site went down because Gen failed to start due to Grid bad vol=
tage and poor battery backup // Grid stabilized","emmanuel.ghani@ihstowers.=
com","307","24-12-2024 18:34:14","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003927908","Nko=
ulou Carriere carrefourt","","24-12-2024 18:00:37","24-12-2024 17:52:30","2=
4-12-2024 22:10:22","Grid outage site went down because Gen Started and sto=
pped with alarm low oil pressure // He added oil and Gen manually started",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil =
Pressure","Grid outage site went down because Gen Started and stopped with =
alarm low oil pressure // He added oil and Gen manually started","christian=
.fonkou@ihstowers.com","488","24-12-2024 18:00:37","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003927551","AWA=
E OCM","","24-12-2024 16:42:26","24-12-2024 16:39:21","24-12-2024 18:53:39"=
," grid outage, Site went down to due to PWC ""ZTE' dysfunction// he reset =
it and started Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded"," grid outage, Site went down to due to =
PWC ""ZTE' dysfunction// he reset it and started Gen","christian.fonkou@ihs=
towers.com","237","24-12-2024 16:42:26","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_263","NOCINC0003927267","Mendong Pl=
ateau","","24-12-2024 15:56:48","","","site on high temp //he open the shel=
ter","Hyemafo Gildas","Warning","Warning","ENVIRONMENT","Warning - High Tem=
perature","site on high temp //he open the shelter","joelle.ekessi@ihstower=
s.com","70","24-12-2024 15:56:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003927041","M=
fou EPC","","24-12-2024 15:19:24","24-12-2024 15:17:18","24-12-2024 15:36:5=
8","Grid outage, site went down because gen start and stopped with high tem=
p alarm // he added water and manually start the gen","Mba Lazare Herve","E=
quipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Le=
vel Issue","Grid outage, site went down because gen start and stopped with =
high temp alarm // he added water and manually start the gen","emmanuel.gha=
ni@ihstowers.com","128","24-12-2024 15:19:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0003927002","B=
ondjock","","24-12-2024 15:13:01","24-12-2024 15:09:45","24-12-2024 15:15:3=
1","Grid outage, Site went down before Gen start due to poor backup// Gen s=
tart automatically","Fanda Brice","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup// Gen start automatically","emmanuel.ghani@ihstower=
s.com","197","24-12-2024 15:13:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_441","IHS_YND_687","NOCINC0003926525","O=
LAMA","","24-12-2024 13:50:20","24-12-2024 13:47:15","24-12-2024 18:15:58",=
"Active//No power issue on site, Site on Gen , UBAIE=3D54V and Geoges (6974=
61814) From huawei is informed and Site Up AT=3D01.01 PM","Fanda Brice","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site, Site on Gen , UBAIE=3D54V and Geog=
es (697461814) From huawei is informed and Site Up AT=3D01.01 PM","rouselle=
.schoune@ihstowers.com","186","24-12-2024 13:50:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003926449","S=
tade-Abega","","24-12-2024 13:39:07","24-12-2024 13:34:02","24-12-2024 14:0=
6:05","grid outage, site went down due to dysfunctionning of the PWC ZTE //=
 Gen manually started","Mba Lazare Herve","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","grid outage, site went down due to d=
ysfunctionning of the PWC ZTE // Gen manually started","rouselle.schoune@ih=
stowers.com","306","24-12-2024 13:39:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003926384","A=
WAE OCM","","24-12-2024 13:27:00","24-12-2024 13:25:54","24-12-2024 13:44:4=
3","Grid outage, site went down before gen start due to poor battery backup=
 // Gen started automatically","Mba Lazare Herve","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // Gen started automaticall=
y","rouselle.schoune@ihstowers.com","67","24-12-2024 13:27:00","Sagemcom CM=
R"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003926379","Nko=
abang Ebolmedjock","","24-12-2024 13:25:11","24-12-2024 13:17:00","24-12-20=
24 14:25:17","Grid outage,site went down because Gen failed to start due to=
 bad grid voltage, no RCP on site// site on Gen","Mba Lazare Herve","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid out=
age,site went down because Gen failed to start due to bad grid voltage, no =
RCP on site// site on Gen","ange.kongo@ihstowers.com","492","24-12-2024 13:=
25:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003925349","M=
essa-Carriere OCM","","24-12-2024 10:40:20","24-12-2024 10:36:16","24-12-20=
24 11:35:35","ACTIVE // No Power issue on site Ubaie=3D52.7V site  on GridT=
he TX Fme Mohamadou 691144435 of huawei is informed. ","","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIV=
E // No Power issue on site Ubaie=3D52.7V site  on GridThe TX Fme Mohamadou=
 691144435 of huawei is informed. ","rouselle.schoune@ihstowers.com","246",=
"24-12-2024 10:40:20","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003925253","Nsi=
meyong Terre Rouge","","24-12-2024 10:20:44","24-12-2024 10:17:34","24-12-2=
024 10:29:56","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen start automatically","MINKA NICOLAS","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site =
went down before gen start due to poor battery backup // Gen start automati=
cally","ange.kongo@ihstowers.com","191","24-12-2024 10:20:44","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0003925177","N=
kolbong","","24-12-2024 10:05:44","24-12-2024 10:01:39","24-12-2024 10:40:5=
5","ACTIVE No power issue U=3D53,2V site on Grid The TX FME   synphorien / =
675295205 from huawei is informed","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No p=
ower issue U=3D53,2V site on Grid The TX FME   synphorien / 675295205 from =
huawei is informed","rouselle.schoune@ihstowers.com","246","24-12-2024 10:0=
5:44","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003925050","Pha=
rmacie SION","","24-12-2024 09:43:08","24-12-2024 09:37:58","24-12-2024 09:=
48:27","Grid outage, Site went down before Gen start due to poor backup// G=
en start automatically","Paul BIBOUM","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, Site went down before G=
en start due to poor backup// Gen start automatically","ange.kongo@ihstower=
s.com","311","24-12-2024 09:43:08","Sagemcom CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0003925031","CLE=
 Building","","24-12-2024 09:38:54","24-12-2024 09:33:47","03-01-2025 13:37=
:40","Acces issue Grid outage, no space to deploy a mobil gen//Grid return"=
,"","Access Denial","Lease Or Legal","Landlord Related Issues","Access Issu=
e - Land Lord","Acces issue (grid outage, no space to deploy a mobil gen, g=
rid return awaited)","ange.kongo@ihstowers.com","308","24-12-2024 09:38:54"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003924965","Bas=
tos Amb Coree","","24-12-2024 09:26:32","24-12-2024 09:23:25","24-12-2024 0=
9:27:47","Grid outage, no space to deploy MDG // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no s=
pace to deploy MDG // Grid return","ange.kongo@ihstowers.com","189","24-12-=
2024 09:26:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003924538","E=
bogo","","24-12-2024 07:40:51","24-12-2024 07:38:46","24-12-2024 07:40:30",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
t automatically","Siligap Boris","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, Site went down before Gen st=
art due to poor backup// Gen start automatically","rouselle.schoune@ihstowe=
rs.com","126","24-12-2024 07:40:51","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0003924001","Fou=
da Quarter","","24-12-2024 05:26:40","24-12-2024 04:24:15","24-12-2024 04:4=
2:15","grid bad voltage, site went down because gen fails to start due to l=
ack of 01 phase on site // he did a brdge with a good phase","Delor Telezin=
g","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid=
 bad voltage, site went down because gen fails to start due to lack of 01 p=
hase on site // he did a brdge with a good phase","kamga.virgile@ihstowers.=
com","3746","24-12-2024 05:26:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003923372","S=
atcom","","24-12-2024 00:02:58","23-12-2024 23:51:50","23-12-2024 23:52:50"=
,"Active//No power issue on site Ubaie=3D50,8V site on Grid The tx fme Arma=
nd nguetsa(691144412) is informed","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie=3D50,8V site on Grid The tx fme Armand nguetsa(69=
1144412) is informed","alexandre.kamal@ihstowers.com","669","24-12-2024 00:=
02:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_599","IHS_YND_279","NOCINC0003922485","M=
essassi okolo","","23-12-2024 21:46:30","23-12-2024 21:26:22","23-12-2024 2=
1:27:55","No power issue site on grid with U=3D54.4V Symphorien from huawei=
 is informed","Fabrice Pouakam","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wit=
h U=3D54.4V Symphorien from huawei is informed","stephane.nkamwa@ihstowers.=
com","1210","23-12-2024 21:46:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003922261","SOA VILL=
AGE","","23-12-2024 21:17:40","23-12-2024 21:10:55","23-12-2024 21:31:36","=
Cascaded Incident from TTO3891098","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause gen start and stopped due to grid bad voltage // he bypass grid and m=
anually start the gen","system","269790","23-12-2024 21:17:40","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0003922146","S=
OA TOWN","IHS_YND_323","23-12-2024 21:10:02","23-12-2024 21:06:55","23-12-2=
024 21:31:36","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage // he bypass grid and manually start the gen","S=
iligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because gen start and stopped=
 due to grid bad voltage // he bypass grid and manually start the gen","ste=
phane.nkamwa@ihstowers.com","188","23-12-2024 21:10:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003920766","A=
wae Escalier","","23-12-2024 19:07:47","23-12-2024 18:57:40","23-12-2024 20=
:50:47","","Albran Byorel","Access Denial","Security","Security Concerns In=
 Site Environs","Access Issue - Security","site down due to DG breaker faul=
ty // fme bypass DG breaker to be raplace tomorrow ","stephane.nkamwa@ihsto=
wers.com","608","23-12-2024 19:07:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003920485","E=
bogo","","23-12-2024 18:37:51","23-12-2024 18:34:44","23-12-2024 18:40:43",=
"GRID OUTAGE, site went down before gen start due to poor battery backup //=
 gen start automatically","Siligap Boris","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","GRID OUTAGE, site went down befo=
re gen start due to poor battery backup // gen start automatically","stepha=
ne.nkamwa@ihstowers.com","188","23-12-2024 18:37:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003920390","N=
yom OCM","","23-12-2024 18:19:26","23-12-2024 18:06:21","23-12-2024 18:10:1=
7","No power issue site on Gen with U=3D54,2v Symphorien(691316854) from Hu=
awei is informed","Fabrice Pouakam","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on Gen =
with U=3D54,2v Symphorien(691316854) from Huawei is informed","stephane.nka=
mwa@ihstowers.com","787","23-12-2024 18:19:26","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0003918987","Mvo=
g-Manga","","23-12-2024 15:11:39","23-12-2024 14:54:09","23-12-2024 16:35:0=
9","Grid bad voltage, site went down because gen ran untill fuel shortage /=
/ refueling done.","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid bad voltage, site went down because gen ran untill fuel shor=
tage // refueling done.","landry.etame@ihstowers.com","1052","23-12-2024 15=
:11:39","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0003918974","Tou=
ring Club International","","23-12-2024 15:10:27","23-12-2024 14:55:16","23=
-12-2024 15:09:53","Grid outage, site went down before Gen start due to poo=
r battery backup // Grid Restored","Albran Byorel","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before Gen start due to poor battery backup // Grid Restored","landry.=
etame@ihstowers.com","911","23-12-2024 15:10:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003918943","E=
kie sud","","23-12-2024 15:06:54","23-12-2024 15:01:45","23-12-2024 15:19:4=
9","Hybrid Gen Site: Site went down because Gen failed to start due to Hybr=
id system dysfonction//Grid Restored","Albran Byorel","Equipment Repair","P=
assive","Hybrid","Hybrid Module","Hybrid Gen Site: Site went down because G=
en failed to start due to Hybrid system dysfonction//Grid Restored","stepha=
ne.nkamwa@ihstowers.com","310","23-12-2024 15:06:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003918685","Nsimalen=
 OCM","","23-12-2024 14:52:10","23-12-2024 14:11:04","23-12-2024 15:04:52",=
"Cascaded Incident from TTO3887027","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause Gen fails to start du to Grid bad voltage, no rcp on site // he bypa=
ss Grid and manually start the Gen","system","287339","23-12-2024 14:52:10"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003918673","N=
kolda","IHS_YND_327","23-12-2024 14:51:15","23-12-2024 14:11:04","23-12-202=
4 15:04:52","Grid fluctuation, site went down because Gen fails to start du=
 to Grid bad voltage, no rcp on site // he bypass Grid and manually start t=
he Gen","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid fluctuation, site went down because Gen fails t=
o start du to Grid bad voltage, no rcp on site // he bypass Grid and manual=
ly start the Gen","stephane.nkamwa@ihstowers.com","2412","23-12-2024 14:51:=
15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003918323","H=
-Progres","","23-12-2024 14:04:34","23-12-2024 13:59:27","23-12-2024 14:58:=
00","Grid outage, no space to deploy a mobile gen// Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, n=
o space to deploy a mobile gen// Grid return","emmanuel.ghani@ihstowers.com=
","308","23-12-2024 14:04:34","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003918233","MVA=
N","","23-12-2024 13:49:22","23-12-2024 13:47:13","23-12-2024 14:09:28","Gr=
id Outage and Gen overload (20Kva ,290 A)//Grid Restored","MINKA NICOLAS","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage and G=
en overload (20Kva ,290 A)//Grid Restored","christian.fonkou@ihstowers.com"=
,"130","23-12-2024 13:49:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003918164","I=
mm-Olympique","","23-12-2024 13:34:15","23-12-2024 13:26:10","23-12-2024 15=
:00:52","Site went down due to CB(125A) tripped in PWC who feeds equipments=
 OCM// He did a bridge with CB(63A) ","Paul BIBOUM","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went do=
wn due to CB(125A) tripped in PWC who feeds equipments OCM// He did a bridg=
e with CB(63A) ","emmanuel.ghani@ihstowers.com","486","23-12-2024 13:34:15"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003918094","BAT=
A Mokolo OCM","","23-12-2024 13:22:26","23-12-2024 13:20:19","23-12-2024 15=
:05:37","Grid outage, no space to deploy a mobile gen// Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e, no space to deploy a mobile gen// Grid return","christian.fonkou@ihstowe=
rs.com","128","23-12-2024 13:22:26","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003918010","Lad=
a I Yde","","23-12-2024 13:04:27","23-12-2024 13:02:22","23-12-2024 14:53:3=
8","Grid outage, site went down because Gen ran until fuel shortage// Refue=
ling Done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because Gen ran until fuel shortage// Refu=
eling Done","christian.fonkou@ihstowers.com","126","23-12-2024 13:04:27","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003917966","Nsimalen=
 OCM","","23-12-2024 12:56:41","23-12-2024 12:49:32","23-12-2024 13:05:24",=
"Cascaded Incident from TTO3886162","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid OUtage Site went down because=
 Gen Contactors Dysfutionning//he bypass it and Manually Started the Gen","=
system","270784","23-12-2024 12:56:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003917903","N=
kolda","IHS_YND_327","23-12-2024 12:53:36","23-12-2024 12:49:32","23-12-202=
4 13:05:24","Grid OUtage Site went down because Gen Contactors Dysfutionnin=
g//he bypass it and Manually Started the Gen","Albran Byorel","Equipment Re=
pair","Passive","Control Panel","ATS-AMF Issue","Grid OUtage Site went down=
 because Gen Contactors Dysfutionning//he bypass it and Manually Started th=
e Gen","emmanuel.ghani@ihstowers.com","246","23-12-2024 12:53:36","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003917836","Nko=
ulou Carriere carrefourt","","23-12-2024 12:48:25","23-12-2024 12:41:16","2=
3-12-2024 13:00:31","Site was not down","Mba Lazare Herve","Incorrectly Log=
ged Tickets","Error","Error","Error","Site was not down","christian.fonkou@=
ihstowers.com","430","23-12-2024 12:48:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003917829","M=
VAN SACEL","","23-12-2024 12:47:21","23-12-2024 12:42:43","23-12-2024 13:36=
:38","Grid outage, Site went down before Gen start due to poor battery back=
up and causing disjunction at BTS OCM// Gen started automatically and CB pu=
t back on ","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage, Site went down before Gen start d=
ue to poor battery backup and causing disjunction at BTS OCM// Gen started =
automatically and CB put back on ","emmanuel.ghani@ihstowers.com","279","23=
-12-2024 12:47:21","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0003917736","Nko=
lbisson IITA LP","","23-12-2024 12:29:36","23-12-2024 12:28:30","23-12-2024=
 18:30:06","grid ourtage, no space to deploy a mobile gen // Grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid =
ourtage, no space to deploy a mobile gen // Grid return","christian.fonkou@=
ihstowers.com","67","23-12-2024 12:29:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003917719","S=
aa","IHS_YND_401, IHS_YND_404","23-12-2024 12:26:53","23-12-2024 12:24:44",=
"23-12-2024 12:50:09","NO power  issue on site ,site on Grid The TX FME Gre=
goire(654547479) from Huawei is working on site.Site up at 12:26 pm","Parke=
r Tchoup","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","NO power  issue on site ,site on Grid The TX FME Greg=
oire(654547479) from Huawei is working on site.Site up at 12:26 pm","emmanu=
el.ghani@ihstowers.com","130","23-12-2024 12:26:53","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0003917157","SAA=
 2","","23-12-2024 11:02:19","23-12-2024 10:57:11","23-12-2024 12:26:33","G=
rid outage, site went down because gen ran until fuel shortage // refueling=
 done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage, site went down because gen ran until fuel shortage // refueling =
done","christian.fonkou@ihstowers.com","309","23-12-2024 11:02:19","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003916818","M=
essa-Carriere OCM","","23-12-2024 10:37:44","23-12-2024 10:33:08","23-12-20=
24 13:00:42","No power issue on site ,site on Grid with Ubaie=3D 52 .5 V Th=
e Fme Tx Brice Nomo/ 656925472??/ from HUAWEI is informed ","","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site ,site on Grid with Ubaie=3D 52 .5 V The Fme Tx Brice=
 Nomo/ 656925472??/ from HUAWEI is informed ","emmanuel.ghani@ihstowers.com=
","278","23-12-2024 10:37:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003916546","S=
tade-Abega","","23-12-2024 10:05:40","23-12-2024 10:04:36","23-12-2024 10:1=
9:45","Grid outage, site went down due to dysfunctionning of the PWC ZTE //=
 Grid power return","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Grid outage, site went down due to dysf=
unctionning of the PWC ZTE // Grid power return","emmanuel.ghani@ihstowers.=
com","65","23-12-2024 10:05:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003916509","A=
WAE OCM","","23-12-2024 09:58:07","23-12-2024 09:55:02","23-12-2024 11:29:4=
2","Grid outage, site went down due to dysfunctionning of the PWC ZTE // Ge=
n started manually","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Grid outage, site went down due to dysf=
unctionning of the PWC ZTE // Gen started manually","emmanuel.ghani@ihstowe=
rs.com","186","23-12-2024 09:58:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003916503","M=
IMBOMAN LIBERTE","","23-12-2024 09:57:17","23-12-2024 09:53:11","23-12-2024=
 10:13:44","Grid outage,site went down because Main Gen faulty//Grid power =
return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - =
Generator Faulty","Grid outage,site went down because Main Gen faulty//Grid=
 power return","emmanuel.ghani@ihstowers.com","247","23-12-2024 09:57:17","=
Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_293","NOCINC0003916484","Nkoabang M=
TN","","23-12-2024 09:54:51","","","site on alarm on battery due to grid ou=
tage//gen started automatically","Mba Lazare Herve","Warning","Warning","PO=
WER","Warning - Site on Battery","site on alarm on battery due to grid outa=
ge//gen started automatically","joelle.ekessi@ihstowers.com","66","23-12-20=
24 09:54:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003916057","E=
kounou","","23-12-2024 08:57:20","23-12-2024 08:55:16","23-12-2024 09:08:46=
","Grid outage, site went down before gen start due to poor battery backup =
// Grid power return","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, site went down before g=
en start due to poor battery backup // Grid power return","emmanuel.ghani@i=
hstowers.com","126","23-12-2024 08:57:20","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003915794","Elo=
umdem stade","","23-12-2024 08:16:40","23-12-2024 08:07:35","23-12-2024 08:=
25:19","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage and no rcp on ste  // he bypass grid and manually start=
 the gen","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid fluctuation, site went down because gen start a=
nd stopped due to grid bad voltage and no rcp on ste  // he bypass grid and=
 manually start the gen","christian.fonkou@ihstowers.com","546","23-12-2024=
 08:16:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0003915592","S=
cience","","23-12-2024 07:37:31","23-12-2024 07:23:25","23-12-2024 09:15:29=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage and no rcp on site // he bypassed  grid and manually start t=
he gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Grid fluctuation, site went down because =
gen start and stopped due to grid bad voltage and no rcp on site // he bypa=
ssed  grid and manually start the gen","emmanuel.ghani@ihstowers.com","847"=
,"23-12-2024 07:37:31","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_008","NOCINC0003915522","CNDH","","=
23-12-2024 07:21:08","","","The site alarmed because the air conditioner wa=
s completely frozen // defrost Done and air conditioner restarted","Paul BI=
BOUM","Warning","Warning","ENVIRONMENT","Warning - High Temperature","The s=
ite alarmed because the air conditioner was completely frozen // defrost Do=
ne and air conditioner restarted","joelle.ekessi@ihstowers.com","70","23-12=
-2024 07:21:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003915411","O=
dza II","","23-12-2024 06:57:37","23-12-2024 06:56:17","23-12-2024 08:42:50=
","Site went down pecause PWC dysfonction//He reconfigured it ,site on Gen"=
,"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module=
 Overloaded","Site went down pecause PWC dysfonction//He reconfigured it ,s=
ite on Gen","emmanuel.ghani@ihstowers.com","82","23-12-2024 06:57:37","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003915407","D=
amas","","23-12-2024 06:56:26","23-12-2024 06:52:53","23-12-2024 08:09:08",=
"No power issue on site ,site on Grid with Ubaie=3D54.1 V he FME The TX FME=
 Mbah Hosiah (674007438) is informed","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site ,site on Grid with Ubaie=3D54.1 V he FME The TX FME Mbah Hosi=
ah (674007438) is informed","emmanuel.ghani@ihstowers.com","214","23-12-202=
4 06:56:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003915398","T=
amtam Weekend","","23-12-2024 06:52:25","23-12-2024 06:51:16","23-12-2024 0=
8:03:59","Grid outage ,site went down because Gen start and stopped due to =
Gen(20KVA,300A)//He reduced the load on site ","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went down=
 because Gen start and stopped due to Gen(20KVA,300A)//He reduced the load =
on site ","emmanuel.ghani@ihstowers.com","70","23-12-2024 06:52:25","Sagemc=
om CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0003914739","Mae=
tur","","23-12-2024 03:48:39","23-12-2024 03:42:22","23-12-2024 05:04:59","=
grid outage,gen ran till fuel shortage//Refueling done","Mboua Thierry","Fu=
el Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran till fue=
l shortage//Refueling done","ludivine.ngamaleu@ihstowers.com","378","23-12-=
2024 03:48:39","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003914403","OLA=
MA","","23-12-2024 02:50:14","23-12-2024 02:44:08","23-12-2024 03:00:43","g=
rid outage,gen ran till fuel shortage//Refueling done","Fanda Brice","Fuel =
Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran till fuel s=
hortage//Refueling done","ludivine.ngamaleu@ihstowers.com","367","23-12-202=
4 02:50:14","Sagemcom CMR"
"Closed Complete","Warning","CTR_425","IHS_YND_141","NOCINC0003914233","New=
-Marche-Melen","","23-12-2024 01:04:36","","","site alarming because gen ra=
n until fuel shortage // refueling done and alarming cleared","Paul BIBOUM"=
,"Warning","Warning","POWER","Warning - Site on Battery","site alarming bec=
ause gen ran until fuel shortage // refueling done and alarming cleared","l=
udivine.ngamaleu@ihstowers.com","4","23-12-2024 01:04:36","Sagemcom CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0003914053","Mae=
tur","","22-12-2024 23:45:02","22-12-2024 23:39:59","22-12-2024 23:53:59","=
grid outage,gen failed to start due to alarm ""Electrical trip""//he reset =
card and started the gen","Mboua Thierry","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","grid outage,gen failed to start due to alarm=
 ""Electrical trip""//he reset card and started the gen","ludivine.ngamaleu=
@ihstowers.com","304","22-12-2024 23:45:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0003914052","B=
ondjock","","22-12-2024 23:44:52","22-12-2024 23:41:47","22-12-2024 23:53:4=
7","Grid outage, site went down before gen start due to poor battery backup=
 // Gen start automatically","Fanda Brice","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start automatically","olivi=
er.kwedi@ihstowers.com","186","22-12-2024 23:44:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003914018","A=
wae Escalier","","22-12-2024 23:34:54","22-12-2024 23:29:37","23-12-2024 00=
:24:07","No power issue on site U=3D53,8v site on grid Georges 697461814 of=
 huawei is informed","Albran Byorel","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53,8v site on grid Georges 697461814 of huawei is informed","olivier.kwe=
di@ihstowers.com","318","22-12-2024 23:34:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003913975","K=
oweit City","","22-12-2024 23:24:34","22-12-2024 23:21:20","22-12-2024 23:2=
5:20","site went down due to insufficient of rectifier//site stabilized","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","=
site went down due to insufficient of rectifier//site stabilized","olivier.=
kwedi@ihstowers.com","195","22-12-2024 23:24:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003913835","E=
ssomba","","22-12-2024 22:35:47","22-12-2024 22:23:35","23-12-2024 00:18:35=
","No power issue on site U=3D53,8v site on grid Georges 697461814 of huawe=
i is informed notice that disjunction of Bts Ocm","Mba Lazare Herve","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site U=3D53,8v site on grid Georges 697461814 of hu=
awei is informed notice that disjunction of Bts Ocm","olivier.kwedi@ihstowe=
rs.com","733","22-12-2024 22:35:47","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003913710","AWA=
E OCM","","22-12-2024 22:09:32","22-12-2024 22:06:26","22-12-2024 22:28:26"=
,"grid outage, site went down due to dysfunctionning of the PWC ZTE // Gen =
manually started","Mba Lazare Herve","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","grid outage, site went down due to dysfun=
ctionning of the PWC ZTE // Gen manually started","ludivine.ngamaleu@ihstow=
ers.com","187","22-12-2024 22:09:32","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003913704","Eko=
unou","","22-12-2024 22:08:43","22-12-2024 22:04:34","22-12-2024 22:44:34",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","ludivi=
ne.ngamaleu@ihstowers.com","250","22-12-2024 22:08:43","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003913498","Feb=
e Village","","22-12-2024 21:37:44","22-12-2024 21:35:05","22-12-2024 21:37=
:05","site went down because insufficient of rectifier( 04)//he added one r=
ectifier: site on 5 rectifiers","Mboua Thierry","Equipment Repair","Passive=
","Rectifier","Rectifier Module","site went down because insufficient of re=
ctifier( 04)//he added one rectifier: site on 5 rectifiers","kamga.virgile@=
ihstowers.com","160","22-12-2024 21:37:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0003913012","B=
IYEMASSI NIKI","","22-12-2024 20:01:49","22-12-2024 19:34:41","22-12-2024 2=
1:04:15","Site went down due to PWC overloaded (12kva 250 A) //Site stabili=
zed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Sit=
e stabilized","alexandre.kamal@ihstowers.com","1628","22-12-2024 20:01:49",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003912998","S=
calom-IHS","","22-12-2024 19:59:54","22-12-2024 19:12:48","22-12-2024 20:52=
:13","Grid outage, No space to deploy MDG // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space=
 to deploy MDG // Grid return","alexandre.kamal@ihstowers.com","2828","22-1=
2-2024 19:59:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003912993","D=
amas","","22-12-2024 19:58:56","22-12-2024 19:32:25","22-12-2024 19:52:23",=
"","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Site went down due to gen overload (20 kva,300 A)//He reduiced load=
 and gen manually started","alexandre.kamal@ihstowers.com","268255","22-12-=
2024 19:58:56","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0003912928","Mon=
tee-Jouvence-II","","22-12-2024 19:49:25","22-12-2024 19:35:05","22-12-2024=
 20:24:11","Site went down due to PWC over load(12KW.280A)// Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC over load(12KW.280A)// Site stab=
ilized","kamga.virgile@ihstowers.com","861","22-12-2024 19:49:25","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0003912918","Tam=
tam Weekend","IHS_YND_166","22-12-2024 19:47:42","22-12-2024 19:32:25","22-=
12-2024 19:55:04","Site went down due to gen overload (20 kva,300 A)//He re=
duiced load and gen manually started","Hyemafo Gildas","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Site went down due to gen overload (=
20 kva,300 A)//He reduiced load and gen manually started","kamga.virgile@ih=
stowers.com","1446","22-12-2024 19:47:42","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003912434","Nko=
abang Ebolmedjock","","22-12-2024 19:15:47","22-12-2024 18:52:42","23-12-20=
24 00:05:49","no power issue U:53.6V site on Gen. TX FME Leonel Steve (6551=
84876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power iss=
ue U:53.6V site on Gen. TX FME Leonel Steve (655184876) from Huawei is info=
rmed","kamga.virgile@ihstowers.com","1386","22-12-2024 19:15:47","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0003911984","E=
koumdoum OCM","","22-12-2024 17:54:39","22-12-2024 17:47:33","22-12-2024 20=
:18:36","Grid outage, Site went down because Gen overload (20kva, 300A)// H=
e reduiced the load and started Gen manualy","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down be=
cause Gen overload (20kva, 300A)// He reduiced the load and started Gen man=
ualy","alexandre.kamal@ihstowers.com","427","22-12-2024 17:54:39","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0003911960","S=
oa-Sofamac","","22-12-2024 17:49:09","22-12-2024 17:41:01","22-12-2024 20:0=
5:48","Grid outage, Site went down because gen started and stopped due to w=
ater mixed with fuel in tank//he purged it and started the gen","Siligap Bo=
ris","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Wate=
r In The Fuel","Grid outage, Site went down because gen started and stopped=
 due to water mixed with fuel in tank//he purged it and started the gen","a=
lexandre.kamal@ihstowers.com","488","22-12-2024 17:49:09","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003911304","ODZ=
A CITE MBIA","","22-12-2024 16:47:07","22-12-2024 16:31:58","22-12-2024 22:=
35:58","site went down because insufficient of rectifier//he reduice the lo=
ad","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","site went down because insufficient of rectifier//he reduice the load=
","kamga.virgile@ihstowers.com","910","22-12-2024 16:47:07","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003911277","Odz=
a II","","22-12-2024 16:42:13","22-12-2024 16:26:02","22-12-2024 18:40:15",=
"grid outage ,gen stopped witha alarm high temp//he removed the rheostat","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine =
Temp - Coolant Level Issue","grid outage ,gen stopped witha alarm high temp=
//he removed the rheostat","kamga.virgile@ihstowers.com","973","22-12-2024 =
16:42:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003910877","M=
vog-Manga","","22-12-2024 15:44:32","22-12-2024 15:32:22","22-12-2024 22:22=
:22","site went down because insufficient of rectifier on site (05)//he add=
ed 2 rectifiers:site on 07 rectifiers but the site still down after power i=
ssue solved since 22:22 and power rest done Tx Lionne st","Albran Byorel","=
Equipment Repair","Passive","Rectifier","Rectifier Module","site went down =
because insufficient of rectifier on site (05)//he added 2 rectifiers:site =
on 07 rectifiers but the site still down after power issue solved since 22:=
22 and power rest done Tx Lionne steeve 655184876 of huawei is informed","a=
lexandre.kamal@ihstowers.com","732","22-12-2024 15:44:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003910557","M=
essa-Carriere OCM","","22-12-2024 14:57:04","22-12-2024 14:49:58","22-12-20=
24 14:55:38","No Power issue on site Ubaie=3D52.1V site  on Grid The TX Fme=
 Mohamadou 691144435 of huawei is informed. ","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No Power issue=
 on site Ubaie=3D52.1V site  on Grid The TX Fme Mohamadou 691144435 of huaw=
ei is informed. ","alexandre.kamal@ihstowers.com","427","22-12-2024 14:57:0=
4","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003910503","NTU=
I TOWN","","22-12-2024 14:47:04","22-12-2024 14:38:52","22-12-2024 15:49:41=
","Grid fluctuation, Site went down because Gen ran untill fuel shotage// R=
efueling Done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid fluctuation, Site went down because Gen ran untill fuel shotage/=
/ Refueling Done","kamga.virgile@ihstowers.com","493","22-12-2024 14:47:04"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0003910276","S=
IMBOCK BONAMBAPE","","22-12-2024 14:08:57","22-12-2024 14:01:44","22-12-202=
4 14:44:10","Grid fluctuation site went down because Gen started and stoppe=
d due to Grid bad voltage // He bypassed Grid and started Gen manualy","Hye=
mafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen started and stopped=
 due to Grid bad voltage // He bypassed Grid and started Gen manualy","step=
hane.nkamwa@ihstowers.com","434","22-12-2024 14:08:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003909102","M=
vog-Manga","","22-12-2024 11:39:02","22-12-2024 11:09:53","22-12-2024 12:22=
:47","Grid fluctuation, Site went down because Gen failed to start due to G=
rid bad bad voltage// Gen started automatically","Albran Byorel","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctu=
ation, Site went down because Gen failed to start due to Grid bad bad volta=
ge// Gen started automatically","stephane.nkamwa@ihstowers.com","1750","22-=
12-2024 11:39:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_332","NOCINC0003909090","NKOMEKUI=
 OCM","","22-12-2024 11:36:34","22-12-2024 10:38:26","22-12-2024 12:57:26",=
"Cascaded Incident from TTO3876141","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue on site Uba=
ie 53V Site on Gen (hybrid site). Telis is on site Charlie 656097386 and Pe=
guy (675990129/Huawei) is informed.","system","271585","22-12-2024 11:36:34=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0003908504","A=
RMP","","22-12-2024 10:07:19","22-12-2024 09:50:08","22-12-2024 13:25:25","=
Active//No power issue on site Ubaie=3D53.3V site on Grid The Tx Fme Elound=
ou/693212405 of huawei is informed.","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue =
on site Ubaie=3D53.3V site on Grid The Tx Fme Eloundou/693212405 of huawei =
is informed.","stephane.nkamwa@ihstowers.com","1032","22-12-2024 10:07:19",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003908046","N=
GONA","","22-12-2024 09:21:03","22-12-2024 09:18:57","22-12-2024 09:20:12",=
"ACTIVE//No power issue  Site is on Grid and Ubaie =3D54.5V The Tx FME Lion=
el Adjep (655184876)from Huawei is informed. ","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE//No power issue  Site is on Grid and Ubaie =3D54.5V The Tx FME Li=
onel Adjep (655184876)from Huawei is informed. ","stephane.nkamwa@ihstowers=
.com","127","22-12-2024 09:21:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003908041","N=
yom OCM","","22-12-2024 09:18:15","22-12-2024 08:22:03","22-12-2024 09:38:3=
7","Grid outage,site went down because Gen stopped with low oil pressure (a=
larm unproven)// he reset the Gen card and manually started","Fabrice Pouak=
am","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage,site went down because Gen stopped with low oil pressure (alarm unprov=
en)// he reset the Gen card and manually started","stephane.nkamwa@ihstower=
s.com","3374","22-12-2024 09:18:15","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003907901","ODZ=
A CITE MBIA","","22-12-2024 08:44:22","22-12-2024 08:06:16","22-12-2024 11:=
09:11","Grid OUTAGE, site went down because gen fails to start due to ATS d=
isfunctionning // Gen manualy started","Albran Byorel","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down becau=
se gen fails to start due to ATS disfunctionning // Gen manualy started","l=
andry.etame@ihstowers.com","2287","22-12-2024 08:44:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0003907537","OLAMA","=
","22-12-2024 07:01:10","22-12-2024 06:48:11","22-12-2024 07:08:31","Cascad=
ed Incident from TTO3874440","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuation, Site went down because Ge=
n fails to start due Gen card disfunction// He reset Gen and started Gen ma=
nualy","system","278134","22-12-2024 07:01:10","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003907526","Ako=
no","IHS_YND_687","22-12-2024 06:57:15","22-12-2024 06:48:11","22-12-2024 0=
7:08:31","Grid fluctuation, Site went down because Gen fails to start due G=
en card disfunction// He reset Gen and started Gen manualy","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid fluctua=
tion, Site went down because Gen fails to start due Gen card disfunction// =
He reset Gen and started Gen manualy","landry.etame@ihstowers.com","545","2=
2-12-2024 06:57:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003907248","O=
dza II","","22-12-2024 06:05:06","22-12-2024 06:02:03","22-12-2024 15:33:53=
","Grid outage, Site went down because Main Gen faulty// A Main Gen has ins=
talled","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Gen=
erator Faulty","Grid outage, Site went down because Main Gen faulty// A Mai=
n Gen has installed","rouselle.schoune@ihstowers.com","186","22-12-2024 06:=
05:06","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003907105","Ako=
no","IHS_YND_687","22-12-2024 05:37:27","22-12-2024 05:34:16","22-12-2024 0=
5:56:50","Grid fluctuation, Site went down because Gen fails to start due G=
en card disfunction// He reset Gen and started Gen manualy","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid fluctua=
tion, Site went down because Gen fails to start due Gen card disfunction// =
He reset Gen and started Gen manualy","ange.kongo@ihstowers.com","192","22-=
12-2024 05:37:27","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003907090","OLA=
MA","","22-12-2024 05:36:10","22-12-2024 05:34:16","22-12-2024 05:56:50",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid fluctuation, Site went down because Gen fails to start due Gen car=
d disfunction// He reset Gen and started Gen manualy","ange.kongo@ihstowers=
.com","268054","22-12-2024 05:36:10","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0003906944","Bon=
djock","","22-12-2024 04:45:57","22-12-2024 04:15:02","22-12-2024 06:06:09"=
,"Site went down because Gen Failed to Start due to PSC3 dysfuntionning// h=
e restart it and Manuallly Started The Gen","Fanda Brice","Equipment Repair=
","Passive","Rectifier","Rectifier Module Overloaded","Site went down becau=
se Gen Failed to Start due to PSC3 dysfuntionning// he restart it and Manua=
llly Started The Gen","ange.kongo@ihstowers.com","1947","22-12-2024 04:45:5=
7","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003905799","F=
ebe Village","","21-12-2024 22:15:45","21-12-2024 22:14:44","21-12-2024 22:=
19:58","ACTIVE//no power issue, site is on Gen THE fme tx  Mohamadou (69114=
4135) from Huawei is informed","Mboua Thierry","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE//no power=
 issue, site is on Gen THE fme tx  Mohamadou (691144135) from Huawei is inf=
ormed","rouselle.schoune@ihstowers.com","62","21-12-2024 22:15:45","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0003905606","A=
bome","","21-12-2024 21:37:34","21-12-2024 21:34:30","21-12-2024 22:39:24",=
"Grid outage,site went down because Gen failed to start due to bad grid vol=
tage, no RCP on site// site on Gen","MINKA NICOLAS","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid outage,site went do=
wn because Gen failed to start due to bad grid voltage, no RCP on site// si=
te on Gen","ludivine.ngamaleu@ihstowers.com","185","21-12-2024 21:37:34","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0003905587","B=
IYEMASSI NIKI","","21-12-2024 21:34:15","21-12-2024 20:18:52","21-12-2024 2=
1:49:38","Site went down due to PWC overloaded (12kva 250 A) // site stabil=
ized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier =
Module Overloaded","Site went down due to PWC overloaded (12kva 250 A) // s=
ite stabilized","ludivine.ngamaleu@ihstowers.com","4524","21-12-2024 21:34:=
15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003905104","SOA VILL=
AGE","","21-12-2024 20:13:00","21-12-2024 20:06:55","21-12-2024 20:47:55","=
Cascaded Incident from TTO3871674","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause gen start and stopped due to grid bad voltage // he bypass grid and m=
anually start the gen","system","1215534","21-12-2024 20:13:00","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003905103","N=
kolo II New","","21-12-2024 20:12:59","21-12-2024 19:52:43","21-12-2024 20:=
58:55","Active, no power issue site on Grid with U=3D54V The FME Tx  Lionel=
 Steve /655184876/ From huawei is informed.","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active, no power issue site on Grid with U=3D54V The FME Tx  Lionel Steve =
/655184876/ From huawei is informed.","ludivine.ngamaleu@ihstowers.com","12=
17","21-12-2024 20:12:59","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003905091","SOA=
 TOWN","IHS_YND_323","21-12-2024 20:12:07","21-12-2024 20:04:55","21-12-202=
4 20:47:55","Grid fluctuation, site went down because gen start and stopped=
 due to grid bad voltage // he bypass grid and manually start the gen","Sil=
igap Boris","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation, site went down because gen start and stopped d=
ue to grid bad voltage // he bypass grid and manually start the gen","kamga=
.virgile@ihstowers.com","553","21-12-2024 20:12:07","Sagemcom CMR"
"Closed Complete","Site Down","T0465","IHS_YND_143","NOCINC0003905075","Bye=
massi Carrefour","","21-12-2024 20:09:49","21-12-2024 19:54:34","22-12-2024=
 08:02:58","site went down duE to CB (125A) dijoncted in the PWC// he reame=
d the CB (125A) (deep investigation ongoing)","Paul BIBOUM","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site=
 went down duE to CB (125A) dijoncted in the PWC// he reamed the CB (125A) =
(deep investigation ongoing)","kamga.virgile@ihstowers.com","916","21-12-20=
24 20:09:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003905010","E=
bogo","","21-12-2024 19:58:09","21-12-2024 19:55:04","21-12-2024 20:41:25",=
"grid fluctuation, site went down because gen fails to start du to grid bad=
 voltage, no rcp on site // site stabilized","Siligap Boris","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","grid fluctuatio=
n, site went down because gen fails to start du to grid bad voltage, no rcp=
 on site // site stabilized","ludivine.ngamaleu@ihstowers.com","186","21-12=
-2024 19:58:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003904975","B=
iyemassi LAC","","21-12-2024 19:50:06","21-12-2024 19:34:52","21-12-2024 19=
:50:09","grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,n=
o space to deploy a mobil gen//grid return","ludivine.ngamaleu@ihstowers.co=
m","915","21-12-2024 19:50:06","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003904959","MIM=
BOMAN LIBERTE","","21-12-2024 19:47:25","21-12-2024 19:38:06","21-12-2024 2=
1:03:54","Grid outage, site went down because main gen faulty //grid return=
","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid outage, site went down because main gen faulty //grid ret=
urn","kamga.virgile@ihstowers.com","560","21-12-2024 19:47:25","Sagemcom CM=
R"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003904948","NKO=
MEKUI OCM","","21-12-2024 19:45:14","21-12-2024 19:33:54","21-12-2024 20:47=
:30","No power issue on site Ubaie: 54,15V site on GEN. Site went down beca=
use is impacted by Mbankolo_camtel and not managing by IHS","TIENTCHEU NZET=
CHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure=
","Affected by 3rd Party Site","No power issue on site Ubaie: 54,15V site o=
n GEN. Site went down because is impacted by Mbankolo_camtel and not managi=
ng by IHS","kamga.virgile@ihstowers.com","681","21-12-2024 19:45:14","Sagem=
com CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003904921","ODZ=
A CITE MBIA","","21-12-2024 19:35:58","21-12-2024 19:20:49","21-12-2024 20:=
45:43","Grid OUTAGE, site went down because gen fails to start due to ATS d=
isfunctionning // Gen manualy started","Albran Byorel","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down becau=
se gen fails to start due to ATS disfunctionning // Gen manualy started","k=
amga.virgile@ihstowers.com","910","21-12-2024 19:35:58","Sagemcom CMR"
"Closed Complete","Site Down","T2795","IHS_YND_070","NOCINC0003904899","Efo=
ulan","","21-12-2024 19:30:55","21-12-2024 18:57:44","21-12-2024 20:08:01",=
"site went down because CB 125A faulty in Pwc//he did a bridge with CB 125A=
(remplacement ongoing)","MINKA NICOLAS","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Circuit Breaker Issue","site went down because C=
B 125A faulty in Pwc//he did a bridge with CB 125A(remplacement ongoing)","=
kamga.virgile@ihstowers.com","1992","21-12-2024 19:30:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003904407","Saa","",=
"21-12-2024 17:49:50","21-12-2024 17:41:42","21-12-2024 18:37:11","Cascaded=
 Incident from TTO3870866","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down because 1/3 rectifier faulty=
//he changed the faulty rectifier","system","267674","21-12-2024 17:49:50",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0003904406","SAA Entr=
ance","","21-12-2024 17:49:50","21-12-2024 17:41:42","21-12-2024 18:37:11",=
"Cascaded Incident from TTO3870866","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because 1/3 rectifi=
er faulty//he changed the faulty rectifier","system","267673","21-12-2024 1=
7:49:50","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0003904402","SAA=
 2","IHS_YND_542, IHS_YND_405","21-12-2024 17:48:54","21-12-2024 17:41:42",=
"21-12-2024 18:37:11","site went down because 1/3 rectifier faulty//he chan=
ged the faulty rectifier","Parker Tchoup","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","site went down because 1/3 rectifier faulty//he=
 changed the faulty rectifier","kamga.virgile@ihstowers.com","432","21-12-2=
024 17:48:54","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003904328","Nsi=
meyong Terre Rouge","","21-12-2024 17:29:04","21-12-2024 17:24:54","21-12-2=
024 17:36:32","GRID OUTAGE, site went down before gen start due to poor bat=
tery backup // gen started","MINKA NICOLAS","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","GRID OUTAGE, site went down be=
fore gen start due to poor battery backup // gen started","kamga.virgile@ih=
stowers.com","250","21-12-2024 17:29:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003904300","T=
amtam Weekend","IHS_YND_166","21-12-2024 17:24:26","21-12-2024 17:17:22","2=
1-12-2024 18:14:12","grid outage,gen stopped with alarm high temp//he added=
 water in radiator","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen=
","ACDG - High Engine Temp - Coolant Level Issue","grid outage,gen stopped =
with alarm high temp//he added water in radiator","ludivine.ngamaleu@ihstow=
ers.com","424","21-12-2024 17:24:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003904292","D=
amas","","21-12-2024 17:21:51","21-12-2024 17:17:22","21-12-2024 18:13:22",=
"","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","grid outage,gen stopped with alarm high temp//he added water in rad=
iator","ludivine.ngamaleu@ihstowers.com","268966","21-12-2024 17:21:51","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003904289","Sap=
eur","","21-12-2024 17:20:49","21-12-2024 17:09:38","21-12-2024 17:27:38","=
GRID OUTAGE, site went down before gen start due to poor battery backup // =
gen started","Mboua Thierry","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","GRID OUTAGE, site went down before gen start =
due to poor battery backup // gen started","kamga.virgile@ihstowers.com","6=
72","21-12-2024 17:20:49","Sagemcom CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0003904170","Clu=
b France","","21-12-2024 17:03:50","21-12-2024 16:54:37","21-12-2024 18:59:=
37","grid outage//grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","grid outage//grid return","kamga.virgile@ihstowe=
rs.com","554","21-12-2024 17:03:50","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0003904140","Nko=
l-Mbanda","","21-12-2024 16:58:48","21-12-2024 16:48:30","21-12-2024 17:34:=
08","site went down because CB 80A who feeds equipment MTN disjuncted in PW=
c//he reamed th CB","MINKA NICOLAS","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Circuit Breaker Issue","site went down because CB 80=
A who feeds equipment MTN disjuncted in PWc//he reamed th CB","kamga.virgil=
e@ihstowers.com","619","21-12-2024 16:58:48","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003904110","Mok=
olo Yaounde","","21-12-2024 16:55:25","21-12-2024 16:47:04","21-12-2024 16:=
57:28","grid outage,no space to deploy a mobil gen//grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no=
 space to deploy a mobil gen//grid return","kamga.virgile@ihstowers.com","5=
03","21-12-2024 16:55:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0003904029","R=
d-Pt-Express","","21-12-2024 16:42:42","21-12-2024 16:38:38","21-12-2024 19=
:36:36","Grid outage, no space to deploy a mobilke gen, //  grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy a mobilke gen, //  grid return","ludivine.ngamale=
u@ihstowers.com","245","21-12-2024 16:42:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003903810","B=
astos Bethesda","","21-12-2024 15:54:25","21-12-2024 15:52:20","21-12-2024 =
16:05:45","GRID OUTAGE, site went down before gen start due to poor battery=
 backup // gen start automatically","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","GRID OUTAGE, site went=
 down before gen start due to poor battery backup // gen start automaticall=
y","ludivine.ngamaleu@ihstowers.com","126","21-12-2024 15:54:25","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003903775","Scalom-I=
HS","","21-12-2024 15:44:30","21-12-2024 15:34:09","21-12-2024 21:43:40","C=
ascaded Incident from TTO3870113","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","access issue during the weekend,grid outage//grid=
 return","system","296862","21-12-2024 15:44:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0003903770","A=
ccacia New","IHS_YND_505","21-12-2024 15:43:14","21-12-2024 15:34:09","21-1=
2-2024 21:51:01","access issue during the weekend,grid outage//grid return"=
,"","Access Denial","Lease Or Legal","Landlord Related Issues","Access Issu=
e - Land Lord","access issue during the weekend,grid outage//grid return","=
ludivine.ngamaleu@ihstowers.com","547","21-12-2024 15:43:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003903763","N=
GONA","","21-12-2024 15:41:00","21-12-2024 15:31:55","21-12-2024 16:42:55",=
"grid outage;gen stopped with alarm high temp//he added water in radiator",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Eng=
ine Temp - Coolant Level Issue","grid outage;gen stopped with alarm high te=
mp//he added water in radiator","ludivine.ngamaleu@ihstowers.com","546","21=
-12-2024 15:41:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003903761","B=
iyemassi LAC","","21-12-2024 15:40:20","21-12-2024 15:27:15","21-12-2024 19=
:00:57","grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,n=
o space to deploy a mobil gen//grid return","dorothy.djantio@ihstowers.com"=
,"787","21-12-2024 15:40:20","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003903700","ODZ=
A MINKAN EDIBI ASSI","","21-12-2024 15:25:12","21-12-2024 15:10:58","21-12-=
2024 15:28:58","grid bad voltage,and gen failed to start,no rcp//bypassed g=
rid and started the gen","Albran Byorel","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","grid bad voltage,and gen failed to =
start,no rcp//bypassed grid and started the gen","kamga.virgile@ihstowers.c=
om","855","21-12-2024 15:25:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003903490","N=
koabang","","21-12-2024 14:53:39","21-12-2024 14:51:30","21-12-2024 19:42:4=
2","Active: No power issue, site is on GRID with U=3D54.9V ,  The TX FME  L=
ionel adjep //655184876//   Huawei is informed","Mba Lazare Herve","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active: No power issue, site is on GRID with U=3D54.9V ,  The TX FME  L=
ionel adjep //655184876//   Huawei is informed","ludivine.ngamaleu@ihstower=
s.com","130","21-12-2024 14:53:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003903467","M=
essa-Carriere OCM","","21-12-2024 14:48:15","21-12-2024 14:39:06","21-12-20=
24 15:57:54","No power issue on site U=3D52,1v site on grid Mohamadou/69114=
4435 of huawei","","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue on site U=3D52,1v site on gri=
d Mohamadou/691144435 of huawei","ludivine.ngamaleu@ihstowers.com","550","2=
1-12-2024 14:48:15","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003903443","N=
yanon","","21-12-2024 14:43:11","21-12-2024 14:34:05","21-12-2024 19:27:36"=
,"No power issue on site U=3D55,1v site on gen Tx fme Gregoire of huawei is=
 informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D55,1v site on gen Tx fme Gregoire of huawei is informed","ludivine.ngama=
leu@ihstowers.com","547","21-12-2024 14:43:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003903304","N=
KOLMEKONG YDE","","21-12-2024 14:17:05","21-12-2024 14:04:57","21-12-2024 1=
4:21:08","Site went down because rectifiers alarming due to PWC disfunction=
// Site stabilized","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down because rectifiers alarmi=
ng due to PWC disfunction// Site stabilized","ludivine.ngamaleu@ihstowers.c=
om","729","21-12-2024 14:17:05","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003903097","MIM=
BOMAN LIBERTE","","21-12-2024 13:41:53","21-12-2024 13:19:49","21-12-2024 1=
4:06:40","Grid Outage Site went down because Main Gen Faulty//MDG 20Kva has=
 deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Generator Faulty","Grid Outage Site went down because Main Gen Faulty//M=
DG 20Kva has deployed","olivier.kwedi@ihstowers.com","1986","21-12-2024 13:=
41:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003903029","N=
KOLMEKONG YDE","","21-12-2024 13:32:48","21-12-2024 13:25:24","21-12-2024 1=
3:42:30","Site went down because due to PWC dysfunctionned// Site stabilize=
d","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","Site went down because due to PWC dysfunctionned// Site s=
tabilized","alexandre.kamal@ihstowers.com","445","21-12-2024 13:32:48","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0003902974","NGONA","=
","21-12-2024 13:32:07","21-12-2024 13:11:37","21-12-2024 13:41:19","Cascad=
ed Incident from TTO3868892","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n fails to start due to card ge disfunction // he bypass it and manually st=
art the gen","system","269575","21-12-2024 13:32:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0003902975","Nkoabang=
2","","21-12-2024 13:32:07","21-12-2024 13:11:37","21-12-2024 13:41:19","Ca=
scaded Incident from TTO3868892","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen fails to start due to card ge disfunction // he bypass it and manuall=
y start the gen","system","269574","21-12-2024 13:32:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_736","NOCINC0003902976","CRF Nkoa=
bang","","21-12-2024 13:32:07","21-12-2024 13:11:37","21-12-2024 13:41:19",=
"Cascaded Incident from TTO3868892","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause gen fails to start due to card ge disfunction // he bypass it and manu=
ally start the gen","system","269575","21-12-2024 13:32:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003902819","N=
koabang","IHS_YND_295, IHS_YND_526, IHS_YND_736","21-12-2024 13:16:50","21-=
12-2024 13:11:37","21-12-2024 13:41:19","Grid outage, site went down becaus=
e gen fails to start due to card ge disfunction // he bypass it and manuall=
y start the gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage, site went down because gen fails to s=
tart due to card ge disfunction // he bypass it and manually start the gen"=
,"alexandre.kamal@ihstowers.com","314","21-12-2024 13:16:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0003902649","B=
IYEMASSI NIKI","","21-12-2024 12:39:42","21-12-2024 12:08:20","21-12-2024 1=
4:33:24","Site went down due to PWC overloaded (12kw 250 A) // He reduiced =
the load","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectif=
ier Module Overloaded","Site went down due to PWC overloaded (12kw 250 A) /=
/ He reduiced the load","alexandre.kamal@ihstowers.com","1883","21-12-2024 =
12:39:42","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003902064","Mok=
olo Yaounde","","21-12-2024 11:57:22","21-12-2024 11:51:12","21-12-2024 12:=
12:54","Grid outage.no space to deploy mobile gen//Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deploy mobile gen//Grid return","olivier.kwedi@ihstowers.com","371=
","21-12-2024 11:57:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003901940","B=
astos Bethesda","","21-12-2024 11:54:43","21-12-2024 11:50:36","21-12-2024 =
11:55:34","Grid outage, site went down before gen start due to poor battery=
 backup // gen start automatically","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // gen start automaticall=
y","alexandre.kamal@ihstowers.com","249","21-12-2024 11:54:43","Sagemcom CM=
R"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003901928","Sap=
eur","","21-12-2024 11:54:01","21-12-2024 11:51:20","21-12-2024 12:11:40","=
Grid outage, site went down before gen start due to poor battery backup // =
Grid return","Mboua Thierry","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, site went down before gen start =
due to poor battery backup // Grid return","olivier.kwedi@ihstowers.com","3=
08","21-12-2024 11:54:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0003901865","Omnispor=
t-Rail","","21-12-2024 11:49:00","21-12-2024 11:37:57","21-12-2024 12:14:46=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen started automatically","Delor Telezing","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down before gen =
start due to poor battery backup // Gen started automatically","system","12=
17406","21-12-2024 11:49:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003901858","M=
ANGUIERS CHAPELLE","IHS_YND_506","21-12-2024 11:47:15","21-12-2024 11:37:57=
","21-12-2024 12:14:46","Grid outage, site went down before gen start due t=
o poor battery backup // Gen started automatically","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 outage, site went down before gen start due to poor battery backup // Gen =
started automatically","alexandre.kamal@ihstowers.com","559","21-12-2024 11=
:47:15","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003901788","Ema=
na","","21-12-2024 11:39:01","21-12-2024 11:34:47","21-12-2024 11:46:19","G=
rid outage, site went down before gen start due to poor battery backup // G=
rid return","Fabrice Pouakam","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, site went down before gen start=
 due to poor battery backup // Grid return","olivier.kwedi@ihstowers.com","=
255","21-12-2024 11:39:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003901747","M=
arche Odza","","21-12-2024 11:30:11","21-12-2024 11:24:07","21-12-2024 12:4=
9:15","Grid outage site went down because Gen failed to start due to relay =
220 v faulty // He replaced relay 220v faulty and Gen manually started","Al=
bran Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","=
Grid outage site went down because Gen failed to start due to relay 220 v f=
aulty // He replaced relay 220v faulty and Gen manually started","alexandre=
.kamal@ihstowers.com","365","21-12-2024 11:30:11","Sagemcom CMR"
"Closed Complete","Warning","CTR_005","IHS_YND_374","NOCINC0003901712","Mat=
omb","","21-12-2024 11:23:06","","","site went on battery due to Grid Bad V=
oltage on Site //he bypass the Grid and Manually Started the Gen","Kemeni F=
ranklin","Warning","Warning","POWER","Warning - Site on Battery","site went=
 on battery due to Grid Bad Voltage on Site //he bypass the Grid and Manual=
ly Started the Gen","dorothy.djantio@ihstowers.com","185","21-12-2024 11:23=
:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003901624","Saa","",=
"21-12-2024 11:02:30","21-12-2024 10:55:56","21-12-2024 11:46:55","Cascaded=
 Incident from TTO3867624","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because 1/3 rectifier went f=
aulty// He replaced rectifier faulty site on grid ","system","277455","21-1=
2-2024 11:02:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0003901623","SAA Entr=
ance","","21-12-2024 11:02:30","21-12-2024 10:55:56","21-12-2024 11:46:55",=
"Cascaded Incident from TTO3867624","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because 1/3 rectifi=
er went faulty// He replaced rectifier faulty site on grid ","system","2774=
55","21-12-2024 11:02:30","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0003901595","SAA=
 2","IHS_YND_542, IHS_YND_405","21-12-2024 11:01:06","21-12-2024 10:55:56",=
"21-12-2024 11:46:55","Site went down because 1/3 rectifier went faulty// H=
e replaced rectifier faulty site on grid ","Parker Tchoup","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Site went down =
because 1/3 rectifier went faulty// He replaced rectifier faulty site on gr=
id ","olivier.kwedi@ihstowers.com","311","21-12-2024 11:01:06","Sagemcom CM=
R"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003901468","ODZ=
A CITE MBIA","","21-12-2024 10:42:22","21-12-2024 10:32:07","21-12-2024 12:=
16:04","Grid outage, site went down because gen fails to start due to ATS d=
isfunctionning // Gen manualy started","Albran Byorel","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid outage, site went down becau=
se gen fails to start due to ATS disfunctionning // Gen manualy started","o=
livier.kwedi@ihstowers.com","616","21-12-2024 10:42:22","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003901460","NKO=
MEKUI OCM","","21-12-2024 10:40:24","21-12-2024 10:31:56","21-12-2024 11:04=
:37","No power issue on site Ubaie: 54,15V site on GEN. Site went down beca=
use is impacted by Mbankolo_camtel and not managing by IHS.","TIENTCHEU NZE=
TCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","No power issue on site Ubaie: 54,15V site on GEN. =
Site went down because is impacted by Mbankolo_camtel and not managing by I=
HS.","olivier.kwedi@ihstowers.com","509","21-12-2024 10:40:24","Sagemcom CM=
R"
"Cancelled","Warning","T2149","IHS_EDA_056","NOCINC0003901336","Ndogbessol"=
,"","21-12-2024 10:23:11","","","site on battery","Kemeni Franklin","","","=
","","","dorothy.djantio@ihstowers.com","152","21-12-2024 10:23:11","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0003901275","E=
vodoula OCM","","21-12-2024 10:19:49","21-12-2024 10:11:12","21-12-2024 10:=
15:20","Active//No power issue, site on Gen U=3D52,9V, TX FME Mohamadou/691=
144435 from huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue, site on Gen U=3D52,9V, TX FME Mohamadou/691144435 from =
huawei is informed","alexandre.kamal@ihstowers.com","518","21-12-2024 10:19=
:49","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003901175","Elo=
umdem stade","","21-12-2024 09:44:14","21-12-2024 09:37:04","21-12-2024 09:=
55:08","Grid fluctuation, site went because gen start and stopped due to gr=
id bad voltage, no rcp on site // he bypass grid and manually start the gen=
","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid fluctuation, site went because gen start and stopped du=
e to grid bad voltage, no rcp on site // he bypass grid and manually start =
the gen","olivier.kwedi@ihstowers.com","431","21-12-2024 09:44:14","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003901100","O=
dza II","","21-12-2024 09:26:10","21-12-2024 09:20:01","21-12-2024 19:22:20=
","grid outage, site went down because Main Gen faulty,// Grid return","Alb=
ran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fault=
y","grid outage, site went down because Main Gen faulty,// Grid return","al=
exandre.kamal@ihstowers.com","371","21-12-2024 09:26:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003900959","Nkolo II=
 New","","21-12-2024 09:00:01","21-12-2024 08:54:12","21-12-2024 10:16:58",=
"Cascaded Incident from TTO3866903","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bec=
ause PWC ZTE dysfunctionning// He reset PWC and started Gen manualy","syste=
m","270605","21-12-2024 09:00:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003900958","M=
imboman-Village","IHS_YND_709","21-12-2024 08:59:16","21-12-2024 08:54:12",=
"21-12-2024 10:16:58","Grid outage, Site went down because PWC ZTE dysfunct=
ionning// He reset PWC and started Gen manualy","Mba Lazare Herve","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage=
, Site went down because PWC ZTE dysfunctionning// He reset PWC and started=
 Gen manualy","alexandre.kamal@ihstowers.com","305","21-12-2024 08:59:16","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003900936","Ngoum","=
","21-12-2024 08:55:10","21-12-2024 08:46:25","21-12-2024 08:49:41","Cascad=
ed Incident from TTO3866865","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site U=3D51v site on gen T=
x Gregoire of huawei is informed and Up at 08:49 AM","system","271099","21-=
12-2024 08:55:10","Sagemcom CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0003900923","Don=
g","IHS_YND_475, IHS_YND_473","21-12-2024 08:53:34","21-12-2024 08:46:25","=
21-12-2024 10:11:41","No power issue on site U=3D51v site on gen Tx Gregoir=
e of huawei is informed and Up at 08:49 AM","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site U=3D51v site on gen Tx Gregoire of huawei is informed a=
nd Up at 08:49 AM","olivier.kwedi@ihstowers.com","430","21-12-2024 08:53:34=
","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003900329","MIM=
BOMAN LIBERTE","","21-12-2024 06:59:46","21-12-2024 06:55:41","21-12-2024 0=
9:18:19","Grid outage, Site went down because Main Gen faulty// He deployed=
 MDG of 20Kva","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage, Site went down because Main Gen faul=
ty// He deployed MDG of 20Kva","olivier.kwedi@ihstowers.com","246","21-12-2=
024 06:59:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003900274","N=
koabang2","","21-12-2024 06:50:32","21-12-2024 06:43:27","21-12-2024 07:32:=
24","Grid outage, Site went down due to Gen overload (22kva, 300A)// He red=
uiced load and started Gen manualy","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to G=
en overload (22kva, 300A)// He reduiced load and started Gen manualy","alex=
andre.kamal@ihstowers.com","426","21-12-2024 06:50:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0003899603","S=
calom","","21-12-2024 03:34:03","21-12-2024 03:27:59","21-12-2024 05:20:59"=
,"No power issue , Ubaie=3D54.5 V site on Grid.The FME TX Mbah Hosiah //674=
007438//  from huawei is informed.","Paul BIBOUM","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e , Ubaie=3D54.5 V site on Grid.The FME TX Mbah Hosiah //674007438//  from =
huawei is informed.","emmanuel.ghani@ihstowers.com","365","21-12-2024 03:34=
:03","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003899599","Nsi=
meyong Shell","","21-12-2024 03:30:54","21-12-2024 03:28:40","21-12-2024 04=
:34:40","Grid fluctuation, site went because gen start and stopped due to g=
rid bad voltage, no rcp on site // he bypass grid and manually start the ge=
n","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation, site went because gen start and stopped=
 due to grid bad voltage, no rcp on site // he bypass grid and manually sta=
rt the gen","christian.fonkou@ihstowers.com","135","21-12-2024 03:30:54","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0003899598","S=
hell-Nsimeyong","","21-12-2024 03:30:36","21-12-2024 03:28:30","21-12-2024 =
04:29:40","Grid fluctuation, site went because gen start and stopped due to=
 grid bad voltage, no rcp on site // he bypass grid and manually start the =
gen","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid fluctuation, site went because gen start and stopp=
ed due to grid bad voltage, no rcp on site // he bypass grid and manually s=
tart the gen","emmanuel.ghani@ihstowers.com","127","21-12-2024 03:30:36","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0003899331","NGONA","=
","21-12-2024 02:10:01","21-12-2024 02:05:43","21-12-2024 04:00:43","Cascad=
ed Incident from TTO3865059","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se gen fails to start due to card ge disfunction // he bypass it and manual=
ly start the gen","system","273409","21-12-2024 02:10:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0003899332","Nkoabang=
2","","21-12-2024 02:10:01","21-12-2024 02:05:43","21-12-2024 04:00:43","Ca=
scaded Incident from TTO3865059","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause gen fails to start due to card ge disfunction // he bypass it and ma=
nually start the gen","system","273409","21-12-2024 02:10:01","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_736","NOCINC0003899333","CRF Nkoa=
bang","","21-12-2024 02:10:01","21-12-2024 02:05:43","21-12-2024 04:00:43",=
"Cascaded Incident from TTO3865059","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation, site went dow=
n because gen fails to start due to card ge disfunction // he bypass it and=
 manually start the gen","system","273410","21-12-2024 02:10:01","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003899326","N=
koabang","IHS_YND_295, IHS_YND_526, IHS_YND_736","21-12-2024 02:07:52","21-=
12-2024 02:05:43","21-12-2024 04:00:43","Grid fluctuation, site went down b=
ecause gen fails to start due to card ge disfunction // he bypass it and ma=
nually start the gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid fluctuation, site went down because gen =
fails to start due to card ge disfunction // he bypass it and manually star=
t the gen","emmanuel.ghani@ihstowers.com","130","21-12-2024 02:07:52","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003899243","T=
singa","","21-12-2024 01:24:38","21-12-2024 01:24:33","21-12-2024 01:48:33"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ gen start automatically","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen start automatically","emman=
uel.ghani@ihstowers.com","7","21-12-2024 01:24:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003899039","M=
IMBOMAN LIBERTE","","20-12-2024 23:58:08","20-12-2024 23:56:59","21-12-2024=
 01:50:39","Grid outage, Site went down because Main Gen faulty // MDG 20KV=
a has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Generator Faulty","Grid outage, Site went down because Main Gen fau=
lty // MDG 20KVa has deployed","emmanuel.ghani@ihstowers.com","264","20-12-=
2024 23:58:08","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0003898550","Mon=
tee-Jouvence-II","","20-12-2024 22:37:26","20-12-2024 22:35:21","20-12-2024=
 23:38:21","site went down due to PWC over load(12KW.280A) and causing disj=
unction at BTS MTN // Site stabilized and CB BTS rearmed","Hyemafo Gildas",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","sit=
e went down due to PWC over load(12KW.280A) and causing disjunction at BTS =
MTN // Site stabilized and CB BTS rearmed","christian.fonkou@ihstowers.com"=
,"126","20-12-2024 22:37:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0003898065","A=
bome","","20-12-2024 21:18:38","20-12-2024 21:09:59","20-12-2024 21:23:35",=
"site went down because gen failed to start due to grid bad voltage // Gen =
manually started","MINKA NICOLAS","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","site went down because gen failed to start=
 due to grid bad voltage // Gen manually started","rouselle.schoune@ihstowe=
rs.com","521","20-12-2024 21:18:38","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003897851","NKO=
MEKUI OCM","","20-12-2024 20:35:53","20-12-2024 20:31:47","20-12-2024 21:34=
:04","no power issue on site U=3D50,7  V site on Gen.site impacted by Mbank=
olo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","Affected by 3rd Party=
 Site","no power issue on site U=3D50,7  V site on Gen.site impacted by Mba=
nkolo Camtel and not managing by IHS","ange.kongo@ihstowers.com","247","20-=
12-2024 20:35:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003897639","Emana ly=
cee 2","","20-12-2024 20:03:41","20-12-2024 19:57:25","20-12-2024 21:56:38"=
,"Cascaded Incident from TTO3863085","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down due to disjuncti=
on of Cb(80A) in PWC // He reamed Cb(80A), grid return","system","274046","=
20-12-2024 20:03:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003897638","EMANA BI=
LICK CITY","","20-12-2024 20:03:40","20-12-2024 19:57:25","20-12-2024 21:56=
:38","Cascaded Incident from TTO3863085","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site went down due to disju=
nction of Cb(80A) in PWC // He reamed Cb(80A), grid return","system","27404=
6","20-12-2024 20:03:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003897627","Emana Ly=
cee","","20-12-2024 20:01:51","20-12-2024 19:57:25","20-12-2024 21:56:38","=
Cascaded Incident from TTO3863085","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down due to disjunction=
 of Cb(80A) in PWC // He reamed Cb(80A), grid return","system","274047","20=
-12-2024 20:01:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003897628","Messassi=
 okolo","","20-12-2024 20:01:51","20-12-2024 19:57:25","20-12-2024 21:56:38=
","Cascaded Incident from TTO3863085","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down due to disjunct=
ion of Cb(80A) in PWC // He reamed Cb(80A), grid return","system","274047",=
"20-12-2024 20:01:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003897626","Mballa 4=
","","20-12-2024 20:01:50","20-12-2024 19:57:25","20-12-2024 21:56:38","Cas=
caded Incident from TTO3863085","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site went down due to disjunction of =
Cb(80A) in PWC // He reamed Cb(80A), grid return","system","274045","20-12-=
2024 20:01:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003897608","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","20=
-12-2024 20:00:30","20-12-2024 19:57:25","20-12-2024 21:56:38","site went d=
own due to disjunction of Cb(80A) in PWC // He reamed Cb(80A), grid return"=
,"Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Circuit Breaker Issue","site went down due to disjunction of Cb(80A) =
in PWC // He reamed Cb(80A), grid return","rouselle.schoune@ihstowers.com",=
"187","20-12-2024 20:00:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003897563","N=
yom OCM","","20-12-2024 19:53:51","20-12-2024 19:48:46","20-12-2024 20:01:3=
3","grid outage,gen stopped with alarm low oil pressure(not unproven)//he r=
eset the card and started the gen","Fabrice Pouakam","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","grid outage,gen stopped with alar=
m low oil pressure(not unproven)//he reset the card and started the gen","r=
ouselle.schoune@ihstowers.com","306","20-12-2024 19:53:51","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003897541","Elo=
umdem stade","","20-12-2024 19:48:50","20-12-2024 19:27:38","20-12-2024 19:=
55:34","grid bad voltage,and gen failed to start//bypassed grid and started=
 the gen","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","grid bad voltage,and gen failed to start//bypassed g=
rid and started the gen","ange.kongo@ihstowers.com","1273","20-12-2024 19:4=
8:50","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003897537","Nko=
abang Ebolmedjock","","20-12-2024 19:47:22","20-12-2024 19:22:05","21-12-20=
24 01:10:52","no power issue U:54,V site on Grid. TX FME Leonel Steve (6551=
84876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power iss=
ue U:54,V site on Grid. TX FME Leonel Steve (655184876) from Huawei is info=
rmed","ange.kongo@ihstowers.com","1518","20-12-2024 19:47:22","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0003897529","S=
OA TOWN","","20-12-2024 19:45:54","20-12-2024 19:40:50","20-12-2024 20:49:5=
2","grid bad voltage,and gen failed to start//bypassed grid and started the=
 gen","Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","grid bad voltage,and gen failed to start//bypassed gri=
d and started the gen","rouselle.schoune@ihstowers.com","305","20-12-2024 1=
9:45:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003896705","O=
mnisport-Rail","","20-12-2024 18:37:48","20-12-2024 18:00:42","20-12-2024 2=
0:00:42","No power issue on site U=3D54v site on grid Tx fme Armand of huaw=
ei is informed","Delor Telezing","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v=
 site on grid Tx fme Armand of huawei is informed","rouselle.schoune@ihstow=
ers.com","2227","20-12-2024 18:37:48","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003896530","MBI=
MBIM","","20-12-2024 18:18:50","20-12-2024 18:09:59","20-12-2024 19:27:41",=
"site went down before gen start due to poor battery backup // Gen started"=
,"Parker Tchoup","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Battery Low","site went down before gen start due to poor battery backu=
p // Gen started","ange.kongo@ihstowers.com","532","20-12-2024 18:18:50","S=
agemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003896399","MAN=
GUIERS CHAPELLE","","20-12-2024 18:06:41","20-12-2024 18:01:15","20-12-2024=
 19:02:08","grid outage, site went down because gen start and stoppen with =
alarm over frequency // He reset gen card and started Gen manually","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
grid outage, site went down because gen start and stoppen with alarm over f=
requency // He reset gen card and started Gen manually","ange.kongo@ihstowe=
rs.com","1987","20-12-2024 18:06:41","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003896379","Ema=
na","","20-12-2024 18:02:55","20-12-2024 17:59:47","20-12-2024 18:11:31","G=
rid outage, site went down before Gen start due to poor battery backup // G=
en start automatically","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re Gen start due to poor battery backup // Gen start automatically","ange.k=
ongo@ihstowers.com","189","20-12-2024 18:02:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003896349","E=
bogo","","20-12-2024 17:55:33","20-12-2024 17:54:28","20-12-2024 20:46:28",=
"grid bad voltage,and gen failed to start,no rcp//bypassed grid and started=
 the gen","Siligap Boris","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","grid bad voltage,and gen failed to start,no rcp//b=
ypassed grid and started the gen","rouselle.schoune@ihstowers.com","66","20=
-12-2024 17:55:33","Sagemcom CMR"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0003896343","COR=
NIERS","","20-12-2024 17:53:04","20-12-2024 17:46:53","20-12-2024 20:54:39"=
,"Grid outage, No space to deploy MDG// Grid return. Power issues resolved =
since 08:54 PM (Site still down after the power reset) The FME tx Armand Ng=
etsa/691144412/ From Huawei is informed","","Grid Supply","Passive","Grid",=
"National Grid - Grid Outage Issue","Grid outage, No space to deploy MDG// =
Grid return. Power issues resolved since 08:54 PM (Site still down after th=
e power reset) The FME tx Armand Ngetsa/691144412/ From Huawei is informed"=
,"ange.kongo@ihstowers.com","372","20-12-2024 17:53:04","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003896330","ODZ=
A MINKAN EDIBI ASSI","","20-12-2024 17:48:45","20-12-2024 17:38:59","20-12-=
2024 19:22:58","grid bad voltage,and gen failed to start,no rcp//bypassed g=
rid and started the gen","Albran Byorel","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","grid bad voltage,and gen failed to =
start,no rcp//bypassed grid and started the gen","ange.kongo@ihstowers.com"=
,"587","20-12-2024 17:48:45","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003896128","Nsi=
meyong Terre Rouge","","20-12-2024 17:02:40","20-12-2024 16:59:28","20-12-2=
024 17:11:24","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen started automatically","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen started auto=
matically","ange.kongo@ihstowers.com","193","20-12-2024 17:02:40","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0003896115","E=
toug ebe Meweulo","","20-12-2024 16:57:25","20-12-2024 16:54:20","20-12-202=
4 18:58:07","grid bad voltage,and gen failed to start//grid bypassed and st=
arted the gen","Hyemafo Gildas","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","grid bad voltage,and gen failed to start//gr=
id bypassed and started the gen","rouselle.schoune@ihstowers.com","186","20=
-12-2024 16:57:25","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003895733","Nsi=
meyong Shell","","20-12-2024 15:52:36","20-12-2024 15:48:27","20-12-2024 16=
:02:27","grid outage,gen failed to start due to grid bad voltage and lack o=
f one phase//bypassed grid and started the gen","MINKA NICOLAS","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","grid outage,=
gen failed to start due to grid bad voltage and lack of one phase//bypassed=
 grid and started the gen","ange.kongo@ihstowers.com","250","20-12-2024 15:=
52:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0003895726","S=
calom","","20-12-2024 15:51:02","20-12-2024 15:48:58","20-12-2024 19:10:58"=
,"No power issue on site U=3D53v site on grid Tx fme Mbah Hosiah of huawei =
is informed","Paul BIBOUM","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53v site =
on grid Tx fme Mbah Hosiah of huawei is informed","rouselle.schoune@ihstowe=
rs.com","125","20-12-2024 15:51:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0003895724","S=
hell-Nsimeyong","","20-12-2024 15:50:23","20-12-2024 15:48:18","20-12-2024 =
15:57:18","grid outage,gen failed to start due to grid bad voltage and lack=
 of one phase//bypassed grid and started the gen","MINKA NICOLAS","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","grid outag=
e,gen failed to start due to grid bad voltage and lack of one phase//bypass=
ed grid and started the gen","rouselle.schoune@ihstowers.com","126","20-12-=
2024 15:50:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003895691","N=
KOLMEKONG YDE","","20-12-2024 15:43:27","20-12-2024 15:35:19","20-12-2024 1=
5:50:30","Site went down because rectifiers alarming due to PWC disfunction=
// Site stabilized","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down because rectifiers alarmi=
ng due to PWC disfunction// Site stabilized","rouselle.schoune@ihstowers.co=
m","489","20-12-2024 15:43:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003894766","N=
KOLMEKONG YDE","","20-12-2024 13:08:39","20-12-2024 12:56:21","20-12-2024 1=
3:12:15","Site went down because rectifiers alarming due to PWC disfunction=
// Site stabilized","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down because rectifiers alarmi=
ng due to PWC disfunction// Site stabilized","olivier.kwedi@ihstowers.com",=
"739","20-12-2024 13:08:39","Sagemcom CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0003894622","Mvo=
g-Ada_OCM","","20-12-2024 12:38:14","20-12-2024 12:30:18","20-12-2024 20:50=
:49","Grid outage,no space to deploy a mobile DG//grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no s=
pace to deploy a mobile DG//grid return","dorothy.djantio@ihstowers.com","4=
752","20-12-2024 12:38:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003894537","Crf-Mban=
kolo-IHS","","20-12-2024 12:23:21","20-12-2024 12:13:32","20-12-2024 13:01:=
38","Cascaded Incident from TTO3859602","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage,gen failed to star=
t due to Grid contactor faulty//We bypass grid contactor and Gen manually s=
tarted","system","272852","20-12-2024 12:23:21","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003894517","Jea=
n Vespa","IHS_YND_574","20-12-2024 12:19:39","20-12-2024 12:13:32","20-12-2=
024 13:01:38","grid outage,gen failed to start due to Grid contactor faulty=
//We bypass grid contactor and Gen manually started","Mboua Thierry","Equip=
ment Repair","Passive","Control Panel","ATS-AMF Issue","grid outage,gen fai=
led to start due to Grid contactor faulty//We bypass grid contactor and Gen=
 manually started","dorothy.djantio@ihstowers.com","368","20-12-2024 12:19:=
39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_096","NOCINC0003894513","Mobil-Ko=
ndengui","","20-12-2024 12:17:20","20-12-2024 12:08:45","20-12-2024 12:54:3=
9","Wrong ticket","","Incorrectly Logged Tickets","Error","Error","Error","=
Grid outage, site went down because Gen failed to start due to Grid contact=
or faulty // he blocked the Grid contactor manually. site on Gen","system",=
"515","20-12-2024 12:17:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003894506","J=
-Vespa","","20-12-2024 12:16:03","20-12-2024 12:08:45","20-12-2024 12:54:39=
","Grid outage, site went down because Gen failed to start due to Grid cont=
actor faulty // he blocked the Grid contactor manually. site on Gen","Mboua=
 Thierry","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gri=
d outage, site went down because Gen failed to start due to Grid contactor =
faulty // he blocked the Grid contactor manually. site on Gen","olivier.kwe=
di@ihstowers.com","438","20-12-2024 12:16:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0003894486","A=
v-Germaine","","20-12-2024 12:10:34","20-12-2024 12:04:25","20-12-2024 20:4=
9:38","Grid outage,no space to deploy a mobile DG//grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no =
space to deploy a mobile DG//grid return","olivier.kwedi@ihstowers.com","37=
0","20-12-2024 12:10:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003894281","Nkolbiss=
on usines des eaux 2","","20-12-2024 11:40:21","20-12-2024 11:33:13","20-12=
-2024 11:40:20","Cascaded Incident from TTO3859331","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, Site went down before Gen start due to poor backup// Grid power retur=
n","system","268277","20-12-2024 11:40:21","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003894267","Nko=
lbisson","IHS_YND_763","20-12-2024 11:38:20","20-12-2024 11:33:13","20-12-2=
024 11:40:20","Grid outage, Site went down before Gen start due to poor bac=
kup// Grid power return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down before Gen start due to poor backup// Grid power return","dorothy.dja=
ntio@ihstowers.com","308","20-12-2024 11:38:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003894257","N=
KOLMEKONG YDE","","20-12-2024 11:36:49","20-12-2024 11:28:41","20-12-2024 1=
1:42:58","Site went down because due to PWC disfunction// Site stabilized",=
"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e Overloaded","Site went down because due to PWC disfunction// Site stabili=
zed","olivier.kwedi@ihstowers.com","489","20-12-2024 11:36:49","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0003893962","Dagobert=
","","20-12-2024 10:46:51","20-12-2024 10:25:40","20-12-2024 10:29:13","Cas=
caded Incident from TTO3858856","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","TX Issue","system","272423","2=
0-12-2024 10:46:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_223","NOCINC0003893964","Febe Vil=
lage","","20-12-2024 10:46:51","20-12-2024 10:25:40","20-12-2024 10:29:13",=
"Cascaded Incident from TTO3858856","Mboua Thierry","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","TX Issue","system","272423","20-12-20=
24 10:46:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0003893959","Leboudi"=
,"","20-12-2024 10:46:50","20-12-2024 10:25:40","20-12-2024 10:29:13","Casc=
aded Incident from TTO3858856","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","TX Issue","system","272426","20=
-12-2024 10:46:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_804","NOCINC0003893960","BEATITUD=
E ENTR=C9E PAVE","","20-12-2024 10:46:50","20-12-2024 10:25:40","20-12-2024=
 10:29:13","Cascaded Incident from TTO3858856","TIENTCHEU NZETCHIEU GAEL","=
Cascade Outage","Active","Cascade Active","Cascade Active","TX Issue","syst=
em","272427","20-12-2024 10:46:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_237","NOCINC0003893961","Carrefou=
r Simbock","","20-12-2024 10:46:50","20-12-2024 10:25:40","20-12-2024 10:29=
:13","Cascaded Incident from TTO3858856","Hyemafo Gildas","Cascade Outage",=
"Active","Cascade Active","Cascade Active","TX Issue","system","272428","20=
-12-2024 10:46:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_262","NOCINC0003893925","Mendong3=
","","20-12-2024 10:40:42","20-12-2024 10:25:40","20-12-2024 10:29:13","Cas=
caded Incident from TTO3858856","","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","TX Issue","system","272426","20-12-2024 10:40:42","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0003893924","Tamtam W=
eekend","","20-12-2024 10:40:42","20-12-2024 10:25:40","20-12-2024 10:29:13=
","Cascaded Incident from TTO3858856","Hyemafo Gildas","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","TX Issue","system","272425","20-12=
-2024 10:40:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_333","NOCINC0003893921","Mfou MTN=
","","20-12-2024 10:40:41","20-12-2024 10:25:40","20-12-2024 10:29:13","Cas=
caded Incident from TTO3858856","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","TX Issue","system","272424","20-12-202=
4 10:40:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_748","NOCINC0003893920","Nkoabang=
 Alembe","","20-12-2024 10:40:41","20-12-2024 10:25:40","20-12-2024 10:29:1=
3","Cascaded Incident from TTO3858856","Mba Lazare Herve","Cascade Outage",=
"Active","Cascade Active","Cascade Active","TX Issue","system","272427","20=
-12-2024 10:40:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_569","NOCINC0003893922","Mendong =
Maeture","","20-12-2024 10:40:41","20-12-2024 10:25:40","20-12-2024 10:29:1=
3","Cascaded Incident from TTO3858856","Hyemafo Gildas","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","TX Issue","system","272424","20-1=
2-2024 10:40:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0003893923","Mfou EPC=
","","20-12-2024 10:40:41","20-12-2024 10:25:40","20-12-2024 10:29:13","Cas=
caded Incident from TTO3858856","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","TX Issue","system","272425","20-12-202=
4 10:40:41","Sagemcom CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0003893870","Men=
dong Plateau","IHS_YND_748, IHS_YND_309, IHS_YND_333, IHS_YND_569, IHS_YND_=
674, IHS_YND_804, IHS_YND_237, IHS_YND_286, IHS_YND_315, IHS_YND_151, IHS_Y=
ND_223, IHS_YND_271, IHS_YND_262","20-12-2024 10:33:51","20-12-2024 10:25:4=
0","20-12-2024 10:29:13","No power issue site on grid with U=3D50.7v Mbah O=
siah(674007438) from Huaweio is informed ","Hyemafo Gildas","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue site on grid with U=3D50.7v Mbah Osiah(674007438) from Huaweio =
is informed ","dorothy.djantio@ihstowers.com","492","20-12-2024 10:33:51","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0003893861","B=
IYEMASSI NIKI","","20-12-2024 10:33:05","20-12-2024 10:24:59","20-12-2024 1=
0:30:36","No power issue site on grid with U=3D54.5v Mbah OSIAH From Huawei=
 is informed","Hyemafo Gildas","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with=
 U=3D54.5v Mbah OSIAH From Huawei is informed
","olivier.kwedi@ihstowers.com","487","20-12-2024 10:33:05","Sagemcom CMR"
"Closed Complete","Site Down","T0107","IHS_YND_271","NOCINC0003893838","Yon=
a Hotel","","20-12-2024 10:30:54","20-12-2024 10:25:40","20-12-2024 10:29:1=
3","please casscade this site behind Medong plateau","TIENTCHEU NZETCHIEU G=
AEL","Cascade Outage","Active","Cascade Active","Cascade Active","No power =
issue site on grid with U=3D50.7v Mbah Osiah(674007438) from Huaweio is inf=
ormed ","dorothy.djantio@ihstowers.com","272422","20-12-2024 10:30:54","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003893828","O=
dza II OCM","","20-12-2024 10:29:53","20-12-2024 10:10:30","20-12-2024 10:4=
8:23","No power issue, site is on grid with Ubaie=3D53V, Lionel adjep(65518=
4876) from Huawei is informed and Up at 10:48  AM","Albran Byorel","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue, site is on grid with Ubaie=3D53V, Lionel adjep(65518487=
6) from Huawei is informed and Up at 10:48  AM","olivier.kwedi@ihstowers.co=
m","1165","20-12-2024 10:29:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003893744","S=
calom-IHS","","20-12-2024 10:21:18","20-12-2024 10:08:18","20-12-2024 10:57=
:37","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid outage//Grid return","olivier.kwedi@ihstowers.com","1222973","20-12-20=
24 10:21:18","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0003893741","Acc=
acia New","IHS_YND_505","20-12-2024 10:20:22","20-12-2024 10:01:16","20-12-=
2024 11:07:38","Grid outage//Grid return","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid outage//Grid return","dorothy.dj=
antio@ihstowers.com","1148","20-12-2024 10:20:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0003893506","E=
foulan","","20-12-2024 10:02:57","20-12-2024 09:20:47","20-12-2024 11:03:24=
","site went down due to CB 125A who feed equipment OCM disjuncted in PWC//=
/he Made the Bridge with (63 A) and Site is on Grid","MINKA NICOLAS","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Iss=
ue","site went down due to CB 125A who feed equipment OCM disjuncted in PWC=
///he Made the Bridge with (63 A) and Site is on Grid","olivier.kwedi@ihsto=
wers.com","2531","20-12-2024 10:02:57","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0003893316","Beh=
ind P T school Yde","","20-12-2024 09:52:52","20-12-2024 09:32:48","20-12-2=
024 11:50:34","Grid outage.site went down due to ATS malfunctionnin///gen m=
anually started ","Paul BIBOUM","Equipment Repair","Passive","Control Panel=
","ATS-AMF Issue","Grid outage.site went down due to ATS malfunctionnin///g=
en manually started ","dorothy.djantio@ihstowers.com","1204","20-12-2024 09=
:52:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003893314","C=
rf-Nsam","","20-12-2024 09:52:45","20-12-2024 09:05:27","20-12-2024 11:05:2=
1","Site went down due PWC Dysfunctionning on site // he Reset it and Site =
is on Grid","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Recti=
fier Module Overloaded","Site went down due PWC Dysfunctionning on site // =
he Reset it and Site is on Grid","olivier.kwedi@ihstowers.com","2839","20-1=
2-2024 09:52:45","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003893269","HOP=
ITAL GENERAL RAIL YDE","","20-12-2024 09:50:35","20-12-2024 09:27:28","20-1=
2-2024 11:14:47","Grid outage,Gen faled to start due Grid contactor faulty/=
/He blocked grid conactor  and started the Gen manually","Delor Telezing","=
Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,Ge=
n faled to start due Grid contactor faulty//He blocked grid conactor  and s=
tarted the Gen manually","dorothy.djantio@ihstowers.com","1388","20-12-2024=
 09:50:35","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003892531","MAN=
GUIERS CHAPELLE","","20-12-2024 09:24:17","20-12-2024 09:09:12","20-12-2024=
 09:29:18","Grid outage, site went down before gen start due to poor batter=
y backup // Grid return","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Grid return","dorothy.djantio@i=
hstowers.com","907","20-12-2024 09:24:17","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003892494","Tsi=
nga","","20-12-2024 09:22:57","20-12-2024 09:08:53","20-12-2024 09:32:30","=
Grid fluctuation, site went down before gen start due to poor battery backu=
p // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid fluctuation, site went down before =
gen start due to poor battery backup // Grid return","dorothy.djantio@ihsto=
wers.com","845","20-12-2024 09:22:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003892471","M=
ontee-Des-Soeurs","","20-12-2024 09:22:13","20-12-2024 09:07:05","20-12-202=
4 09:20:31","Grid outage, site went down before gen start due to poor batte=
ry backup  // Gen started automatically  ","Hyemafo Gildas","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite went down before gen start due to poor battery backup  // Gen started a=
utomatically  ","olivier.kwedi@ihstowers.com","909","20-12-2024 09:22:13","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003892409","D=
ragage","","20-12-2024 09:19:44","20-12-2024 09:04:38","20-12-2024 09:20:25=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen started automatically","Mboua Thierry","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen started automatically","=
olivier.kwedi@ihstowers.com","907","20-12-2024 09:19:44","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003892407","Mok=
olo Yaounde","","20-12-2024 09:19:27","20-12-2024 09:07:23","20-12-2024 09:=
24:14","Grid outage.no space to deploy mobile gen //Grid power return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age.no space to deploy mobile gen //Grid power return","dorothy.djantio@ihs=
towers.com","725","20-12-2024 09:19:27","Sagemcom CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0003892404","CLE=
 Building","","20-12-2024 09:18:31","20-12-2024 09:06:25","20-12-2024 09:25=
:54","Grid outage.no space to deploy mobile gen//Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no sp=
ace to deploy mobile gen//Grid return","dorothy.djantio@ihstowers.com","727=
","20-12-2024 09:18:31","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003892360","Ema=
na","","20-12-2024 09:15:41","20-12-2024 09:06:37","20-12-2024 09:15:42","	=
Grid outage, site went down before Gen start due to poor battery backup // =
Gen start automatically","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","	Grid outage, site went down be=
fore Gen start due to poor battery backup // Gen start automatically","doro=
thy.djantio@ihstowers.com","545","20-12-2024 09:15:41","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003892330","Sap=
eur","","20-12-2024 09:12:00","20-12-2024 09:05:52","20-12-2024 09:12:20","=
Grid outage, site went down before gen start due to poor battery backup // =
Gen started automatically","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen started automatically","dor=
othy.djantio@ihstowers.com","369","20-12-2024 09:12:00","Sagemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003892321","Bas=
tos Bir","","20-12-2024 09:10:57","20-12-2024 09:04:48","20-12-2024 10:10:1=
6","Grid outage, site went down before gen start due to poor battery backup=
 // Gen started automatically","Mboua Thierry","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Gen started automatically",=
"dorothy.djantio@ihstowers.com","370","20-12-2024 09:10:57","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003892287","Eko=
unou","","20-12-2024 09:08:43","20-12-2024 09:04:39","20-12-2024 09:34:23",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","do=
rothy.djantio@ihstowers.com","246","20-12-2024 09:08:43","Sagemcom CMR"
"Closed Complete","Warning","T0058","IHS_YND_293","NOCINC0003892285","Nkoab=
ang MTN","","20-12-2024 09:08:32","","","site on alarm due to grid outage//=
gen started","Mba Lazare Herve","Warning","Warning","POWER","Warning - Site=
 on Battery","site on alarm due to grid outage//gen started","ludivine.ngam=
aleu@ihstowers.com","3","20-12-2024 09:08:32","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003892035","Ebo=
go","","20-12-2024 08:58:26","20-12-2024 08:56:08","20-12-2024 11:03:07","G=
rid fluctuation, site went down because gen start and stopped due to grid b=
ad voltage // Grid power stabilized","Siligap Boris","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site =
went down because gen start and stopped due to grid bad voltage // Grid pow=
er stabilized","dorothy.djantio@ihstowers.com","139","20-12-2024 08:58:26",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003892021","Dong",""=
,"20-12-2024 08:53:42","20-12-2024 08:46:21","20-12-2024 08:47:02","Cascade=
d Incident from TTO3856862","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue hybrid gen site on batterywith=
 U=3D48.5v Gregoire(652070658) from Huawei is informed","system","278165","=
20-12-2024 08:53:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003892016","MBIMBIM"=
,"","20-12-2024 08:53:41","20-12-2024 08:46:21","20-12-2024 08:47:02","Casc=
aded Incident from TTO3856862","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue hybrid gen site on batteryw=
ith U=3D48.5v Gregoire(652070658) from Huawei is informed","system","278165=
","20-12-2024 08:53:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003892019","Ngoum","=
","20-12-2024 08:53:41","20-12-2024 08:46:21","20-12-2024 08:47:02","Cascad=
ed Incident from TTO3856862","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue hybrid gen site on batterywit=
h U=3D48.5v Gregoire(652070658) from Huawei is informed","system","278166",=
"20-12-2024 08:53:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003892020","Ngouetou=
","","20-12-2024 08:53:41","20-12-2024 08:46:21","20-12-2024 08:47:02","Cas=
caded Incident from TTO3856862","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue hybrid gen site on battery=
with U=3D48.5v Gregoire(652070658) from Huawei is informed","system","27816=
4","20-12-2024 08:53:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003892017","Matsari"=
,"","20-12-2024 08:53:41","20-12-2024 08:46:21","20-12-2024 08:47:02","Casc=
aded Incident from TTO3856862","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue hybrid gen site on batteryw=
ith U=3D48.5v Gregoire(652070658) from Huawei is informed","system","278166=
","20-12-2024 08:53:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003892015","Nguila",=
"","20-12-2024 08:53:40","20-12-2024 08:46:21","20-12-2024 08:47:02","Casca=
ded Incident from TTO3856862","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue hybrid gen site on batterywi=
th U=3D48.5v Gregoire(652070658) from Huawei is informed","system","278166"=
,"20-12-2024 08:53:40","Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0003891999","Don=
ga","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_Y=
ND_444, IHS_YND_473","20-12-2024 08:51:25","20-12-2024 08:46:21","20-12-202=
4 08:47:02","No power issue hybrid gen site on batterywith U=3D48.5v Gregoi=
re(652070658) from Huawei is informed","Parker Tchoup","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue hybrid gen site on batterywith U=3D48.5v Gregoire(652070658) from Hu=
awei is informed","dorothy.djantio@ihstowers.com","305","20-12-2024 08:51:2=
5","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003891912","Crf-Mban=
kolo-IHS","","20-12-2024 08:44:20","20-12-2024 08:38:31","20-12-2024 09:34:=
09","Cascaded Incident from TTO3856746","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation site went dow=
n because Gen and started and stopped due to Grid bad voltage // He bypass =
the Grid and Gen manually started","system","278747","20-12-2024 08:44:20",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003891896","Jea=
n Vespa","IHS_YND_544, IHS_YND_574","20-12-2024 08:41:36","20-12-2024 08:38=
:31","20-12-2024 09:34:09","Grid fluctuation site went down because Gen and=
 started and stopped due to Grid bad voltage // He bypass the Grid and Gen =
manually started","Mboua Thierry","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","Grid fluctuation site went down because Ge=
n and started and stopped due to Grid bad voltage // He bypass the Grid and=
 Gen manually started","dorothy.djantio@ihstowers.com","186","20-12-2024 08=
:41:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0003891885","Jean Ves=
pa 2","","20-12-2024 08:39:30","20-12-2024 07:50:35","20-12-2024 09:34:09",=
"Cascaded Incident from TTO3856499","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because Gen failed =
to start due to Grid contactor faulty // he locked the Grid contactor manua=
lly. site on Grid","system","281661","20-12-2024 08:39:30","Sagemcom CMR"
"Closed Complete","Warning","CTR_414","IHS_YND_202","NOCINC0003891870","Cit=
e-Verte","","20-12-2024 08:35:08","","","grid outage//grid return","","Warn=
ing","Warning","POWER","Warning - Site on Battery","grid outage//grid retur=
n","ludivine.ngamaleu@ihstowers.com","3","20-12-2024 08:35:08","Sagemcom CM=
R"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003891786","NTU=
I TOWN","","20-12-2024 08:25:05","20-12-2024 08:16:00","20-12-2024 09:27:10=
","site went down because (02/03) dysfonctioned  // He change faulty rectif=
ier .site on grid","Parker Tchoup","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","site went down because (02/03) dysfonctioned  // He ch=
ange faulty rectifier .site on grid","dorothy.djantio@ihstowers.com","546",=
"20-12-2024 08:25:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003891686","J=
-Vespa","IHS_YND_544","20-12-2024 07:51:57","20-12-2024 07:50:35","20-12-20=
24 07:56:27","site went down because Gen failed to start due to Grid contac=
tor faulty // he locked the Grid contactor manually. site on Grid","Mboua T=
hierry","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","site =
went down because Gen failed to start due to Grid contactor faulty // he lo=
cked the Grid contactor manually. site on Grid","olivier.kwedi@ihstowers.co=
m","83","20-12-2024 07:51:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003891641","c=
hina embassy yde","","20-12-2024 07:45:12","20-12-2024 07:37:03","20-12-202=
4 07:42:07","No power issue on site Ubaie=3D53.3V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed.","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site Ubaie=3D53.3V site on Grid The Tx Fme Eloundou/693212405 of huawei is =
informed.","olivier.kwedi@ihstowers.com","490","20-12-2024 07:45:12","Sagem=
com CMR"
"Cancelled","Warning","CTR_414","IHS_YND_202","NOCINC0003891568","Cite-Vert=
e","","20-12-2024 07:27:26","","","","","","","","","","ludivine.ngamaleu@i=
hstowers.com","5","20-12-2024 07:27:26","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003891316","NTU=
I TOWN","","20-12-2024 06:24:41","20-12-2024 06:18:36","20-12-2024 07:20:01=
","site went down because 02/03 dysfonction // He reset the rectifier on si=
te","Parker Tchoup","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","site went down because 02/03 dysfonction // He reset the r=
ectifier on site","dorothy.djantio@ihstowers.com","366","20-12-2024 06:24:4=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003891025","Crf-Mban=
kolo-IHS","","20-12-2024 04:14:51","20-12-2024 04:03:58","20-12-2024 05:01:=
18","Cascaded Incident from TTO3855671","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause Gen failed to start due to Grid contactor faulty // he blocked the Gr=
id contactor manually. site on Gen","system","266280","20-12-2024 04:14:51"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003891021","Jea=
n Vespa","IHS_YND_544, IHS_YND_574","20-12-2024 04:13:09","20-12-2024 04:03=
:58","20-12-2024 05:01:18","Grid outage, site went down because Gen failed =
to start due to Grid contactor faulty // he blocked the Grid contactor manu=
ally. site on Gen","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","ATS-AMF Issue","Grid outage, site went down because Gen failed to sta=
rt due to Grid contactor faulty // he blocked the Grid contactor manually. =
site on Gen","landry.etame@ihstowers.com","552","20-12-2024 04:13:09","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0003890981","Jean Ves=
pa 2","","20-12-2024 04:01:40","20-12-2024 03:54:10","20-12-2024 05:01:18",=
"Cascaded Incident from TTO3855624","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e Gen failed to start due to Grid contactor faulty // he blocked the Grid c=
ontactor manually. site on Gen","system","266867","20-12-2024 04:01:40","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003890978","J=
-Vespa","IHS_YND_544","20-12-2024 04:00:17","20-12-2024 03:54:10","20-12-20=
24 04:52:23","Grid outage, site went down because Gen failed to start due t=
o Grid contactor faulty // he blocked the Grid contactor manually. site on =
Gen","Mboua Thierry","Equipment Repair","Passive","Control Panel","ATS-AMF =
Issue","Grid outage, site went down because Gen failed to start due to Grid=
 contactor faulty // he blocked the Grid contactor manually. site on Gen","=
stephane.nkamwa@ihstowers.com","368","20-12-2024 04:00:17","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003890954","NKO=
MEKUI OCM","","20-12-2024 03:53:20","20-12-2024 03:03:12","20-12-2024 03:10=
:02","no power issue on site U=3D50,7  V site on Gen.site impacted by Mbank=
olo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
no power issue on site U=3D50,7  V site on Gen.site impacted by Mbankolo Ca=
mtel and not managing by IHS","landry.etame@ihstowers.com","3009","20-12-20=
24 03:53:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003890924","c=
hina embassy yde","","20-12-2024 03:35:59","20-12-2024 03:25:54","20-12-202=
4 05:15:50","No power issue on site Ubaie=3D53.3V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite Ubaie=3D53.3V site on Grid The Tx Fme Eloundou/693212405 of huawei is i=
nformed
","stephane.nkamwa@ihstowers.com","605","20-12-2024 03:35:59","Sagemcom CMR=
"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003890920","NTU=
I TOWN","","20-12-2024 03:32:33","19-12-2024 23:24:26","20-12-2024 03:50:26=
","site went down because 02/04 dysfonction // He reset the rectifier on si=
te","Parker Tchoup","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","site went down because 02/04 dysfonction // He reset the rectifier on=
 site","landry.etame@ihstowers.com","14888","20-12-2024 03:32:33","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0003890412","E=
ntree Cite Verte","","20-12-2024 00:04:43","19-12-2024 23:47:13","19-12-202=
4 23:55:13","Actives, no power issue on site, Ubaie=3D53.4V  Site on Grid, =
 TheTX FME Brice Stague 650214096 of huawei is informed","Paul BIBOUM","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Actives, no power issue on site, Ubaie=3D53.4V  Site on Grid, TheTX=
 FME Brice Stague 650214096 of huawei is informed
","stephane.nkamwa@ihstowers.com","1051","20-12-2024 00:04:43","Sagemcom CM=
R"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003890260","NYO=
M FACE MAETUR","","19-12-2024 23:20:51","19-12-2024 23:06:47","24-12-2024 1=
5:59:05","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen=
 due to Noise // Grid Restored","landry.etame@ihstowers.com","845","19-12-2=
024 23:20:51","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003890173","Ole=
mbe MTN","","19-12-2024 22:48:40","19-12-2024 22:42:33","20-12-2024 00:28:0=
7","grid outage, site went down because gen failed to start due to gen cont=
actor faulty // He bypassed gen contactor, site on gen","Fabrice Pouakam","=
Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","grid outage=
, site went down because gen failed to start due to gen contactor faulty //=
 He bypassed gen contactor, site on gen","landry.etame@ihstowers.com","368"=
,"19-12-2024 22:48:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003889841","N=
KOLMEKONG YDE","","19-12-2024 21:39:50","19-12-2024 21:39:43","19-12-2024 2=
3:52:43","Site went down because rectifiers alarming due to PWC disfunction=
// Site stabilized","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down because rectifiers alarmi=
ng due to PWC disfunction// Site stabilized","emmanuel.ghani@ihstowers.com"=
,"8","19-12-2024 21:39:50","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003889645","Ole=
mbe MTN","","19-12-2024 21:02:29","19-12-2024 19:41:03","19-12-2024 21:11:4=
9","grid outage, site went down because gen failed to start due to gen cont=
actor faulty // He bypassed gen contactor and gen manually started","Fabric=
e Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","gr=
id outage, site went down because gen failed to start due to gen contactor =
faulty // He bypassed gen contactor and gen manually started","christian.fo=
nkou@ihstowers.com","4887","19-12-2024 21:02:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003889595","E=
bogo","","19-12-2024 20:57:11","19-12-2024 20:54:04","19-12-2024 21:37:05",=
"Grid outage,site went down before gen starts due to poor battery backup//G=
rid return","Siligap Boris","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage,site went down before gen starts d=
ue to poor battery backup//Grid return","emmanuel.ghani@ihstowers.com","188=
","19-12-2024 20:57:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003889463","E=
kounou","","19-12-2024 20:35:22","19-12-2024 20:29:19","19-12-2024 20:40:01=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen started automatically","Albran Byorel","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen started automatically","=
emmanuel.ghani@ihstowers.com","364","19-12-2024 20:35:22","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003889264","SOA=
 TOWN","IHS_YND_323","19-12-2024 19:59:18","19-12-2024 19:49:14","19-12-202=
4 21:28:39","site went down because gen failed to start due to grid fluctua=
tion // He bypassed grid and gen manually started","Siligap Boris","Grid Su=
pply","Passive","Grid","National Grid - Phase Controller Faulty","site went=
 down because gen failed to start due to grid fluctuation // He bypassed gr=
id and gen manually started","christian.fonkou@ihstowers.com","606","19-12-=
2024 19:59:18","Sagemcom CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0003889240","SOA=
 VILLAGE","","19-12-2024 19:53:02","19-12-2024 19:49:14","19-12-2024 20:19:=
01","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","site went down because gen failed to start due to grid fluctuat=
ion // He bypassed grid and gen manually started","christian.fonkou@ihstowe=
rs.com","288750","19-12-2024 19:53:02","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003889205","Bit=
oto","","19-12-2024 19:49:08","19-12-2024 19:45:04","19-12-2024 20:42:32","=
Grid outage , site went down due to dysfunctionning of PWC ZTE // He reset =
PWC, site on Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Grid outage , site went down due to dysfunctionning =
of PWC ZTE // He reset PWC, site on Gen","christian.fonkou@ihstowers.com","=
511","19-12-2024 19:49:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003889200","O=
lembe-Terminus","","19-12-2024 19:45:21","19-12-2024 19:39:13","19-12-2024 =
21:26:38","Grid Outage, site went down because Gen started and stopped with=
 High temp // He added water and started Gen manualy","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Grid Outage, site went down because Gen started and stopped with=
 High temp // He added water and started Gen manualy","emmanuel.ghani@ihsto=
wers.com","370","19-12-2024 19:45:21","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003889167","HOP=
ITAL GENERAL RAIL YDE","","19-12-2024 19:38:36","19-12-2024 19:23:30","19-1=
2-2024 20:31:14","grid outage, site went down because gen failed to start d=
ue to gen contactor not excited // He excited gen contactor and gen manuall=
y started","Delor Telezing","Equipment Repair","Passive","Control Panel","A=
TS-AMF Issue","grid outage, site went down because gen failed to start due =
to gen contactor not excited // He excited gen contactor and gen manually s=
tarted","christian.fonkou@ihstowers.com","907","19-12-2024 19:38:36","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003889110","O=
mnisport-Rail","","19-12-2024 19:30:46","19-12-2024 19:22:38","20-12-2024 0=
7:04:03","Active// No power issue on site U=3D56,2V , Site is on Grid The F=
ME TX Armand Nguesta (699949553) From Huawei is informed","Delor Telezing",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active// No power issue on site U=3D56,2V , Site is on Grid The=
 FME TX Armand Nguesta (699949553) From Huawei is informed","emmanuel.ghani=
@ihstowers.com","490","19-12-2024 19:30:46","Sagemcom CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0003889097","CLE=
 Building","","19-12-2024 19:27:44","19-12-2024 19:13:39","19-12-2024 19:27=
:27","grid outage, no space to deploy a mobil gen// grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, n=
o space to deploy a mobil gen// grid return","christian.fonkou@ihstowers.co=
m","846","19-12-2024 19:27:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0003889064","Mvog-Eba=
nda","","19-12-2024 19:21:10","19-12-2024 19:14:07","19-12-2024 19:26:30","=
Cascaded Incident from TTO3853418","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, site went down because=
 gen start and stopped with alarm under frequency // He reset gen card and =
gen manually started","system","269407","19-12-2024 19:21:10","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003889053","A=
bom","IHS_YND_269","19-12-2024 19:19:27","19-12-2024 19:14:07","19-12-2024 =
19:26:30","grid outage, site went down because gen start and stopped with a=
larm under frequency // He reset gen card and gen manually started","Siliga=
p Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","gr=
id outage, site went down because gen start and stopped with alarm under fr=
equency // He reset gen card and gen manually started","emmanuel.ghani@ihst=
owers.com","321","19-12-2024 19:19:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003889046","S=
atcom","","19-12-2024 19:18:21","19-12-2024 19:11:17","19-12-2024 20:10:07"=
,"Active//No power issue on site, Site on Grid UBAIE=3D58.8V, Geoge (697461=
814) From huawei is informed.","Delor Telezing","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue on site, Site on Grid UBAIE=3D58.8V, Geoge (697461814) From huawei =
is informed.","emmanuel.ghani@ihstowers.com","425","19-12-2024 19:18:21","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003888988","M=
IMBOMAN LIBERTE","","19-12-2024 19:07:23","19-12-2024 19:01:18","19-12-2024=
 19:14:20","Grid Outage,Site went down because Main Gen Faulty // grid retu=
rn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Faulty","Grid Outage,Site went down because Main Gen Faulty // grid r=
eturn","emmanuel.ghani@ihstowers.com","366","19-12-2024 19:07:23","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003888493","B=
iyemassi LAC","","19-12-2024 17:33:47","19-12-2024 17:22:42","19-12-2024 20=
:57:47","grid outage, no space to deploy a mobil gen//  grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outag=
e, no space to deploy a mobil gen//  grid return","emmanuel.ghani@ihstowers=
.com","666","19-12-2024 17:33:47","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003888421","Mim=
boman4","","19-12-2024 17:23:47","19-12-2024 17:14:42","19-12-2024 18:08:31=
","grid outage, site went down because gen start and stopped with alarm low=
 oil pressure // He reset gen card and gen manually started","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid o=
utage, site went down because gen start and stopped with alarm low oil pres=
sure // He reset gen card and gen manually started","christian.fonkou@ihsto=
wers.com","546","19-12-2024 17:23:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003888370","Scalom-I=
HS","","19-12-2024 17:16:30","19-12-2024 17:02:28","19-12-2024 17:45:29","C=
ascaded Incident from TTO3852584","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","grid outage// grid return ","system","277128","19=
-12-2024 17:16:30","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_318","NOCINC0003888343","SOA Univer=
sity","","19-12-2024 17:12:31","","","site on alarm due to grid outage//Gen=
 started","Siligap Boris","Warning","Warning","POWER","Warning - Site on Ba=
ttery","site on alarm due to grid outage//Gen started","joelle.ekessi@ihsto=
wers.com","64","19-12-2024 17:12:31","Sagemcom CMR"
"Closed Complete","Site Down","T0401","IHS_YND_205","NOCINC0003888342","Ton=
golo MTN","","19-12-2024 17:12:09","19-12-2024 17:07:04","19-12-2024 19:19:=
54","","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","grid outage, site went down because gen start and stoppen due=
 to dysfunctionning of gen card // He reset gen card and gen manually start=
ed","christian.fonkou@ihstowers.com","306","19-12-2024 17:12:09","Sagemcom =
CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0003888332","Acc=
acia New","IHS_YND_505","19-12-2024 17:08:33","19-12-2024 17:02:28","19-12-=
2024 18:32:16","grid outage// grid return ","","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue","grid outage// grid return ","christ=
ian.fonkou@ihstowers.com","367","19-12-2024 17:08:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003888296","Nkolo II=
 New","","19-12-2024 17:04:20","19-12-2024 17:01:06","19-12-2024 18:20:18",=
"Cascaded Incident from TTO3852523","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down due to dysfuncti=
onning PWC ZTE // Gen manually started","system","270122","19-12-2024 17:04=
:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003888292","M=
imboman-Village","IHS_YND_709","19-12-2024 17:03:14","19-12-2024 17:01:06",=
"19-12-2024 18:20:18","site went down due to dysfunctionning PWC ZTE // Gen=
 manually started","Mba Lazare Herve","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","site went down due to dysfunctionning PW=
C ZTE // Gen manually started","emmanuel.ghani@ihstowers.com","129","19-12-=
2024 17:03:14","Sagemcom CMR"
"Cancelled","Warning","CTR_483","IHS_YND_564","NOCINC0003888273","Mvog Mbi =
New","","19-12-2024 16:59:24","","","","MINKA NICOLAS","","","","","","emma=
nuel.ghani@ihstowers.com","127","19-12-2024 16:59:24","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003888270","Nsi=
meyong Terre Rouge","","19-12-2024 16:58:53","19-12-2024 16:52:48","19-12-2=
024 17:04:58","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen started automatically","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen started auto=
matically","christian.fonkou@ihstowers.com","366","19-12-2024 16:58:53","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003888265","Ole=
mbe MTN","","19-12-2024 16:57:32","19-12-2024 16:52:27","19-12-2024 17:05:1=
0","grid outage, site went down because gen failed to start due to gen cont=
actor faulty // He bypassed gen contactor and gen manually started","Fabric=
e Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","gr=
id outage, site went down because gen failed to start due to gen contactor =
faulty // He bypassed gen contactor and gen manually started","christian.fo=
nkou@ihstowers.com","306","19-12-2024 16:57:32","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003887873","Nko=
abang Ebolmedjock","","19-12-2024 16:14:19","19-12-2024 16:11:12","19-12-20=
24 17:31:56","Grid outage, site went down due to dysfunctionning of PWC Hua=
wei // He reset PWC, site on Gen","Mba Lazare Herve","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module Overloaded","Grid outage, site went do=
wn due to dysfunctionning of PWC Huawei // He reset PWC, site on Gen","chri=
stian.fonkou@ihstowers.com","188","19-12-2024 16:14:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003887866","H=
-Progres","","19-12-2024 16:12:56","19-12-2024 16:05:50","19-12-2024 16:14:=
51","grid outage, no space to deploy a mobil gen //grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, no=
 space to deploy a mobil gen //grid return","emmanuel.ghani@ihstowers.com",=
"427","19-12-2024 16:12:56","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003887751","BAT=
A Mokolo OCM","","19-12-2024 15:46:50","19-12-2024 15:42:43","19-12-2024 16=
:20:18","grid outage, no space to deploy a mobil gen// grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage=
, no space to deploy a mobil gen// grid return","christian.fonkou@ihstowers=
.com","248","19-12-2024 15:46:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003887699","EMANA BI=
LICK CITY","","19-12-2024 15:39:42","19-12-2024 15:27:03","19-12-2024 15:43=
:15","Cascaded Incident from TTO3851817","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid outage, site went down=
 because gen failed to start due to dysfunctioning of gen card // He reset =
gen card and gen manually started","system","1218071","19-12-2024 15:39:42"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003887701","Messassi=
 okolo","","19-12-2024 15:39:42","19-12-2024 15:27:03","19-12-2024 15:43:15=
","Cascaded Incident from TTO3851817","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, site went down be=
cause gen failed to start due to dysfunctioning of gen card // He reset gen=
 card and gen manually started","system","1218070","19-12-2024 15:39:42","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003887702","Emana ly=
cee 2","","19-12-2024 15:39:42","19-12-2024 15:27:03","19-12-2024 15:43:15"=
,"Cascaded Incident from TTO3851817","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down bec=
ause gen failed to start due to dysfunctioning of gen card // He reset gen =
card and gen manually started","system","1218070","19-12-2024 15:39:42","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003887700","Emana Ly=
cee","","19-12-2024 15:39:42","19-12-2024 15:27:03","19-12-2024 15:43:15","=
Cascaded Incident from TTO3851817","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site went down becau=
se gen failed to start due to dysfunctioning of gen card // He reset gen ca=
rd and gen manually started","system","1218069","19-12-2024 15:39:42","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003887698","Mballa 4=
","","19-12-2024 15:39:41","19-12-2024 15:27:03","19-12-2024 15:43:15","Cas=
caded Incident from TTO3851817","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, site went down because g=
en failed to start due to dysfunctioning of gen card // He reset gen card a=
nd gen manually started","system","1218071","19-12-2024 15:39:41","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003887686","MAN=
GUIERS CHAPELLE","","19-12-2024 15:38:02","19-12-2024 15:27:03","19-12-2024=
 15:40:49","grid outage, site went down before Gen start due to poor batter=
y backup // Gen start automatically","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","rid outage, site we=
nt down before Gen start due to poor battery backup // Gen start automatica=
lly","christian.fonkou@ihstowers.com","660","19-12-2024 15:38:02","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0003887677","CLE=
 Building","","19-12-2024 15:36:07","19-12-2024 15:25:02","19-12-2024 19:05=
:23","grid outage, no space to deploy a mobil gen//grid return ","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, n=
o space to deploy a mobil gen//grid return ","christian.fonkou@ihstowers.co=
m","666","19-12-2024 15:36:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003887666","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_509, IHS=
_YND_685","19-12-2024 15:34:07","19-12-2024 15:27:03","19-12-2024 15:43:15"=
,"grid outage, site went down because gen failed to start due to dysfunctio=
ning of gen card // He reset gen card and gen manually started","Fabrice Po=
uakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid=
 outage, site went down because gen failed to start due to dysfunctioning o=
f gen card // He reset gen card and gen manually started","emmanuel.ghani@i=
hstowers.com","425","19-12-2024 15:34:07","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003887663","Ema=
na","","19-12-2024 15:33:04","19-12-2024 15:24:59","19-12-2024 15:36:12","G=
rid outage, site went down before Gen start due to poor battery backup // G=
en start automatically","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re Gen start due to poor battery backup // Gen start automatically","christ=
ian.fonkou@ihstowers.com","486","19-12-2024 15:33:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003887638","Akak-Nko=
zoa-MTN-IHS","","19-12-2024 15:30:40","19-12-2024 15:24:09","19-12-2024 16:=
16:20","Cascaded Incident from TTO3851771","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","grid outage , site went d=
own due to dysfunctionning of PWC ZTE // He reset PWC, site on Gen","system=
","275989","19-12-2024 15:30:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003887626","S=
oa-II","IHS_YND_316, IHS_YND_324","19-12-2024 15:29:13","19-12-2024 15:24:0=
9","19-12-2024 16:16:20","grid outage , site went down due to dysfunctionni=
ng of PWC ZTE // He reset PWC, site on Gen","Siligap Boris","Equipment Repa=
ir","Passive","Rectifier","Rectifier Module Overloaded","grid outage , site=
 went down due to dysfunctionning of PWC ZTE // He reset PWC, site on Gen",=
"emmanuel.ghani@ihstowers.com","305","19-12-2024 15:29:13","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003887577","MIM=
BOMAN LIBERTE","","19-12-2024 15:22:01","19-12-2024 15:19:56","19-12-2024 1=
7:44:27","grid outage//MDG 20kva deployed","Mba Lazare Herve","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","grid outage//MDG 20k=
va deployed","christian.fonkou@ihstowers.com","126","19-12-2024 15:22:01","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003887515","N=
KOLMEKONG YDE","","19-12-2024 15:13:11","19-12-2024 15:04:07","19-12-2024 1=
7:26:23","Site went down because rectifiers alarming due to PWC disfunction=
// Site stabilized","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module Overloaded","Site went down because rectifiers alarmi=
ng due to PWC disfunction// Site stabilized","emmanuel.ghani@ihstowers.com"=
,"546","19-12-2024 15:13:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0003887310","V=
allee-Bastos OCM","","19-12-2024 14:49:04","19-12-2024 14:40:44","19-12-202=
4 17:10:44","grid outage// grid return","","Grid Supply","Passive","Grid","=
National Grid - Grid Outage Issue","grid outage// grid return","emmanuel.gh=
ani@ihstowers.com","501","19-12-2024 14:49:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0003886936","F=
OUGEROLE","","19-12-2024 13:30:32","19-12-2024 13:21:20","19-12-2024 13:54:=
20","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","grid outage,gen failed to start due to battery Ge faulty//he st=
arted the gen with battery backup","rouselle.schoune@ihstowers.com","268767=
","19-12-2024 13:30:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0003886861","N=
gousso-Savana","IHS_YND_561","19-12-2024 13:23:28","19-12-2024 13:18:20","1=
9-12-2024 13:58:20","grid outage,gen failed to start due to battery Ge faul=
ty//he started the gen with battery backup","Siligap Boris","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Generator Battery","grid outage,gen failed=
 to start due to battery Ge faulty//he started the gen with battery backup"=
,"rouselle.schoune@ihstowers.com","345","19-12-2024 13:23:28","Sagemcom CMR=
"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003886834","NYO=
M FACE MAETUR","","19-12-2024 13:19:06","19-12-2024 13:12:56","19-12-2024 1=
4:00:56","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // grid return","ange.kongo@ihstowers.com","372","19-12-2024 13=
:19:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003886723","S=
tade-Abega","","19-12-2024 13:00:16","19-12-2024 12:53:06","19-12-2024 13:3=
0:49","grid outage, site went down due to dysfunctionning of the PWC ZTE //=
 Gen manually started","Mba Lazare Herve","Equipment Repair","Passive","Rec=
tifier","Rectifier Module Overloaded","grid outage, site went down due to d=
ysfunctionning of the PWC ZTE // Gen manually started","rouselle.schoune@ih=
stowers.com","431","19-12-2024 13:00:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003886721","C=
rf-Nsam","","19-12-2024 12:59:12","19-12-2024 12:51:09","19-12-2024 13:23:5=
4","Site went down Because The Slot off Rectifier is overload//he Normalize=
d it and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passive","Rec=
tifier","Rectifier Distribution","Site went down Because The Slot off Recti=
fier is overload//he Normalized it and Site is on Grid","rouselle.schoune@i=
hstowers.com","484","19-12-2024 12:59:12","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0003886689","ETO=
UDI Entree du palais","","19-12-2024 12:51:16","19-12-2024 12:42:05","19-12=
-2024 13:36:40","grid outage, site went down because gen start and stopped =
with emergency stop alarm // reset of gen card done and gen started","Fabri=
ce Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"grid outage, site went down because gen start and stopped with emergency s=
top alarm // reset of gen card done and gen started","ange.kongo@ihstowers.=
com","552","19-12-2024 12:51:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003886678","A=
WAE OCM","","19-12-2024 12:48:49","19-12-2024 12:44:45","19-12-2024 14:17:1=
7","grid outage, site went down due to dysfunctionning of the PWC ZTE // Ge=
n manually started","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","grid outage, site went down due to dysf=
unctionning of the PWC ZTE // Gen manually started","rouselle.schoune@ihsto=
wers.com","245","19-12-2024 12:48:49","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003886597","Men=
dong3","","19-12-2024 12:40:10","19-12-2024 12:29:51","19-12-2024 13:53:34"=
,"Grid outage,no space to deploy a mobil gen// grid restored.","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no s=
pace to deploy a mobil gen// grid restored.","ange.kongo@ihstowers.com","61=
9","19-12-2024 12:40:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0003886330","Mamch Bu=
ilding","","19-12-2024 11:49:30","19-12-2024 11:37:05","19-12-2024 13:48:52=
","Cascaded Incident from TTO3850334","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid Outage // He deployed MDG o=
f 20Kva","system","339801","19-12-2024 11:49:30","Sagemcom CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0003886304","Cha=
rles-Atangana","IHS_YND_051","19-12-2024 11:45:21","19-12-2024 11:37:05","1=
9-12-2024 13:48:52","Grid Outage // He deployed MDG of 20Kva","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage // He=
 deployed MDG of 20Kva","ange.kongo@ihstowers.com","727","19-12-2024 11:45:=
21","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003886296","Mok=
olo Yaounde","","19-12-2024 11:44:06","19-12-2024 11:35:58","19-12-2024 11:=
43:29","grid, outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid, outage,=
no space to deploy a mobil gen//grid return","ange.kongo@ihstowers.com","48=
9","19-12-2024 11:44:06","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003886172","Ema=
na","","19-12-2024 11:28:06","19-12-2024 11:16:01","19-12-2024 11:28:01","G=
rid fluctuation, site went down because gen fails to start due to grid bad =
voltage // gen start automatically","Fabrice Pouakam","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site=
 went down because gen fails to start due to grid bad voltage // gen start =
automatically","ange.kongo@ihstowers.com","726","19-12-2024 11:28:06","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003886168","M=
ANGUIERS CHAPELLE","","19-12-2024 11:27:15","19-12-2024 11:19:09","19-12-20=
24 11:34:09","Grid outage, site went down before gen start due to poor batt=
ery backup // gen start automatically","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // gen start automat=
ically","rouselle.schoune@ihstowers.com","487","19-12-2024 11:27:15","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003886162","O=
mnisport-Rail","","19-12-2024 11:26:10","19-12-2024 11:18:05","19-12-2024 1=
2:00:05","No power issue on site U=3D54v site on gen Tx fme Armand of huawe=
i is informed up at 11:30","Delor Telezing","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D54v site on gen Tx fme Armand of huawei is informed up at 11:30","r=
ouselle.schoune@ihstowers.com","486","19-12-2024 11:26:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0003886024","Ekoumdou=
m OCM","","19-12-2024 11:04:41","19-12-2024 10:59:21","19-12-2024 12:15:01"=
,"Cascaded Incident from TTO3849979","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site on gen due to grid outage, s=
ite went down because gen stopped with 'charge alternator fails' alarm // r=
eset of gen card done and gen start","system","270209","19-12-2024 11:04:41=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003886023","MEHANDAN=
","","19-12-2024 11:04:41","19-12-2024 10:59:21","19-12-2024 12:15:01","Cas=
caded Incident from TTO3849979","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site on gen due to grid outage, site w=
ent down because gen stopped with 'charge alternator fails' alarm // reset =
of gen card done and gen start","system","270209","19-12-2024 11:04:41","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0003886022","Odza II =
OCM","","19-12-2024 11:04:41","19-12-2024 10:59:21","19-12-2024 12:15:01","=
Cascaded Incident from TTO3849979","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site on gen due to grid outage, sit=
e went down because gen stopped with 'charge alternator fails' alarm // res=
et of gen card done and gen start","system","270210","19-12-2024 11:04:41",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0003886015","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","19-12-2024 11:03:27","19=
-12-2024 10:59:21","19-12-2024 12:15:01","Site on gen due to grid outage, s=
ite went down because gen stopped with 'charge alternator fails' alarm // r=
eset of gen card done and gen start","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Site on gen due to grid outage, s=
ite went down because gen stopped with 'charge alternator fails' alarm // r=
eset of gen card done and gen start","rouselle.schoune@ihstowers.com","247"=
,"19-12-2024 11:03:27","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003885942","NKO=
MEKUI OCM","","19-12-2024 10:49:58","19-12-2024 10:43:50","19-12-2024 11:22=
:38","No power issue on site U=3D54v site on gen site down because is impac=
ted by Mbankolo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL",=
"Customer Equipment Failure","Active","Active Equipment Failure","Affected =
by 3rd Party Site","No power issue on site U=3D54v site on gen site down be=
cause is impacted by Mbankolo Camtel and not managing by IHS","ange.kongo@i=
hstowers.com","369","19-12-2024 10:49:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003885900","T=
singa","","19-12-2024 10:43:11","19-12-2024 10:40:05","19-12-2024 11:02:05"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ gen start automatically","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen start automatically","rouse=
lle.schoune@ihstowers.com","187","19-12-2024 10:43:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003885820","N=
KOLMEKONG YDE","","19-12-2024 10:30:20","19-12-2024 10:28:13","19-12-2024 1=
2:40:35","Site went down due to PWC disfunctionning // he reset it: site on=
 grid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Site went down due to PWC disfunctionning // he reset=
 it: site on grid","rouselle.schoune@ihstowers.com","128","19-12-2024 10:30=
:20","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003885799","NYO=
M FACE MAETUR","","19-12-2024 10:26:44","19-12-2024 10:17:37","19-12-2024 1=
0:55:15","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // grid return","ange.kongo@ihstowers.com","548","19-12-2024 10=
:26:44","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0003885739","Nko=
zoa","","19-12-2024 10:16:40","19-12-2024 10:06:21","19-12-2024 11:37:52","=
Grid outage, site went down because gen fails to start due to gen overload(=
20Kva, 340A) //  he reduice the load and manually start the gen","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, site went down because gen fails to start due to gen overload(20Kva, 3=
40A) //  he reduice the load and manually start the gen","ange.kongo@ihstow=
ers.com","965","19-12-2024 10:16:40","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003885521","Ole=
mbe MTN","","19-12-2024 09:55:03","19-12-2024 09:44:59","19-12-2024 11:41:4=
0","grid outage,site went down because Gen contactor faulty//Gen manually s=
tarted","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS=
-AMF Issue","grid outage,site went down because Gen contactor faulty//Gen m=
anually started","ange.kongo@ihstowers.com","605","19-12-2024 09:55:03","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003885448","MVAN SAC=
EL","","19-12-2024 09:43:20","19-12-2024 09:39:34","19-12-2024 10:17:23","C=
ascaded Incident from TTO3849352","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Grid outage,site went down because =
Gen overload (20KVA,290 A)// he reduice the load on site","system","267827"=
,"19-12-2024 09:43:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003885443","M=
VAN","IHS_YND_510","19-12-2024 09:42:43","19-12-2024 09:38:59","19-12-2024 =
10:18:06"," Grid outage,site went down because Gen overload (20KVA,290 A)//=
 he reduice the load on site","MINKA NICOLAS","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload"," Grid outage,site went down because Gen overl=
oad (20KVA,290 A)// he reduice the load on site","rouselle.schoune@ihstower=
s.com","313","19-12-2024 09:42:43","Sagemcom CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0003885202","Mam=
ch Building","","19-12-2024 09:07:08","19-12-2024 08:58:00","19-12-2024 09:=
20:10","grid outage,gen failed to start due to alarm overccurent//he reduic=
e the load(remove one rectifier)","Mboua Thierry","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start due =
to alarm overccurent//he reduice the load(remove one rectifier)","ange.kong=
o@ihstowers.com","549","19-12-2024 09:07:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_802","NOCINC0003884978","NYOM FAC=
E MAETUR","","19-12-2024 08:29:04","19-12-2024 08:03:30","19-12-2024 08:13:=
30","Cascaded Incident from TTO3848669 - Cascade Removed From TTO3848669","=
Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","grid outage,gen stopped with alarm high temp//he added water in radia=
tor","system","1534","19-12-2024 08:29:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_625","IHS_YND_181","NOCINC0003884874","M=
imboman3","","19-12-2024 08:13:52","19-12-2024 08:06:59","19-12-2024 09:00:=
15","Grid outage, site went down because pwc dysfunction // he bypass it: s=
ite on gen","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Grid outage, site went down because pwc dysfunc=
tion // he bypass it: site on gen","rouselle.schoune@ihstowers.com","605","=
19-12-2024 08:13:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003884798","S=
atcom","","19-12-2024 07:58:47","19-12-2024 07:54:43","19-12-2024 08:14:43"=
,"Active//No power issue on site Ubaie=3D50,8V site on Grid The tx fme Arma=
nd nguetsa(691144412) is informed","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie=3D50,8V site on Grid The tx fme Armand nguetsa(69=
1144412) is informed","rouselle.schoune@ihstowers.com","245","19-12-2024 07=
:58:47","Sagemcom CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0003884704","ELO=
UMDEM CARRIERE 2","","19-12-2024 07:42:00","19-12-2024 07:34:54","19-12-202=
4 07:52:54","grid bad voltage,and gen failed to start,insufficient of recti=
fier(2)//bypassed grid and started the gen","Fanda Brice","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","grid bad voltage,a=
nd gen failed to start,insufficient of rectifier(2)//bypassed grid and star=
ted the gen","ange.kongo@ihstowers.com","428","19-12-2024 07:42:00","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003884638","Akak-Nko=
zoa-MTN-IHS","","19-12-2024 07:25:41","19-12-2024 07:19:13","19-12-2024 07:=
39:48","Cascaded Incident from TTO3848418","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site down due=
 to poor backup // Eneo return","system","269125","19-12-2024 07:25:41","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003884520","Evo=
doula MTN","","19-12-2024 06:59:36","19-12-2024 06:55:31","19-12-2024 07:03=
:00","site went down due to work Gael/SAGEMCOM/652201891:repaired the Mpr//=
End of work","TIENTCHEU NZETCHIEU GAEL","Installation Activity","Passive","=
Planned Activity","Installation Activity","site went down due to work Gael/=
SAGEMCOM/652201891:repaired the Mpr//End of work","ange.kongo@ihstowers.com=
","246","19-12-2024 06:59:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003884514","Entree C=
ite Verte","","19-12-2024 06:57:50","19-12-2024 06:54:30","19-12-2024 06:59=
:30","Cascaded Incident from TTO3848260","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage // grid return","sy=
stem","270585","19-12-2024 06:57:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0003884513","Nkomkana=
","","19-12-2024 06:57:50","19-12-2024 06:54:30","19-12-2024 06:59:30","Cas=
caded Incident from TTO3848260","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage // grid return","system","270586","19-1=
2-2024 06:57:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003884496","C=
ite-Verte","IHS_YND_200, IHS_YND_543","19-12-2024 06:56:34","19-12-2024 06:=
54:30","19-12-2024 06:59:30","Grid outage // grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage // grid r=
eturn","rouselle.schoune@ihstowers.com","125","19-12-2024 06:56:34","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003884462","D=
amas","","19-12-2024 06:47:40","19-12-2024 06:41:35","19-12-2024 06:49:38",=
"Grid Outage Site went down because Gen Overload(9Kva,150A)// Grid return",=
"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid Outage Site went down because Gen Overload(9Kva,150A)// Grid return","=
rouselle.schoune@ihstowers.com","365","19-12-2024 06:47:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003884430","F=
ebe Village","","19-12-2024 06:35:26","19-12-2024 06:34:22","19-12-2024 08:=
27:48","grid outage,gen ran till fuel shortage//Refueling done","Mboua Thie=
rry","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran =
till fuel shortage//Refueling done","rouselle.schoune@ihstowers.com","65","=
19-12-2024 06:35:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003884419","Song-bon=
g","","19-12-2024 06:31:11","19-12-2024 06:24:18","19-12-2024 06:40:18","Ca=
scaded Incident from TTO3848165","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site ,site on Grid w=
ith Ubaie=3D54 V The TX FME Etienne(695033981) from Huawei is informed","sy=
stem","265183","19-12-2024 06:31:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003884418","Eseka To=
wn","","19-12-2024 06:31:10","19-12-2024 06:24:18","19-12-2024 06:40:18","C=
ascaded Incident from TTO3848165","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site ,site on Grid =
with Ubaie=3D54 V The TX FME Etienne(695033981) from Huawei is informed","s=
ystem","265183","19-12-2024 06:31:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003884414","E=
seka OCM","IHS_YND_378, IHS_YND_453","19-12-2024 06:29:29","19-12-2024 06:2=
4:18","19-12-2024 06:59:18","No power issue on site ,site on Grid with Ubai=
e=3D54 V The TX FME Etienne(695033981) from Huawei is informed","Kemeni Fra=
nklin","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site ,site on Grid with Ubaie=3D54 V T=
he TX FME Etienne(695033981) from Huawei is informed","rouselle.schoune@ihs=
towers.com","312","19-12-2024 06:29:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003884168","Song-bon=
g","","19-12-2024 05:04:41","19-12-2024 04:38:47","19-12-2024 04:43:37","Ca=
scaded Incident from TTO3847883","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site ,site on Grid w=
ith Ubaie=3D54 V The TX FME Etienne(695033981) from Huawei is informed and =
up at 04:43 AM","system","264313","19-12-2024 05:04:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003884167","Eseka To=
wn","","19-12-2024 05:04:40","19-12-2024 04:38:47","19-12-2024 04:43:37","C=
ascaded Incident from TTO3847883","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site ,site on Grid =
with Ubaie=3D54 V The TX FME Etienne(695033981) from Huawei is informed and=
 up at 04:43 AM","system","264313","19-12-2024 05:04:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003884165","E=
seka OCM","IHS_YND_378, IHS_YND_453","19-12-2024 05:03:53","19-12-2024 04:3=
8:47","19-12-2024 04:43:37","No power issue on site ,site on Grid with Ubai=
e=3D54 V The TX FME Etienne(695033981) from Huawei is informed and up at 04=
:43 AM","Kemeni Franklin","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site ,site on Grid =
with Ubaie=3D54 V The TX FME Etienne(695033981) from Huawei is informed and=
 up at 04:43 AM","alexandre.kamal@ihstowers.com","1507","19-12-2024 05:03:5=
3","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003883885","Crf-Mban=
kolo-IHS","","19-12-2024 02:52:40","19-12-2024 02:19:33","19-12-2024 03:33:=
57","Cascaded Incident from TTO3847551","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause Gen failed to start due to Grid contactor faulty // he blocked the Gr=
id contactor manually. site on Gen","system","272511","19-12-2024 02:52:40"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003883883","Jea=
n Vespa","IHS_YND_574","19-12-2024 02:50:57","19-12-2024 02:19:33","19-12-2=
024 03:33:57","Grid outage, site went down because Gen failed to start due =
to Grid contactor faulty // he blocked the Grid contactor manually. site on=
 Gen","Mboua Thierry","Equipment Repair","Passive","Control Panel","ATS-AMF=
 Issue","Grid outage, site went down because Gen failed to start due to Gri=
d contactor faulty // he blocked the Grid contactor manually. site on Gen",=
"kamga.virgile@ihstowers.com","1884","19-12-2024 02:50:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0003883826","Jean Ves=
pa 2","","19-12-2024 02:18:10","19-12-2024 02:08:27","19-12-2024 03:28:08",=
"Cascaded Incident from TTO3847482","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e Gen failed to start due to Grid contactor faulty // he blocked the Grid c=
ontactor manually. site on Gen","system","273225","19-12-2024 02:18:10","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003883824","J=
-Vespa","IHS_YND_544","19-12-2024 02:17:31","19-12-2024 02:08:27","19-12-20=
24 03:28:08","Grid outage, site went down because Gen failed to start due t=
o Grid contactor faulty // he blocked the Grid contactor manually. site on =
Gen","Mboua Thierry","Equipment Repair","Passive","Control Panel","ATS-AMF =
Issue","Grid outage, site went down because Gen failed to start due to Grid=
 contactor faulty // he blocked the Grid contactor manually. site on Gen","=
alexandre.kamal@ihstowers.com","545","19-12-2024 02:17:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0003883314","E=
koumdoum OCM","","18-12-2024 23:38:12","18-12-2024 23:21:01","19-12-2024 00=
:09:47","Grid outage, site went down because Gen started and stopped with a=
larm ""overvoltage"" causing by 1/7 rectifier went faulty// He balances pha=
ses, Site on Gen","Albran Byorel","Equipment Repair","Passive","ACDG Gen","=
ACDG - Over Voltage","Grid outage, site went down because Gen started and s=
topped with alarm ""overvoltage"" causing by 1/7 rectifier went faulty// He=
 balances phases, Site on Gen","alexandre.kamal@ihstowers.com","1031","18-1=
2-2024 23:38:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003883150","N=
KOLMEKONG YDE","","18-12-2024 22:55:59","18-12-2024 21:49:52","18-12-2024 2=
3:18:52","Site went down because rectifiers alarming due to PWC disfunction=
// Site stabilized","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down because rectifiers alarming due to P=
WC disfunction// Site stabilized","alexandre.kamal@ihstowers.com","3968","1=
8-12-2024 22:55:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003883028","M=
IMBOMAN LIBERTE","","18-12-2024 22:33:48","18-12-2024 22:19:44","18-12-2024=
 23:21:44","Grid outage, Site went down because Main Gen faulty// Grid retu=
rn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Faulty","Grid outage, Site went down because Main Gen faulty// Grid r=
eturn","alexandre.kamal@ihstowers.com","845","18-12-2024 22:33:48","Sagemco=
m CMR"
"Closed Complete","Warning","CTR_042","IHS_YND_175","NOCINC0003882981","Nko=
mo","","18-12-2024 22:19:48","","","GRID OUTAGE SITE WENT ALARM BEFORE GEN =
START // GEN START AUTOMATICALLY","Mba Lazare Herve","Warning","Warning","P=
OWER","Warning - Site on Battery","GRID OUTAGE SITE WENT ALARM BEFORE GEN S=
TART // GEN START AUTOMATICALLY","kouoh.jean@ihstowers.com","705","18-12-20=
24 22:19:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003882771","Donga","=
","18-12-2024 21:45:51","18-12-2024 21:26:51","18-12-2024 21:47:05","Cascad=
ed Incident from TTO3846174","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site impacted by Batchenga CA=
MRAIL managed by CAMUSAT","system","261329","18-12-2024 21:45:51","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003882772","Dong",""=
,"18-12-2024 21:45:51","18-12-2024 21:26:51","18-12-2024 21:47:05","Cascade=
d Incident from TTO3846174","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue site impacted by Batchenga CAM=
RAIL managed by CAMUSAT","system","261330","18-12-2024 21:45:51","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_424","NOCINC0003882766","Ossombe"=
,"","18-12-2024 21:45:50","18-12-2024 21:26:51","18-12-2024 21:47:05","Casc=
aded Incident from TTO3846174","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site impacted by Batchenga =
CAMRAIL managed by CAMUSAT","system","261330","18-12-2024 21:45:50","Sagemc=
om CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003882180","Nko=
ulou Carriere carrefourt","","18-12-2024 20:22:42","18-12-2024 20:00:37","1=
8-12-2024 21:33:37","Site went down because the Cb(63A) of PWC dysjoncted d=
ue to load increased // He reamed the Cb","Mba Lazare Herve","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Sit=
e went down because the Cb(63A) of PWC dysjoncted due to load increased // =
He reamed the Cb","landry.etame@ihstowers.com","1326","18-12-2024 20:22:42"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003882045","N=
KOLMEKONG YDE","","18-12-2024 20:00:30","18-12-2024 19:51:21","18-12-2024 2=
0:07:31","Site went down because rectifiers alarming due to PWC disfunction=
// Site stabilized","Fabrice Pouakam","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down because rectifiers alarming due to P=
WC disfunction// Site stabilized","stephane.nkamwa@ihstowers.com","550","18=
-12-2024 20:00:30","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003882010","Evo=
doula MTN","","18-12-2024 19:48:45","18-12-2024 19:21:41","19-12-2024 03:41=
:16","Site went down because MPR (12kw), 3/4 rectifiers and 4/5 slots fault=
y// He patch up MPR, 2/5 slots and replaced 2 rectifers faulty (MPR to be r=
eplaced)","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifie=
r","Rectifier Cabinet","Site went down because MPR (12kw), 3/4 rectifiers a=
nd 4/5 slots faulty// He patch up MPR, 2/5 slots and replaced 2 rectifers f=
aulty (MPR to be replaced)","landry.etame@ihstowers.com","1625","18-12-2024=
 19:48:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003882008","SOA VILL=
AGE","","18-12-2024 19:48:10","18-12-2024 19:19:54","18-12-2024 20:08:44","=
Cascaded Incident from TTO3845328","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause Gen start and stopped due to grid bad voltage  // he bypassed Grid an=
d Gen manually started","system","269041","18-12-2024 19:48:10","Sagemcom C=
MR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003881991","NYO=
M FACE MAETUR","","18-12-2024 19:45:40","18-12-2024 19:00:36","19-12-2024 0=
4:05:32","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // Grid return","landry.etame@ihstowers.com","2705","18-12-2024=
 19:45:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0003881831","S=
OA TOWN","IHS_YND_323","18-12-2024 19:26:01","18-12-2024 19:16:54","18-12-2=
024 20:08:49","Grid fluctuation, site went down because Gen start and stopp=
ed due to grid bad voltage  // he bypassed Grid and Gen manually started","=
Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, site went down because Gen start and stoppe=
d due to grid bad voltage  // he bypassed Grid and Gen manually started","s=
tephane.nkamwa@ihstowers.com","548","18-12-2024 19:26:01","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003881687","SOA=
 UNIVERSITY STADIUM","","18-12-2024 19:08:07","18-12-2024 18:57:02","18-12-=
2024 19:30:02","Grid fluctuation site went down because Gen and started and=
 stopped due to Grid bad voltage // He bypass the Grid and Gen manually sta=
rted","Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid fluctuation site went down because Gen and starte=
d and stopped due to Grid bad voltage // He bypass the Grid and Gen manuall=
y started","landry.etame@ihstowers.com","665","18-12-2024 19:08:07","Sagemc=
om CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003881529","Bit=
eng","","18-12-2024 18:34:09","18-12-2024 18:16:04","18-12-2024 19:15:30","=
Grid outage site went down because the PWC Dysfonction  //he reset the PWC,=
site on Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","R=
ectifier Module Overloaded","Grid outage site went down because the PWC Dys=
fonction  //he reset the PWC,site on Gen","landry.etame@ihstowers.com","108=
6","18-12-2024 18:34:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003881473","J=
-Vespa","IHS_YND_544","18-12-2024 18:22:08","18-12-2024 18:02:06","18-12-20=
24 18:56:23","site went down because Gen failed to start due to Grid contac=
tor faulty  // he locked the Grid contactor manually. site on Grid","Mboua =
Thierry","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","site=
 went down because Gen failed to start due to Grid contactor faulty  // he =
locked the Grid contactor manually. site on Grid","stephane.nkamwa@ihstower=
s.com","1202","18-12-2024 18:22:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003881421","Crf-Mban=
kolo-IHS","","18-12-2024 18:15:41","18-12-2024 18:06:42","18-12-2024 18:09:=
42","Cascaded Incident from TTO3844584","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause Gen fails to start due to Grid contactor faulty// he blocked Grid con=
tactor,site on Grid","system","1230016","18-12-2024 18:15:41","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0003881420","Jean Ves=
pa 2","","18-12-2024 18:15:40","18-12-2024 18:02:06","18-12-2024 18:56:23",=
"Cascaded Incident from TTO3844584","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive",".","system","1230291","18-12-2024 =
18:15:40","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003881380","Jea=
n Vespa","IHS_YND_544, IHS_YND_574","18-12-2024 18:11:47","18-12-2024 18:06=
:42","18-12-2024 18:09:42","Grid outage, site went down because Gen fails t=
o start due to Grid contactor faulty// he blocked Grid contactor,site on Gr=
id","Mboua Thierry","Equipment Repair","Passive","Control Panel","ATS-AMF I=
ssue","Grid outage, site went down because Gen fails to start due to Grid c=
ontactor faulty// he blocked Grid contactor,site on Grid","landry.etame@ihs=
towers.com","305","18-12-2024 18:11:47","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003880987","Nom=
ayos montee Meche","","18-12-2024 17:26:26","18-12-2024 17:10:22","18-12-20=
24 18:19:22","Grid outage, site went down because the bay DPC disfunctionni=
ng//He blocked the PWC DPC, Site on GEN","Fanda Brice","Equipment Repair","=
Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site went =
down because the bay DPC disfunctionning//He blocked the PWC DPC, Site on G=
EN","landry.etame@ihstowers.com","965","18-12-2024 17:26:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0003880748","N=
R-Omnisport","","18-12-2024 17:11:59","18-12-2024 16:44:46","18-12-2024 18:=
04:46","Grid outage site went down because Gen stopped with alarm under fre=
quency // He reset the Gen card and Gen manually started","Delor Telezing",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
 site went down because Gen stopped with alarm under frequency // He reset =
the Gen card and Gen manually started","stephane.nkamwa@ihstowers.com","163=
3","18-12-2024 17:11:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003880715","B=
iyemassi LAC","","18-12-2024 17:10:13","18-12-2024 16:43:01","18-12-2024 17=
:45:01","No power issue on site U=3D53v site on grid Tx fme Hosiah of huawe=
i is informed notice that disjunction of CB BTS Ocm","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site U=3D53v site on grid Tx fme Hosiah of huawei is informed no=
tice that disjunction of CB BTS Ocm","stephane.nkamwa@ihstowers.com","1633"=
,"18-12-2024 17:10:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003880685","Scalom-I=
HS","","18-12-2024 17:08:51","18-12-2024 16:26:04","18-12-2024 17:45:35","C=
ascaded Incident from TTO3843610","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid  outage //Grid power return","system","27935=
2","18-12-2024 17:08:51","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0003880174","Acc=
acia New","IHS_YND_505","18-12-2024 16:50:10","18-12-2024 16:26:04","18-12-=
2024 17:54:50","Grid  outage //Grid power return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid  outage //Grid power ret=
urn","landry.etame@ihstowers.com","1447","18-12-2024 16:50:10","Sagemcom CM=
R"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003879896","ODZ=
A CITE MBIA","","18-12-2024 16:25:57","18-12-2024 16:05:51","18-12-2024 16:=
49:41"," site went down because ATS dysfonction // he changed the source ma=
nually, site on Grid","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","ATS-AMF Issue"," site went down because ATS dysfonction // he chan=
ged the source manually, site on Grid","landry.etame@ihstowers.com","1207",=
"18-12-2024 16:25:57","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0003879876","Man=
guiers Dispensaire","","18-12-2024 16:22:37","18-12-2024 16:02:32","18-12-2=
024 17:30:00","Grid Outage,Gen started and stopped with  alarm Over Voltage=
'' //He Reset the Gen Card and Manually Started the Gen","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage=
,Gen started and stopped with  alarm Over Voltage'' //He Reset the Gen Card=
 and Manually Started the Gen","landry.etame@ihstowers.com","1205","18-12-2=
024 16:22:37","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003879715","AWA=
E OCM","","18-12-2024 15:53:46","18-12-2024 15:41:41","18-12-2024 16:23:43"=
,"Site went down due to work Supervisor IHS Bernard Atangana//677548315 wor=
king on site (Normalization PWC ""ZTE"") // End of work ","Mba Lazare Herve=
","Installation Activity","Passive","Planned Activity","Installation Activi=
ty","Site went down due to work Supervisor IHS Bernard Atangana//677548315 =
working on site (Normalization PWC ""ZTE"") // End of work ","landry.etame@=
ihstowers.com","726","18-12-2024 15:53:46","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003879572","Nko=
lbisson usines des eaux 2","","18-12-2024 15:39:19","18-12-2024 15:06:11","=
18-12-2024 17:05:36","Grid Outage Site Went down because main alternator fa=
ulty // He deployed MDG of 20Kva","TIENTCHEU NZETCHIEU GAEL","Equipment Rep=
lacement","Passive","ACDG Gen","ACDG - Main Alternator","Grid Outage Site W=
ent down because main alternator faulty // He deployed MDG of 20Kva","landr=
y.etame@ihstowers.com","1989","18-12-2024 15:39:19","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003879533","Odz=
a II","","18-12-2024 15:38:04","18-12-2024 15:04:54","18-12-2024 16:18:54",=
"grid outage;main gen faulty//MDG 20kva deployed","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Generator Faulty","grid outage;main =
gen faulty//MDG 20kva deployed","landry.etame@ihstowers.com","1992","18-12-=
2024 15:38:04","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0003879435","Mvo=
g-Manga","","18-12-2024 15:30:22","18-12-2024 14:59:39","18-12-2024 17:12:2=
8","grid outage,ge start and stopped due to water mixed with fuel in tank//=
he purged it and started the gen","Albran Byorel","Fuel Outage (Probable)",=
"Passive","Diesel","Tank Sealing Issue - Water In The Fuel","grid outage,ge=
 start and stopped due to water mixed with fuel in tank//he purged it and s=
tarted the gen","landry.etame@ihstowers.com","1845","18-12-2024 15:30:22","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0003878953","S=
AA 2","","18-12-2024 14:40:52","18-12-2024 14:30:44","18-12-2024 14:35:04",=
"No Power issue on site , site on Grid with Ubaie=3D52.7 V The Tx  Gregoire=
(654547479) from Huawei is informed","Parker Tchoup","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No Power i=
ssue on site , site on Grid with Ubaie=3D52.7 V The Tx  Gregoire(654547479)=
 from Huawei is informed","stephane.nkamwa@ihstowers.com","609","18-12-2024=
 14:40:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003878211","S=
OA UNIVERSITY STADIUM","","18-12-2024 13:13:18","18-12-2024 12:54:03","18-1=
2-2024 14:39:33","Grid fluctuation, site went down because started and stop=
ped due to Grid bad voltage no rcp on site// He bypassed Grid and started G=
en manualy","Siligap Boris","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Grid fluctuation, site went down because started=
 and stopped due to Grid bad voltage no rcp on site// He bypassed Grid and =
started Gen manualy","emmanuel.ghani@ihstowers.com","1156","18-12-2024 13:1=
3:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003878078","S=
aa","IHS_YND_401","18-12-2024 12:54:34","18-12-2024 12:48:28","18-12-2024 1=
3:14:45","	Grid outage,Site went down because Gen stopped with alarm ""high=
 temp""causing by  radiator pierced// He added water and started Gen manual=
y","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator=
 Leakage","	Grid outage,Site went down because Gen stopped with alarm ""hig=
h temp""causing by  radiator pierced// He added water and started Gen manua=
ly","emmanuel.ghani@ihstowers.com","367","18-12-2024 12:54:34","Sagemcom CM=
R"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0003877522","Car=
refour Ayissi Ele","","18-12-2024 12:26:26","18-12-2024 12:16:21","18-12-20=
24 12:36:21","No power issue on site U=3D53v site on solar Gregoire of huaw=
ei is informed","Parker Tchoup","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53v =
site on solar Gregoire of huawei is informed","christian.fonkou@ihstowers.c=
om","606","18-12-2024 12:26:26","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003877309","Mok=
olo Yaounde","","18-12-2024 12:19:33","18-12-2024 12:12:27","18-12-2024 14:=
13:43","grid outage, no space to deploy a mobil gen // grid return ","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outag=
e, no space to deploy a mobil gen // grid return ","christian.fonkou@ihstow=
ers.com","427","18-12-2024 12:19:33","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003877151","Ako=
no","IHS_YND_687","18-12-2024 12:15:40","18-12-2024 12:08:32","18-12-2024 1=
2:27:32","Grid fluctuation, Site went down because Gen fails to start due G=
en card disfunction// He reset Gen and started Gen manualy","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid fluctua=
tion, Site went down because Gen fails to start due Gen card disfunction// =
He reset Gen and started Gen manualy","christian.fonkou@ihstowers.com","429=
","18-12-2024 12:15:40","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003877099","OLA=
MA","","18-12-2024 12:13:45","18-12-2024 12:08:32","18-12-2024 12:27:32","P=
lease cascade this ticket behind Akono (NOCINC0003877151)","Fanda Brice","C=
ascade Outage","Passive","Cascade Passive","Cascade Passive","Grid fluctuat=
ion, Site went down because Gen fails to start due Gen card disfunction// H=
e reset Gen and started Gen manualy","christian.fonkou@ihstowers.com","519"=
,"18-12-2024 12:13:45","Sagemcom CMR"
"Closed Complete","Warning","CTR_189","IHS_YND_422","NOCINC0003876664","Bot=
makak","","18-12-2024 12:02:07","","","grid outage, site went alarm because=
 gen fails to start due to grid bad voltage // he bypass grid and manually =
start the gen","Kemeni Franklin","Warning","Warning","POWER","Warning - Sit=
e on Battery","grid outage, site went alarm because gen fails to start due =
to grid bad voltage // he bypass grid and manually start the gen","kombi.sa=
muel@ihstowers.com","3","18-12-2024 12:02:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003876331","A=
wae Escalier","","18-12-2024 11:50:17","18-12-2024 11:45:09","18-12-2024 14=
:06:05","Grid outage,Gen fails to start due to ATS malfunction causing  by =
a short-circuit on the mains terminals //he   isolated the short-circuit an=
d normalized  mains terminals,site on Grid","Albran Byorel","Equipment Repa=
ir","Passive","Control Panel","ATS-AMF Issue","Grid outage,Gen fails to sta=
rt due to ATS malfunction causing  by a short-circuit on the mains terminal=
s //he   isolated the short-circuit and normalized  mains terminals,site on=
 Grid","emmanuel.ghani@ihstowers.com","310","18-12-2024 11:50:17","Sagemcom=
 CMR"
"Closed Complete","Warning","T2502","IHS_YND_781","NOCINC0003875730","BIBOM=
DJIDJIEL","","18-12-2024 11:28:09","","","HYBRID GEN SITE // GEN STARTED","=
Kemeni Franklin","Warning","Warning","POWER","Warning - Site on Battery","H=
YBRID GEN SITE // GEN STARTED","kombi.samuel@ihstowers.com","3","18-12-2024=
 11:28:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003875317","N=
kozoa","","18-12-2024 11:09:44","18-12-2024 11:04:40","18-12-2024 12:28:11"=
,"Grid outage, site went down due to gen overload (20kva, 340A) // He reduc=
ed the load and gen manually started","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload (20kva, 340A) // He reduced the load and gen manually started"=
,"emmanuel.ghani@ihstowers.com","305","18-12-2024 11:09:44","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003875149","Eko=
unou","","18-12-2024 11:04:33","18-12-2024 10:57:25","18-12-2024 11:05:14",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","christ=
ian.fonkou@ihstowers.com","429","18-12-2024 11:04:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003875133","M=
vog-Manga","","18-12-2024 11:01:53","18-12-2024 10:57:28","18-12-2024 12:25=
:51","site went down because Cb(63A) of rectifiers disjuncted due to 01/06 =
rectifier faulty // He reamed Cb(63A) of rectifiers, site on 05 rectifiers"=
,"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier - Circ=
uit Breaker","site went down because Cb(63A) of rectifiers disjuncted due t=
o 01/06 rectifier faulty // He reamed Cb(63A) of rectifiers, site on 05 rec=
tifiers","emmanuel.ghani@ihstowers.com","267","18-12-2024 11:01:53","Sagemc=
om CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003874857","Ole=
mbe MTN","","18-12-2024 10:57:03","18-12-2024 10:48:58","18-12-2024 11:48:2=
8","grid outage, site went down because gen failed to start due to gen cont=
actor faulty and 01 rectifiers faulty // He bypassed gen contactor and chan=
ged 01 rectifiers, site on gen","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","ATS-AMF Issue","grid outage, site went down because ge=
n failed to start due to gen contactor faulty and 01 rectifiers faulty // H=
e bypassed gen contactor and changed 01 rectifiers, site on gen","christian=
.fonkou@ihstowers.com","485","18-12-2024 10:57:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003874113","O=
dza II","","18-12-2024 10:23:40","18-12-2024 10:04:34","18-12-2024 11:38:27=
","grid outage;main gen faulty//MDG 20kva deployed","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Generator Faulty","grid outage;mai=
n gen faulty//MDG 20kva deployed","emmanuel.ghani@ihstowers.com","1149","18=
-12-2024 10:23:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0003873893","S=
calom","","18-12-2024 09:46:07","18-12-2024 09:40:01","18-12-2024 09:45:13"=
,"No power issue, site is on grid with Ubaie=3D53V, Hosiah(674007438) from =
Huawei is informed","Paul BIBOUM","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on gr=
id with Ubaie=3D53V, Hosiah(674007438) from Huawei is informed","emmanuel.g=
hani@ihstowers.com","367","18-12-2024 09:46:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003873852","N=
kolondom","","18-12-2024 09:33:01","18-12-2024 09:29:40","18-12-2024 10:19:=
17","grid outage, site went down due to dysfunctionning of the PWC ZTE // G=
en manually started","Fabrice Pouakam","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","grid outage, site went down due to dysf=
unctionning of the PWC ZTE // Gen manually started","emmanuel.ghani@ihstowe=
rs.com","203","18-12-2024 09:33:01","Sagemcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0003873633","Ntu=
i administration","","18-12-2024 08:56:15","18-12-2024 08:45:08","18-12-202=
4 10:02:20","site went down due to dysfunctionning of (01/02) rectifier // =
He reset rectifier , site on gen","Parker Tchoup","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","site went down due to dysfunctionning o=
f (01/02) rectifier // He reset rectifier , site on gen","christian.fonkou@=
ihstowers.com","668","18-12-2024 08:56:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003873587","Akak-Nko=
zoa-MTN-IHS","","18-12-2024 08:50:00","18-12-2024 08:45:53","18-12-2024 08:=
49:22","Cascaded Incident from TTO3836140","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site down due=
 to poor backup // Gen Started Automatically","system","263883","18-12-2024=
 08:50:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003873518","O=
lembe-Terminus","","18-12-2024 08:40:36","18-12-2024 08:35:32","18-12-2024 =
09:28:13","Grid Outage, site went down because Gen started and stopped due =
to High temp// He added water and started Gen manualy","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Le=
vel Issue","Grid Outage, site went down because Gen started and stopped due=
 to High temp// He added water and started Gen manualy","emmanuel.ghani@ihs=
towers.com","305","18-12-2024 08:40:36","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003873484","Nsi=
meyong Terre Rouge","","18-12-2024 08:30:24","18-12-2024 08:25:18","18-12-2=
024 08:37:04","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen started automatically","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen started auto=
matically","christian.fonkou@ihstowers.com","307","18-12-2024 08:30:24","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003873084","S=
tade-Abega","","18-12-2024 07:04:56","18-12-2024 06:57:51","18-12-2024 07:2=
3:15","	grid outage, site went down due to dysfunctionning of the PWC ZTE /=
/ Gen manually started","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","	grid outage, site went down due to=
 dysfunctionning of the PWC ZTE // Gen manually started","emmanuel.ghani@ih=
stowers.com","426","18-12-2024 07:04:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003873000","M=
ontee-Des-Soeurs","","18-12-2024 06:33:19","18-12-2024 06:27:11","18-12-202=
4 06:32:47","No power issue, site is on grid with Ubaie=3D53V, Mbah Hosiah(=
674007438) from Huawei is informed","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53V, Mbah Hosiah(674007438) from Huawei =
is informed","emmanuel.ghani@ihstowers.com","369","18-12-2024 06:33:19","Sa=
gemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003872998","AWA=
E OCM","","18-12-2024 06:32:03","18-12-2024 06:29:52","18-12-2024 07:28:00"=
,"grid outage, site went down due to dysfunctionning of the PWC ZTE // Gen =
manually started","Mba Lazare Herve","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","grid outage, site went down due to dysfun=
ctionning of the PWC ZTE // Gen manually started","christian.fonkou@ihstowe=
rs.com","132","18-12-2024 06:32:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0003872516","A=
battoir","","18-12-2024 03:39:57","18-12-2024 03:31:51","18-12-2024 04:23:5=
6","Grid outage, site went down because gen start and stopped with high tem=
p alarm // he added water and manually start the gen","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Radiator","Grid outage, site w=
ent down because gen start and stopped with high temp alarm // he added wat=
er and manually start the gen","olivier.kwedi@ihstowers.com","487","18-12-2=
024 03:39:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003872467","MBIMBIM"=
,"IHS_YND_460, IHS_YND_475, IHS_YND_473","18-12-2024 03:17:30","18-12-2024 =
03:13:39","18-12-2024 03:20:25","Active//No power issue on site Ubaie=3D54.=
5V, Site on Gen, The Tx Fme Gregoire( 652070658)from Huawei is informed.","=
Parker Tchoup","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie=3D54.5V, Si=
te on Gen, The Tx Fme Gregoire( 652070658)from Huawei is informed.
","system","231","18-12-2024 03:17:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003872469","Yoko MTN=
","","18-12-2024 03:17:30","18-12-2024 03:13:39","21-12-2024 08:49:41","Cas=
caded Incident from TTO3834829","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site Ubaie=3D54=
.5V, Site on Gen, The Tx Fme Gregoire( 652070658)from Huawei is informed.
","system","550265","18-12-2024 03:17:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003872468","Matsari"=
,"","18-12-2024 03:17:30","18-12-2024 03:13:39","18-12-2024 03:20:25","Casc=
aded Incident from TTO3834829","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue on site Ubaie=3D54.=
5V, Site on Gen, The Tx Fme Gregoire( 652070658)from Huawei is informed.
","system","327054","18-12-2024 03:17:30","Sagemcom CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0003872462","Ngo=
um","","18-12-2024 03:16:45","18-12-2024 03:13:39","18-12-2024 03:13:40",""=
,"Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active=
","Wrongly logged ticket","ludivine.ngamaleu@ihstowers.com","327054","18-12=
-2024 03:16:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0003872460","B=
ondjock","","18-12-2024 03:15:30","18-12-2024 03:07:21","18-12-2024 04:02:1=
1","Grid outage,site went down before gen starts due to poor battery backup=
//Gen started automatically(investigation ongoing)","Fanda Brice","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age,site went down before gen starts due to poor battery backup//Gen starte=
d automatically(investigation ongoing)","olivier.kwedi@ihstowers.com","490"=
,"18-12-2024 03:15:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0003872369","D=
ong","","18-12-2024 02:41:17","18-12-2024 02:37:07","18-12-2024 02:57:07","=
No power issue on site U=3D51,1v site on gen Tx Gregoire of huawei is infor=
med","Parker Tchoup","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue on site U=3D51,1v site on g=
en Tx Gregoire of huawei is informed","olivier.kwedi@ihstowers.com","251","=
18-12-2024 02:41:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003872195","Akak-Nko=
zoa-MTN-IHS","","18-12-2024 01:39:01","18-12-2024 01:32:48","18-12-2024 01:=
37:45","Cascaded Incident from TTO3834510","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site down due=
 to poor backup // Grid return","system","275416","18-12-2024 01:39:01","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003872183","NYO=
M FACE MAETUR","","18-12-2024 01:34:19","17-12-2024 23:59:54","18-12-2024 0=
0:56:42","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // grid return","etienne.itondo@ihstowers.com","5666","18-12-20=
24 01:34:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003872163","N=
gouetou","","18-12-2024 01:24:47","18-12-2024 01:21:40","18-12-2024 04:26:4=
1","No power issue site on gen with U=3D52v Gregoire from Huawei is informe=
d","Parker Tchoup","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue site on gen with U=3D52v Greg=
oire from Huawei is informed","olivier.kwedi@ihstowers.com","189","18-12-20=
24 01:24:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003872087","Biteng-M=
aetur","","18-12-2024 00:50:01","18-12-2024 00:38:41","18-12-2024 00:52:07"=
,"Cascaded Incident from TTO3834373","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,site went down bef=
ore gen starts due to poor battery backup//Gen started automatically","syst=
em","278580","18-12-2024 00:50:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003872084","Bitoto",=
"","18-12-2024 00:50:00","18-12-2024 00:38:41","18-12-2024 00:52:07","Casca=
ded Incident from TTO3834373","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage,site went down before gen=
 starts due to poor battery backup//Gen started automatically","system","27=
8580","18-12-2024 00:50:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003872085","Tradex-N=
komo","","18-12-2024 00:50:00","18-12-2024 00:38:41","18-12-2024 00:52:07",=
"Cascaded Incident from TTO3834373","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,site went down before =
gen starts due to poor battery backup//Gen started automatically","system",=
"278579","18-12-2024 00:50:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003872086","AWAE OCM=
","","18-12-2024 00:50:00","18-12-2024 00:38:41","18-12-2024 00:52:07","Cas=
caded Incident from TTO3834373","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,site went down before g=
en starts due to poor battery backup//Gen started automatically","system","=
278579","18-12-2024 00:50:00","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003871916","Bit=
eng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_249","17-12-2024 23:57=
:53","17-12-2024 23:53:48","18-12-2024 01:02:36","Grid outage,site went dow=
n before gen starts due to poor battery backup//Gen started automatically",=
"Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Battery Low","Grid outage,site went down before gen starts due to poo=
r battery backup//Gen started automatically","ludivine.ngamaleu@ihstowers.c=
om","246","17-12-2024 23:57:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003871898","M=
vog-Manga","","17-12-2024 23:51:23","17-12-2024 23:50:18","17-12-2024 23:52=
:53","site went down due to insufficiency of rectifiers // site stabilized"=
,"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module=
","site went down due to insufficiency of rectifiers // site stabilized","o=
livier.kwedi@ihstowers.com","67","17-12-2024 23:51:23","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003871710","Evo=
doula MTN","","17-12-2024 23:19:37","17-12-2024 23:05:18","18-12-2024 03:46=
:48","Grid outage site went down because Gen failed to start due to Gen bat=
tery faulty // Gen manually started with external battery","TIENTCHEU NZETC=
HIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batter=
y","Grid outage site went down because Gen failed to start due to Gen batte=
ry faulty // Gen manually started with external battery","etienne.itondo@ih=
stowers.com","859","17-12-2024 23:19:37","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003871600","Nko=
abang2","","17-12-2024 22:57:22","17-12-2024 22:56:16","17-12-2024 23:30:43=
","grid outage,site went down because gen overload 20kv;320A//he resduice t=
he load on site","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","grid outage,site went down because gen overload 20kv;32=
0A//he resduice the load on site","ludivine.ngamaleu@ihstowers.com","68","1=
7-12-2024 22:57:22","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003871447","Nko=
lbisson usines des eaux 2","","17-12-2024 22:34:06","17-12-2024 22:24:59","=
17-12-2024 23:10:59","access issue during the night due to landlord;grid ou=
tage;main gen faulty//grid return","TIENTCHEU NZETCHIEU GAEL","Access Denia=
l","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","a=
ccess issue during the night due to landlord;grid outage;main gen faulty//g=
rid return","ludivine.ngamaleu@ihstowers.com","548","17-12-2024 22:34:06","=
Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003871441","Eko=
unou","","17-12-2024 22:32:30","17-12-2024 22:23:24","17-12-2024 22:33:31",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","lu=
divine.ngamaleu@ihstowers.com","548","17-12-2024 22:32:30","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0003871153","Mon=
tee-Jouvence-II","","17-12-2024 21:57:55","17-12-2024 21:53:33","17-12-2024=
 22:37:19","site went down due to PWC over load(12KW.280A) and causing disj=
unction at BTS MTN // Site stabilized and CB BTS rearmed","Hyemafo Gildas",=
"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","sit=
e went down due to PWC over load(12KW.280A) and causing disjunction at BTS =
MTN // Site stabilized and CB BTS rearmed","kamga.virgile@ihstowers.com","2=
63","17-12-2024 21:57:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003871082","Nkolo II=
 New","","17-12-2024 21:42:50","17-12-2024 21:27:23","17-12-2024 22:37:07",=
"Cascaded Incident from TTO3833182","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bec=
ause PWC dysfunctionning// He reset PWC and started Gen manualy","system","=
290200","17-12-2024 21:42:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003871064","M=
imboman-Village","IHS_YND_709","17-12-2024 21:39:32","17-12-2024 21:27:23",=
"17-12-2024 22:37:07","Grid outage, Site went down because PWC dysfunctionn=
ing// He reset PWC and started Gen manualy","Mba Lazare Herve","Equipment R=
epair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, Si=
te went down because PWC dysfunctionning// He reset PWC and started Gen man=
ualy","alexandre.kamal@ihstowers.com","730","17-12-2024 21:39:32","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003871053","E=
ssomba","","17-12-2024 21:36:56","17-12-2024 21:19:52","18-12-2024 05:32:46=
",":  Active: No power issue, site is on Grid with Ubaie=3D54.2V, The fme t=
x George //697461814//from Huawei is informed. Notice Dysjunction at the BT=
S OCM","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm",":  Active: No power issue, site is on=
 Grid with Ubaie=3D54.2V, The fme tx George //697461814//from Huawei is inf=
ormed. Notice Dysjunction at the BTS OCM","alexandre.kamal@ihstowers.com","=
1025","17-12-2024 21:36:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003871037","S=
tade-Abega","","17-12-2024 21:33:56","17-12-2024 21:04:44","18-12-2024 00:0=
5:23","grid outage, site went down due to dysfunctionning of the PWC ZTE //=
 Gen manually started	","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","grid outage, site went down due to =
dysfunctionning of the PWC ZTE // Gen manually started	","alexandre.kamal@i=
hstowers.com","1753","17-12-2024 21:33:56","Sagemcom CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0003870896","ELO=
UMDEM CARRIERE 2","","17-12-2024 21:05:09","17-12-2024 21:02:57","17-12-202=
4 21:57:57","grid bad voltage,and gen failed to start;no rcp//bypassed grid=
 and started the gen","Fanda Brice","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","grid bad voltage,and gen failed to start=
;no rcp//bypassed grid and started the gen","kamga.virgile@ihstowers.com","=
133","17-12-2024 21:05:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003870640","SOA VILL=
AGE","","17-12-2024 20:28:50","17-12-2024 19:57:40","17-12-2024 20:39:01","=
Cascaded Incident from TTO3832652","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation site went down bec=
ause Gen and started and stopped due to Grid bad voltage // He bypass the G=
rid and Gen manually started","system","1252172","17-12-2024 20:28:50","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0003870536","S=
OA TOWN","IHS_YND_323","17-12-2024 20:09:46","17-12-2024 19:54:40","17-12-2=
024 20:39:43","Grid fluctuation site went down because Gen and started and =
stopped due to Grid bad voltage // He bypass the Grid and Gen manually star=
ted","Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid fluctuation site went down because Gen and started=
 and stopped due to Grid bad voltage // He bypass the Grid and Gen manually=
 started","alexandre.kamal@ihstowers.com","907","17-12-2024 20:09:46","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003870428","M=
ANGUIERS CHAPELLE","","17-12-2024 19:53:58","17-12-2024 19:47:54","17-12-20=
24 19:55:27","Grid fluctuation, Site went down before Gen start due to poor=
 backup// Grid stabilized","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid fluctuation, Site went d=
own before Gen start due to poor backup// Grid stabilized","alexandre.kamal=
@ihstowers.com","365","17-12-2024 19:53:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003870294","O=
lembe-Terminus","","17-12-2024 19:32:51","17-12-2024 19:17:47","17-12-2024 =
19:37:42","Grid outage, Site went down because Gen failed to start // Grid =
return (investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down because =
Gen failed to start // Grid return (investigation ongoing)","alexandre.kama=
l@ihstowers.com","905","17-12-2024 19:32:51","Sagemcom CMR"
"Closed Complete","Site Down","T1432","IHS_YND_544","NOCINC0003870235","Jea=
n Vespa 2","","17-12-2024 19:25:03","17-12-2024 17:31:45","17-12-2024 17:55=
:41","Grid outage site went down because Gen failed to start due to Grid co=
ntactor dysfonction // he unlocked the Grid contactor manually and Gen auto=
matically started","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","ATS-AMF Issue","Grid outage site went down because Gen failed to star=
t due to Grid contactor dysfonction // he unlocked the Grid contactor manua=
lly and Gen automatically started","kamga.virgile@ihstowers.com","6799","17=
-12-2024 19:25:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003870131","S=
calom-IHS","","17-12-2024 19:04:59","17-12-2024 16:19:53","17-12-2024 17:43=
:17","grid outage,no space to deploy a mobil gen//grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no s=
pace to deploy a mobil gen//grid return","alexandre.kamal@ihstowers.com","9=
907","17-12-2024 19:04:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003870100","D=
ragage","","17-12-2024 18:56:56","17-12-2024 16:19:41","17-12-2024 17:22:12=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen started","Mboua Thierry","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, site went down before gen sta=
rt due to poor battery backup // Gen started","alexandre.kamal@ihstowers.co=
m","9436","17-12-2024 18:56:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003870099","S=
atcom","","17-12-2024 18:56:10","17-12-2024 16:19:01","17-12-2024 16:30:01"=
,"No power issue on site U=3D52v site on grid Tx Armand of huawei is inform=
ed","Delor Telezing","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue on site U=3D52v site on gri=
d Tx Armand of huawei is informed","alexandre.kamal@ihstowers.com","9430","=
17-12-2024 18:56:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003870091","M=
ontee-Des-Soeurs","","17-12-2024 18:54:51","17-12-2024 16:19:45","17-12-202=
4 17:15:35","Grid outage, site went down before gen start due to poor batte=
ry backup  // Gen manually started ","Hyemafo Gildas","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down before gen start due to poor battery backup  // Gen manually starte=
d ","alexandre.kamal@ihstowers.com","9307","17-12-2024 18:54:51","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003870084","M=
ini-Ferme","","17-12-2024 18:53:26","17-12-2024 16:27:21","17-12-2024 17:45=
:17","Grid outage,no space to deploy  MDG // Grid return ","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no space=
 to deploy  MDG // Grid return ","alexandre.kamal@ihstowers.com","8766","17=
-12-2024 18:53:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_322","NOCINC0003870068","Soa-II",=
"","17-12-2024 18:50:11","17-12-2024 16:37:22","17-12-2024 16:53:29","Casca=
ded Incident from TTO3831986","Siligap Boris","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site Ubaie =3D 53,2V site=
 on Grid. Raoul (691144462/Huawei) is informed. ","system","271525","17-12-=
2024 18:50:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003870067","Akak-Nko=
zoa-MTN-IHS","","17-12-2024 18:50:11","17-12-2024 16:37:22","17-12-2024 16:=
53:29","Cascaded Incident from TTO3831986","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site Ubaie=
 =3D 53,2V site on Grid. Raoul (691144462/Huawei) is informed. ","system","=
271526","17-12-2024 18:50:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003870058","O=
dza II","","17-12-2024 18:48:43","17-12-2024 16:44:36","17-12-2024 17:53:13=
","grid outage,main gen faulty//grid return","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Generator Battery","grid outage,main gen =
faulty//grid return","alexandre.kamal@ihstowers.com","7449","17-12-2024 18:=
48:43","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003870045","Ole=
mbe MTN","","17-12-2024 18:46:25","17-12-2024 16:30:09","17-12-2024 19:34:4=
6","grid outage,gen failed to start due to contactor Eneo faulty//he blocke=
d it and started the gen(remplacement ongoing)","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","ATS-AMF Issue","grid outage,gen failed=
 to start due to contactor Eneo faulty//he blocked it and started the gen(r=
emplacement ongoing)","kamga.virgile@ihstowers.com","8177","17-12-2024 18:4=
6:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003870040","N=
yom OCM","","17-12-2024 18:45:35","17-12-2024 16:49:20","17-12-2024 17:19:3=
3","grid outage,gen stopped witha alarm low oil pressure(not unproven)//he =
rest it and started the gen","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","grid outage,gen stopped witha alarm low=
 oil pressure(not unproven)//he rest it and started the gen","alexandre.kam=
al@ihstowers.com","6976","17-12-2024 18:45:35","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003870038","ODZ=
A CITE MBIA","","17-12-2024 18:45:09","17-12-2024 18:18:59","17-12-2024 18:=
46:16","site went down because gen failed to start due to ATS disfunction//=
Gen manaully started","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","ATS-AMF Issue","site went down because gen failed to start due to =
ATS disfunction//Gen manaully started","kamga.virgile@ihstowers.com","1571"=
,"17-12-2024 18:45:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003870034","S=
OA UNIVERSITY STADIUM","","17-12-2024 18:44:46","17-12-2024 16:49:39","17-1=
2-2024 17:19:17","Site went down because Gen failed to start due to Hybrid =
system dysfonction// He reset the gen card and Gen manually started","Silig=
ap Boris","Equipment Repair","Passive","Hybrid","Hybrid Module","Site went =
down because Gen failed to start due to Hybrid system dysfonction// He rese=
t the gen card and Gen manually start","alexandre.kamal@ihstowers.com","690=
8","17-12-2024 18:44:46","Sagemcom CMR"
"Closed Complete","Site Down","T0401","IHS_YND_205","NOCINC0003870024","Ton=
golo MTN","","17-12-2024 18:40:47","17-12-2024 17:36:37","17-12-2024 18:40:=
38","grid outage,gen failed to start due to card Ge disfunctionning//he res=
et it and started the gen","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start due to ca=
rd Ge disfunctionning//he reset it and started the gen ","kamga.virgile@ihs=
towers.com","3851","17-12-2024 18:40:47","Sagemcom CMR"
"Closed Complete","Site Down","T2795","IHS_YND_070","NOCINC0003869931","Efo=
ulan","","17-12-2024 18:18:35","17-12-2024 16:32:26","17-12-2024 17:44:14",=
"site went down because gen failed to start due to glow plug faulty//Gen ma=
nually started","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","AC=
DG - Kick Starter","site went down because gen failed to start due to glow =
plug faulty//Gen manually started","kamga.virgile@ihstowers.com","6370","17=
-12-2024 18:18:35","Sagemcom CMR"
"Closed Complete","Site Down","T2585","IHS_YND_744","NOCINC0003869925","Ele=
veur Meec Bon Berger","","17-12-2024 18:17:00","17-12-2024 16:28:50","17-12=
-2024 17:41:03","Grid outage, site went down because Gen ran until fuel sho=
rtage// Refueling Done","Siligap Boris","Fuel Outage","Passive","Diesel","D=
iesel Outage","Grid outage, site went down because Gen ran until fuel short=
age// Refueling Done","kamga.virgile@ihstowers.com","6491","17-12-2024 18:1=
7:00","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003869915","BIY=
EMASSI NIKI","","17-12-2024 18:15:34","17-12-2024 16:28:23","17-12-2024 18:=
02:28","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Site =
stabilized","kamga.virgile@ihstowers.com","6431","17-12-2024 18:15:34","Sag=
emcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003869910","MIM=
BOMAN LIBERTE","","17-12-2024 18:14:25","17-12-2024 16:28:16","17-12-2024 1=
7:23:08","Grid outage, Site went because Main Gen faulty// Grid return","Mb=
a Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator F=
aulty","Grid outage, Site went because Main Gen faulty// Grid return","kamg=
a.virgile@ihstowers.com","6370","17-12-2024 18:14:25","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003869899","Nko=
ulou Carriere carrefourt","","17-12-2024 18:11:10","17-12-2024 16:23:58","1=
7-12-2024 19:52:58","grid outage,site went down due to theft of battery Ge =
and alternator of Charge//grid return(remplacement ongoing)","Mba Lazare He=
rve","Site Asset Theft","Theft","Theft","Generator Battery Theft","grid out=
age,site went down due to theft of battery Ge and alternator of Charge//gri=
d return(remplacement ongoing)","kamga.virgile@ihstowers.com","6433","17-12=
-2024 18:11:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003869898","A=
wae Escalier","","17-12-2024 18:10:44","17-12-2024 17:49:38","17-12-2024 18=
:07:50","Grid outage, Site went down before Gen start due to poor backup// =
Grid power return  Power issue resolve at 06:07PM but site remains down at =
OCM THE TX FME George(697461814) from Huawei is informed","Albran Byorel","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","=
Grid outage, Site went down before Gen start due to poor backup// Grid powe=
r return  Power issue resolve at 06:07PM but site remains down at OCM THE T=
X FME George(697461814) from Huawei is informed","alexandre.kamal@ihstowers=
.com","1267","17-12-2024 18:10:44","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003869895","Sim=
bock MTN","IHS_YND_793","17-12-2024 18:10:00","17-12-2024 16:21:50","17-12-=
2024 17:55:37","Grid outage, site went down because gen ran untill fuel sho=
rtage // refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Di=
esel Outage","Grid outage, site went down because gen ran untill fuel short=
age // refueling done","kamga.virgile@ihstowers.com","6491","17-12-2024 18:=
10:00","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003869885","Elo=
umdem stade","","17-12-2024 18:08:46","17-12-2024 16:21:50","17-12-2024 17:=
55:37","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","Fanda Brice","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down because gen ran untill fuel=
 shortage // refueling done","kamga.virgile@ihstowers.com","279712","17-12-=
2024 18:08:46","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003869878","Sap=
eur","","17-12-2024 18:07:25","17-12-2024 16:18:17","17-12-2024 17:28:36","=
Grid outage, Site went down before Gen start due to poor backup// Grid powe=
r return","Mboua Thierry","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage, Site went down before Gen start due=
 to poor backup// Grid power return","kamga.virgile@ihstowers.com","6550","=
17-12-2024 18:07:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0003869874","E=
SSOS OASIS 1111","","17-12-2024 18:06:25","17-12-2024 17:04:17","17-12-2024=
 17:15:43","Active//No power issue on site Ubaie=3D54,6V site on Grid The t=
x fme Armand nguetsa(691144412) is informed notice that disjunction at OCM =
equipment","Siligap Boris","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie=
=3D54,6V site on Grid The tx fme Armand nguetsa(691144412) is informed noti=
ce that disjunction at OCM equipment","alexandre.kamal@ihstowers.com","3729=
","17-12-2024 18:06:25","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_544","NOCINC0003869852","Jean Vespa 2",""=
,"17-12-2024 18:03:10","","","Cascaded Incident from TTO3831729 - Cascade R=
emoved From TTO3831729","Mboua Thierry","","","","","","system","4584","17-=
12-2024 18:03:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003869849","J=
-Vespa","","17-12-2024 18:01:51","17-12-2024 16:46:46","17-12-2024 18:25:46=
","Grid outage// Grid return","Mboua Thierry","Grid Supply","Passive","Grid=
","National Grid - Grid Outage Issue","Grid outage// Grid return","alexandr=
e.kamal@ihstowers.com","4506","17-12-2024 18:01:51","Sagemcom CMR"
"Closed Complete","Warning","CTR_379","IHS_YND_277","NOCINC0003869808","Ngo=
ulmekong-Nord","","17-12-2024 17:55:00","","","Site on Battery due to grid =
outage//DG started automatically","Siligap Boris","Warning","Warning","POWE=
R","Warning - Site on Battery","Site on Battery due to grid outage//DG star=
ted automatically","alexandre.kamal@ihstowers.com","1565","17-12-2024 17:55=
:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003869751","C=
rf-Nsam","","17-12-2024 17:40:22","17-12-2024 17:37:18","17-12-2024 17:44:0=
2","site went down because the slot of rectifier burned//he reduice the loa=
d on site","MINKA NICOLAS","Fire on Site","Passive","Infrastructure","Fire =
- Burned","site went down because the slot of rectifier burned//he reduice =
the load on site","alexandre.kamal@ihstowers.com","185","17-12-2024 17:40:2=
2","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003869731","Mok=
olo Yaounde","","17-12-2024 17:38:08","17-12-2024 16:18:00","17-12-2024 17:=
26:32","Grid outage No space to deploy MDG// Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No space =
to deploy MDG// Grid return","kamga.virgile@ihstowers.com","4810","17-12-20=
24 17:38:08","Sagemcom CMR"
"Closed Complete","Warning","T0183","IHS_YND_184","NOCINC0003869641","Nkolm=
esseng","","17-12-2024 17:16:38","","","Grid outage, Site alarming because =
failed to start due static charger faulty// He started Gen manualy with ext=
ernal battery","Siligap Boris","Warning","Warning","POWER","Warning - Site =
on Battery","Grid outage, Site alarming because failed to start due static =
charger faulty// He started Gen manualy with external battery","dorothy.dja=
ntio@ihstowers.com","244","17-12-2024 17:16:38","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003869616","NKO=
MEKUI OCM","","17-12-2024 17:10:47","17-12-2024 16:18:17","17-12-2024 16:30=
:59","No power issue on site Ubaie: 54,1 V site on GEN. Site went down beca=
use is impacted by Mbankolo_camtel and not managing by IHS","TIENTCHEU NZET=
CHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure=
","Affected by 3rd Party Site","No power issue on site Ubaie: 54,1 V site o=
n GEN. Site went down because is impacted by Mbankolo_camtel and not managi=
ng by IHS","kamga.virgile@ihstowers.com","3151","17-12-2024 17:10:47","Sage=
mcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003869575","NYO=
M FACE MAETUR","","17-12-2024 17:00:34","17-12-2024 16:12:25","17-12-2024 1=
7:36:25","Grid bad voltage (Access issue due to landloard), landlord has fo=
rbiden to start the Gen Because the Noise //Grid voltage restored.","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop S=
witch","Grid bad voltage (Access issue due to landloard), landlord has forb=
iden to start the Gen Because the Noise //Grid voltage restored.","kamga.vi=
rgile@ihstowers.com","2890","17-12-2024 17:00:34","Sagemcom CMR"
"Closed Complete","Warning","T0652","IHS_YND_222","NOCINC0003869447","Jean =
Vespa","","17-12-2024 16:38:52","","","site on  low voltage due to grid out=
age//gen started","Mboua Thierry","Warning","Warning","POWER","Warning - Ba=
ttery Low Voltage","site on  low voltage due to grid outage//gen started","=
dorothy.djantio@ihstowers.com","185","17-12-2024 16:38:52","Sagemcom CMR"
"Closed Complete","Warning","T0129","IHS_YND_379","NOCINC0003869370","Eseka=
 MTN","","17-12-2024 16:24:15","","","GRID OUTAGE SITE WENT ALARM BEFORE GE=
N START // GEN START AUTOMATICALLY","Kemeni Franklin","Warning","Warning","=
POWER","Warning - Site on Battery","GRID OUTAGE SITE WENT ALARM BEFORE GEN =
START // GEN START AUTOMATICALLY","dorothy.djantio@ihstowers.com","247","17=
-12-2024 16:24:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0003869059","H=
-Paradis","","17-12-2024 15:29:15","17-12-2024 15:19:56","17-12-2024 16:18:=
01","Grid outage// He deployed MDG of 13KVA","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid outage// He deployed MDG of 1=
3KVA","alexandre.kamal@ihstowers.com","560","17-12-2024 15:29:15","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003869049","E=
kie sud","","17-12-2024 15:28:20","17-12-2024 15:14:17","17-12-2024 16:22:5=
2","Site went down because Gen failed to start due to Hybrid system dysfonc=
tion// He reset the gen card and Gen manually start","Albran Byorel","Equip=
ment Repair","Passive","Hybrid","Hybrid Module","Site went down because Gen=
 failed to start due to Hybrid system dysfonction// He reset the gen card a=
nd Gen manually start","alexandre.kamal@ihstowers.com","844","17-12-2024 15=
:28:20","Sagemcom CMR"
"Closed Complete","Warning","CTR_211","IHS_YND_248","NOCINC0003868741","Bit=
eng","","17-12-2024 14:36:21","","","site on battery due to grid outage//ge=
n started","Mba Lazare Herve","Warning","Warning","POWER","Warning - Site o=
n Battery","site on battery due to grid outage//gen started","dorothy.djant=
io@ihstowers.com","364","17-12-2024 14:36:21","Sagemcom CMR"
"Closed Complete","Warning","T0920","IHS_YND_416","NOCINC0003868638","Ngwop=
i Boga","","17-12-2024 14:20:54","","","grid outage, site went alarm becaus=
e gen fails to start due to grid bad voltage // he bypass grid and manually=
 start the gen","Kemeni Franklin","Warning","Warning","POWER","Warning - Si=
te on Battery","grid outage, site went alarm because gen fails to start due=
 to grid bad voltage // he bypass grid and manually start the gen","kouoh.j=
ean@ihstowers.com","320","17-12-2024 14:20:54","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003868280","Nko=
lbisson usines des eaux 2","","17-12-2024 13:21:14","17-12-2024 12:59:05","=
17-12-2024 13:21:18","Grid Outage Site Went down because  main alternator f=
aulty // He deployed MDG of 20Kva","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
placement","Passive","ACDG Gen","ACDG - Main Alternator","Grid Outage Site =
Went down because  main alternator faulty // He deployed MDG of 20Kva","lan=
dry.etame@ihstowers.com","1330","17-12-2024 13:21:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003868186","D=
amas","","17-12-2024 13:05:28","17-12-2024 12:56:20","17-12-2024 17:46:49",=
"Grid Outage Site went down because Gen Overload(9Kva,150A)// Grid return",=
"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid Outage Site went down because Gen Overload(9Kva,150A)// Grid return","=
stephane.nkamwa@ihstowers.com","549","17-12-2024 13:05:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0003868131","E=
seka Town","","17-12-2024 12:59:22","17-12-2024 12:50:17","17-12-2024 13:39=
:52","Grid outage, site went down because gen start and stopped with high t=
emp alarm // he added water and manually start the gen","Kemeni Franklin","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, site went down because gen start and stopped with=
 high temp alarm // he added water and manually start the gen","stephane.nk=
amwa@ihstowers.com","546","17-12-2024 12:59:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003868034","E=
bogo","","17-12-2024 12:38:04","17-12-2024 12:28:53","17-12-2024 13:10:14",=
"site went down due to work(Boris/657100525/Sagemcom, PM) // END OF WORKD",=
"Siligap Boris","Equipment Replacement","Passive","Planned Activity","Plann=
ed Activity - Passive","site went down due to work(Boris/657100525/Sagemcom=
, PM) // END OF WORKD","stephane.nkamwa@ihstowers.com","813","17-12-2024 12=
:38:04","Sagemcom CMR"
"Closed Complete","Warning","CTR_234","IHS_YND_415","NOCINC0003867947","Bog=
a-Mahole","","17-12-2024 12:23:10","","","grid outage, site went alarm befo=
re gen start // gen start automatically","Kemeni Franklin","Warning","Warni=
ng","POWER","Warning - Site on Battery","grid outage, site went alarm befor=
e gen start // gen start automatically","kouoh.jean@ihstowers.com","131","1=
7-12-2024 12:23:10","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0003867846","ELO=
UMDEM CARRIERE","","17-12-2024 12:01:22","17-12-2024 11:37:14","17-12-2024 =
12:51:20","Grid outage, site went down because Gen stopped due to low oil p=
ressure (unprouven alarm)//He reset Gen card  and Gen started Gen","Fanda B=
rice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
outage, site went down because Gen stopped due to low oil pressure (unprouv=
en alarm)//He reset Gen card  and Gen started Gen","landry.etame@ihstowers.=
com","1450","17-12-2024 12:01:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003867842","E=
kounou","","17-12-2024 12:00:54","17-12-2024 11:51:44","17-12-2024 12:54:27=
","site went down because gen failed to start due to grid bad voltage and p=
oor battery backup // he bypassed grid and gen manually started","Albran By=
orel","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","site went down because gen failed to start due to grid bad voltage and=
 poor battery backup // he bypassed grid and gen manually started","stephan=
e.nkamwa@ihstowers.com","551","17-12-2024 12:00:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003867798","A=
WAE OCM","","17-12-2024 11:50:46","17-12-2024 10:00:55","17-12-2024 12:30:5=
5","grid outage, site went down due to dysfunctionning of the PWC ZTE // Ge=
n manually started","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","grid outage, site went down due to dysf=
unctionning of the PWC ZTE // Gen manually started","kouoh.jean@ihstowers.c=
om","6592","17-12-2024 11:50:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003867761","B=
itoto","","17-12-2024 11:42:24","17-12-2024 10:14:32","17-12-2024 12:21:30"=
,"grid outage, site went down due to dysfunctionning of the PWC ZTE // Gen =
manually started","Mba Lazare Herve","Equipment Repair","Passive","Rectifie=
r","Rectifier Module Overloaded","grid outage, site went down due to dysfun=
ctionning of the PWC ZTE // Gen manually started","kouoh.jean@ihstowers.com=
","5274","17-12-2024 11:42:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0003867691","B=
ondjock","","17-12-2024 11:30:05","17-12-2024 11:26:58","17-12-2024 11:31:1=
8","Grid outage,site went down before gen starts due to poor battery backup=
//Gen started automatically","Fanda Brice","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage,site went down befo=
re gen starts due to poor battery backup//Gen started automatically","steph=
ane.nkamwa@ihstowers.com","188","17-12-2024 11:30:05","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0003867554","NKO=
LMEKONG YDE","","17-12-2024 11:20:08","17-12-2024 11:01:49","17-12-2024 13:=
11:01","site went down due to work(Fabrice/692852620/ Sagemcom, PM) // End =
of work","Fabrice Pouakam","Equipment Replacement","Passive","Planned Activ=
ity","Planned Activity - Passive","site went down due to work(Fabrice/69285=
2620/ Sagemcom, PM) // End of work","landry.etame@ihstowers.com","1100","17=
-12-2024 11:20:08","Sagemcom CMR"
"Closed Complete","Site Down","T1547","IHS_YND_064","NOCINC0003867241","HOP=
ITAL DE LA CAISSE","IHS_YND_024","17-12-2024 11:01:16","17-12-2024 10:47:12=
","17-12-2024 11:42:47","grid outage, Gen failed to start because battery d=
ischarge due to mass at preheating level // Gen manually started with exter=
nal battery, site on gen","Delor Telezing","Equipment Repair","Passive","AC=
DG Gen","ACDG - Generator Battery","grid outage, Gen failed to start becaus=
e battery discharge due to mass at preheating level // Gen manually started=
 with external battery, site on gen","landry.etame@ihstowers.com","845","17=
-12-2024 11:01:16","Sagemcom CMR"
"Closed Complete","Site Down","T0219","IHS_YND_024","NOCINC0003867218","Gar=
bati building","","17-12-2024 10:57:15","17-12-2024 10:47:12","17-12-2024 1=
1:42:47","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","grid outage, Gen failed to start because battery discharg=
e due to mass at preheating level // Gen manually started with external bat=
tery, site on gen","landry.etame@ihstowers.com","270989","17-12-2024 10:57:=
15","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003867189","OLA=
MA","","17-12-2024 10:50:03","17-12-2024 10:38:58","17-12-2024 10:51:34","G=
rid outage site went down because Gen failed due to gen card dysfonction //=
 He reset the Gen card and Gen manually started ( site impacted by Akono)",=
"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","Grid outage site went down because Gen failed due to gen card dysfonctio=
n // He reset the Gen card and Gen manually started ( site impacted by Akon=
o)","landry.etame@ihstowers.com","666","17-12-2024 10:50:03","Sagemcom CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0003867136","Ako=
no","","17-12-2024 10:39:47","","","Site on battery due to ACDG control pan=
el dysfonctioning//Reset DG card and manually start of DG.","Fanda Brice","=
Warning","Warning","POWER","Warning - Gen Off","Site on battery due to ACDG=
 control panel dysfonctioning//Reset DG card and manually start of DG.","ko=
uoh.jean@ihstowers.com","256","17-12-2024 10:39:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003867129","S=
tade-Abega","","17-12-2024 10:37:35","17-12-2024 10:05:28","17-12-2024 12:0=
4:55","grid outage, site went down due to dysfunctionning of the PWC ZTE //=
 Gen manually started	","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","grid outage, site went down due to =
dysfunctionning of the PWC ZTE // Gen manually started	","stephane.nkamwa@i=
hstowers.com","1928","17-12-2024 10:37:35","Sagemcom CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0003867039","Emo=
mbo Esssomba","","17-12-2024 10:26:51","17-12-2024 10:23:47","17-12-2024 11=
:30:33","Grid outage, site went down due to dysfunctionning of the PWC ZTE =
// Gen manually started.","Mba Lazare Herve","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Grid outage, site went down due t=
o dysfunctionning of the PWC ZTE // Gen manually started.","landry.etame@ih=
stowers.com","185","17-12-2024 10:26:51","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003867021","Nko=
mo stade","","17-12-2024 10:24:34","17-12-2024 10:20:27","17-12-2024 11:20:=
13","Grid outage,site went down due to PWC ZTE dysfunctioning// bypass Grid=
 and Manually start of DG.","Mba Lazare Herve","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module Overloaded","Grid outage,site went down due =
to PWC ZTE dysfunctioning// bypass Grid and Manually start of DG.","landry.=
etame@ihstowers.com","247","17-12-2024 10:24:34","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0003866976","Ngo=
usso Vallee","","17-12-2024 10:16:53","17-12-2024 10:07:48","17-12-2024 10:=
56:32","grid outage, site went down because gen start and stoppen due to lo=
w oil pressure // He reset gen card and gen manually started","Siligap Bori=
s","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid out=
age, site went down because gen start and stoppen due to low oil pressure /=
/ He reset gen card and gen manually started","landry.etame@ihstowers.com",=
"546","17-12-2024 10:16:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003866898","E=
kounou","","17-12-2024 10:05:22","17-12-2024 09:57:07","17-12-2024 11:16:53=
","grid outage, site went down because gen failed to start due to alarm Hig=
ht temperature and poor battery backup // Gen manually started","Albran Byo=
rel","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","grid outage, site went down because gen failed to start due to alarm =
Hight temperature and poor battery backup // Gen manually started","stephan=
e.nkamwa@ihstowers.com","496","17-12-2024 10:05:22","Sagemcom CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0003866883","Ngo=
usso-Savana","","17-12-2024 10:03:07","17-12-2024 09:50:54","17-12-2024 10:=
39:15","grid outage, site went down because gen failed to start due to dysf=
unctionning of the gen card // He reset gen card and gen manually started",=
"Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","grid outage, site went down because gen failed to start due to dysfunc=
tionning of the gen card // He reset gen card and gen manually started","la=
ndry.etame@ihstowers.com","734","17-12-2024 10:03:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003866652","AWAE OCM=
","","17-12-2024 09:25:41","17-12-2024 09:07:00","17-12-2024 10:00:08","Cas=
caded Incident from TTO3827962","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","access issue due to landload, grid =
outage, site went down because gen ran until fuel shortage // Refueling don=
e","system","269686","17-12-2024 09:25:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003866653","Essomba"=
,"","17-12-2024 09:25:41","17-12-2024 09:07:00","17-12-2024 10:40:08","Casc=
aded Incident from TTO3827962","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","access issue due to landload, grid o=
utage, site went down because gen ran until fuel shortage // Refueling done=
","system","269687","17-12-2024 09:25:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003866654","Biteng-M=
aetur","","17-12-2024 09:25:41","17-12-2024 09:07:00","17-12-2024 10:40:08"=
,"Cascaded Incident from TTO3827962","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","access issue due to landload, =
grid outage, site went down because gen ran until fuel shortage // Refuelin=
g done","system","269689","17-12-2024 09:25:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003866631","B=
itoto","","17-12-2024 09:21:08","17-12-2024 09:07:00","17-12-2024 10:13:08"=
,"","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","access issue due to landload, grid outage, site went down becau=
se gen ran until fuel shortage // Refueling done","stephane.nkamwa@ihstower=
s.com","269686","17-12-2024 09:21:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_111","NOCINC0003866623","Essos Ma=
rche","","17-12-2024 09:18:40","17-12-2024 09:03:29","17-12-2024 09:42:54",=
"Cascaded Incident from TTO3827940 - Cascade Removed From TTO3827940","Delo=
r Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Tem=
p - Clogged Radiator","GEN stooped due to high temp. // Coolant added and M=
anual start of GEN. ","system","911","17-12-2024 09:18:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003866617","B=
iteng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179, IHS_YND_249","1=
7-12-2024 09:17:08","17-12-2024 09:07:00","17-12-2024 10:40:08","access iss=
ue due to landload, grid outage, site went down because gen ran until fuel =
shortage // Refueling done","Mba Lazare Herve","Access Denial","Lease Or Le=
gal","Landlord Related Issues","Access Issue - Land Lord","access issue due=
 to landload, grid outage, site went down because gen ran until fuel shorta=
ge // Refueling done","stephane.nkamwa@ihstowers.com","609","17-12-2024 09:=
17:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0003866598","T=
radex-Nkomo","","17-12-2024 09:14:12","17-12-2024 09:07:00","17-12-2024 10:=
40:08","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","access issue due to landload, grid outage, site went down be=
cause gen ran until fuel shortage // Refueling done","stephane.nkamwa@ihsto=
wers.com","269688","17-12-2024 09:14:12","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0003866545","ELO=
UMDEM CARRIERE","","17-12-2024 09:02:12","17-12-2024 08:52:04","17-12-2024 =
09:31:04","Grid outage, site went down because Gen stopped due to  Alarm ""=
low oil pressure ""//He reset Gen card and started Gen(investigation ongoin=
g)","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid outage, site went down because Gen stopped due to  Alarm ""low =
oil pressure ""//He reset Gen card and started Gen(investigation ongoing)",=
"landry.etame@ihstowers.com","611","17-12-2024 09:02:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_625","IHS_YND_181","NOCINC0003866457","M=
imboman3","","17-12-2024 08:44:31","17-12-2024 08:40:23","17-12-2024 09:31:=
40","grid outage, site went down due to dysfunctionning of the new PWC ZTE =
// gen manually started","Mba Lazare Herve","Equipment Repair","Passive","R=
ectifier","Rectifier Module Overloaded","grid outage, site went down due to=
 dysfunctionning of the new PWC ZTE // gen manually started","stephane.nkam=
wa@ihstowers.com","249","17-12-2024 08:44:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0003866426","E=
mombo","","17-12-2024 08:39:24","17-12-2024 08:31:19","17-12-2024 08:36:21"=
,"site went down because PWC CB off//PW CB rearmed","Mba Lazare Herve","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker I=
ssue","site went down because PWC CB off//PW CB rearmed","stephane.nkamwa@i=
hstowers.com","486","17-12-2024 08:39:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003866423","M=
imboman-Ecole","","17-12-2024 08:38:44","17-12-2024 08:30:00","17-12-2024 0=
8:35:49","No power issue on site Ubaie=3D54.3V site on Grid.The FME TX Elou=
ndou Bertrant / 693212405/  From Huawei  is Informed,and up at 08:35 AM","M=
ba Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue on site Ubaie=3D54.3V site on G=
rid.The FME TX Eloundou Bertrant / 693212405/  From Huawei  is Informed,and=
 up at 08:35 AM","stephane.nkamwa@ihstowers.com","525","17-12-2024 08:38:44=
","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003866069","NKO=
MEKUI OCM","","17-12-2024 07:16:43","17-12-2024 07:04:37","17-12-2024 07:10=
:41","No power issue on site U=3D54.5  V site on Gen.site impacted by Mbank=
olo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site U=3D54.5  V site on Gen.site impacted by Mbankolo Ca=
mtel and not managing by IHS","landry.etame@ihstowers.com","727","17-12-202=
4 07:16:43","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0003865900","ELO=
UMDEM CARRIERE","","17-12-2024 06:40:13","17-12-2024 06:13:05","17-12-2024 =
06:55:56","grid outage, Site went down because Gen fails to start due to Ge=
n battery discharged //Gen manually started with external battery(investiga=
tion ongoing)","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG =
- Generator Battery","grid outage, Site went down because Gen fails to star=
t due to Gen battery discharged //Gen manually started with external batter=
y(investigation ongoing)","landry.etame@ihstowers.com","1629","17-12-2024 0=
6:40:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003865797","Ngoum","=
","17-12-2024 06:12:51","17-12-2024 05:56:42","17-12-2024 06:00:17","Cascad=
ed Incident from TTO3826997","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Cascaded Incident from TTO3826997","system",=
"266962","17-12-2024 06:12:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003865798","Yoko MTN=
","","17-12-2024 06:12:51","17-12-2024 05:56:42","17-12-2024 06:00:17","Cas=
caded Incident from TTO3826997","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Cascaded Incident from TTO3826997","syste=
m","266961","17-12-2024 06:12:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003865796","Matsari"=
,"","17-12-2024 06:12:51","17-12-2024 05:56:42","17-12-2024 06:00:17","Casc=
aded Incident from TTO3826997","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Cascaded Incident from TTO3826997","system=
","266962","17-12-2024 06:12:51","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003865794","MBI=
MBIM","IHS_YND_460, IHS_YND_475, IHS_YND_473","17-12-2024 06:11:51","17-12-=
2024 05:56:42","17-12-2024 06:00:17","Active//No power issue on site Ubaie=
=3D54.5V, Site on Gen, The Tx Fme Gregoire( 652070658)from Huawei is inform=
ed.","Parker Tchoup","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie=3D54.=
5V, Site on Gen, The Tx Fme Gregoire( 652070658)from Huawei is informed.","=
alwine.fambou@ihstowers.com","910","17-12-2024 06:11:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003864820","E=
kounou","","17-12-2024 00:11:49","17-12-2024 00:09:44","17-12-2024 00:19:44=
","Grid outage, site went down before gen start due to poor battery backup =
// gen start automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // gen start automatically","rous=
elle.schoune@ihstowers.com","392","17-12-2024 00:11:49","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0003864670","Nko=
lbisson IITA LP","","16-12-2024 23:16:30","16-12-2024 23:13:12","16-12-2024=
 23:22:12","Grid outage, no space to deploy a mobile gen // grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy a mobile gen // grid return","alwine.fambou@ihsto=
wers.com","199","16-12-2024 23:16:30","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003864507","Nom=
ayos montee Meche","","16-12-2024 22:38:14","16-12-2024 22:30:05","17-12-20=
24 07:13:15","Access issue during the night due to landloard,site went down=
    malfunction  PWC  DPC//Gen started manually","Fanda Brice","Access Deni=
al","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","=
Access issue during the night due to landloard,site went down    malfunctio=
n  PWC  DPC//Gen started manually","alwine.fambou@ihstowers.com","489","16-=
12-2024 22:38:14","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003864254","Com=
plex Beac II","","16-12-2024 21:56:14","16-12-2024 21:48:06","16-12-2024 22=
:35:06","Site went down due to insufficiency of rectifiers(2/3) // Site sta=
bilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficiency of rectifiers(2/3) // Site s=
tabilized","dorothy.djantio@ihstowers.com","488","16-12-2024 21:56:14","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003864229","Ngouetou=
","","16-12-2024 21:51:40","16-12-2024 20:56:24","16-12-2024 20:59:53","Cas=
caded Incident from TTO3824974","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site ,site on G=
EN  wiith Ubaie=3D54.3 V The TX FME Gregoire/ 654547479/ From Huawei is inf=
ormed and Up at 08:58 PM","system","263296","16-12-2024 21:51:40","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003864165","Yoko MTN=
","","16-12-2024 21:46:41","16-12-2024 20:56:24","16-12-2024 20:59:53","Cas=
caded Incident from TTO3824974","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site ,site on G=
EN  wiith Ubaie=3D54.3 V The TX FME Gregoire/ 654547479/ From Huawei is inf=
ormed and Up at 08:58 PM","system","263297","16-12-2024 21:46:41","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003864164","Ngoum","=
","16-12-2024 21:46:40","16-12-2024 20:56:24","16-12-2024 20:59:53","Cascad=
ed Incident from TTO3824974","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue on site ,site on GEN =
 wiith Ubaie=3D54.3 V The TX FME Gregoire/ 654547479/ From Huawei is inform=
ed and Up at 08:58 PM","system","263297","16-12-2024 21:46:40","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003864162","MBIMBIM"=
,"","16-12-2024 21:46:40","16-12-2024 20:56:24","16-12-2024 20:59:53","Casc=
aded Incident from TTO3824974","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue on site ,site on GE=
N  wiith Ubaie=3D54.3 V The TX FME Gregoire/ 654547479/ From Huawei is info=
rmed and Up at 08:58 PM","system","263295","16-12-2024 21:46:40","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003864163","Matsari"=
,"","16-12-2024 21:46:40","16-12-2024 20:56:24","16-12-2024 20:59:53","Casc=
aded Incident from TTO3824974","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue on site ,site on GE=
N  wiith Ubaie=3D54.3 V The TX FME Gregoire/ 654547479/ From Huawei is info=
rmed and Up at 08:58 PM","system","263296","16-12-2024 21:46:40","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003864125","Dong",""=
,"16-12-2024 21:43:30","16-12-2024 20:56:24","16-12-2024 20:59:53","Cascade=
d Incident from TTO3824974","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue on site ,site on GEN  =
wiith Ubaie=3D54.3 V The TX FME Gregoire/ 654547479/ From Huawei is informe=
d and Up at 08:58 PM","system","263296","16-12-2024 21:43:30","Sagemcom CMR=
"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0003864123","Don=
ga","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_YND_444, IHS_Y=
ND_473","16-12-2024 21:42:40","16-12-2024 20:56:24","16-12-2024 20:59:53","=
Active//No power issue on site ,site on GEN  wiith Ubaie=3D54.3 V The TX FM=
E Gregoire/ 654547479/ From Huawei is informed and Up at 08:58 PM","Parker =
Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No power issue on site ,site on GEN  wiith Ubai=
e=3D54.3 V The TX FME Gregoire/ 654547479/ From Huawei is informed and Up a=
t 08:58 PM","etienne.itondo@ihstowers.com","2777","16-12-2024 21:42:40","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003863955","Com=
plex Beac II","","16-12-2024 21:18:03","16-12-2024 21:10:57","16-12-2024 21=
:20:33","Site went down due to insufficiency of rectifiers(2/3) //Site stab=
ilized..","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to insufficiency of rectifiers(2/3) //Site s=
tabilized..","dorothy.djantio@ihstowers.com","426","16-12-2024 21:18:03","S=
agemcom CMR"
"Closed Complete","Warning","","IHS_YND_473","NOCINC0003863898","Yoko MTN",=
"","16-12-2024 21:06:31","","","Alarm not proven,site on DG,Ubaie:54.2V; ",=
"Parker Tchoup","Warning","Warning","SYSTEM","Warning - False Alarm","Alarm=
 not proven,site on DG,Ubaie:54.2V; ","system","553","16-12-2024 21:06:31",=
"Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_456","NOCINC0003863896","MBIMBIM","=
","16-12-2024 21:06:30","","","Alarm not proven,site on DG,Ubaie:54V; ","Pa=
rker Tchoup","Warning","Warning","SYSTEM","Warning - Communication Failure"=
,"Alarm not proven,site on DG,Ubaie:54V; ","system","552","16-12-2024 21:06=
:30","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_460","NOCINC0003863897","Matsari","=
","16-12-2024 21:06:30","","","Alarm not proven,site on DG,Ubaie:54.2V; ","=
Parker Tchoup","Warning","Warning","SYSTEM","Warning - False Alarm","Alarm =
not proven,site on DG,Ubaie:54.2V; ","system","552","16-12-2024 21:06:30","=
Sagemcom CMR"
"Cancelled","Warning","T1062","IHS_YND_475","NOCINC0003863883","Ngoum","IHS=
_YND_456, IHS_YND_460, IHS_YND_473","16-12-2024 21:04:27","","","","Parker =
Tchoup","","","","","","dorothy.djantio@ihstowers.com","429","16-12-2024 21=
:04:27","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003863715","SOA=
 UNIVERSITY STADIUM","","16-12-2024 20:40:17","16-12-2024 20:34:09","16-12-=
2024 20:44:11","Grid outage, Site went down due to PWC ""ZTE' dysfunction//=
 Grid return","Siligap Boris","Equipment Repair","Passive","Rectifier","Rec=
tifier Module Overloaded","Grid outage, Site went down due to PWC ""ZTE' dy=
sfunction// Grid return","dorothy.djantio@ihstowers.com","369","16-12-2024 =
20:40:17","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003863706","Com=
plex Beac II","","16-12-2024 20:39:06","16-12-2024 20:32:51","16-12-2024 20=
:43:57","Grid fluctuation, site went down because Gen failed to stard due t=
o Grid bad voltage no rcp // Grid stabilized","Albran Byorel","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on, site went down because Gen failed to stard due to Grid bad voltage no r=
cp // Grid stabilized","dorothy.djantio@ihstowers.com","376","16-12-2024 20=
:39:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003863347","SOA VILL=
AGE","","16-12-2024 19:43:00","16-12-2024 19:39:25","16-12-2024 19:44:33","=
Cascaded Incident from TTO3824052","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation site went down bec=
ause Gen and started and stopped due to Grid bad voltage // He bypass the G=
rid and Gen manually started","system","267640","16-12-2024 19:43:00","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0003863343","S=
OA TOWN","IHS_YND_323","16-12-2024 19:41:42","16-12-2024 19:37:33","16-12-2=
024 19:45:02","Grid fluctuation site went down because Gen and started and =
stopped due to Grid bad voltage // He bypass the Grid and Gen manually star=
ted","Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","Grid fluctuation site went down because Gen and started=
 and stopped due to Grid bad voltage // He bypass the Grid and Gen manually=
 started","olivier.kwedi@ihstowers.com","249","16-12-2024 19:41:42","Sagemc=
om CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003863042","Lad=
a I Yde","","16-12-2024 18:49:46","16-12-2024 18:42:40","16-12-2024 20:09:4=
8","Grid fluctuation, Site went down because Gen failed to start due Grid b=
ad voltage no rcp// He bypassed Grid and started Gen manualy","Mba Lazare H=
erve","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, Site went down because Gen failed to start due Grid =
bad voltage no rcp// He bypassed Grid and started Gen manualy","dorothy.dja=
ntio@ihstowers.com","427","16-12-2024 18:49:46","Sagemcom CMR"
"Closed Complete","Site Down","T1740","IHS_YND_114","NOCINC0003862609","Kon=
dengui","","16-12-2024 17:22:10","16-12-2024 17:07:51","16-12-2024 17:26:54=
","Grid outage, Site went down because Gen started and stopped due to High =
Temp causing by Radiator pierced// Grid return (repairment radiator ongoing=
)","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator=
 Leakage","Grid outage, Site went down because Gen started and stopped due =
to High Temp causing by Radiator pierced// Grid return (repairment radiator=
 ongoing)","etienne.itondo@ihstowers.com","918","16-12-2024 17:22:10","Sage=
mcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003862432","Nko=
abang Ebolmedjock","","16-12-2024 16:42:10","16-12-2024 16:37:06","16-12-20=
24 18:43:26","Site went due to work: Herve Lazarre/657108482/SAGEMCOM and B=
laise Raul SS IHS working on site (GENERATOR MAINTENANCE)// End of work","M=
ba Lazare Herve","Installation Activity","Passive","Planned Activity","Inst=
allation Activity","Site went due to work: Herve Lazarre/657108482/SAGEMCOM=
 and Blaise Raul SS IHS working on site (GENERATOR MAINTENANCE)// End of wo=
rk","dorothy.djantio@ihstowers.com","305","16-12-2024 16:42:10","Sagemcom C=
MR"
"Closed Complete","Warning","T0139","IHS_YND_381","NOCINC0003862377","Boumn=
yebel","","16-12-2024 16:33:48","","","Grid outage, Site alarming on batter=
y bacause Gen started but did not feeds the site due to Gen contactor dysfu=
nction// He blocked Gen contactor, Site on Gen","Kemeni Franklin","Warning"=
,"Warning","POWER","Warning - Site on Battery","Grid outage, Site alarming =
on battery bacause Gen started but did not feeds the site due to Gen contac=
tor dysfunction// He blocked Gen contactor, Site on Gen","ludivine.ngamaleu=
@ihstowers.com","4","16-12-2024 16:33:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0003862174","K=
ondengui","","16-12-2024 15:59:52","16-12-2024 15:54:46","16-12-2024 16:16:=
47","Grid outage.gen failed to start due to ""high temp"""" alarm// We add =
water and gen manually started ","Albran Byorel","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Radiator Leakage","Grid outage.gen failed to start du=
e to ""high temp"""" alarm// We add water and gen manually started ","olivi=
er.kwedi@ihstowers.com","307","16-12-2024 15:59:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003861982","c=
hina embassy yde","","16-12-2024 15:29:55","16-12-2024 15:25:49","16-12-202=
4 16:21:38","Active//No power issue on site Ubaie=3D53,3V site on Grid The =
Tx Fme Eloundou/693212405 of huawei is informed ","","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site Ubaie=3D53,3V site on Grid The Tx Fme Eloundou/6932124=
05 of huawei is informed ","olivier.kwedi@ihstowers.com","247","16-12-2024 =
15:29:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0003861746","L=
eboudi","","16-12-2024 14:39:18","16-12-2024 14:00:12","16-12-2024 18:10:55=
","No power issue site on gen with U=3D54v Bouopda Herbert (655013645) from=
 ZTE is working on site from integration L26","TIENTCHEU NZETCHIEU GAEL","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue site on gen with U=3D54v Bouopda Herbert (65501364=
5) from ZTE is working on site from integration L26","olivier.kwedi@ihstowe=
rs.com","2347","16-12-2024 14:39:18","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0003861694","UPA=
C LP","","16-12-2024 14:29:40","16-12-2024 14:11:29","16-12-2024 18:47:26",=
"Grid outage no space to deploy mobile gen// grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space =
to deploy mobile gen// grid return","kamga.virgile@ihstowers.com","1092","1=
6-12-2024 14:29:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0003860832","L=
eboudi","","16-12-2024 12:21:41","16-12-2024 12:05:32","16-12-2024 12:15:26=
","No power issue Ubaie=3D 54.3 V site on Gen  The TX FME Mohamadou /691144=
435/ from huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue Ubaie=3D 54.3 V site on Gen The TX FME Mohamadou /691144435/ from =
huawei is informed
","alexandre.kamal@ihstowers.com","969","16-12-2024 12:21:41","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0003859034","Ekekam",=
"","16-12-2024 10:11:25","16-12-2024 09:39:44","16-12-2024 09:45:24","Casca=
ded Incident from TTO3818722","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","	Active//No power issue, site on=
 grid U=3D55.3V, TX FME Mohamadou/691144435 from huawei is working on site"=
,"system","267727","16-12-2024 10:11:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0003859035","NKONGKAR=
AK","","16-12-2024 10:11:25","16-12-2024 09:39:44","16-12-2024 09:45:24","C=
ascaded Incident from TTO3818722","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","	Active//No power issue, sit=
e on grid U=3D55.3V, TX FME Mohamadou/691144435 from huawei is working on s=
ite","system","267725","16-12-2024 10:11:25","Sagemcom CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0003858688","LOB=
O MTN","IHS_YND_714, IHS_YND_713","16-12-2024 09:48:56","16-12-2024 09:39:4=
4","16-12-2024 09:45:24","	Active//No power issue, site on grid U=3D55.3V, =
TX FME Mohamadou/691144435 from huawei is working on site","TIENTCHEU NZETC=
HIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","	Active//No power issue, site on grid U=3D55.3V, TX =
FME Mohamadou/691144435 from huawei is working on site","kamga.virgile@ihst=
owers.com","553","16-12-2024 09:48:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003857314","c=
hina embassy yde","","16-12-2024 08:38:18","16-12-2024 08:23:57","16-12-202=
4 08:49:43","Grid outage No space to deploy MDG //Grid power return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e No space to deploy MDG //Grid power return","alexandre.kamal@ihstowers.co=
m","862","16-12-2024 08:38:18","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003856272","Mim=
boman3","","16-12-2024 06:58:48","16-12-2024 06:53:35","16-12-2024 07:49:06=
","Grid outage site went down because PWC of ZTE DYSFONCTION // He reset an=
d Gen manually started","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Grid outage site went down because =
PWC of ZTE DYSFONCTION // He reset and Gen manually started","kamga.virgile=
@ihstowers.com","314","16-12-2024 06:58:48","Sagemcom CMR"
"Closed Complete","Site Down","T0530","IHS_YND_252","NOCINC0003856200","Kow=
eit City","","16-12-2024 06:42:41","16-12-2024 06:22:35","16-12-2024 16:25:=
07","No power issue on site U=3D54,3v site on grid Tx fme Lionnel steeve/65=
5184876 of huawei is informed","Albran Byorel","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D54,3v site on grid Tx fme Lionnel steeve/655184876 of huawei is =
informed","kamga.virgile@ihstowers.com","1207","16-12-2024 06:42:41","Sagem=
com CMR"
"Closed Complete","Warning","","IHS_YND_202","NOCINC0003855993","Cite-Verte=
","","16-12-2024 05:48:59","","","Grid outage// Grid return","","Warning","=
Warning","POWER","Warning - Site on Battery","Grid outage// Grid return","j=
oelle.ekessi@ihstowers.com","65","16-12-2024 05:48:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0003855603","Jean Ves=
pa 2","","16-12-2024 03:38:10","16-12-2024 03:32:49","16-12-2024 04:02:55",=
"Cascaded Incident from TTO3815366","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen failed to start du=
e to No automatism on site //Gen manually started","system","268057","16-12=
-2024 03:38:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003855600","J=
-Vespa","IHS_YND_544","16-12-2024 03:37:03","16-12-2024 03:32:49","16-12-20=
24 04:02:55","grid outage,gen failed to start due to No automatism on site =
//Gen manually started","Mboua Thierry","Equipment Repair","Passive","Contr=
ol Panel","ATS-AMF Issue","grid outage,gen failed to start due to No automa=
tism on site //Gen manually started","emmanuel.ghani@ihstowers.com","254","=
16-12-2024 03:37:03","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003855477","NKO=
MEKUI OCM","","16-12-2024 02:51:13","16-12-2024 02:48:03","16-12-2024 04:51=
:03","No power issue on site U=3D54,5v site on gen  site impacted by Mbanko=
lo Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","Affected by 3rd Party =
Site","No power issue on site U=3D54,5v site on gen  site impacted by Mbank=
olo Camtel and not managing by IHS","christian.fonkou@ihstowers.com","191",=
"16-12-2024 02:51:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003854794","M=
ini-Ferme","","15-12-2024 23:58:32","15-12-2024 23:39:25","16-12-2024 16:20=
:52","No power issue on site Ubaie=3D54.4V site on GRID THE fme Tx Mouamado=
u /691 144 435/ Huawei is informed","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
baie=3D54.4V site on GRID THE fme Tx Mouamadou /691 144 435/ Huawei is info=
rmed","emmanuel.ghani@ihstowers.com","1148","15-12-2024 23:58:32","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0003854743","E=
ntree Cite Verte","","15-12-2024 23:38:18","15-12-2024 23:29:15","16-12-202=
4 00:10:15","No power issue on site U=3D53,5v site on grid Tx fme Brice Sta=
gue of huawei is informed","Paul BIBOUM","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 U=3D53,5v site on grid Tx fme Brice Stague of huawei is informed","emmanue=
l.ghani@ihstowers.com","544","15-12-2024 23:38:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003853652","M=
vog-Manga","","15-12-2024 22:02:07","15-12-2024 22:00:00","15-12-2024 22:17=
:00","site went down due to lack of one phase and gen failed to start//he d=
id a bridge on good phase","Albran Byorel","Grid Supply","Passive","Grid","=
National Grid - Grid Incomplete Phase","site went down due to lack of one p=
hase and gen failed to start//he did a bridge on good phase","rouselle.scho=
une@ihstowers.com","128","15-12-2024 22:02:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003853641","M=
ontee-Jouvence-II","","15-12-2024 21:59:23","15-12-2024 21:56:17","15-12-20=
24 21:59:17","site went down because PWC overload (12Kilo, 260A)//site stab=
ilized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","site went down because PWC overload (12Kilo, 260A)//s=
ite stabilized","rouselle.schoune@ihstowers.com","187","15-12-2024 21:59:23=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0003853332","C=
lge-Advantiste","","15-12-2024 20:57:15","15-12-2024 20:55:11","15-12-2024 =
21:00:11","grid fluctuation, site went down because gen fails to start due =
to grid bad voltage // he bypass grid and manually start the gen","MINKA NI=
COLAS","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid fluctuation, site went down because gen fails to start due to grid bad=
 voltage // he bypass grid and manually start the gen","rouselle.schoune@ih=
stowers.com","124","15-12-2024 20:57:15","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0003853227","Mba=
nkolo petit paris","","15-12-2024 20:35:43","15-12-2024 20:20:48","15-12-20=
24 21:04:14","SITE CASCADED BEHING TTO3812651","Mboua Thierry","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Site went down because =
CB(80A) Disjunted in the DC-BOX MTN// he made a bridge with 50A  and Site i=
s on Grid","alwine.fambou@ihstowers.com","272787","15-12-2024 20:35:43","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0003853217","AFE=
ME NORD","IHS_YND_808","15-12-2024 20:34:55","15-12-2024 20:20:48","15-12-2=
024 21:04:14","Site went down because CB(80A) Disjunted in the DC-BOX MTN//=
 he made a bridge with 50A  and Site is on Grid","TIENTCHEU NZETCHIEU GAEL"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Brea=
ker Issue","Site went down because CB(80A) Disjunted in the DC-BOX MTN// he=
 made a bridge with 50A  and Site is on Grid","alwine.fambou@ihstowers.com"=
,"848","15-12-2024 20:34:55","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003852171","ODZ=
A MINKAN EDIBI ASSI","","15-12-2024 18:13:43","15-12-2024 18:05:23","15-12-=
2024 23:55:23","ACTIVE, no power issue , U=3D54V on grid, tx fme Lionel/655=
 18 48 76/ From HUAWEI is informed.","Albran Byorel","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE, no=
 power issue , U=3D54V on grid, tx fme Lionel/655 18 48 76/ From HUAWEI is =
informed.","alwine.fambou@ihstowers.com","501","15-12-2024 18:13:43","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0003851745","E=
mombo","","15-12-2024 16:53:24","15-12-2024 16:51:20","15-12-2024 17:21:20"=
,"Site on gen due to grid outage, site went down because gen stopped with l=
ow oil pressure alarm // he added oil and manually started","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Site on=
 gen due to grid outage, site went down because gen stopped with low oil pr=
essure alarm // he added oil and manually started","rouselle.schoune@ihstow=
ers.com","124","15-12-2024 16:53:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_729","NOCINC0003851623","Nkolbiss=
on IITA LP","","15-12-2024 16:33:17","15-12-2024 16:11:13","16-12-2024 01:2=
2:13","No power issue site on battery Ubaie=3D53,7V   Impacted by Nkolbisso=
n 2 OCM not managing by IHS.","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","Affected by 3rd Party Site","No power issue site on=
 battery Ubaie=3D53,7V   Impacted by Nkolbisson 2 OCM not managing by IHS."=
,"alwine.fambou@ihstowers.com","1325","15-12-2024 16:33:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0003851621","Scalom",=
"","15-12-2024 16:32:08","15-12-2024 16:12:48","15-12-2024 17:20:48"," Site=
 went down due to 01/06 rectifiers(a refurbished one) is faulty // he repla=
ce it: site on grid","Paul BIBOUM","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module"," Site went down due to 01/06 rectifiers(a refurbished =
one) is faulty // he replace it: site on grid","alwine.fambou@ihstowers.com=
","1161","15-12-2024 16:32:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003851197","Akak-Nko=
zoa-MTN-IHS","","15-12-2024 15:33:40","15-12-2024 15:20:57","15-12-2024 15:=
40:57","Cascaded Incident from TTO3810131","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, Site went do=
wn because PWC dysfonctionning // He bypass it and started Gen manualy","sy=
stem","275999","15-12-2024 15:33:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003851161","S=
oa-II","IHS_YND_316, IHS_YND_324","15-12-2024 15:31:46","15-12-2024 15:20:5=
7","15-12-2024 15:40:57","Grid outage, Site went down because PWC dysfoncti=
onning // He bypass it and started Gen manualy","Siligap Boris","Equipment =
Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage, S=
ite went down because PWC dysfonctionning // He bypass it and started Gen m=
anualy","rouselle.schoune@ihstowers.com","649","15-12-2024 15:31:46","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003851046","T=
ongolo OCM","","15-12-2024 15:14:24","15-12-2024 15:02:53","15-12-2024 15:4=
6:53","Site on gen due to grid outage, site went down because landloard shu=
t down generator due to noise // manual generator start","Delor Telezing","=
Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Site on gen=
 due to grid outage, site went down because landloard shut down generator d=
ue to noise // manual generator start","rouselle.schoune@ihstowers.com","69=
2","15-12-2024 15:14:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003850639","C=
RH-Etoug-Ebe","","15-12-2024 14:07:36","15-12-2024 14:00:31","15-12-2024 14=
:01:31","Active//No power issue on site U=3D52,7V site on Grid , mouhamadou=
 (691144435) of  huawei is informed. Notice that we have disjunction in OCM=
 equipment","Hyemafo Gildas","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site U=
=3D52,7V site on Grid , mouhamadou (691144435) of  huawei is informed. Noti=
ce that we have disjunction in OCM equipment","olivier.kwedi@ihstowers.com"=
,"425","15-12-2024 14:07:36","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003850495","Lad=
a I Yde","","15-12-2024 13:39:26","15-12-2024 13:29:59","15-12-2024 14:30:5=
9","Site went down due CB 80(A) Disjunted in the DC-BOX  because the Load I=
ncrease //He reamed the CB","Mba Lazare Herve","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down du=
e CB 80(A) Disjunted in the DC-BOX  because the Load Increase //He reamed t=
he CB","dorothy.djantio@ihstowers.com","568","15-12-2024 13:39:26","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003850444","T=
ongolo OCM","","15-12-2024 13:26:24","15-12-2024 12:13:11","15-12-2024 13:5=
1:33","Grid outage, site went down before gen start due to poor battery bac=
kup // gen start automatically but the site memained down( site up after po=
wer reset done)","Delor Telezing","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, site went down before gen s=
tart due to poor battery backup // gen start automatically but the site mem=
ained down( site up after power reset done)","etienne.itondo@ihstowers.com"=
,"4394","15-12-2024 13:26:24","Sagemcom CMR"
"Closed Complete","Warning","CTR_214","IHS_YND_296","NOCINC0003850379","Nko=
lfoulou","","15-12-2024 13:15:34","","","Grid outage, Site alarming because=
 Gen stopped due to High temp// He added water and started Gen manualy","Si=
ligap Boris","Warning","Warning","POWER","Warning - Site on Battery","Grid =
outage, Site alarming because Gen stopped due to High temp// He added water=
 and started Gen manualy","ludivine.ngamaleu@ihstowers.com","2","15-12-2024=
 13:15:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003850105","N=
kolondom","","15-12-2024 12:45:26","15-12-2024 12:39:12","15-12-2024 12:49:=
04","Site went Down due to Work Team Mboufack (674955463) is are working on=
 Site''Normalized Power Cable// end Off Work","Fabrice Pouakam","Equipment =
Replacement","Passive","Planned Activity","Planned Activity - Passive","Sit=
e went Down due to Work Team Mboufack (674955463) is are working on Site''N=
ormalized Power Cable// end Off Work","olivier.kwedi@ihstowers.com","375","=
15-12-2024 12:45:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003850008","T=
ongolo OCM","","15-12-2024 12:25:07","15-12-2024 12:08:49","15-12-2024 12:1=
2:32","Grid outage, site went down before gen start due to poor batteries b=
ackup // gen start automatically ","Delor Telezing","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor batteries backup // gen start automatica=
lly ","olivier.kwedi@ihstowers.com","979","15-12-2024 12:25:07","Sagemcom C=
MR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003849132","Mim=
boman3","","15-12-2024 10:20:55","15-12-2024 10:11:16","15-12-2024 10:44:44=
","Grid outage, Site went down because PWC dysfunctionning// He reset PWC a=
nd started Gen manualy","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Grid outage, Site went down because=
 PWC dysfunctionning// He reset PWC and started Gen manualy","dorothy.djant=
io@ihstowers.com","966","15-12-2024 10:20:55","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003848413","Ebo=
go","","15-12-2024 08:25:28","15-12-2024 08:14:54","15-12-2024 09:21:38","G=
rid outage, site went down because Gen failed to start due to Under frequen=
cy alarm// He purged Gen and started Gen manualy","Siligap Boris","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site we=
nt down because Gen failed to start due to Under frequency alarm// He purge=
d Gen and started Gen manualy","dorothy.djantio@ihstowers.com","1815","15-1=
2-2024 08:25:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003848319","M=
imboman-Village","IHS_YND_709","15-12-2024 08:02:16","15-12-2024 07:55:03",=
"15-12-2024 09:09:32","Grid outage, Site went down because New PWC dysfonct=
ionning// He reset PWC and started Gen manualy","Mba Lazare Herve","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage=
, Site went down because New PWC dysfonctionning// He reset PWC and started=
 Gen manualy","olivier.kwedi@ihstowers.com","434","15-12-2024 08:02:16","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003848314","N=
kolo II New","","15-12-2024 08:01:24","15-12-2024 07:55:03","15-12-2024 09:=
09:32","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, Site went down because New PWC dysfonctionni=
ng// He reset PWC and started Gen manualy","olivier.kwedi@ihstowers.com","2=
81152","15-12-2024 08:01:24","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003848012","Nko=
abang2","","15-12-2024 06:54:45","15-12-2024 06:52:36","15-12-2024 08:49:14=
","Grid outage site went down because Gen over load(22KVA, 310A) // He redu=
iced load and started Gen manualy","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage site went down because Ge=
n over load(22KVA, 310A) // He reduiced load and started Gen manualy","doro=
thy.djantio@ihstowers.com","496","15-12-2024 06:54:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003847970","S=
tade-Abega","","15-12-2024 06:47:20","15-12-2024 06:09:15","15-12-2024 06:5=
1:18"," Grid outage ,site went down because the PWC Dysfonction //Grid  pow=
er return ","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded"," Grid outage ,site went down because the PWC Dy=
sfonction //Grid  power return ","olivier.kwedi@ihstowers.com","2286","15-1=
2-2024 06:47:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003847939","Biteng-M=
aetur","","15-12-2024 06:42:01","15-12-2024 06:06:21","15-12-2024 07:01:52"=
,"Cascaded Incident from TTO3806104","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issue due to Landlord, =
Grid outage Site went down because Gen failed to start// Grid return","syst=
em","294858","15-12-2024 06:42:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003847938","Essomba"=
,"","15-12-2024 06:42:01","15-12-2024 06:06:21","15-12-2024 07:01:52","Casc=
aded Incident from TTO3806104","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Access issue due to Landlord, Grid o=
utage Site went down because Gen failed to start// Grid return","system","2=
94858","15-12-2024 06:42:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003847891","M=
ontee-Des-Soeurs","","15-12-2024 06:33:20","15-12-2024 06:01:07","15-12-202=
4 12:45:33","No power Issue Site on Grid Ubai =3D54.3V,   The FME  The TX F=
ME Mbah Hosiah (674007438) is informed. ","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","The =
FME  The TX FME Mbah Hosiah (674007438) is informed.The FME  The TX FME Mba=
h Hosiah (674007438) is informed.","olivier.kwedi@ihstowers.com","1935","15=
-12-2024 06:33:20","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003847885","Bit=
oto","","15-12-2024 06:32:10","15-12-2024 06:06:18","15-12-2024 08:19:54","=
  Site went down to due   to PWC ""ZTE' dysfunction// he reset it and start=
ed Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectif=
ier Module Overloaded","  Site went down to due   to PWC ""ZTE' dysfunction=
// he reset it and started Gen","dorothy.djantio@ihstowers.com","2237","15-=
12-2024 06:32:10","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003847878","MIM=
BOMAN LIBERTE","","15-12-2024 06:30:57","15-12-2024 06:18:53","15-12-2024 0=
7:34:51","Grid outage, Site went down because Main Gen faulty// He deployed=
 MDG of 20Kva","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage, Site went down because Main Gen faul=
ty// He deployed MDG of 20Kva","dorothy.djantio@ihstowers.com","725","15-12=
-2024 06:30:57","Sagemcom CMR"
"Closed Complete","Warning","CTR_062","IHS_YND_310","NOCINC0003847846","Nom=
ayos","","15-12-2024 06:28:43","","","Site alarming on battery due to Grid =
bad voltage// He bypassed Grid and started Gen manualy","Fanda Brice","Warn=
ing","Warning","POWER","Warning - Site on Battery","Site alarming on batter=
y due to Grid bad voltage// He bypassed Grid and started Gen manualy","ludi=
vine.ngamaleu@ihstowers.com","3","15-12-2024 06:28:43","Sagemcom CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0003847776","CLE=
 Building","","15-12-2024 06:17:40","15-12-2024 06:08:35","15-12-2024 06:48=
:45","Grid Outage No Space to deploy a MDG// Grid Restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spac=
e to deploy a MDG// Grid Restored","dorothy.djantio@ihstowers.com","546","1=
5-12-2024 06:17:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003847770","AWAE OCM=
","","15-12-2024 06:16:00","15-12-2024 06:06:21","15-12-2024 07:01:52","Cas=
caded Incident from TTO3805931","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Access issue due to Landlord, Grid =
outage Site went down because Gen failed to start// Grid return","system","=
294857","15-12-2024 06:16:00","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003847766","Bit=
eng","IHS_YND_173, IHS_YND_179, IHS_YND_249","15-12-2024 06:14:20","15-12-2=
024 06:06:21","15-12-2024 07:01:52","Access issue due to Landlord, Grid out=
age Site went down because Gen failed to start// Grid return","Mba Lazare H=
erve","Access Denial","Lease Or Legal","Landlord Related Issues","Access Is=
sue - Land Lord","Access issue due to Landlord, Grid outage Site went down =
because Gen failed to start// Grid return","dorothy.djantio@ihstowers.com",=
"1846","15-12-2024 06:14:20","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003847759","Sap=
eur","","15-12-2024 06:12:35","15-12-2024 06:04:30","15-12-2024 06:30:05","=
Grid outage, site went before gen started due to poor battery backup// Gen =
started automatically","Mboua Thierry","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went before gen s=
tarted due to poor battery backup// Gen started automatically","dorothy.dja=
ntio@ihstowers.com","486","15-12-2024 06:12:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003847254","Emana Ly=
cee","","15-12-2024 03:30:31","15-12-2024 03:19:26","15-12-2024 04:36:35","=
Cascaded Incident from TTO3805261","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage ,site went down becau=
se Gen fails to start due to CHARGING ALTERNATOR and   Static charger  faul=
ty// Gen manually started with Battery external","system","665","15-12-2024=
 03:30:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003847253","EMANA BI=
LICK CITY","","15-12-2024 03:30:31","15-12-2024 03:19:26","15-12-2024 04:36=
:35","Cascaded Incident from TTO3805261","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage ,site went down=
 because Gen fails to start due to CHARGING ALTERNATOR and   Static charger=
  faulty// Gen manually started with Battery external","system","665","15-1=
2-2024 03:30:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003847255","Messassi=
 okolo","","15-12-2024 03:30:31","15-12-2024 03:19:26","15-12-2024 04:36:35=
","Cascaded Incident from TTO3805261","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage ,site went down be=
cause Gen fails to start due to CHARGING ALTERNATOR and   Static charger  f=
aulty// Gen manually started with Battery external","system","665","15-12-2=
024 03:30:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003847252","Mballa 4=
","","15-12-2024 03:30:30","15-12-2024 03:19:26","15-12-2024 04:36:35","Cas=
caded Incident from TTO3805261","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage ,site went down because G=
en fails to start due to CHARGING ALTERNATOR and   Static charger  faulty//=
 Gen manually started with Battery external","system","664","15-12-2024 03:=
30:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003847236","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279","15-12-2024 03:2=
8:31","15-12-2024 03:19:26","15-12-2024 04:36:35","Grid outage ,site went d=
own because Gen fails to start due to CHARGING ALTERNATOR and   Static char=
ger  faulty// Gen manually started with Battery external","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator","Grid=
 outage ,site went down because Gen fails to start due to CHARGING ALTERNAT=
OR and   Static charger  faulty// Gen manually started with Battery externa=
l","stephane.nkamwa@ihstowers.com","546","15-12-2024 03:28:31","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003847087","A=
ngongo","","15-12-2024 02:32:56","15-12-2024 01:51:49","15-12-2024 02:49:46=
","grid outage,gen stopped with alarm high temp//he added water in radiator=
","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine=
 Temp - Coolant Level Issue","grid outage,gen stopped with alarm high temp/=
/he added water in radiator","stephane.nkamwa@ihstowers.com","2468","15-12-=
2024 02:32:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003847039","S=
ous Prefecture","","15-12-2024 02:19:15","15-12-2024 02:12:56","15-12-2024 =
02:32:56"," No power issue on site Ubaie:54,7V;  site on Grid.  The Tx FME =
Georges ( 697461814)) from Huawei is informed","Fanda Brice","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," N=
o power issue on site Ubaie:54,7V;  site on Grid.  The Tx FME Georges ( 697=
461814)) from Huawei is informed","stephane.nkamwa@ihstowers.com","380","15=
-12-2024 02:19:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003846371","A=
ngongo","","14-12-2024 23:09:32","14-12-2024 23:01:18","15-12-2024 00:37:29=
","Grid outage, site went down because gen start and stopped with high temp=
 alarm // he reset the Gen card and manually start the gen","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,=
 site went down because gen start and stopped with high temp alarm // he re=
set the Gen card and manually start the gen","stephane.nkamwa@ihstowers.com=
","495","14-12-2024 23:09:32","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003846331","Com=
plex Beac II","","14-12-2024 22:56:10","14-12-2024 22:48:03","14-12-2024 23=
:29:03","site went down because gen failed to start due to grid bad voltage=
//he did a bridge on good phase","Albran Byorel","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","site went down because gen =
failed to start due to grid bad voltage//he did a bridge on good phase","la=
ndry.etame@ihstowers.com","487","14-12-2024 22:56:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003846286","S=
aa","","14-12-2024 22:49:06","14-12-2024 22:38:01","14-12-2024 23:01:01","G=
rid outage,gen ran until fuel shortage//Refueling done","Parker Tchoup","Fu=
el Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran until fu=
el shortage//Refueling done","stephane.nkamwa@ihstowers.com","666","14-12-2=
024 22:49:06","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003845888","ODZ=
A CITE MBIA","","14-12-2024 21:49:06","14-12-2024 21:45:00","14-12-2024 22:=
47:00","site on DG due to grid outage ,site went down because ATS dysfoncti=
on // he bypassed the ATS and put site on grid","Albran Byorel","Equipment =
Repair","Passive","Control Panel","ATS-AMF Issue","site on DG due to grid o=
utage ,site went down because ATS dysfonction // he bypassed the ATS and pu=
t site on grid","christian.fonkou@ihstowers.com","247","14-12-2024 21:49:06=
","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0003845298","AFE=
ME NORD","","14-12-2024 20:27:03","14-12-2024 20:20:55","14-12-2024 20:45:5=
3","Site went down because CB(80A) Disjunted in the DC-BOX MTN// he reamad =
The CB and Site is on Grid","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went=
 down because CB(80A) Disjunted in the DC-BOX MTN// he reamad The CB and Si=
te is on Grid","christian.fonkou@ihstowers.com","369","14-12-2024 20:27:03"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003845004","Eto koss=
 Yde","","14-12-2024 19:39:10","14-12-2024 19:31:15","14-12-2024 20:22:15",=
"Cascaded Incident from TTO3802587","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause gen start and stopped due to grid bad voltage // he bypass grid and ma=
nually start the gen","system","297145","14-12-2024 19:39:10","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003845005","ELOUMDEM=
 CARRIERE 2","","14-12-2024 19:39:10","14-12-2024 19:31:15","14-12-2024 20:=
22:15","Cascaded Incident from TTO3802587","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because gen start and stopped due to grid bad voltage // he bypass grid=
 and manually start the gen","system","297145","14-12-2024 19:39:10","Sagem=
com CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003845002","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","14-12-2024 19:38:11","14-12-2024 19:31=
:15","14-12-2024 20:22:15","Grid fluctuation, site went down because gen st=
art and stopped due to grid bad voltage // he bypass grid and manually star=
t the gen","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation, site went down because gen start =
and stopped due to grid bad voltage // he bypass grid and manually start th=
e gen","christian.fonkou@ihstowers.com","417","14-12-2024 19:38:11","Sagemc=
om CMR"
"Closed Complete","Warning","","IHS_YND_293","NOCINC0003844894","Nkoabang M=
TN","","14-12-2024 19:20:33","","","Grid outage, site went alarm before gen=
 start // gen start automatically","Mba Lazare Herve","Warning","Warning","=
POWER","Warning - Site on Battery","Grid outage, site went alarm before gen=
 start // gen start automatically","joelle.ekessi@ihstowers.com","64","14-1=
2-2024 19:20:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003844490","Crf Corn=
ier","","14-12-2024 18:29:21","14-12-2024 18:13:35","14-12-2024 18:28:50","=
Cascaded Incident from TTO3801978","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage//Grid Restored","system=
","272795","14-12-2024 18:29:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0003844489","Mobil-Es=
sos","","14-12-2024 18:29:21","14-12-2024 18:13:35","14-12-2024 18:28:50","=
Cascaded Incident from TTO3801978","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage//Grid Restored","system=
","272795","14-12-2024 18:29:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003844481","M=
adison","IHS_YND_109, IHS_YND_566","14-12-2024 18:27:43","14-12-2024 18:13:=
35","14-12-2024 18:28:50","Grid Outage//Grid Restored","MFOUAGUEGUE MATHIEU=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
Outage//Grid Restored","emmanuel.ghani@ihstowers.com","849","14-12-2024 18:=
27:43","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003844414","Ess=
os Marche","","14-12-2024 18:24:44","14-12-2024 18:15:38","14-12-2024 18:39=
:51","Grid outage,site went down because Gen failed to start due to Gen car=
d dysfunction// He Reset the Gen Card and Manually Started The Gen","Delor =
Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage,site went down because Gen failed to start due to Gen card dysfu=
nction// He Reset the Gen Card and Manually Started The Gen","christian.fon=
kou@ihstowers.com","547","14-12-2024 18:24:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003843492","C=
rf-Nsam","","14-12-2024 16:22:43","14-12-2024 16:11:38","14-12-2024 16:27:1=
7","Site went down Because The Slot off Rectifier is overload//he Normalize=
d it and Site is on Grid ","MINKA NICOLAS","Equipment Repair","Passive","Re=
ctifier","Rectifier Module Overloaded","Site went down Because The Slot off=
 Rectifier is overload//he Normalized it and Site is on Grid ","emmanuel.gh=
ani@ihstowers.com","665","14-12-2024 16:22:43","Sagemcom CMR"
"Closed Complete","Site Down","T0530","IHS_YND_252","NOCINC0003843252","Kow=
eit City","","14-12-2024 15:56:25","14-12-2024 15:51:19","14-12-2024 16:20:=
19","Site went down due to work albran/657108542/Sagemcom is working on sit=
e(PM) // end of work","Albran Byorel","Equipment Replacement","Passive","Pl=
anned Activity","Planned Activity - Passive","Site went down due to work al=
bran/657108542/Sagemcom is working on site(PM) // end of work","christian.f=
onkou@ihstowers.com","513","14-12-2024 15:56:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003843202","A=
WAE OCM","","14-12-2024 15:51:49","14-12-2024 15:49:45","14-12-2024 16:06:2=
6","Grid Outage site went down due to dysfunctionning PWC ZTE  and ATS  // =
He Reset The PWC ZTE and Site is on Grid","Mba Lazare Herve","Equipment Rep=
air","Passive","Rectifier","Rectifier Module Overloaded","Grid Outage site =
went down due to dysfunctionning PWC ZTE  and ATS  // He Reset The PWC ZTE =
and Site is on Grid","emmanuel.ghani@ihstowers.com","125","14-12-2024 15:51=
:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003842972","Crf Corn=
ier","","14-12-2024 15:14:31","14-12-2024 14:59:38","14-12-2024 16:04:31","=
Cascaded Incident from TTO3800132","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage//Grid Restored","system=
","277316","14-12-2024 15:14:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_068","IHS_YND_109","NOCINC0003842953","M=
obil-Essos","","14-12-2024 15:11:30","14-12-2024 14:59:38","14-12-2024 16:0=
4:31","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid Outage//Grid Restored","emmanuel.ghani@ihstowers.com","2=
77316","14-12-2024 15:11:30","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003842934","Ess=
os Marche","","14-12-2024 15:08:41","14-12-2024 15:02:35","14-12-2024 16:06=
:07","Grid outage,site went down because Gen failed to start due to Gen car=
d dysfunction// He Reset the Gen Card and Manually Started The Gen","Delor =
Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage,site went down because Gen failed to start due to Gen card dysfu=
nction// He Reset the Gen Card and Manually Started The Gen","christian.fon=
kou@ihstowers.com","367","14-12-2024 15:08:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003842926","M=
adison","IHS_YND_109, IHS_YND_566","14-12-2024 15:05:44","14-12-2024 14:59:=
38","14-12-2024 16:04:31","Grid Outage//Grid Restored","MFOUAGUEGUE MATHIEU=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
Outage//Grid Restored","emmanuel.ghani@ihstowers.com","367","14-12-2024 15:=
05:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0003842539","T=
alla Monatele","","14-12-2024 13:49:59","14-12-2024 13:46:52","14-12-2024 1=
5:08:24","Grid outage, Site went down because Gen ran until fuel shortage//=
 Refueling Done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, Site went down because Gen ran until fuel shortage// R=
efueling Done","rouselle.schoune@ihstowers.com","188","14-12-2024 13:49:59"=
,"Sagemcom CMR"
"Closed Complete","Warning","T0573","IHS_YND_387","NOCINC0003842405","Talla=
 Monatele","","14-12-2024 13:29:24","","","Site went alarm becaus egen ran =
untill fuel shortage // refueling done","Parker Tchoup","Warning","Warning"=
,"DIESEL","Warning - Refuel","Site went alarm becaus egen ran untill fuel s=
hortage // refueling done","denis.mballa@ihstowers.com","222","14-12-2024 1=
3:29:24","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003842283","Nko=
lbisson usines des eaux 2","","14-12-2024 13:07:48","14-12-2024 11:46:34","=
14-12-2024 15:39:01","Grid Outage Site Went down because  main alternator f=
aulty // He deployed MDG of 20Kva","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid Outage Site Went=
 down because  main alternator faulty // He deployed MDG of 20Kva","alwine.=
fambou@ihstowers.com","4875","14-12-2024 13:07:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003842144","MEHANDAN=
","","14-12-2024 12:41:20","14-12-2024 12:37:26","14-12-2024 12:38:36","Cas=
caded Incident from TTO3799108","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue, site is on grid w=
ith Ubaie=3D53V, Lionel adjep(655184876) from Huawei is informed","system",=
"286131","14-12-2024 12:41:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003842140","O=
dza II OCM","IHS_YND_528","14-12-2024 12:40:41","14-12-2024 12:37:26","14-1=
2-2024 19:15:36","Active//No power issue, site is on grid with Ubaie=3D53V,=
 Lionel adjep(655184876) from Huawei is informed","Albran Byorel","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue, site is on grid with Ubaie=3D53V, Lionel adjep(6=
55184876) from Huawei is informed","rouselle.schoune@ihstowers.com","196","=
14-12-2024 12:40:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003841464","K=
oweit City","","14-12-2024 11:14:55","14-12-2024 11:14:51","14-12-2024 12:4=
8:43","Grid outage. gen failed to start due to battery GE faulty //Gen manu=
ally started with external battery","Albran Byorel","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Generator Battery","Grid outage. gen failed to sta=
rt due to battery GE faulty //Gen manually started with external battery","=
rouselle.schoune@ihstowers.com","5","14-12-2024 11:14:55","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003841455","ODZ=
A MINKAN EDIBI ASSI","","14-12-2024 11:14:07","14-12-2024 11:06:58","14-12-=
2024 11:58:06","Grid outage,DG started but did not feed the site,due to ACD=
G  contactor dysfonctioning(contactor DG not excited )//He replaced ACDG co=
ntactor and site on DG.","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","ATS-AMF Issue","Grid outage,DG started but did not feed the sit=
e,due to bloc  contactor dysfonctioning(contactor DG not excited )//He repl=
aced bloc contactor and site on DG.","alwine.fambou@ihstowers.com","430","1=
4-12-2024 11:14:07","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003840341","Nko=
lbisson usines des eaux 2","","14-12-2024 09:53:54","14-12-2024 09:45:42","=
14-12-2024 11:34:14","Grid outage.site  went sown due to main alternator fa=
ulty//grid power return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Generator Faulty","Grid outage.site  went sown due=
 to main alternator faulty//grid power return","alwine.fambou@ihstowers.com=
","493","14-12-2024 09:53:54","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003840041","Eko=
unou","","14-12-2024 09:24:42","14-12-2024 09:20:34","14-12-2024 09:28:58",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Grid Restored","Albran Byorel","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, site went down before gen sta=
rt due to poor battery backup // Grid Restored","alwine.fambou@ihstowers.co=
m","249","14-12-2024 09:24:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003840024","Essomba"=
,"","14-12-2024 09:22:30","14-12-2024 09:17:36","14-12-2024 09:19:19","Casc=
aded Incident from TTO3796691","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down before G=
en start due to poor backup// Grid return","system","276193","14-12-2024 09=
:22:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003840025","Biteng-M=
aetur","","14-12-2024 09:22:30","14-12-2024 09:17:36","14-12-2024 09:19:19"=
,"Cascaded Incident from TTO3796691","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
fore Gen start due to poor backup// Grid return","system","276193","14-12-2=
024 09:22:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003840010","B=
iteng","IHS_YND_179, IHS_YND_249","14-12-2024 09:19:58","14-12-2024 09:17:3=
6","14-12-2024 09:19:19","Grid outage, Site went down before Gen start due =
to poor backup// Grid return","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor backup// Grid return","rouselle.schoune@ihs=
towers.com","143","14-12-2024 09:19:58","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003839143","Nom=
ayos montee Meche","","14-12-2024 07:26:07","14-12-2024 07:23:50","14-12-20=
24 10:22:42","No power issue site on grid with U=3D53.5v Georges(697461814)=
 from Huawei is informed ","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with U=3D53.5v Georges(697461814) from Huawei is informed ","alwine.f=
ambou@ihstowers.com","138","14-12-2024 07:26:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003838570","C=
omplexe-BEAC","","14-12-2024 04:00:56","14-12-2024 03:54:28","14-12-2024 05=
:17:27","Grid fluctuation, site went down due to lack of 01 phase on site /=
/ he did a bridge with a good phase","Albran Byorel","Grid Supply","Passive=
","Grid","National Grid - Grid Incomplete Phase","Grid fluctuation, site we=
nt down due to lack of 01 phase on site // he did a bridge with a good phas=
e","alexandre.kamal@ihstowers.com","389","14-12-2024 04:00:56","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003838538","MVAN SAC=
EL","","14-12-2024 03:44:21","14-12-2024 03:32:39","14-12-2024 04:45:45","C=
ascaded Incident from TTO3794982","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Grid outage,site went down because =
Gen overload (20KVA,290 A)// Grid return","system","297005","14-12-2024 03:=
44:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003838527","M=
VAN","IHS_YND_510","14-12-2024 03:41:51","14-12-2024 03:32:39","14-12-2024 =
04:45:45","Grid outage,site went down because Gen overload (20KVA,290 A)// =
Grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload"," Grid outage,site went down because Gen overload (20KVA,290 A)=
// Grid return","alexandre.kamal@ihstowers.com","553","14-12-2024 03:41:51"=
,"Sagemcom CMR"
"Closed Complete","Warning","CTR_237","IHS_YND_261","NOCINC0003838346","Bar=
riere","","14-12-2024 02:00:40","","","Grid fluctuation, Site alarming beca=
use gen started and Stopped due to Grid bad voltage no rcp// He bypassed Gr=
id and started gen manualy","Hyemafo Gildas","Warning","Warning","POWER","W=
arning - Site on Battery","Grid fluctuation, Site alarming because gen star=
ted and Stopped due to Grid bad voltage no rcp// He bypassed Grid and start=
ed gen manualy","ludovic.tchagna@ihstowers.com","4","14-12-2024 02:00:40","=
Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003838234","ODZ=
A MINKAN EDIBI ASSI","","14-12-2024 01:04:10","14-12-2024 00:50:44","14-12-=
2024 01:31:32","Grid fluctuation site went down because Gen started and sto=
pped due to Grid bad voltage no rcp // he bypass the Grid and gen manually =
started","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation site went down because Gen started=
 and stopped due to Grid bad voltage no rcp // he bypass the Grid and gen m=
anually started","kamga.virgile@ihstowers.com","807","14-12-2024 01:04:10",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003838224","Nom=
ayos montee Meche","","14-12-2024 00:58:20","14-12-2024 00:46:04","14-12-20=
24 01:38:41","Grid outage, site went down because the bay DPC disfunctionni=
ng//He blocked the PWC DPC, Site on GEN ","Fanda Brice","Equipment Repair",=
"Passive","Rectifier","Rectifier Module Overloaded","Grid outage, site went=
 down because the bay DPC disfunctionning//He blocked the PWC DPC, Site on =
GEN ","kamga.virgile@ihstowers.com","737","14-12-2024 00:58:20","Sagemcom C=
MR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003838099","Odz=
a II","","14-12-2024 00:21:19","14-12-2024 00:11:11","14-12-2024 03:58:31",=
"Grid outage ,site went down because  Gen fails to start due to short circu=
it  at the level of GEN starter  circuit  //He connected MDG of 20 Kva","Al=
bran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Starter",=
"Grid outage ,site went down because  Gen fails to start due to short circu=
it  at the level of GEN starter  circuit  //He connected MDG of 20 Kva","ka=
mga.virgile@ihstowers.com","6969","14-12-2024 00:21:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003837988","D=
amas","","13-12-2024 23:52:43","13-12-2024 23:45:39","14-12-2024 04:03:14",=
"Grid Outage Site went down because Gen Overload(9Kva,150A) // Grid Restore=
d","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","Grid Outage Site went down because Gen Overload(9Kva,150A) // Grid Resto=
red","alexandre.kamal@ihstowers.com","425","13-12-2024 23:52:43","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003837003","C=
ite-Verte","","13-12-2024 21:19:19","13-12-2024 21:06:04","13-12-2024 21:10=
:44","No power issue on site U=3D53,6v site on grid Brice Stague/650214096/=
 of huawei is informed. Notice that we have disjunction in OCM equipment","=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site U=3D53,6v site on grid Brice Stague/65=
0214096/ of huawei is informed. Notice that we have disjunction in OCM equi=
pm","stephane.nkamwa@ihstowers.com","796","13-12-2024 21:19:19","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003836862","B=
iteng-Maetur","","13-12-2024 20:51:17","13-12-2024 20:43:11","13-12-2024 20=
:50:12","Active//No power issue, U=3D53,8V on grid, Tx FME lionel steve adj=
ep/655124876/ From huawei is informed","Mba Lazare Herve","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue, U=3D53,8V on grid, Tx FME lionel steve adjep/655124876/ =
From huawei is informed","stephane.nkamwa@ihstowers.com","488","13-12-2024 =
20:51:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003835844","Entree C=
ite Verte","","13-12-2024 17:44:13","13-12-2024 17:24:55","13-12-2024 17:30=
:33","Cascaded Incident from TTO3791736","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue, site is on Grid wi=
th Ubaie=3D53,2V,   The Tx FME Mohammadou/691144435/ From HUAWEI is informe=
d.Site impacted by Ndogpassi Nodal","system","268847","13-12-2024 17:44:13"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0003835841","Crf-Nkol=
bisson","","13-12-2024 17:44:12","13-12-2024 17:24:55","13-12-2024 17:30:33=
","Cascaded Incident from TTO3791736","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue, site is =
on Grid with Ubaie=3D53,2V,   The Tx FME Mohammadou/691144435/ From HUAWEI =
is informed.Site impacted by Ndogpassi Nodal","system","268846","13-12-2024=
 17:44:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0003835843","Dagobert=
","","13-12-2024 17:44:12","13-12-2024 17:24:55","13-12-2024 17:30:33","Cas=
caded Incident from TTO3791736","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue, site is on Gri=
d with Ubaie=3D53,2V,   The Tx FME Mohammadou/691144435/ From HUAWEI is inf=
ormed.Site impacted by Ndogpassi Nodal","system","268847","13-12-2024 17:44=
:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_077","NOCINC0003835842","Obili Ca=
rrefour","","13-12-2024 17:44:12","13-12-2024 17:24:55","13-12-2024 17:30:3=
3","Cascaded Incident from TTO3791736","Paul BIBOUM","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue, site is on Grid with=
 Ubaie=3D53,2V,   The Tx FME Mohammadou/691144435/ From HUAWEI is informed.=
Site impacted by Ndogpassi Nodal","system","268846","13-12-2024 17:44:12","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0003835840","Yona Hot=
el","","13-12-2024 17:44:12","13-12-2024 17:24:55","13-12-2024 17:30:33","C=
ascaded Incident from TTO3791736","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue, site is on G=
rid with Ubaie=3D53,2V,   The Tx FME Mohammadou/691144435/ From HUAWEI is i=
nformed.Site impacted by Ndogpassi Nodal","system","268848","13-12-2024 17:=
44:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0003835836","Nkomkana=
","","13-12-2024 17:44:11","13-12-2024 17:24:55","13-12-2024 17:30:33","Cas=
caded Incident from TTO3791736","","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","No power issue, site is on Grid with Ubaie=3D53,2V,   =
The Tx FME Mohammadou/691144435/ From HUAWEI is informed.Site impacted by N=
dogpassi Nodal","system","268844","13-12-2024 17:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0003835837","Oyomaban=
g Ecole","","13-12-2024 17:44:11","13-12-2024 17:24:55","13-12-2024 17:30:3=
3","Cascaded Incident from TTO3791736","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Active","Cascade Active","Cascade Active","No power issue, site is=
 on Grid with Ubaie=3D53,2V,   The Tx FME Mohammadou/691144435/ From HUAWEI=
 is informed.Site impacted by Ndogpassi Nodal","system","268845","13-12-202=
4 17:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0003835838","Meyong-M=
eyeme","","13-12-2024 17:44:11","13-12-2024 17:24:55","13-12-2024 17:30:33"=
,"Cascaded Incident from TTO3791736","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","No power issue, site is o=
n Grid with Ubaie=3D53,2V,   The Tx FME Mohammadou/691144435/ From HUAWEI i=
s informed.Site impacted by Ndogpassi Nodal","system","268845","13-12-2024 =
17:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_080","NOCINC0003835839","Mini-Fer=
me","","13-12-2024 17:44:11","13-12-2024 17:24:55","13-12-2024 17:30:33","C=
ascaded Incident from TTO3791736","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","No power issue, site is on Grid with Ubaie=3D53,2V, =
  The Tx FME Mohammadou/691144435/ From HUAWEI is informed.Site impacted by=
 Ndogpassi Nodal","system","268846","13-12-2024 17:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0003835835","Cite-Ver=
te","","13-12-2024 17:44:10","13-12-2024 17:24:55","13-12-2024 17:30:33","C=
ascaded Incident from TTO3791736","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","No power issue, site is on Grid with Ubaie=3D53,2V, =
  The Tx FME Mohammadou/691144435/ From HUAWEI is informed.Site impacted by=
 Ndogpassi Nodal","system","268844","13-12-2024 17:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0003835833","Nkolbi-B=
oss","","13-12-2024 17:44:10","13-12-2024 17:24:55","13-12-2024 17:30:33","=
Cascaded Incident from TTO3791736","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","No power issue, site is on =
Grid with Ubaie=3D53,2V,   The Tx FME Mohammadou/691144435/ From HUAWEI is =
informed.Site impacted by Ndogpassi Nodal","system","268843","13-12-2024 17=
:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0003835834","AFEME NO=
RD","","13-12-2024 17:44:10","13-12-2024 17:24:55","13-12-2024 17:30:33","C=
ascaded Incident from TTO3791736","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue, site is on G=
rid with Ubaie=3D53,2V,   The Tx FME Mohammadou/691144435/ From HUAWEI is i=
nformed.Site impacted by Ndogpassi Nodal","system","268843","13-12-2024 17:=
44:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0003835812","O=
yomabang OCM","IHS_YND_273, IHS_YND_519, IHS_YND_202, IHS_YND_200, IHS_YND_=
686, IHS_YND_230, IHS_YND_080, IHS_YND_271, IHS_YND_232, IHS_YND_077, IHS_Y=
ND_286, IHS_YND_543","13-12-2024 17:38:03","13-12-2024 17:24:55","13-12-202=
4 19:00:29","No power issue, site is on Grid with Ubaie=3D53,2V,   The Tx F=
ME Mohammadou/691144435/ From HUAWEI is informed.Site impacted by Ndogpassi=
 Nodal","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on G=
rid with Ubaie=3D53,2V,   The Tx FME Mohammadou/691144435/ From HUAWEI is i=
nformed.Site impacted by Ndogpassi Nodal","stephane.nkamwa@ihstowers.com","=
789","13-12-2024 17:38:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_810","NOCINC0003835381","Carrefou=
r Ayissi Ele","","13-12-2024 16:31:30","13-12-2024 16:20:55","13-12-2024 16=
:50:03","Cascaded Incident from TTO3791198","Parker Tchoup","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down because 02/=
03 rectifiers Hanging //He reset  rectifiers,site on Grid","system","272363=
","13-12-2024 16:31:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003835369","Saa","",=
"13-12-2024 16:29:04","13-12-2024 16:20:55","13-12-2024 16:50:03","Cascaded=
 Incident from TTO3791198","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because 02/03 rectifiers Han=
ging //He reset  rectifiers,site on Grid","system","272362","13-12-2024 16:=
29:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0003835368","SAA Entr=
ance","","13-12-2024 16:29:03","13-12-2024 16:20:55","13-12-2024 16:50:03",=
"Cascaded Incident from TTO3791198","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because 02/03 recti=
fiers Hanging //He reset  rectifiers,site on Grid","system","272362","13-12=
-2024 16:29:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0003835367","Tsinga",=
"","13-12-2024 16:29:03","13-12-2024 16:19:55","13-12-2024 16:42:44","	Grid=
 outage, site went down before gen start due to poor battery backup // Grid=
 Restored","Mboua Thierry","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","	Grid outage, site went down before gen start d=
ue to poor battery backup // Grid Restored","system","675","13-12-2024 16:2=
9:03","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0003835361","SAA=
 2","IHS_YND_810, IHS_YND_542, IHS_YND_405","13-12-2024 16:27:59","13-12-20=
24 16:15:55","13-12-2024 16:50:34","Site went down because 02/03 rectifiers=
 Hanging //He reset  rectifiers,site on Grid","Parker Tchoup","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down because 02/0=
3 rectifiers Hanging //He reset  rectifiers,site on Grid","landry.etame@ihs=
towers.com","1262","13-12-2024 16:27:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003835199","E=
kombitie","","13-12-2024 15:59:16","13-12-2024 15:50:04","13-12-2024 15:55:=
08","No power issue site on gen with U=3D54.6V site on grid  The  TX Synpho=
rien (691316854) from Huawei is informed","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue site on gen with U=3D54.6V site on grid=20
The  TX Synphorien (691316854) from Huawei is informed
","stephane.nkamwa@ihstowers.com","553","13-12-2024 15:59:16","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0003834766","N=
R-Bastos","","13-12-2024 15:22:51","13-12-2024 14:27:36","13-12-2024 15:36:=
40","Site went down because the cable in the Dcbox burn // He normalized th=
e cable","","Equipment Repair","Passive","Infrastructure","Armoured Cable",=
"Site went down because the cable in the Dcbox burn // He normalized the ca=
ble","stephane.nkamwa@ihstowers.com","3317","13-12-2024 15:22:51","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003834649","B=
ATA-Mokolo","","13-12-2024 15:17:53","13-12-2024 14:19:41","13-12-2024 15:0=
5:41","Grid outage No space to deploy MDG //Grid power return Power issue r=
esolve at 03:05 PM but site remains down at OCM fme BRICE Tsague/ 650214096=
 from huawie is informed","","Grid Supply","Passive","Grid","National Grid =
- Grid Outage Issue","Grid outage No space to deploy MDG //Grid power retur=
n Power issue resolve at 03:05 PM but site remains down at OCM fme BRICE Ts=
ague/ 650214096 from huawie is informed","stephane.nkamwa@ihstowers.com","3=
493","13-12-2024 15:17:53","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003834110","ODZ=
A CITE MBIA","","13-12-2024 14:43:49","13-12-2024 14:31:45","13-12-2024 15:=
03:04","Grid OUTAGE, site went down because gen fails to start due to ATS d=
isfunctionning // Grid power return","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down because=
 gen fails to start due to ATS disfunctionning // Grid power return","landr=
y.etame@ihstowers.com","725","13-12-2024 14:43:49","Sagemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003834044","Bas=
tos Bir","","13-12-2024 14:34:59","13-12-2024 14:26:49","13-12-2024 15:20:4=
9","site went down because gen start and stopped with alarm Over current //=
 He reset gen card , site manually  gen","Mboua Thierry","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","site went down because gen st=
art and stopped with alarm Over current // He reset gen card , site manuall=
y  gen","landry.etame@ihstowers.com","491","13-12-2024 14:34:59","Sagemcom =
CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0003834010","Sap=
eur Mimboman","","13-12-2024 14:28:35","13-12-2024 14:17:29","13-12-2024 14=
:25:51","No power issue on site Ubaie=3D54.1V and Ubaie2=3D51.6V  site on G=
rid  The TX FME Lionel adjep//655 18 48 76//  from huawei is informed","Mba=
 Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","No power issue on site Ubaie=3D54.1V and Ubaie2=
=3D51.6V  site on Grid

The TX FME Lionel adjep//655 18 48 76//  from huawei is informed
","landry.etame@ihstowers.com","667","13-12-2024 14:28:35","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003833992","SOA=
 UNIVERSITY STADIUM","","13-12-2024 14:25:25","13-12-2024 14:12:21","13-12-=
2024 14:26:21","Site went down due to PWC ""ZTE' dysfunction// he restart h=
e and Site is on Grid","Siligap Boris","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Site went down due to PWC ""ZTE' dysfun=
ction// he restart he and Site is on Grid","landry.etame@ihstowers.com","78=
5","13-12-2024 14:25:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003833956","S=
atcom","","13-12-2024 14:18:30","13-12-2024 13:39:25","13-12-2024 13:45:24"=
,"	Active//No power issue on site Ubaie=3D50,8V site on Grid The tx fme Arm=
and nguetsa(691144412) is informed","Delor Telezing","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","	Active//N=
o power issue on site Ubaie=3D50,8V site on Grid The tx fme Armand nguetsa(=
691144412) is informed","emmanuel.ghani@ihstowers.com","2346","13-12-2024 1=
4:18:30","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003833955","Lad=
a I Yde","","13-12-2024 14:18:27","13-12-2024 14:08:23","13-12-2024 15:13:0=
9","Grid outage ,Site went down because Gen CB (32A) disjunted //He reamed =
CB investigation ongoing)","Mba Lazare Herve","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Load Breaker","Grid outage ,Site went down because Gen C=
B (32A) disjunted //He reamed CB investigation ongoing)","landry.etame@ihst=
owers.com","605","13-12-2024 14:18:27","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003833938","Bit=
oto","","13-12-2024 14:17:19","13-12-2024 14:07:15","13-12-2024 14:18:07","=
	Site went down due to PWC ""ZTE' dysfunction// he restart he and Site is o=
n Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectif=
ier Module Overloaded","	Site went down due to PWC ""ZTE' dysfunction// he =
restart he and Site is on Grid","landry.etame@ihstowers.com","605","13-12-2=
024 14:17:19","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003833910","Eko=
unou","","13-12-2024 14:14:20","13-12-2024 14:06:13","13-12-2024 14:24:13",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","la=
ndry.etame@ihstowers.com","489","13-12-2024 14:14:20","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003833898","Odz=
a II","","13-12-2024 14:13:18","13-12-2024 14:05:11","13-12-2024 14:17:15",=
"Grid outage ,site went down because  Gen fails to start due to short circu=
it  at the level of GEN starter  circuit  //Grid power return ","Albran Byo=
rel","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid ou=
tage ,site went down because  Gen fails to start due to short circuit  at t=
he level of GEN starter  circuit  //Grid power return ","landry.etame@ihsto=
wers.com","489","13-12-2024 14:13:18","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003833895","NYO=
M FACE MAETUR","","13-12-2024 14:12:45","13-12-2024 13:57:34","13-12-2024 1=
4:42:26","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // grid return","christian.fonkou@ihstowers.com","912","13-12-2=
024 14:12:45","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0003833835","Bit=
eng-Maetur","","13-12-2024 14:10:39","13-12-2024 14:00:36","13-12-2024 14:2=
5:36","Grid outage, site went down before gen start due to poor battery bac=
kup // gen start automatically","Mba Lazare Herve","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // gen start automatically=
","landry.etame@ihstowers.com","604","13-12-2024 14:10:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003833561","S=
tade-Abega","","13-12-2024 14:05:20","13-12-2024 13:44:15","13-12-2024 15:2=
0:07","Grid outage site went down because the PWC Dysfonction and poor back=
up  //he reset the PWC and  manually started","Mba Lazare Herve","Equipment=
 Repair","Passive","Rectifier","Rectifier Module Overloaded","Grid outage s=
ite went down because the PWC Dysfonction and poor backup  //he reset the P=
WC and  manually started","emmanuel.ghani@ihstowers.com","1266","13-12-2024=
 14:05:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003833534","Messassi=
 okolo","","13-12-2024 14:03:21","13-12-2024 13:40:08","13-12-2024 14:26:45=
","Cascaded Incident from TTO3789055","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage;Gen fails to start=
 due to  Gen starter faulty //Grid power return(Replacement Gen starter ong=
oing)","system","282191","13-12-2024 14:03:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003833531","EMANA BI=
LICK CITY","","13-12-2024 14:03:21","13-12-2024 13:40:08","13-12-2024 14:26=
:45","Cascaded Incident from TTO3789055","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage;Gen fails to st=
art due to  Gen starter faulty //Grid power return(Replacement Gen starter =
ongoing)","system","282190","13-12-2024 14:03:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003833532","Emana Ly=
cee","","13-12-2024 14:03:21","13-12-2024 13:40:08","13-12-2024 14:26:45","=
Cascaded Incident from TTO3789055","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage;Gen fails to start du=
e to  Gen starter faulty //Grid power return(Replacement Gen starter ongoin=
g)","system","282190","13-12-2024 14:03:21","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003833533","Mok=
olo Yaounde","","13-12-2024 14:03:21","13-12-2024 13:41:13","13-12-2024 14:=
43:10","grid outage, no space to deploy// grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","grid outage, no space to=
 deploy// grid return","christian.fonkou@ihstowers.com","1329","13-12-2024 =
14:03:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003833530","Mballa 4=
","","13-12-2024 14:03:20","13-12-2024 13:40:08","13-12-2024 14:26:45","Cas=
caded Incident from TTO3789055","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage;Gen fails to start due to=
  Gen starter faulty //Grid power return(Replacement Gen starter ongoing)",=
"system","282191","13-12-2024 14:03:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003833496","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279","13-12-2024 14:0=
1:15","13-12-2024 13:40:08","13-12-2024 14:26:45","Grid outage;Gen fails to=
 start due to Gen starter faulty //Grid power return(Replacement Gen starte=
r ongoing)","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Kick Starter","Grid outage;Gen fails to start due to  Gen starter faulty=
 //Grid power return(Replacement Gen starter ongoing)","emmanuel.ghani@ihst=
owers.com","1268","13-12-2024 14:01:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003833429","D=
amas","","13-12-2024 13:58:41","13-12-2024 13:39:37","13-12-2024 14:20:53",=
"Grid Outage Site went down because Gen Overload(9Kva,150A) // Grid Restore=
d","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","Grid Outage Site went down because Gen Overload(9Kva,150A) // Grid Resto=
red","emmanuel.ghani@ihstowers.com","1145","13-12-2024 13:58:41","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003833321","M=
ontee-Des-Soeurs","","13-12-2024 13:57:19","13-12-2024 13:39:13","13-12-202=
4 13:45:43","No power Issue Site on Grid Ubai =3D54.5V,   The FME  The TX F=
ME Mbah Hosiah (674007438) is informed. ","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","// N=
o power Issue Site on Grid Ubai =3D54.5V,=20

The FME  The TX FME Mbah Hosiah (674007438) is informed.=20

","emmanuel.ghani@ihstowers.com","1087","13-12-2024 13:57:19","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003833316","A=
WAE OCM","","13-12-2024 13:56:20","13-12-2024 13:39:15","13-12-2024 14:18:2=
1","Grid outage site went down because the PWC Dysfonction  //he reset the =
PWC and  manually started","Mba Lazare Herve","Equipment Repair","Passive",=
"Rectifier","Rectifier Module Overloaded","Grid outage site went down becau=
se the PWC Dysfonction  //he reset the PWC and  manually started","emmanuel=
.ghani@ihstowers.com","1026","13-12-2024 13:56:20","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003833312","Sap=
eur","","13-12-2024 13:56:07","13-12-2024 13:39:59","13-12-2024 14:49:53","=
Grid fluctuation, site went down before gen start due to poor battery backu=
p // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid fluctuation, site went down before =
gen start due to poor battery backup // Grid return","christian.fonkou@ihst=
owers.com","969","13-12-2024 13:56:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003833306","S=
calom-IHS","","13-12-2024 13:54:48","13-12-2024 13:39:24","13-12-2024 14:43=
:44","	Grid outage No space to deploy // Grid power return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","	Grid outage No spa=
ce to deploy // Grid power return","emmanuel.ghani@ihstowers.com","926","13=
-12-2024 13:54:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0003832795","Barriere=
 IHS","","13-12-2024 13:16:50","13-12-2024 13:09:35","13-12-2024 13:12:18",=
"Cascaded Incident from TTO3788243","Hyemafo Gildas","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site  GRID  , Ubai=
e=3D54.V site On Grid   The Tx FME Georges 697461814 from Huawei is informe=
d..","system","284173","13-12-2024 13:16:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003832772","M=
efou-Assi","IHS_YND_696","13-12-2024 13:14:13","13-12-2024 13:09:35","13-12=
-2024 13:12:18","No power issue on site  GRID  , Ubaie=3D54.V site On Grid =
  The Tx FME Georges 697461814 from Huawei is informed..","Fanda Brice","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue on site  GRID  , Ubaie=3D54.V site On Grid   The Tx=
 FME Georges 697461814 from Huawei is informed..","emmanuel.ghani@ihstowers=
.com","279","13-12-2024 13:14:13","Sagemcom CMR"
"Closed Complete","Site Down","T1557","IHS_YND_313","NOCINC0003832433","Afa=
noya","","13-12-2024 12:14:47","13-12-2024 12:08:25","13-12-2024 14:16:29",=
"Active//No power issue on site , Ubaie=3D54.4V site On Grid The RM Alain  =
691144423 from Huawei is informed","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site , Ubaie=3D54.4V site On Grid The RM Alain  691144423 fr=
om Huawei is informed","christian.fonkou@ihstowers.com","383","13-12-2024 1=
2:14:47","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003830840","Nko=
lmvack","","13-12-2024 09:28:14","13-12-2024 09:19:09","13-12-2024 11:39:09=
","hybrid gen site, site went down because gen stopped with low oil pressur=
e // he added oil and manually start the gen","Parker Tchoup","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Low Oil Pressure","hybrid gen site, site=
 went down because gen stopped with low oil pressure // he added oil and ma=
nually start the gen","christian.fonkou@ihstowers.com","546","13-12-2024 09=
:28:14","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003830722","Nko=
g-Edzen","","13-12-2024 09:26:03","13-12-2024 09:04:50","13-12-2024 12:15:1=
1","Active//No power issue on site with Ubaie=3D52.4V site on Gen (start th=
reshold ubai=3D50 V The Tx Fme Gregoire( 652070658)from Huawei is informed"=
,"Parker Tchoup","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active//No power issue on site with Ubaie=3D52=
.4V site on Gen (start threshold ubai=3D50 V The Tx Fme Gregoire( 652070658=
)from Huawei is informed","christian.fonkou@ihstowers.com","1274","13-12-20=
24 09:26:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_625","IHS_YND_181","NOCINC0003830718","M=
imboman3","","13-12-2024 09:25:58","13-12-2024 09:19:53","13-12-2024 10:48:=
24","site went down because the PWC dysfonction // he bypass the Grid . sit=
e on Gen","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rect=
ifier Module Overloaded","site went down because the PWC dysfonction // he =
bypass the Grid . site on Gen","emmanuel.ghani@ihstowers.com","366","13-12-=
2024 09:25:58","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_046","NOCINC0003830712","Djoungolo"=
,"","13-12-2024 09:24:38","","","Site went alarm before gen start due to gr=
id outage // gen start","Mboua Thierry","Warning","Warning","POWER","Warnin=
g - Site on Battery","Site went alarm before gen start due to grid outage /=
/ gen start","joelle.ekessi@ihstowers.com","65","13-12-2024 09:24:38","Sage=
mcom CMR"
"Closed Complete","Site Down","T0816","IHS_YND_260","NOCINC0003830483","Sim=
bock Maetur","","13-12-2024 08:48:41","13-12-2024 08:43:29","13-12-2024 12:=
47:02","Active//No power Issue Site on Grid Ubai =3D54.3V, The FME The TX F=
ME Mbah Hosiah (674007438) is informed.","Hyemafo Gildas","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power Issue Site on Grid Ubai =3D54.3V, The FME The TX FME Mbah Hosia=
h (674007438) is informed.","christian.fonkou@ihstowers.com","312","13-12-2=
024 08:48:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0003830303","E=
koumdoum","","13-12-2024 08:11:26","13-12-2024 08:04:22","13-12-2024 09:24:=
22","Site went down due to disjunction of CB(63) in PWC // CB put back on",=
"Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet=
 - Circuit Breaker Issue","Site went down due to disjunction of CB(63) in P=
WC // CB put back on","emmanuel.ghani@ihstowers.com","425","13-12-2024 08:1=
1:26","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_434","NOCINC0003830289","Donga","",=
"13-12-2024 08:09:46","","","Hybrid gen site // gen start automatically","P=
arker Tchoup","Warning","Warning","POWER","Warning - Site on Battery","Hybr=
id gen site // gen start automatically","joelle.ekessi@ihstowers.com","67",=
"13-12-2024 08:09:46","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003830245","ODZ=
A CITE MBIA","","13-12-2024 08:00:17","13-12-2024 07:01:01","13-12-2024 08:=
35:10","Site went down due to insufficiency of rectifier (03 on site)// Sit=
e stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down due to insufficiency of rectifier (03 on sit=
e)// Site stabilized","christian.fonkou@ihstowers.com","3557","13-12-2024 0=
8:00:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003829684","B=
ATA-Mokolo","","13-12-2024 05:53:42","13-12-2024 05:49:12","13-12-2024 10:3=
2:12","Grid outage, No space to deploy MDG, // Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spa=
ce to deploy MDG, // Grid return","olivier.kwedi@ihstowers.com","271","13-1=
2-2024 05:53:42","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003829467","BAT=
A Mokolo OCM","","13-12-2024 04:52:18","13-12-2024 04:48:47","13-12-2024 10=
:36:47","Grid outage, No space to deploy MDG, // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No s=
pace to deploy MDG, // Grid return","ludivine.ngamaleu@ihstowers.com","212"=
,"13-12-2024 04:52:18","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003828386","ODZ=
A CITE MBIA","","12-12-2024 23:36:51","12-12-2024 23:33:13","13-12-2024 01:=
18:53","Site went down due to insufficiency of rectifier (03 on site)// Sit=
e stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down due to insufficiency of rectifier (03 on sit=
e)// Site stabilized","ludivine.ngamaleu@ihstowers.com","219","12-12-2024 2=
3:36:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0003828078","B=
ONAS YDE","","12-12-2024 22:30:37","12-12-2024 22:04:30","12-12-2024 23:29:=
23","Active// No power Issue Site on Grid Ubai =3D54,6 V, The RM Alain (691=
144423)  from Huawei is informed and  Notice that we have disjunction at BT=
S OCM","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active// No power Issue Site on Grid Ubai =
=3D54,6 V, The RM Alain (691144423)  from Huawei is informed and  Notice th=
at we have disjunction at BTS OCM","olivier.kwedi@ihstowers.com","1568","12=
-12-2024 22:30:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003827867","Nkongtoc=
k","","12-12-2024 21:50:23","12-12-2024 20:35:38","12-12-2024 22:42:01","Ca=
scaded Incident from TTO3782423","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because PWC dysfunct=
ioning// He reduced the load, Site on Gen (PWC to be replace)","system","27=
8951","12-12-2024 21:50:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0003827868","Ekekam",=
"","12-12-2024 21:50:23","12-12-2024 20:35:38","12-12-2024 22:42:01","Casca=
ded Incident from TTO3782423","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because PWC dy=
sfunctioning// He reduced the load, Site on Gen (PWC to be replace)","syste=
m","278949","12-12-2024 21:50:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0003827869","LOBO MTN=
","","12-12-2024 21:50:23","12-12-2024 20:35:38","12-12-2024 22:42:01","Cas=
caded Incident from TTO3782423","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down because PWC =
dysfunctioning// He reduced the load, Site on Gen (PWC to be replace)","sys=
tem","278950","12-12-2024 21:50:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0003827870","NKONGKAR=
AK","","12-12-2024 21:50:23","12-12-2024 20:35:38","12-12-2024 22:42:01","C=
ascaded Incident from TTO3782423","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down because PW=
C dysfunctioning// He reduced the load, Site on Gen (PWC to be replace)","s=
ystem","278948","12-12-2024 21:50:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0003827863","Bot Maka=
k","","12-12-2024 21:50:22","12-12-2024 20:35:38","12-12-2024 22:42:01","Ca=
scaded Incident from TTO3782423","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site went down because PWC dysfunctioning// He red=
uced the load, Site on Gen (PWC to be replace)","system","278951","12-12-20=
24 21:50:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_366","NOCINC0003827864","Mandoumb=
a MTN","","12-12-2024 21:50:22","12-12-2024 20:35:38","12-12-2024 22:42:01"=
,"Cascaded Incident from TTO3782423","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because PWC dysf=
unctioning// He reduced the load, Site on Gen (PWC to be replace)","system"=
,"278950","12-12-2024 21:50:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003827865","Mambine"=
,"","12-12-2024 21:50:22","12-12-2024 20:35:38","12-12-2024 22:42:01","Casc=
aded Incident from TTO3782423","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because PWC dysfunctioning=
// He reduced the load, Site on Gen (PWC to be replace)","system","278952",=
"12-12-2024 21:50:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0003827860","Nkeng li=
kok","","12-12-2024 21:50:21","12-12-2024 20:35:38","12-12-2024 22:42:01","=
Cascaded Incident from TTO3782423","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because PWC dysfun=
ctioning// He reduced the load, Site on Gen (PWC to be replace)","system","=
278948","12-12-2024 21:50:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003827862","Ebeba","=
","12-12-2024 21:50:21","12-12-2024 20:35:38","12-12-2024 22:42:01","Cascad=
ed Incident from TTO3782423","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because PWC dysfunctioning//=
 He reduced the load, Site on Gen (PWC to be replace)","system","278949","1=
2-12-2024 21:50:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003827861","Ngog Map=
ubi","","12-12-2024 21:50:21","12-12-2024 20:35:38","12-12-2024 22:42:01","=
Cascaded Incident from TTO3782423","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because PWC dysfun=
ctioning// He reduced the load, Site on Gen (PWC to be replace)","system","=
278950","12-12-2024 21:50:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0003827859","Lobo 2",=
"","12-12-2024 21:50:21","12-12-2024 20:35:38","12-12-2024 22:42:01","Casca=
ded Incident from TTO3782423","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because PWC dy=
sfunctioning// He reduced the load, Site on Gen (PWC to be replace)","syste=
m","278951","12-12-2024 21:50:21","Sagemcom CMR"
"Closed Complete","Site Down","T0236","IHS_YND_373","NOCINC0003827847","Mal=
oun","IHS_YND_783, IHS_YND_347, IHS_YND_419, IHS_YND_339, IHS_YND_421, IHS_=
YND_366, IHS_YND_350, IHS_EDA_101, IHS_YND_349, IHS_YND_714, IHS_YND_342, I=
HS_YND_713","12-12-2024 21:46:57","12-12-2024 20:35:38","12-12-2024 22:42:2=
7","Site went down because PWC dysfunctioning// He reduced the load, Site o=
n Gen (PWC to be replace)","Kemeni Franklin","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down because PWC dysfun=
ctioning// He reduced the load, Site on Gen (PWC to be replace)","kamga.vir=
gile@ihstowers.com","4279","12-12-2024 21:46:57","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003827761","Nko=
abang Ebolmedjock","","12-12-2024 21:33:26","12-12-2024 20:43:13","13-12-20=
24 01:41:28","no power issue U:53.5V site on Gen. TX FME Leonel Steve (6551=
84876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power iss=
ue U:53.5V site on Gen. TX FME Leonel Steve (655184876) from Huawei is info=
rmed","kamga.virgile@ihstowers.com","3014","12-12-2024 21:33:26","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0003827712","NKONGKAR=
AK","","12-12-2024 21:28:23","12-12-2024 19:59:35","12-12-2024 20:20:27","C=
ascaded Incident from TTO3782231","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","site went down because Ge=
n started and stopped due to Gen card dysfonction // He reset the Gen card =
and Gen manually started","system","266624","12-12-2024 21:28:23","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003827709","Nkongtoc=
k","","12-12-2024 21:28:22","12-12-2024 19:59:35","12-12-2024 20:20:27","Ca=
scaded Incident from TTO3782231","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because Gen started =
and stopped due to Gen card dysfonction // He reset the Gen card and Gen ma=
nually started","system","266624","12-12-2024 21:28:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0003827711","LOBO MTN=
","","12-12-2024 21:28:22","12-12-2024 19:59:35","12-12-2024 20:20:27","Cas=
caded Incident from TTO3782231","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site went down because Gen =
started and stopped due to Gen card dysfonction // He reset the Gen card an=
d Gen manually started","system","266622","12-12-2024 21:28:22","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0003827710","Ekekam",=
"","12-12-2024 21:28:22","12-12-2024 19:59:35","12-12-2024 20:20:27","Casca=
ded Incident from TTO3782231","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because Gen st=
arted and stopped due to Gen card dysfonction // He reset the Gen card and =
Gen manually started","system","266625","12-12-2024 21:28:22","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003827707","Mambine"=
,"","12-12-2024 21:28:22","12-12-2024 19:59:35","12-12-2024 20:20:27","Casc=
aded Incident from TTO3782231","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because Gen started and st=
opped due to Gen card dysfonction // He reset the Gen card and Gen manually=
 started","system","266624","12-12-2024 21:28:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0003827705","Bot Maka=
k","","12-12-2024 21:28:21","12-12-2024 19:59:35","12-12-2024 20:20:27","Ca=
scaded Incident from TTO3782231","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","site went down because Gen started and stopped due=
 to Gen card dysfonction // He reset the Gen card and Gen manually started"=
,"system","266623","12-12-2024 21:28:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_366","NOCINC0003827706","Mandoumb=
a MTN","","12-12-2024 21:28:21","12-12-2024 19:59:35","12-12-2024 20:20:27"=
,"Cascaded Incident from TTO3782231","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down because Gen star=
ted and stopped due to Gen card dysfonction // He reset the Gen card and Ge=
n manually started","system","266622","12-12-2024 21:28:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003827704","Ebeba","=
","12-12-2024 21:28:21","12-12-2024 19:59:35","12-12-2024 20:20:27","Cascad=
ed Incident from TTO3782231","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down because Gen started and stop=
ped due to Gen card dysfonction // He reset the Gen card and Gen manually s=
tarted","system","266622","12-12-2024 21:28:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0003827703","Nkeng li=
kok","","12-12-2024 21:28:21","12-12-2024 19:59:35","12-12-2024 20:20:27","=
Cascaded Incident from TTO3782231","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because Gen starte=
d and stopped due to Gen card dysfonction // He reset the Gen card and Gen =
manually started","system","266623","12-12-2024 21:28:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0003827702","Lobo 2",=
"","12-12-2024 21:28:20","12-12-2024 19:59:35","12-12-2024 20:20:27","Casca=
ded Incident from TTO3782231","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because Gen st=
arted and stopped due to Gen card dysfonction // He reset the Gen card and =
Gen manually started","system","266621","12-12-2024 21:28:20","Sagemcom CMR=
"
"Closed Complete","Site Down","T0236","IHS_YND_373","NOCINC0003827690","Mal=
oun","IHS_YND_783, IHS_YND_347, IHS_YND_339, IHS_YND_421, IHS_YND_366, IHS_=
YND_350, IHS_EDA_101, IHS_YND_349, IHS_YND_714, IHS_YND_342, IHS_YND_713","=
12-12-2024 21:24:54","12-12-2024 19:59:35","12-12-2024 20:20:27","site went=
 down because Gen started and stopped due to Gen card dysfonction // He res=
et the Gen card and Gen manually started","Kemeni Franklin","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","site went down because Gen=
 started and stopped due to Gen card dysfonction // He reset the Gen card a=
nd Gen manually started","kamga.virgile@ihstowers.com","5120","12-12-2024 2=
1:24:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003827403","H=
-General-Yde","","12-12-2024 20:46:06","12-12-2024 19:54:59","12-12-2024 21=
:45:55","Site went down because 1/3 rectifier faulty// He replaced rectifie=
r faulty, Site on Grid","Siligap Boris","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down because 1/3 rectifier faulty// He =
replaced rectifier faulty, Site on Grid","alexandre.kamal@ihstowers.com","3=
068","12-12-2024 20:46:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_337","NOCINC0003827304","Okola","=
","12-12-2024 20:35:44","12-12-2024 19:59:02","12-12-2024 20:10:47","Cascad=
ed Incident from TTO3781710","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation site went dow=
n because Gen started and stopped due to Grid bad voltage no rcp on site// =
He bypass the Grid and site on Gen","system","281127","12-12-2024 20:35:44"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0003827307","Monatele=
 MTN","","12-12-2024 20:35:44","12-12-2024 19:59:02","12-12-2024 20:10:47",=
"Cascaded Incident from TTO3781710","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation site went down be=
cause Gen started and stopped due to Grid bad voltage no rcp on site// He b=
ypass the Grid and site on Gen","system","281126","12-12-2024 20:35:44","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0003827306","Monatele=
","","12-12-2024 20:35:44","12-12-2024 19:59:02","12-12-2024 20:10:47","Cas=
caded Incident from TTO3781710","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation site went down becaus=
e Gen started and stopped due to Grid bad voltage no rcp on site// He bypas=
s the Grid and site on Gen","system","281125","12-12-2024 20:35:44","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003827233","Eto koss=
 Yde","","12-12-2024 20:31:01","12-12-2024 20:22:56","12-12-2024 20:46:56",=
"Cascaded Incident from TTO3781683","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid bad voltage,and gen failed to s=
tart//bypassed grid and started the gen","system","286825","12-12-2024 20:3=
1:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003827234","ELOUMDEM=
 CARRIERE 2","","12-12-2024 20:31:01","12-12-2024 20:22:56","12-12-2024 20:=
46:56","Cascaded Incident from TTO3781683","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid bad voltage,and gen fail=
ed to start//bypassed grid and started the gen","system","286824","12-12-20=
24 20:31:01","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003827218","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","12-12-2024 20:28:03","12-12-2024 20:19=
:54","12-12-2024 20:50:54","grid bad voltage,and gen failed to start//bypas=
sed grid and started the gen","Fanda Brice","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","grid bad voltage,and gen failed =
to start//bypassed grid and started the gen","kamga.virgile@ihstowers.com",=
"2767","12-12-2024 20:28:03","Sagemcom CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0003827209","Pha=
rmacie Bleue","","12-12-2024 20:24:59","12-12-2024 20:11:56","12-12-2024 22=
:06:42","Site went down because 1/2 rectifier faulty// He replaced rectifie=
r faulty, site on Grid","Siligap Boris","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down because 1/2 rectifier faulty// He =
replaced rectifier faulty, site on Grid","kamga.virgile@ihstowers.com","827=
","12-12-2024 20:24:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0003826978","E=
zezang","IHS_YND_337, IHS_YND_530, IHS_YND_406, IHS_YND_407, IHS_YND_390","=
12-12-2024 20:03:08","12-12-2024 19:54:02","12-12-2024 20:11:02","Grid fluc=
tuation site went down because Gen started and stopped due to Grid bad volt=
age no rcp on site// He bypass the Grid and site on Gen","Parker Tchoup","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d fluctuation site went down because Gen started and stopped due to Grid ba=
d voltage no rcp on site// He bypass the Grid and site on Gen","alexandre.k=
amal@ihstowers.com","547","12-12-2024 20:03:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0003826894","B=
ONAS YDE","","12-12-2024 19:46:26","12-12-2024 19:35:22","12-12-2024 22:03:=
01","Active// No power Issue Site on Grid Ubai =3D54,6 V,   The TX FME Mbah=
 Hosiah (674007438)  from Huawei is informed and  Notice that we have disju=
nction (CB 100 A)at BTS OCM","Paul BIBOUM","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power Is=
sue Site on Grid Ubai =3D54,6 V, The TX FME Mbah Hosiah (674007438)  from H=
uawei is informed and  Notice that we have disjunction (CB 100 A)at BTS OCM
","alexandre.kamal@ihstowers.com","665","12-12-2024 19:46:26","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003826790","Akak-Nko=
zoa-MTN-IHS","","12-12-2024 19:31:10","12-12-2024 19:25:20","12-12-2024 19:=
34:00","Cascaded Incident from TTO3781183","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site down due=
 to poor backup // Grid return","system","261502","12-12-2024 19:31:10","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003826731","C=
RH-Etoug-Ebe","","12-12-2024 19:20:07","12-12-2024 19:12:39","13-12-2024 01=
:30:20","No power issue on site U=3D54.1V site on Grid , The Tx FME  Mohama=
dou/691 144 435/ from Huawei is informed. Notice thad disjunction in OCM eq=
uipment","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54.1V site=
 on Grid ,
The Tx FME  Mohamadou/691 144 435/ from Huawei is informed. Notice thad dis=
junction in OCM equipment
","alexandre.kamal@ihstowers.com","449","12-12-2024 19:20:07","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0003826019","LOBO MTN=
","","12-12-2024 17:21:03","12-12-2024 16:32:11","12-12-2024 18:24:16","Cas=
caded Incident from TTO3780137","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site went down because Gen =
started and stopped due to gen card dysfonction // He reset the gen card an=
d Gen manually started","system","278884","12-12-2024 17:21:03","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0003826020","NKONGKAR=
AK","","12-12-2024 17:21:03","12-12-2024 16:32:11","12-12-2024 18:24:16","C=
ascaded Incident from TTO3780137","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","site went down because Ge=
n started and stopped due to gen card dysfonction // He reset the gen card =
and Gen manually started","system","278885","12-12-2024 17:21:03","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003826017","Nkongtoc=
k","","12-12-2024 17:21:02","12-12-2024 16:32:11","12-12-2024 18:24:16","Ca=
scaded Incident from TTO3780137","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because Gen started =
and stopped due to gen card dysfonction // He reset the gen card and Gen ma=
nually started","system","278883","12-12-2024 17:21:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0003826018","Ekekam",=
"","12-12-2024 17:21:02","12-12-2024 16:32:11","12-12-2024 18:24:16","Casca=
ded Incident from TTO3780137","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because Gen st=
arted and stopped due to gen card dysfonction // He reset the gen card and =
Gen manually started","system","278884","12-12-2024 17:21:02","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0003826013","Bot Maka=
k","","12-12-2024 17:21:01","12-12-2024 16:32:11","12-12-2024 18:24:16","Ca=
scaded Incident from TTO3780137","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","site went down because Gen started and stopped due=
 to gen card dysfonction // He reset the gen card and Gen manually started"=
,"system","278882","12-12-2024 17:21:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003826012","Ebeba","=
","12-12-2024 17:21:01","12-12-2024 16:32:11","12-12-2024 18:24:16","Cascad=
ed Incident from TTO3780137","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down because Gen started and stop=
ped due to gen card dysfonction // He reset the gen card and Gen manually s=
tarted","system","278881","12-12-2024 17:21:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_366","NOCINC0003826014","Mandoumb=
a MTN","","12-12-2024 17:21:01","12-12-2024 16:32:11","12-12-2024 18:24:16"=
,"Cascaded Incident from TTO3780137","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down because Gen star=
ted and stopped due to gen card dysfonction // He reset the gen card and Ge=
n manually started","system","278882","12-12-2024 17:21:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003826015","Mambine"=
,"","12-12-2024 17:21:01","12-12-2024 16:32:11","12-12-2024 18:24:16","Casc=
aded Incident from TTO3780137","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because Gen started and st=
opped due to gen card dysfonction // He reset the gen card and Gen manually=
 started","system","278882","12-12-2024 17:21:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0003826010","Nkeng li=
kok","","12-12-2024 17:21:00","12-12-2024 16:32:11","12-12-2024 18:24:16","=
Cascaded Incident from TTO3780137","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because Gen starte=
d and stopped due to gen card dysfonction // He reset the gen card and Gen =
manually started","system","278881","12-12-2024 17:21:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003826011","Ngog Map=
ubi","","12-12-2024 17:21:00","12-12-2024 16:32:11","12-12-2024 18:24:16","=
Cascaded Incident from TTO3780137","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because Gen starte=
d and stopped due to gen card dysfonction // He reset the gen card and Gen =
manually started","system","278881","12-12-2024 17:21:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0003826009","Lobo 2",=
"","12-12-2024 17:21:00","12-12-2024 16:32:11","12-12-2024 18:24:16","Casca=
ded Incident from TTO3780137","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because Gen st=
arted and stopped due to gen card dysfonction // He reset the gen card and =
Gen manually started","system","278885","12-12-2024 17:21:00","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_360","IHS_YND_373","NOCINC0003825729","M=
aloun","IHS_YND_783, IHS_YND_347, IHS_YND_419, IHS_YND_339, IHS_YND_421, IH=
S_YND_366, IHS_YND_350, IHS_EDA_101, IHS_YND_349, IHS_YND_714, IHS_YND_342,=
 IHS_YND_713","12-12-2024 16:36:27","12-12-2024 16:27:11","12-12-2024 18:26=
:16","site went down because Gen started and stopped due to gen card dysfon=
ction // He reset the gen card and Gen manually started","Kemeni Franklin",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","site went d=
own because Gen started and stopped due to gen card dysfonction // He reset=
 the gen card and Gen manually started","alexandre.kamal@ihstowers.com","55=
7","12-12-2024 16:36:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003825353","Bastos E=
koudou","","12-12-2024 15:49:11","12-12-2024 15:35:01","12-12-2024 15:40:30=
","Cascaded Incident from TTO3779418","Mboua Thierry","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","Active // No power issue on site, S=
ite on GRID and UBAIE=3D54.6V ,The Team Robert KIMBOCK(699944517) FROM ZTE =
 is working on site (Normalized GPS )","system","268005","12-12-2024 15:49:=
11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0003825347","B=
astos-BAT","IHS_YND_193","12-12-2024 15:48:07","12-12-2024 15:35:01","12-12=
-2024 15:40:30","Active // No power issue on site, Site on GRID and UBAIE=
=3D54.6V ,The Team Robert KIMBOCK(699944517) FROM ZTE  is working on site (=
Normalized GPS )","Mboua Thierry","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active // No power issue on s=
ite, Site on GRID and UBAIE=3D54.6V ,The Team Robert KIMBOCK(699944517) FRO=
M ZTE  is working on site (Normalized GPS )","alexandre.kamal@ihstowers.com=
","787","12-12-2024 15:48:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0003825097","O=
bili Carrefour","","12-12-2024 15:22:19","12-12-2024 15:09:15","12-12-2024 =
15:15:32","No power Issue Site on Grid Ubai =3D53.4 V, The FME The TX FME M=
bah Hosiah (674007438) is informed.","Paul BIBOUM","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power Iss=
ue Site on Grid Ubai =3D53.4 V, The FME The TX FME Mbah Hosiah (674007438) =
is informed.","alexandre.kamal@ihstowers.com","785","12-12-2024 15:22:19","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003823867","D=
amas","","12-12-2024 12:46:46","12-12-2024 12:37:38","12-12-2024 16:02:44",=
"Grid Outage Site went down because Gen Overload(9Kva,150A) // Grid Restore=
d","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","Grid Outage Site went down because Gen Overload(9Kva,150A) // Grid Resto=
red","stephane.nkamwa@ihstowers.com","549","12-12-2024 12:46:46","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0003823857","Mom","",=
"12-12-2024 12:45:21","12-12-2024 12:00:08","12-12-2024 12:48:32","Cascaded=
 Incident from TTO3777488","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","grid outage, site went down due to Cb(125A) f=
aulty in PWC and poor battery backup// He changed Cb(125A) with a CB(2*63A)=
, sgen manually started","system","266621","12-12-2024 12:45:21","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0003823852","OKOA Pea=
ge","","12-12-2024 12:45:20","12-12-2024 12:00:08","12-12-2024 12:48:32","C=
ascaded Incident from TTO3777488","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage, site went down due to Cb(=
125A) faulty in PWC and poor battery backup// He changed Cb(125A) with a CB=
(2*63A), sgen manually started","system","266622","12-12-2024 12:45:20","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0003823853","OTELE MT=
N","","12-12-2024 12:45:20","12-12-2024 12:00:08","12-12-2024 12:48:32","Ca=
scaded Incident from TTO3777488","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","grid outage, site went down due to Cb(1=
25A) faulty in PWC and poor battery backup// He changed Cb(125A) with a CB(=
2*63A), sgen manually started","system","266620","12-12-2024 12:45:20","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0003823855","Minka","=
","12-12-2024 12:45:20","12-12-2024 12:00:08","12-12-2024 12:48:32","Cascad=
ed Incident from TTO3777488","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","grid outage, site went down due to Cb(125A)=
 faulty in PWC and poor battery backup// He changed Cb(125A) with a CB(2*63=
A), sgen manually started","system","266621","12-12-2024 12:45:20","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0003823854","Angongo"=
,"","12-12-2024 12:45:20","12-12-2024 12:00:08","12-12-2024 12:48:32","Casc=
aded Incident from TTO3777488","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","grid outage, site went down due to Cb(125=
A) faulty in PWC and poor battery backup// He changed Cb(125A) with a CB(2*=
63A), sgen manually started","system","266620","12-12-2024 12:45:20","Sagem=
com CMR"
"Closed Complete","Warning","T0236","IHS_YND_373","NOCINC0003823801","Malou=
n","","12-12-2024 12:32:59","","","Site alarming because Gen stopped due to=
 PWC disfunction// He reduiced load, Site on Gen (PWC to be replaced)","Kem=
eni Franklin","Warning","Warning","POWER","Warning - Site on Battery","Site=
 alarming because Gen stopped due to PWC disfunction// He reduiced load, Si=
te on Gen (PWC to be replaced)","kouoh.jean@ihstowers.com","129","12-12-202=
4 12:32:59","Sagemcom CMR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0003823658","Sou=
s Prefecture","IHS_YND_330, IHS_YND_531, IHS_YND_335, IHS_YND_371, IHS_YND_=
345, IHS_YND_370","12-12-2024 12:10:16","12-12-2024 12:00:08","12-12-2024 1=
2:48:32","grid outage, site went down due to Cb(125A) faulty in PWC and poo=
r battery backup// He changed Cb(125A) with  CB(2*63A), sgen manually start=
ed","Fanda Brice","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Circuit Breaker Issue","grid outage, site went down due to Cb(125A) fa=
ulty in PWC and poor battery backup// He changed Cb(125A) with  CB(2*63A), =
sgen manually started","landry.etame@ihstowers.com","609","12-12-2024 12:10=
:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003823492","c=
hina embassy yde","","12-12-2024 11:41:07","12-12-2024 11:27:02","13-12-202=
4 00:19:03","Active//No power issue on site Ubaie=3D53,3V site on Grid The =
Tx Fme Eloundou/693212405 of huawei is informed and Site UP at=3D11:56 AM",=
"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issue on site Ubaie=3D53,3V site on Grid Th=
e Tx Fme Eloundou/693212405 of huawei is informed and Site UP at=3D11:56 AM=
","stephane.nkamwa@ihstowers.com","847","12-12-2024 11:41:07","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0003823279","B=
astos-BAT","","12-12-2024 11:08:16","12-12-2024 10:50:07","12-12-2024 10:51=
:09","Active // No power issue on site, Site on GRID and UBAIE=3D54.6V ,The=
 Team Robert KIMBOCK(699944517) FROM ZTE  is working on site (Normalized GP=
S )","Mboua Thierry","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active // No power issue on site, Site on =
GRID and UBAIE=3D54.6V ,The Team Robert KIMBOCK(699944517) FROM ZTE  is wor=
king on site (Normalized GPS )","stephane.nkamwa@ihstowers.com","1090","12-=
12-2024 11:08:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003822922","B=
arriere","","12-12-2024 10:29:42","12-12-2024 10:09:28","12-12-2024 10:34:2=
7","Grid bad voltage,and Gen failed to start,No RCP //he bypassed Grid and =
started the Gen","Hyemafo Gildas","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","Grid bad voltage,and Gen failed to start,N=
o RCP //he bypassed Grid and started the Gen","stephane.nkamwa@ihstowers.co=
m","1215","12-12-2024 10:29:42","Sagemcom CMR"
"Cancelled","Warning","T1491","IHS_YND_808","NOCINC0003822437","Mbankolo pe=
tit paris","","12-12-2024 09:13:26","","","","Mboua Thierry","","","","",""=
,"landry.etame@ihstowers.com","127","12-12-2024 09:13:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0003822321","OLAMA","=
","12-12-2024 08:53:20","12-12-2024 08:49:04","12-12-2024 09:07:58","Cascad=
ed Incident from TTO3775996","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuation, Site went down because Ge=
n fails to start due Gen card disfunction// He reset Gen and started","syst=
em","278098","12-12-2024 08:53:20","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003822316","Ako=
no","IHS_YND_687","12-12-2024 08:52:11","12-12-2024 08:49:04","12-12-2024 0=
9:07:58","Grid fluctuation, Site went down because Gen fails to start due G=
en card disfunction// He reset Gen and started","Fanda Brice","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid fluctuation, Site w=
ent down because Gen fails to start due Gen card disfunction// He reset Gen=
 and started","landry.etame@ihstowers.com","187","12-12-2024 08:52:11","Sag=
emcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003821789","Ako=
no","IHS_YND_687","12-12-2024 06:49:57","12-12-2024 06:43:53","12-12-2024 0=
6:49:09","Grid fluctuation, Site went down because Gen fails to start due G=
en card disfunction// He reset Gen and started Gen manualy","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid fluctua=
tion, Site went down because Gen fails to start due Gen card disfunction// =
He reset Gen and started Gen manualy","landry.etame@ihstowers.com","365","1=
2-12-2024 06:49:57","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003821776","OLA=
MA","","12-12-2024 06:44:04","12-12-2024 06:43:53","12-12-2024 06:49:09",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid fluctuation, Site went down because Gen fails to start due Gen car=
d disfunction// He reset Gen and started Gen manualy","landry.etame@ihstowe=
rs.com","271082","12-12-2024 06:44:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003821758","B=
arriere","","12-12-2024 06:39:30","12-12-2024 06:34:22","12-12-2024 09:51:5=
2","Site went down due to  CB(125A) in PWC Disjunted  // He Reamed the CB(1=
25A) ","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Circuit Breaker Issue","Site went down due to  CB(125A) in PWC D=
isjunted  // He Reamed the CB(125A) ","stephane.nkamwa@ihstowers.com","309"=
,"12-12-2024 06:39:30","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0003821486","AKA=
K Nkozoa","","12-12-2024 06:22:09","12-12-2024 06:12:04","12-12-2024 07:54:=
28","site went down due to Cb(125A) in PWC faulty // He changed Cb(125A) wi=
th another of Cb(125A)","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","site went down due to =
Cb(125A) in PWC faulty // He changed Cb(125A) with another of Cb(125A)","la=
ndry.etame@ihstowers.com","606","12-12-2024 06:22:09","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003820509","HOP=
ITAL GENERAL RAIL YDE","","11-12-2024 23:51:57","11-12-2024 23:48:52","12-1=
2-2024 06:16:11","Access issue due to landlord site went down due to disjun=
ction Cb(125A) in PWC // He make the bridge with Cb(125A), site on grid","D=
elor Telezing","Access Denial","Lease Or Legal","Landlord Related Issues","=
Access Issue - Land Lord","Access issue due to landlord site went down due =
to disjunction Cb(125A) in PWC // He make the bridge with Cb(125A), site on=
 grid","rouselle.schoune@ihstowers.com","186","11-12-2024 23:51:57","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003819082","D=
amas","","11-12-2024 20:14:47","11-12-2024 20:04:26","11-12-2024 21:30:16",=
"grid outage, site went down due to Gen overload (09kva, 150A)// Grid retur=
n","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","grid outage, site went down due to Gen overload (09kva, 150A)// Grid ret=
urn","olivier.kwedi@ihstowers.com","622","11-12-2024 20:14:47","Sagemcom CM=
R"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003818858","NKO=
MEKUI OCM","","11-12-2024 19:33:43","11-12-2024 19:29:36","11-12-2024 20:21=
:19","No power issue on site U=3D54v site on gen site impacted by Mbankolo =
Camtel and not managing by IHS","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","Affected by 3rd Party Sit=
e","No power issue on site U=3D54v site on gen site impacted by Mbankolo Ca=
mtel and not managing by IHS","ludivine.ngamaleu@ihstowers.com","248","11-1=
2-2024 19:33:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003817746","Donga","=
","11-12-2024 17:34:31","11-12-2024 17:20:55","11-12-2024 17:30:15","Cascad=
ed Incident from TTO3770605","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubaie: 54,9V site on =
Grid (Hybrid site). Site impacted By Mbadjok camrail. ","system","261827","=
11-12-2024 17:34:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003817747","Dong",""=
,"11-12-2024 17:34:31","11-12-2024 17:20:55","11-12-2024 17:30:15","Cascade=
d Incident from TTO3770605","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site Ubaie: 54,9V site on G=
rid (Hybrid site). Site impacted By Mbadjok camrail. ","system","261827","1=
1-12-2024 17:34:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003817743","Nguila",=
"","11-12-2024 17:34:30","11-12-2024 17:20:55","11-12-2024 17:30:15","Casca=
ded Incident from TTO3770605","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site Ubaie: 54,9V site on=
 Grid (Hybrid site). Site impacted By Mbadjok camrail. ","system","261826",=
"11-12-2024 17:34:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0003817232","M=
beng","IHS_YND_553","11-12-2024 16:19:08","11-12-2024 16:06:02","11-12-2024=
 17:27:07"," site went down because Gen stopped with ""high temp"" alarm// =
He added water and started Gen manually","Fanda Brice","Equipment Repair","=
Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"," site =
went down because Gen stopped with ""high temp"" alarm// He added water and=
 started Gen manually","olivier.kwedi@ihstowers.com","788","11-12-2024 16:1=
9:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003817228","E=
kombitie","","11-12-2024 16:17:37","11-12-2024 16:09:28","11-12-2024 16:19:=
28","No power issue, site is on grid with Ubaie=3D54V, Synphorien(691316854=
) from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, si=
te is on grid with Ubaie=3D54V, Synphorien(691316854) from Huawei is inform=
ed","olivier.kwedi@ihstowers.com","490","11-12-2024 16:17:37","Sagemcom CMR=
"
"Closed Complete","Warning","T0288","IHS_YND_001","NOCINC0003817068","Royal=
 Hotel Yde","","11-12-2024 15:54:15","","","site on alarmdue to grid outage=
//gen started automatically","Paul BIBOUM","Warning","Warning","POWER","War=
ning - Site on Battery","site on alarmdue to grid outage//gen started autom=
atically","dorothy.djantio@ihstowers.com","249","11-12-2024 15:54:15","Sage=
mcom CMR"
"Closed Complete","Warning","T0123","IHS_YND_013","NOCINC0003817055","Labor=
atoire T.Bella","","11-12-2024 15:52:25","","","site on alarm due to grid o=
utage//gen started ","Paul BIBOUM","Warning","Warning","POWER","Warning - S=
ite on Battery","site on alarm due to grid outage//gen started ","dorothy.d=
jantio@ihstowers.com","127","11-12-2024 15:52:25","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0003816729","Bas=
tos Bethesda","","11-12-2024 15:04:33","11-12-2024 14:58:23","11-12-2024 15=
:04:06","Grid outage, site Went down before Gen start due to poor backup// =
Gen started ","Mboua Thierry","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, site Went down before Gen start=
 due to poor backup// Gen started ","ludivine.ngamaleu@ihstowers.com","372"=
,"11-12-2024 15:04:33","Sagemcom CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0003816289","Mba=
nkomo CAF","","11-12-2024 14:14:29","11-12-2024 14:12:22","11-12-2024 20:11=
:56","","Fanda Brice","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","TxNo power issue on site ubaie=3D54v site=
 on grid Georges (Huawei) is informed","ludivine.ngamaleu@ihstowers.com","1=
28","11-12-2024 14:14:29","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003815907","N=
yanon","","11-12-2024 13:36:45","11-12-2024 13:30:41","11-12-2024 13:35:59"=
,"No power issue  site on Gen  Ubaie=3D 53.3V.  The TX FME Gr=E9goire  //65=
2070658//  from huawei is informed .","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue  site on Gen  Ubaie=3D 53.3V.  The TX FME Gr=E9goire  //65=
2070658//  from huawei is informed .","alexandre.kamal@ihstowers.com","366"=
,"11-12-2024 13:36:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003815662","N=
KOLMEKONG YDE","","11-12-2024 13:09:32","11-12-2024 07:55:26","11-12-2024 1=
1:12:26","The site went down due to a short circuit at the MPR (Several cab=
les affected) // we replaced some cables and reconnected the MPR: Site on g=
rid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier =
Module Overloaded","The site went down due to a short circuit at the MPR (S=
everal cables affected) // we replaced some cables and reconnected the MPR:=
 Site on grid","alexandre.kamal@ihstowers.com","18847","11-12-2024 13:09:32=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003815535","M=
ontee-Des-Soeurs","","11-12-2024 12:46:44","11-12-2024 12:39:40","11-12-202=
4 14:48:53","Grid outage, site went down before gen start due to poor batte=
ry backup   // Gen manually started ","Hyemafo Gildas","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup and a load balance  //=
 Gen manually started ","alexandre.kamal@ihstowers.com","425","11-12-2024 1=
2:46:44","Sagemcom CMR"
"Closed Complete","Warning","T0573","IHS_YND_387","NOCINC0003815485","Talla=
 Monatele","","11-12-2024 12:38:09","","","Grid fluctuation, site went alar=
m before gen start // gen start automatically","Parker Tchoup","Warning","W=
arning","POWER","Warning - Site on Battery","Grid fluctuation, site went al=
arm before gen start // gen start automatically","dorothy.djantio@ihstowers=
.com","186","11-12-2024 12:38:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003815404","C=
RH-Etoug-Ebe","","11-12-2024 12:23:24","11-12-2024 12:14:17","11-12-2024 15=
:59:29","Active//No power issue, site on grid U=3D54V, TX FME Mohamadou/691=
144435 from huawei is informed","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No pow=
er issue, site on grid U=3D54V, TX FME Mohamadou/691144435 from huawei is i=
nformed","alexandre.kamal@ihstowers.com","548","11-12-2024 12:23:24","Sagem=
com CMR"
"Closed Complete","Warning","CTR_029","IHS_YND_046","NOCINC0003815344","Djo=
ungolo","","11-12-2024 12:14:38","","","site went alarm due to 02 rectifier=
 disfunction //reset done and gen start","Mboua Thierry","Warning","Warning=
","POWER","Warning - Rectifier Module","site went alarm due to 02 rectifier=
 disfunction //reset done and gen start","dorothy.djantio@ihstowers.com","2=
45","11-12-2024 12:14:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003814835","O=
dza II","","11-12-2024 10:55:30","11-12-2024 10:44:26","11-12-2024 14:49:51=
","grid outage, site went down because the power cable burned of gen causin=
g by short circuit//bypassed it and started the gen(investigation ongoing)"=
,"Albran Byorel","Equipment Repair","Passive","Infrastructure","Armoured Ca=
ble","grid outage, site went down because the power cable burned of gen cau=
sing by short circuit//bypassed it and started the gen(investigation ongoin=
g)","alexandre.kamal@ihstowers.com","666","11-12-2024 10:55:30","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003814684","D=
amas","","11-12-2024 10:38:44","11-12-2024 10:29:39","11-12-2024 10:55:52",=
"Grid outage site went down due to Gen overload(9kva, 150Kva)//Grid return"=
,"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage site went down due to Gen overload(9kva, 150Kva)//Grid return"=
,"alexandre.kamal@ihstowers.com","546","11-12-2024 10:38:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003814009","Akak-Nko=
zoa-MTN-IHS","","11-12-2024 09:06:40","11-12-2024 08:56:01","11-12-2024 09:=
04:04","Cascaded Incident from TTO3766225","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site down due=
 to poor backup // Grid return","system","263242","11-12-2024 09:06:40","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003813791","BIY=
EMASSI NIKI","","11-12-2024 08:35:49","11-12-2024 08:17:19","11-12-2024 08:=
41:29","	Site went down due to PWC overloaded (12kva 250 A) //Site stabiliz=
ed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","	Site went down due to PWC overloaded (12kva 250 A) //Sit=
e stabilized","kamga.virgile@ihstowers.com","1111","11-12-2024 08:35:49","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003813203","S=
tade-Abega","","11-12-2024 06:36:37","11-12-2024 06:27:34","11-12-2024 06:5=
2:26","Grid outage, site Went down before Gen start due to poor backup// Ge=
n started automatily","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site Went down befor=
e Gen start due to poor backup// Gen started automatily","alexandre.kamal@i=
hstowers.com","544","11-12-2024 06:36:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003813183","A=
WAE OCM","","11-12-2024 06:30:58","11-12-2024 06:20:54","11-12-2024 06:52:3=
9","Grid outage , Site went down before Gen start due to poor backup// Grid=
 return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage , Site went down before Gen start =
due to poor backup// Grid return","alexandre.kamal@ihstowers.com","605","11=
-12-2024 06:30:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003812979","N=
KOLMEKONG YDE","","11-12-2024 05:52:21","11-12-2024 05:45:16","11-12-2024 0=
7:09:40","The site went down due to a short circuit at the MPR (Several cab=
les affected) // we replaced some cables and reconnected the MPR: Site on g=
rid","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier =
Module Overloaded","The site went down due to a short circuit at the MPR (S=
everal cables affected) // we replaced some cables and reconnected the MPR:=
 Site on grid","emmanuel.ghani@ihstowers.com","426","11-12-2024 05:52:21","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003812135","Akak-Nko=
zoa-MTN-IHS","","11-12-2024 00:32:30","11-12-2024 00:21:25","11-12-2024 00:=
31:59","Cascaded Incident from TTO3764013","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site down due=
 to poor backup // Grid return","system","265310","11-12-2024 00:32:30","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003812098","BIY=
EMASSI NIKI","","11-12-2024 00:24:37","11-12-2024 00:18:31","11-12-2024 00:=
25:38","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Site =
stabilized","christian.fonkou@ihstowers.com","367","11-12-2024 00:24:37","S=
agemcom CMR"
"Closed Complete","Warning","","IHS_YND_270","NOCINC0003811869","Santa Barb=
ara Yde","","10-12-2024 23:13:31","","","Site alarming High Temp 38=B0C// T=
emp dicrease ","Delor Telezing","Warning","Warning","ENVIRONMENT","Warning =
- High Temperature","Site alarming High Temp 38=B0C// Temp dicrease ","joel=
le.ekessi@ihstowers.com","64","10-12-2024 23:13:31","Sagemcom CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0003811640","Mba=
nkomo CAF","","10-12-2024 22:33:16","10-12-2024 22:26:05","11-12-2024 05:27=
:07","Active//No power issue on site U=3D54,5v site on Gen The TX fme Georg=
e(697461814) from huawei is informed","Fanda Brice","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site U=3D54,5v site on Gen The TX fme George(697461814) from huawei =
is informed","christian.fonkou@ihstowers.com","432","10-12-2024 22:33:16","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003811618","N=
gouetou","","10-12-2024 22:28:45","10-12-2024 22:25:38","11-12-2024 01:14:5=
6"," site went down because Gen stopped with ""high temp"" alarm ""  causin=
g by External pierced pad // He seal it and Manually Started the Gen ","Par=
ker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Tem=
p - Coolant Level Issue","site went down because Gen stopped with ""high te=
mp"" alarm ""  causing by External pierced pad // He seal it and Manually S=
tarted the Gen ","emmanuel.ghani@ihstowers.com","188","10-12-2024 22:28:45"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003811582","C=
RH-Etoug-Ebe","","10-12-2024 22:21:21","10-12-2024 22:08:18","10-12-2024 22=
:55:11","Site went down because CB(80A) tripped in PWC who feeds equipments=
 OCM// CB put back on","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Circuit Breaker Issue","Site went down because C=
B(80A) tripped in PWC who feeds equipments OCM// CB put back on","emmanuel.=
ghani@ihstowers.com","784","10-12-2024 22:21:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003810743","H=
-General-Yde","","10-12-2024 20:04:40","10-12-2024 19:09:19","10-12-2024 20=
:07:18","Site went down due to 01/03 Rectifier Faulty// He replaced the Fau=
lty rectifier and Site is on Grid ","Siligap Boris","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Site went down due to 01/03 Rectifier=
 Faulty// He replaced the Faulty rectifier and Site is on Grid ","denis.mba=
lla@ihstowers.com","3322","10-12-2024 20:04:40","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003810557","HOP=
ITAL GENERAL RAIL YDE","","10-12-2024 19:33:16","10-12-2024 19:25:12","10-1=
2-2024 20:19:36","site went down due to 1/3 rectifier faulty//He replaced t=
he faulty rectifier","Delor Telezing","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","site went down due to 1/3 rectifier faulty//He repl=
aced the faulty rectifier","rouselle.schoune@ihstowers.com","485","10-12-20=
24 19:33:16","Sagemcom CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0003810548","Pha=
rmacie Bleue","","10-12-2024 19:32:31","10-12-2024 19:25:24","10-12-2024 20=
:19:15","site went down due to 1/2rectifier faulty and CB 32A disjuncted//h=
e replaced the faulty rectifier and reamed the CB","Siligap Boris","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","site went down due to =
1/2rectifier faulty and CB 32A disjuncted//he replaced the faulty rectifier=
 and reamed the CB","rouselle.schoune@ihstowers.com","428","10-12-2024 19:3=
2:31","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_316","NOCINC0003810276","Akak-Nkozo=
a-MTN-IHS","","10-12-2024 18:44:00","","","Alarm not proven,site on DG,Ubai=
e:54.2V; ","Fabrice Pouakam","Warning","Warning","SYSTEM","Warning - False =
Alarm","Alarm not proven,site on DG,Ubaie:54.2V; ","system","359","10-12-20=
24 18:44:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0003808120","S=
oa-Sofamac","","10-12-2024 15:01:04","10-12-2024 14:54:52","10-12-2024 15:0=
6:25","site went down due to system hybrid disfunctionning//Gen manually st=
arted","Siligap Boris","Equipment Repair","Passive","Hybrid","Hybrid Module=
","site went down due to system hybrid disfunctionning//Gen manually starte=
d","denis.mballa@ihstowers.com","373","10-12-2024 15:01:04","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003807989","BIY=
EMASSI NIKI","","10-12-2024 14:47:08","10-12-2024 14:38:59","10-12-2024 14:=
48:43","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Site =
stabilized","rouselle.schoune@ihstowers.com","490","10-12-2024 14:47:08","S=
agemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003807592","N=
yanon","","10-12-2024 13:57:03","10-12-2024 13:47:53","10-12-2024 13:48:22"=
,": No power issue site on Gen ubaie=3D 55.3V.The TX FME Gr=E9goire  //6520=
70658//  from huawei is informed .","TIENTCHEU NZETCHIEU GAEL","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
: No power issue site on Gen ubaie=3D 55.3V.The TX FME Gr=E9goire  //652070=
658//  from huawei is informed .","olivier.kwedi@ihstowers.com","551","10-1=
2-2024 13:57:03","Sagemcom CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0003807281","Ese=
ka Town","","10-12-2024 13:16:19","10-12-2024 13:03:05","10-12-2024 15:17:5=
3"," site went down because gen stopped with a high temperature alarm causi=
ng by  punctured durick // he added water to the radiator (he glued the dur=
ick)","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - Hig=
h Engine Temp - Coolant Level Issue"," site went down because gen stopped w=
ith a high temperature alarm causing by  punctured durick // he added water=
 to the radiator (he glued the durick)","dorothy.djantio@ihstowers.com","17=
26","10-12-2024 13:16:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0003806995","M=
essassi 2","","10-12-2024 12:44:33","10-12-2024 12:39:08","10-12-2024 14:09=
:31","Grid outage.gen start and stopped due to alarm""low oil  pressure""//=
Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACD=
G - Low Oil Pressure","Grid outage.gen start and stopped due to alarm""low =
oil  pressure""//Grid return","olivier.kwedi@ihstowers.com","327","10-12-20=
24 12:44:33","Sagemcom CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0003806924","Mes=
sassi Ngonlonk","","10-12-2024 12:35:43","10-12-2024 12:29:36","10-12-2024 =
13:48:20","Grid outage.gen failed to start due to battery GE faulty//Gen ma=
nually started with external battery ","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Generator Battery","Grid outage.gen failed to=
 start due to battery GE faulty//Gen manually started with external battery=
 ","dorothy.djantio@ihstowers.com","368","10-12-2024 12:35:43","Sagemcom CM=
R"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0003806682","NKO=
LMEKONG YDE","","10-12-2024 12:05:38","10-12-2024 12:02:34","10-12-2024 13:=
17:24","Grid outage, Site went down because Gen started and stopped with al=
arm overvoltage// He reset Gen card and started Gen manualy","Fabrice Pouak=
am","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage, Site went down because Gen started and stopped with alarm overvoltage=
// He reset Gen card and started Gen manualy","dorothy.djantio@ihstowers.co=
m","185","10-12-2024 12:05:38","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003805993","BIY=
EMASSI NIKI","","10-12-2024 11:21:08","10-12-2024 11:19:03","10-12-2024 11:=
21:31","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Site =
stabilized","dorothy.djantio@ihstowers.com","126","10-12-2024 11:21:08","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003805710","Nkolbiss=
on usines des eaux 2","","10-12-2024 11:05:50","10-12-2024 10:58:05","10-12=
-2024 11:04:59","Cascaded Incident from TTO3756491","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, site went down before Gen start due to poor backup// Grid return","sy=
stem","277396","10-12-2024 11:05:50","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003805700","Nko=
lbisson","IHS_YND_763","10-12-2024 11:05:13","10-12-2024 10:58:05","10-12-2=
024 11:04:59","Grid outage, site went down before Gen start due to poor bac=
kup// Grid return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before Gen start due to poor backup// Grid return","dorothy.djantio@ihstowe=
rs.com","429","10-12-2024 11:05:13","Sagemcom CMR"
"Cancelled","Warning","T3217","IHS_YND_763","NOCINC0003805648","Nkolbisson =
usines des eaux 2","","10-12-2024 11:02:06","","","","TIENTCHEU NZETCHIEU G=
AEL","","","","","","dorothy.djantio@ihstowers.com","187","10-12-2024 11:02=
:06","Sagemcom CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0003804705","Ako=
no","","10-12-2024 09:15:17","","","Site alarmig with grid outage// alarm c=
leared wit reset card GE and gen manually started ","Fanda Brice","Warning"=
,"Warning","POWER","Warning - Site on Battery","Site alarmig with grid outa=
ge// alarm cleared wit reset card GE and gen manually started ","ludivine.n=
gamaleu@ihstowers.com","2","10-12-2024 09:15:17","Sagemcom CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0003804339","Odz=
a petit marche new","","10-12-2024 08:25:14","10-12-2024 08:21:09","10-12-2=
024 08:26:32","Site went  down because 02/03 rectifiers Hanging // He reset=
 rectifiers ,site on GEN","Albran Byorel","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went  down because 02/03 rectifiers Hangin=
g // He reset rectifiers ,site on GEN","dorothy.djantio@ihstowers.com","246=
","10-12-2024 08:25:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003804040","SOA VILL=
AGE","","10-12-2024 07:30:30","10-12-2024 07:27:44","10-12-2024 07:46:36","=
Cascaded Incident from TTO3754564","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen started and stopped with alarm ""undervoltage""// He reset Gen card and=
 started Gen manualy","system","268500","10-12-2024 07:30:30","Sagemcom CMR=
"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003804030","SOA=
 TOWN","IHS_YND_323","10-12-2024 07:29:47","10-12-2024 07:24:40","10-12-202=
4 07:46:36","Grid outage site went down because Gen started and stopped wit=
h alarm ""undervoltage""// He reset Gen card and started Gen manualy","Sili=
gap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage site went down because Gen started and stopped with alarm ""und=
ervoltage""// He reset Gen card and started Gen manualy","dorothy.djantio@i=
hstowers.com","369","10-12-2024 07:29:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003803125","N=
kolfon Cimencam","","10-12-2024 05:17:21","10-12-2024 05:07:07","10-12-2024=
 05:12:29","Active//No power issue on site U=3D54,5v site on Gen The TX fme=
 George(697461814) from huawei is informed. Noticed that site is impacted b=
y Afanoya (Not manage by HIS)impacted by afanoya II not manage b","Hyemafo =
Gildas","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No power issue on site U=3D54,5v site on Gen Th=
e TX fme George(697461814) from huawei is informed. Noticed that site is im=
pacted by Afanoya (Not manage by HIS)impacted by afanoya II not manage by I=
HS","stephane.nkamwa@ihstowers.com","615","10-12-2024 05:17:21","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003802472","N=
komkana","","10-12-2024 01:27:57","10-12-2024 01:25:41","10-12-2024 18:47:5=
0","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space t=
o deploy a MDG//Grid Restored","stephane.nkamwa@ihstowers.com","137","10-12=
-2024 01:27:57","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003801961","HOP=
ITAL GENERAL RAIL YDE","","09-12-2024 23:09:04","09-12-2024 23:01:50","10-1=
2-2024 00:31:18","Site went down because CB(125A) tripped in PWC// CB put b=
ack on","Delor Telezing","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Circuit Breaker Issue","Site went down because CB(125A) tripped=
 in PWC// CB put back on","landry.etame@ihstowers.com","434","09-12-2024 23=
:09:04","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0003801807","Bas=
tos Bethesda","","09-12-2024 22:27:38","09-12-2024 22:20:25","10-12-2024 00=
:12:01","Grid outage, site went down because gen start and stopped with hig=
h temp alarm // he added water and manually start the gen","Mboua Thierry",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid outage, site went down because gen start and stopped wit=
h high temp alarm // he added water and manually start the gen","landry.eta=
me@ihstowers.com","434","09-12-2024 22:27:38","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003801617","Nom=
ayos montee Meche","","09-12-2024 21:54:24","09-12-2024 21:46:13","09-12-20=
24 22:26:35","Grid outage, site went down because the bay DPC disfunctionni=
ng//Grid return","Fanda Brice","Equipment Repair","Passive","Rectifier","Re=
ctifier Module Overloaded","Grid outage, site went down because the bay DPC=
 disfunctionning//Grid return","christian.fonkou@ihstowers.com","492","09-1=
2-2024 21:54:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003801145","M=
ontee-Jouvence-II","","09-12-2024 21:03:49","09-12-2024 21:02:42","09-12-20=
24 21:05:22","Grid fluctuation site went down because Gen failed to start d=
ue to Grid bad voltage and RCP on site // He bypass the Grid and Gen manual=
ly started","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","Grid fluctuation site went down because Gen fai=
led to start due to Grid bad voltage and RCP on site // He bypass the Grid =
and Gen manually started","emmanuel.ghani@ihstowers.com","68","09-12-2024 2=
1:03:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003800808","SOA VILL=
AGE","","09-12-2024 19:59:00","09-12-2024 19:53:43","09-12-2024 20:44:45","=
Cascaded Incident from TTO3750636","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation site went down bec=
ause Gen failed to start due to Grid bad voltage and RCP on site // He bypa=
ss the Grid and Gen manually started","system","266821","09-12-2024 19:59:0=
0","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003800802","SOA=
 TOWN","IHS_YND_323","09-12-2024 19:57:48","09-12-2024 19:50:43","09-12-202=
4 20:44:45","Grid fluctuation site went down because Gen failed to start du=
e to Grid bad voltage and RCP on site // He bypass the Grid and Gen manuall=
y started","Siligap Boris","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","Grid fluctuation site went down because Gen faile=
d to start due to Grid bad voltage and RCP on site // He bypass the Grid an=
d Gen manually started","christian.fonkou@ihstowers.com","926","09-12-2024 =
19:57:48","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003800285","MBI=
MBIM","","09-12-2024 18:35:17","09-12-2024 18:27:10","09-12-2024 18:52:30",=
"Solar Gen: Site went down before Gen start due to poor battery backup// Ge=
n started automatically","Parker Tchoup","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Solar Gen: Site went down before =
Gen start due to poor battery backup// Gen started automatically","christia=
n.fonkou@ihstowers.com","488","09-12-2024 18:35:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0003799956","SAA Entr=
ance","","09-12-2024 17:49:20","09-12-2024 17:44:37","09-12-2024 18:31:12",=
"Cascaded Incident from TTO3749614","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,Gen Ran till fuel shor=
tage//Refueling Done","system","267601","09-12-2024 17:49:20","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003799957","Saa","",=
"09-12-2024 17:49:20","09-12-2024 17:44:37","09-12-2024 18:31:12","Cascaded=
 Incident from TTO3749614","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage,Gen Ran till fuel shortage//Ref=
ueling Done","system","267601","09-12-2024 17:49:20","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0003799944","SAA=
 2","IHS_YND_542, IHS_YND_405","09-12-2024 17:47:43","09-12-2024 17:39:37",=
"09-12-2024 18:31:41","Grid outage,Gen Ran till fuel shortage//Refueling Do=
ne","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid =
outage,Gen Ran till fuel shortage//Refueling Done","christian.fonkou@ihstow=
ers.com","566","09-12-2024 17:47:43","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003799341","Nsi=
meyong Terre Rouge","","09-12-2024 16:13:29","09-12-2024 16:07:22","09-12-2=
024 16:18:40","Grid outage, site went down before gen start due to poor bat=
teries backup // Grid power return","MINKA NICOLAS","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor batteries backup // Grid power return","=
christian.fonkou@ihstowers.com","368","09-12-2024 16:13:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0003799299","S=
imbock OCM","","09-12-2024 16:06:57","09-12-2024 15:58:41","09-12-2024 18:0=
0:42","Active//No power issue U=3D54,9V site on Grid The Tx Fme Hosiah Mbah=
 (674007438) of Huawei is informed and Site UP AT=3D04:11 PM","Hyemafo Gild=
as","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue U=3D54,9V site on Grid The Tx Fme Ho=
siah Mbah (674007438) of Huawei is informed and Site UP AT=3D04:11 PM","emm=
anuel.ghani@ihstowers.com","497","09-12-2024 16:06:57","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003799122","ODZ=
A CITE MBIA","","09-12-2024 15:34:49","09-12-2024 15:30:42","09-12-2024 17:=
04:59","Grid fluctuctuation,site went down because gen failed to start due =
grid bad voltage// He bypassed grid, Gen manually started","Albran Byorel",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid fluctuctuation,site went down because gen failed to start due grid bad =
voltage// He bypassed grid, Gen manually started","christian.fonkou@ihstowe=
rs.com","248","09-12-2024 15:34:49","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_319","NOCINC0003799035","SOA 2","",=
"09-12-2024 15:18:35","","","Site on Gen, site alarming High temp 43=B0c// =
He open shelter and temp dicrease","Siligap Boris","Warning","Warning","ENV=
IRONMENT","Warning - High Temperature","Site on Gen, site alarming High tem=
p 43=B0c// He open shelter and temp dicrease","joelle.ekessi@ihstowers.com"=
,"70","09-12-2024 15:18:35","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003798518","ODZ=
A MINKAN EDIBI ASSI","","09-12-2024 14:18:47","09-12-2024 14:14:39","09-12-=
2024 15:34:12","Grid outage,DG started but did not feed the site,due to ACD=
G contactor dysfonctioning(contactor DG not excited )//He excited DG and si=
te on DG.","Albran Byorel","Equipment Repair","Passive","Control Panel","AT=
S-AMF Issue","Grid outage,DG started but did not feed the site,due to ACDG =
contactor dysfonctioning(contactor DG not excited )//He excited DG and site=
 on DG.","christian.fonkou@ihstowers.com","249","09-12-2024 14:18:47","Sage=
mcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003798380","N=
yanon","","09-12-2024 13:57:06","09-12-2024 13:43:38","09-12-2024 17:30:13"=
,"No Power issue on site , site on Grid with Ubaie=3D55.8V The Tx Gregoire(=
654547479) from Huawei is working on site.","TIENTCHEU NZETCHIEU GAEL","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No Power issue on site , site on Grid with Ubaie=3D55.8V The Tx Gre=
goire(654547479) from Huawei is working on site.","denis.mballa@ihstowers.c=
om","810","09-12-2024 13:57:06","Sagemcom CMR"
"Closed Complete","Warning","T1059","IHS_YND_434","NOCINC0003797843","Donga=
","","09-12-2024 12:48:51","","","Site on battery due yo hybrid system // D=
G started automatically.","Parker Tchoup","Warning","Warning","POWER","Warn=
ing - Site on Battery","Site on battery due yo hybrid system // DG started =
automatically.","kombi.samuel@ihstowers.com","3","09-12-2024 12:48:51","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003796125","Yoko MTN=
","IHS_YND_475","09-12-2024 09:08:00","09-12-2024 09:02:07","09-12-2024 09:=
47:19","site down because gen start and stopped due to pear perced//he glue=
d the pear (pear to be replace), started the gen","Parker Tchoup","Fuel Out=
age (Probable)","Passive","Diesel","Fuel Line Issue","site down because gen=
 start and stopped due to pear perced//he glued the pear (pear to be replac=
e), started the gen","system","353","09-12-2024 09:08:00","Sagemcom CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0003796120","Ngo=
um","","09-12-2024 09:07:13","09-12-2024 09:02:07","09-12-2024 09:47:19","s=
ite down because gen start and stopped due to pear perced//he glued the pea=
r (pear to be replace), started the gen","Parker Tchoup","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site down because gen start a=
nd stopped due to pear perced//he glued the pear (pear to be replace), star=
ted the gen","rouselle.schoune@ihstowers.com","277169","09-12-2024 09:07:13=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0003795821","Nomayos-=
IHS","","09-12-2024 08:18:42","09-12-2024 07:45:34","09-12-2024 08:05:55","=
Cascaded Incident from TTO3744672","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuctuation,site went down be=
cause gen failed to start due grid bad voltage// He bypassed grid, Gen manu=
ally started","system","267517","09-12-2024 08:18:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0003795822","NKONGKAR=
AK","","09-12-2024 08:18:42","09-12-2024 07:45:34","09-12-2024 08:05:55","C=
ascaded Incident from TTO3744672","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid fluctuctuation,site =
went down because gen failed to start due grid bad voltage// He bypassed gr=
id, Gen manually started","system","267515","09-12-2024 08:18:42","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0003795820","Ekekam",=
"","09-12-2024 08:18:42","09-12-2024 07:45:34","09-12-2024 08:05:55","Casca=
ded Incident from TTO3744672","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuctuation,site went=
 down because gen failed to start due grid bad voltage// He bypassed grid, =
Gen manually started","system","267517","09-12-2024 08:18:42","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0003795818","Bot Maka=
k","","09-12-2024 08:18:41","09-12-2024 07:45:34","09-12-2024 08:05:55","Ca=
scaded Incident from TTO3744672","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid fluctuctuation,site went down because gen fai=
led to start due grid bad voltage// He bypassed grid, Gen manually started"=
,"system","267516","09-12-2024 08:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003795817","Ngog Map=
ubi","","09-12-2024 08:18:41","09-12-2024 07:45:34","09-12-2024 08:05:55","=
Cascaded Incident from TTO3744672","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuctuation,site went dow=
n because gen failed to start due grid bad voltage// He bypassed grid, Gen =
manually started","system","267514","09-12-2024 08:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003795819","Nkongtoc=
k","","09-12-2024 08:18:41","09-12-2024 07:45:34","09-12-2024 08:05:55","Ca=
scaded Incident from TTO3744672","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuctuation,site went down =
because gen failed to start due grid bad voltage// He bypassed grid, Gen ma=
nually started","system","267514","09-12-2024 08:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0003795816","Nkeng li=
kok","","09-12-2024 08:18:41","09-12-2024 07:45:34","09-12-2024 08:05:55","=
Cascaded Incident from TTO3744672","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuctuation,site went dow=
n because gen failed to start due grid bad voltage// He bypassed grid, Gen =
manually started","system","267518","09-12-2024 08:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_373","NOCINC0003795815","Maloun",=
"","09-12-2024 08:18:40","09-12-2024 07:45:34","09-12-2024 08:05:55","Casca=
ded Incident from TTO3744672","Kemeni Franklin","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuctuation,site went down bec=
ause gen failed to start due grid bad voltage// He bypassed grid, Gen manua=
lly started","system","267515","09-12-2024 08:18:40","Sagemcom CMR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0003795624","Sou=
s Prefecture","IHS_YND_373, IHS_YND_347, IHS_YND_419, IHS_YND_421, IHS_YND_=
349, IHS_YND_714, IHS_YND_697, IHS_YND_713","09-12-2024 07:46:38","09-12-20=
24 07:45:34","09-12-2024 08:07:39","Grid fluctuctuation,site went down beca=
use gen failed to start due grid bad voltage// He bypassed grid, Gen manual=
ly started","Fanda Brice","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","Grid fluctuctuation,site went down because gen fai=
led to start due grid bad voltage// He bypassed grid, Gen manually started"=
,"rouselle.schoune@ihstowers.com","65","09-12-2024 07:46:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003794227","O=
lembe-Terminus","","09-12-2024 01:04:28","09-12-2024 00:05:20","09-12-2024 =
02:13:15","Site went down due to insufficience of rectifier (05)// Site Sta=
bilized (rectifier to be added)","Fabrice Pouakam","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","Site went down due to insufficience of=
 rectifier (05)// Site Stabilized (rectifier to be added)","alexandre.kamal=
@ihstowers.com","3549","09-12-2024 01:04:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0003794060","M=
bedoumou - Ekali","","09-12-2024 00:12:52","08-12-2024 23:44:33","08-12-202=
4 23:50:46","Active// No power issue site on Gen Ubai=3D 53,9V, Claude Adio=
bo / From SNEF/ 696023457 working on site (Swap MW)","Albran Byorel","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue site on Gen Ubai=3D 53,9V, Claude Adiobo / Fr=
om SNEF/ 696023457 working on site (Swap MW)","alexandre.kamal@ihstowers.co=
m","1699","09-12-2024 00:12:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003793629","C=
RH-Etoug-Ebe","","08-12-2024 22:30:59","08-12-2024 22:00:47","08-12-2024 23=
:13:42","Site went down because CB(80A) tripped in PWC who feeds equipments=
 OCM// CB put back on ","Hyemafo Gildas","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down because =
CB(80A) tripped in PWC who feeds equipments OCM// CB put back on ","alexand=
re.kamal@ihstowers.com","1812","08-12-2024 22:30:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003792874","A=
bom","","08-12-2024 20:57:21","08-12-2024 20:46:01","08-12-2024 21:04:02","=
site went down because Gen overload(16KVA, 220A) // site stabilized","Silig=
ap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","site w=
ent down because Gen overload(16KVA, 220A) // site stabilized","stephane.nk=
amwa@ihstowers.com","681","08-12-2024 20:57:21","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003792783","OBA=
M NGOLA OCM","","08-12-2024 20:51:25","08-12-2024 20:46:19","08-12-2024 21:=
40:48","Grid fluctuation site went down because Gen failed to start due to =
Grid bad voltage // he bypass the Grid and Gen manually started","MINKA NIC=
OLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation site went down because Gen failed to start due to Gri=
d bad voltage // he bypass the Grid and Gen manually started","landry.etame=
@ihstowers.com","307","08-12-2024 20:51:25","Sagemcom CMR"
"Closed Complete","Warning","T1546","IHS_YND_164","NOCINC0003792671","OBAM =
NGOLA OCM","","08-12-2024 20:27:52","","","Grid fluctuation site went Alarm=
 because Gen fails to start due to Grid bad voltage // he bypass the Grid a=
nd Gen manually started","MINKA NICOLAS","Warning","Warning","POWER","Warni=
ng - Site on Battery","Grid fluctuation site went Alarm because Gen fails t=
o start due to Grid bad voltage // he bypass the Grid and Gen manually star=
ted","kouoh.jean@ihstowers.com","426","08-12-2024 20:27:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_801","NOCINC0003792560","HOPITAL =
GENERAL RAIL YDE","","08-12-2024 19:59:20","08-12-2024 19:44:18","08-12-202=
4 21:06:05","Cascaded Incident from TTO3740882","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","site went down becaus=
e  the Cb(32A) of rectifier dysjuncted and 01/02 rectifier faulty // he add=
ed  01 rectifier and reamed the Cb of rectifier on site ","system","267391"=
,"08-12-2024 19:59:20","Sagemcom CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0003792517","Pha=
rmacie Bleue","IHS_YND_801","08-12-2024 19:54:25","08-12-2024 19:44:18","08=
-12-2024 21:06:05","site went down because  the Cb(32A) of rectifier dysjun=
cted and 01/02 rectifier faulty // he added  01 rectifier and reamed the Cb=
 of rectifier on site ","Siligap Boris","Equipment Repair","Passive","Recti=
fier","Rectifier - Circuit Breaker","site went down because  the Cb(32A) of=
 rectifier dysjuncted due to 01/02 rectifier faulty // he added  01 rectifi=
er and reamed the Cb of rectifier on site ","landry.etame@ihstowers.com","6=
07","08-12-2024 19:54:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003792473","A=
bom","","08-12-2024 19:49:51","08-12-2024 19:42:43","08-12-2024 19:59:55","=
Grid outage site went down because Gen overload (16Kva.220A) // Site stabil=
lized","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage site went down because Gen overload (16Kva.220A) // Site=
 stabillized","stephane.nkamwa@ihstowers.com","429","08-12-2024 19:49:51","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003792460","T=
amtam Weekend","","08-12-2024 19:47:04","08-12-2024 19:32:55","08-12-2024 1=
9:45:58","No power issue, site is on Grid with Ubaie=3D51,9 V The TX FME Mb=
ah Hosiah (674007438) from Huawei is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue, site is on Grid with Ubaie=3D51,9 V The TX FME Mbah Hosiah=
 (674007438) from Huawei is informed, Notice that we have disjunction at BT=
S OCM","stephane.nkamwa@ihstowers.com","849","08-12-2024 19:47:04","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003792353","H=
-General-Yde","","08-12-2024 19:36:12","08-12-2024 19:26:52","08-12-2024 20=
:48:40","site went down because 02/04 rectifier faulty // he added  01 rect=
ifier on site ","Siligap Boris","Equipment Repair","Passive","Rectifier","R=
ectifier Module","site went down because 02/04 rectifier faulty // he added=
  01 rectifier on site ","stephane.nkamwa@ihstowers.com","561","08-12-2024 =
19:36:12","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0003792296","Bas=
tos Bethesda","","08-12-2024 19:25:34","08-12-2024 19:17:22","08-12-2024 19=
:24:47","Grid outage, site went down before Gen start due to poor backup// =
Grid power return","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before Gen =
start due to poor backup// Grid power return","landry.etame@ihstowers.com",=
"493","08-12-2024 19:25:34","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003792265","Mok=
olo Yaounde","","08-12-2024 19:23:51","08-12-2024 19:17:45","08-12-2024 19:=
26:28","No power issue U =3D53,2V site on grid. The Tx FME Eloundou Bertran=
d (693212405)from Huawei is informed","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U =3D53=
,2V site on grid. The Tx FME Eloundou Bertrand (693212405)from Huawei is in=
formed","landry.etame@ihstowers.com","367","08-12-2024 19:23:51","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003791994","M=
ontee-Jouvence-II","","08-12-2024 18:45:58","08-12-2024 18:10:49","08-12-20=
24 20:34:53","site went down because PWC overload (12Kilo, 260A) // site st=
abilized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectif=
ier Module Overloaded","site went down because PWC overload (12Kilo, 260A) =
// site stabilized","stephane.nkamwa@ihstowers.com","2110","08-12-2024 18:4=
5:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003791559","E=
mombo-Tchad","IHS_YND_114","08-12-2024 17:37:23","08-12-2024 16:26:11","08-=
12-2024 20:32:52","Grid outage No space to deploy the MDG // Grid power ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid outage No space to deploy the MDG // Grid power return","stephane.nka=
mwa@ihstowers.com","4273","08-12-2024 17:37:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0003791546","K=
ondengui","","08-12-2024 17:36:06","08-12-2024 16:26:11","08-12-2024 20:32:=
52","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid outage No space to deploy the MDG // Grid power return","s=
tephane.nkamwa@ihstowers.com","279424","08-12-2024 17:36:06","Sagemcom CMR"
"Closed Complete","Site Down","T3175","IHS_YND_566","NOCINC0003790825","Crf=
 Cornier","","08-12-2024 15:45:58","08-12-2024 15:32:48","08-12-2024 17:40:=
39","grid outage, site went down because gen failed to start due to battery=
 gen faulty // He gen manuallys with the external battery","MINKA NICOLAS",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","grid ou=
tage, site went down because gen failed to start due to battery gen faulty =
// He gen manuallys with the external battery","landry.etame@ihstowers.com"=
,"791","08-12-2024 15:45:58","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0003790808","Jou=
vence Mbenda","","08-12-2024 15:42:27","08-12-2024 15:06:19","08-12-2024 15=
:10:15","No power issue U=3D55.5 v site on grid The Tx Fme Hosiah Mbah (674=
007438) of Huawei is informed","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
U=3D55.5 v site on grid The Tx Fme Hosiah Mbah (674007438) of Huawei is inf=
ormed","landry.etame@ihstowers.com","2169","08-12-2024 15:42:27","Sagemcom =
CMR"
"Closed Complete","Site Down","T1746","IHS_YND_178","NOCINC0003790794","Emo=
mbo","","08-12-2024 15:38:58","08-12-2024 15:08:53","08-12-2024 15:56:49","=
Grid outage site went down because Gen started and stopped with alarm low o=
il pressure // he reset the Gen card and Gen manually started","Mba Lazare =
Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage site went down because Gen started and stopped with alarm low oil p=
ressure // he reset the Gen card and Gen manually started","landry.etame@ih=
stowers.com","1806","08-12-2024 15:38:58","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003790445","ODZ=
A CITE MBIA","","08-12-2024 14:42:53","08-12-2024 14:06:46","08-12-2024 17:=
53:56","grid outage, site went down because gen failed to start due to batt=
ery gen faulty // He gen manuallys with the external battery","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","grid=
 outage, site went down because gen failed to start due to battery gen faul=
ty // He gen manuallys with the external battery","landry.etame@ihstowers.c=
om","2168","08-12-2024 14:42:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003790307","M=
ANGUIERS CHAPELLE","","08-12-2024 14:25:24","08-12-2024 09:08:55","08-12-20=
24 09:08:56","Active // No  power issue UBaie =3D53,4V site on Grid. The FM=
E TX  Armand (699949553) From Huawei is informed","Fabrice Pouakam","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active // No  power issue UBaie =3D53,4V site on Grid. The FME TX  Arm=
and (699949553) From Huawei is informed","emmanuel.ghani@ihstowers.com","18=
990","08-12-2024 14:25:24","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003790116","N=
yanon","","08-12-2024 13:57:32","08-12-2024 13:51:26","08-12-2024 14:00:43"=
,"No Power issue on site , site on Grid with Ubaie=3D55.1V The Tx Gregoire(=
654547479) from Huawei is informe","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o Power issue on site , site on Grid with Ubaie=3D55.1V The Tx Gregoire(654=
547479) from Huawei is informe","emmanuel.ghani@ihstowers.com","368","08-12=
-2024 13:57:32","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_110","NOCINC0003789635","Camp-Sonel=
","","08-12-2024 12:53:25","","","unproven alarm","Siligap Boris","Warning"=
,"Warning","POWER","Warning - Site on Battery","08-12-2024 12:52:22","joell=
e.ekessi@ihstowers.com","63","08-12-2024 12:53:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003788834","N=
kolndongo","","08-12-2024 11:39:01","08-12-2024 11:31:57","08-12-2024 12:07=
:41","Grid Outage Site went down due to Gen Card dysfunction//He reset the =
Gen Card and Manually Started","MINKA NICOLAS","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid Outage Site went down due to Gen C=
ard dysfunction//He reset the Gen Card and Manually Started","emmanuel.ghan=
i@ihstowers.com","425","08-12-2024 11:39:01","Sagemcom CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0003788772","Bit=
eng-Maetur","","08-12-2024 11:36:15","08-12-2024 11:27:05","08-12-2024 12:0=
9:41","Grid outage site went down due to Gen overload (20KVA, 270A) // He r=
educed the load on site, Power issue resolve at 12:09 PM but site remains d=
own at OCM The Tx FME  Lionel Adjep /65518487 from Huawei","Mba Lazare Herv=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage s=
ite went down due to Gen overload (20KVA, 270A) // He reduced the load on s=
ite, Power issue resolve at 12:09 PM but site remains down at OCM The Tx FM=
E  Lionel Adjep /65518487 from Huawei is informed","christian.fonkou@ihstow=
ers.com","623","08-12-2024 11:36:15","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_037","NOCINC0003788730","Nkolndongo=
","","08-12-2024 11:32:32","","","Site in alarm due to grid outage,and DG c=
ard dysfunctioning // Reset ACDG control panel and manually start of DG.","=
MINKA NICOLAS","Warning","Warning","POWER","Warning - Gen Failure","Site in=
 alarm due to grid outage,and DG card dysfunctioning // Reset ACDG control =
panel and manually start of DG.","joelle.ekessi@ihstowers.com","65","08-12-=
2024 11:32:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0003788631","Omnispor=
t-Rail","","08-12-2024 11:28:51","08-12-2024 11:22:34","08-12-2024 11:22:55=
","Cascaded Incident from TTO3736083","Delor Telezing","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue on site Uba=
ie =3D50,6V site on Grid The TX FME Synphorien  /650257151//  from huawei i=
s informed Dysjunction in the BTS OCM ","system","297496","08-12-2024 11:28=
:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0003788513","H=
-Paradis","IHS_YND_506","08-12-2024 11:27:41","08-12-2024 11:22:34","08-12-=
2024 11:22:55","Active//No power issue on site Ubaie =3D50,6V site on Grid =
The TX FME Synphorien  /650257151//  from huawei is informed Dysjunction in=
 the BTS OCM ","","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie =3D50,6V=
 site on Grid The TX FME Synphorien  /650257151//  from huawei is informed =
Dysjunction in the BTS OCM ","emmanuel.ghani@ihstowers.com","307","08-12-20=
24 11:27:41","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_028","NOCINC0003788510","H-Central"=
,"","08-12-2024 11:27:34","","","Site alarming High temp 37=B0C// temp dicr=
ease","Paul BIBOUM","Warning","Warning","ENVIRONMENT","Warning - High Tempe=
rature","Site alarming High temp 37=B0C// temp dicrease","joelle.ekessi@ihs=
towers.com","68","08-12-2024 11:27:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003787877","M=
ontee-Des-Soeurs","","08-12-2024 11:00:55","08-12-2024 10:53:43","08-12-202=
4 11:00:45","No power issue U=3D54.5 v site on grid The Tx Fme Hosiah Mbah =
(674007438) of Huawei is informed.","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue U=3D54.5 v site on grid The Tx Fme Hosiah Mbah (674007438) of Huawei i=
s informed.","emmanuel.ghani@ihstowers.com","433","08-12-2024 11:00:55","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003787284","Ole=
mbe MTN","","08-12-2024 09:34:07","08-12-2024 09:22:02","08-12-2024 09:34:5=
9","Site went down because 02/03 rectifier dysfonction // he reset the Rect=
ifier on site","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down because 02/03 rectifier dysfonction // he=
 reset the Rectifier on site","christian.fonkou@ihstowers.com","726","08-12=
-2024 09:34:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003787276","N=
kozoa","","08-12-2024 09:33:17","08-12-2024 09:29:13","08-12-2024 09:41:52"=
,"Grid outage, site went down due to gen overload(20KVA, 305A) // he reduic=
ed the load and started Gen manually","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload(20KVA, 305A) // he reduiced the load and started Gen manually"=
,"emmanuel.ghani@ihstowers.com","245","08-12-2024 09:33:17","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003787099","NYO=
M FACE MAETUR","","08-12-2024 09:17:36","08-12-2024 09:03:28","08-12-2024 1=
1:25:18","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // grid return","christian.fonkou@ihstowers.com","849","08-12-2=
024 09:17:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003786955","B=
itoto","","08-12-2024 09:06:35","08-12-2024 08:49:10","08-12-2024 11:31:11"=
,"Site went down due to PWC ""ZTE' dysfunction// he restart he and Site is =
on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Recti=
fier Module Overloaded","Site went down due to PWC ""ZTE' dysfunction// he =
restart he and Site is on Grid","emmanuel.ghani@ihstowers.com","1046","08-1=
2-2024 09:06:35","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003786926","NYO=
M 2 IHS","","08-12-2024 09:02:52","08-12-2024 08:54:43","08-12-2024 11:27:2=
0","Grid Outage Site went down because Main Gen Faulty//MDG 20Kva has deplo=
yed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Faulty","Grid Outage Site went down because Main Gen Faulty//MDG 20Kv=
a has deployed","christian.fonkou@ihstowers.com","8087","08-12-2024 09:02:5=
2","Sagemcom CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0003786744","CLE=
 Building","","08-12-2024 08:35:45","08-12-2024 08:27:37","08-12-2024 09:07=
:10","Grid Outage No Space to deploy a MDG// Grid Restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spac=
e to deploy a MDG// Grid Restored","christian.fonkou@ihstowers.com","489","=
08-12-2024 08:35:45","Sagemcom CMR"
"Closed Complete","Site Down","T0401","IHS_YND_205","NOCINC0003786726","Ton=
golo MTN","","08-12-2024 08:31:47","08-12-2024 08:25:42","08-12-2024 09:14:=
51","Grid otage site went down because Gen started and stopped due to Gen c=
ard Dysfonction // he reset the Gen card and Gen manually started","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid otage site went down because Gen started and stopped due to Gen card Dy=
sfonction // he reset the Gen card and Gen manually started","christian.fon=
kou@ihstowers.com","365","08-12-2024 08:31:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003786551","N=
kolondom","","08-12-2024 08:05:03","08-12-2024 07:54:56","08-12-2024 09:12:=
31","Grid Outage, site went down because Gen failed to start due to Gen bat=
tery discharged// He started Gen with external battery (investigation ongoi=
ng)","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Battery","Grid Outage, site went down because Gen failed to start due=
 to Gen battery discharged// He started Gen with external battery (investig=
ation ongoing)","emmanuel.ghani@ihstowers.com","608","08-12-2024 08:05:03",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003786519","HOP=
ITAL GENERAL RAIL YDE","","08-12-2024 07:58:31","08-12-2024 07:51:25","08-1=
2-2024 08:29:52","Grid outage DG fails to start// Grid return (investigatio=
n on going).","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Grid outage DG fails to start// Grid return (investigat=
ion on going).","christian.fonkou@ihstowers.com","427","08-12-2024 07:58:31=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0003786449","M=
balla 4","","08-12-2024 07:43:46","08-12-2024 07:38:28","08-12-2024 08:04:3=
7","Grid outage, site went down because gen start and stoppedwith oil press=
ure alarm // he added oil and manually started","Delor Telezing","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage, site =
went down because gen start and stoppedwith oil pressure alarm // he added =
oil and manually started","emmanuel.ghani@ihstowers.com","319","08-12-2024 =
07:43:46","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003786422","SOA=
 UNIVERSITY STADIUM","","08-12-2024 07:41:15","08-12-2024 07:34:10","08-12-=
2024 08:22:56","Grid outage, site went down because gen failed to start due=
 to dysfunctionning Hybrid system // gen manually started(investigation ong=
oing)","Siligap Boris","Equipment Repair","Passive","Hybrid","Hybrid Module=
","Grid outage, site went down because gen failed to start due to dysfuncti=
onning Hybrid system // gen manually started(investigation ongoing)","chris=
tian.fonkou@ihstowers.com","426","08-12-2024 07:41:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003786324","N=
yom OCM","","08-12-2024 07:33:04","08-12-2024 07:29:54","08-12-2024 07:43:5=
5","Site went down because Gen started and stoppad due to Grid bad voltage =
// Grid Restored","Fabrice Pouakam","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Site went down because Gen started and s=
toppad due to Grid bad voltage // Grid Restored","emmanuel.ghani@ihstowers.=
com","191","08-12-2024 07:33:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003786279","Akak-Nko=
zoa-MTN-IHS","","08-12-2024 07:28:20","08-12-2024 07:20:17","08-12-2024 07:=
46:40","","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Site went down due to Work Team  ISSOFA /677293413/ FOR EN=
KOR TECNOLOGIE  Working on site(replaced the Power cable betwen DCBOX and P=
WC)// End of work","system","269113","08-12-2024 07:28:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003786256","S=
oa-II","IHS_YND_316, IHS_YND_324","08-12-2024 07:25:25","08-12-2024 07:20:1=
7","08-12-2024 07:46:40","Site went down due to Work Team  ISSOFA /67729341=
3/ FOR ENKOR TECNOLOGIE  Working on site(replaced the Power cable betwen DC=
BOX and PWC)// End of work","Siligap Boris","Equipment Replacement","Passiv=
e","Planned Activity","Planned Activity - Passive","Site went down due to W=
ork Team  ISSOFA /677293413/ FOR ENKOR TECNOLOGIE  Working on site(replaced=
 the Power cable betwen DCBOX and PWC)// End of work","emmanuel.ghani@ihsto=
wers.com","309","08-12-2024 07:25:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003786214","M=
ANGUIERS CHAPELLE","","08-12-2024 07:17:06","08-12-2024 07:01:58","08-12-20=
24 08:01:03","Grid outage, site went down because gen start and stopped wit=
h high temp alarm // he added water and manually start the gen","Fabrice Po=
uakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Grid outage, site went down because gen start and stop=
ped with high temp alarm // he added water and manually start the gen","emm=
anuel.ghani@ihstowers.com","909","08-12-2024 07:17:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003786206","M=
IMBOMAN LIBERTE","","08-12-2024 07:15:54","08-12-2024 07:09:45","08-12-2024=
 09:13:37","Grid Outage Site went down because Main Gen Faulty//Grid Restor=
ed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Faulty","Grid Outage Site went down because Main Gen Faulty//Grid Res=
tored","emmanuel.ghani@ihstowers.com","370","08-12-2024 07:15:54","Sagemcom=
 CMR"
"Closed Complete","Warning","","IHS_YND_333","NOCINC0003786184","Mfou MTN",=
"","08-12-2024 07:11:56","","","Grid fluctuation, site went alarm because g=
en fails to start due to grid bad voltage // he bypass grid and manually st=
art the gen","Mba Lazare Herve","Warning","Warning","POWER","Warning - Site=
 on Battery","Grid fluctuation, site went alarm because gen fails to start =
due to grid bad voltage // he bypass grid and manually start the gen","joel=
le.ekessi@ihstowers.com","65","08-12-2024 07:11:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003786146","T=
ongolo OCM","","08-12-2024 07:07:38","08-12-2024 07:00:33","08-12-2024 09:0=
7:49","Grid outage, site went down before gen start due to poor batteries b=
ackup // gen start automatically and Power reset done ","Delor Telezing","E=
quipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","G=
rid outage, site went down before gen start due to poor batteries backup //=
 gen start automatically and Power reset done ","emmanuel.ghani@ihstowers.c=
om","426","08-12-2024 07:07:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003786137","S=
atcom","","08-12-2024 07:04:58","08-12-2024 06:57:51","08-12-2024 13:15:51"=
,"Active//No power issue on site Ubaie=3D50,8V site on Grid The tx fme Arma=
nd nguetsa(691144412) is informed","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site Ubaie=3D50,8V site on Grid The tx fme Armand nguetsa(69=
1144412) is informed","emmanuel.ghani@ihstowers.com","428","08-12-2024 07:0=
4:58","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0003785666","Eko=
mbitie","","08-12-2024 05:39:28","08-12-2024 05:35:14","08-12-2024 06:24:26=
","Grid outage,Gen Ran till fuel shortage//Refueling done","Fabrice Pouakam=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,Gen Ran til=
l fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.com","554","0=
8-12-2024 05:39:28","Sagemcom CMR"
"Cancelled","Warning","CTR_696","IHS_YND_713","NOCINC0003785563","NKONGKARA=
K","","08-12-2024 05:01:27","","","Grid outage, site went down because gen =
fails to start due to fuse of gen card faulty // he did a bridge with anoth=
er fuse: site on gen","TIENTCHEU NZETCHIEU GAEL","","","","","","olivier.kw=
edi@ihstowers.com","17","08-12-2024 05:01:27","Sagemcom CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0003784929","NKO=
NGKARAK","","08-12-2024 01:28:38","08-12-2024 01:22:11","08-12-2024 03:07:2=
4","grid outage,gen failed to start due to fuse of gen card faulty//he did =
a bridge and restarted the Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","grid outage,gen failed to s=
tart due to fuse of gen card faulty//he did a bridge and restarted the Gen"=
,"ludivine.ngamaleu@ihstowers.com","15587","08-12-2024 01:28:38","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003784729","A=
WAE OCM","","08-12-2024 00:43:38","08-12-2024 00:37:26","08-12-2024 03:40:4=
6","Site went down due to work: Ronique 695934760/OPUS working on site (SWA=
PP PWC )//end off work  Site Up at OCM 03.40AM   but Site still down at MTN=
 after the power reset done The RM TX Martial/69008704","Mba Lazare Herve",=
"Equipment Replacement","Passive","Planned Activity","Planned Activity - Pa=
ssive","Site went down due to work: Ronique 695934760/OPUS working on site =
(SWAPP PWC )//end off work  Site Up at OCM 03.40AM   but Site still down at=
 MTN after the power reset done The RM TX Martial/690087047/ From Huawei is=
 informed","olivier.kwedi@ihstowers.com","373","08-12-2024 00:43:38","Sagem=
com CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003784550","NYO=
M FACE MAETUR","","07-12-2024 23:57:30","07-12-2024 23:56:25","08-12-2024 0=
0:46:45","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // grid return","ludivine.ngamaleu@ihstowers.com","66","07-12-2=
024 23:57:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003784135","MEHANDAN=
","","07-12-2024 22:21:41","07-12-2024 21:59:17","07-12-2024 23:30:17","Cas=
caded Incident from TTO3730850","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage,gen failed to start due to=
 battery Ge discharged//he started the gen with battery backup","system","2=
88269","07-12-2024 22:21:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003784129","O=
dza II OCM","IHS_YND_528","07-12-2024 22:20:23","07-12-2024 21:59:17","07-1=
2-2024 23:30:17","grid outage,gen failed to start due to battery Ge dischar=
ged//he started the gen with battery backup","Albran Byorel","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Charging Alternator","grid outage,gen fai=
led to start due to battery Ge discharged//he started the gen with battery =
backup","alexandre.kamal@ihstowers.com","1267","07-12-2024 22:20:23","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003783934","O=
lembe-Terminus","","07-12-2024 21:54:56","07-12-2024 21:41:52","08-12-2024 =
01:16:13","No power issue on site U=3D53v site on grid tx fme Synphomrien o=
f huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D53v site on grid tx fme Synphomrien of huawei is informed","alexandre.k=
amal@ihstowers.com","785","07-12-2024 21:54:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003783639","M=
ontee-Jouvence-II","","07-12-2024 21:13:32","07-12-2024 21:06:27","07-12-20=
24 21:53:37","Site went down due to PWC overload ( 12 kw, 230 A)// site sta=
bilized","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifi=
er Module Overloaded","Site went down due to PWC overload ( 12 kw, 230 A)//=
 site stabilized","alexandre.kamal@ihstowers.com","427","07-12-2024 21:13:3=
2","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003783507","Messassi=
 okolo","","07-12-2024 20:51:01","07-12-2024 20:39:44","07-12-2024 21:23:51=
","Cascaded Incident from TTO3730091","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid putage,gen failed to star=
t due to card Ge disfunctionning//Gen manually started","system","278700","=
07-12-2024 20:51:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003783508","Emana ly=
cee 2","","07-12-2024 20:51:01","07-12-2024 20:39:44","07-12-2024 21:23:51"=
,"Cascaded Incident from TTO3730091","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid putage,gen failed to start=
 due to card Ge disfunctionning//Gen manually started","system","278699","0=
7-12-2024 20:51:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003783506","Emana Ly=
cee","","07-12-2024 20:51:00","07-12-2024 20:39:44","07-12-2024 21:23:51","=
Cascaded Incident from TTO3730091","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid putage,gen failed to start d=
ue to card Ge disfunctionning//Gen manually started","system","278699","07-=
12-2024 20:51:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003783505","EMANA BI=
LICK CITY","","07-12-2024 20:51:00","07-12-2024 20:39:44","07-12-2024 21:23=
:51","Cascaded Incident from TTO3730091","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid putage,gen failed to s=
tart due to card Ge disfunctionning//Gen manually started","system","278699=
","07-12-2024 20:51:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003783504","Mballa 4=
","","07-12-2024 20:51:00","07-12-2024 20:39:44","07-12-2024 21:23:51","Cas=
caded Incident from TTO3730091","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid putage,gen failed to start due t=
o card Ge disfunctionning//Gen manually started","system","278700","07-12-2=
024 20:51:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003783494","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","07=
-12-2024 20:48:48","07-12-2024 20:39:44","07-12-2024 21:23:51","grid putage=
,gen failed to start due to card Ge disfunctionning//he reset it and Gen ma=
nually started","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","grid putage,gen failed to start due to card Ge disfu=
nctionning//he reset it and Gen manually started","alexandre.kamal@ihstower=
s.com","545","07-12-2024 20:48:48","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003783471","Nko=
abang Ebolmedjock","","07-12-2024 20:45:38","07-12-2024 20:10:25","07-12-20=
24 21:40:25","Site went down because CB (63A) in DC BOX// CB put back on","=
Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Circuit Breaker Issue","Site went down because CB (63A) in DC BOX// CB=
 put back on","kamga.virgile@ihstowers.com","2114","07-12-2024 20:45:38","S=
agemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0003783411","Beh=
ind P T school Yde","","07-12-2024 20:37:06","07-12-2024 19:58:46","08-12-2=
024 00:44:46","No power issue on site U=3D52v site on grid hosiah of huawei=
 is informed","Paul BIBOUM","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","...","kamga.virgile@ihstowers.com",=
"2301","07-12-2024 20:37:06","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003783223","Ema=
na","","07-12-2024 20:15:01","07-12-2024 19:47:23","07-12-2024 22:19:36","g=
rid outage,gen failed to start due to card Ge disfunctionning//he reset it =
and Gen manually started","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","grid outage,gen failed to start due to car=
d Ge disfunctionning//he reset it and Gen manually started","kamga.virgile@=
ihstowers.com","1659","07-12-2024 20:15:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003783156","H=
-General-Yde","","07-12-2024 20:04:03","07-12-2024 19:54:59","07-12-2024 21=
:10:59","Site went down because 1/4 rectifier went faulty due to Grid bad v=
oltage// He replaced rectifier faulty","Siligap Boris","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down because 1/4 rectifi=
er went faulty due to Grid bad voltage// He replaced rectifier faulty","ale=
xandre.kamal@ihstowers.com","545","07-12-2024 20:04:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_801","NOCINC0003783122","HOPITAL =
GENERAL RAIL YDE","","07-12-2024 19:59:00","07-12-2024 19:33:54","07-12-202=
4 21:27:54","Cascaded Incident from TTO3729653","Delor Telezing","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Site went down becaus=
e 1/3 rectifier went faulty due to Grid bad voltage// He removed rectifier =
faulty","system","296780","07-12-2024 19:59:00","Sagemcom CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0003783112","Pha=
rmacie Bleue","IHS_YND_801","07-12-2024 19:56:21","07-12-2024 19:33:54","07=
-12-2024 21:27:54","Site went down because 1/3 rectifier went faulty due to=
 Grid bad voltage// He removed rectifier faulty","Siligap Boris","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","Site went down because 1=
/3 rectifier went faulty due to Grid bad voltage// He removed rectifier fau=
lty","kamga.virgile@ihstowers.com","1348","07-12-2024 19:56:21","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003782983","Nkolo II=
 New","","07-12-2024 19:36:30","07-12-2024 15:46:16","07-12-2024 17:27:28",=
"Cascaded Incident from TTO3727657","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen failed to start due to Cable disconnected // He reconnected and Gri=
d power return","system","274801","07-12-2024 19:36:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0003782695","E=
vodoula OCM","","07-12-2024 18:40:03","07-12-2024 18:34:57","07-12-2024 19:=
31:23","Grid Outage, site went down because Gen stopped with ""high temp"" =
alarm due to accordion faulty// He added water and started Gen manualy","TI=
ENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Hig=
h Engine Temp - Coolant Level Issue","Grid Outage, site went down because G=
en stopped with ""high temp"" alarm due to accordion faulty// He added wate=
r and started Gen manualy","alexandre.kamal@ihstowers.com","307","07-12-202=
4 18:40:03","Sagemcom CMR"
"Closed Complete","Warning","CTR_201","IHS_YND_368","NOCINC0003782043","Ote=
le","","07-12-2024 17:05:51","","","Grid outage, Site alarming on battery b=
ecause Gen failed to start due to Hybrid system malfunction//Gen manually s=
tarted","Fanda Brice","Warning","Warning","POWER","Warning - Site on Batter=
y","Grid outage, Site alarming on battery because Gen failed to start due t=
o Hybrid system malfunction//Gen manually started","dorothy.djantio@ihstowe=
rs.com","309","07-12-2024 17:05:51","Sagemcom CMR"
"Cancelled","Warning","T1559","IHS_YND_709","NOCINC0003781707","Nkolo II Ne=
w","","07-12-2024 16:37:13","","","","Mba Lazare Herve","","","","","","kam=
ga.virgile@ihstowers.com","2113","07-12-2024 16:37:13","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003781442","Mim=
boman4","IHS_YND_709","07-12-2024 15:58:24","07-12-2024 15:46:16","07-12-20=
24 17:27:28","Grid outage site went down because Gen failed to start due to=
 Cable disconnected // He reconnected and Grid power return","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage site went down because Gen failed to start due to Cable disconnected =
// He reconnected and Grid power return","kamga.virgile@ihstowers.com","729=
","07-12-2024 15:58:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0003781369","M=
bedoumou - Ekali","","07-12-2024 15:50:06","07-12-2024 14:30:56","08-12-202=
4 01:19:02","No power issue site on Gen with U=3D53,4v Lionne Steeve/655184=
876 from Huawei is informed","Albran Byorel","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on Gen with U=3D53,4v Lionne Steeve/655184876 from Huawei is informed","a=
lexandre.kamal@ihstowers.com","4751","07-12-2024 15:50:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003781354","N=
koabang2","","07-12-2024 15:47:35","07-12-2024 15:41:31","07-12-2024 16:11:=
58","Grid outage site went down because Gen over load(22KVA, 310A) // Grid =
power return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage site went down because Gen over load(22KVA, 31=
0A) // Grid power return","alexandre.kamal@ihstowers.com","365","07-12-2024=
 15:47:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003781268","M=
IMBOMAN LIBERTE","","07-12-2024 15:41:11","07-12-2024 15:15:07","07-12-2024=
 15:50:41","Grid Outage Site went down due to Main Gen Faulty// Grid Restor=
ed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Faulty","Grid Outage Site went down due to Main Gen Faulty// Grid Res=
tored","alexandre.kamal@ihstowers.com","1565","07-12-2024 15:41:11","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0003781107","Barriere=
 IHS","","07-12-2024 15:24:51","07-12-2024 14:49:41","07-12-2024 16:41:47",=
"Cascaded Incident from TTO3727246","Hyemafo Gildas","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because 2(CB) batt=
ery disjuncted due to short-circuit of 1/5 slot // He isolated Slot faulty =
and CB battery put back on","system","278177","07-12-2024 15:24:51","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_537","NOCINC0003781106","MEFOU AS=
SI","","07-12-2024 15:24:50","07-12-2024 14:49:41","07-12-2024 16:41:47","C=
ascaded Incident from TTO3727246","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because 2(CB) battery d=
isjuncted due to short-circuit of 1/5 slot // He isolated Slot faulty and C=
B battery put back on","system","278177","07-12-2024 15:24:50","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003781100","M=
efou-Assi","IHS_YND_537, IHS_YND_696","07-12-2024 15:23:49","07-12-2024 14:=
49:41","07-12-2024 16:41:47","Site went down because 2(CB) battery disjunct=
ed due to short-circuit of 1/5 slot // He isolated Slot faulty and CB batte=
ry put back on","Fanda Brice","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Circuit Breaker Issue","Site went down because 2(CB) batte=
ry disjuncted due to short-circuit of 1/5 slot // He isolated Slot faulty a=
nd CB battery put back on","alexandre.kamal@ihstowers.com","2049","07-12-20=
24 15:23:49","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003781089","AWA=
E OCM","","07-12-2024 15:20:51","07-12-2024 14:58:37","07-12-2024 17:46:17"=
,"Site went down due to work: Ronique 695934760/OPUS working on site (SWAPP=
 GEN )// End of work","Mba Lazare Herve","Equipment Replacement","Passive",=
"Planned Activity","Planned Activity - Passive","Site went down due to work=
: Ronique 695934760/OPUS working on site (SWAPP GEN )// End of work","kamga=
.virgile@ihstowers.com","1335","07-12-2024 15:20:51","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003780620","Nom=
ayos montee Meche","","07-12-2024 13:58:24","07-12-2024 13:47:13","08-12-20=
24 00:01:31","No power issue on site , Ubaie=3D53 V site On Grid The Tx FME=
 Georges 697461814 from Huawei is informed","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site , Ubaie=3D53 V site On Grid The Tx FME Georges 697461814 =
from Huawei is informed","landry.etame@ihstowers.com","672","07-12-2024 13:=
58:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003780242","D=
amas","","07-12-2024 13:09:35","07-12-2024 12:44:26","07-12-2024 20:32:26",=
"Grid outage site went down due to Gen overload(9kva, 150Kva)//Grid return"=
,"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage site went down due to Gen overload(9kva, 150Kva)//Grid return"=
,"stephane.nkamwa@ihstowers.com","1510","07-12-2024 13:09:35","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003778844","E=
lig Edzoa","","07-12-2024 10:04:01","07-12-2024 09:54:04","07-12-2024 11:37=
:42","Grid bad voltage, site went down because Gen failed to start due to G=
en battery discharged // He started Gen with external battery","Delor Telez=
ing","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Gr=
id bad voltage, site went down because Gen failed to start due to Gen batte=
ry discharged// He started Gen with external battery","stephane.nkamwa@ihst=
owers.com","598","07-12-2024 10:04:01","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003776482","Elo=
umdem stade","","07-12-2024 00:24:21","06-12-2024 22:35:55","07-12-2024 01:=
52:09","site went down due to insufficiency of rectifiers (01)// He added 0=
1 rectifier (02 on site)","Fanda Brice","Equipment Repair","Passive","Recti=
fier","Rectifier Module","site went down due to insufficiency of rectifiers=
 (01)// He added 01 rectifier (02 on site)","rouselle.schoune@ihstowers.com=
","6507","07-12-2024 00:24:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0003775138","S=
calom","","06-12-2024 20:06:47","06-12-2024 19:29:30","06-12-2024 21:10:29"=
,"no power issue, site is on grid with Ubaie=3D53v,Hosiah(699699694) from H=
uawei is informed","Paul BIBOUM","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","no power issue, site is on gri=
d with Ubaie=3D53v,Hosiah(699699694) from Huawei is informed","etienne.iton=
do@ihstowers.com","2238","06-12-2024 20:06:47","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003775086","Elo=
umdem stade","","06-12-2024 19:57:44","06-12-2024 19:53:39","06-12-2024 22:=
18:46","site went down due to insufficiency of rectifiers// He added 01 rec=
tifer","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down due to insufficiency of rectifiers// He added 01 rect=
ifer","dorothy.djantio@ihstowers.com","246","06-12-2024 19:57:44","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003775084","E=
ssomba","","06-12-2024 19:57:22","06-12-2024 18:44:12","06-12-2024 21:19:51=
","site went down due to neutral burned out in ATS // He changed cable , si=
te on grid","Mba Lazare Herve","Equipment Repair","Passive","Control Panel"=
,"ATS-AMF Issue","site went down due to neutral burned out in ATS // He cha=
nged cable , site on grid","etienne.itondo@ihstowers.com","4391","06-12-202=
4 19:57:22","Sagemcom CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0003775043","SOA=
 VILLAGE","","06-12-2024 19:46:02","06-12-2024 19:40:56","06-12-2024 20:16:=
04","site went down due to dysfunctionning of rectifiers // Reset of rectif=
iers , site on grid","Siligap Boris","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","site went down due to dysfunctionning of rectifiers =
// Reset of rectifiers , site on grid","dorothy.djantio@ihstowers.com","307=
","06-12-2024 19:46:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003774911","E=
bogo","","06-12-2024 19:26:28","06-12-2024 18:39:14","06-12-2024 19:47:34",=
"site went down because gen failed to start due grid bad voltage// :He bypa=
ssed grid, Gen manually started","Siligap Boris","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","site went down because gen =
failed to start due grid bad voltage// Gen manually started","etienne.itond=
o@ihstowers.com","2835","06-12-2024 19:26:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003774575","N=
omayos-IHS","","06-12-2024 18:37:16","06-12-2024 14:48:48","06-12-2024 19:1=
8:50","Site went down because 02/04 rectifiers dysfunction//He reset rectif=
ier,site on Grid","Fanda Brice","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down because 02/04 rectifiers dysfunction//He r=
eset rectifier,site on Grid","etienne.itondo@ihstowers.com","13709","06-12-=
2024 18:37:16","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003774033","Eko=
unou","","06-12-2024 17:18:49","06-12-2024 17:17:23","06-12-2024 17:27:59",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","do=
rothy.djantio@ihstowers.com","505","06-12-2024 17:18:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003774020","Essomba"=
,"","06-12-2024 17:16:20","06-12-2024 17:06:17","06-12-2024 17:13:46","Casc=
aded Incident from TTO3718613","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation , site Went down be=
fore Gen start due to poor backup// Grid power return","system","269995","0=
6-12-2024 17:16:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003774021","Biteng-M=
aetur","","06-12-2024 17:16:20","06-12-2024 17:06:17","06-12-2024 17:13:46"=
,"Cascaded Incident from TTO3718613","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation , site Went d=
own before Gen start due to poor backup// Grid power return","system","2699=
94","06-12-2024 17:16:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003774008","B=
iteng","IHS_YND_179, IHS_YND_249","06-12-2024 17:14:22","06-12-2024 17:06:1=
7","06-12-2024 17:13:46","Grid fluctuation , site Went down before Gen star=
t due to poor backup// Grid power return","Mba Lazare Herve","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid fluctuat=
ion , site Went down before Gen start due to poor backup// Grid power retur=
n","olivier.kwedi@ihstowers.com","486","06-12-2024 17:14:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003773594","L=
abogenie","","06-12-2024 16:08:53","06-12-2024 15:59:38","06-12-2024 16:13:=
17","grid outage, no space to deploy a mobil gen// Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, no=
 space to deploy a mobil gen// Grid return","olivier.kwedi@ihstowers.com","=
556","06-12-2024 16:08:53","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0003773234","EMA=
NA BILICK CITY","","06-12-2024 15:42:28","06-12-2024 14:34:21","07-12-2024 =
02:50:37","wrongly ticket","Fabrice Pouakam","Incorrectly Logged Tickets","=
Error","Error","Error","wrongly ticket","dorothy.djantio@ihstowers.com","40=
88","06-12-2024 15:42:28","Sagemcom CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0003772902","Biy=
emassi LAC","","06-12-2024 15:03:20","06-12-2024 14:57:07","06-12-2024 16:0=
4:26","Grid outage, no space to deploy a mobil gen, lgrid return return awa=
ited","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"=
,"grid outage, no space for a MDG//grid return","dorothy.djantio@ihstowers.=
com","493","06-12-2024 15:03:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0003772896","B=
IYEMASSI NIKI","","06-12-2024 15:02:21","06-12-2024 14:53:11","06-12-2024 1=
6:01:25","Site went down due to PWC overloaded (12kva 250 A) //Site stabili=
zed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Sit=
e stabilized","olivier.kwedi@ihstowers.com","551","06-12-2024 15:02:21","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0003772784","Mes=
sassi Ngonlonk","","06-12-2024 14:45:27","06-12-2024 14:35:59","06-12-2024 =
17:11:59","Site on gen due to grid outage, Site went down because Grid rest=
ored but the grid contactor disfunction // He blocked Grid Contactor, Site =
on Grid","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","AT=
S-AMF Issue","Site on gen due to grid outage, Site went down because Grid r=
estored but the grid contactor disfunction // He blocked Grid Contactor, Si=
te on Grid","dorothy.djantio@ihstowers.com","570","06-12-2024 14:45:27","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003772471","Nko=
lmvack","","06-12-2024 13:57:31","06-12-2024 13:39:18","06-12-2024 15:58:48=
","","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Oil Le=
akage","gen stopped due to oil leakage at the level of injectors//added 2 L=
 of oil (work ongoing to solve the issue)","kamga.virgile@ihstowers.com","1=
093","06-12-2024 13:57:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003772210","Scalom-I=
HS","","06-12-2024 13:29:01","06-12-2024 13:19:17","06-12-2024 16:00:06","C=
ascaded Incident from TTO3716505","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","grid outage, no space to deploy a mobil gen // gr=
id return","system","290707","06-12-2024 13:29:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0003772206","A=
ccacia New","IHS_YND_505","06-12-2024 13:28:29","06-12-2024 13:19:17","06-1=
2-2024 16:09:38","grid outage, no space to deploy a mobil gen // grid retur=
n","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","g=
rid outage, no space to deploy a mobil gen // grid return","alexandre.kamal=
@ihstowers.com","554","06-12-2024 13:28:29","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003771473","NYO=
M FACE MAETUR","","06-12-2024 11:36:07","06-12-2024 10:38:56","06-12-2024 1=
0:40:04","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // grid return","kamga.virgile@ihstowers.com","3432","06-12-202=
4 11:36:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003770961","N=
YOM 2 IHS","","06-12-2024 10:47:36","06-12-2024 10:36:25","06-12-2024 11:24=
:55","Grid outage with main gen faulty//Grid return","Fabrice Pouakam","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage =
with main gen faulty//Grid return","alexandre.kamal@ihstowers.com","672","0=
6-12-2024 10:47:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_736","NOCINC0003770942","CRF Nkoa=
bang","","06-12-2024 10:45:50","06-12-2024 10:32:33","06-12-2024 10:42:27",=
"Cascaded Incident from TTO3715019","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage ,site went down bec=
ause Gen started and stopped due to Gen OVERLOAD (16.KVA,150 A)//Grid retur=
n","system","300743","06-12-2024 10:45:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003770933","N=
koabang","IHS_YND_736","06-12-2024 10:44:39","06-12-2024 10:32:33","06-12-2=
024 10:42:27","Grid outage ,site went down because Gen started and stopped =
due to Gen OVERLOAD (16.KVA,150 A)//Grid return","Mba Lazare Herve","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went =
down because Gen started and stopped due to Gen OVERLOAD (16.KVA,150 A)//Gr=
id return","alexandre.kamal@ihstowers.com","727","06-12-2024 10:44:39","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0003770783","M=
bedoumou - Ekali","","06-12-2024 10:26:32","06-12-2024 10:10:27","06-12-202=
4 17:15:48","No power issue site on grid with U=3D53,4v Lionel Steeve from =
Huawei is informed.","Albran Byorel","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gri=
d with U=3D53,4v Lionne Steeve from Huawei is informed
","alexandre.kamal@ihstowers.com","966","06-12-2024 10:26:32","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003770322","E=
bogo","","06-12-2024 09:21:45","06-12-2024 09:02:17","06-12-2024 15:25:48",=
"Site went down due work made by Kameni Roberto(697010591) from Broadcom(re=
placement DC BOX)","Siligap Boris","Equipment Replacement","Passive","Plann=
ed Activity","Planned Activity - Passive","Site went down due work made by =
Kameni Roberto(697010591) from Broadcom(replacement DC BOX)","alexandre.kam=
al@ihstowers.com","1169","06-12-2024 09:21:45","Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0003770220","Yok=
o MTN","","06-12-2024 09:01:04","06-12-2024 08:48:47","06-12-2024 09:14:23"=
,"Grid outage.gen failed to start due to battery GE faulty//Gen manually st=
arted with external battery","Parker Tchoup","Equipment Repair","Passive","=
ACDG Gen","ACDG - Generator Battery","Grid outage.gen failed to start due t=
o battery GE faulty//Gen manually started with external battery","kamga.vir=
gile@ihstowers.com","738","06-12-2024 09:01:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003770009","N=
omayos-IHS","","06-12-2024 08:35:19","06-12-2024 08:23:09","06-12-2024 08:5=
8:18","Site went down because 02/04 rectifiers dysfunction//He reset rectif=
ier,site on Grid.","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down because 02/04 rectifiers dysfunction//He =
reset rectifier,site on Grid.
","alexandre.kamal@ihstowers.com","731","06-12-2024 08:35:19","Sagemcom CMR=
"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003769883","NYO=
M FACE MAETUR","","06-12-2024 08:15:48","06-12-2024 06:05:33","06-12-2024 0=
6:07:34","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // grid return","kamga.virgile@ihstowers.com","7815","06-12-202=
4 08:15:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003769161","N=
omayos-IHS","","06-12-2024 06:02:30","06-12-2024 05:57:18","06-12-2024 06:2=
1:14","Site went down because 01/04 rectifiers dysfunction//He reset rectif=
ier,site on Grid","Fanda Brice","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down because 01/04 rectifiers dysfunction//He r=
eset rectifier,site on Grid","emmanuel.ghani@ihstowers.com","313","06-12-20=
24 06:02:30","Sagemcom CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0003768867","Ese=
ka MTN","IHS_YND_378","06-12-2024 04:13:03","06-12-2024 04:05:58","06-12-20=
24 04:10:43","No power issue site on grid with U=3D54.2v Etienne(695033981)=
 from Huawei is informed","Kemeni Franklin","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on grid with U=3D54..2v Etienne(695033981) from Huawei is informed","chris=
tian.fonkou@ihstowers.com","426","06-12-2024 04:13:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003768691","Akak-Nko=
zoa-MTN-IHS","","06-12-2024 03:04:10","06-12-2024 02:59:49","06-12-2024 03:=
03:45","Cascaded Incident from TTO3712371","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage site down due=
 to poor backup // Gen started automatically","system","1219529","06-12-202=
4 03:04:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003768660","Song-bon=
g","","06-12-2024 02:56:51","06-12-2024 02:50:07","06-12-2024 02:50:08","Ca=
scaded Incident from TTO3712330","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue on site ,site o=
n Grid with Ubaie=3D54 V The TX FME Etienne(695033981) from Huawei is infor=
med","system","270598","06-12-2024 02:56:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003768659","Eseka To=
wn","","06-12-2024 02:56:51","06-12-2024 02:50:07","06-12-2024 04:10:43","C=
ascaded Incident from TTO3712330","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue on site ,site =
on Grid with Ubaie=3D54 V The TX FME Etienne(695033981) from Huawei is info=
rmed","system","404","06-12-2024 02:56:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003768647","E=
seka OCM","IHS_YND_378, IHS_YND_453","06-12-2024 02:53:36","06-12-2024 02:5=
0:07","06-12-2024 05:30:08","Active//No power issue on site ,site on Grid w=
ith Ubaie=3D54 V The TX FME Etienne(695033981) from Huawei is informed","Ke=
meni Franklin","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid wit=
h Ubaie=3D54 V The TX FME Etienne(695033981) from Huawei is informed","emma=
nuel.ghani@ihstowers.com","210","06-12-2024 02:53:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003768612","M=
arche Odza","","06-12-2024 02:40:46","06-12-2024 02:32:34","06-12-2024 05:4=
0:35","Active//No power issue on site U=3D53,5v site on grid Tx fme Lionnel=
 steeve/655184876 of huawei is informed","Albran Byorel","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site U=3D53,5v site on grid Tx fme Lionnel steeve/655184876 of =
huawei is informed","emmanuel.ghani@ihstowers.com","493","06-12-2024 02:40:=
46","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003768271","Tsi=
nga","","06-12-2024 01:19:35","06-12-2024 01:17:28","06-12-2024 01:39:32","=
Grid outage, site went down before gen start due to poor battery backup // =
Grid Restored","Mboua Thierry","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before gen star=
t due to poor battery backup // Grid Restored","christian.fonkou@ihstowers.=
com","128","06-12-2024 01:19:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003768136","M=
ambine","","06-12-2024 00:25:50","06-12-2024 00:21:42","06-12-2024 00:48:26=
","Grid outage,gen ran until fuel shortage//Refueling done","Fanda Brice","=
Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran until =
fuel shortage//Refueling done","emmanuel.ghani@ihstowers.com","249","06-12-=
2024 00:25:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0003768116","E=
mana Lycee","","06-12-2024 00:16:46","05-12-2024 21:40:30","06-12-2024 05:4=
0:18","Active//No power issue on site U=3D54,4v site on grid Tx fme SYMPHOR=
IEN of huawei is informed","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue on site U=3D54,4v site on grid Tx fme SYMPHORIEN of huawei is informed=
","emmanuel.ghani@ihstowers.com","9377","06-12-2024 00:16:46","Sagemcom CMR=
"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003767353","NYO=
M FACE MAETUR","","05-12-2024 21:32:48","05-12-2024 21:31:42","05-12-2024 2=
3:30:13","Grid Outage landlord has forbiden to start the Gen Because the No=
ise // Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Emergency Stop","Grid Outage landlord has forbiden to start th=
e Gen Because the Noise // Grid Restored","rouselle.schoune@ihstowers.com",=
"67","05-12-2024 21:32:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003767294","EMANA BI=
LICK CITY","","05-12-2024 21:24:20","05-12-2024 21:15:40","05-12-2024 21:39=
:40","Cascaded Incident from TTO3710653","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid Outage Site went down =
due to Gen Card dysfunction//He reset the Gen Card and Manually Started the=
 Gen","system","520","05-12-2024 21:24:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003767295","Emana Ly=
cee","","05-12-2024 21:24:20","05-12-2024 21:15:40","05-12-2024 21:39:40","=
Cascaded Incident from TTO3710653","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage Site went down due to=
 Gen Card dysfunction//He reset the Gen Card and Manually Started the Gen",=
"system","520","05-12-2024 21:24:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003767293","Mballa 4=
","","05-12-2024 21:24:20","05-12-2024 21:15:40","05-12-2024 21:39:40","Cas=
caded Incident from TTO3710653","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid Outage Site went down due to Gen=
 Card dysfunction//He reset the Gen Card and Manually Started the Gen","sys=
tem","269188","05-12-2024 21:24:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003767296","Messassi=
 okolo","","05-12-2024 21:24:20","05-12-2024 21:15:40","05-12-2024 21:39:40=
","Cascaded Incident from TTO3710653","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage Site went down due=
 to Gen Card dysfunction//He reset the Gen Card and Manually Started the Ge=
n","system","520","05-12-2024 21:24:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003767276","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279","05-12-2024 21:2=
1:57","05-12-2024 21:15:40","05-12-2024 21:39:40","Grid Outage Site went do=
wn due to Gen Card dysfunction//He reset the Gen Card and Manually Started =
the Gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid Outage Site went down due to Gen Card dysfunction//He =
reset the Gen Card and Manually Started the Gen","denis.mballa@ihstowers.co=
m","377","05-12-2024 21:21:57","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003767231","Ema=
na","","05-12-2024 21:16:08","05-12-2024 21:14:01","05-12-2024 22:26:43","G=
rid Outage Site went down due to Gen Card dysfunction//He reset the Gen Car=
d and Manually Started","Fabrice Pouakam","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid Outage Site went down due to Gen Card d=
ysfunction//He reset the Gen Card and Manually Started","rouselle.schoune@i=
hstowers.com","128","05-12-2024 21:16:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003767094","MEHANDAN=
","","05-12-2024 20:56:40","05-12-2024 20:49:30","05-12-2024 22:08:36","Cas=
caded Incident from TTO3710416","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid bad voltage, site went down becau=
se Gen failed to start due to Gen battery discharged// He started Gen with =
external battery (investigation ongoing)","system","270927","05-12-2024 20:=
56:40","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003767092","MIM=
BOMAN LIBERTE","","05-12-2024 20:56:36","05-12-2024 20:49:31","05-12-2024 2=
2:45:47","Grid Outage Site went down due to Main Gen Faulty// Grid Restored=
","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid Outage Site went down due to Main Gen Faulty// Grid Resto=
red","rouselle.schoune@ihstowers.com","426","05-12-2024 20:56:36","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003767086","O=
dza II OCM","IHS_YND_528","05-12-2024 20:55:41","05-12-2024 20:49:30","05-1=
2-2024 22:08:36","Grid bad voltage, site went down because Gen failed to st=
art due to Gen battery discharged// He started Gen with external battery (i=
nvestigation ongoing)","Albran Byorel","Equipment Repair","Passive","ACDG G=
en","ACDG - Generator Battery","Grid bad voltage, site went down because Ge=
n failed to start due to Gen battery discharged// He started Gen with exter=
nal battery (investigation ongoing)","denis.mballa@ihstowers.com","372","05=
-12-2024 20:55:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0003767038","Nkoabang=
2","","05-12-2024 20:45:31","05-12-2024 20:41:02","05-12-2024 20:46:02","Ca=
scaded Incident from TTO3710346","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 Gen overload (16.5kva, 185A)// Grid power return","system","269","05-12-20=
24 20:45:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_736","NOCINC0003767039","CRF Nkoa=
bang","","05-12-2024 20:45:31","05-12-2024 20:41:02","05-12-2024 20:46:02",=
"Cascaded Incident from TTO3710346","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down due=
 to Gen overload (16.5kva, 185A)// Grid power return","system","269","05-12=
-2024 20:45:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003767030","N=
koabang","IHS_YND_526, IHS_YND_736","05-12-2024 20:44:15","05-12-2024 20:41=
:02","05-12-2024 20:46:02","Grid outage, Site went down due to Gen overload=
 (16.5kva, 185A)// Grid power return","Mba Lazare Herve","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, Site went down due to=
 Gen overload (16.5kva, 185A)// Grid power return","denis.mballa@ihstowers.=
com","194","05-12-2024 20:44:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003767017","M=
efou-Assi","","05-12-2024 20:41:59","05-12-2024 20:40:58","05-12-2024 21:02=
:58","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage // he bypass grid and manually start the gen","Fanda Bric=
e","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, site went down because gen start and stopped due to gri=
d bad voltage // he bypass grid and manually start the gen","denis.mballa@i=
hstowers.com","62","05-12-2024 20:41:59","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003766602","SOA=
 UNIVERSITY STADIUM","","05-12-2024 19:39:46","05-12-2024 19:37:41","05-12-=
2024 20:43:53","Grid outage, site went down because gen fails to start due =
to battery ge discharged // gen start with batterie backup","Siligap Boris"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid o=
utage, site went down because gen fails to start due to battery ge discharg=
ed // gen start with batterie backup","rouselle.schoune@ihstowers.com","126=
","05-12-2024 19:39:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0003766577","S=
imbock OCM","","05-12-2024 19:33:57","05-12-2024 19:25:45","05-12-2024 21:3=
6:45","No power issue U=3D54V site on grid The Tx Fme Hosiah Mbah (67400743=
8) of Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=3D5=
4V site on grid The Tx Fme Hosiah Mbah (674007438) of Huawei is informed","=
denis.mballa@ihstowers.com","493","05-12-2024 19:33:57","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003766549","Ebo=
go","","05-12-2024 19:27:20","05-12-2024 19:21:09","05-12-2024 20:01:09","S=
ite went down due work made by Kameni Roberto(697010591) from Broadcom(repl=
acement of DC BOX) // End of work","Siligap Boris","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Site went down due wo=
rk made by Kameni Roberto(697010591) from Broadcom(replacement of DC BOX) /=
/ End of work","rouselle.schoune@ihstowers.com","372","05-12-2024 19:27:20"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003765665","E=
bogo","","05-12-2024 16:57:51","05-12-2024 16:53:32","05-12-2024 16:58:32",=
"Grid outage, site went down before gen start due to poor batteries backup =
// gen start automaically","Siligap Boris","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor batteries backup // gen start automaically","deni=
s.mballa@ihstowers.com","260","05-12-2024 16:57:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0003765633","A=
FEME NORD","","05-12-2024 16:54:46","05-12-2024 16:46:33","05-12-2024 17:20=
:33","Site went down due to work FRANCK/655217253/ FROM OPUS is working on =
site (SWAP DC box orange) // End of work","TIENTCHEU NZETCHIEU GAEL","Insta=
llation Activity","Passive","Planned Activity","Installation Activity","Sit=
e went down due to work FRANCK/655217253/ FROM OPUS is working on site (SWA=
P DC box orange) // End of work","denis.mballa@ihstowers.com","494","05-12-=
2024 16:54:46","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003765380","Nom=
ayos montee Meche","","05-12-2024 16:05:55","05-12-2024 16:03:50","05-12-20=
24 16:37:50","Grid outage, site went down because the bay DPC disfunctionni=
ng//He blocked the PWC DPC, Site on Grid","Fanda Brice","Equipment Repair",=
"Passive","Control Panel","Panel Distribution Board","Grid outage, site wen=
t down because the bay DPC disfunctionning//He blocked the PWC DPC, Site on=
 Grid","rouselle.schoune@ihstowers.com","126","05-12-2024 16:05:55","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0003765212","M=
bedoumou - Ekali","","05-12-2024 15:47:45","05-12-2024 15:39:32","05-12-202=
4 17:50:32","No  power Ubaie=3D53,4V site on Gen TX FME Rodrigue (655102999=
)from Huawei is informed","Albran Byorel","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No  power Ubaie=3D53,=
4V site on Gen TX FME Rodrigue (655102999)from Huawei is informed","denis.m=
balla@ihstowers.com","494","05-12-2024 15:47:45","Sagemcom CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0003764912","Mes=
sassi Ngonlonk","","05-12-2024 14:58:11","05-12-2024 14:56:08","05-12-2024 =
16:06:08","Site on gen due to grid outage, Site went down because Grid rest=
ored but the grid contactor disfunction // He blocked Grid Contactor, Site =
on Grid","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","AT=
S-AMF Issue","Site on gen due to grid outage, Site went down because Grid r=
estored but the grid contactor disfunction // He blocked Grid Contactor, Si=
te on Grid","rouselle.schoune@ihstowers.com","124","05-12-2024 14:58:11","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003764830","Akak-Nko=
zoa-MTN-IHS","","05-12-2024 14:41:30","05-12-2024 14:25:26","05-12-2024 15:=
30:26","Cascaded Incident from TTO3707626","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down BECAUSE CB=
(125A) Disjuncted in PWC // CB put back on","system","279580","05-12-2024 1=
4:41:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003764818","S=
oa-II","IHS_YND_316, IHS_YND_324","05-12-2024 14:39:38","05-12-2024 14:25:2=
6","05-12-2024 15:30:26","Site went down BECAUSE CB(125A) Disjuncted in PWC=
 // CB put back on","Siligap Boris","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Circuit Breaker Issue","Site went down BECAUSE CB(12=
5A) Disjuncted in PWC // CB put back on","denis.mballa@ihstowers.com","852"=
,"05-12-2024 14:39:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003764251","N=
yom OCM","","05-12-2024 13:17:26","05-12-2024 13:09:15","05-12-2024 13:49:3=
0","Site was on Gen due to Grid outage, site went down because Gen stopped =
due to High temp// He added water and started Gen manualy","Fabrice Pouakam=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Site was on Gen due to Grid outage, site went down because =
Gen stopped due to High temp// He added water and started Gen manualy","oli=
vier.kwedi@ihstowers.com","493","05-12-2024 13:17:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0003764166","M=
bedoumou - Ekali","","05-12-2024 13:05:06","05-12-2024 12:55:50","05-12-202=
4 13:00:49","Active: No pwer issue, site is on Gen with Ubaie=3D53V, Rodrig=
ue(655102999) from Huawei is informed","Albran Byorel","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No pwer issue, site is on Gen with Ubaie=3D53V, Rodrigue(655102999) from Hu=
awei is informed","olivier.kwedi@ihstowers.com","557","05-12-2024 13:05:06"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003763896","S=
tade-Abega","","05-12-2024 12:33:33","05-12-2024 10:27:24","05-12-2024 12:3=
5:52","No pwer issus, site is on grid with Ubaie=3D53V, Lionel adjep(655184=
876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pwer issus,=
 site is on grid with Ubaie=3D53V, Lionel adjep(655184876) from Huawei is i=
nformed","olivier.kwedi@ihstowers.com","7570","05-12-2024 12:33:33","Sagemc=
om CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003763771","Sap=
eur","","05-12-2024 12:17:21","05-12-2024 11:56:05","05-12-2024 12:16:34","=
Grid fluctuation, site went down before gen start due to poor battery backu=
p // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid fluctuation, site went down before =
gen start due to poor battery backup // Grid return","etienne.itondo@ihstow=
ers.com","1277","05-12-2024 12:17:21","Sagemcom CMR"
"Closed Complete","Site Down","T0526","IHS_YND_088","NOCINC0003763627","Elo=
bi Mokolo","","05-12-2024 11:54:48","05-12-2024 11:45:44","05-12-2024 12:35=
:09","Grid outage, site went down because Gen failed to start due to hybrid=
 system dysfonction // He bypassed Hybrid  system and gen manually started"=
,"Mboua Thierry","Equipment Repair","Passive","Hybrid","Hybrid Module","Gri=
d outage, site went down because Gen failed to start due to hybrid system d=
ysfonction // He bypassed Hybrid  system and gen manually started","dorothy=
.djantio@ihstowers.com","545","05-12-2024 11:54:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003763295","MBIMBIM"=
,"","05-12-2024 11:22:31","05-12-2024 11:08:23","05-12-2024 11:10:30","Casc=
aded Incident from TTO3705730","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
54V Hybrid gen site with threshold =3D 47.5V). TX FME WILLY 650254398of Hua=
wei is informed","system","269774","05-12-2024 11:22:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003763294","Ngouetou=
","","05-12-2024 11:22:30","05-12-2024 11:08:23","05-12-2024 11:10:30","Cas=
caded Incident from TTO3705730","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 54V Hybrid gen site with threshold =3D 47.5V). TX FME WILLY 650254398of Hu=
awei is informed","system","269773","05-12-2024 11:22:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003763293","Matsari"=
,"","05-12-2024 11:22:30","05-12-2024 11:08:23","05-12-2024 11:10:30","Casc=
aded Incident from TTO3705730","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
54V Hybrid gen site with threshold =3D 47.5V). TX FME WILLY 650254398of Hua=
wei is informed","system","269773","05-12-2024 11:22:30","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003762825","Sap=
eur","","05-12-2024 10:53:32","05-12-2024 10:49:24","05-12-2024 11:21:33","=
Grid fluctuation, site went down before gen start due to poor battery backu=
p // Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid fluctuation, site went down before =
gen start due to poor battery backup // Grid return","dorothy.djantio@ihsto=
wers.com","249","05-12-2024 10:53:32","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_460","NOCINC0003762399","Matsari","=
","05-12-2024 10:04:21","","","Alarm not proven,site on DG,Ubaie:54.2V; ","=
Parker Tchoup","Warning","Warning","SYSTEM","Warning - False Alarm","Alarm =
not proven,site on DG,Ubaie:54.2V; ","system","1511","05-12-2024 10:04:21",=
"Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_456","NOCINC0003762401","MBIMBIM","=
","05-12-2024 10:04:21","","","Alarm not proven,site on DG,Ubaie:54.4V;","P=
arker Tchoup","Warning","Warning","SYSTEM","Warning - Controler Time","Alar=
m not proven,site on DG,Ubaie:54.4V;","system","1511","05-12-2024 10:04:21"=
,"Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_454","NOCINC0003762400","Ngouetou","","05=
-12-2024 10:04:21","","","Cascaded Incident from TTO3704767","Parker Tchoup=
","","","","","","system","1511","05-12-2024 10:04:21","Sagemcom CMR"
"Cancelled","Warning","CTR_335","IHS_YND_474","NOCINC0003762369","Yoko OCM"=
,"IHS_YND_460, IHS_YND_454, IHS_YND_456, IHS_YND_476","05-12-2024 09:59:44"=
,"","","","Parker Tchoup","","","","","","olivier.kwedi@ihstowers.com","123=
4","05-12-2024 09:59:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003761950","Yoko MTN=
","IHS_YND_475","05-12-2024 09:04:00","05-12-2024 08:47:10","05-12-2024 09:=
46:15","grid outage, site went down because gen failed to start due to Oil =
sensor faulty // He bypassed  oil sensor, site on gen","Parker Tchoup","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Oil Pressure Sensor Faulty","gr=
id outage, site went down because gen failed to start due to Oil pressure s=
ensor faulty // He bypassed  oil sensor, site on gen","system","1010","05-1=
2-2024 09:04:00","Sagemcom CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0003761947","Ngo=
um","","05-12-2024 09:03:28","05-12-2024 08:47:10","05-12-2024 09:46:15",""=
,"Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","grid outage, site went down because gen failed to start due to Oil pr=
essure sensor faulty // He bypassed  oil sensor, site on gen","ludivine.nga=
maleu@ihstowers.com","277979","05-12-2024 09:03:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0003761793","S=
AA 2","","05-12-2024 08:39:04","05-12-2024 08:36:57","05-12-2024 09:41:18",=
"No power issue site on grid with U=3D54,8v Gregoire(654547479) from Huawei=
 is working on site","Parker Tchoup","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gri=
d with U=3D54,8v Gregoire(654547479) from Huawei is working on site","olivi=
er.kwedi@ihstowers.com","128","05-12-2024 08:39:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003761684","E=
bogo","","05-12-2024 08:17:46","05-12-2024 08:16:18","05-12-2024 08:54:31",=
"Site went down due work made by Kameni Roberto(697010591) from Broadcom(re=
placement DC BOX)//End of work","Siligap Boris","Equipment Replacement","Pa=
ssive","Planned Activity","Planned Activity - Passive","Site went down due =
work made by Kameni Roberto(697010591) from Broadcom(replacement DC BOX)//E=
nd of work","olivier.kwedi@ihstowers.com","246","05-12-2024 08:17:46","Sage=
mcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003761437","NYO=
M FACE MAETUR","","05-12-2024 07:32:11","05-12-2024 07:30:00","05-12-2024 0=
7:32:51","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // grid return","dorothy.djantio@ihstowers.com","131","05-12-20=
24 07:32:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0003760555","Bondjock=
","","05-12-2024 04:09:01","05-12-2024 03:40:17","05-12-2024 04:14:39","Cas=
caded Incident from TTO3702495","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage,gen ran until fuel shortage/=
/Refueling done","system","267686","05-12-2024 04:09:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0003760552","Mbeng","=
","05-12-2024 04:09:00","05-12-2024 03:40:17","05-12-2024 04:14:39","Cascad=
ed Incident from TTO3702495","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage,gen ran until fuel shortage//Re=
fueling done","system","267687","05-12-2024 04:09:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0003760553","Minka","=
","05-12-2024 04:09:00","05-12-2024 03:40:17","05-12-2024 04:14:39","Cascad=
ed Incident from TTO3702495","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage,gen ran until fuel shortage//Re=
fueling done","system","267686","05-12-2024 04:09:00","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0003760466","Mom=
","IHS_YND_369, IHS_YND_371, IHS_YND_553, IHS_YND_372","05-12-2024 03:50:24=
","05-12-2024 03:40:17","05-12-2024 04:14:39","Grid outage,gen ran until fu=
el shortage//Refueling done","Fanda Brice","Fuel Outage","Passive","Diesel"=
,"Diesel Outage","Grid outage,gen ran until fuel shortage//Refueling done",=
"landry.etame@ihstowers.com","696","05-12-2024 03:50:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0003759330","SAA 2","=
","04-12-2024 22:37:52","04-12-2024 22:21:07","04-12-2024 22:27:47","Cascad=
ed Incident from TTO3701118","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down because Gen Oe=
rload(20kva; 250A) // He reduced the power limitation on site","system","27=
9644","04-12-2024 22:37:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003759238","H=
-Progres","","04-12-2024 22:21:31","04-12-2024 21:59:21","04-12-2024 22:41:=
20","Grid outage,no space to deploy mobile gen // grid powerReturn","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
,no space to deploy mobile gen // grid powerReturn","emmanuel.ghani@ihstowe=
rs.com","1331","04-12-2024 22:21:31","Sagemcom CMR"
"Closed Complete","Site Down","T1577","IHS_YND_086","NOCINC0003759146","POL=
YCLINIQUE TSINGA","","04-12-2024 22:02:55","04-12-2024 21:53:46","04-12-202=
4 22:13:38","Grid outage DG fails to start// Grid return (investigation on =
going)","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","Grid outage DG fails to start// Grid return (investigation on =
going)","christian.fonkou@ihstowers.com","549","04-12-2024 22:02:55","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003758954","M=
vog-Manga","","04-12-2024 21:44:52","04-12-2024 21:42:40","04-12-2024 21:57=
:26","Site went down due to insufficient of rectifiers (06) due to load inc=
rease// Site stabilized","Albran Byorel","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Site went down due to insufficient of rectifiers=
 (06) due to load increase// Site stabilized","emmanuel.ghani@ihstowers.com=
","134","04-12-2024 21:44:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003758924","B=
ATA-Mokolo","","04-12-2024 21:37:37","04-12-2024 21:27:16","04-12-2024 22:4=
1:41","Grid outage,no space to deploy mobile gen // grid powerReturn","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge,no space to deploy mobile gen // grid powerReturn","emmanuel.ghani@ihsto=
wers.com","622","04-12-2024 21:37:37","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003758352","Nko=
abang Ebolmedjock","","04-12-2024 20:13:08","04-12-2024 20:06:59","04-12-20=
24 20:10:48","ACTIVE No power issue Gen only site U=3D54V The Tx fme  Lione=
l Adjep /655184876 from huawei is informed. R=E9p=E9titif issue","Mba Lazar=
e Herve","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","ACTIVE No power issue Gen only site U=3D54V The Tx fme=
  Lionel Adjep /655184876 from huawei is informed. R=E9p=E9titif issue","ch=
ristian.fonkou@ihstowers.com","370","04-12-2024 20:13:08","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_217","NOCINC0003758347","Abom","","=
04-12-2024 20:11:07","","","site on alarm due to grid outage//gen started",=
"Siligap Boris","Warning","Warning","POWER","Warning - Site on Battery","si=
te on alarm due to grid outage//gen started","joelle.ekessi@ihstowers.com",=
"65","04-12-2024 20:11:07","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003758082","Elo=
umdem stade","","04-12-2024 19:31:48","04-12-2024 19:24:40","04-12-2024 20:=
23:43","site went down due to 01/02 rectifiers faulty // He changed 01 rect=
ifiers, site on grid","Fanda Brice","Equipment Repair","Passive","Rectifier=
","Rectifier Module","site went down due to 01/02 rectifiers faulty // He c=
hanged 01 rectifiers, site on grid","christian.fonkou@ihstowers.com","429",=
"04-12-2024 19:31:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003758063","Donga","=
","04-12-2024 19:28:32","04-12-2024 19:03:49","04-12-2024 19:33:11","Cascad=
ed Incident from TTO3699599","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site impacted by Mbadjock camrail","syste=
m","269874","04-12-2024 19:28:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003758064","Dong",""=
,"04-12-2024 19:28:32","04-12-2024 19:03:49","04-12-2024 19:33:11","Cascade=
d Incident from TTO3699599","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","site impacted by Mbadjock camrail","system=
","1483","04-12-2024 19:28:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003758059","Nguila",=
"","04-12-2024 19:28:31","04-12-2024 19:03:49","04-12-2024 19:33:11","Casca=
ded Incident from TTO3699599","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site impacted by Mbadjock camrail","syst=
em","269876","04-12-2024 19:28:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003757988","N=
YOM 2 IHS","","04-12-2024 19:08:32","04-12-2024 19:00:27","04-12-2024 19:51=
:35","Grid outage with main gen faulty//Grid return","Fabrice Pouakam","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage =
with main gen faulty//Grid return","emmanuel.ghani@ihstowers.com","486","04=
-12-2024 19:08:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_696","NOCINC0003757982","Barriere=
 IHS","","04-12-2024 19:07:50","04-12-2024 17:02:38","04-12-2024 20:07:47",=
"Cascaded Incident from TTO3698714","Hyemafo Gildas","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down due to 01/04 recti=
fiers faulty // he changed 01 rectifiers, site on grid","system","277057","=
04-12-2024 19:07:50","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003757860","Ebo=
go","","04-12-2024 18:38:32","04-12-2024 18:32:27","04-12-2024 18:43:47","S=
ite went down due work made by Kameni Roberto(697010591) from Broadcom(repl=
acement DC BOX)//End of work ","Siligap Boris","Installation Activity","Pas=
sive","Planned Activity","Installation Activity","Site went down due work m=
ade by Kameni Roberto(697010591) from Broadcom(replacement DC BOX)//End of =
work ","christian.fonkou@ihstowers.com","366","04-12-2024 18:38:32","Sagemc=
om CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0003757566","Aha=
la Echangeur","","04-12-2024 17:51:40","04-12-2024 17:30:34","04-12-2024 18=
:08:30","Grid fluctuation site went down because Gen failed to start due to=
 Grid bad voltage // we bypass grid and gen manually started","MINKA NICOLA=
S","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation site went down because Gen failed to start due to Grid b=
ad voltage // we bypass grid and gen manually started","kombi.samuel@ihstow=
ers.com","1267","04-12-2024 17:51:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003757491","N=
yom OCM","","04-12-2024 17:39:25","04-12-2024 17:36:18","04-12-2024 18:44:0=
3","Grid fluctuation site went down because Gen failed to start due to Grid=
 bad voltage // we bypass grid and gen manually started","Fabrice Pouakam",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid fluctuation site went down because Gen failed to start due to Grid bad =
voltage // we bypass grid and gen manually started","emmanuel.ghani@ihstowe=
rs.com","188","04-12-2024 17:39:25","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0003757294","SAA=
 2","","04-12-2024 17:14:46","04-12-2024 17:09:33","04-12-2024 18:35:50","N=
o power issue site on grid with U=3D54,8v Gregoire(654547479) from Huawei i=
s working on site","Parker Tchoup","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D54,8v Gregoire(654547479) from Huawei is working on site","christi=
an.fonkou@ihstowers.com","314","04-12-2024 17:14:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003757260","M=
efou-Assi","IHS_YND_696","04-12-2024 17:10:41","04-12-2024 17:02:38","04-12=
-2024 20:07:47","site went down due to 01/04 rectifiers faulty // he change=
d 01 rectifiers, site on grid","Fanda Brice","Equipment Repair","Passive","=
Rectifier","Rectifier Module","site went down due to 01/04 rectifiers fault=
y // he changed 01 rectifiers, site on grid","emmanuel.ghani@ihstowers.com"=
,"484","04-12-2024 17:10:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003757106","E=
kie-Elegance","","04-12-2024 16:42:50","04-12-2024 15:33:06","04-12-2024 16=
:17:07","Grid outage//MDG of 20 kva has deployed","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG=
 of 20 kva has deployed","emmanuel.ghani@ihstowers.com","4185","04-12-2024 =
16:42:50","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0003757044","Mba=
nkolo petit paris","","04-12-2024 16:32:24","04-12-2024 16:13:14","04-12-20=
24 17:01:48","site went down due to work(ROCKSYS(696961721)/LOUMAD ENGINERI=
NG is working from Swapp IPT// End of work","Mboua Thierry","Equipment Repl=
acement","Passive","Planned Activity","Planned Activity - Passive","site we=
nt down due to work(ROCKSYS(696961721)/LOUMAD ENGINERING is working from Sw=
app IPT// End of work","christian.fonkou@ihstowers.com","1150","04-12-2024 =
16:32:24","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_167","NOCINC0003756707","Touring Cl=
ub International","","04-12-2024 15:44:51","","","Site alarming due to High=
 temp 34 C// 25 C and alarm cleared","Albran Byorel","Warning","Warning","E=
NVIRONMENT","Warning - High Temperature","Site alarming due to High temp 34=
 C// 25 C and alarm cleared","joelle.ekessi@ihstowers.com","65","04-12-2024=
 15:44:51","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_319","NOCINC0003756569","SOA 2","",=
"04-12-2024 15:15:18","","","Site alarming High Temp 41=B0C because Aircon =
faulty and shelter is already open// Temp dicrease","Siligap Boris","Warnin=
g","Warning","ENVIRONMENT","Warning - Aircon Compressor Faulty","Site alarm=
ing High Temp 41=B0C because Aircon faulty and shelter is already open// Te=
mp dicrease","joelle.ekessi@ihstowers.com","76","04-12-2024 15:15:18","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003756456","E=
lobi Mokolo","","04-12-2024 14:52:35","04-12-2024 14:49:31","04-12-2024 15:=
47:57","Grid Outage, site went down because Gen started and stopped due to =
High temp// He added water and started Gen manualy","Mboua Thierry","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Grid Outage, site went down because Gen started and stopped due to H=
igh temp// He added water and started Gen manualy","emmanuel.ghani@ihstower=
s.com","184","04-12-2024 14:52:35","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003755947","AWA=
E OCM","","04-12-2024 13:39:39","04-12-2024 13:33:33","04-12-2024 14:23:12"=
,"Grid fluctuation, site went down before gen start due to poor battery bac=
kup // Gen started automatically","Mba Lazare Herve","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid fluctuation, sit=
e went down before gen start due to poor battery backup // Gen started auto=
matically","rouselle.schoune@ihstowers.com","367","04-12-2024 13:39:39","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0003755581","Aha=
la Echangeur","","04-12-2024 12:54:07","04-12-2024 12:50:02","04-12-2024 13=
:45:32","grid outage, site went down because Dg start and stopped due to lo=
ad with alarm ""over current"" // He reduced the load and reset gen card, s=
ite on gen","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","grid outage, site went down because Dg start and stopped d=
ue to load with alarm ""over current"" // He reduced the load and reset gen=
 card, site on gen","rouselle.schoune@ihstowers.com","246","04-12-2024 12:5=
4:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0003754976","OKOA Pea=
ge","","04-12-2024 11:47:02","04-12-2024 11:41:06","04-12-2024 11:57:06","C=
ascaded Incident from TTO3695869","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down due to 02/06 rectifiers=
 faulty // He changed 02 rectifiers ,site on grid","system","356","04-12-20=
24 11:47:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003754977","Mambine"=
,"","04-12-2024 11:47:02","04-12-2024 11:41:06","04-12-2024 11:57:06","Casc=
aded Incident from TTO3695869","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down due to 02/06 rectifiers fa=
ulty // He changed 02 rectifiers ,site on grid","system","356","04-12-2024 =
11:47:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0003754978","Angongo"=
,"","04-12-2024 11:47:02","04-12-2024 11:41:06","04-12-2024 11:57:06","Casc=
aded Incident from TTO3695869","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down due to 02/06 rectifiers fa=
ulty // He changed 02 rectifiers ,site on grid","system","356","04-12-2024 =
11:47:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003754979","Nkongtoc=
k","","04-12-2024 11:47:02","04-12-2024 11:41:06","04-12-2024 11:57:06","Ca=
scaded Incident from TTO3695869","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down due to 02/06 rectifi=
ers faulty // He changed 02 rectifiers ,site on grid","system","356","04-12=
-2024 11:47:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0003754975","Nomayos-=
IHS","","04-12-2024 11:47:01","04-12-2024 11:41:06","04-12-2024 11:57:06","=
Cascaded Incident from TTO3695869","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site went down due to 02/06 rectifier=
s faulty // He changed 02 rectifiers ,site on grid","system","355","04-12-2=
024 11:47:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0003754973","Mbankomo=
 IHS","","04-12-2024 11:47:01","04-12-2024 11:41:06","04-12-2024 11:57:06",=
"Cascaded Incident from TTO3695869","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to 02/06 rectifie=
rs faulty // He changed 02 rectifiers ,site on grid","system","355","04-12-=
2024 11:47:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0003754972","Mandoumb=
a OCM","","04-12-2024 11:47:01","04-12-2024 11:41:06","04-12-2024 11:57:06"=
,"Cascaded Incident from TTO3695869","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down due to 02/06 rec=
tifiers faulty // He changed 02 rectifiers ,site on grid","system","355","0=
4-12-2024 11:47:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0003754974","Nkenglik=
ok","","04-12-2024 11:47:01","04-12-2024 11:41:06","04-12-2024 11:57:06","C=
ascaded Incident from TTO3695869","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down due to 02/06 rectif=
iers faulty // He changed 02 rectifiers ,site on grid","system","355","04-1=
2-2024 11:47:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0003754971","Sous Pre=
fecture","","04-12-2024 11:47:00","04-12-2024 11:41:06","04-12-2024 11:57:0=
6","Cascaded Incident from TTO3695869","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down due to 02/06 recti=
fiers faulty // He changed 02 rectifiers ,site on grid","system","354","04-=
12-2024 11:47:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0003754890","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_697, I=
HS_YND_330, IHS_YND_350, IHS_YND_335, IHS_YND_349","04-12-2024 11:43:16","0=
4-12-2024 11:41:06","04-12-2024 11:57:06","site went down due to 02/06 rect=
ifiers faulty // He changed 02 rectifiers ,site on grid","Fanda Brice","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module","site went down due=
 to 02/06 rectifiers faulty // He changed 02 rectifiers ,site on grid","den=
is.mballa@ihstowers.com","132","04-12-2024 11:43:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003754739","E=
kie-Elegance","","04-12-2024 11:30:24","04-12-2024 11:21:10","04-12-2024 13=
:59:20","grid ouatage //Grid Outage //he deployed a MDG (20KVA)	","Albran B=
yorel","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid ouatage //Grid Outage //he deployed a MDG (20KVA)	","denis.mballa@ihst=
owers.com","555","04-12-2024 11:30:24","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003754348","BAT=
A Mokolo OCM","","04-12-2024 10:55:48","04-12-2024 10:51:42","04-12-2024 20=
:18:51","grid outage,no space to deploy a mobil gen // grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage=
,no space to deploy a mobil gen // grid return","rouselle.schoune@ihstowers=
.com","247","04-12-2024 10:55:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003754193","H=
-Progres","","04-12-2024 10:33:26","04-12-2024 10:31:16","04-12-2024 20:11:=
46","grid poutage,no space to deploy a mobil gen // grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","grid poutage,n=
o space to deploy a mobil gen // grid return","denis.mballa@ihstowers.com",=
"132","04-12-2024 10:33:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003754168","B=
ATA-Mokolo","","04-12-2024 10:31:42","04-12-2024 10:29:29","04-12-2024 20:1=
3:08","grid outage,no space to deploy a mobil gen // grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,n=
o space to deploy a mobil gen // grid return","denis.mballa@ihstowers.com",=
"135","04-12-2024 10:31:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003753980","MVAN SAC=
EL","","04-12-2024 10:17:10","04-12-2024 10:07:02","04-12-2024 18:32:03","C=
ascaded Incident from TTO3694866","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Gen overload 20kva 290A waiting grid=
 return","system","302265","04-12-2024 10:17:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003753973","M=
VAN","IHS_YND_510","04-12-2024 10:16:17","04-12-2024 10:06:59","04-12-2024 =
18:32:24","grid outage, site went dwon due to Gen Oerload(20kva; 290A) // G=
rid return ","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","grid outage, site went dwon due to Gen Oerload(20kva; 290A) //=
 Grid return ","denis.mballa@ihstowers.com","619","04-12-2024 10:16:17","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0003753851","Fou=
da Quarter","","04-12-2024 09:54:29","04-12-2024 09:51:20","04-12-2024 10:0=
9:09","site went down because 1/3 rectifier faulty//he remove the faulty re=
ctifier:site on 2 rectifiers","Delor Telezing","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module","site went down because 1/3 rectifier fault=
y//he remove the faulty rectifier:site on 2 rectifiers","rouselle.schoune@i=
hstowers.com","189","04-12-2024 09:54:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_082","NOCINC0003753757","Mokolo Y=
aounde","","04-12-2024 09:42:01","04-12-2024 09:33:34","04-12-2024 10:53:39=
","grid outage,no space to deploy a mobil gen//grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no spac=
e to deploy a mobil gen//grid return","system","507","04-12-2024 09:42:01",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0526","IHS_YND_088","NOCINC0003753750","Elo=
bi Mokolo","","04-12-2024 09:40:40","04-12-2024 09:31:06","04-12-2024 11:28=
:23","Grid outage, Site went down because gen fails to start due to emergen=
cy stop button actived //he desactived it and started the gen","Mboua Thier=
ry","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid o=
utage, Site went down because gen fails to start due to emergency stop butt=
on actived //he desactived it and started the gen","rouselle.schoune@ihstow=
ers.com","1515","04-12-2024 09:40:40","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003753508","NYO=
M FACE MAETUR","","04-12-2024 09:07:07","04-12-2024 08:29:00","04-12-2024 1=
3:29:09","Grid Outage landlord has forbiden to start the Gen due to Noise /=
/ grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen d=
ue to Noise // grid return","rouselle.schoune@ihstowers.com","2288","04-12-=
2024 09:07:07","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003753425","Com=
plex Beac II","","04-12-2024 08:51:54","04-12-2024 08:47:49","04-12-2024 09=
:13:26","Grid outage, site went down because gen start and stopped with Oil=
 pressure alarm // Reset done and gen started","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went =
down because gen start and stopped with Oil pressure alarm // Reset done an=
d gen started","rouselle.schoune@ihstowers.com","246","04-12-2024 08:51:54"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003753316","N=
YOM 2 IHS","","04-12-2024 08:32:43","04-12-2024 08:28:30","04-12-2024 10:38=
:15","Grid outage ,Site went down because No Main Gen on site at the moment=
 // Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Generator Faulty","Grid outage ,Site went down because No Main Gen =
on site at the moment // Grid return","denis.mballa@ihstowers.com","254","0=
4-12-2024 08:32:43","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003753215","Odz=
a II","","04-12-2024 08:19:30","04-12-2024 08:16:23","04-12-2024 09:42:23",=
"Grid outage, site went down because gen fails to start due to incomplete p=
wc configuration // Gen manually started","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down =
because gen fails to start due to incomplete pwc configuration // Gen manua=
lly started","rouselle.schoune@ihstowers.com","188","04-12-2024 08:19:30","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003753127","C=
omplexe-BEAC","","04-12-2024 07:59:48","04-12-2024 07:57:38","04-12-2024 08=
:48:38","Grid outage, site went down because gen start and stopped with Ove=
r voltage alarm due to AVR disfunctionning // he bypass avr and manually st=
art the gen","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- AVR","Grid outage, site went down because gen start and stopped with Over=
 voltage alarm due to AVR disfunctionning // he bypass avr and manually sta=
rt the gen","denis.mballa@ihstowers.com","131","04-12-2024 07:59:48","Sagem=
com CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0003752528","NKO=
NGKARAK","","04-12-2024 06:19:04","04-12-2024 06:16:59","04-12-2024 07:16:5=
9","Grid outage, site went down because gen start and stoppedwith oil press=
ure alarm // he added oil and manually started","TIENTCHEU NZETCHIEU GAEL",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
, site went down because gen start and stoppedwith oil pressure alarm // he=
 added oil and manually started","rouselle.schoune@ihstowers.com","126","04=
-12-2024 06:19:04","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003752260","Sap=
eur","","04-12-2024 05:10:02","04-12-2024 05:01:53","04-12-2024 06:47:53","=
Grid outage, site went down because gen start and stopped with Under voltag=
e alarm // reset of gen card done and manually started","Mboua Thierry","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, s=
ite went down because gen start and stopped with Under voltage alarm // res=
et of gen card done and manually started","kamga.virgile@ihstowers.com","49=
0","04-12-2024 05:10:02","Sagemcom CMR"
"Cancelled","Warning","T0535","IHS_YND_234","NOCINC0003752135","Oyomabang M=
TN","","04-12-2024 04:28:33","","","","TIENTCHEU NZETCHIEU GAEL","","","","=
","","kamga.virgile@ihstowers.com","1408","04-12-2024 04:28:33","Sagemcom C=
MR"
"Closed Complete","Site Down","T0579","IHS_YND_366","NOCINC0003751847","Man=
doumba MTN","","04-12-2024 02:41:50","04-12-2024 02:33:58","04-12-2024 06:4=
0:58","Grid outage, site went down because gen fails to start due to relay =
contactor ge faulty // he bypass it and manually started","Kemeni Franklin"=
,"Equipment Repair","Passive","Control Panel","Relay","Grid outage, site we=
nt down because gen fails to start due to relay contactor ge faulty // he b=
ypass it and manually started","kamga.virgile@ihstowers.com","473","04-12-2=
024 02:41:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003751308","L=
abogenie","","03-12-2024 23:28:34","03-12-2024 23:12:24","03-12-2024 23:15:=
36","No  power issue U =3D54,6V site on grid.   The Tx FME Eloundou Bertran=
d (693212405)from Huawei is informed. Repetitive issue","","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No  =
power issue U =3D54,6V site on grid. The Tx FME Eloundou Bertrand (69321240=
5)from Huawei is informed. Repetitive issue



","alexandre.kamal@ihstowers.com","971","03-12-2024 23:28:34","Sagemcom CMR=
"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003751150","NYO=
M 2 IHS","","03-12-2024 22:49:13","03-12-2024 22:42:02","03-12-2024 22:50:4=
1","Grid outage ,Site went down because No Main Gen on site at the moment /=
/ Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Generator Faulty","Grid outage ,Site went down because No Main Gen on=
 site at the moment // Grid return","kamga.virgile@ihstowers.com","693","03=
-12-2024 22:49:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0003751149","Mvog-Eba=
nda","","03-12-2024 22:49:00","03-12-2024 21:16:23","03-12-2024 22:50:47","=
Cascaded Incident from TTO3691018","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage ,site went down  becaus=
e Gen started and stooped  due to  Gen overload (16KVA,220A)//Grid return",=
"system","269144","03-12-2024 22:49:00","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003751147","NYO=
M FACE MAETUR","","03-12-2024 22:47:06","03-12-2024 22:45:56","03-12-2024 2=
2:53:44","Grid Outage landlord has forbiden to start the Gen due to Noise//=
 Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen =
due to Noise// Grid Restored","kamga.virgile@ihstowers.com","71","03-12-202=
4 22:47:06","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003751112","Lad=
a I Yde","","03-12-2024 22:39:51","03-12-2024 21:59:40","03-12-2024 22:51:4=
8","grid outage,gen failed to start due to battery Ge faulty//he started th=
e gen with battery backup","Mba Lazare Herve","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Generator Battery","grid outage,gen failed to start due =
to battery Ge faulty//he started the gen with battery backup","kamga.virgil=
e@ihstowers.com","2412","03-12-2024 22:39:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003750906","N=
omayos-IHS","","03-12-2024 21:59:49","03-12-2024 21:55:43","03-12-2024 22:4=
3:40","Site went down because 02/04 rectifiers hanging//He reset rectifier,=
site on  Grid","Fanda Brice","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down because 02/04 rectifiers hanging//He reset re=
ctifier,site on  Grid","stephane.nkamwa@ihstowers.com","247","03-12-2024 21=
:59:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003750714","A=
bom","IHS_YND_269","03-12-2024 21:30:32","03-12-2024 21:16:23","03-12-2024 =
22:50:47","Grid outage ,site went down  because Gen started and stooped  du=
e to  Gen overload (16KVA,220A)//Grid return","Siligap Boris","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went down  =
because Gen started and stooped  due to  Gen overload (16KVA,220A)//Grid re=
turn","stephane.nkamwa@ihstowers.com","850","03-12-2024 21:30:32","Sagemcom=
 CMR"
"Cancelled","Warning","CTR_341","IHS_YND_269","NOCINC0003750672","Mvog-Eban=
da","","03-12-2024 21:26:13","","","","Siligap Boris","","","","","","steph=
ane.nkamwa@ihstowers.com","623","03-12-2024 21:26:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003750662","Eseka To=
wn","","03-12-2024 21:24:51","03-12-2024 21:17:10","03-12-2024 22:49:16","C=
ascaded Incident from TTO3690916","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down b=
ecause Gen fails to start due to Grid contactor dysfunctionned causing by G=
rid bad voltage//He bypassed it and started Gen manually","system","276349"=
,"03-12-2024 21:24:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003750663","Song-bon=
g","","03-12-2024 21:24:51","03-12-2024 21:17:10","03-12-2024 22:49:16","Ca=
scaded Incident from TTO3690916","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down be=
cause Gen fails to start due to Grid contactor dysfunctionned causing by Gr=
id bad voltage//He bypassed it and started Gen manually","system","276349",=
"03-12-2024 21:24:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003750641","E=
seka OCM","IHS_YND_378, IHS_YND_453","03-12-2024 21:23:16","03-12-2024 21:1=
7:10","03-12-2024 22:49:16","Grid fluctuation, Site went down because Gen f=
ails to start due to Grid contactor dysfunctionned causing by Grid bad volt=
age//He bypassed it and started Gen manually","Kemeni Franklin","Equipment =
Repair","Passive","Control Panel","ATS-AMF Issue","Grid fluctuation, Site w=
ent down because Gen fails to start due to Grid contactor dysfunctionned ca=
using by Grid bad voltage//He bypassed it and started Gen manually","stepha=
ne.nkamwa@ihstowers.com","367","03-12-2024 21:23:16","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003750068","Elo=
umdem stade","","03-12-2024 19:56:08","03-12-2024 19:48:00","03-12-2024 21:=
12:45","	Grid fluctuation, site went down because Gen start and stopped due=
 to Grid bad voltage //He bypass the Grid and Gen manually started","Fanda =
Brice","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","	Grid fluctuation, site went down because Gen start and stopped due t=
o Grid bad voltage //He bypass the Grid and Gen manually started","landry.e=
tame@ihstowers.com","489","03-12-2024 19:56:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003749632","N=
yom OCM","","03-12-2024 18:51:40","03-12-2024 18:42:35","03-12-2024 20:04:0=
1","Grid fluctuation, site went down because gen start and stopped due to g=
rid bad voltage And RCP on site // he bypass grid and gen manually started"=
,"Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation, site went down because gen start and st=
opped due to grid bad voltage And RCP on site // he bypass grid and gen man=
ually started","stephane.nkamwa@ihstowers.com","546","03-12-2024 18:51:40",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0003749622","Nko=
abang MTN","","03-12-2024 18:49:21","03-12-2024 18:46:15","03-12-2024 19:02=
:18","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage // he bypass grid and gen manually started","Mba Lazare H=
erve","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, site went down because gen start and stopped due to =
grid bad voltage // he bypass grid and gen manually started","landry.etame@=
ihstowers.com","187","03-12-2024 18:49:21","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003749608","Nko=
abang2","","03-12-2024 18:46:03","03-12-2024 18:37:57","03-12-2024 19:51:24=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage and No RCP on site // he bypass grid and gen manually starte=
d","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid fluctuation, site went down because gen start and=
 stopped due to grid bad voltage and No RCP on site // he bypass grid and g=
en manually started","landry.etame@ihstowers.com","578","03-12-2024 18:46:0=
3","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003748818","Song-bon=
g","","03-12-2024 16:21:01","03-12-2024 16:10:23","03-12-2024 16:34:03","Ca=
scaded Incident from TTO3688731","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because Gen started =
and stoppad due to Grid bad voltage and No RCP On site // He bypass the Gri=
d and Gen manually started","system","638","03-12-2024 16:21:01","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003748817","Eseka To=
wn","","03-12-2024 16:21:00","03-12-2024 16:10:23","03-12-2024 16:34:03","C=
ascaded Incident from TTO3688731","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because Gen started=
 and stoppad due to Grid bad voltage and No RCP On site // He bypass the Gr=
id and Gen manually started","system","637","03-12-2024 16:21:00","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003748806","E=
seka OCM","IHS_YND_378, IHS_YND_453","03-12-2024 16:18:28","03-12-2024 16:1=
0:23","03-12-2024 16:34:03","Site went down because Gen started and stoppad=
 due to Grid bad voltage and No RCP On site // He bypass the Grid and Gen m=
anually started","Kemeni Franklin","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Site went down because Gen started and st=
oppad due to Grid bad voltage and No RCP On site // He bypass the Grid and =
Gen manually started","stephane.nkamwa@ihstowers.com","486","03-12-2024 16:=
18:28","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003748487","ODZ=
A MINKAN EDIBI ASSI","","03-12-2024 15:34:48","03-12-2024 15:20:42","03-12-=
2024 18:13:34","Site went down due to Works Our FME Albran(657108542) is wo=
rking on Site ''Replaced the ATS""//end OF WORKS","Albran Byorel","Equipmen=
t Replacement","Passive","Planned Activity","Planned Activity - Passive","S=
ite went down due to Works Our FME Albran(657108542) is working on Site ''R=
eplaced the ATS""//end OF WORKS","landry.etame@ihstowers.com","847","03-12-=
2024 15:34:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003748340","C=
rf Cornier","","03-12-2024 15:03:27","03-12-2024 14:53:18","03-12-2024 20:0=
0:33","Active//No power issue on site, Site on Grid UBAIE=3D54.6V and Geoge=
s (697461814) From huawei is informed ","MINKA NICOLAS","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue on site, Site on Grid UBAIE=3D54.6V and Geoges (697461814) =
From huawei is informed ","stephane.nkamwa@ihstowers.com","610","03-12-2024=
 15:03:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0003748199","A=
RMP","","03-12-2024 14:37:47","03-12-2024 14:30:35","03-12-2024 14:42:14","=
Grid Outage //he deployed a MDG (20KVA)","","Grid Supply","Passive","Grid",=
"National Grid - Grid Outage Issue","Grid Outage //he deployed a MDG (20KVA=
)","stephane.nkamwa@ihstowers.com","433","03-12-2024 14:37:47","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0003748189","E=
mombo","","03-12-2024 14:35:18","03-12-2024 14:29:10","03-12-2024 14:37:22"=
,"Grid outage DG fails to start// Grid return (investigation on going)","Mb=
a Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","Grid outage DG fails to start// Grid return (investigation on going)",=
"stephane.nkamwa@ihstowers.com","368","03-12-2024 14:35:18","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_207","NOCINC0003747936","ARMP Build=
ing","","03-12-2024 13:48:39","","","site on alarm due to grid outage//gen =
started","Mboua Thierry","Warning","Warning","POWER","Warning - Site on Bat=
tery","site on alarm due to grid outage//gen started","joelle.ekessi@ihstow=
ers.com","64","03-12-2024 13:48:39","Sagemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003747903","Bas=
tos Bir","","03-12-2024 13:43:58","03-12-2024 13:37:50","03-12-2024 14:11:0=
8","Grid Outage, site went because Gen stoppen with alarm ""high Temp""// H=
e Open the Door and started Gen manualy","Mboua Thierry","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid=
 Outage, site went because Gen stoppen with alarm ""high Temp""// He Open t=
he Door and started Gen manualy","christian.fonkou@ihstowers.com","369","03=
-12-2024 13:43:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0003747558","M=
bankomo IHS","","03-12-2024 12:55:53","03-12-2024 12:52:47","03-12-2024 13:=
47:53","grid outage, site went down because gen start and stopped with Alar=
m ""over voltage"" // He reset gen card and gen manually started","Fanda Br=
ice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid o=
utage, site went down because gen start and stopped with Alarm ""over volta=
ge"" // He reset gen card and gen manually started","emmanuel.ghani@ihstowe=
rs.com","187","03-12-2024 12:55:53","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_319","NOCINC0003747553","SOA 2","",=
"03-12-2024 12:54:46","","","Site alarming due to High temp 42 C// 30 C and=
 alarm cleared","Siligap Boris","Warning","Warning","ENVIRONMENT","Warning =
- High Temperature","Site alarming due to High temp 42 C// 30 C and alarm c=
leared","joelle.ekessi@ihstowers.com","69","03-12-2024 12:54:46","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0003747549","Mfou EPC=
","","03-12-2024 12:54:00","03-12-2024 12:47:33","03-12-2024 13:19:43","Cas=
caded Incident from TTO3687235","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D54,4v site =
on grid Team Guy Nya/ 677550391 (Huawei) upgrade","system","263725","03-12-=
2024 12:54:00","Sagemcom CMR"
"Closed Complete","Site Down","T0144","IHS_YND_333","NOCINC0003747541","Mfo=
u MTN","IHS_YND_674","03-12-2024 12:52:40","03-12-2024 12:47:33","03-12-202=
4 13:39:43","No power issue on site U=3D54,4v site on grid Team Guy Nya/ 67=
7550391 (Huawei) upgrade","Mba Lazare Herve","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site U=3D54,4v site on grid Team Guy Nya/ 677550391 (Huawei) upgrade","chri=
stian.fonkou@ihstowers.com","308","03-12-2024 12:52:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003747385","I=
mm-Olympique","","03-12-2024 12:30:55","03-12-2024 12:26:46","03-12-2024 13=
:46:46","No power issue on site U=3D54v site on grid Tx Brice Stague of hua=
wei is informed notice that disjunction of CB in BTS Ocm","Paul BIBOUM","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue on site U=3D54v site on grid Tx Brice Stague of hua=
wei is informed notice that disjunction of CB in BTS Ocm","emmanuel.ghani@i=
hstowers.com","250","03-12-2024 12:30:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003747079","D=
ragage","","03-12-2024 11:47:39","03-12-2024 11:44:16","03-12-2024 11:47:01=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen automatically started.","Mboua Thierry","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Gen automatically started."=
,"emmanuel.ghani@ihstowers.com","204","03-12-2024 11:47:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003746544","Ndogbess=
ol","","03-12-2024 10:39:02","03-12-2024 10:30:49","03-12-2024 10:58:49","C=
ascaded Incident from TTO3685973","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because is impacted=
 by Sombo Mtn(site went down due to work Marcel/650160759/SAGEMCOM:doing th=
e PM// End of work","system","271977","03-12-2024 10:39:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_781","NOCINC0003746539","BIBOMDJI=
DJIEL","","03-12-2024 10:39:01","03-12-2024 10:30:49","03-12-2024 10:58:49"=
,"Cascaded Incident from TTO3685973","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down because is impac=
ted by Sombo Mtn(site went down due to work Marcel/650160759/SAGEMCOM:doing=
 the PM// End of work","system","492","03-12-2024 10:39:01","Sagemcom CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0003746158","Ese=
ka MTN","","03-12-2024 09:52:23","03-12-2024 09:42:15","03-12-2024 10:16:27=
","Site went down due to insufficiency of rectifiers // He added 02 rectifi=
ers","Kemeni Franklin","Equipment Repair","Passive","Control Panel","ATS-AM=
F Issue","grid outage, site went down because gen failed to start due to ge=
n contactor not excited // He excited gen contactor and gen manually starte=
d
","christian.fonkou@ihstowers.com","608","03-12-2024 09:52:23","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003745711","C=
omplexe-BEAC","","03-12-2024 09:04:35","03-12-2024 09:01:26","03-12-2024 10=
:08:53","Grid outage, site went down because Gen started and stopped due to=
 under voltage alarm// he reset the Gen card and Gen manually started","Alb=
ran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, site went down because Gen started and stopped due to under v=
oltage alarm// he reset the Gen card and Gen manually started","emmanuel.gh=
ani@ihstowers.com","191","03-12-2024 09:04:35","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003745705","ODZ=
A MINKAN EDIBI ASSI","","03-12-2024 09:02:05","03-12-2024 08:57:58","03-12-=
2024 09:09:24","grid outage, site went down due to dysfunctionning of  NEW =
PWC IBS installed // grid return","Albran Byorel","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","grid outage, site went down due to d=
ysfunctionning of  NEW PWC IBS installed // grid return","christian.fonkou@=
ihstowers.com","248","03-12-2024 09:02:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003745521","O=
lembe-Terminus","","03-12-2024 08:26:41","03-12-2024 08:21:28","03-12-2024 =
08:41:46","Grid outage, Site went down because Gen failed to start due to a=
larm ""overvoltage""// Grid power return","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went dow=
n because Gen failed to start due to  alarm ""overvoltage""// Grid power re=
turn","emmanuel.ghani@ihstowers.com","314","03-12-2024 08:26:41","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003745513","Akak-Nko=
zoa-MTN-IHS","","03-12-2024 08:24:41","03-12-2024 08:21:19","03-12-2024 08:=
42:11","Cascaded Incident from TTO3684915","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo outage, site down be=
fore DG started due to poor backup  // Eneo return","system","1214899","03-=
12-2024 08:24:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0003745314","Mvog-Eba=
nda","","03-12-2024 07:43:30","03-12-2024 07:40:18","03-12-2024 08:40:48","=
Cascaded Incident from TTO3684682","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen ran untill fuel shortage // refueling done","system","275131","03-12-2=
024 07:43:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003745311","A=
bom","IHS_YND_269","03-12-2024 07:42:25","03-12-2024 07:40:18","03-12-2024 =
08:40:48","Grid outage, site went down because gen ran untill fuel shortage=
 // refueling done","Siligap Boris","Fuel Outage","Passive","Diesel","Diese=
l Outage","Grid outage, site went down because gen ran untill fuel shortage=
 // refueling done","emmanuel.ghani@ihstowers.com","128","03-12-2024 07:42:=
25","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003745221","Lad=
a I Yde","","03-12-2024 07:24:40","03-12-2024 07:21:34","03-12-2024 07:51:1=
1","grid outage,gen failed to start due to Battery Ge faulty//He started th=
e gen with battery backup","Mba Lazare Herve","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Generator Battery","grid outage,gen failed to start due =
to Battery Ge faulty//He started the gen with battery backup","christian.fo=
nkou@ihstowers.com","187","03-12-2024 07:24:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003745150","L=
abogenie","","03-12-2024 07:07:26","03-12-2024 07:03:17","03-12-2024 07:50:=
15","No power issue on site U=3D54v site on grid Tx fme Eloundou of huawei =
is informed","","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","No power issue on site U=3D54v site on grid Tx =
fme Eloundou of huawei is informed","emmanuel.ghani@ihstowers.com","250","0=
3-12-2024 07:07:26","Sagemcom CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0003745115","Nko=
abang Alembe","","03-12-2024 07:03:54","03-12-2024 06:59:47","03-12-2024 07=
:41:39","grid outage, site went down because gen failed to start // Gen man=
ually started (investigation ongoing)","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","grid outage, site went down =
because gen failed to start // Gen manually started (investigation ongoing)=
","christian.fonkou@ihstowers.com","248","03-12-2024 07:03:54","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003745103","A=
ngongo","","03-12-2024 06:57:36","03-12-2024 06:50:29","03-12-2024 07:50:29=
","No power issue on site U=3D54v site on gen Tx Etienne of huawei is infor=
med","Fanda Brice","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v site on gen T=
x Etienne of huawei is informed","emmanuel.ghani@ihstowers.com","428","03-1=
2-2024 06:57:36","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003744862","Eko=
unou","","03-12-2024 06:07:48","03-12-2024 06:00:43","03-12-2024 06:07:42",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","do=
rothy.djantio@ihstowers.com","426","03-12-2024 06:07:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003744602","A=
ngongo","","03-12-2024 05:03:42","03-12-2024 04:54:26","03-12-2024 05:00:38=
","Active//No power issue site on Gen with U=3D55,1v Georges(697461814)from=
 Huawei is informed and up at 05:09 AM","Fanda Brice","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue site on Gen with U=3D55,1v Georges(697461814)from Huawei is i=
nformed and up at 05:09 AM","olivier.kwedi@ihstowers.com","557","03-12-2024=
 05:03:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003744372","Nkolo II=
 New","","03-12-2024 03:23:40","03-12-2024 03:13:41","03-12-2024 06:20:55",=
"Cascaded Incident from TTO3683575","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage,gen failed to start=
 due to Battery Ge faulty//He started the gen with battery backup","system"=
,"283812","03-12-2024 03:23:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003744369","M=
imboman-Village","IHS_YND_709","03-12-2024 03:21:55","03-12-2024 03:13:41",=
"03-12-2024 06:20:55","grid outage,gen failed to start due to ATS faulty//G=
en manually started","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","ATS-AMF Issue","grid outage,gen failed to start due to ATS fault=
y//Gen manually started","olivier.kwedi@ihstowers.com","495","03-12-2024 03=
:21:55","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003744307","NYO=
M FACE MAETUR","","03-12-2024 03:00:08","03-12-2024 02:41:56","03-12-2024 0=
7:57:34","grid bad voltage,an gen failed to start//he did a bridge on good =
phase","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","grid bad voltage,an gen failed to start//he did a b=
ridge on good phase","dorothy.djantio@ihstowers.com","1093","03-12-2024 03:=
00:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003744216","E=
seka OCM","","03-12-2024 02:18:56","03-12-2024 02:15:49","03-12-2024 02:20:=
06","ACTIVE //No power issue U=3D51V site on Gen The Tx FME Etienne FOPA /6=
95033981/ From HUAWEI is informed and up at 02:18 AM","Kemeni Franklin","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","ACTIVE //No power issue U=3D51V site on Gen The Tx FME Etienne FOP=
A /695033981/ From HUAWEI is informed and up at 02:18 AM","olivier.kwedi@ih=
stowers.com","188","03-12-2024 02:18:56","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0003744163","Bon=
djock","","03-12-2024 02:00:45","03-12-2024 01:57:38","03-12-2024 02:01:24"=
,"Grid outage, site went down before Gen start due to poor backup// Grid po=
wer return","Fanda Brice","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage, site went down before Gen start due=
 to poor backup// Grid power return","dorothy.djantio@ihstowers.com","188",=
"03-12-2024 02:00:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003744160","Biteng-M=
aetur","","03-12-2024 01:59:21","03-12-2024 01:54:04","03-12-2024 02:14:17"=
,"Cascaded Incident from TTO3683313","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
fore Gen start due to poor backup// Grid power return","system","266882","0=
3-12-2024 01:59:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003744159","Tradex-N=
komo","","03-12-2024 01:59:20","03-12-2024 01:54:04","03-12-2024 02:14:17",=
"Cascaded Incident from TTO3683313","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 Gen start due to poor backup// Grid power return","system","266882","03-12=
-2024 01:59:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003744155","B=
iteng","IHS_YND_172, IHS_YND_249","03-12-2024 01:57:16","03-12-2024 01:54:0=
4","03-12-2024 02:14:17","Grid outage, site went down before Gen start due =
to poor backup// Grid power return","Mba Lazare Herve","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before Gen start due to poor backup// Grid power return","olivier.=
kwedi@ihstowers.com","193","03-12-2024 01:57:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003744011","M=
ontee-Des-Soeurs","","03-12-2024 01:26:05","03-12-2024 01:23:55","03-12-202=
4 01:26:06","Active no power issue, U=3D54,6V on grid: The TX FME Mbah Hosi=
ah (674007438) from Huawei is informed","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
 no power issue, U=3D54,6V on grid: The TX FME Mbah Hosiah (674007438) from=
 Huawei is informed","olivier.kwedi@ihstowers.com","131","03-12-2024 01:26:=
05","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003743757","MIM=
BOMAN LIBERTE","","02-12-2024 23:54:26","02-12-2024 23:46:20","03-12-2024 0=
1:20:08","Grid Outage Site went down because Main Gen Faulty//Grid Restored=
","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid Outage Site went down because Main Gen Faulty//Grid Resto=
red","dorothy.djantio@ihstowers.com","488","02-12-2024 23:54:26","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003743714","N=
koabang","","02-12-2024 23:39:15","02-12-2024 23:35:07","02-12-2024 23:39:3=
0","	Grid outage ,site went down because Gen started and stopped due to Gen=
 OVERLOAD (16.KVA,150 A)//Grid return","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","	Grid outage ,site went down beca=
use Gen started and stopped due to Gen OVERLOAD (16.KVA,150 A)//Grid return=
","olivier.kwedi@ihstowers.com","249","02-12-2024 23:39:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003743704","L=
abogenie","","02-12-2024 23:37:10","02-12-2024 23:33:57","02-12-2024 23:40:=
20","No  power issue U =3D54,6V site on grid.   The Tx FME Georges (6974618=
14)from Huawei is informed. Repetitive issue","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No  power issu=
e U =3D54,6V site on grid.   The Tx FME Georges (697461814)from Huawei is i=
nformed. Repetitive issue","olivier.kwedi@ihstowers.com","194","02-12-2024 =
23:37:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003743671","M=
arche Odza","","02-12-2024 23:24:20","02-12-2024 23:17:10","03-12-2024 00:2=
0:26","No power issue on site. Site on Grid with Ubaie=3D54.5V The fme tx L=
ionel steve/655184876 from Huawei is informed","Albran Byorel","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site. Site on Grid with Ubaie=3D54.5V The fme tx Lionel s=
teve/655184876 from Huawei is informed","olivier.kwedi@ihstowers.com","431"=
,"02-12-2024 23:24:20","Sagemcom CMR"
"Closed Complete","Site Down","T0629","IHS_YND_058","NOCINC0003743622","Mvo=
lye","","02-12-2024 23:12:51","02-12-2024 23:08:46","03-12-2024 00:30:35","=
No power issue U=3D52,7 v site on grid The TX FME Lionel steve/655184876 fr=
om Huawei is informed ..Site up at 11:12 PM","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue U=3D52,7 v site on grid The TX FME Lionel steve/655184876 from=
 Huawei is informed ..Site up at 11:12 PM","dorothy.djantio@ihstowers.com",=
"245","02-12-2024 23:12:51","Sagemcom CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0003743617","Cit=
e des nations","","02-12-2024 23:11:59","02-12-2024 23:08:50","02-12-2024 2=
3:30:46","No power issue U=3D52,7 v site on grid The Tx Fme Hosiah Mbah (67=
4007438) of Huawei is informed..Site up at 11:12 PM","Paul BIBOUM","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue U=3D52,7 v site on grid The Tx Fme Hosiah Mbah (67400743=
8) of Huawei is informed..Site up at 11:12 PM","dorothy.djantio@ihstowers.c=
om","190","02-12-2024 23:11:59","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0003742531","Tou=
ring Club International","","02-12-2024 20:00:21","02-12-2024 19:20:07","02=
-12-2024 19:34:43","Grid outage, site went down because Gen started and sto=
pped due to Under under voltage alarm// he reset the Gen card and Gen manua=
lly started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- Control Panel","Grid outage, site went down because Gen started and stopp=
ed due to Under under voltage alarm// he reset the Gen card and Gen manuall=
y started","kamga.virgile@ihstowers.com","2414","02-12-2024 20:00:21","Sage=
mcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003742472","Nko=
londom","","02-12-2024 19:50:13","02-12-2024 19:26:01","02-12-2024 20:02:33=
","Grid fluctuation, site went down because Gen start and stopped due to Gr=
id bad voltage // Gen manually started","Fabrice Pouakam","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, =
site went down because Gen start and stopped due to Grid bad voltage // Gen=
 manually started","kamga.virgile@ihstowers.com","1454","02-12-2024 19:50:1=
3","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003742442","M=
IMBOMAN LIBERTE","","02-12-2024 19:44:24","02-12-2024 19:01:13","02-12-2024=
 19:20:09","Grid Outage Site went down because  Main Gen Faulty//Grid Resto=
red","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Gen=
erator Faulty","Grid Outage Site went down because  Main Gen Faulty//Grid R=
estored","alexandre.kamal@ihstowers.com","2592","02-12-2024 19:44:24","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003742428","T=
ongolo OCM","","02-12-2024 19:42:59","02-12-2024 18:54:52","02-12-2024 19:3=
9:53","Grid outage, site went down before gen start due to poor battery bac=
kup//Gen started automatically","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup//Gen started automatically",=
"alexandre.kamal@ihstowers.com","2888","02-12-2024 19:42:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003742410","Eto koss=
 Yde","","02-12-2024 19:39:50","02-12-2024 19:12:41","02-12-2024 20:39:05",=
"Cascaded Incident from TTO3681207","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Gen start and stopped due to Grid bad voltage // Gen manually started"=
,"system","291000","02-12-2024 19:39:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003742411","ELOUMDEM=
 CARRIERE 2","","02-12-2024 19:39:50","02-12-2024 19:12:41","02-12-2024 20:=
39:05","Cascaded Incident from TTO3681207","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Gen start and stopped due to Grid bad voltage // Gen manually s=
tarted","system","291001","02-12-2024 19:39:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003742403","O=
lembe-Terminus","","02-12-2024 19:37:49","02-12-2024 19:07:43","02-12-2024 =
19:13:08","Grid outage, Site went down because Gen failed to start due alar=
m ""overvoltage""// Grid power return","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down b=
ecause Gen failed to start due alarm ""overvoltage""// Grid power return","=
alexandre.kamal@ihstowers.com","1807","02-12-2024 19:37:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003742398","Mballa 4=
","","02-12-2024 19:36:41","02-12-2024 18:59:38","02-12-2024 19:27:03","Cas=
caded Incident from TTO3681164","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n stopped with alarm under frequency // Grid Restored","system","284632","0=
2-12-2024 19:36:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003742396","N=
yom OCM","","02-12-2024 19:35:23","02-12-2024 19:22:19","02-12-2024 20:23:2=
0","Site went down due to Grid bad voltage,and Gen failed to start  due to =
Grid bad voltage //he bypassed Grid and started the Gen ","Fabrice Pouakam"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Site went down due to Grid bad voltage,and Gen failed to start  due to Grid=
 bad voltage //he bypassed Grid and started the Gen ","alexandre.kamal@ihst=
owers.com","785","02-12-2024 19:35:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003742383","Emana ly=
cee 2","","02-12-2024 19:34:41","02-12-2024 18:59:38","02-12-2024 19:27:03"=
,"Cascaded Incident from TTO3681164","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen stopped with alarm under frequency // Grid Restored","system","2846=
31","02-12-2024 19:34:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003742381","EMANA BI=
LICK CITY","","02-12-2024 19:34:40","02-12-2024 18:59:38","02-12-2024 19:27=
:03","Cascaded Incident from TTO3681164","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage site went down =
because Gen stopped with alarm under frequency // Grid Restored","system","=
284632","02-12-2024 19:34:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003742382","Messassi=
 okolo","","02-12-2024 19:34:40","02-12-2024 18:59:38","02-12-2024 19:27:03=
","Cascaded Incident from TTO3681164","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen stopped with alarm under frequency // Grid Restored","system","284=
631","02-12-2024 19:34:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003742372","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_279, IHS_YND_685","02-12-2024 19:3=
2:46","02-12-2024 18:59:38","02-12-2024 19:27:03","Grid outage site went do=
wn because Gen stopped with alarm under frequency // Grid Restored","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage site went down because Gen stopped with alarm under frequency /=
/ Grid Restored","alexandre.kamal@ihstowers.com","1989","02-12-2024 19:32:4=
6","Sagemcom CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0003742370","S=
oa-Sofamac","","02-12-2024 19:30:58","02-12-2024 19:05:38","02-12-2024 20:3=
2:26","Site went down due to PWC Dysfuntioinning on SIte// He started Gen m=
anually","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Site went down due to PWC Dysfuntioinning on SIte// H=
e started Gen manually","alexandre.kamal@ihstowers.com","1520","02-12-2024 =
19:30:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0003742369","S=
cience","","02-12-2024 19:30:18","02-12-2024 19:07:05","02-12-2024 19:08:28=
","Error ticket","TIENTCHEU NZETCHIEU GAEL","Incorrectly Logged Tickets","E=
rror","Error","Error","Error ticket","alexandre.kamal@ihstowers.com","1394"=
,"02-12-2024 19:30:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003742366","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","02-12-2024 19:29:46","02-12-2024 19:=
10:41","02-12-2024 20:39:05","Grid fluctuation, site went down because Gen =
start and stopped due to Grid bad voltage // Gen manually started","Fanda B=
rice","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, site went down because Gen start and stopped due to =
Grid bad voltage // Gen manually started","alexandre.kamal@ihstowers.com","=
1147","02-12-2024 19:29:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003742363","S=
OA UNIVERSITY STADIUM","","02-12-2024 19:29:19","02-12-2024 19:20:12","02-1=
2-2024 21:09:56","Grid outage ,site went down because  New Gen malfunction/=
/He started Gen manually","Siligap Boris","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage ,site went down because  New Gen=
 malfunction//He started Gen manually","alexandre.kamal@ihstowers.com","547=
","02-12-2024 19:29:19","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003742313","ODZ=
A CITE MBIA","","02-12-2024 19:19:28","02-12-2024 19:00:15","02-12-2024 19:=
44:59","Grid Outage Site went down due to ATS Dysfuntionning on Site//He Re=
set it and Site is on Grid","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","ATS-AMF Issue","Grid Outage Site went down due to ATS Dysfun=
tionning on Site//He Reset it and Site is on Grid","kamga.virgile@ihstowers=
.com","1154","02-12-2024 19:19:28","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003742277","MAN=
GUIERS CHAPELLE","","02-12-2024 19:15:11","02-12-2024 18:56:00","02-12-2024=
 19:17:13","Grid outage, site went down before Gen start due to poor backup=
// Grid power return","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site went down before=
 Gen start due to poor backup// Grid power return","kamga.virgile@ihstowers=
.com","2681","02-12-2024 19:15:11","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003742259","Ema=
na","","02-12-2024 19:13:01","02-12-2024 18:58:48","02-12-2024 19:24:11","G=
rid outage,site went down because Gen failed to start due to gen card dysfu=
nction// Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid outage,site went down because Gen failed =
to start due to gen card dysfunction// Grid return","kamga.virgile@ihstower=
s.com","854","02-12-2024 19:13:01","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003742250","NYO=
M 2 IHS","","02-12-2024 19:11:45","02-12-2024 18:55:31","02-12-2024 19:15:0=
2","Grid outage ,Site went down because No Main Gen on site at the moment /=
/ Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Generator Faulty","Grid outage ,Site went down because No Main Gen on=
 site at the moment // Grid return","kamga.virgile@ihstowers.com","975","02=
-12-2024 19:11:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003741969","M=
VAN SACEL","","02-12-2024 18:46:21","02-12-2024 18:32:16","02-12-2024 20:36=
:22","Grid outage, site went down before gen start due to poor battery back=
up//Gen started manually","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup//Gen started manually","alexandre.k=
amal@ihstowers.com","846","02-12-2024 18:46:21","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003741884","Elo=
umdem stade","","02-12-2024 18:36:10","02-12-2024 18:26:01","03-12-2024 00:=
18:03","Active//No power issue site on grid with U=3D54.5v Georges(69746181=
4)from Huawei is informed","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue=
 site on grid with U=3D54.5v Georges(697461814)from Huawei is informed","ka=
mga.virgile@ihstowers.com","610","02-12-2024 18:36:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003741729","C=
omplexe-BEAC","","02-12-2024 18:16:07","02-12-2024 18:05:03","02-12-2024 18=
:54:44","Grid Outage Site went down because Gen Failed to Start due to PSC3=
 dysfuntionning// he restart it and Manuallly Started The Gen ","Albran Byo=
rel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid Out=
age Site went down because Gen Failed to Start due to PSC3 dysfuntionning//=
 he restart it and Manuallly Started The Gen ","alexandre.kamal@ihstowers.c=
om","665","02-12-2024 18:16:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003741607","Eseka To=
wn","","02-12-2024 17:52:12","02-12-2024 17:27:41","03-12-2024 00:00:11","A=
CTIVE //No power issue U=3D49.9V site on Gen The Tx FME Etienne FOPA /69503=
3981/ From HUAWEI is informed","Kemeni Franklin","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE //No po=
wer issue U=3D49.9V site on Gen The Tx FME Etienne FOPA /695033981/ From HU=
AWEI is informed","system","1471","02-12-2024 17:52:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003741542","E=
seka OCM","","02-12-2024 17:44:46","02-12-2024 17:27:41","03-12-2024 00:11:=
42","ACTIVE //No power issue U=3D49.9V site on Gen The Tx FME Etienne FOPA =
/695033981/ From HUAWEI is informed","Kemeni Franklin","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE /=
/No power issue U=3D49.9V site on Gen The Tx FME Etienne FOPA /695033981/ F=
rom HUAWEI is informed","alexandre.kamal@ihstowers.com","1026","02-12-2024 =
17:44:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003741304","N=
sam Sofavinc T0","","02-12-2024 17:09:01","02-12-2024 16:59:52","02-12-2024=
 17:11:57","Site went down due to Works  Pierre adijono (677 513091) FRom  =
Loumade are working On Site  ( sawap de PWC & Gen)//end Off Work","MINKA NI=
COLAS","Equipment Replacement","Passive","Planned Activity","Planned Activi=
ty - Passive","Site went down due to Works  Pierre adijono (677 513091) FRo=
m  Loumade are working On Site  ( sawap de PWC & Gen)//end Off Work","alexa=
ndre.kamal@ihstowers.com","550","02-12-2024 17:09:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0003741039","E=
mana Lycee","","02-12-2024 16:49:25","02-12-2024 16:34:21","03-12-2024 00:1=
5:21","Active//No power issue on site, Site on Grid UBAIE=3D56.3V synphorie=
n (675295205) From huawei is informed and UP at =3D07:27 PM","Fabrice Pouak=
am","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue on site, Site on Grid UBAIE=3D56.3V =
synphorien (675295205) From huawei is informed and UP at =3D07:27 PM","alex=
andre.kamal@ihstowers.com","905","02-12-2024 16:49:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_311","IHS_YND_453","NOCINC0003740821","S=
ong-bong","","02-12-2024 16:23:33","02-12-2024 16:14:29","03-12-2024 01:00:=
58","No power issue  site on Gen  TX fme etienne / 695033981 from huawei is=
 informed.","Kemeni Franklin","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue  site on Gen  TX f=
me etienne / 695033981 from huawei is informed.","alexandre.kamal@ihstowers=
.com","545","02-12-2024 16:23:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003740722","Akak-Nko=
zoa-MTN-IHS","","02-12-2024 16:09:00","02-12-2024 15:44:49","02-12-2024 16:=
00:31","Cascaded Incident from TTO3679219","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down due to wor=
k DJOUFACK PROSPER//672 13 61 56/ from ANCHOR is working on site (Normaliza=
tion cable Power) // End of work","system","267754","02-12-2024 16:09:00","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003740720","S=
oa-II","IHS_YND_316, IHS_YND_324","02-12-2024 16:07:54","02-12-2024 15:44:4=
9","02-12-2024 16:00:31","Site went down due to work DJOUFACK PROSPER//672 =
13 61 56/ from ANCHOR is working on site (Normalization cable Power) // End=
 of work","Siligap Boris","Equipment Replacement","Passive","Planned Activi=
ty","Planned Activity - Passive","Site went down due to work DJOUFACK PROSP=
ER//672 13 61 56/ from ANCHOR is working on site (Normalization cable Power=
) // End of work","alexandre.kamal@ihstowers.com","1385","02-12-2024 16:07:=
54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003740533","L=
abogenie","","02-12-2024 15:44:06","02-12-2024 15:32:57","02-12-2024 23:11:=
58","Active//No power issue on site, Site on Grid UBAIE=3D54.6V and Geoges =
(697461814) From huawei is informed and Site Up AT=3D04:02 PM","","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site, Site on Grid UBAIE=3D54.6V and Geoges (6=
97461814) From huawei is informed and Site Up AT=3D04:02 PM","alexandre.kam=
al@ihstowers.com","670","02-12-2024 15:44:06","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003739826","Ema=
na","","02-12-2024 14:00:10","02-12-2024 13:46:32","02-12-2024 14:06:40",""=
,"Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage site went down because Gen stopped with alarm under fre=
quency // He reset the Gen card and Gen manually started","landry.etame@ihs=
towers.com","618083","02-12-2024 14:00:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003739803","Messassi=
 okolo","","02-12-2024 13:56:21","02-12-2024 13:46:32","02-12-2024 14:10:09=
","Cascaded Incident from TTO3678078","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen stopped with alarm under frequency // He reset the Gen card and Ge=
n manually started","system","267273","02-12-2024 13:56:21","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_267","NOCINC0003739804","Mimboman-Village=
","","02-12-2024 13:56:21","","","Incorrectly Logged Tickets","Mba Lazare H=
erve","","","","","","system","589","02-12-2024 13:56:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003739805","Emana ly=
cee 2","","02-12-2024 13:56:21","02-12-2024 13:46:32","02-12-2024 14:10:09"=
,"Cascaded Incident from TTO3678078","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen stopped with alarm under frequency // He reset the Gen card and Gen=
 manually started","system","267273","02-12-2024 13:56:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003739802","Emana Ly=
cee","","02-12-2024 13:56:20","02-12-2024 13:46:32","02-12-2024 14:10:09","=
Cascaded Incident from TTO3678078","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage site went down becaus=
e Gen stopped with alarm under frequency // He reset the Gen card and Gen m=
anually started","system","267272","02-12-2024 13:56:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003739801","Mballa 4=
","","02-12-2024 13:56:20","02-12-2024 13:46:32","02-12-2024 14:10:09","Cas=
caded Incident from TTO3678078","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n stopped with alarm under frequency // He reset the Gen card and Gen manua=
lly started","system","267272","02-12-2024 13:56:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003739728","O=
kolo","IHS_YND_242, IHS_YND_274, IHS_YND_279, IHS_YND_246, IHS_YND_685","02=
-12-2024 13:53:50","02-12-2024 13:46:32","02-12-2024 14:10:09","Grid outage=
 site went down because Gen stopped with alarm under frequency // He reset =
the Gen card and Gen manually started","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down be=
cause Gen stopped with alarm under frequency // He reset the Gen card and G=
en manually started","stephane.nkamwa@ihstowers.com","439","02-12-2024 13:5=
3:50","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003739642","NYO=
M FACE MAETUR","","02-12-2024 13:40:28","02-12-2024 13:32:22","02-12-2024 2=
3:39:15","Grid Outage landlord has forbiden to start the Gen due to Noise//=
 Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Emergency Stop","Grid Outage landlord has forbiden to start the Gen =
due to Noise// Grid Restored","landry.etame@ihstowers.com","487","02-12-202=
4 13:40:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003739611","A=
bom","IHS_YND_269","02-12-2024 13:35:39","02-12-2024 13:29:28","02-12-2024 =
13:45:50","Grid Outage, site went down because Gen stopped with ""high temp=
"" alarm// He added water and started Gen manualy","Siligap Boris","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Is=
sue","Grid Outage, site went down because Gen stopped with ""high temp"" al=
arm// He added water and started Gen manualy","stephane.nkamwa@ihstowers.co=
m","500","02-12-2024 13:35:39","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003738769","ODZ=
A MINKAN EDIBI ASSI","","02-12-2024 11:29:19","02-12-2024 11:19:15","02-12-=
2024 12:39:11","Site went down because  Njoya mouhamed//658849259  from LOU=
MADE is working on site (Swap PWC)","Albran Byorel","Installation Activity"=
,"Passive","Planned Activity","Installation Activity","Site went down becau=
se Njoya mouhamed//658849259  from LOUMADE is working on site (Swap PWC)","=
landry.etame@ihstowers.com","605","02-12-2024 11:29:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003738150","O=
lembe-Terminus","","02-12-2024 10:06:20","02-12-2024 09:58:14","02-12-2024 =
11:06:26","Grid outage, Site went down because New Gen installed has not Ba=
ttery // He started Gen manualy with external battery","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outa=
ge, Site went down because New Gen installed has not Battery // He started =
Gen manualy with external battery","stephane.nkamwa@ihstowers.com","488","0=
2-12-2024 10:06:20","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0003738008","Bon=
djock","","02-12-2024 09:50:56","02-12-2024 09:43:31","02-12-2024 09:51:51"=
,"Grid outage,site went down before gen starts due to poor battery backup//=
Grid return","Fanda Brice","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage,site went down before gen starts du=
e to poor battery backup//Grid return","landry.etame@ihstowers.com","446","=
02-12-2024 09:50:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003737065","C=
omplexe-BEAC","","02-12-2024 08:01:55","02-12-2024 07:53:46","02-12-2024 08=
:45:22","Grid outage, Site went down because Gen started and stopped with a=
larm overvoltage// He reset Gen card and started Gen manualy","Albran Byore=
l","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid out=
age, Site went down because Gen started and stopped with alarm overvoltage/=
/ He reset Gen card and started Gen manualy","stephane.nkamwa@ihstowers.com=
","490","02-12-2024 08:01:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003737046","C=
rf-Nsam","","02-12-2024 07:58:41","02-12-2024 07:51:35","02-12-2024 08:05:5=
7","Site went down due to PWC overload ( 24 kw, 270 A)// he reduice the Loa=
d and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Site went down due to PWC overload ( 24 kw, 270 A)//=
 he reduice the Load and Site is on Grid","stephane.nkamwa@ihstowers.com","=
427","02-12-2024 07:58:41","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0003736534","Jou=
vence Mbenda","","02-12-2024 06:30:37","02-12-2024 06:25:47","02-12-2024 08=
:04:05","Grid outage.gen start and stopped due to ""high temp"" alarm//we a=
dd water and gen manually started ","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Radiator","Grid outage.gen start and stopped due =
to ""high temp"" alarm//we add water and gen manually started ","landry.eta=
me@ihstowers.com","291","02-12-2024 06:30:37","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003736517","Elo=
umdem stade","","02-12-2024 06:27:10","02-12-2024 06:24:07","02-12-2024 06:=
30:06","No power issue site on grid with U=3D54.5v Georges(697461814)from H=
uawei is informed","Fanda Brice","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wi=
th U=3D54.5v Georges(697461814)from Huawei is informed","landry.etame@ihsto=
wers.com","184","02-12-2024 06:27:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003736219","A=
WAE OCM","","02-12-2024 05:13:33","02-12-2024 05:11:30","02-12-2024 05:14:3=
0","Site went down due to PWC overload(12K, 200A) // site stabilized","Mba =
Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module Ov=
erloaded","Site went down due to PWC overload(12K, 200A) // site stabilized=
","rouselle.schoune@ihstowers.com","124","02-12-2024 05:13:33","Sagemcom CM=
R"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003735965","Nom=
ayos montee Meche","","02-12-2024 03:56:56","02-12-2024 03:51:14","02-12-20=
24 05:33:20","Grid outage, site went down because the bay DPC disfunctionni=
ng//He blocked the PWC DPC, Site on Grid","Fanda Brice","Equipment Repair",=
"Passive","Control Panel","Panel Distribution Board","Grid outage, site wen=
t down because the bay DPC disfunctionning//He blocked the PWC DPC, Site on=
 Grid","denis.mballa@ihstowers.com","343","02-12-2024 03:56:56","Sagemcom C=
MR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0003735809","Mon=
tee Jouvence","","02-12-2024 02:45:10","02-12-2024 01:04:02","02-12-2024 03=
:00:43","Grid outage, site went down because Gen failed to start due to Gen=
 battery discharged// He started Gen with external battery (investigation o=
ngoing)","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - G=
enerator Battery","Grid outage, site went down because Gen failed to start =
due to Gen battery discharged// He started Gen with external battery (inves=
tigation ongoing)","alwine.fambou@ihstowers.com","6069","02-12-2024 02:45:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_255","IHS_YND_286","NOCINC0003735788","D=
agobert","","02-12-2024 02:37:03","02-12-2024 02:33:00","02-12-2024 03:12:4=
3","Grid Outage, site went down because Gen started and stopped due to High=
 temp// He added water and started Gen manualy","TIENTCHEU NZETCHIEU GAEL",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","Grid Outage, site went down because Gen started and stopped d=
ue to High temp// He added water and started Gen manualy","rouselle.schoune=
@ihstowers.com","244","02-12-2024 02:37:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0003735708","SAA 2","=
","02-12-2024 01:57:50","02-12-2024 01:51:24","02-12-2024 04:01:27","Cascad=
ed Incident from TTO3673535","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage site went down because Gen fa=
iled to start due to Gen battery faulty // Gen manually started with extern=
al battery","system","274313","02-12-2024 01:57:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003735706","S=
aa","IHS_YND_401, IHS_YND_404","02-12-2024 01:56:29","02-12-2024 01:51:24",=
"02-12-2024 04:01:27","Grid outage site went down because Gen failed to sta=
rt due to Gen battery faulty // Gen manually started with external battery"=
,"Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Generator =
Battery","Grid outage site went down because Gen failed to start due to Gen=
 battery faulty // Gen manually started with external battery","rouselle.sc=
houne@ihstowers.com","306","02-12-2024 01:56:29","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0003735438","UPA=
C LP","","02-12-2024 00:32:19","01-12-2024 23:43:05","02-12-2024 04:50:33",=
"No power issue on site Ubaie=3D55,2V site on Grid The tx fme Armand nguets=
a(691144412) is informed","","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie=3D55,=
2V site on Grid The tx fme Armand nguetsa(691144412) is informed","alwine.f=
ambou@ihstowers.com","2955","02-12-2024 00:32:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003735388","O=
lembe-Terminus","","02-12-2024 00:12:15","02-12-2024 00:06:59","02-12-2024 =
01:50:21","Grid outage, Site went down because New Gen installed has not Ba=
ttery // He started Gen manualy with external battery","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outa=
ge, Site went down because New Gen installed has not Battery // He started =
Gen manualy with external battery","rouselle.schoune@ihstowers.com","317","=
02-12-2024 00:12:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003735188","L=
abogenie","","01-12-2024 23:17:50","01-12-2024 23:12:43","02-12-2024 00:59:=
26","No power issue on site U=3D54.5v site on grid tx fme Georges of huawei=
 is informed. Repetitive issue","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
4.5v site on grid tx fme Georges of huawei is informed. Repetitive issue","=
rouselle.schoune@ihstowers.com","308","01-12-2024 23:17:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003734873","B=
iteng-Maetur","","01-12-2024 22:01:43","01-12-2024 21:35:30","01-12-2024 21=
:36:55","Error ticket","Mba Lazare Herve","Incorrectly Logged Tickets","Err=
or","Error","Error","Error ticket","olivier.kwedi@ihstowers.com","1574","01=
-12-2024 22:01:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003734823","M=
IMBOMAN LIBERTE","","01-12-2024 21:50:47","01-12-2024 21:42:19","01-12-2024=
 22:00:19","Grid Outage ;site went down because Main Gen faulty // MDG 20 K=
va has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Faulty","Grid Outage ;site went down because Main Gen fa=
ulty // MDG 20 Kva has deployed","olivier.kwedi@ihstowers.com","509","01-12=
-2024 21:50:47","Sagemcom CMR"
"Closed Complete","Warning","CTR_209","IHS_YND_070","NOCINC0003734421","Efo=
ulan","","01-12-2024 21:01:49","","","Site went alarm due to inssuficiency =
of rectifier // site stabilized ","MINKA NICOLAS","Warning","Warning","POWE=
R","Warning - Rectifier Module","Site went alarm due to inssuficiency of re=
ctifier // site stabilized ","ludivine.ngamaleu@ihstowers.com","985","01-12=
-2024 21:01:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003734256","T=
amtam Weekend","","01-12-2024 20:31:08","01-12-2024 20:23:52","01-12-2024 2=
1:40:57","No power issue, site is on Grid with Ubaie=3D53,3  V  The TX FME =
Mbah Hosiah (674007438)  from Huawei is informed, Notice that we have disju=
nction at BTS OCM","Hyemafo Gildas","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on =
Grid with Ubaie=3D53,3  V  The TX FME Mbah Hosiah (674007438)  from Huawei =
is informed, Notice that we have disjunction at BTS OCM","olivier.kwedi@ihs=
towers.com","436","01-12-2024 20:31:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003734061","ELOUMDEM=
 CARRIERE 2","","01-12-2024 19:58:40","01-12-2024 19:53:39","01-12-2024 19:=
58:52","Cascaded Incident from TTO3671588","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Gen start and stopped due to Grid bad voltage // Gen manually s=
tarted","system","267108","01-12-2024 19:58:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003734055","Eto koss=
 Yde","","01-12-2024 19:58:00","01-12-2024 19:53:39","01-12-2024 19:58:52",=
"Cascaded Incident from TTO3671588","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Gen start and stopped due to Grid bad voltage // Gen manually started"=
,"system","267108","01-12-2024 19:58:00","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003734051","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","01-12-2024 19:57:18","01-12-2024 19:53=
:39","01-12-2024 19:58:52","Grid fluctuation, site went down because Gen st=
art and stopped due to Grid bad voltage // Gen manually started","Fanda Bri=
ce","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because Gen start and stopped due to Gr=
id bad voltage // Gen manually started","dorothy.djantio@ihstowers.com","22=
0","01-12-2024 19:57:18","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003733841","MIM=
BOMAN LIBERTE","","01-12-2024 19:45:00","01-12-2024 19:39:21","01-12-2024 1=
9:58:41","Grid Outage ;site went down because Main Gen faulty // MDG 20 Kva=
 has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid Outage ;site went down because Main Gen faul=
ty // MDG 20 Kva has deployed","dorothy.djantio@ihstowers.com","374","01-12=
-2024 19:45:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003733265","A=
bom","IHS_YND_269","01-12-2024 18:29:36","01-12-2024 18:21:32","01-12-2024 =
20:11:42","Grid outage, site went down because gen started and stopped due =
to a screw on the gen fuel line broke // he blocked it and started the gen =
manually.","Siligap Boris","Fuel Outage (Probable)","Passive","Diesel","Fue=
l Line Issue","Grid outage, site went down because gen started and stopped =
due to a screw on the gen fuel line broke // he blocked it and started the =
gen manually.","olivier.kwedi@ihstowers.com","485","01-12-2024 18:29:36","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0003733249","M=
vog-Ebanda","","01-12-2024 18:26:50","01-12-2024 18:21:32","02-12-2024 13:4=
5:50","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Grid outage, site went down because gen started and stopped d=
ue to a screw on the gen fuel line broke // he blocked it and started the g=
en manually.","olivier.kwedi@ihstowers.com","344367","01-12-2024 18:26:50",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003733076","MBI=
MBIM","","01-12-2024 18:00:39","01-12-2024 17:53:54","01-12-2024 19:58:18",=
"Hybrid Gen Site: site went down because of the dysfunctioning of hybrid sy=
stem // He reset Gen card and started Gen","Parker Tchoup","Equipment Repai=
r","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: site went down beca=
use of the dysfunctioning of hybrid system // He reset Gen card and started=
 Gen","dorothy.djantio@ihstowers.com","406","01-12-2024 18:00:39","Sagemcom=
 CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003733051","ODZ=
A MINKAN EDIBI ASSI","","01-12-2024 17:56:01","01-12-2024 17:46:58","01-12-=
2024 23:46:24","Site went down due to work: Njoya mouhamed//658849259  from=
 LOUMADE is working on site (Swap PWC)// End of work","Albran Byorel","Inst=
allation Activity","Passive","Planned Activity","Installation Activity","Si=
te went down due to work: Njoya mouhamed//658849259  from LOUMADE is workin=
g on site (Swap PWC)// End of work","dorothy.djantio@ihstowers.com","544","=
01-12-2024 17:56:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003733048","Ebeba","=
","01-12-2024 17:54:50","01-12-2024 17:46:25","01-12-2024 17:52:25","Cascad=
ed Incident from TTO3670371","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site ,site on Grid with Ubai=
e=3D52 V The TX FME Etienne(695033981) from Huawei is informed.","system","=
267344","01-12-2024 17:54:50","Sagemcom CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0003733047","Nke=
ng likok","IHS_YND_339","01-12-2024 17:54:09","01-12-2024 17:46:25","01-12-=
2024 19:25:25","No power issue on site ,site on Grid with Ubaie=3D52 V The =
TX FME Etienne(695033981) from Huawei is informed.","Kemeni Franklin","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site ,site on Grid with Ubaie=3D52 V The TX FME Et=
ienne(695033981) from Huawei is informed.","dorothy.djantio@ihstowers.com",=
"465","01-12-2024 17:54:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003732963","N=
yom OCM","","01-12-2024 17:35:34","01-12-2024 17:30:49","01-12-2024 18:40:3=
4","Site went down due to Grid bad voltage,and Gen failed to start  due to =
Grid bad voltage //he bypassed Grid and started the Gen ","Fabrice Pouakam"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Site went down due to Grid bad voltage,and Gen failed to start  due to Grid=
 bad voltage //he bypassed Grid and started the Gen ","olivier.kwedi@ihstow=
ers.com","286","01-12-2024 17:35:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_148","IHS_YND_724","NOCINC0003732341","B=
IYEMASSI NIKI","","01-12-2024 15:46:25","01-12-2024 15:44:28","01-12-2024 1=
6:38:09","Site went down due to PWC overloaded (12kva 250 A) //Site stabili=
zed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier M=
odule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Sit=
e stabilized","olivier.kwedi@ihstowers.com","118","01-12-2024 15:46:25","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0003732250","N=
goum","","01-12-2024 15:32:04","01-12-2024 15:04:10","01-12-2024 17:41:23",=
",  No power issue site on Solar, with U=3D51V   The Tx Fme Gregoire (65454=
7479) from Huawei informed .","Parker Tchoup","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm"," No power issue s=
ite on Solar, with U=3D51V   The Tx Fme Gregoire (654547479) from Huawei in=
formed .","olivier.kwedi@ihstowers.com","1675","01-12-2024 15:32:04","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0003732131","Nkoabang=
2","","01-12-2024 15:13:10","01-12-2024 14:31:24","01-12-2024 15:38:56","Ca=
scaded Incident from TTO3669228","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage ,site went down becaus=
e Gen started and stopped due to Gen OVERLOAD (16.KVA,150 A)// He reduced t=
he load ","system","286216","01-12-2024 15:13:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003732118","N=
koabang","IHS_YND_295, IHS_YND_526","01-12-2024 15:12:23","01-12-2024 14:31=
:24","01-12-2024 15:38:56","Grid outage ,site went down because Gen started=
 and stopped due to Gen OVERLOAD (16.KVA,150 A)// He reduced the load ","Mb=
a Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage ,site went down because Gen started and stopped due to Gen OVER=
LOAD (16.KVA,150 A)// He reduced the load ","olivier.kwedi@ihstowers.com","=
2460","01-12-2024 15:12:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003732070","N=
GONA","","01-12-2024 15:06:23","01-12-2024 14:31:24","01-12-2024 15:38:56",=
"please cascaded this ticked behind Nkoabang OCM","Mba Lazare Herve","Casca=
de Outage","Passive","Cascade Passive","Cascade Passive","Grid outage ,site=
 went down because Gen started and stopped due to Gen OVERLOAD (16.KVA,150 =
A)// He reduced the load ","olivier.kwedi@ihstowers.com","7117","01-12-2024=
 15:06:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003732033","O=
mnisport-Rail","","01-12-2024 15:01:07","01-12-2024 14:24:07","01-12-2024 1=
5:30:32","Site went down because CB(80A) tripped in Dcbox who feeds equipme=
nts OCM causing by load increase on site // He replaced  with another CB(12=
5A),Site on Grid ","Delor Telezing","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Circuit Breaker Issue","Site went down because CB(80=
A) tripped in Dcbox who feeds equipments OCM causing by load increase on si=
te // He replaced  with another CB(125A),Site on Grid ","olivier.kwedi@ihst=
owers.com","2221","01-12-2024 15:01:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003731856","Crf-Mban=
kolo-IHS","","01-12-2024 14:41:10","01-12-2024 14:30:06","01-12-2024 15:51:=
14","Cascaded Incident from TTO3668888","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down due to work Tea=
m Yamna/695934760/OPUS/:swapp of Gen and PWC //End of work	","system","2719=
71","01-12-2024 14:41:10","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003731831","Jea=
n Vespa","IHS_YND_574","01-12-2024 14:38:01","01-12-2024 14:30:06","01-12-2=
024 15:51:14","site went down due to work Team Yamna/695934760/OPUS/:swapp =
of Gen and PWC //End of work	","Mboua Thierry","Installation Activity","Pas=
sive","Planned Activity","Installation Activity","site went down due to wor=
k Team Yamna/695934760/OPUS/:swapp of Gen and PWC //End of work	","dorothy.=
djantio@ihstowers.com","476","01-12-2024 14:38:01","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003731800","MAN=
GUIERS CHAPELLE","","01-12-2024 14:35:21","01-12-2024 14:18:23","01-12-2024=
 15:05:55","Grid outage, site went down before gen start due to poor batter=
y backup // Gen started automatically","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // Gen started autom=
atically","dorothy.djantio@ihstowers.com","2286","01-12-2024 14:35:21","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003731665","N=
kolondom","","01-12-2024 14:12:55","01-12-2024 13:55:57","01-12-2024 14:41:=
54","Grid outage,site went down because Gen fails to start due to  ATS is n=
ot  normalized  on site //He started Gen manuaally","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,site w=
ent down because Gen fails to start due to  ATS is not  normalized  on site=
 //He started Gen manuaally","alexandre.kamal@ihstowers.com","1020","01-12-=
2024 14:12:55","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003731567","NYO=
M FACE MAETUR","","01-12-2024 14:02:21","01-12-2024 13:42:14","01-12-2024 1=
5:07:05","Grid Outage landlord has forbiden to start the Gen Because the No=
ise Waiting Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Emergency Stop","Grid Outage landlord has forbiden to sta=
rt the Gen Because the Noise Waiting Grid Restored","landry.etame@ihstowers=
.com","1208","01-12-2024 14:02:21","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003731075","MIM=
BOMAN LIBERTE","","01-12-2024 12:43:43","01-12-2024 12:33:42","01-12-2024 1=
2:54:11","Grid Outage Site went Down due to Main Gen Faulty// MDG of 20 Kva=
 has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid Outage Site went Down due to Main Gen Faulty=
// MDG of 20 Kva has deployed","landry.etame@ihstowers.com","602","01-12-20=
24 12:43:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003729795","Nkolo II=
 New","","01-12-2024 10:59:50","01-12-2024 10:47:13","01-12-2024 11:49:58",=
"Cascaded Incident from TTO3666689","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage Site went Down beca=
use Gen Failed to Start due to ATS Faulty on Site//Hre Manually Started The=
 Gen","system","757","01-12-2024 10:59:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003729786","M=
imboman-Village","IHS_YND_709","01-12-2024 10:58:23","01-12-2024 10:47:13",=
"01-12-2024 12:20:58","Grid Outage Site went Down because Gen Failed to Sta=
rt due to ATS Faulty on Site//Hre Manually Started The Gen","Mba Lazare Her=
ve","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid Outa=
ge Site went Down because Gen Failed to Start due to ATS Faulty on Site//Hr=
e Manually Started The Gen","alexandre.kamal@ihstowers.com","671","01-12-20=
24 10:58:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003729715","Crf-Mban=
kolo-IHS","","01-12-2024 10:43:50","01-12-2024 10:05:09","01-12-2024 10:50:=
07","Cascaded Incident from TTO3666563","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down due to work Tea=
m Yamna/695934760/OPUS/:swapp of Gen and PWC //End of work	","system","1222=
832","01-12-2024 10:43:50","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003729675","Jea=
n Vespa","IHS_YND_574","01-12-2024 10:41:36","01-12-2024 10:05:09","01-12-2=
024 10:50:07","site went down due to work Team Yamna/695934760/OPUS/:swapp =
of Gen and PWC //End of work	","Mboua Thierry","Equipment Replacement","Pas=
sive","Planned Activity","Planned Activity - Passive","site went down due t=
o work Team Yamna/695934760/OPUS/:swapp of Gen and PWC //End of work	","lan=
dry.etame@ihstowers.com","2187","01-12-2024 10:41:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003729072","N=
koabang2","","01-12-2024 09:04:12","01-12-2024 08:49:02","01-12-2024 09:46:=
07","Grid outage, site went down because Gen Start and Stop due to Under Vo=
ltage alarm// he reset the Gen card and started Gen manualy","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","Grid outage, site went down because Gen Start and Stop d=
ue to Under Voltage alarm// he reset the Gen card and started Gen manualy",=
"alexandre.kamal@ihstowers.com","911","01-12-2024 09:04:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003728824","M=
IMBOMAN LIBERTE","","01-12-2024 08:29:06","01-12-2024 08:23:00","01-12-2024=
 11:55:52","Grid Outage Site went Down due to Main Gen Faulty// MDG of 20 K=
va has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Faulty","Grid Outage Site went Down due to Main Gen Faul=
ty// MDG of 20 Kva has deployed","alexandre.kamal@ihstowers.com","367","01-=
12-2024 08:29:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003728787","S=
tade-Abega","","01-12-2024 08:22:12","01-12-2024 08:10:08","01-12-2024 09:0=
5:50","site down due to work of  /our Supervisor Judigael/656072620 / Sagem=
com (Normalization of power cable in the PWC)//end of work ","Mba Lazare He=
rve","Equipment Replacement","Passive","Planned Activity","Planned Activity=
 - Passive","site down due to work of  /our Supervisor Judigael/656072620 /=
 Sagemcom (Normalization of power cable in the PWC)//end of work ","alexand=
re.kamal@ihstowers.com","725","01-12-2024 08:22:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003728725","O=
lembe-Terminus","","01-12-2024 08:10:01","01-12-2024 08:00:52","01-12-2024 =
08:19:38","Grid outage site went down because Main gen faulty // Grid Resto=
red","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Faulty","Grid outage site went down because Main gen faulty // Grid R=
estored","alexandre.kamal@ihstowers.com","550","01-12-2024 08:10:01","Sagem=
com CMR"
"Closed Complete","Warning","","IHS_YND_116","NOCINC0003728649","Stade-Abeg=
a","","01-12-2024 07:59:49","","","Site alarming on battery becaus our Supe=
rvisor Judigael/656072620 / Sagemcom (Normalization of power cable in the P=
WC)//end of work","Mba Lazare Herve","Warning","Warning","POWER","Warning -=
 Site on Battery","Site alarming on battery becaus our Supervisor Judigael/=
656072620 / Sagemcom (Normalization of power cable in the PWC)//end of work=
","ludovic.tchagna@ihstowers.com","5","01-12-2024 07:59:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0003728165","Nkomkana=
","","01-12-2024 06:44:50","01-12-2024 04:32:55","01-12-2024 04:39:22","Cas=
caded Incident from TTO3664194","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","grid outage//MDG 20 kva deployed","system","7915","=
01-12-2024 06:44:50","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_333","NOCINC0003727898","Mfou MTN",=
"","01-12-2024 05:42:52","","","Site went alarm because gen fails to start =
due to grid bad voltage // gen start automatically","Mba Lazare Herve","War=
ning","Warning","POWER","Warning - Site on Battery","Site went alarm becaus=
e gen fails to start due to grid bad voltage // gen start automatically","j=
oelle.ekessi@ihstowers.com","64","01-12-2024 05:42:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003727598","C=
ite-Verte","IHS_YND_200, IHS_YND_543","01-12-2024 04:35:09","01-12-2024 04:=
32:55","01-12-2024 04:39:22","grid outage//MDG 20 kva deployed","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","grid outage//MD=
G 20 kva deployed","emmanuel.ghani@ihstowers.com","135","01-12-2024 04:35:0=
9","Sagemcom CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0003727590","E=
ntree Cite Verte","","01-12-2024 04:34:15","01-12-2024 04:32:55","01-12-202=
4 04:39:22","","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","grid outage//MDG 20 kva deployed","emmanuel.ghani@ihstowe=
rs.com","247","01-12-2024 04:34:15","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_202","NOCINC0003727512","Cite-Verte=
","","01-12-2024 03:55:54","","","grid outage//MDG 20 kva deployed","","War=
ning","Warning","POWER","Warning - Site on Battery","grid outage//MDG 20 kv=
a deployed","joelle.ekessi@ihstowers.com","65","01-12-2024 03:55:54","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003727480","M=
ontee-Des-Soeurs","","01-12-2024 03:45:00","01-12-2024 03:36:55","01-12-202=
4 03:45:49","Active no power issue, U=3D54V on grid: The TX FME Mbah Hosiah=
 (674007438) from Huawei is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active n=
o power issue, U=3D54V on grid: The TX FME Mbah Hosiah (674007438) from Hua=
wei is informed","emmanuel.ghani@ihstowers.com","486","01-12-2024 03:45:00"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0003727064","S=
oa-Sofamac","","01-12-2024 01:19:42","01-12-2024 01:13:34","01-12-2024 03:2=
1:22","Site went down due to work DJOUFACK PROSPER/672 13 61 56/  from ANCH=
OR is working on site  (Swap Baie and gen) // End of work","Siligap Boris",=
"Installation Activity","Passive","Planned Activity","Installation Activity=
","Site went down due to work DJOUFACK PROSPER/672 13 61 56/  from ANCHOR i=
s working on site  (Swap Baie and gen) // End of work","emmanuel.ghani@ihst=
owers.com","369","01-12-2024 01:19:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003726836","C=
rf Cornier","","01-12-2024 00:18:58","01-12-2024 00:11:31","01-12-2024 02:0=
0:01","no power issue, site is on grid with Ubaie=3D53V, George(697461814) =
from Jhuawei is informed","MINKA NICOLAS","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","no power issue, site =
is on grid with Ubaie=3D53V, George(697461814) from Jhuawei is informed","e=
mmanuel.ghani@ihstowers.com","7276","01-12-2024 00:18:58","Sagemcom CMR"
"Closed Complete","Site Down","T0579","IHS_YND_366","NOCINC0003726660","Man=
doumba MTN","IHS_YND_349","30-11-2024 23:52:06","30-11-2024 23:44:56","01-1=
2-2024 00:33:18","No power issue on site U=3D53v site on grid Tx Etienne of=
 huawei is informed","Kemeni Franklin","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53v site on grid Tx Etienne of huawei is informed","christian.fonkou@ihs=
towers.com","431","30-11-2024 23:52:06","Sagemcom CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0003726585","Nko=
ngtock","","30-11-2024 23:30:53","30-11-2024 23:44:56","01-12-2024 00:24:18=
","","Kemeni Franklin","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue on site U=3D53v site on grid Tx Etienne of huawei i=
s informed","christian.fonkou@ihstowers.com","765","30-11-2024 23:30:53","S=
agemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003726377","BIY=
EMASSI NIKI","","30-11-2024 22:52:09","30-11-2024 22:48:01","30-11-2024 23:=
21:25","Site went down due to PWC overloaded (12kva 250 A) //Site stabilize=
d","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC overloaded (12kva 250 A) //Site =
stabilized","christian.fonkou@ihstowers.com","248","30-11-2024 22:52:09","S=
agemcom CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0003726329","Nke=
ng likok","","30-11-2024 22:44:12","30-11-2024 22:41:05","01-12-2024 00:45:=
05","No power issue on site U=3D52v site on gen Tx Etienne of huawei is inf=
ormed up at 22:48","Kemeni Franklin","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D52v site on gen Tx Etienne of huawei is informed up at 22:48","christian=
.fonkou@ihstowers.com","188","30-11-2024 22:44:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003725970","B=
iyemassi LAC","","30-11-2024 21:49:11","30-11-2024 21:45:59","01-12-2024 01=
:15:13","Active, no power isssue, site on grid with u=3D53.4V, Tx fme Mbah =
hosiah/674007438 From Huawei is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power i=
sssue, site on grid with u=3D53.4V, Tx fme Mbah hosiah/674007438 From Huawe=
i is informed","olivier.kwedi@ihstowers.com","193","30-11-2024 21:49:11","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003725796","M=
ontee-Des-Soeurs","","30-11-2024 21:27:07","30-11-2024 18:49:52","30-11-202=
4 21:32:06","access issue during the night due to landloard,grid outage gen=
 failed to start//grid return(investigation ongoing)","Hyemafo Gildas","Acc=
ess Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land=
 Lord","access issue during the night due to landloard,grid outage gen fail=
ed to start//grid return(investigation ongoing)","olivier.kwedi@ihstowers.c=
om","9436","30-11-2024 21:27:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003725667","O=
lembe-Terminus","","30-11-2024 21:11:01","30-11-2024 18:14:45","30-11-2024 =
21:56:45","grid outage site went down because Main gen faulty // MDG of 20 =
Kva has deployed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Faulty","grid outage site went down because Main gen fau=
lty // MDG of 20 Kva has deployed","olivier.kwedi@ihstowers.com","10577","3=
0-11-2024 21:11:01","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003725523","Nom=
ayos montee Meche","","30-11-2024 20:48:23","30-11-2024 20:28:14","30-11-20=
24 22:28:56","Site went down Site down due to Work The Team Vela Invor // 6=
76492807 from Grattos working on site (Swap Gen )// End of work","Fanda Bri=
ce","Equipment Replacement","Passive","Planned Activity","Planned Activity =
- Passive","Site went down Site down due to Work The Team Vela Invor // 676=
492807 from Grattos working on site (Swap Gen )// End of work","rouselle.sc=
houne@ihstowers.com","1209","30-11-2024 20:48:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003725396","ELOUMDEM=
 CARRIERE 2","","30-11-2024 20:29:50","30-11-2024 20:21:04","30-11-2024 21:=
13:33","Cascaded Incident from TTO3661570","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Gen start and stopped due to Grid bad voltage // Gen manually s=
tarted","system","279753","30-11-2024 20:29:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003725395","Eto koss=
 Yde","","30-11-2024 20:29:50","30-11-2024 20:21:04","30-11-2024 21:13:33",=
"Cascaded Incident from TTO3661570","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Gen start and stopped due to Grid bad voltage // Gen manually started"=
,"system","279753","30-11-2024 20:29:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003725353","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","30-11-2024 20:23:11","30-11-2024 20:19=
:03","30-11-2024 21:13:59","Grid fluctuation, site went down because Gen st=
art and stopped due to Grid bad voltage // Gen manually started","Fanda Bri=
ce","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because Gen start and stopped due to Gr=
id bad voltage // Gen manually started","rouselle.schoune@ihstowers.com","3=
521","30-11-2024 20:23:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003725038","L=
abogenie","","30-11-2024 19:39:30","30-11-2024 15:24:05","30-11-2024 16:52:=
05","grid outage,no space to deploy a mobil gen//grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no sp=
ace to deploy a mobil gen//grid return","olivier.kwedi@ihstowers.com","2148=
8","30-11-2024 19:39:30","Sagemcom CMR"
"Cancelled","Warning","CTR_427","IHS_YND_200","NOCINC0003725021","Nkomkana"=
,"","30-11-2024 19:36:14","","","please cascaded this Ticket behind Cite ve=
rte","","","","","","","olivier.kwedi@ihstowers.com","9254","30-11-2024 19:=
36:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0003724997","E=
ntree Cite Verte","","30-11-2024 19:34:28","30-11-2024 17:13:19","30-11-202=
4 17:20:46","No power issue on site U=3D53v site on grid Brice Stague of hu=
awei is informed, Notice thad disjunction in OCM equipment","Paul BIBOUM","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue on site U=3D53v site on grid Brice Stague of huaw=
ei is informed, Notice thad disjunction in OCM equipment","olivier.kwedi@ih=
stowers.com","8470","30-11-2024 19:34:28","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003724775","AWA=
E OCM","","30-11-2024 19:08:36","30-11-2024 18:57:43","30-11-2024 21:33:43"=
,"site went down due to work Team Ronny/OPUS/695934760:swapp of Gen//End of=
 work","Mba Lazare Herve","Installation Activity","Passive","Planned Activi=
ty","Installation Activity","site went down due to work Team Ronny/OPUS/695=
934760:swapp of Gen//End of work","rouselle.schoune@ihstowers.com","9437","=
30-11-2024 19:08:36","Sagemcom CMR"
"Closed Complete","Site Down","T0236","IHS_YND_373","NOCINC0003724722","Mal=
oun","IHS_YND_330, IHS_YND_350","30-11-2024 19:04:45","30-11-2024 18:54:39"=
,"30-11-2024 19:25:22","No power issue on site ,site on Gen with Ubaie=3D54=
 V  The TX FME Etienne(695033981) from Huawei is   informed.","Kemeni Frank=
lin","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue on site ,site on Gen with Ubaie=3D54 V  The=
 TX FME Etienne(695033981) from Huawei is   informed.","rouselle.schoune@ih=
stowers.com","606","30-11-2024 19:04:45","Sagemcom CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0003724701","OKO=
A Peage","","30-11-2024 19:02:30","30-11-2024 18:54:39","30-11-2024 19:01:2=
2","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Act=
ive","No power issue on site ,site on Gen with Ubaie=3D54 V  The TX FME Eti=
enne(695033981) from Huawei is   informed.","rouselle.schoune@ihstowers.com=
","683","30-11-2024 19:02:30","Sagemcom CMR"
"Closed Complete","Site Down","T1579","IHS_YND_480","NOCINC0003724389","Sic=
 Cite Verte Matgenie","","30-11-2024 17:59:53","30-11-2024 17:53:47","30-11=
-2024 20:15:25","Grid outage, no space to deploy a mobile gen, //  grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid outage, no space to deploy a mobile gen, //  grid return","rouselle.s=
choune@ihstowers.com","367","30-11-2024 17:59:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003724241","Saa","",=
"30-11-2024 17:35:41","30-11-2024 17:24:13","30-11-2024 17:40:20","Cascaded=
 Incident from TTO3660203","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site Down due to work in the site // end wo=
rk","system","1225445","30-11-2024 17:35:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003724238","Nguila",=
"","30-11-2024 17:35:40","30-11-2024 17:24:13","30-11-2024 17:40:20","Casca=
ded Incident from TTO3660203","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site Down due to work in the site // end=
 work","system","1225440","30-11-2024 17:35:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0003724240","NTUI TOW=
N","","30-11-2024 17:35:40","30-11-2024 17:24:13","30-11-2024 17:40:20","Ca=
scaded Incident from TTO3660203","Parker Tchoup","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site Down due to work in the site // =
end work","system","1225445","30-11-2024 17:35:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_690","NOCINC0003724239","Ntui adm=
inistration","","30-11-2024 17:35:40","30-11-2024 17:24:13","30-11-2024 17:=
40:20","Cascaded Incident from TTO3660203","Parker Tchoup","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site Down due to work in th=
e site // end work","system","1225444","30-11-2024 17:35:40","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003724158","Nom=
ayos montee Meche","","30-11-2024 17:26:06","30-11-2024 17:18:44","30-11-20=
24 19:07:44","Site went down Site down due to Work  The Team Vela  Invor //=
 676492807 from Grattos working on site (Swap Gen )// End of work","Fanda B=
rice","Installation Activity","Passive","Planned Activity","Installation Ac=
tivity","Site went down Site down due to Work  The Team Vela  Invor // 6764=
92807 from Grattos working on site (Swap Gen )// End of work","rouselle.sch=
oune@ihstowers.com","442","30-11-2024 17:26:06","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003724132","Mok=
olo Yaounde","","30-11-2024 17:21:34","30-11-2024 17:16:24","30-11-2024 17:=
50:24","Grid outage, no space to deploy a mobile gen, // grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, no space to deploy a mobile gen, // grid return","rouselle.schoune@ihst=
owers.com","311","30-11-2024 17:21:34","Sagemcom CMR"
"Closed Complete","Site Down","T0460","IHS_YND_201","NOCINC0003723845","Cit=
e Verte","","30-11-2024 16:44:06","30-11-2024 16:41:56","30-11-2024 20:12:5=
6","Grid outage, no space to deploy a mobile gen, //  grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,=
 no space to deploy a mobile gen, //  grid return","rouselle.schoune@ihstow=
ers.com","130","30-11-2024 16:44:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003723763","S=
tade-Abega","","30-11-2024 16:36:18","30-11-2024 16:04:06","30-11-2024 22:5=
8:14","Site went down due to technician  Gildas (656040578) FROM ETECH PRO =
Sarl working from swapp PWC// End of work","Mba Lazare Herve","Equipment Re=
placement","Passive","Planned Activity","Planned Activity - Passive","Site =
went down due to technician  Gildas (656040578) FROM ETECH PRO Sarl working=
 from swapp PWC// End of work","olivier.kwedi@ihstowers.com","1933","30-11-=
2024 16:36:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003723616","M=
essa-Carriere OCM","","30-11-2024 16:18:54","30-11-2024 15:29:30","30-11-20=
24 20:10:30","grid outage,no space to deploy a mobil gen // Grid power retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid outage,no space to deploy a mobil gen // Grid power return","olivier.k=
wedi@ihstowers.com","2965","30-11-2024 16:18:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003723494","E=
lobi Mokolo","","30-11-2024 16:02:58","30-11-2024 14:36:42","30-11-2024 14:=
37:42","Active//No power issue on site Ubaie=3D55,2 V; site on Grid tx fme =
BRICE Tsague/ 650214096 from huawie is informed","Mboua Thierry","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site Ubaie=3D55,2 V; site on Grid tx fme BRICE =
Tsague/ 650214096 from huawie is informed","olivier.kwedi@ihstowers.com","5=
177","30-11-2024 16:02:58","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0003723438","Mam=
bine","","30-11-2024 15:53:28","30-11-2024 18:54:39","30-11-2024 19:25:22",=
"please cascaded this ticket behind Maloum","Fanda Brice","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue on site ,site on=
 Gen with Ubaie=3D54 V  The TX FME Etienne(695033981) from Huawei is   info=
rmed.","rouselle.schoune@ihstowers.com","63919","30-11-2024 15:53:28","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003723410","Nkolbiss=
on usines des eaux 2","","30-11-2024 15:49:00","30-11-2024 15:41:07","30-11=
-2024 15:49:07","Cascaded Incident from TTO3659278","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, site went down before Gen start due to poor backup// Grid return","sy=
stem","267814","30-11-2024 15:49:00","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003723404","Nko=
lbisson","IHS_YND_763","30-11-2024 15:47:16","30-11-2024 15:41:07","30-11-2=
024 15:49:07","Grid outage, site went down before Gen start due to poor bac=
kup// Grid return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before Gen start due to poor backup// Grid return","rouselle.schoune@ihstow=
ers.com","370","30-11-2024 15:47:16","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003723397","Bas=
tos Amb Coree","","30-11-2024 15:45:37","30-11-2024 15:39:27","30-11-2024 1=
7:19:29","grid outage,no space to deploy a mobil gen //Grid power return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid =
outage,no space to deploy a mobil gen //Grid power return","rouselle.schoun=
e@ihstowers.com","371","30-11-2024 15:45:37","Sagemcom CMR"
"Closed Complete","Site Down","T0579","IHS_YND_366","NOCINC0003723326","Man=
doumba MTN","","30-11-2024 15:37:31","30-11-2024 15:24:22","30-11-2024 18:3=
0:09","No power issue on site ,site on Grid with Ubaie=3D53.6 V.Site impact=
ed by Maloum","Kemeni Franklin","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","Affected by 3rd Party Site","No power issue on site =
,site on Grid with Ubaie=3D53.6 V.Site impacted by Maloum","rouselle.schoun=
e@ihstowers.com","790","30-11-2024 15:37:31","Sagemcom CMR"
"Cancelled","Warning","T1852","IHS_YND_335","NOCINC0003723245","Angongo",""=
,"30-11-2024 15:25:54","","","","Fanda Brice","","","","","","rouselle.scho=
une@ihstowers.com","250","30-11-2024 15:25:54","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003722917","Feb=
e Village","","30-11-2024 14:49:34","30-11-2024 14:32:33","30-11-2024 16:45=
:19","Grid outage, Site went because Gen started and stopped due to Alarm""=
 High temp""// He added water and started Gen manualy","Mboua Thierry","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Leve=
l Issue","Grid outage, Site went because Gen started and stopped due to Ala=
rm"" High temp""// He added water and started Gen manualy","rouselle.schoun=
e@ihstowers.com","2363","30-11-2024 14:49:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003722351","Essomba"=
,"","30-11-2024 13:56:36","30-11-2024 13:54:27","30-11-2024 13:59:27","Acti=
ve: No power issue, site is on Grid with Ubaie=3D54.2V,   The fme tx George=
 //697461814//from Huawei is informed. up at 13:59","Mba Lazare Herve","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active: No power issue, site is on Grid with Ubaie=3D54.2V,   The f=
me tx George //697461814//from Huawei is informed. up at 13:59","etienne.it=
ondo@ihstowers.com","130","30-11-2024 13:56:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003722347","Ebeba","=
","30-11-2024 13:56:00","30-11-2024 11:46:23","30-11-2024 11:50:37","Cascad=
ed Incident from TTO3657091","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by Maloun T0236","system","7777"=
,"30-11-2024 13:56:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0003722301","Nkeng li=
kok","","30-11-2024 13:50:32","30-11-2024 11:46:23","30-11-2024 11:50:37","=
Cascaded Incident from TTO3657091","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Site impacted by Maloun T0236","syst=
em","7449","30-11-2024 13:50:32","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003722240","NYO=
M 2 IHS","","30-11-2024 13:42:18","30-11-2024 13:30:08","30-11-2024 14:19:1=
9","Grid outage, site went down because Gen start and stopped with Over Vol=
tage alarm // He Reset the Gen Card and Manually Started the Gen","Fabrice =
Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage, site went down because Gen start and stopped with Over Voltage a=
larm // He Reset the Gen Card and Manually Started the Gen","dorothy.djanti=
o@ihstowers.com","731","30-11-2024 13:42:18","Sagemcom CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0003721861","Nko=
lfon Cimencam","","30-11-2024 12:51:39","30-11-2024 12:44:30","01-12-2024 0=
1:28:57","Active//No power issue on site U=3D54,5v site on Gen The Rm Alain=
 (691144423) of huawei is informed","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue on site U=3D54,5v site on Gen The Rm Alain (691144423) of huaw=
ei is informed","dorothy.djantio@ihstowers.com","430","30-11-2024 12:51:39"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003721824","Ako=
no","IHS_YND_687","30-11-2024 12:43:17","30-11-2024 12:39:11","30-11-2024 1=
2:41:46","Grid fluctuation, Site went down because Gen fails to start due G=
en card disfunction// He reset Gen and started Gen manualy","Fanda Brice","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid fluctua=
tion, Site went down because Gen fails to start due Gen card disfunction// =
He reset Gen and started Gen manualy","dorothy.djantio@ihstowers.com","247"=
,"30-11-2024 12:43:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0003721820","Nomayos-=
IHS","","30-11-2024 12:42:20","30-11-2024 11:46:23","30-11-2024 11:50:37","=
Cascaded Incident from TTO3657091","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Site impacted by Maloun T0236","system",=
"3357","30-11-2024 12:42:20","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003721693","OLA=
MA","","30-11-2024 12:28:32","30-11-2024 12:39:11","30-11-2024 12:41:46",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid fluctuation, Site went down because Gen fails to start due Gen car=
d disfunction// He reset Gen and started Gen manualy","dorothy.djantio@ihst=
owers.com","465","30-11-2024 12:28:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003721550","Nkongtoc=
k","","30-11-2024 12:02:40","30-11-2024 11:46:23","30-11-2024 11:50:37","Ca=
scaded Incident from TTO3657091","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Site impacted by Maloun T0236","system=
","977","30-11-2024 12:02:40","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003721359","NYO=
M 2 IHS","","30-11-2024 11:30:07","30-11-2024 10:56:16","30-11-2024 13:14:1=
7","Grid outage site went down because Gen failed to start with alarm over =
voltage // He reset the Gen card and reduced the load.site on Gen","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Gr=
id outage site went down because Gen failed to start with alarm over voltag=
e // He reset the Gen card and reduced the load.site on Gen","dorothy.djant=
io@ihstowers.com","6026","30-11-2024 11:30:07","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003721159","Nsi=
meyong Terre Rouge","","30-11-2024 11:00:05","30-11-2024 10:53:57","30-11-2=
024 11:05:30","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen started automatically","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen started auto=
matically","dorothy.djantio@ihstowers.com","370","30-11-2024 11:00:05","Sag=
emcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003721085","Feb=
e Village","","30-11-2024 10:48:09","30-11-2024 10:36:14","30-11-2024 11:43=
:34","Grid Outage, site went down because Gen stopped with ""high temp"" al=
arm// He added water and started Gen manualy","Mboua Thierry","Equipment Re=
pair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue",=
"Grid Outage, site went down because Gen stopped with ""high temp"" alarm//=
 He added water and started Gen manualy","dorothy.djantio@ihstowers.com","7=
487","30-11-2024 10:48:09","Sagemcom CMR"
"Closed Complete","Site Down","T0236","IHS_YND_373","NOCINC0003721083","Mal=
oun","IHS_YND_347, IHS_YND_339, IHS_YND_314, IHS_YND_349, IHS_YND_697","30-=
11-2024 10:47:01","30-11-2024 11:46:23","30-11-2024 11:50:37","No power iss=
ue on site ,site on Gen with Ubaie=3D54 V  The TX FME Etienne(695033981) fr=
om Huawei is   informed.","Kemeni Franklin","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite ,site on Gen with Ubaie=3D54 V  The TX FME Etienne(695033981) from Huaw=
ei is   informed.","dorothy.djantio@ihstowers.com","2862","30-11-2024 10:47=
:01","Sagemcom CMR"
"Cancelled","Warning","T2192","IHS_YND_783","NOCINC0003721075","Lobo 2","",=
"30-11-2024 10:44:22","","","","TIENTCHEU NZETCHIEU GAEL","","","","","","d=
orothy.djantio@ihstowers.com","488","30-11-2024 10:44:22","Sagemcom CMR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0003720967","Sou=
s Prefecture","","30-11-2024 10:28:28","30-11-2024 11:46:23","30-11-2024 11=
:50:37","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascad=
e Active","No power issue on site ,site on Gen with Ubaie=3D54 V  The TX FM=
E Etienne(695033981) from Huawei is   informed.","dorothy.djantio@ihstowers=
.com","3107","30-11-2024 10:28:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003720891","O=
lembe-Terminus","","30-11-2024 10:20:04","30-11-2024 08:17:56","30-11-2024 =
12:04:16","Grid outage ,Site went down because No Main  Gen on site at the =
moment // MDG 20KVA deployed","Fabrice Pouakam","Equipment Repair","Passive=
","ACDG Gen","ACDG - Generator Faulty","Grid outage ,Site went down because=
 No Main  Gen on site at the moment // MDG 20KVA deployed","etienne.itondo@=
ihstowers.com","7329","30-11-2024 10:20:04","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003720866","NYO=
M 2 IHS","","30-11-2024 10:16:29","30-11-2024 08:37:14","30-11-2024 10:13:4=
0","Grid outage site went down because Gen stopped with alarm Gen under vol=
tage // He reset the Gen card and Gen manually","Fabrice Pouakam","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site wen=
t down because Gen stopped with alarm Gen under voltage // He reset the Gen=
 card and Gen manually","dorothy.djantio@ihstowers.com","5956","30-11-2024 =
10:16:29","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003720577","Nko=
londom","","30-11-2024 09:34:03","30-11-2024 09:07:58","30-11-2024 11:55:06=
","Grid outage, Site went down because Gen was on Manual Mode// He Put Gen =
at auto (Investigation ongoing)","Fabrice Pouakam","Equipment Repair","Pass=
ive","Control Panel","ATS-AMF Issue","Grid outage, Site went down because G=
en was on Manual Mode// He Put Gen at auto (Investigation ongoing)","doroth=
y.djantio@ihstowers.com","1566","30-11-2024 09:34:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003720569","Crf-Mban=
kolo-IHS","","30-11-2024 09:32:50","30-11-2024 09:00:29","30-11-2024 11:28:=
54","Cascaded Incident from TTO3656017","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work: KO=
NDJIE Franck 655217253 From OPUS working on site ( SWAPP GEN and  PWC)","sy=
stem","1941","30-11-2024 09:32:50","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003720565","Jea=
n Vespa","IHS_YND_574","30-11-2024 09:31:36","30-11-2024 09:00:29","30-11-2=
024 11:28:54","Site went down due to work: KONDJIE Franck 655217253 From OP=
US working on site ( SWAPP GEN and  PWC)// End of Work","Mboua Thierry","In=
stallation Activity","Passive","Planned Activity","Installation Activity","=
Site went down due to work: KONDJIE Franck 655217253 From OPUS working on s=
ite ( SWAPP GEN and  PWC)","dorothy.djantio@ihstowers.com","1867","30-11-20=
24 09:31:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0003720406","NTUI TOW=
N","","30-11-2024 09:03:22","30-11-2024 08:41:35","30-11-2024 09:04:15","Ca=
scaded Incident from TTO3655810","Parker Tchoup","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site. Ubaie: 51.8V sit=
e on Battery. Raoul (691144462/Huawei) is informed.","system","1307","30-11=
-2024 09:03:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003720405","Dong",""=
,"30-11-2024 09:03:21","30-11-2024 08:41:35","30-11-2024 09:04:15","Cascade=
d Incident from TTO3655810","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site. Ubaie: 51.8V site on =
Battery. Raoul (691144462/Huawei) is informed.","system","278618","30-11-20=
24 09:03:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003720403","Nguila",=
"","30-11-2024 09:03:21","30-11-2024 08:41:35","30-11-2024 09:04:15","Casca=
ded Incident from TTO3655810","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site. Ubaie: 51.8V site o=
n Battery. Raoul (691144462/Huawei) is informed.","system","278619","30-11-=
2024 09:03:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003720404","Donga","=
","30-11-2024 09:03:21","30-11-2024 08:41:35","30-11-2024 09:04:15","Cascad=
ed Incident from TTO3655810","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site. Ubaie: 51.8V site on=
 Battery. Raoul (691144462/Huawei) is informed.","system","278618","30-11-2=
024 09:03:21","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0003720244","Nko=
zoa","","30-11-2024 08:38:48","30-11-2024 08:21:36","30-11-2024 09:59:16","=
Grid outage, site went down due to gen overload (20kva, 340A) // He reduced=
 the load and gen manually started","Fabrice Pouakam","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to ge=
n overload (20kva, 340A) // He reduced the load and gen manually started","=
dorothy.djantio@ihstowers.com","1033","30-11-2024 08:38:48","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003720222","NYO=
M FACE MAETUR","","30-11-2024 08:36:30","30-11-2024 08:23:25","30-11-2024 1=
8:58:24","Grid Outage,site went down because  landlord has forbiden to star=
t the Gen Because the Noise //Grid Restored","Fabrice Pouakam","Equipment R=
epair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid Outage,site went =
down because  landlord has forbiden to start the Gen Because the Noise //Gr=
id Restored","dorothy.djantio@ihstowers.com","786","30-11-2024 08:36:30","S=
agemcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0003720201","Ntu=
i administration","","30-11-2024 08:32:18","30-11-2024 08:16:13","30-11-202=
4 09:33:02","Site went down because 01/02 rectifier faulty // He reset the =
rectifier","Parker Tchoup","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down because 01/02 rectifier faulty // He reset the =
rectifier","dorothy.djantio@ihstowers.com","965","30-11-2024 08:32:18","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0003719999","Angongo"=
,"","30-11-2024 08:12:02","30-11-2024 07:59:23","30-11-2024 09:00:28","Casc=
aded Incident from TTO3655363","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because rectifier (1/6) sh=
orted// He remove rectifier shorted, site on Grid (remplacement rectifier o=
ngoing)","system","273858","30-11-2024 08:12:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003720000","Nkongtoc=
k","","30-11-2024 08:12:02","30-11-2024 07:59:23","30-11-2024 09:00:28","Ca=
scaded Incident from TTO3655363","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because rectifier (1=
/6) shorted// He remove rectifier shorted, site on Grid (remplacement recti=
fier ongoing)","system","273858","30-11-2024 08:12:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003719998","Mambine"=
,"","30-11-2024 08:12:02","30-11-2024 07:59:23","30-11-2024 09:00:28","Casc=
aded Incident from TTO3655363","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because rectifier (1/6) sh=
orted// He remove rectifier shorted, site on Grid (remplacement rectifier o=
ngoing)","system","273857","30-11-2024 08:12:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003719995","Ebeba","=
","30-11-2024 08:12:01","30-11-2024 07:59:23","30-11-2024 09:00:28","Cascad=
ed Incident from TTO3655363","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because rectifier (1/6) shor=
ted// He remove rectifier shorted, site on Grid (remplacement rectifier ong=
oing)","system","273856","30-11-2024 08:12:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0003719997","OKOA Pea=
ge","","30-11-2024 08:12:01","30-11-2024 07:59:23","30-11-2024 09:00:28","C=
ascaded Incident from TTO3655363","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because rectifier (1/6)=
 shorted// He remove rectifier shorted, site on Grid (remplacement rectifie=
r ongoing)","system","273857","30-11-2024 08:12:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0003719996","Nomayos-=
IHS","","30-11-2024 08:12:01","30-11-2024 07:59:23","30-11-2024 09:00:28","=
Cascaded Incident from TTO3655363","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down because rectifier (1/6=
) shorted// He remove rectifier shorted, site on Grid (remplacement rectifi=
er ongoing)","system","273856","30-11-2024 08:12:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0003719994","Nkenglik=
ok","","30-11-2024 08:12:01","30-11-2024 07:59:23","30-11-2024 09:00:28","C=
ascaded Incident from TTO3655363","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because rectifier (=
1/6) shorted// He remove rectifier shorted, site on Grid (remplacement rect=
ifier ongoing)","system","273855","30-11-2024 08:12:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0003719992","Mandoumb=
a OCM","","30-11-2024 08:12:00","30-11-2024 07:59:23","30-11-2024 09:00:28"=
,"Cascaded Incident from TTO3655363","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because rectifie=
r (1/6) shorted// He remove rectifier shorted, site on Grid (remplacement r=
ectifier ongoing)","system","273854","30-11-2024 08:12:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0003719993","Mbankomo=
 IHS","","30-11-2024 08:12:00","30-11-2024 07:59:23","30-11-2024 09:00:28",=
"Cascaded Incident from TTO3655363","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because rectifier (1/=
6) shorted// He remove rectifier shorted, site on Grid (remplacement rectif=
ier ongoing)","system","273855","30-11-2024 08:12:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0003719991","Sous Pre=
fecture","","30-11-2024 08:12:00","30-11-2024 07:59:23","30-11-2024 09:00:2=
8","Cascaded Incident from TTO3655363","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because rectifier =
(1/6) shorted// He remove rectifier shorted, site on Grid (remplacement rec=
tifier ongoing)","system","273859","30-11-2024 08:12:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0003719989","Nkolfon =
Cimencam","","30-11-2024 08:11:01","30-11-2024 08:03:23","30-11-2024 09:17:=
14","Cascaded Incident from TTO3655364","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because rectif=
ier (1/6) shorted// He remove rectifier shorted, site on Grid (remplacement=
 rectifier ongoing)","system","1223193","30-11-2024 08:11:01","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0003719988","Nomayos =
montee Meche","","30-11-2024 08:11:00","30-11-2024 08:03:23","30-11-2024 09=
:17:14","Cascaded Incident from TTO3655364","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down because recti=
fier (1/6) shorted// He remove rectifier shorted, site on Grid (remplacemen=
t rectifier ongoing)","system","1223194","30-11-2024 08:11:00","Sagemcom CM=
R"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0003719979","Nom=
ayos","IHS_YND_314, IHS_YND_367, IHS_YND_791, IHS_YND_695, IHS_YND_348, IHS=
_YND_339, IHS_YND_697, IHS_YND_762, IHS_YND_330, IHS_YND_350, IHS_YND_335, =
IHS_YND_349","30-11-2024 08:08:31","30-11-2024 07:59:23","30-11-2024 09:17:=
14","Site went down because rectifier (1/6) shorted// He remove rectifier s=
horted, site on Grid (rectifier to be replace)","Fanda Brice","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down because rect=
ifier (1/6) shorted// He remove rectifier shorted, site on Grid (rectifier =
to be replace)","dorothy.djantio@ihstowers.com","779","30-11-2024 08:08:31"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003719753","L=
abogenie","","30-11-2024 07:31:17","30-11-2024 07:24:10","30-11-2024 07:30:=
20","No  power issue U =3D54,6V site on grid. FME Tx Georges (697461814)fro=
m Huawei is informed. Repetitif issue","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No  power issue U =3D=
54,6V site on grid. FME Tx Georges (697461814)from Huawei is informed. Repe=
titif issue","etienne.itondo@ihstowers.com","428","30-11-2024 07:31:17","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003718438","A=
hala","","30-11-2024 00:29:05","30-11-2024 00:19:02","30-11-2024 04:10:45",=
"Active//No power issue on site, Site on Grid UBAIE=3D53V  The FME TX Georg=
es/697461814 From huawei is informed.site up at 00:55 AM","MINKA NICOLAS","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site, Site on Grid UBAIE=3D53V  The FM=
E TX Georges/697461814 From huawei is informed.site up at 00:55 AM","stepha=
ne.nkamwa@ihstowers.com","604","30-11-2024 00:29:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003718048","A=
WAE OCM","","29-11-2024 22:33:04","29-11-2024 22:05:53","30-11-2024 00:10:5=
0","No power issue site on grid with U=3D53,4v Georges from Huawei informed=
 //site up at 10:42 PM","Mba Lazare Herve","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on grid with U=3D53,4v Georges from Huawei informed //site up at 10:42 PM",=
"stephane.nkamwa@ihstowers.com","1632","29-11-2024 22:33:04","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0003717834","Crf=
-Mbankolo-IHS","","29-11-2024 22:08:41","29-11-2024 21:58:41","29-11-2024 2=
2:12:41","Please Cascade this Ticket behind Jean Vespa (TTO3652846)","Mboua=
 Thierry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","P=
lease Cascade this Ticket behind Jean Vespa (TTO3652846)","christian.fonkou=
@ihstowers.com","280901","29-11-2024 22:08:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003717814","J=
-Vespa","","29-11-2024 22:03:50","29-11-2024 21:58:40","29-11-2024 22:12:09=
","Grid outage, Site went down because Gen fails to start due to Grid conta=
ctor dysfunctionned// He blocked Grid Contactor, Site on Grid.","Mboua Thie=
rry","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid =
outage, Site went down because Gen fails to start due to Grid contactor dys=
functionned// He blocked Grid Contactor, Site on Grid.","emmanuel.ghani@ihs=
towers.com","311","29-11-2024 22:03:50","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003717808","Jea=
n Vespa","IHS_YND_574","29-11-2024 22:02:49","29-11-2024 21:58:41","29-11-2=
024 22:12:41","Grid outage, Site went down because Gen fails to start due t=
o Grid contactor dysfunctionned// He blocked Grid Contactor, Site on Grid."=
,"Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Load Conta=
ctor","Grid outage, Site went down because Gen fails to start due to Grid c=
ontactor dysfunctionned// He blocked Grid Contactor, Site on Grid.","christ=
ian.fonkou@ihstowers.com","249","29-11-2024 22:02:49","Sagemcom CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0003717460","Ese=
ka MTN","IHS_YND_378","29-11-2024 21:08:26","29-11-2024 20:27:55","29-11-20=
24 20:31:55","grid outage,gen failed to start due to Grid contactor faulty/=
/Gen manually started","Kemeni Franklin","Equipment Repair","Passive","Cont=
rol Panel","ATS-AMF Issue","grid outage,gen failed to start due to Grid con=
tactor faulty//Gen manually started","christian.fonkou@ihstowers.com","2431=
","29-11-2024 21:08:26","Sagemcom CMR"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0003717208","Ngo=
g Mapubi","","29-11-2024 20:28:17","29-11-2024 20:21:10","29-11-2024 23:13:=
56","Grid outage ,gen failed to star due to battery discharged causing by s=
tatic charger faulty//gen manually started with external battery","Kemeni F=
ranklin","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery"=
,"Grid outage ,gen failed to star due to battery discharged causing by stat=
ic charger faulty//gen manually started with external battery","christian.f=
onkou@ihstowers.com","520","29-11-2024 20:28:17","Sagemcom CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0003717093","Ese=
ka Town","","29-11-2024 20:14:02","29-11-2024 20:27:55","29-11-2024 20:31:5=
5","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","grid outage,gen failed to start due to Grid contactor faulty//=
Gen manually started","christian.fonkou@ihstowers.com","272102","29-11-2024=
 20:14:02","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0003716978","Nko=
lo II New","IHS_YND_266","29-11-2024 20:02:10","29-11-2024 19:33:03","29-11=
-2024 19:53:03","No power issue on site U=3D54,7v site on grid Tx Lionnel s=
teeve of huawei is informed","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site U=3D54,7v site on grid Tx Lionnel steeve of huawei is informed","ch=
ristian.fonkou@ihstowers.com","1748","29-11-2024 20:02:10","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003716821","Mim=
boman4","","29-11-2024 19:46:03","29-11-2024 19:33:03","29-11-2024 19:53:03=
","","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Cascade=
 Active","No power issue on site U=3D54,7v site on grid Tx Lionnel steeve o=
f huawei is informed","christian.fonkou@ihstowers.com","268110","29-11-2024=
 19:46:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_424","NOCINC0003716711","Ossombe"=
,"","29-11-2024 19:37:00","29-11-2024 18:55:01","29-11-2024 20:00:00","Casc=
aded Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Gen fail to start  due to alarm oil lev=
el   //  oil added","system","270530","29-11-2024 19:37:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003716667","Saa","",=
"29-11-2024 19:33:34","29-11-2024 18:55:01","29-11-2024 20:00:00","Cascaded=
 Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Gen fail to start  due to alarm oil level  =
 //  oil added","system","2313","29-11-2024 19:33:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003716664","Donga","=
","29-11-2024 19:33:34","29-11-2024 18:55:01","29-11-2024 20:00:00","Cascad=
ed Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Gen fail to start  due to alarm oil level=
   //  oil added","system","270534","29-11-2024 19:33:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0003716666","NTUI TOW=
N","","29-11-2024 19:33:34","29-11-2024 18:55:01","29-11-2024 20:00:00","Ca=
scaded Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Gen fail to start  due to alarm oil l=
evel   //  oil added","system","270535","29-11-2024 19:33:34","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003716665","Dong",""=
,"29-11-2024 19:33:34","29-11-2024 18:55:01","29-11-2024 20:00:00","Cascade=
d Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Gen fail to start  due to alarm oil level =
  //  oil added","system","270531","29-11-2024 19:33:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003716669","Yoko MTN=
","","29-11-2024 19:33:34","29-11-2024 18:55:01","29-11-2024 20:00:00","Cas=
caded Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Gen fail to start  due to alarm oil le=
vel   //  oil added","system","270536","29-11-2024 19:33:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_690","NOCINC0003716662","Ntui adm=
inistration","","29-11-2024 19:33:33","29-11-2024 18:55:01","29-11-2024 20:=
00:00","Cascaded Incident from TTO3651310","Parker Tchoup","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Gen fail to start  due to a=
larm oil level   //  oil added","system","270536","29-11-2024 19:33:33","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003716661","Ngouetou=
","","29-11-2024 19:33:33","29-11-2024 18:55:01","29-11-2024 20:00:00","Cas=
caded Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Gen fail to start  due to alarm oil le=
vel   //  oil added","system","270532","29-11-2024 19:33:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0003716659","SAA 2","=
","29-11-2024 19:33:32","29-11-2024 18:55:01","29-11-2024 20:00:00","Cascad=
ed Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Gen fail to start  due to alarm oil level=
   //  oil added","system","2311","29-11-2024 19:33:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003716655","Matsari"=
,"","29-11-2024 19:33:31","29-11-2024 18:55:01","29-11-2024 20:00:00","Casc=
aded Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Gen fail to start  due to alarm oil lev=
el   //  oil added","system","2310","29-11-2024 19:33:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003716652","Nguila",=
"","29-11-2024 19:33:31","29-11-2024 18:55:01","29-11-2024 20:00:00","Casca=
ded Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Gen fail to start  due to alarm oil leve=
l   //  oil added","system","270537","29-11-2024 19:33:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003716653","MBIMBIM"=
,"","29-11-2024 19:33:31","29-11-2024 18:55:01","29-11-2024 20:00:00","Casc=
aded Incident from TTO3651310","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Gen fail to start  due to alarm oil lev=
el   //  oil added","system","2310","29-11-2024 19:33:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003716449","M=
IMBOMAN LIBERTE","","29-11-2024 19:10:49","29-11-2024 19:04:44","29-11-2024=
 19:58:36","grid outage,site went down main gen faulty//grid return","Mba L=
azare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faul=
ty","grid outage,site went down main gen faulty//grid return","emmanuel.gha=
ni@ihstowers.com","366","29-11-2024 19:10:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003715886","S=
tade-Abega","","29-11-2024 18:02:19","29-11-2024 17:54:13","29-11-2024 22:1=
9:01","Site went down due to technician  Gildas (656040578) FROM ETECH PRO =
Sarl working from swapp PWC //End of work","Mba Lazare Herve","Installation=
 Activity","Passive","Planned Activity","Installation Activity","Site went =
down due to technician  Gildas (656040578) FROM ETECH PRO Sarl working from=
 swapp PWC //End of work","emmanuel.ghani@ihstowers.com","488","29-11-2024 =
18:02:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0003715819","T=
radex-Nkomo","","29-11-2024 17:56:09","29-11-2024 17:50:19","29-11-2024 19:=
15:19","Tx Issue: site on grid,Ubaie:53.4V; Lionel Adjep//655-18-48-76 is i=
nformed.","Albran Byorel","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Tx Issue: site on grid,Ubaie:53.4V; L=
ionel Adjep//655-18-48-76 is informed.","emmanuel.ghani@ihstowers.com","351=
","29-11-2024 17:56:09","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_167","NOCINC0003715790","Touring Cl=
ub International","","29-11-2024 17:51:13","","","High temp alarms temp : 3=
3 =B0C//FME informed us that false alarm","Albran Byorel","Warning","Warnin=
g","ENVIRONMENT","Warning - High Temperature","High temp alarms temp : 33 =
=B0C//FME informed us that false alarm","joelle.ekessi@ihstowers.com","71",=
"29-11-2024 17:51:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003715697","B=
iteng","","29-11-2024 17:44:58","29-11-2024 17:40:44","29-11-2024 19:15:14"=
,"No power issue on site U=3D54v site on grid Tx Lionnel steeve of Huawei i=
s informed","Mba Lazare Herve","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v s=
ite on grid Tx Lionnel steeve of Huawei is informed","emmanuel.ghani@ihstow=
ers.com","256","29-11-2024 17:44:58","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_109","NOCINC0003715555","Mobil-Esso=
s","","29-11-2024 17:38:20","","","Alarm unprouven","Siligap Boris","Warnin=
g","Warning","ENVIRONMENT","Warning - High Temperature","Alarm unprouven","=
joelle.ekessi@ihstowers.com","71","29-11-2024 17:38:20","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_319","NOCINC0003715536","SOA 2","",=
"29-11-2024 17:37:21","","","site alarming High temp 43=B0c// alrm cleared"=
,"Siligap Boris","Warning","Warning","ENVIRONMENT","Warning - High Temperat=
ure","site alarming High temp 43=B0c// alrm cleared","joelle.ekessi@ihstowe=
rs.com","72","29-11-2024 17:37:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003714653","B=
iteng-Maetur","","29-11-2024 17:01:12","29-11-2024 16:52:47","29-11-2024 19=
:20:47","Active//No power issue, U=3D54V on grid, Tx FME lionel steve adjep=
/655124876/ From huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue, U=3D54V on grid, Tx FME lionel steve adjep/655124876/ From=
 huawei is informed
","emmanuel.ghani@ihstowers.com","507","29-11-2024 17:01:12","Sagemcom CMR"
"Closed Complete","Warning","CTR_211","IHS_YND_248","NOCINC0003714444","Bit=
eng","","29-11-2024 16:29:41","","","No power issue on site U=3D54v site on=
 grid Lionel steeve of huawei is informed","Mba Lazare Herve","Warning","Wa=
rning","POWER","Warning - Site on Grid","No power issue on site U=3D54v sit=
e on grid Lionel steeve of huawei is informed","joelle.ekessi@ihstowers.com=
","69","29-11-2024 16:29:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0003714391","K=
ondengui","","29-11-2024 16:20:12","29-11-2024 16:10:35","29-11-2024 18:21:=
44","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","grid outage,no space to deploy a mobil gen//grid return","emman=
uel.ghani@ihstowers.com","273160","29-11-2024 16:20:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003714353","E=
mombo-Tchad","IHS_YND_114","29-11-2024 16:16:43","29-11-2024 16:10:35","29-=
11-2024 18:21:44","grid outage,no space to deploy a mobil gen//grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","gri=
d outage,no space to deploy a mobil gen//grid return","emmanuel.ghani@ihsto=
wers.com","369","29-11-2024 16:16:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003714293","K=
oweit City","","29-11-2024 16:13:40","29-11-2024 15:57:32","29-11-2024 16:3=
3:12","grid outage,gen ran till fuel shortage//Refueling done","Albran Byor=
el","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran t=
ill fuel shortage//Refueling done","emmanuel.ghani@ihstowers.com","969","29=
-11-2024 16:13:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003714291","A=
WAE OCM","","29-11-2024 16:13:09","29-11-2024 15:49:55","29-11-2024 16:20:5=
5","No power issue on site U=3D55v site on grid Tx fme Georges of huawei is=
 informed","Mba Lazare Herve","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D55v si=
te on grid Tx fme Georges of huawei is informed","emmanuel.ghani@ihstowers.=
com","1395","29-11-2024 16:13:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003714273","L=
abogenie","","29-11-2024 16:10:07","29-11-2024 16:07:55","29-11-2024 21:45:=
23","No power issue on site U=3D55v site on grid tx fme Georges of huawei i=
s informed","","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","No power issue on site U=3D55v site on grid tx f=
me Georges of huawei is informed","emmanuel.ghani@ihstowers.com","134","29-=
11-2024 16:10:07","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_387","NOCINC0003713889","Talla Mona=
tele","","29-11-2024 15:25:53","","","Grid fluctuation, Site went alarm bec=
ause gen start and stopped due to grid bad voltage // he bypass grid and ma=
nually start the gen","Parker Tchoup","Warning","Warning","POWER","Warning =
- Site on Battery","Grid fluctuation, Site went alarm because gen start and=
 stopped due to grid bad voltage // he bypass grid and manually start the g=
en","joelle.ekessi@ihstowers.com","67","29-11-2024 15:25:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003713761","Akak-Nko=
zoa-MTN-IHS","","29-11-2024 15:14:51","29-11-2024 15:09:02","29-11-2024 15:=
12:42","Cascaded Incident from TTO3648282","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo outage, site down be=
fore DG started due to poor backup //Eneo return","system","277047","29-11-=
2024 15:14:51","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_293","NOCINC0003713529","Nkoabang M=
TN","","29-11-2024 14:47:31","","","Grid fluctuation, site alarming on batt=
ery because Gen started and Stopped due to Grid bad voltage//He bypassed Gr=
id and started Gen manualy","Mba Lazare Herve","Warning","Warning","POWER",=
"Warning - Site on Battery","Grid fluctuation, site alarming on battery bec=
ause Gen started and Stopped due to Grid bad voltage//He bypassed Grid and =
started Gen manualy","joelle.ekessi@ihstowers.com","69","29-11-2024 14:47:3=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003713041","O=
lembe-Terminus","","29-11-2024 13:48:20","29-11-2024 13:29:08","29-11-2024 =
13:48:53","grid outage site went down because Main gen faulty // MDG of 20 =
Kva has deployed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Faulty","grid outage site went down because Main gen fau=
lty // MDG of 20 Kva has deployed","denis.mballa@ihstowers.com","1154","29-=
11-2024 13:48:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003712907","E=
ssomba","","29-11-2024 13:35:15","29-11-2024 13:30:03","29-11-2024 22:00:44=
","No power issue on site U=3D54v site on grid Tx fme Georges of huawei is =
informed","Mba Lazare Herve","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v sit=
e on grid Tx fme Georges of huawei is informed","denis.mballa@ihstowers.com=
","314","29-11-2024 13:35:15","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0003712825","Aha=
la Echangeur","","29-11-2024 13:28:20","29-11-2024 12:45:01","29-11-2024 13=
:40:53","Site went down due to work: Njoya Mohamed/658849259 From NOUMAD wo=
rking on site (swapp pwc)// End of work","MINKA NICOLAS","Installation Acti=
vity","Passive","Planned Activity","Installation Activity","Site went down =
due to work: Njoya Mohamed/658849259 From NOUMAD working on site (swapp pwc=
)// End of work","rouselle.schoune@ihstowers.com","2600","29-11-2024 13:28:=
20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0003712757","M=
atomb","","29-11-2024 13:19:40","29-11-2024 13:10:27","29-11-2024 14:30:06"=
,"grid outage,gen failed to start due to contactor Ge faulty//he blocked th=
e contactor and restarted it(remplacement ongoing)","Kemeni Franklin","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","grid outage,gen fa=
iled to start due to contactor Ge faulty//he blocked the contactor and rest=
arted it(remplacement ongoing)","denis.mballa@ihstowers.com","554","29-11-2=
024 13:19:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003712686","B=
itoto","","29-11-2024 13:11:26","29-11-2024 13:04:09","29-11-2024 21:40:09"=
,"No power issue on site U=3D53v site on grid Tx fme Georges of huawei is i=
nformed","Mba Lazare Herve","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53v site=
 on grid Tx fme Georges of huawei is informed","denis.mballa@ihstowers.com"=
,"439","29-11-2024 13:11:26","Sagemcom CMR"
"Closed Complete","Warning","T0236","IHS_YND_373","NOCINC0003712613","Malou=
n","","29-11-2024 13:02:08","","","Site alarming on battery because Our FME=
 Kemeni Francklin From SAGEMCOM was on site for refueling// Refueling Done"=
,"Kemeni Franklin","Warning","Warning","POWER","Warning - Site on Battery",=
"Site alarming on battery because Our FME Kemeni Francklin From SAGEMCOM wa=
s on site for refueling// Refueling Done","alwine.fambou@ihstowers.com","3"=
,"29-11-2024 13:02:08","Sagemcom CMR"
"Closed Complete","Site Down","T0050","IHS_YND_039","NOCINC0003712556","Sia=
ntou Radio TV","","29-11-2024 12:56:16","29-11-2024 12:49:10","29-11-2024 1=
3:18:03","Grid outage, No space to deploy MDG // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No s=
pace to deploy MDG // Grid return","rouselle.schoune@ihstowers.com","427","=
29-11-2024 12:56:16","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003712365","Nko=
londom","","29-11-2024 12:35:54","29-11-2024 12:32:45","29-11-2024 12:34:44=
","Site went down due to work: The Team Djoufack Prosper /674955463/ From A=
NCHOR (swapp PWC)// End of work","Fabrice Pouakam","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Site went down due to=
 work: The Team Djoufack Prosper /674955463/ From ANCHOR (swapp PWC)// End =
of work","rouselle.schoune@ihstowers.com","190","29-11-2024 12:35:54","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003712101","O=
dza II","","29-11-2024 11:55:03","29-11-2024 11:46:50","29-11-2024 12:43:41=
","Site went down due to work: The Team Verla Ivo/ 676492807/ From Grato in=
genering Swap Gen and Power cabinet","Albran Byorel","Installation Activity=
","Passive","Planned Activity","Installation Activity","Site went down due =
to work: of Verla Ivo/ 676492807/ From Grato ingenering Swap Gen and Power =
cabinet//end of work","denis.mballa@ihstowers.com","495","29-11-2024 11:55:=
03","Sagemcom CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0003711840","Odz=
a petit marche new","","29-11-2024 11:09:17","29-11-2024 11:06:57","29-11-2=
024 12:15:01","Grid fluctuation, site went down because Gen start and stopp=
ed due to Grid bad voltage no rcp // Grid stabilized","Albran Byorel","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid f=
luctuation, site went down because Gen start and stopped due to Grid bad vo=
ltage no rcp // Grid stabilized","rouselle.schoune@ihstowers.com","141","29=
-11-2024 11:09:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0003710083","Mvog-Eba=
nda","","29-11-2024 06:02:00","29-11-2024 05:49:01","29-11-2024 05:55:01","=
Cascaded Incident from TTO3644083","Siligap Boris","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue on site Ubaie=
=3D54,6V site on Grid The tx fme Armand nguetsa(691144412) is informed","sy=
stem","267311","29-11-2024 06:02:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003710079","A=
bom","IHS_YND_269","29-11-2024 06:00:08","29-11-2024 05:49:01","29-11-2024 =
05:55:01","Active//No power issue on site Ubaie=3D54,6V site on Grid The tx=
 fme Armand nguetsa(691144412) is informed","Siligap Boris","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue on site Ubaie=3D54,6V site on Grid The tx fme Armand ng=
uetsa(691144412) is informed","alexandre.kamal@ihstowers.com","668","29-11-=
2024 06:00:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003710023","C=
rf Cornier","","29-11-2024 05:31:19","29-11-2024 05:22:11","29-11-2024 05:2=
6:11","Active//No power issue, U=3D54V on grid Tx FME George/697461814/ Fro=
m huawei is informed","MINKA NICOLAS","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, U=
=3D54V on grid Tx FME George/697461814/ From huawei is informed","alexandre=
.kamal@ihstowers.com","549","29-11-2024 05:31:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003709976","c=
hina embassy yde","","29-11-2024 05:21:23","29-11-2024 05:13:11","29-11-202=
4 05:14:02","No power issue on site Ubaie=3D53.3V site on Grid The Tx Fme E=
loundou/693212405 of huawei is informed","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite Ubaie=3D53.3V site on Grid The Tx Fme Eloundou/693212405 of huawei is i=
nformed","alexandre.kamal@ihstowers.com","493","29-11-2024 05:21:23","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003709833","L=
abogenie","","29-11-2024 04:51:40","29-11-2024 04:39:32","29-11-2024 04:45:=
32","Active//No power issue, U=3D54V on grid Tx FME George/697461814/ From =
huawei is informed","","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Active//No power issue, U=3D54V on grid =
Tx FME George/697461814/ From huawei is informed","alexandre.kamal@ihstower=
s.com","729","29-11-2024 04:51:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003709803","M=
arche Odza","","29-11-2024 04:35:19","29-11-2024 04:17:14","29-11-2024 04:2=
5:15","No power issue on site U=3D54,5v site on grid Tx fme Lionnel steeve =
of huawei is informed","Albran Byorel","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,5v site on grid Tx fme Lionnel steeve of huawei is informed","alexand=
re.kamal@ihstowers.com","1086","29-11-2024 04:35:19","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003708513","MIM=
BOMAN LIBERTE","","28-11-2024 22:09:05","28-11-2024 21:59:48","28-11-2024 2=
2:17:12","Grid outage, site went down due to main gen faulty // grid return=
","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid outage, site went down sue to main gen faulty // grid ret=
urn","landry.etame@ihstowers.com","558","28-11-2024 22:09:05","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003708286","S=
tade-Abega","","28-11-2024 21:35:00","28-11-2024 21:18:31","28-11-2024 23:2=
1:52","Grid outage,gen fails to start due to candle faulty//Gen Manually St=
arted","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - K=
ick Starter","Grid outage,gen fails to start due to candle faulty//Gen Manu=
ally Started","stephane.nkamwa@ihstowers.com","990","28-11-2024 21:35:00","=
Sagemcom CMR"
"Closed Complete","Site Down","T0050","IHS_YND_039","NOCINC0003708220","Sia=
ntou Radio TV","","28-11-2024 21:29:26","28-11-2024 21:21:19","29-11-2024 0=
9:53:35","Grid outage,no space to deploy mobiile gen// grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
,no space to deploy mobiile gen// grid return","landry.etame@ihstowers.com"=
,"488","28-11-2024 21:29:26","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003708178","Ole=
mbe MTN","","28-11-2024 21:25:10","28-11-2024 21:17:49","28-11-2024 21:41:1=
7","grid bad voltage,and gen failed to start//bypassed grid and started the=
 gen","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","grid bad voltage,and gen failed to start//bypassed g=
rid and started the gen","landry.etame@ihstowers.com","442","28-11-2024 21:=
25:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003707930","ELOUMDEM=
 CARRIERE 2","","28-11-2024 21:01:20","28-11-2024 20:55:53","28-11-2024 21:=
17:29","Cascaded Incident from TTO3641533","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid bad voltage,and gen fail=
ed to start //bypassed grid and started the gen","system","327","28-11-2024=
 21:01:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003707929","Eto koss=
 Yde","","28-11-2024 21:01:20","28-11-2024 20:55:53","28-11-2024 21:17:29",=
"Cascaded Incident from TTO3641533","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid bad voltage,and gen failed to s=
tart //bypassed grid and started the gen","system","327","28-11-2024 21:01:=
20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003707921","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","28-11-2024 21:00:00","28-11-2024 20:55=
:53","28-11-2024 21:17:29","grid bad voltage,and gen failed to start //bypa=
ssed grid and started the gen","Fanda Brice","Grid Supply","Passive","Grid"=
,"National Grid - Phase Controller Faulty","grid bad voltage,and gen failed=
 to start //bypassed grid and started the gen","landry.etame@ihstowers.com"=
,"251","28-11-2024 21:00:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003707905","O=
lembe-Terminus","","28-11-2024 20:57:23","28-11-2024 20:22:15","29-11-2024 =
00:49:03","grid outage site went down because Main gen faulty // MDG of 20 =
Kva has deployed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Faulty","grid outage site went down because Main gen fau=
lty // MDG of 20 Kva has deployed","stephane.nkamwa@ihstowers.com","2109","=
28-11-2024 20:57:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003706598","O=
lembe-Terminus","","28-11-2024 18:38:35","28-11-2024 18:29:29","28-11-2024 =
20:21:37","Grid outage,site went down before DG started :poor batteries bac=
kup//Grid restored.","Fabrice Pouakam","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage,site went down before D=
G started :poor batteries backup//Grid restored.","stephane.nkamwa@ihstower=
s.com","548","28-11-2024 18:38:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003706567","Akak-Nko=
zoa-MTN-IHS","","28-11-2024 18:36:50","28-11-2024 18:31:37","28-11-2024 18:=
33:46","Cascaded Incident from TTO3639955","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo outage, site down be=
fore DG started due to poor backup //  Eneo return","system","264811","28-1=
1-2024 18:36:50","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003705170","NYO=
M FACE MAETUR","","28-11-2024 16:16:41","28-11-2024 16:10:33","28-11-2024 1=
6:27:33","Grid Outage landlord has forbiden to start the Gen Because the No=
ise // Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Emergency Stop","Grid Outage landlord has forbiden to start th=
e Gen Because the Noise // Grid Restored","landry.etame@ihstowers.com","369=
","28-11-2024 16:16:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0003704949","E=
mombo 2","","28-11-2024 15:48:40","28-11-2024 15:41:30","28-11-2024 16:12:4=
1","Site went down due to technician  Gildas (656040578) FROM ETECH PRO Sar=
l working from Replacement DC box //End of work","MINKA NICOLAS","Installat=
ion Activity","Passive","Planned Activity","Installation Activity","Site we=
nt down due to technician  Gildas (656040578) FROM ETECH PRO Sarl working f=
rom Replacement DC box //End of work","stephane.nkamwa@ihstowers.com","431"=
,"28-11-2024 15:48:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003704659","D=
amas","","28-11-2024 15:11:25","28-11-2024 14:54:55","28-11-2024 15:02:23",=
"Grid outage site went down due to Gen overload(9kva, 150Kva)//Grid return"=
,"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage site went down due to Gen overload(9kva, 150Kva)//Grid return"=
,"stephane.nkamwa@ihstowers.com","991","28-11-2024 15:11:25","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003703947","Ema=
na","","28-11-2024 13:47:00","28-11-2024 13:42:52","28-11-2024 14:22:26","G=
rid outage, site went down because Gen fails to start due to GEN CARD Dysfu=
nction // He reset the Gen card and Gen manualy started","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage=
, site went down because Gen fails to start due to GEN CARD Dysfunction // =
He reset the Gen card and Gen manualy started","christian.fonkou@ihstowers.=
com","249","28-11-2024 13:47:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0003703943","C=
NR","","28-11-2024 13:46:11","28-11-2024 13:40:05","28-11-2024 14:34:31","G=
rid outage ,gen failed to start due to battery GE discharged causing by sta=
tic charger faulty//Grid return","Mboua Thierry","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Charging Alternator","Grid outage ,gen failed to star=
t due to battery GE discharged causing by static charger faulty//Grid retur=
n","emmanuel.ghani@ihstowers.com","367","28-11-2024 13:46:11","Sagemcom CMR=
"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003703893","Pha=
rmacie SION","","28-11-2024 13:40:47","28-11-2024 13:34:42","28-11-2024 13:=
44:26","Grid outage,site went down before DG start: Poor Batteries Backup /=
/ DG started automatically.","Paul BIBOUM","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage,site went down befo=
re DG start: Poor Batteries Backup // DG started automatically.","christian=
.fonkou@ihstowers.com","366","28-11-2024 13:40:47","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_010","NOCINC0003703881","CNR","","2=
8-11-2024 13:38:21","","","Site on battery due to DG battery discharged (st=
atic charger)// Grid restored.","Mboua Thierry","Warning","Warning","POWER"=
,"Warning - ACDG - Charging Alternator","Site on battery due to DG battery =
discharged (static charger)// Grid restored.","joelle.ekessi@ihstowers.com"=
,"67","28-11-2024 13:38:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003703561","D=
ragage","","28-11-2024 13:13:39","28-11-2024 13:09:34","28-11-2024 14:36:50=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen automatically started. But site up after power reset","Mboua Thierry=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen automatically started. But site up after power reset","emmanuel.ghan=
i@ihstowers.com","247","28-11-2024 13:13:39","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003703352","SOA=
 TOWN","","28-11-2024 12:41:52","28-11-2024 12:31:45","28-11-2024 13:05:45"=
,"","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","gen only site: site went down because gen stopped with under under=
 voltage alarm // reset of gen card done and gen started","christian.fonkou=
@ihstowers.com","608","28-11-2024 12:41:52","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_319","NOCINC0003703292","SOA 2","",=
"28-11-2024 12:28:50","","","Site on battery due to grid outage // DG start=
ed automatically.","Siligap Boris","Warning","Warning","POWER","Warning - N=
ational Grid - Grid Outage Issue","Site on battery due to grid outage // DG=
 started automatically.","joelle.ekessi@ihstowers.com","78","28-11-2024 12:=
28:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003702894","Akak-Nko=
zoa-MTN-IHS","","28-11-2024 11:38:10","28-11-2024 11:32:40","28-11-2024 11:=
40:37","Cascaded Incident from TTO3635875","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo outage, site down be=
fore DG started due to poor backup // Eneo return","system","330","28-11-20=
24 11:38:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003702872","O=
lembe-Terminus","","28-11-2024 11:34:01","28-11-2024 11:31:51","28-11-2024 =
11:38:47","Grid outage,site went down before DG started :poor batteries bac=
kup//Grid restored.","Fabrice Pouakam","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage,site went down before D=
G started :poor batteries backup//Grid restored.","emmanuel.ghani@ihstowers=
.com","131","28-11-2024 11:34:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_396","NOCINC0003702753","Nkolmvac=
k","","28-11-2024 11:24:30","28-11-2024 10:57:59","28-11-2024 10:58:59","Ca=
scaded Incident from TTO3635638","Parker Tchoup","Cascade Outage","Active",=
"Cascade Active","Cascade Active","impacted oby ombessa which is not mAnaag=
ed by IHS","system","263048","28-11-2024 11:24:30","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003702160","NKO=
MEKUI OCM","","28-11-2024 10:10:18","28-11-2024 10:00:09","28-11-2024 10:05=
:36","No power issue on site Ubaie: 54,1 V site on GEN. Site went down beca=
use is impacted by Mbankolo_camtel and not managing by IHS.","TIENTCHEU NZE=
TCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failur=
e","Affected by 3rd Party Site","No power issue on site Ubaie: 54,1 V site =
on GEN. Site went down because is impacted by Mbankolo_camtel and not manag=
ing by IHS.","christian.fonkou@ihstowers.com","611","28-11-2024 10:10:18","=
Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_067","NOCINC0003701254","Nkoa Ayos"=
,"","28-11-2024 08:20:30","","","Grid outage Hybrid // DG started automatic=
ally.","MINKA NICOLAS","Warning","Warning","POWER","Warning - National Grid=
 - Grid Outage Issue","Grid outage Hybrid // DG started automatically.","jo=
elle.ekessi@ihstowers.com","67","28-11-2024 08:20:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003701143","M=
VAN SACEL","","28-11-2024 08:02:39","28-11-2024 08:00:56","28-11-2024 08:07=
:56","Grid outage, site went down before gen start due to poor batteries ba=
ckup // gen start automatically","MINKA NICOLAS","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor batteries backup // gen start automatically=
","emmanuel.ghani@ihstowers.com","104","28-11-2024 08:02:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003701067","D=
amas","","28-11-2024 07:46:39","28-11-2024 07:40:35","28-11-2024 14:42:20",=
"Grid outage site went down due to Gen overload(9kva, 150Kva)//Grid return"=
,"MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage site went down due to Gen overload(9kva, 150Kva)//Grid return"=
,"emmanuel.ghani@ihstowers.com","365","28-11-2024 07:46:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003700685","Yoko MTN=
","","28-11-2024 06:31:31","28-11-2024 06:25:47","28-11-2024 06:26:47","Cas=
caded Incident from TTO3633444","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site with Ubaie=
=3D56V site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gregoire( 6520=
70658)from Huawei is informed and Site UP at 06:34 AM","system","344","28-1=
1-2024 06:31:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003700684","Ngoum","=
","28-11-2024 06:31:31","28-11-2024 06:25:47","28-11-2024 06:26:47","Cascad=
ed Incident from TTO3633444","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue on site with Ubaie=3D=
56V site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gregoire( 6520706=
58)from Huawei is informed and Site UP at 06:34 AM","system","344","28-11-2=
024 06:31:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003700683","MBIMBIM"=
,"","28-11-2024 06:31:31","28-11-2024 06:25:47","28-11-2024 06:26:47","Casc=
aded Incident from TTO3633444","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue on site with Ubaie=
=3D56V site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gregoire( 6520=
70658)from Huawei is informed and Site UP at 06:34 AM","system","344","28-1=
1-2024 06:31:31","Sagemcom CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0003700677","Mat=
sari","IHS_YND_456, IHS_YND_475, IHS_YND_473","28-11-2024 06:29:53","28-11-=
2024 06:25:47","28-11-2024 06:45:47","Active//No power issue on site with U=
baie=3D56V site on Gen (start threshold ubai=3D48.4V) The Tx Fme Gregoire( =
652070658)from Huawei is informed and Site UP at 06:34 AM","Parker Tchoup",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active//No power issue on site with Ubaie=3D56V site on Gen (st=
art threshold ubai=3D48.4V) The Tx Fme Gregoire( 652070658)from Huawei is i=
nformed and Site UP at 06:34 AM","christian.fonkou@ihstowers.com","247","28=
-11-2024 06:29:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003699955","M=
VAN SACEL","","28-11-2024 02:51:59","28-11-2024 02:49:13","28-11-2024 02:55=
:13","Grid outage, site went down before gen start due to poor battery back=
up // Grid Restored","MINKA NICOLAS","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before ge=
n start due to poor battery backup // Grid Restored","ludivine.ngamaleu@ihs=
towers.com","280","28-11-2024 02:51:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0003699819","Mfou EPC=
","","28-11-2024 01:41:40","28-11-2024 01:35:57","28-11-2024 01:41:46","Cas=
caded Incident from TTO3632465","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation site went down bec=
ause Gen failed to start due to Grid bad voltage and no RCP on site // nHe =
bypass the Grid and Gen manually started","system","282302","28-11-2024 01:=
41:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0003699818","M=
fou OCM","IHS_YND_674","28-11-2024 01:41:03","28-11-2024 01:35:57","28-11-2=
024 01:41:46","Grid fluctuation site went down because Gen failed to start =
due to Grid bad voltage and no RCP on site // nHe bypass the Grid and Gen m=
anually started","Mba Lazare Herve","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Grid fluctuation site went down because =
Gen failed to start due to Grid bad voltage and no RCP on site // nHe bypas=
s the Grid and Gen manually started","ludivine.ngamaleu@ihstowers.com","307=
","28-11-2024 01:41:03","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003699322","BIY=
EMASSI NIKI","","27-11-2024 23:38:22","27-11-2024 23:33:14","28-11-2024 08:=
05:57","Access Issue during the Night: Site went down due to PWC overloaded=
 (12kva 250 A) //Site stabilized","Hyemafo Gildas","Access Denial","Lease O=
r Legal","Landlord Related Issues","Access Issue - Land Lord","Access Issue=
 during the Night: Site went down due to PWC overloaded (12kva 250 A) //Sit=
e stabilized","olivier.kwedi@ihstowers.com","309","27-11-2024 23:38:22","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0003698815","Ona=
ngondi (melen bikop)","","27-11-2024 22:00:53","27-11-2024 21:46:38","27-11=
-2024 22:26:31","Grid outage, Site went down because Gen started and stoppe=
d with ""high temp"" alarm// He added water and started Gen manualy","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - =
Coolant Level Issue","Grid outage, Site went down because Gen started and s=
topped with ""high temp"" alarm// He added water and started Gen manualy","=
kamga.virgile@ihstowers.com","856","27-11-2024 22:00:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003698568","A=
WAE OCM","","27-11-2024 21:24:07","27-11-2024 21:05:59","28-11-2024 08:55:5=
9","Access Issue The landlord forbidden to start Gen due to noise: Grid flu=
ctuation site went down due to lack of 02/03 phases on site // he did a bri=
dge with a good phase, Site on Grid","Mba Lazare Herve","Access Denial","Le=
ase Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access =
Issue The landlord forbidden to start Gen due to noise: Grid fluctuation si=
te went down due to lack of 02/03 phases on site // he did a bridge with a =
good phase, Site on Grid","alexandre.kamal@ihstowers.com","1089","27-11-202=
4 21:24:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003698401","M=
elen Ba'aba","","27-11-2024 21:06:41","27-11-2024 20:45:32","27-11-2024 21:=
26:05","site went down because The Cb(125A) of Pwc dysjoncted due to Grid b=
ad voltage // He bypass the Cb and site on Gen","Siligap Boris","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","=
site went down because The Cb(125A) of Pwc dysjoncted due to Grid bad volta=
ge // He bypass the Cb and site on Gen","alexandre.kamal@ihstowers.com","12=
70","27-11-2024 21:06:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0003698137","K=
ondengui","","27-11-2024 20:36:59","27-11-2024 20:06:54","27-11-2024 20:07:=
36","Active//No power issue on site Ubaie=3D54,6V site on Grid The tx fme A=
rmand nguetsa(691144412) is informed","Albran Byorel","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue on site Ubaie=3D54,6V site on Grid The tx fme Armand nguetsa(=
691144412) is informed","alexandre.kamal@ihstowers.com","1806","27-11-2024 =
20:36:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003698078","ELOUMDEM=
 CARRIERE 2","","27-11-2024 20:27:32","27-11-2024 20:16:39","27-11-2024 20:=
24:54","Cascaded Incident from TTO3630429","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Gen start and stopped due to Grid bad voltage // Gen manually s=
tarted","system","1215140","27-11-2024 20:27:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003698077","Eto koss=
 Yde","","27-11-2024 20:27:31","27-11-2024 20:16:39","27-11-2024 20:24:54",=
"Cascaded Incident from TTO3630429","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Gen start and stopped due to Grid bad voltage // Gen manually started"=
,"system","1215140","27-11-2024 20:27:31","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003698061","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","27-11-2024 20:25:51","27-11-2024 20:16=
:39","27-11-2024 20:24:54","Grid fluctuation, site went down because Gen st=
art and stopped due to Grid bad voltage // Gen manually started","Fanda Bri=
ce","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because Gen start and stopped due to Gr=
id bad voltage // Gen manually started","kamga.virgile@ihstowers.com","553"=
,"27-11-2024 20:25:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003697681","Donga","=
","27-11-2024 19:24:01","27-11-2024 18:04:55","27-11-2024 18:25:18","Cascad=
ed Incident from TTO3629962","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Site impacted by Mbandjock which is not hand=
led by IHS","system","273429","27-11-2024 19:24:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003697682","Dong",""=
,"27-11-2024 19:24:01","27-11-2024 18:04:55","27-11-2024 18:25:18","Cascade=
d Incident from TTO3629962","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Site impacted by Mbandjock which is not handl=
ed by IHS","system","273431","27-11-2024 19:24:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003696710","A=
kak-Nkozoa-MTN-IHS","","27-11-2024 16:59:08","27-11-2024 16:48:04","27-11-2=
024 16:59:05","Grid bad voltage, site went down because Gen failed to start=
 due to Grid bad voltage and RCP faulty// Gen Manully Started","Fabrice Pou=
akam","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid bad voltage, site went down because Gen failed to start due to Gr=
id bad voltage and RCP faulty// Gen Manully Started","alexandre.kamal@ihsto=
wers.com","666","27-11-2024 16:59:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003695925","I=
mm-Olympique","","27-11-2024 15:45:12","27-11-2024 15:37:04","27-11-2024 23=
:37:01","No power issue site on grid with U=3D53.1v Notice that we have dis=
junction at OCM Equipements RM Alain Tchaptchet(691144423) from Huawei is i=
nformed","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.=
1v Notice that we have disjunction at OCM Equipements RM Alain Tchaptchet(6=
91144423) from Huawei is informed","alexandre.kamal@ihstowers.com","489","2=
7-11-2024 15:45:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0003695524","N=
goum","","27-11-2024 15:01:32","27-11-2024 14:56:27","27-11-2024 23:32:39",=
"No power issue site on Solar, with U=3D51V The Tx Fme Gregoire (654547479)=
 from Huawei informed .","Parker Tchoup","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 Solar, with U=3D51V The Tx Fme Gregoire (654547479) from Huawei informed .=
","alexandre.kamal@ihstowers.com","307","27-11-2024 15:01:32","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0003695389","E=
koumdoum","","27-11-2024 14:59:07","27-11-2024 14:52:03","27-11-2024 23:28:=
17","No power issue site on grid with U=3D54.1v Lionnel Steeve(655184876) f=
rom Huawei site up at 04:04 PM","Albran Byorel","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
site on grid with U=3D54.1v Lionnel Steeve(655184876) from Huawei site up a=
t 04:04 PM","alexandre.kamal@ihstowers.com","425","27-11-2024 14:59:07","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003695290","M=
endong vallee","","27-11-2024 14:46:43","27-11-2024 14:29:34","27-11-2024 1=
5:18:35","grid outage, site went down due to Grid bad voltage// he did a br=
idge on good phase Site on Grid","Fanda Brice","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","grid outage, site went down d=
ue to Grid bad voltage// he did a bridge on good phase Site on Grid","alexa=
ndre.kamal@ihstowers.com","1030","27-11-2024 14:46:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003694700","E=
ssomba","","27-11-2024 13:19:58","27-11-2024 12:54:42","27-11-2024 13:51:53=
","Grid outage site went down because Gen failed to start due to Gen batter=
y faulty // Gen manually started with external battery","Mba Lazare Herve",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid ou=
tage site went down because Gen failed to start due to Gen battery faulty /=
/ Gen manually started with external battery","stephane.nkamwa@ihstowers.co=
m","1517","27-11-2024 13:19:58","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003692816","SOA=
 UNIVERSITY STADIUM","","27-11-2024 10:35:31","27-11-2024 10:27:24","27-11-=
2024 11:10:19","Site went down due to work Team  Piere Adigono/677513091/ F=
rom LOUMARD is are working on site ""Swapp PWC""//End of work    ","Siligap=
 Boris","Installation Activity","Passive","Planned Activity","Installation =
Activity","Site went down due to work Team  Piere Adigono/677513091/ From L=
OUMARD is are working on site ""Swapp PWC""//End of work    ","landry.etame=
@ihstowers.com","487","27-11-2024 10:35:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003692030","O=
lembe-Terminus","","27-11-2024 09:19:20","27-11-2024 09:11:15","27-11-2024 =
09:24:15","Grid outage, site went down due to main gen faulty // Grid retur=
n","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid outage, site went down due to main gen faulty // Grid ret=
urn","stephane.nkamwa@ihstowers.com","486","27-11-2024 09:19:20","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003691253","Akak-Nko=
zoa-MTN-IHS","","27-11-2024 08:23:10","27-11-2024 08:14:15","27-11-2024 08:=
23:35","Cascaded Incident from TTO3622846","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","grid outage, site down be=
fore DG started due to poor backup   //  Grid return","system","265816","27=
-11-2024 08:23:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003690384","H=
-General-Yde","","27-11-2024 05:16:22","27-11-2024 05:07:11","27-11-2024 09=
:45:26","No power issue on site ,site on Grid with Ubaie=3D54.4  V Synphori=
en of huawei is informed","Siligap Boris","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e ,site on Grid with Ubaie=3D54.4  V Synphorien of huawei is informed","den=
is.mballa@ihstowers.com","552","27-11-2024 05:16:22","Sagemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0003690293","Nko=
abang entree carriere","","27-11-2024 04:42:25","27-11-2024 04:40:30","27-1=
1-2024 04:50:30","No power issue on site U=3D54,6v site on grid Tx fme Lion=
nel steeve of huawei is informed","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site U=3D54,6v site on grid Tx fme Lionnel steeve of huawei is info=
rmed","rouselle.schoune@ihstowers.com","116","27-11-2024 04:42:25","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003689312","Mamb",""=
,"26-11-2024 22:54:13","26-11-2024 22:40:35","27-11-2024 00:14:41","Cascade=
d Incident from TTO3620564","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage ,site went down because Gen =
started and stopped due to  main alternator  is faulty//He  started manuall=
y  the second GEN","system","285807","26-11-2024 22:54:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0003689308","Eseka OC=
M","","26-11-2024 22:54:12","26-11-2024 22:40:35","27-11-2024 00:14:41","Ca=
scaded Incident from TTO3620564","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage ,site went down because=
 Gen started and stopped due to  main alternator  is faulty//He  started ma=
nually  the second GEN","system","285806","26-11-2024 22:54:12","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003689310","Song-bon=
g","","26-11-2024 22:54:12","26-11-2024 22:40:35","27-11-2024 00:14:41","Ca=
scaded Incident from TTO3620564","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage ,site went down because=
 Gen started and stopped due to  main alternator  is faulty//He  started ma=
nually  the second GEN","system","285808","26-11-2024 22:54:12","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003689305","Ngog Map=
ubi","","26-11-2024 22:54:11","26-11-2024 22:40:35","27-11-2024 00:14:41","=
Cascaded Incident from TTO3620564","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage ,site went down becau=
se Gen started and stopped due to  main alternator  is faulty//He  started =
manually  the second GEN","system","285809","26-11-2024 22:54:11","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003689302","Ndogbess=
ol","","26-11-2024 22:54:10","26-11-2024 22:40:35","27-11-2024 00:14:41","C=
ascaded Incident from TTO3620564","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage ,site went down becaus=
e Gen started and stopped due to  main alternator  is faulty//He  started m=
anually  the second GEN","system","285804","26-11-2024 22:54:10","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003689301","Eseka To=
wn","","26-11-2024 22:54:10","26-11-2024 22:40:35","27-11-2024 00:14:41","C=
ascaded Incident from TTO3620564","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage ,site went down becaus=
e Gen started and stopped due to  main alternator  is faulty//He  started m=
anually  the second GEN","system","285806","26-11-2024 22:54:10","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0003689299","Boumnyeb=
el OCM","","26-11-2024 22:54:10","26-11-2024 22:40:35","27-11-2024 00:14:41=
","Cascaded Incident from TTO3620564","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage ,site went down be=
cause Gen started and stopped due to  main alternator  is faulty//He  start=
ed manually  the second GEN","system","285804","26-11-2024 22:54:10","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003688890","Nkongtoc=
k","","26-11-2024 21:45:32","26-11-2024 21:29:31","26-11-2024 21:32:16","Ca=
scaded Incident from TTO3620057","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site Ubaie=3D53.4V s=
ite on Grid. The Tx FME Georges  //697461814 From Huawei is informed.","sys=
tem","961","26-11-2024 21:45:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003688886","Ebeba","=
","26-11-2024 21:45:31","26-11-2024 21:29:31","26-11-2024 21:32:16","Cascad=
ed Incident from TTO3620057","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site Ubaie=3D53.4V site on G=
rid. The Tx FME Georges  //697461814 From Huawei is informed.","system","27=
5521","26-11-2024 21:45:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0003688888","OKOA Pea=
ge","","26-11-2024 21:45:31","26-11-2024 21:29:31","26-11-2024 21:32:16","C=
ascaded Incident from TTO3620057","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubaie=3D53.4V site=
 on Grid. The Tx FME Georges  //697461814 From Huawei is informed.","system=
","960","26-11-2024 21:45:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0003688885","Nkenglik=
ok","","26-11-2024 21:45:31","26-11-2024 21:29:31","26-11-2024 21:32:16","C=
ascaded Incident from TTO3620057","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site Ubaie=3D53.4V =
site on Grid. The Tx FME Georges  //697461814 From Huawei is informed.","sy=
stem","275520","26-11-2024 21:45:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0003688887","Nomayos-=
IHS","","26-11-2024 21:45:31","26-11-2024 21:29:31","26-11-2024 21:32:16","=
Cascaded Incident from TTO3620057","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site Ubaie=3D53.4V sit=
e on Grid. The Tx FME Georges  //697461814 From Huawei is informed.","syste=
m","960","26-11-2024 21:45:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003688889","Mambine"=
,"","26-11-2024 21:45:31","26-11-2024 21:29:31","26-11-2024 21:32:16","Casc=
aded Incident from TTO3620057","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubaie=3D53.4V site on=
 Grid. The Tx FME Georges  //697461814 From Huawei is informed.","system","=
960","26-11-2024 21:45:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0003688884","Mbankomo=
 IHS","","26-11-2024 21:45:30","26-11-2024 21:29:31","26-11-2024 21:32:16",=
"Cascaded Incident from TTO3620057","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site Ubaie=3D53.4V si=
te on Grid. The Tx FME Georges  //697461814 From Huawei is informed.","syst=
em","275521","26-11-2024 21:45:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0003688883","Mandoumb=
a OCM","","26-11-2024 21:45:30","26-11-2024 21:29:31","26-11-2024 21:32:16"=
,"Cascaded Incident from TTO3620057","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site Ubaie=3D53.=
4V site on Grid. The Tx FME Georges  //697461814 From Huawei is informed.",=
"system","959","26-11-2024 21:45:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0003688868","Mfou EPC=
","","26-11-2024 21:40:41","26-11-2024 21:29:59","26-11-2024 22:33:57","Cas=
caded Incident from TTO3620064","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because gen failed t=
o start due to grid bad voltage and no RCP // Gen manually started","system=
","275655","26-11-2024 21:40:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0003688821","M=
fou OCM","IHS_YND_674","26-11-2024 21:39:28","26-11-2024 21:29:59","26-11-2=
024 22:33:57","site went down because gen failed to start due to grid bad v=
oltage and no RCP // Gen manually started","Mba Lazare Herve","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","site went down=
 because gen failed to start due to grid bad voltage and no RCP // Gen manu=
ally started","ludivine.ngamaleu@ihstowers.com","569","26-11-2024 21:39:28"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0003688816","N=
omayos","IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_697, I=
HS_YND_330, IHS_YND_350, IHS_YND_349","26-11-2024 21:37:42","26-11-2024 21:=
29:31","26-11-2024 21:32:16","No power issue on site Ubaie=3D53.4V site on =
Grid. The Tx FME Georges  //697461814 From Huawei is informed.","Fanda Bric=
e","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue on site Ubaie=3D53.4V site on Grid. The Tx FM=
E Georges  //697461814 From Huawei is informed.","ludivine.ngamaleu@ihstowe=
rs.com","492","26-11-2024 21:37:42","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003688607","Ole=
mbe MTN","","26-11-2024 21:09:33","26-11-2024 21:06:25","26-11-2024 23:59:4=
9","Grid fluctuation site went down because Gen failed to start due to Grid=
 bad voltage and RCP on site // He bypass the Grid and Gen manually Started=
","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Grid Ou=
tage Issue","Grid fluctuation site went down because Gen failed to start du=
e to Grid bad voltage and RCP on site // He bypass the Grid and Gen manuall=
y Started","dorothy.djantio@ihstowers.com","189","26-11-2024 21:09:33","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0003688499","T=
SINGA VILLAGE 2","","26-11-2024 20:52:10","26-11-2024 20:48:04","26-11-2024=
 21:10:16","site went down duE to CB 125A dijoncted in the PWC// he reamed =
the CB 125A) ","Delor Telezing","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Circuit Breaker Issue","site went down duE to CB 125A di=
joncted in the PWC// he reamed the CB 125A) ","ludivine.ngamaleu@ihstowers.=
com","247","26-11-2024 20:52:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003688186","S=
OA UNIVERSITY STADIUM","","26-11-2024 20:19:37","26-11-2024 20:14:33","26-1=
1-2024 23:11:35","Site went down due to work Team  Piere Adigono/677513091/=
 From LOUMARD is are working on site ""Swapp PWC""//End of work//SOA","Sili=
gap Boris","Installation Activity","Passive","Planned Activity","Installati=
on Activity","Site went down due to work Team  Piere Adigono/677513091/ Fro=
m LOUMARD is are working on site ""Swapp PWC""//End of work//SOA","ludivine=
.ngamaleu@ihstowers.com","305","26-11-2024 20:19:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003688161","M=
efou-Assi","","26-11-2024 20:13:59","26-11-2024 20:06:53","26-11-2024 20:10=
:01","No power issue on site , Ubaie=3D53.3 V site On Grid   The Tx FME Geo=
rges 697461814 from Huawei is informed. Notice that we have Disjunction at =
BTS OCM.","Fanda Brice","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site , Ubaie=3D53.3 V=
 site On Grid   The Tx FME Georges 697461814 from Huawei is informed. Notic=
e that we have Disjunction at BTS OCM.","ludivine.ngamaleu@ihstowers.com","=
426","26-11-2024 20:13:59","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003687692","SOA=
 UNIVERSITY STADIUM","","26-11-2024 19:06:34","26-11-2024 18:39:18","26-11-=
2024 19:38:43","Site went down due to work Team  Piere Adigono/677513091/ F=
rom LOUMARD is are working on site ""Swapp PWC""//End of work ","Siligap Bo=
ris","Equipment Replacement","Passive","Planned Activity","Planned Activity=
 - Passive","Site went down due to work Team  Piere Adigono/677513091/ From=
 LOUMARD is are working on site ""Swapp PWC""//End of work ","dorothy.djant=
io@ihstowers.com","1698","26-11-2024 19:06:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003687471","Akak-Nko=
zoa-MTN-IHS","","26-11-2024 18:30:20","26-11-2024 18:24:19","26-11-2024 18:=
27:12","Cascaded Incident from TTO3618501","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo outage, site down be=
fore DG started due to poor backup // Eneo return","system","265299","26-11=
-2024 18:30:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0003687206","SAA Entr=
ance","","26-11-2024 17:58:10","26-11-2024 17:44:20","26-11-2024 18:14:06",=
"Cascaded Incident from TTO3618100","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to Grid bad vol=
tage,and Gen failed to start ,No rcp//he bypassed Grid and started the Gen"=
,"system","1216995","26-11-2024 17:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003687105","Saa","",=
"26-11-2024 17:54:20","26-11-2024 17:44:20","26-11-2024 18:14:06","Cascaded=
 Incident from TTO3618100","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to Grid bad voltage,and =
Gen failed to start ,No rcp//he bypassed Grid and started the Gen","system"=
,"1216995","26-11-2024 17:54:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0003687101","S=
AA 2","IHS_YND_542, IHS_YND_405","26-11-2024 17:53:26","26-11-2024 17:39:20=
","26-11-2024 18:14:28","Site went down due to Grid bad voltage,and Gen fai=
led to start ,No rcp//he bypassed Grid and started the Gen","Parker Tchoup"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Site went down due to Grid bad voltage,and Gen failed to start ,No rcp//he =
bypassed Grid and started the Gen","dorothy.djantio@ihstowers.com","848","2=
6-11-2024 17:53:26","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003687002","BAT=
A Mokolo OCM","","26-11-2024 17:34:39","26-11-2024 17:29:24","26-11-2024 17=
:38:41","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Sp=
ace to deploy a MDG//Grid Restored","dorothy.djantio@ihstowers.com","316","=
26-11-2024 17:34:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003686914","M=
ANGUIERS CHAPELLE","","26-11-2024 17:21:59","26-11-2024 17:19:54","26-11-20=
24 18:42:19","Site went down due to works SS IHS Atangana is working on Sit=
e// end Off Work","Fabrice Pouakam","Equipment Replacement","Passive","Plan=
ned Activity","Planned Activity - Passive","Site went down due to works SS =
IHS Atangana is working on Site// end Off Work","ludivine.ngamaleu@ihstower=
s.com","126","26-11-2024 17:21:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0003686780","N=
kongtock","","26-11-2024 16:54:56","26-11-2024 16:49:49","26-11-2024 18:36:=
01","Hybrid Gen Site: site went down because of the dysfunctioning of hybri=
d system // He reset Gen card and started Gen","Kemeni Franklin","Equipment=
 Repair","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: site went dow=
n because of the dysfunctioning of hybrid system // He reset Gen card and s=
tarted Gen","ludivine.ngamaleu@ihstowers.com","308","26-11-2024 16:54:56","=
Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003686753","Nsi=
meyong Terre Rouge","","26-11-2024 16:50:14","26-11-2024 16:48:06","26-11-2=
024 16:59:29","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen started automatically","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen started auto=
matically","dorothy.djantio@ihstowers.com","129","26-11-2024 16:50:14","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003686146","A=
fanoya","","26-11-2024 15:52:14","26-11-2024 15:49:08","26-11-2024 15:50:36=
","Active//No power issue on site , Ubaie=3D54.4V site On GridThe Tx FME Ge=
orges (697461814 ) From Huawei is Working on Site.","Hyemafo Gildas","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue on site , Ubaie=3D54.4V site On GridThe Tx FME=
 Georges (697461814 ) From Huawei is Working on Site.","ludivine.ngamaleu@i=
hstowers.com","187","26-11-2024 15:52:14","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003685682","NYO=
M FACE MAETUR","","26-11-2024 15:04:54","26-11-2024 14:02:44","26-11-2024 1=
5:28:27","Grid Outage landlord has forbiden to start the Gen Because the No=
ise // Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Emergency Stop","Grid Outage landlord has forbiden to start th=
e Gen Because the Noise // Grid Restored","dorothy.djantio@ihstowers.com","=
3731","26-11-2024 15:04:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_796","NOCINC0003685139","Nkoabang=
 Ebolmedjock","","26-11-2024 13:54:57","26-11-2024 12:09:38","26-11-2024 12=
:10:29","Cascaded Incident from TTO3615838","Mba Lazare Herve","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue, site down =
due to Huawei fiber cut","system","273203","26-11-2024 13:54:57","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0003685055","S=
OA TOWN","","26-11-2024 13:42:55","26-11-2024 13:22:52","26-11-2024 14:01:4=
5","Grid outage site went down because Gen stopped with alarm Gen under fre=
quency // He reset the Gen card and Gen manually started","Siligap Boris","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage =
site went down because Gen stopped with alarm Gen under frequency // He res=
et the Gen card and Gen manually started","alexandre.kamal@ihstowers.com","=
1204","26-11-2024 13:42:55","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003684861","SOA=
 UNIVERSITY STADIUM","","26-11-2024 12:58:36","26-11-2024 12:54:42","26-11-=
2024 13:17:03","Site went down due to work Team  Piere Adigono/677513091/ F=
rom LOUMARD is are working on site ""Swapp PWC""//End of work","Siligap Bor=
is","Equipment Replacement","Passive","Planned Activity","Planned Activity =
- Passive","Site went down due to work Team  Piere Adigono/677513091/ From =
LOUMARD is are working on site ""Swapp PWC""//End of work","kamga.virgile@i=
hstowers.com","908","26-11-2024 12:58:36","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0003683214","ETO=
UDI Entree du palais","","26-11-2024 11:20:37","26-11-2024 11:12:18","26-11=
-2024 11:39:39","site went down due to work Team William Djeumo of IHS work=
ing on site :restored the phase Eneo on site//End of Work","Fabrice Pouakam=
","Installation Activity","Passive","Planned Activity","Installation Activi=
ty","site went down due to work Team William Djeumo of IHS working on site =
:restored the phase Eneo on site//End of Work","kamga.virgile@ihstowers.com=
","500","26-11-2024 11:20:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003682766","Nkolo II=
 New","","26-11-2024 10:47:30","26-11-2024 10:34:28","26-11-2024 12:56:51",=
"Cascaded Incident from TTO3613397","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage,gen ran till fuel s=
hortage//Refueling done","system","271868","26-11-2024 10:47:30","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003682747","M=
imboman-Village","IHS_YND_709","26-11-2024 10:43:35","26-11-2024 10:34:28",=
"26-11-2024 12:56:51","grid outage,gen ran till fuel shortage//Refueling do=
ne","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outage","gr=
id outage,gen ran till fuel shortage//Refueling done","alexandre.kamal@ihst=
owers.com","548","26-11-2024 10:43:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003682213","E=
kombitie","","26-11-2024 09:28:29","26-11-2024 09:14:23","26-11-2024 09:52:=
03","grid bad voltage,and gen failed to start//bypassed grid and started th=
e gen","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","grid bad voltage,and gen failed to start//bypassed =
grid and started the gen","alexandre.kamal@ihstowers.com","847","26-11-2024=
 09:28:29","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003681682","NYO=
M FACE MAETUR","","26-11-2024 07:42:54","26-11-2024 07:32:47","26-11-2024 0=
9:07:25","grid bad voltage, landlord has forbiden to start the Gen Because =
the Noise// grid stabilzed","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Emergency Stop","grid bad voltage, landlord has forbiden=
 to start the Gen Because the Noise// grid stabilzed","kamga.virgile@ihstow=
ers.com","608","26-11-2024 07:42:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003680908","A=
WAE OCM","","26-11-2024 04:31:52","26-11-2024 04:24:33","26-11-2024 07:41:5=
6","grid bad voltage,and gen failed to start,no rcp//bypassed grid and star=
ted the gen","Mba Lazare Herve","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","grid bad voltage,and gen failed to start//by=
passed grid and started the gen","emmanuel.ghani@ihstowers.com","441","26-1=
1-2024 04:31:52","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003680533","BAT=
A Mokolo OCM","","26-11-2024 02:07:14","26-11-2024 02:01:08","26-11-2024 02=
:49:00","grid outage,no space to deploy a mobil gen// Grid power return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid o=
utage,no space to deploy a mobil gen// Grid power return","christian.fonkou=
@ihstowers.com","367","26-11-2024 02:07:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003680311","B=
astos Bethesda","","26-11-2024 01:03:23","26-11-2024 01:01:47","26-11-2024 =
01:03:34","Grid outage,site went down before DG start : Poor Batteries Back=
up //Grid return","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage,site went down before DG sta=
rt : Poor Batteries Backup //Grid return","emmanuel.ghani@ihstowers.com","9=
8","26-11-2024 01:03:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0003680308","H=
-Prince","","26-11-2024 01:01:43","26-11-2024 01:00:35","26-11-2024 02:45:3=
2","Active// No power issue on site, Ubaie=3D54,7V site on Grid . Tx FME Br=
ice (650214096) from Huawei is informed","Mboua Thierry","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// No power issue on site, Ubaie=3D54,7V site on Grid . Tx FME Brice (65021=
4096) from Huawei is informed","emmanuel.ghani@ihstowers.com","69","26-11-2=
024 01:01:43","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003680285","Mok=
olo Yaounde","","26-11-2024 00:53:39","26-11-2024 00:44:33","26-11-2024 01:=
05:03","Grid outage, No space to deploy MDG// Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No spac=
e to deploy MDG// Grid return","christian.fonkou@ihstowers.com","547","26-1=
1-2024 00:53:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0003680274","S=
apeur","","26-11-2024 00:45:44","26-11-2024 00:43:18","26-11-2024 01:07:48"=
,"Grid outage, site went before gen started due to poor battery backup// Ge=
n started automatically","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went before gen=
 started due to poor battery backup// Gen started automatically","emmanuel.=
ghani@ihstowers.com","148","26-11-2024 00:45:44","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_026","NOCINC0003680272","ENAM","","=
26-11-2024 00:44:17","","","Grid outage, Site alarming on battery// Grid re=
turn","","Warning","Warning","POWER","Warning - Site on Battery","Grid outa=
ge, Site alarming on battery// Grid return","joelle.ekessi@ihstowers.com","=
64","26-11-2024 00:44:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003680162","A=
fanoya","","26-11-2024 00:15:16","26-11-2024 00:07:12","26-11-2024 01:30:26=
","Active//No power issue, U=3D54.4V on grid Tx FME Georges /697461814/ Fro=
m huawei is informed","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, =
U=3D54.4V on grid Tx FME Georges /697461814/ From huawei is informed","emma=
nuel.ghani@ihstowers.com","485","26-11-2024 00:15:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0003680087","N=
kongtock","","26-11-2024 00:06:28","26-11-2024 00:01:22","26-11-2024 01:35:=
38","Solar Gen: Site went down because Gen ran until fuel shortage// Refuel=
ing Done","Kemeni Franklin","Fuel Outage","Passive","Diesel","Diesel Outage=
","Solar Gen: Site went down because Gen ran until fuel shortage// Refuelin=
g Done","emmanuel.ghani@ihstowers.com","307","26-11-2024 00:06:28","Sagemco=
m CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003679913","NYO=
M FACE MAETUR","","25-11-2024 23:25:15","25-11-2024 23:24:10","25-11-2024 2=
3:50:09","Grid fluctuation landlord has forbiden to start the Gen Because t=
he Noise //Grid stabilized","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Emergency Stop","Grid fluctuation landlord has forbiden =
to start the Gen Because the Noise //Grid stabilized","christian.fonkou@ihs=
towers.com","66","25-11-2024 23:25:15","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003679353","Nom=
ayos montee Meche","","25-11-2024 21:56:21","25-11-2024 21:31:13","25-11-20=
24 22:13:32","Grid outage, site went down because the bay DPC disfunctionni=
ng//He blocked the PWC DPC, Site on Grid","Fanda Brice","Equipment Repair",=
"Passive","Control Panel","Panel Distribution Board","Grid outage, site wen=
t down because the bay DPC disfunctionning//He blocked the PWC DPC, Site on=
 Grid","rouselle.schoune@ihstowers.com","1508","25-11-2024 21:56:21","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003679325","M=
vog-Manga","","25-11-2024 21:48:59","25-11-2024 21:46:45","25-11-2024 22:30=
:53","Site went down due to insufficient of rectifiers (06) due to load inc=
rease// Site stabilized (rectifier to be added)","Albran Byorel","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","Site went down due to in=
sufficient of rectifiers (06) due to load increase// Site stabilized (recti=
fier to be added)","denis.mballa@ihstowers.com","136","25-11-2024 21:48:59"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0003679003","T=
SINGA VILLAGE 2","","25-11-2024 21:08:24","25-11-2024 20:59:08","25-11-2024=
 21:25:40","site went down duE to CB 125A dijoncted in the PWC// he reamed =
the CB 125A) ","Delor Telezing","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Circuit Breaker Issue","site went down duE to CB 125A di=
joncted in the PWC// he reamed the CB 125A) ","denis.mballa@ihstowers.com",=
"557","25-11-2024 21:08:24","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0003677402","Mon=
tee Jouvence","","25-11-2024 19:08:26","25-11-2024 19:04:58","25-11-2024 19=
:20:24","Grid fluctuation site went down because Gen failed to start due to=
 Grid bad voltage and RCP on site // He bypass the Grid and site on Gen","H=
yemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation site went down because Gen failed to start d=
ue to Grid bad voltage and RCP on site // He bypass the Grid and site on Ge=
n","rouselle.schoune@ihstowers.com","209","25-11-2024 19:08:26","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003677221","M=
ontee-Jouvence-II","","25-11-2024 18:49:42","25-11-2024 18:16:44","25-11-20=
24 21:35:45","ACTIVE// No  power issue on site, site on Grid with Ubaie=3D =
53.9V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed","Hyem=
afo Gildas","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","ACTIVE// No  power issue on site, site on Grid with=
 Ubaie=3D 53.9V The Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is infor=
med","denis.mballa@ihstowers.com","1979","25-11-2024 18:49:42","Sagemcom CM=
R"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003677192","Men=
dong3","","25-11-2024 18:47:31","25-11-2024 18:43:25","25-11-2024 21:21:58"=
,"Grid outage No space to deploy //Grid power return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage No space to d=
eploy //Grid power return","rouselle.schoune@ihstowers.com","247","25-11-20=
24 18:47:31","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003676585","NYO=
M FACE MAETUR","","25-11-2024 17:47:06","25-11-2024 17:41:00","25-11-2024 1=
7:47:57","Grid Outage landlord has forbiden to start the Gen Because the No=
ise //Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG G=
en","ACDG - Emergency Stop","Grid Outage landlord has forbiden to start the=
 Gen Because the Noise //Grid Restored","rouselle.schoune@ihstowers.com","3=
67","25-11-2024 17:47:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003676454","A=
fanoya","","25-11-2024 17:23:06","25-11-2024 17:14:56","25-11-2024 21:25:02=
","Active//No power issue, U=3D54V on grid Tx FME George/697461814/ From hu=
awei is informed.repetitif issue","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No p=
ower issue, U=3D54V on grid Tx FME George/697461814/ From huawei is informe=
d.repetitif issue","denis.mballa@ihstowers.com","491","25-11-2024 17:23:06"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0003675012","Men=
dong vallee","","25-11-2024 15:48:22","25-11-2024 15:42:00","25-11-2024 18:=
15:43","Active// No power issue, site is on Gen  with Ubaie=3D54.2V, the Te=
am Gilbert  (687300616) from TELE-INFRA  is Working on Site","Fanda Brice",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active// No power issue, site is on Gen  with Ubaie=3D54.2V, th=
e Team Gilbert  (687300616) from TELE-INFRA  is Working on Site","rouselle.=
schoune@ihstowers.com","383","25-11-2024 15:48:22","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003674767","N=
yanon","","25-11-2024 15:09:11","25-11-2024 15:00:01","25-11-2024 17:00:01"=
,"No power issue on site with Ubaie=3D55,1V site on Gen  The Tx Fme Gregoir=
e( 652070658)from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site with Ubaie=3D55,1V site on Gen  The Tx Fme Gregoir=
e( 652070658)from Huawei is informed
","denis.mballa@ihstowers.com","551","25-11-2024 15:09:11","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003674625","MVA=
N","","25-11-2024 14:48:40","25-11-2024 14:45:40","25-11-2024 15:11:21","Gr=
id Outage  Site went down due to Gen Overload (20Kva, 290 A)//Grid Restored=
","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid Outage  Site went down due to Gen Overload (20Kva, 290 A)//Grid Rest=
ored","rouselle.schoune@ihstowers.com","181","25-11-2024 14:48:40","Sagemco=
m CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0003674487","Ema=
na Lycee","","25-11-2024 14:30:03","25-11-2024 14:11:56","25-11-2024 19:00:=
56","Active// No power issue, Site on Grid Ubai=3D 53.4V, The TX FME Synpho=
rien/691316854/ From Huawei is working on Site.","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active// No power issue, Site on Grid Ubai=3D 53.4V, The TX FME Synphor=
ien/691316854/ From Huawei is working on Site.","olivier.kwedi@ihstowers.co=
m","1088","25-11-2024 14:30:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0003674299","P=
olytechnique","","25-11-2024 14:03:18","25-11-2024 13:56:47","25-11-2024 15=
:44:46","Site went down due to CB(125A) and CB(32A) burns on Site//He Repla=
ced the 125( A) by  Another","","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Circuit Breaker Issue","Site went down due to CB(125A) a=
nd CB(32A) burns on Site//He Replaced the 125( A) by  Another","ludivine.ng=
amaleu@ihstowers.com","392","25-11-2024 14:03:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003673402","Nkolo II=
 New","","25-11-2024 12:47:50","25-11-2024 12:41:20","25-11-2024 14:10:20",=
"Cascaded Incident from TTO3603004","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause Gen Ran Untill fuel shortage // Refueling done","system","390","25-11-=
2024 12:47:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003673396","M=
imboman-Village","IHS_YND_709","25-11-2024 12:46:29","25-11-2024 12:41:20",=
"25-11-2024 14:10:20","Grid outage, site went down because Gen Ran Untill f=
uel shortage // Refueling done","Mba Lazare Herve","Fuel Outage","Passive",=
"Diesel","Diesel Outage","Grid outage, site went down because Gen Ran Until=
l fuel shortage // Refueling done","ludivine.ngamaleu@ihstowers.com","310",=
"25-11-2024 12:46:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0003672934","Eloumdem=
 stade","","25-11-2024 11:36:40","25-11-2024 11:31:59","25-11-2024 12:32:35=
","Cascaded Incident from TTO3602466","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to 1/3 rectifie=
rs faulty //He removed the faulty rectifier,waiting for replacement.","syst=
em","268262","25-11-2024 11:36:40","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003672923","Sim=
bock MTN","IHS_YND_793","25-11-2024 11:34:19","25-11-2024 11:31:59","25-11-=
2024 12:32:35","Site went down due to 1/3 rectifiers faulty //He removed th=
e faulty rectifier,waiting for replacement.","Fanda Brice","Equipment Repai=
r","Passive","Rectifier","Rectifier Module","Site went down due to 1/3 rect=
ifiers faulty //He removed the faulty rectifier,waiting for replacement.","=
olivier.kwedi@ihstowers.com","141","25-11-2024 11:34:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003672847","Akak-Nko=
zoa-MTN-IHS","","25-11-2024 11:25:31","25-11-2024 11:19:40","25-11-2024 11:=
47:09","Cascaded Incident from TTO3602376","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo outage, site down be=
fore DG started due to poor backup (power resolved at 11:21 AM, but site re=
mainde down, and power reset done the site was up) // DG started automatica=
lly
","system","1225711","25-11-2024 11:25:31","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0003671045","Mon=
tee Jouvence","","25-11-2024 08:13:11","25-11-2024 08:04:00","25-11-2024 08=
:10:53","Grid Bad voltage, Site went down due to Eneo phase missing// He di=
d a bridge on Good phase","Hyemafo Gildas","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","Grid Bad voltage, Site went down =
due to Eneo phase missing// He did a bridge on Good phase","olivier.kwedi@i=
hstowers.com","552","25-11-2024 08:13:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003670815","T=
singa","","25-11-2024 07:32:02","25-11-2024 07:27:57","25-11-2024 07:52:52"=
,"Grid fluctuation, Site went down before Gen start due to poor backup// Gr=
id return","Mboua Thierry","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid fluctuation, Site went down before Gen sta=
rt due to poor backup// Grid return","ludivine.ngamaleu@ihstowers.com","246=
","25-11-2024 07:32:02","Sagemcom CMR"
"Closed Complete","Warning","T0459","IHS_YND_240","NOCINC0003670715","Monte=
e Jouvence","","25-11-2024 07:02:18","","","Site on battery due to grid bad=
 voltage//BYpass GRID and manually start of DG.","Hyemafo Gildas","Warning"=
,"Warning","POWER","Warning - Site on Battery","Site on battery due to grid=
 bad voltage//BYpass GRID and manually start of DG.","dorothy.djantio@ihsto=
wers.com","492","25-11-2024 07:02:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003670706","A=
fanoya","","25-11-2024 06:58:46","25-11-2024 06:50:40","25-11-2024 06:51:21=
","Active//No power issue, U=3D54V on grid Tx FME George/697461814/ From hu=
awei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, U=3D=
54V on grid Tx FME George/697461814/ From huawei is informed","ludivine.nga=
maleu@ihstowers.com","487","25-11-2024 06:58:46","Sagemcom CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0003670412","TON=
GOLO SNEC","","25-11-2024 05:26:41","25-11-2024 03:41:34","25-11-2024 04:19=
:42","Grid fluctuation, site went down due to lack of 01 phase on site // h=
e did a bridge with a good phase, Site on Grid","Fabrice Pouakam","Grid Sup=
ply","Passive","Grid","National Grid - Grid Incomplete Phase","Grid fluctua=
tion, site went down due to lack of 01 phase on site // he did a bridge wit=
h a good phase, Site on Grid","landry.etame@ihstowers.com","6308","25-11-20=
24 05:26:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0003669936","C=
RF Nkoabang","","25-11-2024 03:02:51","25-11-2024 02:46:37","25-11-2024 10:=
48:13","No power issue site on grid with U=3D54v Georges from Huawei is inf=
ormed//site up at 07:40 AM","Mba Lazare Herve","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on grid with U=3D54v Georges from Huawei is informed//site up at 07:40 =
AM","stephane.nkamwa@ihstowers.com","975","25-11-2024 03:02:51","Sagemcom C=
MR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003669192","Nko=
ulou Carriere carrefourt","","24-11-2024 23:49:39","24-11-2024 23:40:34","2=
5-11-2024 01:07:53","Grid outage site went down because Gen Started and sto=
pped with alarm low oil pressure // He added oil and Gen manually started",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid outage site went down because Gen Started and stopped with ala=
rm low oil pressure // He added oil and Gen manually started","landry.etame=
@ihstowers.com","546","24-11-2024 23:49:39","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003669119","NYO=
M FACE MAETUR","","24-11-2024 23:30:26","24-11-2024 19:04:00","25-11-2024 0=
0:16:00","Site went due to 02 faulty rectifier caused by MPR dysfunctionnin=
g // reset done and 01 rectifier added (MPR to be replace)","Fabrice Pouaka=
m","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went d=
ue to 02 faulty rectifier caused by MPR dysfunctionning // reset done and 0=
1 rectifier added (MPR to be replace)","landry.etame@ihstowers.com","15987"=
,"24-11-2024 23:30:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003669067","S=
tade-Abega","","24-11-2024 23:20:15","24-11-2024 23:01:06","24-11-2024 23:5=
8:06","Grid outage,gen fails to start due to candle faulty//Grid return ","=
Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Star=
ter","Grid outage,gen fails to start due to candle faulty//Grid return ","s=
tephane.nkamwa@ihstowers.com","1150","24-11-2024 23:20:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003668946","C=
rf-Nsam","","24-11-2024 23:02:32","24-11-2024 22:54:25","25-11-2024 00:04:2=
5","Site went down due to PWC overload ( 24 kw, 270 A)// he reduice the Loa=
d and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Site went down due to PWC overload ( 24=
 kw, 270 A)// he reduice the Load and Site is on Grid","stephane.nkamwa@ihs=
towers.com","488","24-11-2024 23:02:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0003668896","T=
SINGA VILLAGE 2","","24-11-2024 22:58:08","24-11-2024 20:25:58","25-11-2024=
 02:15:42","Active//No power issue on site, Site on Battery UBAIE=3D49.2V (=
start threshold=3D 47.5V) synphorien (675295205) From huawei is informed. N=
otice that we have disjunction at BTS","Delor Telezing","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue on site, Site on Battery UBAIE=3D49.2V (start threshold=3D =
47.5V) synphorien (675295205) From huawei is informed. Notice that we have =
disjunction at BTS","stephane.nkamwa@ihstowers.com","9131","24-11-2024 22:5=
8:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003668028","M=
essa-Carriere OCM","","24-11-2024 21:22:31","24-11-2024 21:15:27","25-11-20=
24 07:10:56","Access issue due to Lanlord(site went down duE to CB 125A dij=
oncted in the PWC// he reamed the CB 125A) ","","Access Denial","Lease Or L=
egal","Landlord Related Issues","Access Issue - Land Lord","Access issue du=
e to Lanlord(site went down duE to CB 125A dijoncted in the PWC// he reamed=
 the CB 125A) ","emmanuel.ghani@ihstowers.com","425","24-11-2024 21:22:31",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003668016","B=
ATA-Mokolo","","24-11-2024 21:21:30","24-11-2024 21:18:07","24-11-2024 22:1=
4:09","Grid outage, No space to deploy MDG// Grid power return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No=
 space to deploy MDG// Grid power return","emmanuel.ghani@ihstowers.com","2=
04","24-11-2024 21:21:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003667977","M=
elen Ba'aba","","24-11-2024 21:20:06","24-11-2024 20:59:19","24-11-2024 21:=
37:20","Site went down because cb(125A) tripped in DC Box who feeds equipme=
nts OCM// CB put back on","Siligap Boris","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down because=
 cb(125A) tripped in DC Box who feeds equipments OCM// CB put back on","emm=
anuel.ghani@ihstowers.com","1249","24-11-2024 21:20:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003667831","M=
vog-Manga","","24-11-2024 21:18:19","24-11-2024 21:01:14","24-11-2024 22:21=
:14","Site went down because CB(125) of power cabinet disjuncted // CB put =
back on","Albran Byorel","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Circuit Breaker Issue","Site went down because CB(125) of power=
 cabinet disjuncted // CB put back on","emmanuel.ghani@ihstowers.com","1027=
","24-11-2024 21:18:19","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003667742","N=
yanon","","24-11-2024 21:10:46","24-11-2024 21:02:41","24-11-2024 21:21:59"=
,"Hybrid Gen Site: site went down because of the dysfunctioning of hybrid s=
ystem // He reset Gen card and started Gen","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: site we=
nt down because of the dysfunctioning of hybrid system // He reset Gen card=
 and started Gen","emmanuel.ghani@ihstowers.com","487","24-11-2024 21:10:46=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003667273","T=
amtam Weekend","","24-11-2024 20:26:44","24-11-2024 20:23:38","24-11-2024 2=
0:30:16","No power issue, site is on Grid with Ubaie=3D53,3  V  The TX FME =
Mbah Hosiah (674007438)  from Huawei is informed, Notice that we have disju=
nction at BTS OCM","Hyemafo Gildas","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on =
Grid with Ubaie=3D53,3  V  The TX FME Mbah Hosiah (674007438)  from Huawei =
is informed, Notice that we have disjunction at BTS OCM","emmanuel.ghani@ih=
stowers.com","187","24-11-2024 20:26:44","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0003667222","Crf=
-Mbankolo-IHS","","24-11-2024 20:19:22","24-11-2024 20:17:18","24-11-2024 2=
1:59:56","Site went down due to 1/6 rectifier faulty// He replaced rectifie=
r faulty","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","Site went down due to 1/6 rectifier faulty// He replaced rectif=
ier faulty","christian.fonkou@ihstowers.com","125","24-11-2024 20:19:22","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003667161","M=
ontee-Jouvence-II","","24-11-2024 20:05:31","24-11-2024 19:57:18","24-11-20=
24 21:00:46","site went down because CB(125A) tripped in Dcbox who feeds eq=
uipments OCM // He reamed  CB","Hyemafo Gildas","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Circuit Breaker Issue","site went down b=
ecause CB(125A) tripped in Dcbox who feeds equipments OCM // He reamed  CB"=
,"emmanuel.ghani@ihstowers.com","494","24-11-2024 20:05:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003667134","Nkolo II=
 New","","24-11-2024 20:00:40","24-11-2024 19:55:43","24-11-2024 20:00:06",=
"Cascaded Incident from TTO3596018","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because The Team=
 ADIGONO Pierre// 677513091 from LOUMADE is working on site ( SWAP GEN and =
PWC)// End of Work","system","281404","24-11-2024 20:00:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003667112","M=
imboman-Village","IHS_YND_709","24-11-2024 19:59:48","24-11-2024 19:55:43",=
"24-11-2024 20:00:06","Site went down because The Team ADIGONO Pierre// 677=
513091 from LOUMADE is working on site ( SWAP GEN and PWC)// End of Work","=
Mba Lazare Herve","Installation Activity","Passive","Planned Activity","Ins=
tallation Activity","Site went down because The Team ADIGONO Pierre// 67751=
3091 from LOUMADE is working on site ( SWAP GEN and PWC)// End of Work","em=
manuel.ghani@ihstowers.com","246","24-11-2024 19:59:48","Sagemcom CMR"
"Closed Complete","Site Down","T3214","IHS_YND_761","NOCINC0003666894","Djo=
nassi-Yde","","24-11-2024 19:23:27","24-11-2024 19:18:20","24-11-2024 19:57=
:15","Site went down due to insufficiency of rectifier on site // site stab=
ilized (02 rectifier most be added","Fabrice Pouakam","Equipment Repair","P=
assive","Rectifier","Rectifier Module","Site went down due to insufficiency=
 of rectifier on site // site stabilized (02 rectifier most be added","chri=
stian.fonkou@ihstowers.com","308","24-11-2024 19:23:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003666630","B=
itoto","","24-11-2024 18:33:07","24-11-2024 18:29:03","24-11-2024 20:34:49"=
,"site went down duer to work team TELINO / 681345277 SWAPP baie on site// =
end off work","Mba Lazare Herve","Installation Activity","Passive","Planned=
 Activity","Installation Activity","site went down duer to work team TELINO=
 / 681345277 SWAPP baie on site// end off work","emmanuel.ghani@ihstowers.c=
om","246","24-11-2024 18:33:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003666459","Afanoya"=
,"","24-11-2024 18:24:31","24-11-2024 18:19:34","24-11-2024 18:28:36","Casc=
aded Incident from TTO3595242","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because 03/08 rectifier=
s hanging//he reset rectifiers ,site on Grid","system","272531","24-11-2024=
 18:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003666458","MBALNGON=
G LYCEE","","24-11-2024 18:24:31","24-11-2024 18:19:34","24-11-2024 18:28:3=
6","Cascaded Incident from TTO3595242","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because 03/08 rect=
ifiers hanging//he reset rectifiers ,site on Grid","system","297","24-11-20=
24 18:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003666457","ELOUMDEM=
 CARRIERE","","24-11-2024 18:24:31","24-11-2024 18:19:34","24-11-2024 18:28=
:36","Cascaded Incident from TTO3595242","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because 03/08 re=
ctifiers hanging//he reset rectifiers ,site on Grid","system","272531","24-=
11-2024 18:24:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003666443","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","24-11-2024 18:22:40","24-11-=
2024 18:19:34","24-11-2024 18:28:36","Site went down because 03/08 rectifie=
rs hanging//he reset rectifiers ,site on Grid","Hyemafo Gildas","Equipment =
Repair","Passive","Rectifier","Rectifier Module","Site went down because 03=
/08 rectifiers hanging//he reset rectifiers ,site on Grid","emmanuel.ghani@=
ihstowers.com","188","24-11-2024 18:22:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003666263","B=
iteng-Maetur","","24-11-2024 17:59:58","24-11-2024 17:55:53","24-11-2024 19=
:25:31","Grid outage site went down because Gen overload (20KVA, 280A) //Gr=
id power return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage site went down because Gen overload (20KVA,=
 280A) //Grid power return","emmanuel.ghani@ihstowers.com","246","24-11-202=
4 17:59:58","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003666206","BAT=
A Mokolo OCM","","24-11-2024 17:50:21","24-11-2024 17:47:14","25-11-2024 09=
:41:11","Grid Outage No Space to deploy a MDG //Grid power return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage =
No Space to deploy a MDG //Grid power return","christian.fonkou@ihstowers.c=
om","187","24-11-2024 17:50:21","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_028","NOCINC0003665954","H-Central"=
,"","24-11-2024 17:19:40","","","Site alarming High Temp 41=B0C// Technicia=
n reported that alarm is unprouven","Paul BIBOUM","Warning","Warning","ENVI=
RONMENT","Warning - High Temperature","Site alarming High Temp 41=B0C// Tec=
hnician reported that alarm is unprouven","joelle.ekessi@ihstowers.com","71=
","24-11-2024 17:19:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003665810","M=
efou-Assi","","24-11-2024 16:57:13","24-11-2024 16:32:09","24-11-2024 16:36=
:37","No power issue on site with Ubaie=3D53V site On Grid The Tx FME Georg=
es 697461814 from Huawei is informed. Notice that we have Disjunction at BT=
S OCM.","Fanda Brice","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power issue on site with Ubaie=3D53V s=
ite On Grid The Tx FME Georges 697461814 from Huawei is informed. Notice th=
at we have Disjunction at BTS OCM.","emmanuel.ghani@ihstowers.com","1504","=
24-11-2024 16:57:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003665795","Afanoya"=
,"","24-11-2024 16:54:31","24-11-2024 16:38:16","24-11-2024 17:29:26","Casc=
aded Incident from TTO3594369","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive"," Grid fluctuation site went down becau=
se Gen failed to start due to Grid bad voltage AND No RCP on site // Grid s=
tabilized","system","264380","24-11-2024 16:54:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003665793","ELOUMDEM=
 CARRIERE","","24-11-2024 16:54:30","24-11-2024 16:38:16","24-11-2024 17:29=
:26","Cascaded Incident from TTO3594369","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive"," Grid fluctuation site went dow=
n because Gen failed to start due to Grid bad voltage AND No RCP on site //=
 Grid stabilized","system","264381","24-11-2024 16:54:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003665794","MBALNGON=
G LYCEE","","24-11-2024 16:54:30","24-11-2024 16:38:16","24-11-2024 17:29:2=
6","Cascaded Incident from TTO3594369","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive"," Grid fluctuation site went down =
because Gen failed to start due to Grid bad voltage AND No RCP on site // G=
rid stabilized","system","264380","24-11-2024 16:54:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003665684","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","24-11-2024 16:44:38","24-11-=
2024 16:38:16","24-11-2024 17:29:26"," Grid fluctuation site went down beca=
use Gen failed to start due to Grid bad voltage AND No RCP on site // Grid =
stabilized","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty"," Grid fluctuation site went down because Gen fa=
iled to start due to Grid bad voltage AND No RCP on site // Grid stabilized=
","emmanuel.ghani@ihstowers.com","384","24-11-2024 16:44:38","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_299","NOCINC0003665649","Olembe MTN=
","","24-11-2024 16:36:43","","","Site alrming because low voltage due to  =
Grid outage, and  Gen faled to start causing by Grid contactor faulty//He b=
ypass it and started the Gen manually","Fabrice Pouakam","Warning","Warning=
","POWER","Warning - Battery Low Voltage","Site alrming because low voltage=
 due to  Grid outage, and  Gen faled to start causing by Grid contactor fau=
lty//He bypass it and started the Gen manually","joelle.ekessi@ihstowers.co=
m","62","24-11-2024 16:36:43","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003665620","Ole=
mbe MTN","","24-11-2024 16:30:07","24-11-2024 16:17:10","24-11-2024 18:11:0=
1","Grid outage,Gen faled to start due Grid contactor faulty//He bypass it =
and started the Gen manually","Fabrice Pouakam","Equipment Repair","Passive=
","Control Panel","ATS-AMF Issue","Grid outage,Gen faled to start due Grid =
contactor faulty//He bypass it and started the Gen manually","christian.fon=
kou@ihstowers.com","778","24-11-2024 16:30:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0003665184","K=
amajou Building","","24-11-2024 15:34:40","24-11-2024 15:30:14","24-11-2024=
 16:00:14","Grid fluctuation site went down because Gen started and stopped=
 due to Grid bad voltage // Grid stabilized","Paul BIBOUM","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation =
site went down because Gen started and stopped due to Grid bad voltage // G=
rid stabilized","emmanuel.ghani@ihstowers.com","267","24-11-2024 15:34:40",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0003665176","Angongo"=
,"","24-11-2024 15:31:50","24-11-2024 15:25:01","24-11-2024 16:20:11","Casc=
aded Incident from TTO3593756","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Gid outage, site went down because gen st=
opped with ""low oil pressure ""// He added oil pressure and Gen manually s=
tarted","system","409","24-11-2024 15:31:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0003665171","E=
beba","IHS_YND_335","24-11-2024 15:30:56","24-11-2024 15:25:01","24-11-2024=
 16:20:11","Gid outage, site went down because gen stopped with ""low oil p=
ressure ""// He added oil pressure and Gen manually started","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gid outage,=
 site went down because gen stopped with ""low oil pressure ""// He added o=
il pressure and Gen manually started","emmanuel.ghani@ihstowers.com","356",=
"24-11-2024 15:30:56","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003665140","Nko=
lbisson usines des eaux 2","","24-11-2024 15:25:54","24-11-2024 15:07:56","=
24-11-2024 15:29:26","Grid outage ,site went down because Gen started and s=
topped due to gen overload(9kva,105 A)//He reduced load on site","TIENTCHEU=
 NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage ,site went down because Gen started and stopped due to gen ove=
rload(9kva,105 A)//He reduced load on site","christian.fonkou@ihstowers.com=
","1079","24-11-2024 15:25:54","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0003665069","Fla=
menco","","24-11-2024 15:13:17","24-11-2024 14:58:17","24-11-2024 15:32:59"=
,"Grid Outage Site went down due to Gen Card Faulty  // Grid Restored","Mbo=
ua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Coolant Pipe","=
Grid Outage Site went down due to Gen Card Faulty  // Grid Restored","chris=
tian.fonkou@ihstowers.com","901","24-11-2024 15:13:17","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_207","NOCINC0003664897","ARMP Build=
ing","","24-11-2024 14:56:36","","","Grid fluctuation, site went alarm beca=
use gen fails to start due to grid bad voltage","Mboua Thierry","Warning","=
Warning","POWER","Warning - Site on Battery","Grid fluctuation, site went a=
larm because gen fails to start due to grid bad voltage","joelle.ekessi@ihs=
towers.com","59","24-11-2024 14:56:36","Sagemcom CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0003664729","TON=
GOLO SNEC","","24-11-2024 14:42:28","24-11-2024 14:38:29","24-11-2024 14:52=
:54","Grid fluctuation, site went down due to lack of 01 phase on site // s=
ite stabilzed","Fabrice Pouakam","Grid Supply","Passive","Grid","National G=
rid - Grid Incomplete Phase","Grid fluctuation, site went down due to lack =
of 01 phase on site // site stabilzed","christian.fonkou@ihstowers.com","24=
0","24-11-2024 14:42:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0003664727","S=
hell-Nsimeyong","","24-11-2024 14:42:11","24-11-2024 14:34:15","24-11-2024 =
15:35:34","Site on DG due to grid outage,DG has been stopped by Children wh=
ich playing alongside//Manually start of DG.","MINKA NICOLAS","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Emergency Stop","Site on DG due to grid =
outage,DG has been stopped by Children which playing alongside//Manually st=
art of DG.","emmanuel.ghani@ihstowers.com","477","24-11-2024 14:42:11","Sag=
emcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003664698","Tsi=
nga","","24-11-2024 14:39:04","24-11-2024 14:36:02","24-11-2024 15:44:41","=
Grid outage, Site went down before Gen start due to poor battery backup// G=
en started manually","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down before Ge=
n start due to poor battery backup// Gen started manually","christian.fonko=
u@ihstowers.com","183","24-11-2024 14:39:04","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0003664650","Ako=
k Ndoe Yde","","24-11-2024 14:34:25","24-11-2024 14:10:27","24-11-2024 15:2=
6:10","Grid outage,site went down before Gen start due to poor battery back=
up// he started the Gen manually","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage,site went d=
own before Gen start due to poor battery backup// he started the Gen manual=
ly","christian.fonkou@ihstowers.com","1439","24-11-2024 14:34:25","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003664640","Nko=
ulou Carriere carrefourt","","24-11-2024 14:32:29","24-11-2024 14:24:30","2=
4-11-2024 15:42:23","Grid Outage,site went because   Gen Failed to start du=
e to The Static charger faulty and Gen battery discharged// Gen manually st=
arted with external battery","Mba Lazare Herve","Equipment Repair","Passive=
","ACDG Gen","ACDG - Charging Alternator","Grid Outage,site went because   =
Gen Failed to start due to The Static charger faulty and Gen battery discha=
rged// Gen manually started with external battery","christian.fonkou@ihstow=
ers.com","480","24-11-2024 14:32:29","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0003664563","Fou=
da rue des g=E9n=E9raux","","24-11-2024 14:28:39","24-11-2024 14:06:40","24=
-11-2024 16:38:22","Site went down due to work The team yovo (698529863) fr=
om   SFM working on site (Swap PWC ) // End of work ","Delor Telezing","Ins=
tallation Activity","Passive","Planned Activity","Installation Activity","S=
ite went down due to work The team yovo (698529863) from   SFM working on s=
ite (Swap PWC ) // End o","christian.fonkou@ihstowers.com","1319","24-11-20=
24 14:28:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003664111","Nkolo II=
 New","","24-11-2024 13:43:41","24-11-2024 13:39:01","24-11-2024 18:15:45",=
"Cascaded Incident from TTO3592482","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because  The Tea=
m  ADIGONO Pierre// 677513091  from LOUMADE is working on site ( SWAP GEN  =
and PWC)// End of Work","system","282404","24-11-2024 13:43:41","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003664062","M=
imboman-Village","IHS_YND_709","24-11-2024 13:42:08","24-11-2024 13:39:01",=
"24-11-2024 18:15:45","Site went down because  The Team  ADIGONO Pierre// 6=
77513091  from LOUMADE is working on site ( SWAP GEN  and PWC)// End of Wor=
k","Mba Lazare Herve","Installation Activity","Passive","Planned Activity",=
"Installation Activity","Site went down because  The Team  ADIGONO Pierre//=
 677513091  from LOUMADE is working on site ( SWAP GEN  and PWC)// End of W=
ork","denis.mballa@ihstowers.com","188","24-11-2024 13:42:08","Sagemcom CMR=
"
"Closed Complete","Site Down","T0539","IHS_YND_034","NOCINC0003664039","EMI=
A MTN","","24-11-2024 13:39:00","24-11-2024 13:33:01","24-11-2024 13:59:54"=
,"Grid outage, no space to deploy // Grid power return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage, no space t=
o deploy // Grid power return","rouselle.schoune@ihstowers.com","360","24-1=
1-2024 13:39:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0003663916","R=
d-Pt-Express","","24-11-2024 13:28:04","24-11-2024 13:14:58","24-11-2024 13=
:55:22","Grid outage No space to deploy //Grid power return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No spa=
ce to deploy //Grid power return","denis.mballa@ihstowers.com","787","24-11=
-2024 13:28:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003663824","B=
iteng","","24-11-2024 13:14:58","24-11-2024 12:51:43","24-11-2024 13:48:43"=
,"Grid outage, Site went because Gen started and stopped due to High temp//=
 He added water and started Gen manualy","Mba Lazare Herve","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","G=
rid outage, Site went because Gen started and stopped due to High temp// He=
 added water and started Gen manualy","denis.mballa@ihstowers.com","1396","=
24-11-2024 13:14:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003663803","B=
ATA-Mokolo","","24-11-2024 13:09:01","24-11-2024 12:46:46","24-11-2024 16:1=
7:22","Grid outage No space to deploy //Grid power return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No space=
 to deploy //Grid power return","denis.mballa@ihstowers.com","1337","24-11-=
2024 13:09:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003663792","Akak-Nko=
zoa-MTN-IHS","","24-11-2024 13:06:40","24-11-2024 12:38:10","24-11-2024 14:=
57:59","Cascaded Incident from TTO3592169","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","eneo outage GEN stop due =
to high temp //radiator cleaned and GEN in Automatic mode","system","285877=
","24-11-2024 13:06:40","Sagemcom CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0003663788","Clu=
b France","","24-11-2024 13:06:03","24-11-2024 13:02:02","24-11-2024 13:55:=
41","Grid Outage//Grid Restored","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Outage Issue","Grid Outage//Grid Restored","rouselle.schoune@=
ihstowers.com","242","24-11-2024 13:06:03","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0003663696","Ngo=
a Ekelle","","24-11-2024 12:49:02","24-11-2024 12:26:56","24-11-2024 13:44:=
56","Site on DG due to grid outage,DG stopped due to fuel shortage // Refue=
ling done,site on DG.","Paul BIBOUM","Fuel Outage","Passive","Diesel","Dies=
el Outage","Site on DG due to grid outage,DG stopped due to fuel shortage /=
/ Refueling done,site on DG.","rouselle.schoune@ihstowers.com","1326","24-1=
1-2024 12:49:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003663488","Scalom-I=
HS","","24-11-2024 12:25:20","24-11-2024 12:18:13","24-11-2024 13:53:00","C=
ascaded Incident from TTO3591814","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Access issue during the Weekend","system","287039=
","24-11-2024 12:25:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0003663480","A=
ccacia New","IHS_YND_505","24-11-2024 12:24:22","24-11-2024 12:18:13","24-1=
1-2024 14:00:36","Access issue during the Weekend,  Grid outage ,//Grid pow=
er return","","Access Denial","Lease Or Legal","Landlord Related Issues","A=
ccess Issue - Land Lord","Access issue during the Weekend,  Grid outage ,//=
Grid power return","denis.mballa@ihstowers.com","370","24-11-2024 12:24:22"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003663465","H=
-Progres","","24-11-2024 12:22:11","24-11-2024 12:17:05","24-11-2024 13:53:=
47","grid outage,no space to deploy a mobil gen//,Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no s=
pace to deploy a mobil gen//,Grid return","denis.mballa@ihstowers.com","307=
","24-11-2024 12:22:11","Sagemcom CMR"
"Closed Complete","Site Down","T1669","IHS_YND_195","NOCINC0003663445","chi=
na embassy yde","","24-11-2024 12:14:51","24-11-2024 11:49:37","24-11-2024 =
13:53:21","Grid outage No space to deploy // Grid power return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No =
space to deploy // Grid power return","rouselle.schoune@ihstowers.com","151=
5","24-11-2024 12:14:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003663373","B=
iyemassi LAC","","24-11-2024 12:03:23","24-11-2024 11:49:15","24-11-2024 13=
:57:50","grid outage,no space to deploy a mobil gen, // Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outag=
e,no space to deploy a mobil gen, // Grid return","denis.mballa@ihstowers.c=
om","849","24-11-2024 12:03:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_003","NOCINC0003663349","Mercure"=
,"","24-11-2024 11:58:20","24-11-2024 11:27:20","24-11-2024 14:02:20","Casc=
aded Incident from TTO3591642","","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","GRID OUTAGE NO SPACE TO DEPLOY A MDG // GRID RETURN"=
,"system","1860","24-11-2024 11:58:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_005","NOCINC0003663350","Imm-Olym=
pique","","24-11-2024 11:58:20","24-11-2024 11:27:20","24-11-2024 14:02:20"=
,"Cascaded Incident from TTO3591642","Paul BIBOUM","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","GRID OUTAGE NO SPACE TO DEPLOY A MD=
G // GRID RETURN","system","318832","24-11-2024 11:58:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0003663341","E=
lig-Essono","IHS_YND_003, IHS_YND_005","24-11-2024 11:56:36","24-11-2024 11=
:27:20","24-11-2024 14:02:20","GRID OUTAGE NO SPACE TO DEPLOY A MDG // GRID=
 RETURN","Paul BIBOUM","Grid Supply","Passive","Grid","National Grid - Grid=
 Outage Issue","GRID OUTAGE NO SPACE TO DEPLOY A MDG // GRID RETURN","denis=
.mballa@ihstowers.com","1757","24-11-2024 11:56:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003663333","B=
riqueterie","","24-11-2024 11:54:31","24-11-2024 11:30:21","24-11-2024 16:0=
0:15","Grid outage No space to deploy // Grid power return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No spac=
e to deploy awaiting Grid power return","denis.mballa@ihstowers.com","1451"=
,"24-11-2024 11:54:31","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0003663295","Bri=
quetterie","","24-11-2024 11:45:35","24-11-2024 11:33:32","24-11-2024 13:55=
:43","Grid outage No space to deploy //Grid power return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No space =
to deploy // Grid power return","rouselle.schoune@ihstowers.com","724","24-=
11-2024 11:45:35","Sagemcom CMR"
"Closed Complete","Site Down","T3172","IHS_YND_043","NOCINC0003663290","Emi=
a","IHS_YND_030, IHS_YND_029","24-11-2024 11:44:04","24-11-2024 11:30:55","=
24-11-2024 13:59:48","grid outage,no space to deploy a mobil gen,//Grid pow=
er ","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"grid outage,no space to deploy a mobil gen,//Grid power ","rouselle.schoun=
e@ihstowers.com","789","24-11-2024 11:44:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0003663285","Sapeur",=
"","24-11-2024 11:43:40","24-11-2024 11:30:55","24-11-2024 13:59:48","Casca=
ded Incident from TTO3591532 - Cascade Removed From TTO3591532","Mboua Thie=
rry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","grid o=
utage,no space to deploy a mobil gen,//Grid power ","system","289971","24-1=
1-2024 11:43:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0003663250","E=
-Police","","24-11-2024 11:39:26","24-11-2024 11:30:55","24-11-2024 13:59:4=
8","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","gr=
id outage,no space to deploy a mobil gen,//Grid power ","denis.mballa@ihsto=
wers.com","289971","24-11-2024 11:39:26","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003663222","Lad=
a I Yde","","24-11-2024 11:36:43","24-11-2024 09:13:35","24-11-2024 11:28:3=
4","Grid outage site went down because Gen failed to start due to Gen batte=
ry faulty // Gen manually started with external battery","Mba Lazare Herve"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid o=
utage site went down because Gen failed to start due to Gen battery faulty =
// Gen manually started with external battery","rouselle.schoune@ihstowers.=
com","8589","24-11-2024 11:36:43","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003662770","Bas=
tos Amb Coree","","24-11-2024 10:52:54","24-11-2024 10:46:53","24-11-2024 1=
3:54:53","Grid Outage No Space to deploy a MDG// Grid Restored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No =
Space to deploy a MDG// Grid Restored","rouselle.schoune@ihstowers.com","36=
2","24-11-2024 10:52:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003662635","B=
astos Bethesda","","24-11-2024 10:33:16","24-11-2024 10:28:08","24-11-2024 =
11:38:45","Grid outage, Site went because Gen started and stopped due to Hi=
gh temp// He added water and started Gen manualy","Mboua Thierry","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid outage, Site went because Gen started and stopped due to High tem=
p// He added water and started Gen manualy","denis.mballa@ihstowers.com","3=
09","24-11-2024 10:33:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0003662553","NYOM 2 I=
HS","","24-11-2024 10:11:10","24-11-2024 10:03:26","24-11-2024 16:05:02","C=
ascaded Incident from TTO3590731","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Eneo outage, MGE on site faulty //=
New  MGE 20kva deployed","system","302491","24-11-2024 10:11:10","Sagemcom =
CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003662227","AWA=
E OCM","","24-11-2024 09:20:47","24-11-2024 09:18:27","24-11-2024 11:58:06"=
,"site went down because PWC overload(12Kw, 200A) // Site stabilized","Mba =
Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module Ov=
erloaded","site went down because PWC overload(12Kw, 200A) // Site stabiliz=
ed","rouselle.schoune@ihstowers.com","141","24-11-2024 09:20:47","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003662129","B=
itoto","","24-11-2024 08:55:59","24-11-2024 08:46:36","24-11-2024 09:45:19"=
,"site went down  duer to work team TELINO  / 681345277 SWAPP baie on site/=
/ end off work","Mba Lazare Herve","Equipment Replacement","Passive","Plann=
ed Activity","Planned Activity - Passive","site went down  duer to work tea=
m TELINO  / 681345277 SWAPP baie on site// end off work","denis.mballa@ihst=
owers.com","564","24-11-2024 08:55:59","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0003662105","Mba=
nkolo petit paris","","24-11-2024 08:50:09","24-11-2024 08:42:04","24-11-20=
24 14:15:04","Active: No power issue site on Gen with U=3D50.9v  BRICE Tsag=
ue/ 650214096 from Huawei is informed","Mboua Thierry","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No power issue site on Gen with U=3D50.9v BRICE Tsague/ 650214096 from Huaw=
ei is informed

","rouselle.schoune@ihstowers.com","485","24-11-2024 08:50:09","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003662086","S=
tade-Abega","","24-11-2024 08:44:11","24-11-2024 08:37:58","24-11-2024 10:3=
5:02","Active//No power issue on site Ubaie=3D54.7V;  site on Gen . The FME=
 Leonel Steve/ 655184876/  Huawei is informed","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site Ubaie=3D54.7V;  site on Gen . The FME Leo=
nel Steve/ 655184876/  Huawei is informed","denis.mballa@ihstowers.com","37=
4","24-11-2024 08:44:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003662016","N=
GONA","","24-11-2024 08:24:28","24-11-2024 08:16:19","24-11-2024 19:25:59",=
"No power iissue site  on Grid ubaie=3D56 V Site impacted by CTR_084_Nkoaba=
ng","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power iissue site  on Grid ubaie=3D56=
 V Site impacted by CTR_084_Nkoabang","denis.mballa@ihstowers.com","490","2=
4-11-2024 08:24:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003661963","Ngog Map=
ubi","","24-11-2024 08:14:12","24-11-2024 08:06:35","24-11-2024 08:07:35","=
Cascaded Incident from TTO3590029","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active/No power issue on site.Site o=
n Grid with Ubaie=3D54.6V  The TX FME Etienne(695033981) from Huawei is   i=
nformed.","system","1215668","24-11-2024 08:14:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003661964","Mamb",""=
,"24-11-2024 08:14:12","24-11-2024 08:06:35","24-11-2024 08:07:35","Cascade=
d Incident from TTO3590029","Kemeni Franklin","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active/No power issue on site.Site on Grid =
with Ubaie=3D54.6V  The TX FME Etienne(695033981) from Huawei is   informed=
.","system","266268","24-11-2024 08:14:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003661962","Ndogbess=
ol","","24-11-2024 08:14:12","24-11-2024 08:06:35","24-11-2024 08:07:35","C=
ascaded Incident from TTO3590029","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active/No power issue on site.Site on=
 Grid with Ubaie=3D54.6V  The TX FME Etienne(695033981) from Huawei is   in=
formed.","system","266268","24-11-2024 08:14:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_286","IHS_YND_381","NOCINC0003661954","B=
oumnyebel","IHS_EDA_056, IHS_YND_419, IHS_YND_376","24-11-2024 08:12:47","2=
4-11-2024 08:06:35","24-11-2024 09:07:35","Active/No power issue on site.Si=
te on Grid with Ubaie=3D54.6V  The TX FME Etienne(695033981) from Huawei is=
   informed.","Kemeni Franklin","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active/No power issue on site.S=
ite on Grid with Ubaie=3D54.6V  The TX FME Etienne(695033981) from Huawei i=
s   informed.","denis.mballa@ihstowers.com","373","24-11-2024 08:12:47","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003661919","Biteng-M=
aetur","","24-11-2024 08:01:00","24-11-2024 07:52:19","24-11-2024 08:07:37"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Grid power return","Mba Lazare Herve","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site went down before=
 gen start due to poor battery backup // Grid power return","system","521",=
"24-11-2024 08:01:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003661918","Essomba"=
,"","24-11-2024 08:01:00","24-11-2024 07:52:19","24-11-2024 07:58:19","Casc=
aded Incident from TTO3589978","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before g=
en start due to poor battery backup // Gen started automatically","system",=
"281874","24-11-2024 08:01:00","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003661916","Mok=
olo Yaounde","","24-11-2024 08:00:27","24-11-2024 07:50:15","24-11-2024 13:=
52:39","Grid Outage No Space to deploy a MDG// Grid Restored","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Sp=
ace to deploy a MDG// Grid Restored","rouselle.schoune@ihstowers.com","613"=
,"24-11-2024 08:00:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003661912","B=
iteng","IHS_YND_179","24-11-2024 07:59:31","24-11-2024 07:52:19","24-11-202=
4 07:58:19","Grid outage, site went down before gen start due to poor batte=
ry backup // Gen started automatically","Mba Lazare Herve","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before gen start due to poor battery backup // Gen started aut=
omatically","denis.mballa@ihstowers.com","433","24-11-2024 07:59:31","Sagem=
com CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003661871","Sap=
eur","","24-11-2024 07:53:40","24-11-2024 07:41:36","24-11-2024 07:54:36","=
Grid outage, site went down before gen start due to poor battery backup // =
Grid power return","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before gen =
start due to poor battery backup // Grid power return","rouselle.schoune@ih=
stowers.com","725","24-11-2024 07:53:40","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003661562","Lab=
oratoire  Meka","IHS_YND_193","24-11-2024 06:53:57","24-11-2024 06:47:22","=
24-11-2024 08:11:32","Grid Outage//Grid Restored","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid Outage//Grid Restored","=
rouselle.schoune@ihstowers.com","396","24-11-2024 06:53:57","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003661559","Bas=
tos Ekoudou","","24-11-2024 06:52:23","24-11-2024 06:47:22","24-11-2024 08:=
11:32","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Outage//Grid Restored","rouselle.schoune@ihstowers.com"=
,"292512","24-11-2024 06:52:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003661494","N=
koabang","","24-11-2024 06:40:11","24-11-2024 06:25:01","24-11-2024 06:35:5=
3","Active//No power issue on site Ubaie=3D54.9V; site on Grid and The FME =
Leonel Steve / 655184876/ Huawei is informed","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site Ubaie=3D54.9V; site on Grid and The FME Le=
onel Steve / 655184876/ Huawei is informed","denis.mballa@ihstowers.com","9=
11","24-11-2024 06:40:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003661323","Dong",""=
,"24-11-2024 05:55:21","24-11-2024 05:46:30","24-11-2024 05:46:31","Cascade=
d Incident from TTO3589327","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue on site with Ubaie=3D4=
9.4V site on Battery (start threshold ubai=3D48.4V) The Tx Fme Gregoire( 65=
2070658)from Huawei is informed and Site UP at=3D05:46:56","system","267486=
","24-11-2024 05:55:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003661324","Yoko MTN=
","","24-11-2024 05:55:21","24-11-2024 05:46:30","24-11-2024 05:46:31","Cas=
caded Incident from TTO3589327","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site with Ubaie=
=3D49.4V site on Battery (start threshold ubai=3D48.4V) The Tx Fme Gregoire=
( 652070658)from Huawei is informed and Site UP at=3D05:46:56","system","26=
7487","24-11-2024 05:55:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003661320","MBIMBIM"=
,"","24-11-2024 05:55:20","24-11-2024 05:46:30","24-11-2024 05:46:31","Casc=
aded Incident from TTO3589327","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue on site with Ubaie=
=3D49.4V site on Battery (start threshold ubai=3D48.4V) The Tx Fme Gregoire=
( 652070658)from Huawei is informed and Site UP at=3D05:46:56","system","26=
7487","24-11-2024 05:55:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003661321","Matsari"=
,"","24-11-2024 05:55:20","24-11-2024 05:46:30","24-11-2024 05:46:31","Casc=
aded Incident from TTO3589327","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue on site with Ubaie=
=3D49.4V site on Battery (start threshold ubai=3D48.4V) The Tx Fme Gregoire=
( 652070658)from Huawei is informed and Site UP at=3D05:46:56","system","26=
7486","24-11-2024 05:55:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003661322","Ngoum","=
","24-11-2024 05:55:20","24-11-2024 05:46:30","24-11-2024 05:46:31","Cascad=
ed Incident from TTO3589327","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue on site with Ubaie=3D=
49.4V site on Battery (start threshold ubai=3D48.4V) The Tx Fme Gregoire( 6=
52070658)from Huawei is informed and Site UP at=3D05:46:56","system","26748=
6","24-11-2024 05:55:20","Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0003661317","Don=
ga","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_444, IHS_YND_473","24-1=
1-2024 05:53:52","24-11-2024 05:46:30","24-11-2024 05:46:31","Active//No po=
wer issue on site with Ubaie=3D49.4V site on Battery (start threshold ubai=
=3D48.4V) The Tx Fme Gregoire( 652070658)from Huawei is informed and Site U=
P at=3D05:46:56","Parker Tchoup","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site=
 with Ubaie=3D49.4V site on Battery (start threshold ubai=3D48.4V) The Tx F=
me Gregoire( 652070658)from Huawei is informed and Site UP at=3D05:46:56","=
kamga.virgile@ihstowers.com","442","24-11-2024 05:53:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003661093","S=
ous Prefecture","","24-11-2024 04:21:22","24-11-2024 02:13:09","24-11-2024 =
02:15:09","No power issue on site , Ubaie=3D54.6V site On Grid The Tx FME G=
eorges 697461814 from Huawei is informed.","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site , Ubaie=3D54.6V site On Grid The Tx FME Georges 697461814 =
from Huawei is informed.","alexandre.kamal@ihstowers.com","7694","24-11-202=
4 04:21:22","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003660928","Nko=
g-Edzen","","24-11-2024 03:08:54","24-11-2024 01:49:15","24-11-2024 01:50:1=
5","No power issue on site with Ubaie=3D52.4V site on Gen (start threshold =
ubai=3D50 V) The Tx Fme Gregoire( 652070658)from Huawei is informed","Parke=
r Tchoup","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue on site with Ubaie=3D52.4V site on Gen=
 (start threshold ubai=3D50 V) The Tx Fme Gregoire( 652070658)from Huawei i=
s informed","kamga.virgile@ihstowers.com","4780","24-11-2024 03:08:54","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003660734","E=
lobi Mokolo","","24-11-2024 01:31:36","24-11-2024 01:21:59","24-11-2024 01:=
22:59","Active//No power issue on site Ubaie=3D55,2 V; site on Grid tx fme =
BRICE Tsague/ 650214096 from huawie is informed","Mboua Thierry","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site Ubaie=3D55,2 V; site on Grid tx fme BRICE =
Tsague/ 650214096 from huawie is informed","alexandre.kamal@ihstowers.com",=
"578","24-11-2024 01:31:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003660260","N=
koabang2","","23-11-2024 22:53:30","23-11-2024 22:44:24","23-11-2024 22:45:=
24","No power issue on site Ubaie=3D54,5 V site on Grid. The Tx fme  Lionel=
 Adjep /655184876 from huawei is informed","Mba Lazare Herve","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site Ubaie=3D54,5 V site on Grid. The Tx fme  Lionel Adjep=
 /655184876 from huawei is informed","alexandre.kamal@ihstowers.com","547",=
"23-11-2024 22:53:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003660197","M=
IMBOMAN LIBERTE","","23-11-2024 22:36:25","23-11-2024 22:22:21","23-11-2024=
 22:36:21","grid outage,Site went down because main gen faulty // grid retu=
rn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Gene=
rator Faulty","grid outage,Site went down because main gen faulty // grid r=
eturn","alexandre.kamal@ihstowers.com","845","23-11-2024 22:36:25","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003659966","MBALNGON=
G LYCEE","","23-11-2024 21:52:11","23-11-2024 21:42:34","23-11-2024 21:56:0=
9","Cascaded Incident from TTO3587765","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Access issue during the night due=
 to land loard Grid fluctuation site went down because Gen failed  to start=
 due to Grid bad voltage AND No RCP on site // He bypass the Grid and Gen m=
anually started","system","332470","23-11-2024 21:52:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003659967","Afanoya"=
,"","23-11-2024 21:52:11","23-11-2024 21:42:34","23-11-2024 21:56:09","Casc=
aded Incident from TTO3587765","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Access issue during the night due to l=
and loard Grid fluctuation site went down because Gen failed  to start due =
to Grid bad voltage AND No RCP on site // He bypass the Grid and Gen manual=
ly started","system","332471","23-11-2024 21:52:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003659965","ELOUMDEM=
 CARRIERE","","23-11-2024 21:52:11","23-11-2024 21:42:34","23-11-2024 21:56=
:09","Cascaded Incident from TTO3587765","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Access issue during the night d=
ue to land loard Grid fluctuation site went down because Gen failed  to sta=
rt due to Grid bad voltage AND No RCP on site // He bypass the Grid and Gen=
 manually started","system","332471","23-11-2024 21:52:11","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003659959","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","23-11-2024 21:50:42","23-11-20=
24 21:42:34","23-11-2024 21:44:09","Access issue during the night due to la=
nd loard Grid fluctuation site went down because Gen failed  to start due t=
o Grid bad voltage AND No RCP on site // He bypass the Grid and Gen manuall=
y started","Hyemafo Gildas","Access Denial","Lease Or Legal","Landlord Rela=
ted Issues","Access Issue - Land Lord","Access issue during the night due t=
o land loard Grid fluctuation site went down because Gen failed  to start d=
ue to Grid bad voltage AND No RCP on site // He bypass the Grid and Gen man=
ually started","olivier.kwedi@ihstowers.com","490","23-11-2024 21:50:42","S=
agemcom CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0003659948","Nko=
ngtock","","23-11-2024 21:48:40","23-11-2024 21:38:33","23-11-2024 21:40:33=
","no power issue on site U=3D50v site on gen Etienne  ( 695033981 ) // HUA=
WEI is informed.","Kemeni Franklin","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","no power issue on site U=3D=
50v site on gen Etienne  ( 695033981 ) // HUAWEI is informed.
","olivier.kwedi@ihstowers.com","607","23-11-2024 21:48:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003659599","Akak-Nko=
zoa-MTN-IHS","","23-11-2024 20:57:20","23-11-2024 20:46:06","23-11-2024 21:=
26:04","Cascaded Incident from TTO3587328","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo outage, site down be=
fore DG start due to poor backup // DG started automatically","system","271=
115","23-11-2024 20:57:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0003659557","T=
SINGA VILLAGE 2","","23-11-2024 20:51:17","23-11-2024 20:40:07","23-11-2024=
 21:39:33","Site went down because CB(125A) tripped in PWC who feeds equipm=
ents OCM// CB put back on ","Delor Telezing","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down beca=
use CB(125A) tripped in PWC who feeds equipments OCM// CB put back on ","st=
ephane.nkamwa@ihstowers.com","671","23-11-2024 20:51:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003659334","O=
lembe-Terminus","","23-11-2024 20:11:47","23-11-2024 19:51:55","23-11-2024 =
21:20:55","Grid outage ,Site went down because No Main  Gen on site at the =
moment // MDG 20KVA deployed","Fabrice Pouakam","Equipment Repair","Passive=
","ACDG Gen","ACDG - Generator Faulty","Grid outage ,Site went down because=
 No Main  Gen on site at the moment // MDG 20KVA deployed","stephane.nkamwa=
@ihstowers.com","1193","23-11-2024 20:11:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003659319","M=
efou-Assi","","23-11-2024 20:08:14","23-11-2024 19:39:15","23-11-2024 19:45=
:54","Active// No power issue on site , Ubaie=3D53.3V site On Grid The Tx F=
ME Georges 697461814 from Huawei is informed. Notice that we have Disjuncti=
on at BTS OCM","Fanda Brice","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active// No power issue on site , =
Ubaie=3D53.3V site On Grid The Tx FME Georges 697461814 from Huawei is info=
rmed. Notice that we have Disjunction at BTS OCM","stephane.nkamwa@ihstower=
s.com","1740","23-11-2024 20:08:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003659305","ELOUMDEM=
 CARRIERE 2","","23-11-2024 20:07:50","23-11-2024 20:02:03","23-11-2024 20:=
06:47","Cascaded Incident from TTO3586972","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Gen start and stopped due to Grid bad voltage // Gen manually s=
tarted","system","347","23-11-2024 20:07:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003659304","Eto koss=
 Yde","","23-11-2024 20:07:50","23-11-2024 20:02:03","23-11-2024 20:06:47",=
"Cascaded Incident from TTO3586972","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Gen start and stopped due to Grid bad voltage // Gen manually started"=
,"system","347","23-11-2024 20:07:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003659287","B=
itoto","","23-11-2024 20:05:56","23-11-2024 19:32:55","23-11-2024 20:08:55"=
,"  site went down  duer to work  The Team //  681345270 FROM TELINO SWAPP =
PWC //End of work","Mba Lazare Herve","Installation Activity","Passive","Pl=
anned Activity","Installation Activity","  site went down  duer to work  Th=
e Team //  681345270 FROM TELINO SWAPP PWC //End of work","stephane.nkamwa@=
ihstowers.com","1982","23-11-2024 20:05:56","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003659286","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","23-11-2024 20:05:54","23-11-2024 20:02=
:03","23-11-2024 20:06:47","Grid fluctuation, site went down because Gen st=
art and stopped due to Grid bad voltage // Gen manually started","Fanda Bri=
ce","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because Gen start and stopped due to Gr=
id bad voltage // Gen manually started","olivier.kwedi@ihstowers.com","232"=
,"23-11-2024 20:05:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003659237","N=
koabang","IHS_YND_526, IHS_YND_736","23-11-2024 19:58:05","23-11-2024 19:31=
:04","23-11-2024 19:38:22","No power issue on site Ubaie=3D54,5 V site on G=
rid. The Tx fme  Lionel Adjep /655184876 from huawei is informed","Mba Laza=
re Herve","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue on site Ubaie=3D54,5 V site on Grid. T=
he Tx fme  Lionel Adjep /655184876 from huawei is informed","stephane.nkamw=
a@ihstowers.com","1622","23-11-2024 19:58:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0003659167","Nkoabang=
2","","23-11-2024 19:44:40","23-11-2024 19:31:04","23-11-2024 19:38:22","Ca=
scaded Incident from TTO3586814 - Cascade Removed From TTO3586814","Mba Laz=
are Herve","Cascade Outage","Active","Cascade Active","Cascade Active","No =
power issue on site Ubaie=3D54,5 V site on Grid. The Tx fme  Lionel Adjep /=
655184876 from huawei is informed","system","275480","23-11-2024 19:44:40",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0003659149","C=
RF Nkoabang","","23-11-2024 19:41:39","23-11-2024 19:31:04","23-11-2024 19:=
38:22","","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Ca=
scade Active","No power issue on site Ubaie=3D54,5 V site on Grid. The Tx f=
me  Lionel Adjep /655184876 from huawei is informed","stephane.nkamwa@ihsto=
wers.com","275480","23-11-2024 19:41:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003658860","Nkongtoc=
k","","23-11-2024 18:55:22","23-11-2024 18:30:32","23-11-2024 18:35:48","Ca=
scaded Incident from TTO3586474","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site , Ubaie=3D53,5 =
V site On Grid The Tx FME Georges 697461814 from Huawei is informed","syste=
m","1490","23-11-2024 18:55:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0003658858","Nkenglik=
ok","","23-11-2024 18:55:22","23-11-2024 18:30:32","23-11-2024 18:35:48","C=
ascaded Incident from TTO3586474","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site , Ubaie=3D53,5=
 V site On Grid The Tx FME Georges 697461814 from Huawei is informed","syst=
em","1490","23-11-2024 18:55:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0003658859","Eseka OC=
M","","23-11-2024 18:55:22","23-11-2024 18:30:32","23-11-2024 18:35:48","Ca=
scaded Incident from TTO3586474","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site , Ubaie=3D53,5 =
V site On Grid The Tx FME Georges 697461814 from Huawei is informed","syste=
m","272019","23-11-2024 18:55:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0003658856","Mbeng","=
","23-11-2024 18:55:21","23-11-2024 18:30:32","23-11-2024 18:35:48","Cascad=
ed Incident from TTO3586474","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site , Ubaie=3D53,5 V site O=
n Grid The Tx FME Georges 697461814 from Huawei is informed","system","2720=
19","23-11-2024 18:55:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0003658857","Mbankomo=
 IHS","","23-11-2024 18:55:21","23-11-2024 18:30:32","23-11-2024 18:35:48",=
"Cascaded Incident from TTO3586474","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site , Ubaie=3D53,5 V=
 site On Grid The Tx FME Georges 697461814 from Huawei is informed","system=
","1489","23-11-2024 18:55:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0003658850","N=
omayos","IHS_YND_369, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_697, I=
HS_YND_377, IHS_YND_349","23-11-2024 18:53:21","23-11-2024 18:30:32","23-11=
-2024 20:45:34","No power issue on site , Ubaie=3D53,5 V site On Grid The T=
x FME Georges 697461814 from Huawei is informed","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site , Ubaie=3D53,5 V site On Grid The Tx FME Georges 697=
461814 from Huawei is informed","stephane.nkamwa@ihstowers.com","1370","23-=
11-2024 18:53:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003658847","N=
omayos-IHS","","23-11-2024 18:52:23","23-11-2024 18:30:32","23-11-2024 18:3=
5:48","","Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade =
Active","No power issue on site , Ubaie=3D53,5 V site On Grid The Tx FME Ge=
orges 697461814 from Huawei is informed","stephane.nkamwa@ihstowers.com","2=
72018","23-11-2024 18:52:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003658714","D=
amas","","23-11-2024 18:22:23","23-11-2024 18:18:29","23-11-2024 19:46:44",=
"Grid outage, Site went down due to Gen overload (09Kva, 150A)// Grid retur=
n","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","Grid outage, Site went down due to Gen overload (09Kva, 150A)// Grid ret=
urn","stephane.nkamwa@ihstowers.com","235","23-11-2024 18:22:23","Sagemcom =
CMR"
"Closed Complete","Warning","T1625","IHS_YND_204","NOCINC0003658712","TONGO=
LO SNEC","","23-11-2024 18:21:36","","","Grid outage,DG failed to start //S=
tarted DG manually investigations ongoing.","Fabrice Pouakam","Warning","Wa=
rning","POWER","Warning - Site on Battery","Grid outage,DG failed to start =
//Started DG manually investigations ongoing.","nadjia.njaya@ihstowers.com"=
,"377","23-11-2024 18:21:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003658502","Nsimalen=
 OCM","","23-11-2024 17:47:00","23-11-2024 17:30:17","23-11-2024 18:49:38",=
"Cascaded Incident from TTO3586056","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went because Gen=
 started and stopped with ""under frequency"" alarm (unprouven)// He reset =
Gen Card and started Gen manualy","system","268408","23-11-2024 17:47:00","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003658479","N=
kolda","IHS_YND_327","23-11-2024 17:45:13","23-11-2024 17:30:17","23-11-202=
4 18:49:38","Grid outage, Site went because Gen started and stopped with ""=
under frequency"" alarm (unprouven)// He reset Gen Card and started Gen man=
ualy","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","Grid outage, Site went because Gen started and stopped with ""un=
der frequency"" alarm (unprouven)// He reset Gen Card and started Gen manua=
ly","stephane.nkamwa@ihstowers.com","897","23-11-2024 17:45:13","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003658176","Afanoya"=
,"","23-11-2024 17:05:01","23-11-2024 16:58:31","23-11-2024 17:30:45","Casc=
aded Incident from TTO3585709","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, Site went down Gen s=
tarted and stopped with ""overcurent"" alarm// He reset Gen card, Site on G=
rid","system","277436","23-11-2024 17:05:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003658175","MBALNGON=
G LYCEE","","23-11-2024 17:05:01","23-11-2024 16:58:31","23-11-2024 17:30:4=
5","Cascaded Incident from TTO3585709","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation, Site went down =
Gen started and stopped with ""overcurent"" alarm// He reset Gen card, Site=
 on Grid","system","277436","23-11-2024 17:05:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003658174","ELOUMDEM=
 CARRIERE","","23-11-2024 17:05:00","23-11-2024 16:58:31","23-11-2024 17:30=
:45","Cascaded Incident from TTO3585709","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation, Site went dow=
n Gen started and stopped with ""overcurent"" alarm// He reset Gen card, Si=
te on Grid","system","277436","23-11-2024 17:05:00","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003658170","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","23-11-2024 17:03:27","23-11-20=
24 16:58:31","23-11-2024 17:30:45","Grid fluctuation, Site went down becaus=
e Gen started and stopped with ""overcurent"" alarm// He reset Gen card, Si=
te on Grid","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG =
- Control Panel","Grid fluctuation, Site went down because Gen started and =
stopped with ""overcurent"" alarm// He reset Gen card, Site on Grid","olivi=
er.kwedi@ihstowers.com","298","23-11-2024 17:03:27","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0003658133","ETO=
UDI Entree du palais","","23-11-2024 16:56:38","23-11-2024 16:50:41","23-11=
-2024 16:55:58","Active// No power issue on site, Site on Grid Ubai: 54.8V,=
 The FME TX Armand Nguetsa/691144412 From Huawei is informed","Fabrice Poua=
kam","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active// No power issue on site, Site on Grid Ubai: 54.8V,=
 The FME TX Armand Nguetsa/691144412 From Huawei is informed","olivier.kwed=
i@ihstowers.com","358","23-11-2024 16:56:38","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003658071","Tsi=
nga","","23-11-2024 16:47:41","23-11-2024 16:41:46","23-11-2024 17:03:39","=
Grid outage, Site went down before Gen start due to poor backup// Gen start=
ed automatically","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup// Gen started automatically","olivier.kwedi@ihstowe=
rs.com","356","23-11-2024 16:47:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0003657974","B=
astos-BAT","","23-11-2024 16:30:02","23-11-2024 16:23:57","23-11-2024 19:10=
:53","No power issue on site Ubaie=3D51,8 V  The Team Yannick  Kenfack//675=
798448 from ZTE is working on site","Mboua Thierry","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site Ubaie=3D51,8 V  The Team Yannick  Kenfack//675798448 from ZTE i=
s working on site","stephane.nkamwa@ihstowers.com","366","23-11-2024 16:30:=
02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003657904","E=
lobi Mokolo","","23-11-2024 16:23:25","23-11-2024 16:09:05","23-11-2024 21:=
00:14","Active//No power issue on site Ubaie=3D55,2 V;  site on Grid tx fme=
 BRICE Tsague/ 650214096 from huawie is informed","Mboua Thierry","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site Ubaie=3D55,2 V;  site on Grid tx fme BRIC=
E Tsague/ 650214096 from huawie is informed","stephane.nkamwa@ihstowers.com=
","860","23-11-2024 16:23:25","Sagemcom CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0003657715","Ebe=
ba","","23-11-2024 15:38:46","23-11-2024 15:29:38","23-11-2024 18:35:48","H=
ybrid Gen: Site went down because Gen started and stopped due to High temp/=
/ He added water in radiator and started Gen manualy","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Hybrid Gen: Site went down because Gen started and stopped due to Hi=
gh temp// He added water in radiator and started Gen manualy","olivier.kwed=
i@ihstowers.com","549","23-11-2024 15:38:46","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0003657637","MVA=
N SACEL","","23-11-2024 15:27:32","23-11-2024 15:18:03","23-11-2024 15:26:3=
3","Grid outage, Site went down before Gen start due to poor backup// Grid =
return","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, Site went down before Gen start due t=
o poor backup// Grid return","olivier.kwedi@ihstowers.com","570","23-11-202=
4 15:27:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0003657484","O=
bili Carrefour","","23-11-2024 15:05:53","23-11-2024 14:30:53","23-11-2024 =
15:58:58","Grid fluctuation, site went down because Gen started and stopped=
 due to Grid bad voltage// He bypassed Grid and Gen manualy started","Paul =
BIBOUM","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, site went down because Gen started and stopped due=
 to Grid bad voltage// He bypassed Grid and Gen manualy started","stephane.=
nkamwa@ihstowers.com","2100","23-11-2024 15:05:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003657390","Nkolbiss=
on usines des eaux 2","","23-11-2024 14:55:10","23-11-2024 14:06:52","23-11=
-2024 14:52:46","Cascaded Incident from TTO3584786","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, Site went down before Gen start due to poor backup// Grid power retur=
n","system","345723","23-11-2024 14:55:10","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003657380","Nko=
lbisson","IHS_YND_763","23-11-2024 14:53:07","23-11-2024 14:06:52","23-11-2=
024 14:52:46","Grid outage, site went down before Gen start due to poor bac=
kup// Grid return","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down =
before Gen start due to poor backup// Grid power return","olivier.kwedi@ihs=
towers.com","2776","23-11-2024 14:53:07","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0003657310","ETO=
UDI Entree du palais","","23-11-2024 14:41:37","23-11-2024 14:14:35","23-11=
-2024 14:55:43","Grid outage, Site went down because Gen fails to start due=
 to Grid contactor disfunction// He blocked Grid Contactor, Site on Grid. P=
ower issues resolved since 02:55 PM (Site still down after the powe","Fabri=
ce Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","G=
rid outage, Site went down because Gen fails to start due to Grid contactor=
 disfunction// He blocked Grid Contactor, Site on Grid. Power issues resolv=
ed since 02:55 PM (Site still down after the power reset) The FME tx Armand=
 Ngetsa/691144412/ From Huawei is informed","christian.fonkou@ihstowers.com=
","1623","23-11-2024 14:41:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003657304","MEHANDAN=
","","23-11-2024 14:40:30","23-11-2024 14:08:33","23-11-2024 14:42:47","Cas=
caded Incident from TTO3584677","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se Gen started and stopped due to Grid bad voltage no rcp and poor backup//=
 He bypassed Grid and started Gen manualy","system","1917","23-11-2024 14:4=
0:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003657284","O=
dza II OCM","IHS_YND_528","23-11-2024 14:39:29","23-11-2024 14:08:33","23-1=
1-2024 14:42:47","Grid fluctuation, site went down because Gen started and =
stopped due to Grid bad voltage no rcp and poor backup// He bypassed Grid a=
nd started Gen manualy","Albran Byorel","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","Grid fluctuation, site went down bec=
ause Gen started and stopped due to Grid bad voltage no rcp and poor backup=
// He bypassed Grid and started Gen manualy","joelle.ekessi@ihstowers.com",=
"1858","23-11-2024 14:39:29","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003657277","NYO=
M FACE MAETUR","","23-11-2024 14:37:54","23-11-2024 14:12:54","24-11-2024 1=
0:44:56","Grid Outage landlord has forbiden to start the Gen Because the No=
ise//Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Emergency Stop","Grid Outage landlord has forbiden to start the =
Gen Because the Noise//Grid Restored","christian.fonkou@ihstowers.com","150=
1","23-11-2024 14:37:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003657268","C=
omplexe-BEAC","","23-11-2024 14:36:22","23-11-2024 14:04:26","23-11-2024 15=
:21:11","Site went down because cb(100A) of batteries disjuncted // CB put =
back on","Albran Byorel","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Circuit Breaker Issue","Site went down because cb(100A) of batt=
eries disjuncted // CB put back on","joelle.ekessi@ihstowers.com","1917","2=
3-11-2024 14:36:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0003657042","S=
apeur","","23-11-2024 13:52:29","23-11-2024 13:43:29","23-11-2024 13:57:29"=
,"Grid outage, site went down before Gen start due to poor backup// Gen sta=
rted automaticaly","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before Gen =
start due to poor backup// Gen started automaticaly","joelle.ekessi@ihstowe=
rs.com","776","23-11-2024 13:52:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003657036","S=
ous Prefecture","","23-11-2024 13:50:18","23-11-2024 13:44:21","23-11-2024 =
18:50:07","No power issue on site , Ubaie=3D54.6V site On Grid The Tx FME G=
eorges 697461814 from Huawei is informed. Notice that we have disjunction a=
t BTS OCM","Fanda Brice","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue on site , Ubaie=3D54.6V=
 site On Grid The Tx FME Georges 697461814 from Huawei is informed. Notice =
that we have disjunction at BTS OCM","joelle.ekessi@ihstowers.com","358","2=
3-11-2024 13:50:18","Sagemcom CMR"
"Closed Complete","Site Down","T1669","IHS_YND_195","NOCINC0003656826","chi=
na embassy yde","","23-11-2024 13:25:51","23-11-2024 13:19:50","23-11-2024 =
17:38:39","grid outage,no space to deploy a mobil gen //Grid return","","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","grid outage,no space to deploy a mobil gen //Grid return","christi=
an.fonkou@ihstowers.com","416","23-11-2024 13:25:51","Sagemcom CMR"
"Closed Complete","Site Down","T1430","IHS_YND_790","NOCINC0003656559","TRB=
 Centre ville","","23-11-2024 12:47:39","23-11-2024 12:45:39","23-11-2024 1=
2:45:40","Wrongly logged ticket","Yamen Herman","Incorrectly Logged Tickets=
","Error","Error","Error","Wrongly logged ticket","christian.fonkou@ihstowe=
rs.com","121","23-11-2024 12:47:39",""
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0003656309","MVA=
N SACEL","","23-11-2024 11:58:11","23-11-2024 11:54:07","23-11-2024 12:25:3=
6","No power issue on site U=3D53,9v site on grid Tx fme lionel steeve of h=
uawei is informed","MINKA NICOLAS","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
3,9v site on grid Tx fme lionel steeve of huawei is informed","christian.fo=
nkou@ihstowers.com","245","23-11-2024 11:58:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003656262","S=
tade-Abega","","23-11-2024 11:49:06","23-11-2024 11:41:05","23-11-2024 11:5=
1:05","Active//No power issue on site Ubaie=3D54.7V;  site on Grid. The FME=
 Leonel Steve/ 655184876/  Huawei is informed. Notice that Disjunction in t=
he BTS OCM ","Mba Lazare Herve","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site =
Ubaie=3D54.7V;  site on Grid. The FME Leonel Steve/ 655184876/  Huawei is i=
nformed. Notice that Disjunction in the BTS OCM ","joelle.ekessi@ihstowers.=
com","482","23-11-2024 11:49:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003656202","B=
astos Bethesda","","23-11-2024 11:44:18","23-11-2024 11:39:17","23-11-2024 =
11:49:17","Grid outage, site went down before gen start due to poor battery=
 backup // Gen started automatically","Mboua Thierry","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down before gen start due to poor battery backup // Gen started automati=
cally","joelle.ekessi@ihstowers.com","302","23-11-2024 11:44:18","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0003656104","E=
seka Town","","23-11-2024 11:30:46","23-11-2024 11:27:37","23-11-2024 12:51=
:57","Grid outage, Site went down because Gen stopped with alarm ""high tem=
p""due to radiator pierced// He resoldering the pierced radiator and added =
water and started Gen manualy","Kemeni Franklin","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage,=
 Site went down because Gen stopped with alarm ""high temp""due to radiator=
 pierced// He resoldering the pierced radiator and added water and started =
Gen manualy","joelle.ekessi@ihstowers.com","190","23-11-2024 11:30:46","Sag=
emcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0003655391","Ntu=
i administration","","23-11-2024 09:39:04","23-11-2024 09:37:59","23-11-202=
4 09:41:59","site went down because 1/2 rectifier disfunctionning//he reset=
 the rectifier","Parker Tchoup","Equipment Repair","Passive","Rectifier","R=
ectifier Module","site went down because 1/2 rectifier disfunctionning//he =
reset the rectifier","christian.fonkou@ihstowers.com","66","23-11-2024 09:3=
9:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003655330","Bastos E=
koudou","","23-11-2024 09:27:10","23-11-2024 09:06:09","23-11-2024 15:32:02=
","Cascaded Incident from TTO3582412","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage// He deploy MDG of 2=
0Kva","system","1261","23-11-2024 09:27:10","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003655328","Lab=
oratoire  Meka","IHS_YND_193","23-11-2024 09:26:15","23-11-2024 09:06:09","=
23-11-2024 15:32:02","grid outage// He deploy MDG of 20Kva","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","grid outage// He de=
ploy MDG of 20Kva","kombi.samuel@ihstowers.com","1207","23-11-2024 09:26:15=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003655259","E=
lig Edzoa","","23-11-2024 09:16:52","23-11-2024 09:14:45","23-11-2024 09:16=
:24","Site went down due to work: Yovo Atswede/698529863/ From SFM working =
on site (Swapp PWC)//End of work","Delor Telezing","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Site went down due to=
 work: Yovo Atswede/698529863/ From SFM working on site (Swapp PWC)//End of=
 work","joelle.ekessi@ihstowers.com","128","23-11-2024 09:16:52","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003655182","c=
hina embassy yde","","23-11-2024 09:01:04","23-11-2024 08:57:57","23-11-202=
4 10:27:51","No power issue on site U=3D49v site on battery Tx fme Eloundou=
 Bertrand of huawei is informed","","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D=
49v site on battery Tx fme Eloundou Bertrand of huawei is informed","joelle=
.ekessi@ihstowers.com","188","23-11-2024 09:01:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003654809","S=
tade-Abega","","23-11-2024 08:00:57","23-11-2024 07:35:47","23-11-2024 09:1=
2:11","grid outage,gen fails to start due to candle faulty//Gen manually st=
arted","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - K=
ick Starter","grid outage,gen fails to start due to candle faulty//Gen manu=
ally started","kombi.samuel@ihstowers.com","1511","23-11-2024 08:00:57","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003654326","A=
fanoya","","23-11-2024 06:00:00","23-11-2024 02:39:48","23-11-2024 06:50:33=
","Active//No power issue, U=3D54V on grid Tx FME George/697461814/ From hu=
awei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, U=3D=
54V on grid Tx FME George/697461814/ From huawei is informed","etienne.iton=
do@ihstowers.com","12017","23-11-2024 06:00:00","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003654117","Bas=
tos Ekoudou","","23-11-2024 04:55:19","23-11-2024 04:44:03","23-11-2024 05:=
46:32","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","grid outage,no space to deploy a mobile gen//Grid return","o=
livier.kwedi@ihstowers.com","263911","23-11-2024 04:55:19","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003654111","Lab=
oratoire  Meka","IHS_YND_193","23-11-2024 04:53:14","23-11-2024 04:44:03","=
23-11-2024 05:46:32","grid outage,no space to deploy a mobile gen//Grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"grid outage,no space to deploy a mobile gen//Grid return","olivier.kwedi@i=
hstowers.com","552","23-11-2024 04:53:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003653441","M=
ANGUIERS CHAPELLE","","23-11-2024 01:00:29","22-11-2024 21:52:01","23-11-20=
24 00:04:14","grid outage, site went down due to gen Overload(20KVA,270) //=
 grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","grid outage, site went down due to gen Overload(20KVA,270) =
// grid return","ludivine.ngamaleu@ihstowers.com","11309","23-11-2024 01:00=
:29","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0003653158","Eli=
g Edzoa","","22-11-2024 23:38:55","22-11-2024 23:29:43","23-11-2024 02:54:2=
8","grid outage, site went down because Pwc dysfunctionnement due to work o=
f Yovo Atswede/698529863/ From SFM who was on site to swap the PWC // He by=
passed PWC","Delor Telezing","Installation Activity","Passive","Planned Act=
ivity","Installation Activity","grid outage, site went down because Pwc dys=
functionnement due to work of Yovo Atswede/698529863/ From SFM who was on s=
ite to swap the PWC // He bypassed PWC","olivier.kwedi@ihstowers.com","553"=
,"22-11-2024 23:38:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003652951","A=
fanoya","","22-11-2024 22:53:08","22-11-2024 22:48:57","23-11-2024 00:32:56=
","Active//No power issue, U=3D54V on grid Tx FME George/697461814/ From hu=
awei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, U=3D=
54V on grid Tx FME George/697461814/ From huawei is informed","ludivine.nga=
maleu@ihstowers.com","252","22-11-2024 22:53:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003652863","E=
kombitie","","22-11-2024 22:37:07","22-11-2024 22:30:57","22-11-2024 22:34:=
00","site went down because gen failed to start due to grid bad voltage // =
Grid stabilzed","Fabrice Pouakam","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","site went down because gen failed to start=
 due to grid bad voltage // Grid stabilzed","ludivine.ngamaleu@ihstowers.co=
m","371","22-11-2024 22:37:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003652607","Bastos E=
koudou","","22-11-2024 21:51:30","22-11-2024 21:09:12","22-11-2024 21:47:28=
","Cascaded Incident from TTO3579221","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage,no space to deploy a=
 mobil gen//grid return","system","276791","22-11-2024 21:51:30","Sagemcom =
CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003652600","Lab=
oratoire  Meka","IHS_YND_193","22-11-2024 21:50:24","22-11-2024 21:09:12","=
22-11-2024 21:47:28","grid outage,no space to deploy a mobil gen//grid retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid outage,no space to deploy a mobil gen//grid return","kamga.virgile@ihs=
towers.com","2472","22-11-2024 21:50:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003652261","Nkolbiss=
on usines des eaux 2","","22-11-2024 21:00:10","22-11-2024 19:56:19","22-11=
-2024 22:48:54","Cascaded Incident from TTO3578506","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","access =
issue during the night Grid outage, site went down before gen start due to =
poor battery backup // Gen automatically started","system","302964","22-11-=
2024 21:00:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003652235","O=
mnisport-Rail","","22-11-2024 20:54:58","22-11-2024 20:33:53","22-11-2024 2=
3:58:14","Active: no power issue, site is on grid with Ubaie =3D53V, Armand=
 nguetsa(691144412) from Huawei is nformed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: no power issue, site is on grid with Ubaie =3D53V, Armand nguetsa(691=
144412) from Huawei is nformed","alexandre.kamal@ihstowers.com","1266","22-=
11-2024 20:54:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003652093","Nkolo II=
 New","","22-11-2024 20:29:41","22-11-2024 20:19:26","22-11-2024 20:20:26",=
"Cascaded Incident from TTO3578639","Mba Lazare Herve","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","no power issue on site ,site on Gr=
id with U=3D54.6V The TX FME Eloundou Bertrand/ 693212405 of huawei is info=
rmed. Notice that we have disjunction at BTS OCM","system","265410","22-11-=
2024 20:29:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003652089","M=
imboman-Village","IHS_YND_709","22-11-2024 20:28:36","22-11-2024 20:19:26",=
"22-11-2024 20:20:26","no power issue on site ,site on Grid with U=3D54.6V =
The TX FME Eloundou Bertrand/ 693212405 of huawei is informed. Notice that =
we have disjunction at BTS OCM","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power iss=
ue on site ,site on Grid with U=3D54.6V The TX FME Eloundou Bertrand/ 69321=
2405 of huawei is informed. Notice that we have disjunction at BTS OCM","al=
exandre.kamal@ihstowers.com","551","22-11-2024 20:28:36","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003651966","Nko=
lbisson","IHS_YND_763","22-11-2024 20:13:35","22-11-2024 19:56:19","22-11-2=
024 22:48:54","access issue during the night Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started","TIENTCHEU NZETCH=
IEU GAEL","Access Denial","Lease Or Legal","Landlord Related Issues","Acces=
s Issue - Land Lord","access issue during the night Grid outage, site went =
down before gen start due to poor battery backup // Gen started","kamga.vir=
gile@ihstowers.com","1036","22-11-2024 20:13:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003651762","Bastos E=
koudou","","22-11-2024 19:52:30","22-11-2024 16:38:40","22-11-2024 18:34:31=
","Cascaded Incident from TTO3578278","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage,no space to deploy a=
 mobil gen//grid return","system","278768","22-11-2024 19:52:30","Sagemcom =
CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003651755","Lab=
oratoire  Meka","IHS_YND_193","22-11-2024 19:51:54","22-11-2024 16:38:40","=
22-11-2024 18:34:31","grid outage,no space to deploy a mobil gen//grid retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid outage,no space to deploy a mobil gen//grid return","kamga.virgile@ihs=
towers.com","11594","22-11-2024 19:51:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003651532","T=
singa","","22-11-2024 19:07:17","22-11-2024 18:59:12","22-11-2024 19:13:51"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen automatically started","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // Gen automatically started","a=
lexandre.kamal@ihstowers.com","487","22-11-2024 19:07:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003651525","M=
ANGUIERS CHAPELLE","","22-11-2024 19:05:25","22-11-2024 18:49:18","22-11-20=
24 19:21:22","grid outage,gen failed to start due to alarm undervoltage//he=
 reset the gen card and started it","Fabrice Pouakam","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start =
due to alarm undervoltage//he reset the gen card and started it","alexandre=
.kamal@ihstowers.com","968","22-11-2024 19:05:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0003651428","Nkoulou =
Carriere carrefourt","","22-11-2024 18:48:10","22-11-2024 17:39:22","22-11-=
2024 18:56:14","Cascaded Incident from TTO3577872","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","grid bad voltage=
,and gen failed to start//bypassed grid and started the gen","system","2750=
23","22-11-2024 18:48:10","Sagemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0003651424","Aba=
ng","IHS_YND_794","22-11-2024 18:46:54","22-11-2024 17:39:22","22-11-2024 1=
8:56:14","grid bad voltage,and gen failed to start//bypassed grid and start=
ed the gen","Mba Lazare Herve","Grid Supply","Passive","Grid","National Gri=
d - Phase Controller Faulty","grid bad voltage,and gen failed to start//byp=
assed grid and started the gen","kamga.virgile@ihstowers.com","4053","22-11=
-2024 18:46:54","Sagemcom CMR"
"Cancelled","Warning","T1241","IHS_YND_794","NOCINC0003650234","Nkoulou Car=
riere carrefourt","","22-11-2024 17:45:03","","","","Mba Lazare Herve","","=
","","","","kamga.virgile@ihstowers.com","312","22-11-2024 17:45:03","Sagem=
com CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003650055","Nko=
lbisson usines des eaux 2","","22-11-2024 17:33:08","22-11-2024 17:15:50","=
22-11-2024 18:10:41","grid outage,site went down because gen overload 9kva;=
105A//he reduice the load on site","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Overload","grid outage,site went down be=
cause gen overload 9kva;105A//he reduice the load on site","kamga.virgile@i=
hstowers.com","1039","22-11-2024 17:33:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003650034","MBIMBIM"=
,"","22-11-2024 17:27:55","22-11-2024 16:44:48","22-11-2024 17:25:09","Casc=
aded Incident from TTO3576393","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site went down because gen stopped with=
 alarm high temp//he open all the door and restarted it","system","271231",=
"22-11-2024 17:27:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003650033","Ngouetou=
","","22-11-2024 17:27:55","22-11-2024 16:44:48","22-11-2024 17:25:09","Cas=
caded Incident from TTO3576393","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because gen stopped wit=
h alarm high temp//he open all the door and restarted it","system","1220670=
","22-11-2024 17:27:55","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003649989","ODZ=
A CITE MBIA","","22-11-2024 17:23:17","22-11-2024 17:02:06","22-11-2024 17:=
40:06","Grid OUTAGE, site went down because gen fails to start due to ATS d=
isfunctionning // Gen manualy started","Albran Byorel","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down becau=
se gen fails to start due to ATS disfunctionning // Gen manualy started","k=
amga.virgile@ihstowers.com","1272","22-11-2024 17:23:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003649813","Yoko MTN=
","","22-11-2024 16:55:02","22-11-2024 16:44:48","22-11-2024 17:31:34","Cas=
caded Incident from TTO3576196","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because gen stopped wit=
h alarm high temp//he open all the door and restarted it","system","1220670=
","22-11-2024 16:55:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003649812","Ngoum","=
","22-11-2024 16:55:01","22-11-2024 16:44:48","22-11-2024 17:31:34","Cascad=
ed Incident from TTO3576196","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because gen stopped with a=
larm high temp//he open all the door and restarted it","system","271232","2=
2-11-2024 16:55:01","Sagemcom CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0003649800","Mat=
sari","IHS_YND_475, IHS_YND_454, IHS_YND_473, IHS_YND_456","22-11-2024 16:5=
3:57","22-11-2024 16:44:48","22-11-2024 17:31:34","site went down because g=
en stopped with alarm high temp//he open all the door and restarted it","Pa=
rker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Te=
mp - Coolant Level Issue","site went down because gen stopped with alarm hi=
gh temp//he open all the door and restarted it","kamga.virgile@ihstowers.co=
m","550","22-11-2024 16:53:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003649744","C=
omplexe-BEAC","","22-11-2024 16:46:41","22-11-2024 16:11:36","22-11-2024 16=
:50:36","Site went down because cb(100A) of batteries disjuncted // CB put =
back on","Albran Byorel","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Circuit Breaker Issue","Site went down because cb(100A) of batt=
eries disjuncted // CB put back on","alexandre.kamal@ihstowers.com","2106",=
"22-11-2024 16:46:41","Sagemcom CMR"
"Closed Complete","Warning","CTR_196","IHS_YND_159","NOCINC0003649675","Com=
plexe-BEAC","","22-11-2024 16:40:28","","","Site went Alarm because cb(100A=
) of batteries disjuncted // CB put back on","Albran Byorel","Warning","War=
ning","POWER","Warning - Site on Battery","Site went Alarm because cb(100A)=
 of batteries disjuncted // CB put back on","ludovic.tchagna@ihstowers.com"=
,"4","22-11-2024 16:40:28","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003648233","Nom=
ayos montee Meche","","22-11-2024 15:26:28","22-11-2024 15:19:15","22-11-20=
24 16:18:53","site went down because grid contactor of the bay DPC disfunct=
ionning//bypassed the grid contactor ","Fanda Brice","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","site went down because grid contact=
or of the bay DPC disfunctionning//bypassed the grid contactor ","kamga.vir=
gile@ihstowers.com","433","22-11-2024 15:26:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003648221","Bastos E=
koudou","","22-11-2024 15:24:21","22-11-2024 14:13:59","22-11-2024 16:25:25=
","Cascaded Incident from TTO3573948","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage,no space to deploy a=
 mobil gen//grid return","system","280184","22-11-2024 15:24:21","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003648117","E=
kie-Elegance","","22-11-2024 15:07:15","22-11-2024 13:51:07","22-11-2024 16=
:11:33","grid outage//MDG 13 kva deployed","Albran Byorel","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","grid outage//MDG 13 kva=
 deployed","alexandre.kamal@ihstowers.com","4569","22-11-2024 15:07:15","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003647928","A=
fanoya","","22-11-2024 14:42:30","22-11-2024 14:33:25","22-11-2024 14:43:25=
","Active//No power issue, U=3D54V on grid Tx FME George/697461814/ From hu=
awei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, U=3D=
54V on grid Tx FME George/697461814/ From huawei is informed","alexandre.ka=
mal@ihstowers.com","547","22-11-2024 14:42:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003647897","B=
itoto","","22-11-2024 14:38:05","22-11-2024 14:23:52","22-11-2024 21:33:52"=
,"Site went down due to work(Swap PWC and GEN) // End of work","Mba Lazare =
Herve","Installation Activity","Passive","Planned Activity","Installation A=
ctivity","Site went down due to work(Swap PWC and GEN) // End of work","ale=
xandre.kamal@ihstowers.com","855","22-11-2024 14:38:05","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0003647895","Jou=
vence Mbenda","","22-11-2024 14:38:00","22-11-2024 14:26:39","22-11-2024 14=
:55:39","grid outage,gen stopped with alarm high temp//he added water in ra=
diator","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Hi=
gh Engine Temp - Coolant Level Issue","grid outage,gen stopped with alarm h=
igh temp//he added water in radiator","kamga.virgile@ihstowers.com","682","=
22-11-2024 14:38:00","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003647801","Lab=
oratoire  Meka","IHS_YND_193","22-11-2024 14:31:45","22-11-2024 14:13:59","=
22-11-2024 16:25:25","grid outage,no space to deploy a mobil gen//grid retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid outage,no space to deploy a mobil gen//grid return","kamga.virgile@ihs=
towers.com","1067","22-11-2024 14:31:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003647561","E=
lig Edzoa","","22-11-2024 13:49:17","22-11-2024 13:32:11","22-11-2024 19:22=
:11","Site went down due to work: Yovo Atswede/698529863/ From SFM working =
on site (Swapp PWC)//End of work","Delor Telezing","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Site went down due to=
 work: Yovo Atswede/698529863/ From SFM working on site (Swapp PWC)//End of=
 work","stephane.nkamwa@ihstowers.com","1027","22-11-2024 13:49:17","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0003647354","O=
lezoa OCM","","22-11-2024 13:21:23","22-11-2024 09:49:10","27-11-2024 13:30=
:17","Grid outage.no space to deploy mobile gen//Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no sp=
ace to deploy mobile gen//Grid return","stephane.nkamwa@ihstowers.com","127=
34","22-11-2024 13:21:23","Sagemcom CMR"
"Closed Complete","Warning","T0051","IHS_YND_297","NOCINC0003647174","Messa=
ssi","","22-11-2024 12:50:17","","","Grid outage, Site alarming on battery =
because Battery of Gen faulty// Grid return","Fabrice Pouakam","Warning","W=
arning","POWER","Warning - Site on Battery","...Grid outage, Site alarming =
on battery because Battery of Gen faulty// Grid return","landry.etame@ihsto=
wers.com","5","22-11-2024 12:50:17","Sagemcom CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0003647156","Nko=
mo II","","22-11-2024 12:44:20","22-11-2024 12:44:16","22-11-2024 13:10:16"=
,"site was not down at MtN","Albran Byorel","Incorrectly Logged Tickets","E=
rror","Error","Error","site was not down at MtN","landry.etame@ihstowers.co=
m","5","22-11-2024 12:44:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003647106","Nkolbiss=
on usines des eaux 2","","22-11-2024 12:33:30","22-11-2024 12:26:54","22-11=
-2024 14:10:27","Cascaded Incident from TTO3573117","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Site we=
nt down because CB(125A) burned in DC BOX// He did a bridge with domino","s=
ystem","396","22-11-2024 12:33:30","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003647097","Nko=
lbisson","IHS_YND_763","22-11-2024 12:32:05","22-11-2024 12:26:54","22-11-2=
024 14:10:27","Site went down because CB(125A) burned in DC BOX// He did a =
bridge with domino","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down be=
cause CB(125A) burned in DC BOX// He did a bridge with domino","landry.etam=
e@ihstowers.com","312","22-11-2024 12:32:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003647046","S=
tade-Abega","","22-11-2024 12:25:53","22-11-2024 12:09:43","22-11-2024 12:2=
5:07","grid outage,gen fails to start due to candle faulty//Grid return","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Start=
er","grid outage,gen fails to start due to candle faulty//Grid return","ste=
phane.nkamwa@ihstowers.com","971","22-11-2024 12:25:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0003647000","O=
bili Carrefour","","22-11-2024 12:17:28","22-11-2024 12:09:47","22-11-2024 =
13:25:09","Grid fluctuation, site went down because Gen started and stopped=
 due to Grid bad voltage// He bypassed Grid and Gen manualy started","Paul =
BIBOUM","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, site went down because Gen started and stopped due=
 to Grid bad voltage// He bypassed Grid and Gen manualy started","stephane.=
nkamwa@ihstowers.com","462","22-11-2024 12:17:28","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003646571","Nom=
ayos montee Meche","","22-11-2024 11:18:52","22-11-2024 11:12:41","22-11-20=
24 12:32:04","Grid outage site went down because gen fails to start due cha=
rging alternator faulty // gen manually started with external battery","Fan=
da Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternat=
or","Grid outage site went down because gen fails to start due charging alt=
ernator faulty // gen manually started with external battery","landry.etame=
@ihstowers.com","372","22-11-2024 11:18:52","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0003646527","Men=
dong vallee","","22-11-2024 11:14:43","22-11-2024 11:08:37","22-11-2024 11:=
16:40","Grid outage, Site went down because Gen overload (20Kva, 300A)// He=
 reduiced the load and started Gen manualy","Fanda Brice","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Sit=
e went down because Gen overload (20Kva, 300A)// He reduiced the load and s=
tarted Gen manualy","landry.etame@ihstowers.com","367","22-11-2024 11:14:43=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003646353","MVAN SAC=
EL","","22-11-2024 10:56:50","22-11-2024 10:49:04","22-11-2024 16:36:37","C=
ascaded Incident from TTO3572285","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Gen overload (20KVA,290 A) waitting=
 Grid return","system","466","22-11-2024 10:56:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003646337","M=
VAN","IHS_YND_510","22-11-2024 10:56:14","22-11-2024 10:49:04","22-11-2024 =
16:36:37"," grid outage,site went down because Gen overload (20KVA,290 A) /=
/ Grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload"," grid outage,site went down because Gen overload (20KVA,290 =
A) // Grid return","stephane.nkamwa@ihstowers.com","431","22-11-2024 10:56:=
14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003645369","O=
dza II","","22-11-2024 08:32:33","22-11-2024 08:26:27","22-11-2024 08:51:25=
","Grid outage, site went down because gen fails to start due to fuse of gr=
id contactor faulty // he replaced the fuse contactor, Site on Grid","Albra=
n Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gri=
d outage, site went down because gen fails to start due to fuse of grid con=
tactor faulty // he replaced the fuse contactor, Site on Grid","stephane.nk=
amwa@ihstowers.com","368","22-11-2024 08:32:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003645301","N=
GONA","","22-11-2024 08:12:25","22-11-2024 08:07:19","22-11-2024 13:10:25",=
"Active//No power issue on site ,site on GRID  with Ubaie=3D55,5 V The TX F=
ME  Lionel Adjep (655184876)  Huawei is informed","Mba Lazare Herve","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue on site ,site on GRID  with Ubaie=3D55,5 V The=
 TX FME  Lionel Adjep (655184876)  Huawei is informed","stephane.nkamwa@ihs=
towers.com","307","22-11-2024 08:12:25","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003645280","Men=
dong3","","22-11-2024 08:08:57","22-11-2024 07:57:48","22-11-2024 15:51:21"=
,"Grid outage, No space to deploy MDG // Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage, No space to =
deploy MDG // Grid return","landry.etame@ihstowers.com","670","22-11-2024 0=
8:08:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003644878","B=
itoto","","22-11-2024 06:33:27","22-11-2024 06:29:17","22-11-2024 13:10:50"=
,"Active//No power issue on site , Tx Issue : site on Grid ,Ubai: 54,4V;  T=
he fme Tx  George/697461814/ From huawei is informed and notice that disjun=
ction at OCM Equipment","Mba Lazare Herve","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power iss=
ue on site , Tx Issue : site on Grid ,Ubai: 54,4V;  The fme Tx  George/6974=
61814/ From huawei is informed and notice that disjunction at OCM Equipment=
","stephane.nkamwa@ihstowers.com","251","22-11-2024 06:33:27","Sagemcom CMR=
"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003644859","OBA=
M NGOLA OCM","","22-11-2024 06:26:32","22-11-2024 06:20:25","22-11-2024 06:=
26:36","Grid fluctuation, site went down because Gen started and stopped du=
e Grid bad voltage// Grid stabilized","MINKA NICOLAS","Grid Supply","Passiv=
e","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site=
 went down because Gen started and stopped due Grid bad voltage// Grid stab=
ilized","landry.etame@ihstowers.com","368","22-11-2024 06:26:32","Sagemcom =
CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003644504","Nko=
lmvack","","22-11-2024 05:04:35","22-11-2024 04:59:29","22-11-2024 06:13:00=
","Hybrid Gen: Site went down because Gen stopped with alarm ""Low oil pres=
sure""// He added 3L of oil and started Gen manualy","Parker Tchoup","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","Hybrid Gen: Site =
went down because Gen stopped with alarm ""Low oil pressure""// He added 3L=
 of oil and started Gen manualy","rouselle.schoune@ihstowers.com","307","22=
-11-2024 05:04:35","Sagemcom CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0003644290","RUE=
 FOE","","22-11-2024 03:31:59","22-11-2024 03:26:46","22-11-2024 07:42:12",=
"Acces issue during the Night Site went down due to insufficient of rectife=
rs due to load increase(02)// He added 02 rectifiers (04)","Delor Telezing"=
,"Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue -=
 Land Lord","Acces issue during the Night Site went down due to insufficien=
t of rectifers due to load increase(02)// He added 02 rectifiers (04)","rou=
selle.schoune@ihstowers.com","313","22-11-2024 03:31:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003644215","Bastos E=
koudou","","22-11-2024 02:58:20","22-11-2024 02:44:07","22-11-2024 06:14:31=
","Cascaded Incident from TTO3569861","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage, No space to deploy =
MDG// Grid return","system","853","22-11-2024 02:58:20","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003644197","Lab=
oratoire  Meka","IHS_YND_193","22-11-2024 02:51:17","22-11-2024 02:44:07","=
22-11-2024 06:14:31","Grid outage, No space to deploy MDG// Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, No space to deploy MDG// Grid return","rouselle.schoune@ihstowers.co=
m","430","22-11-2024 02:51:17","Sagemcom CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0003644008","Nko=
lfon Cimencam","","22-11-2024 01:44:38","22-11-2024 01:41:32","22-11-2024 0=
6:08:46","Grid outage, Site went down because Gen stopped with alarm ""high=
 temp""due to radiator pierced// He resoldering the pierced radiator and ad=
ded water and started Gen manualy","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outa=
ge, Site went down because Gen stopped with alarm ""high temp""due to radia=
tor pierced// He resoldering the pierced radiator and added water and start=
ed Gen manualy","rouselle.schoune@ihstowers.com","186","22-11-2024 01:44:38=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003643856","A=
fanoya","","22-11-2024 00:40:46","22-11-2024 00:38:33","22-11-2024 04:39:33=
","Active//No power issue, U=3D54.4V and Site is on Grid,The   FME TX Georg=
e/697461814/ From huawei is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue, U=3D54.4V and Site is on Grid,The   FME TX George/697461814=
/ From huawei is informed","denis.mballa@ihstowers.com","135","22-11-2024 0=
0:40:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003643414","N=
GONA","","21-11-2024 22:41:54","21-11-2024 22:36:25","21-11-2024 23:57:35",=
"Active//No power issue on site U=3D55,3V site on Gen ,The Fme Tx Lionel St=
eeve of huawei is informed and UP at=3D10:43 PM","Mba Lazare Herve","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site U=3D55,3V site on Gen ,The Fme Tx Lione=
l Steeve of huawei is informed and UP at=3D10:43 PM","denis.mballa@ihstower=
s.com","330","21-11-2024 22:41:54","Sagemcom CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0003643264","RUE=
 FOE","","21-11-2024 22:12:17","21-11-2024 22:09:12","21-11-2024 23:43:25",=
"Site went down due to insuffisance of rectifier  on Site // He add 01 Rect=
ifier and Site is on Grid","Delor Telezing","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down due to insuffisance of rectifi=
er  on Site // He add 01 Rectifier and Site is on Grid","rouselle.schoune@i=
hstowers.com","186","21-11-2024 22:12:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003642495","N=
GONA","","21-11-2024 20:04:43","21-11-2024 20:01:31","21-11-2024 21:36:31",=
"No power issue on site U=3D55,7v site on gen tx fme Lionel Steeve of huawe=
i is informed","Mba Lazare Herve","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D55=
,7v site on gen tx fme Lionel Steeve of huawei is informed","ludivine.ngama=
leu@ihstowers.com","193","21-11-2024 20:04:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003642277","M=
elen Ba'aba","","21-11-2024 19:25:49","21-11-2024 19:21:44","21-11-2024 20:=
35:23","site went down because CB 125A disjuncted in DC-BOX who feeds equip=
ment OCM//he reamed the CB","Siligap Boris","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Circuit Breaker Issue","site went down becau=
se CB 125A disjuncted in DC-BOX who feeds equipment OCM//he reamed the CB",=
"ludivine.ngamaleu@ihstowers.com","246","21-11-2024 19:25:49","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003642248","Nkolbiss=
on usines des eaux 2","","21-11-2024 19:17:30","21-11-2024 19:06:31","21-11=
-2024 20:17:00","Cascaded Incident from TTO3567507","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, site went down before gen start due to poor batteries backup // gen s=
tarted,and power reset has been done","system","298459","21-11-2024 19:17:3=
0","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003642234","Nko=
lbisson","IHS_YND_763","21-11-2024 19:15:39","21-11-2024 19:06:31","21-11-2=
024 20:17:00","Grid outage, site went down before gen start due to poor bat=
teries backup // gen started,and power reset has been done","TIENTCHEU NZET=
CHIEU GAEL","Equipment Repair","Passive","Control Panel","Power Cabinet - B=
attery Low","Grid outage, site went down before gen start due to poor batte=
ries backup // gen started,and power reset has been done","olivier.kwedi@ih=
stowers.com","549","21-11-2024 19:15:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003642105","N=
koabang2","","21-11-2024 18:51:35","21-11-2024 18:43:30","21-11-2024 18:58:=
15","grid outage,gen failed to start due to alarm undervoltage//he reset th=
e card and started it","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","grid outage,gen failed to start due to alarm=
 undervoltage//he reset the card and started it","ludivine.ngamaleu@ihstowe=
rs.com","486","21-11-2024 18:51:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003642055","B=
riqueterie","","21-11-2024 18:39:19","21-11-2024 18:24:11","22-11-2024 10:5=
8:48","grid outage, no space to deploy a mobil gen // grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,=
 no space to deploy a mobil gen // grid return","etienne.itondo@ihstowers.c=
om","909","21-11-2024 18:39:19","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0003642029","Bri=
quetterie","","21-11-2024 18:33:26","21-11-2024 18:26:16","22-11-2024 11:00=
:35","grid outage, no space to deploy a mobil gen // grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, =
no space to deploy a mobil gen // grid return","olivier.kwedi@ihstowers.com=
","432","21-11-2024 18:33:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003641970","C=
rf-Nsam","","21-11-2024 18:24:56","21-11-2024 18:20:52","21-11-2024 18:44:5=
2","Site went down due to PWC overload ( 24 kw, 270 A)// he reduice the Loa=
d and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Site went down due to PWC overload ( 24=
 kw, 270 A)// he reduice the Load and Site is on Grid","ludivine.ngamaleu@i=
hstowers.com","245","21-11-2024 18:24:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003641910","Dong",""=
,"21-11-2024 18:18:41","21-11-2024 18:03:13","21-11-2024 18:20:45","Cascade=
d Incident from TTO3567088","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site U=3D48,7v site on gen =
site down because is impacted by Mbandjock","system","302359","21-11-2024 1=
8:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0003641909","Montee-J=
ouvence-II","","21-11-2024 18:18:41","21-11-2024 18:03:13","21-11-2024 18:2=
0:45","Cascaded Incident from TTO3567088","Hyemafo Gildas","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D48,=
7v site on gen site down because is impacted by Mbandjock","system","302359=
","21-11-2024 18:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003641906","Nguila",=
"","21-11-2024 18:18:40","21-11-2024 18:03:13","21-11-2024 18:20:45","Casca=
ded Incident from TTO3567088","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site U=3D48,7v site on ge=
n site down because is impacted by Mbandjock","system","302358","21-11-2024=
 18:18:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0003641865","D=
onga","IHS_YND_433, IHS_YND_592, IHS_YND_443, IHS_YND_518, IHS_YND_444, IHS=
_YND_402, IHS_YND_442","21-11-2024 18:12:17","21-11-2024 18:03:13","21-11-2=
024 18:20:45","No power issue on site U=3D48,7v site on gen site down becau=
se is impacted by Mbandjock and not managing by IHS","Parker Tchoup","3RD P=
arty Power Failure","Passive","Power Provided By 3RD Party","Power Provided=
 By 3RD Party","No power issue on site U=3D48,7v site on gen site down beca=
use is impacted by Mbandjock and not managing by IHS","ludivine.ngamaleu@ih=
stowers.com","545","21-11-2024 18:12:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003641820","Essomba"=
,"","21-11-2024 17:59:21","21-11-2024 17:55:55","21-11-2024 17:57:55","Casc=
aded Incident from TTO3567012","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before G=
en start due to poor backup// Gen started automaticaly","system","1216238",=
"21-11-2024 17:59:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003641821","Biteng-M=
aetur","","21-11-2024 17:59:21","21-11-2024 17:55:55","21-11-2024 17:57:55"=
,"Cascaded Incident from TTO3567012","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
fore Gen start due to poor backup// Gen started automaticaly","system","121=
6238","21-11-2024 17:59:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003641819","AWAE OCM=
","","21-11-2024 17:59:21","21-11-2024 17:55:55","21-11-2024 17:57:55","Cas=
caded Incident from TTO3567012","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down before =
Gen start due to poor backup// Gen started automaticaly","system","1216237"=
,"21-11-2024 17:59:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003641818","Tradex-N=
komo","","21-11-2024 17:59:21","21-11-2024 17:55:55","21-11-2024 17:57:55",=
"Cascaded Incident from TTO3567012","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 Gen start due to poor backup// Gen started automaticaly","system","266763"=
,"21-11-2024 17:59:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003641817","Bitoto",=
"","21-11-2024 17:59:20","21-11-2024 17:55:55","21-11-2024 17:57:55","Casca=
ded Incident from TTO3567012","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down before Ge=
n start due to poor backup// Gen started automaticaly","system","266764","2=
1-11-2024 17:59:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003641811","B=
iteng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179, IHS_YND_249","2=
1-11-2024 17:58:00","21-11-2024 17:55:55","21-11-2024 17:57:55","Grid outag=
e, site went down before Gen start due to poor backup// Gen started automat=
icaly","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage, site went down before Gen start due=
 to poor backup// Gen started automaticaly","ludivine.ngamaleu@ihstowers.co=
m","126","21-11-2024 17:58:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003641753","N=
GONA","","21-11-2024 17:45:50","21-11-2024 17:42:44","21-11-2024 19:33:09",=
"grid outage,gen stopped with alarm high temp//he added water in radiator",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Eng=
ine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high te=
mp//he added water in radiator","ludivine.ngamaleu@ihstowers.com","187","21=
-11-2024 17:45:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003641693","A=
fanoya","","21-11-2024 17:31:09","21-11-2024 17:05:54","21-11-2024 18:55:27=
","Active//No power issue, U=3D54V on grid Tx FME George/697461814/ From hu=
awei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, U=3D=
54V on grid Tx FME George/697461814/ From huawei is informed","etienne.iton=
do@ihstowers.com","1516","21-11-2024 17:31:09","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003641380","Pha=
rmacie SION","","21-11-2024 16:45:05","21-11-2024 16:40:58","21-11-2024 16:=
49:58","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen automatically started","Paul BIBOUM","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen automatically started=
","olivier.kwedi@ihstowers.com","248","21-11-2024 16:45:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003641309","B=
riqueterie","","21-11-2024 16:32:04","21-11-2024 16:09:48","21-11-2024 17:4=
0:02","Grid outage no space to deploy a MDG//grid return ","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space=
 to deploy a MDG//grid return ","etienne.itondo@ihstowers.com","1337","21-1=
1-2024 16:32:04","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0003641240","Bri=
quetterie","","21-11-2024 16:21:46","21-11-2024 16:13:37","21-11-2024 17:42=
:55","Grid outage no space to deploy a MDG//grid return ","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space =
to deploy a MDG//grid return ","olivier.kwedi@ihstowers.com","490","21-11-2=
024 16:21:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0003640833","Boga-Mah=
ole","","21-11-2024 15:23:04","21-11-2024 15:04:59","21-11-2024 17:31:40","=
Cascaded Incident from TTO3565774","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to work, Marce=
l (657108566)/ From Sagemcom is working on site(normalization of ATS and re=
placement of AVR)//End of work","system","277248","21-11-2024 15:23:04","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003640832","Mamb",""=
,"21-11-2024 15:23:04","21-11-2024 15:04:59","21-11-2024 17:31:40","Cascade=
d Incident from TTO3565774","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to work, Marcel (6571=
08566)/ From Sagemcom is working on site(normalization of ATS and replaceme=
nt of AVR)//End of work","system","277247","21-11-2024 15:23:04","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0003640828","Eseka OC=
M","","21-11-2024 15:23:03","21-11-2024 15:04:59","21-11-2024 17:31:40","Ca=
scaded Incident from TTO3565774","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work, Marcel =
(657108566)/ From Sagemcom is working on site(normalization of ATS and repl=
acement of AVR)//End of work","system","277252","21-11-2024 15:23:03","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003640830","Song-bon=
g","","21-11-2024 15:23:03","21-11-2024 15:04:59","21-11-2024 17:31:40","Ca=
scaded Incident from TTO3565774","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work, Marcel =
(657108566)/ From Sagemcom is working on site(normalization of ATS and repl=
acement of AVR)//End of work","system","277247","21-11-2024 15:23:03","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003640825","Boumnyeb=
el","","21-11-2024 15:23:02","21-11-2024 15:04:59","21-11-2024 17:31:40","C=
ascaded Incident from TTO3565774","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work, Marcel=
 (657108566)/ From Sagemcom is working on site(normalization of ATS and rep=
lacement of AVR)//End of work","system","277251","21-11-2024 15:23:02","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003640824","Ngog Map=
ubi","","21-11-2024 15:23:02","21-11-2024 15:04:59","21-11-2024 17:31:40","=
Cascaded Incident from TTO3565774","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to work, Marce=
l (657108566)/ From Sagemcom is working on site(normalization of ATS and re=
placement of AVR)//End of work","system","277250","21-11-2024 15:23:02","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003640821","Ndogbess=
ol","","21-11-2024 15:23:01","21-11-2024 15:04:59","21-11-2024 17:31:40","C=
ascaded Incident from TTO3565774","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work, Marcel=
 (657108566)/ From Sagemcom is working on site(normalization of ATS and rep=
lacement of AVR)//End of work","system","277249","21-11-2024 15:23:01","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003640820","Eseka To=
wn","","21-11-2024 15:23:01","21-11-2024 15:04:59","21-11-2024 17:31:40","C=
ascaded Incident from TTO3565774","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work, Marcel=
 (657108566)/ From Sagemcom is working on site(normalization of ATS and rep=
lacement of AVR)//End of work","system","277249","21-11-2024 15:23:01","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0003640819","Boumnyeb=
el OCM","","21-11-2024 15:23:01","21-11-2024 15:04:59","21-11-2024 17:31:40=
","Cascaded Incident from TTO3565774","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work, Ma=
rcel (657108566)/ From Sagemcom is working on site(normalization of ATS and=
 replacement of AVR)//End of work","system","277248","21-11-2024 15:23:01",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0003640789","Beh=
ind P T school Yde","","21-11-2024 15:18:42","21-11-2024 15:11:35","21-11-2=
024 17:07:30","site went down due to disjunction Cb(63A) in DC Box // He di=
d a bridge with Cb(63A), site on grid","Paul BIBOUM","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went d=
own due to disjunction Cb(63A) in DC Box // He did a bridge with Cb(63A), s=
ite on grid","olivier.kwedi@ihstowers.com","428","21-11-2024 15:18:42","Sag=
emcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0003640319","Ntu=
i administration","","21-11-2024 14:06:59","21-11-2024 13:42:45","21-11-202=
4 14:07:33","site went down because 1/2rectifier faulty//he replaced the fa=
ulty rectifier,power issue resolved since 14:07 and the site remain down af=
ter power reset done Tx fme Gergoire 654547479 of huawei is inf","Parker Tc=
houp","Equipment Repair","Passive","Rectifier","Rectifier Module","site wen=
t down because 1/2rectifier faulty//he replaced the faulty rectifier,power =
issue resolved since 14:07 and the site remain down after power reset done =
Tx fme Gergoire 654547479 of huawei is informed","kamga.virgile@ihstowers.c=
om","1455","21-11-2024 14:06:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0003639542","Awae Esc=
alier","","21-11-2024 12:56:10","21-11-2024 12:16:01","21-11-2024 12:20:01"=
,"Cascaded Incident from TTO3564224","Albran Byorel","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site , Ubaie=3D54.=
4V site On GridThe Tx FME Georges 697461814 from Huawei is informed Notice =
thad disjunction in OCM Equipment","system","2409","21-11-2024 12:56:10","S=
agemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003639423","NTU=
I TOWN","","21-11-2024 12:34:09","21-11-2024 11:37:57","21-11-2024 14:17:07=
","Grid outage, site went down due to main gen faulty // Grid return (Main =
Gen to be replaced)","Parker Tchoup","Equipment Repair","Passive","ACDG Gen=
","ACDG - Generator Faulty","Grid outage, site went down due to main gen fa=
ulty // Grid return (Main Gen to be replaced)","kamga.virgile@ihstowers.com=
","3373","21-11-2024 12:34:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0003639357","Awae Ewo=
nkan","","21-11-2024 12:26:10","21-11-2024 12:16:01","21-11-2024 12:20:01",=
"Cascaded Incident from TTO3564224","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site , Ubaie=3D54.4=
V site On GridThe Tx FME Georges 697461814 from Huawei is informed Notice t=
had disjunction in OCM Equipment","system","609","21-11-2024 12:26:10","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0003639347","A=
wae-Yde","IHS_YND_535, IHS_YND_171","21-11-2024 12:25:07","21-11-2024 12:16=
:01","21-11-2024 12:20:01","No power issue on site , Ubaie=3D54.4V site On =
GridThe Tx FME Georges 697461814 from Huawei is informed Notice thad disjun=
ction in OCM Equipment","Albran Byorel","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
, Ubaie=3D54.4V site On GridThe Tx FME Georges 697461814 from Huawei is inf=
ormed Notice thad disjunction in OCM Equipment","alexandre.kamal@ihstowers.=
com","547","21-11-2024 12:25:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003638211","Nkolbiss=
on usines des eaux 2","","21-11-2024 10:03:30","21-11-2024 09:51:59","21-11=
-2024 10:29:59","Cascaded Incident from TTO3562968","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, site went down due to old gen overload( 20Kva, 205A) // He reduice th=
e load and manualy start the gen","system","281410","21-11-2024 10:03:30","=
Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003638199","Nko=
lbisson","IHS_YND_763","21-11-2024 10:02:30","21-11-2024 09:51:59","21-11-2=
024 10:29:59","Grid outage, site went down due to old gen overload( 20Kva, =
205A) // He reduice the load and manualy start the gen","TIENTCHEU NZETCHIE=
U GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid out=
age, site went down due to old gen overload( 20Kva, 205A) // He reduice the=
 load and manualy start the gen","kamga.virgile@ihstowers.com","632","21-11=
-2024 10:02:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003637471","M=
IMBOMAN LIBERTE","","21-11-2024 08:35:19","21-11-2024 08:29:14","21-11-2024=
 09:27:14","GRID OUTAGE, site went down because main gen faulty  // MDG 20K=
va has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Generator Faulty","GRID OUTAGE, site went down because main gen fa=
ulty  // MDG 20Kva has deployed","alexandre.kamal@ihstowers.com","367","21-=
11-2024 08:35:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003637011","C=
rf-Nsam","","21-11-2024 07:04:55","21-11-2024 06:57:48","21-11-2024 07:04:4=
8","Site went down due to PWC overload ( 24 kw, 270 A)// he reduice the Loa=
d and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Site went down due to PWC overload ( 24=
 kw, 270 A)// he reduice the Load and Site is on Grid","alexandre.kamal@ihs=
towers.com","428","21-11-2024 07:04:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003636599","Akak-Nko=
zoa-MTN-IHS","","21-11-2024 05:29:20","21-11-2024 05:27:17","21-11-2024 05:=
36:33","Cascaded Incident from TTO3561159","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo outage, site down be=
fore DG start due to poor backup // DG started automatically","system","275=
761","21-11-2024 05:29:20","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003636267","Nko=
lbisson","","21-11-2024 04:24:48","20-11-2024 19:42:12","21-11-2024 06:45:1=
2","Access issue during the night. Site went down due to Disjunction of CB(=
63) in PWC // he replace it by CB(80)","TIENTCHEU NZETCHIEU GAEL","Access D=
enial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord=
","Access issue during the night. Site went down due to Disjunction of CB(6=
3) in PWC // he replace it by CB(80)","christian.fonkou@ihstowers.com","313=
57","21-11-2024 04:24:48","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003635735","Ema=
na","","21-11-2024 01:25:11","21-11-2024 01:22:04","21-11-2024 06:37:04","a=
ccess issue during the Night: Grid outage, site went down because gen ran u=
ntill fuel shortage // Refueling done","Fabrice Pouakam","Access Denial","L=
ease Or Legal","Landlord Related Issues","Access Issue - Land Lord","access=
 issue during the Night: Grid outage, site went down because gen ran untill=
 fuel shortage // Refueling done","christian.fonkou@ihstowers.com","188","2=
1-11-2024 01:25:11","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_008","NOCINC0003635688","CNDH","","=
21-11-2024 01:22:49","","","The site alarmed because the air conditioner wa=
s completely frozen // defrost Done and air conditioner restarted","Paul BI=
BOUM","Warning","Warning","ENVIRONMENT","Warning - High Temperature","The s=
ite alarmed because the air conditioner was completely frozen // defrost Do=
ne and air conditioner restarted","joelle.ekessi@ihstowers.com","8","21-11-=
2024 01:22:49","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_206","NOCINC0003635134","ARMP","","=
20-11-2024 23:08:49","","","Site alarming on High temp because Aircon is fa=
ulty and shelter closed// He open shelter","Mboua Thierry","Warning","Warni=
ng","ENVIRONMENT","Warning - Aircon Controller Faulty","Site alarming on Hi=
gh temp because Aircon is faulty and shelter closed// He open shelter","joe=
lle.ekessi@ihstowers.com","8","20-11-2024 23:08:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0003635025","Odza Min=
kan IHS","","20-11-2024 22:43:51","20-11-2024 22:18:38","20-11-2024 22:29:0=
2","Cascaded Incident from TTO3559262","Albran Byorel","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site ,site on Gr=
id with Ubaie=3D53.8 V The Tx fme  Lionel adjep(655184876) from Huawei is i=
nformed","system","1513","20-11-2024 22:43:51","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003634950","Nko=
lnda","IHS_YND_715, IHS_YND_749","20-11-2024 22:28:42","20-11-2024 22:18:38=
","20-11-2024 23:29:02","No power issue on site ,site on Grid with Ubaie=3D=
53.8 V The Tx fme  Lionel adjep(655184876) from Huawei is informed","Albran=
 Byorel","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","No power issue on site ,site on Grid with Ubaie=3D53.8=
 V The Tx fme  Lionel adjep(655184876) from Huawei is informed","christian.=
fonkou@ihstowers.com","605","20-11-2024 22:28:42","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003634932","ODZ=
A MINKAN EDIBI ASSI","","20-11-2024 22:26:45","20-11-2024 22:18:38","20-11-=
2024 22:29:02","cascaded behing TTO3559262","Albran Byorel","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue on site ,site =
on Grid with Ubaie=3D53.8 V The Tx fme  Lionel adjep(655184876) from Huawei=
 is informed","christian.fonkou@ihstowers.com","1432","20-11-2024 22:26:45"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003634086","B=
itoto","","20-11-2024 20:45:37","20-11-2024 20:41:25","20-11-2024 23:45:16"=
,"Active//No power issue on site , Tx Issue : site on Grid ,Ubai: 54,4V;  T=
he fme Tx  George/697461814/ From huawei is informed and notice that disjun=
ction at OCM Equipment","Mba Lazare Herve","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power iss=
ue on site , Tx Issue : site on Grid ,Ubai: 54,4V;  The fme Tx  George/6974=
61814/ From huawei is informed and notice that disjunction at OCM Equipment=
","denis.mballa@ihstowers.com","253","20-11-2024 20:45:37","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003633761","Nko=
lnda","","20-11-2024 19:58:57","20-11-2024 19:50:53","20-11-2024 20:45:22",=
"Active: no power issue, site is on grid with Ubaie=3D53V, Lionel adjep (65=
5184876) from Huawei is infomred","Albran Byorel","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue, site is on grid with Ubaie=3D53V, Lionel adjep (655184876) from =
Huawei is infomred","rouselle.schoune@ihstowers.com","485","20-11-2024 19:5=
8:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003633242","E=
ssomba","","20-11-2024 19:00:10","20-11-2024 18:54:55","20-11-2024 20:46:35=
","Grid outage, Site went down because Gen started and stopped with ""High =
temp"" alarm causing // He open Gen door and started Gen manualy","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Grid outage, Site went down because Gen started and=
 stopped with ""High temp"" alarm causing // He open Gen door and started G=
en manualy","denis.mballa@ihstowers.com","317","20-11-2024 19:00:10","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0003632106","O=
mnisport 3","","20-11-2024 17:02:06","20-11-2024 16:57:51","20-11-2024 21:2=
2:36","Active: no power issue, site is on grid with Ubaie=3D53V; Armand Ngu=
etsa(691144412)","Delor Telezing","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, site =
is on grid with Ubaie=3D53V; Armand Nguetsa(691144412)","denis.mballa@ihsto=
wers.com","255","20-11-2024 17:02:06","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0003632074","Bri=
quetterie","","20-11-2024 16:56:46","20-11-2024 16:55:41","21-11-2024 15:15=
:23","Grid outage no space to deploy a MDG// grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space =
to deploy a MDG// grid return","rouselle.schoune@ihstowers.com","66","20-11=
-2024 16:56:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003632073","B=
riqueterie","","20-11-2024 16:56:38","20-11-2024 16:52:22","21-11-2024 15:1=
3:54","Grid outage no space to deploy a MDG// grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space=
 to deploy a MDG// grid return","denis.mballa@ihstowers.com","257","20-11-2=
024 16:56:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003632038","C=
rf-Nsam","","20-11-2024 16:50:38","20-11-2024 16:47:23","20-11-2024 17:49:5=
4","Grid outage,site went down because Gen overload 20kva,280A//We reduce  =
load and gen manually started ","MINKA NICOLAS","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage,site went down because Gen over=
load 20kva,280A//We reduce  load and gen manually started ","denis.mballa@i=
hstowers.com","196","20-11-2024 16:50:38","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_528","NOCINC0003631675","MEHANDAN",=
"","20-11-2024 16:07:10","","","Site alarming because Grid outage // Gen au=
tomatically started and alarm cleraed","Albran Byorel","Warning","Warning",=
"POWER","Warning - Site on Battery","Site alarming because Grid outage // G=
en automatically started and alarm cleraed","denis.mballa@ihstowers.com","3=
","20-11-2024 16:07:10","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003631218","ODZ=
A CITE MBIA","","20-11-2024 15:29:49","20-11-2024 15:17:59","20-11-2024 16:=
15:19","Grid OUTAGE, site went down because gen fails to start due to ATS d=
isfunctionning // Gen manualy started","Albran Byorel","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down becau=
se gen fails to start due to ATS disfunctionning // Gen manualy started","r=
ouselle.schoune@ihstowers.com","710","20-11-2024 15:29:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0003631194","Omnispor=
t-Rail","","20-11-2024 15:25:00","20-11-2024 15:19:05","20-11-2024 16:22:06=
","Cascaded Incident from TTO3555142","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage//MDG of 13 kva has =
deployed","system","283332","20-11-2024 15:25:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0003631189","H=
-Paradis","IHS_YND_506","20-11-2024 15:24:16","20-11-2024 15:19:05","20-11-=
2024 16:22:06","Grid outage//MDG of 13 kva has deployed","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG of 13=
 kva has deployed","denis.mballa@ihstowers.com","312","20-11-2024 15:24:16"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003631034","Nkolbiss=
on usines des eaux 2","","20-11-2024 15:02:10","20-11-2024 14:15:19","20-11=
-2024 15:05:23","Cascaded Incident from TTO3554960","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, site went down before gen start due to poor battery backup // Gen aut=
omatically started","system","2811","20-11-2024 15:02:10","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003631020","Nko=
lbisson","IHS_YND_763","20-11-2024 15:00:29","20-11-2024 14:15:19","20-11-2=
024 15:05:23","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen automatically started","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down before gen start due to poor battery backup // Gen a=
utomatically started","etienne.itondo@ihstowers.com","2711","20-11-2024 15:=
00:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003630987","M=
ontee-Jouvence-II","","20-11-2024 14:58:22","20-11-2024 14:04:00","20-11-20=
24 14:05:21","cascaded behing TTO3554905","Hyemafo Gildas","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active// No power Issue Site o=
n Grid Ubai =3D54,6V, The FME The TX FME Mbah Hosiah (674007438) is informe=
d.","ludivine.ngamaleu@ihstowers.com","17132","20-11-2024 14:58:22","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003630973","N=
kol-Mbanda","IHS_YND_518","20-11-2024 14:57:08","20-11-2024 14:04:00","20-1=
1-2024 19:05:21","Active// No power Issue Site on Grid Ubai =3D54,6V, The F=
ME The TX FME Mbah Hosiah (674007438) is informed.","MINKA NICOLAS","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power Issue Site on Grid Ubai =3D54,6V, The FME The TX FME=
 Mbah Hosiah (674007438) is informed.","ludivine.ngamaleu@ihstowers.com","3=
189","20-11-2024 14:57:08","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0003630972","Obo=
bogo","","20-11-2024 14:56:29","20-11-2024 14:54:21","20-11-2024 14:56:20",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","olivie=
r.kwedi@ihstowers.com","129","20-11-2024 14:56:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003630963","Scalom-I=
HS","","20-11-2024 14:54:30","20-11-2024 14:04:03","20-11-2024 14:05:14","C=
ascaded Incident from TTO3554804","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Active// No power Issue Site on Grid Ubai =3D54,6V, =
The FME The TX FME Mbah Hosiah (674007438) is informed.","system","273685",=
"20-11-2024 14:54:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0003630951","A=
ccacia New","IHS_YND_505","20-11-2024 14:53:11","20-11-2024 14:04:03","20-1=
1-2024 16:25:14","Active// No power Issue Site on Grid Ubai =3D54,6V, The F=
ME The TX FME Mbah Hosiah (674007438) is informed.","","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
 No power Issue Site on Grid Ubai =3D54,6V, The FME The TX FME Mbah Hosiah =
(674007438) is informed.","ludivine.ngamaleu@ihstowers.com","2949","20-11-2=
024 14:53:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0003630312","N=
R-Omnisport","","20-11-2024 13:32:54","20-11-2024 13:25:47","20-11-2024 14:=
07:56","Grid outage .gen failed to start due to alarm ""underfrequency""//w=
e reset card GE and gen manually started ","Delor Telezing","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage .gen failed to=
 start due to alarm ""underfrequency""//we reset card GE and gen manually s=
tarted ","ludivine.ngamaleu@ihstowers.com","428","20-11-2024 13:32:54","Sag=
emcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0003630248","N=
dogbessol","","20-11-2024 13:24:23","20-11-2024 13:05:17","20-11-2024 13:35=
:22","No power issue on site U=3D52,4v hybrid gen site Tx fme Etienne of hu=
awei is informed","Kemeni Franklin","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D=
52,4v hybrid gen site Tx fme Etienne of huawei is informed","ludivine.ngama=
leu@ihstowers.com","1147","20-11-2024 13:24:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003629762","M=
ontee-Des-Soeurs","","20-11-2024 12:37:37","20-11-2024 12:35:30","20-11-202=
4 13:05:31","Active// No power Issue Site on Grid Ubai =3D54,6V, The FME  T=
he TX FME Mbah Hosiah (674007438) is informed. Repetitif issue","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active// No power Issue Site on Grid Ubai =3D54,6V, The F=
ME  The TX FME Mbah Hosiah (674007438) is informed. Repetitif issue","ludiv=
ine.ngamaleu@ihstowers.com","127","20-11-2024 12:37:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0003629734","ARMP",""=
,"20-11-2024 12:30:41","20-11-2024 12:25:32","20-11-2024 12:28:32","Cascade=
d Incident from TTO3553488","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down before gen start due to poo=
r battery backup // Gen automatically started","system","265003","20-11-202=
4 12:30:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0003629733","Bastos B=
ir","","20-11-2024 12:30:40","20-11-2024 12:25:32","20-11-2024 12:28:32","C=
ascaded Incident from TTO3553488","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before g=
en start due to poor battery backup // Gen automatically started","system",=
"265003","20-11-2024 12:30:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003629727","D=
ragage","IHS_YND_704, IHS_YND_208","20-11-2024 12:29:40","20-11-2024 12:25:=
32","20-11-2024 12:28:32","Grid outage, site went down before gen start due=
 to poor battery backup // Gen automatically started","Mboua Thierry","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 outage, site went down before gen start due to poor battery backup // Gen =
automatically started","ludivine.ngamaleu@ihstowers.com","249","20-11-2024 =
12:29:40","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_255","NOCINC0003629655","Odza-PK10"=
,"","20-11-2024 12:17:57","","","Site alarming because Grid outage // Gen a=
utomatically started and alarm cleraed","Albran Byorel","Warning","Warning"=
,"POWER","Warning - Site on Battery","Site alarming because Grid outage // =
Gen automatically started and alarm cleraed","olivier.kwedi@ihstowers.com",=
"3","20-11-2024 12:17:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003629512","B=
riqueterie","","20-11-2024 12:04:57","20-11-2024 11:55:49","20-11-2024 13:2=
6:04","No power issue on site u=3D54v site on grid Rm Alain of huawei is in=
formed","","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","No power issue on site u=3D54v site on grid Rm Alain=
 of huawei is informed","ludivine.ngamaleu@ihstowers.com","550","20-11-2024=
 12:04:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003628909","M=
imboman-Ecole","","20-11-2024 10:53:38","20-11-2024 10:50:31","20-11-2024 1=
0:55:31","Grid outage, site went down before gen start due to poor battery =
backup // Gen automatically started","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site =
went down before gen start due to poor battery backup // Gen automatically =
started","ludivine.ngamaleu@ihstowers.com","188","20-11-2024 10:53:38","Sag=
emcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003628771","Feb=
e Village","IHS_YND_804","20-11-2024 10:36:28","20-11-2024 10:29:03","20-11=
-2024 12:39:00","No power issue on site U=3D54,5v site on grid Tx fme Moham=
adou of huawei is informed","Mboua Thierry","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D54,5v site on grid Tx fme Mohamadou of huawei is informed","olivier=
.kwedi@ihstowers.com","446","20-11-2024 10:36:28","Sagemcom CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0003628747","BEA=
TITUDE ENTR=C9E PAVE","","20-11-2024 10:32:29","20-11-2024 10:29:03","20-11=
-2024 10:36:59","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site U=3D54,5v site on gr=
id Tx fme Mohamadou of huawei is informed","olivier.kwedi@ihstowers.com","1=
173","20-11-2024 10:32:29","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003628466","Pha=
rmacie SION","","20-11-2024 09:46:13","20-11-2024 09:40:05","20-11-2024 09:=
50:05","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen automatically started","Paul BIBOUM","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen automatically started=
","olivier.kwedi@ihstowers.com","369","20-11-2024 09:46:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003628419","A=
fanoya","","20-11-2024 09:37:02","20-11-2024 09:30:52","20-11-2024 10:38:27=
","No power issue on site , Ubaie=3D54.6V site On Grid The Tx FME Georges 6=
97461814 from Huawei is informed,r=E9p=E9titif issue","Hyemafo Gildas","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue on site , Ubaie=3D54.6V site On Grid The Tx FME Geor=
ges 697461814 from Huawei is informed,r=E9p=E9titif issue","ludivine.ngamal=
eu@ihstowers.com","371","20-11-2024 09:37:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003628357","Ngoum","=
","20-11-2024 09:24:41","20-11-2024 08:55:20","20-11-2024 09:31:52","Cascad=
ed Incident from TTO3551911","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","grid outage,gen ran till fuel shortage//r=
efueling done","system","1761","20-11-2024 09:24:41","Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0003628263","Yok=
o MTN","IHS_YND_475","20-11-2024 09:00:38","20-11-2024 08:55:20","20-11-202=
4 09:31:52","grid outage,gen ran till fuel shortage//refueling done","Parke=
r Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen=
 ran till fuel shortage//refueling done","olivier.kwedi@ihstowers.com","322=
","20-11-2024 09:00:38","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0003628166","ETO=
UDI Entree du palais","","20-11-2024 08:54:03","20-11-2024 08:52:57","20-11=
-2024 09:24:43","grid outage,gen ran till fuel shortage//refueling done, po=
wer issue resolved since 09:24 Am but the site remaind down after power res=
et done Tx Fme Armand 671716363 of huawei is informed","Fabrice Pouakam","F=
uel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran till fu=
el shortage//refueling done, power issue resolved since 09:24 Am but the si=
te remaind down after power reset done Tx Fme Armand 671716363 of huawei is=
 informed","olivier.kwedi@ihstowers.com","67","20-11-2024 08:54:03","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0003627995","Omnispor=
t-Rail","","20-11-2024 08:15:10","20-11-2024 08:09:24","20-11-2024 09:00:24=
","Cascaded Incident from TTO3551602","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage//MDG 13 kva deploye=
d","system","346","20-11-2024 08:15:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0003627987","H=
-Paradis","IHS_YND_506","20-11-2024 08:14:33","20-11-2024 08:09:24","20-11-=
2024 09:19:24","grid outage//MDG 13 kva deployed","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","grid outage//MDG 13 kva deplo=
yed","ludivine.ngamaleu@ihstowers.com","309","20-11-2024 08:14:33","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0003627855","Mfou EPC=
","","20-11-2024 07:40:40","20-11-2024 07:34:30","20-11-2024 10:22:00","Cas=
caded Incident from TTO3551437","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down du=
e to lack of 02 phase on site // he did a brid with a good phase, site on g=
en","system","289559","20-11-2024 07:40:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0003627852","M=
fou OCM","IHS_YND_674","20-11-2024 07:39:37","20-11-2024 07:34:30","20-11-2=
024 10:22:00","Grid fluctuation, site went down due to lack of 02 phase on =
site // he did a brid with a good phase, site on gen","Mba Lazare Herve","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d fluctuation, site went down due to lack of 02 phase on site // he did a b=
rid with a good phase, site on gen","ludivine.ngamaleu@ihstowers.com","307"=
,"20-11-2024 07:39:37","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0003627787","Nko=
lafeme","","20-11-2024 07:24:57","20-11-2024 07:21:47","20-11-2024 08:48:11=
","No power issue on site U=3D54,5v site on grid Tx fme Mohamadou of huawei=
 is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 U=3D54,5v site on grid Tx fme Mohamadou of huawei is informed","olivier.kw=
edi@ihstowers.com","191","20-11-2024 07:24:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003627610","Nkolbiss=
on usines des eaux 2","","20-11-2024 06:52:30","20-11-2024 06:43:26","20-11=
-2024 07:06:41","Cascaded Incident from TTO3551162","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid ou=
tage, site went down before gen start due to poor battery backup // Gen aut=
omatically started","system","264109","20-11-2024 06:52:30","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003627607","Nko=
lbisson","IHS_YND_763","20-11-2024 06:51:34","20-11-2024 06:43:26","20-11-2=
024 07:06:41","Grid outage, site went down before gen start due to poor bat=
tery backup // Gen automatically started","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down before gen start due to poor battery backup // Gen a=
utomatically started","olivier.kwedi@ihstowers.com","489","20-11-2024 06:51=
:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003627562","B=
itoto","","20-11-2024 06:39:50","20-11-2024 06:34:45","20-11-2024 06:35:45"=
,"Active//No power issue, U=3D54V on grid Tx FME George/697461814/ From hua=
wei is informed and notice that disjunction at OCM Equipment","Mba Lazare H=
erve","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active//No power issue, U=3D54V on grid Tx FME George/697=
461814/ From huawei is informed and notice that disjunction at OCM Equipmen=
t","ludivine.ngamaleu@ihstowers.com","306","20-11-2024 06:39:50","Sagemcom =
CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0003627541","NKO=
LOSSAN OKOK","","20-11-2024 06:35:25","20-11-2024 06:26:19","20-11-2024 07:=
39:30","No power issue on site U=3D51v site on gen Tx Gregoire of huawei is=
 informed up at 06:39","Parker Tchoup","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D51v site on gen Tx Gregoire of huawei is informed up at 06:39","olivier.=
kwedi@ihstowers.com","547","20-11-2024 06:35:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003627465","M=
essa-Carriere OCM","","20-11-2024 06:29:03","20-11-2024 06:21:55","20-11-20=
24 12:55:44","grid outage,No space to deploy a mobil gen // grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid o=
utage,No space to deploy a mobil gen // grid return","ludivine.ngamaleu@ihs=
towers.com","429","20-11-2024 06:29:03","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0003626895","Ngo=
usso Vallee","","20-11-2024 03:07:03","20-11-2024 02:15:53","20-11-2024 04:=
22:24","Grid outage, site went down because Gen start and stoppen with alar=
m ""low oil pressure // He reset Gen card and Gen manually started","Siliga=
p Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage, site went down because Gen start and stoppen with alarm ""low oi=
l pressure // He reset Gen card and Gen manually started","landry.etame@ihs=
towers.com","3070","20-11-2024 03:07:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003625374","C=
RH-Etoug-Ebe","","19-11-2024 20:42:14","19-11-2024 20:34:10","19-11-2024 20=
:40:09","No power issue on site Ubaie:54.V; site on Grid.The Tx FME  Mohama=
dou/691 144 435/ from Huawei is informed","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site Ubaie:54.V; site on Grid.The Tx FME  Mohamadou/691 144 4=
35/ from Huawei is informed","emmanuel.ghani@ihstowers.com","485","19-11-20=
24 20:42:14","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003625313","Mes=
sa Carriere","","19-11-2024 20:32:11","19-11-2024 20:26:04","19-11-2024 21:=
15:23","site went down because the Cb(40A) of Gen dysjoncted due to short c=
ircuit // he reamed the Cb","Mboua Thierry","Equipment Repair","Passive","A=
CDG Gen","ACDG - Load Breaker","site went down because the Cb(40A) of Gen d=
ysjoncted due to short circuit // he reamed the Cb","christian.fonkou@ihsto=
wers.com","368","19-11-2024 20:32:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003625187","C=
rf-Nsam","","19-11-2024 20:11:27","19-11-2024 20:04:24","19-11-2024 20:11:5=
4","Site went down due PWC Dysfunssionning on site // he Reset it and Site =
is on Grid ","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rect=
ifier Module Overloaded","Site went down due PWC Dysfunssionning on site //=
 he Reset it and Site is on Grid ","emmanuel.ghani@ihstowers.com","424","19=
-11-2024 20:11:27","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003624282","Nko=
lbisson","","19-11-2024 18:18:06","19-11-2024 18:12:56","19-11-2024 18:22:5=
6","Grid outage, site went down before gen start due to poor battery backup=
 // Gen automatically started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen automaticall=
y started","christian.fonkou@ihstowers.com","311","19-11-2024 18:18:06","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003623948","Pha=
rmacie SION","","19-11-2024 17:26:23","19-11-2024 17:23:14","19-11-2024 17:=
34:34","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automatically","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automatically","c=
hristian.fonkou@ihstowers.com","190","19-11-2024 17:26:23","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003623870","MIM=
BOMAN LIBERTE","","19-11-2024 17:19:34","19-11-2024 17:10:28","19-11-2024 1=
8:04:43","Grid Outage ;site went down because Main Gen faulty // MDG 20 Kva=
 has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid Outage ;site went down because Main Gen faul=
ty // MDG 20 Kva has deployed","christian.fonkou@ihstowers.com","547","19-1=
1-2024 17:19:34","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003623813","N=
yanon","","19-11-2024 17:13:38","19-11-2024 17:05:33","19-11-2024 18:19:29"=
,"Hybrid Gen Site: site went down because of the dysfunctioning of hybrid s=
ystem // He reset Gen card and started   Gen","TIENTCHEU NZETCHIEU GAEL","E=
quipment Repair","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: site =
went down because of the dysfunctioning of hybrid system // He reset Gen ca=
rd and started   Gen","emmanuel.ghani@ihstowers.com","487","19-11-2024 17:1=
3:38","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_709","NOCINC0003623694","Nkolo II N=
ew","","19-11-2024 17:00:11","","","Grid fluctuation Site alarming because =
site on battery due to Grid bad voltage// Gen started manualy","Mba Lazare =
Herve","Warning","Warning","POWER","Warning - Site on Battery","Grid fluctu=
ation Site alarming because site on battery due to Grid bad voltage// Gen s=
tarted manualy","joelle.ekessi@ihstowers.com","3","19-11-2024 17:00:11","Sa=
gemcom CMR"
"Closed Complete","Warning","","IHS_YND_365","NOCINC0003622966","Akono","",=
"19-11-2024 16:31:55","","","Site alarming because site on battery  Alex (6=
57108612)/ From Sagemcom is working on site (PM) // End of work","Fanda Bri=
ce","Warning","Warning","POWER","Warning - Site on Battery","Site alarming =
because site on battery  Alex (657108612)/ From Sagemcom is working on site=
 (PM) // End of work","joelle.ekessi@ihstowers.com","2","19-11-2024 16:31:5=
5","Sagemcom CMR"
"Closed Complete","Site Down","T0210","IHS_YND_206","NOCINC0003622953","ARM=
P","","19-11-2024 16:29:57","19-11-2024 16:19:52","19-11-2024 21:20:53","",=
"Mboua Thierry","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","No power issue on site ubaie=3D54v site on grid=
 eloundou is informed","christian.fonkou@ihstowers.com","606","19-11-2024 1=
6:29:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003622827","M=
fou EPC","","19-11-2024 16:17:03","19-11-2024 16:07:00","20-11-2024 00:15:4=
8","fme is on the way to site ETA=3D17:30","Mba Lazare Herve","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site ubaie=3D54v site on grid , Georges(Huawei) is on site=
","emmanuel.ghani@ihstowers.com","604","19-11-2024 16:17:03","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003622800","Nko=
g-Edzen","","19-11-2024 16:10:04","19-11-2024 16:05:58","19-11-2024 19:50:0=
3","No power issue on site with  Ubaie=3D52.4V site on Gen (start threshold=
 ubai=3D50 V) The Tx Fme Gregoire( 652070658)from Huawei is informed","Park=
er Tchoup","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","No power issue on site with  Ubaie=3D52.4V site on G=
en (start threshold ubai=3D50 V) The Tx Fme Gregoire( 652070658)from Huawei=
 is informed","christian.fonkou@ihstowers.com","247","19-11-2024 16:10:04",=
"Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_434","NOCINC0003622306","Donga","",=
"19-11-2024 15:14:56","","","Hybrid Gen Site, Site alarming because site on=
 battery due to Gen stopped//Dg  started automatically at  threshold=3D48.4=
 V.","Parker Tchoup","Warning","Warning","POWER","Warning - Site on Battery=
","Hybrid Gen Site, Site alarming because site on battery due to Gen stoppe=
d//Dg  started automatically at  threshold=3D48.4 V.","joelle.ekessi@ihstow=
ers.com","2","19-11-2024 15:14:56","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0003621402","MVA=
N SACEL","","19-11-2024 13:36:25","19-11-2024 12:38:01","19-11-2024 12:44:1=
0","Grid outage, site went down before gen start due to poor battery backup=
 // Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // Gen start automatically","rou=
selle.schoune@ihstowers.com","3505","19-11-2024 13:36:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003621060","M=
IMBOMAN LIBERTE","","19-11-2024 12:54:44","19-11-2024 12:44:32","19-11-2024=
 13:13:26","grid outage,main gen  faulty//grid return","Mba Lazare Herve","=
Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","grid outa=
ge,main gen  faulty//grid return","denis.mballa@ihstowers.com","613","19-11=
-2024 12:54:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003620668","B=
riqueterie","","19-11-2024 11:57:45","19-11-2024 11:48:30","19-11-2024 12:1=
9:55","grid outage,no space to deploy a mobil gen//grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no =
space to deploy a mobil gen//grid return","denis.mballa@ihstowers.com","556=
","19-11-2024 11:57:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003620654","Akak-Nko=
zoa-MTN-IHS","","19-11-2024 11:55:20","19-11-2024 11:54:21","19-11-2024 11:=
55:54","Cascaded Incident from TTO3543278","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo outage, site down be=
fore DG started due to poor backup  //  DG started automatically","system",=
"295860","19-11-2024 11:55:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003620306","B=
riqueterie","","19-11-2024 11:00:26","19-11-2024 10:52:15","19-11-2024 11:1=
9:41","grid outage, no space to dploy a mobil gen// grid return ","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, =
no space to dploy a mobil gen// grid return ","denis.mballa@ihstowers.com",=
"493","19-11-2024 11:00:26","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0003620299","Bri=
quetterie","","19-11-2024 10:59:09","19-11-2024 10:55:05","19-11-2024 11:21=
:01","grid outage, no space to dploy a mobil gen// grid return ","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, n=
o space to dploy a mobil gen// grid return ","rouselle.schoune@ihstowers.co=
m","245","19-11-2024 10:59:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_422","NOCINC0003619067","Botmakak=
","","19-11-2024 08:13:11","19-11-2024 08:01:00","19-11-2024 08:06:14","Cas=
caded Incident from TTO3541437","Kemeni Franklin","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site.Site on grid wit=
h Ubaie=3D53.1 V  The TX FME Etienne(695033981) from Huawei is   informed."=
,"system","266615","19-11-2024 08:13:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0003619053","Ngoung",=
"","19-11-2024 08:09:01","19-11-2024 08:01:00","19-11-2024 08:06:14","Casca=
ded Incident from TTO3541437","Kemeni Franklin","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site.Site on grid with =
Ubaie=3D53.1 V  The TX FME Etienne(695033981) from Huawei is   informed.","=
system","266615","19-11-2024 08:09:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_373","NOCINC0003619052","Maloun",=
"","19-11-2024 08:09:01","19-11-2024 08:01:00","19-11-2024 08:06:14","Casca=
ded Incident from TTO3541437","Kemeni Franklin","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site.Site on grid with =
Ubaie=3D53.1 V  The TX FME Etienne(695033981) from Huawei is   informed.","=
system","481","19-11-2024 08:09:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0003619046","M=
atomb","IHS_YND_373, IHS_YND_375, IHS_YND_422","19-11-2024 08:07:30","19-11=
-2024 08:01:00","19-11-2024 08:06:14","No power issue on site.Site on grid =
with Ubaie=3D53.1 V  The TX FME Etienne(695033981) from Huawei is   informe=
d.","Kemeni Franklin","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power issue on site.Site on grid with =
Ubaie=3D53.1 V  The TX FME Etienne(695033981) from Huawei is   informed.","=
denis.mballa@ihstowers.com","391","19-11-2024 08:07:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003618855","Yoko MTN=
","","19-11-2024 07:48:31","19-11-2024 07:36:26","19-11-2024 07:39:26","Cas=
caded Incident from TTO3541193","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site.Site on battery wi=
th Ubaie=3D49.1 V  The TX FME GREGOIRE(654547479) from Huawei is   informed=
. Site up at 07:39","system","268101","19-11-2024 07:48:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003618854","Dong",""=
,"19-11-2024 07:48:31","19-11-2024 07:36:26","19-11-2024 07:39:26","Cascade=
d Incident from TTO3541193","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site.Site on battery with U=
baie=3D49.1 V  The TX FME GREGOIRE(654547479) from Huawei is   informed. Si=
te up at 07:39","system","268101","19-11-2024 07:48:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003618851","Matsari"=
,"","19-11-2024 07:48:30","19-11-2024 07:36:26","19-11-2024 07:39:26","Casc=
aded Incident from TTO3541193","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site.Site on battery wit=
h Ubaie=3D49.1 V  The TX FME GREGOIRE(654547479) from Huawei is   informed.=
 Site up at 07:39","system","268099","19-11-2024 07:48:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003618852","Ngoum","=
","19-11-2024 07:48:30","19-11-2024 07:36:26","19-11-2024 07:39:26","Cascad=
ed Incident from TTO3541193","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site.Site on battery with =
Ubaie=3D49.1 V  The TX FME GREGOIRE(654547479) from Huawei is   informed. S=
ite up at 07:39","system","268100","19-11-2024 07:48:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003618853","Ngouetou=
","","19-11-2024 07:48:30","19-11-2024 07:36:26","19-11-2024 07:39:26","Cas=
caded Incident from TTO3541193","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site.Site on battery wi=
th Ubaie=3D49.1 V  The TX FME GREGOIRE(654547479) from Huawei is   informed=
. Site up at 07:39","system","268100","19-11-2024 07:48:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003618849","Nguila",=
"","19-11-2024 07:48:30","19-11-2024 07:36:26","19-11-2024 07:39:26","Casca=
ded Incident from TTO3541193","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site.Site on battery with=
 Ubaie=3D49.1 V  The TX FME GREGOIRE(654547479) from Huawei is   informed. =
Site up at 07:39","system","268101","19-11-2024 07:48:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003618850","MBIMBIM"=
,"","19-11-2024 07:48:30","19-11-2024 07:36:26","19-11-2024 07:39:26","Casc=
aded Incident from TTO3541193","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site.Site on battery wit=
h Ubaie=3D49.1 V  The TX FME GREGOIRE(654547479) from Huawei is   informed.=
 Site up at 07:39","system","724","19-11-2024 07:48:30","Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0003618822","Don=
ga","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_Y=
ND_444, IHS_YND_473","19-11-2024 07:39:35","19-11-2024 07:36:26","19-11-202=
4 07:59:26","No power issue on site.Site on battery with Ubaie=3D49.1 V  Th=
e TX FME GREGOIRE(654547479) from Huawei is   informed. Site up at 07:39","=
Parker Tchoup","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","No power issue on site.Site on battery with Ubai=
e=3D49.1 V  The TX FME GREGOIRE(654547479) from Huawei is   informed. Site =
up at 07:39","rouselle.schoune@ihstowers.com","190","19-11-2024 07:39:35","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003618359","A=
fanoya","","19-11-2024 06:34:20","19-11-2024 06:21:08","19-11-2024 06:56:21=
","No power issue on site , Ubaie=3D54.4V site On GridThe Tx FME Georges 69=
7461814 from Huawei is informed. R=E9petitif issue","Hyemafo Gildas","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site , Ubaie=3D54.4V site On GridThe Tx FME Georges=
 697461814 from Huawei is informed. R=E9petitif issue","denis.mballa@ihstow=
ers.com","793","19-11-2024 06:34:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003618108","N=
kolfon Cimencam","","19-11-2024 05:36:52","19-11-2024 05:21:45","19-11-2024=
 05:26:08","No power issue on site U=3D54,5v site on Gen The TX fme George(=
697461814) from huawei is informed. Noticed that site is impacted by Afanoy=
a","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,5v site on Ge=
n The TX fme George(697461814) from huawei is informed. Noticed that site i=
s impacted by Afanoya","alexandre.kamal@ihstowers.com","908","19-11-2024 05=
:36:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_311","IHS_YND_453","NOCINC0003618095","S=
ong-bong","","19-11-2024 05:35:02","19-11-2024 05:32:57","19-11-2024 11:29:=
54","Solar-Gen,Site went down due to ligthning,Circuit Breaker ACDG Gen was=
 down,ACDG Gen control panel alarmin","Kemeni Franklin","Force Majeure","Na=
tural Disaster","Thunderstrike","Equipment Damaged","Solar-Gen,Site went do=
wn due to lightning,Circuit Breaker ACDG Gen was down,ACDG Gen control pane=
l alarming(Digital input B),Battery Gen was discharged //Circuit Breaker pu=
t back on,Reset control panel and started DG.","alexandre.kamal@ihstowers.c=
om","126","19-11-2024 05:35:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003617900","Yoko MTN=
","","19-11-2024 04:30:11","19-11-2024 04:25:38","19-11-2024 04:30:30","Cas=
caded Incident from TTO3540116","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site ,site on G=
EN  wiith Ubaie=3D53 V The TX FME Gregoire/ 654547479/  Huawei is informed =
and Up at 04:27 AM","system","272090","19-11-2024 04:30:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003617898","MBIMBIM"=
,"","19-11-2024 04:30:10","19-11-2024 04:25:38","19-11-2024 04:30:30","Casc=
aded Incident from TTO3540116","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue on site ,site on GE=
N  wiith Ubaie=3D53 V The TX FME Gregoire/ 654547479/  Huawei is informed a=
nd Up at 04:27 AM","system","272090","19-11-2024 04:30:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003617899","Matsari"=
,"","19-11-2024 04:30:10","19-11-2024 04:25:38","19-11-2024 04:30:30","Casc=
aded Incident from TTO3540116","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue on site ,site on GE=
N  wiith Ubaie=3D53 V The TX FME Gregoire/ 654547479/  Huawei is informed a=
nd Up at 04:27 AM","system","272090","19-11-2024 04:30:10","Sagemcom CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0003617893","Ngo=
um","IHS_YND_456, IHS_YND_460, IHS_YND_473","19-11-2024 04:26:55","19-11-20=
24 04:25:38","19-11-2024 04:30:30","Active//No power issue on site ,site on=
 GEN  wiith Ubaie=3D53 V The TX FME Gregoire/ 654547479/  Huawei is informe=
d and Up at 04:27 AM","Parker Tchoup","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on=
 site ,site on GEN  wiith Ubaie=3D53 V The TX FME Gregoire/ 654547479/  Hua=
wei is informed and Up at 04:27 AM","kamga.virgile@ihstowers.com","79","19-=
11-2024 04:26:55","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0003616870","Men=
dong NB","","18-11-2024 22:55:59","18-11-2024 21:16:49","18-11-2024 22:46:5=
2","Grid outage, No space to to deploy MDG// Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space=
 to to deploy MDG// Grid return","kamga.virgile@ihstowers.com","5951","18-1=
1-2024 22:55:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003616724","A=
fanoya","","18-11-2024 22:18:53","18-11-2024 22:05:49","18-11-2024 22:10:24=
","Active// NO power issue, Site on Grid Ubaie=3D54.6V The Tx FME Georges 6=
97461814 from Huawei is informed. R=E9petitif issue","Hyemafo Gildas","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// NO power issue, Site on Grid Ubaie=3D54.6V The Tx FME Georg=
es 697461814 from Huawei is informed. R=E9petitif issue","alexandre.kamal@i=
hstowers.com","785","18-11-2024 22:18:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0003616652","B=
otmakak","","18-11-2024 22:00:25","18-11-2024 21:47:11","18-11-2024 21:55:1=
0","Active// No power issue, Site on Grid Ubai=3D 53.8V, The Tx Etienne/695=
033981/From Huawei is informed","Kemeni Franklin","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No p=
ower issue, Site on Grid Ubai=3D 53.8V, The Tx Etienne/695033981/From Huawe=
i is informed","stephane.nkamwa@ihstowers.com","795","18-11-2024 22:00:25",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003616567","M=
elen Ba'aba","","18-11-2024 21:41:49","18-11-2024 21:14:44","18-11-2024 22:=
36:08","Grid outage, Site went down because started and stopped due to high=
 Temp// He added water and started Gen manualy","Siligap Boris","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","Grid outage, Site went down because started and stopped due to high Temp=
// He added water and started Gen manualy","stephane.nkamwa@ihstowers.com",=
"1626","18-11-2024 21:41:49","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003616562","Mes=
sa Carriere","","18-11-2024 21:41:05","18-11-2024 21:31:58","18-11-2024 22:=
21:15","Grid fluctuation, site went down because started and stopped due to=
 Grid bad voltage no rcp on site// He bypassed Grid and started Gen manualy=
","Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation, site went down because started and stopp=
ed due to Grid bad voltage no rcp on site// He bypassed Grid and started Ge=
n manualy","landry.etame@ihstowers.com","548","18-11-2024 21:41:05","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003616495","Dong",""=
,"18-11-2024 21:26:31","18-11-2024 21:09:57","18-11-2024 21:10:58","Cascade=
d Incident from TTO3538349","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue on site ,Hybrid Gen si=
te, site on Battery with Ubaie=3D48.3V  Notice that site impacted by MBAJOC=
K CAMRAIL (Not managing by HIS)","system","262504","18-11-2024 21:26:31","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003616494","Donga","=
","18-11-2024 21:26:31","18-11-2024 21:09:57","18-11-2024 21:10:58","Cascad=
ed Incident from TTO3538349","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue on site ,Hybrid Gen s=
ite, site on Battery with Ubaie=3D48.3V  Notice that site impacted by MBAJO=
CK CAMRAIL (Not managing by HIS)","system","262505","18-11-2024 21:26:31","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0003616452","N=
guila","IHS_YND_592, IHS_YND_431, IHS_YND_443, IHS_YND_432, IHS_YND_434, IH=
S_YND_444, IHS_YND_402, IHS_YND_442","18-11-2024 21:20:02","18-11-2024 21:0=
9:57","18-11-2024 21:21:45","Active//No power issue on site ,Hybrid Gen sit=
e, site on Battery with Ubaie=3D48.3V  Notice that site impacted by MBAJOCK=
 CAMRAIL (Not managing by HIS)","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue on site ,Hybrid Gen site, site on Battery with Ubaie=3D48.3V  Notic=
e that site impacted by MBAJOCK CAMRAIL (Not managing by HIS)","stephane.nk=
amwa@ihstowers.com","606","18-11-2024 21:20:02","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0003616108","Men=
dong NB","","18-11-2024 20:13:59","18-11-2024 20:03:27","18-11-2024 20:36:0=
9","Site went down due to CB (63 A) Disjunted in the DC-BOX //He reamed the=
 CB (63A) and Site is on GRID","","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","Site went down due to CB (63 A=
) Disjunted in the DC-BOX //He reamed the CB (63A) and Site is on GRID","la=
ndry.etame@ihstowers.com","634","18-11-2024 20:13:59","Sagemcom CMR"
"Closed Complete","Warning","CTR_526","IHS_YND_696","NOCINC0003616000","Bar=
riere IHS","","18-11-2024 19:57:33","","","Site went on Battery due to GRID=
 outage //Gen Manually Stated ( deep ivestiguestion ongoing)","Hyemafo Gild=
as","Warning","Warning","POWER","Warning - Site on Battery","Site went on B=
attery due to GRID outage //Gen Manually Stated ( deep ivestiguestion ongoi=
ng)","nadjia.njaya@ihstowers.com","427","18-11-2024 19:57:33","Sagemcom CMR=
"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0003615953","Mfo=
u EPC","","18-11-2024 19:48:01","18-11-2024 19:45:42","18-11-2024 19:46:42"=
,"Active//No power issue on site, Site on Grid UBAIE=3D51.4V and Geoges (69=
7461814) From huawei is informed and Site Up AT=3D07:49 PM","Mba Lazare Her=
ve","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue on site, Site on Grid UBAIE=3D51.4V =
and Geoges (697461814) From huawei is informed and Site Up AT=3D07:49 PM","=
landry.etame@ihstowers.com","141","18-11-2024 19:48:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0003615716","Minka","=
","18-11-2024 19:04:30","18-11-2024 18:53:28","18-11-2024 19:33:29","Cascad=
ed Incident from TTO3537436","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, Site went down because Gen ran=
 until fuel shortage// Refueling ongoing","system","662","18-11-2024 19:04:=
30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0003615719","Bondjock=
","","18-11-2024 19:04:30","18-11-2024 18:53:28","18-11-2024 19:33:29","Cas=
caded Incident from TTO3537436","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, Site went down because Gen =
ran until fuel shortage// Refueling ongoing","system","662","18-11-2024 19:=
04:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0003615717","OKOA Pea=
ge","","18-11-2024 19:04:30","18-11-2024 18:53:28","18-11-2024 19:33:29","C=
ascaded Incident from TTO3537436","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down because Ge=
n ran until fuel shortage// Refueling ongoing","system","270559","18-11-202=
4 19:04:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0003615683","M=
om","IHS_YND_371, IHS_YND_330, IHS_YND_553, IHS_YND_372","18-11-2024 19:00:=
47","18-11-2024 18:53:28","18-11-2024 19:33:29","Grid outage, Site went dow=
n because Gen ran until fuel shortage// Refueling ongoing","Fanda Brice","F=
uel Outage","Passive","Diesel","Diesel Outage","Grid outage, Site went down=
 because Gen ran until fuel shortage// Refueling ongoing","stephane.nkamwa@=
ihstowers.com","440","18-11-2024 19:00:47","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003615625","NTU=
I TOWN","","18-11-2024 18:50:10","18-11-2024 18:42:03","18-11-2024 19:45:45=
","Grid outage, Site went down because Gen started and stopped due to high =
temp causing by pastille pierced// Grid restored (reparation pastille ongoi=
ng)","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","Grid outage, Site went down because Gen =
started and stopped due to high temp causing by pastille pierced// Grid res=
tored (reparation pastille ongoing)","landry.etame@ihstowers.com","488","18=
-11-2024 18:50:10","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003615618","Mok=
olo Yaounde","","18-11-2024 18:48:50","18-11-2024 18:40:46","18-11-2024 18:=
51:16","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spa=
ce to deploy a MDG//Grid Restored","landry.etame@ihstowers.com","485","18-1=
1-2024 18:48:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003614294","A=
fanoya","","18-11-2024 15:07:55","18-11-2024 14:55:42","18-11-2024 17:25:23=
","Active//No power issue on site , Ubaie=3D54.6V site On Grid The Tx FME G=
eorges 697461814 from Huawei is informed.","Hyemafo Gildas","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue on site , Ubaie=3D54.6V site On Grid The Tx FME Georges=
 697461814 from Huawei is informed.","stephane.nkamwa@ihstowers.com","762",=
"18-11-2024 15:07:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003614272","F=
ebe Village","","18-11-2024 15:02:30","18-11-2024 14:50:23","18-11-2024 15:=
04:32","Grid outage, site went down before gen start due to poor battery ba=
ckup // Grid restored","Mboua Thierry","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
gen start due to poor battery backup // Grid restored","stephane.nkamwa@ihs=
towers.com","728","18-11-2024 15:02:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0003614054","SAA 2","=
","18-11-2024 14:35:20","18-11-2024 14:09:43","18-11-2024 14:46:23","Cascad=
ed Incident from TTO3535471","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage Site went down because gen st=
arted and stopped due to charging alternator faulty // He changed charging =
alternator faulty","system","309122","18-11-2024 14:35:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003614034","S=
aa","IHS_YND_401, IHS_YND_404","18-11-2024 14:33:54","18-11-2024 14:09:43",=
"18-11-2024 14:46:23","Grid outage Site went down because gen started and s=
topped due to charging alternator faulty // He changed charging alternator =
faulty","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Cha=
rging Alternator","Grid outage Site went down because gen started and stopp=
ed due to charging alternator faulty // He changed charging alternator faul=
ty","stephane.nkamwa@ihstowers.com","1452","18-11-2024 14:33:54","Sagemcom =
CMR"
"Closed Complete","Site Down","T5040","IHS_YND_810","NOCINC0003614028","Car=
refour Ayissi Ele","","18-11-2024 14:33:21","18-11-2024 14:02:17","18-11-20=
24 14:04:25","Active//No power issue on site ,site on Solar with Ubaie=3D 5=
2.9V The Tx FME Gregroire /652070658/From HUAWEI is informed","Parker Tchou=
p","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power issue on site ,site on Solar with Ubaie=3D =
52.9V The Tx FME Gregroire /652070658/From HUAWEI is informed","landry.etam=
e@ihstowers.com","1865","18-11-2024 14:33:21","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003613830","NTU=
I TOWN","","18-11-2024 13:59:22","18-11-2024 13:54:14","18-11-2024 14:07:03=
","Grid Outage Site went down because Gen failed to start due to piercing p=
ellet on the Gen and the low water level in the Gen //Grid Restored","Parke=
r Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue","Grid Outage Site went down because Gen failed to st=
art due to piercing pellet on the Gen and the low water level in the Gen //=
Grid Restored","christian.fonkou@ihstowers.com","309","18-11-2024 13:59:22"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003613568","Eseka To=
wn","","18-11-2024 13:30:52","18-11-2024 13:21:29","18-11-2024 13:27:38","C=
ascaded Incident from TTO3534829","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","(site impacted by SOMBO) Grid outa=
ge, site went down before gen start due to poor battery backup // Gen start=
 automatically","system","261763","18-11-2024 13:30:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0003613566","Eseka MT=
N","","18-11-2024 13:30:52","18-11-2024 13:21:29","18-11-2024 13:27:38","Ca=
scaded Incident from TTO3534829","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","(site impacted by SOMBO) Grid outag=
e, site went down before gen start due to poor battery backup // Gen start =
automatically","system","261763","18-11-2024 13:30:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003613563","Ndogbess=
ol","","18-11-2024 13:30:51","18-11-2024 13:21:29","18-11-2024 13:27:38","C=
ascaded Incident from TTO3534829","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","(site impacted by SOMBO) Grid outa=
ge, site went down before gen start due to poor battery backup // Gen start=
 automatically","system","261759","18-11-2024 13:30:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_781","NOCINC0003613559","BIBOMDJI=
DJIEL","","18-11-2024 13:30:50","18-11-2024 13:21:29","18-11-2024 13:27:38"=
,"Cascaded Incident from TTO3534829","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","(site impacted by SOMBO) Grid o=
utage, site went down before gen start due to poor battery backup // Gen st=
art automatically","system","261761","18-11-2024 13:30:50","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003613451","Nko=
lbisson","","18-11-2024 13:25:09","18-11-2024 13:19:02","18-11-2024 13:26:2=
8","Grid fluctuation, site went down because Gen start and stopped due to G=
rid bad voltage // Gen manually started","TIENTCHEU NZETCHIEU GAEL","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid flu=
ctuation, site went down because Gen start and stopped due to Grid bad volt=
age // Gen manually started","christian.fonkou@ihstowers.com","368","18-11-=
2024 13:25:09","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003612969","BIY=
EMASSI NIKI","","18-11-2024 12:31:18","18-11-2024 12:25:10","18-11-2024 13:=
01:19","Site went down due to PWC overloaded (12kva 250 A)//Site stabilized=
.","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Site went down due to PWC overloaded//Site stabilized.","c=
hristian.fonkou@ihstowers.com","369","18-11-2024 12:31:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0003612815","M=
beng","","18-11-2024 12:09:44","18-11-2024 12:00:41","18-11-2024 12:18:01",=
"Grid outage, Site went down because Gen started and stopped with ""high te=
mp"" alarm// He added water and started Gen manualy","Fanda Brice","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Is=
sue","Grid outage, Site went down because Gen started and stopped with ""hi=
gh temp"" alarm// He added water and started Gen manualy","emmanuel.ghani@i=
hstowers.com","544","18-11-2024 12:09:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_513","NOCINC0003612686","Maison-B=
lanche-IHS","","18-11-2024 11:51:11","18-11-2024 11:26:23","18-11-2024 11:2=
9:51","Cascaded Incident from TTO3533959","","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue sie on grid with U=3D54v Noti=
ce that site is impacted by Nkolzie who is not our responsbality","system",=
"1218079","18-11-2024 11:51:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003612684","Scalom-I=
HS","","18-11-2024 11:51:11","18-11-2024 11:26:23","18-11-2024 11:29:51","C=
ascaded Incident from TTO3533959","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","No power issue sie on grid with U=3D54v Notice that =
site is impacted by Nkolzie who is not our responsbality","system","268546"=
,"18-11-2024 11:51:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_150","NOCINC0003612683","Nkol-Mba=
nda","","18-11-2024 11:51:11","18-11-2024 11:26:23","18-11-2024 11:29:51","=
Cascaded Incident from TTO3533959","MINKA NICOLAS","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue sie on grid with U=3D54=
v Notice that site is impacted by Nkolzie who is not our responsbality","sy=
stem","1218077","18-11-2024 11:51:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0003612685","Montee-J=
ouvence-II","","18-11-2024 11:51:11","18-11-2024 11:26:23","18-11-2024 11:2=
9:51","Cascaded Incident from TTO3533959","Hyemafo Gildas","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue sie on grid wit=
h U=3D54v Notice that site is impacted by Nkolzie who is not our responsbal=
ity","system","268546","18-11-2024 11:51:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_517","NOCINC0003612682","Montee-D=
es-Soeurs","","18-11-2024 11:51:10","18-11-2024 11:26:23","18-11-2024 11:29=
:51","Cascaded Incident from TTO3533959","Hyemafo Gildas","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue sie on grid with=
 U=3D54v Notice that site is impacted by Nkolzie who is not our responsbali=
ty","system","268547","18-11-2024 11:51:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0003612667","A=
ccacia New","IHS_YND_517, IHS_YND_150, IHS_YND_505, IHS_YND_518, IHS_YND_51=
3","18-11-2024 11:47:28","18-11-2024 11:26:23","18-11-2024 12:30:51","No po=
wer issue sie on grid with U=3D54v Notice that site is impacted by Nkolzie =
who is not our responsbality","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","Affected by 3rd Party Site","No power issue sie on =
grid with U=3D54v Notice that site is impacted by Nkolzie who is not our re=
sponsbality","emmanuel.ghani@ihstowers.com","1266","18-11-2024 11:47:28","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0003612254","S=
OA 2","","18-11-2024 10:49:29","18-11-2024 10:46:17","18-11-2024 11:45:29",=
"site went down because disjunction cb(125A) in PWC  due to load// He reame=
d Cb(125A); site on grid","Siligap Boris","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","site went down because=
 disjunction cb(125A) in PWC  due to load// He reamed Cb(125A); site on gri=
d","emmanuel.ghani@ihstowers.com","192","18-11-2024 10:49:29","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0003611925","E=
-Police","","18-11-2024 09:58:20","18-11-2024 09:49:16","18-11-2024 11:50:3=
8","No power issue site on grid with U=3D51.5v Brice Tsague from Huawi is i=
nformed","","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","No power issue site on grid with U=3D51.5v Brice Ts=
ague from Huawi is informed/","emmanuel.ghani@ihstowers.com","545","18-11-2=
024 09:58:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003611763","T=
singa","","18-11-2024 09:34:47","18-11-2024 09:31:20","18-11-2024 09:53:41"=
,"Grid outage,site went down before DG start : Poor batteries Backup //DG s=
tarted automatically.","Mboua Thierry","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage,site went down before D=
G start : Poor batteries Backup //DG started automatically.","emmanuel.ghan=
i@ihstowers.com","208","18-11-2024 09:34:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0003611678","S=
apeur","","18-11-2024 09:16:55","18-11-2024 09:13:38","18-11-2024 11:45:49"=
,"No power issue on site Ubaie:54.3V; site on Grid. The Tx fme Brice Tsague=
 /650214096) from Huawei is informed.//site up at 09:49 AM","Mboua Thierry"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue on site Ubaie:54.3V; site on Grid. The Tx fme B=
rice Tsague /650214096) from Huawei is informed.//site up at 09:49 AM","emm=
anuel.ghani@ihstowers.com","199","18-11-2024 09:16:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003611433","N=
YOM 2 IHS","","18-11-2024 08:31:11","18-11-2024 08:29:19","18-11-2024 08:38=
:27","Grid fluctuation, Site went down before Gen start due to poor backup/=
/ Grid return","Fabrice Pouakam","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid fluctuation, Site went down before G=
en start due to poor backup// Grid return","emmanuel.ghani@ihstowers.com","=
113","18-11-2024 08:31:11","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_434","NOCINC0003611100","Donga","",=
"18-11-2024 07:15:34","","","Alarm not proven,site DG,Ubaie:54.2V; ","Parke=
r Tchoup","Warning","Warning","SYSTEM","Warning - Controler Failure","Alarm=
 not proven,site DG,Ubaie:54.2V; ","joelle.ekessi@ihstowers.com","2","18-11=
-2024 07:15:34","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_046","NOCINC0003611079","Djoungolo"=
,"","18-11-2024 07:13:02","","","Site alarming due to high temp 37=B0 // 25=
=B0 C AND shelter open and alarm cleared","Mboua Thierry","Warning","Warnin=
g","ENVIRONMENT","Warning - High Temperature","Site alarming due to high te=
mp 37=B0 // 25=B0 C AND shelter open and alarm cleared","joelle.ekessi@ihst=
owers.com","2","18-11-2024 07:13:02","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003610935","Eko=
unou","","18-11-2024 06:41:14","18-11-2024 06:35:06","18-11-2024 06:49:35",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","ch=
ristian.fonkou@ihstowers.com","370","18-11-2024 06:41:14","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003610890","NYO=
M FACE MAETUR","","18-11-2024 06:24:54","18-11-2024 06:14:50","18-11-2024 1=
5:39:43","Grid Outage landlord has forbiden to start the Gen Because the No=
ise//Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Emergency Stop","Grid Outage landlord has forbiden to start the =
Gen Because the Noise//Grid Restored","christian.fonkou@ihstowers.com","605=
","18-11-2024 06:24:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003610846","MBALNGON=
G LYCEE","","18-11-2024 06:18:41","18-11-2024 06:09:18","18-11-2024 06:23:3=
5","Cascaded Incident from TTO3531896","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down because 1/8 rectif=
ier faulty// He removed rectifier faulty, Site on Gen","system","266070","1=
8-11-2024 06:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003610847","Afanoya"=
,"","18-11-2024 06:18:41","18-11-2024 06:09:18","18-11-2024 06:23:35","Casc=
aded Incident from TTO3531896","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because 1/8 rectifier f=
aulty// He removed rectifier faulty, Site on Gen","system","266070","18-11-=
2024 06:18:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003610845","ELOUMDEM=
 CARRIERE","","18-11-2024 06:18:41","18-11-2024 06:09:18","18-11-2024 06:23=
:35","Cascaded Incident from TTO3531896","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because 1/8 rect=
ifier faulty// He removed rectifier faulty, Site on Gen","system","563","18=
-11-2024 06:18:41","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003610843","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","18-11-2024 06:17:22","18-11-20=
24 06:09:18","18-11-2024 06:23:35","Site went down because 1/8 rectifier fa=
ulty// He removed rectifier faulty, Site on Gen","Hyemafo Gildas","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module","Site went down because =
1/8 rectifier faulty// He removed rectifier faulty, Site on Gen","christian=
.fonkou@ihstowers.com","485","18-11-2024 06:17:22","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003610706","N=
yanon","","18-11-2024 05:43:07","18-11-2024 05:37:58","18-11-2024 06:17:19"=
,"Hybrid Gen Site: site went down because of the dysfunctioning of hybrid s=
ystem // He reset it, site on Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: site went down b=
ecause of the dysfunctioning of hybrid system // He reset it, site on Gen",=
"ludivine.ngamaleu@ihstowers.com","311","18-11-2024 05:43:07","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0003610266","M=
beng","IHS_YND_553","18-11-2024 02:57:26","18-11-2024 02:51:12","18-11-2024=
 02:58:08","Grid outage, site went down due to hybrid system disfunction// =
He reset it, site on Gen","Fanda Brice","Equipment Repair","Passive","Hybri=
d","Hybrid Module","Grid outage, site went down due to hybrid system disfun=
ction// He reset it, site on Gen","ludivine.ngamaleu@ihstowers.com","375","=
18-11-2024 02:57:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0003609992","C=
arrefourt Nkomo","","18-11-2024 01:50:51","18-11-2024 01:49:42","18-11-2024=
 02:10:56","Grid Bad voltage, Site went down due to Eneo phase missing// He=
 did a bridge on Good phase","Mba Lazare Herve","Grid Supply","Passive","Gr=
id","National Grid - Grid Incomplete Phase","Grid Bad voltage, Site went do=
wn due to Eneo phase missing// He did a bridge on Good phase","ludivine.nga=
maleu@ihstowers.com","70","18-11-2024 01:50:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003609986","M=
VAN SACEL","","18-11-2024 01:48:20","18-11-2024 01:44:07","18-11-2024 01:54=
:41","Grid fluctuation, Site went down before Gen start due to poor backup/=
/ Grid return","MINKA NICOLAS","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid fluctuation, Site went down before Gen=
 start due to poor backup// Grid return","ludivine.ngamaleu@ihstowers.com",=
"254","18-11-2024 01:48:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003609765","Ngoum","=
","18-11-2024 00:15:51","18-11-2024 00:04:27","18-11-2024 00:44:12","Cascad=
ed Incident from TTO3530633","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Hybrid Gen: site went down because gen ra=
n untill fuel shortage // refueling ongoing","system","280770","18-11-2024 =
00:15:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003609766","Ngouetou=
","","18-11-2024 00:15:51","18-11-2024 00:04:27","18-11-2024 00:44:12","Cas=
caded Incident from TTO3530633","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen: site went down because gen=
 ran untill fuel shortage // refueling ongoing","system","280771","18-11-20=
24 00:15:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003609767","Yoko MTN=
","","18-11-2024 00:15:51","18-11-2024 00:04:27","18-11-2024 00:44:12","Cas=
caded Incident from TTO3530633","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen: site went down because gen=
 ran untill fuel shortage // refueling ongoing","system","280770","18-11-20=
24 00:15:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003609763","MBIMBIM"=
,"","18-11-2024 00:15:50","18-11-2024 00:04:27","18-11-2024 00:44:12","Casc=
aded Incident from TTO3530633","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid Gen: site went down because gen =
ran untill fuel shortage // refueling ongoing","system","280770","18-11-202=
4 00:15:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003609764","Matsari"=
,"","18-11-2024 00:15:50","18-11-2024 00:04:27","18-11-2024 00:44:12","Casc=
aded Incident from TTO3530633","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid Gen: site went down because gen =
ran untill fuel shortage // refueling ongoing","system","280771","18-11-202=
4 00:15:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0003609738","D=
ong","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_YND_473","18-=
11-2024 00:02:38","18-11-2024 00:00:27","18-11-2024 00:44:12","Hybrid Gen: =
site went down because gen ran untill fuel shortage // refueling ongoing","=
Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Hybrid Gen=
: site went down because gen ran untill fuel shortage // refueling ongoing"=
,"ludivine.ngamaleu@ihstowers.com","132","18-11-2024 00:02:38","Sagemcom CM=
R"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0003609427","Bri=
quetterie","","17-11-2024 22:32:49","17-11-2024 22:24:42","19-11-2024 08:49=
:09","Grid outage, no space to deploy a MDG// grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spac=
e to deploy a MDG// grid return
","rouselle.schoune@ihstowers.com","488","17-11-2024 22:32:49","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003609416","B=
riqueterie","","17-11-2024 22:31:46","17-11-2024 22:22:40","19-11-2024 08:4=
7:27","Grid outage, no space to deploy a MDG// grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spa=
ce to deploy a MDG// grid return
","ludivine.ngamaleu@ihstowers.com","547","17-11-2024 22:31:46","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003609408","E=
kie-Elegance","","17-11-2024 22:30:24","17-11-2024 22:15:14","17-11-2024 23=
:55:13","Grid outage// He deployed MDG of 15KVA","Albran Byorel","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage// He =
deployed MDG of 15KVA","ludivine.ngamaleu@ihstowers.com","910","17-11-2024 =
22:30:24","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003609386","ODZ=
A CITE MBIA","","17-11-2024 22:23:46","17-11-2024 22:05:39","18-11-2024 00:=
05:11","Grid OUTAGE, site went down because gen fails to start due to ATS d=
isfunctionning // Gen manualy started","Albran Byorel","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down becau=
se gen fails to start due to ATS disfunctionning // Gen manualy started","r=
ouselle.schoune@ihstowers.com","1088","17-11-2024 22:23:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_396","NOCINC0003609349","Nkolmvac=
k","","17-11-2024 22:14:51","17-11-2024 21:55:03","17-11-2024 21:56:03","Ca=
scaded Incident from TTO3530121","Parker Tchoup","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site U =3D 52.8V site =
on Gen=20
FME TX Gregoire  (652070658/huawei) is informed.
","system","273951","17-11-2024 22:14:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003609214","Mambine"=
,"","17-11-2024 21:50:42","17-11-2024 21:17:57","17-11-2024 21:20:38","Casc=
aded Incident from TTO3529943","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site , Ubaie=3D52,3 V site=
 On Grid The Tx FME Georges 697461814 from Huawei is informed","system","19=
65","17-11-2024 21:50:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0003609215","Angongo"=
,"","17-11-2024 21:50:42","17-11-2024 21:17:57","17-11-2024 21:20:38","Casc=
aded Incident from TTO3529943","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site , Ubaie=3D52,3 V site=
 On Grid The Tx FME Georges 697461814 from Huawei is informed","system","19=
65","17-11-2024 21:50:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0003609213","OKOA Pea=
ge","","17-11-2024 21:50:42","17-11-2024 21:17:57","17-11-2024 21:20:38","C=
ascaded Incident from TTO3529943","Fanda Brice","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site , Ubaie=3D52,3 V s=
ite On Grid The Tx FME Georges 697461814 from Huawei is informed","system",=
"1965","17-11-2024 21:50:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0003609212","Nomayos-=
IHS","","17-11-2024 21:50:42","17-11-2024 21:17:57","17-11-2024 21:20:38","=
Cascaded Incident from TTO3529943","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site , Ubaie=3D52,3 V =
site On Grid The Tx FME Georges 697461814 from Huawei is informed","system"=
,"276179","17-11-2024 21:50:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003609216","Nkongtoc=
k","","17-11-2024 21:50:42","17-11-2024 21:17:57","17-11-2024 21:20:38","Ca=
scaded Incident from TTO3529943","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site , Ubaie=3D52,3 =
V site On Grid The Tx FME Georges 697461814 from Huawei is informed","syste=
m","276182","17-11-2024 21:50:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0003609209","Mbankomo=
 IHS","","17-11-2024 21:50:41","17-11-2024 21:17:57","17-11-2024 21:20:38",=
"Cascaded Incident from TTO3529943","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site , Ubaie=3D52,3 V=
 site On Grid The Tx FME Georges 697461814 from Huawei is informed","system=
","1964","17-11-2024 21:50:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003609211","Ebeba","=
","17-11-2024 21:50:41","17-11-2024 21:17:57","17-11-2024 21:20:38","Cascad=
ed Incident from TTO3529943","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site , Ubaie=3D52,3 V site O=
n Grid The Tx FME Georges 697461814 from Huawei is informed","system","1964=
","17-11-2024 21:50:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0003609208","Mandoumb=
a OCM","","17-11-2024 21:50:41","17-11-2024 21:17:57","17-11-2024 21:20:38"=
,"Cascaded Incident from TTO3529943","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site , Ubaie=3D5=
2,3 V site On Grid The Tx FME Georges 697461814 from Huawei is informed","s=
ystem","1964","17-11-2024 21:50:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0003609207","Sous Pre=
fecture","","17-11-2024 21:50:41","17-11-2024 21:17:57","17-11-2024 21:20:3=
8","Cascaded Incident from TTO3529943","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site , Ubaie=3D52,=
3 V site On Grid The Tx FME Georges 697461814 from Huawei is informed","sys=
tem","1964","17-11-2024 21:50:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0003609210","Nkenglik=
ok","","17-11-2024 21:50:41","17-11-2024 21:17:57","17-11-2024 21:20:38","C=
ascaded Incident from TTO3529943","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site , Ubaie=3D52,3=
 V site On Grid The Tx FME Georges 697461814 from Huawei is informed","syst=
em","1964","17-11-2024 21:50:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0003609183","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, I=
HS_YND_697, IHS_YND_330, IHS_YND_350, IHS_YND_335, IHS_YND_349","17-11-2024=
 21:45:07","17-11-2024 21:17:57","18-11-2024 00:35:52","No power issue on s=
ite , Ubaie=3D52,3 V site On Grid The Tx FME Georges 697461814 from Huawei =
is informed","Fanda Brice","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue on site , Ubaie=3D52,=
3 V site On Grid The Tx FME Georges 697461814 from Huawei is informed","ale=
xandre.kamal@ihstowers.com","1631","17-11-2024 21:45:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0003609043","S=
OA 2","","17-11-2024 21:17:26","17-11-2024 20:59:18","17-11-2024 22:26:24",=
"Site went down because 02 CB (80A) tripped in PWC who feed equipment OCM /=
/ CB put back on and  he added 01 CB (80A)","Siligap Boris","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site=
 went down because 02 CB (80A) tripped in PWC who feed equipment OCM // CB =
put back on and  he added 01 CB (80A)","alexandre.kamal@ihstowers.com","108=
9","17-11-2024 21:17:26","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0003608725","Mon=
tee-Jouvence-II","","17-11-2024 20:30:09","17-11-2024 20:05:51","17-11-2024=
 22:55:51","site went down due to PWC over load(12KW.280A) // Site stabiliz=
ed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","site went down due to PWC over load(12KW.280A) // Site st=
abilized","kamga.virgile@ihstowers.com","1459","17-11-2024 20:30:09","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_193","NOCINC0003608576","Bastos E=
koudou","","17-11-2024 20:09:00","17-11-2024 17:28:57","17-11-2024 17:44:16=
","Cascaded Incident from TTO3528234","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage No space to deploy /=
/ Grid power return","system","275712","17-11-2024 20:09:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0003608423","N=
omayos","","17-11-2024 19:43:13","17-11-2024 19:34:07","17-11-2024 19:40:42=
","No power issue on site , Ubaie=3D50 V site On Grid The Tx FME Georges 69=
7461814 from Huawei is informed.Notice that we have Disjunction at BTS OCM.=
","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","No power issue on site , Ubaie=3D50 V site On G=
rid The Tx FME Georges 697461814 from Huawei is informed.Notice that we hav=
e Disjunction at BTS OCM.","alexandre.kamal@ihstowers.com","547","17-11-202=
4 19:43:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003608012","E=
kie-Elegance","","17-11-2024 18:29:20","17-11-2024 18:21:13","17-11-2024 21=
:00:58","Grid outage//MDG of 15 kva ha deployed","Albran Byorel","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG =
of 15 kva ha deployed","alexandre.kamal@ihstowers.com","488","17-11-2024 18=
:29:20","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003607831","ODZ=
A CITE MBIA","","17-11-2024 17:56:14","17-11-2024 17:53:05","17-11-2024 18:=
47:23","Site went down due to insuffisance of rectifier(03) on Site // site=
 stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to insuffisance of rectifier(03) on Site =
// site stabilized","kamga.virgile@ihstowers.com","190","17-11-2024 17:56:1=
4","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003607739","Lab=
oratoire  Meka","IHS_YND_193","17-11-2024 17:41:53","17-11-2024 17:28:37","=
17-11-2024 17:44:45","Grid outage No space to deploy // Grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage No space to deploy // Grid power return","kamga.virgile@ihstowers.c=
om","796","17-11-2024 17:41:53","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003607732","Bas=
tos Ekoudou","","17-11-2024 17:40:14","17-11-2024 17:28:55","17-11-2024 17:=
28:56","","Mboua Thierry","Incorrectly Logged Tickets","Error","Error","Err=
or","NO","kamga.virgile@ihstowers.com","680","17-11-2024 17:40:14","Sagemco=
m CMR"
"Closed Complete","Warning","CTR_409","IHS_YND_090","NOCINC0003607618","BAT=
A-Mokolo","","17-11-2024 17:26:21","","","Grid outage,no space to deploy //=
Grid restored.","","Warning","Warning","POWER","Warning - National Grid - G=
rid Outage Issue","Grid outage,no space to deploy //Grid restored.","ludovi=
c.tchagna@ihstowers.com","4","17-11-2024 17:26:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003607598","M=
efou-Assi","","17-11-2024 17:20:14","17-11-2024 17:04:09","17-11-2024 17:10=
:10","Active// No power issue on site , Ubaie=3D53.3V site On Grid The Tx F=
ME Georges 697461814 from Huawei is informed.   Notice that we have Disjunc=
tion at BTS OCM.","Fanda Brice","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active// No power issue on site=
 , Ubaie=3D53.3V site On Grid The Tx FME Georges 697461814 from Huawei is i=
nformed.=20
Notice that we have Disjunction at BTS OCM.
","alexandre.kamal@ihstowers.com","966","17-11-2024 17:20:14","Sagemcom CMR=
"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0003607330","Aha=
la Echangeur","","17-11-2024 16:34:32","17-11-2024 16:27:58","17-11-2024 16=
:34:50","Grid fluctuation ste went down because Gen failed to start due to =
Grid bad voltage // Grid stabilized","MINKA NICOLAS","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuation ste we=
nt down because Gen failed to start due to Grid bad voltage // Grid stabili=
zed","kamga.virgile@ihstowers.com","395","17-11-2024 16:34:32","Sagemcom CM=
R"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003607199","Nko=
abang2","","17-11-2024 16:15:44","17-11-2024 16:07:59","17-11-2024 16:23:25=
","Grid outage site went down because Gen overload (22Kva. 315A) // Grid po=
wer return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage site went down because Gen overload (22Kva. 315A=
) // Grid power return","kamga.virgile@ihstowers.com","584","17-11-2024 16:=
15:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003607192","M=
ANGUIERS CHAPELLE","","17-11-2024 16:14:42","17-11-2024 16:05:31","17-11-20=
24 16:23:40","Grid outage, site went down before Gen start due to poor back=
up// Grid power return","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re Gen start due to poor backup// Grid power return","alexandre.kamal@ihsto=
wers.com","552","17-11-2024 16:14:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003607186","Nkolo II=
 New","","17-11-2024 16:14:00","17-11-2024 16:02:59","17-11-2024 18:42:51",=
"Cascaded Incident from TTO3527549","Mba Lazare Herve","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","no power issue  on site ,site on G=
rid  with U=3D54.6V  The TX FME Eloundou Bertrand/ 693212405 of huawei is i=
nformed. Notice that we have disjunction at BTS OCM","system","280797","17-=
11-2024 16:14:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003607180","M=
imboman-Village","IHS_YND_709","17-11-2024 16:12:47","17-11-2024 16:02:59",=
"17-11-2024 18:42:51","no power issue  on site ,site on Grid  with U=3D54.6=
V  The TX FME Eloundou Bertrand/ 693212405 of huawei is informed. Notice th=
at we have disjunction at BTS OCM","Mba Lazare Herve","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power =
issue  on site ,site on Grid  with U=3D54.6V  The TX FME Eloundou Bertrand/=
 693212405 of huawei is informed. Notice that we have disjunction at BTS OC=
M","alexandre.kamal@ihstowers.com","590","17-11-2024 16:12:47","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003607106","MVAN SAC=
EL","","17-11-2024 15:58:40","17-11-2024 15:33:00","17-11-2024 22:37:52","C=
ascaded Incident from TTO3527456","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down due to G=
en overload (20KVA, 290A) // grid return","system","1540","17-11-2024 15:58=
:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0003607095","N=
goum","","17-11-2024 15:56:18","17-11-2024 15:49:05","17-11-2024 15:55:18",=
"No power issue site on Solar, with U=3D51V The Tx Fme Gregoire (654547479)=
 from Huawei informed .","Parker Tchoup","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 Solar, with U=3D51V The Tx Fme Gregoire (654547479) from Huawei informed .=
","alexandre.kamal@ihstowers.com","435","17-11-2024 15:56:18","Sagemcom CMR=
"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003607037","MVA=
N","IHS_YND_510","17-11-2024 15:44:33","17-11-2024 15:33:00","17-11-2024 22=
:37:52","Grid outage, Site went down due to Gen overload (20KVA, 290A) // g=
rid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Overload","Grid outage, Site went down due to Gen overload (20KVA, 290A) /=
/ grid return","kamga.virgile@ihstowers.com","1516","17-11-2024 15:44:33","=
Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003606967","Nom=
ayos montee Meche","","17-11-2024 15:31:06","17-11-2024 15:28:51","17-11-20=
24 15:35:10","No power issue on site , Ubaie=3D53 V site On Grid The Tx FME=
 Georges 697461814 from Huawei is informed","Fanda Brice","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site , Ubaie=3D53 V site On Grid The Tx FME Georges 697461814 =
from Huawei is informed","kamga.virgile@ihstowers.com","136","17-11-2024 15=
:31:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003606854","B=
iteng-Maetur","","17-11-2024 15:16:55","17-11-2024 14:44:48","17-11-2024 15=
:37:34","Grid outage site went down because Gen overload (20KVA, 330A) // H=
e reduced the load on site. site on Gen","Mba Lazare Herve","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down beca=
use Gen overload (20KVA, 330A) // He reduced the load on site. site on Gen"=
,"alexandre.kamal@ihstowers.com","1928","17-11-2024 15:16:55","Sagemcom CMR=
"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003606222","ODZ=
A CITE MBIA","","17-11-2024 13:43:37","17-11-2024 13:36:33","17-11-2024 14:=
26:36","Grid outage site went down becuase Gen failed to start due to ATS d=
ysfonction // Gen manually started","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","Grid outage site went down becuase G=
en failed to start due to ATS dysfonction // Gen manually started","landry.=
etame@ihstowers.com","425","17-11-2024 13:43:37","Sagemcom CMR"
"Closed Complete","Site Down","T0530","IHS_YND_252","NOCINC0003606132","Kow=
eit City","","17-11-2024 13:28:26","17-11-2024 13:23:17","17-11-2024 13:57:=
29","Grid outage site went down because Gen failed to start with alarm low =
fuel // He reset the Gen card and Gen manually started","Albran Byorel","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage si=
te went down because Gen failed to start with alarm low fuel // He reset th=
e Gen card and Gen manually started","landry.etame@ihstowers.com","504","17=
-11-2024 13:28:26","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003606067","Men=
dong3","","17-11-2024 13:15:57","17-11-2024 13:08:53","17-11-2024 13:38:12"=
,"Grid Outage No Space to Deploy a MDG // Grid Restored","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space t=
o Deploy a MDG // Grid Restored","landry.etame@ihstowers.com","425","17-11-=
2024 13:15:57","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0003606047","NKO=
LOSSAN OKOK","","17-11-2024 13:13:20","17-11-2024 13:03:10","17-11-2024 15:=
54:12","site went down because 01/03 rectifier faulty // he replaced the re=
ctifier faulty","Parker Tchoup","Equipment Repair","Passive","Rectifier","R=
ectifier Module","site went down because 01/03 rectifier faulty // he repla=
ced the rectifier faulty","landry.etame@ihstowers.com","611","17-11-2024 13=
:13:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003605420","Nkolbiss=
on usines des eaux 2","","17-11-2024 12:05:10","17-11-2024 11:28:06","17-11=
-2024 12:22:53","Cascaded Incident from TTO3525487","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid Ou=
tage Site went down due to Gen overload(20Kva ;200A)//He reduice the Load  =
","system","268561","17-11-2024 12:05:10","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003605414","Nko=
lbisson","IHS_YND_763","17-11-2024 12:04:14","17-11-2024 11:28:06","17-11-2=
024 13:30:41","Grid Outage Site went down due to Gen overload(20Kva ;200A)/=
/He reduice the Load  ","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid Outage Site went down due to Gen ov=
erload(20Kva ;200A)//He reduice the Load  ","landry.etame@ihstowers.com","2=
169","17-11-2024 12:04:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0003605402","M=
endong","IHS_YND_692, IHS_YND_236","17-11-2024 11:59:54","17-11-2024 11:44:=
50","17-11-2024 12:58:34","Grid Outage site went down because Gen failed to=
 start due to battery Gen faulty// Gen manually started with external batte=
ry","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid Outage site went down because Gen failed to start due to =
battery Gen faulty// Gen manually started with external battery","stephane.=
nkamwa@ihstowers.com","905","17-11-2024 11:59:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003605401","M=
endong vallee","","17-11-2024 11:59:00","17-11-2024 11:44:50","17-11-2024 1=
2:58:34","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Outage site went down because Gen failed to start due t=
o battery Gen faulty// Gen manually started with external battery","stephan=
e.nkamwa@ihstowers.com","1216992","17-11-2024 11:59:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0003605383","M=
ontee-Jouvence","","17-11-2024 11:54:18","17-11-2024 11:44:50","17-11-2024 =
12:58:34","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid Outage site went down because Gen failed to start d=
ue to battery Gen faulty// Gen manually started with external battery","ste=
phane.nkamwa@ihstowers.com","1216993","17-11-2024 11:54:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003605380","B=
iteng-Maetur","","17-11-2024 11:53:11","17-11-2024 11:33:05","17-11-2024 13=
:41:37","Grid outage site went down because Gen overload (20KVA, 330A) // H=
e reduced the load on site. site on Gen ","Mba Lazare Herve","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down bec=
ause Gen overload (20KVA, 330A) // He reduced the load on site. site on Gen=
 ","stephane.nkamwa@ihstowers.com","1208","17-11-2024 11:53:11","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_030","NOCINC0003605271","E-Police=
","","17-11-2024 11:22:42","17-11-2024 10:23:31","17-11-2024 13:00:10","No =
power issue U=3D51.9 V site on Grid  tx fme BRICE Tsague/ 650214096 from hu=
awie is informed ","","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power issue U=3D51.9 V site on Grid  t=
x fme BRICE Tsague/ 650214096 from huawie is informed ","stephane.nkamwa@ih=
stowers.com","3552","17-11-2024 11:22:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003605260","Scalom-I=
HS","","17-11-2024 11:21:10","17-11-2024 10:12:32","17-11-2024 10:15:17","C=
ascaded Incident from TTO3525223","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","No power issue  on site Ubaie=3D53.5  V site on Grid=
.  The Tx FME Hosiah//699699694 /Huawei is informed.","system","273013","17=
-11-2024 11:21:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003605197","N=
kol-Mbanda","","17-11-2024 11:12:31","17-11-2024 11:10:27","17-11-2024 13:2=
1:02","Active//No power issue on site ,site on Grid with Ubaie=3D54.6V The =
Tx FME Hosiah (674007438)  from Huawei is informed.","MINKA NICOLAS","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue on site ,site on Grid with Ubaie=3D54.6V The T=
x FME Hosiah (674007438)  from Huawei is informed.","stephane.nkamwa@ihstow=
ers.com","126","17-11-2024 11:12:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003605193","M=
ontee-Jouvence-II","","17-11-2024 11:11:44","17-11-2024 10:10:36","17-11-20=
24 13:10:10","Active//No power issue on site U=3D53.5V site on Gen   The Fm=
e Tx Mbah Hosiah (6 74 00 74 38) from Huawei is informed.","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue on site U=3D53.5V site on Gen   The Fme=
 Tx Mbah Hosiah (6 74 00 74 38) from Huawei is informed.","stephane.nkamwa@=
ihstowers.com","3669","17-11-2024 11:11:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0003605190","A=
ccacia New","IHS_YND_505","17-11-2024 11:10:40","17-11-2024 10:12:32","17-1=
1-2024 13:01:22","No power issue  on site Ubaie=3D53.5  V site on Grid.  Th=
e Tx FME Hosiah//699699694 /Huawei is informed.","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue  on site Ubaie=3D53.5  V site on Grid.  The Tx FME Hosiah//699699694 /H=
uawei is informed.","stephane.nkamwa@ihstowers.com","3489","17-11-2024 11:1=
0:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003605184","M=
aison-Blanche-IHS","","17-11-2024 11:09:38","17-11-2024 10:12:31","17-11-20=
24 13:20:45","No power issue on site U=3D53.8 V site on Grid   The Fme Tx M=
bah Hosiah (6 74 00 74 38) from Huawei is informed. . repetitive issue","",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","No power issue on site U=3D53.8 V site on Grid   The Fme Tx Mba=
h Hosiah (6 74 00 74 38) from Huawei is informed. . repetitive issue","step=
hane.nkamwa@ihstowers.com","3428","17-11-2024 11:09:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003605178","M=
ontee-Des-Soeurs","","17-11-2024 11:08:44","17-11-2024 10:12:36","17-11-202=
4 13:15:18","No  power issue on site, site on Grid with Ubaie=3D 51V  The T=
x Fme  Mbah Hosiah //674007438/   from HUAWEI is informed.","Hyemafo Gildas=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No  power issue on site, site on Grid with Ubaie=3D 51V  The =
Tx Fme  Mbah Hosiah //674007438/   from HUAWEI is informed.","stephane.nkam=
wa@ihstowers.com","3369","17-11-2024 11:08:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0003605041","E=
seka Town","","17-11-2024 10:39:44","17-11-2024 10:29:32","17-11-2024 13:12=
:35","Active//No power issue, site is on Grid and Ubaie=3D52.8V, The FME TX=
  Etienne (695-03-39-81) From Huawei is informed and Site UP AT=3D11:52 AM"=
,"Kemeni Franklin","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active//No power issue, site is on Grid and =
Ubaie=3D52.8V, The FME TX  Etienne (695-03-39-81) From Huawei is informed a=
nd Site UP AT=3D11:52 AM","stephane.nkamwa@ihstowers.com","613","17-11-2024=
 10:39:44","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003605030","NYO=
M FACE MAETUR","","17-11-2024 10:37:37","17-11-2024 10:28:31","17-11-2024 1=
2:42:23","Grid Outage  landlord has forbiden to start the Gen Because the N=
oise // Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Emergency Stop","Grid Outage  landlord has forbiden to start =
the Gen Because the Noise // Grid Restored","landry.etame@ihstowers.com","5=
47","17-11-2024 10:37:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003604834","ELOUMDEM=
 CARRIERE 2","","17-11-2024 10:10:11","17-11-2024 09:58:50","17-11-2024 10:=
32:06","Cascaded Incident from TTO3524783","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Gen start and stopped due to Grid bad voltage // Gen manually s=
tarted","system","681","17-11-2024 10:10:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003604833","Eto koss=
 Yde","","17-11-2024 10:10:11","17-11-2024 09:58:50","17-11-2024 10:32:06",=
"Cascaded Incident from TTO3524783","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Gen start and stopped due to Grid bad voltage // Gen manually started"=
,"system","681","17-11-2024 10:10:11","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003604818","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","17-11-2024 10:07:57","17-11-2024 09:56=
:50","17-11-2024 10:32:06","Grid fluctuation, site went down because Gen st=
art and stopped due to Grid bad voltage // Gen manually started","Fanda Bri=
ce","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because Gen start and stopped due to Gr=
id bad voltage // Gen manually started","landry.etame@ihstowers.com","800",=
"17-11-2024 10:07:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003603905","B=
itoto","","17-11-2024 07:03:11","17-11-2024 06:51:04","17-11-2024 13:15:02"=
,"ACTIVE // No power issue site on grid with U=3D54.2v The RM TX ALAIN  ( 6=
91144423) /From HUAWEI is informed","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE /=
/ No power issue site on grid with U=3D54.2v The RM TX ALAIN  ( 691144423) =
/From HUAWEI is informed","stephane.nkamwa@ihstowers.com","729","17-11-2024=
 07:03:11","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003603865","N=
yanon","","17-11-2024 06:56:34","17-11-2024 06:46:29","17-11-2024 07:38:24"=
,"Hybrid Gen Site: site went down because of the dysfunctioning of hybrid s=
ystem // He reset it, site on Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: site went down b=
ecause of the dysfunctioning of hybrid system // He reset it, site on Gen",=
"stephane.nkamwa@ihstowers.com","606","17-11-2024 06:56:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0003603787","Eseka MT=
N","","17-11-2024 06:41:52","17-11-2024 06:34:18","17-11-2024 06:35:53","Ca=
scaded Incident from TTO3523569","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue site on Gen  wi=
th U=3D54.6V The  Tx Fme Yannick Mbah/670610135/  from Huawei is informed a=
nd Up at  06:48 AM","system","454","17-11-2024 06:41:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003603789","Eseka To=
wn","","17-11-2024 06:41:52","17-11-2024 06:34:18","17-11-2024 06:35:53","C=
ascaded Incident from TTO3523569","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue site on Gen  w=
ith U=3D54.6V The  Tx Fme Yannick Mbah/670610135/  from Huawei is informed =
and Up at  06:48 AM","system","264450","17-11-2024 06:41:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003603784","Ndogbess=
ol","","17-11-2024 06:41:51","17-11-2024 06:34:18","17-11-2024 06:35:53","C=
ascaded Incident from TTO3523569","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue site on Gen  w=
ith U=3D54.6V The  Tx Fme Yannick Mbah/670610135/  from Huawei is informed =
and Up at  06:48 AM","system","453","17-11-2024 06:41:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003603424","N=
koabang2","","17-11-2024 04:36:54","16-11-2024 23:11:32","16-11-2024 23:28:=
56","Grid fluctuation, site went down because gen start and stopped due to =
grid bad voltage no rcp on site // Grid stabilized","Mba Lazare Herve","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation, site went down because gen start and stopped due to grid bad v=
oltage no rcp on site // Grid stabilized","rouselle.schoune@ihstowers.com",=
"20079","17-11-2024 04:36:54","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0003603320","Bon=
djock","","17-11-2024 04:09:15","17-11-2024 04:07:55","17-11-2024 04:10:55"=
,"Grid outage, Site went down before Gen start due to poor backup// Gen sta=
rted automatically","Fanda Brice","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, Site went down before Gen s=
tart due to poor backup// Gen started automatically","denis.mballa@ihstower=
s.com","81","17-11-2024 04:09:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003603056","Akak-Nko=
zoa-MTN-IHS","","17-11-2024 01:58:00","17-11-2024 01:54:01","17-11-2024 01:=
57:20","Cascaded Incident from TTO3522750","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active // No  power issue UB=
aie =3D54,5V site on Grid. The RM TX  SYMPHORIEN (650 25 71 51) From Huawei=
 is informed and up at 01:57 AM","system","266991","17-11-2024 01:58:00","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003603050","S=
oa-II","IHS_YND_316, IHS_YND_324","17-11-2024 01:56:09","17-11-2024 01:54:0=
1","17-11-2024 01:57:20","Active // No  power issue UBaie =3D54,5V site on =
Grid. The RM TX  SYMPHORIEN (650 25 71 51) From Huawei is informed and up a=
t 01:57 AM","Siligap Boris","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Active // No  power issue UBaie =3D=
54,5V site on Grid. The RM TX  SYMPHORIEN (650 25 71 51) From Huawei is inf=
ormed and up at 01:57 AM","rouselle.schoune@ihstowers.com","129","17-11-202=
4 01:56:09","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003602407","Nko=
abang2","","16-11-2024 23:10:50","16-11-2024 22:56:27","16-11-2024 23:10:36=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage no rcp on site // Grid stabilized","Mba Lazare Herve","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation, site went down because gen start and stopped due to grid bad vol=
tage no rcp on site // Grid stabilized","denis.mballa@ihstowers.com","864",=
"16-11-2024 23:10:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003602405","F=
ebe Village","","16-11-2024 23:10:15","16-11-2024 23:04:07","17-11-2024 01:=
00:25","Site went down due to insufficient of rectifiers (04)// He added 01=
 rectifier","Mboua Thierry","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to insufficient of rectifiers (04)// He ad=
ded 01 rectifier","rouselle.schoune@ihstowers.com","369","16-11-2024 23:10:=
15","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003602126","Mvo=
g-Betsi","IHS_YND_140","16-11-2024 22:00:39","16-11-2024 19:59:18","16-11-2=
024 20:17:05","Site went down due to insufficient of rectifier (2)// He add=
ed 01 rectifier","Hyemafo Gildas","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site went down due to insufficient of rectifier (2)// H=
e added 01 rectifier","kamga.virgile@ihstowers.com","7282","16-11-2024 22:0=
0:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0003601863","OLAMA","=
","16-11-2024 21:02:20","16-11-2024 16:52:21","16-11-2024 16:53:21","Cascad=
ed Incident from TTO3521377","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuation, site went down because ge=
n start and stopped due to grid bad voltage // he bypass grid an manually s=
tart the gen","system","14999","16-11-2024 21:02:20","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003601862","Ako=
no","IHS_YND_687","16-11-2024 21:01:32","16-11-2024 16:52:21","16-11-2024 1=
6:53:21","Grid fluctuation, site went down because gen start and stopped du=
e to grid bad voltage // he bypass grid an manually start the gen","Fanda B=
rice","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, site went down because gen start and stopped due to =
grid bad voltage // he bypass grid an manually start the gen","kamga.virgil=
e@ihstowers.com","14952","16-11-2024 21:01:32","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003601442","Mvo=
g-Betsi","","16-11-2024 20:02:23","16-11-2024 16:27:09","16-11-2024 16:45:0=
9","Site went down due to rectifiers insufficiency (2) // site stabilized",=
"Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module=
","Site went down due to rectifiers insufficiency (2) // site stabilized","=
kamga.virgile@ihstowers.com","12915","16-11-2024 20:02:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003601070","B=
riqueterie","","16-11-2024 19:20:05","16-11-2024 19:04:42","16-11-2024 20:1=
4:42","Grid Outage No Space to deploy a MDG// Grid Restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spa=
ce to deploy a MDG// Grid Restored","olivier.kwedi@ihstowers.com","924","16=
-11-2024 19:20:05","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0003601057","Bri=
quetterie","","16-11-2024 19:17:26","16-11-2024 19:01:11","16-11-2024 20:12=
:11","Grid outage, no space to deploy a mdg // grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spa=
ce to deploy a mdg // grid return","kamga.virgile@ihstowers.com","976","16-=
11-2024 19:17:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003600937","C=
ite-Verte","","16-11-2024 18:58:12","16-11-2024 18:52:58","16-11-2024 21:05=
:58","No power issue on site U=3D53v site on grid Brice Stague of huawei is=
 informed, Notice thad disjunction in OCM equipment","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site U=3D53v site on grid Brice Stague of huawei is informed, No=
tice thad disjunction in OCM equipment","olivier.kwedi@ihstowers.com","315"=
,"16-11-2024 18:58:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0003600906","B=
ISCUITERIE","","16-11-2024 18:53:37","16-11-2024 19:59:18","16-11-2024 20:0=
1:56","please cascade this TT behind NOCINC0003602126","Paul BIBOUM","Casca=
de Outage","Passive","Cascade Passive","Cascade Passive","Site went down du=
e to insufficient of rectifier (2)// He added 01 rectifier","olivier.kwedi@=
ihstowers.com","288144","16-11-2024 18:53:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003600490","M=
essa-Carriere OCM","","16-11-2024 17:54:06","16-11-2024 17:35:58","17-11-20=
24 12:53:07","Grid outage no space to deploy a MDG  // Grid power return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage no space to deploy a MDG  // Grid power return","olivier.kwedi@ihsto=
wers.com","1090","16-11-2024 17:54:06","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003600346","BIY=
EMASSI NIKI","","16-11-2024 17:29:53","16-11-2024 17:07:35","16-11-2024 17:=
51:35","Site went down because CB(63A) tripped in PWC who feeds equipments =
OCM// He did a bridge with another CB(63A","Hyemafo Gildas","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site=
 went down because CB(63A) tripped in PWC who feeds equipments OCM// He did=
 a bridge with another CB(63A","kamga.virgile@ihstowers.com","1339","16-11-=
2024 17:29:53","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003600213","NYO=
M FACE MAETUR","","16-11-2024 17:13:56","16-11-2024 17:03:44","16-11-2024 1=
7:29:44","Grid Outage Site went down due to landlord has forbiden to start =
the Gen// Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Emergency Stop","Grid Outage Site went down due to landlord h=
as forbiden to start the Gen// Grid return","kamga.virgile@ihstowers.com","=
613","16-11-2024 17:13:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003600148","Biteng-M=
aetur","","16-11-2024 17:03:41","16-11-2024 16:55:22","16-11-2024 16:57:22"=
,"Cascaded Incident from TTO3519272","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
fore Gen start due to poor backup// Gen started automaticaly","system","277=
654","16-11-2024 17:03:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003600147","Essomba"=
,"","16-11-2024 17:03:40","16-11-2024 16:55:22","16-11-2024 16:57:22","Casc=
aded Incident from TTO3519272","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before G=
en start due to poor backup// Gen started automaticaly","system","277655","=
16-11-2024 17:03:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003600131","B=
iteng","IHS_YND_179, IHS_YND_249","16-11-2024 17:01:51","16-11-2024 16:55:2=
2","16-11-2024 16:57:22","Grid outage, site went down before Gen start due =
to poor backup// Gen started automaticaly","Mba Lazare Herve","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,=
 site went down before Gen start due to poor backup// Gen started automatic=
aly","olivier.kwedi@ihstowers.com","390","16-11-2024 17:01:51","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0003600096","S=
calom","","16-11-2024 16:56:55","16-11-2024 16:49:42","16-11-2024 18:19:42"=
,"No power issue , Ubaie=3D54.5 V site on Grid.  The FME TX Mbah Hosiah //6=
74007438//  from huawei is informed.","Paul BIBOUM","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue , Ubaie=3D54.5 V site on Grid.  The FME TX Mbah Hosiah //674007438//  f=
rom huawei is informed.","olivier.kwedi@ihstowers.com","434","16-11-2024 16=
:56:55","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003600028","OLA=
MA","","16-11-2024 16:48:26","16-11-2024 16:44:16","16-11-2024 16:44:17","I=
ncorrectly Logged Tickets","Fanda Brice","Incorrectly Logged Tickets","Erro=
r","Error","Error","Incorrectly Logged Tickets","kamga.virgile@ihstowers.co=
m","251","16-11-2024 16:48:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003599329","Akak-Nko=
zoa-MTN-IHS","","16-11-2024 15:47:51","16-11-2024 15:43:57","16-11-2024 15:=
45:57","Cascaded Incident from TTO3518236","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue site on grid =
with U=3D54,7v Symphorien(691316854) from Huawei is informe","system","2820=
48","16-11-2024 15:47:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003599325","S=
oa-II","IHS_YND_316, IHS_YND_324","16-11-2024 15:46:23","16-11-2024 15:43:5=
7","16-11-2024 15:45:57","No power issue site on grid with U=3D54,7v Sympho=
rien(691316854) from Huawei is informe","Siligap Boris","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on grid with U=3D54,7v Symphorien(691316854) from Huawei is in=
forme","olivier.kwedi@ihstowers.com","147","16-11-2024 15:46:23","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003599205","Mamb",""=
,"16-11-2024 15:41:55","16-11-2024 13:55:33","16-11-2024 15:41:33","Cascade=
d Incident from TTO3516995","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site was on gen due to grid outage, site=
 went down because gen stopped due to AVR faulty // AVR replaced and gen st=
arted","system","281331","16-11-2024 15:41:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0003599206","Boga-Mah=
ole","","16-11-2024 15:41:55","16-11-2024 13:55:33","16-11-2024 15:41:33","=
Cascaded Incident from TTO3516995","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site was on gen due to grid outag=
e, site went down because gen stopped due to AVR faulty // AVR replaced and=
 gen started","system","281331","16-11-2024 15:41:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003599203","Song-bon=
g","","16-11-2024 15:41:54","16-11-2024 13:55:33","16-11-2024 15:41:33","Ca=
scaded Incident from TTO3516995","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site was on gen due to grid outage,=
 site went down because gen stopped due to AVR faulty // AVR replaced and g=
en started","system","281330","16-11-2024 15:41:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0003599201","Eseka OC=
M","","16-11-2024 15:41:54","16-11-2024 13:55:33","16-11-2024 15:41:33","Ca=
scaded Incident from TTO3516995","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site was on gen due to grid outage,=
 site went down because gen stopped due to AVR faulty // AVR replaced and g=
en started","system","281329","16-11-2024 15:41:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003599198","Boumnyeb=
el","","16-11-2024 15:41:53","16-11-2024 13:55:33","16-11-2024 15:41:33","C=
ascaded Incident from TTO3516995","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site was on gen due to grid outage=
, site went down because gen stopped due to AVR faulty // AVR replaced and =
gen started","system","281333","16-11-2024 15:41:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003599197","Ngog Map=
ubi","","16-11-2024 15:41:52","16-11-2024 13:55:33","16-11-2024 15:41:33","=
Cascaded Incident from TTO3516995","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site was on gen due to grid outag=
e, site went down because gen stopped due to AVR faulty // AVR replaced and=
 gen started","system","281332","16-11-2024 15:41:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003599194","Ndogbess=
ol","","16-11-2024 15:41:52","16-11-2024 13:55:33","16-11-2024 15:41:33","C=
ascaded Incident from TTO3516995","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site was on gen due to grid outage=
, site went down because gen stopped due to AVR faulty // AVR replaced and =
gen started","system","281329","16-11-2024 15:41:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003599193","Eseka To=
wn","","16-11-2024 15:41:52","16-11-2024 13:55:33","16-11-2024 15:41:33","C=
ascaded Incident from TTO3516995","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site was on gen due to grid outage=
, site went down because gen stopped due to AVR faulty // AVR replaced and =
gen started","system","281329","16-11-2024 15:41:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0003598438","N=
goum","","16-11-2024 15:04:26","16-11-2024 14:28:17","16-11-2024 14:30:17",=
"No power issue site on Grid  with U=3D54,6 V The Tx fme Gregoire (69123223=
6) from Huawei is informed","Parker Tchoup","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on Grid  with U=3D54,6 V The Tx fme Gregoire (691232236) from Huawei is in=
formed","olivier.kwedi@ihstowers.com","2171","16-11-2024 15:04:26","Sagemco=
m CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003598072","Mvo=
g-Betsi","","16-11-2024 14:48:47","16-11-2024 14:37:36","16-11-2024 14:55:3=
6","Site went down due to rectifiers insufficiency (2) // site stabilized "=
,"Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to rectifiers insufficiency (2) // site stabilized "=
,"kamga.virgile@ihstowers.com","672","16-11-2024 14:48:47","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003596539","AWA=
E OCM","","16-11-2024 12:13:37","16-11-2024 11:42:29","16-11-2024 12:13:43"=
,"Grid outage site went down because Gen started and stopped with alarm low=
 oil pressure // He reset the Gen card and Gen manually started","Mba Lazar=
e Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage site went down because Gen started and stopped with alarm low oil=
 pressure // He reset the Gen card and Gen manually started","alexandre.kam=
al@ihstowers.com","1870","16-11-2024 12:13:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0003596337","M=
balla 4","","16-11-2024 11:52:51","16-11-2024 11:45:40","16-11-2024 12:09:1=
8","site went down because gen failed due to grid bad voltage and no RCP //=
 Gen manually started","Delor Telezing","Grid Supply","Passive","Grid","Nat=
ional Grid - Grid Incomplete Phase","site went down because gen failed due =
to grid bad voltage and no RCP // Gen manually started","etienne.itondo@ihs=
towers.com","432","16-11-2024 11:52:51","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0003596225","Ako=
k Ndoe Yde","","16-11-2024 11:39:55","16-11-2024 11:27:47","16-11-2024 12:2=
5:34","Grid outage, site went down before gen start due to poor battery bac=
kup // gen manually started","Hyemafo Gildas","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // gen manually started","alexa=
ndre.kamal@ihstowers.com","729","16-11-2024 11:39:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003596200","S=
tade-Abega","","16-11-2024 11:34:07","16-11-2024 11:27:57","16-11-2024 13:2=
8:57","Grid outage, site went down because gen start and stopped with high =
temp alarm // Grid return","Mba Lazare Herve","Equipment Repair","Passive",=
"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage, si=
te went down because gen start and stopped with high temp alarm // Grid ret=
urn","etienne.itondo@ihstowers.com","370","16-11-2024 11:34:07","Sagemcom C=
MR"
"Closed Complete","Warning","T1241","IHS_YND_794","NOCINC0003595848","Nkoul=
ou Carriere carrefourt","","16-11-2024 10:46:03","","","","Mba Lazare Herve=
","Warning","Warning","POWER","Warning - AC Failure","NO","ludovic.tchagna@=
ihstowers.com","3","16-11-2024 10:46:03","Sagemcom CMR"
"Closed Complete","Warning","T1161","IHS_YND_290","NOCINC0003595841","Abang=
","","16-11-2024 10:45:03","","","","Mba Lazare Herve","Warning","Warning",=
"POWER","Warning - AC Failure","NO","ludovic.tchagna@ihstowers.com","4","16=
-11-2024 10:45:03","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003595488","Feb=
e Village","","16-11-2024 09:41:41","16-11-2024 09:26:41","16-11-2024 11:52=
:36","site went down because High temperature due to PWC fan faulty // He o=
pened the doors, site on grid","Mboua Thierry","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Fans Faulty","site went down because High=
 temperature due to PWC fan faulty // He opened the doors, site on grid","a=
lexandre.kamal@ihstowers.com","1635","16-11-2024 09:41:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003595421","A=
fanoya","","16-11-2024 09:27:19","16-11-2024 09:09:07","16-11-2024 09:15:16=
","No power issue on site , Ubaie=3D54.6V site On Grid The Tx FME Georges 6=
97461814 from Huawei is informed,r=E9p=E9titif issue","Hyemafo Gildas","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue on site , Ubaie=3D54.6V site On Grid The Tx FME Geor=
ges 697461814 from Huawei is informed,r=E9p=E9titif issue","etienne.itondo@=
ihstowers.com","3438","16-11-2024 09:27:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_409","NOCINC0003594858","Evodoula=
 OCM","","16-11-2024 07:53:15","16-11-2024 07:38:20","16-11-2024 07:39:20",=
"Cascaded Incident from TTO3513182","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","Site impacted by NKOG-EDZE=
N CTR_041 which is not under supervision of IHS","system","267965","16-11-2=
024 07:53:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0003594854","Monatele=
 MTN","","16-11-2024 07:53:14","16-11-2024 07:38:20","16-11-2024 07:39:20",=
"Cascaded Incident from TTO3513182","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Site impacted by NKOG-EDZEN CTR_041 w=
hich is not under supervision of IHS","system","267958","16-11-2024 07:53:1=
4","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_051","NOCINC0003594856","Nyanon",=
"","16-11-2024 07:53:14","16-11-2024 07:38:20","16-11-2024 07:39:20","Casca=
ded Incident from TTO3513182","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","Site impacted by NKOG-EDZEN CTR_=
041 which is not under supervision of IHS","system","894","16-11-2024 07:53=
:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_393","NOCINC0003594857","Ezezang"=
,"","16-11-2024 07:53:14","16-11-2024 07:38:20","16-11-2024 07:39:20","Casc=
aded Incident from TTO3513182","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by NKOG-EDZEN CTR_041 which =
is not under supervision of IHS","system","267958","16-11-2024 07:53:14","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0003594847","Talla Mo=
natele","","16-11-2024 07:53:12","16-11-2024 07:38:20","16-11-2024 07:39:20=
","Cascaded Incident from TTO3513182","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","Site impacted by NKOG-EDZEN CTR_041=
 which is not under supervision of IHS","system","267956","16-11-2024 07:53=
:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0003594837","Monatele=
","","16-11-2024 07:53:10","16-11-2024 07:38:20","16-11-2024 07:39:20","Cas=
caded Incident from TTO3513182","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Site impacted by NKOG-EDZEN CTR_041 which=
 is not under supervision of IHS","system","890","16-11-2024 07:53:10","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003594364","Donga","=
","16-11-2024 06:02:51","16-11-2024 05:25:18","16-11-2024 05:30:12","Cascad=
ed Incident from TTO3512589","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active: No power issue, site is on grid With=
 Ubaie=3D53V,  Gregoire (654547479) from Huawei is informedSites impacted b=
y Mbandjock CTR_030 which is not managed by IHS","system","268576","16-11-2=
024 06:02:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003594363","Nguila",=
"","16-11-2024 06:02:50","16-11-2024 05:25:18","16-11-2024 05:30:12","Casca=
ded Incident from TTO3512589","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active: No power issue, site is on grid Wit=
h Ubaie=3D53V,  Gregoire (654547479) from Huawei is informedSites impacted =
by Mbandjock CTR_030 which is not managed by IHS","system","268577","16-11-=
2024 06:02:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0003594289","D=
ong","IHS_YND_433, IHS_YND_592, IHS_YND_431, IHS_YND_443, IHS_YND_432, IHS_=
YND_434, IHS_YND_442","16-11-2024 05:45:43","16-11-2024 05:25:18","16-11-20=
24 05:30:12","Active: No power issue, site is on grid With Ubaie=3D53V,  Gr=
egoire (654547479) from Huawei is informedSites impacted by Mbandjock CTR_0=
30 which is not managed by IHS","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No powe=
r issue, site is on grid With Ubaie=3D53V,  Gregoire (654547479) from Huawe=
i is informedSites impacted by Mbandjock CTR_030 which is not managed by IH=
S","kombi.samuel@ihstowers.com","1226","16-11-2024 05:45:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003594015","Saa","",=
"16-11-2024 03:29:01","16-11-2024 02:53:07","16-11-2024 02:55:07","Incorrec=
tly logged tickets","Parker Tchoup","Incorrectly Logged Tickets","Error","E=
rror","Error","Incorrectly logged tickets","system","2154","16-11-2024 03:2=
9:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_409","NOCINC0003593738","Evodoula=
 OCM","","16-11-2024 01:51:24","16-11-2024 01:38:18","16-11-2024 01:39:18",=
"Cascaded Incident from TTO3511886","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","Site impacted by NKOG-EDZE=
N CTR_041 which is not under supervision of IHS","system","267747","16-11-2=
024 01:51:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_051","NOCINC0003593736","Nyanon",=
"","16-11-2024 01:51:24","16-11-2024 01:38:18","16-11-2024 01:39:18","Casca=
ded Incident from TTO3511886","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","Site impacted by NKOG-EDZEN CTR_=
041 which is not under supervision of IHS","system","267746","16-11-2024 01=
:51:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_393","NOCINC0003593737","Ezezang"=
,"","16-11-2024 01:51:24","16-11-2024 01:38:18","16-11-2024 01:39:18","Casc=
aded Incident from TTO3511886","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Site impacted by NKOG-EDZEN CTR_041 which =
is not under supervision of IHS","system","267747","16-11-2024 01:51:24","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0003593734","Monatele=
 MTN","","16-11-2024 01:51:24","16-11-2024 01:38:18","16-11-2024 01:39:18",=
"Cascaded Incident from TTO3511886","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Site impacted by NKOG-EDZEN CTR_041 w=
hich is not under supervision of IHS","system","267746","16-11-2024 01:51:2=
4","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0003593726","Okola OC=
M","","16-11-2024 01:51:22","16-11-2024 01:38:18","16-11-2024 01:39:18","Ca=
scaded Incident from TTO3511886","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Active","Cascade Active","Cascade Active","Site impacted by NKOG-EDZEN C=
TR_041 which is not under supervision of IHS","system","267743","16-11-2024=
 01:51:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003593727","Saa","",=
"16-11-2024 01:51:22","16-11-2024 01:38:18","16-11-2024 01:39:18","Cascaded=
 Incident from TTO3511886","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","Site impacted by NKOG-EDZEN CTR_041 which is n=
ot under supervision of IHS","system","267743","16-11-2024 01:51:22","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0003593725","Talla Mo=
natele","","16-11-2024 01:51:22","16-11-2024 01:38:18","16-11-2024 01:39:18=
","Cascaded Incident from TTO3511886","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","Site impacted by NKOG-EDZEN CTR_041=
 which is not under supervision of IHS","system","267743","16-11-2024 01:51=
:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003593681","T=
amtam Weekend","","16-11-2024 01:29:47","16-11-2024 01:26:13","16-11-2024 0=
6:00:42","Site went down due to rectifiers insufficiency 05 on site //He ad=
ded 01 rectifiers,site on Grid","Hyemafo Gildas","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to rectifiers insuffi=
ciency 05 on site //He added 01 rectifiers,site on Grid","emmanuel.ghani@ih=
stowers.com","215","16-11-2024 01:29:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003593668","D=
amas","","16-11-2024 01:28:10","16-11-2024 01:25:39","16-11-2024 06:03:10",=
"Access issue during the night  grid outage, site went down because Gen fai=
led to start // Grid power return (investigation ongoing)","MINKA NICOLAS",=
"Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue - =
Land Lord","Access issue during the night  grid outage, site went down beca=
use Gen failed to start // Grid power return (investigation ongoing)","emma=
nuel.ghani@ihstowers.com","152","16-11-2024 01:28:10","Sagemcom CMR"
"Cancelled","Warning","T1477","IHS_YND_674","NOCINC0003593575","Mfou EPC","=
","16-11-2024 00:56:16","","","","Mba Lazare Herve","","","","","","christi=
an.fonkou@ihstowers.com","126","16-11-2024 00:56:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003593506","A=
fanoya","","16-11-2024 00:30:55","15-11-2024 23:00:45","16-11-2024 01:05:25=
","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FME Georges 6=
97461814 from Huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site , Ubaie=3D54.4V site On Grid The Tx FME Georges 697461814 from H=
uawei is informed","kombi.samuel@ihstowers.com","5411","16-11-2024 00:30:55=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003593401","N=
yom OCM","","16-11-2024 00:01:14","15-11-2024 23:56:00","16-11-2024 00:06:4=
7","No power issue site on grid with U=3D54,7v Symphorien(691316854) from H=
uawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gri=
d with U=3D54,7v Symphorien(691316854) from Huawei is informed","emmanuel.g=
hani@ihstowers.com","316","16-11-2024 00:01:14","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003592830","Mes=
sa Carriere","","15-11-2024 21:44:15","15-11-2024 21:31:11","15-11-2024 22:=
43:05","Gri fluctuation, site went down because gen start and stopped due t=
o grid bad voltage // He bypass grid and manually start the gen","Mboua Thi=
erry","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Gri fluctuation, site went down because gen start and stopped due to g=
rid bad voltage // He bypass grid and manually start the gen","rouselle.sch=
oune@ihstowers.com","785","15-11-2024 21:44:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0003592808","C=
-Supreme","","15-11-2024 21:42:12","14-11-2024 13:28:01","14-11-2024 22:40:=
01","No power issue on site U=3D54,5v site on grid Rm Alain of huawei is in=
formed","","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","No power issue on site U=3D54,5v site on grid Rm Ala=
in of huawei is informed","denis.mballa@ihstowers.com","116403","15-11-2024=
 21:42:12","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0003592697","NKO=
LOSSAN OKOK","","15-11-2024 21:18:25","15-11-2024 21:15:20","15-11-2024 22:=
29:53","site went down because 2 Rectifiers dysfuntionning // He reset thes=
e  rectifiers","Parker Tchoup","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","site went down because 2 Rectifiers dysfuntionning // He r=
eset these  rectifiers","rouselle.schoune@ihstowers.com","186","15-11-2024 =
21:18:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003592548","N=
yom OCM","","15-11-2024 20:57:34","15-11-2024 20:54:21","15-11-2024 20:56:2=
1","No power issue site on grid with U=3D54,7v Symphorien(691316854) from H=
uawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gri=
d with U=3D54,7v Symphorien(691316854) from Huawei is informed","denis.mbal=
la@ihstowers.com","194","15-11-2024 20:57:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003592508","Messassi=
 okolo","","15-11-2024 20:51:41","15-11-2024 20:32:03","15-11-2024 20:35:24=
","Cascaded Incident from TTO3510398","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active// No power issue, Site on =
Grid Ubai=3D 53.4V, The FME Synphorien/691316854/ From Huawei is informed. =
Notice that we have disjunction at BTS OCM","system","271807","15-11-2024 2=
0:51:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003592507","Emana Ly=
cee","","15-11-2024 20:51:41","15-11-2024 20:32:03","15-11-2024 20:35:24","=
Cascaded Incident from TTO3510398","Fabrice Pouakam","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active// No power issue, Site on Gri=
d Ubai=3D 53.4V, The FME Synphorien/691316854/ From Huawei is informed. Not=
ice that we have disjunction at BTS OCM","system","271807","15-11-2024 20:5=
1:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003592505","Mballa 4=
","","15-11-2024 20:51:40","15-11-2024 20:32:03","15-11-2024 20:35:24","Cas=
caded Incident from TTO3510398","Delor Telezing","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active// No power issue, Site on Grid Ub=
ai=3D 53.4V, The FME Synphorien/691316854/ From Huawei is informed. Notice =
that we have disjunction at BTS OCM","system","271807","15-11-2024 20:51:40=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003592506","EMANA BI=
LICK CITY","","15-11-2024 20:51:40","15-11-2024 20:32:03","15-11-2024 20:35=
:24","Cascaded Incident from TTO3510398","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active// No power issue, Site =
on Grid Ubai=3D 53.4V, The FME Synphorien/691316854/ From Huawei is informe=
d. Notice that we have disjunction at BTS OCM","system","271806","15-11-202=
4 20:51:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003592494","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279","15-11-2024 20:5=
0:13","15-11-2024 20:32:03","15-11-2024 22:30:24","Active// No power issue,=
 Site on Grid Ubai=3D 53.4V, The TX FME Synphorien/691316854/ From Huawei i=
s informed. Notice that we have disjunction at BTS OCM","Fabrice Pouakam","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active// No power issue, Site on Grid Ubai=3D 53.4V, The TX FME =
Synphorien/691316854/ From Huawei is informed. Notice that we have disjunct=
ion at BTS OCM","denis.mballa@ihstowers.com","1091","15-11-2024 20:50:13","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0003592475","Abang","=
","15-11-2024 20:48:11","15-11-2024 20:19:46","15-11-2024 20:23:46","Cascad=
ed Incident from TTO3510364","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// No power Issue on site, Site on =
Grid Ubai: 50.5V, The Fme Eloundou/652586578/From Huawei is informed. Notic=
e that we have disjunction at BTS OCM","system","265255","15-11-2024 20:48:=
11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003592464","M=
imboman-Village","IHS_YND_290","15-11-2024 20:46:59","15-11-2024 20:19:46",=
"15-11-2024 20:23:46","Active// No power Issue on site, Site on Grid Ubai: =
50.5V, The Fme Eloundou/652586578/From Huawei is informed. Notice that we h=
ave disjunction at BTS OCM","Mba Lazare Herve","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No powe=
r Issue on site, Site on Grid Ubai: 50.5V, The Fme Eloundou/652586578/From =
Huawei is informed. Notice that we have disjunction at BTS OCM","denis.mbal=
la@ihstowers.com","1635","15-11-2024 20:46:59","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003591710","NYO=
M FACE MAETUR","","15-11-2024 18:39:43","15-11-2024 18:27:59","15-11-2024 1=
8:59:46","Grid Outage Site went down due to landlord has forbiden to start =
the Gen// Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Emergency Stop","Grid Outage Site went down due to landlord h=
as forbiden to start the Gen// Grid return","rouselle.schoune@ihstowers.com=
","705","15-11-2024 18:39:43","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003591156","OBA=
M NGOLA OCM","","15-11-2024 17:09:29","15-11-2024 17:05:23","15-11-2024 17:=
11:23","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // voltage stabilized","MINKA NICOLAS","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,=
 site went down because gen start and stopped due to grid bad voltage // vo=
ltage stabilized","rouselle.schoune@ihstowers.com","247","15-11-2024 17:09:=
29","Sagemcom CMR"
"Closed Complete","Warning","T1551","IHS_YND_316","NOCINC0003591135","Akak-=
Nkozoa-MTN-IHS","","15-11-2024 17:05:28","","","Grid fluctuation, Site alar=
ming on Battery because Gen started and stopped due to Grid bad voltage// H=
e bypassed Grid and started Gen manualy","Fabrice Pouakam","Warning","Warni=
ng","POWER","Warning - Site on Battery","Grid fluctuation, Site alarming on=
 Battery because Gen started and stopped due to Grid bad voltage// He bypas=
sed Grid and started Gen manualy","alwine.fambou@ihstowers.com","3","15-11-=
2024 17:05:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003590909","A=
fanoya","","15-11-2024 16:25:02","15-11-2024 16:16:51","15-11-2024 16:28:51=
","No power issue on site , Ubaie=3D54.4V site On Grid The Tx FME Georges 6=
97461814 from Huawei is informed.","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site , Ubaie=3D54.4V site On Grid The Tx FME Georges 697461814 from =
Huawei is informed.","denis.mballa@ihstowers.com","555","15-11-2024 16:25:0=
2","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003589589","Ole=
mbe MTN","","15-11-2024 13:49:12","15-11-2024 13:48:02","15-11-2024 13:50:2=
6","Grid fluctuation, site went down because Gen started and stopped due to=
 Grid bad voltage no rcp on site// Grid stabilized","Fabrice Pouakam","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid f=
luctuation, site went down because Gen started and stopped due to Grid bad =
voltage no rcp on site// Grid stabilized","olivier.kwedi@ihstowers.com","71=
","15-11-2024 13:49:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003588397","O=
lembe-Terminus","","15-11-2024 10:50:02","15-11-2024 10:41:50","15-11-2024 =
12:13:45","Tx Issue : Site on Grid ,Ubaie:54.2V; Symphorien Huawei is infor=
med( Disjunction in the BTS OCM.)","Fabrice Pouakam","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Tx Issue :=
 Site on Grid ,Ubaie:54.2V; Symphorien Huawei is informed( Disjunction in t=
he BTS OCM.)","ludivine.ngamaleu@ihstowers.com","493","15-11-2024 10:50:02"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0003588047","Nomayos-=
IHS","","15-11-2024 09:54:31","15-11-2024 09:34:26","15-11-2024 09:51:08","=
Cascaded Incident from TTO3504940","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site went down because gen failed to =
start due to grid bad voltage // Gen manually started","system","1205","15-=
11-2024 09:54:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0003588046","Nkolfon =
Cimencam","","15-11-2024 09:54:30","15-11-2024 09:34:26","15-11-2024 09:51:=
08","Cascaded Incident from TTO3504940","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because gen fa=
iled to start due to grid bad voltage // Gen manually started","system","26=
8318","15-11-2024 09:54:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0003588045","Bondjock=
","","15-11-2024 09:54:30","15-11-2024 09:34:26","15-11-2024 09:51:08","Cas=
caded Incident from TTO3504940","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site went down because gen failed to sta=
rt due to grid bad voltage // Gen manually started","system","1204","15-11-=
2024 09:54:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0003588044","Nomayos =
montee Meche","","15-11-2024 09:54:30","15-11-2024 09:34:26","15-11-2024 09=
:51:08","Cascaded Incident from TTO3504940","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","site went down because gen f=
ailed to start due to grid bad voltage // Gen manually started","system","1=
204","15-11-2024 09:54:30","Sagemcom CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0003588006","OKO=
A Peage","","15-11-2024 09:50:43","15-11-2024 09:34:26","15-11-2024 09:51:0=
8","Please Cascade it behind Sous -Prefecture.","Fanda Brice","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","site went down because g=
en failed to start due to grid bad voltage // Gen manually started","olivie=
r.kwedi@ihstowers.com","7108","15-11-2024 09:50:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003587801","S=
ous Prefecture","IHS_YND_330, IHS_YND_791, IHS_YND_372, IHS_YND_762, IHS_YN=
D_697","15-11-2024 09:35:21","15-11-2024 09:28:16","15-11-2024 10:01:27","s=
ite went down because gen failed to start due to grid bad voltage // Gen ma=
nually started","Fanda Brice","Grid Supply","Passive","Grid","National Grid=
 - Phase Controller Faulty","site went down because gen failed to start due=
 to grid bad voltage // Gen manually started","ludivine.ngamaleu@ihstowers.=
com","426","15-11-2024 09:35:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003587719","Boumnyeb=
el","","15-11-2024 09:29:55","15-11-2024 08:45:41","15-11-2024 08:50:19","C=
ascaded Incident from TTO3504556","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active: no power issue, site is on gr=
id with Ubaie=3D53V, Lucien (697391563) from Huawei is informed, site impac=
ted sikoum fme tx lucien working on site","system","271218","15-11-2024 09:=
29:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0003587709","Ngoung",=
"","15-11-2024 09:29:52","15-11-2024 08:45:41","15-11-2024 08:50:19","Casca=
ded Incident from TTO3504556","Kemeni Franklin","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active: no power issue, site is on grid w=
ith Ubaie=3D53V, Lucien (697391563) from Huawei is informed, site impacted =
sikoum fme tx lucien working on site","system","271240","15-11-2024 09:29:5=
2","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_416","NOCINC0003587702","Ngwopi B=
oga","","15-11-2024 09:29:51","15-11-2024 08:45:41","15-11-2024 08:50:19","=
Cascaded Incident from TTO3504556","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active: no power issue, site is on g=
rid with Ubaie=3D53V, Lucien (697391563) from Huawei is informed, site impa=
cted sikoum fme tx lucien working on site","system","271239","15-11-2024 09=
:29:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003587703","Mamb",""=
,"15-11-2024 09:29:51","15-11-2024 08:45:41","15-11-2024 08:50:19","Cascade=
d Incident from TTO3504556","Kemeni Franklin","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active: no power issue, site is on grid wit=
h Ubaie=3D53V, Lucien (697391563) from Huawei is informed, site impacted si=
koum fme tx lucien working on site","system","271233","15-11-2024 09:29:51"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003587483","O=
lembe","","15-11-2024 08:45:32","15-11-2024 08:42:26","15-11-2024 09:17:32"=
,"Site on DG due to grid outage,DG stopped due to ACDG control panel alarmi=
ng (DG control panel dysfunctioning//Reset DG card,and manually star of DG(=
Investigations ongoing).","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Site on DG due to grid outage,DG stopped d=
ue to ACDG control panel alarming (DG control panel dysfunctioning//Reset D=
G card,and manually star of DG(Investigations ongoing).","ludivine.ngamaleu=
@ihstowers.com","187","15-11-2024 08:45:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003587442","A=
fanoya","","15-11-2024 08:35:46","15-11-2024 08:27:41","15-11-2024 08:32:48=
","No power issue on site , Ubaie=3D54.4V site On Grid  The Tx FME Georges =
697461814 from Huawei is informed.","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site , Ubaie=3D54.4V site On Grid  The Tx FME Georges 697461814 fro=
m Huawei is informed.","ludivine.ngamaleu@ihstowers.com","487","15-11-2024 =
08:35:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0003587389","Awae Esc=
alier","","15-11-2024 08:29:51","15-11-2024 08:27:44","15-11-2024 09:26:58"=
,"Cascaded Incident from TTO3504405","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to rectifiers =
insufficiency //He added 02 Rectifiers,site on Grid.","system","272111","15=
-11-2024 08:29:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0003587388","Awae Ewo=
nkan","","15-11-2024 08:29:50","15-11-2024 08:27:44","15-11-2024 09:26:58",=
"Cascaded Incident from TTO3504405","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to rectifiers i=
nsufficiency //He added 02 Rectifiers,site on Grid.","system","272111","15-=
11-2024 08:29:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0003587384","A=
wae-Yde","IHS_YND_535, IHS_YND_171","15-11-2024 08:28:50","15-11-2024 08:27=
:44","15-11-2024 09:26:58","Site went down due to rectifiers insufficiency =
03/05 //He added 02 rectifiers,site on Grid.","Albran Byorel","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","Site went down due to recti=
fiers insufficiency //He added 02 Rectifiers,site on Grid.","ludivine.ngama=
leu@ihstowers.com","67","15-11-2024 08:28:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003587135","N=
yom OCM","","15-11-2024 08:01:37","15-11-2024 07:52:26","15-11-2024 10:09:1=
6","No power issue site on grid with U=3D54,7v Symphorien(691316854) from H=
uawei is informed.","Fabrice Pouakam","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gr=
id with U=3D54,7v Symphorien(691316854) from Huawei is informed.
","ludivine.ngamaleu@ihstowers.com","552","15-11-2024 08:01:37","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003587074","N=
kozoa","","15-11-2024 07:48:13","15-11-2024 07:40:19","15-11-2024 09:24:42"=
,"Grid outage, site went down due to gen overload (30KVA, 370A) // grid ret=
urn","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Over=
load","Grid outage, site went down due to gen overload (30KVA, 370A) // gri=
d return","ludivine.ngamaleu@ihstowers.com","475","15-11-2024 07:48:13","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003586992","Sim=
bock MTN","","15-11-2024 07:27:09","15-11-2024 07:17:59","15-11-2024 08:19:=
23","Active: No power issue, site is on grid with Ubaie=3D53V, George(69746=
1814)  from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power =
issue, site is on grid with Ubaie=3D53V, George(697461814)  from Huawei is =
informed","olivier.kwedi@ihstowers.com","551","15-11-2024 07:27:09","Sagemc=
om CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003586845","NTU=
I TOWN","","15-11-2024 06:54:08","15-11-2024 06:46:59","15-11-2024 10:47:22=
","Site on DG due to grid outage,Dg stopped due to high temp in the radiato=
,water mixed with oil  (ACDG pellet perforated)//He reduced oil,added water=
 and started DG.","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","=
ACDG - High Engine Temp - Coolant Level Issue","Site on DG due to grid outa=
ge,Dg stopped due to high temp in the radiator,water mixed with oil caused =
by (ACDG pellet perforated)//He reduced oil,added water and started DG.","o=
livier.kwedi@ihstowers.com","430","15-11-2024 06:54:08","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003586538","Ako=
no","","15-11-2024 05:53:17","15-11-2024 05:35:11","15-11-2024 06:21:03","G=
rid Outage, site went down because Gen stopped with ""high temp"" alarm// H=
e added water and started Gen manual","Fanda Brice","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid Outa=
ge, site went down because Gen stopped with ""high temp"" alarm// He added =
water and started Gen manual","landry.etame@ihstowers.com","1087","15-11-20=
24 05:53:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0003586507","OLAMA","=
","15-11-2024 05:45:20","15-11-2024 05:18:26","15-11-2024 06:16:56","Cascad=
ed Incident from TTO3503287 - Cascade Removed From TTO3503287","Fanda Brice=
","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid Outa=
ge, site went down because Gen stopped with ""high temp"" alarm// He added =
water and started Gen manual","system","1614","15-11-2024 05:45:20","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003586489","A=
fanoya","","15-11-2024 05:39:02","15-11-2024 05:26:56","15-11-2024 08:22:43=
","No power issue on site , Ubaie=3D54.4V site On Grid  The Tx FME Georges =
697461814 from Huawei is informed.","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue on site , Ubaie=3D54.4V site On Grid  The Tx FME Georges 697461814 fro=
m Huawei is informed.","stephane.nkamwa@ihstowers.com","727","15-11-2024 05=
:39:02","Sagemcom CMR"
"Cancelled","Warning","CTR_237","IHS_YND_261","NOCINC0003586343","Barriere"=
,"","15-11-2024 04:58:20","","","","Hyemafo Gildas","","","","","","stephan=
e.nkamwa@ihstowers.com","1576","15-11-2024 04:58:20","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003586340","Lad=
a I Yde","","15-11-2024 04:55:08","15-11-2024 04:50:02","15-11-2024 06:42:2=
9","grid outage, site went down because gen failed to start due to disjunct=
ion CB of gen // He reamed CB of gen and gen manually started","Mba Lazare =
Herve","Equipment Repair","Passive","Control Panel","Power Cabinet - Circui=
t Breaker Issue","grid outage, site went down because gen failed to start d=
ue to disjunction CB of gen // He reamed CB of gen and gen manually started=
","landry.etame@ihstowers.com","307","15-11-2024 04:55:08","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003586309","Bit=
oto","","15-11-2024 04:37:02","15-11-2024 04:34:56","15-11-2024 05:31:04","=
Grid outage site went down because Gen overload (20Kva; 315A) // He reduice=
 the Load and Manaully Started the Gen","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down becau=
se Gen overload (20Kva; 315A) // He reduice the Load and Manaully Started t=
he Gen","landry.etame@ihstowers.com","127","15-11-2024 04:37:02","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003586230","M=
arche Odza","","15-11-2024 04:16:00","15-11-2024 03:19:39","15-11-2024 08:1=
1:41","Active//NO power issue, site on Grid with U=3D54.5 V ,the TX Lionel =
steve /655184876/  is informed","Albran Byorel","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//NO powe=
r issue, site on Grid with U=3D54.5 V ,the TX Lionel steve /655184876/  is =
informed","stephane.nkamwa@ihstowers.com","3383","15-11-2024 04:16:00","Sag=
emcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003586097","NTU=
I TOWN","","15-11-2024 03:33:54","15-11-2024 03:29:49","15-11-2024 04:45:02=
","Grid outage, Site went down because Gen ran until fuel shortage// Grid R=
estored","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, Site went down because Gen ran until fuel shortage// Grid Rest=
ored","landry.etame@ihstowers.com","246","15-11-2024 03:33:54","Sagemcom CM=
R"
"Closed Complete","Warning","T0466","IHS_YND_151","NOCINC0003585562","Tamta=
m Weekend","","15-11-2024 00:57:55","","","grid Bad Voltage and Gen failed =
to Start //Grid Stabilized","Hyemafo Gildas","Warning","Warning","POWER","W=
arning - Battery Low Voltage","grid Bad Voltage and Gen failed to Start //G=
rid Stabilized","landry.etame@ihstowers.com","2","15-11-2024 00:57:55","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003585504","Akak-Nko=
zoa-MTN-IHS","","15-11-2024 00:40:40","15-11-2024 00:11:00","15-11-2024 01:=
05:06","Cascaded Incident from TTO3502138","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage, site down du=
e to Gen overload caused by  Huawei controller faulty// we isolated the bat=
teries and started the GE ","system","1251513","15-11-2024 00:40:40","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003585355","Akak-Nko=
zoa-MTN-IHS","","14-11-2024 23:41:30","14-11-2024 23:31:08","14-11-2024 23:=
52:30","Cascaded Incident from TTO3501941","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","GEN overlead    //    Gri=
d Return","system","268264","14-11-2024 23:41:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003585270","N=
yom OCM","","14-11-2024 23:22:24","14-11-2024 23:10:19","14-11-2024 23:10:2=
0","Active//No power issue site on grid with U=3D54,7v Symphorien(691316854=
) from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
ssue site on grid with U=3D54,7v Symphorien(691316854) from Huawei is infor=
med","stephane.nkamwa@ihstowers.com","726","14-11-2024 23:22:24","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003585217","B=
arriere","","14-11-2024 23:11:17","14-11-2024 22:50:11","15-11-2024 00:11:5=
0","Grid outage.Gen failed to start due to Battery GE faulty // Grid Restor=
ed","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Battery","Grid outage.Gen failed to start due to Battery GE faulty // G=
rid Restored","stephane.nkamwa@ihstowers.com","1267","14-11-2024 23:11:17",=
"Sagemcom CMR"
"Cancelled","Warning","T1565","IHS_YND_261","NOCINC0003584988","Barriere","=
","14-11-2024 22:12:47","","","","Hyemafo Gildas","","","","","","landry.et=
ame@ihstowers.com","184","14-11-2024 22:12:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003584796","Akak-Nko=
zoa-MTN-IHS","","14-11-2024 21:40:50","14-11-2024 21:37:11","14-11-2024 21:=
41:10","Cascaded Incident from TTO3501232","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive"," GEN overlead    //  Grid=
 Return","system","268025","14-11-2024 21:40:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003584742","N=
yom OCM","","14-11-2024 21:34:36","14-11-2024 21:26:32","14-11-2024 21:50:1=
8","No power issue site on grid with U=3D54,7v Symphorien(691316854) from H=
uawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gri=
d with U=3D54,7v Symphorien(691316854) from Huawei is informed","emmanuel.g=
hani@ihstowers.com","486","14-11-2024 21:34:36","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003583280","Sim=
bock MTN","","14-11-2024 17:37:46","14-11-2024 17:29:40","14-11-2024 18:30:=
49","No power issue on site, Site on Grid UBAIE=3D54.5V THE FME tx George (=
697461814) From huawei is informed","Fanda Brice","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site, Site on Grid UBAIE=3D54.5V THE FME tx George (697461814) From hu=
awei is informed","christian.fonkou@ihstowers.com","487","14-11-2024 17:37:=
46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_409","NOCINC0003581837","Evodoula=
 OCM","","14-11-2024 13:51:21","14-11-2024 13:41:00","14-11-2024 14:35:35",=
"Cascaded Incident from TTO3497689","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D53,8v site on grid Gregoire 654547479 of Huawei is informed","system","6=
21","14-11-2024 13:51:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0003581836","Monatele=
 MTN","","14-11-2024 13:51:20","14-11-2024 13:41:00","14-11-2024 14:35:35",=
"Cascaded Incident from TTO3497689","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D53,8v site=
 on grid Gregoire 654547479 of Huawei is informed","system","620","14-11-20=
24 13:51:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0003581835","Talla Mo=
natele","","14-11-2024 13:51:20","14-11-2024 13:41:00","14-11-2024 14:35:35=
","Cascaded Incident from TTO3497689","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue on site U=3D53,8v si=
te on grid Gregoire 654547479 of Huawei is informed","system","620","14-11-=
2024 13:51:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_073","IHS_YND_406","NOCINC0003581824","M=
onatele","IHS_YND_387, IHS_YND_407, IHS_YND_409","14-11-2024 13:50:11","14-=
11-2024 13:41:00","14-11-2024 17:10:35","No power issue on site U=3D53,8v s=
ite on grid Gregoire 654547479 of Huawei is informed","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site U=3D53,8v site on grid Gregoire 654547479 of =
Huawei is informed","denis.mballa@ihstowers.com","552","14-11-2024 13:50:11=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0003581705","A=
cropole","","14-11-2024 13:29:21","14-11-2024 09:20:03","14-11-2024 10:26:5=
1","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Site went down due to CB(125A) burn in PWC// He replaced it by a=
nother CB(125A)","denis.mballa@ihstowers.com","18116","14-11-2024 13:29:21"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003581686","MEHANDAN=
","","14-11-2024 13:26:20","14-11-2024 13:17:01","14-11-2024 14:06:56","Cas=
caded Incident from TTO3497509","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Technician Albran/657108542/SAGEMCOM w=
orking on site ""second start 48 V in PWC ","system","559","14-11-2024 13:2=
6:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003581672","O=
dza II OCM","IHS_YND_528","14-11-2024 13:25:07","14-11-2024 13:17:01","14-1=
1-2024 14:55:56","site went down due to work Albran/657108542/SAGEMCOM work=
ing on site ""second start 48 V in PWC //end of work","Albran Byorel","Inst=
allation Activity","Passive","Planned Activity","Installation Activity","si=
te went down due to work Albran/657108542/SAGEMCOM working on site ""second=
 start 48 V in PWC //end of work","denis.mballa@ihstowers.com","488","14-11=
-2024 13:25:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003581661","S=
tade-Abega","","14-11-2024 13:22:49","14-11-2024 13:07:18","14-11-2024 13:4=
8:03","grid outage,gen failed to start due to candle faulty//he started the=
 gen manually","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Kick Starter","grid outage,gen failed to start due to candle faulty/=
/he started the gen manually","denis.mballa@ihstowers.com","933","14-11-202=
4 13:22:49","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003580865","Tsi=
nga","","14-11-2024 11:28:24","14-11-2024 11:20:14","14-11-2024 11:44:49","=
Grid outage, Site went down before Gen start due to poor battery backup// G=
en started automatically","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befo=
re Gen start due to poor battery backup// Gen started automatically","olivi=
er.kwedi@ihstowers.com","492","14-11-2024 11:28:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003580593","A=
fanoya","","14-11-2024 10:48:14","14-11-2024 10:39:03","14-11-2024 10:45:42=
","No power issue site on grid with U=3D54,6v The FME TX Georges ( 69746181=
4) /From HUAWEI is informed","Hyemafo Gildas","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on grid with U=3D54,6v The FME TX Georges ( 697461814) /From HUAWEI is i=
nformed","denis.mballa@ihstowers.com","552","14-11-2024 10:48:14","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0003580028","M=
vog Mbi New","IHS_YND_036","14-11-2024 09:29:18","14-11-2024 09:20:03","14-=
11-2024 10:26:51","Site went down due to CB(125A) burn in PWC// He replaced=
 it by another CB(125A)","MINKA NICOLAS","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to C=
B(125A) burn in PWC// He replaced it by another CB(125A)","denis.mballa@ihs=
towers.com","556","14-11-2024 09:29:18","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003579500","Nsi=
meyong Terre Rouge","","14-11-2024 08:10:08","14-11-2024 08:01:00","14-11-2=
024 08:13:21","Grid outage, site went down before Gen start due to poor bac=
kup// Grid power return","MINKA NICOLAS","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e Gen start due to poor backup// Grid power return","olivier.kwedi@ihstower=
s.com","548","14-11-2024 08:10:08","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003579139","NTU=
I TOWN","","14-11-2024 06:39:58","14-11-2024 06:31:51","14-11-2024 07:28:12=
","grid outage, site went down because generator stopped due to high temper=
ature // He opened the generator flaps","Parker Tchoup","Equipment Repair",=
"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","grid =
outage, site went down because generator stoppen due to high temperature //=
 He opened the generator flaps","olivier.kwedi@ihstowers.com","488","14-11-=
2024 06:39:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0003578700","H-Franco=
 New","","14-11-2024 04:29:40","14-11-2024 04:19:59","14-11-2024 06:34:19",=
"Cascaded Incident from TTO3494077","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to ZTE ATS dis=
function// He bypassed ATS ZTE(investigation Ongoing), Site on Grid","syste=
m","581","14-11-2024 04:29:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0003578697","D=
joungolo","IHS_YND_711","14-11-2024 04:29:19","14-11-2024 04:19:59","14-11-=
2024 06:34:19","Site went down due to ZTE ATS disfunction// He bypassed ATS=
 ZTE(investigation Ongoing), Site on Grid","Mboua Thierry","Equipment Repai=
r","Passive","Control Panel","ATS-AMF Issue","Site went down due to ZTE ATS=
 disfunction// He bypassed ATS ZTE(investigation Ongoing), Site on Grid","a=
lexandre.kamal@ihstowers.com","560","14-11-2024 04:29:19","Sagemcom CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0003577535","Nya=
hoo","","13-11-2024 22:42:08","13-11-2024 22:33:57","13-11-2024 22:35:25","=
No power issue Ubaie=3D55.5V site on grid.  TX FME of HUAWEI GREGOIRE 65454=
7479 is inform.","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ubai=
e=3D55.5V site on grid.TX FME of HUAWEI GREGOIRE 654547479 is inform.
","kamga.virgile@ihstowers.com","492","13-11-2024 22:42:08","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003577086","NYO=
M FACE MAETUR","","13-11-2024 21:40:29","13-11-2024 21:21:24","15-11-2024 1=
6:30:06","Grid Outage Site went down due to landlord has forbiden to start =
the Gen// Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Emergency Stop","Grid Outage Site went down due to landlord h=
as forbiden to start the Gen// Grid return","landry.etame@ihstowers.com","1=
146","13-11-2024 21:40:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003576726","M=
ANGUIERS CHAPELLE","","13-11-2024 20:52:18","13-11-2024 20:23:07","13-11-20=
24 21:28:18","Grid outage site went down because Gen overload(20Kva; 330A)/=
/ he reduced the laod on site","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage site went down because Gen ove=
rload(20Kva; 330A)// he reduced the laod on site","stephane.nkamwa@ihstower=
s.com","1752","13-11-2024 20:52:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003576558","MBALNGON=
G LYCEE","","13-11-2024 20:34:30","13-11-2024 20:24:48","13-11-2024 20:32:1=
2","Cascaded Incident from TTO3491457","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation, site went down =
because gen start and stopped due to grid bad voltage// He bypassed Grid an=
d started Gen manualy","system","1214603","13-11-2024 20:34:30","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003576559","Afanoya"=
,"","13-11-2024 20:34:30","13-11-2024 20:24:48","13-11-2024 20:32:12","Casc=
aded Incident from TTO3491457","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se gen start and stopped due to grid bad voltage// He bypassed Grid and sta=
rted Gen manualy","system","265125","13-11-2024 20:34:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003576557","ELOUMDEM=
 CARRIERE","","13-11-2024 20:34:30","13-11-2024 20:24:48","13-11-2024 20:32=
:12","Cascaded Incident from TTO3491457","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation, site went dow=
n because gen start and stopped due to grid bad voltage// He bypassed Grid =
and started Gen manualy","system","265126","13-11-2024 20:34:30","Sagemcom =
CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003576550","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","13-11-2024 20:33:12","13-11-20=
24 20:24:48","13-11-2024 20:32:12","Grid fluctuation, site went down becaus=
e gen start and stopped due to grid bad voltage// He bypassed Grid and star=
ted Gen manualy","Hyemafo Gildas","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","Grid fluctuation, site went down because g=
en start and stopped due to grid bad voltage// He bypassed Grid and started=
 Gen manualy","landry.etame@ihstowers.com","506","13-11-2024 20:33:12","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003576440","M=
ANGUIERS CHAPELLE","","13-11-2024 20:09:26","13-11-2024 19:55:18","13-11-20=
24 20:09:47","Grid outage, Site went down before Gen start due to poor back=
up// Gen started automatically","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup// Gen started automatically","steph=
ane.nkamwa@ihstowers.com","849","13-11-2024 20:09:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003576430","E=
lig-Edzoa","","13-11-2024 20:06:56","13-11-2024 19:44:46","13-11-2024 22:34=
:32","Access issue due to landlord, grid outage // grid return","","Access =
Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lor=
d","Access issue due to landlord, grid outage // grid return","stephane.nka=
mwa@ihstowers.com","1331","13-11-2024 20:06:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003576057","Song-bon=
g","","13-11-2024 19:04:01","13-11-2024 13:54:47","13-11-2024 15:21:05","Ca=
scaded Incident from TTO3487530","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive",".Site went down due to card GE dysf=
unctionned causing by lightning // we reset card GE and gen manually starte=
d ","system","281484","13-11-2024 19:04:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003576055","Eseka To=
wn","","13-11-2024 19:04:00","13-11-2024 13:54:47","13-11-2024 15:21:05","C=
ascaded Incident from TTO3487530","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive",".Site went down due to card GE dys=
functionned causing by lightning // we reset card GE and gen manually start=
ed ","system","281480","13-11-2024 19:04:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0003576056","Eseka OC=
M","","13-11-2024 19:04:00","13-11-2024 13:54:47","13-11-2024 15:21:05","Ca=
scaded Incident from TTO3487530","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive",".Site went down due to card GE dysf=
unctionned causing by lightning // we reset card GE and gen manually starte=
d ","system","281486","13-11-2024 19:04:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003576037","Mamb",""=
,"13-11-2024 19:00:22","13-11-2024 13:54:47","13-11-2024 15:21:05","Cascade=
d Incident from TTO3487530","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive",".Site went down due to card GE dysfuncti=
onned causing by lightning // we reset card GE and gen manually started ","=
system","281482","13-11-2024 19:00:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003576035","Boumnyeb=
el","","13-11-2024 19:00:21","13-11-2024 13:54:47","13-11-2024 15:21:05","C=
ascaded Incident from TTO3487530","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive",".Site went down due to card GE dys=
functionned causing by lightning // we reset card GE and gen manually start=
ed ","system","281481","13-11-2024 19:00:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003576034","Ngog Map=
ubi","","13-11-2024 19:00:21","13-11-2024 13:54:47","13-11-2024 15:21:05","=
Cascaded Incident from TTO3487530","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive",".Site went down due to card GE dy=
sfunctionned causing by lightning // we reset card GE and gen manually star=
ted ","system","281481","13-11-2024 19:00:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003576032","Ndogbess=
ol","","13-11-2024 19:00:20","13-11-2024 13:54:47","13-11-2024 15:21:05","C=
ascaded Incident from TTO3487530","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive",".Site went down due to card GE dys=
functionned causing by lightning // we reset card GE and gen manually start=
ed ","system","281486","13-11-2024 19:00:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0003576031","Boumnyeb=
el OCM","","13-11-2024 19:00:20","13-11-2024 13:54:47","13-11-2024 15:21:05=
","Cascaded Incident from TTO3487530","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive",".Site went down due to card GE=
 dysfunctionned causing by lightning // we reset card GE and gen manually s=
tarted ","system","281480","13-11-2024 19:00:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003575701","M=
adison","IHS_YND_566","13-11-2024 18:06:32","13-11-2024 17:44:19","13-11-20=
24 18:56:44","Site went down Bbecause CB(125A) tripped in PWC who feeds equ=
ipments OCM// He did a bridge with another CB(125A)","MFOUAGUEGUE MATHIEU",=
"Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Break=
er Issue","Site went down Bbecause CB(125A) tripped in PWC who feeds equipm=
ents OCM// He did a bridge with another CB(125A)","stephane.nkamwa@ihstower=
s.com","1334","13-11-2024 18:06:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003575672","C=
rf Cornier","","13-11-2024 18:01:09","13-11-2024 17:44:19","13-11-2024 18:5=
6:44","Site went down Bbecause CB(125A) tripped in PWC who feeds equipments=
 OCM// He did a bridge with another CB(125A)","MINKA NICOLAS","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down Bbecause =
CB(125A) tripped in PWC who feeds equipments OCM// He did a bridge with ano=
ther CB(125A)","stephane.nkamwa@ihstowers.com","1394","13-11-2024 18:01:09"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0003574687","Bas=
tos Bethesda","","13-11-2024 15:49:22","13-11-2024 15:42:16","13-11-2024 15=
:50:40","Grid outage, site went down before gen start due to poor battery b=
ackup // gen start automaticaly","Mboua Thierry","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // gen start automaticaly","=
landry.etame@ihstowers.com","428","13-11-2024 15:49:22","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003574653","Mok=
olo Yaounde","","13-11-2024 15:47:22","13-11-2024 15:43:25","13-11-2024 15:=
51:46","Grid outage..no space to deploy mobile gen//Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage..n=
o space to deploy mobile gen//Grid return","landry.etame@ihstowers.com","23=
8","13-11-2024 15:47:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003574576","M=
ANGUIERS CHAPELLE","","13-11-2024 15:34:11","13-11-2024 15:24:31","13-11-20=
24 16:29:30","Site went down because CB(80A) tripped in PWC who feeds equip=
ments OCM// He did a bridge with another CB(63A)","Fabrice Pouakam","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issu=
e","Site went down because CB(80A) tripped in PWC who feeds equipments OCM/=
/ He did a bridge with another CB(63A)","stephane.nkamwa@ihstowers.com","58=
1","13-11-2024 15:34:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003574455","MEHANDAN=
","","13-11-2024 15:25:00","13-11-2024 14:53:17","13-11-2024 14:55:09","Cas=
caded Incident from TTO3488910","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue, site is on grid with Ubai=
e=3D53V, Lionel adjep(655184876) from Huawei is informed ","system","277809=
","13-11-2024 15:25:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003574429","O=
dza II OCM","IHS_YND_528","13-11-2024 15:22:41","13-11-2024 14:53:17","13-1=
1-2024 19:15:30","No power issue, site is on grid with Ubaie=3D53V, Lionel =
adjep(655184876) from Huawei is informed ","Albran Byorel","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue, site is on grid with Ubaie=3D53V, Lionel adjep(655184876) from =
Huawei is informed ","stephane.nkamwa@ihstowers.com","1766","13-11-2024 15:=
22:41","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003574010","Sap=
eur","","13-11-2024 14:57:54","13-11-2024 14:50:50","13-11-2024 15:14:16","=
Grid outage, site went down before gen start due to poor battery backup // =
Gen start automatically","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen start automatically","landry.=
etame@ihstowers.com","425","13-11-2024 14:57:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0003573193","Boga-Mah=
ole","","13-11-2024 14:04:23","13-11-2024 13:54:47","13-11-2024 15:21:05","=
Cascaded Incident from TTO3487530","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive",".Site went down due to card GE dy=
sfunctionned causing by lightning // we reset card GE and gen manually star=
ted ","system","281480","13-11-2024 14:04:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0003572820","S=
apeur","","13-11-2024 13:11:55","13-11-2024 13:05:51","13-11-2024 13:14:40"=
,"Grid outage, site went down before gen start due to poor batteries backup=
 // gen start automatically","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor batteries backup // gen start automatically","e=
mmanuel.ghani@ihstowers.com","365","13-11-2024 13:11:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0003572610","B=
arriere IHS","","13-11-2024 12:48:22","13-11-2024 12:44:09","13-11-2024 13:=
18:36","","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","grid outage,site down because gen oveloaded(4 batteries Lithium,=
15KVA, 180A)//balanced the load(A DG of 20kva to be installed)","emmanuel.g=
hani@ihstowers.com","255","13-11-2024 12:48:22","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_206","NOCINC0003572558","ARMP","","=
13-11-2024 12:41:42","","","Site alarming High Temp because compressor Airc=
on  losing efficiency//He replace compressor Aircon","Mboua Thierry","Warni=
ng","Warning","ENVIRONMENT","Warning - Aircon Compressor Faulty","Site alar=
ming High Temp because compressor Aircon  losing efficiency//He replace com=
pressor Aircon","joelle.ekessi@ihstowers.com","10","13-11-2024 12:41:42","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003572541","N=
komkana","","13-11-2024 12:39:48","13-11-2024 12:34:39","14-11-2024 07:30:3=
7","Grid outage.no space to deploy mobile gen// Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no spa=
ce to deploy mobile gen// Grid return","emmanuel.ghani@ihstowers.com","310"=
,"13-11-2024 12:39:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0003572406","A=
cropole","","13-11-2024 12:16:03","13-11-2024 12:09:56","13-11-2024 13:15:5=
6","No power issue on site U=3D54v site on grid Eloundou of huawei is infor=
med","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v site on gri=
d Eloundou of huawei is informed","emmanuel.ghani@ihstowers.com","368","13-=
11-2024 12:16:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0003572393","S=
apeur","","13-11-2024 12:14:06","13-11-2024 12:07:02","13-11-2024 12:18:29"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Grid power return","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before ge=
n start due to poor battery backup // Grid power return","emmanuel.ghani@ih=
stowers.com","426","13-11-2024 12:14:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003572269","Song-bon=
g","","13-11-2024 11:52:40","13-11-2024 11:47:35","13-11-2024 11:52:35","Ca=
scaded Incident from TTO3486503","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue site on gen with U=3D54=
.6v  FME Etienne/ 695033981/ from huawei is informed ","system","288933","1=
3-11-2024 11:52:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003572262","E=
seka OCM","IHS_YND_378, IHS_YND_453","13-11-2024 11:51:40","13-11-2024 11:4=
7:35","13-11-2024 11:52:35","No power issue site on gen with U=3D54.6v  FME=
 Etienne/ 695033981/ from huawei is informed ","Kemeni Franklin","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue site on gen with U=3D54.6v  FME Etienne/ 695033981/ from h=
uawei is informed ","emmanuel.ghani@ihstowers.com","246","13-11-2024 11:51:=
40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003572102","Ngog Map=
ubi","","13-11-2024 11:31:41","13-11-2024 11:27:18","13-11-2024 11:31:44","=
Cascaded Incident from TTO3486313","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D56v FME Etienne/ 695033981/ from huawei is informed","system","263","13-=
11-2024 11:31:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003572104","Mamb",""=
,"13-11-2024 11:31:41","13-11-2024 11:27:18","13-11-2024 11:31:44","Cascade=
d Incident from TTO3486313","Kemeni Franklin","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue site on grid with U=3D56v FM=
E Etienne/ 695033981/ from huawei is informed","system","290259","13-11-202=
4 11:31:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003572103","Boumnyeb=
el","","13-11-2024 11:31:41","13-11-2024 11:27:18","13-11-2024 11:31:44","C=
ascaded Incident from TTO3486313","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
56v FME Etienne/ 695033981/ from huawei is informed","system","290259","13-=
11-2024 11:31:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0003572096","B=
oumnyebel OCM","IHS_EDA_056, IHS_YND_419, IHS_YND_381, IHS_YND_376","13-11-=
2024 11:30:24","13-11-2024 11:27:18","13-11-2024 11:31:44","No power issue =
site on grid with U=3D56v FME Etienne/ 695033981/ from huawei is informed",=
"Kemeni Franklin","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","No power issue site on grid with U=3D56v FME =
Etienne/ 695033981/ from huawei is informed","emmanuel.ghani@ihstowers.com"=
,"187","13-11-2024 11:30:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003572053","Eseka To=
wn","","13-11-2024 11:23:02","13-11-2024 10:19:03","13-11-2024 11:52:35","C=
ascaded Incident from TTO3485817","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Grid outage, site went down before ge=
n start due to poor batteries backup // gen start automatically(site down b=
ecause is impacted by SOMBO MTN)","system","3839","13-11-2024 11:23:02","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0003572051","Eseka MT=
N","","13-11-2024 11:23:02","13-11-2024 10:19:03","13-11-2024 10:33:21","Ca=
scaded Incident from TTO3485817","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down before =
gen start due to poor batteries backup // gen start automatically(site down=
 because is impacted by SOMBO MTN)","system","3839","13-11-2024 11:23:02","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003572048","Ndogbess=
ol","","13-11-2024 11:23:01","13-11-2024 10:19:03","13-11-2024 11:31:44","C=
ascaded Incident from TTO3485817","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Grid outage, site went down before ge=
n start due to poor batteries backup // gen start automatically(site down b=
ecause is impacted by SOMBO MTN)","system","3838","13-11-2024 11:23:01","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_781","NOCINC0003572044","BIBOMDJI=
DJIEL","","13-11-2024 11:23:00","13-11-2024 10:19:03","13-11-2024 10:33:21"=
,"Cascaded Incident from TTO3485817","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor batteries backup // gen start automatically(site =
down because is impacted by SOMBO MTN)","system","3837","13-11-2024 11:23:0=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0003572003","B=
otmakak","IHS_EDA_101","13-11-2024 11:15:59","13-11-2024 11:11:53","13-11-2=
024 11:18:16","no power issue U=3D53,8V site on Gen. the TX FME Etienne/ 69=
5033981/ from huawei is informed","Kemeni Franklin","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power is=
sue U=3D53,8V site on Gen. the TX FME Etienne/ 695033981/ from huawei is in=
formed","emmanuel.ghani@ihstowers.com","247","13-11-2024 11:15:59","Sagemco=
m CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003571791","Lab=
oratoire  Meka","IHS_YND_193","13-11-2024 10:49:31","13-11-2024 10:44:25","=
13-11-2024 11:18:58","grid outage,no space to deploy a mobil gen//grid retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid outage,no space to deploy a mobil gen//grid return","christian.fonkou@=
ihstowers.com","307","13-11-2024 10:49:31","Sagemcom CMR"
"Closed Complete","Warning","T1161","IHS_YND_290","NOCINC0003571771","Abang=
","","13-11-2024 10:48:02","","","SITE On Battery due to grid outage//Gen s=
tarted","Mba Lazare Herve","Warning","Warning","POWER","Warning - Site on B=
attery","SITE On Battery due to grid outage//Gen started","kombi.samuel@ihs=
towers.com","4","13-11-2024 10:48:02","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003571770","Bas=
tos Ekoudou","","13-11-2024 10:47:53","13-11-2024 10:44:25","13-11-2024 11:=
18:58","grid outage,no space to deploy a mobil gen//grid return","Mboua Thi=
erry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","grid =
outage,no space to deploy a mobil gen//grid return","christian.fonkou@ihsto=
wers.com","454","13-11-2024 10:47:53","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_434","NOCINC0003571736","Donga","",=
"13-11-2024 10:45:21","","","Hybrid Gen: Site alarming on battery 49.1V (st=
art threshold 48.4V)// Gen started automatically","Parker Tchoup","Warning"=
,"Warning","POWER","Warning - Site on Battery","Hybrid Gen: Site alarming o=
n battery 49.1V (start threshold 48.4V)// Gen started automatically","joell=
e.ekessi@ihstowers.com","1","13-11-2024 10:45:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003571699","MEHANDAN=
","","13-11-2024 10:37:51","13-11-2024 10:31:10","13-11-2024 12:37:02","Cas=
caded Incident from TTO3485864","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site down due to dysfunctionning of ZT=
E controller//by passed Zte controller (Alphonse IHS is informed).","system=
","279204","13-11-2024 10:37:51","Sagemcom CMR"
"Closed Complete","Site Down","T1669","IHS_YND_195","NOCINC0003571697","chi=
na embassy yde","","13-11-2024 10:37:38","13-11-2024 10:35:32","13-11-2024 =
11:16:30","grid outage,no space to deploy a mobil gen//grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage=
,no space to deploy a mobil gen//grid return","christian.fonkou@ihstowers.c=
om","127","13-11-2024 10:37:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003571694","O=
dza II OCM","IHS_YND_528","13-11-2024 10:37:14","13-11-2024 10:31:10","13-1=
1-2024 12:37:02","","Albran Byorel","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","site down due to dysfunctionning of ZTE controller=
//by passed Zte controller (Alphonse IHS is informed).","emmanuel.ghani@ihs=
towers.com","365","13-11-2024 10:37:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0003571685","Angongo"=
,"","13-11-2024 10:36:21","13-11-2024 10:32:41","13-11-2024 10:52:41","Casc=
aded Incident from TTO3485850","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site U=3D49,6v site on bat=
tery Tx fme Etienne of huawei is informed","system","264773","13-11-2024 10=
:36:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_116","IHS_YND_339","NOCINC0003571682","E=
beba","IHS_YND_335","13-11-2024 10:35:48","13-11-2024 10:32:41","13-11-2024=
 10:52:41","No power issue on site U=3D49,6v site on battery Tx fme Etienne=
 of huawei is informed","Fanda Brice","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D49,6v site on battery Tx fme Etienne of huawei is informed","emmanuel.gh=
ani@ihstowers.com","188","13-11-2024 10:35:48","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0003571575","Men=
dong NB","","13-11-2024 10:22:36","13-11-2024 10:13:30","13-11-2024 13:35:4=
5","No power issue on site U=3D54v site on grid Hosiah of huawei is informe=
d","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site U=3D54v site on grid Hosiah of hua=
wei is informed","christian.fonkou@ihstowers.com","547","13-11-2024 10:22:3=
6","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003571552","MBIMBIM"=
,"","13-11-2024 10:20:01","13-11-2024 10:13:18","13-11-2024 12:14:00","Casc=
aded Incident from TTO3485695","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid meter disconnected, site went down=
 because gen ran untill fuel shortage // refueling done (Fuel manage by edo=
nd=E9)","system","272846","13-11-2024 10:20:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003571549","Matsari"=
,"","13-11-2024 10:20:00","13-11-2024 10:13:18","13-11-2024 12:14:00","Casc=
aded Incident from TTO3485695","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid meter disconnected, site went down=
 because gen ran untill fuel shortage // refueling done (Fuel manage by edo=
nd=E9)","system","272846","13-11-2024 10:20:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003571550","Ngouetou=
","","13-11-2024 10:20:00","13-11-2024 10:13:18","13-11-2024 12:14:00","Cas=
caded Incident from TTO3485695","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid meter disconnected, site went dow=
n because gen ran untill fuel shortage // refueling done (Fuel manage by ed=
ond=E9)","system","272846","13-11-2024 10:20:00","Sagemcom CMR"
"Closed Complete","Warning","CTR_063","IHS_YND_365","NOCINC0003571541","Ako=
no","","13-11-2024 10:19:14","","","grid outage,gen stopped with alarm high=
 temp//he added water in radiator","Fanda Brice","Warning","Warning","POWER=
","Warning - Site on Battery","grid outage,gen stopped with alarm high temp=
//he added water in radiator","joelle.ekessi@ihstowers.com","304","13-11-20=
24 10:19:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0003571539","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","13-11-2024 10:19:02","13-=
11-2024 10:13:18","13-11-2024 12:14:00","Grid meter disconnected, site went=
 down because gen ran until fuel shortage // refueling done (Fuel manage by=
 edond=E9)","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid meter disconnected, site went down because gen ran untill fuel shor=
tage // refueling done (Fuel manage by edond=E9)","emmanuel.ghani@ihstowers=
.com","345","13-11-2024 10:19:02","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003571459","Ako=
no","IHS_YND_687","13-11-2024 10:11:41","13-11-2024 10:02:34","13-11-2024 1=
0:04:34","grid outage,gen stopped with alarm high temp//he added water in r=
adiator","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - High=
 Engine Temp - Coolant Level Issue","grid outage,gen stopped with alarm hig=
h temp//he added water in radiator","christian.fonkou@ihstowers.com","2513"=
,"13-11-2024 10:11:41","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003571382","OLA=
MA","","13-11-2024 10:01:46","13-11-2024 10:02:34","13-11-2024 10:04:34","g=
rid outage,gen stopped with alarm high temp//he added water in radiator // =
CASCADED TTO3485607","Fanda Brice","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","grid outage,gen stopped with alarm high temp//he ad=
ded water in radiator","christian.fonkou@ihstowers.com","2514","13-11-2024 =
10:01:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003571326","A=
fanoya","","13-11-2024 09:53:03","13-11-2024 09:41:59","13-11-2024 10:55:59=
","No power issue on site U=3D54,6v site on grid Rm Alain of huawei is info=
rmed","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,6v site on=
 grid Rm Alain of huawei is informed","emmanuel.ghani@ihstowers.com","665",=
"13-11-2024 09:53:03","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003571265","Pha=
rmacie SION","","13-11-2024 09:44:56","13-11-2024 09:39:51","13-11-2024 09:=
49:51","Grid outage, site went down before gen start due to poor battery ba=
ckup // gen start automatically","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // gen start automatically","c=
hristian.fonkou@ihstowers.com","306","13-11-2024 09:44:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003571167","A=
hala","","13-11-2024 09:34:58","13-11-2024 09:32:53","13-11-2024 09:36:53",=
"Site went down due to work, Mathieu/656072537/ From Sagemcom is working on=
 site (PM) // End of work","Hyemafo Gildas","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to work, =
Mathieu/656072537/ From Sagemcom is working on site (PM) // End of work","e=
mmanuel.ghani@ihstowers.com","126","13-11-2024 09:34:58","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_010","NOCINC0003570977","CNR","","1=
3-11-2024 09:06:55","","","site on alarm due low fuel//refueling done","Mbo=
ua Thierry","Warning","Warning","POWER","Warning - Site on Battery","site o=
n alarm due low fuel//refueling done","joelle.ekessi@ihstowers.com","364","=
13-11-2024 09:06:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003570734","E=
bogo","","13-11-2024 08:18:17","13-11-2024 08:16:18","13-11-2024 08:18:49",=
"Grid outage, site went down before gen start due to poor battery backup //=
 gen start automaticaly","Siligap Boris","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // gen start automaticaly","emmanuel=
.ghani@ihstowers.com","120","13-11-2024 08:18:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003570675","M=
imboman-Ecole","","13-11-2024 08:12:33","13-11-2024 08:09:27","13-11-2024 0=
8:12:27","Grid outage, site went down before gen start due to poor batterie=
s backup // gen start automatically","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site =
went down before gen start due to poor batteries backup // gen start automa=
tically","emmanuel.ghani@ihstowers.com","187","13-11-2024 08:12:33","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003570584","E=
kounou","","13-11-2024 07:52:58","13-11-2024 07:49:35","13-11-2024 07:59:25=
","Grid outage, site went down before gen start due to poor battery backup =
// gen start automaticaly","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen start automaticaly","emmanu=
el.ghani@ihstowers.com","204","13-11-2024 07:52:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003570548","M=
fou EPC","","13-11-2024 07:43:35","13-11-2024 07:39:27","13-11-2024 08:54:5=
3","Gri fluctuation, site went down because gen start and stopped due to gr=
id bad voltage // He bypass grid and manually start the gen","Mba Lazare He=
rve","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Gri fluctuation, site went down because gen start and stopped due to gr=
id bad voltage // He bypass grid and manually start the gen","emmanuel.ghan=
i@ihstowers.com","249","13-11-2024 07:43:35","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003570545","NYO=
M FACE MAETUR","","13-11-2024 07:42:19","13-11-2024 06:02:11","13-11-2024 1=
6:46:27","Grid Outage Site went Down due to  landlord has forbiden to start=
 the Gen Because  the  Noise //Grid Restored","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid Outage Site went=
 Down due to  landlord has forbiden to start the Gen Because  the  Noise //=
Grid Restored","kombi.samuel@ihstowers.com","6009","13-11-2024 07:42:19","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003569975","Afanoya"=
,"","13-11-2024 05:42:41","13-11-2024 05:37:43","13-11-2024 08:05:43","Casc=
aded Incident from TTO3483925","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to disjunction of t=
he rectifier cb(50A) // CB put back on, site on grid","system","298","13-11=
-2024 05:42:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003569973","ELOUMDEM=
 CARRIERE","","13-11-2024 05:42:40","13-11-2024 05:37:43","13-11-2024 08:05=
:43","Cascaded Incident from TTO3483925","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to disjuncti=
on of the rectifier cb(50A) // CB put back on, site on grid","system","297"=
,"13-11-2024 05:42:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003569974","MBALNGON=
G LYCEE","","13-11-2024 05:42:40","13-11-2024 05:37:43","13-11-2024 08:05:4=
3","Cascaded Incident from TTO3483925","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to disjunction=
 of the rectifier cb(50A) // CB put back on, site on grid","system","297","=
13-11-2024 05:42:40","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003569966","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","13-11-2024 05:39:52","13-11-20=
24 05:37:43","13-11-2024 08:05:43","Site went down due to disjunction of th=
e rectifier cb(50A) // CB put back on, site on grid","Hyemafo Gildas","Equi=
pment Repair","Passive","Rectifier","Rectifier - Circuit Breaker","Site wen=
t down due to disjunction of the rectifier cb(50A) // CB put back on, site =
on grid","olivier.kwedi@ihstowers.com","130","13-11-2024 05:39:52","Sagemco=
m CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003569670","NYO=
M FACE MAETUR","","13-11-2024 03:49:39","13-11-2024 03:48:26","13-11-2024 0=
5:16:08","Grid outage, landlord has forbiden to start the gen due to noise =
// Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Emergency Stop","Grid outage, landlord has forbiden to start the gen=
 due to noise // Grid return","olivier.kwedi@ihstowers.com","73","13-11-202=
4 03:49:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003569652","MEHANDAN=
","","13-11-2024 03:37:21","13-11-2024 03:29:11","13-11-2024 08:03:11","Cas=
caded Incident from TTO3483535","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to ats disfunctionn=
ing // he bypass ats, site on Gen( Investigation ongoing)","system","283031=
","13-11-2024 03:37:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003569650","O=
dza II OCM","IHS_YND_528","13-11-2024 03:36:15","13-11-2024 03:29:11","13-1=
1-2024 08:03:11","Site went down due to ats disfunctionning // he bypass at=
s, site on Gen( Investigation ongoing)","Albran Byorel","Equipment Repair",=
"Passive","Control Panel","ATS-AMF Issue","Site went down due to ats disfun=
ctionning // he bypass ats, site on Gen( Investigation ongoing)","ludivine.=
ngamaleu@ihstowers.com","426","13-11-2024 03:36:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0003568696","E=
mana Lycee","","12-11-2024 23:23:33","12-11-2024 23:00:20","13-11-2024 01:1=
7:05","No power issue on site Ubaie=3D54.9 V, site on Gen  //  The TX Fme S=
ynphorien 691316854 of Huewai is informed","Fabrice Pouakam","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site Ubaie=3D54.9 V, site on Gen  //The TX Fme Synphorien 6=
91316854 of Huewai is informed","etienne.itondo@ihstowers.com","1394","12-1=
1-2024 23:23:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003568688","EMANA BI=
LICK CITY","","12-11-2024 23:21:41","12-11-2024 23:00:32","12-11-2024 23:14=
:07","Cascaded Incident from TTO3482290","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage site went down =
because Gen started and stopped with alarm Gen under voltage and poor backu=
p // He reset the Gen card and Gen manually started","system","277266","12-=
11-2024 23:21:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003568689","Messassi=
 okolo","","12-11-2024 23:21:41","12-11-2024 23:00:32","12-11-2024 23:14:07=
","Cascaded Incident from TTO3482290","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen started and stopped with alarm Gen under voltage and poor backup /=
/ He reset the Gen card and Gen manually started","system","277267","12-11-=
2024 23:21:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003568690","Emana ly=
cee 2","","12-11-2024 23:21:41","12-11-2024 23:00:32","12-11-2024 23:14:07"=
,"Cascaded Incident from TTO3482290","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen started and stopped with alarm Gen under voltage and poor backup //=
 He reset the Gen card and Gen manually started","system","277267","12-11-2=
024 23:21:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003568687","Mballa 4=
","","12-11-2024 23:21:41","12-11-2024 23:00:32","12-11-2024 23:14:07","Cas=
caded Incident from TTO3482290","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n started and stopped with alarm Gen under voltage and poor backup // He re=
set the Gen card and Gen manually started","system","1269","12-11-2024 23:2=
1:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003568627","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_279, IHS_YND_685","12-11-2024 23:0=
9:36","12-11-2024 23:00:32","12-11-2024 23:14:07","Grid outage site went do=
wn because Gen started and stopped with alarm Gen under voltage and poor ba=
ckup // He reset the Gen card and Gen manually started","Fabrice Pouakam","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage =
site went down because Gen started and stopped with alarm Gen under voltage=
 and poor backup // He reset the Gen card and Gen manually started","ludivi=
ne.ngamaleu@ihstowers.com","545","12-11-2024 23:09:36","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003568620","ODZ=
A CITE MBIA","","12-11-2024 23:06:25","12-11-2024 23:01:18","13-11-2024 00:=
16:26","Grid OUTAGE, site went down because gen fails to start due to ATS d=
isfunctionning // Grid power return","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down because=
 gen fails to start due to ATS disfunctionning // Grid power return","olivi=
er.kwedi@ihstowers.com","308","12-11-2024 23:06:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003568557","S=
tade-Abega","","12-11-2024 22:51:44","12-11-2024 22:35:38","13-11-2024 04:4=
8:28","Active//No power issue on site Ubaie=3D54.7V;  site on GridThe FME L=
eonel Steve/ 655184876/  Huawei is informed. Notice that Disjunction in the=
 BTS OCM ","Mba Lazare Herve","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site Ub=
aie=3D54.7V;  site on GridThe FME Leonel Steve/ 655184876/  Huawei is infor=
med. Notice that Disjunction in the BTS OCM ","ludivine.ngamaleu@ihstowers.=
com","967","12-11-2024 22:51:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0003568529","Mendong =
vallee","","12-11-2024 22:44:30","12-11-2024 22:21:22","13-11-2024 07:01:14=
","Cascaded Incident from TTO3482164","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Access issue during the Night","sy=
stem","301407","12-11-2024 22:44:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0003568530","Montee-J=
ouvence","","12-11-2024 22:44:30","12-11-2024 22:21:22","13-11-2024 07:01:1=
4","Cascaded Incident from TTO3482164","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Access issue during the Night"=
,"system","301407","12-11-2024 22:44:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0003568526","M=
endong","IHS_YND_692, IHS_YND_236","12-11-2024 22:43:27","12-11-2024 22:21:=
22","13-11-2024 07:01:14","Access issue during the Night; Site went down du=
e to disjunction of the rectifier cb // CB put back on, site on grid","Hyem=
afo Gildas","Access Denial","Lease Or Legal","Landlord Related Issues","Acc=
ess Issue - Land Lord","Access issue during the Night; Site went down due t=
o disjunction of the rectifier cb // CB put back on, site on grid","ludivin=
e.ngamaleu@ihstowers.com","1326","12-11-2024 22:43:27","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003568515","Nko=
lbisson usines des eaux 2","","12-11-2024 22:41:51","12-11-2024 22:33:41","=
12-11-2024 22:41:27","site down because gen fails to start due to grid bad =
voltages // Grid return","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","site down because gen fa=
ils to start due to grid bad voltages // Grid return","olivier.kwedi@ihstow=
ers.com","491","12-11-2024 22:41:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003568512","M=
efou-Assi","","12-11-2024 22:41:23","12-11-2024 22:13:15","13-11-2024 01:07=
:46","Active//No power issue on site ,Site on Gen  with Ubaie=3D53.3V   The=
 Tx fme synphorien/650257151 from huawei is informed. Notice that we have D=
isjunction at BTS OCM","Fanda Brice","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on =
site ,Site on Gen  with Ubaie=3D53.3V The Tx fme synphorien/650257151 from =
huawei is informed. Notice that we have Disjunction at BTS OCM
","ludivine.ngamaleu@ihstowers.com","1689","12-11-2024 22:41:23","Sagemcom =
CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0003568492","MVA=
N SACEL","","12-11-2024 22:36:04","12-11-2024 22:28:56","12-11-2024 22:46:5=
5","Grid outage, site went down before Gen start due to poor backup// Grid =
power return","MINKA NICOLAS","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, site went down before Gen start=
 due to poor backup// Grid power return","olivier.kwedi@ihstowers.com","429=
","12-11-2024 22:36:04","Sagemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0003568447","Mon=
tee-Jouvence-II","","12-11-2024 22:29:46","12-11-2024 22:26:34","12-11-2024=
 22:32:35","site went down due to PWC over load(12KW.280A) // Site stabiliz=
ed","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule Overloaded","site went down due to PWC over load(12KW.280A) // Site st=
abilized","olivier.kwedi@ihstowers.com","192","12-11-2024 22:29:46","Sagemc=
om CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0003568421","Eko=
mbitie","","12-11-2024 22:24:59","12-11-2024 22:14:51","12-11-2024 22:27:52=
","Grid outage site went down because Gen failed to start // Grid power ret=
urn(investigation ongoing)","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen f=
ailed to start // Grid power return(investigation ongoing)","olivier.kwedi@=
ihstowers.com","609","12-11-2024 22:24:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003568413","M=
vog-Manga","","12-11-2024 22:23:09","12-11-2024 22:06:00","12-11-2024 22:44=
:03","Grid fluctuation site went down because Gen failed to start due to Gr=
id bad voltage // Grid stabilized","Albran Byorel","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Grid fluctuation site wen=
t down because Gen failed to start due to Grid bad voltage // Grid stabiliz=
ed","ludivine.ngamaleu@ihstowers.com","1031","12-11-2024 22:23:09","Sagemco=
m CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003568408","Eko=
unou","","12-11-2024 22:21:56","12-11-2024 22:11:47","12-11-2024 22:22:44",=
"Grid outage, site went down before Gen start due to poor backup// Grid pow=
er return","Albran Byorel","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage, site went down before Gen start du=
e to poor backup// Grid power return","olivier.kwedi@ihstowers.com","610","=
12-11-2024 22:21:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0003568109","Mbankolo=
 petit paris","","12-11-2024 21:44:40","12-11-2024 21:06:58","12-11-2024 21=
:10:15","Cascaded Incident from TTO3481523","Mboua Thierry","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue site on grid w=
ith U=3D54.1V Mohamadou(691144435) from Huawei is informed","system","26261=
8","12-11-2024 21:44:40","Sagemcom CMR"
"Cancelled","Warning","T1491","IHS_YND_808","NOCINC0003568045","Mbankolo pe=
tit paris","","12-11-2024 21:33:00","","","","Mboua Thierry","","","","",""=
,"kamga.virgile@ihstowers.com","1581","12-11-2024 21:33:00","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0003568000","AFE=
ME NORD","IHS_YND_808","12-11-2024 21:27:10","12-11-2024 21:06:58","12-11-2=
024 21:10:15","No power issue site on grid with U=3D54.1V Mohamadou(6911444=
35) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on grid with U=3D54.1V Mohamadou(691144435) from Huawei is inf=
ormed","kamga.virgile@ihstowers.com","1213","12-11-2024 21:27:10","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003567922","D=
amas","","12-11-2024 21:15:13","12-11-2024 21:06:09","13-11-2024 07:08:09",=
"Active,NO power issue, site on grid with U=3D53V tx fme Lionel steve /6551=
84876 is informed","MINKA NICOLAS","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active,NO power issue, site =
on grid with U=3D53V tx fme Lionel steve /655184876 is informed","alexandre=
.kamal@ihstowers.com","545","12-11-2024 21:15:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003567727","M=
fou EPC","","12-11-2024 20:52:01","12-11-2024 20:41:59","12-11-2024 20:42:5=
7","No power issue site on grid with U=3D51.6v  The FME TX Georges ( 697461=
814) /From HUAWEI is informed","Mba Lazare Herve","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e site on grid with U=3D51.6v  The FME TX Georges ( 697461814) /From HUAWEI=
 is informed","alexandre.kamal@ihstowers.com","604","12-11-2024 20:52:01","=
Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003567715","Mvo=
g-Betsi","","12-11-2024 20:49:49","12-11-2024 20:41:40","12-11-2024 20:59:1=
3","site went down due to insuficiency of rectifiers // site stabilized","H=
yemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"site went down due to insuficiency of rectifiers // site stabilized","kamg=
a.virgile@ihstowers.com","490","12-11-2024 20:49:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003567344","A=
kak-Nkozoa-MTN-IHS","","12-11-2024 19:54:35","12-11-2024 19:38:26","12-11-2=
024 19:58:26","No power issue site on grid with U=3D5341v The FME TX George=
s ( 697461814) /From HUAWEI is informed","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue site on grid with U=3D5341v The FME TX Georges ( 697461814) /Fro=
m HUAWEI is informed","alexandre.kamal@ihstowers.com","971","12-11-2024 19:=
54:35","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003567299","Nko=
lbisson usines des eaux 2","","12-11-2024 19:47:24","12-11-2024 19:35:18","=
12-11-2024 20:47:02","site went down because gen failed to start due to gri=
d bad voltage and no RCP // We bypass grid and Gen manually started","TIENT=
CHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","site went down because gen failed to start due to grid =
bad voltage and no RCP // We bypass grid and Gen manually started","kamga.v=
irgile@ihstowers.com","727","12-11-2024 19:47:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003567184","M=
efou-Assi","","12-11-2024 19:32:43","12-11-2024 19:19:38","12-11-2024 19:20=
:27","Active//No power issue on site, Site on Grid UBAIE=3D53,3V Georges ( =
697461814) From huawei is informed. Notice that we have disjunction at BTS =
OCM","Fanda Brice","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active//No power issue on site, Site on Grid=
 UBAIE=3D53,3V Georges ( 697461814) From huawei is informed. Notice that we=
 have disjunction at BTS OCM","alexandre.kamal@ihstowers.com","786","12-11-=
2024 19:32:43","Sagemcom CMR"
"Closed Complete","Warning","T1161","IHS_YND_290","NOCINC0003566558","Abang=
","","12-11-2024 17:45:23","","","site on  Battery due to Grid Bad Voltage/=
/ he made the Bidge on the God Phase","Mba Lazare Herve","Warning","Warning=
","POWER","Warning - Site on Battery","site on  Battery due to Grid Bad Vol=
tage// he made the Bidge on the God Phase","ludovic.tchagna@ihstowers.com",=
"10","12-11-2024 17:45:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_356","IHS_YND_376","NOCINC0003566482","M=
amb","","12-11-2024 17:32:29","12-11-2024 17:16:23","12-11-2024 18:19:40","=
Grid outage.gen failed to start due to battery GE faulty //gen manually sta=
rted with external battery","Kemeni Franklin","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Generator Battery","Grid outage.gen failed to start due =
to battery GE faulty //gen manually started with external battery","alexand=
re.kamal@ihstowers.com","967","12-11-2024 17:32:29","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003566148","AWA=
E OCM","","12-11-2024 16:40:21","12-11-2024 16:35:10","12-11-2024 16:41:10"=
,"Active//No power issue on site, Site on Grid UBAIE=3D54.6V  and Geoges (6=
97461814) From huawei is informed and Site Up AT=3D04:41 PM","Mba Lazare He=
rve","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active//No power issue on site, Site on Grid UBAIE=3D54.6V=
  and Geoges (697461814) From huawei is informed and Site Up AT=3D04:41 PM"=
,"kamga.virgile@ihstowers.com","312","12-11-2024 16:40:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0003565605","M=
endong Maeture","","12-11-2024 15:17:46","12-11-2024 14:49:41","12-11-2024 =
14:50:41","Active// No power Issue Site on Grid Ubai =3D54,5V, The FME  The=
 TX FME Mbah Hosiah (674007438) is informed.","Hyemafo Gildas","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power Issue Site on Grid Ubai =3D54,5V, The FME  The TX FME Mba=
h Hosiah (674007438) is informed.","alexandre.kamal@ihstowers.com","1686","=
12-11-2024 15:17:46","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003565587","NYO=
M FACE MAETUR","","12-11-2024 15:14:56","12-11-2024 15:00:41","12-11-2024 1=
5:15:26","Grid outage, Landlord has forbidden to start the generator due to=
 noise // Grid restored","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Emergency Stop","Grid outage, Landlord has forbidden to sta=
rt the generator due to noise // Grid restored","kamga.virgile@ihstowers.co=
m","856","12-11-2024 15:14:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0003565377","C=
rf-Nkolbisson","","12-11-2024 14:43:11","12-11-2024 14:34:07","12-11-2024 1=
4:35:08","No power issue site on grid wjth U=3D54.5v Mohamadou(691144435) f=
rom Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on grid wjth U=3D54.5v Mohamadou(691144435) from Huawei is informed=
","alexandre.kamal@ihstowers.com","546","12-11-2024 14:43:11","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003565353","Afanoya"=
,"","12-11-2024 14:38:11","12-11-2024 14:32:37","12-11-2024 14:40:51","Casc=
aded Incident from TTO3478323","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Grid return","system","279179","12-11-=
2024 14:38:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003565352","MBALNGON=
G LYCEE","","12-11-2024 14:38:11","12-11-2024 14:32:37","12-11-2024 14:40:5=
1","Cascaded Incident from TTO3478323","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid return","system","279179","1=
2-11-2024 14:38:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003565351","ELOUMDEM=
 CARRIERE","","12-11-2024 14:38:10","12-11-2024 14:32:37","12-11-2024 14:40=
:51","Cascaded Incident from TTO3478323","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Grid return","system","279178",=
"12-11-2024 14:38:10","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003565345","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","12-11-2024 14:36:57","12-11-20=
24 14:28:37","12-11-2024 14:40:51","Grid outage, site went down before gen =
start due to poor battery backup // Grid return","Hyemafo Gildas","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, site went down before gen start due to poor battery backup // Grid ret=
urn","kamga.virgile@ihstowers.com","2407","12-11-2024 14:36:57","Sagemcom C=
MR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0003564847","Nya=
hoo","","12-11-2024 13:40:06","12-11-2024 13:26:41","12-11-2024 13:30:41","=
Active//No power issue on site U=3D55,3V site on Gen and The FME TX Gregoir=
e From huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue on site U=3D55,3V site on Gen and The FME TX Gregoire From hu=
awei is informed","landry.etame@ihstowers.com","807","12-11-2024 13:40:06",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003564219","Nko=
londom","","12-11-2024 12:12:05","12-11-2024 11:57:57","12-11-2024 13:11:57=
","Site up waiting feedback","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel",".","landry.etame@ihstowers.com","995","=
12-11-2024 12:12:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0003564053","P=
olytechnique","","12-11-2024 11:49:17","12-11-2024 11:34:10","12-11-2024 12=
:23:05","Site went down due to work /Duclair/680685526/ from GAIO is wrokin=
g on site //End of work","","Installation Activity","Passive","Planned Acti=
vity","Installation Activity","Site went down due to work /Duclair/68068552=
6/ from GAIO is wroking on site //End of work","stephane.nkamwa@ihstowers.c=
om","908","12-11-2024 11:49:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_130","IHS_YND_539","NOCINC0003564041","N=
gousso OCM","","12-11-2024 11:48:03","12-11-2024 11:34:55","12-11-2024 12:0=
3:51","No power issue on site U=3D54,5v site on grid Armand of huawei is in=
formed","Siligap Boris","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,5v site o=
n grid Armand of huawei is informed","stephane.nkamwa@ihstowers.com","789",=
"12-11-2024 11:48:03","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003563799","Eko=
unou","","12-11-2024 11:29:17","12-11-2024 11:21:11","12-11-2024 12:23:11",=
"Site was on gen due to grid outage, site went down because gen stopped wit=
h high temp alarm // reset gen card done and gen started","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Site was on =
gen due to grid outage, site went down because gen stopped with high temp a=
larm // reset gen card done and gen started","landry.etame@ihstowers.com","=
488","12-11-2024 11:29:17","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0003563557","Bas=
tos Bethesda","","12-11-2024 11:14:46","12-11-2024 11:04:42","12-11-2024 11=
:18:35","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen started automatically","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // Gen started automatica=
lly","landry.etame@ihstowers.com","606","12-11-2024 11:14:46","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003563228","MBIMBIM"=
,"","12-11-2024 10:43:02","12-11-2024 10:27:42","12-11-2024 11:23:42","Casc=
aded Incident from TTO3475893","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down because gen=
 ran untill fuel shortage // refueling done (Fuel manage by edond=E9)","sys=
tem","272038","12-11-2024 10:43:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003563227","Ngouetou=
","","12-11-2024 10:43:01","12-11-2024 10:27:42","12-11-2024 11:23:42","Cas=
caded Incident from TTO3475893","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n ran untill fuel shortage // refueling done (Fuel manage by edond=E9)","sy=
stem","919","12-11-2024 10:43:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003563226","Matsari"=
,"","12-11-2024 10:43:01","12-11-2024 10:27:42","12-11-2024 11:23:42","Casc=
aded Incident from TTO3475893","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down because gen=
 ran untill fuel shortage // refueling done (Fuel manage by edond=E9)","sys=
tem","919","12-11-2024 10:43:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0003563203","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","12-11-2024 10:40:46","12-=
11-2024 10:27:42","12-11-2024 11:23:42","Grid outage, site went down becaus=
e gen ran untill fuel shortage // refueling done (Fuel manage by edond=E9)"=
,"Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age, site went down because gen ran untill fuel shortage // refueling done =
(Fuel manage by edond=E9)","stephane.nkamwa@ihstowers.com","786","12-11-202=
4 10:40:46","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003562902","NYO=
M FACE MAETUR","","12-11-2024 10:05:12","12-11-2024 09:51:03","12-11-2024 1=
2:18:03","Grid outage, landlord has forbiden to start the gen due to noise =
// Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Emergency Stop","Grid outage, landlord has forbiden to start the gen=
 due to noise // Grid return","landry.etame@ihstowers.com","852","12-11-202=
4 10:05:12","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003562184","Mok=
olo Yaounde","","12-11-2024 08:20:17","12-11-2024 08:07:05","12-11-2024 10:=
29:05","Grid outage, no space to deploy a Mobile gen  // grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, no space to deploy a Mobile gen  // grid return","landry.etame@ihstower=
s.com","793","12-11-2024 08:20:17","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003559912","NYO=
M 2 IHS","","12-11-2024 00:58:59","12-11-2024 00:54:54","12-11-2024 01:01:3=
4","Grid outage site went down because Gen overload (15Kva; 310A) // Grid p=
ower return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage site went down because Gen overload (15Kva; 310A=
) // Grid power return","rouselle.schoune@ihstowers.com","246","12-11-2024 =
00:58:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003559679","S=
tade-Abega","","12-11-2024 00:02:19","11-11-2024 22:34:00","12-11-2024 01:3=
5:07","Site went down because 2/4 rectifier alarmed// He reset rectifers, s=
ite on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down because 2/4 rectifier alarmed// He reset r=
ectifers, site on Grid","denis.mballa@ihstowers.com","5300","12-11-2024 00:=
02:19","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003559615","NYO=
M FACE MAETUR","","11-11-2024 23:39:08","11-11-2024 21:47:03","12-11-2024 0=
9:05:04","Grid outage, landlord has forbiden to start the gen due to noise =
//he did a bridge on good phase","Fabrice Pouakam","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Emergency Stop","Grid outage, landlord has forbiden=
 to start the gen due to noise //he did a bridge on good phase","rouselle.s=
choune@ihstowers.com","6726","11-11-2024 23:39:08","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003559279","Bit=
eng","","11-11-2024 22:25:14","11-11-2024 22:23:09","11-11-2024 23:59:44","=
Active: no power issue, site is on grid with Ubaie=3D53V, Lionel Adjep(6551=
84876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no p=
ower issue, site is on grid with Ubaie=3D53V, Lionel Adjep(655184876) from =
Huawei is informed","rouselle.schoune@ihstowers.com","127","11-11-2024 22:2=
5:14","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003559222","Mvo=
g-Betsi","","11-11-2024 22:14:35","11-11-2024 22:04:59","11-11-2024 22:24:1=
3","site went down due to insuficiency of rectifiers // site stabilized","H=
yemafo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"site went down due to insuficiency of rectifiers // site stabilized","rous=
elle.schoune@ihstowers.com","577","11-11-2024 22:14:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003558676","M=
vog-Manga","","11-11-2024 20:53:02","11-11-2024 20:44:57","11-11-2024 20:50=
:15","Active// No power issue on site, Site on Grid Ubai:54.1V, The FME Lio=
nel Adjep/655184876/From Huawei is informed. Notice that we have disjunctio=
n at BTS OCM","Albran Byorel","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active// No power issue on site, =
Site on Grid Ubai:54.1V, The FME Lionel Adjep/655184876/From Huawei is info=
rmed. Notice that we have disjunction at BTS OCM","ludivine.ngamaleu@ihstow=
ers.com","486","11-11-2024 20:53:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003558551","M=
efou-Assi","","11-11-2024 20:35:12","11-11-2024 20:34:08","11-11-2024 20:40=
:01","Active//No power issue on site, Site on Grid UBAIE=3D53,3V synphorien=
 (675295205) From huawei is informed. Notice that we have disjunction at BT=
S OCM","Fanda Brice","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active//No power issue on site, Site on Gr=
id UBAIE=3D53,3V synphorien (675295205) From huawei is informed. Notice tha=
t we have disjunction at BTS OCM","ludivine.ngamaleu@ihstowers.com","65","1=
1-11-2024 20:35:12","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003558439","NTU=
I TOWN","","11-11-2024 20:18:15","11-11-2024 19:41:07","11-11-2024 20:21:41=
","Grid Outage, Site went down because Gen started and stopped due to ""hig=
h temp"" alarm// He open Generator swing and started Gen manualy","Parker T=
choup","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Grid Outage, Site went down because Gen started and st=
opped due to ""high temp"" alarm// He open Generator swing and started Gen =
manualy","olivier.kwedi@ihstowers.com","2229","11-11-2024 20:18:15","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003558265","S=
tade-Abega","","11-11-2024 19:49:25","11-11-2024 19:47:16","11-11-2024 19:5=
0:27","Active//No power issue on site Ubaie=3D54.7V;  site on GridThe FME L=
eonel Steve/ 655184876/  Huawei is informed. Notice that Disjunction in the=
 BTS OCM ","Mba Lazare Herve","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site Ub=
aie=3D54.7V;  site on GridThe FME Leonel Steve/ 655184876/  Huawei is infor=
med. Notice that Disjunction in the BTS OCM ","ludivine.ngamaleu@ihstowers.=
com","130","11-11-2024 19:49:25","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0003558255","NKO=
LOSSAN OKOK","","11-11-2024 19:47:30","11-11-2024 19:17:24","11-11-2024 19:=
25:06","Active//No power issue on site ,site on Grid  wiith Ubaie=3D54,5 V =
The TX FME Gregoire/ 654547479/  Huawei is informed.","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site ,site on Grid  wiith Ubaie=3D54,5 V T=
he TX FME Gregoire/ 654547479/  Huawei is informed.","olivier.kwedi@ihstowe=
rs.com","1807","11-11-2024 19:47:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003558234","D=
amas","","11-11-2024 19:44:28","11-11-2024 19:39:24","11-11-2024 19:45:25",=
"Active// No power Issue Site on Grid Ubai =3D54,1V, The FME  The TX FME Mb=
ah Hosiah (674007438) is informed. Notice that we have disjunction at BTS O=
CM","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active// No power Issue Site on Grid Ubai =
=3D54,1V, The FME  The TX FME Mbah Hosiah (674007438) is informed. Notice t=
hat we have disjunction at BTS OCM","ludivine.ngamaleu@ihstowers.com","304"=
,"11-11-2024 19:44:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0003558218","Eseka MT=
N","","11-11-2024 19:40:32","11-11-2024 19:30:10","11-11-2024 19:40:10","Ca=
scaded Incident from TTO3470156","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down before =
gen start due to poor battery backup // Gen started automatically","system"=
,"268432","11-11-2024 19:40:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003558221","Eseka To=
wn","","11-11-2024 19:40:32","11-11-2024 19:30:10","11-11-2024 19:40:10","C=
ascaded Incident from TTO3470156","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 gen start due to poor battery backup // Gen started automatically","system=
","268433","11-11-2024 19:40:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003558215","Ndogbess=
ol","","11-11-2024 19:40:31","11-11-2024 19:30:10","11-11-2024 19:40:10","C=
ascaded Incident from TTO3470156","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 gen start due to poor battery backup // Gen started automatically","system=
","268434","11-11-2024 19:40:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003558126","M=
VAN SACEL","","11-11-2024 19:30:33","11-11-2024 19:26:29","11-11-2024 20:41=
:09","site went down due to CB  (63 A) disjuted in the DC-BOX// He reamed t=
he CB  (63 A) ","MINKA NICOLAS","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Circuit Breaker Issue","site went down due to CB  (63 A)=
 disjuted in the DC-BOX// He reamed the CB  (63 A) ","ludivine.ngamaleu@ihs=
towers.com","245","11-11-2024 19:30:33","Sagemcom CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0003557980","Nya=
hoo","","11-11-2024 19:00:55","11-11-2024 18:50:46","11-11-2024 21:29:47","=
Active//No power issue on site U=3D55,3V site on Gen and The FME TX Gregoir=
e From  huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue on site U=3D55,3V site on Gen and The FME TX Gregoire From  =
huawei is informed","olivier.kwedi@ihstowers.com","610","11-11-2024 19:00:5=
5","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003557934","Sim=
bock MTN","","11-11-2024 18:51:26","11-11-2024 18:43:16","11-11-2024 21:48:=
46","Active//No power issue on site U=3D54,5V  site on Grid and the FME TX =
George(697461814) of huawei is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue on site U=3D54,5V  site on Grid and the FME TX George(697461=
814) of huawei is informed","olivier.kwedi@ihstowers.com","491","11-11-2024=
 18:51:26","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003557780","NYO=
M FACE MAETUR","","11-11-2024 18:24:34","11-11-2024 18:16:20","11-11-2024 1=
9:48:20","site down because 3/4 rectifiers alarmed due to a grid bad voltag=
es// Site stabilized","Fabrice Pouakam","Equipment Repair","Passive","Recti=
fier","Rectifier Module","site down because 3/4 rectifiers alarmed due to a=
 grid bad voltages// Site stabilized","olivier.kwedi@ihstowers.com","494","=
11-11-2024 18:24:34","Sagemcom CMR"
"Cancelled","Warning","T1748","IHS_YND_559","NOCINC0003557446","BATA Mokolo=
 OCM","","11-11-2024 17:33:10","","","","","","","","","","olivier.kwedi@ih=
stowers.com","434","11-11-2024 17:33:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0003557114","C=
rf-Nkolbisson","","11-11-2024 16:41:17","11-11-2024 16:34:05","11-11-2024 2=
0:36:54","Active// No power Issue Site on Grid Ubai =3D55.4V, The FME  The =
TX FME Mouhamadou (699949072) is informed","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power Issue Site on Grid Ubai =3D55.4V, The FME  The TX =
FME Mouhamadou (699949072) is informed","ludivine.ngamaleu@ihstowers.com","=
433","11-11-2024 16:41:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003556885","C=
RH-Etoug-Ebe","","11-11-2024 15:57:21","11-11-2024 15:54:17","11-11-2024 15=
:56:15","Active// No power issue, Site on Grid Ubai=3D52.9V The FME TX Mouh=
amadou (699949072) From Huawei is informed. Notice that we have disjunction=
 at BTS OCM","Hyemafo Gildas","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active// No power issue, Site on =
Grid Ubai=3D52.9V The FME TX Mouhamadou (699949072) From Huawei is informed=
. Notice that we have disjunction at BTS OCM","ludivine.ngamaleu@ihstowers.=
com","185","11-11-2024 15:57:21","Sagemcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0003556734","ODZ=
A BORNE 10","","11-11-2024 15:38:16","11-11-2024 14:15:03","11-11-2024 15:2=
6:54","Site went down due to 03/03 Rectifier Dysfuntionning on Site// He re=
set all  Rectifier and Site is on Grid","Albran Byorel","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","Site went down due to 03/03 Recti=
fier Dysfuntionning on Site// He reset all  Rectifier and Site is on Grid",=
"olivier.kwedi@ihstowers.com","4994","11-11-2024 15:38:16","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003556577","N=
yanon","","11-11-2024 15:14:36","11-11-2024 15:05:31","11-11-2024 15:44:38"=
,"Hybrid Gen Site: site went down because of the dysfunctioning of hybrid s=
ystem // He reset it, site on Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: site went down b=
ecause of the dysfunctioning of hybrid system // He reset it, site on Gen",=
"ludivine.ngamaleu@ihstowers.com","546","11-11-2024 15:14:36","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003556286","M=
fou EPC","","11-11-2024 14:45:11","11-11-2024 14:39:06","11-11-2024 15:26:1=
9","Grid outage site went down because Gen started and stopped with alarm l=
ow oil pressure // He reset the Gen card and Gen manually started","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
Grid outage site went down because Gen started and stopped with alarm low o=
il pressure // He reset the Gen card and Gen manually started","ludivine.ng=
amaleu@ihstowers.com","366","11-11-2024 14:45:11","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003555775","NYO=
M FACE MAETUR","","11-11-2024 13:40:58","11-11-2024 13:30:41","11-11-2024 1=
4:36:41","  site down because 3/4 rectifiers alarmed due to a grid bad volt=
ages//made a bridge and reset the rectifiers","Fabrice Pouakam","Equipment =
Repair","Passive","Rectifier","Rectifier Module","  site down because 3/4 r=
ectifiers alarmed due to a grid bad voltages//made a bridge and reset the r=
ectifier","kamga.virgile@ihstowers.com","618","11-11-2024 13:40:58","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0003554871","K=
ondengui","","11-11-2024 11:31:04","11-11-2024 11:24:00","11-11-2024 11:33:=
34","Grid outage, site went down before gen start due to poor battery backu=
p // Grid power return","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site went down before=
 gen start due to poor battery backup // Grid power return","alexandre.kama=
l@ihstowers.com","426","11-11-2024 11:31:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003553856","Ngoum","=
","11-11-2024 08:59:11","11-11-2024 08:40:50","11-11-2024 09:18:28","Cascad=
ed Incident from TTO3465106","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because Gen started and st=
opped due to air intake causing by fuel pipe pierced // He cut off the pier=
ced part and gen manually started ","system","271442","11-11-2024 08:59:11"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003553855","Matsari"=
,"","11-11-2024 08:59:11","11-11-2024 08:40:50","11-11-2024 09:18:28","Casc=
aded Incident from TTO3465106","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site went down because Gen started and =
stopped due to air intake causing by fuel pipe pierced // He cut off the pi=
erced part and gen manually started ","system","271442","11-11-2024 08:59:1=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003553857","Ngouetou=
","","11-11-2024 08:59:11","11-11-2024 08:40:50","11-11-2024 09:18:28","Cas=
caded Incident from TTO3465106","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because Gen started and=
 stopped due to air intake causing by fuel pipe pierced // He cut off the p=
ierced part and gen manually started ","system","271443","11-11-2024 08:59:=
11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003553858","Yoko MTN=
","","11-11-2024 08:59:11","11-11-2024 08:40:50","11-11-2024 09:18:28","Cas=
caded Incident from TTO3465106","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because Gen started and=
 stopped due to air intake causing by fuel pipe pierced // He cut off the p=
ierced part and gen manually started ","system","271443","11-11-2024 08:59:=
11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003553854","MBIMBIM"=
,"","11-11-2024 08:59:10","11-11-2024 08:40:50","11-11-2024 09:18:28","Casc=
aded Incident from TTO3465106","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site went down because Gen started and =
stopped due to air intake causing by fuel pipe pierced // He cut off the pi=
erced part and gen manually started ","system","271444","11-11-2024 08:59:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0003553773","D=
ong","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_YND_473","11-=
11-2024 08:47:54","11-11-2024 08:40:50","11-11-2024 09:18:28","site went do=
wn because Gen started and stopped due to air intake causing by fuel pipe p=
ierced // He cut off the pierced part and gen manually started ","Parker Tc=
houp","Fuel Outage (Probable)","Passive","Diesel","Fuel Line Issue","site w=
ent down because Gen started and stopped due to air intake causing by fuel =
pipe pierced // He cut off the pierced part and gen manually started ","ale=
xandre.kamal@ihstowers.com","426","11-11-2024 08:47:54","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0003553649","N=
dogbessol","","11-11-2024 08:28:26","11-11-2024 08:12:21","11-11-2024 08:13=
:38","Active//No power issue on site ,site on battery  wiith Ubaie=3D51.8 V=
 The TX FME Etienne/ 695033981/  Huawei is informed.//Site up at 08:23 AM",=
"Kemeni Franklin","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active//No power issue on site ,site on batte=
ry  wiith Ubaie=3D51.8 V The TX FME Etienne/ 695033981/  Huawei is informed=
.//Site up at 08:23 AM","alexandre.kamal@ihstowers.com","966","11-11-2024 0=
8:28:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0003553046","Eseka MT=
N","","11-11-2024 06:17:32","11-11-2024 05:49:37","11-11-2024 05:50:14","Ca=
scaded Incident from TTO3464113","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue site on Gen wit=
h U=3D54.4V The Tx Fme Yanick Mbah// 670610135 from Huawei is informed ","s=
ystem","274439","11-11-2024 06:17:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003553048","Eseka To=
wn","","11-11-2024 06:17:32","11-11-2024 05:49:37","11-11-2024 05:50:14","C=
ascaded Incident from TTO3464113","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue site on Gen wi=
th U=3D54.4V The Tx Fme Yanick Mbah// 670610135 from Huawei is informed ","=
system","274440","11-11-2024 06:17:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_781","NOCINC0003553041","BIBOMDJI=
DJIEL","","11-11-2024 06:17:31","11-11-2024 05:49:37","11-11-2024 05:50:14"=
,"Cascaded Incident from TTO3464113","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue site on Gen=
 with U=3D54.4V The Tx Fme Yanick Mbah// 670610135 from Huawei is informed =
","system","274438","11-11-2024 06:17:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003553044","Ndogbess=
ol","","11-11-2024 06:17:31","11-11-2024 05:49:37","11-11-2024 05:50:14","C=
ascaded Incident from TTO3464113","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue site on Gen wi=
th U=3D54.4V The Tx Fme Yanick Mbah// 670610135 from Huawei is informed ","=
system","274438","11-11-2024 06:17:31","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0003552614","NKO=
LOSSAN OKOK","","11-11-2024 04:12:37","11-11-2024 04:02:27","11-11-2024 04:=
50:00","site went down due to disjunction Cb(16A) of gen // He reamed Cb(16=
A), site on grid","Parker Tchoup","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","site went down due to disjunct=
ion Cb(16A) of gen // He reamed Cb(16A), site on grid","christian.fonkou@ih=
stowers.com","611","11-11-2024 04:12:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003550971","M=
vog-Manga","","10-11-2024 21:20:44","10-11-2024 21:16:32","10-11-2024 23:00=
:14","Active// No power issue on site, Site on Grid Ubai:54.1V, The FME Lio=
nel Adjep/655184876/From Huawei is informed","Albran Byorel","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue on site, Site on Grid Ubai:54.1V, The FME Lionel Adje=
p/655184876/From Huawei is informed","denis.mballa@ihstowers.com","254","10=
-11-2024 21:20:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003550961","M=
efou-Assi","","10-11-2024 21:19:12","10-11-2024 21:10:54","10-11-2024 21:20=
:12","Active//No power issue on site ,Site on Grid  with Ubaie=3D53.5V   tx=
 fme symforien/650257151 from huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site ,Site on Grid  with Ubaie=3D53.5V   tx fme =
symforien/650257151 from huawei is informed","denis.mballa@ihstowers.com","=
499","10-11-2024 21:19:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003550953","D=
amas","","10-11-2024 21:16:23","10-11-2024 21:07:11","10-11-2024 21:10:20",=
"No power issue site on grid with U=3D54.3v Notice that we have disjunction=
 et OCM Equipements Mbah Osiah(674007438) From Huawei is informed","MINKA N=
ICOLAS","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue site on grid with U=3D54.3v Notice that =
we have disjunction et OCM Equipements Mbah Osiah(674007438) From Huawei is=
 informed","denis.mballa@ihstowers.com","553","10-11-2024 21:16:23","Sagemc=
om CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003550626","Nko=
abang2","","10-11-2024 20:30:20","10-11-2024 20:22:15","10-11-2024 20:38:06=
","grid outage, site went down because gen failed to start due to dysfuncti=
onning of gen card // he reset gen card and gen manually started","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","g=
rid outage, site went down because gen failed to start due to dysfunctionni=
ng of gen card // he reset gen card and gen manually started","rouselle.sch=
oune@ihstowers.com","529","10-11-2024 20:30:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003550556","Crf Corn=
ier","","10-11-2024 20:22:40","10-11-2024 20:15:45","10-11-2024 21:39:53","=
Cascaded Incident from TTO3461232","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because CB(125A) tri=
pped in PWC// CB put back on","system","1222180","10-11-2024 20:22:40","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003550554","M=
adison","IHS_YND_566","10-11-2024 20:21:59","10-11-2024 20:15:45","10-11-20=
24 21:39:53","Site went down because CB(125A) tripped in PWC// CB put back =
on","MFOUAGUEGUE MATHIEU","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Circuit Breaker Issue","Site went down because CB(125A) trippe=
d in PWC// CB put back on","denis.mballa@ihstowers.com","376","10-11-2024 2=
0:21:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_515","NOCINC0003550525","Etoug eb=
e Meweulo","","10-11-2024 20:18:51","10-11-2024 20:02:17","10-11-2024 20:26=
:02","Cascaded Incident from TTO3461137","Hyemafo Gildas","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site on Grid, Site went down=
 due to High Temperature on site causing by Aircon dysfunction and Shelter =
Close// He open shelter (Aircon recuperation ongoing)","system","273761","1=
0-11-2024 20:18:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_143","NOCINC0003550524","Byemassi=
 Carrefour","","10-11-2024 20:18:51","10-11-2024 20:02:17","10-11-2024 20:2=
6:02","Cascaded Incident from TTO3461137","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site on Grid, Site went down d=
ue to High Temperature on site causing by Aircon dysfunction and Shelter Cl=
ose// He open shelter (Aircon recuperation ongoing)","system","273760","10-=
11-2024 20:18:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_803","NOCINC0003550528","Etoug eb=
e biscuiterie","","10-11-2024 20:18:51","10-11-2024 20:02:17","10-11-2024 2=
0:26:02","Cascaded Incident from TTO3461137","Hyemafo Gildas","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site on Grid, Site went =
down due to High Temperature on site causing by Aircon dysfunction and Shel=
ter Close// He open shelter (Aircon recuperation ongoing)","system","273760=
","10-11-2024 20:18:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_225","NOCINC0003550526","Science"=
,"","10-11-2024 20:18:51","10-11-2024 20:02:17","10-11-2024 20:26:02","Casc=
aded Incident from TTO3461137","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site on Grid, Site went down=
 due to High Temperature on site causing by Aircon dysfunction and Shelter =
Close// He open shelter (Aircon recuperation ongoing)","system","273761","1=
0-11-2024 20:18:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_747","NOCINC0003550527","Akok Ndo=
e Yde","","10-11-2024 20:18:51","10-11-2024 20:02:17","10-11-2024 20:26:02"=
,"Cascaded Incident from TTO3461137","Hyemafo Gildas","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site on Grid, Site went down due=
 to High Temperature on site causing by Aircon dysfunction and Shelter Clos=
e// He open shelter (Aircon recuperation ongoing)","system","273761","10-11=
-2024 20:18:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_741","NOCINC0003550523","Mvog Bet=
si Hospital","","10-11-2024 20:18:50","10-11-2024 20:02:17","10-11-2024 20:=
26:02","Cascaded Incident from TTO3461137","Hyemafo Gildas","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site on Grid, Site went do=
wn due to High Temperature on site causing by Aircon dysfunction and Shelte=
r Close// He open shelter (Aircon recuperation ongoing)","system","273762",=
"10-11-2024 20:18:50","Sagemcom CMR"
"Closed Complete","Site Down","T0370","IHS_YND_227","NOCINC0003550468","Mvo=
g Betsi","IHS_YND_741, IHS_YND_143, IHS_YND_515, IHS_YND_225, IHS_YND_747, =
IHS_YND_803","10-11-2024 20:13:24","10-11-2024 20:02:17","10-11-2024 20:26:=
02","Site on Grid, Site went down due to High Temperature on site causing b=
y Aircon dysfunction and Shelter Close// He open shelter (Aircon reparation=
 ongoing)","Hyemafo Gildas","Equipment Repair","Passive","Environmental","A=
ircon Compressor Faulty","Site on Grid, Site went down due to High Temperat=
ure on site causing by Aircon dysfunction and Shelter Close// He open shelt=
er (Aircon reparation ongoing)","rouselle.schoune@ihstowers.com","668","10-=
11-2024 20:13:24","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003550178","NYO=
M FACE MAETUR","","10-11-2024 19:25:38","10-11-2024 19:17:31","11-11-2024 0=
0:17:39","Grid outage, landlord has forbiden to start the gen due to noise =
// Grid  stabilized.","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Emergency Stop","Grid outage, landlord has forbiden to start t=
he gen due to noise // Grid  stabilized.","rouselle.schoune@ihstowers.com",=
"488","10-11-2024 19:25:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0003550124","A=
wae-Yde","","10-11-2024 19:17:44","10-11-2024 19:08:33","10-11-2024 20:54:3=
5","Grid outage, site went down because Gen stopped with alarm ""overcurren=
t""// He reduced 01 rectifier, site on Gen","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went dow=
n because Gen stopped with alarm ""overcurrent""// He reduced 01 rectifier,=
 site on Gen","denis.mballa@ihstowers.com","551","10-11-2024 19:17:44","Sag=
emcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0003550091","Awa=
e Ewonkan","","10-11-2024 19:12:19","10-11-2024 18:25:13","10-11-2024 19:32=
:36","grid outage, site went down due to gen overload(20KVA, 270A) // He re=
duced the load and gen manually started","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","grid outage, site went down due to=
 gen overload(20KVA, 270A) // He reduced the load and gen manually started"=
,"rouselle.schoune@ihstowers.com","2864","10-11-2024 19:12:19","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003549777","N=
kolo II New","","10-11-2024 18:33:35","10-11-2024 18:02:17","11-11-2024 00:=
50:52","Active// No power Issue on site, Site on Grid Ubai: 50.5V, The Fme =
Eloundou/652586578/From Huawei  is informed. Notice that we have disjunctio=
n at BTS OCM","Mba Lazare Herve","Cascade Outage","Active","Cascade Active"=
,"Cascade Active","Active// No power Issue on site, Site on Grid Ubai: 50.5=
V, The Fme Eloundou/652586578/From Huawei  is informed. Notice that we have=
 disjunction at BTS OCM","denis.mballa@ihstowers.com","2096","10-11-2024 18=
:33:35","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0003549709","Men=
dong NB","","10-11-2024 18:28:52","10-11-2024 18:25:46","10-11-2024 20:35:3=
3","Site went down because 2 CB(63A) tripped in DC box// CB put back on",""=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Brea=
ker Issue","Site went down because 2 CB(63A) tripped in DC box// CB put bac=
k on","rouselle.schoune@ihstowers.com","187","10-11-2024 18:28:52","Sagemco=
m CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0003549688","Awa=
e Escalier","","10-11-2024 18:27:17","10-11-2024 18:23:42","10-11-2024 19:5=
7:12","Grid outage, Site went down before Gen start due to poor backup// Ge=
n started automatically","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, Site went down befor=
e Gen start due to poor backup// Gen started automatically","rouselle.schou=
ne@ihstowers.com","216","10-11-2024 18:27:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003549547","M=
imboman-Village","IHS_YND_709","10-11-2024 18:10:33","10-11-2024 18:02:17",=
"10-11-2024 21:30:52","Active// No power Issue on site, Site on Grid Ubai: =
50.5V, The Fme Eloundou/652586578/From Huawei  is informed. Notice that we =
have disjunction at BTS OCM","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er Issue on site, Site on Grid Ubai: 50.5V, The Fme Eloundou/652586578/From=
 Huawei  is informed. Notice that we have disjunction at BTS OCM","denis.mb=
alla@ihstowers.com","497","10-11-2024 18:10:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0003549454","Eseka MT=
N","","10-11-2024 17:58:21","10-11-2024 14:39:52","10-11-2024 14:57:17","Ca=
scaded Incident from TTO3459897","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because is impacted =
by power of Sombo(but site is not down): Grid outage, Site went down before=
 Gen start due to poor battery backup// Gen started automatically","system"=
,"293005","10-11-2024 17:58:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003549452","Ndogbess=
ol","","10-11-2024 17:58:21","10-11-2024 14:39:52","10-11-2024 14:57:17","C=
ascaded Incident from TTO3459897","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down because is impacted=
 by power of Sombo(but site is not down): Grid outage, Site went down befor=
e Gen start due to poor battery backup// Gen started automatically","system=
","293005","10-11-2024 17:58:21","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003549398","Nko=
londom","","10-11-2024 17:50:47","10-11-2024 17:49:40","10-11-2024 19:11:32=
","Site was on Gen due to Grid outage, Site went down because Gen stopped w=
ith ""low oil pressure"" alarm// He reset Gen card and started Gen manualy"=
,"Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Site was on Gen due to Grid outage, Site went down because Gen stop=
ped with ""low oil pressure"" alarm// He reset Gen card and started Gen man=
ualy","rouselle.schoune@ihstowers.com","68","10-11-2024 17:50:47","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003549047","S=
tade-Abega","","10-11-2024 16:58:32","10-11-2024 16:51:20","10-11-2024 17:3=
9:01","grid outage, site went down because gen stoppen glow plug faulty // =
He gen manually started","Mba Lazare Herve","Equipment Repair","Passive","A=
CDG Gen","ACDG - Kick Starter","grid outage, site went down because gen sto=
ppen glow plug faulty // He gen manually started","denis.mballa@ihstowers.c=
om","433","10-11-2024 16:58:32","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0003548552","Ole=
mbe","","10-11-2024 15:53:19","10-11-2024 15:48:11","10-11-2024 16:04:16","=
Grid outage, Site went down because Gen fails to start due to Gen card dysf=
unction// He reset Gen card and started Gen manualy(Investigation ongoing)"=
,"Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid outage, Site went down because Gen fails to start due to Gen c=
ard dysfunction// He reset Gen card and started Gen manualy(Investigation o=
ngoing)","rouselle.schoune@ihstowers.com","367","10-11-2024 15:53:19","Sage=
mcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003548439","MIM=
BOMAN LIBERTE","","10-11-2024 15:31:27","10-11-2024 15:25:20","10-11-2024 1=
5:45:17","Grid Outage ;site went down because Main Gen faulty // MDG 20 Kva=
 has  deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Generator Faulty","Grid Outage ;site went down because Main Gen fau=
lty // MDG 20 Kva has  deployed","rouselle.schoune@ihstowers.com","368","10=
-11-2024 15:31:27","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0003548043","Awa=
e Ewonkan","","10-11-2024 14:37:56","10-11-2024 14:35:53","10-11-2024 14:41=
:30","Grid outage ,site went down because Gen started and stopped because G=
EN  overload (20KVA.270A)//GRID RETURN","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went down because=
 Gen started and stopped because GEN  overload (20KVA.270A)//GRID RETURN","=
rouselle.schoune@ihstowers.com","124","10-11-2024 14:37:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_010","NOCINC0003547854","CNR","",=
"10-11-2024 14:05:10","10-11-2024 13:56:19","10-11-2024 15:13:07","Cascaded=
 Incident from TTO3457938","Mboua Thierry","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site. Ubaie: 54,7V site on G=
rid (hybrid site). Raoul (691144462/Huawei) is informed. ","system","531","=
10-11-2024 14:05:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003547625","S=
oa-II","IHS_YND_324","10-11-2024 13:35:36","10-11-2024 13:09:27","10-11-202=
4 14:20:54","Grid Outage, site went down because Gen stopped with ""high te=
mp"" alarm// He added water and started Gen manualy","Siligap Boris","Equip=
ment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level =
Issue","Grid Outage, site went down because Gen stopped with ""high temp"" =
alarm// He added water and started Gen manualy","etienne.itondo@ihstowers.c=
om","1569","10-11-2024 13:35:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003547615","O=
lembe-Terminus","","10-11-2024 13:34:31","10-11-2024 13:24:59","10-11-2024 =
15:03:29","Site went down because 2/5 rectifiers disfunctionning// He reset=
 rectifiers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down because 2/5 rectifiers disfunctionning// He=
 reset rectifiers","ludivine.ngamaleu@ihstowers.com","573","10-11-2024 13:3=
4:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003547567","A=
kak-Nkozoa-MTN-IHS","","10-11-2024 13:28:29","10-11-2024 13:09:24","10-11-2=
024 14:21:01","Grid bad voltage, site went down because Gen failed to start=
 due to Grid bad voltage and RCP faulty// Grid stabilized","Fabrice Pouakam=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid bad voltage, site went down because Gen failed to start due to Grid b=
ad voltage and RCP faulty// Grid stabilized","ludivine.ngamaleu@ihstowers.c=
om","1146","10-11-2024 13:28:29","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003547266","Mim=
boman4","","10-11-2024 12:45:09","10-11-2024 12:20:57","10-11-2024 12:40:29=
","Grid outage site went down because Gen failed to start due to started re=
lay faulty // He replaced the relay and Gen manually started","Mba Lazare H=
erve","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid o=
utage site went down because Gen failed to start due to started relay fault=
y // He replaced the relay and Gen manually started","etienne.itondo@ihstow=
ers.com","1453","10-11-2024 12:45:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003547236","Crf Corn=
ier","","10-11-2024 12:40:00","10-11-2024 12:33:06","10-11-2024 15:48:48","=
Cascaded Incident from TTO3457210","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site down due to work (Abena 699999=
625 dowen service working (Swap PWC)''","system","278883","10-11-2024 12:40=
:00","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003547234","Ess=
os Marche","","10-11-2024 12:39:41","10-11-2024 12:35:29","10-11-2024 15:51=
:59","Site down due to work (Abena 699999625 dowen service working (Swap PW=
C)''//End of work","Delor Telezing","Equipment Replacement","Passive","Plan=
ned Activity","Planned Activity - Passive","Site down due to work (Abena 69=
9999625 dowen service working (Swap PWC)''//End of work","olivier.kwedi@ihs=
towers.com","253","10-11-2024 12:39:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003547232","M=
adison","IHS_YND_566","10-11-2024 12:39:15","10-11-2024 12:33:06","10-11-20=
24 15:48:48","Site down due to work (Abena 699999625 dowen service working =
(Swap PWC)''//End of work","MFOUAGUEGUE MATHIEU","Equipment Replacement","P=
assive","Planned Activity","Planned Activity - Passive","Site down due to w=
ork (Abena 699999625 dowen service working (Swap PWC)''//End of work","ludi=
vine.ngamaleu@ihstowers.com","370","10-11-2024 12:39:15","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003546773","Nko=
ulou Carriere carrefourt","","10-11-2024 11:34:56","10-11-2024 11:32:45","1=
0-11-2024 13:16:48","Grid outage.gen failed to start due to battery GE faul=
ty causing by static charger issue//gen manually started with external batt=
ery","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Gen=
erator Battery","Grid outage.gen failed to start due to battery GE faulty c=
ausing by static charger issue//gen manually started with external battery"=
,"olivier.kwedi@ihstowers.com","131","10-11-2024 11:34:56","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0003546630","Ngo=
usso Vallee","","10-11-2024 11:11:19","10-11-2024 09:32:58","10-11-2024 10:=
23:21","site went down because Gen stopped with low oil pressure (alarm unp=
roven)// he reset the Gen card and manually started","Siligap Boris","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","site went down be=
cause Gen stopped with low oil pressure (alarm unproven)// he reset the Gen=
 card and manually started","etienne.itondo@ihstowers.com","5902","10-11-20=
24 11:11:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0003546612","M=
adagascar-Yde-New","IHS_YND_138","10-11-2024 11:08:42","10-11-2024 10:56:33=
","10-11-2024 10:57:13","Active//No power issue on site Ubaie:52.9V; site o=
n Grid. The Tx fme Brice Tsague /650214096) from Huawei is informed.","","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue on site Ubaie:52.9V; site on Grid. The Tx =
fme Brice Tsague /650214096) from Huawei is informed.","ludivine.ngamaleu@i=
hstowers.com","730","10-11-2024 11:08:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0003546609","N=
komkana 2","","10-11-2024 11:07:58","10-11-2024 10:56:33","10-11-2024 10:57=
:13","","Mboua Thierry","Cascade Outage","Active","Cascade Active","Cascade=
 Active","Active//No power issue on site Ubaie:52.9V; site on Grid. The Tx =
fme Brice Tsague /650214096) from Huawei is informed.","ludivine.ngamaleu@i=
hstowers.com","277598","10-11-2024 11:07:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003546608","A=
wae Escalier","","10-11-2024 11:07:24","10-11-2024 10:58:20","10-11-2024 11=
:15:06","Grid outage, Site went down before Gen start due to poor backup// =
Gen started automatically","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down bef=
ore Gen start due to poor backup// Gen started automatically","ludivine.nga=
maleu@ihstowers.com","545","10-11-2024 11:07:24","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003546571","MIM=
BOMAN LIBERTE","","10-11-2024 11:02:40","10-11-2024 10:52:28","10-11-2024 1=
1:06:06","Grid Outage and Main Gen Faulty// MDG of 20Kva has deplyed","Mba =
Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fau=
lty","Grid Outage and Main Gen Faulty// MDG of 20Kva has deplyed","olivier.=
kwedi@ihstowers.com","613","10-11-2024 11:02:40","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003546519","San=
ta Barbara Gottam","","10-11-2024 10:58:41","10-11-2024 10:46:26","10-11-20=
24 11:24:52","Site went down due to PWC dysfonctioning ( Batteries Backup a=
larming ; PWC FNS)//Reset Batteries Backup,site on Gen.","Delor Telezing","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site=
 went down due to PWC dysfonctioning ( Batteries Backup alarming ; PWC FNS)=
//Reset Batteries Backup,site on Gen.","etienne.itondo@ihstowers.com","736"=
,"10-11-2024 10:58:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0003546308","MONTEE N=
KONDENGUI","","10-11-2024 10:40:51","10-11-2024 10:33:09","10-11-2024 10:48=
:07","Cascaded Incident from TTO3456085","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage/Grid return","sys=
tem","278956","10-11-2024 10:40:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0003546289","M=
obil-Kondengui","IHS_YND_682","10-11-2024 10:37:14","10-11-2024 10:33:09","=
10-11-2024 10:48:07","Grid outage/Grid return","","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","Grid outage/Grid return","ludivi=
ne.ngamaleu@ihstowers.com","246","10-11-2024 10:37:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003545989","A=
wae Ewonkan","","10-11-2024 10:02:35","10-11-2024 09:58:22","10-11-2024 11:=
15:54","grid outage, site went down due to gen overload (20kva, 340A) // He=
 reduced the load and gen manually started","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","grid outage, site went down due=
 to gen overload (20kva, 340A) // He reduced the load and gen manually star=
ted","ludivine.ngamaleu@ihstowers.com","254","10-11-2024 10:02:35","Sagemco=
m CMR"
"Closed Complete","Site Down","T2564","IHS_YND_739","NOCINC0003545982","NKO=
LMESSING rue Manguier","","10-11-2024 10:02:08","10-11-2024 09:55:58","10-1=
1-2024 10:45:14","Grid outage site went down because Gen failed to start du=
e to Gen contactor faulty // He bypass the Gen contactor and Gen manually s=
tarted","Siligap Boris","Equipment Repair","Passive","Control Panel","ATS-A=
MF Issue","Grid outage site went down because Gen failed to start due to Ge=
n contactor faulty // He bypass the Gen contactor and Gen manually started"=
,"olivier.kwedi@ihstowers.com","371","10-11-2024 10:02:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003545920","Kondengu=
i","","10-11-2024 09:59:00","10-11-2024 09:43:54","10-11-2024 10:51:57","Ca=
scaded Incident from TTO3455608","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage No space to deploy a MDG =
//Grid power return","system","906","10-11-2024 09:59:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003545870","E=
mombo-Tchad","IHS_YND_114","10-11-2024 09:50:58","10-11-2024 09:43:54","10-=
11-2024 10:51:57","Grid outage No space to deploy a MDG //Grid power return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage No space to deploy a MDG //Grid power return","ludivine.ngamaleu@=
ihstowers.com","425","10-11-2024 09:50:58","Sagemcom CMR"
"Closed Complete","Site Down","T0636","IHS_YND_299","NOCINC0003545834","Ole=
mbe MTN","","10-11-2024 09:47:32","10-11-2024 09:44:23","10-11-2024 10:16:3=
5","Grid Outage Site went down because Gen Failed to Start due to """"low o=
il pressure"""" (alarm unproven)//he reset the gen card and started it (Dee=
p deep investiguetion ongoing)","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid Outage Site went down because G=
en Failed to Start due to """"low oil pressure"""" (alarm unproven)//he res=
et the gen card and started it (Deep deep investiguetion ongoing)","olivier=
.kwedi@ihstowers.com","190","10-11-2024 09:47:32","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003545763","Bit=
oto","","10-11-2024 09:40:38","10-11-2024 09:38:05","10-11-2024 10:10:29","=
Grid outage  site went down due to Gen overload(20kva,320A) // he reduced t=
he load and manualy start the gen","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage  site went down due to Ge=
n overload(20kva,320A) // he reduced the load and manualy start the gen","o=
livier.kwedi@ihstowers.com","154","10-11-2024 09:40:38","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0003545762","Nko=
lo II New","","10-11-2024 09:40:30","10-11-2024 08:56:57","10-11-2024 10:48=
:55","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Grid outage, site went down before Gen start due to poor ba=
ckup// Gen started automaticaly","etienne.itondo@ihstowers.com","3153","10-=
11-2024 09:40:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003545674","M=
imboman-Village","IHS_YND_709","10-11-2024 09:30:05","10-11-2024 09:25:52",=
"10-11-2024 09:42:46","Grid outage, site went down before Gen start due to =
poor backup// Gen started automaticaly","Mba Lazare Herve","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before Gen start due to poor backup// Gen started automaticaly=
","ludivine.ngamaleu@ihstowers.com","254","10-11-2024 09:30:05","Sagemcom C=
MR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003545534","Nko=
abang2","","10-11-2024 09:13:28","10-11-2024 09:05:20","10-11-2024 09:57:40=
","Grid outage site went down because Gen failed to start due to Gen card d=
ysfonction  // He reset the Gen card and Gen manually started","Mba Lazare =
Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage site went down because Gen failed to start due to Gen card dysfonct=
ion  // He reset the Gen card and Gen manually started","olivier.kwedi@ihst=
owers.com","869","10-11-2024 09:13:28","Sagemcom CMR"
"Cancelled","Warning","T1559","IHS_YND_709","NOCINC0003545474","Nkolo II Ne=
w","","10-11-2024 09:05:07","","","","Mba Lazare Herve","","","","","","oli=
vier.kwedi@ihstowers.com","309","10-11-2024 09:05:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003545435","Anguissa=
 New","","10-11-2024 08:59:20","10-11-2024 08:53:33","10-11-2024 11:03:34",=
"Cascaded Incident from TTO3455070","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage No Space to Deploy a M=
DG awaiting Grid Restored","system","292258","10-11-2024 08:59:20","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003545431","L=
abogenie","IHS_YND_568","10-11-2024 08:58:40","10-11-2024 08:53:33","10-11-=
2024 11:03:34","Grid Outage No Space to Deploy a MDG //Grid Restored","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outa=
ge No Space to Deploy a MDG //Grid Restored","ludivine.ngamaleu@ihstowers.c=
om","308","10-11-2024 08:58:40","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003545425","Mim=
boman4","IHS_YND_709","10-11-2024 08:57:26","10-11-2024 08:56:57","10-11-20=
24 10:48:55","Grid outage site went down because Gen failed to start due to=
 started relay faulty // He replaced the relay and Gen manually started","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Kick Start=
er","Grid outage site went down because Gen failed to start due to started =
relay faulty // He replaced the relay and Gen manually started","olivier.kw=
edi@ihstowers.com","30","10-11-2024 08:57:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0003545355","N=
kolbong","","10-11-2024 08:52:02","10-11-2024 08:49:54","10-11-2024 09:38:4=
9","Grid Outage  Site went down because Gen Started and Stop due to high te=
mp(alarm unproven)//he reset the Gen card and started it","Delor Telezing",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage=
  Site went down because Gen Started and Stop due to high temp(alarm unprov=
en)//he reset the Gen card and started it","ludivine.ngamaleu@ihstowers.com=
","129","10-11-2024 08:52:02","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003545295","MIM=
BOMAN LIBERTE","","10-11-2024 08:44:11","10-11-2024 08:41:05","10-11-2024 1=
0:07:59","Grid Outage and Main Gen Faulty// 20 Kva has be deploy","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty"=
,"Grid Outage and Main Gen Faulty// 20 Kva has be deploy","olivier.kwedi@ih=
stowers.com","442","10-11-2024 08:44:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003545255","C=
rf-Nsam","","10-11-2024 08:35:53","10-11-2024 08:24:50","10-11-2024 09:02:0=
7","Site went down due to PWC overload ( 24 kw, 270 A)// he reduice the Loa=
d and Site is on Grid","MINKA NICOLAS","Equipment Repair","Passive","Rectif=
ier","Rectifier Module Overloaded","Site went down due to PWC overload ( 24=
 kw, 270 A)// he reduice the Load and Site is on Grid","ludivine.ngamaleu@i=
hstowers.com","664","10-11-2024 08:35:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003545254","E=
ssomba","","10-11-2024 08:35:51","10-11-2024 08:22:43","10-11-2024 09:09:07=
","grid outage, site went down because gen start and stoppen with alarm ""l=
ow oil pressure // He reset gen card and gen manually started","Mba Lazare =
Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid=
 outage, site went down because gen start and stoppen with alarm ""low oil =
pressure // He reset gen card and gen manually started","etienne.itondo@ihs=
towers.com","789","10-11-2024 08:35:51","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003545224","San=
ta Barbara Gottam","","10-11-2024 08:31:48","10-11-2024 08:28:42","10-11-20=
24 09:02:32","Site went down due to PWC dysfonctioning ( Batteries Backup a=
larming ; PWC FNS)//Reset Batteries Backup,site on Gen.","Delor Telezing","=
Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Site=
 went down due to PWC dysfonctioning ( Batteries Backup alarming ; PWC FNS)=
//Reset Batteries Backup,site on Gen.","olivier.kwedi@ihstowers.com","187",=
"10-11-2024 08:31:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003545204","S=
atcom","","10-11-2024 08:29:25","10-11-2024 08:21:20","10-11-2024 10:09:14"=
,"Active//No power issue on site, Site on Grid UBAIE=3D58.8V  and Geoge (69=
7461814) From huawei is informed.","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site, Site on Grid UBAIE=3D58.8V  and Geoge (697461814) From=
 huawei is informed.","ludivine.ngamaleu@ihstowers.com","485","10-11-2024 0=
8:29:25","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003545130","Eko=
unou","","10-11-2024 08:16:55","10-11-2024 08:10:31","10-11-2024 08:16:31",=
"Grid outage, Site went down before Gen start due to poor backup// Gen star=
ted automatically","Albran Byorel","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, Site went down before Gen =
start due to poor backup// Gen started automatically","olivier.kwedi@ihstow=
ers.com","386","10-11-2024 08:16:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0003545126","C=
NDH","","10-11-2024 08:15:13","10-11-2024 08:09:08","10-11-2024 10:10:43","=
Active//No power issue, site is on Gen  with Ubaie=3D54.9V, Brice tsague(65=
0214096) from Huawei is informed","Paul BIBOUM","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue, site is on Gen  with Ubaie=3D54.9V, Brice tsague(650214096) from H=
uawei is informed","ludivine.ngamaleu@ihstowers.com","366","10-11-2024 08:1=
5:13","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_179","NOCINC0003545122","Essomba","","10-=
11-2024 08:14:51","","","Cascaded Incident from TTO3454702","Mba Lazare Her=
ve","","","Cascade Active","Cascade Active","Cascaded Incident from TTO3454=
702","system","311","10-11-2024 08:14:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003545123","Biteng-M=
aetur","","10-11-2024 08:14:51","10-11-2024 08:09:40","10-11-2024 08:13:36"=
,"Cascaded Incident from TTO3454702","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage and Main Gen Fault=
y// MDG of 15Kva has deployed","system","280312","10-11-2024 08:14:51","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003545121","Tradex-N=
komo","","10-11-2024 08:14:50","10-11-2024 08:09:40","10-11-2024 08:13:36",=
"Cascaded Incident from TTO3454702","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage and Main Gen Faulty// =
MDG of 15Kva has deployed","system","280312","10-11-2024 08:14:50","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003545118","B=
iteng","IHS_YND_172, IHS_YND_179, IHS_YND_249","10-11-2024 08:13:45","10-11=
-2024 08:09:40","10-11-2024 08:13:36","Grid outage, site went down before G=
en start due to poor backup// Gen started automaticaly","Mba Lazare Herve",=
"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low",=
"Grid outage, site went down before Gen start due to poor backup// Gen star=
ted automaticaly","ludivine.ngamaleu@ihstowers.com","246","10-11-2024 08:13=
:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003544785","Ndogbess=
ol","","10-11-2024 07:38:00","10-11-2024 07:30:35","10-11-2024 07:45:35","C=
ascaded Incident from TTO3454297","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automatically","system","268254=
","10-11-2024 07:38:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0003544786","Eseka MT=
N","","10-11-2024 07:38:00","10-11-2024 07:30:35","10-11-2024 07:45:35","Ca=
scaded Incident from TTO3454297","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down before =
Gen start due to poor backup// Gen started automatically","system","268253"=
,"10-11-2024 07:38:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003544783","Eseka To=
wn","","10-11-2024 07:37:12","10-11-2024 07:30:35","10-11-2024 07:45:35","C=
ascaded Incident from TTO3454297","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down before=
 Gen start due to poor backup// Gen started automatically","system","268252=
","10-11-2024 07:37:12","Sagemcom CMR"
"Closed Complete","Warning","T1868","IHS_YND_524","NOCINC0003543004","ODZA =
BORNE 10","","10-11-2024 01:01:06","","","Site went alarm due to 2 rectifie=
rs dysfutionning on Site // he reset it, site on grid","Albran Byorel","War=
ning","Warning","POWER","Warning - Site on Battery","Site went alarm due to=
 2 rectifiers dysfutionning on Site // he reset it, site on grid","landry.e=
tame@ihstowers.com","4","10-11-2024 01:01:06","Sagemcom CMR"
"Closed Complete","Warning","CTR_154","IHS_YND_518","NOCINC0003542482","Mon=
tee-Jouvence-II","","09-11-2024 22:48:39","","","Grid fluctuation, site wen=
t alarm because gen start and stopped due to grid bad voltage // he bypass =
grid and manually start the gen","Hyemafo Gildas","Warning","Warning","POWE=
R","Warning - Site on Battery","Grid fluctuation, site went alarm because g=
en start and stopped due to grid bad voltage // he bypass grid and manually=
 start the gen","landry.etame@ihstowers.com","2","09-11-2024 22:48:39","Sag=
emcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003541879","Nko=
g-Edzen","","09-11-2024 21:20:44","09-11-2024 21:11:25","09-11-2024 23:40:2=
5"," site went down because gen fails to start due to gen belt cut //  belt=
 replaced and gen manually started","Parker Tchoup","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Fan Belt","site went down because gen fails to sta=
rt due to gen belt cut //  belt replaced and gen manually started","christi=
an.fonkou@ihstowers.com","560","09-11-2024 21:20:44","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0003541731","Mon=
tee Jouvence","","09-11-2024 20:54:24","09-11-2024 20:47:17","09-11-2024 22=
:28:17","Grid fluctuation, site went down because gen start and stopped due=
 to grid bad voltage // he bypass grid and manually start the gen","Hyemafo=
 Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // he bypass grid and manually start the gen","christia=
n.fonkou@ihstowers.com","427","09-11-2024 20:54:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003541461","Nkolo II=
 New","","09-11-2024 20:15:40","09-11-2024 20:10:53","09-11-2024 20:14:49",=
"Cascaded Incident from TTO3450370","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore Gen start due to poor backup// Gen started automaticaly","system","287"=
,"09-11-2024 20:15:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003541458","M=
imboman-Village","IHS_YND_709","09-11-2024 20:15:11","09-11-2024 20:10:53",=
"09-11-2024 20:14:49","Grid outage, site went down before Gen start due to =
poor backup// Gen started automaticaly","Mba Lazare Herve","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before Gen start due to poor backup// Gen started automaticaly=
","emmanuel.ghani@ihstowers.com","259","09-11-2024 20:15:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003541199","M=
vog-Manga","","09-11-2024 19:36:57","09-11-2024 19:32:46","09-11-2024 20:31=
:09","Active// No power issue on site. Site on Grid Ubai=3D54.3 V, The FME =
TX Lionel Adjep/655184876/ From Huawei is informed. Notice that we have dis=
junction at BTS OCM","Albran Byorel","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue on=
 site. Site on Grid Ubai=3D54.3 V, The FME TX Lionel Adjep/655184876/ From =
Huawei is informed. Notice that we have disjunction at BTS OCM","emmanuel.g=
hani@ihstowers.com","253","09-11-2024 19:36:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003541015","A=
wae Ewonkan","","09-11-2024 19:18:14","09-11-2024 19:12:07","09-11-2024 20:=
04:08","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage// He bypassed Grid and started Gen manualy","Albran Byo=
rel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, site went down because gen start and stopped due to g=
rid bad voltage// He bypassed Grid and started Gen manualy","emmanuel.ghani=
@ihstowers.com","368","09-11-2024 19:18:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003540795","M=
ANGUIERS CHAPELLE","","09-11-2024 19:00:35","09-11-2024 18:35:25","09-11-20=
24 19:55:50","Site went down down because CB(125A) tripped in PWC who feeds=
 equipments OCM// He did a bridge with another CB(63A)","Fabrice Pouakam","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breake=
r Issue","Site went down down because CB(125A) tripped in PWC who feeds equ=
ipments OCM// He did a bridge with another CB(63A)","emmanuel.ghani@ihstowe=
rs.com","1512","09-11-2024 19:00:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003540760","Lobo OCM=
","","09-11-2024 18:59:00","09-11-2024 18:51:46","09-11-2024 18:55:19","Cas=
caded Incident from TTO3449521","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, Site went down=
 before Gen start due to poor backup// Gen started automatically","system",=
"434","09-11-2024 18:59:00","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003540734","N=
KOMEKUI OCM","IHS_YND_341","09-11-2024 18:56:53","09-11-2024 18:51:46","09-=
11-2024 18:55:19","Grid outage, Site went down before Gen start due to poor=
 backup// Gen started automatically","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outag=
e, Site went down before Gen start due to poor backup// Gen started automat=
ically","emmanuel.ghani@ihstowers.com","308","09-11-2024 18:56:53","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003540720","Akak-Nko=
zoa-MTN-IHS","","09-11-2024 18:55:10","09-11-2024 18:49:42","09-11-2024 19:=
02:09","Cascaded Incident from TTO3449488","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","GEN overlead caused by Hu=
awei bay controller out of order  // reset of GEN's Card and manual start o=
f GEN","system","328","09-11-2024 18:55:10","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003540400","Nko=
abang2","","09-11-2024 18:30:20","09-11-2024 18:19:12","09-11-2024 18:38:08=
","Grid outage site went down because Gen started and stopped with alarm un=
der voltage // He reset the Gen card and Gen manually started","Mba Lazare =
Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage site went down because Gen started and stopped with alarm under vol=
tage // He reset the Gen card and Gen manually started","christian.fonkou@i=
hstowers.com","796","09-11-2024 18:30:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003540175","M=
ANGUIERS CHAPELLE","","09-11-2024 18:04:05","09-11-2024 17:57:56","09-11-20=
24 18:04:20","Grid outage, Site went down before Gen start due to poor back=
up// Gen started automatically","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went d=
own before Gen start due to poor backup// Gen started automatically","emman=
uel.ghani@ihstowers.com","370","09-11-2024 18:04:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003539994","N=
kolo II New","","09-11-2024 17:43:47","09-11-2024 17:38:41","09-11-2024 17:=
45:52","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, site went down before Gen start due to poor =
backup// Gen started automaticaly","emmanuel.ghani@ihstowers.com","1972","0=
9-11-2024 17:43:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003539966","M=
imboman-Village","IHS_YND_709","09-11-2024 17:39:52","09-11-2024 17:38:41",=
"09-11-2024 17:45:52","Grid outage, site went down before Gen start due to =
poor backup// Gen started automaticaly","Mba Lazare Herve","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before Gen start due to poor backup// Gen started automaticaly=
","emmanuel.ghani@ihstowers.com","73","09-11-2024 17:39:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003539942","Messassi=
 okolo","","09-11-2024 17:34:40","09-11-2024 17:29:35","09-11-2024 17:41:28=
","Cascaded Incident from TTO3448592","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
fore Gen start due to poor backup// Gen started automatically","system","30=
5","09-11-2024 17:34:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0003539937","E=
MANA BILICK CITY","IHS_YND_279","09-11-2024 17:33:40","09-11-2024 17:29:35"=
,"09-11-2024 17:41:28","Grid outage, Site went down before Gen start due to=
 poor backup// Gen started automatically","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, S=
ite went down before Gen start due to poor backup// Gen started automatical=
ly","emmanuel.ghani@ihstowers.com","246","09-11-2024 17:33:40","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003539913","S=
atcom","","09-11-2024 17:30:58","09-11-2024 17:25:52","09-11-2024 18:30:29"=
,"No power issue on site ;site on Grid with Ubaie=3D54 V  The Tx Fme Armand=
 Ngeutsa/699949553/ from Huawei is Informed, REPETITIF ISSUE.site up at 05:=
40 PM","Delor Telezing","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site ;site on Grid wi=
th Ubaie=3D54 V  The Tx Fme Armand Ngeutsa/699949553/ from Huawei is Inform=
ed, REPETITIF ISSUE.site up at 05:40 PM","emmanuel.ghani@ihstowers.com","30=
6","09-11-2024 17:30:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003539881","E=
lig Edzoa","","09-11-2024 17:26:54","09-11-2024 17:24:49","09-11-2024 17:27=
:13","Grid outage, Site went down before Gen start due to poor battery back=
up// Gen started automatically","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went do=
wn before Gen start due to poor battery backup// Gen started automatically"=
,"emmanuel.ghani@ihstowers.com","126","09-11-2024 17:26:54","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003539450","N=
yanon","","09-11-2024 16:26:07","09-11-2024 16:22:57","09-11-2024 20:18:21"=
,"Hybrid Gen Site: site went down because of the dysfunctioning of hybrid s=
ystem // He reset it, site on Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: site went down b=
ecause of the dysfunctioning of hybrid system // He reset it, site on Gen",=
"emmanuel.ghani@ihstowers.com","192","09-11-2024 16:26:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0003539240","Hotel de=
 Ville Yde","","09-11-2024 15:59:40","09-11-2024 15:57:35","09-11-2024 16:4=
2:00","Cascaded Incident from TTO3447752","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage// He deployed MDG =
13KVA","system","125","09-11-2024 15:59:40","Sagemcom CMR"
"Closed Complete","Warning","CTR_031","IHS_YND_319","NOCINC0003539235","SOA=
 2","","09-11-2024 15:58:53","","","Site was on Gen due to Grid outage, Sit=
e alarming on battery because Gen stopped with ""High Temp"" alarm// He add=
ed water and started Gen manualy","Siligap Boris","Warning","Warning","POWE=
R","Warning - Site on Battery","Site was on Gen due to Grid outage, Site al=
arming on battery because Gen stopped with ""High Temp"" alarm// He added w=
ater and started Gen manualy","joelle.ekessi@ihstowers.com","363","09-11-20=
24 15:58:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0003539234","N=
R-Bastos","IHS_YND_019","09-11-2024 15:58:42","09-11-2024 15:57:35","09-11-=
2024 16:42:00","Grid outage// He deployed MDG 13KVA","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid outage// He deployed =
MDG 13KVA","emmanuel.ghani@ihstowers.com","68","09-11-2024 15:58:42","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003539138","S=
tade-Abega","","09-11-2024 15:47:22","09-11-2024 15:29:11","09-11-2024 17:2=
1:03","Site went down due to insuffisance of rectifier(03/04)// Site stabil=
ized (rectifier to be added)","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to insuffisance of re=
ctifier(03/04)// Site stabilized (rectifier to be added)","emmanuel.ghani@i=
hstowers.com","1092","09-11-2024 15:47:22","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003538586","Bas=
tos Amb Coree","","09-11-2024 14:58:49","09-11-2024 14:56:41","09-11-2024 1=
7:00:15","Grid Outage No Space to deploy a MDG  //Grid Restored","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No=
 Space to deploy a MDG  //Grid Restored","christian.fonkou@ihstowers.com","=
129","09-11-2024 14:58:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003538585","O=
lembe-Terminus","","09-11-2024 14:58:19","09-11-2024 14:55:12","09-11-2024 =
16:15:21","site was On Gen due Grid fluctuation, Site went down because Gen=
 overload (12Kva, 185A)// He reduced 01 rectifier","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","site was On Gen due Gr=
id fluctuation, Site went down because Gen overload (12Kva, 185A)// He redu=
ced 01 rectifier","emmanuel.ghani@ihstowers.com","188","09-11-2024 14:58:19=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003538410","Afanoya"=
,"","09-11-2024 14:39:20","09-11-2024 14:17:26","09-11-2024 15:48:13","Casc=
aded Incident from TTO3446776","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because CB(2*50A) of re=
ctifier disjuncted causing by load increase //he reamed CB","system","1314"=
,"09-11-2024 14:39:20","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0003538398","MBA=
LNGONG LYCEE","","09-11-2024 14:37:18","09-11-2024 14:17:26","09-11-2024 15=
:48:13","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Site went down because CB(2*50A) of rectifier disjuncted caus=
ing by load increase //he reamed CB","christian.fonkou@ihstowers.com","1895=
","09-11-2024 14:37:18","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0003538373","ELO=
UMDEM CARRIERE","","09-11-2024 14:32:37","09-11-2024 14:17:26","09-11-2024 =
15:48:13","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","Site went down because CB(2*50A) of rectifier disjuncted ca=
using by load increase //he reamed CB","christian.fonkou@ihstowers.com","18=
37","09-11-2024 14:32:37","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_270","NOCINC0003538366","Santa Barb=
ara Yde","","09-11-2024 14:31:34","","","Site alarming on battery because 2=
/5 rectifiers went faulty// He replaced rectifiers faulty(Site on 05 rectif=
iers)","Delor Telezing","Warning","Warning","POWER","Warning - Site on Batt=
ery","Site alarming on battery because 2/5 rectifiers went faulty// He repl=
aced rectifiers faulty(Site on 05 rectifiers)","joelle.ekessi@ihstowers.com=
","3","09-11-2024 14:31:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003538258","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","09-11-2024 14:19:35","09-11-=
2024 14:17:26","09-11-2024 15:48:13","Site went down because CB(2*50A) of r=
ectifier disjuncted causing by load increase //he reamed CB","Hyemafo Gilda=
s","Equipment Repair","Passive","Rectifier","Rectifier - Circuit Breaker","=
Site went down because CB(2*50A) of rectifier disjuncted causing by load in=
crease //he reamed CB","emmanuel.ghani@ihstowers.com","1090","09-11-2024 14=
:19:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003538050","N=
YOM 2 IHS","","09-11-2024 13:44:43","09-11-2024 13:42:22","09-11-2024 13:47=
:01","grid outage, site went down due to gen overload(15kva, 320A) // grid =
return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","grid outage, site went down due to gen overload(15kva, 320A) // g=
rid return","denis.mballa@ihstowers.com","142","09-11-2024 13:44:43","Sagem=
com CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003538022","ODZ=
A CITE MBIA","","09-11-2024 13:41:00","09-11-2024 13:38:53","09-11-2024 13:=
52:22","site went down due to work: The Team Tchoffo (653046755)/ From DCP =
working on site ""Installation cable Card on  ATS for control voltage// End=
 of work ","Albran Byorel","Installation Activity","Passive","Planned Activ=
ity","Installation Activity","site went down due to work: The Team Tchoffo =
(653046755)/ From DCP working on site ""Installation cable Card on  ATS for=
 control voltage// End of work ","rouselle.schoune@ihstowers.com","128","09=
-11-2024 13:41:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003537796","N=
KOLMEKONG YDE","","09-11-2024 13:19:57","09-11-2024 13:18:43","09-11-2024 1=
4:55:44","Site went down because cable burned in PWC// He replaced cable bu=
rned, Site on Grid ","Fabrice Pouakam","Equipment Repair","Passive","Infras=
tructure","Armoured Cable","Site went down because cable burned in PWC// He=
 replaced cable burned, Site on Grid ","denis.mballa@ihstowers.com","75","0=
9-11-2024 13:19:57","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003537641","Nsi=
meyong Terre Rouge","","09-11-2024 12:56:27","09-11-2024 12:55:21","09-11-2=
024 13:06:00","Grid outage, Site went down due to poor batteries backup bef=
ore Gen start //Gen started automatically","MINKA NICOLAS","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, Si=
te went down due to poor batteries backup before Gen start //Gen started au=
tomatically","rouselle.schoune@ihstowers.com","67","09-11-2024 12:56:27","S=
agemcom CMR"
"Closed Complete","Warning","T1505","IHS_YND_681","NOCINC0003537219","NKOLM=
EKONG YDE","","09-11-2024 12:04:20","","","Site alarming on battery because=
 cable burned in PWC// He replaced cable burned, Site on Grid","Fabrice Pou=
akam","Warning","Warning","POWER","Warning - Site on Battery","Site alarmin=
g on battery because cable burned in PWC// He replaced cable burned, Site o=
n Grid","alwine.fambou@ihstowers.com","2","09-11-2024 12:04:20","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003537177","B=
riqueterie","","09-11-2024 11:57:45","09-11-2024 11:52:29","09-11-2024 16:5=
8:01","Grid Outage No Space to deploy a MDG// Grid Restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spa=
ce to deploy a MDG// Grid Restored","denis.mballa@ihstowers.com","317","09-=
11-2024 11:57:45","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0003537176","Bri=
quetterie","","09-11-2024 11:57:43","09-11-2024 11:55:21","09-11-2024 17:01=
:21","Grid Outage No Space to deploy a MDG// Grid Restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spac=
e to deploy a MDG// Grid Restored","rouselle.schoune@ihstowers.com","143","=
09-11-2024 11:57:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003537078","S=
tade-Abega","","09-11-2024 11:46:58","09-11-2024 11:43:43","09-11-2024 11:5=
7:00","Grid fluctuation, site went down before Gen start due to poor batter=
y backup// Grid return","Mba Lazare Herve","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid fluctuation, site went dow=
n before Gen start due to poor battery backup// Grid return","denis.mballa@=
ihstowers.com","195","09-11-2024 11:46:58","Sagemcom CMR"
"Closed Complete","Warning","T0046","IHS_YND_191","NOCINC0003536434","Mball=
a II","","09-11-2024 10:16:28","","","site alarming because Gen failed to s=
tart due to mixture water and fuel in the tank // he purged the tank","Delo=
r Telezing","Warning","Warning","POWER","Warning - Site on Battery","site a=
larming because Gen failed to start due to mixture water and fuel in the ta=
nk // he purged the tank","alwine.fambou@ihstowers.com","3","09-11-2024 10:=
16:28","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003536019","Feb=
e Village","","09-11-2024 09:13:15","09-11-2024 09:08:09","09-11-2024 09:30=
:38","Grid outage, site went down before gen start due to poor battery back=
up // Gen started automatically","Mboua Thierry","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen started automatically=
","rouselle.schoune@ihstowers.com","307","09-11-2024 09:13:15","Sagemcom CM=
R"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003535977","NKO=
MEKUI OCM","","09-11-2024 09:10:54","09-11-2024 09:06:47","09-11-2024 09:34=
:12","Grid outage, site went down before gen start due to poor battery back=
up // Gen started automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite went down before gen start due to poor battery backup // Gen started au=
tomatically","rouselle.schoune@ihstowers.com","249","09-11-2024 09:10:54","=
Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0003535874","Bon=
djock","","09-11-2024 08:58:17","09-11-2024 08:54:50","09-11-2024 08:57:15"=
,"Grid fluctuation, site went down before Gen start due to poor backup// gr=
id return","Fanda Brice","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid fluctuation, site went down before Gen start=
 due to poor backup// grid return","rouselle.schoune@ihstowers.com","207","=
09-11-2024 08:58:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003535794","Ngoum","=
","09-11-2024 08:48:12","09-11-2024 08:42:22","09-11-2024 10:12:52","Cascad=
ed Incident from TTO3443677","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage, Site went down because Gen s=
tarted and stopped with ""low oil pressure""(unprouven) alarm causing by oi=
l sensor disfunction// He reset Gen card and started Gen manualy","system",=
"350","09-11-2024 08:48:12","Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0003535781","Yok=
o MTN","IHS_YND_475","09-11-2024 08:47:32","09-11-2024 08:42:22","09-11-202=
4 10:12:52","Grid outage, Site went down because Gen started and stopped wi=
th ""low oil pressure""(unprouven) alarm causing by oil sensor disfunction/=
/ He reset Gen card and started Gen manualy","Parker Tchoup","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went do=
wn because Gen started and stopped with ""low oil pressure""(unprouven) ala=
rm causing by oil sensor disfunction// He reset Gen card and started Gen ma=
nualy","rouselle.schoune@ihstowers.com","311","09-11-2024 08:47:32","Sagemc=
om CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003535659","Nko=
lbisson","","09-11-2024 08:38:15","09-11-2024 08:34:09","09-11-2024 08:47:0=
0","site went down due to work(Gaele(657108563) from Sagemcom , PM) // End =
of work","TIENTCHEU NZETCHIEU GAEL","Equipment Replacement","Passive","Plan=
ned Activity","Planned Activity - Passive","site went down due to work(Gael=
e(657108563) from Sagemcom , PM) // End of work","rouselle.schoune@ihstower=
s.com","246","09-11-2024 08:38:15","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003535407","Mok=
olo Yaounde","","09-11-2024 08:09:36","09-11-2024 08:07:30","09-11-2024 17:=
01:26","Grid Outage No Space to deploy a MDG// Grid Restored","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Sp=
ace to deploy a MDG// Grid Restored","rouselle.schoune@ihstowers.com","127"=
,"09-11-2024 08:09:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003535267","N=
omayos-IHS","","09-11-2024 07:48:44","09-11-2024 07:44:33","09-11-2024 08:0=
3:10","site went down due to dysfunctionning of 02/04 rectifiers // He rese=
t rectifiers, site on grid","Fanda Brice","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","site went down due to dysfunctionning of 02/04 =
rectifiers // He reset rectifiers, site on grid","denis.mballa@ihstowers.co=
m","252","09-11-2024 07:48:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003534423","N=
kozoa","","09-11-2024 05:23:16","09-11-2024 05:09:07","09-11-2024 05:35:38"=
,"grid outage, site went down due to gen overload (20kva, 320A) // He reduc=
ed the load and gen manually started","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","grid outage, site went down due to =
gen overload (20kva, 320A) // He reduced the load and gen manually started"=
,"alexandre.kamal@ihstowers.com","851","09-11-2024 05:23:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003534185","M=
arche Odza","","09-11-2024 03:58:27","09-11-2024 03:49:22","09-11-2024 05:1=
7:58","Active//No power issue on site ,site on Grid  wiith Ubaie=3D54.5 V T=
he TX FME Leonel Steve/ 655184876/  Huawei is informed","Albran Byorel","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site ,site on Grid  wiith Ubaie=3D54.5 V=
 The TX FME Leonel Steve/ 655184876/  Huawei is informed","alexandre.kamal@=
ihstowers.com","547","09-11-2024 03:58:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003534167","Entree C=
ite Verte","","09-11-2024 03:54:30","09-11-2024 03:42:59","09-11-2024 05:13=
:28","Cascaded Incident from TTO3441784","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active"," No power issue on site U=3D54v si=
te on grid Brice Stague of huawei is informed","system","691","09-11-2024 0=
3:54:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003534165","C=
ite-Verte","IHS_YND_543","09-11-2024 03:52:52","09-11-2024 03:42:59","09-11=
-2024 05:13:28"," No power issue on site U=3D54v site on grid Brice Stague =
of huawei is informed","","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm"," No power issue on site U=3D54v site =
on grid Brice Stague of huawei is informed","alexandre.kamal@ihstowers.com"=
,"594","09-11-2024 03:52:52","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003533573","NYO=
M FACE MAETUR","","09-11-2024 00:50:10","08-11-2024 23:53:45","08-11-2024 2=
3:54:21","No power issu site on grid with U=3D54,6v Symphorien(691316854) f=
rom Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issu site on=
 grid with U=3D54,6v Symphorien(691316854) from Huawei is informed","kamga.=
virgile@ihstowers.com","3386","09-11-2024 00:50:10","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0003533556","Fou=
da rue des g=E9n=E9raux","","09-11-2024 00:44:34","08-11-2024 23:53:00","08=
-11-2024 23:54:00","","Delor Telezing","Incorrectly Logged Tickets","Error"=
,"Error","Error","NO","kamga.virgile@ihstowers.com","3094","09-11-2024 00:4=
4:34","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003533404","Nko=
lbisson","","08-11-2024 23:59:28","08-11-2024 20:34:17","08-11-2024 22:47:4=
8","site went down due to disjunction Cb(80A) in Dc box // He make the brid=
ge with cb and , site on grid","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site w=
ent down due to disjunction Cb(80A) in Dc box // He make the bridge with CB=
  and , site on grid","kamga.virgile@ihstowers.com","12312","08-11-2024 23:=
59:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003533397","N=
kolndongo","","08-11-2024 23:57:39","08-11-2024 23:48:36","09-11-2024 01:58=
:43","Grid fluctuation, site went down due to lack on 01 phase on site //He=
 make the bridge on good phase","MINKA NICOLAS","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","Grid fluctuation, site went =
down due to lack on 01 phase on site //He make the bridge on good phase","a=
lexandre.kamal@ihstowers.com","544","08-11-2024 23:57:39","Sagemcom CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0003533257","NYA=
NON/DEMBO","","08-11-2024 23:35:36","08-11-2024 23:18:11","08-11-2024 23:35=
:11","site went down because gen failed to start due to fuel theft//refueli=
ng done","TIENTCHEU NZETCHIEU GAEL","Site Asset Theft","Theft","Theft","Die=
sel Theft","site went down because gen failed to start due to fuel theft//r=
efueling done","kamga.virgile@ihstowers.com","1046","08-11-2024 23:35:36","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0003533040","M=
vog-Ebanda","","08-11-2024 23:01:21","08-11-2024 19:25:14","08-11-2024 19:2=
8:26","Active: no power issue, site is on grid with Ubaie=3D54V, Armand Ngu=
etsa(691144412) from Huawei is informed","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
: no power issue, site is on grid with Ubaie=3D54V, Armand Nguetsa(69114441=
2) from Huawei is informed","alexandre.kamal@ihstowers.com","12969","08-11-=
2024 23:01:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003531736","M=
ANGUIERS CHAPELLE","","08-11-2024 20:43:27","08-11-2024 20:00:17","08-11-20=
24 22:44:41","Site went down due to OCM Circuit Breaker down in the PWC (Di=
sjunction of 125 A) due to grid fluctuations //He rearmed  the Circuit Brea=
ker,site on Grid.","Fabrice Pouakam","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Circuit Breaker Issue","Site went down due to OCM C=
ircuit Breaker down in the PWC (Disjunction of 125 A) due to grid fluctuati=
ons //He rearmed  the Circuit Breaker,site on Grid.","stephane.nkamwa@ihsto=
wers.com","2591","08-11-2024 20:43:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003531636","Dong",""=
,"08-11-2024 20:28:31","08-11-2024 20:08:14","08-11-2024 20:08:15","Cascade=
d Incident from TTO3438677","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","IMPACTED BY MBANDJOCK CTR_030 wich is not man=
aging by IHS","system","1217","08-11-2024 20:28:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_010","NOCINC0003531634","CNR","",=
"08-11-2024 20:28:31","08-11-2024 20:08:14","08-11-2024 20:08:15","Cascaded=
 Incident from TTO3438677","Mboua Thierry","Cascade Outage","Active","Casca=
de Active","Cascade Active","IMPACTED BY MBANDJOCK CTR_030 wich is not mana=
ging by IHS","system","1217","08-11-2024 20:28:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003531631","Nguila",=
"","08-11-2024 20:28:30","08-11-2024 20:08:14","08-11-2024 20:08:15","Casca=
ded Incident from TTO3438677","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","IMPACTED BY MBANDJOCK CTR_030 wich is not m=
anaging by IHS","system","1216","08-11-2024 20:28:30","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003531365","NYO=
M FACE MAETUR","","08-11-2024 19:56:20","08-11-2024 19:47:15","08-11-2024 2=
2:31:53","Site went down because 01 rectifier faulty // he replaced the rec=
tifier faulty","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down because 01 rectifier faulty // he replace=
d the rectifier faulty","landry.etame@ihstowers.com","546","08-11-2024 19:5=
6:20","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003531283","ODZ=
A CITE MBIA","","08-11-2024 19:44:26","08-11-2024 19:36:19","08-11-2024 20:=
10:05","Grid bad voltage,DG failed to start : No RCP //Bypass Grid and manu=
ally start of DG.","Albran Byorel","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Grid bad voltage,DG failed to start : No =
RCP //Bypass Grid and manually start of DG.","landry.etame@ihstowers.com","=
488","08-11-2024 19:44:26","Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0003530605","Don=
ga","","08-11-2024 18:44:18","08-11-2024 18:40:13","08-11-2024 21:24:30","g=
rid outage, site went down because gen failed to start due to dysfunctionni=
ng of hybrid system // He reset gen card and manually started (Investigatio=
n ongoing)","Parker Tchoup","Equipment Repair","Passive","Hybrid","Hybrid M=
odule","grid outage, site went down because gen failed to start due to dysf=
unctionning of hybrid system // He reset gen card and manually started (Inv=
estigation ongoing)","landry.etame@ihstowers.com","246","08-11-2024 18:44:1=
8","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003529120","N=
yanon","","08-11-2024 17:36:50","08-11-2024 17:16:39","08-11-2024 19:52:39"=
,"Hybrid Gen Site: site went down because of the dysfunctioning of hybrid s=
ystem // He reset it, site on Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: site went down b=
ecause of the dysfunctioning of hybrid system // He reset it, site on Gen",=
"stephane.nkamwa@ihstowers.com","1212","08-11-2024 17:36:50","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003528300","NKO=
MEKUI OCM","","08-11-2024 16:09:04","08-11-2024 16:03:56","08-11-2024 16:05=
:56","No power issue site on Gen with U=3D54.3 V The Tx Fme Mohamadou mouam=
 // 691144435 from Huawei is informed site impacted by Mbankolo camtel","TI=
ENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue site on Gen with U=3D54.=
3 V The Tx Fme Mohamadou mouam // 691144435 from Huawei is informed site im=
pacted by Mbankolo camtel","landry.etame@ihstowers.com","309","08-11-2024 1=
6:09:04","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003528129","Nko=
abang Ebolmedjock","","08-11-2024 15:39:39","08-11-2024 15:33:18","08-11-20=
24 15:49:18","no power issue U:54,V site on Grid. TX FME Leonel Steve (6551=
84876) from Huawei is informed,","Mba Lazare Herve","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power is=
sue U:54,V site on Grid. TX FME Leonel Steve (655184876) from Huawei is inf=
ormed,","landry.etame@ihstowers.com","382","08-11-2024 15:39:39","Sagemcom =
CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003527765","Nko=
lbisson","IHS_YND_763","08-11-2024 15:02:01","08-11-2024 14:57:54","08-11-2=
024 14:59:54","Active// No power issue on site, Site on Gen Ubai=3D 54.8V, =
The Team Kenfack/699949693/ From Huawei working on site","TIENTCHEU NZETCHI=
EU GAEL","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active// No power issue on site, Site on Gen Ubai=3D 5=
4.8V, The Team Kenfack/699949693/ From Huawei working on site","landry.etam=
e@ihstowers.com","248","08-11-2024 15:02:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0003527493","A=
bang","","08-11-2024 14:42:46","08-11-2024 14:05:18","08-11-2024 17:05:23",=
"","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","Active// No power issue on site, Site on Grid Ubai=3D 54.8V, The FM=
E TX Georges ( 697461814) /From HUAWEI is informed","stephane.nkamwa@ihstow=
ers.com","2322","08-11-2024 14:42:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0003527484","N=
kolangaa","IHS_YND_290","08-11-2024 14:41:25","08-11-2024 14:05:18","08-11-=
2024 18:27:01","Active// No power issue on site, Site on Grid Ubai=3D 54.8V=
, The FME TX Georges ( 697461814) /From HUAWEI is informed","Mba Lazare Her=
ve","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// No power issue on site, Site on Grid Ubai=3D 54.8V=
, The FME TX Georges ( 697461814) /From HUAWEI is informed","stephane.nkamw=
a@ihstowers.com","2169","08-11-2024 14:41:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003527149","E=
lig-Edzoa","","08-11-2024 13:59:43","08-11-2024 13:54:36","08-11-2024 14:15=
:20","Grid outage// He connected MDG 20kva","","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue","Grid outage// He connected MDG 20kv=
a","emmanuel.ghani@ihstowers.com","309","08-11-2024 13:59:43","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_285","NOCINC0003526735","Nkolbiss=
on","IHS_YND_763","08-11-2024 13:14:00","08-11-2024 13:08:12","08-11-2024 1=
3:15:29","Active// No power issue on site, Site on Gen Ubai=3D 54.8V, The T=
eam Kenfack/699949693/ From Huawei working on site","TIENTCHEU NZETCHIEU GA=
EL","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// No power issue on site, Site on Gen Ubai=3D 54.8V,=
 The Team Kenfack/699949693/ From Huawei working on site","system","348","0=
8-11-2024 13:14:00","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003526731","Nko=
lbisson usines des eaux 2","","08-11-2024 13:13:19","08-11-2024 13:08:12","=
08-11-2024 14:59:54","Active// No power issue on site, Site on Gen Ubai=3D =
54.8V, The Team Kenfack/699949693/ From Huawei working on site","TIENTCHEU =
NZETCHIEU GAEL","Cascade Outage","Active","Cascade Active","Cascade Active"=
,"Active// No power issue on site, Site on Gen Ubai=3D 54.8V, The Team Kenf=
ack/699949693/ From Huawei working on site","christian.fonkou@ihstowers.com=
","308","08-11-2024 13:13:19","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003526508","NKO=
MEKUI OCM","","08-11-2024 12:57:47","08-11-2024 12:52:09","08-11-2024 13:00=
:15","Grid Outage, Site went down before Gen start due to poor backup// Gen=
 started automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid Outage, Site went =
down before Gen start due to poor backup// Gen started automatically","chri=
stian.fonkou@ihstowers.com","339","08-11-2024 12:57:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003526164","S=
atcom","","08-11-2024 12:24:28","08-11-2024 12:21:21","08-11-2024 13:25:58"=
,"Active: no power issue, site is on grid with Ubaie=3D53V, Armand Nguetsa(=
691144412) from Huawei is informed","Delor Telezing","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no=
 power issue, site is on grid with Ubaie=3D53V, Armand Nguetsa(691144412) f=
rom Huawei is informed","emmanuel.ghani@ihstowers.com","188","08-11-2024 12=
:24:28","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003525860","ODZ=
A CITE MBIA","","08-11-2024 11:58:18","08-11-2024 11:53:00","08-11-2024 12:=
47:14","Grid OUTAGE, site went down because gen fails to start due to ATS d=
isfunctionning // Gen manually start","Albran Byorel","Equipment Repair","P=
assive","Control Panel","ATS-AMF Issue","Grid OUTAGE, site went down becaus=
e gen fails to start due to ATS disfunctionning // Gen manually start","chr=
istian.fonkou@ihstowers.com","319","08-11-2024 11:58:18","Sagemcom CMR"
"Closed Complete","Warning","T1071","IHS_YND_343","NOCINC0003525853","Mbedo=
umou - Ekali","","08-11-2024 11:57:57","","","Grid outage, Site alarming on=
 battery because Gen ran until fuel shortage// Refueling Done","Albran Byor=
el","Warning","Warning","POWER","Warning - Site on Battery","Grid outage, S=
ite alarming on battery because Gen ran until fuel shortage// Refueling Don=
e","joelle.ekessi@ihstowers.com","2","08-11-2024 11:57:57","Sagemcom CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0003523981","Hot=
el de Ville Yde","","08-11-2024 09:10:58","08-11-2024 09:01:50","08-11-2024=
 11:55:09","Active: No power issue, site is on grid with Ubaie=3D53V, Brice=
 tsague(650214096) from Huawei is informed","Paul BIBOUM","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue, site is on grid with Ubaie=3D53V, Brice tsague(650214096=
) from Huawei is informed","christian.fonkou@ihstowers.com","548","08-11-20=
24 09:10:58","Sagemcom CMR"
"Closed Complete","Site Down","T2743","IHS_YND_721","NOCINC0003523720","VOI=
RIE MUNICIPALE YAOUNDE","","08-11-2024 08:41:49","08-11-2024 08:35:41","08-=
11-2024 10:12:36","site went down due to disjunction Cb(2*63A) in Dc box //=
 He changed Cb(2*63A) , site on grid","Paul BIBOUM","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went do=
wn due to disjunction Cb(2*63A) in Dc box // He changed Cb(2*63A) , site on=
 grid","christian.fonkou@ihstowers.com","368","08-11-2024 08:41:49","Sagemc=
om CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0003523602","Eli=
g Edzoa","","08-11-2024 08:13:51","08-11-2024 08:11:46","08-11-2024 08:13:4=
7","Grid outage, site went down before Gen start due to poor backup// Gen s=
tarted automaticaly","Delor Telezing","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, site went down before G=
en start due to poor backup// Gen started automaticaly","christian.fonkou@i=
hstowers.com","126","08-11-2024 08:13:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003523205","L=
abogenie","","08-11-2024 07:00:25","08-11-2024 06:54:08","08-11-2024 07:15:=
50","Active// No power issue on site, Site on Grid Ubai=3D 54.8V, The FME T=
X Georges ( 697461814) /From HUAWEI is informed // labo genie","","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power issue on site, Site on Grid Ubai=3D 54.8V, The FME TX =
Georges ( 697461814) /From HUAWEI is informed // labo genie","emmanuel.ghan=
i@ihstowers.com","378","08-11-2024 07:00:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003522555","S=
ous Prefecture","","08-11-2024 05:17:37","08-11-2024 05:13:35","08-11-2024 =
05:14:35","Active// No power issue on site, Site on Grid Ubai=3D 54.8V, The=
 FME TX Georges ( 697461814) /From HUAWEI is informed","Fanda Brice","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue on site, Site on Grid Ubai=3D 54.8V, The FME =
TX Georges ( 697461814) /From HUAWEI is informed","ludivine.ngamaleu@ihstow=
ers.com","243","08-11-2024 05:17:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0003521439","Okola OC=
M","","07-11-2024 23:43:01","07-11-2024 23:36:57","08-11-2024 02:17:57","Ca=
scaded Incident from TTO3426945","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue on site Ubaie =
54,1V Site on Grid (hybrid site). gr=E9groire (652070658/Huawei) is informe=
d.","system","363","07-11-2024 23:43:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003520989","ELOUMDEM=
 CARRIERE 2","","07-11-2024 22:03:30","07-11-2024 21:49:54","07-11-2024 22:=
55:30","Cascaded Incident from TTO3426398","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because gen start and stopped due to grid bad voltage // gen manually s=
tarted","system","816","07-11-2024 22:03:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003520988","Eto koss=
 Yde","","07-11-2024 22:03:30","07-11-2024 21:49:54","07-11-2024 22:55:30",=
"Cascaded Incident from TTO3426398","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause gen start and stopped due to grid bad voltage // gen manually started"=
,"system","816","07-11-2024 22:03:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003520979","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","07-11-2024 22:01:25","07-11-2024 21:49=
:54","07-11-2024 22:55:30","Grid fluctuation, site went down because gen st=
art and stopped due to grid bad voltage // gen manually started","Fanda Bri=
ce","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage // gen manually started","kamga.virgile@ihstowers.com","693"=
,"07-11-2024 22:01:25","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_768","NOCINC0003520950","ELOUMDEM CARRIER=
E 2","","07-11-2024 21:56:20","","","Cascaded Incident from TTO3426343","Fa=
nda Brice","","","","","","system","384","07-11-2024 21:56:20","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0003520725","Abang","=
","07-11-2024 21:26:00","07-11-2024 21:15:58","07-11-2024 21:16:48","Cascad=
ed Incident from TTO3426068","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site, Site on G=
rid UBAIE=3D53.4V  and Geoge (697461814) From huawei is informed","system",=
"602","07-11-2024 21:26:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0003520708","N=
kolangaa","IHS_YND_290","07-11-2024 21:23:03","07-11-2024 21:15:58","08-11-=
2024 00:54:48","Active//No power issue on site, Site on Grid UBAIE=3D53.4V =
 and Geoge (697461814) From huawei is informed","Mba Lazare Herve","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active//No power issue on site, Site on Grid UBAIE=3D53.4V  and Geoge (=
697461814) From huawei is informed","alexandre.kamal@ihstowers.com","426","=
07-11-2024 21:23:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003519906","Lobo OCM=
","","07-11-2024 19:40:43","07-11-2024 16:36:48","07-11-2024 16:40:48","Cas=
caded Incident from TTO3425121","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // gen start automatically","s=
ystem","11035","07-11-2024 19:40:43","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003519892","N=
KOMEKUI OCM","IHS_YND_341, IHS_YND_713","07-11-2024 19:39:57","07-11-2024 1=
6:36:48","07-11-2024 16:40:48","Grid outage, site went down before gen star=
t due to poor battery backup // gen start automatically","TIENTCHEU NZETCHI=
EU GAEL","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","Grid outage, site went down before gen start due to poor battery =
backup // gen start automatically","alexandre.kamal@ihstowers.com","10990",=
"07-11-2024 19:39:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003519713","M=
fou EPC","","07-11-2024 19:07:33","07-11-2024 18:57:59","07-11-2024 21:15:5=
9","Grid fluctuation, site went down because gen start and stopped due to g=
rid bad voltage // he bypass grid and manually start the gen","Mba Lazare H=
erve","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, site went down because gen start and stopped due to =
grid bad voltage // he bypass grid and manually start the gen","alexandre.k=
amal@ihstowers.com","575","07-11-2024 19:07:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003519050","MEHANDAN=
","","07-11-2024 17:31:41","07-11-2024 17:23:41","07-11-2024 19:33:42","Cas=
caded Incident from TTO3424029","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site U=3D53v site on gr=
id Lionel steeve of huawei is informed","system","480","07-11-2024 17:31:41=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003518993","O=
dza II OCM","IHS_YND_528","07-11-2024 17:30:44","07-11-2024 17:23:41","07-1=
1-2024 19:33:42","No power issue on site U=3D53v site on grid Lionel steeve=
 of huawei is informed","Albran Byorel","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D53v site on grid Lionel steeve of huawei is informed","alexandre.kamal@=
ihstowers.com","424","07-11-2024 17:30:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0003518735","N=
KONGKARAK","","07-11-2024 16:47:04","07-11-2024 16:36:48","07-11-2024 16:40=
:48","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage, site went down before gen start due to=
 poor battery backup // gen start automatically","alexandre.kamal@ihstowers=
.com","11065","07-11-2024 16:47:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0003518251","E=
vodoula OCM","","07-11-2024 15:39:16","07-11-2024 15:22:10","07-11-2024 15:=
46:10","Grid Outage, site went down because Gen stopped with ""high temp"" =
alarm// He added water and started Gen manualy","TIENTCHEU NZETCHIEU GAEL",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage=
, site went down because Gen stopped with ""high temp"" alarm// He added wa=
ter and started Gen manualy","alexandre.kamal@ihstowers.com","1027","07-11-=
2024 15:39:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0003518239","Nkolkoum=
ou OCM","","07-11-2024 15:37:11","07-11-2024 15:03:12","07-11-2024 15:46:12=
","Cascaded Incident from TTO3422943","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid outage, site wen=
t down due to main gen faulty // Mobile gen 15KVA has deployed","system","2=
039","07-11-2024 15:37:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003518101","N=
kolbisson usine des eaux","IHS_YND_712","07-11-2024 15:17:15","07-11-2024 1=
5:03:12","07-11-2024 15:46:12","Grid outage, site went down due to main gen=
 faulty // Mobile gen 15KVA has deployed","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage, s=
ite went down due to main gen faulty // Mobile gen 15KVA has deployed","ale=
xandre.kamal@ihstowers.com","844","07-11-2024 15:17:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003517733","Kondengu=
i","","07-11-2024 14:37:51","07-11-2024 14:33:41","07-11-2024 14:52:41","Ca=
scaded Incident from TTO3422509","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage // Grid return","system",=
"250","07-11-2024 14:37:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003517725","E=
mombo-Tchad","IHS_YND_114","07-11-2024 14:36:44","07-11-2024 14:33:41","07-=
11-2024 14:52:41","Grid outage // Grid return","","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","Grid outage // Grid return","ale=
xandre.kamal@ihstowers.com","184","07-11-2024 14:36:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003517710","N=
kolondom","","07-11-2024 14:34:58","07-11-2024 14:17:56","07-11-2024 15:16:=
56","gen stoppen and grid return, site went down due to eneo contactor not =
excited // He excited Eneo contactor, site on grid","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","ATS-AMF Issue","gen stoppen and gr=
id return, site went down due to eneo contactor not excited // He excited E=
neo contactor, site on grid","alexandre.kamal@ihstowers.com","1023","07-11-=
2024 14:34:58","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003517594","Bit=
oto","","07-11-2024 14:03:13","07-11-2024 13:54:03","07-11-2024 14:10:56","=
Grid outage  site went down because Gen fails to start due to Gen overload(=
20kva,315A) // he reuice the load and manualy start the gen","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage=
  site went down because Gen fails to start due to Gen overload(20kva,315A)=
 // he reuice the load and manualy start the gen","landry.etame@ihstowers.c=
om","834","07-11-2024 14:03:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003517441","A=
wae Ewonkan","","07-11-2024 13:41:49","07-11-2024 13:25:19","07-11-2024 13:=
50:21","Active, no power issue, U=3D53v on grid, Tx fme George/697461814 fr=
om huawei is informed","Albran Byorel","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issue, =
U=3D53v on grid, Tx fme George/697461814 from huawei is informed","stephane=
.nkamwa@ihstowers.com","991","07-11-2024 13:41:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003517409","Entree C=
ite Verte","","07-11-2024 13:35:51","07-11-2024 13:20:26","07-11-2024 13:25=
:26","Cascaded Incident from TTO3422092","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","tx","system","925","07-11-2024 13:=
35:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0003517408","Nkomkana=
","","07-11-2024 13:35:50","07-11-2024 13:20:26","07-11-2024 13:25:26","Cas=
caded Incident from TTO3422092","","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","tx","system","924","07-11-2024 13:35:50","Sagemcom CMR=
"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0003517407","San=
ta Barbara Yde","","07-11-2024 13:35:42","07-11-2024 13:28:31","07-11-2024 =
13:30:43","","Delor Telezing","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site ubaie=3D54=
v site on grid Rm Alain  is informed, Simphorien is unreachable","landry.et=
ame@ihstowers.com","432","07-11-2024 13:35:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003517396","C=
ite-Verte","IHS_YND_200, IHS_YND_543","07-11-2024 13:33:35","07-11-2024 13:=
20:26","07-11-2024 13:25:26"," No power issue on site U=3D54v site on grid =
Brice Stague of huawei is informed","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm"," No power issue on site =
U=3D54v site on grid Brice Stague of huawei is informed","stephane.nkamwa@i=
hstowers.com","790","07-11-2024 13:33:35","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0003515775","Tou=
ring Club International","","07-11-2024 10:18:22","07-11-2024 10:14:15","07=
-11-2024 10:23:02","Grid outage, Site went down because Gen started and sto=
pped with ""oil pressure"" alarm(unprouven)// He reset Gen card and started=
 Gen manualy(Investigation ongoing)","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage, Site went down becau=
se Gen started and stopped with ""oil pressure"" alarm(unprouven)// He rese=
t Gen card and started Gen manualy(Investigation ongoing)","landry.etame@ih=
stowers.com","248","07-11-2024 10:18:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003515546","B=
astos Bethesda","","07-11-2024 09:43:22","07-11-2024 09:38:13","07-11-2024 =
09:46:28","Grid outage,site went down before DG start : Poor Batteries Back=
up //DG started automatically.","Mboua Thierry","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage,site went down=
 before DG start : Poor Batteries Backup //DG started automatically.","step=
hane.nkamwa@ihstowers.com","311","07-11-2024 09:43:22","Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0003514695","Yok=
o MTN","","07-11-2024 07:52:18","07-11-2024 07:50:27","07-11-2024 07:52:10"=
,"Active// No power issue on site, Site on battery 49.8V, The FME TX Gr=E9g=
oire(65547479) From Huawei is informed and Up at 07:52 AM","Parker Tchoup",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active// No power issue on site, Site on battery 49.8V, The FME=
 TX Gr=E9goire(65547479) From Huawei is informed and Up at 07:52 AM","landr=
y.etame@ihstowers.com","112","07-11-2024 07:52:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003514548","O=
lembe-Terminus","","07-11-2024 07:27:23","07-11-2024 07:24:15","07-11-2024 =
08:48:09","Site went down due to 2/4 rectifiers hanging because of first re=
ctifier slot dysfunctionning//Reset Rectifiers.","Fabrice Pouakam","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","Site went down due to =
2/4 rectifiers hanging because of first rectifier slot dysfunctionning//Res=
et Rectifiers .","stephane.nkamwa@ihstowers.com","189","07-11-2024 07:27:23=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003514343","L=
abogenie","","07-11-2024 07:01:02","07-11-2024 07:00:26","07-11-2024 10:20:=
15","Active// No power issue on site, Site on Grid Ubai=3D 54.8V, The FME T=
X 697461814/From HUAWEI is informed","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue=
 on site, Site on Grid Ubai=3D 54.8V, The FME TX 697461814/From HUAWEI is i=
nformed","stephane.nkamwa@ihstowers.com","37","07-11-2024 07:01:02","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0003513369","N=
kolso","","07-11-2024 01:57:39","07-11-2024 01:48:15","07-11-2024 04:09:43"=
,"site went down due to attempted theft in the bay ZTE // he normalized in =
the site","TIENTCHEU NZETCHIEU GAEL","Site Asset Theft","Theft","Theft","Cu=
stomer Equipment","site went down due to attempted theft in the bay ZTE // =
he normalized in the site","denis.mballa@ihstowers.com","565","07-11-2024 0=
1:57:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0003513195","NYANON/D=
EMBO","","07-11-2024 01:14:41","07-11-2024 00:14:28","07-11-2024 02:32:32",=
"Cascaded Incident from TTO3416946","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","grid outage, site went =
down because gen start and stoppen with alarm ""low oil pressure // He rese=
t gen card and gen manually started","system","3613","07-11-2024 01:14:41",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0003512989","Nya=
hoo","IHS_EDA_102, IHS_EDA_049","07-11-2024 00:18:33","07-11-2024 00:14:28"=
,"07-11-2024 02:32:32","grid outage, site went down because gen start and s=
toppen with alarm ""low oil pressure // He reset gen card and gen manually =
started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","grid outage, site went down because gen start and =
stoppen with alarm ""low oil pressure // He reset gen card and gen manually=
 started","rouselle.schoune@ihstowers.com","245","07-11-2024 00:18:33","Sag=
emcom CMR"
"Closed Complete","Site Down","T1597","IHS_YND_670","NOCINC0003512840","BOB=
OCK","","06-11-2024 23:47:15","06-11-2024 23:32:04","07-11-2024 00:20:18","=
ACTIVE No power issue U=3D56.3V site on Gen The Tx FME Etienne FOPA/6950339=
81/ From HUAWEI is informed","Kemeni Franklin","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power =
issue U=3D56.3V site on Gen The Tx FME Etienne FOPA/695033981/ From HUAWEI =
is informed","rouselle.schoune@ihstowers.com","912","06-11-2024 23:47:15","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0003512556","Awae Esc=
alier","","06-11-2024 22:34:40","06-11-2024 22:31:13","06-11-2024 22:38:04"=
,"Cascaded Incident from TTO3416427","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to insufficien=
t of rectifier on site//Site stabilized with reduced the load","system","20=
7","06-11-2024 22:34:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0003512552","A=
wae-Yde","IHS_YND_171","06-11-2024 22:33:26","06-11-2024 22:31:13","06-11-2=
024 22:38:04","Site went down due to insufficient of rectifier on site//Sit=
e stabilized with reduced the load","Albran Byorel","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Site went down due to insufficient of=
 rectifier on site//Site stabilized with reduced the load","denis.mballa@ih=
stowers.com","134","06-11-2024 22:33:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003511538","A=
wae Ewonkan","","06-11-2024 20:25:19","06-11-2024 20:19:16","06-11-2024 21:=
25:53","Grid outage,DG started and stopped with alarm 'overcurrent' due to =
//  he reset gen card and manually started","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,DG started and=
 stopped with alarm 'overcurrent' due to //  he reset gen card and manually=
 started","ludivine.ngamaleu@ihstowers.com","364","06-11-2024 20:25:19","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003511292","ELOUMDEM=
 CARRIERE 2","","06-11-2024 19:38:21","06-11-2024 19:35:33","06-11-2024 20:=
37:25","Cascaded Incident from TTO3414893","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation site went do=
wn because Gen started and stopped due to Grid bad voltage and RCP on site =
//He bypass the Grid and Gen manually started","system","168","06-11-2024 1=
9:38:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003511291","Eto koss=
 Yde","","06-11-2024 19:38:21","06-11-2024 19:35:33","06-11-2024 20:37:25",=
"Cascaded Incident from TTO3414893","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation site went down beca=
use Gen started and stopped due to Grid bad voltage and RCP on site //He by=
pass the Grid and Gen manually started","system","168","06-11-2024 19:38:21=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003511283","O=
lembe-Terminus","","06-11-2024 19:36:58","06-11-2024 19:26:59","06-11-2024 =
21:59:46","Site went down because 02 /04 dysfonction due load increased // =
He reset the rectifier","Fabrice Pouakam","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down because 02 /04 dysfonction due l=
oad increased // He reset the rectifier","ludivine.ngamaleu@ihstowers.com",=
"600","06-11-2024 19:36:58","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003511282","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","06-11-2024 19:36:42","06-11-2024 19:35=
:33","06-11-2024 20:37:49","Grid fluctuation site went down because Gen sta=
rted and stopped due to Grid bad voltage and RCP on site //He bypass the Gr=
id and Gen manually started","Fanda Brice","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","Grid fluctuation site went down b=
ecause Gen started and stopped due to Grid bad voltage and RCP on site //He=
 bypass the Grid and Gen manually started","olivier.kwedi@ihstowers.com","7=
0","06-11-2024 19:36:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003511243","M=
ANGUIERS CHAPELLE","","06-11-2024 19:28:32","06-11-2024 19:23:28","06-11-20=
24 19:44:10","Grid outage, site went down before gen start due to poor batt=
ery backup // Gen started automatically","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before gen start due to poor battery backup // Gen started aut=
omatically","ludivine.ngamaleu@ihstowers.com","305","06-11-2024 19:28:32","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003511232","E=
lig-Edzoa","","06-11-2024 19:26:20","06-11-2024 19:06:16","06-11-2024 21:51=
:30","No power issue site on grid with U=3D54.6v Notice that we have disjun=
ction at OCM Equipements Armand Nguetsa(691144412) from Huawei is informed =
","","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue site on grid with U=3D54.6v Notice that we =
have disjunction at OCM Equipements Armand Nguetsa(691144412) from Huawei i=
s informed ","ludivine.ngamaleu@ihstowers.com","1205","06-11-2024 19:26:20"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_409","NOCINC0003511090","Evodoula=
 OCM","","06-11-2024 19:02:01","06-11-2024 18:56:12","06-11-2024 18:58:53",=
"Cascaded Incident from TTO3414645","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","Active//No power issue on =
site ,site on Grid  wiith Ubaie=3D54.4V The TX FME Gregoire/ 654547479/  Hu=
awei is informed.","system","349","06-11-2024 19:02:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0003511089","Talla Mo=
natele","","06-11-2024 19:02:01","06-11-2024 18:56:12","06-11-2024 18:58:53=
","Cascaded Incident from TTO3414645","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","Active//No power issue on site ,sit=
e on Grid  wiith Ubaie=3D54.4V The TX FME Gregoire/ 654547479/  Huawei is i=
nformed.","system","349","06-11-2024 19:02:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_869","IHS_YND_407","NOCINC0003511084","M=
onatele MTN","IHS_YND_387, IHS_YND_409","06-11-2024 19:01:17","06-11-2024 1=
8:56:12","06-11-2024 21:35:14","Active//No power issue on site ,site on Gri=
d  wiith Ubaie=3D54.4V The TX FME Gregoire/ 654547479/  Huawei is informed.=
","Parker Tchoup","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid =
 wiith Ubaie=3D54.4V The TX FME Gregoire/ 654547479/  Huawei is informed.",=
"ludivine.ngamaleu@ihstowers.com","306","06-11-2024 19:01:17","Sagemcom CMR=
"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0003511063","Nko=
abang MTN","","06-11-2024 18:56:18","06-11-2024 18:54:11","06-11-2024 18:56=
:14","Grid fluctuation, site went down because Gen started and Stopped due =
to Grid bad voltage//Grid stabilized","Mba Lazare Herve","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, s=
ite went down because Gen started and Stopped due to Grid bad voltage//Grid=
 stabilized","olivier.kwedi@ihstowers.com","127","06-11-2024 18:56:18","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_073","IHS_YND_406","NOCINC0003511042","M=
onatele","","06-11-2024 18:51:59","06-11-2024 18:49:55","06-11-2024 21:37:5=
0","No power issue site on grid with U=3D53.8v  Gregoire from Huawei is inf=
ormed","Parker Tchoup","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.=
8v  Gregoire from Huawei is informed","ludivine.ngamaleu@ihstowers.com","12=
4","06-11-2024 18:51:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003510818","N=
gouetou","","06-11-2024 18:16:09","06-11-2024 18:10:05","06-11-2024 19:15:4=
7","No power issue site on battery with U=3D52 V//Site up at 06:36 PM Grego=
ire from Huawei is informed ","Parker Tchoup","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on battery with U=3D52 V//Site up at 06:36 PM Gregoire from Huawei is in=
formed ","ludivine.ngamaleu@ihstowers.com","365","06-11-2024 18:16:09","Sag=
emcom CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0003510626","Nko=
ngtock","","06-11-2024 17:43:42","06-11-2024 17:35:35","06-11-2024 17:57:45=
","Solar Gen Site: site went down because Hybrid System disfunctionned // H=
e reset it and started Gen manualy","Kemeni Franklin","Equipment Repair","P=
assive","Hybrid","Hybrid Module","Solar Gen Site: site went down because Hy=
brid System disfunctionned // He reset it and started Gen manualy","olivier=
.kwedi@ihstowers.com","488","06-11-2024 17:43:42","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003510249","Bas=
tos Amb Coree","","06-11-2024 16:47:22","06-11-2024 16:44:13","06-11-2024 1=
6:48:16","Site went down due to work Team Eloundou/679120558  From Potcom i=
s working on site (Swapp Battery) // end of work","","Installation Activity=
","Passive","Planned Activity","Installation Activity","Site went down due =
to work Team Eloundou/679120558  From Potcom is working on site (Swapp Batt=
ery) // end of work","olivier.kwedi@ihstowers.com","191","06-11-2024 16:47:=
22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003509849","MBIMBIM"=
,"","06-11-2024 15:50:41","06-11-2024 15:29:43","06-11-2024 15:30:43","Casc=
aded Incident from TTO3412981","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","1258","06-11-2024 15:50:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003509847","Ngouetou=
","","06-11-2024 15:50:41","06-11-2024 15:29:43","06-11-2024 15:30:43","Cas=
caded Incident from TTO3412981","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","1258","06-11-2024 15:50:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003509844","Ngoum","=
","06-11-2024 15:50:40","06-11-2024 15:29:43","06-11-2024 15:30:43","Cascad=
ed Incident from TTO3412981","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","1257","06-11-2024 15:50:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003509846","Yoko OCM=
","","06-11-2024 15:50:40","06-11-2024 15:29:43","06-11-2024 15:30:43","Cas=
caded Incident from TTO3412981","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","1257","06-11-2024 15:50:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003509845","Matsari"=
,"","06-11-2024 15:50:40","06-11-2024 15:29:43","06-11-2024 15:30:43","Casc=
aded Incident from TTO3412981","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","1257","06-11-2024 15:50:40","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0003509832","Mfo=
u EPC","","06-11-2024 15:48:56","06-11-2024 15:38:48","06-11-2024 15:57:50"=
,"Grid fluctuation site went down because Gen started and stopped due to Gr=
id bad voltage and RCP on site //He bypass the Grid and Gen manually starte=
d","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid fluctuation site went down because Gen started an=
d stopped due to Grid bad voltage and RCP on site //He bypass the Grid and =
Gen manually started","olivier.kwedi@ihstowers.com","1085","06-11-2024 15:4=
8:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003509498","B=
itoto","","06-11-2024 15:15:29","06-11-2024 14:59:23","06-11-2024 15:20:18"=
,"Grid outage site went down Gen over load(20KVA, 290A) // grid return","Mb=
a Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","=
Grid outage site went down Gen over load(20KVA, 290A) // grid return","ludi=
vine.ngamaleu@ihstowers.com","967","06-11-2024 15:15:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_517","NOCINC0003508912","Montee-D=
es-Soeurs","","06-11-2024 13:43:20","06-11-2024 13:31:54","06-11-2024 18:28=
:26","No power issue site on grid with U=3D55v Mbah Osiah from Huawei is in=
formed ","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D=
55v Mbah Osiah from Huawei is informed ","system","686","06-11-2024 13:43:2=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003508869","M=
aison-Blanche-IHS","","06-11-2024 13:37:58","06-11-2024 13:31:54","06-11-20=
24 15:00:26","Grid outage.no space to deploy mobile gen//Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge.no space to deploy mobile gen//Grid return","alexandre.kamal@ihstowers.c=
om","365","06-11-2024 13:37:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003508275","B=
arriere","","06-11-2024 12:14:59","06-11-2024 12:08:52","06-11-2024 12:52:0=
0","grid bad voltage,and gen failed to start,no rcp//he bypassed grid and s=
tarted the gen","Hyemafo Gildas","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","grid bad voltage,and gen failed to start,no=
 rcp//he bypassed grid and started the gen","alexandre.kamal@ihstowers.com"=
,"367","06-11-2024 12:14:59","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003507898","Bas=
tos Amb Coree","","06-11-2024 11:22:12","06-11-2024 11:20:00","06-11-2024 1=
1:22:04","Grid outage,no space to deploy a mobile DG,waiting for Grid resto=
red//Grid restored.","","Grid Supply","Passive","Grid","National Grid - Gri=
d Outage Issue","Grid outage,no space to deploy a mobile DG,waiting for Gri=
d restored//Grid restored.","kamga.virgile@ihstowers.com","133","06-11-2024=
 11:22:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003507644","S=
tade-Abega","","06-11-2024 10:43:26","06-11-2024 07:29:21","06-11-2024 08:4=
8:11","Active//No power issue on site Ubaie=3D54.4V;  site on Grid. Disjunc=
tion in the BTS OCM .The FME Leonel Steve/ 655184876/  Huawei is informed."=
,"Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active//No power issue on site Ubaie=3D54.4=
V;  site on Grid. Disjunction in the BTS OCM .The FME Leonel Steve/ 6551848=
76/  Huawei is informed.","alexandre.kamal@ihstowers.com","11646","06-11-20=
24 10:43:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003507072","O=
lembe-Terminus","","06-11-2024 09:23:58","05-11-2024 19:51:47","06-11-2024 =
10:16:46","Site went down due to rectifiers hanging because of first rectif=
ier slot dysfunctionning//Reset Rectifiers  ( Investigations ongoing).","Fa=
brice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Distribu=
tion","Site went down due to rectifiers hanging because of first rectifier =
slot dysfunctionning//Reset Rectifiers  ( Investigations ongoing).","alexan=
dre.kamal@ihstowers.com","48732","06-11-2024 09:23:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003506073","Ngouetou=
","","06-11-2024 06:52:01","06-11-2024 06:42:20","06-11-2024 06:43:56","Cas=
caded Incident from TTO3408702","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","581","06-11-2024 06:52:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003506075","MBIMBIM"=
,"","06-11-2024 06:52:01","06-11-2024 06:42:20","06-11-2024 06:43:56","Casc=
aded Incident from TTO3408702","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","581","06-11-2024 06:52:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003506072","Yoko OCM=
","","06-11-2024 06:52:01","06-11-2024 06:42:20","06-11-2024 06:43:56","Cas=
caded Incident from TTO3408702","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","581","06-11-2024 06:52:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003506070","Ngoum","=
","06-11-2024 06:52:00","06-11-2024 06:42:20","06-11-2024 06:43:56","Cascad=
ed Incident from TTO3408702","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","580","06-11-2024 06:52:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003506071","Matsari"=
,"","06-11-2024 06:52:00","06-11-2024 06:42:20","06-11-2024 06:43:56","Casc=
aded Incident from TTO3408702","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","580","06-11-2024 06:52:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0003505156","N=
kolso","","06-11-2024 02:42:02","06-11-2024 02:36:56","06-11-2024 04:30:19"=
,"No power issue on site Ubaie=3D54,8V  site on Grid. The Tx FME Mouahamado=
u  (691144435) of Huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site Ubaie=3D54,8V  site on Grid. The Tx FME Mouahamad=
ou  (691144435) of Huawei is informed.","emmanuel.ghani@ihstowers.com","307=
","06-11-2024 02:42:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003504498","ELOUMDEM=
 CARRIERE 2","","05-11-2024 23:24:31","05-11-2024 23:17:06","06-11-2024 00:=
13:22","Cascaded Incident from TTO3406775","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to 1/8 rec=
tifier faulty //He changed the faulty rectifier.","system","445","05-11-202=
4 23:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003504497","Eto koss=
 Yde","","05-11-2024 23:24:30","05-11-2024 23:17:06","06-11-2024 00:13:22",=
"Cascaded Incident from TTO3406775","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to 1/8 rectifier =
faulty //He changed the faulty rectifier.","system","444","05-11-2024 23:24=
:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003504477","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","05-11-2024 23:20:11","05-11-2024 23:=
17:06","06-11-2024 00:13:22","Site went down due to 1/8 rectifier faulty //=
He changed the faulty rectifier.","Fanda Brice","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down due to 1/8 rectifier fault=
y //He changed the faulty rectifier.","emmanuel.ghani@ihstowers.com","186",=
"05-11-2024 23:20:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003504466","C=
RH-Etoug-Ebe","","05-11-2024 23:18:09","05-11-2024 23:18:07","06-11-2024 04=
:50:59","No power issue on site U=3D51,1V site on Grid , The Tx FME  Mohama=
dou/691 144 435/ from Huawei is informed","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site U=3D51,1V site on Grid , The Tx FME  Mohamadou/691 144 4=
35/ from Huawei is informed","joelle.ekessi@ihstowers.com","20144","05-11-2=
024 23:18:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003503665","Nsimalen=
 OCM","","05-11-2024 21:10:40","05-11-2024 21:06:10","05-11-2024 21:10:54",=
"Cascaded Incident from TTO3405761","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to insufficient=
 of rectifier on site//Site stabilized","system","270","05-11-2024 21:10:40=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003503654","N=
kolda","IHS_YND_327","05-11-2024 21:09:23","05-11-2024 21:06:10","05-11-202=
4 21:10:54","Site went down due to insufficient of rectifier on site//Site =
stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to insufficient of rectifier on site//Site=
 stabilized","denis.mballa@ihstowers.com","194","05-11-2024 21:09:23","Sage=
mcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0003503382","Awa=
e Ewonkan","","05-11-2024 20:24:17","05-11-2024 20:19:05","05-11-2024 21:40=
:13","Grid outage,DG started and stopped with alarm 'overcurrent' due to //=
  he reset gen card and manually started","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,DG started and s=
topped with alarm 'overcurrent' due to //  he reset gen card and manually s=
tarted","rouselle.schoune@ihstowers.com","312","05-11-2024 20:24:17","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003503194","S=
tade-Abega","","05-11-2024 19:54:27","05-11-2024 19:51:14","05-11-2024 20:2=
5:58","Site went down due to rectifiers dysfunctioning //Reset rectifiers,s=
ite on Grid.","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to rectifiers dysfunctioning //Reset =
rectifiers,site on Grid.","denis.mballa@ihstowers.com","194","05-11-2024 19=
:54:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0003503015","Abang","=
","05-11-2024 19:44:21","05-11-2024 19:14:13","05-11-2024 19:20:25","Cascad=
ed Incident from TTO3404996","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site ,site on G=
rid  wiith Ubaie=3D51.9 V The TX FME Leonel Steve/ 655184876/  Huawei is in=
formed","system","1808","05-11-2024 19:44:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0003502997","N=
kolangaa","IHS_YND_290","05-11-2024 19:42:26","05-11-2024 19:14:13","05-11-=
2024 23:25:25","Active//No power issue on site ,site on Grid  wiith Ubaie=
=3D51.9 V The TX FME Leonel Steve/ 655184876/  Huawei is informed","Mba Laz=
are Herve","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid  wiith =
Ubaie=3D51.9 V The TX FME Leonel Steve/ 655184876/  Huawei is informed","de=
nis.mballa@ihstowers.com","1694","05-11-2024 19:42:26","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0003502834","Nko=
abang MTN","","05-11-2024 19:20:15","05-11-2024 19:15:09","05-11-2024 19:20=
:09","Grid fluctuation, site went down because Gen started and Stopped due =
to Grid bad voltage//Grid stabilized","Mba Lazare Herve","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, s=
ite went down because Gen started and Stopped due to Grid bad voltage//Grid=
 stabilized","rouselle.schoune@ihstowers.com","307","05-11-2024 19:20:15","=
Sagemcom CMR"
"Closed Complete","Site Down","T0395","IHS_YND_065","NOCINC0003502820","Ess=
os DCS","","05-11-2024 19:17:50","05-11-2024 19:10:32","05-11-2024 19:20:32=
","Site went down due to insufficient of rectifier on site//Site stabilized=
","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site went down due to insufficient of rectifier on site//Site stabiliz=
ed","rouselle.schoune@ihstowers.com","439","05-11-2024 19:17:50","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0003502366","M=
ontesquieux","","05-11-2024 18:03:52","05-11-2024 18:01:35","05-11-2024 18:=
03:35","Site went down due to insufficient of rectifier on site//Site stabi=
lized","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficient of rectifier on site//Site stabil=
ized","denis.mballa@ihstowers.com","137","05-11-2024 18:03:52","Sagemcom CM=
R"
"Closed Complete","Site Down","T2149","IHS_EDA_056","NOCINC0003501555","Ndo=
gbessol","","05-11-2024 16:16:55","05-11-2024 15:55:30","05-11-2024 17:34:3=
2","Active//No power issue on site ,site on GEN  wiith Ubaie=3D51.9 V The T=
X FME Etienne/ 695033981/  Huawei is informed","Kemeni Franklin","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site ,site on GEN  wiith Ubaie=3D51.9 V The TX =
FME Etienne/ 695033981/  Huawei is informed","rouselle.schoune@ihstowers.co=
m","1285","05-11-2024 16:16:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0003501105","S=
oa-Sofamac","","05-11-2024 15:16:18","05-11-2024 15:11:52","05-11-2024 16:4=
2:52","Active//No power issue on site, Site on Grid UBAIE=3D54.1V  synphori=
en (675295205) From huawei is informed. Notice that we have disjunction at =
BTS OCM","Siligap Boris","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active//No power issue on site, Site o=
n Grid UBAIE=3D54.1V  synphorien (675295205) From huawei is informed. Notic=
e that we have disjunction at BTS OCM","denis.mballa@ihstowers.com","266","=
05-11-2024 15:16:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003500684","N=
kolfon Cimencam","","05-11-2024 14:40:37","05-11-2024 14:39:20","05-11-2024=
 14:40:20","Active//No power issue on site U=3D54,5v site on Gen The Rm Ala=
in (691144423) of huawei is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue on site U=3D54,5v site on Gen The Rm Alain (691144423) of hu=
awei is informed","denis.mballa@ihstowers.com","78","05-11-2024 14:40:37","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003500184","I=
mm-Olympique","","05-11-2024 13:52:42","05-11-2024 13:49:38","05-11-2024 15=
:20:38","Active//No power issue site on Gen  with U=3D54.2 V The  Rm Tx  //=
 691144423//  from Huawei is informed notice that the  CB 125(A) Disjunted =
 in the BTS OCM","Paul BIBOUM","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active//No power issue site on G=
en  with U=3D54.2 V The  Rm Tx  // 691144423//  from Huawei is informed not=
ice that the  CB 125(A) Disjunted  in the BTS OCM","ludivine.ngamaleu@ihsto=
wers.com","185","05-11-2024 13:52:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0003499799","Elig Edz=
oa","","05-11-2024 13:27:02","05-11-2024 13:14:40","05-11-2024 13:20:40","C=
ascaded Incident from TTO3401125","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work (ss IHS =
Bertrant ) is working on site// End Off Work","system","742","05-11-2024 13=
:27:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0003499798","Hopital =
Central","","05-11-2024 13:27:01","05-11-2024 13:14:40","05-11-2024 13:20:4=
0","Cascaded Incident from TTO3401125","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Site went down due to work (ss IHS Bertrant =
) is working on site// End Off Work","system","741","05-11-2024 13:27:01","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_016","NOCINC0003499797","Maetur",=
"","05-11-2024 13:27:01","05-11-2024 13:14:40","05-11-2024 13:20:40","Casca=
ded Incident from TTO3401125","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to work (ss IHS Bertr=
ant ) is working on site// End Off Work","system","741","05-11-2024 13:27:0=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0003499796","ELIg-Ess=
ono","","05-11-2024 13:27:01","05-11-2024 13:14:40","05-11-2024 13:20:40","=
Cascaded Incident from TTO3401125","Delor Telezing","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work (ss IHS=
 Bertrant ) is working on site// End Off Work","system","741","05-11-2024 1=
3:27:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0003499793","POLYCLIN=
IQUE TSINGA","","05-11-2024 13:27:00","05-11-2024 13:14:40","05-11-2024 13:=
20:40","Cascaded Incident from TTO3401125","Mboua Thierry","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to work =
(ss IHS Bertrant ) is working on site// End Off Work","system","740","05-11=
-2024 13:27:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0003499792","Mamch Bu=
ilding","","05-11-2024 13:27:00","05-11-2024 13:14:40","05-11-2024 13:20:40=
","Cascaded Incident from TTO3401125","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site went down due to work (ss I=
HS Bertrant ) is working on site// End Off Work","system","740","05-11-2024=
 13:27:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0003499795","Garbati =
building","","05-11-2024 13:27:00","05-11-2024 13:14:40","05-11-2024 13:20:=
40","Cascaded Incident from TTO3401125","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to work (s=
s IHS Bertrant ) is working on site// End Off Work","system","740","05-11-2=
024 13:27:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_731","NOCINC0003499794","UPAC LP"=
,"","05-11-2024 13:27:00","05-11-2024 13:14:40","05-11-2024 13:20:40","Casc=
aded Incident from TTO3401125","","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Site went down due to work (ss IHS Bertrant ) is wor=
king on site// End Off Work","system","740","05-11-2024 13:27:00","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0003499753","Hot=
el de Ville Yde","IHS_YND_051, IHS_YND_086, IHS_YND_731, IHS_YND_024, IHS_Y=
ND_014, IHS_YND_016, IHS_YND_027, IHS_YND_504","05-11-2024 13:22:41","05-11=
-2024 13:14:40","05-11-2024 13:20:40","Site went down due to work (ss IHS B=
ertrant ) is working on site// End Off Work","Paul BIBOUM","Equipment Repla=
cement","Passive","Planned Activity","Planned Activity - Passive","Site wen=
t down due to work (ss IHS Bertrant ) is working on site// End Off Work","o=
livier.kwedi@ihstowers.com","482","05-11-2024 13:22:41","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003498985","NKO=
MEKUI OCM","","05-11-2024 12:02:56","05-11-2024 11:56:35","05-11-2024 12:40=
:41","No power issue site on Gen  with U=3D54.3 V The  Tx Fme Mohamadou mou=
am // 691144435  from Huawei is informed site impacted by Mbankolo camtel",=
"TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue site on Gen  with U=
=3D54.3 V The  Tx Fme Mohamadou mouam // 691144435  from Huawei is informed=
 site impacted by Mbankolo camtel","olivier.kwedi@ihstowers.com","383","05-=
11-2024 12:02:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0003498554","M=
efou-Assi","","05-11-2024 11:24:31","05-11-2024 11:22:27","05-11-2024 12:01=
:20","No power issue on site U=3D54,3v site on grid Synphorien of huawei is=
 informed notice that disjunction of CB in BTS OCM","Fanda Brice","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site U=3D54,3v site on grid Synphorien of huawei is in=
formed notice that disjunction of CB in BTS OCM","ludivine.ngamaleu@ihstowe=
rs.com","125","05-11-2024 11:24:31","Sagemcom CMR"
"Closed Complete","Warning","T1557","IHS_YND_313","NOCINC0003498380","Afano=
ya","","05-11-2024 11:04:21","","","site on alarm due to grid bad voltage//=
he put the site on gen","Hyemafo Gildas","Warning","Warning","POWER","Warni=
ng - Site on Battery","site on alarm due to grid bad voltage//he put the si=
te on gen","etienne.itondo@ihstowers.com","923","05-11-2024 11:04:21","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0003498236","C=
hapelle-Essos","","05-11-2024 10:42:07","05-11-2024 10:40:04","05-11-2024 1=
1:00:04","Grid fluctuation, site went down because gen start and stopped du=
e to grid bad voltage, no RCP on site  // he bypass grid and gen manually s=
tarted","Delor Telezing","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation, site went down because gen start =
and stopped due to grid bad voltage, no RCP on site  // he bypass grid and =
gen manually started","ludivine.ngamaleu@ihstowers.com","124","05-11-2024 1=
0:42:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0003498183","ELIg-Ess=
ono","","05-11-2024 10:33:32","05-11-2024 10:27:03","05-11-2024 10:53:03","=
Cascaded Incident from TTO3399266","Delor Telezing","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down due to disjunction =
Cb(125A) in Dc box // we balanced the loads and put back on the CB","system=
","389","05-11-2024 10:33:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0003498186","Elig Edz=
oa","","05-11-2024 10:33:32","05-11-2024 10:27:03","05-11-2024 10:53:03","C=
ascaded Incident from TTO3399266","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down due to disjunction C=
b(125A) in Dc box // we balanced the loads and put back on the CB","system"=
,"389","05-11-2024 10:33:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0003498185","Charles-=
Atangana","","05-11-2024 10:33:32","05-11-2024 10:27:03","05-11-2024 10:53:=
03","Cascaded Incident from TTO3399266","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down due to disjunction Cb(125A) =
in Dc box // we balanced the loads and put back on the CB","system","389","=
05-11-2024 10:33:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0003498184","Hopital =
Central","","05-11-2024 10:33:32","05-11-2024 10:27:03","05-11-2024 10:53:0=
3","Cascaded Incident from TTO3399266","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","site went down due to disjunction Cb(125A) i=
n Dc box // we balanced the loads and put back on the CB","system","389","0=
5-11-2024 10:33:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_049","NOCINC0003498179","Etoa-Mek=
i","","05-11-2024 10:33:31","05-11-2024 10:27:03","05-11-2024 10:53:03","Ca=
scaded Incident from TTO3399266","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to disjunction Cb=
(125A) in Dc box // we balanced the loads and put back on the CB","system",=
"388","05-11-2024 10:33:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0003498180","HOPITAL =
DE LA CAISSE","","05-11-2024 10:33:31","05-11-2024 10:27:03","05-11-2024 10=
:53:03","Cascaded Incident from TTO3399266","Delor Telezing","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","site went down due to dis=
junction Cb(125A) in Dc box // we balanced the loads and put back on the CB=
","system","388","05-11-2024 10:33:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_731","NOCINC0003498181","UPAC LP"=
,"","05-11-2024 10:33:31","05-11-2024 10:27:03","05-11-2024 10:53:03","Casc=
aded Incident from TTO3399266","","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","site went down due to disjunction Cb(125A) in Dc box=
 // we balanced the loads and put back on the CB","system","388","05-11-202=
4 10:33:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0003498182","Sapeur",=
"","05-11-2024 10:33:31","05-11-2024 10:27:03","05-11-2024 10:53:03","Casca=
ded Incident from TTO3399266","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site went down due to disjunction Cb(125=
A) in Dc box // we balanced the loads and put back on the CB","system","388=
","05-11-2024 10:33:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_084","NOCINC0003498177","Briquett=
erie","","05-11-2024 10:33:30","05-11-2024 10:27:03","05-11-2024 10:53:03",=
"Cascaded Incident from TTO3399266","","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","site went down due to disjunction Cb(125A) in D=
c box // we balanced the loads and put back on the CB","system","387","05-1=
1-2024 10:33:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_091","NOCINC0003498178","Jouvence=
 2000","","05-11-2024 10:33:30","05-11-2024 10:27:03","05-11-2024 10:53:03"=
,"Cascaded Incident from TTO3399266","Delor Telezing","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","site went down due to disjunctio=
n Cb(125A) in Dc box // we balanced the loads and put back on the CB","syst=
em","387","05-11-2024 10:33:30","Sagemcom CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0003498164","Hot=
el de Ville Yde","IHS_YND_084, IHS_YND_091, IHS_YND_049, IHS_YND_064, IHS_Y=
ND_731, IHS_YND_029, IHS_YND_014, IHS_YND_027, IHS_YND_125, IHS_YND_504","0=
5-11-2024 10:31:10","05-11-2024 10:27:03","05-11-2024 10:53:03","site went =
down due to disjunction Cb(125A) in Dc box // we balanced the loads and put=
 back on the CB","Paul BIBOUM","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Circuit Breaker Issue","site went down due to disjunction=
 Cb(125A) in Dc box // we balanced the loads and put back on the CB","olivi=
er.kwedi@ihstowers.com","248","05-11-2024 10:31:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003497815","M=
VAN SACEL","","05-11-2024 09:47:59","05-11-2024 09:42:55","05-11-2024 12:32=
:15","No power issue on site U=3D54,5v site on Grid Tx FME Lionel (65518487=
6) of huawei is informed","MINKA NICOLAS","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54,5v site on Grid Tx FME Lionel (655184876) of huawei is informed","=
ludivine.ngamaleu@ihstowers.com","305","05-11-2024 09:47:59","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003497734","NYO=
M FACE MAETUR","","05-11-2024 09:36:46","05-11-2024 09:34:38","06-11-2024 0=
6:08:09","Grid bad voltage (Access issue due to landloard), landlord has fo=
rbiden to start the Gen Because  the  Noise //Grid voltage restored.","Fabr=
ice Pouakam","Access Denial","Lease Or Legal","Landlord Related Issues","Ac=
cess Issue - Land Lord","Grid bad voltage (Access issue due to landloard), =
landlord has forbiden to start the Gen Because  the  Noise //Grid voltage r=
estored.","olivier.kwedi@ihstowers.com","128","05-11-2024 09:36:46","Sagemc=
om CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003497565","Bas=
tos Amb Coree","","05-11-2024 09:15:10","05-11-2024 09:14:04","05-11-2024 0=
9:53:04","site went down due to insuficiency of rectifiers // site stabiliz=
ed","","Equipment Repair","Passive","Rectifier","Rectifier Module","site we=
nt down due to insuficiency of rectifiers // site stabilized","olivier.kwed=
i@ihstowers.com","68","05-11-2024 09:15:10","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003496873","AWA=
E OCM","","05-11-2024 07:36:40","05-11-2024 07:34:33","05-11-2024 10:54:41"=
,"site went down because PWC overload due to load increase // site stabilis=
ed","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier =
Module Overloaded","site went down because PWC overload due to load increas=
e // site stabilised","olivier.kwedi@ihstowers.com","128","05-11-2024 07:36=
:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003496828","N=
kolfon Cimencam","","05-11-2024 07:28:13","05-11-2024 07:27:08","05-11-2024=
 10:31:44","No power issue on site U=3D54,5v site on Gen The Rm Alain (6911=
44423) of huawei is informed","Hyemafo Gildas","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D54,5v site on Gen The Rm Alain (691144423) of huawei is informed=
","ludivine.ngamaleu@ihstowers.com","65","05-11-2024 07:28:13","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003496823","B=
arriere","","05-11-2024 07:26:55","05-11-2024 07:22:51","05-11-2024 08:37:5=
7","Gid bad voltage,and gen failed to start,no rcp//he bypassed grid and st=
arted the gen","Hyemafo Gildas","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Gid bad voltage,and gen failed to start,no r=
cp//he bypassed grid and started the gen","ludivine.ngamaleu@ihstowers.com"=
,"245","05-11-2024 07:26:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0003496819","M=
balla 4","","05-11-2024 07:26:03","05-11-2024 07:12:57","05-11-2024 07:27:5=
7","site went down due to insuficiency of rectifiers (2/5) // site stabiliz=
ed","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down due to insuficiency of rectifiers (2/5) // site stabi=
lized","ludivine.ngamaleu@ihstowers.com","787","05-11-2024 07:26:03","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003496620","Matsari"=
,"","05-11-2024 06:45:51","05-11-2024 06:23:55","05-11-2024 06:24:08","Casc=
aded Incident from TTO3397445","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","1316","05-11-2024 06:45:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003496621","Ngouetou=
","","05-11-2024 06:45:51","05-11-2024 06:23:55","05-11-2024 06:24:08","Cas=
caded Incident from TTO3397445","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","1316","05-11-2024 06:45:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003496623","MBIMBIM"=
,"","05-11-2024 06:45:51","05-11-2024 06:23:55","05-11-2024 06:24:08","Casc=
aded Incident from TTO3397445","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","1316","05-11-2024 06:45:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003496619","Ngoum","=
","05-11-2024 06:45:50","05-11-2024 06:23:55","05-11-2024 06:24:08","Cascad=
ed Incident from TTO3397445","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","1315","05-11-2024 06:45:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003496616","ELOUMDEM=
 CARRIERE 2","","05-11-2024 06:45:30","05-11-2024 06:40:38","05-11-2024 06:=
44:38","Cascaded Incident from TTO3397443","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because gen start and stopped due to grid bad voltage // gen manually s=
tarted","system","292","05-11-2024 06:45:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003496615","Eto koss=
 Yde","","05-11-2024 06:45:30","05-11-2024 06:40:38","05-11-2024 06:44:38",=
"Cascaded Incident from TTO3397443","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause gen start and stopped due to grid bad voltage // gen manually started"=
,"system","292","05-11-2024 06:45:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003496603","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","05-11-2024 06:43:56","05-11-2024 06:40=
:38","05-11-2024 06:44:38","Grid fluctuation, site went down because gen st=
art and stopped due to grid bad voltage // gen manually started","Fanda Bri=
ce","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage // gen manually started","olivier.kwedi@ihstowers.com","199"=
,"05-11-2024 06:43:56","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0003496363","Aha=
la Echangeur","","05-11-2024 05:44:07","05-11-2024 05:36:56","05-11-2024 06=
:42:56","Grid fluctuation, site went down because gen start and stopped due=
 to grid bad voltage // he bypass grid and gen manually started","MINKA NIC=
OLAS","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, site went down because gen start and stopped due to =
grid bad voltage // he bypass grid and gen manually started","denis.mballa@=
ihstowers.com","432","05-11-2024 05:44:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_707","NOCINC0003494152","NYOM 2 I=
HS","","04-11-2024 20:56:00","04-11-2024 20:45:47","04-11-2024 21:06:39","C=
ascaded Incident from TTO3394391","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Eneo Outage, Site Down because the=
 generator is manual // Manual Start of Gen","system","613","04-11-2024 20:=
56:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003494100","M=
vog-Manga","","04-11-2024 20:46:38","04-11-2024 20:43:33","05-11-2024 01:39=
:25","Active: no power issue, site is on grid with Ubaie=3D51.3V, Lionel ad=
jed(655184876) from Huawei is informed","Albran Byorel","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active:=
 no power issue, site is on grid with Ubaie=3D51.3V, Lionel adjed(655184876=
) from Huawei is informed","emmanuel.ghani@ihstowers.com","187","04-11-2024=
 20:46:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003494061","T=
amtam Weekend","","04-11-2024 20:42:44","04-11-2024 20:35:39","05-11-2024 0=
1:40:51","No power issue, site is on Grid with Ubaie=3D51,9  V  The TX FME =
Mbah Hosiah (674007438)  from Huawei is informed","Hyemafo Gildas","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue, site is on Grid with Ubaie=3D51,9  V  The TX FME Mbah H=
osiah (674007438)  from Huawei is informed","emmanuel.ghani@ihstowers.com",=
"426","04-11-2024 20:42:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0003493944","EBOM",""=
,"04-11-2024 20:32:31","04-11-2024 20:27:36","04-11-2024 20:37:10","Cascade=
d Incident from TTO3394188","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue on site, Site on Grid=
 UBAIE=3D53V  The FME TX Georges/697461814 From huawei is informed. Notice =
that we have disjunction at BTS OCM","system","295","04-11-2024 20:32:31","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0003493943","Ahala","=
","04-11-2024 20:32:30","04-11-2024 20:27:36","04-11-2024 20:37:10","Cascad=
ed Incident from TTO3394188","Hyemafo Gildas","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active//No power issue on site, Site on Gri=
d UBAIE=3D53V  The FME TX Georges/697461814 From huawei is informed. Notice=
 that we have disjunction at BTS OCM","system","294","04-11-2024 20:32:30",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003493930","A=
hala","IHS_YND_257, IHS_YND_698","04-11-2024 20:30:42","04-11-2024 20:27:36=
","04-11-2024 20:37:10","Active//No power issue on site, Site on Grid UBAIE=
=3D53V  The FME TX Georges/697461814 From huawei is informed. Notice that w=
e have disjunction at BTS OCM","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power=
 issue on site, Site on Grid UBAIE=3D53V  The FME TX Georges/697461814 From=
 huawei is informed. Notice that we have disjunction at BTS OCM","emmanuel.=
ghani@ihstowers.com","187","04-11-2024 20:30:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003493694","A=
WAE OCM","","04-11-2024 19:54:19","04-11-2024 19:53:14","04-11-2024 19:55:1=
6","site went down because PWC overload due to load increase // site stabil=
ised","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","site went down because PWC overload due to load incre=
ase // site stabilised","emmanuel.ghani@ihstowers.com","66","04-11-2024 19:=
54:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003493687","M=
imboman-Village","","04-11-2024 19:53:08","04-11-2024 19:47:02","05-11-2024=
 02:00:38","No power issue on site ,site on Grid with Ubaie=3D54,6 V The Tx=
 FME Eloundou(693212405) from Huawei is informed. Notice that we have disju=
nction at BTS OCM","Mba Lazare Herve","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site ,s=
ite on Grid with Ubaie=3D54,6 V The Tx FME Eloundou(693212405) from Huawei =
is informed. Notice that we have disjunction at BTS OCM","emmanuel.ghani@ih=
stowers.com","367","04-11-2024 19:53:08","Sagemcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0003493685","ODZ=
A BORNE 10","","04-11-2024 19:52:49","04-11-2024 19:47:41","04-11-2024 20:3=
3:56","site went down due to disfunctionning of rectifiers // he reset rect=
ifiers, site on grid","Albran Byorel","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","site went down due to disfunctionning of rectifiers=
 // he reset rectifiers, site on grid","christian.fonkou@ihstowers.com","30=
9","04-11-2024 19:52:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003493578","B=
iyemassi LAC","","04-11-2024 19:40:50","04-11-2024 19:31:47","05-11-2024 02=
:18:33","Active: no power issue, site is on grid with Ubaie=3D53,2V, Hosiah=
(699699694) from Huawei is informed, Notice that we have disjunction at BTS=
 OCM","","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active: no power issue, site is on grid with Ubaie=3D5=
3,2V, Hosiah(699699694) from Huawei is informed, Notice that we have disjun=
ction at BTS OCM","emmanuel.ghani@ihstowers.com","544","04-11-2024 19:40:50=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003493314","Akak-Nko=
zoa-MTN-IHS","","04-11-2024 18:57:01","04-11-2024 18:48:01","04-11-2024 19:=
57:42","Cascaded Incident from TTO3393426","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Overload sur le GE  Contr=
=F4leur Huawei HS   //  On a d=E9marr=E9 manuellement","system","540","04-1=
1-2024 18:57:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003493301","C=
rf-Nsam","","04-11-2024 18:55:13","04-11-2024 18:47:04","04-11-2024 18:54:3=
3","Site went down because PWC overload // site stabilized","MINKA NICOLAS"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Si=
te went down because PWC overload // site stabilized","emmanuel.ghani@ihsto=
wers.com","490","04-11-2024 18:55:13","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003493260","N=
KOMEKUI OCM","","04-11-2024 18:49:28","04-11-2024 18:42:22","04-11-2024 18:=
43:55","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite went down before gen start due to poor battery backup // Gen start auto=
matically","emmanuel.ghani@ihstowers.com","427","04-11-2024 18:49:28","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003493202","N=
kozoa","","04-11-2024 18:39:18","04-11-2024 18:38:12","04-11-2024 19:02:59"=
,"site went down because gen failed to start due to grid bad voltage // gen=
 manually started","Fabrice Pouakam","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","site went down because gen failed to st=
art due to grid bad voltage // gen manually started","emmanuel.ghani@ihstow=
ers.com","67","04-11-2024 18:39:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003493194","E=
kombitie","","04-11-2024 18:37:06","04-11-2024 18:28:01","05-11-2024 01:28:=
48","Acive// No power issue on site Site on Grid Ubai=3D54,6V The Team Ludo=
vic Kotap/69456958/ From Telis working on site ""Swapp preparation""","Fabr=
ice Pouakam","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Acive// No power issue on site Site on Grid Ubai=
=3D54,6V The Team Ludovic Kotap/69456958/ From Telis working on site ""Swap=
p preparation""","emmanuel.ghani@ihstowers.com","546","04-11-2024 18:37:06"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003492963","Nko=
londom","","04-11-2024 17:48:12","04-11-2024 17:41:06","04-11-2024 19:03:50=
","gen stoppen and grid return, site went down due to eneo contactor not ex=
cited // He excited Eneo contactor, site on grid","Fabrice Pouakam","Equipm=
ent Repair","Passive","Control Panel","ATS-AMF Issue","gen stoppen and grid=
 return, site went down due to eneo contactor not excited // He excited Ene=
o contactor, site on grid","christian.fonkou@ihstowers.com","1075","04-11-2=
024 17:48:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0003492939","M=
vog-Ada_OCM","","04-11-2024 17:41:19","04-11-2024 13:41:17","05-11-2024 16:=
25:14","Acces isssue due to Landlord (site went down due to CB 125A dijonct=
ed in the PWC// he reamed the CB 125A) ","","Access Denial","Lease Or Legal=
","Landlord Related Issues","Access Issue - Land Lord","Acces isssue due to=
 Landlord (site went down due to CB 125A dijoncted in the PWC// he reamed t=
he CB 125A) ","emmanuel.ghani@ihstowers.com","14403","04-11-2024 17:41:19",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003492613","Mim=
boman4","","04-11-2024 16:46:52","04-11-2024 15:46:46","04-11-2024 17:14:56=
","Grid fluctuation, site went down because Gen started and stopped due to =
Grid bad voltage No rcp on site// He bypassed Grid and started Gen manualy"=
,"Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation, site went down because Gen started and=
 stopped due to Grid bad voltage No rcp on site// He bypassed Grid and star=
ted Gen manualy","christian.fonkou@ihstowers.com","3607","04-11-2024 16:46:=
52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003492570","Eto koss=
 Yde","","04-11-2024 16:41:00","04-11-2024 16:36:29","04-11-2024 16:58:44",=
"Cascaded Incident from TTO3392499","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to grid bad volta=
ge and insuficiency of rectifiers// Gen manually started","system","271","0=
4-11-2024 16:41:00","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003492558","MEF=
OU ASSI","IHS_YND_737","04-11-2024 16:39:38","04-11-2024 16:36:29","04-11-2=
024 16:58:44","site went down due to grid bad voltage and insuficiency of r=
ectifiers// Gen manually started","Fanda Brice","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","site went down due to grid b=
ad voltage and insuficiency of rectifiers// Gen manually started","christia=
n.fonkou@ihstowers.com","191","04-11-2024 16:39:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003492506","B=
riqueterie","","04-11-2024 16:31:36","04-11-2024 16:25:29","04-11-2024 16:4=
5:38","Grid outage, no space to deploy a mobile gen // grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, no space to deploy a mobile gen // grid return","emmanuel.ghani@ihstowers=
.com","368","04-11-2024 16:31:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0003492452","N=
goulmekong-Nord","","04-11-2024 16:25:24","04-11-2024 15:11:16","04-11-2024=
 15:11:25","Error Ticket Site not down","Siligap Boris","Incorrectly Logged=
 Tickets","Error","Error","Error","Error Ticket Site not down","emmanuel.gh=
ani@ihstowers.com","4449","04-11-2024 16:25:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003492238","MVAN SAC=
EL","","04-11-2024 16:07:00","04-11-2024 15:52:20","04-11-2024 17:56:11","C=
ascaded Incident from TTO3392120","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Grid outage ,site went down because=
  Gen started and stopped due to Gen overload (20KVA,290 A) //Grid return",=
"system","880","04-11-2024 16:07:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003492236","M=
VAN","IHS_YND_510","04-11-2024 16:06:28","04-11-2024 15:52:20","04-11-2024 =
17:56:39"," Grid outage ,site went down because  Gen started and stopped du=
e to Gen overload (20KVA,290 A) //Grid return","MINKA NICOLAS","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload"," Grid outage ,site went down=
 because  Gen started and stopped due to Gen overload (20KVA,290 A) //Grid =
return","emmanuel.ghani@ihstowers.com","849","04-11-2024 16:06:28","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0003492010","B=
astos Bir","","04-11-2024 15:30:14","04-11-2024 15:04:10","04-11-2024 15:34=
:45","Grid outage site went down Gen over load(20KVA, 290A) // he reduced t=
he load","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage site went down Gen over load(20KVA, 290A) // he reduce=
d the load","emmanuel.ghani@ihstowers.com","1565","04-11-2024 15:30:14","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0003491782","An-=
Marche-Melen","","04-11-2024 15:07:45","04-11-2024 14:43:38","04-11-2024 15=
:13:48","Grid outage , no space to deploy // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage , no spac=
e to deploy // Grid return","christian.fonkou@ihstowers.com","1448","04-11-=
2024 15:07:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003491771","B=
arriere","","04-11-2024 15:06:11","04-11-2024 14:54:06","05-11-2024 01:30:1=
7","No  power issue U =3D55,4V site on grid.FME Tx Georges (697461814)from =
Huawei is informed, Notice that we have disjunction at BTS OCM","Hyemafo Gi=
ldas","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No  power issue U =3D55,4V site on grid.FME Tx Georges (6=
97461814)from Huawei is informed, Notice that we have disjunction at BTS OC=
M","emmanuel.ghani@ihstowers.com","726","04-11-2024 15:06:11","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003491741","M=
ini-Ferme","","04-11-2024 15:03:52","04-11-2024 14:34:48","04-11-2024 19:00=
:53","No power issue on site ,site on Grid =3D55.8 V TheTX FME Mohamadou(69=
1144435) from hauwei is informed","","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site ,si=
te on Grid =3D55.8 V TheTX FME Mohamadou(691144435) from hauwei is informed=
","emmanuel.ghani@ihstowers.com","1745","04-11-2024 15:03:52","Sagemcom CMR=
"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003491734","Pha=
rmacie SION","","04-11-2024 15:03:23","04-11-2024 14:41:09","04-11-2024 15:=
13:14","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen started manually","Paul BIBOUM","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started manually","christi=
an.fonkou@ihstowers.com","1335","04-11-2024 15:03:23","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003491719","ODZ=
A CITE MBIA","","04-11-2024 15:01:06","04-11-2024 14:41:57","04-11-2024 17:=
22:38","Grid fluctuation, site went down because Gen started and stopped du=
e to Grid bad voltage No rcp on site// He bypassed Grid and started Gen man=
ualy","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid fluctuation, site went down because Gen started a=
nd stopped due to Grid bad voltage No rcp on site// He bypassed Grid and st=
arted Gen manualy","christian.fonkou@ihstowers.com","1150","04-11-2024 15:0=
1:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_028","NOCINC0003491543","H-Centra=
l","","04-11-2024 14:38:32","04-11-2024 13:22:46","04-11-2024 13:58:52","Ca=
scaded Incident from TTO3391276","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid Outage site went down because Gen =
failed to start due to Static charger Faulty and battery gen discharged//Ge=
n Started by external Battery(The charger static to be replaced)","system",=
"4546","04-11-2024 14:38:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0003491544","Tsinga",=
"","04-11-2024 14:38:32","04-11-2024 13:22:46","04-11-2024 13:58:52","Casca=
ded Incident from TTO3391276","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid Outage site went down because Gen f=
ailed to start due to Static charger Faulty and battery gen discharged//Gen=
 Started by external Battery(The charger static to be replaced)","system","=
4546","04-11-2024 14:38:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_002","NOCINC0003491542","Yde-M-Ce=
ntral","","04-11-2024 14:38:32","04-11-2024 13:22:46","04-11-2024 13:58:52"=
,"Cascaded Incident from TTO3391276","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid Outage site went down because Gen failed =
to start due to Static charger Faulty and battery gen discharged//Gen Start=
ed by external Battery(The charger static to be replaced)","system","4545",=
"04-11-2024 14:38:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_010","NOCINC0003491541","CNR","",=
"04-11-2024 14:38:31","04-11-2024 13:22:46","04-11-2024 13:58:52","Cascaded=
 Incident from TTO3391276","Mboua Thierry","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid Outage site went down because Gen fail=
ed to start due to Static charger Faulty and battery gen discharged//Gen St=
arted by external Battery(The charger static to be replaced)","system","454=
5","04-11-2024 14:38:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0003491540","Bastos-N=
ylon","","04-11-2024 14:38:31","04-11-2024 13:22:46","04-11-2024 13:58:52",=
"Cascaded Incident from TTO3391276","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage site went down because=
 Gen failed to start due to Static charger Faulty and battery gen discharge=
d//Gen Started by external Battery(The charger static to be replaced)","sys=
tem","4545","04-11-2024 14:38:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0003491516","C=
NDH","IHS_YND_126, IHS_YND_010, IHS_YND_002, IHS_YND_028, IHS_YND_173, IHS_=
YND_127","04-11-2024 14:35:58","04-11-2024 13:22:46","04-11-2024 13:58:52",=
"Grid Outage site went down because Gen failed to start due to Static charg=
er Faulty and battery gen discharged//Gen Started by external Battery(The c=
harger static to be replaced)","Paul BIBOUM","Equipment Repair","Passive","=
ACDG Gen","ACDG - Charging Alternator","Grid Outage site went down because =
Gen failed to start due to Static charger Faulty and battery gen discharged=
//Gen Started by external Battery(The charger static to be replaced)","land=
ry.etame@ihstowers.com","4393","04-11-2024 14:35:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0003491511","Awae Esc=
alier","","04-11-2024 14:35:10","04-11-2024 13:56:31","04-11-2024 14:55:15"=
,"Cascaded Incident from TTO3391251","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to insufficien=
t of rectifier on site//Site stabilized","system","2319","04-11-2024 14:35:=
10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0003491496","A=
wae-Yde","IHS_YND_171","04-11-2024 14:32:45","04-11-2024 13:56:31","04-11-2=
024 14:55:15","Site went down due to insufficient of rectifier on site//Sit=
e stabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","Site went down due to insufficient of rectifier on site//Si=
te stabilized","landry.etame@ihstowers.com","2175","04-11-2024 14:32:45","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003491437","D=
ragage","","04-11-2024 14:24:28","04-11-2024 13:44:13","05-11-2024 01:09:30=
","No power issue on site ,site on Gen with Ubaie=3D53,7 V The Tx FME Eloun=
dou(693212405) from Huawei is informed","Mboua Thierry","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site ,site on Gen with Ubaie=3D53,7 V The Tx FME Eloundou(693212=
405) from Huawei is informed","landry.etame@ihstowers.com","2416","04-11-20=
24 14:24:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_098","NOCINC0003491426","Ekounou"=
,"","04-11-2024 14:22:30","04-11-2024 13:25:08","04-11-2024 15:12:32","Grid=
 outage site went down because Gen started and stopped with alarm coolant h=
igh temp and poor battery backup// He reset the Gen card and Gen manually s=
tarted","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","Grid outage site went down because Gen started and stopped wit=
h alarm coolant high temp and poor battery backup// He reset the Gen card a=
nd Gen manually started","system","3442","04-11-2024 14:22:30","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003491319","B=
riqueterie","","04-11-2024 14:05:18","04-11-2024 13:20:12","04-11-2024 13:5=
3:26","Grid outage , no space to deploy // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage , no space =
to deploy // Grid return","landry.etame@ihstowers.com","2707","04-11-2024 1=
4:05:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003491309","Nsimalen=
 OCM","","04-11-2024 14:02:40","04-11-2024 13:08:20","04-11-2024 13:15:47",=
"Cascaded Incident from TTO3391002","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","ACTIVE no power issue  Site is on Bat=
tery and Ubaie =3D53.5V The Tx FME Lionel Adjep (655184876)from Huawei is i=
nformed","system","3260","04-11-2024 14:02:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003491291","N=
kolda","IHS_YND_327","04-11-2024 14:00:47","04-11-2024 13:08:20","04-11-202=
4 19:10:47","ACTIVE no power issue  Site is on Battery and Ubaie =3D53.5V T=
he Tx FME Lionel Adjep (655184876)from Huawei is informed","Albran Byorel",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","ACTIVE no power issue  Site is on Battery and Ubaie =3D53.5V Th=
e Tx FME Lionel Adjep (655184876)from Huawei is informed","landry.etame@ihs=
towers.com","3148","04-11-2024 14:00:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003491283","Tradex-N=
komo","","04-11-2024 13:59:31","04-11-2024 13:25:08","04-11-2024 14:17:20",=
"Cascaded Incident from TTO3390984","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen start and stopped with alarm coolant high temp // He reset the Gen car=
d and Gen manually started","system","2063","04-11-2024 13:59:31","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003491284","AWAE OCM=
","","04-11-2024 13:59:31","04-11-2024 13:22:46","04-11-2024 14:17:20","Cas=
caded Incident from TTO3390984","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage site went down because =
Gen failed to start due to Static charger Faulty and battery gen discharged=
//Gen Started by external Battery(The charger static to be replaced)","syst=
em","2205","04-11-2024 13:59:31","Sagemcom CMR"
"Closed Complete","Site Down","T0462","IHS_YND_123","NOCINC0003491275","Nko=
mo II","IHS_YND_172, IHS_YND_173","04-11-2024 13:58:14","04-11-2024 13:25:0=
8","04-11-2024 14:17:20","Grid outage site went down because Gen start and =
stopped with alarm coolant high temp // He reset the Gen card and Gen manua=
lly started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- Control Panel","Grid outage site went down because Gen start and stopped =
with alarm coolant high temp // He reset the Gen card and Gen manually star=
ted","rouselle.schoune@ihstowers.com","1987","04-11-2024 13:58:14","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003491272","I=
mm-Olympique","","04-11-2024 13:57:56","04-11-2024 12:57:48","04-11-2024 12=
:59:22","No power issue on site ,site on Grid with Ubaie=3D53.3 V  The TxTx=
 Fme Eloundou ( 652586578 )of Huawei is informed.Notice that we have disjun=
ction at BTS OCM","Paul BIBOUM","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site ,site on=
 Grid with Ubaie=3D53.3 V  The TxTx Fme Eloundou ( 652586578 )of Huawei is =
informed.Notice that we have disjunction at BTS OCM","landry.etame@ihstower=
s.com","3609","04-11-2024 13:57:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003491267","C=
amp-Sic-Tsinga","","04-11-2024 13:57:05","04-11-2024 12:50:10","04-11-2024 =
13:58:34","","","Grid Supply","Passive","Grid","National Grid - Grid Outage=
 Issue","grid outage, no space for a MDG//grid return","landry.etame@ihstow=
ers.com","4016","04-11-2024 13:57:05","Sagemcom CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0003491222","Eto=
ug ebe Meweulo","","04-11-2024 13:56:23","04-11-2024 13:23:14","04-11-2024 =
13:33:37","Active: No power issue, site on grid with Ubaie=3D53V, Hosiah(67=
4007438) from Huawei is informed","Hyemafo Gildas","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No p=
ower issue, site on grid with Ubaie=3D53V, Hosiah(674007438) from Huawei is=
 informed","rouselle.schoune@ihstowers.com","1990","04-11-2024 13:56:23","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003491180","L=
abogenie","","04-11-2024 13:48:40","04-11-2024 13:29:34","04-11-2024 15:44:=
51","Grid outage , no space to deploy // Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage , no space to=
 deploy // Grid return","landry.etame@ihstowers.com","1147","04-11-2024 13:=
48:40","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003491131","Nsi=
meyong Terre Rouge","","04-11-2024 13:42:27","04-11-2024 12:55:20","04-11-2=
024 13:52:11","Grid outage, site went down before gen start due to poor bat=
tery backup // gen automatically started","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // gen automaticall=
y started","rouselle.schoune@ihstowers.com","2828","04-11-2024 13:42:27","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0003490547","M=
vog Mbi New","","04-11-2024 12:42:18","04-11-2024 12:25:13","04-11-2024 13:=
59:36","site went down because disjunction cb(125A) in PWC  due to load// H=
e reamed Cb(125A); site on grid","MINKA NICOLAS","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Circuit Breaker Issue","site went down =
because disjunction cb(125A) in PWC  due to load// He reamed Cb(125A); site=
 on grid","landry.etame@ihstowers.com","1026","04-11-2024 12:42:18","Sagemc=
om CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003490063","Bit=
oto","","04-11-2024 11:57:03","04-11-2024 11:54:55","04-11-2024 14:00:08","=
Grid outage site went down because Gen overload(20KVA, 300A) // he reduced =
the load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","Grid outage site went down because Gen overload(20KVA, 300A) /=
/ he reduced the load","rouselle.schoune@ihstowers.com","129","04-11-2024 1=
1:57:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003489784","B=
ATA-Mokolo","","04-11-2024 11:28:50","04-11-2024 11:23:43","05-11-2024 15:2=
4:55","Grid outage, no space to deploy a mobile Gen // Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, no space to deploy a mobile Gen // Grid return","landry.etame@ihstowers.c=
om","309","04-11-2024 11:28:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0003489748","N=
guila","IHS_YND_434, IHS_YND_444","04-11-2024 11:22:55","04-11-2024 11:11:4=
5","04-11-2024 12:36:27","site went down because Gen failed to start due to=
 battery Gen faulty// Gen manually started with external battery","Parker T=
choup","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","=
site went down because Gen failed to start due to battery Gen faulty// Gen =
manually started with external battery","landry.etame@ihstowers.com","672",=
"04-11-2024 11:22:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003489731","Dong",""=
,"04-11-2024 11:21:10","04-11-2024 11:11:45","04-11-2024 12:36:27","Cascade=
d Incident from TTO3389251","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","site went down because Gen failed to start=
 due to battery Gen faulty// Gen manually started with external battery","s=
ystem","899","04-11-2024 11:21:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0003489719","D=
onga","","04-11-2024 11:19:21","04-11-2024 11:11:45","04-11-2024 12:36:27",=
"","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","site went down because Gen failed to start due to battery Gen fault=
y// Gen manually started with external battery","landry.etame@ihstowers.com=
","955","04-11-2024 11:19:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003489307","B=
astos Bethesda","","04-11-2024 10:32:08","04-11-2024 10:24:02","04-11-2024 =
11:08:20","Grid bad Voltage, DG failed to start , no RCP //He did a bridge.=
","Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid bad Voltage, DG failed to start , no RCP //He did a b=
ridge.","landry.etame@ihstowers.com","487","04-11-2024 10:32:08","Sagemcom =
CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003488937","Feb=
e Village","","04-11-2024 09:46:00","04-11-2024 09:44:55","04-11-2024 09:46=
:17","","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, site went down before gen start due t=
o poor battery backup // Grid Restored","rouselle.schoune@ihstowers.com","6=
6","04-11-2024 09:46:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003488688","Dong",""=
,"04-11-2024 09:06:21","04-11-2024 08:44:50","04-11-2024 10:33:06","Cascade=
d Incident from TTO3388023","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power issue on site ,site on GEN  =
wiith Ubaie=3D51.9 V The TX FME Gregoire/ 654547479/  Huawei is informed.
","system","1291","04-11-2024 09:06:21","Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0003488656","Don=
ga","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_444","04-11-2024 09:00:=
08","04-11-2024 08:44:50","04-11-2024 10:33:06","Active//No power issue on =
site ,site on GEN  wiith Ubaie=3D51.9 V The TX FME Gregoire/ 654547479/  Hu=
awei is informed.","Parker Tchoup","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on si=
te ,site on GEN  wiith Ubaie=3D51.9 V The TX FME Gregoire/ 654547479/  Huaw=
ei is informed.
","rouselle.schoune@ihstowers.com","922","04-11-2024 09:00:08","Sagemcom CM=
R"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0003488614","Ngo=
um","","04-11-2024 08:51:27","04-11-2024 08:44:50","04-11-2024 10:33:06",""=
,"Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active=
","Active//No power issue on site ,site on GEN  wiith Ubaie=3D51.9 V The TX=
 FME Gregoire/ 654547479/  Huawei is informed.
","rouselle.schoune@ihstowers.com","1104","04-11-2024 08:51:27","Sagemcom C=
MR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003488602","MBI=
MBIM","","04-11-2024 08:48:35","04-11-2024 08:44:50","04-11-2024 10:33:06",=
"","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","Active//No power issue on site ,site on GEN  wiith Ubaie=3D51.9 V The =
TX FME Gregoire/ 654547479/  Huawei is informed.
","rouselle.schoune@ihstowers.com","1188","04-11-2024 08:48:35","Sagemcom C=
MR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0003488592","Mat=
sari","","04-11-2024 08:46:56","04-11-2024 08:44:50","04-11-2024 10:33:06",=
"","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","Active//No power issue on site ,site on GEN  wiith Ubaie=3D51.9 V The =
TX FME Gregoire/ 654547479/  Huawei is informed.
","rouselle.schoune@ihstowers.com","1154","04-11-2024 08:46:56","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003488550","N=
GONA","","04-11-2024 08:40:03","04-11-2024 08:35:24","04-11-2024 09:40:14",=
"Active//No power issue on site ,site on GRID  wiith Ubaie=3D55,7 V The TX =
FME  Lionel Adjep (655184876)  Huawei is informed. And Site UP AT =3D08:40 =
AM.","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active//No power issue on site ,site on=
 GRID  wiith Ubaie=3D55,7 V The TX FME  Lionel Adjep (655184876)  Huawei is=
 informed. And Site UP AT =3D08:40 AM.","landry.etame@ihstowers.com","280",=
"04-11-2024 08:40:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003488489","Kondengu=
i","","04-11-2024 08:26:30","04-11-2024 08:17:45","04-11-2024 10:05:11","Ca=
scaded Incident from TTO3387817","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage //Grid restored.","system=
","525","04-11-2024 08:26:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003488485","E=
mombo-Tchad","IHS_YND_114","04-11-2024 08:25:51","04-11-2024 08:17:45","04-=
11-2024 10:05:11","Grid outage //Grid restored.","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage //Grid restored.",=
"landry.etame@ihstowers.com","487","04-11-2024 08:25:51","Sagemcom CMR"
"Cancelled","Warning","T0837","IHS_YND_460","NOCINC0003488460","Matsari",""=
,"04-11-2024 08:19:35","","","","Parker Tchoup","","","","","","rouselle.sc=
houne@ihstowers.com","125","04-11-2024 08:19:35","Sagemcom CMR"
"Closed Complete","Site Down","T2149","IHS_EDA_056","NOCINC0003488309","Ndo=
gbessol","","04-11-2024 07:54:46","04-11-2024 07:22:41","04-11-2024 09:23:4=
1","Active//No power issue on site ,site on GEN  wiith Ubaie=3D51.9 V The T=
X FME Etienne/ 695033981/  Huawei is informed.","Kemeni Franklin","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site ,site on GEN  wiith Ubaie=3D51.9 V The TX=
 FME Etienne/ 695033981/  Huawei is informed.","rouselle.schoune@ihstowers.=
com","1925","04-11-2024 07:54:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003488153","Ngouetou=
","","04-11-2024 07:37:11","04-11-2024 07:29:42","04-11-2024 07:30:42","Cas=
caded Incident from TTO3387424","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","449","04-11-2024 07:37:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003488155","MBIMBIM"=
,"","04-11-2024 07:37:11","04-11-2024 07:29:42","04-11-2024 07:30:42","Casc=
aded Incident from TTO3387424","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","449","04-11-2024 07:37:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003488152","Yoko OCM=
","","04-11-2024 07:37:10","04-11-2024 07:29:42","04-11-2024 07:30:42","Cas=
caded Incident from TTO3387424","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","448","04-11-2024 07:37:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003488151","Matsari"=
,"","04-11-2024 07:37:10","04-11-2024 07:29:42","04-11-2024 07:30:42","Casc=
aded Incident from TTO3387424","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","448","04-11-2024 07:37:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003488149","Ngoum","=
","04-11-2024 07:37:10","04-11-2024 07:29:42","04-11-2024 07:30:42","Cascad=
ed Incident from TTO3387424","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","448","04-11-2024 07:37:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003488083","Nsimalen=
 OCM","","04-11-2024 07:26:20","04-11-2024 07:04:01","04-11-2024 07:37:52",=
"Cascaded Incident from TTO3387348","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid bad voltage,NO RCP,DG failed =
to start //He did a bridge.","system","1339","04-11-2024 07:26:20","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003488073","N=
kolda","IHS_YND_327","04-11-2024 07:23:11","04-11-2024 07:04:01","04-11-202=
4 07:37:52","Grid bad voltage,NO RCP,DG failed to start //He did a bridge."=
,"Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid bad voltage,NO RCP,DG failed to start //He did a bridg=
e.","landry.etame@ihstowers.com","1151","04-11-2024 07:23:11","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003487952","M=
arche Odza","","04-11-2024 06:56:04","04-11-2024 06:24:57","04-11-2024 10:3=
7:51","Active//No power issue on site ,site on Grid  wiith Ubaie=3D51.9 V T=
he TX FME Leonel Steve/ 655184876/  Huawei is informed.","Albran Byorel","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue on site ,site on Grid  wiith Ubaie=3D51.9 =
V The TX FME Leonel Steve/ 655184876/  Huawei is informed.","landry.etame@i=
hstowers.com","1868","04-11-2024 06:56:04","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003487900","NYO=
M FACE MAETUR","","04-11-2024 06:45:31","04-11-2024 06:43:10","04-11-2024 0=
8:45:49","Grid fluctuations  with bad voltages, landlord has forbiden to st=
art the gen due to noise // Grid power stabilized.","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid fluctuatio=
ns  with bad voltages, landlord has forbiden to start the gen due to noise =
// Grid power stabilized
","rouselle.schoune@ihstowers.com","142","04-11-2024 06:45:31","Sagemcom CM=
R"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003487890","MIM=
BOMAN LIBERTE","","04-11-2024 06:44:08","04-11-2024 06:39:22","04-11-2024 0=
7:13:26","Grid outage,main Gen faulty // MDG (20kva ) deploy","Mba Lazare H=
erve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Gr=
id outage,main Gen faulty // MDG (20kva ) deploy
","rouselle.schoune@ihstowers.com","287","04-11-2024 06:44:08","Sagemcom CM=
R"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003487859","Bas=
tos Amb Coree","","04-11-2024 06:35:39","04-11-2024 06:08:35","04-11-2024 1=
1:00:38","Grid outage,no space to deploy a mobile DG,waiting for grid resto=
red //Grid restored.","","Grid Supply","Passive","Grid","National Grid - Gr=
id Outage Issue","Grid outage,no space to deploy a mobile DG,waiting for gr=
id restored //Grid restored.","rouselle.schoune@ihstowers.com","1625","04-1=
1-2024 06:35:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003487771","Entree C=
ite Verte","","04-11-2024 06:11:01","04-11-2024 05:58:31","04-11-2024 09:48=
:29","Cascaded Incident from TTO3386988","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage //Mobile DG deploye=
d 20 kva.","system","750","04-11-2024 06:11:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003487764","C=
ite-Verte","IHS_YND_543","04-11-2024 06:09:43","04-11-2024 05:58:31","04-11=
-2024 09:48:29","Grid outage //Mobile DG deployed 20 kva.","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage //Mobile=
 DG deployed 20 kva.","alexandre.kamal@ihstowers.com","673","04-11-2024 06:=
09:43","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003487743","Mok=
olo Yaounde","","04-11-2024 06:03:58","04-11-2024 05:59:45","04-11-2024 10:=
17:25","Grid outage,no space to deploy a mobile DG,waiting for grid restore=
d//Grid restored.","","Grid Supply","Passive","Grid","National Grid - Grid =
Outage Issue","Grid outage,no space to deploy a mobile DG,waiting for grid =
restored//Grid restored.","kamga.virgile@ihstowers.com","254","04-11-2024 0=
6:03:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0003487741","L=
eboudi","","04-11-2024 06:02:55","04-11-2024 05:58:44","04-11-2024 06:00:52=
","Active//No power issue Ubaie=3D 54.3 V site on Gen The TX FME Mohamadou =
/691144435/ from huawei is informed and Site UP=3D06:01 AM.","TIENTCHEU NZE=
TCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active//No power issue Ubaie=3D 54.3 V site on Gen=
 The TX FME Mohamadou /691144435/ from huawei is informed and Site UP=3D06:=
01 AM
","alexandre.kamal@ihstowers.com","252","04-11-2024 06:02:55","Sagemcom CMR=
"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0003487739","Sim=
e Building","","04-11-2024 06:02:36","04-11-2024 05:57:45","04-11-2024 10:3=
0:44","Active//No power issue on site ,site on Grid  wiith Ubaie=3D51.9 V T=
he TX FME Brice Tsague/ 650214096/  Huawei is informed.","Mboua Thierry","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue on site ,site on Grid  wiith Ubaie=3D51.9 =
V The TX FME Brice Tsague/ 650214096/  Huawei is informed.
","kamga.virgile@ihstowers.com","292","04-11-2024 06:02:36","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0003487729","Mel=
en Ba'aba","","04-11-2024 05:58:26","04-11-2024 05:52:13","04-11-2024 09:49=
:21","Active//No power issue on site, Site on Grid UBAIE=3D54V  synphorien =
(675295205) From huawei is informed and Site UP AT=3D06:01 AM.","Siligap Bo=
ris","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active//No power issue on site, Site on Grid UBAIE=3D54V  =
synphorien (675295205) From huawei is informed and Site UP AT=3D06:01 AM.
","kamga.virgile@ihstowers.com","374","04-11-2024 05:58:26","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003486491","Bit=
eng","","03-11-2024 23:40:11","03-11-2024 23:33:31","03-11-2024 23:33:44","=
Error ticket because site not down","Mba Lazare Herve","Incorrectly Logged =
Tickets","Error","Error","Error","Error ticket because site not down","kamg=
a.virgile@ihstowers.com","401","03-11-2024 23:40:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003485764","N=
koabang","IHS_YND_736","03-11-2024 21:17:20","03-11-2024 20:49:01","03-11-2=
024 21:00:32","Grid outage, Site went down due to Gen overload (16.5kva, 18=
5A)// Grid power return","Mba Lazare Herve","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, Site went down due to Gen overload=
 (16.5kva, 185A)// Grid power return","stephane.nkamwa@ihstowers.com","1700=
","03-11-2024 21:17:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0003485648","C=
RF Nkoabang","","03-11-2024 21:00:58","03-11-2024 20:49:01","03-11-2024 21:=
00:32","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, Site went down due to Gen overload (16.5kva,=
 185A)// Grid power return","stephane.nkamwa@ihstowers.com","1721","03-11-2=
024 21:00:58","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003485613","Mok=
olo Yaounde","","03-11-2024 20:54:12","03-11-2024 20:42:05","03-11-2024 21:=
37:55","Grid outage No space to deploy MDG // Grid restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No spa=
ce to deploy MDG // Grid restored","landry.etame@ihstowers.com","728","03-1=
1-2024 20:54:12","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003485509","Bas=
tos Amb Coree","","03-11-2024 20:35:27","03-11-2024 20:29:10","03-11-2024 2=
1:52:40","Grid outage, no space to deploy MDG  // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no =
space to deploy MDG  // Grid return","landry.etame@ihstowers.com","378","03=
-11-2024 20:35:27","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003485369","OBA=
M NGOLA OCM","","03-11-2024 20:27:36","03-11-2024 20:11:32","03-11-2024 20:=
29:50","Site went down due to insufficient of rectifier on site//Site stabi=
lized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down due to insufficient of rectifier on site//Site stab=
ilized","landry.etame@ihstowers.com","965","03-11-2024 20:27:36","Sagemcom =
CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003485188","ODZ=
A CITE MBIA","","03-11-2024 20:02:15","03-11-2024 19:38:05","03-11-2024 20:=
11:26","Grid fluctuation, site went down because Gen started and stopped du=
e to Grid bad voltage No rcp on site// He bypassed Grid and started Gen man=
ualy","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid fluctuation, site went down because Gen started a=
nd stopped due to Grid bad voltage No rcp on site// He bypassed Grid and st=
arted Gen manualy","landry.etame@ihstowers.com","1451","03-11-2024 20:02:15=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_181","NOCINC0003485145","Mimboman=
3","","03-11-2024 19:55:21","03-11-2024 20:57:57","03-11-2024 21:13:29","Si=
te went down due to insufficient of rectifier on site//Site stabilized","Mb=
a Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due to insufficient of rectifier on site//Site stabilized"=
,"system","598","03-11-2024 19:55:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003485058","M=
fou EPC","","03-11-2024 19:36:34","03-11-2024 19:32:26","03-11-2024 20:43:1=
5","Grid Outage, site went down because Gen stopped with  alarm ""high temp=
"" // He added water and started Gen manualy","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issu=
e","Grid Outage, site went down because Gen stopped with  alarm ""high temp=
"" // He added water and started Gen manualy","stephane.nkamwa@ihstowers.co=
m","249","03-11-2024 19:36:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003484998","B=
iyemassi LAC","","03-11-2024 19:24:39","03-11-2024 19:07:01","03-11-2024 21=
:45:41","Active: no power issue, site is on grid with Ubaie=3D53V, Hosiah(6=
99699694) from Huawei is informed, Notice that we have disjunction at BTS O=
CM","","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active: no power issue, site is on grid with Ubaie=3D53V=
, Hosiah(699699694) from Huawei is informed, Notice that we have disjunctio=
n at BTS OCM","stephane.nkamwa@ihstowers.com","1059","03-11-2024 19:24:39",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003484249","M=
IMBOMAN LIBERTE","","03-11-2024 17:40:59","03-11-2024 17:23:27","03-11-2024=
 18:13:13","grid outage, site went due to disjunction Cb(2*80A) in PWC // H=
e bypassed Cb(2*80A) , site on gen","Mba Lazare Herve","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","grid outa=
ge, site went due to disjunction Cb(2*80A) in PWC // He bypassed Cb(2*80A) =
, site on gen","stephane.nkamwa@ihstowers.com","1053","03-11-2024 17:40:59"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0003484148","UPA=
C LP","","03-11-2024 17:20:46","03-11-2024 17:11:22","03-11-2024 17:21:28",=
"No power issue on site Ubaie=3D52,9V site on Grid The tx fme Armand nguets=
a(691144412) is informed","","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie=3D52,=
9V site on Grid The tx fme Armand nguetsa(691144412) is informed","landry.e=
tame@ihstowers.com","565","03-11-2024 17:20:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003483601","Eto koss=
 Yde","","03-11-2024 16:11:31","03-11-2024 16:05:46","03-11-2024 16:11:56",=
"Cascaded Incident from TTO3382013","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to grid bad volta=
ge and insuficiency of rectifiers// Gen manually started","system","345","0=
3-11-2024 16:11:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003483602","ELOUMDEM=
 CARRIERE 2","","03-11-2024 16:11:31","03-11-2024 16:05:46","03-11-2024 16:=
11:56","Cascaded Incident from TTO3382013","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down due to grid ba=
d voltage and insuficiency of rectifiers// Gen manually started","system","=
1215629","03-11-2024 16:11:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003483574","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","03-11-2024 16:09:06","03-11-2024 16:=
03:00","03-11-2024 16:11:56","site went down due to grid bad voltage and in=
suficiency of rectifiers// Gen manually started","Fanda Brice","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","site went dow=
n due to grid bad voltage and insuficiency of rectifiers// Gen manually sta=
rted","stephane.nkamwa@ihstowers.com","368","03-11-2024 16:09:06","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003483454","Eto koss=
 Yde","","03-11-2024 15:52:40","03-11-2024 15:43:33","03-11-2024 15:46:31",=
"Cascaded Incident from TTO3381766","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to grid bad volta=
ge and insuficiency of rectifiers// Gen manually started","system","547","0=
3-11-2024 15:52:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003483455","ELOUMDEM=
 CARRIERE 2","","03-11-2024 15:52:40","03-11-2024 15:43:33","03-11-2024 15:=
46:31","Cascaded Incident from TTO3381766","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down due to grid ba=
d voltage and insuficiency of rectifiers// Gen manually started","system","=
547","03-11-2024 15:52:40","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003483387","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","03-11-2024 15:45:42","03-11-2024 15:43=
:33","03-11-2024 15:46:31","site went down due to grid bad voltage and insu=
ficiency of rectifiers// Gen manually started","Fanda Brice","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","site went down =
due to grid bad voltage and insuficiency of rectifiers// Gen manually start=
ed","landry.etame@ihstowers.com","130","03-11-2024 15:45:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003483276","MBIMBIM"=
,"","03-11-2024 15:25:01","03-11-2024 15:14:12","03-11-2024 15:14:13","Casc=
aded Incident from TTO3381571","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","649","03-11-2024 15:25:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003483269","Ngoum","=
","03-11-2024 15:25:00","03-11-2024 15:14:12","03-11-2024 15:14:13","Cascad=
ed Incident from TTO3381571","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","648","03-11-2024 15:25:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003483270","Matsari"=
,"","03-11-2024 15:25:00","03-11-2024 15:14:12","03-11-2024 15:14:13","Casc=
aded Incident from TTO3381571","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","648","03-11-2024 15:25:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003483273","Ngouetou=
","","03-11-2024 15:25:00","03-11-2024 15:14:12","03-11-2024 15:14:13","Cas=
caded Incident from TTO3381571","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","648","03-11-2024 15:25:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003483271","Yoko OCM=
","","03-11-2024 15:25:00","03-11-2024 15:14:12","03-11-2024 15:14:13","Cas=
caded Incident from TTO3381571","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","648","03-11-2024 15:25:00","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003482915","Bas=
tos Amb Coree","","03-11-2024 15:01:17","03-11-2024 14:53:12","03-11-2024 1=
5:03:52","grid outage, no space to deploy a mobile gen // grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid out=
age, no space to deploy a mobile gen // grid return","landry.etame@ihstower=
s.com","486","03-11-2024 15:01:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003482418","O=
lembe-Terminus","","03-11-2024 14:30:34","03-11-2024 14:03:16","03-11-2024 =
15:42:09","site went down due to disfunctionning of PSC3 // He bypassed the=
 PSC 3, site on grid","Fabrice Pouakam","Equipment Repair","Passive","Contr=
ol Panel","Panel Distribution Board","site went down due to disfunctionning=
 of PSC3 // He bypassed the PSC 3, site on grid","stephane.nkamwa@ihstowers=
.com","1639","03-11-2024 14:30:34","Sagemcom CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0003482170","Nya=
hoo","","03-11-2024 14:08:17","03-11-2024 13:59:08","03-11-2024 14:10:38","=
No power issue on site U=3D56,3v site on gen Gregoire of huawei is informed=
","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D56,3v s=
ite on gen Gregoire of huawei is informed","christian.fonkou@ihstowers.com"=
,"550","03-11-2024 14:08:17","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003480994","NYO=
M 2 IHS","","03-11-2024 11:20:25","03-11-2024 11:12:17","03-11-2024 11:31:5=
1","Grid outage site went down becaus Gen overload (15Kva; 310A) // Grid po=
wer return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Overload","Grid outage site went down becaus Gen overload (15Kva; 310A) =
// Grid power return","christian.fonkou@ihstowers.com","773","03-11-2024 11=
:20:25","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003480814","Ess=
os Marche","","03-11-2024 10:54:23","03-11-2024 10:45:15","03-11-2024 10:48=
:16","Grid fluctuation, site went down because Gen fails to start due to Gr=
id bad voltage //Grid Restored","Delor Telezing","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Grid fluctuation, site went=
 down because Gen fails to start due to Grid bad voltage //Grid Restored","=
christian.fonkou@ihstowers.com","549","03-11-2024 10:54:23","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003480807","San=
ta Barbara Gottam","","03-11-2024 10:52:55","03-11-2024 10:43:50","03-11-20=
24 11:23:55","Site went down due to PWC dysfonctioning ( Batteries Backup  =
alarming ; PWC FNS)//Reset Batteries Backup,site on Grid.","Delor Telezing"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Si=
te went down due to PWC dysfonctioning ( Batteries Backup  alarming ; PWC F=
NS)//Reset Batteries Backup,site on Grid.","christian.fonkou@ihstowers.com"=
,"546","03-11-2024 10:52:55","Sagemcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0003480770","Nko=
lbisson usine des eaux","IHS_YND_712","03-11-2024 10:47:29","03-11-2024 10:=
41:23","03-11-2024 11:02:58","Grid Outage and Main Gen Faulty// MDG of 15Kv=
a has deployed","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","AC=
DG Gen","ACDG - Generator Faulty","Grid Outage and Main Gen Faulty// MDG of=
 15Kva has deployed","christian.fonkou@ihstowers.com","366","03-11-2024 10:=
47:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0003480756","N=
kolkoumou OCM","","03-11-2024 10:44:58","03-11-2024 10:41:23","03-11-2024 1=
1:02:58","please cascded this Tickect behind Nkolbisson usines des eaux ","=
TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Outage and Main Gen Faulty// MDG of 15Kva has deployed"=
,"emmanuel.ghani@ihstowers.com","10839","03-11-2024 10:44:58","Sagemcom CMR=
"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0003480678","Ngo=
usso Vallee","","03-11-2024 10:33:18","03-11-2024 09:53:13","03-11-2024 10:=
32:27","Grid outage, site went down because gen start and stoppen with alar=
m ""low oil pressure // He reset gen card and gen manually started","Siliga=
p Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage, site went down because gen start and stoppen with alarm ""low oi=
l pressure // He reset gen card and gen manually started","joelle.ekessi@ih=
stowers.com","2406","03-11-2024 10:33:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003480666","C=
rf Cornier","","03-11-2024 10:30:35","03-11-2024 10:27:54","03-11-2024 12:2=
7:55","Active, no power issue, U=3D53V on grid, TX FME georges dassi/697461=
814 From huawei is informed","MINKA NICOLAS","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power i=
ssue, U=3D53V on grid, TX FME georges dassi/697461814 From huawei is inform=
ed","emmanuel.ghani@ihstowers.com","162","03-11-2024 10:30:35","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0003480563","Y=
ona Hotel","","03-11-2024 10:14:38","03-11-2024 10:07:31","03-11-2024 11:45=
:45","Grid outage, site went down because Gen failed to start due to contac=
tor Grid faulty//He bypassed Grid contactor and started Gen manualy","TIENT=
CHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","ATS-AMF =
Issue","Grid outage, site went down because Gen failed to start due to cont=
actor Grid faulty//He bypassed Grid contactor and started Gen manualy","emm=
anuel.ghani@ihstowers.com","428","03-11-2024 10:14:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0003480561","M=
obil-Kondengui","IHS_YND_682","03-11-2024 10:14:04","03-11-2024 10:05:00","=
03-11-2024 10:55:53","Grid Outage//Grid Restored","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid Outage//Grid Restored","=
emmanuel.ghani@ihstowers.com","545","03-11-2024 10:14:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0003480559","M=
ONTEE NKONDENGUI","","03-11-2024 10:13:31","03-11-2024 10:05:00","03-11-202=
4 10:55:53","","Albran Byorel","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid Outage//Grid Restored","emmanuel.ghani@ihstowers.c=
om","1237225","03-11-2024 10:13:31","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003480503","OBA=
M NGOLA OCM","","03-11-2024 10:05:40","03-11-2024 09:59:12","03-11-2024 10:=
17:17","Site went down due to insufficient of rectifier on site//Site stabi=
lized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down due to insufficient of rectifier on site//Site stab=
ilized","christian.fonkou@ihstowers.com","389","03-11-2024 10:05:40","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003480463","I=
mm-Olympique","","03-11-2024 09:57:58","03-11-2024 09:55:51","03-11-2024 10=
:37:06","Grid outage,gen failed to start due to power cable of gen stolen s=
ince//he started the gen with another power cable","Paul BIBOUM","Site Asse=
t Theft","Theft","Theft","AC Cable Stolen","Grid outage,gen failed to start=
 due to power cable of gen stolen since//he started the gen with another po=
wer cable","emmanuel.ghani@ihstowers.com","478","03-11-2024 09:57:58","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003480448","E=
mombo-Tchad","","03-11-2024 09:56:21","03-11-2024 09:50:13","03-11-2024 10:=
50:20","Grid Outage No Space to deploy a MGD // Grid Restored Restored","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Ou=
tage No Space to deploy a MGD // Grid Restored Restored","emmanuel.ghani@ih=
stowers.com","369","03-11-2024 09:56:21","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003480402","HOP=
ITAL GENERAL RAIL YDE","","03-11-2024 09:43:13","03-11-2024 09:39:08","03-1=
1-2024 13:20:08","Active//No power issue, site is on Gen with Ubaie=3D50,9V=
, Armand nguetsa(699949553) from Huawei is informed ","Delor Telezing","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active//No power issue, site is on Gen with Ubaie=3D50,9V, Armand n=
guetsa(699949553) from Huawei is informed ","christian.fonkou@ihstowers.com=
","246","03-11-2024 09:43:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0003480383","F=
OUGEROLE","","03-11-2024 09:40:40","03-11-2024 09:34:29","03-11-2024 11:01:=
59","Grid Outage Gen Failed to Start due to CB (32 A)  Gen Disjunted // He =
reamed the CB (32 A) Gen and site is on Gen","Siligap Boris","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Load Breaker","Grid Outage Gen Failed to =
Start due to CB (32 A)  Gen Disjunted // He reamed the CB (32 A) Gen and si=
te is on Gen","emmanuel.ghani@ihstowers.com","372","03-11-2024 09:40:40","S=
agemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003480240","Nko=
abang2","","03-11-2024 09:25:32","03-11-2024 09:19:15","03-11-2024 09:31:16=
","Grid outage site went down because Gen started and stopped with alarm un=
der voltage // He reset the Gen card and Gen manually started","Mba Lazare =
Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage site went down because Gen started and stopped with alarm under vol=
tage // He reset the Gen card and Gen manually started","christian.fonkou@i=
hstowers.com","378","03-11-2024 09:25:32","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0003480224","Ngo=
usso Vallee","","03-11-2024 09:22:42","03-11-2024 09:13:37","03-11-2024 09:=
29:36","Grdi Outage Site went down because gen start and stopped with alarm=
 'Low oil pressure' // He reset card GE and Gen manually started","Siligap =
Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grdi=
 Outage Site went down because gen start and stopped with alarm 'Low oil pr=
essure' // He reset card GE and Gen manually started","christian.fonkou@ihs=
towers.com","546","03-11-2024 09:22:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_087","NOCINC0003480157","Camp-Sic=
-Tsinga","","03-11-2024 09:16:32","03-11-2024 09:07:47","03-11-2024 09:31:2=
4","Cascaded Incident from TTO3377998","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid outage site went down because the Gen f=
ailed to start due To Gen contactor dysfonction // He bypass the Gen contac=
tor and Gen manually started","system","525","03-11-2024 09:16:32","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_083","NOCINC0003480155","H-Progre=
s","","03-11-2024 09:16:32","03-11-2024 09:07:47","03-11-2024 09:31:24","Ca=
scaded Incident from TTO3377998","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage site went down because the Gen failed =
to start due To Gen contactor dysfonction // He bypass the Gen contactor an=
d Gen manually started","system","525","03-11-2024 09:16:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0003480158","Tsinga",=
"","03-11-2024 09:16:32","03-11-2024 09:07:47","03-11-2024 09:31:24","Casca=
ded Incident from TTO3377998","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage site went down because the G=
en failed to start due To Gen contactor dysfonction // He bypass the Gen co=
ntactor and Gen manually started","system","525","03-11-2024 09:16:32","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_028","NOCINC0003480156","H-Centra=
l","","03-11-2024 09:16:32","03-11-2024 09:07:47","03-11-2024 09:31:24","Ca=
scaded Incident from TTO3377998","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage site went down because the =
Gen failed to start due To Gen contactor dysfonction // He bypass the Gen c=
ontactor and Gen manually started","system","525","03-11-2024 09:16:32","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_010","NOCINC0003480153","CNR","",=
"03-11-2024 09:16:31","03-11-2024 09:07:47","03-11-2024 09:31:24","Cascaded=
 Incident from TTO3377998","Mboua Thierry","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage site went down because the Gen =
failed to start due To Gen contactor dysfonction // He bypass the Gen conta=
ctor and Gen manually started","system","524","03-11-2024 09:16:31","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0003480151","Bastos-N=
ylon","","03-11-2024 09:16:31","03-11-2024 09:07:47","03-11-2024 09:31:24",=
"Cascaded Incident from TTO3377998","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 the Gen failed to start due To Gen contactor dysfonction // He bypass the =
Gen contactor and Gen manually started","system","524","03-11-2024 09:16:31=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_002","NOCINC0003480154","Yde-M-Ce=
ntral","","03-11-2024 09:16:31","03-11-2024 09:07:47","03-11-2024 09:31:24"=
,"Cascaded Incident from TTO3377998","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage site went down because the Gen fai=
led to start due To Gen contactor dysfonction // He bypass the Gen contacto=
r and Gen manually started","system","524","03-11-2024 09:16:31","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0003480152","Bastos B=
ethesda","","03-11-2024 09:16:31","03-11-2024 09:07:47","03-11-2024 09:31:2=
4","Cascaded Incident from TTO3377998","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use the Gen failed to start due To Gen contactor dysfonction // He bypass t=
he Gen contactor and Gen manually started","system","524","03-11-2024 09:16=
:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0003480118","C=
NDH","IHS_YND_126, IHS_YND_563, IHS_YND_010, IHS_YND_002, IHS_YND_083, IHS_=
YND_028, IHS_YND_087, IHS_YND_127","03-11-2024 09:11:55","03-11-2024 09:07:=
47","03-11-2024 09:31:24","Grid outage site went down because the Gen faile=
d to start due To Gen contactor dysfonction // He bypass the Gen contactor =
and Gen manually started","Paul BIBOUM","Equipment Repair","Passive","Contr=
ol Panel","ATS-AMF Issue","Grid outage site went down because the Gen faile=
d to start due To Gen contactor dysfonction // He bypass the Gen contactor =
and Gen manually started","emmanuel.ghani@ihstowers.com","248","03-11-2024 =
09:11:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0003480070","A=
nguissa New","","03-11-2024 09:02:55","03-11-2024 08:48:52","03-11-2024 10:=
54:05","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid Outage No Space to deploy a MDG //Grid Restored","emman=
uel.ghani@ihstowers.com","10829","03-11-2024 09:02:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003480040","H=
-General-Yde","","03-11-2024 08:57:18","03-11-2024 08:49:13","03-11-2024 10=
:33:23","Grid outage site went down because Gen failed to start // Gen manu=
ally started (investigation ongoing)","Siligap Boris","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage site went down becau=
se Gen failed to start // Gen manually started (investigation ongoing)","em=
manuel.ghani@ihstowers.com","486","03-11-2024 08:57:18","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_292","NOCINC0003480039","Bitoto",""=
,"03-11-2024 08:57:11","","","Grid outage site alarming because Gen over lo=
ad (20KVA, 300A) // He reduced the load and alarm cleared","Mba Lazare Herv=
e","Warning","Warning","POWER","Warning - Site on Battery","Grid outage sit=
e alarming because Gen over load (20KVA, 300A) // He reduced the load and a=
larm cleared","joelle.ekessi@ihstowers.com","3","03-11-2024 08:57:11","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003480032","L=
abogenie","IHS_YND_568","03-11-2024 08:55:57","03-11-2024 08:48:52","03-11-=
2024 10:54:05","Grid Outage No Space to deploy a MDG //Grid Restored","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outa=
ge No Space to deploy a MDG //Grid Restored","emmanuel.ghani@ihstowers.com"=
,"427","03-11-2024 08:55:57","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0003480017","Eko=
mbitie","","03-11-2024 08:53:38","03-11-2024 08:46:31","03-11-2024 08:56:43=
","Grid outage site went down because Gen failed to start with alarm Gen cl=
ose // He reset the Gen card and Gen manually started","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage s=
ite went down because Gen failed to start with alarm Gen close // He reset =
the Gen card and Gen manually started","christian.fonkou@ihstowers.com","42=
8","03-11-2024 08:53:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003480000","N=
GONA","","03-11-2024 08:49:56","03-11-2024 08:44:50","03-11-2024 13:15:59",=
"ACTIVE no power issue  Site is on Grid and Ubaie =3D55.5V The Tx FME Lione=
l Adjep (655184876)from Huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE no power issue  Site is on Grid and Ubaie =3D55.5V The Tx FME Lionel=
 Adjep (655184876)from Huawei is informed","emmanuel.ghani@ihstowers.com","=
307","03-11-2024 08:49:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003479983","Emana ly=
cee 2","","03-11-2024 08:46:42","03-11-2024 08:42:25","03-11-2024 09:00:28"=
,"Cascaded Incident from TTO3377816","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause Gen Start and Stop due to Under frequency alarm// he reset the Gen car=
d and started Gen manualy","system","257","03-11-2024 08:46:42","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003479980","EMANA BI=
LICK CITY","","03-11-2024 08:46:42","03-11-2024 08:42:25","03-11-2024 09:00=
:28","Cascaded Incident from TTO3377816","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 because Gen Start and Stop due to Under frequency alarm// he reset the Gen=
 card and started Gen manualy","system","257","03-11-2024 08:46:42","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003479981","Emana Ly=
cee","","03-11-2024 08:46:42","03-11-2024 08:42:25","03-11-2024 09:00:28","=
Cascaded Incident from TTO3377816","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se Gen Start and Stop due to Under frequency alarm// he reset the Gen card =
and started Gen manualy","system","257","03-11-2024 08:46:42","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003479982","Messassi=
 okolo","","03-11-2024 08:46:42","03-11-2024 08:42:25","03-11-2024 09:00:28=
","Cascaded Incident from TTO3377816","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause Gen Start and Stop due to Under frequency alarm// he reset the Gen ca=
rd and started Gen manualy","system","257","03-11-2024 08:46:42","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003479979","Mballa 4=
","","03-11-2024 08:46:41","03-11-2024 08:42:25","03-11-2024 09:00:28","Cas=
caded Incident from TTO3377816","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down because G=
en Start and Stop due to Under frequency alarm// he reset the Gen card and =
started Gen manualy","system","256","03-11-2024 08:46:41","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003479973","NYO=
M FACE MAETUR","","03-11-2024 08:45:44","03-11-2024 08:37:39","03-11-2024 1=
1:33:31","Grid Outage Site went Down due to  landlord has forbiden to start=
 the Gen Because  the  Noise //Grid Restored","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Emergency Stop","Grid Outage Site went=
 Down due to  landlord has forbiden to start the Gen Because  the  Noise //=
Grid Restored","christian.fonkou@ihstowers.com","486","03-11-2024 08:45:44"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003479961","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","03=
-11-2024 08:44:29","03-11-2024 08:42:25","03-11-2024 09:00:28","Grid outage=
, site went down because Gen Start and Stop due to Under frequency alarm// =
he reset the Gen card and started Gen manualy","Fabrice Pouakam","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site wen=
t down because Gen Start and Stop due to Under frequency alarm// he reset t=
he Gen card and started Gen manualy","emmanuel.ghani@ihstowers.com","125","=
03-11-2024 08:44:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003479929","O=
lembe-Terminus","","03-11-2024 08:39:56","03-11-2024 08:32:52","03-11-2024 =
10:22:31","Grid Outage,Gen Failed to Start due to alarms ''Gen-Over Voltage=
'' //He Reset the Gen Card and Manually Started the Gen ","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outag=
e,Gen Failed to Start due to alarms ''Gen-Over Voltage'' //He Reset the Gen=
 Card and Manually Started the Gen ","emmanuel.ghani@ihstowers.com","426","=
03-11-2024 08:39:56","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003479893","Pha=
rmacie SION","","03-11-2024 08:30:45","03-11-2024 08:23:32","03-11-2024 08:=
33:58","Grid outage, site went down before gen start due to poor battery ba=
ckup // gen automatically started","Paul BIBOUM","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // gen automatically started=
","christian.fonkou@ihstowers.com","434","03-11-2024 08:30:45","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0003479890","S=
apeur Mimboman","","03-11-2024 08:30:04","03-11-2024 08:26:57","03-11-2024 =
10:44:02","Grid outage, site went down because Gen failed to start due to b=
attery gen faulty// Gen manually started with external battery","Mba Lazare=
 Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery",=
"Grid outage, site went down because gen failed to start due to battery gen=
 faulty// Gen manually started with external battery","emmanuel.ghani@ihsto=
wers.com","188","03-11-2024 08:30:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0003479855","E=
mombo","","03-11-2024 08:25:35","03-11-2024 08:24:25","03-11-2024 10:01:58"=
,"Grid outage site went down because Gen started and stopped with alarm low=
 oil pressure // He reset the Gen card and Gen manually started","Mba Lazar=
e Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage site went down because Gen started and stopped with alarm low oil=
 pressure // He reset the Gen card and Gen manually started","emmanuel.ghan=
i@ihstowers.com","70","03-11-2024 08:25:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0003479849","K=
ondengui","","03-11-2024 08:24:29","03-11-2024 08:21:21","03-11-2024 09:47:=
47","Grid outage, site went down because gen start and stopped with 'Higth =
temp' Alarm // he added water and manually start the gen","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant L=
evel Issue","Grid outage, site went down because gen start and stopped with=
 'Higth temp' Alarm // he added water and manually start the gen","emmanuel=
.ghani@ihstowers.com","189","03-11-2024 08:24:29","Sagemcom CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0003479847","CLE=
 Building","","03-11-2024 08:23:46","03-11-2024 08:19:42","03-11-2024 10:41=
:43","Grid Outage No Space to deploy a MDG // Grid Restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spa=
ce to deploy a MDG // Grid Restored","christian.fonkou@ihstowers.com","245"=
,"03-11-2024 08:23:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003479846","M=
ANGUIERS CHAPELLE","","03-11-2024 08:22:58","03-11-2024 08:19:49","03-11-20=
24 08:35:10","Grid outage, site went down before gen start due to poor batt=
ery backup // gen start automatically","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // gen start automat=
ically","emmanuel.ghani@ihstowers.com","190","03-11-2024 08:22:58","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003479840","S=
atcom","","03-11-2024 08:20:51","03-11-2024 08:17:45","03-11-2024 12:34:45"=
,"Active//No power issue on site, Site on Grid UBAIE=3D58.8V  and Geoge (69=
7461814) From huawei is informed.","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site, Site on Grid UBAIE=3D58.8V  and Geoge (697461814) From=
 huawei is informed.","emmanuel.ghani@ihstowers.com","187","03-11-2024 08:2=
0:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003479822","S=
tade-Abega","","03-11-2024 08:16:56","03-11-2024 08:15:46","03-11-2024 10:2=
0:29","Grid outage site went down because Gen failed to start  due to bourg=
ie pre-heating faulty //Gen manually started","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid outage site went =
down because Gen failed to start  due to bourgie pre-heating faulty //Gen m=
anually started","emmanuel.ghani@ihstowers.com","71","03-11-2024 08:16:56",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003479752","Biteng-M=
aetur","","03-11-2024 08:11:51","03-11-2024 08:04:51","03-11-2024 08:08:51"=
,"Cascaded Incident from TTO3377563","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down du=
e to poor batteries backup before Gen start //Gen started automatically","s=
ystem","420","03-11-2024 08:11:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003479749","Tradex-N=
komo","","03-11-2024 08:11:50","03-11-2024 08:04:51","03-11-2024 08:08:51",=
"Cascaded Incident from TTO3377563","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Site went down due to=
 poor batteries backup before Gen start //Gen started automatically","syste=
m","419","03-11-2024 08:11:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003479751","Essomba"=
,"","03-11-2024 08:11:50","03-11-2024 08:04:51","03-11-2024 08:08:51","Casc=
aded Incident from TTO3377563","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, Site went down due to p=
oor batteries backup before Gen start //Gen started automatically","system"=
,"419","03-11-2024 08:11:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003479748","Bitoto",=
"","03-11-2024 08:11:50","03-11-2024 08:04:51","03-11-2024 08:08:51","Casca=
ded Incident from TTO3377563","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, Site went down due to po=
or batteries backup before Gen start //Gen started automatically","system",=
"419","03-11-2024 08:11:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003479750","AWAE OCM=
","","03-11-2024 08:11:50","03-11-2024 08:04:51","03-11-2024 08:08:51","Cas=
caded Incident from TTO3377563","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, Site went down due to =
poor batteries backup before Gen start //Gen started automatically","system=
","419","03-11-2024 08:11:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003479731","B=
iteng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179, IHS_YND_249","0=
3-11-2024 08:06:59","03-11-2024 08:04:51","03-11-2024 08:08:51","Grid outag=
e, Site went down due to poor batteries backup before Gen start //Gen start=
ed automatically","Mba Lazare Herve","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, Site went down due to po=
or batteries backup before Gen start //Gen started automatically","emmanuel=
.ghani@ihstowers.com","129","03-11-2024 08:06:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0003479672","L=
obo OCM","","03-11-2024 07:54:11","03-11-2024 07:49:35","03-11-2024 07:55:3=
6","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid outage, Site went down due to poor batteries bac=
kup before Gen start //Gen started automatically","emmanuel.ghani@ihstowers=
.com","1223795","03-11-2024 07:54:11","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003479654","N=
KOMEKUI OCM","IHS_YND_341","03-11-2024 07:50:44","03-11-2024 07:49:35","03-=
11-2024 07:55:36","Grid outage, Site went down due to poor batteries backup=
 before Gen start //Gen started automatically","TIENTCHEU NZETCHIEU GAEL","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","=
Grid outage, Site went down due to poor batteries backup before Gen start /=
/Gen started automatically","emmanuel.ghani@ihstowers.com","70","03-11-2024=
 07:50:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003479348","Yoko OCM=
","","03-11-2024 06:35:21","03-11-2024 06:29:23","03-11-2024 06:30:25","Cas=
caded Incident from TTO3377097","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","358","03-11-2024 06:35:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003479349","Ngouetou=
","","03-11-2024 06:35:21","03-11-2024 06:29:23","03-11-2024 06:30:25","Cas=
caded Incident from TTO3377097","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.",=
"system","358","03-11-2024 06:35:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003479351","MBIMBIM"=
,"","03-11-2024 06:35:21","03-11-2024 06:29:23","03-11-2024 06:30:25","Casc=
aded Incident from TTO3377097","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","358","03-11-2024 06:35:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003479347","Matsari"=
,"","03-11-2024 06:35:21","03-11-2024 06:29:23","03-11-2024 06:30:25","Casc=
aded Incident from TTO3377097","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","358","03-11-2024 06:35:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003479346","Ngoum","=
","03-11-2024 06:35:20","03-11-2024 06:29:23","03-11-2024 06:30:25","Cascad=
ed Incident from TTO3377097","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 53V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","357","03-11-2024 06:35:20","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003479276","N=
yanon","","03-11-2024 06:19:53","03-11-2024 06:12:48","03-11-2024 06:54:02"=
,"Hybrid Gen Site: site went down because of the dysfunctioning of hybrid s=
ystem // He reset it, site on Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Re=
pair","Passive","Hybrid","Hybrid Module","Hybrid Gen Site: site went down b=
ecause of the dysfunctioning of hybrid system // He reset it, site on Gen",=
"emmanuel.ghani@ihstowers.com","427","03-11-2024 06:19:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003478046","N=
kolfon Cimencam","","02-11-2024 23:37:51","02-11-2024 23:36:46","02-11-2024=
 23:56:46","No power issue on site U=3D54,5v site on Gen The Rm Alain (6911=
44423) of huawei is informed","Hyemafo Gildas","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D54,5v site on Gen The Rm Alain (691144423) of huawei is informed=
","ludivine.ngamaleu@ihstowers.com","65","02-11-2024 23:37:51","Sagemcom CM=
R"
"Closed Complete","Site Down","T0050","IHS_YND_039","NOCINC0003477831","Sia=
ntou Radio TV","","02-11-2024 22:55:49","02-11-2024 22:25:41","04-11-2024 1=
6:46:41","access issue due to landlord Grid outage No space to deploy // Gr=
id power return","","Access Denial","Lease Or Legal","Landlord Related Issu=
es","Access Issue - Land Lord","access issue due to landlord Grid outage No=
 space to deploy // Grid power return","olivier.kwedi@ihstowers.com","1809"=
,"02-11-2024 22:55:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003477477","Dong",""=
,"02-11-2024 21:44:41","02-11-2024 21:25:37","03-11-2024 00:16:37","Cascade=
d Incident from TTO3374836","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","site went down because gen fails to start =
due to the battery discharged causing by charging alternator faulty // gen =
start with battery backup","system","1144","02-11-2024 21:44:41","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003477476","Donga","=
","02-11-2024 21:44:41","02-11-2024 21:25:37","03-11-2024 00:16:37","Cascad=
ed Incident from TTO3374836","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because gen fails to start=
 due to the battery discharged causing by charging alternator faulty // gen=
 start with battery backup","system","1144","02-11-2024 21:44:41","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0003477414","Ngu=
ila","IHS_YND_434, IHS_YND_444","02-11-2024 21:33:56","02-11-2024 21:25:37"=
,"03-11-2024 00:16:37","site went down because gen fails to start due to th=
e battery discharged causing by charging alternator faulty // gen start wit=
h battery backup","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","=
ACDG - Charging Alternator","site went down because gen fails to start due =
to the battery discharged causing by charging alternator faulty // gen star=
t with battery backup","kamga.virgile@ihstowers.com","500","02-11-2024 21:3=
3:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003477230","M=
fou EPC","","02-11-2024 21:06:25","02-11-2024 20:53:19","02-11-2024 21:31:1=
9","Grid fluctuation, site went down because Gen fails to start due to Grid=
 bad voltage // he bypass Grid and manually start the Gen","Mba Lazare Herv=
e","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, site went down because Gen fails to start due to Grid b=
ad voltage // he bypass Grid and manually start the Gen","alexandre.kamal@i=
hstowers.com","787","02-11-2024 21:06:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003477078","E=
bogo","","02-11-2024 20:39:26","02-11-2024 20:34:17","03-11-2024 00:19:01",=
"Active//No power issue on site, Site on Grid UBAIE=3D54V  synphorien (6752=
95205) From huawei is informed. Notice that we have disjunction at BTS OCM"=
,"Siligap Boris","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active//No power issue on site, Site on Grid U=
BAIE=3D54V  synphorien (675295205) From huawei is informed. Notice that we =
have disjunction at BTS OCM","alexandre.kamal@ihstowers.com","310","02-11-2=
024 20:39:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003476970","TSINGA V=
ILLAGE 2","","02-11-2024 20:25:11","02-11-2024 20:15:38","02-11-2024 20:30:=
10","Cascaded Incident from TTO3374238","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site ,site on =
Grid with Ubaie=3D53.7 V The Tx Synphorien (675295205) From huawei is infor=
med. Notice that we have disjunction at BTS OCM","system","573","02-11-2024=
 20:25:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003476968","Nkolfoul=
ou 2","","02-11-2024 20:25:10","02-11-2024 20:15:38","02-11-2024 20:30:10",=
"Cascaded Incident from TTO3374238","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site ,site on Grid =
with Ubaie=3D53.7 V The Tx Synphorien (675295205) From huawei is informed. =
Notice that we have disjunction at BTS OCM","system","572","02-11-2024 20:2=
5:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003476969","Melen Ba=
'aba","","02-11-2024 20:25:10","02-11-2024 20:15:38","02-11-2024 20:30:10",=
"Cascaded Incident from TTO3374238","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site ,site on Grid =
with Ubaie=3D53.7 V The Tx Synphorien (675295205) From huawei is informed. =
Notice that we have disjunction at BTS OCM","system","572","02-11-2024 20:2=
5:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003476957","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","02-11-2024 20:23:45","0=
2-11-2024 20:15:38","02-11-2024 20:30:10","No power issue on site ,site on =
Grid with Ubaie=3D53.7 V The Tx Synphorien (675295205) From huawei is infor=
med. Notice that we have disjunction at BTS OCM","Siligap Boris","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site ,site on Grid with Ubaie=3D53.7 V The Tx Synphorie=
n (675295205) From huawei is informed. Notice that we have disjunction at B=
TS OCM","alexandre.kamal@ihstowers.com","488","02-11-2024 20:23:45","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003476418","C=
rf-Nsam","","02-11-2024 18:49:34","02-11-2024 18:44:27","02-11-2024 18:59:3=
7","Site went down because PWC overload // site stabilized","MINKA NICOLAS"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Si=
te went down because PWC overload // site stabilized","alexandre.kamal@ihst=
owers.com","308","02-11-2024 18:49:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003476364","C=
rf Cornier","","02-11-2024 18:33:43","02-11-2024 18:25:40","02-11-2024 18:3=
9:23","No power issue site on Grid with U=3D54.6V  Rm ALAIN//691144423 from=
 Huawei is informed.Site up at 06:39 PM","MINKA NICOLAS","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue site on Grid with U=3D54.6V  Rm ALAIN//691144423 from Huawei is in=
formed.Site up at 06:39 PM","alexandre.kamal@ihstowers.com","484","02-11-20=
24 18:33:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003476142","ELOUMDEM=
 CARRIERE 2","","02-11-2024 17:54:51","02-11-2024 15:59:02","02-11-2024 16:=
03:08","Cascaded Incident from TTO3373227","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation site went do=
wn because Gen failed to start du to Grid bad voltage // He bypassed Grid a=
nd started Gen","system","6949","02-11-2024 17:54:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003476141","Eto koss=
 Yde","","02-11-2024 17:54:50","02-11-2024 15:59:02","02-11-2024 16:03:08",=
"Cascaded Incident from TTO3373227","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation site went down beca=
use Gen failed to start du to Grid bad voltage // He bypassed Grid and star=
ted Gen","system","6948","02-11-2024 17:54:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003476136","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","02-11-2024 17:53:20","02-11-2024 15:59=
:02","02-11-2024 16:03:08","Grid fluctuation site went down because Gen fai=
led to start du to Grid bad voltage // He bypassed Grid and started Gen","F=
anda Brice","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation site went down because Gen failed to start du t=
o Grid bad voltage // He bypassed Grid and started Gen","kamga.virgile@ihst=
owers.com","6859","02-11-2024 17:53:20","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003476098","Lad=
a I Yde","","02-11-2024 17:50:23","02-11-2024 16:01:09","02-11-2024 16:05:0=
6","Site went down due to work: Technician Herve Mba/655999779/SAGEMCOM wor=
king on site ""PM""// End of work","Mba Lazare Herve","Installation Activit=
y","Passive","Planned Activity","Installation Activity","Site went down due=
 to work: Technician Herve Mba/655999779/SAGEMCOM working on site ""PM""// =
End of work","kamga.virgile@ihstowers.com","6666","02-11-2024 17:50:23","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0003475743","L=
eboudi","","02-11-2024 17:02:58","02-11-2024 16:55:53","02-11-2024 16:57:28=
","No power issue Ubaie=3D 54.3 V site on Gen  The TX FME Mohamadou /691144=
435/ from huawei is informed.","TIENTCHEU NZETCHIEU GAEL","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue Ubaie=3D 54.3 V site on Gen  The TX FME Mohamadou /691144435/ fro=
m huawei is informed.","alexandre.kamal@ihstowers.com","426","02-11-2024 17=
:02:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003475711","O=
lembe-Terminus","","02-11-2024 16:55:44","02-11-2024 16:46:40","02-11-2024 =
17:14:00","Site went down because 4/4 rectifiers disfunctionning// He reset=
 rectifiers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down because 4/4 rectifiers disfunctionning// He=
 reset rectifiers","alexandre.kamal@ihstowers.com","607","02-11-2024 16:55:=
44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003475571","Yoko OCM=
","","02-11-2024 16:42:01","02-11-2024 16:14:59","02-11-2024 16:15:59","Cas=
caded Incident from TTO3372514","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on Solar;=
 Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informe=
d.","system","1622","02-11-2024 16:42:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003475575","MBIMBIM"=
,"","02-11-2024 16:42:01","02-11-2024 16:14:59","02-11-2024 16:15:59","Casc=
aded Incident from TTO3372514","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on Solar; =
Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed=
.","system","1622","02-11-2024 16:42:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003475573","Ngouetou=
","","02-11-2024 16:42:01","02-11-2024 16:14:59","02-11-2024 16:15:59","Cas=
caded Incident from TTO3372514","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on Solar;=
 Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informe=
d.","system","1622","02-11-2024 16:42:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003475570","Matsari"=
,"","02-11-2024 16:42:00","02-11-2024 16:14:59","02-11-2024 16:15:59","Casc=
aded Incident from TTO3372514","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on Solar; =
Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed=
.","system","1621","02-11-2024 16:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003475569","Ngoum","=
","02-11-2024 16:42:00","02-11-2024 16:14:59","02-11-2024 16:15:59","Cascad=
ed Incident from TTO3372514","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on Solar; Ub=
aie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","1621","02-11-2024 16:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0003475288","Awae Ewo=
nkan","","02-11-2024 15:57:30","02-11-2024 15:36:41","02-11-2024 15:40:32",=
"Cascaded Incident from TTO3372238","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site ,site on Grid =
with Ubaie=3D54.9 V  The TX Georges/697461814// From Huawei is Informed","s=
ystem","1249","02-11-2024 15:57:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0003475289","Awae Esc=
alier","","02-11-2024 15:57:30","02-11-2024 15:36:41","02-11-2024 15:40:32"=
,"Cascaded Incident from TTO3372238","Albran Byorel","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site ,site on Grid=
 with Ubaie=3D54.9 V  The TX Georges/697461814// From Huawei is Informed","=
system","1249","02-11-2024 15:57:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0003475284","A=
wae-Yde","IHS_YND_535, IHS_YND_171","02-11-2024 15:56:45","02-11-2024 15:36=
:41","02-11-2024 15:40:32","No power issue on site ,site on Grid with Ubaie=
=3D54.9 V  The TX Georges/697461814// From Huawei is Informed","Albran Byor=
el","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site ,site on Grid with Ubaie=3D54.9 V  T=
he TX Georges/697461814// From Huawei is Informed","alexandre.kamal@ihstowe=
rs.com","1205","02-11-2024 15:56:45","Sagemcom CMR"
"Cancelled","Warning","CTR_168","IHS_YND_171","NOCINC0003475269","Awae Esca=
lier","","02-11-2024 15:52:51","","","","Albran Byorel","","","","","","ale=
xandre.kamal@ihstowers.com","908","02-11-2024 15:52:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003474878","N=
komkana","","02-11-2024 14:50:09","02-11-2024 14:17:03","02-11-2024 14:20:1=
5","No power issue on site Ubaie:54.6V;  site on Grid.  The Tx fme Brice Ts=
angue /650214096) from Huawei is informed.","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site Ubaie:54.6V;  site on Grid.  The Tx fme Martial(690087047) from Huaw=
ei is informed.","kamga.virgile@ihstowers.com","1987","02-11-2024 14:50:09"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003474830","N=
YOM 2 IHS","","02-11-2024 14:38:57","02-11-2024 14:14:45","02-11-2024 14:20=
:36"," No power issue, site is on Grid with Ubaie=3D54.5 V The Tx Fme Synph=
orien /650257151/ of huawei is informed.","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No=
 power issue, site is on Grid with Ubaie=3D54.5 V The Tx Fme Synphorien /65=
0257151/ of huawei is informed.","kamga.virgile@ihstowers.com","1453","02-1=
1-2024 14:38:57","Sagemcom CMR"
"Closed Complete","Site Down","T0815","IHS_YND_508","NOCINC0003474661","Crf=
-Nsam","","02-11-2024 14:05:24","02-11-2024 13:55:16","02-11-2024 15:16:13"=
,"Grid fluctuation, site went down due to lack on 01 phase on site //He mak=
e the bridge on good phase","MINKA NICOLAS","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","Grid fluctuation, site went down=
 due to lack on 01 phase on site //He make the bridge on good phase","landr=
y.etame@ihstowers.com","1231","02-11-2024 14:05:24","Sagemcom CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0003474484","Nko=
lfon Cimencam","","02-11-2024 13:36:51","02-11-2024 13:23:47","02-11-2024 1=
3:54:45","site went down due to work(Justin/657100524/, draining the gen) /=
/ End of work","Hyemafo Gildas","Equipment Replacement","Passive","Planned =
Activity","Planned Activity - Passive","site went down due to work(Justin/6=
57100524/, draining the gen) // End of work","landry.etame@ihstowers.com","=
1445","02-11-2024 13:36:51","Sagemcom CMR"
"Cancelled","Warning","CTR_374","IHS_YND_173","NOCINC0003474009","AWAE OCM"=
,"","02-11-2024 12:37:29","","","","Mba Lazare Herve","","","","","","steph=
ane.nkamwa@ihstowers.com","371","02-11-2024 12:37:29","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003473439","OBA=
M NGOLA OCM","","02-11-2024 11:59:06","02-11-2024 11:49:01","02-11-2024 12:=
07:55","Site wen down due to insufficient of rectifier(05)// Site stabilize=
d","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","Site wen down due to insufficient of rectifier(05)// Site stabilized",=
"landry.etame@ihstowers.com","606","02-11-2024 11:59:06","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0003472520","UPA=
C LP","","02-11-2024 11:00:59","02-11-2024 10:52:50","02-11-2024 11:10:17",=
"Active// No power Issue Site on Grid Ubai =3D55.2V, The FME  The TX FME Ar=
mand nguetsa(699949553) is informed","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue=
 Site on Grid Ubai =3D55.2V, The FME  The TX FME Armand nguetsa(699949553) =
is informed","landry.etame@ihstowers.com","491","02-11-2024 11:00:59","Sage=
mcom CMR"
"Closed Complete","Site Down","T0050","IHS_YND_039","NOCINC0003472507","Sia=
ntou Radio TV","","02-11-2024 11:00:08","02-11-2024 10:51:57","02-11-2024 1=
5:00:31","site went down due to work Technician  Ahanda/697487490/LEC CAMER=
OUN working on site ""Swapp equipment PWC""//End of work","","Installation =
Activity","Passive","Planned Activity","Installation Activity","site went d=
own due to work Technician  Ahanda/697487490/LEC CAMEROUN working on site "=
"Swapp equipment PWC""//End of work","landry.etame@ihstowers.com","492","02=
-11-2024 11:00:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003471331","A=
kak-Nkozoa-MTN-IHS","","02-11-2024 07:27:27","02-11-2024 07:07:08","02-11-2=
024 08:38:59","site went down because gen failed to start due to grid fluct=
uation // gen manually started","Fabrice Pouakam","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","site went down because gen=
 failed to start due to grid fluctuation // gen manually started","stephane=
.nkamwa@ihstowers.com","1220","02-11-2024 07:27:27","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003471198","MIM=
BOMAN LIBERTE","","02-11-2024 06:54:05","02-11-2024 06:46:55","02-11-2024 0=
7:22:05","Grid outage, main gen faulty // MDG of 15Kva has deployed","Mba L=
azare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faul=
ty","Grid outage, main gen faulty // MDG of 15Kva has deployed","landry.eta=
me@ihstowers.com","431","02-11-2024 06:54:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003471158","Yoko MTN=
","","02-11-2024 06:42:31","02-11-2024 06:02:55","02-11-2024 06:37:28","Cas=
caded Incident from TTO3367509","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because Gen stopped wit=
h alarm ""high temp""due to radiator pierced// He added water(2liters) and =
started Gen manualy","system","2376","02-11-2024 06:42:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003471157","Ngoum","=
","02-11-2024 06:42:31","02-11-2024 06:02:55","02-11-2024 06:37:28","Cascad=
ed Incident from TTO3367509","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Site went down because Gen stopped with a=
larm ""high temp""due to radiator pierced// He added water(2liters) and sta=
rted Gen manualy","system","2376","02-11-2024 06:42:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003471154","MBIMBIM"=
,"","02-11-2024 06:42:30","02-11-2024 06:02:55","02-11-2024 06:37:28","Casc=
aded Incident from TTO3367509","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because Gen stopped with=
 alarm ""high temp""due to radiator pierced// He added water(2liters) and s=
tarted Gen manualy","system","2375","02-11-2024 06:42:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003471155","Matsari"=
,"","02-11-2024 06:42:30","02-11-2024 06:02:55","02-11-2024 06:37:28","Casc=
aded Incident from TTO3367509","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because Gen stopped with=
 alarm ""high temp""due to radiator pierced// He added water(2liters) and s=
tarted Gen manualy","system","2375","02-11-2024 06:42:30","Sagemcom CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0003471143","Ngo=
uetou","IHS_YND_456, IHS_YND_460, IHS_MAR_402, IHS_YND_475, IHS_YND_473","0=
2-11-2024 06:39:01","02-11-2024 06:02:55","02-11-2024 06:37:56","Site went =
down because Gen stopped with alarm ""high temp""due to radiator pierced// =
He added water(2liters) and started Gen manualy","Parker Tchoup","Equipment=
 Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issu=
e","Site went down because Gen stopped with alarm ""high temp""due to radia=
tor pierced// He added water(2liters) and started Gen manualy","landry.etam=
e@ihstowers.com","2167","02-11-2024 06:39:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0003470638","N=
ew-Marche-Melen","","02-11-2024 03:32:41","02-11-2024 03:29:30","02-11-2024=
 04:50:30","Active// No power Issue Site on Grid Ubai =3D54,3V, The FME  Th=
e TX FME Mbah Hosiah (674007438) is informed","Paul BIBOUM","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive// No power Issue Site on Grid Ubai =3D54,3V, The FME  The TX FME Mbah H=
osiah (674007438) is informed","rouselle.schoune@ihstowers.com","192","02-1=
1-2024 03:32:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0003470430","L=
eboudi","","02-11-2024 02:07:21","02-11-2024 02:02:13","02-11-2024 03:10:13=
","No power issue on site U=3D54,3v site on gen mouhamadou of huawei is inf=
ormed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54=
,3v site on gen mouhamadou of huawei is informed","rouselle.schoune@ihstowe=
rs.com","309","02-11-2024 02:07:21","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0003469646","Nko=
l-Mbanda","","01-11-2024 22:26:17","01-11-2024 22:17:10","01-11-2024 22:29:=
10","Site went down due to 2 rectifiers faulty // he added 01 rectifier, si=
te on gen","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down due to 2 rectifiers faulty // he added 01 recti=
fier, site on gen","denis.mballa@ihstowers.com","548","01-11-2024 22:26:17"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003469420","M=
IMBOMAN LIBERTE","","01-11-2024 21:50:24","01-11-2024 21:38:18","02-11-2024=
 01:48:37","No power issue on site ,site on Grid with Ubaie=3D52,1 V The Tx=
 FME Eloundou(693212405) from Huawei is informed that: There was Disjuntion=
 in the side of OCM.","Mba Lazare Herve","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 ,site on Grid with Ubaie=3D52,1 V The Tx FME Eloundou(693212405) from Huaw=
ei is informed that: There was Disjuntion in the side of OCM.","ludivine.ng=
amaleu@ihstowers.com","727","01-11-2024 21:50:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003469214","C=
RH-Etoug-Ebe","","01-11-2024 21:20:39","01-11-2024 20:47:31","02-11-2024 01=
:13:20","Tx Issue : site on grid,Ubaie:52V; Mohamadou/691-14-44-35 is infor=
med,and confirmed that: There was Disjuntion in the side of OCM.","Hyemafo =
Gildas","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Tx Issue : site on grid,Ubaie:52V; Mohamadou/691-14-44-=
35 is informed,and confirmed that: There was Disjuntion in the side of OCM.=
","ludivine.ngamaleu@ihstowers.com","1989","01-11-2024 21:20:39","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003468870","M=
IMBOMAN LIBERTE","","01-11-2024 20:44:25","01-11-2024 20:31:19","01-11-2024=
 20:49:57","Grid outage, Site went down due Main Gen faulty//He connected M=
DG 20KVA","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG =
- Generator Faulty","Grid outage, Site went down due Main Gen faulty//He co=
nnected MDG 20KVA","ludivine.ngamaleu@ihstowers.com","787","01-11-2024 20:4=
4:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003468599","Melen Ba=
'aba","","01-11-2024 20:34:50","01-11-2024 20:22:13","01-11-2024 21:26:40",=
"Cascaded Incident from TTO3364502","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue on site, Site =
on Grid UBAIE=3D54V  synphorien (675295205) From huawei is informed. Notice=
 that we have disjunction at BTS OCM","system","757","01-11-2024 20:34:50",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003468600","TSINGA V=
ILLAGE 2","","01-11-2024 20:34:50","01-11-2024 20:22:13","01-11-2024 21:26:=
40","Cascaded Incident from TTO3364502","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active//No power issue on site, =
Site on Grid UBAIE=3D54V  synphorien (675295205) From huawei is informed. N=
otice that we have disjunction at BTS OCM","system","757","01-11-2024 20:34=
:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003468598","Nkolfoul=
ou 2","","01-11-2024 20:34:50","01-11-2024 20:22:13","01-11-2024 21:26:40",=
"Cascaded Incident from TTO3364502","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue on site, Site =
on Grid UBAIE=3D54V  synphorien (675295205) From huawei is informed. Notice=
 that we have disjunction at BTS OCM","system","757","01-11-2024 20:34:50",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003468579","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","01-11-2024 20:33:22","0=
1-11-2024 20:22:13","01-11-2024 21:26:40","Active//No power issue on site, =
Site on Grid UBAIE=3D54V  synphorien (675295205) From huawei is informed. N=
otice that we have disjunction at BTS OCM","Siligap Boris","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site, Site on Grid UBAIE=3D54V  synphorien (675295205=
) From huawei is informed. Notice that we have disjunction at BTS OCM","lud=
ivine.ngamaleu@ihstowers.com","670","01-11-2024 20:33:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003468280","MBIMBIM"=
,"","01-11-2024 20:02:41","01-11-2024 19:50:17","01-11-2024 20:17:48","Casc=
aded Incident from TTO3364140","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site went down because gen stopped due =
to radiator pierced//he added water in radiator","system","1223774","01-11-=
2024 20:02:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003468282","Yoko MTN=
","","01-11-2024 20:02:41","01-11-2024 19:50:17","01-11-2024 20:17:48","Cas=
caded Incident from TTO3364140","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because gen stopped due=
 to radiator pierced//he added water in radiator","system","1223774","01-11=
-2024 20:02:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003468281","Ngoum","=
","01-11-2024 20:02:41","01-11-2024 19:50:17","01-11-2024 20:17:48","Cascad=
ed Incident from TTO3364140","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because gen stopped due to=
 radiator pierced//he added water in radiator","system","1223775","01-11-20=
24 20:02:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003468239","N=
gouetou","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_473","01-11-2024 1=
9:58:29","01-11-2024 19:45:26","01-11-2024 20:17:48","site went down becaus=
e gen stopped with alarm high temp causing  by radiator pierced//he added w=
ater in radiator","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","=
ACDG - High Engine Temp - Coolant Level Issue","site went down because gen =
stopped with alarm high temp causing  by radiator pierced//he added water i=
n radiator","ludivine.ngamaleu@ihstowers.com","784","01-11-2024 19:58:29","=
Sagemcom CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0003468232","Mat=
sari","","01-11-2024 19:57:16","01-11-2024 19:50:17","01-11-2024 20:17:48",=
"tikect need to cascade at Ngouetou","Parker Tchoup","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because gen stoppe=
d with alarm high temp causing  by radiator pierced//he added water in radi=
ator","olivier.kwedi@ihstowers.com","1223775","01-11-2024 19:57:16","Sagemc=
om CMR"
"Closed Complete","Site Down","T0050","IHS_YND_039","NOCINC0003468134","Sia=
ntou Radio TV","","01-11-2024 19:39:35","01-11-2024 19:29:24","01-11-2024 1=
9:47:29","site went down due to work Team Ahanda/6 97 48 74 90/LED Cameroun=
,swapp the PWC//End of work","","Installation Activity","Passive","Planned =
Activity","Installation Activity","site went down due to work Team Ahanda/6=
 97 48 74 90/LED Cameroun,swapp the PWC//End of work","olivier.kwedi@ihstow=
ers.com","612","01-11-2024 19:39:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003467723","C=
amp-Sic-Tsinga","","01-11-2024 18:41:57","01-11-2024 18:05:53","01-11-2024 =
18:24:51","Grid outage, no space to deploy MDG// Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no s=
pace to deploy MDG// Grid return","ludivine.ngamaleu@ihstowers.com","2165",=
"01-11-2024 18:41:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003467549","M=
IMBOMAN LIBERTE","","01-11-2024 18:09:06","01-11-2024 18:01:02","01-11-2024=
 18:54:10","grid outage,site went down because main gen faulty//mobil gen 2=
0Kva deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","grid outage,site went down because main gen fault=
y//mobil gen 20Kva deployed","ludivine.ngamaleu@ihstowers.com","485","01-11=
-2024 18:09:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0003467101","N=
simalen OCM","","01-11-2024 17:04:23","01-11-2024 16:49:18","01-11-2024 17:=
58:43","site went down due to disjunction Cb(32A) in Pwc// he reamed Cb , s=
ite on grid","Albran Byorel","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Circuit Breaker Issue","site went down due to disjunction C=
b(32A) in Pwc// he reamed Cb , site on grid","ludivine.ngamaleu@ihstowers.c=
om","906","01-11-2024 17:04:23","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003466494","Lad=
a I Yde","","01-11-2024 15:58:50","01-11-2024 15:48:44","01-11-2024 19:07:5=
1","No power issue on site U=3D54,3v site on gen lionel steeve of huawei is=
 informed","Mba Lazare Herve","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,3v =
site on gen lionel steeve of huawei is informed","olivier.kwedi@ihstowers.c=
om","607","01-11-2024 15:58:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003466304","M=
essa-Carriere OCM","","01-11-2024 15:34:44","01-11-2024 15:19:41","01-11-20=
24 19:02:27","No power issue on site U=3D52,1v site on grid Mohamadou/69114=
4435 of huawei and Up at 03:50 PM","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D52,1v site on grid Mohamadou/691144435 of huawei and Up at 03:50 PM","lu=
divine.ngamaleu@ihstowers.com","904","01-11-2024 15:34:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0003466170","C=
NDH","","01-11-2024 15:16:42","01-11-2024 15:09:38","01-11-2024 15:15:53","=
Grid outage, site went down because gen fails to start due to Grid contacto=
r faulty // he bypassed Grid contactor, Site On Grid","Paul BIBOUM","Equipm=
ent Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, site we=
nt down because gen fails to start due to Grid contactor faulty // he bypas=
sed Grid contactor, Site On Grid","ludivine.ngamaleu@ihstowers.com","424","=
01-11-2024 15:16:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003466150","Messassi=
 okolo","","01-11-2024 15:13:10","01-11-2024 14:58:55","01-11-2024 15:13:49=
","Cascaded Incident from TTO3361557","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down because SS Bern=
ard Atangana/IHS working on site//End of work","system","1248525","01-11-20=
24 15:13:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0003466026","E=
MANA BILICK CITY","IHS_YND_279","01-11-2024 15:05:01","01-11-2024 14:58:55"=
,"01-11-2024 15:13:49","site went down because SS Bernard Atangana/IHS :cha=
nge of contactor Eneo//End of work","Fabrice Pouakam","Installation Activit=
y","Passive","Planned Activity","Installation Activity","site went down bec=
ause SS Bernard Atangana/IHS :change of contactor Eneo//End of work","ludiv=
ine.ngamaleu@ihstowers.com","367","01-11-2024 15:05:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003465990","N=
kolfon Cimencam","","01-11-2024 14:58:47","01-11-2024 14:57:43","01-11-2024=
 17:25:48","No power issue on site U=3D54,5v site on Gen The Rm Alain (6911=
44423) of huawei is informed repetitive issue","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site U=3D54,5v site on Gen The Rm Alain (691144423) of h=
uawei is informed repetitive issue","ludivine.ngamaleu@ihstowers.com","64",=
"01-11-2024 14:58:47","Sagemcom CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0003465880","NKO=
ABANG NKOLO 3","","01-11-2024 14:42:09","01-11-2024 14:17:00","01-11-2024 1=
6:29:59","Grid outage,Site went down due to gen overload(10KVA, 110A) // he=
 reduiced the load and started Gen manually","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Site went down =
due to gen overload(10KVA, 110A) // he reduiced the load and started Gen ma=
nually","olivier.kwedi@ihstowers.com","1510","01-11-2024 14:42:09","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_192","IHS_YND_405","NOCINC0003465835","S=
aa","","01-11-2024 14:33:51","01-11-2024 14:25:47","01-11-2024 15:38:42","N=
o power issue on site U=3D54v site on grid Gregoire of huawei is working on=
 site","Parker Tchoup","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v site on g=
rid Gregoire of huawei is working on site","ludivine.ngamaleu@ihstowers.com=
","484","01-11-2024 14:33:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_171","NOCINC0003465814","Awae Esc=
alier","","01-11-2024 14:30:11","01-11-2024 14:24:30","01-11-2024 16:44:14"=
,"Cascaded Incident from TTO3361286","Albran Byorel","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active//No power issue on Site and U=
baie=3D54,6V, Site is on Gen The FME TX Georges/697461814// From Huawei is =
Informed","system","341","01-11-2024 14:30:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0003465813","Awae Ewo=
nkan","","01-11-2024 14:30:10","01-11-2024 14:24:30","01-11-2024 16:44:14",=
"Cascaded Incident from TTO3361286","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue on Site and Ub=
aie=3D54,6V, Site is on Gen The FME TX Georges/697461814// From Huawei is I=
nformed","system","340","01-11-2024 14:30:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0003465800","A=
wae-Yde","IHS_YND_535, IHS_YND_171","01-11-2024 14:28:36","01-11-2024 14:24=
:30","01-11-2024 18:38:14","Active//No power issue on Site and Ubaie=3D54,6=
V, Site is on Gen The FME TX Georges/697461814// From Huawei is Informed","=
Albran Byorel","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active//No power issue on Site and Ubaie=3D54,6V=
, Site is on Gen The FME TX Georges/697461814// From Huawei is Informed","l=
udivine.ngamaleu@ihstowers.com","247","01-11-2024 14:28:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003465544","C=
rf-Nsam","","01-11-2024 13:50:39","01-11-2024 12:55:15","01-11-2024 13:05:2=
5","Active: no power issue, site is on grid with Ubaie=3D53V, Rm(691144423)=
 from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power issu=
e, site is on grid with Ubaie=3D53V, Rm(691144423) from Huawei is informed"=
,"stephane.nkamwa@ihstowers.com","3325","01-11-2024 13:50:39","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003465527","M=
imboman-Village","","01-11-2024 13:46:51","01-11-2024 12:47:36","01-11-2024=
 12:57:36","No power issue on site U=3D54v site on grid Lionel steeve of hu=
awei is informed","Mba Lazare Herve","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54v site on grid Lionel steeve of huawei is informed","stephane.nkamwa@i=
hstowers.com","3556","01-11-2024 13:46:51","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003464860","Mim=
boman4","","01-11-2024 12:32:08","01-11-2024 12:26:41","01-11-2024 13:08:36=
","grid outage,gen failed to start due to battery Ge discharged//grid retur=
n","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Turbo=
 Charger","grid outage,gen failed to start due to battery Ge discharged//gr=
id return","kamga.virgile@ihstowers.com","328","01-11-2024 12:32:08","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0003464806","Bastos B=
ethesda","","01-11-2024 12:24:31","01-11-2024 11:46:33","01-11-2024 12:39:0=
0","Cascaded Incident from TTO3360079","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down bec=
ause gen failed to start due to battery gen faulty // he changed battery ge=
n, site on gen","system","2278","01-11-2024 12:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0003464809","Tsinga",=
"","01-11-2024 12:24:31","01-11-2024 11:46:33","01-11-2024 12:39:00","Casca=
ded Incident from TTO3360079","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","grid outage, site went down because gen =
failed to start due to battery gen faulty // he changed battery gen, site o=
n gen","system","2278","01-11-2024 12:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_002","NOCINC0003464807","Yde-M-Ce=
ntral","","01-11-2024 12:24:31","01-11-2024 11:46:33","01-11-2024 12:39:00"=
,"Cascaded Incident from TTO3360079","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","grid outage, site went down because gen failed=
 to start due to battery gen faulty // he changed battery gen, site on gen"=
,"system","2278","01-11-2024 12:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_028","NOCINC0003464808","H-Centra=
l","","01-11-2024 12:24:31","01-11-2024 11:46:33","01-11-2024 12:39:00","Ca=
scaded Incident from TTO3360079","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","grid outage, site went down because gen=
 failed to start due to battery gen faulty // he changed battery gen, site =
on gen","system","2278","01-11-2024 12:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0003464805","Golf Qua=
ter","","01-11-2024 12:24:30","01-11-2024 11:46:33","01-11-2024 12:39:00","=
Cascaded Incident from TTO3360079","Mboua Thierry","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, site went down because=
 gen failed to start due to battery gen faulty // he changed battery gen, s=
ite on gen","system","2277","01-11-2024 12:24:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0003464789","C=
NDH","IHS_YND_220, IHS_YND_563, IHS_YND_002, IHS_YND_028, IHS_YND_127","01-=
11-2024 12:20:45","01-11-2024 11:46:33","01-11-2024 12:26:00","grid outage,=
 site went down because gen failed to start due to battery gen faulty // he=
 changed battery gen, site on gen","Paul BIBOUM","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Generator Battery","grid outage, site went down becau=
se gen failed to start due to battery gen faulty // he changed battery gen,=
 site on gen","stephane.nkamwa@ihstowers.com","2052","01-11-2024 12:20:45",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003464640","I=
mm-Olympique","","01-11-2024 11:56:39","01-11-2024 11:29:32","01-11-2024 13=
:07:29","grid outage, gen fails to start du to power cable stolen since//he=
 connected the gen with a power cable","Paul BIBOUM","Equipment Repair","Pa=
ssive","Infrastructure","Armoured Cable","grid outage, gen fails to start d=
u to power cable stolen since//he connected the gen with a power cable","st=
ephane.nkamwa@ihstowers.com","1628","01-11-2024 11:56:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0003464627","C=
NR","","01-11-2024 11:55:41","01-11-2024 10:54:15","01-11-2024 12:26:55","g=
rid outage,gen failed to start due to RCP faulty//he changed with Relais 22=
0V","Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","grid outage,gen failed to start due to RCP faulty//he ch=
anged with Relais 220V","stephane.nkamwa@ihstowers.com","3687","01-11-2024 =
11:55:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003464589","Essomba"=
,"","01-11-2024 11:53:21","01-11-2024 11:35:23","01-11-2024 11:45:35","Casc=
aded Incident from TTO3359809","Mba Lazare Herve","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active: No power issue, site is on grid=
 with Ubaie=3D53V, lionel adjed (655184876) from Huawei is informed","syste=
m","1078","01-11-2024 11:53:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003464588","Tradex-N=
komo","","01-11-2024 11:53:20","01-11-2024 11:35:23","01-11-2024 11:45:35",=
"Cascaded Incident from TTO3359809","Albran Byorel","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active: No power issue, site is on gr=
id with Ubaie=3D53V, lionel adjed (655184876) from Huawei is informed","sys=
tem","1077","01-11-2024 11:53:20","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003464586","Bas=
tos Amb Coree","","01-11-2024 11:53:16","01-11-2024 11:39:07","01-11-2024 1=
1:53:08","site went down due to insuffiency of retifiers // grid stabilized=
","","Equipment Repair","Passive","Rectifier","Rectifier Module","site went=
 down due to insuffiency of retifiers // grid stabilized","kamga.virgile@ih=
stowers.com","850","01-11-2024 11:53:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003464568","B=
iteng","IHS_YND_172, IHS_YND_179","01-11-2024 11:51:44","01-11-2024 11:35:2=
3","01-11-2024 11:45:35","Active: No power issue, site is on grid with Ubai=
e=3D53V, lionel adjed (655184876) from Huawei is informed","Mba Lazare Herv=
e","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active: No power issue, site is on grid with Ubaie=3D53V, li=
onel adjed (655184876) from Huawei is informed","stephane.nkamwa@ihstowers.=
com","982","01-11-2024 11:51:44","Sagemcom CMR"
"Closed Complete","Site Down","T0471","IHS_YND_009","NOCINC0003464056","CLE=
 Building","","01-11-2024 10:39:02","01-11-2024 10:28:58","01-11-2024 12:09=
:54","grid outage, no space for a MDG//grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","grid outage, no space for a=
 MDG//grid return","kamga.virgile@ihstowers.com","605","01-11-2024 10:39:02=
","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0003464020","MVA=
N SACEL","","01-11-2024 10:34:51","01-11-2024 10:26:41","01-11-2024 10:54:4=
7","Grid outage, site went down before gen start due to poor battery backup=
 // Grid restored","MINKA NICOLAS","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before gen =
start due to poor battery backup // Grid restored","kamga.virgile@ihstowers=
.com","491","01-11-2024 10:34:51","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0003464013","Obo=
bogo","","01-11-2024 10:33:18","01-11-2024 10:26:08","01-11-2024 10:34:57",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","kamga.=
virgile@ihstowers.com","431","01-11-2024 10:33:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0003463918","A=
nguissa New","","01-11-2024 10:12:29","01-11-2024 09:56:55","01-11-2024 10:=
10:37","","MINKA NICOLAS","Cascade Outage","Active","Cascade Active","Casca=
de Active","Active:No  power issue U =3D54,8V site on grid.FME Tx Georges (=
697461814)from Huawei is informed. Repetitif issue","stephane.nkamwa@ihstow=
ers.com","1409","01-11-2024 10:12:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003463905","L=
abogenie","IHS_YND_568","01-11-2024 10:10:12","01-11-2024 09:56:55","01-11-=
2024 13:00:51","Active:No  power issue U =3D54,8V site on grid.FME Tx Georg=
es (697461814)from Huawei is informed. Repetitif issue","","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve:No  power issue U =3D54,8V site on grid.FME Tx Georges (697461814)from H=
uawei is informed. Repetitif issue","stephane.nkamwa@ihstowers.com","798","=
01-11-2024 10:10:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003463650","Ngoum","=
","01-11-2024 09:38:50","01-11-2024 09:13:35","01-11-2024 09:49:28","Cascad=
ed Incident from TTO3358704","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","grid outage, site went down because gen f=
ailed start and stoppen due to oil pressure sensor faulty // He bypassed oi=
l pressure senso , grid return","system","1515","01-11-2024 09:38:50","Sage=
mcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0003463631","Yok=
o MTN","IHS_YND_475","01-11-2024 09:35:45","01-11-2024 09:13:35","01-11-202=
4 09:49:28","grid outage, site went down because gen failed start and stopp=
en due to oil pressure sensor faulty // He bypassed oil pressure senso , gr=
id return","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - =
Oil Pressure Sensor Faulty","grid outage, site went down because gen failed=
 start and stoppen due to oil pressure sensor faulty // He bypassed oil pre=
ssure senso , grid return","kamga.virgile@ihstowers.com","1331","01-11-2024=
 09:35:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003463255","Donga","=
","01-11-2024 08:23:11","01-11-2024 08:13:38","01-11-2024 09:50:07","Cascad=
ed Incident from TTO3358253 - Cascade Removed From TTO3358253","Parker Tcho=
up","Cascade Outage","Passive","Cascade Passive","Cascade Passive","grid ou=
tage, site went down because gen stoppen with alarm under voltage // he pur=
ged the fuel circuit and gen manually started","system","573","01-11-2024 0=
8:23:11","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0003463253","Ngu=
ila","IHS_YND_434, IHS_YND_444","01-11-2024 08:22:42","01-11-2024 08:13:38"=
,"01-11-2024 09:50:07","grid outage, site went down because gen stoppen wit=
h alarm under voltage // he purged the fuel circuit and gen manually starte=
d","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","grid outage, site went down because gen stoppen with alarm under vo=
ltage // he purged the fuel circuit and gen manually started","kamga.virgil=
e@ihstowers.com","545","01-11-2024 08:22:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0003463248","D=
ong","","01-11-2024 08:21:48","01-11-2024 08:13:38","01-11-2024 09:50:07","=
","Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","grid outage, site went down because gen stoppen with alarm under vol=
tage // he purged the fuel circuit and gen manually started","stephane.nkam=
wa@ihstowers.com","491","01-11-2024 08:21:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003462926","H=
-Progres","","01-11-2024 07:28:27","01-11-2024 07:15:22","01-11-2024 09:17:=
46","grid outage, no space to deploy a mobile gen// grid return ","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, =
no space to deploy a mobile gen// grid return ","stephane.nkamwa@ihstowers.=
com","786","01-11-2024 07:28:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003462658","C=
amp-Sic-Tsinga","","01-11-2024 06:42:37","01-11-2024 05:59:23","01-11-2024 =
12:26:48","Grid outage, no space to deploy a mobil gen // grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age, no space to deploy a mobil gen // grid return","stephane.nkamwa@ihstow=
ers.com","2595","01-11-2024 06:42:37","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003462506","NKO=
MEKUI OCM","","01-11-2024 05:56:20","01-11-2024 05:54:13","01-11-2024 06:02=
:07","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen start automa=
tically","emmanuel.ghani@ihstowers.com","128","01-11-2024 05:56:20","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003461492","O=
mnisport-Rail","","01-11-2024 01:10:36","01-11-2024 01:00:30","01-11-2024 0=
3:25:30","Active//No power issue, site is on Gen with Ubaie=3D55,1V, Armand=
 nguetsa(699949553) from Huawei is informed","Delor Telezing","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue, site is on Gen with Ubaie=3D55,1V, Armand nguetsa(69=
9949553) from Huawei is informed ","christian.fonkou@ihstowers.com","607","=
01-11-2024 01:10:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_369","IHS_YND_019","NOCINC0003461403","H=
otel de Ville Yde","","01-11-2024 00:44:50","01-11-2024 00:38:45","01-11-20=
24 03:38:47","Active//No power issue on site ,site on Grid wiith Ubaie=3D54=
.1 V The TX FME Brice Tsague/ 690286359/ Huawei is informed and Site UP AT=
=3D01:04 AM","Paul BIBOUM","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active//No power issue on site ,site=
 on Grid wiith Ubaie=3D54.1 V The TX FME Brice Tsague/ 690286359/ Huawei is=
 informed and Site UP AT=3D01:04 AM","christian.fonkou@ihstowers.com","366"=
,"01-11-2024 00:44:50","Sagemcom CMR"
"Closed Complete","Site Down","T1333","IHS_YND_174","NOCINC0003461402","Car=
refourt Nkomo","","01-11-2024 00:43:52","01-11-2024 00:40:27","01-11-2024 0=
1:11:30","Grid fluctuation, site went down because Gen Failed to  start due=
 to grid bad voltage and RCP on site // He bypass the Grid and Manually Sta=
rted  The Gen","Mba Lazare Herve","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","Grid fluctuation, site went down because G=
en Failed to  start due to grid bad voltage and RCP on site // He bypass th=
e Grid and Manually Started  The Gen","emmanuel.ghani@ihstowers.com","243",=
"01-11-2024 00:43:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003461203","N=
komkana","","31-10-2024 23:32:06","31-10-2024 23:25:56","01-11-2024 01:47:3=
5","Grid Outage No Space to deploy a MDG //Grid Restored","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space =
to deploy a MDG //Grid Restored","christian.fonkou@ihstowers.com","372","31=
-10-2024 23:32:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003460569","Nkolfoul=
ou 2","","31-10-2024 21:27:20","31-10-2024 20:27:57","31-10-2024 21:41:20",=
"Cascaded Incident from TTO3355068","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D54v site o=
n grid Rm Alain of huawei is informed disjunction of CB in BTS Ocm","system=
","3563","31-10-2024 21:27:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003460571","TSINGA V=
ILLAGE 2","","31-10-2024 21:27:20","31-10-2024 20:27:57","31-10-2024 21:41:=
20","Cascaded Incident from TTO3355068","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site U=3D54v s=
ite on grid Rm Alain of huawei is informed disjunction of CB in BTS Ocm","s=
ystem","3563","31-10-2024 21:27:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003460570","Melen Ba=
'aba","","31-10-2024 21:27:20","31-10-2024 20:27:57","31-10-2024 21:41:20",=
"Cascaded Incident from TTO3355068","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D54v site o=
n grid Rm Alain of huawei is informed disjunction of CB in BTS Ocm","system=
","3563","31-10-2024 21:27:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003460561","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","31-10-2024 21:26:06","3=
1-10-2024 20:27:57","31-10-2024 21:41:20","No power issue on site U=3D54v s=
ite on grid Rm Alain of huawei is informed disjunction of CB in BTS Ocm","S=
iligap Boris","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","No power issue on site U=3D54v site on grid Rm Al=
ain of huawei is informed disjunction of CB in BTS Ocm","rouselle.schoune@i=
hstowers.com","3490","31-10-2024 21:26:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003460550","N=
komkana","","31-10-2024 21:24:21","31-10-2024 19:19:15","31-10-2024 22:25:3=
2","Grid outage, No space to deploy a MDG // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No space=
 to deploy a MDG // Grid return","rouselle.schoune@ihstowers.com","7507","3=
1-10-2024 21:24:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0003460545","Odza II =
OCM","","31-10-2024 21:23:24","31-10-2024 19:41:32","31-10-2024 19:50:32","=
Cascaded Incident from TTO3355030","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power issue on site U=3D54,=
5V site on Grid The Rm Alain (691144423) of huawei is informed and notice t=
had disjunction in OCM Equipment ","system","6112","31-10-2024 21:23:24","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0003460527","O=
dza-PK10","IHS_YND_527","31-10-2024 21:22:41","31-10-2024 19:41:32","31-10-=
2024 19:50:32","Active//No power issue on site U=3D54,5V site on Grid The R=
m Alain (691144423) of huawei is informed and notice thad disjunction in OC=
M Equipment ","Albran Byorel","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site U=
=3D54,5V site on Grid The Rm Alain (691144423) of huawei is informed and no=
tice thad disjunction in OCM Equipment ","rouselle.schoune@ihstowers.com","=
6070","31-10-2024 21:22:41","Sagemcom CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0003460059","NKO=
NGKARAK","","31-10-2024 20:13:23","31-10-2024 20:04:10","31-10-2024 22:17:3=
3","Site went down due to pin rail burner in the ATS //he removed the Pin R=
ail and Replaced it to the Cable and Site is on  Gen ","TIENTCHEU NZETCHIEU=
 GAEL","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Site w=
ent down due to pin rail burner in the ATS //he removed the Pin Rail and Re=
placed it to the Cable and Site is on  Gen ","denis.mballa@ihstowers.com","=
553","31-10-2024 20:13:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003459531","M=
EFOU ASSI","","31-10-2024 18:50:14","31-10-2024 18:49:06","31-10-2024 18:53=
:04","Grid outage, Site went down due to poor batteries backup before Gen s=
tart //Gen started automatically","Fanda Brice","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n due to poor batteries backup before Gen start //Gen started automatically=
","rouselle.schoune@ihstowers.com","69","31-10-2024 18:50:14","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003458972","O=
lembe-Terminus","","31-10-2024 18:15:47","31-10-2024 18:07:36","31-10-2024 =
19:52:41","Site went down because all rectifier dysfunction // he reset the=
 rectifier, site on grid","Fabrice Pouakam","Equipment Repair","Passive","R=
ectifier","Rectifier Module","Site went down because all rectifier dysfunct=
ion // he reset the rectifier, site on grid","rouselle.schoune@ihstowers.co=
m","492","31-10-2024 18:15:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003458966","D=
amas","","31-10-2024 18:14:28","31-10-2024 17:53:22","31-10-2024 18:10:36",=
"Active// No power Issue Site on Grid Ubai =3D54,3V, The FME  The TX FME Mb=
ah Hosiah (674007438) is informed","MINKA NICOLAS","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No =
power Issue Site on Grid Ubai =3D54,3V, The FME  The TX FME Mbah Hosiah (67=
4007438) is informed","rouselle.schoune@ihstowers.com","1267","31-10-2024 1=
8:14:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003458325","T=
ongolo OCM","","31-10-2024 17:28:10","31-10-2024 17:26:02","31-10-2024 17:2=
8:02","Grid outage, Site went down due to poor batteries backup before Gen =
start //Gen started automatically","Delor Telezing","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down due to poor batteries backup before Gen start //Gen started automatic=
ally","rouselle.schoune@ihstowers.com","129","31-10-2024 17:28:10","Sagemco=
m CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003457933","N=
yanon","","31-10-2024 16:24:42","31-10-2024 16:18:36","31-10-2024 16:49:25"=
,"No power issue on site U=3D56,3v site on gen Gregoire of huawei is inform=
ed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D56,3v=
 site on gen Gregoire of huawei is informed","rouselle.schoune@ihstowers.co=
m","367","31-10-2024 16:24:42","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003457883","Aha=
la","","31-10-2024 16:18:36","31-10-2024 16:10:23","31-10-2024 16:18:08","G=
rid outage, site went down before gen start due to poor battery backup // G=
en started automatically","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen started automatically","den=
is.mballa@ihstowers.com","495","31-10-2024 16:18:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0003457819","E=
seka Town","","31-10-2024 16:08:04","31-10-2024 15:50:54","31-10-2024 16:50=
:42","site went down because CB 60A of gen disjuncted//he reamed the CB","K=
emeni Franklin","Equipment Repair","Passive","Control Panel","Power Cabinet=
 - Circuit Breaker Issue","site went down because CB 60A of gen disjuncted/=
/he reamed the CB","rouselle.schoune@ihstowers.com","1031","31-10-2024 16:0=
8:04","Sagemcom CMR"
"Cancelled","Warning","T1571","IHS_YND_535","NOCINC0003457790","Awae Ewonka=
n","","31-10-2024 16:03:15","","","","Albran Byorel","","","","","","denis.=
mballa@ihstowers.com","501","31-10-2024 16:03:15","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003457697","Bas=
tos Amb Coree","","31-10-2024 15:50:05","31-10-2024 15:49:51","31-10-2024 1=
8:00:51","grid outage,no space to deploy a mobil gen//grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,=
no space to deploy a mobil gen//grid return","denis.mballa@ihstowers.com","=
15","31-10-2024 15:50:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0003457638","M=
bankomo IHS","","31-10-2024 15:43:50","31-10-2024 15:40:44","31-10-2024 16:=
08:12","No power issue on site U=3D50v site on grid Team Gilbert/654266068/=
Huawei is working on site","Fanda Brice","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 U=3D50v site on grid Team Gilbert/654266068/Huawei is working on site","ro=
uselle.schoune@ihstowers.com","186","31-10-2024 15:43:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003457619","B=
arriere","","31-10-2024 15:40:10","31-10-2024 15:32:05","31-10-2024 15:58:1=
0","grid bad voltage,and gen failed to start ,no rcp//he bypassed grid and =
started the gen","Hyemafo Gildas","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","grid bad voltage,and gen failed to start ,=
no rcp//he bypassed grid and started the gen","rouselle.schoune@ihstowers.c=
om","485","31-10-2024 15:40:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003457498","N=
kolfon Cimencam","","31-10-2024 15:25:30","31-10-2024 15:24:23","31-10-2024=
 15:52:59","Active//No power issue on site U=3D54,5V site on Grid The Rm Al=
ain (691144423) of huawei is informed, Repetitive issue","Hyemafo Gildas","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site U=3D54,5V site on Grid The Rm Ala=
in (691144423) of huawei is informed, Repetitive issue","rouselle.schoune@i=
hstowers.com","68","31-10-2024 15:25:30","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003456416","NTU=
I TOWN","","31-10-2024 13:25:24","31-10-2024 13:22:18","31-10-2024 15:41:26=
","site went down because 2/3rectifiers disfunctionning//he changed 1/2 rec=
tifier:site on 3rectifiers","Parker Tchoup","Equipment Repair","Passive","R=
ectifier","Rectifier Module","site went down because 2/3rectifiers disfunct=
ionning//he changed 1/2 rectifier:site on 3rectifiers","olivier.kwedi@ihsto=
wers.com","187","31-10-2024 13:25:24","Sagemcom CMR"
"Closed Complete","Site Down","T0050","IHS_YND_039","NOCINC0003456409","Sia=
ntou Radio TV","","31-10-2024 13:23:49","31-10-2024 13:21:42","31-10-2024 1=
8:43:35","Gridd outage.no space to deploy mobile gen //.grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
d outage.no space to deploy mobile gen //.grid power return","olivier.kwedi=
@ihstowers.com","128","31-10-2024 13:23:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0003456190","Elig Edz=
oa","","31-10-2024 12:52:54","31-10-2024 12:13:30","31-10-2024 12:18:40","C=
ascaded Incident from TTO3349944","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went because the cb(125) which=
 supplies the MTN equipment has tripped // we added second departure, balan=
ced the loads and put on the cb","system","2364","31-10-2024 12:52:54","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0003456189","Charles-=
Atangana","","31-10-2024 12:52:54","31-10-2024 12:13:30","31-10-2024 12:18:=
40","Cascaded Incident from TTO3349944","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went because the cb(125) which supplie=
s the MTN equipment has tripped // we added second departure, balanced the =
loads and put on the cb","system","2364","31-10-2024 12:52:54","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0003456188","Hopital =
Central","","31-10-2024 12:52:53","31-10-2024 12:13:30","31-10-2024 12:18:4=
0","Cascaded Incident from TTO3349944","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Site went because the cb(125) which supplies=
 the MTN equipment has tripped // we added second departure, balanced the l=
oads and put on the cb","system","2363","31-10-2024 12:52:53","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0003456185","ELIg-Ess=
ono","","31-10-2024 12:52:53","31-10-2024 12:13:30","31-10-2024 12:18:40","=
Cascaded Incident from TTO3349944","Delor Telezing","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went because the cb(125) whic=
h supplies the MTN equipment has tripped // we added second departure, bala=
nced the loads and put on the cb","system","2363","31-10-2024 12:52:53","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_134","NOCINC0003456187","Vallee B=
astos MTN","","31-10-2024 12:52:53","31-10-2024 12:13:30","31-10-2024 12:18=
:40","Cascaded Incident from TTO3349944","Mboua Thierry","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went because the cb(125)=
 which supplies the MTN equipment has tripped // we added second departure,=
 balanced the loads and put on the cb","system","2363","31-10-2024 12:52:53=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_016","NOCINC0003456186","Maetur",=
"","31-10-2024 12:52:53","31-10-2024 12:13:30","31-10-2024 12:18:40","Casca=
ded Incident from TTO3349944","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went because the cb(125) which supp=
lies the MTN equipment has tripped // we added second departure, balanced t=
he loads and put on the cb","system","2363","31-10-2024 12:52:53","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0003456182","Sapeur",=
"","31-10-2024 12:52:52","31-10-2024 12:13:30","31-10-2024 12:18:40","Casca=
ded Incident from TTO3349944","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went because the cb(125) which supp=
lies the MTN equipment has tripped // we added second departure, balanced t=
he loads and put on the cb","system","2362","31-10-2024 12:52:52","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0003456183","Garbati =
building","","31-10-2024 12:52:52","31-10-2024 12:13:30","31-10-2024 12:18:=
40","Cascaded Incident from TTO3349944","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went because the cb(125)=
 which supplies the MTN equipment has tripped // we added second departure,=
 balanced the loads and put on the cb","system","2362","31-10-2024 12:52:52=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_731","NOCINC0003456181","UPAC LP"=
,"","31-10-2024 12:52:52","31-10-2024 12:13:30","31-10-2024 12:18:40","Casc=
aded Incident from TTO3349944","","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Site went because the cb(125) which supplies the MTN=
 equipment has tripped // we added second departure, balanced the loads and=
 put on the cb","system","2362","31-10-2024 12:52:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0003456180","HOPITAL =
DE LA CAISSE","","31-10-2024 12:52:52","31-10-2024 12:13:30","31-10-2024 12=
:18:40","Cascaded Incident from TTO3349944","Delor Telezing","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went because the cb(=
125) which supplies the MTN equipment has tripped // we added second depart=
ure, balanced the loads and put on the cb","system","2362","31-10-2024 12:5=
2:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0003456177","Mamch Bu=
ilding","","31-10-2024 12:52:51","31-10-2024 12:13:30","31-10-2024 12:18:40=
","Cascaded Incident from TTO3349944","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site went because the cb(125) wh=
ich supplies the MTN equipment has tripped // we added second departure, ba=
lanced the loads and put on the cb","system","2361","31-10-2024 12:52:51","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_091","NOCINC0003456178","Jouvence=
 2000","","31-10-2024 12:52:51","31-10-2024 12:13:30","31-10-2024 12:18:40"=
,"Cascaded Incident from TTO3349944","Delor Telezing","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Site went because the cb(125) wh=
ich supplies the MTN equipment has tripped // we added second departure, ba=
lanced the loads and put on the cb","system","2361","31-10-2024 12:52:51","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0003456179","POLYCLIN=
IQUE TSINGA","","31-10-2024 12:52:51","31-10-2024 12:13:30","31-10-2024 12:=
18:40","Cascaded Incident from TTO3349944","Mboua Thierry","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went because the cb(12=
5) which supplies the MTN equipment has tripped // we added second departur=
e, balanced the loads and put on the cb","system","2361","31-10-2024 12:52:=
51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0003456176","Bastos B=
ethesda","","31-10-2024 12:52:51","31-10-2024 12:13:30","31-10-2024 12:18:4=
0","Cascaded Incident from TTO3349944","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went because the cb(125) w=
hich supplies the MTN equipment has tripped // we added second departure, b=
alanced the loads and put on the cb","system","2361","31-10-2024 12:52:51",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_084","NOCINC0003456175","Briquett=
erie","","31-10-2024 12:52:50","31-10-2024 12:13:30","31-10-2024 12:18:40",=
"Cascaded Incident from TTO3349944","","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","Site went because the cb(125) which supplies th=
e MTN equipment has tripped // we added second departure, balanced the load=
s and put on the cb","system","2360","31-10-2024 12:52:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0003456174","H-Franco=
 New","","31-10-2024 12:52:50","31-10-2024 12:13:30","31-10-2024 12:18:40",=
"Cascaded Incident from TTO3349944","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went because the cb(125) whi=
ch supplies the MTN equipment has tripped // we added second departure, bal=
anced the loads and put on the cb","system","2360","31-10-2024 12:52:50","S=
agemcom CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0003456141","Hot=
el de Ville Yde","IHS_YND_711, IHS_YND_084, IHS_YND_563, IHS_YND_051, IHS_Y=
ND_091, IHS_YND_049, IHS_YND_086, IHS_YND_064, IHS_YND_731, IHS_YND_029, IH=
S_YND_024, IHS_YND_014, IHS_YND_016, IHS_YND_134, IHS_YND_027, IHS_YND_125,=
 IHS_YND_504","31-10-2024 12:48:40","31-10-2024 13:06:30","31-10-2024 14:43=
:40","Site went because the cb(125) which supplies the MTN equipment has tr=
ipped // we added second departure, balanced the loads and put on the cb","=
Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet - =
Circuit Breaker Issue","Site went because the cb(125) which supplies the MT=
N equipment has tripped // we added second departure, balanced the loads an=
d put on the cb","olivier.kwedi@ihstowers.com","13285","31-10-2024 12:48:40=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0003455982","Jean Ves=
pa 2","","31-10-2024 12:28:31","31-10-2024 12:20:34","31-10-2024 12:46:42",=
"Cascaded Incident from TTO3349732","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work(install=
ation of new breaker which powered OCM equipements) done by Thierry MBOUA(6=
57108452) and Tx Eric Bodo (696422966) //End of work ","system","477","31-1=
0-2024 12:28:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003455963","J=
-Vespa","IHS_YND_544","31-10-2024 12:27:40","31-10-2024 12:20:34","31-10-20=
24 12:46:42","Site went down due to work(installation of new breaker which =
powered OCM equipements) done by Thierry MBOUA(657108452) and Tx Eric Bodo =
(696422966) //End of work ","Mboua Thierry","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to work(i=
nstallation of new breaker which powered OCM equipements) done by Thierry M=
BOUA(657108452) and Tx Eric Bodo (696422966) //End of work ","ludivine.ngam=
aleu@ihstowers.com","427","31-10-2024 12:27:40","Sagemcom CMR"
"Closed Complete","Site Down","T0498","IHS_YND_049","NOCINC0003455937","Eto=
a-Meki","","31-10-2024 12:24:17","31-10-2024 12:13:30","31-10-2024 12:18:40=
","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Site went because the cb(125) which supplies the MTN equipment h=
as tripped // we added second departure, balanced the loads and put on the =
cb","olivier.kwedi@ihstowers.com","4020","31-10-2024 12:24:17","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003455876","M=
VAN SACEL","","31-10-2024 12:13:17","31-10-2024 12:04:14","31-10-2024 12:31=
:13","Grid outage, site went down before gen start due to poor battery back=
up // Grid restored","MINKA NICOLAS","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before ge=
n start due to poor battery backup // Grid restored","ludivine.ngamaleu@ihs=
towers.com","545","31-10-2024 12:13:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003455763","ELOUMDEM=
 CARRIERE","","31-10-2024 12:01:00","31-10-2024 11:52:58","31-10-2024 12:01=
:41","Cascaded Incident from TTO3349485","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Grid restored","system","482","=
31-10-2024 12:01:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003455764","MBALNGON=
G LYCEE","","31-10-2024 12:01:00","31-10-2024 11:52:58","31-10-2024 12:01:4=
1","Cascaded Incident from TTO3349485","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid restored","system","482","31=
-10-2024 12:01:00","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003455746","Aha=
la","IHS_YND_767, IHS_YND_765","31-10-2024 11:59:07","31-10-2024 11:52:58",=
"31-10-2024 12:01:41","Grid outage, site went down before gen start due to =
poor battery backup // Grid restored","Hyemafo Gildas","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup // Grid restored","oli=
vier.kwedi@ihstowers.com","370","31-10-2024 11:59:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0003455559","M=
vog Mbi New","","31-10-2024 11:31:08","31-10-2024 11:21:59","31-10-2024 12:=
14:48","site went down because disjunction cb(125A) in PWC  due to load// H=
e reamed Cb(125A); site on grid","MINKA NICOLAS","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Circuit Breaker Issue","site went down =
because disjunction cb(125A) in PWC  due to load// He reamed Cb(125A); site=
 on grid","ludivine.ngamaleu@ihstowers.com","550","31-10-2024 11:31:08","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0003455551","Bar=
riere IHS","","31-10-2024 11:29:34","31-10-2024 11:20:28","31-10-2024 12:32=
:34","Grid outage, Site went down because Gen started and stopped with alar=
m overvoltage// He reset Gen card and started Gen manualy","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e, Site went down because Gen started and stopped with alarm overvoltage// =
He reset Gen card and started Gen manualy","olivier.kwedi@ihstowers.com","5=
47","31-10-2024 11:29:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003455505","N=
GONA","","31-10-2024 11:23:15","31-10-2024 11:18:11","31-10-2024 11:32:34",=
"Active: no power issue, site is on grid with Ubaie=3D54V, Lionel Adjep (65=
5184876) from Huawei is informed, site up at 11:32 am","Mba Lazare Herve","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active: no power issue, site is on grid with Ubaie=3D54V, Lionel=
 Adjep (655184876) from Huawei is informed, site up at 11:32 am","ludivine.=
ngamaleu@ihstowers.com","305","31-10-2024 11:23:15","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003455371","NKO=
MEKUI OCM","","31-10-2024 11:04:21","31-10-2024 10:54:09","31-10-2024 11:04=
:09","Grid outage, site went down before gen start due to poor battery back=
up // Gen started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen started","olivier.kwedi@=
ihstowers.com","614","31-10-2024 11:04:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0003455036","N=
goum","","31-10-2024 10:12:05","31-10-2024 10:01:59","31-10-2024 10:11:40",=
"No power issue site on Solar with U=3D51V,  tx fme Gregoire (654547479) fr=
om Huawei informed","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on Sola=
r with U=3D51V,  tx fme Gregoire (654547479) from Huawei informed","ludivin=
e.ngamaleu@ihstowers.com","607","31-10-2024 10:12:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003454950","H=
-General-Yde","","31-10-2024 09:58:11","31-10-2024 09:54:07","31-10-2024 10=
:32:42","grid outage, site went down because gen failed to start due to Ala=
rm ""under frequency"" // He reset gen card, gen manually started","Siligap=
 Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","gri=
d outage, site went down because gen failed to start due to Alarm ""under f=
requency"" // He reset gen card, gen manually started","ludivine.ngamaleu@i=
hstowers.com","245","31-10-2024 09:58:11","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003454847","San=
ta Barbara Gottam","","31-10-2024 09:46:31","31-10-2024 09:31:22","31-10-20=
24 10:15:01","Site went down due to PWC dysfonctioning ( Batteries Backup  =
alarming ; PWC FNS)//Reset Batteries Backup,site on Grid.","Delor Telezing"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"Site went down due to PWC dysfonctioning ( Batteries Backup  alarming ; P=
WC FNS)//Reset Batteries Backup,site on Grid.","olivier.kwedi@ihstowers.com=
","910","31-10-2024 09:46:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0003454833","Abang","=
","31-10-2024 09:45:10","31-10-2024 09:33:53","31-10-2024 10:32:08","Cascad=
ed Incident from TTO3348368","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage, site went down because ge=
n start and stoppen with alarm ""low oil pressure // He reset gen card and =
gen manually started","system","677","31-10-2024 09:45:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0003454807","N=
kolangaa","IHS_YND_290","31-10-2024 09:42:01","31-10-2024 09:31:43","31-10-=
2024 10:32:21","grid outage, site went down because gen start and stoppen w=
ith alarm ""low oil pressure // He reset gen card and gen manually started"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","grid outage, site went down because gen start and stoppen with ala=
rm ""low oil pressure // He reset gen card and gen manually started","ludiv=
ine.ngamaleu@ihstowers.com","850","31-10-2024 09:42:01","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003454628","NYO=
M FACE MAETUR","","31-10-2024 09:24:37","31-10-2024 09:16:19","31-10-2024 0=
9:27:21","Grid outage, Landlord has forbidden to start the generator due to=
 noise // Grid restored","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Emergency Stop","Grid outage, Landlord has forbidden to sta=
rt the generator due to noise // Grid restored","olivier.kwedi@ihstowers.co=
m","499","31-10-2024 09:24:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003454557","D=
amas","","31-10-2024 09:13:19","31-10-2024 09:06:14","31-10-2024 11:01:14",=
"Active: no power issue, site is on grid with Ubaie=3D53V, Hosiah(674007438=
) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power iss=
ue, site is on grid with Ubaie=3D53V, Hosiah(674007438) from Huawei is info=
rmed","ludivine.ngamaleu@ihstowers.com","425","31-10-2024 09:13:19","Sagemc=
om CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003454452","NYO=
M 2 IHS","","31-10-2024 09:04:56","31-10-2024 08:59:49","31-10-2024 09:25:4=
4","Grid outage.gen failed to start due to card GE dysfunctionnning//we res=
et card GE and gen manually started ","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to star=
t due to card GE dysfunctionnning//we reset card GE and gen manually starte=
d ","olivier.kwedi@ihstowers.com","573","31-10-2024 09:04:56","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003454348","N=
kolfon Cimencam","","31-10-2024 08:45:45","31-10-2024 08:39:40","31-10-2024=
 13:18:56","No power issue on site U=3D54,5v site on Gen The Rm Alain (6911=
44423) of huawei is informed","Hyemafo Gildas","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D54,5v site on Gen The Rm Alain (691144423) of huawei is informed=
","ludivine.ngamaleu@ihstowers.com","366","31-10-2024 08:45:45","Sagemcom C=
MR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003454330","Mes=
sa Carriere","","31-10-2024 08:41:04","31-10-2024 08:28:40","31-10-2024 13:=
11:08","No power issue on site U=3D54,8v site on grid Mohamadou/691144435 o=
f huawei working on site","Mboua Thierry","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54,8v site on grid Mohamadou/691144435 of huawei working on site","ol=
ivier.kwedi@ihstowers.com","745","31-10-2024 08:41:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0003454266","B=
otmakak","IHS_EDA_101","31-10-2024 08:27:36","31-10-2024 08:18:32","31-10-2=
024 13:25:12","no power issue U=3D53,8V site on Gen. the TX FME Etienne/ 69=
5033981/ from huawei is informed","Kemeni Franklin","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power is=
sue U=3D53,8V site on Gen. the TX FME Etienne/ 695033981/ from huawei is in=
formed","ludivine.ngamaleu@ihstowers.com","544","31-10-2024 08:27:36","Sage=
mcom CMR"
"Closed Complete","Site Down","T1590","IHS_YND_141","NOCINC0003454013","New=
-Marche-Melen","","31-10-2024 07:50:26","31-10-2024 07:42:18","31-10-2024 1=
0:26:17","No power issue on site U=3D53,3v site on grid Mohamadou/691144435=
 of huawei is informed","Paul BIBOUM","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53,3v site on grid Mohamadou/691144435 of huawei is informed","olivier.k=
wedi@ihstowers.com","488","31-10-2024 07:50:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003453915","A=
ngongo","","31-10-2024 07:33:14","31-10-2024 07:30:10","31-10-2024 07:33:15=
","Grid outage site went down because Hybrid system malfunctionning // he r=
eset the hybrid system and Gen manually started","Fanda Brice","Equipment R=
epair","Passive","Hybrid","Hybrid Module","Grid outage site went down becau=
se Hybrid system malfunctionning // he reset the hybrid system and Gen manu=
ally started","ludivine.ngamaleu@ihstowers.com","185","31-10-2024 07:33:14"=
,"Sagemcom CMR"
"Closed Complete","Warning","T0532","IHS_YND_239","NOCINC0003453814","Mendo=
ng2","","31-10-2024 07:20:02","","","Site alarming because gen failed to st=
art due to unknown alarm//we reset card GE and gen manually started ","Hyem=
afo Gildas","Warning","Warning","POWER","Warning - AC Failure","Site alarmi=
ng because gen failed to start due to unknown alarm//we reset card GE and g=
en manually started ","olivier.kwedi@ihstowers.com","433","31-10-2024 07:20=
:02","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003453615","Jea=
n Vespa","IHS_YND_574","31-10-2024 06:40:33","31-10-2024 06:14:25","31-10-2=
024 06:34:47","Grid outage,DG started and stopped with alarm 'overcurrent' =
due to //  he reset gen card and manually started","Mboua Thierry","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,DG star=
ted and stopped with alarm 'overcurrent' due to //  he reset gen card and m=
anually started","olivier.kwedi@ihstowers.com","1568","31-10-2024 06:40:33"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003453610","Messassi=
 okolo","","31-10-2024 06:38:30","31-10-2024 06:36:40","31-10-2024 06:56:12=
","Cascaded Incident from TTO3347004","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage.gen failed to star=
t due to card GE dysfunctioning//we reset card GE and gen manually started =
","system","110","31-10-2024 06:38:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0003453609","E=
MANA BILICK CITY","IHS_YND_279","31-10-2024 06:37:43","31-10-2024 06:34:59"=
,"31-10-2024 06:57:40","Grid outage, site went down because Gen failed to s=
tart due to contactor Grid faulty//He bypassed Grid contactor and started G=
en manualy","Fabrice Pouakam","Equipment Repair","Passive","Control Panel",=
"ATS-AMF Issue","Grid outage, site went down because Gen failed to start du=
e to contactor Grid faulty//He bypassed Grid contactor and started Gen manu=
aly","ludivine.ngamaleu@ihstowers.com","797","31-10-2024 06:37:43","Sagemco=
m CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0003453601","Crf=
-Mbankolo-IHS","","31-10-2024 06:34:14","31-10-2024 06:14:25","31-10-2024 0=
6:34:47","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","Grid outage,DG started and stopped with alarm 'overcurrent=
' due to //  he reset gen card and manually started","olivier.kwedi@ihstowe=
rs.com","1608","31-10-2024 06:34:14","Sagemcom CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0003453597","Saa=
","","31-10-2024 06:32:57","31-10-2024 05:58:44","31-10-2024 07:20:28","Gri=
d Outage, site went down because Gen stopped with ""high temp"" alarm// He =
added water and started Gen manualy","Parker Tchoup","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid Out=
age, site went down because Gen stopped with ""high temp"" alarm// He added=
 water and started Gen manualy","olivier.kwedi@ihstowers.com","2054","31-10=
-2024 06:32:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003453594","J=
-Vespa","","31-10-2024 06:32:16","31-10-2024 06:14:12","31-10-2024 06:24:48=
","grid outage ,Overload , site mutualised with J-vespa 2 // grid return","=
Mboua Thierry","Grid Supply","Passive","Grid","National Grid - Grid Outage =
Issue","grid outage // grid return","ludivine.ngamaleu@ihstowers.com","1085=
","31-10-2024 06:32:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003453436","M=
aison-Blanche-IHS","","31-10-2024 06:02:34","31-10-2024 05:47:19","31-10-20=
24 07:10:18","Grid outage, no space to deploy a mobile gen // grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage, no space to deploy a mobile gen // grid return","kouoh.jean@ihstow=
ers.com","916","31-10-2024 06:02:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003453116","MVAN SAC=
EL","","31-10-2024 04:18:50","30-10-2024 21:30:47","31-10-2024 03:41:57","C=
ascaded Incident from TTO3346425","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage and Gen overload site we=
nt down because  Grid bad voltage // Grid stabilized","system","24483","31-=
10-2024 04:18:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003453115","M=
VAN","IHS_YND_510","31-10-2024 04:18:15","30-10-2024 21:30:47","31-10-2024 =
03:41:57","Grid outage and Gen overload site went down because  Grid bad vo=
ltage // Grid stabilized","MINKA NICOLAS","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Grid outage and Gen overload site went down becau=
se  Grid bad voltage // Grid stabilized","kouoh.jean@ihstowers.com","24449"=
,"31-10-2024 04:18:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0003452751","C=
RF Nkoabang","","31-10-2024 01:59:44","31-10-2024 01:47:26","31-10-2024 07:=
38:47","Grid outage, no space to deploy a mobile gen// Grid return","Mba La=
zare Herve","Grid Supply","Passive","Grid","National Grid - Grid Outage Iss=
ue","sunset ,Grid outage, no space to deploy a mobile gen// Grid return","k=
ouoh.jean@ihstowers.com","738","31-10-2024 01:59:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003452569","L=
abogenie","","31-10-2024 01:22:04","31-10-2024 01:00:50","31-10-2024 01:10:=
57","No  power issue U =3D54,8V site on grid.FME Tx Georges (697461814)from=
 Huawei is informed. Repetitif issue","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No  power issue U =3D5=
4,8V site on grid.FME Tx Georges (697461814)from Huawei is informed. Repeti=
tif issue","kouoh.jean@ihstowers.com","1275","31-10-2024 01:22:04","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003452513","ELOUMDEM=
 CARRIERE 2","","31-10-2024 00:59:51","31-10-2024 00:39:39","31-10-2024 01:=
12:02","Cascaded Incident from TTO3345741","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down be=
cause Gen started and stopped // Grid power return (Investigation ongoing)"=
,"system","1212","31-10-2024 00:59:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003452512","Eto koss=
 Yde","","31-10-2024 00:59:50","31-10-2024 00:39:39","31-10-2024 01:12:02",=
"Cascaded Incident from TTO3345741","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en started and stopped // Grid power return (Investigation ongoing)","syste=
m","1211","31-10-2024 00:59:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003452510","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","31-10-2024 00:58:49","31-10-2024 00:39=
:39","31-10-2024 01:17:30","Grid outage site went down because Gen started =
and stopped // Grid power return (Investigation ongoing)","Fanda Brice","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage si=
te went down because Gen started and stopped // Grid power return (Investig=
ation ongoing)","landry.etame@ihstowers.com","1151","31-10-2024 00:58:49","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003452160","N=
kolfon Cimencam","","30-10-2024 23:34:42","30-10-2024 23:31:30","30-10-2024=
 23:45:58","No power issue on site U=3D54,5v site on Gen The Rm Alain (6911=
44423) of huawei is informed. Repetitive Issue","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site U=3D54,5v site on Gen The Rm Alain (691144423) of =
huawei is informed. Repetitive Issue","kouoh.jean@ihstowers.com","193","30-=
10-2024 23:34:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003452001","MVAN SAC=
EL","","30-10-2024 23:13:00","30-10-2024 17:59:45","30-10-2024 21:21:45","C=
ascaded Incident from TTO3345134","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," Gen overload site went down due to =
Grid bad voltage and absence of a one phase //  we cut ocm and bring up mtn=
, site on Grid","system","27600","30-10-2024 23:13:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003451996","M=
VAN","IHS_YND_510","30-10-2024 23:12:06","30-10-2024 17:56:32","30-10-2024 =
21:21:45","","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload"," Gen overload site went down due to Grid bad voltage and absen=
ce of a one phase //  we cut ocm and bring up mtn, site on Grid","kouoh.jea=
n@ihstowers.com","27735","30-10-2024 23:12:06","Sagemcom CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0003451894","Sof=
avinc","","30-10-2024 22:52:28","30-10-2024 22:43:23","31-10-2024 01:06:55"=
,"Access issue due to Landlord, Site went down because 4/9 rectifiers disfu=
nctionning// Site stabilized","MINKA NICOLAS","Access Denial","Lease Or Leg=
al","Landlord Related Issues","Access Issue - Land Lord","Access issue due =
to Landlord, Site went down because 4/9 rectifiers disfunctionning// Site s=
tabilized","landry.etame@ihstowers.com","546","30-10-2024 22:52:28","Sagemc=
om CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0003451862","NKO=
ABANG NKOLO 3","","30-10-2024 22:48:28","30-10-2024 22:42:21","30-10-2024 2=
3:16:03","Grid fluctuation site went down because Gen started and stopped d=
ue to Grid bad voltage and RCP on site // He bypass the Grid  site on Gen",=
"Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation site went down because Gen started and s=
topped due to Grid bad voltage and RCP on site // He bypass the Grid  site =
on Gen","landry.etame@ihstowers.com","367","30-10-2024 22:48:28","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003451770","Messassi=
 okolo","","30-10-2024 22:30:11","30-10-2024 22:16:59","30-10-2024 23:02:46=
","Cascaded Incident from TTO3344842","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, site went down be=
cause gen fails to start due to ATS disfunctionning // Gen manually start",=
"system","792","30-10-2024 22:30:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0003451759","E=
MANA BILICK CITY","IHS_YND_279","30-10-2024 22:27:04","30-10-2024 22:15:59"=
,"30-10-2024 23:02:46","grid outage, site went down because gen fails to st=
art due to ATS disfunctionning // Gen manually start","Fabrice Pouakam","Eq=
uipment Repair","Passive","Control Panel","ATS-AMF Issue","grid outage, sit=
e went down because gen fails to start due to ATS disfunctionning // Gen ma=
nually start","kouoh.jean@ihstowers.com","900","30-10-2024 22:27:04","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003451387","ELOUMDEM=
 CARRIERE 2","","30-10-2024 21:30:21","30-10-2024 21:26:40","30-10-2024 21:=
51:46","Cascaded Incident from TTO3344382","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation site went do=
wn because Gen failed to start du to Grid bad voltage // He bypassed Grid a=
nd started Gen","system","220","30-10-2024 21:30:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003451386","Eto koss=
 Yde","","30-10-2024 21:30:20","30-10-2024 21:26:40","30-10-2024 21:51:46",=
"Cascaded Incident from TTO3344382","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation site went down beca=
use Gen failed to start du to Grid bad voltage // He bypassed Grid and star=
ted Gen","system","220","30-10-2024 21:30:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003451363","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","30-10-2024 21:28:45","30-10-2024 21:26=
:40","30-10-2024 21:53:46","Grid fluctuation site went down because Gen fai=
led to start du to Grid bad voltage // He bypassed Grid and started Gen","F=
anda Brice","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation site went down because Gen failed to start du t=
o Grid bad voltage // He bypassed Grid and started Gen","emmanuel.ghani@ihs=
towers.com","126","30-10-2024 21:28:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003451172","M=
ontee-Des-Soeurs","","30-10-2024 21:04:16","30-10-2024 20:57:02","30-10-202=
4 20:59:28","Active//No power issue on site UBAIE=3D54.6 V The FME  The TX =
FME Mbah Hosiah (674007438) is informed. Repetitif issue","Hyemafo Gildas",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active//No power issue on site UBAIE=3D54.6 V The FME  The TX F=
ME Mbah Hosiah (674007438) is informed. Repetitif issue","denis.mballa@ihst=
owers.com","436","30-10-2024 21:04:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003451094","TSINGA V=
ILLAGE 2","","30-10-2024 20:56:31","30-10-2024 20:51:42","30-10-2024 20:55:=
07","Cascaded Incident from TTO3344038","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue site on grid with=
 U=3D54.2v Notice that we have dysjunction at OCM Equipements .Symphorien f=
rom Huawei is informed","system","289","30-10-2024 20:56:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003451092","Nkolfoul=
ou 2","","30-10-2024 20:56:31","30-10-2024 20:51:42","30-10-2024 20:55:07",=
"Cascaded Incident from TTO3344038","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
54.2v Notice that we have dysjunction at OCM Equipements .Symphorien from H=
uawei is informed","system","289","30-10-2024 20:56:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003451093","Melen Ba=
'aba","","30-10-2024 20:56:31","30-10-2024 20:51:42","30-10-2024 20:55:07",=
"Cascaded Incident from TTO3344038","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
54.2v Notice that we have dysjunction at OCM Equipements .Symphorien from H=
uawei is informed","system","289","30-10-2024 20:56:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003451067","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","30-10-2024 20:54:53","3=
0-10-2024 20:51:42","30-10-2024 21:55:07","No power issue site on grid with=
 U=3D54.2v Notice that we have dysjunction at OCM Equipements .Symphorien f=
rom Huawei is informed","Siligap Boris","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D54.2v Notice that we have dysjunction at OCM Equipements .Sym=
phorien from Huawei is informed","denis.mballa@ihstowers.com","192","30-10-=
2024 20:54:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003451053","F=
ebe Village","","30-10-2024 20:52:43","30-10-2024 20:50:22","30-10-2024 20:=
55:22","Grid outage, site went down before gen start due to poor battery ba=
ckup // gen started automatically","Mboua Thierry","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // gen started automatical=
ly","denis.mballa@ihstowers.com","142","30-10-2024 20:52:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003451052","Afanoya"=
,"","30-10-2024 20:52:41","30-10-2024 19:47:07","30-10-2024 20:33:53","Casc=
aded Incident from TTO3343972","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site was on gen due to grid outage,sit=
e went down due to gen overload (20Kva, 300A) and poor backup //  Grid powe=
r return","system","3934","30-10-2024 20:52:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003451051","MBALNGON=
G LYCEE","","30-10-2024 20:52:40","30-10-2024 19:47:07","30-10-2024 20:33:5=
3","Cascaded Incident from TTO3343972","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site was on gen due to grid outag=
e,site went down due to gen overload (20Kva, 300A) and poor backup //  Grid=
 power return","system","3933","30-10-2024 20:52:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003451050","ELOUMDEM=
 CARRIERE","","30-10-2024 20:52:40","30-10-2024 19:47:07","30-10-2024 20:33=
:53","Cascaded Incident from TTO3343972","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site was on gen due to grid out=
age,site went down due to gen overload (20Kva, 300A) and poor backup //  Gr=
id power return","system","3933","30-10-2024 20:52:40","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003451015","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","30-10-2024 20:49:13","30-10-20=
24 19:47:07","30-10-2024 20:33:53","site was on gen due to grid outage,site=
 went down due to gen overload (20Kva, 300A) and poor backup //  Grid power=
 return(he did a bridge on good phase Site on Grid)","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","site was on gen due t=
o grid outage,site went down due to gen overload (20Kva, 300A) and poor bac=
kup //  Grid power return","joelle.ekessi@ihstowers.com","3727","30-10-2024=
 20:49:13","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0003450773","Abo=
me","","30-10-2024 20:15:39","30-10-2024 20:11:36","30-10-2024 20:14:14","G=
rid fluctuation, site went down because Gen fails to start due to Grid bad =
voltage // grid power stabilized","MINKA NICOLAS","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site wen=
t down because Gen fails to start due to Grid bad voltage // grid power sta=
bilized","emmanuel.ghani@ihstowers.com","244","30-10-2024 20:15:39","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003450304","O=
lembe-Terminus","","30-10-2024 19:13:31","30-10-2024 18:34:12","30-10-2024 =
21:03:00","Grid Outage Gen Failed to Start due to Grid Contactorts Dysfunti=
onning// Grid Restored","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","ATS-AMF Issue","Grid Outage Gen Failed to Start due to Grid Co=
ntactorts Dysfuntionning// Grid Restored","denis.mballa@ihstowers.com","236=
0","30-10-2024 19:13:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003450290","Emana ly=
cee 2","","30-10-2024 19:09:41","30-10-2024 18:22:09","30-10-2024 19:11:52"=
,"Cascaded Incident from TTO3343112","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down bec=
ause gen start and stoppen with alarm over frequency // He reset gen card a=
nd adjust the frequencies","system","2852","30-10-2024 19:09:41","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003450288","EMANA BI=
LICK CITY","","30-10-2024 19:09:40","30-10-2024 18:22:09","30-10-2024 19:11=
:52","Cascaded Incident from TTO3343112","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid outage, site went down=
 because gen start and stoppen with alarm over frequency // He reset gen ca=
rd and adjust the frequencies","system","2851","30-10-2024 19:09:40","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003450289","Emana Ly=
cee","","30-10-2024 19:09:40","30-10-2024 18:22:09","30-10-2024 19:11:52","=
Cascaded Incident from TTO3343112","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site went down becau=
se gen start and stoppen with alarm over frequency // He reset gen card and=
 adjust the frequencies","system","2851","30-10-2024 19:09:40","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003450287","Mballa 4=
","","30-10-2024 19:09:40","30-10-2024 18:22:09","30-10-2024 19:11:52","Cas=
caded Incident from TTO3343112","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, site went down because g=
en start and stoppen with alarm over frequency // He reset gen card and adj=
ust the frequencies","system","2851","30-10-2024 19:09:40","Sagemcom CMR"
"Closed Complete","Site Down","T1328","IHS_YND_247","NOCINC0003449713","Oko=
lo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_685","30-10-2024 18:25:=
41","30-10-2024 18:22:09","30-10-2024 19:11:52","grid outage, site went dow=
n because gen start and stoppen with alarm over frequency // He reset gen c=
ard and adjust the frequencies","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","grid outage, site went down because =
gen start and stoppen with alarm over frequency // He reset gen card and ad=
just the frequencies","emmanuel.ghani@ihstowers.com","213","30-10-2024 18:2=
5:41","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0003449467","Mam=
bine","","30-10-2024 17:38:42","30-10-2024 17:32:36","30-10-2024 18:00:42",=
"Site went down because Gen failed to start due to Hybrid system dysfonctio=
n// He reset the hybrid system","Fanda Brice","Equipment Repair","Passive",=
"Hybrid","Hybrid Module","Site went down because Gen failed to start due to=
 Hybrid system dysfonction// He reset the hybrid system","emmanuel.ghani@ih=
stowers.com","558","30-10-2024 17:38:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003449436","L=
abogenie","","30-10-2024 17:33:46","30-10-2024 17:25:27","30-10-2024 17:26:=
01","No power issue site on grid with U=3D54v Georeges Dassi(697461814) fro=
m Huawei is informed","","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D5=
4v Georeges Dassi(697461814) from Huawei is informed","denis.mballa@ihstowe=
rs.com","500","30-10-2024 17:33:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003448888","N=
kolndongo","","30-10-2024 16:17:14","30-10-2024 16:09:05","30-10-2024 16:44=
:51","Grid outage site went down because main Gen faulty// Grid power retur=
n","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generato=
r Faulty","Grid outage site went down because main Gen faulty// Grid power =
return","christian.fonkou@ihstowers.com","490","30-10-2024 16:17:14","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0003448856","S=
calom","","30-10-2024 16:14:47","30-10-2024 16:04:37","30-10-2024 16:48:58"=
,"Active//No power issue on site ,site on Grid with Ubaie=3D54,5V The TX FM=
E Mbah Hosiah (674007438) from Huawei is informed","Paul BIBOUM","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site ,site on Grid with Ubaie=3D54,5V The TX FM=
E Mbah Hosiah (674007438) from Huawei is informed","christian.fonkou@ihstow=
ers.com","611","30-10-2024 16:14:47","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003448665","San=
ta Barbara Gottam","","30-10-2024 15:50:33","30-10-2024 15:47:28","30-10-20=
24 16:36:30","Site went down due to PWC dysfonctioning ( Batteries Backup  =
alarming ; PWC FNS)//Reset Batteries Backup,site on Grid.","Delor Telezing"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"Site went down due to PWC dysfonctioning ( Batteries Backup  alarming ; P=
WC FNS)//Reset Batteries Backup,site on Grid.","emmanuel.ghani@ihstowers.co=
m","186","30-10-2024 15:50:33","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003448607","Eko=
unou","","30-10-2024 15:44:22","30-10-2024 15:40:17","30-10-2024 15:49:39",=
"Grid outage,site went down before DG start due to Poor Batteries Backup //=
 Grid power return","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage,site went down before DG s=
tart due to Poor Batteries Backup // Grid power return","emmanuel.ghani@ihs=
towers.com","246","30-10-2024 15:44:22","Sagemcom CMR"
"Closed Complete","Site Down","T1579","IHS_YND_480","NOCINC0003448516","Sic=
 Cite Verte Matgenie","","30-10-2024 15:31:33","30-10-2024 15:27:29","31-10=
-2024 07:37:49","Grid only site.no space to deploy mobile gen // grid power=
 ","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid only site.no space to deploy mobile gen // grid power ","emmanuel.ghani=
@ihstowers.com","245","30-10-2024 15:31:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0003448302","Jean Ves=
pa 2","","30-10-2024 15:09:00","30-10-2024 14:59:25","30-10-2024 15:35:44",=
"Cascaded Incident from TTO3340818","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,DG started and stopped=
 with alarm 'overcurrent' due to //  he reset gen card and manually started=
","system","575","30-10-2024 15:09:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003448295","J=
-Vespa","IHS_YND_544","30-10-2024 15:07:38","30-10-2024 14:59:25","30-10-20=
24 15:35:44","Grid outage,DG started and stopped with alarm 'overcurrent' d=
ue to //  he reset gen card and manually started","Mboua Thierry","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,DG start=
ed and stopped with alarm 'overcurrent' due to //  he reset gen card and ma=
nually started","denis.mballa@ihstowers.com","494","30-10-2024 15:07:38","S=
agemcom CMR"
"Closed Complete","Site Down","T1736","IHS_YND_161","NOCINC0003448287","Sof=
avinc","","30-10-2024 15:06:11","30-10-2024 15:00:06","30-10-2024 19:10:27"=
,"Grid outage, Gen started  site went down because  Grid contactor dysfonct=
ion //He blocked Grid contactor, site on Gen","MINKA NICOLAS","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, Gen starte=
d  site went down because  Grid contactor dysfonction //He blocked Grid con=
tactor, site on Gen","emmanuel.ghani@ihstowers.com","365","30-10-2024 15:06=
:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003448277","Dong",""=
,"30-10-2024 15:05:21","30-10-2024 14:04:54","30-10-2024 17:51:50","Cascade=
d Incident from TTO3340791","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","site went down because Gen failed to start=
 due to battery Gen faulty// Gen manually started with external battery","s=
ystem","3627","30-10-2024 15:05:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003448276","Donga","=
","30-10-2024 15:05:20","30-10-2024 14:04:54","30-10-2024 17:51:50","Cascad=
ed Incident from TTO3340791","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because Gen failed to star=
t due to battery Gen faulty// Gen manually started with external battery","=
system","3626","30-10-2024 15:05:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003448263","Crf-Mban=
kolo-IHS","","30-10-2024 15:04:01","30-10-2024 14:57:17","30-10-2024 15:45:=
55","Cascaded Incident from TTO3340744","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,DG started and sto=
pped with alarm 'overcurrent'  //  he reset gen card and manually started",=
"system","404","30-10-2024 15:04:01","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003448227","Jea=
n Vespa","IHS_YND_574","30-10-2024 15:02:23","30-10-2024 14:57:17","30-10-2=
024 15:45:55","Grid outage,DG started and stopped with alarm 'overcurrent' =
 //  he reset gen card and manually started","Mboua Thierry","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,DG started an=
d stopped with alarm 'overcurrent'  //  he reset gen card and manually star=
ted","emmanuel.ghani@ihstowers.com","307","30-10-2024 15:02:23","Sagemcom C=
MR"
"Closed Complete","Site Down","T0460","IHS_YND_201","NOCINC0003448134","Cit=
e Verte","","30-10-2024 14:52:00","30-10-2024 13:12:45","31-10-2024 07:33:3=
6","Grid outage.no space to deploy mobile gen //grid power","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no spac=
e to deploy mobile gen //grid power","emmanuel.ghani@ihstowers.com","5956",=
"30-10-2024 14:52:00","Sagemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0003448106","Ngu=
ila","IHS_YND_434, IHS_YND_444","30-10-2024 14:48:58","30-10-2024 14:04:54"=
,"30-10-2024 17:53:19","site went down because Gen failed to start due to b=
attery Gen faulty// Gen manually started with external battery","Parker Tch=
oup","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","si=
te went down because Gen failed to start due to battery Gen faulty// Gen ma=
nually started with external battery","emmanuel.ghani@ihstowers.com","2645"=
,"30-10-2024 14:48:58","Sagemcom CMR"
"Closed Complete","Site Down","T0469","IHS_YND_157","NOCINC0003448095","MVA=
N","","30-10-2024 14:47:27","30-10-2024 14:24:24","30-10-2024 14:52:24","Gr=
id outage, site went down before gen start due to poor battery backup // ge=
n start automatically","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
gen start due to poor battery backup // gen start automatically","emmanuel.=
ghani@ihstowers.com","1383","30-10-2024 14:47:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003448092","Entree C=
ite Verte","","30-10-2024 14:47:14","30-10-2024 14:12:37","30-10-2024 15:02=
:23","Cascaded Incident from TTO3340586","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has =
deployed","system","2077","30-10-2024 14:47:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003448088","Afanoya"=
,"","30-10-2024 14:47:00","30-10-2024 14:41:13","30-10-2024 14:51:03","Casc=
aded Incident from TTO3340582","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site was on gen due to grid outage,sit=
e went down due to gen overload (20Kva, 300A) // He reduced the load and st=
arted Gen manually.","system","347","30-10-2024 14:47:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003448086","ELOUMDEM=
 CARRIERE","","30-10-2024 14:46:59","30-10-2024 14:41:13","30-10-2024 14:51=
:03","Cascaded Incident from TTO3340582","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site was on gen due to grid out=
age,site went down due to gen overload (20Kva, 300A) // He reduced the load=
 and started Gen manually.","system","346","30-10-2024 14:46:59","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003448087","MBALNGON=
G LYCEE","","30-10-2024 14:46:59","30-10-2024 14:41:13","30-10-2024 14:51:0=
3","Cascaded Incident from TTO3340582","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site was on gen due to grid outag=
e,site went down due to gen overload (20Kva, 300A) // He reduced the load a=
nd started Gen manually.","system","346","30-10-2024 14:46:59","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003448080","C=
ite-Verte","IHS_YND_543","30-10-2024 14:45:47","30-10-2024 14:12:37","30-10=
-2024 15:02:23","Grid outage//MDG of 20 kva has deployed","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG of 2=
0 kva has deployed","denis.mballa@ihstowers.com","1991","30-10-2024 14:45:4=
7","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003448076","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","30-10-2024 14:45:19","30-10-20=
24 14:41:13","30-10-2024 18:46:03","site was on gen due to grid outage,site=
 went down due to gen overload (20Kva, 300A) // He reduced the load and sta=
rted Gen manually.","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","site was on gen due to grid outage,site went down due =
to gen overload (20Kva, 300A) // He reduced the load and started Gen manual=
ly.","emmanuel.ghani@ihstowers.com","247","30-10-2024 14:45:19","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003447641","B=
iyemassi LAC","","30-10-2024 14:03:34","30-10-2024 13:44:26","30-10-2024 13=
:45:43","No power issue site on grid with U=3D54.6v Noitice that we have dy=
sjunction at OCM Equipements .Mbah Osiah from Huawei is informed","","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue site on grid with U=3D54.6v Noitice that we have dysju=
nction at OCM Equipements .Mbah Osiah from Huawei is informed","christian.f=
onkou@ihstowers.com","1149","30-10-2024 14:03:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003447492","M=
fou EPC","","30-10-2024 13:49:14","30-10-2024 13:35:09","30-10-2024 14:04:1=
3","","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation, site went down because gen start =
and stopped due to grid bad voltage // gen manually started","christian.fon=
kou@ihstowers.com","846","30-10-2024 13:49:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003447360","L=
abogenie","","30-10-2024 13:27:16","30-10-2024 13:00:02","30-10-2024 13:37:=
17","Active//No power isssue, site is on grid with Ubaie=3D54,8V,The FME Ge=
orge (697461814) from Huawei is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
sssue, site is on grid with Ubaie=3D54,8V,The FME George (697461814) from H=
uawei is informed","christian.fonkou@ihstowers.com","1635","30-10-2024 13:2=
7:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003447223","C=
ite-Verte","","30-10-2024 13:07:12","30-10-2024 12:26:05","30-10-2024 13:34=
:25","","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","grid outage//MDG 20Kva deployed","christian.fonkou@ihstowers.com","2468=
","30-10-2024 13:07:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0003446861","S=
apeur Mimboman","","30-10-2024 12:19:16","30-10-2024 11:59:06","30-10-2024 =
12:47:46","grid outage,gen failed to start due to card Ge faulty//he starte=
d the gen manually","Mba Lazare Herve","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","grid outage,gen failed to start due to card Ge =
faulty//he started the gen manually","christian.fonkou@ihstowers.com","1211=
","30-10-2024 12:19:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003446582","N=
kozoa","","30-10-2024 11:52:05","30-10-2024 11:38:58","30-10-2024 13:22:53"=
,"Grid outage, site went down due to gen overload(20KVA, 305A) // he reduic=
ed the load and started Gen manually","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload(20KVA, 305A) // he reduiced the load and started Gen manually"=
,"christian.fonkou@ihstowers.com","788","30-10-2024 11:52:05","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003446563","M=
essa-Carriere OCM","","30-10-2024 11:50:09","30-10-2024 11:34:02","31-10-20=
24 07:33:30","Grid outage.no space to deploy mobile gen//grid power ","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge.no space to deploy mobile gen//grid power ","christian.fonkou@ihstowers.=
com","969","30-10-2024 11:50:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003446400","E=
mombo-Tchad","","30-10-2024 11:33:22","29-10-2024 07:37:55","29-10-2024 07:=
47:09","","","Grid Supply","Passive","Grid","National Grid - Grid Outage Is=
sue","grid outage,no space to deploy a mobl gen//grid return","alwine.fambo=
u@ihstowers.com","100944","30-10-2024 11:33:22","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0003446265","Tsi=
nga village","","30-10-2024 11:18:32","30-10-2024 11:09:22","30-10-2024 12:=
17:22","site went down because the Cb(125A) dysjoncted  in the pwc due to t=
he power cables that feed the MTN equipment, burnt //  he changed the burnt=
 power cable and put on the CB","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Circuit Breaker Issue","site went down =
because the Cb(125A) dysjoncted  in the pwc due to the power cables that fe=
ed the MTN equipment, burnt //  he changed the burnt power cable and put on=
 the CB","rouselle.schoune@ihstowers.com","551","30-10-2024 11:18:32","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003445922","O=
dza II","","30-10-2024 10:48:03","30-10-2024 10:32:57","30-10-2024 11:05:52=
","grid outage,gen stopped with alarm high temp//he added water in radiator=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High Engi=
ne Temp - Coolant Level Issue","grid outage,gen stopped with alarm high tem=
p//he added water in radiator","christian.fonkou@ihstowers.com","908","30-1=
0-2024 10:48:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0003445898","M=
vog-Ada_OCM","","30-10-2024 10:45:04","30-10-2024 10:15:59","30-10-2024 11:=
56:09","No power issue on site U=3D53,4v site on grid Rm Alain of huawei is=
 informed","","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","No power issue on site U=3D53,4v site on grid Rm =
Alain of huawei is informed","christian.fonkou@ihstowers.com","1746","30-10=
-2024 10:45:04","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0003444993","N=
dogbessol","","30-10-2024 08:32:00","30-10-2024 08:26:40","30-10-2024 09:41=
:56","ACTIVE / No power issue site on Grid with U=3D53.6 V The Tx FME Etien=
ne (695033981) from Hauawei is informed,","Kemeni Franklin","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACT=
IVE / No power issue site on Grid with U=3D53.6 V The Tx FME Etienne (69503=
3981) from Hauawei is informed,","christian.fonkou@ihstowers.com","322","30=
-10-2024 08:32:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003444269","E=
kie-Elegance","","30-10-2024 06:23:14","30-10-2024 05:47:56","30-10-2024 07=
:59:56","Grid outage // MDG of 20Kva has deplyed","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage // M=
DG of 20Kva has deplyed","alexandre.kamal@ihstowers.com","2119","30-10-2024=
 06:23:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003444009","Messassi=
 okolo","","30-10-2024 05:17:11","30-10-2024 04:56:16","30-10-2024 06:09:16=
","Cascaded Incident from TTO3336134","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive"," grid outage, site went down b=
ecause gen fails to start due to ATS disfunctionning // Gen manually start"=
,"system","1255","30-10-2024 05:17:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0003444006","E=
MANA BILICK CITY","IHS_YND_279","30-10-2024 05:16:23","30-10-2024 04:56:16"=
,"30-10-2024 06:09:16"," grid outage, site went down because gen fails to s=
tart due to ATS disfunctionning // Gen manually start","Fabrice Pouakam","E=
quipment Repair","Passive","Control Panel","ATS-AMF Issue"," grid outage, s=
ite went down because gen fails to start due to ATS disfunctionning // Gen =
manually start","alexandre.kamal@ihstowers.com","1209","30-10-2024 05:16:23=
","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003443918","ODZ=
A CITE MBIA","","30-10-2024 04:48:34","30-10-2024 04:11:24","30-10-2024 05:=
23:11"," grid OUTAGE, site went down because gen fails to start due to ATS =
disfunctionning // Gen manually start","Albran Byorel","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue"," grid OUTAGE, site went down beca=
use gen fails to start due to ATS disfunctionning // Gen manually start","k=
amga.virgile@ihstowers.com","2230","30-10-2024 04:48:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003443797","E=
kounou","","30-10-2024 04:03:35","30-10-2024 04:01:25","30-10-2024 04:11:01=
","Grid outage,site went down before DG start due to Poor Batteries Backup =
// Grid power return","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage,site went down before DG=
 start due to Poor Batteries Backup // Grid power return","alexandre.kamal@=
ihstowers.com","131","30-10-2024 04:03:35","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003443737","Com=
plex Beac II","","30-10-2024 03:40:03","30-10-2024 03:36:52","30-10-2024 04=
:28:00","Grid outage, site went down because gen failed to start due to Gen=
 card faulty // gen start manually","Albran Byorel","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down becaus=
e gen failed to start due to Gen card faulty // gen start manually","kamga.=
virgile@ihstowers.com","192","30-10-2024 03:40:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003443482","E=
kie-Elegance","","30-10-2024 02:03:55","30-10-2024 01:53:38","30-10-2024 04=
:01:37","Grid outage // MDG of 20Kva has deplyed","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage // M=
DG of 20Kva has deplyed","alexandre.kamal@ihstowers.com","618","30-10-2024 =
02:03:55","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0003443416","Aha=
la Echangeur","","30-10-2024 01:45:03","30-10-2024 01:36:52","30-10-2024 02=
:22:13","Grid fluctuation site went down because Gen failed to start due to=
 Grid bad voltage// Grid stabilized","MINKA NICOLAS","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuation site w=
ent down because Gen failed to start due to Grid bad voltage// Grid stabili=
zed","kamga.virgile@ihstowers.com","492","30-10-2024 01:45:03","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003443132","L=
abogenie","","30-10-2024 00:02:13","29-10-2024 23:52:59","30-10-2024 00:00:=
42","Active//No power issue on site ,site on Grid with Ubaie=3D54.8 V  FME =
Tx Eloundou (652586578)from Huawei is informed. Repetitif issue","","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site ,site on Grid with Ubaie=3D54.8 V  FME =
Tx Eloundou (652586578)from Huawei is informed. Repetitif issue","alexandre=
.kamal@ihstowers.com","555","30-10-2024 00:02:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003442946","M=
VAN SACEL","","29-10-2024 23:07:56","29-10-2024 22:59:46","29-10-2024 23:25=
:31","site went down because Gen failed to start due to Grid bad voltage //=
 He bypass the Grid and site on Gen","MINKA NICOLAS","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","site went down because =
Gen failed to start due to Grid bad voltage // He bypass the Grid and site =
on Gen","alexandre.kamal@ihstowers.com","491","29-10-2024 23:07:56","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0003442823","FOUGEROL=
E","","29-10-2024 22:44:10","29-10-2024 22:00:10","29-10-2024 22:50:15","Ca=
scaded Incident from TTO3334746","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down due to Ge=
n overload(20KVA, 270A)//Grid Restored","system","2640","29-10-2024 22:44:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0003442819","N=
gousso-Savana","IHS_YND_561","29-10-2024 22:43:14","29-10-2024 22:00:10","2=
9-10-2024 22:50:15","Grid outage, site went down due to Gen overload(20KVA,=
 270A)//Grid Restored","Siligap Boris","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Grid outage, site went down due to Gen overload(20KV=
A, 270A)//Grid Restored","alexandre.kamal@ihstowers.com","2585","29-10-2024=
 22:43:14","Sagemcom CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0003442529","RUE=
 FOE","","29-10-2024 22:00:49","29-10-2024 21:51:40","29-10-2024 23:47:41",=
"site went down because the Cb(32A) of PWC dysjoncted due to 03/05 slot of =
rectifier faulty// he reamed the Cb of PWC","Delor Telezing","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","sit=
e went down because the Cb(32A) of PWC dysjoncted due to 03/05 slot of rect=
ifier faulty// he reamed the Cb of PWC","landry.etame@ihstowers.com","550",=
"29-10-2024 22:00:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003442474","Eto koss=
 Yde","","29-10-2024 21:52:20","29-10-2024 21:48:13","29-10-2024 21:54:07",=
"Cascaded Incident from TTO3334341","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid bad voltage, site went down bec=
ause gen start and stopped due to grid bad voltage//He bypassed Grid and st=
arted Gen","system","247","29-10-2024 21:52:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003442475","ELOUMDEM=
 CARRIERE 2","","29-10-2024 21:52:20","29-10-2024 21:48:13","29-10-2024 21:=
54:07","Cascaded Incident from TTO3334341","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid bad voltage, site went d=
own because gen start and stopped due to grid bad voltage//He bypassed Grid=
 and started Gen","system","247","29-10-2024 21:52:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003442470","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","29-10-2024 21:51:22","29-10-2024 21:48=
:13","29-10-2024 21:54:07","Grid bad voltage, site went down because gen st=
art and stopped due to grid bad voltage//He bypassed Grid and started Gen",=
"Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid bad voltage, site went down because gen start and stopped=
 due to grid bad voltage//He bypassed Grid and started Gen","landry.etame@i=
hstowers.com","191","29-10-2024 21:51:22","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003442465","Mes=
sa Carriere","","29-10-2024 21:50:20","29-10-2024 21:44:30","29-10-2024 21:=
59:43","site went down due to insufficient rectifier on site //site stabili=
zed","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down due to insufficient rectifier on site //site stabiliz=
ed","landry.etame@ihstowers.com","350","29-10-2024 21:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0003441891","FOUGEROL=
E","","29-10-2024 20:38:30","29-10-2024 20:29:21","29-10-2024 21:21:13","Ca=
scaded Incident from TTO3333651","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage ,site went down because G=
en started and stopped due to Gen overload (20KVA,260A)//Grid return","syst=
em","549","29-10-2024 20:38:30","Sagemcom CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0003441871","Ngo=
usso-Savana","IHS_YND_561","29-10-2024 20:34:26","29-10-2024 20:29:21","29-=
10-2024 21:21:13","Grid outage ,site went down because Gen started and stop=
ped due to Gen overload (20KVA,260A)//Grid return","Siligap Boris","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went d=
own because Gen started and stopped due to Gen overload (20KVA,260A)//Grid =
return","landry.etame@ihstowers.com","448","29-10-2024 20:34:26","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003441493","B=
astos Bethesda","","29-10-2024 19:53:22","29-10-2024 19:49:17","29-10-2024 =
19:55:22","Grid Outage, site went down before Gen start due to poor backup/=
/ Gen started automatically","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid Outage, site went down b=
efore Gen start due to poor backup// Gen started automatically","kouoh.jean=
@ihstowers.com","246","29-10-2024 19:53:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0003441370","B=
ONAS YDE","","29-10-2024 19:36:29","29-10-2024 19:26:50","29-10-2024 19:30:=
44","No power issue on site,site on Grid with Ubaie=3D56.2 V The TX FME Mba=
h Hosiah (674007438)  from Huawei is informed and notice that disjunction o=
f CB in Bts Ocm","Paul BIBOUM","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue on site,site on G=
rid with Ubaie=3D56.2 V The TX FME Mbah Hosiah (674007438)  from Huawei is =
informed and notice that disjunction of CB in Bts Ocm","kouoh.jean@ihstower=
s.com","580","29-10-2024 19:36:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003441116","K=
oweit City","","29-10-2024 18:44:33","29-10-2024 18:35:08","29-10-2024 19:2=
7:05","Grid Outage,Gen Failed to Start due to alarms ''Low fuel''short circ=
uit //He Reset the Gen Card and Manually Started the Gen ","Albran Byorel",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage=
,Gen Failed to Start due to alarms ''Low fuel''short circuit //He Reset the=
 Gen Card and Manually Started the Gen ","kouoh.jean@ihstowers.com","566","=
29-10-2024 18:44:33","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003441075","Nko=
lnda","","29-10-2024 18:36:17","29-10-2024 18:29:12","29-10-2024 18:37:00",=
"Grid fluctuation site went down because Gen failed to start due to Grid ba=
d voltage // Grid stabilized","Albran Byorel","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid fluctuation site went dow=
n because Gen failed to start due to Grid bad voltage // Grid stabilized","=
landry.etame@ihstowers.com","426","29-10-2024 18:36:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0003440836","S=
calom","","29-10-2024 17:56:24","29-10-2024 17:31:41","29-10-2024 17:35:26"=
,"No power issue , Ubaie=3D54.5 V site on Grid.he TX FME Mbah Hosiah (67400=
7438) from Huawei is informed","Paul BIBOUM","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue , U=
baie=3D54.5 V site on Grid.he TX FME Mbah Hosiah (674007438) from Huawei is=
 informed","kouoh.jean@ihstowers.com","1484","29-10-2024 17:56:24","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0003440384","NKONGKAR=
AK","","29-10-2024 17:07:01","29-10-2024 16:52:01","29-10-2024 16:57:32","C=
ascaded Incident from TTO3331895","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Grid outage, site went down =
before gen start due to poor battery backup // Gen started automatically","=
system","900","29-10-2024 17:07:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003440383","Lobo OCM=
","","29-10-2024 17:07:01","29-10-2024 16:52:01","29-10-2024 16:57:32","Cas=
caded Incident from TTO3331895","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","sy=
stem","900","29-10-2024 17:07:01","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003440380","N=
KOMEKUI OCM","IHS_YND_341, IHS_YND_713","29-10-2024 17:06:13","29-10-2024 1=
6:52:01","29-10-2024 16:57:32","Grid outage, site went down before gen star=
t due to poor battery backup // Gen started automatically","TIENTCHEU NZETC=
HIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","Grid outage, site went down before gen start due to =
poor battery backup // Gen started automatically","kouoh.jean@ihstowers.com=
","853","29-10-2024 17:06:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003440357","L=
abogenie","","29-10-2024 16:59:52","29-10-2024 16:46:54","29-10-2024 16:50:=
47","No power issue on site ,site on Grid with Ubaie=3D54.8 V  FME Tx Eloun=
dou (652586578)from Huawei is informed. ","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site ,site on Grid with Ubaie=3D54.8 V  FME Tx Eloundou (652586578)from Hua=
wei is informed. ","kouoh.jean@ihstowers.com","779","29-10-2024 16:59:52","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0003440345","O=
bili Carrefour","","29-10-2024 16:57:43","29-10-2024 16:35:34","29-10-2024 =
16:40:47","No power site ,site on GRID with Ubaie=3D53.4 V The Tx Fme Hosia=
h Mbah (674007438) of Huawei is informed.","Paul BIBOUM","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er site ,site on GRID with Ubaie=3D53.4 V The Tx Fme Hosiah Mbah (674007438=
) of Huawei is informed.","kouoh.jean@ihstowers.com","1329","29-10-2024 16:=
57:43","Sagemcom CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0003440103","Oko=
lo Kilombo","","29-10-2024 16:19:32","29-10-2024 15:14:22","29-10-2024 16:3=
3:49","Grid Outage,Site went down due to Grid Contactors Dysfuntionning //H=
e bypass the Grid Contactors and Site is on Grid","Fabrice Pouakam","Equipm=
ent Repair","Passive","Control Panel","ATS-AMF Issue","Grid Outage,Site wen=
t down due to Grid Contactors Dysfuntionning //He bypass the Grid Contactor=
s and Site is on Grid","landry.etame@ihstowers.com","3911","29-10-2024 16:1=
9:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0003439906","S=
apeur Mimboman","","29-10-2024 15:50:33","29-10-2024 15:44:21","29-10-2024 =
15:48:26","Grid outage  ,site went down because Gen failed to start due to =
Gen card faulty//Grid power return","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage  ,site went down be=
cause Gen failed to start due to Gen card faulty//Grid power return","kouoh=
.jean@ihstowers.com","372","29-10-2024 15:50:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003439859","M=
adison","","29-10-2024 15:43:00","29-10-2024 15:24:54","29-10-2024 15:41:55=
","Grid outage //Grd power return","MFOUAGUEGUE MATHIEU","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage //Grd power r=
eturn","christian.fonkou@ihstowers.com","1087","29-10-2024 15:43:00","Sagem=
com CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003439797","Ess=
os Marche","","29-10-2024 15:32:18","29-10-2024 15:26:12","29-10-2024 15:44=
:26","Grid outage, site went down before gen start due to poor battery back=
up // Grid power return","Delor Telezing","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Grid power return","landry.etame=
@ihstowers.com","368","29-10-2024 15:32:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003439547","N=
kozoa","","29-10-2024 14:54:55","29-10-2024 13:46:57","29-10-2024 15:10:25"=
,"Grid outage, site went down because Gen started and stopped  due to Gen o=
verload(20KVA, 330A)//Grid power return","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down beca=
use Gen started and stopped  due to Gen overload(20KVA, 330A)//Grid power r=
eturn","kouoh.jean@ihstowers.com","4079","29-10-2024 14:54:55","Sagemcom CM=
R"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003439522","NYO=
M 2 IHS","","29-10-2024 14:50:15","29-10-2024 14:10:52","29-10-2024 16:18:5=
2","Grid outage, site went down due to Gen overload(15KVA, 240A) //he redui=
ce the Load","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACD=
G - Overload","Grid outage, site went down due to Gen overload(15KVA, 240A)=
 //he reduice the Load","landry.etame@ihstowers.com","3313","29-10-2024 14:=
50:15","Sagemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0003439354","Aba=
ng","IHS_YND_794","29-10-2024 14:33:27","29-10-2024 12:27:03","29-10-2024 1=
2:31:53","site down due to work of 696422966 /SANGA/ZTE (second power cable=
 installation)//end of work ","Mba Lazare Herve","Installation Activity","P=
assive","Planned Activity","Installation Activity","site down due to work o=
f 696422966 /SANGA/ZTE (second power cable installation)//end of work ","em=
manuel.ghani@ihstowers.com","7585","29-10-2024 14:33:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003438875","N=
GONA","","29-10-2024 13:27:45","29-10-2024 13:24:37","29-10-2024 16:27:23",=
"No power issue on site ,site on Grid with Ubaie=3D54.7 V The Tx FME Lionel=
 Adjep (655184876)from Huawei is informed. ","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site ,site on Grid with Ubaie=3D54.7 V The Tx FME Lionel=
 Adjep (655184876)from Huawei is informed. ","christian.fonkou@ihstowers.co=
m","189","29-10-2024 13:27:45","Sagemcom CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0003438760","Aba=
ttoir","","29-10-2024 13:14:22","29-10-2024 13:08:18","29-10-2024 13:38:11"=
,"Grid outage,gen stopped with alarm high temp(alarm unproven)//he reset th=
e gen card and started it","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage,gen stopped with alarm high t=
emp(alarm unproven)//he reset the gen card and started it","emmanuel.ghani@=
ihstowers.com","365","29-10-2024 13:14:22","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0003438692","Mon=
tee Jouvence","","29-10-2024 13:00:20","29-10-2024 12:56:11","29-10-2024 14=
:04:30","Grid bad voltage, site went down because gen start and stopped due=
 to grid bad voltage//He bypassed Grid and started Gen","Hyemafo Gildas","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d bad voltage, site went down because gen start and stopped due to grid bad=
 voltage//He bypassed Grid and started Gen","emmanuel.ghani@ihstowers.com",=
"250","29-10-2024 13:00:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003438565","N=
kozoa","","29-10-2024 12:42:57","29-10-2024 12:40:49","29-10-2024 12:59:53"=
,"","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Overl=
oad","grid outage, gen oveloaded(320A  20kva)//grid return","christian.fonk=
ou@ihstowers.com","129","29-10-2024 12:42:57","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003438524","Nko=
ulou Carriere carrefourt","","29-10-2024 12:34:38","29-10-2024 12:27:03","2=
9-10-2024 12:31:04","tikect need to cascade at Abang T1161 down at 12-27","=
Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","site down due to work of 696976792 /Kamga/ZTE (second power cable in=
stallation)//end of work","emmanuel.ghani@ihstowers.com","7653","29-10-2024=
 12:34:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003438516","M=
imboman-Village","","29-10-2024 12:32:11","29-10-2024 12:27:07","29-10-2024=
 12:32:53","","Mba Lazare Herve","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, site went down before gen st=
art due to poor battery backup // Gen start automatically","christian.fonko=
u@ihstowers.com","306","29-10-2024 12:32:11","Sagemcom CMR"
"Closed Complete","Site Down","T1328","IHS_YND_247","NOCINC0003437985","Oko=
lo","","29-10-2024 11:33:44","29-10-2024 11:25:39","29-10-2024 11:34:46","s=
ite went down because the Cb(80A) of Dcbox dysjoncted // He reamed the Cb",=
"Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Circuit Breaker Issue","site went down because the Cb(80A) of Dcbox dy=
sjoncted // He reamed the Cb","emmanuel.ghani@ihstowers.com","486","29-10-2=
024 11:33:44","Sagemcom CMR"
"Closed Complete","Site Down","T0104","IHS_YND_113","NOCINC0003437916","Emo=
mbo 2","","29-10-2024 11:23:02","29-10-2024 11:19:55","29-10-2024 11:53:55"=
,"Site on Grid,but did not feed the site because the Relay LVD went faulty =
// he bypass the LVD and Site is on Grid,","MINKA NICOLAS","Equipment Repai=
r","Passive","Control Panel","Relay","Site on Grid,but did not feed the sit=
e because the Relay LVD went faulty // he bypass the LVD and Site is on Gri=
d,","emmanuel.ghani@ihstowers.com","601","29-10-2024 11:23:02","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0003437900","N=
kolbong","","29-10-2024 11:20:45","29-10-2024 11:17:39","29-10-2024 13:19:2=
9","grid outage,gen stopped with alarm high temp//he added water in radiato=
r","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - High En=
gine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high t=
emp//he added water in radiator","christian.fonkou@ihstowers.com","187","29=
-10-2024 11:20:45","Sagemcom CMR"
"Closed Complete","Site Down","T0539","IHS_YND_034","NOCINC0003437691","EMI=
A MTN","","29-10-2024 10:50:49","29-10-2024 10:45:45","29-10-2024 15:17:48"=
,"Grid outage, No Space to deploy a Mobil Gen  //  Grid Restored","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, =
No Space to deploy a Mobil Gen  //  Grid Restored","emmanuel.ghani@ihstower=
s.com","305","29-10-2024 10:50:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003437687","N=
YOM 2 IHS","","29-10-2024 10:50:23","29-10-2024 10:46:17","29-10-2024 12:10=
:13","grid bad voltage,and gen failed to start//he bypassed grid and starte=
d the gen","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid =
- Phase Controller Faulty","grid bad voltage,and gen failed to start//he by=
passed grid and started the gen","christian.fonkou@ihstowers.com","247","29=
-10-2024 10:50:23","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0003437548","Obo=
bogo","","29-10-2024 10:34:09","29-10-2024 10:27:03","29-10-2024 10:35:03",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","emmanu=
el.ghani@ihstowers.com","427","29-10-2024 10:34:09","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003437336","Pha=
rmacie SION","","29-10-2024 10:14:29","29-10-2024 10:11:24","29-10-2024 13:=
05:25","grid outage,gen stopped with alarm high temp//he added water in rad=
iator","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high =
temp//he added water in radiator","emmanuel.ghani@ihstowers.com","186","29-=
10-2024 10:14:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003437326","Afanoya"=
,"","29-10-2024 10:13:01","29-10-2024 10:09:13","29-10-2024 11:20:26","Casc=
aded Incident from TTO3328389","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, DG Failed to start due to=
 overload (20Kva, 300A) // He reduced the load and started Gen manually","s=
ystem","228","29-10-2024 10:13:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003437324","ELOUMDEM=
 CARRIERE","","29-10-2024 10:13:00","29-10-2024 10:09:13","29-10-2024 11:20=
:26","Cascaded Incident from TTO3328389","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start=
 due to overload (20Kva, 300A) // He reduced the load and started Gen manua=
lly","system","227","29-10-2024 10:13:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003437325","MBALNGON=
G LYCEE","","29-10-2024 10:13:00","29-10-2024 10:09:13","29-10-2024 11:20:2=
6","Cascaded Incident from TTO3328389","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start d=
ue to overload (20Kva, 300A) // He reduced the load and started Gen manuall=
y","system","227","29-10-2024 10:13:00","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003437315","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","29-10-2024 10:11:22","29-10-20=
24 10:09:13","29-10-2024 11:20:26","Grid outage, DG Failed to start due to =
overload (20Kva, 300A) // He reduced the load and started Gen manually","Hy=
emafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage, DG Failed to start due to overload (20Kva, 300A) // He reduced t=
he load and started Gen manually","emmanuel.ghani@ihstowers.com","131","29-=
10-2024 10:11:22","Sagemcom CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0003437266","Kon=
dengui MTN","","29-10-2024 10:01:30","29-10-2024 09:53:24","29-10-2024 10:2=
2:12","site went down because the CB 32A of rectifier disjuncted causing by=
 grid fluctuation//he reamed the CB","Albran Byorel","Equipment Repair","Pa=
ssive","Rectifier","Rectifier - Circuit Breaker","site went down because th=
e CB 32A of rectifier disjuncted causing by grid fluctuation//he reamed the=
 CB","emmanuel.ghani@ihstowers.com","487","29-10-2024 10:01:30","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003437167","M=
ini-Ferme","","29-10-2024 09:44:42","29-10-2024 09:31:36","29-10-2024 09:41=
:31","Active//No power issue, site is on Grid with Ubaie=3D54,7V and Team S=
ADIO  from CDS TECHNOLOGIES (697 09 57 24) is Working on Site","","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue, site is on Grid with Ubaie=3D54,7V and Team SADI=
O  from CDS TECHNOLOGIES (697 09 57 24) is Working on Site","christian.fonk=
ou@ihstowers.com","787","29-10-2024 09:44:42","Sagemcom CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0003437063","Aba=
ttoir","","29-10-2024 09:25:34","29-10-2024 09:19:30","29-10-2024 10:07:41"=
,"Grid outage,gen stopped with alarm high temp(alarm unproven)//he reset th=
e gen card and started it","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage,gen stopped with alarm high t=
emp(alarm unproven)//he reset the gen card and started it","emmanuel.ghani@=
ihstowers.com","444","29-10-2024 09:25:34","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0003437051","Nko=
zoa","","29-10-2024 09:23:42","29-10-2024 09:19:38","29-10-2024 09:34:38","=
grid outage,site went down due to Gen overload(20kva,300A)//he reduice the =
load on site","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","grid outage,site went down due to Gen overload(20kva,300A)/=
/he reduice the load on site","emmanuel.ghani@ihstowers.com","351","29-10-2=
024 09:23:42","Sagemcom CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0003436868","RUE=
 FOE","","29-10-2024 08:53:35","29-10-2024 08:52:30","29-10-2024 11:20:02",=
"Site went down because 2/5 slots of the rectifiers faulty // he change it,=
 site on gen","Delor Telezing","Equipment Repair","Passive","Rectifier","Re=
ctifier Module","Site went down because 2/5 slots of the rectifiers faulty =
// he change it, site on gen","emmanuel.ghani@ihstowers.com","66","29-10-20=
24 08:53:35","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003436833","HOP=
ITAL GENERAL RAIL YDE","","29-10-2024 08:49:26","29-10-2024 08:36:22","29-1=
0-2024 11:35:05","No power issue on site U=3D54v site on gen synphorien of =
huawei is informed","Delor Telezing","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54v site on gen synphorien of huawei is informed","joelle.ekessi@ihstowe=
rs.com","785","29-10-2024 08:49:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003436811","N=
kolfon Cimencam","","29-10-2024 08:45:19","29-10-2024 08:29:11","29-10-2024=
 10:36:06","Active//No power issue on site U=3D54,5V site on Gen The Rm Ala=
in (691144423) of huawei is informed, Repetitive issue","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue on site U=3D54,5V site on Gen The Rm Alain=
 (691144423) of huawei is informed, Repetitive issue","christian.fonkou@ihs=
towers.com","968","29-10-2024 08:45:19","Sagemcom CMR"
"Closed Complete","Site Down","T0536","IHS_YND_210","NOCINC0003436787","Pha=
rmacie Bleue","","29-10-2024 08:42:13","29-10-2024 08:36:09","29-10-2024 09=
:16:59","grid outage,gen failed to start due to battery Ge faulty//he start=
ed the gen with battery backup","Siligap Boris","Equipment Repair","Passive=
","ACDG Gen","ACDG - Generator Battery","grid outage,gen failed to start du=
e to battery Ge faulty//he started the gen with battery backup","emmanuel.g=
hani@ihstowers.com","364","29-10-2024 08:42:13","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003436718","Evo=
doula MTN","","29-10-2024 08:27:41","29-10-2024 08:22:36","29-10-2024 11:41=
:36","Site went down due to 02 rectifier fautlty on site // he added 02 rec=
tifier ","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down due to 02 rectifier fautlty on site //=
 he added 02 rectifier ","emmanuel.ghani@ihstowers.com","305","29-10-2024 0=
8:27:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0003436606","E=
TOUDI CHAPELLE","","29-10-2024 08:15:20","29-10-2024 08:13:16","29-10-2024 =
09:09:29","grid outage,gen start and stopped because water infiltration in =
Tank//he drained the tank","Delor Telezing","Fuel Outage (Probable)","Passi=
ve","Diesel","Tank Sealing Issue - Water In The Fuel","grid outage,gen star=
t and stopped because water infiltration in Tank//he drained the tank","joe=
lle.ekessi@ihstowers.com","125","29-10-2024 08:15:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003436546","B=
astos Bethesda","","29-10-2024 08:00:36","29-10-2024 07:59:31","29-10-2024 =
08:01:55","Grid outage, site went down before gen start due to poor battery=
 backup // Gen start automatically","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // Gen start automaticall=
y","joelle.ekessi@ihstowers.com","67","29-10-2024 08:00:36","Sagemcom CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0003436498","NTE=
MASSI","","29-10-2024 07:50:13","29-10-2024 07:48:07","29-10-2024 08:45:58"=
,"Grid outage, site went down because gen start and stopped with alarm 'gen=
 short circuit' // he reset gen card and manually start the gen","Delor Tel=
ezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage, site went down because gen start and stopped with alarm 'gen short=
 circuit' // he reset gen card and manually start the gen","emmanuel.ghani@=
ihstowers.com","126","29-10-2024 07:50:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003436476","MBALNGON=
G LYCEE","","29-10-2024 07:47:01","29-10-2024 07:44:57","29-10-2024 07:52:1=
7","Cascaded Incident from TTO3327414","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen start automatically","system"=
,"124","29-10-2024 07:47:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003436477","Afanoya"=
,"","29-10-2024 07:47:01","29-10-2024 07:44:57","29-10-2024 07:52:17","Casc=
aded Incident from TTO3327414","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Gen start automatically","system","124=
","29-10-2024 07:47:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003436475","ELOUMDEM=
 CARRIERE","","29-10-2024 07:47:00","29-10-2024 07:44:57","29-10-2024 07:52=
:17","Cascaded Incident from TTO3327414","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start automatically","syste=
m","123","29-10-2024 07:47:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003436470","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","29-10-2024 07:46:02","29-10-=
2024 07:44:57","29-10-2024 07:52:31","Grid outage, site went down before ge=
n start due to poor battery backup // Gen start automatically","Hyemafo Gil=
das","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automatically","joelle.ekessi@ihstowers.com","66","29-10-20=
24 07:46:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003436464","T=
ongolo OCM","","29-10-2024 07:44:53","29-10-2024 07:42:49","29-10-2024 16:5=
0:11","","Delor Telezing","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","no power issue on site ubaie=3D54v si=
te on grid","joelle.ekessi@ihstowers.com","125","29-10-2024 07:44:53","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0003436459","K=
ondengui","","29-10-2024 07:43:14","29-10-2024 07:35:09","29-10-2024 07:47:=
09","tikect need to cascasde at Emonbo-Tchad//grid outage,no space to deplo=
y a mobl gen//grid return","Albran Byorel","Grid Supply","Passive","Grid","=
National Grid - Grid Outage Issue","grid outage,no space to deploy a mobl g=
en//grid return","joelle.ekessi@ihstowers.com","100866","29-10-2024 07:43:1=
4","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003436457","S=
ous Prefecture","","29-10-2024 07:42:15","29-10-2024 07:31:11","29-10-2024 =
11:02:07","No power issue on site Ubaie:55,2V; site on Grid TX FME Hugo (67=
2390202) from Huawei is informed","Fanda Brice","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site Ubaie:55,2V; site on Grid TX FME Hugo (672390202) from Huawei is in=
formed","joelle.ekessi@ihstowers.com","665","29-10-2024 07:42:15","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003436441","N=
kolondom","","29-10-2024 07:37:08","29-10-2024 07:33:04","29-10-2024 08:15:=
21","site went down because gen start and stopped due to pre-filter fuel le=
ak//he fixed the fuel filter and started the gen","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Fuel Filter","site went down becau=
se gen start and stopped due to pre-filter fuel leak//he fixed the fuel fil=
ter and started the gen","joelle.ekessi@ihstowers.com","245","29-10-2024 07=
:37:08","Sagemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0003436429","Nko=
abang entree carriere","","29-10-2024 07:33:39","29-10-2024 07:30:34","29-1=
0-2024 07:44:34","Grid outage, site went down because gen fails to start du=
e to battery ge discharged // Gen start with battery backup","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Turbo Charger","Grid o=
utage, site went down because gen fails to start due to battery ge discharg=
ed // Gen start with battery backup","emmanuel.ghani@ihstowers.com","186","=
29-10-2024 07:33:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003436406","E=
lobi Mokolo","","29-10-2024 07:29:34","29-10-2024 07:27:30","29-10-2024 09:=
38:32","No power issue on site, site on Grid  with U=3D53,2 V The TX FME Br=
ice/650214096 from huawei is informed.","Mboua Thierry","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site, site on Grid  with U=3D53,2 V The TX FME Brice/650214096 f=
rom huawei is informed.","joelle.ekessi@ihstowers.com","125","29-10-2024 07=
:29:34","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003436363","Bit=
oto","","29-10-2024 07:14:48","29-10-2024 07:11:45","29-10-2024 07:49:45","=
grid outage site went down due toGen overload(20KVA, 300A) // grid return",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","grid outage site went down due toGen overload(20KVA, 300A) // grid retur=
n","emmanuel.ghani@ihstowers.com","312","29-10-2024 07:14:48","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003436360","S=
OA UNIVERSITY STADIUM","","29-10-2024 07:13:59","29-10-2024 07:08:54","29-1=
0-2024 09:18:07","No  power issue UBaie =3D55.2 V site on Grid.   The RM TX=
  SYMPHORIEN (650 25 71 51) From Huawei is informed.","Siligap Boris","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No  power issue UBaie =3D55.2 V site on Grid.   The RM TX  SYMPHORIE=
N (650 25 71 51) From Huawei is informed.","joelle.ekessi@ihstowers.com","3=
06","29-10-2024 07:13:59","Sagemcom CMR"
"Closed Complete","Site Down","T0579","IHS_YND_366","NOCINC0003436307","Man=
doumba MTN","","29-10-2024 07:00:18","29-10-2024 06:57:09","29-10-2024 07:0=
1:50"," Active//No  power issue on site ;site on Gen  with Ubaie=3D 53.6V  =
 TX Huawei Etienne(695033981) from Huawei is informed","Kemeni Franklin","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm"," Active//No  power issue on site ;site on Gen  with Ubaie=3D 53.6=
V   TX Huawei Etienne(695033981) from Huawei is informed","emmanuel.ghani@i=
hstowers.com","190","29-10-2024 07:00:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0003436261","N=
kongtock","","29-10-2024 06:47:32","29-10-2024 06:40:28","29-10-2024 07:02:=
24"," site down due to hybrid system dysfunctionning//gen started automatic=
ally(investigations ongoing)","Kemeni Franklin","Equipment Repair","Passive=
","Hybrid","Hybrid Module"," site down due to hybrid system dysfunctionning=
//gen started automatically(investigations ongoing)","joelle.ekessi@ihstowe=
rs.com","425","29-10-2024 06:47:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003436260","Afanoya"=
,"","29-10-2024 06:47:31","29-10-2024 06:45:42","29-10-2024 06:53:11","Casc=
aded Incident from TTO3327124","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Gen start automatically","system","109=
","29-10-2024 06:47:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003436259","MBALNGON=
G LYCEE","","29-10-2024 06:47:31","29-10-2024 06:45:42","29-10-2024 06:53:1=
1","Cascaded Incident from TTO3327124","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen start automatically","system"=
,"109","29-10-2024 06:47:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003436258","ELOUMDEM=
 CARRIERE","","29-10-2024 06:47:30","29-10-2024 06:45:42","29-10-2024 06:53=
:11","Cascaded Incident from TTO3327124","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start automatically","syste=
m","108","29-10-2024 06:47:30","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003436243","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","29-10-2024 06:45:45","29-10-20=
24 06:44:42","29-10-2024 06:53:11","Grid outage, site went down before gen =
start due to poor battery backup // Gen start automatically","Hyemafo Gilda=
s","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid outage, site went down before gen start due to poor battery backup=
 // Gen start automatically","emmanuel.ghani@ihstowers.com","132","29-10-20=
24 06:45:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003436187","Biteng-M=
aetur","","29-10-2024 06:36:40","29-10-2024 06:33:58","29-10-2024 07:46:56"=
,"grid outage, site went down because gen failed to started due to gen Over=
load(20kva, 280A)// He reduced the load","Mba Lazare Herve","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","grid outage, site went down bec=
ause gen failed to started due to gen Overload(20kva, 280A)// He reduced th=
e load","system","162","29-10-2024 06:36:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003436175","N=
kolndongo","","29-10-2024 06:36:03","29-10-2024 06:33:58","29-10-2024 07:46=
:55"," grid outage, site went down due toMain gen faulty // Grid return","M=
INKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fau=
lty"," grid outage, site went down due toMain gen faulty // Grid return","j=
oelle.ekessi@ihstowers.com","125","29-10-2024 06:36:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003436123","Entree C=
ite Verte","","29-10-2024 06:24:20","29-10-2024 06:14:27","29-10-2024 09:11=
:53","Cascaded Incident from TTO3326978","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site U=3D54v sit=
e on grid Brice Stague of huawei is informed notice that havy rain in area"=
,"system","593","29-10-2024 06:24:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003436116","C=
ite-Verte","IHS_YND_543","29-10-2024 06:23:31","29-10-2024 06:14:27","29-10=
-2024 09:11:53","No power issue on site U=3D54v site on grid Brice Stague o=
f huawei is informed notice that havy rain in area","","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site U=3D54v site on grid Brice Stague of huawei is informed noti=
ce that havy rain in area","joelle.ekessi@ihstowers.com","545","29-10-2024 =
06:23:31","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0003436093","NKO=
LOSSAN OKOK","","29-10-2024 06:16:09","29-10-2024 06:14:04","29-10-2024 06:=
28:04","No power issue on site U=3D50v site on gen Synphorien of huawei is =
informed notice that havy rain in area","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site U=3D50v site on gen Synphorien of huawei is informed notice=
 that havy rain in area","emmanuel.ghani@ihstowers.com","126","29-10-2024 0=
6:16:09","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003436073","Mes=
sa Carriere","","29-10-2024 06:07:18","29-10-2024 06:01:13","29-10-2024 12:=
15:30","site went down because 3/3 rectifiers faulty//he changed 2/3 rectif=
iers","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","site went down because 3/3 rectifiers faulty//he changed 2/3 rectif=
iers","emmanuel.ghani@ihstowers.com","365","29-10-2024 06:07:18","Sagemcom =
CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003436071","Bas=
tos Amb Coree","","29-10-2024 06:06:06","29-10-2024 06:04:02","29-10-2024 0=
8:02:13","grid outage,no space to deploy a mobil gen//grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,=
no space to deploy a mobil gen//grid return","emmanuel.ghani@ihstowers.com"=
,"125","29-10-2024 06:06:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003436068","O=
lembe-Terminus","","29-10-2024 06:05:28","29-10-2024 05:49:13","29-10-2024 =
19:21:53","Site went down due to MPR Faulty on site //he Replaced the Fault=
y MPR and Site is on Grid","Fabrice Pouakam","Equipment Repair","Passive","=
Rectifier","Rectifier Module Overloaded","Site went down due to MPR Faulty =
on site //he Replaced the Faulty MPR and Site is on Grid","olivier.kwedi@ih=
stowers.com","977","29-10-2024 06:05:28","Sagemcom CMR"
"Closed Complete","Site Down","T3446","IHS_YND_712","NOCINC0003436065","Nko=
lkoumou OCM","","29-10-2024 06:04:19","29-10-2024 06:02:17","29-10-2024 09:=
12:48","No power issue on sie U=3D54v site on grid Mouhamadou of huawei is =
informed notice that havy rain in area","TIENTCHEU NZETCHIEU GAEL","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on sie U=3D54v site on grid Mouhamadou of huawei is info=
rmed notice that havy rain in area","emmanuel.ghani@ihstowers.com","123","2=
9-10-2024 06:04:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0003436063","L=
eboudi","","29-10-2024 06:03:58","29-10-2024 05:55:34","29-10-2024 06:55:34=
","No power issue on site U=3D54,3v site on gen mouhamadou of huawei is inf=
ormed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54=
,3v site on gen mouhamadou of huawei is informed","olivier.kwedi@ihstowers.=
com","505","29-10-2024 06:03:58","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003436057","Sap=
eur","","29-10-2024 06:02:31","29-10-2024 05:57:14","29-10-2024 10:10:50","=
Site was on Gen due to Grid outage, site went because Gen stopped due to CB=
 Gen tripped// He put back on CB Gen","Mboua Thierry","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site was o=
n Gen due to Grid outage, site went because Gen stopped due to CB Gen tripp=
ed// He put back on CB Gen","stephane.nkamwa@ihstowers.com","318","29-10-20=
24 06:02:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0003436044","M=
bedoumou - Ekali","","29-10-2024 06:00:26","29-10-2024 05:53:19","29-10-202=
4 06:53:19","No power issue on site U=3D53v site on grid Lionel steeve of h=
uawei is informed","Albran Byorel","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
3v site on grid Lionel steeve of huawei is informed","olivier.kwedi@ihstowe=
rs.com","428","29-10-2024 06:00:26","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003436038","Mok=
olo Yaounde","","29-10-2024 05:58:43","29-10-2024 05:48:35","29-10-2024 08:=
04:13","grid outage,no space to deploy a mobil gen//grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no=
 space to deploy a mobil gen//grid return","stephane.nkamwa@ihstowers.com",=
"609","29-10-2024 05:58:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_792","NOCINC0003435987","NKOABANG=
 NKOLO 3","","29-10-2024 05:45:30","29-10-2024 05:39:22","29-10-2024 05:59:=
22","Cascaded Incident from TTO3326817","Mba Lazare Herve","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D53,=
9v site on grid Lionel steeve of huawei is informed","system","368","29-10-=
2024 05:45:30","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003435986","Nko=
abang2","IHS_YND_792","29-10-2024 05:44:58","29-10-2024 05:39:22","29-10-20=
24 05:59:22","No power issue on site U=3D53,9v site on grid Lionel steeve o=
f huawei is informed","Mba Lazare Herve","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 U=3D53,9v site on grid Lionel steeve of huawei is informed","stephane.nkam=
wa@ihstowers.com","337","29-10-2024 05:44:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0003435226","A=
n-Marche-Melen","","29-10-2024 01:39:16","28-10-2024 23:55:04","29-10-2024 =
00:55:04","No power issue on site U=3D52,9v site on grid Mbah Hosiah of hua=
wei is informed","","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue on site U=3D52,9v site on gr=
id Mbah Hosiah of huawei is informed","olivier.kwedi@ihstowers.com","6253",=
"29-10-2024 01:39:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003435148","O=
lembe-Terminus","","29-10-2024 01:09:03","28-10-2024 22:35:48","29-10-2024 =
03:34:54","site went down because the MPR dysfonction // he reset the MPR",=
"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Distr=
ibution","site went down because the MPR dysfonction // he reset the MPR","=
olivier.kwedi@ihstowers.com","9196","29-10-2024 01:09:03","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003435022","HOP=
ITAL GENERAL RAIL YDE","","29-10-2024 00:24:27","29-10-2024 00:19:20","29-1=
0-2024 01:17:50","access issue during the nigh due to landlord,site went du=
e to CB 63A disjuncted in DC-BOX//he replaced with CB 80A","Delor Telezing"=
,"Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue -=
 Land Lord","access issue during the nigh due to landlord,site went due to =
CB 63A disjuncted in DC-BOX//he replaced with CB 80A","stephane.nkamwa@ihst=
owers.com","308","29-10-2024 00:24:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0003434844","B=
astos Ekoudou","","28-10-2024 23:37:27","28-10-2024 23:28:15","28-10-2024 2=
3:38:12","Active: No power issue, site is on grid with Ubaie=3D53V, Eloundo=
u(693212405) from Huawie is infomred","Mboua Thierry","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: N=
o power issue, site is on grid with Ubaie=3D53V, Eloundou(693212405) from H=
uawie is infomred","olivier.kwedi@ihstowers.com","553","28-10-2024 23:37:27=
","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0003434674","Lob=
o 2","","28-10-2024 22:54:06","28-10-2024 22:37:56","29-10-2024 00:37:35","=
grid outage, site went down because gen failed to start due to dysfunctionn=
ing Hybride system //  gen manually started","TIENTCHEU NZETCHIEU GAEL","Eq=
uipment Repair","Passive","Hybrid","Hybrid Module","grid outage, site went =
down because gen failed to start due to dysfunctionning Hybride system //  =
gen manually started","stephane.nkamwa@ihstowers.com","971","28-10-2024 22:=
54:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0003434620","F=
ouda-New","","28-10-2024 22:44:42","28-10-2024 22:07:36","28-10-2024 23:56:=
59","grid bad voltage,and gen failed to start; Rcp faulty//he bypassed grid=
 and started the gen","Delor Telezing","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","grid bad voltage,and gen failed to st=
art; Rcp faulty//he bypassed grid and started the gen","olivier.kwedi@ihsto=
wers.com","2227","28-10-2024 22:44:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003434076","Eto koss=
 Yde","","28-10-2024 21:06:41","28-10-2024 20:57:14","28-10-2024 21:03:03",=
"Cascaded Incident from TTO3324526","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation site went down beca=
use Gen failed to start du to Grid bad voltage // He bypassed Grid and star=
ted Gen","system","7515","28-10-2024 21:06:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003434077","ELOUMDEM=
 CARRIERE 2","","28-10-2024 21:06:41","28-10-2024 20:57:14","28-10-2024 21:=
03:03","Cascaded Incident from TTO3324526","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation site went do=
wn because Gen failed to start du to Grid bad voltage // He bypassed Grid a=
nd started Gen","system","7513","28-10-2024 21:06:41","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003434061","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","28-10-2024 21:04:23","28-10-2024 20:57=
:14","28-10-2024 21:03:03","Grid fluctuation site went down because Gen fai=
led to start du to Grid bad voltage // He bypassed Grid and started Gen","F=
anda Brice","Grid Supply","Passive","Grid","National Grid - Phase Controlle=
r Faulty","Grid fluctuation site went down because Gen failed to start du t=
o Grid bad voltage // He bypassed Grid and started Gen","kamga.virgile@ihst=
owers.com","7511","28-10-2024 21:04:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0003433900","E=
toug ebe Meweulo","","28-10-2024 20:38:01","28-10-2024 20:21:55","28-10-202=
4 21:45:59","","Hyemafo Gildas","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Grid fluctuation, site went down because Gen=
 fails to start due to Grid bad voltage // he bypass Grid and manually star=
t the Gen","alexandre.kamal@ihstowers.com","967","28-10-2024 20:38:01","Sag=
emcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003433837","Lad=
a I Yde","","28-10-2024 20:28:06","28-10-2024 19:58:50","29-10-2024 00:20:1=
2","No power issue, site is on Gen with Ubaie=3D54,9V, Lionel adjep(6551848=
76) from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue,=
 site is on Gen with Ubaie=3D54,9V, Lionel adjep(655184876) from Huawei is =
informed","kamga.virgile@ihstowers.com","1756","28-10-2024 20:28:06","Sagem=
com CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003433819","AWA=
E OCM","","28-10-2024 20:25:26","28-10-2024 19:11:09","28-10-2024 19:46:18"=
,"Grid outage, site went down because Gen failed to start due to Battery ge=
n faulty// Gen manually started with External Battery","Mba Lazare Herve","=
Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid out=
age, site went down because Gen failed to start due to Battery gen faulty//=
 Gen manually started with External Battery","kamga.virgile@ihstowers.com",=
"4571","28-10-2024 20:25:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0003433743","Ngoulmek=
ong-Nord","","28-10-2024 20:11:50","28-10-2024 16:53:04","28-10-2024 17:03:=
39","Cascaded Incident from TTO3324154","Siligap Boris","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","no power issue on site   U=3D52.5=
V site on Grid THE TX  FME SYMPHORIEN (650257151)    from HUAWEI is informe=
d","system","11926","28-10-2024 20:11:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0003433730","E=
leveur","IHS_YND_277","28-10-2024 20:10:13","28-10-2024 16:53:04","29-10-20=
24 00:10:33","no power issue on site   U=3D52.5V site on Grid THE TX  FME S=
YMPHORIEN (650257151)    from HUAWEI is informed","Siligap Boris","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","no power issue on site   U=3D52.5V site on Grid THE TX  FME SYMPHORIEN (=
650257151)    from HUAWEI is informed","alexandre.kamal@ihstowers.com","118=
30","28-10-2024 20:10:13","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003433592","MBI=
MBIM","","28-10-2024 19:49:49","28-10-2024 19:33:35","28-10-2024 19:55:55",=
"site went down because gen start and stoppen due to water infiltration in =
tank // He purge the tank and gen start","Parker Tchoup","Fuel Outage (Prob=
able)","Passive","Diesel","Fuel Line Issue","site went down because gen sta=
rt and stoppen due to water infiltration in tank // He purge the tank and g=
en start","kamga.virgile@ihstowers.com","975","28-10-2024 19:49:49","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003433588","M=
aison-Blanche-IHS","","28-10-2024 19:48:17","28-10-2024 19:44:11","28-10-20=
24 20:17:16","Grid Outage No Space to Deploy a MDG// Grid power return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Ou=
tage No Space to Deploy a MDG// Grid power return","alexandre.kamal@ihstowe=
rs.com","246","28-10-2024 19:48:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003433557","O=
lembe-Terminus","","28-10-2024 19:42:40","28-10-2024 19:34:34","28-10-2024 =
21:24:57","site went down because the MPR dysfonction // he reset the MPR",=
"Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifier Distr=
ibution","site went down because the MPR dysfonction // he reset the MPR","=
alexandre.kamal@ihstowers.com","487","28-10-2024 19:42:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003433553","E=
ssomba","","28-10-2024 19:41:29","28-10-2024 19:26:22","28-10-2024 19:36:09=
","Active: No power issue, site is on Grid with Ubaie=3D54.2V, The fme tx G=
eorge //697461814//from Huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active: No power issue, site is on Grid with Ubaie=3D54.2V, The fme tx Geor=
ge //697461814//from Huawei is informed","alexandre.kamal@ihstowers.com","9=
09","28-10-2024 19:41:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003433547","N=
kolndongo","","28-10-2024 19:40:23","28-10-2024 19:27:20","28-10-2024 20:25=
:19","Grid outage site went down because main Gen faulty// Grid power retur=
n","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generato=
r Faulty","Grid outage site went down because main Gen faulty// Grid power =
return","alexandre.kamal@ihstowers.com","784","28-10-2024 19:40:23","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0003433535","Abang","=
","28-10-2024 19:39:31","28-10-2024 19:36:36","28-10-2024 22:00:12","Cascad=
ed Incident from TTO3323916","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because disjunction Cb(=
125A) faulty in PWC// He reamed Cb(125A),.Power issue resolved at OCM but r=
emains down at MTN George(697461814) from Huawei is infomed","system","175"=
,"28-10-2024 19:39:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0003433522","N=
kolangaa","IHS_YND_290","28-10-2024 19:36:46","28-10-2024 19:14:36","28-10-=
2024 22:00:24","site went down because disjunction Cb(125A) faulty in PWC//=
 He reamed Cb(125A),.Power issue resolved at OCM but remains down at MTN Ge=
orge(697461814) from Huawei is infomed","Mba Lazare Herve","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site =
went down because disjunction Cb(125A) faulty in PWC// He reamed Cb(125A),.=
Power issue resolved at OCM but remains down at MTN George(697461814) from =
Huawei is infomed","alexandre.kamal@ihstowers.com","1974","28-10-2024 19:36=
:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003433256","N=
kozoa","","28-10-2024 18:48:22","28-10-2024 18:38:16","28-10-2024 19:23:32"=
,"grid fluctuation and gen started, site went down due to disjunction Cb(63=
A) and cb(80A) in Pwc // He reamed cb","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","grid fl=
uctuation and gen started, site went down due to disjunction Cb(63A) and cb=
(80A) in Pwc // He reamed cb","alexandre.kamal@ihstowers.com","607","28-10-=
2024 18:48:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003432752","L=
abogenie","","28-10-2024 17:21:58","28-10-2024 17:13:48","28-10-2024 17:39:=
03","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space =
to deploy a MDG//Grid Restored","alexandre.kamal@ihstowers.com","491","28-1=
0-2024 17:21:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003432547","N=
yom OCM","","28-10-2024 16:44:08","28-10-2024 16:07:58","29-10-2024 02:10:4=
9","Active//No power issue  Ubaie:54.4 V   site on Grid, tx fme symphorien =
/650257151 from huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue  Ubaie:54.4 V   site on Grid, tx fme symphorien /650257151 fr=
om huawei is informed","christian.fonkou@ihstowers.com","2171","28-10-2024 =
16:44:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_424","NOCINC0003432535","Ossombe"=
,"","28-10-2024 16:42:00","28-10-2024 16:21:28","28-10-2024 17:15:18","Casc=
aded Incident from TTO3322706","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","load shedding, Hightemp on the GE  ,  w=
e topped up the water in the radiator","system","1232","28-10-2024 16:42:00=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003432379","M=
fou EPC","","28-10-2024 16:22:47","28-10-2024 16:15:40","28-10-2024 17:51:5=
8","Grid fluctuation, site went down because Gen fails to start due to Grid=
 bad voltage // he bypass Grid and manually start the Gen","Mba Lazare Herv=
e","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, site went down because Gen fails to start due to Grid b=
ad voltage // he bypass Grid and manually start the Gen","alexandre.kamal@i=
hstowers.com","428","28-10-2024 16:22:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0003432338","M=
bankomo IHS","","28-10-2024 16:14:46","28-10-2024 16:06:42","28-10-2024 16:=
50:35","Grid Outage Site went down because Gen started and stooped due to w=
ater infiltration in the tank//  He purged the tank, site on Gen","Fanda Br=
ice","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Wate=
r In The Fuel","Grid Outage Site went down because Gen started and stooped =
due to water infiltration in the tank//  He purged the tank, site on Gen","=
alexandre.kamal@ihstowers.com","484","28-10-2024 16:14:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0003432062","E=
mombo 2","","28-10-2024 15:44:41","28-10-2024 15:39:33","28-10-2024 16:09:5=
3","Grid Outage, site went down because CB (100 A) Batttery Backup Disjunte=
d in the PWC //He reamed the CB en Site is on Gen (deep investiguetion ongo=
ing)","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power C=
abinet - Circuit Breaker Issue","Grid Outage, site went down because CB (10=
0 A) Batttery Backup Disjunted in the PWC //He reamed the CB en Site is on =
Gen (deep investiguetion ongoing)","christian.fonkou@ihstowers.com","309","=
28-10-2024 15:44:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003431904","A=
ngongo","","28-10-2024 15:25:05","28-10-2024 15:15:59","28-10-2024 16:16:02=
","Site went down because Gen ran untill fuel shortage // Refueling done","=
Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Site went do=
wn because Gen ran untill fuel shortage // Refueling done","alexandre.kamal=
@ihstowers.com","547","28-10-2024 15:25:05","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003431892","AWA=
E OCM","","28-10-2024 15:23:17","28-10-2024 15:19:11","28-10-2024 15:55:58"=
,"Grid outage, site went down because Gen failed to start due to Battery Ge=
n faulty// Grid Restored","Mba Lazare Herve","Equipment Repair","Passive","=
ACDG Gen","ACDG - Generator Battery","Grid outage, site went down because G=
en failed to start due to Battery Gen faulty// Grid Restored","rouselle.sch=
oune@ihstowers.com","429","28-10-2024 15:23:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003431315","E=
kie-Elegance","","28-10-2024 13:52:24","28-10-2024 13:43:15","28-10-2024 13=
:45:31","No power issue site on grid with U=3D54.9v Erick(696422966) from Z=
TE is working on site ","Albran Byorel","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D54.9v Erick(696422966) from ZTE is working on site ","kouoh.j=
ean@ihstowers.com","550","28-10-2024 13:52:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003431087","S=
tade-Abega","","28-10-2024 13:13:42","28-10-2024 12:25:22","28-10-2024 12:2=
8:13","No power issue site on grid  with U=3D54.7v  Gregroire(697461814) fr=
om Huawei is informed ","Mba Lazare Herve","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on grid  with U=3D54.7v  Gregroire(697461814) from Huawei is informed ","ko=
uoh.jean@ihstowers.com","2901","28-10-2024 13:13:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003430900","Anguissa=
 New","","28-10-2024 12:48:01","28-10-2024 12:15:59","28-10-2024 12:59:15",=
"Cascaded Incident from TTO3320827","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage No space to deploy// G=
rid power return","system","1922","28-10-2024 12:48:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003430890","L=
abogenie","IHS_YND_568","28-10-2024 12:47:05","28-10-2024 12:15:59","28-10-=
2024 12:59:15","Grid outage No space to deploy// Grid power return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
 No space to deploy// Grid power return","christian.fonkou@ihstowers.com","=
1867","28-10-2024 12:47:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_510","NOCINC0003430868","MVAN SAC=
EL","","28-10-2024 12:43:40","28-10-2024 12:31:44","28-10-2024 12:45:40","C=
ascaded Incident from TTO3320793","MINKA NICOLAS","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went downn due to work our FME/=
Nicolas 656587607/ Sagemcom with Tx  Huawei Eric(697461814) for  installati=
on of a new breaker // End of Work","system","716","28-10-2024 12:43:40","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0003430863","M=
VAN","IHS_YND_510","28-10-2024 12:42:51","28-10-2024 12:31:44","28-10-2024 =
12:45:40","Site went downn due to work our FME/Nicolas 656587607/ Sagemcom =
with Tx  Huawei Eric(697461814) for  installation of a new breaker // End o=
f Work","MINKA NICOLAS","Installation Activity","Passive","Planned Activity=
","Installation Activity","Site went downn due to work our FME/Nicolas 6565=
87607/ Sagemcom with Tx  Huawei Eric(697461814) for  installation of a new =
breaker // End of Work","christian.fonkou@ihstowers.com","668","28-10-2024 =
12:42:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0003430792","S=
imbock OCM","","28-10-2024 12:32:48","28-10-2024 12:25:39","28-10-2024 12:5=
4:39","Grid fluctuation, site went down because gen fails to start due to g=
rid bad voltage // he bypass grid and manually start the gen","Hyemafo Gild=
as","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because gen fails to start due to grid =
bad voltage // he bypass grid and manually start the gen","christian.fonkou=
@ihstowers.com","430","28-10-2024 12:32:48","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003430476","Eko=
unou","","28-10-2024 11:38:12","28-10-2024 11:34:46","28-10-2024 11:44:15",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Grid power return","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery backup // Grid power return","rouselle.schoune@i=
hstowers.com","207","28-10-2024 11:38:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003429684","O=
lembe-Terminus","","28-10-2024 09:54:19","28-10-2024 09:13:12","28-10-2024 =
10:07:08","No ower issue site on grid with U=3D53.6v Symphorien(675295205) =
from Huawei is informed ","Fabrice Pouakam","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No ower issue site =
on grid with U=3D53.6v Symphorien(675295205) from Huawei is informed ","kou=
oh.jean@ihstowers.com","2468","28-10-2024 09:54:19","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003429655","NYO=
M FACE MAETUR","","28-10-2024 09:47:04","28-10-2024 09:46:59","28-10-2024 1=
3:30:32","grid fluctuations  with bad voltages, landlord has forbiden to st=
art the gen due to noise//grid good phse returned","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","grid fluctuation=
s  with bad voltages, landlord has forbiden to start the gen due to noise//=
grid good phse returned","landry.etame@ihstowers.com","6","28-10-2024 09:47=
:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003429653","B=
ATA-Mokolo","","28-10-2024 09:46:17","28-10-2024 07:55:08","28-10-2024 07:5=
8:33","No power issue site on grid with U=3D55.9v Brice Tsague(650214096) f=
rom Huawei is informed","","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D55.9v Brice Tsague(650214096) from Huawei is informed","kouoh.jean@ihsto=
wers.com","6670","28-10-2024 09:46:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003429393","N=
koabang","IHS_YND_295, IHS_YND_736","28-10-2024 09:04:07","27-10-2024 14:45=
:28","27-10-2024 15:20:23","Grid outage site went down because the Gen fail=
ed to start due to Hybrid system dysfonction // he reseyt the hybrid system=
 and Gen manually started","Mba Lazare Herve","Equipment Repair","Passive",=
"Hybrid","Hybrid Module","Grid outage site went down because the Gen failed=
 to start due to Hybrid system dysfonction // he reseyt the hybrid system a=
nd Gen manually started","kouoh.jean@ihstowers.com","65919","28-10-2024 09:=
04:07","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0003429244","Tsi=
nga village","","28-10-2024 08:27:25","28-10-2024 08:03:20","28-10-2024 09:=
09:14","Grid fluctuation site went down because Gen failed to start du to G=
rid bad voltage and RCP faulty // He bypassed Grid and started Gen","Delor =
Telezing","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation site went down because Gen failed to start du to =
Grid bad voltage and RCP faulty // He bypassed Grid and started Gen","landr=
y.etame@ihstowers.com","1446","28-10-2024 08:27:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003429228","L=
abogenie","","28-10-2024 08:26:02","28-10-2024 08:01:48","28-10-2024 08:10:=
48","","","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue, site is on grid with Ubaie=3D54,8V, E=
loundou (652586578) from Huawei is informed","kouoh.jean@ihstowers.com","14=
55","28-10-2024 08:26:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003427974","M=
fou EPC","","28-10-2024 02:43:55","28-10-2024 02:40:46","28-10-2024 04:45:4=
2","Grid outage, site went down because gen ran untill fuel shortage // ref=
ueling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage, site went down because gen ran untill fuel shortage // =
refueling done","ange.kongo@ihstowers.com","190","28-10-2024 02:43:55","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003427922","L=
abogenie","","28-10-2024 02:26:48","28-10-2024 02:20:37","28-10-2024 03:18:=
22","No power issue, site is on grid with Ubaie=3D54,8V, Eloundou (65258657=
8) from Huawei is informed","","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on grid =
with Ubaie=3D54,8V, Eloundou (652586578) from Huawei is informed","ange.kon=
go@ihstowers.com","371","28-10-2024 02:26:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003427124","N=
omayos-IHS","","27-10-2024 22:21:39","27-10-2024 22:17:14","27-10-2024 23:3=
8:10","Site went down due 2/4 rectifiers disfunction// He reset rectifiers,=
 Site on Grid","Fanda Brice","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due 2/4 rectifiers disfunction// He reset rec=
tifiers, Site on Grid","ange.kongo@ihstowers.com","266","27-10-2024 22:21:3=
9","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003426573","ELOUMDEM=
 CARRIERE 2","","27-10-2024 20:53:41","27-10-2024 20:42:22","27-10-2024 21:=
09:58","Cascaded Incident from TTO3315732","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because 5/8rec=
tifier disfunctionning//he reset the rectifier","system","679","27-10-2024 =
20:53:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003426572","Eto koss=
 Yde","","27-10-2024 20:53:40","27-10-2024 20:42:22","27-10-2024 21:09:58",=
"Cascaded Incident from TTO3315732","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because 5/8rectifier =
disfunctionning//he reset the rectifier","system","678","27-10-2024 20:53:4=
0","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003426571","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","27-10-2024 20:52:36","27-10-2024 20:42=
:22","27-10-2024 21:09:58","site went down because 5/8rectifier disfunction=
ning//he reset the rectifier","Fanda Brice","Equipment Repair","Passive","R=
ectifier","Rectifier Module","site went down because 5/8rectifier disfuncti=
onning//he reset the rectifier","olivier.kwedi@ihstowers.com","4681","27-10=
-2024 20:52:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003426561","E=
ssomba","","27-10-2024 20:51:16","27-10-2024 20:17:11","27-10-2024 21:11:49=
","Active: No power issue, site is on Grid with Ubaie=3D54.2V, The fme tx G=
eorge //697461814//from Huawei is informed. Notice that we have disjunction=
 at BTS OCM. Repetitive issue","Mba Lazare Herve","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No po=
wer issue, site is on Grid with Ubaie=3D54.2V, The fme tx George //69746181=
4//from Huawei is informed. Notice that we have disjunction at BTS OCM. Rep=
etitive issue","stephane.nkamwa@ihstowers.com","2047","27-10-2024 20:51:16"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0003426500","F=
ouda-New","","27-10-2024 20:38:44","27-10-2024 20:05:33","27-10-2024 20:50:=
03","Grid fluctuation, site went down because Gen failed to start due to Gr=
id bad voltage and RCP faulty//he bypassed Grid and Started Gen","Delor Tel=
ezing","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, site went down because Gen failed to start due to G=
rid bad voltage and RCP faulty//he bypassed Grid and Started Gen","stephane=
.nkamwa@ihstowers.com","1992","27-10-2024 20:38:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003426082","S=
tade-Abega","","27-10-2024 19:12:57","27-10-2024 19:02:50","27-10-2024 21:0=
0:04","Active//No power issue on site Ubaie=3D54.7V;  site on Grid.The FME =
George //697461814//  from Huawei is informed notice that disjunction of CB=
 in BTS Ocm","Mba Lazare Herve","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site =
Ubaie=3D54.7V;  site on Grid.The FME George //697461814//  from Huawei is i=
nformed notice that disjunction of CB in BTS Ocm","stephane.nkamwa@ihstower=
s.com","608","27-10-2024 19:12:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003426032","Eto koss=
 Yde","","27-10-2024 19:05:30","27-10-2024 19:00:12","27-10-2024 19:04:06",=
"Cascaded Incident from TTO3315091","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation site went down beca=
use Gen failed to start du to Grid bad voltage // He bypassed Grid and star=
ted Gen","system","318","27-10-2024 19:05:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003426027","MEF=
OU ASSI","IHS_YND_737","27-10-2024 19:04:19","27-10-2024 19:00:12","27-10-2=
024 19:04:06","Grid fluctuation site went down because Gen failed to start =
du to Grid bad voltage // He bypassed Grid and started Gen","Fanda Brice","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation site went down because Gen failed to start du to Grid bad vo=
ltage // He bypassed Grid and started Gen","olivier.kwedi@ihstowers.com","2=
48","27-10-2024 19:04:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0003425957","S=
AA 2","","27-10-2024 18:49:45","27-10-2024 18:31:32","27-10-2024 22:40:13",=
"Site went down because 03/03 rectifiers faulty due to lightning //He repla=
ced rectifiers faulty, power issue resolved  10:40 PM ,but BTS OCM still do=
wn after power reset done ,The TX FME Gr=E9goire(6545","Parker Tchoup","For=
ce Majeure","Natural Disaster","Thunderstrike","Equipment Damaged","Site we=
nt down because 03/03 rectifiers faulty due to lightning //He replaced rect=
ifiers faulty, power issue resolved  10:40 PM ,but BTS OCM still down after=
 power reset done ,The TX FME Gr=E9goire(654547479) from Huawei is informed=
","stephane.nkamwa@ihstowers.com","1093","27-10-2024 18:49:45","Sagemcom CM=
R"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0003425833","Ako=
k Ndoe Yde","","27-10-2024 18:21:38","27-10-2024 18:05:32","27-10-2024 18:4=
3:46","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"olivier.kwedi@ihstowers.com","967","27-10-2024 18:21:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0003425303","N=
goum","","27-10-2024 16:59:46","27-10-2024 16:36:38","27-10-2024 17:05:56",=
"No power issue site on Solar with U=3D51V,  tx fme Gregoire (654547479) fr=
om Huawei informed","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on Sola=
r with U=3D51V,  tx fme Gregoire (654547479) from Huawei informed","stephan=
e.nkamwa@ihstowers.com","1389","27-10-2024 16:59:46","Sagemcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0003424875","ODZ=
A BORNE 10","","27-10-2024 16:02:26","27-10-2024 15:53:15","27-10-2024 16:4=
6:08","site went down because the 01/03 rectifier on site Dysfonction // he=
 reset the rectifier","Albran Byorel","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","site went down because the 01/03 rectifier on site =
Dysfonction // he reset the rectifier","olivier.kwedi@ihstowers.com","552",=
"27-10-2024 16:02:26","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003424694","Nko=
londom","","27-10-2024 15:42:05","27-10-2024 15:27:59","27-10-2024 20:09:23=
","Site went down because Gen failed to start due to Grid bad voltage // He=
 bypass th egarid site on Gen","Fabrice Pouakam","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Site went down because Gen =
failed to start due to Grid bad voltage // He bypass th egarid site on Gen"=
,"olivier.kwedi@ihstowers.com","900","27-10-2024 15:42:05","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003424656","Eko=
unou","","27-10-2024 15:38:36","27-10-2024 15:29:06","27-10-2024 15:37:52",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Grid power return","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery backup // Grid power return","olivier.kwedi@ihst=
owers.com","571","27-10-2024 15:38:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003424272","N=
GONA","","27-10-2024 14:53:39","27-10-2024 14:45:28","27-10-2024 15:20:23",=
"site coupe par Nkoabang ctr_084, svp cr=E9=E9 le ticket et cascad=E9","Mba=
 Lazare Herve","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid outage site went down because the Gen failed to start due to Hybri=
d system dysfonction // he reseyt the hybrid system and Gen manually starte=
d","stephane.nkamwa@ihstowers.com","66015","27-10-2024 14:53:39","Sagemcom =
CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003424061","ODZ=
A CITE MBIA","","27-10-2024 14:17:13","27-10-2024 14:09:02","27-10-2024 16:=
33:55"," grid OUTAGE, site went down because gen fails to start due to ATS =
disfunctionning // Gen manually start","Albran Byorel","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue"," grid OUTAGE, site went down beca=
use gen fails to start due to ATS disfunctionning // Gen manually start","o=
livier.kwedi@ihstowers.com","491","27-10-2024 14:17:13","Sagemcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003424040","Mes=
sa Carriere","","27-10-2024 14:13:24","27-10-2024 13:13:14","27-10-2024 13:=
26:55","site went down because  Start failure due to grid fluctuation // gr=
id stabilized","Mboua Thierry","Grid Supply","Passive","Grid","National Gri=
d - Phase Controller Faulty","site went down because  Start failure due to =
grid fluctuation // grid stabilized","kamga.virgile@ihstowers.com","3610","=
27-10-2024 14:13:24","Sagemcom CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0003424036","ETO=
UDI CHAPELLE","","27-10-2024 14:11:53","27-10-2024 13:03:39","27-10-2024 13=
:19:53","Grid outage, site went down before gen start due to poor battery b=
ackup // Grid power return","Delor Telezing","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // Grid power return","kamga.vir=
gile@ihstowers.com","4095","27-10-2024 14:11:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003423976","T=
singa","","27-10-2024 14:01:57","27-10-2024 13:55:45","27-10-2024 14:20:00"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Grid power return","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before ge=
n start due to poor battery backup // Grid power return","alexandre.kamal@i=
hstowers.com","373","27-10-2024 14:01:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003423964","M=
aison-Blanche-IHS","","27-10-2024 14:00:07","27-10-2024 13:52:58","27-10-20=
24 14:50:16","grid outage, no space to deploy // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","grid outage, no s=
pace to deploy // Grid return","alexandre.kamal@ihstowers.com","430","27-10=
-2024 14:00:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003423954","E=
ssomba","","27-10-2024 13:58:21","27-10-2024 13:10:17","27-10-2024 13:25:49=
","No power issue on site ,site on Grid with Ubaie=3D54.1 V The fme tx HUGO=
/ 672390202 from Huawei is informed. Notice that we have disjunction at BTS=
 Ocm","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue on site ,site on Grid w=
ith Ubaie=3D54.1 V The fme tx HUGO/ 672390202 from Huawei is informed. Noti=
ce that we have disjunction at BTS Ocm","alexandre.kamal@ihstowers.com","29=
22","27-10-2024 13:58:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003423923","B=
astos Bethesda","","27-10-2024 13:52:43","27-10-2024 13:34:37","27-10-2024 =
14:56:30","grid outage, gen start and stopped with alarm 'Hight temp' // He=
 added water and manually start the gen","Mboua Thierry","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","grid=
 outage, gen start and stopped with alarm 'Hight temp' // He added water an=
d manually start the gen","alexandre.kamal@ihstowers.com","1087","27-10-202=
4 13:52:43","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0003423833","Eko=
umdoum OCM","","27-10-2024 13:39:33","27-10-2024 13:27:54","27-10-2024 13:4=
1:49","Grid fluctuation, site went down because gen start and stopped due t=
o grid bad voltage // grid stabilized","Albran Byorel","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, sit=
e went down because gen start and stopped due to grid bad voltage // grid s=
tabilized","kamga.virgile@ihstowers.com","700","27-10-2024 13:39:33","Sagem=
com CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0003423828","Mes=
sassi 2","","27-10-2024 13:37:28","27-10-2024 13:16:20","27-10-2024 15:18:5=
5","Gen stopped due to Grid poawer return site went down because the Grid c=
ontactor dysfonction // He blocked Grid contactor, site on Grid ","Fabrice =
Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gen =
stopped due to Grid poawer return site went down because the Grid contactor=
 dysfonction // He blocked Grid contactor, site on Grid ","kamga.virgile@ih=
stowers.com","1269","27-10-2024 13:37:28","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003423795","MIM=
BOMAN LIBERTE","","27-10-2024 13:31:52","27-10-2024 13:06:33","27-10-2024 1=
3:26:16","Grid outage ,site went down because Main Gen faulty //Grid return=
","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid outage ,site went down because Main Gen faulty //Grid ret=
urn","kamga.virgile@ihstowers.com","1520","27-10-2024 13:31:52","Sagemcom C=
MR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0003423680","An-=
Marche-Melen","","27-10-2024 13:18:45","27-10-2024 12:52:31","27-10-2024 13=
:26:03","Grid outage, No Space to deploy a Mobil Gen  //  Grid Restored",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, No Space to deploy a Mobil Gen  //  Grid Restored","kamga.virgile@ih=
stowers.com","1575","27-10-2024 13:18:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003423662","B=
iteng-Maetur","","27-10-2024 13:14:37","27-10-2024 12:57:18","27-10-2024 13=
:35:49","grid outage, site went down because gen failed to started due to g=
en Overload(20kva, 280A)// He reduced the load and gen manually started","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"grid outage, site went down because gen failed to started due to gen Overl=
oad(20kva, 280A)// He reduced the load and gen manually started","alexandre=
.kamal@ihstowers.com","1040","27-10-2024 13:14:37","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003423647","Pha=
rmacie SION","","27-10-2024 13:12:35","27-10-2024 12:36:23","27-10-2024 13:=
22:12","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automaticaly","Paul BIBOUM","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen start automaticaly","kam=
ga.virgile@ihstowers.com","2172","27-10-2024 13:12:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003423645","Nsimalen=
 OCM","","27-10-2024 13:12:00","27-10-2024 11:48:14","27-10-2024 13:50:51",=
"Cascaded Incident from TTO3312249","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, site went down becaus=
e gen start and stoppen with  alarm over frequency // He reset gen card and=
 adjust the frequencies","system","5026","27-10-2024 13:12:00","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003423639","N=
kolda","IHS_YND_327","27-10-2024 13:10:20","27-10-2024 11:48:14","27-10-202=
4 13:50:51","grid outage, site went down because gen start and stoppen with=
  alarm over frequency // He reset gen card and adjust the frequencies","Al=
bran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Over Frequency=
","grid outage, site went down because gen start and stoppen with  alarm ov=
er frequency // He reset gen card and adjust the frequencies","alexandre.ka=
mal@ihstowers.com","4927","27-10-2024 13:10:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003423633","O=
lembe-Terminus","","27-10-2024 13:08:48","27-10-2024 12:46:43","27-10-2024 =
14:43:05","Grid outage site went down because the Gen failed to start// Gri=
d power return (investigation ongoing)","Fabrice Pouakam","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down b=
ecause the Gen failed to start// Grid power return (investigation ongoing)"=
,"alexandre.kamal@ihstowers.com","1326","27-10-2024 13:08:48","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003423627","C=
RH-Etoug-Ebe","","27-10-2024 13:07:29","27-10-2024 12:46:43","28-10-2024 09=
:48:44","Tx Issue : site on grid,Ubaie:52V; Mohamadou/691-14-44-35 is infor=
med,and confirmed that: There was Disjuntion in the side of OCM.","Hyemafo =
Gildas","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Tx Issue : site on grid,Ubaie:52V; Mohamadou/691-14-44-=
35 is informed,and confirmed that: There was Disjuntion in the side of OCM.=
","alexandre.kamal@ihstowers.com","68256","27-10-2024 13:07:29","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0003423618","FOUGEROL=
E","","27-10-2024 13:05:50","27-10-2024 12:44:51","27-10-2024 14:18:09","Ca=
scaded Incident from TTO3312202","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down because g=
en fails to start due to gen card faulty // gen start manually","system","1=
259","27-10-2024 13:05:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003423604","Afanoya"=
,"","27-10-2024 13:02:21","27-10-2024 12:11:57","27-10-2024 13:29:48","Casc=
aded Incident from TTO3312193","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, DG Failed to start d=
ue to overload (20Kva, 300A),and poor batteries backup // grid return","sys=
tem","3024","27-10-2024 13:02:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003423603","MBALNGON=
G LYCEE","","27-10-2024 13:02:21","27-10-2024 12:11:57","27-10-2024 13:29:4=
8","Cascaded Incident from TTO3312193","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation, DG Failed to st=
art due to overload (20Kva, 300A),and poor batteries backup // grid return"=
,"system","3024","27-10-2024 13:02:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003423602","ELOUMDEM=
 CARRIERE","","27-10-2024 13:02:20","27-10-2024 12:11:57","27-10-2024 13:29=
:48","Cascaded Incident from TTO3312193","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation, DG Failed to =
start due to overload (20Kva, 300A),and poor batteries backup // grid retur=
n","system","3023","27-10-2024 13:02:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0003423601","N=
gousso-Savana","IHS_YND_561","27-10-2024 13:02:04","27-10-2024 12:44:51","2=
7-10-2024 14:18:09","Grid outage, site went down because gen fails to start=
 due to gen card faulty // gen start manually","Siligap Boris","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
, site went down because gen fails to start due to gen card faulty // gen s=
tart manually","alexandre.kamal@ihstowers.com","1033","27-10-2024 13:02:04"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0003423593","K=
ondengui","","27-10-2024 13:00:51","27-10-2024 12:43:40","27-10-2024 13:38:=
35","Grid outage,Gen stopped with alarm high temp//he added water in radiat=
or","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High En=
gine Temp - Coolant Level Issue","Grid outage,Gen stopped with alarm high t=
emp//he added water in radiator","alexandre.kamal@ihstowers.com","1032","27=
-10-2024 13:00:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003423585","Nkolfoul=
ou 2","","27-10-2024 13:00:00","27-10-2024 12:42:11","27-10-2024 13:54:08",=
"Cascaded Incident from TTO3312174","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen fails to start due to gen card faulty // gen start manually","system"=
,"1069","27-10-2024 13:00:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003423577","N=
kolfoulou","IHS_YND_278","27-10-2024 12:59:19","27-10-2024 12:42:11","27-10=
-2024 13:54:08","Grid outage, site went down because gen fails to start due=
 to gen card faulty // gen start manually","Siligap Boris","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down because gen fails to start due to gen card faulty // gen start=
 manually","alexandre.kamal@ihstowers.com","1028","27-10-2024 12:59:19","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003423560","Bas=
tos Amb Coree","","27-10-2024 12:56:57","27-10-2024 12:04:49","27-10-2024 1=
4:50:16","Grid Outage No Space to Deploy a MDG // Grid Restored","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No=
 Space to Deploy a MDG // Grid Restored","kamga.virgile@ihstowers.com","312=
9","27-10-2024 12:56:57","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003423530","Feb=
e Village","","27-10-2024 12:53:29","27-10-2024 12:01:19","27-10-2024 13:43=
:38","Grid outage,site went down because gen start and stoppen with alarm u=
nder voltage // He reduced the load and gen manually started","Mboua Thierr=
y","Equipment Repair","Passive","ACDG Gen","ACDG - Under Voltage","Grid out=
age,site went down because gen start and stoppen with alarm under voltage /=
/ He reduced the load and gen manually started","kamga.virgile@ihstowers.co=
m","3131","27-10-2024 12:53:29","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003423517","San=
ta Barbara Gottam","","27-10-2024 12:52:02","27-10-2024 11:51:55","27-10-20=
24 14:35:56","Site went down due to PWC dysfonctioning ( Batteries Backup a=
larming ; PWC FNS)//Reset Batteries Backup,site on Grid.","Delor Telezing",=
"Equipment Repair","Passive","Rectifier","Rectifier - Controller Failure","=
Site went down due to PWC dysfonctioning ( Batteries Backup alarming ; PWC =
FNS)//Reset Batteries Backup,site on Grid.","kamga.virgile@ihstowers.com","=
3608","27-10-2024 12:52:02","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003423506","Mok=
olo Yaounde","","27-10-2024 12:50:39","27-10-2024 11:51:24","27-10-2024 14:=
52:35","Grid Outage No Space to Deploy a MDG // Grid Restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No S=
pace to Deploy a MDG // Grid Restored","kamga.virgile@ihstowers.com","3556"=
,"27-10-2024 12:50:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003423435","O=
dza II OCM","","27-10-2024 12:43:45","27-10-2024 11:51:40","27-10-2024 13:4=
6:11","Grid outage, site went down before gen start due to poor battery bac=
kup // gen manually started","Albran Byorel","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // gen manually started","alexan=
dre.kamal@ihstowers.com","3126","27-10-2024 12:43:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003423385","Emana ly=
cee 2","","27-10-2024 12:38:42","27-10-2024 12:32:28","27-10-2024 13:28:36"=
,"Cascaded Incident from TTO3311955","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid fluctuation and gen starte=
d, site went down due to disjunction  Cb(2*80A) in Pwc // He reamed cb(2*80=
A), site on grid","system","373","27-10-2024 12:38:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003423383","Emana Ly=
cee","","27-10-2024 12:38:41","27-10-2024 12:32:28","27-10-2024 13:28:36","=
Cascaded Incident from TTO3311955","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid fluctuation and gen started,=
 site went down due to disjunction  Cb(2*80A) in Pwc // He reamed cb(2*80A)=
, site on grid","system","373","27-10-2024 12:38:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003423382","EMANA BI=
LICK CITY","","27-10-2024 12:38:41","27-10-2024 12:32:28","27-10-2024 13:28=
:36","Cascaded Incident from TTO3311955","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid fluctuation and gen st=
arted, site went down due to disjunction  Cb(2*80A) in Pwc // He reamed cb(=
2*80A), site on grid","system","373","27-10-2024 12:38:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003423381","Mballa 4=
","","27-10-2024 12:38:41","27-10-2024 12:32:28","27-10-2024 13:28:36","Cas=
caded Incident from TTO3311955","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid fluctuation and gen started, sit=
e went down due to disjunction  Cb(2*80A) in Pwc // He reamed cb(2*80A), si=
te on grid","system","373","27-10-2024 12:38:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003423384","Messassi=
 okolo","","27-10-2024 12:38:41","27-10-2024 12:32:28","27-10-2024 13:28:36=
","Cascaded Incident from TTO3311955","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid fluctuation and gen start=
ed, site went down due to disjunction  Cb(2*80A) in Pwc // He reamed cb(2*8=
0A), site on grid","system","373","27-10-2024 12:38:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003423373","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","27=
-10-2024 12:37:33","27-10-2024 12:32:28","27-10-2024 13:28:36","grid fluctu=
ation and gen started, site went down due to disjunction  Cb(2*80A) in Pwc =
// He reamed cb(2*80A), site on grid","Fabrice Pouakam","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","grid flu=
ctuation and gen started, site went down due to disjunction  Cb(2*80A) in P=
wc // He reamed cb(2*80A), site on grid","alexandre.kamal@ihstowers.com","3=
06","27-10-2024 12:37:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003423355","M=
ANGUIERS CHAPELLE","","27-10-2024 12:34:45","27-10-2024 12:31:38","27-10-20=
24 17:20:43","site went down because the Cb(125A) and Cb(80A) dysjoncted du=
e to load increased on site// He reamed the cb","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue"=
,"site went down because the Cb(125A) and Cb(80A) dysjoncted due to load in=
creased on site// He reamed the cb","alexandre.kamal@ihstowers.com","188","=
27-10-2024 12:34:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003423344","E=
bogo","","27-10-2024 12:33:02","27-10-2024 12:29:55","27-10-2024 12:56:47",=
"Grid outage, site went down because gen fails to start due to gen card fau=
lty // gen start automatically","Siligap Boris","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n because gen fails to start due to gen card faulty // gen start automatica=
lly","alexandre.kamal@ihstowers.com","188","27-10-2024 12:33:02","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003423339","E=
lig Edzoa","","27-10-2024 12:32:00","27-10-2024 12:29:55","27-10-2024 13:03=
:04","Grid outage, site went down before gen start due to poor battery back=
up // Gen started automaticaly","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen started automaticaly"=
,"alexandre.kamal@ihstowers.com","126","27-10-2024 12:32:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003423326","H=
-Progres","","27-10-2024 12:30:23","27-10-2024 12:09:12","27-10-2024 14:49:=
36","Grid Outage No Space to Deploy a MDG // Grid Restored","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spac=
e to Deploy a MDG // Grid Restored","alexandre.kamal@ihstowers.com","1272",=
"27-10-2024 12:30:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0003423322","S=
apeur Mimboman","","27-10-2024 12:29:25","27-10-2024 12:10:07","27-10-2024 =
13:05:34","grid outage, site went down because gen failed to start due to g=
en card faulty // gen manually started","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","grid outage, site went down=
 because gen failed to start due to gen card faulty // gen manually started=
","alexandre.kamal@ihstowers.com","1159","27-10-2024 12:29:25","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003423314","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","27-10-2024 12:28:17","27-10-=
2024 12:10:57","27-10-2024 13:29:48","Grid fluctuation, DG Failed to start =
due to overload (20Kva, 300A),and poor batteries backup // grid return","Hy=
emafo Gildas","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Battery Low","Grid fluctuation, DG Failed to start due to overload (20Kva,=
 300A),and poor batteries backup // grid return","alexandre.kamal@ihstowers=
.com","1041","27-10-2024 12:28:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003422954","L=
abogenie","","27-10-2024 11:50:59","27-10-2024 11:42:39","27-10-2024 20:00:=
32","Active//No power isssue, site is on grid with Ubaie=3D54,8V,The FME Ge=
orge (697461814) from Huawei is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power i=
sssue, site is on grid with Ubaie=3D54,8V,The FME George (697461814) from H=
uawei is informed","alexandre.kamal@ihstowers.com","502","27-10-2024 11:50:=
59","Sagemcom CMR"
"Cancelled","Warning","T1232","IHS_YND_792","NOCINC0003422694","NKOABANG NK=
OLO 3","","27-10-2024 11:14:38","","","","Mba Lazare Herve","","","","","",=
"ludovic.tchagna@ihstowers.com","248","27-10-2024 11:14:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003422636","M=
imboman-Village","","27-10-2024 11:05:08","27-10-2024 10:59:02","27-10-2024=
 11:05:32","No power issue on site ,site on Grid with Ubaie=3D52,1 V The Tx=
 FME Eloundou(693212405) from Huawei is informed","Mba Lazare Herve","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site ,site on Grid with Ubaie=3D52,1 V The Tx FME E=
loundou(693212405) from Huawei is informed","alexandre.kamal@ihstowers.com"=
,"367","27-10-2024 11:05:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003422617","Yoko OCM=
","","27-10-2024 11:02:41","27-10-2024 10:48:21","27-10-2024 10:49:21","Cas=
caded Incident from TTO3311075","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 49.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","860","27-10-2024 11:02:41","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003422618","Ngouetou=
","","27-10-2024 11:02:41","27-10-2024 10:48:21","27-10-2024 10:49:21","Cas=
caded Incident from TTO3311075","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 49.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","860","27-10-2024 11:02:41","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003422619","MBIMBIM"=
,"","27-10-2024 11:02:41","27-10-2024 10:48:21","27-10-2024 10:49:21","Casc=
aded Incident from TTO3311075","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
49.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","860","27-10-2024 11:02:41","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003422616","Matsari"=
,"","27-10-2024 11:02:41","27-10-2024 10:48:21","27-10-2024 10:49:21","Casc=
aded Incident from TTO3311075","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
49.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","860","27-10-2024 11:02:41","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003422615","Ngoum","=
","27-10-2024 11:02:40","27-10-2024 10:48:21","27-10-2024 10:49:21","Cascad=
ed Incident from TTO3311075","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Gen with U =3D 49=
.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959647=
of Huawei is informed","system","859","27-10-2024 11:02:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003422391","O=
lembe","","27-10-2024 10:28:52","27-10-2024 10:20:48","27-10-2024 10:38:55"=
,"Grid outage, site went down because gen ran untill fuel shortage // refue=
ling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage, site went down because gen ran untill fuel shortage // ref=
ueling done","alexandre.kamal@ihstowers.com","485","27-10-2024 10:28:52","S=
agemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003420713","OBA=
M NGOLA OCM","","27-10-2024 05:34:50","27-10-2024 05:31:43","27-10-2024 05:=
37:13","site went down due to insufficient (03) rectifier on site//site sta=
bilized(need to change the faulty rectifier)","MINKA NICOLAS","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","site went down due to insuf=
ficient (03) rectifier on site//site stabilized(need to change the faulty r=
ectifier)","emmanuel.ghani@ihstowers.com","188","27-10-2024 05:34:50","Sage=
mcom CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0003420533","Oko=
la","IHS_YND_530, IHS_YND_390","27-10-2024 04:20:51","27-10-2024 04:19:10",=
"27-10-2024 07:17:53","Grid outage, site went down because Gen start and st=
opped with Over Voltage alarm // He Resent the Gen Card and Manually Starte=
d the Gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage, site went down because Gen start an=
d stopped with Over Voltage alarm // He Resent the Gen Card and Manually St=
arted the Gen","emmanuel.ghani@ihstowers.com","101","27-10-2024 04:20:51","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003419693","N=
yom OCM","","26-10-2024 23:39:03","26-10-2024 23:30:59","27-10-2024 00:20:5=
1","Active//No power issue  Ubaie:54.4 V   site on Grid, tx fme symphorien =
/650257151 from huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue  Ubaie:54.4 V   site on Grid, tx fme symphorien /650257151 fr=
om huawei is informed","joelle.ekessi@ihstowers.com","485","26-10-2024 23:3=
9:03","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003419533","Nko=
lbisson usines des eaux 2","","26-10-2024 23:07:29","26-10-2024 23:03:24","=
26-10-2024 23:50:25","No power issue on site U=3D52,7v site on grid Mohamad=
ou/691144435 of huawei is informed and up at 11:09 PM","TIENTCHEU NZETCHIEU=
 GAEL","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site U=3D52,7v site on grid Mohamadou/=
691144435 of huawei is informed and up at 11:09 PM","emmanuel.ghani@ihstowe=
rs.com","246","26-10-2024 23:07:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003419310","O=
lembe-Terminus","","26-10-2024 22:38:17","26-10-2024 22:34:13","26-10-2024 =
23:40:38","Site went down due to MPR disfunction// He reset rectifiers (MPR=
 to be replace)","Fabrice Pouakam","Equipment Repair","Passive","Rectifier"=
,"Rectifier Distribution","Site went down due to MPR disfunction// He reset=
 rectifiers (MPR to be replace)","joelle.ekessi@ihstowers.com","245","26-10=
-2024 22:38:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003419202","M=
IMBOMAN LIBERTE","","26-10-2024 22:19:42","26-10-2024 22:04:37","26-10-2024=
 23:31:51","Site went down because to CB(63A) tripped in PWC who feeds equi=
pment OCM // CB put back on","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down b=
ecause to CB(63A) tripped in PWC who feeds equipment OCM // CB put back on"=
,"joelle.ekessi@ihstowers.com","906","26-10-2024 22:19:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0003419048","T=
SINGA VILLAGE 2","","26-10-2024 21:58:14","26-10-2024 21:32:01","26-10-2024=
 22:48:59","Site went down because to CB(125A) tripped in PWC who feeds equ=
ipment OCM // CB put back on","Delor Telezing","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down be=
cause to CB(125A) tripped in PWC who feeds equipment OCM // CB put back on"=
,"ange.kongo@ihstowers.com","1574","26-10-2024 21:58:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003418377","N=
kozoa","","26-10-2024 20:20:24","26-10-2024 19:54:14","26-10-2024 20:32:54"=
,"Grid outage, site went down due to gen overload(20KVA, 305A) // he reduic=
ed the load and started Gen manually","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down due to =
gen overload(20KVA, 305A) // he reduiced the load and started Gen manually"=
,"ange.kongo@ihstowers.com","1571","26-10-2024 20:20:24","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0003418338","Aka=
k-Nkozoa-MTN-IHS","","26-10-2024 20:13:47","26-10-2024 20:08:34","26-10-202=
4 22:03:55","Grid bad voltage, site went down because Gen failed to start d=
ue to Grid bad voltage and RCP faulty//he bypassed Grid and Started Gen","F=
abrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid bad voltage, site went down because Gen failed to start=
 due to Grid bad voltage and RCP faulty//he bypassed Grid and Started Gen",=
"denis.mballa@ihstowers.com","314","26-10-2024 20:13:47","Sagemcom CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0003418304","SOA=
 VILLAGE","","26-10-2024 20:07:56","26-10-2024 19:58:42","26-10-2024 20:29:=
48","Site went down because the Huawei module malfunctioned // he reset it =
and site on gen","Siligap Boris","Equipment Repair","Passive","Control Pane=
l","Panel Distribution Board","Site went down because the Huawei module mal=
functioned // he reset it and site on gen","denis.mballa@ihstowers.com","55=
4","26-10-2024 20:07:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003417917","M=
elen Ba'aba","","26-10-2024 19:01:50","26-10-2024 18:59:33","26-10-2024 19:=
11:34","Grid fluctuation, site went down before gen start due to poor batte=
ry backup // Gen start automaticaly","Siligap Boris","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid fluctuation, sit=
e went down before gen start due to poor battery backup // Gen start automa=
ticaly","ange.kongo@ihstowers.com","138","26-10-2024 19:01:50","Sagemcom CM=
R"
"Closed Complete","Warning","CTR_315","IHS_YND_292","NOCINC0003417789","Bit=
oto","","26-10-2024 18:39:42","","","site alarm due to 01 rectifier faulty,=
 he added 01 rectifier, site on grid","Mba Lazare Herve","Warning","Warning=
","POWER","Warning - Rectifier Failure","site alarm due to 01 rectifier fau=
lty, he added 01 rectifier, site on grid","ange.kongo@ihstowers.com","4","2=
6-10-2024 18:39:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003417783","M=
ini-Ferme","","26-10-2024 18:38:43","26-10-2024 18:33:38","26-10-2024 18:45=
:53","grid outage, no space to deploy a mobile gen// grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, =
no space to deploy a mobile gen// grid return","ange.kongo@ihstowers.com","=
306","26-10-2024 18:38:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003417478","N=
kolfon Cimencam","","26-10-2024 18:05:53","26-10-2024 18:04:48","26-10-2024=
 18:10:48","Active//No power issue on site U=3D54,5v site on Gen The Rm Ala=
in (691144423) of huawei is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue on site U=3D54,5v site on Gen The Rm Alain (691144423) of hu=
awei is informed","ange.kongo@ihstowers.com","65","26-10-2024 18:05:53","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003416937","O=
lembe-Terminus","","26-10-2024 17:40:44","26-10-2024 17:34:35","26-10-2024 =
21:45:35","Site went down due to insufficient of rectifier// he reduice the=
 load","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","Site went down due to insufficient of rectifier// he reduice the=
 load","ange.kongo@ihstowers.com","370","26-10-2024 17:40:44","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0003416446","S=
apeur","","26-10-2024 16:51:51","26-10-2024 16:47:44","26-10-2024 16:57:44"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen start automatically","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start automatically","ange.=
kongo@ihstowers.com","249","26-10-2024 16:51:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003416391","Afanoya"=
,"","26-10-2024 16:42:31","26-10-2024 16:39:52","26-10-2024 16:57:04","Casc=
aded Incident from TTO3303793","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Gen start automaticaly","system","159"=
,"26-10-2024 16:42:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003416390","ELOUMDEM=
 CARRIERE","","26-10-2024 16:42:30","26-10-2024 16:39:52","26-10-2024 16:57=
:04","Cascaded Incident from TTO3303793","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start automaticaly","system=
","158","26-10-2024 16:42:30","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003416352","Aha=
la","IHS_YND_767, IHS_YND_313","26-10-2024 16:41:04","26-10-2024 16:39:52",=
"26-10-2024 16:57:04","site was on gen due to grid outage,site went down du=
e to gen overload (20Kva, 300A) // He reduced the load and started Gen manu=
ally.","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","site was on gen due to grid outage,site went down due to gen overlo=
ad (20Kva, 300A) // He reduced the load and started Gen manually.","denis.m=
balla@ihstowers.com","73","26-10-2024 16:41:04","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003416255","Eko=
unou","","26-10-2024 16:17:48","26-10-2024 16:13:37","26-10-2024 16:21:21",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","denis.=
mballa@ihstowers.com","252","26-10-2024 16:17:48","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003416189","ODZ=
A CITE MBIA","","26-10-2024 16:08:09","26-10-2024 16:05:56","26-10-2024 16:=
49:10","grid outage, site went down because gen failed to start due to dysf=
unctioning ATS // Gen manually started","Albran Byorel","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Kick Starter","grid outage, site went down bec=
ause gen failed to start due to dysfunctioning ATS // Gen manually started"=
,"denis.mballa@ihstowers.com","133","26-10-2024 16:08:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003415963","N=
kolndongo","","26-10-2024 15:32:13","26-10-2024 15:21:08","26-10-2024 15:33=
:08","Grid outage site went down because mains Gen faulty //MDG 20kva deplo=
yed","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid outage site went down because mains Gen faulty //MDG 20kv=
a deployed","ange.kongo@ihstowers.com","666","26-10-2024 15:32:13","Sagemco=
m CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0003415800","Odz=
a petit marche new","","26-10-2024 15:12:06","26-10-2024 15:05:56","26-10-2=
024 16:19:56","grid outage,gen failed to start due to grid bad voltage,no r=
cp//he did a bridge on good phase","Albran Byorel","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","grid outage,gen failed to=
 start due to grid bad voltage,no rcp//he did a bridge on good phase","deni=
s.mballa@ihstowers.com","370","26-10-2024 15:12:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003415554","S=
tade-Abega","","26-10-2024 14:58:33","26-10-2024 14:51:27","26-10-2024 15:5=
9:55","grid outage, site went down because gen failed to start due to prehe=
ating candle faulty // gen manually started","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Kick Starter","grid outage, site went =
down because gen failed to start due to preheating candle faulty // gen man=
ually started","ange.kongo@ihstowers.com","427","26-10-2024 14:58:33","Sage=
mcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003415489","Nko=
abang Ebolmedjock","","26-10-2024 14:49:50","26-10-2024 14:44:40","26-10-20=
24 15:02:40","grid outage, gen start and stopped with alarm 'Low oil pressu=
re' // He added oil pressure, site on gen","Mba Lazare Herve","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Low Oil Pressure","grid outage, gen star=
t and stopped with alarm 'Low oil pressure' // He added oil pressure, site =
on gen","denis.mballa@ihstowers.com","310","26-10-2024 14:49:50","Sagemcom =
CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003415452","N=
yanon","","26-10-2024 14:45:22","26-10-2024 14:35:14","26-10-2024 16:42:05"=
,"Active//No power issue on site ,site on Gen with Ubaie=3D53V, Tx Fme Greg=
oire( 652070658)From Huawei is informed ","TIENTCHEU NZETCHIEU GAEL","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active//No power issue on site ,site on Gen with Ubaie=3D53V, Tx Fme =
Gregoire( 652070658)From Huawei is informed ","ange.kongo@ihstowers.com","6=
10","26-10-2024 14:45:22","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003415175","Lad=
a I Yde","","26-10-2024 13:55:30","26-10-2024 13:46:20","26-10-2024 15:12:2=
0","site went down because disjunction cb(63*63A) in Dc box due to load // =
He reamed Cb; site on gen","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Circuit Breaker Issue","site went down bec=
ause disjunction cb(63*63A) in Dc box due to load // He reamed Cb; site on =
gen","olivier.kwedi@ihstowers.com","551","26-10-2024 13:55:30","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003414979","B=
ATA-Mokolo","","26-10-2024 13:32:00","26-10-2024 13:13:45","26-10-2024 13:1=
5:45","Active, no power issue, site on grid with U=3D54,6V; Tx FME  Brice/6=
50214096/ From huawei is informed","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issue, s=
ite on grid with U=3D54,6V; Tx FME  Brice/650214096/ From huawei is informe=
d","stephane.nkamwa@ihstowers.com","1096","26-10-2024 13:32:00","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003414943","N=
gouetou","","26-10-2024 13:28:56","26-10-2024 13:24:49","26-10-2024 14:24:1=
7","Active//No power issue on site ,site on Gen with Ubaie=3D53V, Tx Fme Gr=
egoire( 652070658)From Huawei is informed ","Parker Tchoup","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue on site ,site on Gen with Ubaie=3D53V, Tx Fme Gregoire(=
 652070658)From Huawei is informed ","stephane.nkamwa@ihstowers.com","248",=
"26-10-2024 13:28:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003414588","M=
IMBOMAN LIBERTE","","26-10-2024 12:29:01","26-10-2024 12:17:04","26-10-2024=
 12:35:06","Grid outage ,Site went down because Main Gen faulty //MDG 20KVA=
 has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage ,Site went down because Main Gen faul=
ty //MDG 20KVA has deployed","stephane.nkamwa@ihstowers.com","867","26-10-2=
024 12:29:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003414425","M=
vog-Manga","","26-10-2024 12:09:16","26-10-2024 11:42:54","26-10-2024 12:03=
:18","Site went down due to 01/06 faulty//he add 01 Rectifier and site is o=
n Grid power issues resolved since 12:03 PM (Site still down after the Powe=
r reset Done and The FME TX leonal Steve 655184876 is in","Albran Byorel","=
Equipment Repair","Passive","Rectifier","Rectifier Module","Site went down =
due to 01/06 faulty//he add 01 Rectifier and site is on Grid power issues r=
esolved since 12:03 PM (Site still down after the Power reset Done and The =
FME TX leonal Steve 655184876 is informed)","stephane.nkamwa@ihstowers.com"=
,"1584","26-10-2024 12:09:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0003413931","B=
astos Bir","","26-10-2024 10:51:06","26-10-2024 10:43:53","26-10-2024 11:44=
:57","Grid Outage, site went down because Gen stopped with ""high temp"" al=
arm due to  Gen Punctured pellet // he add water and Manually Stated the Ge=
n ","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - High En=
gine Temp - Coolant Level Issue","Grid Outage, site went down because Gen s=
topped with ""high temp"" alarm due to  Gen Punctured pellet // he add wate=
r and Manually Stated the Gen ","stephane.nkamwa@ihstowers.com","434","26-1=
0-2024 10:51:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003413743","N=
yom OCM","","26-10-2024 10:21:41","26-10-2024 10:15:35","26-10-2024 13:16:4=
7","Active//No power issue  Ubaie:54.4 V   site on Grid, tx fme symphorien =
/650257151/ from huawei is informed","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue  Ubaie:54.4 V   site on Grid, tx fme symphorien /650257151/ =
from huawei is informed","stephane.nkamwa@ihstowers.com","367","26-10-2024 =
10:21:41","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003413619","Nko=
ulou Carriere carrefourt","","26-10-2024 10:00:23","26-10-2024 09:53:11","2=
6-10-2024 12:29:30","No power issue on site ,site on Grid with Ubaie=3D54.1=
 V The FME TX Leonel /690087047/ from huawei is infromed.","Mba Lazare Herv=
e","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue on site ,site on Grid with Ubaie=3D54.1 V The=
 FME TX Leonel /690087047/ from huawei is infromed.","olivier.kwedi@ihstowe=
rs.com","433","26-10-2024 10:00:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0003413590","M=
beng","IHS_YND_553","26-10-2024 09:53:32","26-10-2024 09:44:24","26-10-2024=
 11:53:37","Grid outage, site went down because Gen ran untill fuel shortag=
e // refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid outage, site went down because Gen ran untill fuel shortage =
// refueling done","stephane.nkamwa@ihstowers.com","549","26-10-2024 09:53:=
32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0003413467","E=
seka Town","","26-10-2024 09:26:58","26-10-2024 09:19:49","26-10-2024 10:18=
:49","Grid Outage, site went down because Gen stopped with ""high temp"" al=
arm// He added water and started Gen manualy","Kemeni Franklin","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","Grid Outage, site went down because Gen stopped with ""high temp"" alarm=
// He added water and started Gen manualy","stephane.nkamwa@ihstowers.com",=
"430","26-10-2024 09:26:58","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003412878","MBI=
MBIM","","26-10-2024 06:57:44","26-10-2024 06:08:33","26-10-2024 08:44:21",=
"Site went down because Gen started and stopped due to water infiltration i=
n the tank//  He purged the tank, site on Gen","Parker Tchoup","Fuel Outage=
 (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","S=
ite went down because Gen started and stopped due to water infiltration in =
the tank//  He purged the tank, site on Gen","olivier.kwedi@ihstowers.com",=
"2952","26-10-2024 06:57:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003412532","N=
kolfon Cimencam","","26-10-2024 04:54:17","26-10-2024 03:21:04","26-10-2024=
 12:29:04","Active//No power issue on site U=3D54,5V site on Gen The Rm Ala=
in (691144423) of huawei is informed, Repetitive issue","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue on site U=3D54,5V site on Gen The Rm Alain=
 (691144423) of huawei is informed, Repetitive issue","christian.fonkou@ihs=
towers.com","5593","26-10-2024 04:54:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003412472","N=
GONA","","26-10-2024 04:23:07","26-10-2024 04:14:03","26-10-2024 05:52:03",=
"grid outage,gen stopped with alarm high temp//he added water in radiator",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Eng=
ine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high te=
mp//he added water in radiator","kouoh.jean@ihstowers.com","545","26-10-202=
4 04:23:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003412164","S=
ous Prefecture","","26-10-2024 02:05:28","26-10-2024 02:00:22","26-10-2024 =
02:05:22","Active//No power isssue, site is on grid  with Ubaie=3D54,2V, Rm=
 alain (691 14 44 23) from Huawei is informed ","Fanda Brice","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power isssue, site is on grid  with Ubaie=3D54,2V, Rm alain (691 =
14 44 23) from Huawei is informed ","christian.fonkou@ihstowers.com","307",=
"26-10-2024 02:05:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0003412043","B=
otmakak","","26-10-2024 01:13:51","26-10-2024 00:55:42","26-10-2024 03:00:2=
4","no power issue U=3D54V site on Grid. the TX FME ETienne// 695033981// /=
 from huawei is informed ","Kemeni Franklin","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue U=
=3D54V site on Grid. the TX FME ETienne// 695033981// / from huawei is info=
rmed ","christian.fonkou@ihstowers.com","1090","26-10-2024 01:13:51","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003411870","N=
kozoa","","26-10-2024 00:02:03","25-10-2024 23:54:44","26-10-2024 02:20:02"=
,"Grid bad voltage, site went down because Gen failed to start due to Grid =
bad voltage and RCP faulty//he bypassed Grid and Started Gen","Fabrice Poua=
kam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid bad voltage, site went down because Gen failed to start due to Gri=
d bad voltage and RCP faulty//he bypassed Grid and Started Gen","christian.=
fonkou@ihstowers.com","440","26-10-2024 00:02:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003411648","L=
abogenie","","25-10-2024 23:01:56","25-10-2024 22:50:49","26-10-2024 05:20:=
23","No power issue, site is on grid with Ubaie=3D54,8V, Hurgo(672390202) f=
rom Huawei is informed,Repetitif issue","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site=
 is on grid with Ubaie=3D54,8V, Hurgo(672390202) from Huawei is informed,Re=
petitif issue","christian.fonkou@ihstowers.com","668","25-10-2024 23:01:56"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003411266","M=
imboman-Village","","25-10-2024 21:46:39","25-10-2024 20:59:30","25-10-2024=
 21:02:38","Grid outage, site went down before gen start due to poor batter=
y backup // Grid return","Mba Lazare Herve","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Grid return","kombi.samuel@ihs=
towers.com","2830","25-10-2024 21:46:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003411138","N=
GONA","","25-10-2024 21:27:08","25-10-2024 21:18:04","25-10-2024 23:06:57",=
"grid outage,gen stopped with alarm high temp//he added water in radiator",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator=
","grid outage,gen stopped with alarm high temp//he added water in radiator=
","joelle.ekessi@ihstowers.com","545","25-10-2024 21:27:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003411040","M=
IMBOMAN LIBERTE","","25-10-2024 21:09:27","25-10-2024 21:01:22","25-10-2024=
 21:18:30","Grid outage with main gen faulty //Grid return","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid=
 outage with main gen faulty //Grid return","joelle.ekessi@ihstowers.com","=
486","25-10-2024 21:09:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0003410901","O=
ssombe","","25-10-2024 20:46:35","25-10-2024 20:40:31","25-10-2024 20:45:31=
","No power issue on site ,site on Gen with Ubaie=3D53V, Tx Fme Gregoire( 6=
52070658)From Huawei is informed","Parker Tchoup","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site ,site on Gen with Ubaie=3D53V, Tx Fme Gregoire( 652070658)From Hu=
awei is informed","joelle.ekessi@ihstowers.com","365","25-10-2024 20:46:35"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003410790","A=
kak-Nkozoa-MTN-IHS","","25-10-2024 20:32:02","25-10-2024 20:24:59","25-10-2=
024 23:18:58","Grid bad voltage, site went down because Gen failed to start=
 due to Grid bad voltage and RCP faulty//he bypassed Grid and Started Gen",=
"Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid bad voltage, site went down because Gen failed to sta=
rt due to Grid bad voltage and RCP faulty//he bypassed Grid and Started Gen=
","joelle.ekessi@ihstowers.com","425","25-10-2024 20:32:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003410769","M=
ambine","","25-10-2024 20:30:38","25-10-2024 20:29:35","25-10-2024 20:42:59=
","Grid hybrid gen site.site went down due to hybrid system malfunctionning=
//Gen manually started ","Fanda Brice","Equipment Repair","Passive","Hybrid=
","Hybrid Module","Grid hybrid gen site.site went down due to hybrid system=
 malfunctionning//Gen manually started ","joelle.ekessi@ihstowers.com","64"=
,"25-10-2024 20:30:38","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003410702","Nko=
lbisson usines des eaux 2","","25-10-2024 20:24:28","25-10-2024 20:22:24","=
25-10-2024 22:32:24","Access issue during the nigth due to landloard(Grid O=
utage site went down because Gen Failed to Start due to Grid contactor Faul=
ty on site//Grid Restored)","TIENTCHEU NZETCHIEU GAEL","Access Denial","Lea=
se Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access i=
ssue during the nigth due to landloard(Grid Outage site went down because G=
en Failed to Start due to Grid contactor Faulty on site//Grid Restored)","e=
mmanuel.ghani@ihstowers.com","125","25-10-2024 20:24:28","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003410443","MBI=
MBIM","","25-10-2024 19:51:25","25-10-2024 19:42:19","25-10-2024 21:49:44",=
"Site went down because Gen started and stopped due to water infiltration i=
n the tank// He purged the tank, site on gen","Parker Tchoup","Fuel Outage =
(Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","Si=
te went down because Gen started and stopped due to water infiltration in t=
he tank// He purged the tank, site on gen","emmanuel.ghani@ihstowers.com","=
547","25-10-2024 19:51:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003410198","M=
imboman-Village","","25-10-2024 19:07:56","25-10-2024 19:04:49","25-10-2024=
 19:37:29","Grid outage, site went down before gen start due to poor batter=
y backup // Gen started automatically","Mba Lazare Herve","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen started auto=
matically","joelle.ekessi@ihstowers.com","188","25-10-2024 19:07:56","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0003409918","M=
ontee-Jouvence","","25-10-2024 18:30:36","25-10-2024 18:29:32","25-10-2024 =
19:42:32","Grid bad voltage, site went down because Gen failed to start due=
 to Grid bad voltage and RCP faulty//he bypassed Grid and Started Gen","Hye=
mafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid bad voltage, site went down because Gen failed to start du=
e to Grid bad voltage and RCP faulty//he bypassed Grid and Started Gen","jo=
elle.ekessi@ihstowers.com","65","25-10-2024 18:30:36","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003409771","MIM=
BOMAN LIBERTE","","25-10-2024 18:09:59","25-10-2024 18:09:53","25-10-2024 1=
9:11:09","Grid Outage//Grid return","Mba Lazare Herve","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid Outage//Grid return","=
emmanuel.ghani@ihstowers.com","7","25-10-2024 18:09:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003409099","L=
abogenie","","25-10-2024 16:34:55","25-10-2024 16:19:49","25-10-2024 17:45:=
00","No power issue, site is on grid with Ubaie=3D54,8V, Eloundou(652586578=
) from Huawei is informed","","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on grid w=
ith Ubaie=3D54,8V, Eloundou(652586578) from Huawei is informed","christian.=
fonkou@ihstowers.com","907","25-10-2024 16:34:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003409098","O=
lembe-Terminus","","25-10-2024 16:34:54","25-10-2024 16:32:09","25-10-2024 =
17:15:09","no power issue  Ubaie:51,.6 V   site on Grid, tx fme symphorien =
/650257151 from huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power =
issue  Ubaie:51,.6 V   site on Grid, tx fme symphorien /650257151 from huaw=
ei is informed","joelle.ekessi@ihstowers.com","166","25-10-2024 16:34:54","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003409059","N=
kolfon Cimencam","","25-10-2024 16:29:31","25-10-2024 16:17:23","25-10-2024=
 17:25:47","No power issue on site U=3D54,5v site on Gen The Rm Alain (6911=
44423) of huawei is informed, Repetitive issue","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site U=3D54,5v site on Gen The Rm Alain (691144423) of =
huawei is informed, Repetitive issue","christian.fonkou@ihstowers.com","728=
","25-10-2024 16:29:31","Sagemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0003409011","Nko=
abang entree carriere","","25-10-2024 16:21:50","25-10-2024 15:23:55","25-1=
0-2024 16:05:55","grid outage, gen start and stopped with alarm 'Low oil pr=
essure' // He added oil and Gen manually started","Mba Lazare Herve","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage, gen =
start and stopped with alarm 'Low oil pressure' // He added oil and Gen man=
ually started","kombi.samuel@ihstowers.com","3476","25-10-2024 16:21:50","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0003408971","S=
imbock OCM","","25-10-2024 16:16:00","25-10-2024 16:13:16","25-10-2024 16:4=
8:16","Grid outage, site went down because gen fails to start due to gen co=
ntactor faulty // he replace it and manually start the gen","Hyemafo Gildas=
","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage=
, site went down because gen fails to start due to gen contactor faulty // =
he replace it and manually start the gen","christian.fonkou@ihstowers.com",=
"165","25-10-2024 16:16:00","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003408727","NTU=
I TOWN","","25-10-2024 15:52:31","25-10-2024 15:51:58","25-10-2024 17:30:49=
","Grid outage, site went down because gen ran untill fuel shortage // refu=
eling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid outage, site went down because gen ran untill fuel shortage // refu=
eling done","emmanuel.ghani@ihstowers.com","34","25-10-2024 15:52:31","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003408623","E=
lobi Mokolo","","25-10-2024 15:41:31","25-10-2024 15:27:53","25-10-2024 15:=
43:31","Active, no power issue, site on grid with U=3D53,2V; Tx FME  Brice/=
650214096/ From huawei is informed and up at 03:43 PM","Mboua Thierry","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active, no power issue, site on grid with U=3D53,2V; Tx FME  Brice/=
650214096/ From huawei is informed and up at 03:43 PM","christian.fonkou@ih=
stowers.com","819","25-10-2024 15:41:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003408614","N=
yom OCM","","25-10-2024 15:41:04","25-10-2024 15:34:29","25-10-2024 17:47:0=
0","no power issue  Ubaie:54.4 V   site on Grid, tx fme symphorien /6502571=
51 from huawei is informed","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue  U=
baie:54.4 V   site on Grid, tx fme symphorien /650257151 from huawei is inf=
ormed","joelle.ekessi@ihstowers.com","396","25-10-2024 15:41:04","Sagemcom =
CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003408611","OBA=
M NGOLA OCM","","25-10-2024 15:40:43","25-10-2024 15:39:09","25-10-2024 15:=
57:01","site went down due to insufficient (03) rectifier on site//site sta=
bilized(need to change the faulty rectifier)","MINKA NICOLAS","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","site went down due to insuf=
ficient (03) rectifier on site//site stabilized(need to change the faulty r=
ectifier)","emmanuel.ghani@ihstowers.com","95","25-10-2024 15:40:43","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003408445","B=
ATA-Mokolo","","25-10-2024 15:25:13","25-10-2024 14:45:33","26-10-2024 03:1=
5:03","Active, no power issue, site on grid with U=3D54,6V; Tx FME  Brice/6=
50214096/ From huawei is informed","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issue, s=
ite on grid with U=3D54,6V; Tx FME  Brice/650214096/ From huawei is informe=
d","christian.fonkou@ihstowers.com","2381","25-10-2024 15:25:13","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003408432","A=
kak-Nkozoa-MTN-IHS","","25-10-2024 15:24:42","25-10-2024 15:23:03","25-10-2=
024 16:48:03","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage // he bypass grid and manually start the gen","F=
abrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage // he bypass grid and manually start the gen","j=
oelle.ekessi@ihstowers.com","100","25-10-2024 15:24:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0003408413","Bondjock=
","","25-10-2024 15:21:13","25-10-2024 15:14:08","25-10-2024 16:05:08","Cas=
caded Incident from TTO3294393","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
ran untill fuel shortage // refueling done","system","425","25-10-2024 15:2=
1:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0003408411","Minka","=
","25-10-2024 15:21:13","25-10-2024 15:14:08","25-10-2024 16:05:08","Cascad=
ed Incident from TTO3294393","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen ran=
 untill fuel shortage // refueling done","system","425","25-10-2024 15:21:1=
3","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0003408410","Mbeng","=
","25-10-2024 15:21:12","25-10-2024 15:14:08","25-10-2024 16:05:08","Cascad=
ed Incident from TTO3294393","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down because gen ran=
 untill fuel shortage // refueling done","system","424","25-10-2024 15:21:1=
2","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0003408391","M=
om","IHS_YND_369, IHS_YND_371, IHS_YND_553, IHS_YND_372","25-10-2024 15:19:=
44","25-10-2024 15:14:08","25-10-2024 16:08:08","Grid outage, site went dow=
n because gen ran untill fuel shortage // refueling done","Fanda Brice","Fu=
el Outage","Passive","Diesel","Diesel Outage","Grid outage, site went down =
because gen ran untill fuel shortage // refueling done","joelle.ekessi@ihst=
owers.com","338","25-10-2024 15:19:44","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003408054","Bas=
tos Amb Coree","","25-10-2024 14:42:57","25-10-2024 14:41:14","25-10-2024 1=
4:44:15","Site went down due to insufficient of rectifier//Site stabilized"=
,"","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went =
down due to insufficient of rectifier//Site stabilized","emmanuel.ghani@ihs=
towers.com","104","25-10-2024 14:42:57","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0003407425","NKO=
MKANA ELIZA HOTEL","","25-10-2024 13:18:33","25-10-2024 13:10:17","25-10-20=
24 13:30:56","Grid outage,no space to deploy a mobile DG,waiting for grid r=
estored //Grid restored.","","Grid Supply","Passive","Grid","National Grid =
- Grid Outage Issue","Grid outage,no space to deploy a mobile DG,waiting fo=
r grid restored //Grid restored.","denis.mballa@ihstowers.com","496","25-10=
-2024 13:18:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0003407110","O=
mnisport 3","","25-10-2024 12:41:24","25-10-2024 12:34:40","25-10-2024 13:5=
2:44","Tx issue: site on Grid,Ubaie:54.6; Armand Nguetsa/691-14-44-12 is in=
formed.","Delor Telezing","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Tx issue: site on Grid,Ubaie:54.6; Ar=
mand Nguetsa/691-14-44-12 is informed.","ange.kongo@ihstowers.com","405","2=
5-10-2024 12:41:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0003406819","T=
radex-Nkomo","","25-10-2024 12:05:30","25-10-2024 11:52:18","25-10-2024 12:=
01:08","Tx Issue: site on grid,Ubaie:53.4V; Lionel Adjep//655-18-48-76 is i=
nformed.","Albran Byorel","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Tx Issue: site on grid,Ubaie:53.4V; L=
ionel Adjep//655-18-48-76 is informed.","ange.kongo@ihstowers.com","793","2=
5-10-2024 12:05:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003406230","N=
GONA","","25-10-2024 10:29:21","25-10-2024 10:16:10","25-10-2024 13:48:04",=
"Active: no power issue, site is on grid with Ubaie=3D54V, Lionel Adjep (65=
5184876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no=
 power issue, site is on grid with Ubaie=3D54V, Lionel Adjep (655184876) fr=
om Huawei is informed","ange.kongo@ihstowers.com","792","25-10-2024 10:29:2=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003406124","N=
omayos-IHS","","25-10-2024 10:14:07","25-10-2024 10:08:56","25-10-2024 10:1=
3:57","insufiency of rectifier","Fanda Brice","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","site down due to insufficient rectifiers//s=
ite stabilized","ange.kongo@ihstowers.com","312","25-10-2024 10:14:07","Sag=
emcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003406002","NTU=
I TOWN","","25-10-2024 10:03:07","25-10-2024 09:52:57","25-10-2024 10:21:41=
","Grid fluctuation, site went down before gen start due to poor battery ba=
ckup // grid return","Parker Tchoup","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid fluctuation, site went down befo=
re gen start due to poor battery backup // grid return","denis.mballa@ihsto=
wers.com","611","25-10-2024 10:03:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003405862","Biteng-M=
aetur","","25-10-2024 09:41:36","25-10-2024 09:30:23","25-10-2024 09:59:55"=
,"grid outage,gen stopped with alarm high temp//he added water in radiator"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High En=
gine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high t=
emp//he added water in radiator","ange.kongo@ihstowers.com","674","25-10-20=
24 09:41:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_115","NOCINC0003405617","Labogeni=
e","","25-10-2024 08:57:50","25-10-2024 07:36:41","25-10-2024 07:40:13","No=
 power issue, site is on grid with Ubaie=3D54,8V, Hurgo(672390202) from Hua=
wei is informed","","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue, site is on grid with Ubaie=
=3D54,8V, Hurgo(672390202) from Huawei is informed,Repetitif issue","ange.k=
ongo@ihstowers.com","4870","25-10-2024 08:57:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0003405438","Dagobert=
","","25-10-2024 08:20:32","25-10-2024 08:15:01","25-10-2024 08:25:04","Cas=
caded Incident from TTO3290913","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active: no power issue, site i=
s on grid with Ubaie=3D53V, site impacted by NKOLBISSON NODA, Nkolbison nod=
al is not managed by Ihs","system","331","25-10-2024 08:20:32","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0003405437","Yona Hot=
el","","25-10-2024 08:20:32","25-10-2024 08:15:01","25-10-2024 08:25:04","C=
ascaded Incident from TTO3290913","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active: no power issue, site=
 is on grid with Ubaie=3D53V, site impacted by NKOLBISSON NODA, Nkolbison n=
odal is not managed by Ihs","system","331","25-10-2024 08:20:32","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0003405436","Meyong-M=
eyeme","","25-10-2024 08:20:32","25-10-2024 08:15:01","25-10-2024 08:25:04"=
,"Cascaded Incident from TTO3290913","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","Active: no power issue, s=
ite is on grid with Ubaie=3D53V, site impacted by NKOLBISSON NODA, Nkolbiso=
n nodal is not managed by Ihs","system","331","25-10-2024 08:20:32","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003405439","Entree C=
ite Verte","","25-10-2024 08:20:32","25-10-2024 08:15:01","25-10-2024 08:25=
:04","Cascaded Incident from TTO3290913","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active: no power issue, site is on=
 grid with Ubaie=3D53V, site impacted by NKOLBISSON NODA, Nkolbison nodal i=
s not managed by Ihs","system","331","25-10-2024 08:20:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0003405433","Cite-Ver=
te","","25-10-2024 08:20:31","25-10-2024 08:15:01","25-10-2024 08:25:04","C=
ascaded Incident from TTO3290913","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","Active: no power issue, site is on grid with Ubaie=
=3D53V, site impacted by NKOLBISSON NODA, Nkolbison nodal is not managed by=
 Ihs","system","330","25-10-2024 08:20:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_233","NOCINC0003405432","Oyomaban=
g OCM","","25-10-2024 08:20:31","25-10-2024 08:15:01","25-10-2024 08:25:04"=
,"Cascaded Incident from TTO3290913","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","Active: no power issue, s=
ite is on grid with Ubaie=3D53V, site impacted by NKOLBISSON NODA, Nkolbiso=
n nodal is not managed by Ihs","system","330","25-10-2024 08:20:31","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0003405434","Nkomkana=
","","25-10-2024 08:20:31","25-10-2024 08:15:01","25-10-2024 08:25:04","Cas=
caded Incident from TTO3290913","","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","Active: no power issue, site is on grid with Ubaie=3D5=
3V, site impacted by NKOLBISSON NODA, Nkolbison nodal is not managed by Ihs=
","system","330","25-10-2024 08:20:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0003405435","Oyomaban=
g Ecole","","25-10-2024 08:20:31","25-10-2024 08:15:01","25-10-2024 08:25:0=
4","Cascaded Incident from TTO3290913","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Active","Cascade Active","Cascade Active","Active: no power issue,=
 site is on grid with Ubaie=3D53V, site impacted by NKOLBISSON NODA, Nkolbi=
son nodal is not managed by Ihs","system","330","25-10-2024 08:20:31","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0003405390","N=
kolbi-Boss","IHS_YND_233, IHS_YND_202, IHS_YND_200, IHS_YND_686, IHS_YND_23=
0, IHS_YND_271, IHS_YND_232, IHS_YND_286, IHS_YND_543","25-10-2024 08:17:07=
","25-10-2024 08:15:01","25-10-2024 10:32:46","Active: no power issue, site=
 is on grid with Ubaie=3D53V, site impacted by NKOLBISSON NODA, Nkolbison n=
odal is not managed by Ihs","TIENTCHEU NZETCHIEU GAEL","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
no power issue, site is on grid with Ubaie=3D53V, site impacted by NKOLBISS=
ON NODA, Nkolbison nodal is not managed by Ihs","ange.kongo@ihstowers.com",=
"127","25-10-2024 08:17:07","Sagemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0003405324","Nko=
abang entree carriere","","25-10-2024 07:53:19","25-10-2024 07:49:05","25-1=
0-2024 09:00:23","Site on DG due to grid outage,DG stopped due to Alarm oil=
 low pressure ( Alarm not proven)//Reset DG card and manually start of DG."=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","Site on DG due to grid outage,DG stopped due to Alarm oil low pres=
sure ( Alarm not proven)//Reset DG card and manually start of DG.","denis.m=
balla@ihstowers.com","255","25-10-2024 07:53:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003404996","N=
kolfoulou","","25-10-2024 06:33:56","25-10-2024 06:28:41","25-10-2024 08:44=
:25","Active//No power issue on site UBAIE=3D53,8V  synphorien (675295205) =
From huawei is informed ","Siligap Boris","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issu=
e on site UBAIE=3D53,8V  synphorien (675295205) From huawei is informed ","=
ange.kongo@ihstowers.com","316","25-10-2024 06:33:56","Sagemcom CMR"
"Closed Complete","Site Down","T2502","IHS_YND_781","NOCINC0003404846","BIB=
OMDJIDJIEL","","25-10-2024 05:59:29","25-10-2024 05:47:21","25-10-2024 06:4=
6:17","Grid outage, site went down because gen ran untill fuel shortage // =
refueling done","Kemeni Franklin","Fuel Outage","Passive","Diesel","Diesel =
Outage","Grid outage, site went down because gen ran untill fuel shortage /=
/ refueling done","kamga.virgile@ihstowers.com","729","25-10-2024 05:59:29"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0003404808","E=
seka Town","","25-10-2024 05:47:14","25-10-2024 05:41:08","25-10-2024 07:48=
:28","Grid bad voltage,DG failed to start no RCP //Bypass Grid and manually=
 start of DG.","Kemeni Franklin","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid bad voltage,DG failed to start no RCP =
//Bypass Grid and manually start of DG.","stephane.nkamwa@ihstowers.com","3=
67","25-10-2024 05:47:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0003404731","O=
yomabang OCM","IHS_YND_232","25-10-2024 05:24:42","25-10-2024 01:43:20","25=
-10-2024 05:20:36","No power issue on site U=3D53v site on grid Mohamadou/6=
91144435 of huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue on site U=3D53v site on grid Mohamadou/691144435 of huawei is in=
formed","stephane.nkamwa@ihstowers.com","13808","25-10-2024 05:24:42","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003404614","L=
abogenie","","25-10-2024 04:50:38","25-10-2024 04:50:15","25-10-2024 05:36:=
15","Grid outage, no space to deploy a MDG // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no spac=
e to deploy a MDG // Grid return","stephane.nkamwa@ihstowers.com","24","25-=
10-2024 04:50:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0003403883","C=
rf-Nkolbisson","","25-10-2024 01:47:32","25-10-2024 01:43:20","25-10-2024 0=
8:25:04","No power issue on site U=3D53v site on grid Mohamadou/691144435 o=
f huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site U=3D53v site on g=
rid Mohamadou/691144435 of huawei is informed","stephane.nkamwa@ihstowers.c=
om","253","25-10-2024 01:47:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003403859","N=
GONA","","25-10-2024 01:44:05","25-10-2024 01:39:54","25-10-2024 02:05:54",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started","Mba Lazare Herve","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage, site went down before gen st=
art due to poor battery backup // Gen started","stephane.nkamwa@ihstowers.c=
om","251","25-10-2024 01:44:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0003403300","E=
ntree Cite Verte","","24-10-2024 23:28:26","24-10-2024 23:22:19","25-10-202=
4 04:10:36","No power issue on site U=3D53v site on grid Mohamadou/69114443=
5 of huawei is informed","Paul BIBOUM","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53v site on grid Mohamadou/691144435 of huawei is informed","stephane.nk=
amwa@ihstowers.com","368","24-10-2024 23:28:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003403150","O=
lembe-Terminus","","24-10-2024 22:54:47","24-10-2024 22:05:30","25-10-2024 =
04:10:17","no power issue  Ubaie:51,.6 V   site on Grid, tx fme symphorien =
/650257151 from huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power =
issue  Ubaie:51,.6 V   site on Grid, tx fme symphorien /650257151 from huaw=
ei is informed","stephane.nkamwa@ihstowers.com","2958","24-10-2024 22:54:47=
","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003402807","MIM=
BOMAN LIBERTE","","24-10-2024 21:50:42","24-10-2024 21:43:35","24-10-2024 2=
3:37:35","Grid outage Site went Down due to Main Gen Faulty // MDG 20Kva ha=
s deplyed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Generator Faulty","Grid outage Site went Down due to Main Gen Faulty // =
MDG 20Kva has deplyed","landry.etame@ihstowers.com","428","24-10-2024 21:50=
:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003402785","MBALNGON=
G LYCEE","","24-10-2024 21:46:51","24-10-2024 21:40:12","24-10-2024 21:48:1=
2","Cascaded Incident from TTO3287879","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen start automaticaly","system",=
"399","24-10-2024 21:46:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003402784","ELOUMDEM=
 CARRIERE","","24-10-2024 21:46:51","24-10-2024 21:40:12","24-10-2024 21:48=
:12","Cascaded Incident from TTO3287879","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start automaticaly","system=
","399","24-10-2024 21:46:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003402786","Afanoya"=
,"","24-10-2024 21:46:51","24-10-2024 21:40:12","24-10-2024 21:48:12","Casc=
aded Incident from TTO3287879","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Gen start automaticaly","system","399"=
,"24-10-2024 21:46:51","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003402780","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","24-10-2024 21:45:20","24-10-20=
24 21:40:12","24-10-2024 21:48:12","Grid outage, site went down before gen =
start due to poor battery backup // Gen start automaticaly","Hyemafo Gildas=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen start automaticaly","landry.etame@ihstowers.com","309","24-10-2024 2=
1:45:20","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0003402754","Ona=
ngondi (melen bikop)","","24-10-2024 21:39:37","24-10-2024 21:25:31","24-10=
-2024 23:36:31","Grid outage, site went down because gen ran untill fuel sh=
ortage // refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","D=
iesel Outage","Grid outage, site went down because gen ran untill fuel shor=
tage // refueling done","landry.etame@ihstowers.com","847","24-10-2024 21:3=
9:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003402396","Entree C=
ite Verte","","24-10-2024 20:45:22","24-10-2024 19:29:55","24-10-2024 20:02=
:52","Cascaded Incident from TTO3287011","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site U=3D53v sit=
e on grid Mohamadou of huawei is informed","system","4527","24-10-2024 20:4=
5:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0003402395","Crf-Nkol=
bisson","","24-10-2024 20:45:22","24-10-2024 19:29:55","24-10-2024 20:02:52=
","Cascaded Incident from TTO3287011","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D53v site on grid Mohamadou of huawei is informed","system","4527","24-10=
-2024 20:45:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0003402394","Yona Hot=
el","","24-10-2024 20:45:22","24-10-2024 19:29:55","24-10-2024 20:02:52","C=
ascaded Incident from TTO3287011","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site U=3D5=
3v site on grid Mohamadou of huawei is informed","system","4527","24-10-202=
4 20:45:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0003402393","Meyong-M=
eyeme","","24-10-2024 20:45:22","24-10-2024 19:29:55","24-10-2024 20:02:52"=
,"Cascaded Incident from TTO3287011","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D53v site on grid Mohamadou of huawei is informed","system","4527","24-10=
-2024 20:45:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0003402392","Oyomaban=
g Ecole","","24-10-2024 20:45:21","24-10-2024 19:29:55","24-10-2024 20:02:5=
2","Cascaded Incident from TTO3287011","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Active","Cascade Active","Cascade Active","No power issue on site =
U=3D53v site on grid Mohamadou of huawei is informed","system","4526","24-1=
0-2024 20:45:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0003402389","Nkolbi-B=
oss","","24-10-2024 20:45:21","24-10-2024 19:29:55","24-10-2024 20:02:52","=
Cascaded Incident from TTO3287011","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","No power issue on site U=3D=
53v site on grid Mohamadou of huawei is informed","system","4526","24-10-20=
24 20:45:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0003402391","Nkomkana=
","","24-10-2024 20:45:21","24-10-2024 19:29:55","24-10-2024 20:02:52","Cas=
caded Incident from TTO3287011","","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","No power issue on site U=3D53v site on grid Mohamadou =
of huawei is informed","system","4526","24-10-2024 20:45:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0003402390","Cite-Ver=
te","","24-10-2024 20:45:21","24-10-2024 19:29:55","24-10-2024 20:02:52","C=
ascaded Incident from TTO3287011","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","No power issue on site U=3D53v site on grid Mohamado=
u of huawei is informed","system","4526","24-10-2024 20:45:21","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003402245","Kondengu=
i","","24-10-2024 20:12:20","24-10-2024 20:04:55","25-10-2024 00:50:55","Ca=
scaded Incident from TTO3287232","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, no space to deploy a mob=
il gen // grid return","system","445","24-10-2024 20:12:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003402241","E=
mombo-Tchad","IHS_YND_114","24-10-2024 20:11:07","24-10-2024 20:04:55","25-=
10-2024 00:50:55","grid outage, no space to deploy a mobil gen // grid retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid outage, no space to deploy a mobil gen // grid return","kouoh.jean@ihs=
towers.com","373","24-10-2024 20:11:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0003402051","O=
yomabang OCM","IHS_YND_273, IHS_YND_202, IHS_YND_200, IHS_YND_686, IHS_YND_=
230, IHS_YND_271, IHS_YND_232, IHS_YND_543","24-10-2024 19:46:51","24-10-20=
24 19:29:55","24-10-2024 20:02:52","No power issue on site U=3D53v site on =
grid Mohamadou of huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site U=3D53v site on grid Mohamadou of huawei is inform=
ed","kouoh.jean@ihstowers.com","1017","24-10-2024 19:46:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003402029","E=
ssomba","","24-10-2024 19:43:03","24-10-2024 19:09:20","24-10-2024 20:54:45=
"," grid outage,site went down due to gen overload (15Kva, 200A) // He redu=
ced the load and started Gen manually.","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload"," grid outage,site went down due =
to gen overload (15Kva, 200A) // He reduced the load and started Gen manual=
ly.","kouoh.jean@ihstowers.com","2024","24-10-2024 19:43:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003401753","MEHANDAN=
","","24-10-2024 19:03:00","24-10-2024 18:51:11","24-10-2024 19:12:59","Cas=
caded Incident from TTO3286640","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Gen started","system","709","24-10-202=
4 19:03:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003401744","O=
dza II OCM","IHS_YND_528","24-10-2024 19:00:19","24-10-2024 18:51:11","24-1=
0-2024 19:12:59","Grid outage, site went down before gen start due to poor =
battery backup // Gen started","Albran Byorel","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Gen started","kouoh.jean@ih=
stowers.com","550","24-10-2024 19:00:19","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0003401743","Bit=
oto","","24-10-2024 19:00:07","24-10-2024 18:44:19","24-10-2024 19:36:47","=
grid outage, site went down because gen failed to started due to gen Overlo=
ad(20kva, 315A)// He reduced the load and gen manually started","Mba Lazare=
 Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","grid out=
age, site went down because gen failed to started due to gen Overload(20kva=
, 315A)// He reduced the load and gen manually started","landry.etame@ihsto=
wers.com","1272","24-10-2024 19:00:07","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003401690","Eko=
unou","","24-10-2024 18:49:23","24-10-2024 18:44:14","24-10-2024 18:50:02",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","landry=
.etame@ihstowers.com","310","24-10-2024 18:49:23","Sagemcom CMR"
"Closed Complete","Site Down","T0579","IHS_YND_366","NOCINC0003401625","Man=
doumba MTN","","24-10-2024 18:30:22","24-10-2024 17:42:12","24-10-2024 20:1=
5:13","site went down because gen ran till fuel shortage//Refueling done","=
Kemeni Franklin","Fuel Outage","Passive","Diesel","Diesel Outage","site wen=
t down because gen ran till fuel shortage//Refueling done","landry.etame@ih=
stowers.com","2892","24-10-2024 18:30:22","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003401588","OBA=
M NGOLA OCM","","24-10-2024 18:23:13","24-10-2024 18:18:54","24-10-2024 19:=
02:18","site went down due to insufficient (03) rectifier on site//site sta=
bilized(need to change the faulty rectifier)","MINKA NICOLAS","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","site went down due to insuf=
ficient (03) rectifier on site//site stabilized(need to change the faulty r=
ectifier)","landry.etame@ihstowers.com","260","24-10-2024 18:23:13","Sagemc=
om CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0003400863","Nko=
lbisson usine des eaux","","24-10-2024 16:21:48","24-10-2024 16:17:43","24-=
10-2024 16:22:42","site went down due to work Team Gael and SS Daniel Fomek=
ong/6522201891/Sagemcom:repaired the Main Gen//End of work","TIENTCHEU NZET=
CHIEU GAEL","Installation Activity","Passive","Planned Activity","Installat=
ion Activity","site went down due to work Team Gael and SS Daniel Fomekong/=
6522201891/Sagemcom:repaired the Main Gen//End of work","landry.etame@ihsto=
wers.com","246","24-10-2024 16:21:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003400822","Ngouetou=
","","24-10-2024 16:13:21","24-10-2024 15:53:12","24-10-2024 15:54:30","Cas=
caded Incident from TTO3285535","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 49.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","1209","24-10-2024 16:13:21","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003400820","Matsari"=
,"","24-10-2024 16:13:21","24-10-2024 15:53:12","24-10-2024 15:54:30","Casc=
aded Incident from TTO3285535","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
49.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","1209","24-10-2024 16:13:21","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003400823","MBIMBIM"=
,"","24-10-2024 16:13:21","24-10-2024 15:53:12","24-10-2024 15:54:30","Casc=
aded Incident from TTO3285535","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
49.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","1209","24-10-2024 16:13:21","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003400821","Yoko OCM=
","","24-10-2024 16:13:21","24-10-2024 15:53:12","24-10-2024 15:54:30","Cas=
caded Incident from TTO3285535","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 49.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","1209","24-10-2024 16:13:21","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003400532","O=
lembe-Terminus","","24-10-2024 15:37:39","24-10-2024 14:51:30","24-10-2024 =
14:52:15","Active: no power issue, site is on grid with Ubaie=3D51,6V, SYMP=
HORIEN (650257151) from Huawei is informed","Fabrice Pouakam","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive: no power issue, site is on grid with Ubaie=3D51,6V, SYMPHORIEN (6502=
57151) from Huawei is informed","kouoh.jean@ihstowers.com","2770","24-10-20=
24 15:37:39","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003400341","Nko=
lmvack","","24-10-2024 15:01:15","24-10-2024 14:59:09","24-10-2024 17:29:29=
","site went down because gen ran till fuel shortage//Refueling done","Park=
er Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","site went down=
 because gen ran till fuel shortage//Refueling done","landry.etame@ihstower=
s.com","127","24-10-2024 15:01:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0003400270","Okola OC=
M","","24-10-2024 14:54:21","24-10-2024 14:42:33","24-10-2024 15:35:04","Ca=
scaded Incident from TTO3284885","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Eneo Outage, site Down bec=
ause the finder 220 relay faulty(in the ATS) did not order gen to start // =
Manual start of Gen","system","708","24-10-2024 14:54:21","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003399820","Sap=
eur","","24-10-2024 13:53:18","24-10-2024 13:44:13","24-10-2024 13:56:58","=
Grid outage, site went down before gen start due to poor battery backup // =
Gen started automaticaly","Mboua Thierry","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen started automaticaly","emman=
uel.ghani@ihstowers.com","546","24-10-2024 13:53:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003399483","MBALNGON=
G LYCEE","","24-10-2024 12:59:01","24-10-2024 12:57:41","24-10-2024 13:05:0=
7","Cascaded Incident from TTO3283962","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site down before gen=
 start due to poor backup and gen overload//grid returned","system","80","2=
4-10-2024 12:59:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003399484","Afanoya"=
,"","24-10-2024 12:59:01","24-10-2024 12:57:41","24-10-2024 13:05:07","Casc=
aded Incident from TTO3283962","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage, site down before gen star=
t due to poor backup and gen overload//grid returned","system","80","24-10-=
2024 12:59:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003399482","ELOUMDEM=
 CARRIERE","","24-10-2024 12:59:00","24-10-2024 12:57:41","24-10-2024 13:05=
:07","Cascaded Incident from TTO3283962","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site down before g=
en start due to poor backup and gen overload//grid returned","system","79",=
"24-10-2024 12:59:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003399475","TSINGA V=
ILLAGE 2","","24-10-2024 12:58:20","24-10-2024 12:56:41","24-10-2024 13:05:=
33","Cascaded Incident from TTO3283959","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage, site down before=
 gen start due to poor backup and gen overload//grid returned","system","99=
","24-10-2024 12:58:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0003399471","Ahala","=
IHS_YND_767, IHS_YND_719, IHS_YND_765, IHS_YND_313","24-10-2024 12:57:45","=
24-10-2024 12:56:41","24-10-2024 13:05:33","","Hyemafo Gildas","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","grid outage=
, site down before gen start due to poor backup and gen overload//grid retu=
rned","joelle.ekessi@ihstowers.com","65","24-10-2024 12:57:45","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003399420","F=
ebe Village","","24-10-2024 12:51:43","24-10-2024 12:51:40","24-10-2024 12:=
55:52","Grid outage,site went down before DG start due to Poor Batteries Ba=
ckup // DG started automatically.","Mboua Thierry","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage,site went d=
own before DG start due to Poor Batteries Backup // DG started automaticall=
y.","joelle.ekessi@ihstowers.com","4","24-10-2024 12:51:43","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003399393","Bas=
tos Amb Coree","","24-10-2024 12:46:56","24-10-2024 12:45:51","24-10-2024 1=
2:49:49","Grid outage.no space to deploy mobile gen//Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.n=
o space to deploy mobile gen//Grid return","emmanuel.ghani@ihstowers.com","=
66","24-10-2024 12:46:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003399361","N=
kolbisson usine des eaux","","24-10-2024 12:41:25","24-10-2024 12:39:43","2=
4-10-2024 13:13:48","Grid outage with main gen faulty //MDG of 20Kva deploy=
ed","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACD=
G - Generator Faulty","Grid outage with main gen faulty //MDG of 20Kva depl=
oyed","joelle.ekessi@ihstowers.com","103","24-10-2024 12:41:25","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0003399302","N=
R-Bastos","","24-10-2024 12:33:50","24-10-2024 12:21:45","24-10-2024 12:30:=
09","","","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue on site ubaie=3D54v site on grid  Elou=
ndou is informed","olivier.kwedi@ihstowers.com","726","24-10-2024 12:33:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003399204","ODZ=
A MINKAN EDIBI ASSI","","24-10-2024 12:17:28","24-10-2024 11:30:20","24-10-=
2024 13:13:03","grid outage, site went down because gen failed to start due=
 to water infiltration in tank // He purged fuel line","Albran Byorel","Fue=
l Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The =
Fuel","grid outage, site went down because gen failed to start due to water=
 infiltration in tank // He purged fuel line","kombi.samuel@ihstowers.com",=
"2829","24-10-2024 12:17:28","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003399173","BIY=
EMASSI NIKI","","24-10-2024 12:11:28","24-10-2024 12:05:22","24-10-2024 12:=
31:28","grid outage, site went down due to gen overload(10kva,160A)// He re=
duced the load and gen manually started","Hyemafo Gildas","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","grid outage, site went down due t=
o gen overload(10kva,160A)// He reduced the load and gen manually started",=
"emmanuel.ghani@ihstowers.com","367","24-10-2024 12:11:28","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003399047","Nsi=
meyong Terre Rouge","","24-10-2024 11:52:38","24-10-2024 11:47:32","24-10-2=
024 13:41:32","","MINKA NICOLAS","Fuel Outage (Probable)","Passive","Diesel=
","Fuel Line Issue","grid outage, site went down because gen failed to star=
t solenoid valve faulty// gen manually started","emmanuel.ghani@ihstowers.c=
om","306","24-10-2024 11:52:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003398977","AWAE OCM=
","","24-10-2024 11:43:00","24-10-2024 11:37:16","24-10-2024 11:41:57","Cas=
caded Incident from TTO3283351","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, site down due to poor =
backup before gen start//grid return","system","344","24-10-2024 11:43:00",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003398953","B=
iteng","IHS_YND_173","24-10-2024 11:40:30","24-10-2024 11:37:16","24-10-202=
4 11:41:57","","Mba Lazare Herve","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","grid outage, site down due to poor backu=
p before gen start//grid return","joelle.ekessi@ihstowers.com","195","24-10=
-2024 11:40:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003398833","M=
ANGUIERS CHAPELLE","","24-10-2024 11:27:56","24-10-2024 11:24:51","24-10-20=
24 11:46:06","Grid outage,site went down before DG start due to Poor Batter=
ies Backup // DG started automatically.","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,sit=
e went down before DG start due to Poor Batteries Backup // DG started auto=
matically.","olivier.kwedi@ihstowers.com","186","24-10-2024 11:27:56","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0003398730","SOA UNIV=
ERSITY STADIUM","","24-10-2024 11:13:00","24-10-2024 11:06:06","24-10-2024 =
12:40:48","Active: no power issue, site is on grid with Ubaie=3D54,9V, SYMP=
HORIEN (650257151) from Huawei is informed","Siligap Boris","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: no power issue, site is on grid with Ubaie=3D54,9V, SYMPHORIEN (650257=
151) from Huawei is informed","system","414","24-10-2024 11:13:00","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003398723","E=
mombo-Tchad","IHS_YND_114","24-10-2024 11:12:12","24-10-2024 11:06:06","24-=
10-2024 12:40:48","","","Grid Supply","Passive","Grid","National Grid - Gri=
d Outage Issue","grid outage, no space to deploy a mobil gen// grid return =
","olivier.kwedi@ihstowers.com","367","24-10-2024 11:12:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003398688","Kondengu=
i","","24-10-2024 11:04:20","24-10-2024 11:06:06","24-10-2024 12:40:48","Ca=
scaded Incident from TTO3283059 - Cascade Removed From TTO3283059","Albran =
Byorel","Cascade Outage","Passive","Cascade Passive","Cascade Passive","gri=
d outage, gen overload //balanced the load, site on gen","system","11021","=
24-10-2024 11:04:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0003398684","B=
arriere IHS","","24-10-2024 11:03:28","24-10-2024 10:01:32","24-10-2024 13:=
17:29","","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","grid outage, gen overload //balanced the load, site on gen","joe=
lle.ekessi@ihstowers.com","7636","24-10-2024 11:03:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0003398627","C=
RF Nkoabang","","24-10-2024 10:57:19","24-10-2024 10:49:18","27-10-2024 15:=
20:23","tikect need to cascade at Ctr_084 Nkoabang","Mba Lazare Herve","Cas=
cade Outage","Passive","Cascade Passive","Cascade Passive","grid outage, ge=
n fails to start due to gen card idysfunctionning//gen started manually","j=
oelle.ekessi@ihstowers.com","11377","24-10-2024 10:57:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0003398613","NGONA","=
","24-10-2024 10:55:50","24-10-2024 10:49:18","24-10-2024 12:59:33","Cascad=
ed Incident from TTO3282973","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage, gen fails to start due to=
 gen card idysfunctionning//gen started manually","system","392","24-10-202=
4 10:55:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003398606","N=
koabang","IHS_YND_295, IHS_YND_736","24-10-2024 10:54:46","24-10-2024 10:49=
:18","24-10-2024 12:59:33","grid outage, gen fails to start due to gen card=
 idysfunctionning//gen started manually","Mba Lazare Herve","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","grid outage, gen fails to =
start due to gen card idysfunctionning//gen started manually","joelle.ekess=
i@ihstowers.com","329","24-10-2024 10:54:46","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003398520","NTU=
I TOWN","","24-10-2024 10:39:19","24-10-2024 10:35:07","24-10-2024 11:49:56=
","Grid outage, gen ran until fuel shortage//Refueling done","Parker Tchoup=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, gen ran un=
til fuel shortage//Refueling done","emmanuel.ghani@ihstowers.com","253","24=
-10-2024 10:39:19","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003398496","Pha=
rmacie SION","","24-10-2024 10:36:47","24-10-2024 10:30:38","24-10-2024 10:=
52:57","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automaticaly","Paul BIBOUM","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen start automaticaly","emm=
anuel.ghani@ihstowers.com","370","24-10-2024 10:36:47","Sagemcom CMR"
"Closed Complete","Warning","T1259","IHS_YND_424","NOCINC0003398463","Ossom=
be","","24-10-2024 10:30:33","","","hybrid gen site //treshold autamoatical=
ly","Parker Tchoup","Warning","Warning","POWER","Warning - Site on Battery"=
,"hybrid gen site //treshold autamoatically","rouselle.schoune@ihstowers.co=
m","958","24-10-2024 10:30:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003398428","Yoko OCM=
","","24-10-2024 10:24:13","24-10-2024 10:15:30","24-10-2024 10:16:30","Cas=
caded Incident from TTO3282721","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 54.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","523","24-10-2024 10:24:13","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003398429","Ngouetou=
","","24-10-2024 10:24:13","24-10-2024 10:15:30","24-10-2024 10:16:30","Cas=
caded Incident from TTO3282721","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 54.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","523","24-10-2024 10:24:13","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003398426","Ngoum","=
","24-10-2024 10:24:12","24-10-2024 10:15:30","24-10-2024 10:16:30","Cascad=
ed Incident from TTO3282721","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Gen with U =3D 54=
.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959647=
of Huawei is informed","system","522","24-10-2024 10:24:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003398427","Matsari"=
,"","24-10-2024 10:24:12","24-10-2024 10:15:30","24-10-2024 10:16:30","Casc=
aded Incident from TTO3282721","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
54.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","522","24-10-2024 10:24:12","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003398404","B=
iteng-Maetur","","24-10-2024 10:22:57","24-10-2024 10:04:52","24-10-2024 11=
:49:45","grid outage, site went down because gen failed to started due to g=
en Overload(20kva, 280A)// He reduced the load and gen manually started","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"grid outage, site went down because gen failed to started due to gen Overl=
oad(20kva, 280A)// He reduced the load and gen manually started","kombi.sam=
uel@ihstowers.com","1086","24-10-2024 10:22:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003398365","B=
itoto","","24-10-2024 10:17:18","24-10-2024 10:15:12","24-10-2024 11:09:03"=
,"grid outage, site went down because gen failed to started due to gen Over=
load(20kva, 315A)// He reduced the load and gen manually started","Mba Laza=
re Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","grid o=
utage, site went down because gen failed to started due to gen Overload(20k=
va, 315A)// He reduced the load and gen manually started","olivier.kwedi@ih=
stowers.com","128","24-10-2024 10:17:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003398335","N=
koabang2","","24-10-2024 10:12:37","24-10-2024 10:09:29","24-10-2024 10:40:=
56","grid outage;gen stopped with alarm high temp//ge added water in radiat=
or","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High=
 Engine Temp - Coolant Level Issue","grid outage;gen stopped with alarm hig=
h temp//ge added water in radiator","olivier.kwedi@ihstowers.com","189","24=
-10-2024 10:12:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0003398309","C=
RH-Etoug-Ebe","","24-10-2024 10:09:15","24-10-2024 10:06:07","24-10-2024 10=
:34:21","Grid  bad voltage, site went down because Gen failed to start due =
to Grid bad voltage and RCP faulty//he bypassed Grid and Started Gen","Hyem=
afo Gildas","Equipment Repair","Passive","Control Panel","Power Cabinet - B=
attery Low","Grid  bad voltage, site went down because Gen failed to start =
due to Grid bad voltage and RCP faulty//he bypassed Grid and Started Gen","=
olivier.kwedi@ihstowers.com","189","24-10-2024 10:09:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0003398198","Nkolfon =
Cimencam","","24-10-2024 09:46:32","24-10-2024 09:44:50","24-10-2024 12:22:=
50","No power issue on site U=3D54,5v site on Gen The Rm Alain (691144423) =
of huawei is informed","Hyemafo Gildas","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D54,5v site on Gen The Rm Alain (691144423) of huawei is informed","joel=
le.ekessi@ihstowers.com","103","24-10-2024 09:46:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003398035","M=
IMBOMAN LIBERTE","","24-10-2024 09:26:12","24-10-2024 09:21:30","24-10-2024=
 10:44:45","Grid outage with main gen faulty //MDG of 20Kva deployed","Mba =
Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fau=
lty","Grid outage with main gen faulty //MDG of 20Kva deployed","joelle.eke=
ssi@ihstowers.com","283","24-10-2024 09:26:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003398009","Tradex-N=
komo","","24-10-2024 09:21:51","24-10-2024 09:16:49","24-10-2024 09:19:59",=
"Cascaded Incident from TTO3282216","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage, site went down before=
 Gen start due to poor backup// Gen started automatically","system","302","=
24-10-2024 09:21:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003397994","Biteng-M=
aetur","","24-10-2024 09:20:10","24-10-2024 09:16:49","24-10-2024 09:19:59"=
,"Cascaded Incident from TTO3282216","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage, site went down be=
fore Gen start due to poor backup// Gen started automatically","system","20=
1","24-10-2024 09:20:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003397978","B=
iteng","IHS_YND_172, IHS_YND_249","24-10-2024 09:19:34","24-10-2024 09:16:4=
9","24-10-2024 09:19:59","Grid Outage, site went down before Gen start due =
to poor backup// Gen started automatically","Mba Lazare Herve","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage=
, site went down before Gen start due to poor backup// Gen started automati=
cally","joelle.ekessi@ihstowers.com","166","24-10-2024 09:19:34","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003397950","S=
ous Prefecture","","24-10-2024 09:17:57","24-10-2024 09:13:15","24-10-2024 =
11:10:03","","Fanda Brice","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie:55,2V; =
site on Grid TX FME Hugo (672390202) from Huawei is informed.","olivier.kwe=
di@ihstowers.com","283","24-10-2024 09:17:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003397926","N=
kolbisson usine des eaux","","24-10-2024 09:14:57","24-10-2024 09:11:09","2=
4-10-2024 09:59:50","Grid outage with main gen faulty //MDG of 20Kva deploy=
ed","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACD=
G - Generator Faulty","Grid outage with main gen faulty //MDG of 20Kva depl=
oyed","joelle.ekessi@ihstowers.com","229","24-10-2024 09:14:57","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003397871","A=
ngongo","","24-10-2024 09:07:31","24-10-2024 09:02:26","24-10-2024 12:47:00=
","No power issue on site ubaie=3D54v site on grid","Fanda Brice","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site ubaie=3D54v site on grid","joelle.ekessi@ihstower=
s.com","306","24-10-2024 09:07:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0003397870","Nkolanga=
a","","24-10-2024 09:07:21","24-10-2024 08:56:49","24-10-2024 09:32:45","Ca=
scaded Incident from TTO3282094","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","lack of two grid phases, gen fails=
 to start//reconfigurated the RCP, site on grid","system","632","24-10-2024=
 09:07:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0003397869","Nkoulou =
Carriere carrefourt","","24-10-2024 09:07:20","24-10-2024 08:56:49","24-10-=
2024 09:32:45","Cascaded Incident from TTO3282094","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","lack of two grid=
 phases, gen fails to start//reconfigurated the RCP, site on grid","system"=
,"631","24-10-2024 09:07:20","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003397854","MBI=
MBIM","","24-10-2024 09:04:33","24-10-2024 08:55:24","24-10-2024 10:16:30",=
"Site went down because Gen started and stopped due to water infiltration i=
n the tank//  He purged the tank, site on gen","Parker Tchoup","Fuel Outage=
 (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","S=
ite went down because Gen started and stopped due to water infiltration in =
the tank//  He purged the tank, site on gen","emmanuel.ghani@ihstowers.com"=
,"551","24-10-2024 09:04:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0003397821","A=
bang","IHS_YND_794, IHS_YND_289","24-10-2024 08:57:50","24-10-2024 08:56:49=
","24-10-2024 09:32:45","","Mba Lazare Herve","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","lack of two grid phases, gen f=
ails to start//reconfigurated the RCP, site on grid","joelle.ekessi@ihstowe=
rs.com","63","24-10-2024 08:57:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003397718","Afanoya"=
,"","24-10-2024 08:38:21","24-10-2024 08:33:02","24-10-2024 08:41:27","Casc=
aded Incident from TTO3281931","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, DG Failed to start due to=
 overload (20Kva, 300A),and poor batteries backup // The site stabilised","=
system","319","24-10-2024 08:38:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003397717","MBALNGON=
G LYCEE","","24-10-2024 08:38:20","24-10-2024 08:33:02","24-10-2024 08:41:2=
7","Cascaded Incident from TTO3281931","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start d=
ue to overload (20Kva, 300A),and poor batteries backup // The site stabilis=
ed","system","318","24-10-2024 08:38:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003397716","ELOUMDEM=
 CARRIERE","","24-10-2024 08:38:20","24-10-2024 08:33:02","24-10-2024 08:41=
:27","Cascaded Incident from TTO3281931","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start=
 due to overload (20Kva, 300A),and poor batteries backup // The site stabil=
ised","system","318","24-10-2024 08:38:20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003397712","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","24-10-2024 08:36:58","24-10-20=
24 08:33:02","24-10-2024 08:41:27","Grid outage, DG Failed to start due to =
overload (20Kva, 300A),and poor batteries backup // The site stabilised","H=
yemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","G=
rid outage, DG Failed to start due to overload (20Kva, 300A),and poor batte=
ries backup // The site stabilised","emmanuel.ghani@ihstowers.com","237","2=
4-10-2024 08:36:58","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_341","NOCINC0003397666","Lobo OCM","","24=
-10-2024 08:27:11","","","Cascaded Incident from TTO3281866","TIENTCHEU NZE=
TCHIEU GAEL","","","","","","system","298","24-10-2024 08:27:11","Sagemcom =
CMR"
"Cancelled","Warning","SUD_016","IHS_YND_332","NOCINC0003397661","NKOMEKUI =
OCM","IHS_YND_341","24-10-2024 08:26:35","","","","TIENTCHEU NZETCHIEU GAEL=
","","","","","","joelle.ekessi@ihstowers.com","262","24-10-2024 08:26:35",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0003397635","S=
AA 2","","24-10-2024 08:20:08","24-10-2024 08:14:47","24-10-2024 09:20:35",=
"Grid bad voltage,Site went down because Gen failed to start due Grid bad V=
oltage and No RCP on site //He bypassed and started Gen","Parker Tchoup","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gri=
d bad voltage,Site went down because Gen failed to start due Grid bad Volta=
ge and No RCP on site //He bypassed and started Gen","joelle.ekessi@ihstowe=
rs.com","322","24-10-2024 08:20:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0003397592","N=
kolkoumou OCM","","24-10-2024 08:12:43","24-10-2024 08:07:23","24-10-2024 0=
9:26:00","FME is on the way to the site ETA=3D09:10 AM","TIENTCHEU NZETCHIE=
U GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","gri=
d outage, site down because gen stopped due to low oil pressure//added oil =
and restart the gen","joelle.ekessi@ihstowers.com","321","24-10-2024 08:12:=
43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0003397473","A=
n-Marche-Melen","","24-10-2024 07:56:28","24-10-2024 07:53:03","24-10-2024 =
08:52:30","Grid outage.no space to deploy mobile gen//Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.=
no space to deploy mobile gen//Grid return","joelle.ekessi@ihstowers.com","=
206","24-10-2024 07:56:28","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003397394","NKO=
MEKUI OCM","","24-10-2024 07:42:15","24-10-2024 07:38:22","24-10-2024 07:46=
:12","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // Gen start automat=
icaly","emmanuel.ghani@ihstowers.com","234","24-10-2024 07:42:15","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003397294","Ndogbess=
ol","","24-10-2024 07:27:30","24-10-2024 07:22:40","24-10-2024 07:33:11","C=
ascaded Incident from TTO3281425","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, Gen started but did n=
ot feeds the site due to Gen contactor dysfunction// He blocked Gen contact=
or, Site on Gen","system","290","24-10-2024 07:27:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_286","IHS_YND_381","NOCINC0003397287","B=
oumnyebel","IHS_EDA_056","24-10-2024 07:26:06","24-10-2024 07:22:40","24-10=
-2024 07:33:39","Grid outage, Gen started but did not feeds the site due to=
 Gen contactor dysfunction// He blocked Gen contactor, Site on Gen","Kemeni=
 Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor",=
"Grid outage, Gen started but did not feeds the site due to Gen contactor d=
ysfunction// He blocked Gen contactor, Site on Gen","joelle.ekessi@ihstower=
s.com","207","24-10-2024 07:26:06","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0003397185","Lob=
o 2","","24-10-2024 06:58:53","24-10-2024 06:55:05","24-10-2024 07:05:29","=
grid outage, site went down because gen start and stoppen with alarm Underv=
oltage// He reset gen card and gen manually started","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid o=
utage, site went down because gen start and stoppen with alarm Undervoltage=
// He reset gen card and gen manually started","emmanuel.ghani@ihstowers.co=
m","228","24-10-2024 06:58:53","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0003397147","Ako=
k Ndoe Yde","","24-10-2024 06:51:00","24-10-2024 06:48:13","24-10-2024 07:5=
0:58","Grid  bad voltage, site went down because Gen failed to start due to=
 Grid bad voltage//he bypassed Grid and Started Gen","Hyemafo Gildas","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid  =
bad voltage, site went down because Gen failed to start due to Grid bad vol=
tage//he bypassed Grid and Started Gen","emmanuel.ghani@ihstowers.com","168=
","24-10-2024 06:51:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003397112","M=
ini-Ferme","","24-10-2024 06:43:07","24-10-2024 06:40:21","24-10-2024 08:55=
:48","Grid outage .no space to deploy mobile gen .grid power awaited","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outa=
ge, no space to deploy a mobile gen// grid return","joelle.ekessi@ihstowers=
.com","167","24-10-2024 06:43:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0003396901","Jean Ves=
pa 2","","24-10-2024 05:48:00","24-10-2024 05:37:33","24-10-2024 06:00:01",=
"Cascaded Incident from TTO3280981","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel sho=
rtage//Refueling done","system","627","24-10-2024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003396893","J=
-Vespa","IHS_YND_544","24-10-2024 05:46:26","24-10-2024 05:37:33","24-10-20=
24 06:00:01","Grid outage.gen ran until fuel shortage//Refueling done","Mbo=
ua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.g=
en ran until fuel shortage//Refueling done","olivier.kwedi@ihstowers.com","=
533","24-10-2024 05:46:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003396892","Crf-Mban=
kolo-IHS","","24-10-2024 05:46:21","24-10-2024 05:37:03","24-10-2024 06:10:=
16","Cascaded Incident from TTO3280965","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage.gen ran until fuel=
 shortage//Refueling done ","system","558","24-10-2024 05:46:21","Sagemcom =
CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003396878","Jea=
n Vespa","IHS_YND_574","24-10-2024 05:40:59","24-10-2024 05:37:03","24-10-2=
024 06:10:16","Grid outage.gen ran until fuel shortage//Refueling done ","M=
boua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage=
.gen ran until fuel shortage//Refueling done ","stephane.nkamwa@ihstowers.c=
om","236","24-10-2024 05:40:59","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003396648","Feb=
e Village","","24-10-2024 04:16:59","24-10-2024 04:08:44","24-10-2024 06:30=
:40","Grid outage.gen ran until fuel shortage//Refueling done","Mboua Thier=
ry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran u=
ntil fuel shortage//Refueling done","stephane.nkamwa@ihstowers.com","720","=
24-10-2024 04:16:59","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003396599","NKO=
MEKUI OCM","","24-10-2024 04:06:02","24-10-2024 03:57:52","24-10-2024 04:05=
:06","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // Gen start automat=
icaly","stephane.nkamwa@ihstowers.com","491","24-10-2024 04:06:02","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0003395374","T=
alla Monatele","","23-10-2024 23:03:54","23-10-2024 22:53:38","24-10-2024 0=
1:54:34","No power issue on site ,site on Grid with Ubaie =3D54.7 V The Tx =
Fme Gregoire( 652070658)from Huawei is informed.","Parker Tchoup","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site ,site on Grid with Ubaie =3D54.7 V The Tx Fme Gre=
goire( 652070658)from Huawei is informed.","olivier.kwedi@ihstowers.com","6=
16","23-10-2024 23:03:54","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003395245","Nsi=
meyong Shell","","23-10-2024 22:49:22","23-10-2024 22:06:15","24-10-2024 00=
:16:50","Grid fluctuation ,gen failed to start due to grid bad voltage// he=
 bypass grid and manually startad  the gen","MINKA NICOLAS","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation=
 ,gen failed to start due to grid bad voltage// he bypass grid and manually=
 startad  the gen","stephane.nkamwa@ihstowers.com","2588","23-10-2024 22:49=
:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0003395212","S=
hell-Nsimeyong","","23-10-2024 22:43:55","23-10-2024 22:06:41","24-10-2024 =
00:11:40","Grid fluctuation ,gen failed to start due to grid bad voltage// =
he bypass grid and manually startad  the gen","MINKA NICOLAS","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuati=
on ,gen failed to start due to grid bad voltage// he bypass grid and manual=
ly startad  the gen","olivier.kwedi@ihstowers.com","2235","23-10-2024 22:43=
:55","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003394823","Lad=
a I Yde","","23-10-2024 21:42:36","23-10-2024 21:08:20","23-10-2024 22:26:2=
2","Site went down because CB 63  A who feeds equipment MTN  disjuncted in =
DC BOX // he rearmed CB","Mba Lazare Herve","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Circuit Breaker Issue","Site went down becau=
se CB 63  A who feeds equipment MTN  disjuncted in DC BOX // he rearmed CB"=
,"kamga.virgile@ihstowers.com","2057","23-10-2024 21:42:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003394295","MEHANDAN=
","","23-10-2024 20:42:40","23-10-2024 20:31:03","23-10-2024 21:55:38","Cas=
caded Incident from TTO3277854","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation site went down becaus=
e Gen failed to start du to Grid bad voltage and No RCP on site // He bypas=
sed   Grid  and started Gen","system","697","23-10-2024 20:42:40","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003394239","O=
dza II OCM","IHS_YND_528","23-10-2024 20:40:10","23-10-2024 20:31:03","23-1=
0-2024 21:55:38","Grid fluctuation site went down because Gen failed to sta=
rt du to Grid bad voltage and No RCP on site // He bypassed   Grid  and sta=
rted Gen","Albran Byorel","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","Grid fluctuation site went down because Gen failed=
 to start du to Grid bad voltage and No RCP on site // He bypassed   Grid  =
and started Gen","alexandre.kamal@ihstowers.com","549","23-10-2024 20:40:10=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0003393633","E=
BOM","","23-10-2024 18:57:31","23-10-2024 18:31:26","23-10-2024 19:10:29","=
Grid bad voltage ,site went down because Gen failed to start due to Grid ba=
d voltage and No RCP// he bypassed Grid and started Gen manually","Hyemafo =
Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid bad voltage ,site went down because Gen failed to start due to =
Grid bad voltage and No RCP// he bypassed Grid and started Gen manually","a=
lexandre.kamal@ihstowers.com","1566","23-10-2024 18:57:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0003393100","Nkolkoum=
ou OCM","","23-10-2024 17:27:30","23-10-2024 17:15:32","23-10-2024 17:53:16=
","Cascaded Incident from TTO3276426","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive"," Grid outage with mai=
n gen faulty //MDG of  20Kva deployed","system","718","23-10-2024 17:27:30"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003393055","N=
kolbisson usine des eaux","IHS_YND_712","23-10-2024 17:19:36","23-10-2024 1=
7:15:32","23-10-2024 17:53:16"," Grid outage with main gen faulty //MDG of =
 20Kva deployed","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid",=
"National Grid - Grid Outage Issue"," Grid outage with main gen faulty //MD=
G of  20Kva deployed","alexandre.kamal@ihstowers.com","244","23-10-2024 17:=
19:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003393047","S=
ous Prefecture","","23-10-2024 17:18:05","23-10-2024 16:59:39","24-10-2024 =
01:10:36","Active//No power isssue, site is on Gen with Ubaie=3D54,2V,  TX =
FME PATRICK (672390202) from Huawei is informed","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power isssue, site is on Gen with Ubaie=3D54,2V,  TX FME PATRICK=
 (672390202) from Huawei is informed","alexandre.kamal@ihstowers.com","1107=
","23-10-2024 17:18:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_369","IHS_YND_019","NOCINC0003392942","H=
otel de Ville Yde","","23-10-2024 17:01:36","23-10-2024 14:56:22","23-10-20=
24 16:47:11","Site went down because CB 80 A who feeds equipment Ocm disjun=
cted in DC BOX // he rearmed CB","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down be=
cause CB 80 A who feeds equipment Ocm disjuncted in DC BOX // he rearmed CB=
","alexandre.kamal@ihstowers.com","7515","23-10-2024 17:01:36","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003392923","N=
kolndongo","","23-10-2024 16:58:02","23-10-2024 16:44:58","23-10-2024 16:57=
:19","Grid Outage and Main Gen Faulty//Grid Restored","MINKA NICOLAS","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid Outage a=
nd Main Gen Faulty//Grid Restored","alexandre.kamal@ihstowers.com","785","2=
3-10-2024 16:58:02","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003392848","NYO=
M FACE MAETUR","","23-10-2024 16:48:46","23-10-2024 16:39:41","23-10-2024 1=
6:53:07","Grid outage, Landlord has forbidden to start the generator due to=
 noise // Grid restored","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Emergency Stop","Grid outage, Landlord has forbidden to sta=
rt the generator due to noise // Grid restored","christian.fonkou@ihstowers=
.com","545","23-10-2024 16:48:46","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003392645","Eko=
unou","","23-10-2024 16:23:27","23-10-2024 16:15:22","23-10-2024 16:33:53",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automaticaly","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen start automaticaly","christia=
n.fonkou@ihstowers.com","487","23-10-2024 16:23:27","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0003392266","Obo=
bogo","","23-10-2024 15:33:27","23-10-2024 15:25:21","23-10-2024 15:37:08",=
"Grid fluctuation, site went down before Gen start due to poor backup  // G=
en start automaticaly","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid fluctuation, site went down be=
fore Gen start due to poor backup  // Gen start automaticaly","christian.fo=
nkou@ihstowers.com","487","23-10-2024 15:33:27","Sagemcom CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0003392202","Sca=
lom","","23-10-2024 15:24:24","23-10-2024 15:19:18","23-10-2024 15:51:18","=
Grid outage.gen ran unti fuel shortage// Refueling done","Paul BIBOUM","Fue=
l Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unti fuel=
 shortage// Refueling done","christian.fonkou@ihstowers.com","307","23-10-2=
024 15:24:24","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003391924","N=
yanon","","23-10-2024 14:50:35","23-10-2024 14:36:31","24-10-2024 01:26:42"=
,"No power issue on site ,site on Gen with Ubaie=3D53V, Tx Fme Gregoire( 65=
2070658)From Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site ,site on Gen with Ubaie=3D53V, Tx Fme Gregoire( 6520706=
58)From Huawei is informed","alexandre.kamal@ihstowers.com","846","23-10-20=
24 14:50:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003391838","N=
kolndongo","","23-10-2024 14:39:15","23-10-2024 14:15:08","23-10-2024 14:37=
:28","Grid outage with main gen faulty//MDG of 20 kva has deployed","MINKA =
NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty",=
"Grid outage with main gen faulty//MDG of 20 kva has deployed","alexandre.k=
amal@ihstowers.com","1448","23-10-2024 14:39:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003391827","M=
aison-Blanche-IHS","","23-10-2024 14:37:42","23-10-2024 14:29:39","23-10-20=
24 15:03:35","Grid outage.no space to deploy mobile gen.//Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age.no space to deploy mobile gen.//Grid return","alexandre.kamal@ihstowers=
.com","484","23-10-2024 14:37:42","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003391824","Nko=
mo stade","","23-10-2024 14:36:21","23-10-2024 14:18:09","23-10-2024 15:47:=
01","Site went down due to work Blaise Raoul /657108509/IHS normalization o=
f starting order //End of work","Mba Lazare Herve","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Site went down due to=
 work Blaise Raoul /657108509/IHS normalization of starting order //End of =
work","kamga.virgile@ihstowers.com","1093","23-10-2024 14:36:21","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0003391504","B=
otmakak","IHS_EDA_101","23-10-2024 13:50:56","23-10-2024 13:43:43","24-10-2=
024 01:50:43","no power issue U=3D54V site on Grid. the TX FME ETienne// 69=
5033981// / from huawei is informed and Up at 01:56 PM","Kemeni Franklin","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","no power issue U=3D54V site on Grid. the TX FME ETienne// 695033=
981// / from huawei is informed and Up at 01:56 PM","kouoh.jean@ihstowers.c=
om","434","23-10-2024 13:50:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003391485","N=
yom OCM","","23-10-2024 13:48:37","23-10-2024 13:36:30","23-10-2024 13:51:2=
2","no power issue  Ubaie:54.4 V   site on Grid,    tx fme symphorien /6502=
57151 from huawei is inform","Fabrice Pouakam","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue  =
Ubaie:54.4 V   site on Grid,    tx fme symphorien /650257151 from huawei is=
 inform","kouoh.jean@ihstowers.com","728","23-10-2024 13:48:37","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0003391444","A=
nguissa New","","23-10-2024 13:43:52","23-10-2024 13:33:23","23-10-2024 14:=
49:28","Grid outage.gen failed to start due to automation malfunctionning//=
gen manually started ","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","ATS-AMF Issue","Grid outage.gen failed to start due to automation=
 malfunctionning//gen manually started ","kouoh.jean@ihstowers.com","630","=
23-10-2024 13:43:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003391314","A=
wae Ewonkan","","23-10-2024 13:20:13","23-10-2024 13:17:31","23-10-2024 14:=
01:37","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // he bypass grid and manually start the gen","Albran B=
yorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage // he bypass grid and manually start the gen","kouoh.jean=
@ihstowers.com","162","23-10-2024 13:20:13","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003391267","MEF=
OU ASSI","","23-10-2024 13:10:33","23-10-2024 13:07:26","23-10-2024 13:11:2=
6","site went down because insufficiency of rectifiers due to increase load=
 on site // He reduced the load","Fanda Brice","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module","site went down because insufficiency of re=
ctifiers due to increase load on site // He reduced the load","christian.fo=
nkou@ihstowers.com","188","23-10-2024 13:10:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003391032","Eseka To=
wn","","23-10-2024 12:38:35","23-10-2024 11:59:01","23-10-2024 12:17:14","C=
ascaded Incident from TTO3273805","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work(normali=
zation cables) done by Daniel Wakam(695322396) and  thetft of battery backu=
p//End of work ","system","2374","23-10-2024 12:38:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0003391028","Eseka MT=
N","","23-10-2024 12:38:34","23-10-2024 11:59:01","23-10-2024 12:17:14","Ca=
scaded Incident from TTO3273805","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work(normaliz=
ation cables) done by Daniel Wakam(695322396) and  thetft of battery backup=
//End of work ","system","2373","23-10-2024 12:38:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003391023","Ndogbess=
ol","","23-10-2024 12:38:33","23-10-2024 11:59:01","23-10-2024 12:17:14","C=
ascaded Incident from TTO3273805","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work(normali=
zation cables) done by Daniel Wakam(695322396) and  thetft of battery backu=
p//End of work ","system","2372","23-10-2024 12:38:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003391019","Boumnyeb=
el","","23-10-2024 12:38:32","23-10-2024 11:59:01","23-10-2024 12:17:14","C=
ascaded Incident from TTO3273805","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work(normali=
zation cables) done by Daniel Wakam(695322396) and  thetft of battery backu=
p//End of work ","system","2371","23-10-2024 12:38:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003391016","Mamb",""=
,"23-10-2024 12:38:31","23-10-2024 11:59:01","23-10-2024 12:17:14","Cascade=
d Incident from TTO3273805","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to work(normalization=
 cables) done by Daniel Wakam(695322396) and  thetft of battery backup//End=
 of work ","system","2370","23-10-2024 12:38:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_416","NOCINC0003391015","Ngwopi B=
oga","","23-10-2024 12:38:31","23-10-2024 11:59:01","23-10-2024 12:17:14","=
Cascaded Incident from TTO3273805","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to work(normal=
ization cables) done by Daniel Wakam(695322396) and  thetft of battery back=
up//End of work ","system","2370","23-10-2024 12:38:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0003390148","S=
AA 2","","23-10-2024 11:41:33","23-10-2024 11:16:16","23-10-2024 11:20:16",=
"No power issue on site ,site on Grid with Ubaie=3D54,1V, Tx Fme Gregoire( =
652070658)From Huawei is informed","Parker Tchoup","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site ,site on Grid with Ubaie=3D54,1V, Tx Fme Gregoire( 652070658)Fro=
m Huawei is informed","kouoh.jean@ihstowers.com","1518","23-10-2024 11:41:3=
3","Sagemcom CMR"
"Closed Complete","Site Down","CTR_115","IHS_YND_375","NOCINC0003389777","N=
goung","","23-10-2024 10:42:45","23-10-2024 10:32:37","23-10-2024 12:17:14"=
,"grid outage,gen ran till fuel shortage//Refueling done","Kemeni Franklin"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran till=
 fuel shortage//Refueling done","kouoh.jean@ihstowers.com","608","23-10-202=
4 10:42:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0003389509","M=
beng","IHS_YND_553","23-10-2024 10:03:56","23-10-2024 09:56:48","23-10-2024=
 12:13:35","site went down because 1/2rectifier disfunctionning//he reset t=
he rectifier","Fanda Brice","Equipment Repair","Passive","Rectifier","Recti=
fier Module","site went down because 1/2rectifier disfunctionning//he reset=
 the rectifier","kouoh.jean@ihstowers.com","429","23-10-2024 10:03:56","Sag=
emcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003389373","Lab=
oratoire  Meka","IHS_YND_193","23-10-2024 09:43:16","23-10-2024 09:32:11","=
23-10-2024 11:28:36","Grid outage no space to deploy MDG //Grid return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage no space to deploy MDG //Grid return","landry.etame@ihstowers.com","66=
5","23-10-2024 09:43:16","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003389358","Bas=
tos Ekoudou","","23-10-2024 09:42:03","23-10-2024 09:32:11","23-10-2024 11:=
28:36","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage no space to deploy MDG //Grid return","landry.et=
ame@ihstowers.com","1580","23-10-2024 09:42:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0003389267","E=
BOM","","23-10-2024 09:27:57","23-10-2024 09:25:48","23-10-2024 10:13:58","=
Grid outage, site went down because gen ran untill fuel shortage // refueli=
ng done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran untill fuel shortage // refuel=
ing done","kouoh.jean@ihstowers.com","130","23-10-2024 09:27:57","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0003389221","E=
mombo","","23-10-2024 09:22:29","23-10-2024 09:17:12","23-10-2024 09:21:12"=
,"Grid outage, Site went down because CB battery backup tripped// Gen start=
ed automaticaly and CB battery put back on (investigation ongoing)","Mba La=
zare Herve","Equipment Repair","Passive","Control Panel","Power Cabinet - C=
ircuit Breaker Issue","Grid outage, Site went down because CB battery backu=
p tripped// Gen started automaticaly and CB battery put back on (investigat=
ion ongoing)","kouoh.jean@ihstowers.com","318","23-10-2024 09:22:29","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003388615","M=
arche Odza","","23-10-2024 07:23:03","23-10-2024 07:14:43","23-10-2024 08:4=
8:36","Grid outage, Gen started but did not feeds the site due to Gen conta=
ctor disfunction// He blocked Gen contactor, Site on Gen","Albran Byorel","=
Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage, G=
en started but did not feeds the site due to Gen contactor disfunction// He=
 blocked Gen contactor, Site on Gen","kouoh.jean@ihstowers.com","501","23-1=
0-2024 07:23:03","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0003388586","Mam=
bine","","23-10-2024 07:15:50","23-10-2024 07:09:25","23-10-2024 07:54:44",=
"site went down because gen ran till fuel shortage//Refueling done","Fanda =
Brice","Fuel Outage","Passive","Diesel","Diesel Outage","site went down bec=
ause gen ran till fuel shortage//Refueling done","landry.etame@ihstowers.co=
m","426","23-10-2024 07:15:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003388503","Eseka To=
wn","","23-10-2024 07:05:55","23-10-2024 06:59:58","23-10-2024 07:07:51","C=
ascaded Incident from TTO3271089","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Theft Incident : Grid fluctuation,=
 Site went down due to theft of battery backup// He bypassed Grid and start=
ed Gen manualy","system","357","23-10-2024 07:05:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_379","NOCINC0003388499","Eseka MT=
N","","23-10-2024 07:05:54","23-10-2024 06:59:58","23-10-2024 07:07:51","Ca=
scaded Incident from TTO3271089","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Theft Incident : Grid fluctuation, =
Site went down due to theft of battery backup// He bypassed Grid and starte=
d Gen manualy","system","356","23-10-2024 07:05:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003388494","Ndogbess=
ol","","23-10-2024 07:05:53","23-10-2024 06:59:58","23-10-2024 07:07:51","C=
ascaded Incident from TTO3271089","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Theft Incident : Grid fluctuation,=
 Site went down due to theft of battery backup// He bypassed Grid and start=
ed Gen manualy","system","355","23-10-2024 07:05:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003388490","Boumnyeb=
el","","23-10-2024 07:05:52","23-10-2024 06:59:58","23-10-2024 07:07:51","C=
ascaded Incident from TTO3271089","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Theft Incident : Grid fluctuation,=
 Site went down due to theft of battery backup// He bypassed Grid and start=
ed Gen manualy","system","354","23-10-2024 07:05:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0003388486","Ngoung",=
"","23-10-2024 07:05:51","23-10-2024 06:59:58","23-10-2024 07:07:51","Casca=
ded Incident from TTO3271089","Kemeni Franklin","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Theft Incident : Grid fluctuation, Sit=
e went down due to theft of battery backup// He bypassed Grid and started G=
en manualy","system","353","23-10-2024 07:05:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003388485","Mamb",""=
,"23-10-2024 07:05:51","23-10-2024 06:59:58","23-10-2024 07:07:51","Cascade=
d Incident from TTO3271089","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Theft Incident : Grid fluctuation, Site =
went down due to theft of battery backup// He bypassed Grid and started Gen=
 manualy","system","353","23-10-2024 07:05:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_416","NOCINC0003388484","Ngwopi B=
oga","","23-10-2024 07:05:50","23-10-2024 06:59:58","23-10-2024 07:07:51","=
Cascaded Incident from TTO3271089","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Theft Incident : Grid fluctuation=
, Site went down due to theft of battery backup// He bypassed Grid and star=
ted Gen manualy","system","352","23-10-2024 07:05:50","Sagemcom CMR"
"Closed Complete","Warning","T1618","IHS_YND_305","NOCINC0003388226","NYOM"=
,"","23-10-2024 06:11:04","","","Site alarming on battery because Gen ran u=
ntill fuel shortage// Refueling Done","Fabrice Pouakam","Warning","Warning"=
,"POWER","Warning - Site on Battery","Site alarming on battery because Gen =
ran untill fuel shortage// Refueling Done","alwine.fambou@ihstowers.com","2=
","23-10-2024 06:11:04","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003387859","Bas=
tos Amb Coree","","23-10-2024 04:41:59","23-10-2024 04:38:54","23-10-2024 0=
9:14:07","Grid outage , no space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage , no=
 space to deploy MDG // Grid return","ludivine.ngamaleu@ihstowers.com","186=
","23-10-2024 04:41:59","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003387834","OBA=
M NGOLA OCM","","23-10-2024 04:35:56","23-10-2024 04:29:51","23-10-2024 04:=
47:01","Site went down because 01/04 rectifier faulty//he reduice the load =
on site (need to change the faulty rectifier)","MINKA NICOLAS","Equipment R=
epair","Passive","Rectifier","Rectifier Module","Site went down because 01/=
04 rectifier faulty//he reduice the load on site (need to change the faulty=
 rectifier)","ludivine.ngamaleu@ihstowers.com","366","23-10-2024 04:35:56",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003387757","N=
kolo II New","","23-10-2024 04:15:30","23-10-2024 04:04:22","23-10-2024 04:=
10:03","No power issue, site is on Grid with Ubaie=3D53,4V, Lionel adjep(65=
5184876) from Huawei is informed","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on Grid with Ubaie=3D53,4V, Lionel adjep(655184876) from Huaw=
ei is informed","alwine.fambou@ihstowers.com","669","23-10-2024 04:15:30","=
Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003387645","Mok=
olo Yaounde","","23-10-2024 03:50:41","23-10-2024 03:45:35","23-10-2024 09:=
13:28","Grid outage , no space to deploy MDG// Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage , no sp=
ace to deploy MDG// Grid return","ludivine.ngamaleu@ihstowers.com","307","2=
3-10-2024 03:50:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0003387607","E=
vodoula OCM","","23-10-2024 03:36:33","23-10-2024 03:28:26","23-10-2024 03:=
57:29","Grid outage , site went down because Gen stopped with ""high temp""=
 alarm causing by exhaust pipe  pierced//He connected exhaust pipe and star=
ted Gen manualy","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","A=
CDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage , sit=
e went down because Gen stopped with ""high temp"" alarm causing by exhaust=
 pipe  pierced//He connected exhaust pipe and started Gen manualy","alwine.=
fambou@ihstowers.com","488","23-10-2024 03:36:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003387585","N=
gouetou","","23-10-2024 03:31:21","23-10-2024 03:20:14","23-10-2024 03:30:1=
4","No power issue on site U=3D52V site on Gen   The Tx FME Gregoire/654547=
479 from huawei is informed. ","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D52V site on Gen   The Tx FME Gregoire/654547479 from huawei is i=
nformed. ","alwine.fambou@ihstowers.com","668","23-10-2024 03:31:21","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003387477","Eseka To=
wn","","23-10-2024 02:58:33","23-10-2024 02:46:13","23-10-2024 02:53:54","C=
ascaded Incident from TTO3269900","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No  power issue on site ,site on Gen =
with  Ubaie=3D54 V The TX FME Mbah Hosiah (674007438) from Huawei is inform=
ed.Site up at 02:23 AM","system","740","23-10-2024 02:58:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003387469","Ndogbess=
ol","","23-10-2024 02:58:32","23-10-2024 02:46:13","23-10-2024 02:53:54","C=
ascaded Incident from TTO3269900","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No  power issue on site ,site on Gen =
with  Ubaie=3D54 V The TX FME Mbah Hosiah (674007438) from Huawei is inform=
ed.Site up at 02:23 AM","system","739","23-10-2024 02:58:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003387464","Boumnyeb=
el","","23-10-2024 02:58:31","23-10-2024 02:46:13","23-10-2024 02:53:54","C=
ascaded Incident from TTO3269900","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No  power issue on site ,site on Gen =
with  Ubaie=3D54 V The TX FME Mbah Hosiah (674007438) from Huawei is inform=
ed.Site up at 02:23 AM","system","738","23-10-2024 02:58:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0003387461","Ngoung",=
"","23-10-2024 02:58:30","23-10-2024 02:46:13","23-10-2024 02:53:54","Casca=
ded Incident from TTO3269900","Kemeni Franklin","Cascade Outage","Active","=
Cascade Active","Cascade Active","No  power issue on site ,site on Gen with=
  Ubaie=3D54 V The TX FME Mbah Hosiah (674007438) from Huawei is informed.S=
ite up at 02:23 AM","system","737","23-10-2024 02:58:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003387460","Mamb",""=
,"23-10-2024 02:58:30","23-10-2024 02:46:13","23-10-2024 02:53:54","Cascade=
d Incident from TTO3269900","Kemeni Franklin","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No  power issue on site ,site on Gen with  =
Ubaie=3D54 V The TX FME Mbah Hosiah (674007438) from Huawei is informed.Sit=
e up at 02:23 AM","system","737","23-10-2024 02:58:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_416","NOCINC0003387459","Ngwopi B=
oga","","23-10-2024 02:58:30","23-10-2024 02:46:13","23-10-2024 02:53:54","=
Cascaded Incident from TTO3269900","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No  power issue on site ,site on Gen=
 with  Ubaie=3D54 V The TX FME Mbah Hosiah (674007438) from Huawei is infor=
med.Site up at 02:23 AM","system","737","23-10-2024 02:58:30","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003387363","N=
yom OCM","","23-10-2024 02:29:12","23-10-2024 02:28:04","23-10-2024 04:28:1=
1","No power issue on site ,site on Grid wiyh Ubaie=3D54.1 V The  fme symph=
orien /650257151 from huawei is informed","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site ,site on Grid wiyh Ubaie=3D54.1 V The  fme symphorien /=
650257151 from huawei is informed","alwine.fambou@ihstowers.com","69","23-1=
0-2024 02:29:12","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003387354","Nsi=
meyong Shell","","23-10-2024 02:23:32","23-10-2024 02:14:25","23-10-2024 03=
:36:59","grid outage,gen failed o start due to grid bad voltage//grid stabi=
lized","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","grid outage,gen failed to start due to grid bad volta=
ge//grid stabilized","ludivine.ngamaleu@ihstowers.com","548","23-10-2024 02=
:23:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0003387348","S=
hell-Nsimeyong","","23-10-2024 02:21:51","23-10-2024 02:14:41","23-10-2024 =
03:31:54","grid outage,gen failed to start due to grid bad voltage//grid st=
abilized","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","grid outage,gen failed to start due to grid bad vo=
ltage//grid stabilized","alwine.fambou@ihstowers.com","430","23-10-2024 02:=
21:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003387199","A=
kak-Nkozoa-MTN-IHS","","23-10-2024 01:28:05","23-10-2024 01:19:58","23-10-2=
024 03:14:51","Grid outage, site went down because gen ran untill fuel shor=
tage // refueling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel",=
"Diesel Outage","Grid outage, site went down because gen ran untill fuel sh=
ortage // refueling done","alwine.fambou@ihstowers.com","488","23-10-2024 0=
1:28:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003387003","M=
ini-Ferme","","23-10-2024 01:01:50","23-10-2024 00:29:41","23-10-2024 02:40=
:39","No power issue on site ,Site on Grid with Ubaie=3D56  V  TheTX FME Mo=
hamadou(691144435) from hauwei is informed","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site ,Site on Grid with Ubaie=3D56  V  TheTX FME Mohamadou(691144435) fro=
m hauwei is informed","alwine.fambou@ihstowers.com","1930","23-10-2024 01:0=
1:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003386996","T=
ongolo OCM","","23-10-2024 01:00:01","23-10-2024 00:22:53","23-10-2024 02:4=
2:31","No power issue on site ,site on Grid The Fme Tx Armand Ngeutsa/69994=
9553/from HUAWEI is informed.","Delor Telezing","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site ,site on Grid The Fme Tx Armand Ngeutsa/699949553/from HUAWEI is in=
formed.","alwine.fambou@ihstowers.com","2229","23-10-2024 01:00:01","Sagemc=
om CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003386941","BIY=
EMASSI NIKI","","23-10-2024 00:44:17","23-10-2024 00:36:11","23-10-2024 07:=
07:56","Access Issue during the Night: site went down due to insufficience =
of rectifier on site(04)// He added 01 rectifer (Site on 05 rectifier)","Hy=
emafo Gildas","Access Denial","Lease Or Legal","Landlord Related Issues","A=
ccess Issue - Land Lord","Access Issue during the Night: site went down due=
 to insufficience of rectifier on site(04)// He added 01 rectifer (Site on =
05 rectifier)","ludivine.ngamaleu@ihstowers.com","486","23-10-2024 00:44:17=
","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0003386851","Eto=
 koss Yde","","23-10-2024 00:06:16","22-10-2024 23:59:07","23-10-2024 00:34=
:05","Site went down due Grid CB(32A) disjuncted and Gen failed to start du=
e to fuel shortage //He reamed CB,Site on Grid .Power issue resolved 00.34 =
AM ,but site still down  power reset done The Tx  fme tx","Fanda Brice","Gr=
id Supply","Passive","Grid","National Grid - Circuit Breaker","Site went do=
wn due Grid CB(32A) disjuncted and Gen failed to start due to fuel shortage=
 //He reamed CB,Site on Grid .Power issue resolved 00.34 AM ,but site still=
 down  power reset done The Tx  fme tx HUGO/ 672390202 from Huawei is infor=
med","ludivine.ngamaleu@ihstowers.com","431","23-10-2024 00:06:16","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003386772","Essomba"=
,"","22-10-2024 23:41:30","22-10-2024 20:35:21","23-10-2024 00:55:08","No p=
ower issue on site ,site on Grid with Ubaie=3D54.1 V The fme tx HUGO/ 67239=
0202 from Huawei is informed. Notice that we have disjunction at BTS OCM","=
Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","No power issue on site ,site on Grid with Uba=
ie=3D54.1 V The fme tx HUGO/ 672390202 from Huawei is informed. Notice that=
 we have disjunction at BTS OCM","ange.kongo@ihstowers.com","11170","22-10-=
2024 23:41:30","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003386660","BIY=
EMASSI NIKI","","22-10-2024 23:20:19","22-10-2024 23:15:15","22-10-2024 23:=
27:27","site went down because due to insufficient the rectifier on site (S=
ite on 4 rectifiers) // Site stabilized(waiting added 02 rectifiers)","Hyem=
afo Gildas","Equipment Repair","Passive","Rectifier","Rectifier Module","si=
te went down because due to insufficient the rectifier on site (Site on 4 r=
ectifiers) // Site stabilized(waiting added 02 rectifiers)","ludivine.ngama=
leu@ihstowers.com","305","22-10-2024 23:20:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003386622","N=
kolfon Cimencam","","22-10-2024 23:14:38","22-10-2024 23:10:27","23-10-2024=
 00:56:55","No power issue on site U=3D54,5v site on Gen   The Rm Alain (69=
1144423) of huawei is informed","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site U=3D54,5v site on Gen   The Rm Alain (691144423) of huawei is info=
rmed","ange.kongo@ihstowers.com","252","22-10-2024 23:14:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0003386293","E=
BOM","","22-10-2024 22:16:02","22-10-2024 22:11:56","22-10-2024 23:39:00","=
Grid outage, site went down because gen ran untill fuel shortage // refueli=
ng done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran untill fuel shortage // refuel=
ing done","ange.kongo@ihstowers.com","246","22-10-2024 22:16:02","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003385639","N=
kozoa","","22-10-2024 20:33:17","22-10-2024 20:28:03","22-10-2024 21:01:18"=
,"site went down because the Cb(80A) of Dcbox due to load increased on site=
// he reamed the cb","Fabrice Pouakam","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","site went down because the Cb(80A) =
of Dcbox due to load increased on site// he reamed the cb","denis.mballa@ih=
stowers.com","315","22-10-2024 20:33:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0003385603","T=
SINGA VILLAGE 2","","22-10-2024 20:28:38","22-10-2024 20:27:23","23-10-2024=
 01:48:07","Site went down because  due to controller Huawei disfunction// =
He Reset it  site is on gen.","Delor Telezing","Equipment Repair","Passive"=
,"Control Panel","ATS-AMF Issue","Site went down because  due to controller=
 Huawei disfunction// He Reset it  site is on gen.","denis.mballa@ihstowers=
.com","76","22-10-2024 20:28:38","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003385526","Eko=
unou","","22-10-2024 20:19:48","22-10-2024 20:19:39","22-10-2024 20:23:11",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Grid power return","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery backup // Grid power return","olivier.kwedi@ihst=
owers.com","11","22-10-2024 20:19:48","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003385504","Mok=
olo Yaounde","","22-10-2024 20:16:07","22-10-2024 20:06:53","22-10-2024 20:=
17:30","Grid outage , no space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage , no s=
pace to deploy MDG // Grid return","olivier.kwedi@ihstowers.com","555","22-=
10-2024 20:16:07","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003385445","Sap=
eur","","22-10-2024 20:11:48","22-10-2024 20:03:26","22-10-2024 20:17:30","=
Grid outage, site went down before gen start due to poor battery backup // =
Grid power return","Mboua Thierry","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before gen =
start due to poor battery backup // Grid power return","olivier.kwedi@ihsto=
wers.com","503","22-10-2024 20:11:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0003385434","S=
IMBOCK BONAMBAPE","","22-10-2024 20:10:45","22-10-2024 20:05:14","22-10-202=
4 21:57:45","Grid outage, site went down because gen ran untill fuel shorta=
ge // refueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Di=
esel Outage","Grid outage, site went down because gen ran untill fuel short=
age // refueling done","denis.mballa@ihstowers.com","608","22-10-2024 20:10=
:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003385426","C=
amp-Sic-Tsinga","","22-10-2024 20:09:23","22-10-2024 20:03:10","22-10-2024 =
20:16:50","Grid outage , no space to deploy MDG // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage , n=
o space to deploy MDG // Grid return","denis.mballa@ihstowers.com","374","2=
2-10-2024 20:09:23","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003385415","ODZ=
A CITE MBIA","","22-10-2024 20:07:37","22-10-2024 20:03:18","22-10-2024 22:=
51:35","Access issue due to Landlord  Grid outage,gen failed to start due t=
o no automatism on site//Grid return","Albran Byorel","Access Denial","Leas=
e Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access is=
sue due to Landlord  Grid outage,gen failed to start due to no automatism o=
n site//Grid return","olivier.kwedi@ihstowers.com","260","22-10-2024 20:07:=
37","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003385307","MBI=
MBIM","","22-10-2024 19:55:17","22-10-2024 19:46:01","22-10-2024 20:21:06",=
"Site went down because Gen started and stopped due to water infiltration i=
n the tank//  He purged the tank, site on gen","Parker Tchoup","Fuel Outage=
 (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","S=
ite went down because Gen started and stopped due to water infiltration in =
the tank//  He purged the tank, site on gen","olivier.kwedi@ihstowers.com",=
"557","22-10-2024 19:55:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003385215","N=
komkana","","22-10-2024 19:47:39","22-10-2024 19:44:25","23-10-2024 09:07:0=
5","grid outage,no space to deploy a mobil gen//grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no spa=
ce to deploy a mobil gen//grid return","denis.mballa@ihstowers.com","195","=
22-10-2024 19:47:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0003385211","M=
balla 4","","22-10-2024 19:46:18","22-10-2024 19:37:07","22-10-2024 19:40:3=
1","Active No power issue on site, site on Grid with Ubaie=3D54.3V, TX Arma=
nd nguetsa(691144412) from Huawei is informed","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active No power issue on site, site on Grid with Ubaie=3D54.3V, TX Armand =
nguetsa(691144412) from Huawei is informed","denis.mballa@ihstowers.com","5=
53","22-10-2024 19:46:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003385206","N=
yom OCM","","22-10-2024 19:44:48","22-10-2024 19:20:36","22-10-2024 21:26:3=
6","Active///No power issue on site U=3D54,3V site on Grid and The FME TX s=
ynphorien (675295205) From huawei is informed","Fabrice Pouakam","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active///No power issue on site U=3D54,3V site on Grid and The FME TX syn=
phorien (675295205) From huawei is informed","denis.mballa@ihstowers.com","=
1453","22-10-2024 19:44:48","Sagemcom CMR"
"Closed Complete","Site Down","T0459","IHS_YND_240","NOCINC0003385188","Mon=
tee Jouvence","","22-10-2024 19:40:52","22-10-2024 19:35:42","22-10-2024 20=
:29:37","Grid outage, site went down because gen failded to start due to ba=
ttery ge discharged causing by charging alternator Dysfonction// gen manual=
ly started with external battery","Hyemafo Gildas","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Generator Battery","Grid outage, site went down bec=
ause gen failded to start due to battery ge discharged causing by charging =
alternator Dysfonction// gen manually started with external battery","olivi=
er.kwedi@ihstowers.com","310","22-10-2024 19:40:52","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0003385091","Nsi=
meyong Terre Rouge","","22-10-2024 19:20:20","22-10-2024 19:15:11","22-10-2=
024 23:31:55","Access issue due to Landlord Grid Outage, Site went down bec=
ause Gen failed to start due to  the Gen solenoid faulty// Grid return","MI=
NKA NICOLAS","Access Denial","Lease Or Legal","Landlord Related Issues","Ac=
cess Issue - Land Lord","Access issue due to Landlord Grid Outage, Site wen=
t down because Gen failed to start due to  the Gen solenoid faulty// Grid r=
eturn","olivier.kwedi@ihstowers.com","310","22-10-2024 19:20:20","Sagemcom =
CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003385080","NKO=
MEKUI OCM","","22-10-2024 19:17:17","22-10-2024 19:10:09","22-10-2024 19:22=
:59","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // Gen start automat=
icaly","olivier.kwedi@ihstowers.com","429","22-10-2024 19:17:17","Sagemcom =
CMR"
"Cancelled","Warning","T1545","IHS_YND_237","NOCINC0003384986","Carrefour S=
imbock","","22-10-2024 18:59:08","","","site on battery","Hyemafo Gildas","=
","","","","","dorothy.djantio@ihstowers.com","246","22-10-2024 18:59:08","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003384940","MBALNGON=
G LYCEE","","22-10-2024 18:50:31","22-10-2024 18:47:51","22-10-2024 18:55:2=
6","Cascaded Incident from TTO3266960","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid power return","system","160"=
,"22-10-2024 18:50:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003384941","Afanoya"=
,"","22-10-2024 18:50:31","22-10-2024 18:47:51","22-10-2024 18:55:26","Casc=
aded Incident from TTO3266960","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Grid power return","system","160","22-=
10-2024 18:50:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003384939","ELOUMDEM=
 CARRIERE","","22-10-2024 18:50:30","22-10-2024 18:47:51","22-10-2024 18:55=
:26","Cascaded Incident from TTO3266960","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Grid power return","system","15=
9","22-10-2024 18:50:30","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003384933","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","22-10-2024 18:49:09","22-10-20=
24 18:47:51","22-10-2024 18:55:26","Grid outage, site went down before gen =
start due to poor battery backup // Grid power return","Hyemafo Gildas","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gr=
id outage, site went down before gen start due to poor battery backup // Gr=
id power return","olivier.kwedi@ihstowers.com","79","22-10-2024 18:49:09","=
Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003384926","Eko=
unou","","22-10-2024 18:47:21","22-10-2024 18:41:54","22-10-2024 19:03:41",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automaticaly","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen start automaticaly","olivier.=
kwedi@ihstowers.com","329","22-10-2024 18:47:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0003384879","Crf-Nkol=
bisson","","22-10-2024 18:36:41","22-10-2024 18:30:01","22-10-2024 18:40:34=
","Cascaded Incident from TTO3266873","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","no power issue Ubaie=3D5=
3.4V , site on Grid ,The Tx FME Mouhamadou//691144435 from Huawei is inform=
ed","system","400","22-10-2024 18:36:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0003384880","Dagobert=
","","22-10-2024 18:36:41","22-10-2024 18:30:01","22-10-2024 18:40:34","Cas=
caded Incident from TTO3266873","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","no power issue Ubaie=3D53.4V ,=
 site on Grid ,The Tx FME Mouhamadou//691144435 from Huawei is informed","s=
ystem","400","22-10-2024 18:36:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0003384878","Yona Hot=
el","","22-10-2024 18:36:41","22-10-2024 18:30:01","22-10-2024 18:40:34","C=
ascaded Incident from TTO3266873","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","no power issue Ubaie=3D53.4V=
 , site on Grid ,The Tx FME Mouhamadou//691144435 from Huawei is informed",=
"system","400","22-10-2024 18:36:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0003384854","N=
kolbi-Boss","IHS_YND_271, IHS_YND_232, IHS_YND_286","22-10-2024 18:35:14","=
22-10-2024 18:30:01","22-10-2024 19:40:34","no power issue Ubaie=3D53.4V , =
site on Grid ,The Tx FME Mouhamadou//691144435 from Huawei is informed","TI=
ENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","no power issue Ubaie=3D53.4V , site on =
Grid ,The Tx FME Mouhamadou//691144435 from Huawei is informed","denis.mbal=
la@ihstowers.com","314","22-10-2024 18:35:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_105","NOCINC0003384607","Omnispor=
t 3","","22-10-2024 17:41:54","22-10-2024 17:34:34","22-10-2024 17:50:46","=
ACTIVE No power issue U=3D54,6V site on grid TX FME Huawei Armand Nguetsa(6=
91144412) from Huawei is informed. R=E9p=E9titif issue","Delor Telezing","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE No power issue U=3D54,6V site on grid TX FME Huawei Armand=
 Nguetsa(691144412) from Huawei is informed. R=E9p=E9titif issue","denis.mb=
alla@ihstowers.com","441","22-10-2024 17:41:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003384320","M=
fou EPC","","22-10-2024 17:19:20","22-10-2024 17:17:10","22-10-2024 19:01:1=
3","Site went down due to Bad contact on the nuetral //he Normalized the Nu=
etral and site is on Grid ","Mba Lazare Herve","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","Site went down due to Bad con=
tact on the nuetral //he Normalized the Nuetral and site is on Grid ","deni=
s.mballa@ihstowers.com","131","22-10-2024 17:19:20","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003383963","Bas=
tos Amb Coree","","22-10-2024 16:55:06","22-10-2024 16:50:44","22-10-2024 1=
7:35:39","Site went down due  to insufficiency of rectifiers // Site stabil=
ized","","Equipment Repair","Passive","Rectifier","Rectifier Module","Site =
went down due  to insufficiency of rectifiers // Site stabilized","olivier.=
kwedi@ihstowers.com","263","22-10-2024 16:55:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0003383355","N=
kolkoumou OCM","","22-10-2024 15:46:15","22-10-2024 15:42:04","22-10-2024 1=
6:11:29","grid outage, gen start and stopped with alarm 'Low oil pressure' =
// He added oil and Gen manually started","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Oil Pressure Sensor Faulty","grid=
 outage, gen start and stopped with alarm 'Low oil pressure' // He added oi=
l and Gen manually started","denis.mballa@ihstowers.com","252","22-10-2024 =
15:46:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003383021","M=
ini-Ferme","","22-10-2024 14:59:23","22-10-2024 14:55:13","22-10-2024 18:00=
:30","Actives, no power issue on site, Ubaie=3D55,7V  Site on grid, theTX F=
ME Mohamadou(691144435) from hauwei is informed","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Actives, no=
 power issue on site, Ubaie=3D55,7V  Site on grid, theTX FME Mohamadou(6911=
44435) from hauwei is informed","denis.mballa@ihstowers.com","251","22-10-2=
024 14:59:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003382976","M=
ambine","","22-10-2024 14:52:12","22-10-2024 14:43:01","22-10-2024 15:09:41=
","Grid outage, site went down because gen ran untill fuel shortage // refu=
eling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran untill fuel shortage // refuel=
ing done","denis.mballa@ihstowers.com","552","22-10-2024 14:52:12","Sagemco=
m CMR"
"Closed Complete","Site Down","T1582","IHS_YND_138","NOCINC0003382924","Nko=
mkana 2","","22-10-2024 14:41:22","22-10-2024 14:25:10","22-10-2024 16:04:2=
2","Site went down due  to insufficiency of rectifiers // Site stabilized",=
"Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site went down due  to insufficiency of rectifiers // Site stabilized","o=
livier.kwedi@ihstowers.com","973","22-10-2024 14:41:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003382663","Eseka To=
wn","","22-10-2024 13:53:30","22-10-2024 13:42:19","22-10-2024 14:33:28","C=
ascaded Incident from TTO3264314","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage Site went down because=
 the bad contact with the neutral terminal block connected to the Generator=
 contactor//he Normalized it and Site is on Gen ","system","671","22-10-202=
4 13:53:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003382664","Song-bon=
g","","22-10-2024 13:53:30","22-10-2024 13:42:19","22-10-2024 14:33:28","Ca=
scaded Incident from TTO3264314","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage Site went down because =
the bad contact with the neutral terminal block connected to the Generator =
contactor//he Normalized it and Site is on Gen ","system","671","22-10-2024=
 13:53:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003382653","E=
seka OCM","IHS_YND_378, IHS_YND_453","22-10-2024 13:51:29","22-10-2024 13:4=
2:19","22-10-2024 14:33:28","Grid Outage Site went down because the bad con=
tact with the neutral terminal block connected to the Generator contactor//=
he Normalized it and Site is on Gen ","Kemeni Franklin","Equipment Repair",=
"Passive","Control Panel","ATS-AMF Issue","Grid Outage Site went down becau=
se the bad contact with the neutral terminal block connected to the Generat=
or contactor//he Normalized it and Site is on Gen ","stephane.nkamwa@ihstow=
ers.com","551","22-10-2024 13:51:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0003382565","N=
komkana 2","","22-10-2024 13:32:24","22-10-2024 13:25:37","22-10-2024 13:38=
:37","site went down because insufficient of rectifier on site//site stabil=
ized(need to added one rectifier)","Mboua Thierry","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","site went down because insufficient of=
 rectifier on site//site stabilized(need to added one rectifier)","stephane=
.nkamwa@ihstowers.com","408","22-10-2024 13:32:24","Sagemcom CMR"
"Closed Complete","Warning","CTR_067","IHS_YND_377","NOCINC0003382543","Ese=
ka OCM","","22-10-2024 13:29:59","","","","Kemeni Franklin","Warning","Warn=
ing","POWER","Warning - AC Phase 1 Voltage low","Alarm  cleared","christian=
.fonkou@ihstowers.com","2119","22-10-2024 13:29:59","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003382388","ODZ=
A CITE MBIA","","22-10-2024 12:58:25","22-10-2024 12:47:04","22-10-2024 13:=
35:14","grid outage,gen failed to start due to ATS disfunctionning//grid re=
turn","Albran Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF=
 Issue","grid outage,gen failed to start due to ATS disfunctionning//grid r=
eturn","kamga.virgile@ihstowers.com","681","22-10-2024 12:58:25","Sagemcom =
CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003382290","Pha=
rmacie SION","","22-10-2024 12:46:27","22-10-2024 12:25:17","22-10-2024 12:=
47:29","site went down due to work Yamen/657100532/Sagemcom :working on sit=
e securization of TX//End of work","Paul BIBOUM","Installation Activity","P=
assive","Planned Activity","Installation Activity","site went down due to w=
ork Yamen/657100532/Sagemcom :working on site securization of TX//End of wo=
rk","kamga.virgile@ihstowers.com","1271","22-10-2024 12:46:27","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0003381971","O=
mnisport 3","","22-10-2024 12:09:37","22-10-2024 12:01:32","22-10-2024 12:4=
8:42","No power issue on site U=3D54,5v site Armand of huawei is informed",=
"Delor Telezing","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue on site U=3D54,5v site Armand o=
f huawei is informed","stephane.nkamwa@ihstowers.com","487","22-10-2024 12:=
09:37","Sagemcom CMR"
"Closed Complete","Warning","T0638","IHS_YND_318","NOCINC0003381767","SOA U=
niversity","","22-10-2024 11:39:31","","","","Siligap Boris","Warning","War=
ning","POWER","Warning - AC Phase 2 Voltage low","Alarm cleared","christian=
.fonkou@ihstowers.com","226","22-10-2024 11:39:31","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0003381761","Fla=
menco","","22-10-2024 11:38:58","22-10-2024 11:13:45","22-10-2024 12:17:24"=
,"grid outage,gen failed to start due to card Ge faulty//he started the gen=
 manually","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","grid outage,gen failed to start due to card Ge faulty//he s=
tarted the gen manually","kamga.virgile@ihstowers.com","1514","22-10-2024 1=
1:38:58","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0003381729","An-=
Marche-Melen","","22-10-2024 11:36:07","22-10-2024 11:07:51","22-10-2024 12=
:40:53","grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,n=
o space to deploy a mobil gen//grid return","kamga.virgile@ihstowers.com","=
2096","22-10-2024 11:36:07","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003381704","Com=
plex Beac II","","22-10-2024 11:31:01","22-10-2024 10:54:47","22-10-2024 11=
:36:33","grid outage,gen failed to start due to card Ge faulty//he started =
the gen manually","Albran Byorel","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","grid outage,gen failed to start due to card Ge fault=
y//he started the gen manually","kamga.virgile@ihstowers.com","2175","22-10=
-2024 11:31:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_083","NOCINC0003381541","H-Progre=
s","","22-10-2024 11:10:47","22-10-2024 10:27:34","22-10-2024 12:32:02","gr=
id outage,no space to deploy a mobil gen//grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","grid outage,no space to =
deploy a mobil gen//grid return","stephane.nkamwa@ihstowers.com","2594","22=
-10-2024 11:10:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_087","NOCINC0003381329","Camp-Sic=
-Tsinga","","22-10-2024 10:30:40","22-10-2024 10:05:34","22-10-2024 12:35:2=
7","grid outage,no space to deploy a mobil gen//grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no spa=
ce to deploy a mobil gen//grid return","stephane.nkamwa@ihstowers.com","150=
7","22-10-2024 10:30:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003381320","M=
ini-Ferme","","22-10-2024 10:28:37","22-10-2024 10:03:29","22-10-2024 12:36=
:11","grid outage,no space to deploy a mobil gen//grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no s=
pace to deploy a mobil gen//grid return","stephane.nkamwa@ihstowers.com","1=
508","22-10-2024 10:28:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003380816","M=
essa-Carriere OCM","","22-10-2024 09:05:15","22-10-2024 08:18:51","22-10-20=
24 11:24:51","","","Grid Supply","Passive","Grid","National Grid - Grid Out=
age Issue","grid outageNo space to deploy a mobil gen//grid return","kamga.=
virgile@ihstowers.com","2785","22-10-2024 09:05:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003380774","O=
dza II OCM","","22-10-2024 08:54:05","22-10-2024 08:18:55","22-10-2024 09:3=
6:11","grid outage,gen failed to start due to grid bad voltage,no rcp//he d=
id a bridge on good phase","Albran Byorel","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","grid outage,gen failed to start d=
ue to grid bad voltage,no rcp//he did a bridge on good phase","kamga.virgil=
e@ihstowers.com","2111","22-10-2024 08:54:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003380510","O=
dza II OCM","","22-10-2024 07:54:04","21-10-2024 20:05:44","21-10-2024 21:1=
1:44","grid outage,gen failed to start due to grid bad voltage//he bypass g=
rid and started the gen","Albran Byorel","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","grid outage,gen failed to start due=
 to grid bad voltage//he bypass grid and started the gen","kamga.virgile@ih=
stowers.com","45166","22-10-2024 07:54:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_556","NOCINC0003380496","NKOMKANA=
 ELIZA HOTEL","","22-10-2024 07:51:08","22-10-2024 07:29:01","22-10-2024 13=
:39:33","grid outageNo space to deploy a mobil gen//grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","grid outageNo =
space to deploy a mobil gen//grid return","stephane.nkamwa@ihstowers.com","=
1328","22-10-2024 07:51:08","Sagemcom CMR"
"Closed Complete","Site Down","T3180","IHS_YND_253","NOCINC0003380192","Clg=
e-Advantiste","","22-10-2024 06:51:51","22-10-2024 06:40:41","22-10-2024 06=
:57:41","grid outage,site went down because gen overload(15kva,240A)//he re=
duce the load on site","MINKA NICOLAS","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","grid outage,site went down because gen overload(15kv=
a,240A)//he reduce the load on site","kamga.virgile@ihstowers.com","670","2=
2-10-2024 06:51:51","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0003380187","Nko=
mkana","","22-10-2024 06:50:49","22-10-2024 06:37:40","22-10-2024 13:41:42"=
,"grid outageNo space to deploy a mobil gen//grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","grid outageNo space t=
o deploy a mobil gen//grid return","kamga.virgile@ihstowers.com","4108","22=
-10-2024 06:50:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003379650","N=
kolfon Cimencam","","22-10-2024 04:56:32","22-10-2024 03:59:20","22-10-2024=
 09:35:09","No power issue on site U=3D54,5V SITE ON GEN RM aLAIN OF HUAWEI=
 IS INFORMED","Hyemafo Gildas","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,5V=
 SITE ON GEN RM aLAIN OF HUAWEI IS INFORMED","kombi.samuel@ihstowers.com","=
3432","22-10-2024 04:56:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0003379315","B=
otmakak","","22-10-2024 02:43:13","22-10-2024 02:37:09","22-10-2024 05:17:0=
0","no power issue U=3D53.8V site on Grid. the TX FME ETienne// 695033981//=
 / from huawei is informed by sms","Kemeni Franklin","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power i=
ssue U=3D53.8V site on Grid. the TX FME ETienne// 695033981// / from huawei=
 is informed by sms","joelle.ekessi@ihstowers.com","365","22-10-2024 02:43:=
13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003379212","ELOUMDEM=
 CARRIERE","","22-10-2024 02:14:30","22-10-2024 02:10:23","22-10-2024 02:18=
:41","Cascaded Incident from TTO3260380","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start automaticaly","system=
","247","22-10-2024 02:14:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003379213","MBALNGON=
G LYCEE","","22-10-2024 02:14:30","22-10-2024 02:10:23","22-10-2024 02:18:4=
1","Cascaded Incident from TTO3260380","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen start automaticaly","system",=
"247","22-10-2024 02:14:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003379214","Afanoya"=
,"","22-10-2024 02:14:30","22-10-2024 02:10:23","22-10-2024 02:18:41","Casc=
aded Incident from TTO3260380","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Gen start automaticaly","system","247"=
,"22-10-2024 02:14:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003379209","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","22-10-2024 02:12:27","22-10-=
2024 02:10:23","22-10-2024 02:18:41","Grid outage, site went down before ge=
n start due to poor battery backup // Gen start automaticaly","Hyemafo Gild=
as","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery L=
ow","Grid outage, site went down before gen start due to poor battery backu=
p // Gen start automaticaly","joelle.ekessi@ihstowers.com","125","22-10-202=
4 02:12:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003379194","S=
ous Prefecture","","22-10-2024 02:08:18","22-10-2024 02:03:13","22-10-2024 =
04:26:07","No power issue on site Ubaie:55,2V;  site on Grid  TX FME Hugo (=
672390202) from Huawei is informed.by sms","Fanda Brice","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site Ubaie:55,2V;  site on Grid TX FME Hugo (672390202) from Hu=
awei is informed.by sms","joelle.ekessi@ihstowers.com","306","22-10-2024 02=
:08:18","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003379105","NTU=
I TOWN","","22-10-2024 01:34:57","22-10-2024 01:31:44","22-10-2024 03:32:55=
","Grid outage, site went down because gen ran untill fuel shortage // refu=
eling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage=
","Grid outage, site went down because gen ran untill fuel shortage // refu=
eling done","emmanuel.ghani@ihstowers.com","194","22-10-2024 01:34:57","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0003379030","S=
apeur","","22-10-2024 01:07:32","22-10-2024 01:04:27","22-10-2024 01:24:21"=
,"Grid outage site went down because Gen failed to start // Grid power retu=
rn( investigation ongoing)","Mboua Thierry","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage site went down because Gen fai=
led to start // Grid power return( investigation ongoing)","joelle.ekessi@i=
hstowers.com","186","22-10-2024 01:07:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003379024","C=
amp-Sic-Tsinga","","22-10-2024 01:06:06","22-10-2024 01:04:02","22-10-2024 =
01:23:13","Grid outage  No space to deploy // Grid power return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage  N=
o space to deploy // Grid power return","joelle.ekessi@ihstowers.com","125"=
,"22-10-2024 01:06:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0003378860","N=
goulmekong-Nord","","22-10-2024 00:11:15","22-10-2024 00:09:11","22-10-2024=
 01:10:06","Grid outage, site went down because gen failed to start due to =
battery Gen faulty// Gen manually started with external battery","Siligap B=
oris","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","G=
rid outage, site went down because gen failed to start due to battery Gen f=
aulty// Gen manually started with external battery","joelle.ekessi@ihstower=
s.com","125","22-10-2024 00:11:15","Sagemcom CMR"
"Closed Complete","Site Down","T1579","IHS_YND_480","NOCINC0003378812","Sic=
 Cite Verte Matgenie","","21-10-2024 23:57:31","21-10-2024 23:51:22","22-10=
-2024 02:25:25","Active: no power issue, site is on grid with Ubaie=3D53.3V=
,  the fme tx Mbah Hosiah(699699694) from Huawei is informed","","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active: no power issue, site is on grid with Ubaie=3D53.3V, the fme tx Mb=
ah Hosiah(699699694) from Huawei is informed","emmanuel.ghani@ihstowers.com=
","370","21-10-2024 23:57:31","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0003378795","Nko=
mkana","","21-10-2024 23:55:18","21-10-2024 23:51:10","22-10-2024 00:10:13"=
,"Grid outage No space to deploy // Grid power return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage No space to =
deploy // Grid power return","emmanuel.ghani@ihstowers.com","249","21-10-20=
24 23:55:18","Sagemcom CMR"
"Closed Complete","Site Down","T0526","IHS_YND_088","NOCINC0003378789","Elo=
bi Mokolo","","21-10-2024 23:53:13","21-10-2024 23:51:06","22-10-2024 01:29=
:17","No power issue on site, site on Grid  with U=3D53,5 V The TX FME Moha=
madou(691144435)from huawei is informed","Mboua Thierry","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site, site on Grid  with U=3D53,5 V The TX FME Mohamadou(691144=
435)from huawei is informed","emmanuel.ghani@ihstowers.com","128","21-10-20=
24 23:53:13","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003378787","Mok=
olo Yaounde","","21-10-2024 23:52:45","21-10-2024 23:51:37","21-10-2024 23:=
53:34","Grid Outage no space to deploy MDG//Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no space t=
o deploy MDG//Grid return","emmanuel.ghani@ihstowers.com","68","21-10-2024 =
23:52:45","Sagemcom CMR"
"Closed Complete","Site Down","T2039","IHS_YND_724","NOCINC0003378551","BIY=
EMASSI NIKI","","21-10-2024 22:49:03","21-10-2024 22:46:56","21-10-2024 22:=
49:12","Grid fluctuation site went down because Gen failed to start due to =
Grid bad voltage // He bypass the Grid site on Gen","Hyemafo Gildas","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation site went down because Gen failed to start due to Grid bad voltag=
e // He bypass the Grid site on Gen","emmanuel.ghani@ihstowers.com","127","=
21-10-2024 22:49:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0003378550","N=
komkana 2","","21-10-2024 22:48:33","21-10-2024 22:46:28","22-10-2024 09:24=
:36","Access issue during the Night due to landlord,site went down due to 1=
/5rectifier//he reduice the load on site (need to change the faulty rectifi=
er)","Mboua Thierry","Access Denial","Lease Or Legal","Landlord Related Iss=
ues","Access Issue - Land Lord","Access issue during the Night due to landl=
ord,site went down due to 1/5rectifier//he reduice the load on site (need t=
o change the faulty rectifier)","joelle.ekessi@ihstowers.com","126","21-10-=
2024 22:48:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0003378479","O=
mnisport 3","","21-10-2024 22:28:50","21-10-2024 22:24:46","22-10-2024 00:2=
5:52","Site went down because the Cb(63*3 A) of Dcbox burn // he replaced t=
he Cb burn by Cb(80A) and Cb(63*2A)","Delor Telezing","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Circuit Breaker Issue","No power i=
ssue site on grid with U=3D54.6v  the fme tx Armand Nguetsa(691144412) from=
 Huawei is informed","joelle.ekessi@ihstowers.com","245","21-10-2024 22:28:=
50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003378310","E=
ssomba","","21-10-2024 21:53:43","21-10-2024 21:47:37","22-10-2024 01:50:07=
","Active: No power issue, site is on Grid with Ubaie=3D54.2V,The fme tx HU=
GO/ 672390202 from Huawei is informed. Notice that we have disjunction at B=
TS OCM","Mba Lazare Herve","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active: No power issue, site is on G=
rid with Ubaie=3D54.2V, The fme tx HUGO/ 672390202 from Huawei is informed.=
 Notice that we have disjunction at BTS OCM","ange.kongo@ihstowers.com","36=
7","21-10-2024 21:53:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003378122","M=
EFOU ASSI","","21-10-2024 21:22:32","21-10-2024 21:14:26","21-10-2024 21:20=
:30","Site went down due to insufficient the rectifiers on site // site sta=
bilized","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down due to insufficient the rectifiers on site // site =
stabilized","ange.kongo@ihstowers.com","487","21-10-2024 21:22:32","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003377860","Eto koss=
 Yde","","21-10-2024 20:44:30","21-10-2024 20:41:56","21-10-2024 20:45:16",=
"Cascaded Incident from TTO3258718","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage ,site went down before g=
en start due to poor battery backup causing by insufficient of rectifiers (=
 site on 08 rectifiers)// Gen started automatically ( waiting added 02 rect=
ifiers)","system","154","21-10-2024 20:44:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003377861","ELOUMDEM=
 CARRIERE 2","","21-10-2024 20:44:30","21-10-2024 20:41:56","21-10-2024 20:=
45:16","Cascaded Incident from TTO3258718","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage ,site went down b=
efore gen start due to poor battery backup causing by insufficient of recti=
fiers ( site on 08 rectifiers)// Gen started automatically ( waiting added =
02 rectifiers)","system","154","21-10-2024 20:44:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003377854","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","21-10-2024 20:43:08","21-10-2024 20:41=
:56","21-10-2024 20:45:16","Grid outage ,site went down before gen start du=
e to poor battery backup causing by insufficient of rectifiers ( site on 08=
 rectifiers)// Gen started automatically ( waiting added 02 rectifiers)","F=
anda Brice","Equipment Repair","Passive","Control Panel","Power Cabinet - B=
attery Low","Grid outage ,site went down before gen start due to poor batte=
ry backup causing by insufficient of rectifiers ( site on 08 rectifiers)// =
Gen started automatically ( waiting added 02 rectifiers)","denis.mballa@ihs=
towers.com","73","21-10-2024 20:43:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003377644","O=
mnisport-Rail","","21-10-2024 20:11:35","21-10-2024 20:08:18","21-10-2024 2=
1:00:58","site went down because Gen failed to start due to Grid bad voltag=
e and No RCP on site // He bypass the Grid site on Gen","Delor Telezing","G=
rid Supply","Passive","Grid","National Grid - Phase Controller Faulty","sit=
e went down because Gen failed to start due to Grid bad voltage and No RCP =
on site // He bypass the Grid site on Gen","ange.kongo@ihstowers.com","198"=
,"21-10-2024 20:11:35","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003377638","NKO=
MEKUI OCM","","21-10-2024 20:10:42","21-10-2024 20:02:32","21-10-2024 20:15=
:00","Grid outage, site went down before gen start due to poor battery back=
up // Gen started automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite went down before gen start due to poor battery backup // Gen started au=
tomatically","denis.mballa@ihstowers.com","491","21-10-2024 20:10:42","Sage=
mcom CMR"
"Closed Complete","Warning","","IHS_YND_528","NOCINC0003377614","MEHANDAN",=
"","21-10-2024 20:07:50","","","Cascaded Incident from TTO3258431","Albran =
Byorel","Warning","Warning","Unlisted RCA","Warning - Others","Wrong TT ","=
system","363","21-10-2024 20:07:50","Sagemcom CMR"
"Cancelled","Warning","CTR_158","IHS_YND_527","NOCINC0003377603","Odza II O=
CM","IHS_YND_528","21-10-2024 20:05:52","","","grid outage,site went down b=
ecause gen failed to start due to grid bad voltage//he bypassed grid and st=
arted the gen","Albran Byorel","","","","","","ange.kongo@ihstowers.com","2=
45","21-10-2024 20:05:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0003377492","B=
ONAS YDE","","21-10-2024 19:37:04","21-10-2024 19:34:59","21-10-2024 21:31:=
43","No power Issue Site on Grid Ubai =3D52.8  V,   The TX FME Mbah Hosiah =
(674007438)  from Huawei is informed and notice that disjunction of CB in B=
ts Ocm","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power Issue Site on Grid Ubai =3D52.8 =
 V,   The TX FME Mbah Hosiah (674007438)  from Huawei is informed and notic=
e that disjunction of CB in Bts Ocm","ange.kongo@ihstowers.com","125","21-1=
0-2024 19:37:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003377165","Ngouetou=
","","21-10-2024 19:04:31","21-10-2024 18:57:30","21-10-2024 18:58:30","Cas=
caded Incident from TTO3257922","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 51.2V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","421","21-10-2024 19:04:31","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003377164","Yoko OCM=
","","21-10-2024 19:04:31","21-10-2024 18:57:30","21-10-2024 18:58:30","Cas=
caded Incident from TTO3257922","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen with U =3D=
 51.2V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","421","21-10-2024 19:04:31","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003377166","MBIMBIM"=
,"","21-10-2024 19:04:31","21-10-2024 18:57:30","21-10-2024 18:58:30","Casc=
aded Incident from TTO3257922","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
51.2V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","421","21-10-2024 19:04:31","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003377163","Matsari"=
,"","21-10-2024 19:04:31","21-10-2024 18:57:30","21-10-2024 18:58:30","Casc=
aded Incident from TTO3257922","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen with U =3D =
51.2V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","421","21-10-2024 19:04:31","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003377162","Ngoum","=
","21-10-2024 19:04:30","21-10-2024 18:57:30","21-10-2024 18:58:30","Cascad=
ed Incident from TTO3257922","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Gen with U =3D 51=
.2V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959647=
of Huawei is informed","system","420","21-10-2024 19:04:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0003377115","E=
BOM","","21-10-2024 18:56:51","21-10-2024 18:51:45","21-10-2024 19:41:45","=
Grid bad voltage ,site went down because Gen failed to start  due to Grid b=
ad voltage  and No RCP// he bypassed Grid and started Gen manually","Hyemaf=
o Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid bad voltage ,site went down because Gen failed to start  due =
to Grid bad voltage  and No RCP// he bypassed Grid and started Gen manually=
","ange.kongo@ihstowers.com","307","21-10-2024 18:56:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003376694","M=
EHANDAN","","21-10-2024 17:40:51","21-10-2024 17:37:46","21-10-2024 19:43:5=
4","No power issue on site ,site on Grid with Ubaie=3D54 V the TX fme Lione=
l    /655184876 from huawei is Informed ","Albran Byorel","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site ,site on Grid with Ubaie=3D54 V the TX fme Lionel    /655=
184876 from huawei is Informed ","ange.kongo@ihstowers.com","186","21-10-20=
24 17:40:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003376600","T=
singa","","21-10-2024 17:20:38","21-10-2024 17:17:28","21-10-2024 17:42:41"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Grid power return","Mboua Thierry","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage, site went down before ge=
n start due to poor battery backup // Grid power return","ange.kongo@ihstow=
ers.com","191","21-10-2024 17:20:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003376376","M=
ini-Ferme","","21-10-2024 16:35:52","21-10-2024 16:35:43","21-10-2024 16:50=
:46","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space=
 to deploy a MDG//Grid Restored","ange.kongo@ihstowers.com","10","21-10-202=
4 16:35:52","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003375945","N=
KOMEKUI OCM","IHS_YND_341","21-10-2024 15:18:28","21-10-2024 15:12:22","21-=
10-2024 15:18:00","Grid outage,site went down  before DG start : Poor Batte=
ries Backup // DG started automatically.","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage,site went down  before DG start : Poor Batteries Backup // DG starte=
d automatically.","ange.kongo@ihstowers.com","367","21-10-2024 15:18:28","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0003375933","L=
obo OCM","","21-10-2024 15:16:10","21-10-2024 15:12:22","21-10-2024 15:18:0=
0","Grid outage,site went down  before DG start : Poor Batteries Backup // =
DG started automatically.","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage,site went down  befo=
re DG start : Poor Batteries Backup // DG started automatically.","ange.kon=
go@ihstowers.com","592","21-10-2024 15:16:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003374980","M=
ANGUIERS CHAPELLE","","21-10-2024 12:51:55","21-10-2024 12:39:50","21-10-20=
24 12:58:23","Grid fluctuation, sitte went down because gen start and stopp=
ed due to grid bad volage // hy bypass grid and manually start the gen","Fa=
brice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, sitte went down because gen start and stopp=
ed due to grid bad volage // hy bypass grid and manually start the gen","al=
exandre.kamal@ihstowers.com","726","21-10-2024 12:51:55","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003374293","ODZ=
A CITE MBIA","","21-10-2024 11:19:34","21-10-2024 10:53:21","21-10-2024 13:=
07:37"," Grid outage site went down because Gen failed to start due to ATS =
dysfonction //Gen manually started.","Albran Byorel","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue"," Grid outage site went down because=
 Gen failed to start due to ATS dysfonction //Gen manually started.","chris=
tian.fonkou@ihstowers.com","1573","21-10-2024 11:19:34","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003374256","Lad=
a I Yde","","21-10-2024 11:09:44","21-10-2024 10:50:31","21-10-2024 12:22:4=
6","Gen only site,DG stopped due to High temp //He added water and manually=
 start of DG.","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - High Engine Temp - Coolant Level Issue","Gen only site,DG stopped du=
e to High temp //He added water and manually start of DG.","christian.fonko=
u@ihstowers.com","1154","21-10-2024 11:09:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003374176","N=
kolndongo","","21-10-2024 10:50:56","21-10-2024 10:35:50","21-10-2024 10:52=
:20","Grid outage ; Main DG faulty //Grid restored.","MINKA NICOLAS","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage ; =
Main DG faulty //Grid restored.","alexandre.kamal@ihstowers.com","907","21-=
10-2024 10:50:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003374163","A=
wae Escalier","","21-10-2024 10:47:05","21-10-2024 10:31:01","21-10-2024 10=
:49:24","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen start automaticaly","Albran Byorel","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automaticaly","=
alexandre.kamal@ihstowers.com","965","21-10-2024 10:47:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003374133","M=
IMBOMAN LIBERTE","","21-10-2024 10:44:43","21-10-2024 10:31:24","21-10-2024=
 11:09:26","Grid outage,Main DG Faulty //Grid restored.","Mba Lazare Herve"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid ou=
tage,Main DG Faulty //Grid restored.","alexandre.kamal@ihstowers.com","1691=
","21-10-2024 10:44:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003374117","A=
wae Ewonkan","","21-10-2024 10:43:30","21-10-2024 10:30:25","21-10-2024 10:=
49:54","Grid outage,site went down before DG start : Poor batteries Backup =
// DG started automatically.","Albran Byorel","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage,site went down b=
efore DG start : Poor batteries Backup // DG started automatically.","alexa=
ndre.kamal@ihstowers.com","786","21-10-2024 10:43:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003374115","S=
tade-Abega","","21-10-2024 10:42:31","21-10-2024 10:29:24","21-10-2024 11:0=
8:37","Grid outage site went down because Gen failed to start  due to glow =
plug faulty // Grid restored.","Mba Lazare Herve","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Kick Starter","Grid outage site went down because Ge=
n failed to start  due to glow plug faulty // Grid restored.","alexandre.ka=
mal@ihstowers.com","788","21-10-2024 10:42:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0003374074","C-Suprem=
e","","21-10-2024 10:36:10","21-10-2024 10:03:25","21-10-2024 10:37:30","Ca=
scaded Incident from TTO3254420","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage,DG dailed to start due to ACDG Generat=
or battery faulty  //Manually start of DG with external battery.","system",=
"1965","21-10-2024 10:36:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0003374073","Acropole=
","","21-10-2024 10:36:10","21-10-2024 10:03:25","21-10-2024 10:37:30","Cas=
caded Incident from TTO3254420","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,DG dailed to start due to =
ACDG Generator battery faulty  //Manually start of DG with external battery=
.","system","1965","21-10-2024 10:36:10","Sagemcom CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0003374066","Imm=
-Olympique","","21-10-2024 10:34:38","21-10-2024 09:58:27","21-10-2024 11:1=
0:37","Grid outage, DG fails to start due to power cable stolen since//Grid=
 restored.","Paul BIBOUM","Equipment Repair","Passive","Infrastructure","Ar=
moured Cable","Grid outage, DG fails to start due to power cable stolen sin=
ce//Grid restored.","olivier.kwedi@ihstowers.com","2172","21-10-2024 10:34:=
38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0003374054","M=
vog Mbi New","IHS_YND_036, IHS_YND_021","21-10-2024 10:33:32","21-10-2024 1=
0:03:25","21-10-2024 10:37:30","Grid outage,DG dailed to start due to ACDG =
Generator battery faulty  //Manually start of DG with external battery.","M=
INKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Bat=
tery","Grid outage,DG dailed to start due to ACDG Generator battery faulty =
 //Manually start of DG with external battery.","alexandre.kamal@ihstowers.=
com","1808","21-10-2024 10:33:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_715","NOCINC0003373986","Odza Min=
kan IHS","","21-10-2024 10:26:31","21-10-2024 09:52:35","21-10-2024 11:40:0=
2","Cascaded Incident from TTO3254240","Albran Byorel","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to MTN Circu=
it down in the PWC,because of overload( 80 A)  // he did a bridge with a 63=
 A; site on Grid.","system","2036","21-10-2024 10:26:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0003373983","Mbedoumo=
u - Ekali","","21-10-2024 10:26:31","21-10-2024 09:52:35","21-10-2024 11:40=
:02","Cascaded Incident from TTO3254240 - Cascade Removed From TTO3254240",=
"Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade Passi=
ve","Site went down due to MTN Circuit down in the PWC,because of overload(=
 80 A)  // he did a bridge with a 63 A; site on Grid.","system","2036","21-=
10-2024 10:26:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003373984","MEHANDAN=
","","21-10-2024 10:26:31","21-10-2024 09:52:35","21-10-2024 11:40:02","Cas=
caded Incident from TTO3254240","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to MTN Circuit down=
 in the PWC,because of overload( 80 A)  // he did a bridge with a 63 A; sit=
e on Grid.","system","2036","21-10-2024 10:26:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_746","NOCINC0003373985","Mehanda =
1","","21-10-2024 10:26:31","21-10-2024 09:52:35","21-10-2024 11:40:02","Ca=
scaded Incident from TTO3254240","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to MTN Circuit dow=
n in the PWC,because of overload( 80 A)  // he did a bridge with a 63 A; si=
te on Grid.","system","2036","21-10-2024 10:26:31","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003373889","Nko=
lnda","IHS_YND_343, IHS_YND_528, IHS_YND_746, IHS_YND_715, IHS_YND_344","21=
-10-2024 10:08:52","21-10-2024 09:52:35","21-10-2024 11:40:02","Site went d=
own due to MTN Circuit down in the PWC,because of overload( 80 A)  // he di=
d a bridge with a 63 A; site on Grid.","Albran Byorel","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went=
 down due to MTN Circuit down in the PWC,because of overload( 80 A)  // he =
did a bridge with a 63 A; site on Grid.","olivier.kwedi@ihstowers.com","978=
","21-10-2024 10:08:52","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003373858","San=
ta Barbara Gottam","","21-10-2024 10:02:46","21-10-2024 09:51:35","21-10-20=
24 11:21:19","Site went down due to PWC dysfonctioning ( Batteries Backup  =
alarming ; PWC FNS)//Reset Batteries Backup,site on Grid.","Delor Telezing"=
,"Equipment Repair","Passive","Rectifier","Rectifier - Controller Failure",=
"Site went down due to PWC dysfonctioning ( Batteries Backup  alarming ; PW=
C FNS)//Reset Batteries Backup,site on Grid.","olivier.kwedi@ihstowers.com"=
,"672","21-10-2024 10:02:46","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003373825","Ess=
os Marche","","21-10-2024 09:58:07","21-10-2024 09:48:54","21-10-2024 10:14=
:26","Grid outage,site went down before DG start : Poor Batteries  Backup /=
/ DG started automatically.","Delor Telezing","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage,site went down b=
efore DG start : Poor Batteries  Backup // DG started automatically.","oliv=
ier.kwedi@ihstowers.com","554","21-10-2024 09:58:07","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0003373598","Mam=
bine","","21-10-2024 09:19:32","21-10-2024 09:15:22","21-10-2024 09:56:17",=
"","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age, site went down because gen ran untill fuel shortage // refueling done"=
,"olivier.kwedi@ihstowers.com","250","21-10-2024 09:19:32","Sagemcom CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0003373296","Mai=
son komkana New","","21-10-2024 08:25:51","21-10-2024 08:17:42","21-10-2024=
 09:37:56","","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Generator Battery","grid outage, site down because gen fails to start du=
e togen battery faulty//gen started with backup battery","olivier.kwedi@ihs=
towers.com","490","21-10-2024 08:25:51","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003373221","NKO=
MEKUI OCM","","21-10-2024 08:08:30","21-10-2024 08:03:19","21-10-2024 08:11=
:30","","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","grid outage, site down due to poor back=
up//gen started","olivier.kwedi@ihstowers.com","312","21-10-2024 08:08:30",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0003373207","Bastos B=
ir","","21-10-2024 08:06:20","21-10-2024 07:58:28","21-10-2024 11:52:08","C=
ascaded Incident from TTO3253408","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site down due to rectifier issue","s=
ystem","472","21-10-2024 08:06:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0003373208","ARMP",""=
,"21-10-2024 08:06:20","21-10-2024 07:58:28","21-10-2024 11:52:08","Cascade=
d Incident from TTO3253408","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","site down due to rectifier issue","system","472","21-10=
-2024 08:06:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003373193","D=
ragage","IHS_YND_704, IHS_YND_208","21-10-2024 08:04:34","21-10-2024 07:58:=
28","21-10-2024 11:52:08","site down due to rectifier issue","Mboua Thierry=
","Equipment Repair","Passive","Rectifier","Rectifier Module","site down du=
e to rectifier issue//site stabilized","alexandre.kamal@ihstowers.com","369=
","21-10-2024 08:04:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_781","NOCINC0003372766","BIBOMDJI=
DJIEL","","21-10-2024 06:42:20","21-10-2024 06:33:11","21-10-2024 10:31:04"=
,"Technician is still on the way ETA 10h00","Kemeni Franklin","Fuel Outage"=
,"Passive","Diesel","Diesel Outage","gen ran till diesel outage//refueling =
done","olivier.kwedi@ihstowers.com","550","21-10-2024 06:42:20","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003372404","Kondengu=
i","","21-10-2024 05:35:00","19-10-2024 20:00:33","19-10-2024 21:36:33","Ca=
scaded Incident from TTO3242638","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage,no space to deploy a mobi=
l gen//grid return","system","120867","21-10-2024 05:35:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_138","NOCINC0003371970","Nkomkana=
 2","","21-10-2024 02:41:20","21-10-2024 02:34:30","21-10-2024 09:46:59","C=
ascaded Incident from TTO3251950","Mboua Thierry","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage No space to deploy a  MD=
G waiting for grid restored//Grid restored.","system","410","21-10-2024 02:=
41:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0003371968","M=
adagascar-Yde-New","IHS_YND_138","21-10-2024 02:40:43","21-10-2024 02:34:30=
","21-10-2024 09:46:59","Grid Outage No space to deploy a  MDG waiting for =
grid restored//Grid restored.","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid Outage No space to deploy a  MDG waiting fo=
r grid restored//Grid restored.","kouoh.jean@ihstowers.com","374","21-10-20=
24 02:40:43","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0003371911","Nko=
mkana","","21-10-2024 02:19:58","21-10-2024 02:19:46","21-10-2024 10:08:08"=
,"Grid outage;no space to deploy a mobile DG ,waiting for grid restored//Gr=
id restored.","","Grid Supply","Passive","Grid","National Grid - Grid Outag=
e Issue","Grid outage;no space to deploy a mobile DG ,waiting for grid rest=
ored//Grid restored.","landry.etame@ihstowers.com","13","21-10-2024 02:19:5=
8","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0003371909","NKO=
MKANA ELIZA HOTEL","","21-10-2024 02:14:36","21-10-2024 02:07:30","21-10-20=
24 10:05:38","Grid outage,no space to deploy a mobile DG,waiting fro grid r=
estored//Grid restored.","","Grid Supply","Passive","Grid","National Grid -=
 Grid Outage Issue","Grid outage,no space to deploy a mobile DG,waiting fro=
 grid restored//Grid restored.","landry.etame@ihstowers.com","427","21-10-2=
024 02:14:36","Sagemcom CMR"
"Closed Complete","Site Down","T0129","IHS_YND_379","NOCINC0003371906","Ese=
ka MTN","IHS_YND_378","21-10-2024 02:12:32","19-10-2024 19:53:47","19-10-20=
24 23:19:04","Grid outage, site went down because Gen ran till fuel shortag=
e//Refueling done","Kemeni Franklin","Fuel Outage","Passive","Diesel","Dies=
el Outage","Grid outage, site went down because Gen ran till fuel shortage/=
/Refueling done","landry.etame@ihstowers.com","109126","21-10-2024 02:12:32=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003371896","Lobo OCM=
","","21-10-2024 02:04:41","21-10-2024 01:15:46","21-10-2024 01:21:46","Cas=
caded Incident from TTO3251855","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automaticaly","sy=
stem","2935","21-10-2024 02:04:41","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003371893","N=
KOMEKUI OCM","IHS_YND_341","21-10-2024 02:03:24","21-10-2024 01:15:46","21-=
10-2024 01:21:46","Grid outage, site went down before gen start due to poor=
 battery backup // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 outage, site went down before gen start due to poor battery backup // Gen =
start automaticaly","kouoh.jean@ihstowers.com","2859","21-10-2024 02:03:24"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1669","IHS_YND_195","NOCINC0003371876","chi=
na embassy yde","","21-10-2024 01:49:11","21-10-2024 01:47:02","21-10-2024 =
10:42:25","Grid outage,no sapce to deploy a mobile DG,waiting for grid rest=
ored//Grid restored.","","Grid Supply","Passive","Grid","National Grid - Gr=
id Outage Issue","Grid outage,no sapce to deploy a mobile DG,waiting for gr=
id restored//Grid restored.","landry.etame@ihstowers.com","130","21-10-2024=
 01:49:11","Sagemcom CMR"
"Closed Complete","Site Down","T0122","IHS_YND_131","NOCINC0003371854","Lab=
oratoire  Meka","IHS_YND_193","21-10-2024 01:41:54","21-10-2024 01:36:48","=
21-10-2024 05:04:17","Grid outage No space to deploy // Grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage No space to deploy // Grid power return","landry.etame@ihstowers.co=
m","306","21-10-2024 01:41:54","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003371843","Bas=
tos Ekoudou","","21-10-2024 01:39:44","21-10-2024 01:36:48","21-10-2024 05:=
04:17","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage No space to deploy // Grid power return","landry=
.etame@ihstowers.com","536","21-10-2024 01:39:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003371707","M=
essa-Carriere OCM","","21-10-2024 00:59:29","20-10-2024 22:48:57","20-10-20=
24 23:05:24","No power issue site on grid with U=3D52,3V, FME TX Mohamadou/=
691144435/ from Huawei is informed","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D52,3V, FME TX Mohamadou/691144435/ from Huawei is informed","k=
ouoh.jean@ihstowers.com","7834","21-10-2024 00:59:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003371682","c=
hina embassy yde","","21-10-2024 00:45:53","20-10-2024 10:41:35","21-10-202=
4 00:42:16","Grid outage No space to deploy // Grid power return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage N=
o space to deploy // Grid power return","kouoh.jean@ihstowers.com","50659",=
"21-10-2024 00:45:53","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0003371665","An-=
Marche-Melen","","21-10-2024 00:37:41","20-10-2024 11:46:39","21-10-2024 00=
:40:41","Grid outage No space to deploy // Grid power return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No sp=
ace to deploy // Grid power return","kouoh.jean@ihstowers.com","46263","21-=
10-2024 00:37:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003371653","N=
kolfon Cimencam","","21-10-2024 00:33:14","20-10-2024 23:03:47","20-10-2024=
 23:10:59","No power issue on site U=3D54,5v site on gen Rm Alain (69114442=
3)of huawei is informed","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54,5v site on gen Rm Alain (691144423)of huawei is informed","kouoh.j=
ean@ihstowers.com","5367","21-10-2024 00:33:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0003371586","M=
adagascar-Yde-New","","21-10-2024 00:06:28","20-10-2024 11:53:28","21-10-20=
24 00:41:38","Grid outage No space to deploy // Grid power return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
No space to deploy // Grid power return","kouoh.jean@ihstowers.com","43981"=
,"21-10-2024 00:06:28","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0003371537","Nko=
lbisson IITA LP","","20-10-2024 23:50:46","20-10-2024 23:45:38","21-10-2024=
 00:36:12","Grid outage No space to deploy // Grid power return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No=
 space to deploy // Grid power return","landry.etame@ihstowers.com","309","=
20-10-2024 23:50:46","Sagemcom CMR"
"Closed Complete","Site Down","T0210","IHS_YND_206","NOCINC0003371408","ARM=
P","","20-10-2024 23:25:17","20-10-2024 23:22:10","21-10-2024 01:01:54","Gr=
id Outage, site went down because Gen started and stopped due to Fuel pump =
faulty // Grid power return","Mboua Thierry","Fuel Outage (Probable)","Pass=
ive","ACDG Gen","ACDG - Fuel Pump","Grid Outage, site went down because Gen=
 started and stopped due to Fuel pump faulty // Grid power return","landry.=
etame@ihstowers.com","188","20-10-2024 23:25:17","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0003371379","Obo=
bogo","","20-10-2024 23:14:40","20-10-2024 23:09:19","20-10-2024 23:39:57",=
"Grid fluctuation, site went down before Gen start due to poor backup  // G=
en start automaticaly","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid fluctuation, site went down be=
fore Gen start due to poor backup  // Gen start automaticaly","landry.etame=
@ihstowers.com","322","20-10-2024 23:14:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_481","IHS_YND_574","NOCINC0003371283","C=
rf-Mbankolo-IHS","","20-10-2024 22:54:50","20-10-2024 19:01:37","20-10-2024=
 23:59:42","Grid Outage, site went down because Gen stopped with ""high tem=
p"" alarm// He added water and started Gen manualy","Mboua Thierry","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Grid Outage, site went down because Gen stopped with ""high temp"" a=
larm// He added water and started Gen manualy","kouoh.jean@ihstowers.com","=
13994","20-10-2024 22:54:50","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0003370839","Nko=
mkana","","20-10-2024 21:25:44","20-10-2024 21:17:22","21-10-2024 00:40:31"=
,"Grid outage No space to deploy // Grid power return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage No space to =
deploy // Grid power return","emmanuel.ghani@ihstowers.com","503","20-10-20=
24 21:25:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0003370707","C=
hapelle-Essos","","20-10-2024 21:06:06","20-10-2024 20:35:57","20-10-2024 2=
1:07:57","site went down due to Eneo contactor faulty // He bypassed Eneo c=
ontactor and gen manually started","Delor Telezing","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","site went down due to Eneo contactor=
 faulty // He bypassed Eneo contactor and gen manually started","kombi.samu=
el@ihstowers.com","1810","20-10-2024 21:06:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003370137","Eto koss=
 Yde","","20-10-2024 19:23:50","20-10-2024 19:20:22","20-10-2024 19:24:33",=
"Cascaded Incident from TTO3249736","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to insufficient o=
f 2 rectifiers on site // site stabilized","system","208","20-10-2024 19:23=
:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003370135","MEF=
OU ASSI","IHS_YND_737","20-10-2024 19:22:27","20-10-2024 19:20:22","20-10-2=
024 20:09:18","Site went down due to insufficient of 2 rectifiers on site /=
/ site stabilized","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to insufficient of 2 rectifiers on si=
te // site stabilized","emmanuel.ghani@ihstowers.com","126","20-10-2024 19:=
22:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003370120","Melen Ba=
'aba","","20-10-2024 19:20:41","20-10-2024 19:17:21","20-10-2024 19:32:21",=
"Grid Outage, site went down because Gen stopped with ""high temp"" alarm//=
 He added water and started Gen manualy","Siligap Boris","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid Outage, site went down b=
ecause Gen stopped with ""high temp"" alarm// He added water and started Ge=
n manualy","system","200","20-10-2024 19:20:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003370112","E=
kounou","","20-10-2024 19:19:24","20-10-2024 19:17:21","20-10-2024 19:40:21=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen start automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen start automatically","joel=
le.ekessi@ihstowers.com","124","20-10-2024 19:19:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0003370100","B=
yemassi Carrefour","","20-10-2024 19:17:11","20-10-2024 18:57:06","20-10-20=
24 19:28:56","Grid outage, Site went down due to gen overload (20Kva ,270A)=
// He reduced a power limitation and started Gen manualy","Paul BIBOUM","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, Site w=
ent down due to gen overload (20Kva ,270A)// He reduced a power limitation =
and started Gen manualy","joelle.ekessi@ihstowers.com","1766","20-10-2024 1=
9:17:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003370075","M=
essa-Carriere OCM","","20-10-2024 19:13:29","20-10-2024 12:51:19","20-10-20=
24 12:55:41","No power issue site on grid with U=3D52,1V, FME TX Mohamadou/=
691144435/ from Huawei is informed","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D52,1V, FME TX Mohamadou/691144435/ from Huawei is informed","k=
ombi.samuel@ihstowers.com","22931","20-10-2024 19:13:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0003369775","C=
hapelle-Essos","","20-10-2024 18:44:24","20-10-2024 18:39:19","20-10-2024 2=
0:06:19","site went down due to Eneo contactor faulty // He bypassed Eneo c=
ontactor and gen manually started","Delor Telezing","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","site went down due to Eneo contactor=
 faulty // He bypassed Eneo contactor and gen manually started","joelle.eke=
ssi@ihstowers.com","305","20-10-2024 18:44:24","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003369762","MBI=
MBIM","","20-10-2024 18:41:36","20-10-2024 18:38:26","20-10-2024 18:54:25",=
"Site went down because Gen started and stopped due to water infiltration i=
n the tank//  He purged the tank, site on gen","Parker Tchoup","Fuel Outage=
 (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","S=
ite went down because Gen started and stopped due to water infiltration in =
the tank//  He purged the tank, site on gen","emmanuel.ghani@ihstowers.com"=
,"191","20-10-2024 18:41:36","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0003369654","Fla=
menco","","20-10-2024 18:24:05","20-10-2024 17:48:56","20-10-2024 23:18:15"=
,"Grid outage, site went down because gen ran untill fuel shortage // refue=
ling done","Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage, site went down because gen ran untill fuel shortage // refue=
ling done","kombi.samuel@ihstowers.com","2109","20-10-2024 18:24:05","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003369629","M=
vog-Manga","","20-10-2024 18:18:53","20-10-2024 18:18:50","20-10-2024 18:28=
:50","Grid fluctuation, sitte went down because gen start and stopped due t=
o grid bad volage // hy bypass grid and manually start tjhe gen","Albran By=
orel","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, sitte went down because gen start and stopped due to=
 grid bad volage // hy bypass grid and manually start tjhe gen","joelle.eke=
ssi@ihstowers.com","4","20-10-2024 18:18:53","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003369323","Ema=
na","","20-10-2024 17:38:49","20-10-2024 17:35:46","20-10-2024 19:02:21","G=
rid outage, site went down because card ge disfunction // he bypassed gen c=
ard and started Gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage, site went down because card ge dis=
function // he bypassed gen card and started Gen","emmanuel.ghani@ihstowers=
.com","184","20-10-2024 17:38:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003369152","M=
fou EPC","","20-10-2024 17:12:04","20-10-2024 17:09:01","20-10-2024 17:26:2=
4","Grid fluctuation, sitte went down because gen started and stopped due t=
o grid bad voltage no rcp on site// Grid stabilized","Mba Lazare Herve","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 fluctuation, sitte went down because gen started and stopped due to grid b=
ad voltage no rcp on site// Grid stabilized","joelle.ekessi@ihstowers.com",=
"184","20-10-2024 17:12:04","Sagemcom CMR"
"Closed Complete","Site Down","T1597","IHS_YND_670","NOCINC0003369034","BOB=
OCK","","20-10-2024 16:53:20","20-10-2024 16:51:15","20-10-2024 16:55:45","=
Active// No power issue on site ,site on Grid with Ubaie=3D 54,4V The fme t=
x Etienne fopa // 695033981 of huawei is informed and Up at 04:55 PM","Keme=
ni Franklin","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active// No power issue on site ,site on Grid with=
 Ubaie=3D 54,4V The fme tx Etienne fopa // 695033981 of huawei is informed =
and Up at 04:55 PM","emmanuel.ghani@ihstowers.com","125","20-10-2024 16:53:=
20","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003368841","Lad=
a I Yde","","20-10-2024 16:16:54","20-10-2024 16:14:50","20-10-2024 20:30:5=
8","Active//No power issue on site ,site on Grid  with Ubaie=3D54,3V The Tx=
 FME Leonel Steve  (655184876) from Huawei is informed.","Mba Lazare Herve"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue on site ,site on Grid  with Ubaie=3D54,=
3V The Tx FME Leonel Steve  (655184876) from Huawei is informed.","emmanuel=
.ghani@ihstowers.com","125","20-10-2024 16:16:54","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003368028","Nko=
lbisson","","20-10-2024 14:45:06","20-10-2024 14:41:26","20-10-2024 16:24:2=
6","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","grid outage, gen start and stopped with alarm 'Hight =
temp' // He added water and manually start the gen","emmanuel.ghani@ihstowe=
rs.com","3864","20-10-2024 14:45:06","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0003368017","Nko=
lbisson usines des eaux 2","IHS_YND_285","20-10-2024 14:43:30","20-10-2024 =
14:41:26","20-10-2024 16:24:26","Site impacted by nkolbisson: grid outage, =
gen start and stopped with alarm 'Hight temp' // He added water and manuall=
y start the gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","grid outage, gen start and stopped with al=
arm 'Hight temp' // He added water and manually start the gen","emmanuel.gh=
ani@ihstowers.com","124","20-10-2024 14:43:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003367925","Afanoya"=
,"","20-10-2024 14:38:51","20-10-2024 14:35:12","20-10-2024 15:51:12","Casc=
aded Incident from TTO3247126","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, DG Failed to start due to=
 overload (20Kva, 300A)  //  He reduice the load on site","system","219","2=
0-10-2024 14:38:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003367924","MBALNGON=
G LYCEE","","20-10-2024 14:38:50","20-10-2024 14:35:12","20-10-2024 15:51:1=
2","Cascaded Incident from TTO3247126","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start d=
ue to overload (20Kva, 300A)  //  He reduice the load on site","system","21=
8","20-10-2024 14:38:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003367923","ELOUMDEM=
 CARRIERE","","20-10-2024 14:38:50","20-10-2024 14:35:12","20-10-2024 15:51=
:12","Cascaded Incident from TTO3247126","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start=
 due to overload (20Kva, 300A)  //  He reduice the load on site","system","=
218","20-10-2024 14:38:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003367908","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","20-10-2024 14:36:18","20-10-=
2024 14:34:12","20-10-2024 15:51:12","Grid outage, DG Failed to start due t=
o overload (20Kva, 300A)  //  He reduice the load on site","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, DG=
 Failed to start due to overload (20Kva, 300A)  //  He reduice the load on =
site","joelle.ekessi@ihstowers.com","127","20-10-2024 14:36:18","Sagemcom C=
MR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003367789","Bas=
tos Bir","","20-10-2024 14:19:10","20-10-2024 14:14:00","20-10-2024 14:45:2=
0","site was on gen due to grid outage,site went down due to gen overload (=
12,5, 150Kva) // He reduced the load and started Gen manually.","Mboua Thie=
rry","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","site was on=
 gen due to grid outage,site went down due to gen overload (12,5, 150Kva) /=
/ He reduced the load and started Gen manually.","emmanuel.ghani@ihstowers.=
com","311","20-10-2024 14:19:10","Sagemcom CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0003367528","Eto=
ug-Ebe 2","","20-10-2024 13:34:25","20-10-2024 13:29:12","21-10-2024 00:41:=
14","Grid outage No space to deploy // Grid power return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No space =
to deploy // Grid power return","denis.mballa@ihstowers.com","314","20-10-2=
024 13:34:25","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003367522","Nko=
londom","","20-10-2024 13:33:20","20-10-2024 13:23:19","20-10-2024 15:23:18=
","Grid outage, site went down because gen ran untill fuel shortage // refu=
eling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran untill fuel shortage // re=
fueling done","denis.mballa@ihstowers.com","731","20-10-2024 13:33:20","Sag=
emcom CMR"
"Closed Complete","Site Down","T1685","IHS_YND_507","NOCINC0003367140","BIY=
EM ASSI LYCEE","","20-10-2024 12:46:51","20-10-2024 12:31:38","20-10-2024 1=
5:45:38","Grid outage, site went down due to PSC 3 dysfunctionning // grid =
return","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid outage, site went down due to PSC 3 dysfunctionning // g=
rid return","denis.mballa@ihstowers.com","914","20-10-2024 12:46:51","Sagem=
com CMR"
"Closed Complete","Site Down","T1411","IHS_YND_543","NOCINC0003367028","Ent=
ree Cite Verte","","20-10-2024 12:20:38","20-10-2024 12:07:50","20-10-2024 =
14:26:09","Grid outage.site went down due to controller PSC3 dysfunctionnin=
g//we bypass it and gen manually started ","Paul BIBOUM","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage.site went down du=
e to controller PSC3 dysfunctionning//we bypass it and gen manually started=
 ","denis.mballa@ihstowers.com","3129","20-10-2024 12:20:38","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003366969","Mvo=
g-Betsi","","20-10-2024 12:10:51","20-10-2024 12:04:38","20-10-2024 12:36:2=
7","site went down because insufficiency of rectifiers due to increase load=
 on site // site stanilized","Hyemafo Gildas","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","site went down because insufficiency of rec=
tifiers due to increase load on site // site stanilized","denis.mballa@ihst=
owers.com","373","20-10-2024 12:10:51","Sagemcom CMR"
"Closed Complete","Site Down","T1599","IHS_YND_245","NOCINC0003366963","Ngo=
usso-Savana","","20-10-2024 12:09:49","20-10-2024 12:00:20","20-10-2024 12:=
12:05","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automaticaly","Siligap Boris","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen start automaticaly","d=
enis.mballa@ihstowers.com","569","20-10-2024 12:09:49","Sagemcom CMR"
"Closed Complete","Site Down","T1744","IHS_YND_556","NOCINC0003366948","NKO=
MKANA ELIZA HOTEL","","20-10-2024 12:05:42","20-10-2024 11:58:21","21-10-20=
24 00:38:42","Grid outage No space to deploy // Grid power return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
No space to deploy // Grid power return","denis.mballa@ihstowers.com","442"=
,"20-10-2024 12:05:42","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003366941","Tsi=
nga","","20-10-2024 12:04:30","20-10-2024 11:55:18","20-10-2024 15:22:18","=
Access issues due to the Landllord: Grid outage, site went down because gen=
 ran untill fuel shortage // refueling done","Mboua Thierry","Access Denial=
","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Ac=
cess issues due to the Landllord: Grid outage, site went down because gen r=
an untill fuel shortage // refueling done","denis.mballa@ihstowers.com","55=
3","20-10-2024 12:04:30","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0003366858","Jou=
vence Mbenda","","20-10-2024 11:43:40","20-10-2024 11:37:24","20-10-2024 12=
:15:27","Grid outage.gen start and stopped due to ""high temp"" alarm//we a=
dd water and gen manually started ","Hyemafo Gildas","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid out=
age.gen start and stopped due to ""high temp"" alarm//we add water and gen =
manually started ","denis.mballa@ihstowers.com","376","20-10-2024 11:43:40"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003366836","T=
ongolo OCM","","20-10-2024 11:38:08","20-10-2024 11:09:54","20-10-2024 12:0=
0:38","Grid outage site went down because Gen failed to start due to Grid c=
ontactor dysfonction // He bypass the Grid contactor and Gen manually start=
ed","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Load C=
ontactor","Grid outage site went down because Gen failed to start due to Gr=
id contactor dysfonction // He bypass the Grid contactor and Gen manually s=
tarted","ange.kongo@ihstowers.com","1695","20-10-2024 11:38:08","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003366825","A=
kak-Nkozoa-MTN-IHS","","20-10-2024 11:34:48","20-10-2024 11:34:43","20-10-2=
024 14:38:58","Grid fluctuation, sitte went down because gen start and stop=
ped due to grid bad volage // hy bypass grid and manually start the gen","F=
abrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid fluctuation, sitte went down because gen start and stop=
ped due to grid bad volage // hy bypass grid and manually start the gen","a=
nge.kongo@ihstowers.com","7","20-10-2024 11:34:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0003366822","A=
RMP","","20-10-2024 11:33:42","20-10-2024 11:31:36","20-10-2024 12:55:55","=
Grid outage.gen failed to start due to no automation//gen manually started"=
,"","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage.gen failed to start due to no automation//gen manually started","ange.=
kongo@ihstowers.com","126","20-10-2024 11:33:42","Sagemcom CMR"
"Closed Complete","Site Down","T1690","IHS_YND_516","NOCINC0003366708","ETO=
UDI Entree du palais","","20-10-2024 11:23:06","20-10-2024 11:17:57","20-10=
-2024 13:28:28","site went down because gen start and stopped with alarm em=
ergency button stop//he reset the button and site on gen.Power issue resolv=
ed at 01:28 PM but site remains down Armand Nguetsa from Huawei is ","Fabri=
ce Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop"=
,"site went down because gen start and stopped with alarm emergency button =
stop//he reset the button and site on gen.Power issue resolved at 01:28 PM =
but site remains down Armand Nguetsa(691144412)from Huawei is informed","de=
nis.mballa@ihstowers.com","310","20-10-2024 11:23:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003366686","Scalom-I=
HS","","20-10-2024 11:20:56","20-10-2024 10:32:47","21-10-2024 00:43:15","G=
rid outage No space to deploy // Grid power return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage No space to dep=
loy // Grid power return","ange.kongo@ihstowers.com","2891","20-10-2024 11:=
20:56","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003366565","Nsi=
meyong Shell","","20-10-2024 10:57:52","20-10-2024 10:48:38","20-10-2024 12=
:03:57","Grid outage.gen failed to start due to high temp alarm//we add wat=
er and gen manually started ","MINKA NICOLAS","Equipment Repair","Passive",=
"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage.gen=
 failed to start due to high temp alarm//we add water and gen manually star=
ted ","denis.mballa@ihstowers.com","555","20-10-2024 10:57:52","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0003366535","S=
hell-Nsimeyong","","20-10-2024 10:54:38","20-10-2024 10:49:33","20-10-2024 =
11:58:56","Grid outage.gen failed started and stopped due to  alarm high te=
mp//He add water and gen manually started ","MINKA NICOLAS","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Radiator","Grid outage.gen failed started =
and stopped due to  alarm high temp//He add water and gen manually started =
","ange.kongo@ihstowers.com","306","20-10-2024 10:54:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0003366519","Y=
ona Hotel","","20-10-2024 10:52:46","20-10-2024 10:32:36","20-10-2024 11:33=
:12","Grid outage.gen failed to start due to high temp alarm//we add water =
and gen manually started ","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","P=
assive","ACDG Gen","ACDG - Radiator","Grid outage.gen failed to start due t=
o high temp alarm//we add water and gen manually started ","ange.kongo@ihst=
owers.com","1211","20-10-2024 10:52:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003366514","F=
ebe Village","","20-10-2024 10:51:38","20-10-2024 10:32:31","20-10-2024 11:=
28:33","Grid outage site went down because Gen failed to start due to PSC 3=
 faulty // He changed the PSC 3  and site on gen ","Mboua Thierry","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site we=
nt down because Gen failed to start due to PSC 3 faulty // He changed the P=
SC 3  and site on gen ","ange.kongo@ihstowers.com","1148","20-10-2024 10:51=
:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003366383","Mballa 4=
","","20-10-2024 10:34:40","20-10-2024 09:23:41","20-10-2024 09:24:41","Cas=
caded Incident from TTO3245318","Delor Telezing","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active//No power issue site on grid with=
 U=3D53,4V, Synphorien ( 691316854 ) from Huawei is informed. Notice that w=
e have disjunction at BTS OCM","system","4259","20-10-2024 10:34:40","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003366384","EMANA BI=
LICK CITY","","20-10-2024 10:34:40","20-10-2024 09:23:41","20-10-2024 09:24=
:41","Cascaded Incident from TTO3245318","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active//No power issue site on=
 grid with U=3D53,4V, Synphorien ( 691316854 ) from Huawei is informed. Not=
ice that we have disjunction at BTS OCM","system","4259","20-10-2024 10:34:=
40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003366385","Messassi=
 okolo","","20-10-2024 10:34:40","20-10-2024 09:23:41","20-10-2024 09:24:41=
","Cascaded Incident from TTO3245318","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active//No power issue site on gr=
id with U=3D53,4V, Synphorien ( 691316854 ) from Huawei is informed. Notice=
 that we have disjunction at BTS OCM","system","4259","20-10-2024 10:34:40"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003366377","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_279","20-10-2024 10:32:48","20-10-=
2024 09:23:41","20-10-2024 11:42:54","Active//No power issue site on grid w=
ith U=3D53,4V, Synphorien ( 691316854 ) from Huawei is informed. Notice tha=
t we have disjunction at BTS OCM","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue site on grid with U=3D53,4V, Synphorien ( 691316854 ) from Huaw=
ei is informed. Notice that we have disjunction at BTS OCM","ange.kongo@ihs=
towers.com","4147","20-10-2024 10:32:48","Sagemcom CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0003366376","BEA=
TITUDE ENTR=C9E PAVE","","20-10-2024 10:32:34","20-10-2024 10:25:19","20-10=
-2024 13:05:37","Grid outage.Site went down due to grid circuit breaker dam=
aged //we bypass Circuit Breaker and put site on gen","TIENTCHEU NZETCHIEU =
GAEL","Equipment Repair","Passive","Control Panel","Circuit Breaker - Off B=
y Unknown","Grid outage.Site went down due to grid circuit breaker damaged =
//we bypass Circuit Breaker and put site on gen","denis.mballa@ihstowers.co=
m","435","20-10-2024 10:32:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0003366346","L=
eboudi","","20-10-2024 10:26:10","20-10-2024 10:21:04","20-10-2024 13:04:13=
","Grid outage, Gen started  site went down because  Grid contactor dysfonc=
tion //He blocked Grid contactor, site on Gen","TIENTCHEU NZETCHIEU GAEL","=
Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage=
, Gen started  site went down because  Grid contactor dysfonction //He bloc=
ked Grid contactor, site on Gen","ange.kongo@ihstowers.com","307","20-10-20=
24 10:26:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0003366334","Nsam esc=
ale LP","","20-10-2024 10:24:40","20-10-2024 10:19:46","20-10-2024 10:43:46=
","Cascaded Incident from TTO3245252","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage site went down because Gen failed=
 to start due to psc 3 FAULTY// He Changed  the psc 3 by Relay 220V","syste=
m","294","20-10-2024 10:24:40","Sagemcom CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0003366322","Nsa=
m Sofavinc","IHS_YND_732","20-10-2024 10:22:01","20-10-2024 10:19:46","20-1=
0-2024 10:43:46","Grid outage site went down because Gen failed to start du=
e to psc 3 FAULTY// He Changed  the psc 3 by Relay 220V","MINKA NICOLAS","E=
quipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage sit=
e went down because Gen failed to start due to psc 3 FAULTY// He Changed  t=
he psc 3 by Relay 220V","denis.mballa@ihstowers.com","136","20-10-2024 10:2=
2:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0003366255","M=
vog-Ada_OCM","","20-10-2024 10:13:54","19-10-2024 21:06:40","19-10-2024 21:=
16:34","","","Grid Supply","Passive","Grid","National Grid - Grid Outage Is=
sue","grid outage, no space for a MDG//grid return","kouoh.jean@ihstowers.c=
om","47235","20-10-2024 10:13:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_131","NOCINC0003366179","Laborato=
ire  Meka","IHS_YND_193","20-10-2024 10:00:10","20-10-2024 09:50:58","21-10=
-2024 00:49:39","Grid outage No space to deploy // Grid power return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge No space to deploy // Grid power return","system","552","20-10-2024 10:0=
0:10","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003366175","Bas=
tos Ekoudou","","20-10-2024 09:59:10","20-10-2024 09:50:58","21-10-2024 00:=
49:39","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage No space to deploy // Grid power return","denis.=
mballa@ihstowers.com","493","20-10-2024 09:59:10","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0003366162","Crf=
-Mbankolo-IHS","","20-10-2024 09:56:40","20-10-2024 09:47:26","20-10-2024 1=
1:09:47","Grid outage, site went down because gen start a,nd stopped with A=
larm undervoltage // reduice the load an manually start the gen","Mboua Thi=
erry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
outage, site went down because gen start a,nd stopped with Alarm undervolta=
ge // reduice the load an manually start the gen","denis.mballa@ihstowers.c=
om","554","20-10-2024 09:56:40","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003366148","MIM=
BOMAN LIBERTE","","20-10-2024 09:54:02","20-10-2024 09:37:47","20-10-2024 0=
9:56:47","Grid outage Site went Down due to Main Gen Faulty//Grid Restored"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generat=
or Faulty","Grid outage Site went Down due to Main Gen Faulty//Grid Restore=
d","denis.mballa@ihstowers.com","976","20-10-2024 09:54:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_721","NOCINC0003366141","VOIRIE M=
UNICIPALE YAOUNDE","","20-10-2024 09:53:10","19-10-2024 21:05:58","19-10-20=
24 21:34:58","Cascaded Incident from TTO3245040","Paul BIBOUM","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","grid outage,no space to=
 deploy a mobil gen//grid return","system","46032","20-10-2024 09:53:10","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003366110","Eto koss=
 Yde","","20-10-2024 09:46:31","20-10-2024 09:39:56","20-10-2024 09:45:47",=
"Cascaded Incident from TTO3244993","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because insufficient =
of rectifiers due to increase load on site// site stabilized","system","395=
","20-10-2024 09:46:31","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003366101","MEF=
OU ASSI","IHS_YND_737","20-10-2024 09:45:02","20-10-2024 09:39:56","20-10-2=
024 09:45:47","site went down because insufficient of rectifiers due to inc=
rease load on site// site stabilized","Fanda Brice","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","site went down because insufficient o=
f rectifiers due to increase load on site// site stabilized","denis.mballa@=
ihstowers.com","308","20-10-2024 09:45:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003366011","S=
atcom","","20-10-2024 09:33:49","20-10-2024 09:21:35","20-10-2024 09:22:25"=
,"ACTIVE No power issue on site, site on Gen with Ubaie=3D52,1V Tx fme Arma=
nd Ngeuts/699949553/ from Huawei is Informed","Delor Telezing","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE No power issue on site, site on Gen with Ubaie=3D52,1V Tx fme Armand=
 Ngeuts/699949553/ from Huawei is Informed","ange.kongo@ihstowers.com","735=
","20-10-2024 09:33:49","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003366006","Pha=
rmacie SION","","20-10-2024 09:33:10","20-10-2024 09:25:58","20-10-2024 09:=
36:06","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automaticaly","Paul BIBOUM","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen start automaticaly","den=
is.mballa@ihstowers.com","432","20-10-2024 09:33:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0003365947","Nkolkoum=
ou OCM","","20-10-2024 09:21:30","20-10-2024 09:14:24","20-10-2024 15:41:44=
","Cascaded Incident from TTO3244807","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Priming pum faulty","=
system","426","20-10-2024 09:21:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003365944","N=
kolbisson usine des eaux","IHS_YND_712","20-10-2024 09:20:41","20-10-2024 0=
9:14:24","20-10-2024 15:16:44","grid outage, site down due to priming pump =
faulty//mdg 20 kva deplyed","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","=
Passive","ACDG Gen","ACDG - Fuel Lifting Pump Faulty","grid outage, site do=
wn due to priming pump faulty//mdg 20 kva deplyed","ange.kongo@ihstowers.co=
m","378","20-10-2024 09:20:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003365915","N=
koabang2","","20-10-2024 09:17:03","19-10-2024 19:21:44","19-10-2024 19:35:=
32","Grid outage, site went down before gen start due to poor battery backu=
p // Gen start automatically","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"kouoh.jean@ihstowers.com","50120","20-10-2024 09:17:03","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0003365892","Nko=
lbisson IITA LP","","20-10-2024 09:13:15","20-10-2024 08:47:03","20-10-2024=
 11:46:30","Grid outage No space to deploy //Grid power return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No =
space to deploy //Grid power return","denis.mballa@ihstowers.com","1573","2=
0-10-2024 09:13:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0003365885","N=
simalen OCM","","20-10-2024 09:10:34","19-10-2024 18:54:26","19-10-2024 22:=
07:18","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage, Site went down because Gen failed to start  wit=
h  Alarm""Over-Voltage""//he resert Gen card and started Gen","kouoh.jean@i=
hstowers.com","60212","20-10-2024 09:10:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003365875","c=
hina embassy yde","","20-10-2024 09:07:19","19-10-2024 18:54:05","19-10-202=
4 20:04:43","","","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","No power issue site on grid wth U=3D53.3v Elo=
undou Bertrand(652586578) from Huawei is informed","kouoh.jean@ihstowers.co=
m","51195","20-10-2024 09:07:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003365799","A=
wae Ewonkan","","20-10-2024 09:04:26","19-10-2024 18:39:09","19-10-2024 18:=
59:30","","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - C=
ontrol Panel","grid outage, site down before gen start//gen started (invest=
igations ongoing)","kouoh.jean@ihstowers.com","51918","20-10-2024 09:04:26"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003365755","T=
singa","","20-10-2024 08:54:48","19-10-2024 18:28:37","19-10-2024 18:52:10"=
,"","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Battery Low","grid outage site down due to poor backup//gen started"=
,"kouoh.jean@ihstowers.com","51973","20-10-2024 08:54:48","Sagemcom CMR"
"Closed Complete","Site Down","T2180","IHS_YND_569","NOCINC0003365745","Men=
dong Maeture","","20-10-2024 08:51:02","20-10-2024 08:43:48","20-10-2024 11=
:27:43","grid outage, gen fail to start due to F7 fuse cuts//made a shunt, =
gen started","Hyemafo Gildas","Equipment Repair","Passive","Control Panel",=
"ATS-AMF Issue","grid outage, gen fail to start due to F7 fuse cuts//made a=
 shunt, gen started","denis.mballa@ihstowers.com","434","20-10-2024 08:51:0=
2","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003365735","NYO=
M FACE MAETUR","","20-10-2024 08:48:53","20-10-2024 08:31:41","20-10-2024 0=
8:55:20","","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Emergency Stop Switch","Grid outage, Landlord has forbidden to start the=
 generator due to noise // Grid restored","denis.mballa@ihstowers.com","103=
3","20-10-2024 08:48:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_506","NOCINC0003365725","Omnispor=
t-Rail","","20-10-2024 08:47:00","19-10-2024 19:48:33","19-10-2024 21:21:33=
","Cascaded Incident from TTO3242581","Delor Telezing","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage//grid return","syst=
em","46707","20-10-2024 08:47:00","Sagemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003365666","Bas=
tos Bir","","20-10-2024 08:36:21","20-10-2024 08:33:59","20-10-2024 10:20:1=
3","grid outage, site went down because gen failed to start due to battery =
Gen faulty// gen manually started with external battery","Mboua Thierry","E=
quipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","grid outa=
ge, site went down because gen failed to start due to battery Gen faulty// =
gen manually started with external battery","denis.mballa@ihstowers.com","6=
26","20-10-2024 08:36:21","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003365649","Ebo=
go","","20-10-2024 08:32:47","20-10-2024 08:28:32","20-10-2024 08:45:33","G=
rid outage, site went down before gen start due to poor battery backup // G=
en start automaticaly","Siligap Boris","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
gen start due to poor battery backup // Gen start automaticaly","denis.mbal=
la@ihstowers.com","18885","20-10-2024 08:32:47","Sagemcom CMR"
"Closed Complete","Site Down","T2859","IHS_YND_071","NOCINC0003365554","Sca=
lom","","20-10-2024 08:14:42","20-10-2024 08:06:28","20-10-2024 09:54:28","=
","Paul BIBOUM","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"CB of rectifier tripped due to two rectifiers faulties//replaced faulties=
 rectifiers","denis.mballa@ihstowers.com","495","20-10-2024 08:14:42","Sage=
mcom CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0003365545","Efo=
ulan MTN","","20-10-2024 08:11:33","20-10-2024 08:02:18","20-10-2024 09:02:=
28","","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Kick=
 Starter","Grid outage site went down because Gen failed to start  due to g=
low plug// he heated the glow plug and Gen manually started ","denis.mballa=
@ihstowers.com","556","20-10-2024 08:11:33","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0003365464","An-=
Marche-Melen","","20-10-2024 07:54:21","20-10-2024 07:45:23","20-10-2024 11=
:46:35","Grid outage No space to deploy //Grid power return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No spa=
ce to deploy //Grid power return","denis.mballa@ihstowers.com","610","20-10=
-2024 07:54:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003365450","M=
aison-Blanche-IHS","","20-10-2024 07:51:19","20-10-2024 07:31:10","21-10-20=
24 00:37:55","Grid Outage No Space to deploy a MDG // Grid Restored","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outag=
e No Space to deploy a MDG // Grid Restored","ange.kongo@ihstowers.com","12=
10","20-10-2024 07:51:19","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0003365444","Eto=
ug ebe biscuiterie","","20-10-2024 07:50:02","20-10-2024 07:42:47","20-10-2=
024 10:54:40","grid outage, gen start and stopped with alarm 'Low oil press=
ure' // He added oil and Gen manually started","Hyemafo Gildas","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage, gen start=
 and stopped with alarm 'Low oil pressure' // He added oil and Gen manually=
 started","denis.mballa@ihstowers.com","435","20-10-2024 07:50:02","Sagemco=
m CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0003365216","Men=
dong NB","","20-10-2024 07:18:35","20-10-2024 06:36:23","20-10-2024 15:06:5=
7","Grid Outage No Space to deploy a MDG //Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space to=
 deploy a MDG //Grid return","denis.mballa@ihstowers.com","2533","20-10-202=
4 07:18:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003365068","E=
kombitie","","20-10-2024 06:41:58","20-10-2024 06:39:48","20-10-2024 06:40:=
23","Active, No power issue on site ,site on Grid with Ubaie=3D54.5 V The T=
x FME Synphorien /691316854//from huawei is informed","Fabrice Pouakam","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active, No power issue on site ,site on Grid with Ubaie=3D54.5 V T=
he Tx FME Synphorien /691316854//from huawei is informed","ange.kongo@ihsto=
wers.com","131","20-10-2024 06:41:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003365034","M=
ini-Ferme","","20-10-2024 06:36:01","20-10-2024 06:21:53","21-10-2024 00:40=
:10","Grid outage No space to deploy // Grid power return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No space=
 to deploy // Grid power return","ange.kongo@ihstowers.com","849","20-10-20=
24 06:36:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003365001","Yoko OCM=
","","20-10-2024 06:32:11","20-10-2024 06:25:08","20-10-2024 06:26:08","Cas=
caded Incident from TTO3243705","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen  with U =
=3D 50.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657=
959647of Huawei is informed","system","423","20-10-2024 06:32:11","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003365002","Ngouetou=
","","20-10-2024 06:32:11","20-10-2024 06:25:08","20-10-2024 06:26:08","Cas=
caded Incident from TTO3243705","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen  with U =
=3D 50.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657=
959647of Huawei is informed","system","423","20-10-2024 06:32:11","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003365003","MBIMBIM"=
,"","20-10-2024 06:32:11","20-10-2024 06:25:08","20-10-2024 06:26:08","Casc=
aded Incident from TTO3243705","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen  with U =3D=
 50.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","423","20-10-2024 06:32:11","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003364999","Ngoum","=
","20-10-2024 06:32:10","20-10-2024 06:25:08","20-10-2024 06:26:08","Cascad=
ed Incident from TTO3243705","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Gen  with U =3D 5=
0.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795964=
7of Huawei is informed","system","422","20-10-2024 06:32:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003365000","Matsari"=
,"","20-10-2024 06:32:10","20-10-2024 06:25:08","20-10-2024 06:26:08","Casc=
aded Incident from TTO3243705","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen  with U =3D=
 50.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","422","20-10-2024 06:32:10","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003364794","ELOUMDEM=
 CARRIERE 2","","20-10-2024 05:47:36","20-10-2024 05:38:31","20-10-2024 05:=
52:32","","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Hig=
h Engine Temp - Coolant Level Issue","Site was on Gen due to Grid outage, s=
ite went down because Gen stopped with ""high temp"" alarm// he added water=
 and started Gen manualy","stephane.nkamwa@ihstowers.com","546","20-10-2024=
 05:47:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003364590","TSINGA V=
ILLAGE 2","","20-10-2024 04:41:34","20-10-2024 04:35:27","20-10-2024 06:39:=
27","site up","Delor Telezing","Fuel Outage (Probable)","Passive","Diesel",=
"Tank Sealing Issue - Water In The Fuel","grid outage, gen stopped due to w=
ater intake in the tank due to the rain//removed water, purged and started =
the gen","stephane.nkamwa@ihstowers.com","488","20-10-2024 04:41:34","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003364479","N=
kolfon Cimencam","","20-10-2024 03:55:09","20-10-2024 03:49:04","20-10-2024=
 03:50:49","Active//No power issue on site U=3D54,5v site on Gen and  Rm Al=
ain (691144423)of huawei is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue on site U=3D54,5v site on Gen and  Rm Alain (691144423)of hu=
awei is informed","ludivine.ngamaleu@ihstowers.com","366","20-10-2024 03:55=
:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0003364440","B=
ondjock","","20-10-2024 03:45:39","20-10-2024 03:36:34","20-10-2024 04:09:2=
1","Grid outage, Gen started but did not feeds the site due to Gen contacto=
r disfunction// He blocked Gen contactor, Site on Gen","Fanda Brice","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Grid outage, Gen=
 started but did not feeds the site due to Gen contactor disfunction// He b=
locked Gen contactor, Site on Gen","ludivine.ngamaleu@ihstowers.com","546",=
"20-10-2024 03:45:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0003364167","MONTEE N=
KONDENGUI","","20-10-2024 02:12:30","19-10-2024 20:47:38","19-10-2024 21:15=
:45","Cascaded Incident from TTO3242712","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage// grid return","s=
ystem","19492","20-10-2024 02:12:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0003364165","M=
obil-Kondengui","IHS_YND_682","20-10-2024 02:11:56","19-10-2024 20:47:38","=
19-10-2024 21:15:45","grid outage// grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","grid outage// grid return","ko=
uoh.jean@ihstowers.com","19459","20-10-2024 02:11:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0003364117","A=
cropole","","20-10-2024 01:44:34","19-10-2024 20:15:40","19-10-2024 21:18:5=
7","Site up","MINKA NICOLAS","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","no power issue on site ubaie=3D54v=
 site on grid","kouoh.jean@ihstowers.com","19734","20-10-2024 01:44:34","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003364105","E=
mombo-Tchad","IHS_YND_114","20-10-2024 01:38:42","19-10-2024 20:00:33","19-=
10-2024 21:36:33","grid outage,no space to deploy a mobil gen//grid return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","gri=
d outage,no space to deploy a mobil gen//grid return","kouoh.jean@ihstowers=
.com","20290","20-10-2024 01:38:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003364101","B=
ATA-Mokolo","","20-10-2024 01:37:11","19-10-2024 20:31:17","19-10-2024 21:1=
7:17","grid outage,no space to deploy a mobil gen//grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no =
space to deploy a mobil gen//grid return","kouoh.jean@ihstowers.com","18356=
","20-10-2024 01:37:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_800","NOCINC0003364062","ODZA CIT=
E MBIA","","20-10-2024 01:26:56","20-10-2024 01:20:49","20-10-2024 07:28:37=
","Access during the night due to landload","Albran Byorel","Access Denial"=
,"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Acc=
ess during the night due to landload, grid outage, gen fails to start due t=
o ATS disfunction//site on grid","stephane.nkamwa@ihstowers.com","368","20-=
10-2024 01:26:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0003364055","E=
koumdoum","","20-10-2024 01:23:22","19-10-2024 19:49:20","19-10-2024 20:09:=
20","grid outage, site went down because gen start and stoppen with  alarm =
overvoltage //he balanced the loads, site on gen","Albran Byorel","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage, site we=
nt down because gen start and stoppen with  alarm overvoltage //he balanced=
 the loads, site on gen","kouoh.jean@ihstowers.com","20043","20-10-2024 01:=
23:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0003364054","H=
-Paradis","IHS_YND_506","20-10-2024 01:21:23","19-10-2024 19:48:33","19-10-=
2024 21:21:33","grid outage//grid return","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","grid outage//grid return","kouoh.jean=
@ihstowers.com","19971","20-10-2024 01:21:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003364029","H=
-General-Yde","","20-10-2024 01:13:42","19-10-2024 19:06:30","20-10-2024 04=
:40:37","No power issue site on grid with U=3D53,2v Armand Nguetsa(69114441=
2) from Huawei is informed. Notice that we have disjunction at BTS OCM","Si=
ligap Boris","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","No power issue site on grid with U=3D53,2v Armand =
Nguetsa(691144412) from Huawei is informed. Notice that we have disjunction=
 at BTS OCM","kouoh.jean@ihstowers.com","22033","20-10-2024 01:13:42","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0003364025","S=
imbock OCM","","20-10-2024 01:12:38","19-10-2024 19:05:06","19-10-2024 21:5=
4:06","Grid Outage, site went down because Gen stopped with ""high temp"" a=
larm due to radiator perced // Grid power return","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Is=
sue","Grid Outage, site went down because Gen stopped with ""high temp"" al=
arm due to radiator perced // Grid power return","kouoh.jean@ihstowers.com"=
,"22053","20-10-2024 01:12:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003364007","E=
lig-Edzoa","","20-10-2024 01:09:01","19-10-2024 18:59:31","19-10-2024 21:38=
:31","grid outage//grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","grid outage//grid return","kouoh.jean@ihstowers=
.com","22171","20-10-2024 01:09:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003363973","B=
arriere","","20-10-2024 00:59:07","19-10-2024 18:46:46","19-10-2024 19:55:3=
1","Grid fluctuation, site went down because gen fails to start due to grid=
 bad voltage // he bypass grid and manually start the gen","Hyemafo Gildas"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid fluctuation, site went down because gen fails to start due to grid bad=
 voltage // he bypass grid and manually start the gen","kouoh.jean@ihstower=
s.com","22341","20-10-2024 00:59:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003363957","Emana Ly=
cee","","20-10-2024 00:52:33","19-10-2024 18:51:45","19-10-2024 19:33:45","=
Cascaded Incident from TTO3242451","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid fluctuation  gen fails to st=
art with alarm undervoltage//grid returned","system","21648","20-10-2024 00=
:52:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003363958","Messassi=
 okolo","","20-10-2024 00:52:33","19-10-2024 18:51:45","19-10-2024 19:33:45=
","Cascaded Incident from TTO3242451","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid fluctuation  gen fails to=
 start with alarm undervoltage//grid returned","system","21648","20-10-2024=
 00:52:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003363959","Emana ly=
cee 2","","20-10-2024 00:52:33","19-10-2024 18:51:45","19-10-2024 19:33:45"=
,"Cascaded Incident from TTO3242451","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid fluctuation  gen fails to =
start with alarm undervoltage//grid returned","system","21648","20-10-2024 =
00:52:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003363955","Mballa 4=
","","20-10-2024 00:52:32","19-10-2024 18:51:45","19-10-2024 19:33:45","Cas=
caded Incident from TTO3242451","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid fluctuation  gen fails to start =
with alarm undervoltage//grid returned","system","21647","20-10-2024 00:52:=
32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003363956","EMANA BI=
LICK CITY","","20-10-2024 00:52:32","19-10-2024 18:51:45","19-10-2024 19:33=
:45","Cascaded Incident from TTO3242451","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid fluctuation  gen fails=
 to start with alarm undervoltage//grid returned","system","21647","20-10-2=
024 00:52:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0003363930","M=
vog Mbi New","","20-10-2024 00:43:32","19-10-2024 18:47:22","19-10-2024 19:=
40:14","Grid outage, site went down because Gen failed to start due to batt=
ery Gen faulty// Gen manually started with external battery","MINKA NICOLAS=
","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid =
outage, site went down because Gen failed to start due to battery Gen fault=
y// Gen manually started with external battery","kouoh.jean@ihstowers.com",=
"21371","20-10-2024 00:43:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003363927","S=
tade-Abega","","20-10-2024 00:41:45","19-10-2024 18:40:35","19-10-2024 20:0=
4:27","grid outage, gen fails to start due to glow plug//he removed and rec=
onnected glow plug and gen started","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - Kick Starter","grid outage, gen fails to start =
due to glow plug//he removed and reconnected glow plug and gen started","ko=
uoh.jean@ihstowers.com","21671","20-10-2024 00:41:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003363687","N=
kolda","IHS_YND_327","19-10-2024 23:14:52","19-10-2024 18:54:26","19-10-202=
4 22:07:18","Grid outage, Site went down because Gen failed to start  with =
 Alarm""Over-Voltage""//he resert Gen card and started Gen","Albran Byorel"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outag=
e, Site went down because Gen failed to start  with  Alarm""Over-Voltage""/=
/he resert Gen card and started Gen","kouoh.jean@ihstowers.com","22154","19=
-10-2024 23:14:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003363678","N=
kolndongo","","19-10-2024 23:12:07","19-10-2024 18:57:51","19-10-2024 22:08=
:55","Grid outage site went down because Main Gen faulty// He connected MDG=
 20Kva","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Gen=
erator Faulty","Grid outage site went down because Main Gen faulty// He con=
nected MDG 20Kva","kouoh.jean@ihstowers.com","22024","19-10-2024 23:12:07",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003363633","Ngouetou=
","","19-10-2024 23:05:31","19-10-2024 22:59:52","19-10-2024 23:00:59","Cas=
caded Incident from TTO3242076","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Battery with U=
 =3D 49.6V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane =
657959647of Huawei is informed","system","339","19-10-2024 23:05:31","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003363631","Matsari"=
,"","19-10-2024 23:05:31","19-10-2024 22:59:52","19-10-2024 23:00:59","Casc=
aded Incident from TTO3242076","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Battery with U =
=3D 49.6V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 6=
57959647of Huawei is informed","system","339","19-10-2024 23:05:31","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003363634","MBIMBIM"=
,"","19-10-2024 23:05:31","19-10-2024 22:59:52","19-10-2024 23:00:59","Casc=
aded Incident from TTO3242076","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Battery with U =
=3D 49.6V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 6=
57959647of Huawei is informed","system","339","19-10-2024 23:05:31","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003363632","Yoko OCM=
","","19-10-2024 23:05:31","19-10-2024 22:59:52","19-10-2024 23:00:59","Cas=
caded Incident from TTO3242076","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Battery with U=
 =3D 49.6V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane =
657959647of Huawei is informed","system","339","19-10-2024 23:05:31","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003363630","Ngoum","=
","19-10-2024 23:05:30","19-10-2024 22:59:52","19-10-2024 23:00:59","Cascad=
ed Incident from TTO3242076","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Battery with U =
=3D 49.6V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 6=
57959647of Huawei is informed","system","338","19-10-2024 23:05:30","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003363521","S=
ous Prefecture","","19-10-2024 22:36:25","19-10-2024 22:33:21","20-10-2024 =
03:29:51","Active//No power isssue, site is on Gen with Ubaie=3D54,2V,  TX =
FME PATRICK (672390202) from Huawei is informed","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power isssue, site is on Gen with Ubaie=3D54,2V,  TX FME PATRICK=
 (672390202) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","18=
5","19-10-2024 22:36:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_189","IHS_YND_422","NOCINC0003363459","B=
otmakak","","19-10-2024 22:20:39","19-10-2024 22:03:34","19-10-2024 22:04:4=
0","Active//No power issue Ubaie=3D53.4V;  site on Grid TX  FME Etienne 695=
033981  from Huawei is informed.","Kemeni Franklin","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue Ubaie=3D53.4V;  site on Grid TX  FME Etienne 695033981  from Hu=
awei is informed.","ludivine.ngamaleu@ihstowers.com","1026","19-10-2024 22:=
20:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0003363337","N=
komkana 2","","19-10-2024 21:54:55","19-10-2024 20:41:39","20-10-2024 07:12=
:19","access issue during the night inverter CB tripped //nverter CB puts b=
ackon/","Mboua Thierry","Access Denial","Lease Or Legal","Landlord Related =
Issues","Access Issue - Land Lord","access issue during the night inverter =
CB tripped //nverter CB puts backon/","kouoh.jean@ihstowers.com","4397","19=
-10-2024 21:54:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0003363336","Mvog-Eba=
nda","","19-10-2024 21:54:20","19-10-2024 20:33:29","19-10-2024 22:22:11","=
Cascaded Incident from TTO3241707","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause gen fails to start due to grid bad voltage and poor backup // he bypa=
ss grid and manually start the gen","system","4851","19-10-2024 21:54:20","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003363332","A=
bom","IHS_YND_269","19-10-2024 21:53:39","19-10-2024 20:33:29","19-10-2024 =
22:22:11","Grid fluctuation, site went down because gen fails to start due =
to grid bad voltage and poor backup // he bypass grid and manually start th=
e gen","Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation, site went down because gen fails to=
 start due to grid bad voltage and poor backup // he bypass grid and manual=
ly start the gen","kouoh.jean@ihstowers.com","4811","19-10-2024 21:53:39","=
Sagemcom CMR"
"Closed Complete","Site Down","T0463","IHS_YND_215","NOCINC0003363252","Ele=
veurs","","19-10-2024 21:40:41","19-10-2024 21:28:30","19-10-2024 22:07:30"=
,"Grid outage, site went down because Gen failed to start due to contactor =
Grid faulty//Grid restored","Siligap Boris","Equipment Repair","Passive","C=
ontrol Panel","ATS-AMF Issue","Grid outage, site went down because Gen fail=
ed to start due to contactor Grid faulty//Grid restored","kamga.virgile@ihs=
towers.com","732","19-10-2024 21:40:41","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0003363246","MVA=
N SACEL","","19-10-2024 21:39:09","19-10-2024 21:27:46","19-10-2024 21:40:5=
9","Grid outage, site went down before gen start due to poor battery backup=
 // Gen start automaticaly","MINKA NICOLAS","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen start automaticaly","kamga=
.virgile@ihstowers.com","46569","19-10-2024 21:39:09","Sagemcom CMR"
"Closed Complete","Site Down","T0120","IHS_YND_031","NOCINC0003363241","Sim=
e Building","","19-10-2024 21:37:46","19-10-2024 21:16:38","19-10-2024 21:5=
0:38","grid outage, gen ran till diesel outage//refueling done","Mboua Thie=
rry","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage, gen ran=
 till diesel outage//refueling done","kamga.virgile@ihstowers.com","1269","=
19-10-2024 21:37:46","Sagemcom CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0003363215","Cha=
rles-Atangana","","19-10-2024 21:34:52","19-10-2024 21:21:41","19-10-2024 2=
1:38:41","grid outage//grid return","","Grid Supply","Passive","Grid","Nati=
onal Grid - Grid Outage Issue","grid outage//grid return","kamga.virgile@ih=
stowers.com","792","19-10-2024 21:34:52","Sagemcom CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0003363115","ENA=
M","IHS_YND_721","19-10-2024 21:20:40","19-10-2024 21:05:30","19-10-2024 21=
:35:30","grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,n=
o space to deploy a mobil gen//grid return","kamga.virgile@ihstowers.com","=
911","19-10-2024 21:20:40","Sagemcom CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0003362994","Mae=
tur","","19-10-2024 21:04:40","19-10-2024 20:49:26","19-10-2024 21:12:26","=
Site on DG due to grid outage,Site went down due to ACDG circuit breaker do=
wn //Circuit Breaker put back on(Inverstigations ongoing).","Mboua Thierry"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Brea=
ker Issue","Site on DG due to grid outage,Site went down due to ACDG circui=
t breaker down //Circuit Breaker put back on(Inverstigations ongoing).","ka=
mga.virgile@ihstowers.com","915","19-10-2024 21:04:40","Sagemcom CMR"
"Closed Complete","Site Down","T0035","IHS_YND_051","NOCINC0003362986","Mam=
ch Building","","19-10-2024 21:03:22","19-10-2024 20:46:08","19-10-2024 21:=
15:37","site up","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","A=
CDG - Control Panel","site was on gen due to grid outage, gen stopped with =
alarm overcurrent(unproven)//disconnected the current pin, and started the =
gen","kamga.virgile@ihstowers.com","1035","19-10-2024 21:03:22","Sagemcom C=
MR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0003362980","Imm=
-Olympique","","19-10-2024 21:01:19","19-10-2024 20:45:54","19-10-2024 21:2=
9:54","grid outage, gen fails to start du to power cable stolen since//he c=
onnected the gen with a power cable","Paul BIBOUM","Equipment Repair","Pass=
ive","Infrastructure","Armoured Cable","grid outage, gen fails to start du =
to power cable stolen since//he connected the gen with a power cable","kamg=
a.virgile@ihstowers.com","925","19-10-2024 21:01:19","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003362969","Mim=
boman3","","19-10-2024 20:58:42","19-10-2024 20:15:09","19-10-2024 21:37:25=
","Site was on Gen due to Grid outage, site went because Gen stopped due to=
 CB Gen tripped// He put back on CB Gen","Mba Lazare Herve","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Load Breaker","Site was on Gen due to Grid=
 outage, site went because Gen stopped due to CB Gen tripped// He put back =
on CB Gen","kamga.virgile@ihstowers.com","19870","19-10-2024 20:58:42","Sag=
emcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003362887","Nko=
lnda","","19-10-2024 20:44:41","19-10-2024 20:11:33","20-10-2024 04:25:56",=
"","Albran Byorel","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue, site is on Gen with Ubaie=3D=
54,9V, Lionel adjep(655184876) from Huawei is informed","kamga.virgile@ihst=
owers.com","1988","19-10-2024 20:44:41","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0003362875","Nko=
lbisson IITA LP","","19-10-2024 20:43:12","19-10-2024 20:11:58","19-10-2024=
 21:55:58","grid outage,no space to deploy a mobil gen//grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outag=
e,no space to deploy a mobil gen//grid return","kamga.virgile@ihstowers.com=
","1875","19-10-2024 20:43:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003362858","M=
imboman-Village","","19-10-2024 20:40:28","19-10-2024 18:35:22","19-10-2024=
 19:47:22","Grid outage, site went down before gen start due to poor batter=
y backup // Gen started","Mba Lazare Herve","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started","kouoh.jean@ihsto=
wers.com","7507","19-10-2024 20:40:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003362832","C=
amp-Sic-Tsinga","","19-10-2024 20:36:36","19-10-2024 18:34:06","19-10-2024 =
21:17:06","grid outage,no space to deploy a mobil gen // grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outa=
ge,no space to deploy a mobil gen // grid return","kouoh.jean@ihstowers.com=
","7351","19-10-2024 20:36:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003362796","M=
adison","","19-10-2024 20:33:36","19-10-2024 18:32:25","19-10-2024 21:12:01=
","grid outage,no space to deploy a mobil gen//grid return","MFOUAGUEGUE MA=
THIEU","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
grid outage,no space to deploy a mobil gen//grid return","kouoh.jean@ihstow=
ers.com","7272","19-10-2024 20:33:36","Sagemcom CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0003362728","Ese=
ka Town","","19-10-2024 20:20:46","19-10-2024 19:53:47","20-10-2024 23:19:0=
4","","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","tx","kamga.virgile@ihstowers.com","109197","19-10-2024 20:20:4=
6","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003362713","T=
ongolo OCM","","19-10-2024 20:18:00","19-10-2024 18:26:47","19-10-2024 20:2=
8:47","site up","Delor Telezing","Equipment Repair","Passive","Control Pane=
l","ATS-AMF Issue","Grid outage site went down because Gen failed to start =
due to Grid contactor dysfonction // He bypass the Grid contactor and Gen m=
anually started","kouoh.jean@ihstowers.com","6675","19-10-2024 20:18:00","S=
agemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0003362686","Fla=
menco","","19-10-2024 20:09:13","19-10-2024 19:45:57","19-10-2024 21:59:57"=
,"Grid Outage Site went down due to Gen Card Faulty on Site // Grid Restore=
d","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","Grid Outage Site went down due to Gen Card Faulty on Site // Grid R=
estored","kamga.virgile@ihstowers.com","1397","19-10-2024 20:09:13","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0003362614","C=
NR","","19-10-2024 19:55:18","19-10-2024 19:45:12","20-10-2024 07:59:43","a=
ccess issue during the weekend Grid outage .gen failed to start due to star=
ter relay faulty//Grid return","Mboua Thierry","Access Denial","Lease Or Le=
gal","Landlord Related Issues","Access Issue - Land Lord","access issue dur=
ing the weekend Grid outage .gen failed to start due to starter relay fault=
y//Grid return","kouoh.jean@ihstowers.com","607","19-10-2024 19:55:18","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003362611","M=
ini-Ferme","","19-10-2024 19:54:10","19-10-2024 19:43:57","19-10-2024 22:10=
:57","grid outage,no space to deploy a mobil gen//grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no s=
pace to deploy a mobil gen//grid return","kouoh.jean@ihstowers.com","614","=
19-10-2024 19:54:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0003362602","B=
astos Bethesda","","19-10-2024 19:52:28","19-10-2024 19:42:22","19-10-2024 =
21:06:52","","Mboua Thierry","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","grid outage, site down due to poor backup//ge=
n started","kouoh.jean@ihstowers.com","607","19-10-2024 19:52:28","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003362599","E=
ssomba","","19-10-2024 19:51:26","19-10-2024 19:37:18","19-10-2024 21:53:13=
","","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, site went down due to gen Overload(15KVA, 200) //   He=
 reduced the load","kouoh.jean@ihstowers.com","849","19-10-2024 19:51:26","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0003362571","A=
n-Marche-Melen","","19-10-2024 19:44:14","19-10-2024 19:34:01","19-10-2024 =
21:52:01","grid outage,no space to deploy a mobil gen//grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage=
,no space to deploy a mobil gen//grid return","kouoh.jean@ihstowers.com","6=
14","19-10-2024 19:44:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0003362529","FOUGEROL=
E","","19-10-2024 19:38:20","19-10-2024 19:31:33","19-10-2024 19:44:33","Ca=
scaded Incident from TTO3240738","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down before ge=
n start due to poor battery backup // Gen start automaticaly","system","407=
","19-10-2024 19:38:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0003362528","N=
gousso-Savana","IHS_YND_561","19-10-2024 19:37:39","19-10-2024 19:31:33","1=
9-10-2024 19:46:33","Grid outage, site went down before gen start due to po=
or battery backup // Gen start automaticaly","Siligap Boris","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
site went down before gen start due to poor battery backup // Gen start aut=
omaticaly","kouoh.jean@ihstowers.com","367","19-10-2024 19:37:39","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003362506","H=
-Progres","","19-10-2024 19:34:43","19-10-2024 19:31:15","19-10-2024 21:40:=
23","grid outage,no space to deploy a mobil gen//grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no sp=
ace to deploy a mobil gen//grid return","kouoh.jean@ihstowers.com","209","1=
9-10-2024 19:34:43","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0003362491","Av =
Kennedy","","19-10-2024 19:31:49","19-10-2024 18:59:30","19-10-2024 21:31:3=
0","grid outage,no space to deploy a mobil gen//grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no spa=
ce to deploy a mobil gen//grid return","kamga.virgile@ihstowers.com","1939"=
,"19-10-2024 19:31:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003362490","N=
kozoa","","19-10-2024 19:31:46","19-10-2024 19:24:40","19-10-2024 22:02:40"=
,"Site went because CB(125A) tripped who feeds BTS OCM in DC BOX due to Gri=
d fluctuation// CB put back on","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went beca=
use CB(125A) tripped who feeds BTS OCM in DC BOX due to Grid fluctuation// =
CB put back on","kouoh.jean@ihstowers.com","427","19-10-2024 19:31:46","Sag=
emcom CMR"
"Closed Complete","Site Down","T0456","IHS_YND_224","NOCINC0003362484","Mes=
sa Carriere","","19-10-2024 19:30:36","19-10-2024 18:56:22","19-10-2024 20:=
12:11","","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - L=
oad Breaker","grid outage, site went down because gen failed to start due t=
o disjunction  Cb(40A) of gen // He reamed Cb(40A), site on gen","kamga.vir=
gile@ihstowers.com","2054","19-10-2024 19:30:36","Sagemcom CMR"
"Closed Complete","Site Down","T1328","IHS_YND_247","NOCINC0003362470","Oko=
lo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","19-1=
0-2024 19:26:06","19-10-2024 18:51:45","19-10-2024 19:33:45","site up","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","grid fluctuation  gen fails to start with alarm undervoltage//grid retur=
ned","kamga.virgile@ihstowers.com","2062","19-10-2024 19:26:06","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003362461","Etoudi 2=
","","19-10-2024 19:23:30","19-10-2024 19:14:23","19-10-2024 20:04:23","sit=
e up","Fabrice Pouakam","Fuel Outage (Probable)","Passive","Diesel","Fuel L=
ine Issue","Grid outage,  site went down because Gen failed to start due fu=
el Line blocked by dirty// He dismantled the tank and removed the dirt","sy=
stem","547","19-10-2024 19:23:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003362459","M=
EHANDAN","","19-10-2024 19:22:33","19-10-2024 19:14:23","19-10-2024 21:40:5=
8","","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Gener=
ator Battery","grid outage, site went down because gen failed to start due =
to battery Gen faulty// gen manually started with external battery","kouoh.=
jean@ihstowers.com","492","19-10-2024 19:22:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0003362450","Ngoulmek=
ong-Nord","","19-10-2024 19:19:40","19-10-2024 19:12:44","19-10-2024 22:09:=
44","Cascaded Incident from TTO3240638","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, Site went down be=
cause Gen failed to start due to module huawei disfunction// Grid return","=
system","416","19-10-2024 19:19:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0003362445","E=
leveur","IHS_YND_277","19-10-2024 19:18:56","19-10-2024 19:12:44","19-10-20=
24 22:09:44","site up","Siligap Boris","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage, Site went down because Gen failed =
to start due to module huawei disfunction// Grid return","kouoh.jean@ihstow=
ers.com","373","19-10-2024 19:18:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003362442","Anguissa=
 New","","19-10-2024 19:18:10","19-10-2024 19:06:59","19-10-2024 21:31:59",=
"Cascaded Incident from TTO3240627","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, no space to deploy a =
MDG//Grid return","system","671","19-10-2024 19:18:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003362437","L=
abogenie","IHS_YND_568","19-10-2024 19:17:05","19-10-2024 19:06:59","19-10-=
2024 21:31:59","Grid outage, no space to deploy a MDG//Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, no space to deploy a MDG//Grid return","kouoh.jean@ihstowers.com","607","=
19-10-2024 19:17:05","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0003362435","Sap=
eur Mimboman","","19-10-2024 19:17:02","19-10-2024 18:46:51","19-10-2024 21=
:19:19","Grid outage, site went down because Gen failed to start due to Gen=
 card faulty // grid return","Mba Lazare Herve","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because Ge=
n failed to start due to Gen card faulty // grid return","kamga.virgile@ihs=
towers.com","1812","19-10-2024 19:17:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003362430","M=
aison-Blanche-IHS","","19-10-2024 19:15:47","19-10-2024 19:09:40","19-10-20=
24 21:43:40","grid outage,no space to deploy a mobil gen//grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid out=
age,no space to deploy a mobil gen//grid return","kouoh.jean@ihstowers.com"=
,"368","19-10-2024 19:15:47","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003362428","MIM=
BOMAN LIBERTE","","19-10-2024 19:15:32","19-10-2024 18:46:13","19-10-2024 2=
0:39:28","","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Generator Faulty","grid outage, main gen is faulty//MDG 20 KVA deployed=
","kamga.virgile@ihstowers.com","1760","19-10-2024 19:15:32","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003362423","Bas=
tos Amb Coree","","19-10-2024 19:14:06","19-10-2024 18:46:52","19-10-2024 2=
1:37:52","grid outage, no space to deploy a mobil gen//grid return ","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outag=
e, no space to deploy a mobil gen//grid return ","kamga.virgile@ihstowers.c=
om","1635","19-10-2024 19:14:06","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003362421","Feb=
e Village","","19-10-2024 19:12:47","19-10-2024 18:39:24","19-10-2024 21:52=
:24","Grid Outage site  went down due to PSC3 Faulty//He bypass it and Site=
 is on Gen ","Mboua Thierry","Equipment Repair","Passive","Control Panel","=
ATS-AMF Issue","Grid Outage site  went down due to PSC3 Faulty//He bypass i=
t and Site is on Gen ","kamga.virgile@ihstowers.com","2004","19-10-2024 19:=
12:47","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003362400","San=
ta Barbara Gottam","","19-10-2024 19:08:18","19-10-2024 18:31:28","19-10-20=
24 19:58:28","grid outage, site went down because Gen failed to start due t=
o battery Gen faulty// Gen manually started with external battery","Delor T=
elezing","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery"=
,"grid outage, site went down because Gen failed to start due to battery Ge=
n faulty// Gen manually started with external battery","kamga.virgile@ihsto=
wers.com","2211","19-10-2024 19:08:18","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003362303","NYO=
M FACE MAETUR","","19-10-2024 18:55:41","19-10-2024 18:15:29","19-10-2024 1=
8:16:29","Grid outage, Landlord has forbidden to start the generator due to=
 noise //Grid restored","Fabrice Pouakam","Equipment Repair","Passive","ACD=
G Gen","ACDG - Emergency Stop","Grid outage, Landlord has forbidden to star=
t the generator due to noise //Grid restored","kamga.virgile@ihstowers.com"=
,"35289","19-10-2024 18:55:41","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003362281","Mok=
olo Yaounde","","19-10-2024 18:51:58","19-10-2024 18:29:50","19-10-2024 21:=
40:04","grid outage, no space to deploy a mobil gen// grid return ","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage=
, no space to deploy a mobil gen// grid return ","kamga.virgile@ihstowers.c=
om","1329","19-10-2024 18:51:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003362199","M=
ambine","","19-10-2024 18:29:15","19-10-2024 17:53:04","19-10-2024 18:30:04=
","Grid outage,Site went down because Gen failed to start due to hybrid sys=
tem disfunctionning//Gen manually started","Fanda Brice","Equipment Repair"=
,"Passive","Hybrid","Hybrid Module","Grid outage,Site went down because Gen=
 failed to start due to hybrid system disfunctionning//Gen manually started=
","kouoh.jean@ihstowers.com","2172","19-10-2024 18:29:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003362035","M=
essa-Carriere OCM","","19-10-2024 18:04:33","19-10-2024 17:17:11","19-10-20=
24 20:12:26","ETA=3D20:10","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","grid outage, no space to deploy a mobil gen //grid r=
eturn","kouoh.jean@ihstowers.com","2843","19-10-2024 18:04:33","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003361704","ELOUMDEM=
 CARRIERE 2","","19-10-2024 17:00:51","19-10-2024 16:52:57","19-10-2024 17:=
00:31","Cascaded Incident from TTO3239710","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","   Grid outage ,site went dow=
n before gen start due to poor battery backup  causing by  insufficient of =
rectifiers (08)// Gen started automatically ( waiting added 02 rectifiers)"=
,"system","474","19-10-2024 17:00:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003361703","Eto koss=
 Yde","","19-10-2024 17:00:50","19-10-2024 16:52:57","19-10-2024 17:00:31",=
"Cascaded Incident from TTO3239710","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","   Grid outage ,site went down befor=
e gen start due to poor battery backup  causing by  insufficient of rectifi=
ers (08)// Gen started automatically ( waiting added 02 rectifiers)","syste=
m","473","19-10-2024 17:00:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003361695","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","19-10-2024 16:59:05","19-10-2024 16:52=
:57","19-10-2024 17:00:31","   Grid outage ,site went down before gen start=
 due to poor battery backup  causing by  insufficient of rectifiers (08)// =
Gen started automatically ( waiting added 02 rectifiers)","Fanda Brice","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","  =
 Grid outage ,site went down before gen start due to poor battery backup  c=
ausing by  insufficient of rectifiers (08)// Gen started automatically ( wa=
iting added 02 rectifiers)","kamga.virgile@ihstowers.com","370","19-10-2024=
 16:59:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003361604","N=
omayos-IHS","","19-10-2024 16:42:41","19-10-2024 16:30:28","19-10-2024 16:4=
2:28","site went down because 02/04 rectifiers  dysfuntionning //He reset r=
ectifiers,Site on Gen","Fanda Brice","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","site went down because 02/04 rectifiers  dysfuntionn=
ing //He reset rectifiers,Site on Gen","kouoh.jean@ihstowers.com","733","19=
-10-2024 16:42:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003361470","MEHANDAN=
","","19-10-2024 16:18:50","19-10-2024 16:04:17","19-10-2024 17:02:08","Cas=
caded Incident from TTO3239397","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down due to disjunction Cb(1=
25A) in PWC // He make a bridge with Cb(63A) , site on grid","system","873"=
,"19-10-2024 16:18:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003361440","O=
dza II OCM","IHS_YND_528","19-10-2024 16:14:22","19-10-2024 16:04:17","19-1=
0-2024 17:02:08","site went down due to disjunction Cb(125A) in PWC // He m=
ake a bridge with Cb(63A) , site on grid","Albran Byorel","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site w=
ent down due to disjunction Cb(125A) in PWC // He make a bridge with Cb(63A=
) , site on grid","kouoh.jean@ihstowers.com","606","19-10-2024 16:14:22","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003361298","K=
oweit City","","19-10-2024 15:47:34","19-10-2024 14:47:09","19-10-2024 15:4=
7:09","site down due to lack one rectifier//added 01 rectifier","Albran Byo=
rel","Equipment Repair","Passive","Rectifier","Rectifier Module","site down=
 due to lack one rectifier//added 01 rectifier","kouoh.jean@ihstowers.com",=
"3626","19-10-2024 15:47:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003361167","MBIMBIM"=
,"","19-10-2024 15:22:05","19-10-2024 15:09:52","19-10-2024 15:47:34","Casc=
aded Incident from TTO3239030","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on GEN with U =3D =
54.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","733","19-10-2024 15:22:05","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003361166","Ngouetou=
","","19-10-2024 15:22:05","19-10-2024 15:09:52","19-10-2024 15:47:34","Cas=
caded Incident from TTO3239030","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on GEN with U =3D=
 54.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","733","19-10-2024 15:22:05","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003361164","Matsari"=
,"","19-10-2024 15:22:04","19-10-2024 15:09:52","19-10-2024 15:47:34","Casc=
aded Incident from TTO3239030","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on GEN with U =3D =
54.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","732","19-10-2024 15:22:04","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003361165","Yoko OCM=
","","19-10-2024 15:22:04","19-10-2024 15:09:52","19-10-2024 15:47:34","Cas=
caded Incident from TTO3239030","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on GEN with U =3D=
 54.6V Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959=
647of Huawei is informed","system","732","19-10-2024 15:22:04","Sagemcom CM=
R"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003360715","Ema=
na","","19-10-2024 14:57:09","19-10-2024 14:49:00","19-10-2024 16:09:36","s=
ite up waiting feelback","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage, site went down because gen fai=
l to start(gen card closed)// he started gen manually(investigations ongoin=
g)","kamga.virgile@ihstowers.com","489","19-10-2024 14:57:09","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003360376","T=
ongolo OCM","","19-10-2024 14:43:08","19-10-2024 14:06:52","19-10-2024 15:3=
5:34","site went down due to Eneo contactor faulty // He bypassed Eneo cont=
actor and gen manually started","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","ATS-AMF Issue","site went down due to Eneo contactor fa=
ulty // He bypassed Eneo contactor and gen manually started","kouoh.jean@ih=
stowers.com","2178","19-10-2024 14:43:08","Sagemcom CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0003360203","Aba=
ttoir","","19-10-2024 14:37:51","19-10-2024 14:08:42","19-10-2024 16:02:42"=
,"grid outage,site went down because controller huawei is faulty//he bypass=
ed ,it and started the gen","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","grid outage,site went down because contr=
oller huawei is faulty//he bypassed ,it and started the gen","kamga.virgile=
@ihstowers.com","2775","19-10-2024 14:37:51","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003360172","N=
yanon","","19-10-2024 14:36:40","19-10-2024 14:26:33","20-10-2024 03:00:46"=
,"No power issue site on Gen ubaie=3D55.3V. The TX FME Gr=E9goire  //654547=
479//  from huawei is informed .","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue site on Gen ubaie=3D55.3V. The TX FME Gr=E9goire  //654547479/=
/  from huawei is informed .","kouoh.jean@ihstowers.com","608","19-10-2024 =
14:36:40","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003358930","Mok=
olo Yaounde","","19-10-2024 11:29:20","19-10-2024 11:25:16","19-10-2024 11:=
36:54","Grid outage No space to deploy// Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage No space to d=
eploy// Grid return","emmanuel.ghani@ihstowers.com","245","19-10-2024 11:29=
:20","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0003358925","Sap=
eur","","19-10-2024 11:28:21","19-10-2024 11:25:59","19-10-2024 11:39:15","=
Grid outage, site went down before gen start due to poor battery backup // =
Gen automatically started","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen automatically started","emm=
anuel.ghani@ihstowers.com","142","19-10-2024 11:28:21","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0003358922","Bas=
tos Bethesda","","19-10-2024 11:27:03","19-10-2024 11:25:58","19-10-2024 11=
:36:48","Grid outage, site went down before gen start due to poor battery b=
ackup // Grid power return","Mboua Thierry","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Grid power return","emmanuel.g=
hani@ihstowers.com","67","19-10-2024 11:27:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003358889","A=
hala","","19-10-2024 11:19:46","19-10-2024 11:17:40","19-10-2024 11:20:52",=
"Grid outage site went down because Gen overload (20KVA, 300A) // site stab=
ilized","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Ov=
erload","Grid outage site went down because Gen overload (20KVA, 300A) // s=
ite stabilized","joelle.ekessi@ihstowers.com","127","19-10-2024 11:19:46","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003358609","N=
kozoa","","19-10-2024 10:30:21","19-10-2024 10:29:17","19-10-2024 10:33:37"=
,"Grid fluctuation site went down because Gen faile to started due to Grid =
bad voltage// Grid stabilized","Fabrice Pouakam","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Grid fluctuation site went =
down because Gen faile to started due to Grid bad voltage// Grid stabilized=
","joelle.ekessi@ihstowers.com","65","19-10-2024 10:30:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003358471","A=
kak-Nkozoa-MTN-IHS","","19-10-2024 10:08:25","19-10-2024 10:07:17","19-10-2=
024 10:44:35","Site went down because CB (80*63A) disjunted in The PWC due =
to Grid bad voltage  // He reamed CB","Fabrice Pouakam","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site wen=
t down because CB (80*63A) disjunted in The PWC due to Grid bad voltage  //=
 He reamed CB","joelle.ekessi@ihstowers.com","69","19-10-2024 10:08:25","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003357746","ELOUMDEM=
 CARRIERE","","19-10-2024 08:28:10","19-10-2024 08:22:58","19-10-2024 09:24=
:40","Cascaded Incident from TTO3235106","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen overload (20KVA, 300A) // site stabilized","system","312","19-10-20=
24 08:28:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003357747","MBALNGON=
G LYCEE","","19-10-2024 08:28:10","19-10-2024 08:22:58","19-10-2024 09:24:4=
0","Cascaded Incident from TTO3235106","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage site went down becaus=
e Gen overload (20KVA, 300A) // site stabilized","system","312","19-10-2024=
 08:28:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003357748","Afanoya"=
,"","19-10-2024 08:28:10","19-10-2024 08:22:58","19-10-2024 09:24:40","Casc=
aded Incident from TTO3235106","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 overload (20KVA, 300A) // site stabilized","system","312","19-10-2024 08:2=
8:10","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003357739","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","19-10-2024 08:27:03","19-10-20=
24 08:22:58","19-10-2024 09:24:40","Grid outage site went down because Gen =
overload (20KVA, 300A) // site stabilized","Hyemafo Gildas","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down beca=
use Gen overload (20KVA, 300A) // site stabilized","emmanuel.ghani@ihstower=
s.com","247","19-10-2024 08:27:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003357552","MBALNGON=
G LYCEE","","19-10-2024 07:51:10","19-10-2024 07:49:55","19-10-2024 07:59:3=
3","Cascaded Incident from TTO3234885","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage site went down becaus=
e Gen overload (20KVA, 300A)// site stabilized","system","75","19-10-2024 0=
7:51:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003357553","Afanoya"=
,"","19-10-2024 07:51:10","19-10-2024 07:49:55","19-10-2024 07:59:33","Casc=
aded Incident from TTO3234885","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 overload (20KVA, 300A)// site stabilized","system","75","19-10-2024 07:51:=
10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003357551","ELOUMDEM=
 CARRIERE","","19-10-2024 07:51:10","19-10-2024 07:49:55","19-10-2024 07:59=
:33","Cascaded Incident from TTO3234885","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen overload (20KVA, 300A)// site stabilized","system","75","19-10-2024=
 07:51:10","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003357548","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","19-10-2024 07:50:00","19-10-20=
24 07:49:55","19-10-2024 07:59:33","Grid outage site went down because Gen =
overload (20KVA, 300A)// site stabilized","Hyemafo Gildas","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down becau=
se Gen overload (20KVA, 300A)// site stabilized","emmanuel.ghani@ihstowers.=
com","6","19-10-2024 07:50:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003357545","H=
-Progres","","19-10-2024 07:48:08","19-10-2024 07:45:04","19-10-2024 10:48:=
03","Grid outage No space to deploy // Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid outage No space to dep=
loy // Grid return","joelle.ekessi@ihstowers.com","185","19-10-2024 07:48:0=
8","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003357488","M=
essa-Carriere OCM","","19-10-2024 07:34:49","19-10-2024 07:29:45","19-10-20=
24 07:35:52","No power issue site on grid with U=3D52,3V, FME TX Mohamadou/=
691144435/ from Huawei is informed.	","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with U=3D52,3V, FME TX Mohamadou/691144435/ from Huawei is informed.	=
","joelle.ekessi@ihstowers.com","305","19-10-2024 07:34:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003357315","C=
amp-Sic-Tsinga","","19-10-2024 07:00:01","19-10-2024 06:53:55","19-10-2024 =
10:50:51","Grid outage No space to deploy // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No space =
to deploy // Grid return","joelle.ekessi@ihstowers.com","367","19-10-2024 0=
7:00:01","Sagemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003357311","Bas=
tos Bir","","19-10-2024 06:58:43","19-10-2024 06:51:37","19-10-2024 08:49:5=
6","Grid outage site went down because Gen failed to start due to Gen batte=
ry faulty // he started the Gen with external battery","Mboua Thierry","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage=
 site went down because Gen failed to start due to Gen battery faulty // he=
 started the Gen with external battery","emmanuel.ghani@ihstowers.com","427=
","19-10-2024 06:58:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_012","NOCINC0003356619","Elig-Ess=
ono","","19-10-2024 02:59:41","19-10-2024 02:26:29","19-10-2024 02:27:39","=
Cascaded Incident from TTO3233732","Paul BIBOUM","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue site on grid with U=3D54.=
6V Notice that site is impacted by CBC who is notour responsability","syste=
m","1992","19-10-2024 02:59:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_003","NOCINC0003356618","Mercure"=
,"","19-10-2024 02:59:41","19-10-2024 02:26:29","19-10-2024 02:27:39","Casc=
aded Incident from TTO3233732","","Cascade Outage","Active","Cascade Active=
","Cascade Active","No power issue site on grid with U=3D54.6V Notice that =
site is impacted by CBC who is notour responsability","system","1992","19-1=
0-2024 02:59:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_007","NOCINC0003356617","Montee-A=
nne-Rouge","","19-10-2024 02:59:40","19-10-2024 02:26:29","19-10-2024 02:27=
:39","Cascaded Incident from TTO3233732","","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue site on grid with U=3D54.6V No=
tice that site is impacted by CBC who is notour responsability","system","1=
991","19-10-2024 02:59:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003356579","I=
mm-Olympique","IHS_YND_007, IHS_YND_003, IHS_YND_012","19-10-2024 02:43:51"=
,"19-10-2024 02:26:29","19-10-2024 03:10:39","No power issue site on grid w=
ith U=3D54.6V Notice that site is impacted by CBC who is notour responsabil=
ity","Paul BIBOUM","Customer Equipment Failure","Active","Active Equipment =
Failure","Affected by 3rd Party Site","No power issue site on grid with U=
=3D54.6V Notice that site is impacted by CBC who is notour responsability",=
"olivier.kwedi@ihstowers.com","1043","19-10-2024 02:43:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0003356532","OLAMA","=
","19-10-2024 02:25:21","19-10-2024 02:13:19","19-10-2024 02:15:23","Cascad=
ed Incident from TTO3233665","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on gen with U=3D57v Notice=
 that site is impacted by Ngoumou who is not our responsability","system","=
722","19-10-2024 02:25:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0003356535","Akono","=
","19-10-2024 02:25:21","19-10-2024 02:13:19","19-10-2024 02:15:23","Cascad=
ed Incident from TTO3233665","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on gen with U=3D57v Notice=
 that site is impacted by Ngoumou who is not our responsability","system","=
722","19-10-2024 02:25:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0003356534","Mom","",=
"19-10-2024 02:25:21","19-10-2024 02:13:19","19-10-2024 02:15:23","Cascaded=
 Incident from TTO3233665","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on gen with U=3D57v Notice t=
hat site is impacted by Ngoumou who is not our responsability","system","72=
2","19-10-2024 02:25:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0003356533","OTELE MT=
N","","19-10-2024 02:25:21","19-10-2024 02:13:19","19-10-2024 02:15:23","Ca=
scaded Incident from TTO3233665","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on gen with U=3D57v No=
tice that site is impacted by Ngoumou who is not our responsability","syste=
m","722","19-10-2024 02:25:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0003356523","Minka","=
IHS_YND_687, IHS_YND_531, IHS_YND_370, IHS_YND_365","19-10-2024 02:22:27","=
19-10-2024 02:13:19","19-10-2024 03:10:23","No power issue site on gen with=
 U=3D57v Notice that site is impacted by Ngoumou who is not our responsabil=
ity","Fanda Brice","Customer Equipment Failure","Active","Active Equipment =
Failure","Affected by 3rd Party Site","No power issue site on gen with U=3D=
57v Notice that site is impacted by Ngoumou who is not our responsability",=
"stephane.nkamwa@ihstowers.com","549","19-10-2024 02:22:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_004","NOCINC0003356494","Av Kenne=
dy","","19-10-2024 02:01:48","19-10-2024 01:51:15","19-10-2024 04:18:15","G=
rid outage.no space to deploy mobile gen // grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no space t=
o deploy mobile gen // grid return","stephane.nkamwa@ihstowers.com","634","=
19-10-2024 02:01:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_163","IHS_YND_242","NOCINC0003356247","M=
balla 4","","19-10-2024 01:13:03","19-10-2024 01:07:55","19-10-2024 01:10:0=
0","No power issue site on grid with U=3D54.3v Armand Nguetsa(691144412) Fr=
om Huawei is informed","Delor Telezing","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D54.3v Armand Nguetsa(691144412) From Huawei is informed","oli=
vier.kwedi@ihstowers.com","309","19-10-2024 01:13:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003356106","N=
kolfon Cimencam","","19-10-2024 00:28:32","19-10-2024 00:25:12","19-10-2024=
 03:25:57","No power issue on site U=3D54,5v site on gen Rm Alain (69114442=
3)of huawei is informed","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54,5v site on gen Rm Alain (691144423)of huawei is informed","olivier=
.kwedi@ihstowers.com","200","19-10-2024 00:28:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003356076","c=
hina embassy yde","","19-10-2024 00:19:48","19-10-2024 00:11:40","19-10-202=
4 02:10:08","No power issue site on grid wth U=3D53.3v Eloundou Bertrand(65=
2586578) from Huawei is informed","","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gri=
d wth U=3D53.3v Eloundou Bertrand(652586578) from Huawei is informed","oliv=
ier.kwedi@ihstowers.com","489","19-10-2024 00:19:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003355918","E=
kombitie","","18-10-2024 23:24:37","18-10-2024 22:29:03","19-10-2024 01:15:=
46","No power issue site on grid with U=3D54.6v Symphorien(675295205) from =
Huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gr=
id with U=3D54.6v Symphorien(675295205) from Huawei is informed","olivier.k=
wedi@ihstowers.com","3335","18-10-2024 23:24:37","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003355811","NYO=
M FACE MAETUR","","18-10-2024 22:58:43","18-10-2024 22:57:33","19-10-2024 1=
7:17:52","Access issue due to landlord;Grid outage, Landlord has forbidden =
to start the generator due to noise //Grid restored","Fabrice Pouakam","Acc=
ess Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land=
 Lord","Access issue due to landlord;Grid outage, Landlord has forbidden to=
 start the generator due to noise //Grid restored","stephane.nkamwa@ihstowe=
rs.com","2683","18-10-2024 22:58:43","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003355804","Mok=
olo Yaounde","","18-10-2024 22:54:49","18-10-2024 22:47:42","18-10-2024 23:=
30:52","Grid outage//Grid return ","","Grid Supply","Passive","Grid","Natio=
nal Grid - Grid Outage Issue","Grid outage//Grid return ","stephane.nkamwa@=
ihstowers.com","428","18-10-2024 22:54:49","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0003355784","Mba=
nkolo petit paris","","18-10-2024 22:52:19","18-10-2024 22:46:05","19-10-20=
24 03:50:47","No power issue site on grid with  U=3D54v//site up at 10:53 P=
M Mohamadou from Huawei is informed","Mboua Thierry","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","Affected by 3rd Party Site","No=
 power issue site on grid with  U=3D54v//site up at 10:53 PM Mohamadou from=
 Huawei is informed","stephane.nkamwa@ihstowers.com","374","18-10-2024 22:5=
2:19","Sagemcom CMR"
"Cancelled","Warning","T0566","IHS_YND_421","NOCINC0003355774","Bot Makak",=
"","18-10-2024 22:49:48","","","","","","","","","","stephane.nkamwa@ihstow=
ers.com","1631","18-10-2024 22:49:48","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003355735","NYO=
M 2 IHS","","18-10-2024 22:45:27","18-10-2024 22:23:58","18-10-2024 22:30:1=
9","N o power issue site on grid with U=3D54v //site up at 10:38 PM Symphor=
ien(675295205) from Huawei is informed ","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N o =
power issue site on grid with U=3D54v //site up at 10:38 PM Symphorien(6752=
95205) from Huawei is informed ","stephane.nkamwa@ihstowers.com","21367","1=
8-10-2024 22:45:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003355470","Afanoya"=
,"","18-10-2024 21:56:21","18-10-2024 21:30:32","18-10-2024 21:50:32","Casc=
aded Incident from TTO3232433","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site was on gen due to grid outage,sit=
e went down due to gen overload (20Kva, 300A) // site stabilized","system",=
"1549","18-10-2024 21:56:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003355469","MBALNGON=
G LYCEE","","18-10-2024 21:56:21","18-10-2024 21:30:32","18-10-2024 21:50:3=
2","Cascaded Incident from TTO3232433","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site was on gen due to grid outag=
e,site went down due to gen overload (20Kva, 300A) // site stabilized","sys=
tem","1549","18-10-2024 21:56:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003355468","ELOUMDEM=
 CARRIERE","","18-10-2024 21:56:20","18-10-2024 21:30:32","18-10-2024 21:50=
:32","Cascaded Incident from TTO3232433","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site was on gen due to grid out=
age,site went down due to gen overload (20Kva, 300A) // site stabilized","s=
ystem","1548","18-10-2024 21:56:20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003355457","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","18-10-2024 21:54:41","18-10-20=
24 21:30:32","18-10-2024 21:50:32","site was on gen due to grid outage,site=
 went down due to gen overload (20Kva, 300A) // site stabilized","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","site was =
on gen due to grid outage,site went down due to gen overload (20Kva, 300A) =
// site stabilized","kamga.virgile@ihstowers.com","1450","18-10-2024 21:54:=
41","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003354963","MBI=
MBIM","","18-10-2024 20:35:09","18-10-2024 20:16:57","18-10-2024 20:46:57",=
"Grid outage site went down because Gen started and stopped due to the fuel=
 and water mixture in the tank // He purged the tank","Parker Tchoup","Fuel=
 Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The F=
uel","Grid outage site went down because Gen started and stopped due to the=
 fuel and water mixture in the tank // He purged the tank","kamga.virgile@i=
hstowers.com","1093","18-10-2024 20:35:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003354817","ELOUMDEM=
 CARRIERE 2","","18-10-2024 20:07:20","18-10-2024 19:51:01","18-10-2024 20:=
42:01","Cascaded Incident from TTO3231654","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down be=
cause Gen stopped due to diesel filter cartridge does not let fuel through/=
/ Grid power return (investigation ongoing)","system","979","18-10-2024 20:=
07:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003354816","Eto koss=
 Yde","","18-10-2024 20:07:20","18-10-2024 19:51:01","18-10-2024 20:42:01",=
"Cascaded Incident from TTO3231654","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en stopped due to diesel filter cartridge does not let fuel through// Grid =
power return (investigation ongoing)","system","979","18-10-2024 20:07:20",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003354794","Afanoya"=
,"","18-10-2024 20:02:41","18-10-2024 19:52:14","18-10-2024 20:12:14","Casc=
aded Incident from TTO3231634","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site was on gen due to grid outage,sit=
e went down due to gen overload (20Kva, 300A) // He reduced the load and st=
arted Gen manually.","system","627","18-10-2024 20:02:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003354793","MBALNGON=
G LYCEE","","18-10-2024 20:02:41","18-10-2024 19:52:14","18-10-2024 20:12:1=
4","Cascaded Incident from TTO3231634","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site was on gen due to grid outag=
e,site went down due to gen overload (20Kva, 300A) // He reduced the load a=
nd started Gen manually.","system","627","18-10-2024 20:02:41","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003354792","ELOUMDEM=
 CARRIERE","","18-10-2024 20:02:40","18-10-2024 19:52:14","18-10-2024 20:12=
:14","Cascaded Incident from TTO3231634","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site was on gen due to grid out=
age,site went down due to gen overload (20Kva, 300A) // He reduced the load=
 and started Gen manually.","system","626","18-10-2024 20:02:40","Sagemcom =
CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003354784","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","18-10-2024 20:00:34","18-10-20=
24 19:52:14","18-10-2024 20:12:14","site was on gen due to grid outage,site=
 went down due to gen overload (20Kva, 300A) // He reduced the load and sta=
rted Gen manually.","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","site was on gen due to grid outage,site went down due =
to gen overload (20Kva, 300A) // He reduced the load and started Gen manual=
ly.","kamga.virgile@ihstowers.com","501","18-10-2024 20:00:34","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003354779","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","18-10-2024 19:59:05","18-10-2024 19:=
51:01","18-10-2024 20:42:01","Grid outage site went down because Gen stoppe=
d due to diesel filter cartridge does not let fuel through// Grid power ret=
urn (investigation ongoing)","Fanda Brice","Fuel Outage (Probable)","Passiv=
e","ACDG Gen","ACDG - Fuel Pump","Grid outage site went down because Gen st=
opped due to diesel filter cartridge does not let fuel through// Grid power=
 return (investigation ongoing)","alexandre.kamal@ihstowers.com","485","18-=
10-2024 19:59:05","Sagemcom CMR"
"Cancelled","Warning","CTR_042","IHS_YND_175","NOCINC0003354773","Nkomo",""=
,"18-10-2024 19:57:17","","","","Mba Lazare Herve","","","","","","alexandr=
e.kamal@ihstowers.com","368","18-10-2024 19:57:17","Sagemcom CMR"
"Closed Complete","Warning","CTR_315","IHS_YND_292","NOCINC0003354742","Bit=
oto","","18-10-2024 19:49:28","","","Site alarming on battery due to insuff=
icient of rectifier(05 on site)// He added 02 rectifiers and site stabilize=
d","Mba Lazare Herve","Warning","Warning","POWER","Warning - Site on Batter=
y","Site alarming on battery due to insufficient of rectifier(05 on site)//=
 He added 02 rectifiers and site stabilized","alexandre.kamal@ihstowers.com=
","5","18-10-2024 19:49:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0003354686","S=
imbock OCM","","18-10-2024 19:38:13","18-10-2024 19:34:50","18-10-2024 19:4=
0:50","Grid fluctuation, site went down because gen fails to start due to g=
rid bad voltage // he bypass grid and manually start the gen","Hyemafo Gild=
as","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because gen fails to start due to grid =
bad voltage // he bypass grid and manually start the gen","alexandre.kamal@=
ihstowers.com","203","18-10-2024 19:38:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003354683","Nsimalen=
 OCM","","18-10-2024 19:37:20","18-10-2024 19:28:14","18-10-2024 20:31:14",=
"Cascaded Incident from TTO3231481","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,DG started and stopped=
 with alarm 'overcurrent' due to //  he reset gen card and manually started=
","system","546","18-10-2024 19:37:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003354663","N=
kolda","IHS_YND_327","18-10-2024 19:34:22","18-10-2024 19:28:14","18-10-202=
4 20:31:14","Grid outage,DG started and stopped with alarm 'overcurrent' du=
e to //  he reset gen card and manually started","Albran Byorel","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,DG starte=
d and stopped with alarm 'overcurrent' due to //  he reset gen card and man=
ually started","alexandre.kamal@ihstowers.com","369","18-10-2024 19:34:22",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003354623","MEHANDAN=
","","18-10-2024 19:23:10","18-10-2024 19:15:45","18-10-2024 21:06:45","Cas=
caded Incident from TTO3231416","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because CB (125A) disju=
nted in The PWC because the Load Increase // He reamed CB and site is on Gr=
id","system","445","18-10-2024 19:23:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003354614","O=
dza II OCM","IHS_YND_528","18-10-2024 19:21:49","18-10-2024 19:15:45","18-1=
0-2024 21:06:45","Site went down because CB (125A) disjunted in The PWC bec=
ause the Load Increase // He reamed CB and site is on Grid","Albran Byorel"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Brea=
ker Issue","Site went down because CB (125A) disjunted in The PWC because t=
he Load Increase // He reamed CB and site is on Grid","alexandre.kamal@ihst=
owers.com","365","18-10-2024 19:21:49","Sagemcom CMR"
"Closed Complete","Site Down","T3206","IHS_YND_759","NOCINC0003354454","Nko=
lfoulou Tsinga Village","","18-10-2024 18:51:37","18-10-2024 18:20:19","18-=
10-2024 18:58:19","Grid outage, site went down because gen fails to start d=
ue to  card disfunction // he resert it and manually start the gen","Siliga=
p Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gr=
id outage, site went down because gen fails to start due to  card disfuncti=
on // he resert it and manually start the gen","kamga.virgile@ihstowers.com=
","1878","18-10-2024 18:51:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003353862","ELOUMDEM=
 CARRIERE","","18-10-2024 17:07:41","18-10-2024 16:57:26","18-10-2024 17:05=
:26","Cascaded Incident from TTO3230513","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site was on gen due to grid out=
age, site went down due to gen overload (20Kva, 300A) // He reduced the loa=
d and started Gen manually.","system","615","18-10-2024 17:07:41","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003353864","Afanoya"=
,"","18-10-2024 17:07:41","18-10-2024 16:57:26","18-10-2024 17:05:26","Casc=
aded Incident from TTO3230513","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site was on gen due to grid outage, si=
te went down due to gen overload (20Kva, 300A) // He reduced the load and s=
tarted Gen manually.","system","615","18-10-2024 17:07:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003353863","MBALNGON=
G LYCEE","","18-10-2024 17:07:41","18-10-2024 16:57:26","18-10-2024 17:05:2=
6","Cascaded Incident from TTO3230513","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site was on gen due to grid outag=
e, site went down due to gen overload (20Kva, 300A) // He reduced the load =
and started Gen manually.","system","615","18-10-2024 17:07:41","Sagemcom C=
MR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003353850","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","18-10-2024 17:06:02","18-10-20=
24 16:57:26","18-10-2024 17:05:26","Site was on gen due to grid outage, sit=
e went down due to gen overload (20Kva, 300A) // He reduced the load and st=
arted Gen manually.","Hyemafo Gildas","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","Site was on gen due to grid outage, site went down du=
e to gen overload (20Kva, 300A) // He reduced the load and started Gen manu=
ally.","kamga.virgile@ihstowers.com","518","18-10-2024 17:06:02","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003353526","Afanoya"=
,"","18-10-2024 16:23:01","18-10-2024 16:00:04","18-10-2024 16:37:04","Casc=
aded Incident from TTO3230120","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage, gen start and stopped wit=
h alarm 'Hight temp' // He added water and manually start the gen","system"=
,"1377","18-10-2024 16:23:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003353524","ELOUMDEM=
 CARRIERE","","18-10-2024 16:23:00","18-10-2024 16:00:04","18-10-2024 16:37=
:04","Cascaded Incident from TTO3230120","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, gen start and stop=
ped with alarm 'Hight temp' // He added water and manually start the gen","=
system","1376","18-10-2024 16:23:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003353525","MBALNGON=
G LYCEE","","18-10-2024 16:23:00","18-10-2024 16:00:04","18-10-2024 16:37:0=
4","Cascaded Incident from TTO3230120","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, gen start and stoppe=
d with alarm 'Hight temp' // He added water and manually start the gen","sy=
stem","1376","18-10-2024 16:23:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003353430","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","18-10-2024 16:09:08","18-10-=
2024 16:00:04","18-10-2024 16:37:04","grid outage, site went down because g=
en start and stopped with alarm 'Hight temp' // He added water and manually=
 start the gen","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","A=
CDG - High Engine Temp - Coolant Level Issue","grid outage, site went down =
because gen start and stopped with alarm 'Hight temp' // He added water and=
 manually start the gen","alexandre.kamal@ihstowers.com","545","18-10-2024 =
16:09:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0003353047","M=
om","","18-10-2024 15:15:57","18-10-2024 15:07:53","18-10-2024 15:15:53","s=
ite went down due to work Brice fanda/657108549/SAGEMCOM :do the PM//End of=
 work","Fanda Brice","Installation Activity","Passive","Planned Activity","=
Installation Activity","site went down due to work Brice fanda/657108549/SA=
GEMCOM :do the PM//End of work","alexandre.kamal@ihstowers.com","486","18-1=
0-2024 15:15:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003352959","M=
ANGUIERS CHAPELLE","","18-10-2024 15:04:59","18-10-2024 14:55:59","18-10-20=
24 15:11:59","Grid outage,site went down before DG start  due to Poor Batte=
ries Backup // DG started automatically.","Fabrice Pouakam","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,si=
te went down before DG start  due to Poor Batteries Backup // DG started au=
tomatically.","alexandre.kamal@ihstowers.com","541","18-10-2024 15:04:59","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003352956","S=
atcom","","18-10-2024 15:04:05","18-10-2024 14:54:53","18-10-2024 15:00:53"=
,"ACTIVE No power issue on site, site on Gen with Ubaie=3D52,1V Tx fme Arma=
nd Ngeuts/699949553/ from Huawei is Informed","Delor Telezing","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE No power issue on site, site on Gen with Ubaie=3D52,1V Tx fme Armand=
 Ngeuts/699949553/ from Huawei is Informed","alexandre.kamal@ihstowers.com"=
,"553","18-10-2024 15:04:05","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003352949","Bas=
tos Amb Coree","","18-10-2024 15:02:50","18-10-2024 14:55:30","18-10-2024 1=
5:05:53","grid outage, No space to deploy a mobil gen // grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outa=
ge, No space to deploy a mobil gen // grid return","kamga.virgile@ihstowers=
.com","442","18-10-2024 15:02:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003352774","M=
essa-Carriere OCM","","18-10-2024 14:36:24","18-10-2024 13:41:11","18-10-20=
24 13:45:11","No power issue site on grid with U=3D52,1V, FME TX Mohamadou/=
691144435/ from Huawei is informed.	","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on=
 grid with U=3D52,1V, FME TX Mohamadou/691144435/ from Huawei is informed.	=
","alexandre.kamal@ihstowers.com","3314","18-10-2024 14:36:24","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_234","IHS_YND_415","NOCINC0003352336","B=
oga-Mahole","","18-10-2024 13:31:07","18-10-2024 13:11:56","18-10-2024 13:5=
8:13","Active//No power issue site on Grid with U=3D53,6V  The Tx Fme Lucie=
n// 697391563 from Huawei is informed","Kemeni Franklin","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue site on Grid with U=3D53,6V  The Tx Fme Lucien// 697391563=
 from Huawei is informed","kouoh.jean@ihstowers.com","1152","18-10-2024 13:=
31:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0003351487","T=
alla Monatele","","18-10-2024 12:41:29","18-10-2024 12:26:23","18-10-2024 1=
2:43:14","Tx Issue : Site on Grid,Ubaie:54.4; Gr=E9goire HUAWEI /654-54-74-=
79 is informed.","Parker Tchoup","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Tx Issue : Site on Grid,Ubaie:=
54.4; Gr=E9goire HUAWEI /654-54-74-79 is informed.","kouoh.jean@ihstowers.c=
om","907","18-10-2024 12:41:29","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0003351052","Obo=
bogo","","18-10-2024 12:17:10","18-10-2024 12:09:06","18-10-2024 12:17:46",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Gen start automatically","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re Gen start due to poor battery backup // Gen start automatically","landry=
.etame@ihstowers.com","485","18-10-2024 12:17:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003351042","O=
dza II","","18-10-2024 12:16:27","18-10-2024 12:02:08","18-10-2024 12:46:16=
","No power issue on site U=3D51,3v site on grid lionel steeve 655184876 of=
 huawei is informed","Albran Byorel","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D51,3v site on grid lionel steeve 655184876 of huawei is informed","kouoh=
.jean@ihstowers.com","861","18-10-2024 12:16:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003349892","MBALNGON=
G LYCEE","","18-10-2024 11:35:51","18-10-2024 11:12:23","18-10-2024 13:21:3=
0","Cascaded Incident from TTO3225668","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site on DG due to grid outage,DG =
stopped due to High Temp //He added water and manually start of DG.","syste=
m","1408","18-10-2024 11:35:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003349893","Afanoya"=
,"","18-10-2024 11:35:51","18-10-2024 11:12:23","18-10-2024 13:21:30","Casc=
aded Incident from TTO3225668","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site on DG due to grid outage,DG stopp=
ed due to High Temp //He added water and manually start of DG.","system","1=
408","18-10-2024 11:35:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003349891","ELOUMDEM=
 CARRIERE","","18-10-2024 11:35:50","18-10-2024 11:12:23","18-10-2024 13:21=
:30","Cascaded Incident from TTO3225668","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site on DG due to grid outage,D=
G stopped due to High Temp //He added water and manually start of DG.","sys=
tem","1407","18-10-2024 11:35:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003349358","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","18-10-2024 11:21:32","18-10-=
2024 11:12:23","18-10-2024 13:21:30","Site on DG due to grid outage,DG stop=
ped due to High Temp //He added water and manually start of DG.","Hyemafo G=
ildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Site on DG due to grid outage,DG stopped due to High T=
emp //He added water and manually start of DG.","kouoh.jean@ihstowers.com",=
"550","18-10-2024 11:21:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003349096","M=
essa-Carriere OCM","","18-10-2024 10:42:19","18-10-2024 10:24:09","18-10-20=
24 12:21:46","No power issue site on grid with U=3D52,1V, FME TX Mohamadou/=
691144435/ from Huawei is informed.","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D52,1V, FME TX Mohamadou/691144435/ from Huawei is informed.",=
"kouoh.jean@ihstowers.com","1091","18-10-2024 10:42:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003348622","Ebeba","=
","18-10-2024 09:48:21","18-10-2024 09:30:27","18-10-2024 09:44:22","Cascad=
ed Incident from TTO3224685","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid bad voltage,DG started and stopped due=
 to grid fluctuation//Bypass Grid and manually start of DG.","system","1074=
","18-10-2024 09:48:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003348624","Nkongtoc=
k","","18-10-2024 09:48:21","18-10-2024 09:30:27","18-10-2024 09:44:22","Ca=
scaded Incident from TTO3224685","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid bad voltage,DG started and sto=
pped due to grid fluctuation//Bypass Grid and manually start of DG.","syste=
m","1074","18-10-2024 09:48:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0003348621","Lobo 2",=
"","18-10-2024 09:48:20","18-10-2024 09:30:27","18-10-2024 09:44:22","Casca=
ded Incident from TTO3224685","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid bad voltage,DG started a=
nd stopped due to grid fluctuation//Bypass Grid and manually start of DG.",=
"system","1073","18-10-2024 09:48:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0003348576","Mom","",=
"18-10-2024 09:42:02","18-10-2024 09:30:27","18-10-2024 09:44:22","Cascaded=
 Incident from TTO3224685","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid bad voltage,DG started and stopped due t=
o grid fluctuation//Bypass Grid and manually start of DG.","system","695","=
18-10-2024 09:42:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_365","NOCINC0003348577","Akono","=
","18-10-2024 09:42:02","18-10-2024 09:30:27","18-10-2024 09:44:22","Cascad=
ed Incident from TTO3224685","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid bad voltage,DG started and stopped due=
 to grid fluctuation//Bypass Grid and manually start of DG.","system","695"=
,"18-10-2024 09:42:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0003348572","OTELE MT=
N","","18-10-2024 09:42:01","18-10-2024 09:30:27","18-10-2024 09:44:22","Ca=
scaded Incident from TTO3224685","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid bad voltage,DG started and stopped=
 due to grid fluctuation//Bypass Grid and manually start of DG.","system","=
694","18-10-2024 09:42:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0003348574","Minka","=
","18-10-2024 09:42:01","18-10-2024 09:30:27","18-10-2024 09:44:22","Cascad=
ed Incident from TTO3224685","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid bad voltage,DG started and stopped due=
 to grid fluctuation//Bypass Grid and manually start of DG.","system","694"=
,"18-10-2024 09:42:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0003348573","Angongo"=
,"","18-10-2024 09:42:01","18-10-2024 09:30:27","18-10-2024 09:44:22","Casc=
aded Incident from TTO3224685","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid bad voltage,DG started and stopped d=
ue to grid fluctuation//Bypass Grid and manually start of DG.","system","69=
4","18-10-2024 09:42:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0003348569","OKOA Pea=
ge","","18-10-2024 09:42:00","18-10-2024 09:30:27","18-10-2024 09:44:22","C=
ascaded Incident from TTO3224685","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid bad voltage,DG started and stoppe=
d due to grid fluctuation//Bypass Grid and manually start of DG.","system",=
"693","18-10-2024 09:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0003348570","OLAMA","=
","18-10-2024 09:42:00","18-10-2024 09:30:27","18-10-2024 09:44:22","Cascad=
ed Incident from TTO3224685","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid bad voltage,DG started and stopped due=
 to grid fluctuation//Bypass Grid and manually start of DG.","system","693"=
,"18-10-2024 09:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_706","NOCINC0003348571","Mbankomo=
 CAF","","18-10-2024 09:42:00","18-10-2024 09:30:27","18-10-2024 09:44:22",=
"Cascaded Incident from TTO3224685","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid bad voltage,DG started and stop=
ped due to grid fluctuation//Bypass Grid and manually start of DG.","system=
","693","18-10-2024 09:42:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003348519","S=
ous Prefecture","IHS_YND_330, IHS_YND_687, IHS_YND_783, IHS_YND_339, IHS_YN=
D_706, IHS_YND_531, IHS_EDA_101, IHS_YND_335, IHS_YND_371, IHS_YND_349, IHS=
_YND_345, IHS_YND_370, IHS_YND_365","18-10-2024 09:33:01","18-10-2024 09:25=
:47","18-10-2024 09:47:05","Grid bad voltage,DG started and stopped due to =
fluctuation of grid bad voltage, //Bypass Grid and manually start of DG.","=
Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid bad voltage,DG started and stopped due to grid fluctuation=
//Bypass Grid and manually start of DG.","kouoh.jean@ihstowers.com","435","=
18-10-2024 09:33:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003347638","Afanoya"=
,"","18-10-2024 06:36:21","18-10-2024 06:30:19","18-10-2024 06:53:46","Casc=
aded Incident from TTO3223598","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site went down before DG s=
tart : Poor Batteries Backup//DG started automatically.","system","362","18=
-10-2024 06:36:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003347637","MBALNGON=
G LYCEE","","18-10-2024 06:36:21","18-10-2024 06:30:19","18-10-2024 06:53:4=
6","Cascaded Incident from TTO3223598","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down before=
 DG start : Poor Batteries Backup//DG started automatically.","system","362=
","18-10-2024 06:36:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003347636","ELOUMDEM=
 CARRIERE","","18-10-2024 06:36:20","18-10-2024 06:30:19","18-10-2024 06:53=
:46","Cascaded Incident from TTO3223598","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage,site went down befo=
re DG start : Poor Batteries Backup//DG started automatically.","system","3=
61","18-10-2024 06:36:20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003347633","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","18-10-2024 06:35:23","18-10-20=
24 06:30:19","18-10-2024 06:53:46","Grid outage,site went down before DG st=
art : Poor Batteries Backup//DG started automatically.","Hyemafo Gildas","E=
quipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","G=
rid outage,site went down before DG start : Poor Batteries Backup//DG start=
ed automatically.","landry.etame@ihstowers.com","305","18-10-2024 06:35:23"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003347629","Tsi=
nga","","18-10-2024 06:34:20","18-10-2024 06:26:15","18-10-2024 06:48:57","=
Grid outage,site went down before DG start : Poor Batteries Backup//Grid Re=
stored.","Mboua Thierry","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage,site went down before DG start : Poor=
 Batteries Backup//Grid Restored.","landry.etame@ihstowers.com","486","18-1=
0-2024 06:34:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003347571","Ndogbess=
ol","","18-10-2024 06:15:01","18-10-2024 05:47:11","18-10-2024 06:10:05","C=
ascaded Incident from TTO3223516","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site on grid,but did not feed the =
site because grid contactor went faulty //Grid contactor blocked ,site on G=
rid.","system","1670","18-10-2024 06:15:01","Sagemcom CMR"
"Closed Complete","Site Down","T0139","IHS_YND_381","NOCINC0003347488","Bou=
mnyebel","IHS_EDA_056","18-10-2024 05:56:42","18-10-2024 05:47:11","18-10-2=
024 06:10:05","Site on grid,but did not feed the site because grid contacto=
r went faulty //Grid contactor blocked ,site on Grid.","Kemeni Franklin","E=
quipment Repair","Passive","Control Panel","ATS-AMF Issue","Site on grid,bu=
t did not feed the site because grid contactor went faulty //Grid contactor=
 blocked ,site on Grid.","denis.mballa@ihstowers.com","1631","18-10-2024 05=
:56:42","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0003347445","AKA=
K Nkozoa","","18-10-2024 05:39:14","18-10-2024 05:08:52","18-10-2024 07:34:=
31","grid outage,gen ran till fuel shortage//Refueling done","Fabrice Pouak=
am","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran t=
ill fuel shortage//Refueling done","denis.mballa@ihstowers.com","1823","18-=
10-2024 05:39:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003347424","M=
fou EPC","","18-10-2024 05:32:32","18-10-2024 05:24:27","18-10-2024 06:41:3=
7","Site on DG due to grid outage,Site went down due to fuel leak due to fu=
el pipe pierced//He clogged fuel pipe,site on DG.","Mba Lazare Herve","Fuel=
 Outage (Probable)","Passive","Diesel","Fuel Line Issue","Site on DG due to=
 grid outage,Site went down due to fuel leak due to fuel pipe pierced//He c=
logged fuel pipe,site on DG.","ange.kongo@ihstowers.com","487","18-10-2024 =
05:32:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003347420","N=
kolfon Cimencam","","18-10-2024 05:31:41","18-10-2024 04:35:08","18-10-2024=
 04:38:08","No power issue on site U=3D54,5v site on gen Rm Alain 691144423=
 of huawei is informed ","Hyemafo Gildas","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54,5v site on gen Rm Alain 691144423 of huawei is informed ","ange.ko=
ngo@ihstowers.com","3394","18-10-2024 05:31:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_082","NOCINC0003346863","Mokolo Y=
aounde","","18-10-2024 01:49:00","18-10-2024 01:43:00","18-10-2024 01:49:27=
","Cascaded Incident from TTO3222658","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Grid outage, site went down before gen start =
due to poor battery backup // Gen start automaticaly ","system","360","18-1=
0-2024 01:49:00","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0003346860","Bas=
tos Bethesda","IHS_YND_082","18-10-2024 01:48:12","18-10-2024 01:43:00","18=
-10-2024 01:49:27","Grid outage, site went down before gen start due to poo=
r battery backup // Gen start automaticaly ","Mboua Thierry","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
site went down before gen start due to poor battery backup // Gen start aut=
omaticaly ","denis.mballa@ihstowers.com","313","18-10-2024 01:48:12","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_632","IHS_YND_721","NOCINC0003346455","V=
OIRIE MUNICIPALE YAOUNDE","","17-10-2024 23:20:43","17-10-2024 23:16:35","1=
8-10-2024 02:55:48","Incorretly Logged Tickets","Paul BIBOUM","Incorrectly =
Logged Tickets","Error","Error","Error","Incorretly Logged Tickets","ange.k=
ongo@ihstowers.com","248","17-10-2024 23:20:43","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003346288","ODZ=
A CITE MBIA","","17-10-2024 22:44:22","17-10-2024 22:40:11","18-10-2024 03:=
56:38","acces issue during the Night due to landlord;grid outage,gen failed=
 to start due to ATS disfunctionning//Grid return","Albran Byorel","Access =
Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lor=
d","acces issue during the Night due to landlord;grid outage,gen failed to =
start due to ATS disfunctionning//Grid return","denis.mballa@ihstowers.com"=
,"252","17-10-2024 22:44:22","Sagemcom CMR"
"Cancelled","Warning","CTR_166","IHS_YND_434","NOCINC0003345946","Donga",""=
,"17-10-2024 21:28:26","","","","Parker Tchoup","","","","","","olivier.kwe=
di@ihstowers.com","2472","17-10-2024 21:28:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003345791","N=
gouetou","","17-10-2024 21:04:11","17-10-2024 20:47:01","17-10-2024 21:21:2=
2","No power issue on site ,site on Gen with Ubaie=3D53V, Tx Fme Gregoire( =
652070658)From Huawei is informed","Parker Tchoup","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site ,site on Gen with Ubaie=3D53V, Tx Fme Gregoire( 652070658)From H=
uawei is informed","olivier.kwedi@ihstowers.com","1031","17-10-2024 21:04:1=
1","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003345554","Tsi=
nga","","17-10-2024 20:35:36","17-10-2024 20:22:26","17-10-2024 22:56:43","=
Site went down due to Cable and CB burt in the DC-BOX// He Normalized The P=
ower Cable and Replaced The CB   ","Mboua Thierry","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went dow=
n due to Cable and CB burt in the DC-BOX// He Normalized The Power Cable an=
d Replaced The CB   ","olivier.kwedi@ihstowers.com","791","17-10-2024 20:35=
:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003345293","N=
omayos-IHS","","17-10-2024 19:47:31","17-10-2024 19:42:14","17-10-2024 20:0=
8:14","site went down because all rectifiers 2/4 disfonctionning//He reset =
rectiifiers ,Site on Grid","Fanda Brice","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","site went down because all rectifiers 2/4 disfon=
ctionning//He reset rectiifiers ,Site on Grid","olivier.kwedi@ihstowers.com=
","318","17-10-2024 19:47:31","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003345253","N=
yanon","","17-10-2024 19:45:36","17-10-2024 19:31:16","17-10-2024 19:40:16"=
,"No power issue site on Gen ubaie=3D55.3V. The TX FME Gr=E9goire  //654547=
479//  from huawei is informed .","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue site on Gen ubaie=3D55.3V. The TX FME Gr=E9goire  //654547479/=
/  from huawei is informed .","olivier.kwedi@ihstowers.com","861","17-10-20=
24 19:45:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003343992","S=
ous Prefecture","","17-10-2024 16:46:34","17-10-2024 16:33:21","17-10-2024 =
19:35:21","Active//No power isssue, site is on Gen with Ubaie=3D54,2V,  TX =
FME PATRICK (672390202) from Huawei is informed","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power isssue, site is on Gen with Ubaie=3D54,2V,  TX FME PATRICK=
 (672390202) from Huawei is informed","olivier.kwedi@ihstowers.com","794","=
17-10-2024 16:46:34","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003343973","Nko=
g-Edzen","","17-10-2024 16:41:44","17-10-2024 16:33:38","17-10-2024 17:10:0=
8","No power issue on site with  Ubaie=3D52.4V site on Gen (start threshold=
 ubai=3D50 V The Tx Fme Gregoire( 652070658)from Huawei is informed","Parke=
r Tchoup","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue on site with  Ubaie=3D52.4V site on Ge=
n (start threshold ubai=3D50 V The Tx Fme Gregoire( 652070658)from Huawei i=
s informed","olivier.kwedi@ihstowers.com","487","17-10-2024 16:41:44","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0003343869","E=
seka Town","","17-10-2024 16:30:42","17-10-2024 16:04:34","17-10-2024 16:30=
:34","no power issue Ubaie=3D53.4V;  site on Grid Tx FME Etienne 695033981 =
 from Huawei is informed","Kemeni Franklin","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","no power issue Ubai=
e=3D53.4V;  site on Grid Tx FME Etienne 695033981  from Huawei is informed"=
,"olivier.kwedi@ihstowers.com","1569","17-10-2024 16:30:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003343392","Afanoya"=
,"","17-10-2024 15:15:21","17-10-2024 14:17:41","17-10-2024 15:41:41","Casc=
aded Incident from TTO3218538","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, DG Failed to start due to=
 overload (20Kva, 300A),and poor batteries backup // He reduced the load an=
d started Gen manually.","system","3460","17-10-2024 15:15:21","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003343390","ELOUMDEM=
 CARRIERE","","17-10-2024 15:15:20","17-10-2024 14:17:41","17-10-2024 15:41=
:41","Cascaded Incident from TTO3218538","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start=
 due to overload (20Kva, 300A),and poor batteries backup // He reduced the =
load and started Gen manually.","system","3459","17-10-2024 15:15:20","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003343391","MBALNGON=
G LYCEE","","17-10-2024 15:15:20","17-10-2024 14:17:41","17-10-2024 15:41:4=
1","Cascaded Incident from TTO3218538","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start d=
ue to overload (20Kva, 300A),and poor batteries backup // He reduced the lo=
ad and started Gen manually.","system","3459","17-10-2024 15:15:20","Sagemc=
om CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003343371","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","17-10-2024 15:13:52","17-10-20=
24 14:17:41","17-10-2024 15:41:41","Grid outage, DG Failed to start due to =
overload (20Kva, 300A),and poor batteries backup // He reduced the load and=
 started Gen manually.","Hyemafo Gildas","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Grid outage, DG Failed to start due to overload (2=
0Kva, 300A),and poor batteries backup // He reduced the load and started Ge=
n manually.","olivier.kwedi@ihstowers.com","3372","17-10-2024 15:13:52","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003341989","M=
essa-Carriere OCM","","17-10-2024 11:44:24","17-10-2024 11:39:15","17-10-20=
24 11:45:09","No power issue site on grid with U=3D52,1V, FME TX Mohamadou/=
691144435/ from Huawei is informed.","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D52,1V, FME TX Mohamadou/691144435/ from Huawei is informed.",=
"stephane.nkamwa@ihstowers.com","310","17-10-2024 11:44:24","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003341285","NYO=
M FACE MAETUR","","17-10-2024 10:22:32","17-10-2024 10:14:27","17-10-2024 1=
2:27:48","Grid outage, Landlord has forbidden to start the generator due to=
 noise //Grid restored","Fabrice Pouakam","Access Denial","Lease Or Legal",=
"Landlord Related Issues","Access Issue - Land Lord","Grid outage, Landlord=
 has forbidden to start the generator due to noise //Grid restored","kamga.=
virgile@ihstowers.com","486","17-10-2024 10:22:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003340953","N=
GONA","","17-10-2024 09:36:15","17-10-2024 09:29:09","17-10-2024 09:37:04",=
"No power issue, site is on grid with Ubaie=3D56V, Lionel adjep(655184876) =
from Huawei is informed and Up at 09:37 AM","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue, site is on grid with Ubaie=3D56V, Lionel adjep(655184876) f=
rom Huawei is informed and Up at 09:37 AM","stephane.nkamwa@ihstowers.com",=
"427","17-10-2024 09:36:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003340901","MBIMBIM"=
,"","17-10-2024 09:28:51","17-10-2024 09:16:55","17-10-2024 09:20:37","Casc=
aded Incident from TTO3215753","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site ,site on Gen with U=
baie=3D53V, Tx Fme Gregoire( 652070658)From Huawei is informed and reported=
 that site is impacted by Doume centre","system","716","17-10-2024 09:28:51=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003340900","Ngouetou=
","","17-10-2024 09:28:51","17-10-2024 09:16:55","17-10-2024 09:20:37","Cas=
caded Incident from TTO3215753","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site ,site on Gen with =
Ubaie=3D53V, Tx Fme Gregoire( 652070658)From Huawei is informed and reporte=
d that site is impacted by Doume centre","system","716","17-10-2024 09:28:5=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003340899","Matsari"=
,"","17-10-2024 09:28:50","17-10-2024 09:16:55","17-10-2024 09:20:37","Casc=
aded Incident from TTO3215753","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue on site ,site on Gen with U=
baie=3D53V, Tx Fme Gregoire( 652070658)From Huawei is informed and reported=
 that site is impacted by Doume centre","system","715","17-10-2024 09:28:50=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0003340898","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","17-10-2024 09:28:02","17-=
10-2024 09:16:55","17-10-2024 09:20:37","No power issue on site ,site on Ge=
n with Ubaie=3D53V, Tx Fme Gregoire( 652070658)From Huawei is informed and =
reported that site is impacted by Doume centre","Parker Tchoup","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site ,site on Gen with Ubaie=3D53V, Tx Fme Gregoire( 652=
070658)From Huawei is informed and reported that site is impacted by Doume =
centre","stephane.nkamwa@ihstowers.com","668","17-10-2024 09:28:02","Sagemc=
om CMR"
"Closed Complete","Warning","T1259","IHS_YND_424","NOCINC0003340744","Ossom=
be","","17-10-2024 09:01:04","","","Alarm not proven,site on battery,Ubaie:=
50.2V;  CMS Issue.","Parker Tchoup","Warning","Warning","SYSTEM","Warning -=
 Controler Communication","Alarm not proven,site on battery,Ubaie:50.2V;  C=
MS Issue.","alexandre.kamal@ihstowers.com","13","17-10-2024 09:01:04","Sage=
mcom CMR"
"Cancelled","Warning","CTR_228","IHS_YND_409","NOCINC0003340436","Evodoula =
OCM","","17-10-2024 07:54:46","","","","TIENTCHEU NZETCHIEU GAEL","","","",=
"","","stephane.nkamwa@ihstowers.com","365","17-10-2024 07:54:46","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0003340336","BEA=
TITUDE ENTR=C9E PAVE","","17-10-2024 07:38:15","17-10-2024 07:22:05","17-10=
-2024 08:00:54","Site on Gen due to Grid fluctuation, site went down becaus=
e gen stopped with alarm ""low oil pressure""//He added oil and started Gen=
","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG =
- Control Panel","Site on Gen due to Grid fluctuation, site went down becau=
se gen stopped with alarm ""low oil pressure""//He added oil and started Ge=
n","kamga.virgile@ihstowers.com","970","17-10-2024 07:38:15","Sagemcom CMR"
"Closed Complete","Warning","T0058","IHS_YND_293","NOCINC0003340149","Nkoab=
ang MTN","","17-10-2024 06:59:42","","","Grid outage ; site alarm because G=
en stopped due to Gen card dysfonction // Gen manually started","Mba Lazare=
 Herve","Warning","Warning","POWER","Warning - Site on Battery","Grid outag=
e ; site alarm because Gen stopped due to Gen card dysfonction // Gen manua=
lly started","alexandre.kamal@ihstowers.com","127","17-10-2024 06:59:42","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0003340019","Monatele=
","IHS_YND_387, IHS_YND_407, IHS_YND_409","17-10-2024 06:33:00","17-10-2024=
 06:02:40","17-10-2024 07:45:41","No power issue on site ,site on Grid with=
 Ubaie=3D53,6V, Tx Fme Gregoire( 652070658)From Huawei is informed","Parker=
 Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","No power issue on site ,site on Grid with Ubaie=3D53,6=
V, Tx Fme Gregoire( 652070658)From Huawei is informed","system","1820","17-=
10-2024 06:33:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0003340021","Talla Mo=
natele","","17-10-2024 06:33:00","17-10-2024 06:02:40","17-10-2024 06:05:37=
","Cascaded Incident from TTO3214737 - Cascade Removed From TTO3214737","Pa=
rker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active","N=
o power issue on site ,site on Grid with Ubaie=3D53,6V, Tx Fme Gregoire( 65=
2070658)From Huawei is informed","system","1820","17-10-2024 06:33:00","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_409","NOCINC0003340022","Evodoula=
 OCM","","17-10-2024 06:33:00","17-10-2024 06:02:40","17-10-2024 06:05:37",=
"Cascaded Incident from TTO3214737 - Cascade Removed From TTO3214737","TIEN=
TCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","No power issue on site ,site on Grid with Ubaie=3D53,6V, Tx Fme Gre=
goire( 652070658)From Huawei is informed","system","1820","17-10-2024 06:33=
:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_869","IHS_YND_407","NOCINC0003340008","M=
onatele MTN","","17-10-2024 06:29:56","17-10-2024 06:02:40","17-10-2024 06:=
05:37","","Parker Tchoup","Cascade Outage","Active","Cascade Active","Casca=
de Active","No power issue on site ,site on Grid with Ubaie=3D53,6V, Tx Fme=
 Gregoire( 652070658)From Huawei is informed","stephane.nkamwa@ihstowers.co=
m","1637","17-10-2024 06:29:56","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003339279","Nko=
lmvack","","17-10-2024 02:29:57","17-10-2024 02:27:31","17-10-2024 03:41:55=
","Hybrid Gen Site : Site went down because Gen failed to start due to  the=
 Gen solenoid faulty// He Bypass it and started Gen manualy","Parker Tchoup=
","Equipment Repair","Passive","ACDG Gen","ACDG - Solenoid Coil","Hybrid Ge=
n Site : Site went down because Gen failed to start due to  the Gen solenoi=
d faulty// He Bypass it and started Gen manualy","emmanuel.ghani@ihstowers.=
com","146","17-10-2024 02:29:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003339149","Ngoum","=
","17-10-2024 01:50:01","17-10-2024 01:40:07","17-10-2024 01:41:07","Cascad=
ed Incident from TTO3213715","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on GEN with U =3D 54=
.7V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 6579596=
47of Huawei is informed","system","594","17-10-2024 01:50:01","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003338783","A=
kak-Nkozoa-MTN-IHS","","16-10-2024 23:41:53","16-10-2024 23:40:49","16-10-2=
024 23:54:05","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage // He bypass grid and manually start the gen","F=
abrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage // He bypass grid and manually start the gen","j=
oelle.ekessi@ihstowers.com","65","16-10-2024 23:41:53","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003338740","Nko=
lmvack","","16-10-2024 23:27:09","16-10-2024 23:26:37","17-10-2024 00:31:21=
","Hybrid Gen Site : site went down because Gen failed to start due to Gen =
card dysfunctionning //He Reset the Gen  Card  and  Gen manually started","=
Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Hybrid Gen Site : site went down because Gen failed to start due to Gen=
 card dysfunctionning //He Reset the Gen  Card  and  Gen manually started",=
"emmanuel.ghani@ihstowers.com","33","16-10-2024 23:27:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0003337989","A=
v-Germaine","","16-10-2024 21:20:32","16-10-2024 21:18:28","17-10-2024 11:4=
5:41","Grid outage// Grid restored. But OCM up after Power reset","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage//=
 Grid restored. But OCM up after Power reset","ange.kongo@ihstowers.com","5=
56","16-10-2024 21:20:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003337291","O=
mnisport-Rail","","16-10-2024 19:59:55","16-10-2024 19:52:59","16-10-2024 2=
0:54:20","site went down because insufficiency of twoe rectifiers due to in=
crease the load // We reduced two rack of batteries to rescue to the site "=
,"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","site went down because insufficiency of twoe rectifiers due to increase=
 the load // We reduced two rack of batteries to rescue to the site ","ange=
.kongo@ihstowers.com","417","16-10-2024 19:59:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003336588","Ngoum","=
","16-10-2024 17:46:00","16-10-2024 17:32:41","16-10-2024 17:35:00","Cascad=
ed Incident from TTO3210704","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on GEN with U =3D 50=
.2V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 6579596=
47of Huawei is informed","system","799","16-10-2024 17:46:00","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0003336481","N=
kolangaa","IHS_YND_290","16-10-2024 17:22:39","16-10-2024 17:17:29","16-10-=
2024 20:07:32","No power issue on site ,site on Grid with Ubaie=3D52.4 V TX=
 FME Lionel //655184876//  from huawei is informed.Notice that we have disj=
unction at BTS OCM","Mba Lazare Herve","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site ,=
site on Grid with Ubaie=3D52.4 V TX FME Lionel //655184876//  from huawei i=
s informed.Notice that we have disjunction at BTS OCM
","ange.kongo@ihstowers.com","311","16-10-2024 17:22:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0003336468","A=
bang","","16-10-2024 17:19:57","16-10-2024 17:17:29","16-10-2024 20:07:32",=
"No power issue on site ,site on Grid with Ubaie=3D52.4 V TX FME Lionel //6=
55184876//  from huawei is informed.Notice that we have disjunction at BTS =
OCM","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Cascade=
 Active","No power issue on site ,site on Grid with Ubaie=3D52.4 V TX FME L=
ionel //655184876//  from huawei is informed.Notice that we have disjunctio=
n at BTS OCM
","ange.kongo@ihstowers.com","10422","16-10-2024 17:19:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0003336209","S=
cience","","16-10-2024 16:39:22","16-10-2024 16:30:11","16-10-2024 19:37:52=
","wrongly ticket","TIENTCHEU NZETCHIEU GAEL","Incorrectly Logged Tickets",=
"Error","Error","Error","wrongly ticket","ange.kongo@ihstowers.com","552","=
16-10-2024 16:39:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003336047","Essomba"=
,"","16-10-2024 16:16:31","16-10-2024 16:03:26","16-10-2024 16:31:26","Casc=
aded Incident from TTO3210037","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage ,site went down because =
Gen started and stopped due to GEN(20KVA;350A) overload//He reduced load on=
 site","system","785","16-10-2024 16:16:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003336048","Biteng-M=
aetur","","16-10-2024 16:16:31","16-10-2024 16:03:26","16-10-2024 16:31:26"=
,"Cascaded Incident from TTO3210037","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage ,site went down be=
cause Gen started and stopped due to GEN(20KVA;350A) overload//He reduced l=
oad on site","system","785","16-10-2024 16:16:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003336046","Tradex-N=
komo","","16-10-2024 16:16:31","16-10-2024 16:03:26","16-10-2024 16:31:26",=
"Cascaded Incident from TTO3210037","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage ,site went down becaus=
e Gen started and stopped due to GEN(20KVA;350A) overload//He reduced load =
on site","system","785","16-10-2024 16:16:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003336045","Bitoto",=
"","16-10-2024 16:16:31","16-10-2024 16:03:26","16-10-2024 16:31:26","Casca=
ded Incident from TTO3210037","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage ,site went down because G=
en started and stopped due to GEN(20KVA;350A) overload//He reduced load on =
site","system","785","16-10-2024 16:16:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003336008","B=
iteng","IHS_YND_292, IHS_YND_172, IHS_YND_179, IHS_YND_249","16-10-2024 16:=
08:34","16-10-2024 16:03:26","16-10-2024 16:31:26","Grid outage ,site went =
down because Gen started and stopped due to GEN(20KVA;350A) overload//He re=
duced load on site","Mba Lazare Herve","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Grid outage ,site went down because Gen started and =
stopped due to GEN(20KVA;350A) overload//He reduced load on site","ange.kon=
go@ihstowers.com","309","16-10-2024 16:08:34","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003335956","Eko=
unou","","16-10-2024 16:00:04","16-10-2024 15:57:56","16-10-2024 16:07:44",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Grid power return","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery backup // Grid power return","denis.mballa@ihsto=
wers.com","129","16-10-2024 16:00:04","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0003335811","Mes=
sassi Carrefourt","","16-10-2024 15:38:53","16-10-2024 15:31:45","16-10-202=
4 17:42:11","No power issue site on grid with U=3D54v Armand Nguetsa(691144=
412) from Huawei is informed","Delor Telezing","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on grid with U=3D54v Armand Nguetsa(691144412) from Huawei is informed"=
,"denis.mballa@ihstowers.com","429","16-10-2024 15:38:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003335519","MBALNGON=
G LYCEE","","16-10-2024 14:54:00","16-10-2024 14:49:28","16-10-2024 16:13:4=
9","Cascaded Incident from TTO3209480","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // gen start automatically.Power res=
et has done to restore the site ","system","272","16-10-2024 14:54:00","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003335520","Afanoya"=
,"","16-10-2024 14:54:00","16-10-2024 14:49:28","16-10-2024 16:13:49","Casc=
aded Incident from TTO3209480","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // gen start automatically.Power reset ha=
s done to restore the site ","system","272","16-10-2024 14:54:00","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003335518","ELOUMDEM=
 CARRIERE","","16-10-2024 14:54:00","16-10-2024 14:49:28","16-10-2024 16:13=
:49","Cascaded Incident from TTO3209480","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen start automatically.Power r=
eset has done to restore the site ","system","272","16-10-2024 14:54:00","S=
agemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003335515","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","16-10-2024 14:52:36","16-10-20=
24 14:49:28","16-10-2024 16:13:49","Grid outage, site went down before gen =
start due to poor battery backup // gen start automatically.Power reset has=
 done to restore the site ","Hyemafo Gildas","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // gen start automatically.Power=
 reset has done to restore the site ","denis.mballa@ihstowers.com","189","1=
6-10-2024 14:52:36","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_265","NOCINC0003335193","Messa-Carriere O=
CM","","16-10-2024 13:53:11","","","","","","","","","","stephane.nkamwa@ih=
stowers.com","555","16-10-2024 13:53:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003335076","O=
dza II OCM","IHS_YND_528","16-10-2024 13:42:00","16-10-2024 13:29:47","16-1=
0-2024 14:57:54","site down due to CB 125A tripped in CB//CB put backon (in=
vestigations ongoing)","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Circuit Breaker Issue","site down due to CB 125A =
tripped in CB//CB put backon (investigations ongoing)","stephane.nkamwa@ihs=
towers.com","734","16-10-2024 13:42:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003335043","M=
EHANDAN","","16-10-2024 13:38:48","16-10-2024 13:29:47","16-10-2024 14:57:5=
4","site down due to CB 125A tripped in CB//CB put backon (investigations o=
ngoing)","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","site down due to CB 125A tripped in CB//CB put backon (invest=
igations ongoing)","stephane.nkamwa@ihstowers.com","844","16-10-2024 13:38:=
48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003334815","M=
imboman-Village","IHS_YND_709","16-10-2024 13:12:55","16-10-2024 12:49:06",=
"16-10-2024 13:00:18","site went down due to work Herve MBAH (657108482/Sag=
emcom; do the PM) //end of work   at 01:00 PM  but the site remains down  E=
loundou(652586578) was informed","Mba Lazare Herve","Installation Activity"=
,"Passive","Planned Activity","Installation Activity","site went down due t=
o work Herve MBAH (657108482/Sagemcom; do the PM) //end of work   at 01:00 =
PM but the site remains down  Eloundou(652586578) was informed","stephane.n=
kamwa@ihstowers.com","1430","16-10-2024 13:12:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003334713","N=
kolo II New","","16-10-2024 12:55:56","16-10-2024 12:49:06","16-10-2024 13:=
00:18","site went down due to work Herve MBAH (657108482/Sagemcom; do the P=
M) //end of work   at 01:00 PM but the site remains down  Eloundou(65258657=
8) was informed","Mba Lazare Herve","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","site went down due to work Herve MBAH (657108482/S=
agemcom; do the PM) //end of work   at 01:00 PM but the site remains down  =
Eloundou(652586578) was informed","stephane.nkamwa@ihstowers.com","1556","1=
6-10-2024 12:55:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003334664","Afanoya"=
,"","16-10-2024 12:49:31","16-10-2024 12:42:57","16-10-2024 13:48:33","Casc=
aded Incident from TTO3208500","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, DG Failed to start due to=
 overload (20Kva, 300A),and poor batteries backup // He reduced 2/9 rectifi=
er and started Gen manually.","system","394","16-10-2024 12:49:31","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003334663","MBALNGON=
G LYCEE","","16-10-2024 12:49:31","16-10-2024 12:42:57","16-10-2024 13:48:3=
3","Cascaded Incident from TTO3208500","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start d=
ue to overload (20Kva, 300A),and poor batteries backup // He reduced 2/9 re=
ctifier and started Gen manually.","system","394","16-10-2024 12:49:31","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003334662","ELOUMDEM=
 CARRIERE","","16-10-2024 12:49:30","16-10-2024 12:42:57","16-10-2024 13:48=
:33","Cascaded Incident from TTO3208500","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start=
 due to overload (20Kva, 300A),and poor batteries backup // He reduced 2/9 =
rectifier and started Gen manually.","system","393","16-10-2024 12:49:30","=
Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003334657","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","16-10-2024 12:48:12","16-10-20=
24 12:42:08","16-10-2024 13:48:55","Grid outage, DG Failed to start due to =
overload (20Kva, 300A),and poor batteries backup // He reduced 2/9 rectifie=
r and started Gen manually.","Hyemafo Gildas","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","Grid outage, DG Failed to start due to overlo=
ad (20Kva, 300A),and poor batteries backup // He reduced 2/9 rectifier and =
started Gen manually.","olivier.kwedi@ihstowers.com","491","16-10-2024 12:4=
8:12","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003334357","ODZ=
A CITE MBIA","","16-10-2024 12:09:44","16-10-2024 12:04:34","16-10-2024 13:=
08:39","Site was on gen due to grid outage, grid return, site went down due=
 to ATS disfunctionning // Grid return","Albran Byorel","Equipment Repair",=
"Passive","Control Panel","ATS-AMF Issue","Site was on gen due to grid outa=
ge, grid return, site went down due to ATS disfunctionning // Grid return",=
"olivier.kwedi@ihstowers.com","311","16-10-2024 12:09:44","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003334223","Com=
plex Beac II","","16-10-2024 11:49:02","16-10-2024 11:41:47","16-10-2024 13=
:00:21","grid outage,gen ran till fuel shortage//Refueling done","Albran By=
orel","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran=
 till fuel shortage//Refueling done","olivier.kwedi@ihstowers.com","436","1=
6-10-2024 11:49:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003334213","MBALNGON=
G LYCEE","","16-10-2024 11:47:41","16-10-2024 11:39:28","16-10-2024 11:47:2=
8","Cascaded Incident from TTO3207993","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // gen start automaticaly","system",=
"493","16-10-2024 11:47:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003334214","Afanoya"=
,"","16-10-2024 11:47:41","16-10-2024 11:39:28","16-10-2024 11:47:28","Casc=
aded Incident from TTO3207993","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // gen start automaticaly","system","493"=
,"16-10-2024 11:47:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003334212","ELOUMDEM=
 CARRIERE","","16-10-2024 11:47:40","16-10-2024 11:39:28","16-10-2024 11:47=
:28","Cascaded Incident from TTO3207993","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen start automaticaly","system=
","492","16-10-2024 11:47:40","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003334186","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","16-10-2024 11:44:39","16-10-20=
24 11:39:28","16-10-2024 11:47:28","Grid outage, site went down before gen =
start due to poor battery backup // gen start automaticaly","Hyemafo Gildas=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low=
","Grid outage, site went down before gen start due to poor battery backup =
// gen start automaticaly","olivier.kwedi@ihstowers.com","312","16-10-2024 =
11:44:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003334122","M=
arche Odza","","16-10-2024 11:34:56","16-10-2024 11:09:47","16-10-2024 12:0=
0:47","Grid Outage, site went down because Gen start and  stopped with ""hi=
gh temp"" alarm// He added water and started Gen manualy","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage,=
 site went down because Gen start and  stopped with ""high temp"" alarm// H=
e added water and started Gen manualy","stephane.nkamwa@ihstowers.com","151=
1","16-10-2024 11:34:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003333833","Matsari"=
,"","16-10-2024 10:45:31","16-10-2024 10:35:03","16-10-2024 10:36:01","Casc=
aded Incident from TTO3207547","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on GEN with U =3D =
50.5V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 65795=
9647of Huawei is informed","system","628","16-10-2024 10:45:31","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003333834","Yoko OCM=
","","16-10-2024 10:45:31","16-10-2024 10:35:03","16-10-2024 10:36:01","Cas=
caded Incident from TTO3207547","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on GEN with U =3D=
 50.5V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 6579=
59647of Huawei is informed","system","628","16-10-2024 10:45:31","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003333835","MBIMBIM"=
,"","16-10-2024 10:45:31","16-10-2024 10:35:03","16-10-2024 10:36:01","Casc=
aded Incident from TTO3207547","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on GEN with U =3D =
50.5V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 65795=
9647of Huawei is informed","system","628","16-10-2024 10:45:31","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003333832","Ngoum","=
","16-10-2024 10:45:30","16-10-2024 10:35:03","16-10-2024 10:36:01","Cascad=
ed Incident from TTO3207547","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on GEN with U =3D 50=
.5V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 6579596=
47of Huawei is informed","system","627","16-10-2024 10:45:30","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003333794","N=
gouetou","","16-10-2024 10:40:14","16-10-2024 10:35:03","16-10-2024 10:36:0=
1","","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade A=
ctive","No power issue. Site is on GEN with U =3D 50.5V Hybrid gen site wit=
h threshold =3D 47.5V).   TX FME Abdouramane 657959647of Huawei is informed=
","stephane.nkamwa@ihstowers.com","312","16-10-2024 10:40:14","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003332898","M=
essa-Carriere OCM","","16-10-2024 07:56:13","16-10-2024 07:49:47","16-10-20=
24 08:15:47","No power issue site on grid with U=3D52,1V, FME TX Mohamadou/=
691144435/ from Huawei is informed ","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D52,1V, FME TX Mohamadou/691144435/ from Huawei is informed ",=
"stephane.nkamwa@ihstowers.com","388","16-10-2024 07:56:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0003332883","B=
astos Bir","","16-10-2024 07:54:15","16-10-2024 07:53:33","16-10-2024 08:34=
:33","No power issue on site  U=3D 54.5V site on Grid The fme tx Eloundou (=
652586578) from Huawei is informed","Mboua Thierry","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site  U=3D 54.5V site on Grid The fme tx Eloundou (652586578) from H=
uawei is informed","stephane.nkamwa@ihstowers.com","44","16-10-2024 07:54:1=
5","Sagemcom CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0003332788","A=
RMP","","16-10-2024 07:30:54","16-10-2024 07:23:46","16-10-2024 08:25:46","=
No power issue on site  U=3D 55.5V site on Grid The fme tx Eloundou (652586=
578) from Huawei is informed","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue on site  U=3D 5=
5.5V site on Grid The fme tx Eloundou (652586578) from Huawei is informed",=
"stephane.nkamwa@ihstowers.com","429","16-10-2024 07:30:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0003332751","B=
astos Bir","","16-10-2024 07:15:01","16-10-2024 07:09:52","16-10-2024 07:30=
:52","No power issue on site  U=3D 54.5V site on Grid The fme tx Eloundou (=
652586578) from Huawei is informed","Mboua Thierry","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site  U=3D 54.5V site on Grid The fme tx Eloundou (652586578) from H=
uawei is informed","stephane.nkamwa@ihstowers.com","311","16-10-2024 07:15:=
01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003332691","C=
omplexe-BEAC","","16-10-2024 06:59:19","16-10-2024 06:53:09","16-10-2024 08=
:15:09","grid outage, site went down because gen start and stoppen with Ala=
rm ""Low oil pressure"" //He added oil and manually start the gen","Albran =
Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","gri=
d outage, site went down because gen start and stoppen with Alarm ""Low oil=
 pressure"" //He added oil and manually start the gen","stephane.nkamwa@ihs=
towers.com","371","16-10-2024 06:59:19","Sagemcom CMR"
"Closed Complete","Site Down","T0530","IHS_YND_252","NOCINC0003332346","Kow=
eit City","","16-10-2024 04:58:02","16-10-2024 04:54:49","16-10-2024 05:44:=
44","Grid fluctuation, site went down because gen start and stopped due to =
grid bad voltage // He bypass grid and manually start the gen","Albran Byor=
el","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage // He bypass grid and manually start the gen","landry.etame@=
ihstowers.com","391","16-10-2024 04:58:02","Sagemcom CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0003332267","NKO=
NGKARAK","","16-10-2024 04:31:44","16-10-2024 04:21:36","16-10-2024 06:24:4=
2","Hybrid gen site, site went down because gen stopped with alarm hight te=
mp // he added water in radiator and Gen manually started","TIENTCHEU NZETC=
HIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp=
 - Coolant Level Issue","Hybrid gen site, site went down because gen stoppe=
d with alarm hight temp // he added water in radiator and Gen manually star=
ted","landry.etame@ihstowers.com","608","16-10-2024 04:31:44","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003331350","Matsari"=
,"","15-10-2024 23:01:41","15-10-2024 22:31:22","15-10-2024 22:32:22","Casc=
aded Incident from TTO3204478","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on GEN with U =3D =
49.7V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 65795=
9647of Huawei is informed","system","1819","15-10-2024 23:01:41","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003331352","Ngouetou=
","","15-10-2024 23:01:41","15-10-2024 22:31:22","15-10-2024 22:32:22","Cas=
caded Incident from TTO3204478","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on GEN with U =3D=
 49.7V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 6579=
59647of Huawei is informed","system","1819","15-10-2024 23:01:41","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003331351","Yoko OCM=
","","15-10-2024 23:01:41","15-10-2024 22:31:22","15-10-2024 22:32:22","Cas=
caded Incident from TTO3204478","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on GEN with U =3D=
 49.7V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 6579=
59647of Huawei is informed","system","1819","15-10-2024 23:01:41","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003331353","MBIMBIM"=
,"","15-10-2024 23:01:41","15-10-2024 22:31:22","15-10-2024 22:32:22","Casc=
aded Incident from TTO3204478","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on GEN with U =3D =
49.7V Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane 65795=
9647of Huawei is informed","system","1819","15-10-2024 23:01:41","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003331116","Nkolfoul=
ou 2","","15-10-2024 22:14:00","15-10-2024 22:09:31","15-10-2024 23:07:49",=
"Cascaded Incident from TTO3204298","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site  went down because CB OCM(2*1=
00A) disjuncted in the DCbox causing by poor backup //He reamed CB","system=
","269","15-10-2024 22:14:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003331117","Melen Ba=
'aba","","15-10-2024 22:14:00","15-10-2024 22:09:31","15-10-2024 23:07:49",=
"Cascaded Incident from TTO3204298","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site  went down because CB OCM(2*1=
00A) disjuncted in the DCbox causing by poor backup //He reamed CB","system=
","269","15-10-2024 22:14:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003331118","TSINGA V=
ILLAGE 2","","15-10-2024 22:14:00","15-10-2024 22:09:31","15-10-2024 23:07:=
49","Cascaded Incident from TTO3204298","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site  went down because CB OC=
M(2*100A) disjuncted in the DCbox causing by poor backup //He reamed CB","s=
ystem","269","15-10-2024 22:14:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003331107","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","15-10-2024 22:12:37","1=
5-10-2024 22:09:31","15-10-2024 23:07:49","Site  went down because CB OCM(2=
*100A) disjuncted in the DCbox causing by poor backup //He reamed CB","Sili=
gap Boris","Equipment Repair","Passive","Control Panel","Power Cabinet - Ci=
rcuit Breaker Issue","Site  went down because CB OCM(2*100A) disjuncted in =
the DCbox causing by poor backup //He reamed CB","kouoh.jean@ihstowers.com"=
,"186","15-10-2024 22:12:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003330787","M=
vog-Manga","","15-10-2024 21:20:26","15-10-2024 21:11:22","15-10-2024 22:49=
:49","Site on Gen due to Grid outage ;site went down  due 02 lack phases//H=
e make the bridge on good phase ","Albran Byorel","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Site on Gen due to Grid ou=
tage ;site went down  due 02 lack phases//He make the bridge on good phase =
","joelle.ekessi@ihstowers.com","545","15-10-2024 21:20:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003330772","C=
omplexe-BEAC","","15-10-2024 21:16:30","15-10-2024 21:15:26","15-10-2024 21=
:34:02","rid fluctuation, site went down before Gen start and stopped due t=
o Gid bad voltage no RCP on site// he bypass the Grid and Gen manually star=
ted","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase =
Controller Faulty","grid fluctuation, site went down before Gen start and s=
topped due to Gid bad voltage no RCP on site// he bypass the Grid and Gen m=
anually started","joelle.ekessi@ihstowers.com","65","15-10-2024 21:16:30","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003330743","E=
ssomba","","15-10-2024 21:12:52","15-10-2024 21:10:49","15-10-2024 22:06:49=
","Grid outage ,site went down because Gen started and stopped due to GEN(1=
5kVA;200A) overload//He reduced load on site","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,site went dow=
n because Gen started and stopped due to GEN(15kVA;200A) overload//He reduc=
ed load on site","joelle.ekessi@ihstowers.com","124","15-10-2024 21:12:52",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003330658","Com=
plex Beac II","","15-10-2024 20:59:25","15-10-2024 20:54:22","15-10-2024 21=
:42:05","Grid outage, site went down because Gen failed to start due to Gen=
 card faulty // Gen manually started","Albran Byorel","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down beca=
use Gen failed to start due to Gen card faulty // Gen manually started","em=
manuel.ghani@ihstowers.com","304","15-10-2024 20:59:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003330532","Yoko MTN=
","","15-10-2024 20:42:31","15-10-2024 20:35:09","15-10-2024 20:40:31","Cas=
caded Incident from TTO3203571","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue  with U=3D54.3V //=
site on Grid  Tx fme Gregroire 654547479 from Huawei is informed SITe up 08=
:40PM","system","442","15-10-2024 20:42:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003330530","Ngoum","=
","15-10-2024 20:42:31","15-10-2024 20:35:09","15-10-2024 20:40:31","Cascad=
ed Incident from TTO3203571","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active//No power issue  with U=3D54.3V //sit=
e on Grid  Tx fme Gregroire 654547479 from Huawei is informed SITe up 08:40=
PM","system","442","15-10-2024 20:42:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003330531","Ngouetou=
","","15-10-2024 20:42:31","15-10-2024 20:35:09","15-10-2024 20:40:31","Cas=
caded Incident from TTO3203571","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue  with U=3D54.3V //=
site on Grid  Tx fme Gregroire 654547479 from Huawei is informed SITe up 08=
:40PM","system","442","15-10-2024 20:42:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003330529","Matsari"=
,"","15-10-2024 20:42:30","15-10-2024 20:35:09","15-10-2024 20:40:31","Casc=
aded Incident from TTO3203571","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue  with U=3D54.3V //s=
ite on Grid  Tx fme Gregroire 654547479 from Huawei is informed SITe up 08:=
40PM","system","441","15-10-2024 20:42:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003330528","MBIMBIM"=
,"","15-10-2024 20:42:30","15-10-2024 20:35:09","15-10-2024 20:40:31","Casc=
aded Incident from TTO3203571","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power issue  with U=3D54.3V //s=
ite on Grid  Tx fme Gregroire 654547479 from Huawei is informed SITe up 08:=
40PM","system","441","15-10-2024 20:42:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003330527","Nguila",=
"","15-10-2024 20:42:30","15-10-2024 20:35:09","15-10-2024 20:40:31","Casca=
ded Incident from TTO3203571","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active//No power issue  with U=3D54.3V //si=
te on Grid  Tx fme Gregroire 654547479 from Huawei is informed SITe up 08:4=
0PM","system","441","15-10-2024 20:42:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003330518","MEHANDAN=
","","15-10-2024 20:41:00","15-10-2024 20:35:01","15-10-2024 22:18:01","Cas=
caded Incident from TTO3203573","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid fluctuation, site went down befor=
e Gen start and stopped due to Gid bad voltage // he bypass the Grid and Ge=
n manually started","system","359","15-10-2024 20:41:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003330503","O=
dza II OCM","IHS_YND_528","15-10-2024 20:39:28","15-10-2024 20:35:01","15-1=
0-2024 22:18:01","grid fluctuation, site went down before Gen start and sto=
pped due to Gid bad voltage // he bypass the Grid and Gen manually started"=
,"Albran Byorel","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","grid fluctuation, site went down before Gen start and stopp=
ed due to Gid bad voltage // he bypass the Grid and Gen manually started","=
joelle.ekessi@ihstowers.com","268","15-10-2024 20:39:28","Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0003330501","Don=
ga","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_Y=
ND_473","15-10-2024 20:39:20","15-10-2024 20:35:09","15-10-2024 21:00:31","=
Active//No power issue  with U=3D54.3V //site on GEN  Tx fme Gregroire 6545=
47479 from Huawei is informed SITe up 08:40PM","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue  with U=3D54.3V //site on GEN  Tx fme Gregroire 6545=
47479 from Huawei is informed SITe up 08:40PM","emmanuel.ghani@ihstowers.co=
m","252","15-10-2024 20:39:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0003330443","ARMP",""=
,"15-10-2024 20:27:51","15-10-2024 20:24:16","15-10-2024 20:35:24","Cascade=
d Incident from TTO3203502","","Cascade Outage","Active","Cascade Active","=
Cascade Active","No power issue Ubaie=3D54.5V site on Grid  The Tx  fme  El=
oundo/ 652586578 From  Huawie is informed","system","215","15-10-2024 20:27=
:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0003330442","Bastos B=
ir","","15-10-2024 20:27:51","15-10-2024 20:24:16","15-10-2024 20:35:24","C=
ascaded Incident from TTO3203502","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue Ubaie=3D54.5V site on Gr=
id  The Tx  fme  Eloundo/ 652586578 From  Huawie is informed","system","215=
","15-10-2024 20:27:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003330439","D=
ragage","IHS_YND_704, IHS_YND_208","15-10-2024 20:26:20","15-10-2024 20:24:=
16","15-10-2024 20:35:24","No power issue Ubaie=3D54.5V site on Grid  The T=
x  fme  Eloundo/ 652586578 From  Huawie is informed","Mboua Thierry","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue Ubaie=3D54.5V site on Grid  The Tx  fme  Eloundo/ 6525=
86578 From  Huawie is informed","joelle.ekessi@ihstowers.com","125","15-10-=
2024 20:26:20","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003330196","Com=
plex Beac II","","15-10-2024 19:34:23","15-10-2024 19:31:18","15-10-2024 19=
:55:19","Grid outage site went down because Gen failed to start due to Gen =
card faulty // Gen manually started","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","Grid outage site went down becaus=
e Gen failed to start due to Gen card faulty // Gen manually started","emma=
nuel.ghani@ihstowers.com","186","15-10-2024 19:34:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003330010","Lobo OCM=
","","15-10-2024 18:53:20","15-10-2024 18:48:42","15-10-2024 18:53:13","Cas=
caded Incident from TTO3202970","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Grid power return","system"=
,"278","15-10-2024 18:53:20","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003330006","N=
KOMEKUI OCM","IHS_YND_341","15-10-2024 18:52:46","15-10-2024 18:48:42","15-=
10-2024 18:53:44","Grid outage, site went down before gen start due to poor=
 battery backup // Grid power return","TIENTCHEU NZETCHIEU GAEL","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge, site went down before gen start due to poor battery backup // Grid powe=
r return","joelle.ekessi@ihstowers.com","244","15-10-2024 18:52:46","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0003329820","C=
RF Nkoabang","","15-10-2024 18:17:49","15-10-2024 17:55:54","15-10-2024 18:=
10:53","","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Ca=
scade Active","Active//No power issue, site on Grid with U=3D53.2V, Lionel =
/655184876/ From Huawei is informed","joelle.ekessi@ihstowers.com","1805","=
15-10-2024 18:17:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003329731","N=
koabang2","IHS_YND_736","15-10-2024 18:02:00","15-10-2024 17:55:54","15-10-=
2024 19:45:25","Active//No power issue, site on Grid with U=3D53.2V, Lionel=
 /655184876/ From Huawei is informed","Mba Lazare Herve","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue, site on Grid with U=3D53.2V, Lionel /655184876/ From Huaw=
ei is informed","joelle.ekessi@ihstowers.com","368","15-10-2024 18:02:00","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0003329714","O=
kola OCM","","15-10-2024 17:58:36","15-10-2024 17:56:28","15-10-2024 20:37:=
33","site went down because gen start and stoppen with alarm low oil pressu=
re // He added oil pressure, site on gen","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Oil Pressure Sensor Faulty","site=
 went down because gen start and stoppen with alarm low oil pressure // He =
added oil pressure, site on gen","joelle.ekessi@ihstowers.com","129","15-10=
-2024 17:58:36","Sagemcom CMR"
"Closed Complete","Warning","T0341","IHS_YND_270","NOCINC0003329525","Santa=
 Barbara Yde","","15-10-2024 17:32:00","","","Site Went to low Batterie due=
 to insuffisance off Rectifier on Site (04) because Load Increase // he add=
 02 Rectifier and Site is on 06 Rectifier","Delor Telezing","Warning","Warn=
ing","POWER","Warning - Battery Low Voltage","Site Went to low Batterie due=
 to insuffisance off Rectifier on Site (04) because Load Increase // he add=
 02 Rectifier and Site is on 06 Rectifier","kombi.samuel@ihstowers.com","8"=
,"15-10-2024 17:32:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003329477","N=
GONA","","15-10-2024 17:26:30","15-10-2024 17:23:26","15-10-2024 18:38:02",=
"Active//No power isssue, site is on Grid with Ubaie=3D56V, Rm alain (691 1=
4 44 23) from Huawei is informed ","Mba Lazare Herve","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power isssue, site is on Grid with Ubaie=3D56V, Rm alain (691 14 44 23) f=
rom Huawei is informed ","joelle.ekessi@ihstowers.com","185","15-10-2024 17=
:26:30","Sagemcom CMR"
"Closed Complete","Site Down","T1121","IHS_YND_690","NOCINC0003329426","Ntu=
i administration","","15-10-2024 17:16:21","15-10-2024 17:09:17","15-10-202=
4 18:20:26","No power issue on site ,site on Grid with Ubaie=3D54,8V, Tx Fm=
e Gregoire( 652070658)From Huawei is unreachable but RM Martial (690087047)=
 is informed SITE UP 05:51 PM","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site ,site on Grid with Ubaie=3D54,8V, Tx Fme Gregoire( 652070658)From Hu=
awei is unreachable but RM Martial (690087047) is informed SITE UP 05:51 PM=
","emmanuel.ghani@ihstowers.com","425","15-10-2024 17:16:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003329390","Afanoya"=
,"","15-10-2024 17:06:21","15-10-2024 17:01:15","15-10-2024 17:43:11","Casc=
aded Incident from TTO3202231","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Gen Mnaually started","system","306","=
15-10-2024 17:06:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003329389","MBALNGON=
G LYCEE","","15-10-2024 17:06:21","15-10-2024 17:01:15","15-10-2024 17:43:1=
1","Cascaded Incident from TTO3202231","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen Mnaually started","system","3=
06","15-10-2024 17:06:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003329388","ELOUMDEM=
 CARRIERE","","15-10-2024 17:06:20","15-10-2024 17:01:15","15-10-2024 17:43=
:11","Cascaded Incident from TTO3202231","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen Mnaually started","system",=
"305","15-10-2024 17:06:20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003329378","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","15-10-2024 17:05:19","15-10-20=
24 17:00:15","15-10-2024 17:43:11","Grid outage, site went down before gen =
start due to poor battery backup // Gen Mnaually started","Hyemafo Gildas",=
"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen Mnaually started","emmanuel.ghani@ihstowers.com","471","15-10-2024 17:=
05:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003329074","Afanoya"=
,"","15-10-2024 16:07:41","15-10-2024 16:05:26","15-10-2024 16:17:41","Casc=
aded Incident from TTO3201860","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Grid return","system","135","15-10-202=
4 16:07:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003329072","ELOUMDEM=
 CARRIERE","","15-10-2024 16:07:40","15-10-2024 16:05:26","15-10-2024 16:17=
:41","Cascaded Incident from TTO3201860","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Grid return","system","134","15=
-10-2024 16:07:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003329073","MBALNGON=
G LYCEE","","15-10-2024 16:07:40","15-10-2024 16:05:26","15-10-2024 16:17:4=
1","Cascaded Incident from TTO3201860","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid return","system","134","15-1=
0-2024 16:07:40","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003329051","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","15-10-2024 16:06:30","15-10-20=
24 16:05:26","15-10-2024 16:17:41","Grid outage, site went down before gen =
start due to poor battery backup // Grid return","Hyemafo Gildas","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, site went down before gen start due to poor battery backup // Grid ret=
urn","emmanuel.ghani@ihstowers.com","65","15-10-2024 16:06:30","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0003328965","M=
amch Building","","15-10-2024 15:59:18","15-10-2024 15:57:08","15-10-2024 1=
6:05:22","no power issue on site Ubaie:54V;  site on Grid.The FME Armand Ng=
uetsa //699949553  from Huawei WORKING ON SITE","Mboua Thierry","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"no power issue on site Ubaie:54V;  site on Grid.The FME Armand Nguetsa //6=
99949553  from Huawei WORKING ON SITE","joelle.ekessi@ihstowers.com","131",=
"15-10-2024 15:59:18","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003328752","Bas=
tos Amb Coree","","15-10-2024 15:26:36","15-10-2024 15:25:30","15-10-2024 1=
6:43:30","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No S=
pace to deploy a MDG//Grid Restored","emmanuel.ghani@ihstowers.com","67","1=
5-10-2024 15:26:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003328592","Afanoya"=
,"","15-10-2024 14:53:51","15-10-2024 14:46:13","15-10-2024 15:01:04","Casc=
aded Incident from TTO3201309","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // gen start automatically","system","458=
","15-10-2024 14:53:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003328590","ELOUMDEM=
 CARRIERE","","15-10-2024 14:53:50","15-10-2024 14:46:13","15-10-2024 15:01=
:04","Cascaded Incident from TTO3201309","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen start automatically","syste=
m","457","15-10-2024 14:53:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003328591","MBALNGON=
G LYCEE","","15-10-2024 14:53:50","15-10-2024 14:46:13","15-10-2024 15:01:0=
4","Cascaded Incident from TTO3201309","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // gen start automatically","system"=
,"457","15-10-2024 14:53:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003328575","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","15-10-2024 14:51:23","15-10-=
2024 14:46:13","15-10-2024 15:01:04","Grid outage, site went down before ge=
n start due to poor battery backup // gen start automatically","Hyemafo Gil=
das","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Grid outage, site went down before gen start due to poor battery back=
up // gen start automatically","joelle.ekessi@ihstowers.com","311","15-10-2=
024 14:51:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003328160","MBALNGON=
G LYCEE","","15-10-2024 13:42:31","15-10-2024 13:30:06","15-10-2024 13:46:0=
2","Cascaded Incident from TTO3200780","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // gen start automatically","system"=
,"745","15-10-2024 13:42:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003328159","ELOUMDEM=
 CARRIERE","","15-10-2024 13:42:30","15-10-2024 13:30:06","15-10-2024 13:46=
:02","Cascaded Incident from TTO3200780","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen start automatically","syste=
m","744","15-10-2024 13:42:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003328131","Afanoya"=
,"","15-10-2024 13:39:00","15-10-2024 13:30:06","15-10-2024 13:46:02","Casc=
aded Incident from TTO3200780","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // gen start automatically","system","534=
","15-10-2024 13:39:00","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003328126","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","15-10-2024 13:38:14","15-10-20=
24 13:30:06","15-10-2024 13:46:02","Grid outage, site went down before gen =
start due to poor battery backup // gen start automatically","Hyemafo Gilda=
s","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid outage, site went down before gen start due to poor battery backup=
 // gen start automatically","adonis.defokoua@ihstowers.com","489","15-10-2=
024 13:38:14","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_293","NOCINC0003328021","Nkoabang M=
TN","","15-10-2024 13:20:15","","","Site went alarmes due to work  SS Blais=
e From IHS is Working On site// end Off Work ","Mba Lazare Herve","Warning"=
,"Warning","POWER","Warning - Site on Battery","Site went alarmes due to wo=
rk  SS Blaise From IHS is Working On site// end Off Work ","ange.kongo@ihst=
owers.com","3","15-10-2024 13:20:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003327381","Y=
de-M-Central","","15-10-2024 12:10:33","15-10-2024 12:09:16","15-10-2024 13=
:07:50","No power issue site on grid with U=3D52,3v,Mohamadou(691144435) fr=
om Huawei is informed//site up at 12:13 PM","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on grid with U=3D52,3v,Mohamadou(691144435) from Huawei is informed//si=
te up at 12:13 PM","ange.kongo@ihstowers.com","78","15-10-2024 12:10:33","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003327140","M=
vog-Manga","","15-10-2024 11:29:16","15-10-2024 11:24:07","15-10-2024 11:58=
:40","grid outage,gen ran till fuel shortage//Refueling done","Albran Byore=
l","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran ti=
ll fuel shortage//Refueling done","ange.kongo@ihstowers.com","311","15-10-2=
024 11:29:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003326831","M=
essa-Carriere OCM","","15-10-2024 10:46:01","15-10-2024 10:40:52","15-10-20=
24 12:13:24","No power issue site on grid with U=3D52,1v//site up at 11:28 =
AM Mohamadou from Huawei is informed ","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site o=
n grid with U=3D52,1v//site up at 11:28 AM Mohamadou from Huawei is informe=
d ","ange.kongo@ihstowers.com","311","15-10-2024 10:46:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0003326805","N=
gousso-II","","15-10-2024 10:40:25","15-10-2024 10:33:20","15-10-2024 11:21=
:11","No power issue on site U=3D50,9v site on grid Armand of huawei is  wo=
rking on site","MFOUAGUEGUE MATHIEU","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D50,9v site on grid Armand of huawei is  working on site","ange.kongo@ihs=
towers.com","425","15-10-2024 10:40:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003326742","E=
kie sud","","15-10-2024 10:30:42","15-10-2024 10:19:28","15-10-2024 11:26:3=
0","No power issue site on grid with U=3D50,5v Lionnel Steeve (655184876) f=
rom Huawei is informed","Albran Byorel","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D50,5v Lionnel Steeve (655184876) from Huawei is informed","an=
ge.kongo@ihstowers.com","675","15-10-2024 10:30:42","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_292","NOCINC0003326591","Bitoto",""=
,"15-10-2024 10:13:29","","","Site went alarmes due to work  SS Blaise From=
 IHS is Working On site// end Off Work ","Mba Lazare Herve","Warning","Warn=
ing","POWER","Warning - Site on Battery","Site went alarmes due to work  SS=
 Blaise From IHS is Working On site// end Off Work ","ange.kongo@ihstowers.=
com","4","15-10-2024 10:13:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003326228","N=
GONA","","15-10-2024 09:22:36","15-10-2024 09:16:31","15-10-2024 11:44:29",=
"No power issue site on grid with U=3D55,8v lionel Adjeg of huawei is infor=
medsite up at 09:36 AM","Mba Lazare Herve","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on grid with U=3D55,8v lionel Adjeg of huawei is informedsite up at 09:36 A=
M","ange.kongo@ihstowers.com","366","15-10-2024 09:22:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003325996","O=
dza II","","15-10-2024 08:35:30","15-10-2024 08:28:21","15-10-2024 08:46:29=
","Grid outage, site went down before gen start due to poor battery backup =
// gen start automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // gen start automatically","ange=
.kongo@ihstowers.com","432","15-10-2024 08:35:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003325976","L=
abogenie","IHS_YND_568","15-10-2024 08:29:54","15-10-2024 08:23:46","15-10-=
2024 10:13:36","Grid outage.no space to deploy mobile gen//grid power retur=
n","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid outage.no space to deploy mobile gen//grid power return","ange.kongo@ih=
stowers.com","369","15-10-2024 08:29:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0003325974","A=
nguissa New","","15-10-2024 08:29:07","15-10-2024 08:23:46","15-10-2024 10:=
13:36","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage.no space to deploy mobile gen//grid power return=
","ange.kongo@ihstowers.com","6512","15-10-2024 08:29:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003325451","A=
ngongo","","15-10-2024 06:25:11","15-10-2024 06:17:04","15-10-2024 09:41:29=
","No power issue site  is on grid Ubaie=3D54,9V Rm Alain of huawei is info=
rmed up at 06:25","Fanda Brice","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site  is on grid=
 Ubaie=3D54,9V Rm Alain of huawei is informed up at 06:25","ange.kongo@ihst=
owers.com","488","15-10-2024 06:25:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_098","NOCINC0003325281","Ekounou"=
,"","15-10-2024 05:34:31","15-10-2024 05:29:22","15-10-2024 07:03:19","Grid=
 outage,gen failed to start due alarm ""low oil pressure"" //We reset card =
GE and gen manually started ","Albran Byorel","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due alar=
m ""low oil pressure"" //We reset card GE and gen manually started ","steph=
ane.nkamwa@ihstowers.com","310","15-10-2024 05:34:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003324839","M=
aison-Blanche-IHS","","15-10-2024 02:37:47","15-10-2024 02:25:38","15-10-20=
24 02:55:22","Grid outage, no space to deploy a mobil gen//grid return ",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy a mobil gen//grid return ","stephane.nkamwa@ihsto=
wers.com","730","15-10-2024 02:37:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0003324830","S=
imbock OCM","","15-10-2024 02:35:10","15-10-2024 02:14:00","15-10-2024 04:4=
2:07","Access issue during  to night site went down because the Cb(32A) of =
rectifier disjoncted causing by one rectifier faulty// he reamed the Cb sit=
e on grid ","Hyemafo Gildas","Access Denial","Lease Or Legal","Landlord Rel=
ated Issues","Access Issue - Land Lord","Access issue during  to night site=
 went down because the Cb(32A) of rectifier disjoncted causing by one recti=
fier faulty// he reamed the Cb site on grid ","stephane.nkamwa@ihstowers.co=
m","1271","15-10-2024 02:35:10","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003324098","ODZ=
A CITE MBIA","","14-10-2024 22:54:34","14-10-2024 22:00:21","15-10-2024 08:=
29:38","Access issue during the night due to landload,grid outage,gen faile=
d to start due to no automatism on site//Gen manually started","Albran Byor=
el","Access Denial","Lease Or Legal","Landlord Related Issues","Access Issu=
e - Land Lord","Access issue during the night due to landload,grid outage,g=
en failed to start due to no automatism on site//Gen manually started","kam=
ga.virgile@ihstowers.com","3254","14-10-2024 22:54:34","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0003323709","Mes=
sassi Carrefourt","","14-10-2024 21:49:09","14-10-2024 21:33:02","14-10-202=
4 22:55:03","grid outage, site went down because gen failed to start due to=
 dysfunctionning of ATS motorized // He put site on grid","Delor Telezing",=
"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","grid outage, =
site went down because gen failed to start due to dysfunctionning of ATS mo=
torized // He put site on grid","landry.etame@ihstowers.com","967","14-10-2=
024 21:49:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0003323633","Ngoulmek=
ong-Nord","","14-10-2024 21:39:20","14-10-2024 21:29:23","14-10-2024 21:58:=
51","Cascaded Incident from TTO3195360","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down due to disjunct=
ion of Cb(80A) in Pwc // he bypassed the cb(80A)","system","597","14-10-202=
4 21:39:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0003323613","E=
leveur","IHS_YND_277","14-10-2024 21:38:32","14-10-2024 21:29:23","14-10-20=
24 21:58:51","site went down due to disjunction of Cb(80A) in Pwc // he byp=
assed the cb(80A)","Siligap Boris","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Circuit Breaker Issue","site went down due to disjunc=
tion of Cb(80A) in Pwc // he bypassed the cb(80A)","kouoh.jean@ihstowers.co=
m","549","14-10-2024 21:38:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0003323178","N=
gousso-II","","14-10-2024 20:31:36","14-10-2024 20:11:22","14-10-2024 20:20=
:23","no power issue on site Ubaie:53.7V;  site on Grid.The FME Armand Ngue=
tsa //699949553  from Huawei is informed notice that disjunction of CB in B=
TS Ocm","MFOUAGUEGUE MATHIEU","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","no power issue on site Ubaie:53.7=
V;  site on Grid.The FME Armand Nguetsa //699949553  from Huawei is informe=
d notice that disjunction of CB in BTS Ocm","kouoh.jean@ihstowers.com","121=
5","14-10-2024 20:31:36","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003323086","MBI=
MBIM","","14-10-2024 20:19:38","14-10-2024 20:08:33","14-10-2024 20:56:50",=
"Grid outage site went down because Gen started and stopped due to the fuel=
 and water mixture in the tank // He purged the tank","Parker Tchoup","Fuel=
 Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The F=
uel","Grid outage site went down because Gen started and stopped due to the=
 fuel and water mixture in the tank // He purged the tank","landry.etame@ih=
stowers.com","666","14-10-2024 20:19:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0003322873","Ngoulmek=
ong-Nord","","14-10-2024 19:35:40","14-10-2024 19:28:52","14-10-2024 21:05:=
43","Cascaded Incident from TTO3194461","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down because the Cb(=
125A) of Pwc faulty// he replaced the Cb(125A) by Cb(80A)","system","408","=
14-10-2024 19:35:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0003322869","E=
leveur","IHS_YND_277","14-10-2024 19:34:22","14-10-2024 19:28:52","14-10-20=
24 21:05:43","site went down because the Cb(125A) of Pwc faulty// he replac=
ed the Cb(125A) by Cb(80A)","Siligap Boris","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Circuit Breaker Issue","site went down becau=
se the Cb(125A) of Pwc faulty// he replaced the Cb(125A) by Cb(80A)","kouoh=
.jean@ihstowers.com","331","14-10-2024 19:34:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0003322800","NKONGKAR=
AK","","14-10-2024 19:20:00","13-10-2024 22:27:00","15-10-2024 14:15:12","C=
ascaded Incident from TTO3187739","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","FME was on site and notic=
ed that engine bloc is faulty and reported that he will go to the site MOM =
take another engine to restore the site","system","75180","14-10-2024 19:20=
:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003322789","M=
IMBOMAN LIBERTE","","14-10-2024 19:17:37","14-10-2024 19:09:22","14-10-2024=
 19:23:45","Grid outage site went down because main Gen faulty// Grid power=
 return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Generator Faulty","Grid outage site went down because main Gen faulty// Gr=
id power return","kouoh.jean@ihstowers.com","495","14-10-2024 19:17:37","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0003322755","Nko=
abang MTN","","14-10-2024 19:11:35","14-10-2024 19:08:25","14-10-2024 19:18=
:48","Grid Outage Site went down due to Gen Card dysfuitionning  // He Manu=
ally Start the Gen ","Mba Lazare Herve","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","Grid Outage Site went down due to Gen Card dys=
fuitionning  // He Manually Start the Gen ","landry.etame@ihstowers.com","1=
91","14-10-2024 19:11:35","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003322599","Eko=
unou","","14-10-2024 18:51:26","14-10-2024 18:43:22","14-10-2024 18:53:03",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Grid power return","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery backup // Grid power return","landry.etame@ihsto=
wers.com","485","14-10-2024 18:51:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003322164","M=
essa-Carriere OCM","","14-10-2024 17:27:12","14-10-2024 17:11:57","14-10-20=
24 17:28:48","Grid OUTAGE no space to deploy MDG // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid OUTAGE no=
 space to deploy MDG // Grid return","kouoh.jean@ihstowers.com","916","14-1=
0-2024 17:27:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003322082","B=
itoto","","14-10-2024 17:10:40","14-10-2024 17:03:14","14-10-2024 18:07:52"=
,"site went down because the Cb(50A) of rectifier disjoncted due to work zt=
e on site// he reamed the Cb","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier - Circuit Breaker","site went down because the Cb=
(50A) of rectifier disjoncted due to work zte on site// he reamed the Cb","=
kouoh.jean@ihstowers.com","447","14-10-2024 17:10:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003321991","Eto koss=
 Yde","","14-10-2024 16:57:41","14-10-2024 16:49:26","14-10-2024 17:01:56",=
"Cascaded Incident from TTO3193368","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en stopped due to diesel filter cartridge does not let fuel through// He by=
pass diesel filter cartridge and Gen manually started(replaced ongoing)","s=
ystem","495","14-10-2024 16:57:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003321992","ELOUMDEM=
 CARRIERE 2","","14-10-2024 16:57:41","14-10-2024 16:49:26","14-10-2024 17:=
01:56","Cascaded Incident from TTO3193368","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down be=
cause Gen stopped due to diesel filter cartridge does not let fuel through/=
/ He bypass diesel filter cartridge and Gen manually started(replaced ongoi=
ng)","system","495","14-10-2024 16:57:41","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003321988","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","14-10-2024 16:56:35","14-10-2024 16:49=
:26","14-10-2024 17:01:56","Grid outage site went down because Gen stopped =
due to diesel filter cartridge does not let fuel through// He bypass diesel=
 filter cartridge and Gen manually started(replaced ongoing)","Fanda Brice"=
,"Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Fuel Pump","Grid out=
age site went down because Gen stopped due to diesel filter cartridge does =
not let fuel through// He bypass diesel filter cartridge and Gen manually s=
tarted(replaced ongoing)","landry.etame@ihstowers.com","430","14-10-2024 16=
:56:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003321987","A=
KONGO","","14-10-2024 16:56:25","14-10-2024 16:29:02","14-10-2024 16:35:57"=
,"active//No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rodr=
igue (655102999)from Huawei is informed. Repetitive issue","Fanda Brice","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","active//No power issue on site Ubaie=3D52,5V site on Gen. The Tx =
FME Rodrigue (655102999)from Huawei is informed. Repetitive issue","kouoh.j=
ean@ihstowers.com","1644","14-10-2024 16:56:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0003321838","ARMP",""=
,"14-10-2024 16:30:40","14-10-2024 16:21:10","14-10-2024 17:59:24","Cascade=
d Incident from TTO3193193","","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Site went down  due to 01/04 Rectifier Faulty on Site /=
/ he remove the faulty Rectifier and Site is on 03 Rectifier  ","system","5=
70","14-10-2024 16:30:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003321833","D=
ragage","IHS_YND_704, IHS_YND_208","14-10-2024 16:29:29","14-10-2024 16:21:=
10","14-10-2024 17:59:24","Site went down  due to 01/04 Rectifier Faulty on=
 Site // he remove the faulty Rectifier and Site is on 03 Rectifier  ","Mbo=
ua Thierry","Equipment Repair","Passive","Rectifier","Rectifier Module","Si=
te went down  due to 01/04 Rectifier Faulty on Site // he remove the faulty=
 Rectifier and Site is on 03 Rectifier  ","kouoh.jean@ihstowers.com","500",=
"14-10-2024 16:29:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0003321677","M=
ontesquieux","","14-10-2024 16:01:53","14-10-2024 15:29:35","14-10-2024 16:=
21:35","Grid fluctuation, site went down before Gen start and stopped due t=
o Gid bad voltage no RCP on site// he bypass the Grid and Gen manually star=
ted","Paul BIBOUM","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","Grid fluctuation, site went down before Gen start and sto=
pped due to Gid bad voltage no RCP on site// he bypass the Grid and Gen man=
ually started","kouoh.jean@ihstowers.com","1938","14-10-2024 16:01:53","Sag=
emcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0003321586","Jou=
vence Mbenda","","14-10-2024 15:47:56","14-10-2024 15:42:49","14-10-2024 16=
:19:49","Grid Outage, site went down because Gen stopped with ""high temp""=
 alarm// He added water and started Gen manualy","Hyemafo Gildas","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid Outage, site went down because Gen stopped with ""high temp"" ala=
rm// He added water and started Gen manualy","landry.etame@ihstowers.com","=
308","14-10-2024 15:47:56","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003321449","Odz=
a II","","14-10-2024 15:32:47","14-10-2024 15:26:33","14-10-2024 15:39:11",=
"Grid Outage, site went down because Gen stopped with ""high temp"" alarm//=
 He added water and started Gen manualy","Albran Byorel","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid=
 Outage, site went down because Gen stopped with ""high temp"" alarm// He a=
dded water and started Gen manualy","landry.etame@ihstowers.com","430","14-=
10-2024 15:32:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003321258","N=
omayos-IHS","","14-10-2024 14:54:51","14-10-2024 14:46:31","14-10-2024 15:1=
1:45","site went down because 02/04 rectifier dysfonction  due to increased=
 the load // He reset the rectifier ","Fanda Brice","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","site went down because 02/04 rectifie=
r dysfonction  due to increased the load // He reset the rectifier ","kouoh=
.jean@ihstowers.com","501","14-10-2024 14:54:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003321149","Anguissa=
 New","","14-10-2024 14:38:20","14-10-2024 14:28:58","14-10-2024 15:12:14",=
"Cascaded Incident from TTO3192432","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid OUTAGE no space to deploy MDG=
 // Grid return","system","562","14-10-2024 14:38:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003321141","L=
abogenie","IHS_YND_568","14-10-2024 14:36:16","14-10-2024 14:28:58","14-10-=
2024 15:12:14","Grid OUTAGE no space to deploy MDG // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid OUTAGE =
no space to deploy MDG // Grid return","kouoh.jean@ihstowers.com","439","14=
-10-2024 14:36:16","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003321134","NYO=
M FACE MAETUR","","14-10-2024 14:35:26","14-10-2024 12:48:17","14-10-2024 1=
4:12:57"," Site down due to work Patrick Bobga (675242905) From Loumad ,( S=
WAP of Battery Backup )//end of work","Fabrice Pouakam","Equipment Replacem=
ent","Passive","Planned Activity","Planned Activity - Passive","Site down d=
ue to work Patrick Bobga (675242905) From Loumad ,( SWAP of Battery Backup =
)//end of work","kombi.samuel@ihstowers.com","6430","14-10-2024 14:35:26","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0003321100","B=
astos Bir","","14-10-2024 14:31:30","14-10-2024 16:21:10","14-10-2024 17:59=
:24","Active//No power issue, site is on Grid with Ubaie=3D54,5 V  The TX F=
ME Eloundou Bertrant  (693212405)  from Huawei is informed","Mboua Thierry"=
,"Cascade Outage","Passive","Cascade Passive","Cascade Passive","Active//No=
 power issue, site is on Grid with Ubaie=3D54,5 V  The TX FME Eloundou Bert=
rant  (693212405)  from Huawei is informed","kouoh.jean@ihstowers.com","587=
1","14-10-2024 14:31:30","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0003320930","Mvo=
g-Manga","","14-10-2024 13:57:49","14-10-2024 13:53:43","14-10-2024 13:59:2=
1"," Site down due to work of Albran, replacement of Distribution terminal =
block//end of work","Albran Byorel","Installation Activity","Passive","Plan=
ned Activity","Installation Activity","Site down due to work Albran, replac=
ement of Distribution terminal block//end of work","emmanuel.ghani@ihstower=
s.com","248","14-10-2024 13:57:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003320839","E=
kounou","","14-10-2024 13:49:32","14-10-2024 13:45:27","14-10-2024 14:02:19=
","grid outage, site down before gen start due to poor backup//gen started"=
,"Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Battery Low","grid outage, site down before gen start due to poor backu=
p//gen started","joelle.ekessi@ihstowers.com","246","14-10-2024 13:49:32","=
Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003320659","Bas=
tos Amb Coree","","14-10-2024 13:17:55","14-10-2024 13:16:51","14-10-2024 1=
3:18:26","Grid OUTAGE no space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid OUTAGE no spa=
ce to deploy MDG // Grid return","emmanuel.ghani@ihstowers.com","65","14-10=
-2024 13:17:55","Sagemcom CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0003320563","Mba=
nkomo CAF","","14-10-2024 13:00:39","14-10-2024 12:54:26","14-10-2024 13:15=
:55","Site went down due to work by Brice Fanda (657108549)  /Sagemcom is w=
orking on site (PM works) // End of work","Fanda Brice","Installation Activ=
ity","Passive","Planned Activity","Installation Activity","Site went down d=
ue to work by Brice Fanda (657108549)  /Sagemcom is working on site (PM wor=
ks) // End of work","emmanuel.ghani@ihstowers.com","374","14-10-2024 13:00:=
39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0003320493","ARMP",""=
,"14-10-2024 12:46:00","14-10-2024 12:39:20","14-10-2024 12:49:47","Cascade=
d Incident from TTO3191697","","Cascade Outage","Active","Cascade Active","=
Cascade Active","Active//No power issue, site is on Grid with Ubaie=3D55,9 =
V  The TX FME Eloundou Bertrant  (693212405)  from Huawei is informed,Site =
up 12:49 PM","system","400","14-10-2024 12:46:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003320483","D=
ragage","IHS_YND_208","14-10-2024 12:43:31","14-10-2024 12:39:20","14-10-20=
24 13:26:51","Active//No power issue, site is on Grid with Ubaie=3D55,9 V  =
The TX FME Eloundou Bertrant  (693212405)  from Huawei is informed,Site up =
12:49 PM","Mboua Thierry","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Active//No power issue, site is on Gr=
id with Ubaie=3D55,9 V  The TX FME Eloundou Bertrant  (693212405)  from Hua=
wei is informed,Site up 12:49 PM","joelle.ekessi@ihstowers.com","252","14-1=
0-2024 12:43:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003320300","N=
kozoa","","14-10-2024 12:14:44","14-10-2024 12:10:29","14-10-2024 12:29:13"=
,"Site went down due to work by Fabrice (657108613)  /Sagemcom is working o=
n site (he changed DC box) // End of work","Fabrice Pouakam","Installation =
Activity","Passive","Planned Activity","Installation Activity","Site went d=
own due to work by Fabrice (657108613)  /Sagemcom is working on site (he ch=
anged DC box) // End of work","joelle.ekessi@ihstowers.com","257","14-10-20=
24 12:14:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0003320071","S=
hell-Nsimeyong","","14-10-2024 11:39:57","14-10-2024 11:34:52","14-10-2024 =
11:40:58","Site went down due to work: Charlie Kenfack /699882672/From  Pro=
 services  working on site //  End of work","MINKA NICOLAS","Installation A=
ctivity","Passive","Planned Activity","Installation Activity","Site went do=
wn due to work: Charlie Kenfack /699882672/From  Pro services  working on s=
ite //  End of work","joelle.ekessi@ihstowers.com","306","14-10-2024 11:39:=
57","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0003319723","Av =
Kennedy","","14-10-2024 10:32:56","14-10-2024 10:31:42","14-10-2024 13:48:2=
4","Grid OUTAGE no space to deploy MDG//Grid return","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","Grid OUTAGE no space to de=
ploy MDG//Grid return","emmanuel.ghani@ihstowers.com","75","14-10-2024 10:3=
2:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003319721","N=
kolfoulou","","14-10-2024 10:31:58","14-10-2024 10:29:54","14-10-2024 10:32=
:09","Grid outage, site went down before gen start due to poor battery back=
up // Gen started automatically","Siligap Boris","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen started automatically=
","joelle.ekessi@ihstowers.com","125","14-10-2024 10:31:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003319711","E=
bogo","","14-10-2024 10:30:36","14-10-2024 10:28:33","14-10-2024 10:31:45",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started automatically","Siligap Boris","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen started automatically","jo=
elle.ekessi@ihstowers.com","124","14-10-2024 10:30:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0003319665","E=
toug ebe Meweulo","","14-10-2024 10:21:34","14-10-2024 10:18:30","14-10-202=
4 10:48:27","Grid outage ,Site went down because Gen CB (32A) disjunted //H=
e reamed CB ,site on gen","Hyemafo Gildas","Equipment Repair","Passive","Co=
ntrol Panel","Circuit Breaker Tripped","Grid outage ,Site went down because=
 Gen CB (32A) disjunted //He reamed CB ,site on gen","joelle.ekessi@ihstowe=
rs.com","185","14-10-2024 10:21:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003319484","E=
kie-Elegance","","14-10-2024 09:54:31","14-10-2024 09:51:27","14-10-2024 11=
:26:09","Grid Outage// MDG 20Kva deployed","Albran Byorel","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid Outage// MDG 20Kva=
 deployed","joelle.ekessi@ihstowers.com","185","14-10-2024 09:54:31","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0003319415","N=
kolkoumou OCM","","14-10-2024 09:43:28","14-10-2024 09:35:24","14-10-2024 1=
3:20:49","No power issue on site ,site on Grid with Ubaie=3D54,5 V he Tx FM=
E Mouahamadou  (691144435) of Huawei is informed, notice that disjunction o=
f CB in BTS Ocm","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite ,site on Grid with Ubaie=3D54,5 V he Tx FME Mouahamadou  (691144435) of=
 Huawei is informed, notice that disjunction of CB in BTS Ocm","joelle.ekes=
si@ihstowers.com","485","14-10-2024 09:43:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003319348","I=
mm-Olympique","","14-10-2024 09:36:41","14-10-2024 09:34:37","14-10-2024 10=
:08:37","grid outage,gen failed to start due to power cable of gen stolen s=
ince//he started the gen with another power cable","Paul BIBOUM","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage,gen faile=
d to start due to power cable of gen stolen since//he started the gen with =
another power cable","joelle.ekessi@ihstowers.com","124","14-10-2024 09:36:=
41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_036","NOCINC0003319143","Acropole=
","","14-10-2024 08:58:00","14-10-2024 08:54:24","14-10-2024 09:34:08","Cas=
caded Incident from TTO3190227","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid fluctuation, site went down becau=
se gen failed to start due grid bad voltage//We bypass grid and  gen manual=
ly started","system","216","14-10-2024 08:58:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_021","NOCINC0003319136","C-Suprem=
e","","14-10-2024 08:55:41","14-10-2024 08:51:37","14-10-2024 09:00:30","Ca=
scaded Incident from TTO3190215","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Grid outage, Site went down because Gen failed to =
start  with  Alarm""failed to start""//he resert Gen card and started Gen",=
"system","244","14-10-2024 08:55:41","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0003319135","EBO=
M","IHS_YND_036","14-10-2024 08:55:36","14-10-2024 08:54:24","14-10-2024 09=
:34:26","grid fluctuation, site went down because gen failed to start due g=
rid bad voltage//We bypass grid and  gen manually started","Hyemafo Gildas"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
grid fluctuation, site went down because gen failed to start due grid bad v=
oltage//We bypass grid and  gen manually started","emmanuel.ghani@ihstowers=
.com","73","14-10-2024 08:55:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0003319132","M=
vog Mbi New","IHS_YND_021","14-10-2024 08:54:42","14-10-2024 08:51:37","14-=
10-2024 09:00:30","Grid outage, Site went down because Gen failed to start =
 with  Alarm""failed to start""//he resert Gen card and started Gen","MINKA=
 NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage, Site went down because Gen failed to start  with  Alarm""failed=
 to start""//he resert Gen card and started Gen","joelle.ekessi@ihstowers.c=
om","185","14-10-2024 08:54:42","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0003318795","Men=
dong NB","","14-10-2024 07:47:34","14-10-2024 07:45:29","14-10-2024 15:14:4=
1","Grid OUTAGE no space to deploy MDG // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid OUTAGE no space to =
deploy MDG // Grid return","emmanuel.ghani@ihstowers.com","126","14-10-2024=
 07:47:34","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0003318075","OTE=
LE MTN","","14-10-2024 04:27:04","14-10-2024 04:18:54","14-10-2024 04:32:30=
"," Site went down because 1/3 rectifiers faulty// He replaced rectifier fa=
ulty","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule"," Site went down because 1/3 rectifiers faulty// He replaced rectifier=
 faulty","olivier.kwedi@ihstowers.com","491","14-10-2024 04:27:04","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0003317950","C=
omplexe-BEAC","","14-10-2024 03:34:27","14-10-2024 03:31:22","14-10-2024 04=
:06:25","Grid outage, site went down because Gen ran untill fuel shortage//=
 Refueling Done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down because Gen ran untill fuel shortage// =
Refueling Done","dorothy.djantio@ihstowers.com","186","14-10-2024 03:34:27"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003317900","Bas=
tos Amb Coree","","14-10-2024 03:17:07","14-10-2024 03:10:56","14-10-2024 0=
6:12:54","Grid OUTAGE no space to deploy MDG // Grid return ","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid OUTAGE no sp=
ace to deploy MDG // Grid return ","olivier.kwedi@ihstowers.com","372","14-=
10-2024 03:17:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003317793","N=
kozoa","","14-10-2024 02:51:30","14-10-2024 02:43:24","14-10-2024 04:21:20"=
,"Site went down because CB(125A) and CB(63A) who feeds equipments OCM  bur=
ned in DC BOX// He make a bridge(CB to be replace)","Fabrice Pouakam","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Is=
sue","Site went down because CB(125A) and CB(63A) who feeds equipments OCM =
 burned in DC BOX// He make a bridge(CB to be replace)","dorothy.djantio@ih=
stowers.com","487","14-10-2024 02:51:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003317655","E=
kie-Elegance","","14-10-2024 02:12:01","14-10-2024 02:06:56","14-10-2024 04=
:52:07","Grid Outage// MDG 20Kva deployed","Albran Byorel","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid Outage// MDG 20Kva=
 deployed","dorothy.djantio@ihstowers.com","306","14-10-2024 02:12:01","Sag=
emcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003317642","Mok=
olo Yaounde","","14-10-2024 02:07:02","14-10-2024 02:02:53","14-10-2024 06:=
14:40","Grid OUTAGE no space to deploy MDG // Grid return ","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid OUTAGE no spac=
e to deploy MDG // Grid return ","olivier.kwedi@ihstowers.com","250","14-10=
-2024 02:07:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0003317622","T=
SINGA VILLAGE 2","","14-10-2024 02:00:02","14-10-2024 01:55:56","14-10-2024=
 04:21:04","Hybrid Gen: Site went down because Gen started and stooped due =
to water infiltration in the tank//  He purged the tank, site on gen","Delo=
r Telezing","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue=
 - Water In The Fuel","Hybrid Gen: Site went down because Gen started and s=
tooped due to water infiltration in the tank//  He purged the tank, site on=
 gen","dorothy.djantio@ihstowers.com","247","14-10-2024 02:00:02","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0003317479","T=
SINGA VILLAGE 2","","14-10-2024 00:59:12","14-10-2024 00:55:08","14-10-2024=
 01:28:37","Hybrid Gen: Site went down because controler of Huawei Power ca=
binet disfunctionned// He reset it and started Gen manualy","Delor Telezing=
","Equipment Repair","Passive","Rectifier","Rectifier - Controller Failure"=
,"Hybrid Gen: Site went down because controler of Huawei Power cabinet disf=
unctionned// He reset it and started Gen manualy","dorothy.djantio@ihstower=
s.com","245","14-10-2024 00:59:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003317431","Afanoya"=
,"","14-10-2024 00:40:51","14-10-2024 00:30:06","14-10-2024 01:04:11","Casc=
aded Incident from TTO3188200","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // gen start automatically","system","645=
","14-10-2024 00:40:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003317430","MBALNGON=
G LYCEE","","14-10-2024 00:40:51","14-10-2024 00:30:06","14-10-2024 01:04:1=
1","Cascaded Incident from TTO3188200","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // gen start automatically","system"=
,"645","14-10-2024 00:40:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003317429","ELOUMDEM=
 CARRIERE","","14-10-2024 00:40:51","14-10-2024 00:30:06","14-10-2024 01:04=
:11","Cascaded Incident from TTO3188200","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen start automatically","syste=
m","645","14-10-2024 00:40:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003317407","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","14-10-2024 00:33:48","14-10-=
2024 00:30:06","14-10-2024 01:04:11","Grid outage, site went down before ge=
n start due to poor battery backup // gen start automatically","Hyemafo Gil=
das","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Grid outage, site went down before gen start due to poor battery back=
up // gen start automatically","dorothy.djantio@ihstowers.com","608","14-10=
-2024 00:33:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003317114","M=
fou EPC","","13-10-2024 22:52:29","13-10-2024 22:48:24","13-10-2024 23:14:3=
9","grid fluctuation, site went down because gen started and stopped due gr=
id bad voltage no rcp on site// He bypassed Grid and Gen manually started",=
"Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Co=
ntroller Faulty","grid fluctuation, site went down because gen started and =
stopped due grid bad voltage no rcp on site// He bypassed Grid and Gen manu=
ally started","dorothy.djantio@ihstowers.com","246","13-10-2024 22:52:29","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003317066","Lobo OCM=
","","13-10-2024 22:40:50","13-10-2024 22:27:00","15-10-2024 14:15:12","Cas=
caded Incident from TTO3187739","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","FME was on site and noticed=
 that engine bloc is faulty and reported that he will go to the site MOM ta=
ke another engine to restore the site","system","830","13-10-2024 22:40:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003317060","NKO=
MEKUI OCM","IHS_YND_341, IHS_YND_713","13-10-2024 22:38:03","13-10-2024 22:=
27:00","15-10-2024 14:15:12","site went down because  that engine bloc of G=
en is faulty// He replaced the engine bloc of Gen","TIENTCHEU NZETCHIEU GAE=
L","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","site =
went down because  that engine bloc of Gen is faulty// He replaced the engi=
ne bloc of Gen","olivier.kwedi@ihstowers.com","729","13-10-2024 22:38:03","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003316963","Eseka To=
wn","","13-10-2024 22:08:00","13-10-2024 21:58:32","14-10-2024 00:00:41","C=
ascaded Incident from TTO3187578","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site was on Gen due to Grid outage=
, site went down because Gen stopped due to Gen contactor disfunction and s=
olenoid faulty// He blocked Gen contactor, site on Gen","system","568","13-=
10-2024 22:08:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003316947","Song-bon=
g","","13-10-2024 22:03:00","13-10-2024 21:58:32","14-10-2024 00:00:41","Ca=
scaded Incident from TTO3187578","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site was on Gen due to Grid outage,=
 site went down because Gen stopped due to Gen contactor disfunction and so=
lenoid faulty// He blocked Gen contactor, site on Gen","system","268","13-1=
0-2024 22:03:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003316945","E=
seka OCM","IHS_YND_378, IHS_YND_453","13-10-2024 22:01:37","13-10-2024 21:5=
8:32","14-10-2024 00:00:41","Site was on Gen due to Grid outage, site went =
down because Gen stopped due to Gen contactor disfunction and solenoid faul=
ty// He blocked Gen contactor, site on Gen","Kemeni Franklin","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Solenoid Coil","Site was on Gen due to G=
rid outage, site went down because Gen stopped due to Gen contactor disfunc=
tion and solenoid faulty// He blocked Gen contactor, site on Gen","alexandr=
e.kamal@ihstowers.com","185","13-10-2024 22:01:37","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003316767","Com=
plex Beac II","","13-10-2024 21:25:23","13-10-2024 21:22:12","13-10-2024 21=
:38:56","grid outage, site went down because gen failed to start due to gen=
 card faulty // Gen manually started","Albran Byorel","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","grid outage, site went down beca=
use gen failed to start due to gen card faulty // Gen manually started","ka=
mga.virgile@ihstowers.com","191","13-10-2024 21:25:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003316763","MBALNGON=
G LYCEE","","13-10-2024 21:24:31","13-10-2024 21:10:59","13-10-2024 21:36:4=
2","Cascaded Incident from TTO3187336","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen manually started","system","8=
12","13-10-2024 21:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003316764","Afanoya"=
,"","13-10-2024 21:24:31","13-10-2024 21:10:59","13-10-2024 21:36:42","Casc=
aded Incident from TTO3187336","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Gen manually started","system","812","=
13-10-2024 21:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003316762","ELOUMDEM=
 CARRIERE","","13-10-2024 21:24:30","13-10-2024 21:10:59","13-10-2024 21:36=
:42","Cascaded Incident from TTO3187336","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen manually started","system",=
"811","13-10-2024 21:24:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003316749","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","13-10-2024 21:20:54","13-10-=
2024 21:10:59","13-10-2024 21:36:42","Grid outage, site went down before ge=
n start due to poor battery backup // Gen manually started","Hyemafo Gildas=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen manually started","alexandre.kamal@ihstowers.com","596","13-10-2024 =
21:20:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0003316676","Marche O=
dza","","13-10-2024 21:05:50","13-10-2024 20:47:28","13-10-2024 21:08:21","=
Cascaded Incident from TTO3187212","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, site went down because=
 gen start and stoppen with Alarm ""Low oil pressure"" //He reset gen card =
, site on gen","system","1102","13-10-2024 21:05:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0003316675","Mvog-Man=
ga","","13-10-2024 21:05:50","13-10-2024 20:47:28","13-10-2024 21:08:21","C=
ascaded Incident from TTO3187212","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, site went down because =
gen start and stoppen with Alarm ""Low oil pressure"" //He reset gen card ,=
 site on gen","system","1102","13-10-2024 21:05:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0003316650","O=
dza","IHS_YND_254, IHS_YND_580","13-10-2024 21:04:33","13-10-2024 20:47:28"=
,"13-10-2024 21:08:21","grid outage, site went down because gen start and s=
toppen with Alarm ""Low oil pressure"" //He reset gen card , site on grid "=
,"Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","grid outage, site went down because gen start and stoppen with Alarm =
""Low oil pressure"" //He reset gen card , site on gen","alexandre.kamal@ih=
stowers.com","1026","13-10-2024 21:04:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_185","IHS_YND_378","NOCINC0003316595","E=
seka Town","","13-10-2024 20:57:42","13-10-2024 18:07:07","13-10-2024 18:17=
:30","Active: No power issue, site is on grid with Ubaie=3D53V, Etienne(695=
033981) from Huawei is informed","Kemeni Franklin","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No p=
ower issue, site is on grid with Ubaie=3D53V, Etienne(695033981) from Huawe=
i is informed","alexandre.kamal@ihstowers.com","10235","13-10-2024 20:57:42=
","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003316391","MBI=
MBIM","","13-10-2024 20:17:23","13-10-2024 20:02:04","13-10-2024 21:28:02",=
"Site went down because Gen started and stopped due to water infiltration i=
n the tank//  He purged the tank, site on gen","Parker Tchoup","Fuel Outage=
 (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","S=
ite went down because Gen started and stopped due to water infiltration in =
the tank//  He purged the tank, site on gen","kamga.virgile@ihstowers.com",=
"920","13-10-2024 20:17:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003316078","N=
gouetou","","13-10-2024 19:20:40","13-10-2024 19:09:35","13-10-2024 23:10:1=
9","No power issue on site ,site on Gen with Ubaie=3D52V, Tx Fme Gregoire( =
652070658)From Huawei is informed and Up 07:20 PM","Parker Tchoup","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site ,site on Gen with Ubaie=3D52V, Tx Fme Gregoire( =
652070658)From Huawei is informed and Up 07:20 PM","alexandre.kamal@ihstowe=
rs.com","666","13-10-2024 19:20:40","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003316070","ODZ=
A MINKAN EDIBI ASSI","","13-10-2024 19:18:34","13-10-2024 15:50:14","13-10-=
2024 17:30:09","site on gen due to grid outage, site went down because disj=
unction Cb(80A) in PWC // he make bridge  with another CB(80A), site on gen=
","Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Circuit Breaker Issue","site on gen due to grid outage, site went down=
 because disjunction Cb(80A) in PWC // he make bridge  with another CB(80A)=
, site on gen","kamga.virgile@ihstowers.com","12501","13-10-2024 19:18:34",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003315960","M=
vog-Manga","","13-10-2024 18:50:45","13-10-2024 18:42:38","13-10-2024 19:17=
:12","Grid outage, site went down before gen start due to poor battery back=
up // Gen manually started","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen manually started","alexand=
re.kamal@ihstowers.com","488","13-10-2024 18:50:45","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003315814","NTU=
I TOWN","","13-10-2024 18:26:26","13-10-2024 18:10:18","13-10-2024 18:20:07=
","Active: No power issue, site is on grid with Ubaie=3D53V, Gregoire (6520=
70658) from Huawei is informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No powe=
r issue, site is on grid with Ubaie=3D53V, Gregoire (652070658) from Huawei=
 is informed","kamga.virgile@ihstowers.com","969","13-10-2024 18:26:26","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003315702","ODZ=
A CITE MBIA","","13-10-2024 18:07:10","13-10-2024 17:48:58","13-10-2024 18:=
28:28","Grid outage,gen failed to start due to no automatism on site//Gen m=
anually started","Albran Byorel","Equipment Repair","Passive","Control Pane=
l","ATS-AMF Issue","Grid outage,gen failed to start due to no automatism on=
 site//Gen manually started","kamga.virgile@ihstowers.com","1092","13-10-20=
24 18:07:10","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0003315645","Man=
guiers Dispensaire","","13-10-2024 17:52:07","13-10-2024 17:38:56","13-10-2=
024 18:05:09","Site on DG due to grid outage, site went down due to dysfunc=
tionning of rectifiers // He reset rectifiers , site on gen","Fabrice Pouak=
am","Equipment Repair","Passive","Rectifier","Rectifier Module","Site on DG=
 due to grid outage, site went down due to dysfunctionning of rectifiers //=
 He reset rectifiers , site on gen","kamga.virgile@ihstowers.com","792","13=
-10-2024 17:52:07","Sagemcom CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0003315591","RUE=
 FOE","","13-10-2024 17:39:01","13-10-2024 17:12:33","13-10-2024 19:10:14",=
"Grid outage, Site went down because Gen ran until fuel shortage// Refuelin=
g done","Delor Telezing","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage, Site went down because Gen ran until fuel shortage// Refueling=
 done","kamga.virgile@ihstowers.com","1588","13-10-2024 17:39:01","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0003315437","Aka=
k-Nkozoa-MTN-IHS","","13-10-2024 17:03:08","13-10-2024 16:51:56","13-10-202=
4 17:25:45","site went down because gen failed to start due to grid bad vol=
tage// Gen manually started","Fabrice Pouakam","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","site went down because gen fa=
iled to start due to grid bad voltage// Gen manually started","kamga.virgil=
e@ihstowers.com","674","13-10-2024 17:03:08","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003315412","Com=
plex Beac II","","13-10-2024 16:57:52","13-10-2024 16:32:40","13-10-2024 16=
:54:31","grid outage, site went down because gen failed to start due to gen=
 card faulty // Gen manually started","Albran Byorel","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","grid outage, site went down beca=
use gen failed to start due to gen card faulty // Gen manually started","ka=
mga.virgile@ihstowers.com","1512","13-10-2024 16:57:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003315378","E=
lig-Edzoa","","13-10-2024 16:48:31","13-10-2024 16:43:27","13-10-2024 18:46=
:23","Grid outage// MDG 20KVA has deploy","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid outage// MDG 20KVA has deploy","=
alexandre.kamal@ihstowers.com","305","13-10-2024 16:48:31","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003315294","NKO=
MEKUI OCM","","13-10-2024 16:34:44","13-10-2024 16:28:35","13-10-2024 16:36=
:35","Grid outage, site went down before gen start due to poor battery back=
up // Gen started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen started","kamga.virgile@=
ihstowers.com","370","13-10-2024 16:34:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003315252","F=
ebe Village","","13-10-2024 16:22:45","13-10-2024 16:17:40","13-10-2024 16:=
29:55","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automatically","Mboua Thierry","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"alexandre.kamal@ihstowers.com","306","13-10-2024 16:22:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003315241","Nsimalen=
 OCM","","13-10-2024 16:21:10","13-10-2024 16:16:59","13-10-2024 16:49:04",=
"Cascaded Incident from TTO3185545","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e Gen started and stopped due to Under frequency alarm// he reset the Gen c=
ard, grid return","system","251","13-10-2024 16:21:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003315233","N=
kolda","IHS_YND_327","13-10-2024 16:20:05","13-10-2024 16:16:59","13-10-202=
4 16:49:04","Grid outage, site went down because Gen started and stopped du=
e to Under frequency alarm// he reset the Gen card, grid return","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
outage, site went down because Gen started and stopped due to Under frequen=
cy alarm// he reset the Gen card, grid return","alexandre.kamal@ihstowers.c=
om","186","13-10-2024 16:20:05","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0003315155","Tou=
ring Club International","","13-10-2024 16:04:56","13-10-2024 15:49:14","13=
-10-2024 16:18:21","Grid outage, site went down because Gen started and sto=
pped due to Under under voltage alarm// he reset the Gen card and Gen manua=
lly started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG =
- Control Panel","Grid outage, site went down because Gen started and stopp=
ed due to Under under voltage alarm// he reset the Gen card and Gen manuall=
y started","kamga.virgile@ihstowers.com","943","13-10-2024 16:04:56","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003315108","Eseka To=
wn","","13-10-2024 15:58:11","13-10-2024 15:44:23","13-10-2024 18:06:20","C=
ascaded Incident from TTO3185400","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, site went down becaus=
e gen start and stoppen with Alarm Emergency stop due to lightning and DG c=
ard damaged  // He reset gen card and gen manually started","system","828",=
"13-10-2024 15:58:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003315109","Song-bon=
g","","13-10-2024 15:58:11","13-10-2024 15:44:23","13-10-2024 18:06:20","Ca=
scaded Incident from TTO3185400","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, site went down because=
 gen start and stoppen with Alarm Emergency stop due to lightning and DG ca=
rd damaged  // He reset gen card and gen manually started","system","828","=
13-10-2024 15:58:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0003315105","E=
seka OCM","IHS_YND_378, IHS_YND_453","13-10-2024 15:57:27","13-10-2024 15:4=
4:23","13-10-2024 18:06:20","grid outage, site went down because gen start =
and stoppen with Alarm Emergency stop due to lightning and DG card damaged =
 // He reset gen card and gen manually started","Kemeni Franklin","Force Ma=
jeure","Natural Disaster","Thunderstrike","Equipment Damaged","grid outage,=
 site went down because gen start and stoppen with Alarm Emergency stop due=
 to lightning and DG card damaged  // He reset gen card and gen manually st=
arted","alexandre.kamal@ihstowers.com","785","13-10-2024 15:57:27","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003314971","O=
lembe-Terminus","","13-10-2024 15:34:32","13-10-2024 15:24:59","13-10-2024 =
23:00:24","Active: no power issue, site is on grid with Ubaie=3D53V, SYMPHO=
RIEN (650257151) from Huawei is informed","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: no power issue, site is on grid with Ubaie=3D53V, SYMPHORIEN (65025715=
1) from Huawei is informed","alexandre.kamal@ihstowers.com","574","13-10-20=
24 15:34:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003314883","Afanoya"=
,"","13-10-2024 15:13:41","13-10-2024 14:52:13","13-10-2024 16:31:00","Casc=
aded Incident from TTO3185129","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Gen manually started","system","1288",=
"13-10-2024 15:13:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003314882","MBALNGON=
G LYCEE","","13-10-2024 15:13:40","13-10-2024 14:52:13","13-10-2024 16:31:0=
0","Cascaded Incident from TTO3185129","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen manually started","system","1=
287","13-10-2024 15:13:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003314881","ELOUMDEM=
 CARRIERE","","13-10-2024 15:13:40","13-10-2024 14:52:13","13-10-2024 16:31=
:00","Cascaded Incident from TTO3185129","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen manually started","system",=
"1287","13-10-2024 15:13:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003314851","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","13-10-2024 15:04:17","13-10-=
2024 14:52:13","13-10-2024 16:31:00","Grid outage, site went down before ge=
n start due to poor battery backup // Gen manually started","Hyemafo Gildas=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen manually started","alexandre.kamal@ihstowers.com","725","13-10-2024 =
15:04:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003314775","C=
rf-Nsam","","13-10-2024 14:44:37","13-10-2024 14:37:26","13-10-2024 15:29:1=
6","grid outage, site went down because gen start and stoppen due to gen un=
der voltage alarm // he balanced the loads, site on grid","MINKA NICOLAS","=
Equipment Repair","Passive","ACDG Gen","ACDG - Under Voltage","grid outage,=
 site went down because gen start and stoppen due to gen under voltage alar=
m // he balanced the loads, site on grid","alexandre.kamal@ihstowers.com","=
431","13-10-2024 14:44:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003314772","Eto koss=
 Yde","","13-10-2024 14:44:10","13-10-2024 14:36:09","13-10-2024 17:15:04",=
"Cascaded Incident from TTO3184980","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down due to 03/10 rectifie=
rs faulty // He changed 03 rectifiers, site on grid","system","481","13-10-=
2024 14:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003314773","ELOUMDEM=
 CARRIERE 2","","13-10-2024 14:44:10","13-10-2024 14:36:09","13-10-2024 17:=
15:04","Cascaded Incident from TTO3184980","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down due to 03/10 r=
ectifiers faulty // He changed 03 rectifiers, site on grid","system","481",=
"13-10-2024 14:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0003314770","Bastos B=
ir","","13-10-2024 14:44:00","13-10-2024 14:37:33","13-10-2024 14:47:30","C=
ascaded Incident from TTO3184984","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active: No power issue, site is on grid=
 with Ubaie=3D53V, Eloundou(652586578) from Huawei is informed ","system","=
387","13-10-2024 14:44:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0003314771","ARMP",""=
,"13-10-2024 14:44:00","13-10-2024 14:37:33","13-10-2024 14:47:30","Cascade=
d Incident from TTO3184984","","Cascade Outage","Active","Cascade Active","=
Cascade Active","Active: No power issue, site is on grid with Ubaie=3D53V, =
Eloundou(652586578) from Huawei is informed ","system","387","13-10-2024 14=
:44:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003314767","D=
ragage","IHS_YND_704, IHS_YND_208","13-10-2024 14:42:59","13-10-2024 14:37:=
33","13-10-2024 14:47:30","Active: No power issue, site is on grid with Uba=
ie=3D53V, Eloundou(652586578) from Huawei is informed ","Mboua Thierry","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active: No power issue, site is on grid with Ubaie=3D53V, Eloundou=
(652586578) from Huawei is informed ","alexandre.kamal@ihstowers.com","327"=
,"13-10-2024 14:42:59","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003314763","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","13-10-2024 14:42:21","13-10-2024 14:34=
:04","13-10-2024 17:15:24","site went down due to 03/10 rectifiers faulty /=
/ He changed 03 rectifiers, site on grid","Fanda Brice","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","site went down due to 03/10 recti=
fiers faulty // He changed 03 rectifiers, site on grid","kamga.virgile@ihst=
owers.com","4810","13-10-2024 14:42:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003314749","E=
kie sud","","13-10-2024 14:39:55","13-10-2024 14:27:51","13-10-2024 15:10:5=
9","Grid outage, site went down because gen failed to start due to (hybrid =
system and automatism) dysfunctioning// Gen manually started","Albran Byore=
l","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outag=
e, site went down because gen failed to start due to (hybrid system and aut=
omatism) dysfunctioning// Gen manually started","alexandre.kamal@ihstowers.=
com","725","13-10-2024 14:39:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0003314088","C=
hapelle-Essos","","13-10-2024 13:06:07","13-10-2024 12:59:57","13-10-2024 1=
4:09:22","site went down due to Eneo contactor faulty// gen manually starte=
d","Delor Telezing","Equipment Repair","Passive","Control Panel","ATS-AMF I=
ssue","site went down due to Eneo contactor faulty// gen manually started",=
"kouoh.jean@ihstowers.com","371","13-10-2024 13:06:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003314060","M=
essa-Carriere OCM","","13-10-2024 12:57:34","13-10-2024 12:37:17","13-10-20=
24 12:57:45","Grid outage,no space to deploy a mobil Gen//Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age,no space to deploy a mobil Gen//Grid return","kouoh.jean@ihstowers.com"=
,"1218","13-10-2024 12:57:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003313918","N=
kolondom","","13-10-2024 12:26:45","13-10-2024 12:24:29","13-10-2024 12:26:=
51","Grid outage, site went down before gen start due to poor battery backu=
p // Grid power return","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Grid power return","kouoh.jean@i=
hstowers.com","137","13-10-2024 12:26:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003313747","MBALNGON=
G LYCEE","","13-10-2024 11:51:00","13-10-2024 11:20:25","13-10-2024 12:32:3=
9","Cascaded Incident from TTO3183723","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen manually started","system","1=
835","13-10-2024 11:51:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003313746","ELOUMDEM=
 CARRIERE","","13-10-2024 11:51:00","13-10-2024 11:20:25","13-10-2024 12:32=
:39","Cascaded Incident from TTO3183723","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen manually started","system",=
"1835","13-10-2024 11:51:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003313728","L=
abogenie","IHS_YND_568","13-10-2024 11:43:49","13-10-2024 11:35:33","13-10-=
2024 15:25:15","Grid outage,no space to deploy a mobil Gen // Grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage,no space to deploy a mobil Gen // Grid return","kouoh.jean@ihstower=
s.com","497","13-10-2024 11:43:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003313681","M=
vog-Manga","","13-10-2024 11:29:12","13-10-2024 11:19:05","13-10-2024 12:07=
:42","Grid outage, site went down before gen start due to poor battery back=
up // Gen manually started","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen manually started","kouoh.j=
ean@ihstowers.com","609","13-10-2024 11:29:12","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003313678","Aha=
la","IHS_YND_767, IHS_YND_765","13-10-2024 11:27:37","13-10-2024 11:20:25",=
"13-10-2024 12:32:39","Grid outage, site went down before gen start due to =
poor battery backup // Gen manually started","Hyemafo Gildas","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,=
 site went down before gen start due to poor battery backup // Gen manually=
 started","stephane.nkamwa@ihstowers.com","433","13-10-2024 11:27:37","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003313562","Lobo OCM=
","","13-10-2024 10:58:00","13-10-2024 10:51:24","13-10-2024 11:56:29","Cas=
caded Incident from TTO3183570","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Gen started","system","396"=
,"13-10-2024 10:58:00","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003313556","N=
KOMEKUI OCM","IHS_YND_341","13-10-2024 10:56:38","13-10-2024 10:51:24","13-=
10-2024 11:56:29","Grid outage, site went down before gen start due to poor=
 battery backup // Gen started","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before gen start due to poor battery backup // Gen started","k=
ouoh.jean@ihstowers.com","315","13-10-2024 10:56:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003313486","Crf Corn=
ier","","13-10-2024 10:44:53","13-10-2024 09:57:09","13-10-2024 10:47:09","=
Cascaded Incident from TTO3183457","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work the Rm W=
illy kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he c=
hanged the LVD) // End of work","system","2864","13-10-2024 10:44:53","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_065","NOCINC0003313485","Essos DC=
S","","13-10-2024 10:44:53","13-10-2024 09:57:09","13-10-2024 10:47:09","Ca=
scaded Incident from TTO3183457","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work the Rm Wi=
lly kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he ch=
anged the LVD) // End of work","system","2864","13-10-2024 10:44:53","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_097","NOCINC0003313484","Kondengu=
i MTN","","13-10-2024 10:44:52","13-10-2024 09:57:09","13-10-2024 10:47:09"=
,"Cascaded Incident from TTO3183457","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to work the Rm=
 Willy kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he=
 changed the LVD) // End of work","system","2863","13-10-2024 10:44:52","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0003313481","Mobil-Es=
sos","","13-10-2024 10:44:52","13-10-2024 09:57:09","13-10-2024 10:47:09","=
Cascaded Incident from TTO3183457","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work the Rm W=
illy kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he c=
hanged the LVD) // End of work","system","2863","13-10-2024 10:44:52","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_178","NOCINC0003313483","Emombo",=
"","13-10-2024 10:44:52","13-10-2024 09:57:09","13-10-2024 10:47:09","Casca=
ded Incident from TTO3183457","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to work the Rm Wil=
ly kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he cha=
nged the LVD) // End of work","system","2863","13-10-2024 10:44:52","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003313482","Anguissa=
 New","","13-10-2024 10:44:52","13-10-2024 09:57:09","13-10-2024 15:25:15",=
"Cascaded Incident from TTO3183457","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to work the Rm =
Willy kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he =
changed the LVD) // End of work","system","2863","13-10-2024 10:44:52","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_108","NOCINC0003313476","RUE FOE"=
,"","13-10-2024 10:44:51","13-10-2024 09:57:09","13-10-2024 10:47:09","Casc=
aded Incident from TTO3183457","Delor Telezing","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work the Rm Will=
y kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he chan=
ged the LVD) // End of work","system","2862","13-10-2024 10:44:51","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_113","NOCINC0003313480","Emombo 2=
","","13-10-2024 10:44:51","13-10-2024 09:57:09","13-10-2024 10:47:09","Cas=
caded Incident from TTO3183457","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work the Rm Will=
y kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he chan=
ged the LVD) // End of work","system","2862","13-10-2024 10:44:51","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_063","NOCINC0003313478","Av-Germa=
ine","","13-10-2024 10:44:51","13-10-2024 09:57:09","13-10-2024 10:47:09","=
Cascaded Incident from TTO3183457","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Site went down due to work the Rm Willy kamga (6=
56072630) and SS ihs Blaise /Sagemcom is working on site (he changed the LV=
D) // End of work","system","2862","13-10-2024 10:44:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_120","NOCINC0003313479","Sapeur M=
imboman","","13-10-2024 10:44:51","13-10-2024 09:57:09","13-10-2024 10:47:0=
9","Cascaded Incident from TTO3183457","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down due to work t=
he Rm Willy kamga (656072630) and SS ihs Blaise /Sagemcom is working on sit=
e (he changed the LVD) // End of work","system","2862","13-10-2024 10:44:51=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_189","NOCINC0003313477","Paradis =
Hotel","","13-10-2024 10:44:51","13-10-2024 09:57:09","13-10-2024 10:47:09"=
,"Cascaded Incident from TTO3183457","Siligap Boris","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to work the Rm=
 Willy kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he=
 changed the LVD) // End of work","system","2862","13-10-2024 10:44:51","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_122","NOCINC0003313475","Emombo E=
sssomba","","13-10-2024 10:44:50","13-10-2024 09:57:09","13-10-2024 10:47:0=
9","Cascaded Incident from TTO3183457","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down due to work t=
he Rm Willy kamga (656072630) and SS ihs Blaise /Sagemcom is working on sit=
e (he changed the LVD) // End of work","system","2861","13-10-2024 10:44:50=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_797","NOCINC0003313474","Messassi=
 Carrefourt","","13-10-2024 10:44:50","13-10-2024 09:57:09","13-10-2024 10:=
47:09","Cascaded Incident from TTO3183457","Delor Telezing","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down due to work=
 the Rm Willy kamga (656072630) and SS ihs Blaise /Sagemcom is working on s=
ite (he changed the LVD) // End of work","system","2861","13-10-2024 10:44:=
50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_180","NOCINC0003313473","Mimboman=
","","13-10-2024 10:44:50","13-10-2024 09:57:09","13-10-2024 10:47:09","Cas=
caded Incident from TTO3183457","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work the Rm W=
illy kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he c=
hanged the LVD) // End of work","system","2861","13-10-2024 10:44:50","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0003313471","OKOA Pea=
ge","","13-10-2024 10:44:50","13-10-2024 09:57:09","13-10-2024 10:47:09","C=
ascaded Incident from TTO3183457","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work the Rm Will=
y kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he chan=
ged the LVD) // End of work","system","2861","13-10-2024 10:44:50","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_111","NOCINC0003313472","Essos Ma=
rche","","13-10-2024 10:44:50","13-10-2024 09:57:09","13-10-2024 10:47:09",=
"Cascaded Incident from TTO3183457","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to work the Rm=
 Willy kamga (656072630) and SS ihs Blaise /Sagemcom is working on site (he=
 changed the LVD) // End of work","system","2861","13-10-2024 10:44:50","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0003313456","Cam=
p-Sonel","IHS_YND_330, IHS_YND_111, IHS_YND_180, IHS_YND_797, IHS_YND_122, =
IHS_YND_108, IHS_YND_189, IHS_YND_063, IHS_YND_120, IHS_YND_113, IHS_YND_10=
9, IHS_YND_568, IHS_YND_178, IHS_YND_097, IHS_YND_065, IHS_YND_566","13-10-=
2024 10:41:21","13-10-2024 09:57:09","13-10-2024 10:47:09","Site went down =
due to work the Rm Willy kamga (656072630) and SS ihs Blaise /Sagemcom is w=
orking on site (he changed the LVD & secure transmission) // End of work","=
Siligap Boris","Equipment Replacement","Passive","Planned Activity","Planne=
d Activity - Passive","Site went down due to work the Rm Willy kamga (65607=
2630) and SS ihs Blaise /Sagemcom is working on site (he changed the LVD & =
secure transmission) // End of work","stephane.nkamwa@ihstowers.com","2652"=
,"13-10-2024 10:41:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0003313121","M=
ontesquieux","","13-10-2024 10:01:15","13-10-2024 09:48:03","13-10-2024 10:=
38:52","Grid outage site went down because Gen start and stopped due to Gen=
 card dysfonction // He reset the Gen card and Gen manually started","Paul =
BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage site went down because Gen start and stopped due to Gen card dysfo=
nction // He reset the Gen card and Gen manually started","kouoh.jean@ihsto=
wers.com","793","13-10-2024 10:01:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003313076","I=
mm-Olympique","","13-10-2024 09:49:49","13-10-2024 09:32:33","13-10-2024 09=
:59:44","Grid outage,Gen failed to start due to power cable of Gen stolen s=
ince//he started the Gen with another power cable","Paul BIBOUM","Site Asse=
t Theft","Theft","Theft","DC Cable Stolen","Grid outage,Gen failed to start=
 due to power cable of Gen stolen since//he started the Gen with another po=
wer cable","kouoh.jean@ihstowers.com","1037","13-10-2024 09:49:49","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003312756","E=
kie sud","","13-10-2024 08:56:55","13-10-2024 08:54:43","13-10-2024 09:05:0=
6","Active//No power issue, site on Gen with U=3D50.7V, Lionel /655184876/ =
From Huawei is informed","Albran Byorel","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","Fibre Failure","Active//No power issue, sit=
e on Gen with U=3D50.7V, Lionel /655184876/ From Huawei is informed","kouoh=
.jean@ihstowers.com","132","13-10-2024 08:56:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_802","NOCINC0003312699","NYOM FAC=
E MAETUR","","13-10-2024 08:43:50","13-10-2024 08:34:43","13-10-2024 12:22:=
59","Grid outage, Site went down because landlord do not permit to start Ge=
n // Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Emergency Stop Switch","Grid outage, Site went down because landlo=
rd do not permit to start Gen // Grid return","stephane.nkamwa@ihstowers.co=
m","547","13-10-2024 08:43:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003312605","M=
vog-Manga","","13-10-2024 08:28:56","13-10-2024 06:54:46","13-10-2024 06:58=
:46","Grid outage, site went down before gen start due to poor battery back=
up // Grid power return","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid power return","kouoh.jean@ih=
stowers.com","5652","13-10-2024 08:28:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_065","NOCINC0003312333","Essos DC=
S","","13-10-2024 07:29:03","13-10-2024 07:15:42","13-10-2024 07:57:31","Ca=
scaded Incident from TTO3182146","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage Site went down due to di=
sfunction of Gen Contactors // He blocked Gen contactor and started Gen man=
ualy(GEN Contactor  to be replaced)","system","801","13-10-2024 07:29:03","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_097","NOCINC0003312332","Kondengu=
i MTN","","13-10-2024 07:29:03","13-10-2024 07:15:42","13-10-2024 07:57:31"=
,"Cascaded Incident from TTO3182146","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage Site went down due to=
 disfunction of Gen Contactors // He blocked Gen contactor and started Gen =
manualy(GEN Contactor  to be replaced)","system","801","13-10-2024 07:29:03=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003312334","Crf Corn=
ier","","13-10-2024 07:29:03","13-10-2024 07:15:42","13-10-2024 07:57:31","=
Cascaded Incident from TTO3182146","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage Site went down due to d=
isfunction of Gen Contactors // He blocked Gen contactor and started Gen ma=
nualy(GEN Contactor  to be replaced)","system","801","13-10-2024 07:29:03",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0003312329","Mobil-Es=
sos","","13-10-2024 07:29:02","13-10-2024 07:15:42","13-10-2024 07:57:31","=
Cascaded Incident from TTO3182146","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage Site went down due to d=
isfunction of Gen Contactors // He blocked Gen contactor and started Gen ma=
nualy(GEN Contactor  to be replaced)","system","800","13-10-2024 07:29:02",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003312330","Anguissa=
 New","","13-10-2024 07:29:02","13-10-2024 07:15:42","13-10-2024 07:57:31",=
"Cascaded Incident from TTO3182146","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage Site went down due to =
disfunction of Gen Contactors // He blocked Gen contactor and started Gen m=
anualy(GEN Contactor  to be replaced)","system","800","13-10-2024 07:29:02"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_120","NOCINC0003312327","Sapeur M=
imboman","","13-10-2024 07:29:02","13-10-2024 07:15:42","13-10-2024 07:57:3=
1","Cascaded Incident from TTO3182146","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid Outage Site went down d=
ue to disfunction of Gen Contactors // He blocked Gen contactor and started=
 Gen manualy(GEN Contactor  to be replaced)","system","800","13-10-2024 07:=
29:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_113","NOCINC0003312328","Emombo 2=
","","13-10-2024 07:29:02","13-10-2024 07:15:42","13-10-2024 07:57:31","Cas=
caded Incident from TTO3182146","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage Site went down due to disf=
unction of Gen Contactors // He blocked Gen contactor and started Gen manua=
ly(GEN Contactor  to be replaced)","system","800","13-10-2024 07:29:02","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_178","NOCINC0003312331","Emombo",=
"","13-10-2024 07:29:02","13-10-2024 07:15:42","13-10-2024 07:57:31","Casca=
ded Incident from TTO3182146","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid Outage Site went down due to dis=
function of Gen Contactors // He blocked Gen contactor and started Gen manu=
aly(GEN Contactor  to be replaced)","system","800","13-10-2024 07:29:02","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_063","NOCINC0003312326","Av-Germa=
ine","","13-10-2024 07:29:01","13-10-2024 07:15:42","13-10-2024 07:57:31","=
Cascaded Incident from TTO3182146","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid Outage Site went down due to disfunction of=
 Gen Contactors // He blocked Gen contactor and started Gen manualy(GEN Con=
tactor  to be replaced)","system","799","13-10-2024 07:29:01","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_122","NOCINC0003312323","Emombo E=
sssomba","","13-10-2024 07:29:01","13-10-2024 07:15:42","13-10-2024 07:57:3=
1","Cascaded Incident from TTO3182146","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid Outage Site went down d=
ue to disfunction of Gen Contactors // He blocked Gen contactor and started=
 Gen manualy(GEN Contactor  to be replaced)","system","799","13-10-2024 07:=
29:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_108","NOCINC0003312324","RUE FOE"=
,"","13-10-2024 07:29:01","13-10-2024 07:15:42","13-10-2024 07:57:31","Casc=
aded Incident from TTO3182146","Delor Telezing","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage Site went down due to disf=
unction of Gen Contactors // He blocked Gen contactor and started Gen manua=
ly(GEN Contactor  to be replaced)","system","799","13-10-2024 07:29:01","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_189","NOCINC0003312325","Paradis =
Hotel","","13-10-2024 07:29:01","13-10-2024 07:15:42","13-10-2024 07:57:31"=
,"Cascaded Incident from TTO3182146","Siligap Boris","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage Site went down due to=
 disfunction of Gen Contactors // He blocked Gen contactor and started Gen =
manualy(GEN Contactor  to be replaced)","system","799","13-10-2024 07:29:01=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_797","NOCINC0003312322","Messassi=
 Carrefourt","","13-10-2024 07:29:00","13-10-2024 07:15:42","13-10-2024 07:=
57:31","Cascaded Incident from TTO3182146","Delor Telezing","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid Outage Site went down=
 due to disfunction of Gen Contactors // He blocked Gen contactor and start=
ed Gen manualy(GEN Contactor  to be replaced)","system","798","13-10-2024 0=
7:29:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_180","NOCINC0003312321","Mimboman=
","","13-10-2024 07:29:00","13-10-2024 07:15:42","13-10-2024 07:57:31","Cas=
caded Incident from TTO3182146","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage Site went down due to d=
isfunction of Gen Contactors // He blocked Gen contactor and started Gen ma=
nualy(GEN Contactor  to be replaced)","system","798","13-10-2024 07:29:00",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0003312320","MONTEE N=
KONDENGUI","","13-10-2024 07:29:00","13-10-2024 07:15:42","13-10-2024 07:57=
:31","Cascaded Incident from TTO3182146","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Outage Site went down du=
e to disfunction of Gen Contactors // He blocked Gen contactor and started =
Gen manualy(GEN Contactor  to be replaced)","system","798","13-10-2024 07:2=
9:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_110","NOCINC0003312308","Camp-Son=
el","IHS_YND_682, IHS_YND_180, IHS_YND_797, IHS_YND_122, IHS_YND_108, IHS_Y=
ND_189, IHS_YND_063, IHS_YND_120, IHS_YND_113, IHS_YND_109, IHS_YND_568, IH=
S_YND_178, IHS_YND_097, IHS_YND_065, IHS_YND_566","13-10-2024 07:24:52","13=
-10-2024 07:15:42","13-10-2024 07:57:31","Grid Outage Site went down due to=
 disfunction of  Contactors  Q11 in the ATS // He blocked contactor Contact=
ors  Q11 and started Gen manualy(Contactors  Q11   to be replaced)","Siliga=
p Boris","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid=
 Outage Site went down due to disfunction of  Contactors  Q11 in the ATS //=
 He blocked contactor Contactors  Q11 and started Gen manualy(Contactors  Q=
11   to be replaced)","stephane.nkamwa@ihstowers.com","551","13-10-2024 07:=
24:52","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003312134","Nko=
g-Edzen","","13-10-2024 06:49:36","13-10-2024 06:44:28","13-10-2024 12:30:2=
3","Active//No power issue on site with  Ubaie=3D52.4V site on Gen (start t=
hreshold ubai=3D50 V The Tx Fme Gregoire( 652070658)from Huawei is informed=
","Parker Tchoup","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active//No power issue on site with  Ubaie=3D=
52.4V site on Gen (start threshold ubai=3D50 V The Tx Fme Gregoire( 6520706=
58)from Huawei is informed","stephane.nkamwa@ihstowers.com","309","13-10-20=
24 06:49:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003312107","E=
kounou","","13-10-2024 06:48:47","13-10-2024 06:44:46","13-10-2024 09:29:20=
","Grid outage site went down because Gen stopped with alarm Failed start a=
nd poor backup( awaited Africa Security more than 1 hour and half)// he res=
et the Gen card and Gen manually started","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down b=
ecause Gen stopped with alarm Failed start and poor backup( awaited Africa =
Security more than 1 hour and half)// he reset the Gen card and Gen manuall=
y started","kouoh.jean@ihstowers.com","242","13-10-2024 06:48:47","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003311512","Crf Corn=
ier","","13-10-2024 04:19:03","13-10-2024 04:09:27","13-10-2024 05:29:27","=
Cascaded Incident from TTO3181224","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to disfunction o=
f Q11// He blocked Gen contactor and started Gen manualy(Q11 to be replaced=
) // Camp sonel","system","576","13-10-2024 04:19:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_065","NOCINC0003311511","Essos DC=
S","","13-10-2024 04:19:02","13-10-2024 04:09:27","13-10-2024 05:29:27","Ca=
scaded Incident from TTO3181224","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to disfunction of=
 Q11// He blocked Gen contactor and started Gen manualy(Q11 to be replaced)=
 // Camp sonel","system","575","13-10-2024 04:19:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003311508","Anguissa=
 New","","13-10-2024 04:19:02","13-10-2024 04:09:27","13-10-2024 05:29:27",=
"Cascaded Incident from TTO3181224","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to disfunction =
of Q11// He blocked Gen contactor and started Gen manualy(Q11 to be replace=
d) // Camp sonel","system","575","13-10-2024 04:19:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_113","NOCINC0003311506","Emombo 2=
","","13-10-2024 04:19:02","13-10-2024 04:09:27","13-10-2024 05:29:27","Cas=
caded Incident from TTO3181224","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to disfunction of Q=
11// He blocked Gen contactor and started Gen manualy(Q11 to be replaced) /=
/ Camp sonel","system","575","13-10-2024 04:19:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_097","NOCINC0003311510","Kondengu=
i MTN","","13-10-2024 04:19:02","13-10-2024 04:09:27","13-10-2024 05:29:27"=
,"Cascaded Incident from TTO3181224","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to disfunction=
 of Q11// He blocked Gen contactor and started Gen manualy(Q11 to be replac=
ed) // Camp sonel","system","575","13-10-2024 04:19:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_178","NOCINC0003311509","Emombo",=
"","13-10-2024 04:19:02","13-10-2024 04:09:27","13-10-2024 05:29:27","Casca=
ded Incident from TTO3181224","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to disfunction of =
Q11// He blocked Gen contactor and started Gen manualy(Q11 to be replaced) =
// Camp sonel","system","575","13-10-2024 04:19:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0003311507","Mobil-Es=
sos","","13-10-2024 04:19:02","13-10-2024 04:09:27","13-10-2024 05:29:27","=
Cascaded Incident from TTO3181224","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to disfunction o=
f Q11// He blocked Gen contactor and started Gen manualy(Q11 to be replaced=
) // Camp sonel","system","575","13-10-2024 04:19:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_120","NOCINC0003311505","Sapeur M=
imboman","","13-10-2024 04:19:01","13-10-2024 04:09:27","13-10-2024 05:29:2=
7","Cascaded Incident from TTO3181224","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down due to disfun=
ction of Q11// He blocked Gen contactor and started Gen manualy(Q11 to be r=
eplaced) // Camp sonel","system","574","13-10-2024 04:19:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_063","NOCINC0003311504","Av-Germa=
ine","","13-10-2024 04:19:01","13-10-2024 04:09:27","13-10-2024 05:29:27","=
Cascaded Incident from TTO3181224","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Site went down due to disfunction of Q11// He bl=
ocked Gen contactor and started Gen manualy(Q11 to be replaced) // Camp son=
el","system","574","13-10-2024 04:19:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_122","NOCINC0003311501","Emombo E=
sssomba","","13-10-2024 04:19:01","13-10-2024 04:09:27","13-10-2024 05:29:2=
7","Cascaded Incident from TTO3181224","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down due to disfun=
ction of Q11// He blocked Gen contactor and started Gen manualy(Q11 to be r=
eplaced) // Camp sonel","system","574","13-10-2024 04:19:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_189","NOCINC0003311503","Paradis =
Hotel","","13-10-2024 04:19:01","13-10-2024 04:09:27","13-10-2024 05:29:27"=
,"Cascaded Incident from TTO3181224","Siligap Boris","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to disfunction=
 of Q11// He blocked Gen contactor and started Gen manualy(Q11 to be replac=
ed) // Camp sonel","system","574","13-10-2024 04:19:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_108","NOCINC0003311502","RUE FOE"=
,"","13-10-2024 04:19:01","13-10-2024 04:09:27","13-10-2024 05:29:27","Casc=
aded Incident from TTO3181224","Delor Telezing","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to disfunction of Q=
11// He blocked Gen contactor and started Gen manualy(Q11 to be replaced) /=
/ Camp sonel","system","574","13-10-2024 04:19:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0003311497","MONTEE N=
KONDENGUI","","13-10-2024 04:19:00","13-10-2024 04:09:27","13-10-2024 05:29=
:27","Cascaded Incident from TTO3181224","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to disfunc=
tion of Q11// He blocked Gen contactor and started Gen manualy(Q11 to be re=
placed) // Camp sonel","system","573","13-10-2024 04:19:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_797","NOCINC0003311500","Messassi=
 Carrefourt","","13-10-2024 04:19:00","13-10-2024 04:09:27","13-10-2024 05:=
29:27","Cascaded Incident from TTO3181224","Delor Telezing","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down due to disf=
unction of Q11// He blocked Gen contactor and started Gen manualy(Q11 to be=
 replaced) // Camp sonel","system","573","13-10-2024 04:19:00","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_111","NOCINC0003311498","Essos Ma=
rche","","13-10-2024 04:19:00","13-10-2024 04:09:27","13-10-2024 05:29:27",=
"Cascaded Incident from TTO3181224","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to disfunction=
 of Q11// He blocked Gen contactor and started Gen manualy(Q11 to be replac=
ed) // Camp sonel","system","573","13-10-2024 04:19:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_180","NOCINC0003311499","Mimboman=
","","13-10-2024 04:19:00","13-10-2024 04:09:27","13-10-2024 05:29:27","Cas=
caded Incident from TTO3181224","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to disfunction o=
f Q11// He blocked Gen contactor and started Gen manualy(Q11 to be replaced=
) // Camp sonel","system","573","13-10-2024 04:19:00","Sagemcom CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0003311489","Cam=
p-Sonel","IHS_YND_682, IHS_YND_111, IHS_YND_180, IHS_YND_797, IHS_YND_122, =
IHS_YND_108, IHS_YND_189, IHS_YND_063, IHS_YND_120, IHS_YND_113, IHS_YND_10=
9, IHS_YND_568, IHS_YND_178, IHS_YND_097, IHS_YND_065, IHS_YND_566","13-10-=
2024 04:14:35","13-10-2024 04:09:27","13-10-2024 05:29:27","Site went down =
due to Gen contactor disfunctionning // He bypass it and manually start the=
 gen","Siligap Boris","Equipment Repair","Passive","Control Panel","ATS-AMF=
 Issue","Site went down due to Gen contactor disfunctionning // He bypass i=
t and manually start the gen","adonis.defokoua@ihstowers.com","309","13-10-=
2024 04:14:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003311344","Yoko OCM=
","","13-10-2024 03:28:11","13-10-2024 02:53:53","13-10-2024 02:53:54","Cas=
caded Incident from TTO3181064","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 54.6V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.=
","system","2058","13-10-2024 03:28:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003311346","MBIMBIM"=
,"","13-10-2024 03:28:11","13-10-2024 02:53:53","13-10-2024 02:53:54","Casc=
aded Incident from TTO3181064","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 54.6V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","2058","13-10-2024 03:28:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003311342","Ngoum","=
","13-10-2024 03:28:11","13-10-2024 02:53:53","13-10-2024 02:53:54","Cascad=
ed Incident from TTO3181064","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 54.6V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","2058","13-10-2024 03:28:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003311343","Matsari"=
,"","13-10-2024 03:28:11","13-10-2024 02:53:53","13-10-2024 02:53:54","Casc=
aded Incident from TTO3181064","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 54.6V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","2058","13-10-2024 03:28:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003311345","Ngouetou=
","","13-10-2024 03:28:11","13-10-2024 02:53:53","13-10-2024 02:53:54","Cas=
caded Incident from TTO3181064","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 54.6V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.=
","system","2058","13-10-2024 03:28:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003310658","M=
imboman-Ecole","","12-10-2024 23:43:52","12-10-2024 23:39:40","13-10-2024 0=
1:14:55","Site went down due to insufficient of rectifiers (02/03)// Site s=
tabilized(rectifer to be added)","Mba Lazare Herve","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Site went down due to insufficient of=
 rectifiers (02/03)// Site stabilized(rectifer to be added)","ange.kongo@ih=
stowers.com","253","12-10-2024 23:43:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003309953","B=
iteng-Maetur","","12-10-2024 21:17:29","12-10-2024 21:13:25","12-10-2024 23=
:49:56","No power issue on site ,site on Grid with Ubaie=3D53,8 V The Tx FM=
E Lionel adjep(655184876) from Huawei is informed","Mba Lazare Herve","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site ,site on Grid with Ubaie=3D53,8 V The Tx FME =
Lionel adjep(655184876) from Huawei is informed","dorothy.djantio@ihstowers=
.com","245","12-10-2024 21:17:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0003309884","Marche O=
dza","","12-10-2024 21:09:11","12-10-2024 20:31:28","12-10-2024 21:19:59","=
Cascaded Incident from TTO3179317","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,DG failed to start due =
hybrid system failure //Manually start of DG.","system","2263","12-10-2024 =
21:09:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0003309862","O=
dza","IHS_YND_580","12-10-2024 21:05:35","12-10-2024 20:31:28","12-10-2024 =
21:19:59","Grid outage,DG failed to start due hybrid system failure //Manua=
lly start of DG.","Albran Byorel","Equipment Repair","Passive","Hybrid","Hy=
brid Software","Grid outage,DG failed to start due hybrid system failure //=
Manually start of DG.","dorothy.djantio@ihstowers.com","2048","12-10-2024 2=
1:05:35","Sagemcom CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0003309831","BEA=
TITUDE ENTR=C9E PAVE","","12-10-2024 21:00:29","12-10-2024 20:56:21","12-10=
-2024 22:18:06","Grid fluctuation, site went down because gen started and s=
topped due to grid bad voltage no rcp// he bypass grid and manually start t=
he gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Grid fluctuation, site went down because =
gen started and stopped due to grid bad voltage no rcp// he bypass grid and=
 manually start the gen","olivier.kwedi@ihstowers.com","249","12-10-2024 21=
:00:29","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0003309670","Av =
Kennedy","","12-10-2024 20:37:22","12-10-2024 20:31:12","12-10-2024 20:40:0=
7","Active//No power issue, site is on Grid with Ubaie=3D55,9 V  The TX FME=
 Eloundou Bertrant  (693212405)  from Huawei is informed","","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue, site is on Grid with Ubaie=3D55,9 V  The TX FME Eloun=
dou Bertrant  (693212405)  from Huawei is informed","olivier.kwedi@ihstower=
s.com","371","12-10-2024 20:37:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0003309584","Emana Ly=
cee","","12-10-2024 20:24:50","12-10-2024 20:05:39","12-10-2024 20:19:50","=
Cascaded Incident from TTO3178958","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,DG failed to start du=
e to ACDG generator battery faulty //Manually start of DG with external bat=
tery.","system","1151","12-10-2024 20:24:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0003309585","Emana ly=
cee 2","","12-10-2024 20:24:50","12-10-2024 20:05:39","12-10-2024 20:19:50"=
,"Cascaded Incident from TTO3178958","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage,DG failed to start =
due to ACDG generator battery faulty //Manually start of DG with external b=
attery.","system","1151","12-10-2024 20:24:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0003309583","Mballa 4=
","","12-10-2024 20:24:50","12-10-2024 20:05:39","12-10-2024 20:19:50","Cas=
caded Incident from TTO3178958","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage,DG failed to start due to=
 ACDG generator battery faulty //Manually start of DG with external battery=
.","system","1151","12-10-2024 20:24:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0003309546","O=
kolo","IHS_YND_242, IHS_YND_274, IHS_YND_685","12-10-2024 20:18:43","12-10-=
2024 20:05:39","12-10-2024 20:19:50","Grid outage,DG failed to start due to=
 ACDG generator battery faulty //Manually start of DG with external battery=
.","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Battery","Grid outage,DG failed to start due to ACDG generator battery =
faulty //Manually start of DG with external battery.","dorothy.djantio@ihst=
owers.com","785","12-10-2024 20:18:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003309389","M=
vog-Manga","","12-10-2024 19:49:34","12-10-2024 19:44:30","12-10-2024 21:19=
:35","Grid outage,DG fails to start due PSC3 Faulty //Manually start of DG.=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid outage,DG fails to start due PSC3 Faulty //Manually start of DG=
.","dorothy.djantio@ihstowers.com","305","12-10-2024 19:49:34","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003309380","E=
kounou","","12-10-2024 19:48:39","12-10-2024 19:44:32","12-10-2024 20:05:10=
","Grid outage,site went down before DG start : Poor batteries backup //DG =
started automatically.","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage,site went down before =
DG start : Poor batteries backup //DG started automatically.","dorothy.djan=
tio@ihstowers.com","248","12-10-2024 19:48:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003309275","MBIMBIM"=
,"","12-10-2024 19:26:11","12-10-2024 18:55:40","12-10-2024 18:56:11","Casc=
aded Incident from TTO3178624","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 54.7V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","1831","12-10-2024 19:26:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003309274","Ngouetou=
","","12-10-2024 19:26:11","12-10-2024 18:55:40","12-10-2024 18:56:11","Cas=
caded Incident from TTO3178624","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 54.7V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.=
","system","1831","12-10-2024 19:26:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003309272","Matsari"=
,"","12-10-2024 19:26:10","12-10-2024 18:55:40","12-10-2024 18:56:11","Casc=
aded Incident from TTO3178624","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 54.7V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","1830","12-10-2024 19:26:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003309273","Yoko OCM=
","","12-10-2024 19:26:10","12-10-2024 18:55:40","12-10-2024 18:56:11","Cas=
caded Incident from TTO3178624","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 54.7V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.=
","system","1830","12-10-2024 19:26:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003309271","Ngoum","=
","12-10-2024 19:26:10","12-10-2024 18:55:40","12-10-2024 18:56:11","Cascad=
ed Incident from TTO3178624","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 54.7V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","1830","12-10-2024 19:26:10","Sagemcom CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0003309260","Eki=
e sud","","12-10-2024 19:22:44","12-10-2024 19:18:36","12-10-2024 20:14:06"=
,"Grid outage, site went down becausegen failed to start due to  (hybrid sy=
stem and automatism) dysfunctioning// Gen manually started","Albran Byorel"=
,"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage,=
 site went down becausegen failed to start due to  (hybrid system and autom=
atism) dysfunctioning// Gen manually started","olivier.kwedi@ihstowers.com"=
,"248","12-10-2024 19:22:44","Sagemcom CMR"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0003309211","COR=
NIERS","","12-10-2024 19:13:32","12-10-2024 19:01:23","12-10-2024 22:21:56"=
,"Grid outage No space to deploy MDG //Grid return power issue resolved  10=
:21 PM at ,but site still down after power reset done The Tx   fme Hugo (67=
2390202) from Huawei informed","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage No space to deploy MDG //Grid return=
 power issue resolved  10:21 PM at ,but site still down after power reset d=
one The Tx   fme Hugo (672390202) from Huawei informed","olivier.kwedi@ihst=
owers.com","730","12-10-2024 19:13:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003309000","S=
tade-Abega","","12-10-2024 18:45:35","12-10-2024 18:39:31","12-10-2024 18:5=
0:15","Grid Outage site went donw because Gen failed to start due to Gen st=
arter Faulty//Grid Restored","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid Outage site went donw=
 because Gen failed to start due to Gen starter Faulty//Grid Restored","dor=
othy.djantio@ihstowers.com","365","12-10-2024 18:45:35","Sagemcom CMR"
"Closed Complete","Warning","T1556","IHS_YND_182","NOCINC0003308735","Titi =
Garage","","12-10-2024 18:06:29","","","Grid outage//DG started automatical=
ly","Delor Telezing","Warning","Warning","POWER","Warning - National Grid -=
 Grid Outage Issue","Grid outage//DG started automatically","ludivine.ngama=
leu@ihstowers.com","1","12-10-2024 18:06:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_065","NOCINC0003308726","Essos DC=
S","","12-10-2024 18:03:14","12-10-2024 17:46:56","12-10-2024 18:20:06","Ca=
scaded Incident from TTO3177921","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to LVD controller=
 dysfunctioning//He reset the controller.site on Grid.(Investigations ongoi=
ng)","system","978","12-10-2024 18:03:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003308727","Crf Corn=
ier","","12-10-2024 18:03:14","12-10-2024 17:46:56","12-10-2024 18:20:06","=
Cascaded Incident from TTO3177921","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to LVD controlle=
r dysfunctioning//He reset the controller.site on Grid.(Investigations ongo=
ing)","system","978","12-10-2024 18:03:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003308723","Anguissa=
 New","","12-10-2024 18:03:13","12-10-2024 18:25:59","12-10-2024 18:32:25",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started","MINKA NICOLAS","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","Grid outage, site went down before gen start=
 due to poor battery backup // Gen started","system","2809","12-10-2024 18:=
03:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_178","NOCINC0003308724","Emombo",=
"","12-10-2024 18:03:13","12-10-2024 17:46:56","12-10-2024 18:20:06","Casca=
ded Incident from TTO3177921","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to LVD controller =
dysfunctioning//He reset the controller.site on Grid.(Investigations ongoin=
g)","system","977","12-10-2024 18:03:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0003308722","Mobil-Es=
sos","","12-10-2024 18:03:13","12-10-2024 17:46:56","12-10-2024 18:20:06","=
Cascaded Incident from TTO3177921","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to LVD controlle=
r dysfunctioning//He reset the controller.site on Grid.(Investigations ongo=
ing)","system","977","12-10-2024 18:03:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_097","NOCINC0003308725","Kondengu=
i MTN","","12-10-2024 18:03:13","12-10-2024 17:46:56","12-10-2024 18:20:06"=
,"Cascaded Incident from TTO3177921","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to LVD control=
ler dysfunctioning//He reset the controller.site on Grid.(Investigations on=
going)","system","977","12-10-2024 18:03:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_122","NOCINC0003308716","Emombo E=
sssomba","","12-10-2024 18:03:12","12-10-2024 17:46:56","12-10-2024 18:20:0=
6","Cascaded Incident from TTO3177921","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down due to LVD co=
ntroller dysfunctioning//He reset the controller.site on Grid.(Investigatio=
ns ongoing)","system","976","12-10-2024 18:03:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_120","NOCINC0003308719","Sapeur M=
imboman","","12-10-2024 18:03:12","12-10-2024 17:46:56","12-10-2024 18:20:0=
6","Cascaded Incident from TTO3177921","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Site went down due to LVD co=
ntroller dysfunctioning//He reset the controller.site on Grid.(Investigatio=
ns ongoing)","system","976","12-10-2024 18:03:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_189","NOCINC0003308718","Paradis =
Hotel","","12-10-2024 18:03:12","12-10-2024 17:46:56","12-10-2024 18:20:06"=
,"Cascaded Incident from TTO3177921","Siligap Boris","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to LVD control=
ler dysfunctioning//He reset the controller.site on Grid.(Investigations on=
going)","system","976","12-10-2024 18:03:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_113","NOCINC0003308720","Emombo 2=
","","12-10-2024 18:03:12","12-10-2024 17:46:56","12-10-2024 18:20:06","Cas=
caded Incident from TTO3177921","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to LVD controller d=
ysfunctioning//He reset the controller.site on Grid.(Investigations ongoing=
)","system","976","12-10-2024 18:03:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_108","NOCINC0003308717","RUE FOE"=
,"","12-10-2024 18:03:12","12-10-2024 17:46:56","12-10-2024 18:20:06","Casc=
aded Incident from TTO3177921","Delor Telezing","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to LVD controller d=
ysfunctioning//He reset the controller.site on Grid.(Investigations ongoing=
)","system","976","12-10-2024 18:03:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_180","NOCINC0003308714","Mimboman=
","","12-10-2024 18:03:11","12-10-2024 17:46:56","12-10-2024 18:20:06","Cas=
caded Incident from TTO3177921","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to LVD controlle=
r dysfunctioning//He reset the controller.site on Grid.(Investigations ongo=
ing)","system","975","12-10-2024 18:03:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_111","NOCINC0003308713","Essos Ma=
rche","","12-10-2024 18:03:11","12-10-2024 17:46:56","12-10-2024 18:20:06",=
"Cascaded Incident from TTO3177921","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to LVD control=
ler dysfunctioning//He reset the controller.site on Grid.(Investigations on=
going)","system","975","12-10-2024 18:03:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0003308712","MONTEE N=
KONDENGUI","","12-10-2024 18:03:11","12-10-2024 17:46:56","12-10-2024 18:20=
:06","Cascaded Incident from TTO3177921","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to LVD con=
troller dysfunctioning//He reset the controller.site on Grid.(Investigation=
s ongoing)","system","975","12-10-2024 18:03:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_797","NOCINC0003308715","Messassi=
 Carrefourt","","12-10-2024 18:03:11","12-10-2024 17:46:56","12-10-2024 18:=
20:06","Cascaded Incident from TTO3177921","Delor Telezing","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Site went down due to LVD =
controller dysfunctioning//He reset the controller.site on Grid.(Investigat=
ions ongoing)","system","975","12-10-2024 18:03:11","Sagemcom CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0003308669","Cam=
p-Sonel","IHS_YND_682, IHS_YND_111, IHS_YND_180, IHS_YND_797, IHS_YND_122, =
IHS_YND_108, IHS_YND_189, IHS_YND_120, IHS_YND_113, IHS_YND_109, IHS_YND_17=
8, IHS_YND_114, IHS_YND_097, IHS_YND_065, IHS_YND_566","12-10-2024 17:59:11=
","12-10-2024 17:46:56","12-10-2024 18:20:06","Site went down due to LVD co=
ntroller dysfunctioning//He reset the controller.site on Grid.(Investigatio=
ns ongoing)","Siligap Boris","Equipment Repair","Passive","Rectifier","PLD/=
LVD Settings Wrong","Site went down due to LVD controller dysfunctioning//H=
e reset the controller.site on Grid.(Investigations ongoing)","olivier.kwed=
i@ihstowers.com","735","12-10-2024 17:59:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003308663","Kondengu=
i","","12-10-2024 17:57:30","12-10-2024 17:34:38","12-10-2024 18:20:06","Ca=
scaded Incident from TTO3177911","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage// grid return","system","=
1372","12-10-2024 17:57:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003308659","E=
mombo-Tchad","IHS_YND_114","12-10-2024 17:56:43","12-10-2024 17:34:38","12-=
10-2024 18:07:59","grid outage// grid return","","Grid Supply","Passive","G=
rid","National Grid - Grid Outage Issue","grid outage// grid return","dorot=
hy.djantio@ihstowers.com","1326","12-10-2024 17:56:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003308538","E=
ssomba","","12-10-2024 17:34:01","12-10-2024 16:55:52","12-10-2024 18:36:48=
","grid outage, site went down due to gen Overload(15KVA; 210A)// He reduce=
d the load, site on gen","Mba Lazare Herve","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","grid outage, site went down due to gen Overload=
(15KVA; 210A)// He reduced the load, site on gen","dorothy.djantio@ihstower=
s.com","2290","12-10-2024 17:34:01","Sagemcom CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0003308005","Mae=
tur","","12-10-2024 15:52:47","12-10-2024 15:40:38","12-10-2024 15:58:11","=
Site on DG due to grid outage,Site went down due to ACDG circuit breaker do=
wn //Circuit Breaker put back on(Inverstigations ongoing).","Mboua Thierry"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Site on DG =
due to grid outage,Site went down due to ACDG circuit breaker down //Circui=
t Breaker put back on(Inverstigations ongoing).","olivier.kwedi@ihstowers.c=
om","730","12-10-2024 15:52:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003307815","A=
WAE OCM","","12-10-2024 15:36:51","12-10-2024 15:32:33","12-10-2024 20:42:4=
8","No power issue, site is on grid with Ubaie=3D54,8V, Hurgo(672390202) fr=
om Huawei is informed","Mba Lazare Herve","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site =
is on grid with Ubaie=3D54,8V, Hurgo(672390202) from Huawei is informed","d=
orothy.djantio@ihstowers.com","259","12-10-2024 15:36:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003307784","N=
kolndongo","","12-10-2024 15:32:59","12-10-2024 15:01:52","12-10-2024 16:00=
:06","Grid outage site went down because mains Gen faulty due to  //MDG 15k=
va deployed","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG =
- Generator Faulty","Grid outage site went down because mains Gen faulty//M=
DG 15kva deployed","dorothy.djantio@ihstowers.com","1867","12-10-2024 15:32=
:59","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003307713","San=
ta Barbara Gottam","","12-10-2024 15:23:01","12-10-2024 14:50:53","12-10-20=
24 16:17:48","Site went down due to PWC dysfonctioning ( Batteries Backup  =
alarming ; PWC FNS)//Reset Batteries Backup,site on Grid.","Delor Telezing"=
,"Equipment Repair","Passive","Rectifier","Rectifier - Controller Failure",=
"Site went down due to PWC dysfonctioning ( Batteries Backup  alarming ; PW=
C FNS)//Reset Batteries Backup,site on Grid.","olivier.kwedi@ihstowers.com"=
,"1929","12-10-2024 15:23:01","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0003307490","MBA=
LNGONG LYCEE","","12-10-2024 14:59:10","12-10-2024 14:35:34","12-10-2024 15=
:07:35","cascade it behind ahala.","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down before Ge=
n start due to poor battery backup // Grid power return.","olivier.kwedi@ih=
stowers.com","16205","12-10-2024 14:59:10","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0003307470","ELO=
UMDEM CARRIERE","","12-10-2024 14:56:44","12-10-2024 14:35:34","12-10-2024 =
15:07:35","cascade it behind ahala.","Fanda Brice","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down before =
Gen start due to poor battery backup // Grid power return.","olivier.kwedi@=
ihstowers.com","15843","12-10-2024 14:56:44","Sagemcom CMR"
"Closed Complete","Site Down","T1557","IHS_YND_313","NOCINC0003307456","Afa=
noya","","12-10-2024 14:54:15","12-10-2024 14:35:34","12-10-2024 15:07:35",=
"cascade it behind ahala.","Hyemafo Gildas","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, site went down before Gen sta=
rt due to poor battery backup // Grid power return.","olivier.kwedi@ihstowe=
rs.com","15741","12-10-2024 14:54:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003307404","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","12-10-2024 14:46:36","12-10-=
2024 14:35:34","12-10-2024 15:07:35","Grid outage, site went down before Ge=
n start due to poor battery backup // Grid power return.","Hyemafo Gildas",=
"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Grid power return.","dorothy.djantio@ihstowers.com","1693","12-10-2024 14:=
46:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003307400","M=
imboman-Ecole","","12-10-2024 14:45:05","12-10-2024 14:36:58","12-10-2024 1=
7:00:41","Site was on Gen due to Grid outage, site went down due to 02/02 r=
ectifiers faulty // He changed 02 rectifiers.","Mba Lazare Herve","Equipmen=
t Repair","Passive","Rectifier","Rectifier Module","Site was on Gen due to =
Grid outage, site went down due to 02/02 rectifiers faulty // He changed 02=
 rectifiers.","dorothy.djantio@ihstowers.com","487","12-10-2024 14:45:05","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0003307276","ARMP",""=
,"12-10-2024 14:14:01","12-10-2024 10:55:53","12-10-2024 12:23:52","Cascade=
d Incident from TTO3176321","","Cascade Outage","Active","Cascade Active","=
Cascade Active","No power issue on site ,site on Grid with Ubaie=3D53,8 V T=
he Tx FME Eloundou(693212405) from Huawei is informed","system","11888","12=
-10-2024 14:14:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0003307275","Bastos B=
ir","","12-10-2024 14:14:01","12-10-2024 10:55:53","12-10-2024 12:23:52","C=
ascaded Incident from TTO3176321","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site ,site on Grid wi=
th Ubaie=3D53,8 V The Tx FME Eloundou(693212405) from Huawei is informed","=
system","11888","12-10-2024 14:14:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003307272","D=
ragage","IHS_YND_704, IHS_YND_208","12-10-2024 14:12:58","12-10-2024 10:55:=
53","12-10-2024 19:36:52","No power issue on site ,site on Grid with Ubaie=
=3D53,8 V The Tx FME Eloundou(693212405) from Huawei is informed","Mboua Th=
ierry","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site ,site on Grid with Ubaie=3D53,8 V=
 The Tx FME Eloundou(693212405) from Huawei is informed","alexandre.kamal@i=
hstowers.com","11826","12-10-2024 14:12:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0003307263","Ngoulmek=
ong-Nord","","12-10-2024 14:12:01","12-10-2024 10:53:08","12-10-2024 14:30:=
20","Cascaded Incident from TTO3176310","Siligap Boris","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active: no power issue, site is o=
n grid with Ubaie=3D53V, SYMPHORIEN (650257151) from Huawei is informed.","=
system","11933","12-10-2024 14:12:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0003307262","E=
leveur","IHS_YND_277","12-10-2024 14:11:19","12-10-2024 10:53:08","12-10-20=
24 14:30:20","Active: no power issue, site is on grid with Ubaie=3D53V, SYM=
PHORIEN (650257151) from Huawei is informed.","Siligap Boris","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive: no power issue, site is on grid with Ubaie=3D53V, SYMPHORIEN (650257=
151) from Huawei is informed.","alexandre.kamal@ihstowers.com","11892","12-=
10-2024 14:11:19","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_698","NOCINC0003307184","EBOM","","=
12-10-2024 13:55:02","","","Site alarming Grid outage Gen ran until still F=
uel outage// Refueling done and Gen manually started ","Hyemafo Gildas","Wa=
rning","Warning","POWER","Warning - Site on Battery","Site alarming Grid ou=
tage Gen ran until still Fuel outage// Refueling done and Gen manually star=
ted ","stephane.nkamwa@ihstowers.com","250","12-10-2024 13:55:02","Sagemcom=
 CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003307078","N=
KOMEKUI OCM","IHS_YND_341","12-10-2024 13:32:10","12-10-2024 13:15:03","12-=
10-2024 16:33:16","Grid Outage, site went down because Gen stopped with ""h=
igh temp"" alarm// He added water and started Gen manually.","TIENTCHEU NZE=
TCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Te=
mp - Coolant Level Issue","Grid Outage, site went down because Gen stopped =
with ""high temp"" alarm// He added water and started Gen manually.","alexa=
ndre.kamal@ihstowers.com","1028","12-10-2024 13:32:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0003307055","A=
v-Germaine","","12-10-2024 13:24:39","12-10-2024 13:21:35","12-10-2024 17:4=
1:26","Grid outage,no space to deploy a mobile DG waiting for Grid power re=
turn//Grid restored.","","Grid Supply","Passive","Grid","National Grid - Gr=
id Outage Issue","Grid outage,no space to deploy a mobile DG waiting for Gr=
id power return//Grid restored.","alexandre.kamal@ihstowers.com","184","12-=
10-2024 13:24:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0003307039","L=
obo OCM","","12-10-2024 13:22:23","12-10-2024 13:15:03","12-10-2024 16:33:1=
6","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid Outage, site went down because Gen stopped with =
""high temp"" alarm// He added water and started Gen manually.","alexandre.=
kamal@ihstowers.com","1159","12-10-2024 13:22:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_643","IHS_YND_105","NOCINC0003307038","O=
mnisport 3","","12-10-2024 13:21:32","12-10-2024 13:07:28","12-10-2024 13:1=
5:00","Active// No power Issue on site, Site on Grid Ubai=3D54,8V   Fme Tx =
Armand Ngetsa/691144412/From Huawei is informed","Delor Telezing","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power Issue on site, Site on Grid Ubai=3D54,8V   Fme Tx Arma=
nd Ngetsa/691144412/From Huawei is informed","alexandre.kamal@ihstowers.com=
","844","12-10-2024 13:21:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0003307023","Nyom OCM=
","","12-10-2024 13:20:12","12-10-2024 12:41:34","12-10-2024 13:10:54","Cas=
caded Incident from TTO3175775","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site was on Gen due to Grid fluctuat=
ion, site went down due to disjunction Circuit breaker of gen  // He reamed=
 Circuit breaker of gen and gen manually started","system","2318","12-10-20=
24 13:20:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0003307024","Messassi=
 2","","12-10-2024 13:20:12","12-10-2024 12:41:34","12-10-2024 13:10:54","C=
ascaded Incident from TTO3175775","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site was on Gen due to Grid fluctu=
ation, site went down due to disjunction Circuit breaker of gen  // He ream=
ed Circuit breaker of gen and gen manually started","system","2318","12-10-=
2024 13:20:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0003307025","Nkolondo=
m","","12-10-2024 13:20:12","12-10-2024 12:41:34","12-10-2024 13:10:54","Ca=
scaded Incident from TTO3175775","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site was on Gen due to Grid fluctua=
tion, site went down due to disjunction Circuit breaker of gen  // He reame=
d Circuit breaker of gen and gen manually started","system","2318","12-10-2=
024 13:20:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003307022","Messassi=
 okolo","","12-10-2024 13:20:12","12-10-2024 12:41:34","12-10-2024 13:10:54=
","Cascaded Incident from TTO3175775","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site was on Gen due to Grid fl=
uctuation, site went down due to disjunction Circuit breaker of gen  // He =
reamed Circuit breaker of gen and gen manually started","system","2318","12=
-10-2024 13:20:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0003307021","Nkozoa",=
"","12-10-2024 13:20:11","12-10-2024 12:41:34","12-10-2024 13:10:54","Casca=
ded Incident from TTO3175775","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site was on Gen due to Grid fluctuatio=
n, site went down due to disjunction Circuit breaker of gen  // He reamed C=
ircuit breaker of gen and gen manually started","system","2317","12-10-2024=
 13:20:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0003307020","Messassi=
","","12-10-2024 13:20:11","12-10-2024 12:41:34","12-10-2024 13:10:54","Cas=
caded Incident from TTO3175775","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site was on Gen due to Grid fluctuat=
ion, site went down due to disjunction Circuit breaker of gen  // He reamed=
 Circuit breaker of gen and gen manually started","system","2317","12-10-20=
24 13:20:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0003307019","Olembe-T=
erminus","","12-10-2024 13:20:11","12-10-2024 12:41:34","12-10-2024 13:10:5=
4","Cascaded Incident from TTO3175775","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site was on Gen due to Grid f=
luctuation, site went down due to disjunction Circuit breaker of gen  // He=
 reamed Circuit breaker of gen and gen manually started","system","2317","1=
2-10-2024 13:20:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0003307018","NKOLMEKO=
NG YDE","","12-10-2024 13:20:11","12-10-2024 12:41:34","12-10-2024 13:10:54=
","Cascaded Incident from TTO3175775","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site was on Gen due to Grid fl=
uctuation, site went down due to disjunction Circuit breaker of gen  // He =
reamed Circuit breaker of gen and gen manually started","system","2317","12=
-10-2024 13:20:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0003307016","Ekombiti=
e","","12-10-2024 13:20:10","12-10-2024 12:41:34","12-10-2024 13:10:54","Ca=
scaded Incident from TTO3175775","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site was on Gen due to Grid fluctua=
tion, site went down due to disjunction Circuit breaker of gen  // He reame=
d Circuit breaker of gen and gen manually started","system","2316","12-10-2=
024 13:20:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003307017","EMANA BI=
LICK CITY","","12-10-2024 13:20:10","12-10-2024 12:41:34","12-10-2024 13:10=
:54","Cascaded Incident from TTO3175775","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site was on Gen due to Grid=
 fluctuation, site went down due to disjunction Circuit breaker of gen  // =
He reamed Circuit breaker of gen and gen manually started","system","2316",=
"12-10-2024 13:20:10","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_444","NOCINC0003306920","Dong","","=
12-10-2024 13:04:48","","","Grid outage site alarming because Gen Failed to=
 start due to Gen battery faulty// he Gen started with external battery","P=
arker Tchoup","Warning","Warning","POWER","Warning - Site on Battery","Grid=
 outage site alarming because Gen Failed to start due to Gen battery faulty=
// he Gen started with external battery","stephane.nkamwa@ihstowers.com","2=
47","12-10-2024 13:04:48","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0003306794","Ole=
mbe","IHS_YND_276, IHS_YND_523, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_=
YND_306, IHS_YND_279, IHS_YND_303, IHS_YND_280, IHS_YND_304","12-10-2024 12=
:44:46","12-10-2024 12:41:34","12-10-2024 13:10:54","Site was on Gen due to=
 Grid fluctuation, site went down due to disjunction Circuit breaker of gen=
  // He reamed Circuit breaker of gen and gen manually started","Fabrice Po=
uakam","Equipment Repair","Passive","ACDG Gen","ACDG - Load Breaker","Site =
was on Gen due to Grid fluctuation, site went down due to disjunction Circu=
it breaker of gen  // He reamed Circuit breaker of gen and gen manually sta=
rted","kamga.virgile@ihstowers.com","590","12-10-2024 12:44:46","Sagemcom C=
MR"
"Closed Complete","Warning","","IHS_YND_305","NOCINC0003306627","NYOM","","=
12-10-2024 12:28:12","","","Grid bad voltage//Bypass grid and manually star=
t of DG.","Fabrice Pouakam","Warning","Warning","POWER","Warning - National=
 Grid - Grid Incomplete Phase","Grid outage Main gen faulty , deployment on=
going from Douala//Mobile DG deployed.","stephane.nkamwa@ihstowers.com","48=
8","12-10-2024 12:28:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0003306611","M=
vog-Ada_OCM","","12-10-2024 12:24:54","12-10-2024 12:13:48","12-10-2024 22:=
15:48","Grid outage No space to deploy // Grid power return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No spa=
ce to deploy // Grid power return","alexandre.kamal@ihstowers.com","809","1=
2-10-2024 12:24:54","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_381","NOCINC0003306606","Boumnyebel=
","","12-10-2024 12:23:23","","","site alarming Grid fluctuation before Gen=
 start and stopped due to Gid bad voltage// Grid stabilized","Kemeni Frankl=
in","Warning","Warning","POWER","Warning - Site on Battery","site alarming =
Grid fluctuation before Gen start and stopped due to Gid bad voltage// Grid=
 stabilized","stephane.nkamwa@ihstowers.com","309","12-10-2024 12:23:23","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003306228","E=
ssomba","","12-10-2024 11:36:58","12-10-2024 11:21:48","12-10-2024 12:12:04=
","Grid outage, site went down because gen fails to start due to gen overlo=
ad(15Kva, 210A)// he reduice the load on site, site on gen","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,=
 site went down because gen fails to start due to gen overload(15Kva, 210A)=
// he reduice the load on site, site on gen","alexandre.kamal@ihstowers.com=
","911","12-10-2024 11:36:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0003306185","Mvog-Eba=
nda","","12-10-2024 11:27:10","12-10-2024 11:17:34","12-10-2024 11:25:56","=
Cascaded Incident from TTO3175053","Siligap Boris","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site Ubaie=3D53V sit=
e on Grid.  The Tx FME Armand//671716363  from Huawei is informed","system"=
,"576","12-10-2024 11:27:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003306182","A=
bom","IHS_YND_269","12-10-2024 11:26:42","12-10-2024 11:17:34","12-10-2024 =
11:25:56","No power issue on site Ubaie=3D53V site on Grid.  The Tx FME Arm=
and//671716363  from Huawei is informed","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site Ubaie=3D53V site on Grid.  The Tx FME Armand//671716363  f=
rom Huawei is informed","alexandre.kamal@ihstowers.com","549","12-10-2024 1=
1:26:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003306111","A=
kak-Nkozoa-MTN-IHS","","12-10-2024 11:16:24","12-10-2024 11:02:21","12-10-2=
024 12:08:26","Grid fluctuation, site went down because Gen start and stopp=
ed due to Grid bad voltage // he bypass Grid and manually start the Gen","F=
abrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid fluctuation, site went down because Gen start and stopp=
ed due to Grid bad voltage // he bypass Grid and manually start the Gen","a=
lexandre.kamal@ihstowers.com","844","12-10-2024 11:16:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0003306039","Olembe-T=
erminus","","12-10-2024 11:02:10","12-10-2024 09:33:10","12-10-2024 09:39:5=
1","Cascaded Incident from TTO3174307","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Gen start and stopped due to Grid bad voltage and RCP ON SITE//=
 he bypass Grid and manually start the Gen","system","5340","12-10-2024 11:=
02:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003305989","Messassi=
 okolo","","12-10-2024 10:54:51","12-10-2024 09:33:10","12-10-2024 09:39:51=
","Cascaded Incident from TTO3174307","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation, site went do=
wn because Gen start and stopped due to Grid bad voltage and RCP ON SITE// =
he bypass Grid and manually start the Gen","system","4901","12-10-2024 10:5=
4:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0003305988","EMANA BI=
LICK CITY","","12-10-2024 10:54:50","12-10-2024 09:33:10","12-10-2024 09:39=
:51","Cascaded Incident from TTO3174307","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went=
 down because Gen start and stopped due to Grid bad voltage and RCP ON SITE=
// he bypass Grid and manually start the Gen","system","4900","12-10-2024 1=
0:54:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0003305828","Nkolondo=
m","","12-10-2024 10:25:41","12-10-2024 09:33:10","12-10-2024 09:39:51","Ca=
scaded Incident from TTO3174307","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause Gen start and stopped due to Grid bad voltage and RCP ON SITE// he by=
pass Grid and manually start the Gen","system","3151","12-10-2024 10:25:41"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0003305826","Nyom OCM=
","","12-10-2024 10:25:41","12-10-2024 09:33:10","12-10-2024 09:39:51","Cas=
caded Incident from TTO3174307","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Gen start and stopped due to Grid bad voltage and RCP ON SITE// he byp=
ass Grid and manually start the Gen","system","3151","12-10-2024 10:25:41",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0003305827","Messassi=
 2","","12-10-2024 10:25:41","12-10-2024 09:33:10","12-10-2024 09:39:51","C=
ascaded Incident from TTO3174307","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause Gen start and stopped due to Grid bad voltage and RCP ON SITE// he b=
ypass Grid and manually start the Gen","system","3151","12-10-2024 10:25:41=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0003305825","Nkozoa",=
"","12-10-2024 10:25:41","12-10-2024 09:33:10","12-10-2024 09:39:51","Casca=
ded Incident from TTO3174307","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se Gen start and stopped due to Grid bad voltage and RCP ON SITE// he bypas=
s Grid and manually start the Gen","system","3151","12-10-2024 10:25:41","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0003305822","Ekombiti=
e","","12-10-2024 10:25:40","12-10-2024 09:33:10","12-10-2024 09:39:51","Ca=
scaded Incident from TTO3174307","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation, site went down be=
cause Gen start and stopped due to Grid bad voltage and RCP ON SITE// he by=
pass Grid and manually start the Gen","system","3150","12-10-2024 10:25:40"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0003305823","NKOLMEKO=
NG YDE","","12-10-2024 10:25:40","12-10-2024 09:33:10","12-10-2024 09:39:51=
","Cascaded Incident from TTO3174307","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation, site went do=
wn because Gen start and stopped due to Grid bad voltage and RCP ON SITE// =
he bypass Grid and manually start the Gen","system","3150","12-10-2024 10:2=
5:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0003305824","Messassi=
","","12-10-2024 10:25:40","12-10-2024 09:33:10","12-10-2024 09:39:51","Cas=
caded Incident from TTO3174307","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Gen start and stopped due to Grid bad voltage and RCP ON SITE// he byp=
ass Grid and manually start the Gen","system","3150","12-10-2024 10:25:40",=
"Sagemcom CMR"
"Cancelled","Warning","CTR_383","IHS_YND_300","NOCINC0003305722","Olembe-Te=
rminus","","12-10-2024 10:02:03","","","","Fabrice Pouakam","","","","","",=
"alexandre.kamal@ihstowers.com","544","12-10-2024 10:02:03","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0003305660","NKO=
LOSSAN OKOK","","12-10-2024 09:56:22","12-10-2024 09:01:12","12-10-2024 11:=
23:03","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","kamga.virgile@ihstowers.com","3310","12-10-2024 09:56:22"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003305543","O=
lembe","IHS_YND_276, IHS_YND_523, IHS_YND_681, IHS_YND_300, IHS_YND_297, IH=
S_YND_306, IHS_YND_279, IHS_YND_303, IHS_YND_280, IHS_YND_304","12-10-2024 =
09:39:16","12-10-2024 09:33:10","12-10-2024 10:57:51","Grid fluctuation, si=
te went down because Gen start and stopped due to Grid bad voltage and RCP =
ON SITE// he bypass Grid and manually start the Gen","Fabrice Pouakam","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation, site went down because Gen start and stopped due to Grid bad v=
oltage and RCP ON SITE// he bypass Grid and manually start the Gen","alexan=
dre.kamal@ihstowers.com","367","12-10-2024 09:39:16","Sagemcom CMR"
"Closed Complete","Warning","T0729","IHS_EDA_052","NOCINC0003305337","Nyaho=
o","","12-10-2024 09:20:07","","","site alarming Grid outage Gen started an=
d stopped due to low oil pressure alarm// He add oil and Gen manually start=
ed","TIENTCHEU NZETCHIEU GAEL","Warning","Warning","POWER","Warning - Site =
on Gen","site alarming Grid outage Gen started and stopped due to low oil p=
ressure alarm// He add oil and Gen manually started","ludovic.tchagna@ihsto=
wers.com","75","12-10-2024 09:20:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003304320","L=
abogenie","","12-10-2024 06:20:32","12-10-2024 06:09:59","12-10-2024 06:15:=
48","No power issue, site is on grid with Ubaie=3D54,8V, Hurgo(672390202) f=
rom Huawei is informed,Repetitif issue","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site=
 is on grid with Ubaie=3D54,8V, Hurgo(672390202) from Huawei is informed,Re=
petitif issue","alexandre.kamal@ihstowers.com","634","12-10-2024 06:20:32",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003302825","N=
gouetou","","12-10-2024 00:20:31","12-10-2024 00:13:26","12-10-2024 01:41:0=
1","No power issue on site ,site on Gen with Ubaie=3D52V, Tx Fme Gregoire( =
652070658)From Huawei is informed and Up 00:25 AM","Parker Tchoup","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site ,site on Gen with Ubaie=3D52V, Tx Fme Gregoire( =
652070658)From Huawei is informed and Up 00:25 AM","joelle.ekessi@ihstowers=
.com","426","12-10-2024 00:20:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003302501","L=
abogenie","","11-10-2024 23:10:34","11-10-2024 23:03:30","11-10-2024 23:49:=
19","No power issue, site is on grid with Ubaie=3D54,8V, Hurgo(672390202) f=
rom Huawei is informed","","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue, site is on grid with=
 Ubaie=3D54,8V, Hurgo(672390202) from Huawei is informed","joelle.ekessi@ih=
stowers.com","425","11-10-2024 23:10:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_190","NOCINC0003302059","Ngousso-=
II","","11-10-2024 22:02:22","11-10-2024 19:39:11","12-10-2024 00:44:28","A=
ctive// No power Issue on site, Site on Grid Ubai=3D53,4V Fme Tx Armand Nge=
tsa/691144412/From Huawei is informed, Notice that we have disjunction at B=
TS OCM","MFOUAGUEGUE MATHIEU","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue on site, =
Site on Grid Ubai=3D53,4V Fme Tx Armand Ngetsa/691144412/From Huawei is inf=
ormed, Notice that we have disjunction at BTS OCM","ange.kongo@ihstowers.co=
m","8592","11-10-2024 22:02:22","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003301906","Nko=
g-Edzen","","11-10-2024 21:38:52","11-10-2024 21:32:42","11-10-2024 23:28:1=
7","site went down becaus gen stopped with alarm high temp//he open all the=
 door and restarted it","Parker Tchoup","Equipment Repair","Passive","ACDG =
Gen","ACDG - High Engine Temp - Coolant Level Issue","site went down becaus=
 gen stopped with alarm high temp//he open all the door and restarted it","=
denis.mballa@ihstowers.com","371","11-10-2024 21:38:52","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003301804","Eko=
unou","","11-10-2024 21:24:38","11-10-2024 21:16:27","11-10-2024 21:24:10",=
"Grid outage, site went down before Gen start due to poor battery backup// =
Gen started automatically","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen start due to poor battery backup// Gen started automatically","deni=
s.mballa@ihstowers.com","493","11-10-2024 21:24:38","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003301723","ODZ=
A MINKAN EDIBI ASSI","","11-10-2024 21:12:08","11-10-2024 21:03:57","11-10-=
2024 23:09:57","site went down because gen failed to start due to hybrid sy=
stem disfunctionning//Gen manually started","Albran Byorel","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","site went down because gen=
 failed to start due to hybrid system disfunctionning//Gen manually started=
","denis.mballa@ihstowers.com","491","11-10-2024 21:12:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0003301603","E=
koumdoum","","11-10-2024 20:57:17","11-10-2024 20:46:12","11-10-2024 22:04:=
12","grid outage,site went down because gen failed to start due to contacto=
r gen disfunction//he bypassed the contactor and started the gen manually",=
"Albran Byorel","Equipment Repair","Passive","Control Panel","ATS-AMF Issue=
","grid outage,site went down because gen failed to start due to contactor =
gen disfunction//he bypassed the contactor and started the gen manually","a=
nge.kongo@ihstowers.com","666","11-10-2024 20:57:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003301593","M=
vog-Manga","","11-10-2024 20:55:39","11-10-2024 20:44:31","11-10-2024 22:32=
:31","grid outage,gen failed start due to controller Psc3 faulty//Gen manua=
ly started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","grid outage,gen failed start due to controller Psc3 faulty=
//Gen manualy started","ange.kongo@ihstowers.com","670","11-10-2024 20:55:3=
9","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003301513","S=
ous Prefecture","","11-10-2024 20:38:19","11-10-2024 20:35:58","11-10-2024 =
20:45:38","Active: no power issue, site is on grid with Ubaie=3D53V, Rm Ala=
in(691144423) from Huawei is informed","Fanda Brice","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no=
 power issue, site is on grid with Ubaie=3D53V, Rm Alain(691144423) from Hu=
awei is informed","ange.kongo@ihstowers.com","142","11-10-2024 20:38:19","S=
agemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003301426","Eko=
unou","","11-10-2024 20:25:35","11-10-2024 20:21:45","11-10-2024 20:32:57",=
"Grid outage, site went down before Gen start due to poor battery backup// =
Gen started automatically","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen start due to poor battery backup// Gen started automatically","deni=
s.mballa@ihstowers.com","306","11-10-2024 20:25:35","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0003301352","Awa=
e Ewonkan","","11-10-2024 20:12:09","11-10-2024 20:00:04","11-10-2024 20:19=
:11","Grid outage, site went down before Gen start due to poor battery back=
up// Gen started automatically","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before Gen start due to poor battery backup// Gen started automatically",=
"denis.mballa@ihstowers.com","1152","11-10-2024 20:12:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003300835","A=
wae Escalier","","11-10-2024 18:44:09","11-10-2024 18:41:00","11-10-2024 19=
:33:16","Grid fluctuation, site went down before Gen start due to poor batt=
ery backup// Gen started automatically","Albran Byorel","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid fluctuation, =
site went down before Gen start due to poor battery backup// Gen started au=
tomatically","ange.kongo@ihstowers.com","190","11-10-2024 18:44:09","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0003300696","SAA Entr=
ance","","11-10-2024 18:25:40","11-10-2024 18:20:10","11-10-2024 19:04:15",=
"Cascaded Incident from TTO3168723","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation, site went down b=
ecause Gen start and stopped due to Grid bad voltage no RCP// he bypass Gri=
d and manually start the Gen","system","330","11-10-2024 18:25:40","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003300697","Saa","",=
"11-10-2024 18:25:40","11-10-2024 18:20:10","11-10-2024 19:04:15","Cascaded=
 Incident from TTO3168723","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuation, site went down because Ge=
n start and stopped due to Grid bad voltage no RCP// he bypass Grid and man=
ually start the Gen","system","330","11-10-2024 18:25:40","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0003300690","SAA=
 2","IHS_YND_542, IHS_YND_405","11-10-2024 18:24:16","11-10-2024 18:15:19",=
"11-10-2024 19:04:44","Grid fluctuation, site went down because Gen start a=
nd stopped due to Grid bad voltage no RCP// he bypass Grid and manually sta=
rt the Gen","Parker Tchoup","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Grid fluctuation, site went down because Gen sta=
rt and stopped due to Grid bad voltage no RCP// he bypass Grid and manually=
 start the Gen","denis.mballa@ihstowers.com","1034","11-10-2024 18:24:16","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0003300386","A=
nguissa New","","11-10-2024 17:39:03","11-10-2024 17:36:57","11-10-2024 17:=
39:17","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen started automatically","MINKA NICOLAS","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen started automatical=
ly","ange.kongo@ihstowers.com","127","11-10-2024 17:39:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003300209","Crf Corn=
ier","","11-10-2024 17:02:01","11-10-2024 16:51:57","11-10-2024 17:31:36","=
Cascaded Incident from TTO3168127","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down because CB(125A) tri=
pped in DC BOX// CB put back on","system","604","11-10-2024 17:02:01","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003300205","M=
adison","IHS_YND_566","11-10-2024 17:01:06","11-10-2024 16:51:57","11-10-20=
24 17:31:36","Site went down because CB(125A) tripped in DC BOX// CB put ba=
ck on","MFOUAGUEGUE MATHIEU","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Circuit Breaker Issue","Site went down because CB(125A) tri=
pped in DC BOX// CB put back on","ange.kongo@ihstowers.com","549","11-10-20=
24 17:01:06","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003299789","N=
yanon","","11-10-2024 15:54:24","11-10-2024 15:46:16","11-10-2024 17:54:21"=
,"No power issue site on Gen ubaie=3D55.3V. The TX FME Gr=E9goire  //654547=
479//  from huawei is informed .","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue site on Gen ubaie=3D55.3V. The TX FME Gr=E9goire  //654547479/=
/  from huawei is informed .","ange.kongo@ihstowers.com","489","11-10-2024 =
15:54:24","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003299183","Bas=
tos Amb Coree","","11-10-2024 14:59:14","11-10-2024 14:57:02","11-10-2024 1=
4:59:02","Site went down due to insufficiency of Rectifires //Site stabiliz=
ed,rectifiers must be upgraded.","","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down due to insufficiency of Rectifires //S=
ite stabilized,rectifiers must be upgraded.","denis.mballa@ihstowers.com","=
133","11-10-2024 14:59:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003299051","Crf Corn=
ier","","11-10-2024 14:42:44","11-10-2024 14:23:10","11-10-2024 14:40:58","=
Cascaded Incident from TTO3166703","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because PSC3 disfunc=
tionning due to Cb(10A) of extrator tripped //He make a bridged with anothe=
r Cb, site on grid","system","1174","11-10-2024 14:42:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_065","NOCINC0003299050","Essos DC=
S","","11-10-2024 14:42:43","11-10-2024 14:23:10","11-10-2024 14:40:58","Ca=
scaded Incident from TTO3166703","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because PSC3 disfunct=
ionning due to Cb(10A) of extrator tripped //He make a bridged with another=
 Cb, site on grid","system","1173","11-10-2024 14:42:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_097","NOCINC0003299049","Kondengu=
i MTN","","11-10-2024 14:42:43","11-10-2024 14:23:10","11-10-2024 14:40:58"=
,"Cascaded Incident from TTO3166703","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because PSC3 disfu=
nctionning due to Cb(10A) of extrator tripped //He make a bridged with anot=
her Cb, site on grid","system","1173","11-10-2024 14:42:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003299048","Kondengu=
i","","11-10-2024 14:42:43","11-10-2024 14:23:10","11-10-2024 14:40:58","Ca=
scaded Incident from TTO3166703","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site went down because PSC3 disfuncti=
onning due to Cb(10A) of extrator tripped //He make a bridged with another =
Cb, site on grid","system","1173","11-10-2024 14:42:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_178","NOCINC0003299047","Emombo",=
"","11-10-2024 14:42:43","11-10-2024 14:23:10","11-10-2024 14:40:58","Casca=
ded Incident from TTO3166703","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site went down because PSC3 disfuncti=
onning due to Cb(10A) of extrator tripped //He make a bridged with another =
Cb, site on grid","system","1173","11-10-2024 14:42:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003299046","Anguissa=
 New","","11-10-2024 14:42:43","11-10-2024 14:23:10","11-10-2024 14:40:58",=
"Cascaded Incident from TTO3166703","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because PSC3 disfun=
ctionning due to Cb(10A) of extrator tripped //He make a bridged with anoth=
er Cb, site on grid","system","1173","11-10-2024 14:42:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_113","NOCINC0003299043","Emombo 2=
","","11-10-2024 14:42:42","11-10-2024 14:23:10","11-10-2024 14:40:58","Cas=
caded Incident from TTO3166703","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because PSC3 disfunctio=
nning due to Cb(10A) of extrator tripped //He make a bridged with another C=
b, site on grid","system","1172","11-10-2024 14:42:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_025","NOCINC0003299044","CORNIERS=
","","11-10-2024 14:42:42","11-10-2024 14:23:10","11-10-2024 14:40:58","Cas=
caded Incident from TTO3166703","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","site went down because PSC3 disfunctionning due to =
Cb(10A) of extrator tripped //He make a bridged with another Cb, site on gr=
id","system","1172","11-10-2024 14:42:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_120","NOCINC0003299042","Sapeur M=
imboman","","11-10-2024 14:42:42","11-10-2024 14:23:10","11-10-2024 14:40:5=
8","Cascaded Incident from TTO3166703","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","site went down because PSC3 =
disfunctionning due to Cb(10A) of extrator tripped //He make a bridged with=
 another Cb, site on grid","system","1172","11-10-2024 14:42:42","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0003299045","Mobil-Es=
sos","","11-10-2024 14:42:42","11-10-2024 14:23:10","11-10-2024 14:40:58","=
Cascaded Incident from TTO3166703","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because PSC3 disfunc=
tionning due to Cb(10A) of extrator tripped //He make a bridged with anothe=
r Cb, site on grid","system","1172","11-10-2024 14:42:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_063","NOCINC0003299041","Av-Germa=
ine","","11-10-2024 14:42:42","11-10-2024 14:23:10","11-10-2024 14:40:58","=
Cascaded Incident from TTO3166703","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","site went down because PSC3 disfunctionning due =
to Cb(10A) of extrator tripped //He make a bridged with another Cb, site on=
 grid","system","1172","11-10-2024 14:42:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_797","NOCINC0003299037","Messassi=
 Carrefourt","","11-10-2024 14:42:41","11-10-2024 14:23:10","11-10-2024 14:=
40:58","Cascaded Incident from TTO3166703","Delor Telezing","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","site went down because PSC=
3 disfunctionning due to Cb(10A) of extrator tripped //He make a bridged wi=
th another Cb, site on grid","system","1171","11-10-2024 14:42:41","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_108","NOCINC0003299039","RUE FOE"=
,"","11-10-2024 14:42:41","11-10-2024 14:23:10","11-10-2024 14:40:58","Casc=
aded Incident from TTO3166703","Delor Telezing","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because PSC3 disfunctio=
nning due to Cb(10A) of extrator tripped //He make a bridged with another C=
b, site on grid","system","1171","11-10-2024 14:42:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_122","NOCINC0003299038","Emombo E=
sssomba","","11-10-2024 14:42:41","11-10-2024 14:23:10","11-10-2024 14:40:5=
8","Cascaded Incident from TTO3166703","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","site went down because PSC3 =
disfunctionning due to Cb(10A) of extrator tripped //He make a bridged with=
 another Cb, site on grid","system","1171","11-10-2024 14:42:41","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_180","NOCINC0003299036","Mimboman=
","","11-10-2024 14:42:41","11-10-2024 14:23:10","11-10-2024 14:40:58","Cas=
caded Incident from TTO3166703","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because PSC3 disfunc=
tionning due to Cb(10A) of extrator tripped //He make a bridged with anothe=
r Cb, site on grid","system","1171","11-10-2024 14:42:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_189","NOCINC0003299040","Paradis =
Hotel","","11-10-2024 14:42:41","11-10-2024 14:23:10","11-10-2024 14:40:58"=
,"Cascaded Incident from TTO3166703","Siligap Boris","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because PSC3 disfu=
nctionning due to Cb(10A) of extrator tripped //He make a bridged with anot=
her Cb, site on grid","system","1171","11-10-2024 14:42:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0003299033","MONTEE N=
KONDENGUI","","11-10-2024 14:42:40","11-10-2024 14:23:10","11-10-2024 14:40=
:58","Cascaded Incident from TTO3166703","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because PSC3 d=
isfunctionning due to Cb(10A) of extrator tripped //He make a bridged with =
another Cb, site on grid","system","1170","11-10-2024 14:42:40","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_111","NOCINC0003299034","Essos Ma=
rche","","11-10-2024 14:42:40","11-10-2024 14:23:10","11-10-2024 14:40:58",=
"Cascaded Incident from TTO3166703","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because PSC3 disfu=
nctionning due to Cb(10A) of extrator tripped //He make a bridged with anot=
her Cb, site on grid","system","1170","11-10-2024 14:42:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_042","NOCINC0003299035","Mvog-Ada=
_OCM","","11-10-2024 14:42:40","11-10-2024 14:23:10","11-10-2024 14:40:58",=
"Cascaded Incident from TTO3166703","","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","site went down because PSC3 disfunctionning due=
 to Cb(10A) of extrator tripped //He make a bridged with another Cb, site o=
n grid","system","1170","11-10-2024 14:42:40","Sagemcom CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0003298995","Cam=
p-Sonel","IHS_YND_682, IHS_YND_111, IHS_YND_042, IHS_YND_180, IHS_YND_797, =
IHS_YND_122, IHS_YND_108, IHS_YND_189, IHS_YND_063, IHS_YND_120, IHS_YND_11=
3, IHS_YND_025, IHS_YND_109, IHS_YND_568, IHS_YND_178, IHS_YND_114, IHS_YND=
_097, IHS_YND_065, IHS_YND_566","11-10-2024 14:39:23","11-10-2024 14:23:10"=
,"11-10-2024 14:40:58","site went down because PSC3 disfunctionning due to =
Cb(10A) of extrator tripped //He make a bridged with another Cb, site on gr=
id","Siligap Boris","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Circuit Breaker Issue","site went down because PSC3 disfunctionning =
due to Cb(10A) of extrator tripped //He make a bridged with another Cb, sit=
e on grid","denis.mballa@ihstowers.com","974","11-10-2024 14:39:23","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0003298987","O=
bobogo","","11-10-2024 14:38:54","11-10-2024 14:02:47","11-10-2024 19:32:31=
","Active, no power issue, site on grid with U=3D54V, FME tx Ngankeu Fabric=
e/695524845/omnium service/ is Working on site","MINKA NICOLAS","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active, no power issue, site on grid with U=3D54V, FME tx Ngankeu Fabrice/=
695524845/omnium service/ is Working on site","ange.kongo@ihstowers.com","2=
168","11-10-2024 14:38:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003298918","N=
GONA","","11-10-2024 14:31:18","11-10-2024 14:23:11","11-10-2024 19:39:37",=
"No power issue, site is on grid with Ubaie=3D56V, Lionel adjep(655184876) =
from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, sit=
e is on grid with Ubaie=3D56V, Lionel adjep(655184876) from Huawei is infor=
med","ange.kongo@ihstowers.com","488","11-10-2024 14:31:18","Sagemcom CMR"
"Cancelled","Warning","T0420","IHS_YND_082","NOCINC0003298709","Mokolo Yaou=
nde","","11-10-2024 13:53:18","","","","","","","","","","olivier.kwedi@ihs=
towers.com","727","11-10-2024 13:53:18","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003297933","Nko=
lmvack","","11-10-2024 12:09:16","11-10-2024 11:54:59","11-10-2024 13:14:59=
","Eta 12h45","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Oil Leakage","gen stopped due to oil leakage at the level of engine//add=
ed oil (investigatios ongoing)","olivier.kwedi@ihstowers.com","859","11-10-=
2024 12:09:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003297711","Ngouetou=
","","11-10-2024 12:03:11","11-10-2024 11:55:39","11-10-2024 12:06:39","Cas=
caded Incident from TTO3165167","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site down due to planned work of Felix=
 Bateu (IHS Supervisor)//end of work","system","452","11-10-2024 12:03:11",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003297710","Ngoum","=
","11-10-2024 12:03:11","11-10-2024 11:55:39","11-10-2024 12:06:39","Cascad=
ed Incident from TTO3165167","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site down due to planned work of Felix Ba=
teu (IHS Supervisor)//end of work","system","452","11-10-2024 12:03:11","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003297713","Dong",""=
,"11-10-2024 12:03:11","11-10-2024 11:55:39","11-10-2024 12:06:39","Cascade=
d Incident from TTO3165167","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","site down due to planned work of Felix Bat=
eu (IHS Supervisor)//end of work","system","452","11-10-2024 12:03:11","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003297707","Nguila",=
"","11-10-2024 12:03:10","11-10-2024 11:55:39","11-10-2024 12:06:39","Casca=
ded Incident from TTO3165167","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site down due to planned work of Felix B=
ateu (IHS Supervisor)//end of work","system","451","11-10-2024 12:03:10","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003297708","MBIMBIM"=
,"","11-10-2024 12:03:10","11-10-2024 11:55:39","11-10-2024 12:06:39","Casc=
aded Incident from TTO3165167","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site down due to planned work of Felix =
Bateu (IHS Supervisor)//end of work","system","451","11-10-2024 12:03:10","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003297709","Matsari"=
,"","11-10-2024 12:03:10","11-10-2024 11:55:39","11-10-2024 12:06:39","Casc=
aded Incident from TTO3165167","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site down due to planned work of Felix =
Bateu (IHS Supervisor)//end of work","system","451","11-10-2024 12:03:10","=
Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0003297635","Don=
ga","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_Y=
ND_444","11-10-2024 12:00:51","11-10-2024 11:55:39","11-10-2024 12:06:39","=
","Parker Tchoup","Installation Activity","Passive","Planned Activity","Ins=
tallation Activity","site down due to planned work of Felix Bateu (IHS Supe=
rvisor)//end of work","olivier.kwedi@ihstowers.com","313","11-10-2024 12:00=
:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003297117","T=
amtam Weekend","","11-10-2024 11:25:36","11-10-2024 11:21:32","11-10-2024 1=
2:05:32","Active: no power issue, site is on grid with Ubaie=3D54,4V, the f=
me tx Mbah Hosiah(699699694) from Huawei is informed, repetitif issue","Hye=
mafo Gildas","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active: no power issue, site is on grid with Ubaie=
=3D54,4V, the fme tx Mbah Hosiah(699699694) from Huawei is informed, repeti=
tif issue","dorothy.djantio@ihstowers.com","245","11-10-2024 11:25:36","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0003297105","D=
amas","","11-10-2024 11:23:22","11-10-2024 11:20:13","11-10-2024 12:00:13",=
"Active//No power isue on site ,site on Grid with Ubaie=3D54,2V TX FME Hosi=
ah// 674007438 from Huawei is informed","MINKA NICOLAS","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power isue on site ,site on Grid with Ubaie=3D54,2V TX FME Hosiah// 674=
007438 from Huawei is informed","dorothy.djantio@ihstowers.com","189","11-1=
0-2024 11:23:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0003296391","Mom","",=
"11-10-2024 09:51:21","10-10-2024 19:22:58","10-10-2024 19:30:58","Cascaded=
 Incident from TTO3163755","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Active: no power issue, site is on grid with Uba=
ie=3D53V,Lionel Adjed (655184876) from Huawei is informed","system","52103"=
,"11-10-2024 09:51:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0003296390","OTELE MT=
N","","11-10-2024 09:51:20","10-10-2024 19:22:58","10-10-2024 19:30:58","Ca=
scaded Incident from TTO3163755","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active: no power issue, site is on grid wi=
th Ubaie=3D53V,Lionel Adjed (655184876) from Huawei is informed","system","=
52102","11-10-2024 09:51:20","Sagemcom CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0003296382","Min=
ka","IHS_YND_531, IHS_YND_370","11-10-2024 09:50:13","10-10-2024 19:22:58",=
"10-10-2024 19:30:58","Active: no power issue, site is on grid with Ubaie=
=3D53V,Lionel Adjed (655184876) from Huawei is informed","Fanda Brice","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active: no power issue, site is on grid with Ubaie=3D53V,Lionel Adj=
ed (655184876) from Huawei is informed","olivier.kwedi@ihstowers.com","5203=
6","11-10-2024 09:50:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003296371","N=
GONA","","11-10-2024 09:49:21","11-10-2024 09:46:17","11-10-2024 10:40:17",=
"No power issue, site is on grid with Ubaie=3D56V, Lionel adjep(655184876) =
from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, sit=
e is on grid with Ubaie=3D56V, Lionel adjep(655184876) from Huawei is infor=
med","dorothy.djantio@ihstowers.com","185","11-10-2024 09:49:21","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003296326","A=
KONGO","","11-10-2024 09:40:07","11-10-2024 09:37:01","11-10-2024 10:15:01"=
,"ctive//No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rodri=
gue (655102999)from Huawei is informed. Repetitive issue","Fanda Brice","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","ctive//No power issue on site Ubaie=3D52,5V site on Gen. The Tx FM=
E Rodrigue (655102999)from Huawei is informed. Repetitive issue","dorothy.d=
jantio@ihstowers.com","187","11-10-2024 09:40:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003295570","T=
ongolo OCM","","11-10-2024 07:25:19","11-10-2024 07:15:59","11-10-2024 09:3=
7:59","Site went down due to Burnt grid contactor, fuse and circuit breaker=
 and gen starter faulty // He bypass it and site on grid","Delor Telezing",=
"Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Site went dow=
n due to Burnt grid contactor, fuse and circuit breaker and gen starter fau=
lty // He bypass it and site on grid","dorothy.djantio@ihstowers.com","561"=
,"11-10-2024 07:25:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003295267","Yoko OCM=
","","11-10-2024 06:27:01","11-10-2024 06:08:20","11-10-2024 06:59:59","Cas=
caded Incident from TTO3162425","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on Solar;=
 Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informe=
d.","system","1121","11-10-2024 06:27:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003295268","Ngouetou=
","","11-10-2024 06:27:01","11-10-2024 06:08:20","11-10-2024 06:59:59","Cas=
caded Incident from TTO3162425","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on Solar;=
 Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informe=
d.","system","1121","11-10-2024 06:27:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003295269","MBIMBIM"=
,"","11-10-2024 06:27:01","11-10-2024 06:08:20","11-10-2024 06:59:59","Casc=
aded Incident from TTO3162425","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on Solar; =
Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed=
.","system","1121","11-10-2024 06:27:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003295265","Ngoum","=
","11-10-2024 06:27:00","11-10-2024 06:08:20","11-10-2024 06:59:59","Cascad=
ed Incident from TTO3162425","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on Solar; Ub=
aie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","1120","11-10-2024 06:27:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003295266","Matsari"=
,"","11-10-2024 06:27:00","11-10-2024 06:08:20","11-10-2024 06:59:59","Casc=
aded Incident from TTO3162425","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on Solar; =
Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed=
.","system","1120","11-10-2024 06:27:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003295187","B=
ATA-Mokolo","","11-10-2024 06:04:37","11-10-2024 02:15:53","11-10-2024 10:0=
1:53","Grid outage no space to deploy MDG // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space =
to deploy MDG // Grid return","kouoh.jean@ihstowers.com","13725","11-10-202=
4 06:04:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0003295160","S=
apeur","","11-10-2024 05:54:10","11-10-2024 05:27:59","11-10-2024 09:15:59"=
,"Active, no power issue, site on grid with U=3D54V; Tx FME  Brice/65021409=
6/ From huawei is informed","Mboua Thierry","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power is=
sue, site on grid with U=3D54V; Tx FME  Brice/650214096/ From huawei is inf=
ormed","kouoh.jean@ihstowers.com","1572","11-10-2024 05:54:10","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003295141","L=
abogenie","","11-10-2024 05:43:30","11-10-2024 05:33:53","11-10-2024 05:44:=
52","grid outage,no space to deploy a mobil gen//grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no sp=
ace to deploy a mobil gen//grid return","kouoh.jean@ihstowers.com","578","1=
1-10-2024 05:43:30","Sagemcom CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0003294593","BEA=
TITUDE ENTR=C9E PAVE","","11-10-2024 03:07:02","11-10-2024 02:39:51","11-10=
-2024 03:21:46","Grid fluctuation, site went down because Gen start and sto=
pped due to Grid bad voltage no RCP// he bypass Grid and manually start the=
 Gen","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation, site went down because Ge=
n start and stopped due to Grid bad voltage no RCP// he bypass Grid and man=
ually start the Gen","landry.etame@ihstowers.com","1632","11-10-2024 03:07:=
02","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003294589","BAT=
A Mokolo OCM","","11-10-2024 03:06:04","11-10-2024 02:17:52","11-10-2024 10=
:01:52","Grid outage, no space to deploy a MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no =
space to deploy a MDG // Grid return","landry.etame@ihstowers.com","2893","=
11-10-2024 03:06:04","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0003294199","OTE=
LE MTN","","11-10-2024 01:06:17","11-10-2024 00:39:07","11-10-2024 00:40:10=
","Active//No power issue, site is on Grid with Ubaie=3D52,3V,Etienne (6950=
33981) from Huawei is informed","Fanda Brice","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power =
issue, site is on Grid with Ubaie=3D52,3V,Etienne (695033981) from Huawei i=
s informed","landry.etame@ihstowers.com","1631","11-10-2024 01:06:17","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003292844","B=
iteng-Maetur","","10-10-2024 21:00:01","10-10-2024 20:55:51","10-10-2024 21=
:03:27","No power issue on site ,site on Grid wth Ubaie=3D53,8 V The Tx FME=
 Lionel adjep(655184876) from Huawei is informed adn up at 09:03 PM","Mba L=
azare Herve","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","No power issue on site ,site on Grid wth Ubaie=3D5=
3,8 V The Tx FME Lionel adjep(655184876) from Huawei is informed adn up at =
09:03 PM","joelle.ekessi@ihstowers.com","252","10-10-2024 21:00:01","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003292756","Eto koss=
 Yde","","10-10-2024 20:43:10","10-10-2024 20:35:20","10-10-2024 21:06:07",=
"Cascaded Incident from TTO3159541","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bef=
ore Gen start because battery PWC did not charged // He bypass grid and man=
ually start the gen","system","470","10-10-2024 20:43:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003292757","ELOUMDEM=
 CARRIERE 2","","10-10-2024 20:43:10","10-10-2024 20:35:20","10-10-2024 21:=
06:07","Cascaded Incident from TTO3159541","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own before Gen start because battery PWC did not charged // He bypass grid =
and manually start the gen","system","470","10-10-2024 20:43:10","Sagemcom =
CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003292747","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","10-10-2024 20:41:23","10-10-2024 20:35=
:20","10-10-2024 21:06:07","Grid fluctuation, site went down before Gen sta=
rt because battery PWC did not charged // He bypass grid and manually start=
 the gen","Fanda Brice","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid fluctuation, site went down before Gen start be=
cause battery PWC did not charged // He bypass grid and manually start the =
gen","emmanuel.ghani@ihstowers.com","364","10-10-2024 20:41:23","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0003292694","N=
gousso-II","","10-10-2024 20:31:11","10-10-2024 20:29:08","10-10-2024 21:42=
:00","Active// No power Issue on site, Site on Grid Ubai=3D53,5V Fme Tx Arm=
and Ngetsa/691144412/From Huawei is informed, Notice that we have disjuncti=
on at BTS OCM","MFOUAGUEGUE MATHIEU","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue on=
 site, Site on Grid Ubai=3D53,5V Fme Tx Armand Ngetsa/691144412/From Huawei=
 is informed, Notice that we have disjunction at BTS OCM","joelle.ekessi@ih=
stowers.com","124","10-10-2024 20:31:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0003292671","M=
atomb","","10-10-2024 20:27:37","10-10-2024 20:21:33","10-10-2024 20:30:33"=
,"Site went down due to work Felix/657108520/Sagemcom is working on site (P=
M) // End of work","Kemeni Franklin","Installation Activity","Passive","Pla=
nned Activity","Installation Activity","Site went down due to work Felix/65=
7108520/Sagemcom is working on site (PM) // End of work","joelle.ekessi@ihs=
towers.com","364","10-10-2024 20:27:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003292054","C=
amp-Sic-Tsinga","","10-10-2024 18:54:58","10-10-2024 18:49:54","10-10-2024 =
19:26:18","Grid outage no space to deploy MDG// Grid restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no s=
pace to deploy MDG// Grid restored","joelle.ekessi@ihstowers.com","305","10=
-10-2024 18:54:58","Sagemcom CMR"
"Closed Complete","Site Down","T0183","IHS_YND_184","NOCINC0003291843","Nko=
lmesseng","","10-10-2024 18:16:49","10-10-2024 18:13:46","10-10-2024 21:30:=
21","Active// No power Issue on site, Site on Grid Ubai=3D53,8V Fme Tx Arma=
nd Ngetsa/691144412/From Huawei is informed","Siligap Boris","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power Issue on site, Site on Grid Ubai=3D53,8V Fme Tx Armand Nget=
sa/691144412/From Huawei is informed","emmanuel.ghani@ihstowers.com","184",=
"10-10-2024 18:16:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003291640","B=
riqueterie","","10-10-2024 17:47:37","10-10-2024 17:41:33","10-10-2024 17:5=
0:12"," No power issue, site is on Grid with ubaie=3D54,5V  the fme tx  Bri=
ce Tsague (650214096) from Huawei is informed,repetitif issue","","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
"," No power issue, site is on Grid with ubaie=3D54,5V  the fme tx  Brice T=
sague (650214096) from Huawei is informed,repetitif issue","joelle.ekessi@i=
hstowers.com","365","10-10-2024 17:47:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0003291378","Mom","",=
"10-10-2024 17:08:10","10-10-2024 17:00:13","10-10-2024 17:10:19","Cascaded=
 Incident from TTO3157901","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Active: no power issue, site is on Gen with Ubai=
e=3D55V, RM Martial (690087047) from Huawei is informed","system","477","10=
-10-2024 17:08:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0003291377","OTELE MT=
N","","10-10-2024 17:08:10","10-10-2024 17:00:13","10-10-2024 17:10:19","Ca=
scaded Incident from TTO3157901","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active: no power issue, site is on Gen wit=
h Ubaie=3D55V, RM Martial (690087047) from Huawei is informed","system","47=
7","10-10-2024 17:08:10","Sagemcom CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0003291367","Min=
ka","IHS_YND_531, IHS_YND_370","10-10-2024 17:07:17","10-10-2024 17:00:13",=
"10-10-2024 17:30:19","Active: no power issue, site is on Gen with Ubaie=3D=
55V, RM Martial (690087047) from Huawei is informed","Fanda Brice","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active: no power issue, site is on Gen with Ubaie=3D55V, RM Martial (69=
0087047) from Huawei is informed","emmanuel.ghani@ihstowers.com","424","10-=
10-2024 17:07:17","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0003291229","Man=
guiers Dispensaire","","10-10-2024 16:46:12","10-10-2024 16:45:07","10-10-2=
024 17:42:07","Grid fluctuation,DG started but did not feed the site due to=
 ENEO contactor faulty // He blocked the Grid contactor manually and site o=
n Grid.","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","AT=
S-AMF Issue","Grid fluctuation,DG started but did not feed the site due to =
ENEO contactor faulty // He blocked the Grid contactor manually and site on=
 Grid.","emmanuel.ghani@ihstowers.com","66","10-10-2024 16:46:12","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003291053","A=
kak-Nkozoa-MTN-IHS","","10-10-2024 16:24:50","10-10-2024 16:24:47","10-10-2=
024 17:04:52","Grid fluctuation , site went down because Gen started and st=
opped due to grid bad voltage // He bypassed Grid and started Gen manualy",=
"Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation , site went down because Gen started and =
stopped due to grid bad voltage // He bypassed Grid and started Gen manualy=
","joelle.ekessi@ihstowers.com","4","10-10-2024 16:24:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003291003","N=
kolondom","","10-10-2024 16:18:31","10-10-2024 16:16:24","10-10-2024 16:25:=
28","site went down because CB of Rectifier disjuncted due to grid fluctuat=
ion // CB put back on","Fabrice Pouakam","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","site went down because =
CB of Rectifier disjuncted due to grid fluctuation // CB put back on","joel=
le.ekessi@ihstowers.com","128","10-10-2024 16:18:31","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003290758","Bas=
tos Amb Coree","","10-10-2024 15:43:56","10-10-2024 15:42:52","10-10-2024 1=
5:45:52","Grid outage, no space to deploy a MDG // grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no=
 space to deploy a MDG // grid return","emmanuel.ghani@ihstowers.com","66",=
"10-10-2024 15:43:56","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0003290752","Ole=
mbe","","10-10-2024 15:42:46","10-10-2024 15:39:41","10-10-2024 16:11:57","=
Grid fluctuation, site went down because 2 CB Battery and CB rectifier trip=
ped in Pwc// CB put back on and Gen started manualy","Fabrice Pouakam","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker I=
ssue","Grid fluctuation, site went down because 2 CB Battery and CB rectifi=
er tripped in Pwc// CB put back on and Gen started manualy","emmanuel.ghani=
@ihstowers.com","450","10-10-2024 15:42:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003290671","M=
ANGUIERS CHAPELLE","","10-10-2024 15:32:34","10-10-2024 15:29:31","10-10-20=
24 15:45:32","Grid outage, site went down before gen start due to poor batt=
ery backup // Gen started automaticaly","Fabrice Pouakam","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // Gen started auto=
maticaly","joelle.ekessi@ihstowers.com","185","10-10-2024 15:32:34","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003290665","E=
lig-Edzoa","","10-10-2024 15:30:59","10-10-2024 15:28:43","10-10-2024 15:43=
:11","Grid outage// Grid restored","","Grid Supply","Passive","Grid","Natio=
nal Grid - Grid Outage Issue","Grid outage// Grid restored","joelle.ekessi@=
ihstowers.com","138","10-10-2024 15:30:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003290648","E=
lig Edzoa","","10-10-2024 15:28:16","10-10-2024 15:26:11","10-10-2024 15:29=
:11","Grid outage, site went down before gen start due to poor battery back=
up // gen start automatically","Delor Telezing","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // gen start automatically","=
joelle.ekessi@ihstowers.com","126","10-10-2024 15:28:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0003290260","P=
olytechnique","","10-10-2024 14:44:49","10-10-2024 14:09:45","10-10-2024 19=
:28:22","site down because CB(125A) tripped in new PWC ZTE installed/ //The=
 Team ZTE reamed the CB(125A)","","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","site down because CB(125A) tri=
pped in new PWC ZTE installed/ //The Team ZTE reamed the CB(125A)","joelle.=
ekessi@ihstowers.com","2105","10-10-2024 14:44:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003290182","N=
kolbisson usine des eaux","","10-10-2024 14:36:50","10-10-2024 14:33:46","1=
0-10-2024 14:39:46","Site was on Gen due to Grid outage, site went down bec=
ause gen stoppen with alarm""Over current""// He reduced de load, Site on G=
rid","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","AC=
DG - Control Panel","Site was on Gen due to Grid outage, site went down bec=
ause gen stoppen with alarm""Over current""// He reduced de load, Site on G=
rid","joelle.ekessi@ihstowers.com","185","10-10-2024 14:36:50","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0003290119","M=
eyo","IHS_YND_762","10-10-2024 14:27:05","10-10-2024 11:15:53","10-10-2024 =
11:27:53","site down  due to work of  tanga /696422966 / ZTE(CB installatio=
n)//end of work","Hyemafo Gildas","Installation Activity","Passive","Planne=
d Activity","Installation Activity","site down  due to work of  tanga /6964=
22966 / ZTE(CB installation)//end of work","ange.kongo@ihstowers.com","1147=
2","10-10-2024 14:27:05","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0003289790","Nko=
mkana","","10-10-2024 13:44:44","10-10-2024 13:23:37","10-10-2024 14:52:37"=
,"Grid outage, no space to deploy // grid return","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage, no space to depl=
oy // grid return","adonis.defokoua@ihstowers.com","1268","10-10-2024 13:44=
:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003289786","Akak-Nko=
zoa-MTN-IHS","","10-10-2024 13:44:00","10-10-2024 13:16:47","10-10-2024 13:=
57:52","Cascaded Incident from TTO3155841","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","outage, gen overloaded(22=
kva)//balanced the load","system","1633","10-10-2024 13:44:00","Sagemcom CM=
R"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0003289620","Mes=
sassi Ngonlonk","","10-10-2024 13:25:44","10-10-2024 13:16:47","10-10-2024 =
13:57:52","Site impacted by TTO3155841","Fabrice Pouakam","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","outage, gen overloaded(22kva=
)//balanced the load","adonis.defokoua@ihstowers.com","2514","10-10-2024 13=
:25:44","Sagemcom CMR"
"Closed Complete","Site Down","T0051","IHS_YND_297","NOCINC0003289609","Mes=
sassi","IHS_YND_316, IHS_YND_799","10-10-2024 13:23:53","10-10-2024 13:14:4=
7","10-10-2024 13:57:52","","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Overload","outage, gen overloaded(22kva)//balanced the l=
oad","adonis.defokoua@ihstowers.com","1346","10-10-2024 13:23:53","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0003289481","M=
essassi 2","","10-10-2024 13:05:30","10-10-2024 12:59:21","10-10-2024 14:09=
:05","Grid outage site went down because Gen failed to start due to Gen car=
d Disfunction//He reset Gen card and Gen manually  started ","Fabrice Pouak=
am","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid ou=
tage site went down because Gen failed to start due to Gen card Disfunction=
//He reset Gen card and Gen manually  started ","ange.kongo@ihstowers.com",=
"371","10-10-2024 13:05:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003289339","Crf Corn=
ier","","10-10-2024 12:49:31","10-10-2024 12:37:16","10-10-2024 12:53:32","=
no power issue on site ubaie=3D54v site on grid hugo is informedid","MINKA =
NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","no power issue on site ubaie=3D54v site on grid hugo i=
s informed","ange.kongo@ihstowers.com","736","10-10-2024 12:49:31","Sagemco=
m CMR"
"Closed Complete","Warning","T0051","IHS_YND_297","NOCINC0003289111","Messa=
ssi","","10-10-2024 12:23:27","","","","Fabrice Pouakam","Warning","Warning=
","POWER","Warning - AC Phase 3 Voltage low","Alarm cleared","adonis.defoko=
ua@ihstowers.com","490","10-10-2024 12:23:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0003288699","Nkolfon =
Cimencam","","10-10-2024 11:27:48","10-10-2024 11:15:53","10-10-2024 11:27:=
53","site down  due to work of  tanga /696422966 / ZTE(CB installation)//en=
d of work","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","C=
ascade Passive","site down  due to work of  tanga /696422966 / ZTE(CB insta=
llation)//end of work","ange.kongo@ihstowers.com","11858","10-10-2024 11:27=
:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003288693","Afanoya"=
,"","10-10-2024 11:26:30","10-10-2024 11:15:51","10-10-2024 11:22:01","Casc=
aded Incident from TTO3154830","Hyemafo Gildas","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubaie: 51.8V on Ba=
ttery (Hybrid site).  Fabrice (656 31 89 47/Huawei ) is informed.","system"=
,"639","10-10-2024 11:26:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003288641","Matsari"=
,"","10-10-2024 11:17:31","10-10-2024 10:55:14","10-10-2024 10:56:18","Casc=
aded Incident from TTO3154771","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on Solar; =
Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed=
.","system","1337","10-10-2024 11:17:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003288642","Yoko OCM=
","","10-10-2024 11:17:31","10-10-2024 10:55:14","10-10-2024 10:56:18","Cas=
caded Incident from TTO3154771","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on Solar;=
 Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informe=
d.","system","1337","10-10-2024 11:17:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003288644","MBIMBIM"=
,"","10-10-2024 11:17:31","10-10-2024 10:55:14","10-10-2024 10:56:18","Casc=
aded Incident from TTO3154771","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on Solar; =
Ubaie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed=
.","system","1337","10-10-2024 11:17:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003288640","Ngoum","=
","10-10-2024 11:17:30","10-10-2024 10:55:14","10-10-2024 10:56:18","Cascad=
ed Incident from TTO3154771","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on Solar; Ub=
aie =3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","1336","10-10-2024 11:17:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003288532","N=
GONA","","10-10-2024 11:03:29","10-10-2024 10:58:18","10-10-2024 11:00:31",=
"","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No powerissue on site ubaie=3D54v site on=
 grid lionel Adjep is informed","ange.kongo@ihstowers.com","312","10-10-202=
4 11:03:29","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003288361","Pha=
rmacie SION","","10-10-2024 10:40:19","10-10-2024 10:32:11","10-10-2024 10:=
41:30","Grid outage ,site went down before DG start : Poor Batteries Backup=
 //Grid Power returned.","Paul BIBOUM","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage ,site went down before =
DG start : Poor Batteries Backup //Grid Power returned.","adonis.defokoua@i=
hstowers.com","489","10-10-2024 10:40:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0003288324","OTELE MT=
N","","10-10-2024 10:37:01","10-10-2024 10:13:24","10-10-2024 11:19:56","Ca=
scaded Incident from TTO3154418","Fanda Brice","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active: no power issue, site is on grid wi=
th Ubaie=3D53V,Etienne (695033981) from Huawei is informed.
","system","1417","10-10-2024 10:37:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0003288325","Mom","",=
"10-10-2024 10:37:01","10-10-2024 10:13:24","10-10-2024 11:19:56","Cascaded=
 Incident from TTO3154418","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","Active: no power issue, site is on grid with Uba=
ie=3D53V,Etienne (695033981) from Huawei is informed.
","system","1417","10-10-2024 10:37:01","Sagemcom CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0003288314","Min=
ka","IHS_YND_531, IHS_YND_370","10-10-2024 10:35:30","10-10-2024 10:13:24",=
"10-10-2024 11:19:56","Active: no power issue, site is on grid with Ubaie=
=3D53V,Etienne (695033981) from Huawei is informed.","Fanda Brice","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active: no power issue, site is on grid with Ubaie=3D53V,Etienne (69503=
3981) from Huawei is informed.
","adonis.defokoua@ihstowers.com","1326","10-10-2024 10:35:30","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003288182","B=
iyemassi LAC","","10-10-2024 10:20:40","08-10-2024 13:59:16","09-10-2024 14=
:10:16","Active, no power isssue, site on grid with u=3D53.4V, Tx fme Mbah =
hosiah/674007438 From Huawei is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power i=
sssue, site on grid with u=3D53.4V, Tx fme Mbah hosiah/674007438 From Huawe=
i is informed","ange.kongo@ihstowers.com","159685","10-10-2024 10:20:40","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003288178","Nkolbiss=
on usines des eaux 2","","10-10-2024 10:20:30","10-10-2024 10:05:43","10-10=
-2024 11:09:43","Cascaded Incident from TTO3154253","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid Ou=
tage, site went down because Gen stopped with ""high temp"" alarm// He adde=
d water and started Gen manualy","system","887","10-10-2024 10:20:30","Sage=
mcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003288173","Nko=
lbisson","IHS_YND_763","10-10-2024 10:19:51","10-10-2024 10:05:43","10-10-2=
024 11:09:43","","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","A=
CDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid Outage, site=
 went down because Gen stopped with ""high temp"" alarm// He added water an=
d started Gen manualy","adonis.defokoua@ihstowers.com","849","10-10-2024 10=
:19:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0003288166","Nkolkoum=
ou OCM","","10-10-2024 10:17:50","10-10-2024 10:02:48","10-10-2024 11:32:35=
","site went down because gen start and stoppen with alarm low oil pressure=
 // He added oil pressure, site on gen","TIENTCHEU NZETCHIEU GAEL","Cascade=
 Outage","Passive","Cascade Passive","Cascade Passive","site went down beca=
use gen start and stoppen with alarm low oil pressure // He added oil press=
ure, site on gen","system","902","10-10-2024 10:17:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003288164","N=
kolbisson usine des eaux","IHS_YND_712","10-10-2024 10:16:58","10-10-2024 1=
0:02:48","10-10-2024 11:32:35","","TIENTCHEU NZETCHIEU GAEL","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","site went down because ge=
n start and stoppen with alarm low oil pressure // He added oil pressure, s=
ite on gen","ange.kongo@ihstowers.com","850","10-10-2024 10:16:58","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0003287843","K=
amajou Building","","10-10-2024 09:31:04","10-10-2024 09:25:59","10-10-2024=
 13:26:14","No power issue on site U=3D54,1v site on grid Hosiah of huawei =
is informed notice that disjunction of CB in BTS Ocm.","Paul BIBOUM","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site U=3D54,1v site on grid Hosiah of huawei is inf=
ormed notice that disjunction of CB in BTS Ocm.
","ange.kongo@ihstowers.com","306","10-10-2024 09:31:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0003287815","P=
olytechnique","","10-10-2024 09:29:45","10-10-2024 09:24:40","10-10-2024 12=
:42:19","ON SITE","","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Circuit Breaker Issue","site down because CB tripped in new PWC ins=
talled( awaited Africa Security more than 1 hour and half)//CB put back o",=
"ange.kongo@ihstowers.com","306","10-10-2024 09:29:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0003287378","M=
om","","10-10-2024 08:20:18","10-10-2024 08:15:08","10-10-2024 09:00:38","G=
rid outage, Site went down because Gen ran until fuel shortage// Refueling =
done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid =
outage, Site went down because Gen ran until fuel shortage// Refueling done=
","ange.kongo@ihstowers.com","311","10-10-2024 08:20:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003287346","L=
abogenie","","10-10-2024 08:12:10","10-10-2024 08:07:28","10-10-2024 12:13:=
27","No power issue, site is on grid with Ubaie=3D53V, Hurgo(672390202) fro=
m Huawei is informed, site impacted by Eki=E9 nodal.","","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue, site is on grid with Ubaie=3D53V, Hurgo(672390202) from Huawei is=
 informed, site impacted by Eki=E9 nodal.","ange.kongo@ihstowers.com","282"=
,"10-10-2024 08:12:10","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0003287302","EBO=
M","","10-10-2024 08:04:56","10-10-2024 07:52:14","10-10-2024 09:00:50","si=
te went down because gen failed to start due to grid fluctuation and no RCP=
// Gen manually started","Hyemafo Gildas","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","site went down because gen failed =
to start due to grid fluctuation and no RCP// Gen manually started","adonis=
.defokoua@ihstowers.com","1331","10-10-2024 08:04:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003286901","N=
kolbisson usine des eaux","","10-10-2024 06:47:34","10-10-2024 06:45:30","1=
0-10-2024 08:44:19","grid outage, site went down because gen start and stop=
pen with alarm""Over current""// He reduced de load, site on gen","TIENTCHE=
U NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","grid outage, site went down because gen start and stoppen with alarm=
""Over current""// He reduced de load, site on gen","ange.kongo@ihstowers.c=
om","125","10-10-2024 06:47:34","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_110","NOCINC0003286150","Camp-Sonel=
","","10-10-2024 03:37:54","","","site alarming High temp // Alarm cleared"=
,"Siligap Boris","Warning","Warning","ENVIRONMENT","Warning - High Temperat=
ure","site alarming High temp // Alarm cleared","stephane.nkamwa@ihstowers.=
com","426","10-10-2024 03:37:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003285775","Ngouetou=
","","10-10-2024 02:03:30","10-10-2024 01:42:42","10-10-2024 04:40:20","Cas=
caded Incident from TTO3151502","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Our FME Felix ATANGANA 691145560 / IENG a=
nd reported No power issue. Site is on GEN with U =3D 54.6V Hybrid gen site=
 with threshold =3D 47.5V).=20

TX FME Abdouramane 657959647 of  Huawei is informed
","system","1248","10-10-2024 02:03:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003285774","Matsari"=
,"","10-10-2024 02:03:30","10-10-2024 01:42:42","10-10-2024 04:40:20","Casc=
aded Incident from TTO3151502","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Our FME Felix ATANGANA 691145560 / IENG an=
d reported No power issue. Site is on GEN with U =3D 54.6V Hybrid gen site =
with threshold =3D 47.5V).=20

TX FME Abdouramane 657959647 of  Huawei is informed
","system","1248","10-10-2024 02:03:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003285776","MBIMBIM"=
,"","10-10-2024 02:03:30","10-10-2024 01:42:42","10-10-2024 04:40:20","Casc=
aded Incident from TTO3151502","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Our FME Felix ATANGANA 691145560 / IENG an=
d reported No power issue. Site is on GEN with U =3D 54.6V Hybrid gen site =
with threshold =3D 47.5V).=20

TX FME Abdouramane 657959647 of  Huawei is informed
","system","1248","10-10-2024 02:03:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003285761","Yoko OCM=
","","10-10-2024 01:56:50","10-10-2024 01:42:42","10-10-2024 04:40:20","Cas=
caded Incident from TTO3151502","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Our FME Felix ATANGANA 691145560 / IENG a=
nd reported No power issue. Site is on GEN with U =3D 54.6V Hybrid gen site=
 with threshold =3D 47.5V).=20

TX FME Abdouramane 657959647 of  Huawei is informed
","system","848","10-10-2024 01:56:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003285760","Ngoum","=
","10-10-2024 01:56:50","10-10-2024 01:42:42","10-10-2024 04:40:20","Cascad=
ed Incident from TTO3151502","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Our FME Felix ATANGANA 691145560 / IENG and =
reported No power issue. Site is on GEN with U =3D 54.6V Hybrid gen site wi=
th threshold =3D 47.5V).=20

TX FME Abdouramane 657959647 of  Huawei is informed
","system","848","10-10-2024 01:56:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003285580","L=
abogenie","","10-10-2024 01:19:28","10-10-2024 00:53:16","10-10-2024 01:05:=
39","Active//No power isssue, site is on grid with Ubaie=3D54,8V,The FME tx=
 Leonel (694693436) from Huawei is informed","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r isssue, site is on grid with Ubaie=3D54,8V,The FME tx Leonel (694693436) =
from Huawei is informed","alexandre.kamal@ihstowers.com","1572","10-10-2024=
 01:19:28","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003285068","Elo=
umdem stade","","09-10-2024 23:23:37","09-10-2024 22:56:08","09-10-2024 23:=
51:14","","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Fue=
l Leakage","grid bad voltage, gen stopped due to fuel leakage at the level =
of fuel pipe//made a bridge on the good phase(work ongoing)","kamga.virgile=
@ihstowers.com","1650","09-10-2024 23:23:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003284586","C=
rf Cornier","","09-10-2024 21:43:35","09-10-2024 21:41:17","09-10-2024 21:4=
3:20","Active, No power issue site on Grid with U=3D54.6V THE TX FME  Lione=
l / 694693436 from huawei is Informed","MINKA NICOLAS","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, =
No power issue site on Grid with U=3D54.6V THE TX FME  Lionel / 694693436 f=
rom huawei is Informed","kouoh.jean@ihstowers.com","138","09-10-2024 21:43:=
35","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0003284391","Nko=
zoa","","09-10-2024 21:16:22","09-10-2024 21:04:14","09-10-2024 22:35:32","=
Grid outage ,Site went down because  Gen overload(20KVA;320 A)//He reduced =
the load on site ","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid outage ,Site went down because  Gen overload(20KV=
A;320 A)//He reduced the load on site ","landry.etame@ihstowers.com","760",=
"09-10-2024 21:16:22","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003284383","Lad=
a I Yde","","09-10-2024 21:15:26","09-10-2024 21:01:19","09-10-2024 22:19:2=
2","Site went down due to power cable of energy meter stolen since//Gen sta=
rted","Mba Lazare Herve","Site Asset Theft","Theft","Theft","AC Cable Stole=
n","Site went down due to power cable of energy meter stolen since//Gen sta=
rted","landry.etame@ihstowers.com","847","09-10-2024 21:15:26","Sagemcom CM=
R"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003284207","Nko=
londom","","09-10-2024 20:54:13","09-10-2024 20:45:03","09-10-2024 22:25:45=
","Grid power return Site went down because Gen stopped due to Grid contact=
or Dysfuntionning // He blocked Grid contactor and site on Grid","Fabrice P=
ouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid =
power return Site went down because Gen stopped due to Grid contactor Dysfu=
ntionning // He blocked Grid contactor and site on Grid","landry.etame@ihst=
owers.com","583","09-10-2024 20:54:13","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0003284195","Nko=
lbisson IITA LP","","09-10-2024 20:52:14","09-10-2024 20:44:09","09-10-2024=
 22:32:54","Acces issues during the Night,Grid outage,no space to deploy a =
mobile waiting for grid restored//Grid restored.","","Access Denial","Lease=
 Or Legal","Landlord Related Issues","Access Issue - Land Lord","Acces issu=
es during the Night,Grid outage,no space to deploy a mobile waiting for gri=
d restored//Grid restored.","landry.etame@ihstowers.com","486","09-10-2024 =
20:52:14","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003283921","NYO=
M FACE MAETUR","","09-10-2024 20:19:30","09-10-2024 20:02:26","09-10-2024 2=
0:50:41","Grid outage, Site went down because landlord do not permit to sta=
rt Gen// Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Emergency Stop","Grid outage, Site went down because landlord =
do not permit to start Gen// Grid return","landry.etame@ihstowers.com","102=
5","09-10-2024 20:19:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003283690","E=
kie sud","","09-10-2024 19:35:02","09-10-2024 19:25:51","09-10-2024 19:30:5=
1","No power issue on site U=3D52,4v site on grid Lionel Adjep/655184876 of=
 huawei is informed","Albran Byorel","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D52,4v site on grid Lionel Adjep/655184876 of huawei is informed","kouoh.=
jean@ihstowers.com","552","09-10-2024 19:35:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003283504","MEHANDAN=
","","09-10-2024 19:02:00","09-10-2024 18:51:19","09-10-2024 19:25:03","Cas=
caded Incident from TTO3148892","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to work  Team Brice=
 wiliam /690981199/ From Broadcom  iS working on site (swap Gen and PWC)// =
End of work ","system","641","09-10-2024 19:02:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003283496","O=
dza II OCM","IHS_YND_528","09-10-2024 19:00:40","09-10-2024 18:51:19","09-1=
0-2024 19:50:03","Site went down due to work  Team Brice wiliam /690981199/=
 From Broadcom  iS working on site (swap Gen and PWC)// End of work ","Albr=
an Byorel","Equipment Replacement","Passive","Planned Activity","Planned Ac=
tivity - Passive","Site went down due to work  Team Brice wiliam /690981199=
/ From Broadcom  iS working on site (swap Gen and PWC)// End of work ","kou=
oh.jean@ihstowers.com","562","09-10-2024 19:00:40","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003283492","Elo=
umdem stade","","09-10-2024 19:00:22","09-10-2024 18:51:14","09-10-2024 19:=
28:08","grid outage,gen failed to start due to grid bad voltage;no rcp//he =
bypassed grid and started the gen","Fanda Brice","Grid Supply","Passive","G=
rid","National Grid - Power Cable Faulty","grid outage,gen failed to start =
due to grid bad voltage;no rcp//he bypassed grid and started the gen","land=
ry.etame@ihstowers.com","548","09-10-2024 19:00:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003283335","Lobo OCM=
","","09-10-2024 18:31:40","09-10-2024 18:22:19","09-10-2024 18:28:19","Cas=
caded Incident from TTO3148696","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Gen started","system","561"=
,"09-10-2024 18:31:40","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003283334","N=
KOMEKUI OCM","IHS_YND_341","09-10-2024 18:31:07","09-10-2024 18:22:19","09-=
10-2024 18:28:19","Grid outage, site went down before gen start due to poor=
 battery backup // Gen started","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before gen start due to poor battery backup // Gen started","k=
ouoh.jean@ihstowers.com","529","09-10-2024 18:31:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003283319","S=
ous Prefecture","","09-10-2024 18:29:26","09-10-2024 18:05:29","09-10-2024 =
18:06:28","Active//No power isssue, site is on Grid with Ubaie=3D54,9V, Rm =
alain (691 14 44 23) from Huawei is informed","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power isssue, site is on Grid with Ubaie=3D54,9V, Rm alain (691 14 =
44 23) from Huawei is informed","kouoh.jean@ihstowers.com","1438","09-10-20=
24 18:29:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003281638","M=
imboman-Ecole","","09-10-2024 14:50:46","09-10-2024 14:46:35","09-10-2024 1=
4:47:50","Active//No power issue, site is on Grid with Ubaie=3D54,3 V  The =
TX FME Eloundou Bertrant  (693212405)  from Huawei is informed","Mba Lazare=
 Herve","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No power issue, site is on Grid with Ubaie=3D54=
,3 V  The TX FME Eloundou Bertrant  (693212405)  from Huawei is informed","=
kouoh.jean@ihstowers.com","252","09-10-2024 14:50:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003281199","Lobo OCM=
","","09-10-2024 13:48:10","09-10-2024 13:43:08","09-10-2024 13:48:07","Cas=
caded Incident from TTO3146265","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid Outage, site went down=
 before Gen start due to poor backup// Gen started automatically","system",=
"302","09-10-2024 13:48:10","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003281197","N=
KOMEKUI OCM","IHS_YND_341","09-10-2024 13:47:14","09-10-2024 13:43:08","09-=
10-2024 13:48:07","Grid Outage, site went down before Gen start due to poor=
 backup// Gen started automatically","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outag=
e, site went down before Gen start due to poor backup// Gen started automat=
ically","joelle.ekessi@ihstowers.com","247","09-10-2024 13:47:14","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003281137","F=
ebe Village","","09-10-2024 13:38:35","09-10-2024 13:37:31","09-10-2024 13:=
58:50","Site went down due to work: Gildas/659-65-36-38/From ZTE is working=
 on site ""add second cable power""//  End of works.","Mboua Thierry","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Is=
sue","Site went down due to work: Gildas/659-65-36-38/From ZTE is working o=
n site ""add second cable power""//  End of works.","joelle.ekessi@ihstower=
s.com","65","09-10-2024 13:38:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003280862","M=
essa-Carriere OCM","","09-10-2024 13:02:19","09-10-2024 12:55:13","09-10-20=
24 13:06:00","Site went down due to work: Pascaline/Supervisor IHS working =
on site//End of works.","","Installation Activity","Passive","Planned Activ=
ity","Installation Activity","Site went down due to work: Pascaline/Supervi=
sor IHS working on site//End of works.","joelle.ekessi@ihstowers.com","427"=
,"09-10-2024 13:02:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0003280798","M=
fou OCM","","09-10-2024 12:53:38","09-10-2024 12:50:34","09-10-2024 12:53:5=
1","No power issue on site U=3D50v site on grid Rm alain 691144423 of huwei=
 is informed ","Mba Lazare Herve","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D50=
v site on grid Rm alain 691144423 of huwei is informed ","joelle.ekessi@ihs=
towers.com","184","09-10-2024 12:53:38","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003280715","NYO=
M FACE MAETUR","","09-10-2024 12:47:14","09-10-2024 12:45:10","09-10-2024 1=
2:48:20","Grid outage, Site went down because landlord do not permit to sta=
rt Gen// Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Emergency Stop","Grid outage, Site went down because landlord =
do not permit to start Gen// Grid return","emmanuel.ghani@ihstowers.com","1=
25","09-10-2024 12:47:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003280453","M=
adison","","09-10-2024 12:16:44","09-10-2024 12:12:35","09-10-2024 12:15:35=
","Active, No power isssue, site on grid with U=3D54V, tx fme Armand Ngetsa=
/699949553/ From huawei is working on site","MFOUAGUEGUE MATHIEU","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active, No power isssue, site on grid with U=3D54V, tx fme Armand Ngetsa=
 From huawei is working on site","joelle.ekessi@ihstowers.com","250","09-10=
-2024 12:16:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0003280415","B=
ISCUITERIE","","09-10-2024 12:09:41","09-10-2024 12:00:37","09-10-2024 13:4=
9:18","No power issue, site is on Grid with Ubaie=3D50,2  V  The TX FME Mba=
h Hosiah (674007438)  from Huawei is informed and up at 12:19PM.","Paul BIB=
OUM","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue, site is on Grid with Ubaie=3D50,2  V  The =
TX FME Mbah Hosiah (674007438)  from Huawei is informed and up at 12:19PM.
","joelle.ekessi@ihstowers.com","545","09-10-2024 12:09:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003280269","ELOUMDEM=
 CARRIERE","","09-10-2024 11:46:00","09-10-2024 11:39:36","09-10-2024 12:35=
:54","Cascaded Incident from TTO3145249","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start=
 due to overload (20Kva, 300A),and poor batteries backup // He reduced 2/9 =
rectifier and started Gen manually.","system","384","09-10-2024 11:46:00","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003280271","Afanoya"=
,"","09-10-2024 11:46:00","09-10-2024 11:39:36","09-10-2024 12:35:54","Casc=
aded Incident from TTO3145249","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, DG Failed to start due to=
 overload (20Kva, 300A),and poor batteries backup // He reduced 2/9 rectifi=
er and started Gen manually.","system","384","09-10-2024 11:46:00","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003280270","MBALNGON=
G LYCEE","","09-10-2024 11:46:00","09-10-2024 11:39:36","09-10-2024 12:35:5=
4","Cascaded Incident from TTO3145249","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, DG Failed to start d=
ue to overload (20Kva, 300A),and poor batteries backup // He reduced 2/9 re=
ctifier and started Gen manually.","system","384","09-10-2024 11:46:00","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0003280258","R=
d-Pt-Express","","09-10-2024 11:43:46","09-10-2024 11:39:42","09-10-2024 13=
:41:29","No power issue, site is on Grid with Ubaie=3D54,3  V  The TX FME M=
bah Hosiah (674007438)  from Huawei is informed.","","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on Grid with Ubaie=3D54,3  V  The TX FME Mbah Hosiah (6740074=
38)  from Huawei is informed.
","joelle.ekessi@ihstowers.com","245","09-10-2024 11:43:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003280253","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","09-10-2024 11:42:41","09-10-=
2024 11:39:36","09-10-2024 12:35:54","Grid outage, DG Failed to start due t=
o overload (20Kva, 300A),and poor batteries backup // He reduced 2/9 rectif=
ier and started Gen manually.","Hyemafo Gildas","Equipment Repair","Passive=
","ACDG Gen","ACDG - Overload","Grid outage, DG Failed to start due to over=
load (20Kva, 300A),and poor batteries backup // He reduced 2/9 rectifier an=
d started Gen manually.","joelle.ekessi@ihstowers.com","186","09-10-2024 11=
:42:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003280081","N=
GONA","","09-10-2024 11:18:59","09-10-2024 11:14:53","09-10-2024 13:24:00",=
"No power issue, site is on grid with Ubaie=3D56V, Lionel adjep(655184876) =
from Huawei is informed and Up at 11:21 Am","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue, site is on grid with Ubaie=3D56V, Lionel adjep(655184876) f=
rom Huawei is informed and Up at 11:21 Am","joelle.ekessi@ihstowers.com","2=
47","09-10-2024 11:18:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003279884","N=
kolbisson usine des eaux","IHS_YND_712","09-10-2024 11:00:11","09-10-2024 1=
0:55:04","09-10-2024 11:06:46","Site went down due to work: Technician Gael=
/657108563/SAGEMCOM/working""second CB(125A)""//end of work","TIENTCHEU NZE=
TCHIEU GAEL","Installation Activity","Passive","Planned Activity","Installa=
tion Activity","Site went down due to work: Technician Gael/657108563/SAGEM=
COM/working""second CB(125A)""//end of work","joelle.ekessi@ihstowers.com",=
"309","09-10-2024 11:00:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0003279866","N=
kolkoumou OCM","","09-10-2024 10:57:04","09-10-2024 10:55:04","09-10-2024 1=
1:06:46","Please cascade behing Nkobisson usine des eaux","TIENTCHEU NZETCH=
IEU GAEL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","S=
ite went down due to work: Technician Gael/657108563/SAGEMCOM/working""seco=
nd CB(125A)""//end of work","joelle.ekessi@ihstowers.com","6581","09-10-202=
4 10:57:04","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003279853","Lad=
a I Yde","","09-10-2024 10:55:11","09-10-2024 10:54:04","09-10-2024 12:00:0=
3","","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","grid fluctuations with bad voltages, gen fail to st=
art//made a bridge on a good phase","emmanuel.ghani@ihstowers.com","68","09=
-10-2024 10:55:11","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_393","NOCINC0003279517","Ezezang","=
","09-10-2024 10:14:24","","","Alarm not proven,site on Grid,Ubaie:54V; ","=
Parker Tchoup","Warning","Warning","SYSTEM","Warning - Controler Failure","=
Alarm not proven,site on Grid,Ubaie:54V; ","joelle.ekessi@ihstowers.com","6=
","09-10-2024 10:14:24","Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0003279433","Ang=
uissa New","","09-10-2024 10:04:36","09-10-2024 10:02:31","09-10-2024 10:08=
:09","Grid outage,site went down before DG start : Poor Batteries Backup //=
Grid restored.","MINKA NICOLAS","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage,site went down before DG start=
 : Poor Batteries Backup //Grid restored.","emmanuel.ghani@ihstowers.com","=
126","09-10-2024 10:04:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003279272","Nkolo II=
 New","","09-10-2024 09:43:01","09-10-2024 09:41:12","09-10-2024 09:50:39",=
"Cascaded Incident from TTO3144126","Mba Lazare Herve","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site ,site on Gr=
id with Ubaie=3D53,6 V The Tx FME Eloundou(693212405) from Huawei is inform=
ed","system","109","09-10-2024 09:43:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003279266","M=
imboman-Village","IHS_YND_709","09-10-2024 09:42:18","09-10-2024 09:41:12",=
"09-10-2024 11:12:30","No power issue on site ,site on Grid with Ubaie=3D53=
,6 V The Tx FME Eloundou(693212405) from Huawei is informed","Mba Lazare He=
rve","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue on site ,site on Grid with Ubaie=3D53,6 V T=
he Tx FME Eloundou(693212405) from Huawei is informed","joelle.ekessi@ihsto=
wers.com","67","09-10-2024 09:42:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0003278926","C=
arington","","09-10-2024 08:37:30","09-10-2024 08:32:24","09-10-2024 09:53:=
13","Grid outage//Grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage//Grid return","joelle.ekessi@ihstowe=
rs.com","308","09-10-2024 08:37:30","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_242","NOCINC0003278916","Mballa 4",=
"","09-10-2024 08:33:37","","","Alarm not proven,site on Grid,Ubaie:54V; ",=
"Delor Telezing","Warning","Warning","SYSTEM","Warning - Controler Failure"=
,"Alarm not proven,site on Grid,Ubaie:54V; ","joelle.ekessi@ihstowers.com",=
"4","09-10-2024 08:33:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0003278716","T=
SINGA VILLAGE 2","","09-10-2024 07:46:15","09-10-2024 07:43:11","09-10-2024=
 08:16:11","Site went down because Gen failed to start due to due to short-=
circuit of the solenoid supply cable// He changed Cable supply  and started=
 Gen manualy","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACD=
G - Solenoid Coil","Site went down because Gen failed to start due to due t=
o short-circuit of the solenoid supply cable// He changed Cable supply  and=
 started Gen manualy","joelle.ekessi@ihstowers.com","185","09-10-2024 07:46=
:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0003278665","M=
beng","IHS_YND_553","09-10-2024 07:34:40","09-10-2024 07:26:34","09-10-2024=
 09:14:34","Site went down due to 1/2 rectifier fauty // he added 01 rectif=
ier, site on grid","Fanda Brice","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down due to 1/2 rectifier fauty // he added 01=
 rectifier, site on grid","joelle.ekessi@ihstowers.com","487","09-10-2024 0=
7:34:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0003278367","M=
bedoumou - Ekali","","09-10-2024 06:33:54","09-10-2024 06:15:50","09-10-202=
4 11:21:50","Actieve, no power issue, site on grid with U=3D54.5V? Rodrigue=
/655102999/ from Huawei is informed","Albran Byorel","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Actieve, n=
o power issue, site on grid with U=3D54.5V? Rodrigue/655102999/ from Huawei=
 is informed","joelle.ekessi@ihstowers.com","1085","09-10-2024 06:33:54","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0003278230","O=
ssombe","","09-10-2024 06:03:07","09-10-2024 05:51:00","09-10-2024 07:06:09=
","Active: no power issue, site is on gen with Ubaie=3D53,2V, Gregoire (654=
547479) from Huawei is informed","Parker Tchoup","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no pow=
er issue, site is on gen with Ubaie=3D53,2V, Gregoire (654547479) from Huaw=
ei is informed","dorothy.djantio@ihstowers.com","728","09-10-2024 06:03:07"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003278157","M=
fou EPC","","09-10-2024 05:39:18","09-10-2024 05:35:10","09-10-2024 05:56:1=
0","Grid fluctuation, site went down because gen start and stopped due to g=
rid bad voltage no rcp// Grid stabilized","Mba Lazare Herve","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuatio=
n, site went down because gen start and stopped due to grid bad voltage no =
rcp// Grid stabilized","dorothy.djantio@ihstowers.com","249","09-10-2024 05=
:39:18","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003277824","Elo=
umdem stade","","09-10-2024 04:09:47","09-10-2024 04:01:39","09-10-2024 05:=
04:15","Grid outage,  site went down because Gen failed to start due fuel L=
ine blocked by dirty// He dismantled the tank and removed the dirt","Fanda =
Brice","Fuel Outage (Probable)","Passive","Diesel","Fuel Line Issue","Grid =
outage,  site went down because Gen failed to start due fuel Line blocked b=
y dirty// He dismantled the tank and removed the dirt","olivier.kwedi@ihsto=
wers.com","488","09-10-2024 04:09:47","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003277763","Ako=
no","","09-10-2024 03:53:56","09-10-2024 03:30:35","09-10-2024 04:02:54","G=
rid outage site went down because Gen failed to started due to Gen card Dis=
funtionny//He reset Gen card and Gen manually  started","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site=
 went down because Gen failed to started due to Gen card Disfuntionny//He r=
eset Gen card and Gen manually  started","olivier.kwedi@ihstowers.com","140=
2","09-10-2024 03:53:56","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003277749","NTU=
I TOWN","","09-10-2024 03:48:00","09-10-2024 03:45:48","09-10-2024 03:51:38=
","Grid outage, site went down before gen start due to poor battery backup =
// gen start automatically","Parker Tchoup","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // gen start automatically","oliv=
ier.kwedi@ihstowers.com","133","09-10-2024 03:48:00","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003277673","OLA=
MA","","09-10-2024 03:16:21","09-10-2024 03:12:08","09-10-2024 03:15:38","N=
o power issue on site ,Site on Gen with Ubaie=3D54,9  V The Tx FME  Lionnel=
 Tchatchoua  (696731233)   from Hauawei  is informed,","Fanda Brice","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site ,Site on Gen with Ubaie=3D54,9  V The Tx FME  =
Lionnel Tchatchoua  (696731233)   from Hauawei  is informed,","olivier.kwed=
i@ihstowers.com","254","09-10-2024 03:16:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0003276751","M=
vog-Betsi","","08-10-2024 23:17:39","08-10-2024 23:00:35","09-10-2024 01:05=
:30","No power issue on site ,Site on Gen with Ubaie=3D54,3  V The Tx Fme M=
ohamadou//691144435 from  Huawei is informed .","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site ,Site on Gen with Ubaie=3D54,3  V The Tx Fme Moham=
adou//691144435 from  Huawei is informed .","dorothy.djantio@ihstowers.com"=
,"1024","08-10-2024 23:17:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0003276748","M=
endong","","08-10-2024 23:16:39","08-10-2024 23:00:30","08-10-2024 23:05:46=
","No power issue on site U=3D54,5v site on GenThe Tx FME HOSIAH//699699694=
 from Huawei is informed.","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D54,5v site on GenThe Tx FME HOSIAH//699699694 from Huawei is inform=
ed.","dorothy.djantio@ihstowers.com","970","08-10-2024 23:16:39","Sagemcom =
CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003276384","Nko=
ulou Carriere carrefourt","","08-10-2024 21:56:08","08-10-2024 16:47:55","0=
8-10-2024 22:41:59","site went down because insufficient of rectifiers (02)=
 on site  //he added 01 rectifier,site on Grid","Mba Lazare Herve","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","site went down because=
 insufficient of rectifiers (02) on site  //he added 01 rectifier","kamga.v=
irgile@ihstowers.com","18493","08-10-2024 21:56:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0003276329","S=
OA 2","","08-10-2024 21:43:59","08-10-2024 21:39:36","08-10-2024 22:34:09",=
"Site went down because CB(100*80A)  OCM  disjuncted in DCBOX cauing by CB(=
100A) faulty//He make the bridge  with another CB(80A)","Siligap Boris","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker =
Issue","Site went down because CB(100*80A)  OCM  disjuncted in DCBOX cauing=
 by CB(100A) faulty//He make the bridge  with another CB(80A)","alexandre.k=
amal@ihstowers.com","264","08-10-2024 21:43:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003276271","E=
ssomba","","08-10-2024 21:32:18","08-10-2024 21:28:12","09-10-2024 09:42:38=
","Access issue due to Landlord, site went down because Gen over load(15Kva=
,212A) // Grid power return.","Mba Lazare Herve","Access Denial","Lease Or =
Legal","Landlord Related Issues","Access Issue - Land Lord","Access issue d=
ue to Landlord, site went down because Gen over load(15Kva,212A) // Grid po=
wer return.","alexandre.kamal@ihstowers.com","247","08-10-2024 21:32:18","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003276206","M=
IMBOMAN LIBERTE","","08-10-2024 21:29:55","08-10-2024 21:21:46","08-10-2024=
 21:46:36","Grir outage;Site went down because Main Gen faulty//Grid power =
return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - =
Generator Faulty","Grir outage;Site went down because Main Gen faulty//Grid=
 power return","alexandre.kamal@ihstowers.com","490","08-10-2024 21:29:55",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0003276173","R=
d-Pt-Express","","08-10-2024 21:23:18","08-10-2024 20:59:08","09-10-2024 04=
:00:27","No power issue, site is on Grid with Ubaie=3D54,2  V  The TX FME M=
bah Hosiah (674007438)  from Huawei is informed","","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue, site is on Grid with Ubaie=3D54,2  V  The TX FME Mbah Hosiah (67400743=
8)  from Huawei is informed","alexandre.kamal@ihstowers.com","1451","08-10-=
2024 21:23:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_343","NOCINC0003276095","Mbedoumo=
u - Ekali","","08-10-2024 21:06:30","08-10-2024 20:56:55","09-10-2024 00:11=
:18","Cascaded Incident from TTO3140425","Albran Byorel","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site No com, U=
baie: 52,9V site on Grid,  Rodrigue (655102999/Huawei) is informed.","syste=
m","575","08-10-2024 21:06:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003276043","Yoko MTN=
","","08-10-2024 21:00:43","08-10-2024 20:35:20","08-10-2024 23:55:05","Cas=
caded Incident from TTO3140357","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen site ,Site went down becaus=
e Gen ran until fuel shortage// Refueling done","system","1523","08-10-2024=
 21:00:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003276042","Dong",""=
,"08-10-2024 21:00:43","08-10-2024 20:35:20","08-10-2024 23:55:05","Cascade=
d Incident from TTO3140357","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Hybrid Gen site ,Site went down because Ge=
n ran until fuel shortage// Refueling done","system","1523","08-10-2024 21:=
00:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003276041","Ngoum","=
","08-10-2024 21:00:42","08-10-2024 20:35:20","09-10-2024 01:06:37","Cascad=
ed Incident from TTO3140357","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Our FME Felix ATANGANA 691145560 / IENG a=
nd reported No power issue. Site is on GEN with U =3D 54.6V Hybrid gen site=
 with threshold =3D 47.5V).=20

TX FME Abdouramane 657959647of Huawei is informed
","system","1522","08-10-2024 21:00:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003276040","Nguila",=
"","08-10-2024 21:00:42","08-10-2024 20:35:20","08-10-2024 23:55:05","Casca=
ded Incident from TTO3140357","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Hybrid Gen site ,Site went down because =
Gen ran until fuel shortage// Refueling done","system","1522","08-10-2024 2=
1:00:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003275986","Biteng-M=
aetur","","08-10-2024 20:50:30","08-10-2024 20:31:23","08-10-2024 22:28:30"=
,"Cascaded Incident from TTO3140301","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, site went down be=
cause gen failed to start due to Gen overload(20 KVA, 280A)// grid return",=
"system","1147","08-10-2024 20:50:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003275985","Tradex-N=
komo","","08-10-2024 20:50:30","08-10-2024 20:31:23","08-10-2024 22:28:30",=
"Cascaded Incident from TTO3140301","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, site went down becaus=
e gen failed to start due to Gen overload(20 KVA, 280A)// grid return","sys=
tem","1147","08-10-2024 20:50:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003275974","B=
iteng","IHS_YND_172, IHS_YND_249","08-10-2024 20:48:55","08-10-2024 20:31:2=
3","08-10-2024 22:28:30","grid outage, site went down because gen failed to=
 start due to Gen overload(20 KVA, 280A)// grid return","Mba Lazare Herve",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","grid outage, sit=
e went down because gen failed to start due to Gen overload(20 KVA, 280A)//=
 grid return","alexandre.kamal@ihstowers.com","1053","08-10-2024 20:48:55",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0003275958","D=
onga","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS=
_YND_444, IHS_YND_473","08-10-2024 20:45:29","08-10-2024 20:30:20","08-10-2=
024 23:55:41","Hybrid Gen site ,Site went down because Gen ran until fuel s=
hortage// Refueling done","Parker Tchoup","Fuel Outage","Passive","Diesel",=
"Diesel Outage","Hybrid Gen site ,Site went down because Gen ran until fuel=
 shortage// Refueling done","alexandre.kamal@ihstowers.com","909","08-10-20=
24 20:45:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0003275933","N=
gousso-II","","08-10-2024 20:39:04","08-10-2024 20:25:52","08-10-2024 21:58=
:33","Site went down because CB OCM (2*125A)  disjuncted in DCBOX //he ream=
ed CB","MFOUAGUEGUE MATHIEU","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Circuit Breaker Issue","Site went down because CB OCM (2*12=
5A)  disjuncted in DCBOX //he reamed CB","alexandre.kamal@ihstowers.com","7=
93","08-10-2024 20:39:04","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0003275883","OTE=
LE MTN","","08-10-2024 20:30:33","08-10-2024 19:49:12","08-10-2024 21:54:30=
","Site went down because Gen CB() disjunted due to more  recttifiers on si=
te (03 )//he removed 01,Site on Gen","Fanda Brice","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Load Breaker","Site went down because Gen CB() disj=
unted due to more  recttifiers on site (03 )//he removed 01,Site on Gen","k=
amga.virgile@ihstowers.com","2482","08-10-2024 20:30:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003275411","O=
dza II","","08-10-2024 19:11:27","08-10-2024 19:00:15","08-10-2024 19:22:35=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage // he bypass grid and manually start the gen","Albran Byorel=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid fluctuation, site went down because gen start and stopped due to grid=
 bad voltage // he bypass grid and manually start the gen","alexandre.kamal=
@ihstowers.com","674","08-10-2024 19:11:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0003275015","Montee-J=
ouvence-II","","08-10-2024 18:19:50","08-10-2024 18:05:22","08-10-2024 19:4=
4:26","Cascaded Incident from TTO3139169","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site went down because insu=
fficient of rectifiers (site on 06 rectifiers)due to increase load on site =
//he added 02 rectifiers,site on Gen:","system","868","08-10-2024 18:19:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003275012","N=
kol-Mbanda","IHS_YND_518","08-10-2024 18:18:30","08-10-2024 18:05:22","08-1=
0-2024 19:57:47","site went down because insufficient of rectifiers (site o=
n 06 rectifiers)due to increase load on site //he added 02 rectifiers,site =
on Gen:","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifie=
r Module","site went down because insufficient of rectifiers (site on 06 re=
ctifiers)due to increase load on site //he added 02 rectifiers,site on Gen:=
","alexandre.kamal@ihstowers.com","789","08-10-2024 18:18:30","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0003274768","N=
kongtock","","08-10-2024 17:37:54","08-10-2024 17:31:48","08-10-2024 17:50:=
48","Site went down because Gen ran until fuel shortage// Refueling done","=
Kemeni Franklin","Fuel Outage","Passive","Diesel","Diesel Outage","Site wen=
t down because Gen ran until fuel shortage// Refueling done","alexandre.kam=
al@ihstowers.com","367","08-10-2024 17:37:54","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0003274654","ODZ=
A CITE MBIA","","08-10-2024 17:26:36","08-10-2024 17:15:25","08-10-2024 19:=
08:24","Grid outage,gen failed to start due to no automatism on site//Gen m=
anually started","Albran Byorel","Equipment Repair","Passive","Control Pane=
l","ATS-AMF Issue","Grid outage,gen failed to start due to no automatism on=
 site//Gen manually started","kamga.virgile@ihstowers.com","671","08-10-202=
4 17:26:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0003274368","C=
arington","","08-10-2024 16:56:13","08-10-2024 16:26:35","08-10-2024 17:43:=
11","Grid outage//Grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage//Grid return","alexandre.kamal@ihsto=
wers.com","1779","08-10-2024 16:56:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003274249","L=
abogenie","","08-10-2024 16:34:28","08-10-2024 16:21:21","08-10-2024 16:44:=
58","Grid outage No space to deploy MDG// Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage No space to =
deploy MDG// Grid return","alexandre.kamal@ihstowers.com","788","08-10-2024=
 16:34:28","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0003274179","Mfo=
u EPC","","08-10-2024 16:30:10","08-10-2024 16:20:02","08-10-2024 16:56:24"=
,"Grid fluctuation, site went down because gen start and stopped due to gri=
d bad voltage no rcp// he bypass grid and manually start the gen","Mba Laza=
re Herve","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluctuation, site went down because gen start and stopped due=
 to grid bad voltage no rcp// he bypass grid and manually start the gen","k=
amga.virgile@ihstowers.com","2625","08-10-2024 16:30:10","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003274166","N=
yanon","","08-10-2024 16:28:46","08-10-2024 15:04:30","08-10-2024 15:06:37"=
,"Active//No power issue, site is on gen with Ubaie=3D54V, Gregoire (654547=
479) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No power issue, site is on gen with Ubaie=3D54V, Gregoire (654547479) fro=
m Huawei is informed","alexandre.kamal@ihstowers.com","5057","08-10-2024 16=
:28:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003273702","Matsari"=
,"","08-10-2024 15:56:10","08-10-2024 15:43:59","08-10-2024 23:55:05","Casc=
aded Incident from TTO3137571","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid Gen site ,Site went down because=
 Gen ran until fuel shortage// Refueling done","system","731","08-10-2024 1=
5:56:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003273704","MBIMBIM"=
,"","08-10-2024 15:56:10","08-10-2024 15:43:59","08-10-2024 23:55:05","Casc=
aded Incident from TTO3137571","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid Gen site ,Site went down because=
 Gen ran until fuel shortage// Refueling done","system","731","08-10-2024 1=
5:56:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003273703","Ngouetou=
","","08-10-2024 15:56:10","08-10-2024 15:43:59","08-10-2024 23:55:05","Cas=
caded Incident from TTO3137571","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid Gen site ,Site went down becaus=
e Gen ran until fuel shortage// Refueling done","system","731","08-10-2024 =
15:56:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0003273647","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","08-10-2024 15:54:25","08-=
10-2024 15:43:59","08-10-2024 17:50:51","Grid outage site went down because=
 Gen started and stopped due to short circuit static  charging static // He=
 bypass the  charging static and Gen manually started","Parker Tchoup","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator","Grid outa=
ge site went down because Gen started and stopped due to short circuit stat=
ic  charging static // He bypass the  charging static and Gen manually star=
ted","alexandre.kamal@ihstowers.com","627","08-10-2024 15:54:25","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003273601","S=
ous Prefecture","","08-10-2024 15:47:38","08-10-2024 15:39:30","08-10-2024 =
15:40:56","Active//No power isssue, site is on Gen  with Ubaie=3D54,6V,The =
FME tx Leonel (694693436) from Huawei is informed and Site up at =3D03:46 P=
M","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active//No power isssue, site is on Gen  with =
Ubaie=3D54,6V,The FME tx Leonel (694693436) from Huawei is informed and Sit=
e up at =3D03:46 PM","alexandre.kamal@ihstowers.com","488","08-10-2024 15:4=
7:38","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003273577","Bas=
tos Amb Coree","","08-10-2024 15:44:38","08-10-2024 15:40:01","08-10-2024 1=
8:56:05","Grid Outage no space to deploy MDG//Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no space=
 to deploy MDG//Grid return","kamga.virgile@ihstowers.com","278","08-10-202=
4 15:44:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0003273502","Bastos B=
ir","","08-10-2024 15:37:41","08-10-2024 14:11:20","08-10-2024 14:15:06","C=
ascaded Incident from TTO3137392","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active//No power issue on site ,site on=
 Grid with Ubaie=3D53,8 V The Tx FME Eloundou(693212405) from Huawei is inf=
ormed","system","5181","08-10-2024 15:37:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0003273503","ARMP",""=
,"08-10-2024 15:37:41","08-10-2024 14:11:20","08-10-2024 14:15:06","Cascade=
d Incident from TTO3137392","","Cascade Outage","Active","Cascade Active","=
Cascade Active","Active//No power issue on site ,site on Grid with Ubaie=3D=
53,8 V The Tx FME Eloundou(693212405) from Huawei is informed","system","51=
81","08-10-2024 15:37:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003273483","D=
ragage","IHS_YND_704, IHS_YND_208","08-10-2024 15:36:27","08-10-2024 14:11:=
20","08-10-2024 14:15:06","Active//No power issue on site ,site on Grid wit=
h Ubaie=3D53,8 V The Tx FME Eloundou(693212405) from Huawei is informed","M=
boua Thierry","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid with=
 Ubaie=3D53,8 V The Tx FME Eloundou(693212405) from Huawei is informed","al=
exandre.kamal@ihstowers.com","5108","08-10-2024 15:36:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003273380","E=
lig-Edzoa","","08-10-2024 15:31:00","08-10-2024 14:59:46","08-10-2024 16:08=
:34","Grid outage // Grid Restored","","Grid Supply","Passive","Grid","Nati=
onal Grid - Grid Outage Issue","Grid outage // Grid Restored","alexandre.ka=
mal@ihstowers.com","1875","08-10-2024 15:31:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003273366","T=
ongolo OCM","","08-10-2024 15:29:17","08-10-2024 15:03:12","08-10-2024 16:4=
4:52","Grid bad voltage, site went down because Gen failed to start causing=
 by CB and fuse of Energy meter burn// He bypass the fuse and make a bridge=
 with 02 anothers CB","Delor Telezing","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Circuit Breaker Issue","site went down Gen failed=
 to start because the Cb and fuse the Energy meter burn due to Grid bad vol=
tage// He bypass the fuse and changed the cb,","alexandre.kamal@ihstowers.c=
om","1566","08-10-2024 15:29:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003273349","A=
KONGO","","08-10-2024 15:26:44","08-10-2024 15:20:40","08-10-2024 15:25:37"=
,"Active//No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rodr=
igue (655102999)from Huawei is informed. Repetitive issue","Fanda Brice","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue on site Ubaie=3D52,5V site on Gen. The Tx =
FME Rodrigue (655102999)from Huawei is informed. Repetitive issue","alexand=
re.kamal@ihstowers.com","365","08-10-2024 15:26:44","Sagemcom CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0003273309","Meh=
anda 1","","08-10-2024 15:22:25","08-10-2024 15:11:01","08-10-2024 15:47:58=
","Grid outage site went down because Gen failed to start due to Gen batter=
y faulty// Grid power return","Albran Byorel","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Generator Battery","Grid outage site went down because G=
en failed to start due to Gen battery faulty// Grid power return","kamga.vi=
rgile@ihstowers.com","685","08-10-2024 15:22:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_273","IHS_YND_214","NOCINC0003273071","N=
kolmesseng-II","","08-10-2024 14:47:42","08-10-2024 14:37:59","08-10-2024 1=
5:09:01","site went down due to lack on 01 phases on site //He make the bri=
dge on good phase","Siligap Boris","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","site went down due to lack on 01 phases o=
n site //He make the bridge on good phase","alexandre.kamal@ihstowers.com",=
"584","08-10-2024 14:47:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003272981","MEHANDAN=
","","08-10-2024 14:34:59","08-10-2024 14:11:39","08-10-2024 14:40:04","Cas=
caded Incident from TTO3136780","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se gen start and stopped due to grid bad voltage // he bypass grid and manu=
ally start the gen","system","1400","08-10-2024 14:34:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003272980","M=
aison-Blanche-IHS","","08-10-2024 14:34:53","08-10-2024 14:28:37","08-10-20=
24 15:59:34","Grid outage, no space to deploy a MDG , // grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, no space to deploy a MDG , // grid return","alexandre.kamal@ihstowers.c=
om","377","08-10-2024 14:34:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003272974","N=
kolndongo","","08-10-2024 14:32:54","08-10-2024 14:20:49","08-10-2024 14:35=
:53","Grid outage site went down because Main Gen faulty// Grid power retur=
n","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generato=
r Faulty","Grid outage site went down because Main Gen faulty// Grid power =
return","alexandre.kamal@ihstowers.com","726","08-10-2024 14:32:54","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003272957","O=
dza II OCM","IHS_YND_528","08-10-2024 14:30:44","08-10-2024 14:11:39","08-1=
0-2024 14:40:04","Grid outage, site went down before gen start due to poor =
battery backup // gen start automatically","Albran Byorel","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before gen start due to poor battery backup // gen start autom=
atically","alexandre.kamal@ihstowers.com","1146","08-10-2024 14:30:44","Sag=
emcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003272952","NKO=
MEKUI OCM","","08-10-2024 14:29:37","08-10-2024 14:02:23","08-10-2024 14:15=
:59","Grid outage, site went down before gen start due to poor battery back=
up // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before gen start due to poor battery backup // gen start automa=
tically","kamga.virgile@ihstowers.com","1635","08-10-2024 14:29:37","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_736","NOCINC0003272934","CRF Nkoa=
bang","","08-10-2024 14:27:12","08-10-2024 13:04:37","08-10-2024 13:25:23",=
"Cascaded Incident from TTO3134659","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","GRID outage site went down beca=
use Gen failed to start due to Gen card faulty// Gen manually started","sys=
tem","4955","08-10-2024 14:27:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003272690","A=
ngongo","","08-10-2024 14:05:14","08-10-2024 13:33:59","08-10-2024 13:38:50=
","Active//No power issue on site Ubaie=3D51,5V site on Grid.The Tx FME  Le=
onel Tchatchou(694693436) from Huawei is informed","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site Ubaie=3D51,5V site on Grid.The Tx FME  Leo=
nel Tchatchou(694693436) from Huawei is informed","kouoh.jean@ihstowers.com=
","1876","08-10-2024 14:05:14","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003272689","Eko=
unou","","08-10-2024 14:05:11","08-10-2024 13:57:53","08-10-2024 14:07:19",=
"grid outage,site down before gen start due to poor backup//gen started","A=
lbran Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Battery Low","grid outage,site down before gen start due to poor backup//g=
en started","landry.etame@ihstowers.com","439","08-10-2024 14:05:11","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003272654","M=
essa-Carriere OCM","","08-10-2024 14:02:09","08-10-2024 13:52:01","08-10-20=
24 14:03:44","grid outage, no space for a mdg//grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","grid outage, no spa=
ce for a mdg//grid return","kouoh.jean@ihstowers.com","609","08-10-2024 14:=
02:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003272644","F=
ebe Village","","08-10-2024 14:00:38","08-10-2024 12:57:26","08-10-2024 14:=
05:13","grid outage, gen fails to start due to gen card faulty//gen started=
 manually","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","grid outage, gen fails to start due to gen card faulty//gen=
 started manually","kouoh.jean@ihstowers.com","3793","08-10-2024 14:00:38",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0003272498","Nko=
abang MTN","","08-10-2024 13:51:30","08-10-2024 13:43:22","08-10-2024 13:57=
:03","Grid Outage, site went down because Gen stopped with ""high temp"" al=
arm// He added water and started Gen manualy","Mba Lazare Herve","Equipment=
 Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issu=
e","Grid Outage, site went down because Gen stopped with ""high temp"" alar=
m// He added water and started Gen manualy","landry.etame@ihstowers.com","4=
88","08-10-2024 13:51:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003272371","Lobo OCM=
","","08-10-2024 13:42:31","08-10-2024 13:16:22","08-10-2024 13:20:22","Cas=
caded Incident from TTO3136018","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // gen start ","system","1569"=
,"08-10-2024 13:42:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003271793","E=
ssomba","","08-10-2024 13:26:54","08-10-2024 10:31:58","08-10-2024 13:55:35=
","Grid outage site went down because Gen overload(15KVA, 212A) // he redui=
ced the load","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Overload","Grid outage site went down because Gen overload(15KVA, 212=
A) // he reduiced the load","kouoh.jean@ihstowers.com","10498","08-10-2024 =
13:26:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0003271046","Nkoabang=
2","","08-10-2024 13:06:20","08-10-2024 13:04:37","08-10-2024 13:25:23","Ca=
scaded Incident from TTO3134659","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","GRID outage site went down because=
 Gen failed to start due to Gen card faulty// Gen manually started","system=
","103","08-10-2024 13:06:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003271037","N=
koabang","IHS_YND_526, IHS_YND_736","08-10-2024 13:05:48","08-10-2024 13:04=
:37","08-10-2024 13:25:23","GRID outage site went down because Gen failed t=
o start due to Gen card faulty// Gen manually started","Mba Lazare Herve","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","GRID outage =
site went down because Gen failed to start due to Gen card faulty// Gen man=
ually started","kouoh.jean@ihstowers.com","71","08-10-2024 13:05:48","Sagem=
com CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003270919","NKO=
MEKUI OCM","IHS_YND_341","08-10-2024 13:01:47","08-10-2024 12:54:31","08-10=
-2024 13:20:22","Grid outage, site went down before gen start due to poor b=
attery backup // gen start ","TIENTCHEU NZETCHIEU GAEL","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site =
went down before gen start due to poor battery backup // gen start ","landr=
y.etame@ihstowers.com","437","08-10-2024 13:01:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003270513","AWAE OCM=
","","08-10-2024 12:36:41","08-10-2024 11:37:54","08-10-2024 12:15:15","Cas=
caded Incident from TTO3133437","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen overload(20KVA, 280A) // he reduiced the load","system","3527","08-10-2=
024 12:36:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003270512","Bitoto",=
"","08-10-2024 12:36:40","08-10-2024 11:37:54","08-10-2024 12:15:15","Casca=
ded Incident from TTO3133437","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n overload(20KVA, 280A) // he reduiced the load","system","3526","08-10-202=
4 12:36:41","Sagemcom CMR"
"Closed Complete","Site Down","T1738","IHS_YND_560","NOCINC0003270502","Cit=
e des nations","","08-10-2024 12:35:36","08-10-2024 12:32:31","08-10-2024 1=
3:28:42","site went down because 1/3 rectifier faulty and CB 40A rectifier =
disjuncted//he changed the faulty rectifier and reamed the CB","Paul BIBOUM=
","Equipment Repair","Passive","Rectifier","Rectifier Module","site went do=
wn because 1/3 rectifier faulty and CB 40A rectifier disjuncted//he changed=
 the faulty rectifier and reamed the CB","landry.etame@ihstowers.com","186"=
,"08-10-2024 12:35:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003270469","E=
lig Edzoa","","08-10-2024 12:30:25","08-10-2024 11:09:18","08-10-2024 11:11=
:56","Grid outage, site went down before Gen start due to poor battery back=
up // Gen start manually","Delor Telezing","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen start due to poor battery backup // Gen start manually","kouoh.jean=
@ihstowers.com","4868","08-10-2024 12:30:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003270449","E=
lig-Edzoa","","08-10-2024 12:29:07","08-10-2024 11:09:46","08-10-2024 11:18=
:46","Grid outage // grid return","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid outage // grid return","kouoh.jean@ihsto=
wers.com","4763","08-10-2024 12:29:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003270369","ELOUMDEM=
 CARRIERE 2","","08-10-2024 12:22:20","08-10-2024 12:20:20","08-10-2024 12:=
30:01","Cascaded Incident from TTO3133946","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down due to work Br=
ice fanda/657108549/SAGEMCOM :do the PM//End of work","system","120","08-10=
-2024 12:22:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003270362","MEF=
OU ASSI","IHS_YND_767, IHS_YND_768","08-10-2024 12:21:24","08-10-2024 12:20=
:20","08-10-2024 12:30:20","site went down due to work Brice fanda/65710854=
9/SAGEMCOM :do the PM//End of work","Fanda Brice","Installation Activity","=
Passive","Planned Activity","Installation Activity","site went down due to =
work Brice fanda/657108549/SAGEMCOM :do the PM//End of work","landry.etame@=
ihstowers.com","66","08-10-2024 12:21:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003270334","ELOUMDEM=
 CARRIERE","","08-10-2024 12:17:30","08-10-2024 12:20:20","08-10-2024 12:30=
:01","Cascaded Incident from TTO3133910 - Cascade Removed From TTO3133910",=
"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","site went down due to work Brice fanda/657108549/SAGEMCOM :do the PM//En=
d of work","system","180","08-10-2024 12:17:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003270336","Afanoya"=
,"","08-10-2024 12:17:30","08-10-2024 12:08:40","08-10-2024 12:56:40","Casc=
aded Incident from TTO3133910","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, site went down before Gen=
 start due to poor backup// Gen started","system","530","08-10-2024 12:17:3=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003270335","MBALNGON=
G LYCEE","","08-10-2024 12:17:30","08-10-2024 12:08:40","08-10-2024 12:56:4=
0","Cascaded Incident from TTO3133910","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, site went down befor=
e Gen start due to poor backup// Gen started","system","530","08-10-2024 12=
:17:30","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003270327","Aha=
la","IHS_YND_765, IHS_YND_313","08-10-2024 12:15:45","08-10-2024 12:08:40",=
"08-10-2024 12:56:40","Grid Outage, site went down before Gen start due to =
poor backup// Gen started","Hyemafo Gildas","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid Outage, site went down be=
fore Gen start due to poor backup// Gen started","landry.etame@ihstowers.co=
m","426","08-10-2024 12:15:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003270275","M=
aison-Blanche-IHS","","08-10-2024 12:09:43","08-10-2024 11:59:24","08-10-20=
24 12:22:35","grid outage,no space to space to deploy a mobil gen//grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"grid outage,no space to space to deploy a mobil gen//grid return","kouoh.j=
ean@ihstowers.com","620","08-10-2024 12:09:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_115","NOCINC0003270242","Labogeni=
e","IHS_YND_568","08-10-2024 12:06:11","08-10-2024 11:59:57","08-10-2024 12=
:10:29","grid outage,no space to deploy a mobil gen //grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,=
no space to deploy a mobil gen //grid return","system","374","08-10-2024 12=
:06:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0003270166","A=
nguissa New","","08-10-2024 12:03:10","08-10-2024 11:59:57","08-10-2024 12:=
04:29","Grid outage, site went down before gen start due to poor battery ba=
ckup // Grid power return","MINKA NICOLAS","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage, site went down before gen star=
t due to poor battery backup // Grid power return","kouoh.jean@ihstowers.co=
m","195","08-10-2024 12:03:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003270084","Crf Corn=
ier","","08-10-2024 11:59:50","08-10-2024 11:09:44","08-10-2024 11:15:20","=
Cascaded Incident from TTO3133172","MINKA NICOLAS","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site ubaie=3D54v sit=
e on grid Armand nguetsa is working on site","system","3006","08-10-2024 11=
:59:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003269937","E=
mana","","08-10-2024 11:53:25","08-10-2024 11:36:19","08-10-2024 13:29:06",=
"grid outage//grid return","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","grid outage//grid return","kouoh.jean@ihstowers.com"=
,"1027","08-10-2024 11:53:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003269909","N=
kolndongo","","08-10-2024 11:51:57","08-10-2024 11:42:32","08-10-2024 12:04=
:32","Grid outage site went down because Main Gen faulty// Grid power retur=
n","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generato=
r Faulty","Grid outage site went down because Main Gen faulty// Grid power =
return","kouoh.jean@ihstowers.com","566","08-10-2024 11:51:57","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003269899","Biteng-M=
aetur","","08-10-2024 11:50:52","08-10-2024 11:37:54","08-10-2024 12:15:15"=
,"Cascaded Incident from TTO3133437","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen overload(20KVA, 280A) // he reduiced the load","system","778","08-=
10-2024 11:50:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003269877","B=
iteng","IHS_YND_292, IHS_YND_173, IHS_YND_249","08-10-2024 11:49:14","08-10=
-2024 11:37:54","08-10-2024 12:15:15","Grid outage site went down because G=
en overload(20KVA, 280A) // he reduiced the load","Mba Lazare Herve","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went =
down because Gen overload(20KVA, 280A) // he reduiced the load","kouoh.jean=
@ihstowers.com","681","08-10-2024 11:49:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0003269867","S=
apeur Mimboman","","08-10-2024 11:47:50","08-10-2024 11:29:43","08-10-2024 =
12:11:49","GRID outage site went down because Gen failed to start due to Ge=
n card faulty// Gen manually  started","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","GRID outage site went down b=
ecause Gen failed to start due to Gen card faulty// Gen manually  started",=
"kouoh.jean@ihstowers.com","1087","08-10-2024 11:47:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003269864","Kondengu=
i","","08-10-2024 11:47:20","08-10-2024 11:11:59","08-10-2024 14:07:41","Ca=
scaded Incident from TTO3133374","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid Outage No space to deploy a MDG/=
/Grid Restored","system","2121","08-10-2024 11:47:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003269862","S=
tade-Abega","","08-10-2024 11:46:56","08-10-2024 11:25:32","08-10-2024 12:1=
8:32","Grid Outage site went donw because Gen failed to start due to Gen st=
arter Faulty//Grid Restored","Mba Lazare Herve","Equipment Repair","Passive=
","ACDG Gen","ACDG - Kick Starter","Grid Outage site went donw because Gen =
failed to start due to Gen starter Faulty//Grid Restored","kouoh.jean@ihsto=
wers.com","1284","08-10-2024 11:46:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0003269853","B=
riqueterie","","08-10-2024 11:44:44","08-10-2024 11:12:30","08-10-2024 12:1=
5:56","grid outage, no space for a mdg//grid return","","Grid Supply","Pass=
ive","Grid","National Grid - Grid Outage Issue","grid outage, no space for =
a mdg//grid return","kouoh.jean@ihstowers.com","1935","08-10-2024 11:44:44"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0003269842","K=
amajou Building","","08-10-2024 11:43:52","08-10-2024 11:11:42","08-10-2024=
 12:39:05","No power issue on site U=3D54,1v site on grid Hosiah of huawei =
is informed notice that disjunction of CB in BTS Ocm","Paul BIBOUM","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power issue on site U=3D54,1v site on grid Hosiah of huawei is info=
rmed notice that disjunction of CB in BTS Ocm","kouoh.jean@ihstowers.com","=
1930","08-10-2024 11:43:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003269817","E=
mombo-Tchad","IHS_YND_114","08-10-2024 11:42:07","08-10-2024 11:11:59","08-=
10-2024 14:07:41","Grid Outage No space to deploy a MDG//Grid Restored","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Ou=
tage No space to deploy a MDG//Grid Restored","kouoh.jean@ihstowers.com","1=
809","08-10-2024 11:42:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003269775","A=
bom","","08-10-2024 11:39:31","08-10-2024 11:05:44","08-10-2024 11:05:46","=
","Siligap Boris","Incorrectly Logged Tickets","Error","Error","Error","Err=
or","kouoh.jean@ihstowers.com","2028","08-10-2024 11:39:31","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003269719","NYO=
M FACE MAETUR","","08-10-2024 11:38:44","08-10-2024 11:23:39","08-10-2024 1=
1:42:39","Grid outage, Site went down because landlord do not permit to sta=
rt Gen// Grid return","Fabrice Pouakam","Access Denial","Lease Or Legal","L=
andlord Related Issues","Access Issue - Land Lord","Grid outage, Site went =
down because landlord do not permit to start Gen// Grid return","landry.eta=
me@ihstowers.com","906","08-10-2024 11:38:44","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003269684","Nko=
ulou Carriere carrefourt","","08-10-2024 11:36:04","08-10-2024 11:18:00","0=
8-10-2024 11:37:00","site went down because insufficient of rectifiers due =
to increase load on site // he reduice the load and site is on Grid","Mba L=
azare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module","s=
ite went down because insufficient of rectifiers due to increase load on si=
te // he reduice the load and site is on Grid","landry.etame@ihstowers.com"=
,"1085","08-10-2024 11:36:04","Sagemcom CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0003269675","Imm=
-Olympique","","08-10-2024 11:35:12","08-10-2024 11:16:25","08-10-2024 12:0=
5:43","grid outage,gen failed to start due to power cable of gen stolen sin=
ce//he started the gen with another power cable","Paul BIBOUM","Site Asset =
Theft","Theft","Theft","AC Cable Stolen","grid outage,gen failed to start d=
ue to power cable of gen stolen since//he started the gen with another powe=
r cable","landry.etame@ihstowers.com","1128","08-10-2024 11:35:12","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003269615","M=
adison","IHS_YND_566","08-10-2024 11:29:52","08-10-2024 11:09:44","08-10-20=
24 11:15:20","No power issue on site ubaie=3D54v site on grid Armand nguets=
a is working on site","MFOUAGUEGUE MATHIEU","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite ubaie=3D54v site on grid Armand nguetsa is working on site","kouoh.jean=
@ihstowers.com","1208","08-10-2024 11:29:52","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003269593","Ess=
os Marche","","08-10-2024 11:27:33","08-10-2024 11:11:05","08-10-2024 12:04=
:54","Grid outage, site went down before gen start due to poor battery back=
up // gen start","Delor Telezing","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, site went down before gen s=
tart due to poor battery backup // gen start","landry.etame@ihstowers.com",=
"988","08-10-2024 11:27:33","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003269578","Jou=
vence 2000","","08-10-2024 11:25:22","08-10-2024 11:10:16","08-10-2024 11:3=
0:16","Grid outage, site went down before gen start due to poor battery bac=
kup // gen start automatically","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // gen start automatically",=
"landry.etame@ihstowers.com","907","08-10-2024 11:25:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003269074","E=
kounou","","08-10-2024 10:43:20","08-10-2024 10:01:05","08-10-2024 10:07:59=
","Grid outage, site went down before gen start due to poor battery backup =
// gen start automatically","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // gen start automatically","kouo=
h.jean@ihstowers.com","2901","08-10-2024 10:43:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003268961","F=
ebe Village","","08-10-2024 10:26:34","08-10-2024 10:15:24","08-10-2024 12:=
12:47","grid outage, gen fails to start due to gen card faulty//gen started=
 manually","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","grid outage, gen fails to start due to gen card faulty//gen=
 started manually","kouoh.jean@ihstowers.com","671","08-10-2024 10:26:34","=
Sagemcom CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0003268959","Eto=
ug-Ebe 2","","08-10-2024 10:26:17","08-10-2024 10:13:59","08-10-2024 12:09:=
02","Grid outage, no space to deploy a mobil gen// grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no=
 space to deploy a mobil gen// grid return","landry.etame@ihstowers.com","7=
39","08-10-2024 10:26:17","Sagemcom CMR"
"Closed Complete","Warning","T1543","IHS_YND_336","NOCINC0003268688","EKIE"=
,"","08-10-2024 09:43:21","","","site on alarm due to CB 63A of Gen disjunc=
ted //He reamed the CB","Albran Byorel","Warning","Warning","POWER","Warnin=
g - Low Voltage","site on alarm due to CB 63A of Gen disjuncted //He reamed=
 the CB","nadjia.njaya@ihstowers.com","187","08-10-2024 09:43:21","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003268380","Mambine"=
,"","08-10-2024 08:57:20","08-10-2024 08:24:36","08-10-2024 09:10:35","Casc=
aded Incident from TTO3131676","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site U=3D48,1v site on bat=
tery The fme Tx Etienne 695033981 of huawei is informed","system","1964","0=
8-10-2024 08:57:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0003268379","Mandoumb=
a OCM","","08-10-2024 08:57:20","08-10-2024 08:24:36","08-10-2024 09:10:35"=
,"Cascaded Incident from TTO3131676","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site U=3D48,1v s=
ite on battery The fme Tx Etienne 695033981 of huawei is informed","system"=
,"1964","08-10-2024 08:57:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0003268280","N=
kenglikok","IHS_YND_367, IHS_YND_350","08-10-2024 08:41:47","08-10-2024 08:=
24:36","08-10-2024 09:10:35","No power issue on site U=3D48,1v site on batt=
ery The fme Tx Etienne 695033981 of huawei is informed","Kemeni Franklin","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue on site U=3D48,1v site on battery The fme Tx Etie=
nne 695033981 of huawei is informed","kouoh.jean@ihstowers.com","1032","08-=
10-2024 08:41:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003267926","M=
IMBOMAN LIBERTE","","08-10-2024 07:40:12","08-10-2024 07:11:52","08-10-2024=
 07:45:52","Grid outage, site went down due to main gen faulty // MDG 20Kva=
 has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage, site went down due to main gen fault=
y // MDG 20Kva has deployed","kouoh.jean@ihstowers.com","1701","08-10-2024 =
07:40:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003267842","Yoko OCM=
","","08-10-2024 07:23:21","08-10-2024 06:55:44","08-10-2024 06:58:00","Cas=
caded Incident from TTO3131014","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 52V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579=
59647of Huawei is informed","system","1657","08-10-2024 07:23:21","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003267844","MBIMBIM"=
,"","08-10-2024 07:23:21","08-10-2024 06:55:44","08-10-2024 06:58:00","Casc=
aded Incident from TTO3131014","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 52V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","1657","08-10-2024 07:23:21","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003267843","Ngouetou=
","","08-10-2024 07:23:21","08-10-2024 06:55:44","08-10-2024 06:58:00","Cas=
caded Incident from TTO3131014","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 52V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579=
59647of Huawei is informed","system","1657","08-10-2024 07:23:21","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003267841","Matsari"=
,"","08-10-2024 07:23:20","08-10-2024 06:55:44","08-10-2024 06:58:00","Casc=
aded Incident from TTO3131014","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 52V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","1656","08-10-2024 07:23:20","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003267686","Dong",""=
,"08-10-2024 06:58:41","08-10-2024 06:51:16","08-10-2024 07:38:31","Cascade=
d Incident from TTO3130970","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site U=3D51,7v site on gen =
Gregoire of huawei is informed","system","445","08-10-2024 06:58:41","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0003267678","D=
onga","IHS_YND_444","08-10-2024 06:57:26","08-10-2024 06:51:16","08-10-2024=
 07:38:31","No power issue on site U=3D51,7v site on gen Gregoire of huawei=
 is informed","Parker Tchoup","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D51,7v =
site on gen Gregoire of huawei is informed","kouoh.jean@ihstowers.com","371=
","08-10-2024 06:57:26","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003267656","Tsi=
nga","","08-10-2024 06:53:21","08-10-2024 06:50:15","08-10-2024 07:12:15","=
Grid outage, site went down before gen start due to poor battery backup // =
gen start automatically","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // gen start automatically","landry.=
etame@ihstowers.com","187","08-10-2024 06:53:21","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003267626","Lad=
a I Yde","","08-10-2024 06:46:19","08-10-2024 06:26:03","08-10-2024 08:22:0=
3","Site was on Gen due to Grid Outage, site went down because Gen stopped =
with ""high temp"" alarm// He added water and started Gen manualy","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp=
 - Coolant Level Issue","Site was on Gen due to Grid Outage, site went down=
 because Gen stopped with ""high temp"" alarm// He added water and started =
Gen manualy","landry.etame@ihstowers.com","1217","08-10-2024 06:46:19","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003267453","M=
IMBOMAN LIBERTE","","08-10-2024 06:04:58","08-10-2024 05:17:30","08-10-2024=
 06:00:30","Grid outage, site went down due to main gen faulty // MDG 20Kva=
 has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage, site went down due to main gen fault=
y // MDG 20Kva has deployed","ange.kongo@ihstowers.com","2849","08-10-2024 =
06:04:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003267399","Eto koss=
 Yde","","08-10-2024 05:47:40","08-10-2024 05:42:41","08-10-2024 05:57:41",=
"Cascaded Incident from TTO3130648","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, site went down because =
gen start and stoppen with alarm ""Under voltage"" // He reset gen card and=
 gen manually started","system","299","08-10-2024 05:47:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003267400","ELOUMDEM=
 CARRIERE 2","","08-10-2024 05:47:40","08-10-2024 05:42:41","08-10-2024 05:=
57:41","Cascaded Incident from TTO3130648","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage, site went down b=
ecause gen start and stoppen with alarm ""Under voltage"" // He reset gen c=
ard and gen manually started","system","299","08-10-2024 05:47:40","Sagemco=
m CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003267398","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","08-10-2024 05:46:56","08-10-2024 05:42=
:41","08-10-2024 05:57:41","grid outage, site went down because gen start a=
nd stoppen with alarm ""Under voltage"" // He reset gen card and gen manual=
ly started","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - C=
ontrol Panel","grid outage, site went down because gen start and stoppen wi=
th alarm ""Under voltage"" // He reset gen card and gen manually started","=
stephane.nkamwa@ihstowers.com","256","08-10-2024 05:46:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003267028","B=
iteng-Maetur","","08-10-2024 04:16:48","08-10-2024 03:51:40","08-10-2024 07=
:27:40","Grid Outage Gen failed to start due to AVR Faulty // He replaced t=
he AVR on site and Manually Started the Gen","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - AVR","Grid Outage Gen failed to start =
due to AVR Faulty // He replaced the AVR on site and Manually Started the G=
en","ange.kongo@ihstowers.com","1509","08-10-2024 04:16:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003266897","Dong",""=
,"08-10-2024 04:09:50","08-10-2024 03:21:56","08-10-2024 03:31:29","Cascade=
d Incident from TTO3130117","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site ,site on Battery with =
Ubaie=3D48,9V, Tx Fme Gregoire( 652070658)From Huawei is informed","system"=
,"2874","08-10-2024 04:09:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0003266895","D=
onga","IHS_YND_444","08-10-2024 04:09:07","08-10-2024 03:21:56","08-10-2024=
 05:49:17","No power issue on site ,site on Battery with Ubaie=3D48,9V, Tx =
Fme Gregoire( 652070658)From Huawei is informed","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site ,site on Battery with Ubaie=3D48,9V, Tx Fme Gregoi=
re( 652070658)From Huawei is informed","ange.kongo@ihstowers.com","2832","0=
8-10-2024 04:09:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003266307","M=
IMBOMAN LIBERTE","","08-10-2024 01:40:37","08-10-2024 01:29:30","08-10-2024=
 04:29:17","Grid outage, main gen faulty// MDG 20KVA has deploy","Mba Lazar=
e Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty",=
"Grid outage, main gen faulty// MDG 20KVA has deploy","ange.kongo@ihstowers=
.com","667","08-10-2024 01:40:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_104","NOCINC0003266250","Caringto=
n","","08-10-2024 01:19:41","08-10-2024 01:12:35","08-10-2024 08:30:35","ac=
cess issue during the night,  Site went down due to lack on 02 phases on si=
te // He make the bridge on good phase ","","Access Denial","Lease Or Legal=
","Landlord Related Issues","Access Issue - Land Lord","access issue during=
 the night,  Site went down due to lack on 02 phases on site // He make the=
 bridge on good phase ","ange.kongo@ihstowers.com","427","08-10-2024 01:19:=
41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003266181","Akak-Nko=
zoa-MTN-IHS","","08-10-2024 01:06:50","08-10-2024 00:54:59","08-10-2024 01:=
06:32","Cascaded Incident from TTO3129290","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active: no power issue, site=
 is on grid with Ubaie=3D53V, symphorien(650257151) from Huawei is informed=
","system","711","08-10-2024 01:06:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_212","NOCINC0003266180","H-Genera=
l-Yde","","08-10-2024 01:06:50","08-10-2024 00:54:59","08-10-2024 01:06:32"=
,"Cascaded Incident from TTO3129290","Siligap Boris","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active: no power issue, site is on g=
rid with Ubaie=3D53V, symphorien(650257151) from Huawei is informed","syste=
m","711","08-10-2024 01:06:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003266174","S=
oa-II","IHS_YND_212, IHS_YND_316, IHS_YND_324","08-10-2024 01:04:50","08-10=
-2024 00:54:59","08-10-2024 04:20:35","Active: no power issue, site is on g=
rid with Ubaie=3D53V, symphorien(650257151) from Huawei is informed","Silig=
ap Boris","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active: no power issue, site is on grid with Ubaie=3D=
53V, symphorien(650257151) from Huawei is informed","ange.kongo@ihstowers.c=
om","592","08-10-2024 01:04:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003265882","L=
abogenie","","07-10-2024 23:43:00","07-10-2024 23:39:50","07-10-2024 23:40:=
50","No  power issue U =3D54,8V site on grid.   FME Tx Leonel ( 694 69  34 =
 36 ) from Huawei is informed .","","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No  power issue U =3D54,8V =
site on grid.   FME Tx Leonel ( 694 69  34  36 ) from Huawei is informed ."=
,"ange.kongo@ihstowers.com","191","07-10-2024 23:43:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003265862","Ngouetou=
","","07-10-2024 23:40:01","07-10-2024 22:01:10","07-10-2024 22:02:30","Cas=
caded Incident from TTO3128921","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 52V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579=
59647of Huawei is informed","system","5931","07-10-2024 23:40:01","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003265863","MBIMBIM"=
,"","07-10-2024 23:40:01","07-10-2024 22:01:10","07-10-2024 22:02:30","Casc=
aded Incident from TTO3128921","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 52V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","5931","07-10-2024 23:40:01","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003265861","Yoko OCM=
","","07-10-2024 23:40:00","07-10-2024 22:01:10","07-10-2024 22:02:30","Cas=
caded Incident from TTO3128921","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 52V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579=
59647of Huawei is informed","system","5930","07-10-2024 23:40:00","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003265860","Matsari"=
,"","07-10-2024 23:40:00","07-10-2024 22:01:10","07-10-2024 22:02:30","Casc=
aded Incident from TTO3128921","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 52V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","5930","07-10-2024 23:40:00","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003265858","Ngoum","=
","07-10-2024 23:40:00","07-10-2024 22:01:10","07-10-2024 22:02:30","Cascad=
ed Incident from TTO3128921","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Grid with U =3D 5=
2V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 657959647=
of Huawei is informed","system","5930","07-10-2024 23:40:00","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0003265848","Nko=
l-Mbanda","","07-10-2024 23:38:01","07-10-2024 23:30:21","08-10-2024 01:02:=
49","site went down because gen failed to start due to grid bad voltage and=
 no RCP// he did a bridge on good phase","MINKA NICOLAS","Grid Supply","Pas=
sive","Grid","National Grid - Phase Controller Faulty","site went down beca=
use gen failed to start due to grid bad voltage and no RCP// he did a bridg=
e on good phase","stephane.nkamwa@ihstowers.com","972","07-10-2024 23:38:01=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0003265557","O=
ssombe","","07-10-2024 22:37:16","07-10-2024 22:07:06","08-10-2024 02:21:36=
","Active: no power issue, site is on gen with Ubaie=3D53V, Gregoire (65454=
7479) from Huawei is informed","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power=
 issue, site is on gen with Ubaie=3D53V, Gregoire (654547479) from Huawei i=
s informed","ange.kongo@ihstowers.com","1811","07-10-2024 22:37:16","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003265404","ELOUMDEM=
 CARRIERE 2","","07-10-2024 22:08:40","07-10-2024 22:01:46","07-10-2024 22:=
35:09","Cascaded Incident from TTO3128409","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage, site went down b=
ecause gen start and stoppen with alarm ""Under voltage"" // He reset gen c=
ard and gen manually started","system","414","07-10-2024 22:08:40","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003265403","Eto koss=
 Yde","","07-10-2024 22:08:40","07-10-2024 22:01:46","07-10-2024 22:35:09",=
"Cascaded Incident from TTO3128409","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, site went down because =
gen start and stoppen with alarm ""Under voltage"" // He reset gen card and=
 gen manually started","system","414","07-10-2024 22:08:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003265363","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","07-10-2024 22:02:22","07-10-2024 21:=
59:09","07-10-2024 22:46:49","grid outage, site went down because gen start=
 and stoppen with alarm ""Under voltage"" // He reset gen card and gen manu=
ally started","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","grid outage, site went down because gen start and stoppen =
with alarm ""Under voltage"" // He reset gen card and gen manually started"=
,"dorothy.djantio@ihstowers.com","194","07-10-2024 22:02:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_881","IHS_YND_736","NOCINC0003265010","C=
RF Nkoabang","","07-10-2024 21:09:29","07-10-2024 20:35:20","07-10-2024 22:=
16:11","Site impacted by CTR_084_Nkoabang_P4.please cascade this ticket","M=
ba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","Grid outage site went down because Gen failed to started due to Gen c=
ard Disfuntionny//He reset gen card and Gen manually  started ","dorothy.dj=
antio@ihstowers.com","2050","07-10-2024 21:09:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0003264965","S=
OA 2","","07-10-2024 21:06:46","07-10-2024 20:38:38","07-10-2024 21:37:04",=
"site went down because the Cb(125A*125A) of Pwc dyjoncted due load increas=
ed// he reamed the Cb","Siligap Boris","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Circuit Breaker Issue","site went down because th=
e Cb(125A*125A) of Pwc dyjoncted due load increased// he reamed the Cb","do=
rothy.djantio@ihstowers.com","1689","07-10-2024 21:06:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0003264953","Nkoabang=
2","","07-10-2024 21:05:50","07-10-2024 20:35:29","07-10-2024 22:53:50","gr=
id outage, gen start and stoppen because low oil pressure due to oil leakin=
g from the flywheel // He added oil pressure and gen manually started","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pres=
sure","grid outage, gen start and stoppen because low oil pressure due to o=
il leaking from the flywheel // He added oil pressure and gen manually star=
ted","system","1821","07-10-2024 21:05:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0003264905","NGONA","=
","07-10-2024 20:59:00","07-10-2024 20:35:29","07-10-2024 22:16:11","Cascad=
ed Incident from TTO3127856","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 failed to started due to Gen card Disfuntionny//He reset gen card and Gen =
manually  started ","system","1411","07-10-2024 20:59:00","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003264904","MAN=
GUIERS CHAPELLE","","07-10-2024 20:58:40","07-10-2024 20:44:28","07-10-2024=
 20:57:24","Grid outage, site went down before gen start due to poor batter=
y backup // gen start automatically","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup // gen start automatic=
ally","olivier.kwedi@ihstowers.com","853","07-10-2024 20:58:40","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003264890","N=
koabang","IHS_YND_295, IHS_YND_736","07-10-2024 20:56:34","07-10-2024 20:35=
:29","07-10-2024 22:16:11","Grid outage site went down because Gen failed t=
o started due to Gen card Disfuntionny//He reset gen card and Gen manually =
 started ","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Grid outage site went down because Gen failed to started=
 due to Gen card Disfuntionny//He reset gen card and Gen manually  started =
","dorothy.djantio@ihstowers.com","1266","07-10-2024 20:56:34","Sagemcom CM=
R"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003264854","MIM=
BOMAN LIBERTE","","07-10-2024 20:53:22","07-10-2024 20:35:56","07-10-2024 2=
3:15:54","Grid outage, main gen faulty// MDG 20KVA has deploy","Mba Lazare =
Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","G=
rid outage, main gen faulty// MDG 20KVA has deploy","olivier.kwedi@ihstower=
s.com","1446","07-10-2024 20:53:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003264801","Nkolo II=
 New","","07-10-2024 20:46:41","07-10-2024 20:39:03","07-10-2024 20:45:55",=
"Cascaded Incident from TTO3127750","Mba Lazare Herve","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site ,site on Ge=
n wth Ubaie=3D54.2 V The Tx FME Lionel adjep(655184876) from Huawei is info=
rmed by Sms","system","458","07-10-2024 20:46:41","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003264793","Mim=
boman4","IHS_YND_709","07-10-2024 20:45:12","07-10-2024 20:39:03","07-10-20=
24 20:45:55","No power issue on site ,site on Gen wth Ubaie=3D54.2 V The Tx=
 FME Lionel adjep(655184876) from Huawei is informed by Sms","Mba Lazare He=
rve","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue on site ,site on Gen wth Ubaie=3D54.2 V The=
 Tx FME Lionel adjep(655184876) from Huawei is informed by Sms","olivier.kw=
edi@ihstowers.com","370","07-10-2024 20:45:12","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003263987","MIM=
BOMAN LIBERTE","","07-10-2024 18:38:14","07-10-2024 18:30:06","07-10-2024 1=
9:07:55","Grid outage, site went down due to main gen faulty //Grid power r=
eturn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - G=
enerator Faulty","Grid outage, site went down due to main gen faulty //Grid=
 power return","olivier.kwedi@ihstowers.com","489","07-10-2024 18:38:14","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0003263570","N=
R-Bastos","","07-10-2024 17:51:42","07-10-2024 17:21:38","07-10-2024 19:26:=
47","grid outage// grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","grid outage// grid return","dorothy.djantio@ihs=
towers.com","1805","07-10-2024 17:51:42","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0003263445","Mes=
sassi Carrefourt","","07-10-2024 17:33:40","07-10-2024 17:23:34","07-10-202=
4 17:30:30","No power issue, site is on grid with Ubaie=3D53,2V, the fme tx=
 Armand Nguetsa(699949553) from Huawei is informed","Delor Telezing","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue, site is on grid with Ubaie=3D53,2V, the fme tx Armand=
 Nguetsa(699949553) from Huawei is informed","olivier.kwedi@ihstowers.com",=
"607","07-10-2024 17:33:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0003263424","Mandoumb=
a OCM","","07-10-2024 17:29:00","07-10-2024 17:19:41","07-10-2024 17:29:15"=
,"Cascaded Incident from TTO3126249","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site Ubaie=3D48V=
 site on Gen.The Tx FME Etienne//695033981  from Huawei is informed","syste=
m","559","07-10-2024 17:29:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003263425","Mambine"=
,"","07-10-2024 17:29:00","07-10-2024 17:19:41","07-10-2024 17:29:15","Casc=
aded Incident from TTO3126249","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue on site Ubaie=3D48V site on G=
en.The Tx FME Etienne//695033981  from Huawei is informed","system","559","=
07-10-2024 17:29:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003263426","Nkongtoc=
k","","07-10-2024 17:29:00","07-10-2024 17:19:41","07-10-2024 17:29:15","Ca=
scaded Incident from TTO3126249","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site Ubaie=3D48V sit=
e on Gen.The Tx FME Etienne//695033981  from Huawei is informed","system","=
559","07-10-2024 17:29:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0003263416","N=
kenglikok","IHS_YND_367, IHS_YND_350, IHS_YND_349","07-10-2024 17:27:48","0=
7-10-2024 17:19:41","08-10-2024 00:35:31","No power issue on site Ubaie=3D4=
8V site on Gen.The Tx FME Etienne//695033981  from Huawei is informed","Kem=
eni Franklin","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","No power issue on site Ubaie=3D48V site on Gen.Th=
e Tx FME Etienne//695033981  from Huawei is informed","dorothy.djantio@ihst=
owers.com","487","07-10-2024 17:27:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_085","NOCINC0003263315","Briquete=
rie","","07-10-2024 17:10:20","07-10-2024 16:56:21","07-10-2024 17:10:44","=
Cascaded Incident from TTO3126133","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","ACTIVE  No power issue on site Ubaie=3D54,1V  site =
on Grid. The Tx FME Mouahamadou  (691144435) of Huawei is informed,Notice t=
hat we have disjunction at BTS OCM","system","839","07-10-2024 17:10:20","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0003263307","K=
amajou Building","IHS_YND_085","07-10-2024 17:09:26","07-10-2024 16:56:21",=
"07-10-2024 19:40:44","ACTIVE  No power issue on site Ubaie=3D54,1V  site o=
n Grid. The Tx FME Mouahamadou  (691144435) of Huawei is informed,Notice th=
at we have disjunction at BTS OCM","Paul BIBOUM","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE  No pow=
er issue on site Ubaie=3D54,1V  site on Grid. The Tx FME Mouahamadou  (6911=
44435) of Huawei is informed,Notice that we have disjunction at BTS OCM","d=
orothy.djantio@ihstowers.com","786","07-10-2024 17:09:26","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003263287","Bas=
tos Amb Coree","","07-10-2024 17:05:12","07-10-2024 16:59:00","07-10-2024 1=
7:07:30","Grid outage no space to deploy MDG// Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spac=
e to deploy MDG// Grid return","olivier.kwedi@ihstowers.com","374","07-10-2=
024 17:05:12","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003263278","Mok=
olo Yaounde","","07-10-2024 17:03:23","07-10-2024 16:56:59","07-10-2024 17:=
08:42","Grid outage no space to deploy MDG// Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space =
to deploy MDG// Grid return","olivier.kwedi@ihstowers.com","385","07-10-202=
4 17:03:23","Sagemcom CMR"
"Closed Complete","Warning","CTR_549","IHS_YND_283","NOCINC0003263260","Abo=
me","","07-10-2024 17:01:55","","","Site on battery","MINKA NICOLAS","Warni=
ng","Warning","POWER","Warning - Site on Battery","Site on battery","doroth=
y.djantio@ihstowers.com","66","07-10-2024 17:01:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003263159","C=
rf Cornier","","07-10-2024 16:48:49","07-10-2024 16:47:26","07-10-2024 18:5=
0:58","Active//No power issue on site U=3D54,6V site on Gen TX FME Leonel T=
chatchou(694693436) of huawei is informed notice that havy rain in area","M=
INKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active//No power issue on site U=3D54,6V site on =
Gen TX FME Leonel Tchatchou(694693436) of huawei is informed notice that ha=
vy rain in area","dorothy.djantio@ihstowers.com","84","07-10-2024 16:48:49"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003262666","M=
fou EPC","","07-10-2024 15:56:50","07-10-2024 15:48:37","07-10-2024 16:32:3=
7","Grid fluctuation, site went down because Gen failed to start due to Gri=
d bad voltage and No RCP on site  // He bypassed Grid and started Gen","Mba=
 Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid fluctuation, site went down because Gen failed to start =
due to Grid bad voltage and No RCP on site  // He bypassed Grid and started=
 Gen","dorothy.djantio@ihstowers.com","493","07-10-2024 15:56:50","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003262586","Dong",""=
,"07-10-2024 15:43:40","07-10-2024 15:26:39","07-10-2024 15:30:04","Cascade=
d Incident from TTO3125344","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site,site on Gen with Ubaie=
=3D50.5 V The Tx FME   Gregoire// 652070658 From Huawei is informed","syste=
m","1021","07-10-2024 15:43:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_542","IHS_YND_182","NOCINC0003262553","T=
iti Garage","","07-10-2024 15:37:13","07-10-2024 15:27:59","07-10-2024 15:3=
0:02","Active//No power issue on site U=3D53.5 V site on Grid The TX  FME A=
rmand // 691144412   from Huawei is informed.","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue on site U=3D53.5 V site on Grid The TX  FME Armand =
// 691144412   from Huawei is informed.","dorothy.djantio@ihstowers.com","5=
55","07-10-2024 15:37:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0003262505","D=
onga","IHS_YND_444","07-10-2024 15:28:49","07-10-2024 15:26:39","07-10-2024=
 18:40:04","No power issue on site,site on Gen with Ubaie=3D50.5 V The Tx F=
ME   Gregoire// 652070658 From Huawei is informed","Parker Tchoup","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site,site on Gen with Ubaie=3D50.5 V The Tx FME   Gre=
goire// 652070658 From Huawei is informed","dorothy.djantio@ihstowers.com",=
"131","07-10-2024 15:28:49","Sagemcom CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0003262386","Clu=
b France","","07-10-2024 15:14:26","07-10-2024 15:07:12","07-10-2024 16:00:=
23","Grid outage//Grid power return","","Grid Supply","Passive","Grid","Nat=
ional Grid - Grid Outage Issue","Grid outage//Grid power return","olivier.k=
wedi@ihstowers.com","435","07-10-2024 15:14:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_255","IHS_YND_286","NOCINC0003262288","D=
agobert","","07-10-2024 15:02:47","07-10-2024 14:55:40","07-10-2024 19:30:4=
6","Active//No power issue on site U=3D54.7V site on Grid ,The tx Fme Mouha=
madou (691144435) of Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site U=3D54.7V site on Grid ,The tx Fme Mouh=
amadou (691144435) of Huawei is informed","dorothy.djantio@ihstowers.com","=
428","07-10-2024 15:02:47","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003262249","Jou=
vence 2000","","07-10-2024 14:58:53","07-10-2024 14:55:38","07-10-2024 15:0=
7:28","Grid outage, site went down before gen start due to poor battery bac=
kup // Grid power return","Delor Telezing","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Grid power return","olivier.kwe=
di@ihstowers.com","196","07-10-2024 14:58:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003262178","N=
koabang2","","07-10-2024 14:53:11","07-10-2024 14:49:06","07-10-2024 15:06:=
34","Grid outage,site went down because gen start and stopped with alarm"" =
low oil pressure// He added oil and started Gen","Mba Lazare Herve","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage,sit=
e went down because gen start and stopped with alarm"" low oil pressure// H=
e added oil and started Gen","dorothy.djantio@ihstowers.com","246","07-10-2=
024 14:53:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_140","NOCINC0003262112","BISCUITE=
RIE","","07-10-2024 14:45:40","07-10-2024 14:35:59","07-10-2024 14:40:55","=
Cascaded Incident from TTO3124939","Paul BIBOUM","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active//No power isssue, site is on Grid=
 with Ubaie=3D54,5V,The FME TX Mouhamadou (691144435) from Huawei is inform=
ed","system","581","07-10-2024 14:45:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0003262108","M=
vog-Betsi","IHS_YND_140","07-10-2024 14:45:00","07-10-2024 14:35:59","07-10=
-2024 14:40:55","Active//No power isssue, site is on Grid with Ubaie=3D54,5=
V,The FME TX Mouhamadou (691144435) from Huawei is informed","Hyemafo Gilda=
s","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active//No power isssue, site is on Grid with Ubaie=3D54,5V,=
The FME TX Mouhamadou (691144435) from Huawei is informed","dorothy.djantio=
@ihstowers.com","542","07-10-2024 14:45:00","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003262096","N=
KOMEKUI OCM","","07-10-2024 14:43:35","07-10-2024 14:38:29","07-10-2024 14:=
42:33","Grid outage, site went down before Gen start due to poor battery ba=
ckup // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite went down before Gen start due to poor battery backup // Gen start auto=
matically","dorothy.djantio@ihstowers.com","307","07-10-2024 14:43:35","Sag=
emcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0003262074","Fla=
menco","","07-10-2024 14:41:08","07-10-2024 14:30:58","07-10-2024 14:50:50"=
,"Grid outage, site went down because gen failed to start due to gen card f=
aulty// Gen manually started","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid outage, site went down because gen =
failed to start due to gen card faulty// Gen manually started","olivier.kwe=
di@ihstowers.com","611","07-10-2024 14:41:08","Sagemcom CMR"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0003262054","TSI=
NGA VILLAGE 2","","07-10-2024 14:39:09","07-10-2024 14:29:54","07-10-2024 1=
4:44:09","Hybrid  Gen site, site went down because gen started  and stopped=
  with alarm undervoltage// He reset Gen card and Gen manually started","De=
lor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","Hybrid  Gen site, site went down because gen started  and stopped  with =
alarm undervoltage// He reset Gen card and Gen manually started","olivier.k=
wedi@ihstowers.com","556","07-10-2024 14:39:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003262051","MBIMBIM"=
,"","07-10-2024 14:39:01","07-10-2024 14:31:09","07-10-2024 14:32:29","Casc=
aded Incident from TTO3124845","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795=
9647of Huawei is informed","system","472","07-10-2024 14:39:01","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003262050","Ngouetou=
","","07-10-2024 14:39:00","07-10-2024 14:31:09","07-10-2024 14:32:29","Cas=
caded Incident from TTO3124845","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","471","07-10-2024 14:39:00","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003262049","Yoko OCM=
","","07-10-2024 14:39:00","07-10-2024 14:31:09","07-10-2024 14:32:29","Cas=
caded Incident from TTO3124845","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","471","07-10-2024 14:39:00","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003262047","Ngoum","=
","07-10-2024 14:39:00","07-10-2024 14:31:09","07-10-2024 14:32:29","Cascad=
ed Incident from TTO3124845","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Grid with U =3D 4=
9.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","471","07-10-2024 14:39:00","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003262048","Matsari"=
,"","07-10-2024 14:39:00","07-10-2024 14:31:09","07-10-2024 14:32:29","Casc=
aded Incident from TTO3124845","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795=
9647of Huawei is informed","system","471","07-10-2024 14:39:00","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0003261396","N=
kolso","","07-10-2024 13:22:56","07-10-2024 12:52:50","07-10-2024 13:00:49"=
,"","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue on site, ubaie=3D=
54v site on grid, Mouamadou is informed","landry.etame@ihstowers.com","1807=
","07-10-2024 13:22:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0003261261","A=
bome","","07-10-2024 13:05:02","07-10-2024 12:51:49","07-10-2024 19:06:30",=
"site went down because PWC Dysfutionning (24KW,280A) // Replacement the PW=
C On site","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectif=
ier Module Overloaded","site went down because PWC Dysfutionning (24KW,280A=
) // Replacement the PWC On site","landry.etame@ihstowers.com","794","07-10=
-2024 13:05:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_140","NOCINC0003261260","BISCUITE=
RIE","","07-10-2024 13:04:21","07-10-2024 12:51:18","07-10-2024 13:00:13","=
Cascaded Incident from TTO3124049","Paul BIBOUM","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site U=3D54,5v site on=
 grid Mohamadou of huawei is informed","system","783","07-10-2024 13:04:21"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0003261231","M=
vog-Betsi","IHS_YND_140","07-10-2024 13:00:25","07-10-2024 12:51:18","07-10=
-2024 13:00:13","No power issue on site U=3D54,5v site on grid Mohamadou of=
 huawei is informed","Hyemafo Gildas","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,5v site on grid Mohamadou of huawei is informed","landry.etame@ihstow=
ers.com","548","07-10-2024 13:00:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003261063","L=
abogenie","","07-10-2024 12:41:55","07-10-2024 12:37:44","07-10-2024 12:45:=
09","Active//No power isssue, site is on Grid with Ubaie=3D54,8 V The TX fm=
e Lionel Tchatchoua/694693436/ fromf Huawei is informed by Sms","","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active//No power isssue, site is on Grid with Ubaie=3D54,8 V The TX fme=
 Lionel Tchatchoua/694693436/ fromf Huawei is informed by Sms","landry.etam=
e@ihstowers.com","252","07-10-2024 12:41:55","Sagemcom CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0003261015","Ese=
ka Town","","07-10-2024 12:35:09","07-10-2024 12:32:59","07-10-2024 14:43:1=
1","Grid  bad voltage, site went down because Gen failed to start due to Gr=
id bad voltage and No RCP on site  //he bypassed Grid and Started Gen","Kem=
eni Franklin","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid  bad voltage, site went down because Gen failed to start =
due to Grid bad voltage and No RCP on site  //he bypassed Grid and Started =
Gen","kamga.virgile@ihstowers.com","131","07-10-2024 12:35:09","Sagemcom CM=
R"
"Cancelled","Warning","CTR_395","IHS_YND_249","NOCINC0003260871","Biteng-Ma=
etur","","07-10-2024 12:15:54","","","","Mba Lazare Herve","","","","","","=
landry.etame@ihstowers.com","370","07-10-2024 12:15:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0003260662","C=
lge-Advantiste","","07-10-2024 11:53:09","07-10-2024 11:46:04","07-10-2024 =
12:20:43","grid outage,gen failed to start due to alarm under voltage//he r=
eset the card and started it","MINKA NICOLAS","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start due to a=
larm under voltage//he reset the card and started it","landry.etame@ihstowe=
rs.com","1177","07-10-2024 11:53:09","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0003260512","Nko=
lbisson IITA LP","","07-10-2024 11:38:06","07-10-2024 11:01:55","07-10-2024=
 11:56:55","grid outage,no space to deploy a mobil gen//grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outag=
e,no space to deploy a mobil gen//grid return","kamga.virgile@ihstowers.com=
","2172","07-10-2024 11:38:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003259841","MBIMBIM"=
,"","07-10-2024 10:07:51","07-10-2024 09:58:20","07-10-2024 09:59:20","Casc=
aded Incident from TTO3122624","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795=
9647of Huawei is informed","system","571","07-10-2024 10:07:51","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003259837","Ngoum","=
","07-10-2024 10:07:50","07-10-2024 09:58:20","07-10-2024 09:59:20","Cascad=
ed Incident from TTO3122624","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Grid with U =3D 4=
9.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","570","07-10-2024 10:07:50","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003259838","Matsari"=
,"","07-10-2024 10:07:50","07-10-2024 09:58:20","07-10-2024 09:59:20","Casc=
aded Incident from TTO3122624","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795=
9647of Huawei is informed","system","570","07-10-2024 10:07:50","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003259839","Yoko OCM=
","","07-10-2024 10:07:50","07-10-2024 09:58:20","07-10-2024 09:59:20","Cas=
caded Incident from TTO3122624","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","570","07-10-2024 10:07:50","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003259840","Ngouetou=
","","07-10-2024 10:07:50","07-10-2024 09:58:20","07-10-2024 09:59:20","Cas=
caded Incident from TTO3122624","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","570","07-10-2024 10:07:50","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0003259547","S=
cience","","07-10-2024 09:30:59","07-10-2024 09:29:30","07-10-2024 10:55:35=
","grid outage, site went down because gen failed to start due to Gen overl=
oad(20 KVA, 380A)// He reduced the load, site on gen","TIENTCHEU NZETCHIEU =
GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","grid outag=
e, site went down because gen failed to start due to Gen overload(20 KVA, 3=
80A)// He reduced the load, site on gen","landry.etame@ihstowers.com","90",=
"07-10-2024 09:30:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003259531","N=
koabang","","07-10-2024 09:26:39","07-10-2024 09:21:35","07-10-2024 10:50:3=
1","grid outage,gen failed to start due to card Ge disfunctionning//Gen man=
ually started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","grid outage,gen failed to start due to card Ge disfu=
nctionning//Gen manually started","landry.etame@ihstowers.com","305","07-10=
-2024 09:26:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_535","NOCINC0003259353","Awae Ewo=
nkan","","07-10-2024 08:52:40","07-10-2024 08:37:16","07-10-2024 09:21:25",=
"Cascaded Incident from TTO3122077","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen failed to start du=
e to CB 32A disjuncted causing by Ligthning//he reamed the CB","system","92=
4","07-10-2024 08:52:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003259311","A=
WAE OCM","IHS_YND_535","07-10-2024 08:39:31","07-10-2024 08:35:16","07-10-2=
024 09:21:49","grid outage,gen failed to start due to CB 32A disjuncted cau=
sing by Ligthning//he reamed the CB","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","grid out=
age,gen failed to start due to CB 32A disjuncted causing by Ligthning//he r=
eamed the CB","landry.etame@ihstowers.com","256","07-10-2024 08:39:31","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003259306","S=
tade-Abega","","07-10-2024 08:38:37","07-10-2024 08:34:21","07-10-2024 09:2=
0:14","Grid Outage site went donw because Gen failed to start due to Gen st=
arter Dysfuntionning//Grid Restored","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Kick Starter","Grid Outage site went donw beca=
use Gen failed to start due to Gen starter Dysfuntionning//Grid Restored","=
landry.etame@ihstowers.com","257","07-10-2024 08:38:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0003259244","A=
nguissa New","","07-10-2024 08:27:37","07-10-2024 08:15:57","07-10-2024 09:=
16:04","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","grid outage,no space to deploy a mobil gen//grid return","la=
ndry.etame@ihstowers.com","1796","07-10-2024 08:27:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003259226","Eto koss=
 Yde","","07-10-2024 08:21:40","07-10-2024 08:01:14","07-10-2024 08:46:14",=
"Cascaded Incident from TTO3121922","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen start and stopped wi=
th alarm low oil pressure//he added oil and started it","system","1226","07=
-10-2024 08:21:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003259222","L=
abogenie","IHS_YND_568","07-10-2024 08:20:07","07-10-2024 08:15:57","07-10-=
2024 09:16:04","grid outage,no space to deploy a mobil gen//grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid o=
utage,no space to deploy a mobil gen//grid return","landry.etame@ihstowers.=
com","251","07-10-2024 08:20:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003259211","MBALNGON=
G LYCEE","","07-10-2024 08:17:10","07-10-2024 07:56:03","07-10-2024 08:24:0=
4","Cascaded Incident from TTO3121832","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, site went down befor=
e Gen start due to poor backup// Gen started automatically","system","1267"=
,"07-10-2024 08:17:10","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0003259203","Ako=
k Ndoe Yde","","07-10-2024 08:14:51","07-10-2024 07:56:17","07-10-2024 09:4=
6:13","grid outage,gen failed to start due to grid bad voltage;no rcp //he =
bypassed grid and started the gen","Hyemafo Gildas","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","grid outage,gen failed t=
o start due to grid bad voltage;no rcp //he bypassed grid and started the g=
en","kamga.virgile@ihstowers.com","1114","07-10-2024 08:14:51","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003259194","ELOUMDEM=
 CARRIERE","","07-10-2024 08:12:40","07-10-2024 07:56:03","07-10-2024 08:24=
:04","Cascaded Incident from TTO3121832","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, site went down bef=
ore Gen start due to poor backup// Gen started automatically","system","997=
","07-10-2024 08:12:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003259195","Afanoya"=
,"","07-10-2024 08:12:40","07-10-2024 07:56:03","07-10-2024 08:24:04","Casc=
aded Incident from TTO3121832","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, site went down before Gen=
 start due to poor backup// Gen started automatically","system","997","07-1=
0-2024 08:12:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003259161","M=
EFOU ASSI","IHS_YND_737","07-10-2024 08:05:22","07-10-2024 07:59:14","07-10=
-2024 08:46:14","grid outage,gen start and stopped with alarm low oil press=
ure//he added oil and started it","Fanda Brice","Equipment Repair","Passive=
","ACDG Gen","ACDG - Low Oil Pressure","grid outage,gen start and stopped w=
ith alarm low oil pressure//he added oil and started it","landry.etame@ihst=
owers.com","370","07-10-2024 08:05:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003259154","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","07-10-2024 08:02:13","07-10-=
2024 07:56:03","07-10-2024 08:24:58","Grid Outage, site went down before Ge=
n start due to poor backup// Gen started automatically","Hyemafo Gildas","E=
quipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","G=
rid Outage, site went down before Gen start due to poor backup// Gen starte=
d automatically","landry.etame@ihstowers.com","372","07-10-2024 08:02:13","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003259135","M=
vog-Manga","","07-10-2024 07:59:21","07-10-2024 07:48:15","07-10-2024 08:57=
:43","grid outage,gen failed start due to controller Psc3 faulty//Gen manua=
ly started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","grid outage,gen failed start due to controller Psc3 faulty=
//Gen manualy started","landry.etame@ihstowers.com","668","07-10-2024 07:59=
:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003259106","S=
ous Prefecture","","07-10-2024 07:51:01","07-10-2024 07:43:58","07-10-2024 =
09:00:15","No power issue on site U=3D54,6v site on grid Lionel tchatchou o=
f huawei is onformed notice that havy rain in area","Fanda Brice","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site U=3D54,6v site on grid Lionel tchatchou of huawei=
 is onformed notice that havy rain in area","landry.etame@ihstowers.com","4=
24","07-10-2024 07:51:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0003258998","Ngoulmek=
ong-Nord","","07-10-2024 07:25:10","07-10-2024 07:14:26","07-10-2024 07:42:=
14","Cascaded Incident from TTO3121648","Siligap Boris","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue on site U=3D50,2v =
site on grid synphorien of huawei is informed notice that havy rain in area=
","system","644","07-10-2024 07:25:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0003258994","E=
leveur","IHS_YND_277","07-10-2024 07:24:30","07-10-2024 07:14:26","07-10-20=
24 07:42:14","No power issue on site U=3D50,2v site on grid synphorien of h=
uawei is informed notice that havy rain in area","Siligap Boris","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site U=3D50,2v site on grid synphorien of huawei is inf=
ormed notice that havy rain in area","landry.etame@ihstowers.com","605","07=
-10-2024 07:24:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003258983","C=
rf Cornier","","07-10-2024 07:21:41","07-10-2024 07:14:36","07-10-2024 07:4=
9:41","Active//No power issue on site U=3D54,6V site on Gen TX FME Leonel T=
chatchou(694693436) of Huawei is informed","MINKA NICOLAS","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site U=3D54,6V site on Gen TX FME Leonel Tchatchou(69=
4693436) of Huawei is informed","landry.etame@ihstowers.com","513","07-10-2=
024 07:21:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003258965","Nkolfoul=
ou 2","","07-10-2024 07:18:10","07-10-2024 07:07:19","07-10-2024 07:39:39",=
"Cascaded Incident from TTO3121600","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D53v site o=
n grid synphorien of huawei is informed notice that havy rain in area","sys=
tem","651","07-10-2024 07:18:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003258966","Melen Ba=
'aba","","07-10-2024 07:18:10","07-10-2024 07:07:19","07-10-2024 07:39:39",=
"Cascaded Incident from TTO3121600","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D53v site o=
n grid synphorien of huawei is informed notice that havy rain in area","sys=
tem","651","07-10-2024 07:18:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003258967","TSINGA V=
ILLAGE 2","","07-10-2024 07:18:10","07-10-2024 07:07:19","07-10-2024 07:39:=
39","Cascaded Incident from TTO3121600","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site U=3D53v s=
ite on grid synphorien of huawei is informed notice that havy rain in area"=
,"system","651","07-10-2024 07:18:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003258959","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","07-10-2024 07:16:25","0=
7-10-2024 07:07:19","07-10-2024 07:39:39","No power issue on site U=3D53v s=
ite on grid synphorien of huawei is informed notice that havy rain in area"=
,"Siligap Boris","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue on site U=3D53v site on grid sy=
nphorien of huawei is informed notice that havy rain in area","landry.etame=
@ihstowers.com","546","07-10-2024 07:16:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_370","IHS_YND_274","NOCINC0003258894","E=
mana Lycee","","07-10-2024 07:02:23","07-10-2024 06:58:02","07-10-2024 07:5=
8:02","No power issue on site U=3D54,5v site on grid Synphorien of huawei i=
s informed notice that havy rain in area","Fabrice Pouakam","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site U=3D54,5v site on grid Synphorien of huawei is informed=
 notice that havy rain in area","landry.etame@ihstowers.com","262","07-10-2=
024 07:02:23","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003258347","Bas=
tos Amb Coree","","07-10-2024 03:48:18","07-10-2024 03:46:12","07-10-2024 0=
6:14:40","Grid outage no space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spa=
ce to deploy MDG // Grid return","emmanuel.ghani@ihstowers.com","127","07-1=
0-2024 03:48:18","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0003258178","Mok=
olo Yaounde","","07-10-2024 02:42:20","07-10-2024 02:41:15","07-10-2024 06:=
14:58","Grid outage no space to deploy MDG// Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space =
to deploy MDG// Grid return","emmanuel.ghani@ihstowers.com","66","07-10-202=
4 02:42:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0003257939","N=
KOLMEKONG YDE","","07-10-2024 01:25:15","07-10-2024 00:21:09","07-10-2024 1=
5:04:49","Site went down because  cables supplying the BTS OCM from PWC was=
 stolen (around 20m) //  He replaced cables supplying the BTS OCM from PWC"=
,"Fabrice Pouakam","Site Asset Theft","Theft","Theft","AC Cable Stolen","Si=
te went down because  cables supplying the BTS OCM from PWC was stolen (aro=
und 20m) //  He replaced cables supplying the BTS OCM from PWC","joelle.eke=
ssi@ihstowers.com","3847","07-10-2024 01:25:15","Sagemcom CMR"
"Closed Complete","Site Down","T0458","IHS_YND_103","NOCINC0003257879","Fou=
da Quarter","","07-10-2024 01:02:51","07-10-2024 01:02:47","07-10-2024 01:4=
8:52","Site was on Gen due Grid outage, Site went down because Gen ran unti=
l fuel shortage// Refueling done","Delor Telezing","Fuel Outage","Passive",=
"Diesel","Diesel Outage","Site was on Gen due Grid outage, Site went down b=
ecause Gen ran until fuel shortage// Refueling done","emmanuel.ghani@ihstow=
ers.com","4","07-10-2024 01:02:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003257620","M=
ambine","","06-10-2024 23:11:37","06-10-2024 23:05:35","06-10-2024 23:31:41=
","Grid outage, site went Site went down because Gen failed to start due to=
 Hybrid system dysfonction// He reset the hybrid system, site on gen","Fand=
a Brice","Equipment Repair","Passive","Hybrid","Hybrid Module","Grid outage=
, site went Site went down because Gen failed to start due to Hybrid system=
 dysfonction// He reset the hybrid system, site on gen","joelle.ekessi@ihst=
owers.com","363","06-10-2024 23:11:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003257573","Eto koss=
 Yde","","06-10-2024 22:56:40","06-10-2024 22:52:30","06-10-2024 23:11:41",=
"Cascaded Incident from TTO3119915","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site was on Gen due Grid fluctuation=
, Site went down because Gen stopped due to ""low oil pressure"" alarm// He=
 added oil  and started Gen manualy (investigation ongoing)","system","250"=
,"06-10-2024 22:56:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003257574","ELOUMDEM=
 CARRIERE 2","","06-10-2024 22:56:40","06-10-2024 22:52:30","06-10-2024 23:=
11:41","Cascaded Incident from TTO3119915","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site was on Gen due Grid fluc=
tuation, Site went down because Gen stopped due to ""low oil pressure"" ala=
rm// He added oil  and started Gen manualy (investigation ongoing)","system=
","250","06-10-2024 22:56:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003257557","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","06-10-2024 22:52:33","06-10-2024 22:=
51:30","06-10-2024 23:11:41","Site was on Gen due Grid fluctuation, Site we=
nt down because Gen stopped due to ""low oil pressure"" alarm// He added oi=
l  and started Gen manualy (investigation ongoing)","Fanda Brice","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Site was on Gen due =
Grid fluctuation, Site went down because Gen stopped due to ""low oil press=
ure"" alarm// He added oil  and started Gen manualy (investigation ongoing)=
","joelle.ekessi@ihstowers.com","64","06-10-2024 22:52:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003257520","C=
rf Cornier","","06-10-2024 22:46:18","06-10-2024 22:42:14","07-10-2024 00:4=
5:36","Active//No power issue on site U=3D54,6V site on Grid TX FME Leonel =
Tchatchou(694693436) of Huawei is informed","MINKA NICOLAS","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue on site U=3D54,6V site on Grid TX FME Leonel Tchatchou(=
694693436) of Huawei is informed","joelle.ekessi@ihstowers.com","245","06-1=
0-2024 22:46:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003257453","Nkolo II=
 New","","06-10-2024 22:30:10","06-10-2024 22:03:34","06-10-2024 22:15:58",=
"Cascaded Incident from TTO3119776","Mba Lazare Herve","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site ,site on Ge=
n with Ubaie=3D53,8 V The Tx FME Eloundou(693212405) from Huawei is informe=
d. Notice that we have disjunction at BTS OCM","system","1596","06-10-2024 =
22:30:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003257448","M=
imboman-Village","IHS_YND_709","06-10-2024 22:28:53","06-10-2024 22:03:34",=
"07-10-2024 03:55:13","No power issue on site ,site on Gen with Ubaie=3D53,=
8 V The Tx FME Eloundou(693212405) from Huawei is informed. Notice that we =
have disjunction at BTS OCM","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site ,site on Gen with Ubaie=3D53,8 V The Tx FME Eloundou(693212405) fro=
m Huawei is informed. Notice that we have disjunction at BTS OCM","ange.kon=
go@ihstowers.com","1520","06-10-2024 22:28:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0003256526","S=
cience","","06-10-2024 19:56:57","06-10-2024 19:52:50","06-10-2024 20:11:39=
","grid outage, site went down because gen failed to start due to Gen overl=
oad(20 KVA, 380A)// He reduced the load, site on gen","TIENTCHEU NZETCHIEU =
GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","grid outag=
e, site went down because gen failed to start due to Gen overload(20 KVA, 3=
80A)// He reduced the load, site on gen","ange.kongo@ihstowers.com","248","=
06-10-2024 19:56:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003256335","A=
WAE OCM","","06-10-2024 19:28:20","06-10-2024 19:26:15","06-10-2024 19:28:4=
6","Site went down due to rectifiers insufficiency// site stabilized.","Mba=
 Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"Site went down due to rectifiers insufficiency// site stabilized.","ange.k=
ongo@ihstowers.com","126","06-10-2024 19:28:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003256111","B=
iteng","IHS_YND_249","06-10-2024 18:50:16","06-10-2024 17:45:53","06-10-202=
4 19:41:08","Site on DG,due to grid outage,DG stopped due to overload ( Ilo=
ad ;280A , Gen capacity : 20kva ) //Grid restored.","Mba Lazare Herve","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Overload","Site on DG,due to gr=
id outage,DG stopped due to overload ( Iload ;280A , Gen capacity : 20kva )=
 //Grid restored.","ange.kongo@ihstowers.com","3864","06-10-2024 18:50:16",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003255837","NYO=
M FACE MAETUR","","06-10-2024 17:51:14","06-10-2024 10:26:58","06-10-2024 1=
8:33:30","Site went down due to Circuit Breaker down in the DC BOX (Circuit=
 Breaker 40A overloaded) //He did a bridge waiting for Normalization.","Fab=
rice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Circuit Breaker Issue","Site went down due to Circuit Breaker down in the =
DC BOX (Circuit Breaker 40A overloaded) //He did a bridge waiting for Norma=
lization.","stephane.nkamwa@ihstowers.com","26657","06-10-2024 17:51:14","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003255531","A=
kak-Nkozoa-MTN-IHS","","06-10-2024 17:02:09","06-10-2024 16:52:01","06-10-2=
024 17:09:31","site went down because CB(125A) disjuncted in DC BOX due to =
load // He reamed Cb(125A), site on gen","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site =
went down because CB(125A) disjuncted in DC BOX due to load // He reamed Cb=
(125A), site on gen","ange.kongo@ihstowers.com","609","06-10-2024 17:02:09"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003255258","Kondengu=
i","","06-10-2024 16:14:41","06-10-2024 16:06:25","06-10-2024 16:53:18","Ca=
scaded Incident from TTO3117130","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage,no space to deploy a mobi=
le DG,waiting for  grid restored//Grid restored.","system","496","06-10-202=
4 16:14:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003255252","E=
mombo-Tchad","IHS_YND_114","06-10-2024 16:13:35","06-10-2024 16:06:25","06-=
10-2024 16:53:18","Grid outage///Grid restored.","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage///Grid restored.",=
"ange.kongo@ihstowers.com","431","06-10-2024 16:13:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003254968","Dong",""=
,"06-10-2024 15:38:51","06-10-2024 15:33:36","06-10-2024 15:43:33","Cascade=
d Incident from TTO3116774","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site ,site on Battery with =
Ubaie=3D48,9V, Tx Fme Gregoire( 652070658)From Huawei is informed","system"=
,"315","06-10-2024 15:38:51","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003254947","Mim=
boman4","","06-10-2024 15:37:31","06-10-2024 15:27:20","06-10-2024 17:27:20=
","No power issue on site ubaie=3D54v site on grid The Tx FME Lionel adjep(=
655184876) from Huawei is informed","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site ubaie=3D54v site on grid The Tx FME Lionel adjep(655184876) =
from Huawei is informed","stephane.nkamwa@ihstowers.com","612","06-10-2024 =
15:37:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0003254944","D=
onga","IHS_YND_444","06-10-2024 15:36:43","06-10-2024 15:33:36","06-10-2024=
 17:18:12","No power issue on site ,site on Battery with Ubaie=3D48,9V, Tx =
Fme Gregoire( 652070658)From Huawei is informed","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site ,site on Battery with Ubaie=3D48,9V, Tx Fme Gregoi=
re( 652070658)From Huawei is informed","ange.kongo@ihstowers.com","188","06=
-10-2024 15:36:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003254905","M=
IMBOMAN LIBERTE","","06-10-2024 15:29:49","06-10-2024 15:23:38","06-10-2024=
 15:43:33","grid outage,MAIN gen faulty // grid return","Mba Lazare Herve",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","grid out=
age,MAIN gen faulty // grid return","ange.kongo@ihstowers.com","372","06-10=
-2024 15:29:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003254632","M=
imboman-Village","IHS_YND_709","06-10-2024 14:53:18","06-10-2024 14:47:13",=
"06-10-2024 15:36:39","Grid Outage, site went down before Gen start due to =
poor backup// Gen started automatically","Mba Lazare Herve","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, s=
ite went down before Gen start due to poor backup// Gen started automatical=
ly","ange.kongo@ihstowers.com","366","06-10-2024 14:53:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003254614","N=
kolo II New","","06-10-2024 14:51:18","06-10-2024 14:47:13","06-10-2024 15:=
36:39","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid Outage, site went down before Gen start due to poor =
backup// Gen started automatically","ange.kongo@ihstowers.com","11703","06-=
10-2024 14:51:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0003254548","A=
bome","","06-10-2024 14:43:00","06-10-2024 14:40:45","06-10-2024 17:45:17",=
"Site went down because Power cabinet dysfuntionning(24kW,280A)// Site stab=
ilized.","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifie=
r Module Overloaded","Site went down because Power cabinet dysfuntionning(2=
4kW,280A)// Site stabilized.","ange.kongo@ihstowers.com","136","06-10-2024 =
14:43:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003254508","MBIMBIM"=
,"","06-10-2024 14:37:01","06-10-2024 14:29:29","06-10-2024 14:30:16","Casc=
aded Incident from TTO3116234","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795=
9647of Huawei is informed","system","452","06-10-2024 14:37:01","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003254504","Matsari"=
,"","06-10-2024 14:37:01","06-10-2024 14:29:29","06-10-2024 14:30:16","Casc=
aded Incident from TTO3116234","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795=
9647of Huawei is informed","system","452","06-10-2024 14:37:01","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003254506","Yoko OCM=
","","06-10-2024 14:37:01","06-10-2024 14:29:29","06-10-2024 14:30:16","Cas=
caded Incident from TTO3116234","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","452","06-10-2024 14:37:01","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003254507","Ngouetou=
","","06-10-2024 14:37:01","06-10-2024 14:29:29","06-10-2024 14:30:16","Cas=
caded Incident from TTO3116234","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","452","06-10-2024 14:37:01","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003254503","Ngoum","=
","06-10-2024 14:37:00","06-10-2024 14:29:29","06-10-2024 14:30:16","Cascad=
ed Incident from TTO3116234","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Grid with U =3D 4=
9.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","451","06-10-2024 14:37:00","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003254459","C=
rf Cornier","","06-10-2024 14:33:46","06-10-2024 14:32:41","06-10-2024 18:4=
7:35","Active//No power issue on site U=3D49V site on Grid TX FME Leonel Tc=
hatchou(694693436) of Huawei is informed","MINKA NICOLAS","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site U=3D49V site on Grid TX FME Leonel Tchatchou(6946=
93436) of Huawei is informed","ange.kongo@ihstowers.com","66","06-10-2024 1=
4:33:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003254450","B=
iteng-Maetur","","06-10-2024 14:31:21","06-10-2024 17:45:53","06-10-2024 19=
:41:08","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Site on DG,due to grid outage,DG stopped due to overload=
 ( Iload ;280A , Gen capacity : 20kva ) //Grid restored.","ange.kongo@ihsto=
wers.com","4148","06-10-2024 14:31:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003254442","M=
essa-Carriere OCM","","06-10-2024 14:30:14","06-10-2024 14:12:09","06-10-20=
24 18:29:34","Active: no power issue, site on grid with Ubaie=3D53V, Mohama=
dou(691144435) from Huawei is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power iss=
ue, site on grid with Ubaie=3D53V, Mohamadou(691144435) from Huawei is info=
rmed","ange.kongo@ihstowers.com","1086","06-10-2024 14:30:14","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003254044","E=
ssomba","","06-10-2024 13:38:21","06-10-2024 13:30:16","06-10-2024 16:50:10=
","Grid outage,DG started and stopped due to alarm overcurrent ( Iload of s=
ite 190 A 15kva) //Grid restored.","Mba Lazare Herve","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid outage,DG started and stopped du=
e to alarm overcurrent ( Iload of site 190 A 15kva) //Grid restored.","doro=
thy.djantio@ihstowers.com","486","06-10-2024 13:38:21","Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0003253936","Ang=
uissa New","","06-10-2024 13:11:42","06-10-2024 13:06:31","06-10-2024 13:20=
:26","Grid outage, site went down before gen start due to poor battery back=
up // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before gen =
start due to poor battery backup // Grid return","olivier.kwedi@ihstowers.c=
om","312","06-10-2024 13:11:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003253869","M=
elen Ba'aba","","06-10-2024 13:00:59","06-10-2024 12:57:54","06-10-2024 13:=
33:46","Grid Outage Site went down because Gen Start and Stop due to ''High=
t Temp'' Alarms// he add water and Manually Started the Gen","Siligap Boris=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Grid Outage Site went down because Gen Start and Stop due t=
o ''Hight Temp'' Alarms// he add water and Manually Started the Gen","dorot=
hy.djantio@ihstowers.com","186","06-10-2024 13:00:59","Sagemcom CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0003253734","Mae=
tur","","06-10-2024 12:38:25","06-10-2024 12:31:18","06-10-2024 12:41:18","=
site was on gen due to grid outage, site went down because CB (32 A) Gen dy=
sjuncted due to ""short circuit "" Alarms // Grid Restored","Mboua Thierry"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","site was o=
n gen due to grid outage, site went down because CB (32 A) Gen dysjuncted d=
ue to ""short circuit "" Alarms // Grid Restored","olivier.kwedi@ihstowers.=
com","427","06-10-2024 12:38:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0003253687","B=
ISCUITERIE","","06-10-2024 12:31:56","06-10-2024 12:29:49","06-10-2024 13:2=
2:50","Site went downn due to work our FME/yovol/ 698529863/ SFFM, working =
on site (Normalization the site)//End of work","Paul BIBOUM","Equipment Rep=
lacement","Passive","Planned Activity","Planned Activity - Passive","Site w=
ent downn due to work our FME/yovol/ 698529863/ SFFM, working on site (Norm=
alization the site)//End of work","dorothy.djantio@ihstowers.com","128","06=
-10-2024 12:31:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003253551","N=
kolndongo","","06-10-2024 12:04:45","06-10-2024 11:59:38","06-10-2024 12:16=
:17","Grid outage site went down because mains Gen faulty  //MDG 15kva depl=
oyed","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Gener=
ator Faulty","Grid outage site went down because mains Gen faulty  //MDG 15=
kva deployed","dorothy.djantio@ihstowers.com","308","06-10-2024 12:04:45","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003253538","Dong",""=
,"06-10-2024 11:59:10","06-10-2024 11:16:05","06-10-2024 11:16:08","Cascade=
d Incident from TTO3114814","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue on site ,site on Battery with =
Ubaie=3D48,9V, Tx Fme Gregoire( 652070658)From Huawei is informed","system"=
,"2585","06-10-2024 11:59:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0003253309","D=
onga","IHS_YND_444","06-10-2024 11:17:12","06-10-2024 11:16:05","06-10-2024=
 11:16:08","No power issue on site ,site on Battery with Ubaie=3D48,9V, Tx =
Fme Gregoire( 652070658)From Huawei is informed","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site ,site on Battery with Ubaie=3D48,9V, Tx Fme Gregoi=
re( 652070658)From Huawei is informed","dorothy.djantio@ihstowers.com","67"=
,"06-10-2024 11:17:12","Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0003253288","Ang=
uissa New","","06-10-2024 11:13:57","06-10-2024 11:09:48","06-10-2024 11:27=
:48","Grid outage Site went down because Gen Start  due to poor Batterry Ba=
ck up//Grid Restored","MINKA NICOLAS","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage Site went down because G=
en Start  due to poor Batterry Back up//Grid Restored","olivier.kwedi@ihsto=
wers.com","250","06-10-2024 11:13:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003253123","E=
kie sud","","06-10-2024 10:48:48","06-10-2024 10:38:59","06-10-2024 10:52:1=
6","Grid outage site went down because Gen failed to start  due to Gen batt=
ery faulty and the Cb(125A)of PWC burn// Grid power return","Albran Byorel"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid o=
utage site went down because Gen failed to start  due to Gen battery faulty=
 and the Cb(125A)of PWC burn// Grid power return","dorothy.djantio@ihstower=
s.com","590","06-10-2024 10:48:48","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003253120","Eko=
unou","","06-10-2024 10:47:18","06-10-2024 10:44:07","06-10-2024 10:52:07",=
"Grid outage,site went down before DG start : Poor Batteries backup // DG s=
tarted automatically.","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage,site went down before D=
G start : Poor Batteries backup // DG started automatically.","olivier.kwed=
i@ihstowers.com","192","06-10-2024 10:47:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003252580","N=
kozoa","","06-10-2024 09:26:09","06-10-2024 09:24:03","06-10-2024 10:23:26"=
,"site went down because Gen failed to start due to Grid bad voltage// He b=
ypass the Grid and Gen manually started","Fabrice Pouakam","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","site went down be=
cause Gen failed to start due to Grid bad voltage// He bypass the Grid and =
Gen manually started","dorothy.djantio@ihstowers.com","127","06-10-2024 09:=
26:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003252474","Essomba"=
,"","06-10-2024 09:04:11","06-10-2024 08:47:45","06-10-2024 10:58:31","Casc=
aded Incident from TTO3113797","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because insufficient =
of rectifiers(06) due to increase load on site //he added 01 rectifiers","s=
ystem","986","06-10-2024 09:04:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003252475","Biteng-M=
aetur","","06-10-2024 09:04:11","06-10-2024 08:47:45","06-10-2024 10:58:31"=
,"Cascaded Incident from TTO3113797","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down because insuffi=
cient of rectifiers(06) due to increase load on site //he added 01 rectifie=
rs","system","986","06-10-2024 09:04:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003252473","AWAE OCM=
","","06-10-2024 09:04:10","06-10-2024 08:47:45","06-10-2024 10:58:31","Cas=
caded Incident from TTO3113797","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because insufficient=
 of rectifiers(06) due to increase load on site //he added 01 rectifiers","=
system","985","06-10-2024 09:04:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003252472","Bitoto",=
"","06-10-2024 09:04:10","06-10-2024 08:47:45","06-10-2024 10:58:31","Casca=
ded Incident from TTO3113797","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site went down because insufficient o=
f rectifiers(06) due to increase load on site //he added 01 rectifiers","sy=
stem","985","06-10-2024 09:04:10","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003252455","Bit=
eng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179, IHS_YND_249","06-=
10-2024 08:59:04","06-10-2024 08:47:45","06-10-2024 10:58:31","site went do=
wn because insufficient of rectifiers(06) due to increase load on site //he=
 added 01 rectifiers","Mba Lazare Herve","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","site went down because insufficient of rectifier=
s(06) due to increase load on site //he added 01 rectifiers","olivier.kwedi=
@ihstowers.com","730","06-10-2024 08:59:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0003252399","T=
radex-Nkomo","","06-10-2024 08:54:32","06-10-2024 08:47:45","06-10-2024 10:=
58:31","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","site went down because insufficient of rectifiers(06) due to=
 increase load on site //he added 01 rectifiers","dorothy.djantio@ihstowers=
.com","1887","06-10-2024 08:54:32","Sagemcom CMR"
"Closed Complete","Site Down","T1278","IHS_YND_802","NOCINC0003251570","NYO=
M FACE MAETUR","","06-10-2024 06:02:25","05-10-2024 22:10:18","06-10-2024 0=
1:42:45","Site went down due to CB(80A) disjunction due to load increase in=
 DC BOX //he make a bridge with anothers CB(80A) and CB(63A)","Fabrice Poua=
kam","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit =
Breaker Issue","Site went down due to CB(80A) disjunction due to load incre=
ase in DC BOX //he make a bridge with anothers CB(80A) and CB(63A)","landry=
.etame@ihstowers.com","28328","06-10-2024 06:02:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003251032","MBIMBIM"=
,"","06-10-2024 02:12:41","06-10-2024 02:01:03","06-10-2024 02:02:03","Casc=
aded Incident from TTO3112089","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795=
9647of Huawei is informed","system","698","06-10-2024 02:12:41","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003251030","Yoko OCM=
","","06-10-2024 02:12:41","06-10-2024 02:01:03","06-10-2024 02:02:03","Cas=
caded Incident from TTO3112089","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","698","06-10-2024 02:12:41","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003251031","Ngouetou=
","","06-10-2024 02:12:41","06-10-2024 02:01:03","06-10-2024 02:02:03","Cas=
caded Incident from TTO3112089","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","698","06-10-2024 02:12:41","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003251029","Matsari"=
,"","06-10-2024 02:12:40","06-10-2024 02:01:03","06-10-2024 02:02:03","Casc=
aded Incident from TTO3112089","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795=
9647of Huawei is informed","system","697","06-10-2024 02:12:40","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003250798","N=
gouetou","","06-10-2024 00:53:21","06-10-2024 00:43:08","06-10-2024 01:01:4=
8","No power issue on site ,site on Gen with Ubaie=3D52V, Tx Fme Gregoire( =
652070658)From Huawei is informed and Up 12:01 AM","Parker Tchoup","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site ,site on Gen with Ubaie=3D52V, Tx Fme Gregoire( =
652070658)From Huawei is informed and Up 12:01 AM","kouoh.jean@ihstowers.co=
m","614","06-10-2024 00:53:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0003250543","Nkomkana=
","","05-10-2024 23:44:20","05-10-2024 21:34:55","06-10-2024 00:36:49","Cas=
caded Incident from TTO3111361","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Site went down due to CB(125A) disjunction in PWC//=
 He rearmed CB","system","7765","05-10-2024 23:44:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003250544","Entree C=
ite Verte","","05-10-2024 23:44:20","05-10-2024 21:34:55","06-10-2024 00:36=
:49","Cascaded Incident from TTO3111361","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to CB(125A) =
disjunction in PWC// He rearmed CB","system","7765","05-10-2024 23:44:20","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003250396","C=
ite-Verte","IHS_YND_200, IHS_YND_543","05-10-2024 22:54:42","05-10-2024 21:=
34:55","06-10-2024 00:36:49","Site went down due to CB(125A) disjunction in=
 PWC// He rearmed CB","","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Circuit Breaker Issue","Site went down due to CB(125A) disjunct=
ion in PWC// He rearmed CB","kouoh.jean@ihstowers.com","4788","05-10-2024 2=
2:54:42","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0003250374","Nko=
zoa","","05-10-2024 22:48:34","05-10-2024 22:34:49","06-10-2024 01:41:49","=
Grid Bad Voltage  Site went down because  Gen Failed to start due to lack o=
n 02 phases on site //He bypassed Grid and started Gen manualy","Fabrice Po=
uakam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid Bad Voltage  Site went down because  Gen Failed to start due to =
lack on 02 phases on site //He bypassed Grid and started Gen manualy","land=
ry.etame@ihstowers.com","3488","05-10-2024 22:48:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003250371","ELOUMDEM=
 CARRIERE 2","","05-10-2024 22:47:41","05-10-2024 22:31:23","06-10-2024 00:=
29:48","Cascaded Incident from TTO3111323","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site was on Gen due Grid fluc=
tuation, Site went down because Gen stopped due to ""low oil pressure"" ala=
rm// He added oil (1L) and started Gen manualy","system","978","05-10-2024 =
22:47:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003250370","Eto koss=
 Yde","","05-10-2024 22:47:40","05-10-2024 22:31:23","06-10-2024 00:29:48",=
"Cascaded Incident from TTO3111323","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site was on Gen due Grid fluctuation=
, Site went down because Gen stopped due to ""low oil pressure"" alarm// He=
 added oil (1L) and started Gen manualy","system","977","05-10-2024 22:47:4=
0","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003250365","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","05-10-2024 22:46:33","05-10-2024 22:29=
:44","06-10-2024 00:29:48","Site was on Gen due Grid fluctuation, Site went=
 down because Gen stopped due to ""low oil pressure"" alarm// He added oil =
(1L) and started Gen manualy","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Site was on Gen due Grid fluctuation, Site=
 went down because Gen stopped due to ""low oil pressure"" alarm// He added=
 oil (1L) and started Gen manualy","landry.etame@ihstowers.com","1953","05-=
10-2024 22:46:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003250193","M=
imboman-Village","","05-10-2024 22:05:52","05-10-2024 21:13:41","05-10-2024=
 21:20:34","Active: no power issue on site ,site on Gen with U=3D53,6V Team=
 Eloundou // 693212405 from HUAWEI is informed","Mba Lazare Herve","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active: no power issue on site ,site on Gen with U=3D53,6V Team Eloundo=
u // 693212405 from HUAWEI is informed","kombi.samuel@ihstowers.com","3132"=
,"05-10-2024 22:05:52","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0003250027","Mes=
sassi Carrefourt","","05-10-2024 21:37:12","05-10-2024 21:29:06","05-10-202=
4 21:40:42","No power issue, site is on grid with Ubaie=3D53,2V, the fme tx=
 Armand Nguetsa(699949553) from Huawei is informed","Delor Telezing","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue, site is on grid with Ubaie=3D53,2V, the fme tx Armand=
 Nguetsa(699949553) from Huawei is informed","emmanuel.ghani@ihstowers.com"=
,"487","05-10-2024 21:37:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003249737","M=
essa-Carriere OCM","","05-10-2024 20:59:13","05-10-2024 20:15:07","06-10-20=
24 01:12:25","Grid outage no space to deploy MDG// Grid power retrurn","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age no space to deploy MDG// Grid power retrurn","kombi.samuel@ihstowers.co=
m","2647","05-10-2024 20:59:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003249724","A=
kak-Nkozoa-MTN-IHS","","05-10-2024 20:57:46","05-10-2024 20:05:22","05-10-2=
024 20:58:43","Grid outage, site went down because gen start and stopped du=
e to grid bad voltage // he bypass grid and manually start the gen","Fabric=
e Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","Grid outage, site went down because gen start and stopped due to =
grid bad voltage // he bypass grid and manually start the gen","kombi.samue=
l@ihstowers.com","3145","05-10-2024 20:57:46","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0003249627","Sap=
eur Mimboman","","05-10-2024 20:44:54","05-10-2024 20:42:50","05-10-2024 21=
:55:07","Grid outage,DG failed to start due to ACDG control panel faulty //=
Manually start of DG.","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage,DG failed to start due to ACDG c=
ontrol panel faulty //Manually start of DG.","emmanuel.ghani@ihstowers.com"=
,"125","05-10-2024 20:44:54","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0003249404","Nko=
lo II New","","05-10-2024 20:15:00","05-10-2024 20:12:59","05-10-2024 20:15=
:39","","Mba Lazare Herve","Cascade Outage","Active","Cascade Active","Casc=
ade Active","No power issue on site ,site on Gen  wth Ubaie=3D54.5 V The Tx=
 FME  Lionel adjep(655184876) from Huawei is informed","emmanuel.ghani@ihst=
owers.com","1270","05-10-2024 20:15:00","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003249401","Mim=
boman4","IHS_YND_709","05-10-2024 20:14:03","05-10-2024 20:12:59","05-10-20=
24 20:15:39","No power issue on site ,site on Gen  wth Ubaie=3D54.5 V The T=
x FME  Lionel adjep(655184876) from Huawei is informed","Mba Lazare Herve",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","No power issue on site ,site on Gen  wth Ubaie=3D54.5 V The Tx =
FME  Lionel adjep(655184876) from Huawei is informed","emmanuel.ghani@ihsto=
wers.com","65","05-10-2024 20:14:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003249398","Biteng-M=
aetur","","05-10-2024 20:13:40","05-10-2024 20:11:01","05-10-2024 22:25:01"=
,"Cascaded Incident from TTO3110167","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen overload(20KVA, 280A) // Site stabilized","system","159","05-10-20=
24 20:13:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003249391","B=
iteng","IHS_YND_249","05-10-2024 20:12:05","05-10-2024 20:11:01","05-10-202=
4 22:25:01","Grid outage site went down because Gen overload(20KVA, 280A) /=
/ Site stabilized","Mba Lazare Herve","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","Grid outage site went down because Gen overload(20KVA=
, 280A) // Site stabilized","joelle.ekessi@ihstowers.com","65","05-10-2024 =
20:12:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003249337","M=
IMBOMAN LIBERTE","","05-10-2024 20:06:09","05-10-2024 20:04:04","05-10-2024=
 21:48:38","Site went down because CB OCM(63*80A)  disjuncted in PWC cauing=
 by increase load site  //He reamed CB","Mba Lazare Herve","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site =
went down because CB OCM(63*80A)  disjuncted in PWC cauing by increase load=
 site  //He reamed CB","joelle.ekessi@ihstowers.com","126","05-10-2024 20:0=
6:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003249241","N=
GONA","","05-10-2024 19:49:32","05-10-2024 19:46:29","05-10-2024 20:57:09",=
"Site went down due to  CB Rectifier Disjunted // He reamed the (CB) Rectif=
ier","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Circuit Breaker Issue","Site went down due to  CB Rectifier Disj=
unted // He reamed the (CB) Rectifier","joelle.ekessi@ihstowers.com","184",=
"05-10-2024 19:49:32","Sagemcom CMR"
"Closed Complete","Site Down","T1366","IHS_YND_804","NOCINC0003249124","BEA=
TITUDE ENTR=C9E PAVE","","05-10-2024 19:31:56","05-10-2024 19:30:52","05-10=
-2024 19:35:30","No power issue on site ,site on Gen with Ubaie=3D52.6 V TX=
 FME Mohamadou//691144435 from Huawei is informed..","TIENTCHEU NZETCHIEU G=
AEL","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue on site ,site on Gen with Ubaie=3D52.6 V TX=
 FME Mohamadou//691144435 from Huawei is informed..","emmanuel.ghani@ihstow=
ers.com","64","05-10-2024 19:31:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0003249048","Nkomkana=
","","05-10-2024 19:17:40","05-10-2024 19:14:45","05-10-2024 21:12:03","Cas=
caded Incident from TTO3109761","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Site went down because CB OCM(125A)  disjuncted in =
PWC //He reamed CB","system","175","05-10-2024 19:17:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0003249049","Entree C=
ite Verte","","05-10-2024 19:17:40","05-10-2024 19:14:45","05-10-2024 21:12=
:03","Cascaded Incident from TTO3109761","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down because CB OCM(1=
25A)  disjuncted in PWC //He reamed CB","system","175","05-10-2024 19:17:40=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003249043","C=
ite-Verte","IHS_YND_200, IHS_YND_543","05-10-2024 19:16:49","05-10-2024 19:=
14:45","05-10-2024 21:12:03","Site went down because CB OCM(125A)  disjunct=
ed in PWC //He reamed CB","","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Circuit Breaker Issue","Site went down because CB OCM(125A)=
  disjuncted in PWC //He reamed CB","joelle.ekessi@ihstowers.com","124","05=
-10-2024 19:16:49","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003249008","Jou=
vence 2000","","05-10-2024 19:09:16","05-10-2024 19:04:13","05-10-2024 19:3=
7:08","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"emmanuel.ghani@ihstowers.com","304","05-10-2024 19:09:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003249005","B=
arriere","","05-10-2024 19:08:50","05-10-2024 19:03:46","05-10-2024 20:21:3=
7","Grid fluctuation , site went down because Gen started and stopped due t=
o grid bad voltage,and  no rcp on site // Grid stabilized","Hyemafo Gildas"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid fluctuation , site went down because Gen started and stopped due to gr=
id bad voltage,and  no rcp on site // Grid stabilized","joelle.ekessi@ihsto=
wers.com","305","05-10-2024 19:08:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003248607","MBIMBIM"=
,"","05-10-2024 17:37:31","05-10-2024 17:29:25","05-10-2024 17:29:26","Casc=
aded Incident from TTO3109209","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795=
9647of Huawei is informed","system","486","05-10-2024 17:37:31","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003248606","Ngouetou=
","","05-10-2024 17:37:31","05-10-2024 17:29:25","05-10-2024 17:29:26","Cas=
caded Incident from TTO3109209","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","486","05-10-2024 17:37:31","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003248605","Yoko OCM=
","","05-10-2024 17:37:31","05-10-2024 17:29:25","05-10-2024 17:29:26","Cas=
caded Incident from TTO3109209","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Grid with U =
=3D 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","486","05-10-2024 17:37:31","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003248604","Matsari"=
,"","05-10-2024 17:37:30","05-10-2024 17:29:25","05-10-2024 17:29:26","Casc=
aded Incident from TTO3109209","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Grid with U =3D=
 49.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65795=
9647of Huawei is informed","system","485","05-10-2024 17:37:30","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003248603","Ngoum","=
","05-10-2024 17:37:30","05-10-2024 17:29:25","05-10-2024 17:29:26","Cascad=
ed Incident from TTO3109209","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Grid with U =3D 4=
9.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6579596=
47of Huawei is informed","system","485","05-10-2024 17:37:30","Sagemcom CMR=
"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003248585","Evo=
doula MTN","","05-10-2024 17:33:43","05-10-2024 17:30:34","05-10-2024 18:45=
:12","No power issue on site ,Site on Gen with Ubaie=3D50 V .The Tx Mouhama=
dou//691144435 from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site ,Site on Gen with Ubaie=3D50 V .The Tx Mouhamado=
u//691144435 from Huawei is informed.Site up at 05:37 PM","emmanuel.ghani@i=
hstowers.com","189","05-10-2024 17:33:43","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003248395","NKO=
MEKUI OCM","","05-10-2024 16:58:39","05-10-2024 16:57:18","05-10-2024 17:05=
:02","Grid outage, site went down before Gen start due to poor battery back=
up // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before Gen start due to poor battery backup // Gen start automa=
tically","emmanuel.ghani@ihstowers.com","82","05-10-2024 16:58:39","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003248394","F=
ebe Village","","05-10-2024 16:58:22","05-10-2024 16:55:18","05-10-2024 17:=
14:28","Grid outage site went down because Gen failed to started due to poo=
r backup  and Gen card faulty //Gen started automatically","Mboua Thierry",=
"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low",=
"Grid outage site went down because Gen failed to started due to poor backu=
p  and Gen card faulty //Gen started automatically","joelle.ekessi@ihstower=
s.com","185","05-10-2024 16:58:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003248228","C=
rf Cornier","","05-10-2024 16:21:34","05-10-2024 16:17:30","05-10-2024 17:0=
7:34","Grid outage, site went down because gen fails to start due to CB gen=
 dysjoncted // he reamed the CB","MINKA NICOLAS","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Circuit Breaker Issue","Grid outage, si=
te went down because gen fails to start due to CB gen dysjoncted // he ream=
ed the CB","joelle.ekessi@ihstowers.com","245","05-10-2024 16:21:34","Sagem=
com CMR"
"Closed Complete","Site Down","T0460","IHS_YND_201","NOCINC0003248210","Cit=
e Verte","","05-10-2024 16:17:50","05-10-2024 16:16:46","05-10-2024 16:58:3=
2","Grid Outage no space to deploy MDG // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid Outage no space to =
deploy MDG // Grid return","emmanuel.ghani@ihstowers.com","65","05-10-2024 =
16:17:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003248199","M=
IMBOMAN LIBERTE","","05-10-2024 16:15:37","05-10-2024 16:08:33","05-10-2024=
 18:24:14","Grid outage, site went down due to main gen faulty // MDG 20Kva=
 has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage, site went down due to main gen fault=
y // MDG 20Kva has deployed","joelle.ekessi@ihstowers.com","425","05-10-202=
4 16:15:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003248188","A=
kak-Nkozoa-MTN-IHS","","05-10-2024 16:14:30","05-10-2024 16:11:26","05-10-2=
024 19:56:34","Grid Fluctuation, Site went down because Gen failed to start=
 due to Grid bad voltage // He bypassed Grid and started Gen","Fabrice Poua=
kam","Grid Supply","Passive","Grid","National Grid - Unstable Grid Supply I=
ssue","Grid Fluctuation, Site went down because Gen failed to start due to =
Grid bad voltage // He bypassed Grid and started Gen","joelle.ekessi@ihstow=
ers.com","185","05-10-2024 16:14:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003248163","N=
kolndongo","","05-10-2024 16:06:04","05-10-2024 16:03:56","05-10-2024 17:29=
:57","Grid outage site went down because Main Gen faulty// MDG 15 KVA has d=
eployed","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Ge=
nerator Faulty","Grid outage site went down because Main Gen faulty// MDG 1=
5 KVA has deployed","joelle.ekessi@ihstowers.com","129","05-10-2024 16:06:0=
4","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0003248012","A=
bome","","05-10-2024 15:39:05","05-10-2024 15:37:00","06-10-2024 00:26:49",=
"Site went down because Power cabinet dysfuntionning(24kW,280A)// Site stab=
ilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier=
 Module Overloaded","Site went down because Power cabinet dysfuntionning(24=
kW,280A)// Site stabilized","joelle.ekessi@ihstowers.com","126","05-10-2024=
 15:39:05","Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0003247941","Ang=
uissa New","","05-10-2024 15:25:40","05-10-2024 15:24:32","05-10-2024 15:31=
:32","Grid outage, site went down before gen start due to poor battery back=
up // Grid power return","MINKA NICOLAS","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid power return","emmanuel.ghan=
i@ihstowers.com","266","05-10-2024 15:25:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0003247744","B=
astos Bir","","05-10-2024 15:04:08","05-10-2024 15:03:04","05-10-2024 15:40=
:04","site went down because insufficient of rectifiers (03) due to increas=
e load on site // He added 01 rectifier,Site on Grid","Mboua Thierry","Equi=
pment Repair","Passive","Rectifier","Rectifier Distribution","site went dow=
n because insufficient of rectifiers (03) due to increase load on site // H=
e added 01 rectifier,Site on Grid","joelle.ekessi@ihstowers.com","65","05-1=
0-2024 15:04:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003247738","M=
essa-Carriere OCM","","05-10-2024 15:02:52","05-10-2024 15:01:48","05-10-20=
24 17:04:13","Grid outage no space to deploy //  Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy //  Grid return","joelle.ekessi@ihstowers.com","65","05-10-20=
24 15:02:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0003247685","Odza II =
OCM","","05-10-2024 14:52:01","05-10-2024 14:44:26","05-10-2024 15:50:51","=
Cascaded Incident from TTO3108080","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,site went down because =
gen start and stopped with alarm"" low oil pressure//He reset Gen card and =
started Gen","system","455","05-10-2024 14:52:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0003247687","Ekoumdou=
m OCM","","05-10-2024 14:52:01","05-10-2024 14:44:26","05-10-2024 15:50:51"=
,"Cascaded Incident from TTO3108080","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down becaus=
e gen start and stopped with alarm"" low oil pressure//He reset Gen card an=
d started Gen","system","455","05-10-2024 14:52:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003247686","MEHANDAN=
","","05-10-2024 14:52:01","05-10-2024 14:44:26","05-10-2024 15:50:51","Cas=
caded Incident from TTO3108080","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site went down because gen=
 start and stopped with alarm"" low oil pressure//He reset Gen card and sta=
rted Gen","system","455","05-10-2024 14:52:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0003247666","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","05-10-2024 14:49:34","05=
-10-2024 14:44:26","05-10-2024 15:50:51","Grid outage,site went down becaus=
e gen start and stopped with alarm"" low oil pressure//He reset Gen card an=
d started Gen","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACD=
G - Low Oil Pressure","Grid outage,site went down because gen start and sto=
pped with alarm"" low oil pressure//He reset Gen card and started Gen","joe=
lle.ekessi@ihstowers.com","309","05-10-2024 14:49:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_283","NOCINC0003247639","Abome","=
","05-10-2024 14:42:34","05-10-2024 13:13:59","05-10-2024 13:50:27","Cascad=
ed Incident from TTO3107536","MINKA NICOLAS","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Our engineer Jean Parfait (677549752 / IENG)=
 was informed and after investigation reports No Power issue on site Ubaie =
54V Site on Grid.
FME TX Honore 677551851 is informed
","system","5315","05-10-2024 14:42:34","Sagemcom CMR"
"Closed Complete","Site Down","T1851","IHS_YND_330","NOCINC0003247545","OKO=
A Peage","","05-10-2024 14:30:44","05-10-2024 14:17:41","05-10-2024 16:15:4=
8","No power issue on site,site on Grid with Ubaie=3D54.1  V The TX fme Lio=
nel Tchatchoua/694693436/  of Huawei is informed","Fanda Brice","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site,site on Grid with Ubaie=3D54.1  V The TX fme Lionel=
 Tchatchoua/694693436/  of Huawei is informed","emmanuel.ghani@ihstowers.co=
m","784","05-10-2024 14:30:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_157","NOCINC0003247520","MVAN",""=
,"05-10-2024 14:27:16","05-10-2024 14:19:12","05-10-2024 20:25:31","No powe=
r issue on site ;site on Grid with Ubaie=3D53.5 V The  Team  Eric // 696422=
966 from ZTE is working on site","MINKA NICOLAS","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site ;site on Grid with Ubaie=3D53.5 V The  Team  Eric // 696422966 fro=
m ZTE is working on site","joelle.ekessi@ihstowers.com","485","05-10-2024 1=
4:27:16","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003247342","Evo=
doula MTN","","05-10-2024 13:50:03","05-10-2024 13:39:54","05-10-2024 13:51=
:17","site went down because gen start and stopped due to alarm over voltag=
e//he reset the card , reduced  voltage on AVR  and started   Gen","TIENTCH=
EU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control =
Panel","site went down because gen start and stopped due to alarm over volt=
age//he reset the card , reduced  voltage on AVR  and started   Gen","ange.=
kongo@ihstowers.com","609","05-10-2024 13:50:03","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0003247125","N=
dogbessol","","05-10-2024 13:02:33","05-10-2024 12:53:25","05-10-2024 13:10=
:29","No power issue on site Ubaie=3D51.9V site on battery.The Tx FME Etien=
ne//695033981  from Huawei is informed","Kemeni Franklin","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site Ubaie=3D51.9V site on battery.The Tx FME Etienne//6950339=
81  from Huawei is informed","alexandre.kamal@ihstowers.com","549","05-10-2=
024 13:02:33","Sagemcom CMR"
"Closed Complete","Site Down","T3560","IHS_YND_704","NOCINC0003247113","Bas=
tos Bir","","05-10-2024 13:01:20","05-10-2024 12:56:10","05-10-2024 14:01:4=
0","site went down because insufficient of rectifiers due to increase load =
on site // site Stabilized","Mboua Thierry","Equipment Repair","Passive","R=
ectifier","Rectifier Module","site went down because insufficient of rectif=
iers due to increase load on site // site Stabilized","ange.kongo@ihstowers=
.com","311","05-10-2024 13:01:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003246446","Crf-Mban=
kolo-IHS","","05-10-2024 12:22:00","05-10-2024 09:59:34","05-10-2024 10:18:=
50","Cascaded Incident from TTO3104449","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site wenyt down be=
cause Gen overload(20KVA, 260A) // he reduiced the load","system","8546","0=
5-10-2024 12:22:00","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003244996","Nko=
abang2","","05-10-2024 10:20:09","05-10-2024 10:07:04","05-10-2024 11:37:35=
","Grid outage, site went went down due to gen overload(16Kva, 210A)) // th=
e fme swapp the gen(16kva) by Gen (22KVA)","Mba Lazare Herve","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage, site wen=
t went down due to gen overload(16Kva, 210A)) // the fme swapp the gen(16kv=
a) by Gen (22KVA)","ange.kongo@ihstowers.com","1146","05-10-2024 10:20:09",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003244706","MIM=
BOMAN LIBERTE","","05-10-2024 10:09:10","05-10-2024 10:02:06","05-10-2024 1=
5:12:37","Grid outage site went down because main Gen faulty //  MDG  20 kv=
a has deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Generator Faulty","Grid outage site went down because main Gen faul=
ty //  MDG 20 kva has deployed","ange.kongo@ihstowers.com","425","05-10-202=
4 10:09:10","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003244670","Lad=
a I Yde","","05-10-2024 10:08:07","05-10-2024 10:00:01","05-10-2024 10:19:5=
8","site went down due to work(Herv=E9 Lazard(657108482)/Sagemcom working o=
n site (automated the site)// end of work","Mba Lazare Herve","Equipment Re=
placement","Passive","Planned Activity","Planned Activity - Passive","site =
went down due to work(Herv=E9 Lazard(657108482)/Sagemcom working on site (a=
utomated the site)// end of work","ange.kongo@ihstowers.com","487","05-10-2=
024 10:08:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0003244482","Jean Ves=
pa 2","","05-10-2024 10:04:50","05-10-2024 09:59:27","05-10-2024 10:08:02",=
"Cascaded Incident from TTO3104418","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen overload(20KVA, 260A) // he reduiced the load","system","323","05-10-2=
024 10:04:50","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003244476","Jea=
n Vespa","IHS_YND_574","05-10-2024 10:04:41","05-10-2024 09:59:34","05-10-2=
024 10:18:50","Grid outage site wenyt down because Gen overload(20KVA, 260A=
) // he reduiced the load","Mboua Thierry","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Grid outage site wenyt down because Gen overload=
(20KVA, 260A) // he reduiced the load","ange.kongo@ihstowers.com","308","05=
-10-2024 10:04:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003244445","J=
-Vespa","IHS_YND_544","05-10-2024 10:03:35","05-10-2024 09:59:27","05-10-20=
24 10:08:02","Grid outage site went down because Gen overload(20KVA, 260A) =
// he reduiced the load","Mboua Thierry","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Grid outage site went down because Gen overload(20=
KVA, 260A) // he reduiced the load","alexandre.kamal@ihstowers.com","249","=
05-10-2024 10:03:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003244343","Yoko OCM=
","","05-10-2024 09:59:41","05-10-2024 09:44:14","05-10-2024 09:56:14","Cas=
caded Incident from TTO3104278","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","927","05-10-2024 09:59:41","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003244342","Matsari"=
,"","05-10-2024 09:59:41","05-10-2024 09:44:14","05-10-2024 09:56:14","Casc=
aded Incident from TTO3104278","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","927","05-10-2024 09:59:41","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003244341","Ngoum","=
","05-10-2024 09:59:41","05-10-2024 09:44:14","05-10-2024 09:56:14","Cascad=
ed Incident from TTO3104278","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","927","05-10-2024 09:59:41","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003244344","Ngouetou=
","","05-10-2024 09:59:41","05-10-2024 09:44:14","05-10-2024 09:56:14","Cas=
caded Incident from TTO3104278","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","927","05-10-2024 09:59:41","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003244345","MBIMBIM"=
,"","05-10-2024 09:59:41","05-10-2024 09:44:14","05-10-2024 09:56:14","Casc=
aded Incident from TTO3104278","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","927","05-10-2024 09:59:41","Sagemco=
m CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003243961","Eko=
unou","","05-10-2024 09:40:28","05-10-2024 09:33:14","05-10-2024 10:01:39",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Grid power return","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before Gen=
 start due to poor battery backup // Grid power return","ange.kongo@ihstowe=
rs.com","435","05-10-2024 09:40:28","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003243685","Feb=
e Village","","05-10-2024 08:59:18","05-10-2024 08:49:10","05-10-2024 10:56=
:57","Grid outage site went down because Gen failed to started due to Gen c=
ard faulty and poor backup//Gen manually  started ","Mboua Thierry","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site w=
ent down because Gen failed to started due to Gen card faulty and poor back=
up//Gen manually  started ","ange.kongo@ihstowers.com","1085","05-10-2024 0=
8:59:18","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003243629","NKO=
MEKUI OCM","","05-10-2024 08:48:41","05-10-2024 08:44:35","05-10-2024 08:52=
:33","Grid outage, site went down before Gen start due to poor battery back=
up // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down before Gen start due to poor battery backup // Gen start automa=
tically","ange.kongo@ihstowers.com","247","05-10-2024 08:48:41","Sagemcom C=
MR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0003243546","Mel=
en Ba'aba","","05-10-2024 08:31:33","05-10-2024 08:26:27","05-10-2024 09:10=
:25","Grid outage, site went down because gen ran untill fuel shortage // r=
efueling done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage, site went down because gen ran untill fuel shortage // r=
efueling done","ange.kongo@ihstowers.com","307","05-10-2024 08:31:33","Sage=
mcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003243368","SOA=
 TOWN","","05-10-2024 08:01:05","05-10-2024 07:53:42","05-10-2024 10:01:52"=
,"Wrongly ticket,the site was not down.","Siligap Boris","Incorrectly Logge=
d Tickets","Error","Error","Error","
Wrongly ticket,the site was not down.
","ange.kongo@ihstowers.com","444","05-10-2024 08:01:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0003242537","E=
vodoula OCM","","05-10-2024 06:27:31","05-10-2024 06:12:27","05-10-2024 07:=
10:15","site went down because gen stopped with alarm high temp due to cut =
accordion //he attached the accordion and Gen manually started","TIENTCHEU =
NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","=
site went down because gen stopped with alarm high temp due to cut accordio=
n //he attached the accordion and Gen manually started","alexandre.kamal@ih=
stowers.com","905","05-10-2024 06:27:31","Sagemcom CMR"
"Cancelled","Warning","T1114","IHS_YND_153","NOCINC0003242308","","","05-10=
-2024 05:14:45","","","","Hyemafo Gildas","","","","","","wamayi.ismaila@ih=
stowers.com","3","05-10-2024 05:14:45",""
"Cancelled","Warning","T1114","IHS_YND_153","NOCINC0003242306","","","05-10=
-2024 05:13:06","","","","Hyemafo Gildas","Incorrectly Logged Tickets","Err=
or","Error","Error","Error TT","wamayi.ismaila@ihstowers.com","3","05-10-20=
24 05:13:06",""
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003242008","MBIMBIM"=
,"","05-10-2024 03:10:41","05-10-2024 02:26:20","05-10-2024 02:27:20","Casc=
aded Incident from TTO3101665","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","2661","05-10-2024 03:10:41","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003242007","Ngouetou=
","","05-10-2024 03:10:41","05-10-2024 02:26:20","05-10-2024 02:27:20","Cas=
caded Incident from TTO3101665","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","2661","05-10-2024 03:10:41","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003242006","Yoko OCM=
","","05-10-2024 03:10:40","05-10-2024 02:26:20","05-10-2024 02:27:20","Cas=
caded Incident from TTO3101665","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","2660","05-10-2024 03:10:40","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003242005","Matsari"=
,"","05-10-2024 03:10:40","05-10-2024 02:26:20","05-10-2024 02:27:20","Casc=
aded Incident from TTO3101665","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","2660","05-10-2024 03:10:40","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003242004","Ngoum","=
","05-10-2024 03:10:40","05-10-2024 02:26:20","05-10-2024 02:27:20","Cascad=
ed Incident from TTO3101665","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","2660","05-10-2024 03:10:40","Sagemc=
om CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003241920","Ess=
os Marche","","05-10-2024 02:39:05","05-10-2024 02:32:58","05-10-2024 04:47=
:01","grid outage gen failed to start due to card Ge disfunctionning//Gen m=
anually started(investigation ongoing)","Delor Telezing","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","grid outage gen failed to sta=
rt due to card Ge disfunctionning//Gen manually started(investigation ongoi=
ng)","stephane.nkamwa@ihstowers.com","368","05-10-2024 02:39:05","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0003241891","M=
essassi","","05-10-2024 02:25:55","05-10-2024 02:22:48","05-10-2024 02:42:4=
8","Active, No power issue on site ,site on Grid with Ubaie=3D54.5 V The Tx=
 FME Synphorien /691316854//from huawei is informed","Fabrice Pouakam","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active, No power issue on site ,site on Grid with Ubaie=3D54.5 V Th=
e Tx FME Synphorien /691316854//from huawei is informed","kamga.virgile@ihs=
towers.com","188","05-10-2024 02:25:55","Sagemcom CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0003241577","Meh=
anda 1","","05-10-2024 00:39:46","05-10-2024 00:33:40","05-10-2024 08:30:58=
","Access issue during the night,Gen stopped, Grid return site went down du=
e to Grid bad voltage//He make the bridge on good phase ","Albran Byorel","=
Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue - L=
and Lord","Access issue during the night,Gen stopped, Grid return site went=
 down due to Grid bad voltage//He make the bridge on good phase ","stephane=
.nkamwa@ihstowers.com","366","05-10-2024 00:39:46","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003241513","HOP=
ITAL GENERAL RAIL YDE","","05-10-2024 00:36:31","05-10-2024 00:31:21","05-1=
0-2024 06:11:07","Access issue during the night the Cb of energy meter dysj=
oncted site went down because gen ran untill fuel shortage // He reamed the=
 cb of energy meter(refueling ongoing)","Delor Telezing","Access Denial","L=
ease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access=
 issue during the night the Cb of energy meter dysjoncted site went down be=
cause gen ran untill fuel shortage // He reamed the cb of energy meter(refu=
eling ongoing)","stephane.nkamwa@ihstowers.com","311","05-10-2024 00:36:31"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003241274","Crf Corn=
ier","","04-10-2024 23:23:10","04-10-2024 22:59:45","04-10-2024 23:53:45","=
Cascaded Incident from TTO3100785","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage,no space to deploy a mo=
bil gen //grid return","system","1405","04-10-2024 23:23:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003241272","M=
adison","IHS_YND_566","04-10-2024 23:22:19","04-10-2024 22:59:45","04-10-20=
24 23:53:45","grid outage,no space to deploy a mobil gen //grid return","MF=
OUAGUEGUE MATHIEU","Grid Supply","Passive","Grid","National Grid - Grid Out=
age Issue","grid outage,no space to deploy a mobil gen //grid return","kamg=
a.virgile@ihstowers.com","1355","04-10-2024 23:22:19","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003241246","Ess=
os Marche","","04-10-2024 23:15:12","04-10-2024 23:01:06","04-10-2024 23:56=
:06","grid outage,gen stopped with alarm high temp//he added water radiator=
","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - High Eng=
ine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high te=
mp//he added water radiator","stephane.nkamwa@ihstowers.com","847","04-10-2=
024 23:15:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003241163","S=
OA UNIVERSITY STADIUM","","04-10-2024 22:56:51","04-10-2024 22:32:38","04-1=
0-2024 23:15:23","Active, No power issue on site ,site on Gen with Ubaie=3D=
55.1 V The Tx FME Synphorien /691316854/from huawei is informed","Siligap B=
oris","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active, No power issue on site ,site on Gen with Ubaie=3D=
55.1 V The Tx FME Synphorien /691316854/from huawei is informed","kamga.vir=
gile@ihstowers.com","1453","04-10-2024 22:56:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003240964","Eto koss=
 Yde","","04-10-2024 22:15:50","04-10-2024 22:04:10","04-10-2024 22:31:35",=
"Cascaded Incident from TTO3100404","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen failed to start //ge=
n manually started(investigation ongoing)","system","700","04-10-2024 22:15=
:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003240965","ELOUMDEM=
 CARRIERE 2","","04-10-2024 22:15:50","04-10-2024 22:04:10","04-10-2024 22:=
31:35","Cascaded Incident from TTO3100404","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,gen failed to sta=
rt //gen manually started(investigation ongoing)","system","700","04-10-202=
4 22:15:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003240954","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","04-10-2024 22:12:18","04-10-2024 22:03=
:41","04-10-2024 22:31:56","grid outage,gen failed to start //gen manually =
started(investigation ongoing)","Fanda Brice","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start //gen ma=
nually started(investigation ongoing)","landry.etame@ihstowers.com","669","=
04-10-2024 22:12:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003240185","K=
oweit City","","04-10-2024 20:13:01","04-10-2024 20:08:44","04-10-2024 20:1=
5:44","Active//No power issue on site ,site on Grid  with Ubaie=3D54,3V The=
 Tx FME Leonel Steve  (655184876) from Huawei is informed.","Albran Byorel"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue on site ,site on Grid  with Ubaie=3D54,=
3V The Tx FME Leonel Steve  (655184876) from Huawei is informed.","kouoh.je=
an@ihstowers.com","258","04-10-2024 20:13:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0003240157","B=
ONAS YDE","","04-10-2024 20:09:52","04-10-2024 19:49:37","04-10-2024 19:55:=
37","No power issue on site,site on Grid with Ubaie=3D56,2  V The TX FME Mb=
ah Hosiah (674007438)  from Huawei is informed notice that disjunction of C=
B in Bts Ocm","Paul BIBOUM","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site,site on Grid=
 with Ubaie=3D56,2  V The TX FME Mbah Hosiah (674007438)  from Huawei is in=
formed notice that disjunction of CB in Bts Ocm","kouoh.jean@ihstowers.com"=
,"1216","04-10-2024 20:09:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003240083","A=
wae Ewonkan","","04-10-2024 19:55:03","04-10-2024 19:42:47","04-10-2024 20:=
41:26","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // he bypass grid and manually start the gen","Albran B=
yorel","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage // he bypass grid and manually start the gen","kouoh.jean=
@ihstowers.com","737","04-10-2024 19:55:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003239600","A=
hala","","04-10-2024 18:25:51","04-10-2024 18:16:35","04-10-2024 19:29:35",=
"Grid outage, site went down due to gen overload(20Kva, 300A) // He reduice=
 the load on site","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid outage, site went down due to gen overload(20Kva, =
300A) // He reduice the load on site","kouoh.jean@ihstowers.com","557","04-=
10-2024 18:25:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003239418","S=
OA UNIVERSITY STADIUM","","04-10-2024 17:52:01","04-10-2024 17:46:44","04-1=
0-2024 17:50:44","Active, No power issue on site ,site on Gen with Ubaie=3D=
54.5 V The Tx FME Synphorien /691316854/from huawei is informed","Siligap B=
oris","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active, No power issue on site ,site on Gen with Ubaie=3D=
54.5 V The Tx FME Synphorien /691316854/from huawei is informed","kouoh.jea=
n@ihstowers.com","317","04-10-2024 17:52:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003239320","Afanoya"=
,"","04-10-2024 17:29:01","04-10-2024 17:25:41","04-10-2024 17:35:41","Casc=
aded Incident from TTO3098462","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site went down before DG s=
tart due to Poor Batteries backup// DG startad automatically","system","200=
","04-10-2024 17:29:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003239318","ELOUMDEM=
 CARRIERE","","04-10-2024 17:29:01","04-10-2024 17:25:41","04-10-2024 17:35=
:41","Cascaded Incident from TTO3098462","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage,site went down befo=
re DG start due to Poor Batteries backup// DG startad automatically","syste=
m","200","04-10-2024 17:29:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003239319","MBALNGON=
G LYCEE","","04-10-2024 17:29:01","04-10-2024 17:25:41","04-10-2024 17:35:4=
1","Cascaded Incident from TTO3098462","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down before=
 DG start due to Poor Batteries backup// DG startad automatically","system"=
,"200","04-10-2024 17:29:01","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003239314","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","04-10-2024 17:27:49","04-10-20=
24 17:24:27","04-10-2024 17:35:41","Grid outage,site went down before DG st=
art due to Poor Batteries backup// DG startad automatically","Hyemafo Gilda=
s","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid outage,site went down before DG start due to Poor Batteries backup=
// DG startad automatically","landry.etame@ihstowers.com","310","04-10-2024=
 17:27:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0003239123","M=
essassi","","04-10-2024 16:56:39","04-10-2024 16:38:18","04-10-2024 16:45:1=
8","Active, No power issue on site ,site on Grid with Ubaie=3D54.5 V The Tx=
 FME Synphorien /691316854//from huawei is informed","Fabrice Pouakam","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active, No power issue on site ,site on Grid with Ubaie=3D54.5 V Th=
e Tx FME Synphorien /691316854//from huawei is informed","kouoh.jean@ihstow=
ers.com","1102","04-10-2024 16:56:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003239115","Nkolfoul=
ou 2","","04-10-2024 16:55:30","04-10-2024 16:21:13","04-10-2024 16:24:59",=
"Cascaded Incident from TTO3098224","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,site went down before =
DG start : Poor Batteries backup// DG startad automatically","system","2057=
","04-10-2024 16:55:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003239116","TSINGA V=
ILLAGE 2","","04-10-2024 16:55:30","04-10-2024 16:21:13","04-10-2024 16:24:=
59","Cascaded Incident from TTO3098224","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage,site went down be=
fore DG start : Poor Batteries backup// DG startad automatically","system",=
"2057","04-10-2024 16:55:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003239106","N=
kolfoulou","IHS_YND_278, IHS_YND_719","04-10-2024 16:54:08","04-10-2024 16:=
21:13","04-10-2024 16:24:59","Grid outage,site went down before DG start : =
Poor Batteries backup// DG startad automatically","Siligap Boris","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age,site went down before DG start : Poor Batteries backup// DG startad aut=
omatically","kouoh.jean@ihstowers.com","2056","04-10-2024 16:54:08","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003238977","E=
bogo","","04-10-2024 16:28:27","04-10-2024 16:20:17","04-10-2024 17:31:58",=
"site was on gen due to grid outage, site went down because CB Gen dysjunct=
ed due to lightning // he rearmed the CB Gen and manually started","Siligap=
 Boris","Force Majeure","Natural Disaster","Thunderstrike","Equipment Damag=
ed","site was on gen due to grid outage, site went down because CB Gen dysj=
uncted due to lightning // he rearmed the CB Gen and manually started","kou=
oh.jean@ihstowers.com","491","04-10-2024 16:28:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003238878","M=
ANGUIERS CHAPELLE","","04-10-2024 16:06:03","04-10-2024 15:57:27","04-10-20=
24 16:14:14","Grid outage,site went down before DG start : Poor Batteries b=
ackup// DG startad automatically.","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage,site went=
 down before DG start : Poor Batteries backup// DG startad automatically.",=
"kouoh.jean@ihstowers.com","517","04-10-2024 16:06:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003238863","E=
lig Edzoa","","04-10-2024 16:03:43","04-10-2024 15:54:27","04-10-2024 17:51=
:40","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automatically but OCM still down and up after a power reset=
","Delor Telezing","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Battery Low","Grid outage, site went down before gen start due to poo=
r battery backup // Gen start automatically but OCM still down and up after=
 a power reset","kouoh.jean@ihstowers.com","557","04-10-2024 16:03:43","Sag=
emcom CMR"
"Closed Complete","Site Down","T1606","IHS_YND_342","NOCINC0003238728","LOB=
O MTN","","04-10-2024 15:40:10","04-10-2024 15:30:06","04-10-2024 15:35:21"=
,"Active// No power issue on site site on Grid Ubai=3D55.3V The Team Alberd=
/694869449/From Afro working on site","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active// No power issue on site site on Grid Ubai=3D55.3V The Team Alberd=
/694869449/From Afro working on site","landry.etame@ihstowers.com","605","0=
4-10-2024 15:40:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003238713","E=
kounou","","04-10-2024 15:36:14","04-10-2024 15:29:00","04-10-2024 15:35:39=
","Grid outage,site went down before DG start : Poor Batteries backup// DG =
startad automatically.","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage,site went down before =
DG start : Poor Batteries backup// DG startad automatically.","kouoh.jean@i=
hstowers.com","435","04-10-2024 15:36:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003238593","M=
imboman-Village","","04-10-2024 15:20:43","04-10-2024 13:48:36","04-10-2024=
 13:55:37","Active: no power issue on site ,site on Grid with U=3D53,6V Tx =
fme  Eloundou // 693212405 from HUAWEI is informed","Mba Lazare Herve","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active: no power issue on site ,site on Grid with U=3D53,6V Tx fme =
 Eloundou // 693212405 from HUAWEI is informed","kouoh.jean@ihstowers.com",=
"5528","04-10-2024 15:20:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003238439","N=
GONA","","04-10-2024 15:02:05","04-10-2024 14:59:45","04-10-2024 15:03:45",=
"No power issue, site is on grid with Ubaie=3D53V, Lionel adjep(655184876) =
from Huawei is informed.","Mba Lazare Herve","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, si=
te is on grid with Ubaie=3D53V, Lionel adjep(655184876) from Huawei is info=
rmed.","kouoh.jean@ihstowers.com","141","04-10-2024 15:02:05","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0003238431","S=
apeur","","04-10-2024 15:00:41","04-10-2024 14:27:28","04-10-2024 16:08:42"=
,"Site went down because CB 125A who feeds equipment Ocm disjuncted in DC B=
OX // he did a bridge with anothers CB(80A) and site up","Mboua Thierry","E=
quipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker=
 Issue","Site went down because CB 125A who feeds equipment Ocm disjuncted =
in DC BOX // he did a bridge with anothers CB(80A) and site up","kouoh.jean=
@ihstowers.com","1995","04-10-2024 15:00:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003238427","Crf Corn=
ier","","04-10-2024 15:00:00","04-10-2024 14:37:18","04-10-2024 15:09:49","=
Cascaded Incident from TTO3097436","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, No space to deploy MDG=
 // Grid restored","system","1362","04-10-2024 15:00:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003238419","M=
adison","IHS_YND_566","04-10-2024 14:59:05","04-10-2024 14:37:18","04-10-20=
24 15:09:49","Grid Outage, No space to deploy MDG // Grid restored","MFOUAG=
UEGUE MATHIEU","Grid Supply","Passive","Grid","National Grid - Grid Outage =
Issue","Grid Outage, No space to deploy MDG // Grid restored","kouoh.jean@i=
hstowers.com","1308","04-10-2024 14:59:05","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0003238063","Sap=
eur Mimboman","","04-10-2024 14:15:04","04-10-2024 14:08:58","04-10-2024 16=
:22:30","Grid outage,DG failed to start due to ACDG control panel faulty //=
Manually start of DG.","Mba Lazare Herve","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid outage,DG failed to start due to ACDG c=
ontrol panel faulty //Manually start of DG.","emmanuel.ghani@ihstowers.com"=
,"367","04-10-2024 14:15:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0003238045","C=
hapelle-Nsimeyong","","04-10-2024 14:09:44","04-10-2024 14:08:39","04-10-20=
24 14:37:32","Active// No power Issue Site on Grid Ubai =3D54,2 V, The TX F=
ME Mbah Hosiah (674007438) is informed","MINKA NICOLAS","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power Issue Site on Grid Ubai =3D54,2 V, The TX FME Mbah Hosiah (67400=
7438) is informed","joelle.ekessi@ihstowers.com","65","04-10-2024 14:09:44"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003237959","Ess=
os Marche","","04-10-2024 13:54:24","04-10-2024 13:45:21","04-10-2024 14:25=
:43","Grid Outage, Site went down due to Poor Backup before Gen start// Gen=
 started automaticaly","Delor Telezing","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Outage, Site went down due to=
 Poor Backup before Gen start// Gen started automaticaly","emmanuel.ghani@i=
hstowers.com","544","04-10-2024 13:54:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003237937","E=
kounou","","04-10-2024 13:49:57","04-10-2024 13:48:50","04-10-2024 13:49:36=
","Grid outage, site went down before Gen start due to poor battery backup =
// Grid power return","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, site went down before G=
en start due to poor battery backup // Grid power return","joelle.ekessi@ih=
stowers.com","67","04-10-2024 13:49:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003237925","Crf Corn=
ier","","04-10-2024 13:46:31","04-10-2024 13:43:28","04-10-2024 14:22:28","=
Cascaded Incident from TTO3096876","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, no space to deploy a m=
obile gen // grid return","system","183","04-10-2024 13:46:31","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003237920","M=
adison","IHS_YND_566","04-10-2024 13:45:32","04-10-2024 13:43:28","04-10-20=
24 14:22:28","Grid outage, no space to deploy a mobile gen // grid return",=
"MFOUAGUEGUE MATHIEU","Grid Supply","Passive","Grid","National Grid - Grid =
Outage Issue","Grid outage, no space to deploy a mobile gen // grid return"=
,"joelle.ekessi@ihstowers.com","125","04-10-2024 13:45:32","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0003237498","Mam=
bine","","04-10-2024 12:59:57","04-10-2024 12:55:50","04-10-2024 13:55:57",=
"No power issue on site U=3D50v site on grid Team Tchakount=E9 693846869 of=
 Telis working on site","Fanda Brice","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D50v site on grid Team Tchakount=E9 693846869 of Telis working on site","=
emmanuel.ghani@ihstowers.com","248","04-10-2024 12:59:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003237388","E=
lig-Edzoa","","04-10-2024 12:36:17","04-10-2024 12:34:12","04-10-2024 13:05=
:48","Grid Outage// Grid restored","","Grid Supply","Passive","Grid","Natio=
nal Grid - Grid Outage Issue","Grid Outage// Grid restored","joelle.ekessi@=
ihstowers.com","126","04-10-2024 12:36:17","Sagemcom CMR"
"Closed Complete","Warning","CTR_031","IHS_YND_319","NOCINC0003237376","SOA=
 2","","04-10-2024 12:33:25","","","Site alarming High Temp because Aircon =
is faulty and Shelter always open awaitting reduction temperature // temper=
ature has stabilized","Siligap Boris","Warning","Warning","ENVIRONMENT","Wa=
rning - High Temperature","Site alarming High Temp because Aircon is faulty=
 and Shelter always open awaitting reduction temperature // temperature has=
 stabilized","alexandre.kamal@ihstowers.com","934","04-10-2024 12:33:25","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0003237358","P=
olytechnique","","04-10-2024 12:28:58","04-10-2024 12:22:49","04-10-2024 14=
:12:37","Site went down due to CB(125A) disjunction in PWC who feeds equipm=
ent OCM//He rearmed CB","","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Circuit Breaker Issue","Site went down due to CB(125A) disjun=
ction in PWC who feeds equipment OCM//He rearmed CB","joelle.ekessi@ihstowe=
rs.com","370","04-10-2024 12:28:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0003237321","E=
SSOS OASIS 1111","","04-10-2024 12:23:36","04-10-2024 12:21:32","04-10-2024=
 12:27:27","Active// No power issue on site site on Grid=3D53.3V The Tx FME=
 Armand Ngetsa/691144412/From Huawei is informed and Up at 12:27 AM","Silig=
ap Boris","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active// No power issue on site site on Grid=3D53.3V =
The Tx FME Armand Ngetsa/691144412/From Huawei is informed and Up at 12:27 =
AM","joelle.ekessi@ihstowers.com","125","04-10-2024 12:23:36","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0003236927","M=
volye-New","","04-10-2024 11:20:38","04-10-2024 11:17:32","04-10-2024 12:44=
:12","Active// No power Issue Site on Grid Ubai =3D51,6 V, The TX FME Mbah =
Hosiah (674007438) is informed and Up at 11:27 AM","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// =
No power Issue Site on Grid Ubai =3D51,6 V, The TX FME Mbah Hosiah (6740074=
38) is informed and Up at 11:27 AM","joelle.ekessi@ihstowers.com","187","04=
-10-2024 11:20:38","Sagemcom CMR"
"Closed Complete","Site Down","T0578","IHS_YND_375","NOCINC0003236677","Ngo=
ung","","04-10-2024 10:42:35","04-10-2024 10:38:45","04-10-2024 11:00:21","=
Active// No power issue on site. site on Grid 55.6V The Team Abel/654078239=
/From AFLO is working on site ""Swapp Micro""","Kemeni Franklin","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active// No power issue on site. site on Grid 55.6V The Team Abel/6540782=
39/From AFLO is working on site ""Swapp Micro""","emmanuel.ghani@ihstowers.=
com","231","04-10-2024 10:42:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0003236639","S=
AA 2","","04-10-2024 10:38:31","04-10-2024 10:32:27","04-10-2024 11:10:05",=
"Active//No power issue on site ,site on GRID with Ubaie=3D53.6 V The TX FM=
E Gregoire(654547479) from Huawei is informed..site up at 10:38 AM","Parker=
 Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active//No power issue on site ,site on GRID with Ubai=
e=3D53.6 V The TX FME Gregoire(654547479) from Huawei is informed..site up =
at010:38 AM","joelle.ekessi@ihstowers.com","365","04-10-2024 10:38:31","Sag=
emcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003236628","Jou=
vence 2000","","04-10-2024 10:35:37","04-10-2024 10:34:31","04-10-2024 10:4=
8:38","Grid Outage Site went down because Gen start due to Poor Backup//Gri=
d Restored","Delor Telezing","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid Outage Site went down because Gen start =
due to Poor Backup//Grid Restored","emmanuel.ghani@ihstowers.com","67","04-=
10-2024 10:35:37","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003236434","Lad=
a I Yde","","04-10-2024 10:04:12","04-10-2024 10:02:08","04-10-2024 10:14:1=
3","Site went downn due to work our FME/Herve Mba / 657108482/ Sagemcom,// =
doing  PM// End of Work","Mba Lazare Herve","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went downn due to work =
our FME/Herve Mba / 657108482/ Sagemcom,// doing  PM// End of Work","emmanu=
el.ghani@ihstowers.com","126","04-10-2024 10:04:12","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0003236402","Abo=
me","","04-10-2024 09:59:32","04-10-2024 09:54:27","04-10-2024 11:16:37"," =
PWC dysfonctionning(24Kw,280A)","MINKA NICOLAS","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded"," PWC dysfonctionning(24Kw,280A=
)","emmanuel.ghani@ihstowers.com","306","04-10-2024 09:59:32","Sagemcom CMR=
"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003236076","Jou=
vence 2000","","04-10-2024 09:22:18","04-10-2024 09:15:12","04-10-2024 09:2=
9:35","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automatically",=
"emmanuel.ghani@ihstowers.com","428","04-10-2024 09:22:18","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0003236041","Lob=
o 2","","04-10-2024 09:15:09","04-10-2024 09:07:04","04-10-2024 11:50:59","=
 No power issue, site is on Gen ubai=3D49V  The fme tx  Mohamadou (69114413=
5) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No powe=
r issue, site is on Gen ubai=3D49V  The fme tx  Mohamadou (691144135) from =
Huawei is informed","emmanuel.ghani@ihstowers.com","485","04-10-2024 09:15:=
09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003236023","Ngoum","=
","04-10-2024 09:12:10","04-10-2024 09:06:00","04-10-2024 09:39:22","Cascad=
ed Incident from TTO3094733","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outade,site went down because gen st=
art and stopped  with alarm"" low oil pressure//He reset Gen card and start=
ed Gen","system","370","04-10-2024 09:12:10","Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0003236018","Yok=
o MTN","IHS_YND_475","04-10-2024 09:11:04","04-10-2024 09:06:00","04-10-202=
4 09:39:22","Grid outade,site went down because gen start and stopped  with=
 alarm"" low oil pressure//He reset Gen card and started Gen","Parker Tchou=
p","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid =
outade,site went down because gen start and stopped  with alarm"" low oil p=
ressure//He reset Gen card and started Gen","emmanuel.ghani@ihstowers.com",=
"305","04-10-2024 09:11:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003235428","A=
KONGO","","04-10-2024 07:13:10","04-10-2024 07:09:03","04-10-2024 07:12:43"=
,"Active:  No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rod=
rigue (655102999)from Huawei is informed. Repetitive issue ","Fanda Brice",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active:  No power issue on site Ubaie=3D52,5V site on Gen. The =
Tx FME Rodrigue (655102999)from Huawei is informed. Repetitive issue ","joe=
lle.ekessi@ihstowers.com","249","04-10-2024 07:13:10","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003235427","OBA=
M NGOLA OCM","","04-10-2024 07:13:09","04-10-2024 07:07:00","04-10-2024 07:=
13:38","Site went down because 02/04 rectifiers hanging //he reset rectifie=
rs,site on Grid ","MINKA NICOLAS","Equipment Repair","Passive","Rectifier",=
"Rectifier Module","Site went down because 02/04 rectifiers hanging //he re=
set rectifiers,site on Grid ","emmanuel.ghani@ihstowers.com","369","04-10-2=
024 07:13:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003235399","Nsimalen=
 OCM","","04-10-2024 07:09:00","04-10-2024 07:02:59","04-10-2024 07:07:47",=
"Cascaded Incident from TTO3093972","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Fluctuation, Site went down b=
ecause Gen failed to start due Grid bad voltage no rcp on site// He bypasse=
d Grid and started Gen manualy","system","361","04-10-2024 07:09:00","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003235388","N=
kolda","IHS_YND_327","04-10-2024 07:07:08","04-10-2024 07:02:59","04-10-202=
4 07:07:47","Grid Fluctuation, Site went down because Gen failed to start d=
ue Grid bad voltage no rcp on site// Grid stabilized","Albran Byorel","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid F=
luctuation, Site went down because Gen failed to start due Grid bad voltage=
 no rcp on site// Grid stabilized","joelle.ekessi@ihstowers.com","250","04-=
10-2024 07:07:08","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0003235289","Nko=
lbisson IITA LP","","04-10-2024 06:34:10","04-10-2024 06:28:02","04-10-2024=
 07:00:23","No power issue The Ubaie=3D54 V site on Grid.The  FME TX Mouama=
dou/658791013 //From  is informed","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue The Ubaie=
=3D54 V site on Grid.The  FME TX Mouamadou/658791013 //From  is informed.Si=
te up at 06:35 AM","emmanuel.ghani@ihstowers.com","369","04-10-2024 06:34:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0003235208","M=
essassi","","04-10-2024 06:24:27","04-10-2024 06:20:19","04-10-2024 07:15:4=
0","No power issue on site ,site on Grid  with Ubaie=3D54.5 V The Tx  FME S=
ynphorien /691316854//from  huawei is informed","Fabrice Pouakam","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site ,site on Grid  with Ubaie=3D54.5 V The Tx  FME Sy=
nphorien /691316854//from  huawei is informed","joelle.ekessi@ihstowers.com=
","248","04-10-2024 06:24:27","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0003235169","Abo=
me","","04-10-2024 06:20:18","04-10-2024 06:12:11","04-10-2024 09:06:45","S=
ite went down because PWC is overload(24Kw,280A)// Load dicrease ","MINKA N=
ICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module Overload=
ed","Site went down because PWC is overload(24Kw,280A)// Load dicrease ","e=
mmanuel.ghani@ihstowers.com","488","04-10-2024 06:20:18","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0003235050","Abo=
me","","04-10-2024 05:49:00","04-10-2024 05:35:42","04-10-2024 05:51:33","S=
ite went down because PWC is overload(24Kw,280A)// Load dicrease ","MINKA N=
ICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module Overload=
ed","Site went down because PWC is overload(24Kw,280A)// Load dicrease ","o=
livier.kwedi@ihstowers.com","800","04-10-2024 05:49:00","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003235049","MBI=
MBIM","","04-10-2024 05:47:51","04-10-2024 05:39:38","04-10-2024 09:13:18",=
"Site went down because Gen ran until fuel shortage// Refueling done (Refue=
ling by EBONDE)","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel O=
utage","Site went down because Gen ran until fuel shortage// Refueling done=
 (Refueling by EBONDE)","olivier.kwedi@ihstowers.com","494","04-10-2024 05:=
47:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003234292","K=
oweit City","","04-10-2024 01:02:18","04-10-2024 00:57:07","04-10-2024 00:5=
8:53","Active//No power issue on site ,site on Grid  with Ubaie=3D54,3V The=
 Tx FME Leonel Steve  (655184876) from Huawei is informed.","Albran Byorel"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue on site ,site on Grid  with Ubaie=3D54,=
3V The Tx FME Leonel Steve  (655184876) from Huawei is informed.","dorothy.=
djantio@ihstowers.com","312","04-10-2024 01:02:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003234197","Nkolo II=
 New","","04-10-2024 00:31:50","04-10-2024 00:22:00","04-10-2024 00:24:51",=
"Cascaded Incident from TTO3092561","Mba Lazare Herve","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power issue, site is on=
 Grid with Ubaie=3D51.3V, Team Sonkoue (694567096) from SNEF by NOKIA worki=
ng on site( Upgrade 10G_COREVO)","system","590","04-10-2024 00:31:50","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003234195","M=
imboman-Village","IHS_YND_709","04-10-2024 00:30:06","04-10-2024 00:22:00",=
"04-10-2024 00:24:51","Active//No power issue, site is on Grid with Ubaie=
=3D51.3V, Team Sonkoue (694567096) from SNEF by NOKIA working on site( Upgr=
ade 10G_COREVO)","Mba Lazare Herve","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issue, sit=
e is on Grid with Ubaie=3D51.3V, Team Sonkoue (694567096) from SNEF by NOKI=
A working on site( Upgrade 10G_COREVO)","dorothy.djantio@ihstowers.com","48=
7","04-10-2024 00:30:06","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0003234076","Lob=
o 2","","03-10-2024 23:49:00","03-10-2024 23:39:52","04-10-2024 01:10:35","=
 Site went down because Gen stopped due to ""Short Circuit"" alarm //He res=
et the Gen Card and Gen manually started","TIENTCHEU NZETCHIEU GAEL","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Control Panel"," Site went down b=
ecause Gen stopped due to ""Short Circuit"" alarm //He reset the Gen Card a=
nd Gen manually started","olivier.kwedi@ihstowers.com","549","03-10-2024 23=
:49:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0003233950","M=
essassi","","03-10-2024 23:21:33","03-10-2024 23:16:29","04-10-2024 03:57:4=
1","Active//No Power issue on site U=3D54,3V site on GRid  and Synphorien /=
691316854/ from huawei is informed","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o Power issue on site U=3D54,3V site on GRid  and Synphorien /691316854/ fr=
om huawei is informed","dorothy.djantio@ihstowers.com","305","03-10-2024 23=
:21:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0003233915","M=
beng","IHS_YND_553","03-10-2024 23:14:57","03-10-2024 23:05:53","04-10-2024=
 01:03:13"," site went down because Gen failed to start due to Gen Card dys=
functioning // Gen manually started","Fanda Brice","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel"," site went down because Gen failed =
to start due to Gen Card dysfunctioning // Gen manually started","dorothy.d=
jantio@ihstowers.com","545","03-10-2024 23:14:57","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0003233841","Abo=
me","","03-10-2024 22:54:06","03-10-2024 22:45:01","04-10-2024 01:10:55","S=
ite went down because PWC is overload(24Kw,280A)// Load dicrease ","MINKA N=
ICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module Overload=
ed","Site went down because PWC is overload(24Kw,280A)// Load dicrease ","o=
livier.kwedi@ihstowers.com","546","03-10-2024 22:54:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003233429","E=
lig-Edzoa","","03-10-2024 21:32:23","03-10-2024 21:24:17","03-10-2024 22:48=
:10","Grid outage//MDG 20kva deployed","","Grid Supply","Passive","Grid","N=
ational Grid - Grid Outage Issue","Grid outage//MDG 20kva deployed","alexan=
dre.kamal@ihstowers.com","487","03-10-2024 21:32:23","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0003232976","Nko=
londom","","03-10-2024 20:25:40","03-10-2024 20:16:29","03-10-2024 21:44:29=
","site went down because all rectifiers(03/03) disfonctionning//He reset r=
ectiifiers ,Site on Grid","Fabrice Pouakam","Equipment Repair","Passive","R=
ectifier","Rectifier - Circuit Breaker","site went down because all rectifi=
ers(03/03) disfonctionning//He reset rectiifiers ,Site on Grid","kamga.virg=
ile@ihstowers.com","552","03-10-2024 20:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003232864","MBIMBIM"=
,"","03-10-2024 20:21:21","03-10-2024 20:10:19","03-10-2024 20:12:00","Casc=
aded Incident from TTO3090938","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","662","03-10-2024 20:21:21","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003232863","Ngouetou=
","","03-10-2024 20:21:21","03-10-2024 20:10:19","03-10-2024 20:12:00","Cas=
caded Incident from TTO3090938","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","662","03-10-2024 20:21:21","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003232860","Ngoum","=
","03-10-2024 20:21:20","03-10-2024 20:10:19","03-10-2024 20:12:00","Cascad=
ed Incident from TTO3090938","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","661","03-10-2024 20:21:20","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003232862","Yoko OCM=
","","03-10-2024 20:21:20","03-10-2024 20:10:19","03-10-2024 20:12:00","Cas=
caded Incident from TTO3090938","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","661","03-10-2024 20:21:20","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003232861","Matsari"=
,"","03-10-2024 20:21:20","03-10-2024 20:10:19","03-10-2024 20:12:00","Casc=
aded Incident from TTO3090938","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","661","03-10-2024 20:21:20","Sagemco=
m CMR"
"Closed Complete","Warning","T0401","IHS_YND_205","NOCINC0003231629","Tongo=
lo MTN","","03-10-2024 18:41:14","","","grid outage, site alarm due to gen =
stoppen with an unknown alarm because screen of the gen card issue// He res=
et gen card and Gen manually started","Fabrice Pouakam","Warning","Warning"=
,"POWER","Warning - Site on Battery","grid outage, site alarm due to gen st=
oppen with an unknown alarm because screen of the gen card issue// He reset=
 gen card and Gen manually started","stephane.nkamwa@ihstowers.com","968","=
03-10-2024 18:41:14","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003231463","Jou=
vence 2000","","03-10-2024 18:10:59","03-10-2024 17:30:47","03-10-2024 17:4=
5:58","Grid outage, site went down before Gen start due to poor battery bac=
kup // Gen start automatically","Delor Telezing","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before Gen start due to poor battery backup // Gen start automatically",=
"kamga.virgile@ihstowers.com","2413","03-10-2024 18:10:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003231335","E=
bogo","","03-10-2024 17:45:03","03-10-2024 17:34:59","03-10-2024 18:01:52",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Gen start automatically","Siligap Boris","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re Gen start due to poor battery backup // Gen start automatically","alexan=
dre.kamal@ihstowers.com","605","03-10-2024 17:45:03","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0003230921","Awa=
e Ewonkan","","03-10-2024 16:48:36","03-10-2024 16:33:21","03-10-2024 17:19=
:21","site was on gen due to grid outage, site went down because CB Gen dys=
juncted due to lightning // Gen manually started","Albran Byorel","Force Ma=
jeure","Natural Disaster","Thunderstrike","Equipment Damaged","site was on =
gen due to grid outage, site went down because CB Gen dysjuncted due to lig=
htning // Gen manually started","kamga.virgile@ihstowers.com","1186","03-10=
-2024 16:48:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003230739","E=
lig-Edzoa","","03-10-2024 16:32:57","03-10-2024 16:18:50","03-10-2024 17:23=
:50","Grid outage // MDG 20Kva has deployed","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid outage // MDG 20Kva has deplo=
yed","alexandre.kamal@ihstowers.com","849","03-10-2024 16:32:57","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_191","IHS_YND_338","NOCINC0003230029","O=
kola OCM","","03-10-2024 15:40:44","03-10-2024 15:31:39","03-10-2024 15:41:=
29","Active: No power issue, site is on grid with Ubaie=3D53V, Mohamadou(69=
1144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435=
) from Huawei is informed","alexandre.kamal@ihstowers.com","546","03-10-202=
4 15:40:44","Sagemcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0003229961","Nko=
lbisson usine des eaux","","03-10-2024 15:29:31","03-10-2024 15:20:21","03-=
10-2024 15:24:17"," No power issue, site is on Grid with  the fme tx  Moham=
adou (691144135) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm"," No power issue, site is on Grid with  the fme tx  Mohamadou (6911441=
35) from Huawei is informed","kamga.virgile@ihstowers.com","551","03-10-202=
4 15:29:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003229958","MBALNGON=
G LYCEE","","03-10-2024 15:28:51","03-10-2024 15:11:22","03-10-2024 16:08:5=
8","Cascaded Incident from TTO3087697","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, Site went down due t=
o Gen overload(20Kva .300A) and poor battery backup// He reduced load and g=
en manually started","system","1049","03-10-2024 15:28:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003229959","Afanoya"=
,"","03-10-2024 15:28:51","03-10-2024 15:11:22","03-10-2024 16:08:58","Casc=
aded Incident from TTO3087697","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, Site went down due to Gen=
 overload(20Kva .300A) and poor battery backup// He reduced load and gen ma=
nually started","system","1049","03-10-2024 15:28:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003229957","ELOUMDEM=
 CARRIERE","","03-10-2024 15:28:50","03-10-2024 15:11:22","03-10-2024 16:08=
:58","Cascaded Incident from TTO3087697","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, Site went down due=
 to Gen overload(20Kva .300A) and poor battery backup// He reduced load and=
 gen manually started","system","1048","03-10-2024 15:28:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003229936","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","03-10-2024 15:24:25","03-10-=
2024 15:10:22","03-10-2024 16:08:58","Grid Outage, Site went down due to Ge=
n overload(20Kva .300A) and poor battery backup// He reduced load and gen m=
anually started","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Grid Outage, Site went down due to Gen overload(20Kva .30=
0A) and poor battery backup// He reduced load and gen manually started","al=
exandre.kamal@ihstowers.com","844","03-10-2024 15:24:25","Sagemcom CMR"
"Cancelled","Warning","T3232","IHS_YND_767","NOCINC0003229916","ELOUMDEM CA=
RRIERE","","03-10-2024 15:22:35","","","","Fanda Brice","","","","","","kam=
ga.virgile@ihstowers.com","669","03-10-2024 15:22:35","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_270","NOCINC0003229660","Santa Barb=
ara Yde","","03-10-2024 15:04:51","","","Grid outage, Site alarming because=
 Gen failed to start due to Gen card faulty// He started Gen manualy(replac=
ement ongoing)","Delor Telezing","Warning","Warning","POWER","Warning - Sit=
e on Battery","Grid outage, Site alarming because Gen failed to start due t=
o Gen card faulty// He started Gen manualy(replacement ongoing)","stephane.=
nkamwa@ihstowers.com","1159","03-10-2024 15:04:51","Sagemcom CMR"
"Cancelled","Warning","CTR_133","IHS_YND_120","NOCINC0003229601","Sapeur Mi=
mboman","","03-10-2024 14:54:33","","","","Mba Lazare Herve","","","","",""=
,"alexandre.kamal@ihstowers.com","574","03-10-2024 14:54:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003229588","F=
ebe Village","","03-10-2024 14:51:55","03-10-2024 14:26:46","03-10-2024 16:=
02:51","grid outage, site went down because gen failed to start due to gen =
card faulty// Gen manually started","Mboua Thierry","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","grid outage, site went down becaus=
e gen failed to start due to gen card faulty// Gen manually started","alexa=
ndre.kamal@ihstowers.com","1510","03-10-2024 14:51:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0003229582","N=
koa Ayos","","03-10-2024 14:50:37","03-10-2024 14:23:32","03-10-2024 15:01:=
29","ACTIVE// Tx issue: Ubaie=3D55.5V site on Grid The TX fme Lionel Tchatc=
houa/694693436/  of Huawei is informed","MINKA NICOLAS","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE/=
/ Tx issue: Ubaie=3D55.5V site on Grid The TX fme Lionel Tchatchoua/6946934=
36/  of Huawei is informed","alexandre.kamal@ihstowers.com","1626","03-10-2=
024 14:50:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0003229303","B=
ISCUITERIE","","03-10-2024 14:03:45","03-10-2024 13:59:05","03-10-2024 14:0=
8:05","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automatically","Paul BIBOUM","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen start automatically","ko=
uoh.jean@ihstowers.com","281","03-10-2024 14:03:45","Sagemcom CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0003229117","Mvo=
g-Ada_OCM","","03-10-2024 13:47:52","03-10-2024 13:43:09","03-10-2024 14:08=
:46","No space to deploy a mobil DG // grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","No space to deploy a mobil =
DG // grid return","landry.etame@ihstowers.com","369","03-10-2024 13:47:52"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0003228983","Abo=
me","","03-10-2024 13:41:51","03-10-2024 13:32:45","03-10-2024 13:48:45","G=
rid Outage, Site went down because PWC is overload(24Kw,280A)// Load dicrea=
se","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule Overloaded","Grid Outage, Site went down because PWC is overload(24Kw,2=
80A)// Load dicrease","landry.etame@ihstowers.com","547","03-10-2024 13:41:=
51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003228941","S=
tade-Abega","","03-10-2024 13:39:19","03-10-2024 13:37:05","03-10-2024 13:4=
3:29","site went down because gen failed to start due to rectifiers disfonc=
tionning causing by grid bad voltage// grid stabilized","Mba Lazare Herve",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","s=
ite went down because gen failed to start due to rectifiers disfonctionning=
 causing by grid bad voltage// grid stabilized","kouoh.jean@ihstowers.com",=
"135","03-10-2024 13:39:19","Sagemcom CMR"
"Closed Complete","Site Down","T3254","IHS_YND_350","NOCINC0003228673","Mam=
bine","","03-10-2024 13:24:23","03-10-2024 13:15:16","03-10-2024 13:41:21",=
"No power issue on site U=3D50,3v site on grid Team Tchakount=E9 693846869 =
of Telis working on site","Fanda Brice","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D50,3v site on grid Team Tchakount=E9 693846869 of Telis working on site=
","landry.etame@ihstowers.com","548","03-10-2024 13:24:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0003228524","N=
kolfon Cimencam","","03-10-2024 13:08:36","03-10-2024 13:06:28","03-10-2024=
 14:12:43","Site went down due to CB(43A) rectifiers disjuncted due to 1/4 =
rectifier faulty// He rearmed the CB rectifier","Hyemafo Gildas","Equipment=
 Repair","Passive","Rectifier","Rectifier - Circuit Breaker","Site went dow=
n due to CB(43A) rectifiers disjuncted due to 1/4 rectifier faulty// He rea=
rmed the CB rectifier","kouoh.jean@ihstowers.com","129","03-10-2024 13:08:3=
6","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003228406","MBALNGON=
G LYCEE","","03-10-2024 12:58:01","03-10-2024 12:49:39","03-10-2024 14:06:0=
1","Cascaded Incident from TTO3085930","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, Site went down due t=
o  Gen overload(20Kva .300A)// He reduced load","system","502","03-10-2024 =
12:58:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003228407","Afanoya"=
,"","03-10-2024 12:58:01","03-10-2024 12:49:39","03-10-2024 14:06:01","Casc=
aded Incident from TTO3085930","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, Site went down due to  Ge=
n overload(20Kva .300A)// He reduced load","system","502","03-10-2024 12:58=
:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003228405","ELOUMDEM=
 CARRIERE","","03-10-2024 12:58:00","03-10-2024 12:49:39","03-10-2024 14:06=
:01","Cascaded Incident from TTO3085930","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, Site went down due=
 to  Gen overload(20Kva .300A)// He reduced load","system","501","03-10-202=
4 12:58:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003228367","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","03-10-2024 12:52:47","03-10-=
2024 12:49:39","03-10-2024 14:06:01","Grid Outage, Site went down due to  G=
en overload(20Kva .300A)// He reduced load","Hyemafo Gildas","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Overload","Grid Outage, Site went down du=
e to  Gen overload(20Kva .300A)// He reduced load","kouoh.jean@ihstowers.co=
m","189","03-10-2024 12:52:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003228074","C=
rf Cornier","","03-10-2024 12:28:56","03-10-2024 12:05:48","03-10-2024 12:4=
0:41","No power issue on site.Site on Grid with Ubaie=3D54,6V  Lionel tchat=
chou 694693436  of huawei is informed","MINKA NICOLAS","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site.Site on Grid with Ubaie=3D54,6V  Lionel tchatchou 694693436 =
 of huawei is informed","kouoh.jean@ihstowers.com","1389","03-10-2024 12:28=
:56","Sagemcom CMR"
"Closed Complete","Warning","T1553","IHS_YND_108","NOCINC0003227947","RUE F=
OE","","03-10-2024 12:20:02","","","Site was on Gen due to Grid outage, Sit=
e alarming on battery because Gen stopped due to CB Gen disjuncted// He rea=
rmed the CB","Delor Telezing","Warning","Warning","POWER","Warning - Site o=
n Battery","Site was on Gen due to Grid outage, Site alarming on battery be=
cause Gen stopped due to CB Gen disjuncted// He rearmed the CB","nadjia.nja=
ya@ihstowers.com","72","03-10-2024 12:20:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003227687","Nkolo II=
 New","","03-10-2024 12:02:20","03-10-2024 11:35:06","03-10-2024 12:20:54",=
"Cascaded Incident from TTO3084787","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down because insuffic=
ient of rectifier on site//site stabilized(need to added 02 rectifiers)","s=
ystem","1634","03-10-2024 12:02:20","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003227663","Jou=
vence 2000","","03-10-2024 12:01:22","03-10-2024 11:37:13","03-10-2024 13:0=
9:36","Grid Outage, site went down due to Poor battery backup before Gen st=
art// Gen started manually","Delor Telezing","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid Outage, site went down d=
ue to Poor battery backup before Gen start// Gen started manually","landry.=
etame@ihstowers.com","1450","03-10-2024 12:01:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003227530","M=
ANGUIERS CHAPELLE","","03-10-2024 11:54:53","03-10-2024 11:47:43","03-10-20=
24 13:06:14","grid outage,gen stopped with alarm high temp//he added water =
in radiator","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACD=
G - High Engine Temp - Coolant Level Issue","grid outage,gen stopped with a=
larm high temp//he added water in radiator","kouoh.jean@ihstowers.com","431=
","03-10-2024 11:54:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0003227477","F=
ouda-New","","03-10-2024 11:52:59","03-10-2024 11:47:01","03-10-2024 11:50:=
01","Grid Outage, site went down due to Poor battery backup before Gen star=
t// Gen started","Delor Telezing","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid Outage, site went down due to Poor =
battery backup before Gen start// Gen started","kouoh.jean@ihstowers.com","=
359","03-10-2024 11:52:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003227355","M=
imboman-Village","IHS_YND_709","03-10-2024 11:50:32","03-10-2024 11:35:06",=
"03-10-2024 12:20:54","site went down because insufficient of rectifier on =
site//site stabilized(need to added 02 rectifiers)","Mba Lazare Herve","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module","site went down bec=
ause insufficient of rectifier on site//site stabilized(need to added 02 re=
ctifiers)","kouoh.jean@ihstowers.com","927","03-10-2024 11:50:32","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003225724","Nko=
mo stade","","03-10-2024 08:44:38","03-10-2024 08:38:25","03-10-2024 08:58:=
25","Site went down due to 01/03 Rectifier Dysfuntionning //He reset the Re=
ctifier and site is on Grid","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down due to 01/03 Rectifier Dys=
funtionning //He reset the Rectifier and site is on Grid","landry.etame@ihs=
towers.com","374","03-10-2024 08:44:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003225461","E=
mana","","03-10-2024 07:48:35","03-10-2024 07:35:20","03-10-2024 08:07:45",=
"site went down because 2/2 rectifiers disfunctionning//he reset the rectif=
iers","","Equipment Repair","Passive","Rectifier","Rectifier Module","site =
went down because 2/2 rectifiers disfunctionning//he reset the rectifiers",=
"kouoh.jean@ihstowers.com","796","03-10-2024 07:48:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0003225448","N=
R-Omnisport","","03-10-2024 07:44:32","03-10-2024 07:24:25","03-10-2024 08:=
00:20","site went down because gen start and stopped with alarm emergency b=
utton stop//he reset the card and started the gen","Delor Telezing","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Emergency Stop","site went down be=
cause gen start and stopped with alarm emergency button stop//he reset the =
card and started the gen","kouoh.jean@ihstowers.com","1207","03-10-2024 07:=
44:32","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003225426","Ebo=
go","","03-10-2024 07:39:33","03-10-2024 07:35:25","03-10-2024 07:39:25","G=
rid outage, site went down before Gen start due to poor battery backup // G=
en start manually","Siligap Boris","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before Gen =
start due to poor battery backup // Gen start manually","landry.etame@ihsto=
wers.com","249","03-10-2024 07:39:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003225211","Lobo OCM=
","","03-10-2024 06:50:40","03-10-2024 06:44:39","03-10-2024 06:49:12","Cas=
caded Incident from TTO3082379","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage: The site went =
down before Gen started due to poor battery backup. Gen started automatical=
ly.","system","361","03-10-2024 06:50:40","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003225202","N=
KOMEKUI OCM","IHS_YND_341","03-10-2024 06:49:47","03-10-2024 06:44:39","03-=
10-2024 06:49:12","","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage: The site went=
 down before Gen started due to poor battery backup. Gen started automatica=
lly.","kouoh.jean@ihstowers.com","309","03-10-2024 06:49:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003225178","O=
mnisport-Rail","","03-10-2024 06:43:00","03-10-2024 06:40:49","03-10-2024 0=
6:49:49","grid outage,gen failed to start due to battery Ge faulty//he star=
ted the gen with battery backup","Delor Telezing","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Generator Battery","grid outage,gen failed to start =
due to battery Ge faulty//he started the gen with battery backup","kouoh.je=
an@ihstowers.com","132","03-10-2024 06:43:00","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0003224770","Eli=
g Edzoa","","03-10-2024 04:12:55","03-10-2024 03:46:36","03-10-2024 04:25:4=
2","Grid outage, site went down before Gen start due to poor battery backup=
 // Gen start manually","Delor Telezing","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e Gen start due to poor battery backup // Gen start manually","denis.mballa=
@ihstowers.com","1580","03-10-2024 04:12:55","Sagemcom CMR"
"Cancelled","Warning","CTR_038","IHS_YND_052","NOCINC0003224758","NR-Bastos=
","","03-10-2024 04:05:28","","","tikect to need cancel","","","","","","",=
"ange.kongo@ihstowers.com","2060","03-10-2024 04:05:28","Sagemcom CMR"
"Closed Complete","Site Down","T0836","IHS_YND_109","NOCINC0003224624","Mob=
il-Essos","","03-10-2024 03:38:32","03-10-2024 03:31:45","03-10-2024 04:47:=
56","site went downbecause the Cb(32A) of rectifier dysjoncted and 01 recti=
fier faulty// he reamed the Cb","Siligap Boris","Equipment Repair","Passive=
","Rectifier","Rectifier Module","site went downbecause the Cb(32A) of rect=
ifier dysjoncted and 01 rectifier faulty// he reamed the Cb","denis.mballa@=
ihstowers.com","2360","03-10-2024 03:38:32","Sagemcom CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0003224564","RUE=
 FOE","","03-10-2024 03:17:08","03-10-2024 02:53:36","03-10-2024 05:06:56",=
"Grid outage site went down because Gen started and stopped with alarm Gen =
at rest mode stop//  gen manually started","Delor Telezing","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down=
 because Gen started and stopped with alarm Gen at rest mode stop//  gen ma=
nually started","denis.mballa@ihstowers.com","1412","03-10-2024 03:17:08","=
Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003224525","Jou=
vence 2000","","03-10-2024 03:07:18","03-10-2024 01:57:50","03-10-2024 04:0=
1:39","Grid outage, site went down before Gen start due to poor battery bac=
kup // Gen start manually","Delor Telezing","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore Gen start due to poor battery backup // Gen start manually","denis.mba=
lla@ihstowers.com","4169","03-10-2024 03:07:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003224453","Lobo OCM=
","","03-10-2024 02:36:50","03-10-2024 02:29:41","03-10-2024 02:35:23","Cas=
caded Incident from TTO3081538","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before Gen start due to poor battery backup // Gen start automatically","s=
ystem","429","03-10-2024 02:36:50","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003224447","N=
KOMEKUI OCM","IHS_YND_341","03-10-2024 02:36:04","03-10-2024 02:29:41","03-=
10-2024 02:35:23","Grid outage, site went down before Gen start due to poor=
 battery backup // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, site went down before Gen start due to poor battery backup // Gen=
 start automatically","ange.kongo@ihstowers.com","384","03-10-2024 02:36:04=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003224424","E=
lig-Edzoa","","03-10-2024 02:24:53","03-10-2024 02:15:47","03-10-2024 07:25=
:12","grid outage//MDG 20kva deployed","","Grid Supply","Passive","Grid","N=
ational Grid - Grid Outage Issue","grid outage//MDG 20kva deployed","ange.k=
ongo@ihstowers.com","547","03-10-2024 02:24:53","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003223953","Nko=
mo stade","","03-10-2024 00:09:05","03-10-2024 00:07:48","03-10-2024 00:39:=
03","Site went down due to 01/03 Rectifier Dysfuntionning //He reset the Re=
ctifier and site is on Grid","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Module","Site went down due to 01/03 Rectifier Dys=
funtionning //He reset the Rectifier and site is on Grid","denis.mballa@ihs=
towers.com","78","03-10-2024 00:09:05","Sagemcom CMR"
"Closed Complete","Warning","CTR_274","IHS_YND_116","NOCINC0003223941","Sta=
de-Abega","","03-10-2024 00:03:59","","","grid outage, site went down becau=
se gen start and stopped due to grid bad voltage//he did a bridge on good p=
hase","Mba Lazare Herve","Warning","Warning","POWER","Warning - Site on Bat=
tery","grid outage, site went down because gen start and stopped due to gri=
d bad voltage//he did a bridge on good phase","adonis.defokoua@ihstowers.co=
m","3614","03-10-2024 00:03:59","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003222776","Nko=
mo stade","","02-10-2024 20:28:13","02-10-2024 20:22:04","02-10-2024 20:28:=
28","Site went down due to 01/03 Rectifier Dysfuntionning //He reset the Re=
ctifier and site is on Grid","Mba Lazare Herve","Equipment Repair","Passive=
","Rectifier","Rectifier Cabinet","Site went down due to 01/03 Rectifier Dy=
sfuntionning //He reset the Rectifier and site is on Grid","olivier.kwedi@i=
hstowers.com","369","02-10-2024 20:28:13","Sagemcom CMR"
"Cancelled","Warning","T1941","IHS_YND_304","NOCINC0003222551","Nkolondom",=
"","02-10-2024 19:47:33","","","","Fabrice Pouakam","","","","","","olivier=
.kwedi@ihstowers.com","368","02-10-2024 19:47:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003222459","Ngouetou=
","","02-10-2024 19:29:41","02-10-2024 19:21:21","02-10-2024 19:22:21","Cas=
caded Incident from TTO3079187","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","500","02-10-2024 19:29:41","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003222458","Yoko OCM=
","","02-10-2024 19:29:41","02-10-2024 19:21:21","02-10-2024 19:22:21","Cas=
caded Incident from TTO3079187","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","500","02-10-2024 19:29:41","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003222460","MBIMBIM"=
,"","02-10-2024 19:29:41","02-10-2024 19:21:21","02-10-2024 19:22:21","Casc=
aded Incident from TTO3079187","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","500","02-10-2024 19:29:41","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003222457","Matsari"=
,"","02-10-2024 19:29:41","02-10-2024 19:21:21","02-10-2024 19:22:21","Casc=
aded Incident from TTO3079187","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","500","02-10-2024 19:29:41","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003222456","Ngoum","=
","02-10-2024 19:29:40","02-10-2024 19:21:21","02-10-2024 19:22:21","Cascad=
ed Incident from TTO3079187","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","499","02-10-2024 19:29:40","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0003222282","Monatele=
","","02-10-2024 18:54:50","02-10-2024 18:44:45","02-10-2024 18:45:53","Cas=
caded Incident from TTO3078980","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active//No power issue on site ,site on G=
RID with Ubaie=3D54.4V The TX FME Gregoire(654547479) from Huawei is inform=
ed and site Up at=3D06:54 PM","system","605","02-10-2024 18:54:50","Sagemco=
m CMR"
"Closed Complete","Site Down","T0053","IHS_YND_407","NOCINC0003222276","Mon=
atele MTN","IHS_YND_406","02-10-2024 18:53:51","02-10-2024 18:44:45","02-10=
-2024 21:30:53","Active//No power issue on site ,site on GRID with Ubaie=3D=
54.4V The TX FME Gregoire(654547479) from Huawei is informed and site Up at=
=3D06:54 PM","Parker Tchoup","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site ,si=
te on GRID with Ubaie=3D54.4V The TX FME Gregoire(654547479) from Huawei is=
 informed and site Up at=3D06:54 PM","olivier.kwedi@ihstowers.com","547","0=
2-10-2024 18:53:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003222181","C=
rf Cornier","","02-10-2024 18:40:17","02-10-2024 18:39:12","02-10-2024 19:4=
0:04","Active//No power issue on site U=3D54,6V site on Grid TX FME Leonel =
Tchatchou(694693436) of Huawei is informed and Site UP at=3D 06:47 PM","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue on site U=3D54,6V site on Gr=
id TX FME Leonel Tchatchou(694693436) of Huawei is informed and Site UP at=
=3D 06:47 PM","dorothy.djantio@ihstowers.com","66","02-10-2024 18:40:17","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0003222159","C=
hapelle-Essos","","02-10-2024 18:36:32","02-10-2024 18:32:26","02-10-2024 2=
0:35:46","Site went down due to Incorrect tightening of the cable - 48V in =
the DC-BOX//He Normalized hi and Site is on Grid","Delor Telezing","Equipme=
nt Repair","Passive","Control Panel","ATS-AMF Issue","Site went down due to=
 Incorrect tightening of the cable - 48V in the DC-BOX//He Normalized hi an=
d Site is on Grid","dorothy.djantio@ihstowers.com","246","02-10-2024 18:36:=
32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003222155","A=
wae Ewonkan","","02-10-2024 18:35:33","02-10-2024 18:26:23","02-10-2024 19:=
34:54","grid outage,gen failed to start due to grid bad voltage//he bypasse=
d grid and started the gen","Albran Byorel","Grid Supply","Passive","Grid",=
"National Grid - Phase Controller Faulty","grid outage,gen failed to start =
due to grid bad voltage//he bypassed grid and started the gen","dorothy.dja=
ntio@ihstowers.com","550","02-10-2024 18:35:33","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0003221404","Lob=
o 2","","02-10-2024 16:34:24","02-10-2024 16:31:10","02-10-2024 16:33:36","=
Active//No power issue site and  with Ubaie=3D50 V site on Gen The  FME TX =
Mouamadou/658791013 //From  is informed","TIENTCHEU NZETCHIEU GAEL","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue site and  with Ubaie=3D50 V site on Gen The  FM=
E TX Mouamadou/658791013 //From  is informed","olivier.kwedi@ihstowers.com"=
,"195","02-10-2024 16:34:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0003221279","V=
allee-Bastos OCM","","02-10-2024 16:15:10","02-10-2024 16:09:05","02-10-202=
4 17:44:33","Grid outage //MDG 20kva deployed ","","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid outage //MDG 20kva deploye=
d ","dorothy.djantio@ihstowers.com","366","02-10-2024 16:15:10","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003220804","A=
KONGO","","02-10-2024 15:20:15","02-10-2024 15:11:07","02-10-2024 16:21:29"=
,"No power issue on site U=3D50v site on gen Rodrigue of huawei is informed=
","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","No power issue on site U=3D50v site on gen Rodr=
igue of huawei is informed","dorothy.djantio@ihstowers.com","549","02-10-20=
24 15:20:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0003220664","V=
allee-Bastos OCM","","02-10-2024 14:55:01","02-10-2024 14:13:15","02-10-202=
4 15:17:02","Grid outage //MDG 20kva deplotyed ","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage //MDG 20kva deplot=
yed ","dorothy.djantio@ihstowers.com","2507","02-10-2024 14:55:01","Sagemco=
m CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003220606","Eko=
unou","","02-10-2024 14:47:06","02-10-2024 14:42:57","02-10-2024 14:52:47",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re Gen start due to poor battery backup // Gen start automatically","olivie=
r.kwedi@ihstowers.com","250","02-10-2024 14:47:06","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0003220156","Nlo=
ngkak","","02-10-2024 13:36:47","02-10-2024 13:28:29","02-10-2024 13:58:56"=
,"Grid outage,Gen failed to start due to alarm overvoltage//he reduced 01 r=
ectifier and started Gen manualy","Delor Telezing","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage,Gen failed to start due=
 to alarm overvoltage//he reduced 01 rectifier and started Gen manualy","ka=
mga.virgile@ihstowers.com","499","02-10-2024 13:36:47","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003220108","NKO=
MEKUI OCM","","02-10-2024 13:26:22","02-10-2024 13:16:10","02-10-2024 13:28=
:05","Grid Outage, site went down due to Poor battery backup before Gen sta=
rt// Gen started automaticaly","TIENTCHEU NZETCHIEU GAEL","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, sit=
e went down due to Poor battery backup before Gen start// Gen started autom=
aticaly","kamga.virgile@ihstowers.com","613","02-10-2024 13:26:22","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0003219923","H=
-Franco New","","02-10-2024 13:05:47","02-10-2024 12:54:40","02-10-2024 13:=
10:43","Site went down due to  Gen overload(20Kva .350A)//he make the Power=
 rate at 100 % ","Delor Telezing","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Site went down due to  Gen overload(20Kva .350A)//he make=
 the Power rate at 100 % ","alexandre.kamal@ihstowers.com","667","02-10-202=
4 13:05:47","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003219773","Eko=
unou","","02-10-2024 12:40:07","02-10-2024 12:38:44","02-10-2024 12:44:35",=
"Grid Outage, site went down due to Poor battery backup before Gen start// =
Gen started automaticaly","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid Outage, site went down due =
to Poor battery backup before Gen start// Gen started automaticaly","kamga.=
virgile@ihstowers.com","84","02-10-2024 12:40:07","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_191","NOCINC0003219564","Mballa II"=
,"","02-10-2024 12:07:16","","","Site alarming on battery (unprouven alarm)=
//Site on Grid Ubai=3D54.5V","Delor Telezing","Warning","Warning","POWER","=
Warning - Site on Battery","Site alarming on battery (unprouven alarm)//Sit=
e on Grid Ubai=3D54.5V","stephane.nkamwa@ihstowers.com","425","02-10-2024 1=
2:07:16","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_191","NOCINC0003219557","Mballa II","","0=
2-10-2024 12:05:59","","","","Delor Telezing","","","","","","stephane.nkam=
wa@ihstowers.com","6","02-10-2024 12:05:59","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0003219441","UPA=
C LP","","02-10-2024 11:45:47","02-10-2024 11:43:39","02-10-2024 16:37:35",=
"Grid Outage no space to deploy MDG // Grid return","","Grid Supply","Passi=
ve","Grid","National Grid - Grid Outage Issue","Grid Outage no space to dep=
loy MDG // Grid return","stephane.nkamwa@ihstowers.com","129","02-10-2024 1=
1:45:47","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0003218394","Nlo=
ngkak","","02-10-2024 08:21:40","02-10-2024 08:14:24","02-10-2024 09:20:10"=
,"Grid outage,site went down because gen start and stoppen due ""Over frequ=
ency"" alarm // He reduced frequency and started Gen manualy","Delor Telezi=
ng","Equipment Repair","Passive","ACDG Gen","ACDG - Governor","Grid outage,=
site went down because gen start and stoppen due ""Over frequency"" alarm /=
/ He reduced frequency and started Gen manualy","kamga.virgile@ihstowers.co=
m","437","02-10-2024 08:21:40","Sagemcom CMR"
"Closed Complete","Warning","T0543","IHS_YND_135","NOCINC0003218359","Nlong=
kak","","02-10-2024 08:13:51","","","Grid outage,site alarming on battery b=
ecause gen start and stoppen due ""Over fequency"" alarm // He reduced freq=
uency","Delor Telezing","Warning","Warning","POWER","Warning - Site on Batt=
ery","Grid outage,site alarming on battery because gen start and stoppen du=
e ""Over fequency"" alarm // He reduced frequency","stephane.nkamwa@ihstowe=
rs.com","189","02-10-2024 08:13:51","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003217778","Ako=
no","IHS_YND_687","02-10-2024 05:31:09","02-10-2024 05:29:05","02-10-2024 0=
5:59:02","Grid Fluctuation site went down because Gen failed to start due t=
o Gen card disfunction causing by Grid multiple fluctuation// He started Ge=
n manualy","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid Fluctuation site went down because Gen failed to start d=
ue to Gen card disfunction causing by Grid multiple fluctuation// He starte=
d Gen manualy","joelle.ekessi@ihstowers.com","124","02-10-2024 05:31:09","S=
agemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003217774","OLA=
MA","","02-10-2024 05:28:21","02-10-2024 05:29:05","02-10-2024 05:59:02",""=
,"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passiv=
e","Grid Fluctuation site went down because Gen failed to start due to Gen =
card disfunction causing by Grid multiple fluctuation// He started Gen manu=
aly","joelle.ekessi@ihstowers.com","466","02-10-2024 05:28:21","Sagemcom CM=
R"
"Closed Complete","Site Down","T0843","IHS_YND_719","NOCINC0003217546","TSI=
NGA VILLAGE 2","","02-10-2024 03:36:28","02-10-2024 03:30:19","02-10-2024 0=
4:32:31","Site went because Gen failed to start due to hybrid system malfun=
ction / /He reset Gen card and started Gen","Delor Telezing","Equipment Rep=
air","Passive","Hybrid","Hybrid Module","Site went because Gen failed to st=
art due to hybrid system malfunction / /He reset Gen card and started Gen",=
"joelle.ekessi@ihstowers.com","488","02-10-2024 03:36:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003217135","Dong",""=
,"02-10-2024 01:06:11","02-10-2024 00:50:49","02-10-2024 01:05:05","Cascade=
d Incident from TTO3073153","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power issue, 55v On Grid. Site impacted by=
 Mbandjock_CTR_030 not managed by IHS","system","922","02-10-2024 01:06:11"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003217134","Donga","=
","02-10-2024 01:06:10","02-10-2024 00:50:49","02-10-2024 01:05:05","Cascad=
ed Incident from TTO3073153","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue, 55v On Grid. Site impacted b=
y Mbandjock_CTR_030 not managed by IHS","system","921","02-10-2024 01:06:10=
","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0003217117","Nko=
zoa","","02-10-2024 01:04:19","02-10-2024 01:00:13","02-10-2024 01:19:01","=
Grid fluctuation ,Site went down because Gen started and stopped due to Gen=
 overload(20KVA;320 A)//He reduced the load on site ","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid fluctuation ,S=
ite went down because Gen started and stopped due to Gen overload(20KVA;320=
 A)//He reduced the load on site ","joelle.ekessi@ihstowers.com","247","02-=
10-2024 01:04:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0003217066","Nkolfon =
Cimencam","","02-10-2024 00:48:20","02-10-2024 00:33:43","02-10-2024 00:40:=
18","Cascaded Incident from TTO3073080","Hyemafo Gildas","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site,site on G=
rid with Ubaie=3D55 V The Tx fme Tchatchou Leonnel  (694693436) of HUAWEI i=
s informed.","system","877","02-10-2024 00:48:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003217054","S=
oa-II","","02-10-2024 00:44:16","02-10-2024 00:33:43","02-10-2024 04:40:18"=
,"No power issue on site,site on Grid with Ubaie=3D55 V The Tx fme Tchatcho=
u Leonnel  (694693436) of HUAWEI is informed.","Siligap Boris","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue on site,sit=
e on Grid with Ubaie=3D55 V The Tx fme Tchatchou Leonnel  (694693436) of HU=
AWEI is informed.","emmanuel.ghani@ihstowers.com","3370","02-10-2024 00:44:=
16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0003217052","A=
fanoya","","02-10-2024 00:43:06","02-10-2024 00:33:43","02-10-2024 02:40:18=
","No power issue on site,site on Grid with Ubaie=3D55 V The Tx fme Tchatch=
ou Leonnel  (694693436) of HUAWEI is informed.","Hyemafo Gildas","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue on site,s=
ite on Grid with Ubaie=3D55 V The Tx fme Tchatchou Leonnel  (694693436) of =
HUAWEI is informed.","emmanuel.ghani@ihstowers.com","3340","02-10-2024 00:4=
3:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0003217037","M=
eyo","IHS_YND_313, IHS_YND_316, IHS_YND_762, IHS_YND_324, IHS_YND_322","02-=
10-2024 00:37:49","02-10-2024 00:33:43","02-10-2024 02:20:23","No power iss=
ue on site,site on Grid with Ubaie=3D55 V The Tx fme Tchatchou Leonnel  (69=
4693436) of HUAWEI is informed.","Hyemafo Gildas","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e on site,site on Grid with Ubaie=3D55 V The Tx fme Tchatchou Leonnel  (694=
693436) of HUAWEI is informed.","emmanuel.ghani@ihstowers.com","247","02-10=
-2024 00:37:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003217026","Akak-Nko=
zoa-MTN-IHS","","02-10-2024 00:32:40","02-10-2024 00:33:43","02-10-2024 02:=
20:18","No power issue on site,site on Grid with Ubaie=3D55 V The Tx fme Tc=
hatchou Leonnel  (694693436) of HUAWEI is informed.","Fabrice Pouakam","Cas=
cade Outage","Active","Cascade Active","Cascade Active","No power issue on =
site,site on Grid with Ubaie=3D55 V The Tx fme Tchatchou Leonnel  (69469343=
6) of HUAWEI is informed.","system","3482","02-10-2024 00:32:40","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003216989","S=
ous Prefecture","","02-10-2024 00:18:22","02-10-2024 00:14:15","02-10-2024 =
01:29:38","Active//No power isssue, site is on grid with Ubaie=3D54,9V, Rm =
alain (691 14 44 23) from Huawei is informed.","Fanda Brice","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power isssue, site is on grid with Ubaie=3D54,9V, Rm alain (691 14=
 44 23) from Huawei is informed.Site up  at 12:18 AM","emmanuel.ghani@ihsto=
wers.com","248","02-10-2024 00:18:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_731","NOCINC0003216939","UPAC LP"=
,"","02-10-2024 00:02:30","01-10-2024 23:59:59","02-10-2024 00:15:56","Casc=
aded Incident from TTO3072961","","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Grid  bad voltage, site went down because Gen failed=
 to start due to Grid bad voltage and No RCP on site//he bypassed Grid and =
Started Gen","system","151","02-10-2024 00:02:30","Sagemcom CMR"
"Closed Complete","Site Down","T2104","IHS_YND_711","NOCINC0003216934","H-F=
ranco New","IHS_YND_731","02-10-2024 00:01:05","01-10-2024 23:59:59","02-10=
-2024 00:17:47","Grid  bad voltage, site went down because Gen failed to st=
art due to Grid bad voltage and No RCP on site//he bypassed Grid and Starte=
d Gen","Delor Telezing","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Grid  bad voltage, site went down because Gen failed=
 to start due to Grid bad voltage and No RCP on site//he bypassed Grid and =
Started Gen","joelle.ekessi@ihstowers.com","67","02-10-2024 00:01:05","Sage=
mcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003216796","Evo=
doula MTN","","01-10-2024 23:13:21","01-10-2024 23:07:17","02-10-2024 01:44=
:00","Grid outage site went down because Gen started and stopped with alarm=
  ""over voltage""// he reset the Gen card and started Gen","TIENTCHEU NZET=
CHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","=
Grid outage site went down because Gen started and stopped with alarm  ""ov=
er voltage""// he reset the Gen card and started Gen","joelle.ekessi@ihstow=
ers.com","365","01-10-2024 23:13:21","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003216584","Jou=
vence 2000","","01-10-2024 22:28:38","01-10-2024 22:26:34","01-10-2024 22:4=
1:07","Grid Outage Site went down because Gen start due to Poor Backup//Gri=
d Restored","Delor Telezing","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid Outage Site went down because Gen start =
due to Poor Backup//Grid Restored","joelle.ekessi@ihstowers.com","125","01-=
10-2024 22:28:38","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003216182","Nko=
mo stade","","01-10-2024 21:36:55","01-10-2024 21:22:41","01-10-2024 23:18:=
50","Site wen down because 01/03 rectifier  hanging//he reset rectifier ,Si=
te  on Grid","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site wen down because 01/03 rectifier  hanging//he reset =
rectifier ,Site  on Grid","denis.mballa@ihstowers.com","855","01-10-2024 21=
:36:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003216147","M=
IMBOMAN LIBERTE","","01-10-2024 21:30:40","01-10-2024 21:21:59","01-10-2024=
 21:53:28","Grid outage site went downbecause  main Gen faulty// Grid power=
 return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Generator Faulty","Grid outage site went downbecause  main Gen faulty// Gr=
id power return","ange.kongo@ihstowers.com","521","01-10-2024 21:30:40","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0003216001","S=
OA 2","","01-10-2024 21:17:33","01-10-2024 21:09:26","01-10-2024 22:22:34",=
"Site went down because  CB OCM  (2*125 A) disjunted in PWC //he reamed CB"=
,"Siligap Boris","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Circuit Breaker Issue","Site went down because  CB OCM  (2*125 A) disju=
nted in PWC //he reamed CB","ange.kongo@ihstowers.com","487","01-10-2024 21=
:17:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0003215991","B=
ONAS YDE","","01-10-2024 21:16:26","01-10-2024 21:02:21","02-10-2024 03:20:=
43","No power issue on site,site on Grid with Ubaie=3D56,2  V The TX FME Mb=
ah Hosiah (674007438)  from Huawei is informed.","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power issue on site,site on Grid with Ubaie=3D56,2  V The TX FME Mbah Ho=
siah (674007438)  from Huawei is informed.","ange.kongo@ihstowers.com","846=
","01-10-2024 21:16:26","Sagemcom CMR"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0003215960","Nko=
ngtock","","01-10-2024 21:10:51","01-10-2024 21:02:39","01-10-2024 23:10:39=
","Active// No power issue on site ,site on Gen with Ubaie=3D 54,1V The fme=
 tx Etienne fopa // 695033981 of huawei is informed and Site UP at =3D09.40=
 PM","Kemeni Franklin","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Active// No power issue on site ,site on=
 Gen with Ubaie=3D 54,1V The fme tx Etienne fopa // 695033981 of huawei is =
informed and Site UP at =3D09.40 PM","denis.mballa@ihstowers.com","493","01=
-10-2024 21:10:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003215873","S=
ous Prefecture","","01-10-2024 20:57:09","01-10-2024 20:54:07","01-10-2024 =
20:57:11","Active//No power isssue, site is on grid with Ubaie=3D54,9V, Rm =
alain (691 14 44 23) from Huawei is informed","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power isssue, site is on grid with Ubaie=3D54,9V, Rm alain (691 14 =
44 23) from Huawei is informed","ange.kongo@ihstowers.com","182","01-10-202=
4 20:57:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003215359","M=
imboman-Village","IHS_YND_709","01-10-2024 20:07:49","01-10-2024 19:59:27",=
"01-10-2024 20:05:04","Site went down due to insufficient of rectifier (01/=
03) and poor backup//Site stabilized","Mba Lazare Herve","Equipment Repair"=
,"Passive","Rectifier","Rectifier Module","Site went down due to insufficie=
nt of rectifier (01/03) and poor backup//Site stabilized","ange.kongo@ihsto=
wers.com","579","01-10-2024 20:07:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003215311","N=
kolo II New","","01-10-2024 20:02:56","01-10-2024 19:59:27","01-10-2024 20:=
54:04","imapcted by IHS_YND_267:Mimboman-Village // TTO3071151","Mba Lazare=
 Herve","Cascade Outage","Passive","Cascade Passive","Cascade Passive","ima=
pcted by IHS_YND_267:Mimboman-Village","ange.kongo@ihstowers.com","210","01=
-10-2024 20:02:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0003214043","S=
AA 2","","01-10-2024 16:33:09","01-10-2024 16:21:03","01-10-2024 18:14:54",=
"Active//No power issue on site ,site on GRID with Ubaie=3D53.8V The TX FME=
 Gregoire(654547479) from Huawei is informed.","Parker Tchoup","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site ,site on GRID with Ubaie=3D53.8V The TX FME =
Gregoire(654547479) from Huawei is informed.","ange.kongo@ihstowers.com","7=
27","01-10-2024 16:33:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003213926","Crf Corn=
ier","","01-10-2024 16:15:20","01-10-2024 16:09:49","01-10-2024 16:16:41","=
Cascaded Incident from TTO3069457","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage //Grid Restored","syste=
m","331","01-10-2024 16:15:20","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0003213924","Eli=
g Edzoa","","01-10-2024 16:15:06","01-10-2024 16:09:04","01-10-2024 17:07:5=
9","site went down because 02/03 rectifier dysfonction // He reset the rect=
ifier","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","site went down because 02/03 rectifier dysfonction // He reset th=
e rectifier","denis.mballa@ihstowers.com","491","01-10-2024 16:15:06","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003213909","M=
adison","IHS_YND_566","01-10-2024 16:13:09","01-10-2024 16:09:49","01-10-20=
24 16:16:41","Grid Outage //Grid Restored","MFOUAGUEGUE MATHIEU","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage //Gri=
d Restored","ange.kongo@ihstowers.com","201","01-10-2024 16:13:09","Sagemco=
m CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003213908","Ess=
os Marche","","01-10-2024 16:13:06","01-10-2024 16:10:27","01-10-2024 16:16=
:14","Grid outage, site went down before gen start due to poor battery back=
up // gen start automatically","Delor Telezing","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // gen start automatically","=
denis.mballa@ihstowers.com","160","01-10-2024 16:13:06","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0003213853","Mes=
sassi Carrefourt","","01-10-2024 16:06:13","01-10-2024 16:02:01","01-10-202=
4 18:22:11","Active// No power issue on site ,site on Gen  with Ubaie=3D 54=
,5V The Rm Martial // 690087047 of huawei is informed","Delor Telezing","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active// No power issue on site ,site on Gen  with Ubaie=3D 54,5V =
The Rm Martial // 690087047 of huawei is informed","denis.mballa@ihstowers.=
com","253","01-10-2024 16:06:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003213693","O=
lembe-Terminus","","01-10-2024 15:30:02","01-10-2024 12:45:46","01-10-2024 =
12:50:19","Active//No power issue site on Grid , with U=3D51,5 V The Tx Fme=
 symphorien //691316854 is informed","Fabrice Pouakam","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue site on Grid , with U=3D51,5 V The Tx Fme symphorien //69131=
6854 is informed","ange.kongo@ihstowers.com","9857","01-10-2024 15:30:02","=
Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003213681","Lad=
a I Yde","","01-10-2024 15:27:49","01-10-2024 15:18:35","01-10-2024 16:06:0=
3","site went down due to work  FME H=E9rv=E9 Lazare /677548918/SAGEMCOM/ d=
oing  PM works//End of work","Mba Lazare Herve","Equipment Replacement","Pa=
ssive","Planned Activity","Planned Activity - Passive","site went down due =
to work  FME H=E9rv=E9 Lazare /677548918/SAGEMCOM/ doing  PM works//End of =
work","denis.mballa@ihstowers.com","554","01-10-2024 15:27:49","Sagemcom CM=
R"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0003212991","Nta=
ba","","01-10-2024 13:56:17","01-10-2024 13:52:09","01-10-2024 13:58:04","G=
rid Outage Site went down because Gen start due to Poor Backup//Gen automat=
ically started","Delor Telezing","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid Outage Site went down because Gen st=
art due to Poor Backup//Gen automatically started","olivier.kwedi@ihstowers=
.com","249","01-10-2024 13:56:17","Sagemcom CMR"
"Closed Complete","Site Down","T1832","IHS_YND_216","NOCINC0003212979","Ele=
veur","","01-10-2024 13:54:17","01-10-2024 13:52:07","01-10-2024 13:58:07",=
"Grid Outage site went down due to controller Huawei dysfonctioning//Grid p=
ower return","Siligap Boris","Equipment Repair","Passive","Control Panel","=
ATS-AMF Issue","Grid Outage site went down due to controller Huawei dysfonc=
tioning//Grid power return","olivier.kwedi@ihstowers.com","131","01-10-2024=
 13:54:17","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003212965","Jou=
vence 2000","","01-10-2024 13:52:59","01-10-2024 13:44:49","01-10-2024 14:4=
8:23","Grid Outage Site went down because Gen start due to Poor Backup//Gen=
 Manually started","Delor Telezing","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid Outage Site went down because Gen=
 start due to Poor Backup//Gen Manually started","olivier.kwedi@ihstowers.c=
om","491","01-10-2024 13:52:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0003212666","N=
kolkoumou OCM","","01-10-2024 13:12:39","01-10-2024 13:04:35","01-10-2024 1=
3:06:43","Active//No power issue, site is on Grid with Ubaie=3D54,1V, the f=
me tx Mbah Mouhamadou (691144435) from Huawei is working on Site,","TIENTCH=
EU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active//No power issue, site is on Grid with=
 Ubaie=3D54,1V, the fme tx Mbah Mouhamadou (691144435) from Huawei is worki=
ng on Site,","dorothy.djantio@ihstowers.com","485","01-10-2024 13:12:39","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0003212006","N=
goum","","01-10-2024 11:48:27","01-10-2024 11:36:22","01-10-2024 12:07:22",=
"No power issue site on Solar with U=3D51V,  tx fme Gregoire (654547479) fr=
om Huawei informed","Parker Tchoup","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on Sola=
r with U=3D51V,  tx fme Gregoire (654547479) from Huawei informed","dorothy=
.djantio@ihstowers.com","726","01-10-2024 11:48:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003211805","Mamb",""=
,"01-10-2024 11:24:34","01-10-2024 11:04:59","01-10-2024 11:27:16","Cascade=
d Incident from TTO3067082","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid Outage Site went down because Gen s=
topped due to air conditioning load increase//he balanced the Load","system=
","1175","01-10-2024 11:24:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0003211806","Boga-Mah=
ole","","01-10-2024 11:24:34","01-10-2024 11:04:59","01-10-2024 11:27:16","=
Cascaded Incident from TTO3067082","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage Site went down becaus=
e Gen stopped due to air conditioning load increase//he balanced the Load",=
"system","1175","01-10-2024 11:24:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0003211801","Eseka OC=
M","","01-10-2024 11:24:33","01-10-2024 11:04:59","01-10-2024 11:27:16","Ca=
scaded Incident from TTO3067082","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage Site went down because =
Gen stopped due to air conditioning load increase//he balanced the Load","s=
ystem","1174","01-10-2024 11:24:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003211803","Song-bon=
g","","01-10-2024 11:24:33","01-10-2024 11:04:59","01-10-2024 11:27:16","Ca=
scaded Incident from TTO3067082","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage Site went down because =
Gen stopped due to air conditioning load increase//he balanced the Load","s=
ystem","1174","01-10-2024 11:24:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003211797","Boumnyeb=
el","","01-10-2024 11:24:32","01-10-2024 11:04:59","01-10-2024 11:27:16","C=
ascaded Incident from TTO3067082","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage Site went down because=
 Gen stopped due to air conditioning load increase//he balanced the Load","=
system","1173","01-10-2024 11:24:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003211796","Ngog Map=
ubi","","01-10-2024 11:24:32","01-10-2024 11:04:59","01-10-2024 11:27:16","=
Cascaded Incident from TTO3067082","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage Site went down becaus=
e Gen stopped due to air conditioning load increase//he balanced the Load",=
"system","1173","01-10-2024 11:24:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003211792","Eseka To=
wn","","01-10-2024 11:24:31","01-10-2024 11:04:59","01-10-2024 11:27:16","C=
ascaded Incident from TTO3067082","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage Site went down because=
 Gen stopped due to air conditioning load increase//he balanced the Load","=
system","1172","01-10-2024 11:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0003211791","Boumnyeb=
el OCM","","01-10-2024 11:24:31","01-10-2024 11:04:59","01-10-2024 11:27:16=
","Cascaded Incident from TTO3067082","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage Site went down bec=
ause Gen stopped due to air conditioning load increase//he balanced the Loa=
d","system","1172","01-10-2024 11:24:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003211793","Ndogbess=
ol","","01-10-2024 11:24:31","01-10-2024 11:04:59","01-10-2024 11:27:16","C=
ascaded Incident from TTO3067082","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage Site went down because=
 Gen stopped due to air conditioning load increase//he balanced the Load","=
system","1172","01-10-2024 11:24:31","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003211735","Pha=
rmacie SION","","01-10-2024 11:15:51","01-10-2024 11:12:44","01-10-2024 11:=
22:44","Grid outage,site went down before DG start : Poor Batteries backup =
// DG started automatically.","Paul BIBOUM","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage,site went down bef=
ore DG start : Poor Batteries backup // DG started automatically.","olivier=
.kwedi@ihstowers.com","188","01-10-2024 11:15:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_744","NOCINC0003211681","Eleveur =
Meec Bon Berger","","01-10-2024 11:05:30","01-10-2024 10:54:36","01-10-2024=
 11:00:01","Cascaded Incident from TTO3067004","Siligap Boris","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","grid outage,gen failed =
to start due to PSC3 disfunctionning//grid return","system","654","01-10-20=
24 11:05:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0003211553","E=
leveur","IHS_YND_744","01-10-2024 10:39:30","01-10-2024 10:35:25","01-10-20=
24 11:00:01","grid outage,gen failed to start due to controller  PSC3 disfu=
nctionning//grid return","Siligap Boris","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","grid outage,gen failed to start due to contro=
ller  PSC3 disfunctionning//grid return","dorothy.djantio@ihstowers.com","2=
46","01-10-2024 10:39:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003211549","M=
imboman-Village","","01-10-2024 10:38:24","01-10-2024 10:35:18","01-10-2024=
 12:41:30","issufisance of rectifier ","Mba Lazare Herve","Equipment Repair=
","Passive","Rectifier","Rectifier Module","issufisance of rectifier ","dor=
othy.djantio@ihstowers.com","187","01-10-2024 10:38:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0003211235","Y=
ona Hotel","","01-10-2024 09:35:19","01-10-2024 09:30:14","01-10-2024 10:36=
:05","site went down due to 5/7rectifiers disfunctionning//he reset the rec=
tifiers","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rectifier=
","Rectifier Module","site went down due to 5/7rectifiers disfunctionning//=
he reset the rectifiers","dorothy.djantio@ihstowers.com","306","01-10-2024 =
09:35:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0003211096","E=
toug ebe Meweulo","","01-10-2024 09:08:58","01-10-2024 09:06:52","01-10-202=
4 10:00:52","Grid fluction, site went down because gen start and stopped du=
e to grid bad voltage // he bypass grid and manually start the gen","Hyemaf=
o Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid fluction, site went down because gen start and stopped due to=
 grid bad voltage // he bypass grid and manually start the gen","dorothy.dj=
antio@ihstowers.com","127","01-10-2024 09:08:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003210677","M=
elen Ba'aba","","01-10-2024 07:40:57","01-10-2024 07:33:51","01-10-2024 07:=
45:51","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // he bypass grid and manually start the gen","Siligap =
Boris","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage // he bypass grid and manually start the gen","dorothy.dj=
antio@ihstowers.com","427","01-10-2024 07:40:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003210616","E=
ssomba","","01-10-2024 07:26:30","01-10-2024 07:24:24","01-10-2024 07:26:24=
","Site Access issue due to landloard, Grid outage, gen fails to start // g=
rid return","Mba Lazare Herve","Access Denial","Lease Or Legal","Landlord R=
elated Issues","Access Issue - Land Lord","Site Access issue due to landloa=
rd, Grid outage, gen fails to start // grid return","dorothy.djantio@ihstow=
ers.com","127","01-10-2024 07:26:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003210485","M=
elen Ba'aba","","01-10-2024 07:00:30","01-10-2024 06:54:24","01-10-2024 07:=
14:24","Grid outage, site went down before gen start due to poor battery ba=
ckup // gen start automatically","Siligap Boris","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // gen start automatically",=
"dorothy.djantio@ihstowers.com","367","01-10-2024 07:00:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0003210063","Mom","",=
"01-10-2024 04:46:30","01-10-2024 04:42:09","01-10-2024 07:04:02","Cascaded=
 Incident from TTO3065155","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","site went down because gen failed to start du=
e to hybrid system disfunctionning//Gen manually started","system","261","0=
1-10-2024 04:46:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0003210061","Bondjock=
","","01-10-2024 04:44:31","01-10-2024 04:38:09","01-10-2024 07:04:17","Cas=
caded Incident from TTO3065143","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site went down because gen failed to sta=
rt due to hybrid system disfunctionning//Gen manually started","system","38=
2","01-10-2024 04:44:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0003210059","Mbeng","=
","01-10-2024 04:44:30","01-10-2024 04:38:09","01-10-2024 07:04:17","Cascad=
ed Incident from TTO3065143","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down because gen failed to start =
due to hybrid system disfunctionning//Gen manually started","system","381",=
"01-10-2024 04:44:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_186","IHS_YND_371","NOCINC0003210051","M=
inka","IHS_YND_369, IHS_YND_553, IHS_YND_370, IHS_YND_372","01-10-2024 04:4=
3:20","01-10-2024 04:38:09","01-10-2024 07:04:17","site went down because g=
en failed to start due to hybrid system disfunctionning//Gen manually start=
ed","Fanda Brice","Equipment Repair","Passive","Hybrid","Hybrid Module","si=
te went down because gen failed to start due to hybrid system disfunctionni=
ng//Gen manually started","kouoh.jean@ihstowers.com","312","01-10-2024 04:4=
3:20","Sagemcom CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0003209829","Eki=
e sud","","01-10-2024 03:05:05","01-10-2024 02:52:56","01-10-2024 06:10:18"=
,"Grid outage, gen failed to start due to ATS disfunctionning // Gen manual=
ly start","Albran Byorel","Equipment Repair","Passive","Control Panel","ATS=
-AMF Issue","Grid outage, gen failed to start due to ATS disfunctionning //=
 Gen manually start","landry.etame@ihstowers.com","729","01-10-2024 03:05:0=
5","Sagemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0003209293","OTE=
LE MTN","","01-10-2024 00:10:29","01-10-2024 00:06:36","01-10-2024 01:27:28=
","Grid outage, site went down due to no automatism on site /// Gen manuall=
y start","Fanda Brice","Equipment Repair","Passive","Control Panel","ATS-AM=
F Issue","Grid outage, site went down due to no automatism on site /// Gen =
manually start","landry.etame@ihstowers.com","234","01-10-2024 00:10:29","S=
agemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0003208923","Ole=
mbe","","30-09-2024 22:14:05","30-09-2024 22:04:00","30-09-2024 22:28:47","=
grid outage, site went down because gen start and stoppen with alarm over c=
urrent // He reset gen card and gen manually started","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage, s=
ite went down because gen start and stoppen with alarm over current // He r=
eset gen card and gen manually started","joelle.ekessi@ihstowers.com","1009=
","30-09-2024 22:14:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003208651","T=
amtam Weekend","","30-09-2024 21:13:09","30-09-2024 21:09:31","30-09-2024 2=
2:10:16","Active: no power issue, site is on grid with Ubaie=3D54,4V, the f=
me tx Mbah Hosiah(699699694) from Huawei is informed, repetitif issue","Hye=
mafo Gildas","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active: no power issue, site is on grid with Ubaie=
=3D54,4V, the fme tx Mbah Hosiah(699699694) from Huawei is informed, repeti=
tif issue","emmanuel.ghani@ihstowers.com","219","30-09-2024 21:13:09","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0003208648","Y=
ona Hotel","","30-09-2024 21:12:28","30-09-2024 21:10:23","30-09-2024 22:59=
:49","site went down because gen failed to start due to grid bad voltage// =
Gen manually started","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","site went down because gen =
failed to start due to grid bad voltage// Gen manually started","emmanuel.g=
hani@ihstowers.com","126","30-09-2024 21:12:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0003208237","NTUI TOW=
N","","30-09-2024 19:57:45","30-09-2024 19:48:37","30-09-2024 20:56:58","No=
 power issue on site ,site on Gen with Ubaie=3D54.3V, Tx Fme Gregoire( 6520=
70658)From Huawei is informed","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site ,site on Gen with Ubaie=3D54.3V, Tx Fme Gregoire( 652070658)From Hua=
wei is informed","joelle.ekessi@ihstowers.com","549","30-09-2024 19:57:45",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_035","NOCINC0003207456","Bastos A=
mb Coree","","30-09-2024 19:25:18","30-09-2024 19:23:11","30-09-2024 19:30:=
28","Grid outage no space to deployed// Grid power return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space=
 to deployed// Grid power return","joelle.ekessi@ihstowers.com","128","30-0=
9-2024 19:25:18","Sagemcom CMR"
"Closed Complete","Site Down","T0818","IHS_YND_122","NOCINC0003206949","Emo=
mbo Esssomba","","30-09-2024 18:12:53","30-09-2024 18:10:49","30-09-2024 20=
:29:52","site went down due to work(Herv=E9 Lazard(657108482)/Sagemcom work=
ing on site (swap of PWC)//End of work","Mba Lazare Herve","Equipment Repla=
cement","Passive","Planned Activity","Planned Activity - Passive","site wen=
t down due to work(Herv=E9 Lazard(657108482)/Sagemcom working on site (swap=
 of PWC)//End of work","joelle.ekessi@ihstowers.com","125","30-09-2024 18:1=
2:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0003206721","Ngoulmek=
ong-Nord","","30-09-2024 17:36:28","30-09-2024 17:25:23","30-09-2024 17:34:=
58","Cascaded Incident from TTO3061210","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage site went down due=
 to controller Huawei dysfonctioning//Grid power returnGrid Outage site wen=
t down due to controller Huawei dysfonctioning//Grid power return","system"=
,"665","30-09-2024 17:36:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0003206719","FOUGEROL=
E","","30-09-2024 17:36:25","30-09-2024 17:25:32","30-09-2024 17:38:47","Ca=
scaded Incident from TTO3061184","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuation, site went down beca=
use  Gen failed to start due to poor battery backup // Grid Power return","=
system","653","30-09-2024 17:36:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003206713","MEHANDAN=
","","30-09-2024 17:35:50","30-09-2024 17:15:57","30-09-2024 17:34:56","Cas=
caded Incident from TTO3061127","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because  G=
en failed to start due to poor battery backup // Grid Power return","system=
","1193","30-09-2024 17:35:50","Sagemcom CMR"
"Closed Complete","Site Down","T2585","IHS_YND_744","NOCINC0003206697","Ele=
veur Meec Bon Berger","","30-09-2024 17:35:12","30-09-2024 17:26:08","30-09=
-2024 17:32:23","Grid Fluctuation, site went down because  Gen failed to st=
art due to poor battery backup // Grid Power return","Siligap Boris","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
Fluctuation, site went down because  Gen failed to start due to poor batter=
y backup // Grid Power return","joelle.ekessi@ihstowers.com","545","30-09-2=
024 17:35:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0003206664","E=
leveur","IHS_YND_277","30-09-2024 17:31:28","30-09-2024 17:25:23","30-09-20=
24 17:34:58","Grid Outage site went down due to controller Huawei dysfoncti=
oning//Grid power return","Siligap Boris","Equipment Repair","Passive","Con=
trol Panel","ATS-AMF Issue","Grid Outage site went down due to controller H=
uawei dysfonctioning//Grid power return","emmanuel.ghani@ihstowers.com","36=
6","30-09-2024 17:31:28","Sagemcom CMR"
"Closed Complete","Site Down","T1625","IHS_YND_204","NOCINC0003206653","TON=
GOLO SNEC","","30-09-2024 17:30:17","30-09-2024 17:25:13","30-09-2024 17:37=
:15","Grid outage, site went down because  Gen failed to start due to poor =
battery backup // Grid Power return","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down because  Gen failed to start due to poor battery backup // Grid Po=
wer return","joelle.ekessi@ihstowers.com","305","30-09-2024 17:30:17","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0003206645","N=
gousso-Savana","IHS_YND_561","30-09-2024 17:29:37","30-09-2024 17:25:32","3=
0-09-2024 17:39:17","Grid fluctuation, site went down because  Gen failed t=
o start due to poor battery backup // Grid Power return","Siligap Boris","E=
quipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","G=
rid fluctuation, site went down because  Gen failed to start due to poor ba=
ttery backup // Grid Power return","emmanuel.ghani@ihstowers.com","245","30=
-09-2024 17:29:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003206600","O=
dza II OCM","IHS_YND_528","30-09-2024 17:21:01","30-09-2024 17:15:57","30-0=
9-2024 17:34:56","Grid outage, site went down because  Gen failed to start =
due to poor battery backup // Grid Power return","Albran Byorel","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge, site went down because  Gen failed to start due to poor battery backup =
// Grid Power return","emmanuel.ghani@ihstowers.com","305","30-09-2024 17:2=
1:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003206565","E=
mana","","30-09-2024 17:14:56","30-09-2024 17:06:47","30-09-2024 17:19:02",=
"Grid outage// Grid power return","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid outage// Grid power return","emmanuel.gh=
ani@ihstowers.com","490","30-09-2024 17:14:56","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0003206555","Av =
Kennedy","","30-09-2024 17:13:33","30-09-2024 17:10:30","30-09-2024 17:20:1=
2","Grid outage no space to deploy // Grid power return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space t=
o deploy // Grid power return","joelle.ekessi@ihstowers.com","184","30-09-2=
024 17:13:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003206396","Lobo OCM=
","","30-09-2024 16:59:32","30-09-2024 16:53:33","30-09-2024 16:58:33","Cas=
caded Incident from TTO3060911","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage  site down due =
to poor backup before gen start // Gen automtically started","system","359"=
,"30-09-2024 16:59:32","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003206390","N=
KOMEKUI OCM","IHS_YND_341","30-09-2024 16:58:38","30-09-2024 16:53:33","30-=
09-2024 16:58:33","Grid outage  site down due to poor backup before gen sta=
rt // Gen automtically started","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage  si=
te down due to poor backup before gen start // Gen automtically started","e=
mmanuel.ghani@ihstowers.com","306","30-09-2024 16:58:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0003206282","Mvog-Eba=
nda","","30-09-2024 16:41:03","30-09-2024 16:35:19","30-09-2024 16:50:13","=
Cascaded Incident from TTO3060631","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage  site down due to poor =
backup before gen start // Grid power return","system","344","30-09-2024 16=
:41:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003206251","Etoudi 2=
","","30-09-2024 16:40:17","30-09-2024 16:31:32","30-09-2024 17:39:23","Cas=
caded Incident from TTO3060599","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Gen stopped site went down because t=
he Grid contactor Faulty  // he bypass the Grid contactor and site on Grid"=
,"system","525","30-09-2024 16:40:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003206250","ETOUDI C=
HAPELLE","","30-09-2024 16:40:17","30-09-2024 16:31:32","30-09-2024 17:39:2=
3","Cascaded Incident from TTO3060599","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Gen stopped site went down bec=
ause the Grid contactor Faulty  // he bypass the Grid contactor and site on=
 Grid","system","525","30-09-2024 16:40:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003206249","Abattoir=
","","30-09-2024 16:40:17","30-09-2024 16:31:32","30-09-2024 17:39:23","Cas=
caded Incident from TTO3060599","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Gen stopped site went down because t=
he Grid contactor Faulty  // he bypass the Grid contactor and site on Grid"=
,"system","525","30-09-2024 16:40:17","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003206248","Pha=
rmacie SION","","30-09-2024 16:40:05","30-09-2024 16:34:00","30-09-2024 16:=
44:09","Grid outage  site down due to poor backup before gen start // Grid =
power return","Paul BIBOUM","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Battery Low","Grid outage  site down due to poor backup befo=
re gen start // Grid power return","joelle.ekessi@ihstowers.com","366","30-=
09-2024 16:40:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003206235","A=
bom","IHS_YND_269","30-09-2024 16:37:24","30-09-2024 16:35:19","30-09-2024 =
16:50:13","Grid outage  site down due to poor backup before gen start // Gr=
id power return","Siligap Boris","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage  site down due to poor backup=
 before gen start // Grid power return","emmanuel.ghani@ihstowers.com","126=
","30-09-2024 16:37:24","Sagemcom CMR"
"Closed Complete","Warning","CTR_263","IHS_YND_217","NOCINC0003206219","Abo=
m","","30-09-2024 16:35:48","","","site alarming becuase Grid outage gen fa=
iled to start//Grid power return","Siligap Boris","Warning","Warning","POWE=
R","Warning - Site on Battery","site alarming becuase Grid outage gen faile=
d to start//Grid power return","kombi.samuel@ihstowers.com","3","30-09-2024=
 16:35:48","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003206203","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","30-09-2024 16:33:38","30-09-2=
024 16:30:32","30-09-2024 17:39:23","Gen stopped site went down because the=
 Grid contactor Faulty  // he bypass the Grid contactor and site on Grid","=
Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issu=
e","Gen stopped site went down because the Grid contactor Faulty  // he byp=
ass the Grid contactor and site on Grid","joelle.ekessi@ihstowers.com","346=
8","30-09-2024 16:33:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003206015","Ndogbess=
ol","","30-09-2024 16:26:33","30-09-2024 15:56:46","30-09-2024 16:04:46","C=
ascaded Incident from TTO3060017","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Gen stoppped site went down becaus=
e the Grid contactor Faulty  // He blocked the Grid contactor manually  and=
 site on Grid","system","1787","30-09-2024 16:26:33","Sagemcom CMR"
"Closed Complete","Warning","T0139","IHS_YND_381","NOCINC0003205837","Boumn=
yebel","","30-09-2024 16:17:53","","","site alarming becuase Grid outage ge=
n failed to start//Grid power return and alarm cleared","Kemeni Franklin","=
Warning","Warning","POWER","Warning - Site on Battery","site alarming becua=
se Grid outage gen failed to start//Grid power return and alarm cleared","k=
ombi.samuel@ihstowers.com","1571","30-09-2024 16:17:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0003205756","M=
endong Maeture","","30-09-2024 16:14:06","30-09-2024 16:11:01","30-09-2024 =
17:40:15","Active: No power issue, site is on grid with Ubaie=3D54.3V, Mbah=
 hosiah(699699694) from Huawei is informedNotice that we have disjunction a=
t BTS OCM","Hyemafo Gildas","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Active: No power issue, site is on =
grid with Ubaie=3D54.3V, Mbah hosiah(699699694) from Huawei is informedNoti=
ce that we have disjunction at BTS OCM","emmanuel.ghani@ihstowers.com","185=
","30-09-2024 16:14:06","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003205595","Pha=
rmacie SION","","30-09-2024 16:09:42","30-09-2024 16:05:38","30-09-2024 16:=
16:55","Grid outage, site went down before gen start due to poor battery ba=
ckup // Grid power return","Paul BIBOUM","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid power return","joelle.ekessi=
@ihstowers.com","245","30-09-2024 16:09:42","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003205572","Ebo=
go","","30-09-2024 16:08:14","30-09-2024 16:01:10","30-09-2024 16:16:13","G=
rid fluctuation site went down because Gen failed to start due to Grid bad =
voltage// Gen automatically started","Siligap Boris","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid fluctuation site=
 went down because Gen failed to start due to Grid bad voltage// Gen automa=
tically started","joelle.ekessi@ihstowers.com","637","30-09-2024 16:08:14",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0139","IHS_YND_381","NOCINC0003205559","Bou=
mnyebel","IHS_EDA_056","30-09-2024 16:06:55","30-09-2024 15:56:46","30-09-2=
024 16:04:46","Gen stoppped site went down because the Grid contactor Fault=
y  // He blocked the Grid contactor manually  and site on Grid","Kemeni Fra=
nklin","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gen st=
oppped site went down because the Grid contactor Faulty  // He blocked the =
Grid contactor manually  and site on Grid","joelle.ekessi@ihstowers.com","8=
07","30-09-2024 16:06:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003205046","Lobo OCM=
","","30-09-2024 15:55:21","30-09-2024 15:52:14","30-09-2024 15:57:14","Cas=
caded Incident from TTO3059668","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automatically","s=
ystem","187","30-09-2024 15:55:21","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003205010","N=
KOMEKUI OCM","IHS_YND_341","30-09-2024 15:54:19","30-09-2024 15:52:14","30-=
09-2024 15:57:14","Grid outage, site went down before gen start due to poor=
 battery backup // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, site went down before gen start due to poor battery backup // Gen=
 start automatically","emmanuel.ghani@ihstowers.com","126","30-09-2024 15:5=
4:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003204947","M=
vog-Manga","","30-09-2024 15:52:18","30-09-2024 15:51:13","30-09-2024 16:12=
:48","Grid fluctuation site went down because Gen failed to start due to Gr=
id bad voltage// Grid stabilized","Albran Byorel","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","Grid fluctuation site went=
 down because Gen failed to start due to Grid bad voltage// Grid stabilized=
","emmanuel.ghani@ihstowers.com","67","30-09-2024 15:52:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003203798","E=
bogo","","30-09-2024 15:21:42","30-09-2024 15:19:59","30-09-2024 15:25:05",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Grid power return","Siligap Boris","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery backup // Grid power return","emmanuel.ghani@ihs=
towers.com","104","30-09-2024 15:21:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0003203067","Mamch Bu=
ilding","","30-09-2024 14:11:01","30-09-2024 13:59:47","30-09-2024 15:30:52=
","No power issue, site is on Grid with Ubaie=3D54V, the fme tx Armand Ngue=
tsa(699949553) from Huawei is informed","Mboua Thierry","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue, site is on Grid with Ubaie=3D54V, the fme tx Armand Nguetsa(699949=
553) from Huawei is informed","ange.kongo@ihstowers.com","675","30-09-2024 =
14:11:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0003202677","ARMP",""=
,"30-09-2024 12:57:41","30-09-2024 12:47:37","30-09-2024 12:57:37","Cascade=
d Incident from TTO3057215","","Cascade Outage","Active","Cascade Active","=
Cascade Active","Active//No power issue on site U=3D53,4v site on grid Elou=
ndou of huawei is informed","system","603","30-09-2024 12:57:41","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0003202671","D=
ragage","IHS_YND_704, IHS_YND_208","30-09-2024 12:56:42","30-09-2024 12:47:=
37","30-09-2024 12:57:37","Active//No power issue on site U=3D53,4v site on=
 grid Eloundou of huawei is informed","Mboua Thierry","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue on site U=3D53,4v site on grid Eloundou of huawei is informed=
","ange.kongo@ihstowers.com","546","30-09-2024 12:56:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0003202661","B=
astos Bir","","30-09-2024 12:55:29","30-09-2024 12:47:37","30-09-2024 12:57=
:37","Active//No power issue on site U=3D53,4v site on grid Eloundou of hua=
wei is informed","Mboua Thierry","Cascade Outage","Active","Cascade Active"=
,"Cascade Active","Active//No power issue on site U=3D53,4v site on grid El=
oundou of huawei is informed","ange.kongo@ihstowers.com","902","30-09-2024 =
12:55:29","Sagemcom CMR"
"Closed Complete","Site Down","T1689","IHS_YND_523","NOCINC0003202516","EMA=
NA BILICK CITY","","30-09-2024 12:37:01","30-09-2024 12:30:46","30-09-2024 =
13:04:21","Site went down due to work William/656072656/Coordinator IHS/ wo=
rking on site ""Replaced the Eneo CB""// End of work","Fabrice Pouakam","Eq=
uipment Replacement","Passive","Planned Activity","Planned Activity - Passi=
ve","Site went down due to work William/656072656/Coordinator IHS/ working =
on site ""Replaced the Eneo CB""// End of work","denis.mballa@ihstowers.com=
","376","30-09-2024 12:37:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003202037","E=
lobi Mokolo","","30-09-2024 11:04:58","30-09-2024 11:01:53","30-09-2024 11:=
09:53","Grid outage,site went down before DG start : Poor Batteries Backup/=
/ DG started automatically.","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage,site went down be=
fore DG start : Poor Batteries Backup// DG started automatically.","ange.ko=
ngo@ihstowers.com","186","30-09-2024 11:04:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003201598","Messassi=
 okolo","","30-09-2024 09:59:50","30-09-2024 09:54:24","30-09-2024 10:14:57=
","Cascaded Incident from TTO3056059","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage,gen start and stop=
ped with alarm under frequency// he reset the card and started the gen","sy=
stem","326","30-09-2024 09:59:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0003201585","E=
MANA BILICK CITY","IHS_YND_279","30-09-2024 09:59:07","30-09-2024 09:54:24"=
,"30-09-2024 10:14:57","grid outage,gen start and stopped with alarm under =
frequency// he reset the card and started the gen","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Under Frequency","grid outage,gen=
 start and stopped with alarm under frequency// he reset the card and start=
ed the gen","ange.kongo@ihstowers.com","284","30-09-2024 09:59:07","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0003201275","M=
om","","30-09-2024 09:23:19","30-09-2024 08:18:57","30-09-2024 10:35:09","A=
ctive// No power issue on site ,site on Gen with Ubaie=3D 54,1V The fme tx =
Etienne fopa // 695033981 of huawei is informed and Site UP at =3D08.20 AM"=
,"Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active// No power issue on site ,site on Gen wit=
h Ubaie=3D 54,1V The fme tx Etienne fopa // 695033981 of huawei is informed=
 and Site UP at =3D08.20 AM","marie.kwin@ihstowers.com","3863","30-09-2024 =
09:23:19","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003201217","Jou=
vence 2000","","30-09-2024 09:15:35","30-09-2024 09:12:58","30-09-2024 09:2=
7:58","Grid outage, site went down before gen start due to poor battery bac=
kup // gen start ","Delor Telezing","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery backup // gen start ","denis.mballa@ihstowers.co=
m","158","30-09-2024 09:15:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0003201163","FOUGEROL=
E","","30-09-2024 09:08:30","30-09-2024 09:03:47","30-09-2024 09:08:12","Ca=
scaded Incident from TTO3055572","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site went down due to work  our FME B=
oris /681809743 /SAGEMCOM/ Replaced the 2*CB 100A to the 2*CB 125 A//End of=
 work","system","283","30-09-2024 09:08:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0003201156","N=
gousso-Savana","IHS_YND_561","30-09-2024 09:06:59","30-09-2024 09:03:47","3=
0-09-2024 09:08:12","site went down due to work  our FME Boris /681809743 /=
SAGEMCOM/ Replaced the 2*CB 100A to the 2*CB 125 A//End of work","Siligap B=
oris","Equipment Replacement","Passive","Planned Activity","Planned Activit=
y - Passive","site went down due to work  our FME Boris /681809743 /SAGEMCO=
M/ Replaced the 2*CB 100A to the 2*CB 125 A//End of work","ange.kongo@ihsto=
wers.com","193","30-09-2024 09:06:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0003200892","Sapeur",=
"","30-09-2024 08:41:21","30-09-2024 08:37:39","30-09-2024 08:39:56","Casca=
ded Incident from TTO3055238","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid Outage No Space to deploy a MDG//Gr=
id Restored","system","222","30-09-2024 08:41:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0003200849","E=
-Police","IHS_YND_029","30-09-2024 08:38:54","30-09-2024 08:37:39","30-09-2=
024 08:39:56","Grid Outage No Space to deploy a MDG//Grid Restored","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage=
 No Space to deploy a MDG//Grid Restored","ange.kongo@ihstowers.com","76","=
30-09-2024 08:38:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0003200785","Messassi=
 Ngonlonk","","30-09-2024 08:27:31","30-09-2024 08:19:26","30-09-2024 08:38=
:26","Cascaded Incident from TTO3055163","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid outage,gen stopped wit=
h alarm high temp//he added water in radiator ","system","485","30-09-2024 =
08:27:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003200784","Akak-Nko=
zoa-MTN-IHS","","30-09-2024 08:27:30","30-09-2024 08:19:26","30-09-2024 08:=
38:26","Cascaded Incident from TTO3055163","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","grid outage,gen stopped w=
ith alarm high temp//he added water in radiator ","system","484","30-09-202=
4 08:27:30","Sagemcom CMR"
"Closed Complete","Site Down","T0051","IHS_YND_297","NOCINC0003200779","Mes=
sassi","IHS_YND_316, IHS_YND_799","30-09-2024 08:26:37","30-09-2024 08:16:4=
0","30-09-2024 08:46:40","grid outage,gen stopped with alarm high temp//he =
added water in radiator ","Fabrice Pouakam","Equipment Repair","Passive","A=
CDG Gen","ACDG - High Engine Temp - Coolant Level Issue","grid outage,gen s=
topped with alarm high temp//he added water in radiator ","denis.mballa@ihs=
towers.com","735","30-09-2024 08:26:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003200292","M=
EHANDAN","","30-09-2024 07:10:15","30-09-2024 07:06:49","30-09-2024 08:46:4=
9","Site on DG due to grid outage,site went down due to AVR dysfunctioning =
//He recalibration of AVR (Deep investigation Ongoing ).","Albran Byorel","=
Equipment Repair","Passive","ACDG Gen","ACDG - AVR","Site on DG due to grid=
 outage,site went down due to AVR dysfunctioning //He recalibration of AVR =
(Deep investigation Ongoing ).","ange.kongo@ihstowers.com","207","30-09-202=
4 07:10:15","Sagemcom CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0003199237","Mes=
sassi Ngonlonk","","30-09-2024 02:31:05","30-09-2024 02:22:54","30-09-2024 =
04:06:41","Site went down because Gen failed to start due to ATS faulty//He=
 hypassed ATS  and started Gen manually","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","ATS-AMF Issue","Site went down because Gen fa=
iled to start due to ATS faulty//He hypassed ATS  and started Gen manually"=
,"kamga.virgile@ihstowers.com","492","30-09-2024 02:31:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003199076","N=
yom OCM","","30-09-2024 01:43:39","29-09-2024 23:25:36","30-09-2024 01:16:0=
4","Grid Outage, Site went because Gen  started and stopped due to ""Oversp=
eed"" alarm // He reset Gen Card and started Gen manualy","Fabrice Pouakam"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outag=
e, Site went because Gen  started and stopped due to ""Overspeed"" alarm //=
 He reset Gen Card and started Gen manualy","alexandre.kamal@ihstowers.com"=
,"8284","30-09-2024 01:43:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_670","NOCINC0003199005","BOBOCK",=
"","30-09-2024 01:22:01","30-09-2024 00:19:25","30-09-2024 04:37:14","Casca=
ded Incident from TTO3053301","Kemeni Franklin","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","ENEO Cb(63A) burned, site went down be=
cause Gen started and stopped due to ""Overvoltage"" alarm// He reset Gen c=
ard and made a bridge with another CB: Site on Grid","system","3756","30-09=
-2024 01:22:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0003199003","NYANON/D=
EMBO","","30-09-2024 01:22:00","30-09-2024 00:19:25","30-09-2024 04:37:14",=
"Cascaded Incident from TTO3053301","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","ENEO Cb(63A) burned, si=
te went down because Gen started and stopped due to ""Overvoltage"" alarm//=
 He reset Gen card and made a bridge with another CB: Site on Grid","system=
","3755","30-09-2024 01:22:00","Sagemcom CMR"
"Closed Complete","Site Down","T1324","IHS_YND_307","NOCINC0003198868","Ebo=
go","","30-09-2024 00:44:03","30-09-2024 00:34:52","30-09-2024 00:51:09","G=
rid outage, site down due to poor backup before gen start // Grid Power ret=
urn","Siligap Boris","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Battery Low","Grid outage, site down due to poor backup before gen =
start // Grid Power return","kamga.virgile@ihstowers.com","551","30-09-2024=
 00:44:03","Sagemcom CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0003198846","Nya=
hoo","IHS_EDA_102, IHS_EDA_049, IHS_YND_670","30-09-2024 00:37:35","30-09-2=
024 00:19:25","30-09-2024 04:37:14","ENEO Cb(63A) burned, site went down be=
cause Gen started and stopped due to ""Overvoltage"" alarm// He reset Gen c=
ard and made a bridge with another CB: Site on Grid","TIENTCHEU NZETCHIEU G=
AEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","ENEO C=
b(63A) burned, site went down because Gen started and stopped due to ""Over=
voltage"" alarm// He reset Gen card and made a bridge with another CB: Site=
 on Grid","kamga.virgile@ihstowers.com","1091","30-09-2024 00:37:35","Sagem=
com CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0003198709","Meh=
anda 1","","29-09-2024 23:52:26","29-09-2024 23:27:15","30-09-2024 08:19:54=
","Access issue during the Night due to Landlord,Grid Outage ,Gen  stopped =
due to ""low oil pressure"" alarm (unprouven alarm) // He reset Gen Card an=
d started Gen manually","Albran Byorel","Access Denial","Lease Or Legal","L=
andlord Related Issues","Access Issue - Land Lord","Access issue during the=
 Night due to Landlord,Grid Outage ,Gen  stopped due to ""low oil pressure"=
" alarm (unprouven alarm) // He reset Gen Card and started Gen manually","k=
amga.virgile@ihstowers.com","1512","29-09-2024 23:52:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_337","NOCINC0003198165","Okola","=
","29-09-2024 21:57:30","29-09-2024 21:47:29","29-09-2024 22:16:50","Cascad=
ed Incident from TTO3052515","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage, site went down be=
cause Gen failed to start because Gen Card disfunctionned due to heavy rain=
// He started Gen manualy","system","601","29-09-2024 21:57:30","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0003198144","E=
zezang","IHS_YND_337, IHS_YND_530, IHS_YND_390","29-09-2024 21:52:45","29-0=
9-2024 21:47:29","29-09-2024 22:17:12","Grid Outage, site went down because=
 Gen failed to start because Gen Card disfunctionned due to heavy rain// He=
 started Gen manualy","Parker Tchoup","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid Outage, site went down because Gen failed t=
o start because Gen Card disfunctionned due to heavy rain// He started Gen =
manualy","kouoh.jean@ihstowers.com","540","29-09-2024 21:52:45","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003198112","K=
oweit City","","29-09-2024 21:48:07","29-09-2024 21:29:41","29-09-2024 21:3=
5:36","No power issue on site ,site on Grid  with Ubaie=3D56,3 V The Tx FME=
 Leonel Steve  (655184876) from Huawei is informed.","Albran Byorel","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site ,site on Grid  with Ubaie=3D56,3 V The Tx FME =
Leonel Steve  (655184876) from Huawei is informed.","kouoh.jean@ihstowers.c=
om","1107","29-09-2024 21:48:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_625","IHS_YND_181","NOCINC0003198108","M=
imboman3","","29-09-2024 21:46:30","29-09-2024 21:24:11","29-09-2024 21:30:=
42","No power issue on site ,site on Grid  with Ubaie=3D54 V Tx fme Eloundo=
u Bertrand /693212405 from huawei is informed","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue on site ,site on Grid  with Ubaie=3D54 V Tx fme Eloundou =
Bertrand /693212405 from huawei is informed","kouoh.jean@ihstowers.com","13=
40","29-09-2024 21:46:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003197830","E=
kounou","","29-09-2024 21:00:45","29-09-2024 20:49:58","29-09-2024 20:57:16=
","Grid outage, site went down before Gen start due to poor battery backup =
// grid return","Albran Byorel","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, site went down before Gen sta=
rt due to poor battery backup // grid return","kouoh.jean@ihstowers.com","6=
48","29-09-2024 21:00:45","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003197809","MBI=
MBIM","","29-09-2024 20:57:43","29-09-2024 19:57:36","29-09-2024 22:38:42",=
"Site went down because Gen started and  stopped due to water infiltration =
in the tank// He purged the Gen and removed water","Parker Tchoup","Fuel Ou=
tage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel=
","Site went down because Gen started and  stopped due to water infiltratio=
n in the tank// He purged the Gen and removed water","landry.etame@ihstower=
s.com","3608","29-09-2024 20:57:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003197806","M=
vog-Manga","","29-09-2024 20:56:56","29-09-2024 20:52:45","29-09-2024 20:59=
:45","grid outage, site went down because gen start and stoppen with alarm =
under frequency and PLC3 faulty // grid return","Albran Byorel","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage, site went=
 down because gen start and stoppen with alarm under frequency and PLC3 fau=
lty // grid return","kouoh.jean@ihstowers.com","252","29-09-2024 20:56:56",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003197485","Eko=
unou","","29-09-2024 20:14:05","29-09-2024 20:07:58","29-09-2024 20:15:13",=
"Grid outage,site went down before DG start: Poor Batteries Backup //Grid r=
estored,","Albran Byorel","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage,site went down before DG start: Poor=
 Batteries Backup //Grid restored,","landry.etame@ihstowers.com","368","29-=
09-2024 20:14:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003196948","Eto koss=
 Yde","","29-09-2024 18:54:40","29-09-2024 18:52:15","29-09-2024 18:56:12",=
"Cascaded Incident from TTO3051276","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation,Gen failed to start=
 due to Grid bad voltge //Grid stabilized","system","145","29-09-2024 18:54=
:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003196949","ELOUMDEM=
 CARRIERE 2","","29-09-2024 18:54:40","29-09-2024 18:52:15","29-09-2024 18:=
56:12","Cascaded Incident from TTO3051276","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation,Gen failed t=
o start due to Grid bad voltge //Grid stabilized","system","145","29-09-202=
4 18:54:40","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003196927","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","29-09-2024 18:53:28","29-09-2024 18:52=
:15","29-09-2024 18:56:12","Grid fluctuation,Gen failed to start due to Gri=
d bad voltge //Grid stabilized","Fanda Brice","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid fluctuation,Gen failed to=
 start due to Grid bad voltge //Grid stabilized","landry.etame@ihstowers.co=
m","74","29-09-2024 18:53:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003195640","Kondengu=
i","","29-09-2024 15:54:10","29-09-2024 15:49:08","29-09-2024 16:25:52","Ca=
scaded Incident from TTO3049862","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage  // Grid return
","system","302","29-09-2024 15:54:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003195632","E=
mombo-Tchad","IHS_YND_114","29-09-2024 15:53:31","29-09-2024 15:49:08","29-=
09-2024 16:25:52","Grid outage  // Grid return","","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid outage  // Grid return
","kouoh.jean@ihstowers.com","264","29-09-2024 15:53:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003195510","T=
ongolo OCM","","29-09-2024 15:37:05","29-09-2024 15:29:48","29-09-2024 15:5=
0:54","site went down due to pwc overload(12kilo, 218A) due to increase loa=
d on site  // Site stabilized","Delor Telezing","Equipment Repair","Passive=
","Rectifier","Rectifier Module Overloaded","site went down due to pwc over=
load(12kilo, 218A) due to increase load on site  // Site stabilized","kouoh=
.jean@ihstowers.com","438","29-09-2024 15:37:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003195391","A=
kak-Nkozoa-MTN-IHS","","29-09-2024 15:22:54","29-09-2024 15:15:46","29-09-2=
024 16:30:52","Site went down because CB OCM(125A)  disjuncted in PWC //He =
reamed CB","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Circuit Breaker Issue","Site went down because CB OCM(125A)=
  disjuncted in PWC //He reamed CB","kouoh.jean@ihstowers.com","429","29-09=
-2024 15:22:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003195378","E=
ssomba","","29-09-2024 15:20:47","29-09-2024 15:07:35","29-09-2024 16:24:00=
","Grid outage site went down because Gen started and stopped   with alarm =
"" over current ""// Grid power return","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went down =
because Gen started and stopped   with alarm "" over current ""// Grid powe=
r return","kouoh.jean@ihstowers.com","793","29-09-2024 15:20:47","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0003195258","B=
astos Ekoudou","","29-09-2024 15:05:38","29-09-2024 15:01:16","29-09-2024 1=
6:07:00","Grid outage Site went down because Gen stopped due to ""high temp=
"" alarm //He added water and Gen manually started","Mboua Thierry","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Grid outage Site went down because Gen stopped due to ""high temp"" =
alarm //He added water and Gen manually started","kouoh.jean@ihstowers.com"=
,"263","29-09-2024 15:05:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003195173","M=
EHANDAN","","29-09-2024 14:52:42","29-09-2024 14:42:33","29-09-2024 15:50:3=
3","Grid  bad voltage, site went down because Gen failed to start due to Gr=
id bad voltage and No RCP on site//he bypassed Grid and Started Gen","Albra=
n Byorel","Grid Supply","Passive","Grid","National Grid - Phase Controller =
Faulty","Grid  bad voltage, site went down because Gen failed to start due =
to Grid bad voltage and No RCP on site//he bypassed Grid and Started Gen","=
kouoh.jean@ihstowers.com","610","29-09-2024 14:52:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_277","NOCINC0003194431","Ngoulmek=
ong-Nord","","29-09-2024 12:47:40","29-09-2024 12:41:31","29-09-2024 12:59:=
01","Cascaded Incident from TTO3048552","Siligap Boris","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down because the Cb(=
125A) of PWC faulty// he bypass the cb and  connected with domino","system"=
,"369","29-09-2024 12:47:40","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003194244","Bas=
tos Ekoudou","","29-09-2024 12:25:42","29-09-2024 12:22:37","29-09-2024 12:=
26:24","Grid outage, Site went down due to poor batteries backup before Gen=
 start //Gen started automatically.","Mboua Thierry","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site wen=
t down due to poor batteries backup before Gen start //Gen started automati=
cally.","joelle.ekessi@ihstowers.com","186","29-09-2024 12:25:42","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1832","IHS_YND_216","NOCINC0003194046","Ele=
veur","IHS_YND_277","29-09-2024 11:47:34","29-09-2024 11:42:31","29-09-2024=
 12:59:39","site went down because the Cb(125A) of PWC faulty// he bypass t=
he cb and  connected with domino","Siligap Boris","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Circuit Breaker Issue","site went down=
 because the Cb(125A) of PWC faulty// he bypass the cb and  connected with =
domino","joelle.ekessi@ihstowers.com","304","29-09-2024 11:47:34","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0003193982","Mes=
sassi Carrefourt","","29-09-2024 11:33:48","29-09-2024 11:18:43","29-09-202=
4 13:34:04","Grid outage site went down because Gen failed to start due to =
No automatism on site // Gen manually started","Delor Telezing","Equipment =
Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage site went do=
wn because Gen failed to start due to No automatism on site // Gen manually=
 started","kombi.samuel@ihstowers.com","906","29-09-2024 11:33:48","Sagemco=
m CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003193859","Jou=
vence 2000","","29-09-2024 11:12:57","29-09-2024 11:07:50","29-09-2024 13:0=
9:11","Grid outage, Site went down due to poor batteries backup before Gen =
start //Gen started manually.","Delor Telezing","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went dow=
n due to poor batteries backup before Gen start //Gen started manually.","j=
oelle.ekessi@ihstowers.com","308","29-09-2024 11:12:57","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0003193292","Mes=
sassi Carrefourt","","29-09-2024 09:31:37","29-09-2024 09:25:37","29-09-202=
4 10:35:49","Grid outage site went down because Gen failed to start due to =
no automatism on site// Gen manually started","Delor Telezing","Equipment R=
epair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site went d=
own because Gen failed to start due to no automatism on site// Gen manually=
 started","joelle.ekessi@ihstowers.com","361","29-09-2024 09:31:37","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003192996","M=
elen Ba'aba","","29-09-2024 08:37:42","29-09-2024 08:34:38","29-09-2024 08:=
49:35","Grid Outage,site went down before Gen start due to poor battery bac=
kup//Grid power return","Siligap Boris","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Outage,site went down before =
Gen start due to poor battery backup//Grid power return","emmanuel.ghani@ih=
stowers.com","185","29-09-2024 08:37:42","Sagemcom CMR"
"Closed Complete","Warning","T1618","IHS_YND_305","NOCINC0003192925","NYOM"=
,"","29-09-2024 08:18:29","","","SIte alarming because the Cable Grid burn =
// He bypass the Grid and Gen manually started","Fabrice Pouakam","Warning"=
,"Warning","POWER","Warning - Site on Battery","SIte alarming because the C=
able Grid burn // He bypass the Grid and Gen manually started","kombi.samue=
l@ihstowers.com","2","29-09-2024 08:18:29","Sagemcom CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0003192525","Nta=
ba","","29-09-2024 07:13:02","29-09-2024 07:09:58","29-09-2024 07:15:04","G=
rid outage, Site went down due to poor batteries backup before Gen start //=
Gen automatically started","Delor Telezing","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down du=
e to poor batteries backup before Gen start //Gen automatically started","j=
oelle.ekessi@ihstowers.com","185","29-09-2024 07:13:02","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003192448","Jou=
vence 2000","","29-09-2024 06:58:33","29-09-2024 06:57:29","29-09-2024 10:0=
9:05","No power issue, site is on Gen with Ubaie=3D49V, the fme tx Armand N=
guetsa(699949553) from Huawei is informed","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue, site is on Gen with Ubaie=3D49V, the fme tx Armand Nguetsa(699=
949553) from Huawei is informed","joelle.ekessi@ihstowers.com","65","29-09-=
2024 06:58:33","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0003192356","Man=
guiers Dispensaire","","29-09-2024 06:37:46","29-09-2024 06:35:41","29-09-2=
024 06:40:35","Grid fluctuation site went down because Gen failed to start =
due to Grid bad voltage// He bypass the Grid and Gen manually started","Fab=
rice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation site went down because Gen failed to start du=
e to Grid bad voltage// He bypass the Grid and Gen manually started","joell=
e.ekessi@ihstowers.com","125","29-09-2024 06:37:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003192129","K=
oweit City","","29-09-2024 05:37:00","29-09-2024 05:32:54","29-09-2024 05:4=
0:16","No power issue U:54,5 V site on Grid. TX FME Leonel Steve   (6551848=
76) from Huawei is informed. ","Albran Byorel","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=
:54,5 V site on Grid. TX FME Leonel Steve   (655184876) from Huawei is info=
rmed. ","ludivine.ngamaleu@ihstowers.com","247","29-09-2024 05:37:00","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0003191911","Boga-Mah=
ole","","29-09-2024 04:25:53","29-09-2024 04:12:14","29-09-2024 05:55:54","=
Cascaded Incident from TTO3046102","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because Gen card a=
nd Grid contactor faulty due to lightning// Gen manually started","system",=
"819","29-09-2024 04:25:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0003191906","Eseka OC=
M","","29-09-2024 04:25:52","29-09-2024 04:12:14","29-09-2024 05:55:54","Ca=
scaded Incident from TTO3046102","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because Gen card and=
 Grid contactor faulty due to lightning// Gen manually started","system","8=
18","29-09-2024 04:25:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003191908","Song-bon=
g","","29-09-2024 04:25:52","29-09-2024 04:12:14","29-09-2024 05:55:54","Ca=
scaded Incident from TTO3046102","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because Gen card and=
 Grid contactor faulty due to lightning// Gen manually started","system","8=
18","29-09-2024 04:25:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003191910","Mamb",""=
,"29-09-2024 04:25:52","29-09-2024 04:12:14","29-09-2024 05:55:54","Cascade=
d Incident from TTO3046102","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site went down because Gen card and Grid=
 contactor faulty due to lightning// Gen manually started","system","818","=
29-09-2024 04:25:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003191902","Boumnyeb=
el","","29-09-2024 04:25:51","29-09-2024 04:12:14","29-09-2024 05:55:54","C=
ascaded Incident from TTO3046102","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because Gen card an=
d Grid contactor faulty due to lightning// Gen manually started","system","=
817","29-09-2024 04:25:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003191901","Ngog Map=
ubi","","29-09-2024 04:25:51","29-09-2024 04:12:14","29-09-2024 05:55:54","=
Cascaded Incident from TTO3046102","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because Gen card a=
nd Grid contactor faulty due to lightning// Gen manually started","system",=
"817","29-09-2024 04:25:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0003191897","Boumnyeb=
el OCM","","29-09-2024 04:25:50","29-09-2024 04:12:14","29-09-2024 05:55:54=
","Cascaded Incident from TTO3046102","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down because Gen car=
d and Grid contactor faulty due to lightning// Gen manually started","syste=
m","816","29-09-2024 04:25:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003191898","Eseka To=
wn","","29-09-2024 04:25:50","29-09-2024 04:12:14","29-09-2024 05:55:54","C=
ascaded Incident from TTO3046102","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because Gen card an=
d Grid contactor faulty due to lightning// Gen manually started","system","=
816","29-09-2024 04:25:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003191253","E=
lig Edzoa","","29-09-2024 01:46:53","29-09-2024 01:44:48","29-09-2024 01:47=
:09","Grid outage, Site went down due to poor batteries backup before Gen s=
tart //Gen started automatically.","Delor Telezing","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, Site went=
 down due to poor batteries backup before Gen start //Gen started automatic=
ally.","ludivine.ngamaleu@ihstowers.com","126","29-09-2024 01:46:53","Sagem=
com CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0003191219","Nta=
ba","","29-09-2024 01:34:48","29-09-2024 01:31:42","29-09-2024 01:38:36","G=
rid outage, Site went down due to poor batteries backup before Gen start //=
Gen started automatically","Delor Telezing","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, Site went down du=
e to poor batteries backup before Gen start //Gen started automatically","o=
livier.kwedi@ihstowers.com","320","29-09-2024 01:34:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003191203","Nkolo II=
 New","","29-09-2024 01:30:20","29-09-2024 01:25:35","29-09-2024 01:37:02",=
"Cascaded Incident from TTO3045515","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down due=
 to poor batteries backup before Gen start //Gen started automatically.","s=
ystem","285","29-09-2024 01:30:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003191201","M=
imboman-Village","IHS_YND_709","29-09-2024 01:29:40","29-09-2024 01:25:35",=
"29-09-2024 01:37:02","Grid outage, Site went down due to poor batteries ba=
ckup before Gen start //Gen started automatically.","Mba Lazare Herve","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, Site went down due to poor batteries backup before Gen start //Ge=
n started automatically.","ludivine.ngamaleu@ihstowers.com","246","29-09-20=
24 01:29:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003191194","E=
lig-Edzoa","","29-09-2024 01:28:34","29-09-2024 01:19:30","29-09-2024 01:38=
:10","Grid Outage// Grid return","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Outage Issue","Grid Outage// Grid return","ludivine.ngamaleu@=
ihstowers.com","546","29-09-2024 01:28:34","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003191190","Jou=
vence 2000","","29-09-2024 01:24:56","29-09-2024 01:18:48","29-09-2024 02:1=
0:13","Grid outage, Site went down due to poor batteries backup before Gen =
start //Gen started automatically but site  Site up after Power reset","Del=
or Telezing","Equipment Repair","Passive","Control Panel","Power Cabinet - =
Battery Low","Grid outage, Site went down due to poor batteries backup befo=
re Gen start //Gen started automatically but site  Site up after Power rese=
t","olivier.kwedi@ihstowers.com","369","29-09-2024 01:24:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003191186","N=
kolondom","","29-09-2024 01:22:16","28-09-2024 22:21:00","29-09-2024 01:37:=
31","No power issue site on Grid , with U=3D57 V The Tx Fme symphorien //69=
1316854 is informed","Fabrice Pouakam","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on G=
rid , with U=3D57 V The Tx Fme symphorien //691316854 is informed","etienne=
.itondo@ihstowers.com","10877","29-09-2024 01:22:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0003191022","M=
VAN SACEL","","29-09-2024 00:32:44","29-09-2024 00:30:56","29-09-2024 00:38=
:43","Grid outage, Site went down due to poor batteries backup before Gen s=
tart //Grid return","MINKA NICOLAS","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, Site went down due to poo=
r batteries backup before Gen start //Grid return","ludivine.ngamaleu@ihsto=
wers.com","370","29-09-2024 00:32:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003190752","Lobo OCM=
","","28-09-2024 23:23:40","28-09-2024 22:21:24","28-09-2024 22:26:24","Cas=
caded Incident from TTO3044815","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // gen start automatically","s=
ystem","3736","28-09-2024 23:23:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0003190608","Messassi=
 2","","28-09-2024 22:45:21","28-09-2024 22:21:18","28-09-2024 22:31:33","C=
ascaded Incident from TTO3044883","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Si=
te went down because Gen stopped due to Gen overload(22KVA;330A)//He unload=
ed 3 RAM of battery;Site on Gen","system","1443","28-09-2024 22:45:21","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0003190607","Nyom OCM=
","","28-09-2024 22:45:21","28-09-2024 22:21:18","28-09-2024 22:31:33","Cas=
caded Incident from TTO3044883","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Site=
 went down because Gen stopped due to Gen overload(22KVA;330A)//He unloaded=
 3 RAM of battery;Site on Gen","system","1443","28-09-2024 22:45:21","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0003190602","NKOLMEKO=
NG YDE","","28-09-2024 22:45:20","28-09-2024 22:21:18","28-09-2024 22:31:33=
","Cascaded Incident from TTO3044883","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage=
 ,Site went down because Gen stopped due to Gen overload(22KVA;330A)//He un=
loaded 3 RAM of battery;Site on Gen","system","1442","28-09-2024 22:45:20",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0003190603","Olembe-T=
erminus","","28-09-2024 22:45:20","28-09-2024 22:21:18","28-09-2024 22:31:3=
3","Cascaded Incident from TTO3044883","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site on Gen due to Grid outag=
e ,Site went down because Gen stopped due to Gen overload(22KVA;330A)//He u=
nloaded 3 RAM of battery;Site on Gen","system","1442","28-09-2024 22:45:20"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0003190601","Ekombiti=
e","","28-09-2024 22:45:20","28-09-2024 22:21:18","28-09-2024 22:31:33","Ca=
scaded Incident from TTO3044883","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Sit=
e went down because Gen stopped due to Gen overload(22KVA;330A)//He unloade=
d 3 RAM of battery;Site on Gen","system","1442","28-09-2024 22:45:20","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0003190604","Messassi=
","","28-09-2024 22:45:20","28-09-2024 22:21:18","28-09-2024 22:31:33","Cas=
caded Incident from TTO3044883","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Site=
 went down because Gen stopped due to Gen overload(22KVA;330A)//He unloaded=
 3 RAM of battery;Site on Gen","system","1442","28-09-2024 22:45:20","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0003190605","Nkozoa",=
"","28-09-2024 22:45:20","28-09-2024 22:21:18","28-09-2024 22:31:33","Casca=
ded Incident from TTO3044883","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Site w=
ent down because Gen stopped due to Gen overload(22KVA;330A)//He unloaded 3=
 RAM of battery;Site on Gen","system","1442","28-09-2024 22:45:20","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003190568","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_280","28-09-2024 22:36:26","28-09-2024 22:21:18","28-09-=
2024 22:31:33","Site on Gen due to Grid outage ,Site went down because Gen =
stopped due to Gen overload(22KVA;330A)//He unloaded 3 RAM of battery;Site =
on Gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Site on Gen due to Grid outage ,Site went down because Gen stoppe=
d due to Gen overload(22KVA;330A)//He unloaded 3 RAM of battery;Site on Gen=
","etienne.itondo@ihstowers.com","909","28-09-2024 22:36:26","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003190511","N=
KOMEKUI OCM","IHS_YND_341","28-09-2024 22:25:28","28-09-2024 22:21:24","28-=
09-2024 22:26:24","Grid outage, site went down before gen start due to poor=
 battery backup // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, site went down before gen start due to poor battery backup // gen=
 start automatically","ludivine.ngamaleu@ihstowers.com","245","28-09-2024 2=
2:25:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0003190174","Nkozoa",=
"","28-09-2024 21:25:20","28-09-2024 20:54:54","28-09-2024 21:25:55","Casca=
ded Incident from TTO3044251","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Site w=
ent down because Gen stopped due to Gen overload(22KVA;330A//He unloaded 3 =
RAM of battery;Site on Gen","system","1826","28-09-2024 21:25:20","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0003190016","NKOLMEKO=
NG YDE","","28-09-2024 20:59:51","28-09-2024 20:54:54","28-09-2024 21:25:55=
","Cascaded Incident from TTO3044251","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage=
 ,Site went down because Gen stopped due to Gen overload(22KVA;330A//He unl=
oaded 3 RAM of battery;Site on Gen","system","297","28-09-2024 20:59:51","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0003190018","Messassi=
","","28-09-2024 20:59:51","28-09-2024 20:54:54","28-09-2024 21:25:55","Cas=
caded Incident from TTO3044251","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Site=
 went down because Gen stopped due to Gen overload(22KVA;330A//He unloaded =
3 RAM of battery;Site on Gen","system","297","28-09-2024 20:59:51","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0003190021","Nkolondo=
m","","28-09-2024 20:59:51","28-09-2024 20:54:54","28-09-2024 21:25:55","Ca=
scaded Incident from TTO3044251","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Sit=
e went down because Gen stopped due to Gen overload(22KVA;330A//He unloaded=
 3 RAM of battery;Site on Gen","system","297","28-09-2024 20:59:51","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0003190017","Olembe-T=
erminus","","28-09-2024 20:59:51","28-09-2024 20:54:54","28-09-2024 21:25:5=
5","Cascaded Incident from TTO3044251","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site on Gen due to Grid outag=
e ,Site went down because Gen stopped due to Gen overload(22KVA;330A//He un=
loaded 3 RAM of battery;Site on Gen","system","297","28-09-2024 20:59:51","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0003190019","Nyom OCM=
","","28-09-2024 20:59:51","28-09-2024 20:54:54","28-09-2024 21:25:55","Cas=
caded Incident from TTO3044251","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Site=
 went down because Gen stopped due to Gen overload(22KVA;330A//He unloaded =
3 RAM of battery;Site on Gen","system","297","28-09-2024 20:59:51","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0003190020","Messassi=
 2","","28-09-2024 20:59:51","28-09-2024 20:54:54","28-09-2024 21:25:55","C=
ascaded Incident from TTO3044251","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Si=
te went down because Gen stopped due to Gen overload(22KVA;330A//He unloade=
d 3 RAM of battery;Site on Gen","system","297","28-09-2024 20:59:51","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0003190015","Ekombiti=
e","","28-09-2024 20:59:50","28-09-2024 20:54:54","28-09-2024 21:25:55","Ca=
scaded Incident from TTO3044251","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage ,Sit=
e went down because Gen stopped due to Gen overload(22KVA;330A//He unloaded=
 3 RAM of battery;Site on Gen","system","296","28-09-2024 20:59:50","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003189997","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_280, IHS_YND_304","28-09-2024 20:56:00","28-09-2024 20:5=
4:54","28-09-2024 21:25:55","Site on Gen due to Grid outage ,Site went down=
 because Gen stopped due to Gen overload(22KVA;330A//He unloaded 3 RAM of b=
attery;Site on Gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Overload","Site on Gen due to Grid outage ,Site went down becaus=
e Gen stopped due to Gen overload(22KVA;330A//He unloaded 3 RAM of battery;=
Site on Gen","alexandre.kamal@ihstowers.com","67","28-09-2024 20:56:00","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0003189621","M=
endong Maeture","","28-09-2024 19:50:48","28-09-2024 16:27:29","28-09-2024 =
16:37:20","No power issue site on Grid , with U=3D51 V TX FME OSIAH MBA //6=
99-69--96-94 is informed.","Hyemafo Gildas","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on Grid , with U=3D51 V TX FME OSIAH MBA //699-69--96-94 is informed.","al=
exandre.kamal@ihstowers.com","12199","28-09-2024 19:50:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003189565","N=
kozoa","","28-09-2024 19:33:30","28-09-2024 19:26:25","28-09-2024 20:08:19"=
,"Grid outage ,Site went down because Gen failed to start due to Gen overlo=
ad(20KVA,320)// Grid return","Fabrice Pouakam","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","Grid outage ,Site went down because Gen fail=
ed to start due to Gen overload(20KVA,320)// Grid return","alexandre.kamal@=
ihstowers.com","426","28-09-2024 19:33:30","Sagemcom CMR"
"Closed Complete","Warning","CTR_067","IHS_YND_377","NOCINC0003189005","Ese=
ka OCM","","28-09-2024 17:48:44","","","site alarming because the energy me=
ter burn// He bypass the Grid and Gen manually started. alarm cleared","Kem=
eni Franklin","Warning","Warning","POWER","Warning - Site on Battery","site=
 alarming because the energy meter burn// He bypass the Grid and Gen manual=
ly started. alarm cleared","stephane.nkamwa@ihstowers.com","488","28-09-202=
4 17:48:44","Sagemcom CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0003188603","Mes=
sassi Ngonlonk","","28-09-2024 16:39:42","28-09-2024 16:24:32","28-09-2024 =
17:22:38","Site went down because Gen failed to start due to ATS faulty//He=
 hypassed ATS  and started Gen manually","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","ATS-AMF Issue","Site went down because Gen fa=
iled to start due to ATS faulty//He hypassed ATS  and started Gen manually"=
,"kamga.virgile@ihstowers.com","911","28-09-2024 16:39:42","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003187643","Nsi=
meyong Shell","","28-09-2024 15:31:43","28-09-2024 15:26:32","28-09-2024 15=
:32:48","Grid outage, site went down before Gen start due to poor battery b=
ackup // Gen started  automatically","MINKA NICOLAS","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down before Gen start due to poor battery backup // Gen started  automati=
cally","kamga.virgile@ihstowers.com","312","28-09-2024 15:31:43","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003187488","M=
imboman-Ecole","","28-09-2024 15:20:03","28-09-2024 15:14:59","28-09-2024 1=
5:41:49","site went down due to work(Herv=E9 Lazard(657108482)/Sagemcom, PM=
)// End of Work","Mba Lazare Herve","Equipment Replacement","Passive","Plan=
ned Activity","Planned Activity - Passive","site went down due to work(Herv=
=E9 Lazard(657108482)/Sagemcom, PM)// End of Work","alexandre.kamal@ihstowe=
rs.com","305","28-09-2024 15:20:03","Sagemcom CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0003186362","Odz=
a petit marche new","","28-09-2024 13:41:57","28-09-2024 13:33:51","28-09-2=
024 21:46:35","Site went down because PWC burned // He replaced it","Albran=
 Byorel","Fire on Site","Passive","Infrastructure","Fire - Burned","Site we=
nt down because PWC burned // He replaced it","landry.etame@ihstowers.com",=
"487","28-09-2024 13:41:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0003185837","M=
endong Maeture","","28-09-2024 12:29:29","28-09-2024 12:26:20","28-09-2024 =
13:36:17","Grid fluctuation site went down because Gen failed to start due =
to Grid bad voltage// Grid stabilized","Hyemafo Gildas","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation sit=
e went down because Gen failed to start due to Grid bad voltage// Grid stab=
ilized","kouoh.jean@ihstowers.com","190","28-09-2024 12:29:29","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0003185172","B=
astos Ekoudou","","28-09-2024 11:05:49","28-09-2024 10:57:22","28-09-2024 1=
4:44:16","site went down because gen failed to start due to grid bad voltag=
e and poor battery backup// Gen manually started","Mboua Thierry","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","site went =
down because gen failed to start due to grid bad voltage and poor battery b=
ackup// Gen manually started","kouoh.jean@ihstowers.com","508","28-09-2024 =
11:05:49","Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003185150","HOP=
ITAL GENERAL RAIL YDE","","28-09-2024 11:02:21","28-09-2024 10:50:10","28-0=
9-2024 11:25:29","Grid bad voltage,no RCP,DG failed to start //He did a bri=
dge.","Delor Telezing","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid bad voltage,no RCP,DG failed to start //He did a=
 bridge.","landry.etame@ihstowers.com","731","28-09-2024 11:02:21","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0003185142","Olembe-T=
erminus","","28-09-2024 11:01:01","28-09-2024 10:47:58","28-09-2024 10:56:5=
8","Cascaded Incident from TTO3039001","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site on DG,due to grid outage=
,Site went down due to Main  PWC overload (24 ko ) Iload of site (340A ;22 =
kva)  // He connected The Tx of Olembe to the second PWC.Site remained of D=
G.","system","783","28-09-2024 11:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0003185141","NKOLMEKO=
NG YDE","","28-09-2024 11:01:01","28-09-2024 10:47:58","28-09-2024 10:56:58=
","Cascaded Incident from TTO3039001","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site on DG,due to grid outage,=
Site went down due to Main  PWC overload (24 ko ) Iload of site (340A ;22 k=
va)  // He connected The Tx of Olembe to the second PWC.Site remained of DG=
.","system","783","28-09-2024 11:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0003185143","Messassi=
","","28-09-2024 11:01:01","28-09-2024 10:47:58","28-09-2024 10:56:58","Cas=
caded Incident from TTO3039001","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site on DG,due to grid outage,Site w=
ent down due to Main  PWC overload (24 ko ) Iload of site (340A ;22 kva)  /=
/ He connected The Tx of Olembe to the second PWC.Site remained of DG.","sy=
stem","783","28-09-2024 11:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0003185145","Nkolondo=
m","","28-09-2024 11:01:01","28-09-2024 10:47:58","28-09-2024 10:56:58","Ca=
scaded Incident from TTO3039001","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site on DG,due to grid outage,Site =
went down due to Main  PWC overload (24 ko ) Iload of site (340A ;22 kva)  =
// He connected The Tx of Olembe to the second PWC.Site remained of DG.","s=
ystem","783","28-09-2024 11:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0003185144","Messassi=
 2","","28-09-2024 11:01:01","28-09-2024 10:47:58","28-09-2024 10:56:58","C=
ascaded Incident from TTO3039001","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site on DG,due to grid outage,Site=
 went down due to Main  PWC overload (24 ko ) Iload of site (340A ;22 kva) =
 // He connected The Tx of Olembe to the second PWC.Site remained of DG.","=
system","783","28-09-2024 11:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0003185140","Ekombiti=
e","","28-09-2024 11:01:00","28-09-2024 10:47:58","28-09-2024 10:56:58","Ca=
scaded Incident from TTO3039001","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site on DG,due to grid outage,Site =
went down due to Main  PWC overload (24 ko ) Iload of site (340A ;22 kva)  =
// He connected The Tx of Olembe to the second PWC.Site remained of DG.","s=
ystem","782","28-09-2024 11:01:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003185052","N=
kolda","","28-09-2024 10:46:42","28-09-2024 10:26:19","28-09-2024 11:05:01"=
,"Site went down during the works : Technician albran was installing a Circ=
uit Breaker //End of works.","Albran Byorel","Installation Activity","Passi=
ve","Planned Activity","Installation Activity","Site went down during the w=
orks : Technician albran was installing a Circuit Breaker //End of works. "=
,"kouoh.jean@ihstowers.com","1224","28-09-2024 10:46:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003184942","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_280, IH=
S_YND_304","28-09-2024 10:34:53","28-09-2024 10:10:28","28-09-2024 10:56:58=
","Site on DG,due to bad grid voltage,Site went down due to Main  PWC overl=
oad (24 ko ) Iload of site (340A ;22 kva)  // He connected The Tx of Olembe=
 to the second PWC.Site remained of DG.","Fabrice Pouakam","Equipment Repai=
r","Passive","Rectifier","Rectifier Module Overloaded","Site on DG,due to g=
rid outage,Site went down due to Main  PWC overload (24 ko ) Iload of site =
(340A ;22 kva)  // He connected The Tx of Olembe to the second PWC.Site rem=
ained of DG.","kouoh.jean@ihstowers.com","1466","28-09-2024 10:34:53","Sage=
mcom CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0003184473","Mes=
sassi Ngonlonk","","28-09-2024 09:33:33","28-09-2024 09:17:28","28-09-2024 =
11:09:17","Active // No Power on site,site on grid, with Ubaie:54,2V; Symph=
orien and RM HUAWEI Yaounde are unreachble.","Fabrice Pouakam","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active // No Power on site,site on grid, with Ubaie:54,2V; Symphorien and R=
M HUAWEI Yaounde are unreachble.","landry.etame@ihstowers.com","966","28-09=
-2024 09:33:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0003184348","E=
mombo","","28-09-2024 09:16:50","28-09-2024 09:09:25","28-09-2024 09:13:25"=
,"Grid outage,site went down before DG start due to Circuit breaker of PWC =
disjuncted //DG started automatically . Circuit breaker put back on(investi=
gations ongoing).","Mba Lazare Herve","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Circuit Breaker Issue","Grid outage,site went down=
 before DG start due to Circuit breaker of PWC disjuncted //DG started auto=
matically . Circuit breaker put back on.","kouoh.jean@ihstowers.com","446",=
"28-09-2024 09:16:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003184030","S=
tade-Abega","","28-09-2024 08:37:08","28-09-2024 08:04:00","28-09-2024 08:3=
0:00","Grid outage,DG failed to start due to ACDG starter dysfunctioning//M=
anaully start of DG (ACDG starter in observations).","Mba Lazare Herve","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Kick Starter","Grid outage,DG =
failed to start due to ACDG starter dysfunctioning//Manaully start of DG (A=
CDG starter in observations).","kouoh.jean@ihstowers.com","1989","28-09-202=
4 08:37:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0003183998","Nkolondo=
m","","28-09-2024 08:33:42","28-09-2024 08:18:44","28-09-2024 09:08:45","Ca=
scaded Incident from TTO3037824","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to start=
 ,RCP Faulty //Bypass Grid and manually start of DG,","system","898","28-09=
-2024 08:33:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0003183993","NKOLMEKO=
NG YDE","","28-09-2024 08:33:41","28-09-2024 08:18:44","28-09-2024 09:08:45=
","Cascaded Incident from TTO3037824","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to =
start ,RCP Faulty //Bypass Grid and manually start of DG,","system","897","=
28-09-2024 08:33:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0003183996","Nkozoa",=
"","28-09-2024 08:33:41","28-09-2024 08:18:44","28-09-2024 09:08:45","Casca=
ded Incident from TTO3037824","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to start ,R=
CP Faulty //Bypass Grid and manually start of DG,","system","897","28-09-20=
24 08:33:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0003183997","Messassi=
 2","","28-09-2024 08:33:41","28-09-2024 08:18:44","28-09-2024 09:08:45","C=
ascaded Incident from TTO3037824","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to star=
t ,RCP Faulty //Bypass Grid and manually start of DG,","system","897","28-0=
9-2024 08:33:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0003183994","Olembe-T=
erminus","","28-09-2024 08:33:41","28-09-2024 08:18:44","28-09-2024 09:08:4=
5","Cascaded Incident from TTO3037824","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to=
 start ,RCP Faulty //Bypass Grid and manually start of DG,","system","897",=
"28-09-2024 08:33:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0003183995","Messassi=
","","28-09-2024 08:33:41","28-09-2024 08:18:44","28-09-2024 09:08:45","Cas=
caded Incident from TTO3037824","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to start =
,RCP Faulty //Bypass Grid and manually start of DG,","system","897","28-09-=
2024 08:33:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0003183992","Ekombiti=
e","","28-09-2024 08:33:40","28-09-2024 08:18:44","28-09-2024 09:08:45","Ca=
scaded Incident from TTO3037824","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to start=
 ,RCP Faulty //Bypass Grid and manually start of DG,","system","896","28-09=
-2024 08:33:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003183970","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_280, IHS_YND_304","28-09-2024 08:28:04","28-09-2024 08:18:44","28-09-=
2024 09:59:50","","Fabrice Pouakam","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Grid Bad voltage,DG failed to start ,RCP=
 Faulty //Bypass Grid and manually start of DG,","kouoh.jean@ihstowers.com"=
,"561","28-09-2024 08:28:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0003183829","E=
vodoula OCM","","28-09-2024 08:00:03","28-09-2024 07:48:44","28-09-2024 08:=
00:10","Active//No power issue site and  with Ubaie=3D54.4 V site on Grid T=
he  FME TX Mouamadou/658791013 //From  is informed.","TIENTCHEU NZETCHIEU G=
AEL","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active//No power issue site and  with Ubaie=3D54.4 V site =
on Grid The  FME TX Mouamadou/658791013 //From  is informed
","kouoh.jean@ihstowers.com","682","28-09-2024 08:00:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003183473","MEHANDAN=
","","28-09-2024 06:55:50","28-09-2024 06:09:00","28-09-2024 08:52:39","Cas=
caded Incident from TTO3037332","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to 1/3 rectifer fau=
lty //He changed the faulty rectifier.","system","2810","28-09-2024 06:55:5=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003183463","O=
dza II OCM","IHS_YND_528","28-09-2024 06:54:10","28-09-2024 06:09:00","28-0=
9-2024 08:52:39","Site went down due to 1/3 rectifer faulty //He changed th=
e faulty rectifier.","Albran Byorel","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down due to 1/3 rectifer faulty //He chang=
ed the faulty rectifier.","kouoh.jean@ihstowers.com","2711","28-09-2024 06:=
54:10","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003183453","Eko=
unou","","28-09-2024 06:50:26","28-09-2024 06:46:20","28-09-2024 06:56:27",=
"Grid outage,site went down before DG start: Poor Batteries Backup //Grid r=
estored,","Albran Byorel","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage,site went down before DG start: Poor=
 Batteries Backup //Grid restored,
","landry.etame@ihstowers.com","247","28-09-2024 06:50:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003183418","Eto koss=
 Yde","","28-09-2024 06:41:10","28-09-2024 06:36:50","28-09-2024 07:02:34",=
"Cascaded Incident from TTO3037282","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to rectifiers dys=
functioning //He reset rectifiers,site on Grid,","system","260","28-09-2024=
 06:41:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003183419","ELOUMDEM=
 CARRIERE 2","","28-09-2024 06:41:10","28-09-2024 06:36:50","28-09-2024 07:=
02:34","Cascaded Incident from TTO3037282","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to rectifi=
ers dysfunctioning //He reset rectifiers,site on Grid,","system","260","28-=
09-2024 06:41:10","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003183411","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","28-09-2024 06:39:59","28-09-2024 06:16=
:50","28-09-2024 07:02:34","Site went down due to rectifiers dysfunctioning=
 //He reset rectifiers,site on Grid,","Fanda Brice","Equipment Repair","Pas=
sive","Rectifier","Rectifier Module","Site went down due to rectifiers dysf=
unctioning //He reset rectifiers,site on Grid,","landry.etame@ihstowers.com=
","2497","28-09-2024 06:39:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0003183263","Nkolondo=
m","","28-09-2024 06:05:31","28-09-2024 05:59:42","28-09-2024 06:41:22","Ca=
scaded Incident from TTO3037121","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to start=
 ,RCP Faulty //Bypass Grid and manually start of DG,","system","349","28-09=
-2024 06:05:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0003183260","Messassi=
","","28-09-2024 06:05:31","28-09-2024 05:59:42","28-09-2024 06:41:22","Cas=
caded Incident from TTO3037121","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to start =
,RCP Faulty //Bypass Grid and manually start of DG,","system","349","28-09-=
2024 06:05:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0003183261","Nkozoa",=
"","28-09-2024 06:05:31","28-09-2024 05:59:42","28-09-2024 06:41:22","Casca=
ded Incident from TTO3037121","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to start ,R=
CP Faulty //Bypass Grid and manually start of DG,","system","349","28-09-20=
24 06:05:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0003183262","Messassi=
 2","","28-09-2024 06:05:31","28-09-2024 05:59:42","28-09-2024 06:41:22","C=
ascaded Incident from TTO3037121","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to star=
t ,RCP Faulty //Bypass Grid and manually start of DG,","system","349","28-0=
9-2024 06:05:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0003183258","NKOLMEKO=
NG YDE","","28-09-2024 06:05:30","28-09-2024 05:59:42","28-09-2024 06:41:22=
","Cascaded Incident from TTO3037121","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to =
start ,RCP Faulty //Bypass Grid and manually start of DG,","system","348","=
28-09-2024 06:05:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0003183257","Ekombiti=
e","","28-09-2024 06:05:30","28-09-2024 05:59:42","28-09-2024 06:41:22","Ca=
scaded Incident from TTO3037121","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to start=
 ,RCP Faulty //Bypass Grid and manually start of DG,","system","348","28-09=
-2024 06:05:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0003183259","Olembe-T=
erminus","","28-09-2024 06:05:30","28-09-2024 05:59:42","28-09-2024 06:41:2=
2","Cascaded Incident from TTO3037121","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Bad voltage,DG failed to=
 start ,RCP Faulty //Bypass Grid and manually start of DG,","system","348",=
"28-09-2024 06:05:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003183241","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_280, IHS_YND_304","28-09-2024 06:02:51","28-09-2024 05:59:42","28-09-=
2024 06:41:22","Grid Bad voltage,DG failed to start ,RCP Faulty //Bypass Gr=
id and manually start of DG,","Fabrice Pouakam","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","Grid Bad voltage,DG failed t=
o start ,RCP Faulty //Bypass Grid and manually start of DG,","ange.kongo@ih=
stowers.com","190","28-09-2024 06:02:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0003183067","E=
vodoula OCM","","28-09-2024 05:08:43","28-09-2024 05:02:34","28-09-2024 05:=
03:34","Active//No power issue site and  with Ubaie=3D54.4 V site on Grid T=
he  FME TX Mouamadou/658791013 //From  is informed","TIENTCHEU NZETCHIEU GA=
EL","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue site and  with Ubaie=3D54.4 V site o=
n Grid The  FME TX Mouamadou/658791013 //From  is informed","ange.kongo@ihs=
towers.com","370","28-09-2024 05:08:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_694","IHS_YND_714","NOCINC0003183014","E=
kekam","","28-09-2024 04:50:43","28-09-2024 04:17:21","28-09-2024 04:18:21"=
,"Active//No power issue site and  with Ubaie=3D51.6 V site on Gen The  FME=
 TX Mouamadou/658791013 //From  is informed","TIENTCHEU NZETCHIEU GAEL","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue site and  with Ubaie=3D51.6 V site on Gen T=
he  FME TX Mouamadou/658791013 //From  is informed","ange.kongo@ihstowers.c=
om","2003","28-09-2024 04:50:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0003182263","E=
MANA BILICK CITY","","28-09-2024 01:22:45","28-09-2024 00:55:16","28-09-202=
4 01:27:26","Grid outage ,Site went down because Gen started and stopped wi=
th alarm""emergency stop""(alarm unprouven)//He reset Gen card and Gen maua=
lly started","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Grid outage ,Site went down because Gen started and sto=
pped with alarm""emergency stop""(alarm unprouven)//He reset Gen card and G=
en maually started","ange.kongo@ihstowers.com","1650","28-09-2024 01:22:45"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0649","IHS_YND_279","NOCINC0003182218","Mes=
sassi okolo","","28-09-2024 01:04:13","28-09-2024 00:55:45","28-09-2024 01:=
46:53","grid outade,site went down because gen start and stoppen with alarm=
 low oil pressure// He added oil pressure, site on gen ","Fabrice Pouakam",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","grid out=
ade,site went down because gen start and stoppen with alarm low oil pressur=
e// He added oil pressure, site on gen ","denis.mballa@ihstowers.com","1517=
","28-09-2024 01:04:13","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0003181837","Men=
dong3","","27-09-2024 23:23:59","27-09-2024 23:18:42","28-09-2024 09:02:36"=
,"Grid Outage No space to deploy a MDG waiting Grid Restored","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No sp=
ace to deploy a MDG //Grid Restored","denis.mballa@ihstowers.com","318","27=
-09-2024 23:23:59","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003181640","BAT=
A Mokolo OCM","","27-09-2024 22:49:14","27-09-2024 22:39:57","28-09-2024 09=
:22:23","Grid Outage,no space to deploy a mobile DG,waiting for grid restor=
ed//Grid restored.","","Grid Supply","Passive","Grid","National Grid - Grid=
 Outage Issue","Grid Outage,no space to deploy a mobile DG,waiting for grid=
 restored//Grid restored.","denis.mballa@ihstowers.com","558","27-09-2024 2=
2:49:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003181634","Melen Ba=
'aba","","27-09-2024 22:48:51","27-09-2024 22:40:28","27-09-2024 23:08:38",=
"Grid Outage,site went down before Gen start due to poor battery backup//Ge=
n started automatically","Siligap Boris","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid Outage,site went down before=
 Gen start due to poor battery backup//Gen started automatically","ange.kon=
go@ihstowers.com","504","27-09-2024 22:48:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003181516","C=
rf-Nsam","","27-09-2024 22:27:19","27-09-2024 22:24:14","28-09-2024 03:34:5=
4","Active// No power issue on site ,site on Grid with Ubaie=3D 53,4V The R=
M Alain /691144423/ Fom huawei is informed, Rpetitif issue","MINKA NICOLAS"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active// No power issue on site ,site on Grid with Ubaie=3D 53=
,4V The RM Alain /691144423/ Fom huawei is informed, Rpetitif issue","ange.=
kongo@ihstowers.com","186","27-09-2024 22:27:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003181488","S=
ous Prefecture","","27-09-2024 22:22:32","27-09-2024 22:09:26","28-09-2024 =
00:39:28","Active//No power isssue, site is on grid with Ubaie=3D53V, Lione=
l Tchatchoua(694693436) from Huawei is informed","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power isssue, site is on grid with Ubaie=3D53V, Lionel Tchatchou=
a(694693436) from Huawei is informed","ange.kongo@ihstowers.com","787","27-=
09-2024 22:22:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0003181256","M=
endong Maeture","","27-09-2024 21:52:55","27-09-2024 21:39:45","28-09-2024 =
07:48:53","(Access issue during the Night) : Technician is on site : Tx Iss=
ue: site on grid,Ubaie:56V; Disjunction in the BTS OCM , OSIAH MBA /699-69-=
-96-94 is informed.","Hyemafo Gildas","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","(Access issue during the =
Night) : Technician is on site : Tx Issue: site on grid,Ubaie:56V; Disjunct=
ion in the BTS OCM , OSIAH MBA /699-69--96-94 is informed.","etienne.itondo=
@ihstowers.com","791","27-09-2024 21:52:55","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0003181147","Jou=
vence Mbenda","","27-09-2024 21:35:52","27-09-2024 21:04:40","27-09-2024 21=
:38:56","Grid outage Site went down because Gen stopped due to ""high temp"=
" alarm //He added water and gen manually started","Hyemafo Gildas","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Grid outage Site went down because Gen stopped due to ""high temp"" =
alarm //He added water and gen manually started","olivier.kwedi@ihstowers.c=
om","1872","27-09-2024 21:35:52","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003181057","Nom=
ayos montee Meche","","27-09-2024 21:22:19","27-09-2024 21:03:13","05-11-20=
24 18:40:42","Access issue due to Landlord( site went down due  to  landlor=
d has forbiden to start the Gen Because  the  Noise //Grid Restored)","Fand=
a Brice","Access Denial","Lease Or Legal","Landlord Related Issues","Access=
 Issue - Land Lord","Access issue due to Landlord( site went down due  to  =
landlord has forbiden to start the Gen Because  the  Noise //Grid Restored)=
","olivier.kwedi@ihstowers.com","1147","27-09-2024 21:22:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003180770","F=
ebe Village","","27-09-2024 20:47:25","27-09-2024 20:43:18","27-09-2024 21:=
22:22"," No power issue, site is on Grid with  the fme tx  Mohamadou (69114=
4135) from Huawei is informed and Up at 09:02 PM","Mboua Thierry","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
"," No power issue, site is on Grid with  the fme tx  Mohamadou (691144135)=
 from Huawei is informed and Up at 09:02 PM","ludivine.ngamaleu@ihstowers.c=
om","248","27-09-2024 20:47:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0003180504","N=
gousso-II","","27-09-2024 20:13:11","27-09-2024 20:01:59","27-09-2024 21:39=
:04","No power issue, site is on grid with Ubaie=3D53,7V, the fme tx Armand=
 Nguetsa(699949553) from Huawei is informed. Notice that we have disjunctio=
n at BTS OCM","MFOUAGUEGUE MATHIEU","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on =
grid with Ubaie=3D53,7V, the fme tx Armand Nguetsa(699949553) from Huawei i=
s informed. Notice that we have disjunction at BTS OCM","etienne.itondo@ihs=
towers.com","673","27-09-2024 20:13:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003180411","MEHANDAN=
","","27-09-2024 19:56:50","27-09-2024 19:47:03","27-09-2024 19:51:10","Cas=
caded Incident from TTO3034327","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se gen start and stopped due to grid bad voltage and poor battery backup// =
He bypass grid and manually start the gen","system","587","27-09-2024 19:56=
:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003180374","O=
dza II OCM","IHS_YND_528","27-09-2024 19:50:14","27-09-2024 19:47:03","27-0=
9-2024 19:51:10","Grid fluctuation, site went down because gen start and st=
opped due to grid bad voltage and poor battery backup// He bypass grid and =
manually start the gen","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid fluctuation, site went down b=
ecause gen start and stopped due to grid bad voltage and poor battery backu=
p// He bypass grid and manually start the gen","ludivine.ngamaleu@ihstowers=
.com","192","27-09-2024 19:50:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003180300","C=
amp-Sic-Tsinga","","27-09-2024 19:39:08","27-09-2024 19:36:03","27-09-2024 =
19:39:31","Grid outage no space to deploy MDG// Grid restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no s=
pace to deploy MDG// Grid restored","ludivine.ngamaleu@ihstowers.com","186"=
,"27-09-2024 19:39:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003180199","M=
ontee-Jouvence-II","","27-09-2024 19:20:39","27-09-2024 19:06:32","27-09-20=
24 20:54:35","Grid Outage, Site went down due to Gen overload (15KVA, 200A)=
// He reduced the load","Hyemafo Gildas","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Overload","Grid Outage, Site went down due to Gen overload (1=
5KVA, 200A)// He reduced the load","etienne.itondo@ihstowers.com","848","27=
-09-2024 19:20:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003179527","N=
sam Sofavinc T0","","27-09-2024 17:55:41","27-09-2024 17:46:35","27-09-2024=
 18:48:39","Site went down due to work Pascaline/Supervisor IHS/ working on=
 site ""Put a second CB in DC Box""// End of work","MINKA NICOLAS","Install=
ation Activity","Passive","Planned Activity","Installation Activity","Site =
went down due to work Pascaline/Supervisor IHS/ working on site ""Put a sec=
ond CB in DC Box""// End of work","ludivine.ngamaleu@ihstowers.com","546","=
27-09-2024 17:55:41","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003179366","BAT=
A Mokolo OCM","","27-09-2024 17:29:19","27-09-2024 17:22:08","27-09-2024 18=
:30:14","Grid outage no space to deploy MDG // Grid Power return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage n=
o space to deploy MDG // Grid Power return","olivier.kwedi@ihstowers.com","=
432","27-09-2024 17:29:19","Sagemcom CMR"
"Closed Complete","Warning","T0033","IHS_YND_167","NOCINC0003179079","Touri=
ng Club International","","27-09-2024 16:58:13","","","Site alarming due to=
 work Technician SS Willy kamga /656 07 26 30  /IS working on site (Audi)//=
 End of work","Albran Byorel","Warning","Warning","POWER","Warning - Site o=
n Battery","Site alarming due to work Technician SS Willy kamga /656 07 26 =
30  /IS working on site (Audi)// End of work","dorothy.djantio@ihstowers.co=
m","186","27-09-2024 16:58:13","Sagemcom CMR"
"Closed Complete","Site Down","T3150","IHS_YND_214","NOCINC0003179047","Nko=
lmesseng-II","","27-09-2024 16:54:29","27-09-2024 16:49:23","27-09-2024 17:=
52:39","CB ENEO down due to lightning (damaged eneo meter), site went down =
because Gen ran and till shortage// Refueling done","Siligap Boris","Fuel O=
utage","Passive","Diesel","Diesel Outage","CB ENEO down due to lightning (d=
amaged eneo meter), site went down because Gen ran and till shortage// Refu=
eling done","olivier.kwedi@ihstowers.com","513","27-09-2024 16:54:29","Sage=
mcom CMR"
"Closed Complete","Warning","T0322","IHS_YND_312","NOCINC0003178719","Nkoln=
da","","27-09-2024 16:17:10","","","low voltage","Albran Byorel","Warning",=
"Warning","POWER","Warning - Site on Battery","Grid outage, site went alarm=
 before gen start // gen start automatically","dorothy.djantio@ihstowers.co=
m","215","27-09-2024 16:17:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003178624","N=
gouetou","","27-09-2024 16:04:55","27-09-2024 15:56:49","27-09-2024 21:47:4=
5","No power issue on site ,site on Gen with Ubaie=3D52V, Tx Fme Gregoire( =
652070658)From Huawei is informed and Up at 04:11PM","Parker Tchoup","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue on site ,site on Gen with Ubaie=3D52V, Tx Fme Gregoire=
( 652070658)From Huawei is informed and Up at 04:11PM","ludivine.ngamaleu@i=
hstowers.com","487","27-09-2024 16:04:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003178587","O=
dza II OCM","IHS_YND_528","27-09-2024 16:01:26","27-09-2024 15:51:59","27-0=
9-2024 16:53:34","Grid fluctuation, site went down because gen start and st=
opped due to grid bad voltage no rcp on site // He bypass grid and manually=
 start the gen","Albran Byorel","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","Grid fluctuation, site went down because gen=
 start and stopped due to grid bad voltage no rcp on site // He bypass grid=
 and manually start the gen","ludivine.ngamaleu@ihstowers.com","569","27-09=
-2024 16:01:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003178556","M=
EHANDAN","","27-09-2024 15:59:31","27-09-2024 15:51:59","27-09-2024 16:53:3=
4","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid fluctuation, site went down because gen start and stopped d=
ue to grid bad voltage no rcp on site // He bypass grid and manually start =
the gen","ludivine.ngamaleu@ihstowers.com","658","27-09-2024 15:59:31","Sag=
emcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0003178065","Eto=
ug ebe biscuiterie","","27-09-2024 14:57:53","27-09-2024 14:45:44","27-09-2=
024 15:22:55","Grid fluctuation, site went down because gen start and stopp=
ed due to grid bad voltage no crp on site // Grid stabilized","Hyemafo Gild=
as","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage no crp on site // Grid stabilized","olivier.kwedi@ihstowers.=
com","729","27-09-2024 14:57:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003177894","K=
oweit City","","27-09-2024 14:37:42","27-09-2024 14:32:38","27-09-2024 19:0=
2:38","No power issue on site Ubai: 54,5 V site on Grid. TX FME Leonel Stev=
e   (655184876) from Huawei is informed","Albran Byorel","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site Ubai: 54,5 V site on Grid. TX FME Leonel Steve   (65518487=
6) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","305","27-09-=
2024 14:37:42","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003177891","Jou=
vence 2000","","27-09-2024 14:37:09","27-09-2024 14:32:57","27-09-2024 16:5=
9:31","No power issue site on GEN with U=3D54 V The Tx Fme Armand Ngetsa/69=
1144412 from Huawei is informed and Up at 02:46 PM","Delor Telezing","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","No power issue site on GEN with U=3D54 V The Tx Fme Armand Ngetsa/691=
144412 from Huawei is informed and Up at 02:46 PM","olivier.kwedi@ihstowers=
.com","253","27-09-2024 14:37:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003177571","O=
lembe-Terminus","","27-09-2024 13:40:47","27-09-2024 13:33:43","27-09-2024 =
21:43:53","Active//No power issue on site U=3D54,9V site on Gen  and Synpho=
rien /691316854/ of huawei is informed","Fabrice Pouakam","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e//No power issue on site U=3D54,9V site on Gen  and Synphorien /691316854/=
 of huawei is informed","alexandre.kamal@ihstowers.com","425","27-09-2024 1=
3:40:47","Sagemcom CMR"
"Closed Complete","Warning","T1449","IHS_YND_692","NOCINC0003177538","Mendo=
ng vallee","","27-09-2024 13:36:56","","","Site alarming because Grid outag=
e// Gen Manually started (investigation ongoing )and alarm cleared ","Fanda=
 Brice","Warning","Warning","POWER","Warning - Site on Battery","Site alarm=
ing because Grid outage// Gen Manually started (investigation ongoing )and =
alarm cleared ","ludovic.tchagna@ihstowers.com","7","27-09-2024 13:36:56","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003177487","M=
fou EPC","","27-09-2024 13:31:28","27-09-2024 13:22:24","27-09-2024 13:42:0=
9","site went down due to work","Mba Lazare Herve","Installation Activity",=
"Passive","Planned Activity","Installation Activity","Site down due to work=
 of Alphonse (IHS) and Willy (SAGEMCOM)//end of work","alexandre.kamal@ihst=
owers.com","545","27-09-2024 13:31:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003177453","M=
EFOU ASSI","","27-09-2024 13:27:43","27-09-2024 13:21:29","27-09-2024 13:51=
:59","site went down due to work( Patrick essa(657108540) from ZTE and ZTE =
working on site)// en of work","Fanda Brice","Equipment Replacement","Passi=
ve","Planned Activity","Planned Activity - Passive","site went down due to =
work( Patrick essa(657108540) from ZTE and ZTE working on site)// en of wor=
k","alexandre.kamal@ihstowers.com","376","27-09-2024 13:27:43","Sagemcom CM=
R"
"Closed Complete","Warning","T0370","IHS_YND_227","NOCINC0003177354","Mvog =
Betsi","","27-09-2024 13:10:30","","","site alarming because Grid outage //=
 Gen automatically started and alarm cleared","Hyemafo Gildas","Warning","W=
arning","POWER","Warning - Site on Battery","site alarming because Grid out=
age // Gen automatically started and alarm cleared","ludovic.tchagna@ihstow=
ers.com","312","27-09-2024 13:10:30","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003177309","Nko=
lnda","","27-09-2024 13:02:12","27-09-2024 11:54:35","27-09-2024 12:28:58",=
"","Albran Byorel","Installation Activity","Passive","Planned Activity","In=
stallation Activity","Site down due to PM of Albran(SAGEMCOM)//end of work"=
,"kamga.virgile@ihstowers.com","4058","27-09-2024 13:02:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003177287","M=
ontee-Des-Soeurs","","27-09-2024 12:58:03","27-09-2024 12:47:57","27-09-202=
4 13:19:24","Grid outage Site went down because Gen stopped due to ""high t=
emp"" alarm //He added water and gen manually started","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Grid outage Site went down because Gen stopped due to ""high tem=
p"" alarm //He added water and gen manually started","alexandre.kamal@ihsto=
wers.com","607","27-09-2024 12:58:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003177267","S=
ous Prefecture","","27-09-2024 12:55:02","27-09-2024 12:47:59","27-09-2024 =
12:57:54","No power isssue, site is on grid with Ubaie=3D53V, Rm Alain (691=
144423) from Huawei is informed","Fanda Brice","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power isssue,=
 site is on grid with Ubaie=3D53V, Rm Alain (691144423) from Huawei is info=
rmed","alexandre.kamal@ihstowers.com","424","27-09-2024 12:55:02","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003177111","M=
EHANDAN","","27-09-2024 12:26:01","27-09-2024 12:14:50","27-09-2024 13:26:1=
0","Grid Outage, site went down because Gen failed to start due to AVR dysf=
onction //he set AVR","Albran Byorel","Equipment Repair","Passive","ACDG Ge=
n","ACDG - AVR","Grid Outage, site went down because Gen failed to start du=
e to AVR dysfonction //he set AVR","alexandre.kamal@ihstowers.com","672","2=
7-09-2024 12:26:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003176881","ELOUMDEM=
 CARRIERE","","27-09-2024 11:50:41","27-09-2024 11:16:03","27-09-2024 11:48=
:40","Cascaded Incident from TTO3030752","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage  site down due to p=
oor backup before gen start // Grid return","system","2078","27-09-2024 11:=
50:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003176883","Afanoya"=
,"","27-09-2024 11:50:41","27-09-2024 11:16:03","27-09-2024 11:48:40","Casc=
aded Incident from TTO3030752","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage  site down due to poor bac=
kup before gen start // Grid return","system","2078","27-09-2024 11:50:41",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003176882","MBALNGON=
G LYCEE","","27-09-2024 11:50:41","27-09-2024 11:16:03","27-09-2024 11:48:4=
0","Cascaded Incident from TTO3030752","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage  site down due to poo=
r backup before gen start // Grid return","system","2078","27-09-2024 11:50=
:41","Sagemcom CMR"
"Cancelled","Warning","T1557","IHS_YND_313","NOCINC0003176858","Afanoya",""=
,"27-09-2024 11:46:55","","","","Hyemafo Gildas","","","","","","kamga.virg=
ile@ihstowers.com","1811","27-09-2024 11:46:55","Sagemcom CMR"
"Closed Complete","Site Down","T0526","IHS_YND_088","NOCINC0003176808","Elo=
bi Mokolo","","27-09-2024 11:38:57","27-09-2024 11:32:13","27-09-2024 11:54=
:45","site was on gen due to grid outage, gen stopped by neighbors//grid re=
turn","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Contr=
ol Panel","site was on gen due to grid outage, gen stopped by neighbors//gr=
id return
","kamga.virgile@ihstowers.com","405","27-09-2024 11:38:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003176726","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","27-09-2024 11:28:14","27-09-=
2024 11:16:03","27-09-2024 11:48:40","Grid outage  site down due to poor ba=
ckup before gen start // Grid return","Hyemafo Gildas","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage  site d=
own due to poor backup before gen start // Grid return","alexandre.kamal@ih=
stowers.com","2069","27-09-2024 11:28:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003176454","MEHANDAN=
","","27-09-2024 10:46:30","27-09-2024 10:39:48","27-09-2024 10:53:41","Cas=
caded Incident from TTO3030296","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage  site went down before gen=
 started due to poor backup//Gen  started ","system","402","27-09-2024 10:4=
6:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003176433","O=
dza II OCM","IHS_YND_528","27-09-2024 10:43:07","27-09-2024 10:39:48","27-0=
9-2024 10:53:41","","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","grid outage  site went down before gen=
 started due to poor backup//Gen  started ","alexandre.kamal@ihstowers.com"=
,"201","27-09-2024 10:43:07","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003176317","Jou=
vence 2000","","27-09-2024 10:27:55","27-09-2024 10:02:35","27-09-2024 11:3=
1:27","on site","Delor Telezing","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","site down due to poor backup  before  gen=
 start and PWC off//gen started","kamga.virgile@ihstowers.com","1521","27-0=
9-2024 10:27:55","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0003176229","Lob=
o 2","","27-09-2024 10:15:17","27-09-2024 09:37:04","27-09-2024 12:45:55","=
ETA=3D11:20","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG =
Gen","ACDG - Control Panel","site down because gen stopped with alarm over =
voltage//reset gen card, under observation","kamga.virgile@ihstowers.com","=
2294","27-09-2024 10:15:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0003176051","B=
astos Ekoudou","","27-09-2024 09:56:39","27-09-2024 09:33:33","27-09-2024 1=
1:59:42","Site was on Gen due Grid outage, Site went down because Gen stopp=
ed due to ""high temp"" alarm //He added water and gen manually started","M=
boua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine T=
emp - Coolant Level Issue","Grid outage Site went down because Gen stopped =
due to ""high temp"" alarm and poor battery backup //He added water and gen=
 manually started","alexandre.kamal@ihstowers.com","1387","27-09-2024 09:56=
:39","Sagemcom CMR"
"Closed Complete","Warning","T0351","IHS_YND_146","NOCINC0003175998","Nsime=
yong","","27-09-2024 09:45:30","","","Visite conjointe avec Huawei","MINKA =
NICOLAS","Warning","Warning","POWER","Warning - Site on Battery","Visite co=
njointe between Pascaline and Sagemcom.","ludovic.tchagna@ihstowers.com","3=
08","27-09-2024 09:45:30","Sagemcom CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0003175885","Eto=
ug-Ebe 2","","27-09-2024 09:28:53","27-09-2024 08:59:15","27-09-2024 14:15:=
09","Grid outage no space to deploy MDG// Grid Power return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spa=
ce to deploy MDG// Grid Power return","kamga.virgile@ihstowers.com","1779",=
"27-09-2024 09:28:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0003175872","M=
endong Maeture","","27-09-2024 09:25:38","27-09-2024 09:19:29","27-09-2024 =
09:59:17","site went down due to work(achile fotso(690854375)/pro service, =
swap PWC)// End of work","Hyemafo Gildas","Equipment Replacement","Passive"=
,"Planned Activity","Planned Activity - Passive","site went down due to wor=
k(achile fotso(690854375)/pro service, swap PWC)// End of work","alexandre.=
kamal@ihstowers.com","370","27-09-2024 09:25:38","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0003175058","AKA=
K Nkozoa","","27-09-2024 06:51:53","27-09-2024 06:41:40","27-09-2024 08:23:=
21","site went down because disjunction CB(125A) due to cable burnt in pwc/=
/ He normalized cable and reamed CB(125A), site on gen","Fabrice Pouakam","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breake=
r Issue","site went down because disjunction CB(125A) due to cable burnt in=
 pwc// He normalized cable and reamed CB(125A), site on gen","kamga.virgile=
@ihstowers.com","614","27-09-2024 06:51:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0003174923","B=
astos Ekoudou","","27-09-2024 06:25:01","27-09-2024 06:03:57","27-09-2024 0=
8:11:54","Grid outage Site went down because Gen stopped due to ""high temp=
"" alarm and poor battery backup //He added water and gen manually started"=
,"Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - High Engin=
e Temp - Coolant Level Issue","Grid outage Site went down because Gen stopp=
ed due to ""high temp"" alarm and poor battery backup //He added water and =
gen manually started","alexandre.kamal@ihstowers.com","1265","27-09-2024 06=
:25:01","Sagemcom CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0003174230","MEH=
ANDAN","","27-09-2024 03:05:23","27-09-2024 02:58:16","27-09-2024 03:51:49"=
,"Grid fluctuation, site went down because gen start and stopped due to gri=
d bad voltage // he bypass grid and manually start the gen","Albran Byorel"=
,"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","=
Grid fluctuation, site went down because gen start and stopped due to grid =
bad voltage // he bypass grid and manually start the gen","joelle.ekessi@ih=
stowers.com","712","27-09-2024 03:05:23","Sagemcom CMR"
"Closed Complete","Site Down","T1111","IHS_YND_118","NOCINC0003174180","ESS=
OS OASIS 1111","","27-09-2024 02:46:00","27-09-2024 02:44:55","27-09-2024 0=
4:10:26","site went down because the Cb(63A)of energy meter dysjoncted due =
to lightning// He reamed the cb","Siligap Boris","Grid Supply","Passive","G=
rid","National Grid - Circuit Breaker","site went down because the Cb(63A)o=
f energy meter dysjoncted due to lightning// He reamed the cb","joelle.ekes=
si@ihstowers.com","66","27-09-2024 02:46:00","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003174080","Nko=
lmvack","","27-09-2024 02:21:08","27-09-2024 02:20:02","27-09-2024 05:30:28=
","site went down because gen start and stoppen with alarm low oil pressure=
// He added oil pressure, site on gen","Parker Tchoup","Fuel Outage","Passi=
ve","Diesel","Diesel Outage","site went down because gen start and stoppen =
with alarm low oil pressure// He added oil pressure, site on gen","joelle.e=
kessi@ihstowers.com","66","27-09-2024 02:21:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003174015","MEHANDAN=
","","27-09-2024 01:56:20","27-09-2024 01:53:45","27-09-2024 02:43:11","Cas=
caded Incident from TTO3027770","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, site went down before Gen=
 start due to poor backup// Gen started automatically","system","155","27-0=
9-2024 01:56:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003174010","O=
dza II OCM","IHS_YND_528","27-09-2024 01:54:51","27-09-2024 01:53:45","27-0=
9-2024 02:43:11","Grid Outage, site went down before Gen start due to poor =
backup// Gen started manually","Albran Byorel","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid Outage, site went down=
 before Gen start due to poor backup// Gen started manually","emmanuel.ghan=
i@ihstowers.com","67","27-09-2024 01:54:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003173952","A=
KONGO","","27-09-2024 01:37:23","27-09-2024 01:35:12","27-09-2024 02:06:06"=
,"Active:  No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rod=
rigue (655102999)from Huawei is informed. Repetitive issue ","Fanda Brice",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active:  No power issue on site Ubaie=3D52,5V site on Gen. The =
Tx FME Rodrigue (655102999)from Huawei is informed. Repetitive issue ","emm=
anuel.ghani@ihstowers.com","132","27-09-2024 01:37:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003173847","E=
ssomba","","27-09-2024 01:11:28","27-09-2024 01:09:10","27-09-2024 01:40:28=
","Site went down because the Cb(32A) of rectifier dysjoncted// the reamed =
the Cb","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Circuit Breaker Issue","Site went down because the Cb(32A) of=
 rectifier dysjoncted// the reamed the Cb","emmanuel.ghani@ihstowers.com","=
139","27-09-2024 01:11:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0003173750","Carrefou=
rt Nkomo","","27-09-2024 00:31:00","27-09-2024 00:26:06","27-09-2024 01:05:=
44","Cascaded Incident from TTO3027476","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went=
 down because gen start and stopped due to grid bad voltage // he bypass gr=
id and manually start the gen","system","294","27-09-2024 00:31:00","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0003173741","N=
komo","IHS_YND_174","27-09-2024 00:28:21","27-09-2024 00:26:06","27-09-2024=
 01:05:44","Grid fluctuation, site went down because gen start and stopped =
due to grid bad voltage // he bypass grid and manually start the gen","Mba =
Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation, site went down because gen start and stopped=
 due to grid bad voltage // he bypass grid and manually start the gen","emm=
anuel.ghani@ihstowers.com","136","27-09-2024 00:28:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003173628","Ngoum","=
","26-09-2024 23:55:41","26-09-2024 23:50:11","27-09-2024 02:54:33","Cascad=
ed Incident from TTO3027359","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because Gen started and st=
opped due to hybrid system dysfonction// He reset the system hybride","syst=
em","330","26-09-2024 23:55:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003173632","Yoko MTN=
","","26-09-2024 23:55:41","26-09-2024 23:50:11","27-09-2024 02:54:33","Cas=
caded Incident from TTO3027359","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because Gen started and=
 stopped due to hybrid system dysfonction// He reset the system hybride","s=
ystem","330","26-09-2024 23:55:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003173630","Donga","=
","26-09-2024 23:55:41","26-09-2024 23:50:11","27-09-2024 02:54:33","Cascad=
ed Incident from TTO3027359","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because Gen started and st=
opped due to hybrid system dysfonction// He reset the system hybride","syst=
em","330","26-09-2024 23:55:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003173631","Dong",""=
,"26-09-2024 23:55:41","26-09-2024 23:50:11","27-09-2024 02:54:33","Cascade=
d Incident from TTO3027359","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","site went down because Gen started and sto=
pped due to hybrid system dysfonction// He reset the system hybride","syste=
m","330","26-09-2024 23:55:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003173629","Ngouetou=
","","26-09-2024 23:55:41","26-09-2024 23:50:11","27-09-2024 02:54:33","Cas=
caded Incident from TTO3027359","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because Gen started and=
 stopped due to hybrid system dysfonction// He reset the system hybride","s=
ystem","330","26-09-2024 23:55:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003173626","MBIMBIM"=
,"","26-09-2024 23:55:40","26-09-2024 23:50:11","27-09-2024 02:54:33","Casc=
aded Incident from TTO3027359","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site went down because Gen started and =
stopped due to hybrid system dysfonction// He reset the system hybride","sy=
stem","329","26-09-2024 23:55:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003173627","Matsari"=
,"","26-09-2024 23:55:40","26-09-2024 23:50:11","27-09-2024 02:54:33","Casc=
aded Incident from TTO3027359","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site went down because Gen started and =
stopped due to hybrid system dysfonction// He reset the system hybride","sy=
stem","329","26-09-2024 23:55:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003173625","Nguila",=
"","26-09-2024 23:55:40","26-09-2024 23:50:11","27-09-2024 02:54:33","Casca=
ded Incident from TTO3027359","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site went down because Gen started and s=
topped due to hybrid system dysfonction// He reset the system hybride","sys=
tem","329","26-09-2024 23:55:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0003173624","E=
koumdoum","","26-09-2024 23:54:58","26-09-2024 23:54:52","27-09-2024 00:47:=
00","Grid fluctuation site went down because Gen failed to start due to Gri=
d bad voltage// Grid stabilized","Albran Byorel","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Grid fluctuation site went =
down because Gen failed to start due to Grid bad voltage// Grid stabilized"=
,"emmanuel.ghani@ihstowers.com","7","26-09-2024 23:54:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0003173606","O=
ssombe","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, I=
HS_YND_434, IHS_YND_444, IHS_YND_473","26-09-2024 23:49:16","26-09-2024 23:=
45:11","27-09-2024 02:54:33","site went down because Gen started and stoppe=
d due to hybrid system dysfonction// He reset the system hybride","Parker T=
choup","Equipment Repair","Passive","Hybrid","Hybrid Module","site went dow=
n because Gen started and stopped due to hybrid system dysfonction// He res=
et the system hybride","emmanuel.ghani@ihstowers.com","246","26-09-2024 23:=
49:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0003173435","M=
endong Maeture","","26-09-2024 23:06:35","26-09-2024 23:04:29","27-09-2024 =
03:55:10","Site went down due to work Technician Fotso Achile / 690854375/ =
pro service  IS working on site (Swap the PWC)// End of work","Hyemafo Gild=
as","Equipment Replacement","Passive","Planned Activity","Planned Activity =
- Passive","Site went down due to work Technician Fotso Achile / 690854375/=
 pro service  IS working on site (Swap the PWC)// End of work","emmanuel.gh=
ani@ihstowers.com","127","26-09-2024 23:06:35","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0003173319","Nko=
zoa","","26-09-2024 22:45:28","26-09-2024 22:40:23","26-09-2024 23:00:42","=
Grid bad voltage,Site went down because Gen failed to start due to Gen over=
load(20KVA,320)// Grid return","Fabrice Pouakam","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid bad voltage,Site went down because Ge=
n failed to start due to Gen overload(20KVA,320)// Grid return","joelle.eke=
ssi@ihstowers.com","355","26-09-2024 22:45:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0003172738","E=
mombo","","26-09-2024 21:38:56","26-09-2024 21:34:48","26-09-2024 22:09:13"=
,"Site went down due to CB(32A) Gen dysjunted // he rehamed the CB and site=
 up","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Loa=
d Breaker","Site went down due to CB(32A) Gen dysjunted // he rehamed the C=
B and site up","ange.kongo@ihstowers.com","248","26-09-2024 21:38:56","Sage=
mcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0003172571","Nko=
zoa","","26-09-2024 21:31:40","26-09-2024 21:15:26","26-09-2024 21:52:26","=
Grid Outage,Site went down because Gen failed to start due to Gen overload(=
20KVA,320)//he load on site and started GEN","Fabrice Pouakam","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid Outage,Site went down b=
ecause Gen failed to start due to Gen overload(20KVA,320)//he load on site =
and started GEN","denis.mballa@ihstowers.com","975","26-09-2024 21:31:40","=
Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003172532","BAT=
A Mokolo OCM","","26-09-2024 21:28:47","26-09-2024 21:15:34","27-09-2024 09=
:05:07","Grid outage no space to deploy awaiting Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy  mobil gen // Grid return","denis.mballa@ihstowers.com","794"=
,"26-09-2024 21:28:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0003172027","B=
astos Ekoudou","","26-09-2024 20:36:31","26-09-2024 20:03:40","26-09-2024 2=
1:44:06","Grid fluctuation, site went down because gen start and stopped du=
e to Grid bad voltage // he bypass Grid and manually start the Gen","Mboua =
Thierry","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation, site went down because gen start and stopped due =
to Grid bad voltage // he bypass Grid and manually start the Gen","ange.kon=
go@ihstowers.com","1972","26-09-2024 20:36:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003171987","M=
imboman-Ecole","","26-09-2024 20:28:51","26-09-2024 20:14:45","26-09-2024 2=
2:22:09","site went down because Gen started and stopped with alarm low oil=
 pressure// He reset the Gen card and Gen manually started","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","site we=
nt down because Gen started and stopped with alarm low oil pressure// He re=
set the Gen card and Gen manually started","ange.kongo@ihstowers.com","847"=
,"26-09-2024 20:28:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003171798","ELOUMDEM=
 CARRIERE","","26-09-2024 20:17:51","26-09-2024 19:35:51","26-09-2024 20:33=
:51","Cascaded Incident from TTO3025483","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, Site went down bec=
ause Gen Overload (20kva,330A)//He reduced the load and started Gen manualy=
","system","2520","26-09-2024 20:17:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003171800","Afanoya"=
,"","26-09-2024 20:17:51","26-09-2024 19:35:51","26-09-2024 20:33:51","Casc=
aded Incident from TTO3025483","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, Site went down because Ge=
n Overload (20kva,330A)//He reduced the load and started Gen manualy","syst=
em","2520","26-09-2024 20:17:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003171799","MBALNGON=
G LYCEE","","26-09-2024 20:17:51","26-09-2024 19:35:51","26-09-2024 20:33:5=
1","Cascaded Incident from TTO3025483","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, Site went down becau=
se Gen Overload (20kva,330A)//He reduced the load and started Gen manualy",=
"system","2520","26-09-2024 20:17:51","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003171795","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","26-09-2024 20:17:04","26-09-20=
24 19:35:46","26-09-2024 20:33:51","Grid Outage, Site went down because Gen=
 Overload (20kva,330A)//He reduced the load and started Gen manualy","Hyema=
fo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
Outage, Site went down because Gen Overload (20kva,330A)//He reduced the lo=
ad and started Gen manualy","denis.mballa@ihstowers.com","5487","26-09-2024=
 20:17:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003171349","M=
ambine","","26-09-2024 19:34:04","26-09-2024 19:20:54","26-09-2024 20:22:54=
","Grid outage, site went down because gen ran untill fuel shortage // refu=
eling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran untill fuel shortage // refuel=
ing done","ange.kongo@ihstowers.com","791","26-09-2024 19:34:04","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003171267","A=
wae Escalier","","26-09-2024 19:31:17","26-09-2024 19:23:06","26-09-2024 20=
:11:06","Grid outage, site went down before gen start due to poor battery b=
ackup // gen start automatically","Albran Byorel","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // gen start automatically"=
,"ange.kongo@ihstowers.com","492","26-09-2024 19:31:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003171250","N=
koabang2","","26-09-2024 19:30:11","26-09-2024 19:21:00","26-09-2024 19:39:=
00","Grid outage, site went went down due to gen overload(16Kva, 210A)) // =
Grid return","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","AC=
DG - Overload","Grid outage, site went went down due to gen overload(16Kva,=
 210A)) // Grid return","ange.kongo@ihstowers.com","552","26-09-2024 19:30:=
11","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003171110","MIM=
BOMAN LIBERTE","","26-09-2024 19:27:59","26-09-2024 19:25:02","26-09-2024 1=
9:47:02","Grid outage site went down because Gen started and stopped with a=
larm Gen under voltage//he Reset the Gen Card and Manually Started the Gen"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","Grid outage site went down because Gen started and stopped with al=
arm Gen under voltage//he Reset the Gen Card and Manually Started the Gen",=
"denis.mballa@ihstowers.com","494","26-09-2024 19:27:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003171099","MEHANDAN=
","","26-09-2024 19:27:00","26-09-2024 19:17:08","26-09-2024 19:20:08","Cas=
caded Incident from TTO3024687","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // gen start automatically","system","592=
","26-09-2024 19:27:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_281","NOCINC0003171060","Odza II"=
,"IHS_YND_528","26-09-2024 19:24:18","26-09-2024 19:17:08","26-09-2024 19:2=
0:08","Grid outage, site went down before gen start due to poor battery bac=
kup // gen start automatically","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // gen start automatically","=
ange.kongo@ihstowers.com","432","26-09-2024 19:24:18","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0003170886","Jou=
vence Mbenda","","26-09-2024 19:17:54","26-09-2024 19:11:37","26-09-2024 20=
:02:09","Site was on Gen due to Grid Outage, site went down because Gen sto=
pped due to ""high temp"" alarm //He added water and gen manually started",=
"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engin=
e Temp - Coolant Level Issue","Site was on Gen due to Grid Outage, site wen=
t down because Gen stopped due to ""high temp"" alarm //He added water and =
gen manually started","denis.mballa@ihstowers.com","378","26-09-2024 19:17:=
54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003170734","M=
essa-Carriere OCM","","26-09-2024 19:14:39","26-09-2024 19:01:23","26-09-20=
24 21:05:23","Grid outage no space to deploy // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spa=
ce to deploy // Grid return","ange.kongo@ihstowers.com","798","26-09-2024 1=
9:14:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003170708","S=
OA UNIVERSITY STADIUM","","26-09-2024 19:12:54","26-09-2024 18:59:46","27-0=
9-2024 19:13:35","Tx Issue : Site on Grid,Ubaie:54.2V; There was Huge rain =
in the Center area. Symphorien/675-29-52-05 has been informed.","Siligap Bo=
ris","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Tx Issue : Site on Grid,Ubaie:54.2V; There was Huge rain i=
n the Center area. Symphorien/675-29-52-05 has been informed.","ange.kongo@=
ihstowers.com","789","26-09-2024 19:12:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003169821","C=
rf-Nsam","","26-09-2024 18:27:55","26-09-2024 18:27:50","26-09-2024 18:28:5=
0","Active// No power issue on site ,site on Grid with Ubaie=3D 53,4V The R=
M Alain /691144423/ Fom huawei is informed and up at 06:30 PM","MINKA NICOL=
AS","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// No power issue on site ,site on Grid with Ubaie=3D=
 53,4V The RM Alain /691144423/ Fom huawei is informed and up at 06:30 PM",=
"ange.kongo@ihstowers.com","6","26-09-2024 18:27:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003169667","E=
lobi Mokolo","","26-09-2024 17:58:31","26-09-2024 17:54:25","26-09-2024 18:=
32:57","Grid outage, Gen start and stopped due to alarm emergency button st=
op//he bypassed the button, reset card and started Gen","Mboua Thierry","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, G=
en start and stopped due to alarm emergency button stop//he bypassed the bu=
tton, reset card and started Gen","ange.kongo@ihstowers.com","246","26-09-2=
024 17:58:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003169471","MBALNGON=
G LYCEE","","26-09-2024 17:45:25","26-09-2024 17:39:51","26-09-2024 17:55:5=
1","Cascaded Incident from TTO3023041","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // gen start automatically","system"=
,"334","26-09-2024 17:45:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003169470","ELOUMDEM=
 CARRIERE","","26-09-2024 17:45:25","26-09-2024 17:39:51","26-09-2024 17:55=
:51","Cascaded Incident from TTO3023041","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // gen start automatically","syste=
m","334","26-09-2024 17:45:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003169472","Afanoya"=
,"","26-09-2024 17:45:25","26-09-2024 17:39:51","26-09-2024 17:55:51","Casc=
aded Incident from TTO3023041","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // gen start automatically","system","334=
","26-09-2024 17:45:25","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003169436","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","26-09-2024 17:43:04","26-09-20=
24 17:39:14","26-09-2024 17:55:51","Grid outage, site went down before gen =
start due to poor battery backup // gen start automatically","Hyemafo Gilda=
s","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid outage, site went down before gen start due to poor battery backup=
 // gen start automatically","denis.mballa@ihstowers.com","432","26-09-2024=
 17:43:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0003168956","N=
omayos","","26-09-2024 17:21:23","26-09-2024 17:19:17","26-09-2024 17:45:17=
","Grid outage, site went down because gen ran untill fuel shortage // refu=
eling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran untill fuel shortage // refuel=
ing done","ange.kongo@ihstowers.com","127","26-09-2024 17:21:23","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003168890","Ngoum","=
","26-09-2024 17:19:21","26-09-2024 17:06:43","26-09-2024 17:07:43","Cascad=
ed Incident from TTO3022455","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. SIte is on Grid with U =3D 5=
4V. TX FME Abdouramane of Huawei is informed","system","758","26-09-2024 17=
:19:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003168893","MBIMBIM"=
,"","26-09-2024 17:19:21","26-09-2024 17:06:43","26-09-2024 17:07:43","Casc=
aded Incident from TTO3022455","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. SIte is on Grid with U =3D=
 54V. TX FME Abdouramane of Huawei is informed","system","758","26-09-2024 =
17:19:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003168891","Matsari"=
,"","26-09-2024 17:19:21","26-09-2024 17:06:43","26-09-2024 17:07:43","Casc=
aded Incident from TTO3022455","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. SIte is on Grid with U =3D=
 54V. TX FME Abdouramane of Huawei is informed","system","758","26-09-2024 =
17:19:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003168892","Ngouetou=
","","26-09-2024 17:19:21","26-09-2024 17:06:43","26-09-2024 17:07:43","Cas=
caded Incident from TTO3022455","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. SIte is on Grid with U =
=3D 54V. TX FME Abdouramane of Huawei is informed","system","758","26-09-20=
24 17:19:21","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0003167033","UPA=
C LP","","26-09-2024 15:57:02","26-09-2024 15:50:51","26-09-2024 20:24:12",=
"Grid outage no space to deploy // Grid return","","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid outage no space to deploy =
// Grid return","denis.mballa@ihstowers.com","373","26-09-2024 15:57:02","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003167013","S=
ous Prefecture","","26-09-2024 15:53:24","26-09-2024 15:49:15","26-09-2024 =
15:55:15","No power isssue, site is on grid with Ubaie=3D53V, Lionel Tchatc=
houa(694693436) from Huawei is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 isssue, site is on grid with Ubaie=3D53V, Lionel Tchatchoua(694693436) fro=
m Huawei is informed","ange.kongo@ihstowers.com","250","26-09-2024 15:53:24=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0003166981","Mfou EPC=
","","26-09-2024 15:48:50","26-09-2024 15:28:33","26-09-2024 15:30:38","Cas=
caded Incident from TTO3020511","Mba Lazare Herve","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active//No power isssue, site is on gr=
id with Ubaie=3D53V, Lionel Tchatchoua(694693436) from Huawei is informed",=
"system","1217","26-09-2024 15:48:50","Sagemcom CMR"
"Closed Complete","Site Down","T0144","IHS_YND_333","NOCINC0003166973","Mfo=
u MTN","IHS_YND_674","26-09-2024 15:47:44","26-09-2024 15:28:33","26-09-202=
4 15:30:38","Active//No power isssue, site is on grid with Ubaie=3D53V, Lio=
nel Tchatchoua(694693436) from Huawei is informed","Mba Lazare Herve","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power isssue, site is on grid with Ubaie=3D53V, Lionel Tc=
hatchoua(694693436) from Huawei is informed","denis.mballa@ihstowers.com","=
1152","26-09-2024 15:47:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0003166903","Y=
oko OCM","","26-09-2024 15:41:11","26-09-2024 15:24:56","26-09-2024 15:37:5=
6","Grid outage, site went down because gen ran untill fuel shortage (Fuel =
manage by edonde) // Grid return","Parker Tchoup","Fuel Outage","Passive","=
Diesel","Diesel Outage","Grid outage, site went down because gen ran untill=
 fuel shortage (Fuel manage by edonde) // Grid return","ange.kongo@ihstower=
s.com","976","26-09-2024 15:41:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0003166472","T=
SINGA VILLAGE 2","","26-09-2024 14:41:46","26-09-2024 14:15:37","26-09-2024=
 15:38:25","Grid Outage site went down due to controller Huawei dysfonction=
ing//he reset it and started the Gen","Delor Telezing","Equipment Repair","=
Passive","Control Panel","ATS-AMF Issue","Grid Outage site went down due to=
 controller Huawei dysfonctioning//he reset it and started the Gen","ange.k=
ongo@ihstowers.com","1570","26-09-2024 14:41:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003166108","Nkolbiss=
on usines des eaux 2","","26-09-2024 13:50:10","26-09-2024 13:22:18","26-09=
-2024 14:30:16","Cascaded Incident from TTO3019580","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Site wa=
s on Gen due to Grid Outage, Site went down because Gen stopped with ""High=
 Temp"" Alarm// He added water and started Gen manualy","system","1672","26=
-09-2024 13:50:10","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003166104","Nko=
lbisson","IHS_YND_763","26-09-2024 13:49:28","26-09-2024 13:22:18","26-09-2=
024 14:30:16","Site was on Gen due to Grid Outage, Site went down because G=
en stopped with ""High Temp"" Alarm// He added water and started Gen manual=
y","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG=
 - High Engine Temp - Coolant Level Issue","Site was on Gen due to Grid Out=
age, Site went down because Gen stopped with ""High Temp"" Alarm// He added=
 water and started Gen manualy","olivier.kwedi@ihstowers.com","1630","26-09=
-2024 13:49:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0003166011","B=
astos Ekoudou","","26-09-2024 13:37:52","26-09-2024 13:32:47","26-09-2024 1=
3:40:07","No power issue on site ubaie=3D54v site on grid Eloundou is infor=
med","Mboua Thierry","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue on site ubaie=3D54v site on=
 grid Eloundou is informed","ludivine.ngamaleu@ihstowers.com","306","26-09-=
2024 13:37:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003165782","N=
kolndongo","","26-09-2024 13:15:13","26-09-2024 13:07:09","26-09-2024 15:22=
:20","Grid Outage and Main Gen Faulty //Grid Restored","MINKA NICOLAS","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid Outage =
and Main Gen Faulty //Grid Restored","ludivine.ngamaleu@ihstowers.com","485=
","26-09-2024 13:15:13","Sagemcom CMR"
"Closed Complete","Warning","CTR_080","IHS_YND_298","NOCINC0003165278","Ole=
mbe","","26-09-2024 12:20:39","","","Site alarming on battery due to work B=
ernard ATANGANA is working on site//End of work","Fabrice Pouakam","Warning=
","Warning","POWER","Warning - Site on Battery","Site alarming on battery d=
ue to work Bernard ATANGANA is working on site//End of work","dorothy.djant=
io@ihstowers.com","306","26-09-2024 12:20:39","Sagemcom CMR"
"Cancelled","Warning","T0636","IHS_YND_299","NOCINC0003165205","Olembe MTN"=
,"","26-09-2024 12:14:19","","","SITE ON BATTERY","Fabrice Pouakam","","","=
","","","dorothy.djantio@ihstowers.com","247","26-09-2024 12:14:19","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003164952","M=
ambine","","26-09-2024 11:46:58","26-09-2024 11:39:54","26-09-2024 11:45:34=
","Hybrid Site;Site went because Gen failed to start due to hybride system =
dysfonction / He reset the Hybride system and site on Gen","Fanda Brice","E=
quipment Repair","Passive","Hybrid","Hybrid Module","Site went because Gen =
failed to start due to hybride system dysfonction / He reset the Hybride sy=
stem and site on Gen","ludivine.ngamaleu@ihstowers.com","425","26-09-2024 1=
1:46:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0003164821","Elig Edz=
oa","","26-09-2024 11:23:51","26-09-2024 11:12:17","26-09-2024 13:40:25","C=
ascaded Incident from TTO3018225","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, gen fails to start due=
 to gen starter faulty//replaced the starter","system","694","26-09-2024 11=
:23:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0003164820","ELIg-Ess=
ono","","26-09-2024 11:23:51","26-09-2024 11:12:17","26-09-2024 13:40:25","=
Cascaded Incident from TTO3018225","Delor Telezing","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, gen fails to start du=
e to gen starter faulty//replaced the starter","system","694","26-09-2024 1=
1:23:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_091","NOCINC0003164819","Jouvence=
 2000","","26-09-2024 11:23:51","26-09-2024 11:12:17","26-09-2024 13:40:25"=
,"Cascaded Incident from TTO3018225","Delor Telezing","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage, gen fails to start =
due to gen starter faulty//replaced the starter","system","694","26-09-2024=
 11:23:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0003164818","Mamch Bu=
ilding","","26-09-2024 11:23:51","26-09-2024 11:12:17","26-09-2024 13:40:25=
","Cascaded Incident from TTO3018225","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage, gen fails to start =
due to gen starter faulty//replaced the starter","system","694","26-09-2024=
 11:23:51","Sagemcom CMR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0003164811","Cha=
rles-Atangana","IHS_YND_051, IHS_YND_091, IHS_YND_014, IHS_YND_504","26-09-=
2024 11:22:22","26-09-2024 11:12:17","26-09-2024 13:40:25","grid outage, ge=
n fails to start due to gen starter faulty//replaced the starter","","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Kick Starter","grid outage, gen f=
ails to start due to gen starter faulty//replaced the starter","olivier.kwe=
di@ihstowers.com","606","26-09-2024 11:22:22","Sagemcom CMR"
"Closed Complete","Warning","T0498","IHS_YND_049","NOCINC0003164701","Etoa-=
Meki","","26-09-2024 11:06:45","","","Grid Outage, site alarming because Ge=
n failed to start due to kick started faulty// He replaced kick started and=
 started Gen manualy","Delor Telezing","Warning","Warning","POWER","Warning=
 - Site on Battery","Grid Outage, site alarming because Gen failed to start=
 due to kick started faulty// He replaced kick started and started Gen manu=
aly","dorothy.djantio@ihstowers.com","193","26-09-2024 11:06:45","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_044","NOCINC0003164647","Polytech=
nique","","26-09-2024 10:59:30","26-09-2024 10:49:50","26-09-2024 11:00:05"=
,"Cascaded Incident from TTO3018037","","Cascade Outage","Active","Cascade =
Active","Cascade Active","Active// No power Issue Site on Grid Ubai =3D55,8=
 V, The TX FME Mbah Hosiah (674007438) is informed, Notice that we have dis=
junction at BTS OCM
","system","580","26-09-2024 10:59:30","Sagemcom CMR"
"Closed Complete","Site Down","T0290","IHS_YND_067","NOCINC0003164641","Nko=
a Ayos","","26-09-2024 10:59:08","26-09-2024 10:51:59","26-09-2024 12:35:59=
","","MINKA NICOLAS","Installation Activity","Passive","Planned Activity","=
Installation Activity","site went down due to work (kamdem(677548363) from =
I-ENG, swap PWC)// End of work","olivier.kwedi@ihstowers.com","585","26-09-=
2024 10:59:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_447","IHS_YND_061","NOCINC0003164640","Y=
de University","IHS_YND_044","26-09-2024 10:58:54","26-09-2024 10:49:50","2=
6-09-2024 12:41:10","Active// No power Issue Site on Grid Ubai =3D55,8 V, T=
he TX FME Mbah Hosiah (674007438) is informed, Notice that we have disjunct=
ion at BTS OCM","Paul BIBOUM","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site on G=
rid Ubai =3D55,8 V, The TX FME Mbah Hosiah (674007438) is informed, Notice =
that we have disjunction at BTS OCM
","ludivine.ngamaleu@ihstowers.com","545","26-09-2024 10:58:54","Sagemcom C=
MR"
"Cancelled","Warning","CTR_128","IHS_YND_044","NOCINC0003164629","Polytechn=
ique","","26-09-2024 10:57:42","","","","","","","","","","ludivine.ngamale=
u@ihstowers.com","486","26-09-2024 10:57:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003164621","M=
fou EPC","","26-09-2024 10:55:58","26-09-2024 10:46:53","26-09-2024 11:05:0=
7","Grid outage;DG failed to start due to ACDG control panel faulty //Manua=
lly start of DG.","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen=
","ACDG - Control Panel","Grid outage;DG failed to start due to ACDG contro=
l panel faulty //Manually start of DG.","ludivine.ngamaleu@ihstowers.com","=
546","26-09-2024 10:55:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0003164503","G=
SO","","26-09-2024 10:41:47","26-09-2024 10:27:30","26-09-2024 12:50:16",""=
,"MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue, site is on grid with Ubaie=3D5=
3V, Erick(696422966) from ZTE working on site","dorothy.djantio@ihstowers.c=
om","858","26-09-2024 10:41:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003163936","M=
essa-Carriere OCM","","26-09-2024 09:18:19","26-09-2024 09:09:14","26-09-20=
24 09:29:09","site went down due to work (KARIM(680601705) from Prime Afric=
a working  (swap PWC) //End of work","","Installation Activity","Passive","=
Planned Activity","Installation Activity","site went down due to work (KARI=
M(680601705) from Prime Africa, swap PWC","ludivine.ngamaleu@ihstowers.com"=
,"546","26-09-2024 09:18:19","Sagemcom CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0003163603","Eto=
ug-Ebe 2","","26-09-2024 08:09:51","26-09-2024 08:01:42","26-09-2024 16:11:=
18","Grid outage No space to deploy a MDG //  Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No space=
 to deploy a MDG //  Grid return","olivier.kwedi@ihstowers.com","490","26-0=
9-2024 08:09:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003163455","M=
ontee-Des-Soeurs","","26-09-2024 07:38:54","26-09-2024 07:31:49","26-09-202=
4 08:50:39","Grid outage Site went down because Gen stopped due to ""high t=
emp"" alarm //He added water and gen manually started","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Grid outage Site went down because Gen stopped due to ""high tem=
p"" alarm //He added water and gen manually started","ludivine.ngamaleu@ihs=
towers.com","426","26-09-2024 07:38:54","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003163247","Nom=
ayos montee Meche","","26-09-2024 06:51:00","26-09-2024 06:48:52","26-09-20=
24 07:07:02","gen ran till fuel shortage//Refueling done","Fanda Brice","Fu=
el Outage","Passive","Diesel","Diesel Outage","gen ran till fuel shortage//=
Refueling done","olivier.kwedi@ihstowers.com","129","26-09-2024 06:51:00","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0003163189","Monatele=
","","26-09-2024 06:35:21","26-09-2024 06:19:30","26-09-2024 06:37:40","Cas=
caded Incident from TTO3016347","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n failed to start due to gen card faulty// gen manaually started","system",=
"951","26-09-2024 06:35:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_869","IHS_YND_407","NOCINC0003163104","M=
onatele MTN","IHS_YND_406","26-09-2024 06:17:49","26-09-2024 06:15:48","26-=
09-2024 06:37:40","Grid outage, site went down because gen failed to start =
due to gen card faulty// gen manaually started","Parker Tchoup","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went=
 down because gen failed to start due to gen card faulty// gen manaually st=
arted","ludivine.ngamaleu@ihstowers.com","122","26-09-2024 06:17:49","Sagem=
com CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003162519","HOP=
ITAL GENERAL RAIL YDE","","26-09-2024 02:41:18","26-09-2024 02:36:08","26-0=
9-2024 11:38:39","Access issue since the nigth, gen fails to start due to g=
rid bad voltage//made bridge on the good phase","Delor Telezing","Access De=
nial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord"=
,"Access issue since the nigth, gen fails to start due to grid bad voltage/=
/made bridge on the good phase","stephane.nkamwa@ihstowers.com","310","26-0=
9-2024 02:41:18","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003162021","Eko=
unou","","25-09-2024 23:48:26","25-09-2024 23:40:03","25-09-2024 23:46:03",=
"Grid outage  site down due to poor backup before gen start // Gen started =
automatically","Albran Byorel","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage  site down due to poor backup b=
efore gen start // Gen started automatically","stephane.nkamwa@ihstowers.co=
m","504","25-09-2024 23:48:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003161638","ELOUMDEM=
 CARRIERE 2","","25-09-2024 22:30:20","25-09-2024 22:11:18","25-09-2024 22:=
53:18","Cascaded Incident from TTO3014566","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,gen ran till fuel=
 shortage//Refueling done","system","1155","25-09-2024 22:30:20","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003161637","Eto koss=
 Yde","","25-09-2024 22:30:20","25-09-2024 22:11:18","25-09-2024 22:53:18",=
"Cascaded Incident from TTO3014566","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen ran till fuel shorta=
ge//Refueling done","system","1153","25-09-2024 22:30:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003161589","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","25-09-2024 22:22:25","25-09-2024 22:=
09:18","25-09-2024 22:53:18","grid outage,gen ran till fuel shortage//Refue=
ling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","=
grid outage,gen ran till fuel shortage//Refueling done","landry.etame@ihsto=
wers.com","788","25-09-2024 22:22:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003160665","M=
essa-Carriere OCM","","25-09-2024 19:54:53","25-09-2024 19:49:47","26-09-20=
24 08:41:07","Grid outage no space to deploy awaiting Grid return;Eta=3D07h=
30","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage no space to deploy //grid return","emmanuel.ghani@ihstowers.com=
","307","25-09-2024 19:54:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003160656","F=
ebe Village","","25-09-2024 19:53:49","25-09-2024 19:48:44","25-09-2024 21:=
03:59"," No power issue, site is on Grid with  the fme tx  Brice Tsague (65=
0214096) from Huawei is informed,repetitif issue","Mboua Thierry","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
"," No power issue, site is on Grid with  the fme tx  Brice Tsague (6502140=
96) from Huawei is informed,repetitif issue","emmanuel.ghani@ihstowers.com"=
,"306","25-09-2024 19:53:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0003160475","N=
omayos","","25-09-2024 19:28:16","25-09-2024 19:24:12","25-09-2024 20:14:07=
","site went down because the Cb(125A) of Dcbox dysjoncted // He reamed the=
 Cb","Fanda Brice","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Circuit Breaker Issue","site went down because the Cb(125A) of Dcbox =
dysjoncted // He reamed the Cb","emmanuel.ghani@ihstowers.com","245","25-09=
-2024 19:28:16","Sagemcom CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0003160059","NKO=
ABANG NKOLO 3","","25-09-2024 18:30:07","25-09-2024 18:21:03","25-09-2024 2=
1:12:38","Site wet down due to work  =C9m=E9rite 677548363/  ING sarl is wo=
rking on site  (Swap PWC)// End of work","Mba Lazare Herve","Equipment Repl=
acement","Passive","Planned Activity","Planned Activity - Passive","Site we=
t down due to work  =C9m=E9rite 677548363/  ING sarl is working on site  (S=
wap PWC)// End of work","joelle.ekessi@ihstowers.com","546","25-09-2024 18:=
30:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003160052","Abattoir=
","","25-09-2024 18:29:30","25-09-2024 18:20:33","25-09-2024 18:34:59","Cas=
caded Incident from TTO3012726","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work Technicia=
n SS Willy kamga /656 07 26 30  /IS working on site (Swap the Gen card)// E=
nd of work","system","537","25-09-2024 18:29:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003160053","ETOUDI C=
HAPELLE","","25-09-2024 18:29:30","25-09-2024 18:20:33","25-09-2024 18:34:5=
9","Cascaded Incident from TTO3012726","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work Tec=
hnician SS Willy kamga /656 07 26 30  /IS working on site (Swap the Gen car=
d)// End of work","system","537","25-09-2024 18:29:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003160054","Etoudi 2=
","","25-09-2024 18:29:30","25-09-2024 18:20:33","25-09-2024 18:34:59","Cas=
caded Incident from TTO3012726","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work Technicia=
n SS Willy kamga /656 07 26 30  /IS working on site (Swap the Gen card)// E=
nd of work","system","537","25-09-2024 18:29:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0003160009","E=
toudi","IHS_YND_244, IHS_YND_694, IHS_YND_211","25-09-2024 18:21:43","25-09=
-2024 18:20:33","25-09-2024 18:34:59","Site went down due to work Technicia=
n SS Willy kamga /656 07 26 30/ iS working on site (Swap the Gen card)// En=
d of work","Fabrice Pouakam","Equipment Replacement","Passive","Planned Act=
ivity","Planned Activity - Passive","Site went down due to work Technician =
SS Willy kamga /656 07 26 30  /IS working on site (Swap the Gen card)// End=
 of work","emmanuel.ghani@ihstowers.com","70","25-09-2024 18:21:43","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_795","NOCINC0003159971","Lada I Y=
de","","25-09-2024 18:15:27","25-09-2024 18:12:23","25-09-2024 19:52:40","S=
ite wet down due to work Team lovet /678657160/  Prime Africa sarl is worki=
ng on site  (Swap PWC)//and of work","Mba Lazare Herve","Equipment Replacem=
ent","Passive","Planned Activity","Planned Activity - Passive","Site wet do=
wn due to work Team lovet /678657160/  Prime Africa sarl is working on site=
  (Swap PWC)//and of work","joelle.ekessi@ihstowers.com","185","25-09-2024 =
18:15:27","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003159789","Nko=
abang Ebolmedjock","","25-09-2024 17:44:42","25-09-2024 17:41:38","25-09-20=
24 19:07:54","Site wet down due to work  Kameni/675242905/  ING sarl is wor=
king on site  (Swap PWC)//and of work","Mba Lazare Herve","Equipment Replac=
ement","Passive","Planned Activity","Planned Activity - Passive","Site wet =
down due to work  Kameni/675242905/  ING sarl is working on site  (Swap PWC=
)//and of work","joelle.ekessi@ihstowers.com","184","25-09-2024 17:44:42","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_447","IHS_YND_061","NOCINC0003159727","Y=
de University","IHS_YND_044","25-09-2024 17:31:48","25-09-2024 17:25:43","2=
5-09-2024 20:00:34","Active// No power Issue Site on Grid Ubai =3D55,8 V, T=
he TX FME Mbah Hosiah (674007438) is informed, Notice that we have disjunct=
ion at BTS OCM","Paul BIBOUM","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site on G=
rid Ubai =3D55,8 V, The TX FME Mbah Hosiah (674007438) is informed, Notice =
that we have disjunction at BTS OCM","emmanuel.ghani@ihstowers.com","366","=
25-09-2024 17:31:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0003159716","C=
hapelle-Nsimeyong","","25-09-2024 17:29:39","25-09-2024 17:20:25","25-09-20=
24 21:30:19","No power issue Ubaie=3D54,4V site on Grid.The tx fme Mbah hos=
iah(674007438) from Huawei is informed. Notice that disjonction in BTS ocm =
 repetitif issue","MINKA NICOLAS","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue Ubaie=3D54,4V =
site on Grid.The tx fme Mbah hosiah(674007438) from Huawei is informed. Not=
ice that disjonction in BTS ocm  repetitif issue","emmanuel.ghani@ihstowers=
.com","555","25-09-2024 17:29:39","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003159532","Nko=
mo stade","","25-09-2024 16:52:23","25-09-2024 16:47:18","25-09-2024 16:53:=
00","Site went down due to 01/03 Rectifier Dysfuntionning //He resert the r=
ectifier and site is on Grid","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier Distribution","Site went down due to 01/03 Rectif=
ier Dysfuntionning //He resert the rectifier and site is on Grid","joelle.e=
kessi@ihstowers.com","306","25-09-2024 16:52:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003159515","M=
EHANDAN","","25-09-2024 16:50:04","25-09-2024 16:45:01","25-09-2024 17:13:5=
7","Grid fluctuation, site went down because gen start and stopped due to g=
rid bad voltage // he bypass grid and manually start the gen","Albran Byore=
l","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty"=
,"Grid fluctuation, site went down because gen start and stopped due to gri=
d bad voltage // he bypass grid and manually start the gen","emmanuel.ghani=
@ihstowers.com","305","25-09-2024 16:50:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0003159469","M=
volye-New","","25-09-2024 16:44:31","25-09-2024 16:41:26","25-09-2024 16:55=
:49","Site went down due to insufficience of rectifier// Site stabilized","=
","Equipment Repair","Passive","Rectifier","Rectifier Module","Site went do=
wn due to insufficience of rectifier// Site stabilized","emmanuel.ghani@ihs=
towers.com","185","25-09-2024 16:44:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003159206","Etoudi 2=
","","25-09-2024 16:10:10","25-09-2024 16:03:15","25-09-2024 16:17:38","Cas=
caded Incident from TTO3011757","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work Technicia=
n SS Willy kamga /656 07 26 30  /IS working on site (Swap the Gen card)// E=
nd of work","system","415","25-09-2024 16:10:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003159205","ETOUDI C=
HAPELLE","","25-09-2024 16:10:10","25-09-2024 16:03:15","25-09-2024 16:17:3=
8","Cascaded Incident from TTO3011757","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work Tec=
hnician SS Willy kamga /656 07 26 30  /IS working on site (Swap the Gen car=
d)// End of work","system","415","25-09-2024 16:10:10","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003159199","Eto=
udi","IHS_YND_694, IHS_YND_211","25-09-2024 16:09:19","25-09-2024 16:03:15"=
,"25-09-2024 16:17:38","Site went down due to work Technician SS Willy kamg=
a /656 07 26 30  /IS working on site (Swap the Gen card)// End of work","Fa=
brice Pouakam","Equipment Replacement","Passive","Planned Activity","Planne=
d Activity - Passive","Site went down due to work Technician SS Willy kamga=
 /656 07 26 30  /IS working on site (Swap the Gen card)// End of work","joe=
lle.ekessi@ihstowers.com","365","25-09-2024 16:09:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0003159011","E=
vodoula OCM","","25-09-2024 15:39:22","25-09-2024 15:34:16","25-09-2024 17:=
00:49","No power issue site and  with Ubaie=3D54.4 V site on Grid The  FME =
TX Mouamadou/658791013 //From  is informed","TIENTCHEU NZETCHIEU GAEL","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue site and  with Ubaie=3D54.4 V site on Grid The  FME =
TX Mouamadou/658791013 //From  is informed","emmanuel.ghani@ihstowers.com",=
"307","25-09-2024 15:39:22","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0003158804","NKO=
LOSSAN OKOK","","25-09-2024 15:09:45","25-09-2024 15:04:41","25-09-2024 15:=
18:56","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // he bypass grid and manually start the gen","Parker T=
choup","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage // he bypass grid and manually start the gen","joelle.eke=
ssi@ihstowers.com","305","25-09-2024 15:09:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003158514","M=
essa-Carriere OCM","","25-09-2024 14:36:37","25-09-2024 14:34:32","25-09-20=
24 15:53:35","Grid outage, No space  to deploy MDG // Grid Power return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, No space  to deploy MDG // Grid Power return","emmanuel.ghani@ihstow=
ers.com","126","25-09-2024 14:36:37","Sagemcom CMR"
"Closed Complete","Site Down","T1570","IHS_YND_140","NOCINC0003158047","BIS=
CUITERIE","","25-09-2024 13:41:04","25-09-2024 13:29:49","25-09-2024 13:30:=
09","Site went down due to Work ,The Technician YOVO Valentin/698529863/Fro=
m SFM working on site (normalisation PWC)//end OF WORK","Paul BIBOUM","Inst=
allation Activity","Passive","Planned Activity","Installation Activity","Si=
te went down due to Work ,The Technician YOVO Valentin/698529863/From SFM w=
orking on site (normalisation PWC)//end OF WORK","denis.mballa@ihstowers.co=
m","676","25-09-2024 13:41:04","Sagemcom CMR"
"Closed Complete","Warning","CTR_238","IHS_YND_148","NOCINC0003158036","Cha=
pelle-Nsimeyong","","25-09-2024 13:38:10","","","","MINKA NICOLAS","Warning=
","Warning","Unlisted RCA","Warning - Others","Error","denis.mballa@ihstowe=
rs.com","3","25-09-2024 13:38:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003157919","C=
rf-Nsam","","25-09-2024 13:31:05","25-09-2024 13:29:00","25-09-2024 14:35:2=
6","Active// No power issue on site ,site on Grid with Ubaie=3D 53,4V The R=
M Alain /691144423/ From huawei is informed","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue on site ,site on Grid with Ubaie=3D 53,4V The RM Alai=
n /691144423/ Fom huawei is informed and up at 01:31 PM","ange.kongo@ihstow=
ers.com","126","25-09-2024 13:31:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003157793","N=
kolndongo","","25-09-2024 13:11:17","25-09-2024 13:02:12","25-09-2024 13:44=
:42","Grid outage site went down because Main Gen faulty// Grid power retur=
n","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generato=
r Faulty","Grid outage site went down because Main Gen faulty// Grid power =
return","ange.kongo@ihstowers.com","546","25-09-2024 13:11:17","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0003157612","Behind P=
 T school Yde","","25-09-2024 12:38:21","25-09-2024 12:27:40","25-09-2024 1=
2:49:58","Cascaded Incident from TTO3009903","Paul BIBOUM","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active//No power on Site Site =
is on Grid and UBAIE=3D52.4V The FME bAH hOSIAH is Informed","system","641"=
,"25-09-2024 12:38:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_507","NOCINC0003157613","BIYEM AS=
SI LYCEE","","25-09-2024 12:38:21","25-09-2024 12:27:40","25-09-2024 12:49:=
58","Cascaded Incident from TTO3009903","Hyemafo Gildas","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active//No power on Site Site is=
 on Grid and UBAIE=3D52.4V The FME bAH hOSIAH is Informed","system","641","=
25-09-2024 12:38:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0003157614","BIYEMASS=
I NIKI","","25-09-2024 12:38:21","25-09-2024 12:27:40","25-09-2024 12:49:58=
","Cascaded Incident from TTO3009903","Hyemafo Gildas","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power on Site Site is o=
n Grid and UBAIE=3D52.4V The FME bAH hOSIAH is Informed","system","641","25=
-09-2024 12:38:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0003157609","Accacia =
New","","25-09-2024 12:38:20","25-09-2024 12:27:40","25-09-2024 12:49:58","=
Cascaded Incident from TTO3009903","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","Active//No power on Site Site is on Grid and UBAIE=
=3D52.4V The FME bAH hOSIAH is Informed","system","640","25-09-2024 12:38:2=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0003157611","BONAS YD=
E","","25-09-2024 12:38:20","25-09-2024 12:27:40","25-09-2024 12:49:58","Ca=
scaded Incident from TTO3009903","Paul BIBOUM","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active//No power on Site Site is on Grid a=
nd UBAIE=3D52.4V The FME bAH hOSIAH is Informed","system","640","25-09-2024=
 12:38:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0003157608","Ngoa Eke=
lle","","25-09-2024 12:38:20","25-09-2024 12:27:40","25-09-2024 12:49:58","=
Cascaded Incident from TTO3009903","Paul BIBOUM","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active//No power on Site Site is on Grid=
 and UBAIE=3D52.4V The FME bAH hOSIAH is Informed","system","640","25-09-20=
24 12:38:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0003157610","Biyemass=
i LAC","","25-09-2024 12:38:20","25-09-2024 12:27:40","25-09-2024 12:49:58"=
,"Cascaded Incident from TTO3009903","","Cascade Outage","Active","Cascade =
Active","Cascade Active","Active//No power on Site Site is on Grid and UBAI=
E=3D52.4V The FME bAH hOSIAH is Informed","system","640","25-09-2024 12:38:=
20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0003157607","Obili Ch=
apelle","","25-09-2024 12:38:19","25-09-2024 12:27:40","25-09-2024 12:49:58=
","Cascaded Incident from TTO3009903","Paul BIBOUM","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power on Site Site is on G=
rid and UBAIE=3D52.4V The FME bAH hOSIAH is Informed","system","639","25-09=
-2024 12:38:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0003157606","Scalom",=
"","25-09-2024 12:38:19","25-09-2024 12:27:40","25-09-2024 12:49:58","Casca=
ded Incident from TTO3009903","Paul BIBOUM","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power on Site Site is on Grid and =
UBAIE=3D52.4V The FME bAH hOSIAH is Informed","system","639","25-09-2024 12=
:38:19","Sagemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0003157572","Nlo=
ng Mvolye New","IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND_562, IHS_YND=
_546, IHS_YND_683, IHS_YND_805, IHS_YND_507, IHS_YND_724","25-09-2024 12:32=
:58","25-09-2024 12:27:40","25-09-2024 12:30:58","Active//No power on Site =
Site is on Grid and UBAIE=3D52.4V The FME bAH hOSIAH is Informed","Paul BIB=
OUM","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active//No power on Site Site is on Grid and UBAIE=3D52.4V=
 The FME bAH hOSIAH is Informed","denis.mballa@ihstowers.com","319","25-09-=
2024 12:32:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0003157414","M=
essassi","","25-09-2024 12:15:05","25-09-2024 12:04:01","25-09-2024 13:16:3=
2","No power issue on site U=3D54,5v site on grid Synphorien/650257151 of h=
uawei is informed and up at 12:16 PM","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site U=3D54,5v site on grid Synphorien/650257151 of huawei is in=
formed and up at 12:16 PM","ange.kongo@ihstowers.com","666","25-09-2024 12:=
15:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_447","IHS_YND_061","NOCINC0003157322","Y=
de University","IHS_YND_044","25-09-2024 12:00:19","25-09-2024 11:57:07","2=
5-09-2024 14:30:29","Active// No power Issue Site on Grid Ubai =3D55,8 V, T=
he TX FME Mbah Hosiah (674007438) is informed, Notice that we have disjunct=
ion at BTS OCM","Paul BIBOUM","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site on G=
rid Ubai =3D55,8 V, The TX FME Mbah Hosiah (674007438) is informed, Notice =
that we have disjunction at BTS OCM","ange.kongo@ihstowers.com","193","25-0=
9-2024 12:00:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0003157313","P=
olytechnique","","25-09-2024 11:59:09","25-09-2024 11:57:07","25-09-2024 17=
:26:34","Grid outage No space  to deploy a MDG  //Grid return","","Cascade =
Outage","Active","Cascade Active","Cascade Active","Grid outage No space  t=
o deploy a MDG  //Grid return","ange.kongo@ihstowers.com","9076","25-09-202=
4 11:59:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003156992","Yoko MTN=
","","25-09-2024 11:22:51","25-09-2024 11:07:57","25-09-2024 13:30:07","Cas=
caded Incident from TTO3009214","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid-DG,DG stopped due to High Temp =
Alarm // He added water,and manually start of DG.","system","894","25-09-20=
24 11:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003156989","Ngouetou=
","","25-09-2024 11:22:51","25-09-2024 11:07:57","25-09-2024 13:30:07","Cas=
caded Incident from TTO3009214","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid-DG,DG stopped due to High Temp =
Alarm // He added water,and manually start of DG.","system","894","25-09-20=
24 11:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003156990","Donga","=
","25-09-2024 11:22:51","25-09-2024 11:07:57","25-09-2024 13:30:07","Cascad=
ed Incident from TTO3009214","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Hybrid-DG,DG stopped due to High Temp Ala=
rm // He added water,and manually start of DG.","system","894","25-09-2024 =
11:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003156991","Dong",""=
,"25-09-2024 11:22:51","25-09-2024 11:07:57","25-09-2024 13:30:07","Cascade=
d Incident from TTO3009214","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Hybrid-DG,DG stopped due to High Temp Alar=
m // He added water,and manually start of DG.","system","894","25-09-2024 1=
1:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003156988","Matsari"=
,"","25-09-2024 11:22:51","25-09-2024 11:07:57","25-09-2024 13:30:07","Casc=
aded Incident from TTO3009214","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid-DG,DG stopped due to High Temp A=
larm // He added water,and manually start of DG.","system","894","25-09-202=
4 11:22:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003156986","Nguila",=
"","25-09-2024 11:22:50","25-09-2024 11:07:57","25-09-2024 13:30:07","Casca=
ded Incident from TTO3009214","Parker Tchoup","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Hybrid-DG,DG stopped due to High Temp Al=
arm // He added water,and manually start of DG.","system","893","25-09-2024=
 11:22:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003156987","MBIMBIM"=
,"","25-09-2024 11:22:50","25-09-2024 11:07:57","25-09-2024 13:30:07","Casc=
aded Incident from TTO3009214","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid-DG,DG stopped due to High Temp A=
larm // He added water,and manually start of DG.","system","893","25-09-202=
4 11:22:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0003156940","O=
ssombe","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_454, IHS_YND_434, I=
HS_YND_444, IHS_YND_473","25-09-2024 11:15:05","25-09-2024 11:07:57","25-09=
-2024 13:30:07","Hybrid-DG,DG stopped due to High Temp Alarm // He added wa=
ter,and manually start of DG.","Parker Tchoup","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Hybrid-DG,DG s=
topped due to High Temp Alarm // He added water,and manually start of DG.",=
"ange.kongo@ihstowers.com","429","25-09-2024 11:15:05","Sagemcom CMR"
"Closed Complete","Site Down","T1570","IHS_YND_140","NOCINC0003156894","BIS=
CUITERIE","","25-09-2024 11:06:19","25-09-2024 10:57:02","25-09-2024 11:07:=
29","Site went down due to work Technician YOVO Valentin/698529863/From SFM=
 working on site (normalisation PWC)// End of work","Paul BIBOUM","Installa=
tion Activity","Passive","Planned Activity","Installation Activity","Site w=
ent down due to work Technician YOVO Valentin/698529863/From SFM working on=
 site (normalisation PWC)// End of work","denis.mballa@ihstowers.com","558"=
,"25-09-2024 11:06:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0003156243","Hotel de=
 Ville Yde","","25-09-2024 10:31:47","25-09-2024 10:24:48","25-09-2024 12:4=
3:17","Cascaded Incident from TTO3008256","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage//Grid restored.","=
system","419","25-09-2024 10:31:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0003156172","N=
R-Bastos","IHS_YND_019","25-09-2024 10:29:03","25-09-2024 10:24:48","25-09-=
2024 12:43:17","Grid outage//Grid restored.","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid outage//Grid restored.","ange=
.kongo@ihstowers.com","256","25-09-2024 10:29:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0003155209","Mendong =
vallee","","25-09-2024 10:04:20","25-09-2024 09:56:13","25-09-2024 10:07:38=
","Site went down due to work Tecnician/Brice Fanda/657108549/SAGEMCOM/work=
ing on site (addition a second CB (125A) in DC BOX who feeds equipments OCM=
)// End of work","Fanda Brice","Installation Activity","Passive","Planned A=
ctivity","Installation Activity","Site went down due to work Tecnician/Bric=
e Fanda/657108549/SAGEMCOM/working on site (addition a second CB (125A) in =
DC BOX who feeds equipments OCM)// End of work","ange.kongo@ihstowers.com",=
"488","25-09-2024 10:04:20","Sagemcom CMR"
"Closed Complete","Warning","CTR_237","IHS_YND_261","NOCINC0003155183","Bar=
riere","","25-09-2024 10:02:34","","","Grid fluation, Site went alarm due t=
o grid bad voltage // he bypass grid and manually start the gen","Hyemafo G=
ildas","Warning","Warning","POWER","Warning - National Grid - Grid Outage I=
ssue","Grid fluation, Site went alarm due to grid bad voltage // he bypass =
grid and manually start the gen","adonis.defokoua@ihstowers.com","428","25-=
09-2024 10:02:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003154723","B=
arriere","","25-09-2024 09:12:02","25-09-2024 09:07:54","25-09-2024 10:47:5=
7","Grid fluctuation , site went down because Gen started and stopped due t=
o grid bad voltage,and  no rcp on site // He bypassed Grid and started Gen =
manually","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - =
Phase Controller Faulty","Grid fluctuation , site went down because Gen sta=
rted and stopped due to grid bad voltage,and  no rcp on site // He bypassed=
 Grid and started Gen manually","ange.kongo@ihstowers.com","249","25-09-202=
4 09:12:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0003154711","M=
volye-New","","25-09-2024 09:10:54","25-09-2024 09:06:46","25-09-2024 12:40=
:41","Site went down due to insuffisance of rectifier// Site stabilized",""=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue Ubaie=3D50,1 V site on Grid.The tx fme Mbah hos=
iah(674007438) from Huawei is informed. Notice that we have disjunction at =
BTS OCM","ange.kongo@ihstowers.com","250","25-09-2024 09:10:54","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0003153924","S=
imbock OCM","","25-09-2024 06:55:56","25-09-2024 06:42:51","25-09-2024 07:2=
0:23","Site was on Gen due to Grid outage, site went down because gen ran u=
ntill fuel shortage // refueling ongoing","Hyemafo Gildas","Fuel Outage","P=
assive","Diesel","Diesel Outage","Site was on Gen due to Grid outage, site =
went down because gen ran untill fuel shortage // refueling ongoing","ange.=
kongo@ihstowers.com","786","25-09-2024 06:55:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003153451","M=
ambine","","25-09-2024 04:15:32","25-09-2024 03:56:23","25-09-2024 04:42:22=
","Grid outage, site went down because gen ran untill fuel shortage // refu=
eling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran untill fuel shortage // refuel=
ing done","alexandre.kamal@ihstowers.com","1150","25-09-2024 04:15:32","Sag=
emcom CMR"
"Closed Complete","Site Down","T0108","IHS_YND_235","NOCINC0003153129","Eto=
ug-Ebe 2","","25-09-2024 02:12:39","25-09-2024 01:56:23","25-09-2024 13:10:=
37","Grid outage, No space  to deploy MDG // Grid Power return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, No=
 space  to deploy MDG // Grid Power return","kamga.virgile@ihstowers.com","=
977","25-09-2024 02:12:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0003152322","B=
ISCUITERIE","","24-09-2024 21:59:29","24-09-2024 21:57:16","24-09-2024 22:0=
5:41","Grid Outage, site went down because  Gen failed to start due to poor=
 battery backup // Grid Power return","Paul BIBOUM","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid Outage, site went=
 down because  Gen failed to start due to poor battery backup // Grid Power=
 return","denis.mballa@ihstowers.com","134","24-09-2024 21:59:29","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1869","IHS_YND_528","NOCINC0003152213","MEH=
ANDAN","","24-09-2024 21:39:08","24-09-2024 21:28:03","24-09-2024 22:08:44"=
,"site went down because the Grid contactor Faulty  // He blocked the Grid =
contactor manually  and site on Grid","Albran Byorel","Equipment Repair","P=
assive","Control Panel","ATS-AMF Issue","site went down because the Grid co=
ntactor Faulty  // He blocked the Grid contactor manually  and site on Grid=
","landry.etame@ihstowers.com","666","24-09-2024 21:39:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003152124","F=
ebe Village","","24-09-2024 21:24:44","24-09-2024 21:19:32","24-09-2024 21:=
22:56"," No power issue, site is on Grid with  the fme tx  Brice Tsague (65=
0214096) from Huawei is informed,","Mboua Thierry","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No power is=
sue, site is on Grid with  the fme tx  Brice Tsague (650214096) from Huawei=
 is informed,","denis.mballa@ihstowers.com","313","24-09-2024 21:24:44","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003151398","M=
aison-Blanche-IHS","","24-09-2024 19:27:32","24-09-2024 19:25:16","25-09-20=
24 00:04:32","Grid outage No free mobile gen to deploy // Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age No free mobile gen to deploy // Grid return","denis.mballa@ihstowers.co=
m","137","24-09-2024 19:27:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003151382","C=
rf-Nsam","","24-09-2024 19:24:13","24-09-2024 19:22:59","24-09-2024 19:31:3=
5","Grid outage site went down because Gen started and stopped with alarm "=
" over voltage""//He reset the Gen card and Gen manually started","MINKA NI=
COLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Grid =
outage site went down because Gen started and stopped with alarm "" over vo=
ltage""//He reset the Gen card and Gen manually started","denis.mballa@ihst=
owers.com","75","24-09-2024 19:24:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0003151197","N=
omayos","","24-09-2024 18:42:27","24-09-2024 18:33:14","24-09-2024 19:09:35=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage // he bypass grid and manually start the gen","Fanda Brice",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid fluctuation, site went down because gen start and stopped due to grid b=
ad voltage // he bypass grid and manually start the gen","denis.mballa@ihst=
owers.com","554","24-09-2024 18:42:27","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003151189","Bas=
tos Amb Coree","","24-09-2024 18:40:04","24-09-2024 18:35:40","24-09-2024 1=
8:49:55","grid outage,no space to deploy a mobil gen//grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,=
no space to deploy a mobil gen//grid return","landry.etame@ihstowers.com","=
265","24-09-2024 18:40:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003151186","L=
abogenie","IHS_YND_568","24-09-2024 18:39:44","24-09-2024 15:10:20","25-09-=
2024 08:10:17","Grid outage, No space  to deploy MDG// Grid Power return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage, No space  to deploy MDG// Grid Power return","denis.mballa@ihstower=
s.com","12565","24-09-2024 18:39:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003151164","E=
mana","","24-09-2024 18:33:07","24-09-2024 18:30:52","24-09-2024 20:18:17",=
"Active: No power issue on site, Ubai =3D 52,8V on Grid The tx fme symphori=
en /650257151 /  from HUAWEI is informed","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power i=
ssue on site, Ubai =3D 52,8V on Grid The tx fme symphorien /650257151 /  fr=
om HUAWEI is informed","denis.mballa@ihstowers.com","136","24-09-2024 18:33=
:07","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0003151122","Nko=
mkana","","24-09-2024 18:29:34","24-09-2024 18:19:26","24-09-2024 18:32:26"=
,"grid outage,no space to deploy a mobil gen//grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","grid outage,no space=
 to deploy a mobil gen//grid return","landry.etame@ihstowers.com","688","24=
-09-2024 18:29:34","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0003150748","NKO=
LOSSAN OKOK","","24-09-2024 17:36:57","24-09-2024 17:19:51","24-09-2024 17:=
57:51","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // he bypass grid and manually start the gen","Parker T=
choup","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage // he bypass grid and manually start the gen","landry.eta=
me@ihstowers.com","1027","24-09-2024 17:36:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0003150739","N=
koa Ayos","","24-09-2024 17:33:39","24-09-2024 17:25:26","24-09-2024 18:44:=
34","Grid fluctuation, site went down because gen start and stopped due to =
grid bad voltage // Grid stabilized","MINKA NICOLAS","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site =
went down because gen start and stopped due to grid bad voltage // Grid sta=
bilized","denis.mballa@ihstowers.com","494","24-09-2024 17:33:39","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0003150728","E=
mombo","","24-09-2024 17:29:27","24-09-2024 17:24:14","24-09-2024 19:06:18"=
,"site went down due to work Team kameni Alex/677548708/I-engeineering: swa=
p the PWC//End of work","Mba Lazare Herve","Installation Activity","Passive=
","Planned Activity","Installation Activity","site went down due to work Te=
am kameni Alex/677548708/I-engeineering: swap the PWC//End of work","denis.=
mballa@ihstowers.com","314","24-09-2024 17:29:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0003150687","A=
nguissa New","","24-09-2024 17:18:45","24-09-2024 15:10:20","25-09-2024 08:=
10:17","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage, No space  to deploy MDG// Grid Power return","d=
enis.mballa@ihstowers.com","19139","24-09-2024 17:18:45","Sagemcom CMR"
"Cancelled","Warning","CTR_395","IHS_YND_249","NOCINC0003150669","Biteng-Ma=
etur","","24-09-2024 17:16:18","","","","Mba Lazare Herve","","","","","","=
denis.mballa@ihstowers.com","7402","24-09-2024 17:16:18","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003150529","Nko=
lnda","","24-09-2024 16:55:52","24-09-2024 16:39:38","24-09-2024 18:49:28",=
"grid outage,gen stopped due to radiator pierced//he clogged the radiator; =
power reset has been done","Albran Byorel","Equipment Repair","Passive","AC=
DG Gen","ACDG - Radiator","grid outage,gen stopped due to radiator pierced/=
/he clogged the radiator; power reset has been done","landry.etame@ihstower=
s.com","974","24-09-2024 16:55:52","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0003150281","Nko=
mkana","","24-09-2024 16:18:05","24-09-2024 16:07:59","24-09-2024 17:23:37"=
,"grid outage,no space to deploy a mobil gen//grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","grid outage,no space=
 to deploy a mobil gen//grid return","landry.etame@ihstowers.com","607","24=
-09-2024 16:18:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_051","NOCINC0003149519","Nyanon",=
"","24-09-2024 15:21:14","24-09-2024 15:10:25","24-09-2024 15:11:21","Casca=
ded Incident from TTO3000889","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","No Power Issue on Site, U =3D 54=
V and Site is on Grid. TX FME Pascal-691648179 is informed","system","649",=
"24-09-2024 15:21:14","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0003149396","Abo=
me","","24-09-2024 15:03:14","24-09-2024 14:58:49","24-09-2024 16:38:14","G=
rid outage site went down because Gen started and stopped with alarm Gen ov=
er voltage//He reset the Gen card and Gen manually started","MINKA NICOLAS"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Over Voltage","Grid outage=
 site went down because Gen started and stopped with alarm Gen over voltage=
//He reset the Gen card and Gen manually started","landry.etame@ihstowers.c=
om","266","24-09-2024 15:03:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003149354","N=
sam Sofavinc T0","","24-09-2024 14:58:00","24-09-2024 13:55:12","24-09-2024=
 17:44:19","Grid outage, site went down because Gen start and stopped due t=
o Gen overload (09kva ,160A)// he reduiced the load on site","MINKA NICOLAS=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, s=
ite went down because Gen start and stopped due to Gen overload (09kva ,160=
A)// he reduiced the load on site","marie.kwin@ihstowers.com","16036","24-0=
9-2024 14:58:00","Sagemcom CMR"
"Closed Complete","Site Down","T0286","IHS_YND_060","NOCINC0003149277","Ngo=
a Ekelle","","24-09-2024 14:47:35","24-09-2024 14:39:18","24-09-2024 15:29:=
02","site went down because 2/5 rectifier faulty and causing the disjunctio=
n of CB 40A of rectifier//he reamed the CB:site on 3 rectifiers(need to rep=
laced the faulty rectifier)","Paul BIBOUM","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","site went down because 2/5 rectifier faulty an=
d causing the disjunction of CB 40A of rectifier//he reamed the CB:site on =
3 rectifiers(need to replaced the faulty rectifier)","landry.etame@ihstower=
s.com","498","24-09-2024 14:47:35","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0003149208","Nko=
lnda","","24-09-2024 14:39:00","24-09-2024 14:28:50","24-09-2024 15:23:27",=
"grid outage,gen stopped with alarm high temp//grid return","Albran Byorel"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","grid outage,gen stopped with alarm high temp//grid return","=
landry.etame@ihstowers.com","611","24-09-2024 14:39:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0003149137","Mvog-Man=
ga","","24-09-2024 14:28:10","24-09-2024 14:09:30","24-09-2024 16:53:42","C=
ascaded Incident from TTO2999446","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work  BOUFACK =
Arcel/694174211/ LOUMAD ING sarl is working on site  (Swap PWC)","system","=
26006","24-09-2024 14:28:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003149108","MEHANDAN=
","","24-09-2024 14:26:41","24-09-2024 14:02:25","24-09-2024 14:17:25","Cas=
caded Incident from TTO3000295","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage  site down due to poor bac=
kup before gen start // Gen automatically started","system","1456","24-09-2=
024 14:26:41","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0003149069","Tou=
ring Club International","IHS_YND_254","24-09-2024 14:24:03","24-09-2024 14=
:16:54","24-09-2024 14:37:54","grid outage,gen start and stopped with alarm=
 undervoltage//he balanced the load","Albran Byorel","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Under Voltage","grid outage,gen start and stopped=
 with alarm undervoltage//he balanced the load","landry.etame@ihstowers.com=
","430","24-09-2024 14:24:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003148956","O=
dza II OCM","IHS_YND_528","24-09-2024 14:06:34","24-09-2024 14:02:25","24-0=
9-2024 14:17:25","Grid outage  site down due to poor backup before gen star=
t // Gen automatically started","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage  site down due=
 to poor backup before gen start // Gen automatically started","emmanuel.gh=
ani@ihstowers.com","250","24-09-2024 14:06:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0003148950","E=
leveur","","24-09-2024 14:05:19","24-09-2024 13:55:01","24-09-2024 17:18:03=
","No power issue on site U=3D54,5v site on grid Synphorien of huawei is in=
formed","Siligap Boris","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,5v site o=
n grid Synphorien of huawei is informed","emmanuel.ghani@ihstowers.com","61=
9","24-09-2024 14:05:19","Sagemcom CMR"
"Closed Complete","Site Down","T0455","IHS_YND_134","NOCINC0003148932","Val=
lee Bastos MTN","","24-09-2024 14:02:36","24-09-2024 13:57:30","24-09-2024 =
16:31:54","No power issue on site U=3D54,5v site on grid Tx fme Synphorien =
of huawei is informed ","Mboua Thierry","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D54,5v site on grid Tx fme Synphorien of huawei is informed ","joelle.ek=
essi@ihstowers.com","307","24-09-2024 14:02:36","Sagemcom CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0003148894","Mvo=
g-Ada_OCM","","24-09-2024 13:56:17","24-09-2024 13:53:11","24-09-2024 13:59=
:09","","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","grid outage, no space for a MDG//grid outage","joelle.ekessi@ihstowers.=
com","187","24-09-2024 13:56:17","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003148874","Eko=
unou","","24-09-2024 13:53:14","24-09-2024 13:51:09","24-09-2024 14:41:22",=
"Grid Fluctuation, site went down before DG start due to poor Battery backu=
p// DG started automatically","Albran Byorel","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid Fluctuation, site went =
down before DG start due to poor Battery backup// DG started automatically"=
,"joelle.ekessi@ihstowers.com","127","24-09-2024 13:53:14","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0003148804","MVA=
N SACEL","","24-09-2024 13:45:58","24-09-2024 13:38:54","24-09-2024 13:52:4=
6","Active// No power issue on site U=3D54,1V site on Grid the fme tx  Bric=
e Tsague (650214096) from Huawei is informed","MINKA NICOLAS","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive// No power issue on site U=3D54,1V site on Grid the fme tx  Brice Tsa=
gue (650214096) from Huawei is informed","joelle.ekessi@ihstowers.com","425=
","24-09-2024 13:45:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0003148789","M=
volye-New","","24-09-2024 13:43:18","24-09-2024 13:38:11","24-09-2024 14:49=
:20","Grid outage//Grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","Grid outage//Grid return","emmanuel.ghani@ihsto=
wers.com","308","24-09-2024 13:43:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0003148786","Sapeur",=
"","24-09-2024 13:42:30","24-09-2024 13:39:19","24-09-2024 13:43:15","Casca=
ded Incident from TTO3000086","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","grid outage, no space for a MDG//grid re=
turn","system","191","24-09-2024 13:42:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0003148781","E=
-Police","IHS_YND_029","24-09-2024 13:41:26","24-09-2024 13:39:19","24-09-2=
024 13:43:15","Grid Outage No space to deploy a MDG waiting Grid Restored",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid=
 outage, no space for a MDG//grid return","emmanuel.ghani@ihstowers.com","1=
29","24-09-2024 13:41:26","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0003148707","Mfo=
u EPC","","24-09-2024 13:27:05","24-09-2024 13:20:56","24-09-2024 15:02:24"=
,"grid outage,gen failed to start due to Card Ge faulty//Grid return","Mba =
Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","grid outage,gen failed to start due to Card Ge faulty//Grid return","joe=
lle.ekessi@ihstowers.com","449","24-09-2024 13:27:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003148684","Afanoya"=
,"","24-09-2024 13:19:21","24-09-2024 13:16:40","24-09-2024 13:43:28","Casc=
aded Incident from TTO2999970","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage, site down before gen star=
t due to poor backup//gen started","system","161","24-09-2024 13:19:21","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003148683","MBALNGON=
G LYCEE","","24-09-2024 13:19:20","24-09-2024 13:16:40","24-09-2024 13:43:2=
8","Cascaded Incident from TTO2999970","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site down before gen=
 start due to poor backup//gen started","system","160","24-09-2024 13:19:20=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003148682","ELOUMDEM=
 CARRIERE","","24-09-2024 13:19:20","24-09-2024 13:16:40","24-09-2024 13:43=
:28","Cascaded Incident from TTO2999970","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site down before g=
en start due to poor backup//gen started","system","160","24-09-2024 13:19:=
20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003148678","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","24-09-2024 13:17:45","24-09-20=
24 13:16:40","24-09-2024 13:43:28","grid outage, site down before gen start=
 due to poor backup//gen started","Hyemafo Gildas","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","grid outage, site down =
before gen start due to poor backup//gen started","joelle.ekessi@ihstowers.=
com","66","24-09-2024 13:17:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003148592","Lobo OCM=
","","24-09-2024 13:02:00","24-09-2024 12:56:20","24-09-2024 13:01:20","Cas=
caded Incident from TTO2999862","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage  site down due =
to poor backup before gen start // Gen started automatically","system","340=
","24-09-2024 13:02:00","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003148583","N=
KOMEKUI OCM","IHS_YND_341","24-09-2024 13:00:30","24-09-2024 12:56:20","24-=
09-2024 13:01:20","Grid outage  site down due to poor backup before gen sta=
rt // Gen started automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage  s=
ite down due to poor backup before gen start // Gen started automatically",=
"emmanuel.ghani@ihstowers.com","251","24-09-2024 13:00:30","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003148494","San=
ta Barbara Gottam","","24-09-2024 12:44:02","24-09-2024 12:37:55","24-09-20=
24 12:49:08","site went down due to work  SS  BERTRANT ATANGANA //IHS/ doin=
g  PM works//End of work","Delor Telezing","Equipment Replacement","Passive=
","Planned Activity","Planned Activity - Passive","site went down due to wo=
rk  SS  BERTRANT ATANGANA //IHS/ doing  PM works//End of work","joelle.ekes=
si@ihstowers.com","368","24-09-2024 12:44:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0003148222","O=
dza","IHS_YND_254","24-09-2024 12:11:36","24-09-2024 12:09:30","24-09-2024 =
16:53:42","Site wet down due to work  BOUFACK Arcel/694174211/ LOUMAD ING s=
arl is working on site  (Swap PWC)","Albran Byorel","Installation Activity"=
,"Passive","Planned Activity","Installation Activity","Site went down due t=
o work  BOUFACK Arcel/694174211/ LOUMAD ING sarl is working on site  (Swap =
PWC)","emmanuel.ghani@ihstowers.com","127","24-09-2024 12:11:36","Sagemcom =
CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0003148217","Nko=
abang MTN","","24-09-2024 12:10:11","24-09-2024 12:07:04","24-09-2024 12:52=
:58","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage // he bypass grid and manually start the gen","Mba Lazare=
 Herve","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid fluctuation, site went down because gen start and stopped due t=
o grid bad voltage // he bypass grid and manually start the gen","joelle.ek=
essi@ihstowers.com","188","24-09-2024 12:10:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0003148047","Montee-J=
ouvence-II","","24-09-2024 11:44:19","24-09-2024 09:39:45","24-09-2024 10:0=
1:45","Cascaded Incident from TTO2999047","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down because CB O=
CM(125 A) disjunted in DCBOX // He did a bridge with another  125*125 A ","=
system","7474","24-09-2024 11:44:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003147855","N=
kol-Mbanda","IHS_YND_518","24-09-2024 11:30:00","24-09-2024 09:39:45","24-0=
9-2024 10:01:45","Site went down because CB OCM(125 A) disjunted in DCBOX /=
/ He did a bridge with another  125*125 A ","MINKA NICOLAS","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site=
 went down because CB OCM(125 A) disjunted in DCBOX // He did a bridge with=
 another  125*125 A ","kombi.samuel@ihstowers.com","6617","24-09-2024 11:30=
:00","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0003147560","Aka=
k-Nkozoa-MTN-IHS","","24-09-2024 11:19:54","24-09-2024 11:16:50","24-09-202=
4 12:42:24","Grid  fluctuation , site went down because gen failed to start=
 due to grid bad voltage // He bypassed Grid and started Gen manually ","Fa=
brice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","Grid  fluctuation , site went down because gen failed to star=
t due to grid bad voltage // He bypassed Grid and started Gen manually ","j=
oelle.ekessi@ihstowers.com","186","24-09-2024 11:19:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003147491","E=
lig Edzoa","","24-09-2024 11:16:55","24-09-2024 11:14:49","24-09-2024 11:21=
:55","Grid outage  site down due to poor backup before gen start // Gen sta=
rted automatically","Delor Telezing","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage  site down due to poor ba=
ckup before gen start // Gen started automatically","emmanuel.ghani@ihstowe=
rs.com","126","24-09-2024 11:16:55","Sagemcom CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0003147025","Oko=
la","IHS_YND_530, IHS_YND_390","24-09-2024 10:58:28","24-09-2024 10:53:21",=
"24-09-2024 13:30:29","Active, no power issue on site, U=3D54,6V Team IKOUN=
TI/653110630 / From hammer is working on site (SWAP) ","TIENTCHEU NZETCHIEU=
 GAEL","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active, no power issue on site, U=3D54,6V Team IKOUNTI/6=
53110630 / From hammer is working on site (SWAP) ","joelle.ekessi@ihstowers=
.com","308","24-09-2024 10:58:28","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003146746","Pha=
rmacie SION","","24-09-2024 10:52:33","24-09-2024 10:50:29","24-09-2024 11:=
00:29","Grid outage, site went down before gen start due poor battery backu=
p // grid return","Paul BIBOUM","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage, site went down before gen sta=
rt due poor battery backup // grid return","joelle.ekessi@ihstowers.com","1=
25","24-09-2024 10:52:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003146364","A=
KONGO","","24-09-2024 10:37:48","24-09-2024 10:35:43","24-09-2024 11:40:43"=
,"Active:  No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rod=
rigue (655102999)from Huawei is informed. Repetitive issue ","Fanda Brice",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active:  No power issue on site Ubaie=3D52,5V site on Gen. The =
Tx FME Rodrigue (655102999)from Huawei is informed. Repetitive issue ","emm=
anuel.ghani@ihstowers.com","127","24-09-2024 10:37:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0003145968","Montee-J=
ouvence-II","","24-09-2024 09:46:30","24-09-2024 08:09:44","24-09-2024 08:4=
4:43","Cascaded Incident from TTO2997002","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down because CB O=
CM(125 A) disjunted in DCBOX // He reamad CB","system","5806","24-09-2024 0=
9:46:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003145910","N=
kol-Mbanda","IHS_YND_518","24-09-2024 09:40:02","24-09-2024 08:09:44","24-0=
9-2024 08:44:43","Site went down because CB OCM(125 A) disjunted in DCBOX /=
/ He reamad CB","MINKA NICOLAS","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Circuit Breaker Issue","Site went down because CB OCM(12=
5 A) disjunted in DCBOX // He reamad CB","kombi.samuel@ihstowers.com","5419=
","24-09-2024 09:40:02","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_248","NOCINC0003145810","Biteng","","24-0=
9-2024 09:22:58","","","","Mba Lazare Herve","","","","","","joelle.ekessi@=
ihstowers.com","139","24-09-2024 09:22:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0003145585","M=
atomb","","24-09-2024 08:54:10","24-09-2024 08:46:07","24-09-2024 09:20:07"=
,"Grid outage, site went down because gen ran untill fuel shortage // refue=
ling ongoing","Kemeni Franklin","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage, site went down because gen ran untill fuel shortage // =
refueling ongoing","emmanuel.ghani@ihstowers.com","484","24-09-2024 08:54:1=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0003145522","Mendong =
vallee","","24-09-2024 08:42:10","24-09-2024 08:35:27","24-09-2024 08:51:27=
","Cascaded Incident from TTO2996568","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage Site went down because=
 Gen stopped due to ""high temp"" alarm //He added water and gen manually s=
tarted","system","403","24-09-2024 08:42:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0003145523","Montee-J=
ouvence","","24-09-2024 08:42:10","24-09-2024 08:35:27","24-09-2024 08:51:2=
7","Cascaded Incident from TTO2996568","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage Site went down bec=
ause Gen stopped due to ""high temp"" alarm //He added water and gen manual=
ly started","system","403","24-09-2024 08:42:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0003145520","M=
endong","IHS_YND_692, IHS_YND_236","24-09-2024 08:40:32","24-09-2024 08:35:=
27","24-09-2024 08:51:27","Grid outage Site went down because Gen stopped d=
ue to ""high temp"" alarm //He added water and gen manually started","Hyema=
fo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp=
 - Coolant Level Issue","Grid outage Site went down because Gen stopped due=
 to ""high temp"" alarm //He added water and gen manually started","emmanue=
l.ghani@ihstowers.com","306","24-09-2024 08:40:32","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0003145329","Car=
refour Simbock","","24-09-2024 08:04:50","24-09-2024 08:00:45","24-09-2024 =
09:03:22","Grid outage Site went down because Gen stopped due to ""high tem=
p"" alarm //He added water and gen manually started","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage Site went down because Gen stopped due to ""high temp"=
" alarm //He added water and gen manually started","joelle.ekessi@ihstowers=
.com","246","24-09-2024 08:04:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0003145036","M=
volye-New","","24-09-2024 06:49:41","24-09-2024 06:44:28","24-09-2024 06:56=
:28","Grid Outage//Grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","Grid Outage//Grid return","emmanuel.ghani@ihsto=
wers.com","314","24-09-2024 06:49:41","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003144928","Lad=
a I Yde","","24-09-2024 06:24:17","24-09-2024 06:21:14","24-09-2024 09:19:1=
2","Grid outage, site went down because gen ran untill fuel shortage // ref=
ueling Done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage, site went down because gen ran untill fuel shortage // =
refueling Done","joelle.ekessi@ihstowers.com","184","24-09-2024 06:24:17","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003144844","N=
kolondom","","24-09-2024 05:55:57","24-09-2024 05:48:53","24-09-2024 08:53:=
36","Grid outage , site went down because Gen started and stooped due to wa=
ter infiltration in the tank// He purged the Gen and removed water","Fabric=
e Pouakam","Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue =
- Water In The Fuel","Grid outage , site went down because Gen started and =
stooped due to water infiltration in the tank// He purged the Gen and remov=
ed water","ludivine.ngamaleu@ihstowers.com","425","24-09-2024 05:55:57","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003144484","Nom=
ayos montee Meche","","24-09-2024 03:24:08","24-09-2024 03:14:59","24-09-20=
24 06:30:42","Access issue during the night due to landlord (Site went down=
 because gen ran untill fuel shortage // refueling done)","Fanda Brice","Ac=
cess Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Lan=
d Lord","Access issue during the night due to landlord (Site went down beca=
use gen ran untill fuel shortage // refueling done)","olivier.kwedi@ihstowe=
rs.com","550","24-09-2024 03:24:08","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0003144251","EBO=
M","","24-09-2024 02:01:48","23-09-2024 21:30:25","24-09-2024 02:58:43","No=
 power issue, site is on grid with Ubaie=3D53V, Lionel adjep(655184876) fro=
m Huawei is informed","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site is =
on grid with Ubaie=3D53V, Lionel adjep(655184876) from Huawei is informed",=
"olivier.kwedi@ihstowers.com","16284","24-09-2024 02:01:48","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0003144187","Men=
dong NB","","24-09-2024 01:48:07","24-09-2024 01:29:50","24-09-2024 08:08:0=
9","Access issue during the night (Grid Outage No Space to deploy a MDG//Gr=
id Restored)","","Access Denial","Lease Or Legal","Landlord Related Issues"=
,"Access Issue - Land Lord","Access issue during the night (Grid Outage No =
Space to deploy a MDG//Grid Restored)","etienne.itondo@ihstowers.com","1097=
","24-09-2024 01:48:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_415","NOCINC0003143585","Boga-Mah=
ole","","23-09-2024 23:05:23","23-09-2024 22:50:08","23-09-2024 23:56:10","=
Cascaded Incident from TTO2994306","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen ran untill fuel shortage // refueling done","system","915","23-09-20=
24 23:05:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003143584","Mamb",""=
,"23-09-2024 23:05:23","23-09-2024 22:50:08","23-09-2024 23:56:10","Cascade=
d Incident from TTO2994306","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because gen =
ran untill fuel shortage // refueling done","system","915","23-09-2024 23:0=
5:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0003143582","Song-bon=
g","","23-09-2024 23:05:23","23-09-2024 22:50:08","23-09-2024 23:56:10","Ca=
scaded Incident from TTO2994306","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen ran untill fuel shortage // refueling done","system","915","23-09-2024=
 23:05:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_377","NOCINC0003143580","Eseka OC=
M","","23-09-2024 23:05:22","23-09-2024 22:50:08","23-09-2024 23:56:10","Ca=
scaded Incident from TTO2994306","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen ran untill fuel shortage // refueling done","system","914","23-09-2024=
 23:05:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003143576","Boumnyeb=
el","","23-09-2024 23:05:22","23-09-2024 22:50:08","23-09-2024 23:56:10","C=
ascaded Incident from TTO2994306","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // refueling done","system","914","23-09-202=
4 23:05:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_380","NOCINC0003143570","Boumnyeb=
el OCM","","23-09-2024 23:05:21","23-09-2024 22:50:08","23-09-2024 23:56:10=
","Cascaded Incident from TTO2994306","Kemeni Franklin","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause gen ran untill fuel shortage // refueling done","system","912","23-09=
-2024 23:05:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0003143571","Eseka To=
wn","","23-09-2024 23:05:21","23-09-2024 22:50:08","23-09-2024 23:56:10","C=
ascaded Incident from TTO2994306","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // refueling done","system","913","23-09-202=
4 23:05:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003143572","Ndogbess=
ol","","23-09-2024 23:05:21","23-09-2024 22:50:08","23-09-2024 23:56:10","C=
ascaded Incident from TTO2994306","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen ran untill fuel shortage // refueling done","system","913","23-09-202=
4 23:05:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003143575","Ngog Map=
ubi","","23-09-2024 23:05:21","23-09-2024 22:50:08","23-09-2024 23:56:10","=
Cascaded Incident from TTO2994306","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se gen ran untill fuel shortage // refueling done","system","913","23-09-20=
24 23:05:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003142943","N=
kolondom","","23-09-2024 21:05:16","23-09-2024 20:57:10","23-09-2024 22:08:=
17","grid outage, main gen faulty// grid return","Fabrice Pouakam","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Generator Faulty","grid outage, mai=
n gen faulty// grid return","alexandre.kamal@ihstowers.com","487","23-09-20=
24 21:05:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003142853","L=
abogenie","","23-09-2024 20:44:55","23-09-2024 20:23:49","23-09-2024 20:45:=
49","grid outage,no space to deploy a mobil gen//grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no sp=
ace to deploy a mobil gen//grid return","alexandre.kamal@ihstowers.com","12=
67","23-09-2024 20:44:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0003142754","EBOM",""=
,"23-09-2024 20:25:01","23-09-2024 20:14:26","23-09-2024 20:28:26","Cascade=
d Incident from TTO2993337","Hyemafo Gildas","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because CB 2*125A disjunct=
ed in DC-BOX Ocm//he reamed the CB","system","635","23-09-2024 20:25:01","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0003142739","Ahala","=
","23-09-2024 20:23:50","23-09-2024 20:14:26","23-09-2024 20:28:26","Cascad=
ed Incident from TTO2993337","Hyemafo Gildas","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site went down because CB 2*125A disjunc=
ted in DC-BOX Ocm//he reamed the CB","system","564","23-09-2024 20:23:50","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003142711","A=
hala","IHS_YND_257, IHS_YND_698","23-09-2024 20:20:33","23-09-2024 20:14:26=
","23-09-2024 20:28:26","site went down because CB 2*125A disjuncted in DC-=
BOX Ocm//he reamed the CB","MINKA NICOLAS","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Circuit Breaker Issue","site went down becaus=
e CB 2*125A disjuncted in DC-BOX Ocm//he reamed the CB","alexandre.kamal@ih=
stowers.com","368","23-09-2024 20:20:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003142701","M=
vog-Manga","","23-09-2024 20:19:51","23-09-2024 20:10:46","23-09-2024 20:55=
:00","Site went down due to insuffisance of rectifier// Site stabilized","A=
lbran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","=
Site went down due to insuffisance of rectifier// Site stabilized","alexand=
re.kamal@ihstowers.com","546","23-09-2024 20:19:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003142390","M=
fou EPC","","23-09-2024 19:26:46","23-09-2024 19:15:42","23-09-2024 19:32:4=
2","Grid outage site went down because Gen failed to start due to Gen card =
faulty// Grid power return","Mba Lazare Herve","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start due to Gen card faulty// Grid power return","alexandre.kama=
l@ihstowers.com","665","23-09-2024 19:26:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0003141795","P=
olytechnique","","23-09-2024 18:11:39","23-09-2024 17:58:31","23-09-2024 18=
:19:10","grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,n=
o space to deploy a mobil gen//grid return","alexandre.kamal@ihstowers.com"=
,"789","23-09-2024 18:11:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003141151","N=
kolondom","","23-09-2024 16:35:19","23-09-2024 16:24:15","23-09-2024 17:34:=
15","Grid Outage ,Gen started and  stopped due to ""low oil pressure"" alar=
m (unprouven alarm) //He reset Gen card and started Gen manualy","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","=
Grid Outage ,Gen started and  stopped due to ""low oil pressure"" alarm (un=
prouven alarm) //He reset Gen card and started Gen manualy","alexandre.kama=
l@ihstowers.com","666","23-09-2024 16:35:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003141032","N=
sam Sofavinc T0","","23-09-2024 16:24:12","23-09-2024 16:18:07","23-09-2024=
 17:15:26","grid outage,site went down because Gen overload(20 KVA,160A) //=
Grid return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG =
- Overload","grid outage,site went down because Gen overload(20 KVA,160A) /=
/Grid return","alexandre.kamal@ihstowers.com","366","23-09-2024 16:24:12","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003140748","Crf Corn=
ier","","23-09-2024 15:41:50","23-09-2024 14:41:46","23-09-2024 15:55:46","=
Cascaded Incident from TTO2991081","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down becasuse CB OCM  (2*=
63 A) disjuncted in Dcbox causing by  DC load increase//he replaced CB(2*63=
A)with another CB(2*125A)","system","3604","23-09-2024 15:41:50","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003140736","M=
adison","IHS_YND_566","23-09-2024 15:40:55","23-09-2024 14:41:46","23-09-20=
24 15:55:46","Site went down because CB OCM  (2*63 A) disjuncted in Dcbox c=
ausing by  DC load increase//he replaced CB(2*63A)with another CB(2*125A)",=
"MFOUAGUEGUE MATHIEU","Equipment Repair","Passive","Control Panel","Power C=
abinet - Circuit Breaker Issue","Site went down because CB OCM  (2*63 A) di=
sjuncted in Dcbox causing by  DC load increase//he replaced CB(2*63A)with a=
nother CB(2*125A)","alexandre.kamal@ihstowers.com","3550","23-09-2024 15:40=
:55","Sagemcom CMR"
"Cancelled","Warning","T1109","IHS_YND_287","NOCINC0003140118","Nkolafeme",=
"","23-09-2024 14:02:38","","","","TIENTCHEU NZETCHIEU GAEL","","","","",""=
,"stephane.nkamwa@ihstowers.com","976","23-09-2024 14:02:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003139905","B=
arriere","","23-09-2024 13:34:21","23-09-2024 12:06:55","23-09-2024 13:19:0=
3","site went down because the Cb(125A) of DcBox dysjoncted// He reamed the=
 Cb","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power C=
abinet - Circuit Breaker Issue","site went down because the Cb(125A) of DcB=
ox dysjoncted// He reamed the Cb","landry.etame@ihstowers.com","5246","23-0=
9-2024 13:34:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003139710","M=
arche Odza","","23-09-2024 13:10:06","23-09-2024 13:04:24","23-09-2024 13:0=
5:45","Active//No power issue Ubaie=3D54,5V site on Grid. TX FME Leonel Ste=
ve   (655184876) from Huawei is working on Site","Albran Byorel","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue Ubaie=3D54,5V site on Grid. TX FME Leonel Steve   =
(655184876) from Huawei is working on Site","landry.etame@ihstowers.com","3=
43","23-09-2024 13:10:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003139227","C=
rf-Nsam","","23-09-2024 12:24:39","23-09-2024 12:19:20","23-09-2024 13:07:2=
0","Site went down due to insufficient of rectifier on site// He reduced th=
e load","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down due to insufficient of rectifier on site// He redu=
ced the load","landry.etame@ihstowers.com","320","23-09-2024 12:24:39","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003138762","B=
arriere","","23-09-2024 11:49:39","23-09-2024 11:38:34","23-09-2024 11:55:3=
5","Grid fluctuation, site went down because gen start and stopped due to g=
rid bad voltage // he bypass grid and manually start the gen","Hyemafo Gild=
as","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage // he bypass grid and manually start the gen","landry.etame@=
ihstowers.com","665","23-09-2024 11:49:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0003138547","C=
arington","","23-09-2024 11:12:13","23-09-2024 11:01:06","23-09-2024 11:27:=
35","site went down because the Cb(63A) of DcBox dysjoncted// He made the B=
ridge betwen 2*63 (A)","","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Circuit Breaker Issue","site went down because the Cb(63A) of =
DcBox dysjoncted// He made the Bridge betwen 2*63 (A)","landry.etame@ihstow=
ers.com","669","23-09-2024 11:12:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_518","NOCINC0003138396","Montee-J=
ouvence-II","","23-09-2024 10:55:40","23-09-2024 09:56:38","24-09-2024 04:4=
7:38","Cascaded Incident from TTO2988593","Hyemafo Gildas","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid Outage Site went down =
due to Gen overload (20Kva, 290A), he went up BTS OCM ","system","3542","23=
-09-2024 10:55:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003138389","N=
kol-Mbanda","IHS_YND_518","23-09-2024 10:54:44","23-09-2024 09:56:38","24-0=
9-2024 04:47:38","Grid Outage Site went down due to Gen overload (20Kva, 29=
0A), he went up BTS OCM ","MINKA NICOLAS","Equipment Repair","Passive","ACD=
G Gen","ACDG - Overload","Grid Outage Site went down due to Gen overload (2=
0Kva, 290A), he went up BTS OCM ","landry.etame@ihstowers.com","3487","23-0=
9-2024 10:54:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0003138171","C=
hapelle-Nsimeyong","","23-09-2024 10:29:30","23-09-2024 10:23:25","23-09-20=
24 10:23:26","""No power issue Ubaie=3D54,4V site on Grid.The tx fme Mbah h=
osiah(674007438) from Huawei is informed,. Notice that disjonction in BTS o=
cm    The tx fme Mbah hosiah(674007438) from Huawei is informed ""","MINKA =
NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","""No power issue Ubaie=3D54,4V site on Grid.The tx fme=
 Mbah hosiah(674007438) from Huawei is informed,. Notice that disjonction i=
n BTS ocm    The tx fme Mbah hosiah(674007438) from Huawei is informed """,=
"landry.etame@ihstowers.com","366","23-09-2024 10:29:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003138111","A=
hala","","23-09-2024 10:20:57","23-09-2024 10:12:51","23-09-2024 10:32:51",=
"Grid outage site down due to poor backup before gen start // Gen started a=
utomatically","Hyemafo Gildas","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage site down due to poor backup be=
fore gen start // Gen started automatically","landry.etame@ihstowers.com","=
486","23-09-2024 10:20:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003138092","N=
sam Sofavinc T0","","23-09-2024 10:17:30","23-09-2024 10:10:18","23-09-2024=
 11:25:59","Grid outage, site went down because Gen start and stopped due t=
o Gen overload (09kva ,160A)// he reduiced the load on site","MINKA NICOLAS=
","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, s=
ite went down because Gen start and stopped due to Gen overload (09kva ,160=
A)// he reduiced the load on site","landry.etame@ihstowers.com","432","23-0=
9-2024 10:17:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003137720","T=
amtam Weekend","","23-09-2024 09:03:23","23-09-2024 08:57:59","23-09-2024 0=
9:00:31","Active: no power issue, site is on grid with Ubaie=3D54,4V, the f=
me tx Mbah Hosiah(699699694) from Huawei is informed, repetitif issue","Hye=
mafo Gildas","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active: no power issue, site is on grid with Ubaie=
=3D54,4V, the fme tx Mbah Hosiah(699699694) from Huawei is informed, repeti=
tif issue","landry.etame@ihstowers.com","325","23-09-2024 09:03:23","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003137242","N=
kolndongo","","23-09-2024 07:27:05","23-09-2024 02:09:56","23-09-2024 06:29=
:49","Grid outage site went down because Main Gen faulty// Grid power retur=
n","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generato=
r Faulty","Grid outage site went down because Main Gen faulty// Grid power =
return","landry.etame@ihstowers.com","19030","23-09-2024 07:27:05","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0003137218","Montee-J=
ouvence","","23-09-2024 07:19:21","23-09-2024 07:12:06","23-09-2024 07:34:4=
3","Cascaded Incident from TTO2987269","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive"," Grid Outage, site went down b=
ecause Gen Start and stopped due to ""high temp"" alarm //He added water an=
d Gen manually started","system","435","23-09-2024 07:19:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0003137216","M=
endong","IHS_YND_236","23-09-2024 07:18:11","23-09-2024 07:12:06","23-09-20=
24 07:34:43"," Grid Outage, site went down because Gen Start and stopped du=
e to ""high temp"" alarm //He added water and Gen manually started","Hyemaf=
o Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp =
- Coolant Level Issue"," Grid Outage, site went down because Gen Start and =
stopped due to ""high temp"" alarm //He added water and Gen manually starte=
d","landry.etame@ihstowers.com","366","23-09-2024 07:18:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0003137080","E=
koumdoum","","23-09-2024 06:43:21","23-09-2024 06:36:12","23-09-2024 07:33:=
46","Grid Outage, site went down before Gen start due to poor backup// Gen =
started automatically","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage  site down due to poor =
backup before gen start // Gen started automatically","landry.etame@ihstowe=
rs.com","430","23-09-2024 06:43:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0003136918","Okola OC=
M","","23-09-2024 06:01:40","23-09-2024 06:00:01","23-09-2024 06:52:33","Ca=
scaded Incident from TTO2986917","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","DG stopped due to burnt sw=
itch caused by Eneo fluctuations // DG put in direct mode","system","99","2=
3-09-2024 06:01:40","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0003136915","SIM=
BOCK BONAMBAPE","","23-09-2024 06:01:26","23-09-2024 05:55:01","23-09-2024 =
06:27:30","Grid outage, site went down because gen ran untill fuel shortage=
 // refueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Dies=
el Outage","Grid outage, site went down because gen ran untill fuel shortag=
e // refueling done","olivier.kwedi@ihstowers.com","386","23-09-2024 06:01:=
26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003136880","ELOUMDEM=
 CARRIERE 2","","23-09-2024 05:55:21","23-09-2024 05:47:34","23-09-2024 06:=
15:19","Cascaded Incident from TTO2986879","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause gen ran untill fuel shortage // refueling done","system","467","23-0=
9-2024 05:55:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003136879","Eto koss=
 Yde","","23-09-2024 05:55:20","23-09-2024 05:47:34","23-09-2024 06:15:19",=
"Cascaded Incident from TTO2986879","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
gen ran untill fuel shortage // refueling done","system","466","23-09-2024 =
05:55:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003136871","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","23-09-2024 05:52:48","23-09-2024 05:=
45:34","23-09-2024 06:15:19","Grid outage, site went down because gen ran u=
ntill fuel shortage // refueling done","Fanda Brice","Fuel Outage","Passive=
","Diesel","Diesel Outage","Grid outage, site went down because gen ran unt=
ill fuel shortage // refueling done","denis.mballa@ihstowers.com","436","23=
-09-2024 05:52:48","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003136852","Nko=
g-Edzen","","23-09-2024 05:48:12","23-09-2024 05:40:47","23-09-2024 06:56:4=
7","Site on DG due to grid outage, DG stopped due to high temp // DG door o=
pened and DG restarted","Parker Tchoup","Equipment Repair","Passive","ACDG =
Gen","ACDG - High Engine Temp - Coolant Level Issue","Site on DG due to gri=
d outage, DG stopped due to high temp // DG door opened and DG restarted","=
olivier.kwedi@ihstowers.com","446","23-09-2024 05:48:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003136848","M=
endong vallee","","23-09-2024 05:46:47","23-09-2024 05:39:36","23-09-2024 0=
6:36:41","Grid outage, site went down because gen ran untill fuel shortage =
// refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel O=
utage","Grid outage, site went down because gen ran untill fuel shortage //=
 refueling done","denis.mballa@ihstowers.com","432","23-09-2024 05:46:47","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0003136757","A=
cropole","","23-09-2024 05:21:28","23-09-2024 03:27:14","23-09-2024 05:15:0=
2","Site went down due to CB (63A) Disjunted during the rain due to lightni=
ng strikes  //He reamed the Rectifier CB and Site is on Grid ","MINKA NICOL=
AS","Force Majeure","Natural Disaster","Thunderstrike","Equipment Damaged",=
"Site went down due to CB (63A) Disjunted during the rain due to lightning =
strikes  //He reamed the Rectifier CB and Site is on Grid ","denis.mballa@i=
hstowers.com","6855","23-09-2024 05:21:28","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003136651","Odz=
a II","","23-09-2024 04:42:01","23-09-2024 04:26:31","23-09-2024 06:15:38",=
"Grid outage, site went down because gen ran untill fuel shortage // refuel=
ing done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran untill fuel shortage // refuel=
ing done","olivier.kwedi@ihstowers.com","969","23-09-2024 04:42:01","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_230","IHS_YND_393","NOCINC0003136560","E=
zezang","","23-09-2024 04:05:34","23-09-2024 03:57:13","23-09-2024 04:10:37=
","Site was on Gen due to grid outage, Gen ran till fuel shortage//Refuelin=
g done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","S=
ite was on Gen due to grid outage, Gen ran till fuel shortage//Refueling do=
ne","denis.mballa@ihstowers.com","502","23-09-2024 04:05:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003136534","N=
yom OCM","","23-09-2024 03:54:19","23-09-2024 02:47:01","23-09-2024 04:55:3=
6","Active//No power issue on site U=3D54,4V site on Grid  The Tx Fme Synph=
orien /691316854/ of huawei is informed","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue on site U=3D54,4V site on Grid  The Tx Fme Synphorien /6=
91316854/ of huawei is informed","denis.mballa@ihstowers.com","4039","23-09=
-2024 03:54:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003136530","Dong",""=
,"23-09-2024 03:52:23","23-09-2024 03:10:59","23-09-2024 05:21:31","Cascade=
d Incident from TTO2986439","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","no power issue on site Ubaie:54,3V site on Ge=
n, Raoul (691144462/Huawei) is informed ","system","2484","23-09-2024 03:52=
:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003136529","Donga","=
","23-09-2024 03:52:23","23-09-2024 03:10:59","23-09-2024 05:21:31","Cascad=
ed Incident from TTO2986439","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","no power issue on site Ubaie:54,3V site on G=
en, Raoul (691144462/Huawei) is informed ","system","2484","23-09-2024 03:5=
2:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0003136522","Okola OC=
M","","23-09-2024 03:52:21","23-09-2024 03:10:59","23-09-2024 05:21:31","Ca=
scaded Incident from TTO2986439","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Active","Cascade Active","Cascade Active","no power issue on site Ubaie:=
54,3V site on Gen, Raoul (691144462/Huawei) is informed ","system","2482","=
23-09-2024 03:52:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003136520","Nguila",=
"","23-09-2024 03:52:21","23-09-2024 03:10:59","23-09-2024 05:21:31","Casca=
ded Incident from TTO2986439","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","no power issue on site Ubaie:54,3V site on =
Gen, Raoul (691144462/Huawei) is informed ","system","2482","23-09-2024 03:=
52:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_424","NOCINC0003136515","Ossombe"=
,"","23-09-2024 03:52:20","23-09-2024 03:10:59","23-09-2024 05:21:31","Casc=
aded Incident from TTO2986439","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","no power issue on site Ubaie:54,3V site on=
 Gen, Raoul (691144462/Huawei) is informed ","system","2481","23-09-2024 03=
:52:20","Sagemcom CMR"
"Closed Complete","Site Down","T0294","IHS_YND_016","NOCINC0003136300","Mae=
tur","","23-09-2024 02:36:54","23-09-2024 02:27:44","23-09-2024 03:13:05","=
Grid Outage, site went down because Gen stopped due to ""Digital Input b"" =
alarm //He reset Card Gen and gen manually started","Mboua Thierry","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage, site =
went down because Gen stopped due to ""Digital Input b"" alarm //He reset C=
ard Gen and gen manually started","olivier.kwedi@ihstowers.com","551","23-0=
9-2024 02:36:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0003136260","A=
v-Germaine","","23-09-2024 02:19:15","23-09-2024 02:09:02","23-09-2024 05:3=
1:55","The site was not down.","","Incorrectly Logged Tickets","Error","Err=
or","Error","The site was not down.","denis.mballa@ihstowers.com","614","23=
-09-2024 02:19:15","Sagemcom CMR"
"Closed Complete","Site Down","T0219","IHS_YND_024","NOCINC0003136224","Gar=
bati building","","23-09-2024 02:02:08","23-09-2024 01:55:01","23-09-2024 0=
4:33:04","Site on DG due to grid outage,DG stopped due to fuel shortage //R=
efueling done.","Delor Telezing","Fuel Outage","Passive","Diesel","Diesel O=
utage","Site on DG due to grid outage,DG stopped due to fuel shortage //Ref=
ueling done.","olivier.kwedi@ihstowers.com","428","23-09-2024 02:02:08","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0003136154","ODZ=
A BORNE 10","","23-09-2024 01:30:02","23-09-2024 01:22:54","23-09-2024 01:3=
8:01","Grid fluctuation , site went down because gen start and stoppen with=
 alarm overcurrent// Grid stabilized","Albran Byorel","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid fluctuation , site went dow=
n because gen start and stoppen with alarm overcurrent// Grid stabilized","=
olivier.kwedi@ihstowers.com","429","23-09-2024 01:30:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003136137","ELOUMDEM=
 CARRIERE","","23-09-2024 01:27:00","23-09-2024 01:15:43","23-09-2024 01:43=
:38","Cascaded Incident from TTO2986015","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage,site went down befo=
re DG start : Poor Batteries Backup //Grid restored.","system","677","23-09=
-2024 01:27:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003136138","MBALNGON=
G LYCEE","","23-09-2024 01:27:00","23-09-2024 01:15:43","23-09-2024 01:43:3=
8","Cascaded Incident from TTO2986015","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down before=
 DG start : Poor Batteries Backup //Grid restored.","system","677","23-09-2=
024 01:27:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003136139","Afanoya"=
,"","23-09-2024 01:27:00","23-09-2024 01:15:43","23-09-2024 01:43:38","Casc=
aded Incident from TTO2986015","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site went down before DG s=
tart : Poor Batteries Backup //Grid restored.","system","677","23-09-2024 0=
1:27:00","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003136130","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","23-09-2024 01:25:51","23-09-20=
24 01:15:43","23-09-2024 01:43:38","Grid outage,site went down before DG st=
art : Poor Batteries Backup //Grid restored.","Hyemafo Gildas","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
,site went down before DG start : Poor Batteries Backup //Grid restored.","=
olivier.kwedi@ihstowers.com","609","23-09-2024 01:25:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003136118","Abattoir=
","","23-09-2024 01:21:10","23-09-2024 01:11:33","23-09-2024 01:45:31","Cas=
caded Incident from TTO2986001","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage,DG failed due to ACDG Co=
ntrol Panel Faulty // Grid restored.","system","577","23-09-2024 01:21:10",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003136119","ETOUDI C=
HAPELLE","","23-09-2024 01:21:10","23-09-2024 01:11:33","23-09-2024 01:45:3=
1","Cascaded Incident from TTO2986001","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage,DG failed due to A=
CDG Control Panel Faulty // Grid restored.","system","577","23-09-2024 01:2=
1:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003136120","Etoudi 2=
","","23-09-2024 01:21:10","23-09-2024 01:11:33","23-09-2024 01:45:31","Cas=
caded Incident from TTO2986001","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage,DG failed due to ACDG Co=
ntrol Panel Faulty // Grid restored.","system","577","23-09-2024 01:21:10",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003136116","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","23-09-2024 01:19:54","23-09-2=
024 01:11:33","23-09-2024 01:45:31","Grid Outage,DG failed due to ACDG Cont=
rol Panel Faulty // Grid restored.","Fabrice Pouakam","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid Outage,DG failed due to ACD=
G Control Panel Faulty // Grid restored.","olivier.kwedi@ihstowers.com","50=
2","23-09-2024 01:19:54","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003136059","Ema=
na","","23-09-2024 00:57:13","23-09-2024 00:47:02","23-09-2024 07:33:30","A=
ccess Issue during the Night due to Landlord,Grid outage site went down bec=
ause Gen started and stopped with alarm Gen fermez// He reset the Gen Card =
anad Gen started","Fabrice Pouakam","Access Denial","Lease Or Legal","Landl=
ord Related Issues","Access Issue - Land Lord","Access Issue during the Nig=
ht due to Landlord,Grid outage site went down because Gen started and stopp=
ed with alarm Gen fermez// He reset the Gen Card anad Gen started","olivier=
.kwedi@ihstowers.com","612","23-09-2024 00:57:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003136033","E=
mana","","23-09-2024 00:50:44","23-09-2024 00:10:28","23-09-2024 01:56:13",=
"Grid outage//He deployed 20Kva","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Outage Issue","Grid outage//He deployed 20Kva","denis.mballa@=
ihstowers.com","2418","23-09-2024 00:50:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003136030","N=
kolda","","23-09-2024 00:47:16","23-09-2024 00:44:03","23-09-2024 02:56:10"=
,"Grid outage,DG failed to start due to Generator Battery Faulty //He start=
ed  DG with External Battery","Albran Byorel","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Generator Battery","Grid outage,DG failed to start due t=
o Generator Battery Faulty //He started  DG with External Battery","denis.m=
balla@ihstowers.com","194","23-09-2024 00:47:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003136021","M=
fou EPC","","23-09-2024 00:43:52","23-09-2024 00:40:40","23-09-2024 02:48:2=
8","Grid outage,DG failed to start due to ACDG control panel Faulty //Manua=
lly start of DG.","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen=
","ACDG - Control Panel","Grid outage,DG failed to start due to ACDG contro=
l panel Faulty //Manually start of DG.","denis.mballa@ihstowers.com","193",=
"23-09-2024 00:43:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003136020","MEHANDAN=
","","23-09-2024 00:43:20","23-09-2024 00:33:52","23-09-2024 01:14:18","Cas=
caded Incident from TTO2985877","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site went down because Gen=
 started and Stopped with Alarm "" under Frequency""//Grid power return","s=
ystem","568","23-09-2024 00:43:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003136018","O=
dza II OCM","IHS_YND_528","23-09-2024 00:42:08","23-09-2024 00:33:52","23-0=
9-2024 01:14:18","Grid outage,site went down because Gen started and Stoppe=
d with Alarm "" under Frequency""//Grid power return","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,site=
 went down because Gen started and Stopped with Alarm "" under Frequency""/=
/Grid power return","denis.mballa@ihstowers.com","498","23-09-2024 00:42:08=
","Sagemcom CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0003135933","Odz=
a Minkan IHS","","23-09-2024 00:24:17","23-09-2024 00:20:57","23-09-2024 03=
:30:33","No power issue on site U=3D53,7v site on Grid lionel steeve (65518=
4876) of huawei is informed and Up at 12:24 AM.","Albran Byorel","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site U=3D53,7v site on Grid lionel steeve (655184876) o=
f huawei is informed and Up at 12:24 AM.
.","olivier.kwedi@ihstowers.com","200","23-09-2024 00:24:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003135657","M=
elen Ba'aba","","22-09-2024 22:54:08","22-09-2024 22:50:54","22-09-2024 22:=
59:54","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen started automatically","Siligap Boris","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen started automatical=
ly","denis.mballa@ihstowers.com","195","22-09-2024 22:54:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0003135544","C=
arington","","22-09-2024 22:19:28","22-09-2024 20:24:16","23-09-2024 10:08:=
03","Access issue due to Landlord, site went down because the Cb(75A) of Dc=
Box dysjoncted// He reamed the Cb","","Access Denial","Lease Or Legal","Lan=
dlord Related Issues","Access Issue - Land Lord","Access issue due to Landl=
ord, site went down because the Cb(75A) of DcBox dysjoncted// He reamed the=
 Cb","ludivine.ngamaleu@ihstowers.com","6914","22-09-2024 22:19:28","Sagemc=
om CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003135318","Odz=
a II","","22-09-2024 21:39:01","22-09-2024 21:36:43","22-09-2024 22:25:32",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen manually started","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
gen start due to poor battery backup // Gen manually started","landry.etame=
@ihstowers.com","139","22-09-2024 21:39:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0003135237","H-Franco=
 New","","22-09-2024 21:28:20","22-09-2024 21:09:33","23-09-2024 09:21:59",=
"Cascaded Incident from TTO2984982","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Access Issue during the Night, si=
te went down because the Cb(40A) of PWC ZTE faulty// He bypass the Cb","sys=
tem","1127","22-09-2024 21:28:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0003135232","D=
joungolo","IHS_YND_711","22-09-2024 21:27:36","22-09-2024 21:09:33","23-09-=
2024 09:21:59","Access Issue during the Night, site went down because the C=
b(40A) of PWC ZTE faulty// He bypass the Cb","Mboua Thierry","Access Denial=
","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Ac=
cess Issue during the Night, site went down because the Cb(40A) of PWC ZTE =
faulty// He bypass the Cb","ludivine.ngamaleu@ihstowers.com","1084","22-09-=
2024 21:27:36","Sagemcom CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0003135147","Clu=
b France","","22-09-2024 21:15:16","22-09-2024 21:11:37","22-09-2024 23:03:=
07","Grid outage,no space to deploy a mobile DG,waiting for grid restored//=
Grid restored.","","Grid Supply","Passive","Grid","National Grid - Grid Out=
age Issue","Grid outage,no space to deploy a mobile DG,waiting for grid res=
tored//Grid restored.","landry.etame@ihstowers.com","219","22-09-2024 21:15=
:16","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003134829","Mvo=
g-Betsi","","22-09-2024 20:25:41","22-09-2024 20:08:30","22-09-2024 20:26:5=
8","site went down due to insufficient of rectifier// He reset controler, s=
ite on grid","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","site went down due to insufficient of rectifier// He reset =
controler, site on grid","landry.etame@ihstowers.com","1032","22-09-2024 20=
:25:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0003134815","Crf-Mban=
kolo-IHS","","22-09-2024 20:24:10","22-09-2024 20:06:00","22-09-2024 20:24:=
54","Cascaded Incident from TTO2984505","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, Site went down du=
e to insufficiency of rectifier on site // He added 01 rectifier, site on g=
en","system","1090","22-09-2024 20:24:10","Sagemcom CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0003134809","Jea=
n Vespa","IHS_YND_574","22-09-2024 20:23:05","22-09-2024 20:06:00","22-09-2=
024 20:24:54","grid outage, Site went down due to insufficiency of rectifie=
r on site // He added 01 rectifier, site on gen","Mboua Thierry","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","grid outage, Site went d=
own due to insufficiency of rectifier on site // He added 01 rectifier, sit=
e on gen","landry.etame@ihstowers.com","1026","22-09-2024 20:23:05","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003134743","M=
ontee-Jouvence-II","","22-09-2024 20:12:22","22-09-2024 20:07:17","22-09-20=
24 20:17:53","Active: no power issue, site is on grid with Ubaie=3D53V, Mba=
h Hosiah(699699694) from Huawei is informed","Hyemafo Gildas","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive: no power issue, site is on grid with Ubaie=3D53V, Mbah Hosiah(699699=
694) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","306","22-0=
9-2024 20:12:22","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0003134698","Nko=
l-Mbanda","","22-09-2024 20:04:42","22-09-2024 19:55:35","23-09-2024 09:55:=
08","site went down because Gen overload (20Kva, 290A)// he went up BTS MTN=
 and left BTS OCM","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","site went down because Gen overload (20Kva, 290A)// he w=
ent up BTS MTN and left BTS OCM","landry.etame@ihstowers.com","548","22-09-=
2024 20:04:42","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003134443","Odz=
a II","","22-09-2024 19:01:35","22-09-2024 18:53:24","22-09-2024 19:45:42",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen manually started","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
gen start due to poor battery backup // Gen manually started","landry.etame=
@ihstowers.com","540","22-09-2024 19:01:35","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0003134252","Mel=
en Ba'aba","","22-09-2024 18:40:07","22-09-2024 18:35:43","22-09-2024 19:18=
:54","grid outage, site went down because gen start and stoppen  with alarm=
 undervoltage// He reset gen card and gen manually started","Siligap Boris"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outag=
e, site went down because gen start and stoppen  with alarm undervoltage// =
He reset gen card and gen manually started","landry.etame@ihstowers.com","1=
448","22-09-2024 18:40:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0003134204","E=
BOM","","22-09-2024 18:27:57","22-09-2024 18:27:54","22-09-2024 18:28:19","=
site went down because gen failed to start due to grid bad voltage// grid s=
tabilized","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","site went down because gen failed to start due t=
o grid bad voltage// grid stabilized","ludivine.ngamaleu@ihstowers.com","4"=
,"22-09-2024 18:27:57","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_046","NOCINC0003134153","Djoungolo"=
,"","22-09-2024 18:16:39","","","site went ALARM, because the Cb(40A) of PW=
C ZTE faulty// He bypass the Cb","Mboua Thierry","Warning","Warning","POWER=
","Warning - Faulty Circuit Breaker","site went ALARM, because the Cb(40A) =
of PWC ZTE faulty// He bypass the Cb","etienne.itondo@ihstowers.com","2665"=
,"22-09-2024 18:16:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0003134053","Nkolondo=
m","","22-09-2024 17:51:22","22-09-2024 17:43:50","22-09-2024 18:05:13","Ca=
scaded Incident from TTO2983631","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because gen failed t=
o start due to grid bad voltage// gen manually started","system","452","22-=
09-2024 17:51:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0003134050","Nkozoa",=
"","22-09-2024 17:51:21","22-09-2024 17:43:50","22-09-2024 18:05:13","Casca=
ded Incident from TTO2983631","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because gen failed to s=
tart due to grid bad voltage// gen manually started","system","451","22-09-=
2024 17:51:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0003134049","Messassi=
","","22-09-2024 17:51:21","22-09-2024 17:43:50","22-09-2024 18:05:13","Cas=
caded Incident from TTO2983631","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because gen failed to=
 start due to grid bad voltage// gen manually started","system","451","22-0=
9-2024 17:51:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0003134051","Nyom OCM=
","","22-09-2024 17:51:21","22-09-2024 17:43:50","22-09-2024 18:05:13","Cas=
caded Incident from TTO2983631","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because gen failed to=
 start due to grid bad voltage// gen manually started","system","451","22-0=
9-2024 17:51:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0003134052","Messassi=
 2","","22-09-2024 17:51:21","22-09-2024 17:43:50","22-09-2024 18:05:13","C=
ascaded Incident from TTO2983631","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because gen failed =
to start due to grid bad voltage// gen manually started","system","451","22=
-09-2024 17:51:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0003134048","Olembe-T=
erminus","","22-09-2024 17:51:21","22-09-2024 17:43:50","22-09-2024 18:05:1=
3","Cascaded Incident from TTO2983631","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because gen fa=
iled to start due to grid bad voltage// gen manually started","system","451=
","22-09-2024 17:51:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0003134047","NKOLMEKO=
NG YDE","","22-09-2024 17:51:20","22-09-2024 17:43:50","22-09-2024 18:05:13=
","Cascaded Incident from TTO2983631","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down because gen fai=
led to start due to grid bad voltage// gen manually started","system","450"=
,"22-09-2024 17:51:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0003134046","Ekombiti=
e","","22-09-2024 17:51:20","22-09-2024 17:43:50","22-09-2024 18:05:13","Ca=
scaded Incident from TTO2983631","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because gen failed t=
o start due to grid bad voltage// gen manually started","system","450","22-=
09-2024 17:51:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003134036","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_280, IHS_YND_304","22-09-2024 17:47:55","22-09-2024 17:4=
3:50","22-09-2024 18:05:13","site went down because gen failed to start due=
 to grid bad voltage// gen manually started","Fabrice Pouakam","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","site went dow=
n because gen failed to start due to grid bad voltage// gen manually starte=
d","ludivine.ngamaleu@ihstowers.com","246","22-09-2024 17:47:55","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003134006","M=
arche Odza","","22-09-2024 17:37:48","22-09-2024 17:18:35","22-09-2024 18:0=
8:29","Grid outage,gen ran until fuel shortage//Refueling done.power resolv=
ed since 06:08 PM and power reset has beeen done but the site remain down.T=
X FME Lionel steve/655184876 from Huawei is informed ","Albran Byorel","Fue=
l Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran until fue=
l shortage//Refueling done..power resolved since 06:08 PM and power reset h=
as beeen done but the site remain down.TX FME Lionel steve/655184876 from H=
uawei is informed ","etienne.itondo@ihstowers.com","1155","22-09-2024 17:37=
:48","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003133984","Nsi=
meyong Shell","","22-09-2024 17:30:57","22-09-2024 17:15:49","22-09-2024 17=
:35:35","Grid outage, site went down before gen start due to poor battery b=
ackup // gen start automatically","MINKA NICOLAS","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // gen start automatically"=
,"landry.etame@ihstowers.com","909","22-09-2024 17:30:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_721","NOCINC0003133854","VOIRIE M=
UNICIPALE YAOUNDE","","22-09-2024 16:57:21","22-09-2024 16:33:35","22-09-20=
24 18:28:32","Cascaded Incident from TTO2983326","Paul BIBOUM","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","site went down due to w=
ork(/kamdem/677548363/I-eng/ Swap PWC)// and of work","system","1426","22-0=
9-2024 16:57:21","Sagemcom CMR"
"Cancelled","Warning","CTR_632","IHS_YND_721","NOCINC0003133842","VOIRIE MU=
NICIPALE YAOUNDE","","22-09-2024 16:53:20","","","","Paul BIBOUM","","","",=
"","","ludivine.ngamaleu@ihstowers.com","1205","22-09-2024 16:53:20","Sagem=
com CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0003133773","ENA=
M","IHS_YND_721","22-09-2024 16:37:18","22-09-2024 16:33:35","22-09-2024 18=
:28:32","site went down due to work(/kamdem/677548363/I-eng/ Swap PWC)// an=
d of work","","Equipment Replacement","Passive","Planned Activity","Planned=
 Activity - Passive","site went down due to work(/kamdem/677548363/I-eng/ S=
wap PWC)// and of work","landry.etame@ihstowers.com","225","22-09-2024 16:3=
7:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003133606","S=
tade-Abega","","22-09-2024 16:09:00","22-09-2024 15:55:54","22-09-2024 17:4=
5:22","site went down because disjunction Cb(60A) due to water infiltration=
 in Pwc// He reamed Cb(60A), site on gen","Mba Lazare Herve","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","sit=
e went down because disjunction Cb(60A) due to water infiltration in Pwc// =
He reamed Cb(60A), site on gen","ludivine.ngamaleu@ihstowers.com","786","22=
-09-2024 16:09:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003133599","ELOUMDEM=
 CARRIERE","","22-09-2024 16:07:41","22-09-2024 16:00:23","22-09-2024 16:10=
:48","Cascaded Incident from TTO2983125","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, site went down bef=
ore Gen start due to poor backup// Gen started automatically","system","438=
","22-09-2024 16:07:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003133601","Afanoya"=
,"","22-09-2024 16:07:41","22-09-2024 16:00:23","22-09-2024 16:10:48","Casc=
aded Incident from TTO2983125","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, site went down before Gen=
 start due to poor backup// Gen started automatically","system","438","22-0=
9-2024 16:07:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003133600","MBALNGON=
G LYCEE","","22-09-2024 16:07:41","22-09-2024 16:00:23","22-09-2024 16:10:4=
8","Cascaded Incident from TTO2983125","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, site went down befor=
e Gen start due to poor backup// Gen started automatically","system","438",=
"22-09-2024 16:07:41","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003133595","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","22-09-2024 16:06:29","22-09-20=
24 16:00:23","22-09-2024 16:10:48","Grid Outage, site went down before Gen =
start due to poor backup// Gen started automatically","Hyemafo Gildas","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d Outage, site went down before Gen start due to poor backup// Gen started =
automatically","landry.etame@ihstowers.com","367","22-09-2024 16:06:29","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0003133523","A=
wae Escalier","","22-09-2024 15:51:04","22-09-2024 15:49:59","22-09-2024 16=
:40:33","Tx Issue,Site on grid,Ubaie:54.2V: Lionel/694-69-34-36 is informed=
.","Albran Byorel","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Tx Issue,Site on grid,Ubaie:54.2V: Lionel/69=
4-69-34-36 is informed.","ludivine.ngamaleu@ihstowers.com","66","22-09-2024=
 15:51:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0003133492","M=
atomb","","22-09-2024 15:46:39","22-09-2024 15:39:35","22-09-2024 16:58:08"=
,"Grid outage, site went down because gen ran untill fuel shortage // refue=
lling done","Kemeni Franklin","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran untill fuel shortage // re=
fuelling done","ludivine.ngamaleu@ihstowers.com","425","22-09-2024 15:46:39=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003133442","Crf Corn=
ier","","22-09-2024 15:36:00","22-09-2024 15:24:59","22-09-2024 15:25:59","=
Cascaded Incident from TTO2982928","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Active//No power issue, site is on =
Grid with Ubaie=3D53,1V, The fme TX Armand Nguetsa(699949553) from Huawei i=
s informed","system","661","22-09-2024 15:36:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003133422","M=
adison","IHS_YND_566","22-09-2024 15:34:29","22-09-2024 15:24:59","23-09-20=
24 09:20:26","site went due to DC load increase Because the PWC is overload=
 (24 KW, 208 A) and  power cable DC heating  // Site up DC dicrease (power =
come from Essos March=E9)","MFOUAGUEGUE MATHIEU","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module Overloaded","site went due to DC load incr=
ease Because the PWC is overload (24 KW, 208 A) and  power cable DC heating=
  // Site up DC dicrease (power come from Essos March=E9)","ludivine.ngamal=
eu@ihstowers.com","570","22-09-2024 15:34:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0003133420","A=
nguissa New","","22-09-2024 15:33:33","22-09-2024 15:20:04","23-09-2024 08:=
55:56","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid outage, no space to deploy a mobil, grid return awaited=
","ludivine.ngamaleu@ihstowers.com","5939","22-09-2024 15:33:33","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003133412","K=
oweit City","","22-09-2024 15:30:42","22-09-2024 15:22:38","22-09-2024 19:1=
7:09","Active: No power issue, site is on gen with Ubaie=3D56.2V, Lionel st=
eeve(655184876) from Huawei is informed","Albran Byorel","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
: No power issue, site is on gen with Ubaie=3D56.2V, Lionel steeve(65518487=
6) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","485","22-09-=
2024 15:30:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003133407","Abattoir=
","","22-09-2024 15:29:50","22-09-2024 15:20:40","22-09-2024 15:50:32","Cas=
caded Incident from TTO2982898","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, site went down because =
gen failed to start due to gen card faulty// Gen manually started","system"=
,"550","22-09-2024 15:29:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003133408","ETOUDI C=
HAPELLE","","22-09-2024 15:29:50","22-09-2024 15:20:40","22-09-2024 15:50:3=
2","Cascaded Incident from TTO2982898","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, site went down be=
cause gen failed to start due to gen card faulty// Gen manually started","s=
ystem","550","22-09-2024 15:29:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003133409","Etoudi 2=
","","22-09-2024 15:29:50","22-09-2024 15:20:40","22-09-2024 15:50:32","Cas=
caded Incident from TTO2982898","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, site went down because =
gen failed to start due to gen card faulty// Gen manually started","system"=
,"550","22-09-2024 15:29:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003133401","L=
abogenie","IHS_YND_568","22-09-2024 15:28:11","22-09-2024 15:20:04","23-09-=
2024 08:55:56","Grid outage no space to deploy a mobil// grid return ","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age no space to deploy a mobil// grid return ","ludivine.ngamaleu@ihstowers=
.com","487","22-09-2024 15:28:11","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003133400","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","22-09-2024 15:28:10","22-09-2=
024 15:20:40","22-09-2024 16:01:01","grid outage, site went down because ge=
n failed to start due to gen card faulty// Gen manually started","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","gri=
d outage, site went down because gen failed to start due to gen card faulty=
// Gen manually started","landry.etame@ihstowers.com","451","22-09-2024 15:=
28:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0003133362","N=
gousso-Savana","IHS_YND_561","22-09-2024 15:19:52","22-09-2024 15:09:59","2=
2-09-2024 16:15:18","grid outage,site went down due to Cb(2*100A) disjuncte=
d in DC Box OCM and poor battery backup// He reamed Cb(2*100A), site on gri=
d","Siligap Boris","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Circuit Breaker Issue","grid outage,site went down due to Cb(2*100A) =
disjuncted in DC Box OCM and poor battery backup// He reamed Cb(2*100A), si=
te on grid","ludivine.ngamaleu@ihstowers.com","594","22-09-2024 15:19:52","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0003133358","F=
OUGEROLE","","22-09-2024 15:18:44","22-09-2024 15:09:59","22-09-2024 16:15:=
18","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","grid outage,site went down due to Cb(2*100A) disjuncted in DC B=
ox OCM and poor battery backup// He reamed Cb(2*100A), site on grid","ludiv=
ine.ngamaleu@ihstowers.com","7761","22-09-2024 15:18:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003133353","M=
vog-Manga","","22-09-2024 15:17:49","22-09-2024 15:06:43","22-09-2024 19:15=
:30","grid outage, site went down due to PLC3 faulty and insufficiency of r=
ectifier on site// He reduced the load , site on grid","Albran Byorel","Equ=
ipment Repair","Passive","Rectifier","Rectifier Module","grid outage, site =
went down due to PLC3 faulty and insufficiency of rectifier on site// He re=
duced the load , site on grid","ludivine.ngamaleu@ihstowers.com","668","22-=
09-2024 15:17:49","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003133342","Nko=
mo stade","","22-09-2024 15:15:21","22-09-2024 15:12:08","22-09-2024 15:30:=
17","Grid outage, site went down because  gen failed tostart due to poor ba=
ttery backup // Grid power return","Mba Lazare Herve","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down because  gen failed tostart due to poor battery backup // Grid powe=
r return","landry.etame@ihstowers.com","194","22-09-2024 15:15:21","Sagemco=
m CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003133332","San=
ta Barbara Gottam","","22-09-2024 15:13:15","22-09-2024 15:09:43","22-09-20=
24 15:43:57","Grid Outage, site went down before Gen start due to poor back=
up// Gen started manually","Delor Telezing","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid Outage, site went down be=
fore Gen start due to poor backup// Gen started manually","landry.etame@ihs=
towers.com","213","22-09-2024 15:13:15","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0003133272","Tou=
ring Club International","","22-09-2024 15:03:45","22-09-2024 15:02:40","22=
-09-2024 15:11:48","Grid  outage,site went down because Gen started and Sto=
pped with Alarm "" under Frequency""/He reset Gen card and started Gen","Al=
bran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid  outage,site went down because Gen started and Stopped with Alarm ""=
 under Frequency""/He reset Gen card and started Gen","landry.etame@ihstowe=
rs.com","66","22-09-2024 15:03:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003133236","M=
essa-Carriere OCM","","22-09-2024 14:54:32","22-09-2024 14:44:59","22-09-20=
24 15:05:33","Active: no power issue, site is on Grid with Ubaie=3D54,2V, M=
ohamadou(691144435) from Huawei is informed, Notice that we have disjunctio=
n at BTS OCM","","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active: no power issue, site is on Grid with U=
baie=3D54,2V, Mohamadou(691144435) from Huawei is informed, Notice that we =
have disjunction at BTS OCM","ludivine.ngamaleu@ihstowers.com","574","22-09=
-2024 14:54:32","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003133217","NTU=
I TOWN","","22-09-2024 14:49:20","22-09-2024 14:46:12","22-09-2024 15:27:48=
","grid outage,Site went down because gen ran untill fuel shortage // refue=
ling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"grid outage,Site went down because gen ran untill fuel shortage // refuel=
ing done","landry.etame@ihstowers.com","188","22-09-2024 14:49:20","Sagemco=
m CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003133173","Eko=
unou","","22-09-2024 14:43:11","22-09-2024 14:42:58","22-09-2024 15:02:12",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","landry=
.etame@ihstowers.com","14","22-09-2024 14:43:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003133128","Matsari"=
,"","22-09-2024 14:36:11","22-09-2024 14:29:06","22-09-2024 15:52:27","Casc=
aded Incident from TTO2982579","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down because gen=
 ran till fuel shortage // refueling done","system","425","22-09-2024 14:36=
:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003133130","MBIMBIM"=
,"","22-09-2024 14:36:11","22-09-2024 14:29:06","22-09-2024 15:52:27","Casc=
aded Incident from TTO2982579","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down because gen=
 ran till fuel shortage // refueling done","system","425","22-09-2024 14:36=
:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003133129","Ngouetou=
","","22-09-2024 14:36:11","22-09-2024 14:29:06","22-09-2024 15:52:27","Cas=
caded Incident from TTO2982579","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n ran till fuel shortage // refueling done","system","425","22-09-2024 14:3=
6:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0003133120","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","22-09-2024 14:35:11","22-=
09-2024 14:29:06","22-09-2024 15:52:27","Grid outage, site went down becaus=
e gen ran till fuel shortage // refueling done","Parker Tchoup","Fuel Outag=
e","Passive","Diesel","Diesel Outage","Grid outage, site went down because =
gen ran till fuel shortage // refueling done by EDO&CO","ludivine.ngamaleu@=
ihstowers.com","366","22-09-2024 14:35:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003133055","N=
komkana","","22-09-2024 14:22:26","22-09-2024 13:59:20","22-09-2024 18:34:1=
8","site went down due to disjunction Cb(80A) in Pwc// He reamed Cb(80A), s=
ite on grid ","","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Circuit Breaker Issue","site went down due to disjunction Cb(80A) in Pw=
c// He reamed Cb(80A), site on grid ","ludivine.ngamaleu@ihstowers.com","13=
87","22-09-2024 14:22:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0003132900","C=
arington","","22-09-2024 13:53:28","22-09-2024 13:40:24","22-09-2024 18:45:=
17","access issuedue to landlord, site went down due to Cb disjuncted in DC=
 Box// He reamed Cb, site on grid","","Access Denial","Lease Or Legal","Lan=
dlord Related Issues","Access Issue - Land Lord","access issuedue to landlo=
rd, site went down due to Cb disjuncted in DC Box// He reamed Cb, site on g=
rid","alexandre.kamal@ihstowers.com","786","22-09-2024 13:53:28","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0003132641","N=
kenglikok","IHS_YND_367, IHS_YND_350, IHS_YND_349","22-09-2024 13:12:54","2=
2-09-2024 12:45:30","22-09-2024 12:55:56","Active// No power issue on site =
,site on battery with Ubaie=3D 54,1V The fme tx Etienne fopa // 695033981 o=
f huawei is informed","Kemeni Franklin","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue=
 on site ,site on battery with Ubaie=3D 54,1V The fme tx Etienne fopa // 69=
5033981 of huawei is informed","alexandre.kamal@ihstowers.com","1645","22-0=
9-2024 13:12:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003132508","Nkongtoc=
k","","22-09-2024 12:46:10","22-09-2024 12:45:30","22-09-2024 12:55:56","Ca=
scaded Incident from TTO2981858 - Cascade Removed From TTO2981858","Kemeni =
Franklin","Cascade Outage","Active","Cascade Active","Cascade Active","Acti=
ve// No power issue on site ,site on battery with Ubaie=3D 54,1V The fme tx=
 Etienne fopa // 695033981 of huawei is informed","system","1972","22-09-20=
24 12:46:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003132507","Mambine"=
,"","22-09-2024 12:46:10","22-09-2024 12:45:30","22-09-2024 12:55:56","Casc=
aded Incident from TTO2981858 - Cascade Removed From TTO2981858","Fanda Bri=
ce","Cascade Outage","Active","Cascade Active","Cascade Active","Active// N=
o power issue on site ,site on battery with Ubaie=3D 54,1V The fme tx Etien=
ne fopa // 695033981 of huawei is informed","system","1932","22-09-2024 12:=
46:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_066","IHS_YND_367","NOCINC0003132503","M=
andoumba OCM","","22-09-2024 12:45:12","22-09-2024 12:45:30","22-09-2024 12=
:55:56","","Kemeni Franklin","Cascade Outage","Active","Cascade Active","Ca=
scade Active","Active// No power issue on site ,site on battery with Ubaie=
=3D 54,1V The fme tx Etienne fopa // 695033981 of huawei is informed","alex=
andre.kamal@ihstowers.com","1796","22-09-2024 12:45:12","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003132155","Bit=
eng","","22-09-2024 11:44:54","22-09-2024 10:55:37","22-09-2024 13:59:14","=
site went down because the Cb(80A) of Dxboxdisjuncted due to load incresead=
 on site //he bypass the cb","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Circuit Breaker Issue","site went down b=
ecause the Cb(80A) of Dxboxdisjuncted due to load incresead on site //he by=
pass the cb","kamga.virgile@ihstowers.com","2957","22-09-2024 11:44:54","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003132153","NKO=
MEKUI OCM","","22-09-2024 11:43:30","22-09-2024 10:05:03","22-09-2024 13:05=
:12","No power issue on site U=3D53.9  V site on Gen.  The fme Tx Mohamadou=
 of Huawei/691144435/ from Huawei is informed. ","TIENTCHEU NZETCHIEU GAEL"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","No power issue on site U=3D53.9  V site on Gen.  The fme Tx Mo=
hamadou of Huawei/691144435/ from Huawei is informed. ","kamga.virgile@ihst=
owers.com","5908","22-09-2024 11:43:30","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_332","NOCINC0003131710","NKOMEKUI OCM",""=
,"22-09-2024 10:32:10","","","Cascaded Incident from TTO2980960 - Cascade R=
emoved From TTO2980960","TIENTCHEU NZETCHIEU GAEL","","","","","","system",=
"1600","22-09-2024 10:32:10","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003131638","Ess=
os Marche","","22-09-2024 10:14:10","22-09-2024 09:54:52","22-09-2024 10:00=
:57","No power issue, site is on grid with Ubaie=3D53,1V, the fme tx Armand=
 Nguetsa(699949553) from Huawei is informed","Delor Telezing","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue, site is on grid with Ubaie=3D53,1V, the fme tx Armand Nguets=
a(699949553) from Huawei is informed","kamga.virgile@ihstowers.com","1159",=
"22-09-2024 10:14:10","Sagemcom CMR"
"Closed Complete","Site Down","T1249","IHS_YND_798","NOCINC0003131497","AKA=
K Nkozoa","","22-09-2024 09:42:36","22-09-2024 08:55:22","22-09-2024 12:38:=
29","site went down because the Cb(125A) of PWC disjuncted due to load incr=
esead on site //he reamed the CB","Fabrice Pouakam","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went do=
wn because the Cb(125A) of PWC disjuncted due to load incresead on site //h=
e reamed the CB","kamga.virgile@ihstowers.com","2835","22-09-2024 09:42:36"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0003131207","Jean Ves=
pa 2","","22-09-2024 09:05:30","22-09-2024 08:50:46","22-09-2024 09:56:35",=
"Cascaded Incident from TTO2980371","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because gen start a=
nd  stopped due to Gen overload (20 KVA, 250A) with alarm Gen overcurrent /=
/he reduce load on site and reset the Gen card","system","884","22-09-2024 =
09:05:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003131170","J=
-Vespa","IHS_YND_544","22-09-2024 09:03:53","22-09-2024 08:50:46","22-09-20=
24 09:56:35","site went down because gen start and  stopped due to Gen over=
load (20 KVA, 250A) with alarm Gen overcurrent //he reduce load on site and=
 reset the Gen card","Mboua Thierry","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","site went down because gen start and  stopped due to G=
en overload (20 KVA, 250A) with alarm Gen overcurrent //he reduce load on s=
ite and reset the Gen card","alexandre.kamal@ihstowers.com","788","22-09-20=
24 09:03:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003130932","F=
ebe Village","","22-09-2024 08:22:33","22-09-2024 08:14:28","22-09-2024 10:=
36:26","grid outage,gen failed to start due to Card Ge faulty//Gen manually=
 started","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - C=
ontrol Panel","grid outage,gen failed to start due to Card Ge faulty//Gen m=
anually started","alexandre.kamal@ihstowers.com","486","22-09-2024 08:22:33=
","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0003130852","SAA=
 Entrance","","22-09-2024 08:02:20","22-09-2024 07:50:03","22-09-2024 08:08=
:05","Grid outage, site went down because gen ran untill fuel shortage // r=
efuelling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage, site went down because gen ran untill fuel shortage // =
refuelling done","kamga.virgile@ihstowers.com","740","22-09-2024 08:02:20",=
"Sagemcom CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0003129965","Nko=
lfon Cimencam","","22-09-2024 03:37:13","22-09-2024 03:28:01","22-09-2024 0=
6:28:03","site went down because gen start and  stopped due to (15 KVA, 205=
A) and load increase on site//he reduce 1/4 rectifier:site on 3 rectifers",=
"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"site went down because gen start and  stopped due to load increase on site=
//he reduce 1/4 rectifier:site on 3 rectifers","olivier.kwedi@ihstowers.com=
","552","22-09-2024 03:37:13","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003129796","Jou=
vence 2000","","22-09-2024 02:38:43","22-09-2024 02:31:33","22-09-2024 03:1=
3:21","Grid Outage, site went down before Gen start due to poor backup// He=
 started Gen manualy","Delor Telezing","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Outage, site went down before =
Gen start due to poor backup// He started Gen manualy","olivier.kwedi@ihsto=
wers.com","431","22-09-2024 02:38:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003129775","E=
lig Edzoa","","22-09-2024 02:31:00","22-09-2024 02:29:36","22-09-2024 02:39=
:36","Grid Outage, site went down before Gen start due to poor backup// Gen=
 started automatically","Delor Telezing","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid Outage, site went down befor=
e Gen start due to poor backup// Gen started automatically","emmanuel.ghani=
@ihstowers.com","85","22-09-2024 02:31:00","Sagemcom CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0003128799","ETO=
UDI CHAPELLE","","21-09-2024 22:00:36","21-09-2024 21:55:19","21-09-2024 21=
:57:33","site went down because gen failed to start due grid bad voltage// =
gen manually started","Delor Telezing","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","site went down because gen failed to =
start due grid bad voltage// gen manually started","stephane.nkamwa@ihstowe=
rs.com","318","21-09-2024 22:00:36","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0003128784","UPA=
C LP","","21-09-2024 21:56:27","21-09-2024 21:49:19","21-09-2024 23:10:30",=
"No power issue, site is on grid with Ubaie=3D55,4V, Armand Nguetsa(6999495=
53) from Huawei is informed","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on grid=
 with Ubaie=3D55,4V, Armand Nguetsa(699949553) from Huawei is informed","st=
ephane.nkamwa@ihstowers.com","429","21-09-2024 21:56:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003128759","N=
kolondom","","21-09-2024 21:48:52","21-09-2024 21:41:49","21-09-2024 21:58:=
37","Grid Outage ,Gen started and  stopped due to ""low oil pressure"" alar=
m (unprouven alarm) //Grid Power return","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage ,Gen started an=
d  stopped due to ""low oil pressure"" alarm (unprouven alarm) //Grid Power=
 return","alexandre.kamal@ihstowers.com","424","21-09-2024 21:48:52","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003128662","Crf Corn=
ier","","21-09-2024 21:35:10","21-09-2024 21:25:59","21-09-2024 22:16:50","=
Cascaded Incident from TTO2977522","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went due to DC load increase//=
 Site up DC dicrease (power come from  Essos March=E9)","system","551","21-=
09-2024 21:35:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003128656","M=
adison","IHS_YND_566","21-09-2024 21:34:42","21-09-2024 21:25:59","21-09-20=
24 22:16:50","site went due to DC load increase// Site up DC dicrease (powe=
r come from  Essos March=E9)","MFOUAGUEGUE MATHIEU","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","site went due to DC lo=
ad increase// Site up DC dicrease (power come from  Essos March=E9)","alexa=
ndre.kamal@ihstowers.com","524","21-09-2024 21:34:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003128561","N=
koabang2","","21-09-2024 21:14:27","21-09-2024 21:07:17","21-09-2024 21:42:=
19","Site went down due to disjunction Cb(125A) in PWC which feeds OCM equi=
pments // He reamed Cb(125A)","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down =
due to disjunction Cb(125A) in PWC which feeds OCM equipments // He reamed =
Cb(125A)","alexandre.kamal@ihstowers.com","431","21-09-2024 21:14:27","Sage=
mcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003128419","Lad=
a I Yde","","21-09-2024 20:46:19","21-09-2024 20:41:07","21-09-2024 21:21:2=
5","Site went due to CB(125A) disjunction in PWC// He rearmed the CB","Mba =
Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Circuit Breaker Issue","Site went due to CB(125A) disjunction in PWC// He =
rearmed the CB","stephane.nkamwa@ihstowers.com","312","21-09-2024 20:46:19"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003128391","M=
vog-Manga","","21-09-2024 20:40:25","21-09-2024 19:58:19","21-09-2024 20:18=
:19","Site on DG due to grid outage,DG stopped due to high temp alarm//He a=
dded water reset DG card and manually start of DG.","Albran Byorel","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level I=
ssue","Site on DG due to grid outage,DG stopped due to high temp alarm//He =
added and manually start of DG.","alexandre.kamal@ihstowers.com","2528","21=
-09-2024 20:40:25","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003128255","Eko=
unou","","21-09-2024 20:11:36","21-09-2024 20:04:23","21-09-2024 20:12:23",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","stepha=
ne.nkamwa@ihstowers.com","434","21-09-2024 20:11:36","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0003128075","Tou=
ring Club International","","21-09-2024 19:31:55","21-09-2024 19:25:48","21=
-09-2024 19:45:48","grid outage, site went down because gen start and stopp=
en  with alarm undervoltage// He reset gen card and gen manually started","=
Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","grid outage, site went down because gen start and stoppen  with alarm u=
ndervoltage// He reset gen card and gen manually started","stephane.nkamwa@=
ihstowers.com","368","21-09-2024 19:31:55","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003128011","Eko=
unou","","21-09-2024 19:16:48","21-09-2024 19:11:40","21-09-2024 19:17:40",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","stepha=
ne.nkamwa@ihstowers.com","309","21-09-2024 19:16:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003127604","A=
KONGO","","21-09-2024 17:50:23","21-09-2024 17:40:59","21-09-2024 17:45:59"=
,"Active:  No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rod=
rigue (655102999)from Huawei is informed. Repetitive issue ","Fanda Brice",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active:  No power issue on site Ubaie=3D52,5V site on Gen. The =
Tx FME Rodrigue (655102999)from Huawei is informed. Repetitive issue ","ale=
xandre.kamal@ihstowers.com","565","21-09-2024 17:50:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003127157","Ngouetou=
","","21-09-2024 16:14:21","21-09-2024 16:03:59","21-09-2024 16:05:00","Cas=
caded Incident from TTO2975772","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","622","21-09-2024 16:14:21","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003127158","MBIMBIM"=
,"","21-09-2024 16:14:21","21-09-2024 16:03:59","21-09-2024 16:05:00","Casc=
aded Incident from TTO2975772","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","622","21-09-2024 16:14:21","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003127156","Yoko OCM=
","","21-09-2024 16:14:21","21-09-2024 16:03:59","21-09-2024 16:05:00","Cas=
caded Incident from TTO2975772","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","622","21-09-2024 16:14:21","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003127155","Matsari"=
,"","21-09-2024 16:14:20","21-09-2024 16:03:59","21-09-2024 16:05:00","Casc=
aded Incident from TTO2975772","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","621","21-09-2024 16:14:20","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003126781","M=
fou EPC","","21-09-2024 15:03:20","21-09-2024 14:54:08","21-09-2024 15:22:3=
0","Grid Outage,DG failed to start ti ACDG Control Panel faulty //Manually =
start of DG.","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Control Panel","Grid Outage,DG failed to start ti ACDG Control Panel =
faulty //Manually start of DG.","alexandre.kamal@ihstowers.com","553","21-0=
9-2024 15:03:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003126771","A=
hala","IHS_YND_257","21-09-2024 14:58:33","21-09-2024 14:43:24","21-09-2024=
 14:56:24","Site went down due to insufficiency of rectifier on site // he =
added 01 rectifier, site on grid","MINKA NICOLAS","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","Site went down due to insufficiency of =
rectifier on site // he added 01 rectifier, site on grid","alexandre.kamal@=
ihstowers.com","910","21-09-2024 14:58:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003126753","A=
hala","","21-09-2024 14:50:58","21-09-2024 14:43:24","21-09-2024 14:56:24",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Site went down due to insufficiency of rectifier on site // he add=
ed 01 rectifier, site on grid","alexandre.kamal@ihstowers.com","1041","21-0=
9-2024 14:50:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003126457","C=
rf Cornier","","21-09-2024 13:58:03","21-09-2024 13:49:59","21-09-2024 13:5=
5:59","No power issue on site U=3D 54,5V site on Grid tx fme Lionel / 69469=
3436 from huawei is Informed.","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D 54,5V site on Grid tx fme Lionel / 694693436 from huawei is Inf=
ormed.","ludivine.ngamaleu@ihstowers.com","485","21-09-2024 13:58:03","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003126386","N=
omayos-IHS","","21-09-2024 13:40:26","21-09-2024 13:33:21","21-09-2024 14:1=
1:39","Site on DG due to grid outage,DG stopped due to water mixed with the=
 fuel inside the tank//He changed Fuel filter,removed water and manually st=
art of DG.","Fanda Brice","Fuel Outage (Probable)","Passive","Diesel","Tank=
 Sealing Issue - Water In The Fuel","Site on DG due to grid outage,DG stopp=
ed due to water mixed with the fuel inside the tank//He changed Fuel filter=
,removed water and manually start of DG.","ludivine.ngamaleu@ihstowers.com"=
,"426","21-09-2024 13:40:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003126382","E=
lobi Mokolo","","21-09-2024 13:37:37","21-09-2024 13:32:32","21-09-2024 14:=
33:18","Active// No power issue on site ,site on Grid with Ubaie=3D 53,4  V=
 The Tx Brice Tsague (650214096) from Huawei is informed .","Mboua Thierry"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active// No power issue on site ,site on Grid with Ubaie=3D 53=
,4  V The Tx Brice Tsague (650214096) from Huawei is informed .","ludivine.=
ngamaleu@ihstowers.com","305","21-09-2024 13:37:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003126024","N=
kolondom","","21-09-2024 12:37:47","21-09-2024 12:27:59","21-09-2024 12:40:=
59"," Grid Bad Voltage, Site wend down because  Gen fails to start due to l=
ack on 01  phase on site //He make the bridge on good phase ","Fabrice Poua=
kam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y"," Grid Bad Voltage, Site wend down because  Gen fails to start due to la=
ck on 01  phase on site //He make the bridge on good phase ","ludivine.ngam=
aleu@ihstowers.com","590","21-09-2024 12:37:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0003125904","C=
hapelle-Nsimeyong","","21-09-2024 12:18:17","21-09-2024 12:07:59","21-09-20=
24 16:32:56","""No power issue Ubaie=3D54,4V site on Grid.The tx fme Mbah h=
osiah(674007438) from Huawei is informed,. Notice that disjonction in BTS o=
cm    The tx fme Mbah hosiah(674007438) from Huawei is informed ""","MINKA =
NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","""No power issue Ubaie=3D54,4V site on Grid.The tx fme=
 Mbah hosiah(674007438) from Huawei is informed,. Notice that disjonction i=
n BTS ocm.The tx fme Mbah hosiah(674007438) from Huawei is informed.
""
","ludivine.ngamaleu@ihstowers.com","619","21-09-2024 12:18:17","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0003125719","N=
R-Bastos","","21-09-2024 11:35:07","21-09-2024 11:33:00","21-09-2024 11:43:=
05","Grid outage//Grid power rerurn","","Grid Supply","Passive","Grid","Nat=
ional Grid - Grid Outage Issue","Grid outage//Grid power rerurn","ludivine.=
ngamaleu@ihstowers.com","128","21-09-2024 11:35:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_632","IHS_YND_721","NOCINC0003125715","V=
OIRIE MUNICIPALE YAOUNDE","","21-09-2024 11:33:53","21-09-2024 11:29:05","2=
1-09-2024 12:08:35","","Paul BIBOUM","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","grid outage,no space to deploy a mobil gen//grid =
return","ludivine.ngamaleu@ihstowers.com","2058","21-09-2024 11:33:53","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0003125701","E=
NAM","IHS_YND_721","21-09-2024 11:30:21","21-09-2024 11:29:05","21-09-2024 =
12:08:35","grid outage,no space to deploy a mobil gen//grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage=
,no space to deploy a mobil gen//grid return","ludivine.ngamaleu@ihstowers.=
com","77","21-09-2024 11:30:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003125677","Saa","",=
"21-09-2024 11:24:40","21-09-2024 11:11:00","21-09-2024 11:55:57","Cascaded=
 Incident from TTO2973991","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","grid outage,gen ran till fuel shortage//Ref=
ueling done","system","820","21-09-2024 11:24:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0003125676","SAA Entr=
ance","","21-09-2024 11:24:40","21-09-2024 11:11:00","21-09-2024 11:55:57",=
"Cascaded Incident from TTO2973991","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen ran till fuel shor=
tage//Refueling done","system","820","21-09-2024 11:24:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003125671","B=
ATA-Mokolo","","21-09-2024 11:23:53","21-09-2024 11:17:49","21-09-2024 11:5=
3:50","Site went down due to work Team Mbom Lovert/Prime Africa / 678657180=
:Swapp the batteries//End of works.","","Installation Activity","Passive","=
Planned Activity","Installation Activity","Site went down due to work Team =
Mbom Lovert/Prime Africa / 678657180:Swapp the batteries//End of works.","l=
udivine.ngamaleu@ihstowers.com","365","21-09-2024 11:23:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0003125641","S=
AA 2","IHS_YND_542, IHS_YND_405","21-09-2024 11:15:45","21-09-2024 11:06:59=
","21-09-2024 11:55:57","grid outage,gen ran till fuel shortage//Refueling =
done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","gri=
d outage,gen ran till fuel shortage//Refueling done","ludivine.ngamaleu@ihs=
towers.com","527","21-09-2024 11:15:45","Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0003125547","Yok=
o MTN","IHS_YND_475","21-09-2024 10:57:02","21-09-2024 09:20:51","21-09-202=
4 09:23:51","grid outage,gen failed to start due to CB(23A) of Gen disjunct=
ed//he reamed the CB","Parker Tchoup","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Circuit Breaker Issue","grid outage,gen failed to =
start due to CB(23A) of Gen disjuncted//he reamed the CB","adonis.defokoua@=
ihstowers.com","5836","21-09-2024 10:57:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0003125466","M=
endong Maeture","","21-09-2024 10:40:00","21-09-2024 10:35:56","21-09-2024 =
13:34:04","Active// No power Issue Site on Grid Ubai =3D54,3V,   The TX FME=
 Mbah Hosiah (674007438) of huawei is informed.","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power Issue Site on Grid Ubai =3D54,3V,   The TX FME Mbah Ho=
siah (674007438) of huawei is informed.","ludivine.ngamaleu@ihstowers.com",=
"245","21-09-2024 10:40:00","Sagemcom CMR"
"Closed Complete","Site Down","T0578","IHS_YND_375","NOCINC0003125462","Ngo=
ung","","21-09-2024 10:37:58","21-09-2024 10:09:52","21-09-2024 10:59:52","=
No power issue on site U=3D55,8v site on grid Etienne 695033981 of huawei i=
s working on site","Kemeni Franklin","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D55,8v site on grid Etienne 695033981 of huawei is working on site","adon=
is.defokoua@ihstowers.com","1687","21-09-2024 10:37:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003125458","M=
ambine","","21-09-2024 10:36:25","21-09-2024 10:25:21","21-09-2024 11:11:21=
","Site went down due to the work ''The Team YANFACK/LEC CAMEROUN/655284880=
/working on site ""Swapp PWC""//End of Work","Fanda Brice","Installation Ac=
tivity","Passive","Planned Activity","Installation Activity","Site went dow=
n due to the work ''The Team YANFACK/LEC CAMEROUN/655284880/working on site=
 ""Swapp PWC""//End of Work","ludivine.ngamaleu@ihstowers.com","665","21-09=
-2024 10:36:25","Sagemcom CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0003125060","Ngo=
um","","21-09-2024 09:27:32","21-09-2024 09:20:26","21-09-2024 09:23:51",""=
,"Parker Tchoup","Cascade Outage","Passive","Cascade Passive","Cascade Pass=
ive","grid outage,gen failed to start due to CB(23A) of Gen disjuncted//he =
reamed the CB","adonis.defokoua@ihstowers.com","427","21-09-2024 09:27:32",=
"Sagemcom CMR"
"Closed Complete","Warning","CTR_070","IHS_YND_104","NOCINC0003124616","Car=
ington","","21-09-2024 07:50:00","","","Grid fluctuation, site alarming on =
battery due to Grid bad voltage// Grid stabilized","","Warning","Warning","=
POWER","Warning - Site on Battery","Grid fluctuation, site alarming on batt=
ery due to Grid bad voltage// Grid stabilized","ludivine.ngamaleu@ihstowers=
.com","6","21-09-2024 07:50:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0003124566","c=
hina embassy yde","","21-09-2024 07:36:01","21-09-2024 07:19:56","21-09-202=
4 09:29:00","Active, no power issue, site on Grid with U=3D53,9V The Tx Fme=
 Eloundou/693212405 of huawei is informed","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power =
issue, site on Grid with U=3D53,9V The Tx Fme Eloundou/693212405 of huawei =
is informed","ludivine.ngamaleu@ihstowers.com","965","21-09-2024 07:36:01",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003124470","E=
lig-Edzoa","","21-09-2024 07:17:06","21-09-2024 07:12:03","21-09-2024 11:01=
:58","grid outage//grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","grid outage//grid return","ludivine.ngamaleu@ih=
stowers.com","304","21-09-2024 07:17:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003124357","M=
fou EPC","","21-09-2024 06:47:09","21-09-2024 06:44:05","21-09-2024 07:26:5=
5","grid outage,gen failed to start due to card Ge faulty//Grid return","Mb=
a Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","grid outage,gen failed to start due to card Ge faulty//Grid return","l=
udivine.ngamaleu@ihstowers.com","185","21-09-2024 06:47:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003124269","Dong",""=
,"21-09-2024 06:21:30","21-09-2024 06:15:14","21-09-2024 07:25:26","Cascade=
d Incident from TTO2972373","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","site went down because gen ran till fuel s=
hortage//Refueling done","system","376","21-09-2024 06:21:30","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003124268","Donga","=
","21-09-2024 06:21:30","21-09-2024 06:15:14","21-09-2024 07:25:26","Cascad=
ed Incident from TTO2972373","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because gen ran till fuel =
shortage//Refueling done","system","376","21-09-2024 06:21:30","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0003124265","N=
guila","IHS_YND_434, IHS_YND_444","21-09-2024 06:20:15","21-09-2024 06:15:1=
4","21-09-2024 07:25:26","site went down because gen ran till fuel shortage=
//Refueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel =
Outage","site went down because gen ran till fuel shortage//Refueling done"=
,"ludivine.ngamaleu@ihstowers.com","302","21-09-2024 06:20:15","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003124251","A=
kak-Nkozoa-MTN-IHS","","21-09-2024 06:18:52","21-09-2024 06:09:52","21-09-2=
024 09:20:52","Site went down because CB(125A)*CB(80 A)  who feeds equipmen=
t Ocm burned in DC BOX //He replaced CB(80A) another CB(80A) and make  the =
bridge CB(125A) with CB(2*63A)","Fabrice Pouakam","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down=
 because CB(125A)*CB(80 A)  who feeds equipment Ocm burned in DC BOX //He r=
eplaced CB(80A) another CB(80A) and make  the bridge CB(125A) with CB(2*63A=
)","ludivine.ngamaleu@ihstowers.com","541","21-09-2024 06:18:52","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003124003","E=
lobi Mokolo","","21-09-2024 04:39:12","21-09-2024 04:11:00","21-09-2024 09:=
31:46","Active// No power issue on site U=3D53,4V site on Grid and  Brice T=
sague (650214096) from Huawei is informed","Mboua Thierry","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power issue on site U=3D53,4V site on Grid and  Brice Tsague (65021=
4096) from Huawei is informed","kouoh.jean@ihstowers.com","1692","21-09-202=
4 04:39:12","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0003123273","Nko=
abang MTN","","21-09-2024 00:37:09","20-09-2024 12:10:33","20-09-2024 23:56=
:33"," site went down due to Cb(63A)  in the DC-Box  // He reamed Cb(63A), =
site on Grid","Mba Lazare Herve","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Circuit Breaker Issue"," site went down due to Cb(63A) =
 in the DC-Box  // He reamed Cb(63A), site on Grid","kouoh.jean@ihstowers.c=
om","44797","21-09-2024 00:37:09","Sagemcom CMR"
"Closed Complete","Site Down","T0792","IHS_YND_506","NOCINC0003123117","Omn=
isport-Rail","","20-09-2024 23:47:59","20-09-2024 23:39:39","21-09-2024 00:=
44:34","Grid outage, site went down because Gen failed to start due to Grid=
 bad voltage // hy bypass the Grid and manually started the Gen","Delor Tel=
ezing","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid outage, site went down because Gen failed to start due to Grid b=
ad voltage // hy bypass the Grid and manually started the Gen","landry.etam=
e@ihstowers.com","794","20-09-2024 23:47:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003123028","A=
kak-Nkozoa-MTN-IHS","","20-09-2024 23:29:14","20-09-2024 22:54:01","21-09-2=
024 01:49:21","site went down because the  CB(2*80A) of PWC Dysjoncted// he=
 reamed the CB(2*80A)  and Site is on Gen","Fabrice Pouakam","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","sit=
e went down because the  CB(2*80A) of PWC Dysjoncted// he reamed the CB(2*8=
0A)  and Site is on Gen","kouoh.jean@ihstowers.com","2114","20-09-2024 23:2=
9:14","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003123008","Odz=
a II","","20-09-2024 23:23:23","20-09-2024 23:17:18","20-09-2024 23:25:32",=
"Grid outage, site went down before DG start due to poor Battery backup// G=
rid Restored.","Albran Byorel","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before DG start=
 due to poor Battery backup// Grid Restored.","landry.etame@ihstowers.com",=
"367","20-09-2024 23:23:23","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003122998","Eko=
unou","","20-09-2024 23:21:05","20-09-2024 23:15:57","20-09-2024 23:35:42",=
"Grid outage, site went down before DG start due to poor Battery backup// D=
G started automatically.","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re DG start due to poor Battery backup// DG started automatically.","landry=
.etame@ihstowers.com","309","20-09-2024 23:21:05","Sagemcom CMR"
"Closed Complete","Site Down","T0578","IHS_YND_375","NOCINC0003122988","Ngo=
ung","","20-09-2024 23:19:54","20-09-2024 23:11:49","21-09-2024 01:12:56","=
Active// No power issue, site is on Grid with Ubaie=3D55,6V The TX FME Etie=
nne //695033981// from Huawei is informed","Kemeni Franklin","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue, site is on Grid with Ubaie=3D55,6V The TX FME Etienn=
e //695033981// from Huawei is informed","landry.etame@ihstowers.com","486"=
,"20-09-2024 23:19:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003122614","N=
koabang2","","20-09-2024 22:06:43","20-09-2024 21:15:31","20-09-2024 21:16:=
14","Active//No power issue Ubaie=3D53,2V site on Gen. TX FME Leonel Steve =
  (655184876) from Huawei is informed,","Mba Lazare Herve","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No power issue Ubaie=3D53,2V site on Gen. TX FME Leonel Steve   (655184=
876) from Huawei is informed,","kombi.samuel@ihstowers.com","3073","20-09-2=
024 22:06:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003122440","E=
lig-Edzoa","","20-09-2024 21:40:54","20-09-2024 21:36:49","20-09-2024 22:28=
:26","Grid Outage // MDG 20 KVA deployed","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid Outage // MDG 20 KVA deployed","=
emmanuel.ghani@ihstowers.com","246","20-09-2024 21:40:54","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003122307","Bit=
eng","","20-09-2024 21:24:54","20-09-2024 21:20:50","20-09-2024 21:29:53","=
Grid Outage, Site went down before Gen start due to poor battery backup// G=
en started automatically","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid Outage, Site went down b=
efore Gen start due to poor battery backup// Gen started automatically","jo=
elle.ekessi@ihstowers.com","245","20-09-2024 21:24:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003122109","T=
amtam Weekend","","20-09-2024 21:03:13","20-09-2024 20:54:06","20-09-2024 2=
0:59:06","Active//No power issue, site is on grid with Ubaie=3D54.5V, Mbah =
hosieh(699699694) from Huawei is informed","Hyemafo Gildas","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue, site is on grid with Ubaie=3D54.5V, Mbah hosieh(699699=
694) from Huawei is informed","emmanuel.ghani@ihstowers.com","548","20-09-2=
024 21:03:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003121732","M=
EFOU ASSI","","20-09-2024 19:55:28","20-09-2024 19:05:21","20-09-2024 21:17=
:29","Grid Outage , site went down because Gen  overload(220KVA, 330)// Gri=
d Restored","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","Grid Outage , site went down because Gen  overload(220KVA, 330)//=
 Grid Restored","kombi.samuel@ihstowers.com","3008","20-09-2024 19:55:28","=
Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003121647","Eko=
unou","","20-09-2024 19:35:38","20-09-2024 19:33:34","20-09-2024 20:07:34",=
"Grid outage, site went down before gen start due to poor battery backup //=
 gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // gen start automatically","joelle=
.ekessi@ihstowers.com","125","20-09-2024 19:35:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_721","NOCINC0003121645","VOIRIE M=
UNICIPALE YAOUNDE","","20-09-2024 19:35:10","20-09-2024 18:59:19","21-09-20=
24 09:26:42","Cascaded Incident from TTO2969057","Paul BIBOUM","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Acess Issue during the =
Night due Landlord,grid outage,no space to deploy a mobil gen//grid return"=
,"system","2151","20-09-2024 19:35:10","Sagemcom CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0003121433","ENA=
M","IHS_YND_721","20-09-2024 19:06:23","20-09-2024 18:59:19","21-09-2024 09=
:26:42","Acess Issue during the Night due Landlord,grid outage,no space to =
deploy a mobil gen//grid return","","Access Denial","Lease Or Legal","Landl=
ord Related Issues","Access Issue - Land Lord","Acess Issue during the Nigh=
t due Landlord,grid outage,no space to deploy a mobil gen//grid return","jo=
elle.ekessi@ihstowers.com","512","20-09-2024 19:06:23","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003121395","Bit=
eng","","20-09-2024 19:04:53","20-09-2024 18:57:48","20-09-2024 20:17:14","=
site went down because CB (63A) who feeds equipments MTN disjuncted in DC-B=
OX//he rearmed the CB (CB to be replace)","Mba Lazare Herve","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","sit=
e went down because CB (63A) who feeds equipments MTN disjuncted in DC-BOX/=
/he rearmed the CB (CB to be replace)","joelle.ekessi@ihstowers.com","426",=
"20-09-2024 19:04:53","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003121235","Lad=
a I Yde","","20-09-2024 18:55:26","20-09-2024 18:49:21","20-09-2024 21:05:4=
0","Site went due to CB(125A) disjunction in PWC// He rearmed the CB","Mba =
Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Circuit Breaker Issue","Site went due to CB(125A) disjunction in PWC// He =
rearmed the CB","joelle.ekessi@ihstowers.com","366","20-09-2024 18:55:26","=
Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003121071","Bas=
tos Amb Coree","","20-09-2024 18:45:59","20-09-2024 18:43:49","20-09-2024 1=
8:45:54","Site went down due to insufficiency of Rectifires //Site stabiliz=
ed,rectifiers must be upgraded.","","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down due to insufficiency of Rectifires //S=
ite stabilized,rectifiers must be upgraded.","joelle.ekessi@ihstowers.com",=
"131","20-09-2024 18:45:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0003121028","B=
ONAS YDE","","20-09-2024 18:41:53","20-09-2024 18:36:47","20-09-2024 21:20:=
30","Active// No power Issue Site on Grid Ubai =3D54,6 V, The TX FME Mbah H=
osiah (674007438)  from huawei is informed","Paul BIBOUM","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power Issue Site on Grid Ubai =3D54,6 V, The TX FME Mbah Hosiah (674=
007438)  from huawei is informed
","emmanuel.ghani@ihstowers.com","307","20-09-2024 18:41:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0003120764","N=
goum","","20-09-2024 18:20:20","20-09-2024 17:55:04","20-09-2024 21:00:04",=
"No power issue site on Gen with U=3D54V,  tx fme Gregoire (654547479) from=
 Huawei informed","Parker Tchoup","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue site on Gen wi=
th U=3D54V,  tx fme Gregoire (654547479) from Huawei informed","emmanuel.gh=
ani@ihstowers.com","1518","20-09-2024 18:20:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003120706","Afanoya"=
,"","20-09-2024 18:13:31","20-09-2024 17:35:13","20-09-2024 20:36:13","Casc=
aded Incident from TTO2968226","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, Site went down because Ge=
n Overload (20kva,330A)//He reduced the load and started Gen manualy","syst=
em","2298","20-09-2024 18:13:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003120705","MBALNGON=
G LYCEE","","20-09-2024 18:13:30","20-09-2024 17:35:13","20-09-2024 20:36:1=
3","Cascaded Incident from TTO2968226","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, Site went down becau=
se Gen Overload (20kva,330A)//He reduced the load and started Gen manualy",=
"system","2297","20-09-2024 18:13:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003120704","ELOUMDEM=
 CARRIERE","","20-09-2024 18:13:30","20-09-2024 17:35:13","20-09-2024 20:36=
:13","Cascaded Incident from TTO2968226","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, Site went down bec=
ause Gen Overload (20kva,330A)//He reduced the load and started Gen manualy=
","system","2297","20-09-2024 18:13:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003120687","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","20-09-2024 18:09:24","20-09-=
2024 17:34:13","20-09-2024 20:36:13","Grid Outage, Site went down because G=
en Overload (20kva,330A)//He reduced the load and started Gen manualy","Hye=
mafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gri=
d Outage, Site went down because Gen Overload (20kva,330A)//He reduced the =
load and started Gen manualy","emmanuel.ghani@ihstowers.com","2112","20-09-=
2024 18:09:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003120293","MBIMBIM"=
,"","20-09-2024 17:26:00","20-09-2024 17:09:58","20-09-2024 17:49:27","Casc=
aded Incident from TTO2967681","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down because gen=
 ran untill fuel shortage (Fuel manage by edonde) // Grid return","system",=
"962","20-09-2024 17:26:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003120290","Matsari"=
,"","20-09-2024 17:26:00","20-09-2024 17:09:58","20-09-2024 17:49:27","Casc=
aded Incident from TTO2967681","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down because gen=
 ran untill fuel shortage (Fuel manage by edonde) // Grid return","system",=
"962","20-09-2024 17:26:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003120292","Ngouetou=
","","20-09-2024 17:26:00","20-09-2024 17:09:58","20-09-2024 17:49:27","Cas=
caded Incident from TTO2967681","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n ran untill fuel shortage (Fuel manage by edonde) // Grid return","system"=
,"962","20-09-2024 17:26:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0003120218","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","20-09-2024 17:18:02","20-=
09-2024 17:09:58","20-09-2024 17:49:27","Grid outage, site went down becaus=
e gen ran untill fuel shortage (Fuel manage by edonde) // Grid return","Par=
ker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, =
site went down because gen ran untill fuel shortage (Fuel manage by edonde)=
 // Grid return","emmanuel.ghani@ihstowers.com","485","20-09-2024 17:18:02"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003120013","S=
calom-IHS","","20-09-2024 16:29:30","20-09-2024 16:19:23","20-09-2024 20:05=
:00","Active// No power Issue Site on Grid Ubai =3D55,2 V, The TX FME Mbah =
Hosiah (674007438) is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site=
 on Grid Ubai =3D55,2 V, The TX FME Mbah Hosiah (674007438) is informed","e=
mmanuel.ghani@ihstowers.com","608","20-09-2024 16:29:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0003119883","Ebeba","=
","20-09-2024 16:13:50","20-09-2024 16:10:59","20-09-2024 16:20:16","Cascad=
ed Incident from TTO2967311","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","Active// No power issue on site. site on Gen 5=
0.8V The Team Abel/654078239/From AFLO is working on site ""Swapp Link""","=
system","171","20-09-2024 16:13:50","Sagemcom CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0003119881","Nke=
ng likok","IHS_YND_339","20-09-2024 16:13:05","20-09-2024 16:10:59","20-09-=
2024 18:38:05","Active// No power issue on site. site on Gen 50.8V The Team=
 Abel/654078239/From AFLO is working on site ""Swapp Link""","Kemeni Frankl=
in","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// No power issue on site. site on Gen 50.8V The Team=
 Abel/654078239/From AFLO is working on site ""Swapp Link""","joelle.ekessi=
@ihstowers.com","127","20-09-2024 16:13:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003119686","ELOUMDEM=
 CARRIERE","","20-09-2024 15:37:30","20-09-2024 15:31:25","20-09-2024 15:41=
:25","Cascaded Incident from TTO2967084","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Fluctuation, site went dow=
n before DG start due to poor Battery backup// DG started automatically.","=
system","365","20-09-2024 15:37:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003119688","Afanoya"=
,"","20-09-2024 15:37:30","20-09-2024 15:31:25","20-09-2024 15:41:25","Casc=
aded Incident from TTO2967084","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Fluctuation, site went down befor=
e DG start due to poor Battery backup// DG started automatically.","system"=
,"365","20-09-2024 15:37:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003119687","MBALNGON=
G LYCEE","","20-09-2024 15:37:30","20-09-2024 15:31:25","20-09-2024 15:41:2=
5","Cascaded Incident from TTO2967084","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Fluctuation, site went down =
before DG start due to poor Battery backup// DG started automatically.","sy=
stem","365","20-09-2024 15:37:30","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003119682","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","20-09-2024 15:36:31","20-09-20=
24 15:31:25","20-09-2024 15:41:25","Grid Fluctuation, site went down before=
 DG start due to poor Battery backup// DG started automatically.","Hyemafo =
Gildas","Equipment Repair","Passive","Control Panel","Power Cabinet - Batte=
ry Low","Grid Fluctuation, site went down before DG start due to poor Batte=
ry backup// DG started automatically.","joelle.ekessi@ihstowers.com","308",=
"20-09-2024 15:36:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0003119624","H=
-Franco New","","20-09-2024 15:28:13","20-09-2024 14:54:06","20-09-2024 21:=
19:29","Please Cascade it behind Djoungolo","Delor Telezing","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down during the=
 works :656-04-05-78 Gildas /Tech Pro  is working on site,swap of PWC// End=
 of works.","emmanuel.ghani@ihstowers.com","2048","20-09-2024 15:28:13","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0003119606","D=
joungolo","IHS_YND_711","20-09-2024 15:25:18","20-09-2024 14:54:09","20-09-=
2024 21:20:01","Site went down during the works :656-04-05-78 Gildas /Tech =
Pro  is working on site,swap of PWC// End of works.","Mboua Thierry","Insta=
llation Activity","Passive","Planned Activity","Installation Activity","Sit=
e went down during the works :656-04-05-78 Gildas /Tech Pro  is working on =
site,swap of PWC// End of works.","emmanuel.ghani@ihstowers.com","1869","20=
-09-2024 15:25:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003119260","N=
yom OCM","","20-09-2024 14:28:57","20-09-2024 14:03:52","21-09-2024 09:24:3=
0","Active//No power issue on site U=3D54,6V site on Grid  and Synphorien /=
650257151/ of huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue on site U=3D54,6V site on Grid  and Synphorien /650257151/ of h=
uawei is informed","emmanuel.ghani@ihstowers.com","1506","20-09-2024 14:28:=
57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003119178","B=
ATA-Mokolo","","20-09-2024 14:07:42","20-09-2024 13:59:28","20-09-2024 15:0=
0:59","Active// No power issue on site U=3D53,7V site on gen Brice Tsague (=
650214096) from Huawei is informed.","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue=
 on site U=3D53,7V site on gen Brice Tsague (650214096) from Huawei is info=
rmed.
.","denis.mballa@ihstowers.com","495","20-09-2024 14:07:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003119031","S=
calom-IHS","","20-09-2024 13:41:36","20-09-2024 13:38:20","20-09-2024 13:48=
:47","Active// No power Issue Site on Grid Ubai =3D55,2 V, The TX FME Mbah =
Hosiah (674007438) is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site=
 on Grid Ubai =3D55,2 V, The TX FME Mbah Hosiah (674007438) is informed","d=
enis.mballa@ihstowers.com","197","20-09-2024 13:41:36","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003119030","Nko=
g-Edzen","","20-09-2024 13:41:22","20-09-2024 13:29:08","20-09-2024 14:19:4=
9","Hybrid-DG,DG started and stopped due high Temp // DG door opened and DG=
 restarted.","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG =
- High Engine Temp - Coolant Level Issue","Hybrid-DG,DG started and stopped=
 due high Temp // DG door opened and DG restarted.","olivier.kwedi@ihstower=
s.com","735","20-09-2024 13:41:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003119016","N=
kolondom","","20-09-2024 13:38:21","20-09-2024 13:35:08","20-09-2024 15:45:=
36","Site went down because DG  started and stopped due to grid bad voltage=
 ,voltage were unstable // He bypass grid and manually start the gen.","Fab=
rice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Site went down because DG  started and stopped due to grid bad=
 voltage ,voltage was very unstable // He bypass grid and manually start th=
e gen.","denis.mballa@ihstowers.com","194","20-09-2024 13:38:21","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003118882","K=
oweit City","","20-09-2024 13:13:58","20-09-2024 13:04:40","20-09-2024 14:1=
8:13","site went down due to work(albran(657108542) /Sagemcom)","Albran Byo=
rel","Installation Activity","Passive","Planned Activity","Installation Act=
ivity","site went down due to work(albran(657108542) /Sagemcom)//end of wor=
k","denis.mballa@ihstowers.com","558","20-09-2024 13:13:58","Sagemcom CMR"
"Closed Complete","Site Down","T0578","IHS_YND_375","NOCINC0003118860","Ngo=
ung","","20-09-2024 13:09:37","20-09-2024 13:00:28","20-09-2024 13:05:25","=
Active// No power issue, site is on grid with Ubaie=3D52,6V The TX FME Etie=
nne //695033981// from Huawei is informed","Kemeni Franklin","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue, site is on grid with Ubaie=3D52,6V The TX FME Etienn=
e //695033981// from Huawei is informed","olivier.kwedi@ihstowers.com","550=
","20-09-2024 13:09:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003118842","M=
imboman-Village","","20-09-2024 13:04:48","20-09-2024 12:45:30","20-09-2024=
 12:50:30","Active: no power issue on site ,site on GRid with U=3D54V Team =
Eloundou // 693212405 from HUAWEI is informed","Mba Lazare Herve","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active: no power issue on site ,site on GRid with U=3D54V Team Eloundou =
// 693212405 from HUAWEI is informed","denis.mballa@ihstowers.com","1159","=
20-09-2024 13:04:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003118832","N=
koabang2","","20-09-2024 13:02:13","20-09-2024 12:53:43","20-09-2024 13:56:=
39","Grid Fluctuation site went before DG start : Poor batteries backup //A=
CDG Gen started automatically.","Mba Lazare Herve","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuation site w=
ent before DG start : Poor batteries backup //Dg started automatically.","d=
enis.mballa@ihstowers.com","511","20-09-2024 13:02:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0003118164","Ekoumdou=
m OCM","","20-09-2024 11:42:00","20-09-2024 11:36:03","20-09-2024 11:47:27"=
,"Cascaded Incident from TTO2965346","Albran Byorel","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active: no power issue, site is on g=
rid with Ubaie=3D53V, Gildas wouafo(659653638) from ZTE working on site","s=
ystem","357","20-09-2024 11:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003118163","MEHANDAN=
","","20-09-2024 11:42:00","20-09-2024 11:36:03","20-09-2024 11:47:27","Cas=
caded Incident from TTO2965346","Albran Byorel","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active: no power issue, site is on grid w=
ith Ubaie=3D53V, Gildas wouafo(659653638) from ZTE working on site","system=
","357","20-09-2024 11:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0003118162","Odza II =
OCM","","20-09-2024 11:42:00","20-09-2024 11:36:03","20-09-2024 11:47:27","=
Cascaded Incident from TTO2965346","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active: no power issue, site is on gri=
d with Ubaie=3D53V, Gildas wouafo(659653638) from ZTE working on site","sys=
tem","357","20-09-2024 11:42:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0003118123","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","20-09-2024 11:40:16","20=
-09-2024 11:36:03","20-09-2024 11:47:27","Active: no power issue, site is o=
n grid with Ubaie=3D53V, Gildas wouafo(659653638) from ZTE working on site"=
,"Albran Byorel","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active: no power issue, site is on grid with U=
baie=3D53V, Gildas wouafo(659653638) from ZTE working on site","denis.mball=
a@ihstowers.com","254","20-09-2024 11:40:16","Sagemcom CMR"
"Closed Complete","Site Down","T0058","IHS_YND_293","NOCINC0003117583","Nko=
abang MTN","","20-09-2024 10:31:39","20-09-2024 10:24:31","20-09-2024 11:20=
:05","Active: no power issue, site is on grid with Ubaie=3D53V, Lionel stee=
ve(655184876) from Huawei is informed","Mba Lazare Herve","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: no power issue, site is on grid with Ubaie=3D53V, Lionel steeve(65518487=
6) from Huawei is informed","olivier.kwedi@ihstowers.com","429","20-09-2024=
 10:31:39","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_191","NOCINC0003117478","Mballa II"=
,"","20-09-2024 10:10:15","","","","Delor Telezing","Warning","Warning","SY=
STEM","Warning - Alarm Cable Loose","NO","denis.mballa@ihstowers.com","3","=
20-09-2024 10:10:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0003117467","S=
cience","","20-09-2024 10:07:11","20-09-2024 10:02:00","20-09-2024 10:59:52=
","Active: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(6911=
44435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: no power issue, site is on grid with Ubaie=3D53V, Mohamadou(691144435) =
from Huawei is informed","denis.mballa@ihstowers.com","312","20-09-2024 10:=
07:11","Sagemcom CMR"
"Cancelled","Warning","T1062","IHS_YND_475","NOCINC0003117438","Ngoum","","=
20-09-2024 10:02:00","","","","Parker Tchoup","","","","","","olivier.kwedi=
@ihstowers.com","1271","20-09-2024 10:02:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003117431","E=
mana","","20-09-2024 10:00:29","20-09-2024 09:33:09","20-09-2024 11:30:28",=
"Grid outage  //MDG of 20 kva has deployed","","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue","Grid outage  //MDG of 20 kva has de=
ployed","denis.mballa@ihstowers.com","1643","20-09-2024 10:00:29","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0003117385","Yok=
o MTN","IHS_YND_475","20-09-2024 09:50:47","20-09-2024 09:41:27","20-09-202=
4 10:05:34","grid outage, site went down because gen failed to start due to=
 oil pressure sensor faulty// He bypassed oil pressure sensor, site on gen"=
,"Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Oil Pressu=
re Sensor Faulty","grid outage, site went down because gen failed to start =
due to oil pressure sensor faulty// He bypassed oil pressure sensor, site o=
n gen","olivier.kwedi@ihstowers.com","561","20-09-2024 09:50:47","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0003116888","M=
endong Maeture","","20-09-2024 08:22:28","20-09-2024 08:12:14","20-09-2024 =
08:22:19","No power issue, site is on grid with Ubaie=3D54.5V, Mbah hosieh(=
699699694) from Huawei is informed","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D54.5V, Mbah hosieh(699699694) from Huawe=
i is informed","denis.mballa@ihstowers.com","614","20-09-2024 08:22:28","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1573","IHS_YND_378","NOCINC0003116826","Ese=
ka Town","","20-09-2024 08:03:04","20-09-2024 08:00:56","20-09-2024 09:15:3=
3","Grid outage,site went down because gen ran untill fuel shortage // refu=
eling done","Kemeni Franklin","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage,site went down because gen ran untill fuel shortage // ref=
ueling done","olivier.kwedi@ihstowers.com","130","20-09-2024 08:03:04","Sag=
emcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003116782","Tsi=
nga","","20-09-2024 07:48:56","20-09-2024 07:45:23","20-09-2024 08:08:38","=
Grid , site went down before DG start due to poor Battery backup// grid ret=
urn.","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid , site went down before DG start due to poor Ba=
ttery backup// grid return.","olivier.kwedi@ihstowers.com","1028","20-09-20=
24 07:48:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003116258","Bitoto",=
"","20-09-2024 05:49:00","20-09-2024 05:40:27","20-09-2024 07:02:00","Casca=
ded Incident from TTO2963194","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, site went down because g=
en start and stoppen with alarm undervoltage// He reset gen card , site on =
gen","system","513","20-09-2024 05:49:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003116260","Essomba"=
,"","20-09-2024 05:49:00","20-09-2024 05:40:27","20-09-2024 07:02:00","Casc=
aded Incident from TTO2963194","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, site went down because =
gen start and stoppen with alarm undervoltage// He reset gen card , site on=
 gen","system","513","20-09-2024 05:49:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003116261","Biteng-M=
aetur","","20-09-2024 05:49:00","20-09-2024 05:40:27","20-09-2024 07:02:00"=
,"Cascaded Incident from TTO2963194","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, site went down be=
cause gen start and stoppen with alarm undervoltage// He reset gen card , s=
ite on gen","system","513","20-09-2024 05:49:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003116259","AWAE OCM=
","","20-09-2024 05:49:00","20-09-2024 05:40:27","20-09-2024 07:02:00","Cas=
caded Incident from TTO2963194","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, site went down because=
 gen start and stoppen with alarm undervoltage// He reset gen card , site o=
n gen","system","513","20-09-2024 05:49:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003116252","B=
iteng","IHS_YND_292, IHS_YND_173, IHS_YND_179, IHS_YND_249","20-09-2024 05:=
45:31","20-09-2024 05:40:27","20-09-2024 07:02:19","grid outage, site went =
down because gen start and stoppen with alarm undervoltage// He reset gen c=
ard , site on gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","grid outage, site went down because gen start an=
d stoppen with alarm undervoltage// He reset gen card , site on gen","alexa=
ndre.kamal@ihstowers.com","305","20-09-2024 05:45:31","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003115814","Nom=
ayos montee Meche","","20-09-2024 02:58:37","20-09-2024 02:38:24","20-09-20=
24 03:22:47","site went because Gen started and stopped  without alarm // G=
en manually started (investigation ongoing)","Fanda Brice","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","site went because Gen start=
ed and stopped  without alarm // Gen manually started (investigation ongoin=
g)","kamga.virgile@ihstowers.com","1214","20-09-2024 02:58:37","Sagemcom CM=
R"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003115275","NTU=
I TOWN","","20-09-2024 00:05:56","19-09-2024 23:52:25","20-09-2024 00:10:46=
","Grid Fluctuation, Site went down because Gen failed to start due to Grid=
 Bad voltage on site// He bypass the Grid and started Gen Manualy","Parker =
Tchoup","Grid Supply","Passive","Grid","National Grid - Phase Controller Fa=
ulty","Grid Fluctuation, Site went down because Gen failed to start due to =
Grid Bad voltage on site// He bypass the Grid and started Gen Manualy
","kamga.virgile@ihstowers.com","811","20-09-2024 00:05:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0003114575","E=
TOUDI CHAPELLE","","19-09-2024 21:30:17","19-09-2024 21:10:09","19-09-2024 =
22:10:51","Grid Fluctuation, Site went down because Gen failed to start due=
 to Grid Bad voltage on site// He started Gen Manualy","Delor Telezing","Gr=
id Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid=
 Fluctuation, Site went down because Gen failed to start due to Grid Bad vo=
ltage on site// He started Gen Manualy","kouoh.jean@ihstowers.com","1209","=
19-09-2024 21:30:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003113371","Essomba"=
,"","19-09-2024 20:31:31","19-09-2024 20:15:41","19-09-2024 21:55:21","Casc=
aded Incident from TTO2959780","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because t=
he cb of battery and poor battery  backup// he reamed the cb and gen manual=
ly started","system","950","19-09-2024 20:31:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003113369","AWAE OCM=
","","19-09-2024 20:31:31","19-09-2024 20:15:41","19-09-2024 21:55:21","Cas=
caded Incident from TTO2959780","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
the cb of battery and poor battery  backup// he reamed the cb and gen manua=
lly started","system","950","19-09-2024 20:31:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003113372","Biteng-M=
aetur","","19-09-2024 20:31:31","19-09-2024 20:15:41","19-09-2024 21:55:21"=
,"Cascaded Incident from TTO2959780","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause the cb of battery and poor battery  backup// he reamed the cb and gen =
manually started","system","950","19-09-2024 20:31:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003113368","Bitoto",=
"","19-09-2024 20:31:30","19-09-2024 20:15:41","19-09-2024 21:55:21","Casca=
ded Incident from TTO2959780","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because th=
e cb of battery and poor battery  backup// he reamed the cb and gen manuall=
y started","system","949","19-09-2024 20:31:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003113239","B=
iteng","IHS_YND_292, IHS_YND_173, IHS_YND_179, IHS_YND_249","19-09-2024 20:=
24:54","19-09-2024 20:15:41","19-09-2024 21:55:48","Grid outage site went d=
own because the cb of battery and poor battery  backup// he reamed the cb a=
nd gen manually started","Mba Lazare Herve","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Circuit Breaker Issue","Grid outage site wen=
t down because the cb of battery and poor battery  backup// he reamed the c=
b and gen manually started","kouoh.jean@ihstowers.com","554","19-09-2024 20=
:24:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0003113125","N=
kolmesseng","","19-09-2024 20:07:12","19-09-2024 19:54:57","19-09-2024 20:0=
5:32","Active//No power issue on site ;site on Gen with Ubaie =3D52.3 V The=
 fme tx  RM Alain // 691144423 //   Huawei is informed . Notice that disjon=
ction in BTS ocm","Siligap Boris","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on sit=
e ;site on Gen with Ubaie =3D52.3 V The fme tx  RM Alain // 691144423 //   =
Huawei is informed . Notice that disjonction in BTS ocm","kouoh.jean@ihstow=
ers.com","735","19-09-2024 20:07:12","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0003112893","Av =
Kennedy","","19-09-2024 19:35:41","19-09-2024 19:23:33","19-09-2024 19:39:3=
3","Grid outage No space to deployed a mobile Gen// Grid Power return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age No space to deployed a mobile Gen// Grid Power return","landry.etame@ih=
stowers.com","729","19-09-2024 19:35:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003112784","N=
sam Sofavinc T0","","19-09-2024 19:16:15","19-09-2024 19:03:58","19-09-2024=
 19:18:58","Grid outage, site went down because Gen start and stopped due t=
o Gen overload (09kva ,160A) // Grid power return","MINKA NICOLAS","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went d=
own because Gen start and stopped due to Gen overload (09kva ,160A) // Grid=
 power return","kouoh.jean@ihstowers.com","737","19-09-2024 19:16:15","Sage=
mcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003112711","Eko=
unou","","19-09-2024 18:56:43","19-09-2024 18:53:36","19-09-2024 18:59:36",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","landry=
.etame@ihstowers.com","188","19-09-2024 18:56:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003112459","E=
kombitie","","19-09-2024 18:27:48","19-09-2024 17:36:25","19-09-2024 17:40:=
25","No power issue on site U=3D54,6v site on grid Synphorien/650257151 of =
huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,6v site on grid Synphorien/650257151 of huawei is informed","kouoh.je=
an@ihstowers.com","3084","19-09-2024 18:27:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003112092","C=
rf-Nsam","","19-09-2024 17:29:58","19-09-2024 17:22:33","19-09-2024 17:46:3=
3","site on gen due to grid outage, site went down due to work (Landloard) =
// End of work and gen manually started","MINKA NICOLAS","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Emergency Stop","site on gen due to grid outa=
ge, site went down due to work (Landloard) // End of work and gen manually =
started","kouoh.jean@ihstowers.com","446","19-09-2024 17:29:58","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0003111999","Ahala","=
","19-09-2024 17:10:20","19-09-2024 16:25:37","19-09-2024 17:12:37","Cascad=
ed Incident from TTO2958208","Hyemafo Gildas","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power isssue, site is on grid with Ubaie=
=3D53V, Biloa(659843334) from ZTE is working on site","system","2683","19-0=
9-2024 17:10:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003111989","A=
hala","","19-09-2024 17:07:35","19-09-2024 16:16:16","19-09-2024 16:22:16",=
"Grid Outage: the site went down before DG started due to poor Battery back=
up// DG started automatically.","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage: the site wen=
t down before DG started due to poor Battery backup// DG started automatica=
lly.","kouoh.jean@ihstowers.com","3080","19-09-2024 17:07:35","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003111974","A=
hala","","19-09-2024 17:04:43","19-09-2024 15:45:30","19-09-2024 15:53:30",=
"Grid Outage: the site went down before DG started due to poor Battery back=
up// DG started automatically.","Hyemafo Gildas","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid Outage: the site wen=
t down before DG started due to poor Battery backup// DG started automatica=
lly.","kouoh.jean@ihstowers.com","4753","19-09-2024 17:04:43","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003111930","Lobo OCM=
","","19-09-2024 16:58:00","19-09-2024 16:39:56","19-09-2024 16:45:56","Cas=
caded Incident from TTO2958279","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automatically","s=
ystem","1084","19-09-2024 16:58:00","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003111918","N=
KOMEKUI OCM","IHS_YND_341","19-09-2024 16:56:07","19-09-2024 16:39:56","19-=
09-2024 16:45:56","Grid outage, site went down before gen start due to poor=
 battery backup // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, site went down before gen start due to poor battery backup // Gen=
 start automatically","kouoh.jean@ihstowers.com","972","19-09-2024 16:56:07=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003111907","Lobo OCM=
","","19-09-2024 16:55:01","19-09-2024 15:31:14","19-09-2024 15:37:14","Cas=
caded Incident from TTO2958255","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before Gen start due to poor battery backup // gen started automatically",=
"system","5027","19-09-2024 16:55:01","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003111898","N=
KOMEKUI OCM","IHS_YND_341","19-09-2024 16:53:26","19-09-2024 15:31:14","19-=
09-2024 15:37:14","Grid outage, site went down before Gen start due to poor=
 battery backup // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, site went down before Gen start due to poor battery backup // gen=
 start automatically","kouoh.jean@ihstowers.com","4933","19-09-2024 16:53:2=
6","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0003111863","EBOM",""=
,"19-09-2024 16:46:50","19-09-2024 16:25:37","19-09-2024 17:12:37","Cascade=
d Incident from TTO2958208","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power isssue, site is on grid with Ubaie=
=3D53V, Biloa(659843334) from ZTE is working on site","system","1273","19-0=
9-2024 16:46:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003111860","A=
hala","IHS_YND_257, IHS_YND_698","19-09-2024 16:45:50","19-09-2024 16:25:37=
","19-09-2024 17:12:37","No power isssue, site is on grid with Ubaie=3D53V,=
 Biloa(659843334) from ZTE is working on site","MINKA NICOLAS","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
No power isssue, site is on grid with Ubaie=3D53V, Biloa(659843334) from ZT=
E is working on site","kouoh.jean@ihstowers.com","1213","19-09-2024 16:45:5=
0","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0003111812","Jou=
vence Mbenda","","19-09-2024 16:42:24","19-09-2024 16:33:19","19-09-2024 16=
:42:19","Grid outage,Gen started and stopped with alarm high temp///he adde=
d water in radiator and Gen started","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid ou=
tage,Gen started and stopped with alarm high temp///he added water in radia=
tor and Gen started","landry.etame@ihstowers.com","545","19-09-2024 16:42:2=
4","Sagemcom CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0003111587","Oko=
la","","19-09-2024 16:23:35","19-09-2024 16:08:30","19-09-2024 17:15:30","A=
ctive, no power issue on site, U=3D54,6V Team IKOUNTI/653110630 / From hamm=
er is working on site (SWAP) ","TIENTCHEU NZETCHIEU GAEL","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e, no power issue on site, U=3D54,6V Team IKOUNTI/653110630 / From hammer i=
s working on site (SWAP) ","landry.etame@ihstowers.com","906","19-09-2024 1=
6:23:35","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003111460","Nsi=
meyong Shell","","19-09-2024 15:58:56","19-09-2024 15:46:46","19-09-2024 16=
:04:46","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen start automatically","MINKA NICOLAS","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site went d=
own before gen start due to poor battery backup // Gen start automatically"=
,"landry.etame@ihstowers.com","731","19-09-2024 15:58:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0003111403","BONAS YD=
E","","19-09-2024 15:50:32","19-09-2024 15:37:29","19-09-2024 15:55:18","Ca=
scaded Incident from TTO2957636","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage Gen failed to start due to =
charger static faulty// Grid Power return(Charger static to be replace)","s=
ystem","783","19-09-2024 15:50:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_507","NOCINC0003111405","BIYEM AS=
SI LYCEE","","19-09-2024 15:50:32","19-09-2024 15:37:29","19-09-2024 15:55:=
18","Cascaded Incident from TTO2957636","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage Gen failed to sta=
rt due to charger static faulty// Grid Power return(Charger static to be re=
place)","system","783","19-09-2024 15:50:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0003111406","BIYEMASS=
I NIKI","","19-09-2024 15:50:32","19-09-2024 15:37:29","19-09-2024 15:55:18=
","Cascaded Incident from TTO2957636","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage Gen failed to start=
 due to charger static faulty// Grid Power return(Charger static to be repl=
ace)","system","783","19-09-2024 15:50:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0003111404","Behind P=
 T school Yde","","19-09-2024 15:50:32","19-09-2024 15:37:29","19-09-2024 1=
5:55:18","Cascaded Incident from TTO2957636","Paul BIBOUM","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage Gen failed to s=
tart due to charger static faulty// Grid Power return(Charger static to be =
replace)","system","783","19-09-2024 15:50:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0003111398","Scalom",=
"","19-09-2024 15:50:31","19-09-2024 15:37:29","19-09-2024 15:55:18","Casca=
ded Incident from TTO2957636","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage Gen failed to start due to cha=
rger static faulty// Grid Power return(Charger static to be replace)","syst=
em","782","19-09-2024 15:50:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0003111400","Ngoa Eke=
lle","","19-09-2024 15:50:31","19-09-2024 15:37:29","19-09-2024 15:55:18","=
Cascaded Incident from TTO2957636","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage Gen failed to start due t=
o charger static faulty// Grid Power return(Charger static to be replace)",=
"system","782","19-09-2024 15:50:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0003111402","Biyemass=
i LAC","","19-09-2024 15:50:31","19-09-2024 15:37:29","19-09-2024 15:55:18"=
,"Cascaded Incident from TTO2957636","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage Gen failed to start due to charger=
 static faulty// Grid Power return(Charger static to be replace)","system",=
"782","19-09-2024 15:50:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0003111401","Accacia =
New","","19-09-2024 15:50:31","19-09-2024 15:37:29","19-09-2024 15:55:18","=
Cascaded Incident from TTO2957636","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage Gen failed to start due to charger s=
tatic faulty// Grid Power return(Charger static to be replace)","system","7=
82","19-09-2024 15:50:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0003111399","Obili Ch=
apelle","","19-09-2024 15:50:31","19-09-2024 15:37:29","19-09-2024 15:55:18=
","Cascaded Incident from TTO2957636","Paul BIBOUM","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage Gen failed to start du=
e to charger static faulty// Grid Power return(Charger static to be replace=
)","system","782","19-09-2024 15:50:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003111376","T=
singa","","19-09-2024 15:46:06","19-09-2024 15:36:56","19-09-2024 15:52:39"=
,"Grid Outage, site went down before DG start due to poor Battery backup// =
DG started automatically.","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid Outage, site went down bef=
ore DG start due to poor Battery backup// DG started automatically.","kouoh=
.jean@ihstowers.com","551","19-09-2024 15:46:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0003111370","B=
astos Ekoudou","","19-09-2024 15:44:29","19-09-2024 15:34:20","19-09-2024 1=
5:44:20","Grid outage, site went down before gen start due to poor battery =
backup // Gen start automatically","Mboua Thierry","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // Gen start automatically=
","kouoh.jean@ihstowers.com","610","19-09-2024 15:44:29","Sagemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0003111361","Nlo=
ng Mvolye New","IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND_562, IHS_YND=
_546, IHS_YND_683, IHS_YND_805, IHS_YND_507, IHS_YND_724","19-09-2024 15:42=
:38","19-09-2024 15:37:29","19-09-2024 15:55:18","Grid outage Gen failed to=
 start due to charger static faulty// Grid Power return(Charger static to b=
e replace)","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - G=
enerator Battery","Grid outage Gen failed to start due to charger static fa=
ulty// Grid Power return(Charger static to be replace)","landry.etame@ihsto=
wers.com","310","19-09-2024 15:42:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003111251","ELOUMDEM=
 CARRIERE","","19-09-2024 15:28:30","19-09-2024 15:19:31","19-09-2024 15:27=
:31","Cascaded Incident from TTO2957512","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, site went down bef=
ore DG start due to poor Battery backup// DG started automatically.","syste=
m","539","19-09-2024 15:28:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003111252","MBALNGON=
G LYCEE","","19-09-2024 15:28:30","19-09-2024 15:19:31","19-09-2024 15:27:3=
1","Cascaded Incident from TTO2957512","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, site went down befor=
e DG start due to poor Battery backup// DG started automatically.","system"=
,"539","19-09-2024 15:28:30","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003111245","Aha=
la","IHS_YND_767, IHS_YND_765","19-09-2024 15:27:36","19-09-2024 15:19:29",=
"19-09-2024 15:27:31","Grid Outage, site went down before DG start due to p=
oor Battery backup// DG started automatically.","Hyemafo Gildas","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outa=
ge, site went down before DG start due to poor Battery backup// DG started =
automatically.","landry.etame@ihstowers.com","1871","19-09-2024 15:27:36","=
Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003111136","San=
ta Barbara Gottam","","19-09-2024 15:08:12","19-09-2024 15:01:03","19-09-20=
24 15:17:58","Grid outage Site went down because Gen started and stop due t=
o ""Over-Current"" alarm //Grid Restored","Delor Telezing","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Grid outage Site went down =
because Gen started and stop due to ""Over-Current"" alarm //Grid Restored"=
,"landry.etame@ihstowers.com","430","19-09-2024 15:08:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003110939","M=
ambine","","19-09-2024 14:27:34","19-09-2024 14:03:56","19-09-2024 15:57:01=
","Site on DG due to grid ,DG stopped due to low oil pressure //He added oi=
lr and maually start of DG","Fanda Brice","Equipment Repair","Passive","ACD=
G Gen","ACDG - Low Oil Pressure","Site on DG due to grid ,DG stopped due to=
 low oil pressure //He added oilr and maually start of DG","kouoh.jean@ihst=
owers.com","1418","19-09-2024 14:27:34","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003110734","Pha=
rmacie SION","","19-09-2024 13:54:49","19-09-2024 13:44:42","19-09-2024 13:=
54:24","Grid outage, site went down before Gen start due to poor battey bac=
kup // gen start automatically","Paul BIBOUM","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before Gen start due to poor battey backup // gen start automatically","ste=
phane.nkamwa@ihstowers.com","608","19-09-2024 13:54:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003110525","M=
IMBOMAN LIBERTE","","19-09-2024 13:17:32","19-09-2024 13:08:27","19-09-2024=
 13:39:59","Grid outage site went down because Gen stopped with alarm low o=
il pressure // He reset the Gen card and Gen manaully started","Mba Lazare =
Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage site went down because Gen stopped with alarm low oil pressure // H=
e reset the Gen card and Gen manaully started","emmanuel.ghani@ihstowers.co=
m","546","19-09-2024 13:17:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0003110520","C=
arington","","19-09-2024 13:15:25","19-09-2024 13:04:22","19-09-2024 13:45:=
12","grid outage//grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","grid outage//grid return","emmanuel.ghani@ihstow=
ers.com","665","19-09-2024 13:15:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0003110471","M=
endong Maeture","","19-09-2024 13:05:08","19-09-2024 12:34:01","19-09-2024 =
13:45:46","Grid Outage  site went down because Gen Ran untill fuel shortage=
 // refuelling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Die=
sel Outage","Grid Outage  site went down because Gen Ran untill fuel shorta=
ge // refuelling done","emmanuel.ghani@ihstowers.com","1868","19-09-2024 13=
:05:08","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003110456","MAN=
GUIERS CHAPELLE","","19-09-2024 13:00:52","19-09-2024 12:54:21","19-09-2024=
 13:06:43","Grid outage, site went down before Gen start due to poor battey=
 backup // gen start automatically","Fabrice Pouakam","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down before Gen start due to poor battey backup // gen start automatical=
ly","stephane.nkamwa@ihstowers.com","392","19-09-2024 13:00:52","Sagemcom C=
MR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003110445","Jou=
vence 2000","","19-09-2024 12:58:49","19-09-2024 12:51:38","19-09-2024 13:4=
0:11","Grid outage, site went down before Gen start due to poor battey back=
up // gen start automatically","Delor Telezing","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before Gen start due to poor battey backup // gen start automatically","s=
tephane.nkamwa@ihstowers.com","432","19-09-2024 12:58:49","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003110441","NKO=
MEKUI OCM","","19-09-2024 12:57:16","19-09-2024 12:49:20","19-09-2024 13:15=
:02","Grid outage, site went down before Gen start due to poor battey backu=
p // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before Gen start due to poor battey backup // gen start automati=
cally","stephane.nkamwa@ihstowers.com","477","19-09-2024 12:57:16","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003110437","M=
imboman-Village","IHS_YND_709","19-09-2024 12:56:48","19-09-2024 12:49:41",=
"19-09-2024 13:22:42","Grid outage, site went down before Gen start due to =
poor battey backup // gen start automatically","Mba Lazare Herve","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, site went down before Gen start due to poor battey backup // gen start=
 automatically","emmanuel.ghani@ihstowers.com","428","19-09-2024 12:56:48",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003110428","N=
kolo II New","","19-09-2024 12:55:15","19-09-2024 12:49:41","19-09-2024 13:=
22:42","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, site went down before Gen start due to poor =
battey backup // gen start automatically","emmanuel.ghani@ihstowers.com","3=
578","19-09-2024 12:55:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003110417","E=
lig-Edzoa","","19-09-2024 12:53:51","19-09-2024 12:50:45","19-09-2024 13:32=
:30","Grid Outage//Grid restored","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid Outage//Grid restored","emmanuel.ghani@i=
hstowers.com","187","19-09-2024 12:53:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003110159","B=
itoto","","19-09-2024 12:17:29","19-09-2024 12:09:24","19-09-2024 12:12:45"=
,"Active// No power issue on site U=3D53,4v site on Grid RM Alain/691144423=
/ of huawei is informed","Mba Lazare Herve","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power i=
ssue on site U=3D53,4v site on Grid RM Alain/691144423/ of huawei is inform=
ed","emmanuel.ghani@ihstowers.com","486","19-09-2024 12:17:29","Sagemcom CM=
R"
"Closed Complete","Warning","T1551","IHS_YND_316","NOCINC0003110057","Akak-=
Nkozoa-MTN-IHS","","19-09-2024 11:57:38","","","Grid Fluctuation site alarm=
ing because Gen started and stopped due to Grid Bad voltage causing alarms =
""undervoltage"" ""underfrequency""(unprouven)//He reset Card Gen bypassed =
Grid and started Gen manual","Fabrice Pouakam","Warning","Warning","POWER",=
"Warning - Site on Battery","Grid Fluctuation site alarming because Gen sta=
rted and stopped due to Grid Bad voltage causing alarms ""undervoltage"" ""=
underfrequency""(unprouven)//He reset Card Gen bypassed Grid and started Ge=
n manually","kombi.samuel@ihstowers.com","2","19-09-2024 11:57:38","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0003110016","S=
IMBOCK BONAMBAPE","","19-09-2024 11:51:05","19-09-2024 11:46:44","19-09-202=
4 12:05:52","Active// No power issue on site U=3D56,4v site on Gen Team Eri=
c BODO /696422966/ZTE working on site","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power issue on site U=3D56,4v site on Gen Team Eric BODO /696422966/ZT=
E working on site","emmanuel.ghani@ihstowers.com","261","19-09-2024 11:51:0=
5","Sagemcom CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0003109823","N=
simalen OCM","","19-09-2024 11:12:26","19-09-2024 11:07:18","19-09-2024 12:=
03:38","grid outage//grid return","Albran Byorel","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","grid outage//grid return","emman=
uel.ghani@ihstowers.com","309","19-09-2024 11:12:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003109618","B=
iteng","","19-09-2024 10:40:05","19-09-2024 10:25:58","19-09-2024 10:29:58"=
,"Active//No power issue on site U=3D54v site on grid lionel steeve (655184=
876) of huawei is informed.","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue on site U=3D54v site on grid lionel steeve (655184876) of huawei is=
 informed.","emmanuel.ghani@ihstowers.com","848","19-09-2024 10:40:05","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003109587","M=
elen Ba'aba","","19-09-2024 10:33:22","19-09-2024 10:32:17","19-09-2024 11:=
05:30","Grid Fluctuation,site went down before DG start : Poor Batteries Ba=
ckup // DG started automatically.","Siligap Boris","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuation,site w=
ent down before DG start : Poor Batteries Backup // DG started automaticall=
y.","emmanuel.ghani@ihstowers.com","67","19-09-2024 10:33:22","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0003109193","M=
om","","19-09-2024 09:34:34","19-09-2024 09:32:30","19-09-2024 09:41:39","g=
rid outage, site went down because gen failed to start due to gen card faul=
ty// gen manually started","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","grid outage, site went down because gen faile=
d to start due to gen card faulty// gen manually started","emmanuel.ghani@i=
hstowers.com","126","19-09-2024 09:34:34","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0003108933","MVA=
N SACEL","","19-09-2024 08:47:56","19-09-2024 08:39:43","19-09-2024 09:26:0=
8","site was on gen due to grid outage,gen stopped due to oil leakage//adde=
d oil and started the gen (still working)","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Oil Leakage","site was on gen due to grid o=
utage,gen stopped due to oil leakage//added oil and started the gen (still =
working)","stephane.nkamwa@ihstowers.com","1001","19-09-2024 08:47:56","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003108852","A=
KONGO","","19-09-2024 08:25:44","19-09-2024 08:17:35","19-09-2024 11:19:43"=
,"Active:  No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rod=
rigue (655102999)from Huawei is informed. Repetitive issue Notice that heav=
y rain on the area","Fanda Brice","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active:  No power issue on si=
te Ubaie=3D52,5V site on Gen. The Tx FME Rodrigue (655102999)from Huawei is=
 informed. Repetitive issue Notice that heavy rain on the area","emmanuel.g=
hani@ihstowers.com","490","19-09-2024 08:25:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003108806","M=
ambine","","19-09-2024 08:15:19","19-09-2024 08:03:12","19-09-2024 08:16:58=
","Site went down because Gen failed to start due to Hybrid system dysfonct=
ion// He reset the hybrid system, site on gen","Fanda Brice","Equipment Rep=
air","Passive","Hybrid","Hybrid Module","Site went down because Gen failed =
to start due to Hybrid system dysfonction// He reset the hybrid system, sit=
e on gen","emmanuel.ghani@ihstowers.com","728","19-09-2024 08:15:19","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0003108568","H=
-Franco New","","19-09-2024 07:47:48","19-09-2024 07:31:37","19-09-2024 08:=
00:23","No power issue, site is on grid with Ubaie=3D53,3V, Armand Nguetsa(=
699949553) from Huawei is informed","Delor Telezing","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue, site is on grid with Ubaie=3D53,3V, Armand Nguetsa(699949553) from Hu=
awei is informed","emmanuel.ghani@ihstowers.com","972","19-09-2024 07:47:48=
","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0003108502","Nom=
ayos montee Meche","","19-09-2024 07:32:15","19-09-2024 07:17:05","19-09-20=
24 08:29:36","","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","site went down due to gen because gen stopped without al=
arm//started the gen (investigations ongoing)","stephane.nkamwa@ihstowers.c=
om","910","19-09-2024 07:32:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003108432","A=
WAE OCM","","19-09-2024 07:16:19","19-09-2024 07:07:08","19-09-2024 11:15:2=
0","No power issue on site U=3D54v site on grid lionel steeve (655184876) o=
f huawei is informed.","Mba Lazare Herve","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54v site on grid lionel steeve (655184876) of huawei is informed.","e=
mmanuel.ghani@ihstowers.com","552","19-09-2024 07:16:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0003108396","T=
radex-Nkomo","","19-09-2024 07:11:23","19-09-2024 07:02:16","19-09-2024 08:=
00:49","Technician is on site.","Albran Byorel","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site ubaie=3D54v site on grid lonel Adjep is informed","emmanuel.ghani@i=
hstowers.com","548","19-09-2024 07:11:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003108365","A=
hala","","19-09-2024 07:02:10","19-09-2024 06:57:00","19-09-2024 11:35:45",=
"No power isssue, site is on grid with Ubaie=3D53V, Lionel Tchatchoua(69469=
3436) from Huawei is informed.","MINKA NICOLAS","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power isssue=
, site is on grid with Ubaie=3D53V, Lionel Tchatchoua(694693436) from Huawe=
i is informed.
","emmanuel.ghani@ihstowers.com","311","19-09-2024 07:02:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003108325","B=
iteng","","19-09-2024 06:52:39","19-09-2024 06:43:33","19-09-2024 10:20:29"=
,"No power issue on site U=3D54v site on grid lionel steeve (655184876) of =
huawei is informed.","Mba Lazare Herve","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D54v site on grid lionel steeve (655184876) of huawei is informed.","emm=
anuel.ghani@ihstowers.com","547","19-09-2024 06:52:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003108178","N=
kozoa","","19-09-2024 06:21:43","19-09-2024 06:06:38","19-09-2024 08:59:50"=
,"Grid bad voltage, site went down because gen ran untill fuel shortage // =
Refueling done.","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Grid bad voltage, site went down because gen ran untill fuel shor=
tage // Refueling done.","emmanuel.ghani@ihstowers.com","906","19-09-2024 0=
6:21:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003108082","B=
iteng-Maetur","","19-09-2024 06:03:21","19-09-2024 05:58:14","19-09-2024 12=
:30:34","No power issue on site U=3D54v site on grid lionel steeve (6551848=
76) of huawei is informed","Mba Lazare Herve","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site U=3D54v site on grid lionel steeve (655184876) of huawei is informed"=
,"ludivine.ngamaleu@ihstowers.com","308","19-09-2024 06:03:21","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003108078","E=
kie-Elegance","","19-09-2024 06:02:24","19-09-2024 05:57:17","19-09-2024 06=
:30:27","Grid outage  //MDG of 20 kva has deployed","Albran Byorel","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage  /=
/MDG of 20 kva has deployed","ludivine.ngamaleu@ihstowers.com","308","19-09=
-2024 06:02:24","Sagemcom CMR"
"Closed Complete","Site Down","T1377","IHS_YND_807","NOCINC0003107651","Aha=
la Echangeur","","19-09-2024 03:24:42","19-09-2024 02:58:29","20-09-2024 12=
:57:14","Access issue during the night, site went down due to Circuit break=
er  of (125A) which feeds the PWC disjuncted // He reamed Cb(125A), site on=
 gen.","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Circuit Breaker Issue","Access issue during the night, site went =
down due to Circuit breaker  of (125A) which feeds the PWC disjuncted // He=
 reamed Cb(125A), site on gen","etienne.itondo@ihstowers.com","1574","19-09=
-2024 03:24:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003106902","A=
WAE OCM","","18-09-2024 23:25:30","18-09-2024 23:15:59","19-09-2024 01:39:3=
1","Active// No power Issue Site on Grid Ubai =3D54,6 V  The FME tx Lionel =
Tchatchoua /694693436 is informed","Mba Lazare Herve","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// =
No power Issue Site on Grid Ubai =3D54,6 V  The FME tx Lionel Tchatchoua /6=
94693436 is informed","ludivine.ngamaleu@ihstowers.com","572","18-09-2024 2=
3:25:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003106867","E=
kombitie","","18-09-2024 23:10:43","18-09-2024 23:06:39","19-09-2024 01:31:=
21","No power issue on site U=3D54,6v site on grid Synphorien 691316854 of =
huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,6v site on grid Synphorien 691316854 of huawei is informed","ludivine=
.ngamaleu@ihstowers.com","244","18-09-2024 23:10:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003106782","Eto koss=
 Yde","","18-09-2024 22:51:50","18-09-2024 22:42:15","18-09-2024 23:56:15",=
"Cascaded Incident from TTO2952453","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,main gen faulty//MDG 20k=
va deployed","system","575","18-09-2024 22:51:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003106783","ELOUMDEM=
 CARRIERE 2","","18-09-2024 22:51:50","18-09-2024 22:42:15","18-09-2024 23:=
56:15","Cascaded Incident from TTO2952453","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage,main gen faulty//=
MDG 20kva deployed","system","575","18-09-2024 22:51:50","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003106753","Com=
plex Beac II","","18-09-2024 22:45:52","18-09-2024 22:33:46","18-09-2024 23=
:44:58","grid outage,gen failed to start due to card Ge faulty//Gen manuall=
y started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","grid outage,gen failed to start due to card Ge faulty//Gen =
manually started","olivier.kwedi@ihstowers.com","727","18-09-2024 22:45:52"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003106749","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","18-09-2024 22:44:30","18-09-2024 22:=
40:25","19-09-2024 19:54:09","grid outage,main gen faulty//MDG 20kva deploy=
ed but site up at MTN and he delected the operator Ocm waiting grid return"=
,"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fa=
ulty","Grid outage,main gen faulty//MDG 20kva deployed","ludivine.ngamaleu@=
ihstowers.com","247","18-09-2024 22:44:30","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003106736","Ess=
os Marche","","18-09-2024 22:42:31","18-09-2024 22:26:23","19-09-2024 00:46=
:45","No power issue on site U=3D54v site on grid Armand 699949553 of huawe=
i is informed","Delor Telezing","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v =
site on grid Armand 699949553 of huawei is informed","olivier.kwedi@ihstowe=
rs.com","969","18-09-2024 22:42:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0003106706","EBOM",""=
,"18-09-2024 22:35:11","18-09-2024 22:31:08","19-09-2024 00:39:35","Cascade=
d Incident from TTO2952362","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active //No power issue, site is on Grid and=
  with Ubaie=3D53,2 V ,  The Rm Alain//691144423// Huawei is informed,Notic=
e that we have disjunction at BTS OCM","system","243","18-09-2024 22:35:11"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0003106705","Ahala","=
","18-09-2024 22:35:11","18-09-2024 22:31:08","19-09-2024 00:39:35","Cascad=
ed Incident from TTO2952362","Hyemafo Gildas","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active //No power issue, site is on Grid an=
d  with Ubaie=3D53,2 V ,  The Rm Alain//691144423// Huawei is informed,Noti=
ce that we have disjunction at BTS OCM","system","243","18-09-2024 22:35:11=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003106702","A=
hala","IHS_YND_257, IHS_YND_698","18-09-2024 22:34:20","18-09-2024 22:31:08=
","19-09-2024 01:09:12","Active //No power issue, site is on Grid and  with=
 Ubaie=3D53,2 V ,  The Rm Alain//691144423// Huawei is informed,Notice that=
 we have disjunction at BTS OCM","MINKA NICOLAS","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //No po=
wer issue, site is on Grid and  with Ubaie=3D53,2 V ,  The Rm Alain//691144=
423// Huawei is informed,Notice that we have disjunction at BTS OCM","ludiv=
ine.ngamaleu@ihstowers.com","193","18-09-2024 22:34:20","Sagemcom CMR"
"Cancelled","Warning","CTR_472","IHS_YND_698","NOCINC0003106697","EBOM","",=
"18-09-2024 22:33:03","","","","Hyemafo Gildas","","","","","","ludivine.ng=
amaleu@ihstowers.com","123","18-09-2024 22:33:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003106675","O=
dza II","","18-09-2024 22:29:58","18-09-2024 22:15:56","18-09-2024 23:03:10=
","","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Contro=
l Panel","grid fluctuations, gen failed to start with alarm low oil pressue=
//reset gen card,tripped grid CB, site on gen","ludivine.ngamaleu@ihstowers=
.com","844","18-09-2024 22:29:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003106335","M=
EFOU ASSI","","18-09-2024 21:27:51","18-09-2024 21:20:47","18-09-2024 21:57=
:21","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage //Grid stabilized","Fanda Brice","Grid Supply","Passive",=
"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site we=
nt down because gen start and stopped due to grid bad voltage //Grid stabil=
ized","alexandre.kamal@ihstowers.com","425","18-09-2024 21:27:51","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0003106189","Ole=
mbe","","18-09-2024 21:08:19","18-09-2024 20:32:55","18-09-2024 23:18:55","=
site went down because CB 2*63A disjuncted in PWC(first Bay) //he bypassed =
the 2CB and connected directly in barette PWC","Fabrice Pouakam","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue",=
"site went down because CB 2*63A disjuncted in PWC(first Bay) //he bypassed=
 the 2CB and connected directly in barette PWC","kamga.virgile@ihstowers.co=
m","2125","18-09-2024 21:08:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0003105871","N=
gousso-II","","18-09-2024 20:15:41","18-09-2024 20:07:30","19-09-2024 01:10=
:24","Active, no power issue, site on grid with U=3D53,3 V, The Tx Armand N=
guetsa /691144412 //   Huawei is informed . Notice that disjonction in BTS =
ocm","MFOUAGUEGUE MATHIEU","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active, no power issue, site on grid=
 with U=3D53,3 V, The Tx Armand Nguetsa /691144412 //   Huawei is informed =
. Notice that disjonction in BTS ocm","alexandre.kamal@ihstowers.com","491"=
,"18-09-2024 20:15:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_078","IHS_YND_213","NOCINC0003105818","N=
kolmesseng","","18-09-2024 20:08:25","18-09-2024 19:55:17","19-09-2024 01:2=
0:57","Active//No power issue on site ;site on Gen with Ubaie =3D52.3 V The=
 fme tx  RM Alain // 691144423 //   Huawei is informed . Notice that disjon=
ction in BTS ocm","Siligap Boris","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on sit=
e ;site on Gen with Ubaie =3D52.3 V The fme tx  RM Alain // 691144423 //   =
Huawei is informed . Notice that disjonction in BTS ocm","alexandre.kamal@i=
hstowers.com","789","18-09-2024 20:08:25","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_146","NOCINC0003105703","Nsimeyong"=
,"","18-09-2024 19:48:45","","","SITE ON BATTERY","MINKA NICOLAS","Warning"=
,"Warning","POWER","Warning - AC Phase 1 Current Low","Alarm cleared","step=
hane.nkamwa@ihstowers.com","2176","18-09-2024 19:48:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003105541","N=
kolbisson usine des eaux","","18-09-2024 19:19:33","18-09-2024 19:16:27","1=
8-09-2024 19:31:55","Grid outage,site went down because Gen overload(15Kva,=
 345A)//site stabilized","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage,site went down because Gen =
overload(15Kva, 345A)//site stabilized","alexandre.kamal@ihstowers.com","18=
7","18-09-2024 19:19:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003105528","N=
koabang2","","18-09-2024 19:15:13","18-09-2024 19:05:59","19-09-2024 01:25:=
20","Active//No power issue on site ;site on Grid with Ubaie =3D50.5 V The =
TX FME Lionel adjep//655184876//   Huawei is informed . Notice that disjonc=
tion in BTS ocm  (repetitive issue)","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/No power issue on site ;site on Grid with Ubaie =3D50.5 V The TX FME Lione=
l adjep//655184876//   Huawei is informed . Notice that disjonction in BTS =
ocm  (repetitive issue)","alexandre.kamal@ihstowers.com","555","18-09-2024 =
19:15:13","Sagemcom CMR"
"Cancelled","Warning","T0351","IHS_YND_146","NOCINC0003105523","Nsimeyong",=
"","18-09-2024 19:13:55","","","site on battery","MINKA NICOLAS","","","","=
","","stephane.nkamwa@ihstowers.com","4","18-09-2024 19:13:55","Sagemcom CM=
R"
"Closed Complete","Site Down","T0760","IHS_YND_419","NOCINC0003105409","Ngo=
g Mapubi","","18-09-2024 18:40:30","18-09-2024 18:07:20","18-09-2024 18:08:=
20","Active// No power issue on site ,site on Gen with Ubaie=3D 54,6V The f=
me tx Etienne fopa // 695033981// of huawei is informed","Kemeni Franklin",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active// No power issue on site ,site on Gen with Ubaie=3D 54,6=
V The fme tx Etienne fopa // 695033981// of huawei is informed","kamga.virg=
ile@ihstowers.com","1991","18-09-2024 18:40:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003105106","N=
kozoa","","18-09-2024 17:45:19","18-09-2024 17:39:52","18-09-2024 19:14:33"=
,"Grid Outage,Site went down because Gen failed to start due to Gen overloa=
d(20KVA,320)//he load on site and started GEN","Fabrice Pouakam","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage,Site went down=
 because Gen failed to start due to Gen overload(20KVA,320)//he load on sit=
e and started GEN","alexandre.kamal@ihstowers.com","328","18-09-2024 17:45:=
19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0003104970","Mfou EPC=
","","18-09-2024 17:23:11","18-09-2024 17:04:14","18-09-2024 17:45:15","Cas=
caded Incident from TTO2950353","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage Site went down because =
Gen stopped due to ""high temp"" alarm //He added water and gen manually st=
arted","system","1137","18-09-2024 17:23:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0003104966","M=
fou OCM","IHS_YND_674","18-09-2024 17:22:19","18-09-2024 17:04:14","18-09-2=
024 17:45:15","Grid outage Site went down because Gen stopped due to ""high=
 temp"" alarm //He added water and gen manually started","Mba Lazare Herve"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant=
 Level Issue","Grid outage Site went down because Gen stopped due to ""high=
 temp"" alarm //He added water and gen manually started","alexandre.kamal@i=
hstowers.com","1085","18-09-2024 17:22:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0003104874","C=
harles-Atangana","","18-09-2024 17:04:48","18-09-2024 16:41:40","19-09-2024=
 01:18:40","Active// No power Issue Site on Grid Ubai =3D52,9V The Team   E=
ric bodo // 696422966 //From ZTE is working in site","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power Issue Site on Grid Ubai =3D52,9V The Team   Eric bodo // 6964229=
66 //From ZTE is working in site","alexandre.kamal@ihstowers.com","1389","1=
8-09-2024 17:04:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0003104851","M=
obil-Kondengui","IHS_YND_682","18-09-2024 17:02:11","18-09-2024 16:20:03","=
19-09-2024 11:18:04","Grid outage// Grid power return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage// Grid power=
 return","alexandre.kamal@ihstowers.com","2528","18-09-2024 17:02:11","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0003104659","M=
ONTEE NKONDENGUI","","18-09-2024 16:29:07","18-09-2024 16:20:03","19-09-202=
4 11:18:04","","Albran Byorel","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage// Grid power return","alexandre.kamal@ihsto=
wers.com","2666","18-09-2024 16:29:07","Sagemcom CMR"
"Cancelled","Warning","T0818","IHS_YND_122","NOCINC0003104376","Emombo Esss=
omba","","18-09-2024 15:43:42","","","site on battery","Mba Lazare Herve","=
","","","","","stephane.nkamwa@ihstowers.com","187","18-09-2024 15:43:42","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0003104327","M=
vog-Ebanda","","18-09-2024 15:38:00","18-09-2024 15:29:53","18-09-2024 16:4=
9:50","Grid outage site went due to short circuit  in the PWC //He resolved=
 the Shot Circuit in the PWC and Manually Started the Gen  ","Siligap Boris=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Bre=
aker Issue","Grid outage site went due to short circuit  in the PWC //He re=
solved the Shot Circuit in the PWC and Manually Started the Gen  ","alexand=
re.kamal@ihstowers.com","488","18-09-2024 15:38:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_481","IHS_YND_574","NOCINC0003104308","C=
rf-Mbankolo-IHS","","18-09-2024 15:33:44","18-09-2024 14:51:58","18-09-2024=
 14:52:58","Active// No power issue on site U=3D54,6V site on Grid Gildas w=
affo  //659653638// From ZTE working on site","Mboua Thierry","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive// No power issue on site U=3D54,6V site on Grid Gildas waffo  //65965=
3638// From ZTE working on site","alexandre.kamal@ihstowers.com","2507","18=
-09-2024 15:33:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003104236","O=
lembe","","18-09-2024 15:15:49","18-09-2024 15:08:45","18-09-2024 15:08:50"=
,"Active// No power Issue Site on Grid Ubai =3D51,9 V The Fme TX Synphorien=
  /675295205// from Huawei is informed ","Fabrice Pouakam","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power Issue Site on Grid Ubai =3D51,9 V The Fme TX Synphorien  /675=
295205// from Huawei is informed ","alexandre.kamal@ihstowers.com","425","1=
8-09-2024 15:15:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0003104226","H=
-Franco New","","18-09-2024 15:14:41","18-09-2024 15:04:59","18-09-2024 15:=
07:56","Active// No power issue, site on grid with U=3D53,3 V, The Tx Arman=
d Nguetsa /691144412/ From Huawei is informed","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power issue, site on grid with U=3D53,3 V, The Tx Armand Nguet=
sa /691144412/ From Huawei is informed","alexandre.kamal@ihstowers.com","58=
3","18-09-2024 15:14:41","Sagemcom CMR"
"Closed Complete","Site Down","T1432","IHS_YND_544","NOCINC0003104116","Jea=
n Vespa 2","","18-09-2024 14:57:31","18-09-2024 14:52:23","19-09-2024 01:20=
:23","Active// No power issue on site ,site on Grid with Ubaie=3D 53,5V, th=
e Team ERIC  (696422966) from ZTE are working on Site.","Mboua Thierry","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active// No power issue on site ,site on Grid with Ubaie=3D 53,5V,=
 the Team ERIC  (696422966) from ZTE are working on Site. ","kamga.virgile@=
ihstowers.com","309","18-09-2024 14:57:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0003103750","EBOM",""=
,"18-09-2024 14:13:41","18-09-2024 13:49:52","18-09-2024 13:50:52","Cascade=
d Incident from TTO2948828","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","tx","system","1429","18-09-2024 14:13:41","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0003103669","M=
essassi 2","","18-09-2024 14:11:19","18-09-2024 12:41:06","19-09-2024 00:42=
:19","Active//No power issue, site is on Grid with Ubaie=3D55V, The fme TX =
Symphorien 675295205 from Huawei is informed","Fabrice Pouakam","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No power issue, site is on Grid with Ubaie=3D55V, The fme TX Symph=
orien 675295205 from Huawei is informed","kouoh.jean@ihstowers.com","5414",=
"18-09-2024 14:11:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0003103652","Ahala","=
","18-09-2024 14:09:00","18-09-2024 13:49:52","18-09-2024 13:50:52","Cascad=
ed Incident from TTO2948828","Hyemafo Gildas","Cascade Outage","Active","Ca=
scade Active","Cascade Active","tx","system","1148","18-09-2024 14:09:00","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003103646","A=
hala","IHS_YND_257, IHS_YND_698","18-09-2024 14:08:13","18-09-2024 13:49:52=
","18-09-2024 13:50:52","Active //No power issue, site is on Grid and  with=
 Ubaie=3D53,2 V ,  The TX FME Leonel//694693436// Huawei is informed,Notice=
 that we have disjunction at BTS OCM ","MINKA NICOLAS","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active /=
/No power issue, site is on Grid and  with Ubaie=3D53,2 V ,  The TX FME Leo=
nel//694693436// Huawei is informed,Notice that we have disjunction at BTS =
OCM ","kouoh.jean@ihstowers.com","1102","18-09-2024 14:08:13","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0003103624","MONTEE N=
KONDENGUI","","18-09-2024 14:04:20","18-09-2024 13:33:00","18-09-2024 14:54=
:00","Cascaded Incident from TTO2948791","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage  //MDG of 20 kva =
has deployed","system","1880","18-09-2024 14:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0003103622","MONTEE N=
KONDENGUI","","18-09-2024 14:04:10","18-09-2024 11:33:01","18-09-2024 12:20=
:01","Cascaded Incident from TTO2947508","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage //Grid power retu=
rn","system","9069","18-09-2024 14:04:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0003103620","M=
obil-Kondengui","IHS_YND_682","18-09-2024 14:03:25","18-09-2024 13:33:00","=
18-09-2024 14:54:00","Grid outage  //MDG of 20 kva has deployed","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage  /=
/MDG of 20 kva has deployed","kouoh.jean@ihstowers.com","1826","18-09-2024 =
14:03:25","Sagemcom CMR"
"Closed Complete","Site Down","T0958","IHS_YND_269","NOCINC0003103388","Mvo=
g-Ebanda","","18-09-2024 13:25:04","18-09-2024 13:19:43","18-09-2024 13:38:=
30","grid outage, site went down because gen start and stopped due to grid =
bad voltage//he did a bridge on good phase","Siligap Boris","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","grid outage, sit=
e went down because gen start and stopped due to grid bad voltage//he did a=
 bridge on good phase","landry.etame@ihstowers.com","726","18-09-2024 13:25=
:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_481","IHS_YND_574","NOCINC0003103197","C=
rf-Mbankolo-IHS","","18-09-2024 12:55:56","18-09-2024 12:37:41","18-09-2024=
 12:40:41","Active// No power Issue Site on Grid Ubai =3D54,6 V The TX FME =
 WAFFO Gildas // 659653638 From ZTE is working in site","Mboua Thierry","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active// No power Issue Site on Grid Ubai =3D54,6 V The TX FME  WA=
FFO Gildas // 659653638 From ZTE is working in site","kouoh.jean@ihstowers.=
com","1096","18-09-2024 12:55:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0003103121","Ahala","=
","18-09-2024 12:43:20","18-09-2024 12:25:37","18-09-2024 12:30:37","Cascad=
ed Incident from TTO2948129","Hyemafo Gildas","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active// No power Issue Site on Gen Ubai =
=3D55,6 V The TX FME  Eric bodo // 696422966 From ZTE is working in site","=
system","1063","18-09-2024 12:43:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0003103075","A=
hala","IHS_YND_257","18-09-2024 12:35:46","18-09-2024 12:25:37","18-09-2024=
 12:30:37","Active// No power Issue Site on Gen Ubai =3D55,6 V The TX FME  =
Eric bodo // 696422966 From ZTE is working in site","MINKA NICOLAS","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power Issue Site on Gen Ubai =3D55,6 V The TX FME  Eric bo=
do // 696422966 From ZTE is working in site","kouoh.jean@ihstowers.com","61=
0","18-09-2024 12:35:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003102768","S=
calom-IHS","","18-09-2024 12:14:51","18-09-2024 09:02:05","19-09-2024 01:10=
:05","Active// No power Issue Site on Grid Ubai =3D55,2 V, The TX FME Mbah =
Hosiah (674007438) is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site=
 on Grid Ubai =3D55,2 V, The TX FME Mbah Hosiah (674007438) is informed","k=
ouoh.jean@ihstowers.com","11567","18-09-2024 12:14:51","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0003102754","Crf=
-Mbankolo-IHS","","18-09-2024 12:11:27","18-09-2024 12:01:37","18-09-2024 1=
2:11:21","Site went down due to work Thierry Mboua/699751197/Sagemcom/Insta=
llation activity/ is working on site // END OF WORK","Mboua Thierry","Insta=
llation Activity","Passive","Planned Activity","Installation Activity","Sit=
e went down due to work Thierry Mboua/699751197/Sagemcom/Installation activ=
ity/ is working on site // END OF WORK","landry.etame@ihstowers.com","3077"=
,"18-09-2024 12:11:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0003102514","M=
obil-Kondengui","IHS_YND_682","18-09-2024 11:35:21","18-09-2024 11:33:01","=
18-09-2024 12:20:01","Grid outage //Grid power return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage //Grid power=
 return","kouoh.jean@ihstowers.com","141","18-09-2024 11:35:21","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003102457","K=
oweit City","","18-09-2024 11:30:07","18-09-2024 11:22:39","18-09-2024 13:3=
1:39","Site went down because CB 125A who feeds equipment Ocm disjuncted in=
 DC BOX//he did a bridge with anothers CB(80A) and CB(63A)","Albran Byorel"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Brea=
ker Issue","Site went down because CB 125A who feeds equipment Ocm disjunct=
ed in DC BOX//he did a bridge with anothers CB(80A) and CB(63A)","kouoh.jea=
n@ihstowers.com","448","18-09-2024 11:30:07","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003102340","Com=
plex Beac II","","18-09-2024 11:14:35","18-09-2024 11:03:29","18-09-2024 11=
:35:29","Grid  outage,site went down because Gen Card Faulty // Grid return=
","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","Grid  outage,site went down because Gen Card Faulty // Grid return",=
"landry.etame@ihstowers.com","667","18-09-2024 11:14:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003102189","A=
kak-Nkozoa-MTN-IHS","","18-09-2024 10:53:20","18-09-2024 10:43:09","18-09-2=
024 11:43:09","site went down because the Cb(125A) of PWC Dysjoncted// he m=
ade the bridge of CB(63*63A) ","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Circuit Breaker Issue","site went down =
because the Cb(125A) of PWC Dysjoncted// he made the bridge of CB(63*63A) "=
,"kouoh.jean@ihstowers.com","613","18-09-2024 10:53:20","Sagemcom CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0003102041","Kon=
dengui MTN","","18-09-2024 10:33:04","18-09-2024 10:28:58","18-09-2024 11:2=
9:58","Site went down due to  CB Rectifier Disjunted Due to 1/4 rectifier f=
aulty // He reamed the (CB) Rectifier","Albran Byorel","Equipment Repair","=
Passive","Rectifier","Rectifier - Circuit Breaker","Site went down due to  =
CB Rectifier Disjunted Due to 1/4 rectifier faulty // He reamed the (CB) Re=
ctifier","landry.etame@ihstowers.com","247","18-09-2024 10:33:04","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0003101989","ETO=
UDI CHAPELLE","","18-09-2024 10:26:41","18-09-2024 10:03:28","18-09-2024 10=
:59:28","GRID fluctuation, site went down because gen fails to start due to=
 grid bad voltage // he bypass grid and manually start the gen","Delor Tele=
zing","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","GRID fluctuation, site went down because gen fails to start due to gri=
d bad voltage // he bypass grid and manually start the gen","landry.etame@i=
hstowers.com","1515","18-09-2024 10:26:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0003101801","O=
bobogo","","18-09-2024 09:58:59","18-09-2024 09:41:50","18-09-2024 10:22:50=
","","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active// No power Issue Site on Gen Ubai =
=3D55,6 V The TX FME  Eric bodo // 696422966 From ZTE is working in site","=
kouoh.jean@ihstowers.com","1029","18-09-2024 09:58:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_332","NOCINC0003101522","NKOMEKUI=
 OCM","IHS_YND_341","18-09-2024 09:03:20","18-09-2024 08:26:40","18-09-2024=
 08:32:40","Grid outage, site went down before gen start due to poor battey=
 backup // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
, site went down before gen start due to poor battey backup // gen start au=
tomatically","system","2200","18-09-2024 09:03:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0003101519","L=
obo OCM","","18-09-2024 09:01:56","18-09-2024 08:26:40","18-09-2024 08:32:4=
0","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid outage, site went down before gen start due to p=
oor battey backup // gen start automatically","kouoh.jean@ihstowers.com","2=
117","18-09-2024 09:01:56","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0003101252","MBA=
LNGONG LYCEE","","18-09-2024 08:36:45","18-09-2024 08:28:34","18-09-2024 09=
:46:34"," Grid Bad Voltage, Site wend down because  Gen fails to start due =
to lack on 02 phases on site //He make the bridge on good phase ","Fanda Br=
ice","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y"," Grid Bad Voltage, Site wend down because  Gen fails to start due to la=
ck on 02 phases on site //He make the bridge on good phase ","landry.etame@=
ihstowers.com","492","18-09-2024 08:36:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0003101096","MONTEE N=
KONDENGUI","","18-09-2024 08:02:52","18-09-2024 07:51:18","18-09-2024 10:22=
:18","Cascaded Incident from TTO2945848","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage  // MDG of 20 kva=
 has deployed","system","694","18-09-2024 08:02:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0003101088","M=
obil-Kondengui","IHS_YND_682","18-09-2024 08:01:24","18-09-2024 07:51:18","=
18-09-2024 10:22:18","Grid outage  // MDG of 20 kva has deployed","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage  =
// MDG of 20 kva has deployed","kouoh.jean@ihstowers.com","608","18-09-2024=
 08:01:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0003100671","A=
WAE OCM","","18-09-2024 07:02:38","18-09-2024 06:20:21","18-09-2024 06:30:2=
1","Active// No power Issue Site on Grid Ubai =3D54,6 V  The FME tx Lionel =
Tchatchoua /694693436 is informed","Mba Lazare Herve","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// =
No power Issue Site on Grid Ubai =3D54,6 V  The FME tx Lionel Tchatchoua /6=
94693436 is informed","kouoh.jean@ihstowers.com","2538","18-09-2024 07:02:3=
8","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003100579","S=
ous Prefecture","","18-09-2024 06:38:34","18-09-2024 06:32:24","18-09-2024 =
06:35:24","Active// No power Issue Site on Grid Ubai =3D54,6 V  The FME tx =
Lionel Tchatchoua /694693436 is informed","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power Issue Site on Grid Ubai =3D54,6 V  The FME tx Lionel Tchatchoua =
/694693436 is informed","kouoh.jean@ihstowers.com","371","18-09-2024 06:38:=
34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0003100459","Nkolkoum=
ou OCM","","18-09-2024 06:23:20","18-09-2024 06:17:52","18-09-2024 06:58:52=
","Cascaded Incident from TTO2945134","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Passive","Cascade Passive","Cascade Passive","Grid bad voltage, gen=
 fails to start due to gen Overload(15Kva, 275A) // He reduice the load on =
site and manually start the gen","system","328","18-09-2024 06:23:20","Sage=
mcom CMR"
"Closed Complete","Site Down","T1497","IHS_YND_545","NOCINC0003100456","Nko=
lbisson usine des eaux","IHS_YND_712","18-09-2024 06:22:28","18-09-2024 06:=
17:52","18-09-2024 06:58:52","Grid bad voltage, gen fails to start due to g=
en Overload(15Kva, 275A) // He reduice the load on site and manually start =
the gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid bad voltage, gen fails to start due to gen Overloa=
d(15Kva, 275A) // He reduice the load on site and manually start the gen","=
landry.etame@ihstowers.com","730","18-09-2024 06:22:28","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0003100159","MBA=
LNGONG LYCEE","","18-09-2024 04:44:22","18-09-2024 04:37:10","18-09-2024 06=
:02:51","Grid Bad Voltage  Site wend down because  Gen Failed to start and =
due to lack on 02 phases on site //He make the bridge on good phase ","Fand=
a Brice","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid Bad Voltage  Site wend down because  Gen Failed to start and d=
ue to lack on 02 phases on site //He make the bridge on good phase ","olivi=
er.kwedi@ihstowers.com","433","18-09-2024 04:44:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0003100020","E=
NAM","","18-09-2024 03:55:49","18-09-2024 03:51:34","18-09-2024 08:52:34","=
Access issue during the night, Site went down due to cb(100A) grid dysjonct=
ed // he reamed the CB","","Access Denial","Lease Or Legal","Landlord Relat=
ed Issues","Access Issue - Land Lord","Access issue during the night, Site =
went down due to cb(100A) grid dysjoncted // he reamed the CB","denis.mball=
a@ihstowers.com","256","18-09-2024 03:55:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0003099611","M=
beng","IHS_YND_553","18-09-2024 02:10:53","18-09-2024 01:35:18","18-09-2024=
 03:37:50","Grid outage,site went down because gen ran untill fuel shortage=
//refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage,site went down because gen ran untill fuel shortage//ref=
ueling done","denis.mballa@ihstowers.com","2136","18-09-2024 02:10:53","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003099208","M=
elen Ba'aba","","18-09-2024 00:35:26","18-09-2024 00:33:07","18-09-2024 00:=
35:36","Grid fluctuation ,site went down before gen start due to poor batte=
ry backup//Gen started automatically","Siligap Boris","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid fluctuation ,si=
te went down before gen start due to poor battery backup//Gen started autom=
atically","denis.mballa@ihstowers.com","140","18-09-2024 00:35:26","Sagemco=
m CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003099123","MBI=
MBIM","","18-09-2024 00:05:38","18-09-2024 00:02:33","18-09-2024 03:06:03",=
"Solar gen site, site went down because Gen started and stopped due to the =
fuel and water mixture in the Tank // He purged the Tank","Parker Tchoup","=
Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In T=
he Fuel","Solar gen site, site went down because Gen started and stopped du=
e to the fuel and water mixture in the Tank // He purged the Tank","olivier=
.kwedi@ihstowers.com","186","18-09-2024 00:05:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003099032","S=
ous Prefecture","","17-09-2024 23:41:14","17-09-2024 23:32:03","17-09-2024 =
23:40:00","Active// No power Issue Site on Grid Ubai =3D54,4 V  The FME tx =
Lionel Tchatchoua /694693436 is informed Notice that heavy rain on the area=
","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active// No power Issue Site on Grid Ubai =3D54=
,4 V  The FME tx Lionel Tchatchoua /694693436 is informed Notice that heavy=
 rain on the area","denis.mballa@ihstowers.com","552","17-09-2024 23:41:14"=
,"Sagemcom CMR"
"Cancelled","Warning","T1241","IHS_YND_794","NOCINC0003098533","Nkoulou Car=
riere carrefourt","","17-09-2024 22:07:07","","","","Mba Lazare Herve","","=
","","","","dorothy.djantio@ihstowers.com","7747","17-09-2024 22:07:07","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0003098251","Odz=
a II","","17-09-2024 21:31:42","17-09-2024 21:29:36","17-09-2024 21:34:12",=
"Grid outage  site down due to poor backup before gen start  //Grid return"=
,"Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Battery Low","Grid outage  site down due to poor backup before gen star=
t  //Grid return","dorothy.djantio@ihstowers.com","127","17-09-2024 21:31:4=
2","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0003098025","Tsi=
nga village","","17-09-2024 20:54:48","17-09-2024 20:48:44","17-09-2024 22:=
43:42","site went down insufficient rectifier  on site(site on 2 rectifiers=
)//site stabilized (need to added 02 rectifiers)","Delor Telezing","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","site went down insuffi=
cient rectifier  on site(site on 2 rectifiers)//site stabilized (need to ad=
ded 02 rectifiers)","dorothy.djantio@ihstowers.com","365","17-09-2024 20:54=
:48","Sagemcom CMR"
"Cancelled","Warning","CTR_675","IHS_YND_719","NOCINC0003097982","TSINGA VI=
LLAGE 2","","17-09-2024 20:50:24","","","","Delor Telezing","","","","","",=
"ludivine.ngamaleu@ihstowers.com","256","17-09-2024 20:50:24","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0003097672","B=
ONAS YDE","","17-09-2024 20:15:52","17-09-2024 20:10:47","17-09-2024 20:15:=
29","Active// No power Issue Site on Grid Ubai =3D54,6 V, The TX FME Mbah H=
osiah (674007438)  from huawei is informed Notice we have dysjonction at OC=
M equipments","Paul BIBOUM","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site on Gri=
d Ubai =3D54,6 V, The TX FME Mbah Hosiah (674007438)  from huawei is inform=
ed Notice we have dysjonction at OCM equipments","ludivine.ngamaleu@ihstowe=
rs.com","306","17-09-2024 20:15:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003097525","N=
koabang2","","17-09-2024 19:51:52","17-09-2024 19:44:46","17-09-2024 19:55:=
17","Active//No power issue U:53,1V site on Gen. TX FME Leonel Steve   (655=
184876) from Huawei is informed,","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 power issue U:53,1V site on Gen. TX FME Leonel Steve   (655184876) from Hu=
awei is informed,","ludivine.ngamaleu@ihstowers.com","427","17-09-2024 19:5=
1:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003097471","O=
lembe-Terminus","","17-09-2024 19:40:20","17-09-2024 19:32:03","17-09-2024 =
20:45:45","site went down because 02/03 rectifier disfunctionning //he rese=
t  the two rectifiers","Fabrice Pouakam","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","site went down because 02/03 rectifier disfuncti=
onning //he reset  the two rectifiers","ludivine.ngamaleu@ihstowers.com","4=
98","17-09-2024 19:40:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003097386","M=
vog-Manga","","17-09-2024 19:21:16","17-09-2024 19:06:12","17-09-2024 21:18=
:54","No power issue on site U=3D53,6v site on grid Lionel steeve of huawei=
 is informed notice that disjunction of CB in BTS Ocm","Albran Byorel","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue on site U=3D53,6v site on grid Lionel steeve of huaw=
ei is informed notice that disjunction of CB in BTS Ocm","ludivine.ngamaleu=
@ihstowers.com","905","17-09-2024 19:21:16","Sagemcom CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0003097350","Clu=
b France","","17-09-2024 19:11:18","17-09-2024 19:04:12","17-09-2024 19:50:=
13","Grid outage//Grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage//Grid return","dorothy.djantio@ihsto=
wers.com","427","17-09-2024 19:11:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003097272","O=
lembe","","17-09-2024 18:56:54","17-09-2024 18:47:59","17-09-2024 21:34:42"=
,"No power issie, site is on grid with Ubaie=3D55V, the fme tx Symphorien 6=
75295205 from Huawei is informed","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sie, site is on grid with Ubaie=3D55V, the fme tx Symphorien 675295205 from=
 Huawei is informed","ludivine.ngamaleu@ihstowers.com","536","17-09-2024 18=
:56:54","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003097141","Bit=
eng","","17-09-2024 18:33:15","17-09-2024 18:27:05","17-09-2024 18:31:02","=
Grid outage  site down due to poor backup before gen start  //Grid outage",=
"Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Battery Low","Grid outage  site down due to poor backup before gen st=
art  //Grid outage","dorothy.djantio@ihstowers.com","371","17-09-2024 18:33=
:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003097115","A=
ngongo","","17-09-2024 18:27:46","17-09-2024 18:19:41","17-09-2024 20:28:05=
","No power issue site went down because lionel tchatchoua/ 694693436 worki=
ng on site with level 0, the The Rm Martial // 690087047 of huawei is confi=
rm the action","Fanda Brice","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site went down beca=
use lionel tchatchoua/ 694693436 working on site with level 0, the The Rm M=
artial // 690087047 of huawei is confirm the action","ludivine.ngamaleu@ihs=
towers.com","486","17-09-2024 18:27:46","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003097113","Eko=
unou","","17-09-2024 18:27:33","17-09-2024 18:25:28","17-09-2024 18:31:28",=
"Grid outage  site down due to poor backup before gen start  //Gen started =
automatically","Albran Byorel","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage  site down due to poor backup b=
efore gen start  //Gen started automatically","dorothy.djantio@ihstowers.co=
m","126","17-09-2024 18:27:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003096657","C=
rf-Nsam","","17-09-2024 17:09:03","17-09-2024 16:37:57","17-09-2024 18:41:1=
4","No power issue on site U=3D54v site on grid Rm Alain of huawei is infor=
med","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v site on gri=
d Rm Alain of huawei is informed","ludivine.ngamaleu@ihstowers.com","1867",=
"17-09-2024 17:09:03","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003096503","Ess=
os Marche","","17-09-2024 16:44:19","17-09-2024 14:41:11","17-09-2024 23:35=
:17","No power issue on site U=3D54,2v site on grid Armand of huawei is inf=
ormed","Delor Telezing","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,2v site o=
n grid Armand of huawei is informed","dorothy.djantio@ihstowers.com","7389"=
,"17-09-2024 16:44:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003096417","B=
iteng","","17-09-2024 16:33:29","17-09-2024 13:09:22","17-09-2024 18:20:55"=
,"Active//No power issue U:54V site on Gen. TX FME Leonel Steve   (65518487=
6) from Huawei is informed,","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No powe=
r issue U:54V site on Gen. TX FME Leonel Steve   (655184876) from Huawei is=
 informed,","ludivine.ngamaleu@ihstowers.com","12249","17-09-2024 16:33:29"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0003096350","Ang=
uissa New","","17-09-2024 16:21:17","17-09-2024 16:18:12","17-09-2024 16:24=
:12","Grid outage, site went down because  Gen failed to start due to poor =
battery backup //Gen  started","MINKA NICOLAS","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 because  Gen failed to start due to poor battery backup //Gen  started","d=
orothy.djantio@ihstowers.com","186","17-09-2024 16:21:17","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0003096298","Tsi=
nga village","","17-09-2024 16:08:59","17-09-2024 16:07:53","17-09-2024 18:=
06:03","site went down insufficient the rectifier  on site// site stabilize=
d","Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","site went down insufficient the rectifier  on site// site stabilized"=
,"dorothy.djantio@ihstowers.com","67","17-09-2024 16:08:59","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_698","NOCINC0003095960","EBOM","","=
17-09-2024 15:15:59","","","site on alarm due to grid bad voltgae and gen f=
ailed to start//gen manually started","Hyemafo Gildas","Warning","Warning",=
"POWER","Warning - Site on Battery","site on alarm due to grid bad voltgae =
and gen failed to start//gen manually started","etienne.itondo@ihstowers.co=
m","72","17-09-2024 15:15:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_273","IHS_YND_214","NOCINC0003095901","N=
kolmesseng-II","","17-09-2024 15:07:59","17-09-2024 15:02:53","17-09-2024 1=
7:48:39","No power issue on site U=3D53v site on grid Armand of huawei is i=
nformed","Siligap Boris","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53v site on=
 grid Armand of huawei is informed","ludivine.ngamaleu@ihstowers.com","307"=
,"17-09-2024 15:07:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003095808","E=
lobi Mokolo","","17-09-2024 14:52:39","17-09-2024 14:45:35","17-09-2024 21:=
51:40","No power issue on site U=3D53,5v site on grid Brice stague of huawe=
i is informed","Mboua Thierry","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53,5v=
 site on grid Brice stague of huawei is informed","ludivine.ngamaleu@ihstow=
ers.com","425","17-09-2024 14:52:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003095792","B=
itoto","","17-09-2024 14:49:42","17-09-2024 14:45:38","18-09-2024 01:49:55"=
,"Active: No Power Issue site on grid, Ubaie:54,4V; Eric/696422966/ From ZT=
E  is working on site","Mba Lazare Herve","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No Power Issu=
e site on grid, Ubaie:54,4V; Eric/696422966/ From ZTE  is working on site",=
"ludivine.ngamaleu@ihstowers.com","245","17-09-2024 14:49:42","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003095768","ELOUMDEM=
 CARRIERE 2","","17-09-2024 14:41:00","17-09-2024 14:32:25","17-09-2024 16:=
15:13","Cascaded Incident from TTO2939671","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because 04/08 =
rectifier dysfonction // He reset the rectifiers","system","515","17-09-202=
4 14:41:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003095767","Eto koss=
 Yde","","17-09-2024 14:41:00","17-09-2024 14:32:25","17-09-2024 16:15:13",=
"Cascaded Incident from TTO2939671","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because 04/08 rectifi=
er dysfonction // He reset the rectifiers","system","515","17-09-2024 14:41=
:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0003095759","M=
om","","17-09-2024 14:39:48","17-09-2024 14:37:45","17-09-2024 15:08:16","G=
rid Fluctuation site went down because Gen failed to started due to Gen car=
d faulty //Grid stabilized","Fanda Brice","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","Grid Fluctuation site went down because Gen =
failed to started due to Gen card faulty //Grid stabilized","ludivine.ngama=
leu@ihstowers.com","124","17-09-2024 14:39:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003095741","S=
ous Prefecture","","17-09-2024 14:37:42","17-09-2024 14:31:38","17-09-2024 =
21:33:47","No power issue on site Ubaie:51.8V;  site on Gen   The Tx FME Li=
onel tchatchoua //694693436 from Huawei is informed. Notice that heavy rain=
 on the area","Fanda Brice","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie:51.8V;=
  site on Gen   The Tx FME Lionel tchatchoua //694693436 from Huawei is inf=
ormed. Notice that heavy rain on the area","ludivine.ngamaleu@ihstowers.com=
","365","17-09-2024 14:37:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003095719","A=
KONGO","","17-09-2024 14:34:37","17-09-2024 14:09:33","17-09-2024 16:09:56"=
,"No power issue on site U=3D50v site on gen Rodrigue 655102999 of huawei i=
s informed notice that havy rain in area(repetitive issue)","Fanda Brice","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue on site U=3D50v site on gen Rodrigue 655102999 of=
 huawei is informed notice that havy rain in area(repetitive issue)","ludiv=
ine.ngamaleu@ihstowers.com","1506","17-09-2024 14:34:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003095699","S=
calom-IHS","","17-09-2024 14:31:36","17-09-2024 14:20:24","17-09-2024 17:17=
:22","Active// No power Issue Site on Grid Ubai =3D54,2 V, The TX FME Mbah =
Hosiah (674007438) is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site=
 on Grid Ubai =3D54,2 V, The TX FME Mbah Hosiah (674007438) is informed","l=
udivine.ngamaleu@ihstowers.com","673","17-09-2024 14:31:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003095694","K=
oweit City","","17-09-2024 14:30:19","17-09-2024 14:09:17","17-09-2024 17:3=
6:34","No power issue U:56,2V site on Grid. TX FME Leonel Steve   (65518487=
6) from Huawei is informed","Albran Byorel","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U:56=
,2V site on Grid. TX FME Leonel Steve   (655184876) from Huawei is informed=
","ludivine.ngamaleu@ihstowers.com","1263","17-09-2024 14:30:19","Sagemcom =
CMR"
"Closed Complete","Site Down","T1852","IHS_YND_335","NOCINC0003095683","Ang=
ongo","","17-09-2024 14:28:33","17-09-2024 14:06:23","17-09-2024 18:00:53",=
"Active// No power issue on site ,site on Grid with Ubaie=3D 52,9V The Rm M=
artial // 690087047 of huawei is informed Notice that heavy rain on the are=
a","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active// No power issue on site ,site on Grid =
with Ubaie=3D 52,9V The Rm Martial // 690087047 of huawei is informed Notic=
e that heavy rain on the area","dorothy.djantio@ihstowers.com","1331","17-0=
9-2024 14:28:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003095677","M=
ontee-Des-Soeurs","","17-09-2024 14:27:11","17-09-2024 14:08:08","17-09-202=
4 18:13:33","Active// No power Issue Site on Grid Ubai =3D54,6 V, The TX FM=
E Mbah Hosiah (674007438)  from huawei is informed, rep=E9titif isue","Hyem=
afo Gildas","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active// No power Issue Site on Grid Ubai =3D54,6 V=
, The TX FME Mbah Hosiah (674007438)  from huawei is informed, rep=E9titif =
isue","ludivine.ngamaleu@ihstowers.com","1144","17-09-2024 14:27:11","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003095488","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","17-09-2024 14:00:26","17-09-2024 13:=
55:08","17-09-2024 16:15:13","site went down because 04/08 rectifier dysfon=
ction // He reset the rectifiers","Fanda Brice","Equipment Repair","Passive=
","Rectifier","Rectifier Module","site went down because 04/08 rectifier dy=
sfonction // He reset the rectifiers","alexandre.kamal@ihstowers.com","319"=
,"17-09-2024 14:00:26","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003095473","Ess=
os Marche","","17-09-2024 13:56:34","17-09-2024 13:18:40","17-09-2024 14:35=
:30","Grid outage, site went down before gen start due to poor battery back=
up // Gen started","Delor Telezing","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery backup // Gen started","kamga.virgile@ihstowers.=
com","2275","17-09-2024 13:56:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003095467","MBALNGON=
G LYCEE","","17-09-2024 13:55:10","17-09-2024 13:18:47","17-09-2024 14:20:0=
9","Cascaded Incident from TTO2939287","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage.  Gen started and sto=
pped because Gen  overload(20 KVA,280 A and poor battery backup//he reduce =
load on site and started Gen manually","system","2183","17-09-2024 13:55:10=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003095466","ELOUMDEM=
 CARRIERE","","17-09-2024 13:55:10","17-09-2024 13:18:47","17-09-2024 14:20=
:09","Cascaded Incident from TTO2939287","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage.  Gen started and s=
topped because Gen  overload(20 KVA,280 A and poor battery backup//he reduc=
e load on site and started Gen manually","system","2183","17-09-2024 13:55:=
10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003095468","Afanoya"=
,"","17-09-2024 13:55:10","17-09-2024 13:18:47","17-09-2024 14:20:09","Casc=
aded Incident from TTO2939287","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage.  Gen started and stopped =
because Gen  overload(20 KVA,280 A and poor battery backup//he reduce load =
on site and started Gen manually","system","2183","17-09-2024 13:55:10","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003095438","Com=
plex Beac II","","17-09-2024 13:51:05","17-09-2024 13:14:51","17-09-2024 13=
:49:01","Grid Outage Gen Failed to Start due To Gen Card Faulty//He Manuall=
y Started The Gen","Albran Byorel","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Grid Outage Gen Failed to Start due To Gen Card Fau=
lty//He Manually Started The Gen","kamga.virgile@ihstowers.com","2175","17-=
09-2024 13:51:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003095421","F=
ebe Village","","17-09-2024 13:48:21","17-09-2024 13:47:50","17-09-2024 14:=
54:22","Grid outage site went down because Gen failed to star due to Gen ca=
rd faulty and poor backup//Gen manually  started ","Mboua Thierry","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site we=
nt down because Gen failed to star due to Gen card faulty and poor backup//=
Gen manually  started ","alexandre.kamal@ihstowers.com","32","17-09-2024 13=
:48:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003095412","N=
sam Sofavinc T0","","17-09-2024 13:46:12","17-09-2024 13:41:32","17-09-2024=
 14:36:00","Grid outage site went down because Gen overload (9Kva, 185A)//h=
e reduce load on site and started Gen manually","MINKA NICOLAS","Equipment =
Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down =
because Gen overload (9Kva, 185A)//he reduce load on site and started Gen m=
anually","alexandre.kamal@ihstowers.com","281","17-09-2024 13:46:12","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0003095402","S=
apeur Mimboman","","17-09-2024 13:43:47","17-09-2024 13:40:39","17-09-2024 =
14:45:44","grid outage,gen failed to start due to card Ge faulty/gen manual=
ly started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","grid outage,gen failed to start due to card Ge faulty/g=
en manually started","alexandre.kamal@ihstowers.com","189","17-09-2024 13:4=
3:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0003095396","K=
ondengui","","17-09-2024 13:42:27","17-09-2024 13:34:18","17-09-2024 14:40:=
12","grid outage,gen stopped with alarm high temp//he added water in radiat=
or","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High En=
gine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high t=
emp//he added water in radiator","alexandre.kamal@ihstowers.com","490","17-=
09-2024 13:42:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003095302","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","17-09-2024 13:25:54","17-09-=
2024 13:18:47","17-09-2024 14:20:09","Grid outage.  Gen started and stopped=
 because Gen  overload(20 KVA,280 A and poor battery backup//he reduce load=
 on site and started Gen manually","Hyemafo Gildas","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Overload","Grid outage.  Gen started and stopped b=
ecause Gen  overload(20 KVA,280 A and poor battery backup//he reduce load o=
n site and started Gen manually","alexandre.kamal@ihstowers.com","428","17-=
09-2024 13:25:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0003095300","MONTEE N=
KONDENGUI","","17-09-2024 13:25:30","17-09-2024 13:16:14","18-09-2024 01:27=
:32","Cascaded Incident from TTO2939137","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage  //MDG of 20 kva =
has deployed","system","556","17-09-2024 13:25:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0003095295","M=
obil-Kondengui","IHS_YND_682","17-09-2024 13:24:20","17-09-2024 13:16:14","=
18-09-2024 01:27:32","Grid outage  //MDG of 20 kva has deployed","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage  /=
/MDG of 20 kva has deployed","alexandre.kamal@ihstowers.com","487","17-09-2=
024 13:24:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0003095267","Crf Corn=
ier","","17-09-2024 13:20:35","17-09-2024 13:15:18","17-09-2024 14:37:22","=
Cascaded Incident from TTO2939065","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage,no space to deploy a mo=
bil gen//grid return","system","317","17-09-2024 13:20:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003095227","M=
adison","IHS_YND_566","17-09-2024 13:18:51","17-09-2024 13:15:18","17-09-20=
24 14:37:22","grid outage,no space to deploy a mobil gen//grid return","MFO=
UAGUEGUE MATHIEU","Grid Supply","Passive","Grid","National Grid - Grid Outa=
ge Issue","grid outage,no space to deploy a mobil gen//grid return","alexan=
dre.kamal@ihstowers.com","214","17-09-2024 13:18:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0003095216","O=
dza II","","17-09-2024 13:16:01","17-09-2024 13:10:57","17-09-2024 14:03:31=
","grid outage,gen start and stopped with alarm low oil pressure//he reset =
the card and started the gen","Albran Byorel","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Low Oil Pressure","grid outage,gen start and stopped wit=
h alarm low oil pressure//he reset the card and started the gen","alexandre=
.kamal@ihstowers.com","306","17-09-2024 13:16:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003095169","K=
oweit City","","17-09-2024 13:08:46","17-09-2024 12:59:41","17-09-2024 13:0=
0:41","Active//No power issue site on grid with U=3D56.3V // Leonel Steve  =
(655184876) from Huawei is informed and  Notice that heavy rain on the area=
","Albran Byorel","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","Active//No power issue site on grid with U=3D=
56.3V // Leonel Steve  (655184876) from Huawei is informed and  Notice that=
 heavy rain on the area","alexandre.kamal@ihstowers.com","546","17-09-2024 =
13:08:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003095078","A=
kak-Nkozoa-MTN-IHS","","17-09-2024 12:54:44","17-09-2024 12:49:29","17-09-2=
024 13:06:13","site went down because CB 125A disjuncted in PWC//he did a b=
ridge with another 2*63A","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Circuit Breaker Issue","site went down becau=
se CB 125A disjuncted in PWC//he did a bridge with another 2*63A","alexandr=
e.kamal@ihstowers.com","316","17-09-2024 12:54:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0003094958","B=
arriere IHS","","17-09-2024 12:30:29","17-09-2024 12:24:25","17-09-2024 13:=
12:54","Grid outage, site went down because gen ran till fuel shortage // r=
efueling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Ou=
tage","Grid outage, site went down because gen ran till fuel shortage // re=
fueling done","alexandre.kamal@ihstowers.com","366","17-09-2024 12:30:29","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_721","NOCINC0003094650","VOIRIE M=
UNICIPALE YAOUNDE","","17-09-2024 11:48:40","17-09-2024 11:40:16","17-09-20=
24 12:29:40","Cascaded Incident from TTO2938412","Paul BIBOUM","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Grid Outage No Space To=
 deploy a MDG//Grid Restored","system","504","17-09-2024 11:48:40","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0003094644","E=
NAM","IHS_YND_721","17-09-2024 11:47:32","17-09-2024 11:40:16","17-09-2024 =
12:30:03","Grid Outage No Space To deploy a MDG//Grid Restored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No =
Space To deploy a MDG//Grid Restored","alexandre.kamal@ihstowers.com","437"=
,"17-09-2024 11:47:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0003094539","Messassi=
 2","","17-09-2024 11:30:30","17-09-2024 11:06:59","17-09-2024 12:20:33","C=
ascaded Incident from TTO2938163","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because gen start a=
nd stopped with alarm 'under voltage' and CB grid dysjoncted due to Lightni=
ng // He reset gen card and manually start the gen","system","1411","17-09-=
2024 11:30:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0003094538","Olembe-T=
erminus","","17-09-2024 11:30:30","17-09-2024 11:06:59","17-09-2024 12:20:3=
3","Cascaded Incident from TTO2938163","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because gen st=
art and stopped with alarm 'under voltage' and CB grid dysjoncted due to Li=
ghtning // He reset gen card and manually start the gen","system","1411","1=
7-09-2024 11:30:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0003094486","NKOLMEKO=
NG YDE","","17-09-2024 11:23:40","17-09-2024 11:06:59","17-09-2024 12:20:33=
","Cascaded Incident from TTO2938163","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down because gen sta=
rt and stopped with alarm 'under voltage' and CB grid dysjoncted due to Lig=
htning // He reset gen card and manually start the gen","system","1001","17=
-09-2024 11:23:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0003094439","Ekombiti=
e","","17-09-2024 11:18:40","17-09-2024 11:06:59","17-09-2024 12:20:33","Ca=
scaded Incident from TTO2938163","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because gen start an=
d stopped with alarm 'under voltage' and CB grid dysjoncted due to Lightnin=
g // He reset gen card and manually start the gen","system","701","17-09-20=
24 11:18:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0003094442","Nkolondo=
m","","17-09-2024 11:18:40","17-09-2024 11:06:59","17-09-2024 12:20:33","Ca=
scaded Incident from TTO2938163","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because gen start an=
d stopped with alarm 'under voltage' and CB grid dysjoncted due to Lightnin=
g // He reset gen card and manually start the gen","system","701","17-09-20=
24 11:18:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0003094441","Nyom OCM=
","","17-09-2024 11:18:40","17-09-2024 11:06:59","17-09-2024 12:20:33","Cas=
caded Incident from TTO2938163","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because gen start and=
 stopped with alarm 'under voltage' and CB grid dysjoncted due to Lightning=
 // He reset gen card and manually start the gen","system","701","17-09-202=
4 11:18:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0003094440","Messassi=
","","17-09-2024 11:18:40","17-09-2024 11:06:59","17-09-2024 12:20:33","Cas=
caded Incident from TTO2938163","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because gen start and=
 stopped with alarm 'under voltage' and CB grid dysjoncted due to Lightning=
 // He reset gen card and manually start the gen","system","701","17-09-202=
4 11:18:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003094428","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_303, IH=
S_YND_280, IHS_YND_304","17-09-2024 11:16:42","17-09-2024 11:06:59","17-09-=
2024 12:20:33","site went down because gen start and stopped with alarm 'un=
der voltage' and CB grid dysjoncted due to Lightning // He reset gen card a=
nd manually start the gen","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","site went down because gen start and stop=
ped with alarm 'under voltage' and CB grid dysjoncted due to Lightning // H=
e reset gen card and manually start the gen","alexandre.kamal@ihstowers.com=
","584","17-09-2024 11:16:42","Sagemcom CMR"
"Closed Complete","Site Down","T0755","IHS_YND_408","NOCINC0003094229","Evo=
doula MTN","","17-09-2024 11:01:43","17-09-2024 10:47:26","17-09-2024 11:25=
:15","Grid outage, site went down because Gen started and stopped with alar=
m ""under voltage"" (alarm unprouven)//He reset Gen card and started Gen","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - O=
ver Voltage","Grid outage, site went down because Gen started and stopped w=
ith alarm ""under voltage"" (alarm unprouven)//He reset Gen card and starte=
d Gen","kamga.virgile@ihstowers.com","858","17-09-2024 11:01:43","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003093685","M=
elen Ba'aba","","17-09-2024 09:32:04","17-09-2024 09:24:00","17-09-2024 09:=
40:00","Grid fluctuation, site went down because gen start and stopped due =
to grid bad voltage // He bypass grid and manually start the gen","Siligap =
Boris","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, site went down because gen start and stopped due to=
 grid bad voltage // He bypass grid and manually start the gen","alexandre.=
kamal@ihstowers.com","485","17-09-2024 09:32:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003093278","A=
KONGO","","17-09-2024 08:32:06","17-09-2024 08:23:01","17-09-2024 08:30:01"=
,"Active:  No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rod=
rigue (655102999)from Huawei is informed. Repetitive issue","Fanda Brice","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active:  No power issue on site Ubaie=3D52,5V site on Gen. The T=
x FME Rodrigue (655102999)from Huawei is informed. Repetitive issue","alexa=
ndre.kamal@ihstowers.com","546","17-09-2024 08:32:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_406","NOCINC0003093096","Monatele=
","","17-09-2024 07:46:50","17-09-2024 07:08:21","17-09-2024 07:52:21","Cas=
caded Incident from TTO2936665","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage Gen Failed to start due Ge=
n Card Faulty//Gen Manually Started","system","2309","17-09-2024 07:46:50",=
"Sagemcom CMR"
"Cancelled","Warning","T0715","IHS_YND_406","NOCINC0003093069","Monatele","=
","17-09-2024 07:41:40","","","","Parker Tchoup","","","","","","kamga.virg=
ile@ihstowers.com","1999","17-09-2024 07:41:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0003093001","E=
mana lycee 2","","17-09-2024 07:24:03","17-09-2024 07:16:56","17-09-2024 08=
:20:56","site was on gen due to grid outage, site went down because Gen sto=
pped with alarm high temp // he added water and manually start the gen","Fa=
brice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine =
Temp - Coolant Level Issue","site was on gen due to grid outage, site went =
down because Gen stopped with alarm high temp // he added water and manuall=
y start the gen","alexandre.kamal@ihstowers.com","428","17-09-2024 07:24:03=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_869","IHS_YND_407","NOCINC0003092983","M=
onatele MTN","IHS_YND_406","17-09-2024 07:19:28","17-09-2024 07:03:21","17-=
09-2024 07:53:21","Grid Outage Gen Failed to start with alarms memory corru=
pt //he Reset the Gen Card and Gen Manually Started (Deep investigation ong=
oing)","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid Outage Gen Failed to start with alarms memory corrupt //he=
 Reset the Gen Card and Gen Manually Started (Deep investigation ongoing)",=
"alexandre.kamal@ihstowers.com","968","17-09-2024 07:19:28","Sagemcom CMR"
"Cancelled","Warning","T1871","IHS_YND_292","NOCINC0003092416","Bitoto","",=
"17-09-2024 04:37:15","","","","Mba Lazare Herve","","","","","","olivier.k=
wedi@ihstowers.com","610","17-09-2024 04:37:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_011","IHS_YND_196","NOCINC0003092313","P=
DC","","17-09-2024 03:59:55","17-09-2024 03:51:46","17-09-2024 04:30:28","A=
ctive//No power issue site on grid with U=3D54,3 V . The Tx FME Eloundou Be=
rtrand(693212405) from Huawei is informed ","Mboua Thierry","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue site on grid with U=3D54,3 V . The Tx FME Eloundou Bert=
rand(693212405) from Huawei is informed ","emmanuel.ghani@ihstowers.com","4=
90","17-09-2024 03:59:55","Sagemcom CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0003092252","Nko=
ulou Carriere carrefourt","","17-09-2024 03:33:32","17-09-2024 03:27:24","1=
7-09-2024 08:45:24","Grid outage, site went down because Gen stopped due to=
 ""high temp"" alarm because  radiator pierced// he seal the Radiator, Add =
Water and Manually Started the Gen","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - High Engine Temp - Radiator Leakage","Grid outa=
ge, site went down because Gen stopped due to ""high temp"" alarm because  =
radiator pierced// he seal the Radiator, Add Water and Manually Started the=
 Gen","olivier.kwedi@ihstowers.com","369","17-09-2024 03:33:32","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0003092168","M=
ambine","","17-09-2024 03:09:47","17-09-2024 03:03:38","17-09-2024 03:25:03=
","Site went Down because Gen failed to start due to Hybrid system dysfonct=
ion// He reset the Gen card  and Gen manually started","Fanda Brice","Equip=
ment Repair","Passive","Hybrid","Hybrid Module","Site went Down because Gen=
 failed to start due to Hybrid system dysfonction// He reset the Gen card  =
and Gen manually started","emmanuel.ghani@ihstowers.com","370","17-09-2024 =
03:09:47","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0003092135","Nko=
lbong","","17-09-2024 02:52:53","17-09-2024 02:44:44","17-09-2024 04:24:59"=
,"Grid outage,Gen started and stopped with alarm high temp///he added water=
 in radiator","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACD=
G - High Engine Temp - Coolant Level Issue","Grid outage,Gen started and st=
opped with alarm high temp///he added water in radiator","olivier.kwedi@ihs=
towers.com","740","17-09-2024 02:52:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003091952","M=
fou EPC","","17-09-2024 01:38:59","17-09-2024 01:36:53","17-09-2024 04:53:2=
6","Grid outage, site went down because gen failed to start due to relay st=
art of gen faulty//  Gen manually started(relay start to be replaced)","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Relay Faulty=
","Grid outage, site went down because gen failed to start due to relay sta=
rt of gen faulty//  Gen manually started(relay start to be replaced)","emma=
nuel.ghani@ihstowers.com","127","17-09-2024 01:38:59","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0003091719","Ema=
na","","17-09-2024 01:27:05","17-09-2024 01:22:57","17-09-2024 07:44:57","A=
ccess issue during the Night due to Landlord, Grid outage, site went down b=
ecause gen ran untill fuel shortage // refueling done","Fabrice Pouakam","A=
ccess Denial","Lease Or Legal","Landlord Related Issues","Access Issue - La=
nd Lord","Access issue during the Night due to Landlord, Grid outage, site =
went down because gen ran untill fuel shortage // refueling done","olivier.=
kwedi@ihstowers.com","249","17-09-2024 01:27:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003091674","E=
kombitie","","17-09-2024 01:19:06","17-09-2024 01:16:42","17-09-2024 03:21:=
32","Grid outage,site went down because gen ran untill fuel shortage // ref=
ueling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage,site went down because gen ran untill fuel shortage // re=
fueling done","emmanuel.ghani@ihstowers.com","145","17-09-2024 01:19:06","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0003091621","M=
om","","17-09-2024 00:55:12","17-09-2024 00:53:43","17-09-2024 01:20:46","G=
rid Outage, Site went down because Gen failed to start due Solenoid valve f=
aulty// He started Gen manualy","Fanda Brice","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Solenoid Coil","Grid Outage, Site went down because Gen =
failed to start due Solenoid valve faulty// He started Gen manualy","emmanu=
el.ghani@ihstowers.com","90","17-09-2024 00:55:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003091587","A=
wae Ewonkan","","17-09-2024 00:43:37","16-09-2024 21:11:05","16-09-2024 21:=
16:50","site went down due to insufficient of rectifier(site on 5 rectifier=
s )//site satbilized(need to added one rectifier)","Albran Byorel","Equipme=
nt Repair","Passive","Rectifier","Rectifier Module","site went down due to =
insufficient of rectifier(site on 5 rectifiers )//site satbilized(need to a=
dded one rectifier)","emmanuel.ghani@ihstowers.com","12753","17-09-2024 00:=
43:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003091478","M=
ontee-Des-Soeurs","","16-09-2024 23:58:06","16-09-2024 23:43:00","17-09-202=
4 00:15:11","Active// No power Issue Site on Grid Ubai =3D54,2 V, The TX FM=
E Mbah Hosiah (674007438) is informed","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/=
/ No power Issue Site on Grid Ubai =3D54,2 V, The TX FME Mbah Hosiah (67400=
7438) is informed","emmanuel.ghani@ihstowers.com","907","16-09-2024 23:58:0=
6","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_409","NOCINC0003091127","Evodoula=
 OCM","","16-09-2024 22:34:30","16-09-2024 22:28:51","16-09-2024 22:30:44",=
"Cascaded Incident from TTO2934495","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","Active// no power issue U=
=3D53.8V site on GenTX FME Gregoire   (652070658) from Huawei is informed",=
"system","339","16-09-2024 22:34:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0003091125","Talla Mo=
natele","","16-09-2024 22:34:30","16-09-2024 22:28:51","16-09-2024 22:30:44=
","Cascaded Incident from TTO2934495","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","Active// no power issue U=3D53.8V s=
ite on GenTX FME Gregoire   (652070658) from Huawei is informed","system","=
339","16-09-2024 22:34:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0003091126","Monatele=
 MTN","","16-09-2024 22:34:30","16-09-2024 22:28:51","16-09-2024 22:30:44",=
"Cascaded Incident from TTO2934495","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active// no power issue U=3D53.8V sit=
e on GenTX FME Gregoire   (652070658) from Huawei is informed","system","33=
9","16-09-2024 22:34:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_073","IHS_YND_406","NOCINC0003091116","M=
onatele","IHS_YND_387, IHS_YND_407, IHS_YND_409","16-09-2024 22:32:57","16-=
09-2024 22:28:51","16-09-2024 23:00:44","Active// no power issue U=3D53.8V =
site on GenTX FME Gregoire   (652070658) from Huawei is informed","Parker T=
choup","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active// no power issue U=3D53.8V site on GenTX FME Greg=
oire   (652070658) from Huawei is informed","emmanuel.ghani@ihstowers.com",=
"247","16-09-2024 22:32:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_674","NOCINC0003091071","Mfou EPC=
","","16-09-2024 22:27:15","16-09-2024 16:42:53","16-09-2024 16:59:24","sit=
e went down because gen failed to start due to grid bad voltage // Gen manu=
ally started ","Mba Lazare Herve","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","site went down because gen failed to start=
 due to grid bad voltage // Gen manually started ","ange.kongo@ihstowers.co=
m","20663","16-09-2024 22:27:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003091048","E=
mana","","16-09-2024 22:24:18","16-09-2024 22:15:13","16-09-2024 23:24:52",=
"Grid Outage// MDG of 20kva has deployed","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid Outage// MDG of 20kva has deploy=
ed","emmanuel.ghani@ihstowers.com","546","16-09-2024 22:24:18","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0003090962","Nkoabang=
2","","16-09-2024 22:08:28","16-09-2024 21:47:17","17-09-2024 00:39:23","Ac=
tive //No power issue, site is on Gen with U=3D53,2 V ,  The TX FME Lionel =
adjep//655184876//   Huawei is informed,Notice that we have disjunction at =
BTS OCM ","Mba Lazare Herve","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active //No power issue, site is o=
n Gen with U=3D53,2 V ,  The TX FME Lionel adjep//655184876//   Huawei is i=
nformed,Notice that we have disjunction at BTS OCM ","ange.kongo@ihstowers.=
com","1272","16-09-2024 22:08:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003090670","M=
vog-Manga","","16-09-2024 21:29:26","16-09-2024 21:24:17","16-09-2024 22:21=
:14","Site on Grid ,site went down because CB OCM (100A) disjunted  causing=
 by cable power burned in Dcbox //He reamed CB","Albran Byorel","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","=
Site on Grid ,site went down because CB OCM (100A) disjunted  causing by ca=
ble power burned in Dcbox //He reamed CB","ange.kongo@ihstowers.com","310",=
"16-09-2024 21:29:26","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0003090197","Aka=
k-Nkozoa-MTN-IHS","","16-09-2024 20:18:48","16-09-2024 20:03:22","16-09-202=
4 20:18:22","grid outage,gen failed to start due to grid bad voltage//grid =
bypassed and started the gen","Fabrice Pouakam","Grid Supply","Passive","Gr=
id","National Grid - Phase Controller Faulty","grid outage,gen failed to st=
art due to grid bad voltage//grid bypassed and started the gen","denis.mbal=
la@ihstowers.com","928","16-09-2024 20:18:48","Sagemcom CMR"
"Closed Complete","Site Down","T1613","IHS_YND_301","NOCINC0003089733","Tsi=
nga village","","16-09-2024 19:08:20","16-09-2024 19:03:53","16-09-2024 20:=
53:47","site went down due to insufficient of rectifier(2/3)//site satbiliz=
ed(need to added one rectifier)","Delor Telezing","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","site went down due to insufficient of r=
ectifier(2/3)//site satbilized(need to added one rectifier)","denis.mballa@=
ihstowers.com","268","16-09-2024 19:08:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0003089603","M=
essassi 2","","16-09-2024 18:40:23","16-09-2024 18:19:14","16-09-2024 19:46=
:17","grid outage,gen failed start and stopped due to alarm overcurrent//He=
 reset the card and started the gen","Fabrice Pouakam","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","grid outage,gen failed start an=
d stopped due to alarm overcurrent//He reset the card and started the gen",=
"ange.kongo@ihstowers.com","1270","16-09-2024 18:40:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003089294","Yoko MTN=
","","16-09-2024 17:37:01","16-09-2024 17:32:34","16-09-2024 18:11:37","Cas=
caded Incident from TTO2932358","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because gen stopped wit=
h alarm high temp//he open all the door and restarted it","system","267","1=
6-09-2024 17:37:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003089293","Ngoum","=
","16-09-2024 17:37:01","16-09-2024 17:32:34","16-09-2024 18:11:37","Cascad=
ed Incident from TTO2932358","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because gen stopped with a=
larm high temp//he open all the door and restarted it","system","267","16-0=
9-2024 17:37:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003089291","MBIMBIM"=
,"","16-09-2024 17:37:00","16-09-2024 17:32:34","16-09-2024 18:11:37","Casc=
aded Incident from TTO2932358","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site went down because gen stopped with=
 alarm high temp//he open all the door and restarted it","system","266","16=
-09-2024 17:37:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003089292","Matsari"=
,"","16-09-2024 17:37:00","16-09-2024 17:32:34","16-09-2024 18:11:37","Casc=
aded Incident from TTO2932358","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","site went down because gen stopped with=
 alarm high temp//he open all the door and restarted it","system","266","16=
-09-2024 17:37:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_300","IHS_YND_454","NOCINC0003089246","N=
gouetou","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_473","16-09-2024 1=
7:31:39","16-09-2024 17:27:34","16-09-2024 18:11:37","site went down becaus=
e gen stopped with alarm high temp//he open all the door and restarted it",=
"Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine=
 Temp - Coolant Level Issue","site went down because gen stopped with alarm=
 high temp//he open all the door and restarted it","ange.kongo@ihstowers.co=
m","246","16-09-2024 17:31:39","Sagemcom CMR"
"Closed Complete","Site Down","T3230","IHS_YND_745","NOCINC0003089182","Oko=
lo Kilombo","","16-09-2024 17:21:29","16-09-2024 17:12:12","16-09-2024 18:2=
5:34","site went down because gen stopped with alarm high temp//he added wa=
ter in radiator","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen",=
"ACDG - High Engine Temp - Coolant Level Issue","site went down because gen=
 stopped with alarm high temp//he added water in radiator","denis.mballa@ih=
stowers.com","558","16-09-2024 17:21:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003088967","A=
KONGO","","16-09-2024 17:00:02","16-09-2024 16:51:55","16-09-2024 19:17:18"=
,"No power issue on site U=3D50v site on gen Rodrigue of huawei is informed=
","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","No power issue on site U=3D50v site on gen Rodr=
igue of huawei is informed","ange.kongo@ihstowers.com","489","16-09-2024 17=
:00:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003088893","T=
singa","","16-09-2024 16:50:56","16-09-2024 16:45:51","16-09-2024 17:07:24"=
,"Grid outage, site went down because  Gen failed to start due to poor batt=
ery backup // Gen started","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bec=
ause  Gen failed to start due to poor battery backup // Gen started","ange.=
kongo@ihstowers.com","306","16-09-2024 16:50:56","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003088825","Elo=
umdem stade","","16-09-2024 16:39:11","16-09-2024 16:37:01","16-09-2024 18:=
07:17","grid outage,gen failed to start due to grid bad voltage//he did a b=
rige on good phase","Fanda Brice","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","grid outage,gen failed to start due to gri=
d bad voltage//he did a brige on good phase","denis.mballa@ihstowers.com","=
131","16-09-2024 16:39:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003088697","A=
kak-Nkozoa-MTN-IHS","","16-09-2024 16:11:14","16-09-2024 16:09:10","16-09-2=
024 16:36:10","grid outage,gen failed to start due to grid bad voltgae,no r=
cp//he bypassed grid and started the gen","Fabrice Pouakam","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","grid outage,gen =
failed to start due to grid bad voltgae,no rcp//he bypassed grid and starte=
d the gen","ange.kongo@ihstowers.com","126","16-09-2024 16:11:14","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003088618","Y=
de-M-Central","","16-09-2024 16:01:31","16-09-2024 16:00:26","16-09-2024 16=
:16:57","grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,n=
o space to deploy a mobil gen//grid return","ange.kongo@ihstowers.com","66"=
,"16-09-2024 16:01:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003088462","Lobo OCM=
","","16-09-2024 15:31:20","16-09-2024 15:22:06","16-09-2024 15:28:06","Cas=
caded Incident from TTO2931371","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // gen start automatically","s=
ystem","554","16-09-2024 15:31:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_332","NOCINC0003088451","NKOMEKUI=
 OCM","IHS_YND_341","16-09-2024 15:30:11","16-09-2024 15:22:06","16-09-2024=
 15:28:06","Grid outage, site went down before gen start due to poor batter=
y backup // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outag=
e, site went down before gen start due to poor battery backup // gen start =
automatically","ange.kongo@ihstowers.com","486","16-09-2024 15:30:11","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0003088403","M=
essassi 2","","16-09-2024 15:28:17","16-09-2024 15:25:10","16-09-2024 16:19=
:13","grid outage,gen failed start and stopped due to alarm overcurrent//He=
 reset the card and started the gen","Fabrice Pouakam","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","grid outage,gen failed start an=
d stopped due to alarm overcurrent//He reset the card and started the gen",=
"ange.kongo@ihstowers.com","188","16-09-2024 15:28:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003088373","M=
fou EPC","","16-09-2024 15:26:41","16-09-2024 15:20:24","16-09-2024 15:36:0=
7","grid outage,gen failed to start due to grid bad voltage//he bypassed gr=
id and started the gen","Mba Lazare Herve","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","grid outage,gen failed to start d=
ue to grid bad voltage//he bypassed grid and started the gen","ange.kongo@i=
hstowers.com","378","16-09-2024 15:26:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0003087793","Nkolanga=
a","","16-09-2024 14:35:51","16-09-2024 14:27:33","16-09-2024 15:57:31","Ca=
scaded Incident from TTO2930614","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen stopped with alarm=
 high temp//he added water in radiator","system","498","16-09-2024 14:35:51=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0003087792","Nkoulou =
Carriere carrefourt","","16-09-2024 14:35:51","16-09-2024 14:27:33","16-09-=
2024 15:57:31","Cascaded Incident from TTO2930614","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","grid outage,gen =
stopped with alarm high temp//he added water in radiator","system","498","1=
6-09-2024 14:35:51","Sagemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0003087785","Aba=
ng","IHS_YND_794, IHS_YND_289","16-09-2024 14:33:51","16-09-2024 14:24:59",=
"16-09-2024 15:57:31","grid outage,gen stopped with alarm high temp//he add=
ed water in radiator","Mba Lazare Herve","Equipment Repair","Passive","ACDG=
 Gen","ACDG - High Engine Temp - Coolant Level Issue","grid outage,gen stop=
ped with alarm high temp//he added water in radiator","denis.mballa@ihstowe=
rs.com","614","16-09-2024 14:33:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003087781","A=
wae Ewonkan","","16-09-2024 14:33:06","16-09-2024 14:26:00","16-09-2024 15:=
16:27","grid outage,gen failed to start due to card Ge disfunctionning//he =
reset the card and started it","Albran Byorel","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start due to =
card Ge disfunctionning//he reset the card and started it","ange.kongo@ihst=
owers.com","427","16-09-2024 14:33:06","Sagemcom CMR"
"Closed Complete","Warning","CTR_526","IHS_YND_696","NOCINC0003087748","Bar=
riere IHS","","16-09-2024 14:30:30","","","site on alarm due to grid outage=
//gen started and alarm cleared","Hyemafo Gildas","Warning","Warning","POWE=
R","Warning - Site on Battery","site on alarm due to grid outage//gen start=
ed and alarm cleared","adonis.defokoua@ihstowers.com","571","16-09-2024 14:=
30:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0003087429","Biteng",=
"","16-09-2024 13:46:58","16-09-2024 13:14:51","16-09-2024 13:28:16","Site =
went due to work SS IHS BLAISE /657108509/Sagemcom is Working on site  // e=
nd of work","Mba Lazare Herve","Equipment Replacement","Passive","Planned A=
ctivity","Planned Activity - Passive","Site went due to work SS IHS BLAISE =
/657108509/Sagemcom is Working on site  // end of work","etienne.itondo@ihs=
towers.com","1928","16-09-2024 13:46:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_248","NOCINC0003087279","Biteng",=
"","16-09-2024 13:26:48","16-09-2024 11:29:00","16-09-2024 13:13:26","Activ=
e//No power issue U:54V site on Gen. TX FME Leonel Steve   (655184876) from=
 Huawei is informed, ","Mba Lazare Herve","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issu=
e U:54V site on Gen. TX FME Leonel Steve   (655184876) from Huawei is infor=
med, ","etienne.itondo@ihstowers.com","7069","16-09-2024 13:26:48","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003087046","Y=
de-M-Central","","16-09-2024 12:55:13","16-09-2024 12:50:10","16-09-2024 13=
:39:41","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Sp=
ace to deploy a MDG//Grid Restored","ludivine.ngamaleu@ihstowers.com","304"=
,"16-09-2024 12:55:13","Sagemcom CMR"
"Closed Complete","Warning","T1551","IHS_YND_316","NOCINC0003085678","Akak-=
Nkozoa-MTN-IHS","","16-09-2024 11:27:57","","","Grid fluctuation,site went =
on Battery because Gen failed to  Grid Bad Voltage//He bypassed Grid and st=
arted Gen","Fabrice Pouakam","Warning","Warning","POWER","Warning - Site on=
 Battery","Grid fluctuation,site went on Battery because Gen failed to  Gri=
d Bad Voltage//He bypassed Grid and started Gen","etienne.itondo@ihstowers.=
com","2592","16-09-2024 11:27:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003085630","Biteng-M=
aetur","","16-09-2024 11:22:21","16-09-2024 11:08:33","16-09-2024 11:28:11"=
,"Cascaded Incident from TTO2928182","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down due=
 to Cb(100A) of PWC dysjonted before Gen start// He remead the CB Power iss=
ue resolved but site up MTN 11:28 AM and remains down OCM  lionel adjp(6 55=
 18 48 76) from Huawei is informed","system","828","16-09-2024 11:22:21","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003085628","AWAE OCM=
","","16-09-2024 11:22:21","16-09-2024 11:08:33","16-09-2024 11:28:11","Cas=
caded Incident from TTO2928182","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down due to C=
b(100A) of PWC dysjonted before Gen start// He remead the CB Power issue re=
solved but site up MTN 11:28 AM and remains down OCM  lionel adjp(6 55 18 4=
8 76) from Huawei is informed","system","828","16-09-2024 11:22:21","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0003085629","Essomba"=
,"","16-09-2024 11:22:21","16-09-2024 11:08:33","16-09-2024 11:28:11","Casc=
aded Incident from TTO2928182","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down due to Cb=
(100A) of PWC dysjonted before Gen start// He remead the CB Power issue res=
olved but site up MTN 11:28 AM and remains down OCM  lionel adjp(6 55 18 48=
 76) from Huawei is informed","system","828","16-09-2024 11:22:21","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003085626","Bitoto",=
"","16-09-2024 11:22:20","16-09-2024 11:08:33","16-09-2024 11:28:11","Casca=
ded Incident from TTO2928182","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down due to Cb(=
100A) of PWC dysjonted before Gen start// He remead the CB Power issue reso=
lved but site up MTN 11:28 AM and remains down OCM  lionel adjp(6 55 18 48 =
76) from Huawei is informed","system","827","16-09-2024 11:22:20","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003085627","Tradex-N=
komo","","16-09-2024 11:22:20","16-09-2024 11:08:33","16-09-2024 11:28:11",=
"Cascaded Incident from TTO2928182","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down due to =
Cb(100A) of PWC dysjonted before Gen start// He remead the CB Power issue r=
esolved but site up MTN 11:28 AM and remains down OCM  lionel adjp(6 55 18 =
48 76) from Huawei is informed","system","827","16-09-2024 11:22:20","Sagem=
com CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0003085564","Bit=
eng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179, IHS_YND_249","16-=
09-2024 11:13:11","16-09-2024 11:08:33","16-09-2024 11:28:47","Grid outage =
site went down due to Cb(100A) of PWC dysjonted before Gen start// He remea=
d the CB Power issue resolved but site up MTN 11:28 AM and remains down OCM=
  lionel adjp(6 55 18 48 76) from Huaw","Mba Lazare Herve","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Grid =
outage site went down due to Cb(100A) of PWC dysjonted before Gen start// H=
e remead the CB Power issue resolved but site up MTN 11:28 AM and remains d=
own OCM  lionel adjp(6 55 18 48 76) from Huawei is informed","dorothy.djant=
io@ihstowers.com","279","16-09-2024 11:13:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003085310","M=
imboman-Ecole","","16-09-2024 10:33:15","16-09-2024 10:29:10","16-09-2024 1=
0:31:25","Site went down due to insufficient of rectifier// Site Stabilized=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","Site went down due to insufficient of rectifier// Site Stabilized","=
ludivine.ngamaleu@ihstowers.com","245","16-09-2024 10:33:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0003085261","E=
SSOS OASIS 1111","","16-09-2024 10:25:43","16-09-2024 10:17:30","16-09-2024=
 11:46:36","Active, no power issue, site on grid with U=3D53.2 V, The Tx Ar=
mand Nguetsa /691144412/ From Huawei is informed","Siligap Boris","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active, no power issue, site on grid with U=3D53.2 V, The Tx Armand Ngue=
tsa /691144412/ From Huawei is informed","ludivine.ngamaleu@ihstowers.com",=
"494","16-09-2024 10:25:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_044","NOCINC0003085060","Polytech=
nique","","16-09-2024 09:52:30","16-09-2024 09:47:47","16-09-2024 10:31:58"=
,"Cascaded Incident from TTO2927554","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","site went down because the CB (125A) tripped  =
in PWC due to load increase//made a shunt of CB 125 and 80 A","system","283=
","16-09-2024 09:52:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_447","IHS_YND_061","NOCINC0003085048","Y=
de University","IHS_YND_044","16-09-2024 09:51:48","16-09-2024 09:47:47","1=
6-09-2024 10:31:58","site went down because the CB (125A) tripped  in PWC d=
ue to load increase//made a shunt of CB 125 and 80 A","Paul BIBOUM","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issu=
e","site went down because the CB (125A) tripped  in PWC due to load increa=
se//made a shunt of CB 125 and 80 A","ludivine.ngamaleu@ihstowers.com","242=
","16-09-2024 09:51:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003084916","Y=
de-M-Central","","16-09-2024 09:27:41","16-09-2024 09:23:44","16-09-2024 09=
:34:03","Grid Outage No space to deploy a MDG//Grid Restored","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No sp=
ace to deploy a MDG//Grid Restored","ludivine.ngamaleu@ihstowers.com","238"=
,"16-09-2024 09:27:41","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003084895","Pha=
rmacie SION","","16-09-2024 09:24:24","16-09-2024 09:20:20","16-09-2024 09:=
32:09","Grid Outage site down due to poor backup before Gen start//Grid Res=
tored","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Battery Low","Grid Outage site down due to poor backup before Gen s=
tart//Grid Restored","dorothy.djantio@ihstowers.com","245","16-09-2024 09:2=
4:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003084874","M=
imboman-Village","IHS_YND_709","16-09-2024 09:22:52","16-09-2024 09:15:54",=
"16-09-2024 09:33:19","Grid outage  site down due to poor backup before gen=
 start  //Grid power return","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage  site down due=
 to poor backup before gen start  //Grid power return","ludivine.ngamaleu@i=
hstowers.com","419","16-09-2024 09:22:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003084869","N=
kolo II New","","16-09-2024 09:21:38","16-09-2024 09:15:54","16-09-2024 09:=
33:19","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage  site down due to poor backup before gen star=
t  //Grid power return","ludivine.ngamaleu@ihstowers.com","961","16-09-2024=
 09:21:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0003084855","Sapeur",=
"","16-09-2024 09:19:00","16-09-2024 09:14:25","16-09-2024 09:21:33","Casca=
ded Incident from TTO2927323","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid Outage No space to deploy a MDG//Gr=
id Restored","system","275","16-09-2024 09:19:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0003084852","E=
-Police","IHS_YND_029","16-09-2024 09:18:24","16-09-2024 09:14:25","16-09-2=
024 09:21:33","Grid Outage No space to deploy a MDG//Grid Restored","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage=
 No space to deploy a MDG//Grid Restored","ludivine.ngamaleu@ihstowers.com"=
,"240","16-09-2024 09:18:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0003084848","Mvog-Man=
ga","","16-09-2024 09:18:00","16-09-2024 09:13:31","16-09-2024 09:15:48","C=
ascaded Incident from TTO2927285","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage  site down due to poor b=
ackup before gen start  //Gen automatically started","system","269","16-09-=
2024 09:18:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0003084849","Marche O=
dza","","16-09-2024 09:18:00","16-09-2024 09:13:31","16-09-2024 09:15:48","=
Cascaded Incident from TTO2927285","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage  site down due to poor =
backup before gen start  //Gen automatically started","system","269","16-09=
-2024 09:18:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0003084818","O=
dza","IHS_YND_254, IHS_YND_580","16-09-2024 09:14:32","16-09-2024 09:13:31"=
,"16-09-2024 09:15:48","Grid outage  site down due to poor backup before ge=
n start  //Gen automatically started","Albran Byorel","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage  site do=
wn due to poor backup before gen start  //Gen automatically started","ludiv=
ine.ngamaleu@ihstowers.com","61","16-09-2024 09:14:32","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003084813","Eko=
unou","","16-09-2024 09:14:11","16-09-2024 09:13:06","16-09-2024 09:31:02",=
"Grid outage  site down due to poor backup before gen start  //Grid power r=
eturn","Albran Byorel","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","Grid outage  site down due to poor backup before ge=
n start  //Grid power return","dorothy.djantio@ihstowers.com","67","16-09-2=
024 09:14:11","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003084417","NTU=
I TOWN","","16-09-2024 07:43:54","16-09-2024 07:38:46","16-09-2024 08:00:06=
","ACTIVE //No power issue site on Grid with Ubai=3D54,3 V  The TX FME Gr=
=E9goire //654547479// from huawei is informed","Parker Tchoup","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE //No power issue site on Grid with Ubai=3D54,3 V  The TX FME Gr=E9g=
oire //654547479// from huawei is informed","dorothy.djantio@ihstowers.com"=
,"309","16-09-2024 07:43:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0003084292","B=
oumnyebel OCM","","16-09-2024 07:05:33","16-09-2024 07:02:28","16-09-2024 0=
7:07:52","Grid outage site went down due to poor battery backup Before Gen =
Started//  Grid power return","Kemeni Franklin","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage site went down=
 due to poor battery backup Before Gen Started//  Grid power return","ludiv=
ine.ngamaleu@ihstowers.com","186","16-09-2024 07:05:33","Sagemcom CMR"
"Closed Complete","Site Down","T0573","IHS_YND_387","NOCINC0003083500","Tal=
la Monatele","","16-09-2024 03:10:27","16-09-2024 03:06:20","16-09-2024 03:=
54:59","Eneo CB down, site went down because Gen ran till fuel shortage// R=
efueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Out=
age","Eneo CB down, site went down because Gen ran till fuel shortage// Ref=
ueling done","landry.etame@ihstowers.com","248","16-09-2024 03:10:27","Sage=
mcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0003082993","Fla=
menco","","16-09-2024 00:13:45","16-09-2024 00:09:35","16-09-2024 01:11:45"=
,"Access Issue during the Night due to Insecurity, Grid Outage site went do=
wn because Gen Card Faulty  // Grid Power return","Mboua Thierry","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Control Panel","Access Issue during =
the Night due to Insecurity, Grid Outage site went down because Gen Card Fa=
ulty  // Grid Power return","landry.etame@ihstowers.com","250","16-09-2024 =
00:13:45","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_357","NOCINC0003082908","Sacre Coeur Cath=
olic Church","","15-09-2024 23:40:40","","","Cascaded Incident from TTO2925=
095 - Cascade Removed From TTO2925095","Mboua Thierry","","","","","","syst=
em","2399","15-09-2024 23:40:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003082781","N=
komkana","","15-09-2024 23:09:34","15-09-2024 22:59:14","16-09-2024 01:08:0=
2","Grid Outage no space to deploy MDG // Grid Power return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no spa=
ce to deploy MDG // Grid Power return","kouoh.jean@ihstowers.com","621","15=
-09-2024 23:09:34","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003082756","Tsi=
nga","","15-09-2024 23:03:12","15-09-2024 22:54:02","16-09-2024 00:54:38","=
grid outage gen failed to start due to charger static faulty//He started  G=
en with external battery","Mboua Thierry","Equipment Repair","Passive","ACD=
G Gen","ACDG - Turbo Charger","grid outage gen failed to start due to charg=
er static faulty//He started  Gen with external battery","landry.etame@ihst=
owers.com","551","15-09-2024 23:03:12","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003082743","Bas=
tos Ekoudou","","15-09-2024 23:00:09","15-09-2024 22:51:39","16-09-2024 00:=
21:30","Grid outage, site went down because Gen stopped due to ""high temp"=
" alarm //He added water and gen manually started","Mboua Thierry","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Is=
sue","Grid outage, site went down because Gen stopped due to ""high temp"" =
alarm //He added water and gen manually started","landry.etame@ihstowers.co=
m","511","15-09-2024 23:00:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0003082651","A=
wae Ewonkan","","15-09-2024 22:34:14","15-09-2024 22:07:56","15-09-2024 22:=
22:37","Site went down due to insuffisance of rectifier(05/06)// Site stabi=
lized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier =
Module","Site went down due to insuffisance of rectifier(05/06)// Site stab=
ilized","kouoh.jean@ihstowers.com","1579","15-09-2024 22:34:14","Sagemcom C=
MR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003081756","Eko=
unou","","15-09-2024 20:17:24","15-09-2024 20:13:18","15-09-2024 20:23:02",=
"grid outage, site went down because gen failed to start due to poor batter=
y backup// grid return","Albran Byorel","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","grid outage, site went down becaus=
e gen failed to start due to poor battery backup// grid return","joelle.eke=
ssi@ihstowers.com","247","15-09-2024 20:17:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003081536","Ngog Map=
ubi","","15-09-2024 19:32:21","15-09-2024 19:27:21","15-09-2024 19:32:45","=
Cascaded Incident from TTO2923479","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site went down becau=
se gen failed to started due to poor battery backup// grid return","system"=
,"300","15-09-2024 19:32:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003081537","Boumnyeb=
el","","15-09-2024 19:32:21","15-09-2024 19:27:21","15-09-2024 19:32:45","C=
ascaded Incident from TTO2923479","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, site went down becaus=
e gen failed to started due to poor battery backup// grid return","system",=
"300","15-09-2024 19:32:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003081538","Mamb",""=
,"15-09-2024 19:32:21","15-09-2024 19:27:21","15-09-2024 19:32:45","Cascade=
d Incident from TTO2923479","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","grid outage, site went down because gen =
failed to started due to poor battery backup// grid return","system","300",=
"15-09-2024 19:32:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003081535","Ndogbess=
ol","","15-09-2024 19:32:20","15-09-2024 19:27:21","15-09-2024 19:32:45","C=
ascaded Incident from TTO2923479","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, site went down becaus=
e gen failed to started due to poor battery backup// grid return","system",=
"299","15-09-2024 19:32:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0003081526","B=
oumnyebel OCM","IHS_EDA_114, IHS_EDA_056, IHS_YND_419, IHS_YND_381, IHS_YND=
_376","15-09-2024 19:30:25","15-09-2024 19:27:21","15-09-2024 19:32:45","gr=
id outage, site went down because gen failed to started due to poor battery=
 backup// grid return","Kemeni Franklin","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","grid outage, site went down becau=
se gen failed to started due to poor battery backup// grid return","emmanue=
l.ghani@ihstowers.com","185","15-09-2024 19:30:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003081498","ELOUMDEM=
 CARRIERE 2","","15-09-2024 19:21:20","15-09-2024 19:17:02","15-09-2024 20:=
22:26","Cascaded Incident from TTO2923432","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid bad voltage, site went d=
own because gen failed to start due to gen overload(220KVA, 330A)// grid st=
abilized","system","258","15-09-2024 19:21:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003081497","Eto koss=
 Yde","","15-09-2024 19:21:20","15-09-2024 19:17:02","15-09-2024 20:22:26",=
"Cascaded Incident from TTO2923432","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid bad voltage, site went down bec=
ause gen failed to start due to gen overload(220KVA, 330A)// grid stabilize=
d","system","258","15-09-2024 19:21:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003081486","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","15-09-2024 19:20:07","15-09-2024 19:17=
:02","15-09-2024 20:22:26","grid bad voltage, site went down because gen fa=
iled to start due to gen overload(220KVA, 330)// grid stabilized","Fanda Br=
ice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","grid bad vo=
ltage, site went down because gen failed to start due to gen overload(220KV=
A, 330A)// grid stabilized","joelle.ekessi@ihstowers.com","187","15-09-2024=
 19:20:07","Sagemcom CMR"
"Closed Complete","Site Down","T1569","IHS_YND_226","NOCINC0003081395","Mvo=
g-Betsi","","15-09-2024 19:06:35","15-09-2024 19:02:29","15-09-2024 19:20:3=
1","Site went down because 01/06 rectifier faulty//He replaced faulty recti=
fier ;Site on Grid","Hyemafo Gildas","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down because 01/06 rectifier faulty//He re=
placed faulty rectifier ;Site on Grid","joelle.ekessi@ihstowers.com","246",=
"15-09-2024 19:06:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003081260","E=
mana","","15-09-2024 18:33:12","15-09-2024 18:30:06","15-09-2024 21:45:01",=
"No power issue on site.Site on Grid with Ubaie=3D52,2  V he TX FME Synphor=
ien//691316854   from Huawei is informed ","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site.Site on Grid with Ubaie=3D52,2  V he TX FME Synphorien//691316854   f=
rom Huawei is informed ","emmanuel.ghani@ihstowers.com","187","15-09-2024 1=
8:33:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_273","IHS_YND_214","NOCINC0003081203","N=
kolmesseng-II","","15-09-2024 18:18:49","15-09-2024 18:04:43","15-09-2024 1=
9:24:17","site went due to CB OCM (125A) disjuncted in PWC  causing by  due=
 icrease load on site  //He reamed CB.Site on Grid","Siligap Boris","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issu=
e","site went due to CB OCM (125A) disjuncted in PWC  causing by  due icrea=
se load on site  //He reamed CB.Site on Grid","emmanuel.ghani@ihstowers.com=
","847","15-09-2024 18:18:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0003081020","S=
IMBOCK BONAMBAPE","","15-09-2024 17:51:31","15-09-2024 17:47:24","15-09-202=
4 17:57:54","No power issue, site is on grid with Ubaie=3D53V, Mba Hosiah (=
5699699694) from Huawei is informed","Hyemafo Gildas","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue, site is on grid with Ubaie=3D53V, Mba Hosiah (5699699694) from Huawe=
i is informed","emmanuel.ghani@ihstowers.com","248","15-09-2024 17:51:31","=
Sagemcom CMR"
"Closed Complete","Site Down","T1266","IHS_YND_801","NOCINC0003080741","HOP=
ITAL GENERAL RAIL YDE","","15-09-2024 17:00:18","15-09-2024 16:57:13","16-0=
9-2024 13:06:06","Access issue due to Landlord Grid bad voltage site went d=
own because the cb of energy meter did not trigger  due to lightning arrest=
er faulty // He bypass lightning arrester and site on Grid","Delor Telezing=
","Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue =
- Land Lord","Access issue due to Landlord Grid bad voltage site went down =
because the cb of energy meter did not trigger  due to lightning arrester f=
aulty // He bypass lightning arrester and site on Grid","joelle.ekessi@ihst=
owers.com","186","15-09-2024 17:00:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003080600","Nkolfoul=
ou 2","","15-09-2024 16:40:41","15-09-2024 16:37:19","15-09-2024 16:45:47",=
"Cascaded Incident from TTO2922357","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue, site is on grid with =
Ubaie=3D53V, Symphorien(691316854//650257151) from Huawei is informed ","sy=
stem","202","15-09-2024 16:40:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003080601","TSINGA V=
ILLAGE 2","","15-09-2024 16:40:41","15-09-2024 16:37:19","15-09-2024 16:45:=
47","Cascaded Incident from TTO2922357","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue, site is on grid =
with Ubaie=3D53V, Symphorien(691316854//650257151) from Huawei is informed =
","system","202","15-09-2024 16:40:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003080588","N=
kolfoulou","IHS_YND_278, IHS_YND_719","15-09-2024 16:38:27","15-09-2024 16:=
37:19","15-09-2024 17:20:47","No power issue, site is on grid with Ubaie=3D=
53V, Symphorien(691316854//650257151) from Huawei is informed ","Siligap Bo=
ris","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue, site is on grid with Ubaie=3D53V, Symphori=
en(691316854//650257151) from Huawei is informed ","emmanuel.ghani@ihstower=
s.com","69","15-09-2024 16:38:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0003080580","M=
essassi","","15-09-2024 16:35:45","15-09-2024 16:34:40","16-09-2024 06:00:1=
2","No power issue on site.Site on Grid with Ubaie=3D54.5 V  The Team  Eric=
 Mbodo//696422966 from ZTE is informed","Fabrice Pouakam","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site.Site on Grid with Ubaie=3D54.5 V  The Team  Eric Mbodo//6=
96422966 from ZTE is informed","emmanuel.ghani@ihstowers.com","66","15-09-2=
024 16:35:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003080539","M=
elen Ba'aba","","15-09-2024 16:27:47","15-09-2024 16:14:09","15-09-2024 17:=
41:46","Grid fluctuation,site went down because Gen failed to start due to =
poor backup//He bypassed Grid and started Gen","Siligap Boris","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid fluctu=
ation,site went down because Gen failed to start due to poor backup//He byp=
assed Grid and started Gen","emmanuel.ghani@ihstowers.com","819","15-09-202=
4 16:27:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003080468","M=
imboman-Ecole","","15-09-2024 16:15:32","15-09-2024 16:12:56","15-09-2024 1=
6:15:46","Grid outage, site down because Gen failed to start due to poor ba=
ttery backup //Gen automaticcaly started","Mba Lazare Herve","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
site down because Gen failed to start due to poor battery backup //Gen auto=
maticcaly started","emmanuel.ghani@ihstowers.com","157","15-09-2024 16:15:3=
2","Sagemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0003080408","N=
gousso-Savana","IHS_YND_561","15-09-2024 16:05:32","15-09-2024 16:01:27","1=
5-09-2024 17:45:26","Site went down due CB OCM (100A)disjunted in PWC causi=
ng  by grid fliuctuation// He make the bridge with CB(63A)","Siligap Boris"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Brea=
ker Issue","Site went down due CB OCM (100A)disjunted in PWC causing  by gr=
id fliuctuation// He make the bridge with CB(63A)","emmanuel.ghani@ihstower=
s.com","246","15-09-2024 16:05:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0003080400","F=
OUGEROLE","","15-09-2024 16:04:33","15-09-2024 16:01:27","15-09-2024 17:45:=
26","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Site went down due CB OCM (100A)disjunted in PWC causing  by gr=
id fliuctuation// He make the bridge with CB(63A)","emmanuel.ghani@ihstower=
s.com","740","15-09-2024 16:04:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003080309","MBIMBIM"=
,"","15-09-2024 15:42:11","15-09-2024 15:37:05","15-09-2024 15:37:06","Casc=
aded Incident from TTO2921998","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site Ubaie 52V Site on b=
attery . FME TX_Abdouraman 657959647 is informed via Call","system","306","=
15-09-2024 15:42:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003080308","Ngouetou=
","","15-09-2024 15:42:10","15-09-2024 15:37:05","15-09-2024 15:37:06","Cas=
caded Incident from TTO2921998","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site Ubaie 52V Site on =
battery . FME TX_Abdouraman 657959647 is informed via Call","system","305",=
"15-09-2024 15:42:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003080305","Ngoum","=
","15-09-2024 15:42:10","15-09-2024 15:37:05","15-09-2024 15:37:06","Cascad=
ed Incident from TTO2921998","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site Ubaie 52V Site on bat=
tery . FME TX_Abdouraman 657959647 is informed via Call","system","305","15=
-09-2024 15:42:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003080307","Yoko OCM=
","","15-09-2024 15:42:10","15-09-2024 15:37:05","15-09-2024 15:37:06","Cas=
caded Incident from TTO2921998","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site Ubaie 52V Site on =
battery . FME TX_Abdouraman 657959647 is informed via Call","system","305",=
"15-09-2024 15:42:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003080306","Matsari"=
,"","15-09-2024 15:42:10","15-09-2024 15:37:05","15-09-2024 15:37:06","Casc=
aded Incident from TTO2921998","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site Ubaie 52V Site on b=
attery . FME TX_Abdouraman 657959647 is informed via Call","system","305","=
15-09-2024 15:42:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003080258","M=
EFOU ASSI","","15-09-2024 15:33:54","15-09-2024 15:31:49","15-09-2024 17:43=
:48","site went down due to Cb(125A) disjuncted in Dx boss OCM // He reamed=
 Cb(125A), site on grid","Fanda Brice","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Circuit Breaker Issue","site went down due to Cb(=
125A) disjuncted in Dx boss OCM // He reamed Cb(125A), site on grid","emman=
uel.ghani@ihstowers.com","126","15-09-2024 15:33:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0003080174","E=
leveur","IHS_YND_277","15-09-2024 15:24:07","15-09-2024 14:20:43","15-09-20=
24 15:31:31","ELEVEUR // Grid fluctuation ,Site went down because  Gen fail=
ed to start due to poor battery backup/ /Grid stabilized,Power issue resolv=
ed at 03:31  PM but site remain down ,The TX FME Synphorien//691","Siligap =
Boris","Equipment Repair","Passive","Control Panel","Power Cabinet - Batter=
y Low","ELEVEUR // Grid fluctuation ,Site went down because  Gen failed to =
start due to poor battery backup/ /Grid stabilized,Power issue resolved at =
03:31  PM but site remain down ,The TX FME Synphorien//691316854   from Hua=
wei is informed","emmanuel.ghani@ihstowers.com","3805","15-09-2024 15:24:07=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003080144","N=
kozoa","","15-09-2024 15:16:43","15-09-2024 15:14:27","15-09-2024 15:17:05"=
,"Grid bad voltage,Site went down because Gen failed to start due to Gen ov=
erload(20KVA,320)//he load on site and started GEN","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid bad voltage,Site=
 went down because Gen failed to start due to Gen overload(20KVA,320)//he l=
oad on site and started GEN","emmanuel.ghani@ihstowers.com","138","15-09-20=
24 15:16:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003080124","Y=
de-M-Central","","15-09-2024 15:11:56","15-09-2024 15:09:51","15-09-2024 15=
:22:50","grid outage, no space to deploy a mobil gen//grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,=
 no space to deploy a mobil gen//grid return","emmanuel.ghani@ihstowers.com=
","126","15-09-2024 15:11:56","Sagemcom CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0003080102","Aba=
ttoir","","15-09-2024 15:07:23","15-09-2024 15:01:19","15-09-2024 16:44:54"=
,"grid outage, site went down because gen failed to start due to no battery=
 charger // Gen started with external battery","Fabrice Pouakam","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Generator Battery","grid outage, site=
 went down because gen failed to start due to no battery charger // Gen sta=
rted with external battery","joelle.ekessi@ihstowers.com","613","15-09-2024=
 15:07:23","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003080071","San=
ta Barbara Gottam","","15-09-2024 14:59:56","15-09-2024 14:55:52","15-09-20=
24 15:52:00","Grid  outage,site went down because Gen started and Stopped w=
ith Alarm "" under current""//He reset Gen card and started Gen","Delor Tel=
ezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
  outage,site went down because Gen started and Stopped with Alarm "" under=
 current""//He reset Gen card and started Gen","joelle.ekessi@ihstowers.com=
","244","15-09-2024 14:59:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003080040","A=
kak-Nkozoa-MTN-IHS","","15-09-2024 14:54:13","15-09-2024 14:49:53","15-09-2=
024 14:54:11","site went down because Gen failed to start due to Grid bad v=
oltage// he bypass the Grid and site on Gen","Fabrice Pouakam","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","site went dow=
n because Gen failed to start due to Grid bad voltage// he bypass the Grid =
and site on Gen","emmanuel.ghani@ihstowers.com","261","15-09-2024 14:54:13"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003079985","Nko=
abang Ebolmedjock","","15-09-2024 14:41:22","15-09-2024 14:40:17","15-09-20=
24 14:42:38","site went down due to work(Mbah lazare(657108482)/ Sagemcom, =
replacement charging alternator)// end of work","Mba Lazare Herve","Equipme=
nt Replacement","Passive","Planned Activity","Planned Activity - Passive","=
site went down due to work(Mbah lazare(657108482)/ Sagemcom, replacement ch=
arging alternator)// end of work","joelle.ekessi@ihstowers.com","65","15-09=
-2024 14:41:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0003079905","N=
goulmekong-Nord","","15-09-2024 14:32:01","15-09-2024 14:20:43","15-09-2024=
 15:31:31","Grid fluctuation ,Site went down because  Gen failed to start d=
ue to poor battery backup//Grid stabilized","Siligap Boris","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid fluctuation ,Site wen=
t down because  Gen failed to start due to poor battery backup//Grid stabil=
ized","emmanuel.ghani@ihstowers.com","4527","15-09-2024 14:32:01","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0003079830","E=
SSOS OASIS 1111","","15-09-2024 14:18:31","15-09-2024 14:00:26","15-09-2024=
 16:30:26","Active, no power issue, site on grid with U=3D53.4 V, The Tx Ar=
mand Nguetsa /691144412/ From Huawei is informed","Siligap Boris","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active, no power issue, site on grid with U=3D53.4 V, The Tx Armand Ngue=
tsa /691144412/ From Huawei is informed","emmanuel.ghani@ihstowers.com","10=
86","15-09-2024 14:18:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003079763","O=
lembe-Terminus","","15-09-2024 14:04:38","15-09-2024 13:59:02","15-09-2024 =
14:52:03","Site went down because 02/03 rectifiers Hanging//he reset rectif=
iers ,site on Gen","Fabrice Pouakam","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","Site went down because 02/03 rectifiers Hanging//he =
reset rectifiers ,site on Gen","ange.kongo@ihstowers.com","337","15-09-2024=
 14:04:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003079687","Lobo OCM=
","","15-09-2024 13:48:01","15-09-2024 13:35:54","15-09-2024 13:41:16","Cas=
caded Incident from TTO2921278","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site down beca=
use Gen failed to start due to poor battery backup //Gen automaticcaly star=
ted","system","727","15-09-2024 13:48:01","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003079685","N=
KOMEKUI OCM","IHS_YND_341","15-09-2024 13:47:06","15-09-2024 13:35:54","15-=
09-2024 13:41:16","Grid outage, site down because Gen failed to start due t=
o poor battery backup //Gen automaticcaly started","TIENTCHEU NZETCHIEU GAE=
L","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid outage, site down because Gen failed to start due to poor battery =
backup //Gen automaticcaly started","ange.kongo@ihstowers.com","673","15-09=
-2024 13:47:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0003079522","A=
battoir","","15-09-2024 13:12:06","15-09-2024 13:03:52","15-09-2024 13:47:5=
6","Grid outage site went down because Gen failed to start due to alarm hig=
h temp// Grid power return and add water","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","G=
rid outage site went down because Gen failed to start due to alarm high tem=
p// Grid power return and add water","ange.kongo@ihstowers.com","495","15-0=
9-2024 13:12:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003079509","A=
KONGO","","15-09-2024 13:09:27","15-09-2024 12:51:18","15-09-2024 13:55:26"=
,"Active:  No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rod=
rigue (655102999)from Huawei is informed. Repetitive issue","Fanda Brice","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","No power issue on site U=3D54v site on gen Rodrigue of huawei is=
 informed","ange.kongo@ihstowers.com","1090","15-09-2024 13:09:27","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003079239","A=
kak-Nkozoa-MTN-IHS","","15-09-2024 12:24:07","15-09-2024 12:15:57","15-09-2=
024 13:30:31","grid outage,gen failed to start due to grid bad voltage,no r=
cp//he bypassed grid and started the gen","Fabrice Pouakam","Grid Supply","=
Passive","Grid","National Grid - Phase Controller Faulty","grid outage,gen =
failed to start due to grid bad voltage,no rcp//he bypassed grid and starte=
d the gen","ange.kongo@ihstowers.com","491","15-09-2024 12:24:07","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_336","IHS_YND_212","NOCINC0003079055","H=
-General-Yde","","15-09-2024 11:47:14","15-09-2024 11:41:09","15-09-2024 13=
:17:11","Active// No power issue on site U=3D54,4v   site on Gen Team Erick=
/696422966/ZTE working on site","Siligap Boris","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue on site U=3D54,4v   site on Gen Team Erick/696422966/ZTE working o=
n site","ange.kongo@ihstowers.com","365","15-09-2024 11:47:14","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0003078957","E=
mana lycee 2","","15-09-2024 11:29:08","15-09-2024 10:24:52","15-09-2024 11=
:30:32","Grid Outage, site went down because Gen  failed to start due to Ge=
n battery faulty // Gen manually started with external battery","Fabrice Po=
uakam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","=
Grid Outage, site went down because Gen  failed to start due to Gen battery=
 faulty // Gen manually started with external battery","ange.kongo@ihstower=
s.com","3856","15-09-2024 11:29:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0003078780","N=
R-Bastos","IHS_YND_019","15-09-2024 10:53:04","15-09-2024 10:16:15","15-09-=
2024 11:51:37","Grid outage//MDG 13kva deployed","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","Grid outage//MDG 13kva deploye=
d","ange.kongo@ihstowers.com","2210","15-09-2024 10:53:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_369","IHS_YND_019","NOCINC0003078768","H=
otel de Ville Yde","","15-09-2024 10:49:48","15-09-2024 10:16:15","15-09-20=
24 11:51:37","tikect need to attach at NR-bastos","Paul BIBOUM","Cascade Ou=
tage","Passive","Cascade Passive","Cascade Passive","Grid outage//MDG 13kva=
 deployed","ange.kongo@ihstowers.com","8804","15-09-2024 10:49:48","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003078749","O=
lembe","","15-09-2024 10:46:13","15-09-2024 10:06:06","15-09-2024 12:01:13"=
,"No power issue on site U=3D57v site on grid Team Erick/696422966/ZTE work=
ing on site","Fabrice Pouakam","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D57v s=
ite on grid Team Erick/696422966/ZTE working on site","ange.kongo@ihstowers=
.com","2408","15-09-2024 10:46:13","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003078725","Bas=
tos Amb Coree","","15-09-2024 10:42:33","15-09-2024 10:39:19","15-09-2024 1=
3:23:09","Grid Outage no space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no spa=
ce to deploy MDG // Grid return","denis.mballa@ihstowers.com","195","15-09-=
2024 10:42:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003078703","Y=
de-M-Central","","15-09-2024 10:40:27","15-09-2024 09:59:13","15-09-2024 13=
:37:26","Grid outage,No space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,N=
o space to deploy a mobil gen//grid return","ange.kongo@ihstowers.com","247=
5","15-09-2024 10:40:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003078551","Etoudi 2=
","","15-09-2024 10:09:01","15-09-2024 10:01:54","15-09-2024 11:02:24","Cas=
caded Incident from TTO2919960","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen failed to start due =
to card Ge faulty//Gen manually started","system","427","15-09-2024 10:09:0=
1","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003078549","ETOUDI C=
HAPELLE","","15-09-2024 10:09:01","15-09-2024 10:01:54","15-09-2024 11:02:2=
4","Cascaded Incident from TTO2919960","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage,gen failed to star=
t due to card Ge faulty//Gen manually started","system","427","15-09-2024 1=
0:09:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003078548","Abattoir=
","","15-09-2024 10:09:00","15-09-2024 10:01:54","15-09-2024 11:02:24","Cas=
caded Incident from TTO2919960","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen failed to start due =
to card Ge faulty//Gen manually started","system","426","15-09-2024 10:09:0=
0","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003078543","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","15-09-2024 10:07:23","15-09-2=
024 10:00:21","15-09-2024 11:02:24","grid outage,gen failed to start due to=
 card Ge faulty//Gen manually started","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","grid outage,gen failed to sta=
rt due to card Ge faulty//Gen manually started","denis.mballa@ihstowers.com=
","2649","15-09-2024 10:07:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0003078525","Mvog-Eba=
nda","","15-09-2024 10:02:40","15-09-2024 09:49:26","15-09-2024 10:21:40","=
Cascaded Incident from TTO2919923","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage,gen failed to start due=
 to alarm under voltage(Gen overload:12,5kva;170A)//he reset the card and s=
tarted it","system","794","15-09-2024 10:02:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003078513","A=
bom","IHS_YND_269","15-09-2024 10:00:39","15-09-2024 09:49:26","15-09-2024 =
10:21:40","grid outage,gen failed to start due to alarm under voltage(Gen o=
verload:12,5kva;170A)//he reset the card and started it","Siligap Boris","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage,g=
en failed to start due to alarm under voltage(Gen overload:12,5kva;170A)//h=
e reset the card and started it","ange.kongo@ihstowers.com","674","15-09-20=
24 10:00:39","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003078174","Elo=
umdem stade","","15-09-2024 08:50:01","15-09-2024 08:41:41","15-09-2024 09:=
07:32","Grid outage  site went down because Gen stopped  due to grid return=
 and Grid contactor did not excited// He excited grid contactor","Fanda Bri=
ce","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outa=
ge  site went down because Gen stopped  due to grid return and Grid contact=
or did not excited// He excited grid contactor","denis.mballa@ihstowers.com=
","501","15-09-2024 08:50:01","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003078165","Nko=
abang Ebolmedjock","","15-09-2024 08:47:39","15-09-2024 08:38:27","15-09-20=
24 10:43:32","site went down because gen failed to start due to card Ge fau=
lty//Gen manaully started","Mba Lazare Herve","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","site went down because gen failed to sta=
rt due to card Ge faulty//Gen manaully started","denis.mballa@ihstowers.com=
","553","15-09-2024 08:47:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003078022","N=
yom OCM","","15-09-2024 08:14:10","15-09-2024 08:11:02","15-09-2024 09:08:5=
5","Grid outage, site went down because Gen stopped due to ""high temp"" al=
arm //He added water and gen manually started","Fabrice Pouakam","Equipment=
 Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issu=
e","Grid outage, site went down because Gen stopped due to ""high temp"" al=
arm //He added water and gen manually started","ange.kongo@ihstowers.com","=
189","15-09-2024 08:14:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003077878","M=
elen Ba'aba","","15-09-2024 07:29:28","15-09-2024 07:21:02","15-09-2024 07:=
26:36","Grid outage, site down because Gen failed to start due to poor batt=
ery backup // Gen started automaticaly","Siligap Boris","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site =
down because Gen failed to start due to poor battery backup // Gen started =
automaticaly","ange.kongo@ihstowers.com","507","15-09-2024 07:29:28","Sagem=
com CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0003077821","Mfo=
u EPC","","15-09-2024 07:12:23","15-09-2024 07:03:37","15-09-2024 07:31:27"=
,"Grid outage, site went down because Gen stopped due to ""high temp"" alar=
m //He added water and gen manually started","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","Grid outage, site went down because Gen stopped due to ""high temp"" ala=
rm //He added water and gen manually started","denis.mballa@ihstowers.com",=
"907","15-09-2024 07:12:23","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003077766","Ess=
os Marche","","15-09-2024 07:00:08","15-09-2024 06:56:58","15-09-2024 07:40=
:33","Active, no power issue, site on grid with U=3D54.4 V, The Tx Armand N=
guetsa /691144412/ From Huawei is informed","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive, no power issue, site on grid with U=3D54.4 V, The Tx Armand Nguetsa /=
691144412/ From Huawei is informed","denis.mballa@ihstowers.com","191","15-=
09-2024 07:00:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0003077755","E=
SSOS OASIS 1111","","15-09-2024 06:56:40","15-09-2024 06:47:33","15-09-2024=
 09:09:08","Active, no power issue, site on grid with U=3D53.4 V, The Tx Ar=
mand Nguetsa /691144412/ From Huawei is informed","Siligap Boris","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active, no power issue, site on grid with U=3D53.4 V, The Tx Armand Ngue=
tsa /691144412/ From Huawei is informed","ange.kongo@ihstowers.com","548","=
15-09-2024 06:56:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0003076845","SOA VILL=
AGE","","15-09-2024 00:27:31","15-09-2024 00:15:33","15-09-2024 00:37:22","=
Cascaded Incident from TTO2917946","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
 gen start and stoppen with alarm ""Undervoltage"" // He reset Gen Card and=
 started GEN manually","system","718","15-09-2024 00:27:31","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0003076819","SOA=
 TOWN","IHS_YND_323","15-09-2024 00:21:46","15-09-2024 00:15:33","15-09-202=
4 00:37:22","Grid outage, site went down because gen start and stoppen with=
 alarm ""Undervoltage"" // He reset Gen Card and started GEN manually","Sil=
igap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, site went down because gen start and stoppen with alarm ""Und=
ervoltage"" // He reset Gen Card and started GEN manually","kamga.virgile@i=
hstowers.com","373","15-09-2024 00:21:46","Sagemcom CMR"
"Cancelled","Warning","T1623","IHS_YND_320","NOCINC0003076808","SOA TOWN","=
","15-09-2024 00:19:19","","","","Siligap Boris","","","","","","kamga.virg=
ile@ihstowers.com","252","15-09-2024 00:19:19","Sagemcom CMR"
"Closed Complete","Warning","CTR_313","IHS_YND_307","NOCINC0003076738","Ebo=
go","","14-09-2024 23:56:31","","","Site on Gen due to Grid Outage, site al=
arming on Low fuel// Refueling done","Siligap Boris","Warning","Warning","D=
IESEL","Warning - Refuel","Site on Gen due to Grid Outage, site alarming on=
 Low fuel// Refueling done","ludovic.tchagna@ihstowers.com","13","14-09-202=
4 23:56:31","Sagemcom CMR"
"Closed Complete","Site Down","T1615","IHS_YND_323","NOCINC0003076520","SOA=
 VILLAGE","","14-09-2024 22:48:09","14-09-2024 22:44:55","14-09-2024 23:18:=
17","Grid outage, site went down because Gen stopped due to ""high temp"" a=
larm //He added water and gen manually started","Siligap Boris","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","Grid outage, site went down because Gen stopped due to ""high temp"" ala=
rm //He added water and gen manually started","kamga.virgile@ihstowers.com"=
,"195","14-09-2024 22:48:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003076303","A=
kak-Nkozoa-MTN-IHS","","14-09-2024 21:54:52","14-09-2024 21:45:11","14-09-2=
024 22:09:58","Grid fluctuation , site went down because Gen started and st=
opped due to grid bad voltage,and  rcp  malfunction // He bypassed Grid and=
 started Gen manually","Fabrice Pouakam","Grid Supply","Passive","Grid","Na=
tional Grid - Phase Controller Faulty","Grid fluctuation , site went down b=
ecause Gen started and stopped due to grid bad voltage, and rcp malfunction=
 // He bypassed Grid and started Gen manually","kouoh.jean@ihstowers.com","=
582","14-09-2024 21:54:52","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0003076252","EBO=
M","","14-09-2024 21:44:04","14-09-2024 20:58:52","14-09-2024 21:15:05","Ac=
tive: No power issue, site is on grid with Ubaie=3D52,7V, lionel tchatchoua=
(694693436) from Huawei is informed","Hyemafo Gildas","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: N=
o power issue, site is on grid with Ubaie=3D52,7V, lionel tchatchoua(694693=
436) from Huawei is informed","stephane.nkamwa@ihstowers.com","2712","14-09=
-2024 21:44:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0003075751","Montee-J=
ouvence","","14-09-2024 20:42:40","14-09-2024 20:35:27","14-09-2024 21:23:5=
6","Cascaded Incident from TTO2916650","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site on DG due to grid outage,=
DG stopped due to high Temp alarm //He added water and manually start of DG=
.","system","433","14-09-2024 20:42:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0003075750","Mendong =
vallee","","14-09-2024 20:42:40","14-09-2024 20:35:27","14-09-2024 21:23:56=
","Cascaded Incident from TTO2916650","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site on DG due to grid outage,DG s=
topped due to high Temp alarm //He added water and manually start of DG.","=
system","433","14-09-2024 20:42:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0003075705","M=
endong","IHS_YND_692, IHS_YND_236","14-09-2024 20:39:39","14-09-2024 20:35:=
27","14-09-2024 21:23:56","Site on DG due to grid outage,DG stopped due to =
high Temp alarm //He added water and manually start of DG.","Hyemafo Gildas=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","Site on DG due to grid outage,DG stopped due to high Temp a=
larm //He added water and manually start of DG.","kouoh.jean@ihstowers.com"=
,"253","14-09-2024 20:39:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_527","NOCINC0003075574","Odza II =
OCM","","14-09-2024 20:20:50","14-09-2024 20:04:51","14-09-2024 20:42:02","=
Cascaded Incident from TTO2916470","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site on DG due to grid outage,Dg st=
opped due to fuel shortage //Refueling done.","system","959","14-09-2024 20=
:20:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0003075576","Ekoumdou=
m OCM","","14-09-2024 20:20:50","14-09-2024 20:04:51","14-09-2024 20:42:02"=
,"Cascaded Incident from TTO2916470","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site on DG due to grid outage,Dg =
stopped due to fuel shortage //Refueling done.","system","959","14-09-2024 =
20:20:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003075575","MEHANDAN=
","","14-09-2024 20:20:50","14-09-2024 20:04:51","14-09-2024 20:42:02","Cas=
caded Incident from TTO2916470","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site on DG due to grid outage,Dg stopp=
ed due to fuel shortage //Refueling done.","system","959","14-09-2024 20:20=
:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0003075553","O=
dza-PK10","IHS_YND_527, IHS_YND_528, IHS_YND_291","14-09-2024 20:17:05","14=
-09-2024 20:04:51","14-09-2024 20:42:02","Site on DG due to grid outage,Dg =
stopped due to fuel shortage //Refueling done.","Albran Byorel","Fuel Outag=
e","Passive","Diesel","Diesel Outage","Site on DG due to grid outage,Dg sto=
pped due to fuel shortage //Refueling done.","kouoh.jean@ihstowers.com","73=
5","14-09-2024 20:17:05","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0003075232","NKO=
MEKUI OCM","","14-09-2024 19:21:28","14-09-2024 19:10:16","14-09-2024 19:18=
:12","Grid outage,DG failed to start due to poor batteries backup // Gen st=
arted automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage,DG failed to s=
tart due to poor batteries backup // Gen started automatically","stephane.n=
kamwa@ihstowers.com","673","14-09-2024 19:21:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003075224","F=
ebe Village","","14-09-2024 19:19:27","14-09-2024 19:11:21","14-09-2024 21:=
18:41","Grid outage site went down because Gen failed to started due to Gen=
 card faulty//Gen manually  started ","Mboua Thierry","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel","Grid outage site went down becau=
se Gen failed to started due to Gen card faulty//Gen manually  started ","k=
ouoh.jean@ihstowers.com","487","14-09-2024 19:19:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003075173","MBALNGON=
G LYCEE","","14-09-2024 19:03:30","14-09-2024 18:59:48","14-09-2024 19:07:1=
6","Cascaded Incident from TTO2916029","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage.  Gen started and sto=
pped because Gen  overload(20 KVA,280 A and   poor backup//he reduce load o=
n site and started Gen manually","system","222","14-09-2024 19:03:30","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003075174","Afanoya"=
,"","14-09-2024 19:03:30","14-09-2024 18:59:48","14-09-2024 19:07:16","Casc=
aded Incident from TTO2916029","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage.  Gen started and stopped =
because Gen  overload(20 KVA,280 A and   poor backup//he reduce load on sit=
e and started Gen manually","system","222","14-09-2024 19:03:30","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003075172","ELOUMDEM=
 CARRIERE","","14-09-2024 19:03:30","14-09-2024 18:59:48","14-09-2024 19:07=
:16","Cascaded Incident from TTO2916029","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage.  Gen started and s=
topped because Gen  overload(20 KVA,280 A and   poor backup//he reduce load=
 on site and started Gen manually","system","222","14-09-2024 19:03:30","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003075167","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","14-09-2024 19:02:01","14-09-20=
24 18:59:48","14-09-2024 19:07:16","Grid outage.  Gen started and stopped b=
ecause Gen  overload(20 KVA,280 A and   poor backup//he reduce load on site=
 and started Gen manually","Hyemafo Gildas","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage.  Gen started and stopped because G=
en  overload(20 KVA,280 A and   poor backup//he reduce load on site and sta=
rted Gen manually","stephane.nkamwa@ihstowers.com","134","14-09-2024 19:02:=
01","Sagemcom CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0003074803","ELO=
UMDEM CARRIERE 2","","14-09-2024 17:53:36","14-09-2024 17:16:25","14-09-202=
4 17:20:25","","Fanda Brice","Cascade Outage","Active","Cascade Active","Ca=
scade Active","Active Tx Issue: site on DG,Ubaie:55.2V; Gr=E9goire/654-54-7=
4-79 is informed.","stephane.nkamwa@ihstowers.com","2744","14-09-2024 17:53=
:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003074773","K=
oweit City","","14-09-2024 17:43:20","14-09-2024 16:42:08","14-09-2024 16:5=
0:46","No power issue U:56,2V site on Grid. TX FME Leonel Steve   (65518487=
6) from Huawei is informed, Notice that we have disjunction at BTS OCM ","A=
lbran Byorel","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","No power issue U:56,2V site on Grid. TX FME Leone=
l Steve   (655184876) from Huawei is informed, Notice that we have disjunct=
ion at BTS OCM ","kouoh.jean@ihstowers.com","3672","14-09-2024 17:43:20","S=
agemcom CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0003074761","NTE=
MASSI","","14-09-2024 17:41:38","14-09-2024 17:35:17","14-09-2024 18:45:19"=
,"No power issue U=3D52,4 V site on GEN TX FME Armand Nghetsa (691144412) f=
rom Huawei is informed","Delor Telezing","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue U=3D52,=
4 V site on GEN TX FME Armand Nghetsa (691144412) from Huawei is informed",=
"stephane.nkamwa@ihstowers.com","381","14-09-2024 17:41:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003074691","Ngoum","=
","14-09-2024 17:28:20","14-09-2024 17:16:25","14-09-2024 17:20:25","Cascad=
ed Incident from TTO2915448","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active Tx Issue: site on DG,Ubaie:55.2V; Gr=
=E9goire/654-54-74-79 is informed.","system","715","14-09-2024 17:28:20","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003074690","Matsari"=
,"","14-09-2024 17:28:20","14-09-2024 17:16:25","14-09-2024 17:20:25","Casc=
aded Incident from TTO2915448","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active Tx Issue: site on DG,Ubaie:55.2V; G=
r=E9goire/654-54-74-79 is informed.","system","715","14-09-2024 17:28:20","=
Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0003074686","Yok=
o MTN","IHS_YND_460, IHS_YND_475, IHS_YND_768","14-09-2024 17:27:34","14-09=
-2024 17:16:25","14-09-2024 18:15:46","Active Tx Issue: site on DG,Ubaie:55=
.2V; Gr=E9goire/654-54-74-79 is informed.","Parker Tchoup","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve Tx Issue: site on DG,Ubaie:55.2V; Gr=E9goire/654-54-74-79 is informed.",=
"stephane.nkamwa@ihstowers.com","670","14-09-2024 17:27:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003074579","Ndogbess=
ol","","14-09-2024 17:10:20","14-09-2024 17:01:08","14-09-2024 17:06:08","C=
ascaded Incident from TTO2915305","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,site went down before =
DG start : Poor Batteries Backup //DG started automatically.","system","552=
","14-09-2024 17:10:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003074580","Ngog Map=
ubi","","14-09-2024 17:10:20","14-09-2024 17:01:08","14-09-2024 17:06:08","=
Cascaded Incident from TTO2915305","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down before=
 DG start : Poor Batteries Backup //DG started automatically.","system","55=
2","14-09-2024 17:10:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003074581","Mamb",""=
,"14-09-2024 17:10:20","14-09-2024 17:01:08","14-09-2024 17:06:08","Cascade=
d Incident from TTO2915305","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage,site went down before DG sta=
rt : Poor Batteries Backup //DG started automatically.","system","552","14-=
09-2024 17:10:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_286","IHS_YND_381","NOCINC0003074562","B=
oumnyebel","IHS_EDA_056, IHS_YND_419, IHS_YND_376","14-09-2024 17:09:14","1=
4-09-2024 17:01:08","14-09-2024 17:06:08","Grid outage,site went down befor=
e DG start : Poor Batteries Backup //DG started automatically.","Kemeni Fra=
nklin","Equipment Repair","Passive","Control Panel","Power Cabinet - Batter=
y Low","Grid outage,site went down before DG start : Poor Batteries Backup =
//DG started automatically.","kouoh.jean@ihstowers.com","487","14-09-2024 1=
7:09:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0003074385","E=
mana lycee 2","","14-09-2024 16:38:57","14-09-2024 16:22:44","14-09-2024 17=
:00:50","Grid Outage, site went down because Gen stopped due to ""high temp=
"" alarm //He added water and Gen manually started","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid Outage, site went down because Gen stopped due to ""high temp=
"" alarm //He added water and Gen manually started","kouoh.jean@ihstowers.c=
om","974","14-09-2024 16:38:57","Sagemcom CMR"
"Closed Complete","Site Down","T3180","IHS_YND_253","NOCINC0003074298","Clg=
e-Advantiste","","14-09-2024 16:24:30","14-09-2024 16:04:23","14-09-2024 16=
:56:59","Grid outage,site went down because Gen stopped due to Gen overload=
(15KVA,240A)//Grid power return","MINKA NICOLAS","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Overload","Grid outage,site went down because Gen sto=
pped due to Gen overload(15KVA,240A)//Grid power return","stephane.nkamwa@i=
hstowers.com","1208","14-09-2024 16:24:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0003074204","C=
NR","","14-09-2024 16:08:14","14-09-2024 13:24:03","14-09-2024 18:06:19","G=
rid outage ,site went down because Gen card faulty and Gen injection pump  =
faulty//he repaired the  injection pump  and Gen started manually","Mboua T=
hierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage ,site went down because Gen card faulty and Gen injection pump  fa=
ulty//he repaired the  injection pump  and Gen started manually","kouoh.jea=
n@ihstowers.com","9852","14-09-2024 16:08:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0003074164","M=
imboman-Ecole","","14-09-2024 15:57:01","14-09-2024 14:18:52","14-09-2024 1=
6:41:48","Grid outage, site went down because gen ran till fuel shortage //=
 refueling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diese=
l Outage","Grid outage, site went down because gen ran till fuel shortage /=
/ refueling done","kouoh.jean@ihstowers.com","5890","14-09-2024 15:57:01","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0003074003","Mvog-Eba=
nda","","14-09-2024 15:31:20","14-09-2024 15:19:18","14-09-2024 16:38:18","=
Cascaded Incident from TTO2914620","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage ,Site went down because=
 Gen started and stopped due to Gen overload(12,5 KVA,205A)// he reduce loa=
d ( MTN remained down to decrease the load),Site up at OCM 05:48 PM","syste=
m","722","14-09-2024 15:31:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003074001","A=
bom","IHS_YND_269","14-09-2024 15:30:22","14-09-2024 15:19:18","14-09-2024 =
17:48:18","Grid outage ,Site went down because Gen started and stopped due =
to Gen overload(12,5 KVA,205A)// he reduce load ( MTN remained down to decr=
ease the load),Site up at OCM 05:48                  05:48 PM","Siligap Bor=
is","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage =
,Site went down because Gen started and stopped due to Gen overload(12,5 KV=
A,205A)// he reduce load ( MTN remained down to decrease the load),Site up =
at OCM 05:48 PM","kouoh.jean@ihstowers.com","666","14-09-2024 15:30:22","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003073974","N=
YOM 2 IHS","","14-09-2024 15:24:39","14-09-2024 15:22:27","14-09-2024 15:33=
:37","Grid outage,DG failed to start due to poor batteries backup //Grid re=
stored.","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage,DG failed to start due to poor batt=
eries backup //Grid restored.","kouoh.jean@ihstowers.com","133","14-09-2024=
 15:24:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003073952","A=
kak-Nkozoa-MTN-IHS","","14-09-2024 15:20:20","14-09-2024 14:38:51","14-09-2=
024 16:35:07","Grid outage,Gen failed to start due to grid bad voltage,and =
 rcp  malfunction //He bypassed Grid and started the gen.","Fabrice Pouakam=
","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty",=
"Grid outage,Gen failed to start due to grid bad voltage,and  rcp  malfunct=
ion //he bypassed Grid and started the gen","kouoh.jean@ihstowers.com","249=
0","14-09-2024 15:20:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_561","NOCINC0003073930","FOUGEROL=
E","","14-09-2024 15:16:30","14-09-2024 14:25:54","14-09-2024 16:21:48","Ca=
scaded Incident from TTO2914383","Siligap Boris","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to OCM Circuit Bre=
aker  down (125 A) in the PWC and  OCM Circuit Breaker down in the DC BOX /=
/ Circuits Btreakers put back on( Investigations ongoins)","system","3036",=
"14-09-2024 15:16:30","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003073928","Aha=
la","","14-09-2024 15:16:02","14-09-2024 15:00:04","14-09-2024 16:06:28","G=
rid outage;DG started and stopped because Gen  overload(20 KVA,280 A ) and =
 poor backup//He reduced the load on site and started Gen manually.","Hyema=
fo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage;DG started and stopped because Gen  overload(20 KVA,280 A ) and  poo=
r backup//He reduced the load on site and started Gen manually.","stephane.=
nkamwa@ihstowers.com","1326","14-09-2024 15:16:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0003073820","E=
kie-Elegance","","14-09-2024 14:54:47","14-09-2024 14:36:35","14-09-2024 16=
:03:43","Grid Outage// He deployed MDG 20KVA","Albran Byorel","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage// He dep=
loyed MDG 20KVA","kouoh.jean@ihstowers.com","1093","14-09-2024 14:54:47","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0003073811","N=
gousso-Savana","IHS_YND_561","14-09-2024 14:52:04","14-09-2024 14:25:54","1=
4-09-2024 16:21:48","Site went down due to OCM Circuit Breaker  down (125 A=
) in the PWC and  OCM Circuit Breaker down in the DC BOX // Circuits Btreak=
ers put back on( Investigations ongoins)","Siligap Boris","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site w=
ent down due to OCM Circuit Breaker  down (125 A) in the PWC and  OCM Circu=
it Breaker down in the DC BOX // Circuits Btreakers put back on( Investigat=
ions ongoins)","kouoh.jean@ihstowers.com","1570","14-09-2024 14:52:04","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003073798","I=
mm-Olympique","","14-09-2024 14:48:43","14-09-2024 14:02:15","14-09-2024 14=
:07:26","""Active, No power issue U=3D53,4 V site on Grid. The Tx Fme Eloun=
dou 652586578 of Huawei is informed. ","Paul BIBOUM","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no=
 power issue U=3D3,4 V site on Grid. The Tx Fme Eloundou 652586578 of Huawe=
i is informed.

","kouoh.jean@ihstowers.com","2789","14-09-2024 14:48:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0003073790","M=
ontee-Anne-Rouge","","14-09-2024 14:46:33","14-09-2024 14:01:24","14-09-202=
4 14:05:24","""Active, no power issue U=3D3,4 V site on Grid. The Tx Fme El=
oundou 652586578 of Huawei is informed. ","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power i=
ssue U=3D3,4 V site on Grid. The Tx Fme Eloundou 652586578 of Huawei is inf=
ormed.

","kouoh.jean@ihstowers.com","2710","14-09-2024 14:46:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_050","NOCINC0003073783","Satcom",=
"","14-09-2024 14:45:21","14-09-2024 14:03:01","14-09-2024 19:58:07","Casca=
ded Incident from TTO2914337","Delor Telezing","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, no space to deploy a mobil=
 Gen//, Grid return ","system","2540","14-09-2024 14:45:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_003","NOCINC0003073782","Mercure"=
,"","14-09-2024 14:45:21","14-09-2024 14:03:01","14-09-2024 19:58:07","Casc=
aded Incident from TTO2914337","","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Grid outage, no space to deploy a mobil Gen//, Grid =
return ","system","2540","14-09-2024 14:45:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0003073777","E=
lig-Essono","IHS_YND_003, IHS_YND_050","14-09-2024 14:44:20","14-09-2024 14=
:03:01","14-09-2024 19:58:07","Grid outage, no space to deploy a mobil Gen/=
/, Grid return ","Paul BIBOUM","Grid Supply","Passive","Grid","National Gri=
d - Grid Outage Issue","Grid outage, no space to deploy a mobil Gen//, Grid=
 return ","kouoh.jean@ihstowers.com","2479","14-09-2024 14:44:20","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0003073442","Aba=
ttoir","","14-09-2024 13:57:02","14-09-2024 13:54:56","14-09-2024 14:51:17"=
,"Grid outage,DG failed to start due to ACDG charging alternator faulty //M=
anually start of DG.","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Charging Alternator","Grid outage,DG failed to start due to AC=
DG charging alternator faulty //Manually start of DG.","joelle.ekessi@ihsto=
wers.com","127","14-09-2024 13:57:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0003073275","Eloumdem=
 stade","","14-09-2024 13:30:30","14-09-2024 13:05:28","14-09-2024 14:07:23=
","Cascaded Incident from TTO2913568","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site on SG due to grid outage,DG s=
topped due to Fuel shortage // Refueling done.","system","1502","14-09-2024=
 13:30:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0003073166","T=
alla Monatele","","14-09-2024 13:11:57","14-09-2024 13:04:52","14-09-2024 1=
3:31:14","grid outage,gen failed to start due to grid bad voltage,no rcp//h=
e bypassed grid and started the gen","Parker Tchoup","Grid Supply","Passive=
","Grid","National Grid - Phase Controller Faulty","grid outage,gen failed =
to start due to grid bad voltage,no rcp//he bypassed grid and started the g=
en","emmanuel.ghani@ihstowers.com","425","14-09-2024 13:11:57","Sagemcom CM=
R"
"Cancelled","Warning","T1236","IHS_YND_793","NOCINC0003073159","Eloumdem st=
ade","","14-09-2024 13:09:35","","","","Fanda Brice","","","","","","joelle=
.ekessi@ihstowers.com","231","14-09-2024 13:09:35","Sagemcom CMR"
"Closed Complete","Site Down","T1630","IHS_YND_187","NOCINC0003073147","NTE=
MASSI","","14-09-2024 13:07:00","14-09-2024 11:38:50","14-09-2024 17:20:18"=
,"No power issue on site U=3D52,7v site on gen Synphorien of huawei is info=
rmed","Delor Telezing","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue on site U=3D52,7v site on=
 gen Synphorien of huawei is informed","kombi.samuel@ihstowers.com","5291",=
"14-09-2024 13:07:00","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003073144","Sim=
bock MTN","IHS_YND_793","14-09-2024 13:06:33","14-09-2024 13:05:28","14-09-=
2024 14:07:23","Site on SG due to grid outage,DG stopped due to Fuel shorta=
ge // Refueling done.","Fanda Brice","Fuel Outage","Passive","Diesel","Dies=
el Outage","Site on SG due to grid outage,DG stopped due to Fuel shortage /=
/ Refueling done.","joelle.ekessi@ihstowers.com","65","14-09-2024 13:06:33"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0003072997","N=
guila","","14-09-2024 12:38:47","14-09-2024 12:29:42","14-09-2024 13:00:55"=
,"ACTIVE No power issue Site on Gen with Ubaie:52.6.V; Gen only site  The F=
me tx Gregoire (654547479) from Huawei is informed.","Parker Tchoup","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","ACTIVE No power issue Site on Gen with Ubaie:52.6.V; Gen only site  T=
he Fme tx Gregoire (654547479) from Huawei is informed.","emmanuel.ghani@ih=
stowers.com","546","14-09-2024 12:38:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003072990","K=
oweit City","","14-09-2024 12:37:12","14-09-2024 12:31:04","14-09-2024 16:0=
5:58","Grid fluctuation, site went down because gen failed  to start due to=
 grid bad voltage // Gen started manually","Albran Byorel","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","Grid fluctuation,=
 site went down because gen failed  to start due to grid bad voltage // Gen=
 started manually","emmanuel.ghani@ihstowers.com","368","14-09-2024 12:37:1=
2","Sagemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0003072890","B=
ISCUITERIE","","14-09-2024 12:20:41","14-09-2024 12:12:38","14-09-2024 12:5=
6:08","Grid Fluctuation,site went down before DG start : Poor Batteries bac=
kup  // Gen started automatically.","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid Fluctuation,site we=
nt down before DG start: Poor Batteries backup  // Gen started manally","em=
manuel.ghani@ihstowers.com","484","14-09-2024 12:20:41","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0003072853","Av =
Kennedy","","14-09-2024 12:15:11","14-09-2024 12:12:07","14-09-2024 19:09:5=
4"," Grid outage,no space to deploy a mobil DG,waiting for grid restored//G=
rid returned.","","Grid Supply","Passive","Grid","National Grid - Grid Outa=
ge Issue"," Grid outage,no space to deploy a mobil DG,waiting for grid rest=
ored//Grid returned.","joelle.ekessi@ihstowers.com","186","14-09-2024 12:15=
:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003072770","Lobo OCM=
","","14-09-2024 12:01:22","14-09-2024 11:49:37","14-09-2024 11:57:37","Cas=
caded Incident from TTO2913047","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage,Site went down =
before DG start : Poor Batteries backup//DG started automatically","system"=
,"705","14-09-2024 12:01:22","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003072742","Pha=
rmacie SION","","14-09-2024 11:58:36","14-09-2024 11:55:32","14-09-2024 13:=
01:43","Site was on Gen due to Grid Outage, site went down because Gen stop=
ped due to ""high temp"" alarm //He added water and gen manually start","Pa=
ul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp=
 - Coolant Level Issue","Site was on Gen due to Grid Outage, site went down=
 because Gen stopped due to ""high temp"" alarm //He added water and gen ma=
nually started
","joelle.ekessi@ihstowers.com","185","14-09-2024 11:58:36","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003072716","N=
KOMEKUI OCM","IHS_YND_341","14-09-2024 11:51:42","14-09-2024 11:49:37","14-=
09-2024 11:57:37","Grid outage,Site went down before DG start : Poor Batter=
ies backup//DG started automatically","TIENTCHEU NZETCHIEU GAEL","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge,Site went down before DG start : Poor Batteries backup//DG started autom=
atically","emmanuel.ghani@ihstowers.com","126","14-09-2024 11:51:42","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0003072709","B=
ISCUITERIE","","14-09-2024 11:50:18","14-09-2024 11:45:13","14-09-2024 11:5=
4:13","Grid outage, site down because Gen failed due to poor backup before =
gen start // Grid power return","Paul BIBOUM","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site down becau=
se Gen failed due to poor backup before gen start // Grid power return","em=
manuel.ghani@ihstowers.com","306","14-09-2024 11:50:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0003072690","A=
battoir","","14-09-2024 11:48:32","14-09-2024 11:33:28","14-09-2024 12:03:0=
5","grid outage,gen failed to start due to no charger static on site//he st=
arted the gen with battery backup","Fabrice Pouakam","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Turbo Charger","grid outage,gen failed to start d=
ue to no charger static on site//he started the gen with battery backup","e=
mmanuel.ghani@ihstowers.com","905","14-09-2024 11:48:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003072238","L=
abogenie","","14-09-2024 11:13:25","14-09-2024 11:06:20","14-09-2024 11:19:=
20","grid outage,no space to deploy a mobil gen//grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no sp=
ace to deploy a mobil gen//grid return","emmanuel.ghani@ihstowers.com","426=
","14-09-2024 11:13:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003072165","O=
mnisport-Rail","","14-09-2024 11:11:35","14-09-2024 10:55:26","14-09-2024 1=
2:04:29","attached tis tikect at H-Paradis","Delor Telezing","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","grid outage//MDG 13kva de=
ployed","emmanuel.ghani@ihstowers.com","12229","14-09-2024 11:11:35","Sagem=
com CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0003072079","Ema=
na Lycee","","14-09-2024 11:07:01","14-09-2024 11:05:56","14-09-2024 12:30:=
56","Grid outage  site went down because gen failed to start due to low fue=
l//Refueling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Dies=
el Outage","Grid outage  site went down because gen failed to start due to =
low fuel//Refueling done","joelle.ekessi@ihstowers.com","66","14-09-2024 11=
:07:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0003071993","H=
-Paradis","IHS_YND_506","14-09-2024 10:57:30","14-09-2024 10:55:26","14-09-=
2024 12:04:29","grid outage//MDG 13kva deployed","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","grid outage//MDG 13kva deploye=
d","emmanuel.ghani@ihstowers.com","125","14-09-2024 10:57:30","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0003071865","C=
NR","","14-09-2024 10:53:15","14-09-2024 10:46:10","14-09-2024 12:55:15",""=
,"Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid out=
age  site went down because gen failed to start due to low fuel//Refueling =
done","emmanuel.ghani@ihstowers.com","426","14-09-2024 10:53:15","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003071845","MBALNGON=
G LYCEE","","14-09-2024 10:51:41","14-09-2024 10:48:49","14-09-2024 12:12:2=
9","Cascaded Incident from TTO2912043","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, Site went down becau=
se Gen Overload (20kva,330A)//He reduced the load and started Gen manualy",=
"system","172","14-09-2024 10:51:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003071844","ELOUMDEM=
 CARRIERE","","14-09-2024 10:51:41","14-09-2024 10:48:49","14-09-2024 12:12=
:45","Cascaded Incident from TTO2912043","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, Site went down bec=
ause Gen Overload (20kva,330A)//He reduced the load and started Gen manualy=
","system","172","14-09-2024 10:51:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003071846","Afanoya"=
,"","14-09-2024 10:51:41","14-09-2024 10:48:49","14-09-2024 12:12:45","Casc=
aded Incident from TTO2912043","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, Site went down because Ge=
n Overload (20kva,330A)//He reduced the load and started Gen manualy","syst=
em","172","14-09-2024 10:51:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003071839","E=
lig Edzoa","","14-09-2024 10:51:25","14-09-2024 10:49:11","14-09-2024 10:54=
:11","Grid outage, site down because Gen failed due to poor backup before g=
en start // Grid power return","Delor Telezing","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site down bec=
ause Gen failed due to poor backup before gen start // Grid power return","=
emmanuel.ghani@ihstowers.com","135","14-09-2024 10:51:25","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003071810","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","14-09-2024 10:50:53","14-09-20=
24 10:48:49","14-09-2024 12:12:45","Grid Outage, Site went down because Gen=
 Overload (20kva,330A)//He reduced the load and started Gen manualy","Hyema=
fo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
Outage, Site went down because Gen Overload (20kva,330A)//He reduced the lo=
ad and started Gen manualy","joelle.ekessi@ihstowers.com","125","14-09-2024=
 10:50:53","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0003071789","OBA=
M NGOLA OCM","","14-09-2024 10:49:44","14-09-2024 10:45:57","14-09-2024 10:=
52:49","site went down due to insufficient of rectifier on site//site stabi=
lilzed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","site went down due to insufficient of rectifier on site//site sta=
bililzed","joelle.ekessi@ihstowers.com","227","14-09-2024 10:49:44","Sagemc=
om CMR"
"Closed Complete","Warning","CTR_002","IHS_YND_010","NOCINC0003071588","CNR=
","","14-09-2024 10:35:41","","","Grid outage  site alarming on battery bec=
ause gen failed to start due to low fuel//Refueling done","Mboua Thierry","=
Warning","Warning","POWER","Warning - Site on Battery","Grid outage  site a=
larming on battery because gen failed to start due to low fuel//Refueling d=
one","kombi.samuel@ihstowers.com","2","14-09-2024 10:35:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003071587","E=
mana","","14-09-2024 10:35:37","14-09-2024 10:27:33","14-09-2024 12:34:33",=
"grid outage//grid return","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","grid outage//grid return","emmanuel.ghani@ihstowers.=
com","485","14-09-2024 10:35:37","Sagemcom CMR"
"Closed Complete","Site Down","T2762","IHS_YND_720","NOCINC0003071560","SOA=
 UNIVERSITY STADIUM","","14-09-2024 10:32:23","14-09-2024 10:31:18","14-09-=
2024 10:40:18","grid outage,gen ran till fuel shortage//Refueling done","Si=
ligap Boris","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,=
gen ran till fuel shortage//Refueling done","joelle.ekessi@ihstowers.com","=
66","14-09-2024 10:32:23","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003071514","Eko=
unou","","14-09-2024 10:24:38","14-09-2024 10:20:32","14-09-2024 10:27:32",=
"Grid outage site went down before Gen started due to poor battery back up =
// Grid return","Albran Byorel","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low","Grid outage site went down before Gen star=
ted due to poor battery back up // Grid return","joelle.ekessi@ihstowers.co=
m","247","14-09-2024 10:24:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003071496","M=
EFOU ASSI","","14-09-2024 10:21:05","14-09-2024 10:13:59","14-09-2024 21:54=
:52","Grid Outage, site went down because Gen stopped due to ""high temp"" =
alarm //He added water and gen manually started","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"Grid Outage, site went down because Gen stopped due to ""high temp"" alar=
m //He added water and gen manually started","emmanuel.ghani@ihstowers.com"=
,"427","14-09-2024 10:21:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003071318","B=
iteng","","14-09-2024 10:06:26","14-09-2024 09:57:20","14-09-2024 13:07:45"=
,"Active: No power issue, site is on Grid with U=3D54,4V ,  The TX FME Lion=
el adjep//655184876//  From Huawei is informed","Mba Lazare Herve","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active: No power issue, site is on Grid with U=3D54,4V ,  The TX FME Li=
onel adjep//655184876//  From Huawei is informed","emmanuel.ghani@ihstowers=
.com","547","14-09-2024 10:06:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003071042","N=
yom OCM","","14-09-2024 09:48:24","14-09-2024 09:45:07","14-09-2024 10:39:4=
2","grid outage,gen ran till fuel shortage//Refueling done","Fabrice Pouaka=
m","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran ti=
ll fuel shortage//Refueling done","emmanuel.ghani@ihstowers.com","198","14-=
09-2024 09:48:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0003070976","D=
onga","IHS_YND_444","14-09-2024 09:38:36","14-09-2024 09:34:32","14-09-2024=
 12:00:56","No power issue on site U=3D52,3v hybrid gen gregoire of huawei =
is informed","Parker Tchoup","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52,3v h=
ybrid gen gregoire of huawei is informed","emmanuel.ghani@ihstowers.com","2=
45","14-09-2024 09:38:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0003070970","D=
ong","","14-09-2024 09:37:38","14-09-2024 09:34:32","14-09-2024 10:15:56","=
","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Activ=
e","No power issue on site U=3D52,3v hybrid gen gregoire of huawei is infor=
med","emmanuel.ghani@ihstowers.com","369","14-09-2024 09:37:38","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003070966","A=
kak-Nkozoa-MTN-IHS","","14-09-2024 09:36:20","14-09-2024 09:34:15","14-09-2=
024 11:27:22","site went down because gen failed to start due to grid bad v=
oltage// Gen manually started","Fabrice Pouakam","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","site went down because gen =
failed to start due to grid bad voltage// Gen manually started","emmanuel.g=
hani@ihstowers.com","126","14-09-2024 09:36:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003070786","Etoudi 2=
","","14-09-2024 09:12:00","14-09-2024 09:09:09","14-09-2024 09:39:09","Cas=
caded Incident from TTO2910925","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen failed to start due =
o card Ge faulty//Gen started manually","system","171","14-09-2024 09:12:00=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003070784","Abattoir=
","","14-09-2024 09:12:00","14-09-2024 09:09:09","14-09-2024 09:39:09","Cas=
caded Incident from TTO2910925","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen failed to start due =
o card Ge faulty//Gen started manually","system","171","14-09-2024 09:12:00=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003070785","ETOUDI C=
HAPELLE","","14-09-2024 09:12:00","14-09-2024 09:09:09","14-09-2024 09:39:0=
9","Cascaded Incident from TTO2910925","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage,gen failed to star=
t due o card Ge faulty//Gen started manually","system","171","14-09-2024 09=
:12:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003070782","Y=
de-M-Central","","14-09-2024 09:11:34","14-09-2024 09:07:28","14-09-2024 19=
:25:01",",Grid outage, no space to deploy a mobil gen//grid return ","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue",",Grid outa=
ge, no space to deploy a mobil gen//grid return ","emmanuel.ghani@ihstowers=
.com","247","14-09-2024 09:11:34","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003070777","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","14-09-2024 09:11:14","14-09-2=
024 09:09:09","14-09-2024 09:39:09","grid outage,gen failed to start due to=
 card Ge faulty//Gen started manually","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","grid outage,gen failed to sta=
rt due to card Ge faulty//Gen started manually","joelle.ekessi@ihstowers.co=
m","126","14-09-2024 09:11:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003070744","N=
kolfoulou","","14-09-2024 09:02:39","14-09-2024 09:01:33","14-09-2024 09:04=
:33","Grid outage,DG failed to start due to poor batteries backup //Gen sta=
rted automatically","Siligap Boris","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage,DG failed to start due to =
poor batteries backup //Gen started automatically","emmanuel.ghani@ihstower=
s.com","66","14-09-2024 09:02:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0003070729","T=
ongolo OCM","","14-09-2024 08:58:36","14-09-2024 08:56:31","14-09-2024 08:5=
8:31","Site went down due to PWC OVERLOAD ( 12Kw, 200A) // Site stabilized"=
,"Delor Telezing","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e Overloaded","Site went down due to PWC OVERLOAD ( 12Kw, 200A) // Site sta=
bilized","emmanuel.ghani@ihstowers.com","126","14-09-2024 08:58:36","Sagemc=
om CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003070692","Com=
plex Beac II","","14-09-2024 08:50:20","14-09-2024 08:48:16","14-09-2024 09=
:18:17","grid outage,gen failed to start due to card Ge faulty//Gen started=
 manually","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","grid outage,gen failed to start due to card Ge faulty//Gen =
started manually","joelle.ekessi@ihstowers.com","124","14-09-2024 08:50:20"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003070590","Eto koss=
 Yde","","14-09-2024 08:31:50","14-09-2024 08:29:41","14-09-2024 09:54:28",=
"Cascaded Incident from TTO2910707","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,main gen faulty//MDG 20k=
va deployed","system","129","14-09-2024 08:31:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003070591","ELOUMDEM=
 CARRIERE 2","","14-09-2024 08:31:50","14-09-2024 08:29:41","14-09-2024 09:=
54:28","Cascaded Incident from TTO2910707","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,main gen faulty//=
MDG 20kva deployed","system","129","14-09-2024 08:31:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003070586","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","14-09-2024 08:30:47","14-09-2024 08:=
27:41","14-09-2024 09:54:28","grid outage,main gen faulty//MDG 20kva deploy=
ed","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator=
 Faulty","grid outage,main gen faulty//MDG 20kva deployed","emmanuel.ghani@=
ihstowers.com","187","14-09-2024 08:30:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0003070474","Nkolfoul=
ou 2","","14-09-2024 07:57:01","14-09-2024 07:49:28","14-09-2024 07:56:28",=
"Cascaded Incident from TTO2910552","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e  gen failed tostart due to poor battery backup // Gen automatically start=
ed","system","453","14-09-2024 07:57:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003070475","Melen Ba=
'aba","","14-09-2024 07:57:01","14-09-2024 07:49:28","14-09-2024 07:56:28",=
"Cascaded Incident from TTO2910552","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e  gen failed tostart due to poor battery backup // Gen automatically start=
ed","system","453","14-09-2024 07:57:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003070476","TSINGA V=
ILLAGE 2","","14-09-2024 07:57:01","14-09-2024 07:49:28","14-09-2024 07:56:=
28","Cascaded Incident from TTO2910552","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause  gen failed tostart due to poor battery backup // Gen automatically =
started","system","453","14-09-2024 07:57:01","Sagemcom CMR"
"Closed Complete","Site Down","T2226","IHS_YND_296","NOCINC0003070461","Nko=
lfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","14-09-2024 07:54:34","14-=
09-2024 07:49:28","14-09-2024 07:56:28","Grid outage, site went down becaus=
e  gen failed tostart due to poor battery backup // Gen automatically start=
ed","Siligap Boris","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Battery Low","Grid outage, site went down because  gen failed tostar=
t due to poor battery backup // Gen automatically started","joelle.ekessi@i=
hstowers.com","373","14-09-2024 07:54:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0003070447","Mvog-Man=
ga","","14-09-2024 07:51:30","14-09-2024 07:43:09","14-09-2024 07:45:09","C=
ascaded Incident from TTO2910497","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
 gen failed tostart due to poor battery backup // Gen automatically started=
","system","501","14-09-2024 07:51:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0003070448","Marche O=
dza","","14-09-2024 07:51:30","14-09-2024 07:43:09","14-09-2024 07:45:09","=
Cascaded Incident from TTO2910497","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
  gen failed tostart due to poor battery backup // Gen automatically starte=
d","system","501","14-09-2024 07:51:30","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003070419","Eko=
unou","","14-09-2024 07:46:55","14-09-2024 07:42:50","14-09-2024 07:52:50",=
"Grid outage, site went down because  gen failed tostart due to poor batter=
y backup // Gen automatically started","Albran Byorel","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down because  gen failed tostart due to poor battery backup // Gen auto=
matically started","joelle.ekessi@ihstowers.com","246","14-09-2024 07:46:55=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0003070413","O=
dza","IHS_YND_254, IHS_YND_580","14-09-2024 07:46:22","14-09-2024 07:43:09"=
,"14-09-2024 07:45:09","Grid outage, site went down because  gen failed tos=
tart due to poor battery backup // Gen automatically started","Albran Byore=
l","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid outage, site went down because  gen failed tostart due to poor bat=
tery backup // Gen automatically started","emmanuel.ghani@ihstowers.com","1=
94","14-09-2024 07:46:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003070019","Lobo OCM=
","","14-09-2024 06:22:40","14-09-2024 06:19:49","14-09-2024 06:25:49","Cas=
caded Incident from TTO2910055","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Gen started automatically",=
"system","171","14-09-2024 06:22:41","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003070015","N=
KOMEKUI OCM","IHS_YND_341","14-09-2024 06:21:08","14-09-2024 06:19:49","14-=
09-2024 06:25:49","Grid outage, site went down before gen start due to poor=
 battery backup // Gen started automatically","TIENTCHEU NZETCHIEU GAEL","E=
quipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","G=
rid outage, site went down before gen start due to poor battery backup // G=
en started automatically","emmanuel.ghani@ihstowers.com","80","14-09-2024 0=
6:21:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003069883","E=
lobi Mokolo","","14-09-2024 05:38:56","14-09-2024 05:35:51","14-09-2024 06:=
35:51","No power issue site on grid with U=3D53.4v Mohamadou(691144435) fro=
m Huawei is informed ","Mboua Thierry","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D53.4v Mohamadou(691144435) from Huawei is informed ","ludivine=
.ngamaleu@ihstowers.com","185","14-09-2024 05:38:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003069757","Mambine"=
,"","14-09-2024 05:12:01","14-09-2024 05:00:45","14-09-2024 05:05:45","Casc=
aded Incident from TTO2909738 - Cascade Removed From TTO2909738","Fanda Bri=
ce","Cascade Outage","Active","Cascade Active","Cascade Active","Active// N=
o power issue on site ,site on Grid with Ubaie=3D 52,9V The fme tx Etienne =
fopa // 695033981 of huawei is Working on site","system","676","14-09-2024 =
05:12:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0003069756","Nkenglik=
ok","IHS_YND_367, IHS_YND_350, IHS_YND_349","14-09-2024 05:12:00","14-09-20=
24 05:00:45","14-09-2024 05:35:40","Active// No power issue on site ,site o=
n Grid with Ubaie=3D 52,9V The fme tx Etienne fopa // 695033981 of huawei i=
s Working on site","Kemeni Franklin","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue on=
 site ,site on Grid with Ubaie=3D 52,9V The fme tx Etienne fopa // 69503398=
1 of huawei is Working on site","system","675","14-09-2024 05:12:00","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0003069755","Mandoumb=
a OCM","","14-09-2024 05:12:00","14-09-2024 05:00:45","14-09-2024 05:05:45"=
,"Cascaded Incident from TTO2909738 - Cascade Removed From TTO2909738","Kem=
eni Franklin","Cascade Outage","Active","Cascade Active","Cascade Active","=
Active// No power issue on site ,site on Grid with Ubaie=3D 52,9V The fme t=
x Etienne fopa // 695033981 of huawei is Working on site","system","675","1=
4-09-2024 05:12:00","Sagemcom CMR"
"Closed Complete","Site Down","T0219","IHS_YND_024","NOCINC0003069754","Gar=
bati building","","14-09-2024 05:11:41","14-09-2024 05:02:37","14-09-2024 0=
5:45:37","Active, no power issue U:54V site on Grid. TX FME Armand Nghetsa =
  (691144412) from Huawei is informed","Delor Telezing","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active,=
 no power issue U:54V site on Grid. TX FME Armand Nghetsa   (691144412) fro=
m Huawei is informed","dorothy.djantio@ihstowers.com","545","14-09-2024 05:=
11:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0003069733","N=
kongtock","","14-09-2024 05:08:51","14-09-2024 05:00:45","14-09-2024 05:05:=
45","Active// No power issue on site ,site on Grid with Ubaie=3D 52,9V The =
fme tx Etienne fopa // 695033981 of huawei is Working on site","Kemeni Fran=
klin","Cascade Outage","Active","Cascade Active","Cascade Active","Active//=
 No power issue on site ,site on Grid with Ubaie=3D 52,9V The fme tx Etienn=
e fopa // 695033981 of huawei is Working on site","ludivine.ngamaleu@ihstow=
ers.com","486","14-09-2024 05:08:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0003069586","K=
oweit City","","14-09-2024 04:19:10","14-09-2024 04:15:52","14-09-2024 05:2=
5:52","no power issue U:56,2V site on Grid. TX FME Leonel Steve   (65518487=
6) from Huawei is informed","Albran Byorel","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","no power issue U:56=
,2V site on Grid. TX FME Leonel Steve   (655184876) from Huawei is informed=
","ludivine.ngamaleu@ihstowers.com","199","14-09-2024 04:19:10","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0003069104","OLAMA","=
","14-09-2024 01:12:10","14-09-2024 01:08:36","14-09-2024 01:12:36","Cascad=
ed Incident from TTO2908956","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuation, site went down because ge=
n start and stopped due to grid bad voltage and gen card dysfunction // He =
reset gen card and manually stard the gen","system","214","14-09-2024 01:12=
:10","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003069098","Ako=
no","IHS_YND_687","14-09-2024 01:10:44","14-09-2024 01:08:36","14-09-2024 0=
1:12:36","Grid fluctuation, site went down because gen start and stopped du=
e to grid bad voltage and gen card dysfunction // He reset gen card and man=
ually stard the gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Grid fluctuation, site went down because gen start =
and stopped due to grid bad voltage and gen card dysfunction // He reset ge=
n card and manually stard the gen","dorothy.djantio@ihstowers.com","128","1=
4-09-2024 01:10:44","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_707","NOCINC0003068887","NYOM 2 IHS=
","","13-09-2024 23:56:58","","","Site went alarm due to work Fabrcie /6571=
08613/ Sagemcom is working on site // End of work","Fabrice Pouakam","Warni=
ng","Warning","POWER","Warning - Site on Battery","Site went alarm due to w=
ork Fabrcie /657108613/ Sagemcom is working on site // End of work","etienn=
e.itondo@ihstowers.com","6909","13-09-2024 23:56:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003068551","B=
iteng","","13-09-2024 22:25:35","13-09-2024 22:05:31","14-09-2024 01:18:13"=
,"Active//No power issue, site is on Grid with U=3D54,4V ,  The TX FME Lion=
el adjep//655184876//  From Huawei is informed site up at 09:16 PM","Mba La=
zare Herve","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active//No power issue, site is on Grid with U=3D54=
,4V ,  The TX FME Lionel adjep//655184876//  From Huawei is informed site u=
p at 09:16 PM","ludivine.ngamaleu@ihstowers.com","1205","13-09-2024 22:25:3=
5","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003067962","B=
iteng","","13-09-2024 20:52:40","13-09-2024 20:42:59","13-09-2024 21:05:05"=
,"Active: No power issue, site is on Grid with U=3D54,4V ,  The TX FME Lion=
el adjep//655184876//  From Huawei is informed site up at 09:16 PM","Mba La=
zare Herve","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active: No power issue, site is on Grid with U=3D54=
,4V ,  The TX FME Lionel adjep//655184876//  From Huawei is informed site u=
p at 09:16 PM","alexandre.kamal@ihstowers.com","582","13-09-2024 20:52:40",=
"Sagemcom CMR"
"Closed Complete","Warning","T0476","IHS_YND_163","NOCINC0003067833","Nsam =
Sofavinc","","13-09-2024 20:37:05","","","Grid Fluctuation,site alarming be=
cause Gen failed to start due Grid bad voltage// He started Gen manually","=
MINKA NICOLAS","Warning","Warning","POWER","Warning - Site on Battery","Gri=
d Fluctuation,site alarming because Gen failed to start due Grid bad voltag=
e// He started Gen manually","ludovic.tchagna@ihstowers.com","367","13-09-2=
024 20:37:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003067642","N=
kozoa","","13-09-2024 19:53:54","13-09-2024 19:44:48","13-09-2024 22:27:37"=
,"Grid outage, site went down because Gen start and stopped due to Gen over=
load (20kva 312A) // he reduice the load of site","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went =
down because Gen start and stopped due to Gen overload (20kva 312A) // he r=
eduice the load of site","alexandre.kamal@ihstowers.com","110972","13-09-20=
24 19:53:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003066601","Afanoya"=
,"","13-09-2024 17:43:51","13-09-2024 17:30:22","13-09-2024 17:54:16","Casc=
aded Incident from TTO2906014","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, site went down because Ge=
n failed to start due to battery Gen faulty// Grid Restored","system","809"=
,"13-09-2024 17:43:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003066600","MBALNGON=
G LYCEE","","13-09-2024 17:43:51","13-09-2024 17:30:22","13-09-2024 17:54:1=
6","Cascaded Incident from TTO2906014","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, site went down becau=
se Gen failed to start due to battery Gen faulty// Grid Restored","system",=
"809","13-09-2024 17:43:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003066599","ELOUMDEM=
 CARRIERE","","13-09-2024 17:43:50","13-09-2024 17:30:22","13-09-2024 17:54=
:16","Cascaded Incident from TTO2906014","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, site went down bec=
ause Gen failed to start due to battery Gen faulty// Grid Restored","system=
","808","13-09-2024 17:43:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003066570","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","13-09-2024 17:38:28","13-09-=
2024 17:29:22","13-09-2024 17:54:16","Grid Outage, site went down because G=
en failed to start due to battery Gen faulty// Grid Restored","Hyemafo Gild=
as","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery L=
ow","Grid Outage, site went down because Gen failed to start due to battery=
 Gen faulty// Grid Restored","alexandre.kamal@ihstowers.com","546","13-09-2=
024 17:38:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003066371","A=
KONGO","","13-09-2024 17:16:04","13-09-2024 17:07:58","13-09-2024 17:15:22"=
,"Active:  No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rod=
rigue (655102999)from Huawei is informed. Repetitive issue //site up at 05:=
24 PM","Fanda Brice","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active:  No power issue on site Ubaie=3D52=
,5V site on Gen. The Tx FME Rodrigue (655102999)from Huawei is informed. Re=
petitive issue //site up at 05:24 PM","alexandre.kamal@ihstowers.com","487"=
,"13-09-2024 17:16:04","Sagemcom CMR"
"Closed Complete","Site Down","T1570","IHS_YND_140","NOCINC0003066147","BIS=
CUITERIE","","13-09-2024 16:46:33","13-09-2024 16:28:18","13-09-2024 16:48:=
29","Grid Fluctuation site went down because Gen failed to start due to poo=
r battery backup// Grid stabilized.","Paul BIBOUM","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuation site w=
ent down because Gen failed to start due to poor battery backup// Grid stab=
ilized
","kamga.virgile@ihstowers.com","1096","13-09-2024 16:46:33","Sagemcom CMR"
"Cancelled","Warning","T1557","IHS_YND_313","NOCINC0003065883","Afanoya",""=
,"13-09-2024 16:05:34","","","","Hyemafo Gildas","","","","","","kamga.virg=
ile@ihstowers.com","4457","13-09-2024 16:05:34","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0003065862","Beh=
ind P T school Yde","","13-09-2024 15:59:27","13-09-2024 15:25:09","13-09-2=
024 16:17:47","Eneo CB down, site went down because gen ran till fuel short=
age// He rearmed Eneo CB (Investigation ongoing)","Paul BIBOUM","Fuel Outag=
e","Passive","Diesel","Diesel Outage","Eneo CB down, site went down because=
 gen ran till fuel shortage// He rearmed Eneo CB (Investigation ongoing)","=
kamga.virgile@ihstowers.com","2059","13-09-2024 15:59:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003065722","ELOUMDEM=
 CARRIERE","","13-09-2024 15:39:40","13-09-2024 14:51:30","13-09-2024 15:29=
:40","Cascaded Incident from TTO2904976","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site was on Gen due to Grid out=
age, site went down due to Poor battery backup//Grid power return","system"=
,"2890","13-09-2024 15:39:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003065723","MBALNGON=
G LYCEE","","13-09-2024 15:39:40","13-09-2024 14:51:30","13-09-2024 15:29:4=
0","Cascaded Incident from TTO2904976","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site was on Gen due to Grid outag=
e, site went down due to Poor battery backup//Grid power return","system","=
2890","13-09-2024 15:39:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003065642","A=
hala","IHS_YND_767, IHS_YND_765","13-09-2024 15:23:35","13-09-2024 14:50:30=
","13-09-2024 15:29:40","Site was on Gen due to Grid outage, site went down=
 due to Poor battery backup//Grid power return","Hyemafo Gildas","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Site was =
on Gen due to Grid outage, site went down due to Poor battery backup//Grid =
power return","alexandre.kamal@ihstowers.com","1986","13-09-2024 15:23:35",=
"Sagemcom CMR"
"Cancelled","Warning","T3220","IHS_YND_765","NOCINC0003065621","MBALNGONG L=
YCEE","","13-09-2024 15:19:13","","","","Fanda Brice","","","","","","kamga=
.virgile@ihstowers.com","1641","13-09-2024 15:19:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0003065536","N=
kenglikok","","13-09-2024 15:07:22","13-09-2024 14:57:59","13-09-2024 15:05=
:15","Active// No power issue on site ,site on Grid with Ubaie=3D 53,7V The=
 RM Alain // 691144423 of huawei is informed","Kemeni Franklin","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power issue on site ,site on Grid with Ubaie=3D 53,7V The RM A=
lain // 691144423 of huawei is informed","alexandre.kamal@ihstowers.com","5=
64","13-09-2024 15:07:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003065511","N=
YOM 2 IHS","","13-09-2024 15:06:02","13-09-2024 14:56:49","13-09-2024 15:26=
:26","Site was on Gen due to Grid Outage, site went down because Gen stoppe=
d due to ""high temp"" alarm //He added water and gen manually started","Fa=
brice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine =
Temp - Coolant Level Issue","Site was on Gen due to Grid Outage, site went =
down because Gen stopped due to ""high temp"" alarm //He added water and ge=
n manually started","alexandre.kamal@ihstowers.com","554","13-09-2024 15:06=
:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003065476","M=
EFOU ASSI","","13-09-2024 14:58:55","13-09-2024 14:53:52","13-09-2024 17:31=
:59","Site went down because rectifier disfunctionned//He reset the rectifi=
er","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Distr=
ibution","Site went down because rectifier disfunctionned//He reset the rec=
tifier","alexandre.kamal@ihstowers.com","305","13-09-2024 14:58:55","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003065195","N=
YOM 2 IHS","","13-09-2024 14:01:03","13-09-2024 13:50:56","13-09-2024 14:35=
:49","","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - H=
igh Engine Temp - Coolant Level Issue","site was on gen due to grid outage,=
 gen stopped due to high temp//added water and gen started","kouoh.jean@ihs=
towers.com","608","13-09-2024 14:01:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003064811","M=
IMBOMAN LIBERTE","","13-09-2024 13:02:57","13-09-2024 12:59:00","13-09-2024=
 13:44:46","fme is on the way to site ETA=3D13:30","Mba Lazare Herve","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","site was on gen =
due to grid outage, gen stopped with oil pressure alarm//reset gen card","k=
ouoh.jean@ihstowers.com","238","13-09-2024 13:02:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003064804","M=
imboman-Village","","13-09-2024 13:00:45","13-09-2024 12:54:59","13-09-2024=
 13:48:38","fme is on the way to site ETA=3D14:20","Mba Lazare Herve","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","grid=
 outage, site down before gen start due to poor backup//gen started ","kouo=
h.jean@ihstowers.com","347","13-09-2024 13:00:45","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0003064520","Nko=
l-Mbanda","","13-09-2024 12:16:47","13-09-2024 11:33:37","13-09-2024 13:47:=
07","gen overloaded, ","MINKA NICOLAS","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","grid outage,gen overloaded, //grid return","stephane=
.nkamwa@ihstowers.com","2592","13-09-2024 12:16:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0003064225","E=
TOUDI CHAPELLE","","13-09-2024 11:38:44","13-09-2024 11:17:02","13-09-2024 =
12:36:32","Grid fluctuation site went down because Gen failled to started d=
ue to Grid bad voltage // He bypass the Grid and site on Gen","Delor Telezi=
ng","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid fluctuation site went down because Gen failled to started due to Gr=
id bad voltage // He bypass the Grid and site on Gen","kouoh.jean@ihstowers=
.com","1303","13-09-2024 11:38:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003063879","N=
yom OCM","","13-09-2024 10:27:30","13-09-2024 10:07:18","13-09-2024 11:44:1=
8","Site on DG due to grid bad voltage,DG stopped due to overload // He red=
uiced the load.site on DG","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Site on DG due to grid bad voltage,DG stopped =
due to overload // He reduiced the load.site on DG","kouoh.jean@ihstowers.c=
om","1214","13-09-2024 10:27:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003063854","Etoudi 2=
","","13-09-2024 10:24:10","13-09-2024 10:16:18","13-09-2024 11:22:28","Cas=
caded Incident from TTO2902925","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because the Grid cont=
actor Faulty  // He blocked the Grid contactor manually  and site on Grid",=
"system","472","13-09-2024 10:24:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003063852","Abattoir=
","","13-09-2024 10:24:10","13-09-2024 10:16:18","13-09-2024 11:22:28","Cas=
caded Incident from TTO2902925","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because the Grid cont=
actor Faulty  // He blocked the Grid contactor manually  and site on Grid",=
"system","472","13-09-2024 10:24:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003063853","ETOUDI C=
HAPELLE","","13-09-2024 10:24:10","13-09-2024 10:16:18","13-09-2024 11:16:1=
8","Cascaded Incident from TTO2902925 ","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Cascaded Incident from TTO290=
2925","system","472","13-09-2024 10:24:10","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003063839","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","13-09-2024 10:21:57","13-09-2=
024 10:16:18","13-09-2024 11:22:28","site went down because the Grid contac=
tor Faulty  // He blocked the Grid contactor manually  and site on Grid","F=
abrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue=
","site went down because the Grid contactor Faulty  // He blocked the Grid=
 contactor manually  and site on Grid","stephane.nkamwa@ihstowers.com","340=
","13-09-2024 10:21:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003063749","Mamb",""=
,"13-09-2024 10:07:41","12-09-2024 15:18:51","12-09-2024 15:43:51","Cascade=
d Incident from TTO2902797 - Cascade Removed From TTO2902797","Kemeni Frank=
lin","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Grid Outage, site went down because  Gen failed to start due to poor =
battery backup // Gen started automatically","system","67730","13-09-2024 1=
0:07:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003063669","M=
fou EPC","","13-09-2024 09:49:37","13-09-2024 09:46:22","13-09-2024 10:56:1=
1","fme is on  site ","Mba Lazare Herve","Installation Activity","Passive",=
"Planned Activity","Installation Activity","site down due to swap of Gen by=
 Herve Mba (Sagemcom)//end of work","kouoh.jean@ihstowers.com","196","13-09=
-2024 09:49:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_625","IHS_YND_181","NOCINC0003063359","M=
imboman3","","13-09-2024 08:48:03","13-09-2024 08:40:53","13-09-2024 09:05:=
23","Grid Outage, site went down because Gen stopped with ""high temp"" ala=
rm// He added water and started Gen manualy","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","Grid Outage, site went down because Gen stopped with ""high temp"" alarm=
// He added water and started Gen manualy","kouoh.jean@ihstowers.com","430"=
,"13-09-2024 08:48:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003063070","T=
singa","","13-09-2024 07:32:45","13-09-2024 07:22:33","13-09-2024 07:44:30"=
,"Grid Fluctuation, site went down because  Gen failed to start due to poor=
 battery backup // Grid Power return","Mboua Thierry","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuation, si=
te went down because  Gen failed to start due to poor battery backup // Gri=
d Power return","kouoh.jean@ihstowers.com","613","13-09-2024 07:32:45","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0003063067","E=
SSOS OASIS 1111","","13-09-2024 07:31:58","13-09-2024 06:20:45","13-09-2024=
 06:25:46","Active, no power issue, site on grid with U=3D53.4 V,  The Tx  =
Armand Nguetsa /691144412/  From Huawei is informed","Siligap Boris","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active, no power issue, site on grid with U=3D54V, Armand Nguetsa /69=
1144412/  From Huawei is informed","kouoh.jean@ihstowers.com","4273","13-09=
-2024 07:31:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003063032","N=
kol-Mbanda","","13-09-2024 07:22:21","12-09-2024 22:25:38","13-09-2024 11:2=
7:25","Gen overload (20kva 290A) ","MINKA NICOLAS","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","grid outage, gen overloaded//ocm CB trip=
ped and gen started","kouoh.jean@ihstowers.com","32204","13-09-2024 07:22:2=
1","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003063017","Ess=
os Marche","","13-09-2024 07:16:05","13-09-2024 07:09:50","13-09-2024 07:11=
:17","ACTIVE No power issue on site, site on Grid with Ubaie=3D54V Tx fme A=
rmand Ngeuts/699949553/ from Huawei is Informed","Delor Telezing","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE No power issue on site, site on Grid with Ubaie=3D54V Tx fme Arma=
nd Ngeuts/699949553/ from Huawei is Informed","stephane.nkamwa@ihstowers.co=
m","376","13-09-2024 07:16:05","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003062952","MEF=
OU ASSI","","13-09-2024 06:53:18","13-09-2024 05:00:04","13-09-2024 06:56:4=
5","Site went down beause 05/08 rectifiers  hanging causing by Grid bad vol=
tage//he reset rectifiers ,Site on Grid","Fanda Brice","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down beause 05/08 rectif=
iers  hanging causing by Grid bad voltage//he reset rectifiers ,Site on Gri=
d","stephane.nkamwa@ihstowers.com","7547","13-09-2024 06:53:18","Sagemcom C=
MR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003062835","Nko=
g-Edzen","","13-09-2024 06:06:05","13-09-2024 05:55:55","13-09-2024 06:00:1=
2","No power issue Ubaie=3D52,4V site on Battery ( Hybrid Gen Site ,Start t=
hreshold =3D51 V) The Tx Fme Gregoire( 652070658)from Huawei is informed  "=
,"Parker Tchoup","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue Ubaie=3D52,4V site on Battery (=
 Hybrid Gen Site ,Start threshold =3D51 V) The Tx Fme Gregoire( 652070658)f=
rom Huawei is informed  ","olivier.kwedi@ihstowers.com","610","13-09-2024 0=
6:06:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003062311","ELOUMDEM=
 CARRIERE 2","","13-09-2024 02:52:20","13-09-2024 02:47:59","13-09-2024 04:=
54:04","Cascaded Incident from TTO2901082","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to main gen faulty // grid return","system","261","13-09-2024 02:52:20",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003062310","Eto koss=
 Yde","","13-09-2024 02:52:20","13-09-2024 02:47:59","13-09-2024 04:54:04",=
"Cascaded Incident from TTO2901082","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to m=
ain gen faulty // grid return","system","261","13-09-2024 02:52:20","Sagemc=
om CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003062305","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","13-09-2024 02:50:13","13-09-2024 02:47=
:59","13-09-2024 04:54:04","Grid outage, site went down due to main gen fau=
lty // grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage, site went down due to main gen fault=
y // grid return","olivier.kwedi@ihstowers.com","136","13-09-2024 02:50:13"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0003061524","N=
yom OCM","","12-09-2024 23:18:55","12-09-2024 23:03:35","13-09-2024 03:26:0=
4","Grid outage site went down because Gen started and stopped due to the i=
njection pump blocked//he unblocks the injection pump and site on gen","Fab=
rice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Injectio=
n Pump Calibration","Grid outage site went down because Gen started and sto=
pped due to the injection pump blocked//he unblocks the injection pump and =
site on gen","denis.mballa@ihstowers.com","921","12-09-2024 23:18:55","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003061374","O=
lembe-Terminus","","12-09-2024 22:53:26","12-09-2024 22:29:07","13-09-2024 =
04:28:29","Active: No power issue on site, Ubai =3D 54V on Grid The tx fme =
symphorien /650257151 /  from HUAWEI is informed .Repetitive issue","Fabric=
e Pouakam","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","Active: No power issue on site, Ubai =3D 54V on Grid=
 The tx fme symphorien /650257151 /  from HUAWEI is informed .Repetitive is=
sue","denis.mballa@ihstowers.com","1460","12-09-2024 22:53:26","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0003061357","R=
d-Pt-Express","","12-09-2024 22:48:41","12-09-2024 22:09:26","13-09-2024 07=
:31:39","Grid outage  site no space MDG// GRID power return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage  site =
no space MDG// GRID power return","denis.mballa@ihstowers.com","2356","12-0=
9-2024 22:48:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0003061337","Mambine"=
,"","12-09-2024 22:44:21","12-09-2024 22:33:09","12-09-2024 22:35:25","Casc=
aded Incident from TTO2899956","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active// No power issue on site ,site on Gri=
d with Ubaie=3D 52,9V The fme tx Etienne fopa // 695033981 of huawei is inf=
ormed","system","672","12-09-2024 22:44:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0003061338","Nkongtoc=
k","","12-09-2024 22:44:21","12-09-2024 22:33:09","12-09-2024 22:35:25","Ca=
scaded Incident from TTO2899956","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active// No power issue on site ,site =
on Grid with Ubaie=3D 52,9V The fme tx Etienne fopa // 695033981 of huawei =
is informed","system","672","12-09-2024 22:44:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0003061336","Mandoumb=
a OCM","","12-09-2024 22:44:20","12-09-2024 22:33:09","12-09-2024 22:35:25"=
,"Cascaded Incident from TTO2899956","Kemeni Franklin","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active// No power issue on site ,s=
ite on Grid with Ubaie=3D 52,9V The fme tx Etienne fopa // 695033981 of hua=
wei is informed","system","671","12-09-2024 22:44:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0003061330","N=
kenglikok","IHS_YND_367, IHS_YND_350, IHS_YND_349","12-09-2024 22:43:23","1=
2-09-2024 22:33:09","13-09-2024 04:30:25","Active// No power issue on site =
,site on Grid with Ubaie=3D 52,9V The fme tx Etienne fopa // 695033981 of h=
uawei is informed","Kemeni Franklin","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue on=
 site ,site on Grid with Ubaie=3D 52,9V The fme tx Etienne fopa // 69503398=
1 of huawei is informed","denis.mballa@ihstowers.com","614","12-09-2024 22:=
43:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003061024","MBIMBIM"=
,"","12-09-2024 21:53:22","12-09-2024 21:46:20","13-09-2024 03:50:08","Casc=
aded Incident from TTO2899577 - Cascade Removed From TTO2899577","Parker Tc=
houp","Cascade Outage","Active","Cascade Active","Cascade Active","Active//=
No power issue site on grid with U=3D51.7V // Gregroire  from Huawei is inf=
ormed site up at 10:21 PM Notice that heavy rain on the area","system","422=
","12-09-2024 21:53:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003061026","Ngouetou=
","","12-09-2024 21:53:22","12-09-2024 21:46:20","13-09-2024 03:50:08","Cas=
caded Incident from TTO2899577 - Cascade Removed From TTO2899577","Parker T=
choup","Cascade Outage","Active","Cascade Active","Cascade Active","Active/=
/No power issue site on grid with U=3D51.7V // Gregroire  from Huawei is in=
formed site up at 10:21 PM Notice that heavy rain on the area","system","42=
2","12-09-2024 21:53:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003061025","Matsari"=
,"","12-09-2024 21:53:22","12-09-2024 21:46:20","13-09-2024 03:50:08","Casc=
aded Incident from TTO2899577 - Cascade Removed From TTO2899577","Parker Tc=
houp","Cascade Outage","Active","Cascade Active","Cascade Active","Active//=
No power issue site on grid with U=3D51.7V // Gregroire  from Huawei is inf=
ormed site up at 10:21 PM Notice that heavy rain on the area","system","422=
","12-09-2024 21:53:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003061027","Yoko MTN=
","","12-09-2024 21:53:22","12-09-2024 21:46:20","13-09-2024 03:50:08","Cas=
caded Incident from TTO2899577 - Cascade Removed From TTO2899577","Parker T=
choup","Cascade Outage","Active","Cascade Active","Cascade Active","Active/=
/No power issue site on grid with U=3D51.7V // Gregroire  from Huawei is in=
formed site up at 10:21 PM Notice that heavy rain on the area","system","42=
2","12-09-2024 21:53:22","Sagemcom CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0003061015","Ngo=
um","","12-09-2024 21:51:27","12-09-2024 21:46:20","13-09-2024 03:50:08",""=
,"Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active=
","Active//No power issue site on grid with U=3D51.7V // Gregroire  from Hu=
awei is informed site up at 10:21 PM Notice that heavy rain on the area","d=
orothy.djantio@ihstowers.com","308","12-09-2024 21:51:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003060838","S=
calom-IHS","","12-09-2024 21:28:22","12-09-2024 15:03:14","12-09-2024 15:38=
:38","Grid Outage no space to deploy MDG // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no space t=
o deploy MDG // Grid return","etienne.itondo@ihstowers.com","23110","12-09-=
2024 21:28:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0003060678","C=
hapelle-Nsimeyong","","12-09-2024 20:48:59","12-09-2024 20:32:55","12-09-20=
24 20:33:42","no power issue Ubaie=3D54.4V site on Grid.Mbah hosiah(6740074=
38) from Huawei is informed","MINKA NICOLAS","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue Uba=
ie=3D54.4V site on Grid.Mbah hosiah(674007438) from Huawei is informe","lud=
ivine.ngamaleu@ihstowers.com","965","12-09-2024 20:48:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003060621","T=
amtam Weekend","","12-09-2024 20:40:22","12-09-2024 20:31:14","13-09-2024 0=
0:20:55","Active: No power issue site on Grid with U=3D5,9V The TX FME Mbah=
 Hosiah (674007438) FROM Huawei is informed, Notice that we have disjunctio=
n ar BTS OCM","Hyemafo Gildas","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active: No power issue site on G=
rid with U=3D5,9V The TX FME Mbah Hosiah (674007438) FROM Huawei is informe=
d, Notice that we have disjunction ar BTS OCM","ludivine.ngamaleu@ihstowers=
.com","549","12-09-2024 20:40:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003060587","H=
-Progres","","12-09-2024 20:30:36","12-09-2024 20:24:24","12-09-2024 20:38:=
38","Grid Outage no space to deploy MDG // Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid Outage no space to=
 deploy MDG // Grid return","ludivine.ngamaleu@ihstowers.com","373","12-09-=
2024 20:30:36","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0003060548","Mel=
en Ba'aba","","12-09-2024 20:19:50","12-09-2024 20:14:59","12-09-2024 21:59=
:30","site went down because Gen failed to start due to AVR dysfonction //h=
e adjusted the voltage","Siligap Boris","Equipment Repair","Passive","ACDG =
Gen","ACDG - AVR","site went down because Gen failed to start due to AVR dy=
sfonction //he adjusted the voltage","dorothy.djantio@ihstowers.com","613",=
"12-09-2024 20:19:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0003060541","Mvog-Man=
ga","","12-09-2024 20:19:01","12-09-2024 20:14:59","12-09-2024 20:21:16","C=
ascaded Incident from TTO2898993","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down because =
 gen failed tostart due to poor battery backup // Gen started automaticaly"=
,"system","242","12-09-2024 20:19:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0003060542","Marche O=
dza","","12-09-2024 20:19:01","12-09-2024 20:14:59","12-09-2024 20:21:16","=
Cascaded Incident from TTO2898993","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
  gen failed tostart due to poor battery backup // Gen started automaticaly=
","system","242","12-09-2024 20:19:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0003060535","O=
dza","IHS_YND_254, IHS_YND_580","12-09-2024 20:18:04","12-09-2024 20:14:59"=
,"12-09-2024 20:21:16","Grid outage, site went down because  gen failed tos=
tart due to poor battery backup // Gen started automaticaly","Albran Byorel=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low=
","Grid outage, site went down because  gen failed tostart due to poor batt=
ery backup // Gen started automaticaly","ludivine.ngamaleu@ihstowers.com","=
186","12-09-2024 20:18:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003060525","Donga","=
IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_YND_473","12-09-202=
4 20:15:40","12-09-2024 20:01:41","13-09-2024 03:50:20","Active//No power i=
ssue site on grid with U=3D51.7V // Gregroire  from Huawei is informed site=
 up at 10:21 PM Notice that heavy rain on the area","Parker Tchoup","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue site on grid with U=3D51.7V // Gregroire  from =
Huawei is informed site up at 10:21 PM Notice that heavy rain on the area",=
"system","839","12-09-2024 20:15:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003060526","Dong",""=
,"12-09-2024 20:15:40","12-09-2024 20:01:41","13-09-2024 03:50:47","Cascade=
d Incident from TTO2898981","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","ACTIVE No power issue Site on Gen with U=3D 4=
8.6V Gen only site  The Fme tx Gregoire (654547479) from Huawei is informed=
","system","839","12-09-2024 20:15:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0003060523","N=
guila","IHS_YND_444","12-09-2024 20:14:45","12-09-2024 20:01:41","13-09-202=
4 04:06:26","ACTIVE No power issue Site on Gen with U=3D 48.6V Gen only sit=
e  The Fme tx Gregoire (654547479) from Huawei is informed","Parker Tchoup"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","ACTIVE No power issue Site on Gen with U=3D 48.6V Gen only sit=
e  The Fme tx Gregoire (654547479) from Huawei is informed","ludivine.ngama=
leu@ihstowers.com","785","12-09-2024 20:14:45","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003060389","Nko=
abang Ebolmedjock","","12-09-2024 20:02:59","12-09-2024 19:54:48","12-09-20=
24 21:36:59","site went down due to work Our FME Mba Herve 657108452//Sagem=
com is working on site (Swap Gen ) //end of works.","Mba Lazare Herve","Ins=
tallation Activity","Passive","Planned Activity","Installation Activity","s=
ite went down due to work Our FME Mba Herve 657108452//Sagemcom is working =
on site (Swap Gen ) //end of works.","dorothy.djantio@ihstowers.com","491",=
"12-09-2024 20:02:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0003060334","T=
radex-Nkomo","","12-09-2024 19:56:18","12-09-2024 19:54:13","12-09-2024 19:=
58:13","ACTIVE / No power issue on site Ubaie=3D53,9V site on Grid The TX F=
ME  Lionel steve / 655184876/ From  Huawei is informed ","Albran Byorel","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE / No power issue on site Ubaie=3D53,9V site on Grid The TX=
 FME  Lionel steve / 655184876/ From  Huawei is informed ","ludivine.ngamal=
eu@ihstowers.com","126","12-09-2024 19:56:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003060294","C=
amp-Sic-Tsinga","","12-09-2024 19:47:58","12-09-2024 19:36:53","12-09-2024 =
20:33:28","Grid Outage no space to deploy MDG // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no sp=
ace to deploy MDG // Grid return","ludivine.ngamaleu@ihstowers.com","667","=
12-09-2024 19:47:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003059847","M=
EHANDAN","","12-09-2024 18:57:00","12-09-2024 18:53:48","12-09-2024 20:51:4=
8","Site went down because CB(80A) disjunted in PWC//he change CB with  ano=
ther CB (125 A)","Albran Byorel","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Circuit Breaker Issue","Site went down because CB(80A) =
disjunted in PWC//he change CB with  another CB (125 A)","ludivine.ngamaleu=
@ihstowers.com","194","12-09-2024 18:57:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003059772","Nsimalen=
 OCM","","12-09-2024 18:54:40","12-09-2024 18:39:25","12-09-2024 19:25:23",=
"Cascaded Incident from TTO2898098","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid  outage,site went down becaus=
e Gen started and Stopped with Alarm "" under Frequency""/He reset Gen card=
 and started Gen","system","915","12-09-2024 18:54:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003059754","N=
kolda","IHS_YND_327","12-09-2024 18:53:52","12-09-2024 18:39:25","12-09-202=
4 19:25:23","Grid  outage,site went down because Gen started and Stopped wi=
th Alarm "" under Frequency""/He reset Gen card and started Gen","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
 outage,site went down because Gen started and Stopped with Alarm "" under =
Frequency""/He reset Gen card and started Gen","ludivine.ngamaleu@ihstowers=
.com","868","12-09-2024 18:53:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003059740","N=
kol-Mbanda","","12-09-2024 18:50:28","12-09-2024 17:12:07","12-09-2024 22:2=
5:37","Grid outage, site went down because Gen start and stopped due to Gen=
 overload (20kva 290A) //  Grid Restored","MINKA NICOLAS","Equipment Repair=
","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down becau=
se Gen start and stopped due to Gen overload (20kva 290A) //  Grid Restored=
","etienne.itondo@ihstowers.com","5902","12-09-2024 18:50:28","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0003059725","B=
iteng-Maetur","","12-09-2024 18:46:34","12-09-2024 18:37:59","12-09-2024 19=
:58:59","Grid outage, site went down because gen  started and stoppet with =
 alarm 'Low oil pressure(Unprouven alarm)  //He reset Gen card and started =
Gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Con=
trol Panel","Grid outage, site went down because gen  started and stoppet w=
ith  alarm 'Low oil pressure(Unprouven alarm)  //He reset Gen card and star=
ted Gen","ludivine.ngamaleu@ihstowers.com","516","12-09-2024 18:46:34","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003059721","N=
kol-Mbanda","","12-09-2024 18:43:03","12-09-2024 15:49:38","12-09-2024 16:4=
6:10","Grid outage, site went down because Gen start and stopped due to Gen=
 overload (20kva 290A) // Grid Restored","MINKA NICOLAS","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down becaus=
e Gen start and stopped due to Gen overload (20kva 290A) // Grid Restored",=
"etienne.itondo@ihstowers.com","10406","12-09-2024 18:43:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003059623","ELOUMDEM=
 CARRIERE 2","","12-09-2024 18:18:11","12-09-2024 18:12:26","12-09-2024 18:=
16:48","Cascaded Incident from TTO2897930","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to main gen faulty // grid return","system","345","12-09-2024 18:18:11",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003059622","Eto koss=
 Yde","","12-09-2024 18:18:10","12-09-2024 18:12:26","12-09-2024 18:16:48",=
"Cascaded Incident from TTO2897930","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to m=
ain gen faulty // grid return","system","344","12-09-2024 18:18:10","Sagemc=
om CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003059619","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","12-09-2024 18:16:34","12-09-2024 18:12=
:26","12-09-2024 18:32:07","Grid outage, site went down due to main gen fau=
lty // grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Battery","Grid outage, site went down due to main gen faul=
ty // grid return","dorothy.djantio@ihstowers.com","249","12-09-2024 18:16:=
34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0003059379","M=
ontee-Anne-Rouge","","12-09-2024 17:48:24","12-09-2024 17:41:17","12-09-202=
4 19:54:09","Grid Outage no space to deploy MDG //Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no s=
pace to deploy MDG waitting Grid return","ludivine.ngamaleu@ihstowers.com",=
"428","12-09-2024 17:48:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0003059264","N=
simalen OCM","","12-09-2024 17:28:23","12-09-2024 16:49:13","12-09-2024 17:=
50:44","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","Grid  outage,site went down because Gen started and Stopped =
with Alarm "" under Frequency""/He reset Gen card and started Gen","ludivin=
e.ngamaleu@ihstowers.com","2351","12-09-2024 17:28:23","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0003059232","Acc=
acia New","","12-09-2024 17:22:02","12-09-2024 14:32:56","12-09-2024 15:44:=
38","Grid outage// He deployed MDG 20KVA","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid outage// He deployed MDG 20KVA",=
"dorothy.djantio@ihstowers.com","10148","12-09-2024 17:22:02","Sagemcom CMR=
"
"Closed Complete","Site Down","T0050","IHS_YND_039","NOCINC0003059034","Sia=
ntou Radio TV","","12-09-2024 16:53:53","12-09-2024 16:37:49","12-09-2024 1=
9:56:09","Grid Outage no space to deploy MDG //Grid retun","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no space=
 to deploy MDG //Grid retun","dorothy.djantio@ihstowers.com","965","12-09-2=
024 16:53:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003059001","N=
kolda","IHS_YND_327","12-09-2024 16:52:03","12-09-2024 16:49:13","12-09-202=
4 17:50:44","Grid  outage,site went down because Gen started and Stopped wi=
th Alarm "" under Frequency""/He reset Gen card and started Gen","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
 outage,site went down because Gen started and Stopped with Alarm "" under =
Frequency""/He reset Gen card and started Gen","ludivine.ngamaleu@ihstowers=
.com","2464","12-09-2024 16:52:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003058828","N=
sam Sofavinc T0","","12-09-2024 16:42:51","12-09-2024 16:34:46","12-09-2024=
 21:07:02","Grid outage, site went down because Gen start and stopped due t=
o Gen overload (09kva ,160A) //  Grid power return","MINKA NICOLAS","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went =
down because Gen start and stopped due to Gen overload (09kva ,160A) //  Gr=
id power return","ludivine.ngamaleu@ihstowers.com","485","12-09-2024 16:42:=
51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0003058562","A=
KONGO","","12-09-2024 16:03:12","12-09-2024 15:53:59","12-09-2024 15:55:19"=
," No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rodrigue (6=
55102999)from Huawei is informed. Repetitive issue ","Fanda Brice","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m"," No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rodrigue =
(655102999)from Huawei is informed. Repetitive issue ","ludivine.ngamaleu@i=
hstowers.com","555","12-09-2024 16:03:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003058544","N=
kozoa","","12-09-2024 15:59:50","12-09-2024 15:28:45","12-09-2024 15:38:08"=
,"Grid outage, site went down because Gen start and stopped due to Gen over=
load (20kva 312A) // he reduice the load of site ","Fabrice Pouakam","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went=
 down because Gen start and stopped due to Gen overload (20kva 312A) // he =
reduice the load of site ","ludivine.ngamaleu@ihstowers.com","41205","12-09=
-2024 15:59:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003058540","M=
ontee-Jouvence-II","","12-09-2024 15:58:26","12-09-2024 15:50:11","12-09-20=
24 16:36:18","Active: No power issue site on Grid with U=3D53.5V The TX FME=
 Mbah Hosiah (674007438) FROM Huawei is informed ","Hyemafo Gildas","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: No power issue site on Grid with U=3D53.5V The TX FME Mbah Hos=
iah (674007438) FROM Huawei is informed ","ludivine.ngamaleu@ihstowers.com"=
,"496","12-09-2024 15:58:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_286","IHS_YND_381","NOCINC0003058465","B=
oumnyebel","","12-09-2024 15:45:08","12-09-2024 15:38:04","12-09-2024 15:44=
:04","Grid outage, site went down before gen start due to poor battery back=
up // gen start automatically","Kemeni Franklin","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // gen start automatically",=
"ludivine.ngamaleu@ihstowers.com","425","12-09-2024 15:45:08","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0003058250","B=
iyemassi LAC","","12-09-2024 15:20:28","12-09-2024 15:04:24","12-09-2024 22=
:13:26","Grid Outage No Space to Deploy a MDG // Grid Restored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No =
Space to Deploy a MDG // Grid Restored","ludivine.ngamaleu@ihstowers.com","=
965","12-09-2024 15:20:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003058225","T=
singa","","12-09-2024 15:15:23","12-09-2024 15:03:17","12-09-2024 15:29:17"=
,"Grid Outage, site went down because  Gen  start due to poor battery backu=
p // Grid Power return","Mboua Thierry","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid Outage, site went down becaus=
e  Gen  start due to poor battery backup // Grid Power return","ludivine.ng=
amaleu@ihstowers.com","727","12-09-2024 15:15:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003057904","B=
ATA-Mokolo","","12-09-2024 14:56:53","12-09-2024 14:54:49","12-09-2024 20:2=
9:43","Grid Outage no space to deploy MDG //Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no space t=
o deploy MDG //Grid return","ludivine.ngamaleu@ihstowers.com","125","12-09-=
2024 14:56:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003057898","Anguissa=
 New","","12-09-2024 14:55:00","12-09-2024 10:48:00","12-09-2024 13:28:51",=
"Cascaded Incident from TTO2894147","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,no space to deploy a m=
obile DG,waiting for grid restored//Grid restored.","system","14820","12-09=
-2024 14:55:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_044","NOCINC0003057891","Polytech=
nique","","12-09-2024 14:53:30","12-09-2024 11:41:02","12-09-2024 12:32:52"=
,"Cascaded Incident from TTO2894597","","Cascade Outage","Active","Cascade =
Active","Cascade Active","Active// No power Issue Site on Battery  Ubaie =
=3D48.9V, The FME Tx The TX FME Mbah Hosiah (674007438) is informed, Notice=
 that we have disjunction at BTS OCM","system","11548","12-09-2024 14:53:30=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003057776","N=
komkana","","12-09-2024 14:42:46","12-09-2024 14:29:41","12-09-2024 15:21:1=
0","Grid Outage no space to deploy MDG // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid Outage no space to =
deploy MDG // Grid return","ludivine.ngamaleu@ihstowers.com","786","12-09-2=
024 14:42:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0003057653","B=
astos Ekoudou","","12-09-2024 14:24:58","12-09-2024 14:19:48","12-09-2024 1=
5:24:17","Grid outage, site went down before gen start due to poor battery =
backup // gen start automatically","Mboua Thierry","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen start due to poor battery backup // gen start automatically=
","ludivine.ngamaleu@ihstowers.com","311","12-09-2024 14:24:58","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003057578","E=
mombo-Tchad","","12-09-2024 14:09:53","12-09-2024 13:54:32","12-09-2024 19:=
54:32","Grid Outage no free mobil gen to deploy // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no =
free mobil gen to deploy // Grid return","kamga.virgile@ihstowers.com","922=
","12-09-2024 14:09:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003057575","M=
aison-Blanche-IHS","","12-09-2024 14:09:25","12-09-2024 14:04:14","12-09-20=
24 19:39:50","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage =
No Space to deploy a MDG//Grid Restored","ludivine.ngamaleu@ihstowers.com",=
"312","12-09-2024 14:09:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0003057573","K=
ondengui","","12-09-2024 14:08:13","12-09-2024 13:54:00","12-09-2024 13:55:=
44","Active//No Power Issue site on Grid with Ubaie=3D54,6V  Eloundou//6515=
59985 from Huawei is informed","Albran Byorel","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No Power=
 Issue site on Grid with Ubaie=3D54,6V  Eloundou//651559985 from Huawei is =
informed","kamga.virgile@ihstowers.com","854","12-09-2024 14:08:13","Sagemc=
om CMR"
"Cancelled","Warning","","IHS_YND_568","NOCINC0003057563","Anguissa New",""=
,"12-09-2024 14:06:20","","","Cascaded Incident from TTO2895589 - Cascade R=
emoved From TTO2895589","MINKA NICOLAS","","","","","","system","5855","12-=
09-2024 14:06:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_008","IHS_YND_068","NOCINC0003057560","N=
disamba","","12-09-2024 14:05:01","12-09-2024 12:28:45","07-04-2025 11:47:0=
3","Access issue due to Landlord (RM,SRM, OCM are informed)","MINKA NICOLAS=
","Access Denial","Lease Or Legal","Landlord Related Issues","Access Issue =
- Land Lord","Access issue due to landlord","kamga.virgile@ihstowers.com","=
5777","12-09-2024 14:05:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003057447","A=
kak-Nkozoa-MTN-IHS","","12-09-2024 13:46:15","12-09-2024 13:43:00","12-09-2=
024 13:45:17","No power isue site on grid with U=3D54v Symphorien(650257151=
) from Huawei is informed ","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power isue sit=
e on grid with U=3D54v Symphorien(650257151) from Huawei is informed ","kam=
ga.virgile@ihstowers.com","196","12-09-2024 13:46:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003057409","M=
imboman-Village","","12-09-2024 13:41:26","12-09-2024 13:23:52","12-09-2024=
 21:18:38","Active//No power issue on site ,site on GRid with U=3D54V The F=
ME TX Eloundou // 693212405 from HUAWEI is informed","Mba Lazare Herve","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active: no power issue on site ,site on GRid with U=3D54V The FME =
TX Eloundou // 693212405 from HUAWEI is informed","kamga.virgile@ihstowers.=
com","1055","12-09-2024 13:41:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003057390","E=
lig-Edzoa","","12-09-2024 13:36:26","12-09-2024 13:02:17","12-09-2024 14:17=
:54","Grid outage// He deployed MDG 20KVA","","Grid Supply","Passive","Grid=
","National Grid - Grid Outage Issue","Grid outage// He deployed MDG 20KVA"=
,"kamga.virgile@ihstowers.com","2051","12-09-2024 13:36:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003057380","I=
mm-Olympique","","12-09-2024 13:35:20","12-09-2024 12:58:09","12-09-2024 14=
:02:09","Grid outage,gen failed to start due to power cable alimented Gen t=
heft on sites// he Replaced the power Cable and Manually Started the Gen ",=
"Paul BIBOUM","Site Asset Theft","Theft","Theft","DC Cable Stolen","Grid ou=
tage,gen failed to start due to power cable alimented Gen theft on sites// =
he Replaced the power Cable and Manually Started the Gen ","kamga.virgile@i=
hstowers.com","2232","12-09-2024 13:35:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0003057157","E=
kounou","","12-09-2024 13:12:39","12-09-2024 12:57:29","12-09-2024 13:54:29=
","Grid fluctuation site went down because Gen faled to start due to NO RCP=
 on site // Grid Restored","Albran Byorel","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","Grid fluctuation site went down b=
ecause Gen faled to start due to NO RCP on site // Grid Restored","kamga.vi=
rgile@ihstowers.com","911","12-09-2024 13:12:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003057072","E=
kombitie","","12-09-2024 13:05:10","12-09-2024 12:44:00","12-09-2024 13:08:=
28","Site on DG due to grid outage,DG stopped due to Belt cut //He remplace=
d belt cut and manually start of DG.","Fabrice Pouakam","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Fan Belt","Site on DG due to grid outage,DG st=
opped due to Belt cut //He remplaced belt cut and manually start of DG.","k=
amga.virgile@ihstowers.com","1271","12-09-2024 13:05:10","Sagemcom CMR"
"Cancelled","Warning","CTR_035","IHS_YND_055","NOCINC0003057053","Olezoa OC=
M","","12-09-2024 13:00:49","","","Grid outage, No space to deploy MDG wait=
ing Grid return","","","","","","","kamga.virgile@ihstowers.com","1760","12=
-09-2024 13:00:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0003056947","S=
calom-IHS","","12-09-2024 12:48:58","12-09-2024 12:09:38","12-09-2024 13:00=
:46","Grid outage,No space to deploy mobile Gen//Grid Restored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,No =
space to deploy mobile Gen//Grid Restored","kamga.virgile@ihstowers.com","2=
362","12-09-2024 12:48:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003056935","N=
kol-Mbanda","","12-09-2024 12:46:56","12-09-2024 12:07:25","12-09-2024 13:0=
7:38","Grid outage, site went down because Gen start and stopped due to Gen=
 overload (20kva 290A) // Grid Restored","MINKA NICOLAS","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down becaus=
e Gen start and stopped due to Gen overload (20kva 290A) // Grid Restored",=
"kamga.virgile@ihstowers.com","2371","12-09-2024 12:46:56","Sagemcom CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0003056893","Eko=
umdoum OCM","","12-09-2024 12:40:49","12-09-2024 12:25:38","12-09-2024 13:1=
8:08","Grid outage, site went down because gen stoppet with 'Low oil pressu=
re' alarm // He added oil and manually start the gen","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage, sit=
e went down because gen stoppet with 'Low oil pressure' alarm // He added o=
il and manually start the gen","stephane.nkamwa@ihstowers.com","1928","12-0=
9-2024 12:40:49","Sagemcom CMR"
"Closed Complete","Warning","CTR_320","IHS_YND_282","NOCINC0003056620","Mey=
o","","12-09-2024 12:00:58","","","site on alarm due to grid outage//gen st=
arted and alarm cleared","Hyemafo Gildas","Warning","Warning","POWER","Warn=
ing - Site on Battery","site on alarm due to grid outage//gen started and a=
larm cleared","ludovic.tchagna@ihstowers.com","448","12-09-2024 12:00:58","=
Sagemcom CMR"
"Cancelled","Warning","CTR_128","IHS_YND_044","NOCINC0003056609","Polytechn=
ique","","12-09-2024 11:59:18","","","","","","","","","","kamga.virgile@ih=
stowers.com","1089","12-09-2024 11:59:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_447","IHS_YND_061","NOCINC0003056600","Y=
de University","IHS_YND_044","12-09-2024 11:57:23","12-09-2024 11:41:02","1=
2-09-2024 11:45:52","Active// No power Issue Site on Battery  Ubaie =3D48.9=
V, The FME Tx The TX FME Mbah Hosiah (674007438) is informed, Notice that w=
e have disjunction at BTS OCM","Paul BIBOUM","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power =
Issue Site on Battery  Ubaie =3D48.9V, The FME Tx The TX FME Mbah Hosiah (6=
74007438) is informed, Notice that we have disjunction at BTS OCM","kamga.v=
irgile@ihstowers.com","982","12-09-2024 11:57:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0003056568","Mbankolo=
 petit paris","","12-09-2024 11:51:53","12-09-2024 11:44:39","12-09-2024 12=
:20:02","Cascaded Incident from TTO2894517","Mboua Thierry","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage,DG failed to s=
tart due to alarm Digital input (ACDG control panel dysfunctioning) //Reset=
 DG card and manually start of DG.","system","434","12-09-2024 11:51:53","S=
agemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0003056555","AFE=
ME NORD","IHS_YND_808","12-09-2024 11:49:56","12-09-2024 11:44:39","12-09-2=
024 12:24:43","Grid outage,DG failed to start due to alarm Digital input (A=
CDG control panel dysfunctioning) //Reset DG card and manually start of DG.=
","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG =
- Control Panel","Grid outage,DG failed to start due to alarm Digital input=
 (ACDG control panel dysfunctioning) //Reset DG card and manually start of =
DG.","stephane.nkamwa@ihstowers.com","318","12-09-2024 11:49:56","Sagemcom =
CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0003056546","Acc=
acia New","","12-09-2024 11:48:16","12-09-2024 11:40:08","12-09-2024 11:50:=
07","Grid outage// He deployed MDG 20KVA","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid outage// He deployed MDG 20KVA",=
"stephane.nkamwa@ihstowers.com","489","12-09-2024 11:48:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0003056492","R=
d-Pt-Express","","12-09-2024 11:45:55","12-09-2024 11:25:40","12-09-2024 12=
:59:04","grid outage, no space for a MDG//grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","grid outage, no space fo=
r a MDG//grid return","kamga.virgile@ihstowers.com","1216","12-09-2024 11:4=
5:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0003056310","C=
NR","","12-09-2024 11:42:05","12-09-2024 11:02:54","12-09-2024 12:45:50","G=
rid outage site went down because Gen failed to started due to Gen card fau=
lty//Gen manually  started ","Mboua Thierry","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen fa=
iled to started due to Gen card faulty//Gen manually  started ","kamga.virg=
ile@ihstowers.com","2352","12-09-2024 11:42:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0003056295","T=
amtam Weekend","","12-09-2024 11:40:39","12-09-2024 10:57:20","12-09-2024 1=
1:00:10","Active: No power issue site on Grid with U=3D5,9V The TX FME Mbah=
 Hosiah (674007438) FROM Huawei is informed, Notice that we have disjunctio=
n ar BTS OCM","Hyemafo Gildas","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active: No power issue site on G=
rid with U=3D5,9V The TX FME Mbah Hosiah (674007438) FROM Huawei is informe=
d, Notice that we have disjunction ar BTS OCM","kamga.virgile@ihstowers.com=
","2600","12-09-2024 11:40:39","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0003056271","UPA=
C LP","","12-09-2024 11:37:47","12-09-2024 11:35:40","12-09-2024 12:51:18",=
"Grid outage,no space to deploy a mobile DG //grid restored.","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no sp=
ace to deploy a mobile DG //grid restored.","stephane.nkamwa@ihstowers.com"=
,"128","12-09-2024 11:37:47","Sagemcom CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0003056262","Clu=
b France","","12-09-2024 11:35:51","12-09-2024 11:31:24","12-09-2024 12:59:=
39","Grid outage //Grid restored.","","Grid Supply","Passive","Grid","Natio=
nal Grid - Grid Outage Issue","Grid outage //Grid restored.","stephane.nkam=
wa@ihstowers.com","268","12-09-2024 11:35:51","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0003056159","Com=
plex Beac II","","12-09-2024 11:22:30","12-09-2024 11:16:24","12-09-2024 11=
:34:46","Grid outage,DG failed to start due to ACDG control panel faulty //=
Manually start of DG.","Albran Byorel","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage,DG failed to start due to ACDG cont=
rol panel faulty //Manually start of DG.","stephane.nkamwa@ihstowers.com","=
367","12-09-2024 11:22:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003056148","L=
abogenie","IHS_YND_568","12-09-2024 11:20:25","12-09-2024 10:48:00","12-09-=
2024 13:28:51","Grid outage,no space to deploy a mobile DG,waiting for grid=
 restored//Grid restored.","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","Grid outage,no space to deploy a mobile DG,waiting f=
or grid restored//Grid restored.","kamga.virgile@ihstowers.com","1946","12-=
09-2024 11:20:25","Sagemcom CMR"
"Cancelled","Warning","CTR_478","IHS_YND_568","NOCINC0003056043","Anguissa =
New","","12-09-2024 11:00:06","","","","MINKA NICOLAS","","","","","","kamg=
a.virgile@ihstowers.com","616","12-09-2024 11:00:06","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0003056034","Sap=
eur Mimboman","","12-09-2024 10:58:37","12-09-2024 10:53:29","12-09-2024 11=
:45:14","Site went down due to Power  cable MTN  burned in the DC box//He f=
ixed the cable,site on DG.","Mba Lazare Herve","Equipment Repair","Passive"=
,"Infrastructure","Armoured Cable","Site went down due to Power  cable MTN =
 burned in the DC box//He fixed the cable,site on DG.","stephane.nkamwa@ihs=
towers.com","309","12-09-2024 10:58:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003055906","N=
kol-Mbanda","","12-09-2024 10:41:03","12-09-2024 10:31:38","12-09-2024 11:0=
3:36","site was on gen gen due to grid outage, site down because gen stoppe=
d due to high temp (20KVA, 300A)//added water ","MINKA NICOLAS","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","site was on gen gen due to grid outage, site down because gen stopped du=
e to high temp (20KVA, 300A)//added water ","kamga.virgile@ihstowers.com","=
566","12-09-2024 10:41:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0003055889","M=
ontee-Jouvence-II","","12-09-2024 10:38:20","12-09-2024 10:30:49","12-09-20=
24 10:35:02","Active: No power issue site on Grid with U=3D53V The TX FME M=
bah Hosiah (674007438) FROM Huawei is informed","Hyemafo Gildas","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active: No power issue site on Grid with U=3D53V The TX FME Mbah Hosiah (=
674007438) FROM Huawei is informed","kamga.virgile@ihstowers.com","452","12=
-09-2024 10:38:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003055753","Y=
de-M-Central","","12-09-2024 10:18:53","12-09-2024 10:07:44","12-09-2024 13=
:03:24","Grid outage,no space to deploy a mobile DG,waiting for grid restor=
ed//Grid restored.","","Grid Supply","Passive","Grid","National Grid - Grid=
 Outage Issue","Grid outage,no space to deploy a mobile DG,waiting for grid=
 restored//Grid restored.","kamga.virgile@ihstowers.com","670","12-09-2024 =
10:18:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003055605","N=
koabang","","12-09-2024 09:53:26","12-09-2024 09:17:13","12-09-2024 09:30:4=
9","ACTIVE No power issue Gen site U=3D51,4V The Tx fme  Lionel Adjep /6551=
84876 from huawei is informed","Mba Lazare Herve","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No pow=
er issue Gen site U=3D51,4V The Tx fme  Lionel Adjep /655184876 from huawei=
 is informed","kamga.virgile@ihstowers.com","2174","12-09-2024 09:53:26","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_546","IHS_YND_419","NOCINC0003055333","N=
gog Mapubi","","12-09-2024 09:35:33","12-09-2024 08:48:11","12-09-2024 09:3=
9:09","Active// No power issue on site ,site on Gen with Ubaie=3D 54,6V The=
 fme tx Etienne fopa // 695033981 of huawei is informed and Up at 09:39 AM"=
,"Kemeni Franklin","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active// No power issue on site ,site on Gen=
 with Ubaie=3D 54,6V The fme tx Etienne fopa // 695033981 of huawei is info=
rmed and Up at 09:39 AM","kamga.virgile@ihstowers.com","2842","12-09-2024 0=
9:35:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003055270","S=
atcom","","12-09-2024 09:20:53","12-09-2024 09:02:42","12-09-2024 09:10:28"=
,"ACTIVE No power issue on site, site on Gen with Ubaie=3D52,1V Tx fme Arma=
nd Ngeuts/699949553/ from Huawei is Informed","Delor Telezing","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
ACTIVE No power issue on site, site on Gen with Ubaie=3D52,1V Tx fme Armand=
 Ngeuts/699949553/ from Huawei is Informed","kamga.virgile@ihstowers.com","=
1091","12-09-2024 09:20:53","Sagemcom CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0003055114","Biy=
emassi LAC","","12-09-2024 08:32:33","12-09-2024 08:23:26","12-09-2024 13:0=
1:23","Grid outage,no space to deploy a mobile DG,waiting for grid restored=
.","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid Outage no space to deploy MDG //Grid return","stephane.nkamwa@ihstowers=
.com","778","12-09-2024 08:32:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_069","NOCINC0003055107","Efoulan =
MTN","","12-09-2024 08:30:37","12-09-2024 08:25:23","12-09-2024 08:57:24","=
Site was on Gen due to Grid Outage, site went down because Gen stopped due =
to ""high temp"" alarm //He added water and gen manually started","MINKA NI=
COLAS","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - C=
oolant Level Issue","Site was on Gen due to Grid Outage, site went down bec=
ause Gen stopped due to ""high temp"" alarm //He added water and gen manual=
ly started","stephane.nkamwa@ihstowers.com","315","12-09-2024 08:30:37","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0819","IHS_YND_518","NOCINC0003055072","Mon=
tee-Jouvence-II","","12-09-2024 08:22:04","12-09-2024 08:14:59","12-09-2024=
 08:34:12","Grid outage, Gen started and stopped due to overload(15KVA, 195=
A) // he reduced the load","Hyemafo Gildas","Equipment Repair","Passive","A=
CDG Gen","ACDG - Overload","Grid outage, Gen started and stopped due to ove=
rload(15KVA, 195A) // he reduced the load","stephane.nkamwa@ihstowers.com",=
"912","12-09-2024 08:22:04","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0003055016","Men=
dong vallee","","12-09-2024 08:16:09","12-09-2024 07:59:18","12-09-2024 09:=
03:28","Grid outage Site went down because Gen ran untill fuel shortage // =
refueling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage Site went down because Gen ran untill fuel shortage // ref=
ueling done","stephane.nkamwa@ihstowers.com","1012","12-09-2024 08:16:09","=
Sagemcom CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0003054848","Efo=
ulan MTN","","12-09-2024 07:47:39","12-09-2024 07:40:28","12-09-2024 07:52:=
37","Grid Outage , site down because Gen Failed to start due to glow plugs =
faulty//He started Gen started","MINKA NICOLAS","Equipment Repair","Passive=
","ACDG Gen","ACDG - Kick Starter","Grid Outage , site down because Gen Fai=
led to start due to glow plugs faulty//He started Gen started","stephane.nk=
amwa@ihstowers.com","432","12-09-2024 07:47:39","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003054794","AWA=
E OCM","","12-09-2024 07:35:11","12-09-2024 07:29:03","12-09-2024 09:04:50"=
,"Grid Outage, site went down because Gen stopped due to ""high temp"" alar=
m //He added water and gen manually started","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue=
","Grid Outage, site went down because Gen stopped due to ""high temp"" ala=
rm //He added water and gen manually started","stephane.nkamwa@ihstowers.co=
m","457","12-09-2024 07:35:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003054783","M=
ini-Ferme","","12-09-2024 07:34:21","12-09-2024 07:26:11","12-09-2024 12:59=
:10","Grid outage,no space to deploy a mobile DG,waiting for grid restored/=
/Grid restored","","Grid Supply","Passive","Grid","National Grid - Grid Out=
age Issue","Grid outage,no space to deploy a mobile DG,waiting for grid res=
tored//Grid restored","kamga.virgile@ihstowers.com","490","12-09-2024 07:34=
:21","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003054772","Ess=
os Marche","","12-09-2024 07:31:26","12-09-2024 07:28:20","12-09-2024 07:29=
:28","ACTIVE No power issue on site, site on Grid with Ubaie=3D54V Tx fme A=
rmand Ngeuts/699949553/ from Huawei is Informed","Delor Telezing","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE No power issue on site, site on Grid with Ubaie=3D54V Tx fme Arma=
nd Ngeuts/699949553/ from Huawei is Informed","stephane.nkamwa@ihstowers.co=
m","187","12-09-2024 07:31:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003054734","N=
kolndongo","","12-09-2024 07:25:15","12-09-2024 06:46:53","12-09-2024 08:45=
:04","Grid Outage, Site went down because Main Gen Faulty// He deployed MDG=
 20 KVA","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Ge=
nerator Faulty","Grid Outage, Site went down because Main Gen Faulty// He d=
eployed MDG 20 KVA","kamga.virgile@ihstowers.com","2303","12-09-2024 07:25:=
15","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0003054706","An-=
Marche-Melen","","12-09-2024 07:17:46","12-09-2024 06:59:41","12-09-2024 13=
:01:34","Grid outage,no space to deploy a mobile DG,waiting for grid restor=
ed.","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid Outage no space to deploy MDG //Grid return","stephane.nkamwa@ihstowe=
rs.com","1672","12-09-2024 07:17:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003054645","S=
tade-Abega","","12-09-2024 07:04:53","12-09-2024 06:45:33","12-09-2024 08:4=
8:25","Grid Outage , site down because Gen Failed to start due to preheatin=
g relay faulty//He started Gen started","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Kick Starter","Grid Outage , site down beca=
use Gen Failed to start due to preheating relay faulty//He started Gen star=
ted","kamga.virgile@ihstowers.com","1161","12-09-2024 07:04:53","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0003054598","E=
SSOS OASIS 1111","","12-09-2024 06:49:15","12-09-2024 06:13:03","12-09-2024=
 06:25:15","ACTIVE No power issue on site, site on Grid with Ubaie=3D53,4V =
Tx fme Armand Ngeuts/699949553/ from Huawei is Informed","Siligap Boris","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE No power issue on site, site on Grid with Ubaie=3D53,4V Tx=
 fme Armand Ngeuts/699949553/ from Huawei is Informed","kamga.virgile@ihsto=
wers.com","2173","12-09-2024 06:49:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0003054572","Scalom-I=
HS","","12-09-2024 06:38:20","12-09-2024 06:24:18","12-09-2024 11:30:06","C=
ascaded Incident from TTO2892421","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage// He deployed MDG 20KVA","system","84=
2","12-09-2024 06:38:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0003054568","A=
ccacia New","IHS_YND_505","12-09-2024 06:35:29","12-09-2024 06:24:18","12-0=
9-2024 11:37:40","Grid outage// He deployed MDG 20KVA","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage// He deploye=
d MDG 20KVA","kamga.virgile@ihstowers.com","672","12-09-2024 06:35:29","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0003054546","Nkolanga=
a","","12-09-2024 06:24:50","12-09-2024 06:07:01","12-09-2024 06:59:59","Ca=
scaded Incident from TTO2892386","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, gen start and stopped=
 due to alarm emergency button stop//he bypassed the button, reset card and=
 started Gen","system","1069","12-09-2024 06:24:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0003054545","Nkoulou =
Carriere carrefourt","","12-09-2024 06:24:50","12-09-2024 06:07:01","12-09-=
2024 06:59:59","Cascaded Incident from TTO2892386","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage, gen=
 start and stopped due to alarm emergency button stop//he bypassed the butt=
on, reset card and started Gen","system","1069","12-09-2024 06:24:50","Sage=
mcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0003054538","Aba=
ng","IHS_YND_794, IHS_YND_289","12-09-2024 06:22:13","12-09-2024 06:05:01",=
"12-09-2024 06:59:59","Grid outage, gen start and stopped due to alarm emer=
gency button stop//he bypassed the button, reset card and started Gen","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pane=
l","Grid outage, gen start and stopped due to alarm emergency button stop//=
he bypassed the button, reset card and started Gen","stephane.nkamwa@ihstow=
ers.com","1749","12-09-2024 06:22:13","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003054451","Nsi=
meyong Shell","","12-09-2024 05:50:58","12-09-2024 05:48:54","12-09-2024 05=
:54:55","Grid Outage, site went down because  Gen failed to start due to po=
or battery backup // Grid Power return","MINKA NICOLAS","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, site =
went down because  Gen failed to start due to poor battery backup // Grid P=
ower return","joelle.ekessi@ihstowers.com","125","12-09-2024 05:50:58","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0003054443","O=
bobogo","","12-09-2024 05:49:26","12-09-2024 05:47:20","12-09-2024 05:56:59=
","Grid Outage, site went down because  Gen failed to start due to poor bat=
tery backup // Gen started automatically","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, sit=
e went down because  Gen failed to start due to poor battery backup // Gen =
started automatically","emmanuel.ghani@ihstowers.com","127","12-09-2024 05:=
49:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003054420","ELOUMDEM=
 CARRIERE 2","","12-09-2024 05:43:30","12-09-2024 05:40:40","12-09-2024 06:=
54:39","Cascaded Incident from TTO2892248","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid  outage,Main DG overload=
  // Mobile DG Deploy 20KVA but OCM remained down Waiting Grid return.","sy=
stem","170","12-09-2024 05:43:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003054419","Eto koss=
 Yde","","12-09-2024 05:43:30","12-09-2024 05:40:40","12-09-2024 06:54:39",=
"Cascaded Incident from TTO2892248","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid  outage,Main DG overload  // Mo=
bile DG Deploy 20KVA but OCM remained down Waiting Grid return.","system","=
170","12-09-2024 05:43:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003054409","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","12-09-2024 05:38:58","12-09-2024 05:=
37:40","12-09-2024 10:48:41","Grid  outage,Main DG overload  // Mobile DG D=
eploy 20KVA but OCM remained down Waiting Grid return.","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Overload","Grid  outage,Main DG =
overload  // Mobile DG Deploy 20KVA but OCM remained down Waiting Grid retu=
rn.","emmanuel.ghani@ihstowers.com","79","12-09-2024 05:38:58","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003054366","N=
sam Sofavinc T0","","12-09-2024 05:23:52","12-09-2024 04:34:30","12-09-2024=
 06:15:36","Grid outage ,Site went down because Gen started and stopped due=
 to Gen ovreload(9kva ,150 A)//Grid Power return","MINKA NICOLAS","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage ,Site went do=
wn because Gen started and stopped due to Gen ovreload(9kva ,150 A)//Grid P=
ower return","kombi.samuel@ihstowers.com","2962","12-09-2024 05:23:52","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0003054172","AWAE OCM=
","","12-09-2024 04:30:11","12-09-2024 04:24:33","12-09-2024 04:35:33","Cas=
caded Incident from TTO2891909","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site down before Gen t=
o start due to poor backup before //Gen started automatically","system","33=
8","12-09-2024 04:30:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0003054173","Biteng-M=
aetur","","12-09-2024 04:30:11","12-09-2024 04:24:33","12-09-2024 04:35:33"=
,"Cascaded Incident from TTO2891909","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site down before =
Gen to start due to poor backup before //Gen started automatically","system=
","338","12-09-2024 04:30:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0003054171","Tradex-N=
komo","","12-09-2024 04:30:11","12-09-2024 04:24:33","12-09-2024 04:35:33",=
"Cascaded Incident from TTO2891909","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down before Gen =
to start due to poor backup before //Gen started automatically","system","3=
38","12-09-2024 04:30:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0003054170","Bitoto",=
"","12-09-2024 04:30:10","12-09-2024 04:24:33","12-09-2024 04:35:33","Casca=
ded Incident from TTO2891909","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site down before Gen to =
start due to poor backup before //Gen started automatically","system","337"=
,"12-09-2024 04:30:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003054136","B=
iteng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_249","12-09-2024 04:=
25:50","12-09-2024 04:24:33","12-09-2024 04:35:33","Grid outage, site down =
before Gen to start due to poor backup before //Gen started automatically",=
"Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Battery Low","Grid outage, site down before Gen to start due to poor =
backup before //Gen started automatically","emmanuel.ghani@ihstowers.com","=
78","12-09-2024 04:25:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003053991","Mamb",""=
,"12-09-2024 03:25:40","12-09-2024 03:22:00","12-09-2024 03:27:00","Cascade=
d Incident from TTO2891732","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid Outage, site went down because  Gen=
 failed to start due to poor battery backup // Grid Power return","system",=
"220","12-09-2024 03:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003053990","Boumnyeb=
el","","12-09-2024 03:25:40","12-09-2024 03:22:00","12-09-2024 03:27:00","C=
ascaded Incident from TTO2891732","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage, site went down becaus=
e  Gen failed to start due to poor battery backup // Grid Power return","sy=
stem","220","12-09-2024 03:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003053988","Ndogbess=
ol","","12-09-2024 03:25:40","12-09-2024 03:22:00","12-09-2024 03:27:00","C=
ascaded Incident from TTO2891732","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage, site went down becaus=
e  Gen failed to start due to poor battery backup // Grid Power return","sy=
stem","220","12-09-2024 03:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003053989","Ngog Map=
ubi","","12-09-2024 03:25:40","12-09-2024 03:22:00","12-09-2024 03:27:00","=
Cascaded Incident from TTO2891732","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, site went down becau=
se  Gen failed to start due to poor battery backup // Grid Power return","s=
ystem","220","12-09-2024 03:25:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0003053984","B=
oumnyebel OCM","IHS_EDA_056, IHS_YND_419, IHS_YND_381, IHS_YND_376","12-09-=
2024 03:24:06","12-09-2024 03:22:00","12-09-2024 03:27:00","Grid Outage, si=
te went down because  Gen failed to start due to poor battery backup // Gri=
d Power return","Kemeni Franklin","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid Outage, site went down because  Gen=
 failed to start due to poor battery backup // Grid Power return","emmanuel=
.ghani@ihstowers.com","127","12-09-2024 03:24:06","Sagemcom CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0003053162","Mim=
boman","","11-09-2024 23:30:01","11-09-2024 23:28:57","12-09-2024 00:00:56"=
,"site went down because gen start and stopped due to oil leak in oil senso=
r//he added 1,5L and started the gen","Mba Lazare Herve","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Oil Leakage","site went down because gen star=
t and stopped due to oil leak in oil sensor//he added 1,5L and started the =
gen","joelle.ekessi@ihstowers.com","65","11-09-2024 23:30:01","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003053112","Boumnyeb=
el","","11-09-2024 23:23:11","11-09-2024 23:19:24","11-09-2024 23:23:24","C=
ascaded Incident from TTO2890687","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e  gen failed to start due to poor battery backup // Gen started automatica=
lly","system","227","11-09-2024 23:23:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003053111","Ngog Map=
ubi","","11-09-2024 23:23:11","11-09-2024 23:19:24","11-09-2024 23:23:24","=
Cascaded Incident from TTO2890687","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se  gen failed to start due to poor battery backup // Gen started automatic=
ally","system","227","11-09-2024 23:23:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0003053109","Mom","",=
"11-09-2024 23:23:11","11-09-2024 23:19:24","11-09-2024 23:23:24","Grid Out=
age, Site went down because Gen failed to start due Solenoid valve faulty//=
 He started Gen manually","Fanda Brice","Equipment Repair","Passive","ACDG =
Gen","ACDG - Solenoid Coil","Grid Outage, Site went down because Gen failed=
 to start due Solenoid valve faulty// He started Gen manually","system","22=
7","11-09-2024 23:23:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003053113","Mamb",""=
,"11-09-2024 23:23:11","11-09-2024 23:19:24","11-09-2024 23:23:24","Cascade=
d Incident from TTO2890687","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down because  gen=
 failed to start due to poor battery backup // Gen started automatically","=
system","227","11-09-2024 23:23:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003053110","Ndogbess=
ol","","11-09-2024 23:23:11","11-09-2024 23:19:24","11-09-2024 23:23:24","C=
ascaded Incident from TTO2890687","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e  gen failed to start due to poor battery backup // Gen started automatica=
lly","system","227","11-09-2024 23:23:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0003053095","B=
oumnyebel OCM","IHS_EDA_056, IHS_YND_419, IHS_YND_381, IHS_YND_376","11-09-=
2024 23:20:28","11-09-2024 23:19:24","11-09-2024 23:23:24","Grid outage, si=
te went down because  gen failed to start due to poor battery backup // Gen=
 started automatically","Kemeni Franklin","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down beca=
use  gen failed to start due to poor battery backup // Gen started automati=
cally","emmanuel.ghani@ihstowers.com","65","11-09-2024 23:20:28","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003052935","F=
ebe Village","","11-09-2024 22:50:41","11-09-2024 22:49:36","12-09-2024 10:=
45:45","issuficient of rectifier on site","Mboua Thierry","Equipment Repair=
","Passive","Rectifier","Rectifier Module","site down due to 1/3 rectifer f=
aulty//removed a faulty rectifier and added 2 new rectifiers","emmanuel.gha=
ni@ihstowers.com","66","11-09-2024 22:50:41","Sagemcom CMR"
"Closed Complete","Site Down","T0920","IHS_YND_416","NOCINC0003052445","Ngw=
opi Boga","","11-09-2024 21:30:26","11-09-2024 21:27:17","11-09-2024 21:57:=
17","No power issue on site U=3D54,5v site on grid Yanick mbah of huawei is=
 informed","Kemeni Franklin","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,5v s=
ite on grid Yanick mbah of huawei is informed","olivier.kwedi@ihstowers.com=
","190","11-09-2024 21:30:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0003052089","N=
YOM 2 IHS","","11-09-2024 20:37:56","11-09-2024 20:02:36","11-09-2024 21:51=
:36","site went down due to CB 2*63A disjuncted in Pwc//he did a bridge wit=
h another CB 63A","Fabrice Pouakam","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Circuit Breaker Issue","site went down due to CB 2*6=
3A disjuncted in Pwc//he did a bridge with another CB 63A","denis.mballa@ih=
stowers.com","2121","11-09-2024 20:37:56","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0003051855","Nko=
lbong","","11-09-2024 20:05:35","11-09-2024 19:58:19","12-09-2024 08:25:27"=
,"No power issue on site site on Grid  with  U=3D52,7 V  The TX FME Synphor=
ien //691316854// from Huawei is informed,Site up at 08:06 PM","Delor Telez=
ing","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue on site site on Grid  with  U=3D52,7 V  The=
 TX FME Synphorien //691316854// from Huawei is informed,Site up at 08:06 P=
M","olivier.kwedi@ihstowers.com","436","11-09-2024 20:05:35","Sagemcom CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0003051724","Mba=
lla 4","","11-09-2024 19:46:33","11-09-2024 19:42:21","11-09-2024 20:13:57"=
,"ACTIVE No power issue on site, site on Grid with Ubaie=3D54,3V Tx fme Arm=
and Ngeuts/699949553/ from Huawei is Informed","Delor Telezing","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"ACTIVE No power issue on site, site on Grid with Ubaie=3D54,3V Tx fme Arma=
nd Ngeuts/699949553/ from Huawei is Informed","olivier.kwedi@ihstowers.com"=
,"252","11-09-2024 19:46:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_526","NOCINC0003051683","Nkoabang=
2","","11-09-2024 19:39:01","11-09-2024 19:31:06","11-09-2024 19:35:32","Ca=
scaded Incident from TTO2888999","Mba Lazare Herve","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
56.7v Lionnel Steeve(655184876) from Huawei is informed ","system","475","1=
1-09-2024 19:39:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0003051682","NGONA","=
","11-09-2024 19:39:00","11-09-2024 19:31:06","11-09-2024 19:35:32","Cascad=
ed Incident from TTO2888999","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on grid with U=3D56.7=
v Lionnel Steeve(655184876) from Huawei is informed ","system","474","11-09=
-2024 19:39:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0003051665","N=
koabang","IHS_YND_295, IHS_YND_526","11-09-2024 19:37:19","11-09-2024 19:31=
:06","11-09-2024 19:35:32","No power issue site on grid with U=3D56.7v Lion=
nel Steeve(655184876) from Huawei is informed ","Mba Lazare Herve","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue site on grid with U=3D56.7v Lionnel Steeve(655184876) fr=
om Huawei is informed ","denis.mballa@ihstowers.com","374","11-09-2024 19:3=
7:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0003051651","Mvog-Eba=
nda","","11-09-2024 19:34:02","11-09-2024 19:15:48","11-09-2024 20:25:44","=
Cascaded Incident from TTO2888967","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down because=
  gen failed tostart due to poor battery backup and dysjonction in the Dcbo=
x ocm// Grid power return","system","1094","11-09-2024 19:34:02","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0003051638","A=
bom","IHS_YND_269","11-09-2024 19:33:02","11-09-2024 19:15:48","11-09-2024 =
20:25:44","Grid outage, site went down because  gen failed tostart due to p=
oor battery backup and dysjonction in the Dcbox ocm// Grid power return","S=
iligap Boris","Equipment Repair","Passive","Control Panel","Power Cabinet -=
 Battery Low","Grid outage, site went down because  gen failed tostart due =
to poor battery backup and dysjonction in the Dcbox ocm// Grid power return=
","denis.mballa@ihstowers.com","1035","11-09-2024 19:33:02","Sagemcom CMR"
"Closed Complete","Site Down","T0341","IHS_YND_270","NOCINC0003051637","San=
ta Barbara Yde","","11-09-2024 19:32:49","11-09-2024 19:28:12","11-09-2024 =
20:43:49","ACTIVE No power issue on site, site on Grid with Ubaie=3D54,3V T=
x fme Armand Ngeuts/699949553/ from Huawei is Informed","Delor Telezing","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE No power issue on site, site on Grid with Ubaie=3D54,3V Tx=
 fme Armand Ngeuts/699949553/ from Huawei is Informed
","olivier.kwedi@ihstowers.com","278","11-09-2024 19:32:49","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003051589","ODZ=
A MINKAN EDIBI ASSI","","11-09-2024 19:25:08","11-09-2024 19:06:58","11-09-=
2024 20:06:59","Grid outage, site went down because gen ran untill fuel sho=
rtage // refueling done","Albran Byorel","Fuel Outage","Passive","Diesel","=
Diesel Outage","Grid outage, site went down because gen ran untill fuel sho=
rtage // refueling done","olivier.kwedi@ihstowers.com","1091","11-09-2024 1=
9:25:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003051577","ETOUDI C=
HAPELLE","","11-09-2024 19:23:30","11-09-2024 19:03:21","11-09-2024 20:15:0=
9","Cascaded Incident from TTO2888881","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen failed to started due to Gen card faulty//Gen manually  started ",=
"system","1209","11-09-2024 19:23:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003051578","Etoudi 2=
","","11-09-2024 19:23:30","11-09-2024 19:03:21","11-09-2024 20:15:09","Cas=
caded Incident from TTO2888881","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to started due to Gen card faulty//Gen manually  started ","syste=
m","1209","11-09-2024 19:23:30","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003051568","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","11-09-2024 19:20:41","11-09-2=
024 19:03:21","11-09-2024 20:15:09","Grid outage site went down because Gen=
 failed to started due to Gen card faulty//Gen manually  started ","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","G=
rid outage site went down because Gen failed to started due to Gen card fau=
lty//Gen manually  started ","olivier.kwedi@ihstowers.com","1040","11-09-20=
24 19:20:41","Sagemcom CMR"
"Closed Complete","Site Down","T1864","IHS_YND_244","NOCINC0003051539","Aba=
ttoir","","11-09-2024 19:17:29","11-09-2024 19:03:21","11-09-2024 20:15:09"=
,"Grid outage site went down because Gen failed to started due to Gen card =
faulty//Gen manually  started ","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to started due to Gen card faulty//Gen manually  started ","olivi=
er.kwedi@ihstowers.com","1130","11-09-2024 19:17:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_273","IHS_YND_214","NOCINC0003051477","N=
kolmesseng-II","","11-09-2024 19:09:36","11-09-2024 18:44:18","11-09-2024 2=
0:38:12","site went down because the CB (125A) tripped  in PWC //he reamed =
the Cb","Siligap Boris","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Circuit Breaker Issue","site went down because the CB (125A) tri=
pped  in PWC //he reamed the Cb","denis.mballa@ihstowers.com","1519","11-09=
-2024 19:09:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003051335","M=
fou EPC","","11-09-2024 19:00:36","11-09-2024 18:54:14","11-09-2024 20:52:4=
3","site went down because Gen started due to disjonction of GEN CB(63A) //=
 he reamed the gen cb","Mba Lazare Herve","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","site went down because=
 Gen started due to disjonction of GEN CB(63A) // he reamed the gen cb","de=
nis.mballa@ihstowers.com","383","11-09-2024 19:00:36","Sagemcom CMR"
"Closed Complete","Site Down","T1832","IHS_YND_216","NOCINC0003051334","Ele=
veur","","11-09-2024 19:00:20","11-09-2024 18:49:54","11-09-2024 19:57:23",=
"site went down because Gen started due to disjonction of GEN CB(32A) // he=
 reamed the gen cb","Siligap Boris","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Circuit Breaker Issue","site went down because Gen s=
tarted due to disjonction of GEN CB(32A) // he reamed the gen cb","olivier.=
kwedi@ihstowers.com","731","11-09-2024 19:00:20","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0003050495","Beh=
ind P T school Yde","","11-09-2024 17:04:26","11-09-2024 16:57:07","11-09-2=
024 17:52:07","site went down because gen failed to start due to diesel cir=
cuit deconnected//he reconnected it and started the gen","Paul BIBOUM","Fue=
l Outage (Probable)","Passive","Diesel","Fuel Line Issue","site went down b=
ecause gen failed to start due to diesel circuit deconnected//he reconnecte=
d it and started the gen","olivier.kwedi@ihstowers.com","440","11-09-2024 1=
7:04:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0003050364","E=
kombitie","","11-09-2024 16:42:17","11-09-2024 16:34:04","11-09-2024 18:32:=
27","Grid outage  site went down Gen stopped to start because  grid return =
and Grid contactor did not excited// He excited grid contactor","Fabrice Po=
uakam","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","Gri=
d outage  site went down Gen stopped to start because  grid return and Grid=
 contactor did not excited// He excited grid contactor","denis.mballa@ihsto=
wers.com","494","11-09-2024 16:42:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003050312","O=
lembe-Terminus","","11-09-2024 16:31:43","11-09-2024 16:01:27","11-09-2024 =
17:37:30","Grid outage ,Site went down because Gen started and stopped with=
 alarm""emergency stop""(alarm unprouven)//He reset Gen card and Gen mauall=
y started","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG =
- Control Panel","Grid outage ,Site went down because Gen started and stopp=
ed with alarm""emergency stop""(alarm unprouven)//He reset Gen card and Gen=
 maually started","denis.mballa@ihstowers.com","1817","11-09-2024 16:31:43"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0003050056","M=
elen Ba'aba","","11-09-2024 16:05:09","11-09-2024 15:59:52","11-09-2024 16:=
26:39","Site was on gen, site went down because gen ran untill fuel shortag=
e // refueling done","Siligap Boris","Fuel Outage","Passive","Diesel","Dies=
el Outage","Site was on gen, site went down because gen ran untill fuel sho=
rtage // refueling done","denis.mballa@ihstowers.com","319","11-09-2024 16:=
05:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003050033","N=
kozoa","","11-09-2024 16:00:23","11-09-2024 15:55:03","11-09-2024 16:34:09"=
,"Grid ooutage site went down because  Gen overload (20 KVA,312 A)// We red=
uce load and gen manually started ","Fabrice Pouakam","Equipment Repair","P=
assive","ACDG Gen","ACDG - Overload","Grid ooutage site went down because  =
Gen overload (20 KVA,312 A)// We reduce load and gen manually started ","de=
nis.mballa@ihstowers.com","321","11-09-2024 16:00:23","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0003049840","Av =
Kennedy","","11-09-2024 15:33:43","11-09-2024 15:29:33","11-09-2024 17:59:2=
3","Grid Outage no space to deploy MDG // Grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid Outage no space to =
deploy MDG // Grid return","olivier.kwedi@ihstowers.com","251","11-09-2024 =
15:33:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003049697","F=
ebe Village","","11-09-2024 15:08:06","11-09-2024 15:00:52","11-09-2024 16:=
52:05","site went down due to work  by Thierry Mboua/Sagemcom/657108452/ wo=
rking on site(normalization of ATS)//End of work","Mboua Thierry","Installa=
tion Activity","Passive","Planned Activity","Installation Activity","site w=
ent down due to work  by Thierry Mboua/Sagemcom/657108452/ working on site(=
normalization of ATS)//End of work","denis.mballa@ihstowers.com","435","11-=
09-2024 15:08:06","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003049570","Pha=
rmacie SION","","11-09-2024 14:44:18","11-09-2024 14:34:12","11-09-2024 14:=
45:33","Grid outage site went down before Gen started due to poor battery b=
ack up // Gen started automatically","Paul BIBOUM","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage site went d=
own before Gen started due to poor battery back up // Gen started automatic=
ally","olivier.kwedi@ihstowers.com","607","11-09-2024 14:44:18","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0003049491","C=
NR","","11-09-2024 14:28:34","11-09-2024 14:24:22","11-09-2024 14:58:43","G=
rid outage.gen failed to start due to card GE dysfunctionned //we reset car=
d GE and gen manually started ","Mboua Thierry","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to start due to=
 card GE dysfunctionned //we reset card GE and gen manually started ","deni=
s.mballa@ihstowers.com","253","11-09-2024 14:28:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003049329","A=
kak-Nkozoa-MTN-IHS","","11-09-2024 14:03:35","11-09-2024 13:57:28","11-09-2=
024 14:12:05","site went down because the CB (125A) tripped  in PWC due to =
Grid fluctuation //he reamed the Cb","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went=
 down because the CB (125A) tripped  in PWC due to Grid fluctuation //he re=
amed the Cb","ludivine.ngamaleu@ihstowers.com","368","11-09-2024 14:03:35",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003049141","Y=
de-M-Central","","11-09-2024 13:37:15","11-09-2024 13:28:59","11-09-2024 18=
:03:40","Grid Outage no space to deploy MDG // Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage no spac=
e to deploy MDG // Grid return","ludivine.ngamaleu@ihstowers.com","545","11=
-09-2024 13:37:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003049127","M=
imboman-Village","","11-09-2024 13:35:09","11-09-2024 13:27:03","11-09-2024=
 13:27:04","Active: no power issue on site ,site on GRid with U=3D53,6V Tea=
m Eloundou // 693212405 from HUAWEI is informed","Mba Lazare Herve","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: no power issue on site ,site on GRid with U=3D53,6V Team Eloun=
dou // 693212405 from HUAWEI is informed","ludivine.ngamaleu@ihstowers.com"=
,"487","11-09-2024 13:35:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0003049105","E=
SSOS OASIS 1111","","11-09-2024 13:33:15","11-09-2024 12:51:00","11-09-2024=
 12:52:49","ACTIVE No power issue on site, site on Grid with Ubaie=3D54,3V =
Tx fme Armand Ngeuts/699949553/ from Huawei is Informed","Siligap Boris","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE No power issue on site, site on Grid with Ubaie=3D54,3V Tx=
 fme Armand Ngeuts/699949553/ from Huawei is Informed","ludivine.ngamaleu@i=
hstowers.com","2536","11-09-2024 13:33:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003049019","Akak-Nko=
zoa-MTN-IHS","","11-09-2024 13:21:40","11-09-2024 12:59:31","11-09-2024 13:=
05:56","Cascaded Incident from TTO2885745","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active// No power issue on s=
ite U=3D54,4v site on Grid Team Erick/696422966/ZTE working on site","syste=
m","1329","11-09-2024 13:21:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0003048917","S=
oa-II","IHS_YND_316, IHS_YND_324","11-09-2024 13:07:37","11-09-2024 12:59:3=
1","11-09-2024 13:38:34","Active// No power issue on site U=3D54,4v site on=
 Grid Team Erick/696422966/ZTE working on site","Siligap Boris","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power issue on site U=3D54,4v site on Grid Team Erick/69642296=
6/ZTE working on site","ludivine.ngamaleu@ihstowers.com","487","11-09-2024 =
13:07:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003048834","Mamb",""=
,"11-09-2024 12:57:20","11-09-2024 12:52:22","11-09-2024 12:57:03","Cascade=
d Incident from TTO2885646","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid Outage, site went down because  Gen=
  start due to poor battery backup // Grid Power return","system","298","11=
-09-2024 12:57:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003048833","Boumnyeb=
el","","11-09-2024 12:57:20","11-09-2024 12:52:22","11-09-2024 12:57:03","C=
ascaded Incident from TTO2885646","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage, site went down becaus=
e  Gen  start due to poor battery backup // Grid Power return","system","29=
8","11-09-2024 12:57:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0003048827","B=
oumnyebel OCM","IHS_YND_381, IHS_YND_376","11-09-2024 12:56:27","11-09-2024=
 12:52:22","11-09-2024 12:57:03","Grid Outage, site went down because  Gen =
 start due to poor battery backup // Grid Power return","Kemeni Franklin","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","=
Grid Outage, site went down because  Gen  start due to poor battery backup =
// Grid Power return","ludivine.ngamaleu@ihstowers.com","245","11-09-2024 1=
2:56:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0003048611","E=
TOUDI CHAPELLE","","11-09-2024 12:16:36","11-09-2024 12:14:32","11-09-2024 =
12:47:42","Grid Fluctuation, Site went down because Gen failed to start due=
 to Grid Bad voltage No rcp on site// He started Gen Manualy","Delor Telezi=
ng","Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty=
","Grid Fluctuation, Site went down because Gen failed to start due to Grid=
 Bad voltage No rcp on site// He started Gen Manualy","ludivine.ngamaleu@ih=
stowers.com","125","11-09-2024 12:16:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003048181","N=
GONA","","11-09-2024 11:23:02","11-09-2024 11:19:57","11-09-2024 12:52:17",=
"Active: No power issue, site is on Grid with U=3D56V , The TX FME Lionel a=
djep//655184876// From Huawei is informed and Up at 11:29 PM","Mba Lazare H=
erve","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active: No power issue, site is on Grid with U=3D56V , Th=
e TX FME Lionel adjep//655184876// From Huawei is informed and Up at 11:29 =
PM","ludivine.ngamaleu@ihstowers.com","186","11-09-2024 11:23:02","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0003048146","S=
apeur Mimboman","","11-09-2024 11:18:21","11-09-2024 11:10:17","11-09-2024 =
12:30:21","Active//No power issue site on grid with U=3D54,5V Eloundou Bert=
rand (652586578) from Huawei is informed ","Mba Lazare Herve","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//No power issue site on grid with U=3D54,5V Eloundou Bertrand (652586=
578) from Huawei is informed","ludivine.ngamaleu@ihstowers.com","485","11-0=
9-2024 11:18:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003048053","M=
endong vallee","","11-09-2024 11:04:55","11-09-2024 10:56:49","11-09-2024 1=
6:21:04","Fire on site (DC-BOX Burned on Site)","Fanda Brice","Fire on Site=
","Passive","Infrastructure","Fire - Burned","Fire on site (DC-BOX Burned o=
n Site)","ludivine.ngamaleu@ihstowers.com","486","11-09-2024 11:04:55","Sag=
emcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003048033","Feb=
e Village","","11-09-2024 11:01:45","11-09-2024 10:51:35","11-09-2024 12:30=
:58","Grid Outage, site went down because Gen stopped with ""high temp"" al=
arm// He added water and started Gen manualy","Mboua Thierry","Equipment Re=
pair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue",=
"Grid Outage, site went down because Gen stopped with ""high temp"" alarm//=
 He added water and started Gen manualy","dorothy.djantio@ihstowers.com","8=
97","11-09-2024 11:01:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0003048004","A=
bome","","11-09-2024 10:56:16","11-09-2024 10:46:59","11-09-2024 13:43:31",=
"Active: No power issue, site is on Grid with U=3D53,7V , The TX FME Lionel=
 adjep//655184876// From Huawei is informed","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue, site is on Grid with U=3D53,7V , The TX FME Lionel ad=
jep//655184876// From Huawei is informed","ludivine.ngamaleu@ihstowers.com"=
,"558","11-09-2024 10:56:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0003047945","Marche O=
dza","","11-09-2024 10:45:30","11-09-2024 10:43:38","11-09-2024 10:47:53","=
Cascaded Incident from TTO2884626","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site went down before =
gen start due to poor battery backup // Gen start automatically","system","=
112","11-09-2024 10:45:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0003047944","Mvog-Man=
ga","","11-09-2024 10:45:30","11-09-2024 10:43:38","11-09-2024 10:47:53","C=
ascaded Incident from TTO2884626","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before g=
en start due to poor battery backup // Gen start automatically","system","1=
12","11-09-2024 10:45:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0003047940","O=
dza","IHS_YND_254, IHS_YND_580","11-09-2024 10:44:43","11-09-2024 10:43:38"=
,"11-09-2024 10:47:53","Grid outage, site went down before gen start due to=
 poor battery backup // Gen start automatically","Albran Byorel","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge, site went down before gen start due to poor battery backup // Gen start=
 automatically","ludivine.ngamaleu@ihstowers.com","66","11-09-2024 10:44:43=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003047679","B=
arriere","","11-09-2024 10:05:30","11-09-2024 10:01:26","11-09-2024 11:46:2=
0","Active: No power issue, site is on grid with Ubaie=3D54,6V, lionel tcha=
tchoua(694693436) from Huawei is unreachable and up at 10:07 AM","Hyemafo G=
ildas","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active: No power issue, site is on grid with Ubaie=3D54,=
6V, lionel tchatchoua(694693436) from Huawei is unreachable and up at 10:07=
 AM","ludivine.ngamaleu@ihstowers.com","244","11-09-2024 10:05:30","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0003047224","O=
ssombe","","11-09-2024 08:57:13","11-09-2024 08:53:08","11-09-2024 09:00:24=
","Active// No power issue, site is on Battery with Ubaie=3D50,6 V(Start th=
reshold ubai=3D49,6V)  The Team  DIAKITE NAKAN //652369313//  from Huawei  =
working on site ","Parker Tchoup","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active// No power issue, site=
 is on Battery with Ubaie=3D50,6 V(Start threshold ubai=3D49,6V)  The Team =
 DIAKITE NAKAN //652369313//  from Huawei  working on site ","ludivine.ngam=
aleu@ihstowers.com","246","11-09-2024 08:57:13","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003047200","NYO=
M 2 IHS","","11-09-2024 08:54:04","11-09-2024 08:50:51","11-09-2024 09:37:4=
5","Grid Fluctuation, Site went down because Gen failed to start due to Gri=
d Bad voltage No rcp on site// He bypassed Grid and started Gen Manualy","F=
abrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","Grid Fluctuation, Site went down because Gen failed to start=
 due to Grid Bad voltage No rcp on site// He bypassed Grid and started Gen =
Manualy","dorothy.djantio@ihstowers.com","194","11-09-2024 08:54:04","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0003047005","T=
radex-Nkomo","","11-09-2024 08:04:50","11-09-2024 08:00:46","11-09-2024 08:=
31:03","Grid Fluctuation, Site went down because Gen failed to start due to=
 Grid Bad voltage No rcp on site// He started Gen Manualy","Albran Byorel",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid Fluctuation, Site went down because Gen failed to start due to Grid Bad=
 voltage No rcp on site// He started Gen Manualy","ludivine.ngamaleu@ihstow=
ers.com","244","11-09-2024 08:04:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003046925","Afanoya"=
,"","11-09-2024 07:47:20","11-09-2024 07:41:01","11-09-2024 07:50:25","Casc=
aded Incident from TTO2883473","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, site went down because  G=
en failed to start due to poor battery backup // Grid Power return","system=
","379","11-09-2024 07:47:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003046923","ELOUMDEM=
 CARRIERE","","11-09-2024 07:47:20","11-09-2024 07:41:01","11-09-2024 07:50=
:25","Cascaded Incident from TTO2883473","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, site went down bec=
ause  Gen failed to start due to poor battery backup // Grid Power return",=
"system","379","11-09-2024 07:47:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003046924","MBALNGON=
G LYCEE","","11-09-2024 07:47:20","11-09-2024 07:41:01","11-09-2024 07:50:2=
5","Cascaded Incident from TTO2883473","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage, site went down becau=
se  Gen failed to start due to poor battery backup // Grid Power return","s=
ystem","379","11-09-2024 07:47:20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003046921","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","11-09-2024 07:46:08","11-09-20=
24 07:41:01","11-09-2024 07:50:25","Grid Outage, site went down because  Ge=
n failed to start due to poor battery backup // Grid Power return","Hyemafo=
 Gildas","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","Grid Outage, site went down because  Gen failed to start due to p=
oor battery backup // Grid Power return","dorothy.djantio@ihstowers.com","3=
08","11-09-2024 07:46:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003045483","N=
sam Sofavinc T0","","11-09-2024 00:29:19","10-09-2024 23:05:04","11-09-2024=
 02:05:12","Grid outage ,Site went down because Gen started and stopped due=
 to Gen ovreload(9kva ,150 A)//he reduce the load ,site on Gen ","MINKA NIC=
OLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outag=
e ,Site went down because Gen started and stopped due to Gen ovreload(9kva =
,150 A)//he reduce the load ,site on Gen ","kouoh.jean@ihstowers.com","5056=
","11-09-2024 00:29:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003044338","F=
ebe Village","","10-09-2024 20:35:57","10-09-2024 20:23:49","10-09-2024 21:=
15:31","No power issue site oN gen with U=3D54v//Mohamadou (691144435) from=
 Huawei is informed site up at 08:38 PM","Mboua Thierry","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue site oN gen with U=3D54v//Mohamadou (691144435) from Huawei is inf=
ormed site up at 08:38 PM","emmanuel.ghani@ihstowers.com","729","10-09-2024=
 20:35:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003044155","B=
itoto","","10-09-2024 20:09:58","10-09-2024 20:01:54","10-09-2024 22:21:13"=
,"site went down because insufficiency of rectifiers (site on 05 rectifiers=
)due to increase load on site // site Stabilized( 01 Rectifier to be added)=
","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down because insufficiency of rectifiers (site on 05 recti=
fiers)due to increase load on site // site Stabilized( 01 Rectifier to be a=
dded)","emmanuel.ghani@ihstowers.com","485","10-09-2024 20:09:58","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0003044031","M=
EHANDAN","","10-09-2024 19:47:10","10-09-2024 19:41:05","10-09-2024 21:04:5=
4","Site went down because CB OCM (125A) at DC BOX disjoncted Causing by in=
crease load in site //He reamed CB","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went do=
wn because CB OCM (125A) at DC BOX disjoncted Causing by increase load in s=
ite //He reamed CB","emmanuel.ghani@ihstowers.com","366","10-09-2024 19:47:=
10","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003043633","Jou=
vence 2000","","10-09-2024 18:37:35","10-09-2024 18:31:32","10-09-2024 18:3=
9:32","Grid Fluctuation, site went down because  Gen failed to start due to=
 poor battery backup // Grid Power return","Delor Telezing","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuati=
on, site went down because  Gen failed to start due to poor battery backup =
// Grid Power return","joelle.ekessi@ihstowers.com","364","10-09-2024 18:37=
:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0003043594","E=
lig Edzoa","","10-09-2024 18:31:12","10-09-2024 18:29:07","10-09-2024 18:40=
:45","Grid Fluctuation, site went down because  Gen failed to start due to =
poor battery backup // Grid Power return","Delor Telezing","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuatio=
n, site went down because  Gen failed to start due to poor battery backup /=
/ Grid Power return","emmanuel.ghani@ihstowers.com","126","10-09-2024 18:31=
:12","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003043138","Mim=
boman3","","10-09-2024 17:13:48","10-09-2024 17:06:42","10-09-2024 17:47:42=
","site went down due to work Lazare/657108482/Sagemcom he bypassed the Rel=
ay Q11 in bay//End of work","Mba Lazare Herve","Installation Activity","Pas=
sive","Planned Activity","Installation Activity","site went down due to wor=
k Lazare/657108482/Sagemcom he bypassed the Relay Q11 in bay//End of work",=
"joelle.ekessi@ihstowers.com","1173","10-09-2024 17:13:48","Sagemcom CMR"
"Closed Complete","Site Down","T1591","IHS_YND_172","NOCINC0003043093","Tra=
dex-Nkomo","","10-09-2024 17:07:12","10-09-2024 17:00:08","10-09-2024 17:31=
:22","Site  on gen due to grid outage, site down because water infiltration=
 in the tank// He purged the Gen and  removed water","Albran Byorel","Fuel =
Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In The Fu=
el","Site  on gen due to grid outage, site down because water infiltration =
in the tank// He purged the Gen and  removed water","joelle.ekessi@ihstower=
s.com","1358","10-09-2024 17:07:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003043053","Ngog Map=
ubi","","10-09-2024 16:59:20","10-09-2024 16:52:50","10-09-2024 16:59:01","=
Cascaded Incident from TTO2878741","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,Site went down before=
 DG start : Poor Batteries backup//DG started automatically","system","390"=
,"10-09-2024 16:59:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0003043054","Boumnyeb=
el","","10-09-2024 16:59:20","10-09-2024 16:52:50","10-09-2024 16:59:01","C=
ascaded Incident from TTO2878741","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,Site went down before =
DG start : Poor Batteries backup//DG started automatically","system","390",=
"10-09-2024 16:59:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003043055","Mamb",""=
,"10-09-2024 16:59:20","10-09-2024 16:52:50","10-09-2024 16:59:01","Cascade=
d Incident from TTO2878741","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage,Site went down before DG sta=
rt : Poor Batteries backup//DG started automatically","system","390","10-09=
-2024 16:59:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003043052","Ndogbess=
ol","","10-09-2024 16:59:20","10-09-2024 16:52:50","10-09-2024 16:59:01","C=
ascaded Incident from TTO2878741","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,Site went down before =
DG start : Poor Batteries backup//DG started automatically","system","390",=
"10-09-2024 16:59:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0003043004","B=
oumnyebel OCM","IHS_EDA_056, IHS_YND_419, IHS_YND_381, IHS_YND_376","10-09-=
2024 16:56:56","10-09-2024 16:52:50","10-09-2024 16:59:01","Grid outage,Sit=
e went down before DG start : Poor Batteries backup//DG started automatical=
ly","Kemeni Franklin","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage,Site went down before DG start : Poor Ba=
tteries backup//DG started automatically","emmanuel.ghani@ihstowers.com","2=
47","10-09-2024 16:56:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003042623","N=
sam Sofavinc T0","","10-09-2024 16:05:26","10-09-2024 15:44:15","10-09-2024=
 16:45:46","Grid outage, site went down because gen start and stopped due t=
o gen Overload (9Kva, 150A) //Grid return","MINKA NICOLAS","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Overload","Grid outage, site went down beca=
use gen start and stopped due to gen Overload (9Kva, 150A) //Grid return","=
emmanuel.ghani@ihstowers.com","1272","10-09-2024 16:05:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0003042178","S=
atcom","","10-09-2024 15:20:56","10-09-2024 15:04:50","10-09-2024 16:43:18"=
,"Grid Bad Voltage  Site wend down because  Gen Failed to start and due to =
lack on 01 phases on site //He make the bridge on good phase ","Delor Telez=
ing","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid Bad Voltage  Site wend down because  Gen Failed to start and due t=
o lack on 01 phases on site //He make the bridge on good phase ","emmanuel.=
ghani@ihstowers.com","966","10-09-2024 15:20:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003042170","M=
imboman-Village","","10-09-2024 15:19:23","10-09-2024 14:55:18","10-09-2024=
 16:33:38","No power issue on site U=3D53,6v site on grid Eloundou of huawe=
i is informed","Mba Lazare Herve","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53=
,6v site on grid Eloundou of huawei is informed","emmanuel.ghani@ihstowers.=
com","1446","10-09-2024 15:19:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0003041973","C=
rf-Nsam","","10-09-2024 14:58:33","10-09-2024 14:34:26","10-09-2024 15:56:4=
6","Grid outage  site went down because gen failed to start due to fuel the=
ft//Refueling done","MINKA NICOLAS","Site Asset Theft","Theft","Theft","Die=
sel Theft","Grid outage  site went down because gen failed to start due to =
fuel theft//Refueling done","emmanuel.ghani@ihstowers.com","1448","10-09-20=
24 14:58:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003041846","Afanoya"=
,"","10-09-2024 14:42:51","10-09-2024 14:38:34","10-09-2024 14:46:31","Casc=
aded Incident from TTO2877387","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site went down before DG s=
tart : Poor Batteries Backup // DG started automatically.","system","257","=
10-09-2024 14:42:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003041844","ELOUMDEM=
 CARRIERE","","10-09-2024 14:42:50","10-09-2024 14:38:34","10-09-2024 14:46=
:31","Cascaded Incident from TTO2877387","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage,site went down befo=
re DG start : Poor Batteries Backup // DG started automatically.","system",=
"256","10-09-2024 14:42:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003041845","MBALNGON=
G LYCEE","","10-09-2024 14:42:50","10-09-2024 14:38:34","10-09-2024 14:46:3=
1","Cascaded Incident from TTO2877387","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down before=
 DG start : Poor Batteries Backup // DG started automatically.","system","2=
56","10-09-2024 14:42:50","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003041835","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","10-09-2024 14:41:40","10-09-20=
24 14:38:34","10-09-2024 14:46:31","Grid outage,site went down before DG st=
art : Poor Batteries Backup // DG started automatically.","Hyemafo Gildas",=
"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low",=
"Grid outage,site went down before DG start : Poor Batteries Backup // DG s=
tarted automatically.","joelle.ekessi@ihstowers.com","187","10-09-2024 14:4=
1:40","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003041521","Eko=
unou","","10-09-2024 14:07:50","10-09-2024 14:05:44","10-09-2024 14:13:44",=
"Grid outage,site went down before DG start : Poor Batteries Backup // DG s=
tarted automatically.","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage,site went down before D=
G start : Poor Batteries Backup // DG started automatically.","joelle.ekess=
i@ihstowers.com","127","10-09-2024 14:07:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003041343","M=
IMBOMAN LIBERTE","","10-09-2024 13:41:13","10-09-2024 13:35:00","10-09-2024=
 13:55:41","Grid Outage and Main Gen Faulty//Grid Restored","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid=
 Outage and Main Gen Faulty//Grid Restored","denis.mballa@ihstowers.com","3=
74","10-09-2024 13:41:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_632","IHS_YND_721","NOCINC0003041218","V=
OIRIE MUNICIPALE YAOUNDE","","10-09-2024 13:25:17","10-09-2024 13:16:03","1=
0-09-2024 14:34:22","No power issue on site U=3D54,1v site on grid Brice st=
ague of huawei is informed","Paul BIBOUM","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54,1v site on grid Brice stague of huawei is informed","denis.mballa@=
ihstowers.com","554","10-09-2024 13:25:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0003041167","E=
lobi Mokolo","","10-09-2024 13:15:42","10-09-2024 13:10:19","10-09-2024 13:=
11:19","No power issue site on grid with U=3D53.4v Mohamadou(691144435) fro=
m Huawei is informed Notice that heavy rain on the area","Mboua Thierry","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue site on grid with U=3D53.4v Mohamadou(691144435) f=
rom Huawei is informed Notice that heavy rain on the area","denis.mballa@ih=
stowers.com","324","10-09-2024 13:15:42","Sagemcom CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0003040906","ENA=
M","","10-09-2024 12:39:01","10-09-2024 12:26:48","10-09-2024 14:19:40","gr=
id outage,no space to deploy a mobil gen//grid return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","grid outage,no space to =
deploy a mobil gen//grid return","olivier.kwedi@ihstowers.com","3628","10-0=
9-2024 12:39:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0003040740","E=
-Police","","10-09-2024 12:32:25","10-09-2024 12:24:13","10-09-2024 12:32:1=
3","grid outageno space to deploy a mobil gen//grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","grid outageno space=
 to deploy a mobil gen//grid return","denis.mballa@ihstowers.com","493","10=
-09-2024 12:32:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0003040668","A=
RMP","","10-09-2024 12:22:19","10-09-2024 12:13:58","10-09-2024 12:13:59","=
No power issue on site U=3D54v site on grid Eloundou of huawei is informed"=
,"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site U=3D54v site on grid Eloundou of hua=
wei is informed","denis.mballa@ihstowers.com","502","10-09-2024 12:22:19","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003040583","T=
singa","","10-09-2024 12:06:17","10-09-2024 12:00:04","10-09-2024 13:21:23"=
,"Grid Fluctuation, site went down because  Gen failed to start due to poor=
 battery backup // Grid Power return","Mboua Thierry","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuation, si=
te went down because  Gen failed to start due to poor battery backup // Gri=
d Power return","denis.mballa@ihstowers.com","374","10-09-2024 12:06:17","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003040491","Matsari"=
,"","10-09-2024 11:54:21","10-09-2024 11:35:59","10-09-2024 11:45:20","Casc=
aded Incident from TTO2875805","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active// No power issue, site is on GEN wi=
th Ubaie=3D54 V  The Team  DIAKITE NAKAN //652369313//  from Huawei  workin=
g on site ","system","1102","10-09-2024 11:54:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003040490","MBIMBIM"=
,"","10-09-2024 11:54:21","10-09-2024 11:35:59","10-09-2024 11:45:20","Casc=
aded Incident from TTO2875805","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active// No power issue, site is on GEN wi=
th Ubaie=3D54 V  The Team  DIAKITE NAKAN //652369313//  from Huawei  workin=
g on site ","system","1102","10-09-2024 11:54:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003040492","Yoko MTN=
","","10-09-2024 11:54:21","10-09-2024 11:35:59","10-09-2024 11:45:20","Cas=
caded Incident from TTO2875805","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// No power issue, site is on GEN w=
ith Ubaie=3D54 V  The Team  DIAKITE NAKAN //652369313//  from Huawei  worki=
ng on site ","system","1102","10-09-2024 11:54:21","Sagemcom CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0003040470","Ngo=
uetou","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_473","10-09-2024 11:=
53:15","10-09-2024 11:35:59","10-09-2024 11:45:20","Active// No power issue=
, site is on GEN with Ubaie=3D54 V  The Team  DIAKITE NAKAN //652369313//  =
from Huawei  working on site ","Parker Tchoup","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No powe=
r issue, site is on GEN with Ubaie=3D54 V  The Team  DIAKITE NAKAN //652369=
313//  from Huawei  working on site ","olivier.kwedi@ihstowers.com","1037",=
"10-09-2024 11:53:15","Sagemcom CMR"
"Closed Complete","Site Down","T1062","IHS_YND_475","NOCINC0003040445","Ngo=
um","","10-09-2024 11:50:15","10-09-2024 11:35:59","10-09-2024 11:45:20",""=
,"Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active=
","Active// No power issue, site is on GEN with Ubaie=3D54 V  The Team  DIA=
KITE NAKAN //652369313//  from Huawei  working on site ","olivier.kwedi@ihs=
towers.com","4548","10-09-2024 11:50:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003040421","H=
-Progres","","10-09-2024 11:46:00","10-09-2024 08:59:45","10-09-2024 14:15:=
10","grid outage,no space to deploy  a mobil gen//grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no s=
pace to deploy  a mobil gen//grid return","denis.mballa@ihstowers.com","997=
6","10-09-2024 11:46:00","Sagemcom CMR"
"Closed Complete","Site Down","T0532","IHS_YND_239","NOCINC0003040353","Men=
dong2","","10-09-2024 11:33:55","10-09-2024 10:34:29","10-09-2024 11:48:36"=
,"Grid outage Site went down because Gen ran untill fuel shortage // refuel=
ing done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"Grid outage Site went down because Gen ran untill fuel shortage // refuel=
ing done","olivier.kwedi@ihstowers.com","3567","10-09-2024 11:33:55","Sagem=
com CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003040343","BAT=
A Mokolo OCM","","10-09-2024 11:32:35","10-09-2024 10:24:22","11-09-2024 13=
:44:22","Grid outage, no space to deploy // grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no space =
to deploy // grid return","olivier.kwedi@ihstowers.com","4094","10-09-2024 =
11:32:35","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0003040323","Nko=
abang2","","10-09-2024 11:31:30","10-09-2024 10:24:28","10-09-2024 11:34:22=
","grid outage site went down due to Gen overload 16,5;212A//he reduice the=
 load on site","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","grid outage site went down due to Gen overload 16,5,212A/=
/he reduice the load on site","olivier.kwedi@ihstowers.com","4023","10-09-2=
024 11:31:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0003039664","B=
itoto","","10-09-2024 10:57:15","10-09-2024 10:53:00","10-09-2024 11:09:52"=
,"site went down because 01/05 rectifier faulty and the CB(63A) of rectifie=
r dysjoncted// He reamed the Cb of rectifier","Mba Lazare Herve","Equipment=
 Repair","Passive","Rectifier","Rectifier Module","site went down because 0=
1/05 rectifier faulty and the CB(63A) of rectifier dysjoncted// He reamed t=
he Cb of rectifier","denis.mballa@ihstowers.com","256","10-09-2024 10:57:15=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0003039605","M=
ini-Ferme","","10-09-2024 10:49:38","10-09-2024 10:40:20","10-09-2024 14:08=
:39","Grid outage //Grid power return","","Grid Supply","Passive","Grid","N=
ational Grid - Grid Outage Issue","Grid outage //Grid power return","denis.=
mballa@ihstowers.com","559","10-09-2024 10:49:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003039575","M=
aison-Blanche-IHS","","10-09-2024 10:46:21","10-09-2024 10:12:02","10-09-20=
24 14:09:57","grid outage,no space to deploy a mobil gen//grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid out=
age,no space to deploy a mobil gen//grid return","denis.mballa@ihstowers.co=
m","2060","10-09-2024 10:46:21","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0003039367","Av =
Kennedy","","10-09-2024 10:19:18","10-09-2024 10:10:11","10-09-2024 11:31:1=
1","grid outage,no space to deploy a mobil gen//grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no spa=
ce to deploy a mobil gen//grid return","olivier.kwedi@ihstowers.com","548",=
"10-09-2024 10:19:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003039366","N=
kozoa","","10-09-2024 10:19:10","10-09-2024 10:12:53","10-09-2024 11:04:55"=
,"","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase=
 Controller Faulty","Grid Fluctuation, site went down before gen start due =
to poor battery backup and Grid bad voltage // He bypassed Grid and Started=
 Gen Manualy","denis.mballa@ihstowers.com","378","10-09-2024 10:19:10","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0003039314","S=
cience","","10-09-2024 10:13:55","10-09-2024 10:04:44","10-09-2024 10:10:24=
","","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","Active //No power issue, site i=
s on Gen with U=3D53,2 V ,  The TX FME Mouhamadou //691144435//   Huawei is=
 informed,Notice that we have disjunction at BTS OCM","denis.mballa@ihstowe=
rs.com","552","10-09-2024 10:13:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0003039303","C=
rf Cornier","","10-09-2024 10:11:17","10-09-2024 10:03:47","10-09-2024 10:1=
0:01","","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue site on Grid with U=3D5=
3.1V  The Rm (Alain) (691144423) from Huawei is informed","denis.mballa@ihs=
towers.com","451","10-09-2024 10:11:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003039184","Anguissa=
 New","","10-09-2024 10:00:30","10-09-2024 09:00:11","10-09-2024 14:15:59",=
"Cascaded Incident from TTO2874369","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,no space to deploy a m=
obil gen//grid return","system","3619","10-09-2024 10:00:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003039166","L=
abogenie","IHS_YND_568","10-09-2024 09:58:24","10-09-2024 09:00:11","10-09-=
2024 14:15:59","grid outage,no space to deploy a mobil gen//grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid o=
utage,no space to deploy a mobil gen//grid return","denis.mballa@ihstowers.=
com","3494","10-09-2024 09:58:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0003039067","E=
toug ebe Meweulo","","10-09-2024 09:41:22","10-09-2024 09:34:04","10-09-202=
4 10:41:16","Grid outage site went down because Gen failed to start due to =
charging alternator faulty// Gen manually started with external battery","H=
yemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alt=
ernator","Grid outage site went down because Gen failed to start due to cha=
rging alternator faulty// Gen manually started with external battery","deni=
s.mballa@ihstowers.com","439","10-09-2024 09:41:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0003039001","S=
imbock OCM","","10-09-2024 09:31:24","10-09-2024 09:22:10","10-09-2024 10:2=
3:16","Grid Fluctuation, site went down because  Gen failed to start due to=
 poor battery backup // Grid Power return","Hyemafo Gildas","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuati=
on, site went down because  Gen failed to start due to poor battery backup =
// Grid Power return","denis.mballa@ihstowers.com","554","10-09-2024 09:31:=
24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003038992","Kondengu=
i","","10-09-2024 09:29:20","10-09-2024 09:19:15","10-09-2024 14:10:29","Ca=
scaded Incident from TTO2874152","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage No space to deploy a mobi=
l gen// Grid power return","system","605","10-09-2024 09:29:20","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003038984","E=
mombo-Tchad","IHS_YND_114","10-09-2024 09:28:30","10-09-2024 09:19:15","10-=
09-2024 14:10:29","Grid outage No space to deploy a mobil gen// Grid power =
return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid outage No space to deploy a mobil gen// Grid power return","denis.=
mballa@ihstowers.com","556","10-09-2024 09:28:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0003038921","N=
GONA","","10-09-2024 09:20:44","10-09-2024 09:16:31","10-09-2024 09:20:09",=
"Active: No power issue, site is on Grid with U=3D55,7V , The TX FME Lionel=
 adjep//655184876// From Huawei is informed","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active: No power issue, site is on Grid with U=3D55,7V , The TX FME Lionel=
 adjep//655184876// From Huawei is informed","denis.mballa@ihstowers.com","=
253","10-09-2024 09:20:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003038738","B=
ATA-Mokolo","","10-09-2024 08:48:44","10-09-2024 08:41:32","10-09-2024 14:0=
9:33","grid outage,no space to deploy a mobil gen//grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no =
space to deploy a mobil gen//grid return","denis.mballa@ihstowers.com","432=
","10-09-2024 08:48:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003038729","C=
amp-Sic-Tsinga","","10-09-2024 08:47:14","10-09-2024 08:39:03","10-09-2024 =
14:05:48","grid outage,no space to deploy a mobil gen//grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage=
,no space to deploy a mobil gen//grid return","denis.mballa@ihstowers.com",=
"492","10-09-2024 08:47:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003038678","T=
singa","","10-09-2024 08:36:13","10-09-2024 08:27:00","10-09-2024 08:43:44"=
,"Grid Fluctuation, site went down because  Gen failed to start due to poor=
 battery backup // Grid Power return","Mboua Thierry","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid Fluctuation, si=
te went down because  Gen failed to start due to poor battery backup // Gri=
d Power return","denis.mballa@ihstowers.com","554","10-09-2024 08:36:13","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003038667","Y=
de-M-Central","","10-09-2024 08:34:56","10-09-2024 08:25:46","10-09-2024 11=
:44:07","grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,n=
o space to deploy a mobil gen//grid return","denis.mballa@ihstowers.com","5=
51","10-09-2024 08:34:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0003038356","N=
omayos-IHS","","10-09-2024 07:21:42","10-09-2024 07:19:29","10-09-2024 08:1=
9:32","site went down because 02/04 RECTIFIER  dysfoncton// He reset the re=
ctifier","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier =
Module","site went down because 02/04 RECTIFIER  dysfoncton// He reset the =
rectifier","denis.mballa@ihstowers.com","133","10-09-2024 07:21:42","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003038313","N=
kolndongo","","10-09-2024 07:13:36","10-09-2024 07:08:24","10-09-2024 07:18=
:59","Grid Outage and Main Gen Faulty//Grid Restored","MINKA NICOLAS","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid Outage a=
nd Main Gen Faulty//Grid Restored","denis.mballa@ihstowers.com","313","10-0=
9-2024 07:13:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003037932","Donga","=
","10-09-2024 05:24:00","09-09-2024 18:36:39","09-09-2024 19:12:39","Cascad=
ed Incident from TTO2872859","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power  issue U=3D50,7 V  site on Gen The =
TxFMe Gr=E9goire//652070658 is informed ,Site up 01:33 PM.","system","38841=
","10-09-2024 05:24:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003037933","Dong",""=
,"10-09-2024 05:24:00","09-09-2024 18:36:39","09-09-2024 19:12:39","Cascade=
d Incident from TTO2872859","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power  issue U=3D50,7 V  site on Gen The T=
xFMe Gr=E9goire//652070658 is informed ,Site up 01:33 PM.","system","38841"=
,"10-09-2024 05:24:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003037811","N=
kolda","","10-09-2024 04:26:49","09-09-2024 17:54:23","09-09-2024 18:19:25"=
,"Grid Fluctuation, site went down before gen start due to poor battery bac=
kup and Grid bad voltage and RCP // Grid power stabilized","Albran Byorel",=
"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low",=
"Grid Fluctuation, site went down before gen start due to poor battery back=
up and Grid bad voltage and RCP // Grid power stabilized","kouoh.jean@ihsto=
wers.com","37947","10-09-2024 04:26:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0003037806","N=
kol-Mbanda","","10-09-2024 04:23:40","09-09-2024 17:50:21","09-09-2024 18:0=
5:54","Grid ooutage site went down because Gen Gen overload (20 KVA,300A)//=
 Grid power return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Grid ooutage site went down because Gen Gen overload (2=
0 KVA,300A)// Grid power return","kouoh.jean@ihstowers.com","37999","10-09-=
2024 04:23:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0003037805","C=
NR","","10-09-2024 04:20:51","09-09-2024 17:34:33","09-09-2024 18:39:44","G=
rid outage, site went down because Gen failed to start due to Gen CARD  Fau=
lty // Gen manually start","Mboua Thierry","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage, site went down because Gen fai=
led to start due to Gen CARD  Faulty // Gen manually start","kouoh.jean@ihs=
towers.com","38778","10-09-2024 04:20:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0003037790","E=
NAM","","10-09-2024 04:14:07","09-09-2024 17:21:47","09-09-2024 18:32:47","=
Grid Outage No Space to deploy a MDG //Grid Restored","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space to d=
eploy a MDG //Grid Restored","kouoh.jean@ihstowers.com","39141","10-09-2024=
 04:14:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0003037776","M=
adison","","10-09-2024 04:10:08","09-09-2024 17:29:45","09-09-2024 18:01:30=
","Grid outage no space to deployed a mobil gen // Grid return","MFOUAGUEGU=
E MATHIEU","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","	Grid outage no space to deployed a mobil gen // Grid return","kouoh.je=
an@ihstowers.com","38424","10-09-2024 04:10:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0003037759","J=
-Vespa","","10-09-2024 04:05:20","09-09-2024 17:26:10","09-09-2024 17:58:41=
","Grid outage, site went down because Gen start and stopped with alarm 'Ov=
ercurrent' // Grid Restored","Mboua Thierry","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage, site went down because Gen s=
tart and stopped with alarm 'Overcurrent' // Grid Restored","kouoh.jean@ihs=
towers.com","38351","10-09-2024 04:05:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003037758","E=
mombo-Tchad","","10-09-2024 04:04:09","09-09-2024 17:24:43","09-09-2024 18:=
47:53","Grid Outage//Grid Restored","","Grid Supply","Passive","Grid","Nati=
onal Grid - Grid Outage Issue","Grid Outage//Grid Restored","kouoh.jean@ihs=
towers.com","38366","10-09-2024 04:04:09","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0003037752","Mom=
","","10-09-2024 03:59:18","10-09-2024 03:55:05","10-09-2024 05:43:57","Gri=
d Outage site went down because gen ran till fuel shortage//Refueling done"=
,"Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Grid Outag=
e site went down because gen ran till fuel shortage//Refueling done","steph=
ane.nkamwa@ihstowers.com","254","10-09-2024 03:59:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0003037737","B=
arriere","","10-09-2024 03:53:34","09-09-2024 17:14:19","09-09-2024 18:28:5=
9","Grid Fluctuation, site went down before gen start due to poor battery b=
ackup and Grid bad voltage and RCP // Grid power stabilized","Hyemafo Gilda=
s","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid Fluctuation, site went down before gen start due to poor battery b=
ackup and Grid bad voltage and RCP // Grid power stabilized","kouoh.jean@ih=
stowers.com","38356","10-09-2024 03:53:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0003037733","C=
NDH","","10-09-2024 03:51:13","09-09-2024 17:07:17","09-09-2024 18:39:08","=
Grid outage site went down because Gen failed to started due to Gen card fa=
ulty//Gen manually  started","Paul BIBOUM","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","Grid outage site went down because Gen fail=
ed to started due to Gen card faulty//Gen manually  started","kouoh.jean@ih=
stowers.com","38637","10-09-2024 03:51:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0003037707","N=
gousso-Savana","","10-09-2024 03:45:55","09-09-2024 16:59:40","09-09-2024 1=
9:11:30","Grid outage, site went down because  gen failed tostart due to po=
or battery backup and dysjonction in the Dcbox ocm// Grid power return","Si=
ligap Boris","Equipment Repair","Passive","Control Panel","Power Cabinet - =
Battery Low","Grid outage, site went down because  gen failed tostart due t=
o poor battery backup and dysjonction in the Dcbox ocm// Grid power return"=
,"kouoh.jean@ihstowers.com","38776","10-09-2024 03:45:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0003037688","V=
allee-Bastos OCM","","10-09-2024 03:41:20","09-09-2024 16:53:48","09-09-202=
4 18:19:23","Grid outage  //MDG of 20 kva has deployed","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage  //MDG of 2=
0 kva has deployed","kouoh.jean@ihstowers.com","38853","10-09-2024 03:41:20=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0003037679","S=
apeur Mimboman","","10-09-2024 03:36:55","09-09-2024 16:49:26","09-09-2024 =
17:36:46","GRID outage site went down because Gen failed to start due to Ge=
n card faulty// Gen manually  started","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","GRID outage site went down b=
ecause Gen failed to start due to Gen card faulty// Gen manually  started",=
"kouoh.jean@ihstowers.com","38850","10-09-2024 03:36:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0003037665","M=
vog Mbi New","","10-09-2024 03:30:45","09-09-2024 16:43:32","09-09-2024 18:=
53:44","site went down because the CB (125A) tripped  in PWC due to load in=
crease//made a shunt of CB 125 and 125 A","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site w=
ent down because the CB (125A) tripped  in PWC due to load increase//made a=
 shunt of CB 125 and 125 A","kouoh.jean@ihstowers.com","38834","10-09-2024 =
03:30:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0003037660","C=
arington","","10-09-2024 03:28:56","09-09-2024 16:40:23","09-09-2024 18:41:=
34","Grid Outage//Grid Restored","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Outage Issue","Grid Outage//Grid Restored","kouoh.jean@ihstow=
ers.com","38914","10-09-2024 03:28:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0003037614","H=
-Progres","","10-09-2024 03:21:43","09-09-2024 16:35:17","09-09-2024 18:18:=
07","Grid outage No Space to deploy a MDG//Grid Restored","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No Space =
to deploy a MDG//Grid Restored","kouoh.jean@ihstowers.com","38786","10-09-2=
024 03:21:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003037591","M=
EFOU ASSI","","10-09-2024 03:09:05","09-09-2024 16:25:45","09-09-2024 19:22=
:12","Grid outage main gen faulty //MDG of 20 kva has deployed","Fanda Bric=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid =
outage main gen faulty //MDG of 20 kva has deployed","kouoh.jean@ihstowers.=
com","38601","10-09-2024 03:09:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003037580","Y=
de-M-Central","","10-09-2024 03:07:45","09-09-2024 16:25:20","09-09-2024 17=
:57:56","""Grid outage No space to deploy //  Grid power return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","""Grid outage =
No space to deploy //  Grid power return
""
","kouoh.jean@ihstowers.com","38546","10-09-2024 03:07:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003037569","E=
lig-Edzoa","","10-09-2024 03:05:32","09-09-2024 16:24:55","09-09-2024 18:39=
:55","","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid outage //Grid return","kouoh.jean@ihstowers.com","38438","10-09-20=
24 03:05:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0003037008","M=
aison-Blanche-IHS","","10-09-2024 01:05:24","09-09-2024 16:31:24","09-09-20=
24 18:32:24","Grid Outage No Space to deploy a MDG//Grid Restored","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage =
No Space to deploy a MDG//Grid Restored","kouoh.jean@ihstowers.com","30844"=
,"10-09-2024 01:05:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003036847","B=
ATA-Mokolo","","10-09-2024 00:34:27","09-09-2024 09:14:10","09-09-2024 21:0=
0:10","site went down due to insufficient of rectifier on site// site stabi=
lized","","Equipment Repair","Passive","Rectifier","Rectifier Module","site=
 went down due to insufficient of rectifier on site// site stabilized","kou=
oh.jean@ihstowers.com","55218","10-09-2024 00:34:27","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0003036572","NKO=
LOSSAN OKOK","","09-09-2024 23:21:16","09-09-2024 23:15:05","10-09-2024 01:=
14:17","Site on DG  due to grid outage ,DG stopped due to fuel shortage //R=
efueling of site,","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel=
 Outage","Site on DG  due to grid outage ,DG stopped due to fuel shortage /=
/Refueling of site,
","stephane.nkamwa@ihstowers.com","372","09-09-2024 23:21:16","Sagemcom CMR=
"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0003036543","OTE=
LE MTN","","09-09-2024 23:18:22","09-09-2024 22:59:09","10-09-2024 03:32:25=
","Site on DG due to grid ,DG stopped due to low oil pressure //He added oi=
l and maually start of DG","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Low Oil Pressure","Site on DG due to grid ,DG stopped due to =
low oil pressure //He added oil and maually start of DG","stephane.nkamwa@i=
hstowers.com","1153","09-09-2024 23:18:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0003036469","A=
FEME NORD","","09-09-2024 23:00:37","09-09-2024 22:52:27","09-09-2024 23:10=
:47","Grid bad voltage ,DG failed to start ,no RCP //Manually start of DG,"=
,"TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid -=
 Phase Controller Faulty","Grid bad voltage ,DG failed to start ,no RCP //M=
anually start of DG,","alexandre.kamal@ihstowers.com","491","09-09-2024 23:=
00:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0003036358","N=
kozoa","","09-09-2024 22:44:02","09-09-2024 22:29:53","09-09-2024 23:20:46"=
,"Site on DG due to grid outage  , DG stoppd due to overload (20 kva 300A) =
//He reduiced the load,","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Site on DG , DG stoppd due to overload (20 kva 3=
00A) //He reduiced the load,
","alexandre.kamal@ihstowers.com","850","09-09-2024 22:44:02","Sagemcom CMR=
"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0003036146","Clu=
b France","","09-09-2024 22:05:11","09-09-2024 21:56:51","09-09-2024 23:11:=
07","Grid outage //Grid restored","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid outage //Grid restored
","kouoh.jean@ihstowers.com","501","09-09-2024 22:05:11","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0003036068","Man=
guiers Dispensaire","","09-09-2024 21:49:57","09-09-2024 17:25:35","09-09-2=
024 18:36:54","Grid Outage site went down because the Grid contactor Faulty=
 // He bypass the Grid contactor and site on Grid","Fabrice Pouakam","Equip=
ment Repair","Passive","Control Panel","ATS-AMF Issue","Grid Outage site we=
nt down because the Grid contactor Faulty // He bypass the Grid contactor a=
nd site on Grid","kouoh.jean@ihstowers.com","15863","09-09-2024 21:49:57","=
Sagemcom CMR"
"Closed Complete","Site Down","T1832","IHS_YND_216","NOCINC0003036053","Ele=
veur","","09-09-2024 21:47:34","09-09-2024 16:57:06","09-09-2024 18:41:45",=
"Grid outage.gen failed to start due to alarm'""low oil pressure""//we rese=
t card GE and gen manually started","Siligap Boris","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to start du=
e to alarm'""low oil pressure""//we reset card GE and gen manually started"=
,"kouoh.jean@ihstowers.com","38864","09-09-2024 21:47:34","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0003035914","An-=
Marche-Melen","","09-09-2024 21:31:10","09-09-2024 17:24:59","09-09-2024 18=
:57:59","Grid outage No space to deploy //Grid power return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage No spa=
ce to deploy //Grid power return","kouoh.jean@ihstowers.com","38263","09-09=
-2024 21:31:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003035818","ETOUDI C=
HAPELLE","","09-09-2024 21:14:11","09-09-2024 20:59:05","10-09-2024 00:15:4=
3","Cascaded Incident from TTO2870114","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,DG failed to start=
 due to ACDG control panel Faulty //Manually start of DG.","system","906","=
09-09-2024 21:14:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003035819","Etoudi 2=
","","09-09-2024 21:14:11","09-09-2024 20:59:05","10-09-2024 00:15:43","Cas=
caded Incident from TTO2870114","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,DG failed to start due t=
o ACDG control panel Faulty //Manually start of DG.","system","906","09-09-=
2024 21:14:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003035817","Abattoir=
","","09-09-2024 21:14:10","09-09-2024 20:59:05","10-09-2024 00:15:43","Cas=
caded Incident from TTO2870114","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,DG failed to start due t=
o ACDG control panel Faulty //Manually start of DG.","system","905","09-09-=
2024 21:14:10","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003035800","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","09-09-2024 21:12:29","09-09-2=
024 20:59:05","10-09-2024 00:15:43","Grid outage,DG failed to start due to =
ACDG control panel Faulty //Manually start of DG","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,DG fai=
led to start due to ACDG control panel Faulty //Manually start of DG.","kou=
oh.jean@ihstowers.com","805","09-09-2024 21:12:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003035785","E=
mana","","09-09-2024 21:10:47","09-09-2024 20:54:36","09-09-2024 22:52:09",=
"Grid Outage//Grid Power Return","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Outage Issue","Grid Outage//Grid Power Return","kouoh.jean@ih=
stowers.com","973","09-09-2024 21:10:47","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003035634","Bas=
tos Ekoudou","","09-09-2024 20:39:59","09-09-2024 17:44:14","09-09-2024 18:=
21:14","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automaticaly","Mboua Thierry","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen start automaticaly","k=
ouoh.jean@ihstowers.com","25801","09-09-2024 20:39:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003035633","S=
ous Prefecture","","09-09-2024 20:39:40","09-09-2024 20:21:12","09-09-2024 =
20:31:37","Grid Outage Gen failed to start due to AVR Faulty// He replaced =
the AVR on site and Manually Started the Gen (the site still down at OCM af=
ter the power reset DONE the RM Alain from huawei is informed","Fanda Brice=
","Equipment Repair","Passive","ACDG Gen","ACDG - AVR","Grid Outage Gen fai=
led to start due to AVR Faulty// He replaced the AVR on site and Manually S=
tarted the Gen (the site still down at OCM after the power reset DONE the R=
M Alain from huawei is informed.)","kouoh.jean@ihstowers.com","1109","09-09=
-2024 20:39:40","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0003035527","San=
ta Barbara Gottam","","09-09-2024 20:23:54","09-09-2024 20:06:35","09-09-20=
24 20:38:59","Site went donw because the Battery backup take  the alarm //H=
e resert the Battery Backup (Deep investigations ongoing)","Delor Telezing"=
,"Equipment Repair","Passive","Rectifier","Rectifier Module Overloaded","Si=
te went donw because the Battery backup take  the alarm //He resert the Bat=
tery Backup (Deep investigations ongoing)","kouoh.jean@ihstowers.com","1039=
","09-09-2024 20:23:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0003035454","S=
cience","","09-09-2024 20:08:17","09-09-2024 20:00:53","09-09-2024 20:08:13=
","Active //No power issue, site is on Gen with U=3D53,2 V ,  The TX FME Mo=
uhamadou //691144435//   Huawei is informed,Notice that we have disjunction=
 at BTS OCM ","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active //No power issu=
e, site is on Gen with U=3D53,2 V ,  The TX FME Mouhamadou //691144435//   =
Huawei is informed,Notice that we have disjunction at BTS OCM ","kouoh.jean=
@ihstowers.com","445","09-09-2024 20:08:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0003035417","M=
essa-Carriere OCM","","09-09-2024 20:02:09","09-09-2024 16:53:55","09-09-20=
24 21:19:06","No power issue on site U=3D574v site on grid mohamadou of hua=
wei is informed;notice that disjonction of CB in BTS Ocm","","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site U=3D574v site on grid mohamadou of huawei is informed;=
notice that disjonction of CB in BTS Ocm","kouoh.jean@ihstowers.com","11295=
","09-09-2024 20:02:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0003035410","C=
ite-Verte","","09-09-2024 20:00:39","09-09-2024 17:11:28","09-09-2024 21:24=
:45","No power issue on site U=3D54v site on grid Brice Stague of huawei is=
 informed notice that disjunction of CB in BTS Ocm","","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site U=3D54v site on grid Brice Stague of huawei is informed noti=
ce that disjunction of CB in BTS Ocm","kouoh.jean@ihstowers.com","10152","0=
9-09-2024 20:00:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0003035402","C=
hapelle-Nsimeyong","","09-09-2024 19:58:21","09-09-2024 18:05:04","09-09-20=
24 20:13:26","Active// No power Issue Site on Grid Ubai =3D54,5V, The TX FM=
E Mbah Hosiah (674007438) is informed Notice that we have dysjunction at OC=
M equipements","MINKA NICOLAS","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site on =
Grid Ubai =3D54,5V, The TX FME Mbah Hosiah (674007438) is informed Notice t=
hat we have dysjunction at OCM equipements","kouoh.jean@ihstowers.com","679=
8","09-09-2024 19:58:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003035355","N=
sam Sofavinc T0","","09-09-2024 19:50:58","09-09-2024 18:53:38","09-09-2024=
 21:05:04","Grid ooutage site went down because Gen overload (9 KVA KVA,150=
)// Grid power return","MINKA NICOLAS","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Grid ooutage site went down because Gen overload (9 =
KVA KVA,150)// Grid power return","kouoh.jean@ihstowers.com","3441","09-09-=
2024 19:50:58","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003034690","Feb=
e Village","","09-09-2024 18:12:05","09-09-2024 16:45:50","09-09-2024 20:46=
:33","Grid Outage Gen Failed to start due to  lightning on site during Duri=
ng The Rain and (statique Charger ,Gen Card,CB eneo and Controler IPT) Faul=
ty on site//He Manually Started the Gen ","Mboua Thierry","Force Majeure","=
Natural Disaster","Thunderstrike","Equipment Damaged","Grid Outage Gen Fail=
ed to start due to  lightning on site during During The Rain and (statique =
Charger ,Gen Card,CB eneo and Controler IPT) Faulty on site//He Manually St=
arted the Gen ","kouoh.jean@ihstowers.com","18866","09-09-2024 18:12:05","S=
agemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0003034666","Mes=
sassi 2","","09-09-2024 18:06:56","09-09-2024 16:44:44","09-09-2024 18:21:4=
4","Grid Outage site went down because the Grid contactor Faulty // He bypa=
ss the Grid contactor and site on Gen","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","ATS-AMF Issue","Grid Outage site went down beca=
use the Grid contactor Faulty // He bypass the Grid contactor and site on G=
en","kouoh.jean@ihstowers.com","38900","09-09-2024 18:06:56","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0003034636","Nko=
mkana","","09-09-2024 17:58:53","09-09-2024 16:33:28","09-09-2024 18:20:28"=
,"Grid Outage No Space to deploy a MDG//Grid Restored","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid Outage No Space to =
deploy a MDG//Grid Restored","kouoh.jean@ihstowers.com","38840","09-09-2024=
 17:58:53","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0003034623","NYO=
M 2 IHS","","09-09-2024 17:56:32","09-09-2024 16:31:14","09-09-2024 22:15:4=
9","site went down because the CB (125A) tripped  in PWC due to load increa=
se//made a shunt of CB 125 and 63 A","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went=
 down because the CB (125A) tripped  in PWC due to load increase//made a sh=
unt of CB 125 and 63 A","kouoh.jean@ihstowers.com","5119","09-09-2024 17:56=
:32","Sagemcom CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0003034610","Imm=
-Olympique","","09-09-2024 17:53:36","09-09-2024 16:29:12","09-09-2024 17:4=
6:37","Grid outage,gen failed to start due to power cable alimented Gen the=
ft on sites// he Replaced the power Cable and Manually Started the Gen ","P=
aul BIBOUM","Site Asset Theft","Theft","Theft","DC Cable Stolen","Grid outa=
ge,gen failed to start due to power cable alimented Gen theft on sites// he=
 Replaced the power Cable and Manually Started the Gen ","kouoh.jean@ihstow=
ers.com","5065","09-09-2024 17:53:36","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003034519","Ess=
os Marche","","09-09-2024 17:38:41","09-09-2024 16:30:26","09-09-2024 16:35=
:04","","Delor Telezing","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active //No power issue, site is on Gr=
id with U=3D54 V","kouoh.jean@ihstowers.com","4096","09-09-2024 17:38:41","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003034503","C=
amp-Sic-Tsinga","","09-09-2024 17:35:07","09-09-2024 16:24:51","09-09-2024 =
18:19:50","Grid outage,no space to deploy a mobile DG //grid restored","","=
Grid Supply","Passive","Grid","National Grid - Low Current Supply","Grid ou=
tage,no space to deploy a mobile DG //grid restored","kouoh.jean@ihstowers.=
com","4217","09-09-2024 17:35:07","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003034497","Bas=
tos Amb Coree","","09-09-2024 17:34:27","09-09-2024 16:27:14","09-09-2024 1=
8:02:28","Grid outage,no space to deploy a mobile DG //Grid restored.","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age,no space to deploy a mobile DG //Grid restored.","kouoh.jean@ihstowers.=
com","4034","09-09-2024 17:34:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003034405","M=
fou EPC","","09-09-2024 17:23:48","09-09-2024 17:05:17","09-09-2024 23:10:5=
9","Grid ooutage site went down because Gen Gen overload (12,5 KVA,160 A)//=
 Site stabilized","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen=
","ACDG - Generator Faulty","Grid ooutage site went down because Gen Gen ov=
erload (12,5 KVA,160 A)// Site stabilized","kouoh.jean@ihstowers.com","1743=
2","09-09-2024 17:23:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0003034246","Sapeur",=
"","09-09-2024 17:04:40","09-09-2024 16:24:39","09-09-2024 18:29:59","Casca=
ded Incident from TTO2868129","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage No space to deploy //  Grid =
power return
","system","2401","09-09-2024 17:04:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0003034228","E=
-Police","IHS_YND_029","09-09-2024 17:02:46","09-09-2024 16:24:39","09-09-2=
024 18:29:59","Grid outage No space to deploy //  Grid power return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e No space to deploy //  Grid power return
","kouoh.jean@ihstowers.com","2288","09-09-2024 17:02:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003034178","N=
kolndongo","","09-09-2024 16:57:30","09-09-2024 16:11:23","09-09-2024 17:42=
:23","Grid outage Main DG faulty //Mobile DG deployed (20 kva)","MINKA NICO=
LAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Gri=
d outage Main DG faulty //Mobile DG deployed (20 kva).","kouoh.jean@ihstowe=
rs.com","2767","09-09-2024 16:57:30","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003034154","Mim=
boman3","","09-09-2024 16:54:01","09-09-2024 16:24:32","09-09-2024 16:54:50=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen started automaticaly","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen started automaticaly",=
"kouoh.jean@ihstowers.com","31762","09-09-2024 16:54:01","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003034118","Eko=
unou","","09-09-2024 16:48:53","09-09-2024 16:12:18","09-09-2024 18:08:41",=
"grid outage,gen stopped with alarm high temp//he reset the card and starte=
d it","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - High =
Engine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high=
 temp//he reset the card and started it","kouoh.jean@ihstowers.com","33327"=
,"09-09-2024 16:48:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0003033983","E=
bogo","","09-09-2024 16:33:20","09-09-2024 16:09:00","09-09-2024 16:57:23",=
"Tx issue ,site on Grid,ubaie:49; ZTE Technician: erick //696422966 was wor=
king on site.","Siligap Boris","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Tx issue ,site on Grid,ubaie:49;=
 ZTE Technician: erick //696422966 was working on site.","kouoh.jean@ihstow=
ers.com","1461","09-09-2024 16:33:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0003033846","Abang","=
","09-09-2024 16:11:31","09-09-2024 15:59:38","09-09-2024 17:00:58","Cascad=
ed Incident from TTO2867648","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site on DG due to grid ,DG stopped due=
 to low oil pressure //He added oil and maually start of DG
","system","713","09-09-2024 16:11:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0003033843","N=
kolangaa","IHS_YND_290","09-09-2024 16:10:50","09-09-2024 15:59:38","09-09-=
2024 17:00:58","Site on DG due to grid ,DG stopped due to low oil pressure =
//He added oil and maually start of DG","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Low Oil Pressure","Site on DG due to grid ,=
DG stopped due to low oil pressure //He added oil and maually start of DG
","kouoh.jean@ihstowers.com","672","09-09-2024 16:10:50","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0003033789","Nko=
abang Ebolmedjock","","09-09-2024 16:03:58","09-09-2024 15:52:26","09-09-20=
24 17:22:03","Gen only ,Gen overload(9 KVA,117A)//balanced the loads","Mba =
Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Ge=
n only ,Gen overload(9 KVA,117A)//balanced the loads","kouoh.jean@ihstowers=
.com","693","09-09-2024 16:03:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0003033610","M=
IMBOMAN LIBERTE","","09-09-2024 15:43:54","09-09-2024 15:36:42","09-09-2024=
 18:22:22","Grid outage,Main DG faulty //Mobile DG deployment 15 kva.","Mba=
 Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fa=
ulty","Grid outage,Main DG faulty //Mobile DG deployment 15 kva.","kouoh.je=
an@ihstowers.com","596","09-09-2024 15:43:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0003033582","Anguissa=
 New","","09-09-2024 15:38:41","09-09-2024 15:10:12","10-09-2024 06:35:28",=
"Cascaded Incident from TTO2867325","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage No space to deploy //G=
rid power return","system","1709","09-09-2024 15:38:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003033575","L=
abogenie","IHS_YND_568","09-09-2024 15:37:31","09-09-2024 15:10:12","10-09-=
2024 06:35:28","Grid outage No space to deploy //Grid power return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
 No space to deploy //Grid power return","kouoh.jean@ihstowers.com","1652",=
"09-09-2024 15:37:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003033565","N=
koabang2","","09-09-2024 15:35:35","09-09-2024 15:25:16","09-09-2024 15:35:=
18","Active //No power issue, site is on gen with U=3D53,2 V ,  The TX FME =
Lionel adjep//655184876//   Huawei is informed,Notice that we have disjunct=
ion at BTS OCM ","Mba Lazare Herve","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","Active //No power issue, si=
te is on gen with U=3D53,2 V ,  The TX FME Lionel adjep//655184876//   Huaw=
ei is informed,Notice that we have disjunction at BTS OCM ","kouoh.jean@ihs=
towers.com","620","09-09-2024 15:35:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003033552","M=
imboman-Village","","09-09-2024 15:33:58","09-09-2024 15:20:52","09-09-2024=
 20:56:24","","Mba Lazare Herve","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","grid outage, site down before gen start d=
ue to poor backup and PWC switched off//gen started manaually","kouoh.jean@=
ihstowers.com","787","09-09-2024 15:33:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003033483","ELOUMDEM=
 CARRIERE","","09-09-2024 15:24:40","09-09-2024 14:26:18","09-09-2024 16:39=
:26","Cascaded Incident from TTO2867197","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage,gen failed to start=
 due to gen overload(20kva,370A)//he reduice two rack of battery and two re=
ctifier","system","3502","09-09-2024 15:24:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003033485","Afanoya"=
,"","09-09-2024 15:24:40","09-09-2024 14:26:18","09-09-2024 16:39:26","Casc=
aded Incident from TTO2867197","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage,gen failed to start due to=
 gen overload(20kva,370A)//he reduice two rack of battery and two rectifier=
","system","3502","09-09-2024 15:24:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003033484","MBALNGON=
G LYCEE","","09-09-2024 15:24:40","09-09-2024 14:26:18","09-09-2024 16:39:2=
6","Cascaded Incident from TTO2867197","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage,gen failed to start d=
ue to gen overload(20kva,370A)//he reduice two rack of battery and two rect=
ifier","system","3502","09-09-2024 15:24:40","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003033342","N=
yanon","","09-09-2024 15:01:42","09-09-2024 14:34:22","09-09-2024 14:40:26"=
,"No power issue on site U=3D55 V site on Gen The TX FME Gr=E9goire //65454=
7479// from huawei is informed (Repetitive issue)","TIENTCHEU NZETCHIEU GAE=
L","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue on site U=3D55 V site on Gen The TX FME Gr=E9=
goire //654547479// from huawei is informed (Repetitive issue)","kouoh.jean=
@ihstowers.com","1642","09-09-2024 15:01:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003033269","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","09-09-2024 14:49:24","09-09-=
2024 14:26:18","09-09-2024 16:39:26","grid outage,gen failed to start due t=
o gen overload(20kva,370A)//he reduice two rack of battery and two rectifie=
r","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overloa=
d","grid outage,gen failed to start due to gen overload(20kva,370A)//he red=
uice two rack of battery and two rectifier","kouoh.jean@ihstowers.com","138=
7","09-09-2024 14:49:24","Sagemcom CMR"
"Closed Complete","Warning","T0602","IHS_YND_259","NOCINC0003032953","Simbo=
ck MTN","","09-09-2024 14:00:59","","","site on alarm due to grid outage//g=
en started","Fanda Brice","Warning","Warning","POWER","Warning - Site on Ba=
ttery","site on alarm due to grid outage//gen started","kombi.samuel@ihstow=
ers.com","8","09-09-2024 14:00:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0003032869","S=
ous Prefecture","","09-09-2024 13:52:51","09-09-2024 13:47:45","09-09-2024 =
13:55:26","Active// No power issue, site is on grid with Ubaie=3D54,6V The =
Tx FME Lionel tchatchoua //694693436 from Huawei is informed","Fanda Brice"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active// No power issue, site is on grid with Ubaie=3D54,6V Th=
e Tx FME Lionel tchatchoua //694693436 from Huawei is informed","emmanuel.g=
hani@ihstowers.com","307","09-09-2024 13:52:51","Sagemcom CMR"
"Closed Complete","Warning","T0602","IHS_YND_259","NOCINC0003032744","Simbo=
ck MTN","","09-09-2024 13:37:33","","","site on alarm due to grid outage//g=
en started and alarm cleared","Fanda Brice","Warning","Warning","POWER","Wa=
rning - Site on Battery","site on alarm due to grid outage//gen started and=
 alarm cleared","kombi.samuel@ihstowers.com","14","09-09-2024 13:37:33","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0844","IHS_YND_433","NOCINC0003032725","Ngu=
ila","IHS_YND_434, IHS_YND_444","09-09-2024 13:32:58","09-09-2024 13:25:54"=
,"10-09-2024 02:20:03","No power  issue U=3D50,7 V  site on Gen The TxFMe G=
r=E9goire//652070658 is informed ,Site up 01:33 PM","Parker Tchoup","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power  issue U=3D50,7 V  site on Gen The TxFMe Gr=E9goire//65207065=
8 is informed ,Site up 01:33 PM.","joelle.ekessi@ihstowers.com","425","09-0=
9-2024 13:32:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003032721","S=
OA UNIVERSITY STADIUM","","09-09-2024 13:30:40","09-09-2024 13:09:27","09-0=
9-2024 13:10:30","Active// No power issue on site U=3D54,9v site on Gen Tea=
m Erick/696422966/ZTE working on site // soa university","Siligap Boris","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active// No power issue on site U=3D54,9v site on Gen Team Erick/=
696422966/ZTE working on site // soa university","kombi.samuel@ihstowers.co=
m","1274","09-09-2024 13:30:40","Sagemcom CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0003032648","Odz=
a petit marche new","","09-09-2024 13:20:16","09-09-2024 13:13:10","09-09-2=
024 14:45:12","Site down due to one rectifier faulty// Rectifier replaced",=
"Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module"=
,"Site down due to one rectifier faulty// Rectifier replaced","joelle.ekess=
i@ihstowers.com","427","09-09-2024 13:20:16","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0003032570","Tsi=
nga","","09-09-2024 13:10:44","09-09-2024 13:05:38","09-09-2024 13:29:52","=
","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Battery Low","grid outage, site down before gen start due to poor back=
up//gen started","joelle.ekessi@ihstowers.com","411","09-09-2024 13:10:44",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0003032538","Saa","",=
"09-09-2024 13:04:51","09-09-2024 13:00:48","09-09-2024 13:57:30","Cascaded=
 Incident from TTO2866041","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down due to insufficient of recti=
fier on site // site stabilized","system","243","09-09-2024 13:04:51","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0003032537","SAA Entr=
ance","","09-09-2024 13:04:50","09-09-2024 13:00:48","09-09-2024 13:57:30",=
"Cascaded Incident from TTO2866041","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down due to insufficient=
 of rectifier on site // site stabilized","system","242","09-09-2024 13:04:=
50","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0003032534","SAA=
 2","IHS_YND_542, IHS_YND_405","09-09-2024 13:03:54","09-09-2024 13:00:48",=
"09-09-2024 13:57:30","site went down due to insufficient of rectifier on s=
ite // site stabilized","Parker Tchoup","Equipment Repair","Passive","Recti=
fier","Rectifier Module","site went down due to insufficient of rectifier o=
n site // site stabilized","joelle.ekessi@ihstowers.com","187","09-09-2024 =
13:03:54","Sagemcom CMR"
"Closed Complete","Site Down","T2596","IHS_YND_746","NOCINC0003032255","Meh=
anda 1","","09-09-2024 12:34:29","09-09-2024 12:32:21","09-09-2024 13:36:40=
","Grid Bad Voltage and Gen Failed to start and Site wend down due to lack =
on 02 phases on site //He make the bridge on good phase ","Albran Byorel","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id Bad Voltage and Gen Failed to start and Site wend down due to lack on 02=
 phases on site //He make the bridge on good phase ","joelle.ekessi@ihstowe=
rs.com","129","09-09-2024 12:34:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_721","NOCINC0003032236","VOIRIE M=
UNICIPALE YAOUNDE","","09-09-2024 12:31:51","09-09-2024 12:27:42","09-09-20=
24 12:37:42","Cascaded Incident from TTO2865677","Paul BIBOUM","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","Grid outage.no space to=
 deploy mobile gen//grid power retun","system","249","09-09-2024 12:31:51",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0003032225","E=
NAM","IHS_YND_721","09-09-2024 12:30:53","09-09-2024 12:27:42","09-09-2024 =
13:47:42","Grid outage.no space to deploy mobile gen//grid power retun","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage.no space to deploy mobile gen//grid power retun","emmanuel.ghani@ihsto=
wers.com","192","09-09-2024 12:30:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003031638","Nkolo II=
 New","","09-09-2024 11:13:10","09-09-2024 11:07:28","09-09-2024 11:27:23",=
"Cascaded Incident from TTO2864936","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause  gen failed tostart due to poor battery backup // Grid power return","=
system","342","09-09-2024 11:13:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003031612","M=
imboman-Village","IHS_YND_709","09-09-2024 11:10:39","09-09-2024 11:07:28",=
"09-09-2024 11:27:23","Grid outage, site went down because  gen failed tost=
art due to poor battery backup // Grid power return","Mba Lazare Herve","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gr=
id outage, site went down because  gen failed tostart due to poor battery b=
ackup // Grid power return","emmanuel.ghani@ihstowers.com","192","09-09-202=
4 11:10:39","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0003031544","Lob=
o 2","","09-09-2024 10:59:18","09-09-2024 10:50:13","09-09-2024 12:44:36","=
FME is on site","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Gen only Site ,Site went down be cause ,Gen star=
ted and stopped due to  Gen  overload (9 KVA,105A )//he reduice the load in=
 site","joelle.ekessi@ihstowers.com","546","09-09-2024 10:59:18","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0003031305","C=
arrefourt Nkomo","","09-09-2024 10:27:32","09-09-2024 10:22:07","09-09-2024=
 13:00:47","Active// No power issue on site U=3D52,8v site on Grid Team Eri=
ck/682840529/ZTE working on site","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// N=
o power issue on site U=3D52,8v site on Grid Team Erick/682840529/ZTE worki=
ng on site","emmanuel.ghani@ihstowers.com","326","09-09-2024 10:27:32","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0003031168","Mamb",""=
,"09-09-2024 10:08:00","09-09-2024 07:58:32","09-09-2024 08:00:00","Cascade=
d Incident from TTO2863438","Kemeni Franklin","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue site on grid with U=3D54.5v =
//site up at 08:01 AM  Etienne(695033981) from Huawei is informed","system"=
,"7768","09-09-2024 10:08:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0003031166","Ndogbess=
ol","","09-09-2024 10:08:00","09-09-2024 07:58:32","09-09-2024 08:00:00","C=
ascaded Incident from TTO2863438","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
54.5v //site up at 08:01 AM  Etienne(695033981) from Huawei is informed","s=
ystem","7768","09-09-2024 10:08:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0003031167","Ngog Map=
ubi","","09-09-2024 10:08:00","09-09-2024 07:58:32","09-09-2024 08:00:00","=
Cascaded Incident from TTO2863438","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D54.5v //site up at 08:01 AM  Etienne(695033981) from Huawei is informed"=
,"system","7768","09-09-2024 10:08:00","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0003030775","Tou=
ring Club International","","09-09-2024 09:19:34","09-09-2024 09:16:28","09=
-09-2024 09:22:38","Grid fluctuation , site went down because Gen started a=
nd stopped with alarm ""under voltage"" (alarm unprouven)//He reset Gen car=
d and started Gen","Albran Byorel","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Control Panel","Grid fluctuation , site went down because Gen start=
ed and stopped with alarm ""under voltage"" (alarm unprouven)//He reset Gen=
 card and started Gen","joelle.ekessi@ihstowers.com","187","09-09-2024 09:1=
9:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0003030741","TSINGA V=
ILLAGE 2","","09-09-2024 09:15:51","09-09-2024 09:11:27","09-09-2024 09:15:=
58","Cascaded Incident from TTO2863879","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause  gen failed tostart due to poor battery backup // Grid power return"=
,"system","264","09-09-2024 09:15:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0003030740","Melen Ba=
'aba","","09-09-2024 09:15:50","09-09-2024 09:11:27","09-09-2024 09:15:58",=
"Cascaded Incident from TTO2863879","Siligap Boris","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e  gen failed tostart due to poor battery backup // Grid power return","sys=
tem","263","09-09-2024 09:15:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0003030727","N=
kolfoulou","IHS_YND_308, IHS_YND_719","09-09-2024 09:13:31","09-09-2024 09:=
11:27","09-09-2024 09:15:58","Grid outage, site went down because  gen fail=
ed tostart due to poor battery backup // Grid power return","Siligap Boris"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"Grid outage, site went down because  gen failed tostart due to poor batte=
ry backup // Grid power return","emmanuel.ghani@ihstowers.com","125","09-09=
-2024 09:13:31","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003030724","MIM=
BOMAN LIBERTE","","09-09-2024 09:13:03","09-09-2024 09:11:59","09-09-2024 0=
9:35:26","Grid outage//MDG  15kva has deployed","Mba Lazare Herve","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MD=
G  15kva has deployed","joelle.ekessi@ihstowers.com","65","09-09-2024 09:13=
:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003030495","ELOUMDEM=
 CARRIERE 2","","09-09-2024 08:26:21","09-09-2024 08:22:27","09-09-2024 08:=
26:33","Cascaded Incident from TTO2863596","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because 03/08 =
rectifier faulty on site // He replaced the rectifier faulty","system","234=
","09-09-2024 08:26:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003030494","Eto koss=
 Yde","","09-09-2024 08:26:20","09-09-2024 08:22:27","09-09-2024 08:26:33",=
"Cascaded Incident from TTO2863596","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because 03/08 rectifi=
er faulty on site // He replaced the rectifier faulty","system","233","09-0=
9-2024 08:26:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003030492","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","09-09-2024 08:25:31","09-09-2024 08:22=
:27","09-09-2024 08:26:33","site went down because 03/08 rectifier faulty o=
n site // He replaced the rectifier faulty","Fanda Brice","Equipment Repair=
","Passive","Rectifier","Rectifier Module","site went down because 03/08 re=
ctifier faulty on site // He replaced the rectifier faulty","joelle.ekessi@=
ihstowers.com","185","09-09-2024 08:25:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003030486","Ngoum","=
","09-09-2024 08:24:01","09-09-2024 08:15:11","09-09-2024 09:46:26","Cascad=
ed Incident from TTO2863564","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid outage.gen failed to start due to al=
arm ""low oil pressure/"" we reset card GE and gen manually started ","syst=
em","530","09-09-2024 08:24:01","Sagemcom CMR"
"Closed Complete","Site Down","T0379","IHS_YND_473","NOCINC0003030464","Yok=
o MTN","IHS_YND_475","09-09-2024 08:21:17","09-09-2024 08:15:11","09-09-202=
4 09:46:26","Grid outage.gen failed to start due to alarm ""low oil pressur=
e/"" we reset card GE and gen manually started ","Parker Tchoup","Equipment=
 Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage.gen fa=
iled to start due to alarm ""low oil pressure/"" we reset card GE and gen m=
anually started ","joelle.ekessi@ihstowers.com","366","09-09-2024 08:21:17"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003030390","Eko=
unou","","09-09-2024 08:07:59","09-09-2024 08:00:55","09-09-2024 08:10:13",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen start automatically","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down befo=
re gen start due to poor battery backup // Gen start automatically","joelle=
.ekessi@ihstowers.com","425","09-09-2024 08:07:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_286","IHS_YND_381","NOCINC0003030359","B=
oumnyebel","IHS_EDA_056, IHS_YND_419, IHS_YND_376, IHS_EDA_060","09-09-2024=
 08:00:45","09-09-2024 07:58:32","09-09-2024 09:50:00","No power issue site=
 on grid with U=3D54.5v //site up at 08:01 AM  Etienne(695033981) from Huaw=
ei is informed","Kemeni Franklin","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid w=
ith U=3D54.5v //site up at 08:01 AM  Etienne(695033981) from Huawei is info=
rmed","emmanuel.ghani@ihstowers.com","134","09-09-2024 08:00:45","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003029901","Eto koss=
 Yde","","09-09-2024 06:38:00","09-09-2024 06:35:17","09-09-2024 06:41:52",=
"Cascaded Incident from TTO2862894","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,grid bad voltage and mai=
n gen faulty//grid stabilized","system","163","09-09-2024 06:38:00","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003029902","ELOUMDEM=
 CARRIERE 2","","09-09-2024 06:38:00","09-09-2024 06:35:17","09-09-2024 06:=
41:52","Cascaded Incident from TTO2862894","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,grid bad voltage =
and main gen faulty//grid stabilized","system","163","09-09-2024 06:38:00",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003029900","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","09-09-2024 06:37:21","09-09-2024 06:35=
:17","09-09-2024 06:41:52","grid outage,grid bad voltage and main gen fault=
y//grid stabilized","Fanda Brice","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","grid outage,grid bad voltage and main gen faulty/=
/grid stabilized","joelle.ekessi@ihstowers.com","125","09-09-2024 06:37:21"=
,"Sagemcom CMR"
"Closed Complete","Warning","T1851","IHS_YND_330","NOCINC0003029739","OKOA =
Peage","","09-09-2024 05:55:26","","","site alarming and gen failed to star=
t due to low fuel//refueling done","Fanda Brice","Warning","Warning","POWER=
","Warning - Low Voltage","site alarming and gen failed to start due to low=
 fuel//refueling done","dorothy.djantio@ihstowers.com","307","09-09-2024 05=
:55:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003029717","M=
ontee-Des-Soeurs","","09-09-2024 05:48:34","09-09-2024 05:43:26","09-09-202=
4 05:50:25","Active// No power Issue Site on Grid Ubai =3D54,5V, The TX FME=
 Mbah Hosiah (674007438) is informed","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
 No power Issue Site on Grid Ubai =3D54,5V, The TX FME Mbah Hosiah (6740074=
38) is informed","ludivine.ngamaleu@ihstowers.com","309","09-09-2024 05:48:=
34","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003029591","Lad=
a I Yde","","09-09-2024 05:17:02","09-09-2024 05:13:47","09-09-2024 06:49:5=
5","Grid outage site went down because Gen over load (09KVA, 110A)// Gen ma=
nually started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","Grid outage site went down because Gen over load (09KVA,=
 110A)// Gen manually started","olivier.kwedi@ihstowers.com","196","09-09-2=
024 05:17:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003028918","M=
EFOU ASSI","","09-09-2024 01:52:28","09-09-2024 01:51:50","09-09-2024 01:53=
:11","Grid Fluctuation Site went down due main gen faulty and grid bad volt=
age//grid stabilized","Fanda Brice","Grid Supply","Passive","Grid","Nationa=
l Grid - Phase Controller Faulty","Grid Fluctuation Site went down due main=
 gen faulty and grid bad voltage//grid stabilized","ludivine.ngamaleu@ihsto=
wers.com","39","09-09-2024 01:52:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0003028564","B=
ISCUITERIE","","09-09-2024 00:07:53","09-09-2024 00:02:51","09-09-2024 01:1=
1:39","Grid Fluctuation, site went down before gen start due to poor batter=
y backup and Grid bad voltage // He bypassed Grid and Started Gen Manualy",=
"Paul BIBOUM","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid Fluctuation, site went down before gen start due to poor =
battery backup and Grid bad voltage // He bypassed Grid and Started Gen Man=
ualy","ludivine.ngamaleu@ihstowers.com","302","09-09-2024 00:07:53","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0003028494","B=
ISCUITERIE","","08-09-2024 23:38:08","08-09-2024 23:31:14","08-09-2024 23:4=
4:33","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen started automaticaly","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Gen started automaticaly","=
ludivine.ngamaleu@ihstowers.com","414","08-09-2024 23:38:08","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003028347","Nko=
g-Edzen","","08-09-2024 23:14:16","08-09-2024 23:08:13","09-09-2024 00:37:1=
3","Site was on gen, site went down because gen started and stopped with 'h=
igh temp' alarm // he opened the gen flaps and manually started the gen","P=
arker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine T=
emp - Coolant Level Issue","Site was on gen, site went down because gen sta=
rted and stopped with 'high temp' alarm // he opened the gen flaps and manu=
ally started the gen","olivier.kwedi@ihstowers.com","364","08-09-2024 23:14=
:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003028198","O=
lembe-Terminus","","08-09-2024 22:48:51","08-09-2024 22:44:53","08-09-2024 =
23:24:17","Site went down because 02/03 rectifiers disfunctionned// He rese=
t the rectifiers","Fabrice Pouakam","Equipment Repair","Passive","Rectifier=
","Rectifier Distribution","Site went down because 02/03 rectifiers disfunc=
tionned// He reset the rectifiers","ludivine.ngamaleu@ihstowers.com","239",=
"08-09-2024 22:48:51","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0003028193","UPA=
C LP","","08-09-2024 22:48:13","08-09-2024 22:42:00","08-09-2024 23:37:33",=
"Active: No power issue, site is on grid with Ubaie=3D55,2V, Armand Ngetsa(=
691144412)  from Huawei is informed","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issue,=
 site is on grid with Ubaie=3D55,2V, Armand Ngetsa(691144412)  from Huawei =
is informed","olivier.kwedi@ihstowers.com","374","08-09-2024 22:48:13","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0003028175","T=
radex-Nkomo","","08-09-2024 22:42:35","08-09-2024 22:40:36","08-09-2024 23:=
36:02","ACTIVE / No power issue on site Ubaie=3D53,9V site on Grid The TX F=
ME  Lionel steve / 655184876/ From  Huawei is informed and up at 10:43 PM",=
"Albran Byorel","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","ACTIVE / No power issue on site Ubaie=3D53,9V s=
ite on Grid The TX FME  Lionel steve / 655184876/ From  Huawei is informed =
and up at 10:43 PM","ludivine.ngamaleu@ihstowers.com","119","08-09-2024 22:=
42:35","Sagemcom CMR"
"Closed Complete","Warning","T0144","IHS_YND_333","NOCINC0003028172","Mfou =
MTN","","08-09-2024 22:42:20","","","site went alarm because Gen started an=
d stopped due to the fuel and water mixture in the circuit gazoil // He pur=
ged the circuit gazoil","Mba Lazare Herve","Warning","Warning","POWER","War=
ning - Battery Low Voltage","site went alarm because Gen started and stoppe=
d due to the fuel and water mixture in the circuit gazoil // He purged the =
circuit gazoil","dorothy.djantio@ihstowers.com","243","08-09-2024 22:42:20"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003027635","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","08-09-2024 21:17:26","08-09-2024 23:29=
:03","09-09-2024 00:21:21","Grid Fluctuation Site went down due main gen fa=
ulty and grid bad voltage//grid stabilized","Fanda Brice","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid Fluctuation S=
ite went down due main gen faulty and grid bad voltage//grid stabilized","s=
tephane.nkamwa@ihstowers.com","637","08-09-2024 21:17:26","Sagemcom CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0003027452","ELO=
UMDEM CARRIERE 2","","08-09-2024 20:54:10","08-09-2024 23:29:03","09-09-202=
4 00:21:21","Site impacted by Mefou T1550.please cascaded this Ticket	","Fa=
nda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
Grid Fluctuation Site went down due main gen faulty and grid bad voltage//g=
rid stabilized","stephane.nkamwa@ihstowers.com","648","08-09-2024 20:54:10"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0003027190","Eto=
 koss Yde","","08-09-2024 20:20:39","08-09-2024 23:29:03","09-09-2024 00:21=
:21","Site impacted by Mefou T1550.please cascaded this Ticket","Fanda Bric=
e","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid Flu=
ctuation Site went down due main gen faulty and grid bad voltage//grid stab=
ilized","stephane.nkamwa@ihstowers.com","650","08-09-2024 20:20:39","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003027122","N=
sam Sofavinc T0","","08-09-2024 20:09:28","08-09-2024 19:57:22","08-09-2024=
 20:35:13","Grid outage, site went down because gen start and stopped due t=
o Gen overload(9KVA;150 A)/ / He reduice the load ,site on Gen ","MINKA NIC=
OLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outag=
e, site went down because gen start and stopped due to Gen overload(9KVA;15=
0 A)/ / He reduice the load ,site on Gen ","alexandre.kamal@ihstowers.com",=
"727","08-09-2024 20:09:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0003027064","M=
bankomo IHS","","08-09-2024 19:56:10","08-09-2024 19:43:07","08-09-2024 23:=
49:44","Active no power issue on site, site on Gen with U=3D54V Tx FME Leon=
el Tchatchou/69463436/ from huawei is informed(Site up at 19:47)","Fanda Br=
ice","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active no power issue on site, site on Gen with U=3D54V Tx=
 FME Leonel Tchatchou/69463436/ from huawei is informed(Site up at 19:47)",=
"alexandre.kamal@ihstowers.com","784","08-09-2024 19:56:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003026829","Kondengu=
i","","08-09-2024 19:23:40","08-09-2024 19:04:20","08-09-2024 22:40:38","Ca=
scaded Incident from TTO2859171","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid Outage//Grid Power Return","syst=
em","1160","08-09-2024 19:23:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003026796","E=
mombo-Tchad","IHS_YND_114","08-09-2024 19:21:27","08-09-2024 19:04:20","08-=
09-2024 22:40:38","Grid Outage//Grid Power Return","","Grid Supply","Passiv=
e","Grid","National Grid - Grid Outage Issue","Grid Outage//Grid Power Retu=
rn","alexandre.kamal@ihstowers.com","1028","08-09-2024 19:21:27","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003026667","E=
ssomba","","08-09-2024 19:00:30","08-09-2024 18:51:22","08-09-2024 20:46:08=
","Grid outage,gen failed to start due to grid bad voltage,no rcp on site//=
he bypassed Grid and  started the gen","Mba Lazare Herve","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","Grid outage,gen fa=
iled to start due to grid bad voltage,no rcp on site//he bypassed Grid and =
 started the gen","alexandre.kamal@ihstowers.com","549","08-09-2024 19:00:3=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003026391","Eto koss=
 Yde","","08-09-2024 18:26:31","08-09-2024 17:59:48","08-09-2024 18:17:55",=
"Cascaded Incident from TTO2858653","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,main gen faulty and grid=
 bad voltage//grid stabilized","system","1603","08-09-2024 18:26:31","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0003026393","MBALNGON=
G LYCEE","","08-09-2024 18:26:31","08-09-2024 17:59:48","08-09-2024 18:17:5=
5","Cascaded Incident from TTO2858653 - Cascade Removed From TTO2858653","F=
anda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"grid outage,main gen faulty and grid bad voltage//grid stabilized","system=
","1603","08-09-2024 18:26:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003026394","Afanoya"=
,"","08-09-2024 18:26:31","08-09-2024 17:59:48","08-09-2024 18:17:55","Casc=
aded Incident from TTO2858653 - Cascade Removed From TTO2858653","Hyemafo G=
ildas","Cascade Outage","Passive","Cascade Passive","Cascade Passive","grid=
 outage,main gen faulty and grid bad voltage//grid stabilized","system","16=
03","08-09-2024 18:26:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003026392","ELOUMDEM=
 CARRIERE 2","","08-09-2024 18:26:31","08-09-2024 17:59:48","08-09-2024 18:=
17:55","Cascaded Incident from TTO2858653","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,main gen faulty a=
nd grid bad voltage//grid stabilized","system","1603","08-09-2024 18:26:31"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003026390","ELOUMDEM=
 CARRIERE","","08-09-2024 18:26:31","08-09-2024 17:59:48","08-09-2024 18:17=
:55","Cascaded Incident from TTO2858653 - Cascade Removed From TTO2858653",=
"Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","grid outage,main gen faulty and grid bad voltage//grid stabilized","syst=
em","1603","08-09-2024 18:26:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_257","NOCINC0003026389","Ahala","=
IHS_YND_767, IHS_YND_765, IHS_YND_313","08-09-2024 18:26:30","08-09-2024 17=
:59:48","08-09-2024 18:50:39","Grid fluctuations,site went down before DG s=
tart : Poor Batteries backup// grid restored.","Hyemafo Gildas","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid fluct=
uations,site went down before DG start : Poor Batteries backup// grid resto=
red.","system","1602","08-09-2024 18:26:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0003026388","N=
koa Ayos","","08-09-2024 18:26:28","08-09-2024 18:14:25","08-09-2024 19:40:=
12","Grid outage,Gen stopped with alarm low oil pressure (unprouven alarm)/=
/he reset Gen Card and Manually started the Gen (investigation ongoing)","M=
INKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Press=
ure","Grid outage,Gen stopped with alarm low oil pressure (unprouven alarm)=
//he reset Gen Card and Manually started the Gen (investigation ongoing)","=
alexandre.kamal@ihstowers.com","724","08-09-2024 18:26:28","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003026373","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","08-09-2024 18:22:17","08-09-2024 17:59=
:48","08-09-2024 18:17:55","grid outage,main gen faulty and grid bad voltag=
e//grid stabilized","Fanda Brice","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","grid outage,main gen faulty and grid bad voltage/=
/grid stabilized","stephane.nkamwa@ihstowers.com","1350","08-09-2024 18:22:=
17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003026235","C=
amp-Sic-Tsinga","","08-09-2024 17:57:09","08-09-2024 17:41:04","08-09-2024 =
18:15:29","Grid Outage, No space to deploy MDG // Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No =
space to deploy MDG // Grid return","alexandre.kamal@ihstowers.com","966","=
08-09-2024 17:57:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003025991","B=
iteng","","08-09-2024 17:19:58","08-09-2024 17:12:54","08-09-2024 17:36:38"=
,"Grid Outage, site went down because Gen failed to start due to poor Backu=
p//Grid Power return","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid Outage, site went down becau=
se Gen failed to start due to poor Backup//Grid Power return","alexandre.ka=
mal@ihstowers.com","425","08-09-2024 17:19:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0003025989","P=
olytechnique","","08-09-2024 17:19:10","08-09-2024 17:12:07","08-09-2024 17=
:30:51","Grid outage ;No space to deploy MDG // Grid power return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
;No space to deploy MDG // Grid power return","alexandre.kamal@ihstowers.co=
m","424","08-09-2024 17:19:10","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0003025887","ODZ=
A MINKAN EDIBI ASSI","","08-09-2024 17:05:41","08-09-2024 16:50:31","08-09-=
2024 18:30:15","Gen only site ,Site went down because Gen failed to start d=
ue to Gen battery discharged//Gen manually started with external battery (i=
nvestigation ongoing)","Albran Byorel","Equipment Repair","Passive","ACDG G=
en","ACDG - Generator Battery","Gen only site ,Site went down because Gen f=
ailed to start due to Gen battery discharged//Gen manually started with ext=
ernal battery (investigation ongoing)","stephane.nkamwa@ihstowers.com","911=
","08-09-2024 17:05:41","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003025269","MEF=
OU ASSI","","08-09-2024 15:38:04","08-09-2024 15:33:58","08-09-2024 15:37:4=
4","grid outage,main gen faulty and grid bad voltage//grid stabilized","Fan=
da Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty"=
,"grid outage,main gen faulty and grid bad voltage//grid stabilized","steph=
ane.nkamwa@ihstowers.com","247","08-09-2024 15:38:04","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0003025122","N=
yanon","","08-09-2024 15:21:21","08-09-2024 15:07:16","08-09-2024 15:10:29"=
,"No power issue on site U=3D55 V site on Gen The TX FME Gr=E9goire  //6545=
47479//  from huawei is informed (Repetitive issue)","TIENTCHEU NZETCHIEU G=
AEL","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue on site U=3D55 V site on Gen The TX FME Gr=
=E9goire  //654547479//  from huawei is informed (Repetitive issue)","alexa=
ndre.kamal@ihstowers.com","846","08-09-2024 15:21:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0003024518","G=
olf Quater","","08-09-2024 13:43:07","08-09-2024 13:19:59","08-09-2024 14:0=
2:44","Active// No power issue on site U=3D53,1V site on Grid Team Abel/682=
840529/ZTE working on site ","Mboua Thierry","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power =
issue on site U=3D53,1V site on Grid Team Abel/682840529/ZTE working on sit=
e ","landry.etame@ihstowers.com","1388","08-09-2024 13:43:07","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0003024457","Mamch Bu=
ilding","","08-09-2024 13:36:40","08-09-2024 13:29:38","08-09-2024 13:45:27=
","Cascaded Incident from TTO2856335","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage//grid return","syste=
m","422","08-09-2024 13:36:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0003024454","C=
harles-Atangana","IHS_YND_051","08-09-2024 13:35:53","08-09-2024 13:29:38",=
"08-09-2024 13:45:27","grid outage//grid return","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","grid outage//grid return","lan=
dry.etame@ihstowers.com","376","08-09-2024 13:35:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0003024421","H=
-Paradis","IHS_YND_506","08-09-2024 13:31:14","08-09-2024 13:15:07","08-09-=
2024 13:38:05","grid outage//grid return","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","grid outage//grid return","landry.eta=
me@ihstowers.com","968","08-09-2024 13:31:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003024409","O=
mnisport-Rail","","08-09-2024 13:28:58","08-09-2024 13:15:07","08-09-2024 1=
3:38:05","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","grid outage//grid return","landry.etame@ihstowers.com","1=
014","08-09-2024 13:28:58","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003024376","Bas=
tos Amb Coree","","08-09-2024 13:21:31","08-09-2024 13:09:18","08-09-2024 1=
3:43:18","Grid outage, no space to deploy mobil DG //  Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
, no space to deploy mobil DG //  Grid return","kouoh.jean@ihstowers.com","=
735","08-09-2024 13:21:31","Sagemcom CMR"
"Closed Complete","Site Down","T3231","IHS_YND_743","NOCINC0003024342","Ngo=
usso Vallee","","08-09-2024 13:14:19","08-09-2024 12:57:04","08-09-2024 13:=
37:06",".Grid hyrid Gen site ,Grid outage Site went down because Gen failed=
 to start due to Hybrid system dysfonction//Grid power return","Siligap Bor=
is","Equipment Repair","Passive","Hybrid","Hybrid Module",".Grid hyrid Gen =
site ,Grid outage Site went down because Gen failed to start due to Hybrid =
system dysfonction//Grid power return","kouoh.jean@ihstowers.com","1035","0=
8-09-2024 13:14:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0003023865","M=
essassi 2","","08-09-2024 11:53:32","08-09-2024 11:43:15","08-09-2024 12:47=
:17","grid outage,gen stopped with alarm high temp//he added water in  radi=
ator","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Hig=
h Engine Temp - Coolant Level Issue","grid outage,gen stopped with alarm hi=
gh temp//he added water in  radiator","landry.etame@ihstowers.com","869","0=
8-09-2024 11:53:32","Sagemcom CMR"
"Closed Complete","Warning","T1739","IHS_YND_691","NOCINC0003023782","Mball=
a 2 REGIE","","08-09-2024 11:38:59","","","site on alarm because gen failed=
 to sart due to battery discharged //he sarted with battery backup","Delor =
Telezing","Warning","Warning","POWER","Warning - Site on Battery","site on =
alarm because gen failed to sart due to battery discharged //he sarted with=
 battery backup","nadjia.njaya@ihstowers.com","389","08-09-2024 11:38:59","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003023758","N=
koabang2","","08-09-2024 11:36:59","08-09-2024 11:21:51","08-09-2024 12:02:=
26","grid outage,gen ran till fuel shortage//Refueling done","Mba Lazare He=
rve","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran =
till fuel shortage//Refueling done","landry.etame@ihstowers.com","908","08-=
09-2024 11:36:59","Sagemcom CMR"
"Closed Complete","Warning","CTR_395","IHS_YND_249","NOCINC0003023540","Bit=
eng-Maetur","","08-09-2024 10:55:19","","","Site on alarm due to grid bad v=
oltage//he put the site on gen","Mba Lazare Herve","Warning","Warning","POW=
ER","Warning - Site on Battery","Site on alarm due to grid bad voltage//he =
put the site on gen","nadjia.njaya@ihstowers.com","309","08-09-2024 10:55:1=
9","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003023522","Nkolo II=
 New","","08-09-2024 10:53:40","08-09-2024 10:44:27","08-09-2024 11:08:03",=
"Cascaded Incident from TTO2855220","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site down before G=
en to start due to poor backup before //Gen started automatically","system"=
,"553","08-09-2024 10:53:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003023501","M=
imboman-Village","IHS_YND_709","08-09-2024 10:52:38","08-09-2024 10:44:27",=
"08-09-2024 11:08:03","Grid outage, site down before Gen to start due to po=
or backup before //Gen started automatically","Mba Lazare Herve","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge, site down before Gen to start due to poor backup before //Gen started a=
utomatically","landry.etame@ihstowers.com","492","08-09-2024 10:52:38","Sag=
emcom CMR"
"Closed Complete","Warning","CTR_315","IHS_YND_292","NOCINC0003023488","Bit=
oto","","08-09-2024 10:51:00","","","Site on alarm due to grid bad voltage/=
/he put the site on gen","Mba Lazare Herve","Warning","Warning","POWER","Wa=
rning - Site on Battery","Site on alarm due to grid bad voltage//he put the=
 site on gen","nadjia.njaya@ihstowers.com","328","08-09-2024 10:51:00","Sag=
emcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003023452","MIM=
BOMAN LIBERTE","","08-09-2024 10:46:39","08-09-2024 10:40:24","08-09-2024 1=
1:46:59","Grid outage//MDG of 15 kva has deployed","Mba Lazare Herve","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage/=
/MDG of 15 kva has deployed","kouoh.jean@ihstowers.com","376","08-09-2024 1=
0:46:39","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003023159","Mim=
boman3","","08-09-2024 09:50:34","08-09-2024 09:44:22","08-09-2024 09:56:01=
","Grid Outage, site went down because Gen failed to start due to poor Back=
up // Gen started automatically","Mba Lazare Herve","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid Outage, the site =
went down because Gen failed to start due to poor Backup // Gen started aut=
omatically","kouoh.jean@ihstowers.com","373","08-09-2024 09:50:34","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_369","IHS_YND_019","NOCINC0003023150","H=
otel de Ville Yde","","08-09-2024 09:47:21","08-09-2024 09:34:05","08-09-20=
24 11:13:02","","Paul BIBOUM","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","grid outage//MDG 13 kva deployed","landry.etame@ihstower=
s.com","2660","08-09-2024 09:47:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0003023144","N=
R-Bastos","IHS_YND_019","08-09-2024 09:46:21","08-09-2024 09:34:05","08-09-=
2024 11:13:02","grid outage//MDG 13 kva deployed","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","grid outage//MDG 13 kva deplo=
yed","landry.etame@ihstowers.com","737","08-09-2024 09:46:21","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0003023128","A=
kak-Nkozoa-MTN-IHS","","08-09-2024 09:43:32","08-09-2024 09:09:26","08-09-2=
024 09:10:56","No power isue site on grid with U=3D54v Symphorien(650527151=
) from Huawei is informed ","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power isue sit=
e on grid with U=3D54v Symphorien(650527151) from Huawei is informed ","lan=
dry.etame@ihstowers.com","2047","08-09-2024 09:43:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003023018","ELOUMDEM=
 CARRIERE 2","","08-09-2024 09:27:00","08-09-2024 09:08:17","08-09-2024 09:=
12:17","Cascaded Incident from TTO2854631","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,main gen faulty a=
nd grid bad voltage//grid stabilized","system","1123","08-09-2024 09:27:00"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003023017","Eto koss=
 Yde","","08-09-2024 09:27:00","08-09-2024 09:08:17","08-09-2024 09:12:17",=
"Cascaded Incident from TTO2854631","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,main gen faulty and grid=
 bad voltage//grid stabilized","system","1123","08-09-2024 09:27:00","Sagem=
com CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003023010","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","08-09-2024 09:24:51","08-09-2024 09:08=
:17","08-09-2024 09:12:17","grid outage,main gen faulty and grid bad voltag=
e//grid stabilized","Fanda Brice","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","grid outage,main gen faulty and grid bad voltage/=
/grid stabilized","kouoh.jean@ihstowers.com","995","08-09-2024 09:24:51","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003022718","B=
iteng","","08-09-2024 08:24:43","08-09-2024 08:17:32","08-09-2024 08:18:54"=
,"Active: No power issue, site is on Grid with U=3D54,4V ,  The TX FME Lion=
el adjep//655184876//  Huawei is informed Notice that we have dysjunction a=
t OCM equipements site up at 09:02 AM","Mba Lazare Herve","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue, site is on Grid with U=3D54,4V ,  The TX FME Lionel adje=
p//655184876//  Huawei is informed Notice that we have dysjunction at OCM e=
quipements site up at 09:02 AM","landry.etame@ihstowers.com","431","08-09-2=
024 08:24:43","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0003022645","OLA=
MA","","08-09-2024 08:14:42","08-09-2024 08:07:20","08-09-2024 09:58:01","g=
rid outage,gen ran till fuel shortage//Refueling done","Fanda Brice","Fuel =
Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran till fuel s=
hortage//Refueling done","kouoh.jean@ihstowers.com","443","08-09-2024 08:14=
:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0003022644","C=
amp-Sic-Tsinga","","08-09-2024 08:14:16","08-09-2024 08:07:11","08-09-2024 =
14:33:22","Grid outage ,No space to deploy MDG //Grid power return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
 ,No space to deploy MDG //Grid power return","landry.etame@ihstowers.com",=
"426","08-09-2024 08:14:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0003021937","Kondengu=
i","","08-09-2024 05:07:50","08-09-2024 05:00:42","08-09-2024 07:44:00","Ca=
scaded Incident from TTO2853339","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage//Grid return","system","4=
28","08-09-2024 05:07:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0003021936","E=
mombo-Tchad","IHS_YND_114","08-09-2024 05:07:00","08-09-2024 05:00:42","08-=
09-2024 07:44:00","Grid outage//Grid return","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid outage//Grid return","ange.ko=
ngo@ihstowers.com","379","08-09-2024 05:07:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003021677","E=
ssomba","","08-09-2024 03:57:58","08-09-2024 03:33:55","08-09-2024 05:15:09=
","Grid outage, site went down because gen failed to start due to card gen =
dysfunction // gen manually started","Mba Lazare Herve","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down be=
cause gen failed to start due to card gen dysfunction // gen manually start=
ed","ange.kongo@ihstowers.com","1444","08-09-2024 03:57:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_011","IHS_YND_196","NOCINC0003021426","P=
DC","","08-09-2024 02:03:12","08-09-2024 01:45:03","08-09-2024 01:50:03","A=
ctive//No power issue site on grid with U=3D54,5V .Eloundou Bertrand(693212=
405) from Huawei is informed","Mboua Thierry","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power =
issue site on grid with U=3D54,5V .Eloundou Bertrand(693212405) from Huawei=
 is informed","ange.kongo@ihstowers.com","1090","08-09-2024 02:03:12","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003021210","Lobo OCM=
","","08-09-2024 00:48:40","08-09-2024 00:43:02","08-09-2024 00:49:02","Cas=
caded Incident from TTO2852469","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // gen start automatically","s=
ystem","338","08-09-2024 00:48:40","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003021206","N=
KOMEKUI OCM","IHS_YND_341","08-09-2024 00:47:09","08-09-2024 00:43:02","08-=
09-2024 00:49:02","Grid outage, site went down before gen start due to poor=
 battery backup // gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, site went down before gen start due to poor battery backup // gen=
 start automatically","ange.kongo@ihstowers.com","247","08-09-2024 00:47:09=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003020582","B=
iteng","","07-09-2024 22:08:37","07-09-2024 21:35:30","07-09-2024 21:40:30"=
,"No power issue on site U=3D54,5v site on grid Lionel steve / 655184876/ F=
rom  Huawei is informed","Mba Lazare Herve","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D54,5v site on grid Lionel steve / 655184876/ From  Huawei is inform=
ed","ludivine.ngamaleu@ihstowers.com","1988","07-09-2024 22:08:37","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003020022","B=
iteng","","07-09-2024 21:00:14","07-09-2024 20:32:04","07-09-2024 21:08:01"=
,"Grid Outage, site went down because Gen failed to start due to poor Backu=
p//Grid Power return","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid Outage, site went down becau=
se Gen failed to start due to poor Backup//Grid Power return","etienne.iton=
do@ihstowers.com","1691","07-09-2024 21:00:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003019720","B=
iteng","","07-09-2024 20:02:21","07-09-2024 19:57:14","07-09-2024 20:07:00"=
,"Grid Outage, site went down because Gen failed to start due to poor Backu=
p//Grid power return","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid Outage, site went down becau=
se Gen failed to start due to poor Backup//Grid power return","ludivine.nga=
maleu@ihstowers.com","308","07-09-2024 20:02:21","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003019686","Nko=
mo stade","","07-09-2024 19:55:36","07-09-2024 19:45:19","07-09-2024 20:03:=
23","Site went down due to Insufficient of rectifier on site (03/04)// Site=
 stabilized","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to Insufficient of rectifier on site (=
03/04)// Site stabilized","olivier.kwedi@ihstowers.com","618","07-09-2024 1=
9:55:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0003019472","T=
radex-Nkomo","","07-09-2024 19:20:55","07-09-2024 19:12:51","07-09-2024 21:=
27:42","ACTIVE / No power issue on site Ubaie=3D53,1V site on Grid The TX F=
ME  Lionel steve / 655184876/ From  Huawei is informed ","Albran Byorel","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE / No power issue on site Ubaie=3D53,1V site on Grid The TX=
 FME  Lionel steve / 655184876/ From  Huawei is informed ","ludivine.ngamal=
eu@ihstowers.com","485","07-09-2024 19:20:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0003019468","Marche O=
dza","","07-09-2024 19:20:01","07-09-2024 19:05:03","07-09-2024 20:07:08","=
Cascaded Incident from TTO2850394","Albran Byorel","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage, site went down because=
 Gen failed to start due to poor Backup//He started Gen started manualy","s=
ystem","898","07-09-2024 19:20:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_254","NOCINC0003019467","Mvog-Man=
ga","","07-09-2024 19:20:00","07-09-2024 19:05:03","07-09-2024 20:07:08","C=
ascaded Incident from TTO2850394","Albran Byorel","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage, site went down because =
Gen failed to start due to poor Backup//He started Gen started manualy","sy=
stem","897","07-09-2024 19:20:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003019466","ELOUMDEM=
 CARRIERE 2","","07-09-2024 19:19:30","07-09-2024 19:15:12","07-09-2024 19:=
19:58","Cascaded Incident from TTO2850409","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Fluctuation, site went d=
own because Main Gen Faulty//Grid Stabilized","system","258","07-09-2024 19=
:19:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003019465","Eto koss=
 Yde","","07-09-2024 19:19:30","07-09-2024 19:15:12","07-09-2024 19:19:58",=
"Cascaded Incident from TTO2850409","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Fluctuation, site went down bec=
ause Main Gen Faulty//Grid Stabilized","system","258","07-09-2024 19:19:30"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003019463","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","07-09-2024 19:18:20","07-09-2024 19:15=
:12","07-09-2024 19:19:58","Grid Fluctuation, site went down because Main G=
en Faulty//Grid Stabilized","Fanda Brice","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Grid Fluctuation, site went down b=
ecause Main Gen Faulty//Grid Stabilized","olivier.kwedi@ihstowers.com","189=
","07-09-2024 19:18:20","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003019457","Eko=
unou","","07-09-2024 19:15:45","07-09-2024 19:06:38","07-09-2024 19:16:44",=
"Grid outage, site went down because  Gen failed to start due to poor batte=
ry backup // Grid Power return","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n because  Gen failed to start due to poor battery backup // Grid Power ret=
urn","olivier.kwedi@ihstowers.com","548","07-09-2024 19:15:45","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0003019450","O=
dza","IHS_YND_254, IHS_YND_580","07-09-2024 19:13:08","07-09-2024 19:05:03"=
,"07-09-2024 20:07:08","Grid Outage, site went down because Gen failed to s=
tart due to poor Backup//He started Gen started manualy","Albran Byorel","E=
quipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","G=
rid Outage, site went down because Gen failed to start due to poor Backup//=
He started Gen started manualy","ludivine.ngamaleu@ihstowers.com","485","07=
-09-2024 19:13:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0003019193","O=
lembe-Terminus","","07-09-2024 18:23:37","07-09-2024 18:19:33","07-09-2024 =
19:28:54","Site went down because rectifier disfunctionned(2/3)// He reset =
the rectifier","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","=
Rectifier Distribution","Site went down because rectifier disfunctionned(2/=
3)// He reset the rectifier","ludivine.ngamaleu@ihstowers.com","245","07-09=
-2024 18:23:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_051","NOCINC0003018814","Nyanon",=
"","07-09-2024 17:28:47","07-09-2024 15:53:05","07-09-2024 15:54:05","Casca=
ded Incident from TTO2849603","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","Impacted by Souza OCM that is no=
t manageg by IHS-IENG","system","5742","07-09-2024 17:28:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0003018386","M=
om","","07-09-2024 16:11:52","07-09-2024 15:49:45","07-09-2024 15:53:42","G=
rid Outage, Site went down because Gen failed to start due Solenoid valve f=
aulty// He started Gen manualy","Fanda Brice","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Solenoid Coil","Grid Outage, Site went down because Gen =
failed to start due Solenoid valve faulty// He started Gen manualy","etienn=
e.itondo@ihstowers.com","1328","07-09-2024 16:11:52","Sagemcom CMR"
"Closed Complete","Warning","CTR_213","IHS_YND_247","NOCINC0003018326","Oko=
lo","","07-09-2024 15:56:41","","","Site alarming on battery because Techni=
cian Fabrice/657108613/Sagemcom/working on site""Drain""//End of work","Fab=
rice Pouakam","Warning","Warning","POWER","Warning - Site on Battery","Site=
 alarming on battery because Technician Fabrice/657108613/Sagemcom/working =
on site""Drain""//End of work","dorothy.djantio@ihstowers.com","366","07-09=
-2024 15:56:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0003018325","G=
olf Quater","","07-09-2024 15:56:17","07-09-2024 15:50:12","07-09-2024 17:4=
6:56","ACTIVE / No power issue on site Ubaie=3D53,1V site on Grid Team  Abe=
l/682840529/ZTE working on site ""Swapp""","Mboua Thierry","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTI=
VE / No power issue on site Ubaie=3D53,1V site on Grid Team  Abel/682840529=
/ZTE working on site ""Swapp""","ludivine.ngamaleu@ihstowers.com","365","07=
-09-2024 15:56:17","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0003018315","Nko=
g-Edzen","","07-09-2024 15:54:03","07-09-2024 15:23:44","07-09-2024 16:19:1=
1","Active: No power issue site on Battery with U=3D52.4 V  ( start thresho=
ld =3D50 V)The Tx Fme  Gregoire(654547479) from Huawei is informed","Parker=
 Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active: No power issue site on Battery with U=3D52.4 V=
  ( start threshold =3D50 V)The Tx Fme  Gregoire(654547479) from Huawei is =
informed","olivier.kwedi@ihstowers.com","1820","07-09-2024 15:54:03","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003018192","Matsari"=
,"","07-09-2024 15:35:41","07-09-2024 15:21:20","07-09-2024 15:26:01","Casc=
aded Incident from TTO2848862","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active// No power issue on site U=3D49,3V(=
start threshold ubai=3D49,2V) site on Battery Team DIAKITE NAKAN/652369313/=
HUAWEI working on site","system","861","07-09-2024 15:35:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003018191","MBIMBIM"=
,"","07-09-2024 15:35:41","07-09-2024 15:21:20","07-09-2024 15:26:01","Casc=
aded Incident from TTO2848862","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active// No power issue on site U=3D49,3V(=
start threshold ubai=3D49,2V) site on Battery Team DIAKITE NAKAN/652369313/=
HUAWEI working on site","system","861","07-09-2024 15:35:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003018194","Ngouetou=
","","07-09-2024 15:35:41","07-09-2024 15:21:20","07-09-2024 15:26:01","Cas=
caded Incident from TTO2848862","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// No power issue on site U=3D49,3V=
(start threshold ubai=3D49,2V) site on Battery Team DIAKITE NAKAN/652369313=
/HUAWEI working on site","system","861","07-09-2024 15:35:41","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003018193","Ngoum","=
","07-09-2024 15:35:41","07-09-2024 15:21:20","07-09-2024 15:26:01","Cascad=
ed Incident from TTO2848862","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active// No power issue on site U=3D49,3V(st=
art threshold ubai=3D49,2V) site on Battery Team DIAKITE NAKAN/652369313/HU=
AWEI working on site","system","861","07-09-2024 15:35:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0003018195","Yoko MTN=
","","07-09-2024 15:35:41","07-09-2024 15:21:20","07-09-2024 15:26:01","Cas=
caded Incident from TTO2848862","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active// No power issue on site U=3D49,3V=
(start threshold ubai=3D49,2V) site on Battery Team DIAKITE NAKAN/652369313=
/HUAWEI working on site","system","861","07-09-2024 15:35:41","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0003018190","Nguila",=
"","07-09-2024 15:35:40","07-09-2024 15:21:20","07-09-2024 15:26:01","Casca=
ded Incident from TTO2848862","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active// No power issue on site U=3D49,3V(s=
tart threshold ubai=3D49,2V) site on Battery Team DIAKITE NAKAN/652369313/H=
UAWEI working on site","system","860","07-09-2024 15:35:40","Sagemcom CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0003018152","Don=
g","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_454, IHS_YN=
D_473","07-09-2024 15:31:26","07-09-2024 15:21:20","07-09-2024 17:16:01","A=
ctive// No power issue on site U=3D49,3V(start threshold ubai=3D49,2V) site=
 on Battery Team DIAKITE NAKAN/652369313/HUAWEI working on site","Parker Tc=
houp","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active// No power issue on site U=3D49,3V(start threshold=
 ubai=3D49,2V) site on Battery Team DIAKITE NAKAN/652369313/HUAWEI working =
on site","olivier.kwedi@ihstowers.com","607","07-09-2024 15:31:26","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003018064","F=
ebe Village","","07-09-2024 15:18:58","07-09-2024 15:18:55","07-09-2024 16:=
52:53","Grid Fluctuation, site went down because Gen failed to start due to=
 Poor backup//He make a bridge on the good phase","Mboua Thierry","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid Fluct=
uation, site went down because Gen failed to start due to Poor backup//He m=
ake a bridge on the good phase","ludivine.ngamaleu@ihstowers.com","4","07-0=
9-2024 15:18:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0003017974","T=
alla Monatele","","07-09-2024 14:57:48","07-09-2024 14:54:42","07-09-2024 1=
6:34:39","Active //No power issue on site ,site on Grid with Ubaie=3D55.1 V=
  The Tx FMe Gr=E9goire//652070658 is informed ,Site up 02:59  PM","Parker =
Tchoup","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active //No power issue on site ,site on Grid with Ubai=
e=3D55.1 V  The Tx FMe Gr=E9goire//652070658 is informed ,Site up 02:59  PM=
","ludivine.ngamaleu@ihstowers.com","187","07-09-2024 14:57:48","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003017807","B=
ATA-Mokolo","","07-09-2024 14:30:41","07-09-2024 14:29:37","07-09-2024 15:2=
2:45","site went down because insufficiency of rectifiers due to increase l=
oad// site Stabilized(Rectifiers to be replaced)","","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","site went down because insufficiency=
 of rectifiers due to increase load// site Stabilized(Rectifiers to be repl=
aced)","ludivine.ngamaleu@ihstowers.com","65","07-09-2024 14:30:41","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0003017804","T=
radex-Nkomo","","07-09-2024 14:29:18","07-09-2024 14:22:13","07-09-2024 19:=
01:18","ACTIVE / No power issue on site Ubaie=3D53,1V site on Grid The TX F=
ME  Lionel steve / 655184876/ From  Huawei is informed and up at 02:33 PM",=
"Albran Byorel","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","ACTIVE / No power issue on site Ubaie=3D53,1V s=
ite on Grid The TX FME  Lionel steve / 655184876/ From  Huawei is informed =
and up at 02:33 PM","ludivine.ngamaleu@ihstowers.com","425","07-09-2024 14:=
29:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0003017609","Sapeur",=
"","07-09-2024 13:49:10","07-09-2024 13:39:19","07-09-2024 14:06:37","Casca=
ded Incident from TTO2848198","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid Outage, No space to deploy a MDG //=
 Grid Power return","system","591","07-09-2024 13:49:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0003017599","E=
-Police","IHS_YND_029","07-09-2024 13:47:05","07-09-2024 13:39:19","07-09-2=
024 14:06:37","Grid Outage, No space to deploy a MDG // Grid Power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 Outage, No space to deploy a MDG // Grid Power return","alexandre.kamal@ih=
stowers.com","467","07-09-2024 13:47:05","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003017403","Nsi=
meyong Shell","","07-09-2024 13:08:28","07-09-2024 12:53:13","07-09-2024 13=
:11:43","Grid outage, site went down because  Gen failed to start due to po=
or battery backup //Gen manually started","MINKA NICOLAS","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, sit=
e went down because  Gen failed to start due to poor battery backup //Gen m=
anually started","stephane.nkamwa@ihstowers.com","916","07-09-2024 13:08:28=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_008","IHS_YND_068","NOCINC0003017042","N=
disamba","","07-09-2024 12:07:31","07-09-2024 11:58:59","08-09-2024 03:27:0=
9","Access issue due to Landlord,grid outage,gen failed to start due to low=
 fuel//grid return","MINKA NICOLAS","Access Denial","Lease Or Legal","Landl=
ord Related Issues","Access Issue - Land Lord","Access issue due to Landlor=
d,grid outage,gen failed to start due to low fuel//grid return","alexandre.=
kamal@ihstowers.com","513","07-09-2024 12:07:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0003016892","A=
n-Marche-Melen","","07-09-2024 11:44:19","07-09-2024 11:34:59","07-09-2024 =
14:13:39","Grid outage,No space to deploy a mobil gen //grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e,No space to deploy a mobil gen //grid return","alexandre.kamal@ihstowers.=
com","561","07-09-2024 11:44:19","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0003016828","Mom=
","","07-09-2024 11:37:08","07-09-2024 11:16:59","07-09-2024 12:20:37","Gri=
d Outage, Site went down because Gen failed to start due Solenoid valve fau=
lty// He started Gen manualy","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Solenoid Coil","Grid Outage, Site went down because Gen fa=
iled to start due Solenoid valve faulty// He started Gen manualy","stephane=
.nkamwa@ihstowers.com","1211","07-09-2024 11:37:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003016583","B=
iteng","","07-09-2024 10:46:46","07-09-2024 10:27:33","07-09-2024 11:18:18"=
,"No power issue on site U=3D54,5v site on grid Lionel steve / 655184876/ F=
rom  Huawei is informed,notice that disjonction of CB in BTS Ocm","Mba Laza=
re Herve","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue on site U=3D54,5v site on grid Lionel =
steve / 655184876/ From  Huawei is informed,notice that disjonction of CB i=
n BTS Ocm","alexandre.kamal@ihstowers.com","1154","07-09-2024 10:46:46","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003016578","E=
lig-Edzoa","","07-09-2024 10:45:28","07-09-2024 10:16:21","07-09-2024 11:17=
:30","grid outage//MDG 20 kva deployed","","Grid Supply","Passive","Grid","=
National Grid - Grid Outage Issue","grid outage//MDG 20 kva deployed","alex=
andre.kamal@ihstowers.com","1748","07-09-2024 10:45:28","Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0003016507","Ang=
uissa New","","07-09-2024 10:35:36","07-09-2024 10:24:25","07-09-2024 11:15=
:47","Grid outage, site went down because  Gen failed to start due to poor =
battery backup //Gen manually started","MINKA NICOLAS","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down because  Gen failed to start due to poor battery backup //Gen manu=
ally started","stephane.nkamwa@ihstowers.com","672","07-09-2024 10:35:36","=
Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0003016463","MAN=
GUIERS CHAPELLE","","07-09-2024 10:29:51","07-09-2024 10:19:02","07-09-2024=
 10:35:16","Grid outage, site went down because  Gen failed to start due to=
 poor battery backup // Gen automatically started","Fabrice Pouakam","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down because  Gen failed to start due to poor battery bac=
kup // Gen automatically started","stephane.nkamwa@ihstowers.com","4533","0=
7-09-2024 10:29:51","Sagemcom CMR"
"Closed Complete","Site Down","T1162","IHS_YND_256","NOCINC0003015550","MES=
SAME NDONGO 1162","","07-09-2024 08:06:24","07-09-2024 06:43:10","07-09-202=
4 07:49:35","grid outage,gen failed to start due to card Ge dysfonctioning/=
/he reset the card and started it","MINKA NICOLAS","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start due=
 to card Ge dysfonctioning//he reset the card and started it","stephane.nka=
mwa@ihstowers.com","4995","07-09-2024 08:06:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003014819","T=
singa","","07-09-2024 04:54:50","07-09-2024 04:53:28","07-09-2024 05:15:55"=
,"Grid outage, site went down because  Gen failed to start due to poor batt=
ery backup // Grid power return","Mboua Thierry","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn because  Gen failed to start due to poor battery backup // Grid power re=
turn","emmanuel.ghani@ihstowers.com","83","07-09-2024 04:54:50","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003014613","E=
kie sud","","07-09-2024 03:26:16","07-09-2024 03:19:48","07-09-2024 04:09:2=
5","Active//No power issue, site on Grid with U=3D54,2V, Lionel /655184876/=
 From Huawei is informed","Albran Byorel","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power issu=
e, site on Grid with U=3D54,2V, Lionel /655184876/ From Huawei is informed"=
,"emmanuel.ghani@ihstowers.com","389","07-09-2024 03:26:16","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0003014437","Lad=
a I Yde","","07-09-2024 02:33:40","07-09-2024 02:29:36","07-09-2024 04:33:3=
0","Grid outage site went down because Gen failed to start due to alarm Gen=
 overload // He reset the Gen card and Gen manually started","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid o=
utage site went down because Gen failed to start due to alarm Gen overload =
// He reset the Gen card and Gen manually started","joelle.ekessi@ihstowers=
.com","245","07-09-2024 02:33:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0003014019","M=
om","","06-09-2024 23:56:42","06-09-2024 23:53:37","06-09-2024 23:55:36","G=
rid outage site went down because Gen failed to start// Grid power return (=
investigation ongoing)","Fanda Brice","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Grid outage site went down because Gen failed to=
 start// Grid power return (investigation ongoing)","emmanuel.ghani@ihstowe=
rs.com","186","06-09-2024 23:56:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003013796","Afanoya"=
,"","06-09-2024 22:55:11","06-09-2024 22:46:57","06-09-2024 22:57:43","Casc=
aded Incident from TTO2843632","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because  G=
en failed to start due to poor battery backup // Gen automatically started"=
,"system","494","06-09-2024 22:55:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003013795","ELOUMDEM=
 CARRIERE","","06-09-2024 22:55:10","06-09-2024 22:46:57","06-09-2024 22:57=
:43","Cascaded Incident from TTO2843632","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause  Gen failed to start due to poor battery backup // Gen automatically s=
tarted","system","493","06-09-2024 22:55:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003013792","A=
hala","IHS_YND_767, IHS_YND_313","06-09-2024 22:53:45","06-09-2024 22:46:57=
","06-09-2024 22:57:43","Grid outage, site went down because  Gen failed to=
 start due to poor battery backup // Gen automatically started","Hyemafo Gi=
ldas","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery=
 Low","Grid outage, site went down because  Gen failed to start due to poor=
 battery backup // Gen automatically started","emmanuel.ghani@ihstowers.com=
","409","06-09-2024 22:53:45","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0003013786","Eto=
ug ebe biscuiterie","","06-09-2024 22:51:54","06-09-2024 22:48:43","06-09-2=
024 23:30:48","Grid fluctuation site went down because Gen failed to start =
due to Grid bad voltage// He bypass the Grid and Gen manually started","Hye=
mafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen failed to start due=
 to Grid bad voltage// He bypass the Grid and Gen manually started","joelle=
.ekessi@ihstowers.com","191","06-09-2024 22:51:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_358","IHS_YND_335","NOCINC0003013683","A=
ngongo","","06-09-2024 22:30:02","06-09-2024 22:04:56","07-09-2024 00:13:19=
","Grid outage, site went down because gen ran untill fuel shortage // refu=
eling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Grid outage, site went down because gen ran untill fuel shortage // refuel=
ing done","emmanuel.ghani@ihstowers.com","1507","06-09-2024 22:30:02","Sage=
mcom CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0003013624","Eto=
ug ebe Meweulo","","06-09-2024 22:19:37","06-09-2024 21:58:00","06-09-2024 =
23:24:47","Grid outage site went down because Gen failed to started due to =
Gen battery discharge// he started with external battery","Hyemafo Gildas",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid ou=
tage site went down because Gen failed to started due to Gen battery discha=
rge// he started with external battery","joelle.ekessi@ihstowers.com","1393=
","06-09-2024 22:19:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0003013623","M=
ontee-Des-Soeurs","","06-09-2024 22:19:33","06-09-2024 22:07:30","07-09-202=
4 00:40:26","Active// No power Issue Site on Grid Ubai =3D54,5V, The FME Tx=
 The TX FME Mbah Hosiah (674007438) is informed","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power Issue Site on Grid Ubai =3D54,5V, The FME Tx The TX FM=
E Mbah Hosiah (674007438) is informed","emmanuel.ghani@ihstowers.com","724"=
,"06-09-2024 22:19:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003013425","B=
iteng","","06-09-2024 21:43:58","06-09-2024 21:37:44","06-09-2024 21:47:50"=
,"ACTIVE / No power issue on site Ubaie=3D54,4V site on Grid The TX FME  Li=
onel steve / 655184876/ From  Huawei is informed","Mba Lazare Herve","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","ACTIVE / No power issue on site Ubaie=3D54,4V site on Grid The TX FME=
  Lionel steve / 655184876/ From  Huawei is informed","ange.kongo@ihstowers=
.com","375","06-09-2024 21:43:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003012830","Eto koss=
 Yde","","06-09-2024 20:24:01","06-09-2024 20:13:40","06-09-2024 20:39:24",=
"Cascaded Incident from TTO2842511","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Fluctuation, site went down bec=
ause Main Gen faulty//Grid stabilized","system","621","06-09-2024 20:24:01"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003012831","ELOUMDEM=
 CARRIERE 2","","06-09-2024 20:24:01","06-09-2024 20:13:40","06-09-2024 20:=
39:24","Cascaded Incident from TTO2842511","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Fluctuation, site went d=
own because Main Gen faulty//Grid stabilized","system","621","06-09-2024 20=
:24:01","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003012826","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","06-09-2024 20:21:49","06-09-2024 20:09=
:33","06-09-2024 20:39:24","Grid Fluctuation, site went down because Main G=
en faulty//Grid stabilized","Fanda Brice","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Grid Fluctuation, site went down b=
ecause Main Gen faulty//Grid stabilized","olivier.kwedi@ihstowers.com","103=
0","06-09-2024 20:21:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003012450","Afanoya"=
,"","06-09-2024 19:29:31","06-09-2024 19:06:24","06-09-2024 21:18:54","Casc=
aded Incident from TTO2842082","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Outage, Site went down because Ge=
n Overload (20kva,330A)//He reduced the load and started Gen manualy","syst=
em","1387","06-09-2024 19:29:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003012449","ELOUMDEM=
 CARRIERE","","06-09-2024 19:29:30","06-09-2024 19:06:24","06-09-2024 21:18=
:54","Cascaded Incident from TTO2842082","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage, Site went down bec=
ause Gen Overload (20kva,330A)//He reduced the load and started Gen manualy=
","system","1386","06-09-2024 19:29:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003012431","A=
hala","IHS_YND_767, IHS_YND_313","06-09-2024 19:25:21","06-09-2024 19:06:12=
","06-09-2024 21:18:54","Grid Outage, Site went down because Gen Overload (=
20kva,330A)//He reduced the load and started Gen manualy","Hyemafo Gildas",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid Outage, Sit=
e went down because Gen Overload (20kva,330A)//He reduced the load and star=
ted Gen manualy","ange.kongo@ihstowers.com","1150","06-09-2024 19:25:21","S=
agemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0003011992","Mfo=
u EPC","","06-09-2024 18:12:02","06-09-2024 18:00:56","06-09-2024 18:35:08"=
,"Technician Herve Lazare/Sagemcom/657108482/working on site/End of work","=
Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Battery Low","Technician Herve Lazare/Sagemcom/657108482/working on si=
te/End of work","olivier.kwedi@ihstowers.com","1150","06-09-2024 18:12:02",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003011969","S=
OA UNIVERSITY STADIUM","","06-09-2024 18:05:33","06-09-2024 18:01:29","06-0=
9-2024 18:06:32","Active// No power issue on site ,Site on Grid with Ubaie=
=3D54,9 V  The TX FME Synphorien //691316854// from Huawei is working on si=
te and Up at 06:07 PM","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue =
on site ,Site on Grid with Ubaie=3D54,9 V  The TX FME Synphorien //69131685=
4// from Huawei is working on site and Up at 06:07 PM","ange.kongo@ihstower=
s.com","245","06-09-2024 18:05:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0003011878","Akak-Nko=
zoa-MTN-IHS","","06-09-2024 17:51:00","06-09-2024 17:48:54","06-09-2024 18:=
28:23","Grid Fluctuation, Site went down because grid contactor disfunction=
ned//He bypassed Grid and started Gen manualy","Fabrice Pouakam","Equipment=
 Repair","Passive","Control Panel","ATS-AMF Issue","Grid Fluctuation, Site =
went down because grid contactor disfunctionned//He bypassed Grid and start=
ed Gen manualy","ange.kongo@ihstowers.com","127","06-09-2024 17:51:00","Sag=
emcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0003011655","MBI=
MBIM","","06-09-2024 17:19:50","06-09-2024 17:06:39","06-09-2024 19:24:24",=
"Site went down because Gen started and stopped due to infiltration of wate=
r in the tank//He removed water and started Gen manualy","Parker Tchoup","F=
uel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In Th=
e Fuel","Site went down because Gen started and stopped due to infiltration=
 of water in the tank//He removed water and started Gen manualy","olivier.k=
wedi@ihstowers.com","792","06-09-2024 17:19:50","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003011649","MIM=
BOMAN LIBERTE","","06-09-2024 17:17:57","06-09-2024 16:59:03","06-09-2024 1=
7:20:15","Grid outage,Main DG overload//  Grid Restored","Mba Lazare Herve"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage,Mai=
n DG overload//  Grid Restored","olivier.kwedi@ihstowers.com","2290","06-09=
-2024 17:17:57","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0003011591","Obo=
bogo","","06-09-2024 17:04:30","06-09-2024 16:54:20","06-09-2024 17:02:18",=
"Grid Outage, site went down because  Gen failed to start due to poor batte=
ry backup // Gen started automatically","MINKA NICOLAS","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, site =
went down because  Gen failed to start due to poor battery backup // Gen st=
arted automatically","olivier.kwedi@ihstowers.com","611","06-09-2024 17:04:=
30","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003011588","Nsi=
meyong Shell","","06-09-2024 17:03:44","06-09-2024 16:54:27","06-09-2024 17=
:02:27","Grid outage, site went down because  Gen  start due to poor batter=
y backup // Grid Power return","MINKA NICOLAS","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 because  Gen  start due to poor battery backup // Grid Power return","oliv=
ier.kwedi@ihstowers.com","558","06-09-2024 17:03:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_100","NOCINC0003011560","Shell-Ns=
imeyong","","06-09-2024 16:57:22","06-09-2024 16:51:14","06-09-2024 16:55:4=
7","Site went down due to Insufficient of rectifier on site (02/03)// Site =
stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Recti=
fier Module","Site went down due to Insufficient of rectifier on site (02/0=
3)// Site stabilized","ange.kongo@ihstowers.com","369","06-09-2024 16:57:22=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_424","NOCINC0003011357","Ossombe"=
,"","06-09-2024 16:21:35","06-09-2024 16:13:29","06-09-2024 19:30:35","Acti=
ve// No power issue on site U=3D50,3V site on Battery Team DIAKITE NAKAN/65=
2369313/HUAWEI working on site ","Parker Tchoup","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No po=
wer issue on site U=3D50,3V site on Battery Team DIAKITE NAKAN/652369313/HU=
AWEI working on site ","ange.kongo@ihstowers.com","486","06-09-2024 16:21:3=
5","Sagemcom CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0003011344","E=
toug ebe Meweulo","","06-09-2024 16:18:15","06-09-2024 16:15:04","06-09-202=
4 17:00:50","Grid outage, site went down because fuse card Gen faulty//He m=
ake a bridge and started Gen manualy","Hyemafo Gildas","Equipment Repair","=
Passive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down bec=
ause fuse card Gen faulty//He make a bridge and started Gen manualy","ange.=
kongo@ihstowers.com","192","06-09-2024 16:18:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003011332","E=
kie sud","","06-09-2024 16:15:04","06-09-2024 16:07:53","06-09-2024 16:08:4=
3","Active//No power issue, site on Grid with U=3D54,2V, Lionel /655184876/=
 From Huawei is informed  ","Albran Byorel","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue, site on Grid with U=3D54,2V, Lionel /655184876/ From Huawei is informe=
d ","ange.kongo@ihstowers.com","432","06-09-2024 16:15:04","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003011300","Eko=
unou","","06-09-2024 16:04:03","06-09-2024 15:53:47","06-09-2024 16:17:05",=
"Site on Gen due to Grid Outage, site went down because  Gen failed to star=
t due to poor battery backup // Grid Power return","Albran Byorel","Equipme=
nt Repair","Passive","Control Panel","Power Cabinet - Battery Low","Site on=
 Gen due to Grid Outage, site went down because  Gen failed to start due to=
 poor battery backup // Grid Power return","olivier.kwedi@ihstowers.com","6=
17","06-09-2024 16:04:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0003011298","O=
dza","","06-09-2024 16:03:19","06-09-2024 15:55:58","06-09-2024 16:49:10","=
Grid Outage, site went down because  Gen failed to start due to poor batter=
y backup // Gen started automatically","Albran Byorel","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, site w=
ent down because  Gen failed to start due to poor battery backup // Gen sta=
rted automatically","ange.kongo@ihstowers.com","442","06-09-2024 16:03:19",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0003011196","Nko=
lmvack","","06-09-2024 15:45:31","06-09-2024 15:36:22","06-09-2024 15:38:06=
","ACTIVE// No power issue: Ubaie=3D51,6V site on Battery The Tx Fme Tsague=
( 690488850)from Huawei is informed and Up at 03:55 PM","Parker Tchoup","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","ACTIVE// No power issue: Ubaie=3D51,6V site on Battery The Tx Fme =
Tsague( 690488850)from Huawei is informed and Up at 03:55 PM","olivier.kwed=
i@ihstowers.com","550","06-09-2024 15:45:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003010994","B=
ATA-Mokolo","","06-09-2024 15:19:27","06-09-2024 15:17:21","06-09-2024 20:3=
5:46","Site went down due to insufficient of rectifier on site//site stabil=
ized","","Equipment Repair","Passive","Rectifier","Rectifier Module","Site =
went down due to insufficient of rectifier on site//site stabilized","ange.=
kongo@ihstowers.com","127","06-09-2024 15:19:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0003010928","G=
olf Quater","","06-09-2024 15:13:14","06-09-2024 14:59:02","06-09-2024 15:0=
5:48","Active// No power issue on site U=3D53,4V site on Grid Team Abel/682=
840529/ZTE working on site ""Swapp""","Mboua Thierry","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// =
No power issue on site U=3D53,4V site on Grid Team Abel/682840529/ZTE worki=
ng on site ""Swapp""","ange.kongo@ihstowers.com","853","06-09-2024 15:13:14=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0003010806","S=
cience","","06-09-2024 14:53:12","06-09-2024 14:50:08","06-09-2024 20:41:40=
","Active//No power issue on site ,site on Gen with U=3D53,4V Team Mouhamad=
ou /691144435/  from HUAWEI is informed Notice that we have dysjunction at =
OCM equipements","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power is=
sue on site ,site on Gen with U=3D53,4V Team Mouhamadou /691144435/  from H=
UAWEI is informed Notice that we have dysjunction at OCM equipements","ange=
.kongo@ihstowers.com","185","06-09-2024 14:53:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0003010754","A=
RMP","","06-09-2024 14:40:25","06-09-2024 14:33:19","06-09-2024 20:46:01","=
Active// No power issue on site U=3D54,5V site on Grid,The Team Christian H=
okcheu (652088525) From ZTE is working on Site","","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No =
power issue on site U=3D54,5V site on Grid,The Team Christian Hokcheu (6520=
88525) From ZTE is working on Site","ange.kongo@ihstowers.com","427","06-09=
-2024 14:40:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003010742","M=
endong vallee","","06-09-2024 14:36:36","06-09-2024 09:46:00","06-09-2024 1=
0:25:38"," site went down due to work Our FME Brice Fanda  /658952552/Sagem=
com/"" PM //end of works.","Fanda Brice","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low"," site went down due to work Our F=
ME Brice Fanda  /658952552/Sagemcom/"" PM //end of works.","ludivine.ngamal=
eu@ihstowers.com","17437","06-09-2024 14:36:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003010737","M=
EFOU ASSI","","06-09-2024 14:35:07","06-09-2024 12:39:37","06-09-2024 14:57=
:11","Grid outage and Main Gen Faulty//Grid Restored","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage and=
 Main Gen Faulty//Grid Restored","ludivine.ngamaleu@ihstowers.com","6931","=
06-09-2024 14:35:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0003010733","N=
kolbisson usine des eaux","IHS_YND_712","06-09-2024 14:33:10","06-09-2024 1=
4:14:56","06-09-2024 15:14:15","Grid outage,site went down because Gen over=
load(15Kva, 345A)//He reduced 3/6 rectifier and started Gen manualy","TIENT=
CHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overlo=
ad","Grid outage,site went down because Gen overload(15Kva, 345A)//He reduc=
ed 3/6 rectifier and started Gen manualy","ange.kongo@ihstowers.com","1094"=
,"06-09-2024 14:33:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0003010600","N=
kolkoumou OCM","","06-09-2024 14:28:48","06-09-2024 14:14:56","06-09-2024 1=
5:14:15","site impacted by TTO2840150 Nkolbisson usine des eaux ","TIENTCHE=
U NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passive","Cascade Pas=
sive","Grid outage,site went down because Gen overload(15Kva, 345A)//He red=
uced 3/6 rectifier and started Gen manualy","ange.kongo@ihstowers.com","460=
5","06-09-2024 14:28:48","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0003010424","Fla=
menco","","06-09-2024 13:58:14","06-09-2024 13:48:59","06-09-2024 14:03:39"=
,"GRID outage site went down because Gen failed to start due to Gen card fa=
ulty// Gen manually  started","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","GRID outage site went down because Gen f=
ailed to start due to Gen card faulty// Gen manually  started","dorothy.dja=
ntio@ihstowers.com","555","06-09-2024 13:58:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003010226","MBIMBIM"=
,"","06-09-2024 13:46:42","06-09-2024 13:33:15","06-09-2024 13:34:15","Casc=
aded Incident from TTO2839368","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Our FME Felix 691145560 / 677002977 / IENG=
 is informed and reverts No Power issue on site, Site is on Solar; Ubaie =
=3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","807","06-09-2024 13:46:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0003010221","Ngoum","=
","06-09-2024 13:46:41","06-09-2024 13:33:15","06-09-2024 13:34:15","Cascad=
ed Incident from TTO2839368","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Our FME Felix 691145560 / 677002977 / IENG i=
s informed and reverts No Power issue on site, Site is on Solar; Ubaie =3D =
50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","system=
","806","06-09-2024 13:46:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003010224","Ngouetou=
","","06-09-2024 13:46:41","06-09-2024 13:33:15","06-09-2024 13:34:15","Cas=
caded Incident from TTO2839368","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Our FME Felix 691145560 / 677002977 / IEN=
G is informed and reverts No Power issue on site, Site is on Solar; Ubaie =
=3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","806","06-09-2024 13:46:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003010223","Yoko OCM=
","","06-09-2024 13:46:41","06-09-2024 13:33:15","06-09-2024 13:34:15","Cas=
caded Incident from TTO2839368","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Our FME Felix 691145560 / 677002977 / IEN=
G is informed and reverts No Power issue on site, Site is on Solar; Ubaie =
=3D 50.3V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","806","06-09-2024 13:46:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_763","NOCINC0003010056","Nkolbiss=
on usines des eaux 2","","06-09-2024 13:34:43","06-09-2024 13:25:39","06-09=
-2024 14:11:18","Cascaded Incident from TTO2839313","TIENTCHEU NZETCHIEU GA=
EL","Cascade Outage","Passive","Cascade Passive","Cascade Passive","site wa=
s on gen due to grid outge, gen stopped due to high temp//added water and r=
estarted the gen","system","544","06-09-2024 13:34:43","Sagemcom CMR"
"Closed Complete","Site Down","T3402","IHS_YND_285","NOCINC0003010035","Nko=
lbisson","IHS_YND_763","06-09-2024 13:32:46","06-09-2024 13:25:39","06-09-2=
024 14:11:18","site was on gen due to grid outge, gen stopped due to high t=
emp//added water and restarted the gen","TIENTCHEU NZETCHIEU GAEL","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Is=
sue","site was on gen due to grid outge, gen stopped due to high temp//adde=
d water and restarted the gen","dorothy.djantio@ihstowers.com","427","06-09=
-2024 13:32:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0003009802","N=
komkana","","06-09-2024 13:06:22","06-09-2024 12:57:15","06-09-2024 13:59:1=
5","No space to deploy a mobile DG//Grid Restored","","Grid Supply","Passiv=
e","Grid","National Grid - Grid Outage Issue","No space to deploy a mobile =
DG//Grid Restored","ludivine.ngamaleu@ihstowers.com","548","06-09-2024 13:0=
6:22","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0003009762","Mfo=
u EPC","","06-09-2024 12:58:50","06-09-2024 12:47:46","06-09-2024 13:27:04"=
,"Grid fructuation,Gen failed to start due to Grid bad voltage,no rcp on si=
te //he bypassed Grid and started the Gen","Mba Lazare Herve","Grid Supply"=
,"Passive","Grid","National Grid - Phase Controller Faulty","Grid fructuati=
on,Gen failed to start due to Grid bad voltage,no rcp on site //he bypassed=
 Grid and started the Gen","dorothy.djantio@ihstowers.com","843","06-09-202=
4 12:58:50","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0003009756","Nsi=
meyong Shell","","06-09-2024 12:57:35","06-09-2024 12:50:30","06-09-2024 13=
:08:35","Grid outage, site went down before Dg start: Poor batteries backup=
 //DG started automatically.","MINKA NICOLAS","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before Dg start: Poor batteries backup //DG started automatically.","doroth=
y.djantio@ihstowers.com","426","06-09-2024 12:57:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0003009737","Lobo OCM=
","","06-09-2024 12:52:20","06-09-2024 12:48:30","06-09-2024 12:53:27","Cas=
caded Incident from TTO2838940","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid outage,site down due t=
o poor backup//gen started","system","230","06-09-2024 12:52:20","Sagemcom =
CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0003009734","N=
KOMEKUI OCM","IHS_YND_341","06-09-2024 12:51:34","06-09-2024 12:48:30","06-=
09-2024 12:53:27","grid outage,site down due to poor backup//gen started","=
TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","grid outage,site down due to poor backup//gen st=
arted","ludivine.ngamaleu@ihstowers.com","185","06-09-2024 12:51:34","Sagem=
com CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003009510","MIM=
BOMAN LIBERTE","","06-09-2024 12:36:14","06-09-2024 12:05:08","06-09-2024 1=
2:23:04","Grid outage,Main DG overload// Mobile DG deployment 15 kva","Mba =
Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage,Main DG overload// Mobile DG deployment 15 kva","dorothy.djantio@=
ihstowers.com","1867","06-09-2024 12:36:14","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0003009386","Elo=
umdem stade","","06-09-2024 12:23:05","06-09-2024 12:15:58","06-09-2024 12:=
48:03","Grid fluctuation site went down because Gen failled to started due =
to Grid bad voltage and RCP on Site // He bypass the Grid and site on Gen",=
"Fanda Brice","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","Grid fluctuation site went down because Gen failled to started=
 due to Grid bad voltage and RCP on Site // He bypass the Grid and site on =
Gen","dorothy.djantio@ihstowers.com","428","06-09-2024 12:23:05","Sagemcom =
CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0003009224","Nko=
lbisson IITA LP","","06-09-2024 11:58:20","06-09-2024 11:52:16","06-09-2024=
 14:00:35","grid outage, no space to deploy a MDG//grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, no=
 space to deploy a MDG//grid return","dorothy.djantio@ihstowers.com","365",=
"06-09-2024 11:58:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003009075","Eto koss=
 Yde","","06-09-2024 11:35:50","06-09-2024 11:20:52","06-09-2024 12:39:36",=
"Cascaded Incident from TTO2838158","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,Main DG faulty  // Mobil=
e DG deployed (20 kva)","system","898","06-09-2024 11:35:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003009065","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","06-09-2024 11:34:58","06-09-2024 11:20=
:52","06-09-2024 12:39:36","Grid outage,Main DG faulty  // Mobile DG deploy=
ed (20 kva)","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - =
Generator Faulty","Grid outage,Main DG faulty  // Mobile DG deployed (20 kv=
a)","dorothy.djantio@ihstowers.com","847","06-09-2024 11:34:58","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003008884","Y=
de-M-Central","","06-09-2024 11:27:52","06-09-2024 11:21:47","06-09-2024 11=
:34:27","Grid outage, no space to deploy a MDG//grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","grid outage, no sp=
ace to deploy a MDG//grid return","ludivine.ngamaleu@ihstowers.com","366","=
06-09-2024 11:27:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0003008816","B=
ATA-Mokolo","","06-09-2024 11:20:18","06-09-2024 11:18:12","06-09-2024 13:1=
0:07","grid outage, the space of MDG is not free//grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, the=
 space of MDG is not free//grid return","ludivine.ngamaleu@ihstowers.com","=
127","06-09-2024 11:20:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0003008812","B=
astos Ekoudou","","06-09-2024 11:19:10","06-09-2024 11:15:03","06-09-2024 1=
2:15:41","Grid outage, site went down before Dg start: Poor batteries backu=
p //DG started automatically.","Mboua Thierry","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before Dg start: Poor batteries backup //DG started automatically.","ludiv=
ine.ngamaleu@ihstowers.com","248","06-09-2024 11:19:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003008500","E=
kie sud","","06-09-2024 10:54:36","06-09-2024 10:47:29","06-09-2024 10:49:0=
3","no power issue on site ubaie=3D54v site on grid   Lionel  is informed",=
"Albran Byorel","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","no power issue on site ubaie=3D54v site on grid=
   Lionel  is informed","ludivine.ngamaleu@ihstowers.com","428","06-09-2024=
 10:54:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0003008486","ELOUMDEM=
 CARRIERE","","06-09-2024 10:52:20","06-09-2024 10:17:52","06-09-2024 12:07=
:04","Cascaded Incident from TTO2837309","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage,Main DG overload (2=
0 kva  315 A) ,Poor battery backup // He reduiced the toad ,site on DG.","s=
ystem","2068","06-09-2024 10:52:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003008430","Afanoya"=
,"","06-09-2024 10:41:21","06-09-2024 10:17:52","06-09-2024 12:07:04","Casc=
aded Incident from TTO2837309","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,Main DG overload (20 kva  =
315 A) ,Poor battery backup // He reduiced the toad ,site on DG.","system",=
"1409","06-09-2024 10:41:21","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0003008400","MBA=
LNGONG LYCEE","","06-09-2024 10:35:33","06-09-2024 10:17:52","06-09-2024 12=
:07:04","Site impacted by TTO2837309 ahala","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage,Main DG overload=
 (20 kva  315 A) ,Poor battery backup // He reduiced the toad ,site on DG."=
,"dorothy.djantio@ihstowers.com","2129","06-09-2024 10:35:33","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0003008253","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","06-09-2024 10:23:02","06-09-=
2024 10:16:58","06-09-2024 12:07:04","Grid outage,Main DG overload (20 kva =
 315 A) ,Poor battery backup // He reduiced the toad ,site on DG.","Hyemafo=
 Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid ou=
tage,Main DG overload (20 kva  315 A) ,Poor battery backup // He reduiced t=
he toad ,site on DG.","ludivine.ngamaleu@ihstowers.com","364","06-09-2024 1=
0:23:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0003008184","M=
ONTEE NKONDENGUI","","06-09-2024 10:10:27","06-09-2024 10:02:23","06-09-202=
4 11:52:24","Site went down due to BTS OCM power cable burned //He cut the =
burned cable and reconnect it.","Albran Byorel","Equipment Repair","Passive=
","Infrastructure","Armoured Cable","Site went down due to BTS OCM power ca=
ble burned //He cut the burned cable and reconnect it.","ludivine.ngamaleu@=
ihstowers.com","485","06-09-2024 10:10:27","Sagemcom CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0003008176","ELO=
UMDEM CARRIERE 2","","06-09-2024 10:09:28","06-09-2024 11:20:52","06-09-202=
4 12:39:36","Grid outage,Main DG faulty  // Mobile DG deployed (20 kva)","F=
anda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"Grid outage,Main DG faulty  // Mobile DG deployed (20 kva)","dorothy.djant=
io@ihstowers.com","1508","06-09-2024 10:09:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0003008063","M=
endong","IHS_YND_236","06-09-2024 09:54:22","06-09-2024 09:47:14","06-09-20=
24 10:27:04","Site on DG due to grid outage,DG stopped due to high temp ala=
rm // He added water and manually start of DG.","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issu=
e","Site on DG due to grid outage,DG stopped due to high temp alarm // He a=
dded water and manually start of DG.","ludivine.ngamaleu@ihstowers.com","42=
9","06-09-2024 09:54:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0003008057","M=
ontee-Jouvence","","06-09-2024 09:53:00","06-09-2024 09:47:55","06-09-2024 =
10:25:04","Please cascade it behind Mendong ctr_025.","Hyemafo Gildas","Cas=
cade Outage","Passive","Cascade Passive","Cascade Passive","Site on DG due =
to grid outage,DG stopped due to high temp alarm // He added water and manu=
ally start of DG.","ludivine.ngamaleu@ihstowers.com","306","06-09-2024 09:5=
3:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0003007988","S=
tade-Abega","","06-09-2024 09:43:37","06-09-2024 09:39:33","06-09-2024 10:2=
1:30","Grid outage,DG failed to start due to glow plugs faulty //Manually s=
tart of DG.","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","AC=
DG - Kick Starter","Grid outage,DG failed to start due to glow plugs faulty=
 //Manually start of DG.
","ludivine.ngamaleu@ihstowers.com","245","06-09-2024 09:43:37","Sagemcom C=
MR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0003007946","Sou=
s Prefecture","","06-09-2024 09:35:05","06-09-2024 09:20:57","06-09-2024 12=
:35:48","no power issue on site ubaie=3D54v site on grid  lionel isunreacha=
ble, RM R=E9n=E9 691144423//huawei  is informed","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
no power issue on site ubaie=3D54v site on grid  lionel isunreachable, RM R=
=E9n=E9 691144423//huawei  is informed","dorothy.djantio@ihstowers.com","84=
8","06-09-2024 09:35:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0003007911","S=
cience","","06-09-2024 09:33:02","06-09-2024 09:24:58","06-09-2024 12:45:01=
","","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel=
","ATS-AMF Hanged","Grid fluctuations, no rcp gen fail to start//grid CB tr=
ipped, and gen started","ludivine.ngamaleu@ihstowers.com","485","06-09-2024=
 09:33:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0003007894","C=
arrefourt Nkomo","","06-09-2024 09:30:55","06-09-2024 09:17:51","06-09-2024=
 10:01:51","Site on DG due to grid outage,Dg stopped due to high temp // He=
 added water and manually start of DG.","Mba Lazare Herve","Equipment Repai=
r","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Si=
te on DG due to grid outage,Dg stopped due to high temp // He added water a=
nd manually start of DG.","ludivine.ngamaleu@ihstowers.com","785","06-09-20=
24 09:30:55","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003007865","Mim=
boman4","","06-09-2024 09:28:37","06-09-2024 09:18:59","06-09-2024 09:30:55=
","Grid outage,DG failed to start due to static charger faulty (battery was=
 completly discharged)//manually start of DG with battery backup. Although =
power resolved,site remained down,Lionel steve was in","Mba Lazare Herve","=
Equipment Repair","Passive","ACDG Gen","ACDG - Turbo Charger","Grid outage,=
DG failed to start due to static charger faulty (battery was completly disc=
harged)//manually start of DG with battery backup. Although power resolved,=
site remained down,Lionel steve was informed.","dorothy.djantio@ihstowers.c=
om","579","06-09-2024 09:28:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0003007813","A=
FEME NORD","","06-09-2024 09:16:27","06-09-2024 09:08:23","06-09-2024 09:22=
:46","grid outage, site down due to grid contactor faulty//gen started manu=
ally","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Pane=
l","ATS-AMF Issue","grid outage, site down due to grid contactor faulty//ge=
n started manually","ludivine.ngamaleu@ihstowers.com","485","06-09-2024 09:=
16:27","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003007728","MIM=
BOMAN LIBERTE","","06-09-2024 09:07:53","06-09-2024 08:53:47","06-09-2024 0=
9:33:50","Grid outage,Main DG overload// Mobile DG deployment 15 kva","Mba =
Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Gr=
id outage,Main DG overload// Mobile DG deployment 15 kva","dorothy.djantio@=
ihstowers.com","847","06-09-2024 09:07:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0003007694","E=
ssomba","","06-09-2024 09:01:55","06-09-2024 08:53:46","06-09-2024 09:25:39=
","Site on DG due to grid outage,DG stopped due to fuel shortage //Refuelin=
g done.","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outage=
","Site on DG due to grid outage,DG stopped due to fuel shortage //Refuelin=
g done.","ludivine.ngamaleu@ihstowers.com","490","06-09-2024 09:01:55","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0003007629","N=
koabang2","","06-09-2024 08:50:12","06-09-2024 08:37:07","06-09-2024 09:26:=
10","Grid fluctuation,site went down before DG start : Poor Batteries backu=
p //DG started automatically","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid fluctuation,site wen=
t down before DG start : Poor Batteries backup //DG started automatically",=
"ludivine.ngamaleu@ihstowers.com","786","06-09-2024 08:50:12","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003007593","M=
imboman-Village","","06-09-2024 08:42:44","06-09-2024 08:40:39","06-09-2024=
 08:46:48","Grid outage, site went down before gen start due to poor batter=
y backup // grid return","Mba Lazare Herve","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // grid return","ludivine.ngamale=
u@ihstowers.com","126","06-09-2024 08:42:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0003007529","N=
kolo II New","","06-09-2024 08:36:31","06-09-2024 08:32:26","07-09-2024 00:=
20:39","Technician is on the way ETA ;11h45","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site ubaie=3D54v Lionel is informed","ludivine.ngamaleu@=
ihstowers.com","246","06-09-2024 08:36:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0003007184","M=
endong vallee","","06-09-2024 07:37:18","06-09-2024 07:32:04","06-09-2024 0=
7:54:58","Site on DG due to grid outage,Poor Batteries Backup,site went dow=
n during refueling //End of refueling site on DG.","Fanda Brice","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Site on D=
G due to grid outage,Poor Batteries Backup,site went down during refueling =
//End of refueling site on DG.","ludivine.ngamaleu@ihstowers.com","315","06=
-09-2024 07:37:18","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0003007156","Bas=
tos Ekoudou","","06-09-2024 07:27:35","06-09-2024 07:24:29","06-09-2024 07:=
34:32","Grid outage,site went down before DG start : Poor Batteries Backup =
//Grid restored.","Mboua Thierry","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage,site went down before DG sta=
rt : Poor Batteries Backup //Grid restored.","dorothy.djantio@ihstowers.com=
","187","06-09-2024 07:27:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0003006904","E=
mana","","06-09-2024 06:32:48","06-09-2024 06:30:44","06-09-2024 06:31:45",=
"Active//No power issue on site ubaie=3D54v site on Grid  Simphorien is inf=
ormed","","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue on site ubaie=3D54v site on grid  Simp=
horien is informed","ludivine.ngamaleu@ihstowers.com","125","06-09-2024 06:=
32:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0003006900","S=
OA UNIVERSITY STADIUM","","06-09-2024 06:32:08","06-09-2024 06:27:03","06-0=
9-2024 10:07:03","Tx issue: site on grid,Ubaie:55.1 V; Symphorien/650-25-71=
-51 is informed.","Siligap Boris","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Tx issue: site on grid,Ubaie:=
55.1 V; Symphorien/650-25-71-51 is informed.","ludivine.ngamaleu@ihstowers.=
com","306","06-09-2024 06:32:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0003006898","O=
dza","IHS_YND_254, IHS_YND_580","06-09-2024 06:31:11","06-09-2024 06:21:07"=
,"06-09-2024 06:53:39","Tx Issue : site on grid,Ubaie:53.4V; Lionel steve /=
655-18-48-76 is informed. Noticed that there was OCM disjunction.","Albran =
Byorel","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Tx Issue : site on grid,Ubaie:53.4V; Lionel steve /655-=
18-48-76 is informed. Noticed that there was OCM disjunction.","ludivine.ng=
amaleu@ihstowers.com","605","06-09-2024 06:31:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0003006890","M=
arche Odza","","06-09-2024 06:30:11","06-09-2024 06:21:06","06-09-2024 06:5=
3:38","please cascaded this ticket .Site impacted by  Odza OCM","Albran Byo=
rel","Cascade Outage","Active","Cascade Active","Cascade Active","Tx Issue =
: site on grid,Ubaie:53.4V; Lionel steve /655-18-48-76 is informed. Noticed=
 that there was OCM disjunction.","ludivine.ngamaleu@ihstowers.com","546","=
06-09-2024 06:30:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003006888","M=
vog-Manga","","06-09-2024 06:29:32","06-09-2024 06:20:26","06-09-2024 06:53=
:41","please cascaded this ticket .Site impacted by  Odza OCM","Albran Byor=
el","Cascade Outage","Active","Cascade Active","Cascade Active","Tx Issue :=
 site on grid,Ubaie:53.4V; Lionel steve /655-18-48-76 is informed. Noticed =
that there was OCM disjunction.","ludivine.ngamaleu@ihstowers.com","547","0=
6-09-2024 06:29:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0003006881","Eloumdem=
 stade","","06-09-2024 06:28:51","06-09-2024 06:04:12","06-09-2024 06:32:29=
","Cascaded Incident from TTO2835645","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,DG failed to start due=
 to ACDG Generator Battery Faulty //Manually start of DG with External Batt=
ery.","system","1479","06-09-2024 06:28:51","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0003006874","Sim=
bock MTN","IHS_YND_793","06-09-2024 06:28:12","06-09-2024 06:04:12","06-09-=
2024 06:32:29","Grid outage,DG failed to start due to ACDG Generator Batter=
y Faulty //Manually start of DG with External Battery.","Fanda Brice","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage,=
DG failed to start due to ACDG Generator Battery Faulty //Manually start of=
 DG with External Battery.","dorothy.djantio@ihstowers.com","1441","06-09-2=
024 06:28:12","Sagemcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0003006776","Bar=
riere IHS","","06-09-2024 06:03:10","06-09-2024 05:57:47","06-09-2024 06:56=
:06","eneo line issue, site down because gen ran till diesel outage//refuel=
ing done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Outage"=
,"eneo line issue, site down because gen ran till diesel outage//refueling =
done","kouoh.jean@ihstowers.com","1345","06-09-2024 06:03:10","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0003006719","A=
nguissa New","","06-09-2024 05:43:55","06-09-2024 05:37:49","06-09-2024 07:=
15:17","please cascaded this ticket .Site Impacted by  Labogenie","MINKA NI=
COLAS","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid=
 outage.no space to deploy pmobile gen//grid power awaited","nadjia.njaya@i=
hstowers.com","367","06-09-2024 05:43:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003006639","ELOUMDEM=
 CARRIERE 2","","06-09-2024 05:26:31","06-09-2024 05:19:36","06-09-2024 06:=
57:26","Cascaded Incident from TTO2835358","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage Main DG faulty//M=
obile DG connected (20 kva). Oange will remained until ENEO return.","syste=
m","415","06-09-2024 05:26:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003006638","Eto koss=
 Yde","","06-09-2024 05:26:30","06-09-2024 05:19:36","06-09-2024 06:57:26",=
"Cascaded Incident from TTO2835358","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage Main DG faulty//Mobile D=
G connected (20 kva). Oange will remained until ENEO return.","system","414=
","06-09-2024 05:26:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0003006617","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","06-09-2024 05:19:05","06-09-2024 05:=
17:58","06-09-2024 06:57:26","","Fanda Brice","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Generator Faulty","Grid outage Main DG faulty//Mobile DG=
 connected (20 kva). Oange will remained until ENEO return.","nadjia.njaya@=
ihstowers.com","68","06-09-2024 05:19:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003006555","T=
singa","","06-09-2024 04:55:32","06-09-2024 04:49:28","06-09-2024 05:12:14"=
,"Grid outage site went down because Gen failed to start due to poor batter=
y backup // Grid power return","Mboua Thierry","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage site went down =
because Gen failed to start due to poor battery backup // Grid power return=
","nadjia.njaya@ihstowers.com","365","06-09-2024 04:55:32","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003006487","Eko=
unou","","06-09-2024 04:30:19","06-09-2024 04:24:22","06-09-2024 04:36:44",=
"Grid outage, site went down because  Gen failed to start due to poor batte=
ry backup // Grid return","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site went down beca=
use  Gen failed to start due to poor battery backup // Grid return","kouoh.=
jean@ihstowers.com","358","06-09-2024 04:30:19","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0003005910","Sapeur",=
"","06-09-2024 01:57:50","05-09-2024 23:18:49","06-09-2024 01:44:06","Casca=
ded Incident from TTO2833719","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has deployed"=
,"system","9541","06-09-2024 01:57:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_091","NOCINC0003005909","Jouvence=
 2000","","06-09-2024 01:57:50","05-09-2024 23:18:49","06-09-2024 01:44:06"=
,"Cascaded Incident from TTO2833719","Delor Telezing","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has d=
eployed","system","9541","06-09-2024 01:57:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0003005908","Bastos B=
ethesda","","06-09-2024 01:57:50","05-09-2024 23:18:49","06-09-2024 01:44:0=
6","Cascaded Incident from TTO2833719","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has =
deployed","system","9541","06-09-2024 01:57:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_687","NOCINC0003005904","OLAMA","=
","06-09-2024 01:57:01","06-09-2024 01:45:11","06-09-2024 02:20:24","Cascad=
ed Incident from TTO2834478","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuation, site went down because ge=
n failed to start due to grid bad voltage // he bypass the Grid and Gen man=
ually started","system","710","06-09-2024 01:57:01","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0003005902","Ako=
no","IHS_YND_687","06-09-2024 01:55:18","06-09-2024 01:45:11","06-09-2024 0=
2:20:24","Grid fluctuation, site went down because gen failed to start due =
to grid bad voltage // he bypass the Grid and Gen manually started","Fanda =
Brice","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation, site went down because gen failed to start due to g=
rid bad voltage // he bypass the Grid and Gen manually started","kouoh.jean=
@ihstowers.com","608","06-09-2024 01:55:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0003005398","Dong",""=
,"06-09-2024 00:29:42","06-09-2024 00:20:35","06-09-2024 00:25:32","Cascade=
d Incident from TTO2833878","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","No power  issue U=3D53,7 V  site on Gen The T=
xFMe Gr=E9goire//652070658 is informed ,Site up 00:40 AM","system","547","0=
6-09-2024 00:29:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0003005397","Donga","=
","06-09-2024 00:29:42","06-09-2024 00:20:35","06-09-2024 00:25:32","Cascad=
ed Incident from TTO2833878","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power  issue U=3D53,7 V  site on Gen The =
TxFMe Gr=E9goire//652070658 is informed ,Site up 00:40 AM","system","547","=
06-09-2024 00:29:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0003005383","N=
guila","IHS_YND_434, IHS_YND_444","06-09-2024 00:27:40","06-09-2024 00:20:3=
5","06-09-2024 00:25:32","No power  issue U=3D53,7 V  site on Gen The TxFMe=
 Gr=E9goire//652070658 is informed ,Site up 00:40 AM","Parker Tchoup","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power  issue U=3D53,7 V  site on Gen The TxFMe Gr=E9goire//652070=
658 is informed ,Site up 00:40 AM","nadjia.njaya@ihstowers.com","426","06-0=
9-2024 00:27:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0003005288","Elig Edz=
oa","","06-09-2024 00:05:13","05-09-2024 23:18:49","06-09-2024 01:44:06","C=
ascaded Incident from TTO2833719","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has depl=
oyed","system","2784","06-09-2024 00:05:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0003005287","Charles-=
Atangana","","06-09-2024 00:05:13","05-09-2024 23:18:49","06-09-2024 01:44:=
06","Cascaded Incident from TTO2833719","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage//MDG of 20 kva has deployed","s=
ystem","2784","06-09-2024 00:05:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_016","NOCINC0003005284","Maetur",=
"","06-09-2024 00:05:12","05-09-2024 23:18:49","06-09-2024 01:44:06","Casca=
ded Incident from TTO2833719","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has deployed"=
,"system","2783","06-09-2024 00:05:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0003005282","Garbati =
building","","06-09-2024 00:05:12","05-09-2024 23:18:49","06-09-2024 01:44:=
06","Cascaded Incident from TTO2833719","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva ha=
s deployed","system","2783","06-09-2024 00:05:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0003005286","Hopital =
Central","","06-09-2024 00:05:12","05-09-2024 23:18:49","06-09-2024 01:44:0=
6","Cascaded Incident from TTO2833719","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Grid outage//MDG of 20 kva has deployed","sy=
stem","2783","06-09-2024 00:05:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_134","NOCINC0003005285","Vallee B=
astos MTN","","06-09-2024 00:05:12","05-09-2024 23:18:49","06-09-2024 01:44=
:06","Cascaded Incident from TTO2833719","Mboua Thierry","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva ha=
s deployed","system","2783","06-09-2024 00:05:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0003005283","ELIg-Ess=
ono","","06-09-2024 00:05:12","05-09-2024 23:18:49","06-09-2024 01:44:06","=
Cascaded Incident from TTO2833719","Delor Telezing","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has dep=
loyed","system","2783","06-09-2024 00:05:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0003005279","POLYCLIN=
IQUE TSINGA","","06-09-2024 00:05:11","05-09-2024 23:18:49","06-09-2024 01:=
44:06","Cascaded Incident from TTO2833719","Mboua Thierry","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva =
has deployed","system","2782","06-09-2024 00:05:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0003005280","HOPITAL =
DE LA CAISSE","","06-09-2024 00:05:11","05-09-2024 23:18:49","06-09-2024 01=
:44:06","Cascaded Incident from TTO2833719","Delor Telezing","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kv=
a has deployed","system","2782","06-09-2024 00:05:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0003005281","Hotel de=
 Ville Yde","","06-09-2024 00:05:11","05-09-2024 23:18:49","06-09-2024 01:4=
4:06","Cascaded Incident from TTO2833719","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has=
 deployed","system","2782","06-09-2024 00:05:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_049","NOCINC0003005278","Etoa-Mek=
i","","06-09-2024 00:05:11","05-09-2024 23:18:49","06-09-2024 01:44:06","Ca=
scaded Incident from TTO2833719","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has deplo=
yed","system","2782","06-09-2024 00:05:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0003005277","Mamch Bu=
ilding","","06-09-2024 00:05:10","05-09-2024 23:18:49","06-09-2024 01:44:06=
","Cascaded Incident from TTO2833719","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has d=
eployed","system","2781","06-09-2024 00:05:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0003005275","H-Franco=
 New","","06-09-2024 00:05:10","05-09-2024 23:18:49","06-09-2024 01:44:06",=
"Cascaded Incident from TTO2833719","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage//MDG of 20 kva has de=
ployed","system","2781","06-09-2024 00:05:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_084","NOCINC0003005276","Briquett=
erie","","06-09-2024 00:05:10","05-09-2024 23:18:49","06-09-2024 01:44:06",=
"Cascaded Incident from TTO2833719","","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","Grid outage//MDG of 20 kva has deployed","syste=
m","2781","06-09-2024 00:05:10","Sagemcom CMR"
"Closed Complete","Site Down","T0123","IHS_YND_013","NOCINC0003005254","Lab=
oratoire T.Bella","IHS_YND_711, IHS_YND_084, IHS_YND_563, IHS_YND_051, IHS_=
YND_091, IHS_YND_049, IHS_YND_086, IHS_YND_064, IHS_YND_019, IHS_YND_029, I=
HS_YND_024, IHS_YND_014, IHS_YND_016, IHS_YND_134, IHS_YND_027, IHS_YND_125=
, IHS_YND_504","05-09-2024 23:56:04","05-09-2024 23:18:49","06-09-2024 01:4=
4:06","Grid outage//MDG of 20 kva has deployed","Paul BIBOUM","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG of =
20 kva has deployed","kouoh.jean@ihstowers.com","2235","05-09-2024 23:56:04=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0003005104","Ngouetou=
","","05-09-2024 23:08:01","05-09-2024 22:18:37","05-09-2024 22:18:38","Cas=
caded Incident from TTO2833491","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","2964","05-09-2024 23:08:01","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0003005103","Yoko OCM=
","","05-09-2024 23:08:01","05-09-2024 22:18:37","05-09-2024 22:18:38","Cas=
caded Incident from TTO2833491","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.7V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","2964","05-09-2024 23:08:01","Sagem=
com CMR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0003004928","Sou=
s Prefecture","","05-09-2024 22:38:58","05-09-2024 21:33:49","05-09-2024 21=
:35:41","No power issue site on gen with U=3D55.7v Martial(690087047) from =
Huawei is informed","Fanda Brice","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue site on gen wi=
th U=3D55.7v Martial(690087047) from Huawei is informed","kouoh.jean@ihstow=
ers.com","3909","05-09-2024 22:38:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0003004557","T=
singa","","05-09-2024 21:53:44","05-09-2024 14:11:23","05-09-2024 14:20:30"=
,"Grid outage, site went down because  Gen failed to start due to poor batt=
ery backup // Grid Power return","Mboua Thierry","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn because  Gen failed to start due to poor battery backup // Grid Power re=
turn","kombi.samuel@ihstowers.com","46339","05-09-2024 21:53:44","Sagemcom =
CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0003004416","Ako=
k Ndoe Yde","","05-09-2024 21:33:12","05-09-2024 21:18:46","05-09-2024 22:2=
9:46","Site went down because CB(63A) in PWC  that feeds the BTS burned//He=
 make a bridge with 02 anothers CB(63A) ","Hyemafo Gildas","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site =
went down because CB(63A) in PWC  that feeds the BTS burned//He make a brid=
ge with 02 anothers CB(63A) ","joelle.ekessi@ihstowers.com","867","05-09-20=
24 21:33:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_367","IHS_YND_475","NOCINC0003004392","N=
goum","","05-09-2024 21:24:54","05-09-2024 21:02:51","05-09-2024 21:10:53",=
"Solar Hybrid GEN  site,  No power issue site on Solar,  tx fme Gregoire (6=
54547479) from Huawei informed","Parker Tchoup","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Solar Hybrid GE=
N  site,  No power issue site on Solar,  tx fme Gregoire (654547479) from H=
uawei informed","emmanuel.ghani@ihstowers.com","1324","05-09-2024 21:24:54"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0003004041","Abang","=
","05-09-2024 20:20:51","05-09-2024 20:10:50","05-09-2024 21:15:50","Cascad=
ed Incident from TTO2832262","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation, site went down becau=
se gen start and stopped due to grid bad voltage // Voltage stabilized","sy=
stem","601","05-09-2024 20:20:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0003004029","N=
kolangaa","IHS_YND_290","05-09-2024 20:17:58","05-09-2024 20:10:50","05-09-=
2024 21:15:50","Grid fluctuation, site went down because gen start and stop=
ped due to grid bad voltage // Voltage stabilized","Mba Lazare Herve","Grid=
 Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid f=
luctuation, site went down because gen start and stopped due to grid bad vo=
ltage // Voltage stabilized","emmanuel.ghani@ihstowers.com","429","05-09-20=
24 20:17:58","Sagemcom CMR"
"Cancelled","Warning","CTR_604","IHS_YND_252","NOCINC0003003857","Koweit Ci=
ty","","05-09-2024 19:48:33","","","","Albran Byorel","","","","","","emman=
uel.ghani@ihstowers.com","3068","05-09-2024 19:48:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0003003848","M=
fou EPC","","05-09-2024 19:46:46","05-09-2024 19:43:27","05-09-2024 20:41:3=
8","Grid fructuation,Gen failed to start due to Grid bad voltage,no rcp on =
site //he bypassed Grid and started the Gen","Mba Lazare Herve","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fructua=
tion,Gen failed to start due to Grid bad voltage,no rcp on site //he bypass=
ed Grid and started the Gen","emmanuel.ghani@ihstowers.com","200","05-09-20=
24 19:46:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0003003712","Sous Pre=
fecture","","05-09-2024 19:16:32","05-09-2024 19:09:27","05-09-2024 19:41:4=
8","Grid fluctuation, site went down because gen failed to start due to gri=
d bad voltage // he bypass grid and manually start the gen","Fanda Brice","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation, site went down because gen failed to start due to grid bad =
voltage // he bypass grid and manually start the gen","joelle.ekessi@ihstow=
ers.com","426","05-09-2024 19:16:32","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003003569","Pha=
rmacie SION","","05-09-2024 18:49:03","05-09-2024 18:26:00","05-09-2024 20:=
54:10","Grid outage, Site went down before gen start due to poor battery ba=
ckup and  the controller Psc3 dysfonctioning // he reset it and started the=
 Gen","Paul BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","Grid outage, Site went down before gen start due to poor battery b=
ackup and  the controller Psc3 dysfonctioning // he reset it and started th=
e Gen","joelle.ekessi@ihstowers.com","1384","05-09-2024 18:49:03","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0003003517","N=
sam Sofavinc T0","","05-09-2024 18:39:53","04-09-2024 11:38:10","04-09-2024=
 11:39:04","No power issue site on grid with U=3D53v Mbah Osiah from Huawei=
 is informed","MINKA NICOLAS","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with =
U=3D53v Mbah Osiah from Huawei is informed","kombi.samuel@ihstowers.com","1=
11704","05-09-2024 18:39:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003003440","L=
abogenie","IHS_YND_568","05-09-2024 18:26:51","05-09-2024 17:03:44","06-09-=
2024 07:15:37","Grid outage.no space to deploy pmobile gen.grid power await=
ed","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage.no space to deploy pmobile gen//grid power awaited","emmanuel.g=
hani@ihstowers.com","4988","05-09-2024 18:26:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_110","IHS_YND_028","NOCINC0003003430","H=
-Central","","05-09-2024 18:23:40","05-09-2024 18:18:17","06-09-2024 10:57:=
10","Active, no power issue, site on grid with U)53V, Mohamadou/691144435/ =
from Huawei is informed","Paul BIBOUM","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issue, =
site on grid with U)53V, Mohamadou/691144435/ from Huawei is informed","emm=
anuel.ghani@ihstowers.com","324","05-09-2024 18:23:40","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003003254","Mim=
boman3","","05-09-2024 18:01:43","05-09-2024 17:58:37","05-09-2024 18:22:23=
","Grid outage, Site went down before gen start due to poor battery backup =
// Gen start automatically","Mba Lazare Herve","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before gen start due to poor battery backup // Gen start automatically","j=
oelle.ekessi@ihstowers.com","187","05-09-2024 18:01:43","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0003003239","Feb=
e Village","","05-09-2024 17:57:08","05-09-2024 17:49:04","05-09-2024 18:30=
:35","Grid outage, Site went down before gen start due to poor battery back=
up // Gen start automatically","Mboua Thierry","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, Site went down=
 before gen start due to poor battery backup // Gen start automatically","j=
oelle.ekessi@ihstowers.com","911","05-09-2024 17:57:08","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_474","NOCINC0003003182","Yoko OCM","","05=
-09-2024 17:46:22","","","Cascaded Incident from TTO2831243","Parker Tchoup=
","","","","","","system","735","05-09-2024 17:46:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_008","IHS_YND_068","NOCINC0003003090","N=
disamba","","05-09-2024 17:30:15","05-09-2024 17:28:10","05-09-2024 17:30:1=
2","Grid outage, Gen fail to start due to Gen battery discharged//Gen start=
ed with backup battery","MINKA NICOLAS","Equipment Repair","Passive","ACDG =
Gen","ACDG - Generator Battery","Grid outage, Gen fail to start due to Gen =
battery discharged//Gen started with backup battery","emmanuel.ghani@ihstow=
ers.com","126","05-09-2024 17:30:15","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_475","NOCINC0003002966","Ngoum","","05-09=
-2024 17:09:00","","","Cascaded Incident from TTO2830982","Parker Tchoup","=
","","","","","system","113","05-09-2024 17:09:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0003002964","Matsari"=
,"","05-09-2024 17:09:00","05-09-2024 17:07:07","05-09-2024 22:18:38","Casc=
aded Incident from TTO2830982","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active// No power issue, site is on GEN wi=
th Ubaie=3D52,7 V  The Team  PRAUDICIA  //679781562//  from Huawei  working=
 on site  '"" Alignement TX'","system","113","05-09-2024 17:09:00","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0003002963","MBIMBIM"=
,"","05-09-2024 17:09:00","05-09-2024 17:07:07","05-09-2024 22:18:38","Casc=
aded Incident from TTO2830982","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active// No power issue, site is on GEN wi=
th Ubaie=3D52,7 V  The Team  PRAUDICIA  //679781562//  from Huawei  working=
 on site  '"" Alignement TX'","system","113","05-09-2024 17:09:00","Sagemco=
m CMR"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0003002959","Ngo=
uetou","IHS_YND_475, IHS_YND_460, IHS_YND_474, IHS_YND_456, IHS_YND_476","0=
5-09-2024 17:08:10","05-09-2024 17:07:07","05-09-2024 20:30:07","Active// N=
o power issue, site is on GEN with Ubaie=3D52,7 V  The Team  PRAUDICIA  //6=
79781562//  from Huawei  working on site  '"" Alignement TX'","Parker Tchou=
p","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active// No power issue, site is on GEN with Ubaie=3D52,7 V =
 The Team  PRAUDICIA  //679781562//  from Huawei  working on site  '"" Alig=
nement TX'","joelle.ekessi@ihstowers.com","64","05-09-2024 17:08:10","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0003002904","E=
kie sud","","05-09-2024 16:58:56","05-09-2024 16:51:48","06-09-2024 10:30:3=
3","Active, no power issue, site on grid with U=3D53,2V, Lionel /655184876/=
 From Huawei is informed  ","Albran Byorel","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power is=
sue, site on grid with U=3D53,2V, Lionel /655184876/ From Huawei is informe=
d  ","emmanuel.ghani@ihstowers.com","429","05-09-2024 16:58:56","Sagemcom C=
MR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0003002838","NTU=
I TOWN","","05-09-2024 16:47:01","05-09-2024 16:42:57","05-09-2024 17:10:53=
","Grid outage,Gen ran till fuel shortage//Refueling done","Parker Tchoup",=
"Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,Gen ran till =
fuel shortage//Refueling done","joelle.ekessi@ihstowers.com","245","05-09-2=
024 16:47:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003002768","Etoudi 2=
","","05-09-2024 16:29:11","05-09-2024 16:24:31","05-09-2024 17:00:56","Cas=
caded Incident from TTO2830728","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due to Gen card faulty // Gen manually started","system"=
,"280","05-09-2024 16:29:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003002767","ETOUDI C=
HAPELLE","","05-09-2024 16:29:11","05-09-2024 16:24:31","05-09-2024 17:00:5=
6","Cascaded Incident from TTO2830728","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen failed to start due to Gen card faulty // Gen manually started","s=
ystem","280","05-09-2024 16:29:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0003002766","Abattoir=
","","05-09-2024 16:29:10","05-09-2024 16:24:31","05-09-2024 17:00:56","Cas=
caded Incident from TTO2830728","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due to Gen card faulty // Gen manually started","system"=
,"279","05-09-2024 16:29:10","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003002740","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","05-09-2024 16:28:18","05-09-2=
024 16:24:31","05-09-2024 17:00:56","Grid outage site went down because Gen=
 failed to start due to Gen card faulty // Gen manually started","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Gri=
d outage site went down because Gen failed to start due to Gen card faulty =
// Gen manually started","joelle.ekessi@ihstowers.com","228","05-09-2024 16=
:28:18","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003002736","Eko=
unou","","05-09-2024 16:25:15","05-09-2024 16:17:09","05-09-2024 16:27:03",=
"Grid Outage, site went down because  Gen  start due to poor battery backup=
 // Grid Power return","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Outage, site went down because=
  Gen  start due to poor battery backup // Grid Power return","joelle.ekess=
i@ihstowers.com","488","05-09-2024 16:25:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0003002719","F=
ebe Village","","05-09-2024 16:21:29","05-09-2024 16:19:00","05-09-2024 16:=
23:14","Grid Outage, site went down because  Gen  start due to poor battery=
 backup // Grid Power return","Mboua Thierry","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid Outage, site went down =
because  Gen  start due to poor battery backup // Grid Power return","emman=
uel.ghani@ihstowers.com","150","05-09-2024 16:21:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0003002604","Afanoya"=
,"","05-09-2024 16:07:20","05-09-2024 16:03:18","05-09-2024 16:15:07","Casc=
aded Incident from TTO2830546","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid Fluctuation, site went down becau=
se  Gen failed to start due to poor battery backup // Grid Power return","s=
ystem","242","05-09-2024 16:07:20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0003002598","Aha=
la","IHS_YND_313","05-09-2024 16:06:23","05-09-2024 16:03:18","05-09-2024 1=
6:15:07","Grid Outage, site went down because  Gen failed to start due to p=
oor battery backup // Grid Power return","Hyemafo Gildas","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Battery Low","Grid Outage, sit=
e went down because  Gen failed to start due to poor battery backup // Grid=
 Power return","joelle.ekessi@ihstowers.com","185","05-09-2024 16:06:23","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0003002586","Carrefou=
rt Nkomo","","05-09-2024 16:01:40","05-09-2024 15:42:00","05-09-2024 16:12:=
55","Cascaded Incident from TTO2830514","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 because Gen started and stopped due to ""high temp"" alarm //He added wate=
r and gen manually started","system","1180","05-09-2024 16:01:40","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0003002574","N=
komo","IHS_YND_174","05-09-2024 15:59:05","05-09-2024 15:42:00","05-09-2024=
 16:12:55","Grid outage, site went down because Gen started and stopped due=
 to ""high temp"" alarm //He added water and gen manually started","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp=
 - Coolant Level Issue","Grid outage, site went down because Gen started an=
d stopped due to ""high temp"" alarm //He added water and gen manually star=
ted","emmanuel.ghani@ihstowers.com","1025","05-09-2024 15:59:05","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0003002527","Mbeng","=
","05-09-2024 15:52:51","05-09-2024 14:59:09","05-09-2024 15:54:47","Cascad=
ed Incident from TTO2830422","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down because Gen failed to start =
due to Hybrid system dysfonction// He reset the hybrid system","system","32=
22","05-09-2024 15:52:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0003002529","Bondjock=
","","05-09-2024 15:52:51","05-09-2024 14:59:09","05-09-2024 15:54:47","Cas=
caded Incident from TTO2830422","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down because Gen failed to sta=
rt due to Hybrid system dysfonction// He reset the hybrid system","system",=
"3222","05-09-2024 15:52:51","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003002499","Bas=
tos Amb Coree","","05-09-2024 15:49:28","05-09-2024 15:46:23","05-09-2024 1=
6:27:23","Grid outage no space to deploy // grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space t=
o deploy // grid return","joelle.ekessi@ihstowers.com","186","05-09-2024 15=
:49:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0003002236","Mom","",=
"05-09-2024 15:11:01","05-09-2024 14:59:09","05-09-2024 15:54:47","Cascaded=
 Incident from TTO2830102","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Site went down because Gen failed to start du=
e to Hybrid system dysfonction// He reset the hybrid system","system","712"=
,"05-09-2024 15:11:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0003002235","OTELE MT=
N","","05-09-2024 15:11:00","05-09-2024 15:03:09","05-09-2024 15:54:10","Ca=
scaded Incident from TTO2830102","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down because Gen failed to st=
art due to Hybrid system dysfonction// He reset the hybrid system","system"=
,"471","05-09-2024 15:11:00","Sagemcom CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0003002227","Min=
ka","IHS_YND_369, IHS_YND_531, IHS_YND_553, IHS_YND_370, IHS_YND_372","05-0=
9-2024 15:10:13","05-09-2024 14:59:09","05-09-2024 15:54:47","Site went dow=
n because Gen failed to start due to Hybrid system dysfonction// He reset t=
he hybrid system","Fanda Brice","Equipment Repair","Passive","Hybrid","Hybr=
id Module","Site went down because Gen failed to start due to Hybrid system=
 dysfonction// He reset the hybrid system","joelle.ekessi@ihstowers.com","2=
960","05-09-2024 15:10:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_327","NOCINC0003002136","Nsimalen=
 OCM","","05-09-2024 14:59:10","05-09-2024 14:50:24","05-09-2024 15:58:24",=
"Cascaded Incident from TTO2829983","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down becaus=
e gen start and stopped with alarm 'Overcurrent' // He reset gen card and m=
anually start the gen","system","526","05-09-2024 14:59:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0003002128","N=
kolda","IHS_YND_327","05-09-2024 14:57:32","05-09-2024 14:50:24","05-09-202=
4 15:58:24","","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACD=
G - Control Panel","Grid outage, site went down because gen start and stopp=
ed with alarm 'Overcurrent' // He reset gen card and manually start the gen=
","emmanuel.ghani@ihstowers.com","429","05-09-2024 14:57:32","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0003002115","Nko=
mo stade","","05-09-2024 14:54:05","05-09-2024 14:48:01","05-09-2024 15:10:=
43","site went down  because 01/03 RECTIFIER dysfonction due to load iincre=
ased // He reset the rectifier","Mba Lazare Herve","Equipment Repair","Pass=
ive","Rectifier","Rectifier Module","site went down  because 01/03 RECTIFIE=
R dysfonction due to load iincreased // He reset the rectifier","joelle.eke=
ssi@ihstowers.com","365","05-09-2024 14:54:05","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0003002106","Pha=
rmacie SION","","05-09-2024 14:52:43","05-09-2024 14:50:38","05-09-2024 15:=
00:42","Grid Outage site went down due to controller Psc3 dysfonctioning//h=
e reset it and started the Gen","Paul BIBOUM","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","Grid Outage site went down due to contro=
ller Psc3 dysfonctioning//he reset it and started the Gen","joelle.ekessi@i=
hstowers.com","126","05-09-2024 14:52:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0003001837","Elig Edz=
oa","","05-09-2024 14:06:43","05-09-2024 12:58:59","05-09-2024 13:00:17","C=
ascaded Incident from TTO2829131","Delor Telezing","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site ubaie=3D54v sit=
e on grid brice Tsague (Huawei) is informed","system","4064","05-09-2024 14=
:06:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0003001835","Hopital =
Central","","05-09-2024 14:06:43","05-09-2024 12:58:59","05-09-2024 13:00:1=
7","Cascaded Incident from TTO2829131","","Cascade Outage","Active","Cascad=
e Active","Cascade Active","No power issue on site ubaie=3D54v site on grid=
 brice Tsague (Huawei) is informed","system","4064","05-09-2024 14:06:43","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_016","NOCINC0003001833","Maetur",=
"","05-09-2024 14:06:43","05-09-2024 12:58:59","05-09-2024 13:00:17","Casca=
ded Incident from TTO2829131","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site ubaie=3D54v site on =
grid brice Tsague (Huawei) is informed","system","4064","05-09-2024 14:06:4=
3","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0003001836","Charles-=
Atangana","","05-09-2024 14:06:43","05-09-2024 12:58:59","05-09-2024 13:00:=
17","Cascaded Incident from TTO2829131","","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue on site ubaie=3D54v site on gri=
d brice Tsague (Huawei) is informed","system","4064","05-09-2024 14:06:43",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_134","NOCINC0003001834","Vallee B=
astos MTN","","05-09-2024 14:06:43","05-09-2024 12:58:59","05-09-2024 13:00=
:17","Cascaded Incident from TTO2829131","Mboua Thierry","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site ubaie=3D5=
4v site on grid brice Tsague (Huawei) is informed","system","4064","05-09-2=
024 14:06:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0003001831","Garbati =
building","","05-09-2024 14:06:42","05-09-2024 12:58:59","05-09-2024 13:00:=
17","Cascaded Incident from TTO2829131","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site ubaie=3D5=
4v site on grid brice Tsague (Huawei) is informed","system","4063","05-09-2=
024 14:06:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_013","NOCINC0003001830","Laborato=
ire T.Bella","","05-09-2024 14:06:42","05-09-2024 12:58:59","05-09-2024 13:=
00:17","Cascaded Incident from TTO2829131","Paul BIBOUM","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site ubaie=3D5=
4v site on grid brice Tsague (Huawei) is informed","system","4063","05-09-2=
024 14:06:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0003001832","ELIg-Ess=
ono","","05-09-2024 14:06:42","05-09-2024 12:58:59","05-09-2024 13:00:17","=
Cascaded Incident from TTO2829131","Delor Telezing","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site ubaie=3D54v si=
te on grid brice Tsague (Huawei) is informed","system","4063","05-09-2024 1=
4:06:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_001","NOCINC0003001829","Royal Ho=
tel Yde","","05-09-2024 14:06:42","05-09-2024 12:58:59","05-09-2024 13:00:1=
7","Cascaded Incident from TTO2829131","Paul BIBOUM","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site ubaie=3D54v s=
ite on grid brice Tsague (Huawei) is informed","system","4063","05-09-2024 =
14:06:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0003001828","HOPITAL =
DE LA CAISSE","","05-09-2024 14:06:41","05-09-2024 12:58:59","05-09-2024 13=
:00:17","Cascaded Incident from TTO2829131","Delor Telezing","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site ubaie=
=3D54v site on grid brice Tsague (Huawei) is informed","system","4062","05-=
09-2024 14:06:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0003001827","POLYCLIN=
IQUE TSINGA","","05-09-2024 14:06:41","05-09-2024 12:58:59","05-09-2024 13:=
00:17","Cascaded Incident from TTO2829131","Mboua Thierry","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site ubaie=
=3D54v site on grid brice Tsague (Huawei) is informed","system","4062","05-=
09-2024 14:06:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0003001825","Mamch Bu=
ilding","","05-09-2024 14:06:41","05-09-2024 12:58:59","05-09-2024 13:00:17=
","Cascaded Incident from TTO2829131","Mboua Thierry","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue on site ubaie=3D54v =
site on grid brice Tsague (Huawei) is informed","system","4062","05-09-2024=
 14:06:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_049","NOCINC0003001826","Etoa-Mek=
i","","05-09-2024 14:06:41","05-09-2024 12:58:59","05-09-2024 13:00:17","Ca=
scaded Incident from TTO2829131","Delor Telezing","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site ubaie=3D54v site=
 on grid brice Tsague (Huawei) is informed","system","4062","05-09-2024 14:=
06:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_084","NOCINC0003001824","Briquett=
erie","","05-09-2024 14:06:41","05-09-2024 12:58:59","05-09-2024 13:00:17",=
"Cascaded Incident from TTO2829131","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue on site ubaie=3D54v site on grid br=
ice Tsague (Huawei) is informed","system","4062","05-09-2024 14:06:41","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0003001823","H-Franco=
 New","","05-09-2024 14:06:40","05-09-2024 12:58:59","05-09-2024 13:00:17",=
"Cascaded Incident from TTO2829131","Delor Telezing","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site ubaie=3D54v s=
ite on grid brice Tsague (Huawei) is informed","system","4061","05-09-2024 =
14:06:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0003001738","M=
ontee-Anne-Rouge","","05-09-2024 14:02:09","05-09-2024 13:39:01","05-09-202=
4 14:14:13","Grid outage.no space to deploy mobile gen//Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e.no space to deploy mobile gen//Grid return","landry.etame@ihstowers.com",=
"1389","05-09-2024 14:02:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0003001717","M=
vog-Manga","","05-09-2024 13:58:06","05-09-2024 13:44:59","05-09-2024 14:14=
:51","Grid fluctuation, site went down because gen failed to start due to g=
rid bad voltage // Grid stabilized","Albran Byorel","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation, site w=
ent down because gen failed to start due to grid bad voltage // Grid stabil=
ized","landry.etame@ihstowers.com","788","05-09-2024 13:58:06","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0003001633","N=
kolondom","","05-09-2024 13:42:52","05-09-2024 13:07:24","06-09-2024 11:24:=
06","Active, no power issue, site on Grid u=3D54v Symphorien /650257151/ fr=
om huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issue=
, site on Grid u=3D54v Symphorien /650257151/ from huawei is informed","lan=
dry.etame@ihstowers.com","2129","05-09-2024 13:42:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0003001622","MEHANDAN=
","","05-09-2024 13:41:00","05-09-2024 13:18:10","05-09-2024 13:33:10","Cas=
caded Incident from TTO2829353","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down before Gen =
started due to poor battery back up // Grid return","system","1370","05-09-=
2024 13:41:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0003001610","O=
dza II OCM","IHS_YND_528","05-09-2024 13:39:42","05-09-2024 13:18:10","05-0=
9-2024 13:33:10","Grid outage site went down before Gen started due to poor=
 battery back up // Grid return","Albran Byorel","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage site went dow=
n before Gen started due to poor battery back up // Grid return","landry.et=
ame@ihstowers.com","1294","05-09-2024 13:39:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0003001595","Messassi=
 2","","05-09-2024 13:38:22","05-09-2024 13:08:28","05-09-2024 13:36:43","C=
ascaded Incident from TTO2829311","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site was on gen due to grid outage=
, gen stopped with alarm overvoltage//reset gen card (investigations ongoin=
g)","system","1794","05-09-2024 13:38:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0003001594","Nyom OCM=
","","05-09-2024 13:38:22","05-09-2024 13:08:28","05-09-2024 13:36:43","Cas=
caded Incident from TTO2829311","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site was on gen due to grid outage, =
gen stopped with alarm overvoltage//reset gen card (investigations ongoing)=
","system","1794","05-09-2024 13:38:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0003001591","Olembe-T=
erminus","","05-09-2024 13:38:21","05-09-2024 13:08:28","05-09-2024 13:36:4=
3","Cascaded Incident from TTO2829311","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site was on gen due to grid o=
utage, gen stopped with alarm overvoltage//reset gen card (investigations o=
ngoing)","system","1793","05-09-2024 13:38:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0003001592","Messassi=
","","05-09-2024 13:38:21","05-09-2024 13:08:28","05-09-2024 13:36:43","Cas=
caded Incident from TTO2829311","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site was on gen due to grid outage, =
gen stopped with alarm overvoltage//reset gen card (investigations ongoing)=
","system","1793","05-09-2024 13:38:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0003001590","Ekombiti=
e","","05-09-2024 13:38:21","05-09-2024 13:08:28","05-09-2024 13:36:43","Ca=
scaded Incident from TTO2829311","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site was on gen due to grid outage,=
 gen stopped with alarm overvoltage//reset gen card (investigations ongoing=
)","system","1793","05-09-2024 13:38:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0003001593","Nkozoa",=
"","05-09-2024 13:38:21","05-09-2024 13:08:28","05-09-2024 13:36:43","Casca=
ded Incident from TTO2829311","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site was on gen due to grid outage, ge=
n stopped with alarm overvoltage//reset gen card (investigations ongoing)",=
"system","1793","05-09-2024 13:38:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0003001571","O=
lembe","IHS_YND_276, IHS_YND_300, IHS_YND_297, IHS_YND_306, IHS_YND_303, IH=
S_YND_280","05-09-2024 13:33:38","05-09-2024 13:08:28","05-09-2024 13:36:43=
","site was on gen due to grid outage, gen stopped with alarm overvoltage//=
reset gen card (investigations ongoing)","Fabrice Pouakam","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","site was on gen due to grid=
 outage, gen stopped with alarm overvoltage//reset gen card (investigations=
 ongoing)","landry.etame@ihstowers.com","1512","05-09-2024 13:33:38","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0003001551","Messassi=
 okolo","","05-09-2024 13:30:40","05-09-2024 12:54:14","05-09-2024 13:00:00=
","Cascaded Incident from TTO2829281","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","no power issue on site ubaie=3D54=
v Eric Zte 696422966 on site for swap","system","2186","05-09-2024 13:30:40=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0003001544","E=
MANA BILICK CITY","IHS_YND_279","05-09-2024 13:29:23","05-09-2024 12:54:14"=
,"06-09-2024 08:15:00","no power issue on site ubaie=3D54v Eric Zte 6964229=
66 on site for swap","Fabrice Pouakam","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","no power issue on site u=
baie=3D54v Eric Zte 696422966 on site for swap","landry.etame@ihstowers.com=
","2110","05-09-2024 13:29:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0003001531","N=
taba","IHS_YND_133","05-09-2024 13:24:38","05-09-2024 12:49:28","05-09-2024=
 13:42:24","site went down due to grid contactor fue cuts and gen didn't st=
art//bypassed the fuse","Delor Telezing","Equipment Repair","Passive","Cont=
rol Panel","ATS-AMF Issue","site went down due to grid contactor fue cuts a=
nd gen didn't start//bypassed the fuse","landry.etame@ihstowers.com","2111"=
,"05-09-2024 13:24:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0003001519","E=
lig-Edzoa","","05-09-2024 13:22:13","05-09-2024 12:49:28","05-09-2024 13:42=
:24","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
site went down due to grid contactor fue cuts and gen didn't start//bypasse=
d the fuse","landry.etame@ihstowers.com","2266","05-09-2024 13:22:13","Sage=
mcom CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0003001412","Hot=
el de Ville Yde","IHS_YND_711, IHS_YND_084, IHS_YND_563, IHS_YND_051, IHS_Y=
ND_049, IHS_YND_086, IHS_YND_064, IHS_YND_001, IHS_YND_013, IHS_YND_024, IH=
S_YND_014, IHS_YND_016, IHS_YND_134, IHS_YND_027, IHS_YND_125, IHS_YND_504"=
,"05-09-2024 13:08:44","05-09-2024 12:58:59","05-09-2024 13:00:17","No powe=
r issue on site ubaie=3D54v site on grid brice Tsague (Huawei) is informed"=
,"Paul BIBOUM","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","No power issue on site ubaie=3D54v site on grid =
brice Tsague (Huawei) is informed","ange.kongo@ihstowers.com","586","05-09-=
2024 13:08:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0003001362","O=
mnisport-Rail","","05-09-2024 13:01:09","05-09-2024 12:48:02","05-09-2024 1=
3:13:17","","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG =
- Generator Battery","grid outage, gen fail to start due to gen battery dis=
charged//gen started with backup battery","landry.etame@ihstowers.com","788=
","05-09-2024 13:01:09","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0003001358","Bas=
tos Amb Coree","","05-09-2024 13:00:29","05-09-2024 12:35:18","05-09-2024 1=
3:01:18","","","Grid Supply","Passive","Grid","National Grid - Grid Outage =
Issue","grid outage, no space for a MDG//grid return","ange.kongo@ihstowers=
.com","1512","05-09-2024 13:00:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003001354","M=
ANGUIERS CHAPELLE","","05-09-2024 12:59:28","05-09-2024 12:43:20","05-09-20=
24 12:59:33","Grid outage, site went down because  Gen failed to start due =
to poor battery backup // Gen automatically started","Fabrice Pouakam","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, site went down because  Gen failed to start due to poor battery b=
ackup // Gen automatically started","landry.etame@ihstowers.com","969","05-=
09-2024 12:59:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0003001324","N=
R-Bastos","","05-09-2024 12:54:43","05-09-2024 12:37:38","06-09-2024 08:27:=
56","Active: no power issue on site ,site on GRid with U=3D55,7V Team Eloun=
dou // 693212405 from HUAWEI is informed Notice that we have dysjunction at=
 OCM equipements","","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active: no power issue on site ,site on GR=
id with U=3D55,7V Team Eloundou // 693212405 from HUAWEI is informed Notice=
 that we have dysjunction at OCM equipements","landry.etame@ihstowers.com",=
"1026","05-09-2024 12:54:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0003001306","E=
-Police","","05-09-2024 12:51:42","05-09-2024 12:14:36","05-09-2024 14:21:4=
1","Grid outage No space to deploy //  Grid power return","","Grid Supply",=
"Passive","Grid","National Grid - Low Current Supply","Grid outage No space=
 to deploy //  Grid power return","landry.etame@ihstowers.com","2228","05-0=
9-2024 12:51:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0003001173","E=
NAM","","05-09-2024 12:39:32","05-09-2024 12:11:23","05-09-2024 16:00:55","=
Grid outage.no space to deploy mobile gen//Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage.no space to=
 deploy mobile gen//Grid return","landry.etame@ihstowers.com","1690","05-09=
-2024 12:39:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0003001098","C=
arington","","05-09-2024 12:28:18","05-09-2024 11:57:12","05-09-2024 12:26:=
42","Grid Outage//Grid Power return","","Grid Supply","Passive","Grid","Nat=
ional Grid - Grid Outage Issue","Grid Outage//Grid Power return","landry.et=
ame@ihstowers.com","1868","05-09-2024 12:28:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0003001050","Bastos B=
ethesda","","05-09-2024 12:21:51","05-09-2024 11:54:21","05-09-2024 13:00:1=
7","Cascaded Incident from TTO2828611","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage,gen stopped due to =
high temp alarm// reset the gen card(investigation ongoing), added water","=
system","1650","05-09-2024 12:21:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_010","NOCINC0003001051","CNR","",=
"05-09-2024 12:21:51","05-09-2024 11:54:21","05-09-2024 12:19:27","Cascaded=
 Incident from TTO2828611","Mboua Thierry","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","grid outage,gen stopped due to high temp al=
arm// reset the gen card(investigation ongoing), added water","system","165=
0","05-09-2024 12:21:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_126","NOCINC0003001049","Bastos-N=
ylon","","05-09-2024 12:21:50","05-09-2024 11:54:21","05-09-2024 12:19:27",=
"Cascaded Incident from TTO2828611","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen stopped due to hig=
h temp alarm// reset the gen card(investigation ongoing), added water","sys=
tem","1649","05-09-2024 12:21:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0003000965","C=
NDH","IHS_YND_126, IHS_YND_563, IHS_YND_010","05-09-2024 12:05:29","05-09-2=
024 11:54:21","05-09-2024 12:19:27","","Paul BIBOUM","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","grid out=
age,gen stopped due to high temp alarm// reset the gen card(investigation o=
ngoing), added water","landry.etame@ihstowers.com","668","05-09-2024 12:05:=
29","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0003000923","Jou=
vence 2000","","05-09-2024 12:02:16","05-09-2024 11:58:06","05-09-2024 14:2=
7:40","Grid outage, site went down because  Gen failed to start due to poor=
 battery backup // Grid Power return","Delor Telezing","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down because  Gen failed to start due to poor battery backup // Grid Po=
wer return","ange.kongo@ihstowers.com","251","05-09-2024 12:02:16","Sagemco=
m CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0003000896","AWA=
E OCM","","05-09-2024 11:59:42","05-09-2024 11:56:36","05-09-2024 12:54:48"=
,"site was on gen due to grid outage, gen stopped due to high temp//added w=
ater","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Hi=
gh Engine Temp - Coolant Level Issue","site was on gen due to grid outage, =
gen stopped due to high temp//added water","ange.kongo@ihstowers.com","187"=
,"05-09-2024 11:59:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0003000741","B=
iteng","","05-09-2024 11:31:28","05-09-2024 10:57:14","05-09-2024 12:20:23"=
,"Grid outage, site went down because  Gen failed to start due to poor batt=
ery backup // Gen automatically started","Mba Lazare Herve","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite went down because  Gen failed to start due to poor battery backup // Ge=
n automatically started","landry.etame@ihstowers.com","2056","05-09-2024 11=
:31:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0003000685","H=
-Prince","","05-09-2024 11:26:48","05-09-2024 10:43:36","05-09-2024 11:56:0=
6","Grid outage, site went down because  Gen failed to start due to poor ba=
ttery backup // Gen automatically started","Mboua Thierry","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down because  Gen failed to start due to poor battery backup // Gen=
 automatically started","landry.etame@ihstowers.com","2593","05-09-2024 11:=
26:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0003000672","M=
vog-Ada_OCM","","05-09-2024 11:24:51","05-09-2024 10:28:45","05-09-2024 21:=
42:31","Grid outage.no space to deploy mobile gen//Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deploy mobile gen//Grid return","landry.etame@ihstowers.com","3367=
","05-09-2024 11:24:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0003000670","A=
cropole","","05-09-2024 11:23:59","05-09-2024 10:26:51","05-09-2024 12:06:5=
7","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","grid outage, gen fail to start due to gen battery discharged//ge=
n started with backup battery","landry.etame@ihstowers.com","15540","05-09-=
2024 11:23:59","Sagemcom CMR"
"Closed Complete","Warning","T0051","IHS_YND_297","NOCINC0003000669","Messa=
ssi","","05-09-2024 11:23:40","","","site alarming because Grid outage// Ge=
n manaully started anad alarm cleared","Fabrice Pouakam","Warning","Warning=
","POWER","Warning - Site on Battery","site alarming because Grid outage// =
Gen manaully started anad alarm cleared","adonis.defokoua@ihstowers.com","4=
87","05-09-2024 11:23:40","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0003000666","Mim=
boman3","","05-09-2024 11:23:11","05-09-2024 11:05:58","05-09-2024 11:23:30=
","grid outage, site down before gen start due to poor backup//gen started"=
,"Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Battery Low","grid outage, site down before gen start due to poor ba=
ckup//gen started","ange.kongo@ihstowers.com","1034","05-09-2024 11:23:11",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0003000543","M=
vog Mbi New","IHS_YND_068, IHS_YND_036","05-09-2024 11:03:57","05-09-2024 1=
0:26:51","05-09-2024 12:06:57","grid outage, gen fail to start due to gen b=
attery discharged//gen started with backup battery","MINKA NICOLAS","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Generator Battery","grid outage, g=
en fail to start due to gen battery discharged//gen started with backup bat=
tery","landry.etame@ihstowers.com","2226","05-09-2024 11:03:57","Sagemcom C=
MR"
"Closed Complete","Site Down","T1328","IHS_YND_247","NOCINC0003000524","Oko=
lo","","05-09-2024 10:58:53","05-09-2024 10:55:22","05-09-2024 11:19:01",""=
,"Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil =
Pressure","grid outage, gen stopped with alarm low oil pressure//added oil =
and reset gen card","ange.kongo@ihstowers.com","212","05-09-2024 10:58:53",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0003000500","RUE=
 FOE","","05-09-2024 10:57:20","05-09-2024 10:51:12","05-09-2024 11:09:02",=
"site went down because the CB (32A) Gen dysjoncted due to lightning // He =
reamed the CB Gen","Delor Telezing","Force Majeure","Natural Disaster","Thu=
nderstrike","Equipment Damaged","site went down because the CB (32A) Gen dy=
sjoncted due to lightning // He reamed the CB Gen","ange.kongo@ihstowers.co=
m","369","05-09-2024 10:57:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0003000470","C=
arington","","05-09-2024 10:55:46","05-09-2024 10:24:38","05-09-2024 11:05:=
50","","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","grid outage//grid return","landry.etame@ihstowers.com","1870","05-09-202=
4 10:55:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0003000454","N=
kolndongo","","05-09-2024 10:52:35","05-09-2024 10:51:31","05-09-2024 11:32=
:38","Grid outage, site went down due to main gen faulty // 20Kva has deplo=
yed","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Genera=
tor Faulty","Grid outage, site went down due to main gen faulty // 20Kva ha=
s deployed","landry.etame@ihstowers.com","65","05-09-2024 10:52:35","Sagemc=
om CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0003000453","An-=
Marche-Melen","","05-09-2024 10:52:29","05-09-2024 10:49:22","05-09-2024 11=
:09:34","Grid outage.no space to deplo mobile gen//Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deplo mobile gen//Grid return","ange.kongo@ihstowers.com","188","0=
5-09-2024 10:52:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0003000402","Y=
de-M-Central","","05-09-2024 10:45:21","05-09-2024 10:15:15","05-09-2024 11=
:06:56","Grid Outage, No space to deploy MDG //Grid  Power return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage,=
 No space to deploy MDG //Grid  Power return","landry.etame@ihstowers.com",=
"1807","05-09-2024 10:45:21","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0003000379","Nko=
mkana","","05-09-2024 10:40:33","05-09-2024 10:22:28","05-09-2024 11:06:33"=
,"Grid Outage, No space to deploy MDG //Grid Power return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No spac=
e to deploy MDG //Grid Power return","ange.kongo@ihstowers.com","1086","05-=
09-2024 10:40:33","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0003000366","Ess=
os Marche","","05-09-2024 10:38:23","05-09-2024 10:16:18","06-09-2024 08:19=
:37","No power issue on site ubaie=3D54v site on grid","Delor Telezing","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","No power issue on site ubaie=3D54v site on grid","ange.kongo@ihsto=
wers.com","1326","05-09-2024 10:38:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_008","IHS_YND_068","NOCINC0003000364","N=
disamba","","05-09-2024 10:38:05","05-09-2024 10:26:51","05-09-2024 12:06:5=
7","grid outage, gen fail to start due to gen battery discharged//gen start=
ed with backup battery","MINKA NICOLAS","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","grid outage, gen fail to start due to gen batt=
ery discharged//gen started with backup battery","landry.etame@ihstowers.co=
m","2351","05-09-2024 10:38:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0003000308","ETOUDI C=
HAPELLE","","05-09-2024 10:31:21","05-09-2024 10:22:27","05-09-2024 11:10:2=
3","Cascaded Incident from TTO2827847","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","
Grid outage,DG Failed to start due to ACDG control panel faulty //Manually =
start of DG.
","system","534","05-09-2024 10:31:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0003000309","Etoudi 2=
","","05-09-2024 10:31:21","05-09-2024 10:22:27","05-09-2024 11:10:23","Cas=
caded Incident from TTO2827847","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","
Grid outage,DG Failed to start due to ACDG control panel faulty //Manually =
start of DG.
","system","534","05-09-2024 10:31:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_132","NOCINC0003000307","Manguier=
s Dispensaire","","05-09-2024 10:31:20","05-09-2024 10:22:27","05-09-2024 1=
1:10:23","Cascaded Incident from TTO2827847","Fabrice Pouakam","Cascade Out=
age","Passive","Cascade Passive","Cascade Passive","
Grid outage,DG Failed to start due to ACDG control panel faulty //Manually =
start of DG.
","system","533","05-09-2024 10:31:20","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0003000295","Eto=
udi","IHS_YND_132, IHS_YND_694, IHS_YND_211","05-09-2024 10:29:51","05-09-2=
024 10:22:27","05-09-2024 11:10:23"," Grid outage,DG Failed to start due to=
 ACDG control panel faulty //Manually start of DG.","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","
Grid outage,DG Failed to start due to ACDG control panel faulty //Manually =
start of DG.
","ange.kongo@ihstowers.com","445","05-09-2024 10:29:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0003000291","I=
mm-Olympique","","05-09-2024 10:29:29","05-09-2024 10:14:24","05-09-2024 14=
:08:11","grid outage,gen failed to start due to power cable alimented Gen t=
heft on sites// Grid return","Paul BIBOUM","Site Asset Theft","Theft","Thef=
t","AC Cable Stolen","grid outage,gen failed to start due to power cable al=
imented Gen theft on site s// Grid return","landry.etame@ihstowers.com","90=
6","05-09-2024 10:29:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0003000269","M=
ANGUIERS CHAPELLE","","05-09-2024 10:28:05","05-09-2024 10:13:59","05-09-20=
24 10:26:54","grid outage, site down before gen start due to poor backup//g=
en started","Fabrice Pouakam","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","grid outage, site down before gen start due =
to poor backup//gen started","landry.etame@ihstowers.com","847","05-09-2024=
 10:28:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0003000236","Eto koss=
 Yde","","05-09-2024 10:24:40","05-09-2024 10:11:36","05-09-2024 12:55:07",=
"Cascaded Incident from TTO2827781","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, main gen faulty//Mdg de=
ployed","system","784","05-09-2024 10:24:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0003000237","ELOUMDEM=
 CARRIERE 2","","05-09-2024 10:24:40","05-09-2024 10:11:36","05-09-2024 12:=
55:07","Cascaded Incident from TTO2827781","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage, main gen faulty/=
/Mdg deployed","system","784","05-09-2024 10:24:40","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0003000230","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","05-09-2024 10:23:41","05-09-2024 10:11=
:36","05-09-2024 12:55:07","Grid outage, main Gen faulty//Mdg deployed","Fa=
nda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty=
","Grid outage, main Gen faulty//Mdg deployed","ange.kongo@ihstowers.com","=
726","05-09-2024 10:23:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0003000216","L=
abogenie","","05-09-2024 10:20:00","05-09-2024 09:53:51","05-09-2024 14:09:=
45","Grid Outage, No space to deploy MDG // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No space =
to deploy MDG // Grid return","landry.etame@ihstowers.com","1570","05-09-20=
24 10:20:00","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0003000141","Eko=
unou","","05-09-2024 10:02:44","05-09-2024 12:09:34","05-09-2024 12:59:51",=
"grid outage,  gen stopped due to high temp alarm//added water","Albran Byo=
rel","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coo=
lant Level Issue","grid outage,  gen stopped due to high temp alarm//added =
water","ange.kongo@ihstowers.com","1430","05-09-2024 10:02:44","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0003000136","Carrefou=
rt Nkomo","","05-09-2024 10:01:21","05-09-2024 09:33:44","05-09-2024 11:26:=
03","Cascaded Incident from TTO2827663","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site was on gen due to grid=
 outage, gen stopped with oil pressure alarm unproven //reset gen card","sy=
stem","1657","05-09-2024 10:01:21","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0003000123","BAT=
A Mokolo OCM","","05-09-2024 09:57:26","05-09-2024 09:52:18","05-09-2024 15=
:46:30","Grid Outage, No space to deploy MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No sp=
ace to deploy MDG // Grid return","ange.kongo@ihstowers.com","309","05-09-2=
024 09:57:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0003000075","Nkolo II=
 New","","05-09-2024 09:48:30","05-09-2024 09:14:27","05-09-2024 11:02:41",=
"Cascaded Incident from TTO2827574","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site down because =
gen fail to start due to gen battery faulty//gen started with battery backu=
p","system","2043","05-09-2024 09:48:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0003000070","M=
imboman-Village","IHS_YND_709","05-09-2024 09:47:39","05-09-2024 09:14:27",=
"05-09-2024 11:02:41","grid outage, site down because gen fail to start due=
 to gen battery faulty//gen started with battery backup","Mba Lazare Herve"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","grid o=
utage, site down because gen fail to start due to gen battery faulty//gen s=
tarted with battery backup","landry.etame@ihstowers.com","1992","05-09-2024=
 09:47:39","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0003000060","Mim=
boman4","","05-09-2024 09:45:35","05-09-2024 09:41:23","05-09-2024 11:26:08=
","grid outage, gen fail to start due to gen battery charger faulty//gen st=
arted with battery backup","Mba Lazare Herve","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Charging Alternator","grid outage, gen fail to start due=
 to gen battery charger faulty//gen started with battery backup","ange.kong=
o@ihstowers.com","253","05-09-2024 09:45:35","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0003000046","Tou=
ring Club International","","05-09-2024 09:41:48","05-09-2024 09:33:43","05=
-09-2024 09:38:42","site was on gen due to grid outage, gen stopped with un=
proven low oil pressure alarm //reset gen card (investigations ongoing)","A=
lbran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel=
","site was on gen due to grid outage, gen stopped with unproven low oil pr=
essure alarm //reset gen card (investigations ongoing)","ange.kongo@ihstowe=
rs.com","486","05-09-2024 09:41:48","Sagemcom CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0003000040","Nko=
mo","IHS_YND_174","05-09-2024 09:40:50","05-09-2024 09:33:44","05-09-2024 1=
0:41:30","site was on gen due to grid outage, gen stopped with oil pressure=
 alarm unproven //reset gen card","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Control Panel","site was on gen due to grid outag=
e, gen stopped with oil pressure alarm unproven //reset gen card","ange.kon=
go@ihstowers.com","426","05-09-2024 09:40:50","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0003000034","MIM=
BOMAN LIBERTE","","05-09-2024 09:39:19","05-09-2024 09:32:11","05-09-2024 1=
1:08:07","grid outage, main gen is faulty//MDG of 20 Kva deployed","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty=
","grid outage, main gen is faulty//MDG of 20 Kva deployed","ange.kongo@ihs=
towers.com","429","05-09-2024 09:39:19","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002999921","Nsi=
meyong Shell","","05-09-2024 09:21:36","05-09-2024 09:12:28","05-09-2024 09=
:24:15","Grid outage,site went down before DG start : Poor Batteries backup=
 //DG started automatically.","MINKA NICOLAS","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage,site went down b=
efore DG start : Poor Batteries backup //DG started automatically.","ange.k=
ongo@ihstowers.com","549","05-09-2024 09:21:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0002999818","E=
mombo-Tchad","IHS_YND_114","05-09-2024 09:07:04","05-09-2024 08:58:58","05-=
09-2024 15:21:15","Grid Outage//Grid Restored","","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","Grid Outage//Grid Restored","lan=
dry.etame@ihstowers.com","487","05-09-2024 09:07:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0002999798","K=
ondengui","","05-09-2024 09:03:33","05-09-2024 08:58:58","05-09-2024 15:21:=
15","","Albran Byorel","Cascade Outage","Passive","Cascade Passive","Cascad=
e Passive","Grid Outage//Grid Restored","landry.etame@ihstowers.com","543",=
"05-09-2024 09:03:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0002999641","H=
-Progres","","05-09-2024 08:31:39","05-09-2024 08:27:27","05-09-2024 14:25:=
45","Grid Outage, No space to deploy MDG // Grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No space =
to deploy MDG // Grid return","landry.etame@ihstowers.com","253","05-09-202=
4 08:31:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0002999628","E=
ssomba","","05-09-2024 08:29:18","05-09-2024 08:19:12","05-09-2024 09:18:28=
","Grid outage site went down because Gen failed to started due to Gen card=
 Dysfunction // He reset the Gen card and Manually Started the Gen ","Mba L=
azare Herve","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","=
Grid outage site went down because Gen failed to started due to Gen card Dy=
sfunction // He reset the Gen card and Manually Started the Gen ","landry.e=
tame@ihstowers.com","607","05-09-2024 08:29:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0002999615","Abang","=
","05-09-2024 08:25:10","05-09-2024 08:14:41","05-09-2024 08:32:02","Cascad=
ed Incident from TTO2827023","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage, gen stopped due to diesel=
 outage//refueling done","system","629","05-09-2024 08:25:10","Sagemcom CMR=
"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0002999561","Nko=
langaa","IHS_YND_290","05-09-2024 08:12:46","05-09-2024 08:09:41","05-09-20=
24 08:33:43","grid outage, gen stopped due to diesel outage//refueling done=
","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outage","grid=
 outage, gen stopped due to diesel outage//refueling done","ange.kongo@ihst=
owers.com","186","05-09-2024 08:12:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0002999560","C=
amp-Sic-Tsinga","","05-09-2024 08:12:18","05-09-2024 08:03:14","05-09-2024 =
14:27:10","Grid Outage, No space to deploy MDG // Grid restored","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, N=
o space to deploy MDG // Grid restored","landry.etame@ihstowers.com","545",=
"05-09-2024 08:12:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002999536","B=
ATA-Mokolo","","05-09-2024 08:06:01","05-09-2024 07:59:56","05-09-2024 15:4=
6:48","Grid Outage, No space to deploy MDG // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No spac=
e to deploy MDG // Grid return","landry.etame@ihstowers.com","366","05-09-2=
024 08:06:01","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002999433","Jou=
vence 2000","","05-09-2024 07:49:24","05-09-2024 07:11:17","05-09-2024 07:5=
5:38","Site was on Gen due to Grid Outage, site down because Gen failed due=
 to poor backup before gen start//Grid Power return","Delor Telezing","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Site=
 was on Gen due to Grid Outage, site down because Gen failed due to poor ba=
ckup before gen start//Grid Power return","ange.kongo@ihstowers.com","2288"=
,"05-09-2024 07:49:24","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002999416","Jou=
vence 2000","","05-09-2024 07:43:34","05-09-2024 05:00:27","05-09-2024 06:4=
8:27","Grid outage, site down because Gen failed due to poor backup before =
gen start//Gen started manually","Delor Telezing","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site down b=
ecause Gen failed due to poor backup before gen start//Gen started manually=
","ange.kongo@ihstowers.com","9788","05-09-2024 07:43:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0002999331","E=
lig Edzoa","","05-09-2024 07:24:02","05-09-2024 07:09:52","05-09-2024 07:27=
:00","Site was on Gen due to Grid Outage, site down because Gen failed due =
to poor backup before gen start//Grid Power return","Delor Telezing","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Site =
was on Gen due to Grid Outage, site down because Gen failed due to poor bac=
kup before gen start//Grid Power return","landry.etame@ihstowers.com","851"=
,"05-09-2024 07:24:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0002999169","G=
olf Quater","","05-09-2024 07:01:02","05-09-2024 06:51:54","06-09-2024 08:4=
4:30","Active// No power issue on site U=3D53,5V site on Grid Team Abel/682=
840529/ZTE working on site ""Installation""","Mboua Thierry","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue on site U=3D53,5V site on Grid Team Abel/682840529/ZT=
E working on site ""Installation""","landry.etame@ihstowers.com","549","05-=
09-2024 07:01:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0002999127","D=
amas","","05-09-2024 06:54:11","05-09-2024 06:51:05","05-09-2024 06:54:52",=
"Site went due insufficient of rectifier on site(03)//He added 01 rectifier=
","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went due insufficient of rectifier on site(03)//He added 01 rectif=
ier","landry.etame@ihstowers.com","187","05-09-2024 06:54:11","Sagemcom CMR=
"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002998885","NKO=
MEKUI OCM","","05-09-2024 05:56:16","05-09-2024 05:50:07","05-09-2024 05:58=
:07","grid outage, site went down because gen faild to start due to poor ba=
ttery backup // gen automatically started","TIENTCHEU NZETCHIEU GAEL","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","grid=
 outage, site went down because gen faild to start due to poor battery back=
up // gen automatically started","stephane.nkamwa@ihstowers.com","370","05-=
09-2024 05:56:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0002998874","F=
ouda-New","","05-09-2024 05:51:40","05-09-2024 05:46:27","05-09-2024 06:50:=
40","Grid Outage, Site went down because Gen failed to start due Solenoid v=
alve faulty// He started Gen manualy","Delor Telezing","Equipment Repair","=
Passive","ACDG Gen","ACDG - Solenoid Coil","Grid Outage, Site went down bec=
ause Gen failed to start due Solenoid valve faulty// He started Gen manualy=
","alexandre.kamal@ihstowers.com","313","05-09-2024 05:51:40","Sagemcom CMR=
"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0002998836","Nta=
ba","","05-09-2024 05:41:10","05-09-2024 05:34:02","05-09-2024 05:45:49","N=
o power issue on site U=3D57v site on gen Armand of huawei is informed up a=
t 05:40","Delor Telezing","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D57v site o=
n gen Armand of huawei is informed up at 05:40","stephane.nkamwa@ihstowers.=
com","429","05-09-2024 05:41:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002998826","C=
arington","","05-09-2024 05:38:04","05-09-2024 05:26:58","05-09-2024 07:26:=
52","Grid Outage//Grid Power return","","Grid Supply","Passive","Grid","Nat=
ional Grid - Grid Outage Issue","Grid Outage//Grid Power return","alexandre=
.kamal@ihstowers.com","667","05-09-2024 05:38:04","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0002998683","Eli=
g Edzoa","","05-09-2024 05:04:22","05-09-2024 04:59:08","05-09-2024 06:29:5=
2","Grid outage.gen failed to start due to alarm'""low oil pressure""//we r=
eset card GE and gen manually started","Delor Telezing","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to star=
t due to alarm'""low oil pressure""//we reset card GE and gen manually star=
ted","stephane.nkamwa@ihstowers.com","315","05-09-2024 05:04:22","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0002998542","SOA VILL=
AGE","","05-09-2024 04:25:10","05-09-2024 04:16:11","05-09-2024 04:38:23","=
Cascaded Incident from TTO2825752","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage,gen stopped with alarm =
high temp//he added water in radiator","system","539","05-09-2024 04:25:10"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0002998541","SOA=
 TOWN","IHS_YND_323","05-09-2024 04:24:24","05-09-2024 04:14:11","05-09-202=
4 04:38:45","grid outage,gen stopped with alarm high temp//he added water i=
n radiator","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG -=
 High Engine Temp - Coolant Level Issue","grid outage,gen stopped with alar=
m high temp//he added water in radiator","stephane.nkamwa@ihstowers.com","8=
11","05-09-2024 04:24:24","Sagemcom CMR"
"Closed Complete","Site Down","T1432","IHS_YND_544","NOCINC0002998248","Jea=
n Vespa 2","","05-09-2024 02:50:25","05-09-2024 02:34:12","05-09-2024 03:11=
:39","grid outage,gen ran till fuel shortage//Refueling done","Mboua Thierr=
y","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran ti=
ll fuel shortage//Refueling done","stephane.nkamwa@ihstowers.com","1229","0=
5-09-2024 02:50:25","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002997610","Jou=
vence 2000","","05-09-2024 00:11:54","04-09-2024 23:56:43","05-09-2024 01:0=
2:56","Grid outage, site went down because  Gen failed to start due to poor=
 battery backup // Grid Power return","Delor Telezing","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down because  Gen failed to start due to poor battery backup // Grid Po=
wer return","stephane.nkamwa@ihstowers.com","912","05-09-2024 00:11:54","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0002997565","E=
lig Edzoa","","05-09-2024 00:04:55","04-09-2024 23:54:48","05-09-2024 01:02=
:17","Grid outage, site went down because  Gen failed to start due to poor =
battery backup // Grid Power return","Delor Telezing","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down because  Gen failed to start due to poor battery backup // Grid Pow=
er return","alexandre.kamal@ihstowers.com","608","05-09-2024 00:04:55","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002997194","B=
iteng","","04-09-2024 22:43:55","04-09-2024 22:32:59","04-09-2024 23:35:11"=
,"Active //No power issue, site is on gen with U=3D53,1 V ,  The TX FME Lio=
nel adjep//655184876//   Huawei is informed,Notice that we have disjunction=
 at BTS OCM ","Mba Lazare Herve","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active //No power issue, site =
is on gen with U=3D53,1 V ,  The TX FME Lionel adjep//655184876//   Huawei =
is informed,Notice that we have disjunction at BTS OCM ","alexandre.kamal@i=
hstowers.com","657","04-09-2024 22:43:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0002996886","MEHANDAN=
","","04-09-2024 21:45:10","04-09-2024 21:39:55","04-09-2024 21:46:39","Cas=
caded Incident from TTO2823732","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down before Gen =
started due to poor battery back up // Grid return","system","315","04-09-2=
024 21:45:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002996880","O=
dza II OCM","IHS_YND_528","04-09-2024 21:44:02","04-09-2024 21:39:55","04-0=
9-2024 21:46:39","Grid outage site went down before Gen started due to poor=
 battery back up // Grid return","Albran Byorel","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage site went dow=
n before Gen started due to poor battery back up // Grid return","landry.et=
ame@ihstowers.com","248","04-09-2024 21:44:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002996479","N=
koabang2","","04-09-2024 20:41:08","04-09-2024 20:34:01","04-09-2024 20:45:=
52","no power issue U:48V site on Grid. TX FME Leonel Steve   (655184876) f=
rom Huawei is informed,","Mba Lazare Herve","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","no power issue U:48=
V site on Grid. TX FME Leonel Steve   (655184876) from Huawei is informed,"=
,"landry.etame@ihstowers.com","428","04-09-2024 20:41:08","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0002996311","Odz=
a II","","04-09-2024 20:10:59","04-09-2024 20:04:45","04-09-2024 20:35:41",=
"site went down because Gen started and stopped due to ""high temp"" alarm =
//He added water and gen manually started","Albran Byorel","Equipment Repai=
r","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","si=
te went down because Gen started and stopped due to ""high temp"" alarm //H=
e added water and gen manually started","kouoh.jean@ihstowers.com","635","0=
4-09-2024 20:10:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_793","NOCINC0002996215","Eloumdem=
 stade","","04-09-2024 19:48:20","04-09-2024 19:09:35","04-09-2024 20:52:55=
","Cascaded Incident from TTO2822905","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage.gen failed to start du=
e to battery GE faulty//Gen manually started with external battery","system=
","2325","04-09-2024 19:48:20","Sagemcom CMR"
"Closed Complete","Site Down","T0602","IHS_YND_259","NOCINC0002996209","Sim=
bock MTN","IHS_YND_793","04-09-2024 19:44:41","04-09-2024 19:09:35","04-09-=
2024 20:52:55","Grid outage.gen failed to start due to battery GE faulty//G=
en manually started with external battery","Fanda Brice","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Generator Battery","Grid outage.gen failed to=
 start due to battery GE faulty//Gen manually started with external battery=
","kouoh.jean@ihstowers.com","2106","04-09-2024 19:44:41","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002995990","Eko=
unou","","04-09-2024 19:00:48","04-09-2024 18:56:34","04-09-2024 19:02:08",=
"Grid outage, site went down because  Gen failed to start due to poor batte=
ry backup // Grid Power return","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n because  Gen failed to start due to poor battery backup // Grid Power ret=
urn","kouoh.jean@ihstowers.com","256","04-09-2024 19:00:48","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0002995833","ODZ=
A CITE MBIA","","04-09-2024 18:36:33","04-09-2024 18:27:17","26-09-2024 12:=
55:25","Access issue due to landlord, Site went down because Landlord stopp=
ed Gen due to Noise// Grid restored on site","Albran Byorel","Access Denial=
","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Ac=
cess issue due to landlord, Site went down because Landlord stopped Gen due=
 to Noise// Grid restored on site","kouoh.jean@ihstowers.com","557","04-09-=
2024 18:36:33","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002995793","Bas=
tos Amb Coree","","04-09-2024 18:32:23","04-09-2024 17:09:37","04-09-2024 2=
2:24:32","site went down due to insufficient of rectifier on site//site sta=
bilized(need to added rectifier)","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","site went down due to insufficient of rectifier on s=
ite//site stabilized(need to added rectifier)","kouoh.jean@ihstowers.com","=
4967","04-09-2024 18:32:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002995788","ELOUMDEM=
 CARRIERE","","04-09-2024 18:31:30","04-09-2024 18:13:54","04-09-2024 18:55=
:54","Cascaded Incident from TTO2822358","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bec=
ause  Gen failed to start due to poor battery backup // Grid Power return",=
"system","1056","04-09-2024 18:31:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002995790","Afanoya"=
,"","04-09-2024 18:31:30","04-09-2024 18:13:54","04-09-2024 18:55:54","Casc=
aded Incident from TTO2822358","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because  G=
en failed to start due to poor battery backup // Grid Power return","system=
","1056","04-09-2024 18:31:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002995789","MBALNGON=
G LYCEE","","04-09-2024 18:31:30","04-09-2024 18:13:54","04-09-2024 18:55:5=
4","Cascaded Incident from TTO2822358","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down becau=
se  Gen failed to start due to poor battery backup // Grid Power return","s=
ystem","1056","04-09-2024 18:31:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0002995748","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","04-09-2024 18:22:02","04-09-=
2024 18:12:54","04-09-2024 18:55:54","Grid outage, site went down because  =
Gen failed to start due to poor battery backup // Grid Power return","Hyema=
fo Gildas","Equipment Repair","Passive","Control Panel","Power Cabinet - Ba=
ttery Low","Grid outage, site went down because  Gen failed to start due to=
 poor battery backup // Grid Power return","landry.etame@ihstowers.com","54=
9","04-09-2024 18:22:02","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002995399","Nko=
abang Ebolmedjock","","04-09-2024 17:25:27","04-09-2024 17:12:09","04-09-20=
24 17:25:34","no power issue U:54,V site on Grid. TX FME Leonel Steve   (65=
5184876) from Huawei is informed,","Mba Lazare Herve","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power =
issue U:54,V site on Grid. TX FME Leonel Steve   (655184876) from Huawei is=
 informed,","kouoh.jean@ihstowers.com","799","04-09-2024 17:25:27","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0002995274","N=
yom OCM","","04-09-2024 16:52:36","04-09-2024 16:44:28","04-09-2024 17:21:3=
7","Grid outage site went down because Gen stopped with alarm low oil press=
ure // He add the oil and Gen started","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Oil Pressure Sensor Faulty","Grid outage site=
 went down because Gen stopped with alarm low oil pressure // He add the oi=
l and Gen started","landry.etame@ihstowers.com","488","04-09-2024 16:52:36"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0002995145","O=
mnisport-Rail","","04-09-2024 16:32:53","04-09-2024 16:22:48","04-09-2024 1=
6:35:27","Active// No power issue on site U=3D54,5v site on Grid Gildas waf=
fo  Erick/659653638/ZTE working on site","Delor Telezing","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e// No power issue on site U=3D54,5v site on Grid Gildas waffo  Erick/65965=
3638/ZTE working on site","landry.etame@ihstowers.com","606","04-09-2024 16=
:32:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002994550","N=
koabang2","","04-09-2024 15:25:35","04-09-2024 15:03:26","04-09-2024 15:50:=
25"," grid outage, gen start and stopped due to Gen overload (16.5kva 220A)=
 // he reduice the load of site ","Mba Lazare Herve","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Overload"," grid outage, gen start and stopped du=
e to Gen overload (16.5kva 220A) // he reduice the load of site ","landry.e=
tame@ihstowers.com","1330","04-09-2024 15:25:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0002994449","K=
oweit City","","04-09-2024 15:05:57","04-09-2024 14:57:52","04-09-2024 15:1=
0:15","no power issue U:56,2V site on Grid. TX FME Leonel Steve   (65518487=
6) from Huawei is informed,Notice that we have disjunction at BTS OCM ","Al=
bran Byorel","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","no power issue U:56,2V site on Grid. TX FME Leonel=
 Steve   (655184876) from Huawei is informed,Notice that we have disjunctio=
n at BTS OCM ","landry.etame@ihstowers.com","486","04-09-2024 15:05:57","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002994417","Eko=
unou","","04-09-2024 15:03:27","04-09-2024 14:54:59","04-09-2024 15:08:46",=
"Grid outage, site went down because Gen failed to start due to poor batter=
y backup // Gen automatically started","Albran Byorel","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down because Gen failed to start due to poor battery backup // Gen auto=
matically started","kouoh.jean@ihstowers.com","509","04-09-2024 15:03:27","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002994407","N=
kolo II New","","04-09-2024 15:00:28","04-09-2024 14:54:47","04-09-2024 15:=
11:58","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, site went down because  Gen failed to start =
due to poor battery backup // Gen automatically started","landry.etame@ihst=
owers.com","6436","04-09-2024 15:00:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002994382","M=
imboman-Village","IHS_YND_709","04-09-2024 14:57:20","04-09-2024 14:54:47",=
"04-09-2024 15:11:58","Grid outage, site went down because  Gen failed to s=
tart due to poor battery backup // Gen automatically started","Mba Lazare H=
erve","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery=
 Low","Grid outage, site went down because  Gen failed to start due to poor=
 battery backup // Gen automatically started","landry.etame@ihstowers.com",=
"154","04-09-2024 14:57:20","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002994198","Mim=
boman3","","04-09-2024 14:39:10","04-09-2024 14:29:57","04-09-2024 14:47:37=
","Grid outage.site went down before gen failed to start due to poor backup=
//grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage.site went down before gen fa=
iled to start due to poor backup//grid return","kouoh.jean@ihstowers.com","=
554","04-09-2024 14:39:10","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002994146","Nsi=
meyong Shell","","04-09-2024 14:33:46","04-09-2024 14:24:31","04-09-2024 14=
:50:34","Grid outage, site went down before gen start due to poor battery b=
ackup // Grid Restored","MINKA NICOLAS","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site went down before=
 gen start due to poor battery backup // Grid Restored","kouoh.jean@ihstowe=
rs.com","556","04-09-2024 14:33:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0002994024","Y=
de-M-Central","","04-09-2024 14:05:47","04-09-2024 13:51:28","04-09-2024 16=
:41:13","Grid outage.no space to deploy mobile gen//Grid return ","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.n=
o space to deploy mobile gen//Grid return ","emmanuel.ghani@ihstowers.com",=
"860","04-09-2024 14:05:47","Sagemcom CMR"
"Closed Complete","Site Down","T0958","IHS_YND_269","NOCINC0002993974","Mvo=
g-Ebanda","","04-09-2024 13:56:39","04-09-2024 13:53:35","04-09-2024 14:29:=
15","Grid fluctuation;site went down because Gen failed to start due to Gri=
d bad voltage /He bypassed Grid and Gen started manually","Siligap Boris","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation;site went down because Gen failed to start due to Grid bad v=
oltage /He bypassed Grid and Gen started manually","joelle.ekessi@ihstowers=
.com","184","04-09-2024 13:56:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0002993804","M=
vog Mbi New","","04-09-2024 13:46:05","04-09-2024 13:37:58","04-09-2024 15:=
29:21","site went down because the Cb(125A) of PWC Dysjoncted// he made the=
 bridge of CB(125*125A) ","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","site went down because=
 the Cb(125A) of PWC Dysjoncted// he made the bridge of CB(125*125A) ","emm=
anuel.ghani@ihstowers.com","488","04-09-2024 13:46:05","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0002993751","UPA=
C LP","","04-09-2024 13:40:27","04-09-2024 13:38:23","04-09-2024 17:41:40",=
"Grid outage,No space to deploy a mobil gen //grid return  awaited","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
,No space to deploy a mobil gen //grid return  awaited","joelle.ekessi@ihst=
owers.com","125","04-09-2024 13:40:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002993737","B=
ATA-Mokolo","","04-09-2024 13:37:58","04-09-2024 12:18:46","04-09-2024 14:0=
8:37","rectifier issue","","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","site down due to not enough rectifiers on site//site stabilize=
d","kombi.samuel@ihstowers.com","4753","04-09-2024 13:37:58","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002993630","Pha=
rmacie SION","","04-09-2024 13:22:04","04-09-2024 13:19:00","04-09-2024 14:=
08:32","Grid outage.gen failed to start due to alarm'""low oil pressure""//=
we reset card GE and gen manually started","Paul BIBOUM","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to sta=
rt due to alarm'""low oil pressure""//we reset card GE and gen manually sta=
rted","joelle.ekessi@ihstowers.com","185","04-09-2024 13:22:04","Sagemcom C=
MR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0002993284","Imm=
-Olympique","","04-09-2024 12:49:59","04-09-2024 12:47:53","04-09-2024 13:3=
9:32","grid outage,gen failed to start due to power cable alimented Gen the=
ft on site s// Grid return","Paul BIBOUM","Site Asset Theft","Theft","Theft=
","AC Cable Stolen","grid outage,gen failed to start due to power cable ali=
mented Gen theft on site s// Grid return","joelle.ekessi@ihstowers.com","12=
7","04-09-2024 12:49:59","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002993195","Mim=
boman3","","04-09-2024 12:39:43","04-09-2024 12:32:39","04-09-2024 12:44:50=
","","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power=
 Cabinet - Battery Low","Grid outage, site went down because  Gen failed to=
 start due to poor battery backup // Grid Power return","joelle.ekessi@ihst=
owers.com","425","04-09-2024 12:39:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0002993141","E=
kounou","","04-09-2024 12:35:23","04-09-2024 12:13:16","04-09-2024 12:36:29=
","Grid outage, site went down because Gen failed to start due to poor batt=
ery backup // Gen automatically started","Albran Byorel","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down because Gen failed to start due to poor battery backup // Gen au=
tomatically started","emmanuel.ghani@ihstowers.com","10049","04-09-2024 12:=
35:23","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0002992979","Nko=
mo stade","","04-09-2024 12:13:53","04-09-2024 12:09:47","04-09-2024 12:27:=
30","Site went down due to one rectifier dysfunctioning//Site up ,rectifier=
s must be upgraded","Mba Lazare Herve","Equipment Repair","Passive","Rectif=
ier","Rectifier Module","Site went down due to one rectifier dysfunctioning=
//Site up ,rectifiers must be upgraded","joelle.ekessi@ihstowers.com","247"=
,"04-09-2024 12:13:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0002992587","M=
endong Maeture","","04-09-2024 11:44:46","04-09-2024 11:38:23","04-09-2024 =
11:40:02","","Hyemafo Gildas","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power Issue Site on Grid Ubai =
=3D5,5V, The FME Tx The TX FME Mbah Hosiah (674007438) is informed, Notice =
that we have disjunction at BTS OCM","emmanuel.ghani@ihstowers.com","383","=
04-09-2024 11:44:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_507","NOCINC0002992582","BIYEM AS=
SI LYCEE","","04-09-2024 11:43:52","04-09-2024 11:37:00","04-09-2024 11:53:=
19","Cascaded Incident from TTO2818658","Hyemafo Gildas","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active// Active: No power issue,=
 site is on Gen with Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 74 38) from H=
uawei is informed and Up at 11:53 AM","system","412","04-09-2024 11:43:52",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0002992581","Behind P=
 T school Yde","","04-09-2024 11:43:52","04-09-2024 11:37:00","04-09-2024 1=
1:53:19","Cascaded Incident from TTO2818658","Paul BIBOUM","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active// Active: No power issu=
e, site is on Gen with Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 74 38) from=
 Huawei is informed and Up at 11:53 AM","system","412","04-09-2024 11:43:52=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0002992583","BIYEMASS=
I NIKI","","04-09-2024 11:43:52","04-09-2024 11:37:00","04-09-2024 11:53:19=
","Cascaded Incident from TTO2818658","Hyemafo Gildas","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active// Active: No power issue, s=
ite is on Gen with Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 74 38) from Hua=
wei is informed and Up at 11:53 AM","system","412","04-09-2024 11:43:52","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0002992580","BONAS YD=
E","","04-09-2024 11:43:51","04-09-2024 11:37:00","04-09-2024 11:53:19","Ca=
scaded Incident from TTO2818658","Paul BIBOUM","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active// Active: No power issue, site is o=
n Gen with Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is i=
nformed and Up at 11:53 AM","system","411","04-09-2024 11:43:51","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0002992579","Biyemass=
i LAC","","04-09-2024 11:43:51","04-09-2024 11:37:00","04-09-2024 11:53:19"=
,"Cascaded Incident from TTO2818658","","Cascade Outage","Active","Cascade =
Active","Cascade Active","Active// Active: No power issue, site is on Gen w=
ith Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed=
 and Up at 11:53 AM","system","411","04-09-2024 11:43:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0002992576","Obili Ch=
apelle","","04-09-2024 11:43:51","04-09-2024 11:37:00","04-09-2024 11:53:19=
","Cascaded Incident from TTO2818658","Paul BIBOUM","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active// Active: No power issue, site=
 is on Gen with Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 74 38) from Huawei=
 is informed and Up at 11:53 AM","system","411","04-09-2024 11:43:51","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0002992578","Accacia =
New","","04-09-2024 11:43:51","04-09-2024 11:37:00","04-09-2024 11:53:19","=
Cascaded Incident from TTO2818658","","Cascade Outage","Active","Cascade Ac=
tive","Cascade Active","Active// Active: No power issue, site is on Gen wit=
h Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed a=
nd Up at 11:53 AM","system","411","04-09-2024 11:43:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0002992577","Ngoa Eke=
lle","","04-09-2024 11:43:51","04-09-2024 11:37:00","04-09-2024 11:53:19","=
Cascaded Incident from TTO2818658","Paul BIBOUM","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active// Active: No power issue, site is=
 on Gen with Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is=
 informed and Up at 11:53 AM","system","411","04-09-2024 11:43:51","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0002992575","Scalom",=
"","04-09-2024 11:43:50","04-09-2024 11:37:00","04-09-2024 11:53:19","Casca=
ded Incident from TTO2818658","Paul BIBOUM","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active// Active: No power issue, site is on G=
en with Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is info=
rmed and Up at 11:53 AM","system","410","04-09-2024 11:43:50","Sagemcom CMR=
"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0002992560","Nlo=
ng Mvolye New","IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND_562, IHS_YND=
_546, IHS_YND_683, IHS_YND_805, IHS_YND_507, IHS_YND_724","04-09-2024 11:41=
:04","04-09-2024 11:37:00","04-09-2024 12:58:20","Active// No power issue, =
site is on Gen with Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 74 38) from Hu=
awei is informed and Up at 11:53 AM","Paul BIBOUM","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No =
power issue, site is on Gen with Ubaie=3D54,5V,The tx Fme Hosiah (6 74 00 7=
4 38) from Huawei is informed and Up at 11:53 AM","joelle.ekessi@ihstowers.=
com","245","04-09-2024 11:41:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0002992316","N=
kolndongo","","04-09-2024 10:56:25","04-09-2024 10:49:06","04-09-2024 13:20=
:49","Grid Outage  Main Gen Faulty  MDG to be  deploy","MINKA NICOLAS","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","grid outage,=
 site down because gen engine blocked//grid return MDG deployment ongoing)"=
,"emmanuel.ghani@ihstowers.com","440","04-09-2024 10:56:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0002992309","T=
radex-Nkomo","","04-09-2024 10:55:00","04-09-2024 10:46:57","04-09-2024 11:=
20:56","Active// No power issue on site U=3D53,7v site on grid Team Erick/6=
96422966/ZTE working on site","Albran Byorel","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power=
 issue on site U=3D53,7v site on grid Team Erick/696422966/ZTE working on s=
ite","emmanuel.ghani@ihstowers.com","484","04-09-2024 10:55:00","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002992218","ELOUMDEM=
 CARRIERE","","04-09-2024 10:38:20","04-09-2024 09:16:01","04-09-2024 10:57=
:01","Cascaded Incident from TTO2817697","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage Main Gen Faulty// M=
DG of 20kva has deployed","system","4939","04-09-2024 10:38:20","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002992219","MBALNGON=
G LYCEE","","04-09-2024 10:38:20","04-09-2024 09:16:01","04-09-2024 10:57:0=
1","Cascaded Incident from TTO2817697","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid Outage Main Gen Faulty// MDG=
 of 20kva has deployed","system","4939","04-09-2024 10:38:20","Sagemcom CMR=
"
"Closed Complete","Site Down","T1060","IHS_YND_454","NOCINC0002992008","Ngo=
uetou","IHS_YND_456, IHS_YND_460, IHS_YND_475, IHS_YND_473","04-09-2024 10:=
10:14","04-09-2024 09:57:55","04-09-2024 12:58:20","Active// No power issue=
, site is on GEN with Ubaie=3D52,7 V  The Team  PRAUDICIA  //679781562//  f=
rom Huawei  working on site  '"" Alignement TX'","Parker Tchoup","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active// No power issue, site is on GEN with Ubaie=3D52,7 V  The Team  PR=
AUDICIA  //679781562//  from Huawei  working on site  '"" Alignement TX'","=
joelle.ekessi@ihstowers.com","740","04-09-2024 10:10:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002991973","B=
iteng","","04-09-2024 10:06:25","04-09-2024 09:54:19","04-09-2024 09:56:15"=
,"Active //No power issue, site is on gen with U=3D53,1 V ,  The TX FME Lio=
nel adjep//655184876//   Huawei is informed,Notice that we have disjunction=
 at BTS OCM ","Mba Lazare Herve","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active //No power issue, site =
is on gen with U=3D53,1 V ,  The TX FME Lionel adjep//655184876//   Huawei =
is informed,Notice that we have disjunction at BTS OCM ","emmanuel.ghani@ih=
stowers.com","727","04-09-2024 10:06:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0002991950","Yoko MTN=
","","04-09-2024 10:00:04","04-09-2024 09:57:55","04-09-2024 09:58:33","Cas=
caded Incident from TTO2817958 - Cascade Removed From TTO2817958","Parker T=
choup","Cascade Outage","Active","Cascade Active","Cascade Active","Active/=
/ No power issue, site is on GEN with Ubaie=3D52,7 V  The Team  PRAUDICIA  =
//679781562//  from Huawei  working on site  '"" Alignement TX'","system","=
925","04-09-2024 10:00:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002991949","Ngoum","=
","04-09-2024 10:00:03","04-09-2024 09:57:55","04-09-2024 09:58:33","Cascad=
ed Incident from TTO2817958 - Cascade Removed From TTO2817958","Parker Tcho=
up","Cascade Outage","Active","Cascade Active","Cascade Active","Active// N=
o power issue, site is on GEN with Ubaie=3D52,7 V  The Team  PRAUDICIA  //6=
79781562//  from Huawei  working on site  '"" Alignement TX'","system","966=
","04-09-2024 10:00:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002991948","Matsari"=
,"","04-09-2024 10:00:00","04-09-2024 09:57:55","04-09-2024 09:58:33","Casc=
aded Incident from TTO2817958 - Cascade Removed From TTO2817958","Parker Tc=
houp","Cascade Outage","Active","Cascade Active","Cascade Active","Active//=
 No power issue, site is on GEN with Ubaie=3D52,7 V  The Team  PRAUDICIA  /=
/679781562//  from Huawei  working on site  '"" Alignement TX'","system","7=
97","04-09-2024 10:00:00","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0002991930","MBI=
MBIM","","04-09-2024 09:58:49","04-09-2024 09:57:55","04-09-2024 12:58:20",=
"Active// No power issue, site is on GEN with Ubaie=3D52,7 V  The Team  PRA=
UDICIA  //679781562//  from Huawei  working on site  '"" Alignement TX'","P=
arker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Active","=
Active// No power issue, site is on GEN with Ubaie=3D52,7 V  The Team  PRAU=
DICIA  //679781562//  from Huawei  working on site  '"" Alignement TX'","jo=
elle.ekessi@ihstowers.com","12159","04-09-2024 09:58:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0002991909","A=
nguissa New","","04-09-2024 09:55:55","04-09-2024 09:54:46","04-09-2024 12:=
39:22","Grid outage, site went down because gen failed to start due to PWC =
dysfunction // Gen manually start","MINKA NICOLAS","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage, site went down because=
 gen failed to start due to PWC dysfunction // Gen manually start","emmanue=
l.ghani@ihstowers.com","70","04-09-2024 09:55:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002991898","Afanoya"=
,"","04-09-2024 09:52:20","04-09-2024 09:46:29","04-09-2024 10:10:14","Casc=
aded Incident from TTO2817914","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Gen started automatically ","system","=
351","04-09-2024 09:52:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0002991891","A=
hala","IHS_YND_313","04-09-2024 09:51:33","04-09-2024 09:46:29","04-09-2024=
 10:10:46","Grid outage, site went down before gen start due to poor batter=
y backup // Gen started automatically and Power issues Resolved Since 10:10=
 Am,The FME TX Leonel (694693436) From Huawei is informed","Hyemafo Gildas"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen started automatically and Power issues Resolved Since 10:10 Am,The FM=
E TX Leonel (694693436) From Huawei is informed","emmanuel.ghani@ihstowers.=
com","304","04-09-2024 09:51:33","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002991859","NKO=
MEKUI OCM","","04-09-2024 09:45:53","04-09-2024 09:38:49","04-09-2024 09:46=
:52","Grid outage site went down because Gen  start due to poor battery bac=
kup/// Gen Automatically Started","TIENTCHEU NZETCHIEU GAEL","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage s=
ite went down because Gen  start due to poor battery backup/// Gen Automati=
cally Started","joelle.ekessi@ihstowers.com","425","04-09-2024 09:45:53","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0002991831","E=
mombo-Tchad","","04-09-2024 09:38:31","04-09-2024 09:36:11","04-09-2024 11:=
55:32","Grid outage//Grid Restored","","Grid Supply","Passive","Grid","Nati=
onal Grid - Grid Outage Issue","Grid outage//Grid Restored","emmanuel.ghani=
@ihstowers.com","141","04-09-2024 09:38:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002991707","ELOUMDEM=
 CARRIERE 2","","04-09-2024 09:22:00","04-09-2024 09:16:01","04-09-2024 10:=
57:01","Cascaded Incident from TTO2817697","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Outage Main Gen Faulty//=
 MDG of 20kva has deployed","system","359","04-09-2024 09:22:00","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002991706","Eto koss=
 Yde","","04-09-2024 09:22:00","04-09-2024 09:16:01","04-09-2024 10:57:01",=
"Cascaded Incident from TTO2817697","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage Main Gen Faulty// MDG of=
 20kva has deployed","system","359","04-09-2024 09:22:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0002991700","O=
lezoa OCM","","04-09-2024 09:19:48","04-09-2024 07:42:54","04-09-2024 22:54=
:54","Access issue due to Landlord,grid outage,gen failed to start due to l=
ow fuel//grid return","","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","Access issue due to Landlord,","emmanuel.ghani@ihstowers.com"=
,"9117","04-09-2024 09:19:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0002991695","M=
EFOU ASSI","IHS_YND_767, IHS_YND_737, IHS_YND_768, IHS_YND_765","04-09-2024=
 09:18:16","04-09-2024 09:15:01","04-09-2024 10:57:33","Grid Outage Main Ge=
n Faulty// MDG of 20kva has deployed","Fanda Brice","Equipment Repair","Pas=
sive","ACDG Gen","ACDG - Generator Faulty","Grid Outage Main Gen Faulty// M=
DG of 20kva has deployed","emmanuel.ghani@ihstowers.com","196","04-09-2024 =
09:18:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0002991592","Biteng-M=
aetur","","04-09-2024 08:52:20","04-09-2024 08:47:47","04-09-2024 08:50:57"=
,"Cascaded Incident from TTO2817559","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage, site went down be=
cause Gen failed to start due to poor battery backup // Gen automatically s=
tarted","system","273","04-09-2024 08:52:20","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0002991586","Bit=
eng","IHS_YND_249","04-09-2024 08:50:51","04-09-2024 08:47:47","04-09-2024 =
08:50:57","Grid outage, site went down because Gen failed to start due to p=
oor battery backup // Gen automatically started","Mba Lazare Herve","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage, site went down because Gen failed to start due to poor battery backu=
p // Gen automatically started","joelle.ekessi@ihstowers.com","232","04-09-=
2024 08:50:51","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0002991539","NYO=
M 2 IHS","","04-09-2024 08:38:58","04-09-2024 08:35:55","04-09-2024 08:59:5=
3","Grid Outage  site went down because Gen ran untill fuel shortage // ref=
ueling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid Outage  site went down because Gen ran untill fuel shortage // r=
efueling done","joelle.ekessi@ihstowers.com","228","04-09-2024 08:38:58","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_008","IHS_YND_068","NOCINC0002991316","N=
disamba","IHS_YND_055","04-09-2024 07:52:00","04-09-2024 07:42:54","04-09-2=
024 22:54:54","Access issue due to Landlord,grid outage,gen failed to start=
 due to low fuel//grid return","MINKA NICOLAS","Access Denial","Lease Or Le=
gal","Landlord Related Issues","Access Issue - Land Lord","Access issue due=
 to Landlord,grid outage,gen failed to start due to low fuel//grid return",=
"emmanuel.ghani@ihstowers.com","547","04-09-2024 07:52:00","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002990391","Tsi=
nga","","04-09-2024 03:57:23","04-09-2024 03:54:16","04-09-2024 04:16:04","=
Grid outage,site went down before DG start: Poor Batteries Backup //Grid re=
turn","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage,site went down before DG start: Poor Bat=
teries Backup //Grid return","olivier.kwedi@ihstowers.com","188","04-09-202=
4 03:57:23","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002989766","Jou=
vence 2000","","04-09-2024 00:34:16","04-09-2024 00:24:07","04-09-2024 00:3=
2:34","Grid outage, site went down because  Gen failed to start due to poor=
 battery backup // Grid Power return","Delor Telezing","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down because  Gen failed to start due to poor battery backup // Grid Po=
wer return","olivier.kwedi@ihstowers.com","610","04-09-2024 00:34:16","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0002989743","E=
lig Edzoa","","04-09-2024 00:25:52","04-09-2024 00:22:47","04-09-2024 00:30=
:25","Grid outage, site went down because  Gen failed to start due to poor =
battery backup // Gen automatically started","Delor Telezing","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,=
 site went down because  Gen failed to start due to poor battery backup // =
Gen automatically started","dorothy.djantio@ihstowers.com","185","04-09-202=
4 00:25:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0002989729","E=
kie-Elegance","","04-09-2024 00:20:52","04-09-2024 00:14:46","04-09-2024 08=
:50:33","Grid outage//He deployed 20KVA","Albran Byorel","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage//He deployed =
20KVA","dorothy.djantio@ihstowers.com","367","04-09-2024 00:20:52","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_515","NOCINC0002989543","Etoug eb=
e Meweulo","","03-09-2024 23:28:41","03-09-2024 23:24:57","03-09-2024 23:25=
:36","Cascaded Incident from TTO2815179","Hyemafo Gildas","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid fluctuation;site went d=
own because Gen failed to start due to Grid bad voltage and No RCP on site =
//He bypassed Grid and Gen started manually","system","874","03-09-2024 23:=
28:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_143","NOCINC0002989542","Byemassi=
 Carrefour","","03-09-2024 23:28:40","03-09-2024 23:24:57","03-09-2024 23:2=
5:36","Cascaded Incident from TTO2815179","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation;site went dow=
n because Gen failed to start due to Grid bad voltage and No RCP on site //=
He bypassed Grid and Gen started manually","system","874","03-09-2024 23:28=
:40","Sagemcom CMR"
"Closed Complete","Site Down","T2584","IHS_YND_741","NOCINC0002989528","Mvo=
g Betsi Hospital","IHS_YND_143, IHS_YND_515","03-09-2024 23:27:10","03-09-2=
024 23:24:57","03-09-2024 23:25:36","Grid fluctuation;site went down becaus=
e Gen failed to start due to Grid bad voltage and No RCP on site //He bypas=
sed Grid and Gen started manually","Hyemafo Gildas","Grid Supply","Passive"=
,"Grid","National Grid - Phase Controller Faulty","Grid fluctuation;site we=
nt down because Gen failed to start due to Grid bad voltage and No RCP on s=
ite //He bypassed Grid and Gen started manually","olivier.kwedi@ihstowers.c=
om","866","03-09-2024 23:27:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0002989217","E=
SSOS OASIS 1111","","03-09-2024 22:30:46","03-09-2024 22:26:40","03-09-2024=
 22:36:51","No power issue on site.Site on Gen with Ubaie=3D53,5 V  The TX =
Fme  Armand Nguetsa /691144412/  From Huawei is informed.Site up at 10:36 P=
M","Siligap Boris","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue on site.Site on Gen with Ubai=
e=3D53,5 V  The TX Fme  Armand Nguetsa /691144412/  From Huawei is informed=
.Site up at 10:36 PM","dorothy.djantio@ihstowers.com","247","03-09-2024 22:=
30:46","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0002989106","Ako=
k Ndoe Yde","","03-09-2024 22:08:32","03-09-2024 21:56:21","03-09-2024 23:0=
6:41","Site went down because CB(63 A) MTN disjuncted in DC Box due to incr=
ease load in site//he reamed CB ,Site on Grid ","Hyemafo Gildas","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue",=
"Site went down because CB(63 A) MTN disjuncted in DC Box due to increase l=
oad in site//he reamed CB ,Site on Grid ","stephane.nkamwa@ihstowers.com","=
731","03-09-2024 22:08:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0002988649","M=
endong Maeture","","03-09-2024 20:58:48","03-09-2024 20:39:26","04-09-2024 =
11:00:58","Active// No power Issue Site on Grid Ubai =3D54,5V, The FME Tx T=
he TX FME Mbah Hosiah (674007438) is informed, Notice that we have disjunct=
ion at BTS OCM","Hyemafo Gildas","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active// No power Issue Site o=
n Grid Ubai =3D54,5V, The FME Tx The TX FME Mbah Hosiah (674007438) is info=
rmed, Notice that we have disjunction at BTS OCM","alexandre.kamal@ihstower=
s.com","1162","03-09-2024 20:58:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0002988554","SAA Entr=
ance","","03-09-2024 20:50:50","03-09-2024 20:36:59","03-09-2024 21:27:03",=
"Cascaded Incident from TTO2813966","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage ,site went down becaus=
e Gen  stopped due  to Gen belt was cut // he replaced the belt and Started=
 Gen ","system","831","03-09-2024 20:50:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0002988555","Saa","",=
"03-09-2024 20:50:50","03-09-2024 20:36:59","03-09-2024 21:27:03","Cascaded=
 Incident from TTO2813966","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid outage ,site went down because Gen  st=
opped due  to Gen belt was cut // he replaced the belt and Started Gen ","s=
ystem","831","03-09-2024 20:50:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_829","IHS_YND_404","NOCINC0002988527","S=
AA 2","IHS_YND_542, IHS_YND_405","03-09-2024 20:42:08","03-09-2024 20:31:59=
","03-09-2024 21:27:03","Grid outage ,site went down because Gen  stopped d=
ue  to Gen belt was cut // he replaced the belt and Started Gen ","Parker T=
choup","Equipment Repair","Passive","ACDG Gen","ACDG - Fan Belt","Grid outa=
ge ,site went down because Gen  stopped due  to Gen belt was cut // he repl=
aced the belt and Started Gen ","alexandre.kamal@ihstowers.com","609","03-0=
9-2024 20:42:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0002988406","H=
-Deputes","","03-09-2024 20:11:54","03-09-2024 17:36:48","03-09-2024 20:20:=
29","No power issue on site U=3D55v site on grid Brice stague 650214096 of =
huawei is informed,notice that disjunction of CB in BTS OCM","","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue on site U=3D55v site on grid Brice stague 650214096 of huaw=
ei is informed,notice that disjunction of CB in BTS OCM","alexandre.kamal@i=
hstowers.com","9307","03-09-2024 20:11:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0002988252","N=
kozoa","","03-09-2024 19:40:26","03-09-2024 19:34:09","03-09-2024 20:08:38"=
,"grid outage,gen start and stopped due to alarm under frequency//he reset =
the card and started it","Fabrice Pouakam","Equipment Repair","Passive","AC=
DG Gen","ACDG - Control Panel","grid outage,gen start and stopped due to al=
arm under frequency//he reset the card and started it","alexandre.kamal@ihs=
towers.com","378","03-09-2024 19:40:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0002988231","F=
ouda-New","","03-09-2024 19:35:23","03-09-2024 19:27:19","04-09-2024 06:00:=
26","Active// No power issue, site is on Grid with U=3D54,8 V The Tx Fme Ar=
mand //691144412 from Huawei is informed","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve// No power issue, site is on Grid with U=3D54,8 V The Tx Fme Armand //69=
1144412 from Huawei is informed","alexandre.kamal@ihstowers.com","485","03-=
09-2024 19:35:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0002988223","O=
dza II","","03-09-2024 19:34:19","03-09-2024 19:24:59","03-09-2024 19:58:17=
","grid outage,gen failed to start due grid bad voltage,no rcp // he bypass=
ed grid and started the gen","Albran Byorel","Grid Supply","Passive","Grid"=
,"National Grid - Phase Controller Faulty","grid outage,gen failed to start=
 due grid bad voltage,no rcp // he bypassed grid and started the gen","alex=
andre.kamal@ihstowers.com","562","03-09-2024 19:34:19","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0002988218","Com=
plex Beac II","","03-09-2024 19:33:09","03-09-2024 19:22:01","03-09-2024 20=
:34:25","grid outage,gen failed to start due to card Ge faulty//Gen manuall=
y started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","grid outage,gen failed to start due to card Ge faulty//Gen =
manually started","stephane.nkamwa@ihstowers.com","668","03-09-2024 19:33:0=
9","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002988076","E=
lig-Edzoa","","03-09-2024 19:12:58","03-09-2024 19:02:51","03-09-2024 20:17=
:19","No power issue on site U=3D53v site on grid Armand of huawei is infor=
med notice that disjunction of CB in BTS OCm","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site U=3D53v site on grid Armand of huawei is informed notice that disj=
unction of CB in BTS OCm","alexandre.kamal@ihstowers.com","608","03-09-2024=
 19:12:58","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0002987988","Awa=
e Escalier","","03-09-2024 19:03:31","03-09-2024 18:55:19","03-09-2024 19:1=
1:28","Grid outage, site went down because  Gen failed to start due to poor=
 battery backup // Gen started","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n because  Gen failed to start due to poor battery backup // Gen started","=
stephane.nkamwa@ihstowers.com","493","03-09-2024 19:03:31","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002987522","Bas=
tos Amb Coree","","03-09-2024 17:30:03","03-09-2024 17:24:49","03-09-2024 1=
7:28:49","  site went down because insufficient of rectifier on site//site =
stabilized(need to added one rectifier)","","Equipment Repair","Passive","R=
ectifier","Rectifier Module","  site went down because insufficient of rect=
ifier on site//site stabilized(need to added one rectifier)","stephane.nkam=
wa@ihstowers.com","316","03-09-2024 17:30:03","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002987479","Mim=
boman3","","03-09-2024 17:22:27","03-09-2024 17:18:12","03-09-2024 17:30:41=
","Grid outage, site went down because  Gen failed to start due to poor bat=
tery backup // Grid Power return","Mba Lazare Herve","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down because  Gen failed to start due to poor battery backup // Grid Powe=
r return","stephane.nkamwa@ihstowers.com","256","03-09-2024 17:22:27","Sage=
mcom CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0002987459","NKO=
ABANG NKOLO 3","","03-09-2024 17:15:19","03-09-2024 17:07:08","03-09-2024 1=
7:27:08","site went down due to work Lazare/SAGEMCOM/655999779/do the PM//E=
nd of work","Mba Lazare Herve","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","site went down due to work Lazare/SAGEMCOM/=
655999779/do the PM//End of work","stephane.nkamwa@ihstowers.com","492","03=
-09-2024 17:15:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_578","IHS_YND_017","NOCINC0002987137","H=
-Deputes","","03-09-2024 16:03:41","03-09-2024 11:58:36","03-09-2024 12:47:=
59","grid outage,no space to deploy a mobil gen // grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no =
space to deploy a mobil gen // grid return","alexandre.kamal@ihstowers.com"=
,"14706","03-09-2024 16:03:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_721","NOCINC0002987130","VOIRIE M=
UNICIPALE YAOUNDE","","03-09-2024 16:02:10","03-09-2024 12:19:32","03-09-20=
24 18:08:28","Cascaded Incident from TTO2810737","Paul BIBOUM","Cascade Out=
age","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D53,1v site on grid Hosiah of huawei is informed notice that disjunction =
of CB in BTS ocm","system","13358","03-09-2024 16:02:10","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002986483","Lad=
a I Yde","","03-09-2024 14:22:11","03-09-2024 13:39:50","03-09-2024 15:57:0=
6","site went down because gen overload (7kva;110A)//he started the gen man=
ually","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","site went down because gen overload (7kva;110A)//he started the g=
en manually","kouoh.jean@ihstowers.com","2541","03-09-2024 14:22:11","Sagem=
com CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0002986352","Bas=
tos Bethesda","","03-09-2024 14:02:27","03-09-2024 11:52:13","03-09-2024 12=
:21:13","Grid outage, site went down because  Gen failed to start due to po=
or battery backup // Grid Power return","Mboua Thierry","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site =
went down because  Gen failed to start due to poor battery backup // Grid P=
ower return","kouoh.jean@ihstowers.com","7815","03-09-2024 14:02:27","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0002986341","C=
arrefourt Nkomo","","03-09-2024 14:00:08","03-09-2024 13:27:50","03-09-2024=
 14:17:40","grid outage,gen failed to start due to grid bad voltage,no rcp/=
/he bypassed grid and started the gen","Mba Lazare Herve","Grid Supply","Pa=
ssive","Grid","National Grid - Phase Controller Faulty","grid outage,gen fa=
iled to start due to grid bad voltage,no rcp//he bypassed grid and started =
the gen","landry.etame@ihstowers.com","1939","03-09-2024 14:00:08","Sagemco=
m CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002986325","Pha=
rmacie SION","","03-09-2024 13:56:41","03-09-2024 11:55:16","03-09-2024 12:=
25:50","Grid outage, site went down because  Gen failed to start due to poo=
r battery backup // Grid Power return","Paul BIBOUM","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down because  Gen failed to start due to poor battery backup // Grid Powe=
r return","kouoh.jean@ihstowers.com","7285","03-09-2024 13:56:41","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002986307","Eko=
unou","","03-09-2024 13:51:30","03-09-2024 12:43:14","03-09-2024 12:51:15",=
"Grid outage, site went down because  Gen failed to start due to poor batte=
ry backup // Grid Power return","Albran Byorel","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n because  Gen failed to start due to poor battery backup // Grid Power ret=
urn","kouoh.jean@ihstowers.com","4123","03-09-2024 13:51:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0002986223","D=
joungolo","IHS_YND_711","03-09-2024 13:38:38","03-09-2024 13:04:33","03-09-=
2024 14:46:53","grid outage,gen failed to start//grid return(investigation =
ongoing)","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - C=
ontrol Panel","grid outage,gen failed to start//grid return(investigation o=
ngoing)","landry.etame@ihstowers.com","2046","03-09-2024 13:38:38","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0002986216","H=
-Franco New","","03-09-2024 13:37:12","03-09-2024 13:04:33","03-09-2024 14:=
46:53","","Delor Telezing","Cascade Outage","Passive","Cascade Passive","Ca=
scade Passive","grid outage,gen failed to start//grid return(investigation =
ongoing)","landry.etame@ihstowers.com","2117","03-09-2024 13:37:12","Sagemc=
om CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002985991","Nsi=
meyong Shell","","03-09-2024 13:00:35","03-09-2024 12:47:15","03-09-2024 13=
:05:56","Grid outage, site went down because gen failed start due to poor b=
attery backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
because gen failed start due to poor battery backup // Grid return","kouoh.=
jean@ihstowers.com","801","03-09-2024 13:00:35","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002985987","Jou=
vence 2000","","03-09-2024 12:59:31","03-09-2024 12:46:16","03-09-2024 13:0=
0:10","Grid outage, site went down because gen failed start due to poor bat=
tery backup // Grid return","Delor Telezing","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
ecause gen failed start due to poor battery backup // Grid return","kouoh.j=
ean@ihstowers.com","796","03-09-2024 12:59:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0002985981","N=
kolndongo","","03-09-2024 12:59:00","03-09-2024 12:54:52","03-09-2024 13:20=
:51","grid outage,gen stopped with alarm high temp//he added water in radia=
tor","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high =
temp//he added water in radiator","landry.etame@ihstowers.com","249","03-09=
-2024 12:59:00","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0002985974","MVA=
N SACEL","","03-09-2024 12:58:10","03-09-2024 12:45:00","03-09-2024 13:03:3=
3","Grid outage, site went down because gen failed start due to poor batter=
y backup // Grid return","MINKA NICOLAS","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down becau=
se gen failed start due to poor battery backup // Grid return","kouoh.jean@=
ihstowers.com","791","03-09-2024 12:58:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0002985942","N=
goulmekong-Nord","","03-09-2024 12:53:36","03-09-2024 12:29:18","03-09-2024=
 13:09:40","","Siligap Boris","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site went down because gen stoppet with 'Lo=
w oil pressure' alarm // he reset the Gen card","landry.etame@ihstowers.com=
","1630","03-09-2024 12:53:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0002985937","E=
leveur","IHS_YND_277","03-09-2024 12:52:24","03-09-2024 12:29:18","03-09-20=
24 13:09:40","","Siligap Boris","Equipment Repair","Passive","ACDG Gen","AC=
DG - Control Panel","Grid outage, site went down because gen stoppet with '=
Low oil pressure' alarm // he reset the Gen card","landry.etame@ihstowers.c=
om","1387","03-09-2024 12:52:24","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0002985915","Com=
plex Beac II","","03-09-2024 12:49:09","03-09-2024 12:17:50","03-09-2024 12=
:53:03","grid outage,gen failed to start due to card Ge faulty//Gen manuall=
y started ","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","grid outage,gen failed to start due to card Ge faulty//Gen=
 manually started ","kouoh.jean@ihstowers.com","1880","03-09-2024 12:49:09"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_311","IHS_YND_453","NOCINC0002985912","S=
ong-bong","","03-09-2024 12:48:45","03-09-2024 12:24:41","03-09-2024 12:30:=
46","No power issue on site.Site on Gen with Ubaie=3D54,9 V TX Fme Etienne =
/ 695033981 from huawei Iis informed ,","Kemeni Franklin","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site.Site on Gen with Ubaie=3D54,9 V TX Fme Etienne / 69503398=
1 from huawei Iis informed ,","landry.etame@ihstowers.com","1445","03-09-20=
24 12:48:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002985911","Afanoya"=
,"","03-09-2024 12:48:41","03-09-2024 12:11:37","03-09-2024 12:53:13","Casc=
aded Incident from TTO2810773","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site down because Gen fai=
led due to poor backup before gen start//Grid power return","system","2224"=
,"03-09-2024 12:48:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002985909","ELOUMDEM=
 CARRIERE","","03-09-2024 12:48:40","03-09-2024 12:11:37","03-09-2024 12:53=
:13","Cascaded Incident from TTO2810773","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site down because =
Gen failed due to poor backup before gen start//Grid power return","system"=
,"2223","03-09-2024 12:48:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002985910","MBALNGON=
G LYCEE","","03-09-2024 12:48:40","03-09-2024 12:11:37","03-09-2024 12:53:1=
3","Cascaded Incident from TTO2810773","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site down because Ge=
n failed due to poor backup before gen start//Grid power return","system","=
2223","03-09-2024 12:48:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0002985879","E=
NAM","IHS_YND_721","03-09-2024 12:40:47","03-09-2024 12:19:32","03-09-2024 =
18:08:28","No power issue on site U=3D53,1v site on grid Hosiah of huawei i=
s informed notice that disjunction of CB in BTS ocm","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site U=3D53,1v site on grid Hosiah of huawei is informed notice =
that disjunction of CB in BTS ocm","landry.etame@ihstowers.com","1276","03-=
09-2024 12:40:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0002985875","ETOUDI C=
HAPELLE","","03-09-2024 12:40:01","03-09-2024 12:05:14","03-09-2024 12:48:5=
0","Cascaded Incident from TTO2810724 - Cascade Removed From TTO2810724","D=
elor Telezing","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Battery Low","Grid outage, site went down because  Gen failed to start du=
e to poor battery backup // Gen automatically started","system","2087","03-=
09-2024 12:40:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0002985876","Etoudi 2=
","","03-09-2024 12:40:01","03-09-2024 12:05:14","03-09-2024 12:45:35","Cas=
caded Incident from TTO2810724","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen failed to start due =
to card Ge faulty//Gen manually started","system","2087","03-09-2024 12:40:=
01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0002985874","Abattoir=
","","03-09-2024 12:40:00","03-09-2024 12:05:14","03-09-2024 12:45:35","Cas=
caded Incident from TTO2810724","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen failed to start due =
to card Ge faulty//Gen manually started","system","2086","03-09-2024 12:40:=
00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0002985870","S=
tade-Abega","","03-09-2024 12:39:37","03-09-2024 12:19:29","03-09-2024 13:3=
8:02","grid outage,gen failed to start due to alarm failed to start//gen ca=
rd reset and started it","Mba Lazare Herve","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","grid outage,gen failed to start due to ala=
rm failed to start//gen card reset and started it","landry.etame@ihstowers.=
com","1209","03-09-2024 12:39:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0002985860","K=
ondengui","","03-09-2024 12:38:12","03-09-2024 12:19:03","03-09-2024 17:10:=
12","Active: no power issue, site is on grid with Ubaie=3D54,5V, Eloundou (=
693212405) from Huawei is informed site up","Albran Byorel","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: no power issue, site is on grid with Ubaie=3D54,5V, Eloundou (69321240=
5) from Huawei is informed site up","landry.etame@ihstowers.com","1150","03=
-09-2024 12:38:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0002985854","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","03-09-2024 12:37:16","03-09-=
2024 12:10:10","03-09-2024 12:53:13","Grid outage, site down because Gen fa=
iled due to poor backup before gen start//Grid power return","Hyemafo Gilda=
s","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid outage, site down because Gen failed due to poor backup before gen=
 start//Grid power return","landry.etame@ihstowers.com","1627","03-09-2024 =
12:37:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0002985845","E=
toudi","IHS_YND_244, IHS_YND_211","03-09-2024 12:36:03","03-09-2024 12:05:1=
4","03-09-2024 12:31:35","grid outage,gen failed to start due to card Ge fa=
ulty//Gen manually started","Fabrice Pouakam","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start due to c=
ard Ge faulty//Gen manually started","landry.etame@ihstowers.com","2049","0=
3-09-2024 12:36:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0002985834","M=
aison-Blanche-IHS","","03-09-2024 12:34:18","03-09-2024 12:05:08","03-09-20=
24 13:05:08","No power issue on site U=3D54v site on grid Hosiah of huawei =
is informed notice that disjunction of CB in BTS Ocm","","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site U=3D54v site on grid Hosiah of huawei is informed notice t=
hat disjunction of CB in BTS Ocm","landry.etame@ihstowers.com","1751","03-0=
9-2024 12:34:18","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0002985775","Nko=
mkana","","03-09-2024 12:32:09","03-09-2024 12:01:53","03-09-2024 12:49:49"=
,"Grid outage.no space to deploy mobile gen//Grid return ","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no space=
 to deploy mobile gen//Grid return ","kouoh.jean@ihstowers.com","1818","03-=
09-2024 12:32:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0002985770","E=
lig Edzoa","","03-09-2024 12:31:20","03-09-2024 12:04:15","03-09-2024 12:48=
:55","Grid outage, site went down because  Gen failed to start due to poor =
battery backup // Gen automatically started","Delor Telezing","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage,=
 site went down because  Gen failed to start due to poor battery backup // =
Gen automatically started","landry.etame@ihstowers.com","1626","03-09-2024 =
12:31:20","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002985750","Ess=
os Marche","","03-09-2024 12:27:31","03-09-2024 11:52:09","03-09-2024 12:00=
:31","No power issue on site U=3D54v site on grid Armand of huawei is infor=
med","Delor Telezing","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power issue on site ubaie=3D52V Armand=
 Nguetsa is informed","kouoh.jean@ihstowers.com","2123","03-09-2024 12:27:3=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002985749","C=
arington","","03-09-2024 12:27:02","03-09-2024 12:04:54","03-09-2024 12:47:=
07","Grid outage//Grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","Grid outage//Grid return","landry.etame@ihstower=
s.com","1330","03-09-2024 12:27:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002985742","Eto koss=
 Yde","","03-09-2024 12:26:32","03-09-2024 11:52:33","03-09-2024 14:23:15",=
"Cascaded Incident from TTO2810569","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,site went down because m=
ain gen faulty and grid bad voltage//he did a bridge on good phase","system=
","2039","03-09-2024 12:26:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002985743","ELOUMDEM=
 CARRIERE 2","","03-09-2024 12:26:32","03-09-2024 11:52:33","03-09-2024 14:=
23:15","Cascaded Incident from TTO2810569","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,site went down be=
cause main gen faulty and grid bad voltage//he did a bridge on good phase",=
"system","2039","03-09-2024 12:26:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002985729","N=
koabang2","","03-09-2024 12:24:57","03-09-2024 12:03:49","03-09-2024 13:02:=
32"," grid outage, gen start and stopped due to Gen overload (16.5kva 220A)=
 // he reduice the load of site  (Site swapped by ZTE)","Mba Lazare Herve",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Overload"," grid outage, ge=
n start and stopped due to Gen overload (16.5kva 220A) // he reduice the lo=
ad of site  (Site swapped by ZTE)","landry.etame@ihstowers.com","1269","03-=
09-2024 12:24:57","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002985728","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","03-09-2024 12:24:45","03-09-2024 11:52=
:33","03-09-2024 14:23:15","grid outage,site went down because main gen fau=
lty and grid bad voltage//he did a bridge on good phase","Fanda Brice","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","grid outage,=
site went down because main gen faulty and grid bad voltage//he did a bridg=
e on good phase","kouoh.jean@ihstowers.com","1933","03-09-2024 12:24:45","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002985686","N=
kolo II New","","03-09-2024 12:19:29","03-09-2024 11:50:24","03-09-2024 11:=
52:27","Active//No power issue on site.Site on Gen with Ubaie=3D50,3 V  The=
 TX Fme  Leonel Steve /655184876/  From Huawei is informed.","Mba Lazare He=
rve","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active//No power issue on site.Site on Gen with Ubaie=3D50=
,3 V  The TX Fme  Leonel Steve /655184876/  From Huawei is informed.","land=
ry.etame@ihstowers.com","1746","03-09-2024 12:19:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0002985682","C=
amp-Sic-Tsinga","","03-09-2024 12:18:34","03-09-2024 11:50:28","03-09-2024 =
12:49:42","Grid outage.no space to deploy mobile gen//grid power return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage.no space to deploy mobile gen//grid power return","landry.etame@ihsto=
wers.com","1687","03-09-2024 12:18:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0002985646","H=
-Progres","","03-09-2024 12:13:29","03-09-2024 12:00:19","03-09-2024 12:58:=
17","","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Grid outage No space to deploy //  Grid power return","landry.etame@ihst=
owers.com","791","03-09-2024 12:13:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0002985632","E=
ssomba","","03-09-2024 12:12:20","03-09-2024 11:57:12","03-09-2024 12:32:10=
","grid outage,gen stopped with alarm low oil pressure//he added oil and st=
arted the gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Low Oil Pressure","grid outage,gen stopped with alarm low oil pressu=
re//he added oil and started the gen","landry.etame@ihstowers.com","909","0=
3-09-2024 12:12:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0002985614","Y=
de-M-Central","","03-09-2024 12:10:41","03-09-2024 11:54:33","03-09-2024 11=
:56:40","Active: No power issue, site on Grid with Ubaie=3D54.5V, Brice Tsa=
gue (650 21 40 96) from Huawei is informed, Notice that we have disjunction=
 at BTS OCM","","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active: No power issue, site on Grid with Ubaie=
=3D54.5V, Brice Tsague (650 21 40 96) from Huawei is informed, Notice that =
we have disjunction at BTS OCM","landry.etame@ihstowers.com","969","03-09-2=
024 12:10:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0002985602","T=
ongolo OCM","","03-09-2024 12:09:35","03-09-2024 11:52:23","03-09-2024 13:2=
2:09","grid outage,gen failed to start due to fuse alimented the contactor =
Ge faulty//he did a bridge and started the gen","Delor Telezing","Equipment=
 Repair","Passive","Control Panel","ATS-AMF Issue","grid outage,gen failed =
to start due to fuse alimented the contactor Ge faulty//he did a bridge and=
 started the gen","landry.etame@ihstowers.com","1033","03-09-2024 12:09:35"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0002985597","A=
nguissa New","","03-09-2024 12:08:11","03-09-2024 11:51:53","03-09-2024 13:=
34:04","Grid outage, the site went down before gen failed to start due to p=
oor battery backup // Grid Power return","MINKA NICOLAS","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, the =
site went down before gen failed to start due to poor battery backup // Gri=
d Power return","landry.etame@ihstowers.com","1869","03-09-2024 12:08:11","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002985594","Sapeur",=
"","03-09-2024 12:07:10","03-09-2024 11:50:28","03-09-2024 12:51:51","tikec=
t need to cascade at E-police","Mboua Thierry","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 because  Gen...","system","1002","03-09-2024 12:07:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002985578","E=
-Police","IHS_YND_029","03-09-2024 12:06:09","03-09-2024 11:50:28","03-09-2=
024 12:51:32","","","Grid Supply","Passive","Grid","National Grid - Grid Ou=
tage Issue","Grid outage No space to deploy //  Grid power return","landry.=
etame@ihstowers.com","942","03-09-2024 12:06:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0002985480","I=
mm-Olympique","","03-09-2024 11:48:42","03-09-2024 11:36:36","03-09-2024 13=
:28:12","grid outage,gen failed to start due to power cable alimented Gen t=
heft on site since//he starte the gen with another power cable","Paul BIBOU=
M","Site Asset Theft","Theft","Theft","AC Cable Stolen","grid outage,gen fa=
iled to start due to power cable alimented Gen theft on site since//he star=
te the gen with another power cable","landry.etame@ihstowers.com","726","03=
-09-2024 11:48:42","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002985475","Mim=
boman3","","03-09-2024 11:47:33","03-09-2024 11:32:22","03-09-2024 11:44:22=
","Grid outage, site went down because  Gen failed to start due to poor bat=
tery backup // Gen automatically started","Mba Lazare Herve","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
site went down because  Gen failed to start due to poor battery backup // G=
en automatically started","kouoh.jean@ihstowers.com","912","03-09-2024 11:4=
7:33","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0002984756","UPA=
C LP","","03-09-2024 09:48:56","03-09-2024 09:38:43","03-09-2024 09:45:39",=
"Active, no power issue, site on grid with U=3D55,2V Tx FME mand Ngetsa (??=
699949553??)  From  Huawei is informed.  ","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power =
issue, site on grid with U=3D55,2V Tx FME mand Ngetsa (??699949553??)  From=
  Huawei is informed.  ","kouoh.jean@ihstowers.com","614","03-09-2024 09:48=
:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002984397","B=
ATA-Mokolo","","03-09-2024 08:43:16","03-09-2024 08:39:06","03-09-2024 19:0=
9:59","site went down due to insufficient of rectifier on site//site stabil=
ized(need to added 01 rectifier)","","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","site went down due to insufficient of rectifier on s=
ite//site stabilized(need to added 01 rectifier)","landry.etame@ihstowers.c=
om","251","03-09-2024 08:43:16","Sagemcom CMR"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0002984363","Eto=
ug ebe biscuiterie","","03-09-2024 08:34:01","03-09-2024 08:23:59","03-09-2=
024 09:20:19","Grid fluctuation, site went down because Gen failed to start=
 due to Grid bad voltage and no RCP on site// he bypass the Grid and Gen ma=
nually started","Hyemafo Gildas","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation, site went down because Ge=
n failed to start due to Grid bad voltage and no RCP on site// he bypass th=
e Grid and Gen manually started","kouoh.jean@ihstowers.com","603","03-09-20=
24 08:34:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0002984077","M=
elen Ba'aba","","03-09-2024 07:31:54","03-09-2024 07:27:38","03-09-2024 08:=
02:43","Grid fluctuation, site went down because Gen failed to start due to=
 Grid bad voltage// he bypass the Grid and Gen manually started","Siligap B=
oris","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","Grid fluctuation, site went down because Gen failed to start due to Gr=
id bad voltage// he bypass the Grid and Gen manually started","landry.etame=
@ihstowers.com","257","03-09-2024 07:31:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0002982573","M=
elen Ba'aba","","03-09-2024 00:25:17","02-09-2024 22:35:08","02-09-2024 23:=
57:35","Site went down because CB OCM (100A) disjunted at DC Box causing by=
  Grid  fluctuation //he reamed  CB ,site on GEN","Siligap Boris","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue"=
,"Site went down because CB OCM (100A) disjunted at DC Box causing by  Grid=
  fluctuation //he reamed  CB ,site on GEN","adonis.defokoua@ihstowers.com"=
,"6610","03-09-2024 00:25:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0002982036","O=
mnisport-Rail","","02-09-2024 22:19:20","02-09-2024 21:28:00","02-09-2024 2=
1:30:20","Active// No power issue, site is on Grid  with Ubaie=3D56,4 V, TH=
E Tx  Fme Armand Ngetsa(691144412)  from Huawei is informed, Notice that we=
 have disjunction at BTS OCM ","Delor Telezing","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er issue, site is on Grid  with Ubaie=3D56,4 V, THE Tx  Fme Armand Ngetsa(6=
91144412)  from Huawei is informed, Notice that we have disjunction at BTS =
OCM ","ludivine.ngamaleu@ihstowers.com","3081","02-09-2024 22:19:20","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0002981863","S=
OA 2","","02-09-2024 21:58:06","02-09-2024 20:27:00","02-09-2024 22:55:00",=
"Site went down because CB(100*80 A) disjunted in PWC//He reaned CB,Site on=
 Grid(investigation ongoing)","Siligap Boris","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down bec=
ause CB(100*80 A) disjunted in PWC//He reaned CB,Site on Grid(investigation=
 ongoing)","ludivine.ngamaleu@ihstowers.com","6397","02-09-2024 21:58:06","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002981850","ELOUMDEM=
 CARRIERE 2","","02-09-2024 21:54:20","02-09-2024 21:48:29","02-09-2024 21:=
50:14","Cascaded Incident from TTO2806104","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,grid bad voltage,=
main gen faulty//grid stabilized","system","351","02-09-2024 21:54:20","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002981849","Eto koss=
 Yde","","02-09-2024 21:54:20","02-09-2024 21:48:29","02-09-2024 21:50:14",=
"Cascaded Incident from TTO2806104","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,grid bad voltage,main ge=
n faulty//grid stabilized","system","351","02-09-2024 21:54:20","Sagemcom C=
MR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002981838","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","02-09-2024 21:51:38","02-09-2024 21:48=
:29","02-09-2024 21:51:14","grid outage,grid bad voltage,main gen faulty//g=
rid stabilized","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Generator Faulty","grid outage,grid bad voltage,main gen faulty//grid st=
abilized","olivier.kwedi@ihstowers.com","190","02-09-2024 21:51:38","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002981749","N=
koabang2","","02-09-2024 21:37:14","02-09-2024 21:07:04","02-09-2024 21:10:=
12","Active //No power issue, site is on gen with U=3D53,1 V ,  The TX FME =
Lionel adjep//655184876//   Huawei is informed,Notice that we have disjunct=
ion at BTS OCM","Mba Lazare Herve","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active //No power issue, sit=
e is on gen with U=3D53,1 V ,  The TX FME Lionel adjep//655184876//   Huawe=
i is informed,Notice that we have disjunction at BTS OCM","etienne.itondo@i=
hstowers.com","1810","02-09-2024 21:37:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002981036","ELOUMDEM=
 CARRIERE 2","","02-09-2024 19:27:00","02-09-2024 19:21:19","02-09-2024 19:=
24:09","Cascaded Incident from TTO2805167","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,grid bad voltage =
and main gen faulty//grid stabilized","system","341","02-09-2024 19:27:00",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002981030","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","02-09-2024 19:25:29","02-09-2024 19:21=
:19","02-09-2024 19:25:09","grid outage,grid bad voltage and main gen fault=
y//grid stabilized","Fanda Brice","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","grid outage,grid bad voltage and main gen faulty/=
/grid stabilized","olivier.kwedi@ihstowers.com","251","02-09-2024 19:25:29"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002980953","Nsi=
meyong Shell","","02-09-2024 19:15:41","02-09-2024 19:11:28","02-09-2024 19=
:29:07","Grid outage, site went down before gen start due to poor battery b=
ackup // Grid Power return","MINKA NICOLAS","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Grid Power return","olivier.kw=
edi@ihstowers.com","254","02-09-2024 19:15:41","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0002980942","Eto=
 koss Yde","","02-09-2024 19:13:13","02-09-2024 19:21:19","02-09-2024 19:25=
:09","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","grid outage,grid bad voltage and main gen faulty//grid stabilize=
d","olivier.kwedi@ihstowers.com","1424","02-09-2024 19:13:13","Sagemcom CMR=
"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0002980810","Obo=
bogo","","02-09-2024 18:56:09","02-09-2024 18:49:59","02-09-2024 18:57:37",=
"Grid outage, site down because Gen due to poor backup before gen start//ge=
n started automatically","MINKA NICOLAS","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site down because Ge=
n due to poor backup before gen start//gen started automatically","olivier.=
kwedi@ihstowers.com","371","02-09-2024 18:56:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0002980311","S=
OA TOWN","","02-09-2024 17:05:42","02-09-2024 17:04:36","02-09-2024 18:06:4=
3","site went down because insufficient of rectifier on site//he added 02 r=
ectifiers","Siligap Boris","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","site went down because insufficient of rectifier on site//he a=
dded 02 rectifiers","ludivine.ngamaleu@ihstowers.com","66","02-09-2024 17:0=
5:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0002979994","T=
radex-Nkomo","","02-09-2024 16:18:06","02-09-2024 16:15:02","02-09-2024 16:=
46:16","No power issue on site U=3D53,7v site on grid Lionel steeve of huaw=
ei is informed","Albran Byorel","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53,7=
v site on grid Lionel steeve of huawei is informed","ludivine.ngamaleu@ihst=
owers.com","185","02-09-2024 16:18:06","Sagemcom CMR"
"Closed Complete","Warning","T0573","IHS_YND_387","NOCINC0002979832","Talla=
 Monatele","","02-09-2024 15:49:11","","","site on alarm due to work Ulrich=
/656072680/Sagemcom working on site;do the PM//End of work","Parker Tchoup"=
,"Warning","Warning","POWER","Warning - Site on Battery","site on alarm due=
 to work Ulrich/656072680/Sagemcom working on site;do the PM//End of work",=
"dorothy.djantio@ihstowers.com","493","02-09-2024 15:49:11","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002979795","Bas=
tos Amb Coree","","02-09-2024 15:46:02","02-09-2024 15:43:55","02-09-2024 1=
6:10:12","site went down because insufficient of rectifier on site//site st=
abilized(need to added one rectifier)","","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","site went down because insufficient of rectifie=
r on site//site stabilized(need to added one rectifier)","olivier.kwedi@ihs=
towers.com","127","02-09-2024 15:46:02","Sagemcom CMR"
"Closed Complete","Site Down","T1367","IHS_YND_805","NOCINC0002979234","Beh=
ind P T school Yde","","02-09-2024 14:51:37","02-09-2024 14:31:27","02-09-2=
024 15:23:14","grid outage, gen start and stopped due to alarm emergency bu=
tton stop//he bypassed the button, reset card and started Gen","Paul BIBOUM=
","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency Stop","grid out=
age, gen start and stopped due to alarm emergency button stop//he bypassed =
the button, reset card and started Gen","olivier.kwedi@ihstowers.com","1211=
","02-09-2024 14:51:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0002979140","N=
ew-Marche-Melen","","02-09-2024 14:34:27","02-09-2024 14:28:23","02-09-2024=
 16:55:45","No power issue on site U=3D54v site on grid Team Erick/69642296=
6/ZTE working on site","Paul BIBOUM","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54v site on grid Team Erick/696422966/ZTE working on site","ludivine.nga=
maleu@ihstowers.com","365","02-09-2024 14:34:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002979007","B=
ATA-Mokolo","","02-09-2024 14:15:16","02-09-2024 14:14:12","02-09-2024 15:2=
9:21","Active// No power issue on site U=3D53,7V   site on gen Brice Tsague=
 (650214096) from Huawei is informed","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issu=
e on site U=3D53,7V   site on gen Brice Tsague (650214096) from Huawei is i=
nformed","ludivine.ngamaleu@ihstowers.com","65","02-09-2024 14:15:16","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0002978786","Y=
de-M-Central","","02-09-2024 13:34:06","02-09-2024 13:28:24","02-09-2024 15=
:06:25","Grid outage.no space to deploy mobile gen//grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no=
 space to deploy mobile gen//grid return","alexandre.kamal@ihstowers.com","=
343","02-09-2024 13:34:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0002978128","B=
astos Ekoudou","","02-09-2024 11:49:47","02-09-2024 11:45:33","02-09-2024 1=
1:58:18","Grid outage, site went down because gen failed to start due to po=
or battery backup // Gen automatically started","Mboua Thierry","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outag=
e, site went down because gen failed to start due to poor battery backup //=
 Gen automatically started","alexandre.kamal@ihstowers.com","255","02-09-20=
24 11:49:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0002978127","M=
adagascar-Yde-New","","02-09-2024 11:47:51","02-09-2024 11:40:43","02-09-20=
24 11:50:23","Active// No power issue on site U=3D53,2v site on gen Team Er=
ick/696422966/ZTE working on site","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active// No power issue o=
n site U=3D53,2v site on gen Team Erick/696422966/ZTE working on site","ale=
xandre.kamal@ihstowers.com","428","02-09-2024 11:47:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_625","IHS_YND_181","NOCINC0002978006","M=
imboman3","","02-09-2024 11:24:12","02-09-2024 11:15:06","02-09-2024 11:25:=
41","Active: no power issue on site ,site on GRid with U=3D54,5V Team Eloun=
dou // 693212405 from HUAWEI is informed ","Mba Lazare Herve","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive: no power issue on site ,site on GRid with U=3D54,5V Team Eloundou //=
 693212405 from HUAWEI is informed ","alexandre.kamal@ihstowers.com","547",=
"02-09-2024 11:24:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002977862","B=
ATA-Mokolo","","02-09-2024 10:59:26","02-09-2024 10:50:21","02-09-2024 10:5=
5:13","Active// No power issue on site U=3D53,7v site on gen Team Erick/696=
422966/ZTE working on site (installation in 2nde start)","","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive// No power issue on site U=3D53,7v site on gen Team Erick/696422966/ZTE=
 working on site (installation in 2nde start)","alexandre.kamal@ihstowers.c=
om","545","02-09-2024 10:59:26","Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0002977580","Ang=
uissa New","","02-09-2024 10:25:43","02-09-2024 10:19:33","02-09-2024 10:29=
:28","Grid outage, site went down before gen failed to start due to poor ba=
ttery backup // Grid Power return","MINKA NICOLAS","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went =
down before gen failed to start due to poor battery backup // Grid Power re=
turn","stephane.nkamwa@ihstowers.com","371","02-09-2024 10:25:43","Sagemcom=
 CMR"
"Cancelled","Warning","T1851","IHS_YND_330","NOCINC0002976861","OKOA Peage"=
,"","02-09-2024 07:40:13","","","","Fanda Brice","","","","","","stephane.n=
kamwa@ihstowers.com","260","02-09-2024 07:40:13","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002976805","NKO=
MEKUI OCM","","02-09-2024 07:20:12","02-09-2024 07:08:05","02-09-2024 07:15=
:53","Active// No power issue on site U=3D53,9v site on Gen mohamadou /6911=
44435of huawei is informed,R=E9p=E9titif issue","TIENTCHEU NZETCHIEU GAEL",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active// No power issue on site U=3D53,9v site on Gen mohamadou=
 /691144435of huawei is informed,R=E9p=E9titif issue","stephane.nkamwa@ihst=
owers.com","728","02-09-2024 07:20:12","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0002976423","Lob=
o 2","","02-09-2024 05:49:16","02-09-2024 05:44:35","02-09-2024 08:41:04","=
, site went down because Gen stopped due to ""high temp"" alarm //He added =
water and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Radiator",", site went down because Gen sto=
pped due to ""high temp"" alarm //He added water and gen manually started",=
"emmanuel.ghani@ihstowers.com","281","02-09-2024 05:49:16","Sagemcom CMR"
"Closed Complete","Site Down","T1494","IHS_YND_686","NOCINC0002976414","Oyo=
mabang Ecole","","02-09-2024 05:43:50","02-09-2024 05:39:45","02-09-2024 05=
:59:06","site went down because Gen stopped with alarm Gen over voltage// H=
e reduiced the AVR 230 V","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Over Voltage","site went down because Gen stopped=
 with alarm Gen over voltage// He reduiced the AVR 230 V","emmanuel.ghani@i=
hstowers.com","433","02-09-2024 05:43:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0002976270","M=
essa-Carriere OCM","","02-09-2024 04:59:02","02-09-2024 04:55:55","02-09-20=
24 06:25:34","Grid outage, No space to deploy the MDG // Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, No space to deploy the MDG // Grid return","joelle.ekessi@ihstowers.com=
","188","02-09-2024 04:59:02","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0002976261","Feb=
e Village","","02-09-2024 04:53:51","02-09-2024 04:49:32","02-09-2024 06:32=
:08","Grid outage , site went down because Gen stopped due to ""high temp""=
 alarm //He added water and gen manually started","Mboua Thierry","Equipmen=
t Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Iss=
ue","Grid outage , site went down because Gen stopped due to ""high temp"" =
alarm //He added water and gen manually started","emmanuel.ghani@ihstowers.=
com","337","02-09-2024 04:53:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0002976240","Entree C=
ite Verte","","02-09-2024 04:45:10","02-09-2024 04:35:20","02-09-2024 07:09=
:41","Cascaded Incident from TTO2799615","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid Outage// MDG of 20kva has =
deployed","system","590","02-09-2024 04:45:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0002976239","Nkomkana=
","","02-09-2024 04:45:10","02-09-2024 04:35:20","02-09-2024 07:09:41","Cas=
caded Incident from TTO2799615","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid Outage// MDG of 20kva has deployed","system","=
590","02-09-2024 04:45:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0002976233","C=
ite-Verte","IHS_YND_200, IHS_YND_543","02-09-2024 04:43:24","02-09-2024 04:=
35:20","02-09-2024 07:09:41","Grid Outage// MDG of 20kva has deployed","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Out=
age// MDG of 20kva has deployed","joelle.ekessi@ihstowers.com","485","02-09=
-2024 04:43:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0002975424","B=
astos Bethesda","","01-09-2024 23:53:55","01-09-2024 23:49:50","01-09-2024 =
23:58:50","Grid outage site went down because Gen start due to poor battery=
 backup///Grid power return","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage site went down be=
cause Gen start due to poor battery backup///Grid power return","joelle.eke=
ssi@ihstowers.com","246","01-09-2024 23:53:55","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002975293","NKO=
MEKUI OCM","","01-09-2024 23:18:43","01-09-2024 23:16:11","02-09-2024 01:00=
:37","Active// No power issue on site U=3D53,9v site on gen mohamadou of hu=
awei is informed and Up 11:24 PM","TIENTCHEU NZETCHIEU GAEL","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue on site U=3D53,9v site on gen mohamadou of huawei is =
informed and Up 11:24 PM","emmanuel.ghani@ihstowers.com","152","01-09-2024 =
23:18:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002975277","E=
lig-Edzoa","","01-09-2024 23:10:14","01-09-2024 23:06:10","02-09-2024 01:55=
:43","Active: No power issue, site is on Grid  with Ubaie=3D54,6V, THE fme =
Armand Ngetsa(691144412)  from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: N=
o power issue, site is on Grid  with Ubaie=3D54,6V, THE fme Armand Ngetsa(6=
91144412)  from Huawei is informed","joelle.ekessi@ihstowers.com","245","01=
-09-2024 23:10:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0002974659","SOA VILL=
AGE","","01-09-2024 21:27:30","01-09-2024 21:22:36","01-09-2024 22:32:36","=
Cascaded Incident from TTO2797804","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, site went down because=
 gen started and Stopped to start with alarm""over current"" // He Reset th=
e Gen card, remove 01 rectifier and started Gen manualy","system","294","01=
-09-2024 21:27:30","Sagemcom CMR"
"Closed Complete","Site Down","T1623","IHS_YND_320","NOCINC0002974655","SOA=
 TOWN","IHS_YND_323","01-09-2024 21:26:42","01-09-2024 21:20:57","01-09-202=
4 22:32:36","grid outage, site went down because gen started and Stopped to=
 start with alarm""over current"" // He Reset the Gen card, remove 01 recti=
fier and started Gen manualy","Siligap Boris","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","grid outage, site went down because gen =
started and Stopped to start with alarm""over current"" // He Reset the Gen=
 card, remove 01 rectifier and started Gen manualy","ange.kongo@ihstowers.c=
om","1686","01-09-2024 21:26:42","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0002974317","Eli=
g Edzoa","","01-09-2024 20:29:23","01-09-2024 20:09:11","01-09-2024 21:30:4=
0","Grid bad voltage ,Site went down because Gen failed to start due to gri=
d bad voltage;//he bypassed grid and started the gen","Delor Telezing","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
bad voltage ,Site went down because Gen failed to start due to grid bad vol=
tage;//he bypassed grid and started the gen","ange.kongo@ihstowers.com","31=
91","01-09-2024 20:29:23","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0002974236","Mel=
en Ba'aba","","01-09-2024 20:11:04","01-09-2024 19:59:08","01-09-2024 21:02=
:16","Grid outage, site went down gecause gen started and stoppead  with al=
arm ""under voltage""  causing by malfuntion AVR// He reset gen card ,set A=
VR and  started Gen ","Siligap Boris","Equipment Repair","Passive","ACDG Ge=
n","ACDG - AVR","Grid outage, site went down gecause gen started and stoppe=
ad  with alarm ""under voltage""  causing by malfuntion AVR// He reset gen =
card ,set AVR and  started Gen ","ange.kongo@ihstowers.com","3552","01-09-2=
024 20:11:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0002974111","Mbankolo=
 petit paris","","01-09-2024 19:41:31","01-09-2024 19:29:13","01-09-2024 19=
:58:56","Cascaded Incident from TTO2797143","Mboua Thierry","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage , Site went do=
wn because Gen started and stopped due to PWC overload(12Kilo; 210 A) causi=
ng by  increase on site// site stabilized","system","738","01-09-2024 19:41=
:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0002974070","A=
FEME NORD","IHS_YND_808","01-09-2024 19:31:30","01-09-2024 19:26:25","01-09=
-2024 19:58:56","Grid outage ;DG started but did feed the site due to Grid =
contactor faullty//Grid restored,waiting for replacement of grid contactor.=
","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","=
ATS-AMF Issue","Grid outage ;DG started but did feed the site due to Grid c=
ontactor faullty//Grid restored,waiting for replacement of grid contactor."=
,"adonis.defokoua@ihstowers.com","305","01-09-2024 19:31:30","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002974060","Aka=
k-Nkozoa-MTN-IHS","","01-09-2024 19:29:47","01-09-2024 19:17:07","01-09-202=
4 21:27:39","Grid bad voltage,no RCP ,DG failed to start //Manually start o=
f DG.","Fabrice Pouakam","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid bad voltage,no RCP ,DG failed to start //Manua=
lly start of DG.","ange.kongo@ihstowers.com","3670","01-09-2024 19:29:47","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002973795","ELOUMDEM=
 CARRIERE 2","","01-09-2024 18:36:30","01-09-2024 18:32:52","01-09-2024 18:=
39:08","Cascaded Incident from TTO2796774","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation,main gen fau=
lty//grid stabilized","system","218","01-09-2024 18:36:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002973794","Eto koss=
 Yde","","01-09-2024 18:36:30","01-09-2024 18:32:52","01-09-2024 18:39:08",=
"Cascaded Incident from TTO2796774","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation,main gen faulty//gr=
id stabilized","system","218","01-09-2024 18:36:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002973779","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","01-09-2024 18:33:59","01-09-2024 18:32=
:52","01-09-2024 18:39:08","Grid fluctuation,main gen faulty//grid stabiliz=
ed","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator=
 Faulty","Grid fluctuation,main gen faulty//grid stabilized","ange.kongo@ih=
stowers.com","68","01-09-2024 18:33:59","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002973561","Mim=
boman3","","01-09-2024 17:52:21","01-09-2024 15:35:10","01-09-2024 15:47:10=
","Grid outage,site went down before DG start  : Poor Batteries Backup //DG=
 started automaticallly.","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage,site went down be=
fore DG start  : Poor Batteries Backup //DG started automaticallly.","ange.=
kongo@ihstowers.com","23385","01-09-2024 17:52:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0002973482","NTUI TOW=
N","","01-09-2024 17:39:56","01-09-2024 17:28:49","01-09-2024 17:46:07","Gr=
id outage, site went down because gen ran untill fuel shortage // Grid retu=
rn (refueling ongoing)","Parker Tchoup","Fuel Outage","Passive","Diesel","D=
iesel Outage","Grid outage, site went down because gen ran untill fuel shor=
tage // Grid return (refueling ongoing)","ange.kongo@ihstowers.com","668","=
01-09-2024 17:39:56","Sagemcom CMR"
"Closed Complete","Warning","CTR_080","IHS_YND_298","NOCINC0002973416","Ole=
mbe","","01-09-2024 17:25:19","","","Site on battery due to grid bad voltag=
e //Manually start of DG.","Fabrice Pouakam","Warning","Warning","POWER","W=
arning - AC Phase 1 Voltage low","Site on battery due to grid bad voltage /=
/Manually start of DG.","alwine.fambou@ihstowers.com","4","01-09-2024 17:25=
:19","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002973375","MAN=
GUIERS CHAPELLE","","01-09-2024 17:15:01","01-09-2024 17:13:52","01-09-2024=
 17:25:24","Grid outage, site went down before gen start due to poor batter=
y backup // Gen start automatically","Fabrice Pouakam","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup // Gen start automatic=
ally","ange.kongo@ihstowers.com","70","01-09-2024 17:15:01","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002972614","Nsi=
meyong Shell","","01-09-2024 14:53:37","01-09-2024 14:51:29","01-09-2024 15=
:09:30","Grid outage, site down because Gen failed to start due to poor bac=
kup //Grid power return ","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site down because G=
en failed to start due to poor backup //Grid power return ","ange.kongo@ihs=
towers.com","129","01-09-2024 14:53:37","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0002972276","Nko=
lbong","","01-09-2024 14:03:14","01-09-2024 13:39:51","01-09-2024 15:31:32"=
,"Grid Outage, Site went down due to dysfunction  of controller Huawei// we=
 bypass controller Huawei and site on gen.","Delor Telezing","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Control Panel","Grid Outage, Site went do=
wn due to dysfunction  of controller Huawei// we bypass controller Huawei a=
nd site on gen.","olivier.kwedi@ihstowers.com","2914","01-09-2024 14:03:14"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_124","IHS_YND_208","NOCINC0002972208","A=
RMP","","01-09-2024 13:47:31","01-09-2024 13:43:27","01-09-2024 13:50:12","=
No power issue on site Ubaie=3D54,8 V site on grid The Tx Fme  Armand NGUET=
SA //691144412  from huawei is informed .","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site Ubaie=3D54,8 V site on grid The Tx Fme  Armand NGUETSA //691144412  f=
rom huawei is informed .","ludivine.ngamaleu@ihstowers.com","245","01-09-20=
24 13:47:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0002972160","Mamch Bu=
ilding","","01-09-2024 13:43:00","01-09-2024 13:33:26","01-09-2024 15:18:29=
","Cascaded Incident from TTO2794773","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage // MDG 15Kva has dep=
loyed","system","574","01-09-2024 13:43:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002972139","M=
essassi 2","","01-09-2024 13:39:38","01-09-2024 13:01:32","01-09-2024 15:43=
:57","Grid fluctuation, site went down because gen failed to start due to g=
rid bad voltage // He bypass grid and manually start the gen","Fabrice Poua=
kam","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, site went down because gen failed to start due to gri=
d bad voltage // He bypass grid and manually start the gen","etienne.itondo=
@ihstowers.com","2287","01-09-2024 13:39:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0002972118","C=
harles-Atangana","IHS_YND_051","01-09-2024 13:34:34","01-09-2024 13:33:26",=
"01-09-2024 15:18:29","Grid outage // MDG 15Kva has deployed","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage // MD=
G 15Kva has deployed","ludivine.ngamaleu@ihstowers.com","69","01-09-2024 13=
:34:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_360","IHS_YND_373","NOCINC0002972073","M=
aloun","","01-09-2024 13:25:03","01-09-2024 13:01:52","01-09-2024 13:05:35"=
,"Active//no power issue on site ,site on Gen  with U=3D51.7 V The FME  TX =
Etienne /695033981 from Huawei is informed","Kemeni Franklin","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive//no power issue on site ,site on Gen  with U=3D51.7 V The FME  TX Eti=
enne /695033981 from Huawei is informed","etienne.itondo@ihstowers.com","13=
92","01-09-2024 13:25:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0002971932","Elig-Edz=
oa","","01-09-2024 13:02:59","01-09-2024 11:22:40","01-09-2024 11:41:53","g=
rid outage//grid return","","Grid Supply","Passive","Grid","National Grid -=
 Grid Outage Issue","grid outage//grid return","etienne.itondo@ihstowers.co=
m","6021","01-09-2024 13:02:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002971820","B=
iteng","","01-09-2024 12:46:02","01-09-2024 12:37:49","01-09-2024 12:43:19"=
,"Active: No power issue, site is on Grid with U=3D54,4V , The TX FME Lione=
l adjep//655184876// Huawei is informed","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue, site is on Grid with U=3D54,4V , The TX FME Lionel adj=
ep//655184876// Huawei is informed","ludivine.ngamaleu@ihstowers.com","494"=
,"01-09-2024 12:46:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0002971747","c=
hina embassy yde","","01-09-2024 12:29:37","01-09-2024 12:22:33","01-09-202=
4 13:52:38","No power issue on site U=3D54v site on grid Eloundou of huawei=
 is informed","","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue on site U=3D54v site on grid El=
oundou of huawei is informed","ludivine.ngamaleu@ihstowers.com","425","01-0=
9-2024 12:29:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0002971352","Messassi=
 Ngonlonk","","01-09-2024 10:59:10","01-09-2024 10:35:45","01-09-2024 12:05=
:13","Cascaded Incident from TTO2793841","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid outage,gen failed to s=
tart due to alarm overvoltage//he reset card and started the gen","system",=
"1405","01-09-2024 10:59:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0002971351","Akak-Nko=
zoa-MTN-IHS","","01-09-2024 10:59:10","01-09-2024 10:35:45","01-09-2024 12:=
05:13","Cascaded Incident from TTO2793841","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","grid outage,gen failed to=
 start due to alarm overvoltage//he reset card and started the gen","system=
","1405","01-09-2024 10:59:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0002971270","M=
essassi","IHS_YND_316, IHS_YND_799","01-09-2024 10:40:41","01-09-2024 10:32=
:36","01-09-2024 12:05:44","grid outage,gen failed to start due to alarm ov=
ervoltage//he reset card and started the gen","Fabrice Pouakam","Equipment =
Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage,gen failed=
 to start due to alarm overvoltage//he reset card and started the gen","lud=
ivine.ngamaleu@ihstowers.com","485","01-09-2024 10:40:41","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002971123","Bas=
tos Amb Coree","","01-09-2024 10:17:28","01-09-2024 10:10:10","01-09-2024 1=
5:42:41","Grid outage, No space to deploy a mobil gen // grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge, No space to deploy a mobil gen // grid return","olivier.kwedi@ihstowers=
.com","438","01-09-2024 10:17:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0002971028","Hotel de=
 Ville Yde","","01-09-2024 09:52:10","01-09-2024 09:47:22","01-09-2024 12:4=
9:05","Cascaded Incident from TTO2793475","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage//MDG 13kva deploye=
d","system","288","01-09-2024 09:52:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0002971026","N=
R-Bastos","IHS_YND_019","01-09-2024 09:51:27","01-09-2024 09:47:22","01-09-=
2024 12:49:05","grid outage//MDG 13kva deployed","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","grid outage//MDG 13kva deploye=
d","ludivine.ngamaleu@ihstowers.com","246","01-09-2024 09:51:27","Sagemcom =
CMR"
"Closed Complete","Warning","T0046","IHS_YND_191","NOCINC0002970909","Mball=
a II","","01-09-2024 09:15:20","","","Site was on Battery and Gen Failed to=
 start  because water infiltration in the tank// He purged the Gen, removed=
 water and start Gen manualy","Delor Telezing","Warning","Warning","POWER",=
"Warning - Site on Battery","Site was on Battery and Gen Failed to start  b=
ecause water infiltration in the tank// He purged the Gen, removed water an=
d start Gen manualy","dorothy.djantio@ihstowers.com","315","01-09-2024 09:1=
5:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0002970899","N=
yom OCM","","01-09-2024 09:13:38","01-09-2024 09:09:35","01-09-2024 09:49:3=
8","grid outage,gen failed to start due to alarm overload//he reset card an=
d started the gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen=
","ACDG - Control Panel","grid outage,gen failed to start due to alarm over=
load//he reset card and started the gen","ludivine.ngamaleu@ihstowers.com",=
"244","01-09-2024 09:13:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002970801","B=
ATA-Mokolo","","01-09-2024 08:56:14","01-09-2024 08:54:10","01-09-2024 09:5=
4:20","No power issue on site U=3D53v site on grid Brice Stague of huawei i=
s informed","","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","No power issue on site U=3D53v site on grid Bric=
e Stague of huawei is informed","ludivine.ngamaleu@ihstowers.com","125","01=
-09-2024 08:56:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_005","IHS_YND_374","NOCINC0002970552","M=
atomb","","01-09-2024 08:09:05","01-09-2024 08:04:58","01-09-2024 08:14:42"=
,"grid outage,gen ran till fuel shortage//refueling done","Kemeni Franklin"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran till=
 fuel shortage//refueling done","ludivine.ngamaleu@ihstowers.com","247","01=
-09-2024 08:09:05","Sagemcom CMR"
"Closed Complete","Warning","CTR_005","IHS_YND_374","NOCINC0002970533","Mat=
omb","","01-09-2024 08:02:47","","","site on battery due to low fuel//refue=
ling done","Kemeni Franklin","Warning","Warning","DIESEL","Warning - Low Fu=
el Level","site on battery due to low fuel//refueling done","dorothy.djanti=
o@ihstowers.com","434","01-09-2024 08:02:47","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002970448","Mim=
boman3","","01-09-2024 07:34:01","01-09-2024 07:26:47","01-09-2024 07:38:47=
","Grid outage, site went down before gen start due to poor battery backup =
//Gen started automatically","Mba Lazare Herve","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup //Gen started automatically",=
"olivier.kwedi@ihstowers.com","434","01-09-2024 07:34:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0002970093","E=
SSOS OASIS 1111","","01-09-2024 06:15:14","01-09-2024 06:11:11","01-09-2024=
 06:33:43","Active, no power issue, site on grid with U=3D54V, Armand Nguet=
sa /691144412/  From Huawei is informed","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
, no power issue, site on grid with U=3D54V, Armand Nguetsa /691144412/  Fr=
om Huawei is informed","ludivine.ngamaleu@ihstowers.com","243","01-09-2024 =
06:15:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002969828","E=
mana","","01-09-2024 04:16:10","01-09-2024 04:03:05","01-09-2024 06:53:37",=
"grid outage//MDG 20kva deployed","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","grid outage//MDG 20kva deployed","landry.etam=
e@ihstowers.com","786","01-09-2024 04:16:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0002969799","S=
apeur Mimboman","","01-09-2024 04:00:13","01-09-2024 03:52:08","01-09-2024 =
06:00:16","Grid outage, gen failed to start due to gen card faulty // gen m=
anually started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","Grid outage, gen failed to start due to gen card f=
aulty // gen manually started","landry.etame@ihstowers.com","486","01-09-20=
24 04:00:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0002969635","E=
SSOS OASIS 1111","","01-09-2024 02:36:59","01-09-2024 02:26:44","01-09-2024=
 04:10:06","Active, no power issue, site on grid with U=3D54V, Armand Nguet=
sa /691144412/  From Huawei is informed","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
, no power issue, site on grid with U=3D54V, Armand Nguetsa /691144412/  Fr=
om Huawei is informed","landry.etame@ihstowers.com","615","01-09-2024 02:36=
:59","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002969522","Tsi=
nga","","01-09-2024 01:33:44","01-09-2024 01:28:22","01-09-2024 01:50:18","=
Grid outage, site went down before gen start due to poor battery backup // =
Grid Restored","Mboua Thierry","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before gen star=
t due to poor battery backup // Grid Restored","kouoh.jean@ihstowers.com","=
323","01-09-2024 01:33:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_356","IHS_YND_376","NOCINC0002969507","M=
amb","","01-09-2024 01:25:23","01-09-2024 01:17:24","01-09-2024 02:29:50","=
site went down because the Cb (60A) Gen dysjoncted due to lightning // He r=
eamed the CB Gen","Kemeni Franklin","Force Majeure","Natural Disaster","Thu=
nderstrike","Equipment Damaged","site went down because the Cb (60A) Gen dy=
sjoncted due to lightning // He reamed the CB Gen","landry.etame@ihstowers.=
com","479","01-09-2024 01:25:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0002968921","Mbankolo=
 petit paris","","31-08-2024 22:34:10","31-08-2024 22:02:44","31-08-2024 23=
:22:23","Cascaded Incident from TTO2790951","Mboua Thierry","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","site went down because the=
 Grid contactor Dysfuntionning // He bypass the Grid contactor and site on =
Grid","system","1886","31-08-2024 22:34:10","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0002968882","AFE=
ME NORD","IHS_YND_808","31-08-2024 22:23:53","31-08-2024 22:02:44","31-08-2=
024 23:22:23","site went down because the Grid contactor Dysfuntionning // =
He bypass the Grid contactor and site on Grid","TIENTCHEU NZETCHIEU GAEL","=
Equipment Repair","Passive","Control Panel","ATS-AMF Issue","site went down=
 because the Grid contactor Dysfuntionning // He bypass the Grid contactor =
and site on Grid","kouoh.jean@ihstowers.com","1269","31-08-2024 22:23:53","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002968712","M=
imboman-Village","","31-08-2024 21:57:10","31-08-2024 21:55:01","31-08-2024=
 21:56:19","Active: no power issue on site ,site on GRid with U=3D54V Tx FM=
E Eloundou // 693212405 from HUAWEI is informed Notice that we have dysjunc=
tion at OCM equipements","Mba Lazare Herve","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power is=
sue on site ,site on GRid with U=3D54V Tx FME Eloundou // 693212405 from HU=
AWEI is informed Notice that we have dysjunction at OCM equipements","joell=
e.ekessi@ihstowers.com","129","31-08-2024 21:57:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002968532","ELOUMDEM=
 CARRIERE 2","","31-08-2024 21:05:20","31-08-2024 21:02:49","31-08-2024 21:=
05:58","Cascaded Incident from TTO2790535","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Main Gen faulty//Grid stabilized","system","151","31-08-2024 21=
:05:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002968531","Eto koss=
 Yde","","31-08-2024 21:05:20","31-08-2024 21:02:49","31-08-2024 21:05:58",=
"Cascaded Incident from TTO2790535","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Main Gen faulty//Grid stabilized","system","151","31-08-2024 21:05:20"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002968524","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","31-08-2024 21:03:55","31-08-2024 21:02=
:49","31-08-2024 21:05:58","Grid fluctuation, site went down because Main G=
en faulty//Grid stabilized","Fanda Brice","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Grid fluctuation, site went down b=
ecause Main Gen faulty//Grid stabilized","emmanuel.ghani@ihstowers.com","67=
","31-08-2024 21:03:55","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002968194","MAN=
GUIERS CHAPELLE","","31-08-2024 20:00:56","31-08-2024 19:57:32","31-08-2024=
 20:52:56","Site was on Gen due to Grid outage , site went down because Gen=
 stopped due to ""high temp"" alarm //He added water and gen manually start=
ed","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High =
Engine Temp - Coolant Level Issue","Site was on Gen due to Grid outage , si=
te went down because Gen stopped due to ""high temp"" alarm //He added wate=
r and gen manually started","emmanuel.ghani@ihstowers.com","313","31-08-202=
4 20:00:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_625","IHS_YND_181","NOCINC0002967962","M=
imboman3","","31-08-2024 19:14:45","31-08-2024 19:09:40","31-08-2024 20:03:=
20","Grid  fluctuation, site went down because Gen failed to start due to b=
ad voltage// Grid stabilized","Mba Lazare Herve","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","Grid  fluctuation, site wen=
t down because Gen failed to start due to bad voltage// Grid stabilized","j=
oelle.ekessi@ihstowers.com","305","31-08-2024 19:14:45","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002967689","Nko=
abang Ebolmedjock","","31-08-2024 18:20:55","31-08-2024 18:19:49","31-08-20=
24 18:22:41","Poor Batteries, site went down during the work Mba Herve /657=
108482/Sagemcom/doing draining // End of work","Mba Lazare Herve","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Poor Bat=
teries, site went down during the work Mba Herve /657108482/Sagemcom/doing =
draining // End of work","emmanuel.ghani@ihstowers.com","66","31-08-2024 18=
:20:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002967618","Eto koss=
 Yde","","31-08-2024 18:00:10","31-08-2024 17:57:58","31-08-2024 18:03:37",=
"Cascaded Incident from TTO2789467","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Main Gen faulty//Grid stabilized","system","132","31-08-2024 18:00:10"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002967619","ELOUMDEM=
 CARRIERE 2","","31-08-2024 18:00:10","31-08-2024 17:57:58","31-08-2024 18:=
03:37","Cascaded Incident from TTO2789467","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Main Gen faulty//Grid stabilized","system","132","31-08-2024 18=
:00:10","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002967615","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","31-08-2024 17:59:02","31-08-2024 17:57=
:58","31-08-2024 18:03:37","Grid fluctuation, site went down because Main G=
en faulty//Grid stabilized","Fanda Brice","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Grid fluctuation, site went down b=
ecause Main Gen faulty//Grid stabilized","emmanuel.ghani@ihstowers.com","65=
","31-08-2024 17:59:02","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002967388","Mim=
boman3","","31-08-2024 17:19:41","31-08-2024 17:18:15","31-08-2024 17:30:49=
","Grid outage, site went down before Gen start due to poor battery backup =
// grid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before Gen =
start due to poor battery backup // grid return","emmanuel.ghani@ihstowers.=
com","86","31-08-2024 17:19:41","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002967381","Lad=
a I Yde","","31-08-2024 17:18:26","31-08-2024 17:16:08","31-08-2024 17:42:1=
1","Poor Batteries, site went down during the work Mba Herve /657108482/Sag=
emcom/PM work // End of work","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Poor Batteries, site went=
 down during the work Mba Herve /657108482/Sagemcom/PM work // End of work"=
,"emmanuel.ghani@ihstowers.com","138","31-08-2024 17:18:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0002967380","A=
FEME NORD","","31-08-2024 17:17:54","31-08-2024 17:13:50","31-08-2024 17:15=
:40","Active// No power issue on site U=3D53,7v site on gen Team Erick/6964=
22966/ZTE working on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// =
No power issue on site U=3D53,7v site on gen Team Erick/696422966/ZTE worki=
ng on site","joelle.ekessi@ihstowers.com","245","31-08-2024 17:17:54","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002967280","O=
lembe-Terminus","","31-08-2024 17:00:33","31-08-2024 16:56:27","31-08-2024 =
19:06:15","Site went down because rectifier slot disfunctionned// He reset =
slot rectifier","Fabrice Pouakam","Equipment Repair","Passive","Rectifier",=
"Rectifier Distribution","Site went down because rectifier slot disfunction=
ned// He reset slot rectifier","joelle.ekessi@ihstowers.com","247","31-08-2=
024 17:00:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0002967250","Dagobert=
","","31-08-2024 16:52:00","31-08-2024 15:50:02","31-08-2024 16:47:28","Cas=
caded Incident from TTO2788669","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active// No power issue on sit=
e U=3D53,4v site on gen Team Erick/696422966/ZTE working on site","system",=
"3718","31-08-2024 16:52:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0002967249","Yona Hot=
el","","31-08-2024 16:52:00","31-08-2024 15:50:02","31-08-2024 16:47:28","C=
ascaded Incident from TTO2788669","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active// No power issue on s=
ite U=3D53,4v site on gen Team Erick/696422966/ZTE working on site","system=
","3718","31-08-2024 16:52:00","Sagemcom CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0002967097","ETO=
UDI CHAPELLE","","31-08-2024 16:19:43","31-08-2024 16:17:23","31-08-2024 16=
:21:38","Grid outage, site went down because gen failded to start due to ba=
ttery Ge faulty // gen manually started with external battery","Delor Telez=
ing","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Gr=
id outage, site went down because gen failded to start due to battery Ge fa=
ulty // gen manually started with external battery","emmanuel.ghani@ihstowe=
rs.com","141","31-08-2024 16:19:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0002966986","M=
volye-New","","31-08-2024 16:04:32","31-08-2024 15:59:27","31-08-2024 16:17=
:45","Grid outage//Grid power return","","Grid Supply","Passive","Grid","Na=
tional Grid - Grid Outage Issue","Grid outage//Grid power return","joelle.e=
kessi@ihstowers.com","306","31-08-2024 16:04:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0002966926","N=
kolbi-Boss","IHS_YND_271, IHS_YND_286","31-08-2024 15:53:07","31-08-2024 15=
:50:02","31-08-2024 16:47:28","Active// No power issue on site U=3D53,4v si=
te on gen Team Erick/696422966/ZTE working on site","TIENTCHEU NZETCHIEU GA=
EL","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// No power issue on site U=3D53,4v site on gen Team =
Erick/696422966/ZTE working on site","joelle.ekessi@ihstowers.com","185","3=
1-08-2024 15:53:07","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002966694","Pha=
rmacie SION","","31-08-2024 15:00:16","31-08-2024 14:56:09","31-08-2024 15:=
07:40","Grid outage site went down before Gen started due to poor battery b=
ack up // Gen started automatically","Paul BIBOUM","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage site went d=
own before Gen started due to poor battery back up // Gen started automatic=
ally","emmanuel.ghani@ihstowers.com","248","31-08-2024 15:00:16","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0002966604","B=
ISCUITERIE","","31-08-2024 14:44:35","31-08-2024 14:41:31","31-08-2024 14:4=
5:57","Grid outage, site went down before gen start due to poor battery bac=
kup // grid return","Paul BIBOUM","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, site went down before gen s=
tart due to poor battery backup // grid return","joelle.ekessi@ihstowers.co=
m","185","31-08-2024 14:44:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0002966579","M=
volye-New","","31-08-2024 14:42:28","31-08-2024 14:39:19","31-08-2024 15:07=
:47","Grid Outage//Grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","Grid Outage//Grid return","joelle.ekessi@ihstow=
ers.com","190","31-08-2024 14:42:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0002966395","E=
ntree Cite Verte","","31-08-2024 14:31:34","31-08-2024 14:21:29","31-08-202=
4 15:51:02","site Went down because CB OCM  (80A) is burned in PWC// He mak=
e a bridge with  CB( 2*80A) ,Site on Grid","Paul BIBOUM","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site We=
nt down because CB OCM  (80A) is burned in PWC// He make a bridge with  CB(=
 2*80A) ,Site on Grid","joelle.ekessi@ihstowers.com","606","31-08-2024 14:3=
1:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002966361","E=
lig-Edzoa","","31-08-2024 14:26:45","31-08-2024 13:56:36","31-08-2024 14:31=
:16","Grid Outage// MDG 20kva  has deployed","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid Outage// MDG 20kva  has deplo=
yed","adonis.defokoua@ihstowers.com","1810","31-08-2024 14:26:45","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002966185","B=
ATA-Mokolo","","31-08-2024 14:04:28","31-08-2024 14:01:15","31-08-2024 15:3=
1:09","site went down because insufficiency of rectifiers due to increase l=
oad// site Stabilized(Rectifiers to be replaced)","","Equipment Repair","Pa=
ssive","Rectifier","Rectifier Module","site went down because insufficiency=
 of rectifiers due to increase load// site Stabilized(Rectifiers to be repl=
aced)","adonis.defokoua@ihstowers.com","194","31-08-2024 14:04:28","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0002966030","A=
wae Ewonkan","","31-08-2024 13:28:01","31-08-2024 13:20:57","31-08-2024 14:=
21:15","Site went down because 02/05 rectifiers hanging  causing by  Grid b=
ad voltage//He reset rectifiers and He make the bridge on good phase","Albr=
an Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","Sit=
e went down because 02/05 rectifiers hanging  causing by  Grid bad voltage/=
/He reset rectifiers and He make the bridge on good phase","adonis.defokoua=
@ihstowers.com","424","31-08-2024 13:28:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0002966011","C=
rf-Nkolbisson","","31-08-2024 13:24:20","31-08-2024 13:10:16","31-08-2024 1=
3:50:21","No power issue on site U=3D54v site on gen Team Erick/696422966/Z=
TE working on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D54v site on gen Team Erick/696422966/ZTE working on site","adoni=
s.defokoua@ihstowers.com","845","31-08-2024 13:24:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0002966009","B=
astos Bir","","31-08-2024 13:23:38","31-08-2024 12:51:31","31-08-2024 14:33=
:47","grid outagee,gen failed to start due to alarm overccurrent//he reduic=
e the load on site","Mboua Thierry","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Control Panel","grid outagee,gen failed to start due to alarm over=
ccurrent//he reduice the load on site","adonis.defokoua@ihstowers.com","192=
8","31-08-2024 13:23:38","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002965977","Pha=
rmacie SION","","31-08-2024 13:17:33","31-08-2024 13:13:28","31-08-2024 13:=
23:36","Grid outage, site went down before gen start due to poor battery ba=
ckup //Grid return","Paul BIBOUM","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, site went down before gen s=
tart due to poor battery backup //Grid return","ange.kongo@ihstowers.com","=
246","31-08-2024 13:17:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002965948","E=
mana","","31-08-2024 13:10:30","31-08-2024 12:34:17","31-08-2024 13:44:57",=
"grid outage//MDG 20kva deployed","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","grid outage//MDG 20kva deployed","adonis.defo=
koua@ihstowers.com","2174","31-08-2024 13:10:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_507","NOCINC0002965816","BIYEM AS=
SI LYCEE","","31-08-2024 12:49:01","31-08-2024 12:39:06","31-08-2024 13:26:=
41","Cascaded Incident from TTO2787352","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
efore gen start due to poor battery backup //Gen started manually","system"=
,"595","31-08-2024 12:49:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0002965817","BIYEMASS=
I NIKI","","31-08-2024 12:49:01","31-08-2024 12:39:06","31-08-2024 13:26:41=
","Cascaded Incident from TTO2787352","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup //Gen started manually","system","=
595","31-08-2024 12:49:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0002965813","Biyemass=
i LAC","","31-08-2024 12:49:01","31-08-2024 12:39:06","31-08-2024 13:26:41"=
,"Cascaded Incident from TTO2787352","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage, site went down before gen start d=
ue to poor battery backup //Gen started manually","system","595","31-08-202=
4 12:49:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0002965815","Behind P=
 T school Yde","","31-08-2024 12:49:01","31-08-2024 12:39:06","31-08-2024 1=
3:26:41","Cascaded Incident from TTO2787352","Paul BIBOUM","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup //Gen started manually","syste=
m","595","31-08-2024 12:49:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0002965814","BONAS YD=
E","","31-08-2024 12:49:01","31-08-2024 12:39:06","31-08-2024 13:26:41","Ca=
scaded Incident from TTO2787352","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down before gen =
start due to poor battery backup //Gen started manually","system","595","31=
-08-2024 12:49:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0002965811","Ngoa Eke=
lle","","31-08-2024 12:49:00","31-08-2024 12:39:06","31-08-2024 13:26:41","=
Cascaded Incident from TTO2787352","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down before ge=
n start due to poor battery backup //Gen started manually","system","594","=
31-08-2024 12:49:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0002965809","Scalom",=
"","31-08-2024 12:49:00","31-08-2024 12:39:06","31-08-2024 13:26:41","Casca=
ded Incident from TTO2787352","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, site went down before gen sta=
rt due to poor battery backup //Gen started manually","system","594","31-08=
-2024 12:49:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0002965810","Obili Ch=
apelle","","31-08-2024 12:49:00","31-08-2024 12:39:06","31-08-2024 13:26:41=
","Cascaded Incident from TTO2787352","Paul BIBOUM","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 gen start due to poor battery backup //Gen started manually","system","594=
","31-08-2024 12:49:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0002965812","Accacia =
New","","31-08-2024 12:49:00","31-08-2024 12:39:06","31-08-2024 13:26:41","=
Cascaded Incident from TTO2787352","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage, site went down before gen start due=
 to poor battery backup //Gen started manually","system","594","31-08-2024 =
12:49:00","Sagemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0002965777","Nlo=
ng Mvolye New","IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND_562, IHS_YND=
_546, IHS_YND_683, IHS_YND_805, IHS_YND_507, IHS_YND_724","31-08-2024 12:44=
:11","31-08-2024 12:39:06","31-08-2024 13:26:41","Grid outage, site went do=
wn before gen start due to poor battery backup //Gen started manually","Pau=
l BIBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet - Bat=
tery Low","Grid outage, site went down before gen start due to poor battery=
 backup //Gen started manually","ange.kongo@ihstowers.com","306","31-08-202=
4 12:44:11","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0002965419","Feb=
e Village","","31-08-2024 12:18:13","31-08-2024 12:09:42","31-08-2024 13:01=
:07","grid outage,gen stopped with alarm high temp//he added water in radia=
tor","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high =
temp//he added water in radiator","ange.kongo@ihstowers.com","1388","31-08-=
2024 12:18:13","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0002965401","Nko=
lbisson IITA LP","","31-08-2024 12:15:38","31-08-2024 12:03:23","31-08-2024=
 12:41:05","grid outage,no space to deploy a mobil gen//grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outag=
e,no space to deploy a mobil gen//grid return","ange.kongo@ihstowers.com","=
735","31-08-2024 12:15:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0002965302","M=
aison-Blanche-IHS","","31-08-2024 12:07:31","31-08-2024 11:17:25","31-08-20=
24 11:20:09","Active// No power Issue Site on Grid Ubai =3D56V, The FME Tx =
The TX FME Mbah Hosiah (674007438) is informed, Notice that we have disjunc=
tion at BTS OCM","","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active// No power Issue Site on Grid Ubai =
=3D56V, The FME Tx The TX FME Mbah Hosiah (674007438) is informed, Notice t=
hat we have disjunction at BTS OCM","adonis.defokoua@ihstowers.com","3006",=
"31-08-2024 12:07:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0002965297","M=
ini-Ferme","","31-08-2024 12:05:28","31-08-2024 11:15:19","31-08-2024 12:44=
:36","grid outage,no space to deploy a mobil gen//grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no s=
pace to deploy a mobil gen//grid return","adonis.defokoua@ihstowers.com","3=
010","31-08-2024 12:05:28","Sagemcom CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0002965162","Efo=
ulan MTN","","31-08-2024 11:35:22","31-08-2024 11:32:17","31-08-2024 11:42:=
21","site went down due to insufficient  rectifier on site//site stabilized=
","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","site went down due to insufficient  rectifier on site//site stabilized"=
,"ange.kongo@ihstowers.com","186","31-08-2024 11:35:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0002964973","N=
kolso","","31-08-2024 11:08:10","31-08-2024 10:40:03","31-08-2024 13:25:57"=
,"No power issue on site U=3D54,9v site on gen Team Erick/696422966/ZTE wor=
king on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 U=3D54,9v site on gen Team Erick/696422966/ZTE working on site","adonis.de=
fokoua@ihstowers.com","1688","31-08-2024 11:08:10","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0002964960","An-=
Marche-Melen","","31-08-2024 11:05:57","31-08-2024 11:01:33","31-08-2024 12=
:42:58","grid outage,no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,n=
o space to deploy a mobil gen//grid return","ange.kongo@ihstowers.com","373=
2","31-08-2024 11:05:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_803","NOCINC0002964899","Etoug eb=
e biscuiterie","","31-08-2024 10:52:10","31-08-2024 10:42:59","31-08-2024 1=
2:38:31","grid outage,gen failed to start due to battery Ge faulty//he star=
ted the gen with battery backup","Hyemafo Gildas","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Generator Battery","grid outage,gen failed to start =
due to battery Ge faulty//he started the gen with battery backup","ange.kon=
go@ihstowers.com","551","31-08-2024 10:52:10","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002964731","N=
KOMEKUI OCM","IHS_YND_341","31-08-2024 10:42:52","31-08-2024 09:22:45","31-=
08-2024 09:28:45","Grid outage, site went down before gen start due to poor=
 battery backup // Gen started","TIENTCHEU NZETCHIEU GAEL","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, si=
te went down before gen start due to poor battery backup // Gen started","a=
donis.defokoua@ihstowers.com","4807","31-08-2024 10:42:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002964711","E=
lig-Edzoa","","31-08-2024 10:39:56","31-08-2024 09:47:48","31-08-2024 11:44=
:11","grid outage//grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","grid outage//grid return","adonis.defokoua@ihst=
owers.com","3129","31-08-2024 10:39:56","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0002964671","Fla=
menco","","31-08-2024 10:33:42","31-08-2024 10:28:35","31-08-2024 11:42:56"=
,"grid outage,gen failed to start due to card Ge faulty//gen manually start=
ed","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control=
 Panel","grid outage,gen failed to start due to card Ge faulty//gen manuall=
y started","ange.kongo@ihstowers.com","307","31-08-2024 10:33:42","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0002964627","Nta=
ba","","31-08-2024 10:26:43","31-08-2024 09:38:29","31-08-2024 09:44:29","G=
rid outage, site went down before gen start due to poor battery backup // G=
rid Restored","Delor Telezing","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before gen star=
t due to poor battery backup // Grid Restored","ange.kongo@ihstowers.com","=
2895","31-08-2024 10:26:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0002964603","Accacia =
New","","31-08-2024 10:24:01","31-08-2024 09:25:53","31-08-2024 09:35:01","=
Cascaded Incident from TTO2785643","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","Grid outage, site down because Gen failed due to=
 poor backup before gen start//Gen started automatically","system","3488","=
31-08-2024 10:24:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0002964602","BIYEMASS=
I NIKI","","31-08-2024 10:23:40","31-08-2024 09:25:53","31-08-2024 09:35:01=
","Cascaded Incident from TTO2785643","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site down because =
Gen failed due to poor backup before gen start//Gen started automatically",=
"system","3467","31-08-2024 10:23:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0002964601","Behind P=
 T school Yde","","31-08-2024 10:23:40","31-08-2024 09:25:53","31-08-2024 0=
9:35:01","Cascaded Incident from TTO2785643","Paul BIBOUM","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site down beca=
use Gen failed due to poor backup before gen start//Gen started automatical=
ly","system","3467","31-08-2024 10:23:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0002964598","Scalom",=
"","31-08-2024 10:23:40","31-08-2024 09:25:53","31-08-2024 09:35:01","Casca=
ded Incident from TTO2785643","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid outage, site down because Gen failed =
due to poor backup before gen start//Gen started automatically","system","3=
467","31-08-2024 10:23:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0002964599","Biyemass=
i LAC","","31-08-2024 10:23:40","31-08-2024 09:25:53","31-08-2024 09:35:01"=
,"Cascaded Incident from TTO2785643","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage, site down because Gen failed due =
to poor backup before gen start//Gen started automatically","system","3467"=
,"31-08-2024 10:23:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0002964600","BONAS YD=
E","","31-08-2024 10:23:40","31-08-2024 09:25:53","31-08-2024 09:35:01","Ca=
scaded Incident from TTO2785643","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site down because Gen fail=
ed due to poor backup before gen start//Gen started automatically","system"=
,"3467","31-08-2024 10:23:40","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002964484","Man=
guiers Dispensaire","","31-08-2024 10:08:38","31-08-2024 10:00:29","31-08-2=
024 10:38:59","grid outage gen failed to start due to contactor Ge faulty//=
grid return(remplacement ongoing)","Fabrice Pouakam","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","grid outage gen failed to start due=
 to contactor Ge faulty//grid return(remplacement ongoing)","ange.kongo@ihs=
towers.com","490","31-08-2024 10:08:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_149","NOCINC0002964477","Nsimeyon=
g Terre Rouge","","31-08-2024 10:06:31","31-08-2024 09:58:23","31-08-2024 1=
0:57:37","grid outage,gen failed to start due to alarm""failed to start""//=
he reset card and started it","MINKA NICOLAS","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","grid outage,gen failed to start due to a=
larm""failed to start""//he reset card and started it","ange.kongo@ihstower=
s.com","489","31-08-2024 10:06:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0002964340","B=
astos Ekoudou","","31-08-2024 09:47:56","31-08-2024 09:25:24","31-08-2024 1=
2:10:24","grid outage,gen stopped with alarm high temp//he added water in r=
adiator","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Hi=
gh Engine Temp - Coolant Level Issue","grid outage,gen stopped with alarm h=
igh temp//he added water in radiator","adonis.defokoua@ihstowers.com","1392=
","31-08-2024 09:47:56","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002964324","Nsi=
meyong Shell","","31-08-2024 09:47:05","31-08-2024 09:25:38","31-08-2024 10=
:45:51","grid outage gen failed to start due to charger static faulty//he c=
hanged it and started the gen","MINKA NICOLAS","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Turbo Charger","grid outage gen failed to start due to =
charger static faulty//he changed it and started the gen","ange.kongo@ihsto=
wers.com","1287","31-08-2024 09:47:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0002964308","S=
hell-Nsimeyong","","31-08-2024 09:45:30","31-08-2024 09:25:25","31-08-2024 =
10:45:09","grid outage gen failed to start due to charger static faulty//he=
 changed it and started the gen","MINKA NICOLAS","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Turbo Charger","grid outage gen failed to start due t=
o charger static faulty//he changed it and started the gen","adonis.defokou=
a@ihstowers.com","1206","31-08-2024 09:45:30","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0002964306","Nko=
mkana","","31-08-2024 09:44:56","31-08-2024 09:34:12","31-08-2024 12:40:51"=
,"grid outage,no space to deploy a mobil gen//grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","grid outage,no space=
 to deploy a mobil gen//grid return","ange.kongo@ihstowers.com","1028","31-=
08-2024 09:44:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0002964284","Obili Ch=
apelle","","31-08-2024 09:39:41","31-08-2024 09:25:53","31-08-2024 09:35:01=
","Cascaded Incident from TTO2785643","Paul BIBOUM","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site down because Gen=
 failed due to poor backup before gen start//Gen started automatically","sy=
stem","828","31-08-2024 09:39:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_507","NOCINC0002964286","BIYEM AS=
SI LYCEE","","31-08-2024 09:39:41","31-08-2024 09:25:53","31-08-2024 09:35:=
01","Cascaded Incident from TTO2785643","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site down becaus=
e Gen failed due to poor backup before gen start//Gen started automatically=
","system","828","31-08-2024 09:39:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0002964285","Ngoa Eke=
lle","","31-08-2024 09:39:41","31-08-2024 09:25:53","31-08-2024 09:35:01","=
Cascaded Incident from TTO2785643","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site down because Gen fa=
iled due to poor backup before gen start//Gen started automatically","syste=
m","828","31-08-2024 09:39:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_727","NOCINC0002964271","Nlong Mv=
olye New","IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND_562, IHS_YND_546,=
 IHS_YND_683, IHS_YND_805, IHS_YND_507, IHS_YND_724","31-08-2024 09:36:00",=
"31-08-2024 09:25:53","31-08-2024 09:35:01","Grid outage, site down because=
 Gen failed due to poor backup before gen start//Gen started automatically"=
,"Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Battery Low","Grid outage, site down because Gen failed due to poor backu=
p before gen start//Gen started automatically","ange.kongo@ihstowers.com","=
607","31-08-2024 09:36:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0002964240","L=
obo OCM","","31-08-2024 09:29:05","31-08-2024 09:22:45","31-08-2024 09:28:4=
5","SITE IMPACTED BY TTO2786173 NKOMEKUI OCM.","TIENTCHEU NZETCHIEU GAEL","=
Cascade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage,=
 site went down before gen start due to poor battery backup // Gen started"=
,"adonis.defokoua@ihstowers.com","4895","31-08-2024 09:29:05","Sagemcom CMR=
"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002964128","MAN=
GUIERS CHAPELLE","","31-08-2024 09:02:48","31-08-2024 09:00:37","31-08-2024=
 09:12:49","Grid outage, site went down before gen start due to poor batter=
y backup // Gen started automatically","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // Gen started autom=
atically","ange.kongo@ihstowers.com","132","31-08-2024 09:02:48","Sagemcom =
CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002963785","NKO=
MEKUI OCM","","31-08-2024 07:58:15","31-08-2024 07:50:08","31-08-2024 08:00=
:16","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // Gen start automat=
icaly","ange.kongo@ihstowers.com","488","31-08-2024 07:58:15","Sagemcom CMR=
"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002963745","Jou=
vence 2000","","31-08-2024 07:44:42","31-08-2024 07:42:36","31-08-2024 09:0=
5:16","Grid outage, site down because Gen failed due to poor backup before =
gen start//Gen started manually","Delor Telezing","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site down b=
ecause Gen failed due to poor backup before gen start//Gen started manually=
","ange.kongo@ihstowers.com","127","31-08-2024 07:44:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0002963732","B=
yemassi Carrefour","","31-08-2024 07:39:51","31-08-2024 07:30:44","31-08-20=
24 12:19:35","site went down because CB 125A disjuncted in Pwc causing by l=
oad increase//he put the second depart with power cable 48V in Pwc","Paul B=
IBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet - Circui=
t Breaker Issue","site went down because CB 125A disjuncted in Pwc causing =
by load increase//he put the second depart with power cable 48V in Pwc","ad=
onis.defokoua@ihstowers.com","548","31-08-2024 07:39:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0002963709","A=
KONGO","","31-08-2024 07:35:00","31-08-2024 07:29:55","31-08-2024 07:53:34"=
,"No power issue on site U=3D50v site on gen Rodrigue 655102999 of huawei i=
s informed","Fanda Brice","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D50v site o=
n gen Rodrigue 655102999 of huawei is informed","adonis.defokoua@ihstowers.=
com","307","31-08-2024 07:35:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0002963286","Bondjock=
","","31-08-2024 05:45:11","31-08-2024 04:10:09","31-08-2024 04:15:30","Cas=
caded Incident from TTO2784483","Fanda Brice","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue site on Gen ubaie=3D54.5v si=
te impacted by ngoumou-camrail","system","5702","31-08-2024 05:45:11","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_371","NOCINC0002963284","Minka","=
","31-08-2024 05:45:11","31-08-2024 04:10:09","31-08-2024 04:15:30","Cascad=
ed Incident from TTO2784483","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on Gen ubaie=3D54.5v site =
impacted by ngoumou-camrail","system","5702","31-08-2024 05:45:11","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_370","NOCINC0002963282","Mom","",=
"31-08-2024 05:45:10","31-08-2024 04:10:09","31-08-2024 04:15:30","Cascaded=
 Incident from TTO2784483","Fanda Brice","Cascade Outage","Active","Cascade=
 Active","Cascade Active","No power issue site on Gen ubaie=3D54.5v site im=
pacted by ngoumou-camrail","system","5701","31-08-2024 05:45:10","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_368","NOCINC0002963283","Otele","=
","31-08-2024 05:45:10","31-08-2024 04:10:09","31-08-2024 04:15:30","Cascad=
ed Incident from TTO2784483","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on Gen ubaie=3D54.5v site =
impacted by ngoumou-camrail","system","5701","31-08-2024 05:45:10","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0002963274","M=
beng","IHS_YND_370, IHS_YND_368, IHS_YND_371, IHS_YND_553, IHS_YND_451, IHS=
_YND_372","31-08-2024 05:43:21","31-08-2024 04:10:09","31-08-2024 04:15:30"=
,"No power issue site on Gen ubaie=3D54.5v site impacted by ngoumou-camrail=
","Fanda Brice","Customer Equipment Failure","Active","Active Equipment Fai=
lure","Affected by 3rd Party Site","No power issue site on Gen ubaie=3D54.5=
v site impacted by ngoumou-camrail","alexandre.kamal@ihstowers.com","5592",=
"31-08-2024 05:43:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_532","NOCINC0002962811","NKOLOSSA=
N OKOK","","31-08-2024 03:01:41","31-08-2024 02:45:50","31-08-2024 02:50:13=
","Cascaded Incident from TTO2783948","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","ACTIVE// No power issue: Ubaie=3D55=
,1V site on Grid The Tx Fme Gregoire( 652070658)from Huawei is informed","s=
ystem","951","31-08-2024 03:01:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_670","NOCINC0002962812","BOBOCK",=
"","31-08-2024 03:01:41","31-08-2024 02:45:50","31-08-2024 02:50:13","Casca=
ded Incident from TTO2783948","Kemeni Franklin","Cascade Outage","Active","=
Cascade Active","Cascade Active","ACTIVE// No power issue: Ubaie=3D55,1V si=
te on Grid The Tx Fme Gregoire( 652070658)from Huawei is informed","system"=
,"951","31-08-2024 03:01:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_102","NOCINC0002962807","NYANON/D=
EMBO","","31-08-2024 03:01:40","31-08-2024 02:45:50","31-08-2024 02:50:13",=
"Cascaded Incident from TTO2783948","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","ACTIVE// No power issue: U=
baie=3D55,1V site on Grid The Tx Fme Gregoire( 652070658)from Huawei is inf=
ormed","system","950","31-08-2024 03:01:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_408","NOCINC0002962808","Evodoula=
 MTN","","31-08-2024 03:01:40","31-08-2024 02:45:50","31-08-2024 02:50:13",=
"Cascaded Incident from TTO2783948","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","ACTIVE// No power issue: U=
baie=3D55,1V site on Grid The Tx Fme Gregoire( 652070658)from Huawei is inf=
ormed","system","950","31-08-2024 03:01:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_052","NOCINC0002962810","Nyahoo",=
"","31-08-2024 03:01:40","31-08-2024 02:45:50","31-08-2024 02:50:13","Casca=
ded Incident from TTO2783948","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Active","Cascade Active","Cascade Active","ACTIVE// No power issue: Ubaie=
=3D55,1V site on Grid The Tx Fme Gregoire( 652070658)from Huawei is informe=
d","system","950","31-08-2024 03:01:40","Sagemcom CMR"
"Closed Complete","Site Down","T0573","IHS_YND_387","NOCINC0002962788","Tal=
la Monatele","IHS_EDA_102, IHS_YND_408, IHS_EDA_049, IHS_EDA_052, IHS_YND_5=
32, IHS_YND_670","31-08-2024 02:57:56","31-08-2024 02:45:50","31-08-2024 02=
:50:13","ACTIVE// No power issue: Ubaie=3D55,1V site on Grid The Tx Fme Gre=
goire( 652070658)from Huawei is informed","Parker Tchoup","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIV=
E// No power issue: Ubaie=3D55,1V site on Grid The Tx Fme Gregoire( 6520706=
58)from Huawei is informed","stephane.nkamwa@ihstowers.com","726","31-08-20=
24 02:57:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0002962125","B=
yemassi Carrefour","","30-08-2024 23:18:38","30-08-2024 21:55:33","31-08-20=
24 00:34:09","Site went down because the Cb(125A) of PWC dysjuncted due to =
load increased on site // He reamed CB","Paul BIBOUM","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went =
down because the Cb(125A) of PWC dysjuncted due to load increased on site /=
/ He reamed CB","alexandre.kamal@ihstowers.com","4985","30-08-2024 23:18:38=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002961260","ELOUMDEM=
 CARRIERE 2","","30-08-2024 20:55:10","30-08-2024 20:48:51","30-08-2024 20:=
54:51","Cascaded Incident from TTO2782200","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation, site went d=
own because Main Gen faulty//Grid stabilized","system","379","30-08-2024 20=
:55:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002961259","Eto koss=
 Yde","","30-08-2024 20:55:10","30-08-2024 20:48:51","30-08-2024 20:54:51",=
"Cascaded Incident from TTO2782200","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation, site went down bec=
ause Main Gen faulty//Grid stabilized","system","379","30-08-2024 20:55:10"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002961255","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","30-08-2024 20:54:00","30-08-2024 20:48=
:51","30-08-2024 20:54:51","Grid fluctuation, site went down because Main G=
en faulty//Grid stabilized","Fanda Brice","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Grid fluctuation, site went down b=
ecause Main Gen faulty//Grid stabilized","kouoh.jean@ihstowers.com","310","=
30-08-2024 20:54:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0002961082","B=
yemassi Carrefour","","30-08-2024 20:35:20","30-08-2024 19:54:11","30-08-20=
24 21:38:40","Site went down because the Cb(125A) of PWC dysjuncted due to =
load increased on site // He reamed CB","Paul BIBOUM","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went =
down because the Cb(125A) of PWC dysjuncted due to load increased on site /=
/ He reamed CB","landry.etame@ihstowers.com","2469","30-08-2024 20:35:20","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002960674","MBIMBIM"=
,"","30-08-2024 19:05:51","30-08-2024 18:49:25","30-08-2024 18:50:10","Casc=
aded Incident from TTO2781502","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Our FME Felix 691145560 / 677002977 / IENG=
 is informed and reverts No Power issue on site, Site is on battery; Ubaie =
=3D 48.6V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","986","30-08-2024 19:05:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002960672","Ngouetou=
","","30-08-2024 19:05:51","30-08-2024 18:49:25","30-08-2024 18:50:10","Cas=
caded Incident from TTO2781502","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Our FME Felix 691145560 / 677002977 / IEN=
G is informed and reverts No Power issue on site, Site is on battery; Ubaie=
 =3D 48.6V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","s=
ystem","986","30-08-2024 19:05:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002960671","Yoko OCM=
","","30-08-2024 19:05:51","30-08-2024 18:49:25","30-08-2024 18:50:10","Cas=
caded Incident from TTO2781502","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Our FME Felix 691145560 / 677002977 / IEN=
G is informed and reverts No Power issue on site, Site is on battery; Ubaie=
 =3D 48.6V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","s=
ystem","986","30-08-2024 19:05:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002960669","Ngoum","=
","30-08-2024 19:05:50","30-08-2024 18:49:25","30-08-2024 18:50:10","Cascad=
ed Incident from TTO2781502","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Our FME Felix 691145560 / 677002977 / IENG i=
s informed and reverts No Power issue on site, Site is on battery; Ubaie =
=3D 48.6V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","985","30-08-2024 19:05:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002960670","Matsari"=
,"","30-08-2024 19:05:50","30-08-2024 18:49:25","30-08-2024 18:50:10","Casc=
aded Incident from TTO2781502","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Our FME Felix 691145560 / 677002977 / IENG=
 is informed and reverts No Power issue on site, Site is on battery; Ubaie =
=3D 48.6V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","sy=
stem","985","30-08-2024 19:05:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0002960558","H=
-Progres","","30-08-2024 18:44:44","30-08-2024 18:34:37","30-08-2024 18:44:=
09","Grid outage No space to deployed a mobile Gen// Grid power return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage No space to deployed a mobile Gen// Grid power return","landry.etame@i=
hstowers.com","608","30-08-2024 18:44:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002960361","B=
ATA-Mokolo","","30-08-2024 18:10:46","30-08-2024 18:04:40","30-08-2024 18:4=
6:33","Site went down due to Insufficient of rectifier on site (02/03)// Si=
te stabilized","","Equipment Repair","Passive","Rectifier","Rectifier Modul=
e","Site went down due to Insufficient of rectifier on site (02/03)// Site =
stabilized","landry.etame@ihstowers.com","366","30-08-2024 18:10:46","Sagem=
com CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0002959793","Av =
Kennedy","","30-08-2024 16:38:13","30-08-2024 16:28:59","30-08-2024 16:44:5=
9","Grid outage No Space to deploy a MDG//Grid Restored","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage No Space t=
o deploy a MDG//Grid Restored","kouoh.jean@ihstowers.com","554","30-08-2024=
 16:38:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0002959786","M=
vog Mbi New","","30-08-2024 16:37:36","30-08-2024 16:21:30","30-08-2024 16:=
25:01","Site went down due to insufficient of rectifier on site (03/04)// S=
ite stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to insufficient of rectifier on site (=
03/04)// Site stabilized","landry.etame@ihstowers.com","967","30-08-2024 16=
:37:36","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002959718","Nsi=
meyong Shell","","30-08-2024 16:19:47","30-08-2024 13:32:18","30-08-2024 16=
:44:05","Grid Outage, site went down because Gen  failed to start due to st=
actic charger faulty  // Gen manually started with external battery ","MINK=
A NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batter=
y","Grid Outage, site went down because Gen  failed to start due to stactic=
 charger faulty  // Gen manually started with external battery ","kouoh.jea=
n@ihstowers.com","10050","30-08-2024 16:19:47","Sagemcom CMR"
"Closed Complete","Site Down","T0603","IHS_YND_069","NOCINC0002959462","Efo=
ulan MTN","","30-08-2024 15:33:05","30-08-2024 15:16:18","30-08-2024 15:32:=
37","Site went down due to insufficient of rectifier on site (03/04)// Site=
 stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rect=
ifier Module","Site went down due to insufficient of rectifier on site (03/=
04)// Site stabilized","kouoh.jean@ihstowers.com","1007","30-08-2024 15:33:=
05","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002959324","Aha=
la","","30-08-2024 15:01:34","30-08-2024 10:40:08","30-08-2024 13:53:08",""=
,"Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, DG started and stopped due to overload and high temperature/=
/He reduced the load.site on DG.","kouoh.jean@ihstowers.com","15686","30-08=
-2024 15:01:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0002959145","Kondengu=
i","","30-08-2024 14:29:00","30-08-2024 14:02:21","30-08-2024 17:18:32","Ca=
scaded Incident from TTO2779794","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage No Space to deploy a MDG/=
/Grid Restored","system","1599","30-08-2024 14:29:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0002959143","E=
mombo-Tchad","IHS_YND_114","30-08-2024 14:28:27","30-08-2024 14:02:21","30-=
08-2024 17:18:32","Grid outage No Space to deploy a MDG//Grid Restored","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage No Space to deploy a MDG//Grid Restored","landry.etame@ihstowers.com",=
"1567","30-08-2024 14:28:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0002958885","Abattoir=
","","30-08-2024 13:49:30","30-08-2024 13:46:19","30-08-2024 14:06:45","Cas=
caded Incident from TTO2779501","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation site went down beca=
use Gen Card Faulty  // He Manually Started the  Gen","system","191","30-08=
-2024 13:49:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0002958887","Etoudi 2=
","","30-08-2024 13:49:30","30-08-2024 13:46:19","30-08-2024 14:06:45","Cas=
caded Incident from TTO2779501","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation site went down beca=
use Gen Card Faulty  // He Manually Started the  Gen","system","191","30-08=
-2024 13:49:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0002958886","ETOUDI C=
HAPELLE","","30-08-2024 13:49:30","30-08-2024 13:46:19","30-08-2024 14:06:4=
5","Cascaded Incident from TTO2779501","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation site went dow=
n because Gen Card Faulty  // He Manually Started the  Gen","system","191",=
"30-08-2024 13:49:30","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0002958882","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","30-08-2024 13:48:23","30-08-2=
024 13:46:19","30-08-2024 14:06:45","Grid fluctuation site went down becaus=
e Gen Card Faulty  // He Manually Started the  Gen","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid fluctuation=
 site went down because Gen Card Faulty  // He Manually Started the  Gen","=
emmanuel.ghani@ihstowers.com","125","30-08-2024 13:48:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0002958788","Nguila",=
"IHS_YND_434, IHS_YND_444","30-08-2024 13:31:11","30-08-2024 13:26:25","30-=
08-2024 13:28:10","Active//No power  issue U=3D50,7 V  site on Gen The Tx F=
Me Gr=E9goire (652070658) is informed ,Site up 01:32 PM","Parker Tchoup","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power  issue U=3D50,7 V  site on Gen The Tx FMe Gr=E9g=
oire (652070658) is informed ,Site up 01:32 PM","system","286","30-08-2024 =
13:31:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0002958789","Dong",""=
,"30-08-2024 13:31:11","30-08-2024 13:26:25","30-08-2024 13:28:10","Cascade=
d Incident from TTO2779392","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","Active//No power  issue U=3D50,7 V  site on G=
en The Tx FMe Gr=E9goire (652070658) is informed ,Site up 01:32 PM","system=
","286","30-08-2024 13:31:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0002958783","D=
onga","","30-08-2024 13:30:29","30-08-2024 13:26:25","30-08-2024 13:28:10",=
"Active//No power  issue U=3D50,7 V  site on Gen The Tx FMe Gr=E9goire (652=
070658) is informed ,Site up 01:32 PM","Parker Tchoup","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active//No power  issue U=3D50,7 V=
  site on Gen The Tx FMe Gr=E9goire (652070658) is informed ,Site up 01:32 =
PM","joelle.ekessi@ihstowers.com","245","30-08-2024 13:30:29","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0002958773","Accacia =
New","","30-08-2024 13:28:31","30-08-2024 13:23:16","30-08-2024 13:33:14","=
Cascaded Incident from TTO2779358","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","grid outage, site down before gen start due to p=
oor backupp//grid return","system","315","30-08-2024 13:28:31","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_546","NOCINC0002958774","Biyemass=
i LAC","","30-08-2024 13:28:31","30-08-2024 13:23:16","30-08-2024 13:33:14"=
,"Cascaded Incident from TTO2779358","","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","grid outage, site down before gen start due to=
 poor backupp//grid return","system","315","30-08-2024 13:28:31","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_683","NOCINC0002958775","BONAS YD=
E","","30-08-2024 13:28:31","30-08-2024 13:23:16","30-08-2024 13:33:14","Ca=
scaded Incident from TTO2779358","Paul BIBOUM","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","grid outage, site down before gen start=
 due to poor backupp//grid return","system","315","30-08-2024 13:28:31","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_507","NOCINC0002958777","BIYEM AS=
SI LYCEE","","30-08-2024 13:28:31","30-08-2024 13:23:16","30-08-2024 13:33:=
14","Cascaded Incident from TTO2779358","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage, site down before=
 gen start due to poor backupp//grid return","system","315","30-08-2024 13:=
28:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0002958772","Ngoa Eke=
lle","","30-08-2024 13:28:31","30-08-2024 13:23:16","30-08-2024 13:33:14","=
Cascaded Incident from TTO2779358","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, site down before gen sta=
rt due to poor backupp//grid return","system","315","30-08-2024 13:28:31","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_724","NOCINC0002958778","BIYEMASS=
I NIKI","","30-08-2024 13:28:31","30-08-2024 13:23:16","30-08-2024 13:33:14=
","Cascaded Incident from TTO2779358","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site down before g=
en start due to poor backupp//grid return","system","315","30-08-2024 13:28=
:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_805","NOCINC0002958776","Behind P=
 T school Yde","","30-08-2024 13:28:31","30-08-2024 13:23:16","30-08-2024 1=
3:33:14","Cascaded Incident from TTO2779358","Paul BIBOUM","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid outage, site down befo=
re gen start due to poor backupp//grid return","system","315","30-08-2024 1=
3:28:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0002958770","Scalom",=
"","30-08-2024 13:28:30","30-08-2024 13:23:16","30-08-2024 13:33:14","Casca=
ded Incident from TTO2779358","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","grid outage, site down before gen start du=
e to poor backupp//grid return","system","314","30-08-2024 13:28:30","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_074","NOCINC0002958771","Obili Ch=
apelle","","30-08-2024 13:28:30","30-08-2024 13:23:16","30-08-2024 13:33:14=
","Cascaded Incident from TTO2779358","Paul BIBOUM","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, site down before gen =
start due to poor backupp//grid return","system","314","30-08-2024 13:28:30=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_155","NOCINC0002958769","Obobogo"=
,"","30-08-2024 13:28:30","30-08-2024 13:23:16","30-08-2024 13:33:14","Casc=
aded Incident from TTO2779358","MINKA NICOLAS","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","grid outage, site down before gen start=
 due to poor backupp//grid return","system","314","30-08-2024 13:28:30","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0002958754","Nlo=
ng Mvolye New","IHS_YND_155, IHS_YND_071, IHS_YND_074, IHS_YND_060, IHS_YND=
_562, IHS_YND_546, IHS_YND_683, IHS_YND_805, IHS_YND_507, IHS_YND_724","30-=
08-2024 13:25:21","30-08-2024 13:23:16","30-08-2024 13:33:14","grid outage,=
 site down before gen start due to poor backupp//grid return","Paul BIBOUM"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low"=
,"grid outage, site down before gen start due to poor backupp//grid return"=
,"emmanuel.ghani@ihstowers.com","126","30-08-2024 13:25:21","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002958705","Eko=
unou","","30-08-2024 13:15:38","30-08-2024 13:12:33","30-08-2024 13:20:50",=
"Grid outage,site went down before DG start : Poor Batteries Backup //DG st=
arted automatically.","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage,site went down before DG=
 start : Poor Batteries Backup //DG started automatically.","emmanuel.ghani=
@ihstowers.com","186","30-08-2024 13:15:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0002958301","M=
om","","30-08-2024 12:09:32","30-08-2024 12:04:25","30-08-2024 12:16:03","G=
rid outage,Main DG faulty //Mobile DG  20 kva has deployed.","Fanda Brice",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid out=
age,Main DG faulty //Mobile DG  20 kva has deployed.","joelle.ekessi@ihstow=
ers.com","308","30-08-2024 12:09:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002958194","B=
ATA-Mokolo","","30-08-2024 11:48:08","30-08-2024 11:45:03","30-08-2024 13:5=
0:28","Grid outage No space to deployed a mobile Gen  // Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge No space to deployed a mobile Gen  because the space is not free//   Gri=
d return","joelle.ekessi@ihstowers.com","185","30-08-2024 11:48:08","Sagemc=
om CMR"
"Closed Complete","Site Down","T1587","IHS_YND_291","NOCINC0002957684","Eko=
umdoum OCM","","30-08-2024 10:25:06","30-08-2024 10:21:47","30-08-2024 11:0=
8:19","Grid outage ,Site went down because Gen started and stopped with ala=
rm""low oil pressure""(alarm unprouven)//He reset Gen card and started Gen =
(investigation ongoing)","Albran Byorel","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","Grid outage ,Site went down because Gen start=
ed and stopped with alarm""low oil pressure""(alarm unprouven)//He reset Ge=
n card and started Gen (investigation ongoing)
","emmanuel.ghani@ihstowers.com","719","30-08-2024 10:25:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002957476","Eto koss=
 Yde","","30-08-2024 09:57:00","30-08-2024 09:43:54","30-08-2024 10:25:37",=
"Cascaded Incident from TTO2777909","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,Main DG faulty //Mobile =
DG  20 kva has deployed","system","786","30-08-2024 09:57:00","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002957477","ELOUMDEM=
 CARRIERE 2","","30-08-2024 09:57:00","30-08-2024 09:43:54","30-08-2024 10:=
25:37","Cascaded Incident from TTO2777909","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage,Main DG faulty //=
Mobile DG  20 kva has deployed","system","786","30-08-2024 09:57:00","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002957469","MBALNGON=
G LYCEE","","30-08-2024 09:55:21","30-08-2024 09:42:37","30-08-2024 10:20:4=
1","Cascaded Incident from TTO2777887","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, DG started and stopp=
ed due to overload  and high temperature//He reduice the load.site on DG.",=
"system","764","30-08-2024 09:55:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002957470","Afanoya"=
,"","30-08-2024 09:55:21","30-08-2024 09:42:37","30-08-2024 10:20:41","Casc=
aded Incident from TTO2777887","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, DG started and stopped du=
e to overload  and high temperature//He reduice the load.site on DG.","syst=
em","764","30-08-2024 09:55:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002957468","ELOUMDEM=
 CARRIERE","","30-08-2024 09:55:20","30-08-2024 09:42:37","30-08-2024 10:20=
:41","Cascaded Incident from TTO2777887","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, DG started and sto=
pped due to overload  and high temperature//He reduice the load.site on DG.=
","system","763","30-08-2024 09:55:21","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002957450","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","30-08-2024 09:52:43","30-08-20=
24 09:42:37","30-08-2024 10:20:41","Grid outage, DG started and stopped due=
 to overload  and high temperature//He reduice the load.site on DG.","Hyema=
fo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage, DG started and stopped due to overload  and high temperature//He re=
duice the load.site on DG.","emmanuel.ghani@ihstowers.com","606","30-08-202=
4 09:52:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0002957413","M=
EFOU ASSI","IHS_YND_737, IHS_YND_768","30-08-2024 09:44:57","30-08-2024 09:=
41:54","30-08-2024 10:25:37","Grid outage,Main DG faulty //Mobile DG  20 kv=
a has deployed","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Generator Faulty","Grid outage,Main DG faulty //Mobile DG  20 kva has de=
ployed","joelle.ekessi@ihstowers.com","184","30-08-2024 09:44:57","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0002957291","Abo=
me","","30-08-2024 09:19:50","30-08-2024 09:11:45","30-08-2024 10:30:41","f=
me is on the way to site ETA=3D10:15","MINKA NICOLAS","Equipment Repair","P=
assive","ACDG Gen","ACDG - Control Panel"," Grid outage ,site went down bec=
ause Gen started and stopped with alarm""low water level""//he reset Gen ca=
rd , remvoved  water sensor and started Gen ","emmanuel.ghani@ihstowers.com=
","1119","30-08-2024 09:19:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002957253","ELOUMDEM=
 CARRIERE","","30-08-2024 09:09:40","30-08-2024 09:04:32","30-08-2024 09:26=
:25","Cascaded Incident from TTO2777635","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site down because =
Gen failed to start due to poor backup //Grid power return ","system","308"=
,"30-08-2024 09:09:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002957254","MBALNGON=
G LYCEE","","30-08-2024 09:09:40","30-08-2024 09:04:32","30-08-2024 09:26:2=
5","Cascaded Incident from TTO2777635","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site down because Ge=
n failed to start due to poor backup //Grid power return ","system","308","=
30-08-2024 09:09:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002957255","Afanoya"=
,"","30-08-2024 09:09:40","30-08-2024 09:04:32","30-08-2024 09:26:25","Casc=
aded Incident from TTO2777635","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site down because Gen fai=
led to start due to poor backup //Grid power return ","system","308","30-08=
-2024 09:09:40","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002957246","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","30-08-2024 09:08:37","30-08-20=
24 09:04:32","30-08-2024 09:32:49","Grid outage, site went down before gen =
start due to poor battery backup // Gen started automatically","Hyemafo Gil=
das","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery =
Low","Grid outage, site went down before gen start due to poor battery back=
up // Gen started automatically","emmanuel.ghani@ihstowers.com","245","30-0=
8-2024 09:08:37","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002957128","Nsi=
meyong Shell","","30-08-2024 08:51:28","30-08-2024 08:50:19","30-08-2024 09=
:00:31","Grid outage, site down because Gen failed to start due to poor bac=
kup //Grid power return ","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site down because G=
en failed to start due to poor backup //Grid power return ","emmanuel.ghani=
@ihstowers.com","70","30-08-2024 08:51:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0002957123","A=
nguissa New","","30-08-2024 08:50:27","30-08-2024 08:44:59","30-08-2024 13:=
14:01","","MINKA NICOLAS","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","grid outage no space for a MDG, //grid return","joelle.ekess=
i@ihstowers.com","873","30-08-2024 08:50:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_115","NOCINC0002957113","Labogeni=
e","IHS_YND_568","30-08-2024 08:47:03","30-08-2024 08:44:59","30-08-2024 13=
:14:01","grid outage no space for a MDG, //grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","grid outage no space fo=
r a MDG, //grid return","joelle.ekessi@ihstowers.com","125","30-08-2024 08:=
47:03","Sagemcom CMR"
"Closed Complete","Warning","CTR_079","IHS_YND_306","NOCINC0002957057","Nko=
zoa","","30-08-2024 08:28:21","","","Grid fluctuation site alarming because=
 site on battery causing by  Gen failled to started due to Grid bad voltage=
 // He bypass the Grid and site on Gen manually started","Fabrice Pouakam",=
"Warning","Warning","POWER","Warning - Site on Battery","Grid fluctuation s=
ite alarming because site on battery causing by  Gen failled to started due=
 to Grid bad voltage // He bypass the Grid and site on Gen manually started=
","kombi.samuel@ihstowers.com","3","30-08-2024 08:28:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002956923","MBALNGON=
G LYCEE","","30-08-2024 07:58:30","30-08-2024 07:56:05","30-08-2024 08:16:1=
8","Cascaded Incident from TTO2777247","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,site went down before=
 DG start : Poor Batteries Backup //DG started automatically.","system","14=
5","30-08-2024 07:58:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002956922","ELOUMDEM=
 CARRIERE","","30-08-2024 07:58:30","30-08-2024 07:56:05","30-08-2024 08:16=
:18","Cascaded Incident from TTO2777247","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage,site went down befo=
re DG start : Poor Batteries Backup //DG started automatically.","system","=
145","30-08-2024 07:58:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002956924","Afanoya"=
,"","30-08-2024 07:58:30","30-08-2024 07:56:05","30-08-2024 08:16:18","Casc=
aded Incident from TTO2777247","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,site went down before DG s=
tart : Poor Batteries Backup //DG started automatically.","system","145","3=
0-08-2024 07:58:30","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002956915","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","30-08-2024 07:57:10","30-08-20=
24 07:54:05","30-08-2024 08:16:18","Grid outage,site went down before DG st=
art : Poor Batteries Backup //DG started automatically.","Hyemafo Gildas","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","=
Grid outage,site went down before DG start : Poor Batteries Backup //DG sta=
rted automatically.","emmanuel.ghani@ihstowers.com","336","30-08-2024 07:57=
:10","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002956906","Eko=
unou","","30-08-2024 07:55:59","30-08-2024 07:54:55","30-08-2024 08:00:10",=
"Grid outage,site went down before DG start : Poor Batteries Backup //DG st=
arted automatically.","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage,site went down before DG=
 start : Poor Batteries Backup //DG started automatically.","emmanuel.ghani=
@ihstowers.com","65","30-08-2024 07:55:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0002956547","N=
omayos-IHS","","30-08-2024 06:42:17","30-08-2024 06:22:13","30-08-2024 08:2=
0:39","Site went down because 02/04 rectifiers hanging//He reset  rectifier=
s ,Site on Grid.","Fanda Brice","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down because 02/04 rectifiers hanging//He reset=
  rectifiers ,Site on Grid.","joelle.ekessi@ihstowers.com","6884","30-08-20=
24 06:42:17","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0002956518","Mom=
","","30-08-2024 06:32:51","30-08-2024 06:25:27","30-08-2024 07:24:41","Gri=
d outage,Main DG faulty //Mobile DG deployed.","Fanda Brice","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage,Main DG fa=
ulty //Mobile DG deployed.","emmanuel.ghani@ihstowers.com","711","30-08-202=
4 06:32:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_360","IHS_YND_373","NOCINC0002955905","M=
aloun","","30-08-2024 03:39:39","30-08-2024 03:29:59","30-08-2024 05:18:02"=
,"Hybrid gen site gen failed to start due to alarm ""uderfrequency""//we re=
set card GE and gen manually started ","Kemeni Franklin","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Hybrid gen site gen failed to=
 start due to alarm ""uderfrequency""//we reset card GE and gen manually st=
arted ","dorothy.djantio@ihstowers.com","581","30-08-2024 03:39:39","Sagemc=
om CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0002954724","Tam=
tam Weekend","","29-08-2024 22:05:20","29-08-2024 21:41:11","29-08-2024 22:=
54:22","Site went down because the Cb(63A) of PWC dysjoncted due to load in=
creased on site // He reamed the CB","Hyemafo Gildas","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site went =
down because the Cb(63A) of PWC dysjoncted due to load increased on site //=
 He reamed the CB","stephane.nkamwa@ihstowers.com","1450","29-08-2024 22:05=
:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0002954723","A=
wae Ewonkan","","29-08-2024 22:05:17","29-08-2024 21:57:11","29-08-2024 23:=
04:24","site went down because 01/05 rectifier dysfonction due to load incr=
eased // He reset the rectifier","Albran Byorel","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","site went down because 01/05 rectifier d=
ysfonction due to load increased // He reset the rectifier","alexandre.kama=
l@ihstowers.com","486","29-08-2024 22:05:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0002954602","M=
ontee-Jouvence-II","","29-08-2024 21:37:30","29-08-2024 21:22:24","29-08-20=
24 22:37:16","Site went down because the Cb(125A) of PWC dysjoncted due to =
load increased on site // He reamed the CB","Hyemafo Gildas","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Sit=
e went down because the Cb(125A) of PWC dysjoncted due to load increased on=
 site // He reamed the CB","alexandre.kamal@ihstowers.com","907","29-08-202=
4 21:37:30","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0002954533","BAT=
A Mokolo OCM","","29-08-2024 21:23:41","29-08-2024 21:14:23","29-08-2024 22=
:32:46","Grid outage no space to deploy MDG //Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space=
 to deploy MDG //Grid return","stephane.nkamwa@ihstowers.com","559","29-08-=
2024 21:23:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_010","IHS_YND_327","NOCINC0002954307","N=
simalen OCM","","29-08-2024 20:52:04","29-08-2024 20:47:58","29-08-2024 23:=
06:35","Site went down due to insufficient of rectifier on site// Site stab=
ilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","Site went down due to insufficient of rectifier on site// Site st=
abilized","alexandre.kamal@ihstowers.com","247","29-08-2024 20:52:04","Sage=
mcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0002954297","Nko=
lbisson IITA LP","","29-08-2024 20:51:45","29-08-2024 20:45:28","29-08-2024=
 20:50:23"," No power issue site on battery Ubaie=3D49,8V Impacted by Nkolb=
isson 2 OCM not managing by IHS","","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm"," No power issue site on bat=
tery Ubaie=3D49,8V Impacted by Nkolbisson 2 OCM not managing by IHS","steph=
ane.nkamwa@ihstowers.com","378","29-08-2024 20:51:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0002954261","B=
yemassi Carrefour","","29-08-2024 20:49:44","29-08-2024 20:39:59","30-08-20=
24 00:40:49","Active// Active: No power issue, site is on Grid with Ubaie=
=3D53,5 The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","Paul BI=
BOUM","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active// Active: No power issue, site is on Grid with Uba=
ie=3D53,5 The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","alexa=
ndre.kamal@ihstowers.com","586","29-08-2024 20:49:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0002954254","S=
cience","","29-08-2024 20:48:12","29-08-2024 20:37:59","30-08-2024 01:15:30=
","No power issue Ubaie=3D 53.5 V site on Grid  The TX FME Mohamadou 691144=
435//  from huawei is informed. Notice that we have disjunction at BTS OCM"=
,"TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue Ubaie=3D 53.5 V site=
 on Grid  The TX FME Mohamadou 691144435//  from huawei is informed. Notice=
 that we have disjunction at BTS OCM","alexandre.kamal@ihstowers.com","614"=
,"29-08-2024 20:48:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0002954209","H=
-Progres","","29-08-2024 20:39:47","29-08-2024 19:29:42","29-08-2024 22:20:=
02","Grid Outage, No space to deploy a MDG // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No spac=
e to deploy a MDG // Grid return
","alexandre.kamal@ihstowers.com","4205","29-08-2024 20:39:47","Sagemcom CM=
R"
"Closed Complete","Site Down","T1282","IHS_YND_803","NOCINC0002954100","Eto=
ug ebe biscuiterie","","29-08-2024 20:16:27","29-08-2024 20:06:22","29-08-2=
024 20:10:13","Active: No power issue, site is on Gen with Ubaie=3D53,2V, T=
X RM martial(690087047) from Huawei is informed","Hyemafo Gildas","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active: No power issue, site is on Gen with Ubaie=3D53,2V, TX RM martial=
(690087047) from Huawei is informed","stephane.nkamwa@ihstowers.com","605",=
"29-08-2024 20:16:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0002953901","N=
kolda","","29-08-2024 19:25:20","29-08-2024 19:14:59","29-08-2024 20:39:22"=
,"Grid Outage Gen Failed to Start due to Battery Terminal  Oxyde//He clean =
The Battery Terminal and Gen Manually Started","Albran Byorel","Equipment R=
epair","Passive","ACDG Gen","ACDG - Generator Battery","Grid Outage Gen Fai=
led to Start due to Battery Terminal  Oxyde//He clean The Battery Terminal =
and Gen Manually Started","alexandre.kamal@ihstowers.com","621","29-08-2024=
 19:25:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0002953889","N=
kongtock","","29-08-2024 19:22:07","29-08-2024 19:05:22","29-08-2024 21:08:=
45","Solar gen site .gen start and stopped due to air intake//we purged ans=
 gen manually started","Kemeni Franklin","Fuel Outage (Probable)","Passive"=
,"ACDG Gen","ACDG - Air Intake","Solar gen site .gen start and stopped due =
to air intake//we purged ans gen manually started","alexandre.kamal@ihstowe=
rs.com","1006","29-08-2024 19:22:07","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002953877","Tsi=
nga","","29-08-2024 19:17:18","29-08-2024 19:06:03","29-08-2024 19:28:47","=
Grid outage, site went down before gen start due to poor battery backup // =
Gen start automatically","Mboua Thierry","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // Gen start automatically","stephan=
e.nkamwa@ihstowers.com","676","29-08-2024 19:17:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0002953781","C=
amp-Sic-Tsinga","","29-08-2024 19:10:16","29-08-2024 18:56:05","29-08-2024 =
22:12:44","Grid Outage, No space to deploy a MDG // Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, N=
o space to deploy a MDG // Grid return
","alexandre.kamal@ihstowers.com","852","29-08-2024 19:10:16","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002953779","B=
ATA-Mokolo","","29-08-2024 19:09:23","29-08-2024 18:55:19","29-08-2024 22:2=
2:43","Grid Outage, No space to deploy a MDG // Grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage, No sp=
ace to deploy a MDG // Grid return","alexandre.kamal@ihstowers.com","845","=
29-08-2024 19:09:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002953761","N=
koabang2","","29-08-2024 19:06:12","29-08-2024 17:56:12","29-08-2024 18:42:=
21","Site went down because 02/06 rectifier dysfonction on site // he remov=
ed 02 rectifier","Mba Lazare Herve","Equipment Repair","Passive","Rectifier=
","Rectifier Module","Site went down because 02/06 rectifier dysfonction on=
 site // he removed 02 rectifier","alexandre.kamal@ihstowers.com","4201","2=
9-08-2024 19:06:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0002953387","Dagobert=
","","29-08-2024 17:34:41","29-08-2024 17:25:45","29-08-2024 17:30:11","Act=
ive// No power Issue,  site on grid,Ubaie:55,1V; Erick/696422966 From ZTE  =
is working on site.","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No pow=
er Issue,  site on grid,Ubaie:55,1V; Erick/696422966 From ZTE  is working o=
n site.","system","1492","29-08-2024 17:34:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0002952804","N=
kozoa","","29-08-2024 15:54:37","29-08-2024 15:39:32","29-08-2024 16:25:50"=
,"Grid fluctuation site went down because Gen failled to started due to Gri=
d bad voltage // He bypass the Grid and site on Gen","Fabrice Pouakam","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation site went down because Gen failled to started due to Grid bad v=
oltage // He bypass the Grid and site on Gen","alexandre.kamal@ihstowers.co=
m","905","29-08-2024 15:54:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0002952742","Y=
de-M-Central","","29-08-2024 15:36:40","29-08-2024 14:37:06","29-08-2024 14=
:42:12","Active: No power issue, site on Grid with Ubaie=3D55.8V, Brice Tsa=
gue (650 21 40 96) from Huawei is informed, Notice that we have disjunction=
 at BTS OCM","","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active: No power issue, site on Grid with Ubaie=
=3D55.8V, Brice Tsague (650 21 40 96) from Huawei is informed, Notice that =
we have disjunction at BTS OCM","alexandre.kamal@ihstowers.com","3575","29-=
08-2024 15:36:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_135","IHS_YND_387","NOCINC0002952697","T=
alla Monatele","","29-08-2024 15:26:30","29-08-2024 14:44:23","29-08-2024 1=
7:18:55","Grid Outage, Site went down because gen start and  stopped with "=
"low oil pressure"" alarm  // He added oil, reset Card GEN and started Gen =
manualy","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Grid Outage, Site went down because gen start and  stopped wi=
th ""low oil pressure"" alarm  // He added oil, reset Card GEN and started =
Gen manualy","alexandre.kamal@ihstowers.com","2527","29-08-2024 15:26:30","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0002952112","N=
kozoa","","29-08-2024 13:19:38","29-08-2024 13:04:32","29-08-2024 14:23:27"=
,"Grid Bad Voltage and Gen Failed to start and Site wend down due to lack o=
n 02 phases on site //He make the bridge on good phase","Fabrice Pouakam","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id Bad Voltage and Gen Failed to start and Site wend down due to lack on 02=
 phases on site //He make the bridge on good phase","landry.etame@ihstowers=
.com","906","29-08-2024 13:19:38","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002951910","Eko=
unou","","29-08-2024 12:30:31","29-08-2024 12:22:22","29-08-2024 12:30:42",=
"Grid outage,site went down before DG start : poor batteries backup //DG st=
arted automatically.","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage,site went down before DG=
 start : poor batteries backup //DG started automatically.","kouoh.jean@ihs=
towers.com","490","29-08-2024 12:30:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0002951856","L=
abogenie","","29-08-2024 12:18:59","29-08-2024 12:00:53","29-08-2024 12:23:=
38","grid outage; no space to deploy a MDG//grid return","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","grid outage; no space =
to deploy a MDG//grid return","landry.etame@ihstowers.com","1087","29-08-20=
24 12:18:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0002951706","S=
apeur Mimboman","","29-08-2024 12:02:17","29-08-2024 11:50:11","29-08-2024 =
12:21:02","Grid outage DG failed to start due to ACDG control panel faulty =
//Grid restored.","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen=
","ACDG - Control Panel","Grid outage DG failed to start due to ACDG contro=
l panel faulty //Grid restored.","landry.etame@ihstowers.com","727","29-08-=
2024 12:02:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002951671","M=
imboman-Village","","29-08-2024 11:55:24","29-08-2024 11:44:18","29-08-2024=
 13:31:28","Tx Issue: site on grid,Ubaie:52.1V;  Eloundou bertrand/652-586-=
578 is informed","Mba Lazare Herve","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","Tx Issue: site on grid,Ubai=
e:52.1V;  Eloundou bertrand/652-586-578 is informed","landry.etame@ihstower=
s.com","667","29-08-2024 11:55:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0002951661","M=
IMBOMAN LIBERTE","","29-08-2024 11:52:41","29-08-2024 11:41:35","29-08-2024=
 12:05:10","Grid outage,Main DG overload // Mobile DG deployed (15 kva)","M=
ba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage,Main DG overload // Mobile DG deployed (15 kva)","landry.etame=
@ihstowers.com","667","29-08-2024 11:52:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002951598","N=
kolo II New","","29-08-2024 11:37:14","29-08-2024 11:19:09","29-08-2024 13:=
18:32","Tx Issue: site on grid,Ubaie:54V; Eloundou/652-58-65-78 is informed=
.","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","Tx Issue: site on grid,Ubaie:54V; Eloundo=
u/652-58-65-78 is informed.","landry.etame@ihstowers.com","1086","29-08-202=
4 11:37:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0002951579","Ngog Map=
ubi","","29-08-2024 11:33:10","29-08-2024 11:21:34","29-08-2024 11:23:16","=
Cascaded Incident from TTO2771139","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage,Site went down before=
 DG start : Poor Batteries backup//DG started automatically,Although power =
issue resolved site remained down power reset has been done
Etienne Fopa was informed.","system","696","29-08-2024 11:33:10","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0002951581","Mamb",""=
,"29-08-2024 11:33:10","29-08-2024 11:21:34","29-08-2024 11:23:16","Cascade=
d Incident from TTO2771139","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage,Site went down before DG sta=
rt : Poor Batteries backup//DG started automatically,Although power issue r=
esolved site remained down power reset has been done
Etienne Fopa was informed.","system","696","29-08-2024 11:33:10","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0002951578","Ndogbess=
ol","","29-08-2024 11:33:10","29-08-2024 11:21:34","29-08-2024 11:23:16","C=
ascaded Incident from TTO2771139","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,Site went down before =
DG start : Poor Batteries backup//DG started automatically,Although power i=
ssue resolved site remained down power reset has been done
Etienne Fopa was informed.","system","696","29-08-2024 11:33:10","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0002951580","Boumnyeb=
el","","29-08-2024 11:33:10","29-08-2024 11:21:34","29-08-2024 11:23:16","C=
ascaded Incident from TTO2771139","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,Site went down before =
DG start : Poor Batteries backup//DG started automatically,Although power i=
ssue resolved site remained down power reset has been done
Etienne Fopa was informed.","system","696","29-08-2024 11:33:10","Sagemcom =
CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002951566","Eko=
unou","","29-08-2024 11:30:41","29-08-2024 11:19:47","29-08-2024 11:25:47",=
"Grid outage,site went down before DG start : Poor Batteries Backup //DG st=
arted automatically","Albran Byorel","Equipment Repair","Passive","Control =
Panel","Power Cabinet - Battery Low","Grid outage,site went down before DG =
start : Poor Batteries Backup //DG started automatically","kouoh.jean@ihsto=
wers.com","655","29-08-2024 11:30:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0002951564","B=
oumnyebel OCM","IHS_EDA_056, IHS_YND_419, IHS_YND_381, IHS_YND_376","29-08-=
2024 11:30:14","29-08-2024 11:21:34","29-08-2024 11:23:16","Grid outage,Sit=
e went down before DG start : Poor Batteries backup//DG started automatical=
ly,Although power issue resolved site remained down power reset has been do=
ne Etienne Fopa was informed.","Kemeni Franklin","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage,Site went dow=
n before DG start : Poor Batteries backup//DG started automatically,Althoug=
h power issue resolved site remained down power reset has been done
Etienne Fopa was informed.","landry.etame@ihstowers.com","521","29-08-2024 =
11:30:14","Sagemcom CMR"
"Closed Complete","Warning","CTR_079","IHS_YND_306","NOCINC0002950831","Nko=
zoa","","29-08-2024 09:44:51","","","Site on Battery due to grid bad voltag=
e ,DG failed to start //DG started automatically.","Fabrice Pouakam","Warni=
ng","Warning","POWER","Warning - National Grid - Grid Incomplete Phase","Si=
te on Battery due to grid bad voltage ,DG failed to start //DG started auto=
matically.","nadjia.njaya@ihstowers.com","250","29-08-2024 09:44:51","Sagem=
com CMR"
"Closed Complete","Warning","CTR_079","IHS_YND_306","NOCINC0002950828","Nko=
zoa","","29-08-2024 09:44:12","","","SITE ON BATTERY due to grid bad voltag=
e //DG manually start.","Fabrice Pouakam","Warning","Warning","POWER","Warn=
ing - AC Phase 1 Voltage low","SITE ON BATTERY due to grid bad voltage //DG=
 manually start.","nadjia.njaya@ihstowers.com","207","29-08-2024 09:44:12",=
"Sagemcom CMR"
"Closed Complete","Warning","CTR_080","IHS_YND_298","NOCINC0002950760","Ole=
mbe","","29-08-2024 09:27:33","","","Site alarming because low voltage due =
to work Supervisor  IHS Bernard Atagana working on site //end of work ;Alar=
m is cleared","Fabrice Pouakam","Warning","Warning","POWER","Warning - Low =
Voltage","Site alarming because low voltage due to work Supervisor  IHS Ber=
nard Atagana working on site //end of work ;Alarm is cleared","nadjia.njaya=
@ihstowers.com","1604","29-08-2024 09:27:33","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002950720","MAN=
GUIERS CHAPELLE","","29-08-2024 09:20:28","29-08-2024 09:12:04","29-08-2024=
 09:29:56","Grid outage, site went down before Gen start due to poor batter=
y backup // grid return","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore Gen start due to poor battery backup // grid return","kouoh.jean@ihstow=
ers.com","2983","29-08-2024 09:20:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002950701","O=
lembe-Terminus","","29-08-2024 09:15:21","29-08-2024 08:44:15","29-08-2024 =
09:46:23","Grid outage,Gen Start and Stop due to alarm Over-voltage //Grid =
Restored","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG -=
 Control Panel","Grid outage,Gen Start and Stop due to alarm Over-voltage /=
/Grid Restored","landry.etame@ihstowers.com","1867","29-08-2024 09:15:21","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0002950692","Akak-Nko=
zoa-MTN-IHS","","29-08-2024 09:13:50","29-08-2024 08:41:26","29-08-2024 09:=
47:40","Cascaded Incident from TTO2770149","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Eneo outrage, GE failed t=
o start due the power pins at the disconnected board// Reconnecting the pin=
","system","1944","29-08-2024 09:13:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0002950536","N=
kongtock","","29-08-2024 08:44:02","29-08-2024 08:37:40","29-08-2024 11:15:=
40","Solar,DG,DG stopped due to fuel shortage //Refueling done.","Kemeni Fr=
anklin","Fuel Outage","Passive","Diesel","Diesel Outage","Solar,DG,DG stopp=
ed due to fuel shortage //Refueling done.","landry.etame@ihstowers.com","38=
2","29-08-2024 08:44:02","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002949930","Jou=
vence 2000","","29-08-2024 06:26:45","29-08-2024 06:17:36","29-08-2024 07:5=
0:00","Grid Fluctuation,site went down before DG start: Poor Batteries Back=
up // grid restored.","Delor Telezing","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid Fluctuation,site went down bef=
ore DG start: Poor Batteries Backup // Grid restored.","kouoh.jean@ihstower=
s.com","550","29-08-2024 06:26:45","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002949596","Tsi=
nga","","29-08-2024 03:52:40","29-08-2024 03:36:14","29-08-2024 03:58:16","=
Grid outage,site went down before DG start: Poor Batteries Backup //Grid re=
turn","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power C=
abinet - Battery Low","Grid outage,site went down before DG start: Poor Bat=
teries Backup //Grid return","ange.kongo@ihstowers.com","987","29-08-2024 0=
3:52:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002948901","O=
lembe-Terminus","","28-08-2024 23:55:01","28-08-2024 23:45:56","29-08-2024 =
00:33:58","Active, no power issue,site on grid with U=3D54V Symphorien /650=
257151/ From huawei is informed","Fabrice Pouakam","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no p=
ower issue,site on grid with U=3D54V Symphorien /650257151/ From huawei is =
informed","adonis.defokoua@ihstowers.com","546","28-08-2024 23:55:01","Sage=
mcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0002948862","Lob=
o 2","","28-08-2024 23:30:32","28-08-2024 23:27:22","29-08-2024 00:54:08","=
site went down because gen start and stopped due to alarm overvoltage//he r=
eset the Gen card and started it","TIENTCHEU NZETCHIEU GAEL","Equipment Rep=
air","Passive","ACDG Gen","ACDG - Over Voltage","site went down because gen=
 start and stopped due to alarm overvoltage//he reset the Gen card and star=
ted it","ange.kongo@ihstowers.com","190","28-08-2024 23:30:32","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002948639","MBALNGON=
G LYCEE","","28-08-2024 22:40:40","28-08-2024 22:29:55","28-08-2024 22:43:5=
5","Cascaded Incident from TTO2767793","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid return","system","645","28-0=
8-2024 22:40:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002948638","ELOUMDEM=
 CARRIERE","","28-08-2024 22:40:40","28-08-2024 22:29:55","28-08-2024 22:43=
:55","Cascaded Incident from TTO2767793","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Grid return","system","645","28=
-08-2024 22:40:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002948640","Afanoya"=
,"","28-08-2024 22:40:40","28-08-2024 22:29:55","28-08-2024 22:43:55","Casc=
aded Incident from TTO2767793","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // Grid return","system","645","28-08-202=
4 22:40:40","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002948581","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","28-08-2024 22:38:20","28-08-20=
24 22:29:55","28-08-2024 22:43:55","Grid outage, site went down before gen =
start due to poor battery backup // Grid return","Hyemafo Gildas","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, site went down before gen start due to poor battery backup // Grid ret=
urn","ange.kongo@ihstowers.com","506","28-08-2024 22:38:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002948425","E=
lig-Edzoa","","28-08-2024 22:14:43","28-08-2024 21:44:37","28-08-2024 22:00=
:56","ACTIVE No power issue on site, site on Grid with Ubaie=3D54,6V Tx fme=
 Armand Ngeuts/699949553/ from Huawei is Informed  ","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE =
No power issue on site, site on Grid with Ubaie=3D54,6V Tx fme Armand Ngeut=
s/699949553/ from Huawei is Informed. =20
","dorothy.djantio@ihstowers.com","1807","28-08-2024 22:14:43","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0002947640","C=
-Supreme","","28-08-2024 20:02:29","28-08-2024 19:59:20","28-08-2024 20:05:=
06","Active: No power issue, site on Grid with Ubaie=3D54.5V, Brice Tsague =
(650 21 40 96) from Huawei is informed","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power iss=
ue, site on Grid with Ubaie=3D54.5V, Brice Tsague (650 21 40 96) from Huawe=
i is informed","dorothy.djantio@ihstowers.com","190","28-08-2024 20:02:29",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0002947481","M=
ontee-Jouvence-II","","28-08-2024 19:37:34","28-08-2024 19:30:27","28-08-20=
24 19:55:59","Grid fluctuation site went down because Gen failled to starte=
d due to Grid bad voltage // He bypass the Grid and site on Gen","Hyemafo G=
ildas","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation site went down because Gen failled to started due to=
 Grid bad voltage // He bypass the Grid and site on Gen","dorothy.djantio@i=
hstowers.com","428","28-08-2024 19:37:34","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0002947448","Com=
plex Beac II","","28-08-2024 19:29:26","28-08-2024 19:00:12","28-08-2024 20=
:02:03","Grid outage  site went down because Gen failed to start due to Gen=
 card faulty // Grid power return","Albran Byorel","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Control Panel","Grid outage  site went down because=
 Gen failed to start due to Gen card faulty // Grid power return","olivier.=
kwedi@ihstowers.com","1755","28-08-2024 19:29:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0002947435","M=
aison-Blanche-IHS","","28-08-2024 19:25:25","28-08-2024 19:16:20","28-08-20=
24 21:30:03","Active// Active: No power issue, site is on Grid with Ubaie=
=3D54The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active// Active: No power issue, site is on Grid with Ubaie=3D54The tx =
Fme Hosiah (6 74 00 74 38) from Huawei is informed","dorothy.djantio@ihstow=
ers.com","545","28-08-2024 19:25:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0002946899","Mendong =
vallee","","28-08-2024 17:31:50","28-08-2024 17:11:15","28-08-2024 18:06:21=
","Cascaded Incident from TTO2765862","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation site went down be=
cause Gen failled to started due to Grid bad voltage // He bypass the Grid =
and site on Gen","system","1235","28-08-2024 17:31:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0002946900","Montee-J=
ouvence","","28-08-2024 17:31:50","28-08-2024 17:11:15","28-08-2024 18:06:2=
1","Cascaded Incident from TTO2765862","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid fluctuation site went dow=
n because Gen failled to started due to Grid bad voltage // He bypass the G=
rid and site on Gen","system","1235","28-08-2024 17:31:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0002946892","M=
endong","IHS_YND_692, IHS_YND_236","28-08-2024 17:30:20","28-08-2024 17:11:=
15","28-08-2024 18:06:21","Grid fluctuation site went down because Gen fail=
led to started due to Grid bad voltage // He bypass the Grid and site on Ge=
n","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase C=
ontroller Faulty","Grid fluctuation site went down because Gen failled to s=
tarted due to Grid bad voltage // He bypass the Grid and site on Gen","doro=
thy.djantio@ihstowers.com","1146","28-08-2024 17:30:20","Sagemcom CMR"
"Cancelled","Warning","CTR_521","IHS_YND_692","NOCINC0002946889","Mendong v=
allee","","28-08-2024 17:27:42","","","","Fanda Brice","","","","","","doro=
thy.djantio@ihstowers.com","964","28-08-2024 17:27:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0002946426","C=
-Supreme","","28-08-2024 15:52:52","28-08-2024 15:44:48","28-08-2024 18:50:=
29","No power issue site on grid with U=3D54v RM Alain Tchaptchet(691144423=
) from Hauwei is informed ","","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with=
 U=3D54v RM Alain Tchaptchet(691144423) from Hauwei is informed ","dorothy.=
djantio@ihstowers.com","485","28-08-2024 15:52:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0002946423","A=
cropole","","28-08-2024 15:51:57","28-08-2024 15:44:52","28-08-2024 19:00:5=
1","Nopower issue site on grid with U=3D52.9v Elounndou Bertrand(652586578)=
 from Huawei is informed//site up at 03:52 PM","MINKA NICOLAS","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Nopower issue site on grid with U=3D52.9v Elounndou Bertrand(652586578) fro=
m Huawei is informed//site up at 03:52 PM","dorothy.djantio@ihstowers.com",=
"425","28-08-2024 15:51:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0002946413","C=
arrefourt Nkomo","","28-08-2024 15:50:00","28-08-2024 15:27:56","28-08-2024=
 16:10:33","No power issue ubaie=3D52.7V site impacted by Nkomo ctr_042","M=
ba Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue ubaie=3D52.7V site impacted by =
Nkomo ctr_042","dorothy.djantio@ihstowers.com","1325","28-08-2024 15:50:00"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0002946370","Nko=
mo","","28-08-2024 15:47:00","28-08-2024 15:26:40","28-08-2024 16:11:33","G=
rid fluctuation site went down because Gen failled to started due to Grid b=
ad voltage // He bypass the Grid and site on Gen","Mba Lazare Herve","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation site went down because Gen failled to started due to Grid bad vol=
tage // He bypass the Grid and site on Gen","olivier.kwedi@ihstowers.com","=
1329","28-08-2024 15:47:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002946329","O=
lembe-Terminus","","28-08-2024 15:42:48","28-08-2024 15:14:44","28-08-2024 =
19:30:19","No power issue site on grid with U=3D53.4v Symphorien(650257151)=
  from Huawei is informed ","Fabrice Pouakam","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue si=
te on grid with U=3D53.4v Symphorien(650257151)  from Huawei is informed ",=
"dorothy.djantio@ihstowers.com","1685","28-08-2024 15:42:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002946303","ELOUMDEM=
 CARRIERE 2","","28-08-2024 15:38:00","28-08-2024 15:27:59","28-08-2024 16:=
08:52","Cascaded Incident from TTO2765174","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to main gen Faulty // MDG 20kva deployed","system","601","28-08-2024 15:=
38:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002946302","Eto koss=
 Yde","","28-08-2024 15:38:00","28-08-2024 15:27:59","28-08-2024 16:08:52",=
"Cascaded Incident from TTO2765174","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to m=
ain gen Faulty // MDG 20kva deployed","system","601","28-08-2024 15:38:00",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002946289","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","28-08-2024 15:36:20","28-08-2024 15:24=
:03","28-08-2024 16:08:52","Grid outage, site went down due to main gen Fau=
lty // MDG 20kva deployed","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Generator Faulty","Grid outage, site went down due to main ge=
n Faulty // MDG 20kva deployed","olivier.kwedi@ihstowers.com","1387","28-08=
-2024 15:36:20","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002946269","Aka=
k-Nkozoa-MTN-IHS","","28-08-2024 15:30:57","28-08-2024 15:21:28","28-08-202=
4 16:11:07","Grid fluctuation site went down because Gen failled to started=
 due to Grid bad voltage // Grid stabilized","Fabrice Pouakam","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion site went down because Gen failled to started due to Grid bad voltage /=
/ Grid stabilized","olivier.kwedi@ihstowers.com","1446","28-08-2024 15:30:5=
7","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0002945898","E=
SSOS OASIS 1111","","28-08-2024 15:03:44","28-08-2024 14:27:35","28-08-2024=
 21:30:37","Active, no power issue, site on grid with U=3D54V, Armand Nguet=
sa /691144412/  From Huawei is informed","Siligap Boris","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
, no power issue, site on grid with U=3D54V, Armand Nguetsa /691144412/  Fr=
om Huawei is informed","dorothy.djantio@ihstowers.com","2170","28-08-2024 1=
5:03:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0002945616","Y=
de-M-Central","","28-08-2024 14:46:20","28-08-2024 14:04:03","28-08-2024 22=
:00:50","Active: No power issue, site on Grid with Ubaie=3D54.2V, Brice Tsa=
gue (650 21 40 96) from Huawei is informed, Notice that we have disjunction=
 at BTS OCM","","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active: No power issue, site on Grid with Ubaie=
=3D54.2V, Brice Tsague (650 21 40 96) from Huawei is informed, Notice that =
we have disjunction at BTS OCM","dorothy.djantio@ihstowers.com","2538","28-=
08-2024 14:46:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0002944464","M=
aison-Blanche-IHS","","28-08-2024 12:31:14","28-08-2024 11:50:05","28-08-20=
24 11:52:31","Active//No power issue, site on grid with U=3D54V, Team Olivi=
er /651559985/ From ZTE is working on site","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power=
 issue, site on grid with U=3D54V, Team Olivier /651559985/ From ZTE is wor=
king on site","alexandre.kamal@ihstowers.com","2470","28-08-2024 12:31:14",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0002943873","E=
mombo 2","","28-08-2024 09:58:28","28-08-2024 09:39:23","28-08-2024 09:45:1=
4","Active, No power issue site on grid with U=3D54,4V Team erick/Arnaud /6=
96422966/696287614/ From ZTE is working on site","MINKA NICOLAS","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active, No power issue site on grid with U=3D54,4V Team erick/Arnaud /696=
422966/696287614/ From ZTE is working on site","alexandre.kamal@ihstowers.c=
om","1146","28-08-2024 09:58:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0002943815","Nkoulou =
Carriere carrefourt","","28-08-2024 09:54:50","28-08-2024 09:19:02","28-08-=
2024 09:52:38","Cascaded Incident from TTO2762552 - Cascade Removed From TT=
O2762552","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","=
Cascade Passive","Grid outage, site went down because gen stoppet with 'Low=
 oil pressure' alarm // He added oil and manually start the gen","system","=
2148","28-08-2024 09:54:50","Sagemcom CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0002943796","Nko=
langaa","","28-08-2024 09:51:15","28-08-2024 09:19:02","28-08-2024 09:52:16=
","","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Casca=
de Passive","Grid outage, site went down because gen stoppet with 'Low oil =
pressure' alarm // He added oil and manually start the gen","stephane.nkamw=
a@ihstowers.com","1934","28-08-2024 09:51:15","Sagemcom CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0002943704","Aba=
ng","IHS_YND_794, IHS_YND_289","28-08-2024 09:34:49","28-08-2024 09:19:37",=
"28-08-2024 09:55:16","Grid outage, site went down because gen stoppet with=
 'Low oil pressure' alarm // He added oil and manually start the gen","Mba =
Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Press=
ure","Grid outage, site went down because gen stoppet with 'Low oil pressur=
e' alarm // He added oil and manually start the gen","stephane.nkamwa@ihsto=
wers.com","912","28-08-2024 09:34:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0002943156","E=
kie sud","","28-08-2024 07:56:29","28-08-2024 07:51:21","28-08-2024 07:52:2=
1","Active// No power issue, site on Grid with U=3D53,9V, The Tx FME Leonel=
 Steve /655184876/ from Huawei is informed","Albran Byorel","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive// No power issue, site on Grid with U=3D53,9V, The Tx FME Leonel Steve =
/655184876/ from Huawei is informed","alexandre.kamal@ihstowers.com","309",=
"28-08-2024 07:56:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0002942786","T=
singa","","28-08-2024 06:26:24","28-08-2024 06:11:18","28-08-2024 06:28:22"=
,"Grid Outage site down because Gen Start  due to poor backup //Grid Restor=
ed","Mboua Thierry","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Battery Low","Grid Outage site down because Gen Start  due to poor b=
ackup //Grid Restored","alexandre.kamal@ihstowers.com","907","28-08-2024 06=
:26:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0002942369","S=
imbock OCM","","28-08-2024 03:55:35","27-08-2024 22:41:29","27-08-2024 22:5=
2:54","Acces Issue During the night (Grid Fructuetion and Gen failed to sta=
rt // Grid Restored)","Hyemafo Gildas","Access Denial","Lease Or Legal","La=
ndlord Related Issues","Access Issue - Land Lord","Acces Issue During the n=
ight (Grid Fructuetion and Gen failed to start // Grid Restored)","joelle.e=
kessi@ihstowers.com","18847","28-08-2024 03:55:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0002942248","A=
FEME NORD","IHS_YND_808","28-08-2024 03:07:25","28-08-2024 02:44:19","28-08=
-2024 04:10:38","site went down because the Grid contactor Dysfuntionning /=
/ He bypass the Grid contactor and site on Grid ","TIENTCHEU NZETCHIEU GAEL=
","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","site went d=
own because the Grid contactor Dysfuntionning // He bypass the Grid contact=
or and site on Grid ","joelle.ekessi@ihstowers.com","1386","28-08-2024 03:0=
7:25","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0002942215","Mba=
nkolo petit paris","","28-08-2024 02:58:54","28-08-2024 02:47:19","28-08-20=
24 04:06:04","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","site went down because the Grid contactor Dysfuntionni=
ng // He bypass the Grid contactor and site on Grid ","emmanuel.ghani@ihsto=
wers.com","2162","28-08-2024 02:58:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0002942037","G=
olf Quater","","28-08-2024 01:37:01","28-08-2024 01:32:57","28-08-2024 03:2=
9:30","ACTIVE //No Power issue on site Ubaie=3D53,5V site on Grid  The Tx F=
ME Eloumdou betrrand//693212405 from Huawei is informed","Mboua Thierry","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","ACTIVE //No Power issue on site Ubaie=3D53,5V site on Grid  The T=
x FME Eloumdou betrrand//693212405 from Huawei is informed","joelle.ekessi@=
ihstowers.com","244","28-08-2024 01:37:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002942017","N=
koabang2","","28-08-2024 01:23:38","27-08-2024 20:55:29","27-08-2024 21:00:=
52","No power issue on site ,site on Gen with Ubaie=3D53.5 V The TX FME Lio=
nel adjep//655184876//   Huawei is informed .Notice that disjonction in BTS=
 ocm  ","Mba Lazare Herve","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue on site ,site on Gen =
with Ubaie=3D53.5 V The TX FME Lionel adjep//655184876//   Huawei is inform=
ed .Notice that disjonction in BTS ocm  ","joelle.ekessi@ihstowers.com","16=
090","28-08-2024 01:23:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0002940622","M=
ontee-Jouvence-II","","27-08-2024 20:51:37","27-08-2024 20:06:26","27-08-20=
24 21:23:35","site went down because CB 63A disjuntecd in PWC//he reamed th=
e CB","Hyemafo Gildas","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Circuit Breaker Issue","site went down because CB 63A disjuntecd =
in PWC//he reamed the CB","adonis.defokoua@ihstowers.com","2711","27-08-202=
4 20:51:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002940348","O=
lembe-Terminus","","27-08-2024 20:08:25","27-08-2024 19:32:16","27-08-2024 =
21:12:08","No power issue on site U=3D53,5v site on grid Synphorien of huaw=
ei is informed","Fabrice Pouakam","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53=
,5v site on grid Synphorien of huawei is informed","adonis.defokoua@ihstowe=
rs.com","2169","27-08-2024 20:08:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0002940345","N=
komkana","","27-08-2024 20:07:20","27-08-2024 19:25:12","28-08-2024 07:37:1=
7","Grid outage No Space to deploy a MDG // Grid Restored","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage No Space=
 to deploy a MDG // Grid Restored","adonis.defokoua@ihstowers.com","2529","=
27-08-2024 20:07:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002939700","MEF=
OU ASSI","","27-08-2024 18:20:29","27-08-2024 14:01:21","27-08-2024 18:52:3=
6","grid fluctuation,main gen faulty//grid stabilized","Fanda Brice","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","grid fluctuati=
on,main gen faulty//grid stabilized","ange.kongo@ihstowers.com","15549","27=
-08-2024 18:20:29","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002939532","Nko=
g-Edzen","","27-08-2024 17:34:46","27-08-2024 17:21:39","27-08-2024 17:40:4=
0","site went down because CB 125A disjunted in Pwc//he reamed the CB","Par=
ker Tchoup","Equipment Repair","Passive","Control Panel","Power Cabinet - C=
ircuit Breaker Issue","site went down because CB 125A disjunted in Pwc//he =
reamed the CB","ange.kongo@ihstowers.com","787","27-08-2024 17:34:46","Sage=
mcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002939488","Mok=
olo Yaounde","","27-08-2024 17:23:52","27-08-2024 16:25:44","28-08-2024 01:=
26:51","site went down because insufficiency of rectifiers on site // site =
Stabilized(Rectifiers to be replaced)","","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","site went down because insufficiency of rectifi=
ers on site // site Stabilized(Rectifiers to be replaced)","ange.kongo@ihst=
owers.com","3489","27-08-2024 17:23:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002938726","MBALNGON=
G LYCEE","","27-08-2024 15:39:20","27-08-2024 15:31:04","27-08-2024 17:03:0=
6","Cascaded Incident from TTO2756773","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage,gen failed to start d=
ue to grid bad voltage,no rcp and poor battery backup//he bypassed grid and=
 started the gen","system","496","27-08-2024 15:39:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002938725","ELOUMDEM=
 CARRIERE","","27-08-2024 15:39:20","27-08-2024 15:31:04","27-08-2024 17:03=
:06","Cascaded Incident from TTO2756773","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage,gen failed to start=
 due to grid bad voltage,no rcp and poor battery backup//he bypassed grid a=
nd started the gen","system","496","27-08-2024 15:39:20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002938721","Aha=
la","IHS_YND_767, IHS_YND_765","27-08-2024 15:38:15","27-08-2024 15:31:04",=
"27-08-2024 17:03:06","grid outage,gen failed to start due to grid bad volt=
age,no rcp and poor battery backup//he bypassed grid and started the gen","=
Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","grid outage,gen failed to start due to grid bad voltage,no r=
cp and poor battery backup//he bypassed grid and started the gen","ange.kon=
go@ihstowers.com","431","27-08-2024 15:38:15","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0002938697","Feb=
e Village","","27-08-2024 15:32:01","27-08-2024 14:33:51","27-08-2024 15:53=
:43","grid outage,gen stopped with alarm high temp//he added water in radia=
tor","Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high =
temp//he added water in radiator","ange.kongo@ihstowers.com","3491","27-08-=
2024 15:32:01","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0002938693","MVA=
N SACEL","","27-08-2024 15:31:05","27-08-2024 14:20:56","27-08-2024 17:00:0=
8","Grid outage,site went down before DG start: Poor Batteries Backup //Gri=
d return","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","Grid outage,site went down before DG start: Poor=
 Batteries Backup //Grid return","ange.kongo@ihstowers.com","4210","27-08-2=
024 15:31:05","Sagemcom CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0002938681","Mai=
son komkana New","","27-08-2024 15:30:04","27-08-2024 14:11:54","28-08-2024=
 08:47:07","Site went down due to inssufisancy of rectifier // He added 02 =
rectifier and site is on 03 Rectifier","Mboua Thierry","Equipment Repair","=
Passive","Rectifier","Rectifier Module","Site went down due to inssufisancy=
 of rectifier // He added 02 rectifier and site is on 03 Rectifier","ange.k=
ongo@ihstowers.com","4690","27-08-2024 15:30:04","Sagemcom CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0002938679","Imm=
-Olympique","","27-08-2024 15:29:09","27-08-2024 14:10:01","27-08-2024 17:3=
8:15","grid outage,site went down because cable of gen theft//he started th=
e gen with another cable","Paul BIBOUM","Site Asset Theft","Theft","Theft",=
"AC Cable Stolen","grid outage,site went down because cable of gen theft//h=
e started the gen with another cable","ange.kongo@ihstowers.com","4749","27=
-08-2024 15:29:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_286","IHS_YND_381","NOCINC0002938428","B=
oumnyebel","","27-08-2024 15:05:51","27-08-2024 14:59:43","27-08-2024 15:38=
:43","grid bad voltages,site went done because the fuse of relay 220V fault=
y,no rcp and gen failed to start//he did a  bridge and gen manually started=
","Kemeni Franklin","Equipment Repair","Passive","Control Panel","Relay","g=
rid bad voltages,site went done because the fuse of relay 220V faulty,no rc=
p and gen failed to start//he did a  bridge and gen manually started","adon=
is.defokoua@ihstowers.com","368","27-08-2024 15:05:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002938358","E=
lig-Edzoa","","27-08-2024 14:47:07","27-08-2024 13:53:00","27-08-2024 17:25=
:59","grid outage//grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","grid outage//grid return","dorothy.djantio@ihst=
owers.com","3248","27-08-2024 14:47:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0002938355","C=
NR","","27-08-2024 14:46:09","27-08-2024 13:34:02","27-08-2024 15:54:29","g=
rid outage,gen failed to start due to card Ge faulty//gen manually started"=
,"Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pa=
nel","grid outage,gen failed to start due to card Ge faulty//gen manually s=
tarted","dorothy.djantio@ihstowers.com","4327","27-08-2024 14:46:09","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0002938340","S=
imbock OCM","","27-08-2024 14:42:48","27-08-2024 13:20:41","27-08-2024 14:3=
9:22","grid bad voltage,no rcp on site and gen failed to start//grid stabil=
ized","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","grid bad voltage,no rcp on site and gen failed to sta=
rt//grid stabilized","dorothy.djantio@ihstowers.com","4928","27-08-2024 14:=
42:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0002938312","S=
apeur Mimboman","","27-08-2024 14:38:54","27-08-2024 13:18:45","27-08-2024 =
14:44:47","grid outage,gen failed to start due to card Ge faulty//Gen manua=
lly started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","AC=
DG - Control Panel","grid outage,gen failed to start due to card Ge faulty/=
/Gen manually started","dorothy.djantio@ihstowers.com","4809","27-08-2024 1=
4:38:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0002938310","A=
nguissa New","","27-08-2024 14:38:00","27-08-2024 12:52:53","27-08-2024 18:=
08:07","No power issue on site U=3D52v site on grid Eloundou of huawei is i=
nformed","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52v site on=
 grid Eloundou  of huawei is informed","dorothy.djantio@ihstowers.com","630=
9","27-08-2024 14:38:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0002938306","Y=
de-M-Central","","27-08-2024 14:37:05","27-08-2024 12:49:57","28-08-2024 08=
:33:46","Grid Outage No space to Deploy a MDG //Grid Restored","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Active// No powe=
r Issues on SIte , Site is on Grid and UBAIE=3D54.5V ,The FME TX  Brice Tsa=
gue (656925472) from Huawei is informed","dorothy.djantio@ihstowers.com","6=
428","27-08-2024 14:37:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002938099","E=
mana","","27-08-2024 14:08:18","27-08-2024 13:20:12","27-08-2024 14:56:13",=
"grid outage//grid return","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","grid outage//grid return","dorothy.djantio@ihstowers=
.com","2887","27-08-2024 14:08:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0002938072","Bastos B=
ethesda","","27-08-2024 14:02:30","27-08-2024 11:48:09","27-08-2024 12:49:0=
9","Cascaded Incident from TTO2755388","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site wentdown because the CB 63=
A who feed the bay oversized causing by load increase//he changed with anot=
her CB 125A","system","8061","27-08-2024 14:02:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_134","NOCINC0002938075","Vallee B=
astos MTN","","27-08-2024 14:02:30","27-08-2024 11:48:09","27-08-2024 12:49=
:09","Cascaded Incident from TTO2755388","Mboua Thierry","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site wentdown because the CB =
63A who feed the bay oversized causing by load increase//he changed with an=
other CB 125A","system","8061","27-08-2024 14:02:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0002938070","H-Franco=
 New","","27-08-2024 14:02:30","27-08-2024 11:48:09","27-08-2024 12:49:09",=
"Cascaded Incident from TTO2755388","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site wentdown because the CB 63A =
who feed the bay oversized causing by load increase//he changed with anothe=
r CB 125A","system","8061","27-08-2024 14:02:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002938074","Sapeur",=
"","27-08-2024 14:02:30","27-08-2024 11:48:09","27-08-2024 12:49:09","Casca=
ded Incident from TTO2755388","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","site wentdown because the CB 63A who fee=
d the bay oversized causing by load increase//he changed with another CB 12=
5A","system","8061","27-08-2024 14:02:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0002938073","POLYCLIN=
IQUE TSINGA","","27-08-2024 14:02:30","27-08-2024 11:48:09","27-08-2024 12:=
49:09","Cascaded Incident from TTO2755388","Mboua Thierry","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site wentdown because the C=
B 63A who feed the bay oversized causing by load increase//he changed with =
another CB 125A","system","8061","27-08-2024 14:02:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_084","NOCINC0002938071","Briquett=
erie","","27-08-2024 14:02:30","27-08-2024 11:48:09","27-08-2024 12:49:09",=
"Cascaded Incident from TTO2755388","","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","site wentdown because the CB 63A who feed the b=
ay oversized causing by load increase//he changed with another CB 125A","sy=
stem","8061","27-08-2024 14:02:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0002937992","M=
essassi","","27-08-2024 13:47:03","27-08-2024 13:38:54","27-08-2024 13:50:1=
2","No power issue site on grid with U=3D54v Yvan(679375329) from ZTE is wo=
rking on site ","Fabrice Pouakam","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid w=
ith U=3D54v Yvan(679375329) from ZTE is working on site ","dorothy.djantio@=
ihstowers.com","489","27-08-2024 13:47:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0002937792","L=
abogenie","","27-08-2024 13:38:34","27-08-2024 13:34:27","27-08-2024 14:26:=
04","Grid outage.no space to deploy mobile gen//grid power return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.=
no space to deploy mobile gen//grid power return","dorothy.djantio@ihstower=
s.com","247","27-08-2024 13:38:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0002937476","E=
mombo 2","","27-08-2024 12:59:50","27-08-2024 12:53:42","27-08-2024 12:55:0=
0","No power issue site on grid with U=3D53,7v TEAM Olivier Virgile ( 67726=
9888) from ZTE is working on site","MINKA NICOLAS","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue site on grid with U=3D53,7v TEAM Olivier Virgile ( 677269888) from ZTE i=
s working on site","dorothy.djantio@ihstowers.com","368","27-08-2024 12:59:=
50","Sagemcom CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0002937472","Hot=
el de Ville Yde","IHS_YND_711, IHS_YND_084, IHS_YND_563, IHS_YND_086, IHS_Y=
ND_029, IHS_YND_134","27-08-2024 12:58:51","27-08-2024 11:48:09","27-08-202=
4 12:49:09","site went down because the CB 63A who feed the bay oversized c=
ausing by load increase//he changed with another CB 125A","Paul BIBOUM","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker =
Issue","site went down because the CB 63A who feed the bay oversized causin=
g by load increase//he changed with another CB 125A","olivier.kwedi@ihstowe=
rs.com","4243","27-08-2024 12:58:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0002937334","M=
aison-Blanche-IHS","","27-08-2024 12:40:33","27-08-2024 12:21:28","27-08-20=
24 12:30:19","Active// Active: No power issue, site is on Grid with Ubaie=
=3D54The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active// Active: No power issue, site is on Grid with Ubaie=3D54The tx =
Fme Hosiah (6 74 00 74 38) from Huawei is informed","dorothy.djantio@ihstow=
ers.com","1145","27-08-2024 12:40:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0002936985","Lobo OCM=
","","27-08-2024 11:48:10","27-08-2024 11:41:46","27-08-2024 11:46:40","Cas=
caded Incident from TTO2754854","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before Gen start due to poor battery backup // Gen start automatically","s=
ystem","384","27-08-2024 11:48:10","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002936978","N=
KOMEKUI OCM","IHS_YND_341","27-08-2024 11:47:03","27-08-2024 11:41:46","27-=
08-2024 11:46:40","Grid outage, site went down before Gen start due to poor=
 battery backup // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, site went down before Gen start due to poor battery backup // Gen=
 start automatically","dorothy.djantio@ihstowers.com","318","27-08-2024 11:=
47:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_014","IHS_YND_003","NOCINC0002936930","M=
ercure","","27-08-2024 11:39:04","27-08-2024 11:14:34","27-08-2024 13:15:49=
","No power issue site on grid with U=3D53.5v Clovis (650031080) from ZTE i=
s working on site","","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.5=
v Clovis (650031080) from ZTE is working on site","dorothy.djantio@ihstower=
s.com","1470","27-08-2024 11:39:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0002936690","N=
kozoa","","27-08-2024 10:55:04","27-08-2024 10:41:00","27-08-2024 12:59:20"=
,"No power issue site on grid with U=3D54v Cambelle(67657540) from ZTE is w=
orking on site ","Fabrice Pouakam","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D54v Cambelle(67657540) from ZTE is working on site ","dorothy.djan=
tio@ihstowers.com","845","27-08-2024 10:55:04","Sagemcom CMR"
"Closed Complete","Warning","T0527","IHS_YND_019","NOCINC0002936615","Hotel=
 de Ville Yde","","27-08-2024 10:39:34","","","site on alrm due to grid out=
age//alarm cleared","Paul BIBOUM","Warning","Warning","POWER","Warning - Si=
te on Battery","site on alrm due to grid outage//alarm cleared","ludivine.n=
gamaleu@ihstowers.com","2","27-08-2024 10:39:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0002936578","M=
vog-Betsi","","27-08-2024 10:31:22","27-08-2024 10:27:16","27-08-2024 10:30=
:17","No ppower issue site on gen with U=3D52v Mohamadou(691144435) from Hu=
awei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No ppower issue site on gen =
with U=3D52v Mohamadou(691144435) from Huawei is informed","dorothy.djantio=
@ihstowers.com","246","27-08-2024 10:31:22","Sagemcom CMR"
"Closed Complete","Warning","T0920","IHS_YND_416","NOCINC0002936402","Ngwop=
i Boga","","27-08-2024 10:08:28","","","Grid outage, site went alarm becaus=
e gen ran untill fuel shortage // refueling done","Kemeni Franklin","Warnin=
g","Warning","DIESEL","Warning - Low Fuel Level","Grid outage, site went al=
arm because gen ran untill fuel shortage // refueling done","ludivine.ngama=
leu@ihstowers.com","9","27-08-2024 10:08:28","Sagemcom CMR"
"Closed Complete","Warning","CTR_234","IHS_YND_415","NOCINC0002936392","Bog=
a-Mahole","","27-08-2024 10:07:16","","","Grid outage, site went alarm beca=
use gen ran untill fuel shortage // refueling done","Kemeni Franklin","Warn=
ing","Warning","DIESEL","Warning - Low Fuel Level","Grid outage, site went =
alarm because gen ran untill fuel shortage // refueling done","ludivine.nga=
maleu@ihstowers.com","1","27-08-2024 10:07:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0002936290","Lobo OCM=
","","27-08-2024 09:45:00","27-08-2024 09:36:49","27-08-2024 09:42:46","Cas=
caded Incident from TTO2754052","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site down beca=
use Gen failed due to poor backup before gen start//Gen started manually","=
system","491","27-08-2024 09:45:00","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002936283","N=
KOMEKUI OCM","IHS_YND_341","27-08-2024 09:42:53","27-08-2024 09:36:49","27-=
08-2024 09:42:46","Grid outage, site down because Gen failed due to poor ba=
ckup before gen start//Gen started manually","TIENTCHEU NZETCHIEU GAEL","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gr=
id outage, site down because Gen failed due to poor backup before gen start=
//Gen started manually","dorothy.djantio@ihstowers.com","364","27-08-2024 0=
9:42:53","Sagemcom CMR"
"Cancelled","Warning","CTR_227","IHS_YND_341","NOCINC0002936276","Lobo OCM"=
,"","27-08-2024 09:41:53","","","","TIENTCHEU NZETCHIEU GAEL","","","","","=
","dorothy.djantio@ihstowers.com","303","27-08-2024 09:41:53","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0002936262","E=
toudi","","27-08-2024 09:40:27","27-08-2024 09:39:23","27-08-2024 09:50:15"=
,"Grid fluctuation, site down because GEN failed to start due to bad bad vo=
ltage// Grid Stabilized","Fabrice Pouakam","Grid Supply","Passive","Grid","=
National Grid - Phase Controller Faulty","Grid fluctuation, site down becau=
se GEN failed to start due to bad grid voltage// Grid Stabilized","dorothy.=
djantio@ihstowers.com","65","27-08-2024 09:40:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002936250","M=
imboman-Village","","27-08-2024 09:39:33","27-08-2024 09:35:28","27-08-2024=
 09:37:13","Active: no power issue, site is on grid with Ubaie=3D54V, Eloun=
dou (693212405) from Huawei is informed","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: no power issue, site is on grid with Ubaie=3D54V, Eloundou (693212405)=
 from Huawei is informed","dorothy.djantio@ihstowers.com","245","27-08-2024=
 09:39:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0002936246","M=
IMBOMAN LIBERTE","","27-08-2024 09:38:31","27-08-2024 09:33:27","27-08-2024=
 10:33:27","site went down because main gen faulty//he MDG of 15kva has dep=
loyed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - G=
enerator Faulty","site went down because main gen faulty//he MDG of 15kva h=
as deployed","dorothy.djantio@ihstowers.com","305","27-08-2024 09:38:31","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_632","IHS_YND_721","NOCINC0002936239","V=
OIRIE MUNICIPALE YAOUNDE","","27-08-2024 09:37:42","27-08-2024 09:32:37","2=
7-08-2024 09:35:02","No power issue site on Grid with U=3D54.1V  The Rm (Al=
ain) (691144423) from Huawei is informed","Paul BIBOUM","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on Grid with U=3D54.1V  The Rm (Alain) (691144423) from Huawei=
 is informed","dorothy.djantio@ihstowers.com","306","27-08-2024 09:37:42","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002936230","N=
kolo II New","","27-08-2024 09:35:49","27-08-2024 09:25:59","27-08-2024 09:=
27:09","Active// No power issue, site is on Grid with Ubaie=3D51.4V, Leonel=
 Ajet  (694693436) from Huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power issue, site is on Grid with Ubaie=3D51.4V, Leonel Ajet  (=
694693436) from Huawei is informed","dorothy.djantio@ihstowers.com","590","=
27-08-2024 09:35:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0002935957","MONTEE N=
KONDENGUI","","27-08-2024 08:46:30","27-08-2024 08:44:41","27-08-2024 09:31=
:50","Cascaded Incident from TTO2753696","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid Bad voltage site went do=
wn due to Lack of 1 Phase // he make the bridge on the Good Phase","system"=
,"109","27-08-2024 08:46:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0002935952","M=
obil-Kondengui","IHS_YND_682","27-08-2024 08:45:49","27-08-2024 08:44:41","=
27-08-2024 09:31:50","Grid Bad voltage site went down due to Lack of 1 Phas=
e // he make the bridge on the Good Phase","","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","Grid Bad voltage site went dow=
n due to Lack of 1 Phase // he make the bridge on the Good Phase","dorothy.=
djantio@ihstowers.com","68","27-08-2024 08:45:49","Sagemcom CMR"
"Closed Complete","Warning","T0870","IHS_YND_444","NOCINC0002935686","Dong"=
,"","27-08-2024 07:42:46","","","Site alarming du to  work /The fme Ulrich =
/656072680/ is working on site (PM) //End of work  And alarm cleared","Park=
er Tchoup","Warning","Warning","POWER","Warning - Site on Battery","Site al=
arming du to  work /The fme Ulrich /656072680/ is working on site (PM) //En=
d of work  And alarm cleared","ludivine.ngamaleu@ihstowers.com","1","27-08-=
2024 07:42:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0002935381","M=
vog-Ada_OCM","","27-08-2024 06:32:30","27-08-2024 06:02:24","27-08-2024 12:=
20:03","No power issue site on Grid with U=3D53.1V  The Rm (Alain) (6911444=
23) from Huawei is informed","","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on Grid wit=
h U=3D53.1V  The Rm (Alain) (691144423) from Huawei is informed","dorothy.d=
jantio@ihstowers.com","1807","27-08-2024 06:32:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002935256","E=
mana","","27-08-2024 05:43:59","27-08-2024 02:46:53","27-08-2024 05:38:59",=
"Grid outage//MDG of 20kva has deployed,","","Grid Supply","Passive","Grid"=
,"National Grid - Grid Outage Issue","Grid outage//MDG of 20kva has deploye=
d,","landry.etame@ihstowers.com","10627","27-08-2024 05:43:59","Sagemcom CM=
R"
"Closed Complete","Site Down","T0922","IHS_YND_349","NOCINC0002935228","Nko=
ngtock","","27-08-2024 05:35:24","27-08-2024 05:28:16","27-08-2024 06:37:24=
","Site went down Gen ran till fuel shortage//Refueling (ongoing)","Kemeni =
Franklin","Fuel Outage","Passive","Diesel","Diesel Outage","Site went down =
Gen ran till fuel shortage//Refueling (ongoing)","kouoh.jean@ihstowers.com"=
,"428","27-08-2024 05:35:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0002934794","Abattoir=
","","27-08-2024 03:11:31","27-08-2024 03:05:51","27-08-2024 04:29:51","Cas=
caded Incident from TTO2752361","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because Gen failed to=
 start due to due to lack on 02 phases on site //he bypassed Grid and start=
ed the Gen Manually","system","340","27-08-2024 03:11:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0002934795","ETOUDI C=
HAPELLE","","27-08-2024 03:11:31","27-08-2024 03:05:51","27-08-2024 04:29:5=
1","Cascaded Incident from TTO2752361","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","site went down because Gen fai=
led to start due to due to lack on 02 phases on site //he bypassed Grid and=
 started the Gen Manually","system","340","27-08-2024 03:11:31","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0002934796","Etoudi 2=
","","27-08-2024 03:11:31","27-08-2024 03:05:51","27-08-2024 04:29:51","Cas=
caded Incident from TTO2752361","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because Gen failed to=
 start due to due to lack on 02 phases on site //he bypassed Grid and start=
ed the Gen Manually","system","340","27-08-2024 03:11:31","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0002934793","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","27-08-2024 03:09:00","27-08-2=
024 03:04:51","27-08-2024 04:29:51","site went down because Gen failed to s=
tart due to due to lack on 02 phases on site //he bypassed Grid and started=
 the Gen Manually","Fabrice Pouakam","Grid Supply","Passive","Grid","Nation=
al Grid - Phase Controller Faulty","site went down because Gen failed to st=
art due to due to lack on 02 phases on site //he bypassed Grid and started =
the Gen Manually","kouoh.jean@ihstowers.com","2599","27-08-2024 03:09:00","=
Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0002934668","Eko=
mbitie","","27-08-2024 02:19:29","27-08-2024 02:10:40","27-08-2024 03:39:48=
","Grid outage, site went down because gen stoppet with 'Low oil pressure' =
alarm // He added oil and manually start the gen","Fabrice Pouakam","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage, si=
te went down because gen stoppet with 'Low oil pressure' alarm // He added =
oil and manually start the gen","kouoh.jean@ihstowers.com","2494","27-08-20=
24 02:19:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_580","NOCINC0002934370","Marche O=
dza","","27-08-2024 00:21:00","27-08-2024 00:01:17","27-08-2024 00:05:32","=
Cascaded Incident from TTO2751860","Albran Byorel","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active// No power issue site on Grid w=
ith U=3D53,5 V The Fme Tx  Lionel Steeve /655184876 is informed,","system",=
"1183","27-08-2024 00:21:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0002934368","O=
dza","IHS_YND_254, IHS_YND_580","27-08-2024 00:20:24","27-08-2024 00:01:17"=
,"27-08-2024 01:05:22","Active// No power issue site on Grid with U=3D53,5 =
V The Fme Tx  Lionel Steeve /655184876 is informed,","Albran Byorel","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active// No power issue site on Grid with U=3D53,5 V The Fme Tx  Lion=
el Steeve /655184876 is informed,","landry.etame@ihstowers.com","1147","27-=
08-2024 00:20:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002934358","M=
vog-Manga","","27-08-2024 00:15:52","27-08-2024 00:01:17","27-08-2024 00:05=
:32","","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascade=
 Active","Active// No power issue site on Grid with U=3D53,5 V The Fme Tx  =
Lionel Steeve /655184876 is informed,","landry.etame@ihstowers.com","1229",=
"27-08-2024 00:15:52","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002933424","Tsi=
nga","","26-08-2024 21:35:45","26-08-2024 21:34:40","27-08-2024 00:00:24","=
site went down due to cables burned in Dxbox MTN // he cut the burnt cable =
, reconnected and  normalized cable , site on Grid ","Mboua Thierry","Equip=
ment Repair","Passive","Infrastructure","Armoured Cable","site went down du=
e to cables burned in Dxbox MTN // he cut the burnt cable , reconnected and=
  normalized cable , site on Grid ","emmanuel.ghani@ihstowers.com","65","26=
-08-2024 21:35:45","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002933118","Bas=
tos Amb Coree","","26-08-2024 20:56:10","26-08-2024 20:55:02","26-08-2024 2=
1:07:59","site went down due to insufficient of rectifier on site//site sta=
bilized","","Equipment Repair","Passive","Rectifier","Rectifier Module","si=
te went down due to insufficient of rectifier on site//site stabilized","em=
manuel.ghani@ihstowers.com","69","26-08-2024 20:56:10","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0002932812","MBI=
MBIM","","26-08-2024 19:44:55","26-08-2024 19:41:38","26-08-2024 21:52:28",=
"Solar GEN: Site down because water infiltration in the tank// He purged th=
e Gen, removed water and start Gen manualy","Parker Tchoup","Fuel Outage (P=
robable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","Sola=
r GEN: Site down because water infiltration in the tank// He purged the Gen=
, removed water and start Gen manualy","emmanuel.ghani@ihstowers.com","198"=
,"26-08-2024 19:44:55","Sagemcom CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0002932672","Mai=
son komkana New","","26-08-2024 19:32:54","26-08-2024 19:31:50","26-08-2024=
 19:33:50","site went down due to insufficient of rectifier on site//site s=
tabilized","Mboua Thierry","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","site went down due to insufficient of rectifier on site//site =
stabilized","emmanuel.ghani@ihstowers.com","64","26-08-2024 19:32:54","Sage=
mcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002932615","Mim=
boman3","","26-08-2024 19:18:08","26-08-2024 19:09:04","26-08-2024 19:19:04=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen start automatically","Mba Lazare Herve","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automatically","e=
mmanuel.ghani@ihstowers.com","544","26-08-2024 19:18:08","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002932556","Bas=
tos Amb Coree","","26-08-2024 18:57:44","26-08-2024 18:56:39","26-08-2024 1=
8:58:39","site went down due to insufficient of rectifier on site(2/4)//sit=
e stabilized","","Equipment Repair","Passive","Rectifier","Rectifier Module=
","site went down due to insufficient of rectifier on site(2/4)//site stabi=
lized","emmanuel.ghani@ihstowers.com","66","26-08-2024 18:57:44","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002931883","Yoko OCM=
","","26-08-2024 17:55:11","26-08-2024 17:46:50","26-08-2024 17:47:50","Cas=
caded Incident from TTO2749122","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site Ubaie 55.2V Site o=
n GE. FME TX_Abdouraman 657959647 is informed via Call","system","501","26-=
08-2024 17:55:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002931884","Ngouetou=
","","26-08-2024 17:55:11","26-08-2024 17:46:50","26-08-2024 17:47:50","Cas=
caded Incident from TTO2749122","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site Ubaie 55.2V Site o=
n GE. FME TX_Abdouraman 657959647 is informed via Call","system","501","26-=
08-2024 17:55:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002931882","Matsari"=
,"","26-08-2024 17:55:11","26-08-2024 17:46:50","26-08-2024 17:47:50","Casc=
aded Incident from TTO2749122","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site Ubaie 55.2V Site on=
 GE. FME TX_Abdouraman 657959647 is informed via Call","system","501","26-0=
8-2024 17:55:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002931881","Ngoum","=
","26-08-2024 17:55:11","26-08-2024 17:46:50","26-08-2024 17:47:50","Cascad=
ed Incident from TTO2749122","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site Ubaie 55.2V Site on G=
E. FME TX_Abdouraman 657959647 is informed via Call","system","501","26-08-=
2024 17:55:11","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002931732","Aka=
k-Nkozoa-MTN-IHS","","26-08-2024 17:36:24","26-08-2024 17:32:20","26-08-202=
4 18:57:46","grid outage,gen failed to start due to grid bad voltage,no rcp=
 //he bypassed grid and started the gen","Fabrice Pouakam","Grid Supply","P=
assive","Grid","National Grid - Phase Controller Faulty","grid outage,gen f=
ailed to start due to grid bad voltage,no rcp //he bypassed grid and starte=
d the gen","emmanuel.ghani@ihstowers.com","245","26-08-2024 17:36:24","Sage=
mcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0002931681","ODZ=
A CITE MBIA","","26-08-2024 17:32:26","26-08-2024 17:12:22","26-08-2024 18:=
48:03","site went down because gen ran till fuel shortage//Refueling done",=
"Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outage","site went=
 down because gen ran till fuel shortage//Refueling done","emmanuel.ghani@i=
hstowers.com","1205","26-08-2024 17:32:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0002931364","A=
nguissa New","","26-08-2024 16:42:23","26-08-2024 16:39:19","26-08-2024 17:=
31:54","No power issue on site U=3D54v site on grid team/CLIFFORT/652770944=
/ZTE working on site","MINKA NICOLAS","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54v site on grid team/CLIFFORT/652770944/ZTE working on site","joelle.ek=
essi@ihstowers.com","185","26-08-2024 16:42:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0002931356","V=
allee-Bastos OCM","","26-08-2024 16:41:00","26-08-2024 16:39:54","26-08-202=
4 17:08:45","grid outage,site went down because grid bad voltage//he did a =
bridge on good phase(site swapped by ZTE)","","Grid Supply","Passive","Grid=
","National Grid - Phase Controller Faulty","grid outage,site went down bec=
ause grid bad voltage//he did a bridge on good phase(site swapped by ZTE)",=
"joelle.ekessi@ihstowers.com","67","26-08-2024 16:41:00","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0002931340","NKO=
LOSSAN OKOK","","26-08-2024 16:34:34","26-08-2024 16:26:31","26-08-2024 17:=
23:53","site went down because gen ran till fuel shortage//Refueling done",=
"Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","site went=
 down because gen ran till fuel shortage//Refueling done","emmanuel.ghani@i=
hstowers.com","484","26-08-2024 16:34:34","Sagemcom CMR"
"Closed Complete","Site Down","T1317","IHS_YND_029","NOCINC0002929629","Sap=
eur","","26-08-2024 12:32:48","26-08-2024 12:26:39","26-08-2024 14:28:52","=
site went down because CB 80A disjuncted in Pwc causing by load increase//h=
e changed with another CB 125A","Mboua Thierry","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Circuit Breaker Issue","site went down b=
ecause CB 80A disjuncted in Pwc causing by load increase//he changed with a=
nother CB 125A","ange.kongo@ihstowers.com","370","26-08-2024 12:32:48","Sag=
emcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0002929621","Nom=
ayos montee Meche","","26-08-2024 12:30:44","26-08-2024 12:25:18","26-08-20=
24 18:32:37","Access issue due to landlord;site went down because Gen stopp=
ed due to noise by landlord//gen started","Fanda Brice","Access Denial","Le=
ase Or Legal","Landlord Related Issues","Access Issue - Land Lord","Access =
issue due to landlord;site went down because Gen stopped due to noise by la=
ndlord//gen started","ange.kongo@ihstowers.com","326","26-08-2024 12:30:44"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002929450","Aka=
k-Nkozoa-MTN-IHS","","26-08-2024 12:02:02","26-08-2024 11:48:54","26-08-202=
4 12:04:09","Grid fluctuation, gen failed to start due to grid bad voltage =
// he bypass grid and manually start the gen","Fabrice Pouakam","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctua=
tion, gen failed to start due to grid bad voltage // he bypass grid and man=
ually start the gen","ange.kongo@ihstowers.com","789","26-08-2024 12:02:02"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T2418","IHS_YND_730","NOCINC0002929162","Odz=
a petit marche new","","26-08-2024 11:42:54","26-08-2024 11:41:47","26-08-2=
024 12:07:26","Site went down because 1/4 rectifier faulty on site// Site s=
tabilized","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectif=
ier Module","Site went down because 1/4 rectifier faulty on site// Site sta=
bilized","ange.kongo@ihstowers.com","68","26-08-2024 11:42:54","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0002929031","Elig Edz=
oa","","26-08-2024 11:22:12","26-08-2024 07:21:59","26-08-2024 07:39:06","C=
ascaded Incident from TTO2744821","Delor Telezing","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue site on grid with U=3D5=
4v Brice Tsague(650514096) from Huawei is informed","system","14413","26-08=
-2024 11:22:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0002929030","Charles-=
Atangana","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:=
06","Cascaded Incident from TTO2744821","","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v Brice=
 Tsague(650514096) from Huawei is informed","system","14412","26-08-2024 11=
:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_731","NOCINC0002929023","UPAC LP"=
,"","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:06","Casc=
aded Incident from TTO2744821","","Cascade Outage","Active","Cascade Active=
","Cascade Active","No power issue site on grid with U=3D54v Brice Tsague(6=
50514096) from Huawei is informed","system","14412","26-08-2024 11:22:11","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0002929018","Mamch Bu=
ilding","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:06=
","Cascaded Incident from TTO2744821","Mboua Thierry","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D54v Brice Tsague(650514096) from Huawei is informed","system","14412","2=
6-08-2024 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0002929021","POLYCLIN=
IQUE TSINGA","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:=
39:06","Cascaded Incident from TTO2744821","Mboua Thierry","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue site on grid wi=
th U=3D54v Brice Tsague(650514096) from Huawei is informed","system","14412=
","26-08-2024 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002929024","Sapeur",=
"","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:06","Casca=
ded Incident from TTO2744821","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue site on grid with U=3D54v Br=
ice Tsague(650514096) from Huawei is informed","system","14412","26-08-2024=
 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0002929015","H-Franco=
 New","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:06",=
"Cascaded Incident from TTO2744821","Delor Telezing","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D54v Brice Tsague(650514096) from Huawei is informed","system","14412","2=
6-08-2024 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_084","NOCINC0002929016","Briquett=
erie","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:06",=
"Cascaded Incident from TTO2744821","","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue site on grid with U=3D54v Brice Tsa=
gue(650514096) from Huawei is informed","system","14412","26-08-2024 11:22:=
11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_091","NOCINC0002929019","Jouvence=
 2000","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:06"=
,"Cascaded Incident from TTO2744821","Delor Telezing","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D54v Brice Tsague(650514096) from Huawei is informed","system","14412","2=
6-08-2024 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0002929025","Garbati =
building","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:=
06","Cascaded Incident from TTO2744821","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue site on grid with=
 U=3D54v Brice Tsague(650514096) from Huawei is informed","system","14412",=
"26-08-2024 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_049","NOCINC0002929020","Etoa-Mek=
i","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:06","Ca=
scaded Incident from TTO2744821","Delor Telezing","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D54=
v Brice Tsague(650514096) from Huawei is informed","system","14412","26-08-=
2024 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_016","NOCINC0002929027","Maetur",=
"","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:06","Casca=
ded Incident from TTO2744821","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue site on grid with U=3D54v Br=
ice Tsague(650514096) from Huawei is informed","system","14412","26-08-2024=
 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0002929017","Bastos B=
ethesda","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:0=
6","Cascaded Incident from TTO2744821","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D54v Brice Tsague(650514096) from Huawei is informed","system","14412","2=
6-08-2024 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0002929026","ELIg-Ess=
ono","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:06","=
Cascaded Incident from TTO2744821","Delor Telezing","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
54v Brice Tsague(650514096) from Huawei is informed","system","14412","26-0=
8-2024 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0002929029","Hopital =
Central","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07:39:0=
6","Cascaded Incident from TTO2744821","","Cascade Outage","Active","Cascad=
e Active","Cascade Active","No power issue site on grid with U=3D54v Brice =
Tsague(650514096) from Huawei is informed","system","14412","26-08-2024 11:=
22:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0002929022","HOPITAL =
DE LA CAISSE","","26-08-2024 11:22:11","26-08-2024 07:21:59","26-08-2024 07=
:39:06","Cascaded Incident from TTO2744821","Delor Telezing","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue site on grid =
with U=3D54v Brice Tsague(650514096) from Huawei is informed","system","144=
12","26-08-2024 11:22:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0002928180","T=
ongolo OCM","","26-08-2024 08:30:09","26-08-2024 07:40:04","26-08-2024 07:4=
5:57","ACTIVE No power issue on site, site on Grid with Ubaie=3D54,3V Tx fm=
e Armand Ngeuts/699949553/ from Huawei is Informed  (Swapped by ZTE)","Delo=
r Telezing","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","ACTIVE No power issue on site, site on Grid with Ub=
aie=3D54,3V Tx fme Armand Ngeuts/699949553/ from Huawei is Informed  (Swapp=
ed by ZTE)","adonis.defokoua@ihstowers.com","3006","26-08-2024 08:30:09","S=
agemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0002928131","N=
dogbessol","","26-08-2024 08:26:18","26-08-2024 08:19:45","26-08-2024 08:25=
:58","Active// No power issue, site is on Battery with Ubaie=3D52,6V The TX=
 FME Etienne //695033981// from Huawei is informed","Kemeni Franklin","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue, site is on Battery with Ubaie=3D52,6V The T=
X FME Etienne //695033981// from Huawei is informed","adonis.defokoua@ihsto=
wers.com","393","26-08-2024 08:26:18","Sagemcom CMR"
"Closed Complete","Site Down","T2183","IHS_YND_089","NOCINC0002928129","H-P=
rince","","26-08-2024 08:26:10","26-08-2024 07:31:40","26-08-2024 08:33:01"=
,"Grid outage, site went down because gen ran untill fuel shortage // Refue=
ling done(Swapped by ZTE)","Mboua Thierry","Fuel Outage","Passive","Diesel"=
,"Diesel Outage","Grid outage, site went down because gen ran untill fuel s=
hortage // Refueling done(Swapped by ZTE)","ange.kongo@ihstowers.com","3435=
","26-08-2024 08:26:10","Sagemcom CMR"
"Closed Complete","Site Down","T0527","IHS_YND_019","NOCINC0002927924","Hot=
el de Ville Yde","IHS_YND_711, IHS_YND_084, IHS_YND_563, IHS_YND_051, IHS_Y=
ND_091, IHS_YND_049, IHS_YND_086, IHS_YND_064, IHS_YND_731, IHS_YND_029, IH=
S_YND_024, IHS_YND_014, IHS_YND_016, IHS_DLA_174, IHS_YND_027, IHS_YND_125,=
 IHS_YND_504","26-08-2024 07:31:50","26-08-2024 07:21:59","26-08-2024 07:39=
:06","No power issue site on grid with U=3D54v Brice Tsague(650514096) from=
 Huawei is informed","Paul BIBOUM","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D54v Brice Tsague(650514096) from Huawei is informed","ange.kongo@i=
hstowers.com","591","26-08-2024 07:31:50","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0002927816","MBI=
MBIM","","26-08-2024 07:06:27","26-08-2024 06:56:59","26-08-2024 17:47:50",=
"Solar GEN: Site down because water infiltration in the tank// He purged th=
e Gen, removed water and start Gen manualy","Parker Tchoup","Fuel Outage (P=
robable)","Passive","Diesel","Tank Sealing Issue - Water In The Fuel","Sola=
r GEN: Site down because water infiltration in the tank// He purged the Gen=
, removed water and start Gen manualy","ange.kongo@ihstowers.com","569","26=
-08-2024 07:06:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0002927800","T=
SINGA VILLAGE 2","","26-08-2024 07:03:37","26-08-2024 05:45:30","26-08-2024=
 06:41:04","Site went Down because Gen failed to start due to Hybrid system=
 dysfonction// He reset the Gen card  and Gen manually started (Swapped by =
ZTE)","Delor Telezing","Equipment Repair","Passive","Hybrid","Hybrid Module=
","Site went Down because Gen failed to start due to Hybrid system dysfonct=
ion// He reset the Gen card  and Gen manually started (Swapped by ZTE)","ad=
onis.defokoua@ihstowers.com","4688","26-08-2024 07:03:37","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002927026","Nko=
g-Edzen","","26-08-2024 04:20:39","26-08-2024 03:32:13","26-08-2024 03:40:0=
5","ACTIVE// No power issue: Ubaie=3D53V site on Battery The Tx Fme Gregoir=
e( 652070658)from Huawei is informed","Parker Tchoup","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// =
No power issue: Ubaie=3D53V site on Battery The Tx Fme Gregoire( 652070658)=
from Huawei is informed","stephane.nkamwa@ihstowers.com","2907","26-08-2024=
 04:20:39","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0002924236","ODZ=
A CITE MBIA","","25-08-2024 18:56:05","25-08-2024 18:47:38","25-08-2024 20:=
46:45","Access issue due to landloard Grid outage, site went down because g=
en ran untill fuel shortage // refueling done","Albran Byorel","Fuel Outage=
","Passive","Diesel","Diesel Outage","Access issue due to landloard Grid ou=
tage, site went down because gen ran untill fuel shortage // refueling done=
","kouoh.jean@ihstowers.com","508","25-08-2024 18:56:05","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0002924055","Nko=
mo stade","","25-08-2024 18:18:39","25-08-2024 18:09:34","25-08-2024 18:27:=
18","Site went down due to one rectifier dysfunctioning//Site up ,rectifier=
s must be upgraded.","Mba Lazare Herve","Equipment Repair","Passive","Recti=
fier","Rectifier Module","Site went down due to one rectifier dysfunctionin=
g//Site up ,rectifiers must be upgraded.","kouoh.jean@ihstowers.com","545",=
"25-08-2024 18:18:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002923698","MBIMBIM"=
,"","25-08-2024 16:54:41","25-08-2024 16:44:27","25-08-2024 16:45:10","Casc=
aded Incident from TTO2740118","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","system"=
,"614","25-08-2024 16:54:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002923695","Yoko OCM=
","","25-08-2024 16:54:40","25-08-2024 16:44:27","25-08-2024 16:45:10","Cas=
caded Incident from TTO2740118","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","system=
","613","25-08-2024 16:54:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002923694","Matsari"=
,"","25-08-2024 16:54:40","25-08-2024 16:44:27","25-08-2024 16:45:10","Casc=
aded Incident from TTO2740118","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 53V. TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","system"=
,"613","25-08-2024 16:54:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002923693","Ngoum","=
","25-08-2024 16:54:40","25-08-2024 16:44:27","25-08-2024 16:45:10","Cascad=
ed Incident from TTO2740118","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 53V. TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","system","=
613","25-08-2024 16:54:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002923696","Ngouetou=
","","25-08-2024 16:54:40","25-08-2024 16:44:27","25-08-2024 16:45:10","Cas=
caded Incident from TTO2740118","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 53V. TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","system=
","613","25-08-2024 16:54:40","Sagemcom CMR"
"Closed Complete","Site Down","T2563","IHS_YND_748","NOCINC0002922875","Nko=
abang Alembe","","25-08-2024 14:34:20","25-08-2024 14:12:12","25-08-2024 14=
:47:22","Tx Issue:Site on grid,Ubaie:54.2V; Lionel Adjep/655-18-48-76 is in=
formed.","Mba Lazare Herve","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","Tx Issue:Site on grid,Ubaie:54.2V; =
Lionel Adjep/655-18-48-76 is informed.","kouoh.jean@ihstowers.com","1329","=
25-08-2024 14:34:20","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0002922150","Com=
plex Beac II","","25-08-2024 13:13:39","25-08-2024 13:09:26","25-08-2024 13=
:31:03","grid outage,gen failed to start due to card Ge faulty//Gen manuall=
y started","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","grid outage,gen failed to start due to card Ge faulty//Gen =
manually started","emmanuel.ghani@ihstowers.com","254","25-08-2024 13:13:39=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002922051","E=
lig-Edzoa","","25-08-2024 12:55:41","25-08-2024 12:04:36","25-08-2024 12:05=
:47","No power issue on site U=3D54v site on grid Armand of huawei is infor=
med (Site Swapped by ZTE)","","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v si=
te on grid Armand of huawei is informed (Site Swapped by ZTE)","joelle.ekes=
si@ihstowers.com","3066","25-08-2024 12:55:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002921887","C=
arington","","25-08-2024 12:27:32","25-08-2024 08:52:52","25-08-2024 11:53:=
47","grid outage//MDG 20kva deployed(site swapped by ZTE)","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","grid outage//MDG 20k=
va deployed(site swapped by ZTE)","kombi.samuel@ihstowers.com","12881","25-=
08-2024 12:27:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002921441","MBIMBIM"=
,"","25-08-2024 11:55:21","25-08-2024 11:34:53","25-08-2024 13:12:53","Casc=
aded Incident from TTO2737701","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 51.2V. TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","syste=
m","1228","25-08-2024 11:55:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002921437","Matsari"=
,"","25-08-2024 11:55:20","25-08-2024 11:34:53","25-08-2024 13:12:53","Casc=
aded Incident from TTO2737701","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 51.2V. TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","syste=
m","1227","25-08-2024 11:55:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002921438","Yoko OCM=
","","25-08-2024 11:55:20","25-08-2024 11:34:53","25-08-2024 13:12:53","Cas=
caded Incident from TTO2737701","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 51.2V. TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","syst=
em","1227","25-08-2024 11:55:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002921436","Ngoum","=
","25-08-2024 11:55:20","25-08-2024 11:34:53","25-08-2024 13:12:53","Cascad=
ed Incident from TTO2737701","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 51.2V. TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","system"=
,"1227","25-08-2024 11:55:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002921439","Ngouetou=
","","25-08-2024 11:55:20","25-08-2024 11:34:53","25-08-2024 13:12:53","Cas=
caded Incident from TTO2737701","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 51.2V. TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","syst=
em","1227","25-08-2024 11:55:20","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0002921189","Mes=
sassi Carrefourt","","25-08-2024 11:17:08","25-08-2024 11:07:05","25-08-202=
4 11:48:58","site went down because gen failed to start due to no automatis=
m//Gen manually started","Delor Telezing","Equipment Repair","Passive","Con=
trol Panel","ATS-AMF Issue","site went down because gen failed to start due=
 to no automatism//Gen manually started","emmanuel.ghani@ihstowers.com","60=
3","25-08-2024 11:17:08","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002920755","Aka=
k-Nkozoa-MTN-IHS","","25-08-2024 10:00:47","25-08-2024 09:51:37","25-08-202=
4 11:10:25","Grid outage, site went down because gen ran until fuel shortag=
e // refueling done     ( Site Swapped by ZTE)","Fabrice Pouakam","Fuel Out=
age","Passive","Diesel","Diesel Outage","Grid outage, site went down becaus=
e gen ran until fuel shortage // refueling done     ( Site Swapped by ZTE)"=
,"emmanuel.ghani@ihstowers.com","2570","25-08-2024 10:00:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002920659","O=
lembe-Terminus","","25-08-2024 09:47:17","25-08-2024 08:57:53","25-08-2024 =
09:50:32","No power issue on site ,Site on Grid with Ubaie=3D53,3 V  The TX=
 FME Synphorien //691316854// from Huawei is informed(Site Swapped by ZTE)"=
,"Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue on site ,Site on Grid with Ub=
aie=3D53,3 V  The TX FME Synphorien //691316854// from Huawei is informed(S=
ite Swapped by ZTE)","kombi.samuel@ihstowers.com","2965","25-08-2024 09:47:=
17","Sagemcom CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0002920571","Mba=
nkomo CAF","","25-08-2024 09:34:21","25-08-2024 09:25:15","25-08-2024 10:07=
:37"," Grid outage,gen ran till fuel shortage//Grid power return(refueling =
ongoing)","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage"," =
Grid outage,gen ran till fuel shortage//Grid power return(refueling ongoing=
)","emmanuel.ghani@ihstowers.com","546","25-08-2024 09:34:21","Sagemcom CMR=
"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002920201","Jou=
vence 2000","","25-08-2024 08:39:47","25-08-2024 08:33:44","25-08-2024 10:2=
0:26","Grid outage, site down because Gen failed due to poor backup before =
gen start//Gen started manually","Delor Telezing","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site down b=
ecause Gen failed due to poor backup before gen start//Gen started manually=
","emmanuel.ghani@ihstowers.com","363","25-08-2024 08:39:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0002919296","M=
anguier","","25-08-2024 04:57:18","25-08-2024 03:31:05","25-08-2024 04:37:3=
7","Grid outage, site went down because gen ran until fuel shortage // refu=
ling done ( Site Swapped by ZTE)","Fabrice Pouakam","Fuel Outage","Passive"=
,"Diesel","Diesel Outage","Grid outage, site went down because gen ran unti=
l fuel shortage // refuling done ( Site Swapped by ZTE)","etienne.itondo@ih=
stowers.com","5173","25-08-2024 04:57:18","Sagemcom CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0002919244","NKO=
ABANG NKOLO 3","","25-08-2024 04:17:17","25-08-2024 03:38:03","25-08-2024 0=
5:40:46","Grid outage site went down because the Cb(10A) of Gen dysjoncted =
due to dysfonction of rectifier// He reamed the CB of Gen and cancel the re=
ctifier which malfunctions","Mba Lazare Herve","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Load Breaker","Grid outage site went down because the C=
b(10A) of Gen dysjoncted due to dysfonction of rectifier// He reamed the CB=
 of Gen and cancel the rectifier which malfunctions","etienne.itondo@ihstow=
ers.com","2355","25-08-2024 04:17:17","Sagemcom CMR"
"Closed Complete","Site Down","T0467","IHS_YND_077","NOCINC0002918928","Obi=
li Carrefour","","25-08-2024 01:15:52","25-08-2024 01:11:03","25-08-2024 07=
:50:49","Site went down due to work / SS IHS Patrick ESSA /657108540/ is wo=
rking on site (swap baie) //End of Work","Paul BIBOUM","Installation Activi=
ty","Passive","Planned Activity","Installation Activity","Site went down du=
e to work / SS IHS Patrick ESSA /657108540/ is working on site (swap baie) =
//End of Work","olivier.kwedi@ihstowers.com","13690","25-08-2024 01:15:52",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002918653","Nko=
abang Ebolmedjock","","24-08-2024 23:42:34","24-08-2024 23:22:19","24-08-20=
24 23:44:36","Grid outage, site went down because gen start and stopped due=
 to gen Overload (09Kva, 120A) // He reduice the load on site and manually =
start the gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Overload","Grid outage, site went down because gen start and stopped=
 due to gen Overload (09Kva, 120A) // He reduice the load on site and manua=
lly start the gen","olivier.kwedi@ihstowers.com","1216","24-08-2024 23:42:3=
4","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002918650","Lad=
a I Yde","","24-08-2024 23:41:28","24-08-2024 23:01:07","25-08-2024 00:03:0=
8","Grid outage, site went down because gen start and stopped due to gen Ov=
erload (09Kva, 120A) // He reduice the load on site and manually start the =
gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, site went down because gen start and stopped due to ge=
n Overload (09Kva, 120A) // He reduice the load on site and manually start =
the gen","olivier.kwedi@ihstowers.com","2421","24-08-2024 23:41:28","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002917722","O=
lembe-Terminus","","24-08-2024 20:32:20","24-08-2024 19:55:12","24-08-2024 =
20:00:54","No power issue on site ,Site on Grid with Ubaie=3D53,3 V  The TX=
 FME Synphorien //691316854// from Huawei is informed(Site Swapped by ZTE)"=
,"Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","No power issue on site ,Site on Grid with Ub=
aie=3D53,3 V  The TX FME Synphorien //691316854// from Huawei is informed(S=
ite Swapped by ZTE)","alexandre.kamal@ihstowers.com","2228","24-08-2024 20:=
32:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0002917602","M=
ambine","","24-08-2024 20:05:53","24-08-2024 19:56:24","24-08-2024 20:49:54=
","Grid Hybrid Gen Site ,site went down due to hybrid system disfunctionnin=
g//Gen manually started","Fanda Brice","Equipment Repair","Passive","Hybrid=
","Hybrid Module","Grid Hybrid Gen Site ,site went down due to hybrid syste=
m disfunctionning//Gen manually started","alexandre.kamal@ihstowers.com","5=
70","24-08-2024 20:05:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0002916847","B=
riqueterie","","24-08-2024 17:07:31","24-08-2024 11:14:24","24-08-2024 15:2=
0:48","site went down due to CB 125A disjuncted in Pwc causing by load of i=
ncrease// he Reamed the CB","","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Circuit Breaker Issue","site went down due to CB 125A dis=
juncted in Pwc causing by load of increase// he Reamed the CB","alexandre.k=
amal@ihstowers.com","21187","24-08-2024 17:07:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0002916734","M=
om","","24-08-2024 16:49:21","24-08-2024 16:46:00","24-08-2024 20:03:25","G=
rid outage ,Site went down because Main Gen faulty//Grid power return","Fan=
da Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty"=
,"Grid outage ,Site went down because Main Gen faulty//Grid power return","=
alexandre.kamal@ihstowers.com","201","24-08-2024 16:49:21","Sagemcom CMR"
"Closed Complete","Site Down","T1737","IHS_YND_005","NOCINC0002913576","Imm=
-Olympique","","24-08-2024 11:41:13","24-08-2024 11:27:06","24-08-2024 11:5=
3:06","site went down due to power cable Gen theft//he started the gen with=
 another power cable","Paul BIBOUM","Site Asset Theft","Theft","Theft","AC =
Cable Stolen","site went down due to power cable Gen theft//he started the =
gen with another power cable","kouoh.jean@ihstowers.com","848","24-08-2024 =
11:41:13","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002913417","Eko=
unou","","24-08-2024 11:09:07","24-08-2024 11:02:57","24-08-2024 11:14:57",=
"Grid outage, site wen down because gen failed to start due to poor battery=
 backup // Gen start automatically","Albran Byorel","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen =
down because gen failed to start due to poor battery backup // Gen start au=
tomatically","kouoh.jean@ihstowers.com","370","24-08-2024 11:09:07","Sagemc=
om CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002913369","Aka=
k-Nkozoa-MTN-IHS","","24-08-2024 10:55:51","24-08-2024 10:45:17","24-08-202=
4 11:34:18","site went down due to CB 125 A who feed equipment MTN disjunct=
ed //he did a bridge with CB 80A","Fabrice Pouakam","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went do=
wn due to CB 125 A who feed equipment MTN disjuncted //he did a bridge with=
 CB 80A","kouoh.jean@ihstowers.com","635","24-08-2024 10:55:51","Sagemcom C=
MR"
"Closed Complete","Site Down","T0573","IHS_YND_387","NOCINC0002913338","Tal=
la Monatele","","24-08-2024 10:46:45","24-08-2024 09:51:38","24-08-2024 10:=
15:51","grid outage,gen failed to start due to battery Ge faulty//he starte=
d the gen with battery backup","Parker Tchoup","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Generator Battery","grid outage,gen failed to start due=
 to battery Ge faulty//he started the gen with battery backup","kouoh.jean@=
ihstowers.com","3308","24-08-2024 10:46:45","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002912620","Ess=
os Marche","","24-08-2024 08:20:27","24-08-2024 08:12:23","24-08-2024 09:48=
:53","No power issue on site U=3D54,4v site on grid Armand of huawei is inf=
ormed","Delor Telezing","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,4v site o=
n grid Armand of huawei is informed","kouoh.jean@ihstowers.com","485","24-0=
8-2024 08:20:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_160","NOCINC0002912121","Complex =
Beac II","","24-08-2024 05:52:54","24-08-2024 05:51:29","24-08-2024 06:10:5=
6","Grid outage,gen failed to start due to card GE faulty// we reset card G=
E and gen manually started.","Albran Byorel","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due to ca=
rd GE faulty// we reset card GE and gen manually started.","ange.kongo@ihst=
owers.com","85","24-08-2024 05:52:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0002911759","Nkolfon =
Cimencam","","24-08-2024 03:28:33","24-08-2024 03:15:17","24-08-2024 04:15:=
00","Site went down because gen failed to start due  battery GEN faulty//GE=
N manually started with external battery (Swapped by ZTE)","Hyemafo Gildas"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Site w=
ent down because gen failed to start due  battery GEN faulty//GEN manually =
started with external battery (Swapped by ZTE)","ange.kongo@ihstowers.com",=
"796","24-08-2024 03:28:33","Sagemcom CMR"
"Closed Complete","Warning","CTR_351","IHS_YND_734","NOCINC0002911470","Mim=
boman Chateau","","24-08-2024 01:24:26","","","Site alarming because 1/3 re=
ctifier disfunction//He reset it and Site stabilized","","Warning","Warning=
","POWER","Warning - Site on Battery","Site alarming because 1/3 rectifier =
disfunction//He reset it and Site stabilized","alwine.fambou@ihstowers.com"=
,"2","24-08-2024 01:24:26","Sagemcom CMR"
"Closed Complete","Site Down","T2420","IHS_YND_574","NOCINC0002911468","Crf=
-Mbankolo-IHS","","24-08-2024 01:24:11","24-08-2024 01:19:01","24-08-2024 0=
1:59:41","Grid outage; Site went down because Gen start and Stopped  due to=
 Gen overload(15 KVA,200 A)//We reduce load and gen manually started","Mbou=
a Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid =
outage; Site went down because Gen start and Stopped  due to Gen overload(1=
5 KVA,200 A)//We reduce load and gen manually started","ange.kongo@ihstower=
s.com","311","24-08-2024 01:24:11","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002910755","Nko=
g-Edzen","","23-08-2024 22:34:42","23-08-2024 22:14:28","24-08-2024 00:53:5=
2","Active: No power issue site on Battery with U=3D52v Gregoire(654547479)=
 from Huawei is informed","Parker Tchoup","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issu=
e site on Battery with U=3D52v Gregoire(654547479) from Huawei is informed"=
,"ange.kongo@ihstowers.com","1214","23-08-2024 22:34:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0002910752","Ebeba","=
","23-08-2024 22:33:50","23-08-2024 22:11:24","24-08-2024 04:26:13","Cascad=
ed Incident from TTO2725728","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive"," Site on Gen due to Grid Outage, Site went =
down because gen ran until fuel shortage//Refueling done","system","1346","=
23-08-2024 22:33:50","Sagemcom CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0002910747","Nke=
ng likok","IHS_YND_339","23-08-2024 22:32:47","23-08-2024 22:11:24","24-08-=
2024 04:26:13"," Site on Gen due to Grid Outage, Site went down because gen=
 ran until fuel shortage//Refueling done","Kemeni Franklin","Fuel Outage","=
Passive","Diesel","Diesel Outage"," Site on Gen due to Grid Outage, Site we=
nt down because gen ran until fuel shortage//Refueling done","ange.kongo@ih=
stowers.com","1283","23-08-2024 22:32:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0002910020","L=
eboudi","","23-08-2024 20:12:50","23-08-2024 20:11:37","23-08-2024 21:15:21=
","Active : No power issue Ubaie=3D 54.3 V site on Gen The TX FME Mohamadou=
 691144435//  from huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active : No power issue Ubaie=3D 54.3 V site on Gen The TX FME Mohamadou=
 691144435//  from huawei is informed","dorothy.djantio@ihstowers.com","73"=
,"23-08-2024 20:12:50","Sagemcom CMR"
"Closed Complete","Warning","CTR_031","IHS_YND_319","NOCINC0002909775","SOA=
 2","","23-08-2024 19:47:49","","","site alarming High temp 41=B0c// 29=B0c=
 and alarm cleared","Siligap Boris","Warning","Warning","ENVIRONMENT","Warn=
ing - High Temperature","site alarming High temp 41=B0c// 29=B0c and alarm =
cleared","ludivine.ngamaleu@ihstowers.com","13","23-08-2024 19:47:49","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0002909657","N=
GONA","","23-08-2024 19:25:33","23-08-2024 17:32:21","23-08-2024 18:22:13",=
"Grid outage, site went down because gen start and stoppen with alarm ""Low=
 oil pressure"" // He  reset the Gen card  and  GE manually started","Mba L=
azare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage, site went down because gen start and stoppen with alarm ""Lo=
w oil pressure"" // He  reset the Gen card  and  GE manually started","etie=
nne.itondo@ihstowers.com","6792","23-08-2024 19:25:33","Sagemcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0002909134","ODZ=
A BORNE 10","","23-08-2024 18:24:31","23-08-2024 18:06:18","23-08-2024 21:2=
0:36","Active: No power issue, site is on Grid with U=3D54.1V ,  The TX FME=
 Lionel adjep//655184876//   From Huawei is informed","Albran Byorel","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active: No power issue, site is on Grid with U=3D54.1V ,  The TX FME=
 Lionel adjep//655184876//   From Huawei is informed","olivier.kwedi@ihstow=
ers.com","1093","23-08-2024 18:24:31","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0002908752","MIM=
BOMAN LIBERTE","","23-08-2024 17:30:22","23-08-2024 16:51:38","23-08-2024 1=
7:37:43","Grid outage site went because main  Gen faulty // MDG of 15KVA ha=
s deployed","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Generator Faulty","Grid outage site went because main  Gen faulty // MD=
G of 15KVA has deployed","olivier.kwedi@ihstowers.com","2324","23-08-2024 1=
7:30:22","Sagemcom CMR"
"Closed Complete","Warning","T0058","IHS_YND_293","NOCINC0002908360","Nkoab=
ang MTN","","23-08-2024 16:16:34","","","Grid outage site alarming because =
Gen Failed to start due to poor battery backup// Grid power return and alar=
m cleared","Mba Lazare Herve","Warning","Warning","POWER","Warning - Site o=
n Battery","Grid outage site alarming because Gen Failed to start due to po=
or battery backup// Grid power return and alarm cleared","ludivine.ngamaleu=
@ihstowers.com","3","23-08-2024 16:16:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0002908238","B=
riqueterie","","23-08-2024 15:57:55","23-08-2024 14:26:49","24-08-2024 09:1=
3:49","Access issue during the night due to Landlord;site went down due to =
CB 125A disjuncted in Pwc causing by load of increase//he did a bridge with=
 CB 63A","","Access Denial","Lease Or Legal","Landlord Related Issues","Acc=
ess Issue - Land Lord","Access issue during the night due to Landlord;site =
went down due to CB 125A disjuncted in Pwc causing by load of increase//he =
did a bridge with CB 63A","dorothy.djantio@ihstowers.com","5467","23-08-202=
4 15:57:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_323","IHS_YND_043","NOCINC0002908005","E=
mia","","23-08-2024 15:10:45","23-08-2024 15:05:39","23-08-2024 21:10:52","=
Active, no power issue, site on grid with U=3D54V, Team MENOUNGA SAMUEL/693=
678259/ From ZTE is working on site","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issue,=
 site on grid with U=3D54V, Team MENOUNGA SAMUEL/693678259/ From ZTE is wor=
king on site","dorothy.djantio@ihstowers.com","306","23-08-2024 15:10:45","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0002907920","M=
om","","23-08-2024 14:54:50","23-08-2024 14:51:44","23-08-2024 15:45:50","G=
rid outage site went because main  Gen faulty // MDG of 20KVA has deployed"=
,"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fa=
ulty","Grid outage site went because main  Gen faulty // MDG of 20KVA has d=
eployed","dorothy.djantio@ihstowers.com","187","23-08-2024 14:54:50","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0002907790","B=
ONAS YDE","","23-08-2024 14:30:09","23-08-2024 14:11:01","23-08-2024 21:20:=
08","Active, no power issue, site on grid with U=3D56.4V, Team Theodor/6998=
65526/ From ZTE is working on site","Paul BIBOUM","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no po=
wer issue, site on grid with U=3D56.4V, Team Theodor/699865526/ From ZTE is=
 working on site","dorothy.djantio@ihstowers.com","1149","23-08-2024 14:30:=
09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0002907535","S=
ous Prefecture","","23-08-2024 14:01:44","23-08-2024 13:53:36","23-08-2024 =
21:20:45","Active, no power issue, site on grid with U=3D54,6V, The FME tx =
Lionel Tchatchoua /694693436/ From huawei is working on site","Fanda Brice"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active, no power issue, site on grid with U=3D54,6V, The FME t=
x Lionel Tchatchoua /694693436/ From huawei is working on site","alexandre.=
kamal@ihstowers.com","489","23-08-2024 14:01:44","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0002907515","ODZ=
A CITE MBIA","","23-08-2024 13:58:14","23-08-2024 13:32:59","23-08-2024 16:=
37:08","Grid outage, site went down due to gen Overload (10Kva, 125A) // He=
 reduice the load on site","Albran Byorel","Equipment Repair","Passive","AC=
DG Gen","ACDG - Overload","Grid outage, site went down due to gen Overload =
(10Kva, 125A) // He reduice the load on site","stephane.nkamwa@ihstowers.co=
m","1515","23-08-2024 13:58:14","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002907396","Aka=
k-Nkozoa-MTN-IHS","","23-08-2024 13:31:08","23-08-2024 13:07:25","23-08-202=
4 13:23:38","site went down due to CB 125 (A) disjuncted in Pwc//he reamed =
the CB(site swapped by ZTE)","Fabrice Pouakam","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Circuit Breaker Issue","site went down du=
e to CB 125 (A) disjuncted in Pwc//he reamed the CB(site swapped by ZTE)","=
stephane.nkamwa@ihstowers.com","1423","23-08-2024 13:31:08","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_532","NOCINC0002907379","NKOLOSSA=
N OKOK","","23-08-2024 13:26:27","23-08-2024 13:04:13","23-08-2024 14:00:01=
","Grid fluctuation site went down because Gen failed to start due t Grid b=
ad voltage// He bypass the Grid and Gen manually started","Parker Tchoup","=
Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","Gr=
id fluctuation site went down because Gen failed to start due t Grid bad vo=
ltage and No RCP  on site// He bypass the Grid and Gen manually started","s=
tephane.nkamwa@ihstowers.com","1334","23-08-2024 13:26:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0002907100","G=
SO","","23-08-2024 12:20:18","23-08-2024 10:59:36","23-08-2024 11:11:10","A=
ctive// No power issue, site is on Grid,The TX FME BRICE Tsague //650214096=
// from Huawei is informed (Site Swapped by ZTE)","MINKA NICOLAS","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power issue, site is on Grid,The TX FME BRICE Tsague //65021=
4096// from Huawei is informed (Site Swapped by ZTE)","alexandre.kamal@ihst=
owers.com","4842","23-08-2024 12:20:18","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0002905728","N=
dogbessol","","23-08-2024 08:59:24","23-08-2024 08:51:17","23-08-2024 08:52=
:21","Active// No power issue, site is on Battery with Ubaie=3D52,1 V The T=
X FME Etienne //695033981// from Huawei is informed","Kemeni Franklin","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active// No power issue, site is on Battery with Ubaie=3D52,1 V The=
 TX FME Etienne //695033981// from Huawei is informed","alexandre.kamal@ihs=
towers.com","487","23-08-2024 08:59:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0002904980","Mbankolo=
 petit paris","","23-08-2024 05:38:50","23-08-2024 05:32:42","23-08-2024 06=
:01:38","Cascaded Incident from TTO2719202","Mboua Thierry","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid fluctuation, Gen star=
t and stopped due to grid bad voltage, no rcp on site // He bypass grid and=
 manually start the gen (Swapped by ZTE)","system","368","23-08-2024 05:38:=
50","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0002904974","AFE=
ME NORD","IHS_YND_808","23-08-2024 05:33:45","23-08-2024 05:32:42","23-08-2=
024 06:01:38","Grid fluctuation, Gen start and stopped due to grid bad volt=
age, no rcp on site // He bypass grid and manually start the gen (Swapped b=
y ZTE)","TIENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","Grid fluctuation, Gen start and stopped d=
ue to grid bad voltage, no rcp on site // He bypass grid and manually start=
 the gen (Swapped by ZTE)","emmanuel.ghani@ihstowers.com","2199","23-08-202=
4 05:33:45","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002903991","MAN=
GUIERS CHAPELLE","","23-08-2024 00:23:02","23-08-2024 00:21:14","23-08-2024=
 01:29:42","Site went down due to disjunction Cb(80A) in PWC// He replace w=
ith another  Cb(80A) , site on grid (Swapped by ZTE)","Fabrice Pouakam","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker =
Issue","Site went down due to disjunction Cb(80A) in PWC// He replace with =
another  Cb(80A) , site on grid (Swapped by ZTE)","emmanuel.ghani@ihstowers=
.com","109","23-08-2024 00:23:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0002903442","L=
eboudi","","22-08-2024 22:50:09","22-08-2024 22:48:03","23-08-2024 00:21:38=
","Active : No power issue Ubaie=3D 54.3 V site on Grid  The TX FME Mohamad=
ou 691144435//  from huawei is informed","TIENTCHEU NZETCHIEU GAEL","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active : No power issue Ubaie=3D 54.3 V site on Grid  The TX FME Moham=
adou 691144435//  from huawei is informed","joelle.ekessi@ihstowers.com","1=
27","22-08-2024 22:50:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0002903332","S=
cience","","22-08-2024 22:43:04","22-08-2024 22:14:58","23-08-2024 03:40:41=
","No power issue Ubaie=3D 53.5 V site on Grid  The TX FME Mohamadou 691144=
435//  from huawei is informed. Notice that we have disjunction at BTS OCM(=
Swapped by ZTE)","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Ubai=
e=3D 53.5 V site on Grid  The TX FME Mohamadou 691144435//  from huawei is =
informed. Notice that we have disjunction at BTS OCM(Swapped by ZTE)","joel=
le.ekessi@ihstowers.com","1686","22-08-2024 22:43:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0002903157","S=
OA UNIVERSITY STADIUM","","22-08-2024 22:12:01","22-08-2024 20:47:55","22-0=
8-2024 20:55:55","Active// No power issue, site is on GEN with Ubaie=3D53,6=
 V The TX FME Synphorien //691316854// from Huawei is informed (Swapped by =
ZTE)","Siligap Boris","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","Active// No power issue, site is on GEN w=
ith Ubaie=3D53,6 V The TX FME Synphorien //691316854// from Huawei is infor=
med (Swapped by ZTE)","adonis.defokoua@ihstowers.com","5047","22-08-2024 22=
:12:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0002902710","L=
eboudi","","22-08-2024 21:12:44","22-08-2024 21:06:38","22-08-2024 21:10:25=
","No power issue Ubaie=3D 54.6 V site on Grid  The TX FME Mohamadou 691144=
435//  from huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue Ubaie=3D 54.6 V site on Grid  The TX FME Mohamadou 691144435//  =
from huawei is informed","adonis.defokoua@ihstowers.com","366","22-08-2024 =
21:12:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0002901562","Akak-Nko=
zoa-MTN-IHS","","22-08-2024 18:21:50","22-08-2024 18:09:59","22-08-2024 18:=
15:37","Cascaded Incident from TTO2715441","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue site on Grid =
ubaie=3D53.9 V  Impacted by work huawei","system","711","22-08-2024 18:21:5=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002901563","Messassi=
","","22-08-2024 18:21:50","22-08-2024 18:09:59","22-08-2024 18:15:37","Cas=
caded Incident from TTO2715441","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on Grid ubaie=3D53.=
9 V  Impacted by work huawei","system","711","22-08-2024 18:21:50","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0002901565","Messassi=
 Ngonlonk","","22-08-2024 18:21:50","22-08-2024 18:09:59","22-08-2024 18:15=
:37","Cascaded Incident from TTO2715441","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue site on Grid ub=
aie=3D53.9 V  Impacted by work huawei","system","711","22-08-2024 18:21:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0002901564","Messassi=
 2","","22-08-2024 18:21:50","22-08-2024 18:09:59","22-08-2024 18:15:37","C=
ascaded Incident from TTO2715441","Fabrice Pouakam","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on Grid ubaie=3D5=
3.9 V  Impacted by work huawei","system","711","22-08-2024 18:21:50","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_305","NOCINC0002901566","NYOM",""=
,"22-08-2024 18:21:50","22-08-2024 18:09:59","22-08-2024 18:15:37","Cascade=
d Incident from TTO2715441","Fabrice Pouakam","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue site on Grid ubaie=3D53.9 V =
 Impacted by work huawei","system","711","22-08-2024 18:21:50","Sagemcom CM=
R"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0002901559","Ole=
mbe","IHS_YND_316, IHS_YND_297, IHS_YND_280, IHS_YND_799, IHS_YND_305","22-=
08-2024 18:19:44","22-08-2024 18:09:59","22-08-2024 18:38:08","No power iss=
ue site on Grid ubaie=3D53.9 V  Impacted by work huawei","Fabrice Pouakam",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","No power issue site on Grid ubaie=3D53.9 V  Impacted by work hu=
awei","ange.kongo@ihstowers.com","586","22-08-2024 18:19:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_404","NOCINC0002901448","SAA 2","=
","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01","Cascad=
ed Incident from TTO2714458","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Hybrid Gen  No power issue site on battery  =
Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS","system","683=
7","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002901451","Ngoum","=
","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01","Cascad=
ed Incident from TTO2714458","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Hybrid Gen  No power issue site on battery  =
Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS","system","683=
7","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002901447","Matsari"=
,"","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01","Casc=
aded Incident from TTO2714458","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Hybrid Gen  No power issue site on battery=
  Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS","system","6=
837","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_424","NOCINC0002901449","Ossombe"=
,"","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01","Casc=
aded Incident from TTO2714458","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Hybrid Gen  No power issue site on battery=
  Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS","system","6=
837","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002901446","MBIMBIM"=
,"","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01","Casc=
aded Incident from TTO2714458","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Hybrid Gen  No power issue site on battery=
  Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS","system","6=
837","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0002901455","Donga","=
","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01","Cascad=
ed Incident from TTO2714458","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Hybrid Gen  No power issue site on battery  =
Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS","system","683=
7","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0002901456","NTUI TOW=
N","","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01","Ca=
scaded Incident from TTO2714458","Parker Tchoup","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Hybrid Gen  No power issue site on batte=
ry  Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS","system",=
"6837","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_690","NOCINC0002901453","Ntui adm=
inistration","","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:=
10:01","Cascaded Incident from TTO2714458","Parker Tchoup","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Hybrid Gen  No power issue sit=
e on battery  Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS"=
,"system","6837","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0002901454","SAA Entr=
ance","","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01",=
"Cascaded Incident from TTO2714458","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Hybrid Gen  No power issue site on ba=
ttery  Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS","syste=
m","6837","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002901452","Ngouetou=
","","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01","Cas=
caded Incident from TTO2714458","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Hybrid Gen  No power issue site on batter=
y  Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS","system","=
6837","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0002901445","Nguila",=
"","22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01","Casca=
ded Incident from TTO2714458","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Hybrid Gen  No power issue site on battery =
 Ubaie=3D50.7V site impacted by N'tui T0187 No manager by IHS","system","68=
37","22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0002901457","Saa","",=
"22-08-2024 17:50:20","22-08-2024 15:56:23","22-08-2024 16:10:01","Cascaded=
 Incident from TTO2714458","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","Hybrid Gen  No power issue site on battery  Ub=
aie=3D50.7V site impacted by N'tui T0187 No manager by IHS","system","6837"=
,"22-08-2024 17:50:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002901444","O=
lembe-Terminus","","22-08-2024 17:50:07","22-08-2024 17:11:03","22-08-2024 =
18:28:29","Site went down because 03/03 rectifier dysfonction due to load i=
ncrease on site // He reset the rectifier","Fabrice Pouakam","Equipment Rep=
air","Passive","Rectifier","Rectifier Module","Site went down because 03/03=
 rectifier dysfonction due to load increase on site // He reset the rectifi=
er","adonis.defokoua@ihstowers.com","2345","22-08-2024 17:50:07","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_360","IHS_YND_373","NOCINC0002901097","M=
aloun","","22-08-2024 17:07:48","22-08-2024 16:58:58","22-08-2024 17:33:39"=
,"Grid outage site went down because Gen failed to start due to Hybrid syst=
em// He reset the hybrid system","Kemeni Franklin","Equipment Repair","Pass=
ive","Hybrid","Hybrid Module","Grid outage site went down because Gen faile=
d to start due to Hybrid system// He reset the hybrid system","adonis.defok=
oua@ihstowers.com","530","22-08-2024 17:07:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_011","IHS_YND_196","NOCINC0002900933","P=
DC","","22-08-2024 16:47:35","22-08-2024 16:40:28","22-08-2024 18:05:21","A=
ctive, no power issue, site on grid with=3DU=3D54,3 Charles Benda /69555994=
8/  From ZTE is working on site","Mboua Thierry","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no pow=
er issue, site on grid with=3DU=3D54,3 Charles Benda /695559948/  From ZTE =
is working on site","adonis.defokoua@ihstowers.com","427","22-08-2024 16:47=
:35","Sagemcom CMR"
"Closed Complete","Warning","CTR_131","IHS_YND_504","NOCINC0002900876","Eli=
g Edzoa","","22-08-2024 16:35:57","","","site alarming because Gen failed t=
o start due to  the generator cable has been teft //  Grid return and alarm=
 cleared","Delor Telezing","Warning","Warning","POWER","Warning - Site on B=
attery","site alarming because Gen failed to start due to  the generator ca=
ble has been teft //  Grid return and alarm cleared","marie.kwin@ihstowers.=
com","7","22-08-2024 16:35:57","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0002900735","Eli=
g Edzoa","","22-08-2024 16:21:43","22-08-2024 16:05:38","22-08-2024 16:53:3=
3","Grid outage site went down because gen fail to start due to power cable=
 of gen thef stolen// Grid power return","Delor Telezing","Site Asset Theft=
","Theft","Theft","DC Cable Stolen","Grid outage site went down because gen=
 fail to start due to power cable of gen thef stolen// Grid power return","=
ange.kongo@ihstowers.com","966","22-08-2024 16:21:43","Sagemcom CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0002900642","Don=
g","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_404, IHS_YND_424, IHS_YN=
D_392, IHS_YND_475, IHS_YND_454, IHS_YND_690, IHS_YND_542, IHS_YND_434, IHS=
_YND_403, IHS_YND_405","22-08-2024 16:00:36","22-08-2024 15:56:23","22-08-2=
024 18:00:01","Hybrid Gen  No power issue site on battery  Ubaie=3D50.7V si=
te impacted by N'tui T0187 No manager by IHS","Parker Tchoup","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","H=
ybrid Gen  No power issue site on battery  Ubaie=3D50.7V site impacted by N=
'tui T0187 No manager by IHS","ange.kongo@ihstowers.com","254","22-08-2024 =
16:00:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0002900456","M=
fou EPC","","22-08-2024 15:39:25","22-08-2024 15:34:20","22-08-2024 16:29:5=
5","Grid fluctuation site went down because Gen failed to start due to Grid=
 bad voltage // He bypass the Grid and site on Gen","Mba Lazare Herve","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation site went down because Gen failed to start due to Grid bad volt=
age // He bypass the Grid and site on Gen","adonis.defokoua@ihstowers.com",=
"305","22-08-2024 15:39:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0002900415","A=
nguissa New","","22-08-2024 15:32:39","22-08-2024 15:05:26","22-08-2024 16:=
10:35","Active, no power issue, site on grid with U=3D53,5V, Team CLIFFORT =
/652770944/ From ZTE is working on site","MINKA NICOLAS","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
, no power issue, site on grid with U=3D53,5V, Team CLIFFORT /652770944/ Fr=
om ZTE is working on site","adonis.defokoua@ihstowers.com","1634","22-08-20=
24 15:32:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0002899957","A=
nguissa New","","22-08-2024 14:59:09","22-08-2024 14:53:04","22-08-2024 14:=
55:04","Active, no power issue, site on grid with U=3D53,5V, Team CLIFFORT =
/652770944/ From ZTE is working on site","MINKA NICOLAS","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
, no power issue, site on grid with U=3D53,5V, Team CLIFFORT /652770944/ Fr=
om ZTE is working on site","adonis.defokoua@ihstowers.com","366","22-08-202=
4 14:59:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002899820","Sapeur",=
"","22-08-2024 14:37:09","22-08-2024 14:34:04","22-08-2024 16:28:16","Site =
went down because  CB (80A ) of PWC Disjoncted // He reamed the CB","Mboua =
Thierry","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","Site went down because  CB (80A ) of PWC Disjoncted // He reamed =
the CB","ange.kongo@ihstowers.com","185","22-08-2024 14:37:09","Sagemcom CM=
R"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002899803","Jou=
vence 2000","","22-08-2024 14:33:00","22-08-2024 14:12:50","22-08-2024 14:2=
7:20","Grid outage site went down because Gen failed to start due to poor b=
attery//Grid power return","Delor Telezing","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage site went down bec=
ause Gen failed to start due to poor battery//Grid power return","ange.kong=
o@ihstowers.com","1211","22-08-2024 14:33:00","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002899797","Ess=
os Marche","","22-08-2024 14:31:05","22-08-2024 14:12:49","22-08-2024 16:36=
:27","ACTIVE No power issue on site, site on Grid with Ubaie=3D52,8V Tx fme=
 Armand Ngeuts/699949553/ from Huawei is Informed ","Delor Telezing","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","ACTIVE No power issue on site, site on Grid with Ubaie=3D52,8V Tx fme=
 Armand Ngeuts/699949553/ from Huawei is Informed ","ange.kongo@ihstowers.c=
om","1096","22-08-2024 14:31:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_305","NOCINC0002899071","NYOM",""=
,"22-08-2024 12:38:00","22-08-2024 12:10:08","22-08-2024 13:20:22","Cascade=
d Incident from TTO2712726","Fabrice Pouakam","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Tx issue: site on Grid,Ubaie:54.5V;  Sympho=
rien/675-295-205 Huawei is informed .","system","1672","22-08-2024 12:38:00=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0002899069","Messassi=
 2","","22-08-2024 12:38:00","22-08-2024 12:10:08","22-08-2024 13:20:22","C=
ascaded Incident from TTO2712726","Fabrice Pouakam","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Tx issue: site on Grid,Ubaie:54.5V;  =
Symphorien/675-295-205 Huawei is informed .","system","1672","22-08-2024 12=
:38:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_298","NOCINC0002899067","Olembe",=
"","22-08-2024 12:38:00","22-08-2024 12:10:08","22-08-2024 13:20:22","Casca=
ded Incident from TTO2712726","Fabrice Pouakam","Cascade Outage","Active","=
Cascade Active","Cascade Active","Tx issue: site on Grid,Ubaie:54.5V;  Symp=
horien/675-295-205 Huawei is informed .","system","1672","22-08-2024 12:38:=
00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0002899070","Messassi=
 Ngonlonk","","22-08-2024 12:38:00","22-08-2024 12:10:08","22-08-2024 13:20=
:22","Cascaded Incident from TTO2712726","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Tx issue: site on Grid,Ubaie:5=
4.5V;  Symphorien/675-295-205 Huawei is informed .","system","1672","22-08-=
2024 12:38:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0002899068","Akak-Nko=
zoa-MTN-IHS","","22-08-2024 12:38:00","22-08-2024 12:10:08","22-08-2024 13:=
20:22","Cascaded Incident from TTO2712726","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Tx issue: site on Grid,Ubaie=
:54.5V;  Symphorien/675-295-205 Huawei is informed .","system","1672","22-0=
8-2024 12:38:00","Sagemcom CMR"
"Closed Complete","Site Down","T0051","IHS_YND_297","NOCINC0002899056","Mes=
sassi","IHS_YND_298, IHS_YND_316, IHS_YND_280, IHS_YND_799, IHS_YND_305","2=
2-08-2024 12:35:19","22-08-2024 12:10:08","22-08-2024 13:20:22","Tx issue: =
site on Grid,Ubaie:54.5V;  Symphorien/675-295-205 Huawei is informed .","Fa=
brice Pouakam","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Tx issue: site on Grid,Ubaie:54.5V;  Symphorien/=
675-295-205 Huawei is informed .","olivier.kwedi@ihstowers.com","1512","22-=
08-2024 12:35:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0002898672","M=
EFOU ASSI","","22-08-2024 11:30:25","22-08-2024 10:45:18","22-08-2024 11:45=
:51","  site went down due to work  SS Patrick ESSA /657108540/From IHS/is =
working on site ""Replaced DC-BOX//End of work(Site Swapped by ZTE)","Fanda=
 Brice","Installation Activity","Passive","Planned Activity","Installation =
Activity","  site went down due to work  SS Patrick ESSA /657108540/From IH=
S/is working on site ""Replaced DC-BOX//End of work(Site Swapped by ZTE)","=
dorothy.djantio@ihstowers.com","2707","22-08-2024 11:30:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0002898596","M=
fou EPC","","22-08-2024 11:20:35","22-08-2024 11:12:31","22-08-2024 11:28:0=
3","Grid fluctuation, site went down due to Grid bad voltage, no RCP on sit=
e // he bypass Grid and Gen manually start","Mba Lazare Herve","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion, site went down due to Grid bad voltage, no RCP on site // he bypass Gr=
id and Gen manually start","dorothy.djantio@ihstowers.com","485","22-08-202=
4 11:20:35","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_537","NOCINC0002898396","MEFOU ASSI=
","","22-08-2024 10:42:07","","","site alarming due to grid fluctuations//g=
rid power stabilized","Fanda Brice","Warning","Warning","POWER","Warning - =
Site on Battery","site alarming due to grid fluctuations//grid power stabil=
ized","etienne.itondo@ihstowers.com","1807","22-08-2024 10:42:07","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0002898003","N=
KONGKARAK","","22-08-2024 09:25:33","22-08-2024 07:24:09","22-08-2024 07:26=
:44","Active//No power issue, site is on Gen with Ubaie=3D52,1V,The tx Fme =
Mouhamadou (691144435) from Huawei is informed and Up at 07:39 AM ","TIENTC=
HEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","Active//No power issue, site is on Gen with=
 Ubaie=3D52,1V,The tx Fme Mouhamadou (691144435) from Huawei is informed an=
d Up at 07:39 AM ","marie.kwin@ihstowers.com","7284","22-08-2024 09:25:33",=
"Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002897579","N=
KOMEKUI OCM","IHS_YND_341","22-08-2024 08:01:35","22-08-2024 07:23:18","22-=
08-2024 07:29:05","Grid outage, site went down before Gen start due to poor=
 battery backup // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, site went down before Gen start due to poor battery backup // Gen=
 start automatically","etienne.itondo@ihstowers.com","2297","22-08-2024 08:=
01:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0002897415","L=
obo OCM","","22-08-2024 07:29:32","22-08-2024 07:23:18","22-08-2024 07:29:0=
5","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid outage, site went down before Gen start due to p=
oor battery backup // Gen start automatically","dorothy.djantio@ihstowers.c=
om","2372","22-08-2024 07:29:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0002897402","Leboudi"=
,"","22-08-2024 07:25:10","22-08-2024 07:16:13","22-08-2024 08:04:13","Casc=
aded Incident from TTO2710900","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage, gen start and s=
topped due to Gen overload ( 20kva, 375 A) // he reduice the load of site  =
(Site swapped by ZTE)","system","537","22-08-2024 07:25:10","Sagemcom CMR"
"Closed Complete","Site Down","T1109","IHS_YND_287","NOCINC0002897399","Nko=
lafeme","IHS_YND_309","22-08-2024 07:24:23","22-08-2024 07:16:13","22-08-20=
24 08:05:07","Grid outage, gen start and stopped due to Gen overload ( 20kv=
a, 375 A) // he reduice the load of site  (Site swapped by ZTE)","TIENTCHEU=
 NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Overload",=
"Grid outage, gen start and stopped due to Gen overload ( 20kva, 375 A) // =
he reduice the load of site  (Site swapped by ZTE)","dorothy.djantio@ihstow=
ers.com","490","22-08-2024 07:24:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_008","IHS_YND_068","NOCINC0002896619","N=
disamba","","22-08-2024 02:40:17","22-08-2024 02:34:51","22-08-2024 02:40:0=
4","Active issue on site site on Grid with Ubaie=3D54.5 V Tx Huawei FME Bri=
ce Tsague ( 650214096) is informed.","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active iss=
ue on site site on Grid with Ubaie=3D54.5 V Tx Huawei FME Brice Tsague ( 65=
0214096) is informed.","landry.etame@ihstowers.com","327","22-08-2024 02:40=
:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0002895763","N=
kolafeme","","21-08-2024 22:44:05","21-08-2024 21:53:00","21-08-2024 23:03:=
07","Site on gen  due to  Grid outage ,site went down because  Gen  overloa=
d (20kvA,375A) due to load increase on site// site stabilized(site swapped =
by ZTE)","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Overload","Site on gen  due to  Grid outage ,site went down becaus=
e  Gen  overload (20kvA,375A) due to load increase on site// site stabilize=
d(site swapped by ZTE)","landry.etame@ihstowers.com","3066","21-08-2024 22:=
44:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0002895321","E=
kie sud","","21-08-2024 21:22:39","21-08-2024 19:41:25","21-08-2024 19:45:1=
1","No power issue on site ,site on Grid with Ubaie=3D53.5 V The Tx  Lionel=
 steeve //655184876 // from Huawei from huawei is informed(Site Swapped by =
ZTE)","Albran Byorel","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power issue on site ,site on Grid with=
 Ubaie=3D53.5 V The Tx  Lionel steeve //655184876 // from Huawei from huawe=
i is informed(Site Swapped by ZTE)","joelle.ekessi@ihstowers.com","6075","2=
1-08-2024 21:22:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0002895286","T=
amtam Weekend","","21-08-2024 21:14:49","21-08-2024 20:29:42","21-08-2024 2=
1:53:02","Active// Active: No power issue, site is on Grid with Ubaie=3D54,=
6V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed (swapped by ZT=
E)","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active// Active: No power issue, site is o=
n Grid with Ubaie=3D54,6V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is =
informed (swapped by ZTE)","joelle.ekessi@ihstowers.com","2707","21-08-2024=
 21:14:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0002895082","L=
eboudi","","21-08-2024 20:46:19","21-08-2024 20:44:15","21-08-2024 20:45:50=
","Active//No Power Issue site on Grid with Ubaie=3D54,3 V  The Tx Fme Mouh=
amadou (691144435) from Huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active//No Power Issue site on Grid with Ubaie=3D54,3 V  The Tx Fme=
 Mouhamadou (691144435) from Huawei is informed","joelle.ekessi@ihstowers.c=
om","124","21-08-2024 20:46:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0002894979","T=
SINGA VILLAGE 2","","21-08-2024 20:20:21","21-08-2024 19:41:14","21-08-2024=
 19:53:54","Site went down due to dysfunction  of controller Huawei// we by=
pass controller Huawei and site on gen (Swapped by ZTE)","Delor Telezing","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Site went do=
wn due to dysfunction  of controller Huawei// we bypass controller Huawei a=
nd site on gen (Swapped by ZTE)","joelle.ekessi@ihstowers.com","2347","21-0=
8-2024 20:20:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0002894428","E=
toudi","","21-08-2024 18:19:54","21-08-2024 17:23:47","21-08-2024 18:11:09"=
,"Grid Outage, Site went down due to dysfunction  of controller Huawei// we=
 bypass controller Huawei and site on gen (Swapped by ZTE)","Fabrice Pouaka=
m","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid Out=
age, Site went down due to dysfunction  of controller Huawei// we bypass co=
ntroller Huawei and site on gen (Swapped by ZTE)","joelle.ekessi@ihstowers.=
com","3368","21-08-2024 18:19:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0002894404","A=
KONGO","","21-08-2024 18:12:23","21-08-2024 18:04:20","21-08-2024 18:54:35"=
,"Active:  No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rod=
rigue (655102999)from Huawei is informed. Repetitive issue //site up at 06:=
28 PM","Fanda Brice","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active:  No power issue on site Ubaie=3D52=
,5V site on Gen. The Tx FME Rodrigue (655102999)from Huawei is informed. Re=
petitive issue //site up at 06:28 PM","joelle.ekessi@ihstowers.com","484","=
21-08-2024 18:12:23","Sagemcom CMR"
"Closed Complete","Site Down","T1874","IHS_YND_520","NOCINC0002894381","SIM=
BOCK BONAMBAPE","","21-08-2024 18:03:49","21-08-2024 17:59:43","21-08-2024 =
18:55:39","Active// Active: No power issue, site is on Grid with Ubaie=3D54=
,6V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed and Up at 06:=
06 PM","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active// Active: No power issue, site i=
s on Grid with Ubaie=3D54,6V,The tx Fme Hosiah (6 74 00 74 38) from Huawei =
is informed and Up at 06:06 PM","emmanuel.ghani@ihstowers.com","246","21-08=
-2024 18:03:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0002894172","Abang","=
","21-08-2024 17:28:01","21-08-2024 17:05:31","21-08-2024 18:18:44","Cascad=
ed Incident from TTO2707288","Mba Lazare Herve","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down due to CB(125A) disjunc=
tion in PWC// He rearmed the CB (Swapped by ZTE)","system","1350","21-08-20=
24 17:28:01","Sagemcom CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0002894137","Nko=
langaa","IHS_YND_290","21-08-2024 17:21:36","21-08-2024 17:05:31","21-08-20=
24 18:18:44","Site went down due to CB(125A) disjunction in PWC// He rearme=
d the CB (Swapped by ZTE)","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Circuit Breaker Issue","Site went down due=
 to CB(125A) disjunction in PWC// He rearmed the CB (Swapped by ZTE)","emma=
nuel.ghani@ihstowers.com","1346","21-08-2024 17:21:36","Sagemcom CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0002893658","Men=
dong Plateau","IHS_YND_742, IHS_YND_237, IHS_YND_151","21-08-2024 16:22:24"=
,"21-08-2024 15:51:12","21-08-2024 15:52:48","Grid outage, site went down b=
efore gen start due to poor battery backup // Gen start automatically","Hye=
mafo Gildas","Equipment Repair","Passive","Control Panel","Power Cabinet - =
Battery Low","Grid outage, site went down before gen start due to poor batt=
ery backup // Gen start automatically","kombi.samuel@ihstowers.com","3946",=
"21-08-2024 16:22:24","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002893607","Bas=
tos Amb Coree","","21-08-2024 16:09:28","21-08-2024 16:08:23","21-08-2024 1=
6:10:12","Site went down due to insufficent of rectifier on site (02/03)// =
Site Stabilized","","Equipment Repair","Passive","Rectifier","Rectifier Mod=
ule","Site went down due to insufficent of rectifier on site (02/03)// Site=
 Stabilized","emmanuel.ghani@ihstowers.com","66","21-08-2024 16:09:28","Sag=
emcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0002893596","Awa=
e Ewonkan","","21-08-2024 16:07:23","21-08-2024 16:00:19","21-08-2024 16:54=
:52"," Site on Gen due to Grid Outage, Site went down because gen ran until=
 fuel shortage//Refueling done (Swapped by ZTE)","Albran Byorel","Fuel Outa=
ge","Passive","Diesel","Diesel Outage"," Site on Gen due to Grid Outage, Si=
te went down because gen ran until fuel shortage//Refueling done (Swapped b=
y ZTE)","emmanuel.ghani@ihstowers.com","2479","21-08-2024 16:07:23","Sagemc=
om CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0002893572","Tam=
tam Weekend","","21-08-2024 15:59:51","21-08-2024 15:51:12","21-08-2024 15:=
52:48","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automatically","Hyemafo Gildas","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before g=
en start due to poor battery backup // Gen start automatically","emmanuel.g=
hani@ihstowers.com","4953","21-08-2024 15:59:51","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0002893556","Car=
refour Simbock","","21-08-2024 15:58:47","21-08-2024 15:51:12","21-08-2024 =
15:52:48","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage, site went down before gen start due to poor=
 battery backup // Gen start automatically","emmanuel.ghani@ihstowers.com",=
"4953","21-08-2024 15:58:47","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0002893537","Men=
dong NB","","21-08-2024 15:54:58","21-08-2024 15:51:12","21-08-2024 15:52:4=
8","","","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Gr=
id outage, site went down before gen start due to poor battery backup // Ge=
n start automatically","emmanuel.ghani@ihstowers.com","4954","21-08-2024 15=
:54:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0002893439","Abattoir=
","","21-08-2024 15:32:20","21-08-2024 15:09:49","21-08-2024 15:40:31","Cas=
caded Incident from TTO2706483","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage, Site went down due to d=
ysfunction  of controller Huawei// we bypass controller Huawei and site on =
gen","system","1351","21-08-2024 15:32:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0002893440","ETOUDI C=
HAPELLE","","21-08-2024 15:32:20","21-08-2024 15:09:49","21-08-2024 15:40:3=
1","Cascaded Incident from TTO2706483","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage, Site went down du=
e to dysfunction  of controller Huawei// we bypass controller Huawei and si=
te on gen","system","1351","21-08-2024 15:32:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0002893441","Etoudi 2=
","","21-08-2024 15:32:20","21-08-2024 15:09:49","21-08-2024 15:40:31","Cas=
caded Incident from TTO2706483","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage, Site went down due to d=
ysfunction  of controller Huawei// we bypass controller Huawei and site on =
gen","system","1351","21-08-2024 15:32:20","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002893387","Bas=
tos Amb Coree","","21-08-2024 15:20:38","21-08-2024 15:19:34","21-08-2024 1=
5:21:19","Grid outage.,no space to deploy mobile gen//Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.=
,no space to deploy mobile gen//Grid return","emmanuel.ghani@ihstowers.com"=
,"64","21-08-2024 15:20:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002892874","E=
mana","","21-08-2024 14:42:03","21-08-2024 14:19:59","21-08-2024 16:17:24",=
"Site went down because CB OCM (125A) at DC BOX disjuncted Causing by incre=
ase load in site //He reamed CB","","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Circuit Breaker Issue","Site went down because CB OC=
M (125A) at DC BOX disjuncted Causing by increase load in site //He reamed =
CB","joelle.ekessi@ihstowers.com","1324","21-08-2024 14:42:03","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0002892862","Saa","",=
"21-08-2024 14:40:20","21-08-2024 13:47:14","21-08-2024 13:50:15","Cascaded=
 Incident from TTO2705655","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on Gen Ubaie=3D54.1 V. sit=
e impacted by N'tui no manager by IHS","system","3186","21-08-2024 14:40:20=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002892858","MBIMBIM"=
,"","21-08-2024 14:40:20","21-08-2024 13:47:14","21-08-2024 13:50:15","Casc=
aded Incident from TTO2705655","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on Gen Ubaie=3D54.1 V.=
 site impacted by N'tui no manager by IHS","system","3186","21-08-2024 14:4=
0:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002892860","Ngouetou=
","","21-08-2024 14:40:20","21-08-2024 13:47:14","21-08-2024 13:50:15","Cas=
caded Incident from TTO2705655","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on Gen Ubaie=3D54.1 V=
. site impacted by N'tui no manager by IHS","system","3186","21-08-2024 14:=
40:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0002892863","Yoko MTN=
","","21-08-2024 14:40:20","21-08-2024 13:47:14","21-08-2024 13:50:15","Cas=
caded Incident from TTO2705655","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue site on Gen Ubaie=3D54.1 V=
. site impacted by N'tui no manager by IHS","system","3186","21-08-2024 14:=
40:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0002892861","Donga","=
","21-08-2024 14:40:20","21-08-2024 13:47:14","21-08-2024 13:50:15","Cascad=
ed Incident from TTO2705655","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on Gen Ubaie=3D54.1 V. s=
ite impacted by N'tui no manager by IHS","system","3186","21-08-2024 14:40:=
20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_424","NOCINC0002892859","Ossombe"=
,"","21-08-2024 14:40:20","21-08-2024 13:47:14","21-08-2024 13:50:15","Casc=
aded Incident from TTO2705655","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue site on Gen Ubaie=3D54.1 V.=
 site impacted by N'tui no manager by IHS","system","3186","21-08-2024 14:4=
0:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0002892857","Nguila",=
"","21-08-2024 14:40:20","21-08-2024 13:47:14","21-08-2024 13:50:15","Casca=
ded Incident from TTO2705655","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue site on Gen Ubaie=3D54.1 V. =
site impacted by N'tui no manager by IHS","system","3186","21-08-2024 14:40=
:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002892801","B=
ATA-Mokolo","","21-08-2024 14:26:40","21-08-2024 14:09:36","21-08-2024 15:1=
0:36","No power issue site on grid with U=3D54.5V Cl=E9ment (6 80 55 79 75)=
 from ZTE is working on site","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wi=
th U=3D54.5V Cl=E9ment (6 80 55 79 75) from ZTE is working on site","joelle=
.ekessi@ihstowers.com","1024","21-08-2024 14:26:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002892682","Ngoum","=
","21-08-2024 13:55:20","21-08-2024 13:47:14","21-08-2024 13:50:15","Cascad=
ed Incident from TTO2705655","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on Grid Ubaie=3D54.1 V. =
site impacted by N'tui","system","486","21-08-2024 13:55:20","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0002892677","SAA=
 2","IHS_YND_433, IHS_YND_456, IHS_YND_424, IHS_YND_475, IHS_YND_454, IHS_Y=
ND_434, IHS_YND_444, IHS_YND_405, IHS_YND_473, IHS_YND_782","21-08-2024 13:=
54:20","21-08-2024 13:47:14","21-08-2024 14:30:15","No power issue site on =
Gen Ubaie=3D54.1 V. site impacted by N'tui no manager by IHS","Parker Tchou=
p","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue site on Gen Ubaie=3D54.1 V. site impacted by =
N'tui no manager by IHS","ange.kongo@ihstowers.com","426","21-08-2024 13:54=
:20","Sagemcom CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0002892658","Don=
g","","21-08-2024 13:49:31","21-08-2024 13:40:10","21-08-2024 13:45:11","No=
 power issue site on Battery Ubaie=3D51.8 V. site impacted by N'tui no mana=
ger by IHS","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cas=
cade Active","No power issue site on Battery Ubaie=3D51.8 V. site impacted =
by N'tui no manager by IHS","ange.kongo@ihstowers.com","562","21-08-2024 13=
:49:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0002892567","E=
toudi","IHS_YND_244, IHS_YND_694, IHS_YND_211","21-08-2024 13:28:56","21-08=
-2024 10:50:49","21-08-2024 15:49:30","Grid Outage, Site went down due to d=
ysfunction  of controller Huawei// we bypass controller Huawei and site on =
gen(site  swapped by ZTE)","Fabrice Pouakam","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","Grid Outage, Site went down due to dysfun=
ction  of controller Huawei// we bypass controller Huawei and site on gen",=
"adonis.defokoua@ihstowers.com","9487","21-08-2024 13:28:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0002892342","M=
fou EPC","","21-08-2024 13:02:56","21-08-2024 12:54:46","21-08-2024 14:07:1=
2","grid outage,gen failed to start due to grid bad voltage,no rcp //he byp=
ass grid and started the gen","Mba Lazare Herve","Grid Supply","Passive","G=
rid","National Grid - Phase Controller Faulty","grid outage,gen failed to s=
tart due to grid bad voltage,no rcp //he bypass grid and started the gen","=
adonis.defokoua@ihstowers.com","490","21-08-2024 13:02:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0002892326","B=
riqueterie","","21-08-2024 12:59:12","21-08-2024 12:53:07","21-08-2024 13:2=
0:31","Active//No Power Issue site on Grid with Ubaie=3D54,6V  The Team Cri=
stian//680557975// from ZTE is working on site","","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No P=
ower Issue site on Grid with Ubaie=3D54,6V  The Team Cristian//680557975// =
from ZTE is working on site","adonis.defokoua@ihstowers.com","365","21-08-2=
024 12:59:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0002891948","T=
amtam Weekend","","21-08-2024 11:37:01","21-08-2024 10:17:52","21-08-2024 1=
2:18:33","Active//No Power Issue site on Grid with Ubaie=3D54,6V  The Team =
ERIC//696422966// from ZTE is working on site","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No Power Issue site on Grid with Ubaie=3D54,6V  The Team ERIC//696=
422966// from ZTE is working on site","adonis.defokoua@ihstowers.com","4749=
","21-08-2024 11:37:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0002891210","E=
mombo 2","","21-08-2024 09:20:56","21-08-2024 09:11:51","21-08-2024 09:25:3=
8","site went down because Relay LBD dysfonction// He relay activated manua=
lly (Investigation ongoing)","MINKA NICOLAS","Equipment Repair","Passive","=
Control Panel","Relay","site went down because Relay LBD dysfonction// He r=
elay activated manually (Investigation ongoing)","adonis.defokoua@ihstowers=
.com","545","21-08-2024 09:20:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0002891189","K=
ondengui","","21-08-2024 09:12:33","21-08-2024 09:05:27","21-08-2024 09:36:=
03","Active//No Power Issue site on Grid with Ubaie=3D54,4V  The Team Virgi=
le//651559985 from ZTE is working on site","Albran Byorel","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No Power Issue site on Grid with Ubaie=3D54,4V  The Team Virgile//65155=
9985 from ZTE is working on site","adonis.defokoua@ihstowers.com","426","21=
-08-2024 09:12:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0002890512","S=
ous Prefecture","","21-08-2024 06:49:32","21-08-2024 06:40:27","21-08-2024 =
09:38:26","Active// No power issue, site is on grid with Ubaie=3D54,6V The =
Tx FME Lionel tchatchoua //694693436 from Huawei is informed","Fanda Brice"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active// No power issue, site is on grid with Ubaie=3D54,6V Th=
e Tx FME Lionel tchatchoua //694693436 from Huawei is informed","adonis.def=
okoua@ihstowers.com","545","21-08-2024 06:49:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0002890075","M=
ambine","","21-08-2024 04:05:23","21-08-2024 03:42:15","21-08-2024 04:12:30=
","Grid outage.Gen ran until fuel shortage// refueling  ongoing","Fanda Bri=
ce","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.Gen ran u=
ntil fuel shortage// refueling  ongoing","alexandre.kamal@ihstowers.com","1=
389","21-08-2024 04:05:23","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0002889835","MBI=
MBIM","","21-08-2024 02:31:43","21-08-2024 02:23:30","21-08-2024 03:45:08",=
"Site went down because Gen started and stopped due to infiltration of wate=
r in the tank// He removed the water and started the Gen","Parker Tchoup","=
Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In T=
he Fuel","Site went down because Gen started and stopped due to infiltratio=
n of water in the tank// He removed the water and started the Gen","denis.m=
balla@ihstowers.com","493","21-08-2024 02:31:43","Sagemcom CMR"
"Closed Complete","Site Down","T1234","IHS_YND_456","NOCINC0002889234","MBI=
MBIM","","21-08-2024 00:02:52","20-08-2024 23:55:37","21-08-2024 00:28:36",=
"Site went down because Gen started and stopped due to infiltration of wate=
r in the tank// He removed the water and started the Gen","Parker Tchoup","=
Fuel Outage (Probable)","Passive","Diesel","Tank Sealing Issue - Water In T=
he Fuel","Site went down because Gen started and stopped due to infiltratio=
n of water in the tank// He removed the water and started the Gen","denis.m=
balla@ihstowers.com","436","21-08-2024 00:02:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0002889204","S=
ous Prefecture","","21-08-2024 00:00:58","20-08-2024 23:51:59","21-08-2024 =
00:17:58","No power issue on site U=3D54,9 V site on grid TX FME Lionnel /6=
94693436 from huawei is informed.Site up at 12:17 AM","Fanda Brice","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power issue on site U=3D54,9 V site on grid TX FME Lionnel /6946934=
36 from huawei is informed.Site up at 12:17 AM","alexandre.kamal@ihstowers.=
com","539","21-08-2024 00:00:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0002888487","Akak-Nko=
zoa-MTN-IHS","","20-08-2024 20:55:30","20-08-2024 17:14:38","20-08-2024 17:=
30:38","Cascaded Incident from TTO2701021","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site U=3D5=
2v site on grid Synphorien of huawei is informed ","system","13252","20-08-=
2024 20:55:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0002888489","Messassi=
 2","","20-08-2024 20:55:30","20-08-2024 17:14:38","20-08-2024 17:30:38","C=
ascaded Incident from TTO2701021","Fabrice Pouakam","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site U=3D52v site o=
n grid Synphorien of huawei is informed ","system","13252","20-08-2024 20:5=
5:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_298","NOCINC0002888486","Olembe",=
"","20-08-2024 20:55:30","20-08-2024 17:14:38","20-08-2024 17:30:38","Casca=
ded Incident from TTO2701021","Fabrice Pouakam","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site U=3D52v site on gr=
id Synphorien of huawei is informed ","system","13252","20-08-2024 20:55:30=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002888488","Messassi=
","","20-08-2024 20:55:30","20-08-2024 17:14:38","20-08-2024 17:30:38","Cas=
caded Incident from TTO2701021","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site U=3D52v site on =
grid Synphorien of huawei is informed ","system","13252","20-08-2024 20:55:=
30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0002888490","Messassi=
 Ngonlonk","","20-08-2024 20:55:30","20-08-2024 17:14:38","20-08-2024 17:30=
:38","Cascaded Incident from TTO2701021","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D52v=
 site on grid Synphorien of huawei is informed ","system","13252","20-08-20=
24 20:55:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_305","NOCINC0002888491","NYOM",""=
,"20-08-2024 20:55:30","20-08-2024 17:14:38","20-08-2024 17:30:38","Cascade=
d Incident from TTO2701021","Fabrice Pouakam","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No power issue on site U=3D52v site on grid=
 Synphorien of huawei is informed ","system","13252","20-08-2024 20:55:30",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0237","IHS_YND_302","NOCINC0002888473","Nko=
lndom","IHS_YND_298, IHS_YND_316, IHS_YND_297, IHS_YND_280, IHS_YND_799, IH=
S_YND_305, IHS_YND_324","20-08-2024 20:51:59","20-08-2024 17:14:38","20-08-=
2024 17:30:38","No power issue on site U=3D52v site on grid Synphorien of h=
uawei is informed ","Fabrice Pouakam","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D52v site on grid Synphorien of huawei is informed ","kouoh.jean@ihstower=
s.com","13041","20-08-2024 20:51:59","Sagemcom CMR"
"Closed Complete","Warning","T0237","IHS_YND_302","NOCINC0002888463","Nkoln=
dom","","20-08-2024 20:49:19","","","","Fabrice Pouakam","Warning","Warning=
","Unlisted RCA","Warning - Others","Bad Log","kouoh.jean@ihstowers.com","2=
0087","20-08-2024 20:49:19","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_373","NOCINC0002886935","Maloun",""=
,"20-08-2024 17:03:08","","","","Kemeni Franklin","Warning","Warning","POWE=
R","Warning - Planned Activity - Passive","Bernard is on-site // End of wor=
k","kouoh.jean@ihstowers.com","137","20-08-2024 17:03:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002886639","B=
ATA-Mokolo","","20-08-2024 16:16:03","20-08-2024 16:11:57","20-08-2024 16:5=
1:57","No power isssue on site U=3D54,5v site on grid Team Clement/6 80 55 =
79 75/ZTE working on site and Brice stague of huwai is informed","","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power isssue on site U=3D54,5v site on grid Team Clement/6 80 55 79=
 75/ZTE working on site and Brice stague of huwai is informed","landry.etam=
e@ihstowers.com","246","20-08-2024 16:16:03","Sagemcom CMR"
"Closed Complete","Warning","T1551","IHS_YND_316","NOCINC0002885923","Akak-=
Nkozoa-MTN-IHS","","20-08-2024 14:22:35","","","Site alarming because  SITE=
 ON BATTERY due to Grid outage//Dg is started automatically","Fabrice Pouak=
am","Warning","Warning","POWER","Warning - Site on Battery","Site alarming =
because  SITE ON BATTERY due to Grid outage//Dg is started automatically","=
kombi.samuel@ihstowers.com","2","20-08-2024 14:22:35","Sagemcom CMR"
"Closed Complete","Warning","T0236","IHS_YND_373","NOCINC0002885339","Malou=
n","","20-08-2024 12:53:14","","","Site alarming because site on battery //=
Dg is   started   automaticallyat  start threshold=3D51 V","Kemeni Franklin=
","Warning","Warning","POWER","Warning - Site on Battery","Site alarming be=
cause site on battery //Dg is   started   automaticallyat  start threshold=
=3D51 V","kombi.samuel@ihstowers.com","3","20-08-2024 12:53:14","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0002885249","E=
BOM","","20-08-2024 12:34:00","20-08-2024 12:07:48","20-08-2024 13:23:28","=
Active//No Power Issue site on Grid with Ubaie=3D54,4 V  The Team eric//696=
422966 from ZTE is working on site","Hyemafo Gildas","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No=
 Power Issue site on Grid with Ubaie=3D54,4 V  The Team eric//696422966 fro=
m ZTE is working on site","joelle.ekessi@ihstowers.com","1573","20-08-2024 =
12:34:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0002885135","M=
om","","20-08-2024 12:07:44","20-08-2024 12:05:40","20-08-2024 12:51:27","G=
rid Outage, Site went down because main Gen faulty// He MDG OF 20Kva has de=
ployed","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Gener=
ator Faulty","Grid Outage, Site went down because main Gen faulty// He MDG =
OF 20Kva has deployed","joelle.ekessi@ihstowers.com","125","20-08-2024 12:0=
7:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002884810","MBIMBIM"=
,"","20-08-2024 10:57:20","20-08-2024 10:52:24","20-08-2024 10:53:15","Casc=
aded Incident from TTO2696941","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 51.2V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","296","20-08-2024 10:57:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002884808","Ngouetou=
","","20-08-2024 10:57:20","20-08-2024 10:52:24","20-08-2024 10:53:15","Cas=
caded Incident from TTO2696941","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 51.2V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.=
","system","296","20-08-2024 10:57:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002884807","Yoko OCM=
","","20-08-2024 10:57:20","20-08-2024 10:52:24","20-08-2024 10:53:15","Cas=
caded Incident from TTO2696941","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 51.2V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.=
","system","296","20-08-2024 10:57:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002884805","Ngoum","=
","20-08-2024 10:57:20","20-08-2024 10:52:24","20-08-2024 10:53:15","Cascad=
ed Incident from TTO2696941","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 51.2V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","296","20-08-2024 10:57:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002884806","Matsari"=
,"","20-08-2024 10:57:20","20-08-2024 10:52:24","20-08-2024 10:53:15","Casc=
aded Incident from TTO2696941","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 51.2V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","296","20-08-2024 10:57:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0002884168","A=
nguissa New","","20-08-2024 09:22:47","20-08-2024 09:19:43","20-08-2024 10:=
15:51","No power issue on site Ubaie =3D53.2V site on Grid The TX FMEElound=
ou Bertrand 693212405 44423  from huawei is informed","MINKA NICOLAS","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site Ubaie =3D53.2V site on Grid The TX FMEEloundo=
u Bertrand 693212405 44423  from huawei is informed","joelle.ekessi@ihstowe=
rs.com","184","20-08-2024 09:22:47","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0002884100","NTU=
I TOWN","","20-08-2024 09:03:06","20-08-2024 09:01:03","20-08-2024 09:44:02=
","Grid outage, site went down because gen ran until fuel shortage // Grid =
power return( refuelling ongoing)","Parker Tchoup","Fuel Outage","Passive",=
"Diesel","Diesel Outage","Grid outage, site went down because gen ran until=
 fuel shortage // Grid power return( refuelling ongoing)","emmanuel.ghani@i=
hstowers.com","124","20-08-2024 09:03:06","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0002883898","N=
dogbessol","","20-08-2024 08:03:30","20-08-2024 07:58:25","20-08-2024 08:20=
:07","No power issue site on gen with U=3D54.6v Etienne(695033981) from Hua=
wei is informed","Kemeni Franklin","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on gen w=
ith U=3D54.6v Etienne(695033981) from Huawei is informed","joelle.ekessi@ih=
stowers.com","306","20-08-2024 08:03:30","Sagemcom CMR"
"Closed Complete","Site Down","T0293","IHS_YND_180","NOCINC0002883339","Mim=
boman","","20-08-2024 05:30:36","20-08-2024 05:27:22","20-08-2024 06:21:42"=
,"site went down because Gen failed to start due to Grid bad voltage and no=
 RCP on site// He bypass the Grid and Site onGen","Mba Lazare Herve","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","site we=
nt down because Gen failed to start due to Grid bad voltage and no RCP on s=
ite// He bypass the Grid and Site onGen","olivier.kwedi@ihstowers.com","194=
","20-08-2024 05:30:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0002882469","Olembe-T=
erminus","","20-08-2024 00:36:35","20-08-2024 00:10:28","20-08-2024 05:15:2=
1","Active: No power issue on site, Ubai =3D 54,3 V on Grid the tx fme symp=
horien /650257151 /   from HUAWEI is informed  ","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active: No power issue on site, Ubai =3D 54,3 V on Grid the tx fme symp=
horien /650257151 /   from HUAWEI is informed  ","etienne.itondo@ihstowers.=
com","1568","20-08-2024 00:36:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0002882313","S=
OA 2","","19-08-2024 23:40:01","19-08-2024 21:16:51","20-08-2024 01:32:16",=
"Site went down because the Cb(125*80A) bridge OF pwc dysjoncted due to loa=
d incresead// He reamed the CB  (Site swapped by ZTE)","Siligap Boris","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker I=
ssue","Site went down because the Cb(125*80A) bridge OF pwc dysjoncted due =
to load incresead// He reamed the CB  (Site swapped by ZTE)","dorothy.djant=
io@ihstowers.com","8590","19-08-2024 23:40:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0002882003","E=
koumdoum","","19-08-2024 21:56:18","19-08-2024 20:54:10","19-08-2024 22:04:=
07","Grid outage, site went down because gen ran until fuel shortage // Gri=
d return (Site Swapped by ZTE)","Albran Byorel","Fuel Outage","Passive","Di=
esel","Diesel Outage","Grid outage, site went down because gen ran until fu=
el shortage // Grid return (Site Swapped by ZTE)","alexandre.kamal@ihstower=
s.com","3728","19-08-2024 21:56:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0002881550","S=
OA TOWN","","19-08-2024 20:35:39","19-08-2024 19:25:33","19-08-2024 22:03:4=
1","Site went down due to CB   125(A) Disjunted in the PWC // He make the b=
ridge with another CB (50+50)A  (Site Swapped by ZTE)","Siligap Boris","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker I=
ssue","Site went down due to CB   125(A) Disjunted in the PWC // He make th=
e bridge with another CB (50+50)A  (Site Swapped by ZTE)","alexandre.kamal@=
ihstowers.com","4206","19-08-2024 20:35:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002880945","Ngouetou=
","","19-08-2024 18:07:30","19-08-2024 17:53:59","19-08-2024 17:54:07","Cas=
caded Incident from TTO2692589","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.9V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","811","19-08-2024 18:07:30","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002880944","Yoko OCM=
","","19-08-2024 18:07:30","19-08-2024 17:53:59","19-08-2024 17:54:07","Cas=
caded Incident from TTO2692589","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.9V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","811","19-08-2024 18:07:30","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002880942","Ngoum","=
","19-08-2024 18:07:30","19-08-2024 17:53:59","19-08-2024 17:54:07","Cascad=
ed Incident from TTO2692589","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.9V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","811","19-08-2024 18:07:30","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002880943","Matsari"=
,"","19-08-2024 18:07:30","19-08-2024 17:53:59","19-08-2024 17:54:07","Casc=
aded Incident from TTO2692589","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.9V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","811","19-08-2024 18:07:30","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002880946","MBIMBIM"=
,"","19-08-2024 18:07:30","19-08-2024 17:53:59","19-08-2024 17:54:07","Casc=
aded Incident from TTO2692589","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.9V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","811","19-08-2024 18:07:30","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0002880376","N=
kol-Mbanda","","19-08-2024 16:19:26","19-08-2024 15:39:21","19-08-2024 15:4=
5:55","Active//No Power Issue site on Grid with Ubaie=3D54,6 V  The Team er=
ic//696422966 from ZTE is working on site","MINKA NICOLAS","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No Power Issue site on Grid with Ubaie=3D54,6 V  The Team eric//6964229=
66 from ZTE is working on site","alexandre.kamal@ihstowers.com","2406","19-=
08-2024 16:19:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0002880351","S=
ous Prefecture","","19-08-2024 16:14:56","19-08-2024 16:03:51","19-08-2024 =
16:10:46","No power issue on site U=3D54,9 V site on grid  Rm Alain of huaw=
ei is informed notice that Disjunction of CB in BTS Ocm","Fanda Brice","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue on site U=3D54,9 V site on grid  Rm Alain of huawei =
is informed notice that Disjunction of CB in BTS Ocm","alexandre.kamal@ihst=
owers.com","665","19-08-2024 16:14:56","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002879992","Bas=
tos Amb Coree","","19-08-2024 15:32:22","19-08-2024 15:24:10","19-08-2024 1=
6:42:05","Grid outage, no space to deploy a MDG // Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no=
 space to deploy a MDG // Grid return","denis.mballa@ihstowers.com","493","=
19-08-2024 15:32:22","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_243","NOCINC0002879982","Emana","",=
"19-08-2024 15:28:05","","","Site alarming because site on battery  due to =
Grid outage//Grid power return","","Warning","Warning","POWER","Warning - S=
ite on Battery","Site alarming because site on battery  due to Grid outage/=
/Grid power return","stephane.nkamwa@ihstowers.com","929","19-08-2024 15:28=
:05","Sagemcom CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0002879950","Ema=
na Lycee","","19-08-2024 15:20:43","19-08-2024 15:12:28","19-08-2024 15:37:=
51","Grid outage ,gen failed to start due to alarm""low oil pressure""// He=
 reset card GE and gen manually started ","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage ,gen failed=
 to start due to alarm""low oil pressure""// He reset card GE and gen manua=
lly started ","denis.mballa@ihstowers.com","496","19-08-2024 15:20:43","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002879917","ELOUMDEM=
 CARRIERE","","19-08-2024 15:11:10","19-08-2024 15:05:50","19-08-2024 15:13=
:31","Cascaded Incident from TTO2691475","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // Grid Restored","system","320","=
19-08-2024 15:11:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002879918","MBALNGON=
G LYCEE","","19-08-2024 15:11:10","19-08-2024 15:05:50","19-08-2024 15:13:3=
1","Cascaded Incident from TTO2691475","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid Restored","system","320","19=
-08-2024 15:11:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0002879916","Nkolkoum=
ou OCM","","19-08-2024 15:10:50","19-08-2024 14:54:34","19-08-2024 14:59:02=
","Cascaded Incident from TTO2691452","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","Active//No Power Issue s=
ite on Grid with Ubaie=3D54,3 V  The Tx Fme Mouhamadou (691144435) from Hua=
wei is informed","system","976","19-08-2024 15:10:50","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002879914","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","19-08-2024 15:10:03","19-08-20=
24 15:05:50","19-08-2024 15:13:31","Grid outage, site went down before gen =
start due to poor battery backup // Grid Restored","Hyemafo Gildas","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage, site went down before gen start due to poor battery backup // Grid R=
estored","denis.mballa@ihstowers.com","254","19-08-2024 15:10:03","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0002879892","L=
eboudi","IHS_YND_712","19-08-2024 15:03:49","19-08-2024 14:54:34","19-08-20=
24 14:59:02","Active//No Power Issue site on Grid with Ubaie=3D54,3 V  The =
Tx Fme Mouhamadou (691144435) from Huawei is informed","TIENTCHEU NZETCHIEU=
 GAEL","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No Power Issue site on Grid with Ubaie=3D54,3 V =
 The Tx Fme Mouhamadou (691144435) from Huawei is informed","alexandre.kama=
l@ihstowers.com","555","19-08-2024 15:03:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0002879884","N=
koabang","","19-08-2024 15:01:43","19-08-2024 14:01:39","19-08-2024 15:18:3=
8"," Grid outage ,site went  down because Gen failed to start due to soleno=
id relay  faulty// He bypassed it and Gen started manaully","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Solenoid Coil"," Grid o=
utage ,site went  down because Gen failed to start due to solenoid relay  f=
aulty// He bypassed it and Gen started manaully","alexandre.kamal@ihstowers=
.com","3605","19-08-2024 15:01:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0002879825","A=
fanoya","","19-08-2024 14:44:03","19-08-2024 14:43:59","19-08-2024 15:13:31=
","site impacted by  Ahala T0403 ","Hyemafo Gildas","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 gen start due to poor battery backup // Grid Restored","alexandre.kamal@ih=
stowers.com","5","19-08-2024 14:44:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002879498","ELOUMDEM=
 CARRIERE","","19-08-2024 13:42:40","19-08-2024 13:29:27","19-08-2024 13:37=
:27","Cascaded Incident from TTO2690959","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid fluctuation, site went dow=
n because gen failed to started due to poor battery backup // grid return",=
"system","793","19-08-2024 13:42:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002879499","MBALNGON=
G LYCEE","","19-08-2024 13:42:40","19-08-2024 13:29:27","19-08-2024 13:37:2=
7","Cascaded Incident from TTO2690959","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid fluctuation, site went down =
because gen failed to started due to poor battery backup // grid return","s=
ystem","793","19-08-2024 13:42:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002879500","Afanoya"=
,"","19-08-2024 13:42:40","19-08-2024 13:29:27","19-08-2024 13:37:27","Casc=
aded Incident from TTO2690959","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid fluctuation, site went down becau=
se gen failed to started due to poor battery backup // grid return","system=
","793","19-08-2024 13:42:40","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002879462","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","19-08-2024 13:37:36","19-08-20=
24 13:29:27","19-08-2024 13:37:27","grid fluctuation, site went down becaus=
e gen failed to started due to poor battery backup // grid return","Hyemafo=
 Gildas","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","grid fluctuation, site went down because gen failed to started du=
e to poor battery backup // grid return","kouoh.jean@ihstowers.com","489","=
19-08-2024 13:37:36","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002879368","Nko=
g-Edzen","","19-08-2024 13:23:28","19-08-2024 13:13:59","20-08-2024 02:24:2=
0","No power issue site on Battery with U=3D52v Gregoire(654547479) from Hu=
awei is informed ","Parker Tchoup","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on Batte=
ry with U=3D52v Gregoire(654547479) from Huawei is informed ","kouoh.jean@i=
hstowers.com","570","19-08-2024 13:23:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0002879288","B=
itoto","","19-08-2024 13:03:25","19-08-2024 12:41:16","19-08-2024 13:39:58"=
,"No powerissue site on grid with U=3D54.4v erick (696422966) from ZTE is w=
orking on site","Mba Lazare Herve","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No powerissue site on grid w=
ith U=3D54.4v erick (696422966) from ZTE is working on site","landry.etame@=
ihstowers.com","1330","19-08-2024 13:03:25","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002879231","Eko=
unou","","19-08-2024 12:52:30","19-08-2024 12:38:16","19-08-2024 12:48:16",=
"Grid outage site went down because Gen failed to start due to poor battery=
 backup///Gen start automatically(site swapped by ZTE)","Albran Byorel","Eq=
uipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gr=
id outage site went down because Gen failed to start due to poor battery ba=
ckup///Gen start automatically(site swapped by ZTE)","kouoh.jean@ihstowers.=
com","854","19-08-2024 12:52:30","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0002878955","MIM=
BOMAN LIBERTE","","19-08-2024 12:11:56","19-08-2024 12:05:46","19-08-2024 1=
6:18:47","Grid outage;Gen start and Stopped  due to Gen overload(12,5 KVA,2=
20 A)//MDG  15 KVA has deployed (Site Swapped by ZTE)","Mba Lazare Herve","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage;Gen s=
tart and Stopped  due to Gen overload(12,5 KVA,220 A)//MDG  15 KVA has depl=
oyed (Site Swapped by ZTE)","kouoh.jean@ihstowers.com","371","19-08-2024 12=
:11:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002878938","Afanoya"=
,"","19-08-2024 12:06:40","19-08-2024 11:52:34","19-08-2024 12:00:43","Casc=
aded Incident from TTO2690356","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // grid return","system","846","19-08-202=
4 12:06:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002878936","ELOUMDEM=
 CARRIERE","","19-08-2024 12:06:40","19-08-2024 11:52:34","19-08-2024 12:00=
:43","Cascaded Incident from TTO2690356","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // grid return","system","846","19=
-08-2024 12:06:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002878937","MBALNGON=
G LYCEE","","19-08-2024 12:06:40","19-08-2024 11:52:34","19-08-2024 12:00:4=
3","Cascaded Incident from TTO2690356","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // grid return","system","846","19-0=
8-2024 12:06:40","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002878925","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","19-08-2024 12:04:50","19-08-20=
24 11:52:34","19-08-2024 12:00:43","Grid outage, site went down before gen =
start due to poor battery backup // grid return","Hyemafo Gildas","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, site went down before gen start due to poor battery backup // grid ret=
urn","kouoh.jean@ihstowers.com","737","19-08-2024 12:04:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_320","IHS_YND_282","NOCINC0002878896","M=
eyo","IHS_YND_313","19-08-2024 12:01:59","19-08-2024 11:48:48","19-08-2024 =
14:27:37","  site went down due to work  Herman/699999625/From Dowen/is wor=
king on site ""Swapp PWC//End of work(Site Swapped by ZTE)","Hyemafo Gildas=
","Installation Activity","Passive","Planned Activity","Installation Activi=
ty","  site went down due to work  Herman/699999625/From Dowen/is working o=
n site ""Swapp PWC//End of work(Site Swapped by ZTE)","landry.etame@ihstowe=
rs.com","792","19-08-2024 12:01:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002878407","M=
asque","","19-08-2024 10:37:24","19-08-2024 10:16:19","19-08-2024 11:05:32"=
,"No power issue site on grid with U=3D54v Adam ( 658958386) from ZTE  is w=
orking on site ","Fabrice Pouakam","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D54v Adam ( 658958386) from ZTE  is working on site ","landry.etame=
@ihstowers.com","1265","19-08-2024 10:37:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002878298","Ngouetou=
","","19-08-2024 10:14:30","19-08-2024 10:07:54","19-08-2024 10:08:35","Cas=
caded Incident from TTO2689650","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 51.2V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.=
","system","396","19-08-2024 10:14:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002878296","Matsari"=
,"","19-08-2024 10:14:30","19-08-2024 10:07:54","19-08-2024 10:08:35","Casc=
aded Incident from TTO2689650","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 51.2V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","396","19-08-2024 10:14:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002878297","Yoko OCM=
","","19-08-2024 10:14:30","19-08-2024 10:07:54","19-08-2024 10:08:35","Cas=
caded Incident from TTO2689650","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site, Site is on GEN; U=
baie =3D 51.2V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.=
","system","396","19-08-2024 10:14:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002878300","MBIMBIM"=
,"","19-08-2024 10:14:30","19-08-2024 10:07:54","19-08-2024 10:08:35","Casc=
aded Incident from TTO2689650","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site, Site is on GEN; Ub=
aie =3D 51.2V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed."=
,"system","396","19-08-2024 10:14:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002878295","Ngoum","=
","19-08-2024 10:14:30","19-08-2024 10:07:54","19-08-2024 10:08:35","Cascad=
ed Incident from TTO2689650","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site, Site is on GEN; Ubai=
e =3D 51.2V. TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.","=
system","396","19-08-2024 10:14:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0002878226","M=
ontee-Jouvence-II","","19-08-2024 10:06:56","18-08-2024 12:24:34","18-08-20=
24 12:30:39","Active: No power issue site on Grid with U=3D53.5V The TX FME=
 Mbah Hosiah (674007438) FROM Huawei is informed (Swapped by ZTE)","Hyemafo=
 Gildas","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active: No power issue site on Grid with U=3D53.5V The=
 TX FME Mbah Hosiah (674007438) FROM Huawei is informed (Swapped by ZTE)","=
marie.kwin@ihstowers.com","78143","19-08-2024 10:06:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_031","IHS_YND_319","NOCINC0002878151","S=
OA 2","","19-08-2024 09:48:47","19-08-2024 09:32:43","19-08-2024 09:55:25",=
"Active: No Power Issue site on grid,Ubaie:53,9V; Charles Benda/693287035 F=
rom ZTE  is working on site ''Swapp""","Siligap Boris","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No Power Issue site on grid,Ubaie:53,9V; Charles Benda/693287035 From ZTE  =
is working on site ''Swapp""","landry.etame@ihstowers.com","964","19-08-202=
4 09:48:47","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0002878147","MIM=
BOMAN LIBERTE","","19-08-2024 09:47:59","19-08-2024 09:43:48","19-08-2024 1=
0:48:14","Site was on Gen due to Grid Outage, Site went down because Gen is=
 overload (13Kva, 200A)// Site stabilized  (Swapped by ZTE)","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site was on=
 Gen due to Grid Outage, Site went down because Gen is overload (13Kva, 200=
A)// Site stabilized  (Swapped by ZTE)","kouoh.jean@ihstowers.com","252","1=
9-08-2024 09:47:59","Sagemcom CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0002877995","Nko=
lfon Cimencam","","19-08-2024 09:15:41","19-08-2024 09:07:19","19-08-2024 0=
9:25:01","Site went down due to  (01/04)rectifier faulty //He Remove  the f=
aulty rectifier.site on gen ","Hyemafo Gildas","Equipment Repair","Passive"=
,"Rectifier","Rectifier Module","Site went down due to  (01/04)rectifier fa=
ulty //He Remove  the faulty rectifier.site on gen ","kouoh.jean@ihstowers.=
com","503","19-08-2024 09:15:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002877335","Afanoya"=
,"","19-08-2024 08:06:00","19-08-2024 07:57:43","19-08-2024 08:06:31","Casc=
aded Incident from TTO2688516","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, gen start and stopped due=
 to Gen overload ( 30kva,300A) // he reduice the load of site  (Site swappe=
d by ZTE)","system","497","19-08-2024 08:06:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002877333","ELOUMDEM=
 CARRIERE","","19-08-2024 08:06:00","19-08-2024 07:57:43","19-08-2024 08:06=
:31","Cascaded Incident from TTO2688516","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, gen start and stop=
ped due to Gen overload ( 30kva,300A) // he reduice the load of site  (Site=
 swapped by ZTE)","system","497","19-08-2024 08:06:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002877334","MBALNGON=
G LYCEE","","19-08-2024 08:06:00","19-08-2024 07:57:43","19-08-2024 08:06:3=
1","Cascaded Incident from TTO2688516","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, gen start and stoppe=
d due to Gen overload ( 30kva,300A) // he reduice the load of site  (Site s=
wapped by ZTE)","system","497","19-08-2024 08:06:00","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002877283","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","19-08-2024 08:04:21","19-08-20=
24 07:57:43","19-08-2024 08:06:31","Grid outage, gen start and stopped due =
to Gen overload ( 30kva,300A) // he reduice the load of site  (Site swapped=
 by ZTE)","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - =
Overload","Grid outage, gen start and stopped due to Gen overload ( 30kva,3=
00A) // he reduice the load of site  (Site swapped by ZTE)","kouoh.jean@ihs=
towers.com","399","19-08-2024 08:04:21","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0002877263","MIM=
BOMAN LIBERTE","","19-08-2024 08:01:40","19-08-2024 07:52:15","19-08-2024 0=
8:49:15","Site was on Gen due to Grid Outage, Site went down because Gen is=
 overload (13Kva, 200A)// Site stabilized (Swapped by ZTE)","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site was on =
Gen due to Grid Outage, Site went down because Gen is overload (13Kva, 200A=
)// Site stabilized (Swapped by ZTE)","kouoh.jean@ihstowers.com","566","19-=
08-2024 08:01:40","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0002877139","MIM=
BOMAN LIBERTE","","19-08-2024 07:33:51","19-08-2024 07:15:46","19-08-2024 0=
7:33:48","Site was on Gen due to Grid Outage, Site went down because Gen is=
 overload (13Kva, 200A)// Site stabilized(Swapped by ZTE)","Mba Lazare Herv=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site was on G=
en due to Grid Outage, Site went down because Gen is overload (13Kva, 200A)=
// Site stabilized(Swapped by ZTE)","kouoh.jean@ihstowers.com","1085","19-0=
8-2024 07:33:51","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002876485","Tsi=
nga","","19-08-2024 04:44:26","19-08-2024 04:37:20","19-08-2024 04:59:13","=
Grid outage, site went down before gen start due to poor battery backup // =
Grid Restored","Mboua Thierry","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before gen star=
t due to poor battery backup // Grid Restored","ange.kongo@ihstowers.com","=
427","19-08-2024 04:44:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002876285","M=
imboman-Village","","19-08-2024 03:25:50","19-08-2024 02:34:42","19-08-2024=
 05:25:19","Active: no power issue on site ,site on GRid with U=3D53,2V Tea=
m Eloundou // 693212405 from HUAWEI is informed Notice that we have dysjunc=
tion at OCM equipements(site Swapped by ZTE)","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active: no power issue on site ,site on GRid with U=3D53,2V Team Eloundou=
 // 693212405 from HUAWEI is informed Notice that we have dysjunction at OC=
M equipements(site Swapped by ZTE)","adonis.defokoua@ihstowers.com","3069",=
"19-08-2024 03:25:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0002876094","M=
fou EPC","","19-08-2024 02:18:35","19-08-2024 02:10:29","19-08-2024 02:31:0=
8","Grid fluctuation, site went down due to grid bad voltage // Gen start a=
utomatically","Mba Lazare Herve","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","Grid fluctuation, site went down due to gri=
d bad voltage // Gen start automatically","adonis.defokoua@ihstowers.com","=
486","19-08-2024 02:18:35","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002876066","Mim=
boman3","","19-08-2024 02:06:30","19-08-2024 02:03:22","19-08-2024 02:13:19=
","Grid outage, site went down before gen start due to poor battery backup =
(Site Swapped by ZTE) // Gen start automatically","Mba Lazare Herve","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down before gen start due to poor battery backup (Site Sw=
apped by ZTE) // Gen start automatically","ange.kongo@ihstowers.com","188",=
"19-08-2024 02:06:30","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002875994","Lad=
a I Yde","","19-08-2024 01:57:07","19-08-2024 01:53:02","19-08-2024 04:10:2=
9","grid outage, site went down due to Gen overload(09 KVA, 110A) // Gen ma=
nually started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","grid outage, site went down due to Gen overload(09 KVA, =
110A) // Gen manually started","ange.kongo@ihstowers.com","246","19-08-2024=
 01:57:07","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0002875635","Sap=
eur Mimboman","","19-08-2024 00:08:01","19-08-2024 00:00:52","19-08-2024 01=
:57:47","Grid outage,gen failed to start due to card GE faulty //  gen manu=
ally started (Card GE to be replaced)","Mba Lazare Herve","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to st=
art due to card GE faulty //  gen manually started (Card GE to be replaced)=
","ange.kongo@ihstowers.com","429","19-08-2024 00:08:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002875558","MBIMBIM"=
,"","18-08-2024 23:53:00","18-08-2024 23:44:56","19-08-2024 00:44:50","Casc=
aded Incident from TTO2686541","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Our FME Felix 691145560 / 677002977  / IEN=
G is informed and reverts No Power issue on site, Site is on GEN; Ubaie =3D=
 53.2V.=20

TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.

","system","484","18-08-2024 23:53:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002875556","Ngouetou=
","","18-08-2024 23:53:00","18-08-2024 23:44:56","19-08-2024 00:44:50","Cas=
caded Incident from TTO2686541","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Our FME Felix 691145560 / 677002977  / IE=
NG is informed and reverts No Power issue on site, Site is on GEN; Ubaie =
=3D 53.2V.=20

TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.

","system","484","18-08-2024 23:53:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002875553","Ngoum","=
","18-08-2024 23:53:00","18-08-2024 23:44:56","19-08-2024 00:44:50","Cascad=
ed Incident from TTO2686541","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Our FME Felix 691145560 / 677002977  / IENG =
is informed and reverts No Power issue on site, Site is on GEN; Ubaie =3D 5=
3.2V.=20

TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.

","system","484","18-08-2024 23:53:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002875554","Matsari"=
,"","18-08-2024 23:53:00","18-08-2024 23:44:56","19-08-2024 00:44:50","Casc=
aded Incident from TTO2686541","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","Our FME Felix 691145560 / 677002977  / IEN=
G is informed and reverts No Power issue on site, Site is on GEN; Ubaie =3D=
 53.2V.=20

TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.

","system","484","18-08-2024 23:53:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002875555","Yoko OCM=
","","18-08-2024 23:53:00","18-08-2024 23:44:56","19-08-2024 00:44:50","Cas=
caded Incident from TTO2686541","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","Our FME Felix 691145560 / 677002977  / IE=
NG is informed and reverts No Power issue on site, Site is on GEN; Ubaie =
=3D 53.2V.=20

TX FME TX FME WILLY NGOUNI 655999839 of HUAWEI is informed.

","system","484","18-08-2024 23:53:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_680","NOCINC0002875530","MIMBOMAN=
 LIBERTE","","18-08-2024 23:43:50","18-08-2024 23:41:42","19-08-2024 00:15:=
29","Grid outage, Site  went down because Gen started and Stopped due  to G=
en overload(13KVA,200A)//He reduced  the load (RAM of battery),and started =
Gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","Grid outage, Site  went down because Gen started and Stopped due  t=
o Gen overload(13KVA,200A)//He reduced  the load (RAM of battery),and start=
ed Gen","ange.kongo@ihstowers.com","128","18-08-2024 23:43:50","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0002874714","S=
ous Prefecture","","18-08-2024 20:51:12","18-08-2024 20:45:07","18-08-2024 =
21:33:49","No power issue on site U=3D55v site on grid  Rm Alain of huawei =
is informed notice that Disjunction of CB in BTS Ocm","Fanda Brice","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power issue on site U=3D55v site on grid  Rm Alain of huawei is inf=
ormed notice that Disjunction of CB in BTS Ocm","dorothy.djantio@ihstowers.=
com","366","18-08-2024 20:51:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0002874464","N=
koabang","","18-08-2024 20:01:18","18-08-2024 18:34:12","18-08-2024 18:40:0=
1","Active: No power issue, site is on Grid with U=3D56,7V ,  The TX FME Li=
onel adjep//655184876//   From Huawei is informed (swapping by ZTE ))","Mba=
 Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active: No power issue, site is on Grid with U=
=3D56,7V ,  The TX FME Lionel adjep//655184876//   From Huawei is informed =
(swapping by ZTE ))","dorothy.djantio@ihstowers.com","5226","18-08-2024 20:=
01:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0002874297","M=
IMBOMAN LIBERTE","","18-08-2024 19:33:20","18-08-2024 17:36:03","18-08-2024=
 18:01:03","Site was on Gen due to Grid Outage, Site went down because Gen =
is overload (13Kva, 200A)// Site stabilized(Swapped by ZTE)","Mba Lazare He=
rve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site was on=
 Gen due to Grid Outage, Site went down because Gen is overload (13Kva, 200=
A)// Site stabilized(Swapped by ZTE)","dorothy.djantio@ihstowers.com","7038=
","18-08-2024 19:33:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002874251","M=
vog-Manga","","18-08-2024 19:24:44","18-08-2024 13:49:38","18-08-2024 13:57=
:38","site went down due to insufficient of rectifier on site//site stabili=
zed(site swapped by ZTE)","Albran Byorel","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","site went down due to insufficient of rectifier=
 on site//site stabilized(site swapped by ZTE)","dorothy.djantio@ihstowers.=
com","20106","18-08-2024 19:24:44","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002874189","NKO=
MEKUI OCM","","18-08-2024 19:11:32","18-08-2024 19:04:28","18-08-2024 19:36=
:40","No power issue on site U=3D53,9v site on gen mohamadou of huawei is i=
nformed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D=
53,9v site on gen mohamadou of huawei is informed","ludivine.ngamaleu@ihsto=
wers.com","424","18-08-2024 19:11:32","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_313","NOCINC0002873844","Afanoya","","18-=
08-2024 17:51:20","","","Cascaded Incident from TTO2684683","Hyemafo Gildas=
","","","","","","system","545","18-08-2024 17:51:20","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_765","NOCINC0002873843","MBALNGONG LYCEE"=
,"","18-08-2024 17:51:20","","","Cascaded Incident from TTO2684683","Fanda =
Brice","","","","","","system","545","18-08-2024 17:51:20","Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_767","NOCINC0002873842","ELOUMDEM CARRIER=
E","","18-08-2024 17:51:20","","","Cascaded Incident from TTO2684683","Fand=
a Brice","","","","","","system","545","18-08-2024 17:51:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_011","IHS_YND_196","NOCINC0002873840","P=
DC","","18-08-2024 17:49:27","18-08-2024 17:46:22","18-08-2024 18:30:22","N=
o power issue on site U=3D54,5v site on grid Eloundou of huawei is informed=
 site up at 17:47","Mboua Thierry","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
4,5v site on grid Eloundou of huawei is informed site up at 17:47","dorothy=
.djantio@ihstowers.com","185","18-08-2024 17:49:27","Sagemcom CMR"
"Cancelled","Warning","T0403","IHS_YND_257","NOCINC0002873839","Ahala","IHS=
_YND_767, IHS_YND_765, IHS_YND_313","18-08-2024 17:49:21","","","Grid outag=
e,gen stopped with alarm high temp causing by  to Gen overload( 30kva,300A)=
//he added water in radiator and started the gen (Swapped by ZTE)","Hyemafo=
 Gildas","","","","","","ludivine.ngamaleu@ihstowers.com","426","18-08-2024=
 17:49:21","Sagemcom CMR"
"Closed Complete","Site Down","T0871","IHS_YND_306","NOCINC0002873450","Nko=
zoa","","18-08-2024 16:16:24","18-08-2024 16:13:19","18-08-2024 16:20:11","=
Site went down down due to bad voltage no rcp on site// He bypassed Grid an=
d gen manually started","Fabrice Pouakam","Grid Supply","Passive","Grid","N=
ational Grid - Phase Controller Faulty","Site went down down due to bad vol=
tage no rcp on site// He bypassed Grid and gen manually started","ludivine.=
ngamaleu@ihstowers.com","186","18-08-2024 16:16:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002873220","MBIMBIM"=
,"","18-08-2024 15:40:50","18-08-2024 15:27:05","18-08-2024 18:14:53","Casc=
aded Incident from TTO2683994","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","grid outage,gen ran till fuel shortage/=
/refueling done","system","825","18-08-2024 15:40:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002873218","Matsari"=
,"","18-08-2024 15:40:50","18-08-2024 15:27:05","18-08-2024 18:14:53","Casc=
aded Incident from TTO2683994","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","grid outage,gen ran till fuel shortage/=
/refueling done","system","825","18-08-2024 15:40:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002873219","Ngouetou=
","","18-08-2024 15:40:50","18-08-2024 15:27:05","18-08-2024 18:14:53","Cas=
caded Incident from TTO2683994","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage,gen ran till fuel shortage=
//refueling done","system","825","18-08-2024 15:40:50","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0002873214","MIM=
BOMAN LIBERTE","","18-08-2024 15:40:20","18-08-2024 15:37:11","18-08-2024 1=
6:45:34","Site was on Gen due to Grid Outage, Site went down because Gen is=
 overload (13Kva, 200A)// Site stabilized (Swapped by ZTE)","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site was on =
Gen due to Grid Outage, Site went down because Gen is overload (13Kva, 200A=
)// Site stabilized (Swapped by ZTE)","ludivine.ngamaleu@ihstowers.com","19=
0","18-08-2024 15:40:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0002873205","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","18-08-2024 15:39:15","18-=
08-2024 15:27:05","18-08-2024 18:14:53","grid outage,gen ran till fuel shor=
tage//refueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Die=
sel Outage","grid outage,gen ran till fuel shortage//refueling done","dorot=
hy.djantio@ihstowers.com","731","18-08-2024 15:39:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_524","IHS_YND_683","NOCINC0002872799","B=
ONAS YDE","","18-08-2024 14:43:45","18-08-2024 14:40:40","18-08-2024 19:22:=
31","Active: No power issue site on Grid with U=3D56.2V The TX FME Mbah Hos=
iah (674007438) FROM Huawei is informed and site up at 14:57","Paul BIBOUM"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active: No power issue site on Grid with U=3D56.2V The TX FME =
Mbah Hosiah (674007438) FROM Huawei is informed and site up at 14:57","doro=
thy.djantio@ihstowers.com","185","18-08-2024 14:43:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0002872638","A=
nguissa New","","18-08-2024 14:20:54","18-08-2024 14:13:49","18-08-2024 18:=
32:53","site went down due to workSylvain kamdem/671881683/Etech Pro workin=
g on site/Swapp the bay//End  of work (Swapped by ZTE) but the site remaind=
 down at MTN and up at OCM since 18:32 Eloundou 693212405 ","MINKA NICOLAS"=
,"Installation Activity","Passive","Planned Activity","Installation Activit=
y","site went down due to workSylvain kamdem/671881683/Etech Pro working on=
 site/Swapp the bay//End  of work (Swapped by ZTE) but the site remaind dow=
n at MTN and up at OCM since 18:32 Eloundou 693212405 is informed","dorothy=
.djantio@ihstowers.com","426","18-08-2024 14:20:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002872626","ELOUMDEM=
 CARRIERE","","18-08-2024 14:19:30","18-08-2024 14:03:46","18-08-2024 15:04=
:54","Cascaded Incident from TTO2683337","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive"," Grid Outage site went down bec=
ause Gen started and stopped due to ""high temp"" alarm //He added water an=
d Gen manually started (Swapped by ZTE)","system","944","18-08-2024 14:19:3=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002872627","Afanoya"=
,"","18-08-2024 14:19:30","18-08-2024 14:03:46","18-08-2024 15:04:54","Casc=
aded Incident from TTO2683337","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive"," Grid Outage site went down because Ge=
n started and stopped due to ""high temp"" alarm //He added water and Gen m=
anually started (Swapped by ZTE)","system","944","18-08-2024 14:19:30","Sag=
emcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002872582","Aha=
la","IHS_YND_767, IHS_YND_313","18-08-2024 14:12:51","18-08-2024 14:01:55",=
"18-08-2024 15:04:54"," Grid Outage site went down because Gen started and =
stopped due to ""high temp"" alarm //He added water and Gen manually starte=
d (Swapped by ZTE)","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen=
","ACDG - High Engine Temp - Coolant Level Issue"," Grid Outage site went d=
own because Gen started and stopped due to ""high temp"" alarm //He added w=
ater and Gen manually started (Swapped by ZTE)","ludivine.ngamaleu@ihstower=
s.com","30665","18-08-2024 14:12:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002872357","N=
koabang2","","18-08-2024 13:43:24","18-08-2024 11:03:18","18-08-2024 19:30:=
01","Grid outage, site went down before gen start due to poor battery backu=
p // Gen start manaully(Site Swapped by Zte)","Mba Lazare Herve","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge, site went down before gen start due to poor battery backup // Gen start=
 manaully(Site Swapped by Zte)","alexandre.kamal@ihstowers.com","9607","18-=
08-2024 13:43:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_242","IHS_YND_059","NOCINC0002872347","E=
-Poste 2","","18-08-2024 13:42:12","18-08-2024 11:31:04","18-08-2024 15:34:=
44","Site went down due to work Patrick ESSA/IHS/ is working /Swapp//End of=
 Work (Site Swapped by ZTE)","Paul BIBOUM","Installation Activity","Passive=
","Planned Activity","Installation Activity","Site went down due to work Pa=
trick ESSA/IHS/ is working /Swapp//End of Work (Site Swapped by ZTE)","alex=
andre.kamal@ihstowers.com","7868","18-08-2024 13:42:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0002872344","MEHANDAN=
","","18-08-2024 13:41:30","18-08-2024 11:52:10","18-08-2024 12:20:11","Cas=
caded Incident from TTO2683077","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site on Gen due to Grid outage,site we=
nt down because 01/03 faulty//he changed faulty rectifier(site Swapped by Z=
TE)","system","6560","18-08-2024 13:41:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_291","NOCINC0002872345","Ekoumdou=
m OCM","","18-08-2024 13:41:30","18-08-2024 11:52:10","18-08-2024 12:20:11"=
,"Cascaded Incident from TTO2683077","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site on Gen due to Grid outage,si=
te went down because 01/03 faulty//he changed faulty rectifier(site Swapped=
 by ZTE)","system","6560","18-08-2024 13:41:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0002872340","O=
dza-PK10","IHS_YND_528, IHS_YND_291","18-08-2024 13:40:22","18-08-2024 11:5=
2:10","18-08-2024 12:20:11","Site on Gen due to Grid outage,site went down =
because 01/03 faulty//he changed faulty rectifier(site Swapped by ZTE)","Al=
bran Byorel","Equipment Repair","Passive","Rectifier","Rectifier Module","S=
ite on Gen due to Grid outage,site went down because 01/03 faulty//he chang=
ed faulty rectifier(site Swapped by ZTE)","alexandre.kamal@ihstowers.com","=
6492","18-08-2024 13:40:22","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0002872215","Mom=
","","18-08-2024 13:19:24","18-08-2024 13:10:12","18-08-2024 14:29:21","Gri=
d Outage, Site went down because main Gen faulty// He connected MDG 20Kva",=
"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fau=
lty","Grid Outage, Site went down because main Gen faulty// He connected MD=
G 20Kva","denis.mballa@ihstowers.com","830","18-08-2024 13:19:24","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0002871819","Mim=
boman4","","18-08-2024 12:13:06","18-08-2024 12:07:54","18-08-2024 12:43:01=
","Grid Outage, site went down because gen  failed to start due to   gen ba=
ttery discharged/ // Gen manually started with external battery (Investigat=
ion ongoing)","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","A=
CDG - Generator Battery","Grid Outage, site went down because gen  failed t=
o start due to   gen battery discharged/ // Gen manually started with exter=
nal battery (Investigation ongoing)","denis.mballa@ihstowers.com","312","18=
-08-2024 12:13:06","Sagemcom CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0002871652","ETO=
UDI CHAPELLE","","18-08-2024 11:40:16","18-08-2024 11:32:02","18-08-2024 11=
:51:20","Grid Outage, site went down because gen  failed to start due to st=
actic charger faulty  and  gen battery discharged/ // Gen manually started =
with external battery ","Delor Telezing","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Generator Battery","Grid Outage, site went down because gen  =
failed to start due to stactic charger faulty  and  gen battery discharged/=
 // Gen manually started with external battery ","denis.mballa@ihstowers.co=
m","494","18-08-2024 11:40:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0002871641","Leboudi"=
,"","18-08-2024 11:38:30","18-08-2024 11:17:47","18-08-2024 11:23:02","Casc=
aded Incident from TTO2682352","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue Ubaie=3D 54.6 V =
site on Grid  The TX FME Mohamadou 691144435//  from huawei is informed.Sit=
e up 11:23 AM","system","1243","18-08-2024 11:38:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0002871640","Nkolkoum=
ou OCM","","18-08-2024 11:38:30","18-08-2024 11:17:47","18-08-2024 11:23:02=
","Cascaded Incident from TTO2682352","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue Ubaie=3D =
54.6 V site on Grid  The TX FME Mohamadou 691144435//  from huawei is infor=
med.Site up 11:23 AM","system","1243","18-08-2024 11:38:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0002871636","L=
obo OCM","IHS_YND_712, IHS_YND_309","18-08-2024 11:37:21","18-08-2024 11:17=
:47","18-08-2024 11:23:02","No power issue Ubaie=3D 54.6 V site on Grid  Th=
e TX FME Mohamadou 691144435//  from huawei is informed.Site up 11:23 AM","=
TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue Ubaie=3D 54.6 V site o=
n Grid  The TX FME Mohamadou 691144435//  from huawei is informed.Site up 1=
1:23 AM","alexandre.kamal@ihstowers.com","1174","18-08-2024 11:37:21","Sage=
mcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0002871592","San=
ta Barbara Gottam","","18-08-2024 11:22:58","18-08-2024 11:22:49","18-08-20=
24 11:53:46","Grid  outage,site went down because Gen started and Stopped w=
ith Alarm "" under current""/He reset Gen card and started Gen","Delor Tele=
zing","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid =
 outage,site went down because Gen started and Stopped with Alarm "" under =
current""/He reset Gen card and started Gen","denis.mballa@ihstowers.com","=
10","18-08-2024 11:22:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0002871583","Nkolfoul=
ou 2","","18-08-2024 11:21:00","18-08-2024 10:01:03","18-08-2024 10:05:49",=
"Cascaded Incident from TTO2682291","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue on site;site o=
n Gen with Ubaie=3D54.6 V The Tx FME Synphorien //6975295205// from Huawei =
is informed(Site Swapped by ZTE)","system","4797","18-08-2024 11:21:00","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0002871585","TSINGA V=
ILLAGE 2","","18-08-2024 11:21:00","18-08-2024 10:01:03","18-08-2024 10:05:=
49","Cascaded Incident from TTO2682291","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active//No power issue on site;s=
ite on Gen with Ubaie=3D54.6 V The Tx FME Synphorien //6975295205// from Hu=
awei is informed(Site Swapped by ZTE)","system","4797","18-08-2024 11:21:00=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0002871584","Melen Ba=
'aba","","18-08-2024 11:21:00","18-08-2024 10:01:03","18-08-2024 10:05:49",=
"Cascaded Incident from TTO2682291","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue on site;site o=
n Gen with Ubaie=3D54.6 V The Tx FME Synphorien //6975295205// from Huawei =
is informed(Site Swapped by ZTE)","system","4797","18-08-2024 11:21:00","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0002871579","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","18-08-2024 11:19:09","1=
8-08-2024 10:01:03","18-08-2024 10:05:49","Active//No power issue on site;s=
ite on Gen with Ubaie=3D54.6 V The Tx FME Synphorien //6975295205// from Hu=
awei is informed(Site Swapped by ZTE)","Siligap Boris","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue on site;site on Gen with Ubaie=3D54.6 V The Tx FME Synphorie=
n //6975295205// from Huawei is informed(Site Swapped by ZTE)","alexandre.k=
amal@ihstowers.com","4686","18-08-2024 11:19:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0002871183","S=
oa-II","","18-08-2024 10:08:46","18-08-2024 09:40:41","18-08-2024 10:17:07"=
,"Grid outage,Site went down because Gen failed to start with alarm ""corru=
pted memory""//He reset Gen card and started Gen (Site Swapped by ZTE)","Si=
ligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"Grid outage,Site went down because Gen failed to start with alarm ""corru=
pted memory""//He reset Gen card and started Gen ","alexandre.kamal@ihstowe=
rs.com","1686","18-08-2024 10:08:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_409","NOCINC0002871048","Evodoula=
 OCM","","18-08-2024 09:54:50","18-08-2024 09:44:05","18-08-2024 09:55:37",=
"Cascaded Incident from TTO2681726","TIENTCHEU NZETCHIEU GAEL","Cascade Out=
age","Active","Cascade Active","Cascade Active","Active//No power isssue on=
 site ,site on Gen with Ubaie=3D53.3 V TX FME Gregoire(654547479)from Huawe=
i is informed.Site up at 09:55 AM","system","645","18-08-2024 09:54:50","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0002871046","Talla Mo=
natele","","18-08-2024 09:54:50","18-08-2024 09:44:05","18-08-2024 09:55:37=
","Cascaded Incident from TTO2681726","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","Active//No power isssue on site ,si=
te on Gen with Ubaie=3D53.3 V TX FME Gregoire(654547479)from Huawei is info=
rmed.Site up at 09:55 AM","system","645","18-08-2024 09:54:50","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0002871047","Monatele=
 MTN","","18-08-2024 09:54:50","18-08-2024 09:44:05","18-08-2024 09:55:37",=
"Cascaded Incident from TTO2681726","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power isssue on site ,site=
 on Gen with Ubaie=3D53.3 V TX FME Gregoire(654547479)from Huawei is inform=
ed.Site up at 09:55 AM","system","645","18-08-2024 09:54:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_073","IHS_YND_406","NOCINC0002871034","M=
onatele","IHS_YND_387, IHS_YND_407, IHS_YND_409","18-08-2024 09:52:42","18-=
08-2024 09:44:05","18-08-2024 09:55:37","Active//No power isssue on site ,s=
ite on Gen with Ubaie=3D53.3 V TX FME Gregoire(654547479)from Huawei is inf=
ormed.Site up at 09:55 AM","Parker Tchoup","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power iss=
sue on site ,site on Gen with Ubaie=3D53.3 V TX FME Gregoire(654547479)from=
 Huawei is informed.Site up at 09:55 AM","alexandre.kamal@ihstowers.com","5=
17","18-08-2024 09:52:42","Sagemcom CMR"
"Closed Complete","Warning","CTR_031","IHS_YND_319","NOCINC0002871014","SOA=
 2","","18-08-2024 09:50:50","","","Grid Outage. Site alarming on battery b=
ecause Gen was on Manually Mode//He put on Automatically Mode","Siligap Bor=
is","Warning","Warning","POWER","Warning - Site on Battery","Grid Outage. S=
ite alarming on battery because Gen was on Manually Mode//He put on Automat=
ically Mode","stephane.nkamwa@ihstowers.com","2469","18-08-2024 09:50:50","=
Sagemcom CMR"
"Cancelled","Warning","","IHS_YND_319","NOCINC0002870999","SOA 2","","18-08=
-2024 09:48:02","","","Site on Battery","Siligap Boris","","","","","","ste=
phane.nkamwa@ihstowers.com","2293","18-08-2024 09:48:02","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0002870128","MBA=
LNGONG LYCEE","","18-08-2024 06:25:09","18-08-2024 06:16:06","18-08-2024 07=
:02:13","Site  went down because Gen started and Stopped due  to Gen overlo=
ad(9KVA,70A)//He reduced  the load (RAM of battery),and started Gen","Fanda=
 Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Site  we=
nt down because Gen started and Stopped due  to Gen overload(9KVA,70A)//He =
reduced  the load (RAM of battery),and started Gen","emmanuel.ghani@ihstowe=
rs.com","544","18-08-2024 06:25:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002869724","Matsari"=
,"","18-08-2024 03:39:20","18-08-2024 03:28:45","18-08-2024 03:59:15","Casc=
aded Incident from TTO2680332","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Low solar radiation, HUAWEI module faul=
ty // Level 0 manually started GEN","system","635","18-08-2024 03:39:20","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002869725","Yoko OCM=
","","18-08-2024 03:39:20","18-08-2024 03:28:45","18-08-2024 03:59:15","Cas=
caded Incident from TTO2680332","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Low solar radiation, HUAWEI module fau=
lty // Level 0 manually started GEN","system","635","18-08-2024 03:39:20","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002869726","Ngouetou=
","","18-08-2024 03:39:20","18-08-2024 03:28:45","18-08-2024 03:59:15","Cas=
caded Incident from TTO2680332","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Low solar radiation, HUAWEI module fau=
lty // Level 0 manually started GEN","system","635","18-08-2024 03:39:20","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002869728","MBIMBIM"=
,"","18-08-2024 03:39:20","18-08-2024 03:28:45","18-08-2024 03:59:15","Casc=
aded Incident from TTO2680332","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Low solar radiation, HUAWEI module faul=
ty // Level 0 manually started GEN","system","635","18-08-2024 03:39:20","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002869723","Ngoum","=
","18-08-2024 03:39:20","18-08-2024 03:28:45","18-08-2024 03:59:15","Cascad=
ed Incident from TTO2680332","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Low solar radiation, HUAWEI module faulty=
 // Level 0 manually started GEN","system","635","18-08-2024 03:39:20","Sag=
emcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0002869559","Mel=
en Ba'aba","","18-08-2024 02:49:03","18-08-2024 02:28:04","18-08-2024 04:32=
:51","Site went down because the Cb(125A and 16A) in the DC-BOX dysjoncted =
due to load incresead// He replaced the CB 16A to 63A and  reamed the CB  1=
25A(Site swapped by ZTE)","Siligap Boris","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down because=
 the Cb(125A and 16A) in the DC-BOX dysjoncted due to load incresead// He r=
eplaced the CB 16A to 63A and  reamed the CB  125A(Site swapped by ZTE)","e=
mmanuel.ghani@ihstowers.com","1260","18-08-2024 02:49:03","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002869467","Tsi=
nga","","18-08-2024 02:10:06","18-08-2024 02:08:51","18-08-2024 02:30:09","=
Grid outage, site went down before gen start due to poor battery backup // =
Grid Restored","Mboua Thierry","Equipment Repair","Passive","Control Panel"=
,"Power Cabinet - Battery Low","Grid outage, site went down before gen star=
t due to poor battery backup // Grid Restored","emmanuel.ghani@ihstowers.co=
m","75","18-08-2024 02:10:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0002869456","M=
fou EPC","","18-08-2024 01:58:25","18-08-2024 01:56:21","18-08-2024 03:41:4=
5","site went down due to insufficient of rectifier on site // site stabili=
zed","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifier=
 Module","site went down due to insufficient of rectifier on site // site s=
tabilized","joelle.ekessi@ihstowers.com","125","18-08-2024 01:58:25","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0002868471","N=
kolfoulou","","17-08-2024 21:45:59","17-08-2024 20:54:53","17-08-2024 21:18=
:31","Grid fluctuation, site went down because gen failed to start due to g=
rid bad voltage // He make the bridge on good phases (Site swapped by ZTE)"=
,"Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Cont=
roller Faulty","Grid fluctuation, site went down because gen failed to star=
t due to grid bad voltage // He make the bridge on good phases (Site swappe=
d by ZTE)","adonis.defokoua@ihstowers.com","3066","17-08-2024 21:45:59","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0002868391","B=
ISCUITERIE","","17-08-2024 21:29:09","17-08-2024 20:52:50","17-08-2024 20:5=
5:52","No power issue on site UBaie =3D54,6V site on Grid Tx fme Mbah Osiah=
 // 674007438 // from Huawei is informed(Site swapped by ZTE)","Paul BIBOUM=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site UBaie =3D54,6V site on Grid Tx fme Mba=
h Osiah // 674007438 // from Huawei is informed(Site swapped by ZTE)","adon=
is.defokoua@ihstowers.com","2179","17-08-2024 21:29:09","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002868350","Aka=
k-Nkozoa-MTN-IHS","","17-08-2024 21:17:03","17-08-2024 21:12:48","17-08-202=
4 22:34:46","Site went down because the Cb(125*63A) bridge OF pwc dysjoncte=
d due to load incresead// He reamed the CB","Fabrice Pouakam","Equipment Re=
pair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Si=
te went down because the Cb(125*63A) bridge OF pwc dysjoncted due to load i=
ncresead// He reamed the CB","ange.kongo@ihstowers.com","255","17-08-2024 2=
1:17:03","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0002867980","Nko=
abang2","","17-08-2024 20:15:04","17-08-2024 20:09:58","17-08-2024 22:16:32=
","Grid fluctuation, site went down because gen start and stopped due to gr=
id bad voltage // he bypass grid and gen manually started  (Site swapped by=
 ZTE)","Mba Lazare Herve","Grid Supply","Passive","Grid","National Grid - P=
hase Controller Faulty","Grid fluctuation, site went down because gen start=
 and stopped due to grid bad voltage // he bypass grid and gen manually sta=
rted  (Site swapped by ZTE)","ange.kongo@ihstowers.com","306","17-08-2024 2=
0:15:04","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002867975","Nko=
abang Ebolmedjock","","17-08-2024 20:14:02","17-08-2024 20:06:57","17-08-20=
24 23:17:53","Active, No power issue, site on gen with U=3D51,1V The FME tx=
 Lionel ADJEP/655184876/ from huawei is informed","Mba Lazare Herve","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active, No power issue, site on gen with U=3D51,1V The FME tx Lionel =
ADJEP/655184876/ from huawei is informed","ange.kongo@ihstowers.com","426",=
"17-08-2024 20:14:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002867856","Eto koss=
 Yde","","17-08-2024 19:47:20","17-08-2024 19:11:38","17-08-2024 19:49:22",=
"Cascaded Incident from TTO2678269","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to m=
ain gen Faulty // MDG 20kva deployed","system","2142","17-08-2024 19:47:20"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002867857","ELOUMDEM=
 CARRIERE 2","","17-08-2024 19:47:20","17-08-2024 19:11:38","17-08-2024 19:=
49:22","Cascaded Incident from TTO2678269","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to main gen Faulty // MDG 20kva deployed","system","2142","17-08-2024 19=
:47:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002867849","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","17-08-2024 19:45:49","17-08-2024 19:11=
:38","17-08-2024 19:49:22","Grid outage, site went down due to main gen Fau=
lty // MDG 20kva deployed","Fanda Brice","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Generator Faulty","Grid outage, site went down due to main ge=
n Faulty // MDG 20kva deployed","ange.kongo@ihstowers.com","2051","17-08-20=
24 19:45:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002867523","Eto koss=
 Yde","","17-08-2024 18:23:10","17-08-2024 18:17:20","17-08-2024 19:06:33",=
"Cascaded Incident from TTO2677881","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to m=
ain gen Faulty // Grid return","system","350","17-08-2024 18:23:10","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002867524","ELOUMDEM=
 CARRIERE 2","","17-08-2024 18:23:10","17-08-2024 18:17:20","17-08-2024 19:=
06:33","Cascaded Incident from TTO2677881","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to main gen Faulty // Grid return","system","350","17-08-2024 18:23:10",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002867514","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","17-08-2024 18:21:27","17-08-2024 18:17=
:20","17-08-2024 19:06:33","Grid outage, site went down due to main gen Fau=
lty // Grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage, site went down due to main gen Fault=
y // Grid return","ange.kongo@ihstowers.com","248","17-08-2024 18:21:27","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0002867493","N=
sam Sofavinc T0","","17-08-2024 18:16:31","17-08-2024 16:38:17","17-08-2024=
 20:02:48","Site went down due to insufficiency of rctifier // he added 2 r=
ectifier  (Site swapped by ZTE)","MINKA NICOLAS","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","Site went down due to insufficiency of r=
ctifier // he added 2 rectifier  (Site swapped by ZTE)","adonis.defokoua@ih=
stowers.com","5894","17-08-2024 18:16:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002867465","Matsari"=
,"","17-08-2024 18:08:50","17-08-2024 17:58:50","17-08-2024 18:49:39","Casc=
aded Incident from TTO2677822","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down because gen=
 ran until fuel shortage // Grid return","system","600","17-08-2024 18:08:5=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002867466","Ngouetou=
","","17-08-2024 18:08:50","17-08-2024 17:58:50","17-08-2024 18:49:39","Cas=
caded Incident from TTO2677822","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because ge=
n ran until fuel shortage // Grid return","system","600","17-08-2024 18:08:=
50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002867467","MBIMBIM"=
,"","17-08-2024 18:08:50","17-08-2024 17:58:50","17-08-2024 18:49:39","Casc=
aded Incident from TTO2677822","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage, site went down because gen=
 ran until fuel shortage // Grid return","system","600","17-08-2024 18:08:5=
0","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0002867462","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","17-08-2024 18:07:33","17-=
08-2024 17:58:50","17-08-2024 18:49:39","Grid outage, site went down becaus=
e gen ran until fuel shortage (Site refueled by EDONDE)// Grid return","Par=
ker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage, =
site went down because gen ran until fuel shortage // Grid return","adonis.=
defokoua@ihstowers.com","523","17-08-2024 18:07:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_236","NOCINC0002867410","Montee-J=
ouvence","","17-08-2024 17:59:00","17-08-2024 17:13:22","17-08-2024 18:31:1=
2","Cascaded Incident from TTO2677713","Hyemafo Gildas","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive"," Grid Outage site went down be=
cause Gen started and stopped due to ""high temp"" alarm //He added water a=
nd Gen manually started","system","2738","17-08-2024 17:59:00","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0002867409","Mendong =
vallee","","17-08-2024 17:59:00","17-08-2024 17:13:22","17-08-2024 18:31:12=
","Cascaded Incident from TTO2677713","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive"," Grid Outage site went down becaus=
e Gen started and stopped due to ""high temp"" alarm //He added water and G=
en manually started","system","2738","17-08-2024 17:59:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0002867362","M=
endong","IHS_YND_692, IHS_YND_236","17-08-2024 17:53:27","17-08-2024 17:13:=
22","17-08-2024 18:31:12"," Grid Outage site went down because Gen started =
and stopped due to ""high temp"" alarm //He added water and Gen manually st=
arted","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - Hig=
h Engine Temp - Coolant Level Issue"," Grid Outage site went down because G=
en started and stopped due to ""high temp"" alarm //He added water and Gen =
manually started","adonis.defokoua@ihstowers.com","2405","17-08-2024 17:53:=
27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0002866966","M=
fou EPC","","17-08-2024 16:25:56","17-08-2024 16:19:50","17-08-2024 16:29:5=
6","Grid fluctuation, site went down due to grid bad voltage, no RCP on sit=
e // he bypass grid and gen manually start","Mba Lazare Herve","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion, site went down due to grid bad voltage, no RCP on site // he bypass gr=
id and gen manually start","adonis.defokoua@ihstowers.com","366","17-08-202=
4 16:25:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0002866851","M=
ambine","","17-08-2024 16:07:00","17-08-2024 15:59:54","17-08-2024 16:48:22=
","Grid outage, site went down due to CB gen dysjoncted  // He reamed the C=
B and site on gen","Fanda Brice","Equipment Repair","Passive","ACDG Gen","A=
CDG - Load Breaker","Grid outage, site went down due to CB gen dysjoncted  =
// He reamed the CB and site on gen","adonis.defokoua@ihstowers.com","427",=
"17-08-2024 16:07:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002866739","ELOUMDEM=
 CARRIERE 2","","17-08-2024 15:38:40","17-08-2024 15:36:24","17-08-2024 15:=
40:24","Cascaded Incident from TTO2677002","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down d=
ue to main gen Faulty // Grid return","system","136","17-08-2024 15:38:40",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002866738","Eto koss=
 Yde","","17-08-2024 15:38:40","17-08-2024 15:36:24","17-08-2024 15:40:24",=
"Cascaded Incident from TTO2677002","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down due to m=
ain gen Faulty // Grid return","system","136","17-08-2024 15:38:40","Sagemc=
om CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002866732","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","17-08-2024 15:37:36","17-08-2024 15:36=
:24","17-08-2024 16:32:22","Grid outage, site went down due to main gen Fau=
lty // Grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage, site went down due to main gen Fault=
y // Grid return","ange.kongo@ihstowers.com","73","17-08-2024 15:37:36","Sa=
gemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002866056","N=
KOMEKUI OCM","","17-08-2024 13:55:53","17-08-2024 13:53:48","17-08-2024 13:=
58:57","Active, no power issue, site on Gen with U=3D53,4V, The FME tx Moha=
madou /691144435/ From huawei is informed","TIENTCHEU NZETCHIEU GAEL","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active, no power issue, site on Gen with U=3D53,4V, The FME tx Moham=
adou /691144435/ From huawei is informed","dorothy.djantio@ihstowers.com","=
125","17-08-2024 13:55:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0002866049","K=
oweit City","","17-08-2024 13:54:17","17-08-2024 13:37:00","17-08-2024 13:4=
0:00","Active, no power issue U:49.9V site on Grid. TX FME Leonel Steve   (=
655184876) from Huawei is informed","Albran Byorel","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no =
power issue U:49.9V site on Grid. TX FME Leonel Steve   (655184876) from Hu=
awei is informed","dorothy.djantio@ihstowers.com","1037","17-08-2024 13:54:=
17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0002865842","E=
kie sud","","17-08-2024 13:24:08","17-08-2024 11:31:59","17-08-2024 11:40:0=
2","Active, no power issue U:53.2V site on Grid. TX FME Leonel Steve   (655=
184876) from Huawei is informed","Albran Byorel","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no pow=
er issue U:53.2V site on Grid. TX FME Leonel Steve   (655184876) from Huawe=
i is informed","dorothy.djantio@ihstowers.com","6729","17-08-2024 13:24:08"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002865488","Eto koss=
 Yde","","17-08-2024 12:32:30","17-08-2024 12:30:35","17-08-2024 13:46:11",=
"Cascaded Incident from TTO2675611","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage;main gen faulty//MDG 20k=
va deployed","system","115","17-08-2024 12:32:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002865489","ELOUMDEM=
 CARRIERE 2","","17-08-2024 12:32:30","17-08-2024 12:30:35","17-08-2024 13:=
46:11","Cascaded Incident from TTO2675611","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage;main gen faulty//=
MDG 20kva deployed","system","115","17-08-2024 12:32:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002865486","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","17-08-2024 12:31:40","17-08-2024 12:28=
:39","17-08-2024 13:46:11","grid outage;main gen faulty//MDG 20kva deployed=
","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator F=
aulty","grid outage;main gen faulty//MDG 20kva deployed","ludivine.ngamaleu=
@ihstowers.com","5051","17-08-2024 12:31:40","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0002865219","Nko=
lo II New","IHS_YND_266","17-08-2024 11:37:55","17-08-2024 11:31:49","17-08=
-2024 12:00:26","No power issue on site U=3D53v site on grid Team OkoloLadi=
s/695684963/H-TELIS working on site ""Normalisation of Fiber""","Mba Lazare=
 Herve","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site U=3D53v site on grid Team OkoloL=
adis/695684963/H-TELIS working on site ""Normalisation of Fiber""","ludivin=
e.ngamaleu@ihstowers.com","366","17-08-2024 11:37:55","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0002865214","Mim=
boman4","","17-08-2024 11:36:55","17-08-2024 11:31:49","17-08-2024 12:00:26=
","No power issue on site U=3D53v site on grid Team OkoloLadis/695684963/H-=
TELIS working on site ""Normalisation of Fiber""","Mba Lazare Herve","Casca=
de Outage","Active","Cascade Active","Cascade Active","No power issue on si=
te U=3D53v site on grid Team OkoloLadis/H-TELIS working on site ""Normalisa=
tion of Fiber""","ludivine.ngamaleu@ihstowers.com","1572","17-08-2024 11:36=
:55","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0002864971","San=
ta Barbara Gottam","","17-08-2024 10:58:20","17-08-2024 10:55:16","17-08-20=
24 11:48:25","Grid outage site went down because Gen failed to start due to=
 RCP faulty // He manually started the Gen","Delor Telezing","Grid Supply",=
"Passive","Grid","National Grid - Phase Controller Faulty","Grid outage sit=
e went down because Gen failed to start due to RCP faulty // He manually st=
arted the Gen","ludivine.ngamaleu@ihstowers.com","184","17-08-2024 10:58:20=
","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002864687","Tsi=
nga","","17-08-2024 10:10:41","17-08-2024 10:08:37","17-08-2024 10:30:22","=
Grid outage, site down because Gen failed due to poor backup before gen sta=
rt//Grid power return ","Mboua Thierry","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site down because Gen=
 failed due to poor backup before gen start//Grid power return ","ludivine.=
ngamaleu@ihstowers.com","125","17-08-2024 10:10:41","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0002864680","Bas=
tos Ekoudou","","17-08-2024 10:09:21","17-08-2024 10:06:53","17-08-2024 10:=
10:52","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automaticaly","Mboua Thierry","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen start automaticaly","l=
udivine.ngamaleu@ihstowers.com","148","17-08-2024 10:09:21","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0002863503","Mfo=
u EPC","","17-08-2024 06:23:33","17-08-2024 06:09:37","17-08-2024 07:22:58"=
,"site went down because gen failed to start due to lack of 2 phases//grid =
bypass and Gen manually started","Mba Lazare Herve","Grid Supply","Passive"=
,"Grid","National Grid - Grid Incomplete Phase","site went down because gen=
 failed to start due to lack of 2 phases//grid bypass and Gen manually star=
ted","ludivine.ngamaleu@ihstowers.com","1388","17-08-2024 06:23:33","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0002863434","NKONGKAR=
AK","","17-08-2024 05:48:00","17-08-2024 05:41:10","17-08-2024 06:56:45","C=
ascaded Incident from TTO2673355","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site went down due to mal=
function controller Huawei//he reset it,site on Gen (investigation ongoing)=
","system","410","17-08-2024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0002863432","Ekekam",=
"","17-08-2024 05:48:00","17-08-2024 05:41:10","17-08-2024 06:56:45","Casca=
ded Incident from TTO2673355","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to malfunc=
tion controller Huawei//he reset it,site on Gen (investigation ongoing)","s=
ystem","410","17-08-2024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0002863426","Nkeng li=
kok","","17-08-2024 05:48:00","17-08-2024 05:41:10","17-08-2024 06:56:45","=
Cascaded Incident from TTO2673355","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to malfunction=
 controller Huawei//he reset it,site on Gen (investigation ongoing)","syste=
m","410","17-08-2024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0002863431","Nkongtoc=
k","","17-08-2024 05:48:00","17-08-2024 05:41:10","17-08-2024 06:56:45","Ca=
scaded Incident from TTO2673355","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to malfunction c=
ontroller Huawei//he reset it,site on Gen (investigation ongoing)","system"=
,"410","17-08-2024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_366","NOCINC0002863430","Mandoumb=
a MTN","","17-08-2024 05:48:00","17-08-2024 05:41:10","17-08-2024 06:56:45"=
,"Cascaded Incident from TTO2673355","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to malfuncti=
on controller Huawei//he reset it,site on Gen (investigation ongoing)","sys=
tem","410","17-08-2024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0002863427","Ngog Map=
ubi","","17-08-2024 05:48:00","17-08-2024 05:41:10","17-08-2024 06:56:45","=
Cascaded Incident from TTO2673355","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site went down due to malfunction=
 controller Huawei//he reset it,site on Gen (investigation ongoing)","syste=
m","410","17-08-2024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0002863425","Lobo 2",=
"","17-08-2024 05:48:00","17-08-2024 05:41:10","17-08-2024 06:56:45","Casca=
ded Incident from TTO2673355","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down due to malfunc=
tion controller Huawei//he reset it,site on Gen (investigation ongoing)","s=
ystem","410","17-08-2024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0002863429","Bot Maka=
k","","17-08-2024 05:48:00","17-08-2024 05:41:10","17-08-2024 06:56:45","Ca=
scaded Incident from TTO2673355","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site went down due to malfunction controller Huawe=
i//he reset it,site on Gen (investigation ongoing)","system","410","17-08-2=
024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0002863428","Ebeba","=
","17-08-2024 05:48:00","17-08-2024 05:41:10","17-08-2024 06:56:45","Cascad=
ed Incident from TTO2673355","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to malfunction controlle=
r Huawei//he reset it,site on Gen (investigation ongoing)","system","410","=
17-08-2024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0002863433","LOBO MTN=
","","17-08-2024 05:48:00","17-08-2024 05:41:10","17-08-2024 06:56:45","Cas=
caded Incident from TTO2673355","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site went down due to malfu=
nction controller Huawei//he reset it,site on Gen (investigation ongoing)",=
"system","410","17-08-2024 05:48:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_360","IHS_YND_373","NOCINC0002863389","M=
aloun","IHS_YND_783, IHS_YND_347, IHS_YND_419, IHS_YND_339, IHS_YND_421, IH=
S_YND_366, IHS_YND_349, IHS_YND_714, IHS_YND_342, IHS_YND_713","17-08-2024 =
05:37:10","17-08-2024 05:30:01","17-08-2024 06:56:45","Site went down due t=
o malfunction controller Huawei//he reset it,site on Gen (investigation ong=
oing)","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","Site went down due to malfunction controller Huawei//he reset=
 it,site on Gen (investigation ongoing)","landry.etame@ihstowers.com","430"=
,"17-08-2024 05:37:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0002863312","Donga","=
","17-08-2024 05:03:40","17-08-2024 04:44:21","17-08-2024 06:26:56","Cascad=
ed Incident from TTO2673248","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down because gen failed to star=
t due to terminal of battery deconnected//he reconnect it and started the G=
en","system","1159","17-08-2024 05:03:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0002863313","Dong",""=
,"17-08-2024 05:03:40","17-08-2024 04:44:21","17-08-2024 06:26:56","Cascade=
d Incident from TTO2673248","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","site went down because gen failed to start=
 due to terminal of battery deconnected//he reconnect it and started the Ge=
n","system","1159","17-08-2024 05:03:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0002863311","N=
guila","IHS_YND_434, IHS_YND_444","17-08-2024 05:02:28","17-08-2024 04:44:2=
1","17-08-2024 06:27:26","site went down because gen failed to start due to=
 terminal of battery deconnected//he reconnect it and started the Gen","Par=
ker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Batte=
ry","site went down because gen failed to start due to terminal of battery =
deconnected//he reconnect it and started the Gen","landry.etame@ihstowers.c=
om","1088","17-08-2024 05:02:28","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002862950","Tsi=
nga","","17-08-2024 02:16:39","17-08-2024 02:10:16","17-08-2024 02:32:16","=
Grid outage, site down because Gen failed due to poor backup before gen sta=
rt//Grid power return ","Mboua Thierry","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site down because Gen=
 failed due to poor backup before gen start//Grid power return ","kouoh.jea=
n@ihstowers.com","384","17-08-2024 02:16:39","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002862004","Nko=
abang Ebolmedjock","","16-08-2024 21:48:56","16-08-2024 21:46:51","16-08-20=
24 21:50:51","Active, No power issue, site on gen with U=3D51,1V The FME tx=
 Lionel ADJEP/655184876/ from huawei is informed","Mba Lazare Herve","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active, No power issue, site on gen with U=3D51,1V The FME tx Lionel =
ADJEP/655184876/ from huawei is informed","emmanuel.ghani@ihstowers.com","1=
25","16-08-2024 21:48:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002861955","Afanoya"=
,"","16-08-2024 21:37:21","16-08-2024 21:34:45","16-08-2024 21:46:35","Casc=
aded Incident from TTO2671787","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 failed to start due to poor battery backup///Grid power return","system","=
156","16-08-2024 21:37:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002861954","MBALNGON=
G LYCEE","","16-08-2024 21:37:21","16-08-2024 21:34:45","16-08-2024 21:46:3=
5","Cascaded Incident from TTO2671787","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage site went down becaus=
e Gen failed to start due to poor battery backup///Grid power return","syst=
em","156","16-08-2024 21:37:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002861953","ELOUMDEM=
 CARRIERE","","16-08-2024 21:37:21","16-08-2024 21:34:45","16-08-2024 21:46=
:35","Cascaded Incident from TTO2671787","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen failed to start due to poor battery backup///Grid power return","sy=
stem","156","16-08-2024 21:37:21","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002861949","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","16-08-2024 21:35:51","16-08-20=
24 21:34:45","16-08-2024 21:46:35","Grid outage site went down because Gen =
failed to start due to poor battery backup///Grid power return","Hyemafo Gi=
ldas","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery=
 Low","Grid outage site went down because Gen failed to start due to poor b=
attery backup///Grid power return","emmanuel.ghani@ihstowers.com","67","16-=
08-2024 21:35:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0002861381","S=
ous Prefecture","","16-08-2024 19:45:40","16-08-2024 19:39:33","16-08-2024 =
20:22:47","Site went down because the Cb(125A) of PWC dysjoncted //He reame=
d the Cb,Power issue resolved but site remains down Alain(691144423) from H=
uawei is informed ","Fanda Brice","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Circuit Breaker Issue","Site went down because the Cb(=
125A) of PWC dysjoncted //He reamed the Cb,Power issue resolved but site re=
mains down Alain(691144423) from Huawei is informed ","joelle.ekessi@ihstow=
ers.com","368","16-08-2024 19:45:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002861326","ELOUMDEM=
 CARRIERE 2","","16-08-2024 19:26:20","16-08-2024 19:20:07","16-08-2024 20:=
02:24","Cascaded Incident from TTO2671084","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage and Main DG fault=
y//Grid Restored","system","373","16-08-2024 19:26:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002861325","Eto koss=
 Yde","","16-08-2024 19:26:20","16-08-2024 19:20:07","16-08-2024 20:02:24",=
"Cascaded Incident from TTO2671084","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage and Main DG faulty//Grid=
 Restored","system","373","16-08-2024 19:26:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002861322","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","16-08-2024 19:25:26","16-08-2024 19:20=
:07","16-08-2024 20:02:24","Grid outage and Main DG faulty//Grid Restored",=
"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fau=
lty","Grid outage and Main DG faulty//Grid Restored","emmanuel.ghani@ihstow=
ers.com","320","16-08-2024 19:25:26","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0002861162","Nko=
lbong","","16-08-2024 19:02:16","16-08-2024 18:55:09","16-08-2024 19:37:42"=
,"Grid outage,Gen stopped with alarm low oil pressure//he added oil and sta=
rted it(Site swapped by ZTE)","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Low Oil Pressure","Grid outage,Gen stopped with alarm l=
ow oil pressure//he added oil and started it(Site swapped by ZTE)","emmanue=
l.ghani@ihstowers.com","1220","16-08-2024 19:02:16","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002861086","Nko=
abang Ebolmedjock","","16-08-2024 18:40:55","16-08-2024 18:38:38","16-08-20=
24 19:19:52","Grid outage, site went down due to Gen overload(09 KVA, 110A)=
 // Gen manually started","Mba Lazare Herve","Equipment Repair","Passive","=
ACDG Gen","ACDG - Overload","Grid outage, site went down due to Gen overloa=
d(09 KVA, 110A) // Gen manually started","emmanuel.ghani@ihstowers.com","13=
8","16-08-2024 18:40:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002860979","Eto koss=
 Yde","","16-08-2024 18:22:30","16-08-2024 18:17:50","16-08-2024 18:21:50",=
"Cascaded Incident from TTO2670707","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage and Main DG faulty//Mobi=
le DG (20 kva) to deployed ","system","280","16-08-2024 18:22:30","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002860980","ELOUMDEM=
 CARRIERE 2","","16-08-2024 18:22:30","16-08-2024 18:17:50","16-08-2024 18:=
21:50","Cascaded Incident from TTO2670707","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage and Main DG fault=
y//Mobile DG (20 kva) to deployed ","system","280","16-08-2024 18:22:30","S=
agemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002860972","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","16-08-2024 18:20:53","16-08-2024 18:17=
:50","16-08-2024 18:21:50","Grid outage and Main DG faulty//Mobile DG (20 k=
va) to deployed ","Fanda Brice","Equipment Repair","Passive","ACDG Gen","AC=
DG - Generator Faulty","Grid outage and Main DG faulty//Mobile DG (20 kva) =
to deployed ","emmanuel.ghani@ihstowers.com","184","16-08-2024 18:20:53","S=
agemcom CMR"
"Closed Complete","Site Down","T3150","IHS_YND_214","NOCINC0002860833","Nko=
lmesseng-II","","16-08-2024 17:41:50","16-08-2024 17:35:08","16-08-2024 18:=
20:54","","Siligap Boris","Cascade Outage","Passive","Cascade Passive","Cas=
cade Passive","site down affected by CAMP Sonel/(site went down because Gen=
 failed to start due to due to lack on 02 phases on site //he bypassed Grid=
 en started the Gen Manually)","emmanuel.ghani@ihstowers.com","11262","16-0=
8-2024 17:41:50","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0002860829","MIM=
BOMAN LIBERTE","IHS_YND_214","16-08-2024 17:40:14","16-08-2024 17:35:08","1=
6-08-2024 18:20:54","site down affected by CAMP Sonel/(site went down becau=
se Gen failed to start due to due to lack on 02 phases on site //he bypasse=
d Grid en started the Gen Manually)","Mba Lazare Herve","Grid Supply","Pass=
ive","Grid","National Grid - Phase Controller Faulty","site down affected b=
y CAMP Sonel/(site went down because Gen failed to start due to due to lack=
 on 02 phases on site //he bypassed Grid en started the Gen Manually)","emm=
anuel.ghani@ihstowers.com","307","16-08-2024 17:40:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_065","NOCINC0002860687","Essos DC=
S","","16-08-2024 17:25:41","16-08-2024 17:08:31","16-08-2024 18:22:24","Ca=
scaded Incident from TTO2670307","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","site went down because Gen failed to=
 start due to due to lack on 02 phases on site //he bypassed Grid en starte=
d the Gen Manually","system","1030","16-08-2024 17:25:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_097","NOCINC0002860686","Kondengu=
i MTN","","16-08-2024 17:25:41","16-08-2024 17:08:31","16-08-2024 18:22:24"=
,"Cascaded Incident from TTO2670307","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because Gen failed=
 to start due to due to lack on 02 phases on site //he bypassed Grid en sta=
rted the Gen Manually","system","1030","16-08-2024 17:25:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0002860688","Crf Corn=
ier","","16-08-2024 17:25:41","16-08-2024 17:08:31","16-08-2024 18:22:24","=
Cascaded Incident from TTO2670307","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because Gen failed t=
o start due to due to lack on 02 phases on site //he bypassed Grid en start=
ed the Gen Manually","system","1030","16-08-2024 17:25:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0002860683","Anguissa=
 New","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24",=
"Cascaded Incident from TTO2670307","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down because Gen failed =
to start due to due to lack on 02 phases on site //he bypassed Grid en star=
ted the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_063","NOCINC0002860678","Av-Germa=
ine","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24","=
Cascaded Incident from TTO2670307","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive","site went down because Gen failed to start due t=
o due to lack on 02 phases on site //he bypassed Grid en started the Gen Ma=
nually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0002860685","Kondengu=
i","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24","Ca=
scaded Incident from TTO2670307","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site went down because Gen failed to =
start due to due to lack on 02 phases on site //he bypassed Grid en started=
 the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_178","NOCINC0002860684","Emombo",=
"","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24","Casca=
ded Incident from TTO2670307","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","site went down because Gen failed to =
start due to due to lack on 02 phases on site //he bypassed Grid en started=
 the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_122","NOCINC0002860675","Emombo E=
sssomba","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:2=
4","Cascaded Incident from TTO2670307","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","site went down because Gen f=
ailed to start due to due to lack on 02 phases on site //he bypassed Grid e=
n started the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_113","NOCINC0002860680","Emombo 2=
","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24","Cas=
caded Incident from TTO2670307","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because Gen failed to s=
tart due to due to lack on 02 phases on site //he bypassed Grid en started =
the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_180","NOCINC0002860673","Mimboman=
","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24","Cas=
caded Incident from TTO2670307","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because Gen failed t=
o start due to due to lack on 02 phases on site //he bypassed Grid en start=
ed the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0002860670","MONTEE N=
KONDENGUI","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22=
:24","Cascaded Incident from TTO2670307","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went down because Gen fa=
iled to start due to due to lack on 02 phases on site //he bypassed Grid en=
 started the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_042","NOCINC0002860672","Mvog-Ada=
_OCM","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24",=
"Cascaded Incident from TTO2670307","","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","site went down because Gen failed to start due =
to due to lack on 02 phases on site //he bypassed Grid en started the Gen M=
anually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_111","NOCINC0002860671","Essos Ma=
rche","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24",=
"Cascaded Incident from TTO2670307","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because Gen failed=
 to start due to due to lack on 02 phases on site //he bypassed Grid en sta=
rted the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0002860682","Mobil-Es=
sos","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24","=
Cascaded Incident from TTO2670307","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because Gen failed t=
o start due to due to lack on 02 phases on site //he bypassed Grid en start=
ed the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_108","NOCINC0002860676","RUE FOE"=
,"","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24","Casc=
aded Incident from TTO2670307","Delor Telezing","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because Gen failed to s=
tart due to due to lack on 02 phases on site //he bypassed Grid en started =
the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_120","NOCINC0002860679","Sapeur M=
imboman","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:2=
4","Cascaded Incident from TTO2670307","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","site went down because Gen f=
ailed to start due to due to lack on 02 phases on site //he bypassed Grid e=
n started the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_025","NOCINC0002860681","CORNIERS=
","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24","Cas=
caded Incident from TTO2670307","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","site went down because Gen failed to start due to d=
ue to lack on 02 phases on site //he bypassed Grid en started the Gen Manua=
lly","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_189","NOCINC0002860677","Paradis =
Hotel","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:22:24"=
,"Cascaded Incident from TTO2670307","Siligap Boris","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because Gen failed=
 to start due to due to lack on 02 phases on site //he bypassed Grid en sta=
rted the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_797","NOCINC0002860674","Messassi=
 Carrefourt","","16-08-2024 17:25:40","16-08-2024 17:08:31","16-08-2024 18:=
22:24","Cascaded Incident from TTO2670307","Delor Telezing","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","site went down because Gen=
 failed to start due to due to lack on 02 phases on site //he bypassed Grid=
 en started the Gen Manually","system","1029","16-08-2024 17:25:40","Sagemc=
om CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0002860600","Cam=
p-Sonel","IHS_YND_682, IHS_YND_111, IHS_YND_042, IHS_YND_180, IHS_YND_797, =
IHS_YND_122, IHS_YND_108, IHS_YND_189, IHS_YND_063, IHS_YND_120, IHS_YND_11=
3, IHS_YND_025, IHS_YND_109, IHS_YND_568, IHS_YND_178, IHS_YND_114, IHS_YND=
_097, IHS_YND_065, IHS_YND_566","16-08-2024 17:11:10","16-08-2024 17:08:31"=
,"16-08-2024 18:22:24","site went down because Gen failed to start due to l=
ack of 02 phases on site //he bypassed Grid and started the Gen Manually","=
Siligap Boris","Grid Supply","Passive","Grid","National Grid - Phase Contro=
ller Faulty","site went down because Gen failed to start  due to lack of 02=
 phases on site //he bypassed Grid and started the Gen Manually","emmanuel.=
ghani@ihstowers.com","160","16-08-2024 17:11:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_011","IHS_YND_196","NOCINC0002860442","P=
DC","","16-08-2024 16:36:13","16-08-2024 16:31:55","16-08-2024 18:54:42","A=
ctive//No power issue site on grid with U=3D53.8V .Eloundou Bertrand(693212=
405) from Huawei is informed site up at 04:46 PM","Mboua Thierry","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue site on grid with U=3D53.8V .Eloundou Bertrand(69=
3212405) from Huawei is informed site up at 04:46 PM","joelle.ekessi@ihstow=
ers.com","258","16-08-2024 16:36:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002859599","O=
lembe-Terminus","","16-08-2024 13:43:54","16-08-2024 12:24:46","16-08-2024 =
12:29:08"," Active// No power issue, site is on Grid with Ubaie=3D53,9V The=
 Tx FME Synphorien //6975295205// from Huawei is informed(Swapped by ZTE)",=
"Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm"," Active// No power issue, site is on Grid wit=
h Ubaie=3D53,9V The Tx FME Synphorien //6975295205// from Huawei is informe=
d(Swapped by ZTE)","adonis.defokoua@ihstowers.com","4748","16-08-2024 13:43=
:54","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0002859273","Obo=
bogo","","16-08-2024 12:42:11","16-08-2024 12:38:04","16-08-2024 12:40:10",=
"Active//No power issue on site U=3D54,2V site on Grid , The FME TX; hosiah=
/674-00-74-38 // is informed.","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No power=
 issue on site U=3D54,2V site on Grid , The FME TX; hosiah/674-00-74-38 // =
is informed.","ange.kongo@ihstowers.com","248","16-08-2024 12:42:11","Sagem=
com CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0002859255","Nom=
ayos montee Meche","","16-08-2024 12:39:28","16-08-2024 12:34:18","16-08-20=
24 13:12:50","gen  stopped//gen started manually(investigations ongoing)","=
Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"=
,"gen  stopped//gen started manually(investigations ongoing)","ange.kongo@i=
hstowers.com","310","16-08-2024 12:39:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0002859135","B=
astos Bir","","16-08-2024 12:17:17","16-08-2024 12:01:01","16-08-2024 12:50=
:29","Tx Issue : Site on  grid,Ubaie:54,5V;  Christian Hoktcheu From ZTE 69=
9295400 is informed.","Mboua Thierry","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Tx Issue : Site on  grid,=
Ubaie:54,5V;  Christian Hoktcheu From ZTE 699295400 is informed.","adonis.d=
efokoua@ihstowers.com","976","16-08-2024 12:17:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002859075","M=
arche Odza","","16-08-2024 12:01:09","16-08-2024 11:46:02","16-08-2024 12:4=
7:36","Tx Issue : site on grid,Ubaie:54,5V; clifort/696422966 From ZTE  is =
working on site.","Albran Byorel","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Tx Issue : site on grid,Ubaie=
:54,5V; clifort/696422966 From ZTE  is working on site.","adonis.defokoua@i=
hstowers.com","908","16-08-2024 12:01:09","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0002859013","Bit=
eng","","16-08-2024 11:50:01","16-08-2024 11:40:29","16-08-2024 11:51:38","=
","Mba Lazare Herve","Installation Activity","Passive","Planned Activity","=
Installation Activity","Site dow due to work of  Salif Mouyiche (GAIO)//en =
of work","ange.kongo@ihstowers.com","1673","16-08-2024 11:50:01","Sagemcom =
CMR"
"Closed Complete","Warning","T1059","IHS_YND_434","NOCINC0002858968","Donga=
","","16-08-2024 11:38:42","","","","Parker Tchoup","Warning","Warning","PO=
WER","Warning - AC Phase 1 Current Low","Site on battery  Alarm// Alarm cle=
ared","marie.kwin@ihstowers.com","29","16-08-2024 11:38:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0002858640","D=
onga","","16-08-2024 10:44:36","16-08-2024 10:26:29","16-08-2024 12:18:39",=
"Site went down because Gen was on  Manually Mode// Site put in Automatical=
ly Mode and Gen Automatically Started ","Parker Tchoup","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Control Panel","Site went down because Gen was=
 on  Manually Mode// Site put in Automatically Mode and Gen Automatically S=
tarted ","adonis.defokoua@ihstowers.com","1088","16-08-2024 10:44:36","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002858564","ELOUMDEM=
 CARRIERE 2","","16-08-2024 10:27:40","16-08-2024 10:24:12","16-08-2024 16:=
37:05","Cascaded Incident from TTO2668027","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","main gen is faulty;","system"=
,"208","16-08-2024 10:27:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002858563","Eto koss=
 Yde","","16-08-2024 10:27:40","16-08-2024 10:24:12","16-08-2024 16:37:05",=
"Cascaded Incident from TTO2668027","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","main gen is faulty;","system","208",=
"16-08-2024 10:27:40","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002858559","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","16-08-2024 10:26:24","16-08-2024 10:21=
:46","16-08-2024 16:37:05","Grid outage and Main DG faulty//Mobile DG (20 k=
va) to deployed ","Fanda Brice","Equipment Repair","Passive","ACDG Gen","AC=
DG - Generator Faulty","Grid outage and Main DG faulty//Mobile DG (20 kva) =
to deployed ","ange.kongo@ihstowers.com","2472","16-08-2024 10:26:24","Sage=
mcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0002858549","Nko=
mkana","","16-08-2024 10:24:09","16-08-2024 10:17:34","16-08-2024 10:43:30"=
,"Grid outage,no space to deploy a mobile DG.","","Grid Supply","Passive","=
Grid","National Grid - Grid Outage Issue","Grid outage,no space to deploy a=
 mobile DG.//grid return","ange.kongo@ihstowers.com","2591","16-08-2024 10:=
24:09","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0002857493","Mom=
","","16-08-2024 06:40:30","16-08-2024 06:34:59","16-08-2024 08:53:13","Gri=
d outage,Main DG faulty //Mobile DG deployed 20 kva.","Fanda Brice","Equipm=
ent Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage,Mai=
n DG faulty //Mobile DG deployed 20 kva.
","ange.kongo@ihstowers.com","605","16-08-2024 06:40:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002857364","E=
lig-Edzoa","","16-08-2024 06:03:32","16-08-2024 02:10:25","16-08-2024 06:41=
:56","Grid outage// Mobile DG deployed,power issue resolved,site remained d=
own,Although power reset done,  Armand Nguetsa is informed.","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage// Mobi=
le DG deployed, Although power issue resolved,site remained down Armand Ngu=
etsa is informed.","alexandre.kamal@ihstowers.com","13988","16-08-2024 06:0=
3:32","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0002857311","N=
yanon","","16-08-2024 05:44:24","16-08-2024 05:23:18","16-08-2024 09:34:00"=
,"","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Hybrid","Hybri=
d Module","site down due to hybrid system dysfunctionning//reset te control=
ler and gen started","alexandre.kamal@ihstowers.com","1267","16-08-2024 05:=
44:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0002857194","M=
fou EPC","","16-08-2024 05:09:30","16-08-2024 05:02:26","16-08-2024 06:34:0=
5","Grid bad voltage,DG failed to start ,site went down//Bypass Grid and ma=
nually start of DG.","Mba Lazare Herve","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","Grid bad voltage,DG failed to start =
,site went down//Bypass Grid and manually start of DG.","alexandre.kamal@ih=
stowers.com","425","16-08-2024 05:09:30","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0002856924","SAA=
 Entrance","","16-08-2024 03:52:28","16-08-2024 02:38:01","16-08-2024 05:22=
:15","Site on gen due to grid outage, site went down due to Gen contactor  =
dysfunctionned // He excited the Contactor and Gen started manually","Parke=
r Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor","=
Site on gen due to grid outage, site went down due to Gen contactor  dysfun=
ctionned // He excited the Contactor and Gen started manually","denis.mball=
a@ihstowers.com","4468","16-08-2024 03:52:28","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002856917","MAN=
GUIERS CHAPELLE","","16-08-2024 03:49:34","16-08-2024 03:40:23","16-08-2024=
 03:53:50","Grid outage, site down because Gen due to poor backup before ge=
n start//Gen started automatically (Swapped by ZTE)","Fabrice Pouakam","Equ=
ipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Gri=
d outage, site down because Gen due to poor backup before gen start//Gen st=
arted automatically (Swapped by ZTE)","denis.mballa@ihstowers.com","552","1=
6-08-2024 03:49:34","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002856852","Man=
guiers Dispensaire","","16-08-2024 03:14:03","16-08-2024 03:07:28","16-08-2=
024 04:00:59","Grid Outage, site went down due to Gen contactor  did not ex=
cited // He excited the Contactor and Gen started manually","Fabrice Pouaka=
m","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid Outag=
e, site went down due to Gen contactor  did not excited // He excited the C=
ontactor and Gen started manually","denis.mballa@ihstowers.com","395","16-0=
8-2024 03:14:03","Sagemcom CMR"
"Closed Complete","Warning","T1834","IHS_YND_132","NOCINC0002856753","Mangu=
iers Dispensaire","","16-08-2024 02:49:30","","","Grid Outage, site alarmin=
g due to Gen contactor  did not excited // He excited the Contactor and Gen=
 started manually","Fabrice Pouakam","Warning","Warning","POWER","Warning -=
 Site on Battery","Grid Outage, site alarming due to Gen contactor  did not=
 excited // He excited the Contactor and Gen started manually","stephane.nk=
amwa@ihstowers.com","2712","16-08-2024 02:49:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_720","NOCINC0002856490","SOA UNIV=
ERSITY STADIUM","","16-08-2024 01:35:23","15-08-2024 23:28:31","15-08-2024 =
23:30:53","Cascaded Incident from TTO2665602","Siligap Boris","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","Active ; No power issue on =
site U=3D54,4v site on grid Synphorien/691316854/ from Huawei is informed",=
"system","7612","16-08-2024 01:35:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_307","NOCINC0002856488","Ebogo","=
","16-08-2024 01:35:23","15-08-2024 23:28:31","15-08-2024 23:30:53","Cascad=
ed Incident from TTO2665602","Siligap Boris","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active ; No power issue on site U=3D54,4v si=
te on grid Synphorien/691316854/ from Huawei is informed","system","7612","=
16-08-2024 01:35:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_320","NOCINC0002856492","SOA TOWN=
","","16-08-2024 01:35:23","15-08-2024 23:28:31","15-08-2024 23:30:53","Cas=
caded Incident from TTO2665602","Siligap Boris","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active ; No power issue on site U=3D54,4v=
 site on grid Synphorien/691316854/ from Huawei is informed","system","7612=
","16-08-2024 01:35:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0002856489","Akak-Nko=
zoa-MTN-IHS","","16-08-2024 01:35:23","15-08-2024 23:28:31","15-08-2024 23:=
30:53","Cascaded Incident from TTO2665602","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Active ; No power issue on s=
ite U=3D54,4v site on grid Synphorien/691316854/ from Huawei is informed","=
system","7612","16-08-2024 01:35:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0002856411","S=
oa-II","IHS_YND_307, IHS_YND_316, IHS_YND_720, IHS_YND_324, IHS_YND_320","1=
6-08-2024 01:22:42","15-08-2024 23:28:31","15-08-2024 23:30:53","Active ; N=
o power issue on site U=3D54,4v site on grid Synphorien/691316854/ from Hua=
wei is informed","Siligap Boris","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active ; No power issue on sit=
e U=3D54,4v site on grid Synphorien/691316854/ from Huawei is informed","al=
exandre.kamal@ihstowers.com","6851","16-08-2024 01:22:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002856295","MBIMBIM"=
,"","16-08-2024 01:17:00","15-08-2024 23:08:44","16-08-2024 03:46:36","Sola=
r Gen, Site went down because gen runned and stopped due to alarm undervolt=
age//he reset the Gen card and started it","Parker Tchoup","Equipment Repai=
r","Passive","ACDG Gen","ACDG - Control Panel","Solar Gen, Site went down b=
ecause gen runned and stopped due to alarm undervoltage//he reset the Gen c=
ard and started it","system","7696","16-08-2024 01:17:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0002856291","Mbankolo=
 petit paris","","16-08-2024 01:15:20","16-08-2024 01:07:08","16-08-2024 02=
:10:15","Cascaded Incident from TTO2665458","Mboua Thierry","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid Outage, site went dow=
n because gen failed to start due to battery Gen faulty// Gen manually star=
ted with external battery (Swapped by ZTE)","system","492","16-08-2024 01:1=
5:20","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0002856287","AFE=
ME NORD","IHS_YND_808","16-08-2024 01:14:22","16-08-2024 01:04:08","16-08-2=
024 02:10:18","Grid Outage, site went down because gen failed to start due =
to battery Gen faulty// Gen manually started with external battery (Swapped=
 by ZTE)","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen=
","ACDG - Generator Battery","Grid Outage, site went down because gen faile=
d to start due to battery Gen faulty// Gen manually started with external b=
attery (Swapped by ZTE)","denis.mballa@ihstowers.com","2231","16-08-2024 01=
:14:22","Sagemcom CMR"
"Cancelled","Warning","CTR_317","IHS_YND_322","NOCINC0002856186","Soa-II","=
","16-08-2024 00:41:03","","","","Siligap Boris","","","","","","alexandre.=
kamal@ihstowers.com","725","16-08-2024 00:41:03","Sagemcom CMR"
"Closed Complete","Warning","T1059","IHS_YND_434","NOCINC0002855857","Donga=
","","15-08-2024 23:29:02","","","Site alarming due to hybrid system failur=
e//gen manually started ","Parker Tchoup","Warning","Warning","POWER","Warn=
ing - Site on Battery","Site alarming due to hybrid system failure//gen man=
ually started ","stephane.nkamwa@ihstowers.com","3147","15-08-2024 23:29:02=
","Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0002855797","Don=
ga","","15-08-2024 23:12:59","15-08-2024 23:08:44","16-08-2024 01:23:55","S=
ite went down and gen failed to startet due to missing of neural phase at t=
he terminal block//we reconnected the neural phase and site on gen ","Parke=
r Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","S=
ite went down and gen failed to startet due to missing of neural phase at t=
he terminal block//we reconnected the neural phase and site on gen ","denis=
.mballa@ihstowers.com","256","15-08-2024 23:12:59","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0002855748","SAA=
 Entrance","","15-08-2024 23:02:37","15-08-2024 22:57:24","15-08-2024 23:12=
:33","grid outage, site went down because gen failed to start due to relay =
220 and contactor Gen faulty// He bypassed and excited the Grid contactor, =
Site on Grid","Parker Tchoup","Equipment Repair","Passive","Control Panel",=
"ATS-AMF Issue","grid outage, site went down because gen failed to start du=
e to relay 220 and contactor Gen faulty// He bypassed and excited the Grid =
contactor, Site on Grid","denis.mballa@ihstowers.com","313","15-08-2024 23:=
02:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0002854748","O=
mnisport-Rail","","15-08-2024 20:10:59","15-08-2024 18:28:53","15-08-2024 1=
8:35:10","Active: No power issue, site is on Grid  with Ubaie=3D54,5V, THE =
fme Armand Ngetsa(691144412)  from Huawei is informed( Site swap by ZTE.)",=
"Delor Telezing","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active: No power issue, site is on Grid  with =
Ubaie=3D54,5V, THE fme Armand Ngetsa(691144412)  from Huawei is informed( S=
ite swap by ZTE.)","landry.etame@ihstowers.com","6127","15-08-2024 20:10:59=
","Sagemcom CMR"
"Closed Complete","Warning","CTR_079","IHS_YND_306","NOCINC0002854134","Nko=
zoa","","15-08-2024 17:46:03","","","site is on Battery due to theTechnicia=
n was working on site (normalization cables power)//End of works","Fabrice =
Pouakam","Warning","Warning","POWER","Warning - Site on Battery","site is o=
n Battery due to theTechnician was working on site (normalization cables po=
wer)//End of works","nadjia.njaya@ihstowers.com","322","15-08-2024 17:46:03=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002853839","MBIMBIM"=
,"","15-08-2024 17:04:20","15-08-2024 16:52:41","15-08-2024 19:33:48","Casc=
aded Incident from TTO2662789 - Cascade Removed From TTO2662789","Parker Tc=
houp","Cascade Outage","Active","Cascade Active","Cascade Active","No Power=
 issue on site Ubaie 55.2V Site on GE. FME TX_Willy: 6 50 25 43 98 is infor=
med via Call","system","699","15-08-2024 17:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002853835","Matsari"=
,"","15-08-2024 17:04:20","15-08-2024 16:52:41","15-08-2024 19:33:48","Casc=
aded Incident from TTO2662789 - Cascade Removed From TTO2662789","Parker Tc=
houp","Cascade Outage","Active","Cascade Active","Cascade Active","No Power=
 issue on site Ubaie 55.2V Site on GE. FME TX_Willy: 6 50 25 43 98 is infor=
med via Call","system","699","15-08-2024 17:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002853836","Yoko OCM=
","","15-08-2024 17:04:20","15-08-2024 16:52:41","15-08-2024 19:33:48","Cas=
caded Incident from TTO2662789 - Cascade Removed From TTO2662789","Parker T=
choup","Cascade Outage","Active","Cascade Active","Cascade Active","No Powe=
r issue on site Ubaie 55.2V Site on GE. FME TX_Willy: 6 50 25 43 98 is info=
rmed via Call","system","699","15-08-2024 17:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002853837","Ngouetou=
","","15-08-2024 17:04:20","15-08-2024 16:52:41","15-08-2024 19:33:48","Cas=
caded Incident from TTO2662789 - Cascade Removed From TTO2662789","Parker T=
choup","Cascade Outage","Active","Cascade Active","Cascade Active","No Powe=
r issue on site Ubaie 55.2V Site on GE. FME TX_Willy: 6 50 25 43 98 is info=
rmed via Call","system","699","15-08-2024 17:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002853834","Ngoum","=
","15-08-2024 17:04:20","15-08-2024 16:52:41","15-08-2024 19:33:48","Cascad=
ed Incident from TTO2662789 - Cascade Removed From TTO2662789","Parker Tcho=
up","Cascade Outage","Active","Cascade Active","Cascade Active","No Power i=
ssue on site Ubaie 55.2V Site on GE. FME TX_Willy: 6 50 25 43 98 is informe=
d via Call","system","699","15-08-2024 17:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_808","NOCINC0002853654","Mbankolo=
 petit paris","","15-08-2024 16:32:30","15-08-2024 16:21:49","15-08-2024 17=
:17:16","Cascaded Incident from TTO2662592","Mboua Thierry","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","Grid outage site went down=
 because Gen failed to start with alarm Digital  input// He reset the Gen c=
ard and Gen manually started","system","641","15-08-2024 16:32:30","Sagemco=
m CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0002853647","AFE=
ME NORD","IHS_YND_808","15-08-2024 16:30:54","15-08-2024 16:21:49","15-08-2=
024 17:17:16","Grid outage site went down because Gen failed to start with =
alarm Digital  input// He reset the Gen card and Gen manually started","TIE=
NTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid outage site went down because Gen failed to start with ala=
rm Digital  input// He reset the Gen card and Gen manually started","kouoh.=
jean@ihstowers.com","546","15-08-2024 16:30:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0002853557","M=
anguier","","15-08-2024 16:09:46","15-08-2024 12:07:41","15-08-2024 16:20:2=
3","Grid outage site went down because Gen failed to start due to poor batt=
ery Backup// Grid power return(Swapped by ZTE)","Fabrice Pouakam","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age site went down because Gen failed to start due to poor battery Backup//=
 Grid power return(Swapped by ZTE)","landry.etame@ihstowers.com","14526","1=
5-08-2024 16:09:46","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0002853439","SAA=
 Entrance","","15-08-2024 15:34:43","15-08-2024 15:28:10","15-08-2024 15:32=
:47","site went down because 01/02 rectifer  faulty due to over current// H=
e replaced the rectifier on site","Parker Tchoup","Equipment Repair","Passi=
ve","Rectifier","Rectifier Module","site went down because 01/02 rectifer  =
faulty due to over current// He replaced the rectifier on site","kouoh.jean=
@ihstowers.com","394","15-08-2024 15:34:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_036","IHS_YND_334","NOCINC0002853206","M=
fou OCM","","15-08-2024 15:02:40","15-08-2024 14:58:26","15-08-2024 15:10:3=
5","Active: No power issue, site is on Gen with Ubaie=3D54,2 V, the Fme TX =
lionel tchatchoua(694693436) from Huawei is informed (Swapped by ZTE)","Mba=
 Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active: No power issue, site is on Gen with Ubai=
e=3D54,2 V, the Fme TX lionel tchatchoua(694693436) from Huawei is informed=
 (Swapped by ZTE)","landry.etame@ihstowers.com","255","15-08-2024 15:02:40"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0002853122","Boumnyeb=
el","","15-08-2024 14:50:30","15-08-2024 14:35:48","15-08-2024 14:40:01","C=
ascaded Incident from TTO2661981","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active, no power issue on site, U=3D5=
5.7V on Grid The tx FME Etienne FOPA /651320188/ From Huawei is informed","=
system","882","15-08-2024 14:50:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0002853121","Ngog Map=
ubi","","15-08-2024 14:50:30","15-08-2024 14:35:48","15-08-2024 14:40:01","=
Cascaded Incident from TTO2661981","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active, no power issue on site, U=3D=
55.7V on Grid The tx FME Etienne FOPA /651320188/ From Huawei is informed",=
"system","882","15-08-2024 14:50:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0002853123","Mamb",""=
,"15-08-2024 14:50:30","15-08-2024 14:35:48","15-08-2024 14:40:01","Cascade=
d Incident from TTO2661981","Kemeni Franklin","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active, no power issue on site, U=3D55.7V o=
n Grid The tx FME Etienne FOPA /651320188/ From Huawei is informed","system=
","882","15-08-2024 14:50:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0002853120","Ndogbess=
ol","","15-08-2024 14:50:30","15-08-2024 14:35:48","15-08-2024 14:40:01","C=
ascaded Incident from TTO2661981","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active, no power issue on site, U=3D5=
5.7V on Grid The tx FME Etienne FOPA /651320188/ From Huawei is informed","=
system","882","15-08-2024 14:50:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0002853104","B=
oumnyebel OCM","IHS_EDA_056, IHS_YND_419, IHS_YND_381, IHS_YND_376","15-08-=
2024 14:48:54","15-08-2024 14:35:48","15-08-2024 16:10:25","Active, no powe=
r issue on Active, no power issue on site, U=3D55.7V on Grid The tx FME Eti=
enne FOPA /651320188/ From Huawsite, U=3D55.7V on Grid The tx FME Etienne F=
OPA /651320188/ From Huawei is informed","Kemeni Franklin","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve, no power issue on site, U=3D55.7V on Grid The tx FME Etienne FOPA /6513=
20188/ From Huawei is informed","landry.etame@ihstowers.com","787","15-08-2=
024 14:48:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0002852839","N=
kozoa","","15-08-2024 13:55:39","15-08-2024 13:55:31","15-08-2024 14:00:57"=
,"site on battery","Fabrice Pouakam","Incorrectly Logged Tickets","Error","=
Error","Error","wrong ticket","kombi.samuel@ihstowers.com","8","15-08-2024 =
13:55:39","Sagemcom CMR"
"Closed Complete","Warning","T1551","IHS_YND_316","NOCINC0002852735","Akak-=
Nkozoa-MTN-IHS","","15-08-2024 13:30:45","","","Site  ON BATTERY due to gri=
d bad voltage //Voltage normalized.","Fabrice Pouakam","Warning","Warning",=
"POWER","Warning - National Grid - Grid Incomplete Phase","Site  ON BATTERY=
 due to grid bad voltage //Voltage normalized.","kombi.samuel@ihstowers.com=
","5","15-08-2024 13:30:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0002851891","N=
kozoa","","15-08-2024 11:13:48","15-08-2024 11:09:20","15-08-2024 11:31:03"=
,"No power issue on site U=3D54v site on grid Synphorien of huawei is infor=
med up at 11:13","Fabrice Pouakam","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
4v site on grid Synphorien of huawei is informed up at 11:13","joelle.ekess=
i@ihstowers.com","269","15-08-2024 11:13:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0002851612","M=
endong","","15-08-2024 10:33:20","15-08-2024 10:22:16","15-08-2024 11:32:25=
","No power issue on site U=3D54,6v site on gen Team Fabrice/690945875/ZTE =
working on site","Hyemafo Gildas","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54=
,6v site on gen Team Fabrice/690945875/ZTE working on site","joelle.ekessi@=
ihstowers.com","664","15-08-2024 10:33:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0002851532","O=
mnisport-Rail","","15-08-2024 10:14:00","15-08-2024 08:26:54","15-08-2024 1=
1:32:25","ACTIVE No power issue on site, site on Grid with Ubaie=3D54,5V Tx=
 fme Armand Ngeuts from Huawei is Informed, Notice that we have disjunction=
 at BTS OCM (Swapped by ZTE)","Delor Telezing","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power =
issue on site, site on Grid with Ubaie=3D54,5V Tx fme Armand Ngeuts from Hu=
awei is Informed, Notice that we have disjunction at BTS OCM (Swapped by ZT=
E)","joelle.ekessi@ihstowers.com","6426","15-08-2024 10:14:00","Sagemcom CM=
R"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0002850958","Bas=
tos Bethesda","","15-08-2024 08:42:47","15-08-2024 08:40:43","15-08-2024 08=
:46:43","Grid outage, site down because Gen due to poor backup before gen s=
tart//Gen started automatically","Mboua Thierry","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site down be=
cause Gen due to poor backup before gen start//Gen started automatically","=
emmanuel.ghani@ihstowers.com","125","15-08-2024 08:42:47","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002850949","Mok=
olo Yaounde","","15-08-2024 08:41:52","15-08-2024 08:40:49","15-08-2024 08:=
48:49","Grid outage,no space to deploy a mobil DG// grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no=
 space to deploy a mobil DG// grid return","emmanuel.ghani@ihstowers.com","=
64","15-08-2024 08:41:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0002850913","M=
obil-Kondengui","","15-08-2024 08:34:08","15-08-2024 07:55:59","15-08-2024 =
09:05:43","site went down due to disjunction Cb(80A) and (125A) faulty// He=
 did a bridge with CB 63A,and replaced the faulty CB with 63A bipolaire (Sw=
apped by ZTE)","","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Circuit Breaker Issue","site went down due to disjunction Cb(80A) and =
(125A) faulty// He did a bridge with CB 63A,and replaced the faulty CB with=
 63A bipolaire (Swapped by ZTE)","joelle.ekessi@ihstowers.com","2289","15-0=
8-2024 08:34:08","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0002850808","Mba=
nkolo petit paris","","15-08-2024 08:14:19","15-08-2024 08:10:20","15-08-20=
24 09:04:56","site went down because gen ran till fuel shortage//Refueling =
done","Mboua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","sit=
e went down because gen ran till fuel shortage//Refueling done","emmanuel.g=
hani@ihstowers.com","239","15-08-2024 08:14:19","Sagemcom CMR"
"Closed Complete","Site Down","T3447","IHS_YND_713","NOCINC0002850791","NKO=
NGKARAK","","15-08-2024 08:04:26","15-08-2024 07:05:17","15-08-2024 09:17:1=
7","site went down because gen stopped with alarm high temp//he added water=
 in radiator","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG=
 Gen","ACDG - High Engine Temp - Coolant Level Issue","site went down becau=
se gen stopped with alarm high temp//he added water in radiator","emmanuel.=
ghani@ihstowers.com","3549","15-08-2024 08:04:26","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002850754","Nko=
g-Edzen","","15-08-2024 07:51:46","15-08-2024 07:44:43","15-08-2024 08:04:5=
7","No power issue site on genwith U=3D54,9v Gregoire(654547479) from Huawe=
i is informed ","Parker Tchoup","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on genwith =
U=3D54,9v Gregoire(654547479) from Huawei is informed ","emmanuel.ghani@ihs=
towers.com","423","15-08-2024 07:51:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0002848666","SAA Entr=
ance","","15-08-2024 01:58:14","15-08-2024 01:53:04","15-08-2024 02:26:04",=
"grid outage, site went down because gen failed to start due to relay 220 a=
nd gen contactor  faulty// He changed relay 220 , site on Grid (gen contact=
or to be replaced)","Parker Tchoup","Equipment Repair","Passive","ACDG Gen"=
,"ACDG - Relay Faulty","grid outage, site went down because gen failed to s=
tart due to relay 220 and gen contactor  faulty// He changed relay 220 , si=
te on Grid (gen contactor to be replaced)","olivier.kwedi@ihstowers.com","3=
10","15-08-2024 01:58:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0002847555","M=
om","","14-08-2024 22:24:21","14-08-2024 22:14:50","15-08-2024 00:37:11","g=
rid outage, site went down due to main gen faulty// MDG 20kva has deployed"=
,"Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Fa=
ulty","grid outage, site went down due to main gen faulty// MDG 20kva has d=
eployed","dorothy.djantio@ihstowers.com","571","14-08-2024 22:24:21","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0002847415","M=
obil-Kondengui","","14-08-2024 21:55:30","14-08-2024 21:23:21","14-08-2024 =
23:36:09","","","Equipment Repair","Passive","Power","RT_Faulty Power Cable=
","disjonction des disjoncteurs DC 125A et 80A dans la baie d'=E9nergie ","=
alexandre.kamal@ihstowers.com","1929","14-08-2024 21:55:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0002847332","O=
mnisport-Rail","","14-08-2024 21:43:13","14-08-2024 20:46:05","15-08-2024 0=
1:30:38","ACTIVE No power issue on site, site on Grid with Ubaie=3D56,2V Tx=
 fme Armand Ngeuts from Huawei is Informed, Notice that we have disjunction=
 at BTS OCM (Swapped by ZTE)","Delor Telezing","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power =
issue on site, site on Grid with Ubaie=3D56,2V Tx fme Armand Ngeuts from Hu=
awei is Informed, Notice that we have disjunction at BTS OCM (Swapped by ZT=
E)","alexandre.kamal@ihstowers.com","3428","14-08-2024 21:43:13","Sagemcom =
CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002847243","Nko=
abang Ebolmedjock","","14-08-2024 21:35:04","14-08-2024 21:25:53","15-08-20=
24 02:12:31","Active, No power issue, site on gen with U=3D51,1V The FME tx=
 Lionel ADJEP/655184876/ from huawei is informed ","Mba Lazare Herve","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active, No power issue, site on gen with U=3D51,1V The FME tx Lionel=
 ADJEP/655184876/ from huawei is informed ","denis.mballa@ihstowers.com","5=
51","14-08-2024 21:35:04","Sagemcom CMR"
"Closed Complete","Site Down","T0468","IHS_YND_120","NOCINC0002846642","Sap=
eur Mimboman","","14-08-2024 20:04:22","14-08-2024 20:04:12","14-08-2024 20=
:05:17","No power issue site on grid with U=3D52.7v Lionnel Steeve(65518487=
6) from Huawei is informed ","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
site on grid with U=3D52.7v Lionnel Steeve(655184876) from Huawei is inform=
ed ","denis.mballa@ihstowers.com","11","14-08-2024 20:04:22","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0002845604","Nko=
londom","","14-08-2024 17:20:04","14-08-2024 17:14:52","14-08-2024 18:50:58=
","site went down due to 2/3 rectifier disfunctionning//he reset the rectif=
iers :site on grid  (swapped by ZTE)","Fabrice Pouakam","Equipment Repair",=
"Passive","Rectifier","Rectifier Module","site went down due to 2/3 rectifi=
er disfunctionning//he reset the rectifiers :site on grid  (swapped by ZTE)=
","denis.mballa@ihstowers.com","1790","14-08-2024 17:20:04","Sagemcom CMR"
"Closed Complete","Warning","T2149","IHS_EDA_056","NOCINC0002845599","Ndogb=
essol","","14-08-2024 17:18:26","","","site went down because Gen Failed to=
 start due to Hybride system dysfonction// He reset the Gen card and Gen ma=
nually started ","Kemeni Franklin","Warning","Warning","POWER","Warning - S=
ite on Battery","site went down because Gen Failed to start due to Hybride =
system dysfonction// He reset the Gen card and Gen manually started ","deni=
s.mballa@ihstowers.com","187","14-08-2024 17:18:26","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0002845598","N=
dogbessol","","14-08-2024 17:18:09","14-08-2024 17:10:05","14-08-2024 22:24=
:38","site went down because Gen Failed to start due to Hybride system dysf=
onction// He reset the Gen card and Gen manually started ","Kemeni Franklin=
","Equipment Repair","Passive","Hybrid","Hybrid Module","site went down bec=
ause Gen Failed to start due to Hybride system dysfonction// He reset the G=
en card and Gen manually started ","alexandre.kamal@ihstowers.com","484","1=
4-08-2024 17:18:09","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_280","NOCINC0002845223","Messassi 2=
","","14-08-2024 16:22:37","","","","Fabrice Pouakam","Warning","Warning","=
POWER","Warning - Site on Battery","site on alarm due to grid bad voltage//=
gen started and alarm cleared","ludovic.tchagna@ihstowers.com","727","14-08=
-2024 16:22:37","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_280","NOCINC0002845220","Messassi 2=
","","14-08-2024 16:21:37","","","site on alarm due to grid outage//Gen sta=
rted","Fabrice Pouakam","Warning","Warning","POWER","Warning - Site on Batt=
ery","site on alarm due to grid outage//Gen started","denis.mballa@ihstower=
s.com","3","14-08-2024 16:21:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0002845183","Etoudi 2=
","","14-08-2024 16:15:10","14-08-2024 16:07:50","14-08-2024 16:48:40","Cas=
caded Incident from TTO2653475","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,gen failed to start due =
to grid bad voltage//he bypassed grid and started the gen","system","440","=
14-08-2024 16:15:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0002845182","ETOUDI C=
HAPELLE","","14-08-2024 16:15:10","14-08-2024 16:07:50","14-08-2024 16:48:4=
0","Cascaded Incident from TTO2653475","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,gen failed to star=
t due to grid bad voltage//he bypassed grid and started the gen","system","=
440","14-08-2024 16:15:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0002845181","Abattoir=
","","14-08-2024 16:15:10","14-08-2024 16:07:50","14-08-2024 16:48:40","Cas=
caded Incident from TTO2653475","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,gen failed to start due =
to grid bad voltage//he bypassed grid and started the gen","system","440","=
14-08-2024 16:15:10","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0002845176","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","14-08-2024 16:14:03","14-08-2=
024 16:07:50","14-08-2024 16:48:40","Grid outage,gen failed to start due to=
 grid bad voltage//he bypassed grid and started the gen","Fabrice Pouakam",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","G=
rid outage,gen failed to start due to grid bad voltage//he bypassed grid an=
d started the gen","denis.mballa@ihstowers.com","373","14-08-2024 16:14:03"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002845063","Mim=
boman3","","14-08-2024 15:50:22","14-08-2024 15:29:06","14-08-2024 15:57:33=
","Grid outage, site down because Gen due to poor backup before gen start//=
Gen started automatically (Site Swaped by ZTE)","Mba Lazare Herve","Equipme=
nt Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid ou=
tage, site down because Gen due to poor backup before gen start//Gen starte=
d automatically (Site Swaped by ZTE)","denis.mballa@ihstowers.com","1277","=
14-08-2024 15:50:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0002845023","C=
lge-Advantiste","","14-08-2024 15:41:13","14-08-2024 13:54:08","14-08-2024 =
14:00:52","No power issue site on grid with U=3D53v Notice that we have dys=
junction at OCM equipements Lionnel Steeve(655184876) from Huawei is inform=
ed","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53v No=
tice that we have dysjunction at OCM equipements Lionnel Steeve(655184876) =
from Huawei is informed","alexandre.kamal@ihstowers.com","6426","14-08-2024=
 15:41:13","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002844724","Bas=
tos Amb Coree","","14-08-2024 15:00:35","14-08-2024 14:58:19","14-08-2024 1=
5:00:48","site went down because insufficiency of rectifiers (site on 02 re=
ctifiers)due to increase load on site // site Stabilized","","Equipment Rep=
air","Passive","Rectifier","Rectifier Module","site went down because insuf=
ficiency of rectifiers (site on 02 rectifiers)due to increase load on site =
// site Stabilized","denis.mballa@ihstowers.com","137","14-08-2024 15:00:35=
","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_297","NOCINC0002844622","Messassi",=
"","14-08-2024 14:41:24","","","site on alarm due to grid outage//gen start=
ed and alarm cleared","Fabrice Pouakam","Warning","Warning","POWER","Warnin=
g - Site on Battery","site on alarm due to grid outage//gen started and ala=
rm cleared","ludovic.tchagna@ihstowers.com","4","14-08-2024 14:41:24","Sage=
mcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002844286","Nko=
g-Edzen","","14-08-2024 13:53:25","14-08-2024 13:48:09","14-08-2024 13:50:0=
6","Active: No power issue on site, Ubai =3D 56.4 V on Gen the tx fme Grego=
ire /652070658 /   from HUAWEI is informed  ","Parker Tchoup","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive: No power issue on site, Ubai =3D 56.4 V on Gen the tx fme Gregoire /=
652070658 /   from HUAWEI is informed  ","kouoh.jean@ihstowers.com","317","=
14-08-2024 13:53:25","Sagemcom CMR"
"Closed Complete","Warning","T0030","IHS_YND_041","NOCINC0002844023","Lycee=
 Leclerc School","","14-08-2024 12:51:59","","","Site alarming because Alph=
onse/IHS working on site// End of work","Paul BIBOUM","Warning","Warning","=
POWER","Warning - Site on Battery","Site alarming because Alphonse/IHS work=
ing on site// End of work","kouoh.jean@ihstowers.com","190","14-08-2024 12:=
51:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_125","IHS_YND_096","NOCINC0002843748","M=
obil-Kondengui","","14-08-2024 12:07:41","14-08-2024 12:01:17","14-08-2024 =
12:20:11","Active, no power issue, site on grid with U=3D54,3V, Team olivie=
r /677269888/ From ZTE is working on site","","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power =
issue, site on grid with U=3D54,3V, Team olivier /677269888/ From ZTE is wo=
rking on site","landry.etame@ihstowers.com","384","14-08-2024 12:07:41","Sa=
gemcom CMR"
"Closed Complete","Warning","T1059","IHS_YND_434","NOCINC0002843744","Donga=
","","14-08-2024 12:06:55","","","Site alarming with Hybrid gen site//gen s=
tart automaticallly","Parker Tchoup","Warning","Warning","POWER","Warning -=
 Site on Battery","Site alarming with Hybrid gen site//gen start automatica=
llly","marie.kwin@ihstowers.com","3","14-08-2024 12:06:55","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002843729","MAN=
GUIERS CHAPELLE","","14-08-2024 12:04:44","14-08-2024 11:54:33","14-08-2024=
 12:06:52","","Fabrice Pouakam","Equipment Replacement","Passive","Planned =
Activity","Planned Activity - Site Inspection","Management Center Region  i=
s on-site  // End of inspection","kouoh.jean@ihstowers.com","612","14-08-20=
24 12:04:44","Sagemcom CMR"
"Closed Complete","Warning","CTR_446","IHS_YND_509","NOCINC0002843615","MAN=
GUIERS CHAPELLE","","14-08-2024 11:42:53","","","Alphonse Deufo is on site =
for   HandOver","Fabrice Pouakam","Warning","Warning","Unlisted RCA","Warni=
ng - Others","Management Center Region  is on-site  // End of inspection","=
kouoh.jean@ihstowers.com","157","14-08-2024 11:42:53","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002843124","Tsi=
nga","","14-08-2024 10:10:49","14-08-2024 10:02:39","14-08-2024 10:24:02","=
Site went down because controller of Huawei faulty// site stabilized  (cont=
roller to be replaced)","Mboua Thierry","Equipment Repair","Passive","Hybri=
d","Hybrid Module","Site went down because controller of Huawei faulty// si=
te stabilized  (controller to be replaced)","kouoh.jean@ihstowers.com","491=
","14-08-2024 10:10:49","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0002842953","Ako=
no","IHS_YND_687","14-08-2024 09:39:18","14-08-2024 09:22:12","14-08-2024 0=
9:29:12","Grid fluctuation site went down because Gen faled to start due to=
 NO RCP on site // Gen manually started","Fanda Brice","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid fluctuation site=
 went down because Gen faled to start due to NO RCP on site // Gen manually=
 started","kouoh.jean@ihstowers.com","1027","14-08-2024 09:39:18","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0002842936","Lobo OCM=
","","14-08-2024 09:34:40","14-08-2024 08:06:11","14-08-2024 08:12:02","Cas=
caded Incident from TTO2650929","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automaticaly","sy=
stem","5309","14-08-2024 09:34:40","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002842928","N=
KOMEKUI OCM","IHS_YND_341","14-08-2024 09:34:08","14-08-2024 08:06:11","14-=
08-2024 08:12:02","Grid outage, site went down before gen start due to poor=
 battery backup // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 outage, site went down before gen start due to poor battery backup // Gen =
start automaticaly","marie.kwin@ihstowers.com","5277","14-08-2024 09:34:08"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0002842904","N=
KONGKARAK","","14-08-2024 09:29:57","14-08-2024 08:07:38","14-08-2024 08:15=
:24","no power issue  on site, tx issue no power issue on site U=3D54v site=
 on Gen Mohamadou /6911144435 of huawei is informed  ","TIENTCHEU NZETCHIEU=
 GAEL","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","no power issue  on site, tx issue no power issue on site=
 U=3D54v site on Gen Mohamadou /6911144435 of huawei is informed  ","marie.=
kwin@ihstowers.com","4940","14-08-2024 09:29:57","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0002842849","OLA=
MA","","14-08-2024 09:16:18","14-08-2024 09:22:12","14-08-2024 09:29:12","f=
me is on the way eta=3D09:50","Fanda Brice","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Grid fluctuation site went down because Ge=
n faled to start due to NO RCP on site // Gen manually started","kouoh.jean=
@ihstowers.com","1108","14-08-2024 09:16:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0002842207","S=
apeur","","14-08-2024 06:43:54","13-08-2024 19:23:45","13-08-2024 19:30:22"=
,"No power issue site on grid with U=3D53,5v Notice that we have disjunctio=
n at OCM equipements Brice Tsague(650214096) from Huawei is informed ( Site=
 swap by ZTE.)","Mboua Thierry","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wit=
h U=3D53,5v Notice that we have disjunction at OCM equipements Brice Tsague=
(650214096) from Huawei is informed ( Site swap by ZTE.)","landry.etame@ihs=
towers.com","40810","14-08-2024 06:43:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0002842202","M=
ANGUIERS CHAPELLE","","14-08-2024 06:41:56","13-08-2024 19:41:48","13-08-20=
24 19:45:16","Active: No power issue, site is on GEN  with Ubaie=3D53,5V, T=
HE fme Armand Ngetsa(691144412)  from Huawei is informed( Site swap by ZTE.=
)","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Active: No power issue, site is on GEN  wi=
th Ubaie=3D53,5V, THE fme Armand Ngetsa(691144412)  from Huawei is informed=
( Site swap by ZTE.)","landry.etame@ihstowers.com","39609","14-08-2024 06:4=
1:56","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0002841604","Nko=
londom","","14-08-2024 02:37:32","14-08-2024 02:33:24","14-08-2024 03:22:54=
","Site went down because the CB(63*2A) of PWC dysjoncted due to load incre=
ase //He reamed the Cb","Fabrice Pouakam","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","Site went down because=
 the CB(63*2A) of PWC dysjoncted due to load increase //He reamed the Cb","=
ange.kongo@ihstowers.com","249","14-08-2024 02:37:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0002841520","SAA Entr=
ance","","14-08-2024 02:14:00","14-08-2024 02:07:04","14-08-2024 04:07:50",=
"Cascaded Incident from TTO2649351","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, gen start and stoppen=
 due to belt cut// He changed  belt, site on gen","system","416","14-08-202=
4 02:14:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0002841521","Saa","",=
"14-08-2024 02:14:00","14-08-2024 02:07:04","14-08-2024 04:07:50","Cascaded=
 Incident from TTO2649351","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","grid outage, gen start and stoppen due to b=
elt cut// He changed  belt, site on gen","system","416","14-08-2024 02:14:0=
0","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0002841519","SAA=
 2","IHS_YND_542, IHS_YND_405","14-08-2024 02:13:17","14-08-2024 02:03:35",=
"14-08-2024 04:07:50","grid outage, gen start and stoppen due to belt cut//=
 He changed  belt, site on gen","Parker Tchoup","Equipment Repair","Passive=
","ACDG Gen","ACDG - Fan Belt","grid outage, gen start and stoppen due to b=
elt cut// He changed  belt, site on gen","ange.kongo@ihstowers.com","968","=
14-08-2024 02:13:17","Sagemcom CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0002841464","NKO=
ABANG NKOLO 3","","14-08-2024 01:50:40","14-08-2024 01:48:18","14-08-2024 0=
2:19:59","Active: no power issue, site is on gen with Ubaie=3D51.2V, lionel=
 adjep (655184876) from Huawei is informed","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active: no power issue, site is on gen with Ubaie=3D51.2V, lionel adjep (65=
5184876) from Huawei is informed","ange.kongo@ihstowers.com","142","14-08-2=
024 01:50:40","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0002841396","N=
yanon","","14-08-2024 01:25:33","14-08-2024 00:48:25","14-08-2024 01:44:09"=
,"site went down because gen failed to start due to gen card dysfunctionnin=
g// He reset gen card and gen manually started","TIENTCHEU NZETCHIEU GAEL",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","site went d=
own because gen failed to start due to gen card dysfunctionning// He reset =
gen card and gen manually started","adonis.defokoua@ihstowers.com","2229","=
14-08-2024 01:25:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0002841302","N=
R-Bastos","","14-08-2024 00:33:43","13-08-2024 21:00:33","13-08-2024 22:01:=
46","Access issue during the nigh due to landload, grid outage// grid retur=
n (site swapped by ZTE)","","Access Denial","Lease Or Legal","Landlord Rela=
ted Issues","Access Issue - Land Lord","Access issue during the nigh due to=
 landload, grid outage// grid return (site swapped by ZTE)","adonis.defokou=
a@ihstowers.com","12791","14-08-2024 00:33:43","Sagemcom CMR"
"Closed Complete","Site Down","T1259","IHS_YND_424","NOCINC0002841263","Oss=
ombe","","14-08-2024 00:15:22","14-08-2024 00:08:27","14-08-2024 03:04:10",=
"site went down because gen ran until fuel shortage // refueling done","Par=
ker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","site went dow=
n because gen ran until fuel shortage // refueling done","ange.kongo@ihstow=
ers.com","1208","14-08-2024 00:15:22","Sagemcom CMR"
"Closed Complete","Warning","T0091","IHS_YND_314","NOCINC0002841013","Sous =
Prefecture","","13-08-2024 22:48:51","","","Site on battery","Fanda Brice",=
"Warning","Warning","POWER","Warning - Site on Battery","Site on battery","=
alwine.fambou@ihstowers.com","4","13-08-2024 22:48:51","Sagemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0002840994","San=
ta Barbara Gottam","","13-08-2024 22:39:27","13-08-2024 22:30:17","13-08-20=
24 23:04:46","site went down because gen failed start due to grid bad volta=
ge // gen started manually","Delor Telezing","Equipment Repair","Passive","=
ACDG Gen","ACDG - Control Panel","site went down because gen failed start d=
ue to grid bad voltage // gen started manually","ange.kongo@ihstowers.com",=
"551","13-08-2024 22:39:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_011","IHS_YND_196","NOCINC0002840394","P=
DC","","13-08-2024 20:53:22","13-08-2024 20:51:16","13-08-2024 20:53:47","N=
o power issue site on grid with U=3D53.9v Eloundou Bertrand(693212405) from=
 Huawei is informed site up at 08:53 PM","Mboua Thierry","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue site on grid with U=3D53.9v Eloundou Bertrand(693212405) from Huaw=
ei is informed site up at 08:53 PM","dorothy.djantio@ihstowers.com","126","=
13-08-2024 20:53:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0002840324","S=
ous Prefecture","","13-08-2024 20:40:20","13-08-2024 20:33:13","13-08-2024 =
21:52:51","site went down due to CB(125A) disjuncted in DC-Box//he reamed t=
he CB,Power issue resolved but site remains down Alain(691144423) from Huaw=
ei is informed ,Email of soft reset has done","Fanda Brice","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","site=
 went down due to CB(125A) disjuncted in DC-Box//he reamed the CB,Power iss=
ue resolved but site remains down Alain(691144423) from Huawei is informed =
,Email of soft reset has done","dorothy.djantio@ihstowers.com","427","13-08=
-2024 20:40:20","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002840309","Bas=
tos Amb Coree","","13-08-2024 20:36:17","13-08-2024 20:35:11","13-08-2024 2=
2:01:07","Grid outage,no space to deploy mobile gen//Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,n=
o space to deploy mobile gen//Grid return","ludivine.ngamaleu@ihstowers.com=
","66","13-08-2024 20:36:17","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002840240","Mok=
olo Yaounde","","13-08-2024 20:25:18","13-08-2024 20:20:11","13-08-2024 22:=
03:43","Grid outage,no space to deploy mobile gen,//Grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,no=
 space to deploy mobile gen,//Grid return","ludivine.ngamaleu@ihstowers.com=
","307","13-08-2024 20:25:18","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0002839926","Fla=
menco","","13-08-2024 19:16:39","13-08-2024 19:09:36","13-08-2024 20:01:55"=
,"Grid outage,gen failed to start due to card GE dysfunctionned//We reset c=
ard GE and gen manually started ","Mboua Thierry","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage,gen failed to start due =
to card GE dysfunctionned//We reset card GE and gen manually started ","lud=
ivine.ngamaleu@ihstowers.com","424","13-08-2024 19:16:39","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0002839788","Nko=
londom","","13-08-2024 18:50:29","13-08-2024 18:48:24","13-08-2024 18:56:16=
","Grid outage ,gen failed to start due to alarm""low oil pressure""//We re=
set card GE and gen manually started ","Fabrice Pouakam","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage ,gen failed to st=
art due to alarm""low oil pressure""//We reset card GE and gen manually sta=
rted ","ludivine.ngamaleu@ihstowers.com","126","13-08-2024 18:50:29","Sagem=
com CMR"
"Closed Complete","Site Down","T0065","IHS_YND_735","NOCINC0002839761","Mai=
son komkana New","","13-08-2024 18:44:01","13-08-2024 18:36:57","13-08-2024=
 20:06:38","Grid outage,gen failed to star t due to battery GE faulty//gen =
manually started with external battery ","Mboua Thierry","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Generator Battery","Grid outage,gen failed to=
 star t due to battery GE faulty//gen manually started with external batter=
y ","ludivine.ngamaleu@ihstowers.com","425","13-08-2024 18:44:01","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0002839659","A=
KONGO","","13-08-2024 18:23:18","13-08-2024 18:20:09","13-08-2024 19:48:01"=
," No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rodrigue (6=
55102999)from Huawei is informed. Repetitive issue //site up at 06:23 PM","=
Fanda Brice","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm"," No power issue on site Ubaie=3D52,5V site on Gen.=
 The Tx FME Rodrigue (655102999)from Huawei is informed. Repetitive issue /=
/site up at 06:23 PM","dorothy.djantio@ihstowers.com","190","13-08-2024 18:=
23:18","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0002839635","Nko=
mkana","","13-08-2024 18:20:04","13-08-2024 18:09:06","13-08-2024 20:08:43"=
,"Grid outage.no space to deploy mobile gen //Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no space=
 to deploy mobile gen //Grid return","ludivine.ngamaleu@ihstowers.com","781=
5","13-08-2024 18:20:04","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002839388","Man=
guiers Dispensaire","","13-08-2024 17:23:51","13-08-2024 17:20:47","13-08-2=
024 18:34:37","Grid outage due to grid circuit breaker down  and generator =
start  and  not feeding the site//we rearmed the circuit breaker ","Fabrice=
 Pouakam","Grid Supply","Passive","Grid","National Grid - Circuit Breaker",=
"Grid outage due to grid circuit breaker down  and generator start  and  no=
t feeding the site//we rearmed the circuit breaker ","ludivine.ngamaleu@ihs=
towers.com","185","13-08-2024 17:23:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0002839195","K=
ondengui","","13-08-2024 17:11:00","13-08-2024 17:08:54","13-08-2024 18:02:=
58","Active: no power issue, site is on grid with Ubaie=3D54,4V, Eloundou (=
693212405) from Huawei is informed//site up at 05:11 PM","Albran Byorel","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active: no power issue, site is on grid with Ubaie=3D54,4V, Eloun=
dou (693212405) from Huawei is informed//site up at 05:11 PM","dorothy.djan=
tio@ihstowers.com","126","13-08-2024 17:11:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002839177","B=
ATA-Mokolo","","13-08-2024 17:08:40","13-08-2024 17:03:36","13-08-2024 17:4=
1:37","Active: no power issue, site is on grid with Ubaie=3D54,1V, Brice Ts=
ague (650214096) from Huawei is informed//site up at 05:05 pm","","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active: no power issue, site is on grid with Ubaie=3D54,1V, Brice Tsague=
 (650214096) from Huawei is informed//site up at 05:05 pm","dorothy.djantio=
@ihstowers.com","304","13-08-2024 17:08:40","Sagemcom CMR"
"Closed Complete","Warning","T1834","IHS_YND_132","NOCINC0002839083","Mangu=
iers Dispensaire","","13-08-2024 16:45:21","","","Grid outage due to grid c=
ircuit breaker down  and generator start  and  not feeding the site//we rea=
rmed the circuit breaker ","Fabrice Pouakam","Warning","Warning","POWER","W=
arning - Low Voltage","Grid outage due to grid circuit breaker down  and ge=
nerator start  and  not feeding the site//we rearmed the circuit breaker ",=
"olivier.kwedi@ihstowers.com","566","13-08-2024 16:45:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0002839031","S=
apeur","","13-08-2024 16:34:59","13-08-2024 15:19:51","13-08-2024 15:29:00"=
,"No power issue site on grid with U=3D53,5v Notice that we have disjunctio=
n at OCM equipements Brice Tsague(650214096) from Huawei is informed ","Mbo=
ua Thierry","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","No power issue site on grid with U=3D53,5v Notice t=
hat we have disjunction at OCM equipements Brice Tsague(650214096) from Hua=
wei is informed ","dorothy.djantio@ihstowers.com","4508","13-08-2024 16:34:=
59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0002838604","M=
ANGUIERS CHAPELLE","","13-08-2024 15:32:19","13-08-2024 14:06:09","13-08-20=
24 14:22:44","site went down due to insufficiency of rectifiers on site // =
He added (2/6)rectifiers(swapping by ZTE )","Fabrice Pouakam","Equipment Re=
pair","Passive","Rectifier","Rectifier Module","site went down due to insuf=
ficiency of rectifiers on site // He added (2/6)rectifiers(swapping by ZTE =
)","etienne.itondo@ihstowers.com","5171","13-08-2024 15:32:19","Sagemcom CM=
R"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0002838424","San=
ta Barbara Gottam","","13-08-2024 15:04:05","13-08-2024 15:02:57","13-08-20=
24 16:39:29","Grid fluctuation, site went down because gen failed to start =
due to grid bad voltage // He make the bridge on good phases ","Delor Telez=
ing","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid fluctuation, site went down because gen failed to start due to gri=
d bad voltage // He make the bridge on good phases ","ludivine.ngamaleu@ihs=
towers.com","68","13-08-2024 15:04:05","Sagemcom CMR"
"Closed Complete","Site Down","T1085","IHS_YND_130","NOCINC0002838387","Bas=
tos usine","","13-08-2024 14:54:46","13-08-2024 14:53:42","13-08-2024 16:35=
:53","No power issue site on grid with U=3D53,4v Eloundou Bertrand from Hua=
wei is informed  //site up at 03:13 PM","Mboua Thierry","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue site on grid with U=3D53,4v Eloundou Bertrand from Huawei is inform=
ed  //site up at 03:13 PM","ludivine.ngamaleu@ihstowers.com","64","13-08-20=
24 14:54:46","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0002838199","Nko=
londom","","13-08-2024 14:25:09","13-08-2024 14:01:47","13-08-2024 16:27:40=
","Grid outage, gen failed to start due to alarm ""low oil presure""//Grid =
power return ","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","A=
CDG - Low Oil Pressure","Grid outage, gen failed to start due to alarm ""lo=
w oil presure""//Grid power return ","ludivine.ngamaleu@ihstowers.com","530=
4","13-08-2024 14:25:09","Sagemcom CMR"
"Closed Complete","Site Down","T0211","IHS_YND_393","NOCINC0002838116","Eze=
zang","","13-08-2024 13:58:56","13-08-2024 13:44:41","13-08-2024 13:59:40",=
"Grid fluctuation site went down because Gen failled to started due to Grid=
 bad voltage // He bypass the Grid and site on Gen ","Parker Tchoup","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fl=
uctuation site went down because Gen failled to started due to Grid bad vol=
tage // He bypass the Grid and site on Gen ","denis.mballa@ihstowers.com","=
923","13-08-2024 13:58:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_025","IHS_YND_238","NOCINC0002837448","M=
endong","","13-08-2024 12:26:41","13-08-2024 12:10:38","13-08-2024 12:20:24=
","Active: No power Issue  site on Gen ,ubaie:54,4V;  Fabrice /690945875/ f=
rom ZTE is working on site ""SWAPP""","Hyemafo Gildas","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No power Issue  site on Gen ,ubaie:54,4V;  Fabrice /690945875/ from ZTE is =
working on site ""SWAPP""","alexandre.kamal@ihstowers.com","964","13-08-202=
4 12:26:41","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002837083","Nko=
g-Edzen","","13-08-2024 11:35:29","13-08-2024 11:28:11","13-08-2024 11:55:3=
1","ACTIVE// Tx issue: Ubaie=3D52,2 V site on Battery( Hybrid Gen site Star=
t Threshold=3D51,1V)The Tx Fme Gregoire( 652070658)from Huawei is informed"=
,"Parker Tchoup","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","ACTIVE// Tx issue: Ubaie=3D52,2 V site on Batt=
ery( Hybrid Gen site Start Threshold=3D51,1V)The Tx Fme Gregoire( 652070658=
)from Huawei is informed","denis.mballa@ihstowers.com","439","13-08-2024 11=
:35:29","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002836760","Nko=
abang Ebolmedjock","","13-08-2024 10:51:52","13-08-2024 10:44:35","13-08-20=
24 11:46:06","Grid outage site went down because Gen failed to start with a=
larm Gen overload// He rest the Gen card and Site on Gen","Mba Lazare Herve=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa=
ge site went down because Gen failed to start with alarm Gen overload// He =
rest the Gen card and Site on Gen","denis.mballa@ihstowers.com","437","13-0=
8-2024 10:51:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002836645","M=
arche Odza","","13-08-2024 10:41:01","13-08-2024 10:30:59","13-08-2024 10:5=
8:41","Grid outage site went down because Gen failed to start due to Gen ba=
ttery fautly// Grid power return","Albran Byorel","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Generator Battery","Grid outage site went down becau=
se Gen failed to start due to Gen battery fautly// Grid power return","alex=
andre.kamal@ihstowers.com","603","13-08-2024 10:41:01","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002836253","MAN=
GUIERS CHAPELLE","","13-08-2024 09:35:38","13-08-2024 09:26:25","13-08-2024=
 10:31:34","site went down because gen failed to start due to grid bad volt=
age  // he did a bridge on good phase, Site on Grid (Swapped by ZTE)","Fabr=
ice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","site went down because gen failed to start due to grid bad volt=
age  // he did a bridge on good phase, Site on Grid (Swapped by ZTE)","deni=
s.mballa@ihstowers.com","553","13-08-2024 09:35:38","Sagemcom CMR"
"Closed Complete","Warning","T0870","IHS_YND_444","NOCINC0002836085","Dong"=
,"","13-08-2024 09:08:24","","","alarming because Solar-Gen gen starts at t=
he threshold // 49.7 V and Gen started. alarm cleared","Parker Tchoup","War=
ning","Warning","POWER","Warning - Site on Battery","alarming because Solar=
-Gen gen starts at the threshold // 49.7 V and Gen started. alarm cleared",=
"marie.kwin@ihstowers.com","4","13-08-2024 09:08:24","Sagemcom CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0002835205","NYA=
NON/DEMBO","","13-08-2024 05:13:22","13-08-2024 05:10:58","13-08-2024 05:12=
:46","Site went down because 02/05 rectifier faulty //he replacedc the rect=
ifier faulty","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Rect=
ifier","Rectifier Module","Site went down because 02/05 rectifier faulty //=
he replacedc the rectifier faulty","emmanuel.ghani@ihstowers.com","144","13=
-08-2024 05:13:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0002834813","M=
fou EPC","","13-08-2024 02:41:05","13-08-2024 02:37:00","13-08-2024 03:32:5=
6","Grid outage, site went down because Gen started and stopped due to ""hi=
gh temp"" alarm //He added water and gen manually started(site swapped by Z=
TE)","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Hig=
h Engine Temp - Coolant Level Issue","Grid outage, site went down because G=
en started and stopped due to ""high temp"" alarm //He added water and gen =
manually started(site swapped by ZTE)","joelle.ekessi@ihstowers.com","245",=
"13-08-2024 02:41:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0002834512","E=
bogo","","13-08-2024 00:31:00","12-08-2024 20:25:52","13-08-2024 01:13:56",=
"Active, no power issue,site on grid with U=3D54V Symphorien /650257151/ Fr=
om huawei is informed (site swapped by ZTE)","Siligap Boris","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive, no power issue,site on grid with U=3D54V Symphorien /650257151/ From =
huawei is informed (site swapped by ZTE)","joelle.ekessi@ihstowers.com","14=
708","13-08-2024 00:31:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0002834371","M=
bedoumou - Ekali","","12-08-2024 23:40:14","12-08-2024 23:34:03","13-08-202=
4 00:22:13","Tx issue:Site on Gen,Ubaie:53,6V; Rodrigue/655-100-29-99 is in=
formed","Albran Byorel","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Tx issue:Site on Gen,Ubaie:53,6V; Rodri=
gue/655-100-29-99 is informed","joelle.ekessi@ihstowers.com","371","12-08-2=
024 23:40:14","Sagemcom CMR"
"Closed Complete","Site Down","T2581","IHS_YND_750","NOCINC0002834209","Nko=
abang entree carriere","","12-08-2024 22:53:26","12-08-2024 22:31:21","13-0=
8-2024 00:03:22","grid outage,gen failed to start due to ATS disfunction//G=
rid return","Mba Lazare Herve","Equipment Repair","Passive","Control Panel"=
,"ATS-AMF Issue","grid outage,gen failed to start due to ATS disfunction//G=
rid return","emmanuel.ghani@ihstowers.com","1326","12-08-2024 22:53:26","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0002834200","San=
ta Barbara Gottam","","12-08-2024 22:52:31","12-08-2024 22:44:26","12-08-20=
24 23:22:13","grid outage,gen failed to start due to alarm undervoltage//he=
 reset the Gen card and started it","Delor Telezing","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - Under Voltage","grid outage,gen failed to start d=
ue to alarm undervoltage//he reset the Gen card and started it","emmanuel.g=
hani@ihstowers.com","485","12-08-2024 22:52:31","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002834183","Pha=
rmacie SION","","12-08-2024 22:50:06","12-08-2024 22:48:46","12-08-2024 22:=
58:39","Grid outage, site went down before gen start due to poor battery ba=
ckup // Gen start automatically","Paul BIBOUM","Equipment Repair","Passive"=
,"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automatically","e=
mmanuel.ghani@ihstowers.com","80","12-08-2024 22:50:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0002834076","E=
foulan","","12-08-2024 22:14:21","12-08-2024 21:33:47","12-08-2024 22:15:20=
","Active: No power issue, site is on grid with Ubaie=3D53V, Cable burned i=
n BTS OCM, Christian(6 55 80 23 45) from ZTE  is informed, power resolved  =
 12/08/2024 at  08:43 PM","MINKA NICOLAS","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issu=
e, site is on grid with Ubaie=3D53V, Cable burned in BTS OCM, Christian(6 5=
5 80 23 45) from ZTE  is informed, power resolved   12/08/2024 at  08:43 PM=
","alwine.fambou@ihstowers.com","2601","12-08-2024 22:14:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0002834058","F=
ebe Village","","12-08-2024 22:07:57","12-08-2024 21:19:48","12-08-2024 23:=
40:05","site went down due to CB 80A disjuntecd causing by load increase//h=
e change with another CB 125A(site swapped by ZTE)","Mboua Thierry","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issu=
e","site went down due to CB 80A disjuntecd causing by load increase//he ch=
ange with another CB 125A(site swapped by ZTE)","adonis.defokoua@ihstowers.=
com","2889","12-08-2024 22:07:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0002834022","O=
mnisport-Rail","","12-08-2024 22:06:05","12-08-2024 20:56:58","13-08-2024 0=
0:46:10","No power issue on site U=3D56,2v site on grid Armand of Huawei is=
 informedNotice that disjonction in BTS ocm  (Swapped by ZTE)","Delor Telez=
ing","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue on site U=3D56,2v site on grid Armand of Hu=
awei is informedNotice that disjonction in BTS ocm  (Swapped by ZTE)","adon=
is.defokoua@ihstowers.com","4147","12-08-2024 22:06:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0002834013","C=
lge-Advantiste","","12-08-2024 22:05:38","12-08-2024 21:13:31","12-08-2024 =
22:33:08","site went down due to CB 125A disjuncted in PWc//he ream=F9ed th=
e CB (Swapped by ZTE)","MINKA NICOLAS","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Circuit Breaker Issue","site went down due to CB =
125A disjuncted in PWc//he ream=F9ed the CB (Swapped by ZTE)","adonis.defok=
oua@ihstowers.com","3127","12-08-2024 22:05:38","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0002833636","Nko=
mo stade","","12-08-2024 20:43:19","12-08-2024 20:38:08","12-08-2024 20:44:=
08","Grid fluctuation site went down because 1/3 rectifier disfunction // G=
rid stabilized on site","Mba Lazare Herve","Equipment Repair","Passive","Re=
ctifier","Rectifier Module","Grid fluctuation site went down because 1/3 re=
ctifier disfunction // Grid stabilized on site","ange.kongo@ihstowers.com",=
"312","12-08-2024 20:43:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0002833566","A=
kak-Nkozoa-MTN-IHS","","12-08-2024 20:20:10","12-08-2024 18:21:04","12-08-2=
024 20:55:43","Active//No power issue on site. Site on Grid with Ubaie=3D52=
V The Tx FME Synphorien//650257151 from  Huawei is informed. (Swapped by ZT=
E)","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","Active//No power issue on site. Site on G=
rid with Ubaie=3D52V The Tx FME Synphorien//650257151 from  Huawei is infor=
med. (Swapped by ZTE)","adonis.defokoua@ihstowers.com","7147","12-08-2024 2=
0:20:10","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0002833472","NYO=
M 2 IHS","","12-08-2024 20:04:50","12-08-2024 19:56:19","12-08-2024 20:44:2=
0","Grid outage, Site was on GEN and stopped due to alarm overload//he rese=
t the card and started the gen","Fabrice Pouakam","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Control Panel","Grid outage, Site was on GEN and sto=
pped due to alarm overload//he reset the card and started the gen","ange.ko=
ngo@ihstowers.com","1928","12-08-2024 20:04:50","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0002833043","UPA=
C LP","","12-08-2024 18:39:56","12-08-2024 18:35:46","12-08-2024 20:55:28",=
"Active: No power issue, site is on grid with Ubaie=3D53V, Armand Ngetsa(69=
1144412)  from Huawei is informed","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issue, s=
ite is on grid with Ubaie=3D53V, Armand Ngetsa(691144412)  from Huawei is i=
nformed","ange.kongo@ihstowers.com","251","12-08-2024 18:39:56","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0002832970","E=
foulan","","12-08-2024 18:24:22","12-08-2024 16:12:14","12-08-2024 21:32:15=
","site went down due to 3/7 rectifier disfunctionning//he reset the rectif=
iers :site on grid  (swapped by ZTE)","MINKA NICOLAS","Equipment Repair","P=
assive","Rectifier","Rectifier Module","site went down due to 3/7 rectifier=
 disfunctionning//he reset the rectifiers :site on grid  (swapped by ZTE)",=
"adonis.defokoua@ihstowers.com","7929","12-08-2024 18:24:22","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0002832923","Nko=
londom","","12-08-2024 18:14:13","12-08-2024 18:01:52","12-08-2024 19:16:11=
","grid outage, site went down because gen start and stoppen with alarm""lo=
w oil pressure""// grid return (Swapped by ZTE)","Fabrice Pouakam","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage, site w=
ent down because gen start and stoppen with alarm "" low oil pressure""// g=
rid return (Swapped by ZTE)","ange.kongo@ihstowers.com","3668","12-08-2024 =
18:14:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0002832910","E=
toudi","","12-08-2024 18:09:12","12-08-2024 15:55:04","12-08-2024 20:35:37"=
,"Active//No power issue on site. Site on Grid with Ubaie=3D53V The Tx FME =
Synphorien//650257151 from  Huawei is informed. (Swapped by ZTE)","Fabrice =
Pouakam","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active//No power issue on site. Site on Grid with Ubai=
e=3D53V The Tx FME Armand Nguetsa//691144412 from  Huawei is informed. (Swa=
pped by ZTE)","adonis.defokoua@ihstowers.com","8049","12-08-2024 18:09:12",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_254","IHS_YND_216","NOCINC0002832832","E=
leveur","","12-08-2024 17:59:35","12-08-2024 17:50:28","12-08-2024 20:30:39=
","Active: No power issue on site U=3D52,5v site on Grid Team TCHOUFFEU/659=
149839/ from ZTE working on site ""swapp""","Siligap Boris","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue on site U=3D52,5v site on Grid Team TCHOUFFEU/659149839=
/ from ZTE working on site ""swapp""","adonis.defokoua@ihstowers.com","548"=
,"12-08-2024 17:59:35","Sagemcom CMR"
"Closed Complete","Warning","CTR_213","IHS_YND_247","NOCINC0002832142","Oko=
lo","","12-08-2024 15:36:27","","","site alarm because gen failed to start =
due to poor battery backup // grid return","Fabrice Pouakam","Warning","War=
ning","POWER","Warning - Battery Low Voltage","site alarm because gen faile=
d to start due to poor battery backup // grid return","marie.kwin@ihstowers=
.com","7","12-08-2024 15:36:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0002831958","A=
fanoya","","12-08-2024 15:15:30","12-08-2024 15:01:24","12-08-2024 17:23:58=
","Active: No power issue, site is on grid with Ubaie=3D54,4 V, lionel tcha=
tchoua(694693436) from Huawei is informed","Hyemafo Gildas","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue, site is on grid with Ubaie=3D54,4 V, lionel tchatchoua=
(694693436) from Huawei is informed","adonis.defokoua@ihstowers.com","846",=
"12-08-2024 15:15:30","Sagemcom CMR"
"Closed Complete","Warning","T0322","IHS_YND_312","NOCINC0002831950","Nkoln=
da","","12-08-2024 15:14:26","","","site alarming because Gen failed to sta=
rt // Grid power return (investigation ongoing) and alarm cleared","Albran =
Byorel","Warning","Warning","POWER","Warning - Site on Battery","site alarm=
ing because Gen failed to start // Grid power return (investigation ongoing=
) and alarm cleared","marie.kwin@ihstowers.com","735","12-08-2024 15:14:26"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002831782","Eko=
unou","","12-08-2024 15:02:58","12-08-2024 15:00:53","12-08-2024 15:11:33",=
"grid outage, site went down because gen failed to start due to poor batter=
y backup and disfunctionning of PWC// gen started automatically","Albran By=
orel","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery=
 Low","grid outage, site went down because gen failed to start due to poor =
battery backup and disfunctionning of PWC// gen started automatically","ang=
e.kongo@ihstowers.com","126","12-08-2024 15:02:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002831769","M=
vog-Manga","","12-08-2024 15:00:33","12-08-2024 11:59:25","12-08-2024 12:09=
:48","Active: No power issue  on site ,site on Grid  with U=3D53,2V Team li=
onel adjep  ( 655184876 )  from HUAWEI  is informed (Swapped by ZTE)","Albr=
an Byorel","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","Active: No power issue  on site ,site on Grid  with =
U=3D53,2V Team lionel adjep  ( 655184876 )  from HUAWEI  is informed (Swapp=
ed by ZTE)","adonis.defokoua@ihstowers.com","10869","12-08-2024 15:00:33","=
Sagemcom CMR"
"Closed Complete","Warning","T1613","IHS_YND_301","NOCINC0002831564","Tsing=
a village","","12-08-2024 14:23:17","","","site on battery due to grid outa=
ge//Gen started automatically","Delor Telezing","Warning","Warning","POWER"=
,"Warning - Site on Battery","site on battery due to grid outage//Gen start=
ed automatically","stephane.nkamwa@ihstowers.com","735","12-08-2024 14:23:1=
7","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_319","NOCINC0002830745","SOA 2","",=
"12-08-2024 11:45:21","","","site alarming High temp 43=B0c// 24=B0c and al=
rm cleared","Siligap Boris","Warning","Warning","ENVIRONMENT","Warning - Hi=
gh Temperature","site alarming High temp 43=B0c// 24=B0c and alrm cleared",=
"stephane.nkamwa@ihstowers.com","692","12-08-2024 11:45:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_132","IHS_YND_107","NOCINC0002830395","N=
R-Omnisport","","12-08-2024 10:53:13","12-08-2024 10:49:15","12-08-2024 12:=
30:01"," No power issue site on grid with U=3D57v  Charly TEMGOUA /69844538=
4/ From ZTE is working on site","Delor Telezing","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No power issu=
e site on grid with U=3D57v  Charly TEMGOUA /698445384/ From ZTE is working=
 on site","dorothy.djantio@ihstowers.com","238","12-08-2024 10:53:13","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0002830221","N=
taba","","12-08-2024 10:27:55","12-08-2024 10:23:50","12-08-2024 13:15:11",=
"No Power issue site on grid with U=3D57v Lary Kengne (694675611) from ZTE =
is working on site ","Delor Telezing","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No Power issue site on gr=
id with U=3D57v Lary Kengne (694675611) from ZTE is working on site ","doro=
thy.djantio@ihstowers.com","245","12-08-2024 10:27:55","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0002830100","Lob=
o 2","","12-08-2024 10:12:07","12-08-2024 10:07:03","12-08-2024 11:19:02","=
site went down because gen failed to start due to alarm ""overvoltage""//he=
 reset the card GE and gen manually started ","TIENTCHEU NZETCHIEU GAEL","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","site went dow=
n because gen failed to start due to alarm ""overvoltage""//he reset the ca=
rd GE and gen manually started ","ludivine.ngamaleu@ihstowers.com","305","1=
2-08-2024 10:12:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002829868","Ngouetou=
","","12-08-2024 09:16:40","12-08-2024 09:08:41","12-08-2024 09:38:25","Cas=
caded Incident from TTO2636447","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","LOW SOLAR , huawei modul faulty // man=
ual start DG","system","479","12-08-2024 09:16:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002829865","Ngoum","=
","12-08-2024 09:16:40","12-08-2024 09:08:41","12-08-2024 09:38:25","Cascad=
ed Incident from TTO2636447","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","LOW SOLAR , huawei modul faulty // manual=
 start DG","system","479","12-08-2024 09:16:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002829867","Yoko OCM=
","","12-08-2024 09:16:40","12-08-2024 09:08:41","12-08-2024 09:38:25","Cas=
caded Incident from TTO2636447","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","LOW SOLAR , huawei modul faulty // man=
ual start DG","system","479","12-08-2024 09:16:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002829866","Matsari"=
,"","12-08-2024 09:16:40","12-08-2024 09:08:41","12-08-2024 09:38:25","Casc=
aded Incident from TTO2636447","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","LOW SOLAR , huawei modul faulty // manu=
al start DG","system","479","12-08-2024 09:16:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002829870","MBIMBIM"=
,"","12-08-2024 09:16:40","12-08-2024 09:08:41","12-08-2024 09:38:25","Casc=
aded Incident from TTO2636447","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","LOW SOLAR , huawei modul faulty // manu=
al start DG","system","479","12-08-2024 09:16:40","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0002829673","Nko=
lmvack","","12-08-2024 08:37:56","12-08-2024 08:31:52","12-08-2024 09:47:47=
"," site went down because Gen started and stopped due to ""high temp"" ala=
rm //He added water and gen manually started","Parker Tchoup","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Radiator"," site went down because Gen s=
tarted and stopped due to ""high temp"" alarm //He added water and gen manu=
ally started","ludivine.ngamaleu@ihstowers.com","364","12-08-2024 08:37:56"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002829265","N=
kolo II New","","12-08-2024 07:08:27","11-08-2024 21:42:07","11-08-2024 21:=
50:37","No power issue site on gen with U=3D55.2v Lionnel Tchatchou from Hu=
awei is informed","Mba Lazare Herve","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gen=
 with U=3D55.2v Lionnel Tchatchou from Huawei is informed","etienne.itondo@=
ihstowers.com","33980","12-08-2024 07:08:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002829165","E=
mana","","12-08-2024 06:33:13","12-08-2024 06:30:07","12-08-2024 12:35:24",=
"No power issue site on grid with U=3D53.7v Symphorien(675295205) from Huaw=
ei is informed ","","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53.7v =
Symphorien(675295205) from Huawei is informed ","dorothy.djantio@ihstowers.=
com","186","12-08-2024 06:33:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0002828965","Boumnyeb=
el","","12-08-2024 05:19:20","12-08-2024 05:06:54","12-08-2024 05:16:30","C=
ascaded Incident from TTO2635478","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active: no power issue on site ,site =
on GRid with U=3D56V; Yannick mbah // 698270715 from HUAWEI is informed(sit=
e Swapped by ZTE)","system","746","12-08-2024 05:19:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0002828963","Mamb",""=
,"12-08-2024 05:19:20","12-08-2024 05:06:54","12-08-2024 05:16:30","Cascade=
d Incident from TTO2635478","Kemeni Franklin","Cascade Outage","Active","Ca=
scade Active","Cascade Active","Active: no power issue on site ,site on GRi=
d with U=3D56V; Yannick mbah // 698270715 from HUAWEI is informed(site Swap=
ped by ZTE)","system","746","12-08-2024 05:19:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_375","NOCINC0002828964","Ngoung",=
"","12-08-2024 05:19:20","12-08-2024 05:06:54","12-08-2024 05:16:30","Casca=
ded Incident from TTO2635478","Kemeni Franklin","Cascade Outage","Active","=
Cascade Active","Cascade Active","Active: no power issue on site ,site on G=
Rid with U=3D56V; Yannick mbah // 698270715 from HUAWEI is informed(site Sw=
apped by ZTE)","system","746","12-08-2024 05:19:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_416","NOCINC0002828962","Ngwopi B=
oga","","12-08-2024 05:19:20","12-08-2024 05:06:54","12-08-2024 05:16:30","=
Cascaded Incident from TTO2635478","Kemeni Franklin","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active: no power issue on site ,site=
 on GRid with U=3D56V; Yannick mbah // 698270715 from HUAWEI is informed(si=
te Swapped by ZTE)","system","746","12-08-2024 05:19:20","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002828681","Lad=
a I Yde","","12-08-2024 03:09:42","12-08-2024 00:27:16","12-08-2024 02:57:1=
7","grid outage, site went down due to gen overload(09 KVA, 110A) // gen ma=
nually started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","grid outage, site went down due to gen overload(09 KVA, =
110A) // gen manually started","kouoh.jean@ihstowers.com","9746","12-08-202=
4 03:09:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002828065","M=
imboman-Village","","11-08-2024 23:15:58","11-08-2024 21:42:41","11-08-2024=
 21:52:14","Active: no power issue on site ,site on GRid with U=3D53,2V Tea=
m Eloundou // 693212405 from HUAWEI is informed Notice that we have dysjunc=
tion at OCM equipements(site Swapped by ZTE)","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active: no power issue on site ,site on GRid with U=3D53,2V Team Eloundou=
 // 693212405 from HUAWEI is informed Notice that we have dysjunction at OC=
M equipements(site Swapped by ZTE)","landry.etame@ihstowers.com","5597","11=
-08-2024 23:15:58","Sagemcom CMR"
"Closed Complete","Site Down","T0395","IHS_YND_065","NOCINC0002827954","Ess=
os DCS","","11-08-2024 23:01:00","11-08-2024 21:44:27","12-08-2024 00:56:20=
","access isuue due to land load  grid outage, site went down because gen f=
aild to start//Grid return (investigation ongoing)","Delor Telezing","Acces=
s Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land L=
ord","access isuue due to land load  fme is on the way, grid outage, site w=
ent down because gen faild to start//Grid return (investigation ongoing)","=
kouoh.jean@ihstowers.com","4594","11-08-2024 23:01:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0002827809","O=
ssombe","","11-08-2024 22:19:41","11-08-2024 22:04:36","12-08-2024 00:18:38=
","site went down because gen ran until fuel shortage // refueling done","P=
arker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","Fuel shorta=
ge // Tank inclined. , Gen started","landry.etame@ihstowers.com","906","11-=
08-2024 22:19:41","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002827072","Nko=
g-Edzen","","11-08-2024 21:09:06","11-08-2024 21:04:54","11-08-2024 21:10:1=
2","No power issue on site ;site on battery with Ubaie=3D53 V The Tx FME Gr=
=E9goire //652070658 from Huawei is informe","Parker Tchoup","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site ;site on battery with Ubaie=3D53 V The Tx FME Gr=E9goi=
re //652070658 from Huawei is informe","emmanuel.ghani@ihstowers.com","252"=
,"11-08-2024 21:09:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0002826323","E=
bogo","","11-08-2024 20:39:03","11-08-2024 19:49:57","11-08-2024 21:26:07",=
"Active, no power issue,site on grid with U=3D54.3V Symphorien /650257151/ =
From huawei is informed (site swapped by ZTE)","Siligap Boris","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active, no power issue,site on grid with U=3D54.3V Symphorien /650257151/ F=
rom huawei is informed (site swapped by ZTE)","joelle.ekessi@ihstowers.com"=
,"2947","11-08-2024 20:39:03","Sagemcom CMR"
"Closed Complete","Site Down","T0896","IHS_YND_707","NOCINC0002825658","NYO=
M 2 IHS","","11-08-2024 18:14:36","11-08-2024 18:07:30","11-08-2024 18:56:5=
5","Grid outage, site went down because gen ran until fuel shortage // refu=
eling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran until fuel shortage // ref=
ueling done","emmanuel.ghani@ihstowers.com","427","11-08-2024 18:14:36","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0002825024","Mel=
en Ba'aba","","11-08-2024 16:49:38","11-08-2024 16:47:21","11-08-2024 17:00=
:06","Grid outage, site went down because gen ran until fuel shortage // re=
fueling done","Siligap Boris","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage, site went down because gen ran until fuel shortage // ref=
ueling done","emmanuel.ghani@ihstowers.com","137","11-08-2024 16:49:38","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002824794","M=
imboman-Village","","11-08-2024 15:51:56","10-08-2024 16:54:48","10-08-2024=
 16:55:03","No power issue on site ,site on GRid with U=3D53,2V Team Elound=
ou // 693212405 from HUAWEI is informed Notice that we have dysjunction at =
OCM equipements(site Swapped by ZTE)","Mba Lazare Herve","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site ,site on GRid with U=3D53,2V Team Eloundou // 693212405 fr=
om HUAWEI is informed Notice that we have dysjunction at OCM equipements(si=
te Swapped by ZTE)","joelle.ekessi@ihstowers.com","82628","11-08-2024 15:51=
:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002824760","MBALNGON=
G LYCEE","","11-08-2024 15:44:50","11-08-2024 15:42:18","11-08-2024 17:39:5=
1","Cascaded Incident from TTO2630714","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation site went down b=
ecause Gen failled to started due to Grid bad voltage // He bypass the Grid=
 and site on Gen manually started","system","152","11-08-2024 15:44:50","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002824759","ELOUMDEM=
 CARRIERE","","11-08-2024 15:44:50","11-08-2024 15:42:18","11-08-2024 17:39=
:51","Cascaded Incident from TTO2630714","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation site went down=
 because Gen failled to started due to Grid bad voltage // He bypass the Gr=
id and site on Gen manually started","system","152","11-08-2024 15:44:50","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002824761","Afanoya"=
,"","11-08-2024 15:44:50","11-08-2024 15:42:18","11-08-2024 17:39:51","Casc=
aded Incident from TTO2630714","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation site went down becaus=
e Gen failled to started due to Grid bad voltage // He bypass the Grid and =
site on Gen manually started","system","152","11-08-2024 15:44:50","Sagemco=
m CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002824757","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","11-08-2024 15:43:44","11-08-20=
24 15:42:18","11-08-2024 17:39:51","Grid fluctuation site went down because=
 Gen failled to started due to Grid bad voltage // He bypass the Grid and  =
Gen manually started","Hyemafo Gildas","Grid Supply","Passive","Grid","Nati=
onal Grid - Phase Controller Faulty","Grid fluctuation site went down becau=
se Gen failled to started due to Grid bad voltage // He bypass the Grid and=
 site on Gen manually started","emmanuel.ghani@ihstowers.com","87","11-08-2=
024 15:43:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0002824738","E=
bogo","","11-08-2024 15:38:35","10-08-2024 21:41:15","10-08-2024 21:45:40",=
"Active, no power issue,site on grid with U=3D54V Symphorien /650257151/ Fr=
om huawei is informed (site swapped by ZTE)","Siligap Boris","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive, no power issue,site on grid with U=3D54V Symphorien /650257151/ From =
huawei is informed (site swapped by ZTE)","joelle.ekessi@ihstowers.com","64=
640","11-08-2024 15:38:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002824152","O=
lembe-Terminus","","11-08-2024 14:57:48","11-08-2024 13:55:17","11-08-2024 =
19:07:54","Active: No power issue on site, Ubai =3D 55,7 V on Grid Tx FME s=
ymphorien /650257151 /   from HUAWEI is informed  ","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active: No power issue on site, Ubai =3D 55,7 V on Grid Tx FME symph=
orien /650257151 /   from HUAWEI is informed  ","joelle.ekessi@ihstowers.co=
m","3752","11-08-2024 14:57:48","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002824023","Mok=
olo Yaounde","","11-08-2024 14:22:52","11-08-2024 14:14:49","11-08-2024 14:=
26:47","Grid outage, no space to deploy a MDG // Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage, no s=
pace to deploy a MDG // Grid return","emmanuel.ghani@ihstowers.com","484","=
11-08-2024 14:22:52","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0002823807","N=
yanon","","11-08-2024 13:27:55","11-08-2024 13:20:46","11-08-2024 14:33:29"=
,"Site down due to gen card dysfunctionning //reset gen card(investigation =
ongoing )","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Control Panel","Site down due ti gen card dysfunctionning //rese=
t gen card(investigation ongoing )","adonis.defokoua@ihstowers.com","430","=
11-08-2024 13:27:55","Sagemcom CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0002823784","Nko=
mo","","11-08-2024 13:20:55","11-08-2024 13:19:49","11-08-2024 16:55:56","A=
ctive: No power issue on site, Ubai =3D 52V on Grid Team IENG FEIZE Loic /6=
83622331/ working on site (swapped by ZTE)","Mba Lazare Herve","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active: No power issue on site, Ubai =3D 52V on Grid Team IENG FEIZE Loic /=
683622331/ working on site (swapped by ZTE)","ange.kongo@ihstowers.com","66=
","11-08-2024 13:20:55","Sagemcom CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0002823684","Av-=
Germaine","","11-08-2024 13:05:10","11-08-2024 12:59:04","11-08-2024 15:31:=
05","Grid outage // Grid return","","Grid Supply","Passive","Grid","Nationa=
l Grid - Grid Outage Issue","Grid outage // Grid return","ange.kongo@ihstow=
ers.com","7394","11-08-2024 13:05:10","Sagemcom CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0002823301","Mvo=
g-Ada_OCM","","11-08-2024 12:14:34","11-08-2024 12:06:00","11-08-2024 15:32=
:32","Grid outage // Grid return","","Grid Supply","Passive","Grid","Nation=
al Grid - Grid Outage Issue","Grid outage // Grid return","ange.kongo@ihsto=
wers.com","4571","11-08-2024 12:14:34","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002823127","MAN=
GUIERS CHAPELLE","","11-08-2024 11:43:09","11-08-2024 11:33:59","11-08-2024=
 11:45:13","Grid outage, site went down before gen start due to poor batter=
y backup // Grid return","Fabrice Pouakam","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Grid return","ange.kongo@ihstow=
ers.com","550","11-08-2024 11:43:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0002823026","M=
om","","11-08-2024 11:12:09","11-08-2024 11:04:59","11-08-2024 11:14:59","g=
rid outage,gen failed to start due to contactor Ge did not excited//he exci=
ted the contactor and started the gen","Fanda Brice","Equipment Repair","Pa=
ssive","Control Panel","ATS-AMF Issue","grid outage,gen failed to start due=
 to contactor Gen  did not excited//he excited the contactor and started th=
e gen","adonis.defokoua@ihstowers.com","573","11-08-2024 11:12:09","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0002822710","M=
om","","11-08-2024 10:18:09","11-08-2024 10:13:03","11-08-2024 10:33:03","g=
rid outage,gen failed to start due to contactor Ge did not excited//he exci=
ted the contactor and started the gen ","Fanda Brice","Equipment Repair","P=
assive","Control Panel","ATS-AMF Issue","grid outage,gen failed to start du=
e to contactor Ge did not excited//he excited the contactor and started the=
 gen ","adonis.defokoua@ihstowers.com","307","11-08-2024 10:18:09","Sagemco=
m CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0002822526","Mba=
nkolo petit paris","","11-08-2024 09:41:29","11-08-2024 09:36:43","11-08-20=
24 11:22:53","","Mboua Thierry","Cascade Outage","Passive","Cascade Passive=
","Cascade Passive","grid outage,gen failed to start due to alarm overvolta=
ge//he reset the gen card and started it","ange.kongo@ihstowers.com","6897"=
,"11-08-2024 09:41:29","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0002822518","AFE=
ME NORD","IHS_YND_808","11-08-2024 09:39:03","11-08-2024 09:34:50","11-08-2=
024 11:22:53","grid outage,gen failed to start due to alarm overvoltage//he=
 reset the gen card and started it","TIENTCHEU NZETCHIEU GAEL","Equipment R=
epair","Passive","ACDG Gen","ACDG - Over Voltage","grid outage,gen failed t=
o start due to alarm overvoltage//he reset the gen card and started it","an=
ge.kongo@ihstowers.com","4989","11-08-2024 09:39:03","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0002820958","Nko=
londom","","11-08-2024 02:41:22","11-08-2024 02:27:10","11-08-2024 04:23:35=
","site went down due to grid contactor did not excited// He excited grid c=
ontactor (Swapped by ZTE)","Fabrice Pouakam","Equipment Repair","Passive","=
Control Panel","ATS-AMF Issue","site went down due to grid contactor did no=
t excited// He excited grid contactor (Swapped by ZTE)","denis.mballa@ihsto=
wers.com","8039","11-08-2024 02:41:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002820169","E=
mana","","10-08-2024 22:27:52","10-08-2024 18:13:45","10-08-2024 19:09:59",=
"","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid Outage//grid return","landry.etame@ihstowers.com","15248","10-08-2024 2=
2:27:52","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002819909","Nsi=
meyong Shell","","10-08-2024 21:43:01","10-08-2024 21:34:45","10-08-2024 22=
:05:21","Grid outage, site down because Gen failed to start due to poor bac=
kup //Grid power return ","MINKA NICOLAS","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Grid outage, site down because G=
en failed to start due to poor backup //Grid power return ","kouoh.jean@ihs=
towers.com","496","10-08-2024 21:43:01","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0002818290","ODZ=
A CITE MBIA","","10-08-2024 19:17:24","10-08-2024 19:10:19","10-08-2024 19:=
50:13","site went down due to CB 100A disjuncted in DC-Box//he reamed the C=
B","Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabi=
net - Circuit Breaker Issue","site went down due to CB 100A disjuncted in D=
C-Box//he reamed the CB","kouoh.jean@ihstowers.com","425","10-08-2024 19:17=
:24","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002818223","Mok=
olo Yaounde","","10-08-2024 19:02:42","10-08-2024 17:34:27","10-08-2024 17:=
37:27","site went down due to insufficient of rectifier on site//he added 1=
 rectifier:site on 3 rectifiers","","Equipment Repair","Passive","Rectifier=
","Rectifier Module","site went down due to insufficient of rectifier on si=
te//he added 1 rectifier:site on 3 rectifiers","kouoh.jean@ihstowers.com","=
5295","10-08-2024 19:02:42","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002818208","Mok=
olo Yaounde","","10-08-2024 18:57:36","10-08-2024 16:29:15","10-08-2024 16:=
31:15","","","Equipment Repair","Passive","Rectifier","Rectifier Module","s=
ite went down due to insufficient of rectifier on site// site stabilized","=
kouoh.jean@ihstowers.com","8901","10-08-2024 18:57:36","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002818203","Mok=
olo Yaounde","","10-08-2024 18:55:37","10-08-2024 16:04:12","10-08-2024 16:=
08:12","","","Equipment Repair","Passive","Rectifier","Rectifier Module","t=
he site went down due to insufficient of rectifier on-site// site stabilize=
d","kouoh.jean@ihstowers.com","10286","10-08-2024 18:55:37","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002818191","Mok=
olo Yaounde","","10-08-2024 18:52:30","10-08-2024 15:30:19","10-08-2024 15:=
34:19","","","Equipment Repair","Passive","Rectifier","Rectifier Module","t=
he site went down due to insufficient of rectifier on site// site stabilize=
d","kouoh.jean@ihstowers.com","12132","10-08-2024 18:52:30","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002818162","Mok=
olo Yaounde","","10-08-2024 18:51:24","10-08-2024 14:22:26","10-08-2024 14:=
26:26","","","Equipment Repair","Passive","Rectifier","Rectifier Module","s=
ite went down due to insufficient of the rectifier on site// site stabilize=
d","kouoh.jean@ihstowers.com","16138","10-08-2024 18:51:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0002817672","E=
kie-Elegance","","10-08-2024 16:47:41","10-08-2024 15:29:33","10-08-2024 17=
:30:55","grid outage//MDG 20kva deployed(site swapped by ZTE)","Albran Byor=
el","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","gri=
d outage//MDG 20kva deployed(site swapped by ZTE)","landry.etame@ihstowers.=
com","4689","10-08-2024 16:47:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_732","NOCINC0002817396","Nsam esc=
ale LP","","10-08-2024 15:56:10","10-08-2024 15:49:23","10-08-2024 16:40:59=
","Cascaded Incident from TTO2622446","","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","Cascaded Incident from TTO2622446","system","=
407","10-08-2024 15:56:10","Sagemcom CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0002817379","Nsa=
m Sofavinc","IHS_YND_732","10-08-2024 15:53:31","10-08-2024 15:39:23","10-0=
8-2024 16:40:59","site went down due to  rectifier disfuntionning//he reset=
 the retifiers","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","R=
ectifier Module","site went down due to  rectifier disfuntionning//he reset=
 the retifiers","kouoh.jean@ihstowers.com","4913","10-08-2024 15:53:31","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0002817315","V=
allee-Bastos OCM","","10-08-2024 15:39:51","10-08-2024 14:17:45","10-08-202=
4 16:16:18","grid outage//MDG 20kva deployed(site swapped by ZTE)","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage/=
/MDG 20kva deployed(site swapped by ZTE)","landry.etame@ihstowers.com","492=
7","10-08-2024 15:39:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002817193","M=
imboman-Village","","10-08-2024 15:07:33","10-08-2024 13:45:28","10-08-2024=
 16:30:18","No power issue on site ,site on GRid with U=3D53,2V Team Elound=
ou // 693212405 from HUAWEI is informed Notice that we have dysjunction at =
OCM equipements(site Swapped by ZTE)","Mba Lazare Herve","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site ,site on GRid with U=3D53,2V Team Eloundou // 693212405 fr=
om HUAWEI is informed Notice that we have dysjunction at OCM equipements(si=
te Swapped by ZTE)","landry.etame@ihstowers.com","4926","10-08-2024 15:07:3=
3","Sagemcom CMR"
"Closed Complete","Site Down","T0814","IHS_YND_274","NOCINC0002817160","Ema=
na Lycee","","10-08-2024 15:02:30","10-08-2024 14:53:10","10-08-2024 15:38:=
42","grid outage,gen failed to start due to alarm overload//he reset the ca=
rd and started the gen","Fabrice Pouakam","Equipment Repair","Passive","ACD=
G Gen","ACDG - Control Panel","grid outage,gen failed to start due to alarm=
 overload//he reset the card and started the gen","kouoh.jean@ihstowers.com=
","560","10-08-2024 15:02:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0002817119","Etoudi 2=
","","10-08-2024 14:52:51","10-08-2024 14:32:45","10-08-2024 14:44:45","Cas=
caded Incident from TTO2621999","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen failed to start due =
to grid bad voltage//he bypassed grid and started the gen","system","1206",=
"10-08-2024 14:52:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_244","NOCINC0002817117","Abattoir=
","","10-08-2024 14:52:50","10-08-2024 14:32:45","10-08-2024 14:44:45","Cas=
caded Incident from TTO2621999","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,gen failed to start due =
to grid bad voltage//he bypassed grid and started the gen","system","1205",=
"10-08-2024 14:52:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0002817118","ETOUDI C=
HAPELLE","","10-08-2024 14:52:50","10-08-2024 14:32:45","10-08-2024 14:44:4=
5","Cascaded Incident from TTO2621999","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage,gen failed to star=
t due to grid bad voltage//he bypassed grid and started the gen","system","=
1205","10-08-2024 14:52:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002817084","ELOUMDEM=
 CARRIERE","","10-08-2024 14:47:20","10-08-2024 14:19:59","10-08-2024 14:41=
:59","Cascaded Incident from TTO2621938","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down bec=
ause Gen started and stopped due to ""high temp"" alarm //He added water an=
d gen manually started )","system","1641","10-08-2024 14:47:20","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002817085","MBALNGON=
G LYCEE","","10-08-2024 14:47:20","10-08-2024 14:19:59","10-08-2024 14:41:5=
9","Cascaded Incident from TTO2621938","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site went down becau=
se Gen started and stopped due to ""high temp"" alarm //He added water and =
gen manually started )","system","1641","10-08-2024 14:47:20","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002817086","Afanoya"=
,"","10-08-2024 14:47:20","10-08-2024 14:19:59","10-08-2024 14:41:59","Casc=
aded Incident from TTO2621938","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage, site went down because Ge=
n started and stopped due to ""high temp"" alarm //He added water and gen m=
anually started )","system","1641","10-08-2024 14:47:20","Sagemcom CMR"
"Closed Complete","Site Down","T0394","IHS_YND_241","NOCINC0002816986","Eto=
udi","IHS_YND_244, IHS_YND_694, IHS_YND_211","10-08-2024 14:40:08","10-08-2=
024 14:32:45","10-08-2024 14:44:45","grid outage,gen failed to start due to=
 grid bad voltage//he bypassed grid and started the gen","Fabrice Pouakam",=
"Grid Supply","Passive","Grid","National Grid - Phase Controller Faulty","g=
rid outage,gen failed to start due to grid bad voltage//he bypassed grid an=
d started the gen","kouoh.jean@ihstowers.com","443","10-08-2024 14:40:08","=
Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002816940","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","10-08-2024 14:29:46","10-08-20=
24 14:19:59","10-08-2024 14:41:59","grid outage, site went down because Gen=
 started and stopped due to ""high temp"" alarm //He added water and gen ma=
nually started","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","A=
CDG - High Engine Temp - Coolant Level Issue","grid outage, site went down =
because Gen started and stopped due to ""high temp"" alarm //He added water=
 and gen manually started )","kouoh.jean@ihstowers.com","587","10-08-2024 1=
4:29:46","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002816825","Mok=
olo Yaounde","","10-08-2024 14:00:59","10-08-2024 13:56:53","10-08-2024 14:=
04:10"," site went down due to insufficient of rectifier on site// site sta=
bilized","","Equipment Repair","Passive","Rectifier","Rectifier Module","th=
e site went down due to insufficient of the rectifier on site// site stabil=
ized","emmanuel.ghani@ihstowers.com","246","10-08-2024 14:00:59","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002816494","M=
imboman-Village","","10-08-2024 13:04:43","10-08-2024 10:17:35","10-08-2024=
 12:37:59","No power issue on site ,site on GRid with U=3D53,2V Team Elound=
ou // 693212405 from HUAWEI is informed Notice that we have dysjunction at =
OCM equipements(site Swapped by ZTE)","Mba Lazare Herve","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site ,site on GRid with U=3D53,2V Team Eloundou // 693212405 fr=
om HUAWEI is informed Notice that we have dysjunction at OCM equipements(si=
te Swapped by ZTE)","adonis.defokoua@ihstowers.com","10029","10-08-2024 13:=
04:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002816493","ELOUMDEM=
 CARRIERE 2","","10-08-2024 13:04:01","10-08-2024 12:58:04","10-08-2024 16:=
11:08","Cascaded Incident from TTO2621375","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage,Site went  down b=
ecause main gen faulty//grid return","system","357","10-08-2024 13:04:01","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002816492","Eto koss=
 Yde","","10-08-2024 13:04:01","10-08-2024 12:58:04","10-08-2024 16:11:08",=
"Cascaded Incident from TTO2621375","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage,Site went  down because =
main gen faulty//grid return","system","357","10-08-2024 13:04:01","Sagemco=
m CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002816475","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","10-08-2024 13:02:34","10-08-2024 12:58=
:04","10-08-2024 16:11:08","grid outage,Site went  down because main gen fa=
ulty//grid return","Fanda Brice","Equipment Repair","Passive","ACDG Gen","A=
CDG - Generator Faulty","grid outage,Site went  down because main gen fault=
y//grid return","emmanuel.ghani@ihstowers.com","270","10-08-2024 13:02:34",=
"Sagemcom CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0002816185","Mey=
o","","10-08-2024 12:06:41","10-08-2024 12:02:12","10-08-2024 13:06:51","gr=
id outage, site went down because gen failed due to gen overload(17KVA, 190=
A) //He reduiced the load, site on gen","Hyemafo Gildas","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","grid outage, site went down becaus=
e gen failed due to gen overload(17KVA, 190A) //He reduiced the load, site =
on gen","emmanuel.ghani@ihstowers.com","269","10-08-2024 12:06:41","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002816180","ELOUMDEM=
 CARRIERE","","10-08-2024 12:05:50","10-08-2024 12:00:31","10-08-2024 12:54=
:57","Cascaded Incident from TTO2620981","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down bec=
ause Gen started and stopped due to ""high temp"" alarm //He added water an=
d gen manually started","system","319","10-08-2024 12:05:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002816181","MBALNGON=
G LYCEE","","10-08-2024 12:05:50","10-08-2024 12:00:31","10-08-2024 12:54:5=
7","Cascaded Incident from TTO2620981","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site went down becau=
se Gen started and stopped due to ""high temp"" alarm //He added water and =
gen manually started","system","319","10-08-2024 12:05:50","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002816117","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","10-08-2024 12:03:35","10-08-20=
24 11:59:13","10-08-2024 12:54:57","grid outage, site went down because Gen=
 started and stopped due to ""high temp"" alarm //He added water and gen ma=
nually started(Site swapped by ZTE)","Hyemafo Gildas","Equipment Repair","P=
assive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","grid ou=
tage, site went down because Gen started and stopped due to ""high temp"" a=
larm //He added water and gen manually started","emmanuel.ghani@ihstowers.c=
om","3548","10-08-2024 12:03:35","Sagemcom CMR"
"Closed Complete","Site Down","T1557","IHS_YND_313","NOCINC0002816113","Afa=
noya","","10-08-2024 12:02:37","10-08-2024 11:43:23","10-08-2024 12:54:57",=
"","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","grid outage, site went down because Gen started and stopped due to=
 ""high temp"" alarm //He added water and gen manually started(Site swapped=
 by ZTE)","emmanuel.ghani@ihstowers.com","2534","10-08-2024 12:02:37","Sage=
mcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0002816001","Nko=
londom","","10-08-2024 11:43:30","10-08-2024 11:35:26","10-08-2024 13:18:26=
","grid outage and grid return, site went down due to grid contactor did no=
t excited// He excited grid contactor","Fabrice Pouakam","Equipment Repair"=
,"Passive","Control Panel","ATS-AMF Issue","grid outage and grid return, si=
te went down due to grid contactor did not excited// He excited grid contac=
tor","emmanuel.ghani@ihstowers.com","5531","10-08-2024 11:43:30","Sagemcom =
CMR"
"Closed Complete","Site Down","T1597","IHS_YND_670","NOCINC0002815870","BOB=
OCK","","10-08-2024 11:22:38","10-08-2024 10:55:08","10-08-2024 11:38:34","=
","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","grid outage,gen stopped with alarm low oil pressure//he added oil =
and started it","emmanuel.ghani@ihstowers.com","1889","10-08-2024 11:22:38"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T2140","IHS_EDA_102","NOCINC0002815864","NYA=
NON/DEMBO","","10-08-2024 11:21:29","10-08-2024 10:55:08","10-08-2024 11:38=
:34","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","grid outage,gen stopped with alarm low oil pressure=
//he added oil and started it","emmanuel.ghani@ihstowers.com","1889","10-08=
-2024 11:21:29","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0002815831","Abo=
me","","10-08-2024 11:17:43","10-08-2024 11:16:14","10-08-2024 12:37:30","g=
rid outage, site went down due to gen ""overload(15KVA, 300A) // grid retur=
n","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload=
","grid outage, site went down due to gen ""overload(15KVA, 300A) // grid r=
eturn","emmanuel.ghani@ihstowers.com","89","10-08-2024 11:17:43","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_270","IHS_YND_023","NOCINC0002815782","M=
ontesquieux","","10-08-2024 11:08:32","10-08-2024 10:56:23","10-08-2024 12:=
30:36","No power issue on site ubaie=3D54v site on grid  Charles   (Telino/=
/ 672489041) ins on site for  ZTE swap","Paul BIBOUM","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue on site ubaie=3D54v site on grid  Charles   (Telino// 672489041) is o=
n site for  ZTE swap","adonis.defokoua@ihstowers.com","729","10-08-2024 11:=
08:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_552","IHS_YND_680","NOCINC0002815776","M=
IMBOMAN LIBERTE","","10-08-2024 11:06:54","10-08-2024 10:53:42","10-08-2024=
 14:00:20"," No power issue on site ubaie=3D54v site on grid  Franck  (ZT//=
691144395) ins on site for  ZTE swap","Mba Lazare Herve","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No po=
wer issue on site ubaie=3D54v site on grid  Franck  (ZT//691144395) ins on =
site for  ZTE swap","adonis.defokoua@ihstowers.com","793","10-08-2024 11:06=
:54","Sagemcom CMR"
"Closed Complete","Site Down","T0729","IHS_EDA_052","NOCINC0002815732","Nya=
hoo","IHS_EDA_102, IHS_EDA_049, IHS_YND_670","10-08-2024 11:00:25","10-08-2=
024 10:55:08","10-08-2024 11:38:34","grid outage,gen stopped with alarm low=
 oil pressure//he added oil and started it","TIENTCHEU NZETCHIEU GAEL","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","grid outage,=
gen stopped with alarm low oil pressure//he added oil and started it","emma=
nuel.ghani@ihstowers.com","318","10-08-2024 11:00:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002815642","E=
mana","","10-08-2024 10:36:45","10-08-2024 10:17:59","10-08-2024 17:20:00",=
"Grid Outage// grid return ","","Grid Supply","Passive","Grid","National Gr=
id - Grid Outage Issue","Grid Outage// grid return ","adonis.defokoua@ihsto=
wers.com","1127","10-08-2024 10:36:45","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0002815634","EBO=
M","","10-08-2024 10:35:24","10-08-2024 10:34:20","10-08-2024 11:02:44","Gr=
id outage, site went down because Gen started and stopped due to ""high tem=
p"" alarm //He added water and gen manually started","Hyemafo Gildas","Equi=
pment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level=
 Issue","Grid outage, site went down because Gen started and stopped due to=
 ""high temp"" alarm //He added water and gen manually started","emmanuel.g=
hani@ihstowers.com","64","10-08-2024 10:35:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0002815492","ETOUDI C=
HAPELLE","","10-08-2024 10:05:50","10-08-2024 08:01:54","10-08-2024 09:58:0=
5","Cascaded Incident from TTO2620244","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, site went down ge=
cause gen start and stoppen with alarm ""under voltage"" // He reset gen ca=
rd, site on gen(Site swapped by ZTE)","system","7436","10-08-2024 10:05:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0002815493","Messassi=
 okolo","","10-08-2024 10:05:50","10-08-2024 08:01:54","10-08-2024 09:58:05=
","Cascaded Incident from TTO2620244","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, site went down ge=
cause gen start and stoppen with alarm ""under voltage"" // He reset gen ca=
rd, site on gen(Site swapped by ZTE)","system","7436","10-08-2024 10:05:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0002815489","Mballa 4=
","","10-08-2024 10:05:50","10-08-2024 08:01:54","10-08-2024 09:58:05","Cas=
caded Incident from TTO2620244","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, site went down gecause g=
en start and stoppen with alarm ""under voltage"" // He reset gen card, sit=
e on gen(Site swapped by ZTE)","system","7436","10-08-2024 10:05:50","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0002815494","Emana ly=
cee 2","","10-08-2024 10:05:50","10-08-2024 08:01:54","10-08-2024 09:58:05"=
,"Cascaded Incident from TTO2620244","Fabrice Pouakam","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down gec=
ause gen start and stoppen with alarm ""under voltage"" // He reset gen car=
d, site on gen(Site swapped by ZTE)","system","7436","10-08-2024 10:05:50",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0002815491","Emana Ly=
cee","","10-08-2024 10:05:50","10-08-2024 08:01:54","10-08-2024 09:58:05","=
Cascaded Incident from TTO2620244","Fabrice Pouakam","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage, site went down gecau=
se gen start and stoppen with alarm ""under voltage"" // He reset gen card,=
 site on gen(Site swapped by ZTE)","system","7436","10-08-2024 10:05:50","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0002815490","EMANA BI=
LICK CITY","","10-08-2024 10:05:50","10-08-2024 08:01:54","10-08-2024 09:58=
:05","Cascaded Incident from TTO2620244","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","grid outage, site went down=
 gecause gen start and stoppen with alarm ""under voltage"" // He reset gen=
 card, site on gen(Site swapped by ZTE)","system","7436","10-08-2024 10:05:=
50","Sagemcom CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0002815388","Nsa=
m escale LP","","10-08-2024 09:57:56","10-08-2024 09:54:51","10-08-2024 10:=
42:39","grid outage, no space to deploy a mobil gen//grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, =
no space to deploy a mobil gen//grid return","emmanuel.ghani@ihstowers.com"=
,"185","10-08-2024 09:57:56","Sagemcom CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0002815354","Nsa=
m Sofavinc","","10-08-2024 09:56:37","10-08-2024 09:54:31","10-08-2024 10:4=
2:20","grid outage, site went down because gen failed to start  due to gen =
battery discharged// Gen manually started(investigation ongoing)","MINKA NI=
COLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","=
grid outage, site went down because gen failed to start  due to gen battery=
 discharged// Gen manually started(investigation ongoing)","emmanuel.ghani@=
ihstowers.com","126","10-08-2024 09:56:37","Sagemcom CMR"
"Closed Complete","Site Down","T1552","IHS_YND_281","NOCINC0002815255","Odz=
a II","","10-08-2024 09:39:51","10-08-2024 09:38:46","10-08-2024 10:16:56",=
"grid outage, site went down gen failed to start // gen manually started (i=
nvestigation ongoing)","Albran Byorel","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","grid outage, site went down gen failed to start=
 // gen manually started (investigation ongoing)","emmanuel.ghani@ihstowers=
.com","65","10-08-2024 09:39:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002815238","M=
arche Odza","","10-08-2024 09:37:16","10-08-2024 09:29:10","10-08-2024 10:1=
9:38","grid outage, site went down because gen failed to start due to disch=
arged battery// gen started with external battery","Albran Byorel","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Generator Battery","grid outage, si=
te went down because gen failed to start due to discharged battery// gen st=
arted with external battery","adonis.defokoua@ihstowers.com","487","10-08-2=
024 09:37:16","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0002815187","Com=
plex Beac II","","10-08-2024 09:30:24","10-08-2024 09:28:02","10-08-2024 10=
:58:56","grid outage, site went down because gen failed to start with alarm=
 ""Merory correction"" // He reset the Gen card and site on Gen","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid =
outage, site went down because gen failed to start with alarm ""Merory corr=
ection"" // He reset the Gen card and site on Gen","emmanuel.ghani@ihstower=
s.com","142","10-08-2024 09:30:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002815168","ELOUMDEM=
 CARRIERE 2","","10-08-2024 09:27:20","10-08-2024 09:24:01","10-08-2024 10:=
14:11","Cascaded Incident from TTO2619890","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down be=
cause gen failed to started due to Main Gen faulty // MDG of 20KVA has depl=
oyed ","system","199","10-08-2024 09:27:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002815167","Eto koss=
 Yde","","10-08-2024 09:27:20","10-08-2024 09:24:01","10-08-2024 10:14:11",=
"Cascaded Incident from TTO2619890","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because g=
en failed to started due to Main Gen faulty // MDG of 20KVA has deployed ",=
"system","199","10-08-2024 09:27:20","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002815163","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","10-08-2024 09:26:20","10-08-2024 09:24=
:01","10-08-2024 10:14:11","Grid outage site went down because gen failed t=
o started due to Main Gen faulty // MDG of 20KVA has deployed ","Fanda Bric=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid =
outage site went down because gen failed to started due to Main Gen faulty =
// MDG of 20KVA has deployed ","emmanuel.ghani@ihstowers.com","140","10-08-=
2024 09:26:20","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002815153","Mok=
olo Yaounde","","10-08-2024 09:25:05","10-08-2024 09:21:53","10-08-2024 09:=
54:28","grid outage, no space to deploy a mobil gen// grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,=
 no space to deploy a mobil gen// grid return","emmanuel.ghani@ihstowers.co=
m","192","10-08-2024 09:25:05","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0002815094","Men=
dong vallee","","10-08-2024 09:11:33","10-08-2024 09:07:28","10-08-2024 09:=
34:39","grid outage, site went down because gen faild to start due to gen O=
verload(20KVA, 310 A) // He reduiced the load site on DG.","Fanda Brice","E=
quipment Repair","Passive","ACDG Gen","ACDG - Overload","grid outage, site =
went down because gen faild to start due to gen Overload(20KVA, 310 A) // H=
e reduiced the load site on DG.","emmanuel.ghani@ihstowers.com","245","10-0=
8-2024 09:11:33","Sagemcom CMR"
"Closed Complete","Site Down","T1328","IHS_YND_247","NOCINC0002815069","Oko=
lo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_694, IHS_YND_279, IHS_Y=
ND_685","10-08-2024 09:03:05","10-08-2024 08:01:54","10-08-2024 10:09:40","=
grid outage, site went down gecause gen start and stoppen with alarm ""unde=
r voltage"" // He reset gen card, site on gen(Site swapped by ZTE)","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
grid outage, site went down gecause gen start and stoppen with alarm ""unde=
r voltage"" // He reset gen card, site on gen(Site swapped by ZTE)","emmanu=
el.ghani@ihstowers.com","7207","10-08-2024 09:03:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0002812474","N=
koabang","","10-08-2024 00:31:16","09-08-2024 21:07:19","10-08-2024 02:42:4=
2","Active: No power issue, site is on Grid with U=3D56,7V ,  The TX FME Li=
onel adjep//655184876//   Huawei is informed (swapping by ZTE ))","Mba Laza=
re Herve","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active: No power issue, site is on Grid with U=3D56,7=
V ,  The TX FME Lionel adjep//655184876//   Huawei is informed (swapping by=
 ZTE ))","dorothy.djantio@ihstowers.com","12238","10-08-2024 00:31:16","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0002812457","C=
hapelle-Nsimeyong","","10-08-2024 00:28:50","09-08-2024 21:45:31","09-08-20=
24 21:50:08","Active// Active: No power issue, site is on Grid with Ubaie=
=3D54,4V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed Site swa=
pped by ZTE","MINKA NICOLAS","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active// Active: No power issue, s=
ite is on Grid with Ubaie=3D54,4V,The tx Fme Hosiah (6 74 00 74 38) from Hu=
awei is informed Site swapped by ZTE","dorothy.djantio@ihstowers.com","9800=
","10-08-2024 00:28:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002812410","M=
imboman-Village","","10-08-2024 00:16:48","09-08-2024 21:07:47","10-08-2024=
 07:50:16","No power issue on site ,site on GRid with U=3D53,2V Team Elound=
ou // 693212405 from HUAWEI is informed Notice that we have dysjunction at =
OCM equipements(site Swapped by ZTE)","Mba Lazare Herve","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site ,site on GRid with U=3D53,2V Team Eloundou // 693212405 fr=
om HUAWEI is informed Notice that we have dysjunction at OCM equipements(si=
te Swapped by ZTE)","dorothy.djantio@ihstowers.com","11341","10-08-2024 00:=
16:48","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0002812385","UPA=
C LP","","10-08-2024 00:05:17","10-08-2024 00:00:12","10-08-2024 02:41:12",=
"No power issue site on grid with U=3D54.2v //site up at 00:37 AM Symphorie=
n from Huawei is informed","","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with =
U=3D54.2v //site up at 00:37 AM Symphorien from Huawei is informed","ludivi=
ne.ngamaleu@ihstowers.com","306","10-08-2024 00:05:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0002811781","E=
bogo","","09-08-2024 21:39:02","09-08-2024 20:23:56","10-08-2024 01:50:14",=
"Active, no power issue,site on grid with U=3D54V Symphorien /650257151/ Fr=
om huawei is informed (site swapped by ZTE)","Siligap Boris","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive, no power issue,site on grid with U=3D54V Symphorien /650257151/ From =
huawei is informed (site swapped by ZTE)","alexandre.kamal@ihstowers.com","=
4506","09-08-2024 21:39:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0002811762","A=
kak-Nkozoa-MTN-IHS","","09-08-2024 21:36:46","09-08-2024 21:09:36","10-08-2=
024 01:24:58","No power issue on site Ubaie =3D54V site on Grid The TX FME =
Synphorien//691316854   from huawei is informed","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Ubaie =3D54V site on Grid The TX FME Synphorien/=
/691316854   from huawei is informed","alexandre.kamal@ihstowers.com","1630=
","09-08-2024 21:36:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0002811425","S=
hell-Nsimeyong","","09-08-2024 21:07:44","09-08-2024 19:57:38","10-08-2024 =
03:17:54","Active// Active: No power issue, site is on Grid with Ubaie=3D54=
,2V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed (site swapped=
 by ZTE)","MINKA NICOLAS","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Active// Active: No power issue, site=
 is on Grid with Ubaie=3D54,2V,The tx Fme Hosiah (6 74 00 74 38) from Huawe=
i is informed (site swapped by ZTE)","alexandre.kamal@ihstowers.com","4207"=
,"09-08-2024 21:07:44","Sagemcom CMR"
"Closed Complete","Site Down","T3155","IHS_YND_173","NOCINC0002810631","AWA=
E OCM","","09-08-2024 20:05:43","09-08-2024 19:53:29","09-08-2024 20:22:45"=
,"Grid outage, site down because Gen failed due to poor backup before gen s=
tart//Grid power return ","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site down becaus=
e Gen failed due to poor backup before gen start//Grid power return ","deni=
s.mballa@ihstowers.com","4172","09-08-2024 20:05:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0002810520","E=
lig Edzoa","","09-08-2024 19:51:39","09-08-2024 18:55:29","09-08-2024 19:06=
:06","Grid outage, site down because Gen failed due to poor backup before g=
en start//Grid power return(site swapped by ZTE)","Delor Telezing","Equipme=
nt Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid ou=
tage, site down because Gen failed due to poor backup before gen start//Gri=
d power return(site swapped by ZTE)","alexandre.kamal@ihstowers.com","3371"=
,"09-08-2024 19:51:39","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002810286","Man=
guiers Dispensaire","","09-08-2024 19:09:21","09-08-2024 19:07:12","09-08-2=
024 19:19:22","Site went down due to grid contactor faulty//He replaced the=
 Grid contactor and site on Grid","Fabrice Pouakam","Equipment Repair","Pas=
sive","Control Panel","ATS-AMF Issue","Site went down due to grid contactor=
 faulty//He replaced the Grid contactor and site on Grid","denis.mballa@ihs=
towers.com","129","09-08-2024 19:09:21","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002810264","Jou=
vence 2000","","09-08-2024 19:06:30","09-08-2024 19:00:18","09-08-2024 20:4=
7:06","Grid outage, site down because Gen failed due to poor backup before =
gen start//Grid power return ","Delor Telezing","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site down bec=
ause Gen failed due to poor backup before gen start//Grid power return ","d=
enis.mballa@ihstowers.com","373","09-08-2024 19:06:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0002810060","N=
kolfoulou","","09-08-2024 18:44:14","09-08-2024 18:22:10","09-08-2024 18:25=
:05","No power issue on site U=3D54 v site on grid the Team Kevin /69443499=
3/ZTE working on site.","Siligap Boris","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D54 v site on grid the Team Kevin /694434993/ZTE working on site.","alex=
andre.kamal@ihstowers.com","1325","09-08-2024 18:44:14","Sagemcom CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0002809808","Nko=
mo","","09-08-2024 18:05:20","09-08-2024 18:01:10","09-08-2024 18:41:25","G=
rid outage, site went down because Gen started and stopped due to ""high te=
mp"" alarm //He added water and gen manually started(site swapped by ZTE)",=
"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Eng=
ine Temp - Coolant Level Issue","Grid outage, site went down because Gen st=
arted and stopped due to ""high temp"" alarm //He added water and gen manua=
lly started(site swapped by ZTE)","denis.mballa@ihstowers.com","251","09-08=
-2024 18:05:20","Sagemcom CMR"
"Closed Complete","Site Down","T0604","IHS_YND_171","NOCINC0002809591","Awa=
e Escalier","","09-08-2024 17:25:56","09-08-2024 17:20:40","09-08-2024 17:5=
2:55","Grid outage, site went down because gen start and stoppen with alarm=
 ""Low oil pressure"" // He added Oil and started start GE manually","Albra=
n Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure"=
,"Grid outage, site went down because gen start and stoppen with alarm ""Lo=
w oil pressure"" // He added Oil and started start GE manually","denis.mbal=
la@ihstowers.com","316","09-08-2024 17:25:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0002809297","N=
koabang","","09-08-2024 16:39:35","09-08-2024 15:39:30","09-08-2024 15:45:3=
0","Active: No power issue, site is on Grid with U=3D56,7V ,  The TX FME Li=
onel adjep//655184876//   Huawei is informed (swapping by ZTE ))","Mba Laza=
re Herve","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active: No power issue, site is on Grid with U=3D56,7=
V ,  The TX FME Lionel adjep//655184876//   Huawei is informed (swapping by=
 ZTE ))","alexandre.kamal@ihstowers.com","3605","09-08-2024 16:39:35","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_633","IHS_YND_241","NOCINC0002809295","E=
toudi","","09-08-2024 16:38:37","09-08-2024 15:36:31","09-08-2024 15:40:54"=
,"No power issue on site U=3D51v site on grid the Team yves/699127444/ZTE w=
orking on site.","Fabrice Pouakam","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
1v site on grid the Team yves/699127444/ZTE working on site.","alexandre.ka=
mal@ihstowers.com","3726","09-08-2024 16:38:37","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0002809120","Nko=
mo stade","","09-08-2024 16:16:42","09-08-2024 16:14:13","09-08-2024 16:54:=
37","Grid outage, site went down because Gen started and stopped due to ""h=
igh temp"" alarm //He added water and gen manually started","Mba Lazare Her=
ve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Cool=
ant Level Issue","Grid outage, site went down because Gen started and stopp=
ed due to ""high temp"" alarm //He added water and gen manually started","d=
enis.mballa@ihstowers.com","150","09-08-2024 16:16:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002809038","M=
imboman-Village","","09-08-2024 15:56:24","09-08-2024 12:49:19","09-08-2024=
 12:55:55","No power issue on site ,site on GRid with U=3D53,2V Team Elound=
ou // 693212405 from HUAWEI is informed Notice that we have dysjunction at =
OCM equipements(site Swapped by ZTE)","Mba Lazare Herve","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site ,site on GRid with U=3D53,2V Team Eloundou // 693212405 fr=
om HUAWEI is informed Notice that we have dysjunction at OCM equipements(si=
te Swapped by ZTE)","alexandre.kamal@ihstowers.com","11226","09-08-2024 15:=
56:24","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002809001","Aka=
k-Nkozoa-MTN-IHS","","09-08-2024 15:46:03","09-08-2024 15:42:51","09-08-202=
4 16:24:49","Grid outage;Main gen faulty//he connected MDG 20kva ","Fabrice=
 Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty"=
,"Grid outage;Main gen faulty//he connected MDG 20kva ","denis.mballa@ihsto=
wers.com","193","09-08-2024 15:46:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_621","IHS_YND_278","NOCINC0002808954","N=
kolfoulou 2","","09-08-2024 15:37:56","09-08-2024 15:29:52","09-08-2024 15:=
35:04","No power issue on site U=3D54,4 v site on grid the Team Franck/654 =
24 29 33/ZTE working on site.","Siligap Boris","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D54,4 v site on grid the Team Franck/654 24 29 33/ZTE working on =
site.","alexandre.kamal@ihstowers.com","485","09-08-2024 15:37:56","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002808907","B=
iteng","","09-08-2024 15:29:25","09-08-2024 14:35:48","09-08-2024 14:40:57"=
,"Active: No power issue, site is on Grid with U=3D54,4V ,  The TX FME Lion=
el adjep//655184876//   Huawei is informed Notice that we have dysjunction =
at OCM equipements (swapping by ZTE )","Mba Lazare Herve","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue, site is on Grid with U=3D54,4V ,  The TX FME Lionel adje=
p//655184876//   Huawei is informed Notice that we have dysjunction at OCM =
equipements (swapping by ZTE )","alexandre.kamal@ihstowers.com","3217","09-=
08-2024 15:29:25","Sagemcom CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0002808837","Awa=
e Ewonkan","","09-08-2024 15:17:48","09-08-2024 15:12:35","09-08-2024 16:14=
:59","Grid outa, site went down because Gen failed to start due to Gen card=
 dysfonction// He reset the Gen card and site on GEN","Albran Byorel","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outa, site =
went down because Gen failed to start due to Gen card dysfonction// He rese=
t the Gen card and site on GEN","denis.mballa@ihstowers.com","3870","09-08-=
2024 15:17:48","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0002808671","Mba=
nkolo petit paris","","09-08-2024 15:04:31","09-08-2024 15:01:21","09-08-20=
24 18:05:46","Active: No power issue, site on gen with Ubaie=3D54.5V, Brice=
 Tsague (650 21 40 96) from Huawei working on site.","Mboua Thierry","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active: No power issue, site on gen with Ubaie=3D54.5V, Brice Tsague =
(650 21 40 96) from Huawei working on site.","denis.mballa@ihstowers.com","=
191","09-08-2024 15:04:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0002808645","NKONGKAR=
AK","","09-08-2024 14:58:10","09-08-2024 13:59:56","09-08-2024 15:13:17","C=
ascaded Incident from TTO2612417","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","site went Down because Ge=
n failed to start due to Hybrid system dysfonction// He reset the Gen card =
 and Gen manually started","system","3494","09-08-2024 14:58:10","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0002808636","Lobo 2",=
"","09-08-2024 14:58:10","09-08-2024 13:59:56","09-08-2024 15:13:17","Casca=
ded Incident from TTO2612417","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went Down because Gen fa=
iled to start due to Hybrid system dysfonction// He reset the Gen card  and=
 Gen manually started","system","3494","09-08-2024 14:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0002808639","Ebeba","=
","09-08-2024 14:58:10","09-08-2024 13:59:56","09-08-2024 15:13:17","Cascad=
ed Incident from TTO2612417","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went Down because Gen failed to start =
due to Hybrid system dysfonction// He reset the Gen card  and Gen manually =
started","system","3494","09-08-2024 14:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_366","NOCINC0002808641","Mandoumb=
a MTN","","09-08-2024 14:58:10","09-08-2024 13:59:56","09-08-2024 15:13:17"=
,"Cascaded Incident from TTO2612417","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went Down because Gen fail=
ed to start due to Hybrid system dysfonction// He reset the Gen card  and G=
en manually started","system","3494","09-08-2024 14:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0002808642","Nkongtoc=
k","","09-08-2024 14:58:10","09-08-2024 13:59:56","09-08-2024 15:13:17","Ca=
scaded Incident from TTO2612417","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went Down because Gen failed t=
o start due to Hybrid system dysfonction// He reset the Gen card  and Gen m=
anually started","system","3494","09-08-2024 14:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0002808643","Ekekam",=
"","09-08-2024 14:58:10","09-08-2024 13:59:56","09-08-2024 15:13:17","Casca=
ded Incident from TTO2612417","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","site went Down because Gen fa=
iled to start due to Hybrid system dysfonction// He reset the Gen card  and=
 Gen manually started","system","3494","09-08-2024 14:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0002808640","Bot Maka=
k","","09-08-2024 14:58:10","09-08-2024 13:59:56","09-08-2024 15:13:17","Ca=
scaded Incident from TTO2612417","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","site went Down because Gen failed to start due to =
Hybrid system dysfonction// He reset the Gen card  and Gen manually started=
","system","3494","09-08-2024 14:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0002808638","Ngog Map=
ubi","","09-08-2024 14:58:10","09-08-2024 13:59:56","09-08-2024 15:13:17","=
Cascaded Incident from TTO2612417","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went Down because Gen failed=
 to start due to Hybrid system dysfonction// He reset the Gen card  and Gen=
 manually started","system","3494","09-08-2024 14:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0002808637","Nkeng li=
kok","","09-08-2024 14:58:10","09-08-2024 13:59:56","09-08-2024 15:13:17","=
Cascaded Incident from TTO2612417","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went Down because Gen failed=
 to start due to Hybrid system dysfonction// He reset the Gen card  and Gen=
 manually started","system","3494","09-08-2024 14:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0002808644","LOBO MTN=
","","09-08-2024 14:58:10","09-08-2024 13:59:56","09-08-2024 15:13:17","Cas=
caded Incident from TTO2612417","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","site went Down because Gen =
failed to start due to Hybrid system dysfonction// He reset the Gen card  a=
nd Gen manually started","system","3494","09-08-2024 14:58:10","Sagemcom CM=
R"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0002808562","Eli=
g Edzoa","","09-08-2024 14:40:40","09-08-2024 14:36:26","09-08-2024 15:28:3=
2","Grid outage, site went down because gen start and stoppen with alarm ""=
Low oil pressure"" // He added Oil and started start GE manually","Delor Te=
lezing","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","=
Grid outage, site went down because gen start and stoppen with alarm ""Low =
oil pressure"" // He added Oil and started start GE manually","denis.mballa=
@ihstowers.com","254","09-08-2024 14:40:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_852","IHS_YND_220","NOCINC0002808558","G=
olf Quater","","09-08-2024 14:39:49","09-08-2024 14:30:59","09-08-2024 15:3=
5:52","No power issue on site U=3D54 V site on Grid the fme Tx  Eloundou //=
 693212405 from HUAWEI is informed","Mboua Thierry","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site U=3D54 V site on Grid the fme Tx  Eloundou // 693212405 from HU=
AWEI is informed","alexandre.kamal@ihstowers.com","531","09-08-2024 14:39:4=
9","Sagemcom CMR"
"Closed Complete","Site Down","T0236","IHS_YND_373","NOCINC0002808297","Mal=
oun","IHS_YND_783, IHS_YND_347, IHS_YND_419, IHS_YND_339, IHS_YND_421, IHS_=
YND_366, IHS_YND_349, IHS_YND_714, IHS_YND_342, IHS_YND_713","09-08-2024 14=
:06:49","09-08-2024 13:59:56","09-08-2024 15:13:17","site went Down because=
 Gen failed to start due to Hybrid system dysfonction// He reset the Gen ca=
rd  and Gen manually started","Kemeni Franklin","Equipment Repair","Passive=
","Hybrid","Hybrid Module","site went Down because Gen failed to start due =
to Hybrid system dysfonction// He reset the Gen card  and Gen manually star=
ted","kouoh.jean@ihstowers.com","414","09-08-2024 14:06:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0002808020","M=
volye-New","","09-08-2024 13:22:46","09-08-2024 13:14:34","09-08-2024 15:14=
:12","Grid outage//MDG of 20kva has deployed (site swapped by ZTE)","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
//MDG of 20kva has deployed (site swapped by ZTE)","landry.etame@ihstowers.=
com","492","09-08-2024 13:22:46","Sagemcom CMR"
"Closed Complete","Site Down","T0539","IHS_YND_034","NOCINC0002807993","EMI=
A MTN","","09-08-2024 13:20:36","09-08-2024 13:11:27","09-08-2024 14:56:02"=
,"Grid outage no space to deploy //Grid power return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage no space to d=
eploy //Grid power return","kouoh.jean@ihstowers.com","550","09-08-2024 13:=
20:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0002807935","S=
oa-II","","09-08-2024 13:08:04","09-08-2024 12:42:51","09-08-2024 13:15:19"=
,"No power issue on site U=3D54,4v site on grid Team Clovis 650031080/ZTE w=
orking on site","Siligap Boris","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,4=
v site on grid Team Clovis 650031080/ZTE working on site","landry.etame@ihs=
towers.com","1513","09-08-2024 13:08:04","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0002807934","Av =
Kennedy","","09-08-2024 13:07:16","09-08-2024 13:01:03","09-08-2024 13:29:3=
7","No power issue on site U=3D53v site on grid Eloundou of huawei is infor=
med","","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site U=3D53v site on grid Eloundou of=
 huawei is informed","kouoh.jean@ihstowers.com","373","09-08-2024 13:07:16"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_674","IHS_YND_720","NOCINC0002807759","S=
OA UNIVERSITY STADIUM","","09-08-2024 12:36:34","09-08-2024 09:48:25","09-0=
8-2024 12:38:58","No power issue on site U=3D54v site on grid Team Yvan 679=
375329 working on site","Siligap Boris","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D54v site on grid Team Yvan 679375329 working on site","landry.etame@ihs=
towers.com","10089","09-08-2024 12:36:34","Sagemcom CMR"
"Closed Complete","Site Down","T3149","IHS_YND_044","NOCINC0002807680","Pol=
ytechnique","","09-08-2024 12:19:07","09-08-2024 12:06:53","09-08-2024 14:5=
3:55","Grid outage no space to deploy //Grid power return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space=
 to deploy //Grid power return","kouoh.jean@ihstowers.com","4491","09-08-20=
24 12:19:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0002807545","L=
eboudi","","09-08-2024 11:45:21","09-08-2024 11:32:15","09-08-2024 11:55:15=
","No power issue on site U=3D53,9v site on grid Mohamadou of huawei is inf=
ormed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53=
,9v site on grid Mohamadou of huawei is informed","landry.etame@ihstowers.c=
om","786","09-08-2024 11:45:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0002807502","N=
kolkoumou OCM","","09-08-2024 11:43:21","09-08-2024 11:32:16","09-08-2024 1=
2:16:43","No power issue on site U=3D48,6v site on battery Mohamadou of hua=
wei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D48,6v site on battery Mohamadou of huawei is informed","landry.etam=
e@ihstowers.com","666","09-08-2024 11:43:21","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0002807204","Nko=
londom","","09-08-2024 10:49:17","09-08-2024 10:39:59","09-08-2024 12:28:46=
","grid outage,gen stopped with alarm low oil pressure//he reset card Ge an=
d started the gen","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen=
","ACDG - Low Oil Pressure","grid outage,gen stopped with alarm low oil pre=
ssure//he reset card Ge and started the gen","kouoh.jean@ihstowers.com","55=
9","09-08-2024 10:49:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0002807124","Kondengu=
i","","09-08-2024 10:37:30","09-08-2024 10:28:36","09-08-2024 14:21:11","Ca=
scaded Incident from TTO2610993","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage,No space to deploy a mobi=
l gen//grid return","system","534","09-08-2024 10:37:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0002807119","E=
mombo-Tchad","IHS_YND_114","09-08-2024 10:36:42","09-08-2024 10:28:36","09-=
08-2024 14:21:11","	Grid outage,No space to deploy a mobil gen//grid return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage,No space to deploy a mobil gen//grid return","landry.etame@ihstow=
ers.com","486","09-08-2024 10:36:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002806889","B=
iteng","","09-08-2024 10:01:04","09-08-2024 09:45:57","09-08-2024 10:24:33"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen started(site swapped by ZTE)","Mba Lazare Herve","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site w=
ent down before gen start due to poor battery backup // Gen started(site sw=
apped by ZTE)","landry.etame@ihstowers.com","908","09-08-2024 10:01:04","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002806601","O=
lembe-Terminus","","09-08-2024 09:13:51","09-08-2024 09:01:46","09-08-2024 =
09:18:57","No power issue on site U=3D54v site on grid Team Edy/6 99221717/=
ZTE working on site","Fabrice Pouakam","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54v site on grid Team Edy/6 99221717/ZTE working on site","landry.etame@=
ihstowers.com","725","09-08-2024 09:13:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_378","NOCINC0002806591","Eseka To=
wn","","09-08-2024 09:10:40","09-08-2024 09:00:15","09-08-2024 09:10:11","C=
ascaded Incident from TTO2610372","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen failed to start du=
e to Card Ge,Relay de demarrage,02 fuse are faulty causing by ligtning//Gen=
 started manually","system","625","09-08-2024 09:10:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_453","NOCINC0002806592","Song-bon=
g","","09-08-2024 09:10:40","09-08-2024 09:00:15","09-08-2024 09:10:11","Ca=
scaded Incident from TTO2610372","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage,gen failed to start due=
 to Card Ge,Relay de demarrage,02 fuse are faulty causing by ligtning//Gen =
started manually","system","625","09-08-2024 09:10:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_067","IHS_YND_377","NOCINC0002806589","E=
seka OCM","IHS_YND_378, IHS_YND_453","09-08-2024 09:09:20","09-08-2024 09:0=
0:15","09-08-2024 09:10:11","grid outage,gen failed to start due to Card Ge=
,Relay de demarrage,02 fuse are faulty causing by ligtning//Gen started man=
ually","Kemeni Franklin","Force Majeure","Natural Disaster","Thunderstrike"=
,"Equipment Damaged","grid outage,gen failed to start due to Card Ge,Relay =
de demarrage,02 fuse are faulty causing by ligtning//Gen started manually",=
"landry.etame@ihstowers.com","546","09-08-2024 09:09:20","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002806578","MAN=
GUIERS CHAPELLE","","09-08-2024 09:05:06","09-08-2024 09:00:47","09-08-2024=
 09:39:47","grid outage,gen failed to start due to alarm underfrequency//gr=
id return","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG =
- Control Panel","Grid outage: gen failed to start due to alarm underfreque=
ncy//grid return","kouoh.jean@ihstowers.com","260","09-08-2024 09:05:06","S=
agemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002806064","Mok=
olo Yaounde","","09-08-2024 07:42:29","09-08-2024 07:33:15","09-08-2024 15:=
53:02","Grid outage no space to deploy //Grid power return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no spac=
e to deploy //Grid power return","kouoh.jean@ihstowers.com","554","09-08-20=
24 07:42:29","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0002805302","Bas=
tos Bethesda","","09-08-2024 04:29:26","09-08-2024 04:25:20","09-08-2024 04=
:33:24","Grid outage site went down before Gen started due to poor battery =
back up // Grid return","Mboua Thierry","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage site went down before =
Gen started due to poor battery back up // Grid return","ange.kongo@ihstowe=
rs.com","247","09-08-2024 04:29:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0002805154","Nkolo II=
 New","IHS_YND_266","09-08-2024 03:29:30","09-08-2024 03:18:59","09-08-2024=
 04:48:17","grid outage, site went down because gen started and Stopped  to=
 start with alarm""over current"" // He Reset the Gen card and Gen automati=
cally started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","=
ACDG - Control Panel","grid outage, site went down because gen started and =
Stopped  to start with alarm""over current"" // He Reset the Gen card and G=
en automatically started","system","631","09-08-2024 03:29:30","Sagemcom CM=
R"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0002805153","Mim=
boman4","","09-08-2024 03:28:45","09-08-2024 03:18:59","09-08-2024 04:56:14=
","tikect need to attach at nkolo2","Mba Lazare Herve","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage, site went down bec=
ause gen started and Stopped  to start with alarm""over current"" // He Res=
et the Gen card and Gen automatically started","ange.kongo@ihstowers.com","=
586","09-08-2024 03:28:45","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002804914","Man=
guiers Dispensaire","","09-08-2024 01:51:11","09-08-2024 01:46:59","09-08-2=
024 04:59:16","Access isssue due to landlord,grid outage,site went down due=
 to grid contactor faulty//Gen manually started","Fabrice Pouakam","Access =
Denial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lor=
d","Access isssue due to landlord,grid outage,site went down due to grid co=
ntactor faulty//Gen manually started","ange.kongo@ihstowers.com","252","09-=
08-2024 01:51:11","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002804828","Man=
guiers Dispensaire","","09-08-2024 01:03:53","09-08-2024 00:57:59","09-08-2=
024 01:07:57","site went Down because Gen failed to start due to the Grid c=
ontactor Faulty // He bypass The Grid contactor and  site on Grid","Fabrice=
 Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","sit=
e went Down because Gen failed to start due to the Grid contactor Faulty //=
 He bypass The Grid contactor and  site on Grid","ange.kongo@ihstowers.com"=
,"355","09-08-2024 01:03:53","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002804649","Mok=
olo Yaounde","","08-08-2024 23:52:17","08-08-2024 23:49:10","09-08-2024 06:=
32:25","grid outage,no space to deploy a mobil gen//grid return","","Grid S=
upply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,no=
 space to deploy a mobil gen//grid return","ange.kongo@ihstowers.com","187"=
,"08-08-2024 23:52:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0002804604","A=
kak-Nkozoa-MTN-IHS","","08-08-2024 23:35:32","08-08-2024 22:59:19","08-08-2=
024 23:45:36","Grid outage;Main gen faulty//he connected MDG 20kva  (site s=
wapped by ZTE)","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","=
ACDG - Generator Faulty","Grid outage;Main gen faulty//he connected MDG 20k=
va  (site swapped by ZTE)","joelle.ekessi@ihstowers.com","2174","08-08-2024=
 23:35:32","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002804447","Mok=
olo Yaounde","","08-08-2024 22:46:31","08-08-2024 22:44:09","08-08-2024 23:=
21:29","Grid outage No space to deployed a mobile Gen // Grid return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge No space to deployed a mobile Gen // Grid return","ange.kongo@ihstowers.=
com","142","08-08-2024 22:46:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002804393","M=
imboman-Village","","08-08-2024 22:31:32","08-08-2024 18:31:27","08-08-2024=
 18:36:49","No  power issue  on site ,site on GRid  with U=3D53,2V Team Elo=
undou // 693212405  from HUAWEI  is informed   Notice that we have dysjunct=
ion at OCM equipements(site Swapped by ZTE)","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No  power issue  on site ,site on GRid  with U=3D53,2V Team Eloundou // 69=
3212405  from HUAWEI  is informed   Notice that we have dysjunction at OCM =
equipements(site Swapped by ZTE)","joelle.ekessi@ihstowers.com","14405","08=
-08-2024 22:31:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0002804375","N=
KOLMEKONG YDE","","08-08-2024 22:27:05","08-08-2024 20:09:57","09-08-2024 0=
0:58:07","site down because CB(80A) tripped in PWC because the load of the =
site increased//shunted  a CB 80A with a CB 80A(site swapped by ZTE)","Fabr=
ice Pouakam","Equipment Repair","Passive","Control Panel","Power Cabinet - =
Circuit Breaker Issue","site down because CB(80A) tripped in PWC because th=
e load of the site increased//shunted  a CB 80A with a CB 80A(site swapped =
by ZTE)","joelle.ekessi@ihstowers.com","8228","08-08-2024 22:27:05","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0002803371","Mimboman=
4","","08-08-2024 20:27:10","08-08-2024 20:05:16","08-08-2024 20:31:24","Ca=
scaded Incident from TTO2606635 - Cascade Removed From TTO2606635","Mba Laz=
are Herve","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
site went down because Gen stopped with alarm Gen over current// He reduced=
 01 rectifier on site and Gen manually started","system","1314","08-08-2024=
 20:27:10","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0002803301","Nko=
lo II New","IHS_YND_266","08-08-2024 20:11:24","08-08-2024 20:05:16","08-08=
-2024 20:31:24","site went down because Gen stopped with alarm Gen over cur=
rent// He reduced 01 rectifier on site and Gen manually started","Mba Lazar=
e Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","si=
te went down because Gen stopped with alarm Gen over current// He reduced 0=
1 rectifier on site and Gen manually started","ludivine.ngamaleu@ihstowers.=
com","368","08-08-2024 20:11:24","Sagemcom CMR"
"Cancelled","Warning","T1105","IHS_YND_266","NOCINC0002803282","Mimboman4",=
"","08-08-2024 20:08:37","","","","Mba Lazare Herve","","","","","","ludivi=
ne.ngamaleu@ihstowers.com","186","08-08-2024 20:08:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0002803251","ARMP",""=
,"08-08-2024 20:01:30","08-08-2024 19:47:30","08-08-2024 19:50:05","Cascade=
d Incident from TTO2606546","","Cascade Outage","Active","Cascade Active","=
Cascade Active","no power issue  on site ,site on GRid  with U=3D54,5V Team=
 Eloundou // 693212405  from HUAWEI  is informed","system","840","08-08-202=
4 20:01:30","Sagemcom CMR"
"Cancelled","Warning","CTR_124","IHS_YND_208","NOCINC0002803237","ARMP","",=
"08-08-2024 19:58:58","","","","","","","","","","dorothy.djantio@ihstowers=
.com","724","08-08-2024 19:58:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0002803226","B=
astos Bir","IHS_YND_208","08-08-2024 19:57:01","08-08-2024 19:47:30","08-08=
-2024 20:10:05","no power issue  on site ,site on GRid  with U=3D54,5V Team=
 Eloundou // 693212405  from HUAWEI  is informed","Mboua Thierry","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","no power issue  on site ,site on GRid  with U=3D54,5V Team Eloundou // 6=
93212405  from HUAWEI  is informed","dorothy.djantio@ihstowers.com","572","=
08-08-2024 19:57:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002803113","M=
asque","","08-08-2024 19:35:05","08-08-2024 19:28:52","08-08-2024 20:15:11"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V   The TX FME  Elo=
undou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V=
   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive=
 issue","dorothy.djantio@ihstowers.com","374","08-08-2024 19:35:05","Sagemc=
om CMR"
"Closed Complete","Site Down","T0870","IHS_YND_444","NOCINC0002803099","Don=
g","","08-08-2024 19:31:59","08-08-2024 19:25:24","08-08-2024 21:47:20","Hy=
brid Gen Site, Site went down because gen ran until fuel shortage//Refuelin=
g done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outage","H=
ybrid Gen Site, Site went down because gen ran until fuel shortage//Refueli=
ng done","ludivine.ngamaleu@ihstowers.com","548","08-08-2024 19:31:59","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002803055","C=
arington","","08-08-2024 19:19:26","08-08-2024 16:22:18","08-08-2024 20:30:=
52","No power issue site on grid with U=3D54v Notice that we have disjuncti=
on at OCM Equipements Armand Nguetsa  from Huawei is informed","","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","No power issue site on grid with U=3D54v Notice that we have disjunction=
 at OCM Equipements Armand Nguetsa  from Huawei is informed","etienne.itond=
o@ihstowers.com","10629","08-08-2024 19:19:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_084","IHS_YND_294","NOCINC0002803026","N=
koabang","","08-08-2024 19:13:49","08-08-2024 15:46:33","08-08-2024 22:00:2=
7","Active: No power issue, site is on Grid with U=3D54,2V ,  The TX FME Li=
onel adjep//655184876//   Huawei is informed Notice that Disjunction in BTS=
 Ocm(swapping by ZTE ))","Mba Lazare Herve","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power is=
sue, site is on Grid with U=3D54,2V ,  The TX FME Lionel adjep//655184876//=
   Huawei is informed Notice that Disjunction in BTS Ocm(swapping by ZTE ))=
","etienne.itondo@ihstowers.com","12437","08-08-2024 19:13:49","Sagemcom CM=
R"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002802979","Mok=
olo Yaounde","","08-08-2024 19:04:57","08-08-2024 19:00:53","08-08-2024 21:=
51:43"," Grid ouytage No space to deploy a mobil gen // Grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue"," Gri=
d ouytage No space to deploy a mobil gen // Grid power return","ludivine.ng=
amaleu@ihstowers.com","244","08-08-2024 19:04:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0002802782","N=
kolbong","","08-08-2024 18:30:58","08-08-2024 18:20:50","08-08-2024 19:51:3=
1","No power issue on site U=3D52v site on grid Team Charles/695559948/ZTE =
working on site","Delor Telezing","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52=
v site on grid Team Charles/695559948/ZTE working on site","dorothy.djantio=
@ihstowers.com","608","08-08-2024 18:30:58","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002802698","Eko=
unou","","08-08-2024 18:10:33","08-08-2024 18:10:29","08-08-2024 18:18:56",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Grid power return","Albran Byorel","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before gen=
 start due to poor battery backup // Grid power return","ludivine.ngamaleu@=
ihstowers.com","5","08-08-2024 18:10:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_431","IHS_YND_321","NOCINC0002802427","S=
oa","IHS_YND_324","08-08-2024 17:18:13","08-08-2024 17:11:06","08-08-2024 1=
8:49:21","No power issue on site U=3D54,3v site on grid Team Clement/691927=
185/ZTE working on site.","Siligap Boris","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54,3v site on grid Team Clement/691927185/ZTE working on site.","doro=
thy.djantio@ihstowers.com","427","08-08-2024 17:18:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0002802423","N=
YOM 2 IHS","","08-08-2024 17:17:06","08-08-2024 17:07:30","08-08-2024 19:48=
:39","No power issue on site U=3D54,9v site on grid Team Charles/6 72 48 90=
 41/ZTE working on site.","Fabrice Pouakam","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D54,9v site on grid Team Charles/6 72 48 90 41/ZTE working on site."=
,"dorothy.djantio@ihstowers.com","577","08-08-2024 17:17:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0002802413","Anguissa=
 New","","08-08-2024 17:14:10","08-08-2024 17:04:17","08-08-2024 18:09:56",=
"Cascaded Incident from TTO2605603","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive"," Grid ouytage No space to deploy a=
 mobil gen // Grid power return","system","593","08-08-2024 17:14:10","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0002802409","L=
abogenie","IHS_YND_568","08-08-2024 17:13:21","08-08-2024 17:04:17","08-08-=
2024 18:09:56"," Grid ouytage No space to deploy a mobil gen // Grid power =
return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e"," Grid ouytage No space to deploy a mobil gen // Grid power return","dor=
othy.djantio@ihstowers.com","545","08-08-2024 17:13:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0002802363","N=
kozoa","","08-08-2024 17:02:54","08-08-2024 16:57:45","08-08-2024 17:18:33"=
,"Grid fluctuation site went down because Gen failled to started due to Gri=
d bad voltage // He bypass the Grid and site on Gen manually started","Fabr=
ice Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controll=
er Faulty","Grid fluctuation site went down because Gen failled to started =
due to Grid bad voltage // He bypass the Grid and site on Gen manually star=
ted","dorothy.djantio@ihstowers.com","310","08-08-2024 17:02:54","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0002802301","T=
SINGA VILLAGE 2","","08-08-2024 16:49:09","08-08-2024 16:44:00","08-08-2024=
 17:59:42","No power site on gen with U=3D54.7v Steve pienta ( 696678898)fr=
om ZTE is working on site ","Delor Telezing","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power site on g=
en with U=3D54.7v Steve pienta ( 696678898)from ZTE is working on site ","d=
orothy.djantio@ihstowers.com","309","08-08-2024 16:49:09","Sagemcom CMR"
"Closed Complete","Site Down","T1570","IHS_YND_140","NOCINC0002802196","BIS=
CUITERIE","","08-08-2024 16:33:11","08-08-2024 16:19:52","08-08-2024 17:02:=
29","Grid outage.gen failed to start due to battery GE discharged causing  =
by main alternator faulty//gen manually started with external battery","Pau=
l BIBOUM","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery=
","Grid outage.gen failed to start due to battery GE discharged causing  by=
 main alternator faulty//gen manually started with external battery","ludiv=
ine.ngamaleu@ihstowers.com","11449","08-08-2024 16:33:11","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002802158","Eko=
unou","","08-08-2024 16:26:30","08-08-2024 16:21:26","08-08-2024 16:27:24",=
"Grid outage, site down because Gen due to poor backup before gen start//ge=
n started automatically","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site down because Ge=
n due to poor backup before gen start//gen started automatically","ludivine=
.ngamaleu@ihstowers.com","305","08-08-2024 16:26:30","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0002802148","NTU=
I TOWN","","08-08-2024 16:25:09","08-08-2024 16:20:05","08-08-2024 17:17:34=
","Site was on gen, Site went down because gen ran until fuel shortage//Ref=
ueling done","Parker Tchoup","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Site was on gen, Site went down because gen ran until fuel shortage//Re=
fueling done","ludivine.ngamaleu@ihstowers.com","305","08-08-2024 16:25:09"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002802135","Jou=
vence 2000","","08-08-2024 16:23:40","08-08-2024 16:19:35","08-08-2024 17:2=
5:19","Grid outage site went down because Gen failed to start due to poor b=
attery backup///Gen manually started","Delor Telezing","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site we=
nt down because Gen failed to start due to poor battery backup///Gen manual=
ly started","ludivine.ngamaleu@ihstowers.com","245","08-08-2024 16:23:40","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002802115","M=
arche Odza","","08-08-2024 16:22:31","08-08-2024 16:18:25","08-08-2024 18:5=
0:18","No power issue site on grid with U=3D54.5v Lionnel Steeve from Huawe=
i is informed//site up at 04:23 PM ","Albran Byorel","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue site on grid with U=3D54.5v Lionnel Steeve from Huawei is informed//si=
te up at 04:23 PM ","dorothy.djantio@ihstowers.com","247","08-08-2024 16:22=
:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_529","IHS_YND_316","NOCINC0002802099","A=
kak-Nkozoa-MTN-IHS","","08-08-2024 16:20:27","08-08-2024 14:47:21","08-08-2=
024 17:21:02","No power issue on site ubaie=3D 54v site down due to work of=
  675309535  gueulieu  swap zte","Fabrice Pouakam","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power iss=
ue on site ubaie=3D 54v site down due to work of  675309535  gueulieu  swap=
 zte","dorothy.djantio@ihstowers.com","5587","08-08-2024 16:20:27","Sagemco=
m CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002802000","Mok=
olo Yaounde","","08-08-2024 16:04:28","08-08-2024 16:03:24","08-08-2024 18:=
40:16","Grid outage.no space to deploy mobile gen//grid power ","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deploy mobile gen//grid power ","ludivine.ngamaleu@ihstowers.com",=
"65","08-08-2024 16:04:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0002801917","E=
bogo","","08-08-2024 15:53:49","08-08-2024 15:51:41","08-08-2024 17:20:34",=
"  No power issue on site U=3D54,1V site on grid Team YVAN (679375329  )/fr=
om ZTE  is working  on site ,","Siligap Boris","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","  No power issue=
 on site U=3D54,1V site on grid Team YVAN (679375329  )/from ZTE  is workin=
g  on site ,","dorothy.djantio@ihstowers.com","128","08-08-2024 15:53:49","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002801886","M=
imboman-Village","","08-08-2024 15:47:57","08-08-2024 14:41:42","08-08-2024=
 17:39:08","No power issue site on grid with U=3D54.6v Eloundou Bertrand fr=
om Huawei is informed","Mba Lazare Herve","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site o=
n grid with U=3D54.6v Eloundou Bertrand from Huawei is informed","dorothy.d=
jantio@ihstowers.com","3976","08-08-2024 15:47:57","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0002801815","Eli=
g Edzoa","","08-08-2024 15:32:40","08-08-2024 15:30:35","08-08-2024 15:32:1=
6","Grid outage, site went down before gen start due to poor battery backup=
 // Gen start automaticaly","Delor Telezing","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // Gen start automaticaly","ludi=
vine.ngamaleu@ihstowers.com","125","08-08-2024 15:32:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0002801791","Hotel de=
 Ville Yde","","08-08-2024 15:28:20","08-08-2024 14:37:04","08-08-2024 15:1=
3:41","Cascaded Incident from TTO2604890","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage No space to deploy=
 a mobil gen// Grid power return","system","3076","08-08-2024 15:28:20","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0002801783","N=
R-Bastos","IHS_YND_019","08-08-2024 15:27:23","08-08-2024 14:37:04","08-08-=
2024 15:13:41","Grid outage No space to deploy a mobil gen// Grid power ret=
urn(Site Swaped by ZTE)","","Grid Supply","Passive","Grid","National Grid -=
 Grid Outage Issue","Grid outage No space to deploy a mobil gen// Grid powe=
r return(Site Swaped by ZTE)","etienne.itondo@ihstowers.com","3020","08-08-=
2024 15:27:23","Sagemcom CMR"
"Closed Complete","Site Down","T0191","IHS_YND_337","NOCINC0002801537","Oko=
la","IHS_YND_530, IHS_YND_390","08-08-2024 14:49:13","08-08-2024 14:44:10",=
"08-08-2024 16:56:11","grid outage, site went down because Gen started and =
stopped due to ""high temp"" alarm //He added water and gen manually starte=
d","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG=
 - High Engine Temp - Coolant Level Issue","grid outage, site went down bec=
ause Gen started and stopped due to ""high temp"" alarm //He added water an=
d gen manually started","ludivine.ngamaleu@ihstowers.com","304","08-08-2024=
 14:49:13","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002801455","Bas=
tos Amb Coree","","08-08-2024 14:38:17","08-08-2024 14:32:13","08-08-2024 1=
5:14:38","Grid outage.no space to deploy mobile gen//grid power awaited",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage.no space to deploy mobile gen//grid power awaited","ludivine.ngamaleu=
@ihstowers.com","365","08-08-2024 14:38:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0002801413","S=
oa-Sofamac","","08-08-2024 14:30:08","08-08-2024 14:17:59","08-08-2024 15:2=
7:41","no power issue on site U=3D54,7V site on grid Team   Virgile(6515599=
85  )from ZTE  is working  on site ,","Siligap Boris","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power =
issue on site U=3D54,7V site on grid Team   Virgile(651559985  )from ZTE  i=
s working  on site ,","dorothy.djantio@ihstowers.com","730","08-08-2024 14:=
30:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0002801186","S=
OA TOWN","","08-08-2024 14:06:22","08-08-2024 13:57:13","08-08-2024 16:16:3=
7","No power issue on site U=3D51,2v site on grid Team Straumann/674608437/=
ZTE working on site.","Siligap Boris","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D51,2v site on grid Team Straumann/674608437/ZTE working on site.","alexa=
ndre.kamal@ihstowers.com","549","08-08-2024 14:06:22","Sagemcom CMR"
"Closed Complete","Site Down","T1548","IHS_YND_308","NOCINC0002800928","Mel=
en Ba'aba","","08-08-2024 13:13:58","08-08-2024 13:08:41","08-08-2024 17:17=
:47","No power issue on site U=3D54,3v site on grid Team franky /652369323 =
/  AFRO   working on site.","Siligap Boris","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D54,3v site on grid Team franky /652369323 /  AFRO   working on site=
.","denis.mballa@ihstowers.com","318","08-08-2024 13:13:58","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0002800924","Mfo=
u EPC","","08-08-2024 13:12:58","08-08-2024 13:03:42","08-08-2024 13:31:57"=
,"","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","site down due  to generator servicing, poor backup/=
/end of work","denis.mballa@ihstowers.com","808","08-08-2024 13:12:58","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0002800858","N=
kolbong","","08-08-2024 13:03:38","08-08-2024 12:56:31","08-08-2024 13:09:0=
3","No power issue on site U=3D52v site on grid Team Charles/695559948/ZTE =
working on site","Delor Telezing","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52=
v site on grid Team Charles/695559948/ZTE working on site","alexandre.kamal=
@ihstowers.com","427","08-08-2024 13:03:38","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002800851","Aka=
k-Nkozoa-MTN-IHS","","08-08-2024 13:01:20","08-08-2024 12:54:02","08-08-202=
4 13:40:34","","Fabrice Pouakam","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No power issue on site ubaie=
=3D 54v site down due to work of  675309535  gueulieu  swap zte","denis.mba=
lla@ihstowers.com","439","08-08-2024 13:01:20","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002800801","NKO=
MEKUI OCM","","08-08-2024 12:52:23","08-08-2024 12:43:10","08-08-2024 12:53=
:03","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // Gen start automat=
icaly","denis.mballa@ihstowers.com","553","08-08-2024 12:52:23","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0002800729","M=
ANGUIERS CHAPELLE","","08-08-2024 12:38:24","08-08-2024 12:19:21","08-08-20=
24 17:21:56","No power issue on site  Felix 682840951  is on site for Zte  =
swap","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","No power issue on site  Felix 682840951=
  is on site for Zte  swap","alexandre.kamal@ihstowers.com","1143","08-08-2=
024 12:38:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0002800563","M=
ini-Ferme","","08-08-2024 12:14:14","08-08-2024 11:48:10","08-08-2024 17:45=
:38"," Grid ouytage No space to deploy a mobil gen //Grid power return (sit=
e swapped by ZTE)","","Grid Supply","Passive","Grid","National Grid - Grid =
Outage Issue"," Grid ouytage No space to deploy a mobil gen //Grid power re=
turn (site swapped by ZTE)","alexandre.kamal@ihstowers.com","1565","08-08-2=
024 12:14:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0002800432","E=
kombitie","","08-08-2024 11:48:00","08-08-2024 11:34:56","08-08-2024 12:21:=
51","No power issue on site U=3D54,6v site on grid Team ADAM NJOYA/6 57 72 =
44 63/ZTE working on site","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site U=3D54,6v site on grid Team ADAM NJOYA/6 57 72 44 63/ZTE working on si=
te","alexandre.kamal@ihstowers.com","785","08-08-2024 11:48:00","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_430","IHS_YND_317","NOCINC0002800315","S=
oa-Sofamac","","08-08-2024 11:17:43","08-08-2024 11:02:38","08-08-2024 11:2=
9:30","No power issue on site U=3D53,4v site on grid Team Virgile/651559985=
/ZTE working on site","Siligap Boris","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53,4v site on grid Team Virgile/651559985/ZTE working on site","alexandr=
e.kamal@ihstowers.com","905","08-08-2024 11:17:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0002800235","E=
kounou","","08-08-2024 11:03:38","08-08-2024 10:17:21","08-08-2024 10:21:21=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen start automaticaly","Albran Byorel","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site went down bef=
ore gen start due to poor battery backup // Gen start automaticaly","alexan=
dre.kamal@ihstowers.com","2777","08-08-2024 11:03:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002800226","NKOLMEKO=
NG YDE","","08-08-2024 11:00:10","08-08-2024 09:52:51","08-08-2024 10:25:08=
","No power issue on site U=3D53,4v site on grid Team Junior/698689414/ZTE =
working on site","Fabrice Pouakam","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
3,4v site on grid Team Junior/698689414/ZTE working on site","system","4039=
","08-08-2024 11:00:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002800191","O=
lembe","","08-08-2024 10:53:16","08-08-2024 09:52:51","08-08-2024 10:25:08"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen start automaticaly","Fabrice Pouakam","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage, site went down be=
fore gen start due to poor battery backup // Gen start automaticaly","alexa=
ndre.kamal@ihstowers.com","3625","08-08-2024 10:53:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0002800140","A=
battoir","","08-08-2024 10:43:00","08-08-2024 09:46:55","08-08-2024 10:45:4=
4","No power issue on site U=3D51,2v site on grid Team Joseph/699454235/ZTE=
 working on site","Fabrice Pouakam","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D=
51,2v site on grid Team Joseph/699454235/ZTE working on site","alexandre.ka=
mal@ihstowers.com","3366","08-08-2024 10:43:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0002800136","O=
dza","","08-08-2024 10:41:49","08-08-2024 09:31:38","08-08-2024 09:32:01","=
","Albran Byorel","Customer Equipment Failure","Active","Active Equipment F=
ailure","BTS/TX Fault Alarm","No power issue on site ubaie=3D54v site Lione=
l is informed","alexandre.kamal@ihstowers.com","4212","08-08-2024 10:41:49"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002799944","Aka=
k-Nkozoa-MTN-IHS","","08-08-2024 10:22:13","08-08-2024 10:17:48","08-08-202=
4 10:37:48","grid outage;Main gen faulty//he connected MDG 20kva","Fabrice =
Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty",=
"grid outage;Main gen faulty//he connected MDG 20kva","denis.mballa@ihstowe=
rs.com","265","08-08-2024 10:22:13","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0002799912","An-=
Marche-Melen","","08-08-2024 10:14:38","08-08-2024 10:07:26","08-08-2024 17=
:47:19"," Grid ouytage No space to deploy a mobil gen //Grid power return (=
site swapped by ZTE)","","Grid Supply","Passive","Grid","National Grid - Gr=
id Outage Issue"," Grid ouytage No space to deploy a mobil gen //Grid power=
 return (site swapped by ZTE)","denis.mballa@ihstowers.com","3279","08-08-2=
024 10:14:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0002799840","Anguissa=
 New","","08-08-2024 09:59:20","08-08-2024 09:51:07","08-08-2024 10:18:13",=
"Cascaded Incident from TTO2602616","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,no space to deploy a m=
obil gen//grid return","system","493","08-08-2024 09:59:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0002799831","L=
abogenie","IHS_YND_568","08-08-2024 09:57:12","08-08-2024 09:51:07","08-08-=
2024 10:18:13","grid outage,no space to deploy a mobil gen//grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid o=
utage,no space to deploy a mobil gen//grid return","alexandre.kamal@ihstowe=
rs.com","365","08-08-2024 09:57:12","Sagemcom CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0002799805","Nko=
londom","","08-08-2024 09:49:56","08-08-2024 09:43:41","08-08-2024 10:25:08=
","grid outage;gen failed to start due to CB of battery backup disjuncted//=
he reamed the CB","Fabrice Pouakam","Equipment Repair","Passive","Control P=
anel","Faulty Circuit Breaker","grid outage;gen failed to start due to CB o=
f battery backup disjuncted//he reamed the CB","denis.mballa@ihstowers.com"=
,"376","08-08-2024 09:49:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002799734","M=
arche Odza","","08-08-2024 09:30:31","08-08-2024 09:23:28","08-08-2024 09:5=
7:22","No power issue on site U=3D54,5v site on grid Lionel steve of huwaei=
 is informed","Albran Byorel","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,5v =
site on grid Lionel steve of huwaei is informed","alexandre.kamal@ihstowers=
.com","424","08-08-2024 09:30:31","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002799399","Nsi=
meyong Shell","","08-08-2024 08:02:22","08-08-2024 07:59:10","08-08-2024 08=
:03:44","Grid outage, site down because Gen due to poor backup before gen s=
tart//Grid power return","MINKA NICOLAS","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site down because Ge=
n due to poor backup before gen start//Grid power return","denis.mballa@ihs=
towers.com","193","08-08-2024 08:02:22","Sagemcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0002799391","Mfo=
u EPC","","08-08-2024 07:59:48","08-08-2024 07:53:37","08-08-2024 08:40:26"=
,"grid outage,gen stopped with alarm high temp//ha added water in radiator"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High En=
gine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high t=
emp//ha added water in radiator","denis.mballa@ihstowers.com","684","08-08-=
2024 07:59:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0002798763","Melen Ba=
'aba","","08-08-2024 03:56:40","08-08-2024 03:52:24","08-08-2024 04:00:57",=
"Cascaded Incident from TTO2601390","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active: no power issue, site is on gr=
id with Ubaue=3D53V, A conf call had been made between our FME and Tx FME S=
ynphorien(650257151) From Huawei ","system","256","08-08-2024 03:56:40","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0002798765","TSINGA V=
ILLAGE 2","","08-08-2024 03:56:40","08-08-2024 03:52:24","08-08-2024 04:00:=
57","Cascaded Incident from TTO2601390","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active: no power issue, site is =
on grid with Ubaue=3D53V, A conf call had been made between our FME and Tx =
FME Synphorien(650257151) From Huawei ","system","256","08-08-2024 03:56:40=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_216","NOCINC0002798764","Eleveur"=
,"","08-08-2024 03:56:40","08-08-2024 03:52:24","08-08-2024 04:00:57","Casc=
aded Incident from TTO2601390","Siligap Boris","Cascade Outage","Active","C=
ascade Active","Cascade Active","Active: no power issue, site is on grid wi=
th Ubaue=3D53V, A conf call had been made between our FME and Tx FME Synpho=
rien(650257151) From Huawei ","system","256","08-08-2024 03:56:40","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0002798762","Nkolfoul=
ou 2","","08-08-2024 03:56:40","08-08-2024 03:52:24","08-08-2024 04:00:57",=
"Cascaded Incident from TTO2601390","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active: no power issue, site is on gr=
id with Ubaue=3D53V, A conf call had been made between our FME and Tx FME S=
ynphorien(650257151) From Huawei ","system","256","08-08-2024 03:56:40","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0002798758","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_216, IHS_YND_719","08-08-2024=
 03:55:30","08-08-2024 03:52:24","08-08-2024 05:00:58","Active: no power is=
sue, site is on grid with Ubaue=3D53V, A conf call had been made between ou=
r FME and Tx FME Synphorien(650257151) From Huawei ","Siligap Boris","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active: no power issue, site is on grid with Ubaue=3D53V, A conf call=
 had been made between our FME and Tx FME Synphorien(650257151) From Huawei=
 ","joelle.ekessi@ihstowers.com","186","08-08-2024 03:55:30","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002798374","Man=
guiers Dispensaire","","08-08-2024 01:30:23","08-08-2024 01:27:07","08-08-2=
024 03:54:23","grid outage , Gen failed to start because  grid return and G=
rid contactor did not excited// He excited grid conntactor","Fabrice Pouaka=
m","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","grid outag=
e , Gen failed to start because  grid return and Grid contactor did not exc=
ited// He excited grid conntactor","emmanuel.ghani@ihstowers.com","196","08=
-08-2024 01:30:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_275","NOCINC0002798359","Nkolbong=
","","08-08-2024 01:24:10","08-08-2024 01:13:54","08-08-2024 01:33:54","Cas=
caded Incident from TTO2600918","Delor Telezing","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue on site U=3D54,5v site on=
 grid Synphorien 691316854 of huawei is informed","system","616","08-08-202=
4 01:24:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0002798360","Olembe-T=
erminus","","08-08-2024 01:24:10","08-08-2024 01:13:54","08-08-2024 01:33:5=
4","Cascaded Incident from TTO2600918","Fabrice Pouakam","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site U=3D54,5v=
 site on grid Synphorien 691316854 of huawei is informed","system","616","0=
8-08-2024 01:24:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_137","NOCINC0002798362","Masque",=
"","08-08-2024 01:24:10","08-08-2024 01:13:54","08-08-2024 01:33:54","Casca=
ded Incident from TTO2600918","Fabrice Pouakam","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site U=3D54,5v site on =
grid Synphorien 691316854 of huawei is informed","system","616","08-08-2024=
 01:24:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_509","NOCINC0002798363","MANGUIER=
S CHAPELLE","","08-08-2024 01:24:10","08-08-2024 01:13:54","08-08-2024 01:3=
3:54","Cascaded Incident from TTO2600918","Fabrice Pouakam","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue on site U=3D54=
,5v site on grid Synphorien 691316854 of huawei is informed","system","616"=
,"08-08-2024 01:24:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0002798361","Nkozoa",=
"","08-08-2024 01:24:10","08-08-2024 01:13:54","08-08-2024 01:33:54","Casca=
ded Incident from TTO2600918","Fabrice Pouakam","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site U=3D54,5v site on =
grid Synphorien 691316854 of huawei is informed","system","616","08-08-2024=
 01:24:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0002798364","ARMP",""=
,"08-08-2024 01:24:10","08-08-2024 01:13:54","08-08-2024 01:33:54","Cascade=
d Incident from TTO2600918","","Cascade Outage","Active","Cascade Active","=
Cascade Active","No power issue on site U=3D54,5v site on grid Synphorien 6=
91316854 of huawei is informed","system","616","08-08-2024 01:24:10","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0002798358","E=
kombitie","IHS_YND_275, IHS_YND_300, IHS_YND_306, IHS_YND_137, IHS_YND_509,=
 IHS_YND_208","08-08-2024 01:22:05","08-08-2024 01:13:54","08-08-2024 01:33=
:54","No power issue on site U=3D54,5v site on grid Synphorien 691316854 of=
 huawei is informed","Fabrice Pouakam","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,5v site on grid Synphorien 691316854 of huawei is informed","joelle.e=
kessi@ihstowers.com","492","08-08-2024 01:22:05","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0002798121","Ole=
mbe","","08-08-2024 00:19:15","08-08-2024 00:16:48","08-08-2024 01:42:28","=
No power issue U=3D54.1 site on grid // Symphorien 691316854 of Huawei is i=
nformed.","Fabrice Pouakam","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue U=3D54.1 site on gri=
d // Symphorien 691316854 of Huawei is informed.","emmanuel.ghani@ihstowers=
.com","148","08-08-2024 00:19:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0002797507","B=
arriere","","07-08-2024 22:24:12","07-08-2024 21:14:06","07-08-2024 23:48:3=
5","Active: No power issue, site is on grid with Ubaie=3D52,3V, lionel tcha=
tchoua(694693436) from Huawei is informed, Notice that Disjunction in BTS O=
cm(swapping by ZTE )","Hyemafo Gildas","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issue, =
site is on grid with Ubaie=3D52,3V, lionel tchatchoua(694693436) from Huawe=
i is informed, Notice that Disjunction in BTS Ocm(swapping by ZTE )","adoni=
s.defokoua@ihstowers.com","4206","07-08-2024 22:24:12","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0002796993","Mvo=
g-Manga","","07-08-2024 21:57:40","07-08-2024 21:45:29","07-08-2024 22:46:5=
5","Site on Grid, Site went down because insufficiency of rectifiers due to=
 increase load(280A)// site Stabilized(Rectifiers to be add)","Albran Byore=
l","Equipment Repair","Passive","Rectifier","Rectifier Module","Site on Gri=
d, Site went down because insufficiency of rectifiers due to increase load(=
280A)// site Stabilized(Rectifiers to be add)","ange.kongo@ihstowers.com","=
732","07-08-2024 21:57:40","Sagemcom CMR"
"Closed Complete","Site Down","T0810","IHS_YND_277","NOCINC0002796558","Ngo=
ulmekong-Nord","","07-08-2024 21:37:01","07-08-2024 21:32:53","07-08-2024 2=
1:36:03","site went down because disfunction of rectifiers due to high temp=
erature //  He reamed Cb of rectifier which powers the fan, site on grid","=
Siligap Boris","Equipment Repair","Passive","Rectifier","Rectifier Module",=
"site went down because disfunction of rectifiers due to high temperature /=
/  He reamed Cb of rectifier which powers the fan, site on grid
","ange.kongo@ihstowers.com","249","07-08-2024 21:37:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0002796424","A=
battoir","","07-08-2024 21:23:16","07-08-2024 20:22:04","07-08-2024 23:45:5=
6","Active: no power issue, site is on grid with Ubaie=3D53V, JOSEPH (+2376=
90637972) from ZTE working on site","Fabrice Pouakam","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: n=
o power issue, site is on grid with Ubaie=3D53V, JOSEPH (+237690637972) fro=
m ZTE working on site","adonis.defokoua@ihstowers.com","3673","07-08-2024 2=
1:23:16","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0002796375","Nko=
mo stade","","07-08-2024 21:17:40","07-08-2024 21:15:29","07-08-2024 21:17:=
47","site went down because gen failed to start due to grid bad voltage// g=
rid stabilized","Mba Lazare Herve","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","site went down because gen failed to star=
t due to grid bad voltage// grid stabilized","ange.kongo@ihstowers.com","13=
2","07-08-2024 21:17:40","Sagemcom CMR"
"Closed Complete","Site Down","T1333","IHS_YND_174","NOCINC0002794761","Car=
refourt Nkomo","","07-08-2024 19:12:01","07-08-2024 19:09:01","07-08-2024 2=
0:51:49","site went down because Gen failed to start due to Grid Bad voltag=
e // he bypass the Grid and Gen manually started(Site Swaped by ZTE)","Mba =
Lazare Herve","Grid Supply","Passive","Grid","National Grid - Phase Control=
ler Faulty","site went down because Gen failed to start due to Grid Bad vol=
tage // he bypass the Grid and Gen manually started(Site Swaped by ZTE)","a=
nge.kongo@ihstowers.com","4270","07-08-2024 19:12:01","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002794610","Mim=
boman3","","07-08-2024 18:43:39","07-08-2024 18:39:14","07-08-2024 18:50:50=
","Grid outage, site went down before gen start due to poor battery backup =
// Grid power return","Mba Lazare Herve","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Battery Low","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid power return","ange.kongo@ih=
stowers.com","265","07-08-2024 18:43:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0002794524","B=
arriere","","07-08-2024 18:17:15","07-08-2024 17:42:09","07-08-2024 18:50:2=
8","site went down because Gen failed to start due to Grid Bad voltage // h=
e bypass the Grid and Gen manually started(Site Swaped by ZTE)","Hyemafo Gi=
ldas","Grid Supply","Passive","Grid","National Grid - Phase Controller Faul=
ty","site went down because Gen failed to start due to Grid Bad voltage // =
he bypass the Grid and Gen manually started(Site Swaped by ZTE)","adonis.de=
fokoua@ihstowers.com","2107","07-08-2024 18:17:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_272","IHS_YND_245","NOCINC0002794473","N=
gousso-Savana","","07-08-2024 18:02:55","07-08-2024 17:06:47","07-08-2024 2=
0:10:52","Active// No power issue, site is on grid with Ubaie=3D52,7 V   Th=
e Team Edgard Pem  // 691144397 from ZTE is working on site","Siligap Boris=
","Customer Equipment Failure","Active","Active Equipment Failure","Affecte=
d by 3rd Party Site","Active// No power issue, site is on grid with Ubaie=
=3D52,7 V   The Team Edgard Pem  // 691144397 from ZTE is working on site",=
"adonis.defokoua@ihstowers.com","3368","07-08-2024 18:02:55","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002794357","Nsi=
meyong Shell","","07-08-2024 17:40:45","07-08-2024 17:32:37","07-08-2024 19=
:53:38","Active// Active: No power issue, site is on Grid with Ubaie=3D53,4=
V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","MINKA NICOLAS=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","Active// Active: No power issue, site is on Grid with Ubaie=
=3D53,4V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","ange.k=
ongo@ihstowers.com","488","07-08-2024 17:40:45","Sagemcom CMR"
"Closed Complete","Site Down","T1549","IHS_YND_295","NOCINC0002794315","NGO=
NA","","07-08-2024 17:28:47","07-08-2024 17:24:36","07-08-2024 18:33:24","A=
ctive// No power issue, site is on grid with Ubaie=3D56,7 V   The Team Dika=
ngo// 650137179 from H_TELI is working on site","Mba Lazare Herve","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active// No power issue, site is on grid with Ubaie=3D56,7 V   The Team=
 Dikango// 650137179 from H_TELI is working on site","ange.kongo@ihstowers.=
com","252","07-08-2024 17:28:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0002794314","H=
-Progres","","07-08-2024 17:28:26","07-08-2024 16:31:18","07-08-2024 17:16:=
26"," Grid outage no space to deploy  // Grid power return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue"," Grid outage no spa=
ce to deploy  // Grid power return","adonis.defokoua@ihstowers.com","3428",=
"07-08-2024 17:28:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0002794300","C=
amp-Sic-Tsinga","","07-08-2024 17:26:17","07-08-2024 16:08:11","07-08-2024 =
17:12:53"," Grid outage no space to deploy  // Grid power return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue"," Grid outage =
no space to deploy  // Grid power return","adonis.defokoua@ihstowers.com","=
4687","07-08-2024 17:26:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002794267","M=
imboman-Village","","07-08-2024 17:16:10","07-08-2024 15:09:04","07-08-2024=
 19:15:07","no power issue  on site ,site on GRid  with U=3D53,2V Team Elou=
ndou // 693212405  from HUAWEI  is informed","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"no power issue  on site ,site on GRid  with U=3D53,2V Team Eloundou // 693=
212405  from HUAWEI  is informed","adonis.defokoua@ihstowers.com","7627","0=
7-08-2024 17:16:10","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002794115","Man=
guiers Dispensaire","","07-08-2024 16:54:52","07-08-2024 16:50:47","07-08-2=
024 17:54:52","site went Down because Gen failed to start due to the Grid c=
ontactor Faulty // He bypass The Grid contactor and  site on Grid","Fabrice=
 Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","sit=
e went Down because Gen failed to start due to the Grid contactor Faulty //=
 He bypass The Grid contactor and  site on Grid","ange.kongo@ihstowers.com"=
,"246","07-08-2024 16:54:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002794060","B=
ATA-Mokolo","","07-08-2024 16:39:59","07-08-2024 16:31:54","07-08-2024 17:1=
2:51","Grid outage.no space to deploy mobile gen//Grid return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no s=
pace to deploy mobile gen//Grid return","adonis.defokoua@ihstowers.com","48=
5","07-08-2024 16:39:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_795","NOCINC0002793961","Lada I Y=
de","","07-08-2024 16:18:20","07-08-2024 16:09:09","07-08-2024 16:56:21","s=
ite went down due to work(Herv=E9 Mba(657108482) from Sagemcom/ PM)//End of=
 Work","Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Pow=
er Cabinet - Battery Low","site went down due to work(Herv=E9 Mba(657108482=
) from Sagemcom/ PM)//End of Work","ange.kongo@ihstowers.com","551","07-08-=
2024 16:18:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0002793904","N=
omayos","","07-08-2024 16:02:18","07-08-2024 15:52:59","07-08-2024 16:32:11=
","site went down due to insufficient of rectifier on site// He reduced the=
 load","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down due to insufficient of rectifier on site// He reduced=
 the load","adonis.defokoua@ihstowers.com","559","07-08-2024 16:02:18","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_594","IHS_YND_308","NOCINC0002793881","M=
elen Ba'aba","","07-08-2024 15:53:26","07-08-2024 15:40:20","07-08-2024 19:=
25:09","Active// No power issue, site is on grid with Ubaie=3D54,3 V   The =
Team JULIETTE  //697284774  from ZTE is working on site","Siligap Boris","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active// No power issue, site is on grid with Ubaie=3D54,3 V   Th=
e Team JULIETTE  //697284774  from ZTE is working on site","adonis.defokoua=
@ihstowers.com","786","07-08-2024 15:53:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002793866","M=
essassi 2","","07-08-2024 15:49:17","07-08-2024 15:31:10","07-08-2024 19:15=
:39","Active// No power issue, site is on grid with Ubaie=3D51,3 V   The Te=
am Ebuka // 672741248  from ZTE is working on site","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue, site is on grid with Ubaie=3D51,3 V   The T=
eam Ebuka // 672741248  from ZTE is working on site","adonis.defokoua@ihsto=
wers.com","1088","07-08-2024 15:49:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_160","IHS_YND_523","NOCINC0002793770","E=
MANA BILICK CITY","","07-08-2024 15:25:29","07-08-2024 14:42:15","07-08-202=
4 17:35:57","Active// No power issue, site is on grid with Ubaie=3D56,7 V  =
 The Team FRANCOIS// 6 91 63 40 51 from ZTE is working on site","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active// No power issue, site is on grid with Ubaie=3D56=
,7 V   The Team FRANCOIS// 6 91 63 40 51 from ZTE is working on site","adon=
is.defokoua@ihstowers.com","2594","07-08-2024 15:25:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0002793762","Bondjock=
","","07-08-2024 15:22:06","07-08-2024 15:17:51","07-08-2024 15:20:27","Act=
ive, no power issue on site, U=3D55V on Grid The tx FME Etienne FOPA /65132=
0188/ From Huawei isworking on site","Fanda Brice","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no p=
ower issue on site, U=3D55V on Grid The tx FME Etienne FOPA /651320188/ Fro=
m Huawei isworking on site","ange.kongo@ihstowers.com","255","07-08-2024 15=
:22:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0002793657","E=
mana lycee 2","","07-08-2024 15:00:49","07-08-2024 14:06:41","07-08-2024 17=
:30:56","Active// No power issue, site is on grid with Ubaie=3D51,3 V   The=
 Team Raymond // 6 94 21 20 06 from ZTE is working on site","Fabrice Pouaka=
m","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","Active// No power issue, site is on grid with Ubaie=3D51,3 V=
   The Team Raymond // 6 94 21 20 06 from ZTE is working on site","adonis.d=
efokoua@ihstowers.com","3248","07-08-2024 15:00:49","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_719","NOCINC0002793094","TSINGA V=
ILLAGE 2","","07-08-2024 13:59:10","07-08-2024 13:50:59","07-08-2024 14:00:=
12","Cascaded Incident from TTO2595131","Delor Telezing","Cascade Outage","=
Active","Cascade Active","Cascade Active","No power issue on site ubaie=3D5=
4v site on grid   techniciens ZTE ""Djeugi Rodolphe"" sur site pour le swap=
 de orange 694434993","system","491","07-08-2024 13:59:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_308","NOCINC0002793093","Melen Ba=
'aba","","07-08-2024 13:59:10","07-08-2024 13:50:59","07-08-2024 14:00:12",=
"Cascaded Incident from TTO2595131","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site ubaie=3D54v si=
te on grid   techniciens ZTE ""Djeugi Rodolphe"" sur site pour le swap de o=
range 694434993","system","491","07-08-2024 13:59:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_278","NOCINC0002793092","Nkolfoul=
ou 2","","07-08-2024 13:59:10","07-08-2024 13:50:59","07-08-2024 14:00:12",=
"Cascaded Incident from TTO2595131","Siligap Boris","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue on site ubaie=3D54v si=
te on grid   techniciens ZTE ""Djeugi Rodolphe"" sur site pour le swap de o=
range 694434993","system","491","07-08-2024 13:59:10","Sagemcom CMR"
"Closed Complete","Site Down","T1748","IHS_YND_559","NOCINC0002793082","BAT=
A Mokolo OCM","","07-08-2024 13:57:17","07-08-2024 13:51:13","07-08-2024 14=
:55:16","Grid outage no space to deploy mobile gen//grid power awited","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age no space to deploy mobile gen//grid power awited","ludivine.ngamaleu@ih=
stowers.com","364","07-08-2024 13:57:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_214","IHS_YND_296","NOCINC0002793081","N=
kolfoulou","IHS_YND_278, IHS_YND_308, IHS_YND_719","07-08-2024 13:57:06","0=
7-08-2024 13:50:59","07-08-2024 14:00:12","","Siligap Boris","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site ubaie=3D54v site on grid   techniciens ZTE ""Djeugi Ro=
dolphe"" sur site pour le swap de orange 694434993","dorothy.djantio@ihstow=
ers.com","367","07-08-2024 13:57:06","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002792995","Eko=
unou","","07-08-2024 13:40:22","07-08-2024 13:35:17","07-08-2024 13:46:34",=
"Grid outage,site went down before DG start : Poor Batteries Backup // DG s=
tarted automatically.","Albran Byorel","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage,site went down before D=
G start : Poor Batteries Backup // DG started automatically.","ludivine.nga=
maleu@ihstowers.com","305","07-08-2024 13:40:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0002792847","N=
kolkoumou OCM","","07-08-2024 13:24:34","07-08-2024 13:20:26","07-08-2024 1=
3:30:20","","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site u=
baie=3D54v site on grid, Mouamadou is informed","dorothy.djantio@ihstowers.=
com","248","07-08-2024 13:24:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0002792813","Dagobert=
","","07-08-2024 13:18:21","07-08-2024 11:35:37","07-08-2024 11:40:56","Cas=
caded Incident from TTO2594807","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site ubaie=
=3D54v site on grid,Rm Alain(Huawei)is informed","system","6164","07-08-202=
4 13:18:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0002792814","Entree C=
ite Verte","","07-08-2024 13:18:21","07-08-2024 11:35:37","07-08-2024 11:40=
:56","Cascaded Incident from TTO2594807","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site ubaie=3D54v=
 site on grid,Rm Alain(Huawei)is informed","system","6164","07-08-2024 13:1=
8:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0002792809","Oyomaban=
g Ecole","","07-08-2024 13:18:20","07-08-2024 11:35:37","07-08-2024 11:40:5=
6","Cascaded Incident from TTO2594807","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Active","Cascade Active","Cascade Active","No power issue on site =
ubaie=3D54v site on grid,Rm Alain(Huawei)is informed","system","6163","07-0=
8-2024 13:18:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0002792812","Crf-Nkol=
bisson","","07-08-2024 13:18:20","07-08-2024 11:35:37","07-08-2024 11:40:56=
","Cascaded Incident from TTO2594807","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue on site u=
baie=3D54v site on grid,Rm Alain(Huawei)is informed","system","6163","07-08=
-2024 13:18:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0002792806","Nkolbi-B=
oss","","07-08-2024 13:18:20","07-08-2024 11:35:37","07-08-2024 11:40:56","=
Cascaded Incident from TTO2594807","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","No power issue on site ubai=
e=3D54v site on grid,Rm Alain(Huawei)is informed","system","6163","07-08-20=
24 13:18:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0002792807","Cite-Ver=
te","","07-08-2024 13:18:20","07-08-2024 11:35:37","07-08-2024 11:40:56","C=
ascaded Incident from TTO2594807","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","No power issue on site ubaie=3D54v site on grid,Rm A=
lain(Huawei)is informed","system","6163","07-08-2024 13:18:20","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0002792810","Meyong-M=
eyeme","","07-08-2024 13:18:20","07-08-2024 11:35:37","07-08-2024 11:40:56"=
,"Cascaded Incident from TTO2594807","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","No power issue on site ub=
aie=3D54v site on grid,Rm Alain(Huawei)is informed","system","6163","07-08-=
2024 13:18:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0002792811","Yona Hot=
el","","07-08-2024 13:18:20","07-08-2024 11:35:37","07-08-2024 11:40:56","C=
ascaded Incident from TTO2594807","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site ubaie=
=3D54v site on grid,Rm Alain(Huawei)is informed","system","6163","07-08-202=
4 13:18:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0002792808","Nkomkana=
","","07-08-2024 13:18:20","07-08-2024 11:35:37","07-08-2024 11:40:56","Cas=
caded Incident from TTO2594807","","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","No power issue on site ubaie=3D54v site on grid,Rm Ala=
in(Huawei)is informed","system","6163","07-08-2024 13:18:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0002792793","O=
yomabang OCM","IHS_YND_273, IHS_YND_202, IHS_YND_200, IHS_YND_686, IHS_YND_=
230, IHS_YND_271, IHS_YND_232, IHS_YND_286, IHS_YND_543","07-08-2024 13:15:=
46","07-08-2024 11:35:37","07-08-2024 11:40:56","No power issue on site uba=
ie=3D54v site on grid,Rm Alain(Huawei)is informed","TIENTCHEU NZETCHIEU GAE=
L","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue on site ubaie=3D54v site on grid,Rm Alain(Hua=
wei)is informed","dorothy.djantio@ihstowers.com","6010","07-08-2024 13:15:4=
6","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0002792738","Lobo OCM=
","","07-08-2024 13:11:30","07-08-2024 13:05:48","07-08-2024 13:14:15","Cas=
caded Incident from TTO2594740","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage,site went down =
before DG start : Poor Batteries backup //DG started automatically.","syste=
m","342","07-08-2024 13:11:30","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002792731","N=
KOMEKUI OCM","IHS_YND_341","07-08-2024 13:09:53","07-08-2024 13:05:48","07-=
08-2024 13:14:15","Grid outage,site went down before DG start : Poor Batter=
ies backup //DG started automatically.","TIENTCHEU NZETCHIEU GAEL","Equipme=
nt Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid ou=
tage,site went down before DG start : Poor Batteries backup //DG started au=
tomatically.","dorothy.djantio@ihstowers.com","245","07-08-2024 13:09:53","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0002792729","M=
anguier","","07-08-2024 13:08:37","07-08-2024 13:03:28","07-08-2024 13:13:3=
7","Grid outage, site down because Gen due to poor backup before gen start/=
/gen started automatically","Fabrice Pouakam","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site down becau=
se Gen due to poor backup before gen start//gen started automatically","dor=
othy.djantio@ihstowers.com","310","07-08-2024 13:08:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002792555","M=
asque","","07-08-2024 12:42:47","07-08-2024 12:34:36","07-08-2024 13:36:53"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V   The TX FME  Elo=
undou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V=
   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive=
 issue","dorothy.djantio@ihstowers.com","492","07-08-2024 12:42:47","Sagemc=
om CMR"
"Closed Complete","Site Down","T1941","IHS_YND_304","NOCINC0002792471","Nko=
londom","","07-08-2024 12:28:06","07-08-2024 12:27:01","07-08-2024 12:30:38=
","fme is on the way to site After Nkozoa MTN","Fabrice Pouakam","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site ubaie=3D54v  site on grid ","ludivine.ngamaleu@ihs=
towers.com","66","07-08-2024 12:28:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0002792465","E=
toudi 2","","07-08-2024 12:26:29","07-08-2024 12:12:21","07-08-2024 14:00:2=
3","Active//No power issue on site. Site on Grid with Ubaie=3D53.8V The TX =
 Armand Ngetsa(699949553) from Huawei is informed.","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site. Site on Grid with Ubaie=3D53.8V, The=
 TX  Armand Ngetsa(699949553) from Huawei is informed.
","dorothy.djantio@ihstowers.com","848","07-08-2024 12:26:29","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002792464","B=
iteng","","07-08-2024 12:26:08","07-08-2024 10:18:51","07-08-2024 10:20:25"=
,"No power issue on site ubaie=3D54v site on grid, CB tripped in OCM BTS, R=
M Alain(Huawei) is informed","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site ubaie=3D54v site on grid, CB tripped in OCM BTS, RM Alain(Huawei) i=
s informed","etienne.itondo@ihstowers.com","7637","07-08-2024 12:26:08","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2950","IHS_YND_129","NOCINC0002792029","Bas=
tos-BAT","","07-08-2024 11:18:35","07-08-2024 11:13:28","07-08-2024 13:43:4=
6","Active// No power issue, site is on grid with Ubaie=3D54,9  V The Tx Fm=
e, Eloundou(652586578) from Huawei is informed","Mboua Thierry","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active// No power issue, site is on grid with Ubaie=3D54,9  V The Tx Fme, =
Eloundou(652586578) from Huawei is informed","ludivine.ngamaleu@ihstowers.c=
om","307","07-08-2024 11:18:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0002791769","Messassi=
 okolo","","07-08-2024 10:27:50","07-08-2024 10:05:26","07-08-2024 10:10:47=
","Cascaded Incident from TTO2593576","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active// No power issue, site is =
on grid with Ubaie=3D52,9  V  The Team Tchio // 693678259 from ZTE is worki=
ng on site
","system","1344","07-08-2024 10:27:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0002791767","EMANA BI=
LICK CITY","","07-08-2024 10:27:50","07-08-2024 10:05:26","07-08-2024 10:10=
:47","Cascaded Incident from TTO2593576","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active// No power issue, site =
is on grid with Ubaie=3D52,9  V  The Team Tchio // 693678259 from ZTE is wo=
rking on site
","system","1344","07-08-2024 10:27:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0002791768","Emana Ly=
cee","","07-08-2024 10:27:50","07-08-2024 10:05:26","07-08-2024 10:10:47","=
Cascaded Incident from TTO2593576","Fabrice Pouakam","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active// No power issue, site is on =
grid with Ubaie=3D52,9  V  The Team Tchio // 693678259 from ZTE is working =
on site
","system","1344","07-08-2024 10:27:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0002791770","Emana ly=
cee 2","","07-08-2024 10:27:50","07-08-2024 10:05:26","07-08-2024 10:10:47"=
,"Cascaded Incident from TTO2593576","Fabrice Pouakam","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active// No power issue, site is o=
n grid with Ubaie=3D52,9  V  The Team Tchio // 693678259 from ZTE is workin=
g on site
","system","1344","07-08-2024 10:27:50","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002791716","Eko=
unou","","07-08-2024 10:19:02","07-08-2024 10:18:57","07-08-2024 10:26:40",=
"Grid outage, site went down before gen start due to poor battery backup //=
 Gen started  automatically","Albran Byorel","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
efore gen start due to poor battery backup // Gen started  automatically","=
ludivine.ngamaleu@ihstowers.com","6","07-08-2024 10:19:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0002791713","T=
ongolo OCM","","07-08-2024 10:18:37","07-08-2024 10:09:30","07-08-2024 11:1=
2:43","Active// No power issue, site is on grid  The Team  Baurice KENFACK =
//237693932700 from ZTE is working on site","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive// No power issue, site is on grid  The Team  Baurice KENFACK //2376939=
32700 from ZTE is working on site","dorothy.djantio@ihstowers.com","547","0=
7-08-2024 10:18:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0002791702","Mballa 4=
","","07-08-2024 10:15:50","07-08-2024 10:05:26","07-08-2024 10:10:47","Cas=
caded Incident from TTO2593576","Delor Telezing","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active// No power issue, site is on grid=
 with Ubaie=3D52,9  V  The Team Tchio // 693678259 from ZTE is working on s=
ite
","system","624","07-08-2024 10:15:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0002791697","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","07=
-08-2024 10:14:36","07-08-2024 10:05:26","07-08-2024 13:45:10","Active// No=
 power issue, site is on grid with Ubaie=3D52,9  V  The Team Tchio // 69367=
8259 from ZTE is working on site","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active// No=
 power issue, site is on grid with Ubaie=3D52,9  V  The Team Tchio // 69367=
8259 from ZTE is working on site
","dorothy.djantio@ihstowers.com","551","07-08-2024 10:14:36","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0002791539","N=
yom OCM","","07-08-2024 09:58:23","07-08-2024 09:55:15","07-08-2024 10:59:1=
1","Active// No power issue, site is on grid with Ubaie=3D52 V   The Team M=
elissa// 656024115 from ZTE is working on site","Fabrice Pouakam","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power issue, site is on grid with Ubaie=3D52 V   The Team Me=
lissa// 656024115 from ZTE is working on site","dorothy.djantio@ihstowers.c=
om","188","07-08-2024 09:58:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0002791497","Anguissa=
 New","","07-08-2024 09:51:30","07-08-2024 09:44:29","07-08-2024 10:36:08",=
"Cascaded Incident from TTO2593350","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage ,no space to deploy a =
mobile DG,waiting for Grid restored//Grid Restored.","system","421","07-08-=
2024 09:51:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0002791478","L=
abogenie","IHS_YND_568","07-08-2024 09:49:46","07-08-2024 09:44:29","07-08-=
2024 10:36:08","Grid outage ,no space to deploy a mobile DG,waiting for Gri=
d restored//Grid Restored.","","Grid Supply","Passive","Grid","National Gri=
d - Grid Outage Issue","Grid outage ,no space to deploy a mobile DG,waiting=
 for Grid restored//Grid Restored.","dorothy.djantio@ihstowers.com","317","=
07-08-2024 09:49:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002791298","Nkolondo=
m","","07-08-2024 09:23:30","07-08-2024 09:15:03","07-08-2024 09:18:55","Ca=
scaded Incident from TTO2593121","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active// No power issue, site is on gr=
id with Ubaie=3D54,5  V The Team Christian //698661479 from ZTE is working =
on site
 ","system","507","07-08-2024 09:23:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002791296","NKOLMEKO=
NG YDE","","07-08-2024 09:23:30","07-08-2024 09:15:03","07-08-2024 09:18:55=
","Cascaded Incident from TTO2593121","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active// No power issue, site is =
on grid with Ubaie=3D54,5  V The Team Christian //698661479 from ZTE is wor=
king on site
 ","system","507","07-08-2024 09:23:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002791297","Messassi=
","","07-08-2024 09:23:30","07-08-2024 09:15:03","07-08-2024 09:18:55","Cas=
caded Incident from TTO2593121","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active// No power issue, site is on gri=
d with Ubaie=3D54,5  V The Team Christian //698661479 from ZTE is working o=
n site
 ","system","507","07-08-2024 09:23:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002791271","O=
lembe","IHS_YND_681, IHS_YND_297, IHS_YND_304","07-08-2024 09:18:12","07-08=
-2024 09:15:03","07-08-2024 09:18:55","Active// No power issue, site is on =
grid with Ubaie=3D54,5  V The Team Christian //698661479 from ZTE is workin=
g on site  ","Fabrice Pouakam","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active// No power issue, site is=
 on grid with Ubaie=3D54,5  V The Team Christian //698661479 from ZTE is wo=
rking on site
 ","dorothy.djantio@ihstowers.com","189","07-08-2024 09:18:12","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0002791183","A=
battoir","","07-08-2024 08:59:03","07-08-2024 08:56:55","07-08-2024 10:59:5=
8","Active// No power issue, site is on grid with Ubaie=3D52 V The Team  Jo=
seph //+237690637972 from ZTE is working on site","Fabrice Pouakam","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power issue, site is on grid with Ubaie=3D52 V The Team  J=
oseph //+237690637972 from ZTE is working on site","dorothy.djantio@ihstowe=
rs.com","129","07-08-2024 08:59:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002791179","E=
TOUDI CHAPELLE","","07-08-2024 08:57:07","07-08-2024 08:53:56","07-08-2024 =
08:59:33","Active// No power issue, site is on grid with Ubaie=3D52 V The T=
eam  Ange// 620811823 from ZTE is working in site","Delor Telezing","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power issue, site is on grid with Ubaie=3D52 V The Team  A=
nge// 620811823 from ZTE is working in site","dorothy.djantio@ihstowers.com=
","192","07-08-2024 08:57:07","Sagemcom CMR"
"Closed Complete","Site Down","T1687","IHS_YND_509","NOCINC0002790917","MAN=
GUIERS CHAPELLE","","07-08-2024 07:43:40","07-08-2024 07:38:35","07-08-2024=
 08:55:46","Active// No power issue, site is on grid with Ubaie=3D52 V TX T=
X FME Synphorien //691316854// from Huawei is informed.Site up at 08:05 AM"=
,"Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active// No power issue, site is on grid wit=
h Ubaie=3D52 V TX TX FME Synphorien //691316854// from Huawei is informed.S=
ite up at 08:05 AM","ludivine.ngamaleu@ihstowers.com","306","07-08-2024 07:=
43:40","Sagemcom CMR"
"Closed Complete","Site Down","T1198","IHS_YND_791","NOCINC0002790637","Nom=
ayos montee Meche","","07-08-2024 06:29:50","07-08-2024 05:55:22","07-08-20=
24 07:23:31","site went down because gen failded to start due to battery Ge=
 faulty and charging alternator faulty // gen manually started with externa=
l battery","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Ge=
nerator Battery","site went down because gen failded to start due to batter=
y Ge faulty and charging alternator faulty // gen manually started with ext=
ernal battery","ludivine.ngamaleu@ihstowers.com","2069","07-08-2024 06:29:5=
0","Sagemcom CMR"
"Closed Complete","Site Down","T1614","IHS_YND_403","NOCINC0002790379","NTU=
I TOWN","","07-08-2024 04:20:40","07-08-2024 04:02:29","07-08-2024 05:44:38=
","grid outage , site went down because gen failed to start due to battery =
Gen  faulty// gen manually started with external battery","Parker Tchoup","=
Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","grid out=
age , site went down because gen failed to start due to battery Gen  faulty=
// gen manually started with external battery","kouoh.jean@ihstowers.com","=
1091","07-08-2024 04:20:40","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0002790195","Abo=
me","","07-08-2024 02:31:44","07-08-2024 01:49:08","07-08-2024 08:27:18","G=
rid outage site went down because Gen started and stopped due to GEN Overlo=
d (15Kva, Iload 300A)//Grid power return(Site Swaped by ZTE)","MINKA NICOLA=
S","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage s=
ite went down because Gen started and stopped due to GEN Overlod (15Kva, Il=
oad 300A)//Grid power return(Site Swaped by ZTE)","kouoh.jean@ihstowers.com=
","2988","07-08-2024 02:31:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_504","NOCINC0002790128","Elig Edz=
oa","","07-08-2024 02:04:21","07-08-2024 00:41:46","07-08-2024 02:38:44","C=
ascaded Incident from TTO2591571","Delor Telezing","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Team was on site on site to PWC ins=
tallation // End of work","system","4955","07-08-2024 02:04:21","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0002790120","Hotel de=
 Ville Yde","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:3=
8:44","Cascaded Incident from TTO2591571","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Team was on site on site to PW=
C installation // End of work","system","4954","07-08-2024 02:04:20","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0002790113","Bastos B=
ethesda","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:4=
4","Cascaded Incident from TTO2591571","Mboua Thierry","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Team was on site on site to PWC=
 installation // End of work","system","4954","07-08-2024 02:04:20","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_134","NOCINC0002790125","Vallee B=
astos MTN","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38=
:44","Cascaded Incident from TTO2591571","Mboua Thierry","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Team was on site on site to P=
WC installation // End of work","system","4954","07-08-2024 02:04:20","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_084","NOCINC0002790112","Briquett=
erie","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:44",=
"Cascaded Incident from TTO2591571","","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive","Team was on site on site to PWC installation //=
 End of work","system","4954","07-08-2024 02:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_027","NOCINC0002790126","Hopital =
Central","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:4=
4","Cascaded Incident from TTO2591571","","Cascade Outage","Passive","Casca=
de Passive","Cascade Passive","Team was on site on site to PWC installation=
 // End of work","system","4954","07-08-2024 02:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_731","NOCINC0002790119","UPAC LP"=
,"","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:44","Casc=
aded Incident from TTO2591571","","Cascade Outage","Passive","Cascade Passi=
ve","Cascade Passive","Team was on site on site to PWC installation // End =
of work","system","4954","07-08-2024 02:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_091","NOCINC0002790115","Jouvence=
 2000","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:44"=
,"Cascaded Incident from TTO2591571","Delor Telezing","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Team was on site on site to PWC =
installation // End of work","system","4954","07-08-2024 02:04:20","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002790121","Sapeur",=
"","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:44","Casca=
ded Incident from TTO2591571","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Team was on site on site to PWC installa=
tion // End of work","system","4954","07-08-2024 02:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_014","NOCINC0002790123","ELIg-Ess=
ono","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:44","=
Cascaded Incident from TTO2591571","Delor Telezing","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Team was on site on site to PWC in=
stallation // End of work","system","4954","07-08-2024 02:04:20","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_049","NOCINC0002790116","Etoa-Mek=
i","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:44","Ca=
scaded Incident from TTO2591571","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Team was on site on site to PWC inst=
allation // End of work","system","4954","07-08-2024 02:04:20","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0002790114","Mamch Bu=
ilding","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:44=
","Cascaded Incident from TTO2591571","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Team was on site on site to PWC =
installation // End of work","system","4954","07-08-2024 02:04:20","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_125","NOCINC0002790127","Charles-=
Atangana","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:=
44","Cascaded Incident from TTO2591571","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Team was on site on site to PWC installatio=
n // End of work","system","4954","07-08-2024 02:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_711","NOCINC0002790111","H-Franco=
 New","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:44",=
"Cascaded Incident from TTO2591571","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Team was on site on site to PWC i=
nstallation // End of work","system","4954","07-08-2024 02:04:20","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_086","NOCINC0002790117","POLYCLIN=
IQUE TSINGA","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:=
38:44","Cascaded Incident from TTO2591571","Mboua Thierry","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Team was on site on site to=
 PWC installation // End of work","system","4954","07-08-2024 02:04:20","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_016","NOCINC0002790124","Maetur",=
"","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:44","Casca=
ded Incident from TTO2591571","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Team was on site on site to PWC installa=
tion // End of work","system","4954","07-08-2024 02:04:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_024","NOCINC0002790122","Garbati =
building","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02:38:=
44","Cascaded Incident from TTO2591571","Delor Telezing","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Team was on site on site to P=
WC installation // End of work","system","4954","07-08-2024 02:04:20","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_064","NOCINC0002790118","HOPITAL =
DE LA CAISSE","","07-08-2024 02:04:20","07-08-2024 00:41:46","07-08-2024 02=
:38:44","Cascaded Incident from TTO2591571","Delor Telezing","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Team was on site on site =
to PWC installation // End of work","system","4954","07-08-2024 02:04:20","=
Sagemcom CMR"
"Closed Complete","Site Down","T0123","IHS_YND_013","NOCINC0002789930","Lab=
oratoire T.Bella","IHS_YND_711, IHS_YND_084, IHS_YND_563, IHS_YND_051, IHS_=
YND_091, IHS_YND_049, IHS_YND_086, IHS_YND_064, IHS_YND_731, IHS_YND_019, I=
HS_YND_029, IHS_YND_024, IHS_YND_014, IHS_YND_016, IHS_YND_134, IHS_YND_027=
, IHS_YND_125, IHS_YND_504","07-08-2024 00:43:59","07-08-2024 00:41:46","07=
-08-2024 02:38:44","site went down due to work( Bernard Atanga from Ihs , P=
laning work)","Paul BIBOUM","Installation Activity","Passive","Planned Acti=
vity","Installation Activity","Team was on site on site to PWC installation=
 // End of work","kouoh.jean@ihstowers.com","134","07-08-2024 00:43:59","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0002789823","ODZ=
A MINKAN EDIBI ASSI","","07-08-2024 00:08:46","07-08-2024 00:00:33","07-08-=
2024 01:11:21","fme is on site","Albran Byorel","Equipment Repair","Passive=
","ACDG Gen","ACDG - Generator Battery","Grid outage, site went down becaus=
e Gen failed to start due to the battery GE faulty// Gen  manually started =
with an external battery","kouoh.jean@ihstowers.com","493","07-08-2024 00:0=
8:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0002789742","A=
fanoya","","06-08-2024 23:40:48","06-08-2024 23:23:41","06-08-2024 23:33:29=
","Active: No power issue, site is on grid with Ubaie=3D54,4V, lionel tchat=
choua(694693436) from Huawei is informed ","Hyemafo Gildas","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue, site is on grid with Ubaie=3D54,4V, lionel tchatchoua(=
694693436) from Huawei is informed ","landry.etame@ihstowers.com","1027","0=
6-08-2024 23:40:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002789615","M=
imboman-Village","","06-08-2024 23:02:32","06-08-2024 20:55:29","06-08-2024=
 21:05:10","Active: No power issue, site is on Grid with U=3D54,2V ,  The T=
X FME Lionel adjep//655184876//   Huawei is informed ( Site swap by ZTE.)",=
"Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active: No power issue, site is on Grid with=
 U=3D54,2V ,  The TX FME Lionel adjep//655184876//   Huawei is informed ( S=
ite swap by ZTE.)","landry.etame@ihstowers.com","7624","06-08-2024 23:02:32=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0002789229","N=
omayos","","06-08-2024 21:29:55","06-08-2024 21:19:50","06-08-2024 21:47:22=
","site went down because 01/06 rectifier dysfonctionned // He reset the re=
ctifier","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier =
Module","site went down because 01/06 rectifier dysfonctionned // He reset =
the rectifier","joelle.ekessi@ihstowers.com","606","06-08-2024 21:29:55","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0002789081","O=
mnisport-Rail","","06-08-2024 20:56:56","06-08-2024 20:16:49","06-08-2024 2=
0:26:10","Active, No power issue, site on grid with U=3D56V , Armand Nguets=
a /691144412/ From Huawei is informed","Delor Telezing","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active,=
 No power issue, site on grid with U=3D56V , Armand Nguetsa /691144412/ Fro=
m Huawei is informed","joelle.ekessi@ihstowers.com","2407","06-08-2024 20:5=
6:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0002788459","N=
omayos","","06-08-2024 19:43:00","06-08-2024 19:35:55","06-08-2024 20:11:05=
","site went down because 01/06 rectifier dysfonctionned // He reset the re=
ctifier","Fanda Brice","Equipment Repair","Passive","Rectifier","Rectifier =
Module","site went down because 01/06 rectifier dysfonctionned // He reset =
the rectifier","joelle.ekessi@ihstowers.com","425","06-08-2024 19:43:00","S=
agemcom CMR"
"Closed Complete","Site Down","T1333","IHS_YND_174","NOCINC0002788446","Car=
refourt Nkomo","","06-08-2024 19:39:49","06-08-2024 19:29:46","06-08-2024 1=
9:45:20","Grid outage, site went down because gen failed to start due to po=
or backup // grid return","Mba Lazare Herve","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site went down b=
ecause gen failed to start due to poor backup // grid return","emmanuel.gha=
ni@ihstowers.com","2757","06-08-2024 19:39:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0002788314","B=
astos Ekoudou","","06-08-2024 18:59:36","06-08-2024 17:49:25","07-08-2024 0=
8:26:35","Active// No power issue, site is on grid with Ubaie=3D54,8 The Tx=
 ; Eloundou bertrand//693212405  is informed.. (Swapped by ZTE) ","Mboua Th=
ierry","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active// No power issue, site is on grid with Ubaie=3D54=
,8 The Tx ; Eloundou bertrand//693212405  is informed.. (Swapped by ZTE) ",=
"joelle.ekessi@ihstowers.com","4211","06-08-2024 18:59:36","Sagemcom CMR"
"Cancelled","Warning","CTR_621","IHS_YND_278","NOCINC0002788272","Nkolfoulo=
u 2","","06-08-2024 18:51:15","","","","Siligap Boris","","","","","","joel=
le.ekessi@ihstowers.com","247","06-08-2024 18:51:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002787924","M=
essassi 2","","06-08-2024 18:16:23","06-08-2024 18:12:19","06-08-2024 20:45=
:19","Active, no power issue, TEAM Ebuka /672741248 / From ZTE is working o=
n site ","Fabrice Pouakam","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active, no power issue, TEAM Ebuka /=
672741248 / From ZTE is working on site ","joelle.ekessi@ihstowers.com","24=
5","06-08-2024 18:16:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0002787741","E=
NAM","","06-08-2024 17:38:13","06-08-2024 17:22:07","06-08-2024 17:48:34","=
Grid outage.no space to deploy mobile gen//Grid return","","Grid Supply","P=
assive","Grid","National Grid - Grid Outage Issue","Grid outage.no space to=
 deploy mobile gen//Grid return","joelle.ekessi@ihstowers.com","967","06-08=
-2024 17:38:13","Sagemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0002787429","Mba=
nkolo petit paris","","06-08-2024 16:32:55","06-08-2024 16:28:28","06-08-20=
24 16:52:32","Grid outage.gen failed to start due to card GE dyfunctionning=
//we reset card GE and gen manually sstarted","Mboua Thierry","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Grid outage.gen failed t=
o start due to card GE dyfunctionning//we reset card GE and gen manually ss=
tarted","emmanuel.ghani@ihstowers.com","2373","06-08-2024 16:32:55","Sagemc=
om CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0002787422","AFE=
ME NORD","IHS_YND_808","06-08-2024 16:31:32","06-08-2024 16:26:28","06-08-2=
024 16:52:32","Grid outage.gen failed to start due to card GE dyfunctionnin=
g//we reset card GE and gen manually sstarted","TIENTCHEU NZETCHIEU GAEL","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage.=
gen failed to start due to card GE dyfunctionning//we reset card GE and gen=
 manually sstarted","emmanuel.ghani@ihstowers.com","1151","06-08-2024 16:31=
:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002787281","M=
imboman-Village","","06-08-2024 16:15:58","06-08-2024 15:55:51","06-08-2024=
 17:46:51","Active, no power issue, site on gen with U=3D54,5V Team kingsle=
y / 682435031(correction et d=E9m=E9ntelement ) ( Site swap by ZTE.) ","Mba=
 Lazare Herve","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active, no power issue, site on gen with U=3D54,=
5V Team kingsley / 682435031(correction et d=E9m=E9ntelement ) ( Site swap =
by ZTE.) ","joelle.ekessi@ihstowers.com","1207","06-08-2024 16:15:58","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0002787253","A=
bom","","06-08-2024 16:08:18","06-08-2024 15:45:10","06-08-2024 16:18:59","=
Grid outage, site went down Due to Gen overload(12.5KVA, 200 A) // Grid ret=
urn","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Overlo=
ad","Grid outage, site went down Due to Gen overload(12.5KVA, 200 A) // Gri=
d return","joelle.ekessi@ihstowers.com","1389","06-08-2024 16:08:18","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0002787210","E=
bogo","","06-08-2024 16:00:02","06-08-2024 15:54:58","06-08-2024 16:38:58",=
"Active //No power issue on site U=3D53,1V  site on Gen  The Tx Fme Symphor=
ien //650257157 is informed","Siligap Boris","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active //No power =
issue on site U=3D53,1V  site on Gen  The Tx Fme Symphorien //650257157 is =
informed","joelle.ekessi@ihstowers.com","304","06-08-2024 16:00:02","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002787042","Nkolondo=
m","","06-08-2024 15:24:00","06-08-2024 15:18:40","06-08-2024 15:20:53","Ca=
scaded Incident from TTO2588264","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active //No power issue on site U=3D53=
,1V  site on Gen  The Tx Fme Symphorien //650257157 is informed","system","=
320","06-08-2024 15:24:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002787041","Messassi=
","","06-08-2024 15:24:00","06-08-2024 15:18:40","06-08-2024 15:20:53","Cas=
caded Incident from TTO2588264","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active //No power issue on site U=3D53,=
1V  site on Gen  The Tx Fme Symphorien //650257157 is informed","system","3=
20","06-08-2024 15:24:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002787040","NKOLMEKO=
NG YDE","","06-08-2024 15:24:00","06-08-2024 15:18:40","06-08-2024 15:20:53=
","Cascaded Incident from TTO2588264","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active //No power issue on site U=
=3D53,1V  site on Gen  The Tx Fme Symphorien //650257157 is informed","syst=
em","320","06-08-2024 15:24:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002787031","O=
lembe","IHS_YND_681, IHS_YND_297, IHS_YND_304","06-08-2024 15:22:44","06-08=
-2024 15:18:40","06-08-2024 16:25:59","Active //No power issue on site U=3D=
53,1V  site on Gen  The Tx Fme Symphorien //650257157 is informed","Fabrice=
 Pouakam","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active //No power issue on site U=3D53,1V  site on Ge=
n  The Tx Fme Symphorien //650257157 is informed","joelle.ekessi@ihstowers.=
com","245","06-08-2024 15:22:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_356","IHS_YND_376","NOCINC0002787025","M=
amb","","06-08-2024 15:20:56","06-08-2024 15:17:51","06-08-2024 16:13:38","=
Site was on gen, Site went down because gen ran until fuel shortage//Refuel=
ing done","Kemeni Franklin","Fuel Outage","Passive","Diesel","Diesel Outage=
","Site was on gen, Site went down because gen ran until fuel shortage//Ref=
ueling done","joelle.ekessi@ihstowers.com","186","06-08-2024 15:20:56","Sag=
emcom CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0002786966","ENA=
M","","06-08-2024 15:16:26","06-08-2024 15:13:39","06-08-2024 16:00:24","Gr=
id outage.no space to deploy mobile gen//Grid return","","Grid Supply","Pas=
sive","Grid","National Grid - Grid Outage Issue","Grid outage.no space to d=
eploy mobile gen//Grid return","emmanuel.ghani@ihstowers.com","168","06-08-=
2024 15:16:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_542","IHS_YND_182","NOCINC0002786891","T=
iti Garage","","06-08-2024 14:57:52","06-08-2024 13:23:47","06-08-2024 16:3=
5:11","Active, No power issue, site on grid with U=3D54.6V Team Franck /691=
144395/ From ZTE is working on site","Delor Telezing","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, N=
o power issue, site on grid with U=3D54.6V Team Franck /691144395/ From ZTE=
 is working on site","joelle.ekessi@ihstowers.com","5645","06-08-2024 14:57=
:52","Sagemcom CMR"
"Closed Complete","Site Down","T1431","IHS_YND_561","NOCINC0002786876","FOU=
GEROLE","","06-08-2024 14:55:47","06-08-2024 14:54:16","06-08-2024 15:09:04=
","grid outage, site went down because Gen started and stopped due to ""hig=
h temp"" alarm //He added water and gen manually started ","Siligap Boris",=
"Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant =
Level Issue","grid outage, site went down because Gen started and stopped d=
ue to ""high temp"" alarm //He added water and gen manually started ","emma=
nuel.ghani@ihstowers.com","91","06-08-2024 14:55:47","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0002786816","Ako=
no","IHS_YND_687","06-08-2024 14:41:15","06-08-2024 14:37:10","06-08-2024 1=
7:12:26","Active, No power issue, site on gen with U=3D49V, Lionel /6946934=
36/ From huawei is informed","Fanda Brice","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active, No power iss=
ue, site on gen with U=3D49V, Lionel /694693436/ From huawei is informed","=
emmanuel.ghani@ihstowers.com","1351","06-08-2024 14:41:15","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0002786809","OLA=
MA","","06-08-2024 14:40:14","06-08-2024 14:37:10","06-08-2024 14:40:26",""=
,"Fanda Brice","Cascade Outage","Active","Cascade Active","Cascade Active",=
"Active, No power issue, site on gen with U=3D49V, Lionel /694693436/ From =
huawei is informed","emmanuel.ghani@ihstowers.com","185","06-08-2024 14:40:=
14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002786369","C=
arington","","06-08-2024 13:21:57","06-08-2024 12:46:46","06-08-2024 13:20:=
57","Active, no power issue, site on grid with U=3D54,5V, Team Douglas / 6 =
59149839/ From ZTE is working on site (SWAP)","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no pow=
er issue, site on grid with U=3D54,5V, Team Douglas / 6 59149839/ From ZTE =
is working on site (SWAP)","adonis.defokoua@ihstowers.com","2111","06-08-20=
24 13:21:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0002785704","A=
bome","","06-08-2024 11:41:39","06-08-2024 11:25:57","06-08-2024 12:40:41",=
"Grid outage, site went down Due to Gen overload(15KVA, 300) // Grid return=
","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Overload"=
,"Grid outage, site went down Due to Gen overload(15KVA, 300) // Grid retur=
n","adonis.defokoua@ihstowers.com","943","06-08-2024 11:41:39","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0002785681","N=
goulmekong-Nord","","06-08-2024 11:35:40","06-08-2024 11:15:11","06-08-2024=
 12:24:30","The site went down because the CB of PWC disjointed// he reamed=
 the CB","Siligap Boris","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Circuit Breaker Issue","The site went down because the CB of PW=
C disjointed// he reamed the CB","adonis.defokoua@ihstowers.com","1230","06=
-08-2024 11:35:40","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0002785630","UPA=
C LP","","06-08-2024 11:30:24","06-08-2024 11:25:05","06-08-2024 13:16:36",=
"Active, no power issue, site on grid with U=3D55,2V Tx FME mand Ngetsa (??=
699949553??)  From  Huawei is working on site","","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no po=
wer issue, site on grid with U=3D55,2V Tx FME mand Ngetsa (??699949553??)  =
From  Huawei is working on site","ange.kongo@ihstowers.com","319","06-08-20=
24 11:30:24","Sagemcom CMR"
"Closed Complete","Site Down","T2743","IHS_YND_721","NOCINC0002785621","VOI=
RIE MUNICIPALE YAOUNDE","","06-08-2024 11:28:53","06-08-2024 11:20:48","06-=
08-2024 13:52:33","site went down due to CB 80(A) disjonction on Dcbox // H=
e replaced the CB(80A) by Cb(125A)  (Site already swapped by ZTE )","Paul B=
IBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet - Circui=
t Breaker Issue","site went down due to CB 80(A) disjonction on Dcbox // He=
 replaced the CB(80A) by Cb(125A)  (Site already swapped by ZTE )","ange.ko=
ngo@ihstowers.com","486","06-08-2024 11:28:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002785077","Nkolondo=
m","","06-08-2024 09:58:20","06-08-2024 09:47:43","06-08-2024 09:54:00","Ca=
scaded Incident from TTO2585999","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active //No power issue on site U=3D53=
,1V  site on Gen  The Tx Fme Symphorien //650257157 is informed","system","=
637","06-08-2024 09:58:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0002785075","Olembe-T=
erminus","","06-08-2024 09:58:20","06-08-2024 09:47:43","06-08-2024 09:54:0=
0","Cascaded Incident from TTO2585999","Fabrice Pouakam","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active //No power issue on site =
U=3D53,1V  site on Gen  The Tx Fme Symphorien //650257157 is informed","sys=
tem","637","06-08-2024 09:58:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002785074","NKOLMEKO=
NG YDE","","06-08-2024 09:58:20","06-08-2024 09:47:43","06-08-2024 09:54:00=
","Cascaded Incident from TTO2585999","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active //No power issue on site U=
=3D53,1V  site on Gen  The Tx Fme Symphorien //650257157 is informed","syst=
em","637","06-08-2024 09:58:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002785076","Messassi=
","","06-08-2024 09:58:20","06-08-2024 09:47:43","06-08-2024 09:54:00","Cas=
caded Incident from TTO2585999","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active //No power issue on site U=3D53,=
1V  site on Gen  The Tx Fme Symphorien //650257157 is informed","system","6=
37","06-08-2024 09:58:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002785062","O=
lembe","IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_304","06-08-2024 09:=
55:08","06-08-2024 09:47:43","06-08-2024 12:34:00","Active //No power issue=
 on site U=3D53,1V  site on Gen  The Tx Fme Symphorien //650257157 is infor=
med","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","Active //No power issue on site U=3D53,1=
V  site on Gen  The Tx Fme Symphorien //650257157 is informed","adonis.defo=
koua@ihstowers.com","446","06-08-2024 09:55:08","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002784836","Nsi=
meyong Shell","","06-08-2024 09:34:32","06-08-2024 09:24:59","06-08-2024 09=
:34:59","Grid outage, site down because Gen due to poor backup before gen s=
tart//gen started automatically","MINKA NICOLAS","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site down be=
cause Gen due to poor backup before gen start//gen started automatically","=
ange.kongo@ihstowers.com","574","06-08-2024 09:34:32","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002784829","NKO=
MEKUI OCM","","06-08-2024 09:33:40","06-08-2024 09:24:35","06-08-2024 09:32=
:35","Grid outage, site down because Gen due to poor backup before gen star=
t//gen started automatically","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 down because Gen due to poor backup before gen start//gen started automati=
cally","ange.kongo@ihstowers.com","546","06-08-2024 09:33:40","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_323","NOCINC0002783542","SOA VILL=
AGE","","06-08-2024 04:00:40","06-08-2024 03:52:59","06-08-2024 04:26:58","=
Cascaded Incident from TTO2584268","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","site went down because gen failed t=
o start due to grid bad voltage// Gen manually started","system","461","06-=
08-2024 04:00:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_649","IHS_YND_320","NOCINC0002783532","S=
OA TOWN","IHS_YND_323","06-08-2024 03:58:17","06-08-2024 03:47:59","06-08-2=
024 04:26:58","site went down because gen failed to start due to grid bad v=
oltage// Gen manually started","Siligap Boris","Grid Supply","Passive","Gri=
d","National Grid - Phase Controller Faulty","site went down because gen fa=
iled to start due to grid bad voltage// Gen manually started","alexandre.ka=
mal@ihstowers.com","619","06-08-2024 03:58:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_518","IHS_YND_685","NOCINC0002783453","E=
mana lycee 2","","06-08-2024 03:30:48","06-08-2024 02:12:41","06-08-2024 02=
:53:41","site went down because gen failed to start due to grid bad voltage=
 and no RCP // he did a bridge on good phase","Fabrice Pouakam","Grid Suppl=
y","Passive","Grid","National Grid - Phase Controller Faulty","site went do=
wn because gen failed to start due to grid bad voltage and no RCP // he did=
 a bridge on good phase","alexandre.kamal@ihstowers.com","4687","06-08-2024=
 03:30:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0002783446","E=
vodoula OCM","","06-08-2024 03:28:40","06-08-2024 02:36:24","06-08-2024 03:=
20:54","Grid outage, site went down because gen failed to start // Gen manu=
ally started with external battery (investigation ongoing)","TIENTCHEU NZET=
CHIEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel",=
"Grid outage, site went down because gen failed to start // Gen manually st=
arted with external battery (investigation ongoing)","alexandre.kamal@ihsto=
wers.com","3137","06-08-2024 03:28:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_273","IHS_YND_214","NOCINC0002783061","N=
kolmesseng-II","","06-08-2024 00:08:33","05-08-2024 22:32:24","06-08-2024 0=
0:59:23","site went down due to disjunction Cb(125A) in PWC Causing by incr=
ease load in site// He reamed Cb(125A), site on grid (Swapped by ZTE)","Sil=
igap Boris","Equipment Repair","Passive","Control Panel","Power Cabinet - C=
ircuit Breaker Issue","site went down due to disjunction Cb(125A) in PWC Ca=
using by increase load in site// He reamed Cb(125A), site on grid (Swapped =
by ZTE)","alexandre.kamal@ihstowers.com","5769","06-08-2024 00:08:33","Sage=
mcom CMR"
"Closed Complete","Warning","T1739","IHS_YND_691","NOCINC0002782989","Mball=
a 2 REGIE","","05-08-2024 23:47:28","","","","Delor Telezing","Warning","Wa=
rning","POWER","Warning - AC Failure","Alarm cleared","ludovic.tchagna@ihst=
owers.com","2832","05-08-2024 23:47:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0002782780","N=
goulmekong-Nord","","05-08-2024 22:45:59","05-08-2024 22:15:55","05-08-2024=
 22:25:33","Active: No power issue, site is on grid with Ubaie=3D53V, Synph=
orien(691316854) from Huawei is informed(Swapped by ZTE)","Siligap Boris","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active: No power issue, site is on grid with Ubaie=3D53V, Synpho=
rien(691316854) from Huawei is informed","alexandre.kamal@ihstowers.com","1=
804","05-08-2024 22:45:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002782696","N=
koabang2","","05-08-2024 22:14:05","05-08-2024 20:29:57","05-08-2024 20:40:=
57","Active: No power issue, site is on grid with Ubaie=3D53V, Notice that =
we have dysjunction at OCM equipements, The TX FME Lionel adjep//655184876/=
/   Huawei is informed ( Site swap by ZTE.)","Mba Lazare Herve","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active: No power issue, site is on grid with Ubaie=3D53V, Notice that we h=
ave dysjunction at OCM equipements, The TX FME Lionel adjep//655184876//   =
Huawei is informed ( Site swap by ZTE.)","landry.etame@ihstowers.com","6249=
","05-08-2024 22:14:05","Sagemcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0002781690","Bar=
riere IHS","","05-08-2024 20:16:54","05-08-2024 20:11:40","05-08-2024 20:26=
:47","grid outage,gen failed to start due to grid bad voltage;no rcp//he by=
passed grid and started the gen","Hyemafo Gildas","Grid Supply","Passive","=
Grid","National Grid - Phase Controller Faulty","grid outage,gen failed to =
start due to grid bad voltage;no rcp//he bypassed grid and started the gen"=
,"kouoh.jean@ihstowers.com","315","05-08-2024 20:16:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002781588","N=
kolo II New","","05-08-2024 19:54:57","05-08-2024 18:44:46","05-08-2024 20:=
48:42","No power issue on site U=3D53v site on grid  Rm alain 691144423 of =
huawei is informed(site swapped by ZTE)","Mba Lazare Herve","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No =
power issue on site U=3D53v site on grid  Rm alain 691144423 of huawei is i=
nformed(site swapped by ZTE)","landry.etame@ihstowers.com","4211","05-08-20=
24 19:54:57","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002781419","Pha=
rmacie SION","","05-08-2024 19:05:17","05-08-2024 19:03:09","05-08-2024 19:=
13:09","Grid outage site went down before Gen start due to poor battery bac=
kup // Gen start automatically","Paul BIBOUM","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage site went down b=
efore Gen start due to poor battery backup // Gen start automatically","kou=
oh.jean@ihstowers.com","129","05-08-2024 19:05:17","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0002781251","UPA=
C LP","","05-08-2024 18:23:46","05-08-2024 18:17:37","05-08-2024 18:36:09",=
"No power issue on site U=3D55v site on grid Armand of huawei is informed",=
"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue on site U=3D55v site on grid Armand of huawei=
 is informed","kouoh.jean@ihstowers.com","369","05-08-2024 18:23:46","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_341","IHS_YND_269","NOCINC0002781229","M=
vog-Ebanda","","05-08-2024 18:15:26","05-08-2024 18:00:17","05-08-2024 18:2=
4:12","No power issue on site U=3D54,3v SITE ON GRID Team bassock Samuel /6=
93014014/Zte working on site","Siligap Boris","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on=
 site U=3D54,3v SITE ON GRID Team bassock Samuel /693014014/Zte working on =
site","landry.etame@ihstowers.com","910","05-08-2024 18:15:26","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0002781097","E=
ssomba","","05-08-2024 17:41:33","05-08-2024 16:08:26","05-08-2024 16:54:26=
","grid outage,gen stopped with alarm low oil pressure//he added oil and st=
arted the gen(site swapped by ZTE)","Mba Lazare Herve","Equipment Repair","=
Passive","ACDG Gen","ACDG - Low Oil Pressure","grid outage,gen stopped with=
 alarm low oil pressure//he added oil and started the gen(site swapped by Z=
TE)","landry.etame@ihstowers.com","5587","05-08-2024 17:41:33","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002780891","M=
imboman-Village","","05-08-2024 16:59:32","05-08-2024 15:32:25","05-08-2024=
 17:11:18","No power issue on site U=3D54v site on grid Team kingsley/68243=
5031/ZTE working on site","Mba Lazare Herve","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on =
site U=3D54v site on grid Team kingsley/682435031/ZTE working on site","lan=
dry.etame@ihstowers.com","5227","05-08-2024 16:59:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_327","IHS_YND_092","NOCINC0002780823","F=
ouda-New","","05-08-2024 16:39:55","05-08-2024 16:29:52","05-08-2024 16:51:=
17","No power issue on site U=3D53v site on grid Team DEFFO LANDRY/69502323=
5/ZTE working on site","Delor Telezing","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D53v site on grid Team DEFFO LANDRY/695023235/ZTE working on site","land=
ry.etame@ihstowers.com","604","05-08-2024 16:39:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_794","NOCINC0002780797","Nkoulou =
Carriere carrefourt","","05-08-2024 16:35:40","05-08-2024 15:39:53","05-08-=
2024 17:13:45","Cascaded Incident from TTO2580923","Mba Lazare Herve","Casc=
ade Outage","Passive","Cascade Passive","Cascade Passive","grid outage,gen =
failed to start due to battery Ge faultyand grid bad voltage//he did a brid=
ge on good phase(remplacement ongoing)","system","3347","05-08-2024 16:35:4=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002780786","Nkolondo=
m","","05-08-2024 16:32:20","05-08-2024 16:25:04","05-08-2024 16:47:06","Ca=
scaded Incident from TTO2581141","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D53v site on=
 grid Team Dominique Membila/694552106/ZTE working on site","system","436",=
"05-08-2024 16:32:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002780785","Messassi=
","","05-08-2024 16:32:20","05-08-2024 16:25:04","05-08-2024 16:47:06","Cas=
caded Incident from TTO2581141","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site U=3D53v site on =
grid Team Dominique Membila/694552106/ZTE working on site","system","436","=
05-08-2024 16:32:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002780778","O=
lembe","IHS_YND_297, IHS_YND_304","05-08-2024 16:31:15","05-08-2024 16:25:0=
4","05-08-2024 16:47:06","No power issue on site U=3D53v site on grid Team =
Dominique Membila/694552106/ZTE working on site","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site U=3D53v site on grid Team Dominique Membila/6945=
52106/ZTE working on site","landry.etame@ihstowers.com","371","05-08-2024 1=
6:31:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0002780742","N=
yom OCM","","05-08-2024 16:20:28","05-08-2024 16:16:23","05-08-2024 16:25:2=
3","grid outage,gen failed to start due to grid bad voltage//grid bypassed =
and gen started","Fabrice Pouakam","Grid Supply","Passive","Grid","National=
 Grid - Phase Controller Faulty","grid outage,gen failed to start due to gr=
id bad voltage//grid bypassed and gen started","landry.etame@ihstowers.com"=
,"245","05-08-2024 16:20:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0002780608","Nkolanga=
a","","05-08-2024 15:52:20","05-08-2024 15:39:53","05-08-2024 17:13:45","Ca=
scaded Incident from TTO2580923","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen failed to start du=
e to battery Ge faultyand grid bad voltage//he did a bridge on good phase(r=
emplacement ongoing)","system","747","05-08-2024 15:52:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0002780600","A=
bang","IHS_YND_794, IHS_YND_289","05-08-2024 15:48:57","05-08-2024 15:36:53=
","05-08-2024 17:13:45","grid outage,gen failed to start due to battery Ge =
faultyand grid bad voltage//he did a bridge on good phase(remplacement ongo=
ing)","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ge=
nerator Battery","grid outage,gen failed to start due to battery Ge faultya=
nd grid bad voltage//he did a bridge on good phase(remplacement ongoing)","=
landry.etame@ihstowers.com","725","05-08-2024 15:48:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0002780354","M=
EHANDAN","","05-08-2024 15:16:20","05-08-2024 13:52:12","05-08-2024 15:21:4=
7","site down because CB(100A) tripped in PWC because the load of the site =
increased//shunted  a CB 100A with a CB 50 A(site swapped by ZTE)","Albran =
Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet - Circu=
it Breaker Issue","site down because CB(100A) tripped in PWC because the lo=
ad of the site increased//shunted  a CB 100A with a CB 50 A(site swapped by=
 ZTE)","landry.etame@ihstowers.com","5049","05-08-2024 15:16:20","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0002780279","T=
ongolo OCM","","05-08-2024 15:06:25","05-08-2024 14:56:20","05-08-2024 15:0=
5:20","grid outage, site went down because gen start and stopped with alarm=
 ""Failed to start"" // He started gen manually started","Delor Telezing","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage,=
 site went down because gen start and stopped with alarm ""Failed to start"=
" // He started gen manually started","landry.etame@ihstowers.com","605","0=
5-08-2024 15:06:25","Sagemcom CMR"
"Closed Complete","Warning","T1059","IHS_YND_434","NOCINC0002780262","Donga=
","","05-08-2024 15:03:29","","","hybrid gen site//treshold automatically",=
"Parker Tchoup","Warning","Warning","POWER","Warning - Site on Battery","hy=
brid gen site//treshold automatically","marie.kwin@ihstowers.com","7","05-0=
8-2024 15:03:29","Sagemcom CMR"
"Closed Complete","Site Down","T0056","IHS_YND_189","NOCINC0002780259","Par=
adis Hotel","","05-08-2024 15:02:57","05-08-2024 14:33:35","05-08-2024 15:1=
5:01","grid outage,gen failed to start due to CB 32A  Ge disjuncted //he re=
amed it and started the gen","Siligap Boris","Equipment Repair","Passive","=
Control Panel","Faulty Circuit Breaker","grid outage,gen failed to start du=
e to CB 32A  Ge disjuncted //he reamed it and started the gen","kouoh.jean@=
ihstowers.com","1763","05-08-2024 15:02:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002780218","M=
essassi 2","","05-08-2024 14:54:45","05-08-2024 14:49:30","05-08-2024 16:03=
:09","Active, No power isuue, site on grid with U=3D54V, Team Ebuka/6727412=
48 / From ZTE IS WORKING ON SITE","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, No =
power isuue, site on grid with U=3D54V, Team Ebuka/672741248 / From ZTE IS =
WORKING ON SITE","landry.etame@ihstowers.com","316","05-08-2024 14:54:45","=
Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0002780142","N=
yanon","","05-08-2024 14:45:10","05-08-2024 14:00:39","05-08-2024 15:12:24"=
,"site went down due to controller Psc3 disfonctioning//he reset it anf sta=
rted the gen","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Control Panel","site went down due to controller Psc3 disfonc=
tioning//he reset it anf started the gen","landry.etame@ihstowers.com","267=
2","05-08-2024 14:45:10","Sagemcom CMR"
"Closed Complete","Warning","T1551","IHS_YND_316","NOCINC0002780009","Akak-=
Nkozoa-MTN-IHS","","05-08-2024 14:21:32","","","SITE ON BATTERY","Fabrice P=
ouakam","Warning","Warning","POWER","Warning - Current Low","SITE ON BATTER=
Y// Alarm cleared","kombi.samuel@ihstowers.com","3","05-08-2024 14:21:32","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_093","IHS_YND_188","NOCINC0002779863","H=
-Paradis","","05-08-2024 13:47:51","05-08-2024 13:42:40","05-08-2024 13:43:=
55","Active, No power isuue, site on grid with U=3D54V, Team Marius /698986=
611/ From ZTE IS WORKING ON SITE","","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active, No power isuue, si=
te on grid with U=3D54V, Team Marius /698986611/ From ZTE IS WORKING ON SIT=
E","joelle.ekessi@ihstowers.com","312","05-08-2024 13:47:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_090","IHS_YND_063","NOCINC0002779631","A=
v-Germaine","","05-08-2024 13:09:22","05-08-2024 12:57:15","05-08-2024 13:0=
0:35","Active, No power issue, site on grid with U=3D54.6V Team Clauvis /69=
8726782/ From ZTE is working on site","","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","Active, No power issue=
, site on grid with U=3D54.6V Team Clauvis /698726782/ From ZTE is working =
on site","joelle.ekessi@ihstowers.com","727","05-08-2024 13:09:22","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0002779566","M=
adison","","05-08-2024 13:00:59","05-08-2024 12:53:53","05-08-2024 13:00:39=
","","MFOUAGUEGUE MATHIEU","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","No power issue on site  ubaie 54v si=
te on grid Guy Laurent  Tel: 656177673 Zte is on site for swap","joelle.eke=
ssi@ihstowers.com","427","05-08-2024 13:00:59","Sagemcom CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0002779465","Nsa=
m escale LP","","05-08-2024 12:48:10","05-08-2024 12:46:05","05-08-2024 12:=
58:13","Grid outage.no space to deploy mobile gen//Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to deploy mobile gen//Grid return","emmanuel.ghani@ihstowers.com","12=
5","05-08-2024 12:48:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_202","IHS_YND_370","NOCINC0002779443","M=
om","","05-08-2024 12:42:54","05-08-2024 12:40:50","05-08-2024 14:04:48","g=
rid outage,gen failed to start due to grid bad voltage,no rcp//grid bypasse=
d and gen started","Fanda Brice","Grid Supply","Passive","Grid","National G=
rid - Phase Controller Faulty","grid outage,gen failed to start due to grid=
 bad voltage,no rcp//grid bypassed and gen started","joelle.ekessi@ihstower=
s.com","125","05-08-2024 12:42:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_473","IHS_YND_561","NOCINC0002779437","F=
OUGEROLE","","05-08-2024 12:41:28","05-08-2024 12:17:22","05-08-2024 12:20:=
04","","Siligap Boris","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","No power issue, site on grid with U=3D54=
.6V  Stephan Tel: 621627837 on site for swap ZTE","joelle.ekessi@ihstowers.=
com","1447","05-08-2024 12:41:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_105","NOCINC0002779426","Omnispor=
t 3","","05-08-2024 12:37:36","05-08-2024 11:54:30","05-08-2024 11:55:36","=
No power issue site on grid with U=3D54.6v  lord wise(681884512) from ZTE i=
s working on site ","Delor Telezing","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gri=
d with U=3D54.6v  lord wise(681884512) from ZTE is working on site ","joell=
e.ekessi@ihstowers.com","2586","05-08-2024 12:37:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_342","IHS_YND_190","NOCINC0002779411","N=
gousso-II","","05-08-2024 12:33:24","05-08-2024 12:20:20","05-08-2024 12:25=
:08","No power issue site on grid with U=3D53.1v Guy Laurent (656177673) fr=
om ZTE is working on site ","MFOUAGUEGUE MATHIEU","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issu=
e site on grid with U=3D53.1v Guy Laurent (656177673) from ZTE is working o=
n site ","joelle.ekessi@ihstowers.com","785","05-08-2024 12:33:24","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_237","NOCINC0002779387","Carrefou=
r Simbock","","05-08-2024 12:27:30","05-08-2024 12:25:10","05-08-2024 12:30=
:45","Cascaded Incident from TTO2579532","Hyemafo Gildas","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue site on grid wit=
h U=3D53.5v Mbah Hosiah from Huawei is informed //site up at 12:35 PM","sys=
tem","140","05-08-2024 12:27:30","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0002779381","Men=
dong NB","IHS_YND_237","05-08-2024 12:26:14","05-08-2024 12:25:10","05-08-2=
024 13:00:45","No power issue site on grid with U=3D53.5v Mbah Hosiah from =
Huawei is informed //site up at 12:35 PM","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on grid with U=3D53.5v Mbah Hosiah from Huawei is informed //site up at 1=
2:35 PM","emmanuel.ghani@ihstowers.com","65","05-08-2024 12:26:14","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_200","IHS_YND_129","NOCINC0002779227","B=
astos-BAT","","05-08-2024 11:50:16","05-08-2024 11:21:10","05-08-2024 11:30=
:46","Active, No power issue, site on grid with U=3D54.7V Team Clovis Tenda=
 /652749812/ From ZTE is working on site","Mboua Thierry","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e, No power issue, site on grid with U=3D54.7V Team Clovis Tenda /652749812=
/ From ZTE is working on site","joelle.ekessi@ihstowers.com","1746","05-08-=
2024 11:50:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_542","IHS_YND_182","NOCINC0002779214","T=
iti Garage","","05-08-2024 11:46:32","05-08-2024 11:40:27","05-08-2024 11:4=
5:32","Active, No power issue, site on grid with U=3D53.2V Team Franck /691=
144395/ From ZTE is working on site","Delor Telezing","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, N=
o power issue, site on grid with U=3D53.2V Team Franck /691144395/ From ZTE=
 is working on site","joelle.ekessi@ihstowers.com","365","05-08-2024 11:46:=
32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0002779204","C=
rf Cornier","","05-08-2024 11:41:41","05-08-2024 11:34:33","05-08-2024 14:0=
0:34","Active, No power issue, site on grid with U=3D54.6V Team TAKAM CRISL=
AIN /694434993/ From ZTE is working on site","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive, No power issue, site on grid with U=3D54.6V Team TAKAM CRISLAIN /6944=
34993/ From ZTE is working on site","joelle.ekessi@ihstowers.com","428","05=
-08-2024 11:41:41","Sagemcom CMR"
"Closed Complete","Site Down","T1437","IHS_YND_694","NOCINC0002779142","ETO=
UDI CHAPELLE","","05-08-2024 11:32:44","05-08-2024 11:26:37","05-08-2024 11=
:51:38","Grid outage .gen failed to start due to alarm ""underfrequency""//=
 we reset card GE and gen manually started ","Delor Telezing","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage .gen failed =
to start due to alarm ""underfrequency""// we reset card GE and gen manuall=
y started ","emmanuel.ghani@ihstowers.com","367","05-08-2024 11:32:44","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0002779137","O=
mnisport-Rail","","05-08-2024 11:32:26","05-08-2024 11:28:19","05-08-2024 1=
3:55:12","Active, No power issue, site on grid with U=3D54,5V Team SIMO Lar=
y /690884577/ From ZTE is working on site","Delor Telezing","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive, No power issue, site on grid with U=3D54,5V Team SIMO Lary /690884577/=
 From ZTE is working on site","joelle.ekessi@ihstowers.com","248","05-08-20=
24 11:32:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_379","IHS_YND_277","NOCINC0002779087","N=
goulmekong-Nord","","05-08-2024 11:28:20","05-08-2024 11:18:13","05-08-2024=
 11:40:32","Active, No power issue, site on grid with U=3D54.3V Team Nguets=
a /677382923/ From ZTE is working on site","Siligap Boris","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve, No power issue, site on grid with U=3D54.3V Team Nguetsa /677382923/ Fr=
om ZTE is working on site","joelle.ekessi@ihstowers.com","608","05-08-2024 =
11:28:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_351","IHS_YND_734","NOCINC0002779051","M=
imboman Chateau","","05-08-2024 11:20:19","05-08-2024 11:11:13","05-08-2024=
 11:30:24","Active, No power issue, site on grid with U=3D52,8V Team Franck=
 /691144395/ From ZTE is working on site","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, No power i=
ssue, site on grid with U=3D52,8V Team Franck /691144395/ From ZTE is worki=
ng on site","joelle.ekessi@ihstowers.com","546","05-08-2024 11:20:19","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_217","NOCINC0002778983","Abom",""=
,"05-08-2024 11:03:57","05-08-2024 10:57:09","05-08-2024 11:35:22","Active,=
 No power issue, site on grid with U=3D52,8V Team Franck /691144395/ From Z=
TE is working on site","Siligap Boris","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active, No power issue, =
site on grid with U=3D52,8V Team Franck /691144395/ From ZTE is working on =
site","joelle.ekessi@ihstowers.com","409","05-08-2024 11:03:57","Sagemcom C=
MR"
"Closed Complete","Site Down","T2583","IHS_YND_740","NOCINC0002778973","San=
ta Barbara Gottam","","05-08-2024 11:01:00","05-08-2024 10:59:55","05-08-20=
24 11:19:06","site went down because due to Gen contactor denegized due to =
 battery backup dysdunctionning//He rest the battery bacup and gen contacto=
r excited","Delor Telezing","Equipment Repair","Passive","Control Panel","A=
TS-AMF Issue","site went down because due to Gen contactor denegized due to=
  battery backup dysdunctionning//He rest the battery bacup and gen contact=
or excited","emmanuel.ghani@ihstowers.com","66","05-08-2024 11:01:00","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_203","NOCINC0002778963","Tongolo =
OCM","","05-08-2024 10:57:50","05-08-2024 10:53:49","05-08-2024 11:43:35","=
Active, No power issue, site on grid with U=3D52,8V Team Baurice KENFACK /6=
93932700/ From ZTE is working on site","Delor Telezing","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active,=
 No power issue, site on grid with U=3D52,8V Team Baurice KENFACK /69393270=
0/ From ZTE is working on site","joelle.ekessi@ihstowers.com","242","05-08-=
2024 10:57:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_484","IHS_YND_118","NOCINC0002778855","E=
SSOS OASIS 1111","","05-08-2024 10:34:47","05-08-2024 10:28:43","05-08-2024=
 13:29:35","Active//No  power issue on site ;site onGrid with Ubaie=3D 53.5=
 V The Team Arno  Adam//658958386 from ZTE is working on site","Siligap Bor=
is","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No  power issue on site ;site onGrid with Ubaie=3D =
53.5 V The Team Arno  Adam//658958386 from ZTE is working on site","joelle.=
ekessi@ihstowers.com","365","05-08-2024 10:34:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0002778852","S=
imbock OCM","","05-08-2024 10:33:15","05-08-2024 10:01:09","05-08-2024 10:3=
2:14","Grid fluctuation site went down because Gen failled to started due t=
o Grid bad voltage //  He make the bridge on good phases  (site swapped by =
zte)","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phas=
e Controller Faulty","Grid fluctuation site went down because Gen failled t=
o started due to Grid bad voltage //  He make the bridge on good phases  (s=
ite swapped by zte)","joelle.ekessi@ihstowers.com","1926","05-08-2024 10:33=
:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0002778652","K=
ondengui","","05-08-2024 10:11:00","05-08-2024 10:03:55","05-08-2024 13:38:=
55","Active: no power issue, site is on grid with Ubaie=3D54V, Eloundou (69=
3212405) from Huawei is informed","Albran Byorel","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue, site is on grid with Ubaie=3D54V, Eloundou (693212405) from Huaw=
ei is informed","joelle.ekessi@ihstowers.com","425","05-08-2024 10:11:00","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_207","IHS_YND_093","NOCINC0002778646","C=
hapelle-Essos","","05-08-2024 10:09:28","05-08-2024 10:02:24","05-08-2024 1=
0:03:50","No power issue site on grid with U=3D54.5v  Aristide OHANDJA (690=
994011) from ZTE is working on site ","Delor Telezing","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue site on grid with U=3D54.5v  Aristide OHANDJA (690994011) from ZTE i=
s working on site ","joelle.ekessi@ihstowers.com","424","05-08-2024 10:09:2=
8","Sagemcom CMR"
"Closed Complete","Site Down","CTR_068","IHS_YND_109","NOCINC0002778581","M=
obil-Essos","","05-08-2024 09:53:28","05-08-2024 09:48:23","05-08-2024 09:5=
9:17","No power issue site on grid with U=3D54.3v Elvis Nshom (6 95 37 89 7=
4) from ZTE is working on site ","Siligap Boris","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 site on grid with U=3D54.3v Elvis Nshom (6 95 37 89 74) from ZTE is workin=
g on site ","joelle.ekessi@ihstowers.com","305","05-08-2024 09:53:28","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0002778553","E=
lig Edzoa","","05-08-2024 09:50:43","05-08-2024 09:46:39","05-08-2024 09:55=
:31","No power issue site on grid with U=3D54.6v  Christophe Dongmo(6902660=
01 ) from ZTE is working on site ","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue site on grid with U=3D54.6v  Charly(698445384) from ZTE is working on s=
ite ","joelle.ekessi@ihstowers.com","245","05-08-2024 09:50:43","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002778546","C=
arington","","05-08-2024 09:47:46","05-08-2024 09:40:41","05-08-2024 09:55:=
06","No power issue site on grid with U=3D54.4v Douglas (6 59149839) from Z=
TE is working on site","","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=3D=
54.4v Douglas (6 59149839) from ZTE is working on site","joelle.ekessi@ihst=
owers.com","426","05-08-2024 09:47:46","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0002778490","Men=
dong NB","","05-08-2024 09:30:32","05-08-2024 09:23:27","05-08-2024 09:31:1=
7","Grid outage no space to deploy mobile gen  // Grid power return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e no space to deploy mobile gen  // Grid power return","emmanuel.ghani@ihst=
owers.com","425","05-08-2024 09:30:32","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002778444","Nko=
abang Ebolmedjock","","05-08-2024 09:18:13","05-08-2024 09:12:50","05-08-20=
24 12:42:16","Site was on gen, site went down because gen stopped due to di=
sjonction of GEN CB // he reamed the gen cb","Mba Lazare Herve","Equipment =
Repair","Passive","ACDG Gen","ACDG - Load Breaker","Site was on gen, site w=
ent down because gen stopped due to disjonction of GEN CB // he reamed the =
gen cb","emmanuel.ghani@ihstowers.com","324","05-08-2024 09:18:13","Sagemco=
m CMR"
"Cancelled","Warning","T2829","IHS_YND_526","NOCINC0002778395","Nkoabang2",=
"","05-08-2024 09:11:36","","","","Mba Lazare Herve","","","","","","joelle=
.ekessi@ihstowers.com","4","05-08-2024 09:11:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002777296","N=
koabang2","","05-08-2024 04:40:41","04-08-2024 20:33:25","04-08-2024 20:40:=
20","No power issue , site is on grid with Ubaie=3D53V,Notice that we have =
dysjunction at OCM equipements, The TX FME Lionel adjep//655184876//   Huaw=
ei is informed ( Site swap by ZTE.)","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue , site is on grid with Ubaie=3D53V,Notice that we have dysjunction =
at OCM equipements, The TX FME Lionel adjep//655184876//   Huawei is inform=
ed ( Site swap by ZTE.)","dorothy.djantio@ihstowers.com","29238","05-08-202=
4 04:40:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0002777265","M=
EHANDAN","","05-08-2024 04:23:16","04-08-2024 20:37:01","05-08-2024 06:13:5=
1","  site down because CB(100A) tripped in PWC because the load of the sit=
e increased//shunted  a CB 100A with a CB 50 A(site swapped by ZTE)","Albra=
n Byorel","Equipment Repair","Passive","Control Panel","Power Cabinet - Cir=
cuit Breaker Issue","  site down because CB(100A) tripped in PWC because th=
e load of the site increased//shunted  a CB 100A with a CB 50 A(site swappe=
d by ZTE)","dorothy.djantio@ihstowers.com","27975","05-08-2024 04:23:16","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0002777230","K=
ondengui","","05-08-2024 04:06:59","05-08-2024 03:49:40","05-08-2024 05:30:=
30","Active: no power issue, site is on grid with Ubaie=3D54V, Eloundou (69=
3212405) from Huawei is informed","Albran Byorel","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue, site is on grid with Ubaie=3D54V, Eloundou (693212405) from Huaw=
ei is informed","dorothy.djantio@ihstowers.com","1039","05-08-2024 04:06:59=
","Sagemcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0002777012","Bar=
riere IHS","","05-08-2024 02:17:50","05-08-2024 01:59:33","05-08-2024 02:22=
:33","grid outage, Site went down because gen ran until fuel shortage//Refu=
eling done","Hyemafo Gildas","Fuel Outage","Passive","Diesel","Diesel Outag=
e","grid outage, Site went down because gen ran until fuel shortage//Refuel=
ing done","denis.mballa@ihstowers.com","1099","05-08-2024 02:17:50","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0002774524","B=
itoto","","04-08-2024 19:34:43","04-08-2024 16:41:33","04-08-2024 16:55:53"=
,"No power issue on site U=3D54,2v site on gen lionel tchatchou of huawei i=
ds informed","Mba Lazare Herve","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,2=
v site on gen lionel tchatchou of huawei ids informed","kamga.virgile@ihsto=
wers.com","10392","04-08-2024 19:34:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0002774508","M=
ontee-Jouvence-II","","04-08-2024 19:30:15","04-08-2024 17:50:06","04-08-20=
24 19:54:34","site went down due to CB 125 A disjuncted in Pwc due to zte w=
orks //he reamed the CB(site swapped by ZTE)","Hyemafo Gildas","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","s=
ite went down due to CB 125 A disjuncted in Pwc due to zte works //he reame=
d the CB(site swapped by ZTE)","kamga.virgile@ihstowers.com","6010","04-08-=
2024 19:30:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0002774082","K=
ondengui","","04-08-2024 17:37:38","04-08-2024 17:11:29","04-08-2024 17:20:=
12","No power issue on site. Site on Grid with Ubaie=3D54.6V   The TX FME  =
Eloundou // 693212405// From  Huawei is informed. Repetitive issue","Albran=
 Byorel","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.6=
V   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitiv=
e issue","kamga.virgile@ihstowers.com","1571","04-08-2024 17:37:38","Sagemc=
om CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0002773773","N=
yanon","","04-08-2024 16:49:54","04-08-2024 16:34:43","04-08-2024 17:41:41"=
,"Site went down because controller of Huawei dysfuntioning// He reset card=
 GE and gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Hybrid","Hybrid Module","Site went down because controller of H=
uawei dysfuntioning// He reset card GE and gen manually started","kamga.vir=
gile@ihstowers.com","913","04-08-2024 16:49:54","Sagemcom CMR"
"Closed Complete","Site Down","T3148","IHS_YND_276","NOCINC0002773677","Eko=
mbitie","","04-08-2024 16:31:57","04-08-2024 16:16:59","04-08-2024 17:21:33=
","Grid outage site went down because Gen start and stop with alarm low oil=
 presure // He reset card GE and gen manually started","Fabrice Pouakam","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage s=
ite went down because Gen start and stop with alarm low oil presure // He r=
eset card GE and gen manually started","alexandre.kamal@ihstowers.com","153=
4","04-08-2024 16:31:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002773638","N=
kolo II New","","04-08-2024 16:24:16","04-08-2024 15:30:03","04-08-2024 15:=
31:42","Active, no power issue, site on grid with U=3D54,7V, Team Brice Zak=
aria Galadji/ 695023235/ From ZTE is working on site","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active, no power issue, site on grid with U=3D54,7V, Team Brice Z=
akaria Galadji/ 695023235/ From ZTE is working on site","kamga.virgile@ihst=
owers.com","3254","04-08-2024 16:24:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002773633","E=
-Police","","04-08-2024 16:22:41","04-08-2024 15:05:31","04-08-2024 17:24:3=
9","Grid outage no space to deploy a mobil gen //Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy a mobil gen //Grid return","kamga.virgile@ihstowers.com","463=
1","04-08-2024 16:22:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002773134","NKOLMEKO=
NG YDE","","04-08-2024 14:52:00","04-08-2024 14:25:54","04-08-2024 14:30:55=
","Cascaded Incident from TTO2572458","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active, no power issue, site on g=
rid with U=3D53,1V, Team Dominique Membila /694552106/ From ZTE is working =
on site.
","system","1566","04-08-2024 14:52:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002773135","Messassi=
","","04-08-2024 14:52:00","04-08-2024 14:25:54","04-08-2024 14:30:55","Cas=
caded Incident from TTO2572458","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active, no power issue, site on grid wi=
th U=3D53,1V, Team Dominique Membila /694552106/ From ZTE is working on sit=
e.
","system","1566","04-08-2024 14:52:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002773136","Nkolondo=
m","","04-08-2024 14:52:00","04-08-2024 14:25:54","04-08-2024 14:30:55","Ca=
scaded Incident from TTO2572458","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active, no power issue, site on grid w=
ith U=3D53,1V, Team Dominique Membila /694552106/ From ZTE is working on si=
te.
","system","1566","04-08-2024 14:52:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002773091","O=
lembe","IHS_YND_681, IHS_YND_297, IHS_YND_304","04-08-2024 14:44:30","04-08=
-2024 14:25:54","04-08-2024 14:30:55","Active, no power issue, site on grid=
 with U=3D53,1V, Team Dominique Membila /694552106/ From ZTE is working on =
site.","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active, no power issue, site on grid w=
ith U=3D53,1V, Team Dominique Membila /694552106/ From ZTE is working on si=
te.
","kamga.virgile@ihstowers.com","1117","04-08-2024 14:44:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0002772402","C=
amp-Sic-Tsinga","","04-08-2024 13:18:06","04-08-2024 12:01:59","04-08-2024 =
14:16:39","Grid outage,No space to deploy a mobil gen//grid return(site swa=
pped by ZTE)","","Grid Supply","Passive","Grid","National Grid - Grid Outag=
e Issue","Grid outage,No space to deploy a mobil gen//grid return(site swap=
ped by ZTE)","landry.etame@ihstowers.com","4568","04-08-2024 13:18:06","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0002772395","H=
-Progres","","04-08-2024 13:17:00","04-08-2024 11:55:46","04-08-2024 13:53:=
34","Grid outage,No space to deploy a mobil gen//Grid return(site swapped b=
y ZTE)","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid outage,No space to deploy a mobil gen//Grid return(site swapped by=
 ZTE)","landry.etame@ihstowers.com","4876","04-08-2024 13:17:00","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002772387","E=
-Police","","04-08-2024 13:15:43","04-08-2024 11:45:35","04-08-2024 13:40:3=
2","Grid outage,No space to deploy a mobil gen//grid return(site swapped by=
 ZTE)","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Grid outage,No space to deploy a mobil gen//grid return(site swapped by =
ZTE)","landry.etame@ihstowers.com","5409","04-08-2024 13:15:43","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002772144","B=
ATA-Mokolo","","04-08-2024 12:30:17","04-08-2024 12:19:09","04-08-2024 13:4=
8:16","Grid outage,No space to deploy a mobil gen//grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage,No =
space to deploy a mobil gen//grid return","landry.etame@ihstowers.com","669=
","04-08-2024 12:30:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002772012","NKOLMEKO=
NG YDE","","04-08-2024 11:53:10","04-08-2024 11:46:04","04-08-2024 12:21:52=
","Cascaded Incident from TTO2571278","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","No power issue on site U=3D53v si=
te on grid Team Dominique Membila/694552106/ZTE working on site","system","=
426","04-08-2024 11:53:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002772014","Nkolondo=
m","","04-08-2024 11:53:10","04-08-2024 11:46:04","04-08-2024 12:21:52","Ca=
scaded Incident from TTO2571278","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue on site U=3D53v site on=
 grid Team Dominique Membila/694552106/ZTE working on site","system","426",=
"04-08-2024 11:53:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002772013","Messassi=
","","04-08-2024 11:53:10","04-08-2024 11:46:04","04-08-2024 12:21:52","Cas=
caded Incident from TTO2571278","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue on site U=3D53v site on =
grid Team Dominique Membila/694552106/ZTE working on site","system","426","=
04-08-2024 11:53:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002772009","O=
lembe","IHS_YND_681, IHS_YND_297, IHS_YND_304","04-08-2024 11:52:09","04-08=
-2024 11:46:04","04-08-2024 12:21:52","No power issue on site U=3D53v site =
on grid Team Dominique Membila/694552106/ZTE working on site","Fabrice Poua=
kam","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","No power issue on site U=3D53v site on grid Team Dominique=
 Membila/694552106/ZTE working on site","landry.etame@ihstowers.com","367",=
"04-08-2024 11:52:09","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002771989","Nko=
abang Ebolmedjock","","04-08-2024 11:48:56","04-08-2024 11:41:45","04-08-20=
24 11:58:08","Site on gen, site went down due to gen Overload(10Kva, 110A) =
// site stabilized","Mba Lazare Herve","Equipment Repair","Passive","ACDG G=
en","ACDG - Overload","Site on gen, site went down due to gen Overload(10Kv=
a, 110A) // site stabilized","kouoh.jean@ihstowers.com","433","04-08-2024 1=
1:48:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002771988","E=
mana","","04-08-2024 11:48:42","04-08-2024 11:43:37","04-08-2024 20:19:29",=
"Grid outage/grid return","","Grid Supply","Passive","Grid","National Grid =
- Grid Outage Issue","Grid outage/grid return","landry.etame@ihstowers.com"=
,"308","04-08-2024 11:48:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0002771497","Kondengu=
i","","04-08-2024 10:14:20","04-08-2024 10:01:50","04-08-2024 10:35:54","Ca=
scaded Incident from TTO2570687","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage,No space to deploy a mobi=
l gen//grid return","system","750","04-08-2024 10:14:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0002771491","E=
mombo-Tchad","IHS_YND_114","04-08-2024 10:12:57","04-08-2024 10:01:50","04-=
08-2024 10:35:54","	Grid outage,No space to deploy a mobil gen//grid return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id outage,No space to deploy a mobil gen//grid return","landry.etame@ihstow=
ers.com","669","04-08-2024 10:12:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_161","IHS_YND_506","NOCINC0002771433","O=
mnisport-Rail","","04-08-2024 09:53:38","04-08-2024 09:39:28","04-08-2024 1=
1:15:41","No power issue on site U=3D54,5v site on grid Team  Guy-roger /69=
9920529/Omniacom  working on site","Delor Telezing","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site U=3D54,5v site on grid Team  Guy-roger /699920529/Omniacom  wor=
king on site","landry.etame@ihstowers.com","852","04-08-2024 09:53:38","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0002771417","V=
allee-Bastos OCM","","04-08-2024 09:50:27","04-08-2024 09:27:16","04-08-202=
4 10:48:51","grid outage//MDG 20KVA deployed(site swapped by zte)","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage/=
/MDG 20KVA deployed(site swapped by zte)","landry.etame@ihstowers.com","139=
4","04-08-2024 09:50:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_017","NOCINC0002771398","H-Depute=
s","","04-08-2024 09:44:01","04-08-2024 09:28:52","04-08-2024 10:04:12","Ca=
scaded Incident from TTO2570569","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Fuel shortage // Inclined fuel tank","system","909=
","04-08-2024 09:44:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002771184","Sapeur",=
"","04-08-2024 08:45:10","04-08-2024 08:25:23","04-08-2024 11:12:53","Casca=
ded Incident from TTO2570326","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","grid outage,No space to deploy a mobil g=
en//grid return(site swapped by ZTE)","system","1187","04-08-2024 08:45:10"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002771182","E=
-Police","IHS_YND_029","04-08-2024 08:44:27","04-08-2024 08:25:23","04-08-2=
024 11:12:53","grid outage,No space to deploy a mobil gen//grid return(site=
 swapped by ZTE)","","Grid Supply","Passive","Grid","National Grid - Grid O=
utage Issue","grid outage,No space to deploy a mobil gen//grid return(site =
swapped by ZTE)","landry.etame@ihstowers.com","1145","04-08-2024 08:44:27",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002771033","Mim=
boman3","","04-08-2024 08:01:12","04-08-2024 07:54:43","04-08-2024 08:08:43=
","Grid outage, site went down before gen start due to poor battery backup =
//Gerid return","Mba Lazare Herve","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before gen =
start due to poor battery backup //Gerid return","kouoh.jean@ihstowers.com"=
,"391","04-08-2024 08:01:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0002770824","B=
yemassi Carrefour","","04-08-2024 06:50:09","03-08-2024 19:42:47","04-08-20=
24 09:02:04","site went down due to CB 125 A disjuncted in Pwc//he reamed t=
he CB(site swapped by ZTE)","Paul BIBOUM","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","site went down due to =
CB 125 A disjuncted in Pwc//he reamed the CB(site swapped by ZTE)","landry.=
etame@ihstowers.com","40044","04-08-2024 06:50:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_473","NOCINC0002770443","Yoko MTN=
","","04-08-2024 03:42:01","04-08-2024 03:27:59","04-08-2024 03:37:15","Cas=
caded Incident from TTO2569486","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site , site on Grid wit=
h Ubaie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is informed,,=
Site up at 03:37 AM
","system","842","04-08-2024 03:42:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0002770439","Donga","=
","04-08-2024 03:42:00","04-08-2024 03:27:59","04-08-2024 03:37:15","Cascad=
ed Incident from TTO2569486","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site , site on Grid with U=
baie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is informed,,Sit=
e up at 03:37 AM
","system","841","04-08-2024 03:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002770436","Ngoum","=
","04-08-2024 03:42:00","04-08-2024 03:27:59","04-08-2024 03:37:15","Cascad=
ed Incident from TTO2569486","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No Power issue on site , site on Grid with U=
baie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is informed,,Sit=
e up at 03:37 AM
","system","841","04-08-2024 03:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002770434","Matsari"=
,"","04-08-2024 03:42:00","04-08-2024 03:27:59","04-08-2024 03:37:15","Casc=
aded Incident from TTO2569486","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site , site on Grid with=
 Ubaie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is informed,,S=
ite up at 03:37 AM
","system","841","04-08-2024 03:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002770437","Ngouetou=
","","04-08-2024 03:42:00","04-08-2024 03:27:59","04-08-2024 03:37:15","Cas=
caded Incident from TTO2569486","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No Power issue on site , site on Grid wit=
h Ubaie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is informed,,=
Site up at 03:37 AM
","system","841","04-08-2024 03:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_433","NOCINC0002770432","Nguila",=
"","04-08-2024 03:42:00","04-08-2024 03:27:59","04-08-2024 03:37:15","Casca=
ded Incident from TTO2569486","Parker Tchoup","Cascade Outage","Active","Ca=
scade Active","Cascade Active","No Power issue on site , site on Grid with =
Ubaie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is informed,,Si=
te up at 03:37 AM
","system","841","04-08-2024 03:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0002770442","Saa","",=
"04-08-2024 03:42:00","04-08-2024 03:27:59","04-08-2024 03:37:15","Cascaded=
 Incident from TTO2569486","Parker Tchoup","Cascade Outage","Active","Casca=
de Active","Cascade Active","No Power issue on site , site on Grid with Uba=
ie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is informed,,Site =
up at 03:37 AM
","system","841","04-08-2024 03:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_690","NOCINC0002770438","Ntui adm=
inistration","","04-08-2024 03:42:00","04-08-2024 03:27:59","04-08-2024 03:=
37:15","Cascaded Incident from TTO2569486","Parker Tchoup","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No Power issue on site , site =
on Grid with Ubaie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is=
 informed,,Site up at 03:37 AM
","system","841","04-08-2024 03:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002770433","MBIMBIM"=
,"","04-08-2024 03:42:00","04-08-2024 03:27:59","04-08-2024 03:37:15","Casc=
aded Incident from TTO2569486","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No Power issue on site , site on Grid with=
 Ubaie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is informed,,S=
ite up at 03:37 AM
","system","841","04-08-2024 03:42:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_403","NOCINC0002770440","NTUI TOW=
N","","04-08-2024 03:42:00","04-08-2024 03:27:59","04-08-2024 03:37:15","Ca=
scaded Incident from TTO2569486","Parker Tchoup","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No Power issue on site , site on Grid wi=
th Ubaie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is informed,=
,Site up at 03:37 AM
","system","841","04-08-2024 03:42:00","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0002770427","SAA=
 2","IHS_YND_433, IHS_YND_456, IHS_YND_460, IHS_YND_424, IHS_YND_392, IHS_Y=
ND_475, IHS_YND_454, IHS_YND_690, IHS_YND_434, IHS_YND_403, IHS_DLA_210, IH=
S_YND_405, IHS_YND_473, IHS_YND_782","04-08-2024 03:36:07","04-08-2024 03:2=
7:59","04-08-2024 04:00:18","No Power issue on site , site on Grid with Uba=
ie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is informed,,Site =
up at 03:37 AM","Parker Tchoup","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No Power issue on site , site o=
n Grid with Ubaie=3D54.1V The Tx FME Gregoire //652070658 from   Huawei is =
informed,,Site up at 03:37 AM
","ange.kongo@ihstowers.com","490","04-08-2024 03:36:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_405","IHS_YND_424","NOCINC0002770420","O=
ssombe","","04-08-2024 03:31:56","04-08-2024 03:25:43","04-08-2024 03:37:15=
","ACTIVE// Tx issue: Ubaie=3D50 V site on Battery( Hybrid Gen site Start T=
hreshold=3D48,5V)The Tx Fme Gregoire( 652070658)from Huawei is informed,Sit=
e up at 03:33 AM","Parker Tchoup","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","ACTIVE// Tx issue: Ubaie=3D50=
 V site on Battery( Hybrid Gen site Start Threshold=3D48,5V)The Tx Fme Greg=
oire( 652070658)from Huawei is informed,Site up at 03:33 AM","adonis.defoko=
ua@ihstowers.com","375","04-08-2024 03:31:56","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002770279","Messassi=
","","04-08-2024 02:25:20","04-08-2024 02:18:06","04-08-2024 02:21:02","Cas=
caded Incident from TTO2569276","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active //No power issue on site U=3D54 =
 V  site on Grid  The Tx Fme Symphorien //650257157 is informed,Site up at =
02:21 AM","system","434","04-08-2024 02:25:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002770280","Nkolondo=
m","","04-08-2024 02:25:20","04-08-2024 02:18:06","04-08-2024 02:21:02","Ca=
scaded Incident from TTO2569276","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active //No power issue on site U=3D54=
  V  site on Grid  The Tx Fme Symphorien //650257157 is informed,Site up at=
 02:21 AM","system","434","04-08-2024 02:25:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002770278","NKOLMEKO=
NG YDE","","04-08-2024 02:25:20","04-08-2024 02:18:06","04-08-2024 02:21:02=
","Cascaded Incident from TTO2569276","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active //No power issue on site U=
=3D54  V  site on Grid  The Tx Fme Symphorien //650257157 is informed,Site =
up at 02:21 AM","system","434","04-08-2024 02:25:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002770253","O=
lembe","IHS_YND_681, IHS_YND_297, IHS_YND_304","04-08-2024 02:20:29","04-08=
-2024 02:18:06","04-08-2024 02:21:02","Active //No power issue on site U=3D=
54  V  site on Grid  The Tx Fme Symphorien //650257157 is informed,Site up =
at 02:21 AM","Fabrice Pouakam","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active //No power issue on site =
U=3D54  V  site on Grid  The Tx Fme Symphorien //650257157 is informed,Site=
 up at 02:21 AM","adonis.defokoua@ihstowers.com","146","04-08-2024 02:20:29=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002769536","O=
lembe-Terminus","","03-08-2024 22:02:36","03-08-2024 21:58:28","03-08-2024 =
23:03:31","Site on gen due to grid outage, site went down due to Gen contac=
tor  disfunction // He excited the Contactor and started Gen manualy","Fabr=
ice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Load Contactor=
","Site on gen due to grid outage, site went down due to Gen contactor  dis=
function // He excited the Contactor and started Gen manualy","dorothy.djan=
tio@ihstowers.com","250","03-08-2024 22:02:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002769476","M=
asque","","03-08-2024 21:51:27","03-08-2024 21:47:18","03-08-2024 23:58:08"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V   The TX FME  Elo=
undou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V=
   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive=
 issue","dorothy.djantio@ihstowers.com","251","03-08-2024 21:51:27","Sagemc=
om CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0002769426","Nko=
mo stade","","03-08-2024 21:40:04","03-08-2024 21:36:59","03-08-2024 21:54:=
09","site went down due to 1/3 rectifier disfunctionning//he reset the rect=
ifier","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rectifi=
er Module","site went down due to 1/3 rectifier disfunctionning//he reset t=
he rectifier","ludivine.ngamaleu@ihstowers.com","187","03-08-2024 21:40:04"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0002768127","Mes=
sassi Ngonlonk","","03-08-2024 20:26:12","03-08-2024 20:17:07","03-08-2024 =
22:30:52","Site on Grid,  Site went down because Grid dit not supply power/=
/we bypass grid and gen manually started for restore the site (investigatio=
n ongoing)","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","Site on Grid,  Site went down because Grid dit not suppl=
y power//we bypass grid and gen manually started for restore the site (inve=
stigation ongoing)","ludivine.ngamaleu@ihstowers.com","547","03-08-2024 20:=
26:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002767909","O=
lembe-Terminus","","03-08-2024 19:39:37","03-08-2024 19:33:30","03-08-2024 =
20:58:47","Site on gen due to grid outage, site went down due to Gen contac=
tor  disfunction // He excited the Contactor and started Gen manualy","Fabr=
ice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","=
Site on gen due to grid outage, site went down due to Gen contactor  disfun=
ction // He excited the Contactor and started Gen manualy","dorothy.djantio=
@ihstowers.com","368","03-08-2024 19:39:37","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0002767790","Lob=
o 2","","03-08-2024 18:59:25","03-08-2024 18:54:19","03-08-2024 21:14:39","=
site went down because gen failed to start due to alarm overvoltage//he res=
et the card and started it","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","=
Passive","ACDG Gen","ACDG - Over Voltage","site went down because gen faile=
d to start due to alarm overvoltage//he reset the card and started it","lud=
ivine.ngamaleu@ihstowers.com","307","03-08-2024 18:59:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002767737","O=
lembe","IHS_YND_681, IHS_YND_297, IHS_YND_304","03-08-2024 18:48:31","03-08=
-2024 14:38:21","03-08-2024 18:54:49","Tx Issue : site on grid ,ubaie:54,4V=
; Dominique Membila    6 694552106 ZTE is working on site, (Pre installatio=
n swap)","Fabrice Pouakam","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Tx Issue : site on grid ,ubaie:54,4V=
; Dominique Membila    6 694552106 ZTE is working on site, (Pre installatio=
n swap)","etienne.itondo@ihstowers.com","15012","03-08-2024 18:48:31","Sage=
mcom CMR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0002767573","Mfo=
u EPC","","03-08-2024 18:00:57","03-08-2024 17:54:50","03-08-2024 18:27:41"=
,"No power issue on site U=3D52v site on gen lionel tchatchou of huawei ids=
 informed","Mba Lazare Herve","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D52v si=
te on gen lionel tchatchou of huawei ids informed","ludivine.ngamaleu@ihsto=
wers.com","369","03-08-2024 18:00:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0002767520","A=
bome","","03-08-2024 17:47:37","03-08-2024 15:56:00","03-08-2024 16:12:15",=
"Grid outage site went down because Gen started and stopped due to Gen Over=
load (1power solved since 16:12 but the site remain down at ocm fme TX Lion=
el Steve of huawei is informed(site swapped by ZTE)","MINKA NICOLAS","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went =
down because Gen started and stopped due to Gen Overload (1power solved sin=
ce 16:12 but the site remain down at ocm fme TX Lionel Steve of huawei is i=
nformed(site swapped by ZTE)","etienne.itondo@ihstowers.com","6697","03-08-=
2024 17:47:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0002767310","V=
allee-Bastos OCM","","03-08-2024 16:55:58","03-08-2024 15:01:50","03-08-202=
4 15:26:50","grid outage//MDG 20kva deployed'site swapped by ZTE)","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage/=
/MDG 20kva deployed'site swapped by ZTE)","etienne.itondo@ihstowers.com","6=
849","03-08-2024 16:55:58","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002767296","Jou=
vence 2000","","03-08-2024 16:51:07","03-08-2024 16:42:03","03-08-2024 16:5=
7:09","Grid outage site went down because Gen failed to start due to poor b=
attery backup///Grid power return","Delor Telezing","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage site went =
down because Gen failed to start due to poor battery backup///Grid power re=
turn","ludivine.ngamaleu@ihstowers.com","547","03-08-2024 16:51:07","Sagemc=
om CMR"
"Closed Complete","Site Down","T0290","IHS_YND_067","NOCINC0002767153","Nko=
a Ayos","","03-08-2024 16:12:20","03-08-2024 16:03:19","03-08-2024 17:15:43=
","Grid CB disjuntecd,and gen ran till fuel shortage//CB reamed and refueli=
ng done (50L)","MINKA NICOLAS","Equipment Repair","Passive","Control Panel"=
,"Faulty Circuit Breaker","Grid CB disjuntecd,and gen ran till fuel shortag=
e//CB reamed and refueling done (50L)","ludivine.ngamaleu@ihstowers.com","1=
2151","03-08-2024 16:12:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002767132","C=
arington","","03-08-2024 16:08:25","03-08-2024 16:04:18","03-08-2024 16:36:=
37","No power issue on site U=3D5v site on grid Team Douglas/659149839/ZTE =
working on site","","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue on site U=3D5v site on grid =
Team Douglas/659149839/ZTE working on site","dorothy.djantio@ihstowers.com"=
,"250","03-08-2024 16:08:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0002766761","N=
kolondom","","03-08-2024 14:43:12","03-08-2024 14:38:21","03-08-2024 18:54:=
49","tikect need to cascade at Olembe ocm","Fabrice Pouakam","Cascade Outag=
e","Active","Cascade Active","Cascade Active","Tx Issue : site on grid ,uba=
ie:54,4V; Dominique Membila    6 694552106 ZTE is working on site, (Pre ins=
tallation swap)","dorothy.djantio@ihstowers.com","15089","03-08-2024 14:43:=
12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_523","IHS_YND_681","NOCINC0002766754","N=
KOLMEKONG YDE","","03-08-2024 14:42:22","03-08-2024 14:38:21","03-08-2024 1=
8:54:49","tikect need to cascade at Olembe ocm","Fabrice Pouakam","Cascade =
Outage","Active","Cascade Active","Cascade Active","Tx Issue : site on grid=
 ,ubaie:54,4V; Dominique Membila    6 694552106 ZTE is working on site, (Pr=
e installation swap)","dorothy.djantio@ihstowers.com","15062","03-08-2024 1=
4:42:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_468","IHS_YND_297","NOCINC0002766747","M=
essassi","","03-08-2024 14:39:46","03-08-2024 14:38:21","03-08-2024 18:54:4=
9","tikect need to cascade at Olembe ocm","Fabrice Pouakam","Cascade Outage=
","Active","Cascade Active","Cascade Active","Tx Issue : site on grid ,ubai=
e:54,4V; Dominique Membila    6 694552106 ZTE is working on site, (Pre inst=
allation swap)","dorothy.djantio@ihstowers.com","15119","03-08-2024 14:39:4=
6","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_187","NOCINC0002766679","NTEMASSI=
","","03-08-2024 14:19:30","03-08-2024 14:09:29","03-08-2024 14:30:48","Cas=
caded Incident from TTO2565268","Delor Telezing","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage//MDG 13kva deployed","sys=
tem","601","03-08-2024 14:19:30","Sagemcom CMR"
"Closed Complete","Site Down","T0542","IHS_YND_185","NOCINC0002766675","Ngo=
usso MTN","IHS_YND_187","03-08-2024 14:18:32","03-08-2024 14:09:29","03-08-=
2024 14:30:48","grid outage//MDG 13kva deployed","","Grid Supply","Passive"=
,"Grid","National Grid - Grid Outage Issue","grid outage//MDG 13kva deploye=
d","ludivine.ngamaleu@ihstowers.com","545","03-08-2024 14:18:32","Sagemcom =
CMR"
"Cancelled","Warning","T1630","IHS_YND_187","NOCINC0002766666","NTEMASSI","=
","03-08-2024 14:17:32","","","","Delor Telezing","","","","","","ludivine.=
ngamaleu@ihstowers.com","484","03-08-2024 14:17:32","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0002766596","Bas=
tos Bethesda","","03-08-2024 13:54:56","03-08-2024 13:49:49","03-08-2024 13=
:59:05","Grid outage site went down because Gen failed to start due to poor=
 battery backup///Gen manually start","Mboua Thierry","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage site wen=
t down because Gen failed to start due to poor battery backup///Gen manuall=
y start","alexandre.kamal@ihstowers.com","309","03-08-2024 13:54:56","Sagem=
com CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002766586","Pha=
rmacie SION","","03-08-2024 13:51:10","03-08-2024 13:46:03","03-08-2024 13:=
56:49","Grid outage site went down because Gen failed to start due to poor =
battery backup///Grid power return","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage site went do=
wn because Gen failed to start due to poor battery backup///Grid power retu=
rn","alexandre.kamal@ihstowers.com","308","03-08-2024 13:51:10","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002766580","E=
lig-Edzoa","","03-08-2024 13:48:35","03-08-2024 10:06:19","03-08-2024 10:30=
:52","ACTIVE no power issue U=3D54,7V site on Grid the tx fme RM alain /691=
144423 from huawei is informed","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","ACTIVE no power issue U=3D54=
,7V site on Grid the tx fme RM alain /691144423 from huawei is informed","k=
amga.virgile@ihstowers.com","13337","03-08-2024 13:48:35","Sagemcom CMR"
"Closed Complete","Site Down","T1103","IHS_YND_242","NOCINC0002766535","Mba=
lla 4","","03-08-2024 13:38:53","03-08-2024 13:31:45","03-08-2024 16:55:51"=
,"No power issue on site U=3D54,3v site on grid Armanf of huawei is informe=
d","Delor Telezing","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,3v site on gr=
id Armanf of huawei is informed","alexandre.kamal@ihstowers.com","429","03-=
08-2024 13:38:53","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0002766465","Mes=
sassi 2","","03-08-2024 13:26:47","03-08-2024 13:13:43","03-08-2024 14:12:5=
9","grid outage,gen stopped with alarm high temp//he added water in radiato=
r","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - High E=
ngine Temp - Coolant Level Issue","grid outage,gen stopped with alarm high =
temp//he added water in radiator","alexandre.kamal@ihstowers.com","2624","0=
3-08-2024 13:26:47","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0002766461","Abo=
me","","03-08-2024 13:26:05","03-08-2024 13:16:59","03-08-2024 15:55:22","G=
rid outage site went down because Gen started and stopped due to Gen Overlo=
ad (15kva ;125 A) // Grid return","MINKA NICOLAS","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage site went down because Gen st=
arted and stopped due to Gen Overload (15kva ;125 A) // Grid return","alexa=
ndre.kamal@ihstowers.com","546","03-08-2024 13:26:05","Sagemcom CMR"
"Closed Complete","Site Down","T2570","IHS_YND_749","NOCINC0002766215","ODZ=
A MINKAN EDIBI ASSI","","03-08-2024 12:56:29","03-08-2024 12:51:26","03-08-=
2024 13:55:51","grid outage,gen failed to star due to battery Ge discharged=
//he started the gen with battery backup","Albran Byorel","Equipment Repair=
","Passive","ACDG Gen","ACDG - Generator Battery","grid outage,gen failed t=
o star due to battery Ge discharged//he started the gen with battery backup=
","alexandre.kamal@ihstowers.com","303","03-08-2024 12:56:29","Sagemcom CMR=
"
"Closed Complete","Site Down","T1688","IHS_YND_025","NOCINC0002766134","COR=
NIERS","","03-08-2024 12:43:03","03-08-2024 09:56:40","03-08-2024 10:00:27"=
,"","","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site, site on Grid with Ubaie=3D54,8V =
Tx fme Armand Ngeuts from Huawei is Informed ","alexandre.kamal@ihstowers.c=
om","9984","03-08-2024 12:43:03","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002766100","Mok=
olo Yaounde","","03-08-2024 12:35:20","03-08-2024 12:32:32","03-08-2024 12:=
35:32","Grid outage No space to deployed a mobile Gen// Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e No space to deployed a mobile Gen// Grid return","alexandre.kamal@ihstowe=
rs.com","169","03-08-2024 12:35:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0002766099","N=
R-Bastos","","03-08-2024 12:35:11","03-08-2024 11:09:45","03-08-2024 12:50:=
06","Grid outage No space to deployed a mobile Gen // Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
No space to deployed a mobile Gen // Grid return","kamga.virgile@ihstowers.=
com","5131","03-08-2024 12:35:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0002766074","V=
allee-Bastos OCM","","03-08-2024 12:31:12","03-08-2024 11:37:02","03-08-202=
4 13:22:44","eta=3D 13:20","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","Grid outage//MDG of 20kva has deployed","kamga.virgi=
le@ihstowers.com","3252","03-08-2024 12:31:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002766057","Sapeur",=
"","03-08-2024 12:27:10","03-08-2024 10:25:11","03-08-2024 13:02:02","Casca=
ded Incident from TTO2564545","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage No space to deployed a mobil=
e Gen //Grid return ( Site swap by ZTE.)","system","7319","03-08-2024 12:27=
:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002766029","E=
-Police","IHS_YND_029","03-08-2024 12:23:19","03-08-2024 10:25:11","03-08-2=
024 13:02:02","Grid outage No space to deployed a mobile Gen //Grid return =
( Site swap by ZTE.)","","Grid Supply","Passive","Grid","National Grid - Gr=
id Outage Issue","Grid outage No space to deployed a mobile Gen //Grid retu=
rn ( Site swap by ZTE.)","kamga.virgile@ihstowers.com","7089","03-08-2024 1=
2:23:19","Sagemcom CMR"
"Closed Complete","Site Down","T3156","IHS_YND_063","NOCINC0002765892","Av-=
Germaine","","03-08-2024 11:56:05","03-08-2024 11:44:44","03-08-2024 16:12:=
13","Grid outage No space to deployed a mobile Gen// Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage N=
o space to deployed a mobile Gen// Grid return","alexandre.kamal@ihstowers.=
com","1953","03-08-2024 11:56:05","Sagemcom CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0002765832","Mba=
nkomo CAF","","03-08-2024 11:37:45","03-08-2024 11:30:36","03-08-2024 12:19=
:46","site was on gen due to grid outage, site went down due to fuel spilla=
ge at the return hose// he reconnected the hose","Fanda Brice","Fuel Outage=
 (Probable)","Passive","Diesel","Fuel Line Issue","site was on gen due to g=
rid outage, site went down due to fuel spillage at the return hose// he rec=
onnected the hose","alexandre.kamal@ihstowers.com","431","03-08-2024 11:37:=
45","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002765829","Bas=
tos Amb Coree","","03-08-2024 11:36:37","03-08-2024 11:24:59","03-08-2024 1=
2:50:29","Grid outage No space to deployed a mobile Gen // Grid return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage No space to deployed a mobile Gen // Grid return","alexandre.kamal@ihs=
towers.com","699","03-08-2024 11:36:37","Sagemcom CMR"
"Closed Complete","Site Down","T1248","IHS_YND_797","NOCINC0002765813","Mes=
sassi Carrefourt","","03-08-2024 11:31:32","03-08-2024 10:44:24","03-08-202=
4 12:00:18","Grid outage site went down because Gen start and stopped with =
alarm over frequency // He reduce the frequency of site","Delor Telezing","=
Equipment Repair","Passive","ACDG Gen","ACDG - Over Frequency","Grid outage=
 site went down because Gen start and stopped with alarm over frequency // =
He reduce the frequency of site","alexandre.kamal@ihstowers.com","2830","03=
-08-2024 11:31:32","Sagemcom CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0002765790","Mvo=
g-Ada_OCM","","03-08-2024 11:29:34","03-08-2024 10:44:30","03-08-2024 16:19=
:33","Grid outage No space to deployed a mobile Gen// Grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage =
No space to deployed a mobile Gen// Grid return","alexandre.kamal@ihstowers=
.com","6783","03-08-2024 11:29:34","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0002765559","Bas=
tos Bethesda","","03-08-2024 10:42:25","03-08-2024 10:33:59","03-08-2024 11=
:51:44","Grid outage site went down because Gen failed to start due to poor=
 battery backup///Gen manually start","Mboua Thierry","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage site wen=
t down because Gen failed to start due to poor battery backup///Gen manuall=
y start","alexandre.kamal@ihstowers.com","509","03-08-2024 10:42:25","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0002765462","Akak-Nko=
zoa-MTN-IHS","","03-08-2024 10:25:30","03-08-2024 09:55:40","03-08-2024 10:=
47:04","Cascaded Incident from TTO2563914","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Grid outage ,site went do=
wn because Gen started and stopped with alarm low oil pressure //He reset c=
ard GE and gen manually started","system","1790","03-08-2024 10:25:30","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_799","NOCINC0002765463","Messassi=
 Ngonlonk","","03-08-2024 10:25:30","03-08-2024 09:55:40","03-08-2024 10:47=
:04","Cascaded Incident from TTO2563914","Fabrice Pouakam","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage ,site went down=
 because Gen started and stopped with alarm low oil pressure //He reset car=
d GE and gen manually started","system","1790","03-08-2024 10:25:30","Sagem=
com CMR"
"Closed Complete","Site Down","T0051","IHS_YND_297","NOCINC0002765459","Mes=
sassi","IHS_YND_316, IHS_YND_799","03-08-2024 10:24:48","03-08-2024 09:55:4=
0","03-08-2024 10:47:04","Grid outage ,site went down because Gen started a=
nd stopped with alarm low oil pressure //He reset card GE and gen manually =
started","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - =
Control Panel","Grid outage ,site went down because Gen started and stopped=
 with alarm low oil pressure //He reset card GE and gen manually started","=
alexandre.kamal@ihstowers.com","1749","03-08-2024 10:24:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002765334","E=
mana","","03-08-2024 09:48:39","03-08-2024 09:26:26","03-08-2024 13:12:16",=
"grid outage//grid return","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","No free mobile Gen to deploie waitting grid return",=
"kamga.virgile@ihstowers.com","1336","03-08-2024 09:48:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0002765318","Kondengu=
i","","03-08-2024 09:44:11","03-08-2024 09:14:32","03-08-2024 09:48:29","Ca=
scaded Incident from TTO2563687","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive"," grid outage, site went down because =
gen faild to start// Gen manually start (investigation ongoing)","system","=
1779","03-08-2024 09:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_025","NOCINC0002765312","CORNIERS=
","","03-08-2024 09:44:11","03-08-2024 09:14:32","03-08-2024 09:48:29","Cas=
caded Incident from TTO2563687","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive"," grid outage, site went down because gen faild to s=
tart// Gen manually start (investigation ongoing)","system","1779","03-08-2=
024 09:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_680","NOCINC0002765316","MIMBOMAN=
 LIBERTE","","03-08-2024 09:44:11","03-08-2024 09:14:32","03-08-2024 09:48:=
29","Cascaded Incident from TTO2563687","Mba Lazare Herve","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive"," grid outage, site went dow=
n because gen faild to start// Gen manually start (investigation ongoing)",=
"system","1779","03-08-2024 09:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_734","NOCINC0002765314","Mimboman=
 Chateau","","03-08-2024 09:44:11","03-08-2024 09:14:32","03-08-2024 09:48:=
29","Cascaded Incident from TTO2563687","","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive"," grid outage, site went down because gen fa=
ild to start// Gen manually start (investigation ongoing)","system","1779",=
"03-08-2024 09:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_097","NOCINC0002765319","Kondengu=
i MTN","","03-08-2024 09:44:11","03-08-2024 09:14:32","03-08-2024 09:48:29"=
,"Cascaded Incident from TTO2563687","Albran Byorel","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive"," grid outage, site went down beca=
use gen faild to start// Gen manually start (investigation ongoing)","syste=
m","1779","03-08-2024 09:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_178","NOCINC0002765317","Emombo",=
"","03-08-2024 09:44:11","03-08-2024 09:14:32","03-08-2024 09:48:29","Casca=
ded Incident from TTO2563687","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive"," grid outage, site went down because =
gen faild to start// Gen manually start (investigation ongoing)","system","=
1779","03-08-2024 09:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_109","NOCINC0002765313","Mobil-Es=
sos","","03-08-2024 09:44:11","03-08-2024 09:14:32","03-08-2024 09:48:29","=
Cascaded Incident from TTO2563687","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive"," grid outage, site went down becaus=
e gen faild to start// Gen manually start (investigation ongoing)","system"=
,"1779","03-08-2024 09:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_065","NOCINC0002765320","Essos DC=
S","","03-08-2024 09:44:11","03-08-2024 09:14:32","03-08-2024 09:48:29","Ca=
scaded Incident from TTO2563687","Delor Telezing","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive"," grid outage, site went down because=
 gen faild to start// Gen manually start (investigation ongoing)","system",=
"1779","03-08-2024 09:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0002765315","Anguissa=
 New","","03-08-2024 09:44:11","03-08-2024 09:14:32","03-08-2024 09:48:29",=
"Cascaded Incident from TTO2563687","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive"," grid outage, site went down becau=
se gen faild to start// Gen manually start (investigation ongoing)","system=
","1779","03-08-2024 09:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0002765321","Crf Corn=
ier","","03-08-2024 09:44:11","03-08-2024 09:14:32","03-08-2024 09:48:29","=
Cascaded Incident from TTO2563687","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive"," grid outage, site went down becaus=
e gen faild to start// Gen manually start (investigation ongoing)","system"=
,"1779","03-08-2024 09:44:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_180","NOCINC0002765305","Mimboman=
","","03-08-2024 09:44:10","03-08-2024 09:14:32","03-08-2024 09:48:29","Cas=
caded Incident from TTO2563687","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive"," grid outage, site went down becaus=
e gen faild to start// Gen manually start (investigation ongoing)","system"=
,"1778","03-08-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_189","NOCINC0002765308","Paradis =
Hotel","","03-08-2024 09:44:10","03-08-2024 09:14:32","03-08-2024 09:48:29"=
,"Cascaded Incident from TTO2563687","Siligap Boris","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive"," grid outage, site went down beca=
use gen faild to start// Gen manually start (investigation ongoing)","syste=
m","1778","03-08-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_111","NOCINC0002765303","Essos Ma=
rche","","03-08-2024 09:44:10","03-08-2024 09:14:32","03-08-2024 09:48:29",=
"Cascaded Incident from TTO2563687","Delor Telezing","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive"," grid outage, site went down beca=
use gen faild to start// Gen manually start (investigation ongoing)","syste=
m","1778","03-08-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_042","NOCINC0002765304","Mvog-Ada=
_OCM","","03-08-2024 09:44:10","03-08-2024 09:14:32","03-08-2024 09:48:29",=
"Cascaded Incident from TTO2563687","","Cascade Outage","Passive","Cascade =
Passive","Cascade Passive"," grid outage, site went down because gen faild =
to start// Gen manually start (investigation ongoing)","system","1778","03-=
08-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_120","NOCINC0002765310","Sapeur M=
imboman","","03-08-2024 09:44:10","03-08-2024 09:14:32","03-08-2024 09:48:2=
9","Cascaded Incident from TTO2563687","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive"," grid outage, site went down=
 because gen faild to start// Gen manually start (investigation ongoing)","=
system","1778","03-08-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_797","NOCINC0002765306","Messassi=
 Carrefourt","","03-08-2024 09:44:10","03-08-2024 09:14:32","03-08-2024 09:=
48:29","Cascaded Incident from TTO2563687","Delor Telezing","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive"," grid outage, site went do=
wn because gen faild to start// Gen manually start (investigation ongoing)"=
,"system","1778","03-08-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_682","NOCINC0002765302","MONTEE N=
KONDENGUI","","03-08-2024 09:44:10","03-08-2024 09:14:32","03-08-2024 09:48=
:29","Cascaded Incident from TTO2563687","Albran Byorel","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive"," grid outage, site went down =
because gen faild to start// Gen manually start (investigation ongoing)","s=
ystem","1778","03-08-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_063","NOCINC0002765309","Av-Germa=
ine","","03-08-2024 09:44:10","03-08-2024 09:14:32","03-08-2024 09:48:29","=
Cascaded Incident from TTO2563687","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive"," grid outage, site went down because gen faild t=
o start// Gen manually start (investigation ongoing)","system","1778","03-0=
8-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_113","NOCINC0002765311","Emombo 2=
","","03-08-2024 09:44:10","03-08-2024 09:14:32","03-08-2024 09:48:29","Cas=
caded Incident from TTO2563687","MINKA NICOLAS","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive"," grid outage, site went down because g=
en faild to start// Gen manually start (investigation ongoing)","system","1=
778","03-08-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_122","NOCINC0002765307","Emombo E=
sssomba","","03-08-2024 09:44:10","03-08-2024 09:14:32","03-08-2024 09:48:2=
9","Cascaded Incident from TTO2563687","Mba Lazare Herve","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive"," grid outage, site went down=
 because gen faild to start// Gen manually start (investigation ongoing)","=
system","1778","03-08-2024 09:44:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002765276","Messassi=
","","03-08-2024 09:38:30","03-08-2024 09:11:19","03-08-2024 09:20:44","Cas=
caded Incident from TTO2563697","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Tx Issue : site on grid ,ubaie:54,4V; D=
ominique Membila    6 694552106 ZTE is working on site, (Pre installation s=
wap)","system","1631","03-08-2024 09:38:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002765275","NKOLMEKO=
NG YDE","","03-08-2024 09:38:30","03-08-2024 09:11:19","03-08-2024 09:20:44=
","Cascaded Incident from TTO2563697","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Tx Issue : site on grid ,ubaie:54=
,4V; Dominique Membila    6 694552106 ZTE is working on site, (Pre installa=
tion swap)","system","1631","03-08-2024 09:38:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002765277","Nkolondo=
m","","03-08-2024 09:38:30","03-08-2024 09:11:19","03-08-2024 09:20:44","Ca=
scaded Incident from TTO2563697","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","Tx Issue : site on grid ,ubaie:54,4V; =
Dominique Membila    6 694552106 ZTE is working on site, (Pre installation =
swap)","system","1631","03-08-2024 09:38:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002765267","O=
lembe","IHS_YND_681, IHS_YND_297, IHS_YND_304","03-08-2024 09:35:35","03-08=
-2024 09:11:19","03-08-2024 09:20:44","Tx Issue : site on grid ,ubaie:54,4V=
; Dominique Membila    6 694552106 ZTE is working on site, (Pre installatio=
n swap)","Fabrice Pouakam","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Tx Issue : site on grid ,ubaie:54,4V=
; Dominique Membila    6 694552106 ZTE is working on site, (Pre installatio=
n swap)","kamga.virgile@ihstowers.com","1456","03-08-2024 09:35:35","Sagemc=
om CMR"
"Closed Complete","Site Down","T0103","IHS_YND_110","NOCINC0002765256","Cam=
p-Sonel","IHS_YND_682, IHS_YND_111, IHS_YND_042, IHS_YND_180, IHS_YND_797, =
IHS_YND_122, IHS_YND_189, IHS_YND_063, IHS_YND_120, IHS_YND_113, IHS_YND_02=
5, IHS_YND_109, IHS_YND_734, IHS_YND_568, IHS_YND_680, IHS_YND_178, IHS_YND=
_114, IHS_YND_097, IHS_YND_065, IHS_YND_566","03-08-2024 09:32:37","03-08-2=
024 09:14:32","03-08-2024 09:48:29"," grid outage, site went down because g=
en faild to start// Gen manually start (investigation ongoing)","Siligap Bo=
ris","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel"," grid =
outage, site went down because gen faild to start// Gen manually start (inv=
estigation ongoing)","alexandre.kamal@ihstowers.com","1087","03-08-2024 09:=
32:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002765247","B=
iteng","","03-08-2024 09:30:50","03-08-2024 09:23:34","03-08-2024 09:30:56"=
,"Tx Issue : site on grid ,ubaie:54,4V;  Clement  680557975 ZTE is working =
on site,SWAP ZTE.","Mba Lazare Herve","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Tx Issue : site on grid ,=
ubaie:54,4V;  Clement  680557975 ZTE is working on site,SWAP ZTE.","kamga.v=
irgile@ihstowers.com","437","03-08-2024 09:30:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002765189","E=
lig-Edzoa","","03-08-2024 09:15:01","03-08-2024 08:42:16","03-08-2024 10:05=
:05","Grid outage//MDG of 20kva has deployed","","Grid Supply","Passive","G=
rid","National Grid - Grid Outage Issue","Grid outage//MDG of 20kva has dep=
loyed","kamga.virgile@ihstowers.com","1967","03-08-2024 09:15:01","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002765160","NKO=
MEKUI OCM","","03-08-2024 09:02:12","03-08-2024 08:55:07","03-08-2024 09:11=
:18","Grid outage site went down because Gen failed to start due to poor ba=
ttery backup///Grid power return","TIENTCHEU NZETCHIEU GAEL","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage s=
ite went down because Gen failed to start due to poor battery backup///Grid=
 power return","alexandre.kamal@ihstowers.com","427","03-08-2024 09:02:12",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002765143","Man=
guiers Dispensaire","","03-08-2024 08:56:45","03-08-2024 08:50:37","03-08-2=
024 09:14:49","site went down  due to grid  contactor  faulty//He bypassed =
Grid and Gen manually started","Fabrice Pouakam","Equipment Repair","Passiv=
e","Control Panel","ATS-AMF Issue","site went down  due to grid  contactor =
 faulty//He bypassed Grid and Gen manually started","alexandre.kamal@ihstow=
ers.com","369","03-08-2024 08:56:45","Sagemcom CMR"
"Closed Complete","Site Down","T1553","IHS_YND_108","NOCINC0002765080","RUE=
 FOE","","03-08-2024 08:51:03","03-08-2024 08:50:56","03-08-2024 09:52:45",=
"grid outage,gen failed to start due to solenoid valve disconnected//he con=
nect it and started the gen","Delor Telezing","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Solenoid Coil","grid outage,gen failed to start due to s=
olenoid valve disconnected//he connect it and started the gen","alexandre.k=
amal@ihstowers.com","9","03-08-2024 08:51:03","Sagemcom CMR"
"Closed Complete","Site Down","T1583","IHS_YND_102","NOCINC0002765005","Nta=
ba","","03-08-2024 08:29:20","03-08-2024 08:23:14","03-08-2024 08:29:27","G=
rid outage site went down before Gen started due to poor battery back up //=
 Gen started automatically.","Delor Telezing","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage site went down b=
efore Gen started due to poor battery back up // Gen started automatically.=
","alexandre.kamal@ihstowers.com","367","03-08-2024 08:29:20","Sagemcom CMR=
"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002764897","Jou=
vence 2000","","03-08-2024 08:03:17","03-08-2024 07:45:09","03-08-2024 09:2=
4:32","site went down  due to grid  contactor  faulty//He bypassed Grid and=
 Gen manually started","Delor Telezing","Equipment Repair","Passive","Contr=
ol Panel","ATS-AMF Issue","site went down  due to grid  contactor  faulty//=
He bypassed Grid and Gen manually started","alexandre.kamal@ihstowers.com",=
"1090","03-08-2024 08:03:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002764885","C=
arington","","03-08-2024 07:59:12","03-08-2024 07:54:22","03-08-2024 12:27:=
49","Grid outage//MDG of 20kva has deployed","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid outage//MDG of 20kva has depl=
oyed","kamga.virgile@ihstowers.com","292","03-08-2024 07:59:12","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002764603","M=
asque","","03-08-2024 06:41:39","03-08-2024 06:26:33","03-08-2024 06:30:55"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V   The TX FME  Elo=
undou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V=
   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive=
 issue","kamga.virgile@ihstowers.com","907","03-08-2024 06:41:39","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002764380","O=
dza II OCM","","03-08-2024 04:55:32","02-08-2024 20:31:08","02-08-2024 23:3=
9:05","Site went down due to insuffisance of rectifier // site stabilized (=
swapping by ZTE )","Albran Byorel","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to insuffisance of rectifier // sit=
e stabilized (swapping by ZTE )","joelle.ekessi@ihstowers.com","30265","03-=
08-2024 04:55:32","Sagemcom CMR"
"Closed Complete","Warning","T0029","IHS_YND_357","NOCINC0002763958","Sacre=
 Coeur Catholic Church","","03-08-2024 01:24:07","","","SITE ON BATTERY","M=
boua Thierry","Warning","Warning","POWER","Warning - Site on Battery","Unpr=
ouven Alarm site on grid with U=3D54.8V","kombi.samuel@ihstowers.com","4","=
03-08-2024 01:24:07","Sagemcom CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0002763872","Mey=
o","IHS_YND_313","03-08-2024 00:39:02","03-08-2024 00:32:56","03-08-2024 01=
:35:26","Site went down because the CB (40A) rectifier dysjuncted  due to G=
rid bad voltages// He  reamed the CB,site on Grid","Hyemafo Gildas","Equipm=
ent Repair","Passive","Rectifier","Rectifier - Circuit Breaker","Site went =
down because the CB (40A) rectifier dysjuncted  due to Grid bad voltages// =
He  reamed the CB,site on Grid","emmanuel.ghani@ihstowers.com","368","03-08=
-2024 00:39:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002763815","M=
asque","","03-08-2024 00:21:57","03-08-2024 00:13:44","03-08-2024 00:25:29"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V  The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V =
 The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive i=
ssue","joelle.ekessi@ihstowers.com","494","03-08-2024 00:21:57","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0002763809","A=
fanoya","","03-08-2024 00:19:50","03-08-2024 00:32:56","03-08-2024 01:35:26=
","Site went down because the CB (40A) rectifier dysjuncted  due to Grid ba=
d voltages// He  reamed the CB,site on Grid","Hyemafo Gildas","Cascade Outa=
ge","Passive","Cascade Passive","Cascade Passive","Site went down because t=
he CB (40A) rectifier dysjuncted  due to Grid bad voltages// He  reamed the=
 CB,site on Grid","joelle.ekessi@ihstowers.com","1094","03-08-2024 00:19:50=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0002763630","M=
EHANDAN","","02-08-2024 23:15:41","02-08-2024 20:31:08","02-08-2024 20:52:0=
5","","Albran Byorel","Equipment Repair","Passive","Rectifier","Rectifier M=
odule","The site went down due to insuffisance of the rectifier // site was=
 stabilized (swapping by ZTE )","joelle.ekessi@ihstowers.com","30383","02-0=
8-2024 23:15:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0002763054","Saa","",=
"02-08-2024 21:34:50","02-08-2024 21:29:26","02-08-2024 21:33:04","Cascaded=
 Incident from TTO2561184","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to rectifiers 02/03 dysf=
unctionning // he Reset of Rectifiers","system","324","02-08-2024 21:34:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0002763053","SAA Entr=
ance","","02-08-2024 21:34:50","02-08-2024 21:29:26","02-08-2024 21:33:04",=
"Cascaded Incident from TTO2561184","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site went down due to rectifiers 0=
2/03 dysfunctionning // he Reset of Rectifiers","system","324","02-08-2024 =
21:34:50","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0002763049","SAA=
 2","IHS_YND_542, IHS_YND_405","02-08-2024 21:33:34","02-08-2024 21:29:26",=
"02-08-2024 21:39:05","Site went down due to rectifiers 02/03 dysfunctionni=
ng // he Reset of Rectifiers","Parker Tchoup","Equipment Repair","Passive",=
"Rectifier","Rectifier Module","Site went down due to rectifiers 02/03 dysf=
unctionning // he Reset of Rectifiers","ange.kongo@ihstowers.com","4005","0=
2-08-2024 21:33:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0002762862","C=
hapelle-Nsimeyong","","02-08-2024 21:14:00","02-08-2024 20:03:52","02-08-20=
24 23:10:51","Active// Active: No power issue, site is on Grid with Ubaie=
=3D54,4V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed Site swa=
pped by ZTE","MINKA NICOLAS","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active// Active: No power issue, s=
ite is on Grid with Ubaie=3D54,4V,The tx Fme Hosiah (6 74 00 74 38) from Hu=
awei is informed Site swapped by ZTE","adonis.defokoua@ihstowers.com","4209=
","02-08-2024 21:14:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0002762847","M=
endong vallee","","02-08-2024 21:12:44","02-08-2024 19:29:37","02-08-2024 1=
9:32:03","Active //No power issue on site U=3D55,1  V The Tx FME Hosiah//69=
9699694 is informed  ","Fanda Brice","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","Active //No power issue on=
 site U=3D55,1  V The Tx FME Hosiah//699699694 is informed ","adonis.defoko=
ua@ihstowers.com","6189","02-08-2024 21:12:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0002762235","Nkomkana=
","","02-08-2024 20:18:00","02-08-2024 18:24:03","02-08-2024 21:55:41","Cas=
caded Incident from TTO2560079","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Site went down due to OCM circuit breaker disjuncte=
d in the PWC // Circuit breaker put back on in vestigations( Site swapped b=
y ZTE)","system","6837","02-08-2024 20:18:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0002762236","Entree C=
ite Verte","","02-08-2024 20:18:00","02-08-2024 18:24:03","02-08-2024 21:55=
:41","Cascaded Incident from TTO2560079","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site went down due to OCM circu=
it breaker disjuncted in the PWC // Circuit breaker put back on in vestigat=
ions( Site swapped by ZTE)","system","6837","02-08-2024 20:18:00","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0002762022","C=
ite-Verte","IHS_YND_200, IHS_YND_543","02-08-2024 20:14:24","02-08-2024 18:=
24:03","02-08-2024 21:55:41","Site went down due to OCM circuit breaker dis=
juncted in the PWC // Circuit breaker put back on in vestigations( Site swa=
pped by ZTE)","","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Circuit Breaker Issue","Site went down due to OCM circuit breaker disju=
ncted in the PWC // Circuit breaker put back on in vestigations( Site swapp=
ed by ZTE)","adonis.defokoua@ihstowers.com","6623","02-08-2024 20:14:24","S=
agemcom CMR"
"Closed Complete","Site Down","T1491","IHS_YND_808","NOCINC0002761761","Mba=
nkolo petit paris","","02-08-2024 19:55:00","02-08-2024 19:49:52","02-08-20=
24 19:52:47",": No power issue, site is on gen with Ubaie=3D54.5V,   Brice =
Tsague (650 21 40 96) from Huawei is informed.","Mboua Thierry","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"No power issue, site is on gen with Ubaie=3D54.5V, Brice Tsague (650 21 40=
 96) from Huawei is informed.


","ange.kongo@ihstowers.com","309","02-08-2024 19:55:00","Sagemcom CMR"
"Closed Complete","Site Down","T1872","IHS_YND_519","NOCINC0002761756","AFE=
ME NORD","","02-08-2024 19:53:05","02-08-2024 19:49:00","02-08-2024 20:19:5=
1","Grid outage,DG failed to started DG battery  pod bad tightened //He tig=
htened well,and manually start of DG,Site swapped by ZTE","TIENTCHEU NZETCH=
IEU GAEL","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery=
","Grid outage,DG failed to started DG battery  pod bad tightened //He tigh=
tened well,and manually start of DG,Site swapped by ZTE","ange.kongo@ihstow=
ers.com","247","02-08-2024 19:53:05","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0002761704","ODZ=
A CITE MBIA","","02-08-2024 19:44:04","02-08-2024 19:13:59","02-08-2024 23:=
15:10","no power issue  on site ,site on GRid  with U=3D53,2V Team lionel a=
djep  ( 655184876 )  from HUAWEI  is informed","Albran Byorel","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
no power issue  on site ,site on GRid  with U=3D53,2V Team lionel adjep  ( =
655184876 )  from HUAWEI  is informed","ange.kongo@ihstowers.com","1805","0=
2-08-2024 19:44:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0002761699","B=
yemassi Carrefour","","02-08-2024 19:41:14","02-08-2024 18:44:05","02-08-20=
24 18:50:39","Active// Active: No power issue, site is on Grid with Ubaie=
=3D54V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","Paul BIB=
OUM","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active// Active: No power issue, site is on Grid with Ubai=
e=3D54V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","adonis.=
defokoua@ihstowers.com","3430","02-08-2024 19:41:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0002761684","S=
hell-Nsimeyong","","02-08-2024 19:37:01","02-08-2024 18:39:53","02-08-2024 =
18:42:23","Tx issue ,site on grid,Ubaie:54,2v; Hosiah Mba is informed","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Tx issue ,site on grid,Ubaie:54,2v; Hosiah Mba is i=
nformed","adonis.defokoua@ihstowers.com","3430","02-08-2024 19:37:01","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002761489","ELOUMDEM=
 CARRIERE 2","","02-08-2024 18:54:40","02-08-2024 18:43:58","02-08-2024 19:=
45:50","Cascaded Incident from TTO2559476","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went due to insufficienc=
y of rectifiers // Rectifiers must be added.","system","642","02-08-2024 18=
:54:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002761488","Eto koss=
 Yde","","02-08-2024 18:54:40","02-08-2024 18:43:58","02-08-2024 19:45:50",=
"Cascaded Incident from TTO2559476","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went due to insufficiency of re=
ctifiers // Rectifiers must be added.","system","642","02-08-2024 18:54:40"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002761462","Afanoya"=
,"","02-08-2024 18:50:10","02-08-2024 16:58:05","02-08-2024 17:32:10","Casc=
aded Incident from TTO2559487","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site on DG due to grid outage,grid res=
tored,site went down due to battery backup discharged//Grid restored,site o=
n Grid,
","system","6725","02-08-2024 18:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002761460","ELOUMDEM=
 CARRIERE","","02-08-2024 18:50:10","02-08-2024 16:58:05","02-08-2024 17:32=
:10","Cascaded Incident from TTO2559487","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site on DG due to grid outage,g=
rid restored,site went down due to battery backup discharged//Grid restored=
,site on Grid,
","system","6725","02-08-2024 18:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002761461","MBALNGON=
G LYCEE","","02-08-2024 18:50:10","02-08-2024 16:58:05","02-08-2024 17:32:1=
0","Cascaded Incident from TTO2559487","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site on DG due to grid outage,gri=
d restored,site went down due to battery backup discharged//Grid restored,s=
ite on Grid,
","system","6725","02-08-2024 18:50:10","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002761456","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","02-08-2024 18:48:24","02-08-20=
24 16:58:05","02-08-2024 17:32:10","Site on DG due to grid outage,grid rest=
ored,site went down due to battery backup discharged//Grid restored,site on=
 Grid,Site swap by ZTE.","Hyemafo Gildas","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low","Site on DG due to grid outage,gr=
id restored,site went down due to battery backup discharged//Grid restored,=
site on Grid,
","ange.kongo@ihstowers.com","6620","02-08-2024 18:48:24","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002761446","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","02-08-2024 18:46:07","02-08-2024 18:43=
:58","02-08-2024 19:45:50","Site went due to insufficiency of rectifiers //=
 Rectifiers must be added.","Fanda Brice","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went due to insufficiency of rectifiers //=
 Rectifiers must be added.","ange.kongo@ihstowers.com","129","02-08-2024 18=
:46:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_315","IHS_YND_292","NOCINC0002761380","B=
itoto","","02-08-2024 18:30:31","02-08-2024 18:04:25","02-08-2024 21:19:39"=
,"""Tx Issue : site on grid ,ubaie:54,2V;  Christian 691927185 ZTE is worki=
ng on site,SWAP ZTE. ""","Mba Lazare Herve","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","""Tx Issue : site o=
n grid ,ubaie:54,2V;  Christian 691927185 ZTE is working on site,SWAP ZTE.
""","adonis.defokoua@ihstowers.com","1568","02-08-2024 18:30:31","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_309","IHS_YND_343","NOCINC0002761369","M=
bedoumou - Ekali","","02-08-2024 18:28:40","02-08-2024 18:01:35","02-08-202=
4 21:20:34","Tx issue:Site on Grid,Ubaie:54,2V; Lionel Adjep/655-18-48-76 i=
s informed.","Albran Byorel","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Tx issue:Site on Grid,Ubaie:54,2V;=
 Lionel Adjep/655-18-48-76 is informed.
","adonis.defokoua@ihstowers.com","1626","02-08-2024 18:28:40","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0002760923","B=
iteng-Maetur","","02-08-2024 16:51:06","02-08-2024 13:37:43","02-08-2024 14=
:00:49","Tx issue ;Site on Grid,Ubaie:54,2; Disjunction in the BTS OCM  Lio=
nel Adjep is informed.","Mba Lazare Herve","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Tx issue ;Site on Gr=
id,Ubaie:54,2; Disjunction in the BTS OCM  Lionel Adjep is informed.
","adonis.defokoua@ihstowers.com","11605","02-08-2024 16:51:06","Sagemcom C=
MR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0002760738","Abo=
me","","02-08-2024 16:24:34","02-08-2024 16:17:25","02-08-2024 17:17:06","G=
rid outage ,DG started and stopped due to DG overload// He reduiced the loa=
d ;Grid restored.Site wap by ZTE.","MINKA NICOLAS","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - Overload","Grid outage ,DG started and stopped due =
to DG overload//Grid restored.Site wap by ZTE.
","ange.kongo@ihstowers.com","431","02-08-2024 16:24:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0002760717","B=
ISCUITERIE","","02-08-2024 16:20:08","02-08-2024 16:09:03","02-08-2024 18:1=
7:19","Tx Issue site on grid,Ubaie:54,5V; Technician ZTE /697-305-221 sis w=
orking on site,SWAP ZTE.","Paul BIBOUM","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Tx Issue site on grid,U=
baie:54,5V; Technician ZTE /697-305-221 sis working on site,SWAP ZTE.
","adonis.defokoua@ihstowers.com","667","02-08-2024 16:20:08","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0002760673","O=
dza II","","02-08-2024 16:11:09","02-08-2024 12:04:55","03-08-2024 05:10:51=
","Tx Issue Site on Grid,Ubaie:54,2 V; Lionel Adjep is informed  Site swap =
by ZTE","Albran Byorel","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Tx Issue Site on Grid,Ubaie:54,2 V; Lio=
nel Adjep is informed  Site swap by ZTE","adonis.defokoua@ihstowers.com","1=
4776","02-08-2024 16:11:09","Sagemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0002760622","Nko=
lo II New","","02-08-2024 15:54:54","02-08-2024 15:40:39","02-08-2024 16:37=
:23","Tx Issue Site on Grid,Ubaie:54,5V;  Okolo/695-68-49-63 is working on =
site : Normalisation, Lionel Adjep is informed.","Mba Lazare Herve","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Tx Issue Site on Grid,Ubaie:54,5V;  Okolo/695-68-49-63 is working on s=
ite : Normalisation, Lionel Adjep is informed.","ange.kongo@ihstowers.com",=
"856","02-08-2024 15:54:54","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0002760616","Mim=
boman4","","02-08-2024 15:52:46","02-08-2024 15:40:21","02-08-2024 18:10:59=
","Tx Issue Site on Grid,Ubaie:54,5V; Lionel Adjep 655-18-48-76 is informed=
.","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","Tx Issue Site on Grid,Ubaie:54,5V; Lionel=
 Adjep 655-18-48-76 is informed.","ange.kongo@ihstowers.com","746","02-08-2=
024 15:52:46","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002760058","ELOUMDEM=
 CARRIERE","","02-08-2024 13:56:40","02-08-2024 13:46:38","02-08-2024 14:44=
:30","Cascaded Incident from TTO2557896","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, Site went down bec=
aus gen start and stopped due to hight temp alarm // He added water and gen=
 manually start.
","system","602","02-08-2024 13:56:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002760060","Afanoya"=
,"","02-08-2024 13:56:40","02-08-2024 13:46:38","02-08-2024 14:44:30","Casc=
aded Incident from TTO2557896","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, Site went down becaus gen=
 start and stopped due to hight temp alarm // He added water and gen manual=
ly start.
","system","602","02-08-2024 13:56:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002760059","MBALNGON=
G LYCEE","","02-08-2024 13:56:40","02-08-2024 13:46:38","02-08-2024 14:44:3=
0","Cascaded Incident from TTO2557896","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, Site went down becau=
s gen start and stopped due to hight temp alarm // He added water and gen m=
anually start.
","system","602","02-08-2024 13:56:40","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002760056","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","02-08-2024 13:55:41","02-08-20=
24 13:46:38","02-08-2024 14:44:30","Grid outage, Site went down becaus gen =
start and stopped due to hight temp alarm // He added water and gen manuall=
y start.","Hyemafo Gildas","Equipment Repair","Passive","ACDG Gen","ACDG - =
High Engine Temp - Coolant Level Issue","Grid outage, Site went down becaus=
 gen start and stopped due to hight temp alarm // He added water and gen ma=
nually start.
","ludivine.ngamaleu@ihstowers.com","544","02-08-2024 13:55:41","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002759562","Sapeur",=
"","02-08-2024 12:22:40","02-08-2024 11:24:08","02-08-2024 13:03:51","Casca=
ded Incident from TTO2557349","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","grid outage,gen stopped with alarm high =
temp//he added water in radiator","system","3512","02-08-2024 12:22:40","Sa=
gemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0002759403","Bon=
djock","","02-08-2024 11:59:21","02-08-2024 11:51:16","02-08-2024 12:37:08"=
,"Grid outage site went down because Gen started and stopped due to priming=
 pump Faulty// He replaced the priming pump and Gen manually started","Fand=
a Brice","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Fuel Pump","=
Grid outage site went down because Gen started and stopped due to priming p=
ump Faulty// He replaced the priming pump and Gen manually started","ludivi=
ne.ngamaleu@ihstowers.com","486","02-08-2024 11:59:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002759323","MBALNGON=
G LYCEE","","02-08-2024 11:37:50","02-08-2024 11:24:17","02-08-2024 13:02:2=
3","Cascaded Incident from TTO2557023","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","grid outage,gen stopped with alar=
m high temp//he added water in radiator","system","813","02-08-2024 11:37:5=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002759324","Afanoya"=
,"","02-08-2024 11:37:50","02-08-2024 11:24:17","02-08-2024 13:02:23","Casc=
aded Incident from TTO2557023","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","grid outage,gen stopped with alarm hig=
h temp//he added water in radiator","system","813","02-08-2024 11:37:50","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002759322","ELOUMDEM=
 CARRIERE","","02-08-2024 11:37:50","02-08-2024 11:24:17","02-08-2024 13:02=
:23","Cascaded Incident from TTO2557023","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","grid outage,gen stopped with al=
arm high temp//he added water in radiator","system","813","02-08-2024 11:37=
:50","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002759281","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_029, IHS_YND_313","02-08-2024 11:29:=
35","02-08-2024 11:24:08","02-08-2024 13:03:51","grid outage,gen stopped wi=
th alarm high temp//he added water in radiator","Hyemafo Gildas","Equipment=
 Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issu=
e","grid outage,gen stopped with alarm high temp//he added water in radiato=
r","ludivine.ngamaleu@ihstowers.com","3489","02-08-2024 11:29:35","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0002759213","B=
ISCUITERIE","","02-08-2024 11:18:51","02-08-2024 11:14:29","02-08-2024 11:2=
2:29","Grid outage, site went down before gen start due to poor battery bac=
kup // grid return","Paul BIBOUM","Equipment Repair","Passive","Control Pan=
el","Power Cabinet - Battery Low","Grid outage, site went down before gen s=
tart due to poor battery backup // grid return","dorothy.djantio@ihstowers.=
com","264","02-08-2024 11:18:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0002759201","E=
ssomba","","02-08-2024 11:15:11","02-08-2024 11:09:03","02-08-2024 11:32:23=
","No power issue on site U=3D54,1v site on grid Team Charles/672489041/ZTE=
 working on site","Mba Lazare Herve","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,1v site on grid Team Charles/672489041/ZTE working on site","dorothy.=
djantio@ihstowers.com","369","02-08-2024 11:15:11","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0002758739","Bon=
djock","","02-08-2024 09:34:03","02-08-2024 09:32:58","02-08-2024 09:54:27"=
,"Grid outage, Site went down becaus gen start and stopped due to high temp=
 alarm // He added water and gen manually start","Fanda Brice","Equipment R=
epair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue"=
,"Grid outage, Site went down becaus gen start and stopped due to high temp=
 alarm // He added water and gen manually start","ludivine.ngamaleu@ihstowe=
rs.com","66","02-08-2024 09:34:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0002758573","Yona Hot=
el","","02-08-2024 09:01:01","02-08-2024 08:29:43","02-08-2024 09:15:06","C=
ascaded Incident from TTO2556172","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site U=3D5=
3,2v site on gen Mohamadou of huawei is informed","system","1878","02-08-20=
24 09:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0002758574","Crf-Nkol=
bisson","","02-08-2024 09:01:01","02-08-2024 08:29:43","02-08-2024 09:15:06=
","Cascaded Incident from TTO2556172","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D53,2v site on gen Mohamadou of huawei is informed","system","1878","02-0=
8-2024 09:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0002758570","Nkomkana=
","","02-08-2024 09:01:01","02-08-2024 08:29:43","02-08-2024 09:15:06","Cas=
caded Incident from TTO2556172","","Cascade Outage","Active","Cascade Activ=
e","Cascade Active","No power issue on site U=3D53,2v site on gen Mohamadou=
 of huawei is informed","system","1878","02-08-2024 09:01:01","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_202","NOCINC0002758569","Cite-Ver=
te","","02-08-2024 09:01:01","02-08-2024 08:29:43","02-08-2024 09:15:06","C=
ascaded Incident from TTO2556172","","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","No power issue on site U=3D53,2v site on gen Mohamad=
ou of huawei is informed","system","1878","02-08-2024 09:01:01","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_230","NOCINC0002758572","Meyong-M=
eyeme","","02-08-2024 09:01:01","02-08-2024 08:29:43","02-08-2024 09:15:06"=
,"Cascaded Incident from TTO2556172","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D53,2v site on gen Mohamadou of huawei is informed","system","1878","02-0=
8-2024 09:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0002758576","Entree C=
ite Verte","","02-08-2024 09:01:01","02-08-2024 08:29:43","02-08-2024 09:15=
:06","Cascaded Incident from TTO2556172","Paul BIBOUM","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","No power issue on site U=3D53,2v s=
ite on gen Mohamadou of huawei is informed","system","1878","02-08-2024 09:=
01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0002758575","Dagobert=
","","02-08-2024 09:01:01","02-08-2024 08:29:43","02-08-2024 09:15:06","Cas=
caded Incident from TTO2556172","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue on site U=3D53,=
2v site on gen Mohamadou of huawei is informed","system","1878","02-08-2024=
 09:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_686","NOCINC0002758571","Oyomaban=
g Ecole","","02-08-2024 09:01:01","02-08-2024 08:29:43","02-08-2024 09:15:0=
6","Cascaded Incident from TTO2556172","TIENTCHEU NZETCHIEU GAEL","Cascade =
Outage","Active","Cascade Active","Cascade Active","No power issue on site =
U=3D53,2v site on gen Mohamadou of huawei is informed","system","1878","02-=
08-2024 09:01:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_273","NOCINC0002758568","Nkolbi-B=
oss","","02-08-2024 09:01:01","02-08-2024 08:29:43","02-08-2024 09:15:06","=
Cascaded Incident from TTO2556172","TIENTCHEU NZETCHIEU GAEL","Cascade Outa=
ge","Active","Cascade Active","Cascade Active","No power issue on site U=3D=
53,2v site on gen Mohamadou of huawei is informed","system","1878","02-08-2=
024 09:01:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0002758559","O=
yomabang OCM","IHS_YND_273, IHS_YND_202, IHS_YND_200, IHS_YND_686, IHS_YND_=
230, IHS_YND_271, IHS_YND_232, IHS_YND_286, IHS_YND_543","02-08-2024 08:59:=
02","02-08-2024 08:29:43","02-08-2024 09:15:06","No power issue on site U=
=3D53,2v site on gen Mohamadou of huawei is informed","TIENTCHEU NZETCHIEU =
GAEL","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site U=3D53,2v site on gen Mohamadou of=
 huawei is informed","etienne.itondo@ihstowers.com","1760","02-08-2024 08:5=
9:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002758295","M=
asque","","02-08-2024 07:31:08","02-08-2024 07:27:01","02-08-2024 07:43:04"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V  The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V =
 The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive i=
ssue","dorothy.djantio@ihstowers.com","248","02-08-2024 07:31:08","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0002757786","Nkolfon =
Cimencam","","02-08-2024 03:45:50","02-08-2024 03:29:17","02-08-2024 03:51:=
24","Cascaded Incident from TTO2555259","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid fluctuation site went do=
wn because Gen failled to started due to Grid bad voltage // He bypass the =
Grid and gen manually started ","system","993","02-08-2024 03:45:50","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_791","NOCINC0002757785","Nomayos =
montee Meche","","02-08-2024 03:45:50","02-08-2024 03:29:17","02-08-2024 03=
:51:24","Cascaded Incident from TTO2555259","Fanda Brice","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid fluctuation site went d=
own because Gen failled to started due to Grid bad voltage // He bypass the=
 Grid and gen manually started ","system","993","02-08-2024 03:45:50","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0002757764","Nomayos-=
IHS","","02-08-2024 03:34:50","02-08-2024 03:29:17","02-08-2024 03:43:36","=
Cascaded Incident from TTO2555231","Fanda Brice","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid fluctuation site went down becau=
se Gen failled to started due to Grid bad voltage // He bypass the Grid and=
 gen manually started ","system","333","02-08-2024 03:34:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0002757760","Mandoumb=
a OCM","","02-08-2024 03:34:50","02-08-2024 03:29:17","02-08-2024 03:43:36"=
,"Cascaded Incident from TTO2555231","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid fluctuation site went down=
 because Gen failled to started due to Grid bad voltage // He bypass the Gr=
id and gen manually started ","system","333","02-08-2024 03:34:50","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0002757768","Nkongtoc=
k","","02-08-2024 03:34:50","02-08-2024 03:29:17","02-08-2024 03:43:36","Ca=
scaded Incident from TTO2555231","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid fluctuation site went down bec=
ause Gen failled to started due to Grid bad voltage // He bypass the Grid a=
nd gen manually started ","system","333","02-08-2024 03:34:50","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0002757759","Sous Pre=
fecture","","02-08-2024 03:34:50","02-08-2024 03:29:17","02-08-2024 03:43:3=
6","Cascaded Incident from TTO2555231","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid fluctuation site went down b=
ecause Gen failled to started due to Grid bad voltage // He bypass the Grid=
 and gen manually started ","system","333","02-08-2024 03:34:50","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0002757761","Mbankomo=
 IHS","","02-08-2024 03:34:50","02-08-2024 03:29:17","02-08-2024 03:43:36",=
"Cascaded Incident from TTO2555231","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid fluctuation site went down beca=
use Gen failled to started due to Grid bad voltage // He bypass the Grid an=
d gen manually started ","system","333","02-08-2024 03:34:50","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0002757763","Ebeba","=
","02-08-2024 03:34:50","02-08-2024 03:29:17","02-08-2024 03:43:36","Cascad=
ed Incident from TTO2555231","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Grid fluctuation site went down because Gen=
 failled to started due to Grid bad voltage // He bypass the Grid and gen m=
anually started ","system","333","02-08-2024 03:34:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0002757765","OKOA Pea=
ge","","02-08-2024 03:34:50","02-08-2024 03:29:17","02-08-2024 03:43:36","C=
ascaded Incident from TTO2555231","Fanda Brice","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid fluctuation site went down becaus=
e Gen failled to started due to Grid bad voltage // He bypass the Grid and =
gen manually started ","system","333","02-08-2024 03:34:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0002757767","Angongo"=
,"","02-08-2024 03:34:50","02-08-2024 03:29:17","02-08-2024 03:43:36","Casc=
aded Incident from TTO2555231","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid fluctuation site went down because G=
en failled to started due to Grid bad voltage // He bypass the Grid and gen=
 manually started ","system","333","02-08-2024 03:34:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0002757762","Nkenglik=
ok","","02-08-2024 03:34:50","02-08-2024 03:29:17","02-08-2024 03:43:36","C=
ascaded Incident from TTO2555231","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid fluctuation site went down be=
cause Gen failled to started due to Grid bad voltage // He bypass the Grid =
and gen manually started ","system","333","02-08-2024 03:34:50","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0002757766","Mambine"=
,"","02-08-2024 03:34:50","02-08-2024 03:29:17","02-08-2024 03:43:36","Casc=
aded Incident from TTO2555231","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Grid fluctuation site went down because G=
en failled to started due to Grid bad voltage // He bypass the Grid and gen=
 manually started ","system","333","02-08-2024 03:34:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0002757756","N=
omayos","IHS_YND_314, IHS_YND_367, IHS_YND_791, IHS_YND_695, IHS_YND_348, I=
HS_YND_339, IHS_YND_697, IHS_YND_762, IHS_YND_330, IHS_YND_350, IHS_YND_335=
, IHS_YND_349","02-08-2024 03:32:23","02-08-2024 03:29:17","02-08-2024 03:5=
1:24","Grid fluctuation site went down because Gen failled to started due t=
o Grid bad voltage // He bypass the Grid and gen manually started ","Fanda =
Brice","Grid Supply","Passive","Grid","National Grid - Phase Controller Fau=
lty","Grid fluctuation site went down because Gen failled to started due to=
 Grid bad voltage // He bypass the Grid and gen manually started ","landry.=
etame@ihstowers.com","187","02-08-2024 03:32:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002757332","Messassi=
","","02-08-2024 00:20:20","02-08-2024 00:03:53","02-08-2024 00:10:07","Cas=
caded Incident from TTO2554740","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active //No power issue on site U=3D53,=
7  V  site on Grid  The Tx Fme Symphorien //650257157 is informed.repetitif=
 issue","system","987","02-08-2024 00:20:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002757331","NKOLMEKO=
NG YDE","","02-08-2024 00:20:20","02-08-2024 00:03:53","02-08-2024 00:10:07=
","Cascaded Incident from TTO2554740","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active //No power issue on site U=
=3D53,7  V  site on Grid  The Tx Fme Symphorien //650257157 is informed.rep=
etitif issue","system","987","02-08-2024 00:20:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002757333","Nkolondo=
m","","02-08-2024 00:20:20","02-08-2024 00:03:53","02-08-2024 00:10:07","Ca=
scaded Incident from TTO2554740","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active //No power issue on site U=3D53=
,7  V  site on Grid  The Tx Fme Symphorien //650257157 is informed.repetiti=
f issue","system","987","02-08-2024 00:20:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002757329","O=
lembe","IHS_YND_681, IHS_YND_297, IHS_YND_401, IHS_YND_304","02-08-2024 00:=
19:04","02-08-2024 00:03:53","02-08-2024 00:10:07","Active //No power issue=
 on site U=3D53,7  V  site on Grid  The Tx Fme Symphorien //650257157 is in=
formed.repetitif issue","Fabrice Pouakam","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active //No power iss=
ue on site U=3D53,7  V  site on Grid  The Tx Fme Symphorien //650257157 is =
informed.repetitif issue","landry.etame@ihstowers.com","911","02-08-2024 00=
:19:04","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002757259","Aka=
k-Nkozoa-MTN-IHS","","01-08-2024 23:54:57","01-08-2024 23:51:45","02-08-202=
4 01:43:08","grid outage, site went down because gen failed to start due to=
 AVR faulty// Grid power return","Fabrice Pouakam","Equipment Repair","Pass=
ive","ACDG Gen","ACDG - AVR","grid outage, site went down because gen faile=
d to start due to AVR faulty// Grid power return","denis.mballa@ihstowers.c=
om","194","01-08-2024 23:54:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0002757248","B=
arriere","","01-08-2024 23:49:46","01-08-2024 21:49:40","01-08-2024 21:55:4=
1","No power issue U=3D 52V Site on Gen The TX FME Lionnel /694693436 from =
huawei is informed(Site Swapped by ZTE)","Hyemafo Gildas","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue U=3D 52V Site on Gen The TX FME Lionnel /694693436 from huawei is=
 informed(Site Swapped by ZTE)","landry.etame@ihstowers.com","7207","01-08-=
2024 23:49:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002757141","O=
lembe-Terminus","","01-08-2024 23:12:51","01-08-2024 23:09:40","02-08-2024 =
01:10:48","site went down because 01/04 rectifier dysfonction // He reset t=
he rectifier","Fabrice Pouakam","Equipment Repair","Passive","Rectifier","R=
ectifier Module","site went down because 01/04 rectifier dysfonction // He =
reset the rectifier","landry.etame@ihstowers.com","193","01-08-2024 23:12:5=
1","Sagemcom CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0002757090","B=
yemassi Carrefour","","01-08-2024 22:57:28","01-08-2024 22:02:23","01-08-20=
24 22:03:51","Active// Active: No power issue, site is on Gen with Ubaie=3D=
53.5V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","Paul BIBO=
UM","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active// Active: No power issue, site is on Gen with Ubaie=
=3D53.5V,The tx Fme Hosiah (6 74 00 74 38) from Huawei is informed","landry=
.etame@ihstowers.com","3306","01-08-2024 22:57:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0002757082","M=
endong vallee","","01-08-2024 22:53:43","01-08-2024 20:03:00","01-08-2024 2=
0:10:31","Active //No power issue on site U=3D55,1  V  site on Grid Tthe Te=
am Christian // 659365744 from ZTE is working on site","Fanda Brice","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","Active //No power issue on site U=3D55,1  V  site on Grid Tthe Team C=
hristian // 659365744 from ZTE is working on site","landry.etame@ihstowers.=
com","10245","01-08-2024 22:53:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002757063","M=
asque","","01-08-2024 22:46:48","01-08-2024 22:36:43","01-08-2024 22:37:49"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V   The TX FME  Elo=
undou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V=
   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive=
 issue","landry.etame@ihstowers.com","605","01-08-2024 22:46:48","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002756262","Afanoya"=
,"","01-08-2024 21:33:50","01-08-2024 21:30:07","01-08-2024 21:36:39","Casc=
aded Incident from TTO2553558","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // grid return","system","223","01-08-202=
4 21:33:50","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002756252","Aha=
la","IHS_YND_313","01-08-2024 21:32:12","01-08-2024 21:30:07","01-08-2024 2=
1:36:39","Grid outage, site went down before gen start due to poor battery =
backup // grid return","Hyemafo Gildas","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site went down before=
 gen start due to poor battery backup // grid return","emmanuel.ghani@ihsto=
wers.com","125","01-08-2024 21:32:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002756248","NKOLMEKO=
NG YDE","","01-08-2024 21:32:00","01-08-2024 21:27:14","01-08-2024 21:30:29=
","Cascaded Incident from TTO2553549","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active //No power issue on site U=
=3D53,7  V  site on Grid  The Tx Fme Symphorien //650257157 is informed","s=
ystem","286","01-08-2024 21:32:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002756250","Nkolondo=
m","","01-08-2024 21:32:00","01-08-2024 21:27:14","01-08-2024 21:30:29","Ca=
scaded Incident from TTO2553549","Fabrice Pouakam","Cascade Outage","Active=
","Cascade Active","Cascade Active","Active //No power issue on site U=3D53=
,7  V  site on Grid  The Tx Fme Symphorien //650257157 is informed","system=
","286","01-08-2024 21:32:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002756249","Messassi=
","","01-08-2024 21:32:00","01-08-2024 21:27:14","01-08-2024 21:30:29","Cas=
caded Incident from TTO2553549","Fabrice Pouakam","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active //No power issue on site U=3D53,=
7  V  site on Grid  The Tx Fme Symphorien //650257157 is informed","system"=
,"286","01-08-2024 21:32:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002756244","O=
lembe","IHS_YND_681, IHS_YND_297, IHS_YND_304","01-08-2024 21:30:29","01-08=
-2024 21:27:14","01-08-2024 21:30:29","Active //No power issue on site U=3D=
53,7  V  site on Grid  The Tx Fme Symphorien //650257157 is informed","Fabr=
ice Pouakam","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active //No power issue on site U=3D53,7  V  site =
on Grid  The Tx Fme Symphorien //650257157 is informed","joelle.ekessi@ihst=
owers.com","197","01-08-2024 21:30:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002756051","E=
lig-Edzoa","","01-08-2024 21:01:49","01-08-2024 20:55:42","01-08-2024 20:58=
:23","No Power issue on site ,site on Grid with Ubaie=3D54,6 V The Tx FME A=
rmand Nguetsa // 699949553// From  Huawei is informed(Site Swapped by ZTE)"=
,"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No Power issue on site ,site on Grid with Ubaie=3D54,6 V Th=
e Tx FME Armand Nguetsa // 699949553// From  Huawei is informed(Site Swappe=
d by ZTE)","joelle.ekessi@ihstowers.com","368","01-08-2024 21:01:49","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0002756028","O=
bobogo","","01-08-2024 20:56:58","01-08-2024 20:35:54","01-08-2024 20:40:31=
","No power issue site on grid with U=3D54v Notice that we have dysjunction=
 at OCM equipements RM Alain(691144423) from Huawei is informed","MINKA NIC=
OLAS","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue site on grid with U=3D54v Notice that we h=
ave dysjunction at OCM equipements RM Alain(691144423) from Huawei is infor=
med","joelle.ekessi@ihstowers.com","1265","01-08-2024 20:56:58","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0002756014","B=
arriere","","01-08-2024 20:53:28","01-08-2024 19:27:21","01-08-2024 21:26:0=
7","Grid fluctuation site went down because Gen failled to started due to G=
rid bad voltage // He bypass the Grid and site on Gen(Site Swapped by ZTE)"=
,"Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Con=
troller Faulty","Grid fluctuation site went down because Gen failled to sta=
rted due to Grid bad voltage // He bypass the Grid and site on Gen(Site Swa=
pped by ZTE)","joelle.ekessi@ihstowers.com","5168","01-08-2024 20:53:28","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002755785","N=
koabang2","","01-08-2024 20:25:21","01-08-2024 19:41:14","01-08-2024 21:52:=
37","Active//No power issue on site ;site on Grid with Ubaie =3D53,3 V The =
Team clauvis// 696678889 from ZTE is working on site","Mba Lazare Herve","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue on site ;site on Grid with Ubaie =3D53,3 V=
 The Team clauvis// 696678889 from ZTE is working on site","joelle.ekessi@i=
hstowers.com","2649","01-08-2024 20:25:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002755099","ELOUMDEM=
 CARRIERE 2","","01-08-2024 19:25:10","01-08-2024 19:16:58","01-08-2024 19:=
41:50","Cascaded Incident from TTO2552224","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down be=
cause gen failed to started due to Main Gen faulty // Grid power return","s=
ystem","492","01-08-2024 19:25:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002755098","Eto koss=
 Yde","","01-08-2024 19:25:10","01-08-2024 19:16:58","01-08-2024 19:41:50",=
"Cascaded Incident from TTO2552224","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because g=
en failed to started due to Main Gen faulty // Grid power return","system",=
"492","01-08-2024 19:25:10","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002755069","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","01-08-2024 19:19:04","01-08-2024 19:16=
:58","01-08-2024 19:41:50","Grid outage site went down because gen failed t=
o started due to Main Gen faulty // Grid power return","Fanda Brice","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid outage si=
te went down because gen failed to started due to Main Gen faulty // Grid p=
ower return","emmanuel.ghani@ihstowers.com","126","01-08-2024 19:19:04","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0002754847","B=
arriere","","01-08-2024 18:29:50","01-08-2024 18:04:46","01-08-2024 18:58:5=
6","site went down gen failed to start due to grid bad voltage // He make t=
he bridge on good phases (Site Swapped By ZTE)","Hyemafo Gildas","Grid Supp=
ly","Passive","Grid","National Grid - Phase Controller Faulty","site went d=
own gen failed to start due to grid bad voltage // He make the bridge on go=
od phases (Site Swapped By ZTE)","joelle.ekessi@ihstowers.com","1505","01-0=
8-2024 18:29:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0002754835","N=
kolbisson usine des eaux","","01-08-2024 18:27:53","01-08-2024 18:01:50","0=
1-08-2024 18:55:21","Active: no power issue, site is on grid with Ubaie=3D5=
3V, Paul (699029796) from OMNIACOM working on site","TIENTCHEU NZETCHIEU GA=
EL","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active: no power issue, site is on grid with Ubaie=3D53V, P=
aul (699029796) from OMNIACOM working on site","joelle.ekessi@ihstowers.com=
","1564","01-08-2024 18:27:53","Sagemcom CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0002754561","Nko=
mo","","01-08-2024 17:18:38","01-08-2024 17:05:31","01-08-2024 17:27:43","s=
ite went down due to 02/05 rectifiers Hanging  //He reset rectifiers,site o=
n grid (Site Swapped by ZTE)","Mba Lazare Herve","Equipment Repair","Passiv=
e","Rectifier","Rectifier Module","site went down due to 02/05 rectifiers H=
anging  //He reset rectifiers,site on grid (Site Swapped by ZTE)","emmanuel=
.ghani@ihstowers.com","788","01-08-2024 17:18:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0002754473","Mballa 4=
","","01-08-2024 17:06:10","01-08-2024 16:59:06","01-08-2024 17:09:53","Cas=
caded Incident from TTO2551539","Delor Telezing","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active: No power issue, site is on grid =
with Ubaie=3D54V, ","system","424","01-08-2024 17:06:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0002754476","Emana ly=
cee 2","","01-08-2024 17:06:10","01-08-2024 16:59:06","01-08-2024 17:09:53"=
,"Cascaded Incident from TTO2551539","Fabrice Pouakam","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active: No power issue, site is on=
 grid with Ubaie=3D54V, ","system","424","01-08-2024 17:06:10","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0002754474","EMANA BI=
LICK CITY","","01-08-2024 17:06:10","01-08-2024 16:59:06","01-08-2024 17:09=
:53","Cascaded Incident from TTO2551539","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active: No power issue, site i=
s on grid with Ubaie=3D54V, ","system","424","01-08-2024 17:06:10","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0002754475","Messassi=
 okolo","","01-08-2024 17:06:10","01-08-2024 16:59:06","01-08-2024 17:09:53=
","Cascaded Incident from TTO2551539","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active: No power issue, site is o=
n grid with Ubaie=3D54V, ","system","424","01-08-2024 17:06:10","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0002754467","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_279, IHS_YND_685","01-08-2024 17:0=
4:50","01-08-2024 16:59:06","01-08-2024 17:09:53","Active: No power issue, =
site is on grid with Ubaie=3D54V, The Team Tx TIOTSOP Edmond(696341933) fro=
m Oniom working on site(Swapp)  ","Fabrice Pouakam","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No =
power issue, site is on grid with Ubaie=3D54V, The Team Tx TIOTSOP Edmond(6=
96341933) from Oniom working on site(Swapp)  ","joelle.ekessi@ihstowers.com=
","345","01-08-2024 17:04:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002754326","M=
asque","","01-08-2024 16:30:15","01-08-2024 16:23:11","01-08-2024 16:33:21"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V   The TX FME  Elo=
undou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V=
   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive=
 issue","joelle.ekessi@ihstowers.com","427","01-08-2024 16:30:15","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0002754306","E=
ssomba","","01-08-2024 16:27:06","01-08-2024 16:22:01","01-08-2024 17:15:35=
","Grid outage, site went down because gen failed to start due to battery G=
E faulty// Gen  manually started with external battery","Mba Lazare Herve",=
"Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid ou=
tage, site went down because gen failed to start due to battery GE faulty//=
 Gen  manually started with external battery","joelle.ekessi@ihstowers.com"=
,"308","01-08-2024 16:27:06","Sagemcom CMR"
"Closed Complete","Site Down","T1551","IHS_YND_316","NOCINC0002754270","Aka=
k-Nkozoa-MTN-IHS","","01-08-2024 16:20:43","01-08-2024 16:13:07","01-08-202=
4 19:46:42","grid outage, site went down because gen failed to start due to=
 AVR faulty// MDG OF 20 KVA has deployed","Fabrice Pouakam","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - AVR","grid outage, site went down because =
gen failed to start due to AVR faulty// MDG OF 20 KVA has deployed","emmanu=
el.ghani@ihstowers.com","458","01-08-2024 16:20:43","Sagemcom CMR"
"Closed Complete","Site Down","T0957","IHS_YND_715","NOCINC0002754239","Odz=
a Minkan IHS","","01-08-2024 16:11:27","01-08-2024 16:02:23","01-08-2024 17=
:09:33","site went down due to disjunction Cb(3*63A) in DC BOX// He reamed =
Cb(3*63A), site on grid","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Circuit Breaker Tripped","site went down due to disjunction Cb(=
3*63A) in DC BOX// He reamed Cb(3*63A), site on grid","emmanuel.ghani@ihsto=
wers.com","546","01-08-2024 16:11:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002754233","ELOUMDEM=
 CARRIERE","","01-08-2024 16:10:10","01-08-2024 16:00:30","01-08-2024 16:13=
:12","Cascaded Incident from TTO2551256","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage, site went down bef=
ore gen start due to poor battery backup // grid return","system","580","01=
-08-2024 16:10:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002754234","Afanoya"=
,"","01-08-2024 16:10:10","01-08-2024 16:00:30","01-08-2024 16:13:12","Casc=
aded Incident from TTO2551256","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down before gen=
 start due to poor battery backup // grid return","system","580","01-08-202=
4 16:10:10","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002754225","Aha=
la","IHS_YND_767, IHS_YND_313","01-08-2024 16:07:34","01-08-2024 16:00:30",=
"01-08-2024 16:13:12","Grid outage, site went down before gen start due to =
poor battery backup // grid return","Hyemafo Gildas","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen=
t down before gen start due to poor battery backup // grid return","emmanue=
l.ghani@ihstowers.com","426","01-08-2024 16:07:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0002754086","Lobo OCM=
","","01-08-2024 15:50:50","01-08-2024 15:45:33","01-08-2024 15:51:21","Cas=
caded Incident from TTO2551087","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automaticaly","sy=
stem","317","01-08-2024 15:50:50","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002754073","N=
KOMEKUI OCM","IHS_YND_341","01-08-2024 15:49:37","01-08-2024 15:45:33","01-=
08-2024 15:51:21","Grid outage, site went down before gen start due to poor=
 battery backup // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 outage, site went down before gen start due to poor battery backup // Gen =
start automaticaly","joelle.ekessi@ihstowers.com","246","01-08-2024 15:49:3=
7","Sagemcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0002753972","Tam=
tam Weekend","","01-08-2024 15:27:58","01-08-2024 15:15:53","01-08-2024 15:=
18:07","Active //No power issue on site U=3D54,8 V  site on Grid The TX FME=
 Hosiah/674007438 /Huawei is informed","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active =
//No power issue on site U=3D54,8 V  site on Grid The TX FME Hosiah/6740074=
38 /Huawei is informed","emmanuel.ghani@ihstowers.com","729","01-08-2024 15=
:27:58","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0002753966","Car=
refour Simbock","","01-08-2024 15:27:03","01-08-2024 15:15:16","01-08-2024 =
15:18:09","Active //No power issue on site U=3D52,2 V  site on Grid The TX =
fme MBA haosiah/ 674007438  from huawei is informed","Hyemafo Gildas","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active //No power issue on site U=3D52,2 V  site on Grid The TX fme =
MBA haosiah/ 674007438  from huawei is informed","emmanuel.ghani@ihstowers.=
com","709","01-08-2024 15:27:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_478","IHS_YND_568","NOCINC0002753916","A=
nguissa New","","01-08-2024 15:15:13","01-08-2024 15:12:07","01-08-2024 16:=
20:18","site went down due to Cb(10A) of extration of the PWC  faulty// He =
bypassed Cb(10A), site on grid","MINKA NICOLAS","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Circuit Breaker Issue","site went down d=
ue to Cb(10A) of extration of the PWC  faulty// He bypassed Cb(10A), site o=
n grid","joelle.ekessi@ihstowers.com","188","01-08-2024 15:15:13","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0002753659","Nyom OCM=
","","01-08-2024 13:58:40","01-08-2024 12:22:01","01-08-2024 15:45:15","Cas=
caded Incident from TTO2550179","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site down due to work of Bernard Ata=
ngana IHS","system","5799","01-08-2024 13:58:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002753658","NKOLMEKO=
NG YDE","","01-08-2024 13:58:40","01-08-2024 12:22:01","01-08-2024 15:45:15=
","Cascaded Incident from TTO2550179","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site down due to work of Berna=
rd Atangana IHS","system","5799","01-08-2024 13:58:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002753660","Nkolondo=
m","","01-08-2024 13:58:40","01-08-2024 12:22:01","01-08-2024 15:45:15","Ca=
scaded Incident from TTO2550179","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site down due to work of Bernard At=
angana IHS","system","5799","01-08-2024 13:58:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_706","NOCINC0002753583","Mbankomo=
 CAF","","01-08-2024 13:45:18","01-08-2024 13:40:11","01-08-2024 13:49:41",=
"site went down due to work BRICE Fanda/657108549/SAGEMCOM/do the PM on sit=
e//End of Work","Fanda Brice","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Battery Low","site went down due to work BRICE Fanda/65710=
8549/SAGEMCOM/do the PM on site//End of Work","ange.kongo@ihstowers.com","3=
08","01-08-2024 13:45:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_174","NOCINC0002753499","Carrefou=
rt Nkomo","","01-08-2024 13:30:40","01-08-2024 13:22:34","01-08-2024 13:36:=
35","Grid outage, Site went down becaus gen start and stopped due to hight =
temp alarm // He added water and gen manually start  (site swapped by ZTE)"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High En=
gine Temp - Coolant Level Issue","Grid outage, Site went down becaus gen st=
art and stopped due to hight temp alarm // He added water and gen manually =
start  (site swapped by ZTE)","ange.kongo@ihstowers.com","487","01-08-2024 =
13:30:40","Sagemcom CMR"
"Closed Complete","Site Down","T1572","IHS_YND_117","NOCINC0002753436","Nko=
mo stade","","01-08-2024 13:12:40","01-08-2024 13:02:33","01-08-2024 13:43:=
32","grid outage, site went down because gen failed due to static charger f=
aulty// grid return (static charger to be replaced)","Mba Lazare Herve","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator","grid out=
age, site went down because gen failed due to static charger faulty// grid =
return (static charger to be replaced)","ange.kongo@ihstowers.com","607","0=
1-08-2024 13:12:40","Sagemcom CMR"
"Closed Complete","Site Down","T1620","IHS_YND_405","NOCINC0002753379","Saa=
","","01-08-2024 12:58:33","01-08-2024 12:52:44","01-08-2024 13:09:28","No =
power issue on site U=3D53v site on grid Gregoire of Huawei is working on s=
ite","Parker Tchoup","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","No power issue on site U=3D53v site on gri=
d Gregoire of Huawei is working on site","ange.kongo@ihstowers.com","351","=
01-08-2024 12:58:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_212","IHS_YND_178","NOCINC0002753340","E=
mombo","","01-08-2024 12:46:31","01-08-2024 12:41:17","01-08-2024 12:54:00"=
,"Active, no power issue, site on grid with U=3D54,9V Team ALENOU /65584657=
8/ From ZTE is working on site","Mba Lazare Herve","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no p=
ower issue, site on grid with U=3D54,9V Team ALENOU /655846578/ From ZTE is=
 working on site","ludivine.ngamaleu@ihstowers.com","314","01-08-2024 12:46=
:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0002753289","Ekombiti=
e","","01-08-2024 12:33:20","01-08-2024 12:22:01","01-08-2024 15:45:15","Ca=
scaded Incident from TTO2550179","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site down due to work of Bernard At=
angana IHS","system","679","01-08-2024 12:33:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0002753290","Olembe-T=
erminus","","01-08-2024 12:33:20","01-08-2024 12:22:01","01-08-2024 15:45:1=
5","Cascaded Incident from TTO2550179","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site down due to work of Bern=
ard Atangana IHS","system","679","01-08-2024 12:33:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_280","NOCINC0002753291","Messassi=
 2","","01-08-2024 12:33:20","01-08-2024 12:22:01","01-08-2024 15:45:15","C=
ascaded Incident from TTO2550179","Fabrice Pouakam","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Site down due to work of Bernard A=
tangana IHS","system","679","01-08-2024 12:33:20","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0002753281","Ole=
mbe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_303, IHS_YND_280, IHS_=
YND_304","01-08-2024 12:28:11","01-08-2024 12:22:01","01-08-2024 15:45:15",=
"Site went down due to work (Supervisor IHS  Bernard//677548315  working on=
 site )// end of work power issue resolved at 03:45 PM,But site remaim down=
 after power reset done ,The Tx Fme Symphorien //65","Fabrice Pouakam","Ins=
tallation Activity","Passive","Planned Activity","Installation Activity","S=
ite went down due to work (Supervisor IHS  Bernard//677548315  working on s=
ite )// end of work power issue resolved at 03:45 PM,But site remaim down a=
fter power reset done ,The Tx Fme Symphorien //650257157 is informed","ange=
.kongo@ihstowers.com","373","01-08-2024 12:28:11","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0002753278","I=
mm-Olympique","","01-08-2024 12:27:25","01-08-2024 12:09:21","01-08-2024 13=
:38:39","Grid outage, site went down because gen fail to start due to power=
 cable of gen thef stolen (site swapped by ZTE)","Paul BIBOUM","Site Asset =
Theft","Theft","Theft","AC Cable Stolen","Grid outage, site went down becau=
se gen fail to start due to power cable of gen thef stolen (site swapped by=
 ZTE)","ludivine.ngamaleu@ihstowers.com","1085","01-08-2024 12:27:25","Sage=
mcom CMR"
"Cancelled","Warning","CTR_387","IHS_YND_276","NOCINC0002753267","Ekombitie=
","","01-08-2024 12:23:23","","","","Fabrice Pouakam","","","","","","ludiv=
ine.ngamaleu@ihstowers.com","126","01-08-2024 12:23:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0002753264","N=
GONA","","01-08-2024 12:22:02","01-08-2024 12:13:58","01-08-2024 12:40:24",=
"No power issue on site U=3D54v site is on grid Team/Claude/687648830/ZTE w=
orking on site","Mba Lazare Herve","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
4v site is on grid Team/Claude/687648830/ZTE working on site","ludivine.nga=
maleu@ihstowers.com","485","01-08-2024 12:22:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0002753040","S=
apeur Mimboman","","01-08-2024 11:33:54","01-08-2024 11:27:50","01-08-2024 =
11:37:08","No power issue on site U=3D54,3v site on grid Team/Prince/654153=
956/ZTE working on site","Mba Lazare Herve","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D54,3v site on grid Team/Prince/654153956/ZTE working on site","ludi=
vine.ngamaleu@ihstowers.com","366","01-08-2024 11:33:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002752882","N=
kolo II New","","01-08-2024 10:51:29","01-08-2024 10:44:25","01-08-2024 10:=
54:25","No power issue on site U=3D50,5v site on grid Team/Brice Zakaria Ga=
ladji/695023235/ZTE working on site","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site U=3D50,5v site on grid Team/Brice Zakaria Galadji/695023235=
/ZTE working on site","ludivine.ngamaleu@ihstowers.com","425","01-08-2024 1=
0:51:29","Sagemcom CMR"
"Closed Complete","Site Down","T1618","IHS_YND_305","NOCINC0002752846","NYO=
M","","01-08-2024 10:36:07","01-08-2024 10:30:55","01-08-2024 11:30:36","No=
 power issue on site U=3D54,5v site on grid Team Cedric/657836700 / I-Eng w=
orking on site normalisation  huawei","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site U=3D54,5v site on grid Team Cedric/657836700 / I-Eng workin=
g on site normalisation  huawei","ange.kongo@ihstowers.com","313","01-08-20=
24 10:36:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0002752833","N=
kolda","","01-08-2024 10:32:42","01-08-2024 10:02:38","01-08-2024 11:25:36"=
,"Grid outage site went down because Gen overloaded(old gen) 17,5Kva //he r=
educe the load (power limitation at 7kilo)(site swapped by ZTE)","Albran By=
orel","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outag=
e site went down because Gen overloaded(old gen) 17,5Kva //he reduce the lo=
ad (power limitation at 7kilo)(site swapped by ZTE)","ludivine.ngamaleu@ihs=
towers.com","1806","01-08-2024 10:32:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0002752815","M=
imboman-Ecole","","01-08-2024 10:27:07","01-08-2024 10:23:02","01-08-2024 1=
1:18:48","No power issue on site U=3D52,5v site on grid Team Austin/ 670581=
123/ZTE working on site","Mba Lazare Herve","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on s=
ite U=3D52,5v site on grid Team Austin/ 670581123/ZTE working on site","lud=
ivine.ngamaleu@ihstowers.com","247","01-08-2024 10:27:07","Sagemcom CMR"
"Closed Complete","Site Down","T0211","IHS_YND_393","NOCINC0002752662","Eze=
zang","","01-08-2024 09:35:19","01-08-2024 09:30:10","01-08-2024 09:37:10",=
"site went down due to work Ulrich/SAGEMCOM/656072680/do the PM on site//En=
d of work","Parker Tchoup","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","site went down due to work Ulrich/SAGEMCOM/6560=
72680/do the PM on site//End of work","ange.kongo@ihstowers.com","371","01-=
08-2024 09:35:19","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0002752627","Ema=
na","","01-08-2024 09:21:56","01-08-2024 09:10:44","01-08-2024 20:55:46","A=
ctive, No power issue, site on grid with U=3D56V Team okolo /695684963/ Fro=
m h-teli is working on site","Fabrice Pouakam","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, No power=
 issue, site on grid with U=3D56V Team okolo /695684963/ From h-teli is wor=
king on site","ange.kongo@ihstowers.com","672","01-08-2024 09:21:56","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_255","IHS_YND_286","NOCINC0002752598","D=
agobert","","01-08-2024 09:08:57","01-08-2024 09:00:48","01-08-2024 11:52:5=
3","No power issue on site U=3D54,5v site on grid Team Yves/699127444/ZTE w=
orking on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on si=
te U=3D54,5v site on grid Team Yves/699127444/ZTE working on site","ludivin=
e.ngamaleu@ihstowers.com","490","01-08-2024 09:08:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0002752497","L=
eboudi","IHS_YND_712","01-08-2024 08:30:12","01-08-2024 08:20:06","01-08-20=
24 11:29:38","No power issue on site U=3D54v site on grid site down because=
 is impacted by Nkolbisson nodal and not managing by IHS","TIENTCHEU NZETCH=
IEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","No power issue on site U=3D54v site on grid site down=
 because is impacted by Nkolbisson nodal and not managing by IHS","ludivine=
.ngamaleu@ihstowers.com","608","01-08-2024 08:30:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_676","IHS_YND_712","NOCINC0002752491","N=
kolkoumou OCM","","01-08-2024 08:26:16","01-08-2024 08:20:06","01-08-2024 1=
0:04:02","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade A=
ctive","Cascade Active","No power issue on site U=3D54v site on grid site d=
own because is impacted by Nkolbisson nodal and not managing by IHS","ludiv=
ine.ngamaleu@ihstowers.com","5874","01-08-2024 08:26:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002752189","M=
asque","","01-08-2024 06:22:57","01-08-2024 06:19:52","01-08-2024 06:42:29"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V   The TX FME  Elo=
undou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V=
   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive=
 issue","ludivine.ngamaleu@ihstowers.com","185","01-08-2024 06:22:57","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_685","NOCINC0002751657","Emana ly=
cee 2","","01-08-2024 01:32:50","01-08-2024 01:20:32","01-08-2024 01:25:36"=
,"Cascaded Incident from TTO2548387","Fabrice Pouakam","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active","Active: no power issue, site is on=
 grid with Ubaie=3D53,5V, The Team Tx TIOTSOP Edmond(696341933) from SNEF  =
WORKING ON SITE snef edmond (Swapp)  ","system","738","01-08-2024 01:32:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_274","NOCINC0002751655","Emana Ly=
cee","","01-08-2024 01:32:50","01-08-2024 01:20:32","01-08-2024 01:25:36","=
Cascaded Incident from TTO2548387","Fabrice Pouakam","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","Active: no power issue, site is on g=
rid with Ubaie=3D53,5V, The Team Tx TIOTSOP Edmond(696341933) from SNEF  WO=
RKING ON SITE snef edmond (Swapp)  ","system","738","01-08-2024 01:32:50","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_279","NOCINC0002751656","Messassi=
 okolo","","01-08-2024 01:32:50","01-08-2024 01:20:32","01-08-2024 01:25:36=
","Cascaded Incident from TTO2548387","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active: no power issue, site is o=
n grid with Ubaie=3D53,5V, The Team Tx TIOTSOP Edmond(696341933) from SNEF =
 WORKING ON SITE snef edmond (Swapp)  ","system","738","01-08-2024 01:32:50=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_523","NOCINC0002751654","EMANA BI=
LICK CITY","","01-08-2024 01:32:50","01-08-2024 01:20:32","01-08-2024 01:25=
:36","Cascaded Incident from TTO2548387","Fabrice Pouakam","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","Active: no power issue, site i=
s on grid with Ubaie=3D53,5V, The Team Tx TIOTSOP Edmond(696341933) from SN=
EF  WORKING ON SITE snef edmond (Swapp)  ","system","738","01-08-2024 01:32=
:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_242","NOCINC0002751653","Mballa 4=
","","01-08-2024 01:32:50","01-08-2024 01:20:32","01-08-2024 01:25:36","Cas=
caded Incident from TTO2548387","Delor Telezing","Cascade Outage","Active",=
"Cascade Active","Cascade Active","Active: no power issue, site is on grid =
with Ubaie=3D53,5V, The Team Tx TIOTSOP Edmond(696341933) from SNEF  WORKIN=
G ON SITE snef edmond (Swapp)  ","system","738","01-08-2024 01:32:50","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_213","IHS_YND_247","NOCINC0002751645","O=
kolo","IHS_YND_242, IHS_YND_523, IHS_YND_274, IHS_YND_279, IHS_YND_685","01=
-08-2024 01:29:41","01-08-2024 01:20:32","01-08-2024 01:25:36","Active: no =
power issue, site is on grid with Ubaie=3D53,5V, The Team Tx TIOTSOP Edmond=
(696341933) from SNEF  WORKING ON SITE snef edmond (Swapp)  ","Fabrice Poua=
kam","Customer Equipment Failure","Active","Active Equipment Failure","BTS/=
TX Fault Alarm","Active: no power issue, site is on grid with Ubaie=3D53,5V=
, The Team Tx TIOTSOP Edmond(696341933) from SNEF  WORKING ON SITE snef edm=
ond (Swapp)  ","kamga.virgile@ihstowers.com","550","01-08-2024 01:29:41","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0002751176","A=
wae-Yde","","31-07-2024 22:54:13","31-07-2024 22:16:06","31-07-2024 22:25:5=
3","Site on Grid. Site went down due to 1/3 rectifier disfunctionned //Site=
 stabilized and Site On Grid (site swapped by ZTE)","Albran Byorel","Equipm=
ent Repair","Passive","Rectifier","Rectifier Module","Site on Grid. Site we=
nt down due to 1/3 rectifier disfunctionned //Site stabilized and Site On G=
rid (site swapped by ZTE)","kamga.virgile@ihstowers.com","2287","31-07-2024=
 22:54:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0002750847","E=
kie sud","","31-07-2024 21:50:10","31-07-2024 16:49:51","31-07-2024 16:50:5=
6","No power issue site on grid with U=3D53,4v Notice that we have disjunct=
ion at ZTE Equiments RM Alain from Huawei is informed(site swapped by ZTE)"=
,"Albran Byorel","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","No power issue site on grid with U=3D53,4v Not=
ice that we have disjunction at ZTE Equiments RM Alain from Huawei is infor=
med(site swapped by ZTE)","kouoh.jean@ihstowers.com","18020","31-07-2024 21=
:50:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0002750821","M=
EHANDAN","","31-07-2024 21:46:41","31-07-2024 21:13:30","31-07-2024 21:18:0=
8","Site went down because the Cb(63A) of PWC dysjuncted due to increased s=
ite load// he made the bridge of CB(80*63A) (Site already  swapping by ZTE =
) ","Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Circuit Breaker Issue","Site went down because the Cb(63A) of PWC dy=
sjuncted due to increased site load// he made the bridge of CB(80*63A) (Sit=
e already  swapping by ZTE ) ","kouoh.jean@ihstowers.com","1991","31-07-202=
4 21:46:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0002750801","M=
endong vallee","","31-07-2024 21:43:57","31-07-2024 21:21:00","31-07-2024 2=
1:25:34","No power issue site on grid with U=3D54,3v,Notice that we have di=
sjunction at OCM Equipements Hosiah from Huawei is informed","Fanda Brice",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","No power issue site on grid with U=3D54,3v,Notice that we have =
disjunction at OCM Equipements Hosiah from Huawei is informed","kouoh.jean@=
ihstowers.com","1378","31-07-2024 21:43:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0002750793","O=
bobogo","","31-07-2024 21:42:09","31-07-2024 20:59:02","31-07-2024 21:00:30=
","No power issue site on grid with U=3D54v Notice that we have dysjunction=
 at OCM equipements RM Alain(691144423) from Huawei is informed(site swappe=
d by ZTE)","MINKA NICOLAS","Customer Equipment Failure","Active","Active Eq=
uipment Failure","Affected by 3rd Party Site","No power issue site on grid =
with U=3D54v Notice that we have dysjunction at OCM equipements RM Alain(69=
1144423) from Huawei is informed(site swapped by ZTE)","kouoh.jean@ihstower=
s.com","2587","31-07-2024 21:42:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0002750773","N=
kolafeme","","31-07-2024 21:39:17","31-07-2024 20:54:28","31-07-2024 20:57:=
50","Active: no power issue, site is on grid with Ubaie=3D54,5V; Notice tha=
t we have dysjunction at OCM equipements RM Alain from Huawei is informed",=
"TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","Active: no power issue, site is on g=
rid with Ubaie=3D54,5V; Notice that we have dysjunction at OCM equipements =
RM Alain from Huawei is informed","kouoh.jean@ihstowers.com","2689","31-07-=
2024 21:39:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002750765","N=
koabang2","","31-07-2024 21:37:35","31-07-2024 20:34:26","31-07-2024 20:40:=
39"," Active: no power issue, site is on grid with Ubaie=3D53,7V, Notice th=
at we have dysjunction at OCM equipements, RM Alain frm Huawei is informed"=
,"Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm"," Active: no power issue, site is on grid wi=
th Ubaie=3D53,7V, Notice that we have dysjunction at OCM equipements, RM Al=
ain frm Huawei is informed","kouoh.jean@ihstowers.com","3790","31-07-2024 2=
1:37:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0002750639","E=
ssomba","","31-07-2024 21:14:26","31-07-2024 21:05:14","31-07-2024 21:10:12=
","No power issue site on grid with U=3D54,1v Notice that we have dysjuncti=
on at OCM equipements RM Alain(691144423) from Huawei is informed","Mba Laz=
are Herve","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","No power issue site on grid with U=3D54,1v Notice th=
at we have dysjunction at OCM equipements RM Alain(691144423) from Huawei i=
s informed","kouoh.jean@ihstowers.com","552","31-07-2024 21:14:26","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002750344","ELOUMDEM=
 CARRIERE 2","","31-07-2024 20:09:10","31-07-2024 20:06:05","31-07-2024 20:=
10:14","Cascaded Incident from TTO2546905","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went daown b=
ecause Main Gen faulty// MDG of 20kva has  deployed","system","185","31-07-=
2024 20:09:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002750343","Eto koss=
 Yde","","31-07-2024 20:09:10","31-07-2024 20:06:05","31-07-2024 20:10:14",=
"Cascaded Incident from TTO2546905","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went daown because =
Main Gen faulty// MDG of 20kva has  deployed","system","185","31-07-2024 20=
:09:10","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002750306","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","31-07-2024 20:08:32","31-07-2024 20:06=
:05","31-07-2024 20:10:14","Grid outage site went daown because Main Gen fa=
ulty// MDG of 20kva has  deployed","Fanda Brice","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - Generator Faulty","Grid outage site went daown becaus=
e Main Gen faulty// MDG of 20kva has  deployed","denis.mballa@ihstowers.com=
","148","31-07-2024 20:08:32","Sagemcom CMR"
"Closed Complete","Site Down","T3153","IHS_YND_280","NOCINC0002750290","Mes=
sassi 2","","31-07-2024 20:01:21","31-07-2024 19:58:04","31-07-2024 20:58:5=
2","Site went down because gen ran until fuel shortage//Refueling done","Fa=
brice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Site went =
down because gen ran until fuel shortage//Refueling done","denis.mballa@ihs=
towers.com","199","31-07-2024 20:01:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002750284","E=
mana","","31-07-2024 20:00:07","31-07-2024 19:53:53","01-08-2024 00:33:30",=
"Grid outage//Grid return","","Grid Supply","Passive","Grid","National Grid=
 - Grid Outage Issue","Grid outage//Grid return","kouoh.jean@ihstowers.com"=
,"376","31-07-2024 20:00:07","Sagemcom CMR"
"Closed Complete","Site Down","T3240","IHS_YND_771","NOCINC0002750074","Jou=
vence Mbenda","","31-07-2024 19:27:44","31-07-2024 19:19:18","31-07-2024 20=
:08:41","Grid outage, site went down because Gen started and stopped due to=
 ""high temp"" alarm //He added water and Gen manually started","Hyemafo Gi=
ldas","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Co=
olant Level Issue","Grid outage, site went down because Gen started and sto=
pped due to ""high temp"" alarm //He added water and Gen manually started",=
"denis.mballa@ihstowers.com","508","31-07-2024 19:27:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002749897","M=
asque","","31-07-2024 18:48:13","31-07-2024 18:40:08","31-07-2024 19:45:57"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V   The TX FME  Elo=
undou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V=
   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive=
 issue","kouoh.jean@ihstowers.com","486","31-07-2024 18:48:13","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0002749792","Y=
de-M-Central","","31-07-2024 18:26:01","31-07-2024 17:59:52","31-07-2024 21=
:10:32","Grid outage no space to deploy // Grid power return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy // Grid power return","kouoh.jean@ihstowers.com","1570","31-0=
7-2024 18:26:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0002749416","B=
astos Bir","","31-07-2024 17:20:19","31-07-2024 17:10:52","31-07-2024 17:26=
:18","ACTIVE No power isue U=3D 54.5V site on Grid TX fme Eloundoun /652586=
578/ from huawei is informed","Mboua Thierry","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power i=
sue U=3D 54.5V site on Grid TX fme Eloundoun /652586578/ from huawei is inf=
ormed","kouoh.jean@ihstowers.com","569","31-07-2024 17:20:19","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_591","IHS_YND_519","NOCINC0002749137","A=
FEME NORD","","31-07-2024 16:10:04","31-07-2024 15:44:34","31-07-2024 16:00=
:46","No power issue site on grid with U=3D53,4v  Ange (620811823) from ZTE=
 is working on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
site on grid with U=3D53,4v  Ange (620811823) from ZTE is working on site",=
"kouoh.jean@ihstowers.com","1532","31-07-2024 16:10:04","Sagemcom CMR"
"Closed Complete","Site Down","T2743","IHS_YND_721","NOCINC0002748891","VOI=
RIE MUNICIPALE YAOUNDE","","31-07-2024 15:34:06","31-07-2024 15:24:57","31-=
07-2024 16:40:48","site went down due to CB 80(A) disjonction on Dcbox // H=
e rearmed the CB   (Site already swapped by ZTE )","Paul BIBOUM","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue",=
"site went down due to CB 80(A) disjonction on Dcbox // He rearmed the CB  =
 (Site already swapped by ZTE )","denis.mballa@ihstowers.com","550","31-07-=
2024 15:34:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0002748750","V=
allee-Bastos OCM","","31-07-2024 15:05:53","31-07-2024 14:46:40","31-07-202=
4 14:50:26","No power issue site on grid with U=3D53,7v  Franck (691144395)=
 from ZTE is working on site ,","","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid =
with U=3D53,7v  Franck (691144395) from ZTE is working on site ,","kouoh.je=
an@ihstowers.com","1155","31-07-2024 15:05:53","Sagemcom CMR"
"Closed Complete","Site Down","T1505","IHS_YND_681","NOCINC0002748719","NKO=
LMEKONG YDE","","31-07-2024 15:00:53","31-07-2024 14:49:21","31-07-2024 15:=
32:35"," Grid outage ,site went down because Gen started and stopped with a=
larm low oil pressure //He reset card GE and gen manually started ","Fabric=
e Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","=
 Grid outage ,site went down because Gen started and stopped with alarm low=
 oil pressure //He reset card GE and gen manually started ","denis.mballa@i=
hstowers.com","1089","31-07-2024 15:00:53","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0002748715","Elo=
umdem stade","","31-07-2024 14:58:36","31-07-2024 14:55:24","31-07-2024 15:=
13:11","Site went down because 01/02 rectifier faulty on site// He replaced=
 the recticfier faulty","Fanda Brice","Equipment Repair","Passive","Rectifi=
er","Rectifier Module","Site went down because 01/02 rectifier faulty on si=
te// He replaced the recticfier faulty","denis.mballa@ihstowers.com","192",=
"31-07-2024 14:58:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002748712","N=
koabang2","","31-07-2024 14:57:05","31-07-2024 14:31:56","31-07-2024 14:40:=
05","No power issue site on grid with U=3D52.9v  clauvis(696678889) from ZT=
E is working on site ,","Mba Lazare Herve","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site =
on grid with U=3D52.9v  clauvis(696678889) from ZTE is working on site ,","=
kouoh.jean@ihstowers.com","1511","31-07-2024 14:57:05","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002748664","Bas=
tos Amb Coree","","31-07-2024 14:47:40","31-07-2024 14:30:29","31-07-2024 1=
5:56:51","Grid outage no space to deploy //Grid power return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy //Grid power return","denis.mballa@ihstowers.com","1033","31-=
07-2024 14:47:40","Sagemcom CMR"
"Closed Complete","Site Down","T0773","IHS_YND_262","NOCINC0002748648","Men=
dong3","","31-07-2024 14:45:12","31-07-2024 14:21:02","31-07-2024 20:05:42"=
,"Grid outage no space to deploy // Grid power return","","Grid Supply","Pa=
ssive","Grid","National Grid - Grid Outage Issue","Grid outage no space to =
deploy // Grid power return","denis.mballa@ihstowers.com","1452","31-07-202=
4 14:45:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0002748609","Mandoumb=
a OCM","","31-07-2024 14:38:30","31-07-2024 14:25:54","31-07-2024 16:38:56"=
,"Cascaded Incident from TTO2545018","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down due to CB 125(A)=
 disjonction on Dcbox // He rearmed the CB ","system","756","31-07-2024 14:=
38:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0002748610","Mambine"=
,"","31-07-2024 14:38:30","31-07-2024 14:25:54","31-07-2024 16:38:56","Casc=
aded Incident from TTO2545018","Fanda Brice","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","site went down due to CB 125(A) disjoncti=
on on Dcbox // He rearmed the CB ","system","756","31-07-2024 14:38:30","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_060","IHS_YND_348","NOCINC0002748602","N=
kenglikok","IHS_YND_367, IHS_YND_350","31-07-2024 14:36:59","31-07-2024 14:=
25:54","31-07-2024 16:38:56","site went down due to CB 125(A) disjonction o=
n Dcbox // He rearmed the CB ","Kemeni Franklin","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Circuit Breaker Issue","site went down =
due to CB 125(A) disjonction on Dcbox // He rearmed the CB ","emmanuel.ghan=
i@ihstowers.com","666","31-07-2024 14:36:59","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0002748234","UPA=
C LP","","31-07-2024 13:30:17","31-07-2024 13:22:13","31-07-2024 13:36:44",=
"Active, no power issue, site on grid with U=3D55V Tx FME mand Ngetsa (??69=
9949553??)  From  Huawei is informed.  ","","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power is=
sue, site on grid with U=3D55V Tx FME mand Ngetsa (??699949553??)  From  Hu=
awei is informed.  ","joelle.ekessi@ihstowers.com","485","31-07-2024 13:30:=
17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_640","IHS_YND_704","NOCINC0002748176","B=
astos Bir","","31-07-2024 13:16:53","31-07-2024 13:12:46","31-07-2024 13:25=
:36","ACTIVE No power isue U=3D 54.5V site on Grid TX fme Eloundoun /652586=
578/ from huawei is informed","Mboua Thierry","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power i=
sue U=3D 54.5V site on Grid TX fme Eloundoun /652586578/ from huawei is inf=
ormed","emmanuel.ghani@ihstowers.com","249","31-07-2024 13:16:53","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_381","IHS_YND_303","NOCINC0002748050","N=
yom OCM","","31-07-2024 12:42:41","31-07-2024 12:34:36","31-07-2024 13:32:4=
4","Site on DG due to grid outage , DG stopped due to high temp alarm //He =
added water ,reset DG card and manually start of DG.","Fabrice Pouakam","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolant Lev=
el Issue","Site on DG due to grid outage , DG stopped due to high temp alar=
m //He added water ,reset DG card and manually start of DG.","emmanuel.ghan=
i@ihstowers.com","487","31-07-2024 12:42:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0002747816","N=
kolso","","31-07-2024 12:02:29","31-07-2024 11:58:16","31-07-2024 13:20:20"=
,"Active: no power issue, site is on grid with Ubaie=3D53V, Mamoudzou(6 91 =
30 61 25) from ZTE WORKING ON SITE.","TIENTCHEU NZETCHIEU GAEL","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active: no power issue, site is on grid with Ubaie=3D53V, Mamoudzou(6 91 3=
0 61 25) from ZTE WORKING ON SITE
","emmanuel.ghani@ihstowers.com","255","31-07-2024 12:02:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_466","IHS_YND_271","NOCINC0002747749","Y=
ona Hotel","","31-07-2024 11:48:42","31-07-2024 11:41:33","31-07-2024 11:55=
:56","Active//No power issue on site ,site on Grid with Ubaie=3D54.3 V  The=
 Tx Fme Mouhamadou (691144435) from  Huawei is informed.","TIENTCHEU NZETCH=
IEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid with Uba=
ie=3D54.3 V  The Tx Fme Mouhamadou (691144435) from  Huawei is informed.","=
emmanuel.ghani@ihstowers.com","431","31-07-2024 11:48:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_255","IHS_YND_286","NOCINC0002747730","D=
agobert","","31-07-2024 11:43:49","31-07-2024 11:40:44","31-07-2024 12:50:3=
3","No power issue, site is on grid with Ubaie=3D53V, Yves(699127444) from =
ZTE working on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue,=
 site is on grid with Ubaie=3D53V, Yves(699127444) from ZTE working on site=
","emmanuel.ghani@ihstowers.com","186","31-07-2024 11:43:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_234","IHS_YND_415","NOCINC0002747701","B=
oga-Mahole","","31-07-2024 11:41:53","31-07-2024 11:35:48","31-07-2024 13:2=
5:25","Active/ No power issue, site is on grid with Ubaie=3D53V, Lucien(697=
391563) from Huawei is informed.","Kemeni Franklin","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active/ No =
power issue, site is on grid with Ubaie=3D53V, Lucien(697391563) from Huawe=
i is informed
.","emmanuel.ghani@ihstowers.com","368","31-07-2024 11:41:53","Sagemcom CMR=
"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0002747530","Nko=
ulou Carriere carrefourt","","31-07-2024 10:57:26","31-07-2024 10:51:22","3=
1-07-2024 11:49:18","Grid outage site went down because Gen start and stop =
with alarm low oil presure // He added oil and started the Gen","Mba Lazare=
 Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","=
Grid outage site went down because Gen start and stop with alarm low oil pr=
esure // He added oil and started the Gen","joelle.ekessi@ihstowers.com","3=
64","31-07-2024 10:57:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_289","NOCINC0002747520","Nkolanga=
a","","31-07-2024 10:55:10","31-07-2024 10:51:37","31-07-2024 11:43:14","Ca=
scaded Incident from TTO2543777","Mba Lazare Herve","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen started and stopped due to gasoil pump Faulty// He replaced the gasoil=
 pump and Gen manually started","system","213","31-07-2024 10:55:10","Sagem=
com CMR"
"Closed Complete","Site Down","T1161","IHS_YND_290","NOCINC0002747516","Aba=
ng","IHS_YND_289","31-07-2024 10:54:40","31-07-2024 10:51:37","31-07-2024 1=
1:43:14","Grid outage site went down because Gen started and stopped due to=
 gasoil pump Faulty// He replaced the gasoil pump and Gen manually started"=
,"Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Fuel Li=
fting Pump Faulty","Grid outage site went down because Gen started and stop=
ped due to gasoil pump Faulty// He replaced the gasoil pump and Gen manuall=
y started","joelle.ekessi@ihstowers.com","186","31-07-2024 10:54:40","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0002747459","C=
omplexe-BEAC","","31-07-2024 10:42:27","31-07-2024 08:35:19","31-07-2024 09=
:00:45","(site already swapped by Zte)","Albran Byorel","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r  issue on site ubaie=3D54v site on grid CB tripped in BTS  Lionnel Adjep =
is informed","emmanuel.ghani@ihstowers.com","7629","31-07-2024 10:42:27","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0002747356","D=
onga","","31-07-2024 10:21:18","31-07-2024 10:15:12","31-07-2024 12:42:45",=
"site down due to Gen swap","Parker Tchoup","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","site down due to Gen swap by=
 Ulrich   Sagemcom //end of work","emmanuel.ghani@ihstowers.com","368","31-=
07-2024 10:21:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0002747342","N=
kolbisson usine des eaux","","31-07-2024 10:18:48","31-07-2024 10:00:43","3=
1-07-2024 13:15:20","Active// No power issue ,site on Grid with Ubaie=3D50 =
V  The Team  claude  //  699029796 from ZTE is working in site","TIENTCHEU =
NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Fai=
lure","BTS/TX Fault Alarm","Active// No power issue ,site on Grid with Ubai=
e=3D50 V  The Team  claude  //  699029796 from ZTE is working in site","emm=
anuel.ghani@ihstowers.com","1089","31-07-2024 10:18:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002747339","Eto koss=
 Yde","","31-07-2024 10:18:40","31-07-2024 10:13:56","31-07-2024 11:16:10",=
"Cascaded Incident from TTO2543576","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site on DG due to grid outage,DG sto=
pped due to overload //He reduiced the load site on DG.","system","284","31=
-07-2024 10:18:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002747340","ELOUMDEM=
 CARRIERE 2","","31-07-2024 10:18:40","31-07-2024 10:13:56","31-07-2024 11:=
16:10","Cascaded Incident from TTO2543576","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site on DG due to grid outage=
,DG stopped due to overload //He reduiced the load site on DG.","system","2=
84","31-07-2024 10:18:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0002747337","Crf-Nkol=
bisson","","31-07-2024 10:18:20","31-07-2024 10:08:51","31-07-2024 10:10:20=
","Cascaded Incident from TTO2543568","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","Active// No power issue =
on site ,site on Grid with Ubaie=3D53.2 V   The Team RWAN  //+237 6 91 41 0=
2 3 from ZTE is working on site ","system","569","31-07-2024 10:18:20","Sag=
emcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002747336","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","31-07-2024 10:18:00","31-07-2024 10:13=
:56","31-07-2024 11:16:10","Site on DG due to grid outage,DG stopped due to=
 overload //He reduiced the load site on DG.","Fanda Brice","Equipment Repa=
ir","Passive","ACDG Gen","ACDG - Overload","Site on DG due to grid outage,D=
G stopped due to overload //He reduiced the load site on DG.","joelle.ekess=
i@ihstowers.com","245","31-07-2024 10:18:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_340","IHS_YND_233","NOCINC0002747331","O=
yomabang OCM","IHS_YND_232","31-07-2024 10:16:57","31-07-2024 10:08:51","31=
-07-2024 12:50:20","Active// No power issue on site ,site on Grid with Ubai=
e=3D53.2 V   The Team RWAN  //+237 6 91 41 02 3 6from ZTE is working on sit=
e ","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","Active// No power issue on site =
,site on Grid with Ubaie=3D53.2 V   The Team RWAN  //+237 6 91 41 02 3 from=
 ZTE is working on site ","emmanuel.ghani@ihstowers.com","488","31-07-2024 =
10:16:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_692","IHS_YND_223","NOCINC0002747243","F=
ebe Village","","31-07-2024 10:01:36","30-07-2024 18:11:56","30-07-2024 18:=
15:44","No power issue on site ubaie=3D54v site on grid","Mboua Thierry","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site ubaie=3D54v site on grid","marie.kwin@ihst=
owers.com","56982","31-07-2024 10:01:36","Sagemcom CMR"
"Closed Complete","Site Down","T1257","IHS_YND_800","NOCINC0002747236","ODZ=
A CITE MBIA","","31-07-2024 09:58:53","31-07-2024 09:55:49","31-07-2024 11:=
38:50","site went down Gen failed to start due to fuse of contactor Ge faul=
ty//he replaced the Fuse and started the Gen","Albran Byorel","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Load Contactor","site went down Gen fail=
ed to start due to fuse of contactor Ge faulty//he replaced the Fuse and st=
arted the Gen","joelle.ekessi@ihstowers.com","185","31-07-2024 09:58:53","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_040","IHS_YND_114","NOCINC0002747226","K=
ondengui","","31-07-2024 09:55:33","31-07-2024 09:46:27","31-07-2024 13:15:=
56","Active: no power issue, site is on grid with ubaie=3D53V, WAMBE(697655=
132) from ZTE WORKING ON SITE","Albran Byorel","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power=
 issue, site is on grid with ubaie=3D53V, WAMBE(697655132) from ZTE WORKING=
 ON SITE
","emmanuel.ghani@ihstowers.com","548","31-07-2024 09:55:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_553","IHS_YND_686","NOCINC0002747202","O=
yomabang Ecole","","31-07-2024 09:48:48","31-07-2024 09:40:44","31-07-2024 =
12:00:54","Active//No power issue on site ,site on Grid with Ubaie=3D55.6 V=
  The Team  JUNIOR  // 652444763 from ZTE is working in site","TIENTCHEU NZ=
ETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid with=
 Ubaie=3D55.6 V  The Team  JUNIOR  // 652444763 from ZTE is working in site=
","emmanuel.ghani@ihstowers.com","485","31-07-2024 09:48:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0002747112","N=
kolafeme","","31-07-2024 09:32:14","31-07-2024 09:22:11","31-07-2024 12:15:=
36","Active: no power issue, site is on grid with Ubaie=3D53V; Kayo christi=
an(698661479) from ZTE working on site.","TIENTCHEU NZETCHIEU GAEL","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: no power issue, site is on grid with Ubaie=3D53V; Kayo christi=
an(698661479) from ZTE working on site.
","emmanuel.ghani@ihstowers.com","604","31-07-2024 09:32:14","Sagemcom CMR"
"Closed Complete","Site Down","T1861","IHS_YND_682","NOCINC0002747094","MON=
TEE NKONDENGUI","","31-07-2024 09:25:23","31-07-2024 09:19:19","31-07-2024 =
09:32:23","Grid hybrid gen site  , site went down due to malfunction of hyb=
rid system//Gen manually started","Albran Byorel","Equipment Repair","Passi=
ve","Hybrid","Hybrid Module","Grid hybrid gen site  , site went down due to=
 malfunction of hybrid system//Gen manually started","joelle.ekessi@ihstowe=
rs.com","365","31-07-2024 09:25:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0002746933","N=
kolbi-Boss","","31-07-2024 08:43:10","31-07-2024 08:37:03","31-07-2024 08:4=
0:21","","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on =
grid with Ubaie=3D53V, Dominique Membila (694552106) from ZTE working on si=
te( Swap)","emmanuel.ghani@ihstowers.com","369","31-07-2024 08:43:10","Sage=
mcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0002746925","MVA=
N SACEL","","31-07-2024 08:40:19","31-07-2024 08:34:14","31-07-2024 08:44:3=
9","grid outage, site down due to poor backup before gen start//gen started=
","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Battery Low","grid outage, site down due to poor backup before gen sta=
rt//gen started","joelle.ekessi@ihstowers.com","367","31-07-2024 08:40:19",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0002746781","B=
iteng-Maetur","","31-07-2024 08:21:30","31-07-2024 07:24:25","31-07-2024 13=
:21:09","","Mba Lazare Herve","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","no power issue on site ubaie=3D54=
v site on grid CB tripped in BTS    Lionel Adjep is informed","emmanuel.gha=
ni@ihstowers.com","3426","31-07-2024 08:21:30","Sagemcom CMR"
"Closed Complete","Site Down","T1333","IHS_YND_174","NOCINC0002746602","Car=
refourt Nkomo","","31-07-2024 07:37:36","31-07-2024 07:31:30","31-07-2024 1=
0:31:14","Site on DG due to grid outage,DG stopped due to low water level  =
in the radiator  // He added water and manually start of DG.","Mba Lazare H=
erve","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","Site on DG=
 due to grid outage,DG stopped due to low water level  in the radiator // H=
e added water and manually start of DG.","joelle.ekessi@ihstowers.com","310=
7","31-07-2024 07:37:36","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0002746378","Akak-Nko=
zoa-MTN-IHS","","31-07-2024 06:39:10","31-07-2024 06:15:02","31-07-2024 07:=
07:57","Cascaded Incident from TTO2542622","Fabrice Pouakam","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","grid outage, site went do=
wn because gen faild to start due to battery Gen faulty// Gen manually star=
ted with Battery external","system","1448","31-07-2024 06:39:10","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0002746371","S=
oa-II","IHS_YND_316, IHS_YND_324","31-07-2024 06:37:07","31-07-2024 06:15:0=
2","31-07-2024 07:07:57","grid outage, site went down because gen faild to =
start due to battery Gen faulty// Gen manually started with Battery externa=
l","Siligap Boris","Equipment Repair","Passive","ACDG Gen","ACDG - Generato=
r Battery","grid outage, site went down because gen faild to start due to b=
attery Gen faulty// Gen manually started with Battery external","emmanuel.g=
hani@ihstowers.com","1326","31-07-2024 06:37:07","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_133","NOCINC0002746369","Elig-Edz=
oa","","31-07-2024 06:36:29","31-07-2024 06:14:14","31-07-2024 06:49:08","C=
ascaded Incident from TTO2542612","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","site went down because 01/ 05 recifier faulty: ca=
using by over -current//site up,site on Gen (Added rectifier ongoing","syst=
em","1335","31-07-2024 06:36:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_380","IHS_YND_102","NOCINC0002746350","N=
taba","IHS_YND_133","31-07-2024 06:35:18","31-07-2024 06:14:14","31-07-2024=
 06:54:19","site went down because 01/ 05 recifier faulty causing by over -=
current//site on Gen (Added rectifier ongoing","Delor Telezing","Equipment =
Repair","Passive","Rectifier","Rectifier Module","site went down because 01=
/ 05 recifier faulty causing by over -current//site on Gen (Added rectifier=
 ongoing","emmanuel.ghani@ihstowers.com","1266","31-07-2024 06:35:18","Sage=
mcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002746144","Jou=
vence 2000","","31-07-2024 05:25:05","31-07-2024 05:12:53","31-07-2024 06:1=
5:57","grid fluctuation, site went down because gen faild to start due to p=
oor battery backup and  grid contactor did not excited// site on grid and H=
e excited grid contactor","Delor Telezing","Equipment Repair","Passive","Co=
ntrol Panel","ATS-AMF Issue","grid fluctuation, site went down because gen =
faild to start due to poor battery backup and  grid contactor did not excit=
ed// site on grid and He excited grid contactor","dorothy.djantio@ihstowers=
.com","735","31-07-2024 05:25:05","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0002745531","Bon=
djock","","31-07-2024 02:38:36","31-07-2024 02:32:28","31-07-2024 03:40:17"=
,"Site was on gen, Site went down because gen ran until fuel shortage//Refu=
eling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage",=
"Site was on gen, Site went down because gen ran until fuel shortage//Refue=
ling done","dorothy.djantio@ihstowers.com","369","31-07-2024 02:38:36","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002745507","M=
asque","","31-07-2024 02:23:35","31-07-2024 02:16:22","31-07-2024 03:49:47"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V   The TX FME  Elo=
undou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V=
   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive=
 issue","ange.kongo@ihstowers.com","436","31-07-2024 02:23:35","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_692","NOCINC0002745443","Mendong =
vallee","","31-07-2024 01:56:13","30-07-2024 21:49:57","30-07-2024 21:49:58=
","No power issue site on grid with U=3D54,3v,Notice that we have disjuncti=
on at OCM Equipements Hosiah from Huawei is informed","Fanda Brice","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power issue site on grid with U=3D54,3v,Notice that we have disjunc=
tion at OCM Equipements Hosiah from Huawei is informed","ange.kongo@ihstowe=
rs.com","14778","31-07-2024 01:56:13","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_742","NOCINC0002745109","Mendong =
NB","","31-07-2024 00:18:20","31-07-2024 00:12:11","31-07-2024 00:29:27","C=
ascaded Incident from TTO2541499","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage site went down before Gen started due=
 to poor battery back up // Grid return","system","369","31-07-2024 00:18:2=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0002745111","Tamtam W=
eekend","","31-07-2024 00:18:20","31-07-2024 00:12:11","31-07-2024 00:29:27=
","Cascaded Incident from TTO2541499","Hyemafo Gildas","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down befo=
re Gen started due to poor battery back up // Grid return","system","369","=
31-07-2024 00:18:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_237","NOCINC0002745110","Carrefou=
r Simbock","","31-07-2024 00:18:20","31-07-2024 00:12:11","31-07-2024 00:29=
:27","Cascaded Incident from TTO2541499","Hyemafo Gildas","Cascade Outage",=
"Passive","Cascade Passive","Cascade Passive","Grid outage site went down b=
efore Gen started due to poor battery back up // Grid return","system","369=
","31-07-2024 00:18:20","Sagemcom CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0002745106","Men=
dong Plateau","IHS_YND_742, IHS_YND_237, IHS_YND_151","31-07-2024 00:17:23"=
,"31-07-2024 00:10:11","31-07-2024 00:12:27","Grid outage site went down be=
fore Gen started due to poor battery back up // Grid return","Hyemafo Gilda=
s","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid outage site went down before Gen started due to poor battery back =
up // Grid return","dorothy.djantio@ihstowers.com","11105","31-07-2024 00:1=
7:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002744997","Eto koss=
 Yde","","30-07-2024 23:28:30","30-07-2024 23:22:17","30-07-2024 23:52:52",=
"Cascaded Incident from TTO2541388","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because g=
en failed to started due to Main Gen faulty // MDG of 20KVA has deployed ",=
"system","373","30-07-2024 23:28:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002744998","ELOUMDEM=
 CARRIERE 2","","30-07-2024 23:28:30","30-07-2024 23:22:17","30-07-2024 23:=
52:52","Cascaded Incident from TTO2541388","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage site went down be=
cause gen failed to started due to Main Gen faulty // MDG of 20KVA has depl=
oyed ","system","373","30-07-2024 23:28:30","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002744994","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","30-07-2024 23:27:26","30-07-2024 23:22=
:17","30-07-2024 23:52:52","Grid outage site went down because gen failed t=
o started due to Main Gen faulty // MDG of 20KVA has deployed ","Fanda Bric=
e","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Faulty","Grid =
outage site went down because gen failed to started due to Main Gen faulty =
// MDG of 20KVA has deployed ","dorothy.djantio@ihstowers.com","311","30-07=
-2024 23:27:26","Sagemcom CMR"
"Closed Complete","Site Down","T0395","IHS_YND_065","NOCINC0002744430","Ess=
os DCS","","30-07-2024 21:29:12","30-07-2024 21:19:59","31-07-2024 08:43:19=
","Access Issue during the night","Delor Telezing","Access Denial","Lease O=
r Legal","Landlord Related Issues","Access Issue - Land Lord","Access issue=
 during the night due to Landlord, grid outage, gen failst to start//grid r=
eturn (investigations ongoing)Power reset done","alexandre.kamal@ihstowers.=
com","554","30-07-2024 21:29:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0002744138","M=
endong vallee","","30-07-2024 20:46:34","30-07-2024 20:14:12","30-07-2024 2=
0:20:03","No power issue site on grid with U=3D54,3v,Notice that we have di=
sjunction at OCM Equipements Hosiah from Huawei is informed","Fanda Brice",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","No power issue site on grid with U=3D54,3v,Notice that we have =
disjunction at OCM Equipements Hosiah from Huawei is informed","kamga.virgi=
le@ihstowers.com","1945","30-07-2024 20:46:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_436","IHS_YND_551","NOCINC0002742946","A=
KONGO","","30-07-2024 17:41:03","30-07-2024 17:19:47","30-07-2024 17:20:25"=
,"No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rodrigue (65=
5102999)from Huawei is informed. Repetitive issue ,","Fanda Brice","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site Ubaie=3D52,5V site on Gen. The Tx FME Rodrigue (=
655102999)from Huawei is informed. Repetitive issue ,","kamga.virgile@ihsto=
wers.com","1278","30-07-2024 17:41:03","Sagemcom CMR"
"Cancelled","Warning","CTR_321","IHS_YND_085","NOCINC0002742390","Briqueter=
ie","","30-07-2024 16:54:52","","","","","","","","","","kamga.virgile@ihst=
owers.com","347","30-07-2024 16:54:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0002742368","M=
EHANDAN","","30-07-2024 16:49:27","30-07-2024 16:25:20","30-07-2024 16:36:1=
9","Site went down because the Cb(63A) of PWC dysjuncted due to increased s=
ite load// he made the bridge of CB(80*63A) (Site already swapped by ZTE )"=
,"Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Circuit Breaker Issue","Site went down because the Cb(63A) of PWC dysju=
ncted due to increased site load// he made the bridge of CB(80*63A) (Site a=
lready swapped by ZTE )","kamga.virgile@ihstowers.com","1447","30-07-2024 1=
6:49:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002742350","O=
dza II OCM","","30-07-2024 16:45:44","30-07-2024 16:27:16","30-07-2024 17:3=
9:11","Site went down due to insuffisance of rectifier // site stabilized (=
swapping by ZTE )","Albran Byorel","Equipment Repair","Passive","Rectifier"=
,"Rectifier Module","Site went down due to insuffisance of rectifier // sit=
e stabilized (swapping by ZTE )","kamga.virgile@ihstowers.com","1108","30-0=
7-2024 16:45:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_419","IHS_YND_227","NOCINC0002742100","M=
vog Betsi","","30-07-2024 16:18:34","30-07-2024 16:00:20","30-07-2024 16:10=
:06","Active, no power issue on site, U=3D54V on grid, TEAM Thimoty Nji /6 =
97 08 10 70/ From ZTE is working on site","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve, no power issue on site, U=3D54V on grid, TEAM Thimoty Nji /6 97 08 10 7=
0/ From ZTE is working on site","kamga.virgile@ihstowers.com","1097","30-07=
-2024 16:18:34","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0002741728","Nkolfon =
Cimencam","","30-07-2024 15:19:00","30-07-2024 14:26:59","30-07-2024 16:01:=
54","Cascaded Incident from TTO2538063","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","grid outage, gen start and st=
opped due to Gen overload 17kva 180A//he reduice the load of site","system"=
,"13193","30-07-2024 15:19:00","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002741540","Nko=
g-Edzen","","30-07-2024 15:01:57","30-07-2024 14:53:32","30-07-2024 15:37:1=
1","site went down because the generator belt was cut // he replaced the be=
lt ","Parker Tchoup","Equipment Repair","Passive","ACDG Gen","ACDG - Fan Be=
lt","site went down because the generator belt was cut // he replaced the b=
elt ","alexandre.kamal@ihstowers.com","506","30-07-2024 15:01:57","Sagemcom=
 CMR"
"Closed Complete","Site Down","T2208","IHS_YND_282","NOCINC0002741180","Mey=
o","IHS_YND_762","30-07-2024 14:47:55","30-07-2024 14:26:59","30-07-2024 16=
:31:41","grid outage, gen start and stopped due to Gen overload 17kva 180A/=
/he reduice the load of site","Hyemafo Gildas","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Overload","grid outage, gen start and stopped due to Ge=
n overload 17kva 180A//he reduice the load of site","alexandre.kamal@ihstow=
ers.com","3228","30-07-2024 14:47:55","Sagemcom CMR"
"Closed Complete","Warning","CTR_463","IHS_YND_313","NOCINC0002740835","Afa=
noya","","30-07-2024 14:37:48","","","wrongly ticket","Hyemafo Gildas","War=
ning","Warning","POWER","Warning - AC Phase 3 Voltage low","wrongly ticket"=
,"kamga.virgile@ihstowers.com","914","30-07-2024 14:37:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0002738327","S=
apeur","","30-07-2024 12:34:39","30-07-2024 10:39:27","30-07-2024 10:50:32"=
,"Active//No power issue on site ,site on Grid with Ubaie=3D53 .5 V Team El=
orm Fiaku-Wyse// 657300711 from ZTE is working on site","Mboua Thierry","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site ,site on Grid with Ubaie=3D53 .5 V =
Team Elorm Fiaku-Wyse// 657300711 from ZTE is working on site","landry.etam=
e@ihstowers.com","6914","30-07-2024 12:34:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0002738215","E=
NAM","","30-07-2024 12:07:38","30-07-2024 10:34:31","30-07-2024 10:40:34","=
No power issue site on grid with U=3D54,3v,Notice that we have disjunction =
at OCM Equipements Hosiah from Huawei is informed","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue site on grid with U=3D54,3v,Notice that we have disjunction at OCM Eq=
uipements Hosiah from Huawei is informed","landry.etame@ihstowers.com","558=
8","30-07-2024 12:07:38","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002738212","Eko=
unou","","30-07-2024 12:06:33","30-07-2024 11:56:12","30-07-2024 12:06:38",=
"Grid outage site went down because Gen failed to start due to poor battery=
 backup///Grid power return (site swapped by ZTE)","Albran Byorel","Equipme=
nt Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid ou=
tage site went down because Gen failed to start due to poor battery backup/=
//Grid power return (site swapped by ZTE)","denis.mballa@ihstowers.com","62=
2","30-07-2024 12:06:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0002738180","V=
allee-Bastos OCM","","30-07-2024 11:56:41","30-07-2024 11:49:34","30-07-202=
4 12:20:46","No power issue site on grid with U=3D53,4v  Franck (691144395)=
 from ZTE is working on site ","","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid w=
ith U=3D53,4v  Franck (691144395) from ZTE is working on site ","landry.eta=
me@ihstowers.com","428","30-07-2024 11:56:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0002738081","C=
ite-Verte","","30-07-2024 11:50:26","30-07-2024 10:29:54","30-07-2024 11:09=
:54","Grid outage //Grid return(swapping by ZTE )","","Grid Supply","Passiv=
e","Grid","National Grid - Grid Outage Issue","Grid outage //Grid return(sw=
apping by ZTE )","kouoh.jean@ihstowers.com","4833","30-07-2024 11:50:26","S=
agemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002738009","Pha=
rmacie SION","","30-07-2024 11:27:12","30-07-2024 11:24:01","30-07-2024 11:=
34:01","Grid outage site went down before Gen started due to poor battery b=
ack up//Gen started automatically","Paul BIBOUM","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage site went dow=
n before Gen started due to poor battery back up//Gen started automatically=
","denis.mballa@ihstowers.com","193","30-07-2024 11:27:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_733","IHS_YND_349","NOCINC0002737783","N=
kongtock","","30-07-2024 10:43:14","30-07-2024 10:36:08","30-07-2024 11:15:=
40","site down due to poor weather, gen fails to start//sunshine return","K=
emeni Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - Control Pan=
el","site down due to poor weather, gen fails to start//sunshine return","l=
andry.etame@ihstowers.com","427","30-07-2024 10:43:14","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0002737779","MVA=
N SACEL","","30-07-2024 10:41:48","30-07-2024 10:39:33","30-07-2024 10:45:1=
0","Grid outage, site went down before gen start due to poor battery backup=
 // Gen start automatically(site swapped by ZTE)","MINKA NICOLAS","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, site went down before gen start due to poor battery backup // Gen star=
t automatically(site swapped by ZTE)","denis.mballa@ihstowers.com","137","3=
0-07-2024 10:41:48","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002737715","Tsi=
nga","","30-07-2024 10:23:58","30-07-2024 10:20:45","30-07-2024 10:42:05","=
Site went down because  controller of Huawei faulty//   site up (controller=
 to be replaced)","Mboua Thierry","Equipment Repair","Passive","Hybrid","Hy=
brid Module","Site went down because  controller of Huawei faulty//   site =
up (controller to be replaced)","denis.mballa@ihstowers.com","195","30-07-2=
024 10:23:58","Sagemcom CMR"
"Closed Complete","Warning","T1059","IHS_YND_434","NOCINC0002737695","Donga=
","","30-07-2024 10:15:24","","","Hybrid Gen Site ,Site alarming because Si=
te on battery //DG is started at start threshold =3D47.5 V","Parker Tchoup"=
,"Warning","Warning","POWER","Warning - Site on Battery","Hybrid Gen Site ,=
Site alarming because Site on battery //DG is started at start threshold =
=3D47.5 V","marie.kwin@ihstowers.com","8","30-07-2024 10:15:24","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0002737187","N=
kolfon Cimencam","","30-07-2024 08:49:27","30-07-2024 08:39:14","30-07-2024=
 09:35:20","No power issue site on grid with U=3D53,4v Marcelin ( 655091215=
) from ZTE is working on site ","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 site on grid with U=3D53,4v Marcelin ( 655091215) from ZTE is working on s=
ite ","landry.etame@ihstowers.com","614","30-07-2024 08:49:27","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002735727","M=
asque","","30-07-2024 06:45:18","30-07-2024 06:42:11","30-07-2024 07:30:40"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V   The TX FME  Elo=
undou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice P=
ouakam","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V=
   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive=
 issue","landry.etame@ihstowers.com","188","30-07-2024 06:45:18","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0002729679","Leboudi"=
,"","30-07-2024 02:01:50","30-07-2024 01:55:44","30-07-2024 02:00:54","Casc=
aded Incident from TTO2532272","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","ACTIVE No power issue  U=3D 54,=
7V site on Grid   THE tx fme mouhamadou /691144435 from Huawei is informed"=
,"system","366","30-07-2024 02:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0002729678","AFEME NO=
RD","","30-07-2024 02:01:50","30-07-2024 01:55:44","30-07-2024 02:00:54","C=
ascaded Incident from TTO2532272","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","ACTIVE No power issue  U=3D =
54,7V site on Grid   THE tx fme mouhamadou /691144435 from Huawei is inform=
ed","system","366","30-07-2024 02:01:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0002729653","N=
kolafeme","IHS_YND_519, IHS_YND_309","30-07-2024 02:00:01","30-07-2024 01:5=
5:44","30-07-2024 04:17:05","ACTIVE No power issue  U=3D 54,7V site on Grid=
   THE tx fme mouhamadou /691144435 from Huawei is informed","TIENTCHEU NZE=
TCHIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","ACTIVE No power issue  U=3D 54,7V site on Grid   T=
HE tx fme mouhamadou /691144435 from Huawei is informed","ange.kongo@ihstow=
ers.com","259","30-07-2024 02:00:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002729632","M=
asque","","30-07-2024 01:55:34","30-07-2024 01:20:27","30-07-2024 04:19:33"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V    The TX FME  El=
oundou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice =
Pouakam","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3=
V   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitiv=
e issue
","ange.kongo@ihstowers.com","2154","30-07-2024 01:55:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0002729119","M=
EHANDAN","","29-07-2024 23:26:48","29-07-2024 21:05:38","29-07-2024 23:07:0=
4","site went down due to Disjunction at OCM CB (80A*50A) // He reamed the =
CB (swapping by ZTE)","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Circuit Breaker Issue","site went down due to Disj=
unction at OCM CB (80A*50A) // He reamed the CB (swapping by ZTE)","ange.ko=
ngo@ihstowers.com","8473","29-07-2024 23:26:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0002728526","A=
hala","","29-07-2024 21:27:04","29-07-2024 20:23:56","29-07-2024 20:30:55",=
"ACTIVE no power issue U=3D54,7V site on Grid the tx fme RM alain /69114442=
3 from huawei is informed","MINKA NICOLAS","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE no power issu=
e U=3D54,7V site on Grid the tx fme RM alain /691144423 from huawei is info=
rmed","etienne.itondo@ihstowers.com","3789","29-07-2024 21:27:04","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0002728517","K=
oweit City","","29-07-2024 21:24:48","29-07-2024 20:31:40","29-07-2024 23:1=
8:17","site went down due to Disjunction at OCM CB (125A) // He reamed the =
CB (swapping by ZTE)","Albran Byorel","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Circuit Breaker Issue","site went down due to Disj=
unction at OCM CB (125A) // He reamed the CB (swapping by ZTE)","etienne.it=
ondo@ihstowers.com","3190","29-07-2024 21:24:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0002728419","M=
amch Building","","29-07-2024 21:03:19","29-07-2024 20:06:04","29-07-2024 2=
0:30:42"," No power issue site on grid with U=3D53,4v  Kelly (659933473) fr=
om ZTE is working on site ","Mboua Thierry","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm"," No power issue sit=
e on grid with U=3D53,4v  Kelly (659933473) from ZTE is working on site ","=
etienne.itondo@ihstowers.com","3438","29-07-2024 21:03:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0002728397","E=
mombo 2","","29-07-2024 21:00:32","29-07-2024 20:09:26","29-07-2024 20:15:2=
5","ACTIVE no power issue U=3D 54.7V site on Grid.   The FME tx Leonel (694=
693436)  From Huawei is Informed.","MINKA NICOLAS","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE no po=
wer issue U=3D 54.7V site on Grid. The FME tx Leonel (694693436)  From Huaw=
ei is Informed.
","etienne.itondo@ihstowers.com","3068","29-07-2024 21:00:32","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0002728272","M=
endong vallee","","29-07-2024 20:41:59","29-07-2024 19:26:38","29-07-2024 2=
2:37:10","No power issue on site U=3D54,5v site on grid hosiah of huawei is=
 informed notice that disjunction in CB in BTS(site swapped by ZTE)","Fanda=
 Brice","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue on site U=3D54,5v site on grid hosiah of=
 huawei is informed notice that disjunction in CB in BTS(site swapped by ZT=
E)","etienne.itondo@ihstowers.com","4523","29-07-2024 20:41:59","Sagemcom C=
MR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0002728157","Ang=
uissa New","","29-07-2024 20:14:12","29-07-2024 19:49:55","29-07-2024 20:49=
:19","site went down due to  rectifier faulty//He replace the faulty rectif=
ier ,site on grid ","MINKA NICOLAS","Equipment Repair","Passive","Rectifier=
","Rectifier Module","site went down due to  rectifier faulty//He replace t=
he faulty rectifier ,site on grid ","dorothy.djantio@ihstowers.com","1458",=
"29-07-2024 20:14:12","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0002727851","Abo=
me","","29-07-2024 19:13:07","29-07-2024 18:55:55","29-07-2024 19:07:38","S=
ite went down due to work (Nicolas/ Sagemcom/657108614/ installation of sec=
ond power cabinet )// end of work,","MINKA NICOLAS","Installation Activity"=
,"Passive","Planned Activity","Installation Activity","Site went down due t=
o work (Nicolas/ Sagemcom/657108614/ installation of second power cabinet )=
// end of work,","dorothy.djantio@ihstowers.com","1034","29-07-2024 19:13:0=
7","Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0002727388","Ang=
uissa New","","29-07-2024 17:27:07","29-07-2024 17:24:58","29-07-2024 19:39=
:31","No power issue site on grid with U=3D53,7v//sit up at 05:30 PM Elound=
ou Bertand  from Huawei is informed","MINKA NICOLAS","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power i=
ssue site on grid with U=3D53,7v//sit up at 05:30 PM Eloundou Bertand  from=
 Huawei is informed","dorothy.djantio@ihstowers.com","131","29-07-2024 17:2=
7:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_256","IHS_YND_232","NOCINC0002727318","C=
rf-Nkolbisson","","29-07-2024 17:03:31","29-07-2024 16:53:21","29-07-2024 1=
6:55:16","No power isssue site on grid with U=3D54,6v Dominique Membila (69=
4552106) from ZTE is working on site","TIENTCHEU NZETCHIEU GAEL","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power isssue site on grid with U=3D54,6v Dominique Membila (694552106)=
 from ZTE is working on site
","etienne.itondo@ihstowers.com","610","29-07-2024 17:03:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0002727153","Yona Hot=
el","","29-07-2024 16:46:50","29-07-2024 16:40:10","29-07-2024 16:47:45","C=
ascaded Incident from TTO2529650","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue site on grid =
with U=3D53,6v Dominique Membila(694552106) from ZTE is working on site  ",=
"system","400","29-07-2024 16:46:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_286","NOCINC0002727154","Dagobert=
","","29-07-2024 16:46:50","29-07-2024 16:40:10","29-07-2024 16:47:45","Cas=
caded Incident from TTO2529650","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Active","Cascade Active","Cascade Active","No power issue site on grid wi=
th U=3D53,6v Dominique Membila(694552106) from ZTE is working on site  ","s=
ystem","400","29-07-2024 16:46:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0002727144","N=
kolbi-Boss","IHS_YND_271, IHS_YND_286","29-07-2024 16:45:16","29-07-2024 16=
:40:10","29-07-2024 17:00:45","No power issue site on grid with U=3D53,6v D=
ominique Membila(694552106) from ZTE is working on site  ","TIENTCHEU NZETC=
HIEU GAEL","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","No power issue site on grid with U=3D53,6v Dominique=
 Membila(694552106) from ZTE is working on site  ","etienne.itondo@ihstower=
s.com","308","29-07-2024 16:45:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0002727137","B=
astos Ekoudou","","29-07-2024 16:43:57","29-07-2024 16:30:49","29-07-2024 1=
6:32:35","No power issue site on grid with U=3D54,7v Adam(658958386) from Z=
TE is working on site ","Mboua Thierry","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D54,7v Adam(658958386) from ZTE is working on site ","etienne.=
itondo@ihstowers.com","791","29-07-2024 16:43:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0002727132","B=
astos-Nylon","","29-07-2024 16:43:09","29-07-2024 16:26:58","29-07-2024 20:=
27:19","No power issue site on grid with U=3D53,4v Fran=E7ois (692511642) f=
rom ZTE is working on site","Mboua Thierry","Customer Equipment Failure","A=
ctive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site=
 on grid with U=3D53,4v Fran=E7ois (692511642) from ZTE is working on site"=
,"etienne.itondo@ihstowers.com","974","29-07-2024 16:43:09","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0002726953","Abo=
me","","29-07-2024 16:05:56","29-07-2024 15:59:51","29-07-2024 16:21:56","S=
ite went down due to work (Nicolas/ Sagemcom/657108614/ installation of sec=
ond power cabinet )// end of work,","MINKA NICOLAS","Installation Activity"=
,"Passive","Planned Activity","Installation Activity","Site went down due t=
o work (Nicolas/ Sagemcom/657108614/ installation of second power cabinet )=
// end of work,","dorothy.djantio@ihstowers.com","8229","29-07-2024 16:05:5=
6","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0002726851","N=
yanon","","29-07-2024 15:53:02","29-07-2024 15:32:52","29-07-2024 18:11:11"=
,"site went dowen because Gen failed to start due to Hybrid system dysfonct=
ion// He reset the Hybrid system and Gen manually started","TIENTCHEU NZETC=
HIEU GAEL","Equipment Repair","Passive","Hybrid","Hybrid Module","site went=
 dowen because Gen failed to start due to Hybrid system dysfonction// He re=
set the Hybrid system and Gen manually started","etienne.itondo@ihstowers.c=
om","1211","29-07-2024 15:53:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0002726590","C=
amp-Sic-Tsinga","","29-07-2024 14:55:37","29-07-2024 13:04:25","29-07-2024 =
21:15:57","Active, No power issue, site on grid with U=3D54V Team Clauvis /=
698726782 From ZTE is working on site","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active, No power issu=
e, site on grid with U=3D54V Team Clauvis /698726782 From ZTE is working on=
 site","etienne.itondo@ihstowers.com","6674","29-07-2024 14:55:37","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_102","IHS_YND_711","NOCINC0002726581","H=
-Franco New","","29-07-2024 14:51:58","29-07-2024 14:45:52","29-07-2024 20:=
45:09","No power issue site on grid with U=3D54V Okoro (672741248) from ZTE=
 is working on site ","Delor Telezing","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D54V Okoro (672741248) from ZTE is working on site=20
","etienne.itondo@ihstowers.com","368","29-07-2024 14:51:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002726558","M=
asque","","29-07-2024 14:45:35","29-07-2024 14:36:29","29-07-2024 21:00:48"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V, The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V,=
 The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive i=
ssue","etienne.itondo@ihstowers.com","548","29-07-2024 14:45:35","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0002726540","H=
-Prince","","29-07-2024 14:39:31","29-07-2024 13:35:22","29-07-2024 21:00:1=
0","No power issue on site U=3D54,5v site on grid Team Guy Laurent/65617767=
3/ZTE working on site","Mboua Thierry","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,5v site on grid Team Guy Laurent/656177673/ZTE working on site","etie=
nne.itondo@ihstowers.com","3850","29-07-2024 14:39:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0002726536","S=
cience","","29-07-2024 14:37:02","29-07-2024 14:04:52","29-07-2024 21:19:23=
","No power issue on site U=3D54v site on grid Team Pierre/677513091/ZTE wo=
rking on site","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54v site on grid Team Pierre/677513091/ZTE working on site","etienne.=
itondo@ihstowers.com","1930","29-07-2024 14:37:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0002726312","M=
EHANDAN","","29-07-2024 13:55:35","29-07-2024 12:36:11","29-07-2024 16:46:3=
5","Site went down because the Cb(63A) of PWC dysjuncted due to  increased =
site load// he made the bridge of CB(80*63A) (Site already swapped by ZTE )=
","Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Circuit Breaker Issue","Site went down because the Cb(63A) of PWC dysj=
uncted due to  increased site load// he made the bridge of CB(80*63A) (Site=
 already swapped by ZTE )","kamga.virgile@ihstowers.com","4765","29-07-2024=
 13:55:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_470","IHS_YND_088","NOCINC0002726136","E=
lobi Mokolo","","29-07-2024 13:22:11","29-07-2024 13:09:04","29-07-2024 13:=
15:18","Active, no power issue on site, U=3D53.5V on Grid Team Hopeson /652=
619749/ From ZTE is working on site","Mboua Thierry","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active, no=
 power issue on site, U=3D53.5V on Grid Team Hopeson /652619749/ From ZTE i=
s working on site","kamga.virgile@ihstowers.com","790","29-07-2024 13:22:11=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0002726112","C=
harles-Atangana","","29-07-2024 13:18:40","29-07-2024 12:57:26","29-07-2024=
 13:05:35","Active, no power issue on site, U=3D52,6V on Grid Team Franck /=
691144395 From ZTE is working on site","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issu=
e on site, U=3D52,6V on Grid Team Franck /691144395 From ZTE is working on =
site","kamga.virgile@ihstowers.com","1276","29-07-2024 13:18:40","Sagemcom =
CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0002726037","UPA=
C LP","","29-07-2024 13:06:14","29-07-2024 12:56:59","29-07-2024 12:59:05",=
"Active, no power issue, site on grid with U=3D55V Tx FME mand Ngetsa (??69=
9949553??)  From  Huawei is informed.","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active, no power issu=
e, site on grid with U=3D55V Tx FME mand Ngetsa (??699949553??)  From  Huaw=
ei is informed.","alexandre.kamal@ihstowers.com","557","29-07-2024 13:06:14=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0002725639","E=
toug ebe Meweulo","","29-07-2024 12:00:50","29-07-2024 11:29:25","29-07-202=
4 11:30:40","Active, no power issue on site, U=3D54,6V on Grid Team Andre /=
697609283 From ZTE is working on site","Hyemafo Gildas","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active,=
 no power issue on site, U=3D54,6V on Grid Team Andre /697609283 From ZTE i=
s working on site","kamga.virgile@ihstowers.com","1886","29-07-2024 12:00:5=
0","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_208","NOCINC0002725466","ARMP",""=
,"29-07-2024 11:28:40","29-07-2024 11:19:08","29-07-2024 11:25:46","Cascade=
d Incident from TTO2527780","","Cascade Outage","Active","Cascade Active","=
Cascade Active","Active: No power issue, site is on Grid with Ubaie=3D54.1V=
, TEAM Franck /691144395//// from ZTE work on site.","system","572","29-07-=
2024 11:28:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_704","NOCINC0002725465","Bastos B=
ir","","29-07-2024 11:28:40","29-07-2024 11:19:08","29-07-2024 11:25:46","C=
ascaded Incident from TTO2527780","Mboua Thierry","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active: No power issue, site is on Grid=
 with Ubaie=3D54.1V, TEAM Franck /691144395//// from ZTE work on site.","sy=
stem","572","29-07-2024 11:28:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_344","IHS_YND_192","NOCINC0002725418","D=
ragage","IHS_YND_704, IHS_YND_208","29-07-2024 11:24:41","29-07-2024 11:19:=
08","29-07-2024 11:25:46","Active: No power issue, site is on Grid with Uba=
ie=3D54.1V, TEAM Franck /691144395//// from ZTE work on site.","Mboua Thier=
ry","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active: No power issue, site is on Grid with Ubaie=3D54.1V,=
 TEAM Franck /691144395//// from ZTE work on site.","kamga.virgile@ihstower=
s.com","334","29-07-2024 11:24:41","Sagemcom CMR"
"Closed Complete","Site Down","T2743","IHS_YND_721","NOCINC0002725415","VOI=
RIE MUNICIPALE YAOUNDE","","29-07-2024 11:24:04","29-07-2024 11:14:39","29-=
07-2024 12:52:16","Site went down because CB  OCM (80A) at  DC BOX  disjonc=
ted Causing by increase load in site //He reamed CB ","Paul BIBOUM","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issu=
e","Site went down because CB  OCM (80A) at  DC BOX  disjoncted Causing by =
increase load in site //He reamed CB ","alexandre.kamal@ihstowers.com","567=
","29-07-2024 11:24:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0002725392","E=
ssomba","","29-07-2024 11:17:09","29-07-2024 11:06:52","29-07-2024 11:10:06=
","Active: No power issue, site is on Grid with Ubaie=3D54.1V, Charles /672=
489041//// from ZTE work on site.","Mba Lazare Herve","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: N=
o power issue, site is on Grid with Ubaie=3D54.1V, Charles /672489041//// f=
rom ZTE work on site.","kamga.virgile@ihstowers.com","618","29-07-2024 11:1=
7:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0002725307","M=
amch Building","","29-07-2024 10:55:28","29-07-2024 10:49:18","29-07-2024 1=
0:55:10","Active: No power issue, site is on Grid with Ubaie=3D54.5V, Kelly=
 /659933473// from ZTE work on site.","Mboua Thierry","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: N=
o power issue, site is on Grid with Ubaie=3D54.5V, Kelly /659933473// from =
ZTE work on site.","kamga.virgile@ihstowers.com","373","29-07-2024 10:55:28=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_029","IHS_YND_046","NOCINC0002725284","D=
joungolo","","29-07-2024 10:51:42","29-07-2024 10:48:34","29-07-2024 10:55:=
45","Active: No power issue, site is on Grid with Ubaie=3D54.6V, Vincent /6=
90994011/// from ZTE work on site.","Mboua Thierry","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No =
power issue, site is on Grid with Ubaie=3D54.6V, Vincent /690994011/// from=
 ZTE work on site.","kamga.virgile@ihstowers.com","190","29-07-2024 10:51:4=
2","Sagemcom CMR"
"Closed Complete","Site Down","CTR_322","IHS_YND_029","NOCINC0002725238","S=
apeur","","29-07-2024 10:45:43","29-07-2024 10:43:31","29-07-2024 10:50:38"=
,"Active: No power issue, site is on Grid with Ubaie=3D53.5V, Elorm Fiaku-W=
yse /657300711/// from ZTE work on site.","Mboua Thierry","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue, site is on Grid with Ubaie=3D53.5V, Elorm Fiaku-Wyse /65=
7300711/// from ZTE work on site.","kamga.virgile@ihstowers.com","133","29-=
07-2024 10:45:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_199","IHS_YND_050","NOCINC0002725221","S=
atcom","","29-07-2024 10:41:15","29-07-2024 10:32:00","29-07-2024 10:35:24"=
,"Active: No power issue, site is on Grid with Ubaie=3D54.6V, Team=F9 Samue=
l /678430046// from ZTE work on site.","Delor Telezing","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active:=
 No power issue, site is on Grid with Ubaie=3D54.6V, Team=F9 Samuel /678430=
046// from ZTE work on site.","kamga.virgile@ihstowers.com","556","29-07-20=
24 10:41:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002725194","E=
-Police","","29-07-2024 10:32:10","29-07-2024 10:27:55","29-07-2024 10:35:0=
5","Active: No power issue, site is on Grid with Ubaie=3D54.6V, Team Crisla=
in /694434993// from ZTE work on site.","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power iss=
ue, site is on Grid with Ubaie=3D54.6V, Team Crislain /694434993// from ZTE=
 work on site.","kamga.virgile@ihstowers.com","255","29-07-2024 10:32:10","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0002725187","T=
singa","","29-07-2024 10:30:18","29-07-2024 10:13:08","29-07-2024 10:25:45"=
,"Active: No power issue, site is on Grid with Ubaie=3D52.8V, TEAM Okpe / 6=
82367804// from ZTE work on site.","Mboua Thierry","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No p=
ower issue, site is on Grid with Ubaie=3D52.8V, TEAM Okpe / 682367804// fro=
m ZTE work on site.","kamga.virgile@ihstowers.com","1033","29-07-2024 10:30=
:18","Sagemcom CMR"
"Closed Complete","Site Down","T1742","IHS_YND_042","NOCINC0002725179","Mvo=
g-Ada_OCM","","29-07-2024 10:28:37","29-07-2024 10:23:26","29-07-2024 10:41=
:39","Grid outage no space  to deploy // Grid power return(site already swa=
pped by ZTE)","","Grid Supply","Passive","Grid","National Grid - Grid Outag=
e Issue","Grid outage no space  to deploy // Grid power return(site already=
 swapped by ZTE)","alexandre.kamal@ihstowers.com","311","29-07-2024 10:28:3=
7","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0002725097","B=
oumnyebel OCM","","29-07-2024 10:20:23","29-07-2024 09:59:37","29-07-2024 1=
0:05:05","Active, no power issue on site, U=3D55V on Grid The tx FME Etienn=
e FOPA /651320188/ From Huawei is informed ","Kemeni Franklin","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active, no power issue on site, U=3D55V on Grid The tx FME Etienne FOPA /65=
1320188/ From Huawei is informed ","kamga.virgile@ihstowers.com","1246","29=
-07-2024 10:20:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0002725034","N=
R-Bastos","","29-07-2024 10:03:21","29-07-2024 09:50:05","29-07-2024 09:55:=
52","Active: No power issue, site is on Grid with Ubaie=3D54.6V, EZENWOKO /=
673259896/ from ZTE work on site.","","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issue, s=
ite is on Grid with Ubaie=3D54.6V, EZENWOKO /673259896/ from ZTE work on si=
te.","kamga.virgile@ihstowers.com","797","29-07-2024 10:03:21","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0002725027","B=
astos Bethesda","","29-07-2024 10:01:54","29-07-2024 09:43:39","29-07-2024 =
09:50:18","Active: No power issue, site is on Grid with Ubaie=3D54.5V, Isma=
el  /678631637//// from ZTE work on site.","Mboua Thierry","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: No power issue, site is on Grid with Ubaie=3D54.5V, Ismael  /678631637/=
/// from ZTE work on site.","kamga.virgile@ihstowers.com","1097","29-07-202=
4 10:01:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0002725014","c=
hina embassy yde","","29-07-2024 09:57:20","29-07-2024 09:38:11","29-07-202=
4 09:45:31","Active: No power issue, site is on Grid with Ubaie=3D53.3V, Ns=
hom /695378974/ from ZTE work on site.","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","Fibre Failure","Active: No power issue, s=
ite is on Grid with Ubaie=3D53.3V, Nshom /695378974/ from ZTE work on site.=
","kamga.virgile@ihstowers.com","1151","29-07-2024 09:57:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_385","IHS_YND_369","NOCINC0002724994","M=
beng","IHS_YND_553","29-07-2024 09:52:04","29-07-2024 09:16:48","29-07-2024=
 11:57:45","Site went down because gen ran until fuel shortage//Refueling d=
one","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Site w=
ent down because gen ran until fuel shortage//Refueling done","kamga.virgil=
e@ihstowers.com","2117","29-07-2024 09:52:04","Sagemcom CMR"
"Closed Complete","Site Down","T1850","IHS_YND_376","NOCINC0002724420","Mam=
b","","29-07-2024 07:05:24","29-07-2024 06:53:17","29-07-2024 08:19:35","Gr=
id outage  site went down because GEN CB disjuncted due to  lightning// He =
reamed the CB","Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","A=
CDG - Load Breaker","Grid outage  site went down because GEN CB disjuncted =
due to  lightning// He reamed the CB","alexandre.kamal@ihstowers.com","2041=
","29-07-2024 07:05:24","Sagemcom CMR"
"Closed Complete","Site Down","T1595","IHS_YND_275","NOCINC0002724359","Nko=
lbong","","29-07-2024 06:51:40","29-07-2024 06:44:34","29-07-2024 07:25:33"=
,"Grid outage site went down because Gen failed to start // Gen manually st=
arted(Investigation ongoing)","Delor Telezing","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed to start // Gen manually started(Investigation ongoing)","alexandre.=
kamal@ihstowers.com","2469","29-07-2024 06:51:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002724322","M=
asque","","29-07-2024 06:40:44","29-07-2024 06:30:15","29-07-2024 06:35:56"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V, The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V,=
 The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive i=
ssue","kamga.virgile@ihstowers.com","631","29-07-2024 06:40:44","Sagemcom C=
MR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0002724320","Bit=
eng-Maetur","","29-07-2024 06:39:38","29-07-2024 06:21:29","29-07-2024 08:5=
4:05","Site went down due to  CB Rectifier Disjunted During The Rain and li=
ghtning // He reamed the (CB) Rectifier (site swapped by ZTE)","Mba Lazare =
Herve","Equipment Repair","Passive","Rectifier","Rectifier - Circuit Breake=
r","Site went down due to  CB Rectifier Disjunted During The Rain and light=
ning // He reamed the (CB) Rectifier (site swapped by ZTE)","alexandre.kama=
l@ihstowers.com","2203","29-07-2024 06:39:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_748","NOCINC0002723381","Nkoabang=
 Alembe","","29-07-2024 01:42:15","29-07-2024 01:40:07","29-07-2024 05:37:0=
4","Grid bfluctuation site went down because gen failed to start due to gri=
d bad voltage// He bypassed Grid  and Gen manually started ","Mba Lazare He=
rve","Grid Supply","Passive","Grid","National Grid - Phase Controller Fault=
y","Grid bfluctuation site went down because gen failed to start due to gri=
d bad voltage// He bypassed Grid  and Gen manually started ","joelle.ekessi=
@ihstowers.com","129","29-07-2024 01:42:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002723345","Ngouetou=
","","29-07-2024 01:37:21","29-07-2024 01:31:37","29-07-2024 01:32:37","Cas=
caded Incident from TTO2525798","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.9V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","344","29-07-2024 01:37:21","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002723346","MBIMBIM"=
,"","29-07-2024 01:37:21","29-07-2024 01:31:37","29-07-2024 01:32:37","Casc=
aded Incident from TTO2525798","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.9V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","344","29-07-2024 01:37:21","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002723342","Ngoum","=
","29-07-2024 01:37:20","29-07-2024 01:31:37","29-07-2024 01:32:37","Cascad=
ed Incident from TTO2525798","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.9V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","343","29-07-2024 01:37:20","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002723344","Yoko OCM=
","","29-07-2024 01:37:20","29-07-2024 01:31:37","29-07-2024 01:32:37","Cas=
caded Incident from TTO2525798","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.9V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 6=
57959647of Huawei is informed","system","343","29-07-2024 01:37:20","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002723343","Matsari"=
,"","29-07-2024 01:37:20","29-07-2024 01:31:37","29-07-2024 01:32:37","Casc=
aded Incident from TTO2525798","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.9V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane 65=
7959647of Huawei is informed","system","343","29-07-2024 01:37:20","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_712","NOCINC0002723304","Nkolkoum=
ou OCM","","29-07-2024 01:23:40","29-07-2024 01:17:59","29-07-2024 01:27:44=
","Cascaded Incident from TTO2525767","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","no power issue  on site =
,site on Grid  with U=3D53,2V Team lionel adjep  ( 655184876 )  from HUAWEI=
  is informed","system","341","29-07-2024 01:23:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_522","IHS_YND_545","NOCINC0002723280","N=
kolbisson usine des eaux","IHS_YND_712","29-07-2024 01:22:06","29-07-2024 0=
1:17:59","29-07-2024 01:27:44","no power issue  on site ,site on Grid  with=
 U=3D53,2V Team lionel adjep  ( 655184876 )  from HUAWEI  is informed","TIE=
NTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","no power issue  on site ,site on Grid  w=
ith U=3D53,2V Team lionel adjep  ( 655184876 )  from HUAWEI  is informed","=
emmanuel.ghani@ihstowers.com","249","29-07-2024 01:22:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_635","IHS_YND_528","NOCINC0002723047","M=
EHANDAN","","29-07-2024 00:23:58","28-07-2024 22:31:45","29-07-2024 03:32:4=
9","site went down  due to disjunction Cb in DC box// He reamed Cb , site o=
n grid (site swapped by ZTE)","Albran Byorel","Equipment Repair","Passive",=
"Control Panel","BTS Breaker Tripped","site went down  due to disjunction C=
b in DC box// He reamed Cb , site on grid (site swapped by ZTE)","emmanuel.=
ghani@ihstowers.com","6736","29-07-2024 00:23:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0002722900","A=
fanoya","","28-07-2024 23:48:24","28-07-2024 23:42:09","29-07-2024 00:15:28=
","Active: No power issue, site is on grid with Ubaie=3D53V, lionel tchatch=
oua(694693436) from Huawei is informed","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
: No power issue, site is on grid with Ubaie=3D53V, lionel tchatchoua(69469=
3436) from Huawei is informed","emmanuel.ghani@ihstowers.com","376","28-07-=
2024 23:48:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0002722008","A=
bome","","28-07-2024 20:59:10","28-07-2024 19:45:48","28-07-2024 22:07:07",=
"Grid outage site went because Gen overlord (15Kva, 250A) // MDG OF 20KVA h=
as deployed(site swapped by ZTE)","MINKA NICOLAS","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage site went because Gen overlor=
d (15Kva, 250A) // MDG OF 20KVA has deployed(site swapped by ZTE)","ange.ko=
ngo@ihstowers.com","4403","28-07-2024 20:59:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002721759","M=
asque","","28-07-2024 20:08:57","28-07-2024 19:52:59","28-07-2024 20:00:13"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V    The TX FME  El=
oundou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice =
Pouakam","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3=
V   The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitiv=
e issue
","ange.kongo@ihstowers.com","959","28-07-2024 20:08:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_311","IHS_YND_453","NOCINC0002721517","S=
ong-bong","","28-07-2024 19:37:12","28-07-2024 19:32:07","29-07-2024 00:28:=
10","site went down because Gen started and stopped due to alarm under Volt=
age//he reset Gen card and Started Gen","Kemeni Franklin","Equipment Repair=
","Passive","ACDG Gen","ACDG - Control Panel","site went down because Gen s=
tarted and stopped due to alarm under Voltage//he reset Gen card and Starte=
d Gen","ange.kongo@ihstowers.com","307","28-07-2024 19:37:12","Sagemcom CMR=
"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0002721423","Abo=
me","","28-07-2024 19:14:47","28-07-2024 19:08:41","28-07-2024 19:23:23","G=
rid outage site went down because Gen started and stopped due to Gen Overlo=
ad (15kva ;125 A) // Grid return","MINKA NICOLAS","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage site went down because Gen st=
arted and stopped due to Gen Overload (15kva ;125 A) // Grid return","ludiv=
ine.ngamaleu@ihstowers.com","368","28-07-2024 19:14:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0002721348","Bitoto",=
"","28-07-2024 19:00:20","28-07-2024 18:55:46","28-07-2024 18:59:46","Casca=
ded Incident from TTO2523897","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down before ge=
n start due to poor battery backup // Gen start automaticaly","system","274=
","28-07-2024 19:00:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0002721349","Essomba"=
,"","28-07-2024 19:00:20","28-07-2024 18:55:46","28-07-2024 18:59:46","Casc=
aded Incident from TTO2523897","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before g=
en start due to poor battery backup // Gen start automaticaly","system","27=
4","28-07-2024 19:00:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002721347","B=
iteng","IHS_YND_292, IHS_YND_179","28-07-2024 18:58:51","28-07-2024 18:55:4=
6","28-07-2024 19:06:02","Grid outage, site went down before gen start due =
to poor battery backup // Gen start automaticaly","Mba Lazare Herve","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down before gen start due to poor battery backup // Gen s=
tart automaticaly","ange.kongo@ihstowers.com","187","28-07-2024 18:58:51","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002721341","Matsari"=
,"","28-07-2024 18:58:00","28-07-2024 18:45:59","28-07-2024 18:46:59","Casc=
aded Incident from TTO2523879","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen  with U =3D=
 51V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane  Willy =
650254398 of Huawei is informed","system","721","28-07-2024 18:58:00","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002721342","Yoko OCM=
","","28-07-2024 18:58:00","28-07-2024 18:45:59","28-07-2024 18:46:59","Cas=
caded Incident from TTO2523879","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen  with U =
=3D 51V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane  Wil=
ly 650254398 of Huawei is informed","system","721","28-07-2024 18:58:00","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002721343","Ngouetou=
","","28-07-2024 18:58:00","28-07-2024 18:45:59","28-07-2024 18:46:59","Cas=
caded Incident from TTO2523879","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on Gen  with U =
=3D 51V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane  Wil=
ly 650254398 of Huawei is informed","system","721","28-07-2024 18:58:00","S=
agemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002721344","MBIMBIM"=
,"","28-07-2024 18:58:00","28-07-2024 18:45:59","28-07-2024 18:46:59","Casc=
aded Incident from TTO2523879","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on Gen  with U =3D=
 51V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane  Willy =
650254398 of Huawei is informed","system","721","28-07-2024 18:58:00","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002721340","Ngoum","=
","28-07-2024 18:58:00","28-07-2024 18:45:59","28-07-2024 18:46:59","Cascad=
ed Incident from TTO2523879","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on Gen  with U =3D 5=
1V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane  Willy 65=
0254398 of Huawei is informed","system","721","28-07-2024 18:58:00","Sagemc=
om CMR"
"Closed Complete","Site Down","T2400","IHS_YND_249","NOCINC0002721273","Bit=
eng-Maetur","","28-07-2024 18:44:47","28-07-2024 18:33:07","28-07-2024 20:3=
2:36","Grid outage Site went down because gen ran until fuel shortage//Refu=
eling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Out=
age","Grid outage Site went down because gen ran until fuel shortage//Refue=
ling done","ludivine.ngamaleu@ihstowers.com","3138","28-07-2024 18:44:47","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0002721248","M=
adison","","28-07-2024 18:39:21","28-07-2024 16:53:57","28-07-2024 17:02:26=
","Grid outage no space to deployed a mobil gen // Grid return","MFOUAGUEGU=
E MATHIEU","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid outage no space to deployed a mobil gen // Grid return","ange.kong=
o@ihstowers.com","6324","28-07-2024 18:39:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002720758","M=
asque","","28-07-2024 16:53:28","28-07-2024 16:48:21","28-07-2024 17:16:57"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V, The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V,=
 The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive i=
ssue","ange.kongo@ihstowers.com","309","28-07-2024 16:53:28","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_295","NOCINC0002720579","NGONA","=
","28-07-2024 16:30:30","28-07-2024 16:27:21","28-07-2024 16:40:07","ACTIVE=
 no power issue U=3D53.2V site on Gen  lionel adjed//655184876 from huawei =
is working on site","Mba Lazare Herve","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE no power issue U=
=3D53.2V site on Gen  lionel adjed//655184876 from huawei is working on sit=
e","ange.kongo@ihstowers.com","192","28-07-2024 16:30:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0002720354","N=
sam Sofavinc T0","","28-07-2024 16:08:35","28-07-2024 14:26:14","28-07-2024=
 17:06:06","Grid outage site went down because Gen started and stopped due =
to Gen Overload (09kva ;150 A) // Grid return","MINKA NICOLAS","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","Grid outage site went down b=
ecause Gen started and stopped due to Gen Overload (09kva ;150 A) // Grid r=
eturn","ange.kongo@ihstowers.com","6142","28-07-2024 16:08:35","Sagemcom CM=
R"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0002720308","ODZ=
A BORNE 10","","28-07-2024 15:49:10","28-07-2024 15:44:03","28-07-2024 16:1=
2:05","No power issue on site U=3D53v site on grid Lionel adjed of huawei i=
s informed","Albran Byorel","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53v site=
 on grid Lionel adjed of huawei is informed","ludivine.ngamaleu@ihstowers.c=
om","309","28-07-2024 15:49:10","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002720277","Ess=
os Marche","","28-07-2024 15:42:48","28-07-2024 15:39:43","28-07-2024 17:09=
:49","grid outage, site went down because Gen started and stopped due to ""=
high temp"" alarm //He added water and gen manually started the site remain=
 down after the power reset tx fme armand/691144442 from h","Delor Telezing=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","grid outage, site went down because Gen started and stopped=
 due to ""high temp"" alarm //He added water and gen manually started the s=
ite remain down after the power reset tx fme armand/691144442 from huawei i=
s informed","ludivine.ngamaleu@ihstowers.com","186","28-07-2024 15:42:48","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0002720267","Crf Corn=
ier","","28-07-2024 15:41:30","28-07-2024 15:35:35","28-07-2024 16:31:02","=
Cascaded Incident from TTO2522724","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage no space to deployed a =
mobil gen // Grid return","system","355","28-07-2024 15:41:30","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0002720261","M=
adison","IHS_YND_566","28-07-2024 15:40:40","28-07-2024 15:35:35","28-07-20=
24 16:31:02","Grid outage no space to deployed a mobil gen // Grid return",=
"MFOUAGUEGUE MATHIEU","Grid Supply","Passive","Grid","National Grid - Grid =
Outage Issue","Grid outage no space to deployed a mobil gen // Grid return"=
,"ange.kongo@ihstowers.com","308","28-07-2024 15:40:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0002720163","Essomba"=
,"","28-07-2024 15:21:30","28-07-2024 15:18:00","28-07-2024 15:22:00","Casc=
aded Incident from TTO2522616","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before g=
en start due to poor battery backup // Gen start automaticaly","system","21=
0","28-07-2024 15:21:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0002720162","Bitoto",=
"","28-07-2024 15:21:30","28-07-2024 15:18:00","28-07-2024 15:22:00","Casca=
ded Incident from TTO2522616","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down before ge=
n start due to poor battery backup // Gen start automaticaly","system","210=
","28-07-2024 15:21:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002720155","B=
iteng","IHS_YND_292, IHS_YND_179","28-07-2024 15:20:08","28-07-2024 15:18:0=
0","28-07-2024 15:24:00","Grid outage, site went down before gen start due =
to poor battery backup // Gen start automaticaly","Mba Lazare Herve","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down before gen start due to poor battery backup // Gen s=
tart automaticaly","ange.kongo@ihstowers.com","129","28-07-2024 15:20:08","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0002720116","Lobo OCM=
","","28-07-2024 15:05:10","28-07-2024 14:57:12","28-07-2024 15:02:16","Cas=
caded Incident from TTO2522560","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage site went down =
before Gen started due to poor battery back up // Gen started automatically=
","system","478","28-07-2024 15:05:10","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002720112","N=
KOMEKUI OCM","IHS_YND_341","28-07-2024 15:03:23","28-07-2024 14:57:12","28-=
07-2024 15:02:16","Grid outage site went down before Gen started due to poo=
r battery back up // Gen started automatically","TIENTCHEU NZETCHIEU GAEL",=
"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low",=
"Grid outage site went down before Gen started due to poor battery back up =
// Gen started automatically","ange.kongo@ihstowers.com","372","28-07-2024 =
15:03:23","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0002719976","Nko=
lbisson usines des eaux 2","","28-07-2024 14:28:03","28-07-2024 14:25:59","=
28-07-2024 14:47:55","grid poutage,site went down  due to gen overload 9kva=
 115A//he reduice the load of site","TIENTCHEU NZETCHIEU GAEL","Equipment R=
epair","Passive","ACDG Gen","ACDG - Overload","grid poutage,site went down =
 due to gen overload 9kva 115A//he reduice the load of site","ludivine.ngam=
aleu@ihstowers.com","126","28-07-2024 14:28:03","Sagemcom CMR"
"Closed Complete","Site Down","T1281","IHS_YND_283","NOCINC0002719893","Abo=
me","","28-07-2024 14:14:05","28-07-2024 14:09:47","28-07-2024 17:38:16","G=
rid outage site went down because Gen started and stopped due to Gen Overlo=
ad (15kva ;125 A) // Grid return","MINKA NICOLAS","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - Overload","Grid outage site went down because Gen st=
arted and stopped due to Gen Overload (15kva ;125 A) // Grid return","ludiv=
ine.ngamaleu@ihstowers.com","1752","28-07-2024 14:14:05","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0002719890","MVA=
N SACEL","","28-07-2024 14:13:26","28-07-2024 14:08:21","28-07-2024 14:14:2=
1","Grid outage site went down before Gen started due to poor battery back =
up // Gen started automatically(site swapped by ZTE)","MINKA NICOLAS","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 outage site went down before Gen started due to poor battery back up // Ge=
n started automatically(site swapped by ZTE)","ludivine.ngamaleu@ihstowers.=
com","306","28-07-2024 14:13:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0002719811","Ndogbess=
ol","","28-07-2024 13:54:00","28-07-2024 13:44:29","28-07-2024 14:10:26","C=
ascaded Incident from TTO2522238","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen failed to start du=
e to fuse of contactor Ge faulty//he did a bridge and started the Gen","sys=
tem","571","28-07-2024 13:54:00","Sagemcom CMR"
"Closed Complete","Site Down","T0139","IHS_YND_381","NOCINC0002719805","Bou=
mnyebel","IHS_EDA_056","28-07-2024 13:52:51","28-07-2024 13:44:29","28-07-2=
024 14:10:26","grid outage,gen failed to start due to fuse of contactor Ge =
faulty//he did a bridge and started the Gen","Kemeni Franklin","Equipment R=
epair","Passive","ACDG Gen","ACDG - Load Contactor","grid outage,gen failed=
 to start due to fuse of contactor Ge faulty//he did a bridge and started t=
he Gen","dorothy.djantio@ihstowers.com","547","28-07-2024 13:52:51","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0002719157","Crf Corn=
ier","","28-07-2024 11:24:30","28-07-2024 11:14:29","28-07-2024 11:57:33","=
Cascaded Incident from TTO2521567","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage.no space to deploy mobi=
le generator//Grid return","system","601","28-07-2024 11:24:30","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0002719153","M=
adison","IHS_YND_566","28-07-2024 11:23:41","28-07-2024 11:14:29","28-07-20=
24 11:57:33","Grid outage.no space to deploy mobile generator//Grid return"=
,"MFOUAGUEGUE MATHIEU","Grid Supply","Passive","Grid","National Grid - Grid=
 Outage Issue","Grid outage.no space to deploy mobile generator//Grid retur=
n","etienne.itondo@ihstowers.com","553","28-07-2024 11:23:41","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_342","NOCINC0002718770","LOBO MTN=
","","28-07-2024 09:50:11","28-07-2024 09:43:16","28-07-2024 11:47:40","Cas=
caded Incident from TTO2521121","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Site was on gen, Site went =
down because gen ran until fuel shortage//Refueling done","system","415","2=
8-07-2024 09:50:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_713","NOCINC0002718771","NKONGKAR=
AK","","28-07-2024 09:50:11","28-07-2024 09:43:16","28-07-2024 11:47:40","C=
ascaded Incident from TTO2521121","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Passive","Cascade Passive","Cascade Passive","Site was on gen, Site wen=
t down because gen ran until fuel shortage//Refueling done","system","415",=
"28-07-2024 09:50:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_714","NOCINC0002718769","Ekekam",=
"","28-07-2024 09:50:11","28-07-2024 09:43:16","28-07-2024 11:47:40","Casca=
ded Incident from TTO2521121","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site was on gen, Site went do=
wn because gen ran until fuel shortage//Refueling done","system","415","28-=
07-2024 09:50:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0002718768","Nkongtoc=
k","","28-07-2024 09:50:11","28-07-2024 09:43:16","28-07-2024 11:47:40","Ca=
scaded Incident from TTO2521121","Kemeni Franklin","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site was on gen, Site went down bec=
ause gen ran until fuel shortage//Refueling done","system","415","28-07-202=
4 09:50:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_421","NOCINC0002718765","Bot Maka=
k","","28-07-2024 09:50:10","28-07-2024 09:43:16","28-07-2024 11:47:40","Ca=
scaded Incident from TTO2521121","","Cascade Outage","Passive","Cascade Pas=
sive","Cascade Passive","Site was on gen, Site went down because gen ran un=
til fuel shortage//Refueling done","system","414","28-07-2024 09:50:10","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0002718764","Ebeba","=
","28-07-2024 09:50:10","28-07-2024 09:43:16","28-07-2024 11:47:40","Cascad=
ed Incident from TTO2521121","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site was on gen, Site went down because gen=
 ran until fuel shortage//Refueling done","system","414","28-07-2024 09:50:=
10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_366","NOCINC0002718766","Mandoumb=
a MTN","","28-07-2024 09:50:10","28-07-2024 09:43:16","28-07-2024 11:47:40"=
,"Cascaded Incident from TTO2521121","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Site was on gen, Site went down=
 because gen ran until fuel shortage//Refueling done","system","414","28-07=
-2024 09:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_347","NOCINC0002718762","Nkeng li=
kok","","28-07-2024 09:50:10","28-07-2024 09:43:16","28-07-2024 11:47:40","=
Cascaded Incident from TTO2521121","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site was on gen, Site went down b=
ecause gen ran until fuel shortage//Refueling done","system","414","28-07-2=
024 09:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_783","NOCINC0002718761","Lobo 2",=
"","28-07-2024 09:50:10","28-07-2024 09:43:16","28-07-2024 11:47:40","Casca=
ded Incident from TTO2521121","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site was on gen, Site went do=
wn because gen ran until fuel shortage//Refueling done","system","414","28-=
07-2024 09:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0002718763","Ngog Map=
ubi","","28-07-2024 09:50:10","28-07-2024 09:43:16","28-07-2024 11:47:40","=
Cascaded Incident from TTO2521121","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Site was on gen, Site went down b=
ecause gen ran until fuel shortage//Refueling done","system","414","28-07-2=
024 09:50:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_376","IHS_YND_113","NOCINC0002718755","E=
mombo 2","","28-07-2024 09:48:57","28-07-2024 09:39:46","28-07-2024 10:43:4=
4","Grid outage.gen failed to star due to automation malfunctionning//gen m=
anually started (investigation ongoing)","MINKA NICOLAS","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Control Panel","Grid outage.gen failed to sta=
r due to automation malfunctionning//gen manually started (investigation on=
going)","etienne.itondo@ihstowers.com","553","28-07-2024 09:48:57","Sagemco=
m CMR"
"Closed Complete","Site Down","T0236","IHS_YND_373","NOCINC0002718740","Mal=
oun","IHS_YND_783, IHS_YND_347, IHS_YND_419, IHS_YND_339, IHS_YND_421, IHS_=
YND_366, IHS_EDA_101, IHS_YND_349, IHS_YND_714, IHS_YND_342, IHS_YND_713","=
28-07-2024 09:45:29","28-07-2024 09:37:21","28-07-2024 11:47:40","Site was =
on gen, Site went down because gen ran until fuel shortage//Refueling done"=
,"Kemeni Franklin","Fuel Outage","Passive","Diesel","Diesel Outage","Site w=
as on gen, Site went down because gen ran until fuel shortage//Refueling do=
ne","dorothy.djantio@ihstowers.com","1450","28-07-2024 09:45:29","Sagemcom =
CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002718728","Ess=
os Marche","","28-07-2024 09:42:15","28-07-2024 09:39:05","28-07-2024 13:15=
:00","ACTIVE No power issue on site, site on Grid with Ubaie=3D54,8V Tx fme=
 Armand Ngeutsa from Huawei is Informed ","Delor Telezing","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTI=
VE No power issue on site, site on Grid with Ubaie=3D54,8V Tx fme Armand Ng=
eutsa from Huawei is Informed ","dorothy.djantio@ihstowers.com","191","28-0=
7-2024 09:42:15","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0002718203","N=
yanon","","28-07-2024 08:01:05","28-07-2024 07:51:57","28-07-2024 08:24:09"=
,"site went down  because Gen failed to start due to Hybrid system dysfonct=
ion// He reset the Hybrid system and Gen automatically started","TIENTCHEU =
NZETCHIEU GAEL","Equipment Repair","Passive","Hybrid","Hybrid Module","site=
 went down  because Gen failed to start due to Hybrid system dysfonction// =
He reset the Hybrid system and Gen automatically started","etienne.itondo@i=
hstowers.com","550","28-07-2024 08:01:05","Sagemcom CMR"
"Closed Complete","Site Down","T0837","IHS_YND_460","NOCINC0002718196","Mat=
sari","","28-07-2024 07:58:01","28-07-2024 07:51:54","28-07-2024 07:55:01",=
"Site went down due to work (EDONDE COMPANY // Refueling on site )// end of=
 work,","Parker Tchoup","Installation Activity","Passive","Planned Activity=
","Installation Activity","Site went down due to work (EDONDE COMPANY // Re=
fueling on site )// end of work,","dorothy.djantio@ihstowers.com","368","28=
-07-2024 07:58:01","Sagemcom CMR"
"Closed Complete","Site Down","T1250","IHS_YND_799","NOCINC0002718150","Mes=
sassi Ngonlonk","","28-07-2024 07:40:00","28-07-2024 07:33:51","28-07-2024 =
07:55:50","Grid outage gen failed to start due to battery GE faulty//Grid r=
eturn ","Fabrice Pouakam","Equipment Repair","Passive","ACDG Gen","ACDG - G=
enerator Battery","Grid outage gen failed to start due to battery GE faulty=
//Grid return ","dorothy.djantio@ihstowers.com","371","28-07-2024 07:40:00"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0002718024","ODZ=
A BORNE 10","","28-07-2024 06:55:05","28-07-2024 06:49:55","28-07-2024 07:3=
0:55","Active: No power issue on site, U=3D54,3V on grid, The TX FME Lionel=
 steve Adjep is informed","Albran Byorel","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issu=
e on site, U=3D54,3V on grid, The TX FME Lionel steve Adjep is informed","d=
orothy.djantio@ihstowers.com","311","28-07-2024 06:55:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002718005","M=
asque","","28-07-2024 06:48:53","28-07-2024 06:40:47","28-07-2024 07:30:55"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V, The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V,=
 The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive i=
ssue","etienne.itondo@ihstowers.com","488","28-07-2024 06:48:53","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002716980","N=
koabang2","","28-07-2024 00:56:41","28-07-2024 00:52:36","28-07-2024 02:59:=
45","grid on outage, site wen down because gen start and stopped due to fue=
l pump faulty // He replace the fuel pump and gen manually started ","Mba L=
azare Herve","Fuel Outage (Probable)","Passive","ACDG Gen","ACDG - Fuel Pum=
p","grid on outage, site wen down because gen start and stopped due to fuel=
 pump faulty // He replace the fuel pump and gen manually started ","landry=
.etame@ihstowers.com","356","28-07-2024 00:56:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0002716764","Essomba"=
,"","27-07-2024 23:57:00","27-07-2024 23:53:48","27-07-2024 23:57:47","Casc=
aded Incident from TTO2518971","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage, site went down before g=
en start due to poor battery backup // Gen start automaticaly","system","19=
2","27-07-2024 23:57:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0002716763","Bitoto",=
"","27-07-2024 23:57:00","27-07-2024 23:53:48","27-07-2024 23:57:47","Casca=
ded Incident from TTO2518971","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage, site went down before ge=
n start due to poor battery backup // Gen start automaticaly","system","192=
","27-07-2024 23:57:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002716759","B=
iteng","IHS_YND_292, IHS_YND_179","27-07-2024 23:55:53","27-07-2024 23:53:4=
8","27-07-2024 23:57:47","Grid outage, site went down before gen start due =
to poor battery backup // Gen start automaticaly","Mba Lazare Herve","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid =
outage, site went down before gen start due to poor battery backup // Gen s=
tart automaticaly","landry.etame@ihstowers.com","126","27-07-2024 23:55:53"=
,"Sagemcom CMR"
"Closed Complete","Warning","CTR_378","IHS_YND_254","NOCINC0002716471","Mvo=
g-Manga","","27-07-2024 22:45:14","","","","Albran Byorel","Warning","Warni=
ng","Unlisted RCA","Warning - Others","Bad LOg","landry.etame@ihstowers.com=
","11945","27-07-2024 22:45:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0002716437","S=
imbock OCM","","27-07-2024 22:37:35","27-07-2024 21:15:18","27-07-2024 21:1=
6:59","No power issue site on grid with U=3D54.8v Hosiah(674007438) from Hu=
awei is informed .Notice that we have disjunction at OCM Equipements","Hyem=
afo Gildas","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","No power issue site on grid with U=3D54.8v Hosiah(6=
74007438) from Huawei is informed .Notice that we have disjunction at OCM E=
quipements","landry.etame@ihstowers.com","4939","27-07-2024 22:37:35","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002716396","M=
asque","","27-07-2024 22:27:24","27-07-2024 22:08:11","28-07-2024 00:15:53"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3V, The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3V,=
 The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive i=
ssue","landry.etame@ihstowers.com","1154","27-07-2024 22:27:24","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0002715608","Lobo OCM=
","","27-07-2024 19:33:50","27-07-2024 19:29:57","27-07-2024 19:39:42","Cas=
caded Incident from TTO2517656","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive"," Grid outage, site went dow=
n before Gen start due to poor battery backup // Gen automatically started
","system","233","27-07-2024 19:33:50","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002715592","N=
KOMEKUI OCM","IHS_YND_341","27-07-2024 19:33:01","27-07-2024 19:29:57","27-=
07-2024 19:39:42"," Grid outage, site went down before Gen start due to poo=
r battery backup // Gen automatically started","TIENTCHEU NZETCHIEU GAEL","=
Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low","=
 Grid outage, site went down before Gen start due to poor battery backup //=
 Gen automatically started
","emmanuel.ghani@ihstowers.com","187","27-07-2024 19:33:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0002715525","Boumnyeb=
el","","27-07-2024 19:16:30","27-07-2024 19:10:13","27-07-2024 19:12:14","C=
ascaded Incident from TTO2517566","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive"," Grid outage, site went down befor=
e Gen start due to poor battery backup // Gen automatically started","syste=
m","377","27-07-2024 19:16:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0002715526","Mamb",""=
,"27-07-2024 19:16:30","27-07-2024 19:10:13","27-07-2024 19:12:14","Cascade=
d Incident from TTO2517566","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive"," Grid outage, site went down before Gen =
start due to poor battery backup // Gen automatically started","system","37=
7","27-07-2024 19:16:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0002715522","Ndogbess=
ol","","27-07-2024 19:16:30","27-07-2024 19:10:13","27-07-2024 19:12:14","C=
ascaded Incident from TTO2517566","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive"," Grid outage, site went down befor=
e Gen start due to poor battery backup // Gen automatically started","syste=
m","377","27-07-2024 19:16:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0002715524","Ngog Map=
ubi","","27-07-2024 19:16:30","27-07-2024 19:10:13","27-07-2024 19:12:14","=
Cascaded Incident from TTO2517566","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive"," Grid outage, site went down befo=
re Gen start due to poor battery backup // Gen automatically started","syst=
em","377","27-07-2024 19:16:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0002715510","B=
oumnyebel OCM","IHS_EDA_114, IHS_EDA_056, IHS_EDA_063, IHS_YND_419, IHS_YND=
_381, IHS_YND_376, IHS_EDA_060","27-07-2024 19:13:21","27-07-2024 19:10:13"=
,"27-07-2024 19:12:14"," Grid outage, site went down before Gen start due t=
o poor battery backup // Gen automatically started","Kemeni Franklin","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low"," Gri=
d outage, site went down before Gen start due to poor battery backup // Gen=
 automatically started","emmanuel.ghani@ihstowers.com","190","27-07-2024 19=
:13:21","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002715372","Eko=
unou","","27-07-2024 18:34:41","27-07-2024 18:28:37","27-07-2024 18:38:29",=
" Grid outage, site went down before Gen start due to poor battery backup /=
/ Gen automatically started","Albran Byorel","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low"," Grid outage, site went down =
before Gen start due to poor battery backup // Gen automatically started","=
joelle.ekessi@ihstowers.com","365","27-07-2024 18:34:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002715335","M=
arche Odza","","27-07-2024 18:28:03","27-07-2024 18:25:58","27-07-2024 21:3=
5:21","Active//No power issue on site,site on Grid with Ubaie=3D54,5 V TX F=
ME Lionel steve/655184876 from Huawei is informed , repetitif issue","Albra=
n Byorel","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active//No power issue on site,site on Grid with Ubai=
e=3D54,5 V TX FME Lionel steve/655184876 from Huawei is informed , repetiti=
f issue","emmanuel.ghani@ihstowers.com","129","27-07-2024 18:28:03","Sagemc=
om CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002715115","Eko=
unou","","27-07-2024 17:46:49","27-07-2024 17:44:41","27-07-2024 17:53:34",=
" Grid outage, site went down before Gen start due to poor battery backup /=
/ Grid power return ( down behing TTO2515498 )","Albran Byorel","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Battery Low"," Grid outa=
ge, site went down before Gen start due to poor battery backup // Grid powe=
r return","joelle.ekessi@ihstowers.com","129","27-07-2024 17:46:49","Sagemc=
om CMR"
"Closed Complete","Site Down","T1241","IHS_YND_794","NOCINC0002715020","Nko=
ulou Carriere carrefourt","","27-07-2024 17:23:23","27-07-2024 17:09:18","2=
7-07-2024 18:02:25","grid outage, site went down because gen failed to star=
t due to relay of gen faulty// He changed relay of gen and gen manually sta=
rted","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Re=
lay Faulty","grid outage, site went down because gen failed to start due to=
 relay of gen faulty// He changed relay of gen and gen manually started","j=
oelle.ekessi@ihstowers.com","846","27-07-2024 17:23:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0002714804","B=
astos Bethesda","","27-07-2024 16:41:57","27-07-2024 16:40:51","27-07-2024 =
16:49:51","Grid outage site went down before gen started due to poor batter=
y backup // Gen started automatically","Mboua Thierry","Equipment Repair","=
Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site we=
nt down before gen started due to poor battery backup // Gen started automa=
tically","emmanuel.ghani@ihstowers.com","68","27-07-2024 16:41:57","Sagemco=
m CMR"
"Closed Complete","Site Down","T3179","IHS_YND_289","NOCINC0002714788","Nko=
langaa","","27-07-2024 16:38:32","27-07-2024 16:29:26","27-07-2024 17:55:43=
","grid outage, site went down because Gen started and stopped due to ""hig=
h temp"" alarm //He added water and gen manually started","Mba Lazare Herve=
","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - Coolan=
t Level Issue","grid outage, site went down because Gen started and stopped=
 due to ""high temp"" alarm //He added water and gen manually started","joe=
lle.ekessi@ihstowers.com","547","27-07-2024 16:38:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0002714640","Kondengu=
i","","27-07-2024 16:14:01","27-07-2024 16:10:10","27-07-2024 17:54:13","Ca=
scaded Incident from TTO2516614","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage no space to deployed a mo=
bile Gen // grid return","system","231","27-07-2024 16:14:01","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0002714631","E=
mombo-Tchad","IHS_YND_114","27-07-2024 16:13:14","27-07-2024 16:10:10","27-=
07-2024 17:54:13","Grid Outage. No space to deploy the MDG waiting Grid ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid outage no space to deployed a mobile Gen // grid return","emmanuel.gh=
ani@ihstowers.com","186","27-07-2024 16:13:14","Sagemcom CMR"
"Closed Complete","Site Down","T3446","IHS_YND_712","NOCINC0002714569","Nko=
lkoumou OCM","","27-07-2024 16:02:11","27-07-2024 15:55:05","27-07-2024 16:=
51:05","grid outage,gen failed to start due battery Ge faulty//Gen started =
with battery backup","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive=
","ACDG Gen","ACDG - Generator Battery","grid outage,gen failed to start du=
e battery Ge faulty//Gen started with battery backup","joelle.ekessi@ihstow=
ers.com","630","27-07-2024 16:02:11","Sagemcom CMR"
"Closed Complete","Site Down","T2829","IHS_YND_526","NOCINC0002714514","Nko=
abang2","","27-07-2024 15:52:18","27-07-2024 15:48:13","27-07-2024 16:14:05=
","grid outage,gen failed to start due to pear pierced//he clogged the pear=
 and restarted DG","Mba Lazare Herve","Fuel Outage (Probable)","Passive","A=
CDG Gen","ACDG - Fuel Pump","grid outage,gen failed to start due to pear pi=
erced//he clogged the pear and restarted DG","joelle.ekessi@ihstowers.com",=
"246","27-07-2024 15:52:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0002714494","M=
ontee-Anne-Rouge","","27-07-2024 15:46:46","27-07-2024 13:57:39","27-07-202=
4 17:23:25","Grid Outage. No space to deploy the MDG // Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outag=
e. No space to deploy the MDG // Grid return","emmanuel.ghani@ihstowers.com=
","6549","27-07-2024 15:46:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_262","IHS_YND_150","NOCINC0002714487","N=
kol-Mbanda","","27-07-2024 15:45:33","27-07-2024 13:26:24","27-07-2024 14:4=
0:50","grid outage, site went down due to Gen overload (20KVA; 320A )// gri=
d return","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - O=
verload","grid outage, site went down due to Gen overload (20KVA; 320A )// =
grid return","emmanuel.ghani@ihstowers.com","8350","27-07-2024 15:45:33","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002714190","M=
asque","","27-07-2024 15:01:59","27-07-2024 14:58:52","27-07-2024 15:55:49"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","emm=
anuel.ghani@ihstowers.com","189","27-07-2024 15:01:59","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002714099","Mim=
boman3","","27-07-2024 14:44:32","27-07-2024 14:39:27","27-07-2024 14:49:02=
","Grid outage site went down because Gen failed to start due to poor batte=
ry backup//Grid power return","Mba Lazare Herve","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage site went dow=
n because Gen failed to start due to poor battery backup//Grid power return=
","joelle.ekessi@ihstowers.com","308","27-07-2024 14:44:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_338","NOCINC0002714070","Okola OC=
M","","27-07-2024 14:35:10","27-07-2024 14:32:42","27-07-2024 15:00:10","Ca=
scaded Incident from TTO2516042","TIENTCHEU NZETCHIEU GAEL","Cascade Outage=
","Active","Cascade Active","Cascade Active","No power issue on site Ubaie =
53.8V on GEN. Gregoire (652070658/Huawei) is informed","system","148","27-0=
7-2024 14:35:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_232","NOCINC0002713712","Crf-Nkol=
bisson","","27-07-2024 13:25:30","27-07-2024 13:12:21","27-07-2024 15:00:18=
","Cascaded Incident from TTO2515661","TIENTCHEU NZETCHIEU GAEL","Cascade O=
utage","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D53v site on gen Team JOSEPH/670 836468/ZTE working on site ","system","7=
89","27-07-2024 13:25:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_271","NOCINC0002713711","Yona Hot=
el","","27-07-2024 13:25:30","27-07-2024 13:12:21","27-07-2024 15:00:18","C=
ascaded Incident from TTO2515661","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue on site U=3D5=
3v site on gen Team JOSEPH/670 836468/ZTE working on site ","system","789",=
"27-07-2024 13:25:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_233","NOCINC0002713710","Oyomaban=
g OCM","","27-07-2024 13:25:30","27-07-2024 13:12:21","27-07-2024 15:00:18"=
,"Cascaded Incident from TTO2515661","TIENTCHEU NZETCHIEU GAEL","Cascade Ou=
tage","Active","Cascade Active","Cascade Active","No power issue on site U=
=3D53v site on gen Team JOSEPH/670 836468/ZTE working on site ","system","7=
89","27-07-2024 13:25:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_333","IHS_YND_273","NOCINC0002713696","N=
kolbi-Boss","IHS_YND_233, IHS_YND_271, IHS_YND_232, IHS_YND_286","27-07-202=
4 13:22:35","27-07-2024 13:12:21","27-07-2024 15:55:18","No power issue on =
site U=3D53v site on gen Team JOSEPH/670 836468/ZTE working on site ","TIEN=
TCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power issue on site U=3D53v site on ge=
n Team JOSEPH/670 836468/ZTE working on site ","ange.kongo@ihstowers.com","=
616","27-07-2024 13:22:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_255","IHS_YND_286","NOCINC0002713669","D=
agobert","","27-07-2024 13:16:59","27-07-2024 13:12:21","27-07-2024 15:00:1=
8","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade Active"=
,"Cascade Active","No power issue on site U=3D53v site on gen Team JOSEPH/6=
70 836468/ZTE working on site ","ange.kongo@ihstowers.com","839","27-07-202=
4 13:16:59","Sagemcom CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0002713618","Men=
dong Plateau","IHS_YND_742, IHS_YND_237, IHS_YND_151","27-07-2024 13:04:15"=
,"27-07-2024 12:45:08","27-07-2024 12:47:55","Grid outage site went down be=
fore Gen started due to poor battery back up // Grid return","Hyemafo Gilda=
s","Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Lo=
w","Grid outage site went down before Gen started due to poor battery back =
up // Grid return","ludivine.ngamaleu@ihstowers.com","1148","27-07-2024 13:=
04:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0002713591","T=
ongolo OCM","","27-07-2024 12:58:02","27-07-2024 12:44:56","27-07-2024 12:4=
9:38","Site went down due to PWC OVERLOAD ( 12Kw, 200A) // Site stabilized"=
,"Delor Telezing","Equipment Repair","Passive","Control Panel","Panel Distr=
ibution Board","Site went down due to PWC OVERLOAD ( 12Kw, 200A) // Site st=
abilized","ange.kongo@ihstowers.com","787","27-07-2024 12:58:02","Sagemcom =
CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0002713572","Car=
refour Simbock","","27-07-2024 12:56:14","27-07-2024 12:45:08","27-07-2024 =
12:47:55","tikect need to cascade at Mendong plateau","Hyemafo Gildas","Cas=
cade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage sit=
e went down before Gen started due to poor battery back up // Grid return",=
"ludivine.ngamaleu@ihstowers.com","23172","27-07-2024 12:56:14","Sagemcom C=
MR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0002713570","Men=
dong NB","","27-07-2024 12:55:34","27-07-2024 12:45:08","27-07-2024 12:47:5=
5","Grid outage site went down before Gen started due to poor battery back =
up // Grid return","","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage site went down before Gen started due to poor batter=
y back up // Grid return","ludivine.ngamaleu@ihstowers.com","23202","27-07-=
2024 12:55:34","Sagemcom CMR"
"Closed Complete","Site Down","T0466","IHS_YND_151","NOCINC0002713556","Tam=
tam Weekend","","27-07-2024 12:53:31","27-07-2024 12:45:08","27-07-2024 12:=
47:55","Grid outage site went down before Gen started due to poor battery b=
ack up // Grid return","Hyemafo Gildas","Cascade Outage","Passive","Cascade=
 Passive","Cascade Passive","Grid outage site went down before Gen started =
due to poor battery back up // Grid return","ludivine.ngamaleu@ihstowers.co=
m","23225","27-07-2024 12:53:31","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0002713542","MVA=
N SACEL","","27-07-2024 12:50:36","27-07-2024 12:44:32","27-07-2024 13:00:5=
6","Grid outage site went down before Gen started due to poor battery back =
up // Gen started automatically","MINKA NICOLAS","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage site went dow=
n before Gen started due to poor battery back up // Gen started automatical=
ly","ludivine.ngamaleu@ihstowers.com","365","27-07-2024 12:50:36","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0470","IHS_YND_022","NOCINC0002713537","Mvo=
g Ada","IHS_YND_004","27-07-2024 12:49:24","27-07-2024 12:39:08","27-07-202=
4 17:21:18","Grid outage no space to deployed a mobile Gen // grid return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid=
 outage no space to deployed a mobile Gen // grid return","ludivine.ngamale=
u@ihstowers.com","618","27-07-2024 12:49:24","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0002713506","Av =
Kennedy","","27-07-2024 12:40:32","27-07-2024 12:39:08","27-07-2024 17:21:1=
8","Grid outage no space to deployed a mobile Gen // grid return down behin=
g TTO2515498 )","","Cascade Outage","Passive","Cascade Passive","Cascade Pa=
ssive","Grid outage no space to deployed a mobile Gen // grid return","ludi=
vine.ngamaleu@ihstowers.com","1192","27-07-2024 12:40:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0002713297","L=
eboudi","","27-07-2024 11:56:00","27-07-2024 11:43:45","27-07-2024 11:50:19=
","site went down due to CB(80A) OCM disjuncted in PWC // He reamed the CB"=
,"TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Circuit Breaker Issue","site went down due to CB(80A) OCM di=
sjuncted in PWC // He reamed the CB","ange.kongo@ihstowers.com","736","27-0=
7-2024 11:56:00","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002713076","N=
KOMEKUI OCM","IHS_YND_468","27-07-2024 11:19:23","27-07-2024 11:15:18","27-=
07-2024 11:21:51","Grid outage site went down before Gen started due to poo=
r battery back up // Grid return","TIENTCHEU NZETCHIEU GAEL","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage s=
ite went down before Gen started due to poor battery back up // Grid return=
","ange.kongo@ihstowers.com","247","27-07-2024 11:19:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0002712840","Kondengu=
i","","27-07-2024 10:32:30","27-07-2024 10:12:29","27-07-2024 14:42:49","Ca=
scaded Incident from TTO2514730","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid Outage. No space to deploy the M=
DG //Grid return","system","1201","27-07-2024 10:32:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0002712833","E=
mombo-Tchad","IHS_YND_114","27-07-2024 10:31:35","27-07-2024 10:12:29","27-=
07-2024 14:42:49","Grid Outage. No space to deploy the MDG //Grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
Outage. No space to deploy the MDG //Grid return","ange.kongo@ihstowers.com=
","1147","27-07-2024 10:31:35","Sagemcom CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0002712814","R=
d-Pt-Express","","27-07-2024 10:29:02","27-07-2024 07:27:55","27-07-2024 13=
:31:08","No power issue on site U=3D54.2V, site on Grid. The TX FME Mbah HO=
SIAH //674007438 from HUAWEI Is informed, Notice that Disjunction in BTS Oc=
m","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","No power issue on site U=3D54.2V, site on Grid. The TX FM=
E Mbah HOSIAH //674007438 from HUAWEI Is informed, Notice that Disjunction =
in BTS Ocm","ange.kongo@ihstowers.com","10868","27-07-2024 10:29:02","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0002712668","Anguissa=
 New","","27-07-2024 10:00:00","27-07-2024 09:53:05","27-07-2024 14:45:27",=
"Cascaded Incident from TTO2514547","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid Outage. No space to deploy th=
e MDG // Grid return","system","415","27-07-2024 10:00:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0002712662","L=
abogenie","IHS_YND_568","27-07-2024 09:59:14","27-07-2024 09:53:05","27-07-=
2024 14:45:27","Grid Outage. No space to deploy the MDG // Grid return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Ou=
tage. No space to deploy the MDG // Grid return","ange.kongo@ihstowers.com"=
,"371","27-07-2024 09:59:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0002712522","O=
dza II","","27-07-2024 09:35:32","27-07-2024 06:56:10","27-07-2024 10:50:34=
","site went down due to CB 125A disjuncted in DC-BOX Ocm //he reamed the C=
B (site swapped by ZTE)","Albran Byorel","Equipment Repair","Passive","Cont=
rol Panel","Power Cabinet - Circuit Breaker Issue","site went down due to C=
B 125A disjuncted in DC-BOX Ocm //he reamed the CB (site swapped by ZTE)","=
ange.kongo@ihstowers.com","9565","27-07-2024 09:35:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_593","IHS_YND_309","NOCINC0002712473","L=
eboudi","","27-07-2024 09:19:38","27-07-2024 09:12:28","27-07-2024 10:15:04=
","site went down due to CB(80A) OCM disjuncted in PWC // He reamed the CB"=
,"TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","Control Panel","P=
ower Cabinet - Circuit Breaker Issue","site went down due to CB(80A) OCM di=
sjuncted in PWC // He reamed the CB","ange.kongo@ihstowers.com","431","27-0=
7-2024 09:19:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002712351","M=
arche Odza","","27-07-2024 09:06:31","27-07-2024 09:04:26","27-07-2024 09:0=
5:11","ACTIVE No power issue U=3D54,5V site on Grid TX FME Lionel steve/655=
184876 from Huawei is informed repetitif issue site UP at 09:05AM","Albran =
Byorel","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","ACTIVE No power issue U=3D54,5V site on Grid TX FME Lio=
nel steve/655184876 from Huawei is informed repetitif issue site UP at 09:0=
5AM","ange.kongo@ihstowers.com","127","27-07-2024 09:06:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0002712272","M=
imboman-Ecole","","27-07-2024 08:54:30","27-07-2024 08:13:23","27-07-2024 0=
9:56:07","Grid outage ,site went down because Gen stop with alarm low oil p=
ressure // He add oil and manually started the Gen","Mba Lazare Herve","Equ=
ipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage =
,site went down because Gen stop with alarm low oil pressure // He add oil =
and manually started the Gen","ange.kongo@ihstowers.com","2468","27-07-2024=
 08:54:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002712264","E=
mana","","27-07-2024 08:52:46","27-07-2024 08:46:41","27-07-2024 08:51:12",=
"Grid outage//MDG of 20kva has deployed","","Grid Supply","Passive","Grid",=
"National Grid - Grid Outage Issue","Grid outage//MDG of 20kva has deployed=
","ange.kongo@ihstowers.com","367","27-07-2024 08:52:46","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002712148","Nko=
l-Mbanda","","27-07-2024 08:21:43","27-07-2024 08:16:38","27-07-2024 10:44:=
41","Grid outage Site went down because Gen started and stopped due to Gen =
overload (15KVA ; 150A )//  Grid return","MINKA NICOLAS","Equipment Repair"=
,"Passive","ACDG Gen","ACDG - Overload","Grid outage Site went down because=
 Gen started and stopped due to Gen overload (15KVA ; 150A )//  Grid return=
","ludivine.ngamaleu@ihstowers.com","306","27-07-2024 08:21:43","Sagemcom C=
MR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002712146","Mim=
boman3","","27-07-2024 08:20:41","27-07-2024 08:15:36","27-07-2024 08:33:24=
","Grid outage site went down before gen started due to poor battery backup=
 // Gen started automatically","Mba Lazare Herve","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage site went do=
wn before gen started due to poor battery backup // Gen started automatical=
ly","ludivine.ngamaleu@ihstowers.com","306","27-07-2024 08:20:41","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002711772","M=
asque","","27-07-2024 06:47:24","27-07-2024 06:39:19","27-07-2024 09:01:09"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","ang=
e.kongo@ihstowers.com","486","27-07-2024 06:47:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0002703497","N=
GONA","","27-07-2024 01:15:56","27-07-2024 00:43:39","27-07-2024 06:15:46",=
"Site went down due to DC cable stolen on site // He instale a new DC cable=
 site up at OCM at 06:15 and still down at mtn due to fiber cable CUT the t=
x fme lionel ajep /655184876 from huawei is informe","Mba Lazare Herve","Si=
te Asset Theft","Theft","Theft","DC Cable Stolen","Site went down due to DC=
 cable stolen on site // He instale a new DC cable site up at OCM at 06:15 =
and still down at mtn due to fiber cable CUT the tx fme lionel ajep /655184=
876 from huawei is informed","kamga.virgile@ihstowers.com","1938","27-07-20=
24 01:15:56","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0002702002","N=
yanon","","27-07-2024 00:35:11","27-07-2024 00:17:55","27-07-2024 01:33:37"=
,"site went dowen because Gen failed to start due to Hybrid system dysfonct=
ion// He reset the Hybrid system and Gen automatically started","TIENTCHEU =
NZETCHIEU GAEL","Equipment Repair","Passive","Hybrid","Hybrid Module","site=
 went dowen because Gen failed to start due to Hybrid system dysfonction// =
He reset the Hybrid system and Gen automatically started","kamga.virgile@ih=
stowers.com","1037","27-07-2024 00:35:11","Sagemcom CMR"
"Cancelled","Warning","CTR_467","IHS_YND_281","NOCINC0002701760","Odza II",=
"","27-07-2024 00:18:55","","","","Albran Byorel","","","","","","kamga.vir=
gile@ihstowers.com","10488","27-07-2024 00:18:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0002701350","C=
ite-Verte","","26-07-2024 23:04:50","26-07-2024 22:33:40","27-07-2024 00:54=
:55","Grid outage //Grid return(swapping by ZTE )","","Grid Supply","Passiv=
e","Grid","National Grid - Grid Outage Issue","Grid outage //Grid return(sw=
apping by ZTE )","kamga.virgile@ihstowers.com","1871","26-07-2024 23:04:50"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0002700849","M=
adagascar-Yde-New","","26-07-2024 21:37:25","26-07-2024 20:39:10","27-07-20=
24 11:12:25","Active: No power issue, site is on Grid with Ubaie=3D53.2V, C=
hristian (691927185) from ZTE work on site","","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power=
 issue, site is on Grid with Ubaie=3D53.2V, Christian (691927185) from ZTE =
work on site","landry.etame@ihstowers.com","3497","26-07-2024 21:37:25","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0002700823","J=
-Vespa","","26-07-2024 21:30:39","26-07-2024 20:14:33","26-07-2024 20:20:34=
","Active: No power issue, site is on grid with Ubaie=3D54.5V, Brice Tsague=
 (650 21 40 96) from Huawei is informed.","Mboua Thierry","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: No power issue, site is on grid with Ubaie=3D54.5V, Brice Tsague (650 21=
 40 96) from Huawei is informed.","landry.etame@ihstowers.com","4568","26-0=
7-2024 21:30:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002700611","M=
vog-Manga","","26-07-2024 20:57:16","26-07-2024 19:26:10","26-07-2024 19:30=
:25","Active: no power issue, site is on grid with Ubaie=3D53V, Lionel adje=
d (655184876) from Huawei is informed (swapping by ZTE )","Albran Byorel","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active: no power issue, site is on grid with Ubaie=3D53V, Lionel=
 adjed (655184876) from Huawei is informed (swapping by ZTE )","landry.etam=
e@ihstowers.com","5468","26-07-2024 20:57:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002699998","M=
asque","","26-07-2024 19:24:16","26-07-2024 19:07:02","26-07-2024 19:17:04"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue
","landry.etame@ihstowers.com","1035","26-07-2024 19:24:16","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0002699983","MEHANDAN=
","","26-07-2024 19:23:10","26-07-2024 18:11:40","26-07-2024 22:00:42","Cas=
caded Incident from TTO2510948","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Site went down because the CB(80A) bur=
n of PWC// He replaced the Cb(80A) by Cb(63A)  (swapping by ZTE )","system"=
,"4290","26-07-2024 19:23:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002699850","O=
dza II OCM","IHS_YND_528","26-07-2024 19:08:45","26-07-2024 18:11:40","26-0=
7-2024 22:00:42","Site went down because the CB(80A) burn of PWC// He repla=
ced the Cb(80A) by Cb(63A)  (swapping by ZTE )","Albran Byorel","Equipment =
Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","=
Site went down because the CB(80A) burn of PWC// He replaced the Cb(80A) by=
 Cb(63A)  (swapping by ZTE )","landry.etame@ihstowers.com","3426","26-07-20=
24 19:08:45","Sagemcom CMR"
"Closed Complete","Site Down","T1546","IHS_YND_164","NOCINC0002699838","OBA=
M NGOLA OCM","","26-07-2024 19:04:24","26-07-2024 18:36:05","26-07-2024 20:=
04:46","site went down due to lack of 02 phase on site // Gen manually star=
ted (swapping by ZTE )","MINKA NICOLAS","Grid Supply","Passive","Grid","Nat=
ional Grid - Phase Controller Faulty","site went down due to lack of 02 pha=
se on site // Gen manually started (swapping by ZTE )","denis.mballa@ihstow=
ers.com","1700","26-07-2024 19:04:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0002698958","B=
astos Ekoudou","","26-07-2024 16:41:27","26-07-2024 16:36:46","26-07-2024 1=
6:40:03","Grid outage, site wen down because gen failed to start due to poo=
r battery backup // Gen start automatically","Mboua Thierry","Equipment Rep=
air","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, =
site wen down because gen failed to start due to poor battery backup // Gen=
 start automatically","landry.etame@ihstowers.com","281","26-07-2024 16:41:=
27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0002698940","S=
cience","","26-07-2024 16:36:47","26-07-2024 16:31:42","26-07-2024 18:30:03=
","Active: No power issue, site is on gen, Ebangue(699865526) from ZTE work=
 on site.","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issue, s=
ite is on gen, Ebangue(699865526) from ZTE work on site.","landry.etame@ihs=
towers.com","312","26-07-2024 16:36:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002698937","M=
essassi 2","","26-07-2024 16:34:40","26-07-2024 16:28:27","26-07-2024 17:12=
:02"," site on gen due to grid outage, grid return, site went down due to g=
rid contactor did not excited// He excited grid contactor and site on grid =
","Fabrice Pouakam","Equipment Repair","Passive","Control Panel","ATS-AMF I=
ssue"," site on gen due to grid outage, grid return, site went down due to =
grid contactor did not excited// He excited grid contactor and site on grid=
 ","landry.etame@ihstowers.com","427","26-07-2024 16:34:40","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002698815","Lad=
a I Yde","","26-07-2024 16:09:25","26-07-2024 16:06:13","26-07-2024 18:42:2=
9","Site on DG due to grid outage,DG stopped due to Alarm low oil fuel (Ala=
rm not proven)//He cleaned oil sensor ,and manually start of DG.","Mba Laza=
re Herve","Equipment Repair","Passive","Control Panel","Panel Distribution =
Board","Site on DG due to grid outage,DG stopped due to Alarm low oil fuel =
(Alarm not proven)//He cleaned oil sensor ,and manually start of DG.","deni=
s.mballa@ihstowers.com","193","26-07-2024 16:09:25","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002698809","Nko=
l-Mbanda","","26-07-2024 16:07:22","26-07-2024 16:03:04","26-07-2024 22:10:=
50","Active: No power issue, site is on grid with Ubaie=3D53V, Hosiah (6996=
99694) from Huawei is informed.","MINKA NICOLAS","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No pow=
er issue, site is on grid with Ubaie=3D53V, Hosiah (699699694) from Huawei =
is informed.","denis.mballa@ihstowers.com","260","26-07-2024 16:07:22","Sag=
emcom CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0002698775","Nsa=
m escale LP","","26-07-2024 15:52:51","26-07-2024 13:01:36","26-07-2024 17:=
39:36","Active: No power issue on site U=3D52,5V on grid, Marcel YAMBON/696=
300068/ From clean IT is working on site","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power i=
ssue on site U=3D52,5V on grid, Marcel YAMBON/696300068/ From clean IT is w=
orking on site
","denis.mballa@ihstowers.com","17736","26-07-2024 15:52:51","Sagemcom CMR"
"Closed Complete","Site Down","T1682","IHS_YND_532","NOCINC0002698501","NKO=
LOSSAN OKOK","","26-07-2024 15:17:28","26-07-2024 15:11:18","26-07-2024 20:=
02:12","Tx issue : Site on Grid,Ubaie:54.2V; Martial690-08-70-47 is informe=
d .","Parker Tchoup","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","Tx issue : Site on Grid,Ubaie:54.2V; Marti=
al690-08-70-47 is informed .","denis.mballa@ihstowers.com","371","26-07-202=
4 15:17:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0002698494","N=
komkana 2","","26-07-2024 15:16:11","26-07-2024 15:04:05","26-07-2024 15:20=
:54","Active: No power issue, site is on grid with Ubaie=3D53V, Straumann(6=
74608437) from ZTE work on site,","Mboua Thierry","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No po=
wer issue, site is on grid with Ubaie=3D53V, Straumann(674608437) from ZTE =
work on site,","landry.etame@ihstowers.com","728","26-07-2024 15:16:11","Sa=
gemcom CMR"
"Closed Complete","Site Down","T2141","IHS_YND_531","NOCINC0002698406","OTE=
LE MTN","","26-07-2024 14:48:52","26-07-2024 14:48:42","26-07-2024 15:00:21=
","Tx Issue : site on  DG ,Ubaie:55.9V; Etienne Huawei/695-03-39-81 was wor=
king on site.","Fanda Brice","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Tx Issue : site on  DG ,Ubaie:55.9=
V; Etienne Huawei/695-03-39-81 was working on site.","denis.mballa@ihstower=
s.com","12","26-07-2024 14:48:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002698059","MBIMBIM"=
,"","26-07-2024 13:40:00","26-07-2024 13:36:29","26-07-2024 15:45:00","Casc=
aded Incident from TTO2509219","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid gen site, DG took high temp alar=
m // FME added water and started manually the DG
","system","211","26-07-2024 13:40:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002698058","Ngouetou=
","","26-07-2024 13:40:00","26-07-2024 13:36:29","26-07-2024 15:45:00","Cas=
caded Incident from TTO2509219","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Hybrid gen site, DG took high temp ala=
rm // FME added water and started manually the DG
","system","211","26-07-2024 13:40:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002698056","Ngoum","=
","26-07-2024 13:40:00","26-07-2024 13:36:29","26-07-2024 15:45:00","Cascad=
ed Incident from TTO2509219","Parker Tchoup","Cascade Outage","Passive","Ca=
scade Passive","Cascade Passive","Hybrid gen site, DG took high temp alarm =
// FME added water and started manually the DG
","system","211","26-07-2024 13:40:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002698057","Matsari"=
,"","26-07-2024 13:40:00","26-07-2024 13:36:29","26-07-2024 15:45:00","Casc=
aded Incident from TTO2509219","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Hybrid gen site, DG took high temp alar=
m // FME added water and started manually the DG
","system","211","26-07-2024 13:40:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0002697993","C=
NDH","","26-07-2024 13:20:23","26-07-2024 12:39:16","26-07-2024 13:35:26","=
No power issue on site U=3D54,6v site on grid Team  ZTE Tzonteu olivier 677=
269888 working on site","Paul BIBOUM","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,6v site on grid Team  ZTE Tzonteu olivier 677269888 working on site",=
"emmanuel.ghani@ihstowers.com","2468","26-07-2024 13:20:23","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002697954","Nko=
l-Mbanda","","26-07-2024 13:10:11","26-07-2024 13:01:07","26-07-2024 13:45:=
04","site up","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Control Panel","site was o, gen due to grid outage, gen stopped with ove=
rcurrent alarm//reseted gen card(investigations ongoing)","joelle.ekessi@ih=
stowers.com","545","26-07-2024 13:10:11","Sagemcom CMR"
"Closed Complete","Warning","CTR_080","IHS_YND_298","NOCINC0002697479","Ole=
mbe","","26-07-2024 11:48:02","","","Site on Low Battery Volltage due to gr=
id outage //DG started.","Fabrice Pouakam","Warning","Warning","POWER","War=
ning - National Grid - Grid Outage Issue","Site on Low Battery Volltage due=
 to grid outage //DG started.","marie.kwin@ihstowers.com","6","26-07-2024 1=
1:48:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0002697466","M=
adagascar-Yde-New","","26-07-2024 11:45:56","26-07-2024 11:40:52","26-07-20=
24 12:22:23","No power issue on site U=3D53,2v site on grid Team Christian/=
691927185/ZTE working on site","","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53=
,2v site on grid Team Christian/691927185/ZTE working on site","emmanuel.gh=
ani@ihstowers.com","305","26-07-2024 11:45:56","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002697371","Ess=
os Marche","","26-07-2024 11:37:57","26-07-2024 11:28:49","26-07-2024 13:35=
:31","No power issue Site on Grid U=3D54V tx fme armand /699949553 from hua=
wei is working on site","Delor Telezing","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue Site on=
 Grid U=3D54V tx fme armand /699949553 from huawei is working on site","joe=
lle.ekessi@ihstowers.com","549","26-07-2024 11:37:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_540","IHS_YND_077","NOCINC0002697340","O=
bili Carrefour","","26-07-2024 11:27:59","26-07-2024 11:20:50","26-07-2024 =
12:07:44","No power issue on site U=3D54,5v site on grid Team silvester/671=
046093/ZTE working on site","Paul BIBOUM","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on sit=
e U=3D54,5v site on grid Team silvester/671046093/ZTE working on site","emm=
anuel.ghani@ihstowers.com","430","26-07-2024 11:27:59","Sagemcom CMR"
"Closed Complete","Site Down","T1594","IHS_YND_298","NOCINC0002697189","Ole=
mbe","","26-07-2024 11:15:07","26-07-2024 11:26:01","26-07-2024 12:02:39","=
Site went down due to work (Fabrice / Sagemcom/657072631/ working on site )=
// end of work,","Fabrice Pouakam","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Site went down due to work (Fabrice / S=
agemcom/657072631/ working on site )// end of work,","joelle.ekessi@ihstowe=
rs.com","5027","26-07-2024 11:15:07","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0002697183","Bon=
djock","","26-07-2024 11:13:47","26-07-2024 11:10:43","26-07-2024 13:16:39"=
,"","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","grid ou=
tage, gen ran till diesel outage//refueling done","joelle.ekessi@ihstowers.=
com","185","26-07-2024 11:13:47","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0002696889","Bas=
tos Bethesda","","26-07-2024 10:29:20","26-07-2024 10:23:16","26-07-2024 10=
:29:08","Grid outage site went down before Gen started due to poor battery =
back up // Grid return","Mboua Thierry","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage site went down before =
Gen started due to poor battery back up // Grid return","joelle.ekessi@ihst=
owers.com","364","26-07-2024 10:29:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0002696883","M=
ontee-Jouvence","","26-07-2024 10:26:57","26-07-2024 09:37:22","26-07-2024 =
10:28:35","Site went down because the CB of rectifer dysjuncted due to one =
rectifier faulty// He bypass the faulty rectifier and reamed the CB(site sw=
apped by ZTE)","Hyemafo Gildas","Equipment Repair","Passive","Rectifier","R=
ectifier - Circuit Breaker","Site went down because the CB of rectifer dysj=
uncted due to one rectifier faulty// He bypass the faulty rectifier and rea=
med the CB(site swapped by ZTE)","kombi.samuel@ihstowers.com","2976","26-07=
-2024 10:26:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002696882","O=
lembe-Terminus","","26-07-2024 10:26:31","26-07-2024 10:18:27","26-07-2024 =
10:30:38","No power issue on site ubaie=3D54v site on grid   symphorien is =
informed","Fabrice Pouakam","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site ubaie=3D54v =
site on grid   symphorien is informed","emmanuel.ghani@ihstowers.com","486"=
,"26-07-2024 10:26:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0002696838","N=
komkana 2","","26-07-2024 10:22:02","26-07-2024 10:16:55","26-07-2024 10:59=
:03","No power issue on site U=3D52,5v site on grid Team Straumann/ 6746084=
37/ZTE working on site","Mboua Thierry","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D52,5v site on grid Team Straumann/ 674608437/ZTE working on site","emma=
nuel.ghani@ihstowers.com","307","26-07-2024 10:22:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_050","IHS_YND_080","NOCINC0002696713","M=
ini-Ferme","","26-07-2024 10:04:54","25-07-2024 16:49:23","26-07-2024 11:54=
:20","No power issue on site U=3D54v site on grid Team  Yvan/679375329/ZTE =
working on site","","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue on site U=3D54v site on grid=
 Team  Yvan/679375329/ZTE working on site","marie.kwin@ihstowers.com","6213=
2","26-07-2024 10:04:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_525","IHS_YND_544","NOCINC0002696707","J=
ean Vespa 2","","26-07-2024 10:01:44","26-07-2024 09:59:34","26-07-2024 11:=
08:34","No power issue on site U=3D54,5v site on grid Team Larry/696846671/=
ZTE working on site","Mboua Thierry","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,5v site on grid Team Larry/696846671/ZTE working on site","emmanuel.g=
hani@ihstowers.com","132","26-07-2024 10:01:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0002696655","M=
vog-Betsi","","26-07-2024 09:52:17","26-07-2024 09:47:12","26-07-2024 10:35=
:11","No power issue on site U=3D54v site on grid Team TSOGNE Rodolpho/ 6 5=
6 35 38 62/ZTE working on site","Hyemafo Gildas","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site U=3D54v site on grid Team TSOGNE Rodolpho/ 6 56 35 38 62/ZTE worki=
ng on site","emmanuel.ghani@ihstowers.com","306","26-07-2024 09:52:17","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0002696654","N=
ew-Marche-Melen","","26-07-2024 09:51:44","26-07-2024 09:36:34","26-07-2024=
 10:34:13","No power issue on site U=3D53,2v site on grid Team Aristide/655=
273355/ZTE working on site ","Paul BIBOUM","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on si=
te U=3D53,2v site on grid Team Aristide/655273355/ZTE working on site ","em=
manuel.ghani@ihstowers.com","912","26-07-2024 09:51:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0002696648","M=
essa-Carriere OCM","","26-07-2024 09:51:06","26-07-2024 09:35:01","26-07-20=
24 10:35:06","No power issue on site U=3D54v site on grid Team NSHOM/695378=
974/Zte working on site","","Cascade Outage","Active","Cascade Active","Cas=
cade Active","No power issue on site U=3D54v site on grid Team NSHOM/695378=
974/Zte working on site","emmanuel.ghani@ihstowers.com","967","26-07-2024 0=
9:51:06","Sagemcom CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0002696448","Mba=
nkomo CAF","","26-07-2024 09:29:24","26-07-2024 09:23:20","26-07-2024 10:28=
:16","grid outage,gen ran till fuel shortage//Refueling done","Fanda Brice"=
,"Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran till=
 fuel shortage//Refueling done","joelle.ekessi@ihstowers.com","365","26-07-=
2024 09:29:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0002696322","N=
komkana","","26-07-2024 09:15:56","26-07-2024 09:13:51","26-07-2024 10:49:3=
9","No power issue on site U=3D54,5v site on grid Team Edmon/655754488/ZTE =
working on site","","Customer Equipment Failure","Active","Active Equipment=
 Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,5v site on gr=
id Team Edmon/655754488/ZTE working on site","emmanuel.ghani@ihstowers.com"=
,"126","26-07-2024 09:15:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_122","IHS_YND_230","NOCINC0002696309","M=
eyong-Meyeme","IHS_YND_265","26-07-2024 09:12:42","26-07-2024 09:07:36","26=
-07-2024 10:20:55","No power issue on site U=3D52v site on grid Team Marc/6=
99183408/ZTE working on site ","TIENTCHEU NZETCHIEU GAEL","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No po=
wer issue on site U=3D52v site on grid Team Marc/699183408/ZTE working on s=
ite ","emmanuel.ghani@ihstowers.com","307","26-07-2024 09:12:42","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_519","IHS_YND_543","NOCINC0002696221","E=
ntree Cite Verte","","26-07-2024 08:51:02","26-07-2024 08:47:56","26-07-202=
4 09:00:49","ACTIVE No power issue U=3D53.8V site on Gen Tean  Adam Njoya f=
rom ZTE is working on site Swapp","Paul BIBOUM","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power=
 issue U=3D53.8V site on Gen Tean  Adam Njoya from ZTE is working on site S=
wapp","emmanuel.ghani@ihstowers.com","188","26-07-2024 08:51:02","Sagemcom =
CMR"
"Closed Complete","Site Down","T3172","IHS_YND_043","NOCINC0002696123","Emi=
a","","26-07-2024 08:42:05","26-07-2024 08:37:01","26-07-2024 08:43:45","Gr=
id outage no space to deployed a mobil Gen // Grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space=
 to deployed a mobil Gen // Grid return","joelle.ekessi@ihstowers.com","306=
","26-07-2024 08:42:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0002695907","M=
efou-Assi","","26-07-2024 08:02:04","26-07-2024 05:21:18","26-07-2024 11:22=
:33","Active//No power issue on site ,Site on Grid  with Ubaie=3D53,5 V The=
 RM TX Alain (691144423) from Huawei informed.(Site Swapped by ZTE","Fanda =
Brice","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No power issue on site ,Site on Grid  with Ubaie=
=3D53,5 V The RM TX Alain (691144423) from Huawei informed.(Site Swapped by=
 ZTE","kombi.samuel@ihstowers.com","9649","26-07-2024 08:02:04","Sagemcom C=
MR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0002695895","Nko=
lnda","","26-07-2024 07:57:47","26-07-2024 07:54:42","26-07-2024 08:23:45",=
"Grid outage site went down before Gen started due to poor battery back up =
// Gen started automatically","Albran Byorel","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage site went down b=
efore Gen started due to poor battery back up // Gen started automatically"=
,"joelle.ekessi@ihstowers.com","186","26-07-2024 07:57:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0002695876","M=
EFOU ASSI","","26-07-2024 07:51:01","26-07-2024 05:21:46","26-07-2024 06:00=
:57","No power issue on site ubaie=3D54v site on grid  ","Fanda Brice","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","No power issue on site ubaie=3D54v site on grid  ","kombi.samuel@ih=
stowers.com","8957","26-07-2024 07:51:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002695469","M=
asque","","26-07-2024 05:42:06","26-07-2024 05:28:55","26-07-2024 05:56:19"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","dor=
othy.djantio@ihstowers.com","792","26-07-2024 05:42:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002694663","NKOLMEKO=
NG YDE","","26-07-2024 01:52:23","26-07-2024 00:16:46","26-07-2024 00:20:51=
","Cascaded Incident from TTO2506206","Fabrice Pouakam","Cascade Outage","A=
ctive","Cascade Active","Cascade Active","Active :no power issue on site Ub=
aie: 54.3V;  site on Grid. The TX FME Synphorien(675295205) from Huawei is =
informed.","system","5737","26-07-2024 01:52:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_248","IHS_YND_304","NOCINC0002694610","N=
kolondom","","26-07-2024 01:42:16","26-07-2024 00:16:46","26-07-2024 00:20:=
51","","Fabrice Pouakam","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Active :no power issue on site Ubaie: 54.3V;  site on Grid. The =
TX FME Synphorien(675295205) from Huawei is informed.","dorothy.djantio@ihs=
towers.com","6014","26-07-2024 01:42:16","Sagemcom CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002694371","O=
lembe","IHS_YND_681, IHS_YND_304","26-07-2024 00:24:05","26-07-2024 00:16:4=
6","26-07-2024 02:20:51","Active :no power issue on site Ubaie: 54.3V;  sit=
e on Grid. The TX FME Synphorien(675295205) from Huawei is informed.","Fabr=
ice Pouakam","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","Active :no power issue on site Ubaie: 54.3V;  site=
 on Grid. The TX FME Synphorien(675295205) from Huawei is informed.","dorot=
hy.djantio@ihstowers.com","440","26-07-2024 00:24:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002693845","M=
asque","","25-07-2024 22:37:11","25-07-2024 22:28:29","26-07-2024 00:30:14"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","dor=
othy.djantio@ihstowers.com","523","25-07-2024 22:37:11","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0002693740","EBO=
M","","25-07-2024 22:19:39","25-07-2024 22:07:29","25-07-2024 22:39:26","Gr=
id fluctuation site went down because Gen failed to start due to Grid bad v=
oltage//Grid stabilized(Site Swapped by ZTE)","Hyemafo Gildas","Grid Supply=
","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluctuat=
ion site went down because Gen failed to start due to Grid bad voltage//Gri=
d stabilized(Site Swapped by ZTE)","alexandre.kamal@ihstowers.com","731","2=
5-07-2024 22:19:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002693515","M=
vog-Manga","","25-07-2024 21:43:46","25-07-2024 21:21:40","26-07-2024 00:24=
:04","No power issue, site is on grid with Ubaie=3D53V,, Lionel adjed(65518=
4876) from Huawei is informed, Notice that Disjunction in BTS Ocm. (Site al=
ready swapped by ZTE)","Albran Byorel","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue, site is =
on grid with Ubaie=3D53V,, Lionel adjed(655184876) from Huawei is informed,=
 Notice that Disjunction in BTS Ocm. (Site already swapped by ZTE)","kamga.=
virgile@ihstowers.com","1328","25-07-2024 21:43:46","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0002693199","Nsi=
meyong Terre Rouge","","25-07-2024 20:38:23","25-07-2024 20:29:17","25-07-2=
024 20:44:52","site went down because gen failed to start due to alarm over=
frequency//he reduice the frequency and started the gen","MINKA NICOLAS","E=
quipment Repair","Passive","ACDG Gen","ACDG - Control Panel","site went dow=
n because gen failed to start due to alarm overfrequency//he reduice the fr=
equency and started the gen","alexandre.kamal@ihstowers.com","546","25-07-2=
024 20:38:23","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002693077","Bas=
tos Amb Coree","","25-07-2024 19:53:32","25-07-2024 19:44:27","25-07-2024 1=
9:56:26","Grid outage.no space to deploy mobile gen.grid power awaited//Gri=
d power returned.","","Grid Supply","Passive","Grid","National Grid - Grid =
Outage Issue","Grid outage.no space to deploy mobile gen.grid power awaited=
//Grid power returned.","alexandre.kamal@ihstowers.com","546","25-07-2024 1=
9:53:32","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002692711","Ess=
os Marche","","25-07-2024 18:42:21","25-07-2024 18:19:13","25-07-2024 18:20=
:09","No power issue site on grid with U=3D54v Armand Ngetsa(699949553) fro=
m Huawei is informed","Delor Telezing","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on g=
rid with U=3D54v Armand Ngetsa(699949553) from Huawei is informed","alexand=
re.kamal@ihstowers.com","1389","25-07-2024 18:42:21","Sagemcom CMR"
"Closed Complete","Site Down","T3102","IHS_YND_706","NOCINC0002692525","Mba=
nkomo CAF","","25-07-2024 17:53:17","25-07-2024 17:45:14","25-07-2024 18:53=
:21","Grid outage. Site went down because gen ran until fuel shortage// Gri=
d return (Refueling ongoing) ","Fanda Brice","Fuel Outage","Passive","Diese=
l","Diesel Outage","Grid outage. Site went down because gen ran until fuel =
shortage// Grid return (Refueling ongoing) ","alexandre.kamal@ihstowers.com=
","484","25-07-2024 17:53:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0002692244","M=
ontee-Jouvence","","25-07-2024 16:54:20","25-07-2024 16:39:05","25-07-2024 =
17:20:42","site went down due to disjunction CB(63A) in PWC// He reamed Cb,=
 site on grid (Site Swapped by ZTE)","Hyemafo Gildas","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went =
down due to disjunction CB(63A) in PWC// He reamed Cb, site on grid (Site S=
wapped by ZTE)","kamga.virgile@ihstowers.com","917","25-07-2024 16:54:20","=
Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002691752","Tsi=
nga","","25-07-2024 15:22:43","25-07-2024 15:13:37","25-07-2024 15:35:05","=
site went down due to disfunctionning of controller// voltage stabilized ( =
controller to be replaced)","Mboua Thierry","Equipment Repair","Passive","H=
ybrid","Hybrid Module","site went down due to disfunctionning of controller=
// voltage stabilized ( controller to be replaced)","alexandre.kamal@ihstow=
ers.com","547","25-07-2024 15:22:43","Sagemcom CMR"
"Closed Complete","Site Down","T1059","IHS_YND_434","NOCINC0002691672","Don=
ga","","25-07-2024 14:56:32","25-07-2024 14:43:28","25-07-2024 16:41:17"," =
Hybride, gensite went down because Gen started and stopped due to ""high te=
mp"" alarm //He added water and Gen manually started","Parker Tchoup","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Radiator"," Hybride, gensite wen=
t down because Gen started and stopped due to ""high temp"" alarm //He adde=
d water and Gen manually started","alexandre.kamal@ihstowers.com","880","25=
-07-2024 14:56:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0002691647","H=
-Prince","","25-07-2024 14:47:26","25-07-2024 14:21:16","25-07-2024 15:00:1=
6","Site went down due to work(Thierry MBOUA (657108452) from sagemcom/inst=
allation of new circuit breaker which powered OCM equipements//End of works=
","Mboua Thierry","Installation Activity","Passive","Planned Activity","Ins=
tallation Activity","Site went down due to work(Thierry MBOUA (657108452) f=
rom sagemcom/installation of new circuit breaker which powered OCM equipeme=
nts//End of works","kamga.virgile@ihstowers.com","1572","25-07-2024 14:47:2=
6","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0002691327","Ona=
ngondi (melen bikop)","","25-07-2024 13:54:41","25-07-2024 13:46:29","25-07=
-2024 14:08:29","grid outage,site went down because Gen started and stopped=
 due to ""high temp"" alarm causing by radiador percing // He added water, =
site on gen (radiator to be replaced)","Fanda Brice","Equipment Repair","Pa=
ssive","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","grid out=
age,site went down because Gen started and stopped due to ""high temp"" ala=
rm causing by radiador percing // He added water, site on gen (radiator to =
be replaced)","denis.mballa@ihstowers.com","493","25-07-2024 13:54:41","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_195","IHS_YND_165","NOCINC0002691266","A=
hala","","25-07-2024 13:36:37","25-07-2024 12:37:31","25-07-2024 13:00:57",=
"site already swapped by zte","MINKA NICOLAS","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue on=
 ubaie=3D54v CB tripped in BTS, Lionel tchatchou is unreachable but Rm Alai=
n is informed","landry.etame@ihstowers.com","3548","25-07-2024 13:36:37","S=
agemcom CMR"
"Closed Complete","Site Down","T0197","IHS_YND_263","NOCINC0002691119","Men=
dong Plateau","IHS_YND_742, IHS_YND_237, IHS_YND_151","25-07-2024 13:19:42"=
,"25-07-2024 13:06:13","25-07-2024 13:08:13","Grid outage,site went down  b=
efore DG start : Poor Batteries backup //DG started automatically.","Hyemaf=
o Gildas","Equipment Repair","Passive","Control Panel","Power Cabinet - Bat=
tery Low","Grid outage,site went down  before DG start : Poor Batteries bac=
kup //DG started automatically.","denis.mballa@ihstowers.com","810","25-07-=
2024 13:19:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_151","NOCINC0002691108","Tamtam W=
eekend","","25-07-2024 13:16:20","25-07-2024 13:06:13","25-07-2024 13:08:13=
","Cascaded Incident from TTO2503001 - Cascade Removed From TTO2503001","Hy=
emafo Gildas","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","Grid outage,site went down  before DG start : Poor Batteries backup //DG=
 started automatically.","system","1217","25-07-2024 13:16:20","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_742","NOCINC0002691107","Mendong =
NB","","25-07-2024 13:16:20","25-07-2024 13:06:13","25-07-2024 13:08:13","C=
ascaded Incident from TTO2503001 - Cascade Removed From TTO2503001","","Cas=
cade Outage","Passive","Cascade Passive","Cascade Passive","Grid outage,sit=
e went down  before DG start : Poor Batteries backup //DG started automatic=
ally.","system","1297","25-07-2024 13:16:20","Sagemcom CMR"
"Closed Complete","Site Down","T1545","IHS_YND_237","NOCINC0002691098","Car=
refour Simbock","","25-07-2024 13:14:47","25-07-2024 13:06:13","25-07-2024 =
13:08:13","","Hyemafo Gildas","Cascade Outage","Passive","Cascade Passive",=
"Cascade Passive","Grid outage,site went down  before DG start : Poor Batte=
ries backup //DG started automatically.","denis.mballa@ihstowers.com","1107=
","25-07-2024 13:14:47","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0002691082","EBO=
M","","25-07-2024 13:09:37","25-07-2024 13:06:58","25-07-2024 13:54:58","Gr=
id outage site went down because gen failed to start due to Gen Battery Dis=
charge  //He started Gen  with external battery.","Hyemafo Gildas","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage sit=
e went down because gen failed to start due to Gen Battery Discharge  //He =
started Gen  with external battery.","denis.mballa@ihstowers.com","161","25=
-07-2024 13:09:37","Sagemcom CMR"
"Closed Complete","Site Down","LIT_349","IHS_EDA_051","NOCINC0002690732","N=
yanon","","25-07-2024 12:29:45","25-07-2024 12:22:20","25-07-2024 15:54:20"=
,"Hybrid Gen Site: Site went down because hybrid system malfunctionning // =
Gen manually started","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passiv=
e","Hybrid","Hybrid Module","Hybrid Gen Site: Site went down because hybrid=
 system malfunctionning // Gen manually started","landry.etame@ihstowers.co=
m","448","25-07-2024 12:29:45","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002690617","Bas=
tos Amb Coree","","25-07-2024 12:24:35","25-07-2024 12:15:22","25-07-2024 1=
2:20:22","	Grid outage No space to deployed a mobile gen // Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid =
outage No space to deployed a mobile gen // Grid return","denis.mballa@ihst=
owers.com","554","25-07-2024 12:24:35","Sagemcom CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0002690614","Nsa=
m escale LP","","25-07-2024 12:23:12","25-07-2024 12:16:01","25-07-2024 12:=
20:56","Active: No power issue on site U=3D52,5V on grid, Marcel YAMBON/696=
300068/ From clean IT is working on site","","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power i=
ssue on site U=3D52,5V on grid, Marcel YAMBON/696300068/ From clean IT is w=
orking on site","denis.mballa@ihstowers.com","431","25-07-2024 12:23:12","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0002690596","B=
astos Bethesda","","25-07-2024 12:15:35","25-07-2024 12:11:30","25-07-2024 =
12:22:30","Grid outage, site went down before gen start due to poor battery=
 backup // Gen start automatically","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // Gen start automaticall=
y","landry.etame@ihstowers.com","246","25-07-2024 12:15:35","Sagemcom CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0002690574","Biy=
emassi LAC","","25-07-2024 12:06:51","25-07-2024 11:59:39","25-07-2024 13:1=
0:39","Grid outage No space to deployed a mobile gen // Grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e No space to deployed a mobile gen // Grid return","denis.mballa@ihstowers=
.com","3198","25-07-2024 12:06:51","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0002689986","Acc=
acia New","","25-07-2024 11:41:14","25-07-2024 11:29:55","25-07-2024 13:16:=
55","GRID OUTAGE//GRID RETURN","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","GRID OUTAGE//GRID RETURN","denis.mballa@ihstower=
s.com","3022","25-07-2024 11:41:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0002689754","M=
ontee-Jouvence","","25-07-2024 11:14:41","25-07-2024 11:03:37","25-07-2024 =
11:20:37","grid outage,gen failed to start due to CB 40A disjuncted//he rea=
med the CB(site swapped by ZTE)","Hyemafo Gildas","Equipment Repair","Passi=
ve","Control Panel","Faulty Circuit Breaker","grid outage,gen failed to sta=
rt due to CB 40A disjuncted//he reamed the CB(site swapped by ZTE)","landry=
.etame@ihstowers.com","666","25-07-2024 11:14:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002689351","M=
asque","","25-07-2024 10:09:41","25-07-2024 10:00:36","25-07-2024 10:20:36"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","lan=
dry.etame@ihstowers.com","547","25-07-2024 10:09:41","Sagemcom CMR"
"Closed Complete","Site Down","T1232","IHS_YND_792","NOCINC0002689142","NKO=
ABANG NKOLO 3","","25-07-2024 09:45:31","25-07-2024 06:52:16","25-07-2024 0=
8:12:57","grid outage,gen stopped with alarm low oil pressure// he added oi=
l and started the gen ","Mba Lazare Herve","Equipment Repair","Passive","AC=
DG Gen","ACDG - Low Oil Pressure","grid outage,gen stopped with alarm low o=
il pressure// he added oil and started the gen ","denis.mballa@ihstowers.co=
m","10456","25-07-2024 09:45:31","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002689049","Nko=
l-Mbanda","","25-07-2024 09:28:10","25-07-2024 09:19:00","25-07-2024 11:00:=
51","site went down due to work(Patrick ESSA(650128223) from IHS // End of =
work","MINKA NICOLAS","Installation Activity","Passive","Planned Activity",=
"Installation Activity","site went down due to work(Patrick ESSA(650128223)=
 from IHS // End of work","denis.mballa@ihstowers.com","551","25-07-2024 09=
:28:10","Sagemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0002688679","Nlo=
ng Mvolye New","","25-07-2024 07:59:54","25-07-2024 07:56:44","25-07-2024 0=
8:16:44","No power issue on site U=3D53,1v site on grid Hosiah of huawei is=
 informed","Paul BIBOUM","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53,1v site =
on grid Hosiah of huawei is informed","denis.mballa@ihstowers.com","191","2=
5-07-2024 07:59:54","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0002687802","Ona=
ngondi (melen bikop)","","25-07-2024 04:59:44","25-07-2024 04:56:38","25-07=
-2024 05:40:08","Grid outage,gen failed to start due to high temp alarm cau=
sing by radiator pierced//we add water and gen manually started ","Fanda Br=
ice","Equipment Repair","Passive","ACDG Gen","ACDG - Radiator","Grid outage=
,gen failed to start due to high temp alarm causing by radiator pierced//we=
 add water and gen manually started ","ludivine.ngamaleu@ihstowers.com","18=
7","25-07-2024 04:59:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0002687381","B=
astos Ekoudou","","25-07-2024 03:33:45","25-07-2024 03:31:36","25-07-2024 0=
3:35:01","ACTIVE// No power issue site on Grid U=3D 54,3 V The TX Eloudou//=
693212405 is informed repetitive issue//site up at 03:35 AM","Mboua Thierry=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","ACTIVE// No power issue site on Grid U=3D 54,3 V The TX Eloud=
ou//693212405 is informed repetitive issue//site up at 03:35 AM","ange.kong=
o@ihstowers.com","132","25-07-2024 03:33:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002687372","M=
vog-Manga","","25-07-2024 03:31:40","25-07-2024 00:14:59","25-07-2024 01:14=
:59","No power issue, site is on grid with Ubaie=3D53V, Franck ERIC(6964229=
66) from ZTE work on site, Notice that Disjunction in BTS Ocm","Albran Byor=
el","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue, site is on grid with Ubaie=3D53V, Franck ER=
IC(696422966) from ZTE work on site, Notice that Disjunction in BTS Ocm","a=
nge.kongo@ihstowers.com","11804","25-07-2024 03:31:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_002","IHS_YND_010","NOCINC0002687193","C=
NR","","25-07-2024 02:45:33","25-07-2024 01:54:25","25-07-2024 08:19:35","A=
ccess issue duriing the night; grid outage, site went down because gen card=
 faulty and grid contactor did not excited// He excited grid contactor and =
site on grid","Mboua Thierry","Access Denial","Lease Or Legal","Landlord Re=
lated Issues","Access Issue - Land Lord","Access issue duriing the night; g=
rid outage, site went down because gen card faulty and grid contactor did n=
ot excited// He excited grid contactor and site on grid","ange.kongo@ihstow=
ers.com","3070","25-07-2024 02:45:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_123","IHS_YND_513","NOCINC0002686984","M=
aison-Blanche-IHS","","25-07-2024 02:29:19","25-07-2024 02:22:05","25-07-20=
24 03:31:54","Grid outage.no sape to deploy mobile gen//grid return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e.no sape to deploy mobile gen//grid return","ange.kongo@ihstowers.com","43=
4","25-07-2024 02:29:19","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0002686782","EBO=
M","","25-07-2024 01:51:24","25-07-2024 01:45:58","25-07-2024 05:03:44","Gr=
id outage,gen failed to start due to battery GE faulty//Gen manually starte=
d with external battery ","Hyemafo Gildas","Equipment Repair","Passive","AC=
DG Gen","ACDG - Generator Battery","Grid outage,gen failed to start due to =
battery GE faulty//Gen manually started with external battery ","ludivine.n=
gamaleu@ihstowers.com","3500","25-07-2024 01:51:24","Sagemcom CMR"
"Closed Complete","Site Down","T2182","IHS_YND_078","NOCINC0002686542","An-=
Marche-Melen","","25-07-2024 01:15:57","25-07-2024 01:05:54","25-07-2024 01=
:48:49","Grid outage. No space to deploy the MDG //Grid return","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage. No=
 space to deploy the MDG //Grid return","ludivine.ngamaleu@ihstowers.com","=
1154","25-07-2024 01:15:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0002686378","S=
hell-Nsimeyong","","25-07-2024 00:35:38","24-07-2024 20:05:03","24-07-2024 =
20:10:28","Active: No power issue, site is on grid with Ubaie=3D54V, MAGOTS=
AP Melissa (677085072) from ZTE working on site (site swapped by ZTE)","MIN=
KA NICOLAS","Customer Equipment Failure","Active","Active Equipment Failure=
","BTS/TX Fault Alarm","Active: No power issue, site is on grid with Ubaie=
=3D54V, MAGOTSAP Melissa (677085072) from ZTE working on site (site swapped=
 by ZTE)","ange.kongo@ihstowers.com","20261","25-07-2024 00:35:38","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0002686370","P=
olytechnique","","25-07-2024 00:33:22","24-07-2024 20:18:37","25-07-2024 02=
:39:32","No power issue site on grid with U=3D54,3v //site up at 11:26 PM M=
bah Osiah from Huawie informed us that Team ZTE was working on site at morn=
ing","","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue site on grid with U=3D54,3v //site up at=
 11:26 PM Mbah Osiah from Huawie informed us that Team ZTE was working on s=
ite at morning","ange.kongo@ihstowers.com","15287","25-07-2024 00:33:22","S=
agemcom CMR"
"Closed Complete","Site Down","T1329","IHS_YND_229","NOCINC0002686334","CRH=
-Etoug-Ebe","","25-07-2024 00:23:58","25-07-2024 00:15:53","25-07-2024 00:2=
7:56","Grid outage,gen failled to start due to high temp alarm//we add wate=
r and gen manually started ","Hyemafo Gildas","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Radiator","Grid outage,gen failled to start due to high =
temp alarm//we add water and gen manually started ","ludivine.ngamaleu@ihst=
owers.com","487","25-07-2024 00:23:58","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002686094","Bas=
tos Amb Coree","","24-07-2024 23:42:19","24-07-2024 23:36:09","25-07-2024 1=
0:15:09","Grid Outage. No space to deploy the MDG // Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage. =
No space to deploy the MDG // Grid return","ludivine.ngamaleu@ihstowers.com=
","371","24-07-2024 23:42:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0002686066","N=
omayos","","24-07-2024 23:37:02","24-07-2024 22:19:19","24-07-2024 22:49:46=
","site went down due to insufficient of rectifier on site //We add one rec=
tifier .site on grid ","Fanda Brice","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","site went down due to insufficient of rectifier on s=
ite //We add one rectifier .site on grid ","ange.kongo@ihstowers.com","4665=
","24-07-2024 23:37:02","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0002686006","Nko=
mkana","","24-07-2024 23:26:26","24-07-2024 23:16:03","25-07-2024 01:45:52"=
,"Grid Outage. No space to deploy the MDG // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage. No space=
 to deploy the MDG // Grid return","ludivine.ngamaleu@ihstowers.com","672",=
"24-07-2024 23:26:26","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0002685975","Men=
dong NB","","24-07-2024 23:20:10","24-07-2024 23:12:05","24-07-2024 23:20:5=
1","Grid outage.no space to deploy mobile gen//Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no spac=
e to deploy mobile gen//Grid return","ludivine.ngamaleu@ihstowers.com","486=
","24-07-2024 23:20:10","Sagemcom CMR"
"Closed Complete","Site Down","T0113","IHS_YND_155","NOCINC0002685941","Obo=
bogo","","24-07-2024 23:17:34","24-07-2024 23:08:30","25-07-2024 04:13:30",=
"No power issue site on grid with U=3D54,5v//qite up at 11:16 PM  Martial f=
rom Huawei is informed","MINKA NICOLAS","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on =
grid with U=3D54,5v//qite up at 11:16 PM  Martial from Huawei is informed",=
"ludivine.ngamaleu@ihstowers.com","545","24-07-2024 23:17:34","Sagemcom CMR=
"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002685896","Nsi=
meyong Shell","","24-07-2024 23:14:35","24-07-2024 23:08:30","24-07-2024 23=
:16:57","Grid outage site went down before Gen started due to poor battery =
backup//Gen started automatically","MINKA NICOLAS","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage site went d=
own before Gen started due to poor battery backup//Gen started automaticall=
y","ludivine.ngamaleu@ihstowers.com","365","24-07-2024 23:14:35","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_062","IHS_YND_310","NOCINC0002685144","N=
omayos","","24-07-2024 21:39:45","24-07-2024 20:56:15","24-07-2024 21:43:02=
","site went down due to insufficient of rectifier on site //Site Stabilize=
d","Fanda Brice","Equipment Repair","Passive","Control Panel","Power Cabine=
t - Circuit Breaker Issue","site went down due to insufficient of rectifier=
 on site //Site Stabilized","etienne.itondo@ihstowers.com","2830","24-07-20=
24 21:39:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_222","IHS_YND_314","NOCINC0002684848","S=
ous Prefecture","","24-07-2024 21:04:10","24-07-2024 20:55:00","24-07-2024 =
23:59:36","Active: No power issue, site is on grid with Ubaie=3D54V,  Lione=
l Tchatchou (694693436) from Huawei is informed","Fanda Brice","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active: No power issue, site is on grid with Ubaie=3D54V,  Lionel Tchatchou=
 (694693436) from Huawei is informed","etienne.itondo@ihstowers.com","551",=
"24-07-2024 21:04:10","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002684167","Nko=
l-Mbanda","","24-07-2024 19:33:39","24-07-2024 19:22:32","24-07-2024 19:40:=
40","site went down due to insufficient of rectifier on site //Site Stabili=
zed","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Mo=
dule","site went down due to insufficient of rectifier on site //Site Stabi=
lized","dorothy.djantio@ihstowers.com","668","24-07-2024 19:33:39","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0002683996","B=
astos Ekoudou","","24-07-2024 19:17:30","24-07-2024 19:16:46","24-07-2024 1=
9:30:54","ACTIVE// No power issue site on Grid U=3D 54,3 V The TX Eloudou//=
693212405 is informed repetitive issue","Mboua Thierry","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE/=
/ No power issue site on Grid U=3D 54,3 V The TX Eloudou//693212405 is info=
rmed repetitive issue","etienne.itondo@ihstowers.com","46","24-07-2024 19:1=
7:30","Sagemcom CMR"
"Closed Complete","Site Down","T1400","IHS_YND_254","NOCINC0002683227","Mvo=
g-Manga","","24-07-2024 18:44:49","24-07-2024 18:08:45","25-07-2024 00:14:5=
7"," site went down due to Cb disjuncted in DC BOX // he rearmed the CB(Swa=
pped by ZTE)","Albran Byorel","Equipment Repair","Passive","Control Panel",=
"Power Cabinet - Circuit Breaker Issue"," site went down due to Cb disjunct=
ed in DC BOX which powered OCM equipements// he rearmed the CB(Swapped by Z=
TE)","dorothy.djantio@ihstowers.com","6730","24-07-2024 18:44:49","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002683124","M=
asque","","24-07-2024 18:29:26","24-07-2024 18:09:19","24-07-2024 19:38:05"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","eti=
enne.itondo@ihstowers.com","1211","24-07-2024 18:29:26","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0002682589","UPA=
C LP","","24-07-2024 17:17:25","24-07-2024 17:12:16","24-07-2024 19:55:55",=
"No power issue on site U=3D55v site on grid Armand of huawei is informed",=
"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm","No power issue on site U=3D55v site on grid Armand of huawei=
 is informed","dorothy.djantio@ihstowers.com","311","24-07-2024 17:17:25","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_372","NOCINC0002682385","Bondjock=
","","24-07-2024 16:45:40","24-07-2024 16:29:17","24-07-2024 17:33:08","Cas=
caded Incident from TTO2495564","Fanda Brice","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Site went down due to hybrid system dysf=
unction // Gen start manually","system","983","24-07-2024 16:45:40","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_369","NOCINC0002682381","Mbeng","=
","24-07-2024 16:45:40","24-07-2024 16:29:17","24-07-2024 17:33:08","Cascad=
ed Incident from TTO2495564","Fanda Brice","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","Site went down due to hybrid system dysfunc=
tion // Gen start manually","system","983","24-07-2024 16:45:40","Sagemcom =
CMR"
"Closed Complete","Site Down","","IHS_YND_531","NOCINC0002682338","OTELE MT=
N","","24-07-2024 16:38:00","24-07-2024 16:34:17","24-07-2024 17:33:53","Ca=
scaded Incident from TTO2495563","Fanda Brice","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Site went down due to hybrid system dys=
function // Gen start manually","system","223","24-07-2024 16:38:00","Sagem=
com CMR"
"Closed Complete","Site Down","T0917","IHS_YND_371","NOCINC0002682330","Min=
ka","IHS_YND_369, IHS_YND_531, IHS_YND_554, IHS_YND_553, IHS_YND_372","24-0=
7-2024 16:36:28","24-07-2024 16:29:17","24-07-2024 17:33:53","Site went dow=
n due to hybrid system dysfunction // Gen start manually","Fanda Brice","Eq=
uipment Repair","Passive","Hybrid","Hybrid Module","Site went down due to h=
ybrid system dysfunction // Gen start manually","dorothy.djantio@ihstowers.=
com","452","24-07-2024 16:36:28","Sagemcom CMR"
"Closed Complete","Site Down","T3172","IHS_YND_043","NOCINC0002682027","Emi=
a","","24-07-2024 15:48:56","24-07-2024 15:44:48","24-07-2024 16:32:43","No=
 power issue site on grid with U=3D54v Mbah osiah(674007438) from Huawei is=
 informed","","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","No power issue site on grid with U=3D54v//site up=
 at 08:48 PM Mbah osiah(674007438) from Huawei is informed","dorothy.djanti=
o@ihstowers.com","248","24-07-2024 15:48:56","Sagemcom CMR"
"Closed Complete","Site Down","T0540","IHS_YND_026","NOCINC0002682022","ENA=
M","","24-07-2024 15:47:46","24-07-2024 15:45:38","24-07-2024 16:00:56","Gr=
id outage // Grid return","","Grid Supply","Passive","Grid","National Grid =
- Grid Outage Issue","Grid outage // Grid return","dorothy.djantio@ihstower=
s.com","130","24-07-2024 15:47:46","Sagemcom CMR"
"Closed Complete","Site Down","T0568","IHS_YND_365","NOCINC0002682000","Ako=
no","","24-07-2024 15:41:56","24-07-2024 15:33:48","24-07-2024 15:54:17","G=
rid outage. Site went down because gen ran until fuel shortage//Refueling o=
ngoing","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Gri=
d outage. Site went down because gen ran until fuel shortage//Refueling ong=
oing","dorothy.djantio@ihstowers.com","489","24-07-2024 15:41:56","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002681998","Nko=
abang Ebolmedjock","","24-07-2024 15:41:04","24-07-2024 15:32:56","24-07-20=
24 16:09:10","site went down due to CB 63(A) disjonction on Dcbox // He rea=
rmed the CB","Mba Lazare Herve","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Circuit Breaker Issue","site went down due to CB 63(A) d=
isjonction on Dcbox // He rearmed the CB","dorothy.djantio@ihstowers.com","=
490","24-07-2024 15:41:04","Sagemcom CMR"
"Closed Complete","Site Down","T1492","IHS_YND_687","NOCINC0002681722","OLA=
MA","","24-07-2024 15:00:29","24-07-2024 14:57:18","25-07-2024 00:12:43","A=
ctive: No power issue, site is on grid with Ubaie=3D49V,  Lionel Tchatchou =
(694693436) from Huawei is informed","Fanda Brice","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No p=
ower issue, site is on grid with Ubaie=3D49V,  Lionel Tchatchou (694693436)=
 from Huawei is informed","dorothy.djantio@ihstowers.com","193","24-07-2024=
 15:00:29","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0002681542","Ona=
ngondi (melen bikop)","","24-07-2024 14:37:35","24-07-2024 14:33:24","24-07=
-2024 15:10:06","ACTIVE// No power issue on site U=3D 52.1 V site on Grid, =
The TX  Rodrigue Moungan (651319438) from Huawei is working on site","Fanda=
 Brice","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","ACTIVE// No power issue on site U=3D 52.1 V site on Gri=
d, The TX  Rodrigue Moungan (651319438) from Huawei is working on site","do=
rothy.djantio@ihstowers.com","253","24-07-2024 14:37:35","Sagemcom CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0002681536","Nko=
lfon Cimencam","","24-07-2024 14:36:48","24-07-2024 14:27:40","24-07-2024 1=
4:32:38","Active: No power issue, site is on grid with Ubaie=3D50V  Lionel =
Tchatchou (694693436) from Huawei is informed","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active: No power issue, site is on grid with Ubaie=3D50V  Lionel Tchatchou=
 (694693436) from Huawei is informed","dorothy.djantio@ihstowers.com","550"=
,"24-07-2024 14:36:48","Sagemcom CMR"
"Closed Complete","Site Down","T0580","IHS_YND_310","NOCINC0002681488","Nom=
ayos","","24-07-2024 14:29:07","24-07-2024 14:26:50","24-07-2024 14:32:29",=
"site went down because insufficiency of rectifiers due to increase load //=
He reseted the rectifier","Fanda Brice","Equipment Repair","Passive","Recti=
fier","Rectifier Module","site went down because insufficiency of rectifier=
s due to increase load //He reseted the rectifier","dorothy.djantio@ihstowe=
rs.com","138","24-07-2024 14:29:07","Sagemcom CMR"
"Cancelled","Warning","CTR_161","IHS_YND_506","NOCINC0002681429","Omnisport=
-Rail","","24-07-2024 14:15:06","","","","Delor Telezing","","","","","","k=
amga.virgile@ihstowers.com","4113","24-07-2024 14:15:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0002681270","N=
komkana","","24-07-2024 13:57:32","24-07-2024 13:53:17","24-07-2024 13:55:2=
5","Active: no power issue on site, U=3D54,6 Team Edmon /655754488/ from ZT=
E is working on site","","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","Active: no power issue on site, U=3D54=
,6 Team Edmon /655754488/ from ZTE is working on site","kamga.virgile@ihsto=
wers.com","256","24-07-2024 13:57:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_458","IHS_YND_526","NOCINC0002681148","N=
koabang2","","24-07-2024 13:26:21","24-07-2024 13:15:10","24-07-2024 14:43:=
59","Grid outage. Site went down because gen ran until fuel shortage//Refue=
ling done","Mba Lazare Herve","Fuel Outage","Passive","Diesel","Diesel Outa=
ge","Grid outage. Site went down because gen ran until fuel shortage//Refue=
ling done","kamga.virgile@ihstowers.com","673","24-07-2024 13:26:21","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_046","IHS_YND_008","NOCINC0002681044","C=
NDH","","24-07-2024 13:12:03","24-07-2024 12:44:47","24-07-2024 13:00:45","=
Active: No power issue, site is on grid with Ubaie=3D55,2V,Olivier/Romeo (6=
77269888/651559985) from ZTE working on site","Paul BIBOUM","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive: No power issue, site is on grid with Ubaie=3D55,2V,Olivier/Romeo (6772=
69888/651559985) from ZTE working on site
","kamga.virgile@ihstowers.com","1637","24-07-2024 13:12:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_242","IHS_YND_059","NOCINC0002680973","E=
-Poste 2","","24-07-2024 13:01:48","24-07-2024 12:41:31","24-07-2024 14:12:=
38","Active: No power issue, site is on grid with Ubaie=3D52,8V,Amayla (699=
127444) from ZTE working on site.","Paul BIBOUM","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No pow=
er issue, site is on grid with Ubaie=3D52,8V,Amayla (699127444) from ZTE wo=
rking on site
","kamga.virgile@ihstowers.com","1218","24-07-2024 13:01:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_096","IHS_YND_042","NOCINC0002680929","M=
vog-Ada_OCM","","24-07-2024 12:56:19","24-07-2024 12:29:09","24-07-2024 13:=
00:40","Active: No power issue, site is on grid with Ubaie=3D53,1V, Raymond=
 (694391842) from ZTE working on site.","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power iss=
ue, site is on grid with Ubaie=3D53,1V, Raymond (694391842) from ZTE workin=
g on site
","kamga.virgile@ihstowers.com","1631","24-07-2024 12:56:19","Sagemcom CMR"
"Closed Complete","Warning","CTR_128","IHS_YND_044","NOCINC0002680869","Pol=
ytechnique","","24-07-2024 12:51:16","","","Wrongly ticket","","Warning","W=
arning","SYSTEM","Warning - Config Error","Wrongly ticket","kamga.virgile@i=
hstowers.com","12972","24-07-2024 12:51:16","Sagemcom CMR"
"Closed Complete","Site Down","T2760","IHS_YND_370","NOCINC0002680851","Mom=
","","24-07-2024 12:36:32","24-07-2024 12:23:23","24-07-2024 14:13:04","Gri=
d outage site went down because gen failed to start due to Battery GE  and =
static  charger faulty //he started  with  external battery ","Fanda Brice"=
,"Equipment Repair","Passive","ACDG Gen","ACDG - Charging Alternator","Grid=
 outage site went down because gen failed to start due to Battery GE  and s=
tatic  charger faulty //he started  with  external battery ","alexandre.kam=
al@ihstowers.com","1796","24-07-2024 12:36:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_528","IHS_YND_695","NOCINC0002680716","M=
bankomo IHS","","24-07-2024 12:15:59","24-07-2024 12:00:41","24-07-2024 12:=
49:40","Grid outage.gen ran until fuel shortage//Refueling done","Fanda Bri=
ce","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran u=
ntil fuel shortage//Refueling done","kamga.virgile@ihstowers.com","919","24=
-07-2024 12:15:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0002680703","Y=
de-M-Central","","24-07-2024 12:12:02","24-07-2024 12:11:54","24-07-2024 12=
:27:17","Active: No power issue, site is on grid with Ubaie=3D54,4V, Ange (=
237 6 87 35 14 56) from ZTE working on site.","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No pow=
er issue, site is on grid with Ubaie=3D54,4V, Ange (237 6 87 35 14 56) from=
 ZTE working on site.
","kamga.virgile@ihstowers.com","8","24-07-2024 12:12:02","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0002680690","Ona=
ngondi (melen bikop)","","24-07-2024 12:08:54","24-07-2024 11:44:47","24-07=
-2024 12:52:00","Technician is on the way ETA : 13h00","Fanda Brice","Equip=
ment Repair","Passive","ACDG Gen","ACDG - Radiator Leakage","grid outage an=
d gen started, gen stoppen because hight temperature due to pierced radiato=
r// He added the water in radiator, site on gen","alexandre.kamal@ihstowers=
.com","1448","24-07-2024 12:08:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_377","IHS_YND_005","NOCINC0002680478","I=
mm-Olympique","","24-07-2024 11:28:10","24-07-2024 11:12:48","24-07-2024 11=
:30:46","Active: No power issue, site is on grid with Ubaie=3D54,4V, Domini=
que (694552106) from ZTE working on site.","Paul BIBOUM","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
: No power issue, site is on grid with Ubaie=3D54,4V, Dominique (694552106)=
 from ZTE working on site.","kamga.virgile@ihstowers.com","924","24-07-2024=
 11:28:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_128","IHS_YND_044","NOCINC0002680450","P=
olytechnique","","24-07-2024 11:21:23","24-07-2024 10:52:55","24-07-2024 11=
:00:15","Active: No power issue, site is on grid with Ubaie=3D52,1V,  Romeo=
 (694204295) from ZTE working on site.","","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power iss=
ue, site is on grid with Ubaie=3D52,1V,  Romeo (694204295) from ZTE working=
 on site.
","kamga.virgile@ihstowers.com","1710","24-07-2024 11:21:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_127","IHS_YND_026","NOCINC0002680332","E=
NAM","","24-07-2024 10:58:41","24-07-2024 10:45:17","24-07-2024 11:00:48","=
Active: No power issue, site is on grid with Ubaie=3D53,3V, Serge (69824488=
9) from ZTE working on site.","","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","Active: No power issue, site i=
s on grid with Ubaie=3D53,3V, Serge (698244889) from ZTE working on site
","kamga.virgile@ihstowers.com","806","24-07-2024 10:58:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_874","IHS_YND_195","NOCINC0002680284","c=
hina embassy yde","","24-07-2024 10:54:25","24-07-2024 10:44:17","24-07-202=
4 11:00:18","Acttive: no power issue, site on gen with Ubaie=3D53,3V, Eloun=
dou(6) from Huawei is informed, site impacted by BASTOS GOLF(is not managed=
 by Sagemcom).","","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Acttive: no power issue, site on gen with Ub=
aie=3D53,3V, Eloundou(6) from Huawei is informed, site impacted by BASTOS G=
OLF(is not managed by Sagemcom).
","kamga.virgile@ihstowers.com","609","24-07-2024 10:54:25","Sagemcom CMR"
"Closed Complete","Warning","T1440","IHS_YND_698","NOCINC0002680151","EBOM"=
,"","24-07-2024 10:28:58","","","Site in alarm due to grid outage//DG start=
ed automatically.","Hyemafo Gildas","Warning","Warning","POWER","Warning - =
National Grid - Grid Outage Issue","Site in alarm due to grid outage//DG st=
arted automatically.","ludovic.tchagna@ihstowers.com","5","24-07-2024 10:28=
:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_447","IHS_YND_061","NOCINC0002680105","Y=
de University","","24-07-2024 10:19:08","24-07-2024 10:05:54","24-07-2024 1=
0:29:01","Active: No power issue, site is on grid with Ubaie=3D54V, Serge (=
694250345) from ZTE working on site.","Paul BIBOUM","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No =
power issue, site is on grid with Ubaie=3D54V, Serge (694250345) from ZTE w=
orking on site.","kamga.virgile@ihstowers.com","795","24-07-2024 10:19:08",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_131","IHS_YND_504","NOCINC0002679968","E=
lig Edzoa","","24-07-2024 09:55:39","23-07-2024 13:37:16","23-07-2024 13:47=
:10","Acttive: no power issue, site on gen with Ubaie=3D54V, armand nguesta=
(691144412) from Huawei is informed","Delor Telezing","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acttive: =
no power issue, site on gen with Ubaie=3D54V, armand nguesta(691144412) fro=
m Huawei is informed","marie.kwin@ihstowers.com","73103","24-07-2024 09:55:=
39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_047","IHS_YND_012","NOCINC0002679928","E=
lig-Essono","","24-07-2024 09:46:36","24-07-2024 09:35:24","24-07-2024 09:4=
0:09","Active: No power issue, site is on grid with Ubaie=3D54V,  Dominique=
 (694552106) from ZTE working on site.","Paul BIBOUM","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: N=
o power issue, site is on grid with Ubaie=3D54V,  Dominique (694552106) fro=
m ZTE working on site.
","kamga.virgile@ihstowers.com","673","24-07-2024 09:46:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_548","IHS_YND_032","NOCINC0002679880","K=
amajou Building","","24-07-2024 09:32:45","24-07-2024 09:28:36","24-07-2024=
 09:30:56","Active: No power issue, site is on grid with Ubaie=3D53V,  Deni=
s (693675998) from ZTE working on site.","Paul BIBOUM","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
No power issue, site is on grid with Ubaie=3D53V,  Denis (693675998) from Z=
TE working on site.
","kamga.virgile@ihstowers.com","249","24-07-2024 09:32:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_401","IHS_YND_041","NOCINC0002679875","L=
ycee Leclerc School","","24-07-2024 09:29:28","24-07-2024 09:24:21","24-07-=
2024 10:00:29","Active: No power issue, site is on grid with Ubaie=3D53V,  =
kenfack (693932700) from ZTE working on site.","Paul BIBOUM","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: No power issue, site is on grid with Ubaie=3D53V,  kenfack (693932700=
) from ZTE working on site.
","kamga.virgile@ihstowers.com","308","24-07-2024 09:29:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0002679868","M=
ontee-Anne-Rouge","","24-07-2024 09:28:04","24-07-2024 09:18:53","24-07-202=
4 09:30:48","Active: No power issue, site is on grid with Ubaie=3D53V,  Dom=
inique Membila (69455210) from ZTE working on site.","","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active:=
 No power issue, site is on grid with Ubaie=3D53V,  Dominique Membila (6945=
5210) from ZTE working on site.","kamga.virgile@ihstowers.com","553","24-07=
-2024 09:28:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_632","IHS_YND_721","NOCINC0002679859","V=
OIRIE MUNICIPALE YAOUNDE","","24-07-2024 09:26:23","24-07-2024 08:45:55","2=
4-07-2024 09:00:57","Active: No power issue, site is on grid with Ubaie=3D5=
3V, GUEULIEU TCHOUASSI MARCELIN (675309535) from ZTE working on site.","Pau=
l BIBOUM","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active: No power issue, site is on grid with Ubaie=3D=
53V, GUEULIEU TCHOUASSI MARCELIN (675309535) from ZTE working on site.
","kamga.virgile@ihstowers.com","2429","24-07-2024 09:26:23","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0002678876","MVA=
N SACEL","","24-07-2024 05:15:40","24-07-2024 04:53:21","24-07-2024 05:43:5=
7","Active// No power issue on site ,site on Gen  with Ubaie=3D52.8 V TX FM=
E Lionel steve/655184876 from Huawei is informed ","MINKA NICOLAS","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active// No power issue on site ,site on Gen  with Ubaie=3D52.8 V  TX F=
ME Lionel steve/655184876 from Huawei is informed=20
","joelle.ekessi@ihstowers.com","1340","24-07-2024 05:15:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0002678744","Mambine"=
,"","24-07-2024 04:29:30","24-07-2024 04:15:54","24-07-2024 05:57:11","Casc=
aded Incident from TTO2491576 - Cascade Removed From TTO2491576","Fanda Bri=
ce","Cascade Outage","Passive","Cascade Passive","Cascade Passive","site we=
nt down due to 03/06 rectifiers faulty// He added 02 rectifiers, site on gr=
id(01 rectifer to be replaced)","system","816","24-07-2024 04:29:30","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_367","NOCINC0002678738","Mandoumb=
a OCM","","24-07-2024 04:29:30","24-07-2024 04:15:54","24-07-2024 05:57:11"=
,"Cascaded Incident from TTO2491576 - Cascade Removed From TTO2491576","Kem=
eni Franklin","Cascade Outage","Passive","Cascade Passive","Cascade Passive=
","site went down due to 03/06 rectifiers faulty// He added 02 rectifiers, =
site on grid(01 rectifer to be replaced)","system","816","24-07-2024 04:29:=
30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0002678741","Ebeba","=
","24-07-2024 04:29:30","24-07-2024 04:15:54","24-07-2024 05:57:11","Cascad=
ed Incident from TTO2491576 - Cascade Removed From TTO2491576","Fanda Brice=
","Cascade Outage","Passive","Cascade Passive","Cascade Passive","site went=
 down due to 03/06 rectifiers faulty// He added 02 rectifiers, site on grid=
(01 rectifer to be replaced)","system","816","24-07-2024 04:29:30","Sagemco=
m CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0002678739","Mbankomo=
 IHS","","24-07-2024 04:29:30","24-07-2024 04:15:54","24-07-2024 05:57:11",=
"Cascaded Incident from TTO2491576 - Cascade Removed From TTO2491576","Fand=
a Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passive","si=
te went down due to 03/06 rectifiers faulty// He added 02 rectifiers, site =
on grid(01 rectifer to be replaced)","system","816","24-07-2024 04:29:30","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0002678737","Sous Pre=
fecture","","24-07-2024 04:29:30","24-07-2024 04:15:54","24-07-2024 05:57:1=
1","Cascaded Incident from TTO2491576 - Cascade Removed From TTO2491576","F=
anda Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passive",=
"site went down due to 03/06 rectifiers faulty// He added 02 rectifiers, si=
te on grid(01 rectifer to be replaced)","system","816","24-07-2024 04:29:30=
","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0002678746","Nkongtoc=
k","","24-07-2024 04:29:30","24-07-2024 04:15:54","24-07-2024 05:57:11","Ca=
scaded Incident from TTO2491576 - Cascade Removed From TTO2491576","Kemeni =
Franklin","Cascade Outage","Passive","Cascade Passive","Cascade Passive","s=
ite went down due to 03/06 rectifiers faulty// He added 02 rectifiers, site=
 on grid(01 rectifer to be replaced)","system","816","24-07-2024 04:29:30",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_310","NOCINC0002678742","Nomayos"=
,"IHS_YND_314, IHS_YND_367, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_=
697, IHS_YND_762, IHS_YND_330, IHS_YND_350, IHS_YND_335, IHS_YND_349","24-0=
7-2024 04:29:30","24-07-2024 04:15:54","24-07-2024 07:42:50","site went dow=
n due to 03/06 rectifiers faulty// He added 02 rectifiers, site on grid(01 =
rectifer to be replaced)","Fanda Brice","Equipment Repair","Passive","Recti=
fier","Rectifier Module","site went down due to 03/06 rectifiers faulty// H=
e added 02 rectifiers, site on grid(01 rectifer to be replaced)","system","=
816","24-07-2024 04:29:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_330","NOCINC0002678743","OKOA Pea=
ge","","24-07-2024 04:29:30","24-07-2024 04:15:54","24-07-2024 05:57:11","C=
ascaded Incident from TTO2491576 - Cascade Removed From TTO2491576","Fanda =
Brice","Cascade Outage","Passive","Cascade Passive","Cascade Passive","site=
 went down due to 03/06 rectifiers faulty// He added 02 rectifiers, site on=
 grid(01 rectifer to be replaced)","system","816","24-07-2024 04:29:30","Sa=
gemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0002678745","Angongo"=
,"","24-07-2024 04:29:30","24-07-2024 04:15:54","24-07-2024 05:57:11","Casc=
aded Incident from TTO2491576 - Cascade Removed From TTO2491576","Fanda Bri=
ce","Cascade Outage","Passive","Cascade Passive","Cascade Passive","site we=
nt down due to 03/06 rectifiers faulty// He added 02 rectifiers, site on gr=
id(01 rectifer to be replaced)","system","816","24-07-2024 04:29:30","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0002678740","Nkenglik=
ok","","24-07-2024 04:29:30","24-07-2024 04:15:54","24-07-2024 05:57:11","C=
ascaded Incident from TTO2491576 - Cascade Removed From TTO2491576","Kemeni=
 Franklin","Cascade Outage","Passive","Cascade Passive","Cascade Passive","=
site went down due to 03/06 rectifiers faulty// He added 02 rectifiers, sit=
e on grid(01 rectifer to be replaced)","system","816","24-07-2024 04:29:30"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0002678732","Nko=
lfon Cimencam","","24-07-2024 04:25:47","24-07-2024 04:54:54","24-07-2024 0=
7:42:50","site went down due to 03/06 rectifiers faulty// He added 02 recti=
fiers, site on grid(01 rectifer to be replaced)","Hyemafo Gildas","Cascade =
Outage","Passive","Cascade Passive","Cascade Passive","site went down due t=
o 03/06 rectifiers faulty// He added 02 rectifiers, site on grid(01 rectife=
r to be replaced)","joelle.ekessi@ihstowers.com","1317","24-07-2024 04:25:4=
7","Sagemcom CMR"
"Closed Complete","Site Down","CTR_527","IHS_YND_697","NOCINC0002678730","N=
omayos-IHS","","24-07-2024 04:24:58","24-07-2024 04:15:54","24-07-2024 05:5=
7:14","site went down due to 03/06 rectifiers faulty// He added 02 rectifie=
rs, site on grid(01 rectifer to be replaced)","Fanda Brice","Cascade Outage=
","Passive","Cascade Passive","Cascade Passive","site went down due to 03/0=
6 rectifiers faulty// He added 02 rectifiers, site on grid(01 rectifer to b=
e replaced)","emmanuel.ghani@ihstowers.com","546","24-07-2024 04:24:58","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0002678106","B=
astos Bethesda","","24-07-2024 02:38:33","24-07-2024 02:34:25","24-07-2024 =
02:46:05","Grid outage, site went down before gen start due to poor battery=
 backup // Gen start automatically","Mboua Thierry","Equipment Repair","Pas=
sive","Control Panel","Power Cabinet - Battery Low","Grid outage, site went=
 down before gen start due to poor battery backup // Gen start automaticall=
y","emmanuel.ghani@ihstowers.com","250","24-07-2024 02:38:33","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002677647","M=
asque","","24-07-2024 01:42:42","24-07-2024 01:36:36","24-07-2024 01:59:16"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","emm=
anuel.ghani@ihstowers.com","368","24-07-2024 01:42:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0002676991","B=
iteng-Maetur","","23-07-2024 22:41:34","23-07-2024 20:33:19","23-07-2024 23=
:10:18","No power issue on site. Site on Gen with Ubaie=3D53.4V  The Team R=
aymond/695431118/from ZTE is working on site","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"No power issue on site. Site on Gen with Ubaie=3D53.4V  The Team Raymond/=
695431118/from ZTE is working on site","emmanuel.ghani@ihstowers.com","7696=
","23-07-2024 22:41:34","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002676910","Nko=
l-Mbanda","","23-07-2024 22:24:54","23-07-2024 22:22:49","24-07-2024 01:35:=
04","Grid outage site site went because Gen failed to started due to ATS Bu=
rn // He manually started the Gen (Site Swapped by ZTE)","MINKA NICOLAS","E=
quipment Repair","Passive","Control Panel","ATS-AMF Issue","Grid outage sit=
e site went because Gen failed to started due to ATS Burn // He manually st=
arted the Gen (Site Swapped by ZTE)","joelle.ekessi@ihstowers.com","6804","=
23-07-2024 22:24:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_395","IHS_YND_249","NOCINC0002676307","B=
iteng-Maetur","","23-07-2024 20:29:06","23-07-2024 19:04:38","23-07-2024 19=
:10:18","Active: no power issue on site, U=3D54,6 Team Raymon /695431118/ f=
rom ZTE is working on site","Mba Lazare Herve","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power=
 issue on site, U=3D54,6 Team Raymon /695431118/ from ZTE is working on sit=
e","ange.kongo@ihstowers.com","5069","23-07-2024 20:29:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_339","IHS_YND_073","NOCINC0002676279","C=
hapelle-Obili","","23-07-2024 20:18:37","23-07-2024 17:49:36","23-07-2024 1=
9:55:50","site went down because the CB(125A) of PWC dysjoncted due to incr=
ease load on site // he made a bridge CB(125*63)  (Site Swapped by ZTE)","P=
aul BIBOUM","Equipment Repair","Passive","Control Panel","Power Cabinet - C=
ircuit Breaker Issue","site went down because the CB(125A) of PWC dysjoncte=
d due to increase load on site // he made a bridge CB(125*63)  (Site Swappe=
d by ZTE)","ange.kongo@ihstowers.com","8942","23-07-2024 20:18:37","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0002676232","A=
WAE OCM","","23-07-2024 20:07:31","23-07-2024 19:07:21","24-07-2024 05:30:1=
2","No power issue on site.Site on Grid with Ubaie=3D54.6 V The Tx FME Lion=
el// 694693436of Huawei is informed","Mba Lazare Herve","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site.Site on Grid with Ubaie=3D54.6 V The Tx FME Lionel// 694693=
436of Huawei is informed","alwine.fambou@ihstowers.com","3611","23-07-2024 =
20:07:31","Sagemcom CMR"
"Closed Complete","Site Down","T1150","IHS_YND_363","NOCINC0002676055","Ona=
ngondi (melen bikop)","","23-07-2024 19:32:37","23-07-2024 19:23:32","23-07=
-2024 20:03:54","site went down because Gen failed to start// He reset the =
Gen card( investigation ongoing)","Fanda Brice","Equipment Repair","Passive=
","ACDG Gen","ACDG - Control Panel","site went down because Gen failed to s=
tart// He reset the Gen card( investigation ongoing)","ludivine.ngamaleu@ih=
stowers.com","546","23-07-2024 19:32:37","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002675779","Nko=
g-Edzen","","23-07-2024 18:50:01","23-07-2024 18:43:56","23-07-2024 20:23:1=
0","Grid outage.gen ran until fuel shortage//Refueling done","Parker Tchoup=
","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage.gen ran unt=
il fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.com","366","=
23-07-2024 18:50:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002675770","M=
asque","","23-07-2024 18:47:42","23-07-2024 18:43:34","23-07-2024 20:43:23"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","ang=
e.kongo@ihstowers.com","250","23-07-2024 18:47:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_332","NOCINC0002675586","NKOMEKUI=
 OCM","IHS_YND_341","23-07-2024 17:58:30","23-07-2024 17:51:51","23-07-2024=
 17:57:34","Grid outage, site went down befor gen start due to poor battery=
 backup // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipment R=
epair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage=
, site went down befor gen start due to poor battery backup // Gen start au=
tomatically","system","399","23-07-2024 17:58:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0002675580","L=
obo OCM","","23-07-2024 17:57:09","23-07-2024 17:51:51","23-07-2024 17:57:3=
4","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Passive","Cascade Passiv=
e","Cascade Passive","Grid outage, site went down befor gen start due to po=
or battery backup // Gen start automatically","ange.kongo@ihstowers.com","3=
19","23-07-2024 17:57:09","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002675066","Nko=
l-Mbanda","","23-07-2024 15:52:47","23-07-2024 15:49:42","23-07-2024 16:08:=
52","Grid outage, site went down before gen start due to poor battery backu=
p // Grid power return","MINKA NICOLAS","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site went down before=
 gen start due to poor battery backup // Grid power return","ludivine.ngama=
leu@ihstowers.com","187","23-07-2024 15:52:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0002674802","B=
astos Bethesda","","23-07-2024 14:51:38","23-07-2024 14:44:30","23-07-2024 =
15:04:51","Grid outage, site went down before gen start due to poor battery=
 backup // Grid power return","Mboua Thierry","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Grid power return","ange.kon=
go@ihstowers.com","429","23-07-2024 14:51:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002674642","E=
TOUDI CHAPELLE","","23-07-2024 14:24:23","23-07-2024 14:14:59","23-07-2024 =
18:14:46","ACTIVE No power issue site on Grid with UBaie=3D51.8 V  The TX A=
rmand Nguetsa(699949553) from Huawei is informed . Repetitive issue","Delor=
 Telezing","Customer Equipment Failure","Active","Active Equipment Failure"=
,"BTS/TX Fault Alarm","ACTIVE No power issue site on Grid with UBaie=3D51.8=
 V  The TX Armand Nguetsa(699949553) from Huawei is informed . Repetitive i=
ssue","ange.kongo@ihstowers.com","566","23-07-2024 14:24:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0002674629","Mamb",""=
,"23-07-2024 14:21:10","23-07-2024 14:13:18","23-07-2024 14:16:27","Cascade=
d Incident from TTO2486753","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down before gen s=
tart due to poor battery backup // Grid power return","system","472","23-07=
-2024 14:21:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0002674627","Ngog Map=
ubi","","23-07-2024 14:21:10","23-07-2024 14:13:18","23-07-2024 14:16:27","=
Cascaded Incident from TTO2486753","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // Grid power return","system","472"=
,"23-07-2024 14:21:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0002674628","Boumnyeb=
el","","23-07-2024 14:21:10","23-07-2024 14:13:18","23-07-2024 14:16:27","C=
ascaded Incident from TTO2486753","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 gen start due to poor battery backup // Grid power return","system","472",=
"23-07-2024 14:21:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0002674614","B=
oumnyebel OCM","IHS_YND_419, IHS_YND_381, IHS_YND_376","23-07-2024 14:17:26=
","23-07-2024 14:13:18","23-07-2024 14:16:27","Grid outage, site went down =
before gen start due to poor battery backup // Grid power return","Kemeni F=
ranklin","Equipment Repair","Passive","Control Panel","Power Cabinet - Batt=
ery Low","Grid outage, site went down before gen start due to poor battery =
backup // Grid power return","ange.kongo@ihstowers.com","249","23-07-2024 1=
4:17:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_349","NOCINC0002674555","Nkongtoc=
k","","23-07-2024 14:01:50","23-07-2024 13:46:33","23-07-2024 13:50:58","Ca=
scaded Incident from TTO2486666","Kemeni Franklin","Cascade Outage","Active=
","Cascade Active","Cascade Active","No power issue site on grid with U=3D5=
4v RM alain(691144423) from Huawi informed us that optical fiber issue on t=
he area","system","917","23-07-2024 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_335","NOCINC0002674554","Angongo"=
,"","23-07-2024 14:01:50","23-07-2024 13:46:33","23-07-2024 13:50:58","Casc=
aded Incident from TTO2486666","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on grid with U=3D54v RM =
alain(691144423) from Huawi informed us that optical fiber issue on the are=
a","system","917","23-07-2024 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_697","NOCINC0002674551","Nomayos-=
IHS","","23-07-2024 14:01:50","23-07-2024 13:46:33","23-07-2024 13:50:58","=
Cascaded Incident from TTO2486666","Fanda Brice","Cascade Outage","Active",=
"Cascade Active","Cascade Active","No power issue site on grid with U=3D54v=
 RM alain(691144423) from Huawi informed us that optical fiber issue on the=
 area","system","917","23-07-2024 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_310","NOCINC0002674552","Nomayos"=
,"","23-07-2024 14:01:50","23-07-2024 13:46:33","23-07-2024 13:50:58","Casc=
aded Incident from TTO2486666","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on grid with U=3D54v RM =
alain(691144423) from Huawi informed us that optical fiber issue on the are=
a","system","917","23-07-2024 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_339","NOCINC0002674550","Ebeba","=
","23-07-2024 14:01:50","23-07-2024 13:46:33","23-07-2024 13:50:58","Cascad=
ed Incident from TTO2486666","Fanda Brice","Cascade Outage","Active","Casca=
de Active","Cascade Active","No power issue site on grid with U=3D54v RM al=
ain(691144423) from Huawi informed us that optical fiber issue on the area"=
,"system","917","23-07-2024 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_695","NOCINC0002674548","Mbankomo=
 IHS","","23-07-2024 14:01:50","23-07-2024 13:46:33","23-07-2024 13:50:58",=
"Cascaded Incident from TTO2486666","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","No power issue site on grid with U=3D54=
v RM alain(691144423) from Huawi informed us that optical fiber issue on th=
e area","system","917","23-07-2024 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_314","NOCINC0002674547","Sous Pre=
fecture","","23-07-2024 14:01:50","23-07-2024 13:46:33","23-07-2024 13:50:5=
8","Cascaded Incident from TTO2486666","Fanda Brice","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue site on grid with U=
=3D54v RM alain(691144423) from Huawi informed us that optical fiber issue =
on the area","system","917","23-07-2024 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_348","NOCINC0002674549","Nkenglik=
ok","","23-07-2024 14:01:50","23-07-2024 13:46:33","23-07-2024 13:50:58","C=
ascaded Incident from TTO2486666","Kemeni Franklin","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","No power issue site on grid with U=3D=
54v RM alain(691144423) from Huawi informed us that optical fiber issue on =
the area","system","917","23-07-2024 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_350","NOCINC0002674553","Mambine"=
,"","23-07-2024 14:01:50","23-07-2024 13:46:33","23-07-2024 13:50:58","Casc=
aded Incident from TTO2486666","Fanda Brice","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue site on grid with U=3D54v RM =
alain(691144423) from Huawi informed us that optical fiber issue on the are=
a","system","917","23-07-2024 14:01:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_541","IHS_YND_330","NOCINC0002674539","O=
KOA Peage","IHS_YND_314, IHS_YND_695, IHS_YND_348, IHS_YND_339, IHS_YND_697=
, IHS_YND_310, IHS_YND_350, IHS_YND_335, IHS_YND_349","23-07-2024 13:59:42"=
,"23-07-2024 13:46:33","23-07-2024 13:50:58","No power issue site on grid w=
ith U=3D54v RM alain(691144423) from Huawi informed us that optical fiber i=
ssue on the area","Fanda Brice","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid wit=
h U=3D54v RM alain(691144423) from Huawi informed us that optical fiber iss=
ue on the area","etienne.itondo@ihstowers.com","790","23-07-2024 13:59:42",=
"Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0002674404","Bon=
djock","","23-07-2024 13:31:05","23-07-2024 13:23:56","23-07-2024 14:10:59"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen start automaticaly","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site went down before=
 gen start due to poor battery backup // Gen start automaticaly","dorothy.d=
jantio@ihstowers.com","430","23-07-2024 13:31:05","Sagemcom CMR"
"Closed Complete","Site Down","T1406","IHS_YND_684","NOCINC0002674399","Eki=
e sud","","23-07-2024 13:29:56","23-07-2024 13:12:44","23-07-2024 19:13:24"=
,"Site went down because MPR BURN  and 02 rectifier faulty// He replaced th=
e rectifier and base connector(site swapped by ZTE)","Albran Byorel","Equip=
ment Repair","Passive","Rectifier","Rectifier Distribution","Site went down=
 because MPR BURN  and 02 rectifier faulty// He replaced the rectifier and =
base connector(site swapped by ZTE)","dorothy.djantio@ihstowers.com","1034"=
,"23-07-2024 13:29:56","Sagemcom CMR"
"Closed Complete","Site Down","T0476","IHS_YND_163","NOCINC0002674381","Nsa=
m Sofavinc","","23-07-2024 13:25:58","23-07-2024 13:04:43","23-07-2024 14:4=
2:35","site went down due to grid fluctuation and gen failed to start //Gri=
d stabilized","MINKA NICOLAS","Grid Supply","Passive","Grid","National Grid=
 - Phase Controller Faulty","site went down due to grid fluctuation and gen=
 failed to start //Grid stabilized","dorothy.djantio@ihstowers.com","1276",=
"23-07-2024 13:25:58","Sagemcom CMR"
"Closed Complete","Site Down","T2346","IHS_YND_732","NOCINC0002674369","Nsa=
m escale LP","","23-07-2024 13:23:26","23-07-2024 13:03:07","23-07-2024 14:=
46:29","Grid outage.no space to deploy mobile gen.//Grid power return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age.no space to deploy mobile gen.//Grid power return","dorothy.djantio@ihs=
towers.com","1220","23-07-2024 13:23:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002674236","M=
vog-Manga","","23-07-2024 13:00:39","23-07-2024 12:05:26","23-07-2024 12:10=
:20","Active//No power issue on site,site on Grid with Ubaie=3D53,8 V The T=
eam  franck//699670325 from ZTE is working on site","Albran Byorel","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site,site on Grid with Ubaie=3D53,8 V The Te=
am  franck//699670325 from ZTE is working on site","etienne.itondo@ihstower=
s.com","3314","23-07-2024 13:00:39","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002674201","Man=
guiers Dispensaire","","23-07-2024 12:52:25","23-07-2024 12:41:17","23-07-2=
024 13:03:30","Grid fluctuation site went down because Gen failled to start=
ed due to Grid bad voltage // He bypass the Grid and site on Gen","Fabrice =
Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller F=
aulty","Grid fluctuation site went down because Gen failled to started due =
to Grid bad voltage // He bypass the Grid and site on Gen","dorothy.djantio=
@ihstowers.com","670","23-07-2024 12:52:25","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002674075","Lad=
a I Yde","","23-07-2024 12:22:59","23-07-2024 12:10:48","23-07-2024 12:26:4=
1","Site went down due to work, MBA Herve /655999779 /Sagemcom/ is wotking =
on site (PM)//end of work","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Site went down due to work, =
MBA Herve /655999779 /Sagemcom/ is wotking on site (PM)//end of work","doro=
thy.djantio@ihstowers.com","733","23-07-2024 12:22:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002674031","Eto koss=
 Yde","","23-07-2024 12:08:50","23-07-2024 11:59:42","23-07-2024 14:20:54",=
"Cascaded Incident from TTO2486050","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start// Grid power return (Investigation ongoing)","system","5=
48","23-07-2024 12:08:50","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002674024","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","23-07-2024 12:07:51","23-07-2024 11:59=
:42","23-07-2024 14:20:54","Grid outage site went down because Gen failed t=
o start// Grid power return (Investigation ongoing)","Fanda Brice","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage site we=
nt down because Gen failed to start// Grid power return (Investigation ongo=
ing)","dorothy.djantio@ihstowers.com","489","23-07-2024 12:07:51","Sagemcom=
 CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0002674014","ELO=
UMDEM CARRIERE 2","","23-07-2024 12:06:36","23-07-2024 11:59:42","23-07-202=
4 14:20:54","Grid outage site went down because Gen failed to start// Grid =
power return (Investigation ongoing)","Fanda Brice","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage site went down because=
 Gen failed to start// Grid power return (Investigation ongoing)","dorothy.=
djantio@ihstowers.com","1338","23-07-2024 12:06:36","Sagemcom CMR"
"Closed Complete","Warning","T0091","IHS_YND_314","NOCINC0002673882","Sous =
Prefecture","","23-07-2024 11:42:28","",""," Site alarming because on batte=
ry// GEN started automatically","Fanda Brice","Warning","Warning","POWER","=
Warning - Site on Battery"," Site alarming because on battery// GEN started=
 automatically","marie.kwin@ihstowers.com","8","23-07-2024 11:42:28","Sagem=
com CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0002673816","Nko=
mkana","","23-07-2024 11:31:06","23-07-2024 11:21:48","23-07-2024 13:00:39"=
,"Active: no power issue on site, Ubaie:54.6v; Site went down during the wo=
rks Team Edmon /655754488/ from ZTE is working on site","","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve: no power issue on site, Ubaie:54.6v; Site went down during the works Te=
am Edmon /655754488/ from ZTE is working on site.","dorothy.djantio@ihstowe=
rs.com","559","23-07-2024 11:31:06","Sagemcom CMR"
"Closed Complete","Site Down","T2419","IHS_YND_504","NOCINC0002673719","Eli=
g Edzoa","","23-07-2024 11:13:33","23-07-2024 11:07:25","23-07-2024 12:11:3=
3","Site on Grid,site went down due to one rectifier faulty because of over=
voltage //He put site on DG ,Faulty rectifier must be changed.","Delor Tele=
zing","Equipment Repair","Passive","Rectifier","Rectifier Module","Site on =
Grid,site went down due to one rectifier faulty because of overvoltage //He=
 put site on DG ,Faulty rectifier must be changed.","dorothy.djantio@ihstow=
ers.com","369","23-07-2024 11:13:33","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0002673462","Biteng-M=
aetur","","23-07-2024 10:28:20","23-07-2024 10:19:04","23-07-2024 10:22:00"=
,"Cascaded Incident from TTO2485401","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work, Ra=
oul /657108509 / From IHS is working on site//End of works.","system","556"=
,"23-07-2024 10:28:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_211","NOCINC0002673459","Etoudi 2=
","","23-07-2024 10:28:20","23-07-2024 10:19:04","23-07-2024 10:22:00","Cas=
caded Incident from TTO2485401","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work, Raoul /6=
57108509 / From IHS is working on site//End of works.","system","556","23-0=
7-2024 10:28:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_694","NOCINC0002673458","ETOUDI C=
HAPELLE","","23-07-2024 10:28:20","23-07-2024 10:19:04","23-07-2024 10:22:0=
0","Cascaded Incident from TTO2485401","Delor Telezing","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to work, Ra=
oul /657108509 / From IHS is working on site//End of works.","system","556"=
,"23-07-2024 10:28:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0002673461","Essomba"=
,"","23-07-2024 10:28:20","23-07-2024 10:19:04","23-07-2024 10:22:00","Casc=
aded Incident from TTO2485401","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to work, Raoul /6=
57108509 / From IHS is working on site//End of works.","system","556","23-0=
7-2024 10:28:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0002673460","AWAE OCM=
","","23-07-2024 10:28:20","23-07-2024 10:19:04","23-07-2024 10:22:00","Cas=
caded Incident from TTO2485401","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to work, Raoul /=
657108509 / From IHS is working on site//End of works.","system","556","23-=
07-2024 10:28:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0002673457","Bitoto",=
"","23-07-2024 10:28:20","23-07-2024 10:19:04","23-07-2024 10:22:00","Casca=
ded Incident from TTO2485401","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to work, Raoul /65=
7108509 / From IHS is working on site//End of works.","system","556","23-07=
-2024 10:28:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002673438","B=
iteng","IHS_YND_292, IHS_YND_694, IHS_YND_211, IHS_YND_173, IHS_YND_179, IH=
S_YND_249","23-07-2024 10:23:11","23-07-2024 10:19:04","23-07-2024 10:22:00=
","Site went down due to work, Raoul /657108509 / From IHS is working on si=
te//End of works.","Mba Lazare Herve","Installation Activity","Passive","Pl=
anned Activity","Installation Activity","Site went down due to work, Raoul =
/657108509 / From IHS is working on site//End of works.","etienne.itondo@ih=
stowers.com","247","23-07-2024 10:23:11","Sagemcom CMR"
"Closed Complete","Warning","CTR_211","IHS_YND_248","NOCINC0002673349","Bit=
eng","","23-07-2024 10:04:47","","","Site in alarm  due to work, Raoul /657=
108509 / From IHS is working on site//End of works.","Mba Lazare Herve","Wa=
rning","Warning","POWER","Warning - Planned Activity - Passive","Site in al=
arm  due to work, Raoul /657108509 / From IHS is working on site//End of wo=
rks.","marie.kwin@ihstowers.com","4","23-07-2024 10:04:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_313","IHS_YND_307","NOCINC0002673344","E=
bogo","","23-07-2024 10:04:20","23-07-2024 09:50:13","23-07-2024 11:20:18",=
"no power issue on site Ubaie: 54.3V;  site on Grid. The TX FME Synphorien(=
675295205) from Huawei is informed.","Siligap Boris","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power i=
ssue on site Ubaie: 54.3V;  site on Grid. The TX FME Synphorien(675295205) =
from Huawei is informed.
","etienne.itondo@ihstowers.com","848","23-07-2024 10:04:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002673340","E=
lig-Edzoa","","23-07-2024 10:03:37","23-07-2024 09:48:28","23-07-2024 11:49=
:57","Grid outage //Grid restored,site remained down although grid restored=
,Power reset has been done.","","Grid Supply","Passive","Grid","National Gr=
id - Grid Outage Issue","Grid outage //Grid restored,site remained down alt=
hough grid restored,Power reset has been done.","etienne.itondo@ihstowers.c=
om","910","23-07-2024 10:03:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0002673339","N=
komkana","","23-07-2024 10:02:53","23-07-2024 09:45:47","23-07-2024 10:00:5=
3","Active: no power issue on site, U=3D54,6 Team Edmon /655754488/ from ZT=
E is working on site.","","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","Active: no power issue on site, U=3D5=
4,6 Team Edmon /655754488/ from ZTE is working on site
","etienne.itondo@ihstowers.com","1028","23-07-2024 10:02:53","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0002673293","E=
kie sud","","23-07-2024 09:54:55","23-07-2024 08:46:47","23-07-2024 11:16:4=
2","Site went down  due to Insufficiency of Rectifiers 03/05// Site is up r=
ectifier must be added .","Albran Byorel","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down  due to Insufficiency of Rectifi=
ers 03/05// Site is up rectifier must be added .","etienne.itondo@ihstowers=
.com","4089","23-07-2024 09:54:55","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002673264","Nko=
l-Mbanda","","23-07-2024 09:45:50","23-07-2024 09:02:43","23-07-2024 09:20:=
40","site went down because insufficiency of rectifiers due to increase loa=
d// site Stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","site went down because insufficiency of rectifiers d=
ue to increase load// site Stabilized","etienne.itondo@ihstowers.com","2588=
","23-07-2024 09:45:50","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0002673100","N=
dogbessol","","23-07-2024 09:11:09","23-07-2024 07:57:01","23-07-2024 11:40=
:19","","Kemeni Franklin","Customer Equipment Failure","Active","Active Equ=
ipment Failure","BTS/TX Fault Alarm","ACTIVE //No power issue site on Batte=
ry  with U=3D54,7 V The Tx FME  Etienne  (695033981)   from Hauawei  is inf=
ormed","etienne.itondo@ihstowers.com","4493","23-07-2024 09:11:09","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002672285","M=
asque","","23-07-2024 06:23:58","23-07-2024 06:13:53","23-07-2024 07:20:32"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","eti=
enne.itondo@ihstowers.com","606","23-07-2024 06:23:58","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002672277","Nko=
l-Mbanda","","23-07-2024 06:21:42","23-07-2024 06:04:20","23-07-2024 07:24:=
20","","MINKA NICOLAS","Equipment Repair","Passive","ACDG Gen","ACDG - Cont=
rol Panel","Grid fluctuation site went down because Gen started and stopped=
 due to alarm under Voltage // He bypass the Grid and site on Gen  (Site Sw=
apped by ZTE)","dorothy.djantio@ihstowers.com","3076","23-07-2024 06:21:42"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0002672127","B=
astos Bethesda","","23-07-2024 05:33:55","23-07-2024 05:27:50","23-07-2024 =
05:36:20","Grid outage site went down before Gen started due to poor batter=
y backup//Grid return","Mboua Thierry","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage site went down before G=
en started due to poor battery backup//Grid return","landry.etame@ihstowers=
.com","366","23-07-2024 05:33:55","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002671762","Lad=
a I Yde","","23-07-2024 03:04:03","23-07-2024 02:53:54","23-07-2024 07:00:2=
8","Active: no power issue site on grid with U=3D50V, The tx fme Lionel ste=
ve ADJEP/655184876/ from Huawei is informed and site up at 06:31 AM after a=
 power reset confirmed by him","Mba Lazare Herve","Customer Equipment Failu=
re","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no po=
wer issue site on grid with U=3D50V, The tx fme Lionel steve ADJEP/65518487=
6/ from Huawei is informed and site up at 06:31 AM after a power reset conf=
irmed by him","denis.mballa@ihstowers.com","610","23-07-2024 03:04:03","Sag=
emcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002671582","Nko=
l-Mbanda","","23-07-2024 01:46:47","23-07-2024 01:42:29","23-07-2024 01:55:=
47","site went down because insufficiency of rectifiers due to increase loa=
d// site Stabilized","MINKA NICOLAS","Equipment Repair","Passive","Rectifie=
r","Rectifier Module","site went down because insufficiency of rectifiers d=
ue to increase load// site Stabilized","denis.mballa@ihstowers.com","259","=
23-07-2024 01:46:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002671505","M=
asque","","23-07-2024 00:59:55","23-07-2024 00:56:50","23-07-2024 03:18:41"=
,"that No power issue on site. Site on Grid with Ubaie=3D54.3V    The TX FM=
E  Eloundou // 693212405// From  Huawei is informed. Repetitive issue","Fab=
rice Pouakam","Customer Equipment Failure","Active","Active Equipment Failu=
re","BTS/TX Fault Alarm","that No power issue on site. Site on Grid with Ub=
aie=3D54.3V   The TX FME  Eloundou // 693212405// From  Huawei is informed.=
 Repetitive issue
","landry.etame@ihstowers.com","186","23-07-2024 00:59:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0002671483","M=
volye-New","","23-07-2024 00:56:11","22-07-2024 14:12:03","22-07-2024 15:00=
:09","Active//No power issue on site,site on Grid with Ubaie=3D54,5  V The =
Tx FME  Hosiah //674007438 of Huawei is informed.","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//N=
o power issue on site,site on Grid with Ubaie=3D54,5  V The Tx FME  Hosiah =
//674007438 of Huawei is informed.
","landry.etame@ihstowers.com","38650","23-07-2024 00:56:11","Sagemcom CMR"
"Closed Complete","Site Down","T1835","IHS_YND_160","NOCINC0002671455","Com=
plex Beac II","","23-07-2024 00:42:39","23-07-2024 00:33:25","23-07-2024 00=
:56:16","Grid outage site went down because gen failed to start due to Gen =
Battery Discharge  //he started thr Gen  with external battery","Albran Byo=
rel","Equipment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Gr=
id outage site went down because gen failed to start due to Gen Battery Dis=
charge  //he started thr Gen  with external battery","denis.mballa@ihstower=
s.com","555","23-07-2024 00:42:39","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002671147","Eko=
unou","","22-07-2024 23:27:01","22-07-2024 23:22:46","22-07-2024 23:32:23",=
"Grid outage site went down because Gen failed to start due to poor battery=
 backup//Grid power return","Albran Byorel","Equipment Repair","Passive","C=
ontrol Panel","Power Cabinet - Battery Low","Grid outage site went down bec=
ause Gen failed to start due to poor battery backup//Grid power return","de=
nis.mballa@ihstowers.com","258","22-07-2024 23:27:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_795","NOCINC0002670869","Lada I Y=
de","","22-07-2024 22:31:10","22-07-2024 22:26:08","22-07-2024 22:27:08","C=
ascaded Incident from TTO2482545","Mba Lazare Herve","Cascade Outage","Acti=
ve","Cascade Active","Cascade Active","No power issue on site Ubaie:52v sit=
e on Battery (Hybrid gen site with treshold 50.1V) . TX FME Arthur (6944660=
50/Huawei) is informed	","system","302","22-07-2024 22:31:10","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0002670867","E=
toudi 2","","22-07-2024 22:31:03","22-07-2024 22:28:56","23-07-2024 03:18:4=
1","Active//No power issue on site,site on Grid with Ubaie=3D53,6  V The TX=
  Armand Ngetsa(699949553) from Huawei is informed,Site up at 10:43 PM","Fa=
brice Pouakam","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active//No power issue on site,site on Grid with=
 Ubaie=3D53,6  V The TX  Armand Ngetsa(699949553) from Huawei is informed,S=
ite up at 10:43 PM","landry.etame@ihstowers.com","128","22-07-2024 22:31:03=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002670858","E=
TOUDI CHAPELLE","","22-07-2024 22:28:26","22-07-2024 22:26:16","23-07-2024 =
03:18:41","No power issue site on Grid with UBaie=3D52.1 V   The TX Armand =
Nguetsa(699949553) from Huawei is informed . Repetitif issue","Delor Telezi=
ng","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue site on Grid with UBaie=3D52.1 V  The TX Arm=
and Nguetsa(699949553) from Huawei is informed . Repetitif issue
","landry.etame@ihstowers.com","131","22-07-2024 22:28:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0002670850","A=
wae Ewonkan","","22-07-2024 22:26:10","22-07-2024 22:03:02","22-07-2024 23:=
26:26","Site went down because the rectifier dysfunction on site // He rese=
t the rectifier","Albran Byorel","Equipment Repair","Passive","Rectifier","=
Rectifier Module","Site went down because the rectifier dysfunction on site=
 // He reset the rectifier","landry.etame@ihstowers.com","1390","22-07-2024=
 22:26:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_228","IHS_YND_409","NOCINC0002670651","E=
vodoula OCM","","22-07-2024 21:53:46","22-07-2024 21:49:32","22-07-2024 21:=
54:29","Active//No power issue on site,site on Grid with Ubaie=3D54 V,Moham=
adou of huawei is informed  Site up at 09:54 PM","TIENTCHEU NZETCHIEU GAEL"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active//No power issue on site,site on Grid with Ubaie=3D54 V,=
Mohamadou of huawei is informed  Site up at 09:54 PM","emmanuel.ghani@ihsto=
wers.com","255","22-07-2024 21:53:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0002670549","C=
omplexe-BEAC","","22-07-2024 21:28:45","22-07-2024 20:11:40","22-07-2024 22=
:45:37","Site went down due to dysjunction of CB OCM( C63A ) in PWC due to =
increase load in site  // He reamed the CB (Site Swapped by ZTE)","Albran B=
yorel","Equipment Repair","Passive","Control Panel","Power Cabinet - Circui=
t Breaker Issue","Site went down due to dysjunction of CB OCM( C63A ) in PW=
C due to increase load in site  // He reamed the CB (Site Swapped by ZTE)",=
"emmanuel.ghani@ihstowers.com","4626","22-07-2024 21:28:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_590","IHS_YND_295","NOCINC0002670518","N=
GONA","","22-07-2024 21:18:06","22-07-2024 21:11:59","22-07-2024 22:02:02",=
"Grid outage,gen started and  stopped with alarm high temp//he added water =
in radiator and started Gen ","Mba Lazare Herve","Equipment Repair","Passiv=
e","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Grid outage,=
gen started and  stopped with alarm high temp//he added water in radiator a=
nd started Gen ","emmanuel.ghani@ihstowers.com","368","22-07-2024 21:18:06"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002670487","Lad=
a I Yde","","22-07-2024 21:10:10","22-07-2024 21:09:04","22-07-2024 22:11:3=
1","Active//No power issue on site,site on GEN with Ubaie=3D51,1V  The Team=
  Arouna // from OMNIACOM is working on site","Mba Lazare Herve","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site,site on GEN with Ubaie=3D51,1V  The Team  =
Arouna // from OMNIACOM is working on site","joelle.ekessi@ihstowers.com","=
67","22-07-2024 21:10:10","Sagemcom CMR"
"Closed Complete","Site Down","T1570","IHS_YND_140","NOCINC0002670291","BIS=
CUITERIE","","22-07-2024 20:45:57","22-07-2024 20:41:47","22-07-2024 20:59:=
40","Grid outage, site went down before Gen start due to poor battery backu=
p // Gen started automatically","Paul BIBOUM","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before Gen start due to poor battery backup // Gen started automatically","=
joelle.ekessi@ihstowers.com","250","22-07-2024 20:45:57","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0002670250","Essomba"=
,"","22-07-2024 20:34:40","22-07-2024 20:25:55","22-07-2024 20:32:00","Casc=
aded Incident from TTO2481860","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due to poor battery backup//Gen automatically started","=
system","525","22-07-2024 20:34:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0002670249","Bitoto",=
"","22-07-2024 20:34:40","22-07-2024 20:25:55","22-07-2024 20:32:00","Casca=
ded Incident from TTO2481860","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n failed to start due to poor battery backup//Gen automatically started","s=
ystem","525","22-07-2024 20:34:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0002670251","Biteng-M=
aetur","","22-07-2024 20:34:40","22-07-2024 20:25:55","22-07-2024 20:32:00"=
,"Cascaded Incident from TTO2481860","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen failed to start due to poor battery backup//Gen automatically star=
ted","system","525","22-07-2024 20:34:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002670238","B=
iteng","IHS_YND_292, IHS_YND_179, IHS_YND_249","22-07-2024 20:30:00","22-07=
-2024 20:25:55","22-07-2024 20:32:00","Grid outage site went down because G=
en failed to start due to poor battery backup//Gen automatically started","=
Mba Lazare Herve","Equipment Repair","Passive","Control Panel","Power Cabin=
et - Battery Low","Grid outage site went down because Gen failed to start d=
ue to poor battery backup//Gen automatically started","emmanuel.ghani@ihsto=
wers.com","246","22-07-2024 20:30:00","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002670232","Nko=
l-Mbanda","","22-07-2024 20:27:00","22-07-2024 20:25:56","22-07-2024 20:35:=
35","site went down due to insufficient of rectifier on site causing by inc=
rease load in site )/ (Added 02 rectifiers ongoing), (Site Swapped by ZTE)	=
 ","MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Modu=
le","site went down due to insufficient of rectifier on site causing by inc=
rease load in site )/ (Added 02 rectifiers ongoing), (Site Swapped by ZTE)	=
 ","joelle.ekessi@ihstowers.com","65","22-07-2024 20:27:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0002670224","A=
WAE OCM","","22-07-2024 20:25:11","22-07-2024 20:18:05","22-07-2024 21:18:0=
5","","Mba Lazare Herve","Customer Equipment Failure","Active","Active Equi=
pment Failure","BTS/TX Fault Alarm","ACTIVE No power issue site on Grid U=
=3D54,6V   tx fme lionel /655184876 and RM from huawei  are unreachable Dys=
junction at OCM BTS","emmanuel.ghani@ihstowers.com","428","22-07-2024 20:25=
:11","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002670093","Jou=
vence 2000","","22-07-2024 20:07:41","22-07-2024 20:01:37","22-07-2024 21:2=
5:20","grid outage ,site went due to grid contactor didn't not excicted,poo=
r battery backup//he excited the grid contactor","Delor Telezing","Equipmen=
t Repair","Passive","Control Panel","ATS-AMF Issue","grid outage ,site went=
 due to grid contactor didn't not excicted,poor battery backup//he excited =
the grid contactor","joelle.ekessi@ihstowers.com","365","22-07-2024 20:07:4=
1","Sagemcom CMR"
"Closed Complete","Site Down","T1570","IHS_YND_140","NOCINC0002670057","BIS=
CUITERIE","","22-07-2024 20:00:26","22-07-2024 19:58:17","22-07-2024 20:16:=
33","Grid outage, site went down before Gen start due to poor battery backu=
p // Gen started automatically","Paul BIBOUM","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before Gen start due to poor battery backup // Gen started automatically","=
joelle.ekessi@ihstowers.com","130","22-07-2024 20:00:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0002669673","N=
kolso","","22-07-2024 18:42:47","22-07-2024 18:39:32","22-07-2024 19:40:33"=
,"Active//No power issue on site,site on Grid with Ubaie=3D53,8   V (Site S=
wapped by ZTE) The Tx  Mouhamadou (691144435) from Huawei is informed,","TI=
ENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equip=
ment Failure","BTS/TX Fault Alarm","Active//No power issue on site,site on =
Grid with Ubaie=3D53,8   V (Site Swapped by ZTE) The Tx  Mouhamadou (691144=
435) from Huawei is informed,","emmanuel.ghani@ihstowers.com","198","22-07-=
2024 18:42:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0002669659","E=
toudi 2","","22-07-2024 18:38:35","22-07-2024 18:16:30","22-07-2024 19:55:2=
5","Active//No power issue on site,site on Grid with Ubaie=3D53,6  V The TX=
  Armand Ngetsa(699949553) from Huawei is informed","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site,site on Grid with Ubaie=3D53,6  V The=
 TX  Armand Ngetsa(699949553) from Huawei is informed.","emmanuel.ghani@ihs=
towers.com","1326","22-07-2024 18:38:35","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0002669642","Bitoto",=
"","22-07-2024 18:34:10","22-07-2024 18:30:25","22-07-2024 18:34:13","Casca=
ded Incident from TTO2481156","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid outage site went down because Ge=
n failed to start due to poor battery backup//Gen automatically started
 ","system","225","22-07-2024 18:34:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0002669643","AWAE OCM=
","","22-07-2024 18:34:10","22-07-2024 18:30:25","22-07-2024 18:34:13","Cas=
caded Incident from TTO2481156","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage site went down because =
Gen failed to start due to poor battery backup//Gen automatically started
 ","system","225","22-07-2024 18:34:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0002669644","Essomba"=
,"","22-07-2024 18:34:10","22-07-2024 18:30:25","22-07-2024 18:34:13","Casc=
aded Incident from TTO2481156","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage site went down because G=
en failed to start due to poor battery backup//Gen automatically started
 ","system","225","22-07-2024 18:34:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0002669645","Biteng-M=
aetur","","22-07-2024 18:34:10","22-07-2024 18:30:25","22-07-2024 18:34:13"=
,"Cascaded Incident from TTO2481156","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage site went down bec=
ause Gen failed to start due to poor battery backup//Gen automatically star=
ted
 ","system","225","22-07-2024 18:34:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002669633","B=
iteng","IHS_YND_292, IHS_YND_173, IHS_YND_179, IHS_YND_249","22-07-2024 18:=
31:36","22-07-2024 18:30:25","22-07-2024 18:35:38","Grid outage site went d=
own because Gen failed to start due to poor battery backup//Gen automatical=
ly started  ","Mba Lazare Herve","Equipment Repair","Passive","Control Pane=
l","Power Cabinet - Battery Low","Grid outage site went down because Gen fa=
iled to start due to poor battery backup//Gen automatically started
 ","emmanuel.ghani@ihstowers.com","72","22-07-2024 18:31:36","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002669626","NKO=
MEKUI OCM","","22-07-2024 18:30:24","22-07-2024 18:28:19","22-07-2024 18:36=
:23","Grid outage site went down because Gen failed to start due to poor ba=
ttery backup//Gen automatically started","TIENTCHEU NZETCHIEU GAEL","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage site went down because Gen failed to start due to poor battery backup=
//Gen automatically started","joelle.ekessi@ihstowers.com","127","22-07-202=
4 18:30:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0002669315","O=
dza II","","22-07-2024 17:57:02","22-07-2024 17:34:55","22-07-2024 19:32:47=
","Site went down because CB  OCM (125A) at  DC BOX  disjoncted Causing by =
increase load in site //He reamed CB (Site Swapped By ZTE)","Albran Byorel"=
,"Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Brea=
ker Issue","Site went down because CB  OCM (125A) at  DC BOX  disjoncted Ca=
using by increase load in site //He reamed CB (Site Swapped By ZTE)","emman=
uel.ghani@ihstowers.com","1329","22-07-2024 17:57:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_150","NOCINC0002669300","Nkol-Mba=
nda","","22-07-2024 17:54:41","22-07-2024 17:30:35","22-07-2024 18:47:47","=
 site went down due to insufficient of rectifier on site   causing by  incr=
ease load in site )/ (Added  02 rectifiers ongoing), (Site Swapped by ZTE)"=
,"MINKA NICOLAS","Equipment Repair","Passive","Rectifier","Rectifier Module=
"," site went down due to insufficient of rectifier on site   causing by  i=
ncrease load in site )//  Site Stabilized  (Added  02 rectifiers ongoing), =
(Site Swapped by ZTE)","emmanuel.ghani@ihstowers.com","1447","22-07-2024 17=
:54:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_448","IHS_YND_138","NOCINC0002667976","N=
komkana 2","","22-07-2024 15:10:56","22-07-2024 15:08:18","22-07-2024 20:40=
:48","ACTIVE /No power issue U=3D54,6 V site on Grid  The Team Straumann //=
 from ZTE is working on site ","Mboua Thierry","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE /No power=
 issue U=3D54,6 V site on Grid  The Team Straumann // from ZTE is working o=
n site ","emmanuel.ghani@ihstowers.com","158","22-07-2024 15:10:56","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_104","IHS_YND_244","NOCINC0002667700","A=
battoir","","22-07-2024 14:39:39","22-07-2024 14:36:35","22-07-2024 15:00:3=
9","ACTIVE No power issue on site, site on Grid with Ubaie=3D51,9V Tx fme A=
rmand Ngeutsa from Huawei is Informed ","Fabrice Pouakam","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIV=
E No power issue on site, site on Grid with Ubaie=3D51,9V Tx fme Armand Nge=
utsa from Huawei is Informed ","emmanuel.ghani@ihstowers.com","184","22-07-=
2024 14:39:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0002667638","M=
volye-New","","22-07-2024 14:27:49","22-07-2024 09:38:40","22-07-2024 14:11=
:46","Grid outage // Grid power return(site Swapped by ZTE)","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage // Gri=
d power return(site Swapped by ZTE)","ange.kongo@ihstowers.com","17350","22=
-07-2024 14:27:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0002667631","O=
dza II","","22-07-2024 14:26:19","22-07-2024 11:40:02","22-07-2024 16:15:03=
","Active//No power issue on site ,site on Grid Ubaie=3D52,1 V The TX  Lion=
el steve //655184876 from Huawei is informed.(Site Swapped By ZTE)","Albran=
 Byorel","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid Ubaie=3D5=
2,1 V The TX  Lionel steve //655184876 from Huawei is informed.(Site Swappe=
d By ZTE)","ange.kongo@ihstowers.com","9981","22-07-2024 14:26:19","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002667384","M=
vog-Manga","","22-07-2024 13:46:09","22-07-2024 13:42:01","22-07-2024 14:55=
:16","Active//No power issue on site,site on Grid with Ubaie=3D53,8 V The T=
eam  franck//699670325 from ZTE is working on site","Albran Byorel","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site,site on Grid with Ubaie=3D53,8 V The Te=
am  franck//699670325 from ZTE is working on site","ange.kongo@ihstowers.co=
m","250","22-07-2024 13:46:09","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002667238","M=
arche Odza","","22-07-2024 13:25:23","22-07-2024 13:19:11","22-07-2024 13:3=
0:19","Active//No power issue on site,site on Grid with Ubaie=3D54,4 V  TX =
FME Lionel steve/655184876 from Huawei is informed repetitif issue","Albran=
 Byorel","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active//No power issue on site,site on Grid with Ubaie=
=3D54,4 V  TX FME Lionel steve/655184876 from Huawei is informed repetitif =
issue","ange.kongo@ihstowers.com","373","22-07-2024 13:25:23","Sagemcom CMR=
"
"Closed Complete","Site Down","T3151","IHS_YND_192","NOCINC0002667222","Dra=
gage","","22-07-2024 13:20:05","22-07-2024 13:17:00","22-07-2024 16:20:02",=
"Active//no power issue on site, site on Grid   Team Omniacom//692090021  i=
s working on site","Mboua Thierry","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","Active//no power issue on si=
te, site on Grid   Team Omniacom//692090021  is working on site","ludivine.=
ngamaleu@ihstowers.com","185","22-07-2024 13:20:05","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002667166","Lad=
a I Yde","","22-07-2024 13:15:57","22-07-2024 13:13:44","22-07-2024 13:20:4=
2","No power issue on site,site on GEN with Ubaie=3D51,1V  The Team  Arouna=
 // from OMNIACOM is working on site","Mba Lazare Herve","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No pow=
er issue on site,site on GEN with Ubaie=3D51,1V  The Team  Arouna // from O=
MNIACOM is working on site","ludivine.ngamaleu@ihstowers.com","134","22-07-=
2024 13:15:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002667165","N=
kolo II New","","22-07-2024 13:15:56","22-07-2024 13:06:51","23-07-2024 06:=
30:36","ACTIVE /No power issue U=3D52,4  V site on Gen Tx FME Lionel steeve=
 //655184876 is informed. ","Mba Lazare Herve","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE /No power=
 issue U=3D52,4  V site on Gen Tx FME Lionel steeve //655184876 is informed=
. ","ange.kongo@ihstowers.com","546","22-07-2024 13:15:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002666959","E=
mana","","22-07-2024 12:47:48","22-07-2024 12:30:42","22-07-2024 12:35:01",=
"","","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","no power issue on site ubaie=3D54v site on grid , Symphor=
ien is informed","ange.kongo@ihstowers.com","1027","22-07-2024 12:47:48","S=
agemcom CMR"
"Closed Complete","Site Down","T1559","IHS_YND_709","NOCINC0002666791","Nko=
lo II New","","22-07-2024 12:34:21","22-07-2024 05:24:10","22-07-2024 06:24=
:44","Grid outage site went down because Gen started and stopped with alarm=
 Gen overload // He reduice the rectifier site on Gen","Mba Lazare Herve","=
Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Grid outage site =
went down because Gen started and stopped with alarm Gen overload // He red=
uice the rectifier site on Gen","alwine.fambou@ihstowers.com","25812","22-0=
7-2024 12:34:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_425","IHS_YND_141","NOCINC0002666567","N=
ew-Marche-Melen","","22-07-2024 12:05:19","22-07-2024 12:00:14","22-07-2024=
 13:53:33","Active//No power issue on site,site on Grid with Ubaie=3D54 V T=
he Team   Aristide // 690994011 from ZTE is working on site","Paul BIBOUM",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active//No power issue on site,site on Grid with Ubaie=3D54 V T=
he Team   Aristide // 690994011 from ZTE is working on site","ange.kongo@ih=
stowers.com","307","22-07-2024 12:05:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002666560","M=
asque","","22-07-2024 12:03:21","22-07-2024 11:59:12","22-07-2024 13:31:52"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","ang=
e.kongo@ihstowers.com","251","22-07-2024 12:03:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_099","IHS_YND_168","NOCINC0002665989","O=
dza","","22-07-2024 10:24:38","22-07-2024 10:18:31","22-07-2024 11:35:37","=
Active//No power issue on site,site on Grid with Ubaie=3D54,7  V  The Team =
  Christophe //237 690266001 from ZTE is working on site","Albran Byorel","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site,site on Grid with Ubaie=3D54,7  V=
  The Team   Christophe //237 690266001 from ZTE is working on site","ange.=
kongo@ihstowers.com","370","22-07-2024 10:24:38","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002665965","Ess=
os Marche","","22-07-2024 10:20:31","22-07-2024 10:14:28","22-07-2024 13:37=
:16","Active//No power issue on site,site on Grid with Ubaie=3D54.2  V The =
TX  Armand Ngetsa(699949553) from Huawei is informed.","Delor Telezing","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site,site on Grid with Ubaie=3D54.2  V T=
he TX  Armand Ngetsa(699949553) from Huawei is informed.","ludivine.ngamale=
u@ihstowers.com","366","22-07-2024 10:20:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0002665878","N=
kolfon Cimencam","","22-07-2024 10:09:14","22-07-2024 10:03:58","22-07-2024=
 12:55:10","site went down because Gen failed to started due to  Gen fuse c=
ut // He make the bridge and manually started the Gen","Hyemafo Gildas","Eq=
uipment Repair","Passive","ACDG Gen","ACDG - Control Panel","site went down=
 because Gen failed to started due to  Gen fuse cut // He make the bridge a=
nd manually started the Gen","ange.kongo@ihstowers.com","318","22-07-2024 1=
0:09:14","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002665738","NKO=
MEKUI OCM","","22-07-2024 09:45:25","22-07-2024 09:40:38","22-07-2024 09:48=
:08","Grid outage site went down because Gen failed to start due to poor ba=
ttery backup//Gen automatically started","TIENTCHEU NZETCHIEU GAEL","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage site went down because Gen failed to start due to poor battery backup=
//Gen automatically started","ludivine.ngamaleu@ihstowers.com","287","22-07=
-2024 09:45:25","Sagemcom CMR"
"Closed Complete","Warning","CTR_211","IHS_YND_248","NOCINC0002665611","Bit=
eng","","22-07-2024 09:22:52","","","Site on battery","Mba Lazare Herve","W=
arning","Warning","POWER","Warning - AC Phase 1 Current Low","Alarm Cleared=
","alwine.fambou@ihstowers.com","3","22-07-2024 09:22:52","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_574","NOCINC0002665588","Crf-Mban=
kolo-IHS","","22-07-2024 09:17:10","22-07-2024 08:55:15","22-07-2024 09:39:=
46","Cascaded Incident from TTO2476746","Mboua Thierry","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,gen ran until fuel=
 shortage//Refueling done","system","1315","22-07-2024 09:17:10","Sagemcom =
CMR"
"Closed Complete","Site Down","T0652","IHS_YND_222","NOCINC0002665567","Jea=
n Vespa","IHS_YND_574","22-07-2024 09:16:29","22-07-2024 08:55:15","22-07-2=
024 09:39:46","Grid outage,gen ran until fuel shortage//Refueling done","Mb=
oua Thierry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,=
gen ran until fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.c=
om","1275","22-07-2024 09:16:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_544","NOCINC0002665474","Jean Ves=
pa 2","","22-07-2024 08:57:50","22-07-2024 08:52:33","22-07-2024 09:20:47",=
"Cascaded Incident from TTO2476634","Mboua Thierry","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage// Grid power return","=
system","317","22-07-2024 08:57:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_088","IHS_YND_221","NOCINC0002665467","J=
-Vespa","IHS_YND_544","22-07-2024 08:56:39","22-07-2024 08:52:33","22-07-20=
24 09:20:47","Grid outage// Grid power return","Mboua Thierry","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage// Grid =
power return","ange.kongo@ihstowers.com","248","22-07-2024 08:56:39","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0002665326","M=
vog-Betsi","","22-07-2024 08:26:00","22-07-2024 08:23:52","22-07-2024 10:29=
:41","Active//No power issue on site,site on Grid with Ubaie=3D54,7  V  The=
 Team   TSOGNE Rodolpho //237 6 56 35 38 62 from ZTE is working on site","H=
yemafo Gildas","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active//No power issue on site,site on Grid with=
 Ubaie=3D54,7  V  The Team   TSOGNE Rodolpho //237 6 56 35 38 62 from ZTE i=
s working on site","ange.kongo@ihstowers.com","129","22-07-2024 08:26:00","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002665302","E=
TOUDI CHAPELLE","","22-07-2024 08:16:53","22-07-2024 08:16:47","22-07-2024 =
09:51:58","ACTIVE No power issue Ubaie=3D51.2V site on Grid Armand Nguetsa =
(699949553)from Huawei is informed, repetitif issue","Delor Telezing","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","ACTIVE No power issue Ubaie=3D51.2V site on Grid Armand Nguetsa (699=
949553)from Huawei is informed, repetitif issue","ange.kongo@ihstowers.com"=
,"9","22-07-2024 08:16:53","Sagemcom CMR"
"Closed Complete","Site Down","T1287","IHS_YND_223","NOCINC0002665266","Feb=
e Village","","22-07-2024 08:10:21","22-07-2024 08:06:15","22-07-2024 10:06=
:25","Grid outage,gen ran until fuel shortage//Refueling done","Mboua Thier=
ry","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outage,gen ran u=
ntil fuel shortage//Refueling done","ludivine.ngamaleu@ihstowers.com","248"=
,"22-07-2024 08:10:21","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0002665229","Nko=
lbisson usines des eaux 2","","22-07-2024 08:01:49","22-07-2024 07:58:43","=
22-07-2024 08:02:36","Grid fluctuation site went down because Gen failled t=
o started due to Grid bad voltage // He bypass the Grid and site on Gen","T=
IENTCHEU NZETCHIEU GAEL","Grid Supply","Passive","Grid","National Grid - Ph=
ase Controller Faulty","Grid fluctuation site went down because Gen failled=
 to started due to Grid bad voltage // He bypass the Grid and site on Gen",=
"ludivine.ngamaleu@ihstowers.com","187","22-07-2024 08:01:49","Sagemcom CMR=
"
"Closed Complete","Site Down","","IHS_YND_543","NOCINC0002665090","Entree C=
ite Verte","","22-07-2024 07:39:50","22-07-2024 07:30:29","22-07-2024 08:56=
:32","Cascaded Incident from TTO2476253","Paul BIBOUM","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage// Grid power return=
","system","561","22-07-2024 07:39:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_200","NOCINC0002665089","Nkomkana=
","","22-07-2024 07:39:50","22-07-2024 07:30:29","22-07-2024 08:56:32","Cas=
caded Incident from TTO2476253","","Cascade Outage","Passive","Cascade Pass=
ive","Cascade Passive","Grid outage// Grid power return","system","561","22=
-07-2024 07:39:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_414","IHS_YND_202","NOCINC0002665084","C=
ite-Verte","IHS_YND_200, IHS_YND_543","22-07-2024 07:38:36","22-07-2024 07:=
30:29","22-07-2024 08:56:32","Grid outage// Grid power return","","Grid Sup=
ply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage// Gr=
id power return","ange.kongo@ihstowers.com","489","22-07-2024 07:38:36","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_382","IHS_YND_265","NOCINC0002665024","M=
essa-Carriere OCM","","22-07-2024 07:22:23","22-07-2024 07:18:14","22-07-20=
24 08:11:35","Grid outage.no space to deploy mobile gen //Grid return","","=
Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid out=
age.no space to deploy mobile gen //Grid return","ange.kongo@ihstowers.com"=
,"250","22-07-2024 07:22:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002664838","M=
essassi 2","","22-07-2024 06:39:02","22-07-2024 06:34:53","22-07-2024 09:40=
:38","fme wil be manage after Manguier dispensaire","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","No power issue on site  ubaie=3D54v symphorien is informed","ange.ko=
ngo@ihstowers.com","251","22-07-2024 06:39:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0002664834","E=
toudi 2","","22-07-2024 06:36:58","22-07-2024 06:33:52","22-07-2024 07:39:1=
1","Active//No power issue on site,site on Grid with Ubaie=3D53,6  V The TX=
  Armand Ngetsa(699949553) from Huawei is informed.site up at 06:35 AM","Fa=
brice Pouakam","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active//No power issue on site,site on Grid with=
 Ubaie=3D53,6  V The TX  Armand Ngetsa(699949553) from Huawei is informed.s=
ite up at 06:35 AM","ange.kongo@ihstowers.com","187","22-07-2024 06:36:58",=
"Sagemcom CMR"
"Closed Complete","Site Down","T1549","IHS_YND_295","NOCINC0002664715","NGO=
NA","","22-07-2024 06:01:47","22-07-2024 05:51:40","22-07-2024 06:40:26","G=
rid outage.gen faled to start due alarm ""low oil pressure"" //we add oil a=
nd gen manually started ","Mba Lazare Herve","Equipment Repair","Passive","=
ACDG Gen","ACDG - Low Oil Pressure","Grid outage.gen faled to start due ala=
rm ""low oil pressure"" //we add oil and gen manually started ","alexandre.=
kamal@ihstowers.com","917","22-07-2024 06:01:47","Sagemcom CMR"
"Closed Complete","Site Down","T0457","IHS_YND_246","NOCINC0002664686","Ema=
na","","22-07-2024 05:53:33","22-07-2024 05:44:26","22-07-2024 07:08:55","G=
rid outage ,site went down because Gen stop with alarm low oil pressure // =
He reset the gen card and manually started the Gen","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outage ,=
site went down because Gen stop with alarm low oil pressure // He reset the=
 gen card and manually started the Gen","alexandre.kamal@ihstowers.com","54=
9","22-07-2024 05:53:33","Sagemcom CMR"
"Closed Complete","Site Down","T1105","IHS_YND_266","NOCINC0002664673","Mim=
boman4","","22-07-2024 05:51:55","22-07-2024 05:24:23","22-07-2024 05:27:37=
","No power issue  site on grid with U=3D54v//site up at 06:24 AM  Eloundou=
 from Huawei is informed","Mba Lazare Herve","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue  si=
te on grid with U=3D54v//site up at 06:24 AM  Eloundou from Huawei is infor=
med","alexandre.kamal@ihstowers.com","1653","22-07-2024 05:51:55","Sagemcom=
 CMR"
"Closed Complete","Site Down","T1571","IHS_YND_535","NOCINC0002664619","Awa=
e Ewonkan","","22-07-2024 05:37:41","21-07-2024 20:15:56","21-07-2024 20:36=
:53","site went down due to disjunction Cb(63A) in DC box// He remead cb(63=
A)","Albran Byorel","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Circuit Breaker Issue","site went down due to disjunction Cb(63A) in=
 DC box// He remead cb(63A)","kamga.virgile@ihstowers.com","39198","22-07-2=
024 05:37:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0002664492","T=
singa","","22-07-2024 04:48:03","22-07-2024 04:35:53","22-07-2024 05:00:18"=
,"site went down due to disfunctionning of controller// voltage stabilized =
( controller to be replaced)","Mboua Thierry","Equipment Repair","Passive",=
"Hybrid","Hybrid Module","site went down due to disfunctionning of controll=
er// voltage stabilized ( controller to be replaced)","kamga.virgile@ihstow=
ers.com","731","22-07-2024 04:48:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002664058","E=
mana","","22-07-2024 02:59:32","22-07-2024 02:34:20","22-07-2024 07:44:10",=
"Access issue during the night due to  Landlord, Grid outage// Grid power r=
eturn","","Access Denial","Lease Or Legal","Landlord Related Issues","Acces=
s Issue - Land Lord","Access issue during the night due to  Landlord, Grid =
outage// Grid power return","kamga.virgile@ihstowers.com","1513","22-07-202=
4 02:59:32","Sagemcom CMR"
"Closed Complete","Site Down","T1415","IHS_YND_680","NOCINC0002663622","MIM=
BOMAN LIBERTE","","22-07-2024 00:42:12","21-07-2024 23:22:59","22-07-2024 0=
0:56:35","grid outage, site went down because Gen started and stopped due t=
o alarm under Voltage//he reset Gen card and Started Gen","Mba Lazare Herve=
","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outa=
ge, site went down because Gen started and stopped due to alarm under Volta=
ge//he reset Gen card and Started Gen","alexandre.kamal@ihstowers.com","475=
4","22-07-2024 00:42:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002663462","B=
iteng","","21-07-2024 23:30:36","21-07-2024 23:10:29","21-07-2024 23:15:21"=
,"Grid outage site went down because Gen failed to start due to poor batter=
y backup//Gen automatically started","Mba Lazare Herve","Equipment Repair",=
"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site w=
ent down because Gen failed to start due to poor battery backup//Gen automa=
tically started","kamga.virgile@ihstowers.com","1208","21-07-2024 23:30:36"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002663424","M=
essassi 2","","21-07-2024 23:23:13","21-07-2024 22:53:00","21-07-2024 23:03=
:43","ACTIVE no power issue on site Ubaie=3D54.5V site on Grid ,TX FME  Syn=
phorien (691316854) from Huawei is informed. Notice that Disjunction in BTS=
 Ocm. (Site already swapped by ZTE )","Fabrice Pouakam","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE =
no power issue on site Ubaie=3D54.5V site on Grid ,TX FME  Synphorien (6913=
16854) from Huawei is informed. Notice that Disjunction in BTS Ocm. (Site a=
lready swapped by ZTE )","kamga.virgile@ihstowers.com","1814","21-07-2024 2=
3:23:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_467","IHS_YND_281","NOCINC0002663143","O=
dza II","","21-07-2024 22:17:15","21-07-2024 20:04:07","22-07-2024 07:51:48=
","No power issue site on grid with U=3DUbaie=3D54,3V, The Tx Leonel Steve/=
/655184876 from Huawei is informed(Site already swapped by ZTE ),","Albran =
Byorel","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","No power issue site on grid with U=3DUbaie=3D54,3V, The=
 Tx Leonel Steve//655184876 from Huawei is informed(Site already swapped by=
 ZTE ),","landry.etame@ihstowers.com","7991","21-07-2024 22:17:15","Sagemco=
m CMR"
"Closed Complete","Site Down","T3233","IHS_YND_768","NOCINC0002663026","ELO=
UMDEM CARRIERE 2","","21-07-2024 22:06:30","21-07-2024 21:57:21","21-07-202=
4 23:00:24","site went down because 01/02 Rectifier dysfonction// He reset =
the rectifier ","Fanda Brice","Equipment Repair","Passive","Rectifier","Rec=
tifier Module","site went down because 01/02 Rectifier dysfonction// He res=
et the rectifier ","denis.mballa@ihstowers.com","551","21-07-2024 22:06:30"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_276","NOCINC0002662620","Ekombiti=
e","","21-07-2024 20:50:10","21-07-2024 20:44:07","21-07-2024 21:33:25","Ca=
scaded Incident from TTO2473572","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,gen ran until fuel shor=
tage//Refueling done","system","363","21-07-2024 20:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_681","NOCINC0002662621","NKOLMEKO=
NG YDE","","21-07-2024 20:50:10","21-07-2024 20:44:07","21-07-2024 21:33:25=
","Cascaded Incident from TTO2473572","Fabrice Pouakam","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage,gen ran until fuel=
 shortage//Refueling done","system","363","21-07-2024 20:50:10","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_303","NOCINC0002662625","Nyom OCM=
","","21-07-2024 20:50:10","21-07-2024 20:44:07","21-07-2024 21:33:25","Cas=
caded Incident from TTO2473572","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,gen ran until fuel short=
age//Refueling done","system","363","21-07-2024 20:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_304","NOCINC0002662626","Nkolondo=
m","","21-07-2024 20:50:10","21-07-2024 20:44:07","21-07-2024 21:33:25","Ca=
scaded Incident from TTO2473572","Fabrice Pouakam","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage,gen ran until fuel shor=
tage//Refueling done","system","363","21-07-2024 20:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0002662624","Nkozoa",=
"","21-07-2024 20:50:10","21-07-2024 20:44:07","21-07-2024 21:33:25","Casca=
ded Incident from TTO2473572","Fabrice Pouakam","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage,gen ran until fuel shortag=
e//Refueling done","system","363","21-07-2024 20:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_297","NOCINC0002662623","Messassi=
","","21-07-2024 20:50:10","21-07-2024 20:44:07","21-07-2024 21:33:25","Cas=
caded Incident from TTO2473572","Fabrice Pouakam","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid outage,gen ran until fuel short=
age//Refueling done","system","363","21-07-2024 20:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_300","NOCINC0002662622","Olembe-T=
erminus","","21-07-2024 20:50:10","21-07-2024 20:44:07","21-07-2024 21:33:2=
5","Cascaded Incident from TTO2473572","Fabrice Pouakam","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage,gen ran until fue=
l shortage//Refueling done","system","363","21-07-2024 20:50:10","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_080","IHS_YND_298","NOCINC0002662611","O=
lembe","IHS_YND_276, IHS_YND_681, IHS_YND_300, IHS_YND_297, IHS_YND_306, IH=
S_YND_303, IHS_YND_304","21-07-2024 20:48:12","21-07-2024 20:44:07","21-07-=
2024 21:33:25","Grid outage,gen ran until fuel shortage//Refueling done","F=
abrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid outa=
ge,gen ran until fuel shortage//Refueling done","landry.etame@ihstowers.com=
","246","21-07-2024 20:48:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_549","IHS_YND_283","NOCINC0002662557","A=
bome","","21-07-2024 20:40:01","21-07-2024 19:49:49","22-07-2024 00:15:07",=
"grid outage and gen started, site went down due to insuffisance of rectifi=
er // He added rectifier, grid retun, Lionel adjed(655184876) from Huawei i=
s informed, (Site already swapped by ZTE )","MINKA NICOLAS","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","grid outage an=
d gen started, site went down due to insuffisance of rectifier // He added =
rectifier, grid retun, Lionel adjed(655184876) from Huawei is informed, (Si=
te already swapped by ZTE )","landry.etame@ihstowers.com","3013","21-07-202=
4 20:40:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_060","NOCINC0002662543","Ngoa Eke=
lle","","21-07-2024 20:35:30","21-07-2024 20:18:12","21-07-2024 20:26:29","=
Cascaded Incident from TTO2473472","Paul BIBOUM","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive"," Grid outage site went down before Ge=
n started due to poor battery back up//Gen started automatically","system",=
"1038","21-07-2024 20:35:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_071","NOCINC0002662542","Scalom",=
"","21-07-2024 20:35:30","21-07-2024 20:18:12","21-07-2024 20:26:29","Casca=
ded Incident from TTO2473472","Paul BIBOUM","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive"," Grid outage site went down before Gen sta=
rted due to poor battery back up//Gen started automatically","system","1038=
","21-07-2024 20:35:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_562","NOCINC0002662544","Accacia =
New","","21-07-2024 20:35:30","21-07-2024 20:18:12","21-07-2024 20:26:29","=
Cascaded Incident from TTO2473472","","Cascade Outage","Passive","Cascade P=
assive","Cascade Passive"," Grid outage site went down before Gen started d=
ue to poor battery back up//Gen started automatically","system","1038","21-=
07-2024 20:35:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_101","NOCINC0002662545","Nsimeyon=
g Shell","","21-07-2024 20:35:30","21-07-2024 20:18:12","21-07-2024 20:26:2=
9","Cascaded Incident from TTO2473472","MINKA NICOLAS","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive"," Grid outage site went down bef=
ore Gen started due to poor battery back up//Gen started automatically","sy=
stem","1038","21-07-2024 20:35:30","Sagemcom CMR"
"Closed Complete","Site Down","T0188","IHS_YND_727","NOCINC0002662515","Nlo=
ng Mvolye New","IHS_YND_071, IHS_YND_060, IHS_YND_562, IHS_YND_101","21-07-=
2024 20:30:59","21-07-2024 20:18:12","21-07-2024 20:26:29"," Grid outage si=
te went down before Gen started due to poor battery back up//Gen started au=
tomatically","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low"," Grid outage site went down before Gen started =
due to poor battery back up//Gen started automatically","denis.mballa@ihsto=
wers.com","768","21-07-2024 20:30:59","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_269","NOCINC0002662502","Mvog-Eba=
nda","","21-07-2024 20:27:30","21-07-2024 20:08:43","21-07-2024 20:35:14","=
Cascaded Incident from TTO2473457","Siligap Boris","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage, site wen down because =
gen failed to start due to poor battery backup // Grid return","system","11=
27","21-07-2024 20:27:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_263","IHS_YND_217","NOCINC0002662499","A=
bom","IHS_YND_269","21-07-2024 20:26:54","21-07-2024 20:08:43","21-07-2024 =
20:35:14","Grid outage, site wen down because gen failed to start due to po=
or battery backup // Grid return","Siligap Boris","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen do=
wn because gen failed to start due to poor battery backup // Grid return","=
landry.etame@ihstowers.com","1093","21-07-2024 20:26:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002662481","C=
arington","","21-07-2024 20:22:28","21-07-2024 20:14:09","21-07-2024 20:24:=
56","grid outage//grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","grid outage//grid return","landry.etame@ihstower=
s.com","500","21-07-2024 20:22:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0002662443","M=
adison","","21-07-2024 20:18:06","21-07-2024 20:05:01","21-07-2024 22:47:36=
","  Grid outage, site went down before Gen start due to poor battery backu=
p // Grid power return , site remain down after power reset has done The TX=
   Armand Ngetsa(699949553) from Huawei is informed","MFOUAGUEGUE MATHIEU",=
"Equipment Repair","Passive","Control Panel","Power Cabinet - Battery Low",=
"  Grid outage, site went down before Gen start due to poor battery backup =
// Grid power return , site remain down after power reset has done The TX  =
 Armand Ngetsa(699949553) from Huawei is informed","landry.etame@ihstowers.=
com","786","21-07-2024 20:18:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_351","IHS_YND_734","NOCINC0002662442","M=
imboman Chateau","","21-07-2024 20:17:33","21-07-2024 20:07:28","21-07-2024=
 21:05:39","Grid outage no space to deploy Mobil Gen // Grid power return ,=
power issue resolved at 09:02 PM ,But site still Down  after Power reset do=
ne,The Tx  Lionel adjed(655184876) from Huawei is informed, (S","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no =
space to deploy Mobil Gen // Grid power return ,power issue resolved at 09:=
02 PM ,But site still Down  after Power reset done,The Tx  Lionel adjed(655=
184876) from Huawei is informed, (Site already swapped by ZTE )","landry.et=
ame@ihstowers.com","606","21-07-2024 20:17:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0002662430","T=
ongolo OCM","","21-07-2024 20:14:48","21-07-2024 20:04:42","21-07-2024 20:2=
3:09","Grid outage Site went down due to PWC Overload (13KVA ; 200A ) // Gr=
id return","Delor Telezing","Equipment Repair","Passive","Control Panel","P=
anel Distribution Board","Grid outage Site went down due to PWC Overload (1=
3KVA ; 200A ) // Grid return","landry.etame@ihstowers.com","607","21-07-202=
4 20:14:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0002662332","M=
volye-New","","21-07-2024 19:49:34","20-07-2024 00:43:59","20-07-2024 14:47=
:59","","","Access Denial","Lease Or Legal","Landlord Related Issues","Acce=
ss Issue - Land Lord","Access issue during the night due to landlord PWC ov=
erload caused by increased load on site//he added another PWC","kouoh.jean@=
ihstowers.com","155137","21-07-2024 19:49:34","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002662206","Mim=
boman3","","21-07-2024 19:19:04","21-07-2024 18:47:51","21-07-2024 19:15:36=
"," Grid outage, site went down before Gen start due to poor battery backup=
 // Grid power return","Mba Lazare Herve","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Battery Low"," Grid outage, site went down bef=
ore Gen start due to poor battery backup // Grid power return","kouoh.jean@=
ihstowers.com","1874","21-07-2024 19:19:04","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0002662201","MEHANDAN=
","","21-07-2024 19:17:40","21-07-2024 18:05:39","21-07-2024 23:46:27","Cas=
caded Incident from TTO2473119","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went  down due to disjuction Cb(6=
3A) in PWC due to load of the site increase//make the bridge with CB(100A),=
 site on grid","system","4321","21-07-2024 19:17:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002662194","O=
dza II OCM","IHS_YND_528","21-07-2024 19:16:46","21-07-2024 18:05:39","21-0=
7-2024 23:46:27","site went  down due to disjuction Cb(63A) in PWC due to l=
oad of the site increase//make the bridge with CB(100A), site on grid(Site =
already swapped by ZTE )","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","site went  down due to=
 disjuction Cb(63A) in PWC due to load of the site increase//make the bridg=
e with CB(100A), site on grid(Site already swapped by ZTE )","landry.etame@=
ihstowers.com","4268","21-07-2024 19:16:46","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002662181","Ess=
os Marche","","21-07-2024 19:11:34","21-07-2024 18:52:22","21-07-2024 19:18=
:30"," Grid outage, site went down before Gen start due to poor battery bac=
kup // Grid power return","Delor Telezing","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low"," Grid outage, site went down be=
fore Gen start due to poor battery backup // Grid power return","denis.mbal=
la@ihstowers.com","1153","21-07-2024 19:11:34","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002662166","Jou=
vence 2000","","21-07-2024 19:06:44","21-07-2024 18:46:31","21-07-2024 20:3=
8:26","grid outage ,site went due to grid contactor didn't not excicted,poo=
r battery backup//he excited the grid contactor","Delor Telezing","Equipmen=
t Repair","Passive","Control Panel","ATS-AMF Issue","grid outage ,site went=
 due to grid contactor didn't not excicted,poor battery backup//he excited =
the grid contactor","denis.mballa@ihstowers.com","1214","21-07-2024 19:06:4=
4","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002662112","M=
essassi 2","","21-07-2024 18:58:53","21-07-2024 18:52:39","21-07-2024 19:01=
:52","Grid outage site went down before Gen started due to poor battery bac=
k up //Grid return","Fabrice Pouakam","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage site went down before Ge=
n started due to poor battery back up //Grid return","landry.etame@ihstower=
s.com","375","21-07-2024 18:58:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0002662107","C=
rf Cornier","","21-07-2024 18:57:45","21-07-2024 18:52:39","22-07-2024 07:5=
0:29","No power issue on site U=3D50,2 V site on Gen The Tx FME Lionel// 69=
4693436of Huawei is informed. ","MINKA NICOLAS","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site U=3D50,2 V site on Gen The Tx FME Lionel// 694693436of Huawei is in=
formed.=20
","landry.etame@ihstowers.com","308","21-07-2024 18:57:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0002662104","C=
RH-Etoug-Ebe","","21-07-2024 18:54:15","21-07-2024 18:10:10","21-07-2024 19=
:40:57","ACTIVE no power issue  site  on Grid  Team Koffi /692041199 from Z=
TE is working on site","Hyemafo Gildas","Grid Supply","Passive","Grid","Nat=
ional Grid - Grid Outage Issue","ACTIVE no power issue  site  on Grid  Team=
 Koffi /692041199 from ZTE is working on site","landry.etame@ihstowers.com"=
,"2647","21-07-2024 18:54:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_446","IHS_YND_509","NOCINC0002661654","M=
ANGUIERS CHAPELLE","","21-07-2024 17:04:24","21-07-2024 16:56:18","21-07-20=
24 17:14:21","","Fabrice Pouakam","Grid Supply","Passive","Grid","National =
Grid - Phase Controller Faulty","Grid fluctuation sie went down because Gen=
 failed to start due to Grid bad voltage// He bypass the Grid and site on G=
en","landry.etame@ihstowers.com","488","21-07-2024 17:04:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002661600","M=
asque","","21-07-2024 16:48:13","21-07-2024 16:42:03","21-07-2024 17:26:06"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","lan=
dry.etame@ihstowers.com","373","21-07-2024 16:48:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0002661565","M=
ontee-Des-Soeurs","","21-07-2024 16:39:55","21-07-2024 14:25:44","22-07-202=
4 07:55:51","Active//No power issue on site,site on Grid with Ubaie=3D54,5 =
 V The Tx FME  Hosiah //674007438 of Huawei is informed.","Hyemafo Gildas",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active//No power issue on site,site on Grid with Ubaie=3D54,5  =
V The Tx FME  Hosiah //674007438 of Huawei is informed.","landry.etame@ihst=
owers.com","8053","21-07-2024 16:39:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002661537","MBALNGON=
G LYCEE","","21-07-2024 16:35:00","21-07-2024 12:04:03","21-07-2024 12:24:0=
3","Cascaded Incident from TTO2472290","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage site went down becaus=
e Gen failed to start due to poor battery backup//Gen automatically started=
","system","16257","21-07-2024 16:35:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002661536","ELOUMDEM=
 CARRIERE","","21-07-2024 16:35:00","21-07-2024 12:04:03","21-07-2024 12:24=
:03","Cascaded Incident from TTO2472290","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage site went down beca=
use Gen failed to start due to poor battery backup//Gen automatically start=
ed","system","16257","21-07-2024 16:35:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002661538","Afanoya"=
,"","21-07-2024 16:35:00","21-07-2024 12:04:03","21-07-2024 12:24:03","Casc=
aded Incident from TTO2472290","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 failed to start due to poor battery backup//Gen automatically started","sy=
stem","16257","21-07-2024 16:35:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0002661355","A=
hala","IHS_YND_767, IHS_YND_765, IHS_YND_313","21-07-2024 15:56:18","21-07-=
2024 12:04:03","21-07-2024 12:24:03","Grid outage site went down because Ge=
n failed to start due to poor battery backup//Gen automatically started","H=
yemafo Gildas","Equipment Repair","Passive","Control Panel","Power Cabinet =
- Battery Low","Grid outage site went down because Gen failed to start due =
to poor battery backup//Gen automatically started","landry.etame@ihstowers.=
com","16218","21-07-2024 15:56:18","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0002661255","Nko=
mkana","","21-07-2024 15:38:27","21-07-2024 15:29:14","21-07-2024 21:37:12"=
,"	Grid outage ,no space to deploy mobile gen//grid power return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid outage =
,no space to deploy mobile gen//grid power return","denis.mballa@ihstowers.=
com","555","21-07-2024 15:38:27","Sagemcom CMR"
"Closed Complete","Site Down","T1834","IHS_YND_132","NOCINC0002661189","Man=
guiers Dispensaire","","21-07-2024 15:25:52","21-07-2024 14:43:36","22-07-2=
024 07:40:18","access issue due to land load","Fabrice Pouakam","Access Den=
ial","Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord",=
"Access issue due to landlord// Grid fluctuation sie went down because Gen =
failed to start due to Grid bad voltage// He bypass the Grid and site on Ge=
n","denis.mballa@ihstowers.com","2538","21-07-2024 15:25:52","Sagemcom CMR"
"Closed Complete","Site Down","T2588","IHS_YND_742","NOCINC0002661176","Men=
dong NB","","21-07-2024 15:22:22","21-07-2024 14:28:06","21-07-2024 15:54:2=
0","grid outage;no space to deploy a mobil gen//grid return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","grid outage;no spa=
ce to deploy a mobil gen//grid return","denis.mballa@ihstowers.com","3257",=
"21-07-2024 15:22:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0002661107","MEHANDAN=
","","21-07-2024 14:58:40","21-07-2024 11:51:18","21-07-2024 15:02:37","Cas=
caded Incident from TTO2471773","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down due to disjunction Cb(2=
*80A) in PWC// He reamed Cb(2*80A), site on grid (Site Swapped by ZTE)","sy=
stem","11242","21-07-2024 14:58:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002661105","O=
dza II OCM","IHS_YND_528","21-07-2024 14:57:25","21-07-2024 11:51:18","21-0=
7-2024 15:02:37","site went down due to disjunction Cb(2*80A) in PWC// He r=
eamed Cb(2*80A), site on grid (Site Swapped by ZTE)","Albran Byorel","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Iss=
ue","site went down due to disjunction Cb(2*80A) in PWC// He reamed Cb(2*80=
A), site on grid (Site Swapped by ZTE)","landry.etame@ihstowers.com","11169=
","21-07-2024 14:57:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0002661048","M=
ontee-Jouvence","","21-07-2024 14:45:59","21-07-2024 12:41:49","21-07-2024 =
16:49:02","site went down due to disjunction CB(63A) in PWC// He reamed Cb,=
 site on grid (Site Swapped by ZTE)","Hyemafo Gildas","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Circuit Breaker Issue","site went =
down due to disjunction CB(63A) in PWC// He reamed Cb, site on grid (Site S=
wapped by ZTE)","emmanuel.ghani@ihstowers.com","7451","21-07-2024 14:45:59"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0002661015","E=
toudi 2","","21-07-2024 14:38:55","21-07-2024 14:37:51","21-07-2024 16:27:5=
7","Active//No power issue on site,site on Grid with Ubaie=3D53,6  V The TX=
  Armand Ngetsa(699949553) from Huawei is informed.site up at 02:42 PM","Fa=
brice Pouakam","Customer Equipment Failure","Active","Active Equipment Fail=
ure","BTS/TX Fault Alarm","Active//No power issue on site,site on Grid with=
 Ubaie=3D53,6  V The TX  Armand Ngetsa(699949553) from Huawei is informed.s=
ite up at 02:42 PM","landry.etame@ihstowers.com","65","21-07-2024 14:38:55"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0002660808","Bitoto",=
"","21-07-2024 13:52:00","21-07-2024 11:03:04","21-07-2024 11:51:39","Casca=
ded Incident from TTO2471417","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Site went down due to lightning which=
 caused tripping of Gen CB //We rearmed CB . Site on gen","system","10136",=
"21-07-2024 13:52:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0002660810","Essomba"=
,"","21-07-2024 13:52:00","21-07-2024 11:03:04","21-07-2024 11:51:39","Casc=
aded Incident from TTO2471417","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down due to lightning whic=
h caused tripping of Gen CB //We rearmed CB . Site on gen","system","10136"=
,"21-07-2024 13:52:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0002660809","AWAE OCM=
","","21-07-2024 13:52:00","21-07-2024 11:03:04","21-07-2024 11:51:39","Cas=
caded Incident from TTO2471417","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Site went down due to lightning whi=
ch caused tripping of Gen CB //We rearmed CB . Site on gen","system","10136=
","21-07-2024 13:52:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0002660811","Biteng-M=
aetur","","21-07-2024 13:52:00","21-07-2024 11:03:04","21-07-2024 11:51:39"=
,"Cascaded Incident from TTO2471417","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Site went down due to lightnin=
g which caused tripping of Gen CB //We rearmed CB . Site on gen","system","=
10136","21-07-2024 13:52:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002660796","B=
iteng","IHS_YND_292, IHS_YND_173, IHS_YND_179, IHS_YND_249","21-07-2024 13:=
49:12","21-07-2024 11:03:04","21-07-2024 11:51:39","Site went down due to l=
ightning which caused tripping of Gen CB //We rearmed CB . Site on gen","Mb=
a Lazare Herve","Force Majeure","Natural Disaster","Thunderstrike","Equipme=
nt Damaged","Site went down due to lightning which caused tripping of Gen C=
B //We rearmed CB . Site on gen","emmanuel.ghani@ihstowers.com","9969","21-=
07-2024 13:49:12","Sagemcom CMR"
"Closed Complete","Site Down","T0033","IHS_YND_167","NOCINC0002660782","Tou=
ring Club International","","21-07-2024 13:47:26","21-07-2024 13:36:22","21=
-07-2024 13:58:23","Grid outage,Site went down because Gen started an stopp=
ed due increase load in site// He reset Gen card and started Gen","Albran B=
yorel","Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid=
 outage,Site went down because Gen started an stopped due increase load in =
site// He reset Gen card and started Gen","joelle.ekessi@ihstowers.com","66=
7","21-07-2024 13:47:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0002660561","S=
apeur Mimboman","","21-07-2024 13:11:38","21-07-2024 13:03:34","21-07-2024 =
13:18:53","","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","AC=
DG - Control Panel","Grid outage site went down because Gen failed to start=
 due to Gen card dysfonction// He reset the Gen card and Gen manually start=
ed","emmanuel.ghani@ihstowers.com","484","21-07-2024 13:11:38","Sagemcom CM=
R"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002660539","Nsi=
meyong Shell","","21-07-2024 13:04:22","21-07-2024 12:57:12","21-07-2024 13=
:16:01","","MINKA NICOLAS","Equipment Repair","Passive","Control Panel","Po=
wer Cabinet - Battery Low","Grid outage site went down before Gen started d=
ue to poor battery backup//Gen started automatically","joelle.ekessi@ihstow=
ers.com","432","21-07-2024 13:04:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_157","IHS_YND_140","NOCINC0002660536","B=
ISCUITERIE","","21-07-2024 13:03:24","21-07-2024 12:59:18","21-07-2024 13:1=
2:49","","Paul BIBOUM","Equipment Repair","Passive","Control Panel","Power =
Cabinet - Battery Low","grid outage, site down due to poor backup//gen star=
ted","emmanuel.ghani@ihstowers.com","247","21-07-2024 13:03:24","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_474","IHS_YND_563","NOCINC0002660341","B=
astos Bethesda","","21-07-2024 12:54:50","21-07-2024 12:52:43","21-07-2024 =
12:58:04","","Mboua Thierry","Equipment Repair","Passive","Control Panel","=
Power Cabinet - Battery Low","Grid outage, site went down before Gen start =
due to poor battery backup // Gen started automatically","emmanuel.ghani@ih=
stowers.com","127","21-07-2024 12:54:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002660321","C=
arington","","21-07-2024 12:49:47","21-07-2024 12:46:42","21-07-2024 13:12:=
02","","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Grid outage  // Grid return","emmanuel.ghani@ihstowers.com","187","21-07=
-2024 12:49:47","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002660316","Ess=
os Marche","","21-07-2024 12:48:40","21-07-2024 12:37:33","21-07-2024 12:40=
:13","No power issue on site U=3D54,4 V ,site on Grid The TX   Armand Ngets=
a(699949553) from Huawei is informed","Delor Telezing","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site U=3D54,4 V ,site on Grid The TX   Armand Ngetsa(699949553) f=
rom Huawei is informed","joelle.ekessi@ihstowers.com","668","21-07-2024 12:=
48:40","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002660314","Jou=
vence 2000","","21-07-2024 12:47:38","21-07-2024 12:37:31","21-07-2024 14:3=
4:30","grid outage ,site went due to grid contactor  didn't not excicted,po=
or battery backup//he excited the grid contactor","Delor Telezing","Equipme=
nt Repair","Passive","Control Panel","ATS-AMF Issue","grid outage ,site wen=
t due to grid contactor  didn't not excicted,poor battery backup//he excite=
d the grid contactor","joelle.ekessi@ihstowers.com","609","21-07-2024 12:47=
:38","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002660310","Mim=
boman3","","21-07-2024 12:46:45","21-07-2024 12:34:28","21-07-2024 13:33:23=
","Grid outage site went down because Gen failed to start due to poor batte=
ry backup//Gen automatically started","Mba Lazare Herve","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site =
went down because Gen failed to start due to poor battery backup//Gen autom=
atically started","joelle.ekessi@ihstowers.com","739","21-07-2024 12:46:45"=
,"Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0002660300","H=
-Progres","","21-07-2024 12:44:06","21-07-2024 12:32:59","21-07-2024 12:54:=
28","Grid outage ,no space to deploy mobile gen // grid power return","","G=
rid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outa=
ge ,no space to deploy mobile gen // grid power return","emmanuel.ghani@ihs=
towers.com","668","21-07-2024 12:44:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0002660296","T=
radex-Nkomo","","21-07-2024 12:43:10","21-07-2024 12:34:06","22-07-2024 07:=
42:52","TX ISSUE","Albran Byorel","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on sit=
e,site on Grid with Ubaie=3D54 V The Team   SAMI//678430046 from ZTE is wor=
king on site","emmanuel.ghani@ihstowers.com","545","21-07-2024 12:43:10","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0002660292","C=
amp-Sic-Tsinga","","21-07-2024 12:42:17","21-07-2024 12:32:14","21-07-2024 =
14:22:36","Grid outage, no space to deploy a mobile Gen, // Grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage, no space to deploy a mobile Gen, // Grid return","emmanuel.ghani@ihs=
towers.com","604","21-07-2024 12:42:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002660287","Sapeur",=
"","21-07-2024 12:41:30","21-07-2024 12:32:38","21-07-2024 12:58:38","Casca=
ded Incident from TTO2470844","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage.no space to depoloy mobile g=
en//.grid power ","system","532","21-07-2024 12:41:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002660282","E=
-Police","IHS_YND_029","21-07-2024 12:40:42","21-07-2024 12:32:38","21-07-2=
024 12:58:38","Grid outage.no space to depoloy mobile gen//.grid return",""=
,"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid o=
utage.no space to depoloy mobile gen//.grid power ","emmanuel.ghani@ihstowe=
rs.com","486","21-07-2024 12:40:42","Sagemcom CMR"
"Closed Complete","Warning","","IHS_YND_341","NOCINC0002659814","Lobo OCM",=
"","21-07-2024 10:47:30","","","Cascaded Incident from TTO2470292","TIENTCH=
EU NZETCHIEU GAEL","Warning","Warning","Unlisted RCA","Warning - Others","E=
rror TT","system","389","21-07-2024 10:47:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002659640","E=
mana","","21-07-2024 10:03:46","21-07-2024 09:59:36","21-07-2024 10:50:26",=
"","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid outage//MDG 20 kva deployed","emmanuel.ghani@ihstowers.com","252","21-0=
7-2024 10:03:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_317","IHS_YND_322","NOCINC0002659639","S=
oa-II","IHS_YND_316, IHS_YND_324","21-07-2024 10:02:38","21-07-2024 09:57:3=
0","21-07-2024 10:39:00","","Siligap Boris","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","Grid outage, site wen down because Gen sta=
rted and stopped due to 'corrupted memory' alarm // He reset Gen card and g=
en manually start","emmanuel.ghani@ihstowers.com","309","21-07-2024 10:02:3=
8","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002659636","E=
lig-Edzoa","","21-07-2024 10:01:38","21-07-2024 09:57:30","21-07-2024 13:46=
:38","","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issu=
e","Grid outage  // Grid return","emmanuel.ghani@ihstowers.com","248","21-0=
7-2024 10:01:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0002659630","N=
komkana","","21-07-2024 10:00:44","21-07-2024 09:57:38","21-07-2024 10:17:1=
6","Grid outage.no space to deploy mobile gen//Grid return","","Grid Supply=
","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no spac=
e to deploy mobile gen//Grid return","emmanuel.ghani@ihstowers.com","187","=
21-07-2024 10:00:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_316","NOCINC0002659606","Akak-Nko=
zoa-MTN-IHS","","21-07-2024 09:56:50","21-07-2024 09:57:30","21-07-2024 10:=
39:00","Cascaded Incident from TTO2470047 - Cascade Removed From TTO2470047=
","Fabrice Pouakam","Cascade Outage","Passive","Cascade Passive","Cascade P=
assive","Grid outage, site wen down because Gen started and stopped due to =
'corrupted memory' alarm // He reset Gen card and gen manually start","syst=
em","1293","21-07-2024 09:56:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002659591","O=
lembe-Terminus","","21-07-2024 09:52:32","21-07-2024 09:44:26","21-07-2024 =
12:07:37","Grid outage ,site went down because Gen stop with alarm low oil =
pressure // He reset the gen card and manually started the Gen","Fabrice Po=
uakam","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","G=
rid outage ,site went down because Gen stop with alarm low oil pressure // =
He reset the gen card and manually started the Gen","emmanuel.ghani@ihstowe=
rs.com","486","21-07-2024 09:52:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0002659569","B=
astos Ekoudou","","21-07-2024 09:50:06","21-07-2024 09:45:56","21-07-2024 0=
9:49:32","grid outage, site down before gen start due to poor backup//GEN s=
tarted automatically","Mboua Thierry","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","grid outage, site down before gen st=
art due to poor backup//GEN started automatically","emmanuel.ghani@ihstower=
s.com","253","21-07-2024 09:50:06","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002659479","Afanoya"=
,"","21-07-2024 09:35:20","21-07-2024 09:29:43","21-07-2024 09:43:06","Casc=
aded Incident from TTO2469905","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive"," Grid outage site went down before Gen=
 started due to poor battery back up//Grid return","system","337","21-07-20=
24 09:35:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002659477","ELOUMDEM=
 CARRIERE","","21-07-2024 09:35:20","21-07-2024 09:29:43","21-07-2024 09:43=
:06","Cascaded Incident from TTO2469905","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive"," Grid outage site went down bef=
ore Gen started due to poor battery back up//Grid return","system","337","2=
1-07-2024 09:35:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002659478","MBALNGON=
G LYCEE","","21-07-2024 09:35:20","21-07-2024 09:29:43","21-07-2024 09:43:0=
6","Cascaded Incident from TTO2469905","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive"," Grid outage site went down befor=
e Gen started due to poor battery back up//Grid return","system","337","21-=
07-2024 09:35:20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002659472","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","21-07-2024 09:34:47","21-07-20=
24 09:29:43","21-07-2024 09:43:43"," Grid outage site went down before Gen =
started due to poor battery back up//Grid return","Hyemafo Gildas","Equipme=
nt Repair","Passive","Control Panel","Power Cabinet - Battery Low"," Grid o=
utage site went down before Gen started due to poor battery back up//Grid r=
eturn","joelle.ekessi@ihstowers.com","305","21-07-2024 09:34:47","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_244","IHS_YND_002","NOCINC0002659458","Y=
de-M-Central","","21-07-2024 09:34:18","21-07-2024 09:31:02","21-07-2024 13=
:15:21","Grid outage.no space to deploy mobile gen//.grid power return","",=
"Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid ou=
tage.no space to deploy mobile gen//.grid power return","emmanuel.ghani@ihs=
towers.com","198","21-07-2024 09:34:18","Sagemcom CMR"
"Closed Complete","Warning","T0058","IHS_YND_293","NOCINC0002659368","Nkoab=
ang MTN","","21-07-2024 09:12:47","","","SITE ON BATTERY","Mba Lazare Herve=
","Warning","Warning","POWER","Warning - AC Phase 1 Current Low","Alarm  cl=
eared","kombi.samuel@ihstowers.com","3","21-07-2024 09:12:47","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002659261","E=
TOUDI CHAPELLE","","21-07-2024 08:42:56","21-07-2024 08:37:49","21-07-2024 =
08:40:25","ACTIVE No power issue Ubaie=3D51.2V site on Grid Armand Nguetsa =
(699949553)from Huawei is informed ","Delor Telezing","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No=
 power issue Ubaie=3D51.2V site on Grid Armand Nguetsa (699949553)from Huaw=
ei is informed ","emmanuel.ghani@ihstowers.com","308","21-07-2024 08:42:56"=
,"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_709","NOCINC0002659218","Nkolo II=
 New","","21-07-2024 08:30:10","21-07-2024 09:48:10","21-07-2024 10:18:41",=
"","Mba Lazare Herve","Cascade Outage","Passive","Cascade Passive","Cascade=
 Passive","Grid outage.gen gailed to start due to fuel pump faulty//we chan=
ge fuel pump and gen manually started ","system","89305","21-07-2024 08:30:=
10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_266","NOCINC0002659217","Mimboman=
4","IHS_YND_709","21-07-2024 08:30:10","21-07-2024 08:17:10","21-07-2024 10=
:18:41","","Mba Lazare Herve","Fuel Outage (Probable)","Passive","ACDG Gen"=
,"ACDG - Fuel Pump","Grid outage.gen gailed to start due to fuel pump fault=
y//we change fuel pump and gen manually started ","system","11701","21-07-2=
024 08:30:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_387","IHS_YND_276","NOCINC0002659214","E=
kombitie","","21-07-2024 08:29:57","21-07-2024 08:24:51","21-07-2024 10:04:=
25","Grid outage,site went down because Gen ran still fuel shortage //refue=
ling done","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage,site went down because Gen ran still fuel shortage //refuel=
ing done","emmanuel.ghani@ihstowers.com","307","21-07-2024 08:29:57","Sagem=
com CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002659197","Jou=
vence 2000","","21-07-2024 08:25:23","21-07-2024 08:18:18","21-07-2024 09:4=
3:26","  Grid outage,Gen  failed to start  due to poor battery back up  and=
 grid contactor did not excited// He excited grid contactor and site on gri=
d ","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Load C=
ontactor","  Grid outage,Gen  failed to start  due to poor battery back up =
 and grid contactor did not excited// He excited grid contactor and site on=
 grid ","joelle.ekessi@ihstowers.com","426","21-07-2024 08:25:23","Sagemcom=
 CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002659193","NKO=
MEKUI OCM","IHS_YND_341","21-07-2024 08:24:05","21-07-2024 08:17:01","21-07=
-2024 08:27:30","Grid outage, site went down before DG start due to poor ba=
ttery backup // DG start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equipmen=
t Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid out=
age, site went down before DG start due to poor battery backup // DG start =
automaticaly","joelle.ekessi@ihstowers.com","427","21-07-2024 08:24:05","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_464","IHS_YND_674","NOCINC0002659186","M=
fou EPC","","21-07-2024 08:22:18","21-07-2024 08:17:10","21-07-2024 10:18:4=
1","Grid outage.gen failed to start due to fuel pump faulty//we change fuel=
 pump and gen manually started ","Mba Lazare Herve","Fuel Outage (Probable)=
","Passive","Diesel","Fuel Line Issue","Grid outage.gen failed to start due=
 to fuel pump faulty//we change fuel pump and gen manually started ","emman=
uel.ghani@ihstowers.com","309","21-07-2024 08:22:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_390","IHS_YND_203","NOCINC0002659184","T=
ongolo OCM","","21-07-2024 08:21:05","21-07-2024 08:11:00","21-07-2024 08:2=
2:06","Site went down due to PWC OVERLOAD 12Kw, 220(A)// load reduced","Del=
or Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Overload","Sit=
e went down due to PWC OVERLOAD 12Kw, 220(A)// load reduced","emmanuel.ghan=
i@ihstowers.com","605","21-07-2024 08:21:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0002659151","Bitoto",=
"","21-07-2024 08:14:00","21-07-2024 08:05:44","21-07-2024 08:25:38","Casca=
ded Incident from TTO2469479","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","Grid Outage Site went down due to CB =
(32 A)Gen Disjunted due to  lightning // He reamed the CB Gen","system","49=
6","21-07-2024 08:14:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0002659152","AWAE OCM=
","","21-07-2024 08:14:00","21-07-2024 08:05:44","21-07-2024 08:25:38","Cas=
caded Incident from TTO2469479","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid Outage Site went down due to C=
B (32 A)Gen Disjunted due to  lightning // He reamed the CB Gen","system","=
496","21-07-2024 08:14:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0002659153","Essomba"=
,"","21-07-2024 08:14:00","21-07-2024 08:05:44","21-07-2024 08:25:38","Casc=
aded Incident from TTO2469479","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Grid Outage Site went down due to CB=
 (32 A)Gen Disjunted due to  lightning // He reamed the CB Gen","system","4=
96","21-07-2024 08:14:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_098","NOCINC0002659150","Ekounou"=
,"","21-07-2024 08:14:00","21-07-2024 08:05:44","21-07-2024 08:25:38"," Gri=
d outage, site went down before Gen start due to poor battery backup // Gri=
d power return","Albran Byorel","Equipment Repair","Passive","Control Panel=
","Power Cabinet - Battery Low"," Grid outage, site went down before Gen st=
art due to poor battery backup // Grid power return","system","496","21-07-=
2024 08:14:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0002659154","Biteng-M=
aetur","","21-07-2024 08:14:00","21-07-2024 08:05:44","21-07-2024 08:25:38"=
,"Cascaded Incident from TTO2469479","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid Outage Site went down due=
 to CB (32 A)Gen Disjunted due to  lightning // He reamed the CB Gen","syst=
em","496","21-07-2024 08:14:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_211","IHS_YND_248","NOCINC0002659084","B=
iteng","IHS_YND_292, IHS_YND_173, IHS_YND_179, IHS_YND_249","21-07-2024 08:=
10:05","21-07-2024 08:05:44","21-07-2024 08:27:07","Grid Outage Site went d=
own due to CB (32 A)Gen Disjunted due to  lightning // He reamed the CB Gen=
","Mba Lazare Herve","Force Majeure","Natural Disaster","Thunderstrike","Eq=
uipment Damaged","Grid Outage Site went down due to CB (32 A)Gen Disjunted =
due to  lightning // He reamed the CB Gen","emmanuel.ghani@ihstowers.com","=
264","21-07-2024 08:10:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0002659035","Ndogbess=
ol","","21-07-2024 07:58:30","21-07-2024 07:42:49","21-07-2024 07:44:22","C=
ascaded Incident from TTO2469322","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site wen down because=
 gen failed to start due to poor battery backup // Gen start automatically"=
,"system","941","21-07-2024 07:58:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0002659036","Ngog Map=
ubi","","21-07-2024 07:58:30","21-07-2024 07:42:49","21-07-2024 07:44:22","=
Cascaded Incident from TTO2469322","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site wen down becaus=
e gen failed to start due to poor battery backup // Gen start automatically=
","system","941","21-07-2024 07:58:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0002659037","Boumnyeb=
el","","21-07-2024 07:58:30","21-07-2024 07:42:49","21-07-2024 07:44:22","C=
ascaded Incident from TTO2469322","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site wen down because=
 gen failed to start due to poor battery backup // Gen start automatically"=
,"system","941","21-07-2024 07:58:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0002659038","Mamb",""=
,"21-07-2024 07:58:30","21-07-2024 07:42:49","21-07-2024 07:44:22","Cascade=
d Incident from TTO2469322","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site wen down because gen f=
ailed to start due to poor battery backup // Gen start automatically","syst=
em","941","21-07-2024 07:58:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0002658933","B=
oumnyebel OCM","IHS_EDA_056, IHS_YND_419, IHS_YND_381, IHS_YND_376","21-07-=
2024 07:43:59","21-07-2024 07:42:49","21-07-2024 07:44:22","Grid outage, si=
te wen down because gen failed to start due to poor battery backup // Gen s=
tart automatically","Kemeni Franklin","Equipment Repair","Passive","Control=
 Panel","Power Cabinet - Battery Low","Grid outage, site wen down because g=
en failed to start due to poor battery backup // Gen start automatically","=
emmanuel.ghani@ihstowers.com","71","21-07-2024 07:43:59","Sagemcom CMR"
"Closed Complete","Site Down","T3217","IHS_YND_763","NOCINC0002658669","Nko=
lbisson usines des eaux 2","","21-07-2024 06:34:59","21-07-2024 06:33:55","=
21-07-2024 07:11:35","Grid outage Gen overload ( 09KVA ; 115 A ) // Site st=
abilized","TIENTCHEU NZETCHIEU GAEL","Equipment Repair","Passive","ACDG Gen=
","ACDG - Overload","Grid outage Gen overload ( 09KVA ; 115 A ) // Site sta=
bilized","joelle.ekessi@ihstowers.com","64","21-07-2024 06:34:59","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0002658664","E=
toudi 2","","21-07-2024 06:31:29","21-07-2024 06:29:23","21-07-2024 06:30:1=
6","no power issue Ubaie=3D53,8V, site on Grid. the TX Armand Ngetsa(699949=
553) from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue =
Ubaie=3D53,8V, site on Grid. the TX Armand Ngetsa(699949553) from Huawei is=
 informed","emmanuel.ghani@ihstowers.com","128","21-07-2024 06:31:29","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002658661","M=
vog-Manga","","21-07-2024 06:30:51","21-07-2024 05:36:34","21-07-2024 05:40=
:09","Active//No power issue on site,site on Grid with Ubaie=3D53,8 V The T=
eam  franck//699670325 from ZTE is working on site","Albran Byorel","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site,site on Grid with Ubaie=3D53,8 V The Te=
am  franck//699670325 from ZTE is working on site","emmanuel.ghani@ihstower=
s.com","3258","21-07-2024 06:30:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_249","IHS_YND_225","NOCINC0002658249","S=
cience","","21-07-2024 04:01:47","21-07-2024 03:55:37","21-07-2024 05:11:03=
","grid outage,gen failed to start due to gen overload (20kva,iload:300A)//=
he reduice the load on site","TIENTCHEU NZETCHIEU GAEL","Equipment Repair",=
"Passive","ACDG Gen","ACDG - Overload","grid outage,gen failed to start due=
 to gen overload (20kva,iload:300A)//he reduice the load on site","ange.kon=
go@ihstowers.com","372","21-07-2024 04:01:47","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002658072","MBALNGON=
G LYCEE","","21-07-2024 02:29:10","21-07-2024 02:13:30","21-07-2024 02:29:2=
3","Cascaded Incident from TTO2468316","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","No power issue on site ,site on G=
rid with Ubaie=3D53 V  Rm Alain//  691144423 from Huawei is informed site u=
p 02:29 AM ","system","940","21-07-2024 02:29:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002658073","Afanoya"=
,"","21-07-2024 02:29:10","21-07-2024 02:13:30","21-07-2024 02:29:23","Casc=
aded Incident from TTO2468316","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","No power issue on site ,site on Grid w=
ith Ubaie=3D53 V  Rm Alain//  691144423 from Huawei is informed site up 02:=
29 AM ","system","940","21-07-2024 02:29:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002658071","ELOUMDEM=
 CARRIERE","","21-07-2024 02:29:10","21-07-2024 02:13:30","21-07-2024 02:29=
:23","Cascaded Incident from TTO2468316","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","No power issue on site ,site on=
 Grid with Ubaie=3D53 V  Rm Alain//  691144423 from Huawei is informed site=
 up 02:29 AM ","system","940","21-07-2024 02:29:10","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002658039","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","21-07-2024 02:15:41","21-07-20=
24 02:13:30","21-07-2024 02:29:23"," Grid outage site went down before Gen =
started due to poor battery back up//Grid return","Hyemafo Gildas","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue"," Grid outage si=
te went down before Gen started due to poor battery back up//Grid return","=
dorothy.djantio@ihstowers.com","133","21-07-2024 02:15:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002657832","O=
dza II OCM","","21-07-2024 01:11:50","20-07-2024 22:17:39","21-07-2024 02:4=
7:40","site went down due to disjunction Cb(2*80A) in PWC// He reamed Cb(2*=
80A), site on grid (Site Swapped by ZTE)","Albran Byorel","Equipment Repair=
","Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Site w=
ent down due to CB OCM (100A) disjuncted in PWC //  He reamed the CB (Site =
Swapped  by ZTE)","etienne.itondo@ihstowers.com","10452","21-07-2024 01:11:=
50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002657725","E=
TOUDI CHAPELLE","","21-07-2024 00:17:52","21-07-2024 00:15:47","21-07-2024 =
00:20:22","No power issue on site.Site on Grid with Ubaie=3D52. V The TX Ar=
mand Nguetsa(699949553) from Huawei is informed . Repetitif issue","Delor T=
elezing","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D52. V=
 The TX Armand Nguetsa(699949553) from Huawei is informed . Repetitif issue=
","ange.kongo@ihstowers.com","127","21-07-2024 00:17:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0002657720","E=
toudi 2","","21-07-2024 00:16:33","21-07-2024 00:14:28","21-07-2024 00:20:1=
6","no power issue Ubaie=3D53,8V, site on Grid. the TX Armand Ngetsa(699949=
553) from Huawei is informed","Fabrice Pouakam","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue =
Ubaie=3D53,8V, site on Grid. the TX Armand Ngetsa(699949553) from Huawei is=
 informed","ange.kongo@ihstowers.com","127","21-07-2024 00:16:33","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002657698","M=
vog-Manga","","21-07-2024 00:09:26","21-07-2024 00:02:16","21-07-2024 00:15=
:47","Active//No power issue on site,site on Grid with Ubaie=3D53,8 V The T=
eam  franck//686650915 from ZTE is working on site","Albran Byorel","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active//No power issue on site,site on Grid with Ubaie=3D53,8 V The Te=
am  franck//686650915 from ZTE is working on site","ange.kongo@ihstowers.co=
m","433","21-07-2024 00:09:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002657454","M=
arche Odza","","20-07-2024 22:42:52","20-07-2024 22:39:41","20-07-2024 23:3=
0:18","Active//No power issue on site,site on Grid with Ubaie=3D54,5 V TX F=
ME Lionel steve/655184876 from Huawei is informed , repetitif issue","Albra=
n Byorel","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active//No power issue on site,site on Grid with Ubai=
e=3D54,5 V TX FME Lionel steve/655184876 from Huawei is informed , repetiti=
f issue","ange.kongo@ihstowers.com","192","20-07-2024 22:42:52","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_762","NOCINC0002657184","Nkolfon =
Cimencam","","20-07-2024 21:54:10","20-07-2024 21:27:38","20-07-2024 21:47:=
33","Cascaded Incident from TTO2467271","Hyemafo Gildas","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Grid outage, site went down b=
ecause Gen faild to start due to PSC3 malfunctionninng // He delected PSC3,=
 Gen started","system","1592","20-07-2024 21:54:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002657183","Afanoya"=
,"","20-07-2024 21:54:10","20-07-2024 21:27:38","20-07-2024 21:47:33","Casc=
aded Incident from TTO2467271","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage, site went down because Ge=
n faild to start due to PSC3 malfunctionninng // He delected PSC3, Gen star=
ted","system","1592","20-07-2024 21:54:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002657164","Eto koss=
 Yde","","20-07-2024 21:50:10","20-07-2024 21:45:42","20-07-2024 21:48:10",=
"Cascaded Incident from TTO2467317","Fanda Brice","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","Site went down because insufficiency=
 of rectifier on site due to increase load in site // load reduced and Site=
 Stabilized((waiting has added rectifiers, the site will be unstable).","sy=
stem","268","20-07-2024 21:50:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002657165","ELOUMDEM=
 CARRIERE 2","","20-07-2024 21:50:10","20-07-2024 21:45:42","20-07-2024 21:=
48:10","Cascaded Incident from TTO2467317","Fanda Brice","Cascade Outage","=
Passive","Cascade Passive","Cascade Passive","Site went down because insuff=
iciency of rectifier on site due to increase load in site // load reduced a=
nd Site Stabilized((waiting has added rectifiers, the site will be unstable=
).","system","268","20-07-2024 21:50:10","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002657157","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","20-07-2024 21:48:54","20-07-2024 21:45=
:42","20-07-2024 21:48:10","Site went down because insufficiency of rectifi=
er on site due to increase load in site // load reduced and Site Stabilized=
((waiting has added rectifiers, the site will be unstable).","Fanda Brice",=
"Equipment Repair","Passive","Rectifier","Rectifier Module","Site went down=
 because insufficiency of rectifier on site due to increase load in site //=
 load reduced and Site Stabilized((waiting has added rectifiers, the site w=
ill be unstable).","alexandre.kamal@ihstowers.com","193","20-07-2024 21:48:=
54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0002657118","A=
hala","IHS_YND_313, IHS_YND_762","20-07-2024 21:41:44","20-07-2024 21:27:38=
","20-07-2024 22:13:55","Grid outage, site went down because Gen faild to s=
tart due to PSC3 malfunctionninng // He delected PSC3, Gen started","Hyemaf=
o Gildas","Equipment Repair","Passive","Control Panel","ATS-AMF Issue","Gri=
d outage, site went down because Gen faild to start due to PSC3 malfunction=
ninng // He delected PSC3, Gen started","kamga.virgile@ihstowers.com","849"=
,"20-07-2024 21:41:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_911","IHS_YND_762","NOCINC0002656919","N=
kolfon Cimencam","","20-07-2024 21:00:09","20-07-2024 20:38:51","20-07-2024=
 20:38:52","After Ahala","Hyemafo Gildas","Incorrectly Logged Tickets","Err=
or","Error","Error","WRONGLY TICKET","kamga.virgile@ihstowers.com","1278","=
20-07-2024 21:00:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002656764","MBALNGON=
G LYCEE","","20-07-2024 20:21:30","20-07-2024 19:57:27","20-07-2024 20:25:4=
8","Cascaded Incident from TTO2466755","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because gen failed=
 to start due to grid bad voltage// He bypassed Grid  and Gen manually star=
ted","system","1443","20-07-2024 20:21:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002656765","Afanoya"=
,"","20-07-2024 20:21:30","20-07-2024 19:57:27","20-07-2024 20:25:48","Casc=
aded Incident from TTO2466755","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because gen failed to s=
tart due to grid bad voltage// He bypassed Grid  and Gen manually started",=
"system","1443","20-07-2024 20:21:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002656763","ELOUMDEM=
 CARRIERE","","20-07-2024 20:21:30","20-07-2024 19:57:27","20-07-2024 20:25=
:48","Cascaded Incident from TTO2466755","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down because gen fail=
ed to start due to grid bad voltage// He bypassed Grid  and Gen manually st=
arted","system","1443","20-07-2024 20:21:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002656754","M=
arche Odza","","20-07-2024 20:20:33","20-07-2024 20:17:24","20-07-2024 20:1=
9:30","Active//No power issue on site,site on Grid with Ubaie=3D54,5 V TX F=
ME Lionel steve/655184876 from Huawei is informed ,Site up at 08:19 PM repe=
titif issue","Albran Byorel","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site,sit=
e on Grid with Ubaie=3D54,5 V TX FME Lionel steve/655184876 from Huawei is =
informed ,Site up at 08:19 PM repetitif issue","kamga.virgile@ihstowers.com=
","190","20-07-2024 20:20:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0002656743","M=
vog-Betsi","","20-07-2024 20:18:49","20-07-2024 19:58:18","20-07-2024 20:02=
:33","Active//No power issue on site,site on Grid with Ubaie=3D54,9  V The =
Team TSOGNE Rodolpho/6 56 35 38 62/ZTE working on site","Hyemafo Gildas","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue on site,site on Grid with Ubaie=3D54,9  V =
The Team TSOGNE Rodolpho/6 56 35 38 62/ZTE working on site","kamga.virgile@=
ihstowers.com","1232","20-07-2024 20:18:49","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002656673","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","20-07-2024 20:04:32","20-07-20=
24 19:57:27","20-07-2024 20:25:48","site went down because gen failed to st=
art due to grid bad voltage// He bypassed Grid  and Gen manually started","=
Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid - Phase Contr=
oller Faulty","site went down because gen failed to start due to grid bad v=
oltage// He bypassed Grid  and Gen manually started","alexandre.kamal@ihsto=
wers.com","425","20-07-2024 20:04:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002656361","M=
arche Odza","","20-07-2024 18:57:12","20-07-2024 17:14:39","20-07-2024 17:1=
6:49","Active//No power issue on site,site on Grid with Ubaie=3D54,5 V TX F=
ME Lionel steve/655184876 from Huawei is informed ,Site up at 05:16 PM repe=
titif issue","Albran Byorel","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site,sit=
e on Grid with Ubaie=3D54,5 V TX FME Lionel steve/655184876 from Huawei is =
informed ,Site up at 05:16 PM repetitif issue","kamga.virgile@ihstowers.com=
","6155","20-07-2024 18:57:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_276","IHS_YND_172","NOCINC0002656222","T=
radex-Nkomo","","20-07-2024 18:20:32","20-07-2024 17:33:18","20-07-2024 17:=
35:27","Active//No power issue on site,site on Grid with Ubaie=3D54 V The T=
eam   SAMI//678430046 from ZTE is working on site","Albran Byorel","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active//No power issue on site,site on Grid with Ubaie=3D54 V The Team =
  SAMI//678430046 from ZTE is working on site","kamga.virgile@ihstowers.com=
","2836","20-07-2024 18:20:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002655690","E=
TOUDI CHAPELLE","","20-07-2024 16:30:43","20-07-2024 16:21:32","20-07-2024 =
16:25:47","No power issue on site.Site on Grid with Ubaie=3D52. V The TX Ar=
mand Nguetsa(699949553) from Huawei is informed . Repetitif issue","Delor T=
elezing","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D52. V=
 The TX Armand Nguetsa(699949553) from Huawei is informed . Repetitif issue=
","kamga.virgile@ihstowers.com","552","20-07-2024 16:30:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002655618","M=
asque","","20-07-2024 16:16:16","20-07-2024 16:02:55","20-07-2024 16:05:18"=
,"No power issue on site. Site on Grid with Ubaie=3D54.3 V The TX FME Eloun=
dou // 693212405// From Huawei is informed repetitive issue","Fabrice Pouak=
am","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","No power issue on site. Site on Grid with Ubaie=3D54.3 V Th=
e TX FME Eloundou // 693212405// From Huawei is informed repetitive issue",=
"kamga.virgile@ihstowers.com","803","20-07-2024 16:16:16","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002655454","Pha=
rmacie SION","","20-07-2024 15:45:33","20-07-2024 15:41:25","20-07-2024 15:=
55:12"," Grid outage site went down before Gen started due to poor battery =
back up//Gen started automatically","Paul BIBOUM","Equipment Repair","Passi=
ve","Control Panel","Power Cabinet - Battery Low"," Grid outage site went d=
own before Gen started due to poor battery back up//Gen started automatical=
ly","alexandre.kamal@ihstowers.com","251","20-07-2024 15:45:33","Sagemcom C=
MR"
"Closed Complete","Site Down","T3154","IHS_YND_125","NOCINC0002655368","Cha=
rles-Atangana","","20-07-2024 15:29:54","20-07-2024 15:16:42","20-07-2024 1=
5:29:47","Grid outage//MDG 20 kva deployed","","Grid Supply","Passive","Gri=
d","National Grid - Grid Outage Issue","Grid outage//MDG 20 kva deployed","=
alexandre.kamal@ihstowers.com","796","20-07-2024 15:29:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_449","IHS_YND_051","NOCINC0002655344","M=
amch Building","","20-07-2024 15:27:32","20-07-2024 15:14:24","20-07-2024 1=
5:15:25","Incorrectly Logged Tickets","Mboua Thierry","Incorrectly Logged T=
ickets","Error","Error","Error","Incorrectly Logged Tickets","kamga.virgile=
@ihstowers.com","790","20-07-2024 15:27:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0002655323","C=
RH-Etoug-Ebe","","20-07-2024 15:21:26","20-07-2024 15:02:08","20-07-2024 15=
:05:02","Active//No power issue on site,site on Grid with Ubaie=3D51,1  V  =
The Team   Hopsun Ganu//237 6 52 89 42 from ZTE is working on site","Hyemaf=
o Gildas","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","Active//No power issue on site,site on Grid with Ubai=
e=3D51,1  V  The Team   Hopsun Ganu//237 6 52 89 42 from ZTE is working on =
site","kamga.virgile@ihstowers.com","1159","20-07-2024 15:21:26","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002655006","M=
vog-Manga","","20-07-2024 14:47:22","20-07-2024 14:19:02","20-07-2024 14:19=
:03","Active//No power issue on site,site on Grid with Ubaie=3D53,8 V The T=
eam  franck//686650915 from ZTE is working on site   ","Albran Byorel","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","Affected by 3=
rd Party Site","Active//No power issue on site,site on Grid with Ubaie=3D53=
,8 V The Team  franck//686650915 from ZTE is working on site
  ","kamga.virgile@ihstowers.com","1702","20-07-2024 14:47:22","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_374","IHS_YND_173","NOCINC0002654953","A=
WAE OCM","","20-07-2024 14:32:12","20-07-2024 14:16:02","20-07-2024 14:20:2=
2","Active//No power issue on site,site on Grid with Ubaie=3D54,6 V  The Te=
am  DAVID// 659933473 from ZTE is working on site","Mba Lazare Herve","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site,site on Grid with Ubaie=3D54,6 V  The=
 Team  DAVID// 659933473 from ZTE is working on site","kamga.virgile@ihstow=
ers.com","972","20-07-2024 14:32:12","Sagemcom CMR"
"Closed Complete","Site Down","T0291","IHS_YND_147","NOCINC0002654751","Clu=
b France","","20-07-2024 14:00:49","20-07-2024 13:52:31","20-07-2024 14:26:=
40","Grid Outage// Grid power return","","Grid Supply","Passive","Grid","Na=
tional Grid - Grid Outage Issue","Grid Outage// Grid power return","denis.m=
balla@ihstowers.com","500","20-07-2024 14:00:49","Sagemcom CMR"
"Closed Complete","Site Down","T0524","IHS_YND_004","NOCINC0002654738","Av =
Kennedy","","20-07-2024 13:57:49","20-07-2024 12:31:28","20-07-2024 14:20:4=
1","Grid outage no space to deploy Mobil Gen //Grid power return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage n=
o space to deploy Mobil Gen //Grid power return","denis.mballa@ihstowers.co=
m","5181","20-07-2024 13:57:49","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002654721","Ess=
os Marche","","20-07-2024 13:55:07","20-07-2024 10:36:38","20-07-2024 10:45=
:24","Grid outage, site went down before Gen start due to poor battery back=
up // Gen automatically started, Power issue resolved  at 10:45 AM, Armand(=
691144412) from Huawei is informed ","Delor Telezing","Equipment Repair","P=
assive","Control Panel","Power Cabinet - Battery Low","Grid outage, site we=
nt down before Gen start due to poor battery backup // Gen automatically st=
arted, Power issue resolved  at 10:45 AM, Armand(691144412) from Huawei is =
informed ","denis.mballa@ihstowers.com","11910","20-07-2024 13:55:07","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_505","NOCINC0002654568","Scalom-I=
HS","","20-07-2024 13:18:50","20-07-2024 12:19:30","20-07-2024 14:30:11","C=
ascaded Incident from TTO2464376","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid outage /Grid power return","system","3560","=
20-07-2024 13:18:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0002654514","E=
koumdoum","","20-07-2024 13:16:51","20-07-2024 12:16:46","20-07-2024 12:30:=
39","No power issue on site ,site on Gen with Ubaie=3D 54,3 V  team Willy /=
691145053 from ZTE is working on site","Albran Byorel","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site ,site on Gen with Ubaie=3D 54,3 V team Willy /691145053 from=
 ZTE is working on site
","landry.etame@ihstowers.com","3606","20-07-2024 13:16:51","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0002654453","Hotel de=
 Ville Yde","","20-07-2024 13:05:50","20-07-2024 12:58:51","20-07-2024 14:3=
9:49","Cascaded Incident from TTO2464254","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage//MDG 13 kva deploy=
ed","system","419","20-07-2024 13:05:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0002654451","N=
R-Bastos","IHS_YND_019","20-07-2024 13:05:01","20-07-2024 12:58:51","20-07-=
2024 14:39:49","Grid outage//MDG 13 kva deployed","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","Grid outage//MDG 13 kva deplo=
yed","landry.etame@ihstowers.com","371","20-07-2024 13:05:01","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_265","IHS_YND_229","NOCINC0002654440","C=
RH-Etoug-Ebe","","20-07-2024 13:02:53","20-07-2024 12:27:45","20-07-2024 12=
:30:05"," No power issue on site ,site on Grid with Ubaie=3D 53,6 V,Hopsun =
Ganu( 6 52 89 42 11) from ZTE working on site","Hyemafo Gildas","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
" No power issue on site ,site on Grid with Ubaie=3D 53,6 V,Hopsun Ganu( 6 =
52 89 42 11) from ZTE working on site","landry.etame@ihstowers.com","2109",=
"20-07-2024 13:02:53","Sagemcom CMR"
"Closed Complete","Site Down","T2285","IHS_YND_562","NOCINC0002654261","Acc=
acia New","IHS_YND_505","20-07-2024 12:31:02","20-07-2024 12:19:30","20-07-=
2024 14:32:33","Grid outage /Grid power return","","Grid Supply","Passive",=
"Grid","National Grid - Grid Outage Issue","Grid outage /Grid power return"=
,"denis.mballa@ihstowers.com","3533","20-07-2024 12:31:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_042","IHS_YND_175","NOCINC0002654211","N=
komo","","20-07-2024 12:18:38","20-07-2024 12:09:34","20-07-2024 12:41:46",=
"No power issue on site U=3D52,1v site on grid Team Narcisse Kocing/6906224=
75/ZTE working on site","Mba Lazare Herve","Customer Equipment Failure","Ac=
tive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on si=
te U=3D52,1v site on grid Team Narcisse Kocing/690622475/ZTE working on sit=
e","landry.etame@ihstowers.com","545","20-07-2024 12:18:38","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002654205","O=
dza II OCM","","20-07-2024 12:17:23","20-07-2024 11:44:16","20-07-2024 11:5=
0:05","Active//No power issue on site,site on Grid with Ubaie=3D54,2 V TX F=
ME Lionnel// 655184876 from Huawei is informed,","Albran Byorel","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site,site on Grid with Ubaie=3D54,2 V TX FME Li=
onnel// 655184876 from Huawei is informed,","landry.etame@ihstowers.com","1=
989","20-07-2024 12:17:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_016","IHS_YND_226","NOCINC0002654170","M=
vog-Betsi","","20-07-2024 12:08:01","20-07-2024 11:51:52","20-07-2024 12:17=
:08","No power issue on site U=3D54v site on grid Team TSOGNE Rodolpho/6 56=
 35 38 62/ZTE working on site","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site U=3D54v site on grid Team TSOGNE Rodolpho/6 56 35 38 62/ZTE working=
 on site","landry.etame@ihstowers.com","969","20-07-2024 12:08:01","Sagemco=
m CMR"
"Closed Complete","Site Down","T3149","IHS_YND_044","NOCINC0002654098","Pol=
ytechnique","","20-07-2024 11:56:43","20-07-2024 11:52:21","20-07-2024 14:2=
5:57","Grid outage no space to deploy Mobil Gen awaiting Grid power return"=
,"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gri=
d outage no space to deploy Mobil Gen awaiting Grid power return","denis.mb=
alla@ihstowers.com","264","20-07-2024 11:56:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_535","IHS_YND_682","NOCINC0002654021","M=
ONTEE NKONDENGUI","","20-07-2024 11:44:28","20-07-2024 11:34:23","20-07-202=
4 11:55:06","No power issue on site U=3D53,5v site on grid Team  Prince Joh=
ndon/654153956/ZTE working on site","Albran Byorel","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power is=
sue on site U=3D53,5v site on grid Team  Prince Johndon/654153956/ZTE worki=
ng on site","landry.etame@ihstowers.com","607","20-07-2024 11:44:28","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_323","IHS_YND_043","NOCINC0002654016","E=
mia","","20-07-2024 11:43:36","20-07-2024 11:34:30","20-07-2024 14:30:30","=
Grid outage no space to deploy Mobil Gen //Grid power return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy Mobil Gen //Grid power return
","landry.etame@ihstowers.com","548","20-07-2024 11:43:36","Sagemcom CMR"
"Closed Complete","Site Down","T0420","IHS_YND_082","NOCINC0002653949","Mok=
olo Yaounde","","20-07-2024 11:27:48","20-07-2024 11:24:30","20-07-2024 14:=
26:00","	Grid outage no space to deploy the MDG//Grid power return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid outag=
e no space to deploy the MDG//Grid power return","denis.mballa@ihstowers.co=
m","199","20-07-2024 11:27:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0002653923","E=
kounou","","20-07-2024 11:24:04","20-07-2024 11:20:55","20-07-2024 11:35:07=
","No power issue on site U=3D53,4v site on gen Team OBETTA SIMEON /6527498=
12/ZTE working on site","Albran Byorel","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site =
U=3D53,4v site on gen Team OBETTA SIMEON /652749812/ZTE working on site","l=
andry.etame@ihstowers.com","189","20-07-2024 11:24:04","Sagemcom CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0002653885","Biy=
emassi LAC","","20-07-2024 11:15:45","20-07-2024 11:07:30","20-07-2024 14:3=
2:34","Grid outage no space to deploy// Grid power return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid outage no space=
 to deploy// Grid power return","denis.mballa@ihstowers.com","497","20-07-2=
024 11:15:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0002653878","S=
tade-Abega","","20-07-2024 11:13:28","20-07-2024 11:04:22","20-07-2024 11:2=
2:53","ACTIVE No power issue on site ,site on Grid with Ubaie=3D 54,9 V  Th=
e Team Olumide// 687648830 from ZTE is working on site","Mba Lazare Herve",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","ACTIVE No power issue on site ,site on Grid with Ubaie=3D 54,9 =
V=20
The Team Olumide// 687648830 from ZTE is working on site
","landry.etame@ihstowers.com","548","20-07-2024 11:13:28","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0002653856","Bri=
quetterie","","20-07-2024 11:08:02","20-07-2024 10:59:43","20-07-2024 14:25=
:45","	Grid outage no space to deploy the MDG//Grid power return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","	Grid outage =
no space to deploy the MDG//Grid power return","denis.mballa@ihstowers.com"=
,"500","20-07-2024 11:08:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0002653824","B=
riqueterie","","20-07-2024 10:59:46","20-07-2024 10:54:40","20-07-2024 14:2=
2:48","	Grid outage no space to deploy//Grid power return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","	Grid outage no spac=
e to deploy//Grid power return","landry.etame@ihstowers.com","307","20-07-2=
024 10:59:46","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002653768","Bas=
tos Amb Coree","","20-07-2024 10:44:30","20-07-2024 10:10:06","20-07-2024 1=
1:06:36","grid outage,no space to deploy a mobil gen//grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,=
no space to deploy a mobil gen//grid return","denis.mballa@ihstowers.com","=
2067","20-07-2024 10:44:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_566","NOCINC0002653757","Crf Corn=
ier","","20-07-2024 10:41:10","20-07-2024 10:35:52","20-07-2024 11:37:20","=
Cascaded Incident from TTO2463461","MINKA NICOLAS","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","Grid outage // Grid return","system=
","318","20-07-2024 10:41:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_071","IHS_YND_112","NOCINC0002653745","M=
adison","IHS_YND_566","20-07-2024 10:40:09","20-07-2024 10:35:52","20-07-20=
24 11:37:20","Grid outage // Grid return","MFOUAGUEGUE MATHIEU","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid outage // Gri=
d return","landry.etame@ihstowers.com","259","20-07-2024 10:40:09","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0002653719","A=
wae Escalier","","20-07-2024 10:34:03","20-07-2024 10:28:59","20-07-2024 10=
:46:26","No power issue on site U=3D53,7v site on grid Team Felix/695285353=
/ZTE working on site","Albran Byorel","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53,7v site on grid Team Felix/695285353/ZTE working on site","landry.eta=
me@ihstowers.com","306","20-07-2024 10:34:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_133","IHS_YND_120","NOCINC0002653714","S=
apeur Mimboman","","20-07-2024 10:32:06","20-07-2024 10:25:01","20-07-2024 =
11:30:17","grid outage,gen failed to start due to card ge faulty//Gen manua=
lly started","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","AC=
DG - Control Panel","grid outage,gen failed to start due to card ge faulty/=
/Gen manually started","landry.etame@ihstowers.com","427","20-07-2024 10:32=
:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0002653602","A=
hala","","20-07-2024 10:22:04","20-07-2024 10:17:40","20-07-2024 10:31:15",=
"No power issue on site U=3D54,3v site on grid Team Elorm/657300711/ZTE wor=
king on site ","Hyemafo Gildas","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,3=
v site on grid Team Elorm/657300711/ZTE working on site ","landry.etame@ihs=
towers.com","265","20-07-2024 10:22:04","Sagemcom CMR"
"Closed Complete","Site Down","CTR_129","IHS_YND_036","NOCINC0002653511","A=
cropole","","20-07-2024 10:08:53","20-07-2024 10:00:49","20-07-2024 10:23:0=
4","No power issue on site U=3D53,3v site on grid Team Obioma/673259896/ZTE=
 working on site ","MINKA NICOLAS","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
3,3v site on grid Team Obioma/673259896/ZTE working on site ","landry.etame=
@ihstowers.com","486","20-07-2024 10:08:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_109","IHS_YND_037","NOCINC0002653418","N=
kolndongo","","20-07-2024 09:52:10","20-07-2024 09:49:03","20-07-2024 10:02=
:32","No power issue on site U=3D54,5v site on grid Team Felix/682840951/ZT=
E working on site","MINKA NICOLAS","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
4,5v site on grid Team Felix/682840951/ZTE working on site","landry.etame@i=
hstowers.com","189","20-07-2024 09:52:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0002653404","V=
allee-Bastos OCM","","20-07-2024 09:48:43","20-07-2024 09:45:37","20-07-202=
4 11:27:25","grid outage//MDG 20kva deployed","","Grid Supply","Passive","G=
rid","National Grid - Grid Outage Issue","grid outage//MDG 20kva deployed",=
"landry.etame@ihstowers.com","187","20-07-2024 09:48:43","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0002653285","MVA=
N SACEL","","20-07-2024 09:30:08","20-07-2024 09:20:57","20-07-2024 09:42:0=
4","Active// No power issue on site ,site on Gen  with Ubaie=3D53.5 V TX FM=
E Lionel steve/655184876 from Huawei is informed ","MINKA NICOLAS","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active// No power issue on site ,site on Gen  with Ubaie=3D53.5  TX FME=
 Lionel steve/655184876 from Huawei is informed=20
","denis.mballa@ihstowers.com","552","20-07-2024 09:30:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0002653001","N=
R-Bastos","","20-07-2024 08:58:10","20-07-2024 08:48:07","20-07-2024 10:33:=
57","  Grid outage//MDG of 13  kva has deployed ","","Grid Supply","Passive=
","Grid","National Grid - Grid Outage Issue","  Grid outage//MDG of 13  kva=
 has deployed ","landry.etame@ihstowers.com","605","20-07-2024 08:58:10","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0002652982","M=
EFOU ASSI","","20-07-2024 08:52:19","19-07-2024 18:54:12","20-07-2024 10:30=
:49","site went down due to disjunction of CB 100A in Pwc causing by load o=
f increase//he did a bridge with another CB 80A(site swapped by ZTE)","Fand=
a Brice","Equipment Repair","Passive","Control Panel","Power Cabinet - Circ=
uit Breaker Issue","site went down due to disjunction of CB 100A in Pwc cau=
sing by load of increase//he did a bridge with another CB 80A(site swapped =
by ZTE)","landry.etame@ihstowers.com","50288","20-07-2024 08:52:19","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002652943","B=
ATA-Mokolo","","20-07-2024 08:41:54","20-07-2024 08:33:50","20-07-2024 14:2=
2:04","	Grid Outage No Space to deploy a MDG// Grid Restored   ,,power solv=
ed since 02:22 PM and power reset has been done but the site remain down  R=
M Alain//697424637  from Huawei is informed","","Grid Supply","Passive","Gr=
id","National Grid - Grid Outage Issue","Grid Outage No Space to deploy a M=
DG// Grid Restored   ,,power solved since 02:22 PM and power reset has been=
 done but the site remain down  RM Alain//697424637  from Huawei is informe=
d","landry.etame@ihstowers.com","486","20-07-2024 08:41:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0002652893","H=
-Progres","","20-07-2024 08:24:57","20-07-2024 08:05:51","20-07-2024 14:21:=
12","Grid outage no space to deploy Mobil Gen // Grid power return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
 no space to deploy Mobil Gen // Grid power return","landry.etame@ihstowers=
.com","1147","20-07-2024 08:24:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0002652883","C=
amp-Sic-Tsinga","","20-07-2024 08:23:48","20-07-2024 08:05:43","20-07-2024 =
14:22:01","Grid outage no space to deploy Mobil Gen // Grid power return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid =
outage no space to deploy Mobil Gen // Grid power return","landry.etame@ihs=
towers.com","1090","20-07-2024 08:23:48","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002652866","Sapeur",=
"","20-07-2024 08:17:50","20-07-2024 08:05:01","20-07-2024 14:26:04","Casca=
ded Incident from TTO2462496","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage no space to deploy Mobil Gen=
 // Grid power return","system","769","20-07-2024 08:17:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002652861","E=
-Police","IHS_YND_029","20-07-2024 08:16:19","20-07-2024 08:05:01","20-07-2=
024 14:26:04","Grid outage no space to deploy Mobil Gen // Grid power retur=
n","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","G=
rid outage no space to deploy Mobil Gen // Grid power return","landry.etame=
@ihstowers.com","680","20-07-2024 08:16:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002652529","M=
asque","","20-07-2024 06:53:31","20-07-2024 06:50:26","20-07-2024 07:23:36"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","lan=
dry.etame@ihstowers.com","188","20-07-2024 06:53:31","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002652503","M=
essassi 2","","20-07-2024 06:35:00","20-07-2024 06:32:39","20-07-2024 06:40=
:39","Grid outage site went down because Gen failed to start due to poor ba=
ttery backup//Gen automatically started","Fabrice Pouakam","Equipment Repai=
r","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage sit=
e went down because Gen failed to start due to poor battery backup//Gen aut=
omatically started","landry.etame@ihstowers.com","142","20-07-2024 06:35:00=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0002652501","M=
imboman-Ecole","","20-07-2024 06:33:02","20-07-2024 06:30:55","20-07-2024 0=
7:57:54","Grid outage, site went down because Gen stopped due to low oil pr=
essure alarm// He added oil  and Gen manually started","Mba Lazare Herve","=
Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","Grid outa=
ge, site went down because Gen stopped due to low oil pressure alarm// He a=
dded oil  and Gen manually started","landry.etame@ihstowers.com","127","20-=
07-2024 06:33:02","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002652463","M=
vog-Manga","","20-07-2024 06:17:42","20-07-2024 06:09:37","20-07-2024 09:20=
:43","No power issue on site U=3D53v site on grid Team Bertrand/699670325 /=
ZTE working on site","Albran Byorel","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53v site on grid Team Bertrand/699670325 /ZTE working on site","landry.e=
tame@ihstowers.com","486","20-07-2024 06:17:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002652451","M=
arche Odza","","20-07-2024 06:16:59","20-07-2024 06:13:44","20-07-2024 09:2=
0:43","No power issue on site U=3D54,1v site on grid Lionel adjed of huawei=
 is informed","Albran Byorel","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D54,1v =
site on grid Lionel adjed of huawei is informed","landry.etame@ihstowers.co=
m","197","20-07-2024 06:16:59","Sagemcom CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0002652314","ODZ=
A BORNE 10","","20-07-2024 05:24:39","20-07-2024 05:16:35","20-07-2024 05:2=
7:45","No power issue on site Ubaie =3D53.7V site on Gen The TX FME Lionel =
//655184876// from huawei is informed","Albran Byorel","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue on site Ubaie =3D53.7V site on Gen The TX FME Lionel //655184876// f=
rom huawei is informed","ludivine.ngamaleu@ihstowers.com","484","20-07-2024=
 05:24:39","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0002651849","Kondengu=
i","","20-07-2024 02:26:10","20-07-2024 02:07:39","20-07-2024 09:56:08","Ca=
scaded Incident from TTO2461454","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive"," Grid outage no space to deploy a mob=
il DG // Grid power return","system","1111","20-07-2024 02:26:10","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0002651847","E=
mombo-Tchad","IHS_YND_114","20-07-2024 02:24:57","20-07-2024 02:07:39","20-=
07-2024 09:56:08"," Grid outage no space to deploy a mobil DG // Grid power=
 return","","Grid Supply","Passive","Grid","National Grid - Grid Outage Iss=
ue"," Grid outage no space to deploy a mobil DG // Grid power return","ange=
.kongo@ihstowers.com","1039","20-07-2024 02:24:57","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002651770","Mim=
boman3","","20-07-2024 01:26:18","20-07-2024 01:08:13","20-07-2024 03:14:34=
","Grid outage site went down because Gen started and stopped due to ""high=
 temp"" alarm caused //He added water and Gen manually started","Mba Lazare=
 Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp - =
Coolant Level Issue","Grid outage site went down because Gen started and st=
opped due to ""high temp"" alarm caused //He added water and Gen manually s=
tarted","ludivine.ngamaleu@ihstowers.com","1087","20-07-2024 01:26:18","Sag=
emcom CMR"
"Closed Complete","Warning","CTR_212","IHS_YND_178","NOCINC0002651757","Emo=
mbo","","20-07-2024 01:21:57","","","grid outage, site alarming on battery =
because gen failed to start due to water infiltration in tank// He purged t=
he tank and changed fuel filter","Mba Lazare Herve","Warning","Warning","PO=
WER","Warning - Site on Battery","grid outage, site alarming on battery bec=
ause gen failed to start due to water infiltration in tank// He purged the =
tank and changed fuel filter","alwine.fambou@ihstowers.com","3","20-07-2024=
 01:21:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0002651628","M=
ambine","","20-07-2024 00:30:24","20-07-2024 00:26:17","20-07-2024 00:51:08=
","Grid outage site went down because Gen ran still fuel shortage// Refueli=
ng done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","Gr=
id outage site went down because Gen ran still fuel shortage// Refueling do=
ne","ange.kongo@ihstowers.com","247","20-07-2024 00:30:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002651529","O=
dza II OCM","","19-07-2024 23:44:19","19-07-2024 21:41:10","19-07-2024 22:1=
3:21","SITE went down because The Cb(63*2) of PWC dysjoncted due to over cu=
rrent// He reamed the CB","Albran Byorel","Equipment Repair","Passive","Con=
trol Panel","Power Cabinet - Circuit Breaker Issue","SITE went down because=
 The Cb(63*2) of PWC dysjoncted due to over current// He reamed the CB","an=
ge.kongo@ihstowers.com","7390","19-07-2024 23:44:19","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002651515","Mim=
boman3","","19-07-2024 23:35:41","19-07-2024 23:30:35","19-07-2024 23:49:24=
","Grid outage site went down because Gen failed to start due to poor batte=
ry backup//Gen automatically started","Mba Lazare Herve","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage site =
went down because Gen failed to start due to poor battery backup//Gen autom=
atically started","ludivine.ngamaleu@ihstowers.com","307","19-07-2024 23:35=
:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_479","IHS_YND_580","NOCINC0002651324","M=
arche Odza","","19-07-2024 22:44:57","19-07-2024 22:43:49","20-07-2024 01:3=
3:57","No power issue on site.Site on Grid with Ubaie=3D54.3 V TX FME Lione=
l steve/655184876 from Huawei is informed repetitif issue","Albran Byorel",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V TX FME =
Lionel steve/655184876 from Huawei is informed repetitif issue","ange.kongo=
@ihstowers.com","69","19-07-2024 22:44:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0002651288","E=
toudi 2","","19-07-2024 22:36:14","19-07-2024 22:32:55","20-07-2024 01:29:2=
5","no power issue Ubaie=3D53,8V, site on Grid. the TX  Armand Ngetsa(69994=
9553) from Huawei is informed","Fabrice Pouakam","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue=
 Ubaie=3D53,8V, site on Grid. the TX  Armand Ngetsa(699949553) from Huawei =
is informed","ange.kongo@ihstowers.com","200","19-07-2024 22:36:14","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002651281","E=
TOUDI CHAPELLE","","19-07-2024 22:34:42","19-07-2024 22:32:37","20-07-2024 =
01:45:31","Active//No power issue on site ,site on Grid with Ubaie=3D51,2  =
V The TX Armand Nguetsa(699949553) from Huawei is informed  Repetitif issue=
","Delor Telezing","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active//No power issue on site ,site on Grid=
 with Ubaie=3D51,2  V The TX Armand Nguetsa(699949553) from Huawei is infor=
med  Repetitif issue","ange.kongo@ihstowers.com","127","19-07-2024 22:34:42=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002651266","M=
asque","","19-07-2024 22:27:32","19-07-2024 22:19:13","20-07-2024 01:27:30"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed repetitif issue","Fabrice Pouakam=
","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX =
Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The T=
X FME Eloundou // 693212405// From Huawei is informed repetitif issue","ang=
e.kongo@ihstowers.com","501","19-07-2024 22:27:32","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_765","NOCINC0002651104","MBALNGON=
G LYCEE","","19-07-2024 21:58:10","19-07-2024 20:41:47","19-07-2024 22:32:5=
9","Cascaded Incident from TTO2460135","Fanda Brice","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","site went down because gen failed=
 to start due to grid bad voltage// Gen manually started","system","4583","=
19-07-2024 21:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002651105","Afanoya"=
,"","19-07-2024 21:58:10","19-07-2024 20:41:47","19-07-2024 22:32:59","Casc=
aded Incident from TTO2460135","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because gen failed to s=
tart due to grid bad voltage// Gen manually started","system","4583","19-07=
-2024 21:58:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_767","NOCINC0002651103","ELOUMDEM=
 CARRIERE","","19-07-2024 21:58:10","19-07-2024 20:41:47","19-07-2024 22:32=
:59","Cascaded Incident from TTO2460135","Fanda Brice","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","site went down because gen fail=
ed to start due to grid bad voltage// Gen manually started","system","4583"=
,"19-07-2024 21:58:10","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002650725","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","19-07-2024 20:57:57","19-07-20=
24 20:20:53","19-07-2024 22:35:58","site went down because gen failed to st=
art due to grid bad voltage// Gen manually started","Hyemafo Gildas","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","site we=
nt down because gen failed to start due to grid bad voltage// Gen manually =
started","dorothy.djantio@ihstowers.com","7934","19-07-2024 20:57:57","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002650293","M=
asque","","19-07-2024 19:35:24","19-07-2024 19:17:14","19-07-2024 19:27:28"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FME Elound=
ou // 693212405// From Huawei is informed,site up at ","Fabrice Pouakam","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V The TX FM=
E Eloundou // 693212405// From Huawei is informed,site up at ","etienne.ito=
ndo@ihstowers.com","1093","19-07-2024 19:35:24","Sagemcom CMR"
"Closed Complete","Site Down","T3220","IHS_YND_765","NOCINC0002650049","MBA=
LNGONG LYCEE","","19-07-2024 19:05:47","19-07-2024 18:43:44","19-07-2024 19=
:09:24","","Fanda Brice","Cascade Outage","Passive","Cascade Passive","Casc=
ade Passive","site went down because gen failed to start due to grid bad vo=
ltage// Gen manually started","dorothy.djantio@ihstowers.com","3006","19-07=
-2024 19:05:47","Sagemcom CMR"
"Closed Complete","Site Down","T3232","IHS_YND_767","NOCINC0002649995","ELO=
UMDEM CARRIERE","","19-07-2024 19:03:54","19-07-2024 18:43:44","19-07-2024 =
19:09:24","site went down because gen failed to start due to grid bad volta=
ge// Gen manually started","Fanda Brice","Cascade Outage","Passive","Cascad=
e Passive","Cascade Passive","site went down because gen failed to start du=
e to grid bad voltage// Gen manually started","dorothy.djantio@ihstowers.co=
m","2977","19-07-2024 19:03:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002649978","Afanoya"=
,"","19-07-2024 19:02:20","19-07-2024 18:43:44","19-07-2024 19:09:24","Casc=
aded Incident from TTO2459291","Hyemafo Gildas","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down because gen failed to s=
tart due to grid bad voltage// Gen manually started","system","1116","19-07=
-2024 19:02:20","Sagemcom CMR"
"Closed Complete","Site Down","T0403","IHS_YND_257","NOCINC0002649952","Aha=
la","IHS_YND_767, IHS_YND_765, IHS_YND_313","19-07-2024 18:59:58","19-07-20=
24 18:43:44","19-07-2024 19:09:24","site went down because gen failed to st=
art due to grid bad voltage// Gen manually started","Hyemafo Gildas","Grid =
Supply","Passive","Grid","National Grid - Phase Controller Faulty","site we=
nt down because gen failed to start due to grid bad voltage// Gen manually =
started","dorothy.djantio@ihstowers.com","976","19-07-2024 18:59:58","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_528","NOCINC0002648842","MEHANDAN=
","","19-07-2024 18:07:10","19-07-2024 17:29:56","19-07-2024 19:53:38","Cas=
caded Incident from TTO2458107","Albran Byorel","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","site went down due to disjunction Cb(2=
*80A) in PWC// He reamed Cb(2*80A), site on grid (Site Swapped by ZTE)","sy=
stem","2234","19-07-2024 18:07:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002648838","O=
dza II OCM","IHS_YND_528","19-07-2024 18:06:05","19-07-2024 17:29:56","19-0=
7-2024 19:53:38","site went down due to disjunction Cb(2*80A) in PWC// He r=
eamed Cb(2*80A), site on grid (Site Swapped by ZTE)","Albran Byorel","Equip=
ment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Iss=
ue","site went down due to disjunction Cb(2*80A) in PWC// He reamed Cb(2*80=
A), site on grid (Site Swapped by ZTE)","etienne.itondo@ihstowers.com","217=
2","19-07-2024 18:06:05","Sagemcom CMR"
"Closed Complete","Site Down","CTR_259","IHS_YND_169","NOCINC0002648787","E=
koumdoum","","19-07-2024 17:59:36","19-07-2024 17:27:29","19-07-2024 17:37:=
53","No power issue on site ,site on Grid with Ubaie=3D 52,9 V The Team DON=
GMO//: 696947669 from ZTE is working on site","Albran Byorel","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","N=
o power issue on site ,site on Grid with Ubaie=3D 52,9 V The Team DONGMO//:=
 696947669 from ZTE is working on site","etienne.itondo@ihstowers.com","192=
8","19-07-2024 17:59:36","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002648605","Jou=
vence 2000","","19-07-2024 17:31:01","19-07-2024 17:11:55","19-07-2024 17:2=
6:31","  Grid outage,Gen  failed to start  due to poor battery back up  and=
 grid contactor did not excited// He excited grid contactor and site on gri=
d ","Delor Telezing","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Battery Low","  Grid outage,Gen  failed to start  due to poor batte=
ry back up  and grid contactor did not excited// He excited grid contactor =
and site on grid ","dorothy.djantio@ihstowers.com","1147","19-07-2024 17:31=
:01","Sagemcom CMR"
"Closed Complete","Site Down","T1236","IHS_YND_793","NOCINC0002648465","Elo=
umdem stade","","19-07-2024 16:59:13","19-07-2024 16:54:03","20-07-2024 01:=
41:11"," ""Active// no power issue on site ,site on Gen  with Ubaie=3D55,4V=
 The Tx FME  Etienne  (695033981)   from Hauawei  is informed,","Fanda Bric=
e","Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX=
 Fault Alarm"," ""Active// no power issue on site ,site on Gen  with Ubaie=
=3D55,4V The Tx FME  Etienne  (695033981)   from Hauawei  is informed,","do=
rothy.djantio@ihstowers.com","311","19-07-2024 16:59:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_310","IHS_YND_057","NOCINC0002648116","M=
volye-New","","19-07-2024 16:01:10","19-07-2024 13:03:01","19-07-2024 16:13=
:15"," No power issue on site ,site on Grid with Ubaie=3D 53,6 V The Team C=
LAVIS//: 650031080 from ZTE is working on site","","Customer Equipment Fail=
ure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No power is=
sue on site ,site on Grid with Ubaie=3D 53,6 V The Team CLAVIS//: 650031080=
 from ZTE is working on site","etienne.itondo@ihstowers.com","10691","19-07=
-2024 16:01:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002648070","M=
vog-Manga","","19-07-2024 15:52:40","19-07-2024 15:05:33","19-07-2024 15:15=
:00"," No power issue on site ,site on Grid with Ubaie=3D 53,6 V The Team F=
ranck//: 686650915 from ZTE is working on site","Albran Byorel","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
" No power issue on site ,site on Grid with Ubaie=3D 53,6 V The Team Franck=
//: 686650915 from ZTE is working on site","etienne.itondo@ihstowers.com","=
2829","19-07-2024 15:52:40","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002647912","Jou=
vence 2000","","19-07-2024 15:32:52","19-07-2024 15:29:44","19-07-2024 16:3=
2:42","  Grid outage,Gen  failed to start  due to poor battery back up  and=
 grid contactor did not excited// He excited grid contactor and site on gri=
d","Delor Telezing","Equipment Repair","Passive","Control Panel","Power Cab=
inet - Battery Low","  Grid outage,Gen  failed to start  due to poor batter=
y back up  and grid contactor did not excited// He excited grid contactor a=
nd site on grid","dorothy.djantio@ihstowers.com","189","19-07-2024 15:32:52=
","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002647701","NKO=
MEKUI OCM","","19-07-2024 15:18:46","19-07-2024 15:02:38","19-07-2024 15:10=
:25","Grid outage, site wen down because gen failed to start due to poor ba=
ttery backup // Gen start automatically","TIENTCHEU NZETCHIEU GAEL","Equipm=
ent Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid o=
utage, site wen down because gen failed to start due to poor battery backup=
 // Gen start automatically","etienne.itondo@ihstowers.com","970","19-07-20=
24 15:18:46","Sagemcom CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0002647609","Ang=
uissa New","","19-07-2024 15:02:18","19-07-2024 14:54:10","19-07-2024 15:21=
:43","site went down due to PWC Overload and Cb of rectifier disjuncted // =
He reamed Cb rectifier, site on grid(PWC to be replace)","MINKA NICOLAS","E=
quipment Repair","Passive","Rectifier","Rectifier Module Overloaded","site =
went down due to PWC Overload and Cb of rectifier disjuncted // He reamed C=
b rectifier, site on grid(PWC to be replace)","dorothy.djantio@ihstowers.co=
m","4303","19-07-2024 15:02:18","Sagemcom CMR"
"Closed Complete","Site Down","T1871","IHS_YND_292","NOCINC0002647566","Bit=
oto","","19-07-2024 14:55:57","19-07-2024 14:51:49","19-07-2024 14:58:53","=
Site went down due to insufficiency of rectifiers//Site up, rectifiers must=
 be added. ","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","R=
ectifier Module","Site went down due to insufficiency of rectifiers//Site u=
p, rectifiers must be added. ","dorothy.djantio@ihstowers.com","250","19-07=
-2024 14:55:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0002647386","E=
koumdoum OCM","","19-07-2024 14:14:12","19-07-2024 13:49:45","19-07-2024 14=
:50:28"," No power issue on site ,site on Grid with Ubaie=3D 52,9 V The Tea=
m DONGMO//: 696947669 from ZTE is working on site","Albran Byorel","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m"," No power issue on site ,site on Grid with Ubaie=3D 52,9 V The Team DON=
GMO//: 696947669 from ZTE is working on site","kamga.virgile@ihstowers.com"=
,"1469","19-07-2024 14:14:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_240","IHS_YND_021","NOCINC0002646772","C=
-Supreme","","19-07-2024 12:31:05","19-07-2024 11:43:45","19-07-2024 13:17:=
42","No power issue on site U=3D54v site on grid Brice Tsague of Huawei is =
informed","","Customer Equipment Failure","Active","Active Equipment Failur=
e","BTS/TX Fault Alarm","No power issue on site U=3D54v site on grid Brice =
Tsague of Huawei is informed","kamga.virgile@ihstowers.com","2842","19-07-2=
024 12:31:05","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0002646620","Anguissa=
 New","","19-07-2024 12:19:20","19-07-2024 11:35:00","19-07-2024 12:22:06",=
"Cascaded Incident from TTO2455616","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage no space to deploy  am=
 mobil Gen//Grid power return","system","2660","19-07-2024 12:19:20","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0002646607","L=
abogenie","IHS_YND_568","19-07-2024 12:16:14","19-07-2024 11:35:00","19-07-=
2024 12:22:06","Grid outage no space to deploy  a mobil Gen//Grid power ret=
urn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue",=
"Grid outage no space to deploy  a mobil Gen//Grid power return","kamga.vir=
gile@ihstowers.com","2478","19-07-2024 12:16:14","Sagemcom CMR"
"Closed Complete","Site Down","T1743","IHS_YND_150","NOCINC0002646289","Nko=
l-Mbanda","","19-07-2024 11:44:44","19-07-2024 11:23:59","19-07-2024 11:55:=
59","No power issue on site ,site on Grid with Ubaie=3D54,5 V The Team Step=
hen//: 694946479 from ZTE is working on site(Site went down at MTN due to w=
ork ZTE in site )","MINKA NICOLAS","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site ,site=
 on Grid with Ubaie=3D54,5 V The Team Stephen//: 694946479 from ZTE is work=
ing on site(Site went down at MTN due to work ZTE in site )","alexandre.kam=
al@ihstowers.com","3960","19-07-2024 11:44:44","Sagemcom CMR"
"Closed Complete","Site Down","T1749","IHS_YND_175","NOCINC0002646278","Nko=
mo","","19-07-2024 11:42:21","19-07-2024 11:25:17","19-07-2024 12:10:22","g=
rid outage,gen stopped with alarm low oil pressure//he added oil and starte=
d the gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG=
 - Low Oil Pressure","grid outage,gen stopped with alarm low oil pressure//=
he added oil and started the gen","alexandre.kamal@ihstowers.com","4566","1=
9-07-2024 11:42:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0002645892","S=
tade-Abega","","19-07-2024 11:07:31","19-07-2024 10:51:07","19-07-2024 11:2=
1:01","grid outage,gen stopped with alarm low oil pressure//he added oil an=
d started the gen","Mba Lazare Herve","Equipment Repair","Passive","ACDG Ge=
n","ACDG - Low Oil Pressure","grid outage,gen stopped with alarm low oil pr=
essure//he added oil and started the gen","kamga.virgile@ihstowers.com","98=
4","19-07-2024 11:07:31","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_407","NOCINC0002645716","Monatele=
 MTN","","19-07-2024 10:38:50","19-07-2024 10:25:59","19-07-2024 10:30:38",=
"Cascaded Incident from TTO2454622","Parker Tchoup","Cascade Outage","Activ=
e","Cascade Active","Cascade Active","Active//No power issue on site ,site =
on Grid with Ubaie=3D53,6 V TX FME Gregoire(654547479)from Huawei is inform=
ed,Site up at 10:34 AM","system","771","19-07-2024 10:38:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_387","NOCINC0002645715","Talla Mo=
natele","","19-07-2024 10:38:50","19-07-2024 10:25:59","19-07-2024 10:30:38=
","Cascaded Incident from TTO2454622","Parker Tchoup","Cascade Outage","Act=
ive","Cascade Active","Cascade Active","Active//No power issue on site ,sit=
e on Grid with Ubaie=3D53,6 V TX FME Gregoire(654547479)from Huawei is info=
rmed,Site up at 10:34 AM","system","771","19-07-2024 10:38:50","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_073","IHS_YND_406","NOCINC0002645705","M=
onatele","IHS_YND_387, IHS_YND_407","19-07-2024 10:36:44","19-07-2024 10:25=
:59","19-07-2024 10:30:38","Active//No power issue on site ,site on Grid wi=
th Ubaie=3D53,6 V TX FME Gregoire(654547479)from Huawei is informed,Site up=
 at 10:34 AM","Parker Tchoup","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","Active//No power issue on site ,s=
ite on Grid with Ubaie=3D53,6 V TX FME Gregoire(654547479)from Huawei is in=
formed,Site up at 10:34 AM","kamga.virgile@ihstowers.com","647","19-07-2024=
 10:36:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_661","IHS_YND_067","NOCINC0002645518","N=
koa Ayos","","19-07-2024 10:04:13","18-07-2024 10:45:54","19-07-2024 10:28:=
50","No power issue on site U=3D56,3v site on grid Team David/650753280/ZTE=
 working on site ","MINKA NICOLAS","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
6,3v site on grid Team David/650753280/ZTE working on site ","marie.kwin@ih=
stowers.com","83902","19-07-2024 10:04:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_647","IHS_YND_684","NOCINC0002645513","E=
kie sud","","19-07-2024 10:02:14","18-07-2024 10:45:52","19-07-2024 10:19:3=
5","Active//No power issue on site ,site on Gen with Ubaie=3D53 V The Team =
NSHOM//69537897 from ZTE is working on site","Albran Byorel","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue on site ,site on Gen with Ubaie=3D53 V The Team NSHOM/=
/69537897 from ZTE is working on site","marie.kwin@ihstowers.com","83783","=
19-07-2024 10:02:14","Sagemcom CMR"
"Closed Complete","Warning","CTR_315","IHS_YND_292","NOCINC0002645462","Bit=
oto","","19-07-2024 09:54:23","","","site alarming due to insufisane of rec=
tifier // added rectifier ongoing","Mba Lazare Herve","Warning","Warning","=
POWER","Warning - Site on Battery","site alarming due to insufisane of rect=
ifier // added rectifier ongoing","ludovic.tchagna@ihstowers.com","3","19-0=
7-2024 09:54:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002645300","E=
TOUDI CHAPELLE","","19-07-2024 09:13:00","19-07-2024 07:02:40","19-07-2024 =
07:06:13","Active//No power issue on site ,site on Grid with Ubaie=3D51,2  =
V The TX Armand Nguetsa(699949553) from Huawei is informed .","Delor Telezi=
ng","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue on site ,site on Grid with Ubaie=3D5=
1,2  V The TX Armand Nguetsa(699949553) from Huawei is informed .
","marie.kwin@ihstowers.com","7822","19-07-2024 09:13:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0002645254","C=
omplexe-BEAC","","19-07-2024 09:01:23","18-07-2024 19:57:28","18-07-2024 19=
:59:27","Active//No power issue on site ,site on Grid with Ubaie=3D54,9 V T=
he Team  ADIGONO// 677513091 from ZTE is working on site","Albran Byorel","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site ,site on Grid with Ubaie=3D54,9 V=
 The Team  ADIGONO// 677513091 from ZTE is working on site","kamga.virgile@=
ihstowers.com","47036","19-07-2024 09:01:23","Sagemcom CMR"
"Closed Complete","Site Down","T0373","IHS_YND_097","NOCINC0002644573","Kon=
dengui MTN","","19-07-2024 06:11:52","19-07-2024 06:09:46","19-07-2024 08:1=
8:00","Grid outage site went down because Gen ran still fuel shortage// Ref=
ueling done","Albran Byorel","Fuel Outage","Passive","Diesel","Diesel Outag=
e","Grid outage site went down because Gen ran still fuel shortage// Refuel=
ing done","joelle.ekessi@ihstowers.com","127","19-07-2024 06:11:52","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0002644496","N=
sam Sofavinc T0","","19-07-2024 05:44:43","18-07-2024 21:33:29","19-07-2024=
 05:48:49","site went down due to CB 125 A disjuncted in Pwc//he made a bri=
dge with another CB 50A(site already swapped by ZTE)","MINKA NICOLAS","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Circuit Breaker Is=
sue","site went down due to CB 125 A disjuncted in Pwc//he made a bridge wi=
th another CB 50A(site already swapped by ZTE)","emmanuel.ghani@ihstowers.c=
om","29475","19-07-2024 05:44:43","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_127","NOCINC0002643795","Tsinga",=
"","19-07-2024 02:22:30","19-07-2024 02:13:33","19-07-2024 03:10:15","Casca=
ded Incident from TTO2452478 - Cascade Removed From TTO2452478","Mboua Thie=
rry","Cascade Outage","Active","Cascade Active","Cascade Active","Active//N=
o power issue on site.Site on Grid with Ubaie=3D54,8 V  The  TX fme BRICE/6=
50214096 of Huawei is informed.","system","537","19-07-2024 02:22:30","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_087","NOCINC0002643794","Camp-Sic=
-Tsinga","","19-07-2024 02:22:30","19-07-2024 02:13:33","19-07-2024 03:10:1=
5","Cascaded Incident from TTO2452478 - Cascade Removed From TTO2452478",""=
,"Cascade Outage","Active","Cascade Active","Cascade Active","Active//No po=
wer issue on site.Site on Grid with Ubaie=3D54,8 V  The  TX fme BRICE/65021=
4096 of Huawei is informed.","system","537","19-07-2024 02:22:30","Sagemcom=
 CMR"
"Closed Complete","Site Down","","IHS_YND_008","NOCINC0002643789","CNDH","I=
HS_YND_220, IHS_YND_126, IHS_YND_563, IHS_YND_010, IHS_YND_028, IHS_YND_087=
, IHS_YND_127","19-07-2024 02:22:30","19-07-2024 02:13:33","19-07-2024 03:3=
0:15","Active//No power issue on site.Site on Grid with Ubaie=3D54,8 V  The=
  TX fme BRICE/650214096 of Huawei is informed.","Paul BIBOUM","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active//No power issue on site.Site on Grid with Ubaie=3D54,8 V  The  TX fm=
e BRICE/650214096 of Huawei is informed.","system","537","19-07-2024 02:22:=
30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_028","NOCINC0002643793","H-Centra=
l","","19-07-2024 02:22:30","19-07-2024 02:13:33","19-07-2024 03:10:15","Ca=
scaded Incident from TTO2452478 - Cascade Removed From TTO2452478","Paul BI=
BOUM","Cascade Outage","Active","Cascade Active","Cascade Active","Active//=
No power issue on site.Site on Grid with Ubaie=3D54,8 V  The  TX fme BRICE/=
650214096 of Huawei is informed.","system","537","19-07-2024 02:22:30","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0002643791","Bastos B=
ethesda","","19-07-2024 02:22:30","19-07-2024 02:13:33","19-07-2024 03:10:1=
5","Cascaded Incident from TTO2452478 - Cascade Removed From TTO2452478","M=
boua Thierry","Cascade Outage","Active","Cascade Active","Cascade Active","=
Active//No power issue on site.Site on Grid with Ubaie=3D54,8 V  The  TX fm=
e BRICE/650214096 of Huawei is informed.","system","537","19-07-2024 02:22:=
30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_220","NOCINC0002643790","Golf Qua=
ter","","19-07-2024 02:22:30","19-07-2024 02:13:33","19-07-2024 03:10:15","=
Cascaded Incident from TTO2452478 - Cascade Removed From TTO2452478","Mboua=
 Thierry","Cascade Outage","Active","Cascade Active","Cascade Active","Acti=
ve//No power issue on site.Site on Grid with Ubaie=3D54,8 V  The  TX fme BR=
ICE/650214096 of Huawei is informed.","system","537","19-07-2024 02:22:30",=
"Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_010","NOCINC0002643792","CNR","",=
"19-07-2024 02:22:30","19-07-2024 02:13:33","19-07-2024 03:10:15","Cascaded=
 Incident from TTO2452478 - Cascade Removed From TTO2452478","Mboua Thierry=
","Cascade Outage","Active","Cascade Active","Cascade Active","Active//No p=
ower issue on site.Site on Grid with Ubaie=3D54,8 V  The  TX fme BRICE/6502=
14096 of Huawei is informed.","system","537","19-07-2024 02:22:30","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_198","IHS_YND_126","NOCINC0002643780","B=
astos-Nylon","","19-07-2024 02:17:42","19-07-2024 02:13:33","19-07-2024 04:=
55:15","Active//No power issue on site.Site on Grid with Ubaie=3D54,8 V  Th=
e  TX fme BRICE/650214096 of Huawei is informed.","Mboua Thierry","Cascade =
Outage","Active","Cascade Active","Cascade Active","Active//No power issue =
on site.Site on Grid with Ubaie=3D54,8 V  The  TX fme BRICE/650214096 of Hu=
awei is informed.","emmanuel.ghani@ihstowers.com","250","19-07-2024 02:17:4=
2","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0002643179","Boumnyeb=
el","","19-07-2024 00:38:00","19-07-2024 00:34:20","19-07-2024 00:37:21","C=
ascaded Incident from TTO2451816","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site wen down because=
 gen failed to start due to poor battery backup // Gen start automatically"=
,"system","220","19-07-2024 00:38:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0002643180","Mamb",""=
,"19-07-2024 00:38:00","19-07-2024 00:34:20","19-07-2024 00:37:21","Cascade=
d Incident from TTO2451816","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site wen down because gen f=
ailed to start due to poor battery backup // Gen start automatically","syst=
em","220","19-07-2024 00:38:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0002643178","Ngog Map=
ubi","","19-07-2024 00:38:00","19-07-2024 00:34:20","19-07-2024 00:37:21","=
Cascaded Incident from TTO2451816","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site wen down becaus=
e gen failed to start due to poor battery backup // Gen start automatically=
","system","220","19-07-2024 00:38:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0002643176","B=
oumnyebel OCM","IHS_YND_419, IHS_YND_381, IHS_YND_376","19-07-2024 00:36:27=
","19-07-2024 00:34:20","19-07-2024 00:37:21","Grid outage, site wen down b=
ecause gen failed to start due to poor battery backup // Gen start automati=
cally","Kemeni Franklin","Equipment Repair","Passive","Control Panel","Powe=
r Cabinet - Battery Low","Grid outage, site wen down because gen failed to =
start due to poor battery backup // Gen start automatically","emmanuel.ghan=
i@ihstowers.com","130","19-07-2024 00:36:27","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0002643148","M=
efou-Assi","","19-07-2024 00:18:46","18-07-2024 20:55:29","19-07-2024 03:55=
:20","Active//No power issue on site ,Site on Grid  with Ubaie=3D53,5 V The=
 RM TX Alain (691144423) from Huawei informed","Fanda Brice","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive//No power issue on site ,Site on Grid  with Ubaie=3D53,5 V The RM TX A=
lain (691144423) from Huawei informed","emmanuel.ghani@ihstowers.com","1219=
9","19-07-2024 00:18:46","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0002643102","MVA=
N SACEL","","19-07-2024 00:07:38","19-07-2024 00:02:33","19-07-2024 01:41:4=
0","Active// No power issue on site ,site on Gen  with Ubaie=3D53,4 V TX FM=
E Lionel steve/655184876 from Huawei is informed","MINKA NICOLAS","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power issue on site ,site on Gen  with Ubaie=3D53,4 V TX FME=
 Lionel steve/655184876 from Huawei is informed","joelle.ekessi@ihstowers.c=
om","307","19-07-2024 00:07:38","Sagemcom CMR"
"Closed Complete","Site Down","LIT_499","IHS_EDA_056","NOCINC0002643074","N=
dogbessol","","19-07-2024 00:05:14","19-07-2024 00:00:47","19-07-2024 00:55=
:43","ACTIVE //No power issue site on Battery  with U=3D52,4 V The Tx FME  =
Etienne  (695033981)   from Hauawei  is informed,(site down Impacted by Som=
bo MTN)","Kemeni Franklin","Customer Equipment Failure","Active","Active Eq=
uipment Failure","BTS/TX Fault Alarm","ACTIVE //No power issue site on Batt=
ery  with U=3D52,4 V The Tx FME  Etienne  (695033981)   from Hauawei  is in=
formed,(site down Impacted by Sombo MTN)","emmanuel.ghani@ihstowers.com","2=
68","19-07-2024 00:05:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002642617","M=
asque","","18-07-2024 22:14:24","18-07-2024 21:55:16","18-07-2024 21:58:12"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V  The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue//site up at =
10:14 PM","Fabrice Pouakam","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site.Site on Grid=
 with Ubaie=3D54.3 V  The TX FME  Eloundou // 693212405// From  Huawei is i=
nformed. Repetitive issue//site up at 10:14 PM","ange.kongo@ihstowers.com",=
"1149","18-07-2024 22:14:24","Sagemcom CMR"
"Closed Complete","Site Down","T0601","IHS_YND_098","NOCINC0002642395","Eko=
unou","","18-07-2024 21:39:36","18-07-2024 20:21:29","18-07-2024 20:25:10",=
"Active// No power issue on site ,site on Gen  with Ubaie=3D53,4 V TX FME L=
ionel steve/655184876 from Huawei is informed","Albran Byorel","Customer Eq=
uipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","=
Active// No power issue on site ,site on Gen  with Ubaie=3D53,4 V TX FME Li=
onel steve/655184876 from Huawei is informed","ludivine.ngamaleu@ihstowers.=
com","4688","18-07-2024 21:39:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0002642306","M=
EFOU ASSI","","18-07-2024 21:23:10","18-07-2024 19:25:47","18-07-2024 19:30=
:02","Active// No power issue on site ,site on Grid  with Ubaie=3D53,6 V TX=
 FME Lionel steve/655184876 from Huawei is informed","Fanda Brice","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active// No power issue on site ,site on Grid  with Ubaie=3D53,6 V TX F=
ME Lionel steve/655184876 from Huawei is informed","ange.kongo@ihstowers.co=
m","7044","18-07-2024 21:23:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0002642296","C=
omplexe-BEAC","","18-07-2024 21:21:33","18-07-2024 19:57:22","18-07-2024 19=
:57:23","Active// No power issue on site ,site on Gen  with Ubaie=3D52,5 V =
TX FME Lionel steve/655184876 from Huawei is informed","Albran Byorel","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active// No power issue on site ,site on Gen  with Ubaie=3D52,5 V T=
X FME Lionel steve/655184876 from Huawei is informed","ange.kongo@ihstowers=
.com","5052","18-07-2024 21:21:33","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002642268","Mim=
boman3","","18-07-2024 21:14:19","18-07-2024 21:10:14","18-07-2024 21:28:13=
","Active// No power issue on site ,site on Gen  with Ubaie=3D53,4 V TX FME=
 Lionel steve/655184876 from Huawei is informed","Mba Lazare Herve","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active// No power issue on site ,site on Gen  with Ubaie=3D53,4 V TX F=
ME Lionel steve/655184876 from Huawei is informed","ludivine.ngamaleu@ihsto=
wers.com","247","18-07-2024 21:14:19","Sagemcom CMR"
"Closed Complete","Site Down","T1862","IHS_YND_510","NOCINC0002642190","MVA=
N SACEL","","18-07-2024 21:02:22","18-07-2024 20:58:15","18-07-2024 21:20:2=
5","Active// No power issue on site ,site on Gen  with Ubaie=3D53,4 V TX FM=
E Lionel steve/655184876 from Huawei is informed","MINKA NICOLAS","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active// No power issue on site ,site on Gen  with Ubaie=3D53,4 V TX FME=
 Lionel steve/655184876 from Huawei is informed","ludivine.ngamaleu@ihstowe=
rs.com","250","18-07-2024 21:02:22","Sagemcom CMR"
"Closed Complete","Site Down","T1316","IHS_YND_111","NOCINC0002641937","Ess=
os Marche","","18-07-2024 20:18:26","18-07-2024 20:15:19","18-07-2024 20:20=
:17","no power issue Ubaie=3D53,6V, site on Gen. the TX  Armand Ngetsa(6999=
49553) from Huawei is informed","Delor Telezing","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue=
 Ubaie=3D53,6V, site on Gen. the TX  Armand Ngetsa(699949553) from Huawei i=
s informed","ludivine.ngamaleu@ihstowers.com","189","18-07-2024 20:18:26","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_477","IHS_YND_566","NOCINC0002641912","C=
rf Cornier","","18-07-2024 20:11:30","18-07-2024 20:06:24","18-07-2024 20:0=
6:25","No power issue on site U=3D 54,5V site on Grid tx fme Lionel / 69469=
3436 from huawei is Informed.","MINKA NICOLAS","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue o=
n site U=3D 54,5V site on Grid tx fme Lionel / 694693436 from huawei is Inf=
ormed.","ange.kongo@ihstowers.com","308","18-07-2024 20:11:30","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0002641516","G=
SO","","18-07-2024 18:43:54","18-07-2024 18:34:49","18-07-2024 18:34:50","N=
o power issue on site U=3D 54,5V site on Grid tx fme Lionel / 694693436 fro=
m huawei is Informed.","MINKA NICOLAS","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D 54,5V site on Grid tx fme Lionel / 694693436 from huawei is Informed.",=
"ange.kongo@ihstowers.com","546","18-07-2024 18:43:54","Sagemcom CMR"
"Closed Complete","Site Down","CTR_269","IHS_YND_098","NOCINC0002641415","E=
kounou","","18-07-2024 18:26:37","18-07-2024 17:56:27","18-07-2024 19:02:27=
","Grid fluctuation stie went down because Gen failed to start due to Grid =
bad voltage// He bypass the Grid and site on Gen","Albran Byorel","Grid Sup=
ply","Passive","Grid","National Grid - Phase Controller Faulty","Grid fluct=
uation stie went down because Gen failed to start due to Grid bad voltage//=
 He bypass the Grid and site on Gen","ange.kongo@ihstowers.com","1811","18-=
07-2024 18:26:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_075","IHS_YND_133","NOCINC0002641385","E=
lig-Edzoa","","18-07-2024 18:20:00","18-07-2024 17:09:47","18-07-2024 18:53=
:47","grid outage//grid return","","Grid Supply","Passive","Grid","National=
 Grid - Grid Outage Issue","grid outage//grid return","ange.kongo@ihstowers=
.com","4214","18-07-2024 18:20:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_639","IHS_YND_157","NOCINC0002641217","M=
VAN","","18-07-2024 17:33:19","18-07-2024 16:24:10","18-07-2024 16:24:11","=
No power issue on site U=3D 50,7V site on Grid, FME TX   Feudjio Andre // 6=
97609283 from Service ZTE  working on site.","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site U=3D 50,7V site on Grid, FME TX   Feudjio Andre // 697=
609283 from Service ZTE  working on site.","ange.kongo@ihstowers.com","4152=
","18-07-2024 17:33:19","Sagemcom CMR"
"Closed Complete","Site Down","CTR_622","IHS_YND_535","NOCINC0002641177","A=
wae Ewonkan","","18-07-2024 17:19:07","18-07-2024 11:53:47","19-07-2024 03:=
55:47","No power issue site on grid with U=3D54.5v .Lionnel Tchatchou(69469=
3436) from Huawei is informed","Albran Byorel","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue s=
ite on grid with U=3D54.5v .Lionnel Tchatchou(694693436) from Huawei is inf=
ormed","marie.kwin@ihstowers.com","19522","18-07-2024 17:19:07","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0002641108","A=
bang","","18-07-2024 17:03:57","18-07-2024 17:00:49","18-07-2024 17:10:07",=
"Active: no power issue, site is on Grid with Ubaie=3D54,9V, Tijani Ismael =
( 678631637) from ZTE working on site","Mba Lazare Herve","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Activ=
e: no power issue, site is on Grid with Ubaie=3D54,9V, Tijani Ismael ( 6786=
31637) from ZTE working on site","ange.kongo@ihstowers.com","190","18-07-20=
24 17:03:57","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0002641068","Bri=
quetterie","","18-07-2024 16:53:21","18-07-2024 16:47:17","18-07-2024 17:00=
:37","Grid outage.no space to deploy mobile gen// grid power return","","Gr=
id Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outag=
e.no space to deploy mobile gen// grid power return","ludivine.ngamaleu@ihs=
towers.com","366","18-07-2024 16:53:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_274","IHS_YND_116","NOCINC0002641015","S=
tade-Abega","","18-07-2024 16:47:36","18-07-2024 16:30:18","18-07-2024 16:3=
5:48","Active: no power issue, site is on Grid with Ubaie=3D54,9V, musa ( 6=
87648830) from ZTE working on site","Mba Lazare Herve","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: =
no power issue, site is on Grid with Ubaie=3D54,9V, musa ( 687648830) from =
ZTE working on site","ange.kongo@ihstowers.com","1040","18-07-2024 16:47:36=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002641008","E=
TOUDI CHAPELLE","","18-07-2024 16:45:04","18-07-2024 16:27:55","18-07-2024 =
16:35:04","no power issue Ubaie=3D51V, site on GRID. the TX  Armand Ngetsa(=
699949553) from Huawei is informed","Delor Telezing","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power i=
ssue Ubaie=3D51V, site on GRID. the TX  Armand Ngetsa(699949553) from Huawe=
i is informed","ange.kongo@ihstowers.com","1030","18-07-2024 16:45:04","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0002640997","E=
toudi 2","","18-07-2024 16:39:18","18-07-2024 16:27:28","18-07-2024 16:30:2=
6","no power issue Ubaie=3D53.8V, site on GRID. the TX  Armand Ngetsa(69994=
9553) from Huawei is informed","Fabrice Pouakam","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","no power issue=
 Ubaie=3D53.8V, site on GRID. the TX  Armand Ngetsa(699949553) from Huawei =
is informed","ange.kongo@ihstowers.com","711","18-07-2024 16:39:18","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0002640712","A=
fanoya","","18-07-2024 15:34:41","18-07-2024 15:12:33","18-07-2024 19:54:36=
","Active :No power issue on site , Ubaie=3D54.4V site On Grid The RM ALAIN=
/691144423/ from Huawei is informed","Hyemafo Gildas","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active :N=
o power issue on site , Ubaie=3D54.4V site On Grid The RM ALAIN/691144423/ =
from Huawei is informed","ange.kongo@ihstowers.com","1329","18-07-2024 15:3=
4:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_285","IHS_YND_099","NOCINC0002640500","E=
kie-Elegance","","18-07-2024 14:59:29","18-07-2024 14:50:21","18-07-2024 14=
:55:58","Active: no power issue, site is on Grid with Ubaie=3D52,5V, MBAKOP=
 Emmadith( 6 73 12 82 80) from ZTE working on site","Albran Byorel","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","Active: no power issue, site is on Grid with Ubaie=3D52,5V, MBAKOP Emm=
adith( 6 73 12 82 80) from ZTE working on site","alwine.fambou@ihstowers.co=
m","550","18-07-2024 14:59:29","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_737","NOCINC0002640414","Eto koss=
 Yde","","18-07-2024 14:46:00","18-07-2024 14:37:33","18-07-2024 14:50:14",=
"Cascaded Incident from TTO2448626","Fanda Brice","Cascade Outage","Active"=
,"Cascade Active","Cascade Active","Active: no power issue, site is on Gen =
with Ubaie=3D53,1V, Steve( 691144395) from ZTE working on site","system","5=
07","18-07-2024 14:46:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_768","NOCINC0002640409","ELOUMDEM=
 CARRIERE 2","","18-07-2024 14:43:40","18-07-2024 14:37:33","18-07-2024 14:=
50:14","Cascaded Incident from TTO2448626","Fanda Brice","Cascade Outage","=
Active","Cascade Active","Cascade Active","Active: no power issue, site is =
on Gen with Ubaie=3D53,1V, Steve( 691144395) from ZTE working on site","sys=
tem","367","18-07-2024 14:43:40","Sagemcom CMR"
"Closed Complete","Site Down","T1550","IHS_YND_537","NOCINC0002640401","MEF=
OU ASSI","IHS_YND_737, IHS_YND_768","18-07-2024 14:42:38","18-07-2024 14:37=
:33","18-07-2024 14:50:14","Active: no power issue, site is on Gen with Uba=
ie=3D53,1V, Steve( 691144395) from ZTE working on site","Fanda Brice","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active: no power issue, site is on Gen with Ubaie=3D53,1V, Steve( 69=
1144395) from ZTE working on site","ludivine.ngamaleu@ihstowers.com","307",=
"18-07-2024 14:42:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_114","NOCINC0002640396","Kondengu=
i","","18-07-2024 14:40:50","18-07-2024 14:35:08","18-07-2024 21:12:31","Ca=
scaded Incident from TTO2448617","Albran Byorel","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage// grid return","system","=
342","18-07-2024 14:40:50","Sagemcom CMR"
"Cancelled","Warning","T3233","IHS_YND_768","NOCINC0002640395","ELOUMDEM CA=
RRIERE 2","","18-07-2024 14:40:49","","","","Fanda Brice","","","","","","l=
udivine.ngamaleu@ihstowers.com","185","18-07-2024 14:40:49","Sagemcom CMR"
"Closed Complete","Site Down","CTR_417","IHS_YND_121","NOCINC0002640392","E=
mombo-Tchad","IHS_YND_114","18-07-2024 14:40:17","18-07-2024 14:35:08","18-=
07-2024 21:12:31","fme is on site","","Grid Supply","Passive","Grid","Natio=
nal Grid - Grid Outage Issue","grid outage// grid return","alwine.fambou@ih=
stowers.com","310","18-07-2024 14:40:17","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0002640335","Mamch Bu=
ilding","","18-07-2024 14:32:10","18-07-2024 14:22:12","18-07-2024 14:45:17=
","Cascaded Incident from TTO2448532","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage//MDG 20 kva deployed=
","system","598","18-07-2024 14:32:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0002640311","C=
harles-Atangana","IHS_YND_051","18-07-2024 14:31:24","18-07-2024 14:22:12",=
"18-07-2024 14:49:32","Grid outage//MDG 20 kva deployed","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG 20 kv=
a deployed","alwine.fambou@ihstowers.com","553","18-07-2024 14:31:24","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0002640103","C=
amp-Sic-Tsinga","","18-07-2024 14:02:17","18-07-2024 13:54:03","18-07-2024 =
18:34:03","Grid outage.no space to deploy mobile gen // grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","	Gri=
d outage.no space to deploy mobile gen // grid power return","etienne.itond=
o@ihstowers.com","495","18-07-2024 14:02:17","Sagemcom CMR"
"Closed Complete","Site Down","CTR_554","IHS_YND_174","NOCINC0002639630","C=
arrefourt Nkomo","","18-07-2024 13:26:12","18-07-2024 13:18:02","18-07-2024=
 16:39:43","Active: no power issue, site is on Grid with Ubaie=3D52,5V, Par=
kers(698201118) from ZTE working on site","Mba Lazare Herve","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: no power issue, site is on Grid with Ubaie=3D52,5V, Parkers(698201118=
) from ZTE working on site","etienne.itondo@ihstowers.com","491","18-07-202=
4 13:26:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_035","IHS_YND_055","NOCINC0002639463","O=
lezoa OCM","","18-07-2024 13:10:22","18-07-2024 12:56:12","18-07-2024 13:36=
:36","No power  issue Ubaie=3D53.6V site on Grid,  Lionel  Steve (655184876=
)of HUAWEI is informed.","","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power  issue Ubaie=3D53.6V site =
on Grid,  Lionel  Steve (655184876)of HUAWEI is informed.","etienne.itondo@=
ihstowers.com","851","18-07-2024 13:10:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_389","IHS_YND_066","NOCINC0002639443","G=
SO","","18-07-2024 13:07:46","18-07-2024 12:47:34","18-07-2024 13:37:43","N=
o power issue on site Ubaie:50,9V site on GEN.  Clement(680557975) from ZTE=
 working on site","MINKA NICOLAS","Customer Equipment Failure","Active","Ac=
tive Equipment Failure","BTS/TX Fault Alarm","No power issue on site Ubaie:=
50,9V site on GEN.  Clement(680557975) from ZTE working on site","etienne.i=
tondo@ihstowers.com","1215","18-07-2024 13:07:46","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0002639440","Bri=
quetterie","","18-07-2024 13:07:25","18-07-2024 12:34:08","18-07-2024 12:46=
:13","Grid outage.no space to deploy mobile gen//grid power ","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no sp=
ace to deploy mobile gen//grid power ","etienne.itondo@ihstowers.com","1997=
","18-07-2024 13:07:25","Sagemcom CMR"
"Closed Complete","Site Down","T0533","IHS_YND_181","NOCINC0002639253","Mim=
boman3","","18-07-2024 12:41:35","18-07-2024 12:34:24","18-07-2024 12:52:24=
","Grid outage, site went down before gen start due to poor battery backup =
// Gen start automaticaly","Mba Lazare Herve","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Battery Low","Grid outage, site went down =
before gen start due to poor battery backup // Gen start automaticaly","dor=
othy.djantio@ihstowers.com","432","18-07-2024 12:41:35","Sagemcom CMR"
"Closed Complete","Site Down","T0583","IHS_YND_733","NOCINC0002639248","Nko=
g-Edzen","","18-07-2024 12:39:56","18-07-2024 12:31:48","18-07-2024 12:51:4=
8","site went down due to work Ulrich/SAGEMCOM/656072680/working on site: d=
o the PM//End of work","Parker Tchoup","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","site went down due to work Ulrich/S=
AGEMCOM/656072680/working on site: do the PM//End of work","dorothy.djantio=
@ihstowers.com","491","18-07-2024 12:39:56","Sagemcom CMR"
"Closed Complete","Site Down","CTR_539","IHS_YND_193","NOCINC0002638927","B=
astos Ekoudou","","18-07-2024 12:05:11","18-07-2024 12:01:05","18-07-2024 1=
2:07:58","Grid outage, site went down before gen start due to poor battery =
backup // grid return","Mboua Thierry","Equipment Repair","Passive","Contro=
l Panel","Power Cabinet - Battery Low","Grid outage, site went down before =
gen start due to poor battery backup // grid return","etienne.itondo@ihstow=
ers.com","248","18-07-2024 12:05:11","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_563","NOCINC0002638828","Bastos B=
ethesda","","18-07-2024 11:55:40","18-07-2024 11:42:43","18-07-2024 12:09:1=
1","Cascaded Incident from TTO2446956","Mboua Thierry","Cascade Outage","Ac=
tive","Cascade Active","Cascade Active"," No power issue U=3D54.6 V  site o=
n grid-  Benda Charle (695 55 99 48) from ZTE working on site","system","15=
68","18-07-2024 11:55:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_236","IHS_YND_177","NOCINC0002638827","A=
wae-Yde","IHS_YND_563","18-07-2024 11:54:56","18-07-2024 11:42:43","18-07-2=
024 12:09:11"," No power issue U=3D54.6 V  site on grid-  Benda Charle (695=
 55 99 48) from ZTE working on site","Albran Byorel","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm"," No power =
issue U=3D54.6 V  site on grid-  Benda Charle (695 55 99 48) from ZTE worki=
ng on site","etienne.itondo@ihstowers.com","736","18-07-2024 11:54:56","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0002638707","C=
rf-Nsam","","18-07-2024 11:29:54","18-07-2024 11:00:49","18-07-2024 11:55:1=
9","No power issue on site U=3D53,4v site on grid Team Yvan/679375329/ZTE w=
orking on site","MINKA NICOLAS","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53,4=
v site on grid Team Yvan/679375329/ZTE working on site","etienne.itondo@ihs=
towers.com","1747","18-07-2024 11:29:54","Sagemcom CMR"
"Closed Complete","Site Down","T2347","IHS_YND_731","NOCINC0002638635","UPA=
C LP","","18-07-2024 11:19:39","18-07-2024 11:12:32","18-07-2024 12:06:15",=
"grid outage, No space to de deploy a mobil gen//grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","grid outage, No s=
pace to de deploy a mobil gen//grid return","dorothy.djantio@ihstowers.com"=
,"427","18-07-2024 11:19:39","Sagemcom CMR"
"Closed Complete","Warning","T1551","IHS_YND_316","NOCINC0002638555","Akak-=
Nkozoa-MTN-IHS","","18-07-2024 11:07:45","","","SITE ON BATTERY","Fabrice P=
ouakam","Warning","Warning","POWER","Warning - Grid Voltage Failure","site =
alarming due to Grid bad voltage// He bypass the Grid and site on Gen","eti=
enne.itondo@ihstowers.com","493","18-07-2024 11:07:45","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0002638519","Mamch Bu=
ilding","","18-07-2024 11:00:00","18-07-2024 10:50:15","18-07-2024 11:56:56=
","Cascaded Incident from TTO2446621","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","Grid outage//MDG 20 kva deployed=
","system","585","18-07-2024 11:00:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0002638517","C=
harles-Atangana","IHS_YND_051","18-07-2024 10:59:26","18-07-2024 10:50:15",=
"18-07-2024 12:00:11","Grid outage//MDG 20 kva deployed","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG 20 kv=
a deployed","etienne.itondo@ihstowers.com","553","18-07-2024 10:59:26","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_251","IHS_YND_136","NOCINC0002638470","V=
allee-Bastos OCM","","18-07-2024 10:51:43","18-07-2024 10:49:34","18-07-202=
4 11:19:22","Grid outage//MDG 20kva deployed","","Grid Supply","Passive","G=
rid","National Grid - Grid Outage Issue","Grid outage//MDG 20kva deployed",=
"etienne.itondo@ihstowers.com","131","18-07-2024 10:51:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_168","IHS_YND_171","NOCINC0002638454","A=
wae Escalier","","18-07-2024 10:50:15","18-07-2024 10:37:04","18-07-2024 12=
:17:52","No power issue on site U=3D53,7v site on grid Team Alix/695285353/=
ZTE working on site","Albran Byorel","Customer Equipment Failure","Active",=
"Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D53,7v site on grid Team Alix/695285353/ZTE working on site","etienne.ito=
ndo@ihstowers.com","792","18-07-2024 10:50:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_196","IHS_YND_159","NOCINC0002638445","C=
omplexe-BEAC","","18-07-2024 10:48:42","18-07-2024 10:38:32","18-07-2024 12=
:15:52","No power issue on site U=3D54,1v site on gen Team ADIGONO/67751309=
1/ZTE working on site","Albran Byorel","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=
=3D54,1v site on gen Team ADIGONO/677513091/ZTE working on site","etienne.i=
tondo@ihstowers.com","612","18-07-2024 10:48:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0002638302","SAA Entr=
ance","","18-07-2024 10:23:30","18-07-2024 10:16:00","18-07-2024 10:27:29",=
"Cascaded Incident from TTO2446384","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage,gen ran till fuel shor=
tage//Refueling done","system","450","18-07-2024 10:23:30","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0002638303","Saa","",=
"18-07-2024 10:23:30","18-07-2024 10:16:00","18-07-2024 10:27:29","Cascaded=
 Incident from TTO2446384","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","grid outage,gen ran till fuel shortage//Ref=
ueling done","system","450","18-07-2024 10:23:30","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0002638297","SAA=
 2","IHS_YND_542, IHS_YND_405","18-07-2024 10:22:07","18-07-2024 10:13:26",=
"18-07-2024 10:27:29","grid outage,gen ran till fuel shortage//grid return(=
refueling ongoing)","Parker Tchoup","Fuel Outage","Passive","Diesel","Diese=
l Outage","grid outage,gen ran till fuel shortage//grid return(refueling on=
going)","dorothy.djantio@ihstowers.com","545","18-07-2024 10:22:07","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_241","NOCINC0002638143","Etoudi",=
"","18-07-2024 09:51:30","18-07-2024 01:15:11","18-07-2024 02:00:15","Casca=
ded Incident from TTO2446191","Fabrice Pouakam","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site ubaie=3D54v site o=
n grid","system","30979","18-07-2024 09:51:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_520","IHS_YND_694","NOCINC0002638128","E=
TOUDI CHAPELLE","IHS_YND_241","18-07-2024 09:50:30","18-07-2024 01:15:11","=
18-07-2024 02:00:15","","Delor Telezing","Customer Equipment Failure","Acti=
ve","Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site=
 ubaie=3D54v site on grid","marie.kwin@ihstowers.com","30921","18-07-2024 0=
9:50:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_483","IHS_YND_564","NOCINC0002638083","M=
vog Mbi New","","18-07-2024 09:43:15","18-07-2024 09:32:08","18-07-2024 16:=
48:43","Active: no power issue, site is on grid with Ubaie=3D53V, Christian=
(670076638) From ZTE WORKING ON SITE","MINKA NICOLAS","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: n=
o power issue, site is on grid with Ubaie=3D53V, Christian(670076638) From =
ZTE WORKING ON SITE","etienne.itondo@ihstowers.com","668","18-07-2024 09:43=
:15","Sagemcom CMR"
"Closed Complete","Site Down","T1449","IHS_YND_692","NOCINC0002638047","Men=
dong vallee","","18-07-2024 09:39:42","18-07-2024 09:34:20","18-07-2024 10:=
16:09","grid outage,site went down due to Gen overload 22kva 300A//he reduc=
e 2 rack of battery","Fanda Brice","Equipment Repair","Passive","ACDG Gen",=
"ACDG - Overload","grid outage,site went down due to Gen overload 22kva 300=
A//he reduce 2 rack of battery","dorothy.djantio@ihstowers.com","323","18-0=
7-2024 09:39:42","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0002638025","Nlo=
ngkak","","18-07-2024 09:36:42","18-07-2024 09:27:33","18-07-2024 09:53:25"=
,"grid outage, site went down because Gen started and stopped due to alarm =
under Voltage//he reset Gen card and Started Gen","Delor Telezing","Equipme=
nt Repair","Passive","ACDG Gen","ACDG - Control Panel","grid outage, site w=
ent down because Gen started and stopped due to alarm under Voltage//he res=
et Gen card and Started Gen","dorothy.djantio@ihstowers.com","550","18-07-2=
024 09:36:42","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002638003","Sapeur",=
"","18-07-2024 09:32:50","18-07-2024 09:02:01","18-07-2024 15:53:05","Casca=
ded Incident from TTO2446049","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage.no space to deploy mobile ge=
n // grid power return","system","1849","18-07-2024 09:32:50","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002637995","E=
-Police","IHS_YND_029","18-07-2024 09:32:06","18-07-2024 09:02:01","18-07-2=
024 15:53:05","Grid outage.no space to deploy mobile gen // grid power retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage.no space to deploy mobile gen // grid power return","etienne.it=
ondo@ihstowers.com","1806","18-07-2024 09:32:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0002637986","N=
kolangaa","","18-07-2024 09:30:36","18-07-2024 09:14:30","18-07-2024 15:00:=
05","Active: no power issue, site is on grid with Ubaie=3D53V,Elochukwu(682=
840529) from ZTE working on site","Mba Lazare Herve","Customer Equipment Fa=
ilure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no=
 power issue, site is on grid with Ubaie=3D53V,Elochukwu(682840529) from ZT=
E working on site","etienne.itondo@ihstowers.com","971","18-07-2024 09:30:3=
6","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0002637984","H=
-Progres","","18-07-2024 09:29:50","18-07-2024 09:23:40","18-07-2024 15:53:=
08","Grid outage.no space to depploy mobile gen//Grid restored","","Grid Su=
pply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage.no =
space to depploy mobile gen//Grid restored","etienne.itondo@ihstowers.com",=
"370","18-07-2024 09:29:50","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0002637948","Eto=
 koss Yde","","18-07-2024 09:23:34","18-07-2024 09:15:30","18-07-2024 11:05=
:38","grid outage ,gen failed to start due to battery Ge faulty//he started=
 the gen with battery backup","Fanda Brice","Equipment Repair","Passive","A=
CDG Gen","ACDG - Generator Battery","grid outage ,gen failed to start due t=
o battery Ge faulty//he started the gen with battery backup","dorothy.djant=
io@ihstowers.com","486","18-07-2024 09:23:34","Sagemcom CMR"
"Closed Complete","Site Down","CTR_487","IHS_YND_510","NOCINC0002637792","M=
VAN SACEL","","18-07-2024 08:57:42","18-07-2024 08:53:33","18-07-2024 16:41=
:21","Active: no power issue, site is on grid with Ubaie=3D53V, Lo=EEc(6550=
97686) from ZTE working on site","MINKA NICOLAS","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: no pow=
er issue, site is on grid with Ubaie=3D53V, Lo=EEc(655097686) from ZTE work=
ing on site","etienne.itondo@ihstowers.com","250","18-07-2024 08:57:42","Sa=
gemcom CMR"
"Closed Complete","Site Down","T1570","IHS_YND_140","NOCINC0002637051","BIS=
CUITERIE","","18-07-2024 05:37:22","17-07-2024 22:04:06","17-07-2024 23:19:=
06","Grid outage site went down because Gen failed to started due to  Gen f=
use cut // He make the bridge and manually started the Gen","Paul BIBOUM","=
Equipment Repair","Passive","ACDG Gen","ACDG - Control Panel","Grid outage =
site went down because Gen failed to started due to  Gen fuse cut // He mak=
e the bridge and manually started the Gen","kouoh.jean@ihstowers.com","2722=
8","18-07-2024 05:37:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0002637045","Anguissa=
 New","","18-07-2024 05:35:01","18-07-2024 07:55:10","18-07-2024 07:57:10",=
"Cascaded Incident from TTO2439470","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, No space to de deploy=
 a mobil gen//grid return","system","4458","18-07-2024 05:35:01","Sagemcom =
CMR"
"Closed Complete","Site Down","T0523","IHS_YND_568","NOCINC0002637014","Ang=
uissa New","","18-07-2024 05:24:43","17-07-2024 16:34:54","17-07-2024 19:23=
:24","Site went down due to work, SS IHS Raoul and  judicael//6656072620// =
Sagemcom// working on site","MINKA NICOLAS","Installation Activity","Passiv=
e","Planned Activity","Installation Activity","Site went down due to work, =
SS IHS Raoul and  judicael//6656072620// Sagemcom// working on site","kouoh=
.jean@ihstowers.com","46191","18-07-2024 05:24:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_086","IHS_YND_211","NOCINC0002636913","E=
toudi 2","","18-07-2024 04:34:38","18-07-2024 04:14:34","18-07-2024 04:18:0=
1","No power issue site on grid with U=3D54v// Symphorien from Huawei is in=
formed site up at04:43 AM","Fabrice Pouakam","Customer Equipment Failure","=
Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue sit=
e on grid with U=3D54v// Symphorien from Huawei is informed site up at04:43=
 AM","landry.etame@ihstowers.com","1205","18-07-2024 04:34:38","Sagemcom CM=
R"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002636572","MBIMBIM"=
,"","18-07-2024 02:21:40","18-07-2024 02:13:07","18-07-2024 02:14:07","Casc=
aded Incident from TTO2444468","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.9V (Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane =
657959647of Huawei is informed","system","513","18-07-2024 02:21:40","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002636568","Ngoum","=
","18-07-2024 02:21:40","18-07-2024 02:13:07","18-07-2024 02:14:07","Cascad=
ed Incident from TTO2444468","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.9V (Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane =
657959647of Huawei is informed","system","513","18-07-2024 02:21:40","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002636569","Matsari"=
,"","18-07-2024 02:21:40","18-07-2024 02:13:07","18-07-2024 02:14:07","Casc=
aded Incident from TTO2444468","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 54.9V (Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane =
657959647of Huawei is informed","system","513","18-07-2024 02:21:40","Sagem=
com CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002636571","Ngouetou=
","","18-07-2024 02:21:40","18-07-2024 02:13:07","18-07-2024 02:14:07","Cas=
caded Incident from TTO2444468","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.9V (Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane=
 657959647of Huawei is informed","system","513","18-07-2024 02:21:40","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002636570","Yoko OCM=
","","18-07-2024 02:21:40","18-07-2024 02:13:07","18-07-2024 02:14:07","Cas=
caded Incident from TTO2444468","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 54.9V (Hybrid gen site with threshold =3D 47.5V).   TX FME Abdouramane=
 657959647of Huawei is informed","system","513","18-07-2024 02:21:40","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_023","IHS_YND_243","NOCINC0002636278","E=
mana","","18-07-2024 00:33:23","18-07-2024 00:30:18","18-07-2024 00:55:38",=
"ACTIVE no power issue on site Ubaie=3D52.8V site on Grid , TX FME  Synphor=
ien (691316854) from Huawei is informed// Site up at 12:33 AM","","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","ACTIVE no power issue on site Ubaie=3D52.8V site on Grid , TX FME  Synph=
orien (691316854) from Huawei is informed// Site up at 12:33 AM","landry.et=
ame@ihstowers.com","186","18-07-2024 00:33:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0002636274","T=
SINGA VILLAGE 2","","18-07-2024 00:29:47","18-07-2024 00:27:42","18-07-2024=
 00:51:01","site went down because gen failed to start due to system hybrid=
 disfunctionning//he started the gen manually","Delor Telezing","Equipment =
Repair","Passive","Hybrid","Hybrid Software","site went down because gen fa=
iled to start due to system hybrid disfunctionning//he started the gen manu=
ally","landry.etame@ihstowers.com","556","18-07-2024 00:29:47","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_372","IHS_YND_078","NOCINC0002636179","A=
n-Marche-Melen","","17-07-2024 23:59:22","17-07-2024 23:54:17","18-07-2024 =
01:05:16","Grid Outage. No space to deploy the MDG// Grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage. =
No space to deploy the MDG// Grid return","landry.etame@ihstowers.com","667=
","17-07-2024 23:59:22","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_309","NOCINC0002636177","Leboudi"=
,"","17-07-2024 23:59:00","17-07-2024 23:50:52","17-07-2024 23:53:08","Casc=
aded Incident from TTO2444037","TIENTCHEU NZETCHIEU GAEL","Cascade Outage",=
"Active","Cascade Active","Cascade Active","No power issue site on grid wit=
h U=3D54,5,Notice that site is impacted by Nkolbisson Nodal who is not our =
responsability ","system","488","17-07-2024 23:59:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_519","NOCINC0002636176","AFEME NO=
RD","","17-07-2024 23:59:00","17-07-2024 23:50:52","17-07-2024 23:53:08","C=
ascaded Incident from TTO2444037","TIENTCHEU NZETCHIEU GAEL","Cascade Outag=
e","Active","Cascade Active","Cascade Active","No power issue site on grid =
with U=3D54,5,Notice that site is impacted by Nkolbisson Nodal who is not o=
ur responsability ","system","488","17-07-2024 23:59:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_246","IHS_YND_287","NOCINC0002636173","N=
kolafeme","IHS_YND_519, IHS_YND_309","17-07-2024 23:57:58","17-07-2024 23:5=
0:52","18-07-2024 00:50:52","No power issue site on grid with U=3D54,5,Noti=
ce that site is impacted by Nkolbisson Nodal who is not our responsability =
","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D54,5,Notice that site is impacted by Nkolbisson Nodal who is not our res=
ponsability ","landry.etame@ihstowers.com","427","17-07-2024 23:57:58","Sag=
emcom CMR"
"Closed Complete","Site Down","CTR_623","IHS_YND_515","NOCINC0002636120","E=
toug ebe Meweulo","","17-07-2024 23:44:42","17-07-2024 23:23:34","18-07-202=
4 00:07:25","Grid Outage site went down because GEN CB(40 A) disjuncted// H=
e reamed the CB(investigation ongoing)","Hyemafo Gildas","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Circuit Breaker Issue","Grid Ou=
tage site went down because GEN CB(40 A) disjuncted// He reamed the CB(inve=
stigation ongoing)","landry.etame@ihstowers.com","2359","17-07-2024 23:44:4=
2","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002636011","Tsi=
nga","","17-07-2024 23:16:03","17-07-2024 23:11:34","17-07-2024 23:38:05","=
site went down due to disfunctionning of controller// voltage stabilized ( =
controller to be replaced)","Mboua Thierry","Equipment Repair","Passive","H=
ybrid","Hybrid Module","site went down due to disfunctionning of controller=
// voltage stabilized ( controller to be replaced)","denis.mballa@ihstowers=
.com","371","17-07-2024 23:16:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002635903","M=
asque","","17-07-2024 22:46:03","17-07-2024 22:42:36","18-07-2024 00:29:34"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V  The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue//site up at =
11:02 PM","Fabrice Pouakam","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site.Site on Grid=
 with Ubaie=3D54.3 V  The TX FME  Eloundou // 693212405// From  Huawei is i=
nformed. Repetitive issue//site up at 11:02 PM","landry.etame@ihstowers.com=
","208","17-07-2024 22:46:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_313","NOCINC0002635876","Afanoya"=
,"","17-07-2024 22:39:29","17-07-2024 22:31:02","18-07-2024 00:29:34","Acti=
ve :No power issue on site , Ubaie=3D54.4V site On Grid The FME TX Lionnel =
/694693436/ from Huawei is informed///site up at 10:44 PM","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","Active :No power issue on site , Ubaie=3D54.4V site On Grid Th=
e FME TX Lionnel /694693436/ from Huawei is informed///site up at 10:44 PM"=
,"landry.etame@ihstowers.com","508","17-07-2024 22:39:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0002635714","B=
riqueterie","","17-07-2024 22:06:44","17-07-2024 19:28:32","18-07-2024 12:3=
9:17","grid outage, No space to de deploy a mobil gen//grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage=
, No space to de deploy a mobil gen//grid return","emmanuel.ghani@ihstowers=
.com","9494","17-07-2024 22:06:44","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_051","NOCINC0002635366","Mamch Bu=
ilding","","17-07-2024 20:43:00","17-07-2024 20:36:14","17-07-2024 21:57:46=
","Cascaded Incident from TTO2443065","Mboua Thierry","Cascade Outage","Pas=
sive","Cascade Passive","Cascade Passive","grid outage//MDG 20 kva deployed=
","system","406","17-07-2024 20:43:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_197","IHS_YND_125","NOCINC0002635348","C=
harles-Atangana","IHS_YND_051","17-07-2024 20:41:18","17-07-2024 20:36:14",=
"17-07-2024 22:03:58","grid outage//MDG 20 kva deployed","","Grid Supply","=
Passive","Grid","National Grid - Grid Outage Issue","grid outage//MDG 20 kv=
a deployed","emmanuel.ghani@ihstowers.com","354","17-07-2024 20:41:18","Sag=
emcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002635220","Ngouetou=
","","17-07-2024 20:13:00","17-07-2024 19:55:59","17-07-2024 19:56:03","Cas=
caded Incident from TTO2442900","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 51.4V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane o=
f Huawei is informed","system","1021","17-07-2024 20:13:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002635221","MBIMBIM"=
,"","17-07-2024 20:13:00","17-07-2024 19:55:59","17-07-2024 19:56:03","Casc=
aded Incident from TTO2442900","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 51.4V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane of=
 Huawei is informed","system","1021","17-07-2024 20:13:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_474","NOCINC0002635219","Yoko OCM=
","","17-07-2024 20:13:00","17-07-2024 19:55:59","17-07-2024 19:56:03","Cas=
caded Incident from TTO2442900","Parker Tchoup","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue. Site is on battery with U=
 =3D 51.4V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane o=
f Huawei is informed","system","1021","17-07-2024 20:13:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_475","NOCINC0002635217","Ngoum","=
","17-07-2024 20:13:00","17-07-2024 19:55:59","17-07-2024 19:56:03","Cascad=
ed Incident from TTO2442900","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 51.4V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane of=
 Huawei is informed","system","1021","17-07-2024 20:13:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002635218","Matsari"=
,"","17-07-2024 20:13:00","17-07-2024 19:55:59","17-07-2024 19:56:03","Casc=
aded Incident from TTO2442900","Parker Tchoup","Cascade Outage","Active","C=
ascade Active","Cascade Active","No power issue. Site is on battery with U =
=3D 51.4V (Hybrid gen site with threshold =3D 47.5V). TX FME Abdouramane of=
 Huawei is informed","system","1021","17-07-2024 20:13:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_471","IHS_YND_231","NOCINC0002635086","N=
kolso","","17-07-2024 19:42:48","17-07-2024 19:38:43","17-07-2024 20:35:23"=
,"ACTIVE No power issue site on Gen U=3D54,3V tx fme Mohamadou//691144435 h=
uawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power i=
ssue site on Gen U=3D54,3V tx fme Mohamadou//691144435 huawei is informed",=
"emmanuel.ghani@ihstowers.com","247","17-07-2024 19:42:48","Sagemcom CMR"
"Closed Complete","Site Down","T1568","IHS_YND_084","NOCINC0002635079","Bri=
quetterie","","17-07-2024 19:41:16","17-07-2024 19:32:12","18-07-2024 11:29=
:32","grid outage, No space to de deploy a mobil gen//grid return","","Grid=
 Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage,=
 No space to de deploy a mobil gen//grid return","joelle.ekessi@ihstowers.c=
om","545","17-07-2024 19:41:16","Sagemcom CMR"
"Closed Complete","Site Down","T1243","IHS_YND_795","NOCINC0002635065","Lad=
a I Yde","","17-07-2024 19:37:23","17-07-2024 19:32:19","17-07-2024 20:22:1=
2","grid outage, site went down due to gen Overload(09KVA, 105A)// Grid ret=
urn","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACDG - Ove=
rload","grid outage, site went down due to gen Overload(09KVA, 105A)// Grid=
 return","joelle.ekessi@ihstowers.com","304","17-07-2024 19:37:23","Sagemco=
m CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0002635036","M=
EFOU ASSI","","17-07-2024 19:31:29","17-07-2024 18:56:20","17-07-2024 20:35=
:33","Active :No power issue on site , Ubaie=3D54.4V site On Grid The FME T=
X Lionnel /694693436/ from Huawei is informed  (Site Swap by ZTE)","Fanda B=
rice","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","Active :No power issue on site , Ubaie=3D54.4V site On Gr=
id The FME TX Lionnel /694693436/ from Huawei is informed  (Site Swap by ZT=
E)","emmanuel.ghani@ihstowers.com","2110","17-07-2024 19:31:29","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_290","NOCINC0002634938","Abang","=
","17-07-2024 19:18:01","17-07-2024 19:00:56","17-07-2024 19:10:07","Cascad=
ed Incident from TTO2442603","Mba Lazare Herve","Cascade Outage","Active","=
Cascade Active","Cascade Active","No power issue on site Ubaie =3D53.2V sit=
e on Gen The TX FME Lionel //655184876//  from huawei is informed","system"=
,"1025","17-07-2024 19:18:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_247","IHS_YND_289","NOCINC0002634933","N=
kolangaa","IHS_YND_290","17-07-2024 19:16:03","17-07-2024 19:00:56","17-07-=
2024 21:05:07","No power issue on site Ubaie =3D53.2V site on Gen The TX FM=
E Lionel //655184876//  from huawei is informed","Mba Lazare Herve","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power issue on site Ubaie =3D53.2V site on Gen The TX FME Lionel //=
655184876//  from huawei is informed","emmanuel.ghani@ihstowers.com","907",=
"17-07-2024 19:16:03","Sagemcom CMR"
"Closed Complete","Site Down","T1570","IHS_YND_140","NOCINC0002634818","BIS=
CUITERIE","","17-07-2024 18:54:10","17-07-2024 18:48:06","17-07-2024 21:15:=
48","Grid outage, site wen down because gen failed to start due to poor bat=
tery backup // Gen manually started","Paul BIBOUM","Equipment Repair","Pass=
ive","Control Panel","Power Cabinet - Battery Low","Grid outage, site wen d=
own because gen failed to start due to poor battery backup // Gen manually =
started","joelle.ekessi@ihstowers.com","846","17-07-2024 18:54:10","Sagemco=
m CMR"
"Closed Complete","Site Down","T1868","IHS_YND_524","NOCINC0002634555","ODZ=
A BORNE 10","","17-07-2024 17:58:53","17-07-2024 17:55:48","17-07-2024 21:4=
2:39","No power issue on site Ubaie =3D53.7V site on Gen The TX FME Lionel =
//655184876//  from huawei is informed","Albran Byorel","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No powe=
r issue on site Ubaie =3D53.7V site on Gen The TX FME Lionel //655184876// =
 from huawei is informed","joelle.ekessi@ihstowers.com","187","17-07-2024 1=
7:58:53","Sagemcom CMR"
"Closed Complete","Site Down","T1440","IHS_YND_698","NOCINC0002634512","EBO=
M","","17-07-2024 17:55:01","17-07-2024 17:47:55","17-07-2024 18:37:13","Gr=
id outage, site went down because gen failed to start due to battery Ge fau=
lty // he start the gen with battery backup","Hyemafo Gildas","Equipment Re=
pair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage, site we=
nt down because gen failed to start due to battery Ge faulty // he start th=
e gen with battery backup","joelle.ekessi@ihstowers.com","427","17-07-2024 =
17:55:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_331","IHS_YND_253","NOCINC0002634495","C=
lge-Advantiste","","17-07-2024 17:52:12","17-07-2024 15:33:04","17-07-2024 =
15:45:30","Active :No power issue on site , Ubaie=3D49.7V site On Gen  Lind=
a from ZTE is informed  (Site Swap by ZTE)","MINKA NICOLAS","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive :No power issue on site , Ubaie=3D49.7V site On Gen  Linda from ZTE is =
informed  (Site Swap by ZTE)","emmanuel.ghani@ihstowers.com","8349","17-07-=
2024 17:52:12","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0002634463","Boumnyeb=
el","","17-07-2024 17:47:50","17-07-2024 17:44:34","17-07-2024 17:46:46","C=
ascaded Incident from TTO2442046","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 gen start due to poor battery backup // grid return","system","196","17-07=
-2024 17:47:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0002634461","Ndogbess=
ol","","17-07-2024 17:47:50","17-07-2024 17:44:34","17-07-2024 17:46:46","C=
ascaded Incident from TTO2442046","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 gen start due to poor battery backup // grid return","system","196","17-07=
-2024 17:47:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_376","NOCINC0002634464","Mamb",""=
,"17-07-2024 17:47:50","17-07-2024 17:44:34","17-07-2024 17:46:46","Cascade=
d Incident from TTO2442046","Kemeni Franklin","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","Grid outage, site went down before gen s=
tart due to poor battery backup // grid return","system","196","17-07-2024 =
17:47:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_419","NOCINC0002634462","Ngog Map=
ubi","","17-07-2024 17:47:50","17-07-2024 17:44:34","17-07-2024 17:46:46","=
Cascaded Incident from TTO2442046","Kemeni Franklin","Cascade Outage","Pass=
ive","Cascade Passive","Cascade Passive","Grid outage, site went down befor=
e gen start due to poor battery backup // grid return","system","196","17-0=
7-2024 17:47:50","Sagemcom CMR"
"Closed Complete","Site Down","T0322","IHS_YND_312","NOCINC0002634455","Nko=
lnda","","17-07-2024 17:46:51","17-07-2024 17:42:46","17-07-2024 18:46:34",=
"Grid outage site went down because Gen failed to started // Grid return (I=
nvestigation ongoing)","Albran Byorel","Equipment Repair","Passive","ACDG G=
en","ACDG - Control Panel","Grid outage site went down because Gen failed t=
o started // Grid return (Investigation ongoing)","joelle.ekessi@ihstowers.=
com","246","17-07-2024 17:46:51","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0002634445","B=
oumnyebel OCM","IHS_EDA_056, IHS_YND_419, IHS_YND_381, IHS_YND_376","17-07-=
2024 17:45:41","17-07-2024 17:44:34","17-07-2024 17:46:46","Grid outage, si=
te went down before gen start due to poor battery backup // grid return","K=
emeni Franklin","Equipment Repair","Passive","Control Panel","Power Cabinet=
 - Battery Low","Grid outage, site went down before gen start due to poor b=
attery backup // grid return","emmanuel.ghani@ihstowers.com","69","17-07-20=
24 17:45:41","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0002634393","Bas=
tos Bethesda","","17-07-2024 17:35:47","17-07-2024 17:11:42","17-07-2024 17=
:17:56","Grid outage, site wen down because gen failed to start due to poor=
 battery backup // Gen start automatically","Mboua Thierry","Equipment Repa=
ir","Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, s=
ite wen down because gen failed to start due to poor battery backup // Gen =
start automatically","joelle.ekessi@ihstowers.com","1447","17-07-2024 17:35=
:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_463","IHS_YND_313","NOCINC0002634298","A=
fanoya","","17-07-2024 17:34:23","17-07-2024 17:28:20","17-07-2024 21:10:16=
","Active :No power issue on site , Ubaie=3D54.4V site On Grid The FME TX L=
ionnel /694693436/ from Huawei is informed ","Hyemafo Gildas","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
ctive :No power issue on site , Ubaie=3D54.4V site On Grid The FME TX Lionn=
el /694693436/ from Huawei is informed ","emmanuel.ghani@ihstowers.com","36=
4","17-07-2024 17:34:23","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_019","NOCINC0002634239","Hotel de=
 Ville Yde","","17-07-2024 17:33:00","17-07-2024 17:10:20","17-07-2024 19:3=
6:20","Cascaded Incident from TTO2441665","Paul BIBOUM","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","Grid outage//MDG of 13 kva has=
 deployed ","system","1360","17-07-2024 17:33:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_038","IHS_YND_052","NOCINC0002634080","N=
R-Bastos","IHS_YND_019","17-07-2024 17:22:27","17-07-2024 17:10:20","17-07-=
2024 19:36:20","Grid outage//MDG of 13 kva has deployed ","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage//MDG of 1=
3 kva has deployed ","emmanuel.ghani@ihstowers.com","728","17-07-2024 17:22=
:27","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0002633976","Lobo OCM=
","","17-07-2024 17:08:40","17-07-2024 16:53:33","17-07-2024 17:02:31","Cas=
caded Incident from TTO2441496","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automaticaly","sy=
stem","907","17-07-2024 17:08:40","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002633915","N=
KOMEKUI OCM","IHS_YND_341","17-07-2024 17:04:38","17-07-2024 16:53:33","17-=
07-2024 17:02:31","Grid outage, site went down before gen start due to poor=
 battery backup // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 outage, site went down before gen start due to poor battery backup // Gen =
start automaticaly","emmanuel.ghani@ihstowers.com","667","17-07-2024 17:04:=
38","Sagemcom CMR"
"Closed Complete","Site Down","T1330","IHS_YND_035","NOCINC0002633712","Bas=
tos Amb Coree","","17-07-2024 16:40:02","17-07-2024 16:35:58","17-07-2024 2=
3:57:17","grid outage, No space to de deploy moble gen//Grid power return",=
"","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid=
 outage, No space to de deploy moble gen//Grid power return","joelle.ekessi=
@ihstowers.com","244","17-07-2024 16:40:02","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002633649","Sapeur",=
"","17-07-2024 16:35:10","17-07-2024 16:25:04","17-07-2024 16:37:27","Casca=
ded Incident from TTO2441199 - Cascade Removed From TTO2441199","Mboua Thie=
rry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","grid o=
utage, No space to de deploy // grid return","system","606","17-07-2024 16:=
35:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002633646","E=
-Police","IHS_YND_029","17-07-2024 16:34:07","17-07-2024 16:25:04","17-07-2=
024 16:37:27","grid outage, No space to de deploy // grid return","","Grid =
Supply","Passive","Grid","National Grid - Grid Outage Issue","grid outage, =
No space to de deploy // grid return","emmanuel.ghani@ihstowers.com","544",=
"17-07-2024 16:34:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0002633297","N=
kozoa","","17-07-2024 15:37:48","17-07-2024 15:32:42","17-07-2024 16:18:10"=
,"Grid outage site went down because Gen failed to start due to battery gen=
 faulty// Grid return","Fabrice Pouakam","Equipment Repair","Passive","ACDG=
 Gen","ACDG - Generator Battery","Grid outage site went down because Gen fa=
iled to start due to battery gen faulty// Grid return","emmanuel.ghani@ihst=
owers.com","739","17-07-2024 15:37:48","Sagemcom CMR"
"Closed Complete","Site Down","T2582","IHS_YND_737","NOCINC0002633289","Eto=
 koss Yde","","17-07-2024 15:36:14","17-07-2024 15:32:10","17-07-2024 16:32=
:49","site went down due to 01/03 rectifier faulty  faulty// He change the =
faulty rectifier;site on Grid","Fanda Brice","Equipment Repair","Passive","=
Rectifier","Rectifier Module","site went down due to 01/03 rectifier faulty=
  faulty// He change the faulty rectifier;site on Grid","joelle.ekessi@ihst=
owers.com","245","17-07-2024 15:36:14","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_087","NOCINC0002633225","Camp-Sic=
-Tsinga","","17-07-2024 15:25:50","17-07-2024 15:14:22","17-07-2024 15:19:0=
7","Cascaded Incident from TTO2440646 - Cascade Removed From TTO2440646",""=
,"Cascade Outage","Passive","Cascade Passive","Cascade Passive","site went =
down because Gen start and stopped with alarm ""Emergency stop""// He bypas=
sed the button emergency stopp, site on Gen","system","688","17-07-2024 15:=
25:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_030","NOCINC0002633223","E-Police=
","IHS_YND_029","17-07-2024 15:25:50","17-07-2024 15:14:22","17-07-2024 15:=
19:07","grid outage, No space to de deploy // grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","grid outage, No spac=
e to de deploy // grid return","system","688","17-07-2024 15:25:50","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002633224","Sapeur",=
"","17-07-2024 15:25:50","17-07-2024 15:14:22","17-07-2024 15:19:07","Casca=
ded Incident from TTO2440646 - Cascade Removed From TTO2440646","Mboua Thie=
rry","Cascade Outage","Passive","Cascade Passive","Cascade Passive","grid o=
utage, No space to de deploy // grid return","system","688","17-07-2024 15:=
25:50","Sagemcom CMR"
"Closed Complete","Site Down","T0960","IHS_YND_563","NOCINC0002633210","Bas=
tos Bethesda","IHS_YND_087","17-07-2024 15:24:30","17-07-2024 15:14:22","17=
-07-2024 16:42:10","site went down because Gen start and stopped with alarm=
 ""Emergency stop""// He bypassed the button emergency stopp, site on Gen",=
"Mboua Thierry","Equipment Repair","Passive","ACDG Gen","ACDG - Emergency S=
top","site went down because Gen start and stopped with alarm ""Emergency s=
top""// He bypassed the button emergency stopp, site on Gen","joelle.ekessi=
@ihstowers.com","688","17-07-2024 15:24:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_049","IHS_YND_209","NOCINC0002633179","M=
anguier","","17-07-2024 15:19:35","17-07-2024 15:14:22","17-07-2024 15:25:0=
7","Active//No power issue on site Ubaie=3D54.5V site on Grid The Tx FME Ar=
mand Nguetsa//699949553 from Huawei is informed","Fabrice Pouakam","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active//No power issue on site Ubaie=3D54.5V site on Grid The Tx FME Ar=
mand Nguetsa//699949553 from Huawei is informed","emmanuel.ghani@ihstowers.=
com","314","17-07-2024 15:19:35","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002633068","NKO=
MEKUI OCM","","17-07-2024 15:11:41","17-07-2024 15:01:37","17-07-2024 15:20=
:24","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // Gen start automat=
icaly","joelle.ekessi@ihstowers.com","605","17-07-2024 15:11:41","Sagemcom =
CMR"
"Closed Complete","Site Down","T1504","IHS_YND_546","NOCINC0002632383","Biy=
emassi LAC","","17-07-2024 13:03:10","17-07-2024 12:59:02","17-07-2024 14:0=
0:03","Grid outage no space to deployed a mobile Gen// Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
 no space to deployed a mobile Gen// Grid return","ludivine.ngamaleu@ihstow=
ers.com","250","17-07-2024 13:03:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0002632194","Anguissa=
 New","","17-07-2024 12:43:10","17-07-2024 13:16:34","17-07-2024 13:48:24",=
"Grid outage, site went down before Gen start due to poor battery backup //=
 Grid power return","MINKA NICOLAS","Equipment Repair","Passive","Control P=
anel","Power Cabinet - Battery Low","Grid outage, site went down before Gen=
 start due to poor battery backup // Grid power return","system","57970","1=
7-07-2024 12:43:10","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_306","NOCINC0002632190","Nkozoa",=
"","17-07-2024 12:42:20","17-07-2024 12:40:34","17-07-2024 14:17:14","Grid =
outage site went down because Gen failed to start due to Gen battery faulty=
// Grid power return","Fabrice Pouakam","Equipment Repair","Passive","ACDG =
Gen","ACDG - Generator Battery","Grid outage site went down because Gen fai=
led to start due to Gen battery faulty// Grid power return","system","644",=
"17-07-2024 12:42:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0002632182","L=
abogenie","IHS_YND_568","17-07-2024 12:40:44","17-07-2024 12:37:34","18-07-=
2024 07:52:10","grid outage, No space to de deploy a mobil gen//grid return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","gr=
id outage, No space to de deploy a mobil gen//grid return","ange.kongo@ihst=
owers.com","191","17-07-2024 12:40:44","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002632159","M=
asque","","17-07-2024 12:33:24","17-07-2024 12:27:17","17-07-2024 13:30:12"=
,"","Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipme=
nt Failure","BTS/TX Fault Alarm","No power issue on site ubaie)54v site on =
grid Eloundou is informed","ange.kongo@ihstowers.com","369","17-07-2024 12:=
33:24","Sagemcom CMR"
"Closed Complete","Warning","T0058","IHS_YND_293","NOCINC0002632113","Nkoab=
ang MTN","","17-07-2024 12:25:17","","","grid outage, site alarm due to dis=
junction Cb gen due to lightning// He reame Cb gen, grid return","Mba Lazar=
e Herve","Warning","Warning","POWER","Warning - Low Voltage","grid outage, =
site alarm due to disjunction Cb gen due to lightning// He reame Cb gen, gr=
id return","marie.kwin@ihstowers.com","5","17-07-2024 12:25:17","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_648","IHS_YND_707","NOCINC0002632008","N=
YOM 2 IHS","","17-07-2024 12:00:33","17-07-2024 11:53:25","17-07-2024 14:12=
:17","Grid outage site went down Gen ran until fuel shortage//Refueling don=
e","Fabrice Pouakam","Fuel Outage","Passive","Diesel","Diesel Outage","Grid=
 outage site went down Gen ran until fuel shortage//Refueling done","ange.k=
ongo@ihstowers.com","596","17-07-2024 12:00:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_326","IHS_YND_236","NOCINC0002631290","M=
ontee-Jouvence","","17-07-2024 09:59:14","16-07-2024 09:16:54","16-07-2024 =
09:18:04","no power issue on site, ilorn 657300711  zte was on site fore sw=
ap","Hyemafo Gildas","Customer Equipment Failure","Active","Active Equipmen=
t Failure","BTS/TX Fault Alarm","no power issue on site, ilorn 657300711  z=
te was on site for swap","marie.kwin@ihstowers.com","88987","17-07-2024 09:=
59:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_482","IHS_YND_562","NOCINC0002631281","A=
ccacia New","","17-07-2024 09:56:13","16-07-2024 10:54:49","16-07-2024 11:0=
7:16","Active: No power issue, site is on grid with Ubaie=3D53,9V, Hezekia(=
653493369) from ZTE working on site","","Customer Equipment Failure","Activ=
e","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issue,=
 site is on grid with Ubaie=3D53,9V, Hezekia(653493369) from ZTE working on=
 site","marie.kwin@ihstowers.com","82900","17-07-2024 09:56:13","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_462","IHS_YND_290","NOCINC0002631202","A=
bang","","17-07-2024 09:41:47","17-07-2024 09:32:42","17-07-2024 11:15:14",=
"Active: No power issue, site is on grid with Ubaie=3D53V, hamzat (67863163=
7) from ZTE working on site","Mba Lazare Herve","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active: No powe=
r issue, site is on grid with Ubaie=3D53V, hamzat (678631637) from ZTE work=
ing on site","ange.kongo@ihstowers.com","546","17-07-2024 09:41:47","Sagemc=
om CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002630822","Sapeur",=
"","17-07-2024 08:09:30","17-07-2024 08:02:56","17-07-2024 08:51:21","Casca=
ded Incident from TTO2437895","Mboua Thierry","Cascade Outage","Passive","C=
ascade Passive","Cascade Passive","grid outage, no space to deploy a mobil =
gen// grid return","system","394","17-07-2024 08:09:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002630821","E=
-Police","IHS_YND_029","17-07-2024 08:09:03","17-07-2024 08:02:56","17-07-2=
024 08:51:21","grid outage, no space to deploy a mobil gen// grid return","=
","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","grid =
outage, no space to deploy a mobil gen// grid return","ange.kongo@ihstowers=
.com","369","17-07-2024 08:09:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0002630525","T=
singa","","17-07-2024 07:04:24","17-07-2024 06:57:58","17-07-2024 07:24:33"=
,"site went down due to disfunctionning of controller// voltage stabilized =
( controller to be replaced)","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","site went down due to disfunctionning of=
 controller// voltage stabilized ( controller to be replaced)","ange.kongo@=
ihstowers.com","503","17-07-2024 07:04:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0002629968","E=
BOM","","17-07-2024 03:09:59","16-07-2024 19:33:43","16-07-2024 19:38:45","=
Active//No  power issue on site ;site onGrid with Ubaie=3D 54.6 V  team DEN=
IS/693675998 from ZTE is working on site","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No  power issue on site ;site onGrid with Ubaie=3D 54.6 V  team DENIS/6=
93675998 from ZTE is working on site","kamga.virgile@ihstowers.com","27933"=
,"17-07-2024 03:09:59","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0002629949","D=
amas","","17-07-2024 03:06:16","16-07-2024 20:00:19","16-07-2024 20:10:24",=
"Active: No power issue, site is on grid with Ubaie=3D53V, Lary(694675611) =
from ZTE working on site","MINKA NICOLAS","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active: No power issu=
e, site is on grid with Ubaie=3D53V, Lary(694675611) from ZTE working on si=
te","kamga.virgile@ihstowers.com","25609","17-07-2024 03:06:16","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0002629643","M=
ambine","","17-07-2024 01:38:29","17-07-2024 01:20:21","17-07-2024 01:46:46=
","site went down because Gen failed to start due to Hybrid  system dysfonc=
tion// He reset the Gen card and Gen manually started","Fanda Brice","Equip=
ment Repair","Passive","Hybrid","Hybrid Module","site went down because Gen=
 failed to start due to Hybrid  system dysfonction// He reset the Gen card =
and Gen manually started","kamga.virgile@ihstowers.com","1088","17-07-2024 =
01:38:29","Sagemcom CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0002629443","Bon=
djock","","17-07-2024 00:29:30","16-07-2024 23:14:46","17-07-2024 01:10:10"=
,"","Fanda Brice","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","site was on gen due to grid outage, gen stopped//gen started manuall=
y (investigations ongoing)","alexandre.kamal@ihstowers.com","9281","17-07-2=
024 00:29:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0002629113","M=
endong Maeture","","16-07-2024 22:50:40","16-07-2024 22:05:33","16-07-2024 =
22:10:57","Active// NO power issue on site.  Ubaie=3D54V site on Gen. TX FM=
E Hosiah/674007438 /Huawei is informed","Hyemafo Gildas","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
// NO power issue on site.  Ubaie=3D54V site on Gen. TX FME Hosiah/67400743=
8 /Huawei is informed","kamga.virgile@ihstowers.com","2709","16-07-2024 22:=
50:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0002628558","M=
EFOU ASSI","","16-07-2024 20:57:57","16-07-2024 19:45:47","16-07-2024 19:50=
:27","Active//No power issue on site,site on Grid with Ubaie=3D52.4V  The T=
x FME Lionnel//694693436 From Huawei is informed.","Fanda Brice","Customer =
Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm"=
,"Active//No power issue on site,site on Grid with Ubaie=3D52.4V  The Tx FM=
E Lionnel//694693436 From Huawei is informed.","landry.etame@ihstowers.com"=
,"4331","16-07-2024 20:57:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0002628555","B=
arriere IHS","","16-07-2024 20:56:49","16-07-2024 19:39:30","16-07-2024 19:=
42:57","Active//No power issue U=3D 53V Site on Grid  The TX FME Rm Alain /=
691144423 from huawei is informed","Hyemafo Gildas","Customer Equipment Fai=
lure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//No =
power issue U=3D 53V Site on Grid  The TX FME Rm Alain /691144423 from huaw=
ei is informed","landry.etame@ihstowers.com","4641","16-07-2024 20:56:49","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0002628549","M=
efou-Assi","","16-07-2024 20:55:13","16-07-2024 20:19:03","16-07-2024 20:21=
:18","Active//No power issue on site,site on Grid with Ubaie=3D53.3 V  The =
Tx FME Lionnel//694693436 From Huawei is informed.","Fanda Brice","Customer=
 Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm=
","Active//No power issue on site,site on Grid with Ubaie=3D53.3 V  The Tx =
FME Lionnel//694693436 From Huawei is informed.","landry.etame@ihstowers.co=
m","2171","16-07-2024 20:55:13","Sagemcom CMR"
"Closed Complete","Site Down","CTR_210","IHS_YND_071","NOCINC0002628126","S=
calom","","16-07-2024 19:30:23","16-07-2024 19:18:19","16-07-2024 21:14:05"=
,"No power issue site on grid with U=3D54,5v TX Wandji //652444763//  from =
ZTE is working on site","Paul BIBOUM","Customer Equipment Failure","Active"=
,"Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on gr=
id with U=3D54,5v TX Wandji //652444763//  from ZTE is working on site","la=
ndry.etame@ihstowers.com","725","16-07-2024 19:30:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0002627977","C=
rf-Nsam","","16-07-2024 19:01:21","16-07-2024 18:56:15","16-07-2024 21:14:0=
5","No power issue site on grid with U=3D53,6v TX Mbah Hosiah from Huawei i=
s informed","MINKA NICOLAS","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue site on grid with U=
=3D53,6v TX Mbah Hosiah from Huawei is informed","landry.etame@ihstowers.co=
m","307","16-07-2024 19:01:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_012","IHS_YND_152","NOCINC0002627582","R=
d-Pt-Express","","16-07-2024 17:46:09","16-07-2024 17:42:57","16-07-2024 19=
:22:50","No power issue site on grid with U=3D53,2v TX Olivier //651559985/=
/  from ZTE is working on site ","","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue site on grid=
 with U=3D53,2v TX Olivier //651559985//  from ZTE is working on site ","la=
ndry.etame@ihstowers.com","194","16-07-2024 17:46:09","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0002627325","Dong",""=
,"16-07-2024 17:02:20","16-07-2024 16:46:48","16-07-2024 17:16:58","Cascade=
d Incident from TTO2433787 - Cascade Removed From TTO2433787","Parker Tchou=
p","Cascade Outage","Passive","Cascade Passive","Cascade Passive","Generato=
r lock out alarm  // Clean fuel system and start Gen manually","system","45=
62","16-07-2024 17:02:20","Sagemcom CMR"
"Closed Complete","Site Down","T1303","IHS_YND_396","NOCINC0002626990","Nko=
lmvack","","16-07-2024 16:00:23","16-07-2024 14:16:56","16-07-2024 16:29:51=
","site went down because Gen start and stop with alarm low oil pressure //=
 He add oil and manually started the Gen","Parker Tchoup","Equipment Repair=
","Passive","ACDG Gen","ACDG - Low Oil Pressure","site went down because Ge=
n start and stop with alarm low oil pressure // He add oil and manually sta=
rted the Gen","denis.mballa@ihstowers.com","6208","16-07-2024 16:00:23","Sa=
gemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002626910","M=
asque","","16-07-2024 15:46:12","16-07-2024 15:43:07","16-07-2024 17:10:32"=
,"Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V  The TX F=
ME  Eloundou // 693212405// From  Huawei is informed","Fabrice Pouakam","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V  T=
he TX FME  Eloundou // 693212405// From  Huawei is informed","landry.etame@=
ihstowers.com","187","16-07-2024 15:46:12","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0002626660","Nko=
mkana","","16-07-2024 15:12:49","16-07-2024 15:05:34","16-07-2024 18:57:34"=
,"Grid outage. No space to deploy the MDG // Grid return","","Grid Supply",=
"Passive","Grid","National Grid - Grid Outage Issue","Grid outage. No space=
 to deploy the MDG // Grid return","denis.mballa@ihstowers.com","621","16-0=
7-2024 15:12:49","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002626624","Tsi=
nga","","16-07-2024 15:05:52","16-07-2024 15:00:40","16-07-2024 15:22:29","=
site went down due to disfunctionning of controller// voltage stabilized ( =
controller to be replaced)","Mboua Thierry","Equipment Repair","Passive","H=
ybrid","Hybrid Module","site went down due to disfunctionning of controller=
// voltage stabilized ( controller to be replaced)","denis.mballa@ihstowers=
.com","315","16-07-2024 15:05:52","Sagemcom CMR"
"Closed Complete","Site Down","T2586","IHS_YND_747","NOCINC0002626613","Ako=
k Ndoe Yde","","16-07-2024 15:04:16","16-07-2024 14:59:05","16-07-2024 15:4=
6:35","Grid fluctuation site went down because Gen failed to start due to G=
rid bad voltage// He bypass the Grid and site on Gen","Hyemafo Gildas","Gri=
d Supply","Passive","Grid","National Grid - Phase Controller Faulty","Grid =
fluctuation site went down because Gen failed to start due to Grid bad volt=
age// He bypass the Grid and site on Gen","denis.mballa@ihstowers.com","314=
","16-07-2024 15:04:16","Sagemcom CMR"
"Closed Complete","Site Down","T0632","IHS_YND_101","NOCINC0002626609","Nsi=
meyong Shell","","16-07-2024 15:02:45","16-07-2024 14:57:33","16-07-2024 15=
:05:29","Grid outage, site went down before gen start due to poor battery b=
ackup // Gen start automaticaly","MINKA NICOLAS","Equipment Repair","Passiv=
e","Control Panel","Power Cabinet - Battery Low","Grid outage, site went do=
wn before gen start due to poor battery backup // Gen start automaticaly","=
denis.mballa@ihstowers.com","313","16-07-2024 15:02:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0002626597","B=
iyemassi LAC","","16-07-2024 14:58:56","16-07-2024 14:28:50","16-07-2024 14=
:30:35","No power issue site on grid with U=3D53,2v TX Ebongue Ebone //6734=
77212//  from ZTE is working on site ","","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","No power issue site o=
n grid with U=3D53,2v TX Ebongue Ebone //673477212//  from ZTE is working o=
n site ","landry.etame@ihstowers.com","1810","16-07-2024 14:58:56","Sagemco=
m CMR"
"Closed Complete","Site Down","T0668","IHS_YND_372","NOCINC0002626248","Bon=
djock","","16-07-2024 14:03:23","16-07-2024 13:50:17","16-07-2024 14:05:46"=
,"Grid outage, site went down before gen start due to poor battery backup /=
/ Gen start automaticaly","Fanda Brice","Equipment Repair","Passive","Contr=
ol Panel","Power Cabinet - Battery Low","Grid outage, site went down before=
 gen start due to poor battery backup // Gen start automaticaly","joelle.ek=
essi@ihstowers.com","871","16-07-2024 14:03:23","Sagemcom CMR"
"Closed Complete","Site Down","CTR_472","IHS_YND_698","NOCINC0002625467","E=
BOM","","16-07-2024 12:45:47","16-07-2024 12:19:41","16-07-2024 13:10:22","=
Active//No  power issue on site ;site onGrid with Ubaie=3D 54.6 V  team DEN=
IS/693675998 from ZTE is working on site","Hyemafo Gildas","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Acti=
ve//No  power issue on site ;site onGrid with Ubaie=3D 54.6 V  team DENIS/6=
93675998 from ZTE is working on site","emmanuel.ghani@ihstowers.com","1567"=
,"16-07-2024 12:45:47","Sagemcom CMR"
"Closed Complete","Site Down","CTR_488","IHS_YND_583","NOCINC0002625419","N=
sam Sofavinc T0","","16-07-2024 12:39:51","16-07-2024 12:24:46","16-07-2024=
 12:30:01","","MINKA NICOLAS","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No  power issue on site ;site onG=
rid with Ubaie=3D 53,4 V Team Claude ADIOBO //699029796 // From Omnium Serv=
ice is working on site","emmanuel.ghani@ihstowers.com","906","16-07-2024 12=
:39:51","Sagemcom CMR"
"Closed Complete","Warning","CTR_023","IHS_YND_243","NOCINC0002625008","Ema=
na","","16-07-2024 11:49:48","","","Grid outage ,site alarming because Low =
voltage //Grid power return","","Warning","Warning","POWER","Warning - Low =
Voltage","Grid outage ,site alarming because Low voltage //Grid power retur=
n","marie.kwin@ihstowers.com","3","16-07-2024 11:49:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_121","IHS_YND_151","NOCINC0002624973","T=
amtam Weekend","","16-07-2024 11:42:58","16-07-2024 11:32:55","16-07-2024 1=
2:40:44","Active// No power issue on site, site on grid with Ubaie=3D54,8V =
Hilaire /699716027 / from ZTE is working on site","Hyemafo Gildas","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","no power issue on site, site on grid with Ubaie=3D54,8V Hilaire /699716=
027 / from ZTE is working on site","emmanuel.ghani@ihstowers.com","605","16=
-07-2024 11:42:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_604","IHS_YND_252","NOCINC0002624849","K=
oweit City","","16-07-2024 11:26:18","16-07-2024 11:16:12","16-07-2024 13:1=
0:18","Active//No  power issue on site ;site onGrid with Ubaie=3D 54.5 V  t=
eam Serge //  699825854) // from ZTE is working on site","Albran Byorel","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No  power issue on site ;site onGrid with Ubaie=3D 54.5 V=
  team Serge //  699825854) // from ZTE is working on site","emmanuel.ghani=
@ihstowers.com","606","16-07-2024 11:26:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0002624717","O=
bobogo","","16-07-2024 10:59:42","16-07-2024 10:51:37","16-07-2024 11:40:54=
","Active//No  power issue on site ;site onGrid with Ubaie=3D 54.6 V  Serge=
  699454235 from ZTE is working on site","MINKA NICOLAS","Customer Equipmen=
t Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active=
//No  power issue on site ;site onGrid with Ubaie=3D 54.6 V  Serge  6994542=
35 from ZTE is working on site","emmanuel.ghani@ihstowers.com","487","16-07=
-2024 10:59:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_209","IHS_YND_070","NOCINC0002624626","E=
foulan","","16-07-2024 10:42:35","16-07-2024 10:33:26","16-07-2024 11:40:49=
","Active//No  power issue on site ;site onGrid with Ubaie=3D 54.4 V Domini=
que // 694552106// FROM ZTE is working on site","MINKA NICOLAS","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active//No  power issue on site ;site onGrid with Ubaie=3D 54.4 V Dominiqu=
e // 694552106// FROM ZTE is working on site","emmanuel.ghani@ihstowers.com=
","549","16-07-2024 10:42:35","Sagemcom CMR"
"Closed Complete","Warning","T1103","IHS_YND_242","NOCINC0002624603","Mball=
a 4","","16-07-2024 10:39:03","","","SITE ON BATTERY","Delor Telezing","War=
ning","Warning","POWER","Warning - AC Phase 1 Voltage low","Alarm cleared",=
"kombi.samuel@ihstowers.com","3","16-07-2024 10:39:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_542","NOCINC0002624493","SAA Entr=
ance","","16-07-2024 10:20:00","16-07-2024 10:18:25","16-07-2024 10:27:45",=
"Cascaded Incident from TTO2430664","Parker Tchoup","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","site went down due to work (Ulrich=
 / 656072680 / working on site /Normalisation(the cable that had been stole=
n))// End of work","system","95","16-07-2024 10:20:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_405","NOCINC0002624494","Saa","",=
"16-07-2024 10:20:00","16-07-2024 10:18:25","16-07-2024 10:27:45","Cascaded=
 Incident from TTO2430664","Parker Tchoup","Cascade Outage","Passive","Casc=
ade Passive","Cascade Passive","site went down due to work (Ulrich / 656072=
680 / working on site /Normalisation(the cable that had been stolen))// End=
 of work","system","95","16-07-2024 10:20:00","Sagemcom CMR"
"Closed Complete","Site Down","T0142","IHS_YND_404","NOCINC0002624490","SAA=
 2","IHS_YND_542, IHS_YND_405","16-07-2024 10:19:29","16-07-2024 10:18:25",=
"16-07-2024 10:27:45","site went down due to work (Ulrich / 656072680 / wor=
king on site /Normalisation(the cable that had been stolen))// End of work"=
,"Parker Tchoup","Installation Activity","Passive","Planned Activity","Inst=
allation Activity","site went down due to work (Ulrich / 656072680 / workin=
g on site /Normalisation(the cable that had been stolen))// End of work","j=
oelle.ekessi@ihstowers.com","65","16-07-2024 10:19:29","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0002624259","S=
calom-IHS","","16-07-2024 09:47:26","16-07-2024 09:38:14","16-07-2024 10:55=
:45","ACTIVE //No power issue ;site on Grid with Ubaie =3D53V The Team  MBO=
'OSSI / 697417716 from ZTE working on site swapp ,","","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE /=
/No power issue ;site on Grid with Ubaie =3D53V The Team  MBO'OSSI / 697417=
716 from ZTE working on site swapp ,","emmanuel.ghani@ihstowers.com","554",=
"16-07-2024 09:47:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_074","IHS_YND_166","NOCINC0002624236","D=
amas","","16-07-2024 09:42:01","16-07-2024 09:34:55","16-07-2024 10:50:59",=
"ACTIVE //No power issue ;site on Grid with Ubaie =3D52.2V The Team Larry /=
 694675611 from ZTE working on site swapp ,","MINKA NICOLAS","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","AC=
TIVE //No power issue ;site on Grid with Ubaie =3D52.2V The Team Larry / 69=
4675611 from ZTE working on site swapp ,","emmanuel.ghani@ihstowers.com","4=
28","16-07-2024 09:42:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0002624235","M=
ontee-Jouvence-II","","16-07-2024 09:41:04","16-07-2024 09:33:30","16-07-20=
24 13:15:27","","Hyemafo Gildas","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","No  power issue on site ;site =
onGrid with Ubaie=3D 54.6 V The Team Arno  Biloa//699037504 from ZTE is wor=
king on site","emmanuel.ghani@ihstowers.com","455","16-07-2024 09:41:04","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_538","IHS_YND_143","NOCINC0002624214","B=
yemassi Carrefour","","16-07-2024 09:36:06","16-07-2024 09:26:59","16-07-20=
24 10:00:39","Active//No  power issue on site ;site onGrid with Ubaie=3D 54=
.6 V TEAM KILEGUE // 694212006 from ZTE is working on site","Paul BIBOUM","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No  power issue on site ;site onGrid with Ubaie=3D 54.6 =
V TEAM KILEGUE // 694212006 from ZTE is working on site","emmanuel.ghani@ih=
stowers.com","548","16-07-2024 09:36:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_339","IHS_YND_073","NOCINC0002624211","C=
hapelle-Obili","","16-07-2024 09:33:53","16-07-2024 09:25:46","16-07-2024 1=
0:15:38","ACTIVE //No power issue ;site on Grid with Ubaie =3D54,5V The Tea=
m  MAMOUDOU / 691306125 from ZTE working on site swapp ,","Paul BIBOUM","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","ACTIVE //No power issue ;site on Grid with Ubaie =3D54,5V The Team=
  MAMOUDOU / 691306125 from ZTE working on site swapp ,","emmanuel.ghani@ih=
stowers.com","488","16-07-2024 09:33:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_261","IHS_YND_161","NOCINC0002624148","S=
ofavinc","","16-07-2024 09:22:21","16-07-2024 09:12:15","16-07-2024 09:20:1=
3","Active// No power issue on site, site on grid with Ubaie=3D54,5V FME Bo=
ris KENFACK/693932700) from OMNIUM  is working on site","MINKA NICOLAS","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active// No power issue on site, site on grid with Ubaie=3D54,5V F=
ME Boris KENFACK/693932700) from OMNIUM  is working on site","emmanuel.ghan=
i@ihstowers.com","609","16-07-2024 09:22:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_696","IHS_YND_713","NOCINC0002624123","N=
KONGKARAK","","16-07-2024 09:17:40","16-07-2024 06:37:13","16-07-2024 06:52=
:18","ACTIVE / No power issue site on grid with U=3D54.4 V The Tx FME Moham=
adou (691144435) from Hauawei is informed,","TIENTCHEU NZETCHIEU GAEL","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","ACTIVE / No power issue site on grid with U=3D54.4 V The Tx FME Moh=
amadou (691144435) from Hauawei is informed,","marie.kwin@ihstowers.com","1=
7032","16-07-2024 09:17:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_056","IHS_YND_100","NOCINC0002624082","S=
hell-Nsimeyong","","16-07-2024 09:08:30","16-07-2024 09:02:25","16-07-2024 =
09:25:36","Active// No power issue on site, site on grid with Ubaie=3D54,6V=
 FME MAGOTSAP/677085072) from ZTE is working on site","MINKA NICOLAS","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active// No power issue on site, site on grid with Ubaie=3D54,6V FME=
 MAGOTSAP/677085072) from ZTE is working on site","emmanuel.ghani@ihstowers=
.com","366","16-07-2024 09:08:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_149","IHS_YND_517","NOCINC0002624081","M=
ontee-Des-Soeurs","","16-07-2024 09:07:41","16-07-2024 08:58:30","16-07-202=
4 09:50:22","Active//No  power issue on site ;site onGrid with Ubaie=3D 54.=
6 V The Team Arno  Biloa//699037504 from ZTE is working on site","Hyemafo G=
ildas","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","Active//No  power issue on site ;site onGrid with Ubaie=
=3D 54.6 V The Team Arno  Biloa//699037504 from ZTE is working on site","em=
manuel.ghani@ihstowers.com","552","16-07-2024 09:07:41","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_173","NOCINC0002624064","AWAE OCM=
","","16-07-2024 09:05:01","16-07-2024 08:48:00","16-07-2024 10:17:18","Cas=
caded Incident from TTO2430181","Mba Lazare Herve","Cascade Outage","Passiv=
e","Cascade Passive","Cascade Passive","grid outage, gen fails to start due=
 to gen battery  theft//gen started with backup battery","system","1021","1=
6-07-2024 09:05:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_249","NOCINC0002624066","Biteng-M=
aetur","","16-07-2024 09:05:01","16-07-2024 08:48:00","16-07-2024 10:17:18"=
,"Cascaded Incident from TTO2430181","Mba Lazare Herve","Cascade Outage","P=
assive","Cascade Passive","Cascade Passive","grid outage, gen fails to star=
t due to gen battery  theft//gen started with backup battery","system","102=
1","16-07-2024 09:05:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_179","NOCINC0002624065","Essomba"=
,"","16-07-2024 09:05:01","16-07-2024 08:48:00","16-07-2024 10:17:18","Casc=
aded Incident from TTO2430181","Mba Lazare Herve","Cascade Outage","Passive=
","Cascade Passive","Cascade Passive","grid outage, gen fails to start due =
to gen battery  theft//gen started with backup battery","system","1021","16=
-07-2024 09:05:01","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_172","NOCINC0002624063","Tradex-N=
komo","","16-07-2024 09:05:00","16-07-2024 08:48:00","16-07-2024 10:17:18",=
"Cascaded Incident from TTO2430181","Albran Byorel","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","grid outage, gen fails to start du=
e to gen battery  theft//gen started with backup battery","system","1021","=
16-07-2024 09:05:00","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_292","NOCINC0002624062","Bitoto",=
"","16-07-2024 09:05:00","16-07-2024 08:48:00","16-07-2024 10:17:18","Casca=
ded Incident from TTO2430181","Mba Lazare Herve","Cascade Outage","Passive"=
,"Cascade Passive","Cascade Passive","grid outage, gen fails to start due t=
o gen battery  theft//gen started with backup battery","system","1021","16-=
07-2024 09:05:00","Sagemcom CMR"
"Closed Complete","Site Down","T1284","IHS_YND_248","NOCINC0002624028","Bit=
eng","IHS_YND_292, IHS_YND_172, IHS_YND_173, IHS_YND_179, IHS_YND_249","16-=
07-2024 08:57:04","16-07-2024 08:48:00","16-07-2024 10:19:55","grid outage,=
 gen fails to start due to gen battery  stole//gen started with backup batt=
ery","Mba Lazare Herve","Site Asset Theft","Theft","Theft","Generator Batte=
ry Theft","grid outage, gen fails to start due to gen battery  theft//gen s=
tarted with backup battery","joelle.ekessi@ihstowers.com","718","16-07-2024=
 08:57:04","Sagemcom CMR"
"Closed Complete","Site Down","T3216","IHS_YND_762","NOCINC0002623952","Nko=
lfon Cimencam","","16-07-2024 08:36:00","16-07-2024 08:35:53","16-07-2024 1=
4:10:23","","Hyemafo Gildas","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","No power issue, site is on Grid wi=
th Ubaie=3D54.4V ,TX RM martial(690087047) from Hauawei is informed","joell=
e.ekessi@ihstowers.com","8","16-07-2024 08:36:00","Sagemcom CMR"
"Closed Complete","Site Down","T0579","IHS_YND_366","NOCINC0002623942","Man=
doumba MTN","","16-07-2024 08:34:07","16-07-2024 08:27:02","16-07-2024 10:2=
0:06","ACTIVE / No power issue site on Grid with U=3D53.6  V The Tx FME  Et=
ienne  (695033981)   from Hauawei  is informed,","Kemeni Franklin","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","ACTIVE / No power issue site on Grid with U=3D53.6  V The Tx FME  Etien=
ne  (695033981)   from Hauawei  is informed,","joelle.ekessi@ihstowers.com"=
,"426","16-07-2024 08:34:07","Sagemcom CMR"
"Closed Complete","Site Down","CTR_238","IHS_YND_148","NOCINC0002623882","C=
hapelle-Nsimeyong","","16-07-2024 08:21:59","16-07-2024 07:40:44","16-07-20=
24 07:41:20","ACTIVE //No power issue ;site on Grid with Ubaie =3D54.4V The=
 Team Ngueme / 694675611 from ZTE working on site swapp ,","MINKA NICOLAS",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","ACTIVE //No power issue ;site on Grid with Ubaie =3D54.4V The T=
eam Ngueme / 694675611 from ZTE working on site swapp ,","emmanuel.ghani@ih=
stowers.com","2477","16-07-2024 08:21:59","Sagemcom CMR"
"Closed Complete","Site Down","T0236","IHS_YND_373","NOCINC0002623861","Mal=
oun","","16-07-2024 08:16:03","16-07-2024 08:12:59","16-07-2024 09:21:48","=
ACTIVE / No power issue site on Gen with U=3D55.8  V The Tx FME  Etienne  (=
695033981)   from Hauawei  is informed,","Kemeni Franklin","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTI=
VE / No power issue site on Gen with U=3D55.8  V The Tx FME  Etienne  (6950=
33981)   from Hauawei  is informed,","joelle.ekessi@ihstowers.com","186","1=
6-07-2024 08:16:03","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_341","NOCINC0002623773","Lobo OCM=
","","16-07-2024 08:02:10","16-07-2024 07:59:13","16-07-2024 08:04:34","Cas=
caded Incident from TTO2429897","TIENTCHEU NZETCHIEU GAEL","Cascade Outage"=
,"Passive","Cascade Passive","Cascade Passive","Grid outage, site went down=
 before gen start due to poor battery backup // Gen start automaticaly","sy=
stem","177","16-07-2024 08:02:10","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002623771","N=
KOMEKUI OCM","IHS_YND_341","16-07-2024 08:01:22","16-07-2024 07:59:13","16-=
07-2024 08:04:34","Grid outage, site went down before gen start due to poor=
 battery backup // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equi=
pment Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid=
 outage, site went down before gen start due to poor battery backup // Gen =
start automaticaly","emmanuel.ghani@ihstowers.com","132","16-07-2024 08:01:=
22","Sagemcom CMR"
"Closed Complete","Site Down","T0091","IHS_YND_314","NOCINC0002623752","Sou=
s Prefecture","","16-07-2024 07:57:18","16-07-2024 07:10:13","16-07-2024 10=
:29:14","Active//No power issue, site is on Grid with Ubaie=3D54.45V ,TX RM=
 martial(690087047) from Hauawei is informed","Fanda Brice","Customer Equip=
ment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Act=
ive//No power issue, site is on Grid with Ubaie=3D54.45V ,TX RM martial(690=
087047) from Hauawei is informed","joelle.ekessi@ihstowers.com","2825","16-=
07-2024 07:57:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002623687","M=
asque","","16-07-2024 07:44:07","16-07-2024 07:36:57","16-07-2024 09:30:24"=
,"Active//No power issue on site.Site on Grid with Ubaie=3D54.5 V  The TX F=
ME  Eloundou // 693212405// of Huawei is informed ","Fabrice Pouakam","Cust=
omer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault A=
larm","Active//No power issue on site.Site on Grid with Ubaie=3D54.5 V  The=
 TX FME  Eloundou // 693212405// of Huawei is informed ","emmanuel.ghani@ih=
stowers.com","432","16-07-2024 07:44:07","Sagemcom CMR"
"Closed Complete","Site Down","T0577","IHS_YND_339","NOCINC0002623613","Ebe=
ba","","16-07-2024 07:30:51","16-07-2024 07:26:46","16-07-2024 08:19:53","A=
CTIVE / No power issue site on battery with U=3D50  V The Tx FME  Etienne  =
(695033981)   from Hauawei  is informed,","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE =
/ No power issue site on battery with U=3D50  V The Tx FME  Etienne  (69503=
3981)   from Hauawei  is informed,","joelle.ekessi@ihstowers.com","247","16=
-07-2024 07:30:51","Sagemcom CMR"
"Closed Complete","Site Down","T0532","IHS_YND_239","NOCINC0002623565","Men=
dong2","","16-07-2024 07:19:52","16-07-2024 07:16:48","16-07-2024 08:56:16"=
,"Grid fluctuation site went down because Gen failed to start sue to poor b=
attery backup// Gen manually started","Hyemafo Gildas","Grid Supply","Passi=
ve","Grid","National Grid - Phase Controller Faulty","Grid fluctuation site=
 went down because Gen failed to start sue to poor battery backup// Gen man=
ually started","joelle.ekessi@ihstowers.com","184","16-07-2024 07:19:52","S=
agemcom CMR"
"Closed Complete","Site Down","T0150","IHS_YND_347","NOCINC0002623548","Nke=
ng likok","","16-07-2024 07:12:16","16-07-2024 07:08:11","16-07-2024 09:08:=
43","No power issue on site ,site on battery with Ubaie=3D49,8  V (Solar Hy=
brid Gen site  start threshold =3D47 V) The Tx FME   Etienne /695033981 is =
informed. ","Kemeni Franklin","Customer Equipment Failure","Active","Active=
 Equipment Failure","BTS/TX Fault Alarm","No power issue on site ,site on b=
attery with Ubaie=3D49,8  V (Solar Hybrid Gen site  start threshold =3D47 V=
) The Tx FME   Etienne /695033981 is informed. ","joelle.ekessi@ihstowers.c=
om","246","16-07-2024 07:12:16","Sagemcom CMR"
"Closed Complete","Site Down","T1945","IHS_YND_696","NOCINC0002623506","Bar=
riere IHS","","16-07-2024 06:58:19","16-07-2024 06:56:15","16-07-2024 07:30=
:44","Grid outage site went went down because Gen failed to start due Hybri=
d system dysfonction// Gen manually started","Hyemafo Gildas","Equipment Re=
pair","Passive","Hybrid","Hybrid Module","Grid outage site went went down b=
ecause Gen failed to start due Hybrid system dysfonction// Gen manually sta=
rted","joelle.ekessi@ihstowers.com","125","16-07-2024 06:58:19","Sagemcom C=
MR"
"Closed Complete","Site Down","T1852","IHS_YND_335","NOCINC0002623434","Ang=
ongo","","16-07-2024 06:31:57","16-07-2024 06:29:52","16-07-2024 07:29:52",=
"Active: no power issue site on grid with U=3D54,9, The RM Martial /6900870=
47/from Huawei is informed","Fanda Brice","Customer Equipment Failure","Act=
ive","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power issu=
e site on grid with U=3D54,9, The RM Martial /690087047/from Huawei is info=
rmed","joelle.ekessi@ihstowers.com","126","16-07-2024 06:31:57","Sagemcom C=
MR"
"Closed Complete","Site Down","T1477","IHS_YND_674","NOCINC0002623266","Mfo=
u EPC","","16-07-2024 05:30:21","16-07-2024 05:20:16","16-07-2024 06:35:54"=
," Grid outage site went down because Gen started and stopped due to ""high=
 temp"" alarm caused  //He  added water and Gen manually started ","Mba Laz=
are Herve","Equipment Repair","Passive","ACDG Gen","ACDG - High Engine Temp=
 - Coolant Level Issue"," Grid outage site went down because Gen started an=
d stopped due to ""high temp"" alarm caused  //He  added water and Gen manu=
ally started ","ludivine.ngamaleu@ihstowers.com","909","16-07-2024 05:30:21=
","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0002623202","S=
IMBOCK BONAMBAPE","","16-07-2024 05:04:10","15-07-2024 23:08:57","15-07-202=
4 23:12:43","ACTIVE //No power issue ;site on Grid with Ubaie =3D54,5V The =
Team   Camil / 691144395 from ZTE working on site swapp ,","Hyemafo Gildas"=
,"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX F=
ault Alarm","ACTIVE //No power issue ;site on Grid with Ubaie =3D54,5V The =
Team   Camil / 691144395 from ZTE working on site swapp ,","etienne.itondo@=
ihstowers.com","21313","16-07-2024 05:04:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_205","IHS_YND_372","NOCINC0002623176","B=
ondjock","","16-07-2024 04:55:40","16-07-2024 03:36:29","16-07-2024 03:42:0=
2","Grid outage, site wen down before Gen start due to poor battery backup =
// Gen started automaticaly","Fanda Brice","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","Grid outage, site wen down befo=
re Gen start due to poor battery backup // Gen started automaticaly","etien=
ne.itondo@ihstowers.com","4753","16-07-2024 04:55:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002623114","M=
asque","","16-07-2024 04:26:16","15-07-2024 22:49:06","16-07-2024 05:24:13"=
,"Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V  The TX F=
ME  Eloundou // 693212405// From  Huawei is informed,Site up at 10:52 PM","=
Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active//No power issue on site.Site on Grid wi=
th Ubaie=3D54.3 V  The TX FME  Eloundou // 693212405// From  Huawei is info=
rmed,Site up at 10:52 PM","etienne.itondo@ihstowers.com","20234","16-07-202=
4 04:26:16","Sagemcom CMR"
"Closed Complete","Site Down","T1120","IHS_YND_542","NOCINC0002622878","SAA=
 Entrance","","16-07-2024 03:22:06","16-07-2024 03:15:01","16-07-2024 06:02=
:21","site went down because has stolen due to  the cables were disconnecte=
d in the DC BOX // He reconnected the cables","Parker Tchoup","Site Asset T=
heft","Theft","Theft","DC Cable Stolen","site went down because has stolen =
due to  the cables were disconnected in the DC BOX // He reconnected the ca=
bles","ludivine.ngamaleu@ihstowers.com","426","16-07-2024 03:22:06","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_675","IHS_YND_719","NOCINC0002621784","T=
SINGA VILLAGE 2","","15-07-2024 21:41:25","15-07-2024 21:33:17","15-07-2024=
 22:00:17","Site went down due to Hybrid system dysfunction // He manually =
started the Gen (Investigation ongoing)","Delor Telezing","Equipment Repair=
","Passive","Hybrid","Hybrid Software","Site went down due to Hybrid system=
 dysfunction // He manually started the Gen (Investigation ongoing)","kamga=
.virgile@ihstowers.com","887","15-07-2024 21:41:25","Sagemcom CMR"
"Closed Complete","Site Down","CTR_422","IHS_YND_512","NOCINC0002621533","M=
imboman-Ecole","","15-07-2024 20:57:25","15-07-2024 20:51:19","15-07-2024 2=
0:56:19"," site went down due to insufficient of rectifier on site //Site S=
tabilized","Mba Lazare Herve","Equipment Repair","Passive","Rectifier","Rec=
tifier Module"," site went down due to insufficient of rectifier on site //=
Site Stabilized","kamga.virgile@ihstowers.com","369","15-07-2024 20:57:25",=
"Sagemcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0002621035","H=
-Prince","","15-07-2024 19:13:28","15-07-2024 19:05:17","15-07-2024 19:12:1=
7","site down due to work (Thierry Mboua / 657108452 / working on site /Nor=
malisation)// End of work","Mboua Thierry","Equipment Repair","Passive","Co=
ntrol Panel","Power Cabinet - Battery Low","site down due to work (Thierry =
Mboua / 657108452 / working on site /Normalisation)// End of work","kamga.v=
irgile@ihstowers.com","491","15-07-2024 19:13:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0002620607","N=
kozoa","","15-07-2024 17:57:32","15-07-2024 17:51:25","15-07-2024 19:01:25"=
,"Grid outage.Site went down because Gen failed to start due to GEN battery=
 faulty// He started the Gen with external battery","Fabrice Pouakam","Equi=
pment Repair","Passive","ACDG Gen","ACDG - Generator Battery","Grid outage.=
Site went down because Gen failed to start due to GEN battery faulty// He s=
tarted the Gen with external battery","kamga.virgile@ihstowers.com","9009",=
"15-07-2024 17:57:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002620590","M=
asque","","15-07-2024 17:52:10","15-07-2024 17:44:02","15-07-2024 17:50:29"=
,"Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V  The TX F=
ME  Eloundou // 693212405// From  Huawei is informed","Fabrice Pouakam","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V  T=
he TX FME  Eloundou // 693212405// From  Huawei is informed","kamga.virgile=
@ihstowers.com","489","15-07-2024 17:52:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_476","IHS_YND_520","NOCINC0002619990","S=
IMBOCK BONAMBAPE","","15-07-2024 16:19:59","15-07-2024 15:04:32","15-07-202=
4 15:10:14","ACTIVE no power issue on site U=3D54,5V TX fme  Camil / 691144=
395 from ZTE working on site (SWAP)","Hyemafo Gildas","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE no=
 power issue on site U=3D54,5V TX fme  Camil / 691144395 from ZTE working o=
n site (SWAP)","kamga.virgile@ihstowers.com","4529","15-07-2024 16:19:59","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_486","IHS_YND_569","NOCINC0002619850","M=
endong Maeture","","15-07-2024 15:52:30","15-07-2024 15:22:19","15-07-2024 =
15:30:55","Active//No  power issue on site ;site on Grid with Ubaie=3D 54.2=
 V The Team Romuald//697237563 from ZTE is working(swapp) on site","Hyemafo=
 Gildas","Customer Equipment Failure","Active","Active Equipment Failure","=
BTS/TX Fault Alarm","Active//No  power issue on site ;site on Grid with Uba=
ie=3D 54.2 V The Team Romuald//697237563 from ZTE is working(swapp) on site=
","kamga.virgile@ihstowers.com","1812","15-07-2024 15:52:30","Sagemcom CMR"
"Closed Complete","Warning","T0237","IHS_YND_302","NOCINC0002619617","Nkoln=
dom","","15-07-2024 15:06:26","","","","Fabrice Pouakam","Warning","Warning=
","POWER","Warning - Site on Battery","Site on battery","ludovic.tchagna@ih=
stowers.com","11","15-07-2024 15:06:26","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0002619310","N=
guila","IHS_YND_434, IHS_YND_444","15-07-2024 14:00:01","15-07-2024 13:50:5=
6","15-07-2024 23:22:03","ACTIVE No power issue Site on BATTERY with U=3D 4=
8.8V Gen only site  The Fme tx Gregoire (654547479) from Huawei is informed=
.repetitive issue//site up at 01:56 PM","Parker Tchoup","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE =
No power issue Site on BATTERY with U=3D 48.8V Gen only site  The Fme tx Gr=
egoire (654547479) from Huawei is informed.repetitive issue//site up at 01:=
56 PM","landry.etame@ihstowers.com","547","15-07-2024 14:00:01","Sagemcom C=
MR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0002619288","Dong",""=
,"15-07-2024 13:55:20","15-07-2024 13:50:56","15-07-2024 13:52:50","Cascade=
d Incident from TTO2424662 - Cascade Removed From TTO2424662","Parker Tchou=
p","Cascade Outage","Active","Cascade Active","Cascade Active","ACTIVE No p=
ower issue Site on BATTERY with U=3D 48.8V Gen only site  The Fme tx Gregoi=
re (654547479) from Huawei is informed.repetitive issue//site up at 01:56 P=
M","system","672","15-07-2024 13:55:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0002619285","D=
onga","","15-07-2024 13:54:41","15-07-2024 13:50:56","15-07-2024 13:52:50",=
"","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","ACTIVE No power issue Site on BATTERY with U=3D 48.8V Gen only site  T=
he Fme tx Gregoire (654547479) from Huawei is informed.repetitive issue//si=
te up at 01:56 PM","landry.etame@ihstowers.com","652","15-07-2024 13:54:41"=
,"Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002619221","Jou=
vence 2000","","15-07-2024 13:42:31","15-07-2024 13:34:18","15-07-2024 15:3=
0:18","site went down because the Grid contactor dysfonction (Due to absenc=
e of 48V ) poor back up site // He blocked the Grid contactor and site on G=
rid","Delor Telezing","Equipment Repair","Passive","Control Panel","ATS-AMF=
 Issue","site went down because the Grid contactor dysfonction (Due to abse=
nce of 48V ) poor back up site // He blocked the Grid contactor and site on=
 Grid","denis.mballa@ihstowers.com","494","15-07-2024 13:42:31","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_642","IHS_YND_537","NOCINC0002619132","M=
EFOU ASSI","","15-07-2024 13:21:28","15-07-2024 13:12:23","15-07-2024 13:13=
:02","ACTIVE //No power issue  U=3D 54,9V site on Grid  ,Team Boris /698986=
611 / From ZTE working on site ","Fanda Brice","Customer Equipment Failure"=
,"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE //No powe=
r issue  U=3D 54,9V site on Grid  ,Team Boris /698986611 / From ZTE working=
 on site ","landry.etame@ihstowers.com","546","15-07-2024 13:21:28","Sagemc=
om CMR"
"Closed Complete","Site Down","CTR_069","IHS_YND_264","NOCINC0002618855","S=
imbock OCM","","15-07-2024 12:24:32","15-07-2024 12:17:26","15-07-2024 23:2=
6:57","ACTIVE //No power issue  U=3D 54,9V site on Grid  ,Team Jean /698764=
295 / From ZTE working on site  simbock","Hyemafo Gildas","Customer Equipme=
nt Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIV=
E //No power issue  U=3D 54,9V site on Grid  ,Team Jean /698764295 / From Z=
TE working on site  simbock","landry.etame@ihstowers.com","427","15-07-2024=
 12:24:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_253","IHS_YND_258","NOCINC0002618800","M=
efou-Assi","","15-07-2024 12:18:24","15-07-2024 12:13:10","15-07-2024 13:15=
:10","ACTIVE //No power issue  U=3D 53,3V site on Grid  ,Team NGUEKAM CAMIL=
LE /691144395 / From ZTE working on site","Fanda Brice","Customer Equipment=
 Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE =
//No power issue  U=3D 53,3V site on Grid  ,Team NGUEKAM CAMILLE /691144395=
 / From ZTE working on site","landry.etame@ihstowers.com","315","15-07-2024=
 12:18:24","Sagemcom CMR"
"Closed Complete","Warning","T0051","IHS_YND_297","NOCINC0002618398","Messa=
ssi","","15-07-2024 11:13:37","",""," site went alarm due to insufficient o=
f rectifier on site //Site Stabilized","Fabrice Pouakam","Warning","Warning=
","POWER","Warning - Site on Battery"," site went alarm due to insufficient=
 of rectifier on site //Site Stabilized","marie.kwin@ihstowers.com","8","15=
-07-2024 11:13:37","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_781","NOCINC0002618372","BIBOMDJI=
DJIEL","","15-07-2024 11:08:40","15-07-2024 10:53:49","15-07-2024 12:07:09"=
,"Cascaded Incident from TTO2423623","Kemeni Franklin","Cascade Outage","Pa=
ssive","Cascade Passive","Cascade Passive","Grid outage,site went down due =
to Gen contactor disfunctionned// He manually activated Gen contactor and S=
ite On Gen ","system","891","15-07-2024 11:08:40","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_EDA_056","NOCINC0002618348","Ndogbess=
ol","","15-07-2024 11:02:10","15-07-2024 10:53:49","15-07-2024 12:10:35","C=
ascaded Incident from TTO2423572","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage,site went down due to =
Gen contactor disfunctionned// He manually activated Gen contactor and Site=
 On Gen ","system","501","15-07-2024 11:02:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_286","IHS_YND_381","NOCINC0002618328","B=
oumnyebel","IHS_YND_781, IHS_EDA_056","15-07-2024 10:59:01","15-07-2024 10:=
53:49","15-07-2024 12:10:35","Grid outage,site went down due to Gen contact=
or disfunctionned// He manually activated Gen contactor and Site On Gen ","=
Kemeni Franklin","Equipment Repair","Passive","ACDG Gen","ACDG - Load Conta=
ctor","Grid outage,site went down due to Gen contactor disfunctionned// He =
manually activated Gen contactor and Site On Gen ","landry.etame@ihstowers.=
com","832","15-07-2024 10:59:01","Sagemcom CMR"
"Closed Complete","Warning","T0139","IHS_YND_381","NOCINC0002618293","Boumn=
yebel","","15-07-2024 10:57:14","","","Grid outage,site went down due to Ge=
n contactor disfunctionned// He manually activated Gen contactor and Site O=
n Gen","Kemeni Franklin","Warning","Warning","POWER","Warning - Battery Low=
 Voltage","Grid outage,site went down due to Gen contactor disfunctionned//=
 He manually activated Gen contactor and Site On Gen","marie.kwin@ihstowers=
.com","7","15-07-2024 10:57:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_044","IHS_YND_089","NOCINC0002618236","H=
-Prince","","15-07-2024 10:45:48","15-07-2024 10:41:43","15-07-2024 11:02:4=
0","Grid outage, site wen down before Gen start due to poor battery backup =
// Gen started automaticaly","Mboua Thierry","Equipment Repair","Passive","=
Control Panel","Power Cabinet - Battery Low","Grid outage, site wen down be=
fore Gen start due to poor battery backup // Gen started automaticaly","lan=
dry.etame@ihstowers.com","246","15-07-2024 10:45:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_237","IHS_YND_261","NOCINC0002618051","B=
arriere","","15-07-2024 10:19:48","15-07-2024 10:15:39","15-07-2024 10:16:0=
6","ACTIVE //No power issue  U=3D 53,7V site on Grid  ,Team David /69965628=
2 / From ZTE working on site ","Hyemafo Gildas","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE //No pow=
er issue  U=3D 53,7V site on Grid  ,Team David /699656282 / From ZTE workin=
g on site ","landry.etame@ihstowers.com","251","15-07-2024 10:19:48","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_159","IHS_YND_508","NOCINC0002618030","C=
rf-Nsam","","15-07-2024 10:14:12","15-07-2024 10:10:41","15-07-2024 11:50:4=
1","ACTIVE //No power issue  U=3D 53,8V site on Grid  ,Team Djouatsa Yvan /=
679375329 / From SCTCC (SBC) of ZTE working on site","MINKA NICOLAS","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","ACTIVE //No power issue  U=3D 53,8V site on Grid  ,Team Djouatsa Yvan=
 /679375329 / From SCTCC (SBC) of ZTE working on site","landry.etame@ihstow=
ers.com","211","15-07-2024 10:14:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002617904","M=
essassi 2","","15-07-2024 09:51:58","15-07-2024 09:46:47","15-07-2024 09:52=
:13","ACTIVE / no power issue on site Ubaie=3D54.5V site on Grid , TX FME  =
Synphorien (691316854) from Huawei is informed.  ","Fabrice Pouakam","Custo=
mer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Al=
arm","ACTIVE / no power issue on site Ubaie=3D54.5V site on Grid , TX FME  =
Synphorien (691316854) from Huawei is informed.  ","landry.etame@ihstowers.=
com","312","15-07-2024 09:51:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_409","IHS_YND_090","NOCINC0002617870","B=
ATA-Mokolo","","15-07-2024 09:43:42","15-07-2024 09:40:37","15-07-2024 11:1=
1:38","Grid Outage No Space to deploy a MDG// Grid Restored","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No Spa=
ce to deploy a MDG// Grid Restored","landry.etame@ihstowers.com","187","15-=
07-2024 09:43:42","Sagemcom CMR"
"Closed Complete","Warning","T1259","IHS_YND_424","NOCINC0002617866","Ossom=
be","","15-07-2024 09:42:08","","","Hybrid gen site // Gen start automatica=
lly","Parker Tchoup","Warning","Warning","POWER","Warning - Site on Battery=
","Hybrid gen site // Gen start automatically","marie.kwin@ihstowers.com","=
3","15-07-2024 09:42:08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_375","IHS_YND_087","NOCINC0002617740","C=
amp-Sic-Tsinga","","15-07-2024 09:19:43","15-07-2024 09:14:37","15-07-2024 =
11:03:37","Grid only site.no sapce to deploy mobile gen//Grid  power return=
","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","Gr=
id only site.no sapce to deploy mobile gen//Grid  power return","landry.eta=
me@ihstowers.com","308","15-07-2024 09:19:43","Sagemcom CMR"
"Closed Complete","Site Down","CTR_017","IHS_YND_083","NOCINC0002617700","H=
-Progres","","15-07-2024 09:17:58","15-07-2024 09:14:51","15-07-2024 11:03:=
34","Grid outage.no space to deploy mobile gen//Grid  power return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid outage=
.no space to deploy mobile gen//Grid  power return","landry.etame@ihstowers=
.com","187","15-07-2024 09:17:58","Sagemcom CMR"
"Closed Complete","Site Down","CTR_521","IHS_YND_692","NOCINC0002617618","M=
endong vallee","","15-07-2024 08:58:21","15-07-2024 08:49:09","15-07-2024 0=
8:49:10","Active//No power issue site on Grid with U=3D54,2V, TX Mba Hosiah=
 //674007438//  from Huawei is informed","Fanda Brice","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Active//=
No power issue site on Grid with U=3D54,2V, TX Mba Hosiah //674007438//  fr=
om Huawei is informed","landry.etame@ihstowers.com","553","15-07-2024 08:58=
:21","Sagemcom CMR"
"Closed Complete","Site Down","T0532","IHS_YND_239","NOCINC0002617237","Men=
dong2","","15-07-2024 06:49:14","15-07-2024 06:40:03","15-07-2024 08:21:56"=
,"Grid Outage,Gen faild to start due to Grid bad voltage and No RCP  on sit=
e//he bypassed Grid and Manually started the Gen ","Hyemafo Gildas","Grid S=
upply","Passive","Grid","National Grid - Phase Controller Faulty","Grid Out=
age,Gen faild to start due to Grid bad voltage and No RCP  on site//he bypa=
ssed Grid and Manually started the Gen ","denis.mballa@ihstowers.com","553"=
,"15-07-2024 06:49:14","Sagemcom CMR"
"Closed Complete","Site Down","SUD_016","IHS_YND_332","NOCINC0002617220","N=
KOMEKUI OCM","","15-07-2024 06:40:14","15-07-2024 06:32:06","15-07-2024 08:=
38:06","","TIENTCHEU NZETCHIEU GAEL","Cascade Outage","Active","Cascade Act=
ive","Cascade Active","ACTIVE //No power issue Ubaie=3D 53.6 V site on Gen =
 The TX FME Mohamadou 691144435//  from huawei is informed and UP at 06:38 =
AM","landry.etame@ihstowers.com","1694","15-07-2024 06:40:14","Sagemcom CMR=
"
"Closed Complete","Site Down","CTR_227","IHS_YND_341","NOCINC0002617214","L=
obo OCM","IHS_YND_332","15-07-2024 06:38:12","15-07-2024 06:32:06","15-07-2=
024 08:38:06","ACTIVE //No power issue Ubaie=3D 53.6 V site on Gen  The TX =
FME Mohamadou 691144435//  from huawei is informed and UP at 06:38 AM","TIE=
NTCHEU NZETCHIEU GAEL","Customer Equipment Failure","Active","Active Equipm=
ent Failure","BTS/TX Fault Alarm","ACTIVE //No power issue Ubaie=3D 53.6 V =
site on Gen  The TX FME Mohamadou 691144435//  from huawei is informed and =
UP at 06:38 AM","landry.etame@ihstowers.com","368","15-07-2024 06:38:12","S=
agemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002617140","M=
asque","","15-07-2024 06:25:40","15-07-2024 06:13:35","15-07-2024 06:40:35"=
,"Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V  The TX F=
ME  Eloundou // 693212405// From  Huawei is informed","Fabrice Pouakam","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V  T=
he TX FME  Eloundou // 693212405// From  Huawei is informed","landry.etame@=
ihstowers.com","727","15-07-2024 06:25:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0002616785","M=
adagascar-Yde-New","","15-07-2024 04:43:18","15-07-2024 04:37:09","15-07-20=
24 04:40:06","No power issue U=3D53,4 V site on Grid   The TX fme BRICE/650=
214096 of Huawei is informed. R=E9p=E9titif issue","","Customer Equipment F=
ailure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power =
issue U=3D53,4 V site on Grid  The TX fme BRICE/650214096 of Huawei is info=
rmed. R=E9p=E9titif issue
","alwine.fambou@ihstowers.com","372","15-07-2024 04:43:18","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0002616513","Dong",""=
,"15-07-2024 03:23:20","15-07-2024 03:11:07","15-07-2024 03:13:44","Cascade=
d Incident from TTO2421541","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","ACTIVE No power issue Site on gen with U=3D 4=
8V Gen only site  The Fme tx Gregoire (654547479) from Huawei is informed.r=
epetitive issue
","system","733","15-07-2024 03:23:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0002616495","Donga","=
","15-07-2024 03:16:30","15-07-2024 03:11:07","15-07-2024 03:13:44","Cascad=
ed Incident from TTO2421541","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE No power issue Site on gen with U=3D =
48V Gen only site  The Fme tx Gregoire (654547479) from Huawei is informed.=
repetitive issue
","system","323","15-07-2024 03:16:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0002616491","N=
guila","IHS_YND_434, IHS_YND_444","15-07-2024 03:15:15","15-07-2024 03:11:0=
7","15-07-2024 03:13:44","ACTIVE No power issue Site on gen with U=3D 48V G=
en only site    The Fme tx Gregoire (654547479) from Huawei is informed.rep=
etitive issue","Parker Tchoup","Customer Equipment Failure","Active","Activ=
e Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power issue Site on ge=
n with U=3D 48V Gen only site  The Fme tx Gregoire (654547479) from Huawei =
is informed.repetitive issue
","alwine.fambou@ihstowers.com","249","15-07-2024 03:15:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002616359","O=
dza II OCM","","15-07-2024 02:01:40","14-07-2024 17:04:24","15-07-2024 00:5=
0:02","Site went down due to CB OCM 100A dysjuncted in PWC  due to increase=
 load on-site  // He reamed the CB  (Site swapped  by ZTE )","Albran Byorel=
","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit Bre=
aker Issue","Site went down due to CB OCM 100A dysjuncted in PWC  due to in=
crease load on-site  // He reamed the CB  (Site swapped  by ZTE )","alwine.=
fambou@ihstowers.com","32238","15-07-2024 02:01:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002616309","M=
asque","","15-07-2024 01:48:58","15-07-2024 01:41:50","15-07-2024 01:45:31"=
,"Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V  The TX F=
ME  Eloundou // 693212405// From  Huawei is informed,Site up at 01:45 AM","=
Fabrice Pouakam","Customer Equipment Failure","Active","Active Equipment Fa=
ilure","BTS/TX Fault Alarm","Active//No power issue on site.Site on Grid wi=
th Ubaie=3D54.3 V  The TX FME  Eloundou // 693212405// From  Huawei is info=
rmed,Site up at 01:45 AM","alwine.fambou@ihstowers.com","430","15-07-2024 0=
1:48:58","Sagemcom CMR"
"Closed Complete","Site Down","T2192","IHS_YND_783","NOCINC0002616303","Lob=
o 2","","15-07-2024 01:47:15","15-07-2024 01:45:10","15-07-2024 02:32:09","=
ACTIVE No power issue Ubaie=3D 53.6 V site on Gen  The TX FME Mohamadou 691=
144435//  from huawei is informed","TIENTCHEU NZETCHIEU GAEL","Customer Equ=
ipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","A=
CTIVE No power issue Ubaie=3D 53.6 V site on Gen  The TX FME Mohamadou 6911=
44435//  from huawei is informed","ange.kongo@ihstowers.com","126","15-07-2=
024 01:47:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_378","IHS_YND_254","NOCINC0002615603","M=
vog-Manga","","14-07-2024 22:34:16","14-07-2024 22:32:07","14-07-2024 23:52=
:30","Site went down due to Grid BAD voltage // He make the bridge on good =
phases","Albran Byorel","Grid Supply","Passive","Grid","National Grid - Pha=
se Controller Faulty","Site went down due to Grid BAD voltage // He make th=
e bridge on good phases","alwine.fambou@ihstowers.com","131","14-07-2024 22=
:34:16","Sagemcom CMR"
"Closed Complete","Site Down","T1399","IHS_YND_515","NOCINC0002615467","Eto=
ug ebe Meweulo","","14-07-2024 22:03:18","14-07-2024 21:59:07","14-07-2024 =
22:03:21","Site went down due to Grid BAD voltage // He make the bridge on =
good phases","Hyemafo Gildas","Grid Supply","Passive","Grid","National Grid=
 - Phase Controller Faulty","Site went down due to Grid BAD voltage // He m=
ake the bridge on good phases","ludivine.ngamaleu@ihstowers.com","252","14-=
07-2024 22:03:18","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002615239","M=
asque","","14-07-2024 21:24:41","14-07-2024 14:53:43","14-07-2024 14:54:06"=
,"Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V  The TX F=
ME  Eloundou // 693212405// From  Huawei is informed","Fabrice Pouakam","Cu=
stomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault=
 Alarm","Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V  T=
he TX FME  Eloundou // 693212405// From  Huawei is informed","etienne.itond=
o@ihstowers.com","23458","14-07-2024 21:24:41","Sagemcom CMR"
"Closed Complete","Warning","T1399","IHS_YND_515","NOCINC0002615144","Etoug=
 ebe Meweulo","","14-07-2024 21:06:03","","","","Hyemafo Gildas","Warning",=
"Warning","POWER","Warning - AC Phase 1 Current Low","Alarm cleared","ludiv=
ine.ngamaleu@ihstowers.com","2","14-07-2024 21:06:03","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0002615125","M=
adagascar-Yde-New","","14-07-2024 21:01:28","14-07-2024 20:21:18","14-07-20=
24 20:25:41","Active//No power issue on site.Site on Grid with Ubaie=3D53,8=
 V  The  TX fme BRICE/650214096 of Huawei is informed. R=E9p=E9titif issue"=
,"","Customer Equipment Failure","Active","Active Equipment Failure","BTS/T=
X Fault Alarm","Active//No power issue on site.Site on Grid with Ubaie=3D53=
,8 V  The  TX fme BRICE/650214096 of Huawei is informed. R=E9p=E9titif issu=
e","etienne.itondo@ihstowers.com","2412","14-07-2024 21:01:28","Sagemcom CM=
R"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0002613893","O=
bobogo","","14-07-2024 17:59:54","14-07-2024 16:55:42","14-07-2024 18:18:47=
","No power issue on site.Site on Grid with Ubaie=3D54.9 V  The Team Nzitou=
o Thierry //693308346 from ZTE is working on site","MINKA NICOLAS","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","No power issue on site.Site on Grid with Ubaie=3D54.9 V  The Team Nzito=
uo Thierry //693308346 from ZTE is working on site","etienne.itondo@ihstowe=
rs.com","3853","14-07-2024 17:59:54","Sagemcom CMR"
"Closed Complete","Site Down","T1570","IHS_YND_140","NOCINC0002613543","BIS=
CUITERIE","","14-07-2024 16:47:28","14-07-2024 16:42:22","14-07-2024 16:50:=
42","Grid outage, site went down before gen start due to poor battery backu=
p // Gen started  automaticaly","Paul BIBOUM","Equipment Repair","Passive",=
"Control Panel","Power Cabinet - Fans Faulty","Grid outage, site went down =
before gen start due to poor battery backup // Gen started  automaticaly","=
ludivine.ngamaleu@ihstowers.com","307","14-07-2024 16:47:28","Sagemcom CMR"
"Closed Complete","Site Down","CTR_373","IHS_YND_007","NOCINC0002613512","M=
ontee-Anne-Rouge","","14-07-2024 16:42:33","14-07-2024 16:15:10","14-07-202=
4 16:38:45","Grid outage No space to deployed a mobile gen//grid power retu=
rn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue","=
Grid outage No space to deployed a mobile gen//grid power return","etienne.=
itondo@ihstowers.com","1644","14-07-2024 16:42:33","Sagemcom CMR"
"Closed Complete","Site Down","CTR_266","IHS_YND_179","NOCINC0002613367","E=
ssomba","","14-07-2024 16:03:06","14-07-2024 15:57:44","14-07-2024 16:02:55=
","Site went down due to 1/3 rectifier dysfuntionning //he Reset the Rectif=
ier and site on Grid ","Mba Lazare Herve","Equipment Repair","Passive","Rec=
tifier","Rectifier Module","Site went down due to 1/3 rectifier dysfuntionn=
ing //he Reset the Rectifier and site on Grid ","etienne.itondo@ihstowers.c=
om","323","14-07-2024 16:03:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0002612971","E=
koumdoum OCM","","14-07-2024 14:52:32","14-07-2024 14:19:14","14-07-2024 14=
:23:22","Active// No power issue on site ,site on Gen  with Ubaie=3D52,5 V =
TX FME Lionel steve/655184876 from Huawei is informed","Albran Byorel","Cus=
tomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault =
Alarm","Active// No power issue on site ,site on Gen  with Ubaie=3D52,5 V T=
X FME Lionel steve/655184876 from Huawei is informed","etienne.itondo@ihsto=
wers.com","1999","14-07-2024 14:52:32","Sagemcom CMR"
"Closed Complete","Site Down","CTR_337","IHS_YND_280","NOCINC0002612781","M=
essassi 2","","14-07-2024 13:57:48","14-07-2024 13:12:16","14-07-2024 13:13=
:20","no power issue on site Ubaie: 54.3V;  site on Grid. The TX FME Synpho=
rien(675295205) from Huawei is informed.//site up at 01:56 PM","Fabrice Pou=
akam","Customer Equipment Failure","Active","Active Equipment Failure","BTS=
/TX Fault Alarm","no power issue on site Ubaie: 54.3V;  site on Grid. The T=
X FME Synphorien(675295205) from Huawei is informed.//site up at 01:56 PM",=
"kamga.virgile@ihstowers.com","2734","14-07-2024 13:57:48","Sagemcom CMR"
"Closed Complete","Site Down","CTR_489","IHS_YND_546","NOCINC0002612753","B=
iyemassi LAC","","14-07-2024 13:50:15","14-07-2024 13:47:00","14-07-2024 13=
:50:47","No power issue site on grid with U=3D53,2v TX Mba Hosiah //6740074=
38//  from Huawei is informed//site up at 01:52 PM","","Customer Equipment =
Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power=
 issue site on grid with U=3D53,2v TX Mba Hosiah //674007438//  from Huawei=
 is informed//site up at 01:52 PM","kamga.virgile@ihstowers.com","196","14-=
07-2024 13:50:15","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_004","NOCINC0002611868","Av Kenne=
dy","","14-07-2024 10:44:20","14-07-2024 10:37:41","14-07-2024 16:42:43","C=
ascaded Incident from TTO2416109","","Cascade Outage","Passive","Cascade Pa=
ssive","Cascade Passive","Grid Outage. No space to deploy the MDG //Grid re=
turn","system","399","14-07-2024 10:44:20","Sagemcom CMR"
"Closed Complete","Site Down","T0470","IHS_YND_022","NOCINC0002611867","Mvo=
g Ada","IHS_YND_004","14-07-2024 10:43:46","14-07-2024 10:37:41","14-07-202=
4 16:42:43","Grid Outage. No space to deploy the MDG //Grid return","","Gri=
d Supply","Passive","Grid","National Grid - Grid Outage Issue","Grid Outage=
. No space to deploy the MDG //Grid return","alexandre.kamal@ihstowers.com"=
,"366","14-07-2024 10:43:46","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0002611744","Nlo=
ngkak","","14-07-2024 10:15:44","14-07-2024 10:00:37","14-07-2024 10:54:37"=
,"grid outage,gen failed to start due card Ge faulty//Gen started manually"=
,"Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Control P=
anel","grid outage,gen failed to start due card Ge faulty//Gen started manu=
ally","alexandre.kamal@ihstowers.com","907","14-07-2024 10:15:44","Sagemcom=
 CMR"
"Closed Complete","Site Down","CTR_245","IHS_YND_267","NOCINC0002611654","M=
imboman-Village","","14-07-2024 10:02:57","14-07-2024 08:50:43","14-07-2024=
 11:21:54","grid outage,site went down because Grid contactor faulty and ge=
n failed to start due to grid bad voltage//Gen manually started(remplacemen=
t ongoing)","Mba Lazare Herve","Equipment Repair","Passive","ACDG Gen","ACD=
G - Load Contactor","grid outage,site went down because Grid contactor faul=
ty and gen failed to start due to grid bad voltage//Gen manually started(re=
mplacement ongoing)","kamga.virgile@ihstowers.com","4335","14-07-2024 10:02=
:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0002611580","M=
adagascar-Yde-New","","14-07-2024 09:39:02","14-07-2024 09:25:46","14-07-20=
24 09:28:26","No power issue on site U=3D53,6v site on grid Brice/650214096=
/ of huawei is informed,site up at 11:04 AM","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue =
on site U=3D53,6v site on grid Brice/650214096/ of huawei is informed,site =
up at 11:04 AM","kamga.virgile@ihstowers.com","798","14-07-2024 09:39:02","=
Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_568","NOCINC0002611447","Anguissa=
 New","","14-07-2024 08:59:10","14-07-2024 08:32:09","14-07-2024 17:20:31",=
"Cascaded Incident from TTO2415594","MINKA NICOLAS","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage No space to deployed a=
 mobile gen//grid power return","system","1621","14-07-2024 08:59:10","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_015","IHS_YND_115","NOCINC0002611442","L=
abogenie","IHS_YND_568","14-07-2024 08:58:15","14-07-2024 08:32:09","14-07-=
2024 17:20:31","Grid outage No space to deployed a mobile gen//grid power r=
eturn","","Grid Supply","Passive","Grid","National Grid - Grid Outage Issue=
","Grid outage No space to deployed a mobile gen//grid power return","kamga=
.virgile@ihstowers.com","1567","14-07-2024 08:58:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002611336","N=
kolo II New","","14-07-2024 08:18:55","14-07-2024 08:12:47","14-07-2024 08:=
29:47","Active//No power issue ,site on Grid with Ubaie=3D55,2 V ,The TX FM=
E Lionel adjep//655184876//  from huawei is Informed//site up at 08:29 AM",=
"Mba Lazare Herve","Customer Equipment Failure","Active","Active Equipment =
Failure","BTS/TX Fault Alarm","Active//No power issue ,site on Grid with Ub=
aie=3D55,2 V ,The TX FME Lionel adjep//655184876//  from huawei is Informed=
//site up at 08:29 AM","kamga.virgile@ihstowers.com","370","14-07-2024 08:1=
8:55","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0002611166","Dong",""=
,"14-07-2024 07:36:20","14-07-2024 07:27:28","14-07-2024 07:30:55","Cascade=
d Incident from TTO2415276","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","ACTIVE No power issue site on battery U=3D 48=
 V Gen only site  The Fme tx Gregoire (654547479) from Huawei is informed//=
Site up at 07:41 AM","system","532","14-07-2024 07:36:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0002611165","Donga","=
","14-07-2024 07:36:20","14-07-2024 07:27:28","14-07-2024 07:30:55","Cascad=
ed Incident from TTO2415276","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE No power issue site on battery U=3D 4=
8 V Gen only site  The Fme tx Gregoire (654547479) from Huawei is informed/=
/Site up at 07:41 AM","system","532","14-07-2024 07:36:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0002611158","N=
guila","IHS_YND_434, IHS_YND_444","14-07-2024 07:34:42","14-07-2024 07:27:2=
8","14-07-2024 07:30:55","ACTIVE No power issue site on battery U=3D 48 V G=
en only site  The Fme tx Gregoire (654547479) from Huawei is informed//Site=
 up at 07:41 AM","Parker Tchoup","Customer Equipment Failure","Active","Act=
ive Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power issue site on =
battery U=3D 48 V Gen only site  The Fme tx Gregoire (654547479) from Huawe=
i is informed//Site up at 07:41 AM","kamga.virgile@ihstowers.com","436","14=
-07-2024 07:34:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002610950","M=
asque","","14-07-2024 06:48:21","14-07-2024 06:35:10","14-07-2024 06:36:45"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V  The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue//SITE UP AT =
06:55 AM","Fabrice Pouakam","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site.Site on Grid=
 with Ubaie=3D54.3 V  The TX FME  Eloundou // 693212405// From  Huawei is i=
nformed. Repetitive issue//SITE UP AT 06:55 AM","kamga.virgile@ihstowers.co=
m","792","14-07-2024 06:48:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0002610780","M=
adagascar-Yde-New","","14-07-2024 05:53:08","14-07-2024 05:48:24","14-07-20=
24 05:55:21","No power issue on site U=3D53,6v site on grid Brice/650214096=
/ of huawei is informed, r=E9p=E9titif issue","","Customer Equipment Failur=
e","Active","Active Equipment Failure","BTS/TX Fault Alarm","No power issue=
 on site U=3D53,6v site on grid Brice/650214096/ of huawei is informed, r=
=E9p=E9titif issue","emmanuel.ghani@ihstowers.com","286","14-07-2024 05:53:=
08","Sagemcom CMR"
"Closed Complete","Site Down","CTR_475","IHS_YND_127","NOCINC0002610529","T=
singa","","14-07-2024 04:09:58","14-07-2024 04:07:52","14-07-2024 04:34:19"=
,"site went down due to disfunctionning of controller// voltage stabilized =
( controller to be replaced)","Mboua Thierry","Equipment Repair","Passive",=
"ACDG Gen","ACDG - Control Panel","site went down due to disfunctionning of=
 controller// voltage stabilized ( controller to be replaced)","emmanuel.gh=
ani@ihstowers.com","288","14-07-2024 04:09:58","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0002610341","Donga","=
","14-07-2024 02:27:50","14-07-2024 02:23:20","14-07-2024 02:28:48","Cascad=
ed Incident from TTO2414338","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE No power issue Site on Gen with U=3D =
54 V Gen only site  The Fme tx Gregoire (654547479) from Huawei is informed=
.repetitive issue","system","270","14-07-2024 02:27:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0002610342","Dong",""=
,"14-07-2024 02:27:50","14-07-2024 02:23:20","14-07-2024 02:28:48","Cascade=
d Incident from TTO2414338","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","ACTIVE No power issue Site on Gen with U=3D 5=
4 V Gen only site  The Fme tx Gregoire (654547479) from Huawei is informed.=
repetitive issue","system","270","14-07-2024 02:27:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0002610340","N=
guila","IHS_YND_434, IHS_YND_444","14-07-2024 02:26:24","14-07-2024 02:23:2=
0","14-07-2024 03:00:48","ACTIVE No power issue Site on Gen with U=3D 54 V =
Gen only site    The Fme tx Gregoire (654547479) from Huawei is informed.re=
petitive issue","Parker Tchoup","Customer Equipment Failure","Active","Acti=
ve Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power issue Site on G=
en with U=3D 54 V Gen only site  The Fme tx Gregoire (654547479) from Huawe=
i is informed.repetitive issue","emmanuel.ghani@ihstowers.com","185","14-07=
-2024 02:26:24","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_029","NOCINC0002609887","Sapeur",=
"","13-07-2024 23:27:50","13-07-2024 23:19:36","13-07-2024 23:25:48","Casca=
ded Incident from TTO2413772","Mboua Thierry","Cascade Outage","Active","Ca=
scade Active","Cascade Active","ACTIVE// No power issue U=3D56.4V site on G=
rid=20
tx fme BRICE Tsague/ 650214096 from huawie is informed=20
","system","494","13-07-2024 23:27:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_076","IHS_YND_030","NOCINC0002609884","E=
-Police","IHS_YND_029","13-07-2024 23:24:45","13-07-2024 23:19:36","14-07-2=
024 02:15:48","ACTIVE// No power issue U=3D56.4V site on Grid  tx fme BRICE=
 Tsague/ 650214096 from huawie is informed ","","Customer Equipment Failure=
","Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE// No pow=
er issue U=3D56.4V site on Grid=20
tx fme BRICE Tsague/ 650214096 from huawie is informed=20
","emmanuel.ghani@ihstowers.com","312","13-07-2024 23:24:45","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0002609780","M=
adagascar-Yde-New","","13-07-2024 22:52:42","13-07-2024 22:47:35","13-07-20=
24 22:55:32","ACTIVE// No power issue on site site on Grid with Ubaie=3D53,=
4V   he fme Tx CANETTE//6912322 from Huawei is  informed, r=E9p=E9titif iss=
ue","","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","ACTIVE// No power issue on site site on Grid with Ubaie=
=3D53,4V   he fme Tx CANETTE//6912322 from Huawei is  informed, r=E9p=E9tit=
if issue","emmanuel.ghani@ihstowers.com","307","13-07-2024 22:52:42","Sagem=
com CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0002608987","B=
arriere IHS","","13-07-2024 20:49:15","13-07-2024 19:07:06","13-07-2024 21:=
16:30","No power issue on site U=3D53v site on grid Rm alain 691144423 of h=
uawei is informed","Hyemafo Gildas","Customer Equipment Failure","Active","=
Active Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D=
53v site on grid Rm alain 691144423 of huawei is informed","ange.kongo@ihst=
owers.com","6130","13-07-2024 20:49:15","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002608809","M=
asque","","13-07-2024 20:37:53","13-07-2024 20:29:42","13-07-2024 21:07:55"=
,"No power issue on site.Site on Grid with Ubaie=3D54.3 V  The TX FME  Elou=
ndou // 693212405// From  Huawei is informed. Repetitive issue","Fabrice Po=
uakam","Customer Equipment Failure","Active","Active Equipment Failure","BT=
S/TX Fault Alarm","No power issue on site.Site on Grid with Ubaie=3D54.3 V =
 The TX FME  Eloundou // 693212405// From  Huawei is informed. Repetitive i=
ssue","ange.kongo@ihstowers.com","491","13-07-2024 20:37:53","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_434","NOCINC0002608495","Donga","=
","13-07-2024 19:23:20","13-07-2024 19:18:17","13-07-2024 20:00:54","Cascad=
ed Incident from TTO2412120","Parker Tchoup","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE No power issue site on gen U=3D 48,8 =
V site on battery  The Fme tx Gregoire (654547479) from Huawei is informed.=
repetitive issue","system","303","13-07-2024 19:23:20","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0002608496","Dong",""=
,"13-07-2024 19:23:20","13-07-2024 19:18:17","13-07-2024 20:00:54","Cascade=
d Incident from TTO2412120","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","ACTIVE No power issue site on gen U=3D 48,8 V=
 site on battery  The Fme tx Gregoire (654547479) from Huawei is informed.r=
epetitive issue","system","303","13-07-2024 19:23:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0002608493","N=
guila","IHS_YND_434, IHS_YND_444","13-07-2024 19:22:24","13-07-2024 19:18:1=
7","13-07-2024 20:00:54","ACTIVE No power issue site on gen U=3D 48,8 V sit=
e on battery  The Fme tx Gregoire (654547479) from Huawei is informed.repet=
itive issue","Parker Tchoup","Customer Equipment Failure","Active","Active =
Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power issue site on gen =
U=3D 48,8 V site on battery  The Fme tx Gregoire (654547479) from Huawei is=
 informed.repetitive issue","ange.kongo@ihstowers.com","250","13-07-2024 19=
:22:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0002608197","M=
ontee-Jouvence-II","","13-07-2024 18:22:24","13-07-2024 18:18:08","13-07-20=
24 19:51:05","Active//No  power issue on site ;site onGrid with Ubaie=3D 54=
.4 V The Team Arno  Biloa//699037504 from ZTE is working on site","Hyemafo =
Gildas","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No  power issue on site ;site onGrid with Ubaie=
=3D 54.4 V The Team Arno  Biloa//699037504 from ZTE is working on site","an=
ge.kongo@ihstowers.com","258","13-07-2024 18:22:24","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0002608054","B=
arriere IHS","","13-07-2024 17:48:40","13-07-2024 17:33:26","13-07-2024 19:=
05:17","site went down due to system hybrid disfunctioning//Gen manually st=
arted","Hyemafo Gildas","Equipment Repair","Passive","Hybrid","Hybrid Modul=
e","site went down due to system hybrid disfunctioning//Gen manually starte=
d","ange.kongo@ihstowers.com","1475","13-07-2024 17:48:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_215","IHS_YND_311","NOCINC0002607754","N=
kolda","","13-07-2024 16:31:34","13-07-2024 15:48:27","13-07-2024 16:35:33"=
,"grid outage,gen failed to start due to fuse of relay Ge faulty and gen ra=
n till fuel shortage//he replaced it,grid return(refueling ongoing,Swapped =
by ZTE)","Albran Byorel","Equipment Repair","Passive","ACDG Gen","ACDG - Co=
ntrol Panel","grid outage,gen failed to start due to fuse of relay Ge fault=
y and gen ran till fuel shortage//he replaced it,grid return(refueling ongo=
ing,Swapped by ZTE)","ange.kongo@ihstowers.com","2589","13-07-2024 16:31:34=
","Sagemcom CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002607469","Pha=
rmacie SION","","13-07-2024 15:32:36","13-07-2024 15:25:30","13-07-2024 15:=
35:26","Grid outage, site went down before gen start due to poor battery ba=
ckup // grid return","Paul BIBOUM","Equipment Repair","Passive","Control Pa=
nel","Power Cabinet - Battery Low","Grid outage, site went down before gen =
start due to poor battery backup // grid return","ludivine.ngamaleu@ihstowe=
rs.com","427","13-07-2024 15:32:36","Sagemcom CMR"
"Closed Complete","Site Down","CTR_217","IHS_YND_139","NOCINC0002607434","M=
adagascar-Yde-New","","13-07-2024 15:26:50","13-07-2024 15:23:43","13-07-20=
24 18:52:44","No power issue on site U=3D53,6v site on grid Brice/650214096=
/ of huawei is informed","","Customer Equipment Failure","Active","Active E=
quipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D53,6v si=
te on grid Brice/650214096/ of huawei is informed","ange.kongo@ihstowers.co=
m","189","13-07-2024 15:26:50","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002607057","Jou=
vence 2000","","13-07-2024 14:34:01","13-07-2024 14:10:56","13-07-2024 16:2=
8:20","No power issue on site U=3D56,3v site on grid Armand of huawei is in=
formed Notice that the  problem are level ","Delor Telezing","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No=
 power issue on site U=3D56,3v site on grid Armand of huawei is informed No=
tice that the  problem are level ","ludivine.ngamaleu@ihstowers.com","1387"=
,"13-07-2024 14:34:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0002607031","E=
koumdoum OCM","","13-07-2024 14:27:51","13-07-2024 14:25:33","13-07-2024 18=
:48:38","No power issue on site U=3D52v site on grid lionnel/655184876 of h=
uawei is informed","Albran Byorel","Customer Equipment Failure","Active","A=
ctive Equipment Failure","BTS/TX Fault Alarm","No power issue on site U=3D5=
2v site on grid lionnel/655184876 of huawei is informed","ange.kongo@ihstow=
ers.com","139","13-07-2024 14:27:51","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002606556","Jou=
vence 2000","","13-07-2024 13:37:59","13-07-2024 13:31:50","13-07-2024 13:5=
4:09","Grid outage site went down before Gen started due to poor battery ba=
ck up // Gen automatically started","Delor Telezing","Equipment Repair","Pa=
ssive","Control Panel","Power Cabinet - Battery Low","Grid outage site went=
 down before Gen started due to poor battery back up // Gen automatically s=
tarted","dorothy.djantio@ihstowers.com","371","13-07-2024 13:37:59","Sagemc=
om CMR"
"Closed Complete","Site Down","T0529","IHS_YND_006","NOCINC0002606525","Pha=
rmacie SION","","13-07-2024 13:31:05","13-07-2024 13:23:54","13-07-2024 14:=
51:42","grid outage,gen ran till fuel shortage//refueling done","Paul BIBOU=
M","Fuel Outage","Passive","Diesel","Diesel Outage","grid outage,gen ran ti=
ll fuel shortage//refueling done","dorothy.djantio@ihstowers.com","433","13=
-07-2024 13:31:05","Sagemcom CMR"
"Closed Complete","Site Down","T2132","IHS_YND_729","NOCINC0002606015","Nko=
lbisson IITA LP","","13-07-2024 11:57:17","13-07-2024 11:54:58","13-07-2024=
 13:54:42","Grid outage no space to deploy MDG //Grid return","","Grid Supp=
ly","Passive","Grid","National Grid - Grid Outage Issue","Grid outage no sp=
ace to deploy a mobile Gen // Grid power return","dorothy.djantio@ihstowers=
.com","141","13-07-2024 11:57:17","Sagemcom CMR"
"Closed Complete","Site Down","T0369","IHS_YND_127","NOCINC0002605969","Tsi=
nga","","13-07-2024 11:45:29","13-07-2024 11:33:52","13-07-2024 12:18:55","=
site went down due to disfunctionning of controller// voltage stabilized ( =
controller to be replaced)","Mboua Thierry","Equipment Repair","Passive","A=
CDG Gen","ACDG - Control Panel","site went down due to disfunctionning of c=
ontroller// voltage stabilized ( controller to be replaced)","dorothy.djant=
io@ihstowers.com","1989","13-07-2024 11:45:29","Sagemcom CMR"
"Closed Complete","Site Down","T1101","IHS_YND_193","NOCINC0002605775","Bas=
tos Ekoudou","","13-07-2024 11:14:40","13-07-2024 11:02:06","13-07-2024 12:=
35:52","Access issue due to land load,grid outage gen stopped with alarm hi=
gh temp//he added water in radiator power resolved at ocm since 12:35 and p=
ower reset has been done to put up at MTn","Mboua Thierry","Access Denial",=
"Lease Or Legal","Landlord Related Issues","Access Issue - Land Lord","Acce=
ss issue due to land load,grid outage gen stopped with alarm high temp//he =
added water in radiator power resolved at ocm since 12:35 and power reset h=
as been done to put up at MTn","dorothy.djantio@ihstowers.com","3491","13-0=
7-2024 11:14:40","Sagemcom CMR"
"Closed Complete","Site Down","CTR_079","IHS_YND_306","NOCINC0002605695","N=
kozoa","","13-07-2024 10:59:01","13-07-2024 10:55:55","13-07-2024 12:52:55"=
,"Grid outage site went down because Gen started and stop with alarm over f=
requency // He reset the Gen card and manually started the Gen","Fabrice Po=
uakam","Equipment Repair","Passive","ACDG Gen","ACDG - Over Frequency","Gri=
d outage site went down because Gen started and stop with alarm over freque=
ncy // He reset the Gen card and manually started the Gen","etienne.itondo@=
ihstowers.com","1008","13-07-2024 10:59:01","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002605566","O=
lembe-Terminus","","13-07-2024 10:35:10","13-07-2024 10:17:03","13-07-2024 =
12:19:38","Grid fructuation,site went down because Gen failed to due to Gri=
d bad voltage and No rcp on site//He bypassed Grid and started Gen","Fabric=
e Pouakam","Grid Supply","Passive","Grid","National Grid - Phase Controller=
 Faulty","Grid fructuation,site went down because Gen failed to due to Grid=
 bad voltage and No rcp on site//He bypassed Grid and started Gen","etienne=
.itondo@ihstowers.com","1089","13-07-2024 10:35:10","Sagemcom CMR"
"Closed Complete","Site Down","T1244","IHS_YND_796","NOCINC0002605507","Nko=
abang Ebolmedjock","","13-07-2024 10:22:22","13-07-2024 09:57:18","13-07-20=
24 15:52:30","No power issue U=3D50,9V site on Grid The Tx FME Lionel steev=
e //655184876  from Huawei is informed","Mba Lazare Herve","Customer Equipm=
ent Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","No p=
ower issue U=3D50,9V site on Grid The Tx FME Lionel steeve //655184876  fro=
m Huawei is informed","dorothy.djantio@ihstowers.com","1504","13-07-2024 10=
:22:22","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002605462","M=
asque","","13-07-2024 10:12:12","13-07-2024 10:01:03","13-07-2024 10:05:51"=
,"Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V , The TX =
FME  Eloundou // 693212405// From  Huawei is informed.","Fabrice Pouakam","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V =
, The TX FME  Eloundou // 693212405// From  Huawei is informed.","etienne.i=
tondo@ihstowers.com","671","13-07-2024 10:12:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_154","IHS_YND_518","NOCINC0002605461","M=
ontee-Jouvence-II","","13-07-2024 10:11:14","13-07-2024 10:00:03","13-07-20=
24 10:05:56","Active//No  power issue on site ;site onGrid with Ubaie=3D 54=
.6 V The Team Arno  Biloa//699037504 from ZTE is working on site","Hyemafo =
Gildas","Customer Equipment Failure","Active","Active Equipment Failure","B=
TS/TX Fault Alarm","Active//No  power issue on site ;site onGrid with Ubaie=
=3D 54.6 V The Team Arno  Biloa//699037504 from ZTE is working on site","et=
ienne.itondo@ihstowers.com","672","13-07-2024 10:11:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_469","IHS_YND_709","NOCINC0002605406","N=
kolo II New","","13-07-2024 09:55:54","13-07-2024 09:12:41","13-07-2024 11:=
35:54","No power issue on site Ubaie=3D54.9V site on Grid. The Tx FME Lione=
l steeve //655184876  from Huawei is informed .","Mba Lazare Herve","Custom=
er Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Ala=
rm","No power issue on site Ubaie=3D54.9V site on Grid. The Tx FME Lionel s=
teeve //655184876  from Huawei is informed .","etienne.itondo@ihstowers.com=
","2594","13-07-2024 09:55:54","Sagemcom CMR"
"Closed Complete","Site Down","T0525","IHS_YND_199","NOCINC0002605220","Fla=
menco","","13-07-2024 09:07:08","13-07-2024 09:02:01","13-07-2024 09:54:01"=
,"Grid outage site went down because Gen failed tio start due to Gen card f=
aulty//He started GEN manualy","Mboua Thierry","Equipment Repair","Passive"=
,"ACDG Gen","ACDG - Control Panel","Grid outage site went down because Gen =
failed tio start due to Gen card faulty//He started GEN manualy","dorothy.d=
jantio@ihstowers.com","309","13-07-2024 09:07:08","Sagemcom CMR"
"Closed Complete","Site Down","T3152","IHS_YND_200","NOCINC0002604861","Nko=
mkana","","13-07-2024 07:51:21","13-07-2024 07:42:03","13-07-2024 12:21:51"=
," Grid outage no space to deploy a MDG //Grid power return","","Grid Suppl=
y","Passive","Grid","National Grid - Grid Outage Issue"," Grid outage no sp=
ace to deploy a MDG //Grid power return","dorothy.djantio@ihstowers.com","5=
74","13-07-2024 07:51:21","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0002604182","Dong",""=
,"13-07-2024 05:28:30","13-07-2024 05:21:34","13-07-2024 05:28:31","Cascade=
d Incident from TTO2407122","Parker Tchoup","Cascade Outage","Active","Casc=
ade Active","Cascade Active","ACTIVE No power issue site on gen U=3D 50,4 V=
 Gen only site  The Fme tx Gregoire (654547479) from Huawei is informed","s=
ystem","416","13-07-2024 05:28:30","Sagemcom CMR"
"Closed Complete","Site Down","CTR_299","IHS_YND_433","NOCINC0002604169","N=
guila","IHS_YND_434, IHS_YND_444","13-07-2024 05:25:39","13-07-2024 05:21:3=
4","13-07-2024 06:10:31","ACTIVE No power issue site on gen U=3D 50,4 V Gen=
 only site  The Fme tx Gregoire (654547479) from Huawei is informed","Parke=
r Tchoup","Customer Equipment Failure","Active","Active Equipment Failure",=
"BTS/TX Fault Alarm","ACTIVE No power issue site on gen U=3D 50,4 V Gen onl=
y site  The Fme tx Gregoire (654547479) from Huawei is informed","landry.et=
ame@ihstowers.com","246","13-07-2024 05:25:39","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0002604168","D=
onga","","13-07-2024 05:24:21","13-07-2024 05:21:34","13-07-2024 05:28:31",=
"","Parker Tchoup","Cascade Outage","Active","Cascade Active","Cascade Acti=
ve","ACTIVE No power issue site on gen U=3D 50,4 V Gen only site  The Fme t=
x Gregoire (654547479) from Huawei is informed","landry.etame@ihstowers.com=
","296","13-07-2024 05:24:21","Sagemcom CMR"
"Closed Complete","Site Down","CTR_427","IHS_YND_200","NOCINC0002603843","N=
komkana","","13-07-2024 02:37:42","13-07-2024 02:34:37","13-07-2024 03:05:0=
6","Grid Outage No space to deployed a MDG // grid return","","Grid Supply"=
,"Passive","Grid","National Grid - Grid Outage Issue","Grid Outage No space=
 to deployed a MDG // grid return","landry.etame@ihstowers.com","595","13-0=
7-2024 02:37:42","Sagemcom CMR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002603542","M=
asque","","13-07-2024 00:08:12","13-07-2024 00:04:08","13-07-2024 01:05:39"=
,"Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V , The TX =
FME  Eloundou // 693212405// From  Huawei is informed.","Fabrice Pouakam","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V =
, The TX FME  Eloundou // 693212405// From  Huawei is informed.","landry.et=
ame@ihstowers.com","247","13-07-2024 00:08:12","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002603143","O=
dza II OCM","","12-07-2024 22:25:25","12-07-2024 21:48:14","12-07-2024 23:1=
1:37","Site went down because the Cb(63A) of PWC dysjoncted due to  increas=
ed site load// he made the bridge of CB(63*63A) (Site already swapped by ZT=
E )","Albran Byorel","Equipment Repair","Passive","Control Panel","Power Ca=
binet - Circuit Breaker Issue","Site went down because the Cb(63A) of PWC d=
ysjoncted due to  increased site load// he made the bridge of CB(63*63A) (S=
ite already swapped by ZTE )","emmanuel.ghani@ihstowers.com","2232","12-07-=
2024 22:25:25","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_460","NOCINC0002603083","Matsari"=
,"","12-07-2024 22:09:50","12-07-2024 21:59:30","12-07-2024 22:57:10","Casc=
aded Incident from TTO2405853","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage site went down because Gen =
ran still fuel shortage// Refueling done","system","620","12-07-2024 22:09:=
50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_454","NOCINC0002603084","Ngouetou=
","","12-07-2024 22:09:50","12-07-2024 21:59:30","12-07-2024 22:57:10","Cas=
caded Incident from TTO2405853","Parker Tchoup","Cascade Outage","Passive",=
"Cascade Passive","Cascade Passive","Grid outage site went down because Gen=
 ran still fuel shortage// Refueling done","system","620","12-07-2024 22:09=
:50","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_456","NOCINC0002603085","MBIMBIM"=
,"","12-07-2024 22:09:50","12-07-2024 21:59:30","12-07-2024 22:57:10","Casc=
aded Incident from TTO2405853","Parker Tchoup","Cascade Outage","Passive","=
Cascade Passive","Cascade Passive","Grid outage site went down because Gen =
ran still fuel shortage// Refueling done","system","620","12-07-2024 22:09:=
50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_335","IHS_YND_474","NOCINC0002603080","Y=
oko OCM","IHS_YND_460, IHS_YND_454, IHS_YND_456","12-07-2024 22:08:38","12-=
07-2024 21:59:30","12-07-2024 22:57:10","Grid outage site went down because=
 Gen ran still fuel shortage// Refueling done","Parker Tchoup","Fuel Outage=
","Passive","Diesel","Diesel Outage","Grid outage site went down because Ge=
n ran still fuel shortage// Refueling done","emmanuel.ghani@ihstowers.com",=
"550","12-07-2024 22:08:38","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_444","NOCINC0002602527","Dong",""=
,"12-07-2024 20:34:50","12-07-2024 20:25:28","12-07-2024 21:04:22","Cascade=
d Incident from TTO2405192","Parker Tchoup","Cascade Outage","Passive","Cas=
cade Passive","Cascade Passive","Hybrid Gen  site went down because Gen sto=
pped with alarm high temp//he added water in radiator","system","562","12-0=
7-2024 20:34:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_166","IHS_YND_434","NOCINC0002602522","D=
onga","IHS_YND_444","12-07-2024 20:33:31","12-07-2024 20:25:28","12-07-2024=
 21:04:22","Hybrid Gen  site went down because Gen stopped with alarm high =
temp//he added water in radiator","Parker Tchoup","Equipment Repair","Passi=
ve","ACDG Gen","ACDG - High Engine Temp - Coolant Level Issue","Hybrid Gen =
 site went down because Gen stopped with alarm high temp//he added water in=
 radiator","emmanuel.ghani@ihstowers.com","547","12-07-2024 20:33:31","Sage=
mcom CMR"
"Closed Complete","Site Down","","IHS_YND_381","NOCINC0002602513","Boumnyeb=
el","","12-07-2024 20:31:50","12-07-2024 19:12:51","12-07-2024 19:15:42","C=
ascaded Incident from TTO2405175","Kemeni Franklin","Cascade Outage","Passi=
ve","Cascade Passive","Cascade Passive","Grid outage, site went down before=
 gen start due to poor battery backup // grid return","system","4739","12-0=
7-2024 20:31:50","Sagemcom CMR"
"Closed Complete","Site Down","CTR_058","IHS_YND_380","NOCINC0002602509","B=
oumnyebel OCM","IHS_YND_381, IHS_YND_376","12-07-2024 20:31:02","12-07-2024=
 19:12:51","12-07-2024 19:15:42","Grid outage, site went down before gen st=
art due to poor battery backup // grid return","Kemeni Franklin","Equipment=
 Repair","Passive","Control Panel","Power Cabinet - Battery Low","Grid outa=
ge, site went down before gen start due to poor battery backup // grid retu=
rn","emmanuel.ghani@ihstowers.com","4692","12-07-2024 20:31:02","Sagemcom C=
MR"
"Closed Complete","Site Down","CTR_020","IHS_YND_137","NOCINC0002602422","M=
asque","","12-07-2024 20:08:37","12-07-2024 19:59:23","12-07-2024 20:20:56"=
,"Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V , The TX =
FME  Eloundou // 693212405// From  Huawei is informed.","Fabrice Pouakam","=
Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fau=
lt Alarm","Active//No power issue on site.Site on Grid with Ubaie=3D54.3 V =
, The TX FME  Eloundou // 693212405// From  Huawei is informed.","emmanuel.=
ghani@ihstowers.com","555","12-07-2024 20:08:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_097","IHS_YND_350","NOCINC0002602243","M=
ambine","","12-07-2024 19:40:43","11-07-2024 07:12:57","11-07-2024 07:28:42=
","Grid outage , site went down because Gen ran still fuel shortage// Refue=
ling done","Fanda Brice","Fuel Outage","Passive","Diesel","Diesel Outage","=
Grid outage , site went down because Gen ran still fuel shortage// Refuelin=
g done","emmanuel.ghani@ihstowers.com","131267","12-07-2024 19:40:43","Sage=
mcom CMR"
"Closed Complete","Site Down","CTR_356","IHS_YND_376","NOCINC0002602094","M=
amb","","12-07-2024 19:15:55","12-07-2024 19:12:51","12-07-2024 19:15:42","=
Grid outage, site went down before gen start due to poor battery backup // =
grid return","Kemeni Franklin","Cascade Outage","Passive","Cascade Passive"=
,"Cascade Passive","Grid outage, site went down before gen start due to poo=
r battery backup // grid return","emmanuel.ghani@ihstowers.com","4789","12-=
07-2024 19:15:55","Sagemcom CMR"
"Closed Complete","Site Down","CTR_543","IHS_YND_155","NOCINC0002601365","O=
bobogo","","12-07-2024 17:06:57","12-07-2024 16:59:49","12-07-2024 17:15:17=
","Active: no power issue, site is on grid with Ubaie=3D54V, site up at 17:=
09, Hosiah(6674007438) from Huawei is informed","MINKA NICOLAS","Customer E=
quipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm",=
"Active: no power issue, site is on grid with Ubaie=3D54V, site up at 17:09=
, Hosiah(6674007438) from Huawei is informed","emmanuel.ghani@ihstowers.com=
","429","12-07-2024 17:06:57","Sagemcom CMR"
"Closed Complete","Site Down","CTR_155","IHS_YND_505","NOCINC0002601291","S=
calom-IHS","","12-07-2024 16:51:08","12-07-2024 16:43:02","12-07-2024 17:20=
:53","Active: no power issue, site is on grid with Ubaie=3D53V, MBO'OSSI(69=
7417716) from ZTE working on site ","","Customer Equipment Failure","Active=
","Active Equipment Failure","BTS/TX Fault Alarm","Active: no power issue, =
site is on grid with Ubaie=3D53V, MBO'OSSI(697417716) from ZTE working on s=
ite ","emmanuel.ghani@ihstowers.com","488","12-07-2024 16:51:08","Sagemcom =
CMR"
"Closed Complete","Site Down","CTR_321","IHS_YND_085","NOCINC0002601213","B=
riqueterie","","12-07-2024 16:30:26","12-07-2024 16:18:21","12-07-2024 17:2=
0:57","site went down due to increase load//he made a second start","","Equ=
ipment Replacement","Passive","Planned Activity","Planned Activity - Passiv=
e","site went down due to increase load//he made a second start","emmanuel.=
ghani@ihstowers.com","726","12-07-2024 16:30:26","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0002600774","EBOM",""=
,"12-07-2024 14:53:00","12-07-2024 14:46:05","12-07-2024 14:57:38","Cascade=
d Incident from TTO2403166","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","Active: no power issue, site is on grid with=
 Ubaie=3D53V, site impacted bay Messamendongo(Not managed by sagemcom), Lio=
nel Tchatchoua(694693436) from Huawei is informed","system","415","12-07-20=
24 14:53:00","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0002600769","A=
hala","IHS_YND_527, IHS_YND_698, IHS_YND_291","12-07-2024 14:52:06","12-07-=
2024 14:46:05","12-07-2024 15:57:38","Active: no power issue, site is on gr=
id with Ubaie=3D53V, site impacted bay Messamendongo(Not managed by sagemco=
m), Lionel Tchatchoua(694693436) from Huawei is informed","Hyemafo Gildas",=
"Customer Equipment Failure","Active","Active Equipment Failure","BTS/TX Fa=
ult Alarm","Active: no power issue, site is on grid with Ubaie=3D53V, site =
impacted bay Messamendongo(Not managed by sagemcom), Lionel Tchatchoua(6946=
93436) from Huawei is informed","emmanuel.ghani@ihstowers.com","361","12-07=
-2024 14:52:06","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002600654","O=
dza II OCM","","12-07-2024 14:29:41","12-07-2024 14:46:05","12-07-2024 21:4=
5:38","","Albran Byorel","Cascade Outage","Active","Cascade Active","Cascad=
e Active","Active: no power issue, site is on grid with Ubaie=3D53V, site i=
mpacted bay Messamendongo(Not managed by sagemcom), Lionel Tchatchoua(69469=
3436) from Huawei is informed","emmanuel.ghani@ihstowers.com","2356","12-07=
-2024 14:29:41","Sagemcom CMR"
"Closed Complete","Site Down","CTR_465","IHS_YND_291","NOCINC0002600647","E=
koumdoum OCM","","12-07-2024 14:28:52","12-07-2024 14:46:05","12-07-2024 14=
:57:38","","Albran Byorel","Cascade Outage","Active","Cascade Active","Casc=
ade Active","Active: no power issue, site is on grid with Ubaie=3D53V, site=
 impacted bay Messamendongo(Not managed by sagemcom), Lionel Tchatchoua(694=
693436) from Huawei is informed","emmanuel.ghani@ihstowers.com","2335","12-=
07-2024 14:28:52","Sagemcom CMR"
"Closed Complete","Site Down","CTR_167","IHS_YND_444","NOCINC0002600626","D=
ong","","12-07-2024 14:22:53","12-07-2024 14:21:03","12-07-2024 15:58:53","=
Active: no power issue, site is on gen with Ubaie=3D50V, site up at 14:22, =
Gregoire(654547479) from Huawei is informed","Parker Tchoup","Customer Equi=
pment Failure","Active","Active Equipment Failure","BTS/TX Fault Alarm","Ac=
tive: no power issue, site is on gen with Ubaie=3D50V, site up at 14:22, Gr=
egoire(654547479) from Huawei is informed","emmanuel.ghani@ihstowers.com","=
111","12-07-2024 14:22:53","Sagemcom CMR"
"Closed Complete","Site Down","CTR_158","IHS_YND_527","NOCINC0002600479","O=
dza II OCM","","12-07-2024 13:53:54","12-07-2024 13:48:47","12-07-2024 13:5=
5:36","Active//No power issue on site ;site on Grid with Ubaie =3D54,7 V Th=
e  Team Enerst //659843334  from ZTE is working on site","Albran Byorel","C=
ustomer Equipment Failure","Active","Active Equipment Failure","BTS/TX Faul=
t Alarm","Active//No power issue on site ;site on Grid with Ubaie =3D54,7 V=
 The  Team Enerst //659843334  from ZTE is working on site","ange.kongo@ihs=
towers.com","308","12-07-2024 13:53:54","Sagemcom CMR"
"Closed Complete","Site Down","","IHS_YND_698","NOCINC0002600317","EBOM",""=
,"12-07-2024 13:22:20","12-07-2024 13:09:38","12-07-2024 13:50:19","Cascade=
d Incident from TTO2402664","Hyemafo Gildas","Cascade Outage","Active","Cas=
cade Active","Cascade Active","ACTIVE No power issue on site U=3D54.3V on G=
rid RM Alain/691144423 from huawei is informed","system","762","12-07-2024 =
13:22:20","Sagemcom CMR"
"Closed Complete","Site Down","CTR_164","IHS_YND_257","NOCINC0002600310","A=
hala","IHS_YND_698","12-07-2024 13:20:44","12-07-2024 13:09:38","12-07-2024=
 14:24:22","ACTIVE No power issue on site U=3D54.3V on Grid RM Alain/691144=
423 from huawei is informed","Hyemafo Gildas","Customer Equipment Failure",=
"Active","Active Equipment Failure","BTS/TX Fault Alarm","ACTIVE No power i=
ssue on site U=3D54.3V on Grid RM Alain/691144423 from huawei is informed",=
"ange.kongo@ihstowers.com","667","12-07-2024 13:20:44","Sagemcom CMR"
"Closed Complete","Site Down","T0543","IHS_YND_135","NOCINC0002600135","Nlo=
ngkak","","12-07-2024 12:41:08","12-07-2024 12:35:02","12-07-2024 13:37:47"=
,"grid outage,gen failed to start due to Card Ge faulty//Gen started manual=
ly","Delor Telezing","Equipment Repair","Passive","ACDG Gen","ACDG - Contro=
l Panel","grid outage,gen failed to start due to Card Ge faulty//Gen starte=
d manually","ludivine.ngamaleu@ihstowers.com","366","12-07-2024 12:41:08","=
Sagemcom CMR"
"Closed Complete","Site Down","CTR_070","IHS_YND_104","NOCINC0002600103","C=
arington","","12-07-2024 12:31:07","12-07-2024 12:27:58","12-07-2024 13:29:=
50","grid outage//grid return","","Grid Supply","Passive","Grid","National =
Grid - Grid Outage Issue","grid outage//grid return","ange.kongo@ihstowers.=
com","192","12-07-2024 12:31:07","Sagemcom CMR"
"Closed Complete","Site Down","T0274","IHS_YND_091","NOCINC0002599995","Jou=
vence 2000","","12-07-2024 12:17:46","12-07-2024 12:15:40","12-07-2024 12:3=
4:43","Grid outage, site went down before gen start due to poor battery bac=
kup // Gen start automaticaly","Delor Telezing","Equipment Repair","Passive=
","Control Panel","Power Cabinet - Battery Low","Grid outage, site went dow=
n before gen start due to poor battery backup // Gen start automaticaly","l=
udivine.ngamaleu@ihstowers.com","127","12-07-2024 12:17:46","Sagemcom CMR"
"Closed Complete","Site Down","CTR_526","IHS_YND_696","NOCINC0002599808","B=
arriere IHS","","12-07-2024 11:26:10","12-07-2024 11:19:03","12-07-2024 11:=
50:04","site went down due to grid fluctuation and gen failed to start //Gr=
id stabilized","Hyemafo Gildas","Grid Supply","Passive","Grid","National Gr=
id - Phase Controller Faulty","site went down due to grid fluctuation and g=
en failed to start //Grid stabilized","ange.kongo@ihstowers.com","3743","12=
-07-2024 11:26:10","Sagemcom CMR"
"Closed Complete","Site Down","CTR_271","IHS_YND_275","NOCINC0002599801","N=
kolbong","","12-07-2024 11:24:37","12-07-2024 11:18:31","12-07-2024 12:51:3=
8","Site went down because CB  OCM (100A)  disjunted at  DC BOX Causing by =
heating cable power // he cut  the part burnt   and reamed CB","Delor Telez=
ing","Equipment Repair","Passive","Control Panel","Power Cabinet - Circuit =
Breaker Issue","Site went down because CB  OCM (100A)  disjunted at  DC BOX=
 Causing by heating cable power // he cut  the part burnt   and reamed CB
","ange.kongo@ihstowers.com","368","12-07-2024 11:24:37","Sagemcom CMR"
"Closed Complete","Site Down","CTR_330","IHS_YND_255","NOCINC0002599166","O=
dza-PK10","","12-07-2024 09:25:29","12-07-2024 09:15:20","12-07-2024 10:54:=
18","Active//No power issue on site Ubaie=3D54,6 V Site on Grid,The  Team G=
r=E9goire//697562079 from ZTE  is wooking on site","Albran Byorel","Custome=
r Equipment Failure","Active","Active Equipment Failure","BTS/TX Fault Alar=
m","Active//No power issue on site Ubaie=3D54,6 V Site on Grid,The  Team Gr=
=E9goire//697562079 from ZTE  is wooking on site","ange.kongo@ihstowers.com=
","610","12-07-2024 09:25:29","Sagemcom CMR"
"Closed Complete","Site Down","T1544","IHS_YND_149","NOCINC0002599022","Nsi=
meyong Terre Rouge","","12-07-2024 08:46:34","12-07-2024 08:41:30","12-07-2=
024 09:25:25","grid outage,gen failed to start due to section power cable s=
hort circuit of DG //he replaced it,reset card DG and started it","MINKA NI=
COLAS","Equipment Repair","Passive","Infrastructure","Armoured Cable","grid=
 outage,gen failed to start due to section power cable short circuit of DG =
//he replaced it,reset card DG and started it","ludivine.ngamaleu@ihstowers=
.com","305","12-07-2024 08:46:34","Sagemcom CMR"
"Closed Complete","Site Down","T0563","IHS_YND_332","NOCINC0002599020","NKO=
MEKUI OCM","","12-07-2024 08:44:57","12-07-2024 08:38:53","12-07-2024 08:46=
:48","Grid outage, site went down before gen start due to poor battery back=
up // Gen start automaticaly","TIENTCHEU NZETCHIEU GAEL","Equipment Repair"=
,"Passive","Control Panel","Power Cabinet - Battery Low","Grid outage, site=
 went down before gen start due to poor battery backup // Gen start automat=
icaly","ludivine.ngamaleu@ihstowers.com","365","12-07-2024 08:44:57","Sagem=
com CMR"
"Closed Complete","Warning","T1544","IHS_YND_149","NOCINC0002598774","Nsime=
yong Terre Rouge","","12-07-2024 08:00:14","","","grid outage,gen failed to=
 start due to section power cable short circuit of DG //he replaced it,rese=
t card DG and started it","MINKA NICOLAS","Warning","Warning","POWER","Warn=
ing - Site on Battery","grid outage,gen failed to start due to section powe=
r cable short circuit of DG //he replaced it,reset card DG and started it",=
"alwine.fambou@ihstowers.com","4","12-07-2024 08:00:14","Sagemcom CMR"
"Closed Complete","Site Down","CTR_383","IHS_YND_300","NOCINC0002598486","O=
lembe-Terminus","","12-07-2024 06:55:21","12-07-2024 06:51:14","12-07-2024 =
08:30:39","Grid outage  site went down because Gen started and stopped With=
 alarm low oil pressure// He added oil and Gen manually started","Fabrice P=
ouakam","Equipment Repair","Passive","ACDG Gen","ACDG - Low Oil Pressure","=
Grid outage  site went down because Gen started and stopped With alarm low =
oil pressure// He added oil and Gen manually started","ange.kongo@ihstowers=
.com","248","12-07-2024 06:55:21","Sagemcom CMR"

------=_Part_41_1366212289.1757654151520--